NEOTHERM®
Factory
Mounted
Options
Heater Data Number of Units: Fuel
Natural
Propane
• Electronic PID modulating control
with large color touchscreen
display
• Password-protected parameters
for installer use
• Test feature allows forced min or
maxring
• Complete diagnostics for analog
and digital inputs
• Displays holds, alerts and errors
in clear text form
• Dray alarm contacts for ignition
failure
•Highcondensingefciency
•Modulationdownto20%offullre
(5:1 turndown)
• Sealed combustion chamber
• Pre-mix stainless steel burner
• Low NOx system exceeds the
most stringent regulations for air
quality - less than 10ppm NOx
Standard
Equipment
• Horizontal or vertical direct vent
• Horizontal vent and air terminals
• Vent and air pipe lengths of up to
100 equivalent feet (each)
• Built-in condensate trap
• Vent temperature cutoff feature
• Direct spark ignition system
• Sensor for domestic water tank
• 160 psi maximum working
pressure
• Stainless steel heat exchanger
with welded construction
(no gaskets)
• ASME "H" stamp
• 125 psi (861 kPa) ASME rated
pressure relief valve
•Waterowswitch(399-850 only)
• Temperature & pressure gauge
• Drain valve
• Integrated PID temperature and
ignition controls
• Alarm output
• Accepts external 4-20mA (0-10V
with optional convertor) modulation
signal
• On/off toggle switch
• Manual reset high limit
• Burner site glass
• Zero clearance to combustible sur-
faces
• Built-in cascade function for up to
eight NeoTherms
• 8 year limited warranty
Volume Water
Heater
NTV Volume Water Heater
Indoor Sizes 150-850
Submittal Data
Pump included (150-500 only)
No pump
Date:
Project #:
Engineer:
Prepared By:
Bid Date:
Project Name:
Location:
Contractor:
ASME "HLW" Stamp
CSD-1
(covers FM & GAP) (500-850 only)
Low water cutoff (500-850 only)
High & Low gas pressure
switches (500-850)
Additional auto reset high limit
60 psi pressure relief valve
75 psi pressure relief valve
125 psi pressure relief valve (std)
150 psi pressure relief valve
Bell for ignition failure
H
Submittal Data
Volume Water
Heater
Brute
BNTV
Brutes.
■
■
Sizing Data
Input Output Thermal Gas Conn. Water Shipping
Model Efciency Size Conn.Size Weight
BTU/h kW BTU/h kW % inches inches lbs kg
NTV 150 150,000 44.0 142,500 41.7 95 ½ NPT 1¼ NPT 228 103
NTV 199 199,000 58.3 193,030 56.5 97 ½ NPT 1¼ NPT 270 123
NTV 285 285,000 83.5 270,750 79.3 95 ¾ NPT 2 NPT 299 136
NTV 399 399,000 116.9 383,040 112.2 96 ¾ NPT 2 NPT 364 165
NTV 500 500,000 146.5 480,000 140.6 96 1 NPT 2 NPT 419 190
NTV 600 600,000 175.8 582,000 170.4 97 1 NPT 2 NPT 426 193
NTV 750 750,000 219.8 705,000 206.4 94 1½ NPT 2 NPT 481 218
NTV 850 850,000 249.1 816,000 238.9 96 1½ NPT 2 NPT 503 228
Clearances
Suggested Service
Appliance Access Clearance
Surface inches cm
Left Side 1 2.5
Right Side 12 31
Top 24 61
Back 6 15
Closet, Front 6 15
Alcove, Front 24 61
Vent – –
CertiedbyCSAforzeroclearancetocombustiblematerialsonallsides.
Accessories
for Field
Mounting
Vent System Intake (Air) Exhaust (Vent) Maximum Allowable
Size Pipe Pipe Equivalent Length*
150 3" 3" 100 ft 30 m
199 3" 3" 100 ft 30 m
285 3" 3" 20 ft 6.1 m
4" 4" 100 ft 30 m
399 4" 4" 100 ft 30 m
500 4" 4" 100 ft 30 m
600 4" 4" 40 ft 12 m
**6"** **6"** 100 ft 30 m
750 4" 4" 40 ft 12 m
6" 6" 100 ft 30 m
850 4" 4" 40 ft 12 m
6" 6" 100 ft 30 m
Installations in the U.S. require exhaust vent pipe that is a combination of PVC & CPVC complying with ANSI/ASTM D1785
F441, polypropylene pipe that complies with ULC S636, or stainless steel complying with UL1738. Installations in Canada
requireexhaustventpipethatiscertiedtoULCS636.
Intake (air) pipe may be ABS, PVC, CPVC or galvanized material.
Installer must comply fully with manufacturer's installation instructions, including use of minimum exhaust length CPVC, to
maintainANSIZ21.13safetycertication.
Closet and alcove installations do not allow the use of PVC under any circumstances
* To calculate max equivalent length, measure the linear feet of the pipe, and add 5 feet (1.5m) for each elbow used.
**
Allowed only if the vent pipe is no more than 20 equivalent feet longer than the air pipe.
