Boschhome Bosch Appliances Home Security System Ds7400Xi Users Manual F01U035325 01 (4+) Ref. Guide.PMD

en-us DS7400Xi_Version_4__Quick_Selection_Guide_enUS_2511502475 DS7400Xi Series Addressable Control Panels

DS7447E to the manual e70862ae-1167-4f47-9568-77a6b5c80283

2015-01-21

: Boschhome Boschhome-Bosch-Appliances-Home-Security-System-Ds7400Xi-Users-Manual-239114 boschhome-bosch-appliances-home-security-system-ds7400xi-users-manual-239114 boschhome pdf

Open the PDF directly: View PDF PDF.
Page Count: 100

DownloadBoschhome Boschhome-Bosch-Appliances-Home-Security-System-Ds7400Xi-Users-Manual- F01U035325-01 DS7400Xi (4+) Ref. Guide.PMD  Boschhome-bosch-appliances-home-security-system-ds7400xi-users-manual
Open PDF In BrowserView PDF
Reference Guide
for the DS7400Xi (Ver. 4+)
Control/Communicator
Armed

Perimeter

Status

Supervisory

Power

Bell Silenced

Fire

Trouble

Armed

1 2 3

4 5

6

7

Status

8

Power

9 10 11 12 13 14 15 16
TEST WEEKLY

Fire

TEST WEEKLY

On

On

1

2

3

Off

1

2

3

Off

4

5

6

Perimeter
Only

4

5

6

Perimeter
Only

7

8

9

No
Entry

7

8

9

No
Entry

*

0

#

Bypass

*

0

#

Bypass

System
Reset

System
Reset

DS7445/DS7445i

DS7447/DS7447E

Keypad Quick Reference Guide
Turning On (arming) your System using the DS7445/DS7445i
or DS7447/DS7447E Keypad
Normal Arming

[PIN] + [On]

Perimeter Arming, no entry delay

[PIN] + [No Entry] +
[Perimeter Only]

Perimeter Arming, with entry delay

[PIN] + [Perimeter Only]

Maximum Security Arming

[PIN] + [No Entry] + [On]

Custom Arming

[PIN] + [#] [4]

Set Delayed Arming

[PIN] + [#] [9] [9] and enter
number of hours from
current time to the desired
arming time.

Extend Automatic Arming
Force Arming

Zone Bypass

[PIN] + [OFF] during prearm time
Enter
an
arming
command followed by
[Bypass]
[PIN] + [Bypass] followed
by the Zone number.
[PIN] +[Bypass] [*] to clear
ALL Bypasses.

Commands for other System Features
Chime Mode

[PIN] + [#] [7]

System Walk Test

[PIN] + [#] [8] [1]

Read Event History

[PIN] + [#] [8] [9]

Battery Test

[PIN] + [System Reset]

Communicator Test

[PIN] + [#] [8] [2]

Fire Reset

[PIN] + [System Reset]

Remote Program Dial-out

[PIN] + [#][8] [3]

Remote Program Answer

[PIN] + [#] [8] [6]

Battery/Sounder Test

[PIN] + [#] [8] [5]

Error Display

[PIN] + [#] [8] [7]

Error Display Reset

[PIN] + [System Reset]

Fire Walk Test

[PIN] + [#] [9] [1]

To Silence a Fire Trouble/Alarm

[PIN] + [Off]

To Clear a Fire Trouble Display

[PIN] + [System Reset]

Access Control
Enter your [Access Control PIN] followed by [Off]

Turning Off (disarming) your System
Enter your [PIN] followed by [Off]
NOTE: For additional information on operating this system, consult the DS7400Xi (Ver. 4+) User’s Guide (P/N: 43851) and section 7
of this Reference Guide.

7.4

Table of Contents

Fire Safety ..................................................................... 27
7.4.1
7.4.2
7.4.3

Keypad Quick Reference Guide ........................................ 1
1.0

Specifications ............................................................. 4

1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13

Enclosure Housing ........................................................
Temperature ...................................................................
Power ..............................................................................
Outputs ...........................................................................
Zones ..............................................................................
Keypads ..........................................................................
Communicator ...............................................................
Partitions ........................................................................
Users ..............................................................................
Lightning Protection .......................................................
Burglar/Fire Zone Inputs ................................................
Fire Signal Initiating Circuit (2-wire mode) ...................
Multiplex Bus Wiring Requirements ..............................
1.13.1

1.14
1.15
1.16
1.17
1.18

2.0

4
4
4
4
4
4
4
4
4
4
4
4
4

Multiplex Zone Loop Wiring ................................ 4

Option Bus Wiring Requirements .................................
Max. Load Currents ........................................................
Backup Battery Calculation ............................................
Standby Current Load ....................................................
Options ...........................................................................

Install the Enclosure ...................................................... 8
Install the Control/Communicator ................................. 8

3.0

Control Terminal Wiring ......................................... 10

4.0

Hardware Layout Example ..................................... 11

5.0

System Worksheet ................................................... 12

6.0

Glossary ..................................................................... 19

6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
6.13
6.14
6.15
6.16
6.17
6.18
6.19

7.0

General Control Programming .................................... 19
Zone Function Programming ...................................... 19
Zone Programming ...................................................... 20
Output Programming ................................................... 21
Partition Control Programming ................................... 21
Keypad Assignment Programming ............................. 22
Emergency Key Programming .................................... 22
Custom Arming Programming .................................... 22
Force Arming ................................................................ 22
Ground Fault Detect Programming ............................. 22
Commercial Fire Mode Programming ........................ 22
Open/Close Report Control Programming ................ 23
Report Programming ................................................... 23
Phone Number General Control Programming ......... 24
Phone Answering Programming ................................. 24
FCC Compliance Notice .............................................. 25
FCC Phone Connection Notice To Users ................... 25
Canadian Dept. of Communications .......................... 25
For Installations in New Zealand ................................ 25

Operating Guide ...................................................... 26

7.1

Emergency Procedures ............................................... 26
7.1.1
7.1.2
7.1.3
7.1.4
7.1.5
7.1.6

7.2

Page 2

26
26
26
26
26
26

Fire Reset/Fire Trouble ................................................ 26
7.2.1
7.2.2
7.2.3

7.3

Identifying Alarm Sounds .................................
Silencing Alarms ..............................................
A Cautionary Note ............................................
Use Common Sense .........................................
Caution When Entering a Building .....................
Fire Alarms ......................................................

Fire Reset ........................................................ 26
Fire Trouble ..................................................... 26
Dirty Smoke ..................................................... 26

Emergency Keypad Alarms ......................................... 26
P/N: F01U035325-01

Personal Identification Numbers ................................ 28
7.5.1
7.5.2

7.6

General Information .......................................... 28
Programming PINs ............................................ 28

The Master Keypad ...................................................... 29
7.6.1
General Information ..........................................
7.6.2
Master Keypad Displays ..................................
7.6.3
Single Partition Mode ........................................
7.6.4
Arming from the Master Keypad .......................
7.6.5
Disarming from the Master Keypad ...................
To disarm all the Partitions to which you have access: ......

7.7

7.7.1
7.7.2
7.7.3

7.8

7.8.2
7.8.3
7.8.4

Zone (System Walk) Test .................................
31
Battery Tests ...................................................
31
Communicator Test ...........................................
Fire Walk Test ..................................................

31
31
31
31

How to Program the Control Panel ...................... 32

8.1
8.2
8.3
8.4
8.5
8.6
8.7

9.0

General Information .......................................... 30
System Faults .................................................. 30
Event History ................................................... 30

Testing Your System .................................................... 31
7.8.1

8.0

29
29
29
29
29
29

Keypad Error Displays ................................................. 30

4
5
5
5
6

Enclosure Installation ............................................... 8

2.1
2.2

7.5

If Installed in Family Residences ....................... 27
Having and Practicing an Escape Plan .............. 27
Installation Considerations ................................ 27

Entering the Programmer’s Mode ...............................
Reading Back a Program Address .............................
Entering a Value in a Program Address .....................
HEX values ...................................................................
Defaults ........................................................................
Setting the Control to the Factory Default ....................
Exiting the Programmer’s Mode ..................................

32
32
32
32
32
32
32

Understanding the Programming Charts ............ 33

10.0 Programming ............................................................ 34
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.10
10.11
10.12
10.13
10.14
10.15

General Control Programing:
Program Address (0000) ............................................. 34
Zone Function Programming: ..........................................
Program Addresses (0001-0030) ............................... 35
Zone Programming:
Program Addresses (0031-0278) ............................... 36
Zone Programming:
Zone Type Program Addresses (0415-0538) ............. 37
Zone Partition Assignment:
Program Addresses (0287-0410) ............................... 38
Zone Bypass Programming:
Program Addresses (2721-2724) ............................... 39
Output Programming:
Program Addresses (2734, 2735, 2736) .................... 41
Output Partition Assignment:
Program Addresses (2737-2738) ............................... 42
Partition Control Programming:
Program Address (3420) ............................................. 42
Quick Arm Control Programming:
Program Address (3477) ............................................. 43
Keypad Assignment Programming:
Program Addresses (3131-3138) ............................... 44
Keypad Partition Assignment:
Program Addresses (3139-3146) ............................... 44
Emergency Key Programming:
Program Addresses (3147-3148) ............................... 45
Custom Arming Programming:
Program Addresses (2725-2728) ............................... 45
Force Arming and Ground Fault Detect Programming:
Program Address (2732) ............................................. 47

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.16 Commercial Fire Mode Programming:
Program Address (2733) ............................................. 48
10.17 Open/Close Report Control Programming:
Program Address (3149) ............................................. 49
10.18 Open/Close & Zone Report Control Programming:
Program Address (3151) ............................................. 49
10.19 Report Control Programming:
Program Address (3152) ............................................. 49
10.20 Timer Programming:
Program Addresses (4028-4030, 4032-4033) .......... 50
10.21 AC Fail Report Delay Programming:
Program Address (4034) ............................................. 50
10.22 General Authority Programming:
Program Address (3421-3424) ................................... 51
10.23 Arming Warning Programming:
Program Addresses (3425-3428) ............................... 51
10.24 DS7412 RS232 Interface Control Programming:
Program Address (4019) ............................................. 52
10.25 DS7412 RS232 Interface Configuration Programming:
Program Address (4020) ............................................. 52
10.26 RS232 Carriage Return/Line Feed Control:
Program Address (4027) ............................................. 52
10.27 Report Programming:
Program Addresses (3207-3419) ............................... 53
10.28 Phone/DS7416i Routing Control:
Program Addresses (3153-3154) ............................... 55
10.29 Account Code Programming:
Program Addresses (3429-3459) ............................... 56
10.30 Phone Number General Control Programming:
Program Address (3155) ............................................. 57
10.31 Phone Number Format Programming:
Program Addresses (3156-3157) ............................... 57
10.31.1

Compatible Receivers ...................................... 58

10.32 Phone Answering Programming:
Program Address (3158) ............................................. 58
10.33 Pager Delay Time:
Program Address (4038) ............................................. 59
10.34 Programmer’s and Master Code Programming:
Program Addresses (7589-7592) ............................... 59
10.35 PIN Length Programming:
Program Address (3478) ............................................. 59
10.36 Octal Relay Module Output Programming .................. 60
10.36.1
10.36.2
10.36.3
10.36.4
10.36.5

Follow Action:
Program Addresses (2740-2771) ..................... 60
Follow System Wide Event:
Program Addresses (2740-2771) ..................... 61
Follow Function:
Program Addresses (2740-2771) ..................... 62
Follow Zone:
Program Addresses (2740-2771) ..................... 63
Octal Relay Module Output Partition Assignment:
Program Addresses (2844-2851) ..................... 65

Program Addresses (0545-2720, 5001-6920) .......... 69
10.41.1

Alpha Description Programming:
A Worksheet ................................................... 70

10.42 Phone Number Programming:
Program Addresses (3159, 3175, 3191) .................... 74
10.42.1
10.42.2
10.42.3

Phone Number 1 Programming:
Program Address (3159) ................................. 74
Phone Number 2 Programming:
Program Address (3175) ................................. 74
Phone Number 3 Programming:
Program Address (3191) ................................. 74

11.0 Installation Guide for UL Listed Systems ............ 75
11.1

DS7400Xi UL Listings: ................................................ 75

11.2
11.3

Installation Considerations ......................................... 76
Programming the DS7400Xi ....................................... 76

11.1.1

11.3.1
11.3.2

11.4

Household Fire Alarm Using Digital Alarm
Communicator Transmitter With Local Bell ........ 76
Grade A Household Burglary Alarm Using Digital
Alarm Communicator Transmitter With Local Bell 76

General System Requirements .................................. 76
11.4.1
11.4.2
11.4.3

11.5
11.6

UL System Configurations ................................ 75

Local Burglary Alarm ....................................... 77
Police Station Connection ................................. 77
Central Station Burglary Alarm and
Proprietary ....................................................... 77

Commercial Fire Alarm ................................................ 77
Wiring and Programming Information for Installations
Using the Ademco AB-12 Bell/Housing ...................... 78

12.0 Report Programming .............................................. 79
12.1
12.2
12.3
12.4

4/2 Format ....................................................................
BFSK Format ................................................................
Personal Dialing Format .............................................
Pager Format ...............................................................

79
80
81
81

13.0 Report Programming - Values Sent ..................... 83
13.1
13.2

SIA Formats .................................................................. 83
CID Formats ................................................................. 85

14.0 Multiplex Zone Addressing Guide ........................ 86
15.0 Troubleshooting Guide ........................................... 87
15.1
15.2
15.3
15.4

Keypad Problems ........................................................ 87
Reporting Problems .................................................... 88
Zone Problems ............................................................ 88
General System Problems .......................................... 89

16.0 Program Addresses ................................................. 93

Index ................................................................................ 99

10.37 Output Function Programming:
Program Addresses (2772-2843) ............................... 66
10.37.1

Output Function Partition Assignment:
Program Addresses (2852-2863) ..................... 67

10.38 Dual Phone Line/Bell Supervision Module Output
Programming:
Program Address (4021) ............................................. 67
10.39 Call-Out Timer Programming:
Program Addresses (4022-4025) ............................... 68
10.40 Test Report and Remote Programmer Call-Out
Programming:
Program Address (4026) ............................................. 68
10.41 Alpha Description Programming:

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 3

1.0

Specifications

1.1

Enclosure Housing

The standard enclosure is manufactured from 20 Guage (1.0 mm),
cold-rolled steel, and measures 12.5 by 14.5 by 3 inch (31.8 by
36.8 by 7.6 cm) (HxWxD). A keyed lock is included, and this enclosure
has provision for an optional tamper switch (required for
commercial burglary applications) for monitoring the door.

NOTE:

Fire Systems installed under NFPA-72 or UL Listed Fire
Systems require the use of 18 AWG or larger wire.

1.7

Communicator

• Temperature: +32°F to +120°F (0°C to +49°C)

Will report to two phone numbers with full single, double and backup reporting. Communicates in SIA (110 or 300 baud), 3/1, 3/1 Ext.,
3/1 with Parity, 3/1 Ext. with Parity, 4/1, 4/2, BFSK, Contact ID, and
Pager formats.
FCC Registration Number is ESVUSA-75333-AL-E
The ringer equivalence is 0.1B
Commercial Fire CSFM Listing Number is 7165-1062:113
Residential Fire CSFM Listing Number is 7167-1062:114

1.3

1.8

1.2

Storage and Operating Temperature

Power

NOTE:

•
•
•
•
•
•

The total current output capacity for all auxiliary devices,
including keypads and smoke detectors = 1.5 A standby,
2.5 A alarm. The following ratings are maximum values.
The total combined output cannot exceed the maximum
load current.
Input power:
18 VAC, 50 VA, 50 Hz./60 Hz.
Auxiliary power:
12 VDC, 1.0 A max.
UL Listed Alarm Power Output: 12 VDC, 1.75 A max.
Auxiliary power voltage range:
12 V special application
Optional Standby battery (P334): 12 V, 7.0 Ah - 35 Ah max.
Control panel current draw:
175 mA, Standby
250 mA, Alarm

1.4

Outputs

• Alarm Output:

12 VDC, 1.75 A output. Can be programmed
for steady or pulsed output.
• Programmable Solid state current sink (1.0 A max.). Shorts to
Aux. negative when activated. Connect device
to Aux. power positive. Can be used for alarm,
Output 1*
arming state, or access control.** This output
is generally programmable.
• Programmable Solid state voltage source (500 mA max.). Can
be used for alarm, arming state, or access
control.** This output is generally
Output 2*
programmable. For use with such compatible
devices as the Listed DS250 with a 4-wire
base.
* = Current draw should be subtracted from either maximum
auxiliary or maximum alarm current draw.
** = Not investigated to the requirements of UL294.

1.5

Zones

• 8 on-board zones. Up to 248 total zones with expansion modules.
• Zone Response Time: 300 ms.

1.6

Keypads

•
•
•
•

15 Keypads
1000 feet (305 m)
6000 feet (1830 m) in system
4 conductor, unshielded, #22 AWG
(0.8 mm) “Telephone quad” or #18
AWG (1.0 mm) quad wiring can be
home-run or daisy- chained.
No more than 2 keypads (#22 AWG) or 3 keypads (#18
AWG) are recommended on any 1000 foot (305 m) run.
Shared cable is not recommended for keypad, multiplex,
options bus, telephone, or siren wiring.

Maximum # of keypads:
Maximum wire length each:
Maximum wire length total:
Wire type:

NOTE:
NOTE:

Partitions

The system has the capacity for 8 independent partitions. One
partition may be a common area.

1.9

Users

The DS7400Xi Ver 4+ system allows up to 200 individual users.
Each user will have his own PIN number (the 4- or 6-digit code
entered at the keypads) and his own authority level (to determine
which functions he may perform).

1.10

Lightning Protection

MOVs and spark gaps provide protection from lightning surges
and static discharges.

1.11

Burglar/Fire Zone Inputs

• Number of circuits:
• End-of-line resistor:
• Loop resistance tolerance:

1.12

8 Circuits on-board
2.2 kΩ (P/N 25899, provided)
60 ohms

Fire Signal Initiating Circuit (2-wire mode)

Fire circuit will work with 2- or 4-wire detectors and has optional
alarm verification.
• Number of circuits:
8 Circuits on-board
• Type of circuit:
Class B, latching
• End-of-line resistor:
2.2 kΩ (P/N 25899, provided)
• Supervisory current:
5.5 mA
• Maximum short circuit current: 22 mA
• Maximum line resistance:
60 ohms
• Circuit voltage range:
8.5 to 14.1 VDC
• Total detector standby current: 2.5 mA

1.13

Multiplex Bus Wiring Requirements

NOTE:

Do not use twisted-pair or shielded cable. Do not share
cable with the keypad lines.

• #22 AWG (0.8 mm). Up to 2000 feet (610 m) per system.
• #18 AWG (1.0 mm). Up to 5000 feet (1525 m) per system.

1.13.1 Multiplex Zone Loop Wiring
• Maximum wire length not to exceed 500 feet (150m) regardless
of the wire gauge.

1.14

Option Bus Wiring Requirements

• Maximum wire length 1000 feet (305 m) per home-run.
Page 4

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

1.15

Max. Load Currents

Max. Load Currents
UL Installations

Standby

Alarm

1.5 A

2.5 A

Maximum Current By Output:
Not to exceed the maximum load currents listed above in Standby or Alarm

1.16

Backup Battery Calculation

Aux. Power & Keypad (Combined)

1.0 A

Option Power

1.0 A

1.0 A

X

1.75 A

Programmable Output 2

500 mA

500 mA

Loop Power +

500 mA

500 mA

Bell Output

• The following table is used to calculate the standby battery
capacity required by NFPA when using the DS7400Xi:
Quantity

Device

Standby Current
per Device

Total Standby
Current

Alarm Current
per Device

(Quantity x Standby
Current per Device)

DS7400Xi (4+) Control Panel
DS7416i Advanced Radio Communications Module
DS7412 - RS232 Serial Interface Module
DS7420i -Dual Phone Line/Bell Supervision Module
DS7430 – Multiplex Expansion Module
DS7432 – 8-Input Remote Module
DS7433 – 8-Input Direct Module
DS7436 – Dual Multiplex Expansion Module
DS7445/DS7445i Keypad
DS7447/ DS7447E Keypad
DS7448 Keypad
DS7450, DS7452, DS7455 Contact Points
DS7457 – Single Zone Multiplex Input Module
DS7460 – Dual Zone Module
DS7465 – Input/Output Module
DS7480 – Bell Supervision Module
DS7481 – Single Phone Line Monitor
DS7488 – Octal Relay Module**
DS7489 – Solid State Output Module
MX280 Series Multiplex Smoke Detectors
MX540 (DS7473) PIR Detector
®
MX835 TriTech PIR/Microwave Detector
MX775 (DS7470) PIR Detector
MX794 (DS7474) PIR Detector
MX934 (DS7471) PIR Detector
MX938 (DS7472) PIR Detector
®
MX950 (DS7476) TriTech PIR/Microwave Detector
RF3222 Wireless Receivers
2-Wire Smoke Detectors
4-Wire Smoke Detectors
Bells, Horns, etc.
Other Sensors
Other

1

175 mA
127 mA
35 mA max.
20 mA
65 mA
10 mA
65 mA
130 mA
75 mA
100 mA
80 mA
350 μA
350 μA
1 mA
1 mA
7 mA
20 mA
10 mA + 40 mA**
10 mA
500 μA
800 μA
6 mA
200 μA
800 μA
200 μA
200 μA
6 mA
30 mA

175 mA

Grand Total

1.0 A

Total Alarm
Current
(Quantity x Alarm
Current per Device)

250 mA
127 mA
35 mA max.
140 mA
65 mA
10 mA
80 mA*
130 mA
75 mA
100 mA
100 mA
350 μA
350 μA
1 mA
1 mA
50 mA
20 mA
10 mA + 40 mA**
750 mA max.***
560 μA
800 μA
35 mA
200 μA
800 μA
200 μA
200 μA
35 mA
30 mA

250 mA

Grand Total

* = Add 15 mA for each additional zone in alarm.
** = When calculating Standby and Alarm Current for the Octal Relay Module, use 10 mA plus 40 mA for each activated relay.
*** = Maximum current draw if using the DS7400Xi Panel power supply. Total of all outputs cannot exceed 750 mA.

1.17

Standby Current Load

• Battery Ah - (20% Storage + 0.375 Ah Alarm)
• The following table is the derated battery divided by hours minus the control standby (175 mA):
Rechargeable
Battery Size
7 Ah
8 Ah
14 Ah
15 Ah
17.2 Ah
21 Ah
28 Ah
30 Ah
35 Ah

Max. Standby
for 4 hours
1.0 A
1.2 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A

DS7400Xi ( 4+) Reference Guide

Max. Standby
for 8 hours
470 mA
580 mA
1.1 A
1.2 A
1.5 A
1.5 A
1.5 A
1.5 A
1.5 A

Max. Standby
for 24 hours
X
X
270 mA
300 mA
380 mA
500 mA
740 mA
800 mA
970 mA

Max. Standby
for 48 hours
X
X
X
X
100 mA
160 mA
280 mA
310 mA
400 mA

Max. Standby
for 60 hours
X
X
X
X
X
100 mA
190 mA
210 mA
280 mA

Copyright © 2007 Bosch Security Systems, Inc.

Max. Standby
for 72 hours
X
X
X
X
X
X
130 mA
150 mA
200 mA

Max. Standby
for 80 hours
X
X
X
X
X
X
100 mA
120 mA
170 mA

P/N: F01U035325-01

Page 5

1.18

Options

• DS7412:

RS232 Serial Interface module.
The DS7412 module allows the panel to send event
information, in an ASCII format, directly to a serial
printer or computer. In addition, the interface allows
the direct connection of a computer to the panel for
programming via the WDSRP programming software.
• Current Draw= 25 mA; 35 mA with LEDs on.

• DS7416i: Advanced Radio Communications Module provides
a means of communicating alarm and supervision
signals using the Motient radio network. This can
be a replacement for, or a complement to, the
standard digital communicator.
• Current draw = 127 mA Standby and Alarm.
• DS7420i: Dual Phone Line/Bell Supervision Module (1 per
system).
The DS7420i allows the control to be used in NFPA
72 installations. It provides two supervised 12.0 VDC
signaling outputs, one Class A (Style D) input zone,
and dual phone line transmission and supervision.
• Current Draw = 20 mA Standby; 140 mA Alarm.
• DS7430:

Multiplex Expansion Module (1 per system).
The DS7430 provides a two-wire multiplex bus for
the connection of additional remote zones. It also
supplies up to 200 mA for 4-wire multiplex devices
such as the DS7432.
• Current Draw = 65 mA, Standby; 65 mA, Alarm.

• DS7432:

8-Input Remote Module (up to 30 per system.
Requires a DS7430 or DS7436 Multiplex Expansion
Module).
The DS7432 provides a means of monitoring
conventional Normally Open or Normally Closed
contacts. It reports their status to the control panel
as multiplex addresses. It occupies eight multiplex
zones on the system and can monitor up to eight
separate loops. It will support 4-wire smoke
detectors.
• Current Draw = 10 mA; Standby. 10 mA, Alarm.

• DS7433:

• DS7436:

• DS7448: Control Station. (15 Keypads max. per system)
The DS7448 is a four-wire LCD annunciator
keypad. It has a Silence key and a Reset key used
for controlling annunciator and control panel
operation, a Keylock Switch that can be used to
lock out the annunciator to prevent unwanted
silencing or resetting of the control panel, and a
two-line, 16-character Display capable of showing
all messages normally displayed on a DS7447/
DS7447E keypad.
• Current Draw = 80 mA, Standby; 100 mA, Alarm
• DS7450:

Flush Mount Single Multiplex Contact Point (requires
a DS7430 Multiplex Expansion Module).
The DS7450 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 μA, Standby; 350 μA, Alarm.

• DS7452:

8-Input Direct Module (1 per system. Can not be used
with the DS7430 or DS7436 Multiplex Expansion
Modules).
The DS7433 provides a means of expanding the
system to include eight additional hard-wired zones.
Each zone can support up to twenty 2-wire smoke
detectors (can also support 4-wire smoke detectors).
• Current Draw = 65 mA, Standby; 80 mA, Alarm.
Add 15 mA for each additional zone in alarm.

Surface Mount Single Multiplex Contact Point (requires
a DS7430 Multiplex Expansion Module).
The DS7452 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 μA, Standby; 350 μA, Alarm.

• DS7455:

Multiplex Expansion Module. (1 per system.)
The DS7436 provides two two-wire multiplex buses
for the connection of up to 120 remote points. It
also supplies 200 mA per bus.
• Current Draw = 130 mA, Standby or Alarm.

Surface Mount Single Multiplex Contact Point
(requires a DS7430 Multiplex Expansion Module).
The DS7455 is intended as a replacement for
conventional dry contacts, and to report an actual
multiplex address to the control panel. Occupies 1
zone.
• Current Draw = 350 µA, Standby; 350 µA, Alarm.

• DS7457:

Single Zone Multiplex Input Module (requires a
DS7430 Multiplex Expansion Module).
The DS7457 provides a means of monitoring
conventionally Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies one multiplex zone
on the system and can monitor one loop. It also
includes a tamper loop.
• Current Draw = 350 μA, Standby; 350 μA, Alarm.

• DS7445/DS7445i: Control Station. (15 Keypads max. per
system). The DS7445/DS7445i is an LED keypad
which has LEDs representing the first 8 zones of
the system. It displays information on various
control panel functions. A built in sounder is used
as an interior warning device and to annunciate
keystroke entries.
• Current Draw = 75 mA, Standby; 75 mA, Alarm.
Page 6

• DS7447/DS7447E: Control Station. (15 Keypads max. per
system)
The DS7447/DS7447E is an Alpha-Numeric LCD
keypad. It displays information on various control
panel functions. A built-in sounder is used as an
interior warning device and to annunciate keystroke
entries.
• Current Draw = 100 mA, Standby; 100 mA, Alarm.
• Keypad Access Output: The DS7447/DS7447E
Alpha Keypad will provide a ten (10) second access
relay output if equipped with the optional K800 Relay.
The relay will energize at the keypad if the user has a
master, unlimited, general, or access PIN. The output
will change only if the user has access to the partition
assigned to the keypad. See the DS7445/DS7447
Keypad Installation Instructions (P/N: 22235) or the
DS7445/DS7445i/DS7447E Installation Instructions
(P/N: 4998138630) for wiring information.

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

• DS7460:

Dual Zone Module (up to 60 per system. Requires a
DS7430 Multiplex Expansion Module).
The DS7460 provides a means of monitoring
conventional Normally Open or Normally Closed
contacts. It reports their status to the control panel as
multiplex addresses. It occupies two multiplex zones
on the system and can monitor up to two separate
loops.
• Current Draw = 1 mA, Standby; 1 mA, Alarm.

• DS7465:

Input/Output Module (up to 60 per system. Requires
a DS7430 Multiplex Expansion Module).
The DS7465 provides a Form “C” relay that may be
programmed to activate on system events, and an
input loop to monitor conventional Normally Open or
Normally Closed contacts. It reports their status to
the control panel as multiplex addresses.
• Current Draw = 1 mA Standby; 1 mA with relay
energized.
• Occupies 2 zones.

• DS7480:

Bell Supervision Module (1 per system).
The DS7480 provides a means of monitoring bells. It
provides a supervised (polarity reversing) output relay
to activate the bell. It also provides a Form “C” Bell
Fault Output to be connected to the control panel.
• Current Draw = 7 mA @ 12 VDC, Standby; 50 mA
@ 12 VDC, Alarm.

• DS7481:

Single Phone Line Monitor (1 per system).
The DS7481 provides a means of monitoring a single
phone line for fault conditions. When a fault is
detected, the DS7481 automatically closes its
Normally Open relay contacts to provide a means of
signaling the fault.
• Current Draw = 20 mA, Standby; 20 mA, Alarm.

• DS7488:

• DS7489:

Octal Relay Module (2 per system).
The DS7488 provides 8 Form “C” relay outputs for
addition to the system. The outputs are fully
programmable and can be activated by system
events. Each output operates individually of the other
7 outputs for complete flexibility.
• Current Draw = 10 mA + 40 mA for each relay
when energized.
Solid State Output Module (2 per system).
The DS7489 is a Solid State Octal Driver Module that
provides 8 open collector transistor outputs. The
outputs are fully programmable and can be activated
by system events. Each output operates individually
of the other 7 outputs for complete flexibility. The
DS7489 Module has not been investigated by
Underwriters Laboratories, Inc.
• Current Draw = 10mA.
• Outputs: Provides a current sink (the output shorts
to common (-) when activated). The maximum
current draw for all 8 outputs combined cannot
exceed 750 mA.

DS7400Xi ( 4+) Reference Guide

• DS9484:

The DS9484 is a Remote Notification Appliance
Circuit (NAC) Power Supply designed to add four
additional NACs (NFPA 72 Class B, Style Y) to a
Fire Alarm Control Panel (FACP). When connected
to the Options Bus of the DS7400Xi, it can provide
intelligent control of its individual outputs. It
supplies 6 A of NAC power through four circuits to
drive horn strobe loads. It is UL Listed as a fire
accessory for use in Commercial fire applications
and as a continuous-load power supply for auxiliary
devices.
• Current Draw = 150 mA, Standby; 6 A maximum,
Alarm

• MX280:

Multiplexed Photoelectric Smoke Detector (up to 120
detectors may be used per system. Requires a
DS7430 and occupies one multiplex zone). Detects
smoke and automatically determines the detector’s
sensitivity using the Detection Systems “Chamber
Check” feature.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.

• MX280TH: Multiplexed Photoelectric Smoke Detector with a
135°F heat sensor (up to 120 detectors may be used
per system. Requires a DS7430 and occupies one
multiplex zone). Detects smoke and is equiped with
a 135°F heat sensor for high temperature alarms.
The Detection Systems “Chamber Check” feature
automatically determines the detector’s sensitivity.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.
• MX280THL: Multiplexed Photoelectric Smoke Detector with a
135°F heat sensor and a 45°F freeze alarm (up to 60
detectors may be used per system. Requires a
DS7430 and occupies two multiplex zones). Detects
smoke and is equiped with a 135°F heat sensor for
high temperature alarms and a 45°F sensor for freeze
alarms. Freeze alarms are reported separately from
smoke and high temperature alarms. The Detection
Systems “Chamber Check” feature automatically
determines the detector’s sensitivity.
• Current Draw = 500 μA, Standby; 560 μA, Alarm.
• MX540:

Multiplexed Passive Infrared (PIR) Intrusion Detector
(DS7473) with a standard range of 40 by 50 feet (12
by 15 meters). Requires a DS7430 and occupies
one multiplex zone.
• Current Draw = 200 μA, Standby; 2 mA, Alarm.

• MX835 TriTech Microwave/PIR Intrusion Detector with “Pet
Avoidance” technology and a standard range of 35 by
35 feet (10.7m by 10.7 m). Requires a DS7430 and
occupies one multiplex zone.
• Current Draw = 6 mA, Standby; 35 mA in “Trouble”
and Walk Test mode.
• MX775 Multiplex Passive Infrared (PIR) Intrusion Detector with
(DS7470) a standard range of 50 by 50 feet (15 m by
15 m). Requires a DS7430 and occupies one multiplex
zone.
• Current Draw = 200 μA, Standby; 2 mA in Walk
Test mode.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 7

• MX794 The MX794 is a Long Range Multiplex PIR intrusion
(DS7474) Detector with Self-test. The standard ranges
are 80 ft. by 50 ft. (24.0 m by 15.0 m) and 200 ft. by 10 ft.
(61.0 m by 3.1 m). Requires a DS7430 and occupies
one multiplex zone.
• Current Draw = 800 μA, Standby; 2 mA, Alarm.
• MX934 Multiplex Passive Infrared (PIR) intrusion detector with
(DS7471) a standard range of 35 by 35 feet (10.7 m by
10.7 m). Requires a DS7430 and occupies one multiplex
zone.
• Current Draw = 200 μA, Standby; 2 mA in Walk
Test mode.
• MX938 360° Ceiling Mount Multiplex PIR Intrusion Detector
(DS7472) with a 60 foot (18.3 m) diameter range.
Requires a DS7430 and occupies one multiplex zone.
• Current Draw = 200 μA, Standby; 2.5 mA in Walk
Test mode.

2.0

2.1

2.2

•

• RF3222:

•

The control/communicator is also available in three package formats. The packages include the following:
• DS7400XiF: DS7400Xi in large red enclosure manufactured
from 18 Guage (1.2 mm), cold-rolled steel,
measuring 15.0 by 20.75 by 4.25 inch (38.1 by 52.7
by 10.8 cm) (HxWxD).

Install the Enclosure

• Use the enclosure as a template and mark the top mounting
holes on the mounting surface.
• Pre-start the mounting screws for these two holes. Slide the
enclosure onto these mounting screws so that the screws move
up into the thinner section of the holes. Tighten the screws.
• Screw in the remaining two screws in either set of bottom
mounting holes.
• Knock out the desired wire entrances on the enclosure.

• MX950 Multiplex TriTech Microwave/PIR Intrusion Detector
(DS7476) with motion monitor and antimask features
and with a standard range of 50 by 50 feet (15 m by
15 m). Requires a DS7430 and occupies one multiplex zone.
• Current Draw = 6 mA, Standby; 35 mA in “Trouble”
and Walk Test mode.
120-zone Wireless Receiver. (up to two receivers
per system. Requires use of a DS7430 or DS7436
Multiplex Expansion Module.)
See the DS7400Xi (4+) Wireless Reference Guide
(P/N: 44575) for more information.
• Current Draw = 30 mA

Enclosure Installation

The DS7400Xi control/communicator and the enclosure are
shipped together. The control, however, still needs to be installed
into the enclosure. Hardware for mounting the enclosure to a wall,
and the control to the enclosure is located in its own hardware
pack.

