Bradfordwhite Canada Commercial Gas Natural Light Duty Power Vent Ttw Tw4 Prior Naeca Archived Servicemanual 75Gal 47150A Bwc_manual User Manual
Canada Residential Gas Natural Power Vent Ttw2 M2 Quebec Servicemanual 75Gal 47150 canada_residential_gas_natural_power_vent_ttw2_m2_quebec_servicemanual_75gal_47150 canada_residential_gas_natural_power_vent_ttw2_m2_quebec_servicemanual_75gal_47150 uploads wp-content bradfordwhitecorp :
Commercial Gas Natural Light Duty Power Vent Ttw Tw4 Prior Naeca Archived Servicemanual 75Gal 47150A commercial_gas_natural_light_duty_power_vent_ttw_tw4_prior_naeca_archived_servicemanual_75gal_47150a commercial_gas_natural_light_duty_power_vent_ttw_tw4_prior_naeca_archived_servicemanual_75gal_47150a uploads wp-content bradfordwhitecorp :
Canada Residential Gas Natural Power Vent Ttw2 M2 Defender And Non Defender Prior Naeca Archived Servicemanual 75Gal 47150A canada_residential_gas_natural_power_vent_ttw2_m2_defender_and_non_defender_prior_naeca_archived_servicemanual_75gal_47150a canada_residential_gas_natural_power_vent_ttw2_m2_defender_and_non_defender_prior_naeca_archived_servicemanual_75gal_47150a uploads wp-content bradfordwhitecorp :
Commercial Gas Natural Light Duty Power Vent Ttw Tw4 Prior Naeca Archived Servicemanual 75Gal 47150A.Pdf commercial_gas_natural_light_duty_power_vent_ttw_tw4_prior_naeca_archived_servicemanual_75gal_47150a commercial_gas_natural_light_duty_power_vent_ttw_tw4_prior_naeca_archived_servicemanual_75gal_47150a uploads wp-content bradfordwhitecorp :
Residential Gas Natural Power Vent Ttw2 M2 Defender And Non Defender Prior Naeca Archived Servicemanual 75Gal 47150A residential_gas_natural_power_vent_ttw2_m2_defender_and_non_defender_prior_naeca_archived_servicemanual_75gal_47150a residential_gas_natural_power_vent_ttw2_m2_defender_and_non_defender_prior_naeca_archived_servicemanual_75gal_47150a uploads wp-content bradfordwhitecorp :
2017-01-09
User Manual: Bradfordwhite Canada Commercial Gas Natural Light Duty Power Vent Ttw Tw4 Prior Naeca Archived Servicemanual 75Gal 47150A canada_commercial_gas_natural_light_duty_power_vent_ttw_tw4_prior_naeca_archived_servicemanual_75gal_47150a uploads wp-content bradfordwhitecorp :
Open the PDF directly: View PDF .
Page Count: 36
Download | |
Open PDF In Browser | View PDF |
TTW 75 SERIES ® Gas Water Heaters SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) For Bradford White TTW® Series Models: M2TW75T*(BN,CX) TW475S76(B,C)* (N,X) (*) Denotes Warranty Years Manual 47150A Save this manual for future reference Bradford White TTW Series Gas Water Heaters Table of Contents Page TTW Service Procedure Introduction 4 --- How to use this manual 5 --- Tool required for service 5 --- Specifications 6 --- Control Timings 8 --- Sequence of Operation 9 --- Troubleshooting 12 --- Burner Inspection, Cleaning and Replacement 14 I Pilot Testing, Cleaning and Replacement 16 II Pressure Switch Testing and Replacement 17 III Blower Testing and Replacement 19 IV Blower Temperature Switch Testing and Replacement 21 V Gas Control & Thermal well Testing & Replacement 23 VI Simulated Resistive Device Testing and Replacement 27 VII Safety Circuit Voltage Trace 28 VIII 115VAC Circuit Trace 29 IX Dip Tube inspection and Replacement 30 X Anode Inspection and Replacement 31 XI Flue Baffle Inspection and Replacement 32 XII Glossary of Terms 33 --- Parts List 35 --- Page 2 2 CAUTION WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death. FOR YOUR SAFETY Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. WARNING Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent-air intake system. Use proper care to avoid unnecessary contact (especially by children) with the water heater and vent-air intake components. UNDER NO CIRCUMSTANCES MUST FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM. CAUTION If sweat fittings are to be used DO NOT apply heat to the nipples on top of the water heater. Sweat the tubing to the adapter before fitting the adapter to the water connections. It is imperative that heat is not applied to the nipples containing a plastic liner. WARNING Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not smoke or have open flame near the faucet at the time it is open. Incorrect operation of this appliance may create a hazard to life and property and will nullify the warranty. DANGER Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance. IMPORTANT Before proceeding, please inspect the water heater and its components for possible damage. DO NOT install any water heater with damaged components. If damage is evident then please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts. WARNING DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING: Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas. Most people recognize this odor as a “sulfur” or “rotten egg” smell. Other conditions, such as “odorant fade” can cause the odorant to diminish in intensity, or ”fade”, and not be as readily detectable. If you have a diminished sense of smell, or are in any way unsure of the presence of gas, immediately contact your gas supplier from a neighbor's telephone. Gas detectors are available. Contact your gas supplier, or plumbing professional, for more information. WARNING FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/4” X 3/4” TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE TEMPERATURE AND PRESSURES. CAUTION Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Page 3 3 Introduction The new Bradford White TTW2 & TW4 water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark to pilot ignition system, enhanced diagnostics, simplified servicing, significantly quiet operation and additional vent lengths. Spark to Pilot Ignition System - employing the spark to pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand. Integrated Immersion Thermostat/Gas Control Valve with LED - was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue. New Powerful Blower - will eliminate problems with difficult venting situations. Quieter and Cooler Blower Operation - blower noise is significantly reduced for both interior and exterior environments. Cooler operation increases blower life by reducing bearing wear and noise. Rugged Wiring Connections - receptacle type connections promote error free wiring. Increased Vent Lengths - increased venting performance is achieved while maintaining Energy Factor & FHSR performance. The TTW2 & TW4 water heaters use a combustion system were flue gases are combined with dilution air to reduce the flue gas temperature in the blower. The