COMMERCIAL AIR-COOLED
CONDENSING UNITS WITH
524A AIR-HANDLING UNITS
FEATURES/BENEFITS
These dependable split systems match Bryant’s indoor-air han-
dlers and direct-expansion coils with outdoor condensing units
for a wide selection of commercial cooling solutions.
CONSTRUCTED FOR LONG LIFE — The569D(singlecir-
cuit, scroll compressor), 576C (single circuit semi-hermetic
compressor), 569F/566E (dual circuit, scroll compressor) and
566D (semi-hermetic compressor) models are designed and
built to last. The copper tube-aluminum fin outdoor coil
construction provides years of trouble-free operation. Where
conditions require them, E-coated coils and pre-coated fin coils
are also available. Cabinets are constructed of prepainted
galvanized steel, delivering unparalleled protection from the
environment. Inside and outside surfaces are protected to
ensure long life, good looks, and reliable operation. Safety con-
trols are used for enhanced system protection and reliability.
EFFICIENT OPERATION — Building owners will appreciate
the high unit EERs (Energy Efficiency Ratios) offered by these
condensing units. These units provide greater efficiency than
similar units in the marketplace, which translates into year-
round operating savings.
CONTROLS FOR PERFORMANCE DEPENDABILITY — The
condensing units offer the building owner operating controls
and components designed for performance dependability. The
highly efficient hermetic and semi-hermetic compressors are
engineered for long life and durability. The compressors
include overload protection and vibration isolation for enhance-
ment of quiet operation. The high-pressure switch protects the
entire refrigeration system from abnormally high operating
pressures. A low-pressure switch protects the system from
low-pressure conditions, including loss of charge.
The 569F120 and 566E150-240 units feature 2 scroll compres-
sors and 2 refrigerant circuits that provide continuous air
conditioning and design flexibility. These units also include
Cycle-LOC™ anti-short-cycling protection which helps to
protect the units against compressor failure.
All units include a crankcase heater to eliminate liquid slugging
at start-up. Units with semi-hermetic compressors are also
equipped with an oil-level sight glass.
Latest safety standards are assured through UL and UL
Canada approvals.
INNOVATIVE BRYANT PACKAGED AIR HANDLERS ARE
CUSTOM MATCHED TO THE CONDENSING UNITS — The
524A Series has excellent fan performance, efficient direct-
expansion (DX) coils, a unique combination of indoor-air qual-
ity features, and easy installation. Its versatility and state-of-
the-art features help to ensure that your split system provides
economical performance now and in the future.
Indoor-Air Quality (IAQ) Features — The unique combination
of IAQ features in the 524A Series air handlers help to ensure
that only clean, fresh, conditioned air is delivered to the occu-
pied space.
Direct-expansion (DX) cooling coils prevent the build-up of
humidity in the room, even during part-load conditions. Unit
sizes of 10 tons and above feature dual-circuit coils for
improved temperature control.
Standard 2-in. disposable filters remove dust and airborne par-
ticles from the occupied space for cleaner air.
Models 566D, 566E, 569D,
569F, 576C
with 524A
6to20Tons
569D072-120
576C120
569F120
566D150-240
566E150-240
524A072-300
2
Thermal insulation contains an EPA-registered immobilized
anti-microbial agent to inhibit the growth of bacteria and fungi.
The pitched, non-corroding drain pan can be adjusted for a
right- or left-hand connection to suit many applications and
provide positive drainage and to prevent standing condensate.
The 524A accessory economizer can provide ventilation air to
improve indoor air quality by using demand control ventilation.
When used in conjunction with a 2 to 10 VDC adapter on the
actuator and a CO2sensor, the economizer admits fresh
outdoor air to replace stale, recirculated indoor air as needed.
Economy — The 524A Series packaged air handlers have low
initial costs, and they continue to save money by providing
reduced installation expense and energy-efficient performance.
Quick installation is ensured by the multipoise design. Units can
be installed in either the horizontal or vertical configuration with-
out modifications. Fan motors and contactors are prewired and
thermostatic expansion valves (TXVs) are factory-installed on
all 524A direct-expansion models.
High efficiency, precision-balanced fans minimize air turbu-
lence, surging, and unbalanced operation, cutting operation
expenses.
The economizer accessory precisely controls the blend of out-
door air and room air to achieve comfort levels. When the
outside air enthalpy is suitable, outside air dampers can fully
open to provide “free” cooling without energizing mechanical
cooling.
Rugged Dependability — The 524A series units are made to
last. The die-formed galvanized steel panels ensure structural
integrity under all operating conditions. Galvanized steel fan
housings are securely mounted to a die-formed galvanized
steel fan deck.
Rugged pillow-block bearings (524A150-300) are securely fas-
tened to the solid steel fan shaft with split collets and clamp
locking devices. Smaller unit sizes have spider-type bearings.
Coil Flexibility — Model 524A direct-expansion coils have gal-
vanized steel casings; inlet and outlet connections are on the
same end. The coils are designed for use with Refrigerant 22
and have 3/8-in. diameter copper tubes mechanically bonded to
aluminum sine-wave fins. The coils include matched, factory-
installed thermostatic expansion valves (TXVs) with matching
distributor nozzles.
Easier Installation and Service — Themultipoisedesignand
component layout help you to get the unit installed and running
quickly. Units can be converted from horizontal to vertical oper-
ation by simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters, motor, drive,
TXVs, and coil connections are all easily accessed by removing
a single side panel.
TABLE OF CONTENTS
Page
Features/Benefits .............................................1,2
ARICapacityRatings ............................................3
OptionsandAccessories .......................................4-6
SelectionProcedure.............................................7
Controls.......................................................8
TypicalWiringSchematics .....................................9,10
569D072-120, 576C120, 569F120
ModelNumberNomenclature.....................................11
PhysicalData .................................................12
Dimensions................................................13,14
PerformanceData...........................................15-25
ElectricalData.................................................26
ApplicationData ...............................................27
TypicalPipingandWiring ........................................28
GuideSpecifications.........................................29-32
566D/E150-240
ModelNumberNomenclature.....................................33
PhysicalData ..............................................34,35
Dimensions................................................36-38
PerformanceData...........................................39-52
ElectricalData.................................................53
ApplicationData ............................................54-56
TypicalPipingandWiring .....................................57,58
GuideSpecifications.........................................59,60
524A072-300
ModelNumberNomenclature.....................................61
PhysicalData .................................................62
Dimensions................................................63-65
PerformanceData...........................................66-71
ElectricalData..............................................72-78
ApplicationData ............................................79-81
GuideSpecifications.........................................82,83
3
ARI* CAPACITY RATINGS
LEGEND
*Air Conditioning and Refrigeration Institute.
†Ratings in accordance with latest ARI Standard revisions.
**Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.
††ENERGY STA R ® compliant combination of condensing unit and air handler/
indoor coil.
SOUND LEVELS, dB — 569D/576C/566D,E
ESTIMATED SOUND POWER LEVELS (Lw) — 524A072-300
NOTE: Since this data is calculated, these sound power levels may be different than the actual
sound power levels. The accoustic center of the unit is located at geometric center of the unit.
CONDENSING
UNIT
AIR
HANDLER/
INDOOR COIL
SYSTEM† CONDENSING UNIT ONLY**
Net Cap.
(Btuh) EER IPLV Gross Cap.
(Btuh) EER IPLV
569D072
524A-B072†† 69,000 11.0 N/A
72,000 12.4 N/A
524A-C072†† 72,000 11.2 N/A
524A-B090 71,000 10.8 N/A
524A-C090†† 74,000 11.0 N/A
569D090
524A-B072 87,000 10.6 N/A
100,000 12.7 N/A
524A-C072†† 91,000 11.3 N/A
524A-B090 90,000 10.6 N/A
524A-C090†† 94,000 11.2 N/A
569D120
524A-B120 118,000 10.3 N/A
133,000 12.4 N/A
524A-C120 125,000 10.4 N/A
524A-B150 123,000 10.4 N/A
524A-C150 130,000 10.4 N/A
576C120
524A-B120 114,000 10.3 13.1
124,000 12.0 16.5
524A-C120 119,000 10.3 13.6
524A-B150 118,000 10.4 14.1
524A-C150 125,000 10.3 14.5
569F120
524A-B120 113,000 10.3 11.7
123,000 12.3 16.0
524A-C120 118,000 10.5 12.4
524A-B150 118,000 10.5 12.8
524A-C150 124,000 10.9 13.2
566D150
524A-B150 138,000 10.4 12.7
150,000 12.1 15.8
524A-C150 144,000 10.6 13.0
524A-B180 144,000 10.6 11.6
524A-C180 146,000 10.8 13.1
566E150
524A-B120 135,000 9.7 9.9
158,000 12.5 15.1
524A-C120 143,000 10.2 10.3
524A-B150 145,000 10.5 10.9
524A-C150 153,000 11.1 11.5
524A-B180 152,000 10.8 11.0
524A-C180 161,000 11.3 11.5
566D180
524A-B180 176,000 9.8 12.3
198,000 11 14.9
524A-C180 182,000 9.7 12.1
524A-B240 184,000 9.8 12.2
524A-C240 196,000 10.0 12.5
566E180
524A-B150 176,000 10.0 10.4
204,000 11.9 13.9
524A-C150 185,000 10.3 10.8
524A-B180 187,000 10.2 10.5
524A-C180 198,000 10.6 10.9
524A-B240 194,000 10.1 10.2
524A-C240 204,000 10.4 10.4
566D240 524A-C300 244,000 9.5 11.8 248,000 10.5 13.9
566E240 524A-C240 243,000 9.6 9.8 259,000 11.2 13.1
524A-B300 242,000 9.6 9.9
524A-C300 252,000 9.7 9.9
EER — Energy Efficiency Ratio
IPLV — Integrated Part Load Value
N/A Not Applicable
SST — Saturated Suction Temperature
UNIT SOUND RATING
(60 Hz) dB (A)
OCTAVE BANDS
63 125 250 500 1000 2000 4000 8000
569D
072 80.0 43.8 61.4 66.2 70.8 73.8 75.2 73.0 62.7
090 84.0 58.5 67.3 71.3 75.4 77.2 75.8 76.5 71.3
120 85.0 63.7 67.6 72.5 77.0 80.4 77.5 74.7 65.9
576C 120 83.0 52.5 66.1 75.1 75.4 78.3 73.5 71.0 64.2
566D 150 86.2 93.0 86.0 83.0 80.0 78.0 73.0 71.0
180 86.2 93.0 86.0 83.0 80.0 78.0 73.0 71.0
240 90.0 83.5 81.5 88.5 86.5 85.5 82.5 76.5 61.5
566E
150 86.9 90.9 86.1 83.1 84.0 73.5 71.7 66.7
180 87.5 90.9 86.1 83.4 84.5 76.6 73.2 63.5
240 88.0 90.9 86.1 83.8 84.5 79.2 74.3 65.5
UNIT CFM dB(A) OCTAVE BAND CENTER FREQUENCY
63 125 250 500 1000 2000 4000
524A072 2,400 86.3 93.2 89.2 85.2 84.2 80.2 78.2 74.2
524A090 3,000 88.3 95.3 91.3 87.3 86.3 82.3 80.3 76.3
524A120 4,000 91.6 98.6 94.6 90.6 89.6 85.6 83.6 79.6
524A150 5,000 91.1 97.3 93.3 89.3 90.3 84.3 82.3 78.3
524A180 6,000 92.7 98.9 94.9 90.9 91.9 85.9 83.9 79.9
524A240 8,000 96.4 102.6 98.6 94.6 95.6 89.6 87.6 83.6
524A300 10,000 96.2 102.5 98.5 94.5 95.5 89.5 87.5 83.5
4
OPTIONS AND ACCESSORIES
566D, 566E, 569D, 569F, 576C FACTORY-INSTALLED
OPTIONS
Dura-Shield
Condenser Coils offer several options to match
coil protection to site conditions for optimum durability. See
table below. Consult your Bryant representative for further
information.
E-Coated Aluminum-Fin Coils have a flexible and durable
epoxy coating uniformly applied to all coil surfaces. Unlike brittle
phenolic dip and bake coatings, E-coating provides superior
protection with unmatched flexibility, edge coverage, metal
adhesion, thermal performance, and most importantly, corro-
sion resistance.
E-coated coils provide this protection since all coil surfaces are
completely encapsulated from environmental contamination.
This coating is especially suitable in industrial environments.
Pre-Coated Fin Coils provide protection in mild coastal
environments.
–20 F Low-Ambient Temperature Kit Option (Motormaster®)
(566E, 569D, 569F, 576C Only) controls outdoor-fan motor
operation to maintain the correct head pressure at low outdoor
ambient temperatures.
115-v Convenience Outlet (566E, 569D, 569F, 576C Only) to
power up electric drills, lights, and refrigerant recovery
machines. This means you are no longer required to run a sep-
arate 115-v power supply.
Non-Fused Disconnect Switch (566E, 569D, 569F, 576C
Only) to remove power locally at the condensing unit. This
switch also includes a power lockout capability to protect the
service person. This lockout switch saves the service person
time and effort because there is no need to access a distant dis-
connect switch while servicing the unit.
FIELD-INSTALLED ACCESSORIES
Electric Unloader Package (576C120 Only) includes hard-
ware and solenoid valve to convert a pressure-operated
unloader to electric unloading.
–20 F Low-Ambient Temperature Accessory Kit (Motormas-
ter) controls outdoor-fan motor operation to maintain the correct
head pressure at low outdoor ambient temperatures.
Condenser Coil Grille Package protects condensing unit coil
from impact by large objects and vandalism.
Bryant’s Line ofThermostats provide both programmable and
non-programmable capability with the new Debonair®lineof
commercial programmable thermostats. The Commercial
Electronic thermostats provide 7-day programmable capability
for economical applications.
Hail Guard Package protects against damage from flying
debris and hail.
Gage Panel Package provides a suction and discharge pres-
sure gage for the refrigerant circuit.
CONDENSER COIL OPTIONS
LEGEND
COPPER-TUBE COILS
WITH
DURA-SHIELD
OPTION
ENVIRONMENT
Standard Mild
Coastal
Industrial/
Coastal
Al Fins (Standard Coils) X
Al Fins, E-Coated X
Al Fins, Pre-Coated X
Al Aluminum
LOW AMBIENT CONTROL
(FACTORY-INSTALLED OR
FIELD-INSTALLED)
FACTORY-INSTALLED
CONVENIENCE OUTLET FACTORY-INSTALLED
DISCONNECT SWITCH
FACTORY-INSTALLED
DURA-SHIELD
COIL PROTECTION
Options and Accessories
5
OPTIONS AND ACCESSORIES (cont)
524A-B, C FACTORY-INSTALLED OPTIONS
Alternate Fan Motors and Drives are available to provide the
widest possible range of performance.
High-Capacity 4-Row Coils are available to provide increased
latent and sensible capacities (524A-C).
Prepainted Steel Units are available from the factory for appli-
cations that require painted units. Units are painted with Ameri-
canSterlingGraycolor.
FIELD-INSTALLED ACCESSORIES
Two-Row Hot Water Coils have copper tubes mechanically
bonded to aluminum plate fins and non-ferrous headers.
One-Row Steam Coil has copper tubes and aluminum fins.
The Inner Distributing Tube (IDT) design provides uniform
temperatures across the coil face. The steam coil has a broad
operating pressure range; up to 20 psig (138 kPag) at 260 F
(127 C). The IDT steam coils are especially suited to applica-
tions where sub-freezing air enters the unit.
Electric Resistance Heat Coils have an open-wire design and
are mounted in a rigid frame. Safety cutouts for high tempera-
ture conditions are standard. Terminal block for single-point
power connection is included.
Economizer (Enthalpy Controlled) provides ventilation air
and “free” cooling if outside ambient temperature and humidity
are suitable.
Discharge Plenum directs the air discharge directly into the
occupied space integral horizontal and vertical louvers enable
redirection of airflow. Accessory is available unpainted or
painted. Field assembly required.
Return-Air Grille provides a protective barrier over the return-
air opening and gives a finished appearance to units installed in
the occupied space. Accessory is available unpainted or
painted.
Subbase provides a stable, raised platform and room for con-
densate drain trap connection for vertical floor-mounted units.
Accessory is available unpainted or painted.
Overhead Suspension Package includes necessary brackets
to support units in horizontal ceiling installations.
Bryant’s Line ofThermostats provide both programmable and
non-programmable capability. The Commercial Electronic
thermostats provide 7-day programmable capability for eco-
nomical applications.
Condensate Drain Trap includes an overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includes a wire harness that can be connected
to an alarm if desired. The transparent trap is designed for easy
service and maintenance.
UV-C Germicidal Lamps kill mold and fungus, which may grow
on evaporator coil and condensate pan surfaces. The use of
UV-C germicidal lamps eliminates the foul odors that result from
this growth of mold and fungus. It also provides a self-cleaning
function for the evaporator coil and drain pan.
Commercial Programmable
and Non-Programmable Thermostat
6
OPTIONS AND ACCESSORIES (cont)
DISCHARGE
PLENUM
RETURN-AIR
GRILLE
SUBBASE
FAN
COIL
UNIT
ECONOMIZER
FAN COIL UNIT
FAN COIL
UNIT
HOT WATER OR
STEAM COIL
524A with Economizer
524A with Hot Water or Steam Coil
524A with Discharge Plenum,
Return Grille, and Subbase
524A with Condensate Trap
7
SELECTION PROCEDURE
To determine combination ratings for 569D/F, 576C and 566D/E
units matched with 524A Series air handlers, follow these steps:
I DETERMINE COOLING LOAD, EVAPORATOR-AIR
TEMPERATURE, AND QUANTITY.
