PRODUCT INFORMATION

PI-34.51

GLT - Non-Automatic Fire Detector Series 120
FMC-120-DKM-G-R / FMC-120-DKM-H-R
FMC-120-DKM-G-B / FMC-120-DKM-H-B /
FMC-120-DKM-G-Y
FMC-120-EST-G-B

Page 1

BDL-F.01U.066.178
A3.en / 14.03.2008
ST-FIR/ PRM1 / sib

Page 2 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

Table of contents
1.
2.
3.

Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planning notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
3
4

3.1. Maximum number of detectors that may be connected . . . . . .

4

3.2. Norms, guidelines and planning recommendations . . . . . . . . . .

4

3.3. Labelling variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

4.

Order contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

4.1. Basic model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

4.2. Labelling foils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

4.3. Accessories / Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

5.
6.

Device structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7
8

6.1. Manual call point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

6.2. Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

6.3. Test detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

7.

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

7.1. Installation dimensions (view: housing rear wall interior) . . . .

9

7.2. Cable duct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

7.3. Installation variants for fire hose cabinets . . . . . . . . . . . . . . . . . .

10

7.4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

8.

Notes on maintenance and service . . . . . . . . . . . . . . . . .

12

8.1. Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

8.2. Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

8.3. Additional documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

9. Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .
10. Table of abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13
14
15

Page 3 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

1. Product description
The series 120 non-automatic fire detector is used for manual alarm triggering in conventional
line technology (GLT). The line is monitored according to the principle of voltage reduction and
increase.
The Form H detectors are designed for exterior areas, the Form G detectors for interior areas.
Overview of non-automatic fire detectors, series 120
Manual call points
D FMC-120-DKM-G-R Manual call point for interior areas (Form G), red
D FMC-120-DKM-H-R Manual call point for exterior areas (Form H), red
Manual call points
D FMC-120-DKM-G-B Manual call point for interior areas (Form G), blue
D FMC-120-DKM-H-B Manual call point for exterior areas (Form H), blue
D FMC-120-DKM-G-Y Manual call point for interior areas (Form G), yellow
Stop device
D FMC-120-EST-G-B

Stop device for interior areas (Form G), blue

2. Features
D Manual call point and stop device: Trigger alarm by pushing the button. After alarm
triggering, the push button is adjusted.
D Detector query routines with evaluation and multiple transmission.
D Display (LED) for triggered alarms or inspection evaluation.
D Second contact with connections for panel control.
D Same design for interior use (Form G) and exterior use (Form H).
D Available in different colour variants; see order overview.
D For the red colour variants, a “burning house” is applied to the detector housing in the
factory.
D Variable labelling is possible with foil sets for the blue and yellow colour variants.
D For exterior use in extreme environmental conditions, the detector is equipped with an
especially resistant PC board (parylene layering) and with a seal in the detector door.

Page 4 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

3. Planning notes
D Non-automatic fire detectors must be mounted visibly along escape and rescue routes
(e.g. exits, passageways, stairwells) and be easily accessible.
D An installation height of 1400 mm (±200 mm), measured from the middle of the push
button to the floor, must be maintained.
D Non-automatic fire detectors must be sufficiently lit with sunlight or another light source
(including emergency lighting if present).
D The distance between non-automatic fire detectors should not exceed 100 m according
to DIN 14 675 or 80 m according to VdS.
D In high risk areas, non-automatic fire detectors should be installed at intervals of max. 40 m
(VDE 0833 Part 2, Point 7.2.6).

3.1. Maximum number of detectors that may be connected
In accordance with VdS guidelines, a maximum of 10 non-automatic fire detectors may be
connected to a primary line.
The test detector can be used for primary lines with automatic fire detectors. It is connected to the electrical end of the primary line (max. 1 test detector per primary line).

3.2. Norms, guidelines and planning recommendations
Additional norms, guidelines, and planning recommendations with respect to installation location etc. must be taken into account (see fire detector manual).
The regulations of the local fire services must be observed.
Fire detector
10

3

2

1

BMZ
Last detector

Intermediate
detector

Intermediate
detector

Page 5 of 18

Intermediate
detector

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

3.3. Labelling variants
The detectors can be individually adapted to the location/application with optional labelling variants. This excludes detector variants FMC-120-DKM-G-R and
FMC-120-DKM-H-R, to which the “burning house” symbol has already been applied.
The self-adhesive labelling foils are stuck on the front panel of the detector.