diluted flue gases are evacuated to the exterior through low temperature vent materials. The gas control maintains water temperature, ignition sequence and regulates gas flow. A safety circuit consisting of a pressure switch and blower temperature switch verifies proper conditions exist for safe and reliable operation. If a situation outside of normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue. This service manual is designed to facilitate problem diagnosis and enhance service efficiency. To further promote quicker service times the new gas valve can be removed and replaced without draining the water heater. A special tool is required and will be provided with each gas valve kit shipped from our Service Parts department. Please read the service manual completely before attempting service on this new series of power vent models. Page 4 4 How to Use This Manual It is intended for this manual to be used by qualified service personal for the primary purpose of troubleshooting and repair of the Bradford White TTW Series water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater. The Honeywell WV4460E Electronic Gas Control will display error codes in the event of abnormal operation. Error codes are listed in the troubleshooting chart beginning on page 12 of this service manual. The troubleshooting chart will also indicate the probable cause for the error code and direct the service professional to a service procedure to properly diagnose the abnormal operation. In some difficult to diagnose conditions, it may be necessary to isolate the heater from the vent system to determine the problem. Contact the Bradford White technical support group immediately if diagnosis can not be made using the methods described in this service manual. Tools Required for Service Manometer: A liquid “U” tube type or a digital (magna-helic) type can be used. This device is used to measure gas and/or air pressure and vacuum. Multi-Meter: A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, Amps, micro-amps and ohms. Electronic Probes: In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm reading. It will be necessary to have special electronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets. Thermometer: Used to measure water temperature. An accurate thermometer is recommended. Water Pressure Gage: Used to measure water supply pressure. Also used to determine tank pressure by adapting to the drain valve of the heater. Gas Control Service Tool: BWC part number 239-45991-00. A specialized tool designed to remove the gas control from gas control thermal well. Available from your Bradford White parts supplier. Various Hand Tools: Pipe wrench, channel locks, open end wrenchs (3/8",7/16",½"), 12" crescent wrench, Allen wrench set, screw drivers (common & Phillips), ¼" nut driver, pliers (common & needle nose), socket set, side cutters wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, and flashlight, 5 gallon pail. Page 5 5 Specifications Power supply Dedicated 115VAC, 60 Hz, 15A Gas Supply Pipe Minimum 1/2" NPT (schedule 40 black iron pipe recommended) Approved Gas Type Natural or Propane. Unit must match gas type supplied. Gas Pressure 5.0" W.C. min. for Nat gas, 11.0" W.C. min. for L.P. gas, 14.0" W.C. maximum (Nat. & L.P.) Venting System Power vent through the wall or vertical through the roof Approved Vent Materials PVC, CPVC or ABS Minimum Clearance for Servicing 18" from top, 24" from front, 4" sides and rear. Water Supply Pressure 150 PSI maximum allowable working pressure. Check local codes for supply pressure Thermal well TCO Limit Residential 188°F (87°C), Commercial 199°F (93°C) Residential Temperature 60°F (16°C) to 160°F (71°C) (Approximate temperatures) Set Point Range Commercial Temperature 80°F (27°C) to 180°F (82°C) (Approximate temperatures) Set Point Range Blower Temperature Switch Normally closed, opens @ 165°F (74°C), auto reset @ 130°F (54°C). Pressure switch M2TW75 and TW475S Models: Normally open, closes on vacuum increase @ -1.28, opens on vacuum decrease @ -1.25 Blower M2TW75 and TW475S Models: 115VAC, 60Hz, 3.1 amps, 3000 RPM, 68CFM@0.4" W.C. Page 6 6 Specifications Vent Tables Venting Specifications: 3" Diameter (7.6 cm) PVC Vent Connector Lengths Terminating # of Elbows Maximum Length ft (m) Minimum Length ft (m) Through the Wall 1 45 (13.7) 2 (.6) Through the Wall 2 40 (12.2) 2 (.6) Through the Wall Through the Wall 3 4 35 (10.7) 30 (9.1) 2 (.6) 2 (.6) Through the Roof Through the Roof Through the Roof 0 1 2 50 (15.2) 45 (13.7) 40 (12.2) 7 (2.1) 7 (2.1) 7 (2.1) Through the Roof 3 35 (10.7) 7 (2.1) 4" Diameter (10.2 cm) PVC Vent Connector Lengths Terminating # of Elbows Maximum Length ft (m) Minimum Length ft (m) Through the Wall Through the Wall 1 2 175 (53.3) 170 (51.8) 10 (3.1) 10 (3.1) Through the Wall Through the Wall Through the Wall 3 4 5 165 (50.3) 160 (48.8) 155 (47.2) 10 (3.1) 10 (3.1) 10 (3.1) Through the Roof Through the Roof Through the Roof Through the Roof Through the Roof 0 1 2 3 4 180 (54.9) 175 (53.3) 170 (51.8) 165 (50.3) 160 (48.8) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) 15 (4.6) Page 7 7 Specifications Control Timings Ignition State Timing Pre-purge 2 Seconds Trial for Ignition 90 Seconds Flame Stabilization Period 3 Seconds Inter-purge 15 Seconds Flame Failure Response Time 1.5 Seconds (2 second. Maximum; 1 second minimum.) Post-purge 15 Seconds PS Fault Delay (failed open/close) Retry after 2 Minutes Soft Lockout Retry after 5 Minutes TCO Limit Lockout Indefinite (cycle power to restart) Verify Resistive Delay Retry after 2 Minutes (repeats 5 times) Simulated Resistive Load Lockout Indefinite (cycle power to restart) Hardware Error Lockout Indefinite (self clears if fault clears for at least 15 seconds) Wiring Diagram Blower Temperature Switch Blower Housing Blower Motor Pressure Switch Pilot A B C Simulated Resistive Device Thermal Well Page 8 8 Sequence of Operation Power up Sequence 1 Start Up. Upon power up, the control runs a safe-start check with a typical start-up delay of 1-5 seconds. 2 Simulated Resistive Load Device Check. To assure no outputs are energized if the “Simulated Resistive device” is out of range, the control will test the the device for proper operating range. If the device is within range the control resumes normal operation with no perceptible delay. If the device is out of range, the control LED immediately flashes 7 times with 3 second pause. Normal Heating Sequence 1 Thermostat calls for heat. Prior to energizing blower, gas control checks safety circuit to insure the circuit is open. Normal switch positions in the safety circuit are as follows: a) Pressure switch normally open. b) Blower temperature switch normally closed. If the safety circuit is closed, the control waits 4 seconds, gas control LED flashes 2 times with 3 second pause. Gas control waits 2 minutes then, blower runs for 30 seconds. This cycle repeats until safety circuit opens. 