Given:
Total Cooling Capacity
Required(TC)...................... 127,000Btuh
Sensible Heat Capacity
Required(SHC)..................... 95,000Btuh
CompressorType ...........................Scroll
Temperature Air Entering Condenser (Edb). . . . . . . . 95 F
Temperature Air Entering
Evaporator(db/wb)................80Fdb,67Fwb
EvaporatorAirQuantity...................4,000cfm
ExternalStaticPressure .................. 0.4in.wg
Length of Interconnecting
RefrigerantPiping ...................25ft(Linear)
PowerSupply(V-Ph-Hz) ............... 208/230-3-60
II SELECT CONDENSING UNIT AIR-HANDLER
COMBINATION.
For this example, select a 569D120 matched with a
524A-C120 with high-capacity 4-row coil This 569D120/
524A-C120 condensing unit air-handler combination
provides 130,000 Btuh of total cooling capacity and
98,200 Btuh of sensible capacity at the given conditions. If
other temperatures or airflow values are required, interpo-
late the values from the combination ratings.
III DETERMINE SIZES OF LIQUID AND SUCTION LINES.
Enter Refrigerant Piping Sizes table. The sizes shown are
based on an equivalent length of pipe. This equivalent
length is equal to the linear length of pipe indicated at the
top of each sizing column, plus a 50% allowance for fitting
losses. (For a more accurate determination of actual
equivalent length in place of using the estimated 50%
value, refer to a standard refrigeration piping practice.) For
this example, note in the linear length column that the
proper pipe size is 1/2in. for the liquid line and 13/8in. for
the suction line.
IV DETERMINE FAN RPM AND BHP (BRAKE
HORSEPOWER).
At the Air Handler Fan Performance table enter at 524A-
C120 with high capacity coil at 4000 cfm and move to the
External Static Pressure (ESP) column. Note that the con-
ditions require 803 rpm at 1.77 bhp.
V DETERMINE MOTOR AND DRIVE.
Enter the Fan Motor Data tables and find the standard
motor for 524A-C120 unit rated at 2.4 Hp. Since the bhp
required is 1.77, a standard motor satisfies the require-
ment and should be used.
Next, find the type of drive that satisfies the 803 rpm
requirement in the Drive Data tables. For the 524A-C120
unit, the Standard Drive table on shows an rpm range of
666-863. Since the rpm required is 803, the standard drive
satisfies the requirement and should be used. Select the
standard motor and standard drive combination (option
code GC or ED).
8
CONTROLS
OPERATING SEQUENCES
569D072-120, 576C120 — At start-up, the thermostat calls for
cooling. With all safety devices satisfied, the compressor
contactor and fan contactor energize, causing the compressor
and outdoor-fan motor to operate. Thermostat contacts
energize, allowing the field-supplied and field-installed indoor-
fan contactor to function. A field-supplied and field-installed liq-
uid line valve also opens, allowing the system to function in
Cooling mode. As cooling demand is satisfied, the thermostat
contacts break, deenergizing the contactor and causing the
system to shut off. The liquid line solenoid valve closes, mini-
mizing the potential for refrigerant migration. The compressor
does not restart until the thermostat again calls for cooling. The
system is protected with a safety circuit so that the system will
not start if a fault exists (i.e., high or low pressure fault). To reset
the safety circuit, set the thermostat to eliminate the cooling
demand, then return to original set point. This should be done
only once, and if system shuts down due to the same fault,
determine the problem before attempting to restart the system.
566D150-240 — When the first stage of cooling thermostat
closes, the timer starts. After approximately 3 seconds, the
timer activates the compressor and fan motor no. 1 contactors.
When the liquid pressure builds to approximately 257 psig, fan
motor no. 2 is energized.
When there is demand for additional cooling capacity, the
second stage of the cooling thermostat closes, energizing a
field-supplied liquid line solenoid (LLS) valve, which opens. This
increases the suction pressure, causing the compressor to
operate at higher capacity (compressor loads).
When the fan switch is set at AUTO, the indoor-air fan cycles
with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.
At shutdown, the Time Guard II timer prevents the compressor
from restarting for approximately 5 minutes.
In addition, an LLS valve wired in parallel with the compressor
contactor coil shuts off the liquid line to prevent refrigerant
migration back to the compressor during the off cycle.
569F120 — When the thermostat calls for stage one cooling at
start-up, and all safety devices are satisfied, the compressor
contactor no. 1 (C1) energizes causing compressor no. 1 and
outdoor-fan motor no. 1 to start (the indoor-fan contactor should
be wired to start at the same time as the compressor). The
liquid line solenoid (LLS) valve will open when compressor no. 1
starts, allowing refrigerant to flow in the system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 and
outdoor-fan motor no. 2 to start. As the cooling demand
decreases, stage two on the thermostat opens, causing
compressor no. 2 and outdoor-fan motor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermostat
opens causing compressor no. 1 and outdoor-fan motor no. 1 to
shut down. The LLS valve for each compressor will close when
the associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set to CONT.
Each compressor is protected with a Cycle-LOCTM device so
that the compressor will not operate if there is a high-pressure
fault, low pressure fault, or a compressor is off due to internal
line break overcurrent/overtemperature protection. To reset the
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.
566E150-240 — At start-up, when the thermostat calls for first
stage cooling and all safety devices are satisfied, the compres-
sor contactor (C1) energizes causing compressor no. 1 and fan
motor no. 1 to start. Fan motor no. 2 will start when the fan
cycling pressure switch (FCPS) closes as discharge pressure
builds (refer to physical data table for FCPS specifications).
With the indoor-fan contactor wired to TB2-4 and TB2-9
contacts on the terminal block, the indoor fan will also start with
the compressor. The liquid line solenoid (LLS) valve will open
when compressor no. 1 starts, allowing refrigerant to flow in the
system.
When the thermostat calls for stage two cooling, compressor
contactor no. 2 (C2) energizes causing compressor no. 2 to
start. As the cooling demand decreases, stage two on the
thermostat opens, causing compressor no. 2 to shut down. As
the cooling continues to decrease, stage one of the thermostat
opens causing compressor no. 1 and outdoor-fan motor to shut
down. The LLS valve for each compressor will close when the
associated compressor stops, minimizing the potential for
refrigerant migration during the off cycle.
The indoor-fan motor will stop if the thermostat is set to AUTO
and will continue to operate if the thermostat is set on CONT.
Each compressor is controlled by the thermostat so they will not
start until there is a demand from the thermostat. Each
compressor is protected with a Cycle-LOC device so that the
compressor will not operate if there is a high-pressure fault,
low-pressure fault, or compressor is off due to internal line
break overcurrent/overtemperature protection. To reset the a
Cycle-LOC device, set the thermostat higher to remove the
cooling demand, then return to the original set point. This
should be done only once. If the system shuts down with the
same fault, the cause for the fault should be determined and
corrected before the a Cycle-LOC device is reset again.
9
TYPICAL WIRING SCHEMATICS
569D090, 208/230-3-360 and 460-3-60 Units
NOTES:
1. If any of the original wire furnished must be
replaced, it must be replaced with type 90° C
wire or its equivalent.
2. Thermostat: HH07AT170, 172, 174 & P272-
2783
Subbase: HH93AZ176, 178 & P272-1882, 1883
or HH93AZ177 & 179.
3. Sealed VA for IFC and LLSV is not to exceed
22.
4. Use copper conductors only.
5. TRAN is wired for 230 v unit. If unit is to be run
with 200 v power supply, disconnect BLK wire
from 230 v tap and connect to 200 v tap.
6. If TRAN is wired for 460-3-60 v and unit is to be
run with 400-3-50 v power supply, disconnect
BLK wire from 460 v tap and connect to 400 v
tap.
7. Three-phase motors are protected under pri-
mary single phasing conditions.
VOLTAGE
RATING
CB MUST
TRIP
AMPS
Mfg. Part No.
24 V Potter & Brumfield 3.2
W28X-1024-3.2
AHA Adjustable Heat Anticipator
C—Contactor, Compressor
CAP Capacitor
CB Circuit Breaker
CC Cooling Compensator
CH Crankcase Heater
CLO Compressor Lockout
COMP Compressor Motor
DGT Discharge Gas Thermostat
EQUIP Equipment
GND Ground
HPS High-Pressure Switch
IFC Indoor-Fan Contactor
LLSV Liquid Line Solenoid Valve
LPS Low-Pressure Switch
NEC National Electrical Code
OFM Outdoor-Fan Motor
QT Quadruple Terminal
TB Terminal Block
TC Thermostat-Cooling
TH Thermostat-Heating
TRAN Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
—— Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not Represent Wiring
LEGEND
10
TYPICAL WIRING SCHEMATICS (cont)
LEGEND
AHA Adjustable Heat
Anticipator
C—Contactor,
Compressor
CAP Capacitor
CB Circuit Breaker
CC Cooling Compensator
CH Crankcase Heater
COMP — Compressor Motor
COTP Compressor Over
Temperature Protection
EQUIP — Equipment
GND Ground
HPS High-Pressure Switch
IFC Indoor-Fan Contactor
LLSV Liquid Line Solenoid
Valve
LPS Low-Pressure Switch
NEC National Electrical Code
OFM Outdoor-Fan Motor
OL Overload Relay
R—Relay
TB Terminal Block
TC Thermostat-Cooling
TH Thermostat-Heating
TRAN Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Factory Wiring
—— Field Control Wiring
Field Power Wiring
Accessory or
Optional Wiring
To Indicates Common
Potential Only, Not
Represent Wiring
576C120, 208/230-3-60 and 460-3-60 Units
11
MODEL NUMBER NOMENCLATURE
569D P X 072 000 ––
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T— 575-3-60
Heating
X—None
Nominal Tons Cooling
072 6 (569D Only)
090 7-1/2 (569D Only)
120 — 10 (569D, 569F) Heating Capacity
000 — No Heat
Factory-Installed Options*569D Commercial Air-Cooled Condensing
Unit With Scroll Compressor
569F Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressor
576C P X 120 000 ––
576C Commercial Air-Cooled Condensing
Unit With Semi-Hermetic Compressor
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60
Heating
X—None
Nominal Tons Cooling
120—10
Heating Capacity
000 — No Heat
Factory-Installed Options*
*Contact your local representative for more details.
Certified to ISO 9001:2000
Quality Assurance
50TFQ004-012
569D072-120, 576C120, 569F120
12
PHYSICAL DATA
569D072-120, 576C120, 569F120 UNITS
*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at
95 F.
NOTE:Unit 576C120 has one step of unloading. Full load is at 100% of
capacity, and one step of unloading is 67% capacity. Unit 576C120 has
the following unloader settings: load is 70 ± 1 psig and unload is 60 ±
2psig.
UNIT 569D072 569D090 569D120 576C120 569F120
NOMINAL CAPACITY (tons) 67
1/210 10 10
OPERATING WEIGHT (lb)
Aluminum Coils (Standard) 300 383 430 575 488
Copper Coils (Optional) 352 484 531 676 589
RREFRIGERANT TYPE* R-22
Operating Charge, Typical (lb)† 12 20 22 24 11/Circuit
Shipping Charge (lb) 2.0 2.0 2.0 2.0 2.0
COMPRESSOR
Type Scroll Reciprocating Scroll
Qty...Model 1...SR_68 1...SR_94 1...ZR125 1...06DH824 2...SR_60
Oil Charge (oz) 88 90 110 128 72 (ea)
No. Cylinders N/A 6 N/A
Speed (rpm) 3500 1750 3500
CONDENSER FAN
Qty...Rpm 2...850 2...1100 2...1100 2...1100 2...1100
Motor HP (rpm) 1/81/41/41/41/4
Diameter 22 22 22 22
Nominal Airflow (CfmTotal) 5400 6500 6500 6500
Watts (Total) 340 570 570 570
CONDENSER COIL (Qty) 2 2
Face Area (sqfttotal) 29.2 29.2 29.2
Rows...Fins/in. 1...17 2...17 2...17 2...17 2...17
Storage Capacity (lb)** 17.3 34.2 34.2 34.2 17.1 (ea)
CONTROLS
Pressurestat Settings (psig)
High Cutout 428 ± 10 428 ± 10 428 ± 10
Cut-in 320 ± 20 320 ± 20 320 ± 20
Low Cutout 27 ± 3 27 ± 3 27 ± 3
Cut-in 44 ± 5 44 ± 5 44 ± 5
DISCHARGE GAS THERMOSTAT (°F) 2 2
Cutout 270 ± 9 — — —
Cut-in 190 ± 13 — — —
PRESSURE RELIEF
Location Suction Line
Temperature (F) 200
PIPING CONNECTIONS (in. ODM)
Qty...Suction 1...11/81...11/81...13/81...13/82...11/8
Qty...Liquid 1...3/81...3/81...1/21...1/22...3/8
50TFQ004-012
569D072-120, 576C120, 569F120
13
DIMENSIONS
569D072-120, 576C120
UNIT
ALUMINUM COIL
Standard Unit Weight Corner W Corner XCorner Y Corner ZCenter ofGravity
lb kglbkglbkglbkglbkgXmm [in.]Ymm[in.]
569D072 300 136 62 28 103 47 62 28 72 33 831.9 [32.75] 641.4 [25.25]
569D090 383 174 86 39 123 56 85 39 89 40 822.3 [32.38] 635.0 [25.00]
569D120 430 195 84 38 166 75 66 30 114 52 812.8 [32.00] 676.3 [26.63]
576C120 575 261 55 25 265 120 88 40 167 76 927.1 [36.50] 647.7 [25.50]
UNIT ELECTRICAL
CHARACTERISTICS
569D072 208/230-3-60, 460-3-60, 575-3-60
569D090 208/230-3-60, 460-3-60, 575-3-60
569D120 208/230-3-60, 460-3-60, 575-3-60
576C120 208/230-3-60, 460-3-60, 575-3-60
SERVICE VALVE CONNECTIONS
Unit Suction
mm [in.]
Liquid
mm [in.]
569D072 28.6 [11/8]9.5[
3/8]
569D090 28.6 [11/8]9.5[
3/8]
569D120 34.9 [13/8] 12.7 [1/2]
576C120 34.9 [13/8] 12.7 [1/2]
50TFQ004-012
569D072-120, 576C120, 569F120
14
DIMENSIONS (cont)
CONVENIENCE
OUTLET LOCATION
ELECTRICAL DISCONNECT
LOCATION
CONTROL BOX
ACCESS PANEL
CORNER “D”
CORNER “A” CORNER “B”
CORNER “C”
OUTDOOR COIL
OUTDOOR COIL
TOP VIEW
Y
1162.7
[45.78]
X
LEFT SIDE VIEW
OUTDOOR
COIL
OUTDOOR
COIL
OUTDOOR
COIL
OUTDOOR
COIL
ACCESS PANEL
O 34.5 [1.36]
POWER ENTRY
WITH 50.0/58.0/65.0 K.O.
RIGHT SIDE VIEW
FORK TRUCK SLOTS
(3 SIDES ONLY)
REAR VIEW
FRONT VIEW
COMPRESSOR
ACCESS PANEL
ACCESS
PANEL 872.8
[34.36]
582.5
[22.93]
167.5
[6.59]
111.7
[4.40]
O 22.0 [0.87] FIELD
ENTRY SERVICE PORT
BOTTOM
OF UNIT
116.7
[4.59]
SUCTION
CONNECTION
(SEE CHART
FOR SIZE)
LIQUID
CONNECTION
(SEE CHART
FOR SIZE)
LIQUID CONNECTION
(SEE CHART FOR SIZE)
637.9
[25.11]
1509.3
[59.42]
644.6
[25.38]
172.9
[6.81]
287.8
[11.33]
226.9
[8.93]
341.5
[13.45]
(in.) (in.)
569F120
UNIT ELECTRICAL
CHARACTERISTICS
ALUMINUM COIL
Std. Unit
Wt.
Corner
A
Corner
B
Corner
C
Corner
D
Center of
Gravity
lb kglbkglbkglbkglbkgX
mm [in.]
Y
mm [in.]