•
•

Install the Control/Communicator

The control is static sensitive. Make sure you touch
earth ground before handling the control. This will
discharge any static electricity in your body. Example:
Run the ground wire to the enclosure before handling
the control. Then keep holding the ground wire while
installing the control.
Insert the three support posts into the control retainer holes as
shown in the diagram.
Slide the top of the control into the retainer tabs (the slots under
the top frame).
Once in the retainer tabs, the control will rest on the three support
posts.
Secure the bottom of the enclosure by screwing the bottom three
holes through the support posts and through to the control
retainer holes.
Once the control is installed, be sure to connect its
ground wire to the top hinge of the enclosure (the
unpainted tab).

• DS7400XiFCP: DS7400XiF package with: DS7420i, DS7447/
DS7447E and a AE-TR16
• DS7400XiCC: DS7400Xi in an Attack Enclosure.
When installing a UL Listed system, refer to Section 11.0, Installation
Guide for UL Listed Systems.

Page 8

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Wiring

The Battery Terminals and Wires are NOT Power Limited. A ¼ in. (6.4 mm) spacing must be maintained between
the battery terminals, battery wiring and all other wiring. Battery wiring may not share the same conduit, conduit
fittings or conduit knock-outs with other wiring.
Option or
Keypad Wires
¼ in. (6.4 mm) Minimum
Battery Wires
Output or
Zone Wires
To ensure proper spacing
secure wires using
Tie-Wraps or similar devices
Only required if
external batteries
are used

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 9

3.0

Control Terminal Wiring

TYPICAL BURGLAR AND FIRE WIRING
Zone Loop +
Input
Z–

Zone Loop +
Input

L+

Z–

Zone Loop +
Input or PO2

L+

Z–

Before servicing, remove all power
including the transformer, battery and
phone line. A complete functional test
is required after any programming.

WARNING

Aux. Power (—)
(terminal 5 or 7)
–

L+

in +

+ out

Power

–

Alarm

NO

Incorrect connections may
result in damage to the unit.

NC

CAUTION
in +

System is Power Limited except for
battery terminals. All wiring entering
this enclosure must be power limited.

(for a list of
compatible 2-wire
smoke detectors,
see Technical Service
Note P/N 27685)

EARTH GROUND: Must be connected to
a good earth ground such as a cold water
pipe and also connected to the cabinet cover,
using the supplied wire jumper.

2
A
C

A/C INPUT: Use U. L. listed, 18 VAC 50
VA, class 2 transformer. Model TR-1850
requires 50/60 Hz. unswitched dedicated
outlet - do not share.

5

–

ALARM OUTPUT:

6

A

7

–

3
4

8

+

O
P
T
I
O
N

–

End-of-Line
Supervision Relay
(e.g. Detection Systems’
EOL200)

Typical 4-wire smoke
detector wiring.
For example:
Detection Systems’
DS250 in an MB4W base.

An appropriate two pole disconnect device must be installed
by qualified service personnel, as part of the building installation.

Provides 12 VDC, special application, up to
1.75 A for powering bells, siren drivers, etc.
Function programmed in address 2734.

CAUTION

AUXILIARY POWER:

Danger of explosion if battery is incorrectly replaced.

Provides 12 VDC, special application, up to
1.0 A for powering detectors.

Replace with the same or equivalent type
recommended by the manufacturer.
Dispose of used batteries according to the
manufacturer's instructions.

CAUTION

R
B
G
Y

Alarm

Typical 2-wire
smoke detector
wiring

Typical burglar
alarm loop wiring

A/C Power Indication LED
1

+ out

Power

OPTION BUS:
Used for options such as the DS7416i
Communications Module, the DS7420i Dual
Phone Line Module, etc.
Also for keypads #11 - #15.
For Commercial Fire Mode: Option Bus wiring
should be in conduit if run ouside the
enclosure.

KEYPAD BUS*:
Up to 15 keypads**
may be used. Can be
“home-run” or
“daisy-chained.”

PROGRAMMABLE OUTPUTS:
PO1 shorts to aux. power negative when activated, PO1 can sink up to 1.0 A.
PO1 function programmed in address 2735.
PO2 supplies 12 V and up to 500 mA when activated.
PO2 function programmed in address 2736.

ZONES 1-8: Zones 1-8 are intended for connection of Normally
Open or Normally Closed alarm contacts. They may also be used
for compatible 2-wire smoke detectors. These zones require a
2.21kΩ resistor (P/N 25899) at the end of the loop. Power is
momentarily removed from L+ after a [PIN] + [System Reset] or
during a fire verification.
Zone 1-8 assignments are programmed in address 0031-0038.

PHONE LINE:

T

TH

RH

R

R

B

G

Y

G

B

S

R

9

10

1

12

13

14

15

16

PO1 PO2 1–

17

18

19

L+

2–

3–

L+

4–

5–

L+

6–

7–

L+

8–

20

21

22

23

24

25

26

27

28

29

30

Keypad
(#1 - #10)
Keypad
(#1 - #10)
* = Maximum wire length each: 1000 ft. (305 m).
Maximum wire length total in system: 6000 ft. (1830 m) when using
#22 AWG (0.8 mm) or #18 AWG (1.0 mm) cable.
** = Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15
connect to the Option Bus.

NOTE

Page 10

P/N: F01U035325-01

Shared cable is not recommended for keypad,
multiplex, options bus, telephone, or siren wiring.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

4.0

Hardware Layout Example
DS7416i
Communications
Module
R
B
G
Y
+ – + –1

2 3

4 5

6 7

+ – + –1

8

POWER BUS

Keypads #11 - #15 must be connected to
the Options Bus. Keypads #1 - #10 must
be connected to the Keypad Bus.
Armed

2 3

4 5

6 7

2 3

4 5

6 7

8

POWER BUS

DS7430

Arme d

St atus

Stat us

Power

+

Powe r

Fire

–

+

–

+ – + –1

Fire

Power Bus
On
1

2

3

4

5

6

7

8

9

*

0

#

Per imete r
O nly

No
Entry

Byp ass

1

2

3

4

5

6

7

8

9

*

0

#

Arme
Armed
d

On
1

2

3

Off

6

Per imete r
O nly

4

5

7

8

9

*

0

#

DS7400Xi

No
Entr y

Byp ass

Armed

Fire

St tus
atus
Sta

Perimete
r
Pe ri met
er
Supe
rvis ory
Superv
isory

Power
Pow er
Fire
Fire

e ll Silenc
Bell BSile
nce d ed
Troubl e
Trouble

No
Entry

Byp ass

Syste m
Reset

1 1 2 2 33 44 55 6 6 77 88
9 10 11 12 13 14 15 16
TEST WEEKLY

11

22

33

44

55

77

88

99

**

00

##

66

6 7

+ – + –1

8

®

1
2

R
B

3

G
Y

4
5

On
On

6
7

Off
Off

8
9

PePer
rimimete
eter r
On
Olynly
No
No
Ent
Entryry

10

Dry contact inputs 47kΩ

EOL

Option
Bu s

+
Batte ry
– –
+ –Bell Outp ut
–
Au xiliary
+
Out put
–
–+++– –

Bypass
Byp as s

DS7432 8-Input
Remote Modules

R R T T R R T T R R T T

1 12 1 3 1 4 15 16 17 18 1 9 20 21 22 23 24 25 2 6 27 28

System
em
RSyst
e set
Re
set

Armed
St atus
Power
Fire

Arme
d
Armed
Sta
St tus
atus
Power
Pow
er

Pe ri met
er
Perimete
r
Superv
isory
Supe
rvis ory
e ll Silenc
Bell BSile
nce d ed

Fire
Fire

Troubl e
Trouble

2

3

5

6

7

8

9

*

0

#

Off
Per imete r
O nly

No
Entry

1 1 2 2 33 44 55 6 6 77 88
9 10 11 12 13 14 15 16
TEST WEEKLY

On
1
4

®

On
On

11

22

33

Off
Off

44

55

66

PePer
rimimete
eter r
Olynly
On

77

88

99

**

00

##

DS7420i Dual Phone
Line/Bell Supervision
Module

No
No
Ent
Entryry

Bypass
Byp as s

Syst em
System
set
RRe
e set

Battery

Armed

Armed
Arme
d
St atus
Sta tus
Power
Pow er
Fire
Fire

St atus
Power
Fire

Perimete
r
Pe ri met
er
Supe rvis ory
Superv isory
Be ll Silenc ed
Bell Sile nce d
Troubl e
Trouble

On
1

2

3

Off

4

5

6

Per imete r
O nly

7

8

9

*

0

#

DS7488 Octal
Relay Board

Byp ass

Syste m
Reset

No
Entry

Byp ass

Syste m
Reset

Battery

®

1 1 2 2 33 44 55 6 6 77 88
9 10 11 12 13 14 15 16
TEST WEEKLY

8

POWER BUS

Per imete r
O nly

Sys tem
Reset

St atus

4 5

Off

Syste m
Reset

Power

2 3

POWER BUS

On

Off

On
On

11

22

33

Off
Off

44

55

66

Pe rim eter
Per
imete r
On ly
O nly

77

88

99

**

00

##

1 2 3

2 G1

4 5

-+
BUS

+
1 2 3
NO C NC

DS7450/52 Series Contacts, DS7460 Input Modules,
DS7465 Input/Output Modules, MX540, MX775,
MX794, MX835, MX934, MX938, and MX950 motion
detectors and MX280 Series Smoke Detectors

No
No
Ent
Entryry
Bypass
Byp as s
System
Syst
em
RRe
e set
set

DS7447/DS7447E and DS7445/DS7445i
Keypads

Note: Ensure at least 1/4" separation
between battery wires and all
other cabling.
RF3222 120-Zone
Wireless Receivers
Wireless Sensors

• Up to 15 keypads may be used. Keypads #1 - #10 connect to the Keypad Bus and keypads #11 - #15
connect to the Option Bus. One keypad must be designated as keypad #1 and connected to the Keypad
Bus. See the DS7447/DS7447E, DS7445/DS7445i, and DS7448 Installation Instructions for further details.
• A DS7420i (Dual Phone Line/Bell Supervision Module) may be connected to the Control Panel, and
placed within the enclosure. Connect to the Options Bus of the control panel. See the DS7420i Installation
Instructions for further details.
• Up to 2 DS7488s (Octal Relay Modules) may be connected to the Control Panel, and placed within the
enclosure. Connect to the Options Bus of the Control Panel. This provides an additional 8 Form “C”
relay outputs for the Control Panel. See the DS7488 Installation Instructions for further details.
• A DS7430 or a DS7436 (Multiplex Expansion Module) may be connected to the control panel via the
expansion port. This will allow for the connection of additional zones via the Options Bus. See the DS7430
or DS7436 Installation Instructions for further details.
• Up to 30 DS7432s (8-Input Remote Modules) may be connected to the DS7430 or DS7436. Connect to the
Power and Bus Terminals of the Multiplex Expansion Module. This allows for a means of addressing up to
240 input loops of conventional contacts to the Control Panel. See the DS7432 Installation Instructions for
further details.
• Up to 2 RF3222 (120-Zone Wireless Receivers) may be connected to the DS7430 or DS7436. Connect to
the Power and Bus terminals of the Multiplex Expansion Module. This allows for the monitoring of wireless
detectors.
• A DS7416i Advanced Radio Communications Module may be connected to the Control Panel via the Options
Bus. This allows for connection to a radio network.
• Up to 248 zones are available for the connection of Single, Multiple, Input/Output, and Multiplex devices.
Up to 112 wireless zones (137-248) are also available.
DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 11

5.0

System Worksheet
Account Number

Information

Name

Contact Person

Address

Voice Phone Number
Panel Phone Number

City, State, Zip

Panel Answers Phone

Armed

Disarmed

Equipment Location and Notes
AC Voltage

VAC

Battery Standby

Battery Voltage

Ah

VDC

Bell Current

AUX Current

A

A

Control Panel
Transformer
Telephone Jack
Telephone On Same Line as Panel
Earth Ground Connection
Alarm Sounder (s)

Misc. Notes
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________

Keypad Location and Notes
Location
Keypad # 1
Location

Belongs
to Partition

Example
Belongs
to Partition

Kitchen

2

Master/
Standard

Master/
Standard
Master

Location

Keypad # 1

Keypad # 9

Keypad # 2

Keypad # 10

Keypad # 3

Keypad # 11

Keypad # 4

Keypad # 12

Keypad # 5

Keypad # 13

Keypad # 6

Keypad # 14

Keypad # 7

Keypad # 15

Belongs
to Partition

Master/
Standard

Keypad # 8

Page 12

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

5.0

System Worksheet (continued)

PIN Worksheet

Personal Identification Number Information
Example
PIN Information
User Pin # Auth. Parti- Name
Level tions
#
002

PIN Information
User Pin # Auth. Parti- Name
Level tions
#
001

1001

6

1, 2, 4 James L.

PIN Information
User Pin # Auth. Parti- Name
Level tions
#
034

PIN Information
User Pin # Auth. Parti- Name
Level tions
#
067

002

035

068

003

036

069

004

037

005

038

070
071

006

039

072

007

040

073

008

041

074

009

042

075

010

043

076

011

044

077

012

045

078

013

046

079

014

047

080

015

048

081

016

049

082

017

050

083

018

051

084

019

052

085

020

053

086

021

054

087

022

055

088

023

056

089

024

057

090

025

058

091

026

059

092

027

060

093

028

061

094

029

062

095

030

063

096

031

064

097

032

065

098

033

066

099

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 13

5.0

System Worksheet (continued)

PIN Worksheet

Personal Identification Number Information
PIN Information
User Pin # Auth. Parti- Name
#
Level tions
100

134

PIN Information
User Pin # Auth. Parti- Name
#
Level tions
168

101

135

169

102

136

170

103

137

104

138

171
172

105

139

173

106

140

174

107

141

175

108

142

176

109

143

177

110

144

178

111

145

179

112

146

180

113

147

181

114

148

182

115

149

183

116

150

184

117

151

185

118

152

186

119

153

187

120

154

188

121

155

189

122

156

190

123

157

191

124

158

192

125

159

193

126

160

194

127

161

195

128

162

196

129

163

197

130

164

198

131

165

199

132

166

200

133

167

Page 14

P/N: F01U035325-01

PIN Information
User Pin # Auth. Parti- Name
#
Level tions

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

5.0

System Worksheet (continued)

Zone Location and Notes

Zone Location and Notes Worksheet

* = SZ: Single Zone Input
MZ: Multiple Zone Input
IO: DS7465
(see section 10.3)

Example
Type * Zone/Output
Partition & Location
Function #
Zone # 1 SZ

Zn Funct. 1

Type * Zone/Output
Function #

2, Kitchen

Partition & Location

Type * Zone/Output
Function #

Zone # 1

Zone # 31

Zone # 2

Zone # 32

Zone # 3

Zone # 33

Zone # 4

Zone # 34

Zone # 5

Zone # 35

Zone # 6

Zone # 36

Zone # 7

Zone # 37

Zone # 8

Zone # 38

Zone # 9

Zone # 39

Zone # 10

Zone # 40

Zone # 11

Zone # 41

Zone # 12

Zone # 42

Zone # 13

Zone # 43

Zone # 14

Zone # 44

Zone # 15

Zone # 45

Zone # 16

Zone # 46

Zone # 17

Zone # 47

Zone # 18

Zone # 48

Zone # 19

Zone # 49

Zone # 20

Zone # 50

Zone # 21

Zone # 51

Zone # 22

Zone # 52

Zone # 23

Zone # 53

Zone # 24

Zone # 54

Zone # 25

Zone # 55

Zone # 26

Zone # 56

Zone # 27

Zone # 57

Zone # 28

Zone # 58

Zone # 29

Zone # 59

Zone # 30

Zone # 60

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

Partition & Location

P/N: F01U035325-01

Page 15

5.0

System Worksheet (continued)

Page 16

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

5.0

System Worksheet (continued)

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 17

5.0

System Worksheet (continued)

Zone Location and Notes Worksheet

Page 18

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

6.0

Glossary

6.2

6.1

General Control Programming

• Zone Function
A Zone Function is the description of how a particular zone will
behave (e.g. steady alarm output, bypassing allowed, alarm on
short, trouble on open, perimeter instant).
- There are many possible zone functions. Up to 30 different
zone functions are allowed per control.
- Zone functions may be custom made as needed.
- Each zone must be programmed as a specific zone function.
Any number and combination of zones may be programmed
as particular zone functions.
- Program zone functions at addresses 0001-0030.

• Normal Arming - [PIN] + [On]: If programmed, arms the entire
system while allowing entry delays for entry/exit zones.
• Perimeter Instant Arming - [PIN] + [No Entry] [Perimeter Only]: If
programmed, arms only the perimeter of the system and does
not allow entry delays for entry/exit zones.
• Perimeter Arming - [PIN] + [Perimeter Only]: If programmed,
arms only the perimeter of the system while allowing entry delays
for entry/exit zones.
• Custom Arming - [PIN] + [#] [4]: If programmed, allows custom
arming of the system and bypasses the zone functions specified
in data addresses 2725-2728.
• Maximum Security Arming - [PIN] + [No Entry] [On]: If
programmed, arms the entire system and does not allow an
entry delay for entry/exit zones.
• General Authority by Partition
A general (level 2) authority can be programmed to have armonly authority; arm and bypass authority; arm and disarm
authority; or arm, disarm, and bypass authority by partition. This
is done at addresses 3421-3424.
- Arm-only access by partition allows someone with a General
Authority to arm zones in a partition he can not disarm.
- This level can still be used to arm, disarm, and bypass zones
in the other partitions that it has access to.
• Closing Ring-Back: If programmed, the keypad sounders and
Bell will activate for 2 seconds after the system is armed and the
closing report is successfully sent. This requires Closing RingBack and Closing Report to be programmed.
- If a closing report is not programmed, the control will test for a
dial tone when the system is armed. If the test passes, the
system will arm normally. If the test fails, the system will arm,
but will indicate a trouble condition.
- The DS7447/DS7447E keypad will display “Communication
Err” after [#] [8] [7] is entered.
• Siren on Comm. Fail for Silent Zone: If programmed, a silent
zone will sound the alarm outputs if the zone is in an alarm
condition and the system fails to communicate with the central
station.
• Restore when Sounders Silence: If programmed, a zone sends
a restoral report and is ready to activate again only after the
burglary bell cut-off time expires or the bells are silenced.
- The zone can alarm multiple times per armed period.
• Restore when Zone Restores: If programmed, a zone sends a
restoral report and is ready to activate again as soon as it
physically restores.
- This zone can alarm multiple times per armed period.
• Restore when System Disarms: If programmed, a zone sends
a restoral report when the system is disarmed.
- It can only alarm once per armed period.
• Allow Swinger Shunts: If programmed, a zone can only alarm
or trouble up to three times per armed period. After the third
alarm or trouble, the zone will be bypassed and a bypass report
will be sent.
NOTE: Swinger Shunts are not allowed on UL Certificated
Installations.

DS7400Xi ( 4+) Reference Guide

Zone Function Programming

• Invisible Alarms: This is a zone programmed not to have an
alarm output or an alarm display at any keypad when activated.
An alarm signal will be sent, but the DS7447/DS7447E keypad
display will read “Not Ready” while this zone is violated.
- Invisible Alarm zones are recommended for holdup alarms.
• Silent Alarms: This is a zone programmed to activate the visual
display at the keypad, but not audible signals.
- If this zone is also an entry zone, an entry tone will sound when
this zone is activated.
• Bypassing Allowed: This is a zone programmed to allow
bypassing (shunting). This is done using the bypass command
or the force-arming sequence.
• Alarm on Short: This is a zone programmed to activate an
alarm when its loop is shorted.
• Alarm on Open: This is a zone programmed to activate an
alarm when its loop is opened.
• Trouble on Open: This is a zone programmed to activate a
trouble when its loop is opened and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Open.
• Trouble on Short: This is a zone programmed to activate a
trouble when its loop is shorted and the system is disarmed.
- If the system is armed, this zone will activate an alarm if shorted
or opened.
- For 24-hour zones, regardless of the arming state of the panel,
this always remains as a Trouble on Short.
• Interior Delayed: This is a zone programmed to be ignored
during the entry/exit delay period. If it is violated when the system
is armed, it will activate a delay for the programmed entry delay
time. The keypad pre-alert sounders will activate and the system
may be disarmed during this delay period. If the system is not
disarmed during this delay period, this zone will activate an alarm.
This zone is bypassed by Perimeter Instant or Perimeter Armed.
• Perimeter Instant: This is a zone programmed to activate an
alarm even during the entry/exit delay period.
• 24-Hour: This is a zone programmed to activate when its loop is
faulted, even if the system is disarmed.
• Entry/Exit Delay #1: This is a zone programmed to be ignored
during the entry/exit delay period.
- If it is violated while the system is armed, it will activate a delay
for the amount of time programmed for entry delay time #1
(address 4028). The keypad pre-alert sounders will activate
and the system may be disarmed during this delay period.
- If the system is not disarmed during the entry period, this zone
will activate an alarm.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 19

• Entry/Exit Delay #2: This is a zone programmed to behave
identical to the Entry/Exit Delay #1 zone function except that it
uses entry delay time #2 (address 4029).
NOTE: If both entry delays have been activated, the control will
use the shorter entry delay.
• Entry/Exit Delay Cancel Zone Functions
Entry/Exit Delay Cancel 1 and Entry/Exit Delay Cancel 2 Zone
Functions cause the exit delay to expire as soon as the premises
is vacated.
- If a zone is programmed as an Entry/Exit Delay Cancel zone,
and it is activated during the exit delay, the exit delay will expire
as soon as the zone has been restored.
- Entry/Exit Delay Cancel 1 follows entry delay 1.
- Entry/Exit Delay Cancel 2 follows entry delay 2.
• Interior Entry/Exit Follower: This is a zone programmed to be
ignored during an entry/exit delay and then become an interior
instant zone.
- If this zone is violated while the system is armed and no entry/
exit zones have been violated, it will activate an alarm.
- If this zone is violated after an entry/exit delay zone is violated,
it will follow that entry/exit delay time.
- This zone is bypassed by Perimeter Instant or Perimeter
arming.
• Interior Home/Away: This is a zone programmed to become an
interior instant zone if the system is armed and an entry/exit
delay zone is violated during the exit delay time.
- If the system is armed and an entry/exit delay zone is not
violated, this zone will be bypassed.
- This zone is bypassed by Perimeter Instant or Perimeter
arming.
• Interior Instant: This is a zone programmed to activate an alarm
even during the entry/exit delay periods.
- It is bypassed by Perimeter Instant or Perimeter arming.
• Day Monitor: This is a zone programmed to be a perimeter
instant zone when the system is armed.
- When the system is disarmed, any violation of this zone will
activate the keypad sounders which will sound continuously
until a disarm command sequence is entered.
- The alarm outputs for this zone will not activate and there will
be no report for this zone when the system is disarmed.
• Keyswitch Input: This is a zone programmed to allow the system
to be armed or disarmed using a Normally Open momentary
keyswitch.
- Outputs for keyswitch LEDs and sounders are available using
the programmable outputs or the Octal relay outputs.
- An output is needed for each LED and sounder.
- A keyswitch will only control the partition that these zones are
assigned to unless programmed as a master, then it will
control all at once. See Program Address 0001, Data Digit 1.
- Keyswitches and keypads may be used in the same partition,
if desired.
• Fire Zone: This is a zone programmed to activate if the system
is armed or disarmed.
- It can be silenced (not reset) by entering a valid [PIN] + [Off].
- The display will indicate a Fire Alarm for this zone on all
keypads in every partition.
- A fire reset command must be entered after silencing the
alarm to re-enable this zone.
- If this zone is programmed for trouble and the loop opens, the
DS7447/DS7447E keypad will display “Fire Trouble” for this
zone and the keypad sounders will beep once every ten
Page 20

P/N: F01U035325-01

seconds.
- If the system is a combination fire and burglar alarm, the fire
alarm has priority over the burglar alarm.
• Fire Zone with Verification: This zone is identical to a Fire Zone
except that after the first alarm, it will perform a fire reset and
then wait up to two minutes for a second alarm.
- If a second alarm occurs within this two minute period, the
system will indicate a fire alarm.
- If there is no second alarm within this two minute period, the
control panel will reset back to its normal condition.
NOTE: Use of this control’s alarm verification feature is not permitted for applications in the state of California.
• Water Flow Zone: This is a zone programmed to operate like a
Fire Zone, but is specifically intended for water flow switches.
- An optional retard timer can be programmed to compensate
for changes in water pressure. If the timer is used, the water
flow zone must be activated for the complete time period; an
alarm will be initiated at the end of the timer period.
- The maximum combined water flow delay of the control panel
and the device must not exceed two minutes.
NOTE: Any zone can be a water flow zone, but only zones 1
through 4 may be programmed as delayed water flow
zones.
• Supervisory Zone: This is a zone programmed to accommodate
shut-off valves.
- It will indicate a supervisory condition at the keypads when
activated.

6.3

Zone Programming

• Zone
A Zone is an input to the DS7400Xi Control/Communicator.
- There are 8 hardwired zones on the main circuit board.
- Additional zones may be added by using the DS7433 (8 zone
expansion module), the DS7430 (multiplex loop module), and/
or other modules.
• Single Zone Input: This is an individual zone such as the onboard zones and multiplex contact zones.
• Multiple Zone Input: This is a zone connected to one of the 8Input Modules (DS7432 or DS7433) or to a Dual Zone Module
(DS7460).
- The inputs are programmed separately (see the separate
Programming Addresses Worksheet, P/N: 29802).
- When using the Dual Zone Module (DS7460), loop A is always
programmed as an odd numbered program address (ending
in 1, 3, 5, 7, or 9). Loop B is the even numbered program
address that follows loop A.
• DS7465: This is the input zone or the output relay on a DS7465.
The odd numbered zone is programmed for the input zone
function and the even numbered zone is programmed for the
output function.
• Multiplex Smoke: This is a multiplexed input zone (zones 9248) that is used with a MX280 series smoke detector. This zone
must have a Zone Function of Fire Zone and Trouble on Open
applied to the multiplex smoke zone.
• Multiplex Smoke with Low Temperature: This zone is used
with the MX280 series smoke detectors with a low temperature
alarm. Making this selection requires the programming of two
zones as follows:

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

- Smoke alarm. This must be the odd numbered zone of the
zone pair required for these devices. The zone must be
programmed with a zone function that is set for Fire Zone and
Trouble on Open.
- Low Temperature Alarm. This must be the even numbered
zone of the zone pair required for these devices. This zone
must be programmed with a zone function that is set as
Supervisory and Trouble on Open.

6.4

Output Programming

• Latch on Any Zone Alarm: This is an output programmed to
activate upon any zone alarm (including invisible zones) and will
latch until the system has been disarmed.
- If this output is programmed to respond only to a fire zone, it
will remain latched until the fire reset command is performed.
• ON during Entry Pre-Alert: This is an output programmed to
activate when an entry/exit zone is violated while the system is
armed.
- It will remain activated until the system is disarmed, or until
the entry delay time has expired.
• ON for 10 seconds after [PIN] + [System Reset] is entered: This
is an output programmed to activate for 10 seconds after the fire
reset command is entered at the keypad or if a Fire Zone with
Verification activates.
- This output is intended to be used to power 4-wire smoke
detectors or any other device that requires a power interruption
to reset an alarm condition.
NOTE: When Programmable Output 2 is programmed this way,
it will normally supply auxiliary power and will turn OFF for
10 seconds when the fire reset command is entered.
• ON when System is Armed: This is an output programmed to
activate when the system is armed.
- It will remain activated until the system is disarmed.
• Ground Start: This is an output programmed to activate for 3
seconds when the phone line is seized. It is intended for use
with ground start phone systems that require a momentary short
to ground to obtain a dial tone.
- Connect a separate 12 VDC, DPDT relay.
- Connect both relay contact commons to ground, and connect
the Normally Open of each contact to terminal positions 13
and 16 (one to terminal 13, the other to 16) of the DS7400Xi.
- This output follows all partitions regardless of how data digit 2
of the output programming address is programmed.
- Not intended for UL Listed systems. Not for use with phone
line monitors.
• System Status (ready to arm): This is an output programmed
to follow the Status LED of the keypad.
- It will activate when the system is ready to arm with no zones
violated.
• Zone Alarm: This is an output programmed to activate when a
zone is in an alarm condition.
- It will remain activated until the system is disarmed or the bell
cut-off time expires.
- This output is intended to activate alarm bells and sirens.
- This will not activate from Silent or Invisible Zones.
• Zone Alarm Delayed by 20 sec.: This is an output programmed
to wait 20 seconds after a zone enters an alarm condition to
activate.
- It will remain activated until the system is disarmed or the bell

DS7400Xi ( 4+) Reference Guide

cut-off time expires.
- This output is intended to activate alarm bells and sirens, but
provides a delay to allow the user to silence the system before
it activates.
• Output Functions
Output Functions can be programmed to follow system events
or to follow one or two specific zones in a “cross-matrix” fashion
(see Input/Output Cross-Matrixing).
- These Output Functions can be programmed to control Octal
Relay outputs or Multiplex Bus outputs.
- Output Functions are programmed in addresses 2772-2843.
• Input/Output Cross Matrixing
Input/Output Cross Matrixing allows Output Functions to follow
the status of specific input zones (zones 1 through 248 only).
- Outputs can be programmed to follow any combination of one
or two zones, open or closed, with the system armed or disarmed.
- If programmed to latch, the output will latch until a valid PIN is
entered at the keypad.
• Keypad Sounder Output: This is an output programmed to follow
the keypad sounder.
- It activates during the entry pre-alert and during any day monitor
alarm. It does not follow momentary keypad beeps such as
keystrokes, chimes, etc.
• Access Output: This is an output programmed to activate for
10 seconds when an access control PIN is entered at the keypad.
- Not UL Listed for Access Control (UL294).
• Panic/Duress Output: All outputs, including the three on-board
outputs, the Octal Relays, and the Output Functions, support a
Panic/Duress function. This output will follow Duress activations,
Keypad Emergency Keys B and C, and Invisible and Silent Zone
alarms. It will only be reset by a user acknowledgement and will
not reset after the burglary bell time-out occurs. Duress activations will latch until acknowledged by a user.
• Multiplex Bus Outputs
The DS7400Xi supports up to 60 DS7465 Input/Output Modules.
- These modules are connected to the multiplex bus and provide
one input loop and one Form “C” output relay.
- The input loop operates the same as all other multiplex inputs.
- The output loop can be programmed to follow Output
Functions.
- Multiplex Bus outputs can be bypassed using the bypass
function. If an output zone is bypassed while it is ON, it will turn
OFF. The bypass will not be removed when the system is
armed and then disarmed; it must be cancelled by entering
the bypass command again or by cancelling all bypasses.
NOTE: DS7465 Module outputs will not pulse, even if programmed
to do so.
• Octal Relay Modules (DS7488)
The DS7400Xi can support two Octal Relay Modules.
- Each relay can be programmed to follow system-wide events
or Output Functions as described above.
• Solid State Output Modules (DS7489)
The DS7400Xi can support two Solid State Output Modules.
- Each output can be programmed to follow system-wide events
or Output Functions as described above.

6.5

Partition Control Programming

• Partition Control Programming: Up to eight partitions may be
used. They are assigned (program address 3420) in order.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 21

- For example: When using only one partition, it is partition one.
When using three partitions, they are partitions one, two, and
three.
- Partitioning allows the system to act as up to 8 different
systems.
- Zones, keypads, outputs, and other items may be assigned to
particular partitions.
- Access to partitions may be through each partition’s keypad
or through a Master keypad (see the User’s Guide P/N: 43851
for more details).
• Common Area: Partition 1 can be programmed as a common
area, that is, common to other partitions. This allows it to be
used in an installation with one common entry area such as a
foyer or vestibule.
- When Partition 1 is programmed as a common area, it will
only arm when all the partitions it is common to are armed.
- The common area will disarm when any of the partitions it is
common to are disarmed - only if the user has access to the
common area.
- When using a common area, a Master keypad should be used
and assigned to the common area (see keypad assignment
programming).

6.6

Keypad Assignment Programming

• Keypad Assignment: The keypad type and the partition it is
assigned to must be programmed.
- Each program address (3131-3138) programs the keypad
type for two keypads. For example: for address 3131, data
digit 1 is for keypad 1, data digit 2 is for keypad 2.
- Each program address (3139-3146) programs the partition
assignment for two keypads. For example: for address 3139,
data digit 1is for the partition assignment of keypad 1, data
digit 2 is for the partition assignment of keypad 2.
- Users must have access to the partition the keypad is assigned
to in order to use the keypad.
• Master Keypad Programming : A Master keypad can be used
to access all the partitions.
- It will display the arm/disarm status of all the partitions and
can be used to individually control each partition (see section
7.6).
- A Master keypad can be assigned to any of the partitions.
- Any number of the 15 allowable keypads can be a Master
keypad.
- When using the common area, it is suggested that a Master
keypad be used and that it is assigned to the common area.

6.7

Emergency Key Programming

NOTE:

Do not label these keys if they are unprogrammed. Only
the “A” key may be programmed and labeled as the Fire
key. These keys are not intended to substitute for Listed
manual pull boxes.

• Fire Key: The emergency key (key A) at the bottom left of the
keypad entry area is the Fire Key. If programmed, the key will
activate a fire alarm when pressed for 2 seconds.
- It may be programmed for a steady or pulsed alarm.
NOTE: The Fire Key will generate the fire alarm sounders in the
partition that activated the Fire Key. Any other partitions in
use will only have their keypad sounders activated. All
keypad displays will be the same.
• Special Emergency Key: The emergency key (key B) at the
bottom center of the keypad entry area is the Special Emergency
Page 22

P/N: F01U035325-01

Key.
- If programmed, the key will activate a supplementary or an auxiliary
type alarm when pressed for 2 seconds.
- It may be programmed for a silent, steady, or pulsed alarm.
• Panic Key: The emergency key (key C) at the bottom right of the
keypad entry area is the Panic Key.
- If programmed, the key will activate a panic alarm when
pressed for 2 seconds; nothing will display at the keypad to
indicate an alarm.
- It may be programmed for a silent, steady, or pulsed alarm.
NOTE: The Special Emergency Key and the Panic Key will generate the alarm sounders only in the partition of the keypad that activated that Key.

6.8

Custom Arming Programming

• Custom Arming - [PIN ] + [#] [4]: If programmed, the [PIN] + [#]
+ [4] command sequence may be used to custom arm the system
by arming only certain zone functions.
- For example: All interior zones plus some perimeter zones
may be bypassed while leaving some of the perimeter armed.

6.9

Force Arming

• Force Arming: If programmed, allows violated zones to be force
armed. When force arming, the user must enter the usual arming
command followed by the [Bypass] key. This automatically
bypasses zones that are violated and programmed as
bypassable.
- Fire zones, supervisory zones, keyswitch zones, waterflow
zones, and non-bypassable zones can not be force armed.
- Not available in UL Listed systems.
- See Program Address 2732.

6.10

Ground Fault Detect Programming

• Ground Fault: If programmed, this function will allow the system
to detect ground faults. This function is required for fire panels
and will be forced on when the panel is in the commercial fire
mode.
- See Program Address 2732.

6.11

Commercial Fire Mode Programming

NOTE:

In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different indicating appliances or by using distinct cadences for the
same appliance.

• Commercial Fire Mode: When in Commercial Fire Mode, the
control panel will perform some functions (e.g. communications)
differently to conform with commercial fire regulations.
- See Commercial Fire Mode Programming, program address
2733.
• Water Flow Zone Delay: This is the amount of time a water flow
zone must be violated before the control panel will initiate an
alarm.
- The delay is necessary to accommodate normal changes in
water pressure.
- If the water flow initiating device incorporates its own time
delay, do not program the control panel unit to exceed 120
seconds combined time delay.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

• Pulsing Fire Zone: This is a zone programmed to output a pulse
for a fire alarm in the normal manner (one second ON, one second
OFF).
• California March Time: This is a zone programmed to output a
pulse for a fire alarm in the California Time cadence (ten 1/2
second pulses, followed by one second of quiet time).