2 Blower energizes. 3 Blower pre-purge period (2 seconds) 4 Pressure switch proves blower/vent system operation. If the pressure switch does not close within 30 seconds, the control LED Flashes 3 times with 3 second pause. The blower runs for 30 seconds every 2 minutes trying to get the pressure switch or blower temperature switch to close. This cycle repeats as long as there is a call for heat. 5 Trial for pilot ignition (90 seconds). a) The gas control lights the pilot by activating spark igniter and gas flow to pilot burner. b) If flame is not sensed within 90 seconds, igniter and gas flow are deactivated, blower will post purge and control LED flashes 6 times with 3 second pause. 6 Main burner Ignition After pilot flame is sensed, gas control activates main valve for main burner ignition. The gas control will ignore flame and pressure switch signals for 3 seconds allowing for main burner to stabilize. Page 9 9 Sequence of Operation Normal Heating Sequence (cont.) 7 Steady state operation. During Steady State Operation the Control Monitors: Thermostat temperature sensor- When set point temperature is satisfied, gas valve is shut down and blower will post purge for 15 seconds. Control LED flashes a short flash once every 4 seconds (idle) status code. Pressure switch / Blower temperature switch- If either switch opens, pilot valve and main valve is shut down. The blower continues to runs for 30 seconds attempting to close the circuit. The control LED Flashes 3 times with 3 second pause. Flame Sensor- If flame is lost, pilot & main valve are shut down, blower runs for 15 seconds. Control attempts to re-light pilot 4 times. If unsuccessful, Blower is shut down and control proceeds to 5 minute lockout. Control re-attempts to light pilot starting at normal heating sequence #2. 8 Thermostat satisfies. 9 Burner off. 10 Blower post purge (15 seconds). Abnormal Operation 1. Simulated Resistive Device Fault: a) If the resistance is greater than 70,000 Ohms - the gas control immediately turns off all outputs. Control waits and monitors resistance for 30 seconds. If the resistance is greater than 70,000 ohms after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 8 times then once with a three second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to flashing 7 times with a 3 second pause. b) If the resistance is below 3000 ohms - The gas control immediately turns off all outputs and proceeds to flash 8 times then once with three second pause. The error self clears if the resistance returns to normal range for at least 15 seconds. 2. Temperature Sensor Fault: a) Temperature sensor detected open circuit - The gas control Immediately turns off all outputs and proceeds to flash 8 times then twice with three second pause. The error self clears if the fault clears for at least 15 seconds. b) Temperature sensors not reading the same temperature within ±5.5 °F - The gas control Immediately turns off all outputs and proceeds to flash 8 times then three times with three second pause. The error self clears if the fault clears for at least 15 seconds. c) Water temperature in excess of TCO (Temperature Cut Off) limit - The gas control immediately turns off pilot & main valve and proceeds to flash 4 times with 3 second pause. Blower continues to run until gas control is reset. Power needs to be cycled to remove gas control from TCO lockout. Page 10 10 Sequence of Operation Abnormal Operation (cont.) 3. Pressure Switch/Blower Temperature Fault: a) Pressure switch closed at start of call for heat - The gas control waits four seconds then, proceeds to flash 2 times with 3 second pause. The control waits 2 minutes and then turns on blower for 30 seconds. The blower turns off after 30 seconds and the control waits for pressure switch to open. Any time the Pressure switch opens, the blower turns on (or stays on) and the control proceeds to waiting for pressure switch to close. b) Pressure switch or blower temperature switch failed open - The gas control runs the blower for 30 seconds waiting for the pressure switch and/or blower temperature switch to close. If either switch does not close in 30 seconds, the blower turns off and the control flashes 3 times with 3 second pause. The gas control waits two minutes before turning on the blower for another 30 seconds to see the circuit close. This cycle repeats as long as there is a call for heat or until the circuit closes. c) Pressure switch or blower temperature switch opens during burner operation - The gas control turns off the pilot and main valve, runs blower for 15 seconds (inter-purge) waiting for pressure switch and/or blower temperature switch to close. If either switch fails to close, the control proceeds as described in 3b above. If the circuit closes again by the end of the inter-purge, the recycle counter is incremented, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then 2 times with 3 second pause. The gas control waits 5 minutes before repeating ignition sequence. 4. Trial For Ignition Fault: a) Pressure switch opens during trial - The gas control turns off igniter and pilot valve. The gas control proceeds as described in 3b above. If the pressure switch closes within 30 seconds the gas control will continue with trial for ignition starting at blower pre-purge. b) Flame Not Sensed - The gas control energizes the spark igniter attempting to light the pilot and prove flame. If flame is not sensed within 90 seconds, the igniter turns off, the pilot valve is closed and the gas control runs the blower through post purge and flashes 6 times then once with 3 second pause. The control waits 5 minutes before repeating the ignition sequence. 