569F120
208/230-3-60,
400/460-3-50/60,
575-3-60
488 221 102 46 143 65 139 63 104 47 873.8
[34.4]
591.8
[23.3]
569F120
50TFQ004-012
569D072-120, 576C120, 569F120
15
PERFORMANCE DATA
CONDENSING UNIT RATINGS
LEGEND
569D072
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 53.6 52.3 49.4 48.0 46.5 43.6
kW4.24 4.49 5.02 5.31 5.60 6.24
SDT 101.0 106.0 115.0 120.0 125.0 135.0
30
TC 59.1 57.6 54.6 53.0 51.5 48.3
kW4.33 4.57 5.10 5.39 5.69 6.33
SDT 102.0 107.0 117.0 122.0 126.0 136.0
35
TC 64.9 63.3 60.1 58.4 56.7 53.4
kW4.42 4.67 5.20 5.49 5.79 6.43
SDT 104.0 109.0 118.0 123.0 128.0 138.0
40
TC 71.0 69.3 65.8 64.1 62.3 58.7
kW4.53 4.77 5.31 5.60 5.90 6.55
SDT 106.0 110.0 120.0 125.0 129.0 139.0
45
TC 77.4 75.6 71.9 70.1 68.2 64.3
kW4.65 4.89 5.43 5.72 6.02 6.68
SDT 107.0 112.0 122.0 126.0 131.0 141.0
50
TC 84.2 82.3 78.4 76.4 74.3 70.2
kW4.78 5.03 5.56 5.86 6.16 6.81
SDT 109.0 114.0 123.0 128.0 133.0 142.0
569D090
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 73.9 71.7 67.0 64.6 62.1 57.0
kW5.81 6.14 6.84 7.21 7.58 8.36
SDT 98.6 104.0 114.0 118.0 123.0 133.0
30
TC 82.0 79.7 74.9 72.4 69.9 64.7
kW5.88 6.21 6.90 7.28 7.65 8.46
SDT 99.6 104.0 114.0 119.0 124.0 134.0
35
TC 90.4 88.0 83.0 80.4 77.8 72.4
kW5.98 6.31 7.02 7.40 7.78 8.59
SDT 101.0 106.0 115.0 120.0 125.0 135.0
40
TC 99.2 96.7 91.4 88.7 85.9 80.3
kW6.09 6.43 7.14 7.53 7.92 8.74
SDT 103.0 107.0 117.0 122.0 126.0 136.0
45
TC 109.0 106.0 100.0 97.4 94.5 88.6
kW6.22 6.56 7.28 7.68 8.07 8.91
SDT 104.0 109.0 119.0 123.0 128.0 138.0
50
TC 118.0 116.0 110.0 107.0 104.0 97.2
kW6.36 6.70 7.43 7.83 8.23 9.09
SDT 106.0 111.0 120.0 125.0 130.0 139.0
569D120
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 102.0 99.3 93.8 90.9 88.1 81.9
kW8.04 8.38 9.13 9.55 9.95 10.85
SDT 101.0 106.0 116.0 121.0 126.0 136.0
30
TC 112.0 109.0 103.0 99.8 96.7 90.3
kW8.26 8.60 9.31 9.65 10.05 10.95
SDT 103.0 107.0 117.0 12.02 127.0 136.0
35
TC 122.0 119.0 113.0 109.0 106.0 99.0
kW8.52 8.85 9.55 9.95 10.35 11.15
SDT 104.0 109.0 118.0 123.0 128.0 137.0
40
TC 133.0 130.0 123.0 119.0 115.0 108.0
kW8.81 9.15 9.85 10.25 10.55 11.35
SDT 106.0 110.0 120.0 125.0 129.0 139.0
45
TC 144.0 141.0 133.0 130.0 126.0 118.0
kW9.12 9.45 10.15 10.55 10.85 11.65
SDT 108.0 112.0 122.0 126.0 131.0 140.0
50
TC 156.0 152.0 145.0 141.0 137.0 128.0
kW9.45 9.85 10.55 10.85 11.25 12.05
SDT 109.0 114.0 123.0 128.0 133.0 142.0
576C120
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 89.0 85.1 77.4 73.6 69.7 62.2
kW7.52 7.79 8.29 8.49 8.70 9.02
SDT 103.0 108.0 118.0 123.0 128.0 138.0
30
TC 101.0 96.6 88.5 84.4 80.3 72.2
kW7.76 8.07 8.64 8.89 9.14 9.55
SDT 104.0 108.0 118.0 123.0 128.0 138.0
35
TC 113.0 109.0 100.0 95.8 91.5 83.0
kW8.01 8.36 8.99 9.28 9.55 10.05
SDT 105.0 109.0 119.0 124.0 128.0 138.0
40
TC 125.0 121.0 112.0 107.0 103.0 94.1
kW8.29 8.66 9.35 9.65 9.95 10.55
SDT 106.0 111.0 120.0 125.0 129.0 139.0
45
TC 138.0 133.0 124.0 119.0 115.0 106.0
kW8.57 8.97 9.75 10.05 10.50 11.05
SDT 108.0 113.0 122.0 127.0 131.0 140.0
50
TC 152.0 147.0 137.0 132.0 127.0 117.0
kW8.85 9.28 10.15 10.45 10.90 11.55
SDT 111.0 115.0 124.0 129.0 133.0 142.0
569F120
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 90.5 87.9 82.6 79.8 76.9 71.1
kW7.75 8.17 9.05 9.52 10.00 11.00
SDT 100.0 105.0 115.0 120.0 125.0 135.0
30
TC 100.0 97.8 92.2 89.3 86.3 80.2
kW7.79 8.21 9.09 9.57 10.10 11.10
SDT 101.0 106.0 116.0 120.0 125.0 135.0
35
TC 111.0 108.0 102.0 99.0 96.0 89.7
kW7.89 8.30 9.18 9.66 10.10 11.20
SDT 102.0 107.0 116.0 121.0 126.0 136.0
40
TC 122.0 119.0 112.0 109.0 106.0 99.4
kW8.01 8.42 9.31 9.79 10.30 11.30
SDT 104.0 108.0 118.0 123.0 127.0 137.0
45
TC 133.0 130.0 123.0 120.0 116.0 109.0
kW8.15 8.57 9.46 9.95 10.40 11.50
SDT 105.0 110.0 120.0 124.0 129.0 138.0
50
TC 145.0 141.0 134.0 131.0 127.0 120.0
kW8.30 8.72 9.63 10.10 10.60 11.70
SDT 107.0 112.0 121.0 126.0 131.0 140.0
kW—Compressor Power
SDT — Saturated Discharge Temperature at Compressor (F)
SST — Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
50TFQ004-012
569D072-120, 576C120, 569F120
16
PERFORMANCE DATA (cont)
COMBINATION RATINGS*
UNIT 569D072
LEGEND
*Combinations on this page are ENERGY STA R ® compliant.
569D072/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 66.0 68.6 74.3 80.7 72.0 72.6 77.7 84.1 76.2 76.2 79.9 86.2
SHC 66.0 60.9 51.0 40.8 72.0 70.5 58.6 45.5 76.2 76.2 65.7 50.0
kW4.45 4.49 4.60 4.71 4.55 4.57 4.66 4.78 4.63 4.63 4.70 4.82
85
TC 65.1 67.5 73.1 79.3 71.0 71.4 76.3 82.6 75.0 75.1 78.5 84.6
SHC 65.1 60.3 50.5 40.3 71.0 69.8 58.1 45.0 75.0 75.1 65.2 49.5
kW4.72 4.76 4.87 4.99 4.83 4.84 4.93 5.05 4.91 4.90 4.97 5.09
95
TC 63.3 65.2 70.6 76.7 68.9 69.1 73.6 79.7 72.8 72.8 75.7 81.6
SHC 63.3 59.2 49.4 39.3 68.9 68.3 57.0 44.0 72.8 72.8 64.0 48.5
kW5.26 5.30 5.41 5.53 5.37 5.38 5.47 5.60 5.45 5.45 5.51 5.64
100
TC 62.3 64.0 69.2 75.2 67.7 67.9 72.2 78.2 71.5 71.5 74.2 80.0
SHC 62.3 58.6 48.9 38.8 67.7 67.4 56.5 43.5 71.5 71.5 63.4 47.9
kW5.57 5.61 5.71 5.84 5.68 5.68 5.78 5.90 5.76 5.76 5.82 5.95
105
TC 61.3 62.8 67.9 73.8 66.6 66.7 70.7 76.6 70.3 70.3 72.7 78.4
SHC 61.3 58.0 48.3 38.2 66.6 66.6 55.9 42.9 70.3 70.3 62.8 47.4
kW5.88 5.91 6.02 6.15 5.99 5.99 6.08 6.21 6.07 6.08 6.12 6.26
115
TC 59.3 60.5 65.2 70.9 64.4 64.3 67.8 73.5 67.9 67.9 69.7 75.2
SHC 59.3 56.8 47.2 37.2 64.4 64.3 54.8 41.9 67.9 67.9 61.6 46.4
kW6.51 6.53 6.63 6.77 6.61 6.61 6.70 6.83 6.69 6.70 6.74 6.88
569D072/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 63.4 66.1 71.7 77.8 69.0 69.8 74.9 81.1 72.9 72.9 76.9 83.1
SHC 63.4 58.4 49.0 39.2 69.0 67.2 56.0 43.6 72.9 72.9 62.5 47.6
kW4.40 4.45 4.55 4.66 4.50 4.52 4.60 4.72 4.57 4.57 4.64 4.76
85
TC 62.5 65.1 70.5 76.6 68.0 68.7 73.6 79.7 71.9 71.9 75.6 81.7
SHC 62.5 57.9 48.5 38.8 68.0 66.6 55.5 43.1 71.9 71.9 62.0 47.2
kW4.67 4.72 4.82 4.93 4.77 4.79 4.88 4.99 4.84 4.84 4.91 5.03
95
TC 60.8 62.9 68.2 74.1 66.1 66.5 71.1 77.0 69.7 69.8 73.1 78.9
SHC 60.8 56.8 47.5 37.9 66.1 65.2 54.6 42.2 69.7 69.8 60.9 46.2
kW5.22 5.26 5.36 5.48 5.32 5.33 5.42 5.54 5.39 5.39 5.46 5.58
100
TC 59.9 61.8 67.0 72.8 65.1 65.4 69.8 75.6 68.6 68.6 71.7 77.4
SHC 59.9 56.3 47.0 37.4 65.1 64.4 54.0 41.7 68.6 68.6 60.4 45.7
kW5.53 5.56 5.67 5.79 5.63 5.63 5.73 5.85 5.70 5.70 5.76 5.89
105
TC 59.0 60.7 65.7 71.4 64.0 64.2 68.5 74.1 67.5 67.5 70.3 75.9
SHC 59.0 55.7 46.5 36.9 64.0 63.7 53.5 41.2 67.5 67.5 59.8 45.2
kW5.84 5.87 5.98 6.10 5.94 5.94 6.03 6.16 6.01 6.01 6.07 6.20
115
TC 57.1 58.4 63.3 68.7 61.9 61.9 65.8 71.3 65.2 65.2 67.4 72.9
SHC 57.1 54.6 45.5 35.9 61.9 61.9 52.4 40.2 65.2 65.2 58.7 44.2
kW6.46 6.48 6.59 6.72 6.57 6.56 6.65 6.78 6.64 6.63 6.68 6.82
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
17
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D072 (cont)
LEGEND
*This combination is ENERGY STA R ® compliant.
569D072/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2400 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 71.9 72.9 78.3 84.8 77.7 77.7 81.3 87.6 81.6 81.6 83.4 89.4
SHC 71.9 69.5 57.7 45.1 77.7 77.7 67.0 50.9 81.6 81.6 75.2 56.4
kW4.55 4.57 4.67 4.79 4.66 4.66 4.73 4.85 4.73 4.73 4.77 4.89
85
TC 70.9 71.7 76.9 83.3 76.5 76.5 79.8 86.1 80.3 80.3 81.9 87.8
SHC 70.9 68.8 57.2 44.6 76.5 76.5 66.4 50.3 80.3 80.3 74.6 55.9
kW4.83 4.84 4.94 5.07 4.93 4.93 5.00 5.12 5.01 5.01 5.04 5.16
95
TC 68.8 69.3 74.2 80.4 74.1 74.1 76.9 82.9 77.7 77.8 79.0 84.5
SHC 68.8 67.5 56.1 43.5 74.1 74.1 65.2 49.3 77.7 77.8 73.3 54.8
kW5.37 5.38 5.48 5.61 5.48 5.48 5.54 5.66 5.55 5.56 5.58 5.70
100
TC 67.7 68.0 72.8 78.8 72.8 72.9 75.4 81.3 76.4 76.4 77.4 82.8
SHC 67.7 66.8 55.5 43.0 72.8 72.9 64.6 48.8 76.4 76.4 72.5 54.3
kW5.68 5.69 5.79 5.92 5.79 5.79 5.85 5.97 5.87 5.87 5.89 6.01
105
TC 66.5 66.8 71.3 77.3 71.6 71.6 73.9 79.6 75.0 75.0 75.9 81.1
SHC 66.5 66.0 54.9 42.5 71.6 71.6 64.0 48.2 75.0 75.0 71.8 53.7
kW5.99 6.00 6.09 6.23 6.10 6.10 6.15 6.28 6.18 6.18 6.20 6.32
115
TC 64.3 64.3 68.4 74.2 69.0 69.1 70.8 76.2 72.3 72.3 72.7 77.7
SHC 64.3 64.3 53.8 41.4 69.0 69.1 62.8 47.1 72.3 72.3 70.3 52.6
kW6.61 6.61 6.71 6.85 6.73 6.73 6.77 6.90 6.81 6.8 6.81 6.94
569D072/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2400 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 68.4 69.5 74.8 81.0 73.6 73.6 77.6 83.8 77.3 77.3 79.5 85.5
SHC 68.4 65.8 54.8 42.9 73.6 73.6 63.1 48.1 77.3 77.3 70.4 52.9
kW4.49 4.51 4.61 4.72 4.58 4.58 4.65 4.77 4.65 4.65 4.69 4.81
85
TC 67.4 68.4 73.6 79.7 72.6 72.6 76.3 82.4 76.1 76.1 78.2 84.0
SHC 67.4 65.2 54.3 42.4 72.6 72.6 62.6 47.6 76.1 76.1 69.8 52.4
kW4.76 4.78 4.88 5.00 4.86 4.86 4.93 5.05 4.92 4.92 4.96 5.08
95
TC 65.5 66.2 71.1 77.1 70.4 70.5 73.7 79.5 73.8 73.8 75.5 81.1
SHC 65.5 64.0 53.3 41.5 70.4 70.5 61.5 46.6 73.8 73.8 68.7 51.4
kW5.31 5.32 5.42 5.54 5.40 5.40 5.47 5.59 5.47 5.47 5.51 5.62
100
TC 64.5 65.1 69.7 75.6 69.3 69.3 72.3 78.0 72.6 72.6 74.0 79.5
SHC 64.5 63.3 52.8 41.0 69.3 69.3 60.9 46.1 72.6 72.6 68.0 50.9
kW5.62 5.63 5.72 5.85 5.71 5.72 5.78 5.90 5.78 5.78 5.82 5.93
105
TC 63.4 63.9 68.4 74.1 68.1 68.1 70.9 76.5 71.4 71.4 72.6 77.9
SHC 63.4 62.5 52.2 40.5 68.1 68.1 60.4 45.6 71.4 71.4 67.3 50.4
kW5.93 5.94 6.03 6.16 6.03 6.03 6.08 6.21 6.10 6.10 6.12 6.24
115
TC 61.4 61.6 65.8 71.2 65.9 65.8 68.0 73.4 68.9 68.9 69.7 74.8
SHC 61.4 61.1 51.2 39.4 65.9 65.8 59.2 44.6 68.9 68.9 66.0 49.4
kW6.55 6.55 6.64 6.78 6.65 6.65 6.70 6.83 6.72 6.73 6.74 6.86
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
18
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D090
LEGEND
*This combination is ENERGY STA R ® compliant.
569D090/524A-C072 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 78.9 85.1 92.8 101.0 87.0 90.7 98.3 106.0 93.0 94.7 102.0 110.0
SHC 77.9 69.0 59.0 48.7 87.0 79.9 66.9 53.6 93.0 89.3 74.2 58.0
kW5.75 5.78 5.85 5.94 5.79 5.83 5.91 6.01 5.85 5.87 5.96 6.06
85
TC 77.6 83.6 91.3 99.3 85.7 89.2 96.6 105.0 91.6 93.1 100.0 108.0
SHC 77.0 68.3 58.3 48.0 85.7 79.1 66.3 52.9 91.6 88.4 73.5 57.4
kW6.10 6.13 6.20 6.30 6.14 6.18 6.26 6.37 6.20 6.22 6.31 6.41
95
TC 75.1 80.8 88.3 96.1 83.2 86.1 93.3 101.0 88.9 89.9 96.5 104.0
SHC 75.1 66.8 56.9 46.7 83.2 77.6 64.9 51.6 88.9 86.7 72.2 56.1
kW6.80 6.82 6.90 7.00 6.85 6.87 6.96 7.08 6.91 6.92 7.01 7.12
100
TC 73.9 79.2 86.6 94.4 81.8 84.4 91.4 99.2 87.4 88.2 94.5 102.0
SHC 73.8 66.0 56.2 46.1 81.8 76.7 64.1 50.9 87.4 85.7 71.4 55.3
kW7.20 7.21 7.29 7.40 7.24 7.26 7.36 7.47 7.30 7.31 7.40 7.52
105
TC 72.6 77.6 85.0 92.6 80.4 82.7 89.6 97.3 85.9 86.5 92.6 100.0
SHC 72.6 65.3 55.5 45.4 80.4 75.9 63.4 50.2 85.9 84.7 70.7 54.6
kW7.59 7.60 7.68 7.79 7.64 7.66 7.75 7.87 7.70 7.71 7.80 7.92
115
TC 70.1 74.5 81.7 89.1 77.7 79.4 86.0 93.5 82.9 83.1 88.8 96.2
SHC 70.1 63.7 54.0 44.0 77.7 74.3 61.9 48.8 82.9 82.7 69.2 53.2
kW8.38 8.38 8.47 8.58 8.43 8.44 8.53 8.66 8.48 8.49 8.58 8.71
569D090/524A-B072 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 75.3 81.2 88.5 96.1 82.5 86.4 93.6 101.0 88.0 89.9 96.8 104.0
SHC 74.3 65.8 56.3 46.4 82.5 75.7 63.5 50.9 88.0 84.1 70.0 54.9
kW5.77 5.82 5.91 6.00 5.84 5.88 5.97 6.07 5.90 5.93 6.01 6.12
85
TC 74.2 79.8 87.1 94.6 81.3 84.9 92.0 99.5 86.7 88.4 95.2 103.0
SHC 73.4 65.2 55.6 45.8 81.3 75.0 62.8 50.2 86.7 83.3 69.4 54.3
kW6.12 6.18 6.27 6.37 6.20 6.24 6.33 6.44 6.26 6.28 6.38 6.48
95
TC 71.8 77.2 84.2 91.6 79.0 82.0 88.8 96.2 84.1 85.4 91.9 99.2
SHC 71.6 63.8 54.3 44.6 79.0 73.6 61.5 49.0 84.1 81.7 68.1 53.0
kW6.83 6.89 6.98 7.10 6.91 6.95 7.05 7.17 6.99 7.00 7.10 7.22
100
TC 70.6 75.7 82.6 89.9 77.7 80.4 87.1 94.4 82.7 83.8 90.0 97.3
SHC 70.5 63.1 53.6 43.9 77.7 72.8 60.8 48.3 82.7 80.7 67.4 52.3
kW7.22 7.28 7.38 7.50 7.31 7.35 7.45 7.58 7.39 7.40 7.51 7.63
105
TC 69.4 74.2 81.1 88.3 76.4 78.8 85.4 92.6 81.3 82.2 88.2 95.4
SHC 69.4 62.4 53.0 43.3 76.4 72.0 60.1 47.7 81.3 79.8 66.7 51.7
kW7.61 7.67 7.78 7.91 7.70 7.75 7.86 7.99 7.79 7.80 7.91 8.04
115
TC 67.0 71.3 78.0 85.0 73.8 75.6 82.0 89.0 78.5 78.9 84.6 91.7
SHC 67.0 60.9 51.6 41.9 73.8 70.5 58.7 46.4 78.5 77.9 65.3 50.3
kW8.39 8.45 8.59 8.73 8.49 8.54 8.66 8.80 8.59 8.60 8.71 8.86
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
19
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D090 (cont)
LEGEND
*This combination is ENERGY STA R ® compliant.