• Keypad Emergency Alarm: This report is sent when an
emergency alarm has been activated using the “B” emergency key.
• Keypad Panic: This report is sent when an emergency alarm has
been activated using the “C” emergency key.
• Keypad Tamper: For keypads fitted with a wall tamper switch, this
report is sent when the keypad is removed from the wall.

• Temporal: This is a zone programmed to output a pulse for a
fire alarm in the Temporal cadence (three 1/2 second pulses,
followed by one second of quiet time).

• Keypad Tamper Restoral: For keypads fitted with a wall tamper
switch, this report is sent when the keypad is properly replaced
on the wall after experiencing a tamper condition.

• Single Keypad Use: The keypad should be used on the keypad
bus and be mounted to the front of the control enclosure OR if
within the same room as the control equipment with the wire run
in conduit (or equivalently protected against mechanical injury)
within 20 ft. (6.1 m) of the control equipment.
- This keypad should be assigned as address 1.

• Zone Function Alarm: An alarm report is sent when a zone
alarm occurs. Alarm reports are enabled by zone function. Program this report for any zone functions you wish to send an
alarm report about. For local zones (no reports), do not program
an alarm report. The zone number will automatically be sent for
this report in SIA or Contact ID format.

• Multiple Keypad Use: One keypad only must be used on the
option bus, at any address from 11 - 14, and must meet the
following requirements:
- The keypad must be mounted to the front of the control
enclosure OR mounted within the same room as the control
equipment and the wire is run in conduit (or equivalently
protected against mechanical injury) within 20 ft. (6.1 m) of the
control equipment.
- All other keypads should be connected to the keypad bus and
may be placed as needed (within the noted wiring limitations
in the installation manual).
- One keypad must be assigned as address 1.

• Zone Function Restoral: This report is sent when the zone alarm
and trouble conditions are cleared. The zone number will automatically be sent for this report in SIA or Contact ID format.

6.12

Open/Close Report Control Programming

• Open and Close Reports: If programmed, these reports are
sent when the system is armed or disarmed. They may be sent
independently for the opening and closing of each partition, or
the first partition to open and the last partition to close may send
the reports.
• Send Trouble at Close for Bypassed Zones: If programmed, a
trouble report will be sent for each zone bypassed when the
system is armed.
• Alternate between both Phone Numbers: If programmed, open
and close reports will be sent to phone number one first. If phone
number one does not pick-up, the control panel will alternate to
phone number two. If phone number two does not pick-up, the
control panel will alternate back to phone number one. It will
alternate between both phone numbers until successful.

6.13

Report Programming

• Reports: For pulse formats, reports are programmed by entering data in the reporting and extended digits. The report will
send the data programmed for each event. For SIA and Contact
ID, the report formats are fixed and may be activated by placing a
1 in the reporting digit.
- To disable a report, enter a 0 in the reporting digit.
- To send the Man No. along with Open and Close reports,
program an "F" (enter [*] [5] at the keypad) in the extended
digit.

• Zone Function Trouble: This report is sent when a zone trouble
condition occurs. This can be an open circuit, if the zone is programmed for “trouble on open”, a multiplex tamper switch being
activated, or a multiplex zone not communicating with the control
panel. The zone number will automatically be sent for this report
in SIA or Contact ID format.
• Zone Function Bypass: This report is sent when a zone is bypassed. (Note: Fire zones can never be bypassed.) Zone bypass reports for non-24 hour zones are sent with the closing
report. Bypass reports for 24 hour zones are sent when the zone
is bypassed. If a zone is force armed, the bypass report is sent
with the partial close report. If a 24 hour or non-24 hour zone is
custom armed, the bypass report is sent with the partial close
report.
• Zone Function Bypass Restoral: This report is sent when the
zone bypass is cleared. For non-24 hour zones the bypass restoral is sent with the open report. Bypass restoral reports for 24
hour zones are sent when the zone is manually restored. The
bypass restoral report for a zone that was force armed is sent
when the zone is restored. If a 24 hour or non-24 hour zone was
custom armed, the bypass restoral is sent with the open report.
• Open: This report is sent when the system has been disarmed.
In SIA or Contact ID formats, the user number for the person who
disarmed the system will be sent with this report. To send the
user number along with an Open report in other formats, program
the extended digit of the report as *5. In Contact ID format, the
partition number will also be sent along with this report. The
Open report will only be sent if a Close report was sent previously.
• Close: This report is sent when the system has been armed. In
SIA or Contact ID formats, the user number for the person who
armed the system will be sent with this report. To send the user
number along with a Close report in other formats, program the
extended digit of the report as *5. In Contact ID format, the partition
number will also be sent along with this report.
• Duress: This report is sent when the system is disarmed using
a duress code. The user number is not sent with this report.

• Keypad Fire Alarm: This report is sent when a fire alarm has
been activated by the “A” emergency key.

• Partial Close: This report is sent when the system is armed
partially, or force armed.

• Keypad Fire Restoral: This report is sent when a keypad fire
alarm has been restored using the [System Reset] command.

• First Open After Alarm: This report is sent when the system is
disarmed after an alarm has occurred.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 23

• Low Battery: This report is sent when a low battery condition
occurs.
• Battery Restoral: This report is sent when a low battery condition
restores.
• AC Fail: This report is sent when an AC failure condition occurs.
This report may be delayed in address 4034.
• A/C Failure Report Delay
The A/C power loss report can be programmed to delay for up to
254 minutes (see address 4034). (The same delay would also
apply to the A/C restoral report.)
- If another report is sent during this delay period, the A/C fail
report will be sent along with this report.
- If the A/C power restores during this delay period, the A/C loss
report will not be sent.
- Programming address 4034 as FF causes the report to be
sent at a random interval of at least 15 minutes, but no more
than 2 hours after the A/C failure occurs.
• AC Restoral: This report is sent when an AC failure condition
restores.
• Communicator Test/System Normal: This report is sent at the
24-hour check-in time if there is not a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition. Note: To send a Communicator Test
even if one of these conditions exists, program the Communicator
Test/System Off Normal.
• Remote Program Successful: This report is sent after a Remote
Program session, if the session was terminated properly.
• Remote Program Unsuccessful: This report is sent after a
Remote Program session, if some error has occurred or the
session did not terminate properly.

• System Walk Test: This report is sent when a system test has
been started ([#] [8] [1] key sequence). Zone reports are sent
during a system test.
• System Walk Test Restoral: This report is sent when the system
test has been completed or has timed-out.
• Fire Walk Test: This report is sent when a Fire Walk Test has
been started ([#] [9] [1] key sequence). Zone reports are not sent
during a Fire Walk Test.
• Fire Walk Test Restoral: This report is sent when the Fire Walk
Test has been completed or has timed-out.
• Mux. Smoke Low Temperature Report: This supervisory report
is sent when a MX280 Series smoke detector with a low
temperature feature detects a temperature of 45°F (7.5°C) or
less for a period of 30 minutes or more.
• Mux. Smoke Low Temperature Restoral: This report is sent
when a MX280 Series smoke detector with a low temperature
alarm determines that the temperature has risen above 45°F
(7.5°C).
• Dirty Chamber Report: This report is sent when a MX280 Series
smoke detector fails to pass the “Chamber Check®” sensitivity
test.
• Dirty Chamber Restoral: This report is sent when a MX280
Series smoke detector has been returned to normal operation
after service.

6.14

Phone Number General Control
Programming

• Local Program Successful: This report is sent when local
programmer’s mode is exited and there is no error associated
with the programming.

• Enable Remote Programmer Callback: If programmed, when
the remote programmer tries to initiate a session with the panel,
the panel will hang up and call the remote programmer phone
number.
- Ensures the correct remote programmer is initiating the call.

• Local Program Unsuccessful: This report is sent when local
programmer’s mode is exited and there has been some error
associated with the programming.

• Dial Pulse on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the pulse format.

• System Trouble: This report is sent when a control trouble
condition occurs.

• Dial Tone on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the tone format.

• System Trouble Restoral: This report is sent when all system
trouble conditions restore.
• Communicator Test/System Off Normal: This report is sent at
the 24-hour check-in time if there is a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition.
• Exit Error: This report is sent if an exit error occurs. An exit error
occurs when an entry/exit zone is still violated at the end of the
exit delay. If this happens, the entry delay will begin and any
output programmed to activate an alarm will energize. If the
system is not disarmed before the entry delay expires, an alarm
report for the effected zone will be sent and the Exit Error report
will be sent. If this report is not programmed, the control will not
sound the exit error warning.

6.15

Phone Answering Programming

• Answering Machine Bypass: This feature allows the panel to
answer incoming calls when answering machines are used. If
the line rings, stops ringing, then rings again within one minute,
the panel will seize the phone line on the first ring.
• Phone Answering Programming: The panel can be
programmed to answer the phone after a selected number of
rings for remote programming access. It can also be
programmed to answer the phone after a different number of
rings when in armed or disarmed states.
- This can be used to call the panel location and determine its
arming state.

• Recent Closing: This report is sent, along with any alarm reports,
when there is an alarm within the first five minutes after the
system has been armed.

Page 24

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

6.16

FCC Compliance Notice

6.18

This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This
equipment generates, uses and can radiate radio frequency energy
and if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for
help.

6.17

FCC Phone Connection Notice To Users

This control complies with Part 68 of the FCC rules.
On the inside of the enclosure is a label that contains, among
other information, the FCC Registration Number and the Ringer
Equivalence Number (REN) for this equipment. You must, upon
request, provide this information to your local telephone company.
The REN is useful to determine the quantity of devices that may be
connected to your telephone line and still have all of those devices
ring when your telephone number is called. In most, but not all
areas, the sum of the REN's of all devices connected to one line
should not exceed five (5.0). To be certain of the number of devices
that you may connect to your line, you may want to contact your
local telephone company to determine the maximum REN for your
local calling area.
This equipment may not be used on coin service provided by the
telephone company. This control should not be connected to party
lines.
Should this equipment cause harm to the telephone network, the
telephone company may discontinue your service temporarily. If
possible, they will notify you in advance. But if advanced notice isn’t
practical, you will be notified as soon as possible. You will be
informed of your right to file a complaint with the FCC. The telephone
company may make changes in its facilities, equipment,
operations, or procedures that could affect the proper functioning
of your equipment.
If they do, you will be notified in advance to give you an opportunity
to maintain uninterrupted telephone service.
If you experience trouble with this equipment, please contact the
manufacturer for information on obtaining service or repairs.
The telephone company may ask that you disconnect this
equipment from the network until the problem has been corrected
or until you are sure that the equipment is not malfunctioning. The
repairs to this equipment must be made by the manufacturer and
not the user.

Canadian Dept. of Communications

General Installation Requirements: Notice: The Canadian
Department of Communications label identifies certified
equipment. This certification means that the equipment meets
certain telecommunications network, protective, operational, and
safety requirements. The Department does not guarantee the
equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is
permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be
installed using an acceptable method of connection. In some
cases, the company’s inside wiring associated with a single line
individual service may be extended by means of a certified connector
assembly (telephone extension cord). The customer should be
aware that compliance with the above conditions may not prevent
degradation of service in some situations.
Repairs to certified equipment should be made by an authorized
Canadian maintenance facility designated by the supplier. Any
repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical
ground connections of the power utility, telephone lines, and internal
metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
Users should not attempt to make such connections
themselves, but should contact the appropriate
electric inspection authority, or electrician, as
appropriate.

Terminal Requirements: The Load Number (LN) assigned to
each terminal device denotes the percentage of the total load to be
connected to a telephone loop which is used by the device, to
prevent overloading. The termination on a loop may consist of any
combination of devices subject only to the requirement that the
total of the Load Numbers of all the devices does not exceed 100.
The Load Number of the DS7400Xi is 2.
RFI Requirements: This Class A digital apparatus meets all
requirements of the Canadian Interference-Causing Equipment
Regulations. [Cet appareil numerique de la classe A respecte
toutes les exigences du Reglement sur le material broilleur du
Canada.]

6.19

For Installations in New Zealand

Two-wire Connection:
The operation of this equipment on the same line as telephones
or other equipment with audible warning devices or automatic ring
detectors will give rise to bell tinkle or noise and may cause false
tripping of the ring detector. Should such problems occur, the user
is not to contact Telecom Faults Service.

To guard against accidental disconnection, there is ample room to
mount the Telco jack to the inside of the Control cabinet.
The operation of this Control may also be affected if events such
as accidents or acts of God cause an interruption in telephone
service.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 25

7.0

Operating Guide

For additional information on operating this system, consult the DS7400Xi (Ver. 4+) User’s Guide (P/N: 43851) and the front cover of this
Reference Guide.

7.1

7.2

Emergency Procedures

Fire Reset/Fire Trouble

7.1.1 Identifying Alarm Sounds

7.2.1 Fire Reset

Your alarm system may be programmed for a steady alarm sound
or a pulsed alarm sound. It is important to learn the difference
between a fire alarm sound and an intrusion alarm sound before
you are confronted with an actual emergency.

During a fire alarm, exit the premises immediately. When you have
determined there is no fire, you may silence the bells/sirens before
you initiate the [System Reset] command: [PIN] + [System Reset].
Before the [System Reset] command is used, determine which
smoke detector has alarmed so the monitoring company may
verify its operation.
NOTE: To use the System Reset command sequence, your PIN
must have disarm privileges. The System Reset command will perform a fire reset, a battery test, and will clear
all system troubles.
NOTE: If the System Reset command has not been performed
after 24 hours of the Fire Alarm, the keypad will sound
and it will display “Fire Alarm Not Reset.” If the sounders
have been silenced and the system has been reset properly, this warning will not occur.

7.1.2 Silencing Alarms
All alarms can be silenced with any PIN that has disarm privileges.
Entering your [PIN]+ [Off] will silence the alarm and turn off (disarm)
the control.

7.1.3 A Cautionary Note
How you respond to an alarm will depend, mostly, on the type and
time of the alarm. You should seek the advice of your installing
company as they install your system, not later (e.g. after an alarm)
to develop a response plan.

7.1.4 Use Common Sense
Above all else, common sense should prevail. If there is any threat
or hint of danger to yourself or others on the premises, such as in
the event of a fire alarm, everyone should be instructed to leave the
premises immediately. Do not enter the premises unless
accompanied by the appropriate Emergency Services’ personnel,
or after they have given the OK to enter.

7.1.5 Caution When Entering a Building
If the bells and sirens are on and/or the red Armed Light is flashing
with the DS7447/DS7447E display reading “Zone Alarm” or the
DS7445/DS7445i having its zone LEDs flashing, then the keypad
is signaling that an alarm has occurred. The keypad will also issue
a pulsed tone during the entry delay instead of the usual steady
tone.
If the alarm has not been previously investigated, do not enter the
building unless accompanied by the appropriate Emergency
Services’ personnel.

7.1.6 Fire Alarms
Fire Alarms are silenced using the same procedure as intrusion
alarms: a [PIN] (with disarm privileges) plus the [Off] key.
The Fire Alarm system is not reset until alarms at smoke detectors
are cleared by using the [System Reset] command. The Fire Alarm
system will not be functional until this procedure has been followed.
See the “Fire Reset” section, 7.2.

7.3

7.2.2 Fire Trouble
A Fire Trouble message with a zone number signifies a problem
with the fire system, such as a break in the wiring that monitors
smoke detectors. A Fire Trouble message with no zone number
indicates a ground fault if the unit is in the commercial fire mode.
A Fire Trouble will be indicated by a short beep from the keypad
sounders every 10 seconds. The DS7447/DS7447E will display
“Fire Trouble” followed by the zones in a trouble condition. The
DS7445/DS7445i will turn the Fire and Trouble Lights on steady
and will light the corresponding zone LEDs.
Notify your installing company immediately if the Fire Trouble
message is displayed.
The Fire Trouble beep can be silenced with any [PIN] plus the [Off]
key. After problems have been remedied, a [PIN] plus the [Off] key
should again be entered to clear the “Fire Trouble” display.

7.2.3 Dirty Smoke
A Dirty Smoke display, followed by a zone number and accompanied
by a beep every ten seconds indicates that the smoke detector for
that zone requires cleaning or replacement. The smoke detector
will also give a Dirty indication by flashing its LED once per second.
The Dirty Smoke beep can be silenced by any [PIN] plus the [Off]
key.
Notify your installing company immediately if the Dirty Smoke
message is displayed.

Emergency Keypad Alarms

The Emergency Alarm Keys [A], [B], and [C] may generate Fire,
Special Emergency, and Panic Alarms if programmed by the
installer.
Ask your installing company to explain the function of these
keys.

Armed

Armed

Perimeter

Status

Status

Supervisory

Power

B el l Silenced

Fire

Trouble

Power
Fire

1 2

3

Off

5

6

Perimeter
Only

8

9

No
Entry

0

#

Bypass

1

2

4
7

*

3

4 5

6

B

8

On

1

2

3

Off

4

5

6

Perimeter
Only

7

8

9

No
En try

*

0

#

Bypass

System
Reset

A

7

9 10 11 12 13 14 15 16
TEST WEEKLY

On

System
Rese t

A

C

B

C

When using the Emergency Keys, they must be pressed for two seconds to generate an alarm.
NOTE:

If the Emergency Alarm Keys are to be used, they should be labeled to signify their functions.
The A key should be labeled as the Fire key. This is the only key that may be designated as the Fire key.
The B key should be labeled as the Special Emergency key.
The C key should be labeled as the Panic key.
Use the Disarming Command Sequence to cancel or silence these alarms.

Page 26

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

7.4

Fire
Safety

No fire detection device or system should be considered 100% foolproof.

This fire alarm system can provide early warning of a developing
fire. Such a system, however, does not ensure protection against
property damage or loss of life resulting from a fire. Any fire alarm
system may fail to warn for any number of reasons (e.g. smoke not
reaching a detector that is behind a closed door).
When considering detectors for residential applications, refer to
NFPA Standard 72, “The National Fire Alarm Code.” This standard
is available at a nominal cost from: The National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269.

exits from bedroom windows.
Make copies of the plan and practice it with all family members.
• Pre-arrange a meeting place outside and away from the
residence. Once out of the building, all occupants should
immediately go to the pre-selected location to be accounted for.
• Provide a barricade between family members and fire, smoke,
and toxic gases (e.g. close all bedroom doors before retiring).

Adherence to the NFPA Standard 72 can lead to reasonable fire
safety when the following items are practiced:

• Children should be instructed on opening their bedroom
windows and exiting safely from the building. If exiting is not
possible, they should be taught to stay at the open window and
shout for help until it arrives.

• Minimize hazards: Avoid the three traditional fire killers: smoking
in bed, leaving children home alone, and cleaning with
flammable liquids.

• In the event of a fire alarm after retiring, wake the children by
shouting to them from behind your closed door. Tell them to
keep their bedroom doors closed.

• Providing a fire warning system: Most fire deaths occur in the
home, the majority, during sleeping hours. The minimum level
of protection requires smoke detectors to be installed outside of
each separate sleeping area and on each additional story of the
dwelling.

• If the top of your bedroom door is uncomfortably hot, do not open
it. There is most likely fire, intolerable heat, or smoke on the
other side. Shout to all family members to keep their bedroom
doors closed and to exit the building via alternate routes.

For added early warning protection, it is recommended that
detectors be installed in all separated areas including the
basement, bedrooms, dining room, utility room, furnace room,
and hallways.

• If the top of the door is not uncomfortably hot, brace the bottom of
the door with your foot, and the top with one hand, then open the
door about one inch. Be prepared to slam the door shut if there
is any pressure against the door or if any hot air rushes in.

7.4.2 Having and Practicing an Escape Plan

• If there is no evidence of excessive heat or pressure, leave the
room and close the door behind you. Shout appropriate
instructions to all family members and immediately leave the
building via the pre-planned routes. If heavy smoke is present,
drop to your hands and knees, or crawl to remain below the
smoke level.

7.4.1 If Installed in Family Residences

A fire warning may be wasted unless the family has planned in
advance for a rapid and safe exit from the building.
• Draw a floor plan of the entire house showing two exits from
each bedroom and two from the house. Since stairwells and
hallways may be blocked during a fire, the plan should provide

7.4.3 Installation Considerations
Proper location of detection devices is one of the most critical
factors in a fire alarm system.
The following are some general considerations:

• Smoke detectors should not be installed in “dead air” spaces or
close to ventilating or air conditioning outlets because smoke
may be circulated away from the detector. Locations near air
inlets should be favored.
• Avoid areas subject to normal smoke concentrations such as
kitchens, garages, or near fireplaces.
• Do not install smoke detectors where normal area temperatures are above 100° F (38° C) or below 32° F (0° C).
• Areas of high humidity and dust concentrations should be avoided.
• The edge of ceiling mounted detectors should be no closer than
4 inches (10 cm) from any wall.
• Place the top edge of wall mounted detectors between 4 and 12
inches (10 to 30 cm) from the ceiling.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 27

7.5

Personal Identification Numbers

7.5.1 General Information

6 = Access Code: When a PIN with an Access Code is entered,
any output programmed for Access Output (i.e.
door strikes) will pulse on for 10 seconds
(works when the system is armed or
disarmed).

A PIN (Personal Identification Number) is the 4- or 6-digit code
users must enter at the keypad to gain access to the system. Your
system has the capability to assign up to 200 PINs, each four or six
digits long. A PIN may be assigned to each User Number.

7.5.2 Programming PINs

PINs should never be programmed with common sequences
such as 1 2 3 4, 1 1 1 1, or 2 4 6 8 because they are easily
violated.

PINs can only be added, changed, or removed in Master
Programming Mode, so they are not programmable from an RF
(wireless) keypad.

A User Number is the number that identifies each person using
the system. There are 200 possible User Numbers available for
use (001 through 200).

You should write down your entries before you enter the Master
Code Programming Mode and have them with you as you begin
programming. Make your entries promptly. If a long delay occurs in
your entries, the 3-beep error tone occurs and exits you from the
programming mode.

Each User Number can have only one PIN assigned to it.
Attempting to assign the same PIN to multiple User Numbers will
result in the three-beep error tone, and the entry will not be made.
User Number 001 is designated as a Master code. It can be used
to add, delete, or change other PINs. It will always have access to
all partitions regardless of how it is programmed.
User Number 001 is shipped from the factory with the PIN of 1 2 3
4. If your system has been reprogrammed for 6-digit PINs, the PIN
for User Number 001 will be 123456. This PIN should be changed
to one of your personal preference and must be programmed
as a Master code.
A Master code is one of the available authority levels which can be
assigned to a user to determine which functions that user will be
able to perform. The available authority levels are:
0 = Master:

1 = Unlimited:

2 = General:

3 = Arm Only:

4 = Temporary:

5 = Duress:

Page 28

Can enter all commands, add or change PINs
in assigned partitions, change the time and
date, bypass, arm, disarm, perform system
tests, system reset and view history. User
Number 001 must have the Master authority
level. Any or all PINs can behave as a Master
code.
Can enter all commands, bypass, arm,
disarm, system reset and perform system
tests. It can not change PINs.
Can bypass, arm and disarm. It can not change
PINs, system reset, enter [#] [7] or any of the
[#] [8] functions.
Can arm the system with [PIN] + [ON] arming
sequence only. It can not perform any other
functions, including disarming.
Valid only for a specified time (the PIN will
disappear upon expiration date). It can arm
and disarm the system, but can not perform
any other functions. If this is done from a
Master keypad, you must be in Single Partition
Mode. If access is assigned to more than one
partition, you must enter a Temporary PIN
expiration date for all assigned partitions (see
Changing the Expiration Date for Temporary
PINs).
When the system is disarmed using the duress
code, a silent report is sent to your monitoring
service. The Duress code is intended to be
used when the user is forced to disarm the
system.

P/N: F01U035325-01

It is recommended that all PIN programming procedures be
performed at a DS7447/DS7447E keypad since this keypad will
provided visual prompts throughout the programming sequence.
No visual clues will be given from a D7445/DS7445i keypad. When
the programming sequence is successfully completed, both the
DS7447/DS7447E and DS7445/DS7445i keypads will signal the
seccessful completion with a long beep.
To add or change a PIN:
• Enter Master Programming Mode (press [Master PIN] + [#] [0]).
• Enter a 0 for PIN Setup programming (press [0]).
• Enter the User Number (enter a 3-digit number from 001 to 200).
• Enter the Authority Level (enter a number from 0 to 6).
• Enter the Area(s) (Partitions) to which this user will have access
(press [1], [2], [3], [4], [5], [6], [7], and/or [8] followed by [#]).
• Enter the PIN (enter any 4- or 6-digit number; do not press [#]).
• Enter the PIN again followed by [#].
To set the expiration date for an existing Temporary PIN:
• Enter Master Programming Mode (press [Master PIN] + [#] [0]).
• Enter a 3 for Date of Code Expiration Setup programming (press
[3]).
• Enter the Expiration Month (press [0] [1] for January through [1]
[2] for December).
• Enter the Expiration Day (press [0] [1] through [3] [1]). The Temporary PIN will expire at Midnight on the day selected.
• Enter the Year (enter the last two digits of the year followed by
[#]).
NOTE:

Entering the command sequence [Master Code] [#] [0] [3]
[#] will cause the DS7447/DS7447E keypad to read back
the temporary code expiration date.

To remove a PIN:
• Enter Master Programming Mode (press [Master PIN] + [#] [0]).
• Enter a 0 for PIN Setup programming (press [0]).
• Enter the User number of the PIN to be cancelled, followed by [#]
(enter a 3-digit number from 001 to 200, then press [#]).

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

NOTE:

User Number 001 can not be disabled in this manner.

7.6

The Master Keypad

7.6.1 General Information
Your system may include a Master keypad. A Master keypad is a
DS7447/DS7447E keypad programmed to give a user access to
all the partitions the user has access to, not just the partition in
which the Master keypad is located. This is different from a
Standard keypad in that Standard keypads only give access to the
single partition in which they are located. Commands entered at
the Master keypad will affect all the partitions to which the user has
access. If this is not desirable, the Master keypad can also be
used to control each partition individually; this is called Single
Partition Mode. Single Partition Mode allows a user to control any
or all of the partitions the user has access to on an individual (oneby-one) basis (see section 7.6.3 for more information on Single
Partition Mode).
NOTE:

In order to use the Master keypad, your PIN must be
assigned to the partition in which the Master keypad is
located.

7.6.2 Master Keypad Displays
Master keypad displays will differ slightly from Standard keypads.
The Master keypad display will scroll the Status of each partition,
followed by the partition number. For example, if all partitions are
armed, the Master keypad will scroll through the following displays:
Armed Armed Armed Armed Armed Armed Armed Armed
area 1 area 2 area 3 area 4 area 5 area 6 area 7 area 8
If only partitions 1, 2, 3, 4, 6, and 8 are armed, the Master keypad
will scroll through the following displays:
Armed Armed Armed Armed Ready to Arm Armed Ready to Arm Armed
area 1 area 2 area 3 area 4
area 5
area 6
area 7
area 8

Displays for partitions that are Not Ready will display in the same
manner.
The chart at the bottom of this page will help you understand what
each LED function of the Master keypad represents.

7.6.3 Single Partition Mode
Single Partition Mode is used to control partitions on a “one at a
time/one by one” basis from the Master keypad.
To enter the Single Partition Mode, enter your [PIN], then press the
[#] key twice. This will call up the first partition you have access to.
Enter the command sequence you wish for this partition. You do
not need to use your PIN again. To move on to the next partition you
have access to, press the [#] key twice.
To exit the Single Partition Mode, hold the [*] key down for 2 seconds.
The system will also automatically drop out of Single Partition
Mode after 40 seconds without a keypad entry.
Example of accessing Single Partition Mode
• Enter your [PIN], followed by the [#] key twice: [1] [2] [3] [4] [#] [#].
LED
Armed
(red)
Status
(green)
Power
(green)
Fire
(red)

Off
All partitions are disarmed.
Not ready to arm (if the Armed LED is
On, all partitions are armed).
The Control Panel has lost all power;
no AC or battery.
There are no fire alarms.

DS7400Xi ( 4+) Reference Guide

• The first partition you have access to will be displayed: “Ready
to Arm. Cafeteria.”
• Complete the command sequence (in this case arming) you
wish for this partition: [#] [On].
• Move to the next partition you have access to by pressing the [#]
key twice: [#] [#].
• The next partition you have access to will be displayed: “Ready
to Arm. Office.”
• Complete the command sequence you wish for this partition.
• After you have completed all the command sequences for the
partitions you have access to, exit Single Partition Mode by
pressing the [*] key for two seconds.

7.6.4 Arming from the Master Keypad
To arm all the Partitions to which you have access:
• [PIN] + any Arming Command Sequence. This will arm all the
partitions to which you have access even if they are already
armed.
To arm only some of the Partitions to which you have access:
• [PIN] + [#] + [#]. This puts you into Single Partition Mode.
• The first partition to which you have access is displayed: “Ready
to Arm. Cafeteria.”
• Enter the Arming Command Sequence you want for this partition.
• [#] + [#] opens the next partition to which you have access.
• The next partition to which you have access is displayed: “Ready
to Arm. Office.”
• Enter the Arming Command Sequence you want for this partition.
• After arming any or all partitions to which you have access, you
may exit Single Partition Mode by holding the [*] key for at least
two seconds. The system will also drop out of Single Partition
Mode after 40 seconds without a keypad entry.

7.6.5 Disarming from the Master Keypad
To disarm all the Partitions to which you have access:
• [PIN] + [Off]. This will disarm all the partitions to which you have
access even if they are already disarmed.
To disarm only some of the Partitions to which you have access:
• [PIN] + [#] + [#]. This puts you into Single Partition Mode.
• The first partition to which you have access is displayed: “Armed.
Cafeteria.”
• If you wish to disarm this partition, enter [Off]. If not, go to the next
step.
• [#] + [#] opens the next partition to which you have access.
• The next partition to which you have access is displayed: “Armed.
Office.”
• If you wish to disarm this partition, enter [Off]. If not, go to the next
step.
• After disarming any or all partitions to which you have access,
you may exit Single Partition Mode by holding the [*] key for at

Flashing
One or more partitions are armed, or
an alarm has occurred.
One or more zones are bypassed.

On
All Partitions are armed, and no
alarms have occurred.
All partitions are ready to arm.

Control Panel problems exist.
See Error Displays.

Normal Operation.
The Control Panel is running on AC
power with no problems,
A fire trouble condition exists.

A fire zone is in alarm.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 29

least two seconds. The system will also drop out of Single Partition Mode after 40 seconds without a keypad entry.

7.7

Keypad Error Displays

7.7.1 General Information
Display
DS7445/DS7445i: Power LED flashing
DS7447/DS7447E: Control Trouble Enter #87
DS7445/DS7445i: LED 1 On
DS7447/DS7447E: AC Power Failure
DS7445/DS7445i: LED 2 On
DS7447/DS7447E: Battery Trouble*

DS7445/DS7445i: LED 3 On
DS7447/DS7447E: Communicator Err**
DS7445/DS7445i: LED 4 On
DS7447/DS7447E: System Fault
DS7445/DS7445i: LED 5 On
DS7447/DS7447E: Keypad Fault
DS7445/DS7445i: LED 6 On
DS7447/DS7447E: Keypad Tamper
DS7445/DS7445i: LED 7 On
DS7447/DS7447E: Multiplex Bus
DS7445/DS7445i: LED 8 On
DS7447/DS7447E: Aux. Power Fault
DS7445/DS7445i: not applicable
DS7447/DS7447E: Zone Trouble

DS7445/DS7445i: not applicable
DS7447/DS7447E: RF
DS7445/DS7445i: not applicable
DS7447/DS7447E: Dirty Chamber

Meaning
There is an Error Message. To
display the message, enter [PIN] + [#]
[8] [7].
There is a power failure, and the
panel is operating on backup battery
power.
If the system has just been through a
power failure, wait at least two hours
for the battery to recharge, the enter
[PIN] + [System Reset] to perform a
battery test,
The communicator failed to
communicate with the Central
Station.
Internal error in the control circuitry or
optional circuitry. See System Faults.
One of the keypads is not responding
to the Control Panel.
One of the keypad housings has
been opened.
The multiplex bus is defective or has
been shorted.
The auxiliary power has been
shorted.
One of the zones is not responding to
the Control Panel. This may also be
displayed during power-up; if so,
ignore it.
Indicates a problem with an RF
(wireless) zone.
One of the multiplex smoke detectors
has failed the sensitivity test and may
require cleaning or replacement. The
keypad beep may be cleared by
entering [PIN] + [Off].

Error Displays can only be read when the control is disarmed.
Some Control Panel Errors, such as battery trouble and any RF
troubles, will cause the keypad sounders to beep every 10 seconds.
The keypad sounders may be silenced for 4 hours by entering:
[PIN] + [Off].
The sounders will continue to resound until the problem is fixed.
To Clear a display, enter:
[PIN] + [System Reset].
Clear the Error Display only on the advice of your
installing company or if you are certain the problem
has been remedied.
NOTE:

System faults may be read from any keypad because they
are system-wide. All other Error Displays are limited to
the partition the standard keypad is in. If you are on a
Master keypad, you may read Error Displays one partition
at a time.

7.7.2 System Faults
System faults are designated as follows:

Page 30

P/N: F01U035325-01

[#] [8] [7] will display

[#] [8] [9] will
display

RAM Fault

System Fault 01

ROM Fault

System Fault 02

EEPROM Fault

System Fault 03

Ground Fault

System Fault 04

2Ph/Bell Fault = loss of communication to
DS7420i

System Fault 10

Line 1 Fault = DS7420I phone line 1 fault

System Fault 11

Line 2 Fault = DS7420I phone line 2 fault

System Fault 12

Bell Fault = DS7420i bell circuit fault

System Fault 13

Aux. Relay Fault = DS7420I auxiliary relay
fault

System Fault 14

Oct. Relay Fault = loss of communication to
DS7488

System Fault 20

Reserved for older panels

System Fault 50

AR IB Queue Full = modem buffer full

System Fault 51

AR Host Down = network data switch down

System Fault 52

AR Unreg. Modem = modem not registered

System Fault 53

AR Power Fail = power source below
defined threshold

System Fault 54

AR Network Lost = loss of network

System Fault 55

AR Modem HW Err = modem hardware
error

System Fault 56

AR Modem SW Err = modem software
error

System Fault 57

AR Opt. Bus Err = loss of communications
to ARDIS module

System Fault 58

AR Corrupt MSG = message error

System Fault 59

7.7.3 Event History
The History Buffer stores the last 400 events in memory. The
DS7447/DS7447E can display all of these events. If this test is
performed from a Master keypad, it must be in Single Partition
Mode. The DS7445/DS7445i will only display those zones (1-8)
that have alarmed since the last Event History Readback. The
RF3341 cannot display history events.
To readback the Event History Buffer:
• Press [PIN] + [#] [8] [9]. On a DS7447/DS7447E keypad, the last
event to take place will be displayed. On a DS7445/DS7445i
keypad, the zone LEDs for any zones that have alarmed since
the last Event History Readback in that partition will flash.
• Scroll through the events using the [9], [6], and [#] keys as follows:
To begin scrolling back through the events, press the [#] key. The
[#] key will scroll you back through the history line by line. The [9]
key will scroll you back in reverse chronological order by event. A
[6] will scroll you back up through the events (toward the most
recent) by event.
Each event consists of two or three lines or display screens. The
first line/screen will be the event title and user. The second line/
screen will be the date of the event or the change being made. If
there is a third line/screen, it will be the date of the change.
NOTE: When performing this from a Master keypad, each partition
will display its own history.
• To exit the Event History Mode, press the [*] key or wait 20 seconds
and the keypad will exit automatically.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

7.8

Testing Your System

7.8.1 Zone (System Walk) Test
The Zone Test is used to confirm that detectors will report alarms
to the keypad. A Zone Test works on all zones, except 24-hour
zones and fire zones. While the keypad is in a Zone Test, no control
panel alarms will activate an alarm, except 24-hour zone alarms
and fire alarms; these will override the Zone Test function.
To perform a Zone Test:
• Press [PIN] + [#] [8] [1].
- The DS7445/DS7445i zone LEDs of any untested zones will
flash.
- The DS7447/DS7447E displays “Test Zone” followed by the
zone number of any zones that have not been tested.
• Pick any untested zone and manually cause a detector to alarm
using a method specified in the detector’s Installation
Instructions.
- The DS7445/DS7445i zone LED for the zone currently being
tested will turn on steady.
- The DS7447/DS7447E displays “Now Testing” followed by
the zone number of the zone that is currently being tested.
• Clear the alarm condition from the detector using a method
specified in the detector’s Installation Instructions, and trigger
an alarm on the next detector in that zone. Continue until all
detector’s in that zone have been tested.
- As each zone is tested, its DS7445/DS7445i zone LED turns
off.
- As each zone is tested, the DS7447/DS7447E display returns
to “Test Zone” and indicates the remaining untested zones.
• Test each zone.
• Exit the Zone Test using [PIN] + [#].