Page 6 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

4. Order contents
4.1. Basic model
Product ID

DU*

Designation

F01U011951

Pc

FMC-120-DKM-G-R,
Manual call point for interior areas (Form G), red

F01U011952

Pc

FMC-120-DKM-H-R,
Manual call point for exterior areas (Form H), red

F01U011953

Pc

FMC-120-DKM-G-B,
Manual call point for interior areas (Form G), blue

F01U011954

Pc

FMC-120-DKM-H-B,
Manual call point for exterior areas (Form H), blue

F01U011955

Pc

FMC-120-DKM-G-Y,
Manual call point for interior areas (Form G), yellow

F01U012763

Pc

FMC-120-EST-G-B,
Stop device for interior areas (Form G), blue

4.2. Labelling foils
Product ID

DU*

Designation

F.01U.012.951

PAK FMC-FST-DE,
Pre-cut and labelled foil sets for the top labelling field
(1 PACK = 5 sheets with 12 labelling variants)

F.01U.033.170

PAK FMX-FSO-GLT,
Pre-cut foil sets for the top labelling field (1 PAK = 10
sheets with 6 labelling variants). Appropriate for
printing at standard laser printers. The required print
file is available on the WinPara disk.

4.3. Accessories / Spare parts
Product ID

DU*

3.790.170.005

Pc

“Out of order” - Metal stop sign

3.756.630.007

Pc

Red plastic key (ASA) for detector door

F.01U.025.845

Designation

PAK FMC-SPGL-DEIL,
Replacement glass pane, dimensions 80 x 80 x 0.9 mm
(1 PACK = 5 pieces)

Page 7 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

5. Device structure
The non-automatic fire detector is available in several variants and essentially consists of the
following elements.
1

2

4

3

9

8

7

6
2

5

Pos. Designation
1

Plastic housing

2

Cable ducts (interchangeable), for cable inlet and outlet. The cable
can also be ducted through openings in the rear wall of the housing.

3

Connection terminal strip

4

Detector door with replaceable glass pane, hidden lock
(and seal, for Form H)

5

Glass pane

6

Display (LED)

7

PC board (with protective coating for Form H) The PC board is
clipped onto the floor of the housing.

8

Trigger mechanism (clipped onto the PC board), consisting of plastic
frame and push button with spring.

9

Reset lever (locking mechanism only for manual call points)

Page 8 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

6. Functional description
6.1. Manual call point
Manual call point and stop device: In the event of an alarm, the glass pane (2) is broken
first, then the manual call point (3) is pressed hard.
This activates the microswitch for alarm triggering and the display LED (4) flashes.
A locking mechanism holds the pressed push button down.
The pressed push button is reset by manually activating the reset lever (5) or by opening
the detector door (1) ⇒ The alarm is reset and the display LED goes out (4).
1

5

1
2

4

3
3

2

6.2. Functional test
Manual call point and stop device: To trigger the alarm, press the manual call point (3)
hard. The display LED (4) flashes. Use the reset lever (5) to return the manual call point to
the starting status.

6.3. Test detector
A maximum of 1 test detector (1) may be connected to the electrical end of the primary
line. Up to 30 automatic fire detectors may be connected to the primary line to be tested.
The test detector is supplied by the fire panel.
1

max. 30

3

Page 9 of 18

2

1

BMZ

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

7. Installation
d The non-automatic fire detector is designed for wall mounting.
d The installation height, according to VdS regulations, is 1400 mm
(± 200 mm) from the floor to the centre of the push button.
d The connection cables can be surface or flush-mounted.
The cable ducting should be carried out using the intended openings in
the housing (see 7.2 Cable duct).
d The installation location is to be selected so that approximately 35 mm
space remains free on the right-hand side for opening the door.

7.1. Installation dimensions (view: housing rear wall interior)
135 mm

135 mm

37 mm

17 mm

13 mm

60 mm

approx. 35 mm

7.2. Cable duct
Surface-mounted cable duct

Flush-mounted cable duct
via concealed box

Page 10 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

7.3. Installation variants for fire hose cabinets
1

135

2.5 mm

2

140

10

2

3

139

147

Pos.

Description

1

Installation depth version 1: min. 36 mm

2

Installation depth version 2: 14 mm

3

Installation depth version 3: approx. 30 mm
With this version, it is not necessary to open the door of the hose box e.g. for
maintenance.