569D090/524A-C090 WITH HIGH-CAPACITY 4-ROW COIL*
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2205 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 86.0 90.4 98.0 106.0 94.1 95.7 103.0 111.0 96.9 97.8 104.0 112.0
SHC 86.0 78.0 65.6 52.8 94.1 90.3 75.0 58.5 96.9 94.8 79.3 61.1
kW5.78 5.83 5.91 6.01 5.86 5.88 5.97 6.07 5.90 5.91 5.98 6.09
85
TC 84.8 88.9 96.4 104.0 92.7 94.1 101.0 109.0 95.4 96.2 102.0 110.0
SHC 84.8 77.3 64.9 52.2 92.7 89.4 74.2 57.8 95.4 93.7 78.5 60.5
kW6.14 6.18 6.26 6.37 6.22 6.23 6.32 6.42 6.25 6.26 6.34 6.44
95
TC 82.3 85.8 93.1 101.0 90.0 90.9 97.3 105.0 92.6 93.1 98.7 106.0
SHC 82.3 75.8 63.5 50.9 90.0 87.7 72.8 56.5 92.6 91.4 77.1 59.2
kW6.85 6.88 6.96 7.07 6.92 6.93 7.02 7.13 6.96 6.96 7.04 7.15
100
TC 81.0 84.2 91.3 99.1 88.5 89.2 95.4 103.0 91.0 91.4 96.8 104.0
SHC 81.0 75.0 62.8 50.2 88.5 86.7 72.1 55.8 91.0 90.1 76.4 58.5
kW7.24 7.26 7.36 7.47 7.32 7.33 7.41 7.53 7.35 7.36 7.43 7.55
105
TC 79.6 82.5 89.6 97.2 87.0 87.5 93.5 101.0 89.5 89.7 94.9 102.0
SHC 79.6 74.1 62.1 49.5 87.0 85.7 71.4 55.2 89.5 88.8 75.6 57.8
kW7.63 7.65 7.75 7.87 7.71 7.72 7.81 7.93 7.75 7.75 7.83 7.95
115
TC 77.0 79.2 86.0 93.5 83.9 84.1 89.8 97.2 86.3 86.4 91.0 98.3
SHC 77.0 72.5 60.6 48.1 83.9 83.7 69.9 53.8 86.3 86.2 74.1 56.4
kW8.41 8.42 8.53 8.66 8.50 8.50 8.60 8.73 8.54 8.54 8.62 8.75
569D090/524A-B090 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2205 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 81.7 85.9 93.2 101.0 89.0 90.8 97.5 105.0 91.6 92.6 98.8 106.0
SHC 81.7 74.2 62.4 50.2 89.0 85.2 70.9 55.4 91.6 89.4 74.7 57.7
kW5.83 5.88 5.97 6.07 5.92 5.94 6.02 6.12 5.95 5.96 6.04 6.14
85
TC 80.6 84.5 91.6 99.2 87.7 89.3 95.8 103.0 90.2 91.1 97.1 105.0
SHC 80.6 73.5 61.7 49.6 87.7 84.5 70.2 54.8 90.2 88.4 74.1 57.1
kW6.19 6.23 6.33 6.43 6.28 6.30 6.39 6.49 6.31 6.32 6.40 6.51
95
TC 78.3 81.7 88.5 95.9 85.2 86.3 92.5 99.9 87.6 88.2 93.8 101.0
SHC 78.3 72.1 60.4 48.4 85.2 82.9 69.0 53.6 87.6 86.4 72.8 55.9
kW6.90 6.95 7.05 7.17 7.00 7.02 7.11 7.23 7.04 7.05 7.13 7.25
100
TC 77.0 80.1 86.9 94.2 83.7 84.7 90.7 98.0 86.1 86.6 91.9 99.1
SHC 77.0 71.3 59.8 47.7 83.7 81.9 68.3 52.9 86.1 85.2 72.1 55.2
kW7.30 7.34 7.45 7.57 7.40 7.42 7.52 7.64 7.44 7.45 7.54 7.66
105
TC 75.7 78.6 85.2 92.4 82.3 83.0 88.9 96.1 84.6 85.0 90.1 97.2
SHC 75.7 70.6 59.1 47.0 82.3 80.9 67.6 52.2 84.6 83.9 71.4 54.6
kW7.69 7.74 7.86 7.98 7.80 7.82 7.92 8.05 7.84 7.85 7.94 8.07
115
TC 73.2 75.4 81.9 88.8 79.5 79.8 85.3 92.3 81.7 81.8 86.4 93.3
SHC 73.2 69.0 57.7 45.7 79.5 79.0 66.1 50.9 81.7 81.4 70.0 53.2
kW8.48 8.53 8.67 8.79 8.61 8.61 8.73 8.87 8.65 8.65 8.75 8.89
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
20
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D120
LEGEND
569D120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 117.0 122.0 132.0 142.0 127.0 129.0 138.0 148.0 134.0 134.0 141.0 151.0
SHC 117.0 106.0 88.4 70.9 127.0 122.0 101.0 78.6 134.0 134.0 113.0 85.9
kW8.34 8.48 8.74 9.02 8.61 8.66 8.89 9.18 8.81 8.80 9.00 9.28
85
TC 115.0 120.0 129.0 140.0 125.0 127.0 135.0 145.0 132.0 132.0 139.0 148.0
SHC 115.0 104.0 87.5 70.0 125.0 121.0 100.0 77.6 132.0 132.0 112.0 84.9
kW8.72 8.85 9.11 9.40 8.99 9.04 9.27 9.56 9.19 9.19 9.38 9.67
95
TC 112.0 116.0 125.0 135.0 121.0 122.0 130.0 140.0 128.0 128.0 134.0 143.0
SHC 112.0 102.0 85.5 68.2 121.0 119.0 98.2 75.8 128.0 128.0 110.0 83.1
kW9.49 9.60 9.86 10.20 9.76 9.79 10.00 10.30 9.96 9.95 10.10 10.40
100
TC 110.0 113.0 122.0 132.0 119.0 120.0 127.0 137.0 125.0 125.0 131.0 140.0
SHC 110.0 101.0 84.4 67.1 119.0 117.0 97.1 74.8 125.0 125.0 109.0 82.1
kW9.90 10.00 10.30 10.60 10.20 10.20 10.40 10.70 10.40 10.40 10.50 10.80
105
TC 108.0 111.0 120.0 129.0 117.0 117.0 125.0 134.0 123.0 123.0 128.0 137.0
SHC 108.0 100.0 83.3 66.1 117.0 116.0 96.0 73.7 123.0 123.0 108.0 81.0
kW10.30 10.40 10.70 11.00 10.60 10.60 10.80 11.10 10.80 10.80 10.90 11.20
115
TC 104.0 106.0 114.0 124.0 112.0 112.0 119.0 128.0 118.0 118.0 122.0 131.0
SHC 104.0 97.7 81.2 64.0 112.0 112.0 93.8 71.7 118.0 118.0 105.0 78.9
kW11.10 11.20 11.50 11.70 11.40 11.40 11.60 11.90 11.60 11.60 11.70 12.00
569D120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 110.0 115.0 124.0 134.0 119.0 121.0 130.0 139.0 126.0 126.0 133.0 143.0
SHC 110.0 99.4 83.3 66.8 119.0 114.0 94.6 73.6 126.0 125.0 105.0 79.9
kW8.19 8.32 8.55 8.82 8.41 8.48 8.70 8.96 8.59 8.60 8.80 9.06
85
TC 108.0 113.0 122.0 132.0 117.0 119.0 128.0 137.0 124.0 124.0 131.0 140.0
SHC 108.0 98.4 82.4 66.0 117.0 113.0 93.7 72.8 124.0 123.0 104.0 79.0
kW8.57 8.70 8.93 9.20 8.80 8.85 9.08 9.35 8.97 8.98 9.17 9.44
95
TC 105.0 110.0 118.0 127.0 114.0 115.0 123.0 132.0 120.0 120.0 126.0 135.0
SHC 105.0 96.6 80.7 64.3 114.0 111.0 91.9 71.1 120.0 120.0 102.0 77.3
kW9.34 9.45 9.69 9.96 9.57 9.61 9.83 10.10 9.73 9.74 9.93 10.20
100
TC 104.0 107.0 116.0 125.0 112.0 113.0 121.0 130.0 118.0 118.0 124.0 132.0
SHC 104.0 95.5 79.7 63.4 112.0 109.0 90.9 70.2 118.0 118.0 101.0 76.4
kW9.76 9.86 10.10 10.40 9.98 10.00 10.20 10.50 10.10 10.10 10.30 10.60
105
TC 102.0 105.0 114.0 122.0 110.0 111.0 118.0 127.0 116.0 116.0 121.0 130.0
SHC 102.0 94.4 78.7 62.4 110.0 108.0 89.9 69.2 116.0 116.0 100.0 75.5
kW10.20 10.30 10.5 10.80 10.40 10.40 10.60 10.90 10.60 10.60 10.70 11.00
115
TC 98.4 101.0 109.0 117.0 106.0 106.0 113.0 122.0 111.0 111.0 116.0 124.0
SHC 98.4 92.2 76.7 60.5 106.0 105.0 87.8 67.3 111.0 111.0 97.9 73.6
kW11.00 11.10 11.30 11.60 11.20 11.20 11.40 11.70 11.40 11.40 11.50 11.80
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
21
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569D120 (cont)
LEGEND
569D120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 126.0 129.0 138.0 149.0 136.0 136.0 143.0 153.0 142.0 142.0 147.0 156.0
SHC 126.0 119.0 98.7 77.4 136.0 135.0 114.0 86.5 142.0 142.0 127.0 95.0
kW8.60 8.68 8.94 9.23 8.87 8.87 9.08 9.37 9.06 9.05 9.18 9.46
85
TC 124.0 127.0 136.0 146.0 134.0 134.0 141.0 151.0 140.0 140.0 144.0 154.0
SHC 124.0 118.0 97.7 76.5 134.0 133.0 113.0 85.6 140.0 140.0 126.0 94.1
kW8.98 9.05 9.31 9.61 9.25 9.25 9.46 9.76 9.44 9.44 9.56 9.84
95
TC 120.0 122.0 131.0 141.0 129.0 129.0 136.0 145.0 136.0 136.0 139.0 148.0
SHC 120.0 116.0 95.7 74.6 129.0 129.0 111.0 83.8 136.0 136.0 124.0 92.3
kW9.74 9.80 10.10 10.40 10.00 10.00 10.20 10.50 10.20 10.20 10.30 10.60
100
TC 118.0 120.0 128.0 138.0 127.0 127.0 133.0 142.0 133.0 133.0 136.0 145.0
SHC 118.0 114.0 94.6 73.6 127.0 127.0 109.0 82.7 133.0 133.0 123.0 91.2
kW10.20 10.20 10.50 10.80 10.40 10.40 10.60 10.90 10.60 10.60 10.70 11.00
105
TC 116.0 117.0 126.0 135.0 125.0 125.0 130.0 139.0 130.0 130.0 133.0 142.0
SHC 116.0 113.0 93.5 72.6 125.0 125.0 108.0 81.6 130.0 130.0 121.0 90.1
kW10.60 10.60 10.90 11.20 10.80 10.80 11.00 11.30 11.00 11.00 11.10 11.40
115
TC 112.0 112.0 120.0 129.0 120.0 120.0 124.0 133.0 125.0 125.0 127.0 135.0
SHC 112.0 110.0 91.4 70.5 120.0 120.0 106.0 79.5 125.0 125.0 119.0 87.9
kW11.40 11.40 11.70 12.00 11.60 11.70 11.80 12.10 11.80 11.80 11.90 12.20
569D120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 119.0 123.0 132.0 142.0 128.0 129.0 137.0 147.0 135.0 135.0 140.0 150.0
SHC 119.0 112.0 93.2 73.4 128.0 127.0 106.0 81.4 135.0 135.0 118.0 88.6
kW8.42 8.51 8.77 9.05 8.66 8.68 8.90 9.18 8.84 8.84 8.99 9.27
85
TC 118.0 121.0 130.0 140.0 126.0 127.0 135.0 144.0 133.0 133.0 138.0 147.0
SHC 118.0 111.0 92.3 72.5 126.0 126.0 105.0 80.5 133.0 133.0 117.0 87.8
kW8.80 8.89 9.14 9.43 9.05 9.06 9.28 9.56 9.22 9.22 9.37 9.65
95
TC 114.0 116.0 125.0 135.0 122.0 123.0 130.0 139.0 128.0 128.0 133.0 142.0
SHC 114.0 109.0 90.4 70.7 122.0 122.0 103.0 78.7 128.0 128.0 115.0 86.0
kW9.57 9.64 9.89 10.20 9.81 9.81 10.00 10.30 9.99 9.99 10.10 10.40
100
TC 112.0 114.0 123.0 132.0 120.0 120.0 127.0 136.0 126.0 126.0 130.0 139.0
SHC 112.0 108.0 89.3 69.7 120.0 120.0 102.0 77.7 126.0 126.0 114.0 85.0
kW9.98 10.00 10.30 10.60 10.20 10.20 10.40 10.70 10.40 10.40 10.50 10.80
105
TC 110.0 112.0 120.0 129.0 118.0 118.0 124.0 133.0 123.0 123.0 127.0 136.0
SHC 110.0 106.0 88.2 68.7 118.0 118.0 101.0 76.7 123.0 123.0 113.0 84.0
kW10.40 10.40 10.70 11.00 10.60 10.60 10.80 11.10 10.80 10.80 10.90 11.20
115
TC 106.0 107.0 115.0 124.0 114.0 113.0 119.0 127.0 119.0 119.0 121.0 130.0
SHC 106.0 104.0 86.1 66.6 114.0 113.0 99.1 74.6 119.0 119.0 110.0 81.9
kW11.20 11.20 11.50 11.80 11.40 11.40 11.60 11.90 11.60 11.60 11.70 12.00
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
22
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 576C120
LEGEND
576C120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 113.0 118.0 129.0 141.0 124.0 126.0 135.0 147.0 132.0 132.0 139.0 151.0
SHC 113.0 104.0 87.4 70.5 124.0 121.0 101.0 78.8 132.0 132.0 113.0 86.6
kW8.00 8.12 8.35 8.61 8.26 8.29 8.49 8.75 8.43 8.43 8.58 8.82
85
TC 111.0 115.0 126.0 137.0 122.0 123.0 132.0 144.0 129.0 129.0 136.0 148.0
SHC 111.0 102.0 86.1 69.3 122.0 119.0 99.5 77.6 129.0 129.0 112.0 85.4
kW8.39 8.51 8.76 9.05 8.67 8.69 8.91 9.20 8.86 8.86 9.01 9.28
95
TC 106.0 110.0 120.0 131.0 117.0 117.0 125.0 137.0 124.0 124.0 129.0 140.0
SHC 106.0 99.8 83.7 66.9 117.0 116.0 96.9 75.1 124.0 124.0 109.0 82.9
kW9.17 9.28 9.58 9.93 9.49 9.51 9.76 10.10 9.72 9.72 9.88 10.20
100
TC 104.0 107.0 117.0 128.0 114.0 114.0 122.0 133.0 121.0 121.0 126.0 137.0
SHC 104.0 98.4 82.4 65.7 114.0 114.0 95.6 73.9 121.0 121.0 108.0 81.7
kW9.55 9.65 9.98 10.40 9.90 9.90 10.20 10.50 10.10 10.10 10.30 10.60
105
TC 102.0 104.0 114.0 124.0 112.0 112.0 119.0 130.0 118.0 118.0 122.0 133.0
SHC 102.0 97.0 81.1 64.5 112.0 112.0 94.3 72.7 118.0 118.0 106.0 80.5
kW9.93 10.00 10.40 10.80 10.30 10.30 10.60 11.00 10.60 10.60 10.70 11.10
115
TC 97.2 98.6 107.0 118.0 106.0 106.0 112.0 122.0 113.0 113.0 116.0 125.0
SHC 97.2 94.2 78.6 62.1 106.0 106.0 91.7 70.2 113.0 113.0 104.0 78.0
kW10.70 10.80 11.20 11.60 11.10 11.10 11.40 11.80 11.40 11.40 11.50 12.00
576C120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 107.0 112.0 123.0 134.0 118.0 119.0 129.0 140.0 125.0 125.0 133.0 144.0
SHC 107.0 98.8 83.3 67.2 118.0 114.0 95.5 74.8 125.0 125.0 107.0 81.8
kW7.91 8.03 8.25 8.49 8.14 8.18 8.38 8.62 8.30 8.30 8.46 8.71
85
TC 105.0 110.0 120.0 131.0 115.0 117.0 126.0 137.0 122.0 122.0 129.0 141.0
SHC 105.0 97.5 82.2 66.1 115.0 113.0 94.3 73.7 122.0 122.0 105.0 80.6
kW8.29 8.40 8.65 8.92 8.54 8.57 8.79 9.06 8.71 8.71 8.88 9.15
95
TC 101.0 105.0 114.0 125.0 111.0 111.0 120.0 131.0 117.0 117.0 123.0 134.0
SHC 101.0 95.0 79.8 63.9 111.0 109.0 92.0 71.4 117.0 117.0 103.0 78.4
kW9.04 9.15 9.44 9.78 9.34 9.36 9.61 9.94 9.54 9.54 9.72 10.00
100
TC 98.9 102.0 111.0 122.0 108.0 109.0 117.0 127.0 115.0 115.0 120.0 131.0
SHC 98.9 93.7 78.7 62.8 108.0 108.0 90.8 70.3 115.0 115.0 102.0 77.3
kW9.41 9.51 9.83 10.20 9.73 9.74 10.00 10.40 9.94 9.95 10.10 10.50
105
TC 96.8 99.4 108.0 119.0 106.0 106.0 113.0 124.0 112.0 112.0 117.0 127.0
