COMMERCIAL AIR-COOLED
CONDENSING UNITS WITH
524A AIR-HANDLING UNITS

Models 566D, 566E, 569D,
569F, 576C
with 524A
6 to 20 Tons

569D072-120
576C120
569F120

524A072-300

566D150-240
566E150-240

FEATURES/BENEFITS
These dependable split systems match Bryant’s indoor-air handlers and direct-expansion coils with outdoor condensing units
for a wide selection of commercial cooling solutions.
CONSTRUCTED FOR LONG LIFE — The 569D (single circuit, scroll compressor), 576C (single circuit semi-hermetic
compressor), 569F/566E (dual circuit, scroll compressor) and
566D (semi-hermetic compressor) models are designed and
built to last. The copper tube-aluminum fin outdoor coil
construction provides years of trouble-free operation. Where
conditions require them, E-coated coils and pre-coated fin coils
are also available. Cabinets are constructed of prepainted
galvanized steel, delivering unparalleled protection from the
environment. Inside and outside surfaces are protected to
ensure long life, good looks, and reliable operation. Safety controls are used for enhanced system protection and reliability.
EFFICIENT OPERATION — Building owners will appreciate
the high unit EERs (Energy Efficiency Ratios) offered by these
condensing units. These units provide greater efficiency than
similar units in the marketplace, which translates into yearround operating savings.
CONTROLS FOR PERFORMANCE DEPENDABILITY — The
condensing units offer the building owner operating controls
and components designed for performance dependability. The
highly efficient hermetic and semi-hermetic compressors are
engineered for long life and durability. The compressors
include overload protection and vibration isolation for enhancement of quiet operation. The high-pressure switch protects the
entire refrigeration system from abnormally high operating

pressures. A low-pressure switch protects the system from
low-pressure conditions, including loss of charge.
The 569F120 and 566E150-240 units feature 2 scroll compressors and 2 refrigerant circuits that provide continuous air
conditioning and design flexibility. These units also include
Cycle-LOC™ anti-short-cycling protection which helps to
protect the units against compressor failure.
All units include a crankcase heater to eliminate liquid slugging
at start-up. Units with semi-hermetic compressors are also
equipped with an oil-level sight glass.
Latest safety standards are assured through UL and UL
Canada approvals.
INNOVATIVE BRYANT PACKAGED AIR HANDLERS ARE
CUSTOM MATCHED TO THE CONDENSING UNITS — The
524A Series has excellent fan performance, efficient directexpansion (DX) coils, a unique combination of indoor-air quality features, and easy installation. Its versatility and state-ofthe-art features help to ensure that your split system provides
economical performance now and in the future.
Indoor-Air Quality (IAQ) Features — The unique combination
of IAQ features in the 524A Series air handlers help to ensure
that only clean, fresh, conditioned air is delivered to the occupied space.
Direct-expansion (DX) cooling coils prevent the build-up of
humidity in the room, even during part-load conditions. Unit
sizes of 10 tons and above feature dual-circuit coils for
improved temperature control.
Standard 2-in. disposable filters remove dust and airborne particles from the occupied space for cleaner air.

Form No. PDS 569D.72.2

Thermal insulation contains an EPA-registered immobilized
anti-microbial agent to inhibit the growth of bacteria and fungi.
The pitched, non-corroding drain pan can be adjusted for a
right- or left-hand connection to suit many applications and
provide positive drainage and to prevent standing condensate.
The 524A accessory economizer can provide ventilation air to
improve indoor air quality by using demand control ventilation.
When used in conjunction with a 2 to 10 VDC adapter on the
actuator and a CO2 sensor, the economizer admits fresh
outdoor air to replace stale, recirculated indoor air as needed.
Economy — The 524A Series packaged air handlers have low
initial costs, and they continue to save money by providing
reduced installation expense and energy-efficient performance.
Quick installation is ensured by the multipoise design. Units can
be installed in either the horizontal or vertical configuration without modifications. Fan motors and contactors are prewired and
thermostatic expansion valves (TXVs) are factory-installed on
all 524A direct-expansion models.
High efficiency, precision-balanced fans minimize air turbulence, surging, and unbalanced operation, cutting operation
expenses.
The economizer accessory precisely controls the blend of outdoor air and room air to achieve comfort levels. When the
outside air enthalpy is suitable, outside air dampers can fully

open to provide “free” cooling without energizing mechanical
cooling.
Rugged Dependability — The 524A series units are made to
last. The die-formed galvanized steel panels ensure structural
integrity under all operating conditions. Galvanized steel fan
housings are securely mounted to a die-formed galvanized
steel fan deck.
Rugged pillow-block bearings (524A150-300) are securely fastened to the solid steel fan shaft with split collets and clamp
locking devices. Smaller unit sizes have spider-type bearings.
Coil Flexibility — Model 524A direct-expansion coils have galvanized steel casings; inlet and outlet connections are on the
same end. The coils are designed for use with Refrigerant 22
and have 3/8-in. diameter copper tubes mechanically bonded to
aluminum sine-wave fins. The coils include matched, factoryinstalled thermostatic expansion valves (TXVs) with matching
distributor nozzles.
Easier Installation and Service — The multipoise design and
component layout help you to get the unit installed and running
quickly. Units can be converted from horizontal to vertical operation by simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters, motor, drive,
TXVs, and coil connections are all easily accessed by removing
a single side panel.

TABLE OF CONTENTS
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
ARI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10
569D072-120, 576C120, 569F120
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13,14
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-25
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32
566D/E150-240
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34,35
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-38
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-52
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-56
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57,58
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59,60
524A072-300
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63-65
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66-71
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-78
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79-81
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82,83

2

ARI* CAPACITY RATINGS
CONDENSING
UNIT

SYSTEM†

AIR
HANDLER/
INDOOR COIL

Net Cap.
(Btuh)
69,000
72,000
71,000
74,000
87,000
91,000
90,000
94,000
118,000
125,000
123,000
130,000
114,000
119,000
118,000
125,000
113,000
118,000
118,000
124,000
138,000
144,000
144,000
146,000
135,000
143,000
145,000
153,000
152,000
161,000
176,000
182,000
184,000
196,000
176,000
185,000
187,000
198,000
194,000
204,000
244,000
243,000
242,000
252,000

524A-B072††
524A-C072††
524A-B090
524A-C090††
524A-B072
524A-C072††
524A-B090
524A-C090††
524A-B120
524A-C120
524A-B150
524A-C150
524A-B120
524A-C120
524A-B150
524A-C150
524A-B120
524A-C120
524A-B150
524A-C150
524A-B150
524A-C150
524A-B180
524A-C180
524A-B120
524A-C120
524A-B150
524A-C150
524A-B180
524A-C180
524A-B180
524A-C180
524A-B240
524A-C240
524A-B150
524A-C150
524A-B180
524A-C180
524A-B240
524A-C240
524A-C300
524A-C240
524A-B300
524A-C300

569D072

569D090

569D120

576C120

569F120

566D150

566E150

566D180

566E180

566D240
566E240

EER

IPLV

11.0
11.2
10.8
11.0
10.6
11.3
10.6
11.2
10.3
10.4
10.4
10.4
10.3
10.3
10.4
10.3
10.3
10.5
10.5
10.9
10.4
10.6
10.6
10.8
9.7
10.2
10.5
11.1
10.8
11.3
9.8
9.7
9.8
10.0
10.0
10.3
10.2
10.6
10.1
10.4
9.5
9.6
9.6
9.7

N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
13.1
13.6
14.1
14.5
11.7
12.4
12.8
13.2
12.7
13.0
11.6
13.1
9.9
10.3
10.9
11.5
11.0
11.5
12.3
12.1
12.2
12.5
10.4
10.8
10.5
10.9
10.2
10.4
11.8
9.8
9.9
9.9

CONDENSING UNIT ONLY**
Gross Cap.
EER
(Btuh)
72,000

12.4

N/A

100,000

12.7

N/A

133,000

12.4

N/A

124,000

12.0

16.5

123,000

12.3

16.0

150,000

12.1

15.8

158,000

12.5

15.1

198,000

11

14.9

204,000

11.9

13.9

248,000

10.5

13.9

259,000

11.2

13.1

LEGEND
EER — Energy Efficiency Ratio
IPLV — Integrated Part Load Value
N/A — Not Applicable
SST — Saturated Suction Temperature
*Air Conditioning and Refrigeration Institute.
†Ratings in accordance with latest ARI Standard revisions.
**Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.
††ENERGY STAR® compliant combination of condensing unit and air handler/
indoor coil.

SOUND LEVELS, dB — 569D/576C/566D,E
UNIT
569D
576C
566D

566E

SOUND RATING
(60 Hz) dB (A)

072
090
120
120
150
180
240
150
180
240

80.0
84.0
85.0
83.0
86.2
86.2
90.0
86.9
87.5
88.0

63
43.8
58.5
63.7
52.5
—
—
83.5
—
—
—

125
61.4
67.3
67.6
66.1
93.0
93.0
81.5
90.9
90.9
90.9

250
66.2
71.3
72.5
75.1
86.0
86.0
88.5
86.1
86.1
86.1

OCTAVE BANDS
500 1000 2000
70.8 73.8
75.2
75.4 77.2
75.8
77.0 80.4
77.5
75.4 78.3
73.5
83.0 80.0
78.0
83.0 80.0
78.0
86.5 85.5
82.5
83.1 84.0
73.5
83.4 84.5
76.6
83.8 84.5
79.2

4000
73.0
76.5
74.7
71.0
73.0
73.0
76.5
71.7
73.2
74.3

8000
62.7
71.3
65.9
64.2
71.0
71.0
61.5
66.7
63.5
65.5

ESTIMATED SOUND POWER LEVELS (Lw) — 524A072-300
UNIT

CFM

dB(A)

524A072
524A090
524A120
524A150
524A180
524A240
524A300

2,400
3,000
4,000
5,000
6,000
8,000
10,000

86.3
88.3
91.6
91.1
92.7
96.4
96.2

63
93.2
95.3
98.6
97.3
98.9
102.6
102.5

OCTAVE BAND CENTER FREQUENCY
125
250
500
1000
2000
89.2
85.2
84.2
80.2
78.2
91.3
87.3
86.3
82.3
80.3
94.6
90.6
89.6
85.6
83.6
93.3
89.3
90.3
84.3
82.3
94.9
90.9
91.9
85.9
83.9
98.6
94.6
95.6
89.6
87.6
98.5
94.5
95.5
89.5
87.5

4000
74.2
76.3
79.6
78.3
79.9
83.6
83.5

NOTE: Since this data is calculated, these sound power levels may be different than the actual
sound power levels. The accoustic center of the unit is located at geometric center of the unit.

3

IPLV

OPTIONS AND ACCESSORIES
566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED
OPTIONS
Dura-Shield Condenser Coils offer several options to match
coil protection to site conditions for optimum durability. See
table below. Consult your Bryant representative for further
information.
E-Coated Aluminum-Fin Coils have a flexible and durable
epoxy coating uniformly applied to all coil surfaces. Unlike brittle
phenolic dip and bake coatings, E-coating provides superior
protection with unmatched flexibility, edge coverage, metal
adhesion, thermal performance, and most importantly, corrosion resistance.
E-coated coils provide this protection since all coil surfaces are
completely encapsulated from environmental contamination.
This coating is especially suitable in industrial environments.
Pre-Coated Fin Coils provide protection in mild coastal
environments.
–20 F Low-Ambient Temperature Kit Option (Motormaster®)
(566E, 569D, 569F, 576C Only) controls outdoor-fan motor
operation to maintain the correct head pressure at low outdoor
ambient temperatures.
115-v Convenience Outlet (566E, 569D, 569F, 576C Only) to
power up electric drills, lights, and refrigerant recovery
machines. This means you are no longer required to run a separate 115-v power supply.

Non-Fused Disconnect Switch (566E, 569D, 569F, 576C
Only) to remove power locally at the condensing unit. This
switch also includes a power lockout capability to protect the
service person. This lockout switch saves the service person
time and effort because there is no need to access a distant disconnect switch while servicing the unit.
FIELD-INSTALLED ACCESSORIES
Electric Unloader Package (576C120 Only) includes hardware and solenoid valve to convert a pressure-operated
unloader to electric unloading.
–20 F Low-Ambient Temperature Accessory Kit (Motormaster) controls outdoor-fan motor operation to maintain the correct
head pressure at low outdoor ambient temperatures.
Condenser Coil Grille Package protects condensing unit coil
from impact by large objects and vandalism.
Bryant’s Line of Thermostats provide both programmable and
non-programmable capability with the new Debonair® line of
commercial programmable thermostats. The Commercial
Electronic thermostats provide 7-day programmable capability
for economical applications.
Hail Guard Package protects against damage from flying
debris and hail.
Gage Panel Package provides a suction and discharge pressure gage for the refrigerant circuit.

CONDENSER COIL OPTIONS
ENVIRONMENT
Mild
Industrial/
Standard
Coastal
Coastal
X
X
X

COPPER-TUBE COILS
WITH DURA-SHIELD
OPTION
Al Fins (Standard Coils)
Al Fins, E-Coated
Al Fins, Pre-Coated
LEGEND
Al — Aluminum

LOW AMBIENT CONTROL
(FACTORY-INSTALLED OR
FIELD-INSTALLED)

FACTORY-INSTALLED
DURA-SHIELD
COIL PROTECTION

FACTORY-INSTALLED
CONVENIENCE OUTLET

FACTORY-INSTALLED
DISCONNECT SWITCH

Options and Accessories

4

OPTIONS AND ACCESSORIES (cont)
524A-B, C FACTORY-INSTALLED OPTIONS
Alternate Fan Motors and Drives are available to provide the
widest possible range of performance.
High-Capacity 4-Row Coils are available to provide increased
latent and sensible capacities (524A-C).
Prepainted Steel Units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color.
FIELD-INSTALLED ACCESSORIES
Two-Row Hot Water Coils have copper tubes mechanically
bonded to aluminum plate fins and non-ferrous headers.
One-Row Steam Coil has copper tubes and aluminum fins.
The Inner Distributing Tube (IDT) design provides uniform
temperatures across the coil face. The steam coil has a broad
operating pressure range; up to 20 psig (138 kPag) at 260 F
(127 C). The IDT steam coils are especially suited to applications where sub-freezing air enters the unit.
Electric Resistance Heat Coils have an open-wire design and
are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Terminal block for single-point
power connection is included.
Economizer (Enthalpy Controlled) provides ventilation air
and “free” cooling if outside ambient temperature and humidity
are suitable.
Discharge Plenum directs the air discharge directly into the
occupied space integral horizontal and vertical louvers enable
redirection of airflow. Accessory is available unpainted or
painted. Field assembly required.

Return-Air Grille provides a protective barrier over the returnair opening and gives a finished appearance to units installed in
the occupied space. Accessory is available unpainted or
painted.
Subbase provides a stable, raised platform and room for condensate drain trap connection for vertical floor-mounted units.
Accessory is available unpainted or painted.
Overhead Suspension Package includes necessary brackets
to support units in horizontal ceiling installations.
Bryant’s Line of Thermostats provide both programmable and
non-programmable capability. The Commercial Electronic
thermostats provide 7-day programmable capability for economical applications.
Condensate Drain Trap includes an overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includes a wire harness that can be connected
to an alarm if desired. The transparent trap is designed for easy
service and maintenance.
UV-C Germicidal Lamps kill mold and fungus, which may grow
on evaporator coil and condensate pan surfaces. The use of
UV-C germicidal lamps eliminates the foul odors that result from
this growth of mold and fungus. It also provides a self-cleaning
function for the evaporator coil and drain pan.

Commercial Programmable
and Non-Programmable Thermostat

5

OPTIONS AND ACCESSORIES (cont)
HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT

FAN COIL
UNIT

524A with Discharge Plenum,
Return Grille, and Subbase

524A with Hot Water or Steam Coil

ECONOMIZER

FAN COIL UNIT

524A with Economizer

524A with Condensate Trap

6

SELECTION PROCEDURE
To determine combination ratings for 569D/F, 576C and 566D/E
units matched with 524A Series air handlers, follow these steps:
I DETERMINE COOLING LOAD, EVAPORATOR-AIR
TEMPERATURE, AND QUANTITY.
Given:
Total Cooling Capacity
Required (TC). . . . . . . . . . . . . . . . . . . . . . 127,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . . . 95,000 Btuh
Compressor Type . . . . . . . . . . . . . . . . . . . . . . . . . . .Scroll
Temperature Air Entering Condenser (Edb). . . . . . . . 95 F
Temperature Air Entering
Evaporator (db/wb). . . . . . . . . . . . . . . .80 F db, 67 F wb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 4,000 cfm
External Static Pressure . . . . . . . . . . . . . . . . . . 0.4 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . . . . . 25 ft (Linear)
Power Supply (V-Ph-Hz) . . . . . . . . . . . . . . . 208/230-3-60
II SELECT
CONDENSING
UNIT
AIR-HANDLER
COMBINATION.
For this example, select a 569D120 matched with a
524A-C120 with high-capacity 4-row coil This 569D120/
524A-C120 condensing unit air-handler combination
provides 130,000 Btuh of total cooling capacity and
98,200 Btuh of sensible capacity at the given conditions. If
other temperatures or airflow values are required, interpolate the values from the combination ratings.

III DETERMINE SIZES OF LIQUID AND SUCTION LINES.
Enter Refrigerant Piping Sizes table. The sizes shown are
based on an equivalent length of pipe. This equivalent
length is equal to the linear length of pipe indicated at the
top of each sizing column, plus a 50% allowance for fitting
losses. (For a more accurate determination of actual
equivalent length in place of using the estimated 50%
value, refer to a standard refrigeration piping practice.) For
this example, note in the linear length column that the
proper pipe size is 1/2 in. for the liquid line and 13/8 in. for
the suction line.
IV DETERMINE FAN RPM AND BHP (BRAKE
HORSEPOWER).
At the Air Handler Fan Performance table enter at 524AC120 with high capacity coil at 4000 cfm and move to the
External Static Pressure (ESP) column. Note that the conditions require 803 rpm at 1.77 bhp.
V DETERMINE MOTOR AND DRIVE.
Enter the Fan Motor Data tables and find the standard
motor for 524A-C120 unit rated at 2.4 Hp. Since the bhp
required is 1.77, a standard motor satisfies the requirement and should be used.
Next, find the type of drive that satisfies the 803 rpm
requirement in the Drive Data tables. For the 524A-C120
unit, the Standard Drive table on shows an rpm range of
666-863. Since the rpm required is 803, the standard drive
satisfies the requirement and should be used. Select the
standard motor and standard drive combination (option
code GC or ED).

7

CONTROLS
OPERATING SEQUENCES
569D072-120, 576C120 — At start-up, the thermostat calls for
cooling. With all safety devices satisfied, the compressor
contactor and fan contactor energize, causing the compressor
and outdoor-fan motor to operate. Thermostat contacts
energize, allowing the field-supplied and field-installed indoorfan contactor to function. A field-supplied and field-installed liquid line valve also opens, allowing the system to function in
Cooling mode. As cooling demand is satisfied, the thermostat
contacts break, deenergizing the contactor and causing the
system to shut off. The liquid line solenoid valve closes, minimizing the potential for refrigerant migration. The compressor
does not restart until the thermostat again calls for cooling. The
system is protected with a safety circuit so that the system will
not start if a fault exists (i.e., high or low pressure fault). To reset
the safety circuit, set the thermostat to eliminate the cooling
demand, then return to original set point. This should be done
only once, and if system shuts down due to the same fault,
determine the problem before attempting to restart the system.
566D150-240 — When the first stage of cooling thermostat
closes, the timer starts. After approximately 3 seconds, the
timer activates the compressor and fan motor no. 1 contactors.
When the liquid pressure builds to approximately 257 psig, fan
motor no. 2 is energized.
When there is demand for additional cooling capacity, the
second stage of the cooling thermostat closes, energizing a
field-supplied liquid line solenoid (LLS) valve, which opens. This
increases the suction pressure, causing the compressor to
operate at higher capacity (compressor loads).
When the fan switch is set at AUTO, the indoor-air fan cycles
with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.
At shutdown, the Time Guard II timer prevents the compressor
from restarting for approximately 5 minutes.
In addition, an LLS valve wired in parallel with the compressor
contactor coil shuts off the liquid line to prevent refrigerant
migration back to the compressor during the off cycle.
569F120 — When the thermostat calls for stage one cooling at
start-up, and all safety devices are satisfied, the compressor
contactor no. 1 (C1) energizes causing compressor no. 1 and
outdoor-fan motor no. 1 to start (the indoor-fan contactor should
be wired to start at the same time as the compressor). The
liquid line solenoid (LLS) valve will open when compressor no. 1
starts, allowing refrigerant to flow in the system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 and
outdoor-fan motor no. 2 to start. As the cooling demand
decreases, stage two on the thermostat opens, causing
compressor no. 2 and outdoor-fan motor no. 2 to shut down. As

the cooling continues to decrease, stage one of the thermostat
opens causing compressor no. 1 and outdoor-fan motor no. 1 to
shut down. The LLS valve for each compressor will close when
the associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set to CONT.
Each compressor is protected with a Cycle-LOCTM device so
that the compressor will not operate if there is a high-pressure
fault, low pressure fault, or a compressor is off due to internal
line break overcurrent/overtemperature protection. To reset the
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.
566E150-240 — At start-up, when the thermostat calls for first
stage cooling and all safety devices are satisfied, the compressor contactor (C1) energizes causing compressor no. 1 and fan
motor no. 1 to start. Fan motor no. 2 will start when the fan
cycling pressure switch (FCPS) closes as discharge pressure
builds (refer to physical data table for FCPS specifications).
With the indoor-fan contactor wired to TB2-4 and TB2-9
contacts on the terminal block, the indoor fan will also start with
the compressor. The liquid line solenoid (LLS) valve will open
when compressor no. 1 starts, allowing refrigerant to flow in the
system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 to
start. As the cooling demand decreases, stage two on the
thermostat opens, causing compressor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermostat
opens causing compressor no. 1 and outdoor-fan motor to shut
down. The LLS valve for each compressor will close when the
associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set on CONT.
Each compressor is controlled by the thermostat so they will not
start until there is a demand from the thermostat. Each
compressor is protected with a Cycle-LOC device so that the
compressor will not operate if there is a high-pressure fault,
low-pressure fault, or compressor is off due to internal line
break overcurrent/overtemperature protection. To reset the a
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.

8

TYPICAL WIRING SCHEMATICS

NOTES:
1. If any of the original wire furnished must be
replaced, it must be replaced with type 90° C
wire or its equivalent.
2. Thermostat: HH07AT170, 172, 174 & P2722783
Subbase: HH93AZ176, 178 & P272-1882, 1883
or HH93AZ177 & 179.
3. Sealed VA for IFC and LLSV is not to exceed
22.
4. Use copper conductors only.
5. TRAN is wired for 230 v unit. If unit is to be run
with 200 v power supply, disconnect BLK wire
from 230 v tap and connect to 200 v tap.
6. If TRAN is wired for 460-3-60 v and unit is to be
run with 400-3-50 v power supply, disconnect
BLK wire from 460 v tap and connect to 400 v
tap.
7. Three-phase motors are protected under primary single phasing conditions.
VOLTAGE
RATING
24 V

CB
Mfg. Part No.
Potter & Brumfield
W28X-1024-3.2

MUST
TRIP
AMPS
3.2

LEGEND
AHA
C
CAP
CB
CC
CH
CLO
COMP
DGT
EQUIP
GND
HPS
IFC

—
—
—
—
—
—
—
—
—
—
—
—
—

Adjustable Heat Anticipator
Contactor, Compressor
Capacitor
Circuit Breaker
Cooling Compensator
Crankcase Heater
Compressor Lockout
Compressor Motor
Discharge Gas Thermostat
Equipment
Ground
High-Pressure Switch
Indoor-Fan Contactor

LLSV
LPS
NEC
OFM
QT
TB
TC
TH
TRAN

—
—
—
—
—
—
—
—
—

Liquid Line Solenoid Valve
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Motor
Quadruple Terminal
Terminal Block
Thermostat-Cooling
Thermostat-Heating
Transformer

——

Field Splice
Marked Wire

Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not Represent Wiring

569D090, 208/230-3-360 and 460-3-60 Units

9

TYPICAL WIRING SCHEMATICS (cont)

LEGEND
AHA

— Adjustable Heat
Anticipator
C
— Contactor,
Compressor
CAP
— Capacitor
CB
— Circuit Breaker
CC
— Cooling Compensator
CH
— Crankcase Heater
COMP — Compressor Motor
COTP — Compressor Over
Temperature Protection
EQUIP — Equipment
GND
— Ground
HPS
— High-Pressure Switch
IFC
— Indoor-Fan Contactor
LLSV — Liquid Line Solenoid
Valve
LPS
— Low-Pressure Switch
NEC
— National Electrical Code
OFM
— Outdoor-Fan Motor
OL
— Overload Relay
R
— Relay
TB
— Terminal Block
TC
— Thermostat-Cooling
TH
— Thermostat-Heating
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
——

Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicates Common
Potential Only, Not
Represent Wiring

576C120, 208/230-3-60 and 460-3-60 Units

10

MODEL NUMBER NOMENCLATURE
P

X

072

000

––

569D — Commercial Air-Cooled Condensing
Unit With Scroll Compressor
569F — Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressor

Factory-Installed Options*

Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60
Heating
X — None
Nominal Tons Cooling
072 — 6 (569D Only)
090 — 7-1/2 (569D Only)
120 — 10 (569D, 569F)

Heating Capacity
000 — No Heat

576C

P

X

120

000

––

576C — Commercial Air-Cooled Condensing
Unit With Semi-Hermetic Compressor

Factory-Installed Options*

Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60

Heating Capacity
000 — No Heat

Heating
X — None

Nominal Tons Cooling
120 — 10

Quality Assurance

*Contact your local representative for more details.

Certified to ISO 9001:2000

11

50TFQ004-012
569D072-120,
576C120, 569F120

569D

50TFQ004-012
569D072-120,
576C120, 569F120

PHYSICAL DATA
569D072-120, 576C120, 569F120 UNITS
UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Aluminum Coils (Standard)
Copper Coils (Optional)
RREFRIGERANT TYPE*
Operating Charge, Typical (lb)†
Shipping Charge (lb)
COMPRESSOR
Type
Qty...Model
Oil Charge (oz)
No. Cylinders
Speed (rpm)
CONDENSER FAN
Qty...Rpm
Motor HP (rpm)
Diameter
Nominal Airflow (Cfm Total)
Watts (Total)
CONDENSER COIL (Qty)
Face Area (sq ft total)
Rows...Fins/in.
Storage Capacity (lb)**
CONTROLS
Pressurestat Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
DISCHARGE GAS THERMOSTAT (°F)
Cutout
Cut-in
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. ODM)
Qty...Suction
Qty...Liquid

569D072
6

569D090
71 / 2

300
352

383
484

12
2.0

20
2.0

569D120
10
430
531
R-22
22
2.0

Scroll
1...SR_94
90
N/A
3500

1...SR_68
88

2...850
1/8
22
5400
340

1...ZR125
110

2...1100
1/4

2...1100
1/4
22
6500
570

1...17
17.3

2
29.2
2...17
34.2

—
—

428 ± 10
320 ± 20
27 ± 3
44 ± 5
2
270 ± 9
190 ± 13

2...17
34.2

576C120
10

569F120
10

575
676

488
589

24
2.0

11/Circuit
2.0

Reciprocating
1...06DH824
128
6
1750

Scroll
2...SR_60
72 (ea)
N/A
3500

2...1100
1/ 4
22
6500
570

2...1100
1/ 4
22
6500
570
2
29.2
2...17
17.1 (ea)

29.2
2...17
34.2

428 ± 10
320 ± 20
27 ± 3
44 ± 5
—
—

—
—

428 ± 10
320 ± 20
27 ± 3
44 ± 5
2
—
—

1...13/8
1...1/2

2...11/8
2...3/8

Suction Line
200
1...11/8
1...3/8

1...11/8
1...3/8

*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at
95 F.

1...13/8
1...1/2

NOTE: Unit 576C120 has one step of unloading. Full load is at 100% of
capacity, and one step of unloading is 67% capacity. Unit 576C120 has
the following unloader settings: load is 70 ± 1 psig and unload is 60 ±
2 psig.

12

DIMENSIONS

569D072
569D090
569D120
576C120

Standard Unit Weight
lb
kg
300
136
383
174
430
195
575
261

Corner W
lb
kg
62 28
86 39
84 38
55 25

ALUMINUM COIL
Corner X Corner Y Corner Z
lb kg lb kg
lb kg
103 47 62 28
72 33
123 56 85 39
89 40
166 75 66 30 114 52
265 120 88 40 167 76

Center of Gravity
X mm [in.]
Y mm [in.]
831.9 [32.75] 641.4 [25.25]
822.3 [32.38] 635.0 [25.00]
812.8 [32.00] 676.3 [26.63]
927.1 [36.50] 647.7 [25.50]

UNIT
569D072
569D090
569D120
576C120

ELECTRICAL
CHARACTERISTICS
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60
208/230-3-60, 460-3-60, 575-3-60

SERVICE VALVE CONNECTIONS
Suction
Liquid
Unit
mm [in.]
mm [in.]
1
569D072
28.6 [1 /8]
9.5 [3/8]
569D090
28.6 [11/8]
9.5 [3/8]
569D120
34.9 [13/8]
12.7 [1/2]
576C120
34.9 [13/8]
12.7 [1/2]

569D072-120, 576C120

13

50TFQ004-012
569D072-120,
576C120, 569F120

UNIT

50TFQ004-012
569D072-120,
576C120, 569F120

DIMENSIONS (cont)
OUTDOOR COIL
CORNER “A”

CORNER “B”

1162.7
[45.78]
Y
OUTDOOR COIL

O 34.5 [1.36]
POWER ENTRY
WITH 50.0/58.0/65.0 K.O.