5. Flame Sensing Fault: b) Flame lost during run - The gas control turns off pilot and main valves, runs blower for 15 seconds (inter purge). The gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control turns off the blower and flashes 6 times then 3 times with 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence. c) Flame sensed out of sequence - the gas control only looks for pilot flame when the blower is running. If flame is present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost, once the flame signal is lost, the control flashes 6 times then 4 times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence. Page 11 11 Troubleshooting Green LED Indicator Observe green LED indicator on Electronic gas control. Error flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below. LED Status Control Status Probable Cause Service Procedure None, control LED not on or flashing No electrical power Control power switch in “OFF” position. Supply voltage interrupted. Short flash, once every four seconds Stand-by mode, Waiting for call for heat (no fault). Temperature demand is satisfied “Heartbeat”, alternates bright/dim Thermostat calling Tank temperature below set point of thermostat. for heat (no fault). Short flash once per second Weak pilot signal on last call for heat. 1. Unstable pilot. 2. Pilot tube block or restricted. 3. Oxidation build up on pilot electrode. 4. Wire damage to pilot assembly or bad connection at gas valve. Two flash, three second pause Pressure switch not workingclosed position. 1. Pressure switch tubing kinked or blocked. 2. Blocked pressure tap on switch or blower. 3. Faulty pressure switch. 1. Vent blockage or improper vent configuration. 2. Pressure switch tubing kinked or blocked. 3. Faulty pressure switch. 4. Blower not spinning up to speed. 5. Blower temp or exhaust temp too high 6. Faulty blower temperature switch. 1. Check vent or vent tables. Three flash, three second pause Pressure switch or blower temp. switch not working -open position. Four flash, three second pause Excessive tank temperature. System must be reset. 1. Thermal well sensor out of calibration. 2. Faulty gas control. 3. Pluming leak 1. Page 23 Five flash, three second pause Undesired-false pilot flame present. 1. Pilot valve stuck in open position. Replace gas control, page 23 Turn power on Normal operation. Adjust thermostat to temp level Normal operation. Adjust thermostat to temp level 1. Page 14 2-4. Page 16 Page 17 2 & 3 Page 18 4. Page 19 5 & 6 Page 21 2. Replace gas control, page 23 Page 12 12 Troubleshooting LED Status Control Status Six-one flash, three second pause Failed to light pilot. System auto resets. 1. Unstable pilot. 2. Pilot tube blocked or restricted. 3. Oxidation build up on pilot electrode. 4. Wire damage to pilot assembly or bad connection at gas valve. Six-two flash, three second pause Pressure switch or blower temp switch opened during burner operation. System auto resets. 1. Vent blockage or improper vent configuration. 2. Pressure switch tubing kinked or blocked. 3. Faulty pressure switch. 4. Vent termination being affected by wind 5. Blower not spinning up to speed. 6. Blower temp or exhaust temp too high 7. Faulty blower temperature switch. Six-three flash, three second pause Pilot flame extinguished. System auto resets. 1. Unstable pilot. 2. Pilot tube blocked or restricted. 3. Oxidation build up on pilot electrode. 4. Wire damage to pilot assembly or bad connection at gas valve. 5. Insufficient combustion air. 6. Gas pressure is out of specification. Six-four flash, three second pause Undesired-false pilot flame sensed. System auto resets. Pilot valve stuck in open position. Replace gas control, page 25 Seven flash, three second pause Simulated Resistive Device Harness out of specification. Simulated resistive device out of specification. Page 27 Eight-one flash, three second pause Simulated Resistive Device Harness specification check. Simulated resistive device out of specification. Page 27 Thermal well sensor damaged or unplugged 1. Damage to thermal well wire. 2. Thermal well sensor resistance out of range. Page 23 Gas valve electronics fault detected 1. Control needs to be reset. 2. Control is wet or physically damaged. 1. Interrupt power supply 2. Replace gas control, page 25 Gas valve fault detected. 1. Control needs to be reset. 2. Control is wet or physically damaged. 1. Interrupt power supply 2. Replace gas control, page 25 Eight-three flash, three second pause Eight-four flash, three second pause Probable Cause Service Procedure 1. Page 14 2-4. Page 16 1. Check vent or vent tables. 2 & 3 Page 17 4. Refer to venting section of installation manual 5. Page 19 6 & 7 Page 21 1. Page 14 2-4. Page 16 5. Refer to installation manual Page 13 13 TTW SERVICE PROCEDURE I Burner Operation Inspection, Adjustment, Cleaning and Replacement Burner Inspection and Air Shutter Adjustment. At periodic intervals (every 6 months) a visual inspection should be made of the pilot and main burner for proper operation and to assure no debris is accumulating. Pilot flame should be stable, some causes for an unstable pilot flame are: a) Water heater vent is less than the allowable vent length. b) Gas pressure is out of specification. c) Pilot flame not fully engulfing spark/flame sensor. Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips. Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter. Cast iron burner can have the gas and air mixture properly proportioned by adjusting the air shutter on the mixer face of the main burner (see cast iron burner adjustment below). Main burner must be free from any debris accumulation that may effect burner operation (see burner cleaning procedure on page 15). Cast Iron Burner Air Shutter Adjustment WARNING Inner door and burner components may be HOT when performing this operation. Take necessary precaution to prevent personal injury. Step 1. With main burner in operation, remove outer jacket door and slide inner door from left to right to open. Step 2. To adjust for proper burning, loosen the air shutter nut, rotate the air shutter to close the opening in the burner, then slowly rotate the air shutter open until flame becomes as blue as possible with a minimum of yellow tips. Tighten the air shutter nut. Too much air will cause the flame to lift off the burner ports and create noisy burner operation. Too little air will result in soot formation. Step 3. Close inner door and observe burner operation. Burner should operate as adjusted in step 2. If not, repeat air shutter adjustment compensating for proper burner operation with inner door closed. Air Shutter Nut Air Shutter Page 14 14 TTW SERVICE PROCEDURE I Burner Operation Inspection, Adjustment, Cleaning and Replacement Burner Cleaning Step 1. Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Step 2. Turn off gas supply to water heater. Step 3. Remove outer jacket door and remove inner door. Step 4. Disconnect pilot tube (7/16 wrench) and feedline (¾ wrench) from gas control. Step 5. Disconnect igniter/flame sensor wire from gas control. Step 6. Remove burner assembly from combustion chamber. Step 7. Thoroughly inspect burner surface area and burner port area and remove any loose debris. Step 8. For cast iron burners, inspect for any debris build up inside burner casting. Remove Outer door. Remove inner door Igniter/flame sense wire Feedline nut Pilot tubing nut Burner surface area Burner port area Step 9. Unscrew burner from main burner orifice. On cast iron burners, loosen air shutter nut and unscrew feedline from burner. Step 10. Remove main burner orifice from feedline (½" wrench on steel burners, 3/8" wrench on cast iron) inspect orifice, clean or replace if necessary. Reassemble burner and reinstall into water heater. Restore gas supply and check for gas leaks. Step 11. Step 12 Main burner orifice L.P. Main burner orifice. Left hand thread To resume operation follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operating manual. Page 15 15 TTW SERVICE PROCEDURE II Pilot testing, Cleaning and Replacement Pilot Inspection, Testing and Replacement Step 1. Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Remove Outer door. Step 2. Turn off gas supply to water heater. Step 3. Remove outer jacket door and remove inner door. Remove inner door Igniter/flame sense wire Step 4. Disconnect pilot tube nut (7/16 wrench) and feedline nut (¾ wrench) from gas control. Step 5. Disconnect igniter/flame sense wire from gas control. Step 6. Remove burner assembly from combustion chamber. Step 7. Remove pilot assembly from feedline (¼" nut driver). Step 8. Visually inspect igniter/flame sense wire for damage. Replace pilot if damage is found. Step 9. With a multi-meter set to the ohms setting, check continuity through igniter/flame sense wire. Replace pilot if no continuity. Step 10. Visually inspect igniter/flame sense electrode for deterioration. Replace pilot as necessary. Electrode should not be in contact with pilot hood, If so, carefully adjust electrode to a gap distance of 3/32" (.09) from pilot hood. Feedline nut Pilot tubing nut Ferrule nut Pilot tubing Igniter/flame sense wire Pilot orifice Pilot hood Igniter/flame sense electrode Step 11. Visually inspect igniter/flame sense electrode for oxidation build up. Carefully clean any oxidation using very fine emery cloth. Step 12. Visually inspect pilot tubing for kinks or cracks. If damage is found replace pilot. Step 13. Inspect pilot tubing and pilot orifice for blockage: a) Remove ferrule nut from bottom of pilot assembly (7/16" wrench). b) Remove pilot tube and pilot orifice. c) Inspect pilot tubing and pilot orifice for blockage. Clean or replace as necessary. Step 14. Reassemble pilot and install to feedline. Reinstall burner assembly to water heater. Restore gas supply and check for gas leaks. Step 15 To resume operation follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operating manual. Page 16 16 TTW SERVICE PROCEDURE III Pressure Switch Testing and Replacement Pressure Switch Testing WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury. Step 1. Position power switch on gas control to the “OFF” position. Step 2. Remove the three screws (Phillips screw driver) from control access cover on blower assembly and remove cover (see photo 1). Step 3. Carefully remove pressure switch from blower housing (see photo 2) 1 2 With steps 1,2 & 3 complete, disconnect wire leads from pressure switch. Pressure Switch Pressure switch wire leads Use a multi-meter set to the ohms setting. With blower off, check across pressure switch terminals. Are switch contacts open? (no electrical continuity) Slide pressure switch in direction of arrow while tilting slightly away from blower housing. Check tubing and pressure tap on switch for blockage. Is there blockage? N N Replace switch (see page 18) Y Y Clear blockage Position gas valve power switch to the “ON” position and adjust thermostat to call for heat, this will start the blower. Check with multi-meter, do pressure switch contacts close with blower running? Y Switch contacts are OK. See safety circuit trace (page 28) Y N Check tubing and pressure tap on N switch for blockage. Is there blockage? Y Is vent system blocked N Is vent system length within vent table Y specifications listed on page 7 N Reconfigure vent system to be compliant with vent tables. Y See blower testing (page 19) Is blower OK? N Correct blower problem. Page 17 17 TTW SERVICE PROCEDURE III Pressure Switch Testing and Replacement Pressure Switch Replacement WARNING 120 volt potential exposure. Use caution to avoid personal injury. Step 1. Position gas control power switch to “OFF” position. Step 2. Remove the three screws (Phillips screw driver) from control access cover on blower assembly and remove cover (see photo 3). Pressure Switch 3 Step 3. 4 Carefully remove pressure switch from blower housing (see photo 4) Slide pressure switch in direction of arrow while tilting slightly away from blower housing. 5 Step 4. Disconnect tubing from pressure switch. (see photo 5) Step 5. Disconnect yellow wires from pressure switch (see photo 6) Step 6. Reconnect wires from step 5 to new pressure switch. Step 7. Reconnect tubing to new pressure switch. Step 8. Carefully position pressure switch into blower housing. Step 9. Position gas control power switch to “ON” position and verify proper heater operation. Step 10. Replace control access cover from step 2. 6 Page 18 18 TTW SERVICE PROCEDURE IV Blower Testing and Replacement WARNING 115 volt potential exposure. Use caution when making voltage checks to avoid personal injury. Blower Testing Step 1. Position gas control power switch to “ON” position and adjust control to call for heat. Step 2. Remove the three screws (Phillips Screw driver) from control access cover on blower assembly and remove cover (see photo 7). Does blower energize Within 2 minutes? Y Connect manometer to pressure tap of blower. (see photo 8) Disconnect pressure switch tubing from blower. (see photo 8) N Pressure tap 8 7 Disconnect vent system from top of blower and remove vent adapter. (see photo 10) With blower running, and exhaust adapter removed from top of blower, is there a negative pressure of -2.15" to -2.30" W.C.? N N Determine voltage problem and correct. Y 10 9 Pressure switch tubing Does blower energize after 2 minutes, run for 30 seconds and shut down? Remove exhaust adapter See pressure switch testing Page 17 Is there 115vac across blue and green wires (see photo 13) 11 Y Y Blower OK Replace blower 12 N Disconnect cord set shown in photo 9. Is there 115VAC across terminals