SHC 96.8 92.3 77.5 61.6 106.0 106.0 89.5 69.2 112.0 112.0 100.0 76.1
kW9.78 9.87 10.0 10.60 10.10 10.10 10.40 10.80 10.30 10.30 10.50 10.90
115
TC 92.5 94.1 103.0 113.0 101.0 101.0 107.0 117.0 107.0 107.0 110.0 120.0
SHC 92.5 89.7 75.1 59.4 101.0 101.0 87.1 67.0 107.0 107.0 97.7 73.9
kW10.50 10.60 11.00 11.40 10.90 10.90 11.20 11.60 11.20 11.20 11.30 11.80
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
23
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 576C120 (cont)
LEGEND
576C120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 122.0 125.0 135.0 147.0 133.0 133.0 141.0 153.0 141.0 141.0 145.0 157.0
SHC 122.0 117.0 97.7 77.1 133.0 133.0 113.0 86.9 141.0 141.0 127.0 96.0
kW8.23 8.28 8.51 8.77 8.47 8.47 8.64 8.88 8.62 8.62 8.72 8.95
85
TC 120.0 122.0 132.0 144.0 130.0 130.0 138.0 149.0 138.0 138.0 142.0 153.0
SHC 120.0 116.0 96.5 76.0 130.0 130.0 112.0 85.6 138.0 138.0 126.0 94.7
kW8.64 8.69 8.94 9.22 8.90 8.90 9.07 9.35 9.07 9.07 9.16 9.42
95
TC 115.0 116.0 126.0 137.0 125.0 125.0 131.0 142.0 132.0 132.0 135.0 145.0
SHC 115.0 113.0 93.9 73.6 125.0 125.0 109.0 83.2 132.0 132.0 123.0 92.3
kW9.46 9.50 9.78 10.10 9.76 9.76 9.95 10.30 9.97 9.97 10.10 10.40
100
TC 113.0 113.0 123.0 134.0 122.0 122.0 128.0 139.0 129.0 129.0 131.0 141.0
SHC 113.0 111.0 92.6 72.4 122.0 122.0 108.0 82.0 129.0 129.0 121.0 91.1
kW9.86 9.89 10.20 10.60 10.20 10.20 10.40 10.70 10.40 10.40 10.50 10.80
105
TC 110.0 111.0 119.0 130.0 119.0 119.0 124.0 135.0 126.0 126.0 128.0 138.0
SHC 110.0 109.0 91.4 71.1 119.0 119.0 107.0 80.8 126.0 126.0 120.0 89.9
kW10.30 10.30 10.60 11.00 10.60 10.60 10.80 11.20 10.80 10.80 10.90 11.30
115
TC 105.0 105.0 113.0 123.0 114.0 114.0 117.0 127.0 120.0 120.0 121.0 130.0
SHC 105.0 105.0 88.8 68.7 114.0 114.0 104.0 78.4 120.0 120.0 117.0 87.4
kW11.10 11.10 11.40 11.90 11.50 11.50 11.60 12.10 11.70 11.70 11.80 12.20
576C120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 115.0 118.0 129.0 140.0 125.0 126.0 134.0 146.0 132.0 132.0 138.0 149.0
SHC 115.0 110.0 92.3 73.1 125.0 125.0 106.0 81.7 132.0 132.0 119.0 89.6
kW8.08 8.14 8.37 8.62 8.30 8.30 8.48 8.74 8.45 8.45 8.57 8.81
85
TC 113.0 116.0 126.0 137.0 123.0 123.0 131.0 142.0 130.0 130.0 134.0 146.0
SHC 113.0 109.0 91.1 71.9 123.0 123.0 105.0 80.5 130.0 130.0 117.0 88.5
kW8.47 8.53 8.78 9.06 8.71 8.72 8.91 9.18 8.88 8.88 8.99 9.26
95
TC 109.0 110.0 120.0 131.0 118.0 118.0 124.0 136.0 124.0 124.0 128.0 139.0
SHC 109.0 106.0 88.7 69.6 118.0 118.0 102.0 78.2 124.0 124.0 114.0 86.1
kW9.25 9.31 9.60 9.94 9.54 9.54 9.75 10.10 9.73 9.74 9.85 10.20
100
TC 106.0 108.0 116.0 127.0 115.0 115.0 121.0 132.0 121.0 121.0 124.0 135.0
SHC 106.0 104.0 87.5 68.5 115.0 115.0 101.0 77.0 121.0 121.0 113.0 84.9
kW9.64 9.68 9.99 10.40 9.95 9.95 10.10 10.50 10.20 10.20 10.30 10.60
105
TC 104.0 105.0 113.0 124.0 112.0 113.0 118.0 129.0 118.0 118.0 121.0 131.0
SHC 104.0 103.0 86.2 67.3 112.0 113.0 99.7 75.8 118.0 118.0 111.0 83.8
kW10.00 10.10 10.40 10.80 10.40 10.40 10.60 10.90 10.60 10.60 10.70 11.00
115
TC 99.2 99.3 107.0 117.0 107.0 107.0 111.0 121.0 113.0 113.0 114.0 124.0
SHC 99.2 99.3 83.7 64.9 107.0 107.0 97.1 73.5 113.0 113.0 108.0 81.4
kW10.80 10.80 11.20 11.60 11.20 11.20 11.40 11.80 11.40 11.40 11.50 11.90
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
24
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120
LEGEND
569F120/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 112.0 116.0 126.0 136.0 122.0 123.0 131.0 142.0 129.0 129.0 135.0 146.0
SHC 112.0 102.0 85.9 68.8 122.0 119.0 98.8 76.7 129.0 129.0 111.0 84.2
kW7.90 7.94 8.06 8.19 8.01 8.03 8.13 8.27 8.10 8.10 8.18 8.32
85
TC 110.0 114.0 123.0 134.0 120.0 121.0 129.0 140.0 127.0 127.0 133.0 143.0
SHC 110.0 102.0 85.0 67.9 120.0 118.0 97.9 75.8 127.0 127.0 110.0 83.3
kW8.35 8.39 8.51 8.65 8.46 8.47 8.58 8.72 8.55 8.55 8.63 8.77
95
TC 107.0 110.0 119.0 130.0 116.0 117.0 124.0 135.0 123.0 123.0 128.0 138.0
SHC 107.0 99.6 83.2 66.3 116.0 115.0 96.1 74.1 123.0 123.0 108.0 81.6
kW9.24 9.28 9.40 9.56 9.36 9.37 9.48 9.63 9.46 9.46 9.53 9.69
100
TC 105.0 108.0 117.0 127.0 114.0 115.0 122.0 132.0 121.0 121.0 125.0 135.0
SHC 105.0 98.6 82.3 65.4 114.0 114.0 95.1 73.2 121.0 121.0 107.0 80.7
kW9.74 9.78 9.91 10.10 9.87 9.87 9.98 10.10 9.97 9.97 10.00 10.20
105
TC 103.0 106.0 115.0 125.0 112.0 113.0 119.0 129.0 119.0 119.0 123.0 132.0
SHC 103.0 97.5 81.3 64.4 112.0 112.0 94.1 72.3 119.0 119.0 106.0 79.8
kW10.20 10.30 10.40 10.60 10.40 10.40 10.50 10.70 10.50 10.50 10.50 10.70
115
TC 99.7 102.0 110.0 120.0 108.0 108.0 115.0 124.0 115.0 114.0 118.0 127.0
SHC 99.7 95.5 79.5 62.6 108.0 108.0 92.2 70.5 115.0 114.0 104.0 78.0
kW11.20 11.30 11.40 11.60 11.40 11.40 11.50 11.70 11.50 11.50 11.60 11.70
569F120/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 106.0 110.0 119.0 130.0 115.0 116.0 125.0 135.0 121.0 121.0 128.0 138.0
SHC 106.0 97.2 81.5 65.3 115.0 112.0 93.2 72.4 121.0 121.0 104.0 79.0
kW7.83 7.89 7.98 8.11 7.94 7.95 8.05 8.17 8.01 8.01 8.09 8.22
85
TC 104.0 108.0 117.0 127.0 113.0 114.0 123.0 133.0 120.0 120.0 126.0 136.0
SHC 104.0 96.3 80.7 64.5 113.0 111.0 92.3 71.7 120.0 120.0 103.0 78.2
kW8.28 8.33 8.43 8.56 8.38 8.40 8.49 8.63 8.46 8.46 8.54 8.67
95
TC 101.0 105.0 114.0 123.0 110.0 111.0 118.0 128.0 116.0 116.0 122.0 131.0
SHC 101.0 94.5 79.1 63.0 110.0 108.0 90.7 70.2 116.0 116.0 101.0 76.7
kW9.18 9.21 9.33 9.47 9.28 9.29 9.39 9.54 9.36 9.36 9.44 9.58
100
TC 99.7 103.0 111.0 121.0 108.0 109.0 116.0 126.0 114.0 114.0 119.0 129.0
SHC 99.7 93.6 78.3 62.2 108.0 107.0 89.8 69.3 114.0 114.0 100.0 75.9
kW9.67 9.71 9.83 9.97 9.78 9.79 9.90 10.00 9.87 9.87 9.94 10.1
105
TC 98.1 101.0 109.0 119.0 106.0 107.0 114.0 123.0 112.0 112.0 117.0 126.0
SHC 98.1 92.6 77.4 61.3 106.0 106.0 89.0 68.5 112.0 112.0 99.3 75.1
kW10.20 10.20 10.30 10.50 10.30 10.30 10.40 10.60 10.40 10.40 10.40 10.60
115
TC 94.9 97.1 105.0 114.0 103.0 103.0 110.0 119.0 108.0 108.0 112.0 121.0
SHC 94.9 90.6 75.7 59.7 103.0 103.0 87.3 66.8 108.0 108.0 97.5 73.4
kW11.20 11.20 11.30 11.50 11.30 11.30 11.40 11.60 11.40 11.40 11.50 11.60
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
25
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 569F120 (cont)
LEGEND
569F120/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 121.0 123.0 132.0 143.0 131.0 131.0 138.0 148.0 140.0 138.0 143.0 153.0
SHC 121.0 116.0 96.4 75.6 131.0 131.0 112.0 85.1 140.0 138.0 127.0 94.5
kW8.00 8.03 8.14 8.29 8.12 8.12 8.21 8.36 8.24 8.22 8.28 8.42
85
TC 119.0 121.0 130.0 141.0 129.0 129.0 135.0 146.0 138.0 137.0 140.0 150.0
SHC 119.0 115.0 95.5 74.8 129.0 129.0 111.0 84.3 138.0 137.0 126.0 93.6
kW8.45 8.48 8.59 8.74 8.58 8.58 8.67 8.82 8.70 8.68 8.73 8.88
95
TC 115.0 117.0 125.0 136.0 125.0 125.0 131.0 141.0 134.0 133.0 135.0 145.0
SHC 115.0 112.0 93.7 73.1 125.0 125.0 109.0 82.5 134.0 133.0 124.0 91.9
kW9.35 9.37 9.50 9.66 9.49 9.49 9.57 9.73 9.62 9.60 9.64 9.80
100
TC 113.0 115.0 123.0 133.0 123.0 123.0 128.0 138.0 131.0 131.0 132.0 142.0
SHC 113.0 111.0 92.8 72.1 123.0 123.0 108.0 81.6 131.0 131.0 123.0 91.0
kW9.86 9.87 10.0 10.20 10.00 9.99 10.10 10.20 10.10 10.10 10.10 10.30
105
TC 112.0 113.0 121.0 131.0 121.0 121.0 125.0 135.0 129.0 129.0 130.0 139.0
SHC 112.0 110.0 91.8 71.2 121.0 121.0 107.0 80.7 129.0 129.0 122.0 90.0
kW10.40 10.40 10.50 10.70 10.50 10.50 10.60 10.80 10.60 10.60 10.70 10.80
115
TC 108.0 108.0 116.0 126.0 116.0 116.0 120.0 130.0 124.0 124.0 124.0 133.0
SHC 108.0 107.0 89.9 69.4 116.0 116.0 105.0 78.9 124.0 123.0 120.0 88.2
kW11.40 11.40 11.50 11.70 11.50 11.50 11.60 11.80 11.70 11.70 11.70 11.90
569F120/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 114.0 117.0 126.0 137.0 124.0 124.0 131.0 142.0 132.0 130.0 136.0 146.0
SHC 114.0 109.0 91.1 71.7 124.0 124.0 105.0 80.0 132.0 130.0 118.0 88.2
kW7.93 7.96 8.07 8.20 8.03 8.04 8.13 8.27 8.14 8.12 8.19 8.33
85
TC 113.0 115.0 124.0 134.0 122.0 122.0 129.0 139.0 130.0 129.0 133.0 144.0
SHC 113.0 108.0 90.2 70.8 122.0 122.0 104.0 79.2 130.0 129.0 117.0 87.4
kW8.37 8.40 8.51 8.65 8.49 8.49 8.58 8.72 8.59 8.57 8.64 8.78
95
TC 109.0 111.0 120.0 130.0 118.0 118.0 124.0 135.0 126.0 125.0 129.0 139.0
SHC 109.0 106.0 88.5 69.2 118.0 118.0 102.0 77.6 126.0 125.0 115.0 85.8
kW9.27 9.29 9.41 9.56 9.39 9.39 9.48 9.63 9.51 9.48 9.55 9.70
100
TC 107.0 109.0 117.0 127.0 116.0 116.0 122.0 132.0 124.0 123.0 126.0 136.0
SHC 107.0 105.0 87.6 68.3 116.0 116.0 101.0 76.7 124.0 123.0 114.0 84.9
kW9.77 9.79 9.91 10.10 9.90 9.89 9.99 10.10 10.00 9.99 10.10 10.20
105
TC 106.0 107.0 115.0 125.0 114.0 114.0 119.0 129.0 122.0 121.0 124.0 133.0
SHC 106.0 103.0 86.7 67.4 114.0 114.0 100.0 75.8 122.0 121.0 113.0 84.0
kW10.30 10.30 10.40 10.60 10.40 10.40 10.50 10.70 10.50 10.50 10.60 10.70
115
TC 102.0 103.0 110.0 120.0 110.0 110.0 114.0 124.0 118.0 117.0 118.0 128.0
SHC 102.0 101.0 84.8 65.7 110.0 110.0 98.1 74.1 118.0 117.0 111.0 82.3
kW11.30 11.30 11.40 11.60 11.40 11.40 11.50 11.70 11.50 11.50 11.60 11.70
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
569D072-120, 576C120, 569F120
26
ELECTRICAL DATA
569D072-120, 576C120, 569F120 UNITS
LEGEND *Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
VOLTAGE
RANGE* COMPRESSOR FAN MOTORS
(Qty 2)
POWER
SUPPLY
V-Ph-Hz MIN MAXRLA LRA FLA (ea) LRA (ea) MCA MOCP
569D
072
NONE OR DISCONNECT 208/230-3-60 187 254 19.2 146 0.9 1.6 25.8 35
CONVENIENCE OUTLET 30.6 35
NONE OR DISCONNECT 460-3-60 418 506 9.6 73 0.4 0.9 12.8 20
CONVENIENCE OUTLET 15.0 20
NONE OR DISCONNECT 575-3-60 523 632 7.7 58.4 0.4 0.9 10.2 15
CONVENIENCE OUTLET 12.0 15
090
NONE OR DISCONNECT 208/230-3-60 187 254 25.6 190 1.5 3.1 35.0 60
CONVENIENCE OUTLET 39.8 60
NONE OR DISCONNECT 460-3-60 418 506 12.8 95 0.7 1.9 17.4 30
CONVENIENCE OUTLET 19.6 30
NONE OR DISCONNECT 575-3-60 523 632 10.2 76 0.7 1.9 13.8 20
CONVENIENCE OUTLET 15.5 20
120
NONE OR DISCONNECT 208/230-3-60 187 254 37.8 239 1.5 3.1 50.3 60
CONVENIENCE OUTLET 55.1 70
NONE OR DISCONNECT 460-3-60 418 506 17.2 125 0.7 1.9 22.9 30
CONVENIENCE OUTLET 25.1 30
NONE OR DISCONNECT 575-3-60 523 632 13.4 80 0.7 1.9 17.8 25
CONVENIENCE OUTLET 19.5 25
576C 120
NONE OR DISCONNECT 208/230-3-60 187 254 36 198 1.5 3.1 48.0 60
CONVENIENCE OUTLET 52.8 70
NONE OR DISCONNECT 460-3-60 418 506 18 99 0.7 1.9 23.9 35
CONVENIENCE OUTLET 26.1 35
NONE OR DISCONNECT 575-3-60 523 632 14 79 0.7 1.9 18.6 30
CONVENIENCE OUTLET 20.3 30
569F 120
NONE OR DISCONNECT 208/230-3-60 187 254 16 125 1.5 3.1 39.0 50
CONVENIENCE OUTLET 43.8 50
NONE OR DISCONNECT 460-3-60 418 506 8 66.5 0.7 1.9 19.4 25
CONVENIENCE OUTLET 21.6 25
NONE OR DISCONNECT 575-3-60 523 632 6.4 50 0.7 1.9 15.8 20
CONVENIENCE OUTLET 17.5 20
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC National Electrical Code
RLA Rated Load Amps
50TFQ004-012
569D072-120, 576C120, 569F120
27
APPLICATION DATA — 569D072-120, 576C090-120, 569F120
OPERATING LIMITS
NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal condens-
ing unit capacity).