7.8.2 Battery Tests
You may perform a test of the battery and the local sounder or just
test the battery. If these tests are performed from a Master keypad,
it must be in Single Partition Mode. System Tests are not available
from RF (wireless) keypads.
To initiate a Local Battery / Sounder Test:
• Press [PIN] + [#] [8] [5]. All keypad LEDs will turn on. The keypad
sounder and all alarm sounding devices will operate for two
seconds. If the test fails, the control panel will indicate a control
problem. See Error Displays on page 30.
NOTE: If power in your building has been off recently, wait two
hours for the battery to recharge and then try again.
To initiate a Battery Test:
• Press [PIN] + [System Reset]. The control panel will perform a
battery test. The control panel will report a Low Battery or a Low
Battery Restoral if necessary.

To initiate a Communicator Test:
• Press [PIN] + [#] [8] [2]. A long beep will sound. A “Test” report is
sent to the monitoring service. If the test fails, the keypad sounder
will sound continuously. To silence the sounder, press [System
Reset].
NOTE:

This test may take several minutes to complete because
the control panel will try ten attempts.

7.8.4 Fire Walk Test
This test is used to confirm that Smoke detectors will report alarms
to the keypads. The Fire Walk Test tests all fire zones, including
verified fire and waterflow.
At the start of the Fire Walk Test a Fire Walk Test report, if
programmed, is sent to the central station. Fire alarm reports are
not sent to the central station during the Fire Walk Test. A Fire Walk
Test restoral is sent upon completion of the Fire Walk Test.
The Fire Walk Test is enabled for 20 minutes once it is started. The
test time is extended to 20 minutes every time another zone is
tested.
When a fire zone is tested, any output programmed to follow that
zone will activate for 5 seconds.
To perform a Fire Walk Test:
• Press [PIN] + [#] [9] [1].
- The DS7445/DS7445i zone LEDs of any untested zones will
flash.
- The DS7447/DS7447E displays “Fire Test” followed by the
zone number of any zones that have not been tested.
• Pick any untested zone and manually cause a detector to alarm
using a method specified in the detector’s Installation
Instructions.
- The DS7445/DS7445i zone LED for the zone currently being
tested will turn on steady.
- The DS7447/DS7447E displays “Fire Testing” followed by
the zone number of the zone that is currently being tested.
• Clear the alarm condition from the detector using a method
specified in the detector’s Installation Instructions, and trigger
an alarm on the next detector in that zone. Continue until all
detector’s in that zone have been tested.
- As each zone is tested, its DS7445/DS7445i zone LED turns
off.
- As each zone is tested, the DS7447/DS7447E display returns
to “Fire Test” and indicates the remaining untested zones. *
• Test each zone as instructed by your installing company.
• Exit the Zone Test using [PIN] + [#].
NOTE:

A Fire Walk Test will prevent the system from sending any
Fire Reports during the test.

7.8.3 Communicator Test
This test is available only if the system transmits alarms and system
information to a monitoring service, and has been programmed by
the security installing company to permit communicator tests. This
test can be performed from a Master Keypad. The account code for
partition #1 will be used. System Tests are not available from RF
(wireless) keypads.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 31

8.0

How to Program the Control Panel

8.1

Entering the Programmer’s Mode

To enter the Programmer’s Mode, enter the Programmer’s Code followed by [#] [0]. Shorting the program pads (see section 2.0 for
location) on the control panel will also activate Programmer’s Mode.
NOTE:

The factory set default Programmer’s Code is [9] [8] [7] [6]. If the system has been reprogrammed for 6-digit PINs, the default
Programmer’s Code will be [9] [8] [7] [6] [5] [4].

8.2

Reading Back a Program Address

Once you are in the programmer’s mode, to read back the value of a Program Address, enter that Program Address followed by [#]. Each
data digit is displayed one data digit at a time. To view the second data digit, enter the # button again.
The display will look like this:

8.3

Entering a Value in a Program Address

To enter a value in the Program Address, enter the Program Address, then enter the value for each Data Digit, then enter [#] to save it and
move on to the next Program Address. Entering data digit 1 will increment you to the next data digit.
The display will show the Program Address and will display the value of each Data Digit after you enter it. The data will be programmed
(saved) when you press the [#] key. The control panel will automatically increment to the next program address.
• If you wish to program that next address, enter the necessary information.
• If you wish to read back the value of that address, press the [#] key.
• If you wish to program a different address, press the [*] key two times and enter the program address you wish to program.
If you make a mistake at any time, press the [*] key two times (before pressing the [#] key). This will clear the display, allowing you to enter
the program address you wish to work with.

8.4

HEX values

Some Data Digit values will be higher than 9. These values must be programmed by pressing the [*] key followed by some other
number. These values will display as HEX characters (A - F) when entered. Example: entering *0 at the keypad will display an A.
The HEX character values are as follows:
*0 = A *1 = B *2 = C *3 = D *4 = E

8.5

*5 = F

Defaults

The DS7400Xi is shipped from the factory as a working, pre-programmed control. Many of the programming addresses may already be
set to the values you need. The default values are shown in Reverse Print .
If the value you would like is in Reverse Print , you don’t need to re-program this address.
In the example, a “0” is the default value:

If the default value is not shown in Reverse Print , it will be shown in a separate table.

8.6

Setting the Control to the Factory Default
Only enter [0] [1] [#] in Program Address 4058 when you are completely sure you want to erase all installer programming. Entering [0] [1] [#] in Program Address 4058 will immediately reset the control to the factory default. Any
programming already done by the installer will be erased. This action cannot be reversed.

To set the control’s programming values back to the default, enter the programming mode, then enter [4][0][5][8][0] [1] [#].

8.7

Exiting the Programmer’s Mode

To exit the Programmer’s Mode, press the [*] key for a minimum of 2 seconds. If no keypad entries are made for 4 minutes, the control
will automatically exit you from the Programmer’s Mode.
Page 32

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

9.0

Understanding the Programming Charts

The Programming Reference Guide makes use of three types of charts. Each is described below.
If the chart looks like this, a combination of features is available to be programmed for that particular address.

Enter the Data Digit as a:
Select Options

Enter one of these numbers
for the appropriate data digit

0 1 2 3 4 5 6 7

Feature 1
Feature 2

The dots represent which
options/features are included
with each selection

Feature 3
Feature 4

Example:
To select Feature 2 only,
enter the data digit as a 1.
To select Feature 2 and
Feature 4,
enter the data digit as a 5.

Identifies the options/features
available for this address

If the chart looks like this, only a single feature is available to be programmed for that particular address.

Select Option
Represents the option/feature
available for this address.
Example:
To select Disabled,
enter the data digit as a 0.
To select Entry/Exit Delay #2,
enter the data digit as a 4.

DD

Disabled
Perimeter Instant

0
1

24-Hour

2

Entry/Exit Delay #1

3

Entry/Exit Delay #2

4

Enter one of these numbers
for the appropriate data digit
Some pages may also include a Default chart that looks like this:

DS7400Xi ( 4+) Reference Guide

Zone Function

Address

Default

1
2
3

0001
0002
0003

23
24
21

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 33

10.0

Programming

10.1

General Control Programing: Program Address (0000)

General Control programming defines the system-wide general operating parameters. See Glossary (section 6.1) for further details.
Normal Arming Custom Arming Perimeter Instant Arming Perimeter Arming Maximum Security Arming Closing Ring Back Siren on Communication Fail Restore Swinger Shunts

Data Digit
Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Select Options

1

2

Allow Normal and Custom Arming**

Allow Perimeter Instant Arming**
Allow Perimeter Arming**
Allow Maximum Security Arming**

Closing Ring-Back
Siren on Comm. Fail for Silent Zone

50 Hz. operationΔ
60 Hz. operation
Δ = For installations in North America, select 60 Hz. operation.
*0 - *5 are Hex values. They will display as A - F at the keypads.

Enter DD as a:
Select Options

0 1 2

3 4 5

6

7

8

Restore zone when Sounders Silence
Restore zone when Zone Restores
Restore zone when System is Disarmed
Allow Swinger Shunts. Send Bypass Reports
Allow Swinger Shunts. No Bypass Reports
** =

• Normal Arming = [PIN] + [On]: If programmed, Normal Arming arms the entire system while allowing entry delays for entry/
exit zones.
• Perimeter Instant Arming = [PIN] + [No Entry] + [Perimeter Only]: If programmed, Perimeter Instant Arming arms only the
perimeter of the system and does not allow entry delays for entry/exit zones.
• Perimeter Arming = [PIN] + [Perimeter Only]: If programmed, Perimeter Arming arms only the perimeter of the system
while allowing entry delays for entry/exit zones.
• Custom Arming = [PIN] + [#] [4]: If programmed, Custom Arming allows custom arming of the system and bypasses the
zone functions specified in data addresses 2725-2728.
• Maximum Security Arming = [PIN] + [No Entry] + [On]: If programmed, Maximum Security Arming arms the entire system
and does not allow entry delays for entry/exit zones.

Page 34

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Programming a Zone
Programming a Zone is a four step process. These steps must be performed, in order, to program a zone.
•
•
•
•

Step 1 is programming Zone Functions (what the zone will do in alarm),
Step 2 is assigning a Zone Function to the zone.
Step 3 is assigning a Zone Type to the zone.
Step 4 is assigning the zone to a partition.

Step 1: Programming the Zone Functions
10.2

Zone Function Programming: Program Addresses (0001-0030)

A Zone Function is the description of how a zone will behave. Up to 30 different Zone Functions may
be programmed. You may use the default values (which are already programmed into the panel) and
skip this step, or change the defaults, or add new Zone Functions. See section 6.2 for further
details.

Data Digit

1

2

Enter the Data Digit as a:

Select Options

0 1 2 3 4 5 6

7 *2 *3 *4 *5
Select Option

Invisible Alarm
Silent Alarm
Steady Alarm Output
Pulsing Alarm Output
Alarm on Short
Alarm on Open
Trouble on Open**
Trouble on Short
*2 - *5 are Hex values. They will display as C - F at the keypads.

** = Only when disarmed. When armed, this becomes Alarm on Open or Short for
non-24-hour zones. Note: Multiplex contacts (DS7450 and DS7452) should
not be programmed for Trouble on Open.
Value Zone
(fill in) Funct. Address
1

0001

2

0002

3

0003

4

0004

5

0005

6

0006

7

0007

8

0008

9

0009

10

0010

11

0011

12

0012

13

0013

14

0014

15

0015

16
to
30

0016
to
0030

DS7400Xi ( 4+) Reference Guide

Default Values
(Will be forced to different values when in
Commercial Fire Mode. See section 10.18.3)
2 = Steady alarm output, alarm on short and open.
3 = Entry/exit delay 1.
2 = Steady alarm output, alarm on short and open.
4 = Entry/exit delay 2.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
5 = Interior entry/exit follower.
2 = Steady alarm output, alarm on short and open.
6 = Interior home/away.
2 = Steady alarm output, alarm on short and open.
7 = Interior Instant.
2 = Steady alarm output, alarm on short and open.
2 = 24-hour.
7 = Pulsing alarm output, alarm on short, trouble on open.
*0 = Fire zone with verification.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.
2 = Steady alarm output, alarm on short and open.
1 = Perimeter Instant.

DD

Interior Delayed

0

Perimeter Instant

1

24-Hour

2

Entry/Exit Delay #1

3

Entry/Exit Delay #2

4

Interior Entry/Exit Follower

5

Interior Home/Away

6

Interior Instant

7

Day Monitor

8

Keyswitch (See note below)

9

Fire Zone with verification

*0

Fire Zone w/out verification

*1

Waterflow

*2

Supervisory

*3

Entry/Exit Delay Cancel 1

*4

Entry/Exit Delay Cancel 2

*5

9
Note: If digit 2 = 9 (keyswitch), use
this chart for digit 1.

Select Option

DD

Single Partition-No Force Arm

0

Single Partition-Can Force Arm

1

All Partitions-No Force Arm

2

All Partitions-Can Force Arm

3

An open loop will always produce
a steady alarm response.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 35

Step 2:

Assigning a Zone Function to the Zone

In this step, a Zone function is assigned to the Zone.

10.3

Zone Programming: Program Addresses (0031-0278)

In Zone Programming, each zone is defined according to its input (single or multiple zone input, or a DS7465) and its Zone Function
(1-30) or Output Function (1-24). The DS7465’s relay is the only device that will follow the output functions; its input loop will follow a zone
function. All single and multiple zone inputs will follow a zone function. See section 6.3 for further details.

Data Digit

1

2

Zone
Function
Value

Options
The DS7465 occupies two zones. The odd numbered
zone of the zone pair is the input zone. The even
numbered zone of the zone pair is the output relay.
The output follows an output function.

00

Disable a zone
Enter a Zone Function Value

01-30

Zone Number

Address

Zone
Function
Default

1
2
3
4
5
6
7
8
9-248

0031
0032
0033
0034
0035
0036
0037
0038
0039-0278

01
02
03
04
05
06
07
08
00

Hint: Address = Zone Number + 30

Page 36

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Step 3:
10.4

Assigning a Zone Type to the Zone

Zone Programming: Zone Type Program Addresses (0415-0538)

In Zone Programming, each zone is defined according to its Input (single or multiple zone input, or a DS7465) and its Zone Function
or Output function (1-24). The DS7465’s relay is the only device that will follow the output functions; its input loop will follow a zone
function. All single and multiple zone inputs will follow a zone function. See section 6.3 for further details.

Select Option

DD

DD

(zones 1-8 on the control, multiplex contacts,
sensors, or a DS7457)

0

Multiple Zone Input

1

(any zone that is on a DS7432, DS7433, or DS7460)

DS7465 Connections
(the input zone or the output relay on a DS7465)

IMPORTANT

1

MX280THL Multiplex Smoke Detectors
with Low Temperature Alarm

4

0

2

If Data Digit 1 is 2

2

Data Digit 2 MUST be 2

The D7465 occupies two zones. The odd
numbered zone of the zone pair is the input
zone. The even numbered zone of the zone
pair is the output relay.

3

Single Zone Input

1

2

MX280, MX280TH Multiplex Smoke Detectors

IMPORTANT

Select Option

Data Digit

Single Zone Input

(zones 1-8 on the control, multiplex contacts,
sensors, or a DS7457)

Multiple Zone Input
(any zone that is on a DS7432, DS7433, or DS7460)

DS7465 Connections
(the input zone or the output relay on a DS7465)

The D7465 occupies two zones. The odd
numbered zone of the zone pair is the input
zone. The even numbered zone of the zone
pair is the output relay.

If Data Digit 1 is 4
Data Digit 2 MUST be 4

3

MX280, MX280TH Multiplex Smoke Detectors

4

MX280THL Multiplex Smoke Detectors
with Low Temperature Alarm

The MX280THL occupies two zones. The odd
numbered zone of the zone pair is the smoke
detector. The even numbered zone of the zone
pair is the Low Temperature Alarm.

The MX280THL occupies two zones. The odd
numbered zone of the zone pair is the smoke
detector. The even numbered zone of the zone
pair is the Low Temperature Alarm.

5

Keyfob

Keyfob

Zones

Address

Zones

Address

Zones

Zones 1 & 2
Zones 3 & 4
Zones 5 & 6
Zones 7 & 8
Zones 9 & 10
Zones 11 & 12
Zones 13 & 14
Zones 15 & 16
Zones 17 & 18
Zones 19 & 20
Zones 21 & 22
Zones 23 & 24
Zones 25 & 26
Zones 27 & 28
Zones 29 & 30
Zones 31 & 32
Zones 33 & 34
Zones 35 & 36
Zones 37 & 38
Zones 39 & 40
Zones 41 & 42
Zones 43 & 44
Zones 45 & 46
Zones 47 & 48
Zones 49 & 50
Zones 51 & 52
Zones 53 & 54
Zones 55 & 56
Zones 57 & 58
Zones 59 & 60
Zones 61 & 62
Zones 63 & 64

0415
0416
0417
0418
0419
0420
0421
0422
0423
0424
0425
0426
0427
0428
0429
0430
0431
0432
0433
0434
0435
0436
0437
0438
0439
0440
0441
0442
0443
0444
0445
0446

Zones 65 & 66
Zones 67 & 68
Zones 69 & 70
Zones 71 & 72
Zones 73 & 74
Zones 75 & 76
Zones 77 & 78
Zones 79 & 80
Zones 81 & 82
Zones 83 & 84
Zones 85 & 86
Zones 87 & 88
Zones 89 & 90
Zones 91 & 92
Zones 93 & 94
Zones 95 & 96
Zones 97 & 98
Zones 99 & 100
Zones 101 & 102
Zones 103 & 104
Zones 105 & 106
Zones 107 & 108
Zones 109 & 110
Zones 111 & 112
Zones 113 & 114
Zones 115 & 116
Zones 117 & 118
Zones 119 & 120
Zones 121 & 122
Zones 123 & 124
Zones 125 & 126
Zones 127 & 128

0447
0448
0449
0450
0451
0452
0453
0454
0455
0456
0457
0458
0459
0460
0461
0462
0463
0464
0465
0466
0467
0468
0469
0470
0471
0472
0473
0474
0475
0476
0477
0478

Zones 129 & 130
Zones 131 & 132
Zones 133 & 134
Zones 135 & 136
Zones 137 & 138
Zones 139 & 140
Zones 141 & 142
Zones 143 & 144
Zones 145 & 146
Zones 147& 148
Zones 149 & 150
Zones 151 & 152
Zones 153 & 154
Zones 155 & 156
Zones 157 & 158
Zones 159 & 160
Zones 161 & 162
Zones 163 & 164
Zones 165 & 166
Zones 167 & 168
Zones 169 & 170
Zones 171 & 172
Zones 173 & 174
Zones 175 & 176
Zones 177 & 178
Zones 179 & 180
Zones 181 & 182
Zones 183 & 184
Zones 185 & 186
Zones 187 & 188
Zones 189 & 190
Zones 191 & 192

DS7400Xi ( 4+) Reference Guide

IMPORTANT

Address
0479
0480
0481
0482
0483
0484
0485
0486
0487
0488
0489
0490
0491
0492
0493
0494
0495
0496
0497
0498
0499
0500
0501
0502
0503
0504
0505
0506
0507
0508
0509
0510

Zones
Zones 193 & 194
Zones 195 & 196
Zones 197 & 198
Zones 199 & 200
Zones 201 & 202
Zones 203 & 204
Zones 205 & 206
Zones 207 & 208
Zones 209 & 210
Zones 211 & 212
Zones 213 & 214
Zones 215 & 216
Zones 217 & 218
Zones 219 & 220
Zones 221 & 222
Zones 223 & 224
Zones 225 & 226
Zones 227 & 228
Zones 229 & 230
Zones 231 & 232
Zones 233 & 234
Zones 235 & 236
Zones 237 & 238
Zones 239 & 240
Zones 241 & 242
Zones 243 & 244
Zones 245 & 246
Zones 247 & 248

IMPORTANT

5
Address
0511
0512
0513
0514
0515
0516
0517
0518
0519
0520
0521
0522
0523
0524
0525
0526
0527
0528
0529
0530
0531
0532
0533
0534
0535
0536
0537
0538

When using premises RF,
• zones 129-136 are reserved.
• zones 137-248 are available as RF zones
only! Wired zones can not reside in zones
137-248 when using RF.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 37

Step 4: Assigning a Partition to the Zone
10.5

Zone Partition Assignment: Program Addresses (0287-0410)

In Zone Partition Assignment, each zone is assigned to a partition. By default, all zones are assigned to partition 1.
The partition assignment for odd numbered zones is programmed in the first data digit of these addresses. The partition assignment
for even numbered zones is programmed in the second data digit of these addresses.
For example, to assign zone 1 to partition 1 and zone 2 to partition 2, program address 0287 as 01.

Zones

Address

Zones

Address

Zones

Zones 1 & 2
Zones 3 & 4
Zones 5 & 6
Zones 7 & 8
Zones 9 & 10
Zones 11 & 12
Zones 13 & 14
Zones 15 & 16
Zones 17 & 18
Zones 19 & 20
Zones 21 & 22
Zones 23 & 24
Zones 25 & 26
Zones 27 & 28
Zones 29 & 30
Zones 31 & 32
Zones 33 & 34
Zones 35 & 36
Zones 37 & 38
Zones 39 & 40
Zones 41 & 42
Zones 43 & 44
Zones 45 & 46
Zones 47 & 48
Zones 49 & 50
Zones 51 & 52
Zones 53 & 54
Zones 55 & 56
Zones 57 & 58
Zones 59 & 60
Zones 61 & 62
Zones 63 & 64

0287
0288
0289
0290
0291
0292
0293
0294
0295
0296
0297
0298
0299
0300
0301
0302
0303
0304
0305
0306
0307
0308
0309
0310
0311
0312
0313
0314
0315
0316
0317
0318

Zones 65 & 66
Zones 67 & 68
Zones 69 & 70
Zones 71 & 72
Zones 73 & 74
Zones 75 & 76
Zones 77 & 78
Zones 79 & 80
Zones 81 & 82
Zones 83 & 84
Zones 85 & 86
Zones 87 & 88
Zones 89 & 90
Zones 91 & 92
Zones 93 & 94
Zones 95 & 96
Zones 97 & 98
Zones 99 & 100
Zones 101 & 102
Zones 103 & 104
Zones 105 & 106
Zones 107 & 108
Zones 109 & 110
Zones 111 & 112
Zones 113 & 114
Zones 115 & 116
Zones 117 & 118
Zones 119 & 120
Zones 121 & 122
Zones 123 & 124
Zones 125 & 126
Zones 127 & 128

0319
0320
0321
0322
0323
0324
0325
0326
0327
0328
0329
0330
0331
0332
0333
0334
0335
0336
0337
0338
0339
0340
0341
0342
0343
0344
0345
0346
0347
0348
0349
0350

Zones 129 & 130
Zones 131 & 132
Zones 133 & 134
Zones 135 & 136
Zones 137 & 138
Zones 139 & 140
Zones 141 & 142
Zones 143 & 144
Zones 145 & 146
Zones 147& 148
Zones 149 & 150
Zones 151 & 152
Zones 153 & 154
Zones 155 & 156
Zones 157 & 158
Zones 159 & 160
Zones 161 & 162
Zones 163 & 164
Zones 165 & 166
Zones 167 & 168
Zones 169 & 170
Zones 171 & 172
Zones 173 & 174
Zones 175 & 176
Zones 177 & 178
Zones 179 & 180
Zones 181 & 182
Zones 183 & 184
Zones 185 & 186
Zones 187 & 188
Zones 189 & 190
Zones 191 & 192

Select Option

DD

Belongs to Partition 1

Page 38

Belongs to Partition 2

1

Belongs to Partition 3

2

Belongs to Partition 4

3

Belongs to Partition 5

4

Belongs to Partition 6

5

Belongs to Partition 7

6

Belongs to Partition 8

7

P/N: F01U035325-01

Address
0351
0352
0353
0354
0355
0356
0357
0358
0359
0360
0361
0362
0363
0364
0365
0366
0367
0368
0369
0370
0371
0372
0373
0374
0375
0376
0377
0378
0379
0380
0381
0382

Zones
Zones 193 & 194
Zones 195 & 196
Zones 197 & 198
Zones 199 & 200
Zones 201 & 202
Zones 203 & 204
Zones 205 & 206
Zones 207 & 208
Zones 209 & 210
Zones 211 & 212
Zones 213 & 214
Zones 215 & 216
Zones 217 & 218
Zones 219 & 220
Zones 221 & 222
Zones 223 & 224
Zones 225 & 226
Zones 227 & 228
Zones 229 & 230
Zones 231 & 232
Zones 233 & 234
Zones 235 & 236
Zones 237 & 238
Zones 239 & 240
Zones 241 & 242
Zones 243 & 244
Zones 245 & 246
Zones 247 & 248

Address
0383
0384
0385
0386
0387
0388
0389
0390
0391
0392
0393
0394
0395
0396
0397
0398
0399
0400
0401
0402
0403
0404
0405
0406
0407
0408
0409
0410

Data Digit

1 = odd numbered zones
2 = even numbered zones

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.6

Zone Bypass Programming: Program Addresses (2721-2724)

Zone Bypass programming determines which zone functions can be bypassed. Zone functions that can not be bypassed can not be
force armed either. Fire zones can never be manually bypassed, but can be force armed. The Default of [0] or [8] means those zones can
be bypassed.

PA 2721
Data Digit

Note: This programming item does not affect Custom Arming Programming (PA 2725-2778) or
Swinger Shunt Bypasses (see programming for Program Address 0000).

1

2

Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Select Options
Zone Function 1 Can Be Bypassed
Zone Function 2 Can Be Bypassed
Zone Function 3 Can Be Bypassed
Zone Function 4 Can Be Bypassed

*0 - *5 are Hex values. They will display as A - F at the keypads.

Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Select Options
Zone Function 5 Can Be Bypassed
Zone Function 6 Can Be Bypassed
Zone Function 7 Can Be Bypassed
Zone Function 8 Can Be Bypassed

*0 - *5 are Hex values. They will display as A - F at the keypads.

PA 2722
Data Digit

1

2

Enter the Data Digit as a:
Select Options

0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Zone Function 9 Can Be Bypassed
Zone Function 10 Can Be Bypassed
Zone Function 11 Can Be Bypassed
Zone Function 12 Can Be Bypassed
*0 - *5 are Hex values. They will display as A - F at the keypads.

Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Select Options
Zone Function 13 Can Be Bypassed
Zone Function 14 Can Be Bypassed
Zone Function 15 Can Be Bypassed
Zone Function 16 Can Be Bypassed

*0 - *5 are Hex values. They will display as A - F at the keypads.
DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 39

PA 2723
Data Digit

1

2

Enter the Data Digit as a:
Select Options

1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Zone Function 17 Can Be Bypassed
Zone Function 18 Can Be Bypassed
Zone Function 19 Can Be Bypassed
Zone Function 20 Can Be Bypassed
*0 - *5 are Hex values. They will display as A - F at the keypads.

Enter the Data Digit as a:
Select Options

0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Zone Function 21 Can Be Bypassed
Zone Function 22 Can Be Bypassed
Zone Function 23 Can Be Bypassed
Zone Function 24 Can Be Bypassed
*0 - *5 are Hex values. They will display as A - F at the keypads.

PA 2724
Data Digit

1

2

Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Select Options
Zone Function 25 Can Be Bypassed
Zone Function 26 Can Be Bypassed
Zone Function 27 Can Be Bypassed
Zone Function 28 Can Be Bypassed

*0 - *5 are Hex values. They will display as A - F at the keypads.

Enter the Data Digit as a:
Select Options

0 1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Zone Function 29 Can Be Bypassed
Zone Function 30 Can Be Bypassed
*0 - *5 are Hex values. They will display as A - F at the keypads.

Page 40

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.7

Output Programming: Program Addresses (2734, 2735, 2736)

Output programming defines the event, partition, and type of alarm (burglary or fire) that will trigger each of the three physical outputs on
the control panel.
See section 3.0 for the location of the physical outputs on the control panel.
See Glossary (section 6.4) for further details.

Programmable Output 1 will
be ON for 10 seconds after
pressing [System Reset].
Programmable Output 2 will
be OFF for 10 seconds after
pressing [System Reset].

Select Option

0
ON during Entry Pre-Alert/Exit Warning
1
ON for 10 sec. after pressing [System Reset] 2
ON when system is Armed
3
System Status (ready to arm)
Zone Alarm
Zone Alarm delayed by 20 sec.

Options

DD

DD

Latch on ANY Zone Alarm**

Ground Start

3

Access Output (10 sec. pulse)

Armed Full

0
1

Keyfob

Armed Partial

2

Panic Duress Output***

*1

Armed Any

3

On during battery test

*3

Keypad Sounder Output

** = This includes invisible zones. See glossary for further details.
*** = See section 6.4 for description of this option.

Output

Address

Default

Alarm
Programmable Output 1
Programmable Output 2

2734
2735
2736

63
33
23

DS7400Xi ( 4+) Reference Guide

Options

DD

0
1

Disabled

4
5
6
7
8
9
*0

Disabled

Data Digit
1
2

Burglar Alarm

2
3

Fire Alarm
Burg and Fire Alarm

Data Digit
2
1
*0

Options

RF3334

0

Disabled
Momentary Option

Key

Toggle

Key

Option

Momentary Auxillary

Key

Toggle

Key

Copyright © 2007 Bosch Security Systems, Inc.

DD

Auxillary

P/N: F01U035325-01

1
2
3
4

Page 41

10.8

Output Partition Assignment: Program Addresses (2737-2738)

In Output Partition Assignment, each On-board output is assigned to a partition. By default, outputs are assigned to all partitions.

PA 2737
Data Digit

1

Output

DD

Address

Default

Belongs to Partition 1

0

2737-DD1
2737-DD2
2738-DD1

8
8
8

Belongs to Partition 2

1

Belongs to Partition 3

2

Belongs to Partition 4

3

Belongs to Partition 5

4

Belongs to Partition 6

5

Belongs to Partition 7

6

Belongs to Partition 8

7

Follows all Partitions

8

Alarm
Programmable Output 1
Programmable Output 2

10.9

Select Option

PA 2738
Data Digit

2

1

2

Keyfob Chirp
Options

DD

Chirp Disabled

0

Bell Output

1

P01

2
3

P02

Partition Control Programming: Program Address (3420)

Partition Control programming defines the number of partitions in use and the common area (common area can only be partition 1).
See Glossary (section 6.5) for further details.

Page 42

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.10 Quick Arm Control Programming: Program Address (3477)
Quick Arm Control programming defines which partitions can be quick armed (armed without requiring a PIN to be entered).

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 43

10.11 Keypad Assignment Programming: Program Addresses (3131-3138)
Keypad Assignment Programming is where you assign the keypad type and the partition to which it belongs.
See Glossary (section 6.6) for further details.
Each keypad must have its own Bus address. This must also be selected on the keypad via its address pins. See DS7445/
DS7447 Installation Guide (P/N: 22235). One keypad must be selected as keypad 1.
Defaults:

The default, if using only one keypad, is an Alpha keypad belonging to partition one.

Program Address 3131
Data Digit 1

Program Address 3132

Data Digit 2

Data Digit 1

Program Address 3133

Data Digit 2

Data Digit 1

Program Address 3134

Data Digit 2

Data Digit 1

Data Digit 2

Keypad 1*

Keypad 2

Keypad 3

Keypad 4

Keypad 5

Keypad 6

Keypad 7

Keypad 8

default = 1

default = 0

default = 0

default = 0

default = 0

default = 0

default = 0

default = 0

Program Address 3135
Data Digit 1

Program Address 3136

Data Digit 2

Data Digit 1

Program Address 3137

Data Digit 2

Data Digit 1

Program Address 3138

Data Digit 2

Data Digit 1

Keypad 9

Keypad 10

*
Keypad 11**

*
Keypad 12**

*
Keypad 13**

*
Keypad 14**

*
Keypad 15**

default = 0

default = 0

default = 0

default = 0

default = 0

default = 0

default = 0

Data Digit 2

* = When in Commercial Fire Mode, certain keypads must have specific assignments (see section
6.11).
** = Keypads 11-15 are connected to the Option Bus. If the DS7412 is connected to the Option Bus (at
keypad address 13 or 14), keypad 13 or 14 is unavailable. Similarly, if the DS7420i is connected to the
Option Bus at keypad address 15, keypad 15 is unavailable; and if the DS7488 is connected to the
Option Bus at keypad address 11-15, the corresponding keypad(s) is (are) unavailable.

Select Options
Disabled
Alpha (LCD) Keypad
LED Keypad
Master Keypad***

0 1 2 3

Select Options

Data Digit

1

2

0 1

LCD Backlight Always On
LCD Backlight Off Until Keypress
Backlight selection affects all LCD keypads

*** = If only using one partition, do not program keypads as Master Keypads.
Only program for a Master Keypad if you need to view multiple partitions from a
single keypad.

10.12 Keypad Partition Assignment: Program Addresses (3139-3146)

Page 44

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.13 Emergency Key Programming: Program Addresses (3147-3148)
Emergency Key and Panic Key programming disables or activates these keys (the A, B, and C keys) located on the keypads and/or
keyfobs.
It also determines a silent, pulsed, or steady alarm.
See Glossary (section 6.7) for further details.

PA 3147
Data Digit
Select Option
Fire Key

A

Fire Key Disabled
Fire Key = Disabled
Fire Key = Steady Alarm
Fire Key = Pulsed Alarm

Emergency Key

B

1

C
Panic Key Disabled
Panic Key = Silent Alarm
Panic Key = Steady Alarm
Panic Key = Pulsed Alarm

Select Option
DD
Special Emergency Key Disabled
0
Special Emergency Key = Silent Alarm
1
Special Emergency Key = Steady Alarm 2
Special Emergency Key = Pulsed Alarm 3
PA 3148
Data Digit

Panic Key

2

Armed

Perimeter

Status

Supervi sory

Power

Bell Silenced

Fire

Trouble

0

DD
0
1
2
3

2

1
2
3

May be forced to a different value when in
Commercial Fire Mode. See section 10.16.3.

Select Option

1

DD
0

1

2

3

4 5

6

7

8

9 10 11 12 13 14 15 16
TEST WEEKLY

On

1

2

3

Off

4

5

6

Perimeter
Only

7

8

9

No
Entry

*

0

#

Bypas s

Sys tem
Reset

Data Digit 2
must be 0

0
A

B

C

May be forced to a different value when in Commercial Fire Mode. See section 10.16.3.

10.14 Custom Arming Programming: Program Addresses (2725-2728)
See Glossary (section 6.8) for further details.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 45

10.14 Custom Arming Programming: Program Addresses (2725-2728) (Continued)

PA 2728
Data Digit

Enter the Data Digit as a:
Select Options

0 1 2 3

4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

1

2

Bypass Zone Function 25
Bypass Zone Function 26
Bypass Zone Function 27
Bypass Zone Function 28
Enter the
Data Digit
as a:

*0 - *5 are Hex values. They will display as A - F at the keypads.

Select Options

0 1 2 3

Bypass Zone Function 29
Bypass Zone Function 30
Page 46

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.15 Force Arming and Ground Fault Detect Programming: Program Address (2732)
Force Arming programming defines how many zones may be Force Armed using an Arming sequence followed by the [Bypass] key.
With this entry, all violated zones (up the programmed limit) will automatically be Force Armed (bypassed). Ground Fault Detect
programming determines whether or not the control will detect a ground fault condition.
See Glossary (sections 6.9 and 6.10) for further details.