shown in photo 11 Y Incorrect supply voltage polarity N Determine power source problem and correct. Y Check power cord for damage. N Replace blower Y N N Is there 115 VAC at wall outlet? Is there 115VAC across terminals shown in photo 12 ? Y Repair or replace power cord Replace cord set Reconnect cord set shown in photo 9, is there 115VAC between blue wire and green ground wire (see photo 13) N Does cord set N have electrical continuity? Y Replace blower Green ground wire Y 13 Blue wire Replace gas control Shown with pressure switch removed. Page 19 19 TTW SERVICE PROCEDURE IV Blower Testing and Replacement Blower removal Step 1. Position gas control power switch to the “OFF” position. Step 2. Unplug blower power cord from wall outlet. Remove exhaust adapter and retain for use on new blower. Step 3. Disconnect vent system from exhaust adapter on top of blower. Step 4. Remove exhaust adapter from blower (blade screw driver) and retain for use on new blower Step 5. Unplug cord sets from blower. Step 6. Remove the three blower mounting screws (¼" nut driver). Step 7. Remove blower with gasket from water heater. Blower Mounting Screws Blower Cord Sets Blower Installation Step 8. Clean any debris from jacket head of water heater. Step 9. Set new blower with gasket in place using locating pins on blower flange to line up with location holes in jacket head. Be sure not to damage gasket. Step 10 Secure blower in place using mounting screws from step 6. Step 11. Re-install exhaust adapter from step 4. Step 12. Reconnect vent system to exhaust adapter. Step 13. Reconnect cord sets from step 5. Step 14. Plug blower power cord into wall outlet. Step 15. Position gas control power switch to the “ON” position. Step 16. Verify proper blower operation. Locating Pins on blower flange Pin location holes in jacket head Page 20 20 TTW SERVICE PROCEDURE V Blower Temperature Switch Testing and Replacement Blower Temperature Switch Testing. Step 1. WARNING 120 volt potential exposure. Use caution to avoid personal injury. Position power switch on gas control to the “OFF” position. 14 Step 2. Remove the three screws (Phillips screw driver) from control access cover on blower and remove cover (see photo 14). Step 3. Locate blower temperature switch (see photo 15) 15 Switch Setting Opens on rise @ approximately 165°F Auto resets on fall @ approximately 130°F Blower temperature switch location Cool switch to below 130°F Air mixing inlet Disconnect wire leads to switch. Using a multi-meter set to the ohms setting, is there continuity between the switch terminals? N Replace switch (see page 22) Y Reconnect wire leads and observe heater operation. Do exhaust gas temperatures rise to or above 165°F? N Y Do switch contacts open? N Do switch contacts open? Y Y Exhaust temperature is too hot. Common causes for high exhaust temperature 1. Vent length is below minimum allowable. 2. Vent diameter not to specification. 3. Restricted dilution air inlet. 4. Missing or deteriorated flue baffle. 5. Gas pressure is out of specification. Replace switch (see page 22) N Switch OK Page 21 21 TTW SERVICE PROCEDURE V Blower Temperature Switch Testing and Replacement Blower Temperature Switch Replacement. WARNING 120 volt potential exposure. Use caution to avoid personal injury. Step 1. Position gas control power switch to the “OFF” position and unplug heater from wall outlet. Step 2. Remove the three screws (Phillips screw driver) from the control access cover on blower and remove cover. (see photo 16) Step 3. 16 Locate blower temperature switch (see photo 17) 17 Step 4. Disconnect red and yellow wire leads from switch. Step 5. With an appropriate tool such as side cutters, snip the retaining lug from the blower housing to allow removal of temperature switch (see photo 18). Step 6. Remove switch from blower housing. Step 7. Install new switch. Be sure switch is properly seated in mounting area. Step 8. Reconnect red and yellows wires to new switch. Wires are interchangeable with either terminal. Step 9. Position gas control power switch to the “ON” position and verify proper heater operation. Step 10. Replace control access cover from step 2. 18 Blower temperature switch location Snip retaining lug from blower housing Page 22 22 TTW SERVICE PROCEDURE VI Gas Control/Thermal Well Testing and Replacement Gas Control Testing See pages 24 & 25 for gas control input & output testing. Thermal Well Testing Position gas valve power switch to the “OFF” position and disconnect thermal well harness from gas control. Disconnect thermal well wire harness Using a multi-meter set to the Ohms setting, determine the resistance of thermal well sensors 1 & 2 (see photos 19 & 20) 19 20 Using a multi-meter set to the ohms setting, insert one meter probe into center wire position of thermal well connector, insert the second probe into either of the outside wire positions (see photo 19). Alternate the probe on the outside position to the opposite outside wire position (see photo 20). Once the thermal well resistance values are known, the water temperature must also be known to determine if the resistance values are correct. See page 24 to obtain water temperature. N Replace thermal well (see page 25) Are thermal well resistance values correct? Y Thermal well OK Page 23 23 TTW SERVICE PROCEDURE VI Gas Control/Thermal Well Testing and Replacement WARNING Stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury. Determine Water Temperature Inside Tank Note: It is important to understand once the resistance for the thermal well is determined from page 23, water flow through the heater should not occur. Prior to performing the steps below, turn off the cold water supply to the water heater. This will prevent cold water flow into the tank affecting the resistance value of thermal well. Step 1. Position gas control power switch to “OFF” position. Step 2. Draw approximately 4 gallons of water from drain valve into a container and discard. Draw an additional gallon and immediately measure water temperature using an accurate thermometer. It may be necessary to open a hot water faucet to allow heater to drain. Step 3. Using the chart below, determine correct resistance value for the water temperature from step 2. Example: If temperature of water is 84°F, then the resistance through the sensor would be 8449 (see shaded area). NOTE: Sensor resistance increases as the temperature falls. Sensor Resistance at Various Temperatures °F 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 0 26109 19906 15314 11884 9299 7333 5827 4663 3758 