2. Total combined draw of the field-supplied liquid line solenoid valve
and air handler fan contactor must not exceed 22 va. If the speci-
fied va must be exceeded, use a remote relay to control the load.
1. LIQUID LINE — For applications with liquid lift greater than
20 ft, use 1/2-in. liquid line where 3/8in.isshown;use5/8-in.
liquid line where 1/2in. is shown. The maximum liquid lift is
60 ft.
MAXIMUM REFRIGERANT CHARGE
2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
*Unit has one step of unloading.
REFRIGERANT PIPING SIZES
LEGEND
L—Liquid Line S—Suction Line
NOTES:
1. Pipe sizes are based on a 2°F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
REFRIGERANT SPECIALTIES PART NUMBERS
*Bushings required.
Maximum Cooling Outdoor 115 F
Minimum Outdoor Ambient
See Minimum Outdoor-Air
Operating Temperature
table at right.
Minimum Return-Air
Temperature 55 F
Maximum Return-Air
Temperature 95 F
Normal Acceptable Saturation
Suction Temperature Range 25 to 55 F
Maximum Discharge
Temperature 275 F
Minimum Discharge Superheat 60 F
UNIT
SIZER-22 (lb)
569D
072 17.3
090 34.2
120 34.2
576C 120 34.2
569F 120 (2) 17.1
UNIT
SIZE
COMPR
CAPACITY
COND
TEMP
(F)
MINIMUM
OUTDOOR TEMP
(F)
Std
With
Motormaster®
Control
569D
072 100% 90 35
–20
090 100% 90 35
120 100% 90 35
576C 120* 100% 90 35
67% 80 35
569F 120 100% 90 35
UNIT
SIZE
LINEAR LENGTH OF PIPING — FT
0-25 25-50 50-75 75-100
Line Size (in. OD)
LSLSLSLS
569D
072 3/811/83/811/83/811/83/811/8
090 3/811/81/211/81/211/81/211/8
120 1/213/81/213/81/213/81/213/8
576C 120 1/213/81/213/81/213/81/213/8
569F 120 (2) 3/8(2) 11/8(2) 3/8(2) 11/8(2) 3/8(2) 11/8(2) 3/8(2) 11/8
UNIT LIQUID LINE
SIZE (in.)
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
569D072 3/8200RB5T3M AMG/24V AMI-1TT3 P502-8304S* S-7063S*
569D090
3/8200RB5T3M AMG/24V AMI-1TT3 P502-8304S* S-7063S*
1/2200RB5T4M AMG/24V AMI-1TT4 P502-8304S S-7063S*
569D120 1/2200RB6T4M AMG/24V AMI-1TT4 P502-8307S* S-7063
576C120
1/2200RB6T4M AMG/24V AMI-1TT4 P502-8307S* S-7063
3/8200RB5T3M Qty 2 AMG/24V Qty 2 AMI-1TT3 Qty 2 P502-8304S* Qty 2 S-7061 Qty 2
50TFQ004-012
569D072-120, 576C120, 569F120
28
TYPICAL PIPING AND WIRING
CONDENSING
UNIT
FIELD
SUPPLIED
POWER
INSULATED
VAPOR
LINE
PITCH
WEATHERPROOF
FUSED DISCONNECT*
PER NEC
POWER WIRES
MOISTURE
INDICATOR
SIGHT GLASS*
ELECTRIC
HEATER
ACCESSORY
524A
UNIT
LIQUID
LINE
FILTER
DRIER*
CONDENSATE DRAIN
POWER WIRES
CONTROL
WIRES
INDOOR
THERMOSTAT†
FUSED DISCONNECT
PER NEC
TO OPEN SIGHT
DRAIN
LLSV*
LEGEND
*Field supplied.
†Accessory item.
LLSV — Liquid Line Solenoid Valve
NEC National Electrical Code
TXV—Thermostatic Expansion Valve
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refriger-
ant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Rooftop Installation — 569D072-120, 576C120
50TFQ004-012
569D072-120, 576C120, 569F120
29
GUIDE SPECIFICATIONS — 569D072-120, 576C120
COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 6 TO 10 TONS, NOMINAL
BRYANT MODEL NUMBERS: 569D, SIZES 072-120
576C, SIZE 120
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
reciprocating air-conditioning compressor assembly
(576C) or scroll compressor (569D), an air-cooled coil,
propeller-type condenser fan, and a control box. Unit shall
discharge supply air upward as shown on contract draw-
ings. Unit shall be used in a refrigeration circuit matched
with a packaged air-handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI latest
revisions.
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
E. Air-cooled condenser coils for semi-hermetic compressor
units (576C) shall be leak tested at 150 psig and pressure
tested at 480 psig. Air-cooled condenser coils for scroll
compressor units (569D) shall be leak tested at 200 psig,
and pressure tested at 428 psig.
F. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facil-
itate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.
D. Compressor:
1. Compressor shall be of the scroll type (569D) or
semi-hermetic reciprocating type (576C).
2. Compressors shall be mounted on vibration
isolators.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressor shall be equipped with internal high dis-
charge temperature protection (569D072 and 120
only).
6. Compressor shall unload using suction cutoff unload-
ing (576C120 only). Electric solenoid unloading
available as an accessory.
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include liquid line
service valve, suction line service valve, liquid filter drier,
a full charge of compressor oil, and a holding charge of
refrigerant. Unit 569D120 shall include an accumulator.
Units with semi-hermetic compressors (576C) shall have
oil-level sight glass and all units shall have crankcase
heater.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
a. High discharge pressure cutout.
b. Low Pressure cutout.
c. High discharge temperature cutout (569D090
only).
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed Btuh at a suction temperature of ______ F.
The power consumption at full load shall not exceed
______ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of ______ Btuh or greater at conditions
of ______ cfm entering-air temperature at the evapo-
rator at ______ F wet bulb and ______ F dry bulb,
and air entering the condensing unit at ______ F.
3. The system shall have an EER of ______ Btuh/Watt
or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
______ v, 3-ph, 60 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
______ v to ______ v.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.
50TFQ004-012
569D072-120, 576C120, 569F120
30
GUIDE SPECIFICATIONS — 569D072-120, 576C120 (cont)
J. Special Features:
1. Low-Ambient Temperature Control Accessory:
Low-ambient control shall be available as a factory-
installed option or a field-installed accessory and
shall regulate speed of condenser-fan motor in
response to the saturated condensing temperature
of the unit. The control shall maintain correct con-
densing pressure at outdoor temperatures down to
–20 F (fan motor change required for 569D and
576C units).
2. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal envi-
ronments. Coating shall be applied to the alumi-
num fin stock prior to the fin stamping process to
create an inert barrier between the aluminum
fin and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.
b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating uni-
formly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60°of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness char-
acteristics of 2H per ASTM D3363-92A and cross
hatch adhesion of 4B-5B per ASTM D3359-93.
Impact resistance shall be up to 160 in./lb (ASTM
D2794-93). Humidity and water immersion resis-
tance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be con-
firmed through testing to no less than 1000 hours
salt spray per ASTM B117-90. Coil construction
shall be aluminum-fins mechanically bonded to
copper tubes.
3. Thermostat Control Accessory:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capacity,
and large LCD display.
4. Hail Guard Accessory:
Hail guard package shall protect coils against dam-
age from hail and other flying debris.
5. Condenser Coil Grille Accessory:
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
6. Electric Solenoid Unloader Accessory:
Electric unloader valve piston, coil, and hardware
shall be supplied to convert the pressure-operated
compressor unloader to electric unloading (576C120
only).
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
8. Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
50TFQ004-012
569D072-120, 576C120, 569F120
31
GUIDE SPECIFICATIONS — 569F120
COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 10 TONS, NOMINAL
BRYANT MODEL NUMBER: 569F, SIZE 120
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall have
2 independent refrigeration circuits. Unit shall consist of
dual scroll compressors, air-cooled coils, propeller-type
condenser fans, and a control box. Unit shall discharge
supply air upward as shown on contract drawings. Unit
shall be used in a refrigeration circuit matched with a pack-
aged air-handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard 210/
240, latest revision.
B. Unit construction shall comply with ANSI/ASHRAE 15
safety code latest revision and comply with NEC.
C. Unit shall be constructed in accordance with UL 1995
standard and shall carry the UL and UL, Canada label.
D. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
E. Air-cooled condenser coils shall be leak tested at
200 psig, and pressure tested at 428 psig.
F. UnitshallbemanufacturedinafacilityregisteredtoISO
9001:2000 manufacturing quality standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and shall be
stored and handled according to unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
enamel finish.
2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to facil-
itate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller-type,
discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC coated steel wire safety guards.
4. Condenser fan and motor shaft shall be corrosion
resistant.
D. Compressor:
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on vibration isolators.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressors shall be equipped with high discharge
temperature protection.
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper
fins optional) mechanically bonded to internally
grooved seamless copper tubes which are then
cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include liquid
line service valve, suction line service valve, a full
charge of compressor oil, and a holding charge of
refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat),
shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall not
exceed _____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
3. The system shall have an EER of _____ Btuh/ Watt
or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be _____
v, 3-ph, 60 Hz. The unit shall be capable of satisfac-
tory operation within voltage limits of _____ v to
_____ v.
2. Unit electrical power shall be single-point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be available
as a factory-installed option or as a field-installed
accessory. This low-ambient control shall regulate
speed of the condenser-fan motors in response to
the saturated condensing temperature of the unit.
The control shall maintain correct condensing pres-
sure at outdoor temperatures down to –20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and dis-
charge pressure gage.
50TFQ004-012
569D072-120, 576C120, 569F120
32
GUIDE SPECIFICATIONS 569F120 (cont)
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating
uniformly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60° of 65 to 90% per ASTM D523-89. Uniform
dry film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A
and cross hatch adhesion of 4B-5B per ASTM
D3359-93. Impact resistance shall be up to
160 in./lb (ASTM D2794-93). Humidity and water
immersion resistance shall be up to a minimum
of 1000 and 250 hours respectively (ASTM
D2247-92 and ASTM D870-92). Corrosion dura-
bility shall be confirmed through testing to no less
than 1000 hours salt spray per ASTM B117-90.
Coil construction shall be aluminum fins mechani-
cally bonded to copper tubes.
4. Thermostat Controls:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
5. Hail Guard Package:
Hail guard package shall protect coils against dam-
age from hail and other flying debris.
6. Condenser Coil Grille:
Grille shall add decorative appearance to unit and
protect condenser coil after installation.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
8. Convenience Outlet:
Shall be factory-installed and internally mounted with
easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
50TFQ004-012
569D072-120, 576C120, 569F120
33
MODEL NUMBER NOMENCLATURE
566D E X 150 000
––
Nominal Tons Cooling
150 — 12-1/2
180 — 15
240 — 20
Heating Capacity
000 — No Heat
Factory-Installed Options*
Heating
X—None
566D Commercial Air-Cooled Condensing
Unit With Semi-Hermetic Compressor
566E Dual Circuit Commercial Air-Cooled
Condensing Unit With Scroll Compressors
Voltage Designation
E — 460-3-60
P — 208/230-3-60
T — 575-3-60
*Contact your local representative for more details.
Certified to ISO 9001:2000
Quality Assurance
50TFQ004-012
566D/E150-240
34
PHYSICAL DATA
566D150-240 UNITS
*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system
capacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 120 F.
UNIT 566D150 566D180 566D240
NOMINAL CAPACITY (tons) 121/215 20
OPERATING WEIGHTS (lb)
Aluminum-Fin Coil (Standard) 779 789 929
Copper-Fin Coil (Optional) 919 929 1040
REFRIGERANT TYPE* R-22
Operating Charge, Typical (lb)† 23 23 28
Shipping Charge (lb) 3.1 3.1 3.1
COMPRESSOR Reciprocating, Semi-Hermetic
Qty...Model 1...06DD328 1...06DD537 1...06E4250
No. Cylinders 664
Speed (rpm) 1750 1750 1750
Oil Charge (pt) 10 10 15.5
Capacity Steps
Accessory 33**, 66, 100 33**, 66, 100
Standard 66, 100 66, 100 50, 100
Unloader Setting (psig)
Load 70 ± 1
Unload 60 ± 2
Crankcase Heater Watts 125
CONDENSER FANS Axial Flow, Direct Drive
Qty...Rpm 2...1075
Diameter (in.) 26
Nominal Hp 1/2
Nominal Airflow (cfm, total) 11,000
Watts (total) 1460
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/in. 3...15 3...15 3...15
Face Area (sqft) 29.2 29.2 29.2
Storage Capacity (lb)†† 48 48 38
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 395 ± 10
Cut-in 295 ± 20
Low Pressure
Cutout 27 ± 4
Cut-in 67 ± 7
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close 255 ± 10
Open 160 ± 10
PRESSURE RELIEF
Location Liquid Line
Temperature (F) 200
PIPING CONNECTIONS (in. ODM)
Suction 13/813/815/8
Liquid 5/8
Hot Gas Stub 3/8
50TFQ004-012
566D/E150-240
35
PHYSICAL DATA (cont)
566E150-240 UNITS
*Unit is factory-supplied with holding charge only.
†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for
maximum system capacity.
**Storage capacity is measured at liquid saturated temperatures of 120 F.
UNIT 566E150 566E180 566E240
NOMINAL CAPACITY (tons) 121/215 20
OPERATING WEIGHTS (lb)
Aluminum-Fin Coil (Standard) 676 740 764
Copper-Fin Coil (Optional) 822 886 904
REFRIGERANT TYPE* R-22
Operating Charge, Typical (lb)† 23 23 28
Shipping Charge (lb) 3.1 3.1 3.1
COMPRESSOR Scroll
Qty...Model 2...ZR72 2...ZR94 2...ZR125
Speed (rpm) 3500 3500 3500
Oil Charge (oz) 60 (ea) 85 (ea) 110 (ea)
Crankcase Heater Watts 70
CONDENSER FANS
Qty...Rpm 2...1075
Diameter (in.) 26
Nominal Hp 1/2
Nominal Airflow (cfm, total) 11,000
Watts (total) 1460
CONDENSER COIL
Rows...Fins/in. 3...15
Face Area (sqft) 29.2
Storage Capacity (lb)** 48
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 426 ± 7
Cut-in 320 ± 20
Low Pressure
Cutout 27 ± 4
Cut-in 67 ± 7
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close 255 ± 10
Open 160 ± 10
PRESSURE RELIEF
Location Liquid Line
Temperature (F) 200
PIPING CONNECTIONS (in. ODM)
Suction (2) 13/8
Liquid (2) 1/2
Hot Gas Stub 3/8
50TFQ004-012
566D/E150-240
36
DIMENSIONS
566D150-240
NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2ft
Side (opposite compressor) — 3 ft
Ends—2ft
Top—5ft
2. See page 38 for corner weights and
unit center of gravity.
50TFQ004-012
566D/E150-240
37
DIMENSIONS (cont)
NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2ft (1067 mm)
Side (opposite compressor) — 3 ft (914 mm)
Ends — 2 ft (610 mm)
Top — 5 ft (1524 mm)
2. See page 38 for corner weights and unit
center of gravity.
566E150-240
50TFQ004-012
566D/E150-240
38
DIMENSIONS (cont)
566D150-240, 566E150-240
566D150-240
UNIT
566D
ALUMINUM COIL
Standard
Weight
(lb)
Operational Weight Points (lb)
ABCD E F
150 779 70 177 68 100 261 103
180 789 70 180 69 101 265 104
240 900 84 234 82 108 310 111
UNIT
566D
CENTER OF GRAVITY (in.)