Note: This limit does not apply when arming with
a keyswitch programmed with force arming enabled.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 47

10.16 Commercial Fire Mode Programming: Program Address (2733)
This section describes how to define the parameters for the Commercial Fire Mode.
See Glossary (section 6.11) for further details.

When programming Fire zones, it is recommended that they be zone functions 12 and 13 (see sections 10.2, 10.4 and 10.16.3).
10.16.1 When Central Station Commercial Fire Mode is chosen, address 4021 (DS7420i: Dual Phone Line/Bell Supervision Module Output Programming), will be forced to a value of 5.
10.16.2 When Local Commercial Fire Mode is chosen, address 4021 (DS7420i: Dual Phone Line/Bell Supervision Module Output
Programming),will be forced to a value of 3, 4, or 5. (Turns the Bell Monitor feature ON and the Alarm Output on Line Fault feature
OFF)
10.16.3 Regardless of which Commercial Fire Mode is chosen, the following parameters will be forced when exiting local
programmer’s mode:
• Zone Function 12, address 0012, will be a 7 *0. (Alarm on Short, Trouble on Open, Pulsing Fire with verification)
• Zone Function 13, address 0013, will be a 7 *1. (Alarm on Short, Trouble on Open, Pulsing Fire without verification)
• Zone Function 14, address 0014, will be a 7 *2. (Alarm on Short, Trouble on Open, Pulsing Water Flow)
• Zone Function 15, address 0015, will be a 7 *3. (Alarm on Short, Trouble on Open, Pulsing Supervisory)
• Zone Bypass address 2722 will not allow zone functions 12 - 15 to be bypassed.
• Emergency Key, address 3147, data digit 1, will become a 3 if programmed previously as a 2. Data digit 2 will become a 2 if
programmed previously as a 3.
• Panic Key, address 3148, data digit 1, will become a 2 if programmed previously as a 3.
• Fire Bell Cutoff, address 4032: If less than 5, set to 5, otherwise untouched.
• The AC Fail Report delay will be random between 6-12 hours regardless of the delay time programmed in 4034. Also, the AC Fail
Report will not be sent as a “tag-along.”
10.16.4 In Central Station Commercial Fire Mode, the following communication parameters will be forced:
Report Codes: If 0, the following defaults will be set, otherwise they will be unchanged.

• Phone Control (address 3156): If 0, set to 6 1, 4/2 @ 18/23, 10pps, otherwise untouched.
• Test Report (address 4026): Set to 8, call out every day.
Page 48

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.17 Open/Close Report Control Programming: Program Address (3149)

Data Digit

1

See Glossary (section 6.12) for further details.

2

Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9

Select Options
Do not report opens or closes
Report opens and closes in Partition 1
Report opens and closes in Partition 2
Report opens and closes in Partition 3
Report opens and closes in Partition 4

Send Closing and
Bypass reports at close

0

Send Closing and
Bypass reports after
exit delay

1

Report opens and closes in Partition 5

Data Digit

Report opens and closes in Partition 6

1

Report opens and closes in Partition 7

2

0

Report opens and closes in Partition 8
Report first Partition to open and last Partition to close**
** = When using this option, all partitions should have the same account code.

10.18 Open/Close & Zone Report Control Programming: Program Address (3151)
This section allows you to decide which phone number will send open and close reports, zone alarm, zone restoral, and zone trouble
reports.

10.19 Report Control Programming: Program Address (3152)
This section allows you to decide which phone number will send reports other than open/close reports and zone reports.

Select Option

DD

Alternate between both Phone Numbers

0

Report to Phone Number 1

1

Report to Phone Number 2

2

Report to Phone Number 1 and 2

3

DS7400Xi ( 4+) Reference Guide

Data Digit
2
1

Copyright © 2007 Bosch Security Systems, Inc.

0

NOTE:

Data Digit 1 does
not include Open
and
Close
Reports or Zone
Reports
(see
sections 10.17
and 10.18).

Data Digit 2
must be 0

P/N: F01U035325-01

Page 49

10.20 Timer Programming: Program Addresses (4028-4030, 4032-4033)

Entry and Exit Delay Timers are in
5 second intervals (the maximum
delay time is 255 seconds).

For example:
5 sec. = 01
15 sec. = 03
20 sec. = 04
30 sec. = 06
45 sec. = 09
60 sec. = 12
255 sec. = 51

Data Digit
1
2

Exit Delay Time
Address 4030
0 to 51 (0 to 255 sec.*) Default = 12 (60 sec.)
*5 second intervals

Data Digit
1
2

Data Digit
1
2
May be forced to a different value when in
Commercial Fire Mode. See section 10.18.3.

Entry Delay Time 1

Fire Bell Cutoff

Address 4028

Address 4032

0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)
*5 second intervals

0 to 99 minutes*

Default = 04 minutes

*1 minute intervals; 99 = 30 second cutoff
Data Digit
1
2

Data Digit
1
2

Entry Delay Time 2

Burglary Bell Cutoff

Address 4029

Address 4033

0 to 51 (0 to 255 sec.*) Default = 09 (45 sec.)

0 to 99 minutes*

Default = 04 minutes

*1 minute intervals; 99 = 30 second cutoff

*5 second intervals

10.21 AC Fail Report Delay Programming: Program Address (4034)
The AC Fail Delay Times are programmed as Hexadecimal values.
For example:
00 = Send only with next report
1 *4 = 30 minute delay
3 *2 = 60 minute delay
78 = 120 minute delay
*5 0 = 240 minute delay
*5 *5 = Random delay (at least 15 minutes, but less than 120 minutes)
(*0 - *5 are Hex values. They will display as A through F at the keypads.)
See Glossary (section 6.13) for further details.

Page 50

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.22 General Authority Programming: Program Address (3421-3424)
This allows for a user with a General Authority level to Arm, Disarm and Bypass specified zones.
See Glossary (section 6.1) for further details.
Program Address 3421

Select Option

Program Address 3423

Data Digit 1

Data Digit 2

Data Digit 1

Partition 1

Partition 2

Partition 5

Data Digit 2

Partition 6

DD

General Code can Arm, Disarm, and Bypass

0

General Code can Arm and Bypass

1

General Code can Arm and Disarm

2

General Code can Arm

3

Program Address 3422

Program Address 3424

Data Digit 1

Data Digit 2

Data Digit 1

Data Digit 2

Partition 3

Partition 4

Partition 7

Partition 8

10.23 Arming Warning Programming: Program Addresses (3425-3428)
Arming Warning programming defines whether the keypad will be audible during the exit delay and auto arm period. If programmed, the
keypad sounder will activate once every 5 seconds during the exit delay. At 10 seconds and 5 seconds remaining, the keypad sounder
will activate 3 times. During auto arming, a pre-arming period will begin 15 minutes before the system arms automatically. The keypad
sounders will pulse five times every minute. During the last five minutes before arming, these sounders will be on steady.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 51

10.24 DS7412 RS232 Interface Control Programming: Program Address (4019)
DS7412
RS232
Interface
Control
Programming allows you to enable or disable
the DS7412 and to select which history events
are sent to the printer as they occur. Selecting
“No Events” will cause the history to be printed
only on command.
To print the History Buffer starting from the most
recent event, enter the Master Code followed
by [#] [0] [8]. To stop printing, enter Master Code
[#] [0] [8] again.

10.25 DS7412 RS232 Interface Configuration Programming: Program Address (4020)
DS7412 RS232 Interface Configuration Programming allows you to configure the DS7412 for your printer. Most printers will operate
using the default values for the DS7412. Some printers may operate more efficiently using optional program values.
Consult the operating guide provided with your printer to be sure that its configuration matches
the one programmed here.
NOTE:

If using the WDSRP Direct Connection
option for programming, Address 4019
must be set for 1 0. Address 4020 must
be set for 2 5.

10.26 RS232 Carriage Return/Line Feed Control: Program Address (4027)
The RS232 Carriage Return/Line Feed (CR/LF) Control allows you to choose between sending carriage returns/line feeds or spaces to the DS7412 module. This is only used when Program Address 4019 Data Digit #2 is programmed with the numbers 1 through
7.

Data Digit

Select Option
Send CR/LF
Send Spaces

Page 52

P/N: F01U035325-01

DD
0
1

Copyright © 2007 Bosch Security Systems, Inc.

1

2

0
DS7400Xi (4+) Reference Guide

10.27 Report Programming: Program Addresses (3207-3419)
• To send the User number along with open, close, or partial close reports: place an ‘F’ (*5) in the extended digit.
• To disable a report (meaning that nothing will be sent), place a ‘0’ in the reporting digit.
• When using SIA or Contact ID format, place a ‘1’ in the reporting digit of each report you wish to enable. It is not necessary to program
the extended digit.
• For suggested values for 4/2, BFSK and Pager format, see section 12.1-12.3. For SIA and Contact ID, the values sent are listed in
sections 13.1 and 13.2. For other formats, consult your central station.
• HEX values: Some Data Digit values are higher than 9. These values are programmed by pressing the [*] key followed by another
number. These values will display as HEX characters when entered. The HEX character values are as follows:
*0 = A *1 = B *2 = C *3 = D *4 = E *5 = F
See Glossary (section 6.13) for further details.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 53

Report Programming (Continued)

Page 54

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Report Programming (Continued)

10.28 Phone/DS7416i Routing Control: Program Addresses (3153-3154)
If address 3155 is programmed to “Try DS7416i first”, the following addresses can be used to control report routing. If address 3155
is set to “Send alarms via both DS7416i and digital”, this will force alarms to go to the phone even if the Phone/DS7416i report
routing for alarms does not specify phone usage.
Phone/DS7416i report routing (3153).
First digit: Open and Close Reports.

Data Digit

1

Enter the DD as a:
Select Options
Use Phone
Use DS7416i

1 2

3 7 *1 *5
Enter the DD as a:

Use Either
Use Both
Try Phone First

Select Options
Use Phone
Use DS7416i

Second digit: Zone Alarm, Zone Restoral,
and Zone Trouble Reports.

1 2 3

7 *1 *5

Use Either
Use Both
Try Phone First

Phone/DS7416i report routing and Phone First count (3154)

Data Digit

1

First Digit: System Reports. Enter the DD as a:
Select Options
1 2 3 7 *1 *5
Use Phone
Use DS7416i
Use Either
Use Both
Try Phone First

2

2

Select Option DD Select Option DD Select Option DD Select Option DD

0 Attempts
1 Attempt
2 Attempts
3 Attempts

0
1
2
3

4 Attempts
5 Attempts
6 Attempts
7 Attempts

4
5
6
7

8 Attempts
9 Attempts
10 Attempts
11 Attempts

8
9
*0
*1

12 Attempts
13 Attempts
14 Attempts
15 Attempts

*2
*3
*4
*5

Second digit: Phone First count. Number of attempts before trying the DS7416i:
This value is used to control the number of attempts made on the phone line before switching to the DS7416i. This value is only
referenced if the “Use Phone”, “Use DS7416i”, and “Try Phone First” options are all selected. If the value is less than or equal
to 2, or more than 5, two attempts will be made on the phone before trying the DS7416i if the Phone First option is selected.
DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 55

10.29 Account Code Programming: Program Addresses (3429-3459)
Account Code programming defines the number transmitted to the central station that identifies this panel. It also identifies which
partition is reporting from this panel.

1. Account Codes are programmed from left to right. If programming a 3 digit Account Code, the fourth digit of the address must be “0.”
For example: If the Account Code is 121, program 1210 in the programming address.
2. If you wish to send a zero “0,” enter it as *0 (this does not apply to the added zero in a three digit Account Code).
For example: If the Account Code is 101, program 1*010 in the programming address. If the Account Code is 3050, program 3*05*0
in the programming address.

Page 56

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.30 Phone Number General Control Programming: Program Address (3155)
See Glossary (section 6.14) for further details.

Data Digit
Enter the Data Digit as a:
0 1 2 3 4 5 6 7 8 9 *0 *1

Select Options

1

2

Enable remote programmer call-back
Dial pulse on all phone numbers
Dial tone on all phone numbers**
Dial tone, switch to pulse if required
ΔΔ
Try DS7416i first
*0 - *1 are Hex values. They will display as A - B at the keypads.
ΔΔ = If this option is selected, see address 3153-3154.
** = Required on PBX systems

Select Options

0

Enter the Data Digit as a:
1 2 3 4 5 6 7 8 9 *0 *1 *2 *3 *4 *5

Dialer delay of 15 sec. on non-24H burglar alarms only**
Dialer delay of 15 sec. on 24H burglar & fire alarms only**

Send alarms via either DS7416i or digital Δ
ΔΔ

Send alarms via both DS7416i and digital Δ ***

Use 110 Baud comm. for WDSRP
Use 300 Baud comm. for WDSRP
*0 - *5 are Hex values. They will display as A - F at the keypads.
Δ = Only applicable when using the DS7416i option.
ΔΔ = If this option is selected, see address 3153-3154.
** = These selections can only be used with systems that have only one partition.
*** = This selection must be chosen for UL Listed Requirements when using the DS7416i module.

10.31 Phone Number Format Programming: Program Addresses (3156-3157)
NOTE:
Data Digit
Select Option
Phone Number Disabled
3/1 (no Extended Reporting)
3/1E (Extended Reporting)
3/1 with Parity
3/1E with Parity
4/1
4/2
BFSK
SIA 110 Baud
Contact ID
SIA 300 Baud
Personal Dialing
Pager

1

DD
0
1
2
3
4
5
6
7
8
9
*0
*2

Select Options

Enter the DD as a:
0 1 2 3 4 5

2

Phone Number 1 Format = Address
3156
Phone Number 2 Format = Address
3157
When using the DS7416i Advanced
Radio Communications Module:
Program address 3156 as:
data digit 1 = 9, data digit 2 = 1.
Program address 3157 as:
data digit 1 = 9, data digit 2 = 1.

1900 Hz. Data/1400 Hz. Acknowledge
1800 Hz. Data/2300 Hz. Acknowledge
BFSK, SIA, Contact ID
10 Pulses per Second (PPS)
20 Pulses per Second (PPS)
40 Pulses per Second (PPS)
*0, *2, and *5 are Hex values. They will display as A, C, and F

at the keypads.

*5

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 57

10.31.1 Compatible Receivers
The following table lists those Digital Alarm Communicator Receivers and Formats that
are compatible with the DS7400Xi.
NOTE:

Contact your central station regarding which format to use and if a special line card
is required.

l = The Format type the DS7400Xi
supports and the Digital Alarm
Communicator Receiver accepts.

10.32 Phone Answering Programming: Program Address (3158)
See Glossary (section 6.15) for further details.

Page 58

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.33 Pager Delay Time: Program Address (4038)
When using the Pager Dialing Format (selected in Addresses 3156 and 3157), you may insert a delay time after the phone number is
dialed and before the reports are sent to the pager system. This delay can be used to allow for greeting and instruction messages in the
pager system. This delay will not affect any other report formats.

Data Digit
1
2

Pager Delay Time
Address 4038
Default = 10 seconds

0 to 99 seconds

10.34 Programmer’s and Master Code Programming: Program Addresses (7589-7592)
Programmer’s Code programming defines what the Programmer’s Code will be. This code is used to enter the programming mode
from the keypads.
Although the DS7400Xi (Ver. 4+) Control/Communicator is shipped with 6-digit codes preprogrammed, it is also shipped
with a 4-digit PIN length default. The default codes for the Programmer’s Code and the Master Code will be 4-digits (9876
and 1234 respectively) unless you have reprogrammed for a 6-digit PIN length.

Program Address 7589
Data Digit
1

2

3

4

5

6

9

8

7

6

5

4

Programmer’s Code
Enter as 6 digits.
It can not be the same
as any PIN number.
The Default for the Programmer’s Code = 987654
Master Code programming defines what the Master Code will be. This code is the highest authority level for a PIN.
If the Master Code is lost, this address may be used to program a new one.
Otherwise, the Master Code Programming Mode should be used to create PINs
that have a Master Code authority level.
Program Address 7592

Data Digit
Master Code for User Number 001 has its
authority fixed at level 0. It will always have
access to all partitions.
NOTE:

User Numbers 002 through 200
must be programmed from the
Master Code Programming
Mode.

1

2

3

4

5

6

1

2

3

4

5

6

Master Code PIN Number
(Default for this User 001
is 123456)

10.35 PIN Length Programming: Program Address (3478)
PIN Length Programming defines the length of the PINs that are assigned to each user.
PINS can be programmed to be 4 or 6 digits in length.

Select Option

DS7400Xi ( 4+) Reference Guide

4-digit PINs

0

6-digit PINs

1

Copyright © 2007 Bosch Security Systems, Inc.

Data Digit

1

2

0

P/N: F01U035325-01

Page 59

10.36 Octal Relay Module Output Programming
10.36.1 Follow Action: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Action, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 1 for Follow Action.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.
The Octal Relay Module is the DS7488. See section 1.18 and 6.4 for further details.
NOTE:

If a DS9484 is used, it replaces the DS7488 and takes up outputs 1-4 of the Octal Relay Module. Outputs 5-8 of the Octal Relay
Module are unavailable. If two DS9484 power supplies are used, one replaces Octal Relay Module 1 and the other replaces
Octal Relay Module 2.

For Octal Relay Partition Assignment, see section 10.36.5.

Program Address A
Data Digit

1

2

1

SELECT OPTION DD 2
Follows
0 1 2 3
Disabled
Burglar Alarm
Fire Alarm

Octal
Relay
#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

DS7488-1 DS7488-1
Address Address
A
B
2740
2742
2744
2746
2748
2750
2752
2754
2756
2758
2760
2762
2764
2766
2768
2770

2741
2743
2745
2747
2749
2751
2753
2755
2757
2759
2761
2763
2765
2767
2769
2771

Program Address B
Data Digit

1

2

SELECT OPTION DD 1 & 2
Latch ON after Zone Alarm**

DD
00

ON during Entry Pre-Alert
01
ON for 10 sec. after pressing [System Reset] 0 2
03
ON for Any Armed state
Ground Start
System Status (Ready to Arm)
Zone Alarm
Zone Alarm delayed by 20 seconds
Keypad Sounder Output
Access Output (10 sec. pulse)
Future Selection
Panic/Duress Output***
ON when System is Partial
ON when System is Fully Armed

04
05
06
07
08
09
0*0
0*1
0*2
0*3

** = This includes invisible zones. See glossary for further details.
*** = See section 6.4 for description of this option.

Page 60

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.36 Octal Relay Module Output Programming (continued)
10.36.2 Follow System Wide Event: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow System Wide Event, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 2 for Follow System Wide Event.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.

For Octal Relay Partition Assignment, see section 10.36.5.

Program Address A
Data Digit

1

2

2

SELECT OPTION DD 2
Follows
0 1 2 3
Disabled
Burglar Alarm
Fire Alarm

Octal
Relay
#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

DS7488-1 DS7488-1
Address Address
A
B
2740
2742
2744
2746
2748
2750
2752
2754
2756
2758
2760
2762
2764
2766
2768
2770

2741
2743
2745
2747
2749
2751
2753
2755
2757
2759
2761
2763
2765
2767
2769
2771

Program Address B
Data Digit

1

2

SELECT OPTION DD 1 & 2

DD

Disabled
AC Power Fail
Low Battery

00
01
02

Communicator Failure
System Fault*
Keypad Supervision Fault
Multiplex Bus Fault

03
04
05
06
07
08
09
0*0
0*1
0*2
0*3
0*4
0*5

RF Receiver Fault
Aux Power Fault
Fire Zone Trouble
Supervisory
Zone Trouble
Duress
Battery Test
Future Selection
Future Selection

*System Faults include:
• RAM fault
• ROM fault
• Bell/Line Monitor fault (DS7420i)
• Line 1 fault
• Line 2 fault
• Bell fault
• Aux. Power fault
• Octal Relay fault
• Serial Module fault (DS7412)
• Serial Transmit fault
• Serial Receive fault
• Aux. Relay fault
• DS7416i Communication fault
• RF Receiver Tamper
• RF Receiver Jammed
• RF Receiver Trouble
• Printer Off-line

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 61

10.36 Octal Relay Module Output Programming (continued)
10.36.3 Follow Function: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Output Function, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 3 for Follow Function.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired function.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.

For Octal Relay Partition Assignment, see section 10.36.5.

Page 62

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.36 Octal Relay Module Output Programming (continued)
10.36.4 Follow Zone: Program Addresses (2740-2771)
To program an Octal Relay Module for Follow Zone, follow the steps below.
1. Select Octal Relay to program.
2. Program Data Digit 1 of Program Address A as 4 for Follow Zone.
3. Program Data Digit 2 of Program Address A for the desired function.
4. Program Data Digit 1 and 2 of Program Address B for the desired zone.
Once both Address A and Address B have been programmed, proceed to program the next Octal Relay.

Program Address A
Data Digit

1

2

4

SELECT OPTION DD 2
0 1 2 3 4 5 6

Activate:

7 8 9 *0 *1 *2

Disabled
When zone is shorted
When Zone is opened
When panel is Armed
When panel is not Armed

Latch when activated**
** = This applies only to the DS7465 outputs.
DS7488 outputs will not latch when this is selected.

DS7400Xi ( 4+) Reference Guide

Octal
Relay
#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

DS7488-1 DS7488-1
Address Address
A
B
2740
2742
2744
2746
2748
2750
2752
2754
2756
2758
2760
2762
2764
2766
2768
2770

2741
2743
2745
2747
2749
2751
2753
2755
2757
2759
2761
2763
2765
2767
2769
2771

Copyright © 2007 Bosch Security Systems, Inc.

Program Address B
Data Digit

1

2

Program the HEX value
of the Zone
from the chart
on the next page

P/N: F01U035325-01

Page 63

Page 64

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.36 Octal Relay Module Output Programming (continued)
10.36.5 Octal Relay Module Output Partition Assignment: Program Addresses (2844-2851)
Program Address 2844
Data Digit 1

Data Digit 2

Program Address 2845
Data Digit 1

Data Digit 2

Program Address 2846
Data Digit 1

Data Digit 2

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6

default = 8

default = 8

default = 8

default = 8

default = 8

default = 8

Program Address 2847
Data Digit 1

Data Digit 2

Program Address 2848
Data Digit 1

Data Digit 2

Program Address 2849
Data Digit 1

Data Digit 2

Relay 7

Relay 8

Relay 9

Relay 10

Relay 11

Relay 12

default = 8

default = 8

default = 0

default = 0

default = 0

default = 0

Program Address 2850
Data Digit 1

Data Digit 2

Program Address 2851
Data Digit 1

Data Digit 2

Select Option

DD

Belongs to Partition 1

0

Belongs to Partition 2

1

Belongs to Partition 3

2

Belongs to Partition 4
Belongs to Partition 5

3
4

Belongs to Partition 6

5

Belongs to Partition 7

6

Belongs to Partition 8

7
8

Follows all Partitions
Relay 13

Relay 14

Relay 15

Relay 16

default = 0

default = 0

default = 0

default = 0

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 65

10.37 Output Function Programming: Program Addresses (2772-2843)
Output programming allows you to have the Outputs follow status events by partition or system-wide, or follow zone outputs in an Input/
Output Cross Matrix. See the Programming Addresses Worksheet (P/N: 43850) for a description of each address. See Glossary
(section 6.4) for further details.
Select Option

DD

Latch ON after Zone Alarm

0

ON during Entry Pre-Alert

1

ON when system is armed

3

Zone alarm

6

Zone Alarm delayed by 20 sec.

7

Keypad Sounder output

8

Access output (10 sec. pulse)

9

Keyfob output

*0

Panic/Duress output**

*1

Follow System Status Event

*2

Follow a single zone

*3

Data Digit 1 Options 1-9 and *1 are used to program an Output
Function to follow status events for individual partitions.
Data Digit 1 Option *0 is used to program an Output
Function to follow the Wireless Keyfob Output Buttons.
Data Digit 1 Option *2 is used to program an Output
Function to follow status events system-wide.
Data Digit 1 Options *3-*5 are used to program an Output
Function to follow a zone or two zones in an Input/Output
Cross Matrix.
Data Digit
Program
Data Digit
1
2
Address
Program
1
2
1
Address
1

Data Digit
Option

Data Digit
1
2

*5

*0-*5 are Hex values. They will
display as A-F at the keypads.

DD

Follows

0
Key 1
Key 2
3
4

Disabled
Moment Option
Toggle Option
Moment
Toggle

Follow two zones-When EITHER zone changes state *4
Follow two zones-When BOTH zones change state

RF3334

0

1

2

3

Disabled
Burglar Alarm
Fire Alarm

*2
Select Option
AC Power Failure

DD DD
1

7

Radio Receiver Fault

Low Battery

2

8

Aux Power Fault

Communication Failure

3

9

Fire Trouble

System Fault**

4

*0

Supervisory

Keypad Supervision Fault

5

*1

Zone Trouble

Multiplex Bus Fault

6

*2

Duress PIN

Program
Address
1

Select Option

Program
Address
2

Data Digit
1

Program
Address
3

Data Digit
2

1

*0 - *2 are Hex values. They will display as A - C at the keypads.
**System Faults include:
• Serial Transmit fault
• RAM fault
• Serial Receive fault
• ROM fault
• Bell/Line Monitor fault (DS7420i) • Aux. Relay fault
• DS7416i Communications fault
• Line 1 fault
• RF Receiver Tamper
• Line 2 fault
• RF Receiver Jammed
• Bell fault
• RF Receiver Trouble
• Aux. Power fault
Data Digit
• Printer Off-line
• Octal Relay fault
1
2
• Serial Module fault (DS7412)
3

Data Digit
2

1

Enter the
Zone Number
of Second
Zone to
Follow
(see Zone
HEX Values
chart)

Enter the
Zone Number
of First Zone
to Follow
(see Zone
HEX Values
chart)

Not Required
if following a
single zone

Data Digit
Output Program Program Program
Function Address Address Address
Number
1
2772
2773
2774
2
2775
2776
2777
3
2778
2779
2780
4
2781
2782
2783
5
2784
2785
2876
6
2787
2788
2789
7
2790
2791
2792
8
2793
2794
2795
9
2796
2797
2798
10
2799
2800
2801
11
2802
2803
2804
12
2805
2806
2807
13
2808
2809
2810
2812
14
2811
2813
2815
15
2814
2816
16
2817
2818
2819
17
2820
2821
2822
18
2823
2824
2825
19
2826
2827
2828
20
2829
2830
2831
21
2832
2833
2834
22
2835
2836
2837
23
2838
2839
2840
24
2841
2842
2843

Page 66

P/N: F01U035325-01

Follows

0

2

1

2

3

Disabled
Armed Full
Armed Partial
Armed Any
Enter Data Digit as a:
Activate:

0

1

2

3

4

5

6

7

8

9

*0

*1

*2

Disabled
When zone is shorted
When Zone is opened
When panel is Armed
When panel is not Armed
Latch when activated**
** = This is only for DS7465 Outputs. DS7488 Outputs will not latch when this is selected.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.37.1 Output Function Partition Assignment: Program Addresses (2852-2863)

10.38 Dual Phone Line/Bell Supervision Module Output Programming: Program Address (4021)
The Dual Phone Line/Bell Supervision Module is the DS7420i. See section 1.18 for further details.
When in Central Station or Local Commercial Fire Mode, this address will be forced to specific values (see sections 10.16.1 and
10.16.2).

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 67

10.39 Call-Out Timer Programming: Program Addresses (4022-4025)
This section allows you to define the Hour and Minute for the Communicator Test Report and Remote Programmer Call-Out.
The default time for the Communicator Test Report to be sent and for the control to call the Remote Programmer is Midnight.

10.40 Test Report and Remote Programmer Call-Out Programming: Program Address (4026)
This section allows you to define the Day and Frequency for the Communicator Test Report and the Remote Programmer Call-Out.
If this address is not programmed, the Communicator Test Report will not be sent and the control will not call the Remote Programmer.

Page 68

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.41 Alpha Description Programming: Program Addresses (0545-2720, 5001-6920)
Alpha Description Programming allows up to 16 characters to be programmed for the description of each partition or zone (e.g. “J. Hill’s
Office”). If a description is less than 16 characters, leave the remaining address(es) blank. Once programmed, the descriptions will be
displayed on the alpha keypads.
The following chart lists the Program Addresses used to program Alpha-Numeric characters for each partition or zone:

See Section 10.41.1 for an Alpha Description Programming worksheet for Partitions 1 through 8 and Zones 1 through 8.
See the Programming Addresses Worksheet (P/N: 43850) for a complete Alpha Programming Worksheet
(covering addresses 0545 through 6920).
Words are created one character at a time. Each character uses two data digits.
The data digit values for these characters are shown below:

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 69

10.41.1 Alpha Description Programming: A Worksheet

Page 70

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.41.1 Alpha Description Programming: A Worksheet (Continued)

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 71

10.41.1 Alpha Description Programming: A Worksheet (Continued)

Page 72

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

10.41.1 Alpha Description Programming: A Worksheet (Continued)

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 73

10.42 Phone Number Programming: Program Addresses (3159, 3175, 3191)
10.42.1 Phone Number 1 Programming: Program Address (3159)

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30 31 32

10.42.2 Phone Number 2 Programming: Program Address (3175)

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30 31 32

10.42.3 Phone Number 3 Programming: Program Address (3191)

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20

21 22 23 24 25 26 27 28 29 30 31 32

Notes:
To dial the “*” character, enter *1 (The “*” character is sent as “1” “1” when pulse dialing).
To dial the “#” character, enter *2 (The “#” character is only valid when tone dialing).
To input a three second delay, enter *3.
To wait for the dial tone, enter *4 in the first digit.
To disable a Phone Number, enter *5 in the first digit.
(*1 - *5 are Hex values. They will display as B - F at the keypads.)

Recommendation: The phone line that the control panel is connected to should not have a Call Waiting feature. If it must have call
waiting, program the code to disable call waiting and add a three second delay before the phone number. This will prevent incoming
calls from interrupting a communication. For example: call waiting can be disabled in many areas by dialing *70 before the phone
number for tone dial and 1170 for pulse dial.

Page 74

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

11.0

Installation Guide for UL Listed Systems

11.1

DS7400Xi UL Listings:

• Household Fire Alarm, UL Standard UL985
• Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Type Initiating: Automatic, Manual, Sprinkler
Supervisory, and Waterflow), UL Standard UL864
• Household Burglary Alarm, UL Standard UL1023
• Police Station Connection Grades AA and A, UL Standard UL365
• Central Station Burglary Alarm Grades AA, A, B, and C; UL Standard UL1610
• Proprietary Alarm Units Grades A and AA, UL Standard UL1076
The control panel should be installed in accordance with UL Standard UL681, Installation and Classification of Mercantile and Bank
Burglar Alarm Systems, or UL Standard UL1641, Installation and Classification of Residential Burglar Alarm Systems. It should also be
installed in accordance with NFPA 72 for Household and Commercial Fire installations.

11.1.1UL System Configurations
The following table shows the DS7400Xi system configuration for the various types of fire and burglar alarm service for which the
product is UL Listed.
UL Application
Product
CSF-D

CSF-D/RF

LF

CSB-A

PP-AA

CSB-B/C

PP-A

3007-9001 DS7400Xi

R

R

R

R

R

R

R

Standard Enclosure

1

1

1

n/a

n/a

n/a

Attack Enclosure

1

1

1

R

R

AE-TR16 Enclosure

R

R

R

n/a

DS7416i

n/a

R

n/a

DS7420i

R

4

DS7430

0

DS7432

LB-A

PSCB-D-A

PSCB-RF-A

HF/B

R

R

R

R

n/a

n/a

n/a

n/a

1

R

R

R

R

R

1

n/a

n/a

n/a

n/a

n/a

n/a

n/a

R

R

n/a

n/a

n/a

n/a

R

n/a

R

4

4

n/a

n/a

n/a

n/a

4

n/a

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

DS7433

0

0

0

0

0

0

0

0

0

0

0

DS7447/DS7447E

2

2

2

3

3

3

3

3

3

3

3

DS7460

0

0

0

0

0

0

0

0

0

0

0

DS7480

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

R

DS7481

n/a

4

n/a

4

4

n/a

n/a

n/a

n/a

4

n/a

DS7488

0

0

0

0

0

0

0

0

0

0

0

AB12 Bell w/Housing

n/a

n/a

n/a

R

R

R

R

R

R

R

n/a

Key to Application Codes

Configuration Codes

CSF-D = Central Station Fire w/ DACT (Digital Alarm Communications Transmitter/dialer)
CSF-D/RF = Central Station Fire w/ DACT and Radio (DS7416i)
LF = Local Fire
CSB-A = Central Station Burglary, grades AA and A
PP-AA = Proprietary grade AA
CSB-B/C = Central Station Burglary, grades B and C
PP-A = Proprietary grade A
LB-A = Local Burglary, grade A
PSCB-D-A = Police Station Connected Burglary w/DACT, grade A
PSCB-RF-A = Police Station Connected Burglary w/Radio (DS7416i), grades AA and A
HF/B = Household (residential) Fire and Burglary

R = Required
0 = Optional
n/a = Not Applicable
1 = Standard or attack enclosure may be
used.
2 = Either enclosure may be used. Device
must be mounted to the enclosure cover,
or within 20 ft. w/wiring in conduit.
3 = Either enclosure may be used.
4 = Either the DS7420i or the DS7481
must be used to monitor the phone line
input to the control unit.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 75

11.2

be programmed for not less than 4 minutes.

Installation Considerations

• Failure to install and program the control in accordance with the
requirements in this section voids the listing mark of Underwriters
Laboratories, Inc.
• The maximum standby battery capacity is 35 Ah @ 12 VDC.
• The total nominal standby current must not exceed 1.5 A nor 2.5
A when in alarm.
• The control must be mounted indoors and within the protected
area.
• Enclosure tamper switches (if used) must be connected to a 24hour zone.
• Grounding must be in accordance with article 250 of the NEC
(NFPA 70).
• At least one UL Listed keypad with zone display must be
connected.
• Zones must be connected to UL Listed, compatible devices.
• 50 Hz. AC input cannot be used in UL Listed Requirements.
• The ground wire provided with the enclosure must be connected
to the “Earth GND” connection on the control and the enclosure
tab.
• The keypad panic alarm output must follow the corresponding
zone function’s programming (e.g. fire = pulsing [or steady if not
a combination], burglary = steady). In all cases, the special
emergency keys must be silent.
• The ground start feature shall not be programmed.

11.3

Programming the DS7400Xi

When used in UL Listed Requirements, the control must conform
to certain programming requirements. The following is a list of the
required program entries and required accessories for specific
UL Listed Requirements.

11.3.1Household Fire Alarm Using Digital Alarm
Communicator Transmitter With Local Bell
The control must be installed in accordance with NFPA 72.
Required Accessories:
• At least one Detection Systems, Inc. Model DS250 Series smoke
detector with an MB Series base, DS280 Series, MX280 Series,
or another Listed compatible smoke detector.
• At least one DS7480 Bell Supervision Module.
• One Wheelock 46T-G10-12 bell or 34T-12 horn (will provide
85db for UL985 and NFPA 72 requirements; other Listed
compatible devices with a voltage range of 10.2 to 14.0 V may be
used) is required and must be installed inside the protected
area.
• The standard control enclosure can be used.
• At least one DS7447/DS7447E or DS7445/DS7445i Keypad must
be used.
• Four-wire detectors must be used with Listed power supervision
devices. A compatible Listed 4-wire detector is the Detection
Systems, Inc. DS250 in an MB4W base. A compatible Listed
EOL relay is the Detection Systems, Inc. EOL200.
• All zones must be used with the EOL resistor (P/N 25899),
provided.

3. Zone Function Programming:
• For household fire installations only, the output signal may be
pulsed or steady. For a combination system, see the selection
below on alarm output programming.
4. Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2= 3.
5. General Control Programming:
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.