Page 11 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

7.4. Connection
Detailed wiring diagrams and bridge assignments for connection to different fire panels are
shown in the wiring diagram manual.

+-

+
-

E

a b a’ b’ E

R5

R2
C

G

1 2 3 4 5 6 7 8 9 10

K

D

H

R3

R4

F

J

R6
A

R1

B

R1 (A/B) = 820 Ω
R4 (E/F) = 150 Ω
R6 (A/B) = 2k21

R3 (G/H)= 0 Ω
R5 (J/K) = 0 Ω
Endmelder / Last detector / Laatste melder:
R2 (C/D)= RE=3k92

In order to reach an alarm resistance of 820 Ohm in current gain operation,
resistor R6 must be removed. For other operating modes (voltage reduction), see the wiring diagram manual for the corresponding fire panel.

b’ 4

2 b
B

8

S2

R1

9
10

A

6
S1

To the next detector

E

C
R2
(RE)
D

From the control panel

G

E
R4

5

R3

F

H

(E)

7

a’ 3

1 a
K

Page 12 of 18

R5

J

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

T.2
T.1
a b a’ b’ E

R5
0W

R4
150W
R3
0W

1 2 3 4 5 6 7 8 9 10

2k21 W

R6

820W

R1

T.3

Do not remove the end of line resistor from the last detector!
It must be removed from all other detectors.

8. Notes on maintenance and service
For maintenance and inspection work on security systems, the regulations of DIN VDE 0833
apply in Germany; these regulations refer to the maintenance intervals as per the manufacturer’s instructions.
D Bosch ST recommends a functional and visual inspection at least once a year.
D Maintenance and inspection work should be carried out regularly and by trained personnel.

8.1. Repair
In the event of a defect, the entire unit is exchanged.

8.2. Disposal
Unusable units should be disposed of in accordance with regulations.

8.3. Additional documentation
For those with the appropriate access authorisation,
see Bosch ST ExtraNet at
www.boschbest.de
for the updated product information and the installation manual as a downloadable PDF file.

Page 13 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

9. Technical specifications
Technical specifications
Operating voltage

24 V DC (16.2 V DC to 30 V DC)

Current consumption

specified by the respective security system

Protection category as per EN 60529
- Form H (exterior)
- Form G (interior)

IP 54
IP 52

Permissible ambient temperature
- Form H (exterior)
- Form G (interior)

-25_C to +70_C / -13_F to 158_F
-10_C to +55_C / 14_F to 131_F

Standard (except FMC-120-DKM-G-Y)

EN 54-11

Standard for FMC-120-DKM-G-Y

EN 12094-3

Colours
RAL 5005 signal blue
RAL 1003 signal yellow
RAL 3001 signal red

Housing material

Plastic, ASA (Acrylonitrile-Styrene-Acrylate Terpolymer)

Dimensions (W x H x D)

135 x 135 x 37 mm / 5.31 x 5.31 x 1.38 inches

Weight

224 g

Page 14 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

10. Table of abbreviations
AHB

= Wiring diagram manual

BMZ

= Fire panel

BM

= Fire detector

DIN

= German Institute for Standardisation

DKM

= Manual call point

EMZ

= Intrusion control panel

EN

= European standard

GMZ

= Danger detection system

KI

= Customer service information

LED

= Light Emitting Diode

LSN

= Local Security Network

SM

= Single action call point

UGM

= Universal danger detection system

VDE

= Association of German Electrical Engineers

VdS

= VdS Schadenverhütung GmbH

Page 15 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Produktinformation FMC-120-DKM / EST GLT

PI - 34.51 en

11. Notes
------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

------------------------------------------------------------------

Page 16 of 18

BDL-F.01U.066.178
A3.en/ 14.03.2008
ST-FIR/ PRM1 / sib

Bosch Sicherheitssysteme GmbH
Robert-Koch-Straße 100
D-85521 Ottobrunn, Germany

www.bosch-sicherheitssysteme.de
info.service@de.bosch.com

Page 18 of 18



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0 (Windows)
Create Date                     : 2008:03:14 15:15:25+01:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2008:03:14 15:15:25+01:00
Format                          : application/pdf
Creator                         : sib5ot
Title                           : T-PI GLT(A4.de)