** **
Waterowswitch(285only)
Low water cutoff
0 - 10V convertor for
modulation control
High & Low gas pressure
switches
Boiler pump (285-500)
Concentric vent terminal, 2"
Concentric vent terminal, 3"
Flush-mount terminal, 3"
Flush-mount terminal, 4"
Propane conversion kit
Condensate neutralizer kit
BACnet gateway
LON gateway
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV
BNTV
Recovery
Data
GPH Delivered
REQUIRED WATER TEMPERATURE RISE
40°F 50°F 60°F 70°F 80°F 90°F 100°F 120°F 140°F
Size GPH GPH GPH GPH GPH GPH GPH GPH GPH
150 431 345 287 246 215 191 172 144 123
199 579 463 386 331 290 257 232 193 166
285 818 654 545 467 409 363 327 273 234
399 1153 923 769 659 577 513 461 384 329
500 1451 1161 967 829 726 645 580 484 415
600 1729 1383 1152 988 864 768 691 576 494
750 2170 1736 1447 1240 1085 964 868 723 620
850 2434 1947 1622 1391 1217 1082 973 811 695
L/h Delivered
REQUIRED WATER TEMPERATURE RISE
22°C 28°C 33°C 39°C 44°C 50°C 56°C 67°C 78°C
Size L/h L/h L/h L/h L/h L/h L/h L/h L/h
150 1629 1303 1086 931 814 724 651 543 465
199 2190 1752 1460 1251 1095 973 876 730 626
285 3091 2473 2061 1766 1545 1374 1236 1030 883
399 4359 3487 2906 2491 2181 1937 1744 1453 1245
500 5485 4388 3657 3134 2743 2438 2194 1828 1567
600 6536 5288 4355 3735 3266 2903 2612 2177 1867
750 8203 6562 5470 4687 4101 3644 3281 2733 2344
850 9201 7360 6131 5258 4600 4090 3678 3066 2627
Electrical
Data
Heater Pump Connection Ratings
Sizes Volts Phase Amps
(System Pump and DHW Pump Connections)
150-850 120 Single 2* n/a
No pump
150-199 120 Single 7* 115V - Maximum 1HP
With pump or 7.4A max
285-500 120 Single 8* 115V - Maximum 1 HP
With pump or 7.4A max
*Minimum 15A circuit required
Water Flow
Requirements
NORMAL WATER*
Flow H/L Temp Flow H/L Temp
Size gpm feet Rise °F lpm m Rise °C
150 19 57 15 72 17.4 8
199 25 28 15 95 8.5 8
285 36 33 15 98 10.1 8
399 50 35 15 189 10.7 8
500 63 28 15 239 8.5 8
600 60 24 19 227 7.3 11
750 68 35 21 257 10.7 12
850 68 26 24 257 7.9 13
*Maximum water hardness of 10 grains per gallon allowed
200 Lafayette St.
Middleville, MI 49333
Warranty: (800) 531-2111
www.BradfordWhite.com
Litho in U.S.A. © Bradford White 1608 Document 2152J-BW
Laars Heating Systems Company reserves the right to change specications, components, features, or to discontinue products without notice.
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
Headquarters: 20 Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1608 Document 2152J
Dimensional
Data
A B C D E F G J K M N
Size in cm in cm in cm in cm in cm in cm in cm in cm in cm in cm in cm
150 13¼ 34 5¼ 14 19 48 3¼ 8 10¾ 28 7½ 19 14¼ 36 19½ 49 7½ 19 15¼ 39 13 33
199 20½ 52 5¼ 14 19 48 3¼ 8 17¾ 45 7½ 19 14¼ 36 19½ 49 11¾ 30 15¼ 39 13 33
285 20¼ 52 7¼ 19 19¾ 50 4¼ 16 11¼ 29 13½ 34 14 36 15 38 17 43 18¾ 48 13 33
399 25 64 5¼ 13 19¾ 50 4¼ 11 14¾ 37 18½ 47 19¼ 49 16½ 42 21¾ 55 18¾ 48 13 33
500 30¼ 77 5¼ 13 19¾ 50 4¼ 11 15¼ 38 20 51 20½ 52 19 48 26 66 18¾ 48 13 33
600 29¾ 76 5 13 19½ 50 4¼ 11 15 38 20 51 3 8 19 48 26 66 18¾ 48 8¼ 21
750 35½ 90 6 15 19½ 50 5¼ 13 19 48 40½ 103 3¼ 8 19 48 30¾ 78 18¾ 48 8¼ 21
850 39¾ 101 6 15 19½ 50 5¼ 13 19 48 44¾ 114 3½ 9 19 48 35 89 18¾ 48 8¼ 21
Dimensions are nominal and are shown in inches, cm.
*NeoTherm is shipped with adapters for the air and vent
that accept standard pipe of the proper size and type.
L AIR INLET VENT
Size in cm in cm in cm
150 19½ 49 3 7.6 3 7.6
199 26¾ 68 3 7.6 3 7.6
285 26¾ 68 4 11 4 11
399 31½ 80 4 11 4 11
500 37¾ 96 4 11 4 11
600 37¾ 96 4 11 4 11
750 51 130 4 11 6 17
850 55¼ 140 4 11 6 17
*Brute is shipped with adapters for the air and vent that
accept standard pipe of the proper size and type.