11.3.2Grade A Household Burglary Alarm Using Digital
Alarm Communicator Transmitter With Local
Bell
The control must be installed in accordance with UL Standard
UL1641.
Required Accessories:
• At least one Wheelock 46T-G10-12 bell or 34T-12 horn (other
Listed compatible devices with a voltage range of 10.2 to 14.0 V
may be used) is required for this application.
• The standard DS7400 enclosure can be used.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
2. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 4 minutes.
• Entry Delay Timer (Program Addresses 4028 and 4029) must
be programmed for not longer than 60 seconds.
• Exit Delay Timer (Program Address 4030) must be programmed
for not longer than 45 seconds.
3. General Control Programming:
• Program Address 0000, Data Digit 2 must be programmed for
NO Swinger Shunts (enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
4. Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2= 3.
• Program Address 2737 must be programmed as: Data Digit 1=
8.
In a system that includes both fire alarm and burglar alarm
devices, the system must produce distinct sounds for fire
and burglar alarm conditions either by using different
indicating appliances or by using distinct cadences for
the same appliance.

1. Report Programming:
• Fire Zone Report must be programmed.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
2. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must

Page 76

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

11.4

General System Requirements

Applies to the following grades only:
Local Burglary
Grade A using Digital Alarm Communicator
Alarm Transmitter (DACT)
Police Station
Connection -

Grades AA and A using DACT and DS7416i
Communications module.
Grade A using DACT and local Bell.

• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.

Grades AA and A using DACT and DS7416i
Communications module.
Grade B using DACT and local bell.
Grade C using Digital Alarm Communicator
Transmitter only.
The controls must be installed in accordance with UL Standards
UL681 and UL609 for all grades of service.

B.Grade A Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.

1. Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.
• Open Report (Program Address 3331) must be programmed.
• Close Report (Program Address 3332) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.

1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.

Central Station
Burglary Alarm -

2. General Control Programming:
• The control must not be programmed for auto disarm.
• Must be programmed for no swinger shunts and closing ringback.
(Program Address 0000 data digit 2, enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit 1=
0, Data Digit 2= 0.
3. Zone Function Programming:
• The Burglar alarm signal (whether pulsed or steady) must be
different from the Fire alarm signal.
4. Alarm Output Programming:
• Program Address 2734 must be programmed as: Data Digit 1=
6, Data Digit 2 = 3.
• Program Address 2737 must be programmed as: Data Digit 1=
8.

11.4.1Local Burglary Alarm
A. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• An Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4029) must
be programmed for not longer than 60 seconds.

11.4.2Police Station Connection
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.

DS7400Xi ( 4+) Reference Guide

Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).

11.4.3Central Station Burglary Alarm and Proprietary
A.Central Station Burglary Grades AA and A and Proprietary
Grade AA Installations Using an DS7416i Interface Module
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
• An DS7416i (or DataTAC) interface module.
• The DS7416i module and antenna should be mounted within
the protected area.
• The Detection Systems’ model DS7481 Phone Line Monitor.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
B.Grade B Installations Using Digital Alarm Communicator
Transmitter With Local Bell
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection Systems’ model AE3CC
enclosure with a cover actuated tamper switch installed.
• The Ademco Model AB-12 bell/housing (see section 11.6).
1. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 15 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
C.Central Station Burglary Grade C and Proprietary Grade A
Installations Using Digital Alarm Communicator Transmitter only
Follow General System Requirements as listed in 11.4.
Required Accessories:
• The control must be in the Detection System’s model AE3CC
enclosure with a cover actuated tamper switch installed.
1. Timer Programming:
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 77

11.5

• Open Report (Program Address 3331) must be programmed.
• Close Report (Program Address 3332) must be programmed.
• 24-Hour Check-In Reports (Program Addresses 3340 and 3347)
must be programmed.

Commercial Fire Alarm

A. Central Station (DACT) and Local
The control must be installed in accordance with NFPA 72.
Required Accessories:
• DS7420i Dual Phone Line/Bell Supervision Module.
• For Local Commercial Fire Alarm: A Listed notification appliance
such as a Wheelock 46T-G10-12 bell or 34T-12 horn.
• If not using the phone line supervision, it must be disabled.
• AE-TR16 Transformer Housing.
• At least one DS7447/DS7447E must be used and assigned as
keypad 1. If only one is used, it may be connected to the keypad
bus if the keypad is mounted to the front of the box or within the
same room as the control equipment and the wire is run in
conduit (or equivalently protected against mechanical injury)
within 20 ft.
(6.1 m) of the control equipment. If multiple
keypads are used, one keypad only must be used on the options
bus and assigned as keypad 11-14 and meet the same
requirements as in single keypad use.
• 50 Hz. operation and ground start are automatically forced to the
disabled state when central station fire mode is selected.
1. Report Programming:
• Burglar Zone Reports must be programmed for those zones
used.
• Fire Zone Reports must be programmed for those zones used.
• Low Battery Report (Program Address 3336) must be
programmed.
• AC Failure Report (Program Address 3338) must be
programmed.

11.6

2. Timer Programming:
• Bell Cutoff Times (Program Addresses 4032 and 4033) must
be programmed for not less than 5 minutes.
• Entry, Exit Delay Times (Program Addresses 4028-4030) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
• Must be programmed for no swinger shunts (Program Address
0000 data digit 2, enter 0, 1, or 2).
• Program Address 2732 must be programmed as: Data Digit
1=0, Data Digit 2= 0.
4. Commercial Fire Mode Programming:
• Local (Program Address 2733, data digit 1, enter as a 1 through
6).
• Central Station (Program Address 2733, data digit 1, enter as a
7 through *2).
• The keypad panic functions are not intended to be a substitute
for Listed manual pull boxes.

Wiring and Programming Information for Installations Using the Ademco AB-12 Bell/Housing
Ademco AB-12 Bell/Housing
To control Earth Ground

Control/Communicator

Terminal 1
Alternate EOL (if not

To control Loop Positive

EOL using a Fire card)
27 kΩ Detection Systems’
P/N 28300

Terminal 29 (+)
To control Zone 8 Input
Terminal 30 (8-)
To control Alarm Output –
Terminal 5 (-)
To control Alarm Output +
Terminal 6 (A)

Bell Tampers

JP1

BELL

Inner Bell Box Lining
Outer Bell Box

Cut this jumper

1) Disconnect the wire jumper from terminal 4 to the inner housing of the Bell Box (prevents a ground fault condition).
2) Connect wiring between the control and Bell Box as shown above. To use the AB-12 Bell/Housing, cut the jumper wire “JP1” on the
control. The EOL used in the AB-12 Bell/Housing must be 27 kΩ.
3) Program Zone 8 as a 24-hour zone by programming it to follow zone function 7. (Program address 0038 = 07).
4) Do not change the default programming of zone function 7. (Program address 0007 should be 22).

Page 78

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

12.0

Report Programming

12.1

4/2 Format
Reports with Restorals

Suggested Values
Report

Restoral

Trouble

Value

Address

Trouble Restoral

Value

Address

Address

Zone Function 1

3209

A 1

3241

2

1

3271

6

1

3301

4

1

3358

8

1

3388

9

1

Zone Function 2

3210

A 2

3242

2

2

3272

6

2

3302

4

2

3359

8

2

3389

9

2

Zone Function 3

3211

A 3

3243

2

3

3273

6

3

3303

4

3

3360

8

3

3390

9

3

Zone Function 4

3212

A 4

3244

2

4

3274

6

4

3304

4

4

3361

8

4

3391

9

4

Zone Function 5

3213

A 5

3245

2

5

3275

6

5

3305

4

5

3362

8

5

3392

9

5

Zone Function 6

3214

A 6

3246

2

6

3276

6

6

3306

4

6

3363

8

6

3393

9

6

Zone Function 7

3215

A 7

3247

2

7

3277

6

7

3307

4

7

3364

8

7

3394

9

7

Zone Function 8

3216

A 8

3248

2

8

3278

6

8

3308

4

8

3365

8

8

3395

9

8

Zone Function 9

3217

A 9

3249

2

9

3279

6

9

3309

4

9

3366

8

9

3396

9

9

Zone Function 10 3218

A A

3250

2 A

3280

6

A

3310

4 A

3367

8 A

3397

9

A

Zone Function 11 3219

A B

3251

2 B

3281

6

B

3311

4

B

3368

8

B

3398

9

B

Zone Function 12 3220

A C

3252

2 C

3282

6 C

3312

4

C

3369

8

C

3399

9

C

Zone Function 13 3221

A D

3253

2 D

3283

6 D

3313

4

D

3370

8

D

3400

9

D

Zone Function 14 3222

A E

3254

2 E

3284

6

E

3314

4

E

3371

8

E

3401

9

E

Zone Function 15 3223
Zone Function 16 3224

A F

3255

2 F

3285

6

F

3315

4

F

3372

8

F

3402

9

F

A F

3256

2

F

3286

6

F

3316

4

F

3373

8

F

3403

9

F

Zone Function 17 3225

A F

3257

2

F

3287

6

F

3317

4

F

3374

8

F

3404

9

F

Zone Function 18 3226

A F

3258

2

F

3288

6

F

3318

4

F

3375

8

F

3405

9

F

Zone Function 19 3227

A F

3259

2

F

3289

6

F

3319

4

F

3376

8

F

3406

9

F

Zone Function 20 3228

A F

3260

2

F

3290

6

F

3320

4

F

3377

8

F

3407

9

F

Zone Function 21 3229

A F

3261

2

F

3291

6

F

3321

4

F

3378

8

F

3408

9

F

Zone Function 22 3230
Zone Function 23 3231

A F

3262

2

F

3292

6

F

3322

4

F

3379

8

F

3409

9

F

A F

3263

2

F

3293

6

F

3323

4

F

3380

8

F

3410

9

F

Zone Function 24 3232

A F

3264

2

F

3294

6

F

3324

4

F

3381

8

F

3411

9

F

Zone Function 25 3233

A F

3265

2

F

3295

6

F

3325

4

F

3382

8

F

3412

9

F

Zone Function 26 3234

A F

3266

2

F

3296

6

F

3326

4

F

3383

8

F

3413

9

F

Zone Function 27 3235

A F

3267

2

F

3297

6

F

3327

4

F

3384

8

F

3414

9

F

Zone Function 28 3236

A F

3268

2

F

3298

6

F

3328

4

F

3385

8

F

3415

9

F

Zone Function 29 3237
Zone Function 30 3238

A F

3269

2

F

3299

6

F

3329

4

F

3386

8

F

3416

9

F

A F

3270

2

F

3300

6

F

3330

4

F

3387

8

F

3417

9

F

Report
Address

Address

Bypass Restoral

Value

Reports with Restorals

Value

Bypass

Address

Value

Reports without Restorals

Address

Value

Report
Address

Restoral

Value

Address

Value

Value

Open

3331

5

1

Close

3332

5

2

Low Battery

3336

3

1

3337

7

1

AC Fail

3338

3 2

3339

7 2

Partial Close

3334

5

3

System Trouble

3345

3

3

3346

7

3

First Open after Alarm

3335

5

4

Keypad Fire

3207

3

4

3208

7

4

Exit Error

3348

5

5

System Walk Test

3350

3

5

3351

7

5

Recent Closing

3349

5

6

Fire Walk Test

3352

3

6

3353

7

6

Keypad Emergency

3239

5

7

Low Temperature

3354

3

7

3355

7

7

Dirty Smoke Chamber

3356

3

8

3357

7

8

Keypad Panic
Duress

3240
3333

5 8
5 9

Report Successful

DS7400Xi ( 4+) Reference Guide

Report Unsuccessful

Address

Value

Address

Remote Program

3341

E F

3342

F

F

Local Program

3343

E F

3344

F

F

Copyright © 2007 Bosch Security Systems, Inc.

Value

P/N: F01U035325-01

Page 79

12.2

BFSK Format
Reports with Restorals

Suggested Values
Report
Address

Restoral

Value

Trouble

Address

Value

Address

Trouble Restoral

Value

Bypass

Address

Value

Address

Bypass Restoral
Address

Value

Zone Function 1

3209

1

0

3241

E 1

3271

F

1

3301

E 1

3358

F

1

3388

E 1

Zone Function 2

3210

2

0

3242

E 2

3272

F

2

3302

E 2

3359

F

2

3389

E 2

Zone Function 3

3211

3

0

3243

E 3

3273

F

3

3303

E 3

3360

F

3

3390

E 3

Zone Function 4

3212

4

0

3244

E 4

3274

F

4

3304

E 4

3361

F

4

3391

E 4

Zone Function 5

3213

5

0

3245

E 5

3275

F

5

3305

E 5

3362

F

5

3392

E 5

Zone Function 6

3214

6

0

3246

E 6

3276

F

6

3306

E 6

3363

F

6

3393

E 6

Zone Function 7

3215

7

0

3247

E 7

3277

F

7

3307

E 7

3364

F

7

3394

E 7

Zone Function 8

3216

8

0

3248

E 8

3278

F

8

3308

E 8

3365

F

8

3395

E 8

Zone Function 9

3217

8

0

3249

E 8

3279

F

0

3309

E 8

3366

F

0

3396

E 8

Zone Function 10 3218
Zone Function 11 3219

8 0

3250

E 8

3280

F 0

3310

E 8

3367

F 0

3397

E 8

8

0

3251

E 8

3281

F 0

3311

E 8

3368

F 0

3398

E 8

Zone Function 12 3220
Zone Function 13 3221

8

0

3252

E 8

3282

F 0

3312

E 8

3369

F 0

3399

E 8

8

0

3253

E 8

3283

F 0

3313

E 8

3370

F 0

3400

E 8

Zone Function 14 3222
Zone Function 15 3223

8

0

3254

E 8

3284

F 0

3314

E 8

3371

F 0

3401

E 8

8

0

3255

E 8

3285

F 0

3315

E 8

3372

F 0

3402

E 8

Zone Function 16 3224
Zone Function 17 3225

8

0

3256

E 8

3286

F

0

3316

E 8

3373

F 0

3403

E 8

8

0

3257

E 8

3287

F

0

3317

E 8

3374

F 0

3404

E 8

Zone Function 18 3226
Zone Function 19 3227

8

0

3258

E 8

3288

F

0

3318

E 8

3375

F 0

3405

E 8

8

0

3259

E 8

3289

F

0

3319

E 8

3376

F 0

3406

E 8

Zone Function 20 3228
Zone Function 21 3229

8

0

3260

E 8

3290

F

0

3320

E 8

3377

F 0

3407

E 8

8

0

3261

E 8

3291

F

0

3321

E 8

3378

F 0

3408

E 8

Zone Function 22 3230
Zone Function 23 3231

8

0

3262

E 8

3292

F

0

3322

E 8

3379

F 0

3409

E 8

8

0

3263

E 8

3293

F

0

3323

E 8

3380

F 0

3410

E 8

Zone Function 24 3232
Zone Function 25 3233

8

0

3264

E 8

3294

F

0

3324

E 8

3381

F 0

3411

E 8

8

0

3265

E 8

3295

F

0

3325

E 8

3382

F 0

3412

E 8

Zone Function 26 3234
Zone Function 27 3235

8

0

3266

E 8

3296

F

0

3326

E 8

3383

F 0

3413

E 8

8

0

3267

E 8

3297

F

0

3327

E 8

3384

F 0

3414

E 8

Zone Function 28 3236
Zone Function 29 3237

8

0

3268

E 8

3298

F

0

3328

E 8

3385

F 0

3415

E 8

8

0

3269

E 8

3299

F

0

3329

E 8

3386

F 0

3416

E 8

Zone Function 30 3238

8

0

3270

E 8

3300

F

0

3330

E 8

3387

F 0

3417

E 8

Reports with Restorals
Report

Value

Reports without Restorals

Restoral

Report
Address

Value

Address

Value

Address

Value

Open

3331

B F

Low Battery

3336

F 9

3337

E 9

Close

3332

C F

AC Fail

3338

F A

3339

E A

Partial Close

3334

C F

System Trouble

3345

F D

3346

E D

First Open after Alarm

3335

D F

Keypad Fire

3207

1

0

3208

E 1

Exit Error

3348

0

0

System Walk Test

3350

7

1

3351

7

2

Recent Closing

3349

0

0

Fire Walk Test

3352

7

3

3353

7

4

Keypad Emergency

3239

0

0

Low Temperature

3354

3

1

3355

3

2

Dirty Smoke Chamber

3356

3

3

3357

3

4

Keypad Panic
Duress

3240
3333

9 0
A 0

Report Successful
Address

Page 80

P/N: F01U035325-01

Value

Report Unsuccessful
Address

Value

Remote Program

3341

0

0

3342

0

0

Local Program

3343

0

0

3344

0

0

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

12.3

Personal Dialing Format

This is a 2 pulse per second (PPS) 0/2 (no account code/2 report event digits) format intended for manual reception, i.e. the panel will
call a phone number where a person is expected to answer. After a call is made, the panel will start sending the first report. If the report
was a “Communication Test” and Program Address 3340 had a value of 12 the person answering the phone would hear 1 pulse
followed by a 1 second delay, then 2 pulses followed by a 3 second delay. This sequence will repeat for 60 seconds per call. After the
60 seconds the panel will hang up and call again if any reports still remain to be sent.
A way to expedite this report process would be to provide an acknowledge to the panel that the report was heard and understood by the
receiving party. When an acknowledge is provided, the panel will start sending the next report or hang up if no reports remain. To provide
an acknowledge, press the 1 key of the telephone keypad during the 3 second delay of the report transmission. This “Acknowledge
Feature” is an enhancement that will allow the panel to send all reports in one call. If the call is not acknowledged a communication
failure is sent after all dial attempts are made.
Programming the first data digit as zero will disable the report. Values 1-9 and A-F are acceptable. A zero in the second data digit will
send ten pulses.

12.4

Pager Format

The Pager format allows the control panel to dial a digital pager and leave a numeric message which includes an account ID and report
type. The telephone number is dialed when a report is available. At the completion of the telephone dialing, a time delay equal to 10
seconds occurs. This delay allows time to connect with the pager service, while skipping over any voice announcement. When the delay
has ended, the numeric message is sent. This message includes the account number followed by up to 5 reports. If a delay time greater
than 10 seconds is required, see Programming Address 4038 to adjust the delay time. In addition, increments of 3 seconds can be
added by programming the “*3” character (3 second delay) at the end of the phone number in address 3159 or 3175.
For example, if you call pager number 123-4567 and it takes 20 seconds after you finished dialing before you are allowed to enter the
message, the following digits should be programmed in address 3159: 1 2 3 4 5 6 7 *3 *3 *3 *3. This will give you an overall delay of
22 seconds.
NOTE:

For Pager Format, it is not advisable to use the HEX character values (*0 = A, *1 = B, *2 = C, *3 = D, *4 = E, *5 = F) in the report
programming addresses 3207 through 3419. These characters could cause unpredictable results when sent to a pager
system that only expects numeric characters between 0-9. This is the reason that this format will not allow an associated user
number with an open and close report.

The following are recommended programming values for addresses 3207 through 3419 when using the Pager format.
NOTE:

The Pager format is an open-loop format which has no acknowledge tone. There is no indication at the control panel that the
signal has been sent. Therefore, the Pager format is not recommended as the primary communication method.
Refer to the worksheet on the next page for Reports with Restorals. The values for each report can be determined by the
user in conjunction with the installer. Again, the digit “0” (zero) should not be used as the reporting (first) digit as it will affect
other reports in the system. Examples have been provided for possible reporting values, but the values can be set to the
user’s preferences.

DS7400Xi ( 4+) Reference Guide

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 81

Pager Format (Continued)

Reports with Restorals

Suggested Values
Report
Address

Restoral

Value

Address

Trouble

Value

Address

Trouble Restoral

Value

Address

Value

Bypass
Address

Bypass Restoral

Value

Address

Value

Zone Function 1

3209

1

1

3241

6

4

3271

3

1

3301

6

5

3358

6

1

3388

6

6

Zone Function 2

3210

1

2

3242

6

4

3272

3

2

3302

6

5

3359

6

1

3389

6

6

Zone Function 3

3211

1

3

3243

6

4

3273

3

3

3303

6

5

3360

6

1

3390

6

6

Zone Function 4

3212

1

4

3244

6

4

3274

3

4

3304

6

5

3361

6

1

3391

6

6

Zone Function 5

3213

1

5

3245

6

4

3275

3

5

3305

6

5

3362

6

1

3392

6

6

Zone Function 6

3214

1

6

3246

6

4

3276

3

6

3306

6

5

3363

6

1

3393

6

6

Zone Function 7

3215

1

7

3247

6

4

3277

3

7

3307

6

5

3364

6

1

3394

6

6

Zone Function 8

3216

1

8

3248

6

4

3278

3

8

3308

6

5

3365

6

1

3395

6

6

Zone Function 9

3217

1

9

3249

6

4

3279

3

9

3309

6

5

3366

6

1

3396

6

6

Zone Function 10 3218
Zone Function 11 3219

2 0

3250

6 4

3280

4

0

3310

6 5

3367

6 2

3397

6 6

2

1

3251

6 4

3281

4

1

3311

6

5

3368

6

2

3398

6 6

Zone Function 12 3220

2

2

3252

6 4

3282

4 2

3312

6

5

3369

6

2

3399

6 6

Zone Function 13 3221
Zone Function 14 3222

2

3

3253

6 4

3283

4 3

3313

6

5

3370

6

2

3400

6 6

2

4

3254

6 4

3284

4

4

3314

6

5

3371

6

2

3401

6 6

Zone Function 15 3223

2

5

3255

6 4

3285

4

5

3315

6

5

3372

6

2

3402

6 6

Zone Function 16 3224
Zone Function 17 3225

2

6

3256

6

4

3286

4

6

3316

6

5

3373

6

2

3403

6

6

2

7

3257

6

4

3287

4

7

3317

6

5

3374

6

2

3404

6

6

Zone Function 18 3226

2

8

3258

6

4

3288

4

8

3318

6

5

3375

6

2

3405

6

6

Zone Function 19 3227

2

9

3259

6

4

3289

4

9

3319

6

5

3376

6

2

3406

6

6

Zone Function 20 3228
Zone Function 21 3229

3

0

3260

6

4

3290

5

0

3320

6

5

3377

6

2

3407

6

6

3

0

3261

6

4

3291

5

1

3321

6

5

3378

6

3

3408

6

6

Zone Function 22 3230

3

0

3262

6

4

3292

5

2

3322

6

5

3379

6

3

3409

6

6

Zone Function 23 3231
Zone Function 24 3232

3

0

3263

6

4

3293

5

3

3323

6

5

3380

6

3

3410

6

6

3

0

3264

6

4

3294

5

4

3324

6

5

3381

6

3

3411

6

6

Zone Function 25 3233

3

0

3265

6

4

3295

5

5

3325

6

5

3382

6

3

3412

6

6

Zone Function 26 3234

3

0

3266

6

4

3296

5

6

3326

6

5

3383

6

3

3413

6

6

Zone Function 27 3235
Zone Function 28 3236

3

0

3267

6

4

3297

5

7

3327

6

5

3384

6

3

3414

6

6

3

0

3268

6

4

3298

5

8

3328

6

5

3385

6

3

3415

6

6

Zone Function 29 3237

3

0

3269

6

4

3299

5

9

3329

6

5

3386

6

3

3416

6

6

Zone Function 30 3238

3

0

3270

6

4

3300

6

0

3330

6

5

3387

6

3

3417

6

6

Reports with Restorals
Report
Address

Reports without Restorals

Value

Value

Open

3331

9

0

Close

3332

9

1

Restoral

Value

Address

Report
Address

Low Battery

3336

7

0

3337

8

0

AC Fail

3338

7 1

3339

8 1

Partial Close

3334

9

2

System Trouble

3345

7

2

3346

8

2

First Open after Alarm

3335

9

3

Keypad Fire

3207

7

3

3208

8

3

Exit Error

3348

6

7

System Walk Test

3350

7

4

3351

8

4

Recent Closing

3349

9

4

Fire Walk Test

3352

7

5

3353

8

5

Keypad Emergency

3239

9

5

Low Temperature

3354

7

6

3355

8

6

Dirty Smoke Chamber

3356

7

7

3357

8

7

Keypad Panic
Duress

3240
3333

9 6
9 7

Report Successful
Address

Page 82

P/N: F01U035325-01

Value

Report Unsuccessful
Address

Value

Remote Program

3341

8

8

3342

7

8

Local Program

3343

8

9

3344

7

9

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

13.0

Report Programming - Values Sent

13.1

SIA Formats

Reports
Burglary alarm for a zone

Data Digit 2 value SIA Report
Explanation
1
PA
Panic Alarm
2
PR
Panic Restore
3
QA
Emergency Alarm
4
QR
Emergency Restore
5
TA
Tamper Alarm
6
TR
Tamper Restore
7
UA
Untyped Zone Alarm
8
UR
Untyped Zone Restore
9
UT
Untyped Zone Trouble
*0
UJ
Untyped Trouble Restore
*1
YP
Power Supply Trouble
*2
YQ
Power Supply Restore
*3
YX
Service Required

DS7400Xi ( 4+) Reference Guide

SIA
event
code

SIA
data
field

B

Zone
Number
Zone
Number
Zone
Number
Zone
Number

A

Fire alarm for a zone

F

A

Waterflow alarm for a zone

S

A

Supervisory for a zone

S

S

Keypad fire (A)

F

A

000

Keypad fire restoral (A)

F

R

000

Keypad emergency (B)

Q

A

None

Keypad panic (C)

P

A

None

Burglary restoral for a zone

B

R

Fire restoral for a zone

F

R

Waterflow restoral for a zone

S

R

Supervisory restoral for a zone

S

J

Burglary trouble for a zone

B

T

Burglary trouble restoral

B

J

Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number

Fire trouble for a zone

F

T

Fire trouble restoral

F

J

Waterflow trouble for a zone

F

T

Supervisory trouble for a zone

F

T

Burglary Zone Bypass

B

B

Burglary Zone Bypass restoral

B

U

24 Hour Zone Bypass

B

B

24 Hour Zone Bypass restoral

B

U

Keypad Tamper

E

X

Keypad Tamper restoral

E

R

None

T

Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
User
Number
User
Number

Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
Zone
Number
None

Tamper RF zone

T

Tamper, Alarm RF zone

B

A

Tamper restoral RF zone

B

R

Low Battery RF zone

X

T

Low Battery restoral RF zone

B

R

Open report

O

P

Close report

C

L

Duress report

H

A

000

Partial close report

C

G

User
Number

First open after alarm (cancel) report

O

R

None

Low battery

Y

T

None

Low battery restoral

Y

R

None

AC failure

A

T

None

AC failure restoral

A

R

None

Octal relay fault report

E

T

None

Octal relay restoral

E

R

None

Exit error report

E

E

None

Recent closing report

C

R

None

System walk test start report

T

S

None

System walk test end report

T

E

None

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 83

13.1 SIA Formats (Continued)
Reports

Page 84

P/N: F01U035325-01

SIA
event
code

SIA
data
field

Fire walk test report

F

I

Fire walk test restoral

F

K

None
Zone
Number
Zone
Number
Zone
Number
Zone
Number

Dirty Smoke Chamber report

M

C

Dirty Smoke Chamber restoral

M

O

Mux. Smoke low temperature report

M

F

None

Mux. Smoke low temperature restoral

M

R

Automatic system normal test report

R

P

None

Manual communicator test report

R

X

None

Remote programming successful report

R

S

None

Remote programming failure report

R

U

None

Local programming successful report

Y

G

None

Local programming failure report

Y

F

None

Communication failure report

Y

C

None

Communication restoral

Y

K

None

EEPROM checksum failure or keypad supervision failure report

E

T

None

EEPROM checksum restoral or keypad supervision restoral

E

R

None

Multiplex bus fault

E

T

None

Multiplex bus restoral

E

R

None

Radio receiver tamper

X

S

Receiver
Number

Radio receiver tamper restoral

X

J

Receiver
Number

Radio receiver jammed

X

Q

Receiver
Number

Radio receiver jammed restoral

X

H

Receiver
Number

Radio receiver trouble report

X

Q

Receiver
Number

Radio receiver trouble restoral

X

H

Receiver
Number

RF Zone Missing

T

T

Receiver
Number

Aux. power fault report

Y

P

None

Aux. power restoral

Y

Q

None

Ground fault report

U

T

None

Ground fault restoral

U

J

None

Automatic system off normal test report

R

P

None

Phone line 1 fault report

L

T

None

Phone line 1 restoral

L

R

None

Phone line 2 fault report

L

T

None

Phone line 2 restoral

L

R

None

DS7416i fault report

Y

S

See 8.13.6
Error Displays

DS7416i fault restoral

Y

K

See 8.13.6
Error Displays

Bell fault report

E

T

None

Bell fault restoral

E

R

None

RAM fault report

E

T

None

RAM fault restoral

E

R

None

ROM fault report

E

T

None

ROM fault restoral

E

R

None

Serial interface fault report

V

T

None

Serial interface restoral

V

R

None

Aux. relay fault report

E

T

None

Aux. relay restoral

E

R

None

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

13.2

CID Formats
Reports
Fire alarm for a zone
Fire restoral for a zone
Keypad fire (A)
Keypad fire restoral (A)
Waterflow alarm for a zone
Waterflow restoral for a zone
Duress report

CID
event
code

CID
data
field

Reports

110

Zone
Number

Keypad Tamper

110
Restoral

Zone
Number

110

000

Radio receiver tamper

110
Restoral

000

Radio receiver tamper restoral

113

Zone
Number

Radio receiver jammed

113
Restoral

Zone
Number

Radio receiver jammed restoral

121

000

Keypad Tamper restoral

Phone line 1 fault report

CID
event
code

CID
data
field

341

None

341
Restoral

None

341

Receiver
Number

341
Restoral

Receiver
Number

344

Receiver
Number

344
Restoral

Receiver
Number

351

None

351
Restoral

None

352

None

Keypad emergency (B)

122

None

Phone line 1 restoral

Keypad panic (C)

123

None

Phone line 2 fault report

130

Zone
Number

130
Restoral

Zone
Number

130

Zone
Number

130
Restoral

Zone
Number

354

None

Mux. Smoke low temperature report

159

Zone
Number

Communication restoral

354
Restoral

None

Mux Smoke low temperature restoral

159
Restoral

Zone
Number

Tamper restoral RF zone

370
Restoral

Zone
Number

200

Zone
Number

Burglary trouble for a zone

370

Zone
Number

200
Restoral

Zone
Number

Burglary trouble restoral

370
Restoral

Zone
Number

300

None

Fire trouble for a zone

373

Zone
Number

300
Restoral

None

Fire trouble restoral

373
Restoral

Zone
Number

301

None

Waterflow trouble for a zone

373

Zone
Number

301
Restoral

None

Supervisory trouble for a zone

373

Zone
Number

302

None

RF Zone Missing

381

Zone
Number

302
Restoral

None

Tamper RF zone

383

Zone
Number

303

None

Low Battery RF zone

384

303
Restoral

None

Dirty Smoke Chamber report

385

Zone
Number
Zone
Number

304

None

Dirty Smoke Chamber restoral

385
Restoral

Zone
Number

304
Restoral

None

Open report

401

User
Number

306

None

Close report

401
Restoral

User
Number

306
Restoral

None

Recent closing report

405

None

310

None

First open after alarm (cancel) report

406

None

310
Restoral

None

Remote programming successful report

412

None

320

004

Remote programming failure report

413

None

320
Restoral

004

Partial close report

456
Restoral

User
Number

321

003

Exit error report

457

None

003

Burglary Zone Bypass

573

Zone
Number

573
Restoral

Zone
Number

573

Zone
Number

573
Restoral

Zone
Number

Burglary alarm for a zone
Burglary restoral for a zone
Tamper, Alarm RF zone
Low Battery restoral RF zone

Supervisory for a zone
Supervisory restoral for a zone
Aux. power fault report
Aux. power restoral
AC failure
AC failure restoral
Low battery
Low battery restoral
RAM fault report
RAM restoral
ROM fault report
ROM restoral
Local programming successful report
Local programming failure report
Ground fault report
Ground fault restoral
Aux. relay fault report
Aux. relay restoral
Bell fault report
Bell restoral
Octal relay fault report
Octal relay restoral
Keypad supervision failure report
Keypad supervision restoral
Multiplex bus fault
Multiplex bus restoral
Radio receiver trouble report
Radio receiver trouble restoral
Serial interface fault report
Serial interface restoral

DS7400Xi ( 4+) Reference Guide

321
Restoral

Phone line 2 restoral
DS7416i fault report*
*The 2-digit #89 display System
Fault numbers will be sent in the
CID data field for DS7416i fault DS7416i fault restoral*
reports.
Communication failure report

330

005

Burglary Zone Bypass restoral

330
Restoral

005

24 Hour Zone Bypass

352
Restoral

None

353

See 15.4
Gen Sys Prob

353
Restoral

See 15.4
Gen Sys Prob

330

None

330
Restoral

None

Manual communicator test report

601

None

333

None

Automatic system normal test report

602

None

333
Restoral

None

Automatic system off normal test report

602

None

333

Receiver
Number

Fire walk test report

604

None

333
Restoral

Receiver
Number

Fire walk test restoral

604
Restoral

None

336

None

System walk test start report

607

None

System walk test end report

607
Restoral

None

336
Restoral

None

24 Hour Zone Bypass restoral

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 85

14.0

Multiplex Zone Addressing Guide

Before installing a multiplex device, its address and other
information must be programmed into the control panel. (To disable
or remove a multiplex point, set the program address for 00 [see
Section 10.4]).
If using a DS7436 Multiplex Expansion Module,
programming must be done using bus “A.”
Perform the following:
• Program the control panel.
- Refer to sections 10.2-10.5, Zone Programming.
These sections allow you to define the Multiplex Zone’s
address (zone number), its type (single or multiple zone input
device, a DS7465, a Multiplex Smoke or a Multiplex Smoke
with a Low Temperature Alarm), which zone or output function
it will follow (1-24) and its partition (1-8).
For example:Program zone 9 to be a single zone input device
(MX950 ) that follows zone function 1 and is in
partition 1.
Procedure:

Enter the programmer’s mode.
Enter address 0039.
Enter the data digits as [0] and [1] followed by the
[#] button.
Enter address 0291.
Enter the data digits as [0] and [0] followed by the
[#] button.
Exit the programmer’s mode.

• Program the BusLoc® feature.
At this point, you must decide whether or not to use the BusLoc®
feature.
BusLoc® is a proprietary method of tying the multiplex zones to
the control panel to prevent the system from being taken over.
Using BusLoc® will program an invisible identification code into
the multiplex zones.
NOTE: If using the DS7432 8-Input Remote Module or the DS7433
8-Input Direct Module, the BusLoc® feature can not be
used.
- If you choose to use the BusLoc® feature, program a 5-digit
code at programming address 9999.
It is very important to save this code under lock and key. If
you need to replace the control panel, you will have to program
it with the same BusLoc® code as the previous panel or the
multiplex devices will not match codes with the new control
panel.
For example:Program the BusLoc® code to be 54321.
Procedure:

Enter the programmer’s mode.
Enter address 9999.
Enter the data digits as [5], [4], [3], [2], and [1]
followed by the [#] button.
Exit the programmer’s mode.