3048 2488 2043 1688 1402 1170 982 828 1 25400 19383 14925 11592 9078 7165 5697 4562 3679 2986 2439 2004 1656 1376 1150 965 814 2 24712 18876 14548 11308 8862 7000 5570 4464 3602 2925 2391 1966 1625 1351 1129 949 801 3 24045 18383 14180 11032 8653 6839 5446 4368 3527 2866 2344 1928 1595 1327 1110 933 788 In Degrees 4 23399 17905 13823 10763 8449 6683 5326 4274 3453 2808 2298 1891 1566 1303 1090 917 775 F 5 22771 17440 13477 10502 8250 6531 5208 4183 3382 2752 2253 1856 1537 1280 1071 901 762 6 22163 16990 13140 10248 8057 6383 5094 4094 3312 2697 2209 1820 1509 1257 1953 886 749 7 21573 16553 12812 1000 7869 6238 4982 4006 3244 2643 2166 1786 1481 1235 1035 871 737 8 21000 16128 12494 9760 7685 6098 4873 3922 3177 2590 2124 1753 1454 1213 1017 857 725 9 20445 15715 12185 9526 7507 5961 4767 3839 3112 2538 2083 1720 1427 1191 999 842 713 Page 24 24 TTW SERVICE PROCEDURE VI Gas Control & Thermal Well Testing and Replacement Gas Control & Thermal Well Removal From Water Heater Gas Control Step 1. Position gas valve power switch to the “OFF” position and Unplug Heater from power supply. Step 2. Drain heater to a point below the gas control level. Step 3. Turn off gas supply to water heater and disconnect gas piping from gas control. Step 4. Disconnect wire harnesses and burner assembly from gas control. Step 5. Remove gas control & thermal well by rotating flats of Thermal Well counter clockwise (1-5/16"wrench). Thermal Well Gas Control Removal From Thermal Well Follow the steps below allows removal gas control from thermal well without removing thermal well from tank. Step 1. Position gas control power switch to the “OFF” position and unplug water heater from power supply. Step 2. Turn off gas supply to water heater and disconnect gas piping from gas control. Step 3. Disconnect wire harnesses & burner assembly from gas control. Step 4. Using gas control service tool (239-45991-00) available from your BWC parts supplier, Insert tool into back of gas control (see photos below) View from back of control for clarity Insert tool from back of control Step 5. Service tool shown inserted in to back of control Pivot tool towards heater as far as possible (see photo below). Lift straight up on gas control. The control should move about 1/8". Hold control in position and remove tool. Lift straight up on control to remove completely from Thermal Well. With service tool inserted, pivot tool back towards heater as far as possible. Lift straight up on control, control will move 1/8". Remove tool and continue to lift straight up on control to remove from Thermal Well. Page 25 25 TTW SERVICE PROCEDURE VI Gas Control & Thermal Well Testing and Replacement Gas Control Assembly to Thermal Well Step 1. Install threaded end of thermal well into tank. Be sure thermal well flange is positioned as shown in photo 24 for proper control alignment. Step 2. Route wire leads back into relief opening. (see photo 24) Step 3. Align slots located on thermal well flange with tabs located on back of gas control (see photos 24 & 25) 24 Route wires through relief opening Thermal well flange slots Step 4. Carefully push control back onto thermal well flange as far as possibletowards water heater. Slide control down to lock into position. Step 5. Install burner and connect pilot and feedline to gas control. 25 Gas control Tabs Igniter/sensor connection Step 6. Reconnect wire harnesses to gas control per the illustration. Step 7. Reconnect gas piping to gas control. Restore gas supply and check for gas leaks. Step 8. To resume operation, follow the instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual. Ground Wire connection 5 pin blower harness connection 3 pin thermal well connection Simulated Resistive device Page 26 26 TTW SERVICE PROCEDURE VII Simulated Resistive Device Testing Simulated Resistive Device Testing Step 1. Position power switch on gas control to the “OFF” position. Step 2. Disconnect simulated resistive device from gas control. Step 3. Using a multi-meter set to the ohms setting check resistance of simulated resistive device. Resistance must be within 25,000 ohms and 45,000 ohms. If outside of this range replace simulated resistive device. Simulated Resistive device Multi-meter set to ohms setting Electronic “pin type” Meter Probes Simulated Resistive device Page 27 27 TTW SERVICE PROCEDURE VIII Safety Circuit Voltage Trace Safety Circuit Voltage Trace WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury. NOTE: This procedure assumes a cool tank. 26 Step 2. Remove three screws (Phillips Screw driver) from control access cover on blower and remove cover (see photo 26). Position gas control switch to the “ON” position and adjust thermostat dial to call for heat, Is there 10 to 13 VAC between red wire leading to blower temperature N switch and green ground wire? Blower must be running during this voltage check. (see photo 27) Y Is LED on gas valve flashing Y the “heartbeat” code (alternating bright/dim) N Verify 120VAC to gas control (see page 29) Is there 10 to 13 VAC between yellow wire leading from pressure switch and green ground wire? (see photo 27) Is there continuity through blower temperature switch? (see page 21) N Check for loose or broken wire connection at switch terminals Determine cause of blower temperature switch activation and correct. Correct igniter/ sensor problem. N Check igniter/sensor (see page 16) is igniter/sensor OK? Y Safety circuit voltage is OK. Y N Y Do you hear or can you see the igniter sparking? No voltage from gas control, call for technical support. Y Faulty cord set or gas control. Green ground wire 27 Red wire leading to blower temp. switch If burner does not light, observe LED flash code on gas valve and refer to troubleshooting section on page 12 Yellow wire leading from pressure switch Page 28 28 TTW SERVICE PROCEDURE IX 120 VAC Trace WARNING 120 volt potential exposure. Use caution making voltage checks to avoid personal injury. 120 VAC Circuit Trace Step 1. Verify 120VAC and proper polarity at wall outlet. Step 2. With unit plugged in and control power switch in the “ON” position verify LED status. LED status None, Control LED not on or flashing. LED status Short flash, once every four seconds. LED status “Heartbeat”, alternates bright/dim. LED status Various flashing error codes. Waiting for call for heat. Thermostat calling for heat Verify error code as listed on page 12 29 28 30 Disconnect cord set as shown in photo 28 Using a volt meter set to volts AC, is there 120VAC across terminals shown in photo 29 ? Check for damage to Y AC supply power cord. N N Y Is there 120VAC across terminals shown in photo 30 ? Repair damage Replace Blower Y Reconnect cord set shown in photo 28. 