1 | Application Note | Public Address | PAVIRO Factory Default System
Bosch Security Systems | Public Address
B
hS
it S t
| P bli Add

Application Note
PAVIRO Factory Default System - v1.0

PAVIRO Factory Default System
This application note describes the functions, installation and operation of this system.

Component list:
A basic system consists of:
 1x PVA-4CR12 Controller
 1x PVA-2P500 Amplifier
 1x PVA-15CST Call Station
 1x 24V/2A Power supply
System features:
 12 loudspeaker zones via 2 router clusters
 For each router cluster (zone 1-6 and zone 7-12) 500W loudspeaker load can be
connected
 Selective announcement to each of the 12 loudspeaker zones via the call station
 A background music (program) source can be selectively activated by the call station
into each loudspeaker zone (option)
 Maximum two audio signals can be activated simultaneously, but only one signal per
router cluster
 The English EVAC-message "incident" can be triggered by a contact (option)
 A logical output is provided to mute external systems when an announcement or
EVAC-message is active (option)

2 | Application Note | Public Address | PAVIRO Factory Default System

Block Diagram:

System Behavior:
The system has to be operated with the call station PVA-15CST, only the evacuation is
triggered by an external normal open contact.
The operation of the call station is explained in the following figure:

3 | Application Note | Public Address | PAVIRO Factory Default System

System installation:

Zone 1
Zone 2

Program source

Zone 3

Mute contact
24V/200mA

Zone 4

EVAC start/stop
Zone 5
termination

Zone 6

24V DC
INPUT

Zone 7
Zone 8
Zone 9
Zone 10

termination

Mains
power

Zone 11
Zone 12






o

Create the cabling as shown in the wiring diagram. Take in account the requirements in
the operation manuals PVA-4CR12 and PVA-2P500 in the chapter "Connections".
NOTE: Unused loudspeaker outputs do not have to be wired.
The CAN-BUS has to be terminated with the enclosed terminating resistors.
NOTE: It is not allowed to terminate the audio Line 1-4.
The connections drawn in dashed lines are optional and have to be wired only when the
respective function is used.
After finishing the cabling, the CAN address has to be set to "01" on the PVA-2P500
amplifier.
NOTE: Before the address is set, make sure the PVA-2P500 is disconnected from the
mains.

Now the system can be connected to the power supply and activated.

4 | Application Note | Public Address | PAVIRO Factory Default System

o

The address of the call station PVA-15CST must be set to "01".
This is done via the menu of the call station:
o
o
o
o
o
o
o
o
o

o

To open the main menu, press the ▲ Button keep it held down and press the
▼button at the same time.
Press the ▼ button until you reach the "CST Setup" menu item.
After pressing the ↵ button, the "Input Password" dialog is showing.
Press the button "2" (on the right side) four times and then the ↵ button.
Press the ▼ Button, to navigate to the "CST Setup Menu" menu item and then
the ↵ button.
The display shows “CAN Address”.
Press the ↵ button.
Change the address with the ▲ button from “0” to “1” and press then the ↵
button.
Press twice the ESC button to exit the menu.

The date and clock settings are done via the PVA-15CST call station menu
o
o
o
o

To open the main menu, press the ▲ Button keep it held down and press the
▼button at the same time.
Press the ▼ button until you reach the "Date / Time" menu item.
After pressing the ↵ -button, the current date and time can be entered by using
the numeric keys 0-9.
Press the ↵ button after the input and then the ESC button.

o

The date / time display can also be switched off, by the menu of the call station PVA15CST.
o To open the main menu, press the ▲ Button keep it held down and press the
▼button at the same time.
o Press the ▼ button until you reach the "CST Setup" menu item.
o After pressing the ↵ button, the "Input Password" dialog is showing.
o Press the button "2" (on the right side) four times and then the ↵ button.
o Press the ▼ Button, to navigate to the "CST Setup Menu" menu item and then
the ↵ button.
o Press the ▼ button until you reach the "Show Date & Time" menu item.
o Press the ↵ button.
o Change the value with the ▲ button from “on” to “off” and press the ↵ button.
o Press twice the ESC button to exit the menu.



The system is ready for operation if all steps above are successful performed.

5 | Application Note | Public Address | PAVIRO Factory Default System

Fault description and their elimination:
The following table gives an overview of faults that may occur and how they can be
eliminated.
Explanation of the table
 CST TEXT =
The error text that is displayed in the PVA-15CST call station
 DESCRIPTION = Description of this error type
 ACTION =
Actions to eliminate the fault
CST TEXT

DESCRIPTION

ACTION

Contr. Data Fault

Memory or Read/Write error.

Controller defect, must be repaired by ASA.

Watchdog Fault

Watchdog error of the device. The system has
rebooted.

Press the "System Fault" button on the call
station to reset the error.

Contr. SW Fault

The device firmware version is not compatible
with the IRIS-Net version used.

A firmware update of the Controller is necessary.

Contr. HW Fault

Error in the power supply or the A/D converters
of the device.

Controller defect, must be repaired by ASA.

Temperature Fault

Temperature overload of the device.

The internal temperature of the controller is too
high. Ensure sufficient cooling.

DSP System Fault

Error during the processing of audio data.

Controller defect, must be repaired by ASA.

Message Fault

Collected Error of the message manager.

Further details are provided in the message
manager dialog (ERROR STATES).

CAN Bus Fault

Fault condition on the CAN bus (Amplifier and
Router communication).

Further details are provided in the Interface
dialog (CAN INTERFACE).

CST Bus Fault #%u

Fault condition on the CST bus (call station
communication). The parameter %u gives the
slot number of the erroneous module.

Check cable connections between the call
station and call station port.

Int.Router DSP Fault

Error in the digital signal processing (DSP) of the
Controller defect, must be repaired by ASA
device.

Int.Router HW Fault

Hardware error.

Controller defect, must be repaired by ASA

Int.Router TMP Fault

Temperature overload of the device.

The internal temperature of the controller is too
high. Ensure sufficient cooling.

Int.Router PLT Fault

Missing pilot tone at input 1 of cluster A.

Check cable connections between amplifier
output and AMP-IN 1 cluster A.

Int.Router PLT Fault

Missing pilot tone at input 1 of cluster B.

Check cable connections between amplifier
output and AMP-IN 1 cluster B.

CST Fault #%u

A connected PVA-15CST call station has
transferred an error message. The parameter
%u gives the address of the erroneous call
station.

Further details are provided in the PVACST
dialog (Supervision).

Amplifier Fault #%u

A connected PVA-2P500 power amplifier has
transferred an error message. The parameter
%u gives the address of the erroneous amplifier.

Further details are provided in the PVAAMP
dialog (Supervision).



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.7
Linearized                      : No
Author                          : rac2sab
Create Date                     : 2017:05:05 10:15:18+02:00
Modify Date                     : 2017:06:21 15:00:05+02:00
XMP Toolkit                     : Adobe XMP Core 5.6-c015 84.159810, 2016/09/10-02:41:30
Format                          : application/pdf
Title                           : Microsoft Word - AN PAVIRO Factory Default System v1_1.docx
Creator                         : rac2sab
Creator Tool                    : PScript5.dll Version 5.2.2
Metadata Date                   : 2017:06:21 15:00:05+02:00
Producer                        : Acrobat Distiller 15.0 (Windows)
Document ID                     : uuid:62ebfe6c-e25b-4059-8415-8766a0dc80c3
Instance ID                     : uuid:825ccc27-38f5-449b-935e-087c36454a3e
Page Count                      : 5
EXIF Metadata provided by EXIF.tools

Navigation menu