Once the pre-programming is done, you are ready to program the
multiplex devices. Perform the following:
• Disconnect all multiplex devices from the DS7430.
• Program the multiplex devices through the control panel. Perform the following:
- Enter the programmer’s mode.
- Enter the multiplex programming mode.
Do this by entering [9] [9] [9] [5] followed by the [#] button.
Page 86

P/N: F01U035325-01

- The control will then take a few seconds to check the multiplex
connection to confirm nothing is connected to it. The display
will show the following:

- The display will then call-up the first zone you have preprogrammed to be a multiplex zone. To access a different
zone, press the [Reset/*] key, then enter the three digit value of
the zone you want. The display will show the following:

Before you do anything else, reconnect the multiplex device (that
coincides with the displayed zone) to the multiplex bus of the
DS7430.
For DS7465s and Multiple Input devices, pressing the [#] button
now will program these devices to the control panel. Remember,
these devices take up two addresses. When address 009 (for
example) is a DS7465, pressing the [#] button now will program
both addresses 009 and 010.
For Single Input devices, press the [#] button to continue
programming. The display asks whether you are programming a
sensor or a contact; it will show the following:

If you are programming a sensor, press the [4] button to program
these devices to the control panel. If you are programming a contact,
press the [6] button to program these devices to the control panel.
- If the device is successfully programmed, the keypad will
sound a single beep and increment to the next zone (if there is
one) pre-programmed as a multiplex zone.
Disconnect the device you just programmed and
connect the next device (that belongs to the displayed
zone) to the multiplex bus of the DS7430 and press
the [#] button. Continue programming.
24-hour zones will alarm when you exit the
programmer’s mode. Alarm reports for these zones
will be sent if they have been programmed. If you do
not want these reports sent, disconnect power from
the system now by unplugging the transformer and
removing the red battery lead. Do not reconnect power
until all zones have been installed and connected to
the multiplex bus.
- If no other zones have been pre-programmed, the display will
show the following:

- You may now exit the Zone Programmer’s mode by pressing
the [*/Reset] button for 2 seconds. This brings you back to the
Programmer’s Mode. To exit the Programmer’s Mode, press
the [*/Reset] button for 2 seconds.
- If the zone is unsuccessfully programmed, the keypad will
sound a three-beep error tone.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

15.0

Troubleshooting Guide

15.1

Keypad Problems
Symptom

Probable Cause

Possible Solution

Entry Error: Please Re-enter will
display on keypad. A three beep error
tone will sound continuously.

a) Two or more keypads share the same
address.

a) Install keypad jumper properly in back of
keypads.

b) The DS7430 or DS7433 is installed in
the wrong pins.

b) Be sure the DS7430 or DS7433 is installed
properly.

a) The keypad not addressed properly.

a) Install the keypad jumper properly in the back of
the keypad.

b) The keypad is not programmed
properly.

b) Check keypad programming addresses 31313138.

c) Keypads 11-15 are not properly
configured.

c) Check keypad addresses 11-15. System will
only see keypads on the options bus.

Keypad displays Ready to arm,
partition 1 when using only one
partition.

The keypad is programmed as a Master
keypad.

Master keypads can only be used on multi-partition
systems. Program the keypad as a standard
keypad.

Keypad displays System Fault,
sounder is on, and the keypad does
not operate.

a) Keypad wiring error.

a) Check wiring.

b) Keypad(s) assigned to wrong or nonexistent partition.

b) Assign the keypad(s) to correct partition. If none
of the keypads are correctly assigned, re-enable
keypad 1 by shorting the program contacts in
the lower right corner of the main panel board.
This will force program mode and assign
keypad 1 as alpha, non-master to partition 1.

c) The microprocessor isn’t running.

c) Disconnect battery and any aux. power load. If
the microprocessor has shut down, aux. power
will read approx. 11.5 VDC. If the EEProm chip
has been field-replaced, power down AC and
battery, and check for bent or mis-inserted pins;
Otherwise, replace the panel.

Keypad alpha display is locked up,
but the keys still function.

The keypad is enabled, but as an LED
keypad.

Enter the program mode at the keypad and input
the correct sequence to re-enable it as an alpha
keypad. Care must be taken, since there will be no
visual feedback to verify programming until the
keypad is properly enabled.

Can’t read back history with # 89
input.

a) Entering from Master keypad.

a) First enter Single Partition Mode.

b) Not using a PIN with test authority.

b) Use a PIN with test authority.

In history, the Read-back for the A, B,
and C keys shows:
A = Fire
B = Emergency
C = Panic
But,
the
Central
Station
transmissions display B as Silent
Panic and C as Audible Panic.

Formats display information regarding the
B and C keys differently.
In Contact ID: A = Fire
B = Silent Panic
C = Audible Panic

Discrepancy exists in the definition of these keys in
the two formats. Whatever the keys are
programmed for in the panel, that is what will be
sent.

Can not perform a zone test (#81).

a) Entering from a Master keypad.

a) Zone test is not available from a Master keypad.

b) Not using a PIN with test authority.

b) Use a PIN with test authority.

Keypad displays Not Programmed,
See Instal Guide, sounder is on and
the keypad does not operate.

DS7400Xi ( 4+) Reference Guide

In SIA:

A = Fire
B = Emergency
C = Panic

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 87

Keypad Problems (Continued)
Symptom
Chime Mode (#7) does not work
when a zone is faulted.

Some functions won’t work on a
Master keypad.

15.2

Probable Cause

Possible Solution

a) Not activating for interior zones.

a) Chime mode only activates for perimeter zones
- Chime mode must be programmed. Also, if
the perimeter zone has trouble enabled (trouble
on open), the chime won’t work if that zone is
opening.

b) The keypad is not assigned to the same
partition as the zone being activated.

b) Chime mode will only activate the sounder on
keypads that are assigned to the same partition
as the zone.

Some functions require you to enter single
partition mode when using a Master
keypad.

The following commands require that you are in
Single Partition Mode when entering from a Master
keypad:
• History read-back
• Chime mode
• Checking zone status
• Checking zone trouble status (after #87 - Master
keypad will show only partition name)
• Bypassing zones

Probable Cause

Possible Solution

Reporting Problems
Symptom

Won’t send open or close reports.

Not programmed correctly.

Check addresses: 3331, 3332, 3334, and 3333.

Reports for partitions 2-8 are being The account codes for 2-8 are not pro- Check addresses: 3429-3459.
sent with partition 1’s reporting ID. grammed or are not programmed correctly.
a) AC power fail messages are sent only
with other reports, such as low battery.

a) Try forcing another report to send when AC is
not present.

b) Check AC report offset (3338). If 00, AC
report will work like above, if another
number, AC report will be delayed.

b) Wait until the delay times out or set to a lower
number if desired.

a) Not programmed to send history.

a) Check programming.

b) Time and date not set.

b) Verify that the time in the panel is set.

a) Report not programmed properly.

a) Check programming addresses 4022, 4023,
4026, and 3340.

b) There was a control problem at the time
the report should have been sent. If this
is the case, the communicator test
report will not be sent. Instead, the
control will send the “System Off
Normal” report.

b) Program “System Off Normal” report in address
3347.

Symptom

Probable Cause

Possible Solution

Fire Alarm displays on keypad but
no zone numbers are displayed.

In Commercial Fire Mode, fire alarms must
be silenced before the zone number will
display.

Enter a valid disarm PIN and press #, then enter a
valid disarm PIN and press # again to display the
zones.

Every other zone displays Not Ready.

Zone Programming is incorrect.

Program as a multiple zone input for DS7432 or
DS7460, a single zone input for contacts and
sensors, or program as a DS7465.

Not getting AC power fail reports.

Panel never transmits history to
WDSRP.
The communicator test report is not
being sent.

15.3

Page 88

Zone Problems

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Zone Problems (Continued)
Symptom

Probable Cause

Possible Solution

Zones 9 and above show Not Ready,
Zone Trouble.

a) The multiplex expansion module is not
installed properly.

a) Make sure the multiplex expansion module is
seated properly in the upper pins on the
DS7400Xi circuit board.

b) Multiplex wiring is missing or is not
installed properly.

b) Check wiring and perform a system reset.

c) 8-Input remote module DIP switches
are not set properly.

c) Correctly set the DIP switches for the 8-Input
remote modules.

d) 8-Input remote module covers are
removed.

d) Replace covers or install the tamper bypass
jumper.

e) The BusLoc® code is set incorrectly or
has not been programmed into
modules.

e) BusLoc® can not be used with 8-Input remote
modules. If using 8-Input modules, remove the
BusLoc® code.
OR
If using two-input remote modules or the
DS7465, be sure to use BusLoc® when
programming. If not using BusLoc®, be sure to
remove the BusLoc® code from address 9999.

Never disconnect the
power when in the
programming mode.
Always disconnect the
Multiplex Bus or have the
DS7430 or DS7436 in
the
disable
programming
mode
when powering up or
down.

f) Zone Programming is incorrect.

f) Program as a multiple zone input for DS7432 or
DS7460, a single zone input for contacts and
sensors, or program as a DS7465.
g) Program the module.

g) Multiplex module not programmed.
h) Multiplex Bus voltage is 12VDC or
greater. (Normal is approximately 8 to
10VDC.)

i) Multiplex Bus voltage is 5VDC or less.

Invisible or silent zone activates
alarm output.
Keypad displays Fire Trouble, but
does not indicate any zones.
Keypad displays Not Ready, but no
zone number is displayed.

15.4

h) Two modules are programmed with the same
address. The problem will only occur when both
modulees are off normal. Isolate the duplicate
module by disconnecting sections of the bus
and performing a [PIN] + [System Reset].
Reprogram modules.
OR
The system is in the programming mode. Exit
the programming mode.
OR
Zones have been added to a system protected
by Busloc®. Clear Busloc®.
i) There is a short on the multiplex bus.
OR
There is a bad module on the bus.
OR
One or more modules on the bus are connected
backwards - reverse polarity.

(Normal is approximately 8 to 10VDC.)
The output is programmed as “latch on
alarm” (0).
A ground fault condition exists.

Program the output to follow zone alarms (6).

An invisible zone is not ready.

Press [PIN] + [OFF] to display the zone number of
the invisible zone that is not ready.

See system trouble: Ground fault.

General System Problems
Symptom

How to set the programming values
to the factory default.

DS7400Xi ( 4+) Reference Guide

Probable Cause
Enter a value of 01 in address 4058.

Possible Solution
Caution:

Copyright © 2007 Bosch Security Systems, Inc.

Only enter a value of 01 in address
4058 when you are sure you want to
default the programming. Doing so will
immediately erase all programming.
P/N: F01U035325-01

Page 89

General System Problems (Continued)
Symptom

Probable Cause

Possible Solution

Power LED is flashing, keypad A control trouble exists.
displays Control Trouble Press #87.

Press #87 to determine the trouble condition.

#87 display = Oct. Relay Fault
#89 display = System Fault 20

a) Check the wiring to the module.

a) The octal relay module (DS7488) is
defective or the wiring to the module is
defective.
b) There is no DS7488 or a DS7488 has
been removed from the system.

b) Enter, then exit programming mode. This will rescan the options bus and clear the problem.

#87 display = Multiplex Bus Fault

The Multiplex Bus is defective or shorted.

Check wiring for shorts.

Can’t reset to factory default.

Keypad programming access is set to
PARTIAL from Remote programmer.

Change setting to FULL from the Remote
programmer.

#87 display = RAM Fault
#89 display = System Fault 01
or

a) An EEProm fault can be caused by
disconnecting power from the control while it is
in program mode. In this case, enter then exit
program mode to clear.

#87 display = ROM Fault
#89 display = System Fault 02

b) Try to clear the error at the keypad by entering a
PIN then Reset.

or

c) Remove AC and battery power, then re-apply.
Remember that event history will be lost and
time/date will have to be re-set.

#87 display = EEProm Fault
#89 display = System Fault 03

d) If error persists, return the panel to factory default
programming by setting program address 4058
to “01”. If the error clears, re-program the panel.
e) If error still persists, replace the panel.
#87 display = Communicator Err
#89 display = Report Failure X

The control has failed to communicate.

Check history #89 to determine the source:
Report Failure 1 = Phone number 1
Report Failure 2 = Phone number 2
Report Failure 3 = Phone number 3
(remote programmer)
Report Failure 4 = DS7416i Communications fault

#87 display = 2Ph/Bell Fault
#89 display = System Fault 10

#87 display = Line 1 Fault
#89 display = System Fault 11

a) The dual phone line/bell supervision
module (DS7420i) is defective or the
wiring to the module is defective.

a)Check the wiring to the module.

b) There is no DS7420i or a DS7420i has
been removed from the system.

b) Enter, then exit programming mode. This will rescan the options bus and clear the problem.

There is a phone line fault on line 1.

Check phone line 1 for proper operation.

#87 display = Line 2 Fault
#89 display = System Fault 12

Check phone line 2 for proper operation. If you wish
to monitor only one phone line, reprogram address
4021.

#87 display = Bell Fault
#89 display = System Fault 13

There is a phone line fault on line 2.

Check the bell circuit wiring. Be sure that the endof-line resistor is in place. If you don’t wish to use
the bell circuit, place an end-of-line resistor across
the bell terminals.

#87 display = Aux. Output Fault
#89 display = System Fault 14

The bell circuit on the DS7420i is open or
shorted.
The auxiliary circuit on the DS7420i is open
or shorted.

Check the auxiliary circuit wiring. Be sure that the
end-of-line resistor is in place. If you don’t wish to
use the auxiliary circuit, place an end-of-line resistor
across the auxiliary terminals. If you wish to use the
auxiliary circuit but do not wish to supervise it, cut
the auxiliary supervision jumper on the DS7420i.

Page 90

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

General System Problems (Continued)
Symptom

Probable Cause

Possible Solution

#87 display = Aux Power Fault

The auxiliary power output has been
shorted.

Remove wiring from auxiliary power and check for
shorts.

#87 display = Keypad Fault

a) The keypad wiring is defective.

a) Check keypad operation and wiring.

b) A keypad is missing.

b) Install a keypad.

c) A keypad has been programmed, but is
not intended in this system.

c) Remove from programming (3131-3138).

There is a short to ground somewhere in
the system.

Disconnect field wiring from each terminal while
watching the keypad display. When the keypad power
LED stops flashing, you have found the wire that is
causing the ground fault.

#87 display = Ground Fault
#89 display = System Fault 04

Note:

The LED will not stop flashing if there is
another system fault present.

If there is no keypad nearby, or another control
problem exists, you can use a volt-meter to find the
ground fault:
1) Connect the negative lead of a volt-meter to the
panel ground terminal.
2) Connect the positive terminal to the Aux Power –
terminal.
You should read -4.5 to -7.5 Volts DC. A reading
considerably higher or lower indicates a ground
fault.
Disconnect field wiring from each terminal while
watching the meter. When the voltage reading
returns to between -4.5 and -7.5 VDC, you have
found the wire that is causing the ground fault.
#87 display = AR IB Queue Full
#89 display = System Fault 51

The message queue in the RF modem is
full and no messages can get out to the
radio network.

Check RF coverage of the unit and check for RF
noisy environment.

#87 display = AR Host Down
#89 display = System Fault 52

The central station receiver has ceased to
be available to the network.

Contract the central station and notify of status.

#87 display = AR Unreg. Modem
#89 display = System Fault 53

The modem is not registered through all
parts of the network.

Contact the network administrators or technical
service.

#87 display = AR Power Fail
#89 display = System Fault 54

There is a possible problem with the
DS7416i Module.

Return for service.

#87 display = AR Network Lost
#89 display = System Fault 55

The DS7416i Module has lost contact with
the radio network.

Check the location and coverage of the unit.

#87 display = AR Modem HW Err
#89 display = System Fault 56

There is a possible problem with the radio
modem.

Replace the unit.

#87 display = AR Modem SW Err
#89 display = System Fault 57

The DS7416i Module is having trouble
communicating with the radio modem.

Check for noisy environment and replace the unit if
the problem continues.

#87 display = AR Opt. Bus Err
#89 display = System Fault 58

The panel can no longer communicate
with the DS7416i Module.

Check the wiring between the DS7400Xi and the
DS7416i Module.

#87 display = AR Corrupt MSG
#89 display = System Fault 59

The communication between the panel
and the DS7416i Module is getting
corrupted.
a) Zone(s) faulted.

Check for noisy environment, and check the wiring
between the DS7400Xi and the DS7416i Module.

b) If an AC failure exists, you must force
arm.

b) Enter an arming sequence, then press the
Bypass key during a 5 second beep.

Unable to arm the system.

DS7400Xi ( 4+) Reference Guide

a) Determine the cause of the problem and clear
the indicated zone(s).

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 91

General System Problems (Continued)
Symptom
#87 display = Battery Trouble

#87 display = Zone Trouble

Probable Cause

Possible Solution

a) The battery failed a battery test.

a) If there has just been a power failure, wait at
least two hours for the battery to recharge then
perform a System Reset to re-test the battery
and clear the error.

b) The battery is defective.

b) Replace the battery.

c) The wiring to the battery is
disconnected.

c) Check wiring.

a) A zone is not responding to the control
panel.

a) Check wiring to the zone.
or
If the zone is not to be used, remove from
programming.

b) The zone is programmed for “Trouble
on Open” and the loop is open.
There is a power failure and the panel is
operating on battery backup. If there is a
general power failure, wait for the power to
return. If there is not a general power failure
in the building.

b) If using Normally Closed contacts, re-program
zone for alarm on open.
or
If using Normally Open contacts and trouble on
open is desired, check for opens in the loop.
Remove wiring and place an EOL resistor across
the zone to eliminate a problem with the control.
If the trouble goes away, the problem is in the
wiring or in a contact connected to the zone.

a) The transformer is unplugged.

a) Plug the transformer in.

b) The wiring from the transformer is
defective.

b) Check the wiring.

c) The circuit to the transformer is off or
defective.

c) Check the circuit and circuit breakers.

d) The transformer is defective.

d) Replace the transformer.

e) In some cases, the transformer may
be connected to a circuit controlled by
a switch or a circuit breaker that is
periodically turned off.

e) Connect to a circuit that is not controlled this
way.

Fire Alarm displays “000”.

The Fire Alarm was caused by the “A” key.

Use the System Reset command to clear the
display.

Fire Trouble, no zone number.

When in Commercial Fire Mode, a ground
fault causes this display.

See #87 Ground Fault display for solution.

Fire Trouble ____________
zone number. Dirty

Fire zone wiring problems.

If you try to disable the zone by reprogramming it,
you need to reset the control by either entering then
exiting programmer’s mode, or removing then
restoring power to the control panel.

Chamber ____________
zone number.

A multiplex smoke detector has failed its
internal sensitivity test.

Clean or replace the dirty smoke detector or
chamber. DO NOT USE WATER TO CLEAN THE
CHAMBER.

#87 display = AC Power Failure

Page 92

P/N: F01U035325-01

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

16.0

Program Addresses

Address Description
0000
General Control
0001
Zone Function 1
0002
Zone Function 2
0003
Zone Function 3
0004
Zone Function 4
0005
Zone Function 5
0006
Zone Function 6
0007
Zone Function 7
0008
Zone Function 8
0009
Zone Function 9
0010
Zone Function 10
0011
Zone Function 11
0012
Zone Function 12
0013
Zone Function 13
0014
Zone Function 14
0015
Zone Function 15
0016
Zone Function 16
0017
Zone Function 17
0018
Zone Function 18
0019
Zone Function 19
0020
Zone Function 20
0021
Zone Function 21
0022
Zone Function 22
0023
Zone Function 23
0024
Zone Function 24
0025
Zone Function 25
0026
Zone Function 26
0027
Zone Function 27
0028
Zone Function 28
0029
Zone Function 29
0030
Zone Function 30
0031
Zone Number 1
0032
Zone Number 2
0033
Zone Number 3
0034
Zone Number 4
0035
Zone Number 5
0036
Zone Number 6
0037
Zone Number 7
0038
Zone Number 8
0039
Zone Number 9
0040
Zone Number 10
0041
Zone Number 11
0042
Zone Number 12
0043
Zone Number 13
0044
Zone Number 14
0045
Zone Number 15
0046
Zone Number 16
0047
Zone Number 17
0048
Zone Number 18
0049
Zone Number 19
0050
Zone Number 20
0051
Zone Number 21
0052
Zone Number 22
0053
Zone Number 23
0054
Zone Number 24
0055
Zone Number 25
0056
Zone Number 26
0057
Zone Number 27
0058
Zone Number 28
0059
Zone Number 29
0060
Zone Number 30
0061
Zone Number 31
0062
Zone Number 32
DS7400Xi ( 4+) Reference Guide

Address Description
0063
Zone Number 33
0064
Zone Number 34
0065
Zone Number 35
0066
Zone Number 36
0067
Zone Number 37
0068
Zone Number 38
0069
Zone Number 39
0070
Zone Number 40
0071
Zone Number 41
0072
Zone Number 42
0073
Zone Number 43
0074
Zone Number 44
0075
Zone Number 45
0076
Zone Number 46
0077
Zone Number 47
0078
Zone Number 48
0079
Zone Number 49
0080
Zone Number 50
0081
Zone Number 51
0082
Zone Number 52
0083
Zone Number 53
0084
Zone Number 54
0085
Zone Number 55
0086
Zone Number 56
0087
Zone Number 57
0088
Zone Number 58
0089
Zone Number 59
0090
Zone Number 60
0091
Zone Number 61
0092
Zone Number 62
0093
Zone Number 63
0094
Zone Number 64
0095
Zone Number 65
0096
Zone Number 66
0097
Zone Number 67
0098
Zone Number 68
0099
Zone Number 69
0100
Zone Number 70
0101
Zone Number 71
0102
Zone Number 72
0103
Zone Number 73
0104
Zone Number 74
0105
Zone Number 75
0106
Zone Number 76
0107
Zone Number 77
0108
Zone Number 78
0109
Zone Number 79
0110
Zone Number 80
0111
Zone Number 81
0112
Zone Number 82
0113
Zone Number 83
0114
Zone Number 84
0115
Zone Number 85
0116
Zone Number 86
0117
Zone Number 87
0118
Zone Number 88
0119
Zone Number 89
0120
Zone Number 90
0121
Zone Number 91
0122
Zone Number 92
0123
Zone Number 93
0124
Zone Number 94
0125
Zone Number 95

Address Description
0126
Zone Number 96
0127
Zone Number 97
0128
Zone Number 98
0129
Zone Number 99
0130
Zone Number 100
0131
Zone Number 101
0132
Zone Number 102
0133
Zone Number 103
0134
Zone Number 104
0135
Zone Number 105
0136
Zone Number 106
0137
Zone Number 107
0138
Zone Number 108
0139
Zone Number 109
0140
Zone Number 110
0141
Zone Number 111
0142
Zone Number 112
0143
Zone Number 113
0144
Zone Number 114
0145
Zone Number 115
0146
Zone Number 116
0147
Zone Number 117
0148
Zone Number 118
0149
Zone Number 119
0150
Zone Number 120
0151
Zone Number 121
0152
Zone Number 122
0153
Zone Number 123
0154
Zone Number 124
0155
Zone Number 125
0156
Zone Number 126
0157
Zone Number 127
0158
Zone Number 128
0159
Zone Number 129
0160
Zone Number 130
0161
Zone Number 131
0162
Zone Number 132
0163
Zone Number 133
0164
Zone Number 134
0165
Zone Number 135
0166
Zone Number 136
0167
Zone Number 137
0168
Zone Number 138
0169
Zone Number 139
0170
Zone Number 140
0171
Zone Number 141
0172
Zone Number 142
0173
Zone Number 143
0174
Zone Number 144
0175
Zone Number 145
0176
Zone Number 146
0177
Zone Number 147
0178
Zone Number 148
0179
Zone Number 149
0180
Zone Number 150
0181
Zone Number 151
0182
Zone Number 152
0183
Zone Number 153
0184
Zone Number 154
0185
Zone Number 155
0186
Zone Number 156
0187
Zone Number 157
0188
Zone Number 158

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 93

Address Description
0189
Zone Number 159
0190
Zone Number 160
0191
Zone Number 161
0192
Zone Number 162
0193
Zone Number 163
0194
Zone Number 164
0195
Zone Number 165
0196
Zone Number 166
0197
Zone Number 167
0198
Zone Number 168
0199
Zone Number 169
0200
Zone Number 170
0201
Zone Number 171
0202
Zone Number 172
0203
Zone Number 173
0204
Zone Number 174
0205
Zone Number 175
0206
Zone Number 176
0207
Zone Number 177
0208
Zone Number 178
0209
Zone Number 179
0210
Zone Number 180
0211
Zone Number 181
0212
Zone Number 182
0213
Zone Number 183
0214
Zone Number 184
0215
Zone Number 185
0216
Zone Number 186
0217
Zone Number 187
0218
Zone Number 188
0219
Zone Number 189
0220
Zone Number 190
0221
Zone Number 191
0222
Zone Number 192
0223
Zone Number 193
0224
Zone Number 194
0225
Zone Number 195
0226
Zone Number 196
0227
Zone Number 197
0228
Zone Number 198
0229
Zone Number 199
0230
Zone Number 200
0231
Zone Number 201
0232
Zone Number 202
0233
Zone Number 203
0234
Zone Number 204
0235
Zone Number 205
0236
Zone Number 206
0237
Zone Number 207
0238
Zone Number 208
0239
Zone Number 209
0240
Zone Number 210
0241
Zone Number 211
0242
Zone Number 212
0243
Zone Number 213
0244
Zone Number 214
0245
Zone Number 215
0246
Zone Number 216
0247
Zone Number 217
0248
Zone Number 218
0249
Zone Number 219
0250
Zone Number 220
0251
Zone Number 221
0252
Zone Number 222
0253
Zone Number 223
Page 94

P/N: F01U035325-01

Address Description
0254
Zone Number 224
0255
Zone Number 225
0256
Zone Number 226
0257
Zone Number 227
0258
Zone Number 228
0259
Zone Number 229
0260
Zone Number 230
0261
Zone Number 231
0262
Zone Number 232
0263
Zone Number 233
0264
Zone Number 234
0265
Zone Number 235
0266
Zone Number 236
0267
Zone Number 237
0268
Zone Number 238
0269
Zone Number 239
0270
Zone Number 240
0271
Zone Number 241
0272
Zone Number 242
0273
Zone Number 243
0274
Zone Number 244
0275
Zone Number 245
0276
Zone Number 246
0277
Zone Number 247
0278
Zone Number 248
0287
Zone 1 & 2 Partitin Assign.
0288
Zone 3 & 4 Partition Assign.
0289
Zone 5 & 6 Partition Assign.
0290
Zone 7 & 8 Partition Assign.
0291
Zone 9 & 10 Partition Assign.
0292
Zone 11 & 12 Partition Assign.
0293
Zone 13 & 14 Partition Assign.
0294
Zone 15 & 16 Partition Assign.
0295
Zone 17 & 18 Partition Assign.
0296
Zone 19 & 20 Partition Assign.
0297
Zone 21 & 22 Partition Assign.
0298
Zone 23 & 24 Partition Assign.
0299
Zone 25 & 26 Partition Assign.
0300
Zone 27 & 28 Partition Assign.
0301
Zone 29 & 30 Partition Assign.
0302
Zone 31 & 32 Partition Assign.
0303
Zone 33 & 34 Partition Assign.
0304
Zone 35 & 36 Partition Assign.
0305
Zone 37 & 38 Partition Assign.
0306
Zone 39 & 40 Partition Assign.
0307
Zone 41 & 42 Partition Assign.
0308
Zone 43 & 44 Partition Assign.
0309
Zone 45 & 46 Partition Assign.
0310
Zone 47 & 48 Partition Assign.
0311
Zone 49 & 50 Partition Assign.
0312
Zone 51 & 52 Partition Assign.
0313
Zone 53 & 54 Partition Assign.
0314
Zone 55 & 56 Partition Assign.
0315
Zone 57 & 58 PartitionAssign.
0316
Zone 59 & 60 Partition Assign.
0317
Zone 61 & 62 Partition Assign.
0318
Zone 63 & 64 Partition Assign.
0319
Zone 65 & 66 Partition Assign.
0320
Zone 67 & 68 Partition Assign.
0321
Zone 69 & 70 Partition Assign.
0322
Zone 71 & 72 Partition Assign.
0323
Zone 73 & 74 Partition Assign.
0324
Zone 75 & 76 Partition Assign.
0325
Zone 77 & 78 Partition Assign.
0326
Zone 79 & 80 Partition Assign.

Address Description
0327
Zone 81 & 82 Partition Assign.
0328
Zone 83 & 84 Partition Assign.
0329
Zone 85 & 86 Partition Assign.
0330
Zone 87 & 88 Partition Assign.
0331
Zone 89 & 90 Partition Assign.
0332
Zone 91 & 92 Partition Assign.
0333
Zone 93 & 94 Partition Assign.
0334
Zone 95 & 96 Partition Assign.
0335
Zone 97 & 98 Partition Assign.
0336
Zone 99 & 100 Partition Assign.
0337
Zone 101 & 102 Partition Assign.
0338
Zone 103 & 104 Partition Assign.
0339
Zone 105 & 106 Partition Assign.
0340
Zone 107 & 108 Partition Assign.
0341
Zone 109 & 110 Partition Assign.
0342
Zone 111 & 112 Partition Assign.
0343
Zone 113 & 114 Partition Assign.
0344
Zone 115 & 116 Partition Assign.
0345
Zone 117 & 118 Partition Assign.
0346
Zone 119 & 120 Partition Assign.
0347
Zone 121 & 122 Partition Assign.
0348
Zone 123 & 124 Partition Assign.
0349
Zone 125 & 126 Partition Assign.
0350
Zone 127 & 128 Partition Assign.
0351
Zone 129 & 130 Partition Assign.
0352
Zone 131 & 132 Partition Assign.
0353
Zone 133 & 134 Partition Assign.
0354
Zone 135 & 136 Partition Assign.
0355
Zone 137 & 138 Partition Assign.
0356
Zone 139 & 140 Partition Assign.
0357
Zone 141 & 142 Partition Assign.
0358
Zone 143 & 144 Partition Assign.
0359
Zone 145 & 146 Partition Assign.
0360
Zone 147 & 148 Partition Assign.
0361
Zone 149 & 150 Partition Assign.
0362
Zone 151 & 152 Partition Assign.
0363
Zone 153 & 154 Partition Assign.
0364
Zone 155 & 156 Partition Assign.
0365
Zone 157 & 158 Partition Assign.
0366
Zone 159 & 160 Partition Assign.
0367
Zone 161 & 162 Partition Assign.
0368
Zone 163 & 164 Partition Assign.
0369
Zone 165 & 166 Partition Assign.
0370
Zone 167 & 168 Partition Assign.
0371
Zone 169 & 170 Partition Assign.
0372
Zone 171 & 172 Partition Assign.
0373
Zone 173 & 174 Partition Assign.
0374
Zone 175 & 176 Partition Assign.
0375
Zone 177 & 178 Partition Assign.
0376
Zone 179 & 180 Partition Assign.
0377
Zone 181 & 182 Partition Assign.
0378
Zone 183 & 184 Partition Assign.
0379
Zone 185 & 186 Partition Assign.
0380
Zone 187 & 188 Partition Assign.
0381
Zone 189 & 190 Partition Assign.
0382
Zone 191 & 192 Partition Assign.
0383
Zone 193 & 194 Partition Assign.
0384
Zone 195 & 196 Partition Assign.
0385
Zone 197 & 198 Partition Assign.
0386
Zone 199 & 200 Partition Assign.
0387
Zone 201 & 202 Partition Assign.
0388
Zone 203 & 204 Partition Assign.
0389
Zone 205 & 206 Partition Assign.
0390
Zone 207 & 208 Partition Assign.
0391
Zone 209 & 210 Partition Assign.

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Address Description
0392
Zone 211 & 212 Partition
0393
Zone 213 & 214 Partition
0394
Zone 215 & 216 Partition
0395
Zone 217 & 218 Partition
0396
Zone 219 & 220 Partition
0397
Zone 221 & 222 Partition
0398
Zone 223 & 224 Partition
0399
Zone 225 & 226 Partition
0400
Zone 227 & 228 Partition
0401
Zone 229 & 230 Partition
0402
Zone 231 & 232 Partition
0403
Zone 233 & 234 Partition
0404
Zone 235 & 236 Partition
0405
Zone 237 & 238 Partition
0406
Zone 239 & 240 Partition
0407
Zone 241 & 242 Partition
0408
Zone 243 & 244 Partition
0409
Zone 245 & 246 Partition
0410
Zone 247 & 248 Partition
0415
Zone 1 & 2 Zone Type
0416
Zone 3 & 4 Zone Type
0417
Zone 5 & 6 Zone Type
0418
Zone 7 & 8 Zone Type
0419
Zone 9 & 10 Zone Type
0420
Zone 11 & 12 Zone Type
0421
Zone 13 & 14 Zone Type
0422
Zone 15 & 16 Zone Type
0423
Zone 17 & 18 Zone Type
0424
Zone 19 & 20 Zone Type
0425
Zone 21 & 22 Zone Type
0426
Zone 23 & 24 Zone Type
0427
Zone 25 & 26 Zone Type
0428
Zone 27 & 28 Zone Type
0429
Zone 29 & 30 Zone Type
0430
Zone 31 & 32 Zone Type
0431
Zone 33 & 34 Zone Type
0432
Zone 35 & 36 Zone Type
0433
Zone 37 & 38 Zone Type
0434
Zone 39 & 40 Zone Type
0435
Zone 41 & 42 Zone Type
0436
Zone 43 & 44 Zone Type
0437
Zone 45 & 46 Zone Type
0438
Zone 47 & 48 Zone Type
0439
Zone 49 & 50 Zone Type
0440
Zone 51 & 52 Zone Type
0441
Zone 53 & 54 Zone Type
0442
Zone 55 & 56 Zone Type
0443
Zone 57 & 58 Zone Type
0444
Zone 59 & 60 Zone Type
0445
Zone 61 & 62 Zone Type
0446
Zone 63 & 64 Zone Type
0447
Zone 65 & 66 Zone Type
0448
Zone 67 & 68 Zone Type
0449
Zone 69 & 70 Zone Type
0450
Zone 71 & 72 Zone Type
0451
Zone 73 & 74 Zone Type
0452
Zone 75 & 76 Zone Type
0453
Zone 77 & 78 Zone Type
0454
Zone 79 & 80 Zone Type
0455
Zone 81 & 82 Zone Type
0456
Zone 83 & 84 Zone Type
0457
Zone 85 & 86 Zone Type
0458
Zone 87 & 88 Zone Type
0459
Zone 89 & 90 Zone Type
0460
Zone 91 & 92 Zone Type
DS7400Xi ( 4+) Reference Guide

Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.
Assign.