Aluminum Coil
XY
150 38 16
180 38 16
240 37 17
566E150-240
UNIT
566E
ALUMINUM COIL
Standard
Weight
(lb)
Operational Weight Points (lb)
ABCDE F
150 676 84 168 72 78 183 91
180 740 86 186 71 82 216 99
240 764 87 192 72 85 226 102
UNIT
566E
CENTER OF GRAVITY (in.)
Aluminum Coil
XY
150 35 19
180 35 18
240 35 18
NOTES:
1. Corner weights are approximate.
2. Actual support weights depend on level of unit and evenness of support posts.
3. Total weights represent approximate unit weights without shipping package.
4. Bottom or top skid is NOT included in the weights.
50TFQ004-012
566D/E150-240
39
PERFORMANCE DATA
CONDENSING UNIT RATINGS
LEGEND
566D150
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 101.0 97.6 90.0 86.0 82.2 74.7
kW8.56 8.90 9.55 9.85 10.20 10.70
SDT 94.6 99.4 109.0 114.0 119.0 129.0
30
TC 118.0 113.0 105.0 101.0 96.7 88.5
kW8.80 9.17 9.90 10.20 10.60 11.20
SDT 96.6 101.0 111.0 116.0 121.0 131.0
35
TC 134.0 129.0 120.0 116.0 111.0 102.0
kW9.03 9.44 10.20 10.60 11.00 11.70
SDT 98.6 103.0 113.0 117.0 122.0 132.0
40
TC 150.0 145.0 135.0 130.0 126.0 116.0
kW9.26 9.71 10.60 11.00 11.40 12.20
SDT 101.0 105.0 115.0 119.0 124.0 134.0
45
TC 166.0 161.0 150.0 145.0 140.0 130.0
kW9.50 9.98 10.90 11.40 11.80 12.70
SDT 103.0 107.0 116.0 121.0 126.0 135.0
50
TC 182.0 177.0 166.0 160.0 155.0 144.0
kW9.73 10.30 11.30 11.70 12.20 13.10
SDT 105.0 109.0 118.0 123.0 127.0 136.0
566D180
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 139.0 134.0 126.0 121.0 117.0 108.0
kW12.30 12.70 13.60 14.00 14.40 15.10
SDT 99.5 104.0 114.0 118.0 123.0 133.0
30
TC 159.0 154.0 144.0 139.0 134.0 125.0
kW12.90 13.40 14.30 14.70 15.20 16.00
SDT 102.0 107.0 116.0 121.0 125.0 135.0
35
TC 179.0 173.0 163.0 157.0 152.0 142.0
kW13.50 14.00 15.00 15.50 16.00 16.90
SDT 105.0 109.0 119.0 123.0 128.0 137.0
40
TC 198.0 192.0 181.0 175.0 170.0 158.0
kW14.00 14.60 15.70 16.30 16.80 17.80
SDT 108.0 112.0 121.0 125.0 130.0 139.0
45
TC 218.0 212.0 199.0 193.0 187.0 175.0
kW14.60 15.20 16.50 17.00 17.60 18.70
SDT 110.0 115.0 124.0 128.0 132.0 141.0
50
TC 237.0 231.0 218.0 211.0 205.0 192.0
kW15.20 15.90 17.20 17.80 18.40 19.60
SDT 113.0 117.0 126.0 130.0 135.0 144.0
566D240
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC 175.0 169.0 157.0 151.0 145.0 134.0
kW16.30 16.80 17.70 18.20 18.60 19.40
SDT 104.0 108.0 117.0 122.0 126.0 135.0
30
TC 200.0 193.0 180.0 173.0 166.0 154.0
kW17.20 17.80 18.80 19.30 19.80 20.70
SDT 107.0 111.0 120.0 125.0 129.0 138.0
35
TC 224.0 217.0 202.0 195.0 188.0 175.0
kW18.20 18.80 19.90 20.50 21.00 22.00
SDT 110.0 115.0 123.0 128.0 132.0 141.0
40
TC 249.0 241.0 225.0 218.0 210.0 195.0
kW19.10 19.80 21.00 21.60 22.20 23.30
SDT 114.0 118.0 126.0 131.0 135.0 144.0
45
TC 273.0 265.0 248.0 240.0 232.0 216.0
kW20.10 20.80 22.10 22.70 23.40 24.60
SDT 117.0 121.0 129.0 134.0 138.0 146.0
50
TC 297.0 289.0 271.0 262.0 253.0 236.0
kW21.00 21.80 23.20 23.90 24.60 25.90
SDT 120.0 124.0 132.0 137.0 141.0 149.0
kW—Compressor Power
SDT — Saturated Discharge Temperature at Compressor (F)
SST — Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
566E150
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
20
TC 102.0 99.1 93.2 90.3 87.3 81.1
kW9.04 9.58 10.80 11.40 12.10 13.50
SDT 103.0 108.0 118.0 123.0 128.0 138.0
25
TC 114.0 111.0 105.0 102.0 98.8 92.2
kW9.09 9.64 10.90 11.50 12.20 13.60
SDT 103.0 108.0 118.0 123.0 128.0 138.0
30
TC 127.0 124.0 117.0 114.0 110.0 103.0
kW9.14 9.70 10.90 11.50 12.20 13.70
SDT 103.0 108.0 118.0 123.0 128.0 138.0
35
TC 140.0 137.0 130.0 126.0 123.0 115.0
kW9.19 9.75 11.00 11.60 12.30 13.70
SDT 103.0 108.0 118.0 123.0 128.0 138.0
40
TC 155.0 151.0 144.0 140.0 136.0 128.0
kW9.26 9.81 11.00 11.70 12.30 13.80
SDT 103.0 108.0 118.0 123.0 128.0 138.0
45
TC 170.0 166.0 158.0 154.0 150.0 141.0
kW9.37 9.90 11.10 11.70 12.40 13.90
SDT 103.0 108.0 118.0 123.0 128.0 138.0
50
TC 186.0 182.0 173.0 169.0 164.0 155.0
kW9.55 10.10 11.30 11.90 12.60 14.00
SDT 104.0 109.0 119.0 124.0 129.0 139.0
566E180
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
20
TC 141.0 137.0 129.0 124.0 120.0 110.0
kW12.01 12.60 13.70 14.30 14.90 16.10
SDT 101.0 105.0 115.0 120.0 125.0 135.0
25
TC 156.0 152.0 143.0 138.0 133.0 123.0
kW12.40 12.90 14.00 14.60 15.20 16.40
SDT 102.0 107.0 116.0 121.0 126.0 136.0
30
TC 171.0 166.0 157.0 152.0 147.0 136.0
kW12.70 13.20 14.30 14.90 15.50 16.70
SDT 104.0 108.0 118.0 123.0 127.0 137.0
35
TC 187.0 182.0 172.0 166.0 161.0 150.0
kW13.10 13.60 14.70 15.30 15.90 17.10
SDT 105.0 110.0 119.0 12.04 129.0 138.0
40
TC 203.0 198.0 187.0 181.0 176.0 164.0
kW13.50 14.00 15.10 15.70 16.30 17.50
SDT 107.0 112.0 121.0 126.0 130.0 140.0
45
TC 221.0 215.0 204.0 198.0 192.0 179.0
kW13.90 14.50 15.60 16.10 16.70 17.90
SDT 109.0 114.0 123.0 127.0 132.0 141.0
50
TC 239.0 233.0 221.0 215.0 208.0 195.0
kW14.40 14.90 16.10 16.70 17.20 18.40
SDT 111.0 116.0 125.0 129.0 134.0 143.0
566E240
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
20
TC 184.0 179.0 170.0 165.0 160.0 148.0
kW16.20 17.00 18.50 19.40 20.20 21.70
SDT 105.0 110.0 119.0 124.0 129.0 139.0
25
TC 202.0 197.0 186.0 181.0 176.0 163.0
kW16.80 17.50 19.00 19.80 20.60 22.20
SDT 107.0 112.0 121.0 126.0 131.0 140.0
30
TC 220.0 214.0 203.0 197.0 191.0 179.0
kW17.30 18.00 19.50 20.30 21.10 22.70
SDT 109.0 113.0 123.0 127.0 132.0 141.0
35
TC 239.0 233.0 220.0 214.0 208.0 194.0
kW18.00 18.60 20.10 20.80 21.60 23.20
SDT 111.0 116.0 125.0 129.0 134.0 143.0
40
TC 259.0 253.0 239.0 232.0 225.0 211.0
kW18.70 19.30 20.70 21.50 22.20 23.80
SDT 113.0 118.0 127.0 131.0 136.0 145.0
45
TC 280.0 273.0 259.0 252.0 244.0 229.0
kW19.40 20.10 21.50 22.20 22.90 24.50
SDT 116.0 120.0 129.0 134.0 138.0 147.0
50
TC 302.0 295.0 280.0 272.0 264.0 247.0
kW20.20 20.90 22.30 23.00 23.70 25.20
SDT 118.0 123.0 132.0 136.0 140.0 149.0
50TFQ004-012
566D/E150-240
40
PERFORMANCE DATA (cont)
COMBINATION RATINGS
UNIT 566D150
LEGEND
566D150/524A-C150 WITH HIGH CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 133.0 139.0 151.0 165.0 146.0 147.0 158.0 172.0 154.0 154.0 163.0 177.0
SHC 133.0 123.0 103.0 83.1 146.0 142.0 119.0 92.7 154.0 154.0 133.0 101.0
kW9.00 9.07 9.27 9.48 9.18 9.20 9.38 9.59 9.32 9.32 9.45 9.66
85
TC 131.0 136.0 148.0 161.0 143.0 144.0 155.0 169.0 152.0 151.0 160.0 173.0
SHC 131.0 122.0 102.0 81.9 143.0 140.0 117.0 91.3 152.0 151.0 131.0 100.0
kW9.44 9.54 9.75 9.99 9.66 9.69 9.88 10.10 9.82 9.81 9.96 10.20
95
TC 126.0 130.0 142.0 155.0 138.0 138.0 148.0 161.0 146.0 146.0 153.0 165.0
SHC 126.0 119.0 99.5 79.3 138.0 137.0 115.0 88.8 146.0 146.0 128.0 97.5
kW10.40 10.50 10.70 11.00 10.60 10.60 10.90 11.20 10.80 10.80 11.00 11.30
100
TC 123.0 127.0 138.0 151.0 135.0 135.0 145.0 157.0 143.0 143.0 149.0 161.0
SHC 123.0 117.0 98.2 78.0 135.0 134.0 113.0 87.5 143.0 143.0 127.0 96.2
kW10.80 10.90 11.20 11.50 11.10 11.10 11.30 11.70 11.30 11.30 11.50 11.80
105
TC 121.0 124.0 135.0 148.0 132.0 132.0 141.0 154.0 140.0 140.0 145.0 157.0
SHC 121.0 116.0 96.8 76.8 132.0 132.0 112.0 86.1 140.0 140.0 125.0 94.8
kW11.30 11.40 11.70 12.00 11.60 11.60 11.80 12.20 11.80 11.80 12.00 12.30
115
TC 116.0 118.0 129.0 141.0 127.0 127.0 134.0 146.0 134.0 134.0 138.0 149.0
SHC 116.0 113.0 94.1 74.2 127.0 127.0 109.0 83.5 134.0 134.0 122.0 92.2
kW12.20 12.30 12.60 13.00 12.50 12.50 12.80 13.20 12.80 12.80 12.90 13.30
566D150/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 127.0 134.0 146.0 160.0 140.0 142.0 153.0 167.0 148.0 148.0 158.0 172.0
SHC 127.0 118.0 99.4 80.2 140.0 136.0 114.0 89.0 148.0 148.0 126.0 96.9
kW8.93 9.01 9.19 9.40 9.09 9.12 9.31 9.51 9.22 9.22 9.37 9.58
85
TC 125.0 131.0 143.0 156.0 137.0 139.0 150.0 163.0 145.0 145.0 154.0 168.0
SHC 125.0 117.0 98.2 78.9 137.0 134.0 112.0 87.6 145.0 145.0 125.0 95.6
kW9.37 9.45 9.67 9.90 9.55 9.58 9.79 10.00 9.70 9.71 9.87 10.10
95
TC 121.0 125.0 137.0 150.0 132.0 133.0 143.0 156.0 140.0 140.0 147.0 160.0
SHC 121.0 114.0 95.6 76.4 132.0 130.0 110.0 85.1 140.0 140.0 122.0 93.0
kW10.30 10.30 10.60 10.90 10.50 10.50 10.70 11.00 10.70 10.70 10.80 11.10
100
TC 118.0 122.0 134.0 146.0 129.0 130.0 140.0 152.0 137.0 137.0 144.0 156.0
SHC 118.0 112.0 94.3 75.2 129.0 128.0 108.0 83.8 137.0 137.0 121.0 91.7
kW10.70 10.80 11.10 11.40 11.00 11.00 11.20 11.60 11.20 11.20 11.30 11.70
105
TC 116.0 119.0 131.0 143.0 127.0 127.0 136.0 149.0 134.0 134.0 140.0 153.0
SHC 116.0 111.0 92.9 73.9 127.0 126.0 107.0 82.5 134.0 134.0 119.0 90.4
kW11.20 11.20 11.50 11.90 11.40 11.40 11.70 12.10 11.60 11.60 11.80 12.20
115
TC 111.0 113.0 124.0 136.0 121.0 121.0 129.0 141.0 128.0 128.0 133.0 145.0
SHC 111.0 108.0 90.3 71.4 121.0 121.0 104.0 79.9 128.0 128.0 116.0 87.8
kW12.00 12.10 12.50 12.90 12.40 12.40 12.60 13.10 12.60 12.60 12.80 13.20
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
41
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D150 (cont)
LEGEND
566D150/524A-C180 WITH HIGH CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 142.0 145.0 157.0 171.0 154.0 154.0 164.0 178.0 163.0 163.0 168.0 182.0
SHC 142.0 136.0 114.0 89.6 154.0 154.0 131.0 100.0 163.0 163.0 146.0 110.0
kW9.13 9.17 9.37 9.57 9.31 9.32 9.47 9.66 9.44 9.45 9.53 9.72
85
TC 140.0 142.0 154.0 168.0 151.0 151.0 160.0 174.0 160.0 160.0 165.0 178.0
SHC 140.0 134.0 112.0 88.3 151.0 151.0 129.0 99.1 160.0 160.0 145.0 109.0
kW9.60 9.65 9.86 10.10 9.81 9.81 9.97 10.20 9.96 9.96 10.00 10.30
95
TC 134.0 136.0 147.0 160.0 146.0 146.0 153.0 166.0 153.0 153.0 157.0 170.0
SHC 134.0 131.0 109.0 85.7 146.0 146.0 127.0 96.4 153.0 153.0 142.0 106.0
kW10.50 10.60 10.80 11.20 10.80 10.80 11.00 11.30 11.00 11.00 11.10 11.40
100
TC 132.0 133.0 144.0 157.0 143.0 143.0 150.0 162.0 150.0 150.0 154.0 166.0
SHC 132.0 129.0 108.0 84.4 143.0 143.0 125.0 95.1 150.0 150.0 140.0 105.0
kW11.00 11.10 11.30 11.70 11.30 11.30 11.50 11.80 11.50 11.50 11.60 11.90
105
TC 129.0 130.0 140.0 153.0 140.0 140.0 146.0 158.0 147.0 147.0 150.0 162.0
SHC 129.0 127.0 107.0 83.1 140.0 140.0 124.0 93.8 147.0 147.0 138.0 104.0
kW11.50 11.50 11.80 12.20 11.80 11.80 12.00 12.30 12.00 12.00 12.10 12.40
115
TC 124.0 124.0 133.0 146.0 134.0 134.0 139.0 150.0 140.0 140.0 142.0 153.0
SHC 124.0 123.0 104.0 80.5 134.0 134.0 121.0 91.0 140.0 140.0 135.0 101.0
kW12.40 12.50 12.80 13.20 12.80 12.80 13.00 13.40 13.00 13.00 13.10 13.50
566D150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 140.0 144.0 156.0 170.0 152.0 152.0 162.0 176.0 160.0 160.0 167.0 181.0
SHC 140.0 134.0 112.0 88.3 152.0 152.0 128.0 98.7 160.0 160.0 143.0 108.0
kW9.09 9.14 9.34 9.55 9.28 9.28 9.44 9.65 9.41 9.41 9.51 9.71
85
TC 137.0 140.0 152.0 166.0 149.0 149.0 159.0 172.0 157.0 157.0 163.0 176.0
SHC 137.0 132.0 110.0 87.0 149.0 149.0 127.0 97.3 157.0 157.0 142.0 107.0
kW9.56 9.61 9.84 10.10 9.78 9.77 9.94 10.20 9.92 9.92 10.00 10.20
95
TC 132.0 134.0 146.0 159.0 143.0 143.0 151.0 165.0 151.0 151.0 155.0 168.0
SHC 132.0 129.0 107.0 84.4 143.0 143.0 124.0 94.6 151.0 151.0 138.0 104.0
kW10.50 10.50 10.80 11.10 10.70 10.70 10.90 11.20 10.90 10.90 11.00 11.30
100
TC 130.0 131.0 142.0 155.0 140.0 140.0 148.0 161.0 148.0 148.0 152.0 164.0
SHC 130.0 127.0 106.0 83.1 140.0 140.0 123.0 93.3 148.0 148.0 137.0 103.0
kW11.00 11.00 11.30 11.60 11.30 11.20 11.40 11.80 11.40 11.40 11.50 11.80
105
TC 127.0 128.0 139.0 151.0 137.0 137.0 144.0 157.0 145.0 145.0 148.0 160.0
SHC 127.0 125.0 105.0 81.7 137.0 137.0 12.01 91.9 145.0 145.0 135.0 101.0