CORNER “C”

X

CORNER “D”

ACCESS PANEL

TOP VIEW

ELECTRICAL DISCONNECT
LOCATION

LIQUID
CONNECTION
(SEE CHART
FOR SIZE)

CONTROL BOX
ACCESS PANEL
CONVENIENCE
OUTLET LOCATION

OUTDOOR
COIL

SUCTION
CONNECTION
(SEE CHART
FOR SIZE)

OUTDOOR
COIL
582.5
[22.93]
167.5
[6.59]

BOTTOM
OF UNIT

111.7
116.7
FORK TRUCK SLOTS [4.40]
[4.59]
(3 SIDES ONLY)
O 22.0 [0.87] FIELD
ENTRY SERVICE PORT

637.9
644.6 [25.11]
[25.38]

LIQUID CONNECTION
(SEE CHART FOR SIZE)

RIGHT SIDE VIEW

1509.3
[59.42]

FRONT VIEW

OUTDOOR
COIL

COMPRESSOR
ACCESS PANEL

(in.)

569F120

REAR VIEW

UNIT

569F120

ELECTRICAL
CHARACTERISTICS
208/230-3-60,
400/460-3-50/60,
575-3-60

ACCESS
PANEL

287.8 341.5
172.9 226.9 [11.33] [13.45]
[8.93]
[6.81]

LEFT SIDE VIEW

(in.)

OUTDOOR
COIL

Std. Unit
Wt.

Corner
A

ALUMINUM COIL
Corner
Corner
Corner
B
C
D

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

X
mm [in.]

Y
mm [in.]

488

221

102

46

143

65

139

63

104

47

873.8
[34.4]

591.8
[23.3]

569F120

14

Center of
Gravity

872.8
[34.36]

PERFORMANCE DATA
569D072

576C120

SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

80
53.6
4.24
101.0
59.1
4.33
102.0
64.9
4.42
104.0
71.0
4.53
106.0
77.4
4.65
107.0
84.2
4.78
109.0

Air Temperature Entering Condenser (F)
85
95
100
105
52.3
49.4
48.0
46.5
4.49
5.02
5.31
5.60
106.0
115.0
120.0
125.0
57.6
54.6
53.0
51.5
4.57
5.10
5.39
5.69
107.0
117.0
122.0
126.0
63.3
60.1
58.4
56.7
4.67
5.20
5.49
5.79
109.0
118.0
123.0
128.0
69.3
65.8
64.1
62.3
4.77
5.31
5.60
5.90
110.0
120.0
125.0
129.0
75.6
71.9
70.1
68.2
4.89
5.43
5.72
6.02
112.0
122.0
126.0
131.0
82.3
78.4
76.4
74.3
5.03
5.56
5.86
6.16
114.0
123.0
128.0
133.0

115
43.6
6.24
135.0
48.3
6.33
136.0
53.4
6.43
138.0
58.7
6.55
139.0
64.3
6.68
141.0
70.2
6.81
142.0

80
73.9
5.81
98.6
82.0
5.88
99.6
90.4
5.98
101.0
99.2
6.09
103.0
109.0
6.22
104.0
118.0
6.36
106.0

Air Temperature Entering Condenser (F)
85
95
100
105
71.7
67.0
64.6
62.1
6.14
6.84
7.21
7.58
104.0
114.0
118.0
123.0
79.7
74.9
72.4
69.9
6.21
6.90
7.28
7.65
104.0
114.0
119.0
124.0
88.0
83.0
80.4
77.8
6.31
7.02
7.40
7.78
106.0
115.0
120.0
125.0
96.7
91.4
88.7
85.9
6.43
7.14
7.53
7.92
107.0
117.0
122.0
126.0
106.0
100.0
97.4
94.5
6.56
7.28
7.68
8.07
109.0
119.0
123.0
128.0
116.0
110.0
107.0
104.0
6.70
7.43
7.83
8.23
111.0
120.0
125.0
130.0

115
57.0
8.36
133.0
64.7
8.46
134.0
72.4
8.59
135.0
80.3
8.74
136.0
88.6
8.91
138.0
97.2
9.09
139.0

80
102.0
8.04
101.0
112.0
8.26
103.0
122.0
8.52
104.0
133.0
8.81
106.0
144.0
9.12
108.0
156.0
9.45
109.0

Air Temperature Entering Condenser (F)
85
95
100
105
99.3
93.8
90.9
88.1
8.38
9.13
9.55
9.95
106.0
116.0
121.0
126.0
109.0
103.0
99.8
96.7
8.60
9.31
9.65
10.05
107.0
117.0
12.02
127.0
119.0
113.0
109.0
106.0
8.85
9.55
9.95
10.35
109.0
118.0
123.0
128.0
130.0
123.0
119.0
115.0
9.15
9.85
10.25
10.55
110.0
120.0
125.0
129.0
141.0
133.0
130.0
126.0
9.45
10.15
10.55
10.85
112.0
122.0
126.0
131.0
152.0
145.0
141.0
137.0
9.85
10.55
10.85
11.25
114.0
123.0
128.0
133.0

SST (F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

25

30

35

40

45

50

569D090
SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

SST (F)

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)
85
95
100
105
85.1
77.4
73.6
69.7
7.79
8.29
8.49
8.70
108.0
118.0
123.0
128.0
96.6
88.5
84.4
80.3
8.07
8.64
8.89
9.14
108.0
118.0
123.0
128.0
109.0
100.0
95.8
91.5
8.36
8.99
9.28
9.55
109.0
119.0
124.0
128.0
121.0
112.0
107.0
103.0
8.66
9.35
9.65
9.95
111.0
120.0
125.0
129.0
133.0
124.0
119.0
115.0
8.97
9.75
10.05
10.50
113.0
122.0
127.0
131.0
147.0
137.0
132.0
127.0
9.28
10.15
10.45
10.90
115.0
124.0
129.0
133.0

115
62.2
9.02
138.0
72.2
9.55
138.0
83.0
10.05
138.0
94.1
10.55
139.0
106.0
11.05
140.0
117.0
11.55
142.0

80
90.5
7.75
100.0
100.0
7.79
101.0
111.0
7.89
102.0
122.0
8.01
104.0
133.0
8.15
105.0
145.0
8.30
107.0

Air Temperature Entering Condenser (F)
85
95
100
105
87.9
82.6
79.8
76.9
8.17
9.05
9.52
10.00
105.0
115.0
120.0
125.0
97.8
92.2
89.3
86.3
8.21
9.09
9.57
10.10
106.0
116.0
120.0
125.0
108.0
102.0
99.0
96.0
8.30
9.18
9.66
10.10
107.0
116.0
121.0
126.0
119.0
112.0
109.0
106.0
8.42
9.31
9.79
10.30
108.0
118.0
123.0
127.0
130.0
123.0
120.0
116.0
8.57
9.46
9.95
10.40
110.0
120.0
124.0
129.0
141.0
134.0
131.0
127.0
8.72
9.63
10.10
10.60
112.0
121.0
126.0
131.0

115
71.1
11.00
135.0
80.2
11.10
135.0
89.7
11.20
136.0
99.4
11.30
137.0
109.0
11.50
138.0
120.0
11.70
140.0

569F120

569D120
SST (F)

80
89.0
7.52
103.0
101.0
7.76
104.0
113.0
8.01
105.0
125.0
8.29
106.0
138.0
8.57
108.0
152.0
8.85
111.0

115
81.9
10.85
136.0
90.3
10.95
136.0
99.0
11.15
137.0
108.0
11.35
139.0
118.0
11.65
140.0
128.0
12.05
142.0

kW
SDT
SST
TC

15

—
—
—
—

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

50TFQ004-012
569D072-120,
576C120, 569F120

CONDENSING UNIT RATINGS

50TFQ004-012
569D072-120,
576C120, 569F120

PERFORMANCE DATA (cont)
COMBINATION RATINGS*
UNIT 569D072
569D072/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
80.7
40.8
4.71
79.3
40.3
4.99
76.7
39.3
5.53
75.2
38.8
5.84
73.8
38.2
6.15
70.9
37.2
6.77

Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
72.0
72.6
77.7
84.1
72.0
70.5
58.6
45.5
4.55
4.57
4.66
4.78
71.0
71.4
76.3
82.6
71.0
69.8
58.1
45.0
4.83
4.84
4.93
5.05
68.9
69.1
73.6
79.7
68.9
68.3
57.0
44.0
5.37
5.38
5.47
5.60
67.7
67.9
72.2
78.2
67.7
67.4
56.5
43.5
5.68
5.68
5.78
5.90
66.6
66.7
70.7
76.6
66.6
66.6
55.9
42.9
5.99
5.99
6.08
6.21
64.4
64.3
67.8
73.5
64.4
64.3
54.8
41.9
6.61
6.61
6.70
6.83

72
77.8
39.2
4.66
76.6
38.8
4.93
74.1
37.9
5.48
72.8
37.4
5.79
71.4
36.9
6.10
68.7
35.9
6.72

Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
69.0
69.8
74.9
81.1
69.0
67.2
56.0
43.6
4.50
4.52
4.60
4.72
68.0
68.7
73.6
79.7
68.0
66.6
55.5
43.1
4.77
4.79
4.88
4.99
66.1
66.5
71.1
77.0
66.1
65.2
54.6
42.2
5.32
5.33
5.42
5.54
65.1
65.4
69.8
75.6
65.1
64.4
54.0
41.7
5.63
5.63
5.73
5.85
64.0
64.2
68.5
74.1
64.0
63.7
53.5
41.2
5.94
5.94
6.03
6.16
61.9
61.9
65.8
71.3
61.9
61.9
52.4
40.2
6.57
6.56
6.65
6.78

1800
57
66.0
66.0
4.45
65.1
65.1
4.72
63.3
63.3
5.26
62.3
62.3
5.57
61.3
61.3
5.88
59.3
59.3
6.51

62
68.6
60.9
4.49
67.5
60.3
4.76
65.2
59.2
5.30
64.0
58.6
5.61
62.8
58.0
5.91
60.5
56.8
6.53

67
74.3
51.0
4.60
73.1
50.5
4.87
70.6
49.4
5.41
69.2
48.9
5.71
67.9
48.3
6.02
65.2
47.2
6.63

3000
57
76.2
76.2
4.63
75.0
75.0
4.91
72.8
72.8
5.45
71.5
71.5
5.76
70.3
70.3
6.07
67.9
67.9
6.69

62
76.2
76.2
4.63
75.1
75.1
4.90
72.8
72.8
5.45
71.5
71.5
5.76
70.3
70.3
6.08
67.9
67.9
6.70

67
79.9
65.7
4.70
78.5
65.2
4.97
75.7
64.0
5.51
74.2
63.4
5.82
72.7
62.8
6.12
69.7
61.6
6.74

72
86.2
50.0
4.82
84.6
49.5
5.09
81.6
48.5
5.64
80.0
47.9
5.95
78.4
47.4
6.26
75.2
46.4
6.88

67
76.9
62.5
4.64
75.6
62.0
4.91
73.1
60.9
5.46
71.7
60.4
5.76
70.3
59.8
6.07
67.4
58.7
6.68

72
83.1
47.6
4.76
81.7
47.2
5.03
78.9
46.2
5.58
77.4
45.7
5.89
75.9
45.2
6.20
72.9
44.2
6.82

569D072/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57
63.4
63.4
4.40
62.5
62.5
4.67
60.8
60.8
5.22
59.9
59.9
5.53
59.0
59.0
5.84
57.1
57.1
6.46

62
66.1
58.4
4.45
65.1
57.9
4.72
62.9
56.8
5.26
61.8
56.3
5.56
60.7
55.7
5.87
58.4
54.6
6.48

67
71.7
49.0
4.55
70.5
48.5
4.82
68.2
47.5
5.36
67.0
47.0
5.67
65.7
46.5
5.98
63.3
45.5
6.59

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

*Combinations on this page are ENERGY STAR® compliant.

16

3000
57
72.9
72.9
4.57
71.9
71.9
4.84
69.7
69.7
5.39
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.64

62
72.9
72.9
4.57
71.9
71.9
4.84
69.8
69.8
5.39
68.6
68.6
5.70
67.5
67.5
6.01
65.2
65.2
6.63

PERFORMANCE DATA (cont)
UNIT 569D072 (cont)
569D072/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
84.8
45.1
4.79
83.3
44.6
5.07
80.4
43.5
5.61
78.8
43.0
5.92
77.3
42.5
6.23
74.2
41.4
6.85

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
77.7
77.7
81.3
87.6
77.7
77.7
67.0
50.9
4.66
4.66
4.73
4.85
76.5
76.5
79.8
86.1
76.5
76.5
66.4
50.3
4.93
4.93
5.00
5.12
74.1
74.1
76.9
82.9
74.1
74.1
65.2
49.3
5.48
5.48
5.54
5.66
72.8
72.9
75.4
81.3
72.8
72.9
64.6
48.8
5.79
5.79
5.85
5.97
71.6
71.6
73.9
79.6
71.6
71.6
64.0
48.2
6.10
6.10
6.15
6.28
69.0
69.1
70.8
76.2
69.0
69.1
62.8
47.1
6.73
6.73
6.77
6.90

72
81.0
42.9
4.72
79.7
42.4
5.00
77.1
41.5
5.54
75.6
41.0
5.85
74.1
40.5
6.16
71.2
39.4
6.78

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
73.6
73.6
77.6
83.8
73.6
73.6
63.1
48.1
4.58
4.58
4.65
4.77
72.6
72.6
76.3
82.4
72.6
72.6
62.6
47.6
4.86
4.86
4.93
5.05
70.4
70.5
73.7
79.5
70.4
70.5
61.5
46.6
5.40
5.40
5.47
5.59
69.3
69.3
72.3
78.0
69.3
69.3
60.9
46.1
5.71
5.72
5.78
5.90
68.1
68.1
70.9
76.5
68.1
68.1
60.4
45.6
6.03
6.03
6.08
6.21
65.9
65.8
68.0
73.4
65.9
65.8
59.2
44.6
6.65
6.65
6.70
6.83

2400
57
71.9
71.9
4.55
70.9
70.9
4.83
68.8
68.8
5.37
67.7
67.7
5.68
66.5
66.5
5.99
64.3
64.3
6.61

62
72.9
69.5
4.57
71.7
68.8
4.84
69.3
67.5
5.38
68.0
66.8
5.69
66.8
66.0
6.00
64.3
64.3
6.61

67
78.3
57.7
4.67
76.9
57.2
4.94
74.2
56.1
5.48
72.8
55.5
5.79
71.3
54.9
6.09
68.4
53.8
6.71

3750
57
81.6
81.6
4.73
80.3
80.3
5.01
77.7
77.7
5.55
76.4
76.4
5.87
75.0
75.0
6.18
72.3
72.3
6.81

62
81.6
81.6
4.73
80.3
80.3
5.01
77.8
77.8
5.56
76.4
76.4
5.87
75.0
75.0
6.18
72.3
72.3
6.8

67
83.4
75.2
4.77
81.9
74.6
5.04
79.0
73.3
5.58
77.4
72.5
5.89
75.9
71.8
6.20
72.7
70.3
6.81

72
89.4
56.4
4.89
87.8
55.9
5.16
84.5
54.8
5.70
82.8
54.3
6.01
81.1
53.7
6.32
77.7
52.6
6.94

67
79.5
70.4
4.69
78.2
69.8
4.96
75.5
68.7
5.51
74.0
68.0
5.82
72.6
67.3
6.12
69.7
66.0
6.74

72
85.5
52.9
4.81
84.0
52.4
5.08
81.1
51.4
5.62
79.5
50.9
5.93
77.9
50.4
6.24
74.8
49.4
6.86

569D072/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2400
57
68.4
68.4
4.49
67.4
67.4
4.76
65.5
65.5
5.31
64.5
64.5
5.62
63.4
63.4
5.93
61.4
61.4
6.55

62
69.5
65.8
4.51
68.4
65.2
4.78
66.2
64.0
5.32
65.1
63.3
5.63
63.9
62.5
5.94
61.6
61.1
6.55

67
74.8
54.8
4.61
73.6
54.3
4.88
71.1
53.3
5.42
69.7
52.8
5.72
68.4
52.2
6.03
65.8
51.2
6.64

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

*This combination is ENERGY STAR® compliant.

17

3750
57
77.3
77.3
4.65
76.1
76.1
4.92
73.8
73.8
5.47
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.72

62
77.3
77.3
4.65
76.1
76.1
4.92
73.8
73.8
5.47
72.6
72.6
5.78
71.4
71.4
6.10
68.9
68.9
6.73

50TFQ004-012
569D072-120,
576C120, 569F120

COMBINATION RATINGS (cont)

50TFQ004-012
569D072-120,
576C120, 569F120

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D090
569D090/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57
78.9
77.9
5.75
77.6
77.0
6.10
75.1
75.1
6.80
73.9
73.8
7.20
72.6
72.6
7.59
70.1
70.1
8.38

62
85.1
69.0
5.78
83.6
68.3
6.13
80.8
66.8
6.82
79.2
66.0
7.21
77.6
65.3
7.60
74.5
63.7
8.38

67
92.8
59.0
5.85
91.3
58.3
6.20
88.3
56.9
6.90
86.6
56.2
7.29
85.0
55.5
7.68
81.7
54.0
8.47

72
101.0
48.7
5.94
99.3
48.0
6.30
96.1
46.7
7.00
94.4
46.1
7.40
92.6
45.4
7.79
89.1
44.0
8.58

Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
87.0
90.7
98.3
106.0
87.0
79.9
66.9
53.6
5.79
5.83
5.91
6.01
85.7
89.2
96.6
105.0
85.7
79.1
66.3
52.9
6.14
6.18
6.26
6.37
83.2
86.1
93.3
101.0
83.2
77.6
64.9
51.6
6.85
6.87
6.96
7.08
81.8
84.4
91.4
99.2
81.8
76.7
64.1
50.9
7.24
7.26
7.36
7.47
80.4
82.7
89.6
97.3
80.4
75.9
63.4
50.2
7.64
7.66
7.75
7.87
77.7
79.4
86.0
93.5
77.7
74.3
61.9
48.8
8.43
8.44
8.53
8.66

3000
57
93.0
93.0
5.85
91.6
91.6
6.20
88.9
88.9
6.91
87.4
87.4
7.30
85.9
85.9
7.70
82.9
82.9
8.48

62
94.7
89.3
5.87
93.1
88.4
6.22
89.9
86.7
6.92
88.2
85.7
7.31
86.5
84.7
7.71
83.1
82.7
8.49

67
102.0
74.2
5.96
100.0
73.5
6.31
96.5
72.2
7.01
94.5
71.4
7.40
92.6
70.7
7.80
88.8
69.2
8.58

72
110.0
58.0
6.06
108.0
57.4
6.41
104.0
56.1
7.12
102.0
55.3
7.52
100.0
54.6
7.92
96.2
53.2
8.71

67
96.8
70.0
6.01
95.2
69.4
6.38
91.9
68.1
7.10
90.0
67.4
7.51
88.2
66.7
7.91
84.6
65.3
8.71

72
104.0
54.9
6.12
103.0
54.3
6.48
99.2
53.0
7.22
97.3
52.3
7.63
95.4
51.7
8.04
91.7
50.3
8.86

569D090/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57
75.3
74.3
5.77
74.2
73.4
6.12
71.8
71.6
6.83
70.6
70.5
7.22
69.4
69.4
7.61
67.0
67.0
8.39

62
81.2
65.8
5.82
79.8
65.2
6.18
77.2
63.8
6.89
75.7
63.1
7.28
74.2
62.4
7.67
71.3
60.9
8.45

67
88.5
56.3
5.91
87.1
55.6
6.27
84.2
54.3
6.98
82.6
53.6
7.38
81.1
53.0
7.78
78.0
51.6
8.59

72
96.1
46.4
6.00
94.6
45.8
6.37
91.6
44.6
7.10
89.9
43.9
7.50
88.3
43.3
7.91
85.0
41.9
8.73

Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
82.5
86.4
93.6
101.0
82.5
75.7
63.5
50.9
5.84
5.88
5.97
6.07
81.3
84.9
92.0
99.5
81.3
75.0
62.8
50.2
6.20
6.24
6.33
6.44
79.0
82.0
88.8
96.2
79.0
73.6
61.5
49.0
6.91
6.95
7.05
7.17
77.7
80.4
87.1
94.4
77.7
72.8
60.8
48.3
7.31
7.35
7.45
7.58
76.4
78.8
85.4
92.6
76.4
72.0
60.1
47.7
7.70
7.75
7.86
7.99
73.8
75.6
82.0
89.0
73.8
70.5
58.7
46.4
8.49
8.54
8.66
8.80

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

*This combination is ENERGY STAR® compliant.

18

3000
57
88.0
88.0
5.90
86.7
86.7
6.26
84.1
84.1
6.99
82.7
82.7
7.39
81.3
81.3
7.79
78.5
78.5
8.59

62
89.9
84.1
5.93
88.4
83.3
6.28
85.4
81.7
7.00
83.8
80.7
7.40
82.2
79.8
7.80
78.9
77.9
8.60

PERFORMANCE DATA (cont)
UNIT 569D090 (cont)
569D090/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2205
57
86.0
86.0
5.78
84.8
84.8
6.14
82.3
82.3
6.85
81.0
81.0
7.24
79.6
79.6
7.63
77.0
77.0
8.41

62
90.4
78.0
5.83
88.9
77.3
6.18
85.8
75.8
6.88
84.2
75.0
7.26
82.5
74.1
7.65
79.2
72.5
8.42

67
98.0
65.6
5.91
96.4
64.9
6.26
93.1
63.5
6.96
91.3
62.8
7.36
89.6
62.1
7.75
86.0
60.6
8.53

72
106.0
52.8
6.01
104.0
52.2
6.37
101.0
50.9
7.07
99.1
50.2
7.47
97.2
49.5
7.87
93.5
48.1
8.66

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
94.1
95.7
103.0
111.0
94.1
90.3
75.0
58.5
5.86
5.88
5.97
6.07
92.7
94.1
101.0
109.0
92.7
89.4
74.2
57.8
6.22
6.23
6.32
6.42
90.0
90.9
97.3
105.0
90.0
87.7
72.8
56.5
6.92
6.93
7.02
7.13
88.5
89.2
95.4
103.0
88.5
86.7
72.1
55.8
7.32
7.33
7.41
7.53
87.0
87.5
93.5
101.0
87.0
85.7
71.4
55.2
7.71
7.72
7.81
7.93
83.9
84.1
89.8
97.2
83.9
83.7
69.9
53.8
8.50
8.50
8.60
8.73

3750
57
96.9
96.9
5.90
95.4
95.4
6.25
92.6
92.6
6.96
91.0
91.0
7.35
89.5
89.5
7.75
86.3
86.3
8.54

62
97.8
94.8
5.91
96.2
93.7
6.26
93.1
91.4
6.96
91.4
90.1
7.36
89.7
88.8
7.75
86.4
86.2
8.54

67
104.0
79.3
5.98
102.0
78.5
6.34
98.7
77.1
7.04
96.8
76.4
7.43
94.9
75.6
7.83
91.0
74.1
8.62

72
112.0
61.1
6.09
110.0
60.5
6.44
106.0
59.2
7.15
104.0
58.5
7.55
102.0
57.8
7.95
98.3
56.4
8.75

67
98.8
74.7
6.04
97.1
74.1
6.40
93.8
72.8
7.13
91.9
72.1
7.54
90.1
71.4
7.94
86.4
70.0
8.75

72
106.0
57.7
6.14
105.0
57.1
6.51
101.0
55.9
7.25
99.1
55.2
7.66
97.2
54.6
8.07
93.3
53.2
8.89

569D090/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

2205
57
81.7
81.7
5.83
80.6
80.6
6.19
78.3
78.3
6.90
77.0
77.0
7.30
75.7
75.7
7.69
73.2
73.2
8.48

62
85.9
74.2
5.88
84.5
73.5
6.23
81.7
72.1
6.95
80.1
71.3
7.34
78.6
70.6
7.74
75.4
69.0
8.53

67
93.2
62.4
5.97
91.6
61.7
6.33
88.5
60.4
7.05
86.9
59.8
7.45
85.2
59.1
7.86
81.9
57.7
8.67

72
101.0
50.2
6.07
99.2
49.6
6.43
95.9
48.4
7.17
94.2
47.7
7.57
92.4
47.0
7.98
88.8
45.7
8.79

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
89.0
90.8
97.5
105.0
89.0
85.2
70.9
55.4
5.92
5.94
6.02
6.12
87.7
89.3
95.8
103.0
87.7
84.5
70.2
54.8
6.28
6.30
6.39
6.49
85.2
86.3
92.5
99.9
85.2
82.9
69.0
53.6
7.00
7.02
7.11
7.23
83.7
84.7
90.7
98.0
83.7
81.9
68.3
52.9
7.40
7.42
7.52
7.64
82.3
83.0
88.9
96.1
82.3
80.9
67.6
52.2
7.80
7.82
7.92
8.05
79.5
79.8
85.3
92.3
79.5
79.0
66.1
50.9
8.61
8.61
8.73
8.87

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

*This combination is ENERGY STAR® compliant.