Address Description
0461
Zone 93 & 94 Zone Type
0462
Zone 95 & 96 Zone Type
0463
Zone 97 & 98 Zone Type
0464
Zone 99 & 100 Zone Type
0465
Zone 101 & 102 Zone Type
0466
Zone 103 & 104 Zone Type
0467
Zone 105 & 106 Zone Type
0468
Zone 107 & 108 Zone Type
0469
Zone 109 & 110 Zone Type
0470
Zone 111 & 112 Zone Type
0471
Zone 113 & 114 Zone Type
0472
Zone 116 & 115 Zone Type
0473
Zone 117 & 118 Zone Type
0474
Zone 119 & 120 Zone Type
0475
Zone 121 & 122 Zone Type
0476
Zone 123 & 124 Zone Type
0477
Zone 125 & 126 Zone Type
0478
Zone 127 & 128 Zone Type
0479
Zone 129 & 130 Zone Type
0480
Zone 131 & 132 Zone Type
0481
Zone 133 & 134 Zone Type
0482
Zone 135 & 136 Zone Type
0483
Zone 137 & 138 Zone Type
0484
Zone 139 & 140 Zone Type
0485
Zone 141 & 142 Zone Type
0486
Zone 143 & 144 Zone Type
0487
Zone 145 & 146 Zone Type
0488
Zone 147 & 148 Zone Type
0489
Zone 149 & 150 Zone Type
0490
Zone 151 & 152 Zone Type
0491
Zone 153 & 154 Zone Type
0492
Zone 155 & 156 Zone Type
0493
Zone 157 & 158 Zone Type
0494
Zone 159 & 160 Zone Type
0495
Zone 161 & 162 Zone Type
0496
Zone 163 & 164 Zone Type
0497
Zone 165 & 166 Zone Type
0498
Zone 167 & 168 Zone Type
0499
Zone 169 & 170 Zone Type
0500
Zone 171 & 172 Zone Type
0501
Zone 173 & 174 Zone Type
0502
Zone 175 & 176 Zone Type
0503
Zone 177 & 178 Zone Type
0504
Zone 179 & 180 Zone Type
0505
Zone 181 & 182 Zone Type
0506
Zone 183 & 184 Zone Type
0507
Zone 185 & 186 Zone Type
0508
Zone 187 & 188 Zone Type
0509
Zone 189 & 190 Zone Type
0510
Zone 191 & 192 Zone Type
0511
Zone 193 & 194 Zone Type
0512
Zone 195 & 196 Zone Type
0513
Zone 197 & 198 Zone Type
0514
Zone 199 & 200 Zone Type
0515
Zone 201 & 202 Zone Type
0516
Zone 203 & 204 Zone Type
0517
Zone 205 & 206 Zone Type
0518
Zone 207 & 208 Zone Type
0519
Zone 209 & 210 Zone Type
0520
Zone 211 & 212 Zone Type
0521
Zone 213 & 214 Zone Type
0522
Zone 215 & 216 Zone Type
0523
Zone 217 & 218 Zone Type
0524
Zone 219 & 220 Zone Type
0525
Zone 221 & 222 Zone Type

Address Description
0526
Zone 223 & 224 Zone Type
0527
Zone 225 & 226 Zone Type
0528
Zone 227 & 228 Zone Type
0529
Zone 229 & 230 Zone Type
0530
Zone 231 & 232 Zone Type
0531
Zone 233 & 234 Zone Type
0532
Zone 235 & 236 Zone Type
0533
Zone 237 & 238 Zone Type
0534
Zone 239 & 240 Zone Type
0535
Zone 241 & 242 Zone Type
0536
Zone 243 & 244 Zone Type
0537
Zone 245 & 246 Zone Type
0538
Zone 247 & 248 Zone Type
0545
Alpha for Partition 1
0561
Alpha for Partition 2
0577
Alpha for Partition 3
0593
Alpha for Partition 4
0609
Alpha for Partition 5
0625
Alpha for Partition 6
0641
Alpha for Partition 7
0657
Alpha for Partition 8
0673
Alpha for Zone Number 1
0689
Alpha for Zone Number 2
0705
Alpha for Zone Number 3
0721
Alpha for Zone Number 4
0737
Alpha for Zone Number 5
0753
Alpha for Zone Number 6
0769
Alpha for Zone Number 7
0785
Alpha for Zone Number 8
0801
Alpha for Zone Number 9
0817
Alpha for Zone Number 10
0833
Alpha for Zone Number 11
0849
Alpha for Zone Number 12
0865
Alpha for Zone Number 13
0881
Alpha for Zone Number 14
0897
Alpha for Zone Number 15
0913
Alpha for Zone Number 16
0929
Alpha for Zone Number 17
0945
Alpha for Zone Number 18
0961
Alpha for Zone Number 19
0977
Alpha for Zone Number 20
0993
Alpha for Zone Number 21
1009
Alpha for Zone Number 22
1025
Alpha for Zone Number 23
1041
Alpha for Zone Number 24
1057
Alpha for Zone Number 25
1073
Alpha for Zone Number 26
1089
Alpha for Zone Number 27
1105
Alpha for Zone Number 28
1121
Alpha for Zone Number 29
1137
Alpha for Zone Number 30
1153
Alpha for Zone Number 31
1169
Alpha for Zone Number 32
1185
Alpha for Zone Number 33
1201
Alpha for Zone Number 34
1217
Alpha for Zone Number 35
1233
Alpha for Zone Number 36
1249
Alpha for Zone Number 37
1265
Alpha for Zone Number 38
1281
Alpha for Zone Number 39
1297
Alpha for Zone Number 40
1313
Alpha for Zone Number 41
1329
Alpha for Zone Number 42
1345
Alpha for Zone Number 43
1361
Alpha for Zone Number 44

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 95

Address Description
1377
Alpha for Zone
1393
Alpha for Zone
1409
Alpha for Zone
1425
Alpha for Zone
1441
Alpha for Zone
1457
Alpha for Zone
1473
Alpha for Zone
1489
Alpha for Zone
1505
Alpha for Zone
1521
Alpha for Zone
1537
Alpha for Zone
1553
Alpha for Zone
1569
Alpha for Zone
1585
Alpha for Zone
1601
Alpha for Zone
1617
Alpha for Zone
1633
Alpha for Zone
1649
Alpha for Zone
1665
Alpha for Zone
1681
Alpha for Zone
1697
Alpha for Zone
1713
Alpha for Zone
1729
Alpha for Zone
1745
Alpha for Zone
1761
Alpha for Zone
1777
Alpha for Zone
1793
Alpha for Zone
1809
Alpha for Zone
1825
Alpha for Zone
1841
Alpha for Zone
1857
Alpha for Zone
1873
Alpha for Zone
1889
Alpha for Zone
1905
Alpha for Zone
1921
Alpha for Zone
1937
Alpha for Zone
1953
Alpha for Zone
1969
Alpha for Zone
1985
Alpha for Zone
2001
Alpha for Zone
2017
Alpha for Zone
2033
Alpha for Zone
2049
Alpha for Zone
2065
Alpha for Zone
2081
Alpha for Zone
2097
Alpha for Zone
2113
Alpha for Zone
2129
Alpha for Zone
2145
Alpha for Zone
2161
Alpha for Zone
2177
Alpha for Zone
2193
Alpha for Zone
2209
Alpha for Zone
2225
Alpha for Zone
2241
Alpha for Zone
2257
Alpha for Zone
2273
Alpha for Zone
2289
Alpha for Zone
2305
Alpha for Zone
2321
Alpha for Zone
2337
Alpha for Zone
2353
Alpha for Zone
2369
Alpha for Zone
2385
Alpha for Zone
2401
Alpha for Zone
Page 96

Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number

45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109

P/N: F01U035325-01

Address Description
2417
Alpha for Zone Number 110
2433
Alpha for Zone Number 111
2449
Alpha for Zone Number 112
2465
Alpha for Zone Number 113
2481
Alpha for Zone Number 114
2497
Alpha for Zone Number 115
2513
Alpha for Zone Number 116
2529
Alpha for Zone Number 117
2545
Alpha for Zone Number 118
2561
Alpha for Zone Number 119
2577
Alpha for Zone Number 120
2593
Alpha for Zone Number 121
2609
Alpha for Zone Number 122
2625
Alpha for Zone Number 123
2641
Alpha for Zone Number 124
2657
Alpha for Zone Number 125
2673
Alpha for Zone Number 126
2689
Alpha for Zone Number 127
2705
Alpha for Zone Number 128
2721
Zone Function Bypass 1-8
2722
Zone Function Bypass 9-16
2723
Zone Function Bypass 17-24
2724
Zone Function Bypass 25-30
2725
Command 4 (Cust.) Arming 1-8
2726
Command 4 (Cust.) Arming 9-16
2727
Command 4 (Cust.) Arming 17-24
2728
Command 4 (Cust.) Arming 25-30
2729
RF Zone Group Program. 129-248
2731
Receiver Configuration
2732
Force Arming & Ground Fault
2733
Commerical Fire Mode
2734
Alarm Output
2735
Programmable Output Type 1
2736
Programmable Output Type 2
2737
Output Part. Assign. & Bell Output
2738
Output Part. Assign. & Keyfob Chirp
2740
Octal Module #1, Relay #1
2742
Octal Module #1, Relay #2
2744
Octal Module #1, Relay #3
2746
Octal Module #1, Relay #4
2748
Octal Module #1, Relay #5
2750
Octal Module #1, Relay #6
2752
Octal Module #1, Relay #7
2754
Octal Module #1, Relay #8
2756
Octal Module #2, Relay #1
2758
Octal Module #2, Relay #2
2760
Octal Module #2, Relay #3
2762
Octal Module #2, Relay #4
2764
Octal Module #2, Relay #5
2766
Octal Module #2, Relay #6
2768
Octal Module #2, Relay #7
2770
Octal Module #2, Relay #8
2772
Output Function 1
2775
Output Function 2
2778
Output Function 3
2781
Output Function 4
2784
Output Function 5
2787
Output Function 6
2790
Output Function 7
2793
Output Function 8
2796
Output Function 9
2799
Output Function 10
2802
Output Function 11
2805
Output Function 12
2808
Output Function 13

Address Description
2811
Output Function 14
2814
Output Function 15
2817
Output Function 16
2820
Output Function 17
2823
Output Function 18
2826
Output Function 19
2829
Output Function 20
2832
Output Function 21
2835
Output Function 22
2838
Output Function 23
2841
Output Function 24
2844
Octal Relay Partition Assignment
2845
Octal Relay Partition Assignment
2846
Octal Relay Partition Assignment
2847
Octal Relay Partition Assignment
2848
Octal Relay Partition Assignment
2849
Octal Relay Partition Assignment
2850
Octal Relay Partition Assignment
2851
Octal Relay Partition Assignment
2852
Output Function Partition Assign.
2853
Output Function Partition Assign.
2854
Output Function Partition Assign.
2855
Output Function Partition Assign.
2856
Output Function Partition Assign.
2857
Output Function Partition Assign.
2858
Output Function Partition Assign.
2859
Output Function Partition Assign.
2860
Output Function Partition Assign.
2861
Output Function Partition Assign.
2862
Output Function Partition Assign.
2863
Output Function Partition Assign.
3131
Keypad Assignment
3132
Keypad Assignment
3133
Keypad Assignment
3134
Keypad Assignment
3135
Keypad Assignment
3136
Keypad Assignment
3137
Keypad Assignment
3138
Keypad Assignment & Backlight
Control
3139
Keypad Partition Assignment
3140
Keypad Partition Assignment
3141
Keypad Partition Assignment
3142
Keypad Partition Assignment
3143
Keypad Partition Assignment
3144
Keypad Partition Assignment
3145
Keypad Partition Assignment
3146
Keypad Partition Assignment
3147
Function Key Programming
3148
Function Key Programming
3149
Open/Close Report Control
3151
Open/Close Rprt. & Zone Alarm
Routing
3152
System Routing
3153
Phone/DS7416i Routing
3154
Phone/DS7416i Routing
3155
Phone Number General Control
3156
Phone Number 1 Control
3157
Phone Number 2 Control
3158
Answer Ring Count (Arm/Disarm)
3159
Phone Number 1
3175
Phone Number 2
3191
Phone Number 3
3207
Keypad Fire Alarm Report
3208
Keypad Fire Restoral Report

Copyright © 2007 Bosch Security Systems, Inc.

DS7400Xi (4+) Reference Guide

Address Description
3209
Zone Function 1 Alarm Report
3210
Zone Function 2 Alarm Report
3211
Zone Function 3 Alarm Report
3212
Zone Function 4 Alarm Report
3213
Zone Function 5 Alarm Report
3214
Zone Function 6 Alarm Report
3215
Zone Function 7 Alarm Report
3216
Zone Function 8 Alarm Report
3217
Zone Function 9 Alarm Report
3218
Zone Function 10 Alarm Report
3219
Zone Function 11 Alarm Report
3220
Zone Function 12 Alarm Report
3221
Zone Function 13 Alarm Report
3222
Zone Function 14 Alarm Report
3223
Zone Function 15 Alarm Report
3224
Zone Function 16 Alarm Report
3225
Zone Function 17 Alarm Report
3226
Zone Function 18 Alarm Report
3227
Zone Function 19 Alarm Report
3228
Zone Function 20 Alarm Report
3229
Zone Function 21 Alarm Report
3230
Zone Function 22 Alarm Report
3231
Zone Function 23 Alarm Report
3232
Zone Function 24 Alarm Report
3233
Zone Function 25 Alarm Report
3234
Zone Function 26 Alarm Report
3235
Zone Function 27 Alarm Report
3236
Zone Function 28 Alarm Report
3237
Zone Function 29 Alarm Report
3238
Zone Function 30 Alarm Report
3239
Keypad Emergency Report
3240
Keypad Panic Report
3241
Zone Function 1 Restoral Report
3242
Zone Function 2 Restoral Report
3243
Zone Function 3 Restoral Report
3244
Zone Function 4 Restoral Report
3245
Zone Function 5 Restoral Report
3246
Zone Function 6 Restoral Report
3247
Zone Function 7 Restoral Report
3248
Zone Function 8 Restoral Report
3249
Zone Function 9 Restoral Report
3250
Zone Function 10 Restoral Report
3251
Zone Function 11 Restoral Report
3252
Zone Function 12 Restoral Report
3253
Zone Function 13 Restoral Report
3254
Zone Function 14 Restoral Report
3255
Zone Function 15 Restoral Report
3256
Zone Function 16 Restoral Report
3257
Zone Function 17 Restoral Report
3258
Zone Function 18 Restoral Report
3259
Zone Function 19 Restoral Report
3260
Zone Function 20 Restoral Report
3261
Zone Function 21 Restoral Report
3262
Zone Function 22 Restoral Report
3263
Zone Function 23 Restoral Report
3264
Zone Function 24 Restoral Report
3265
Zone Function 25 Restoral Report
3266
Zone Function 26 Restoral Report
3267
Zone Function 27 Restoral Report
3268
Zone Function 28 Restoral Report
3269
Zone Function 29 Restoral Report
3270
Zone Function 30 Restoral Report
3271
Zone Function 1 Trouble Report
3272
Zone Function 2 Trouble Report
3273
Zone Function 3 Trouble Report
DS7400Xi ( 4+) Reference Guide

Address Description
3274
Zone Function 4 Trouble Report
3275
Zone Function 5 Trouble Report
3276
Zone Function 6 Trouble Report
3277
Zone Function 7 Trouble Report
3278
Zone Function 8 Trouble Report
3279
Zone Function 9 Trouble Report
3280
Zone Function 10 Trouble Report
3281
Zone Function 11 Trouble Report
3282
Zone Function 12 Trouble Report
3283
Zone Function 13 Trouble Report
3284
Zone Function 14 Trouble Report
3285
Zone Function 15 Trouble Report
3286
Zone Function 16 Trouble Report
3287
Zone Function 17 Trouble Report
3288
Zone Function 18 Trouble Report
3289
Zone Function 19 Trouble Report
3290
Zone Function 20 Trouble Report
3291
Zone Function 21 Trouble Report
3292
Zone Function 22 Trouble Report
3293
Zone Function 23 Trouble Report
3294
Zone Function 24 Trouble Report
3295
Zone Function 25 Trouble Report
3296
Zone Function 26 Trouble Report
3297
Zone Function 27 Trouble Report
3298
Zone Function 28 Trouble Report
3299
Zone Function 29 Trouble Report
3300
Zone Function 30 Trouble Report
3301
Zone Function 1 Trouble Restoral
3302
Zone Function 2 Trouble Restoral
3303
Zone Function 3 Trouble Restoral
3304
Zone Function 4 Trouble Restoral
3305
Zone Function 5 Trouble Restoral
3306
Zone Function 6 Trouble Restoral
3307
Zone Function 7 Trouble Restoral
3308
Zone Function 8 Trouble Restoral
3309
Zone Function 9 Trouble Restoral
3310
Zone Function 10 Trouble Restoral
3311
Zone Function 11 Trouble Restoral
3312
Zone Function 12 Trouble Restoral
3313
Zone Function 13 Trouble Restoral
3314
Zone Function 14 Trouble Restoral
3315
Zone Function 15 Trouble Restoral
3316
Zone Function 16 Trouble Restoral
3317
Zone Function 17 Trouble Restoral
3318
Zone Function 18 Trouble Restoral
3319
Zone Function 19 Trouble Restoral
3320
Zone Function 20 Trouble Restoral
3321
Zone Function 21 Trouble Restoral
3322
Zone Function 22 Trouble Restoral
3323
Zone Function 23 Trouble Restoral
3324
Zone Function 24 Trouble Restoral
3325
Zone Function 25 Trouble Restoral
3326
Zone Function 26 Trouble Restoral
3327
Zone Function 27 Trouble Restoral
3328
Zone Function 28 Trouble Restoral
3329
Zone Function 29 Trouble Restoral
3330
Zone Function 30 Trouble Restoral
3331
Open Report
3332
Close Report
3333
Duress Report
3334
Partial Close Report
3335
First Open After Alarm Report.
3336
Low Battery Report
3337
Low Battery Restoral Report
3338
AC Fail Report

Address Description
3339
AC Restoral Report
3340
Communicator Test/System
Normal Report
3341
Remote Prog. Successful Report
3342
Remote Prog. Unsuccessful Report
3343
Local Prog. Successful Rprt.
3344
Local Prog. Unsuccessful Report
3345
System Trouble Report
3346
Sysem Trouble Restoral Report
3347
Communicator Test/System Off
Normal Report
3348
Exit Error Report
3349
Recent Closing Report
3350
System Walk Test Report
3351
System Walk Test Restoral
3352
Fire Walk Test Report
3353
Fire Walk Test Restoral
3354
Mux Low Temperature Report
3355
Mux Low Temperature Restoral
3356
Dirty Smoke Chamber Report
3357
Dirty Smoke Chamber Restoral
3358
Zone Function 1 Bypass
Zone Function 2 Bypass
3359
3360
Zone Function 3 Bypass
3361
Zone Function 4 Bypass
3362
Zone Function 5 Bypass
3363
Zone Function 6 Bypass
3364
Zone Function 7 Bypass
3365
Zone Function 8 Bypass
3366
Zone Function 9 Bypass
3367
Zone Function 10 Bypass
3368
Zone Function 11 Bypass
3369
Zone Function 12 Bypass
3370
Zone Function 13 Bypass
3371
Zone Function 14 Bypass
3372
Zone Function 15 Bypass
3373
Zone Function 16 Bypass
3374
Zone Function 17 Bypass
3375
Zone Function 18 Bypass
3376
Zone Function 19 Bypass
3377
Zone Function 20 Bypass
3378
Zone Function 21 Bypass
3379
Zone Function 22 Bypass
3380
Zone Function 23 Bypass
3381
Zone Function 24 Bypass
3382
Zone Function 25 Bypass
3383
Zone Function 26 Bypass
3384
Zone Function 27 Bypass
3385
Zone Function 28 Bypass
3386
Zone Function 29 Bypass
3387
Zone Function 30 Bypass
3388
Zone Func. 1 Bypass Restoral
3389
Zone Func. 2 Bypass Restoral
3390
Zone Func. 3 Bypass Restoral
3391
Zone Func. 4 Bypass Restoral
3392
Zone Func. 5 Bypass Restoral
3393
Zone Func. 6 Bypass Restoral
3394
Zone Func. 7 Bypass Restoral
3395
Zone Func. 8 Bypass Restoral
3396
Zone Func. 9 Bypass Restoral
3397
Zone Func. 10 Bypass Restoral
3398
Zone Func. 11 Bypass Restoral
3399
Zone Func. 12 Bypass Restoral
3400
Zone Func. 13 Bypass Restoral
3401
Zone Func. 14 Bypass Restoral

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 97

Address Description
3402
Zone Func. 15 Bypass Restoral
3403
Zone Func. 16 Bypass Restoral
3404
Zone Func. 17 Bypass Restoral
3405
Zone Func. 18 Bypass Restoral
3406
Zone Func. 19 Bypass Restoral
3407
Zone Func. 20 Bypass Restoral
3408
Zone Func. 21 Bypass Restoral
3409
Zone Func. 22 Bypass Restoral
3410
Zone Func. 23 Bypass Restoral
3411
Zone Func. 24 Bypass Restoral
3412
Zone Func. 25 Bypass Restoral
3413
Zone Func. 26 Bypass Restoral
3414
Zone Func. 27 Bypass Restoral
3415
Zone Func. 28 Bypass Restoral
3416
Zone Func. 29 Bypass Restoral
3417
Zone Func. 30 Bypass Restoral
3418
Keypad Tamper
3419
Keypad Tamper Restoral
3420
Partition Control
3421
Part. 1 & 2 General Code Control
3422
Part. 3 & 4 General Code Control
3423
Part. 5 & 6 General Code Control
3424
Part. 7 & 8 General Code Control
3425
Part. 1 & 2 Arming Warning Cntrl.
3426
Part. 3 & 4 Arming Warning Cntrl.
3427
Part. 5 & 6 Arming Warning Cntrl.
3428
Part. 7 & 8 Arming Warning Cntrl.
3429
Partition 1 Account Code 1
3431
Partition 1 Account Code 2
3433
Partition 2 Account Code 1
3435
Partition 2 Account Code 2
3437
Partition 3 Account Code 1
3439
Partition 3 Account Code 2
3441
Partition 4 Account Code 1
3443
Partition 4 Account Code 2
3445
Partition 5 Account Code 1
3447
Partition 5 Account Code 2
3449
Partition 6 Account Code 1
3451
Partition 6 Account Code 2
3453
Partition 7 Account Code 1
3455
Partition 7 Account Code 2
3457
Partition 8 Account Code 1
3459
Partition 8 Account Code 2
3477
Quick Arm Allowed
3478
PIN Length
4019
DS7412 Interface Control
4020
DS7412 Interface Configuration
4021
Dual Phone Line / Bell
Supervision Module Output
4022
Comm. Test Report Timer
4024
Remote Programmer Timer
4026
Test Report & Remote
Programmer Call-Out
4027
CR/LF Control
4028
Entry Delay Time 1
4029
Entry Delay Time 2
4030
Exit Delay Time
4032
Fire Bell Cutoff
4033
Burglary Bell Cutoff
4034
AC Fail Report Delay
4038
Pager Delay Timer
4039
RF Receiver Jam Detection Level
5001
Alpha for Zone Number 129
5017
Alpha for Zone Number 130
5033
Alpha for Zone Number 131
Page 98

P/N: F01U035325-01

Address Description
5049
Alpha for Zone
5065
Alpha for Zone
5081
Alpha for Zone
5097
Alpha for Zone
5113
Alpha for Zone
5129
Alpha for Zone
5145
Alpha for Zone
5161
Alpha for Zone
5177
Alpha for Zone
5193
Alpha for Zone
5209
Alpha for Zone
5225
Alpha for Zone
5241
Alpha for Zone
5257
Alpha for Zone
5273
Alpha for Zone
5289
Alpha for Zone
5305
Alpha for Zone
5321
Alpha for Zone
5337
Alpha for Zone
5353
Alpha for Zone
5369
Alpha for Zone
5385
Alpha for Zone
5401
Alpha for Zone
5417
Alpha for Zone
5433
Alpha for Zone
5449
Alpha for Zone
5465
Alpha for Zone
5481
Alpha for Zone
5497
Alpha for Zone
5513
Alpha for Zone
5529
Alpha for Zone
5545
Alpha for Zone
5561
Alpha for Zone
5577
Alpha for Zone
5593
Alpha for Zone
5609
Alpha for Zone
5625
Alpha for Zone
5641
Alpha for Zone
Alpha for Zone
5657
5673
Alpha for Zone
5689
Alpha for Zone
5705
Alpha for Zone
5721
Alpha for Zone
5737
Alpha for Zone
5753
Alpha for Zone
5769
Alpha for Zone
5785
Alpha for Zone
5801
Alpha for Zone
5817
Alpha for Zone
5833
Alpha for Zone
5849
Alpha for Zone
5865
Alpha for Zone
5881
Alpha for Zone
5897
Alpha for Zone
5913
Alpha for Zone
5929
Alpha for Zone
5945
Alpha for Zone
5961
Alpha for Zone
5977
Alpha for Zone
5993
Alpha for Zone
6009
Alpha for Zone
6025
Alpha for Zone
6041
Alpha for Zone
6057
Alpha for Zone
6073
Alpha for Zone

Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number

132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196

Address Description
6089
Alpha for Zone
6105
Alpha for Zone
6121
Alpha for Zone
6137
Alpha for Zone
6153
Alpha for Zone
6169
Alpha for Zone
6185
Alpha for Zone
6201
Alpha for Zone
6217
Alpha for Zone
6233
Alpha for Zone
6249
Alpha for Zone
6265
Alpha for Zone
6281
Alpha for Zone
6297
Alpha for Zone
6313
Alpha for Zone
6329
Alpha for Zone
5345
Alpha for Zone
6361
Alpha for Zone
6377
Alpha for Zone
6393
Alpha for Zone
6409
Alpha for Zone
6425
Alpha for Zone
6441
Alpha for Zone
Alpha for Zone
6457
6473
Alpha for Zone
6489
Alpha for Zone
6505
Alpha for Zone
6521
Alpha for Zone
6537
Alpha for Zone
6553
Alpha for Zone
6569
Alpha for Zone
6585
Alpha for Zone
6601
Alpha for Zone
6617
Alpha for Zone
6633
Alpha for Zone
6649
Alpha for Zone
6665
Alpha for Zone
6681
Alpha for Zone
6697
Alpha for Zone
6713
Alpha for Zone
6729
Alpha for Zone
6745
Alpha for Zone
6761
Alpha for Zone
6777
Alpha for Zone
6793
Alpha for Zone
6809
Alpha for Zone
6825
Alpha for Zone
6841
Alpha for Zone
6857
Alpha for Zone
6873
Alpha for Zone
6889
Alpha for Zone
6905
Alpha for Zone

Copyright © 2007 Bosch Security Systems, Inc.

Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number
Number

197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248

DS7400Xi (4+) Reference Guide

Index
Symbols

D

K

24-Hour Zone ............................................... 19
4/2 Format ..................................................... 79

Day Monitor ................................................... 20
Defaults, Factory .......................................... 32
Delayed Arming .............................................. 1
Dirty Chamber/Smoke ........................... 26, 93
Disarming ........................................................ 1
from Master Keypad ................................ 29
DS7420i ........................................................ 67
DS9484 ........................................................... 7
.................. See also Octal Relay Modules
Duress PIN .................................................... 28

Keypad ........................................................... 4
Keypad Alarms ............................................. 26
Keypad Assignment ............................. 22, 44
Keypad, Master ............................................ 29
Keypad Reports ........................................... 23
Keypad Sounder Output .............................. 21
Keyswitch Input ........................................... 20

A
AC Failure Report Delay ....................... 23, 50
AC Reports ........................................... 23, 24
Access Control .............................................. 1
PIN ............................................................ 28
Access Output ............................................. 21
Account Code Programming ......................... 56
Ademco AB-12 Bell ...................................... 78
Alarm
Fire - how to silence ........................... 1, 26
Invisible ............................................. 19, 35
Low Temperature ............................. 20, 21
on Open .................................................... 19
on Short .................................................... 19
Silent ......................................................... 19
Smoke ....................................................... 20
Zone ......................................................... 21
Zone Function .......................................... 23
Alpha Description ......................................... 69
Answering Machine Bypass ....................... 24
Arm Only PIN ................................................. 28
Arming
Custom .......................... 1, 19, 22, 34, 45
Delayed ...................................................... 1
Force ................................................ 22, 47
from Master Keypad ................................ 29
Maximum Security ....................... 1, 19, 34
Normal ......................................... 1, 19, 34
Perimeter ..................................... 1, 19, 34
Perimeter Instant ......................... 1, 19, 34
Automatic Arming, Extend .............................. 1

B
Battery
Backup Calculation .................................... 5
Reports ..................................................... 23
Test ...................................................... 1, 31
Battery/Sounder Test .............................. 1, 31
Bell Cutoff Delays ......................................... 50
BFSK Format ................................................. 80
Bypassing Allowed ...................................... 19

E
Emergency Key ............................. 22, 26, 45
Emergency Procedures ................................ 26
Enable Remote Programmer Callback .......... 24
Entry Pre-Alert .............................................. 21
Entry/Exit Delays ........................... 19, 20, 50
Error Display ................................................... 1
Event History .................................................. 1
Extend Automatic Arming ............................... 1

F
Factory Defaults ........................................... 32
Fire Key ........................................................ 22
Fire Reset ................................................ 1, 26
Fire Safety .................................................... 27
Fire Trouble .............................................. 1, 26
Alarm - how to silence .............................. 1
Clear Display .............................................. 1
Fire Walk Test .................................. 1, 24, 31
Fire Zone ...................................................... 20
First Open After Alarm ................................. 23
Flow Zone, Water ........................................ 20
Force Arming ................................... 1, 22, 47
Formats
4/2 ............................................................ 79
BFSK ........................................................ 80
CID ............................................................ 85
SIA ............................................................ 83

G
General PIN ................................................... 28
Ground Fault Detect ............................. 22, 47
Ground Start ................................................. 21

C

H

California March Time ................................... 22
Chime Mode .................................................... 1
CID Formats .................................................. 85
Clear Displays ................................................. 1
Closing Ring Back ................................. 19, 34
Commercial Fire Mode .......................... 22, 48
California March Time .............................. 22
Multiple Keypad Use ................................ 23
Pulsing Fire Zone ..................................... 22
Single Keypad Use .................................. 23
Temporal ................................................... 22
Water Flow Zone Delay ........................... 22
Common Area ............................................... 22
Communicator Test .......................... 1, 24, 31
Custom Arming .................. 1, 19, 22, 34, 45

HEX Values ................................................... 32
History, Read Event ................................. 1, 30

DS7400Xi ( 4+) Reference Guide

I

L
Latch on Any Zone Alarm ............................
Load Number ................................................
Local Program Reports .................................
Low Battery ..................................................
Low Temperature Alarm ...................... 20,

21
25
24
23
21

M
Master Code ......................................... 28, 59
Master Keypad
Arming from ............................................. 29
Disarming from ......................................... 29
Displays .................................................... 29
Master Keypad Programming ....................... 22
Master PIN ..................................................... 28
Maximum Security Arming ............... 1, 19, 34
Multiple Keypad Use ..................................... 23
Multiple Zone Input ........................................ 20
Multiplex
Bus Outputs ............................................. 21
Bus Wiring Requirements .......................... 4
Smoke ....................................................... 20
Zone Addressing ..................................... 86

N
Normal Arming .................................

1, 19, 34

O
Octal Relay Modules ..................................... 60
ON Outputs ................................................... 21
Open/Close Reports ...................... 23, 24, 49
Output ............................................................. 4
Access ..................................................... 21
Cross Matrix ..................................... 21, 66
Keypad Sounder ...................................... 21
Multiplex Bus ............................................ 21
Panic/Duress ............................................ 21
Partition Assignment ................................ 42
Programming .................................... 21, 41
Output Function ............................................ 21
Partition Assignment ................................ 67
Programming ............................................ 66

Input
Cross Matrix ..................................... 21, 66
Multiple Zone ............................................ 20
Single Zone .............................................. 20
Installation
Control/Communicator ................................ 8
Enclosure ................................................... 8
Fire Considerations .................................. 27
Interior Delayed ............................................ 19
Interior Entry/Exit Follower ........................... 20
Interior Home/Away ..................................... 20
Interior Instant ................................................ 20
Invisible Alarm ....................................... 19, 35

Copyright © 2007 Bosch Security Systems, Inc.

P/N: F01U035325-01

Page 99

Index - continued
P
Pager Delay ..................................................
Panic Key .............................................. 22,
Panic/Duress Output ....................................
Partition .................................................... 4,
Partition Assignment .....................................
Partition Control Programming .............. 21,
Perimeter Arming ............................. 1, 19,
Perimeter Instant .............................. 1, 19,
Phone Answering Programming .......... 24,
Phone Number
Alternate between two ...........................
Dial Pulse/Tone on All ...............................
Programming .................................... 57,
PIN .................................................................
Authority Levels .......................................
Length ......................................................
Worksheet ........................................ 13,
Program Addresses .....................................
Programmer’s Code .............................. 32,
Programming a Zone ....................................
Pulsing Fire Zone ..........................................

S
59
45
21
29
38
42
34
34
58
23
24
74
28
28
59
14
93
59
35
22

Q
Quick Arm Control ........................................ 43

R
Read Event History .................................. 1, 30
Receivers ..................................................... 58
Remote Program Dial-out & Answer .............. 1
Remote Program Reports ............................. 24
Report Programming ............................. 23, 53
Reporting Problems ...................................... 88
Reports
AC .................................................... 23, 24
Battery ...................................................... 23
Communicator Test .................................. 24
Dirty Chamber .......................................... 24
Duress ...................................................... 23
Exit Error .................................................. 24
Keypad ..................................................... 23
Local Program .......................................... 24
Mux. Smoke Low Temperature ................ 24
Open/Close ............................... 23, 24, 49
Remote Program ....................................... 24
System Trouble ........................................ 24
Walk Test .................................................. 24
Zone ................................................. 19, 23
Zone Restoral .......................................... 19
Reset
Error Display .............................................. 1
Fire ............................................................. 1
Restore ................................................. 19, 34
RS232 Interface ........................................... 52

Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY, USA 14450-9199
(800) 289-0096

SIA Formats ..................................................
Silencing Alarms ...................................... 1,
Silent Alarm ...................................................
Single Keypad Use .......................................
Single Partition Mode ....................................
Single Zone Input ..........................................
Siren on Communication Fail ................ 19,
Smoke Alarm .................................................
Solid State Output Modules ..........................
Special Emergency Key ...............................
Supervisory Zone ........................................
Swinger Shunts ................................... 19,
System
Problems ..................................................
Status (ready to arm) ..............................
Trouble Reports .......................................
Walk Test ............................................. 1,
Worksheet ........................................ 12,
System Reset ...............................................

W
83
26
19
23
29
20
34
20
21
22
20
34
89
21
24
24
18
30

T
Temperature Alarm .......................................
Temporal ........................................................
Temporary PIN ...............................................
Test
Battery ................................................. 1,
Battery/Sounder .................................. 1,
Communicator ..................................... 1,
Fire Walk ............................................. 1,
System Walk ....................................... 1,
Test Report ...................................................
Timer Programming ............................... 50,
Trouble
Fire ...................................................... 1,
On Open ...................................................
On Shor ................................................... t
Zone Function ..........................................

21
22
28
31
31
31
31
31
68
68
26
19
19
23

U
UL Listings .................................................... 75
Unlimited PIN .................................................. 28

Water Flow Zone .........................................
Water Flow Zone Delay ...............................
Wiring .................................................. 4, 9,
Worksheets
4/2 Format ................................................
Alpha Description Programming ...... 70,
BFSK Format ............................................
Pager Format ............................................
Phone Number Programming ...................
PIN .................................................... 13,
System ............................................. 12,
Zone Location and Notes ................ 15,

20
22
10
79
73
80
82
74
14
18
18

Z
Zone ................................................................ 4
24-Hour .................................................... 19
Alarm ........................................................ 21
Alarm Delayed .......................................... 21
Bypass ................................................ 1, 39
Day Monitor .............................................. 20
Entry/Exit Delay ................................ 19, 20
Fire ........................................................... 20
Interior Entry/Exit Follower ....................... 20
Interior Home/Away ................................. 20
Interior Instant .......................................... 20
Keyswitch Input ....................................... 20
Location and Notes Worksheet ....... 15, 18
Multiplex .................................................... 86
Multiplex Smoke ........................................ 20
Perimeter Instant ...................................... 19
Problems .................................................. 88
Programming ............................................ 20
Pulsing Fire ............................................... 22
Supervisory ............................................. 20
Water Flow .............................................. 20
Zone Function ............................................... 19
Programming ............................................ 35
Reports ..................................................... 23
Zone Restoral Reports ................................. 19
Zone Test ....................................................... 31

Copyright © 2007 Bosch Security Systems, Inc.
DS7400Xi (4+) Installation Instructions
P/N: F01U035325-01 7/07
Page 100



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 7.0 (Windows)
Creator Tool                    : PageMaker 7.0
Modify Date                     : 2007:07:27 08:51:30-04:00
Create Date                     : 2007:07:18 11:55:43-04:00
Metadata Date                   : 2007:07:27 08:51:30-04:00
Format                          : application/pdf
Title                           : F01U035325-01 DS7400Xi (4+) Ref. Guide.PMD
Creator                         : fbj5fp
Document ID                     : uuid:480d6d07-9cb4-4bdb-a86e-39aaba01b28c
Instance ID                     : uuid:f4ecaf95-095c-47df-be6f-6553f897395f
Page Count                      : 100
Author                          : fbj5fp
EXIF Metadata provided by EXIF.tools

Navigation menu