31 N Disconnect wire harness from gas control (see photo 31). Incorrect supply voltage polarity Wire harness Locate black & white wires at connector, It may be necessary to pull back wire sheath to identify wire colors. (see photo 32) 32 Wire sheath pulled back to identify wire colors Is there 120VAC across black & white wires as shown in photo 32? N Y Replace gas control. Check for 120VAC between black & white wires. -NOTEElectronic meter probes required. Use care not to damage connector during this check. Call for technical support. Page 29 29 TTW SERVICE PROCEDURE X Dip Tube Inspection and replacement Dip Tube Inspection and Replacement WARNING Water Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury. Step 1. Position on/off switch of gas control valve to “OFF” position and unplug water heater from wall outlet. Step 2. Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain valve of water heater and allow heater to drain to a point below the inlet connection nipple. Step 3. Disconnect inlet nipple from plumbing system. Step 4 With an appropriate tool such as a pipe wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage pipe threads. Step 5. Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage. Hydro-jet slots should be open and free of any blockage. Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable and the inlet nipple/dip tube must be replaced. Step 6. Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into water heater. Connect nipple to plumbing system, resume water supply and refill with water. Step 7. To resume operation follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual. Page 30 30 TTW SERVICE PROCEDURE XI Anode Inspection and replacement Anode Inspection and Replacement WARNING Water Heater components and stored water may be HOT when performing the following steps in this procedure. Take necessary precaution to prevent personal injury. Step 1. Position on/off switch of gas control valve to the “OFF” position and unplug water heater from wall outlet. Step 2. Turn off cold water supply to water heater. Connect hose to drain valve of water heater and route to an open drain. Open a nearby hot water faucet to vent water heater for draining. Open drain valve of water heater and allow water heater to drain to a point below the outlet connection nipple. Step 3. Disconnect outlet nipple from plumbing system. Step 4 With an appropriate tool such as a pipe wrench, remove outlet nipple/anode from the water heater. Use caution not to damage pipe threads. Step 5. Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal. If depletion is ½ of the original anode diameter (approximately ¾” diameter), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended. Step 6. Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into water heater. Connect nipple to plumbing system, resume water supply and refill with water. Step 7. To resume operation, follow the instructions located on the lighting instruction label or the lighting instructions located in the installation and operation manual. Page 31 31 TTW SERVICE PROCEDURE XII Flue Baffle Inspection and replacement Remove blower to gain access to flue baffle Disconnect vent system from exhaust adapter. Step 1. Position gas control power switch to the “OFF” position and unplug blower from wall outlet. Step 2. Disconnect vent system from exhaust adapter on top of blower. Step 3. Unplug cord sets from blower. (see photo 33). Step 4. Remove the three blower mounting screws (¼" nut driver) (see photo 33). Step 5. Remove blower with gasket from water heater. Step 6. Remove flue baffle from Heater (see photo 34). Step 7. Inspect baffle for deterioration, missing restrictors. Clean any scale or debris build up. Replace with new baffle as necessary. Step 8. Reinstall baffle into flue tube. Be sure baffle hanger tab are inserted into notch location at the top of the flue tube (see photos 35 & 36). Step 9 Check Burner to insure no scale has accumulated during this operation. See burner cleaning procedure on page 14. Step 10. Reinstall blower on water heater. Connect vent system and cords set to blower. Plug water heater into wall outlet. Step 11. To resume operation follow the lighting instruction located on the lighting instruction label or the lighting instruction located in the installation and operation manual. 33 Blower Mounting Screws Blower Cord Sets 34 Flue Baffle 35 Flue tube notch 36 Baffle shown installed in flue tube notch. Page 32 32 Glossary of Terms BTU GPM Hz KW/h LED NPT Ohms PSI RPM TCO VAC W.C. °C °F British Thermal Units Gallons per Minute Hertz Kilowatts per hour Light Emitting Diode National Pipe Thread Ohms of resistance Pounds per Square Inch Revolutions per Minute Temperature Cut Off Volts Alternating Current Inches of Water Column Degrees Centigrade Degrees Fahrenheit NOTES Page 33 33 NOTES Page 34 34 Parts List Optional 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Blower Complete Air Mixing Inlet cover Pressure Switch Blower Temp. Switch Blower Gasket Blower Power Cord Vent Adapter Condensate Hose Kit Flue Reducer Heat Trap Outlet Hot Water Outlet Anode Flue Baffle 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. Heat Trap Inlet Inlet Dip Tube Wire Harness T&P Valve ¾ NPT Plug Burner Assy. (Nat) Burner Head Main Burner Orifice Pilot Assy. (Nat) Pilot Orifice Feedline Burner Assy. (L.P.) 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. Cast Iron Burner Pilot Assy. (L.P.) Pilot Orifice (L.P.) Feedline Jam Nut Air Shutter Main Burner Orifice (L.P.) Outer Door Inner Door Brass Drain Valve Resistive Load Device Thermal well 37. Gas Control 38. Gas Control Service Tool 39. Kit-Gas Control 40. ASSE App’vd Mixing Valve 41. Kit-Heat Trap Insert 42. Exhaust Termination Elbow Page 35 35 Email parts@bradfordwhite.com techserv@bradfordwhite.com www.bradfordwhite.com
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No XMP Toolkit : 3.1-701 Create Date : 2007:12:05 10:48:33Z Creator Tool : QuarkXPress(tm) 6.52 Modify Date : 2007:12:05 10:49:54-05:00 Metadata Date : 2007:12:05 10:49:54-05:00 Producer : QuarkXPress(tm) 6.52 X Press Private : %%DocumentProcessColors: Black.%%EndComments Format : application/pdf Title : bwc_manual Document ID : uuid:afc7356a-a349-11dc-b935-0014510bb2fc Instance ID : uuid:b90bf660-a349-11dc-b935-0014510bb2fc Page Count : 36 Creator : QuarkXPress(tm) 6.52EXIF Metadata provided by EXIF.tools