19

3750
57
91.6
91.6
5.95
90.2
90.2
6.31
87.6
87.6
7.04
86.1
86.1
7.44
84.6
84.6
7.84
81.7
81.7
8.65

62
92.6
89.4
5.96
91.1
88.4
6.32
88.2
86.4
7.05
86.6
85.2
7.45
85.0
83.9
7.85
81.8
81.4
8.65

50TFQ004-012
569D072-120,
576C120, 569F120

COMBINATION RATINGS (cont)

50TFQ004-012
569D072-120,
576C120, 569F120

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D120
569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
117.0
117.0
8.34
115.0
115.0
8.72
112.0
112.0
9.49
110.0
110.0
9.90
108.0
108.0
10.30
104.0
104.0
11.10

62
122.0
106.0
8.48
120.0
104.0
8.85
116.0
102.0
9.60
113.0
101.0
10.00
111.0
100.0
10.40
106.0
97.7
11.20

67
132.0
88.4
8.74
129.0
87.5
9.11
125.0
85.5
9.86
122.0
84.4
10.30
120.0
83.3
10.70
114.0
81.2
11.50

72
142.0
70.9
9.02
140.0
70.0
9.40
135.0
68.2
10.20
132.0
67.1
10.60
129.0
66.1
11.00
124.0
64.0
11.70

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
127.0
129.0
138.0
148.0
127.0
122.0
101.0
78.6
8.61
8.66
8.89
9.18
125.0
127.0
135.0
145.0
125.0
121.0
100.0
77.6
8.99
9.04
9.27
9.56
121.0
122.0
130.0
140.0
121.0
119.0
98.2
75.8
9.76
9.79
10.00
10.30
119.0
120.0
127.0
137.0
119.0
117.0
97.1
74.8
10.20
10.20
10.40
10.70
117.0
117.0
125.0
134.0
117.0
116.0
96.0
73.7
10.60
10.60
10.80
11.10
112.0
112.0
119.0
128.0
112.0
112.0
93.8
71.7
11.40
11.40
11.60
11.90

5000
57
134.0
134.0
8.81
132.0
132.0
9.19
128.0
128.0
9.96
125.0
125.0
10.40
123.0
123.0
10.80
118.0
118.0
11.60

62
134.0
134.0
8.80
132.0
132.0
9.19
128.0
128.0
9.95
125.0
125.0
10.40
123.0
123.0
10.80
118.0
118.0
11.60

67
141.0
113.0
9.00
139.0
112.0
9.38
134.0
110.0
10.10
131.0
109.0
10.50
128.0
108.0
10.90
122.0
105.0
11.70

72
151.0
85.9
9.28
148.0
84.9
9.67
143.0
83.1
10.40
140.0
82.1
10.80
137.0
81.0
11.20
131.0
78.9
12.00

67
133.0
105.0
8.80
131.0
104.0
9.17
126.0
102.0
9.93
124.0
101.0
10.30
121.0
100.0
10.70
116.0
97.9
11.50

72
143.0
79.9
9.06
140.0
79.0
9.44
135.0
77.3
10.20
132.0
76.4
10.60
130.0
75.5
11.00
124.0
73.6
11.80

569D120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
110.0
110.0
8.19
108.0
108.0
8.57
105.0
105.0
9.34
104.0
104.0
9.76
102.0
102.0
10.20
98.4
98.4
11.00

62
115.0
99.4
8.32
113.0
98.4
8.70
110.0
96.6
9.45
107.0
95.5
9.86
105.0
94.4
10.30
101.0
92.2
11.10

67
124.0
83.3
8.55
122.0
82.4
8.93
118.0
80.7
9.69
116.0
79.7
10.10
114.0
78.7
10.5
109.0
76.7
11.30

72
134.0
66.8
8.82
132.0
66.0
9.20
127.0
64.3
9.96
125.0
63.4
10.40
122.0
62.4
10.80
117.0
60.5
11.60

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
119.0
121.0
130.0
139.0
119.0
114.0
94.6
73.6
8.41
8.48
8.70
8.96
117.0
119.0
128.0
137.0
117.0
113.0
93.7
72.8
8.80
8.85
9.08
9.35
114.0
115.0
123.0
132.0
114.0
111.0
91.9
71.1
9.57
9.61
9.83
10.10
112.0
113.0
121.0
130.0
112.0
109.0
90.9
70.2
9.98
10.00
10.20
10.50
110.0
111.0
118.0
127.0
110.0
108.0
89.9
69.2
10.40
10.40
10.60
10.90
106.0
106.0
113.0
122.0
106.0
105.0
87.8
67.3
11.20
11.20
11.40
11.70

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

20

5000
57
126.0
126.0
8.59
124.0
124.0
8.97
120.0
120.0
9.73
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40

62
126.0
125.0
8.60
124.0
123.0
8.98
120.0
120.0
9.74
118.0
118.0
10.10
116.0
116.0
10.60
111.0
111.0
11.40

PERFORMANCE DATA (cont)
UNIT 569D120 (cont)
569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
126.0
126.0
8.60
124.0
124.0
8.98
120.0
120.0
9.74
118.0
118.0
10.20
116.0
116.0
10.60
112.0
112.0
11.40

62
129.0
119.0
8.68
127.0
118.0
9.05
122.0
116.0
9.80
120.0
114.0
10.20
117.0
113.0
10.60
112.0
110.0
11.40

67
138.0
98.7
8.94
136.0
97.7
9.31
131.0
95.7
10.10
128.0
94.6
10.50
126.0
93.5
10.90
120.0
91.4
11.70

72
149.0
77.4
9.23
146.0
76.5
9.61
141.0
74.6
10.40
138.0
73.6
10.80
135.0
72.6
11.20
129.0
70.5
12.00

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
136.0
136.0
143.0
153.0
136.0
135.0
114.0
86.5
8.87
8.87
9.08
9.37
134.0
134.0
141.0
151.0
134.0
133.0
113.0
85.6
9.25
9.25
9.46
9.76
129.0
129.0
136.0
145.0
129.0
129.0
111.0
83.8
10.00
10.00
10.20
10.50
127.0
127.0
133.0
142.0
127.0
127.0
109.0
82.7
10.40
10.40
10.60
10.90
125.0
125.0
130.0
139.0
125.0
125.0
108.0
81.6
10.80
10.80
11.00
11.30
120.0
120.0
124.0
133.0
120.0
120.0
106.0
79.5
11.60
11.70
11.80
12.10

6250
57
142.0
142.0
9.06
140.0
140.0
9.44
136.0
136.0
10.20
133.0
133.0
10.60
130.0
130.0
11.00
125.0
125.0
11.80

62
142.0
142.0
9.05
140.0
140.0
9.44
136.0
136.0
10.20
133.0
133.0
10.60
130.0
130.0
11.00
125.0
125.0
11.80

67
147.0
127.0
9.18
144.0
126.0
9.56
139.0
124.0
10.30
136.0
123.0
10.70
133.0
121.0
11.10
127.0
119.0
11.90

72
156.0
95.0
9.46
154.0
94.1
9.84
148.0
92.3
10.60
145.0
91.2
11.00
142.0
90.1
11.40
135.0
87.9
12.20

67
140.0
118.0
8.99
138.0
117.0
9.37
133.0
115.0
10.10
130.0
114.0
10.50
127.0
113.0
10.90
121.0
110.0
11.70

72
150.0
88.6
9.27
147.0
87.8
9.65
142.0
86.0
10.40
139.0
85.0
10.80
136.0
84.0
11.20
130.0
81.9
12.00

569D120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
119.0
119.0
8.42
118.0
118.0
8.80
114.0
114.0
9.57
112.0
112.0
9.98
110.0
110.0
10.40
106.0
106.0
11.20

62
123.0
112.0
8.51
121.0
111.0
8.89
116.0
109.0
9.64
114.0
108.0
10.00
112.0
106.0
10.40
107.0
104.0
11.20

67
132.0
93.2
8.77
130.0
92.3
9.14
125.0
90.4
9.89
123.0
89.3
10.30
120.0
88.2
10.70
115.0
86.1
11.50

72
142.0
73.4
9.05
140.0
72.5
9.43
135.0
70.7
10.20
132.0
69.7
10.60
129.0
68.7
11.00
124.0
66.6
11.80

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
128.0
129.0
137.0
147.0
128.0
127.0
106.0
81.4
8.66
8.68
8.90
9.18
126.0
127.0
135.0
144.0
126.0
126.0
105.0
80.5
9.05
9.06
9.28
9.56
122.0
123.0
130.0
139.0
122.0
122.0
103.0
78.7
9.81
9.81
10.00
10.30
120.0
120.0
127.0
136.0
120.0
120.0
102.0
77.7
10.20
10.20
10.40
10.70
118.0
118.0
124.0
133.0
118.0
118.0
101.0
76.7
10.60
10.60
10.80
11.10
114.0
113.0
119.0
127.0
114.0
113.0
99.1
74.6
11.40
11.40
11.60
11.90

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

21

6250
57
135.0
135.0
8.84
133.0
133.0
9.22
128.0
128.0
9.99
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60

62
135.0
135.0
8.84
133.0
133.0
9.22
128.0
128.0
9.99
126.0
126.0
10.40
123.0
123.0
10.80
119.0
119.0
11.60

50TFQ004-012
569D072-120,
576C120, 569F120

COMBINATION RATINGS (cont)

50TFQ004-012
569D072-120,
576C120, 569F120

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 576C120
576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
113.0
113.0
8.00
111.0
111.0
8.39
106.0
106.0
9.17
104.0
104.0
9.55
102.0
102.0
9.93
97.2
97.2
10.70

62
118.0
104.0
8.12
115.0
102.0
8.51
110.0
99.8
9.28
107.0
98.4
9.65
104.0
97.0
10.00
98.6
94.2
10.80

67
129.0
87.4
8.35
126.0
86.1
8.76
120.0
83.7
9.58
117.0
82.4
9.98
114.0
81.1
10.40
107.0
78.6
11.20

72
141.0
70.5
8.61
137.0
69.3
9.05
131.0
66.9
9.93
128.0
65.7
10.40
124.0
64.5
10.80
118.0
62.1
11.60

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
124.0
126.0
135.0
147.0
124.0
121.0
101.0
78.8
8.26
8.29
8.49
8.75
122.0
123.0
132.0
144.0
122.0
119.0
99.5
77.6
8.67
8.69
8.91
9.20
117.0
117.0
125.0
137.0
117.0
116.0
96.9
75.1
9.49
9.51
9.76
10.10
114.0
114.0
122.0
133.0
114.0
114.0
95.6
73.9
9.90
9.90
10.20
10.50
112.0
112.0
119.0
130.0
112.0
112.0
94.3
72.7
10.30
10.30
10.60
11.00
106.0
106.0
112.0
122.0
106.0
106.0
91.7
70.2
11.10
11.10
11.40
11.80

5000
57
132.0
132.0
8.43
129.0
129.0
8.86
124.0
124.0
9.72
121.0
121.0
10.10
118.0
118.0
10.60
113.0
113.0
11.40

62
132.0
132.0
8.43
129.0
129.0
8.86
124.0
124.0
9.72
121.0
121.0
10.10
118.0
118.0
10.60
113.0
113.0
11.40

67
139.0
113.0
8.58
136.0
112.0
9.01
129.0
109.0
9.88
126.0
108.0
10.30
122.0
106.0
10.70
116.0
104.0
11.50

72
151.0
86.6
8.82
148.0
85.4
9.28
140.0
82.9
10.20
137.0
81.7
10.60
133.0
80.5
11.10
125.0
78.0
12.00

67
133.0
107.0
8.46
129.0
105.0
8.88
123.0
103.0
9.72
120.0
102.0
10.10
117.0
100.0
10.50
110.0
97.7
11.30

72
144.0
81.8
8.71
141.0
80.6
9.15
134.0
78.4
10.00
131.0
77.3
10.50
127.0
76.1
10.90
120.0
73.9
11.80

576C120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
107.0
107.0
7.91
105.0
105.0
8.29
101.0
101.0
9.04
98.9
98.9
9.41
96.8
96.8
9.78
92.5
92.5
10.50

62
112.0
98.8
8.03
110.0
97.5
8.40
105.0
95.0
9.15
102.0
93.7
9.51
99.4
92.3
9.87
94.1
89.7
10.60

67
123.0
83.3
8.25
120.0
82.2
8.65
114.0
79.8
9.44
111.0
78.7
9.83
108.0
77.5
10.0
103.0
75.1
11.00

72
134.0
67.2
8.49
131.0
66.1
8.92
125.0
63.9
9.78
122.0
62.8
10.20
119.0
61.6
10.60
113.0
59.4
11.40

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
118.0
119.0
129.0
140.0
118.0
114.0
95.5
74.8
8.14
8.18
8.38
8.62
115.0
117.0
126.0
137.0
115.0
113.0
94.3
73.7
8.54
8.57
8.79
9.06
111.0
111.0
120.0
131.0
111.0
109.0
92.0
71.4
9.34
9.36
9.61
9.94
108.0
109.0
117.0
127.0
108.0
108.0
90.8
70.3
9.73
9.74
10.00
10.40
106.0
106.0
113.0
124.0
106.0
106.0
89.5
69.2
10.10
10.10
10.40
10.80
101.0
101.0
107.0
117.0
101.0
101.0
87.1
67.0
10.90
10.90
11.20
11.60

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

22

5000
57
125.0
125.0
8.30
122.0
122.0
8.71
117.0
117.0
9.54
115.0
115.0
9.94
112.0
112.0
10.30
107.0
107.0
11.20

62
125.0
125.0
8.30
122.0
122.0
8.71
117.0
117.0
9.54
115.0
115.0
9.95
112.0
112.0
10.30
107.0
107.0
11.20

PERFORMANCE DATA (cont)
UNIT 576C120 (cont)
576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
122.0
122.0
8.23
120.0
120.0
8.64
115.0
115.0
9.46
113.0
113.0
9.86
110.0
110.0
10.30
105.0
105.0
11.10

62
125.0
117.0
8.28
122.0
116.0
8.69
116.0
113.0
9.50
113.0
111.0
9.89
111.0
109.0
10.30
105.0
105.0
11.10

67
135.0
97.7
8.51
132.0
96.5
8.94
126.0
93.9
9.78
123.0
92.6
10.20
119.0
91.4
10.60
113.0
88.8
11.40

72
147.0
77.1
8.77
144.0
76.0
9.22
137.0
73.6
10.10
134.0
72.4
10.60
130.0
71.1
11.00
123.0
68.7
11.90

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
133.0
133.0
141.0
153.0
133.0
133.0
113.0
86.9
8.47
8.47
8.64
8.88
130.0
130.0
138.0
149.0
130.0
130.0
112.0
85.6
8.90
8.90
9.07
9.35
125.0
125.0
131.0
142.0
125.0
125.0
109.0
83.2
9.76
9.76
9.95
10.30
122.0
122.0
128.0
139.0
122.0
122.0
108.0
82.0
10.20
10.20
10.40
10.70
119.0
119.0
124.0
135.0
119.0
119.0
107.0
80.8
10.60
10.60
10.80
11.20
114.0
114.0
117.0
127.0
114.0
114.0
104.0
78.4
11.50
11.50
11.60
12.10

6250
57
141.0
141.0
8.62
138.0
138.0
9.07
132.0
132.0
9.97
129.0
129.0
10.40
126.0
126.0
10.80
120.0
120.0
11.70

62
141.0
141.0
8.62
138.0
138.0
9.07
132.0
132.0
9.97
129.0
129.0
10.40
126.0
126.0
10.80
120.0
120.0
11.70

67
145.0
127.0
8.72
142.0
126.0
9.16
135.0
123.0
10.10
131.0
121.0
10.50
128.0
120.0
10.90
121.0
117.0
11.80

72
157.0
96.0
8.95
153.0
94.7
9.42
145.0
92.3
10.40
141.0
91.1
10.80
138.0
89.9
11.30
130.0
87.4
12.20

67
138.0
119.0
8.57
134.0
117.0
8.99
128.0
114.0
9.85
124.0
113.0
10.30
121.0
111.0
10.70
114.0
108.0
11.50

72
149.0
89.6
8.81
146.0
88.5
9.26
139.0
86.1
10.20
135.0
84.9
10.60
131.0
83.8
11.00
124.0
81.4
11.90

576C120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
115.0
115.0
8.08
113.0
113.0
8.47
109.0
109.0
9.25
106.0
106.0
9.64
104.0
104.0
10.00
99.2
99.2
10.80

62
118.0
110.0
8.14
116.0
109.0
8.53
110.0
106.0
9.31
108.0
104.0
9.68
105.0
103.0
10.10
99.3
99.3
10.80

67
129.0
92.3
8.37
126.0
91.1
8.78
120.0
88.7
9.60
116.0
87.5
9.99
113.0
86.2
10.40
107.0
83.7
11.20

72
140.0
73.1
8.62
137.0
71.9
9.06
131.0
69.6
9.94
127.0
68.5
10.40
124.0
67.3
10.80
117.0
64.9
11.60

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
125.0
126.0
134.0
146.0
125.0
125.0
106.0
81.7
8.30
8.30
8.48
8.74
123.0
123.0
131.0
142.0
123.0
123.0
105.0
80.5
8.71
8.72
8.91
9.18
118.0
118.0
124.0
136.0
118.0
118.0
102.0
78.2
9.54
9.54
9.75
10.10
115.0
115.0
121.0
132.0
115.0
115.0
101.0
77.0
9.95
9.95
10.10
10.50
112.0
113.0
118.0
129.0
112.0
113.0
99.7
75.8
10.40
10.40
10.60
10.90
107.0
107.0
111.0
121.0
107.0
107.0
97.1
73.5
11.20
11.20
11.40
11.80

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

23

6250
57
132.0
132.0
8.45
130.0
130.0
8.88
124.0
124.0
9.73
121.0
121.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40

62
132.0
132.0
8.45
130.0
130.0
8.88
124.0
124.0
9.74
121.0
121.0
10.20
118.0
118.0
10.60
113.0
113.0
11.40

50TFQ004-012
569D072-120,
576C120, 569F120

COMBINATION RATINGS (cont)

50TFQ004-012
569D072-120,
576C120, 569F120

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120
569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
112.0
112.0
7.90
110.0
110.0
8.35
107.0
107.0
9.24
105.0
105.0
9.74
103.0
103.0
10.20
99.7
99.7
11.20

62
116.0
102.0
7.94
114.0
102.0
8.39
110.0
99.6
9.28
108.0
98.6
9.78
106.0
97.5
10.30
102.0
95.5
11.30

67
126.0
85.9
8.06
123.0
85.0
8.51
119.0
83.2
9.40
117.0
82.3
9.91
115.0
81.3
10.40
110.0
79.5
11.40

72
136.0
68.8
8.19
134.0
67.9
8.65
130.0
66.3
9.56
127.0
65.4
10.10
125.0
64.4
10.60
120.0
62.6
11.60

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
122.0
123.0
131.0
142.0
122.0
119.0
98.8
76.7
8.01
8.03
8.13
8.27
120.0
121.0
129.0
140.0
120.0
118.0
97.9
75.8
8.46
8.47
8.58
8.72
116.0
117.0
124.0
135.0
116.0
115.0
96.1
74.1
9.36
9.37
9.48
9.63
114.0
115.0
122.0
132.0
114.0
114.0
95.1
73.2
9.87
9.87
9.98
10.10
112.0
113.0
119.0
129.0
112.0
112.0
94.1
72.3
10.40
10.40
10.50
10.70
108.0
108.0
115.0
124.0
108.0
108.0
92.2
70.5
11.40
11.40
11.50
11.70

5000
57
129.0
129.0
8.10
127.0
127.0
8.55
123.0
123.0
9.46
121.0
121.0
9.97
119.0
119.0
10.50
115.0
115.0
11.50

62
129.0
129.0
8.10
127.0
127.0
8.55
123.0
123.0
9.46
121.0
121.0
9.97
119.0
119.0
10.50
114.0
114.0
11.50

67
135.0
111.0
8.18
133.0
110.0
8.63
128.0
108.0
9.53
125.0
107.0
10.00
123.0
106.0
10.50
118.0
104.0
11.60

72
146.0
84.2
8.32
143.0
83.3
8.77
138.0
81.6
9.69
135.0
80.7
10.20
132.0
79.8
10.70
127.0
78.0
11.70

67
128.0
104.0
8.09
126.0
103.0
8.54
122.0
101.0
9.44
119.0
100.0
9.94
117.0
99.3
10.40
112.0
97.5
11.50

72
138.0
79.0
8.22
136.0
78.2
8.67
131.0
76.7
9.58
129.0
75.9
10.1
126.0
75.1
10.60
121.0
73.4
11.60

569F120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
106.0
106.0
7.83
104.0
104.0
8.28
101.0
101.0
9.18
99.7
99.7
9.67
98.1
98.1
10.20
94.9
94.9
11.20

62
110.0
97.2
7.89
108.0
96.3
8.33
105.0
94.5
9.21
103.0
93.6
9.71
101.0
92.6
10.20
97.1
90.6
11.20

67
119.0
81.5
7.98
117.0
80.7
8.43
114.0
79.1
9.33
111.0
78.3
9.83
109.0
77.4
10.30
105.0
75.7
11.30

72
130.0
65.3
8.11
127.0
64.5
8.56
123.0
63.0
9.47
121.0
62.2
9.97
119.0
61.3
10.50
114.0
59.7
11.50

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
115.0
116.0
125.0
135.0
115.0
112.0
93.2
72.4
7.94
7.95
8.05
8.17
113.0
114.0
123.0
133.0
113.0
111.0
92.3
71.7
8.38
8.40
8.49
8.63
110.0
111.0
118.0
128.0
110.0
108.0
90.7
70.2
9.28
9.29
9.39
9.54
108.0
109.0
116.0
126.0
108.0
107.0
89.8
69.3
9.78
9.79
9.90
10.00
106.0
107.0
114.0
123.0
106.0
106.0
89.0
68.5
10.30
10.30
10.40
10.60
103.0
103.0
110.0
119.0
103.0
103.0
87.3
66.8
11.30
11.30
11.40
11.60

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

24

5000
57
121.0
121.0
8.01
120.0
120.0
8.46
116.0
116.0
9.36
114.0
114.0
9.87
112.0
112.0
10.40
108.0
108.0
11.40

62
121.0
121.0
8.01
120.0
120.0
8.46
116.0
116.0
9.36
114.0
114.0
9.87
112.0
112.0
10.40
108.0
108.0
11.40

PERFORMANCE DATA (cont)
UNIT 569F120 (cont)
569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
121.0
121.0
8.00
119.0
119.0
8.45
115.0
115.0
9.35
113.0
113.0
9.86
112.0
112.0
10.40
108.0
108.0
11.40

62
123.0
116.0
8.03
121.0
115.0
8.48
117.0
112.0
9.37
115.0
111.0
9.87
113.0
110.0
10.40
108.0
107.0
11.40

67
132.0
96.4
8.14
130.0
95.5
8.59
125.0
93.7
9.50
123.0
92.8
10.0
121.0
91.8
10.50
116.0
89.9
11.50

72
143.0
75.6
8.29
141.0
74.8
8.74
136.0
73.1
9.66
133.0
72.1
10.20
131.0
71.2
10.70
126.0
69.4
11.70

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
131.0
131.0
138.0
148.0
131.0
131.0
112.0
85.1
8.12
8.12
8.21
8.36
129.0
129.0
135.0
146.0
129.0
129.0
111.0
84.3
8.58
8.58
8.67
8.82
125.0
125.0
131.0
141.0
125.0
125.0
109.0
82.5
9.49
9.49
9.57
9.73
123.0
123.0
128.0
138.0
123.0
123.0
108.0
81.6
10.00
9.99
10.10
10.20
121.0
121.0
125.0
135.0
121.0
121.0
107.0
80.7
10.50
10.50
10.60
10.80
116.0
116.0
120.0
130.0
116.0
116.0
105.0
78.9
11.50
11.50
11.60
11.80

6250
57
140.0
140.0
8.24
138.0
138.0
8.70
134.0
134.0
9.62
131.0
131.0
10.10
129.0
129.0
10.60
124.0
124.0
11.70

62
138.0
138.0
8.22
137.0
137.0
8.68
133.0
133.0
9.60
131.0
131.0
10.10
129.0
129.0
10.60
124.0
123.0
11.70

67
143.0
127.0
8.28
140.0
126.0
8.73
135.0
124.0
9.64
132.0
123.0
10.10
130.0
122.0
10.70
124.0
120.0
11.70

72
153.0
94.5
8.42
150.0
93.6
8.88
145.0
91.9
9.80
142.0
91.0
10.30
139.0
90.0
10.80
133.0
88.2
11.90

67
136.0
118.0
8.19
133.0
117.0
8.64
129.0
115.0
9.55
126.0
114.0
10.10
124.0
113.0
10.60
118.0
111.0
11.60

72
146.0
88.2
8.33
144.0
87.4
8.78
139.0
85.8
9.70
136.0
84.9
10.20
133.0
84.0
10.70
128.0
82.3
11.70

569F120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
114.0
114.0
7.93
113.0
113.0
8.37
109.0
109.0
9.27
107.0
107.0
9.77
106.0
106.0
10.30
102.0
102.0
11.30

62
117.0
109.0
7.96
115.0
108.0
8.40
111.0
106.0
9.29
109.0
105.0
9.79
107.0
103.0
10.30
103.0
101.0
11.30

67
126.0
91.1
8.07
124.0
90.2
8.51
120.0
88.5
9.41
117.0
87.6
9.91
115.0
86.7
10.40
110.0
84.8
11.40

72
137.0
71.7
8.20
134.0
70.8
8.65
130.0
69.2
9.56
127.0
68.3
10.10
125.0
67.4
10.60
120.0
65.7
11.60

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
124.0
124.0
131.0
142.0
124.0
124.0
105.0
80.0
8.03
8.04
8.13
8.27
122.0
122.0
129.0
139.0
122.0
122.0
104.0
79.2
8.49
8.49
8.58
8.72
118.0
118.0
124.0
135.0
118.0
118.0
102.0
77.6
9.39
9.39
9.48
9.63
116.0
116.0
122.0
132.0
116.0
116.0
101.0
76.7
9.90
9.89
9.99
10.10
114.0
114.0
119.0
129.0
114.0
114.0
100.0
75.8
10.40
10.40
10.50
10.70
110.0
110.0
114.0
124.0
110.0
110.0
98.1
74.1
11.40
11.40
11.50
11.70

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

25

6250
57
132.0
132.0
8.14
130.0
130.0
8.59
126.0
126.0
9.51
124.0
124.0
10.00
122.0
122.0
10.50
118.0
118.0
11.50

62
130.0
130.0
8.12
129.0
129.0
8.57
125.0
125.0
9.48
123.0
123.0
9.99
121.0
121.0
10.50
117.0
117.0
11.50

50TFQ004-012
569D072-120,
576C120, 569F120

COMBINATION RATINGS (cont)

50TFQ004-012
569D072-120,
576C120, 569F120

ELECTRICAL DATA
569D072-120, 576C120, 569F120 UNITS
FACTORYINSTALLED
OPTION

UNIT
SIZE

072

090

569D

120

576C

120

569F

FLA
LRA
MCA
MOCP
NEC
RLA

120

—
—
—
—
—
—

NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET

NOMINAL
VOLTAGE
V-Ph-Hz

VOLTAGE
RANGE*
MIN MAX

COMPRESSOR
RLA

LRA

FAN MOTORS
(Qty 2)
FLA (ea)
LRA (ea)

208/230-3-60

187

254

19.2

146

0.9

1.6

460-3-60

418

506

9.6

73

0.4

0.9

575-3-60

523

632

7.7

58.4

0.4

0.9

208/230-3-60

187

254

25.6

190

1.5

3.1

460-3-60

418

506

12.8

95

0.7

1.9

575-3-60

523

632

10.2

76

0.7

1.9

208/230-3-60

187

254

37.8

239

1.5

3.1

460-3-60

418

506

17.2

125

0.7

1.9

575-3-60

523

632

13.4

80

0.7

1.9

208/230-3-60

187

254

36

198

1.5

3.1

460-3-60

418

506

18

99

0.7

1.9

575-3-60

523

632

14

79

0.7

1.9

208/230-3-60

187

254

16

125

1.5

3.1

460-3-60

418

506

8

66.5

0.7

1.9

575-3-60

523

632

6.4

50

0.7

1.9

LEGEND
Full Load Amps
Locked Rotor Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
Rated Load Amps

POWER
SUPPLY
MCA
MOCP
25.8
35
30.6
35
12.8
20
15.0
20
10.2
15
12.0
15
35.0
60
39.8
60
17.4
30
19.6
30
13.8
20
15.5
20
50.3
60
55.1
70
22.9
30
25.1
30
17.8
25
19.5
25
48.0
60
52.8
70
23.9
35
26.1
35
18.6
30
20.3
30
39.0
50
43.8
50
19.4
25
21.6
25
15.8
20
17.5
20

*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.

26

APPLICATION DATA — 569D072-120, 576C090-120, 569F120

Maximum Cooling Outdoor

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE

115 F
See Minimum Outdoor-Air
Operating Temperature
table at right.

Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat

UNIT
SIZE

COMPR
CAPACITY

COND
TEMP
(F)

100%
100%
100%
100%
67%
100%

90
90
90
90
80
90

MINIMUM
OUTDOOR TEMP
(F)
With
Std
Motormaster®
Control
35
35
35
–20
35
35
35

55 F
95 F

569D

072
090
120

576C

120*

569F

120

25 to 55 F
275 F
60 F

*Unit has one step of unloading.

NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal condensing unit capacity).
2. Total combined draw of the field-supplied liquid line solenoid valve
and air handler fan contactor must not exceed 22 va. If the specified va must be exceeded, use a remote relay to control the load.

REFRIGERANT PIPING SIZES
LINEAR LENGTH OF PIPING — FT
0-25

UNIT
SIZE

1. LIQUID LINE — For applications with liquid lift greater than
20 ft, use 1/2-in. liquid line where 3/8 in. is shown; use 5/8-in.
liquid line where 1/2 in. is shown. The maximum liquid lift is
60 ft.
MAXIMUM REFRIGERANT CHARGE

25-50

50-75

75-100

Line Size (in. OD)
L

S

L

S

L

S

L

S

072

3/ 8

11/8

3/ 8

11 / 8

3/8

11/8

3/ 8

11/8

569D 090

3/ 8

11/8

1/ 2

11 / 8

1/2

11/8

1/ 2

11/8

120

1/ 2

13/8

1/ 2

13 / 8

1/2

13/8

1/ 2

13/8

576C 120

1/ 2

13/8

1/ 2

13 / 8

1/2

13/8

1/ 2

13/8

569F 120 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8 (2) 3/8 (2) 11/8
UNIT
SIZE
569D
576C
569F

R-22 (lb)
072
090
120
120
120

LEGEND
L — Liquid Line
S — Suction Line

17.3
34.2
34.2
34.2
(2) 17.1

NOTES:
1. Pipe sizes are based on a 2° F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.

2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
REFRIGERANT SPECIALTIES PART NUMBERS
UNIT
569D072
569D090
569D120
576C120

LIQUID LINE
SIZE (in.)
3/8
3/8
1/2
1/2
1/2
3/8

LIQUID LINE
SOLENOID VALVE (LLSV)
200RB5T3M
200RB5T3M
200RB5T4M
200RB6T4M
200RB6T4M
200RB5T3M Qty 2

LLSV
COIL
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V Qty 2

*Bushings required.

27

SIGHT
GLASS
AMI-1TT3
AMI-1TT3
AMI-1TT4
AMI-1TT4
AMI-1TT4
AMI-1TT3 Qty 2

FILTER
DRIER
P502-8304S*
P502-8304S*
P502-8304S
P502-8307S*
P502-8307S*
P502-8304S* Qty 2

SUCTION LINE
ACCUMULATOR
S-7063S*
S-7063S*
S-7063S*
S-7063
S-7063
S-7061 Qty 2

50TFQ004-012
569D072-120,
576C120, 569F120

OPERATING LIMITS

50TFQ004-012
569D072-120,
576C120, 569F120

TYPICAL PIPING AND WIRING
WEATHERPROOF
FUSED DISCONNECT*
PER NEC

CONDENSING
UNIT
FIELD
SUPPLIED
POWER

MOISTURE
INDICATOR
SIGHT GLASS*

ELECTRIC
HEATER
ACCESSORY

POWER WIRES
LLSV*

PIT
CH

FILTER
DRIER*

INSULATED
VAPOR
LINE

LIQUID
LINE

CONTROL
WIRES

524A
UNIT

CONDENSATE DRAIN
POWER WIRES

INDOOR
THERMOSTAT†
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN

LEGEND
LLSV — Liquid Line Solenoid Valve
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
*Field supplied.
†Accessory item.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

Rooftop Installation — 569D072-120, 576C120

28

GUIDE SPECIFICATIONS — 569D072-120, 576C120
D. Compressor:
1. Compressor shall be of the scroll type (569D) or
semi-hermetic reciprocating type (576C).
2. Compressors shall be mounted on vibration
isolators.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressor shall be equipped with internal high discharge temperature protection (569D072 and 120
only).
6. Compressor shall unload using suction cutoff unloading (576C120 only). Electric solenoid unloading
available as an accessory.
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include liquid line
service valve, suction line service valve, liquid filter drier,
a full charge of compressor oil, and a holding charge of
refrigerant. Unit 569D120 shall include an accumulator.
Units with semi-hermetic compressors (576C) shall have
oil-level sight glass and all units shall have crankcase
heater.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
a. High discharge pressure cutout.
b. Low Pressure cutout.
c. High discharge temperature cutout (569D090
only).
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed Btuh at a suction temperature of ______ F.
The power consumption at full load shall not exceed
______ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling capacity of ______ Btuh or greater at conditions
of ______ cfm entering-air temperature at the evaporator at ______ F wet bulb and ______ F dry bulb,
and air entering the condensing unit at ______ F.
3. The system shall have an EER of ______ Btuh/Watt
or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
______ v, 3-ph, 60 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
______ v to ______ v.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.

29

50TFQ004-012
569D072-120,
576C120, 569F120

COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 6 TO 10 TONS, NOMINAL
BRYANT MODEL NUMBERS: 569D, SIZES 072-120
576C, SIZE 120
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
reciprocating air-conditioning compressor assembly
(576C) or scroll compressor (569D), an air-cooled coil,
propeller-type condenser fan, and a control box. Unit shall
discharge supply air upward as shown on contract drawings. Unit shall be used in a refrigeration circuit matched
with a packaged air-handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI latest
revisions.
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
E. Air-cooled condenser coils for semi-hermetic compressor
units (576C) shall be leak tested at 150 psig and pressure
tested at 480 psig. Air-cooled condenser coils for scroll
compressor units (569D) shall be leak tested at 200 psig,
and pressure tested at 428 psig.
F. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.

50TFQ004-012
569D072-120,
576C120, 569F120

GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)
J. Special Features:
1. Low-Ambient Temperature Control Accessory:
Low-ambient control shall be available as a factoryinstalled option or a field-installed accessory and
shall regulate speed of condenser-fan motor in
response to the saturated condensing temperature
of the unit. The control shall maintain correct condensing pressure at outdoor temperatures down to
–20 F (fan motor change required for 569D and
576C units).
2. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to
create an inert barrier between the aluminum
fin and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.
b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness characteristics of 2H per ASTM D3363-92A and cross
hatch adhesion of 4B-5B per ASTM D3359-93.
Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion resistance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be confirmed through testing to no less than 1000 hours
salt spray per ASTM B117-90. Coil construction

3.

4.

5.

6.

7.

8.

30

shall be aluminum-fins mechanically bonded to
copper tubes.
Thermostat Control Accessory:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
b. Commercial Electronic Non-programmable Thermostat with auto-changeover, multi-stage capacity,
and large LCD display.
Hail Guard Accessory:
Hail guard package shall protect coils against damage from hail and other flying debris.
Condenser Coil Grille Accessory:
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
Electric Solenoid Unloader Accessory:
Electric unloader valve piston, coil, and hardware
shall be supplied to convert the pressure-operated
compressor unloader to electric unloading (576C120
only).
Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from outside the unit.

GUIDE SPECIFICATIONS — 569F120

E.

F.

G.

H.

I.

J.

31

4. Compressors shall be equipped with a crankcase
heater.
5. Compressors shall be equipped with high discharge
temperature protection.
Condenser Coil:
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
Refrigeration Components:
Refrigeration circuit components shall include liquid
line service valve, suction line service valve, a full
charge of compressor oil, and a holding charge of
refrigerant.
Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall not
exceed _____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
3. The system shall have an EER of _____ Btuh/ Watt
or greater at standard ARI conditions.
Electrical Requirements:
1. Nominal unit electrical characteristics shall be _____
v, 3-ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits of _____ v to
_____ v.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.
Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be available
as a factory-installed option or as a field-installed
accessory. This low-ambient control shall regulate
speed of the condenser-fan motors in response to
the saturated condensing temperature of the unit.
The control shall maintain correct condensing pressure at outdoor temperatures down to –20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and discharge pressure gage.

50TFQ004-012
569D072-120,
576C120, 569F120

COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 10 TONS, NOMINAL
BRYANT MODEL NUMBER: 569F, SIZE 120
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall have
2 independent refrigeration circuits. Unit shall consist of
dual scroll compressors, air-cooled coils, propeller-type
condenser fans, and a control box. Unit shall discharge
supply air upward as shown on contract drawings. Unit
shall be used in a refrigeration circuit matched with a packaged air-handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard 210/
240, latest revision.
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
E. Air-cooled condenser coils shall be leak tested at
200 psig, and pressure tested at 428 psig.
F. Unit shall be manufactured in a facility registered to ISO
9001:2000 manufacturing quality standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.
D. Compressor:
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on vibration isolators.
3. Compressors shall include overload protection.

50TFQ004-012
569D072-120,
576C120, 569F120

GUIDE SPECIFICATIONS — 569F120 (cont)
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65 to 90% per ASTM D523-89. Uniform
dry film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A
and cross hatch adhesion of 4B-5B per ASTM
D3359-93. Impact resistance shall be up to
160 in./lb (ASTM D2794-93). Humidity and water
immersion resistance shall be up to a minimum
of 1000 and 250 hours respectively (ASTM
D2247-92 and ASTM D870-92). Corrosion durability shall be confirmed through testing to no less
than 1000 hours salt spray per ASTM B117-90.
Coil construction shall be aluminum fins mechanically bonded to copper tubes.

4. Thermostat Controls:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
5. Hail Guard Package:
Hail guard package shall protect coils against damage from hail and other flying debris.
6. Condenser Coil Grille:
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
8. Convenience Outlet:
Shall be factory-installed and internally mounted with
easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from outside the unit.

32

MODEL NUMBER NOMENCLATURE
566D

E

X

150

000

––
Factory-Installed Options*

566D — Commercial Air-Cooled Condensing
Unit With Semi-Hermetic Compressor
566E — Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressors

Heating Capacity
000 — No Heat

Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60

Nominal Tons Cooling
150 — 12-1/2
180 — 15
240 — 20

Heating
X — None
*Contact your local representative for more details.

Quality Assurance
Certified to ISO 9001:2000

566D/E150-240
50TFQ004-012

33

PHYSICAL DATA

566D/E150-240
50TFQ004-012

566D150-240 UNITS
UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHTS (lb)
Aluminum-Fin Coil (Standard)
Copper-Fin Coil (Optional)
REFRIGERANT TYPE*
Operating Charge, Typical (lb)†
Shipping Charge (lb)
COMPRESSOR
Qty...Model
No. Cylinders
Speed (rpm)
Oil Charge (pt)
Capacity Steps
Accessory
Standard
Unloader Setting (psig)
Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm, total)
Watts (total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)††
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

566D150
121/2

566D180
15

566D240
20

779
919

929
1040

1...06DD328
6
1750
10

789
929
R-22
23
3.1
Reciprocating, Semi-Hermetic
1...06DD537
6
1750
10

1...06E4250
4
1750
15.5

33**, 66, 100
66, 100

33**, 66, 100
66, 100

—
50, 100

3...15
29.2
48

70 ± 1
60 ± 2
125
Axial Flow, Direct Drive
2...1075
26
1/ 2
11,000
1460
Copper Tubes, Aluminum Fins
3...15
29.2
48

3...15
29.2
38

23
3.1

28
3.1

395 ± 10
295 ± 20
27 ± 4
67 ± 7

255 ± 10
160 ± 10
Liquid Line
200
13 / 8

13/8
5/ 8
3/ 8

15/8

*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system
capacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 120 F.

34

PHYSICAL DATA (cont)
566E150-240 UNITS
UNIT
NOMINAL CAPACITY (tons)
OPERATING WEIGHTS (lb)
Aluminum-Fin Coil (Standard)
Copper-Fin Coil (Optional)
REFRIGERANT TYPE*
Operating Charge, Typical (lb)†
Shipping Charge (lb)
COMPRESSOR
Qty...Model
Speed (rpm)
Oil Charge (oz)
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm, total)
Watts (total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)**
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

566E150
121/2

566E180
15

566E240
20

676
822

740
886
R-22
23
3.1
Scroll
2...ZR94
3500
85 (ea)
70

764
904

23
3.1
2...ZR72
3500
60 (ea)

28
3.1
2...ZR125
3500
110 (ea)

2...1075
26
1/ 2
11,000
1460
3...15
29.2
48

426 ± 7
320 ± 20
27 ± 4
67 ± 7

255 ± 10
160 ± 10

(2) 13/8
(2) 1/2
3/ 8

*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for
maximum system capacity.
**Storage capacity is measured at liquid saturated temperatures of 120 F.

35

566D/E150-240
50TFQ004-012

Liquid Line
200

DIMENSIONS

566D/E150-240
50TFQ004-012

NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2 ft
Side (opposite compressor) — 3 ft
Ends — 2 ft
Top — 5 ft
2. See page 38 for corner weights and
unit center of gravity.

566D150-240

36

DIMENSIONS (cont)

NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2 ft (1067 mm)
Side (opposite compressor) — 3 ft (914 mm)
Ends — 2 ft (610 mm)
Top — 5 ft (1524 mm)
2. See page 38 for corner weights and unit
center of gravity.

566D/E150-240
50TFQ004-012

566E150-240

37

DIMENSIONS (cont)

566D150-240
UNIT
566D
150
180
240

Standard
Weight
(lb)
779
789
900

UNIT
566D

566D/E150-240
50TFQ004-012

150
180
240

ALUMINUM COIL
Operational Weight Points (lb)
A

B

C

D

E

F

70
70
84

177
180
234

68
69
82

100
101
108

261
265
310

103
104
111

CENTER OF GRAVITY (in.)
Aluminum Coil
X
Y
38
16
38
16
37
17

566E150-240
UNIT
566E
150
180
240

Standard
Weight
(lb)
676
740
764

UNIT
566E
150
180
240

ALUMINUM COIL
Operational Weight Points (lb)
A

B

C

D

E

F

84
86
87

168
186
192

72
71
72

78
82
85

183
216
226

91
99
102

CENTER OF GRAVITY (in.)
Aluminum Coil
X
Y
35
19
35
18
35
18

NOTES:
1. Corner weights are approximate.
2. Actual support weights depend on level of unit and evenness of support posts.
3. Total weights represent approximate unit weights without shipping package.
4. Bottom or top skid is NOT included in the weights.

566D150-240, 566E150-240

38

PERFORMANCE DATA
CONDENSING UNIT RATINGS
566D150

566E150

SST (F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

25

30

35

40

45

50

80
139.0
12.30
99.5
159.0
12.90
102.0
179.0
13.50
105.0
198.0
14.00
108.0
218.0
14.60
110.0
237.0
15.20
113.0

Air Temperature Entering Condenser (F)
85
95
100
105
134.0
126.0
121.0
117.0
12.70
13.60
14.00
14.40
104.0
114.0
118.0
123.0
154.0
144.0
139.0
134.0
13.40
14.30
14.70
15.20
107.0
116.0
121.0
125.0
173.0
163.0
157.0
152.0
14.00
15.00
15.50
16.00
109.0
119.0
123.0
128.0
192.0
181.0
175.0
170.0
14.60
15.70
16.30
16.80
112.0
121.0
125.0
130.0
212.0
199.0
193.0
187.0
15.20
16.50
17.00
17.60
115.0
124.0
128.0
132.0
231.0
218.0
211.0
205.0
15.90
17.20
17.80
18.40
117.0
126.0
130.0
135.0

80
175.0
16.30
104.0
200.0
17.20
107.0
224.0
18.20
110.0
249.0
19.10
114.0
273.0
20.10
117.0
297.0
21.00
120.0

Air Temperature Entering Condenser (F)
85
95
100
105
169.0
157.0
151.0
145.0
16.80
17.70
18.20
18.60
108.0
117.0
122.0
126.0
193.0
180.0
173.0
166.0
17.80
18.80
19.30
19.80
111.0
120.0
125.0
129.0
217.0
202.0
195.0
188.0
18.80
19.90
20.50
21.00
115.0
123.0
128.0
132.0
241.0
225.0
218.0
210.0
19.80
21.00
21.60
22.20
118.0
126.0
131.0
135.0
265.0
248.0
240.0
232.0
20.80
22.10
22.70
23.40
121.0
129.0
134.0
138.0
289.0
271.0
262.0
253.0
21.80
23.20
23.90
24.60
124.0
132.0
137.0
141.0

SST (F)

115
74.7
10.70
129.0
88.5
11.20
131.0
102.0
11.70
132.0
116.0
12.20
134.0
130.0
12.70
135.0
144.0
13.10
136.0

20

25

30

35

40

45

566D180

50

SST (F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

25

30

35

40

45

50

115
108.0
15.10
133.0
125.0
16.00
135.0
142.0
16.90
137.0
158.0
17.80
139.0
175.0
18.70
141.0
192.0
19.60
144.0

SST (F)
20

25

30

35

40

45

25

30

35

40

45

50

kW
SDT
SST
TC

—
—
—
—

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Air Temperature Entering Condenser (F)
85
95
100
105
99.1
93.2
90.3
87.3
9.58
10.80
11.40
12.10
108.0
118.0
123.0
128.0
111.0
105.0
102.0
98.8
9.64
10.90
11.50
12.20
108.0
118.0
123.0
128.0
124.0
117.0
114.0
110.0
9.70
10.90
11.50
12.20
108.0
118.0
123.0
128.0
137.0
130.0
126.0
123.0
9.75
11.00
11.60
12.30
108.0
118.0
123.0
128.0
151.0
144.0
140.0
136.0
9.81
11.00
11.70
12.30
108.0
118.0
123.0
128.0
166.0
158.0
154.0
150.0
9.90
11.10
11.70
12.40
108.0
118.0
123.0
128.0
182.0
173.0
169.0
164.0
10.10
11.30
11.90
12.60
109.0
119.0
124.0
129.0

115
81.1
13.50
138.0
92.2
13.60
138.0
103.0
13.70
138.0
115.0
13.70
138.0
128.0
13.80
138.0
141.0
13.90
138.0
155.0
14.00
139.0

80
141.0
12.01
101.0
156.0
12.40
102.0
171.0
12.70
104.0
187.0
13.10
105.0
203.0
13.50
107.0
221.0
13.90
109.0
239.0
14.40
111.0

Air Temperature Entering Condenser (F)
85
95
100
105
137.0
129.0
124.0
120.0
12.60
13.70
14.30
14.90
105.0
115.0
120.0
125.0
152.0
143.0
138.0
133.0
12.90
14.00
14.60
15.20
107.0
116.0
121.0
126.0
166.0
157.0
152.0
147.0
13.20
14.30
14.90
15.50
108.0
118.0
123.0
127.0
182.0
172.0
166.0
161.0
13.60
14.70
15.30
15.90
110.0
119.0
12.04
129.0
198.0
187.0
181.0
176.0
14.00
15.10
15.70
16.30
112.0
121.0
126.0
130.0
215.0
204.0
198.0
192.0
14.50
15.60
16.10
16.70
114.0
123.0
127.0
132.0
233.0
221.0
215.0
208.0
14.90
16.10
16.70
17.20
116.0
125.0
129.0
134.0

115
110.0
16.10
135.0
123.0
16.40
136.0
136.0
16.70
137.0
150.0
17.10
138.0
164.0
17.50
140.0
179.0
17.90
141.0
195.0
18.40
143.0

80
184.0
16.20
105.0
202.0
16.80
107.0
220.0
17.30
109.0
239.0
18.00
111.0
259.0
18.70
113.0
280.0
19.40
116.0
302.0
20.20
118.0

Air Temperature Entering Condenser (F)
85
95
100
105
179.0
170.0
165.0
160.0
17.00
18.50
19.40
20.20
110.0
119.0
124.0
129.0
197.0
186.0
181.0
176.0
17.50
19.00
19.80
20.60
112.0
121.0
126.0
131.0
214.0
203.0
197.0
191.0
18.00
19.50
20.30
21.10
113.0
123.0
127.0
132.0
233.0
220.0
214.0
208.0
18.60
20.10
20.80
21.60
116.0
125.0
129.0
134.0
253.0
239.0
232.0
225.0
19.30
20.70
21.50
22.20
118.0
127.0
131.0
136.0
273.0
259.0
252.0
244.0
20.10
21.50
22.20
22.90
120.0
129.0
134.0
138.0
295.0
280.0
272.0
264.0
20.90
22.30
23.00
23.70
123.0
132.0
136.0
140.0

115
148.0
21.70
139.0
163.0
22.20
140.0
179.0
22.70
141.0
194.0
23.20
143.0
211.0
23.80
145.0
229.0
24.50
147.0
247.0
25.20
149.0

566E180

566D240
SST (F)

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

80
102.0
9.04
103.0
114.0
9.09
103.0
127.0
9.14
103.0
140.0
9.19
103.0
155.0
9.26
103.0
170.0
9.37
103.0
186.0
9.55
104.0

115
134.0
19.40
135.0
154.0
20.70
138.0
175.0
22.00
141.0
195.0
23.30
144.0
216.0
24.60
146.0
236.0
25.90
149.0

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

566E240
SST (F)
20

25

30

35

40

LEGEND
Compressor Power
Saturated Discharge Temperature at Compressor (F)
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

45

50

39

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

566D/E150-240
50TFQ004-012

80
101.0
8.56
94.6
118.0
8.80
96.6
134.0
9.03
98.6
150.0
9.26
101.0
166.0
9.50
103.0
182.0
9.73
105.0

Air Temperature Entering Condenser (F)
85
95
100
105
97.6
90.0
86.0
82.2
8.90
9.55
9.85
10.20
99.4
109.0
114.0
119.0
113.0
105.0
101.0
96.7
9.17
9.90
10.20
10.60
101.0
111.0
116.0
121.0
129.0
120.0
116.0
111.0
9.44
10.20
10.60
11.00
103.0
113.0
117.0
122.0
145.0
135.0
130.0
126.0
9.71
10.60
11.00
11.40
105.0
115.0
119.0
124.0
161.0
150.0
145.0
140.0
9.98
10.90
11.40
11.80
107.0
116.0
121.0
126.0
177.0
166.0
160.0
155.0
10.30
11.30
11.70
12.20
109.0
118.0
123.0
127.0

PERFORMANCE DATA (cont)
COMBINATION RATINGS
UNIT 566D150
566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
133.0
133.0
9.00
131.0
131.0
9.44
126.0
126.0
10.40
123.0
123.0
10.80
121.0
121.0
11.30
116.0
116.0
12.20

62
139.0
123.0
9.07
136.0
122.0
9.54
130.0
119.0
10.50
127.0
117.0
10.90
124.0
116.0
11.40
118.0
113.0
12.30

67
151.0
103.0
9.27
148.0
102.0
9.75
142.0
99.5
10.70
138.0
98.2
11.20
135.0
96.8
11.70
129.0
94.1
12.60

72
165.0
83.1
9.48
161.0
81.9
9.99
155.0
79.3
11.00
151.0
78.0
11.50
148.0
76.8
12.00
141.0
74.2
13.00

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
146.0
147.0
158.0
172.0
146.0
142.0
119.0
92.7
9.18
9.20
9.38
9.59
143.0
144.0
155.0
169.0
143.0
140.0
117.0
91.3
9.66
9.69
9.88
10.10
138.0
138.0
148.0
161.0
138.0
137.0
115.0
88.8
10.60
10.60
10.90
11.20
135.0
135.0
145.0
157.0
135.0
134.0
113.0
87.5
11.10
11.10
11.30
11.70
132.0
132.0
141.0
154.0
132.0
132.0
112.0
86.1
11.60
11.60
11.80
12.20
127.0
127.0
134.0
146.0
127.0
127.0
109.0
83.5
12.50
12.50
12.80
13.20

6250
57
154.0
154.0
9.32
152.0
152.0
9.82
146.0
146.0
10.80
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80

62
154.0
154.0
9.32
151.0
151.0
9.81
146.0
146.0
10.80
143.0
143.0
11.30
140.0
140.0
11.80
134.0
134.0
12.80

67
163.0
133.0
9.45
160.0
131.0
9.96
153.0
128.0
11.00
149.0
127.0
11.50
145.0
125.0
12.00
138.0
122.0
12.90

72
177.0
101.0
9.66
173.0
100.0
10.20
165.0
97.5
11.30
161.0
96.2
11.80
157.0
94.8
12.30
149.0
92.2
13.30

67
158.0
126.0
9.37
154.0
125.0
9.87
147.0
122.0
10.80
144.0
121.0
11.30
140.0
119.0
11.80
133.0
116.0
12.80

72
172.0
96.9
9.58
168.0
95.6
10.10
160.0
93.0
11.10
156.0
91.7
11.70
153.0
90.4
12.20
145.0
87.8
13.20

566D150/524A-B150 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
127.0
127.0
8.93
125.0
125.0
9.37
121.0
121.0
10.30
118.0
118.0
10.70
116.0
116.0
11.20
111.0
111.0
12.00

62
134.0
118.0
9.01
131.0
117.0
9.45
125.0
114.0
10.30
122.0
112.0
10.80
119.0
111.0
11.20
113.0
108.0
12.10

67
146.0
99.4
9.19
143.0
98.2
9.67
137.0
95.6
10.60
134.0
94.3
11.10
131.0
92.9
11.50
124.0
90.3
12.50

72
160.0
80.2
9.40
156.0
78.9
9.90
150.0
76.4
10.90
146.0
75.2
11.40
143.0
73.9
11.90
136.0
71.4
12.90

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
140.0
142.0
153.0
167.0
140.0
136.0
114.0
89.0
9.09
9.12
9.31
9.51
137.0
139.0
150.0
163.0
137.0
134.0
112.0
87.6
9.55
9.58
9.79
10.00
132.0
133.0
143.0
156.0
132.0
130.0
110.0
85.1
10.50
10.50
10.70
11.00
129.0
130.0
140.0
152.0
129.0
128.0
108.0
83.8
11.00
11.00
11.20
11.60
127.0
127.0
136.0
149.0
127.0
126.0
107.0
82.5
11.40
11.40
11.70
12.10
121.0
121.0
129.0
141.0
121.0
121.0
104.0
79.9
12.40
12.40
12.60
13.10

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

40

6250
57
148.0
148.0
9.22
145.0
145.0
9.70
140.0
140.0
10.70
137.0
137.0
11.20
134.0
134.0
11.60
128.0
128.0
12.60

62
148.0
148.0
9.22
145.0
145.0
9.71
140.0
140.0
10.70
137.0
137.0
11.20
134.0
134.0
11.60
128.0
128.0
12.60

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D150 (cont)
566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57
142.0
142.0
9.13
140.0
140.0
9.60
134.0
134.0
10.50
132.0
132.0
11.00
129.0
129.0
11.50
124.0
124.0
12.40

62
145.0
136.0
9.17
142.0
134.0
9.65
136.0
131.0
10.60
133.0
129.0
11.10
130.0
127.0
11.50
124.0
123.0
12.50

67
157.0
114.0
9.37
154.0
112.0
9.86
147.0
109.0
10.80
144.0
108.0
11.30
140.0
107.0
11.80
133.0
104.0
12.80

72
171.0
89.6
9.57
168.0
88.3
10.10
160.0
85.7
11.20
157.0
84.4
11.70
153.0
83.1
12.20
146.0
80.5
13.20

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
154.0
154.0
164.0
178.0
154.0
154.0
131.0
100.0
9.31
9.32
9.47
9.66
151.0
151.0
160.0
174.0
151.0
151.0
129.0
99.1
9.81
9.81
9.97
10.20
146.0
146.0
153.0
166.0
146.0
146.0
127.0
96.4
10.80
10.80
11.00
11.30
143.0
143.0
150.0
162.0
143.0
143.0
125.0
95.1
11.30
11.30
11.50
11.80
140.0
140.0
146.0
158.0
140.0
140.0
124.0
93.8
11.80
11.80
12.00
12.30
134.0
134.0
139.0
150.0
134.0
134.0
121.0
91.0
12.80
12.80
13.00
13.40

7500
57
163.0
163.0
9.44
160.0
160.0
9.96
153.0
153.0
11.00
150.0
150.0
11.50
147.0
147.0
12.00
140.0
140.0
13.00

62
163.0
163.0
9.45
160.0
160.0
9.96
153.0
153.0
11.00
150.0
150.0
11.50
147.0
147.0
12.00
140.0
140.0
13.00

67
168.0
146.0
9.53
165.0
145.0
10.00
157.0
142.0
11.10
154.0
140.0
11.60
150.0
138.0
12.10
142.0
135.0
13.10

72
182.0
110.0
9.72
178.0
109.0
10.30
170.0
106.0
11.40
166.0
105.0
11.90
162.0
104.0
12.40
153.0
101.0
13.50

67
167.0
143.0
9.51
163.0
142.0
10.00
155.0
138.0
11.00
152.0
137.0
11.50
148.0
135.0
12.00
140.0
132.0
13.00

72
181.0
108.0
9.71
176.0
107.0
10.20
168.0
104.0
11.30
164.0
103.0
11.80
160.0
101.0
12.40
152.0
98.7
13.40

566D150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
140.0
140.0
9.09
137.0
137.0
9.56
132.0
132.0
10.50
130.0
130.0
11.00
127.0
127.0
11.40
121.0
121.0
12.40

62
144.0
134.0
9.14
140.0
132.0
9.61
134.0
129.0
10.50
131.0
127.0
11.00
128.0
125.0
11.50
122.0
121.0
12.40

67
156.0
112.0
9.34
152.0
110.0
9.84
146.0
107.0
10.80
142.0
106.0
11.30
139.0
105.0
11.80
131.0
102.0
12.70

72
170.0
88.3
9.55
166.0
87.0
10.10
159.0
84.4
11.10
155.0
83.1
11.60
151.0
81.7
12.10
144.0
79.0
13.10

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
152.0
152.0
162.0
176.0
152.0
152.0
128.0
98.7
9.28
9.28
9.44
9.65
149.0
149.0
159.0
172.0
149.0
149.0
127.0
97.3
9.78
9.77
9.94
10.20
143.0
143.0
151.0
165.0
143.0
143.0
124.0
94.6
10.70
10.70
10.90
11.20
140.0
140.0
148.0
161.0
140.0
140.0
123.0
93.3
11.30
11.20
11.40
11.80
137.0
137.0
144.0
157.0
137.0
137.0
12.01
91.9
11.70
11.70
11.90
12.30
131.0
131.0
136.0
148.0
131.0
131.0
118.0
89.2
12.70
12.70
12.90
13.30

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

41

7500
57
160.0
160.0
9.41
157.0
157.0
9.92
151.0
151.0
10.90
148.0
148.0
11.40
145.0
145.0
11.90
138.0
138.0
12.90

62
160.0
160.0
9.41
157.0
157.0
9.92
151.0
151.0
10.90
148.0
148.0
11.40
145.0
145.0
11.90
138.0
138.0
12.90

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180
566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57
167.0
167.0
13.10
165.0
165.0
13.70
160.0
160.0
14.90
157.0
157.0
15.50
154.0
154.0
16.00
148.0
148.0
17.30

62
177.0
152.0
13.40
174.0
150.0
14.00
167.0
147.0
15.20
164.0
145.0
15.80
160.0
144.0
16.30
153.0
140.0
17.50

67
192.0
128.0
13.90
189.0
127.0
14.50
182.0
123.0
15.70
178.0
122.0
16.40
174.0
120.0
17.00
166.0
117.0
18.20

72
209.0
104.0
14.40
205.0
102.0
15.00
197.0
99.3
16.40
193.0
97.8
17.00
189.0
96.3
17.70
181.0
93.2
19.00

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
183.0
187.0
202.0
219.0
183.0
175.0
146.0
115.0
13.60
13.70
14.10
14.70
180.0
184.0
198.0
214.0
180.0
174.0
145.0
113.0
14.20
14.30
14.80
15.30
174.0
177.0
190.0
206.0
174.0
170.0
141.0
110.0
15.50
15.60
16.10
16.70
171.0
173.0
186.0
202.0
171.0
168.0
140.0
109.0
16.10
16.20
16.70
17.40
168.0
169.0
182.0
197.0
168.0
165.0
138.0
107.0
16.70
16.80
17.40
18.10
162.0
162.0
174.0
188.0
162.0
161.0
135.0
104.0
18.00
18.00
18.60
19.40

7500
57
194.0
194.0
13.90
191.0
191.0
14.60
185.0
185.0
15.90
181.0
181.0
16.50
178.0
178.0
17.20
171.0
171.0
18.50

62
195.0
193.0
13.90
192.0
191.0
14.60
185.0
185.0
15.90
181.0
181.0
16.50
178.0
178.0
17.20
171.0
171.0
18.50

67
208.0
163.0
14.30
204.0
161.0
15.00
196.0
158.0
16.30
191.0
156.0
17.00
187.0
154.0
17.60
178.0
151.0
18.90

72
225.0
125.0
14.80
220.0
124.0
15.50
211.0
120.0
16.90
207.0
119.0
17.60
202.0
117.0
18.30
193.0
114.0
19.70

67
206.0
159.0
14.30
202.0
158.0
14.90
193.0
154.0
16.20
189.0
153.0
16.90
185.0
151.0
17.50
176.0
147.0
18.80

72
223.0
123.0
14.80
218.0
121.0
15.50
209.0
118.0
16.90
205.0
117.0
17.50
200.0
115.0
18.20
191.0
112.0
19.50

566D180/524A-B180 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57
165.0
165.0
13.00
162.0
162.0
13.60
157.0
157.0
14.80
154.0
154.0
15.30
151.0
151.0
15.90
146.0
146.0
17.10

62
175.0
149.0
13.30
171.0
148.0
13.90
165.0
144.0
15.10
161.0
143.0
15.70
158.0
141.0
16.20
151.0
137.0
17.40

67
190.0
126.0
13.80
187.0
125.0
14.40
179.0
121.0
15.70
176.0
120.0
16.30
172.0
118.0
16.90
164.0
115.0
18.10

72
207.0
102.0
14.30
203.0
101.0
15.00
195.0
97.9
16.30
191.0
96.3
17.00
187.0
94.8
17.60
179.0
91.7
18.90

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
180.0
185.0
200.0
217.0
180.0
172.0
143.0
113.0
13.50
13.60
14.10
14.60
177.0
181.0
196.0
213.0
177.0
170.0
142.0
112.0
14.10
14.20
14.70
15.30
171.0
174.0
188.0
204.0
171.0
166.0
139.0
108.0
15.30
15.50
16.00
16.60
168.0
170.0
184.0
199.0
168.0
164.0
137.0
107.0
16.00
16.10
16.70
17.30
165.0
167.0
180.0
195.0
165.0
162.0
135.0
105.0
16.60
16.70
17.30
18.00
159.0
160.0
171.0
186.0
159.0
157.0
132.0
102.0
17.80
17.90
18.50
19.30

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

42

7500
57
191.0
191.0
13.80
188.0
188.0
14.50
182.0
182.0
15.80
178.0
178.0
16.40
175.0
175.0
17.00
168.0
168.0
18.30

62
193.0
190.0
13.90
189.0
187.0
14.50
182.0
181.0
15.80
178.0
178.0
16.40
175.0
175.0
17.00
168.0
168.0
18.30

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180 (cont)
566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000
57
196.0
196.0
13.90
193.0
193.0
14.60
186.0
186.0
15.90
183.0
183.0
16.50
179.0
179.0
17.20
172.0
172.0
18.50

62
200.0
188.0
14.00
196.0
186.0
14.70
188.0
182.0
16.00
184.0
179.0
16.60
180.0
177.0
17.20
172.0
172.0
18.50

67
215.0
156.0
14.50
211.0
154.0
15.20
203.0
151.0
16.50
198.0
149.0
17.20
193.0
147.0
17.80
184.0
144.0
19.10

72
234.0
123.0
15.00
229.0
121.0
15.70
219.0
118.0
17.10
215.0
116.0
17.90
210.0
114.0
18.60
200.0
111.0
20.00

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
212.0
212.0
224.0
242.0
212.0
212.0
181.0
138.0
14.40
14.40
14.70
15.20
209.0
209.0
220.0
237.0
209.0
209.0
179.0
136.0
15.10
15.10
15.40
16.00
201.0
201.0
210.0
227.0
201.0
201.0
175.0
133.0
16.50
16.50
16.80
17.40
197.0
197.0
205.0
222.0
197.0
197.0
173.0
131.0
17.20
17.10
17.50
18.10
193.0
193.0
201.0
216.0
193.0
193.0
171.0
129.0
17.80
17.80
18.20
18.90
185.0
185.0
191.0
206.0
185.0
185.0
168.0
126.0
19.20
19.20
19.50
20.30

10,000
57
223.0
223.0
14.70
219.0
219.0
15.40
211.0
211.0
16.80
207.0
207.0
17.60
203.0
203.0
18.30
194.0
194.0
19.70

62
224.0
224.0
14.70
220.0
220.0
15.40
211.0
211.0
16.80
207.0
207.0
17.50
203.0
203.0
18.30
194.0
194.0
19.70

67
230.0
203.0
14.90
225.0
201.0
15.60
216.0
197.0
17.00
211.0
195.0
17.70
206.0
192.0
18.40
196.0
188.0
19.80

72
247.0
152.0
15.30
242.0
151.0
16.10
231.0
147.0
17.60
226.0
146.0
18.30
221.0
144.0
19.00
210.0
140.0
20.50

566D180/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
186.0
186.0
13.70
183.0
183.0
14.30
176.0
176.0
15.50
173.0
173.0
16.20
170.0
170.0
16.80
163.0
163.0
18.10

62
190.0
178.0
13.80
186.0
176.0
14.40
179.0
172.0
15.60
175.0
170.0
16.20
171.0
167.0
16.90
164.0
163.0
18.10

67
205.0
148.0
14.20
200.0
147.0
14.90
192.0
143.0
16.20
188.0
142.0
16.80
184.0
140.0
17.50
175.0
136.0
18.70

72
222.0
117.0
14.70
217.0
115.0
15.40
208.0
112.0
16.80
204.0
110.0
17.50
199.0
108.0
18.20
190.0
105.0
19.50

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
201.0
201.0
212.0
230.0
201.0
201.0
171.0
130.0
14.10
14.10
14.50
15.00
197.0
197.0
208.0
225.0
197.0
197.0
169.0
129.0
14.80
14.80
15.10
15.70
190.0
190.0
199.0
215.0
190.0
190.0
165.0
125.0
16.10
16.10
16.50
17.10
186.0
186.0
195.0
211.0
186.0
186.0
163.0
124.0
16.80
16.70
17.10
17.80
183.0
183.0
190.0
206.0
183.0
183.0
162.0
122.0
17.40
17.40
17.80
18.50
175.0
175.0
181.0
196.0
175.0
175.0
158.0
119.0
18.70
18.70
19.10
19.80

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

43

10,000
57
211.0
211.0
14.40
207.0
207.0
15.10
199.0
199.0
16.50
195.0
195.0
17.10
191.0
191.0
17.80
183.0
183.0
19.20

62
211.0
211.0
14.40
207.0
207.0
15.10
199.0
199.0
16.50
195.0
195.0
17.10
191.0
191.0
17.80
183.0
183.0
19.10

67
218.0
190.0
14.60
213.0
188.0
15.30
204.0
184.0
16.70
200.0
182.0
17.30
195.0
180.0
18.00
186.0
175.0
19.30

72
235.0
143.0
15.10
230.0
142.0
15.80
220.0
138.0
17.30
215.0
137.0
18.00
210.0
135.0
18.70
199.0
132.0
20.00

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D240
566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
57
244.0
244.0
18.90
239.0
239.0
19.70
230.0
230.0
21.30
226.0
226.0
22.00
221.0
221.0
22.80
212.0
212.0
24.30

62
249.0
233.0
19.20
244.0
231.0
19.90
233.0
225.0
21.40
228.0
222.0
22.10
222.0
219.0
22.80
212.0
211.0
24.30

67
268.0
194.0
19.90
263.0
192.0
20.70
251.0
187.0
22.20
245.0
184.0
23.00
239.0
182.0
23.70
226.0
177.0
25.20

72
291.0
152.0
20.80
284.0
150.0
21.60
272.0
146.0
23.20
265.0
143.0
24.00
259.0
141.0
24.80
245.0
136.0
26.40

Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
57
62
67
72
264.0
264.0
279.0
301.0
264.0
264.0
224.0
171.0
19.70
19.70
20.30
21.20
259.0
259.0
273.0
294.0
259.0
259.0
222.0
169.0
20.50
20.50
21.10
22.00
249.0
249.0
260.0
281.0
249.0
249.0
217.0
164.0
22.10
22.10
22.70
23.70
244.0
244.0
254.0
274.0
244.0
244.0
214.0
162.0
22.90
22.90
23.50
24.50
238.0
238.0
247.0
267.0
238.0
238.0
212.0
160.0
23.70
23.70
24.20
25.30
227.0
227.0
235.0
253.0
227.0
227.0
206.0
155.0
25.30
25.30
25.80
26.90

12,500
57
278.0
278.0
20.30
272.0
272.0
21.10
261.0
261.0
22.70
256.0
256.0
23.60
250.0
250.0
24.40
238.0
238.0
26.00

62
278.0
278.0
20.30
272.0
272.0
21.10
261.0
261.0
22.70
256.0
256.0
23.60
250.0
250.0
24.40
238.0
238.0
26.00

67
286.0
252.0
20.60
280.0
249.0
21.40
267.0
243.0
23.00
260.0
240.0
23.80
254.0
237.0
24.60
240.0
231.0
26.10

72
307.0
189.0
21.40
300.0
187.0
22.30
286.0
182.0
23.90
279.0
180.0
24.80
272.0
177.0
25.60
257.0
172.0
27.20

566D240/524A-B300 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
57
230.0
230.0
18.40
226.0
226.0
19.20
218.0
218.0
20.60
214.0
214.0
21.40
209.0
209.0
22.10
201.0
201.0
23.60

62
236.0
219.0
18.60
231.0
217.0
19.40
221.0
211.0
20.80
217.0
208.0
21.50
212.0
206.0
22.20
202.0
199.0
23.70

67
255.0
183.0
19.40
250.0
181.0
20.20
239.0
176.0
21.70
233.0
174.0
22.40
228.0
172.0
23.10
216.0
167.0
24.60

72
277.0
144.0
20.20
271.0
142.0
21.00
259.0
138.0
22.60
253.0
136.0
23.40
247.0
133.0
24.20
235.0
129.0
25.80

Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
57
62
67
72
249.0
249.0
266.0
287.0
249.0
248.0
209.0
161.0
19.10
19.20
19.80
20.60
244.0
244.0
259.0
281.0
244.0
244.0
207.0
159.0
19.90
19.90
20.60
21.50
235.0
235.0
248.0
268.0
235.0
235.0
203.0
154.0
21.50
21.50
22.10
23.10
230.0
230.0
242.0
261.0
230.0
230.0
200.0
152.0
22.20
22.20
22.90
23.80
225.0
225.0
236.0
255.0
225.0
225.0
198.0
150.0
23.00
23.00
23.60
24.60
215.0
215.0
224.0
242.0
215.0
215.0
193.0
145.0
24.60
24.50
25.10
26.20

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

44

12,500
57
262.0
262.0
19.60
256.0
256.0
20.40
246.0
246.0
22.00
241.0
241.0
22.80
236.0
236.0
23.60
226.0
226.0
25.20

62
262.0
262.0
19.60
256.0
256.0
20.40
246.0
246.0
22.00
241.0
241.0
22.80
236.0
236.0
23.60
226.0
226.0
25.20

67
272.0
233.0
20.10
266.0
231.0
20.80
254.0
226.0
22.40
248.0
223.0
23.20
242.0
220.0
23.90
229.0
214.0
25.40

72
293.0
176.0
20.90
287.0
174.0
21.70
273.0
169.0
23.30
266.0
167.0
24.10
260.0
165.0
24.90
246.0
160.0
26.50

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150
566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000
57
126.0
126.0
9.13
125.0
125.0
9.68
121.0
121.0
10.90
119.0
119.0
11.60
118.0
118.0
12.30
114.0
114.0
13.70

62
135.0
112.0
9.18
133.0
111.0
9.72
129.0
109.0
11.00
127.0
108.0
11.60
124.0
107.0
12.30
120.0
104.0
13.80

67
148.0
95.4
9.22
146.0
94.5
9.79
141.0
92.4
11.00
138.0
91.4
11.70
136.0
90.3
12.40
131.0
88.0
13.80

72
161.0
78.5
9.31
159.0
77.5
9.87
154.0
75.6
11.10
151.0
74.6
11.70
149.0
73.5
12.40
143.0
71.4
13.90

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
140.0
144.0
156.0
170.0
140.0
130.0
109.0
87.0
9.19
9.20
9.26
9.37
138.0
142.0
154.0
168.0
138.0
129.0
108.0
86.0
9.74
9.77
9.82
9.92
134.0
137.0
149.0
162.0
134.0
127.0
106.0
84.0
11.00
11.00
11.00
11.10
132.0
135.0
146.0
159.0
132.0
126.0
105.0
82.9
11.60
11.60
11.70
11.80
130.0
132.0
143.0
156.0
130.0
124.0
104.0
81.9
12.30
12.30
12.40
12.50
126.0
127.0
137.0
150.0
126.0
122.0
101.0
79.6
13.80
13.80
13.80
13.90

5000
57
149.0
149.0
9.22
147.0
147.0
9.78
143.0
143.0
11.00
141.0
141.0
11.60
138.0
138.0
12.30
134.0
134.0
13.80

62
151.0
146.0
9.23
148.0
144.0
9.80
144.0
141.0
11.00
141.0
140.0
11.70
139.0
138.0
12.40
134.0
134.0
13.80

67
162.0
122.0
9.30
159.0
121.0
9.85
154.0
118.0
11.10
151.0
117.0
11.70
148.0
116.0
12.40
142.0
114.0
13.90

72
176.0
94.8
9.43
173.0
93.8
9.98
167.0
91.8
11.20
164.0
90.7
11.80
161.0
89.6
12.50
154.0
87.4
14.00

67
153.0
114.0
9.25
151.0
113.0
9.80
146.0
111.0
11.00
143.0
110.0
11.70
140.0
109.0
12.40
135.0
107.0
13.80

72
166.0
89.0
9.33
164.0
88.1
9.89
158.0
86.3
11.10
156.0
85.3
11.80
153.0
84.3
12.40
147.0
82.3
13.90

566E150/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
119.0
119.0
9.09
118.0
118.0
9.66
115.0
115.0
10.90
113.0
113.0
11.60
111.0
111.0
12.20
108.0
108.0
13.70

62
128.0
106.0
9.15
126.0
105.0
9.72
122.0
103.0
10.90
120.0
102.0
11.60
118.0
101.0
12.30
114.0
99.0
13.70

67
140.0
90.4
9.18
138.0
89.5
9.75
134.0
87.7
11.00
131.0
86.7
11.60
129.0
85.7
12.30
124.0
83.7
13.80

72
153.0
74.3
9.23
151.0
73.4
9.81
146.0
71.7
11.00
144.0
70.8
11.70
141.0
69.8
12.40
136.0
67.8
13.90

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
131.0
136.0
148.0
161.0
131.0
122.0
103.0
82.0
9.15
9.16
9.21
9.30
130.0
134.0
146.0
159.0
130.0
121.0
102.0
81.2
9.72
9.72
9.77
9.87
126.0
130.0
141.0
154.0
126.0
119.0
99.9
79.3
10.90
10.90
11.00
11.10
124.0
128.0
139.0
151.0
124.0
118.0
98.9
78.4
11.60
11.60
11.60
11.70
122.0
125.0
136.0
148.0
122.0
117.0
97.9
77.5
12.30
12.30
12.30
12.40
118.0
121.0
131.0
143.0
118.0
114.0
95.8
75.4
13.70
13.80
13.80
13.90

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

45

5000
57
140.0
140.0
9.19
138.0
138.0
9.75
134.0
134.0
11.00
132.0
132.0
11.60
130.0
130.0
12.30
126.0
126.0
13.80

62
142.0
136.0
9.19
140.0
135.0
9.75
136.0
132.0
11.00
133.0
131.0
11.60
131.0
129.0
12.30
126.0
126.0
13.80

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3000

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
139.0
139.0
9.18
137.0
137.0
9.74
133.0
133.0
11.00
131.0
131.0
11.60
129.0
129.0
12.30
125.0
125.0
13.80

62
145.0
127.0
9.21
143.0
126.0
9.76
138.0
124.0
11.00
136.0
123.0
11.60
133.0
121.0
12.30
128.0
119.0
13.80

67
158.0
107.0
9.27
155.0
106.0
9.84
150.0
104.0
11.10
148.0
103.0
11.70
145.0
102.0
12.40
139.0
99.4
13.90

72
172.0
86.2
9.38
169.0
85.3
9.95
164.0
83.3
11.20
161.0
82.2
11.80
158.0
81.1
12.50
152.0
78.9
14.00

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
152.0
154.0
165.0
180.0
152.0
148.0
123.0
96.1
9.25
9.24
9.33
9.48
150.0
151.0
163.0
177.0
150.0
146.0
122.0
95.1
9.80
9.82
9.90
10.00
146.0
147.0
157.0
171.0
146.0
144.0
120.0
93.1
11.00
11.00
11.10
11.20
143.0
144.0
154.0
168.0
143.0
142.0
119.0
92.1
11.70
11.70
11.80
11.90
141.0
142.0
152.0
165.0
141.0
140.0
118.0
90.9
12.40
12.40
12.50
12.60
136.0
136.0
145.0
158.0
136.0
136.0
115.0
88.7
13.80
13.90
13.90
14.00

6250
57
161.0
161.0
9.29
159.0
159.0
9.86
154.0
154.0
11.10
152.0
152.0
11.70
149.0
149.0
12.40
144.0
144.0
13.90

62
161.0
161.0
9.31
159.0
159.0
9.87
154.0
154.0
11.10
152.0
152.0
11.70
149.0
149.0
12.40
144.0
144.0
13.90

67
170.0
138.0
9.37
168.0
137.0
9.93
162.0
134.0
11.10
159.0
133.0
11.80
156.0
132.0
12.50
150.0
129.0
13.90

72
185.0
105.0
9.54
182.0
104.0
10.10
175.0
102.0
11.30
172.0
101.0
11.90
169.0
100.0
12.60
162.0
97.9
14.10

67
162.0
128.0
9.30
159.0
127.0
9.85
154.0
125.0
11.10
151.0
124.0
11.70
148.0
123.0
12.40
142.0
120.0
13.90

72
176.0
98.5
9.43
173.0
97.5
9.98
167.0
95.6
11.20
164.0
94.5
11.80
161.0
93.5
12.50
154.0
91.3
14.00

566E150/524A-B150 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
130.0
130.0
9.14
129.0
129.0
9.70
125.0
125.0
10.90
123.0
123.0
11.60
122.0
122.0
12.30
118.0
118.0
13.80

62
137.0
120.0
9.18
135.0
119.0
9.73
131.0
117.0
11.00
128.0
115.0
11.60
126.0
114.0
12.30
121.0
112.0
13.80

67
150.0
101.0
9.22
147.0
100.0
9.78
143.0
98.0
11.00
140.0
97.0
11.70
137.0
95.9
12.30
132.0
93.6
13.80

72
163.0
81.6
9.32
161.0
80.7
9.88
156.0
78.7
11.10
153.0
77.7
11.70
150.0
76.7
12.40
144.0
74.5
13.90

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
143.0
145.0
157.0
171.0
143.0
138.0
115.0
90.5
9.20
9.20
9.27
9.38
141.0
143.0
154.0
168.0
141.0
137.0
114.0
89.5
9.76
9.76
9.82
9.93
137.0
138.0
149.0
162.0
137.0
134.0
112.0
87.5
11.00
11.00
11.00
11.10
135.0
136.0
146.0
160.0
135.0
132.0
111.0
86.5
11.60
11.70
11.70
11.80
132.0
133.0
144.0
157.0
132.0
131.0
110.0
85.4
12.30
12.30
12.40
12.50
128.0
128.0
138.0
150.0
128.0
128.0
108.0
83.3
13.80
13.80
13.90
14.00

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

46

6250
57
151.0
151.0
9.24
149.0
149.0
9.79
145.0
145.0
11.00
143.0
143.0
11.70
140.0
140.0
12.30
135.0
135.0
13.80

62
151.0
151.0
9.23
149.0
149.0
9.79
145.0
145.0
11.00
143.0
143.0
11.70
140.0
140.0
12.40
135.0
135.0
13.80

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57
152.0
152.0
9.24
150.0
150.0
9.80
146.0
146.0
11.00
144.0
144.0
11.70
141.0
141.0
12.40
137.0
137.0
13.90

62
156.0
145.0
9.26
154.0
144.0
9.82
148.0
141.0
11.10
146.0
140.0
11.70
143.0
138.0
12.40
138.0
135.0
13.90

67
169.0
121.0
9.35
166.0
120.0
9.92
161.0
117.0
11.10
158.0
116.0
11.80
155.0
115.0
12.50
148.0
112.0
13.90

72
183.0
95.4
9.53
181.0
94.4
10.10
175.0
92.2
11.30
171.0
91.1
11.90
168.0
90.0
12.60
162.0
87.6
14.10

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
166.0
166.0
176.0
190.0
166.0
166.0
140.0
107.0
9.33
9.33
9.43
9.63
164.0
164.0
173.0
187.0
164.0
164.0
139.0
106.0
9.89
9.89
9.99
10.20
159.0
159.0
167.0
181.0
159.0
159.0
136.0
104.0
11.10
11.10
11.20
11.40
156.0
156.0
164.0
178.0
156.0
156.0
135.0
103.0
11.80
11.80
11.90
12.00
154.0
154.0
161.0
174.0
154.0
154.0
134.0
102.0
12.50
12.50
12.50
12.70
148.0
148.0
154.0
167.0
148.0
148.0
131.0
99.5
13.90
14.00
14.00
14.20

7500
57
175.0
175.0
9.42
173.0
173.0
9.98
167.0
167.0
11.20
165.0
165.0
11.80
162.0
162.0
12.50
156.0
156.0
14.00

62
175.0
175.0
9.43
173.0
173.0
9.99
167.0
167.0
11.20
165.0
165.0
11.90
162.0
162.0
12.50
156.0
156.0
14.00

67
181.0
157.0
9.49
178.0
156.0
10.00
172.0
154.0
11.20
169.0
152.0
11.90
165.0
151.0
12.60
159.0
148.0
14.00

72
195.0
119.0
9.69
191.0
118.0
10.20
185.0
115.0
11.40
181.0
114.0
12.10
178.0
113.0
12.80
170.0
111.0
14.20

67
171.0
146.0
9.37
168.0
144.0
9.93
162.0
142.0
11.10
159.0
141.0
11.80
156.0
139.0
12.50
150.0
137.0
13.90

72
185.0
110.0
9.54
182.0
109.0
10.10
175.0
107.0
11.30
172.0
106.0
11.90
169.0
105.0
12.60
162.0
103.0
14.10

566E150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
143.0
143.0
9.19
141.0
141.0
9.75
137.0
137.0
11.00
135.0
135.0
11.60
133.0
133.0
12.30
129.0
129.0
13.80

62
147.0
136.0
9.22
145.0
134.0
9.77
140.0
132.0
11.00
138.0
131.0
11.60
135.0
129.0
12.30
130.0
126.0
13.80

67
160.0
113.0
9.28
157.0
112.0
9.85
152.0
110.0
11.10
149.0
109.0
11.70
146.0
108.0
12.40
140.0
106.0
13.90

72
174.0
89.9
9.42
171.0
89.0
9.98
165.0
86.9
11.20
162.0
85.8
11.80
159.0
84.7
12.50
153.0
82.5
14.00

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
155.0
156.0
166.0
180.0
155.0
155.0
130.0
100.0
9.27
9.26
9.34
9.49
153.0
153.0
164.0
178.0
153.0
153.0
129.0
99.5
9.82
9.82
9.90
10.00
149.0
149.0
158.0
172.0
149.0
149.0
127.0
97.4
11.00
11.00
11.10
11.20
146.0
146.0
155.0
168.0
146.0
146.0
126.0
96.3
11.70
11.70
11.80
11.90
144.0
144.0
152.0
165.0
144.0
144.0
125.0
95.2
12.40
12.40
12.50
12.60
139.0
139.0
146.0
158.0
139.0
139.0
122.0
92.9
13.90
13.90
13.90
14.10

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

47

7500
57
164.0
164.0
9.31
162.0
162.0
9.87
157.0
157.0
11.10
154.0
154.0
11.70
152.0
152.0
12.40
146.0
146.0
13.90

62
164.0
164.0
9.33
162.0
162.0
9.89
157.0
157.0
11.10
154.0
154.0
11.80
152.0
152.0
12.50
146.0
146.0
13.90

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180
566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
163.0
161.0
12.60
160.0
159.0
13.10
155.0
155.0
14.30
152.0
152.0
14.90
150.0
150.0
15.60
144.0
144.0
16.90

62
175.0
142.0
12.80
172.0
141.0
13.40
166.0
138.0
14.60
163.0
136.0
15.20
159.0
134.0
15.80
152.0
131.0
17.10

67
190.0
121.0
13.20
187.0
120.0
13.80
180.0
117.0
15.00
177.0
115.0
15.60
173.0
114.0
16.20
165.0
110.0
17.50

72
206.0
99.8
13.60
203.0
98.5
14.20
196.0
95.6
15.40
192.0
94.0
16.00
188.0
92.4
16.60
179.0
89.1
18.00

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
179.0
186.0
201.0
217.0
179.0
164.0
138.0
110.0
12.90
13.10
13.40
13.80
176.0
183.0
198.0
214.0
176.0
163.0
136.0
109.0
13.50
13.70
14.00
14.40
170.0
176.0
190.0
206.0
170.0
159.0
133.0
106.0
14.70
14.80
15.20
15.70
167.0
172.0
186.0
201.0
167.0
158.0
131.0
104.0
15.30
15.50
15.80
16.30
164.0
168.0
182.0
197.0
164.0
156.0
130.0
102.0
16.00
16.10
16.50
16.90
158.0
161.0
173.0
188.0
158.0
152.0
126.0
99.0
17.30
17.40
17.80
18.20

6250
57
191.0
191.0
13.20
188.0
188.0
13.80
181.0
181.0
15.00
178.0
178.0
15.60
175.0
175.0
16.30
168.0
168.0
17.60

62
194.0
184.0
13.30
190.0
182.0
13.80
183.0
178.0
15.00
180.0
176.0
15.60
176.0
173.0
16.30
168.0
167.0
17.60

67
208.0
153.0
13.60
204.0
151.0
14.20
196.0
148.0
15.40
192.0
146.0
16.00
188.0
145.0
16.60
178.0
141.0
17.90

72
224.0
119.0
14.00
220.0
118.0
14.60
212.0
115.0
15.80
208.0
113.0
16.50
203.0
112.0
17.10
193.0
108.0
18.40

67
197.0
143.0
13.40
194.0
141.0
13.90
187.0
138.0
15.10
182.0
137.0
15.70
178.0
135.0
16.40
170.0
132.0
17.70

72
213.0
112.0
13.70
210.0
111.0
14.30
202.0
108.0
15.50
197.0
106.0
16.20
193.0
105.0
16.80
183.0
101.0
18.10

566E180/524A-B150 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
154.0
152.0
12.40
152.0
150.0
12.90
147.0
146.0
14.10
144.0
144.0
14.80
141.0
141.0
15.40
136.0
136.0
16.80

62
166.0
134.0
12.60
163.0
133.0
13.20
157.0
130.0
14.40
154.0
128.0
15.00
151.0
127.0
15.60
144.0
124.0
16.90

67
181.0
115.0
13.00
178.0
113.0
13.50
171.0
111.0
14.70
168.0
109.0
15.30
164.0
107.0
16.00
157.0
104.0
17.30

72
196.0
94.7
13.30
193.0
93.4
13.90
186.0
90.6
15.10
182.0
89.1
15.70
179.0
87.6
16.40
170.0
84.4
17.70

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
168.0
176.0
191.0
206.0
168.0
154.0
129.0
104.0
12.70
12.90
13.20
13.60
166.0
173.0
188.0
203.0
166.0
153.0
128.0
102.0
13.20
13.40
13.80
14.20
160.0
167.0
180.0
196.0
160.0
149.0
125.0
99.7
14.40
14.60
15.00
15.40
158.0
163.0
177.0
191.0
158.0
148.0
123.0
98.1
15.10
15.20
15.60
16.00
155.0
160.0
173.0
187.0
155.0
146.0
122.0
96.5
15.70
15.80
16.20
16.60
149.0
152.0
165.0
178.0
149.0
142.0
118.0
93.3
17.10
17.20
17.50
17.90

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

48

6250
57
179.0
179.0
12.90
176.0
176.0
13.50
171.0
171.0
14.70
167.0
167.0
15.30
164.0
164.0
16.00
158.0
158.0
17.30

62
183.0
171.0
13.00
180.0
169.0
13.60
173.0
166.0
14.80
170.0
163.0
15.40
166.0
161.0
16.00
159.0
156.0
17.30

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500
57
180.0
180.0
12.90
177.0
177.0
13.50
172.0
172.0
14.70
169.0
169.0
15.40
166.0
166.0
16.00
159.0
159.0
17.30

62
190.0
162.0
13.20
187.0
160.0
13.80
180.0
157.0
14.90
176.0
155.0
15.60
172.0
153.0
16.20
164.0
149.0
17.50

67
206.0
136.0
13.60
203.0
135.0
14.20
195.0
132.0
15.40
191.0
130.0
16.00
187.0
128.0
16.60
178.0
124.0
17.90

72
223.0
110.0
14.00
220.0
109.0
14.60
212.0
106.0
15.80
207.0
104.0
16.40
203.0
102.0
17.10
193.0
98.8
18.40

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
197.0
201.0
216.0
233.0
197.0
188.0
156.0
122.0
13.30
13.40
13.80
14.20
194.0
198.0
212.0
229.0
194.0
186.0
154.0
121.0
13.90
14.00
14.40
14.80
188.0
190.0
204.0
221.0
188.0
182.0
151.0
118.0
15.20
15.20
15.60
16.10
184.0
186.0
200.0
216.0
184.0
180.0
149.0
116.0
15.80
15.80
16.20
16.70
181.0
182.0
195.0
211.0
181.0
178.0
147.0
115.0
16.40
16.50
16.90
17.40
173.0
174.0
185.0
201.0
173.0
172.0
144.0
111.0
17.80
17.80
18.10
18.60

7500
57
209.0
209.0
13.60
206.0
206.0
14.20
199.0
199.0
15.50
195.0
195.0
16.10
191.0
191.0
16.70
183.0
183.0
18.10

62
210.0
208.0
13.70
206.0
206.0
14.20
199.0
199.0
15.50
195.0
195.0
16.10
191.0
191.0
16.80
183.0
183.0
18.10

67
222.0
174.0
14.00
219.0
173.0
14.60
210.0
169.0
15.80
205.0
168.0
16.40
201.0
166.0
17.00
191.0
162.0
18.30

72
239.0
134.0
14.40
235.0
132.0
15.00
226.0
129.0
16.20
221.0
128.0
16.90
216.0
126.0
17.50
205.0
122.0
18.80

67
211.0
162.0
13.70
207.0
160.0
14.30
199.0
157.0
15.50
194.0
155.0
16.10
190.0
153.0
16.70
180.0
150.0
18.00

72
227.0
125.0
14.10
223.0
123.0
14.70
215.0
120.0
15.90
210.0
119.0
16.50
205.0
117.0
17.20
195.0
114.0
18.50

566E180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
169.0
169.0
12.70
167.0
167.0
13.30
161.0
161.0
14.50
159.0
159.0
15.10
156.0
156.0
15.70
150.0
150.0
17.10

62
180.0
152.0
12.90
177.0
151.0
13.50
170.0
147.0
14.70
166.0
145.0
15.30
163.0
144.0
15.90
155.0
140.0
17.20

67
195.0
128.0
13.30
192.0
127.0
13.90
184.0
124.0
15.10
181.0
122.0
15.70
177.0
120.0
16.30
168.0
117.0
17.60

72
211.0
104.0
13.70
208.0
103.0
14.30
200.0
99.8
15.50
196.0
98.2
16.10
192.0
96.6
16.80
183.0
93.2
18.10

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
57
62
67
72
185.0
190.0
204.0
221.0
185.0
175.0
146.0
115.0
13.10
13.20
13.50
13.90
182.0
186.0
201.0
217.0
182.0
173.0
144.0
113.0
13.60
13.70
14.10
14.50
176.0
179.0
193.0
209.0
176.0
169.0
141.0
111.0
14.80
14.90
15.30
15.70
173.0
176.0
189.0
204.0
173.0
167.0
139.0
109.0
15.50
15.50
15.90
16.40
169.0
172.0
185.0
200.0
169.0
165.0
138.0
107.0
16.10
16.20
16.50
17.00
163.0
164.0
175.0
190.0
163.0
160.0
134.0
104.0
17.50
17.50
17.80
18.30

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

49

7500
57
196.0
196.0
13.30
193.0
193.0
13.90
186.0
186.0
15.10
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70

62
197.0
193.0
13.30
194.0
191.0
13.90
187.0
186.0
15.10
183.0
183.0
15.70
179.0
179.0
16.40
172.0
172.0
17.70

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

4500

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000
57
201.0
201.0
13.40
198.0
198.0
14.00
191.0
191.0
15.30
188.0
188.0
15.90
184.0
184.0
16.50
176.0
176.0
17.90

62
205.0
191.0
13.50
202.0
190.0
14.10
194.0
186.0
15.30
190.0
183.0
15.90
185.0
181.0
16.60
177.0
176.0
17.90

67
220.0
159.0
13.90
216.0
157.0
14.50
208.0
154.0
15.70
204.0
152.0
16.30
199.0
150.0
17.00
189.0
146.0
18.30

72
238.0
125.0
14.40
234.0
123.0
15.00
225.0
120.0
16.20
220.0
118.0
16.80
215.0
117.0
17.50
205.0
113.0
18.80

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
217.0
217.0
229.0
246.0
217.0
217.0
184.0
140.0
13.80
13.80
14.10
14.60
214.0
214.0
225.0
242.0
214.0
214.0
182.0
139.0
14.40
14.40
14.70
15.20
207.0
207.0
216.0
232.0
207.0
207.0
179.0
136.0
15.70
15.70
15.90
16.40
202.0
203.0
211.0
227.0
202.0
203.0
177.0
134.0
16.30
16.30
16.60
17.10
198.0
198.0
206.0
222.0
198.0
198.0
175.0
132.0
17.00
17.00
17.20
17.70
190.0
190.0
196.0
211.0
190.0
190.0
171.0
128.0
18.30
18.30
18.50
19.00

10,000
57
228.0
228.0
14.10
225.0
225.0
14.70
217.0
217.0
16.00
213.0
213.0
16.60
208.0
208.0
17.30
199.0
199.0
18.60

62
228.0
228.0
14.10
225.0
225.0
14.70
217.0
217.0
16.00
213.0
213.0
16.60
208.0
208.0
17.30
199.0
199.0
18.60

67
234.0
207.0
14.30
230.0
205.0
14.90
221.0
201.0
16.10
216.0
199.0
16.70
211.0
197.0
17.40
201.0
192.0
18.70

72
251.0
155.0
14.70
247.0
154.0
15.30
237.0
150.0
16.60
232.0
149.0
17.20
226.0
147.0
17.80
214.0
143.0
19.10

566E180/524A-B240 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000
57
190.0
190.0
13.20
187.0
187.0
13.80
181.0
181.0
15.00
178.0
178.0
15.60
174.0
174.0
16.20
167.0
167.0
17.60

62
194.0
181.0
13.30
191.0
179.0
13.90
184.0
175.0
15.00
180.0
173.0
15.70
176.0
171.0
16.30
168.0
166.0
17.60

67
209.0
150.0
13.60
205.0
149.0
14.20
197.0
146.0
15.40
193.0
144.0
16.00
188.0
142.0
16.60
179.0
138.0
18.00

72
226.0
118.0
14.00
222.0
117.0
14.60
213.0
114.0
15.90
209.0
112.0
16.50
204.0
110.0
17.10
194.0
107.0
18.40

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
205.0
205.0
217.0
233.0
205.0
204.0
173.0
132.0
13.50
13.50
13.80
14.20
202.0
202.0
213.0
229.0
202.0
201.0
171.0
131.0
14.10
14.10
14.40
14.80
195.0
195.0
204.0
220.0
195.0
195.0
168.0
128.0
15.30
15.30
15.60
16.10
191.0
191.0
200.0
216.0
191.0
191.0
166.0
126.0
16.00
16.00
16.20
16.70
187.0
187.0
195.0
210.0
187.0
187.0
164.0
124.0
16.60
16.60
16.90
17.30
179.0
179.0
185.0
200.0
179.0
179.0
160.0
121.0
17.90
17.90
18.10
18.60

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

50

10,000
57
215.0
215.0
13.80
211.0
211.0
14.40
204.0
204.0
15.60
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20

62
215.0
215.0
13.80
211.0
211.0
14.40
204.0
204.0
15.60
200.0
200.0
16.20
196.0
196.0
16.90
187.0
187.0
18.20

67
222.0
193.0
14.00
218.0
191.0
14.50
209.0
187.0
15.80
205.0
185.0
16.40
200.0
183.0
17.00
190.0
178.0
18.30

72
238.0
145.0
14.40
234.0
144.0
15.00
225.0
141.0
16.20
220.0
139.0
16.80
215.0
137.0
17.50
203.0
133.0
18.70

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240
566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000
57
228.0
228.0
17.60
225.0
225.0
18.40
218.0
218.0
20.00
214.0
214.0
20.90
211.0
211.0
21.70
203.0
203.0
23.50

62
239.0
207.0
18.00
235.0
205.0
18.70
227.0
201.0
20.30
222.0
199.0
21.10
217.0
196.0
22.00
207.0
192.0
23.70

67
258.0
174.0
18.70
254.0
172.0
19.40
244.0
168.0
21.00
239.0
166.0
21.70
234.0
163.0
22.60
223.0
159.0
24.30

72
279.0
139.0
19.40
274.0
137.0
20.10
263.0
134.0
21.70
258.0
132.0
22.50
252.0
130.0
23.30
241.0
125.0
25.00

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
248.0
252.0
269.0
290.0
248.0
240.0
199.0
155.0
18.30
18.40
19.10
19.80
245.0
248.0
265.0
285.0
245.0
237.0
197.0
153.0
19.10
19.20
19.80
20.60
236.0
238.0
254.0
274.0
236.0
232.0
193.0
149.0
20.70
20.70
21.30
22.10
232.0
234.0
249.0
268.0
232.0
229.0
190.0
147.0
21.50
21.50
22.10
22.90
228.0
229.0
243.0
262.0
228.0
226.0
188.0
145.0
22.40
22.40
22.90
23.70
219.0
219.0
231.0
249.0
219.0
219.0
184.0
140.0
24.10
24.10
24.60
25.40

10,000
57
262.0
262.0
18.80
258.0
258.0
19.60
249.0
249.0
21.10
245.0
245.0
22.00
240.0
240.0
22.80
230.0
230.0
24.60

62
262.0
262.0
18.80
258.0
258.0
19.60
249.0
249.0
21.10
245.0
245.0
22.00
240.0
240.0
22.80
230.0
230.0
24.60

67
277.0
222.0
19.30
272.0
220.0
20.10
261.0
216.0
21.60
255.0
213.0
22.40
249.0
211.0
23.20
237.0
206.0
24.90

72
297.0
169.0
20.10
291.0
167.0
20.80
280.0
163.0
22.40
274.0
161.0
23.10
267.0
159.0
23.90
254.0
155.0
25.60

566E240/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)

85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

57
219.0
219.0
17.30
216.0
216.0
18.10
209.0
209.0
19.70
206.0
206.0
20.60
202.0
202.0
21.40
195.0
195.0
23.30

62
229.0
199.0
17.70
226.0
197.0
18.40
217.0
192.0
20.00
213.0
190.0
20.80
209.0
188.0
21.70
200.0
184.0
23.40

67
248.0
167.0
18.30
243.0
165.0
19.00
234.0
161.0
20.60
230.0
159.0
21.40
225.0
157.0
22.20
215.0
153.0
24.00

72
267.0
134.0
19.00
263.0
132.0
19.70
253.0
128.0
21.30
248.0
126.0
22.10
242.0
124.0
22.90
232.0
120.0
24.60

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
57
62
67
72
237.0
241.0
259.0
278.0
237.0
228.0
190.0
148.0
17.90
18.10
18.70
19.40
234.0
237.0
254.0
273.0
234.0
226.0
188.0
146.0
18.70
18.80
19.40
20.10
226.0
228.0
244.0
263.0
226.0
221.0
184.0
142.0
20.30
20.40
20.90
21.70
222.0
224.0
239.0
257.0
222.0
218.0
182.0
140.0
21.10
21.20
21.70
22.50
218.0
219.0
233.0
251.0
218.0
215.0
180.0
138.0
22.00
22.00
22.60
23.30
210.0
210.0
223.0
239.0
210.0
209.0
175.0
134.0
23.80
23.80
24.30
25.00

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

51

10,000
57
250.0
250.0
18.40
246.0
246.0
19.10
238.0
238.0
20.70
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20

62
251.0
250.0
18.40
247.0
246.0
19.10
238.0
238.0
20.70
234.0
234.0
21.50
229.0
229.0
22.40
220.0
220.0
24.20

67
265.0
211.0
18.90
261.0
209.0
19.70
250.0
205.0
21.20
245.0
202.0
22.00
239.0
200.0
22.80
228.0
196.0
24.50

72
285.0
161.0
19.60
280.0
159.0
20.40
269.0
155.0
21.90
263.0
153.0
22.70
257.0
151.0
23.50
244.0
147.0
25.20

566D/E150-240
50TFQ004-012

80

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

6,000

PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240 (cont)
566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
57
249.0
249.0
18.30
245.0
245.0
19.10
237.0
237.0
20.70
232.0
232.0
21.50
228.0
228.0
22.30
219.0
219.0
24.10

62
254.0
236.0
18.50
249.0
234.0
19.20
240.0
229.0
20.80
235.0
226.0
21.60
230.0
223.0
22.40
219.0
217.0
24.10

67
272.0
196.0
19.20
267.0
194.0
19.90
257.0
190.0
21.40
251.0
187.0
22.20
246.0
185.0
23.00
234.0
180.0
24.70

72
293.0
154.0
19.90
288.0
152.0
20.70
277.0
148.0
22.20
271.0
145.0
23.00
265.0
143.0
23.80
252.0
139.0
25.50

Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
57
62
67
72
268.0
268.0
282.0
303.0
268.0
268.0
226.0
172.0
19.00
19.00
19.50
20.30
263.0
263.0
277.0
297.0
263.0
263.0
224.0
170.0
19.80
19.80
20.30
21.00
254.0
254.0
266.0
285.0
254.0
254.0
220.0
166.0
21.30
21.30
21.80
22.60
249.0
250.0
260.0
279.0
249.0
250.0
217.0
164.0
22.20
22.10
22.60
23.40
244.0
245.0
254.0
272.0
244.0
245.0
215.0
162.0
23.00
23.00
23.40
24.20
234.0
234.0
241.0
259.0
234.0
234.0
210.0
157.0
24.70
24.70
25.00
25.80

12,500
57
281.0
281.0
19.50
276.0
276.0
20.20
266.0
266.0
21.80
261.0
261.0
22.60
256.0
256.0
23.50
244.0
244.0
25.20

62
281.0
281.0
19.50
276.0
276.0
20.20
266.0
266.0
21.80
261.0
261.0
22.60
256.0
256.0
23.40
244.0
244.0
25.20

67
289.0
253.0
19.80
283.0
251.0
20.50
272.0
246.0
22.00
266.0
244.0
22.80
260.0
241.0
23.60
247.0
235.0
25.30

72
309.0
190.0
20.50
303.0
188.0
21.30
290.0
184.0
22.80
284.0
182.0
23.60
277.0
180.0
24.40
263.0
175.0
26.00

566E240/524A-B300 WITH STANDARD 3-ROW COIL

566D/E150-240
50TFQ004-012

Temp (F)
Air Entering
Condenser
(Edb)
80
85
95
100
105
115

Edb
Ewb
kW
SHC
TC

—
—
—
—
—

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

7,500
57
236.0
236.0
17.90
233.0
233.0
18.70
225.0
225.0
20.30
221.0
221.0
21.10
217.0
217.0
22.00
209.0
209.0
23.80

62
242.0
223.0
18.10
238.0
221.0
18.80
229.0
216.0
20.40
225.0
214.0
21.20
220.0
211.0
22.10
211.0
206.0
23.80

67
260.0
185.0
18.70
256.0
184.0
19.50
246.0
179.0
21.00
241.0
178.0
21.80
236.0
175.0
22.60
225.0
171.0
24.40

72
280.0
146.0
19.50
275.0
144.0
20.20
265.0
140.0
21.80
260.0
138.0
22.50
254.0
136.0
23.40
242.0
132.0
25.10

Evaporator Air — Cfm
10,000
Evaporator Air — Ewb (F)
57
62
67
72
254.0
254.0
269.0
290.0
254.0
252.0
212.0
162.0
18.50
18.50
19.10
19.80
250.0
250.0
265.0
285.0
250.0
249.0
210.0
161.0
19.30
19.30
19.80
20.60
242.0
242.0
255.0
273.0
242.0
242.0
206.0
157.0
20.90
20.90
21.40
22.10
237.0
237.0
249.0
268.0
237.0
237.0
204.0
155.0
21.70
21.70
22.10
22.90
233.0
233.0
243.0
262.0
233.0
233.0
202.0
153.0
22.50
22.50
23.00
23.70
223.0
223.0
232.0
249.0
223.0
223.0
197.0
148.0
24.30
24.30
24.60
25.40

LEGEND
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

52

12,500
57
266.0
266.0
18.90
262.0
262.0
19.70
253.0
253.0
21.30
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70

62
266.0
266.0
18.90
262.0
262.0
19.70
253.0
253.0
21.30
248.0
248.0
22.10
243.0
243.0
22.90
233.0
233.0
24.70

67
276.0
236.0
19.30
271.0
234.0
20.00
260.0
230.0
21.60
255.0
227.0
22.40
249.0
225.0
23.20
237.0
219.0
24.90

72
296.0
178.0
20.00
290.0
176.0
20.80
279.0
172.0
22.30
273.0
170.0
23.10
266.0
168.0
23.90
253.0
164.0
25.60

ELECTRICAL DATA
566D150-240
NOMINAL
VOLTAGE
(3-Ph, 60 Hz)

UNIT
SIZE

150

566D

180

240

208/230
460
575
208/230
460
575
208/230
460
575

COMPRESSOR

VOLTAGE
RANGE*
Min
187
414
518
187
414
518
187
414
518

Max
253
528
660
253
528
660
254
508
632

RLA

LRA

49.3
22.1
17.9
63.6
29.3
23.8
67.9
34.7
28.8

191
80
69
266
120
96
345
173
120

LEGEND
— Full Load Amps
— Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)

FAN MOTORS (Qty 2)
FLA (ea)
Fan No.
kW
1
2
4.3
3.7
2.3
1.9
1.41
1.8
1.8
4.3
3.7
2.3
1.9
1.41
1.8
1.8
4.3
3.7
2.3
1.9
1.41
1.8
1.8

POWER SUPPLY
MCA

MOCP†

69.6
31.7
25.6
87.5
40.7
33.0
93.4
48.1
40.1

100
50
40
125
60
50
150
80
60

ICF
199
84
73
274
124
100
353
177
124

*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.

FLA
HACR

566E150-240

Max

RLA

LRA

RLA

LRA

208/230

187

253

20.7

156

20.7

156

4.3

3.7

1.41

OR DISCONNECT
150 NONE
CONVENIENCE OUTLET

460

414

528

10.0

75

10.0

75

2.3

1.9

1.41

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

8.2

54

8.2

54

1.8

1.8

1.41

NONE OR DISCONNECT
CONVENIENCE OUTLET

208/230

187

253

32.1

195

32.1

195

4.3

3.7

1.41

OR DISCONNECT
180 NONE
CONVENIENCE OUTLET

460

414

528

16.4

95

16.4

95

2.3

1.9

1.41

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

12.0

80

12.0

80

1.8

1.8

1.41

NONE OR DISCONNECT
CONVENIENCE OUTLET

208/230

187

253

37.8

239

37.8

239

4.3

3.7

1.41

OR DISCONNECT
240 NONE
CONVENIENCE OUTLET

460

414

528

19.2

125

19.2

125

2.3

1.9

1.41

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

13.8

80

13.8

80

1.8

1.8

1.41

UNIT
SIZE

NONE OR DISCONNECT
CONVENIENCE OUTLET

566E

NOMINAL
VOLTAGE
(3 Ph, 60 Hz)

VOLTAGE
RANGE*

COMPRESSOR 1

LEGEND
— Full Load Amps
— Heating, Air Conditioning and
Refrigeration
ICF
— Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW
— Total Fan Motor Input (kilowatts)
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC,
Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA
— Rated Load Amps (compressor)

COMPRESSOR 2

POWER
SUPPLY
MCA
55.6
63.5
27.7
31.3
23.1
25.9
81.2
89.2
42.1
45.7
31.6
34.5
94.1
102.0
48.4
52.0
35.7
38.5

MOCP†
70
80
35
40
30
30
100
100
50
60
40
40
125
150
60
70
45
50

ICF
186
194
90
94
67
70
236
244
117
120
97
99
286
294
149
153
98
101

*Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a fieldinstalled accessory and is 115-v, 1ph, 60 Hz.

FLA
HACR

53

566D/E150-240
50TFQ004-012

Min

FAN MOTORS
Qty 2)
FLA (ea)
Fan No.
kW
1
2

FACTORYINSTALLED
OPTION

APPLICATION DATA — 566D150-240, 566E150-240
1. INSTALLATION — Select equipment to match or to be
slightly less than peak load. This provides better humidity
control, less unit cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor unit
is operating.
Ductwork should be sized according to unit size, not building load.
To minimize the possibility of air recirculation, avoid the use
of concentric supply/return grilles.
Indoor equipment should be selected at no less than
300 cfm/ton.

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566E150-240 UNITS

UNIT
566E

150
180
240

115 F
See Minimum Outdoor-Air
Operating Temperature
table below.

Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat

566D/E150-240
50TFQ004-012

150

180

240

90

50

–20

UNIT
566D

MAX
ALLOW.
LIFT
(ft)

150
180
240

67
82
87

LIQUID LINE
Max Allow.
Max Allow.
Pressure
Temp
Drop
Loss
(psi)
(°F)
7

2

55 F

NOTE: Data above is for units operating at 45 F saturated suction and
95 F entering air.

95 F

LIQUID LINE DATA — 566E150-240 UNITS

25 to 55 F
295 F

UNIT
566E

MAX
ALLOW.
LIFT
(ft)

150
180
240

60

60 F

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566D150-240 UNITS

UNIT
566D

100/50

LIQUID LINE DATA — 566D150-240 UNITS

OPERATING LIMITS
Maximum Outdoor

MINIMUM
OUTDOOR-AIR
FULL LOAD SATURATED COND TEMPERATURE (F)
CAPACITY TEMPERATURE (F)
With
(%)
Base
Low-Ambient
Unit
Control

NO. OF
CYLINDERS

FULL LOAD
CAPACITY
(%)

6
4
2*
6
4
2*
4
2

100
67
33*
100
67
33*
100
50

MINIMUM
OUTDOOR-AIR
OPERATING
TEMPERATURE (F)
With
Base
Low-Ambient
Unit
Control
20
31
40
20
–20
33
47
15
20

LIQUID LINE
Max Allow.
Max Allow.
Pressure
Temp
Drop
Loss
(psi)
(°F)
7

2

2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.

*Requires field-installed unloader.

REFRIGERANT SPECIALTIES PART NUMBERS
UNIT
566D150

566D180

566D240
566E150
566E180
566E240

LIQUID LINE
SIZE (in.)
1/2
5/8
1/2
5/8
7/8
5/8
7/8
1/2
1/2
5/8
1/2
5/8

LIQUID LINE
SOLENOID VALVE (LLSV)
200RB7T4M
200RA8T5M
200RB7T4M
200RA8T5M
200RA8T7M
200RA9T5M
200RA9T7M
200RB5T4M Qty 2
200RB5T4M Qty 2
200RB5T5M Qty 2
200RB6T4M Qty 2
200RB6T5M Qty 2

LLSV
COIL
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2
AMG/24V Qty 2

*Bushings required.

54

SIGHT
GLASS
AMI-1TT4
AMI-1TT5
AMI-1TT4
AMI-1TT5
AMI-1TT7
AMI-1TT5
AMI-1TT7
AMI-1TT4 Qty 2
AMI-1TT4 Qty 2
AMI-1TT5 Qty 2
AMI-1TT5 Qty 2
AMI-1TT5 Qty 2

FILTER
DRIER
P502-8757S*
P502-8757S*
P502-8757S*
P502-8757S*
P502-8757S
P502-8757S*
P502-8757S
P502-8304S Qty 2
P502-8304S Qty 2
P502-8304S Qty 2
P502-8307S*
P502-8307S*

SUCTION LINE
ACCUMULATOR
S-7063
S-7063
S-7721
S-7721
S-7721
S-7721
S-7721
S-7063S* Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2

APPLICATION DATA — 566D150-240, 566E150-240 (cont)
REFRIGERANT PIPING SIZES
UNIT
566D
150
180
240

LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-15
16-25
26-50
51-75
76-100
Line Size (in. OD)
L
S
L
S
L
S
L
S
L
S
1/2
1/2
5/8
5/8
7/8
11/8
13/8
13/8
15/8*
15/8*
1/2
5/8
5/8
7/8
7/8
13/8
13/8
15/8
15/8
21/8*
5/8
7/8
7/8
7/8
5/8
15/8
15/8
15/8
21/8
21/8
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-25

UNIT
566E
TXV — Thermostatic
Expansion Valve

150
180
240

Location of One Liquid Line Solenoid
Valve Serving 2 Coil Circuits
(Solenoid Drop Control)

25-50

50-75

75-100

Line Size (in. OD)
L

S

L

S

L

S

L

S

1/2

11/8
13/8
13/8

1/2

11/8
13/8
13/8

1/2

11/8
13/8
13/8

1/2

11/8
13/8
13/8

1/2
1/2

1/2
1/2

1/2
5/8

5/8
5/8

LEGEND
L — Liquid
S — Suction
Close-coupled.
*Requires a double suction riser if 2 unloaders are used and the evaporator is
below the condensing unit. See Refrigerant Piping Sizes — Double Suction Risers table and Suction Line Piping figure below for more information.
NOTES:
1. Pipe sizes are based on a 2° F loss for liquid lines and a 1.5° F loss for suction lines.
2. Pipe sizes are based on an equivalent length equal to the maximum length
of interconnecting piping plus 50% for fittings. A more accurate estimate
may result in smaller sizes.

REFRIGERANT PIPING SIZES —
DOUBLE SUCTION RISERS
UNIT
566D

NOTES:
1. See Suction Line Piping figure below for “A,” “B,” and “C” dimensions.
2. No double suction risers are needed for unit size 240.

TXV — Thermostatic
Expansion Valve

Face-Split Coil Suction and
Liquid Line Piping

LEGEND

A Suction Riser Without Trap
B Suction Riser With Trap
C Suction Line to Condensing Unit
Condensing Unit:
D Short Vertical Riser Into
3
566D150,180 — 1 /8 in. OD

Suction Line Piping

55

566D/E150-240
50TFQ004-012

150
180

LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
51-75
76-100
Line Size (in. OD)
A
B
C
A
B
C
11/8
13/8
15/8
11/8
13/8
15/8
—
—
—
13/8
15/8
21/8

APPLICATION DATA — 566D150-240, 566E150-240 (cont)
MULTIPLE CONDENSING UNIT ARRANGEMENTS*

566D, 566E150-240

566D, 566E150-240

566D, 566E150-240
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
566D,566E

566D/E150-240
50TFQ004-012

150-240

56

DIMENSIONS (ft)
A
B
4
4

TYPICAL PIPING AND WIRING

566D/E150-240
50TFQ004-012
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

LEGEND
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.

Rooftop Installation — 566D150-240

57

566D/E150-240
50TFQ004-012

TYPICAL PIPING AND WIRING (cont)

NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

LEGEND
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.

Ground Level Installation — 566D150-240

58

GUIDE SPECIFICATIONS — 566D150-240, 566E150-240
b. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
c. Compressor shall be mounted on spring vibration
isolators with an isolation efficiency of no less
than 95%.
d. Compressor speed shall not exceed 1750 rpm.
e. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
f. Compressor shall include overload protection.
g. Compressor shall be equipped with internal high
discharge temperature protection (566E180 and
240 only).
2. 566E150-240 Units:
a. Compressors shall be of the hermetic scroll type.
b. Compressors shall be mounted on vibration
isolators.
c. Compressors shall include overload protection.
d. Compressors shall be equipped with a crankcase
heater.
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for integral subcooler.
2. Coil shall be constructed of aluminum fins mechanically bonded to copper tubes which are then
cleaned, dehydrated, and sealed. Copper fins shall
be available as an option.
F. Refrigeration Components:
1. Refrigeration circuit components for 566D units shall
include hot gas muffler, high-side pressure relief
device, liquid line shutoff valve, suction and discharge shutoff valves, holding charge of refrigerant
R-22, and compressor oil.
2. Refrigeration circuit components for 566E units shall
include liquid line service valve, suction line service
valve, a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Compressor cycle delay protection prevents the
compressor from restarting for a minimum of
5 minutes after shutdown.
c. Capacity control on the compressor shall be by
suction cutoff unloader in response to compressor suction pressure. Electric solenoid unloading
shall be available as an accessory (566D unit).
d. Head pressure control by fan cycling. One condenser fan shall be cycled by discharge pressure
to maintain proper head pressure.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat)
a. High discharge-pressure cutout.
b. Low suction pressure cutout.
c. Condenser-fan motors to be protected against
overload condition by internal overloads.

59

566D/E150-240
50TFQ004-012

COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 121/2 TO 20 TONS, NOMINAL
BRYANT MODEL NUMBER: 566D, SIZES 150-240
566E, SIZES 150-240
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
semi-hermetic reciprocating compressor (566D) or scroll
compressor (566E), an air-cooled coil, propeller-type condenser fans, and a control box. Unit shall discharge supply
air upward as shown on contract drawings. Unit shall be
used in a refrigeration circuit to match a packaged fan coil
unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI latest revisions
and shall be certified and listed in the latest ARI directory.
B. Unit shall be manufactured in a facility registered to ISO
9001:2000 manufacturing quality standard.
C. Unit construction shall comply with latest edition of ANSI/
ASHRAE and with NEC.
D. Unit shall be constructed in accordance with UL
standards and shall carry the UL and UL, Canada label.
E. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
F. Air-cooled condenser coils shall be leak tested at
150 psig and pressure tested at 480 psig.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as a single package only, and
shall be stored and handled per manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-90 galvanized
steel, bonderized and coated with a prepainted, baked
enamel finish.
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser-fan motor no. 1 shall be ball bearing type
compatible with accessory low-ambient control.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. 566D150-240 Units:
a. Compressor shall be serviceable, reciprocating,
semi-hermetic type.

566D/E150-240
50TFQ004-012

GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)
Manual reset at the unit
Electrical overload protection through the use of definite-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers. Circuit
breakers shall open all 3 phases in the event of an
overload in any one of the phases or a single-phase
condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed_____Btuh at a suction temperature of_____ F.
The power consumption at full load shall not
exceed_____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cooling capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
3. The system shall have an EER of _____ Btuh/Watt or
greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of _____ v to _____ v.
2. Unit electrical power shall be single point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control, with capacity to operate an indoor fan
interlock.
J. Special Features:
1. Low-Ambient Temperature Control (Factory-Installed
Option or Field-Installed Accessory):
Control shall regulate fan motor speed in response
to the saturated condensing temperature of the unit.
The control shall allow the unit to operate down to an
ambient temperature of –20 F.
2. Electric Solenoid Unloader Accessory:
Unloader valve piston, coil, and hardware shall be
supplied to convert the pressure-operated compressor unloader to electric unloading.
3. Hail Guard Package:
Hail guard package shall protect coil against hail and
other flying debris.
4. Condenser Coil Grille Package:
Grilles shall protect the condenser coils after unit
installation.
5. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin
and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.

b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating uniformly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A and
cross hatch adhesion of 4B-5B per ASTM D335993. Impact resistance shall be up to 160 in./lb
(ASTM D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be
confirmed through testing to no less than 1000
hours salt spray per ASTM B117-90. Coil construction shall be aluminum-fins mechanically
bonded to copper tubes.
6. Thermostat Control Accessory:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
b. Commercial Electronic Non-programmable Thermostat with auto-changeover, multi-stage capability, and large LCD temperature display.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
8. Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate convenience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from outside the unit.

60

MODEL NUMBER NOMENCLATURE
524A

P

B

120

000

GC
Factory-Installed Options
GC — Unpainted, Standard Motor
and Standard Drive
HC — Unpainted, Standard Motor
and Medium-Static Drive
(not available for 300 sizes)
TC — Unpainted, Alternate Motor
and Medium-Static Drive
(300 size only)
YC — Unpainted, Alternate Motor
and High-Static Drive*
ED — Painted, Standard Motor
and Standard Drive
FD — Painted, Standard Motor
and Medium-Static Drive
(not available for 300 size)
RD — Painted, Alternate Motor
and Medium-Static Drive
(300 size only)
WD — Painted, Alternate Motor
and High-Static Drive*

524A — Fan Coil
Voltage
E — 460-3-60†
J — 208/230-1-60 (Sizes 072, 090 Only)
P — 208/230-3-60
T — 575-3-60
Coil Option
B — DX Cooling Coil With TXVs
C — DX High Capacity Cooling Coil With TXVs
Nominal Cooling (Tons)
072 — 6
090 — 7-1/2
120 — 10
150 — 12-1/2
180 — 15
240 — 20
300 — 25
Nominal Heating (Btuh)
000 – Not applicable (524A-B and 524A-C Cooling-Only Units)

Quality Assurance
Certified to ISO 9001:2000

LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*The YC and WD option codes for all 090 size units with 208/230-1-60 voltage designate standard motor and high-static drive.
†All 524A072-150 units with an “E” voltage designation are triple voltage (i.e., 208/230/460-3-60). Size 524A180 is also triple voltage in the “E” configuration unless the alternate motor (YC or WD) option is used.

524A072-300
50TFQ004-012

61

PHYSICAL DATA
524A-B,C UNITS
UNIT 524A
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV (3 Row/4 Row)
Plenum
Economizer
Hot Water Coil
Steam Coil
FANS
Qty...Diam. (in.)
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)*
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
Motor Speed (rpm)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
REFRIGERANT
Operating charge (lb)
(approx per circuit)†
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
No. of Splits
Split Type...Percentage
No. of Circuits per Split (3 Row/4 Row)
Fins/in.
STEAM COIL
Max Working Pressure (psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
Water Volume
(gal)
(ft3)
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
FILTERS
Quantity...Size (in.)

072
6

090
71/2

120
10

150
121/2

180
15

240
20

300
25

381/399
175
185
195
215

385/404
175
185
195
215

405/425
175
185
195
215

670/695
225
340
285
340

685/713
225
340
285
340

690/730
225
340
285
340

1020/1050
325
340
345
405

1...15
2400
1800-3000

1...15
3000
2250-3750

1...15
4000
3000-5000

2...15
5000
3750-6250

2...15
6000
4500-7500

2...15
8000
6000-10,000

2...18
10,000
7500-12,500

1.3
2.4
1.0

2.4
2.4
2.0

—
2.4
2.0

—
2.9
3.0

—
3.7
3.0

—
5.0
5.0

—
7.5
7.5

1725
1725
1725

1725
1725
1725

—
1725
1725

—
1725
1725

—
1745
1745

—
1745
1755

3.0

3.0

6.67
1
—
12/12
15

8.33
1
—
15/15
15

6.67
1...9

6.67
1...9

6.67
1...9

175
13.33
1...10

13.33
1...10

13.33
1...10

15.0
1...10

6.67
2...8.5

6.67
2...8.5

6.67
2...8.5

150
13.33
2...8.5

13.33
2...8.5

13.33
2...8.5

15.0
2...12.5

—
1725
1725
R-22

1.5/1.5
2.0/2.0
2.5/2.5
3.5/3.5
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
10.01
13.25
17.67
19.88
2
2
2
2
Face...50/50
9/9
9/12
12/16
13/18
17
15
15
17

8.3
1.1

1...11/8

13.9
1.85

1...11/8
1...5/8
1...21/2
1...11/2
1...11/2
1...11/2

2...11/8

2...11/8

2...11/8
2...5/8
1...21/2
1...11/2

4.5/4.5

24.86
2
15/20
15

14.3
1.90

2...1 1/8

1...11/2
1...11/2

4...16 x 24 x 2

Access Location
LEGEND

DX — Direct Expansion
TXV — Thermostatic Expansion Valve

524A072-300
50TFQ004-012

*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.
†Units are shipped without refrigerant charge.

62

1...2
1...2
1...11/4 ODM/1 IDF
Throwaway — Factory Supplied
4...16 x 20 x 2
4...16 x 24 x 2
Right or Left Side

2...13/8

4...20 x 24 x 2
4...20 x 25 x 2

DIMENSIONS

UNIT
524A-B072
524A-B090
524A-B120
524A-C072
524A-C090
524A-C120

UNIT WEIGHT
(lb)
381
385
405
399
404
425

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

524A-B,C072-120

63

524A072-300
50TFQ004-012

3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.

DIMENSIONS (cont)
.

UNIT
524A
B150
B180
B240
C150
C180
C240

UNIT
WEIGHT
(lb)
670
685
690
695
713
730

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

524A072-300
50TFQ004-012

3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.

524A-B,C150-240

64

DIMENSIONS (cont)

UNIT
524A

CONTROL BOX

B300
C300

ALTERNATE
ACCESS
FOR FILTERS

UNIT
WEIGHT
(lb)
1020
1050

ALTERNATE
ACCESS FOR
MOTOR/BELT

RETURN AIR
OPENING

CONTROL BOX

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

3. Recommended clearance:
• Rear: 3″ (76.2 mm) (2′-6″ [762 mm]
with electric heat accessory)
• Front: 2′-6″ (762 mm)
• Right Side: 2′-6″ (762 mm)
• Left Side: 2′-6″ (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.

65

524A072-300
50TFQ004-012

524A-B,C300

PERFORMANCE DATA
524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP
UNIT
524A-B

AIRFLOW
(Cfm)

0.0

EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
0.60
548
0.35
634
0.47
713
583
0.46
660
0.59
733
0.73
622
0.60
693
0.74
760
0.89
663
0.78
730
0.93
792
1.09
707
0.99
770
1.15
828
1.32

072

1,800
2,100
2,400
2,700
3,000

Rpm
399
446
498
544
594

Bhp
0.19
0.28
0.40
0.55
0.73

0.2
Rpm
Bhp
454
0.24
497
0.34
541
0.47
588
0.63
635
0.82

090

2,250
2,600
3,000
3,400
3,750

273
322
552
615
671

0.08
0.15
0.65
0.91
1.20

493
540
595
653
706

0.37
0.52
0.73
1.01
1.31

580
622
673
726
773

0.49
0.66
0.91
1.21
1.53

656
693
740
789
834

0.62
0.81
1.07
1.40
1.74

727
757
800
846
889

120

3,000
3,500
4,000
4,500
5,000

399
604
680
756
834

0.29
0.92
1.33
1.86
2.51

573
641
713
787
861

0.69
1.02
1.45
1.99
2.67

654
714
778
845
914

0.86
1.22
1.68
2.26
2.96

722
780
839
901
966

1.03
1.42
1.91
2.52
3.25

150

3,750
4,300
5,000
5,700
6,250

394
436
492
550
596

0.40
0.57
0.86
1.23
1.59

453
487
535
587
630

0.52
0.70
0.99
1.37
1.74

558
586
623
664
700

0.80
1.00
1.31
1.71
2.09

643
670
704
740
770

180

4,500
5,300
6,000
6,800
7,500

428
488
542
604
660

0.59
0.92
1.29
1.83
2.42

475
528
578
637
690

0.70
1.04
1.43
1.99
2.59

570
609
649
700
747

0.99
1.34
1.74
2.32
2.95

240

6,000
7,000
8,000
9,000
10,000

532
608
686
764
843

1.25
1.93
2.83
3.97
5.38

569
641
716
791
868

1.39
2.09
3.01
4.18
5.62

639
702
770
841
914

300

7,500
8,750
10,000
11,250
12,500

456
521
587
653
720

1.29
1.98
2.88
4.03
5.46

490
551
614
678
743

1.47
2.18
3.11
4.29
5.75

556
608
664
724
785

1.0

1.2

Rpm
785
802
824
851
883

Bhp
0.74
0.88
1.05
1.26
1.50

Rpm
850
867
885
909
937

Bhp
0.89
1.05
1.22
1.44
1.69

0.76
0.96
1.24
1.59
1.95

794
819
856
899
940

0.92
1.12
1.41
1.78
2.16

858
878
910
950
988

1.08
1.29
1.60
1.97
2.37

784
838
896
955
1180

1.19
1.61
2.14
2.78
3.54

841
892
947
1005
1064

1.37
1.81
2.36
3.03
3.82

896
942
995
1051
1109

1.55
2.01
2.58
3.28
4.11

1.10
1.34
1.69
2.11
2.51

717
742
775
809
837

1.39
1.67
2.08
2.55
2.97

785
806
838
872
899

1.71
2.01
2.47
2.99
3.45

848
867
896
929
955

2.04
2.36
2.86
3.43
3.94

656
689
721
763
804

1.33
1.71
2.11
2.70
3.34

730
762
791
826
861

1.68
2.11
2.55
3.15
3.79

796
827
855
888
919

2.02
2.51
3.00
3.64
4.29

856
886
914
946
975

2.38
2.92
3.46
4.15
4.83

1.69
2.42
3.38
4.59
6.09

711
763
823
888
957

2.06
2.80
3.77
5.02
6.55

781
824
876
935
1000

2.48
3.23
4.21
5.47
7.02

846
885
930
982
1042

2.93
3.71
4.70
5.96
7.53

905
943
983
1030
1084

3.39
4.23
5.24
6.51
8.08

1.85
2.61
3.59
4.82
6.33

621
664
714
768
825

2.25
3.07
4.09
5.37
6.93

678
720
763
812
865

2.64
3.53
4.62
5.95
7.55

729
770
812
856
904

3.06
3.99
5.15
6.54
8.20

778
816
857
899
944

3.60
4.45
5.68
7.14
8.86

524A072-300
50TFQ004-012

See Legend and Notes on page 67.

66

PERFORMANCE DATA (cont)
524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP
UNIT
524A-B

AIRFLOW
(Cfm)

1.4

1.6

EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
Rpm
Bhp
Rpm
Bhp
1180
1.36
1065
1.52
1035
1.56
1084
1.74
1052
1.78
1101
1.98
1069
2.03
1118
2.24
1089
2.31
1136
2.53

072

1,800
2,100
2,400
2,700
3,000

Rpm
910
927
944
964
989

Bhp
1.04
1.21
1.41
1.63
1.89

Rpm
965
983
999
1018
1039

Bhp
1.20
1.38
1.59
1.82
2.10

090

2,250
2,600
3,000
3,400
3,750

918
936
963
998
1360

1.26
1.48
1.79
2.18
2.58

975
991
1150
1045
1078

1.43
1.67
1.99
2.39
2.80

1029
1044
1064
1092
1122

1.62
1.87
2.20
2.61
3.03

1079
1094
1113
1137
1164

120

3,000
3,500
4,000
4,500
5,000

949
990
1040
1094
1151

1.74
2.21
2.80
3.53
4.39

1000
1037
1084
1136
1191

1.93
2.42
3.03
3.78
4.66

1050
1083
1126
1176
—

2.14
2.64
3.26
4.03
—

150

3,750
4,300
5,000
5,700
6,250

909
925
950
981
1072

2.37
2.73
3.26
3.88
4.42

968
980
1002
1031
1057

2.74
3.11
3.67
4.33
4.91

1026
1360
1052
1079
1103

180

4,500
5,300
6,000
6,800
7,500

912
940
968
1000
1300

2.75
3.33
3.92
4.67
5.39

967
992
1018
1050
1078

3.13
3.75
4.38
5.19
5.97

240

6,000
7,000
8,000
9,000
10,000

954
990
1300
1073
1126

3.83
4.74
5.79
7.11
8.75

1005
1040
1078
1120
1166

300

7,500
8,750
10,000
11,250
12,500

831
859
900
941
984

4.41
4.97
6.20
7.73
9.53

870
901
939
980
1022

2.2

2.4

Rpm
1111
1131
1149
1165
1183

Bhp
1.69
1.92
2.18
2.45
2.76

Rpm
1155
1175
1193
—
—

Bhp
1.86
2.11
2.38
—
—

1.80
2.07
2.42
2.83
3.27

1126
1142
1159
1182
—

1.99
2.28
2.64
3.07
—

1172
1188
—
—
—

2.18
2.49
—
—
—

1099
1128
1167
—
—

2.36
2.86
3.50
—
—

1147
1172
—
—
—

2.58
3.10
—
—
—

1192
—
—
—
—

2.81
—
—
—
—

3.12
3.52
4.09
4.79
5.40

1080
1084
1101
1125
1148

3.51
3.92
4.53
5.25
5.90

1131
1135
1148
1169
1191

3.92
4.35
4.98
5.73
6.40

1181
1184
1190
—
—

4.32
4.78
5.44
—
—

1019
1041
1066
1097
1125

3.52
4.18
4.85
5.71
6.54

1070
1088
1112
1142
1170

3.92
4.61
5.32
6.23
7.11

1120
1134
1156
1185
—

4.35
5.06
5.80
6.76
—

1168
1179
1198
—
—

4.79
5.52
6.29
—
—

4.27
5.24
6.38
7.72
9.37

1052
1090
1130
1169
—

4.72
5.80
7.00
8.37
—

1098
1135
1173
—
—

5.22
6.30
7.60
—
—

1142
1176
—
—
—

5.67
6.84
—
—
—

—
—
—
—
—

—
—
—
—
—

5.10
5.59
6.74
8.32
10.19

913
944
976
1017
1058

5.90
6.42
7.33
8.90
10.84

950
980
1013
1052
1093

6.88
7.20
8.00
9.51
11.49

985
1020
1050
1086
—

7.70
8.10
8.82
10.16
—

—
—
—
—
—

—
—
—
—
—

NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.

LEGEND
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure

Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.

524A072-300
50TFQ004-012

67

PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —
0.0-1.2 in. wg ESP
UNIT
524A-C
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

0.0

EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8

0.2

1.0

1.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

072

1,800
2,100
2,400
2,700
3,000

419
471
524
578
633

0.21
0.31
0.44
0.61
0.81

471
519
568
619
671

0.26
0.37
0.51
0.69
0.90

564
602
645
690
738

0.37
0.49
0.64
0.84
1.07

649
679
715
755
799

0.49
0.62
0.79
0.99
1.24

727
751
781
816
856

0.63
0.77
0.94
1.15
1.41

797
819
844
875
910

0.77
0.92
1.11
1.33
1.60

862
882
905
932
963

0.92
1.09
1.28
1.51
1.79

090

2,250
2,600
3,000
3,400
3,750

290
349
579
646
705

0.10
0.19
0.70
0.99
1.31

510
561
621
683
739

0.39
0.55
0.79
1.09
1.42

594
640
695
752
804

0.51
0.70
0.96
1.29
1.63

669
709
759
813
862

0.65
0.84
1.12
1.48
1.85

739
773
818
869
915

0.79
1.00
1.30
1.67
2.05

806
834
874
920
964

0.95
1.16
1.47
1.86
2.26

870
893
928
970
1011

1.12
1.34
1.66
2.06
2.48

120

3,000
3,500
4,000
4,500
5,000

421
626
706
786
867

0.35
0.98
1.42
1.99
2.70

592
664
738
815
893

0.73
1.08
1.54
2.12
2.84

670
735
803
873
946

0.90
1.28
1.77
2.39
3.14

737
798
862
929
997

1.06
1.48
2.00
2.65
3.43

797
855
917
980
1046

1.23
1.67
2.23
2.90
3.72

854
908
967
1300
1092

1.41
1.87
2.45
3.16
4.00

908
958
1150
1073
1135

1.59
2.07
2.67
3.41
4.28

150

3,750
4,300
5,000
5,700
6,250

410
455
514
575
624

0.43
0.62
0.92
1.32
1.71

467
504
556
612
657

0.55
0.74
1.06
1.47
1.87

567
599
641
686
725

0.83
1.05
1.39
1.82
2.24

649
679
718
759
793

1.12
1.38
1.76
2.23
2.66

721
748
786
825
856

1.41
1.70
2.14
2.66
3.12

788
811
847
884
915

1.72
2.04
2.52
3.09
3.59

851
871
903
939
969

2.05
2.39
2.91
3.52
4.06

180

4,500
5,300
6,000
6,800
7,500

437
499
555
620
677

0.61
0.95
1.34
1.91
2.52

483
538
590
651
706

0.72
1.07
1.48
2.06
2.69

576
617
659
712
761

1.01
1.37
1.79
2.39
3.04

660
696
730
774
817

1.35
1.74
2.17
2.78
3.44

732
767
798
836
873

1.69
2.13
2.59
3.22
3.89

797
830
860
896
929

2.03
2.53
3.04
3.71
4.39

856
888
918
952
984

2.38
2.94
3.49
4.21
4.93

240

6,000
7,000
8,000
9,000
10,000

542
620
700
781
862

1.29
1.99
2.92
4.10
5.56

577
652
728
806
885

1.42
2.15
3.10
4.30
5.79

646
711
781
854
929

1.72
2.48
3.46
4.71
6.24

716
771
833
900
971

2.09
2.85
3.85
5.13
6.70

785
831
885
946
1120

2.51
3.28
4.29
5.58
7.18

849
890
938
993
1054

2.95
3.76
4.78
6.08
7.69

907
947
990
1039
1096

3.40
4.27
5.32
6.62
8.24

300

7,500
8,750
10,000
11,250
12,500

476
545
615
685
756

1.39
2.14
3.12
4.37
5.92

510
574
641
709
778

1.58
2.35
3.36
4.64
6.22

579
633
692
754
819

1.99
2.81
3.87
5.20
6.83

644
691
743
800
860

2.40
3.29
4.41
5.79
7.47

701
747
794
845
901

2.81
3.77
4.96
6.40
8.14

752
797
843
891
942

3.29
4.25
5.51
7.02
8.83

804
842
888
935
983

3.96
4.76
6.05
7.64
9.52

524A072-300
50TFQ004-012

See Legend and Notes on page 69.

68

PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C
WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP
UNIT
524A-C
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

1.4

EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0

1.6

2.2

2.4

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

072

1,800
2,100
2,400
2,700
3,000

921
942
963
987
1015

1.07
1.26
1.47
1.71
1.99

975
997
1017
1039
1065

1.23
1.43
1.66
1.91
2.20

1026
1048
1069
1090
1113

1.39
1.61
1.85
2.12
2.42

1074
1097
1118
1138
1161

1.55
1.79
2.05
2.33
2.65

1120
1143
1164
1185
—

1.72
1.97
2.25
2.55
—

1164
1186
—
—
—

1.90
2.16
—
—
—

090

2,250
2,600
3,000
3,400
3,750

930
950
980
1018
1057

1.29
1.53
1.86
2.26
2.69

986
1005
1031
1065
1101

1.47
1.72
2.06
2.48
2.92

1039
1057
1081
1111
1144

1.65
1.92
2.27
2.70
3.15

1089
1107
1129
1156
1186

1.84
2.13
2.49
2.93
3.39

1136
1154
1175
—
—

2.03
2.33
2.72
—
—

1181
—
—
—
—

2.22
—
—
—
—

120

3,000
3,500
4,000
4,500
5,000

961
1005
1058
1116
1176

1.78
2.27
2.90
3.66
4.56

1120
1052
1101
1157
—

1.98
2.49
3.13
3.91
—

1062
1098
1143
1196
—

2.19
2.71
3.36
4.16
—

1111
1142
1184
—
—

2.41
2.94
3.60
—
—

1158
1186
—
—
—

2.64
3.18
—
—
—

—
—
—
—
—

—
—
—
—
—

150

3,750
4,300
5,000
5,700
6,250

912
928
956
990
1019

2.39
2.75
3.30
3.96
4.54

971
982
1072
1039
1067

2.76
3.13
3.71
4.40
5.02

1300
1036
1056
1086
1112

3.14
3.53
4.13
4.85
5.50

1083
1087
1104
1130
1156

3.54
3.94
4.56
5.31
5.99

1135
1138
1151
1174
1198

3.95
4.37
5.00
5.78
6.49

1185
1187
1196
—
—

4.36
4.81
5.46
—
—

180

4,500
5,300
6,000
6,800
7,500

912
942
971
1005
1036

2.75
3.34
3.95
4.72
5.48

967
992
1020
1054
1084

3.12
3.76
4.40
5.23
6.04

1019
1041
1067
1101
1131

3.52
4.18
4.86
5.75
6.61

1070
1088
1112
1145
1174

3.92
4.61
5.33
6.27
7.17

1120
1134
1156
1187
—

4.35
5.06
5.81
6.79
—

1168
1179
1198
—
—

4.79
5.52
6.29
—
—

240

6,000
7,000
8,000
9,000
10,000

961
1000
1041
1086
1138

3.86
4.79
5.88
7.21
8.83

1011
1050
1090
1133
1240

4.31
5.32
6.47
7.82
9.46

1058
1097
1137
1178
—

4.77
5.85
7.07
8.47
—

1104
1142
1181
—
—

5.24
6.38
7.67
—
—

1147
1184
—
—
—

5.71
6.91
—
—
—

—
—
—
—
—

—
—
—
—
—

300

7,500
8,750
10,000
11,250
12,500

874
886
930
976
1023

5.33
5.36
6.60
8.25
10.20

897
930
969
1150
1061

5.91
6.13
7.20
8.86
10.88

940
982
1072
1051
1097

6.80
7.32
7.89
9.49
11.56

990
1020
1045
1086
—

7.50
8.10
8.71
10.17
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

LEGEND
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure

NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.

Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.

524A072-300
50TFQ004-012

69

PERFORMANCE DATA (cont)
FACTORY-SUPPLIED FILTER PRESSURE DROP
UNIT
524A-B
524A-C
072
090
120
150
180
240
300

ACCESSORY PLENUM AIR THROW DATA

AIRFLOW
(Cfm)

PRESSURE DROP
(in. wg)

UNIT
524A

AIRFLOW
(Cfm)

1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500

0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30

072
090
102
120
150
180
240
300

2,400
3,000
3,400
4,000
5,000
6,000
8,000
10,000

VANE DEFLECTION
Straight
39
45
49
55
45
50
60
76

21½°
33
38
41
46
38
43
51
65

45°
24
28
30
33
28
31
37
47

Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X 1.50
X 0.75
X 0.50

ACCESSORY PRESSURE DROP (in. wg)
UNIT
524A
072
090
102
120
150
180
240

DISCHARGE
PLENUM

RETURN AIR
GRILLE

1,800
2,400
3,000
2,250
3,000
3,750
2,550
3,400
4,250
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500

0.06
0.10
0.14
0.09
0.14
0.21
0.11
0.17
0.24
0.14
0.22
0.32
0.07
0.12
0.17
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34

0.01
0.01
0.02
0.01
0.02
0.03
0.02
0.03
0.04
0.02
0.04
0.06
0.01
0.02
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05

HEATING COILS
Hot Water
Steam
0.10
0.10
0.16
0.16
0.23
0.23
0.15
0.15
0.23
0.23
0.35
0.35
0.18
0.18
0.28
0.28
0.41
0.41
0.23
0.23
0.37
0.37
0.53
0.53
0.11
0.11
0.17
0.17
0.25
0.25
0.15
0.15
0.23
0.23
0.33
0.33
0.23
0.23
0.37
0.37
0.53
0.53
0.28
0.28
0.44
0.44
0.63
0.63

524A072-300
50TFQ004-012

300

AIRFLOW
(Cfm)

70

Electric
0.04
0.06
0.10
0.06
0.10
0.15
0.07
0.12
0.19
0.10
0.17
0.26
0.04
0.07
0.11
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24

ECONOMIZER
0.05
0.07
0.09
0.06
0.09
0.15
0.07
0.13
0.19
0.09
0.17
0.28
0.05
0.07
0.11
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14

PERFORMANCE DATA (cont)
HYDRONIC HEATING CAPACITIES
UNIT
524A-B
524A-C

AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500

072
090
120
150
180
240
300

1-ROW
STEAM*
Cap.

Ldb

Cap.

146
173
209
168
209
240
209
243
279
370
425
465
402
458
479
458
487
499
511
575
626

134
126
123
129
123
117
123
115
111
150
137
128
141
129
118
129
115
105
122
112
106

156.0
183.0
206.0
174.0
206.0
238.0
299.0
275.0
316.0
362.0
409.0
456.0
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0

LEGEND
Cap. — Capacity (Btuh in thousands)
Lab — Leaving-Air Dry-Bulb Temp (F)
PD — Pressure Drop (ft water)

2-ROW
HOT WATER COIL†
Water
Ldb
Flow
(Gpm)
15.6
140
18.3
131
20.6
124
133
17.4
124
20.6
118
23.8
152
29.9
124
27.5
119
31.6
149
36.2
136
40.9
128
45.6
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2

PD
3.4
4.3
5.2
4.0
5.2
6.5
5.0
6.6
8.2
4.2
5.1
6.0
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5

NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.
Capacity (Btuh)
2. Leaving db = ent db (F) +
1.1 x cfm
3. See Heating Correction Factors table.

*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
†Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.

HEATING CORRECTION FACTORS
HOT WATER COIL
Water Temp
Drop
(F)
10

20

30

Ent Water
Temp
(F)
140
160
240
200
220
140
160
240
200
220
140
160
240
200
220

Entering-Air Temp (F)
40

50

60

70

80

0.72
0.89
1.06
1.22
1.39
0.64
0.81
0.98
1.15
1.32
0.56
0.74
0.91
1.08
1.25

0.64
0.81
0.98
1.15
1.32
0.57
0.74
0.91
1.08
1.25
0.49
0.66
0.83
1.00
1.18

0.57
0.74
0.90
1.07
1.24
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.76
0.93
1.10

0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.75
0.93
1.10
0.33
0.51
0.68
0.85
1.03

0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95

STEAM COIL
Steam Pressure
(psig)
0
2
5

40
1.06
1.09
1.13

50
0.98
1.02
1.06

Entering-Air Temp (F)
60
0.91
0.95
1.00

70
0.85
0.89
0.93

80
0.78
0.82
0.87

NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually
operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.

524A072-300
50TFQ004-012

71

ELECTRICAL DATA
524A-B,C STANDARD MOTORS
UNIT
524A-B
524A-C

072

090

120

150

180

240

300

FAN MOTOR

V*-PH-Hz

VOLTAGE
LIMITS

Hp (kW)

FLA

208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60

187-253
187-253
414-506
518-632
187-253
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632

1.3 (0.97)
2.4 (1.79)
2.4 (1.79)
1.0 (0.75)
2.4 (1.79)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.4 (1.79)
2.4 (1.79)
2.0 (1.49)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)

7.6
5.2
2.6
1.4
11.0
5.2
2.6
2.3
5.2
2.6
2.3
7.5
3.4
3.8
10.2
4.8
3.8
14.6/12.8
6.4
5.1
21.5/19.4
9.7
7.8

524A072-300
50TFQ004-012

See Legend and Notes on page 73.

72

POWER SUPPLY
Minimum Circuit
Amps
9.5
6.5
3.3
1.8
13.8
6.5
3.3
2.9
6.5
3.3
2.9
9.4
4.3
4.8
12.8
6.0
4.8
18.3/16.0
8.0
6.4
26.9/24.3
12.1
9.8

MOCP
15
15
15
15
20
15
15
15
15
15
15
15
15
15
20
15
15
30/25
15
15
45/40
20
15

ELECTRICAL DATA (cont)
524A-B,C ALTERNATE MOTORS
UNIT
524A-B
524A-C
072

090

120

150

180

240

300

FAN MOTOR

V*-PH-Hz

VOLTAGE
LIMITS

Hp (kW)

FLA

208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60

187-253
187-253
414-506
518-632
187-253
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632
187-253
414-506
518-632

2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
2.0 (1.49)
2.4 (1.79)
2.9 (2.16)
2.9 (2.16)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
3.0 (2.24)
3.7 (2.76)
3.7 (2.76)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
5.0 (3.73)
7.5 (5.59)
7.5 (5.59)
7.5 (5.59)
10.0 (7.46)
10.0 (7.46)
10.0 (7.46)

11.0
7.5
3.4
2.3
11.0
7.5
3.4
3.8
10.2
4.8
3.8
10.2
4.8
5.1
14.6/12.8
6.4
5.1
21.5/19.4
9.7
7.8
28.2/26.8
13.4
10.3

POWER SUPPLY
Minimum Circuit
Amps
13.8
9.4
4.3
2.9
13.8
9.4
4.3
4.8
12.8
6.0
4.8
12.7
6.0
6.4
18.3/16.0
8.0
6.4
26.9/24.3
12.1
9.8
35.3/33.5
16.8
12.9

LEGEND
FLA
— Full Load Amps
MOCP — Maximum Overcurrent Protection

Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v

*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.

Maximum deviation is 6 v.

MOCP
20
15
15
15
15
15
15
15
20
15
15
20
15
15
30/25
15
15
45/40
20
15
60/60
30
20

Determine percent of voltage imbalance.
6

% Voltage Imbalance = 100 x 397
= 1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in
accordance with NEC (National Electrical Code) Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Example: Supply voltage is 460-3-60.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
3
1192
=
3

Average Voltage =

= 397

524A072-300
50TFQ004-012

73

ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA
HEATER PART NO.

UNIT

V-PH-Hz

208-3-60
CAELHEAT001A00
240-3-60

CAELHEAT002A00

480-3-60

CAELHEAT003A00

575-3-60

208-3-60
CAELHEAT004A00
524A-B072-120
524A-C072-120

240-3-60

CAELHEAT005A00

480-3-60

CAELHEAT006A00

575-3-60

208-3-60
CAELHEAT007A00
240-3-60

CAELHEAT008A00

480-3-60

CAELHEAT009A00

575-3-60

FAN MOTOR
Hp
1.3†
2.4†
2.4
2.9
3.7
1.3†
2.4†
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3†
2.4†
2.4
2.9
3.7
1.3†
2.4†
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
1.3†
2.4†
2.4
2.9
3.7
1.3†
2.4†
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0

kW
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24

FLA
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8

524A072-300
50TFQ004-012

See Legend and Notes on page 75.

74

ELECTRIC HEATER(S)
Nominal
Actual Capacity (kW)
Capacity (kW) Stage 1 Stage 2 Total
5
3.8
—
3.8
5
3.8
—
3.8
5
3.8
—
3.8
5
3.8
—
3.8
5
3.8
—
3.8
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
5
5.0
—
5.0
10
7.5
—
7.5
10
7.5
—
7.5
10
7.5
—
7.5
10
7.5
—
7.5
10
7.5
—
7.5
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
10
10.0
—
10.0
15
11.3
—
11.3
15
11.3
—
11.3
15
11.3
—
11.3
15
11.3
—
11.3
15
11.3
—
11.3
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0
15
15.0
—
15.0

FLA
10.4
10.4
10.4
10.4
10.4
12.0
12.0
12.0
12.0
12.0
6.00
6.00
6.00
5.00
5.00
5.00
20.8
20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
24.1
12.0
12.0
12.0
10.0
10.0
10.0
31.3
31.3
31.3
31.3
31.3
36.1
36.1
36.1
36.1
36.1
18.0
18.0
18.0
15.1
15.1
15.1

MCA*

MOCP*

22.5
26.8
19.5
22.4
25.8
24.5
28.8
21.5
24.4
27.8
10.8
11.8
13.5
8.0
9.2
11.0
35.6
39.8
32.6
35.4
38.8
39.6
43.8
36.6
39.4
42.8
18.3
19.3
21.0
14.3
15.4
17.3
48.6
52.9
45.6
48.5
51.9
54.6
58.9
51.6
54.5
57.9
25.8
26.8
28.6
20.6
21.7
23.6

25
35
20
25
30
25
35
25
25
30
15
15
15
15
15
15
40
40
35
40
40
40
50
40
40
50
20
20
25
15
20
20
50
60
50
50
60
60
60
60
60
60
30
30
30
25
25
25

ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
HEATER PART NO.

UNIT

V-PH-Hz

208-3-60
CAELHEAT010A00
240-3-60

CAELHEAT011A00
CAELHEAT012A00

480-3-60
524A-B072-120
524A-C072-120

575-3-60

208-3-60
CAELHEAT013A00
240-3-60

CAELHEAT014A00

480-3-60

CAELHEAT015A00

575-3-60

FLA
Hp
MCA
MOCP

—
—
—
—

FAN MOTOR
Hp
1.3†
2.4†
2.4
2.9
3.7
1.3†
2.4†
2.4
2.9
3.7
2.4
2.9
3.7
1.0
2.0
3.0
2.4†
2.4
2.9
3.7
2.4†
2.4
2.9
3.7
2.4
2.9
3.7
2.0
3.0

kW
0.97
1.79
1.79
2.16
2.76
0.97
1.79
1.79
2.16
2.76
1.79
2.16
2.76
0.75
1.49
2.24
1.79
1.79
2.16
2.76
1.79
1.79
2.16
2.76
1.79
2.16
2.76
1.49
2.24

FLA
7.6
11.0
5.2
7.5
10.2
7.6
11.0
5.2
7.5
10.2
2.6
3.4
4.8
1.4
2.3
3.8
11.0
5.2
7.5
10.2
11.0
5.2
7.5
10.2
2.6
3.4
4.8
2.3
3.8

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1 Stage 2 Total
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
11.3
7.5
18.8
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
10.0
25.0
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
15.0
11.3
26.3
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0
20.0
15.0
35.0

Nominal
Capacity (kW)

FLA

25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
35
35
35
35
35
35
35
35
35
35
35
35
35

52.1
52.1
52.1
52.1
52.1
60.1
60.1
60.1
60.1
60.1
30.1
30.1
30.1
25.1
25.1
25.1
73.0
73.0
73.0
73.0
84.2
84.2
84.2
84.2
42.1
42.1
42.1
35.1
35.1

MCA*

MOCP*

74.7
78.9
71.7
74.5
77.9
84.7
88.9
81.7
84.6
87.9
40.8
41.8
43.6
33.1
34.3
36.1
105.0
97.7
100.6
104.0
119.0
111.7
114.6
118.0
55.9
56.9
58.6
46.8
48.7

80
80
80
80
80
90
90
90
90
90
50
50
50
35
35
40
110
100
110
110
125
125
125
125
60
60
60
50
50

2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.

*Values shown are for single-point connection of electric heat accessory and air handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
200
208
230
240 400 440 460 480 550
VOLTAGE
240
0.694 0.751 0.918 1
—
—
— — —
480
—
—
— — 0.694 0.84 0.918 1
—
575
—
—
— — —
—
— — 0.915

575 600
— —
— —
1 1.089

524A072-300
50TFQ004-012

75

ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
HEATER PART NO.

UNIT

V-PH-Hz

208-3-60
CAELHEAT016A00
240-3-60

CAELHEAT017A00

480-3-60

CAELHEAT018A00

575-3-60

208-3-60
CAELHEAT019A00
240-3-60
524A-B150-240
524A-C150-240
CAELHEAT020A00

480-3-60

CAELHEAT021A00

575-3-60

208-3-60
CAELHEAT022A00
240-3-60

CAELHEAT023A00

480-3-60

CAELHEAT024A00

575-3-60

FAN MOTOR
Hp
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
3.0
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
3.0
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
2.9
3.7
5.0
7.5
3.0
5.0
7.5

kW
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.24
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.24
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.16
2.76
3.73
5.59
2.24
3.73
5.59

FLA
7.5
10.2
14.6
21.5
7.5
10.2
12.8
19.4
3.4
4.8
6.4
9.7
3.8
5.1
7.8
7.5
10.2
14.6
21.5
7.5
10.2
12.8
19.4
3.4
4.8
6.4
9.7
3.8
5.1
7.8
7.5
10.2
14.6
21.5
7.5
10.2
12.8
19.4
3.4
4.8
6.4
9.7
3.8
5.1
7.8

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1 Stage 2 Total
7.5
—
7.5
7.5
—
7.5
7.5
—
7.5
7.5
—
7.5
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
10.0
—
10.0
14.9
—
14.9
14.9
—
14.9
14.9
—
14.9
14.9
—
14.9
19.9
—
19.9
19.9
—
19.9
19.9
—
19.9
19.9
—
19.9
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
15.0
7.5
22.5
15.0
7.5
22.5
15.0
7.5
22.5
15.0
7.5
22.5
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0
20.0
10.0
30.0

Nominal
Capacity (kW)

FLA

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

20.8
20.8
20.8
20.8
24.1
24.1
24.1
24.1
12.0
12.0
12.0
12.0
10.0
10.0
10.0
41.5
41.5
41.5
41.5
47.9
47.9
47.9
47.9
24.1
24.1
24.1
24.1
20.1
20.1
20.1
62.5
62.5
62.5
62.5
72.2
72.2
72.2
72.2
36.1
36.1
36.1
36.1
30.1
30.1
30.1

524A072-300
50TFQ004-012

See Legend and Notes on page 77.

76

MCA*

MOCP*

35.4
38.8
41.3
52.9
39.4
42.8
46.1
54.4
19.3
21.0
23.0
27.2
17.3
19.6
22.1
51.2
64.6
70.1
78.7
69.2
72.6
75.8
84.1
34.3
36.1
39.1
43.2
29.9
31.5
34.9
87.5
90.9
96.4
105.0
99.6
103.0
106.2
114.5
49.4
51.1
53.1
57.2
42.4
44.0
47.4

40
40
50
60
40
50
50
60
20
25
25
30
20
20
25
70
70
80
80
70
80
80
80
35
40
40
50
30
35
35
90
100
100
110
100
110
110
125
50
60
60
60
50
50
50

ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
HEATER PART NO.

UNIT

V-PH-Hz

208-3-60
CAELHEAT025A00
240-3-60
524A-B180,240
524A-C180,240
CAELHEAT026A00

480-3-60

CAELHEAT027A00

575-3-60
208-3-60

CAELHEAT028A00
240-3-60
CAELHEAT029A00
CAELHEAT030A00

480-3-60
524A-B300
524A-C300

575-3-60
208-3-60

CAELHEAT031A00
240-3-60
CAELHEAT032A00

480-3-60

CAELHEAT033A00

575-3-60

FLA —
Hp
—
MCA —
MOCP—

FAN MOTOR
Hp
3.7
5.0
7.5
3.7
5.0
7.5
3.7
5.0
7.5
3.0
5.0
7.5
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

kW
2.76
3.73
5.59
2.76
3.73
5.59
2.76
3.73
5.59
2.24
3.73
5.59
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

FLA
10.2
14.6
21.5
10.2
12.8
19.4
4.8
6.4
9.7
3.8
5.1
7.8
19.8
28.2
19.4
26.8
9.7
13.4
7.8
10.3
19.8
28.0
19.4
26.8
9.7
13.4
7.8
10.3

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

FLA

MCA*

MOCP*

50
50
50
50
50
50
50
50
50
50
50
50
20
20
20
20
20
20
20
20
40
40
40
40
40
40
40
40

104.3
104.3
104.3
120.3
120.3
120.3
60.1
60.1
60.1
50.2
50.2
50.2
41.5
41.5
47.9
47.9
24.1
24.1
20.1
20.1
83.4
83.4
96.2
96.2
47.9
47.9
40.2
40.2

143.1
148.6
157.2
163.1
166.4
174.6
81.2
83.2
87.3
67.5
69.1
72.5
78.7
87.1
81.4
93.3
42.2
46.8
34.9
38.0
131.1
139.5
144.5
153.8
71.9
76.6
60.0
63.1

150
150
175
175
175
200
90
90
90
70
70
80
80
100
90
110
50
50
35
40
150
150
150
175
80
80
60
70

2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.

*Values shown are for single-point connection of electric heat accessory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
200
208
230
240 400 440 460 480 550
VOLTAGE
240
0.694 0.751 0.918 1
—
—
— — —
480
—
—
— — 0.694 0.84 0.918 1
—
575
—
—
— — —
—
— — 0.915

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1 Stage 2 Total
22.6
15.0
37.6
22.6
15.0
37.6
22.6
15.0
37.6
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
30.0
20.0
50.0
14.9
—
14.9
14.9
—
14.9
19.9
—
19.9
19.9
—
19.9
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
20.0
—
20.0
15.0
15.0
30.0
15.0
15.0
30.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0
20.0
20.0
40.0

Nominal
Capacity (kW)

575 600
— —
— —
1 1.089

524A072-300
50TFQ004-012

77

ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
HEATER PART NO.

UNIT

V-PH-Hz
208-3-60

CAELHEAT034A00
240-3-60
CAELHEAT035A00
CAELHEAT036A00

480-3-60
524A-B300
524A-C300

575-3-60
208-3-60

CAELHEAT037A00
240-3-60
CAELHEAT038A00

480-3-60

CAELHEAT039A00

575-3-60

FLA
Hp
MCA
MOCP

—
—
—
—

FAN MOTOR
Hp
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

kW
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

FLA
19.8
28.0
19.4
26.8
9.7
13.4
7.8
10.3
19.8
28.0
19.4
26.8
9.7
13.4
7.8
10.3

ELECTRIC HEATER(S)
Actual Capacity (kW)
Nominal Capacity (kW)
Stage 1 Stage 2 Total
50
22.6
15.0
37.6
50
22.6
15.0
37.6
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
50
30.0
20.0
50.0
70
30.0
22.6
52.6
70
30.0
22.6
52.6
70
40.0
30.0
70.0
70
40.0
30.0
70.0
70
40.0
30.0
70.0
70
40.0
30.0
70.0
70
40.0
30.0
70.0
70
40.0
30.0
70.0

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

104.3
104.3
120.3
120.3
60.1
60.1
50.2
50.2
145.9
145.9
168.4
168.4
84.2
84.2
70.3
70.3

MCA* MOCP*
157.2
165.6
174.6
183.9
87.3
91.9
72.5
75.6
172.8
181.2
192.6
201.9
96.3
100.9
80.0
83.2

175
175
200
200
90
100
80
80
175
200
200
225
100
110
90
90

2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.

*Values shown are for single-point connection of electric heat accessory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.

575 600
— —
— —
1 1.089

524A072-300
50TFQ004-012

HEATER
ACTUAL HEATER VOLTAGE
RATING
200
208
230
240 400 440 460 480 550
VOLTAGE
240
0.694 0.751 0.918 1
—
—
— — —
480
—
—
— — 0.694 0.84 0.918 1
—
575
—
—
— — —
—
— — 0.915

FLA

78

APPLICATION DATA — 524A
1. OPERATING LIMITS
Maximum fan speed — 524A-B,C072-240 . . . . . . . .1200 rpm
Maximum fan speed — 524A-B,C300 . . . 1100 rpm (18.3 r/s)
2. GENERAL — Select equipment to match or to be slightly
less than peak load. This provides better humidity control,
less unit cycling, and less part-load operation. Equipment
should be selected to perform at no less than 300 cfm/ton.

The air handler fan must always be operating when the condensing unit is operating.
Ductwork should be sized according to unit size, not building load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can
be used with slight reduction in external static pressure
capability.

FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA
COIL
TYPE

TXV
Qty...Part No.*

DISTRIBUTOR
Qty...Part No.†

3, 4 Row
3, 4 Row
3, 4 Row
3 Row
4 Row
3 Row
4 Row
3 Row
4 Row
3 Row
4 Row

1...TDEBX8
1...TDEBX8
2...TDEX6
2...TDEBX8
2...TDEBX8
2...TDEBX8
2...TDEBX8
2...TDEBX11
2...TDEBX11
2...TDEBX11
2...TDEBX11

1...1116
1...1126
2...1115
2...1115
2...1115
2...1116
2...1126
2...1116
2...1126
2...1126
2...1126

UNIT
524A-B,C 072
524A-B,C 090
524A-B,C 120
524A-B 150
524A-C 150
524A-B 180
524A-C 180
524A-B 240
524A-C 240
524A-B 300
524A-C 300

*Danfoss part numbers shown.
†Sporlan Valve Co. part numbers shown.

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
15...1/4
9...1/4
9...1/4
12...3/16
12...1/4
16...1/4
13...1/4
18...3/16
15...1/4
20...3/16

NOZZLE
Qty...Part No.
1...E5
1...C6
2...E4
2...E5
2...E5
2...E6
2...C6
2...E8
2...C8
2...C10
2...C15

NOTE: Hot gas bypass applications require field-supplied auxiliary side
connector.

FAN MOTOR DATA
STANDARD MOTOR
UNIT SIZE 524A
208/230-1-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
208/230-3-60 and 460-3-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
575-3-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

072

090

120

150

180

240

300

1725
1.3
56Y
5/ 8

1725
2.4
56Y
5/8

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

1725
2.4
56Y
5/ 8

1725
2.4
56Y
5/8

1725
2.4
56Y
5/8

1725
2.9
56Y
7/ 8

1725
3.7
56Y
7/8

1745
5.0
S184T
11/8

1745
7.5
S213T
13/8

1725
1.0
56
5/ 8

1725
2.0
56HZ
7/8

1725
2.0
56HZ
7/8

1725
3.0
56HZ
7/ 8

1725
3.0
56HZ
7/8

1745
5.0
184T
11/8

1755
7.5
S213T
13/8

LEGEND
NEMA — National Electrical Manufacturers Association

524A072-300
50TFQ004-012

79

APPLICATION DATA — 524A (cont)
FAN MOTOR DATA (cont)
ALTERNATE MOTOR
UNIT SIZE 524A
208/230-1-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
230-3-60 and 460-3-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
575-3-60
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

072

090

120

150

180

240

300

1725
2.4
56Y
5/ 8

1725
2.4
56Y
5/ 8

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

1725
2.9
56Y
7/ 8

1725
2.9
56Y
7/ 8

1725
3.7
Y56Y
7/8

1725
3.7
Y56Y
7/ 8

1725
5.0
S184T
11 / 8

1745
7.5
S213T
13 / 8

1745
10.0
S215T
13 / 8

1725
2.0
56HZ
7/ 8

1725
3.0
56HZ
7/ 8

1725
3.0
56HZ
7/8

1745
5.0
184T
11/8

1745
5.0
184T
11 / 8

1755
7.5
S213T
13 / 8

1750
10.0
D215T
13 / 8

LEGEND
NEMA — National Electrical Manufacturers Association

STANDARD DRIVE DATA
UNIT SIZE 524A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Settings
Range
Max Allowable Speed (rpm)
Change per 1/2 turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)

072

090

120

150

180

240

300

2.4-3.4

2.8-3.8

3.4-4.4

2.8-3.8

2.8-3.8

3.7-4.7

4.3-5.3

2.5

2.5

2.5

2.5

2.5

3.0

3.0

8.8
1
1—A

8.8
1
1—A

8.8
1
1—A

9.0
17/16
1—A

9.0
17/16
1—A

9.4
17/16
1—B

40.3

41.3

42.3

42.3

42.3

41.8

11.0
115/16
2—B*
(2) 42.8
(2) 43.8

568
470-666
1200

647
549-745
1200

764
666-863
1200

632
537-728
1200

632
537-728
1200

771
679-863
1200

752
682-841
1100

19.6

19.6

19.7

19.1

19.1

15.3

13.1

5

5

5

5

5

6

6

10.4412.32

10.4412.32

10.4412.32

10.4412.32

10.4412.32

9.1210.99

6.679.43

524A072-300
50TFQ004-012

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

80

APPLICATION DATA — 524A (cont)
MEDIUM-STATIC DRIVE DATA
UNIT SIZE 524A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)

072

090

120

150

180

240

300

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

3.0

3.0

3.0

8.8
1
1—A

8.0
1
1—A

8.0
1
1—A

8.2
17/16
1—A

8.6
17/16
1—B

9.4
17/16
2—B

42.3

40.3

40.3

41.3

41.8

41.8

9.4
115/16
2—B*
(2) 38.8
(2) 39.8

764
666-863
1200

841
733-949
1200

841
733-949
1200

820
715-926
1200

842
742-943
1200

881
798-984
1200

881
798-984
1100

19.7

21.6

21.6

21.1

16.7

15.3

15.3

5

5

5

5

6

6

6

10.4412.32

10.4412.32

10.4412.32

10.4412.32

10.4412.32

9.1610.99

6.679.43

*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

HIGH-STATIC DRIVE DATA
UNIT SIZE 524A
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)

072

090

120

150

180

240

300

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

3.0

3.0

3.0

3.0

7.0
1
1—A
41.3

6.0*
1
1—A
37.3

6.0
1
1—A
37.3

7.4
17/16
1—B
39.8

7.9
17/16
1—B
39.8

7.4
17/16
2—B
36.8

8.6
115/16
2—B
37.8

961
8381084
1200

1121
9781200*†
1200

1121
9781200†
1200

979
8731096
1200

1060
9501171
1200

1118
10141200†
1200

1024
8731075
1100

24.6

28.7

28.7

19.4

18.4

19.4

16.7

5

5

5

6

6

6

6

10.4412.32

10.4412.32

10.4412.32

10.4412.32**

9.1610.99

8.1610.02

6.679.43

*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.

524A072-300
50TFQ004-012

81

524A072-300
50TFQ004-012

GUIDE SPECIFICATIONS — 524A
COMMERCIAL PACKAGED AIR-HANDLING UNIT
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO
25 TONS, NOMINAL COOLING
BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION
COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION
COIL)
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial
split systems. Unit shall have a multiposition design and
shall be capable of horizontal or vertical installation on a
floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refrigerant circuit with a matching air-cooled condensing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigeration,
latest edition.
B. Unit shall be constructed in accordance with ETL and
ETL, Canada, standards and shall carry the ETL and
ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A
requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized
antimicrobial agent to effectively resist the growth of
bacteria and fungi as proven by tests in accordance with
ASTM standards G21 and 22.
D. Unit shall be manufactured in a facility registered to the
ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion coils shall be burst and leak tested at
435 psi.
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s
recommendations.
PART 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configuration
or a vertical configuration. Unit shall consist of forwardcurved belt-driven centrifugal fan(s), motor and drive
assembly, prewired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units),
cooling coil, 2-in. disposable air filters, and condensate
drain pans for vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in.
fire-retardant material. Insulation shall contain an
EPA-registered immobilized antimicrobial agent to
effectively resist the growth of bacteria and fungi as
proven by tests in accordance with ASTM standards
G21 and 22.
3. Unit shall contain non-corroding condensate drain
pans for both vertical and horizontal applications.
Drain pans shall have connections on right and left
sides of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right or
left side of the unit to prevent standing water from
accumulating in pans.

B.

C.

D.

E.

82

4. Unit shall have factory-supplied 2-in. throwaway-type
filters installed upstream from the cooling coil. Filter
access shall be from either the right or left side of the
unit.
Coils:
Coils shall consist of 3 rows (524A-B) or 4 rows (524A-C)
of copper tubes with sine-wave aluminum fins bonded to
the tubes by mechanical expansion. Suction and liquid
line connections or supply and discharge connections
shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory-installed
thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be capable of external
adjustment. Coil tubing shall be internally rifled to
maximize heat transfer.
2. High-Capacity Coil:
The high-capacity 4-row coil consists of 4 rows of
3/8-in. copper tubes with sine-wave aluminum fins
bonded to the tubes by mechanical expansion. Coil
tubing shall be internally rifled to maximize heat
transfer. Suction and liquid line connections shall be
made on the same side of the coil. Direct-expansion
coils shall feature factory-installed thermostatic
expansion valves (TXVs) for refrigerant control. The
TXVs shall be capable of external adjustment.
Operating Characteristics:
cfm airflow at an
Unit shall be capable of providing
external static pressure of
in. wg.
Motor:
Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied
and installed.
Motors rated at 1.3 through 3.7 hp shall have internal
thermal overload protection. Motors rated at 5, 71/2, and
10 hp shall be protected by a circuit breaker.
Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or highstatic drive shall be available to meet the airflow and
external static pressure requirements specified on
the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with
an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes
and aluminum plate fins bonded to the tubes by
mechanical expansion. Coil shall be mounted in a
galvanized steel housing that shall be fastened to the
unit’s fan deck for blow-thru heating operation. Coil
shall have maximum working pressure of 150 psig.
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with
aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be mounted in a galvanized
steel housing and shall be fastened to the unit’s fan
deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260 F.

GUIDE SPECIFICATIONS — 524A (cont)
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase,
60 Hz power supply shall be factory-supplied for field
installation as shown on the equipment drawings.
Electric heat assembly shall be ETL and ETL, Canada, agency approved, and shall have single-point
power wiring. Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring
terminal blocks, and a hinged access panel. Electric
heaters shall not be used with air discharge plenum.
6. Air Discharge Plenum:
Plenum shall be factory supplied to provide free-blow
air distribution for vertical floor-mounted units. A
grille with moveable vanes for horizontal or vertical
airflow adjustment shall be included. Plenum shall
be field-assembled and field-installed on the unit’s
fan deck for blow-thru air distribution. Plenum shall
not be used with electric heaters.
7. Return-Air Grille:
Grille shall be factory supplied for field installation on
the unit’s return air opening.
8. Unit Subbase:
Subbase assembly shall be factory supplied for field
installation. Subbase shall elevate floor-mounted
vertical units to provide access for correct condensate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be
factory provided for field installation on either return
air opening of air handler. For free cooling applications, economizer shall be compatible with separate
thermostat; economizer dampers shall open when
outdoor air enthalpy is suitable for free cooling.
Economizer shall include enthalpy control and
damper actuator. Economizer shall be compatible
with accessory CO2 sensor. Economizer damper
shall open when indoor CO2 level rises above predetermined set point.
A 2 to 10 vdc actuator adapter must be field-supplied
and installed on economizer for demand control ventilation using the CO2 sensor accessory.
10. Thermostat Controls:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
b. Commercial Electronic Non-programmable Thermostat with auto-changeover, multi-stage capacity, and large LCD display.

11. Overhead Suspension Package:
Package shall include necessary brackets to support
units in a horizontal ceiling installation.
12. Condensate Drain Trap:
Trap shall have transparent, serviceable design for
easy cleaning. Kit shall include overflow shutoff
switch and wiring harness for connection to an alarm
if desired.
13. UV-C Germicidal Lamps:
UV-C emitters and fixtures shall be specifically
designed for use inside an HVAC system. An ASME
nozzled test apparatus using a 45 F airstream moving at not less than 400 fpm shall measure individual
lamp output. Lamp output at 253.7 nm shall not be
less than 10µW/cm2 per inch of arc length measured
at a distance of one meter.
a. UV-C power supplies shall be high efficiency,
electric type which are matched to the emitters
and are capable of producing the specified output
intensity with an input power no more than
80 watts.
b. Emitters and fixtures shall be installed in sufficient
quantity and arranged so as to provide an equal
distribution of UV-C energy on the coil and drain
fan.
c. The minimum UV-C energy striking the leading
edge of the coil fins shall be not less than
820 µW/cm2 at the closest point and through
placement, not less than 60% of that value at the
farthest point. Equal amounts are to strike the
drain pan, either directly or indirectly through
reflection.
d. Emitters and fixtures shall be installed at right
angles to the conforming lines of the coil fins,
such that through incident angle reflection, UV-C
energy strikes all target surfaces of the coil, drain
pan, and the available line of sight airstream.
14. CO2 Sensor:
The field-installed CO2 ventilation sensor measures
the amount of ventilation needed by the space and a
proportional integral derivative loop (PID) calculation
makes adjustments to the economizer minimum
position during occupied operation. The indoor CO2
will be compared to an outdoor CO2 reference before
making adjustments to the economizer minimum
position.

524A072-300
50TFQ004-012

83

INDEX
569D/F072-120, 576C120 11-32
566D/E150-240 33-60
524A072-300 61-83
Alternate motors and drives 5, 73, 80, 81
Application data
569D/F072-120, 576C120 27
566D/E150-240 54-56
524A072-300 79-81
ARI capacity ratings 3
CO2 sensor 83
Combination ratings
566D150-240/524A 40-44
566E150-240/524A 45-52
569D072-120/524A 16-21
569F120/524A 24, 25
576C/524A 22, 23
Condenser coil grille 4
Condensing unit ratings 15, 39
Controls 8
Convenience outlet 4
Dimensions
Base unit
569D/F072-120, 576C120 13, 14
566D/E150-240 36-38
524A072-300 63-65
Discharge plenum 5, 6
Dura-Shield options 4
E-coated coils 4
Economizer 5, 6
Electrical data
569D/F072-120, 576C120 26
566D/E150-240 53
524A072-300 72-78
Electric heat 5, 74-78
Fan performance tables
524A072-300 66-69
Features/Benefits 1, 2
Gage panel 4
Guide specifications
569D072-120, 576C120 29, 30
569F120 31, 32
566D/E150-240 59, 60
524A072-300 82, 83
Hail guard 4
Hot water coil 5, 6, 71
Hydronic heat 71
Indoor-air quality (IAQ) 1
Liquid line piping 27, 55
Low ambient controls 4
Maximum temperature 27, 54
Minimum ambient operating
temperature 27, 54
Minimum temperature 27, 54
Model number nomenclature
569D/E072-120, 576C120 11
566D/E150-240 33
524A072-300 61

Motormaster® options 4
Operating sequence 8
Options and accessories 4-6
569D/F, 576C, 566D/E 4
524A 5, 6
Performance data
569D/F072-120, 576C120 15-25
566D/F150-240 39-52
524A072-300 66-71
Physical data
569D/F072-120, 576C120 12
566D/E150-240 34, 35
524A072-300 62
Piping and wiring
569D072-120, 576C120 28
566D150-240 57, 58
Refrigerant charge 27
Refrigerant piping 27, 54, 55
Return-air grille 5, 6
Selection procedure 7
Sound data 3
Static pressure drop
Filter 70
Economizer 70
Heating coil 70
Plenum 70
Steam coil 5, 6, 71
Subbase 5, 6
Thermostat 4, 5
Thermostatic expansion
valve (TXV) 79
Unloader package 4
Unit-mounted non-fused disconnect
UV-C germicidal lamps 5
Wiring 9, 10

4

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS

Copyright 2004 Bryant Heating & Cooling Systems

Printed in U.S.A.

7/04

Catalog No. 5256-904



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 4.0 for Windows
Keywords                        : 
Create Date                     : 2003:06:24 16:43:16Z
Modify Date                     : 2005:11:09 18:47:48-05:00
Metadata Date                   : 2005:11:09 18:47:48-05:00
Creator Tool                    : ADOBEPS4.DRV Version 4.20
Format                          : application/pdf
Creator                         : Carrier Corporation
Title                           : 
Description                     : 
Subject                         : 
Document ID                     : uuid:c1d8bd10-91be-416d-8a9d-2f0305270d5a
Instance ID                     : uuid:e0f0b6c4-a4a9-4519-99ec-847359afe6e9
Page Count                      : 84
Author                          : Carrier Corporation
EXIF Metadata provided by EXIF.tools

Navigation menu