kW11.40 11.50 11.80 12.10 11.70 11.70 11.90 12.30 11.90 11.90 12.00 12.40
115
TC 121.0 122.0 131.0 144.0 131.0 131.0 136.0 148.0 138.0 138.0 140.0 152.0
SHC 121.0 121.0 102.0 79.0 131.0 131.0 118.0 89.2 138.0 138.0 132.0 98.7
kW12.40 12.40 12.70 13.10 12.70 12.70 12.90 13.30 12.90 12.90 13.00 13.40
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
42
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180
LEGEND
566D180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 167.0 177.0 192.0 209.0 183.0 187.0 202.0 219.0 194.0 195.0 208.0 225.0
SHC 167.0 152.0 128.0 104.0 183.0 175.0 146.0 115.0 194.0 193.0 163.0 125.0
kW13.10 13.40 13.90 14.40 13.60 13.70 14.10 14.70 13.90 13.90 14.30 14.80
85
TC 165.0 174.0 189.0 205.0 180.0 184.0 198.0 214.0 191.0 192.0 204.0 220.0
SHC 165.0 150.0 127.0 102.0 180.0 174.0 145.0 113.0 191.0 191.0 161.0 124.0
kW13.70 14.00 14.50 15.00 14.20 14.30 14.80 15.30 14.60 14.60 15.00 15.50
95
TC 160.0 167.0 182.0 197.0 174.0 177.0 190.0 206.0 185.0 185.0 196.0 211.0
SHC 160.0 147.0 123.0 99.3 174.0 170.0 141.0 110.0 185.0 185.0 158.0 120.0
kW14.90 15.20 15.70 16.40 15.50 15.60 16.10 16.70 15.90 15.90 16.30 16.90
100
TC 157.0 164.0 178.0 193.0 171.0 173.0 186.0 202.0 181.0 181.0 191.0 207.0
SHC 157.0 145.0 122.0 97.8 171.0 168.0 140.0 109.0 181.0 181.0 156.0 119.0
kW15.50 15.80 16.40 17.00 16.10 16.20 16.70 17.40 16.50 16.50 17.00 17.60
105
TC 154.0 160.0 174.0 189.0 168.0 169.0 182.0 197.0 178.0 178.0 187.0 202.0
SHC 154.0 144.0 120.0 96.3 168.0 165.0 138.0 107.0 178.0 178.0 154.0 117.0
kW16.00 16.30 17.00 17.70 16.70 16.80 17.40 18.10 17.20 17.20 17.60 18.30
115
TC 148.0 153.0 166.0 181.0 162.0 162.0 174.0 188.0 171.0 171.0 178.0 193.0
SHC 148.0 140.0 117.0 93.2 162.0 161.0 135.0 104.0 171.0 171.0 151.0 114.0
kW17.30 17.50 18.20 19.00 18.00 18.00 18.60 19.40 18.50 18.50 18.90 19.70
566D180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 165.0 175.0 190.0 207.0 180.0 185.0 200.0 217.0 191.0 193.0 206.0 223.0
SHC 165.0 149.0 126.0 102.0 180.0 172.0 143.0 113.0 191.0 190.0 159.0 123.0
kW13.00 13.30 13.80 14.30 13.50 13.60 14.10 14.60 13.80 13.90 14.30 14.80
85
TC 162.0 171.0 187.0 203.0 177.0 181.0 196.0 213.0 188.0 189.0 202.0 218.0
SHC 162.0 148.0 125.0 101.0 177.0 170.0 142.0 112.0 188.0 187.0 158.0 121.0
kW13.60 13.90 14.40 15.00 14.10 14.20 14.70 15.30 14.50 14.50 14.90 15.50
95
TC 157.0 165.0 179.0 195.0 171.0 174.0 188.0 204.0 182.0 182.0 193.0 209.0
SHC 157.0 144.0 121.0 97.9 171.0 166.0 139.0 108.0 182.0 181.0 154.0 118.0
kW14.80 15.10 15.70 16.30 15.30 15.50 16.00 16.60 15.80 15.80 16.20 16.90
100
TC 154.0 161.0 176.0 191.0 168.0 170.0 184.0 199.0 178.0 178.0 189.0 205.0
SHC 154.0 143.0 120.0 96.3 168.0 164.0 137.0 107.0 178.0 178.0 153.0 117.0
kW15.30 15.70 16.30 17.00 16.00 16.10 16.70 17.30 16.40 16.40 16.90 17.50
105
TC 151.0 158.0 172.0 187.0 165.0 167.0 180.0 195.0 175.0 175.0 185.0 200.0
SHC 151.0 141.0 118.0 94.8 165.0 162.0 135.0 105.0 175.0 175.0 151.0 115.0
kW15.90 16.20 16.90 17.60 16.60 16.70 17.30 18.00 17.00 17.00 17.50 18.20
115
TC 146.0 151.0 164.0 179.0 159.0 160.0 171.0 186.0 168.0 168.0 176.0 191.0
SHC 146.0 137.0 115.0 91.7 159.0 157.0 132.0 102.0 168.0 168.0 147.0 112.0
kW17.10 17.40 18.10 18.90 17.80 17.90 18.50 19.30 18.30 18.30 18.80 19.50
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
43
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D180 (cont)
LEGEND
566D180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 196.0 200.0 215.0 234.0 212.0 212.0 224.0 242.0 223.0 224.0 230.0 247.0
SHC 196.0 188.0 156.0 123.0 212.0 212.0 181.0 138.0 223.0 224.0 203.0 152.0
kW13.90 14.00 14.50 15.00 14.40 14.40 14.70 15.20 14.70 14.70 14.90 15.30
85
TC 193.0 196.0 211.0 229.0 209.0 209.0 220.0 237.0 219.0 220.0 225.0 242.0
SHC 193.0 186.0 154.0 121.0 209.0 209.0 179.0 136.0 219.0 220.0 201.0 151.0
kW14.60 14.70 15.20 15.70 15.10 15.10 15.40 16.00 15.40 15.40 15.60 16.10
95
TC 186.0 188.0 203.0 219.0 201.0 201.0 210.0 227.0 211.0 211.0 216.0 231.0
SHC 186.0 182.0 151.0 118.0 201.0 201.0 175.0 133.0 211.0 211.0 197.0 147.0
kW15.90 16.00 16.50 17.10 16.50 16.50 16.80 17.40 16.80 16.80 17.00 17.60
100
TC 183.0 184.0 198.0 215.0 197.0 197.0 205.0 222.0 207.0 207.0 211.0 226.0
SHC 183.0 179.0 149.0 116.0 197.0 197.0 173.0 131.0 207.0 207.0 195.0 146.0
kW16.50 16.60 17.20 17.90 17.20 17.10 17.50 18.10 17.60 17.50 17.70 18.30
105
TC 179.0 180.0 193.0 210.0 193.0 193.0 201.0 216.0 203.0 203.0 206.0 221.0
SHC 179.0 177.0 147.0 114.0 193.0 193.0 171.0 129.0 203.0 203.0 192.0 144.0
kW17.20 17.20 17.80 18.60 17.80 17.80 18.20 18.90 18.30 18.30 18.40 19.00
115
TC 172.0 172.0 184.0 200.0 185.0 185.0 191.0 206.0 194.0 194.0 196.0 210.0
SHC 172.0 172.0 144.0 111.0 185.0 185.0 168.0 126.0 194.0 194.0 188.0 140.0
kW18.50 18.50 19.10 20.00 19.20 19.20 19.50 20.30 19.70 19.70 19.80 20.50
566D180/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 186.0 190.0 205.0 222.0 201.0 201.0 212.0 230.0 211.0 211.0 218.0 235.0
SHC 186.0 178.0 148.0 117.0 201.0 201.0 171.0 130.0 211.0 211.0 190.0 143.0
kW13.70 13.80 14.20 14.70 14.10 14.10 14.50 15.00 14.40 14.40 14.60 15.10
85
TC 183.0 186.0 200.0 217.0 197.0 197.0 208.0 225.0 207.0 207.0 213.0 230.0
SHC 183.0 176.0 147.0 115.0 197.0 197.0 169.0 129.0 207.0 207.0 188.0 142.0
kW14.30 14.40 14.90 15.40 14.80 14.80 15.10 15.70 15.10 15.10 15.30 15.80
95
TC 176.0 179.0 192.0 208.0 190.0 190.0 199.0 215.0 199.0 199.0 204.0 220.0
SHC 176.0 172.0 143.0 112.0 190.0 190.0 165.0 125.0 199.0 199.0 184.0 138.0
kW15.50 15.60 16.20 16.80 16.10 16.10 16.50 17.10 16.50 16.50 16.70 17.30
100
TC 173.0 175.0 188.0 204.0 186.0 186.0 195.0 211.0 195.0 195.0 200.0 215.0
SHC 173.0 170.0 142.0 110.0 186.0 186.0 163.0 124.0 195.0 195.0 182.0 137.0
kW16.20 16.20 16.80 17.50 16.80 16.70 17.10 17.80 17.10 17.10 17.30 18.00
105
TC 170.0 171.0 184.0 199.0 183.0 183.0 190.0 206.0 191.0 191.0 195.0 210.0
SHC 170.0 167.0 140.0 108.0 183.0 183.0 162.0 122.0 191.0 191.0 180.0 135.0
kW16.80 16.90 17.50 18.20 17.40 17.40 17.80 18.50 17.80 17.80 18.00 18.70
115
TC 163.0 164.0 175.0 190.0 175.0 175.0 181.0 196.0 183.0 183.0 186.0 199.0
SHC 163.0 163.0 136.0 105.0 175.0 175.0 158.0 119.0 183.0 183.0 175.0 132.0
kW18.10 18.10 18.70 19.50 18.70 18.70 19.10 19.80 19.20 19.10 19.30 20.00
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
44
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566D240
LEGEND
566D240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500 10,000 12,500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 244.0 249.0 268.0 291.0 264.0 264.0 279.0 301.0 278.0 278.0 286.0 307.0
SHC 244.0 233.0 194.0 152.0 264.0 264.0 224.0 171.0 278.0 278.0 252.0 189.0
kW18.90 19.20 19.90 20.80 19.70 19.70 20.30 21.20 20.30 20.30 20.60 21.40
85
TC 239.0 244.0 263.0 284.0 259.0 259.0 273.0 294.0 272.0 272.0 280.0 300.0
SHC 239.0 231.0 192.0 150.0 259.0 259.0 222.0 169.0 272.0 272.0 249.0 187.0
kW19.70 19.90 20.70 21.60 20.50 20.50 21.10 22.00 21.10 21.10 21.40 22.30
95
TC 230.0 233.0 251.0 272.0 249.0 249.0 260.0 281.0 261.0 261.0 267.0 286.0
SHC 230.0 225.0 187.0 146.0 249.0 249.0 217.0 164.0 261.0 261.0 243.0 182.0
kW21.30 21.40 22.20 23.20 22.10 22.10 22.70 23.70 22.70 22.70 23.00 23.90
100
TC 226.0 228.0 245.0 265.0 244.0 244.0 254.0 274.0 256.0 256.0 260.0 279.0
SHC 226.0 222.0 184.0 143.0 244.0 244.0 214.0 162.0 256.0 256.0 240.0 180.0
kW22.00 22.10 23.00 24.00 22.90 22.90 23.50 24.50 23.60 23.60 23.80 24.80
105
TC 221.0 222.0 239.0 259.0 238.0 238.0 247.0 267.0 250.0 250.0 254.0 272.0
SHC 221.0 219.0 182.0 141.0 238.0 238.0 212.0 160.0 250.0 250.0 237.0 177.0
kW22.80 22.80 23.70 24.80 23.70 23.70 24.20 25.30 24.40 24.40 24.60 25.60
115
TC 212.0 212.0 226.0 245.0 227.0 227.0 235.0 253.0 238.0 238.0 240.0 257.0
SHC 212.0 211.0 177.0 136.0 227.0 227.0 206.0 155.0 238.0 238.0 231.0 172.0
kW24.30 24.30 25.20 26.40 25.30 25.30 25.80 26.90 26.00 26.00 26.10 27.20
566D240/524A-B300 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500 10,000 12,500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 230.0 236.0 255.0 277.0 249.0 249.0 266.0 287.0 262.0 262.0 272.0 293.0
SHC 230.0 219.0 183.0 144.0 249.0 248.0 209.0 161.0 262.0 262.0 233.0 176.0
kW18.40 18.60 19.40 20.20 19.10 19.20 19.80 20.60 19.60 19.60 20.10 20.90
85
TC 226.0 231.0 250.0 271.0 244.0 244.0 259.0 281.0 256.0 256.0 266.0 287.0
SHC 226.0 217.0 181.0 142.0 244.0 244.0 207.0 159.0 256.0 256.0 231.0 174.0
kW19.20 19.40 20.20 21.00 19.90 19.90 20.60 21.50 20.40 20.40 20.80 21.70
95
TC 218.0 221.0 239.0 259.0 235.0 235.0 248.0 268.0 246.0 246.0 254.0 273.0
SHC 218.0 211.0 176.0 138.0 235.0 235.0 203.0 154.0 246.0 246.0 226.0 169.0
kW20.60 20.80 21.70 22.60 21.50 21.50 22.10 23.10 22.00 22.00 22.40 23.30
100
TC 214.0 217.0 233.0 253.0 230.0 230.0 242.0 261.0 241.0 241.0 248.0 266.0
SHC 214.0 208.0 174.0 136.0 230.0 230.0 200.0 152.0 241.0 241.0 223.0 167.0
kW21.40 21.50 22.40 23.40 22.20 22.20 22.90 23.80 22.80 22.80 23.20 24.10
105
TC 209.0 212.0 228.0 247.0 225.0 225.0 236.0 255.0 236.0 236.0 242.0 260.0
SHC 209.0 206.0 172.0 133.0 225.0 225.0 198.0 150.0 236.0 236.0 220.0 165.0
kW22.10 22.20 23.10 24.20 23.00 23.00 23.60 24.60 23.60 23.60 23.90 24.90
115
TC 201.0 202.0 216.0 235.0 215.0 215.0 224.0 242.0 226.0 226.0 229.0 246.0
SHC 201.0 199.0 167.0 129.0 215.0 215.0 193.0 145.0 226.0 226.0 214.0 160.0
kW23.60 23.70 24.60 25.80 24.60 24.50 25.10 26.20 25.20 25.20 25.40 26.50
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
45
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150
LEGEND
566E150/524A-C120 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 126.0 135.0 148.0 161.0 140.0 144.0 156.0 170.0 149.0 151.0 162.0 176.0
SHC 126.0 112.0 95.4 78.5 140.0 130.0 109.0 87.0 149.0 146.0 122.0 94.8
kW9.13 9.18 9.22 9.31 9.19 9.20 9.26 9.37 9.22 9.23 9.30 9.43
85
TC 125.0 133.0 146.0 159.0 138.0 142.0 154.0 168.0 147.0 148.0 159.0 173.0
SHC 125.0 111.0 94.5 77.5 138.0 129.0 108.0 86.0 147.0 144.0 121.0 93.8
kW9.68 9.72 9.79 9.87 9.74 9.77 9.82 9.92 9.78 9.80 9.85 9.98
95
TC 121.0 129.0 141.0 154.0 134.0 137.0 149.0 162.0 143.0 144.0 154.0 167.0
SHC 121.0 109.0 92.4 75.6 134.0 127.0 106.0 84.0 143.0 141.0 118.0 91.8
kW10.90 11.00 11.00 11.10 11.00 11.00 11.00 11.10 11.00 11.00 11.10 11.20
100
TC 119.0 127.0 138.0 151.0 132.0 135.0 146.0 159.0 141.0 141.0 151.0 164.0
SHC 119.0 108.0 91.4 74.6 132.0 126.0 105.0 82.9 141.0 140.0 117.0 90.7
kW11.60 11.60 11.70 11.70 11.60 11.60 11.70 11.80 11.60 11.70 11.70 11.80
105
TC 118.0 124.0 136.0 149.0 130.0 132.0 143.0 156.0 138.0 139.0 148.0 161.0
SHC 118.0 107.0 90.3 73.5 130.0 124.0 104.0 81.9 138.0 138.0 116.0 89.6
kW12.30 12.30 12.40 12.40 12.30 12.30 12.40 12.50 12.30 12.40 12.40 12.50
115
TC 114.0 120.0 131.0 143.0 126.0 127.0 137.0 150.0 134.0 134.0 142.0 154.0
SHC 114.0 104.0 88.0 71.4 126.0 122.0 101.0 79.6 134.0 134.0 114.0 87.4
kW13.70 13.80 13.80 13.90 13.80 13.80 13.80 13.90 13.80 13.80 13.90 14.00
566E150/524A-B120 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 119.0 128.0 140.0 153.0 131.0 136.0 148.0 161.0 140.0 142.0 153.0 166.0
SHC 119.0 106.0 90.4 74.3 131.0 122.0 103.0 82.0 140.0 136.0 114.0 89.0
kW9.09 9.15 9.18 9.23 9.15 9.16 9.21 9.30 9.19 9.19 9.25 9.33
85
TC 118.0 126.0 138.0 151.0 130.0 134.0 146.0 159.0 138.0 140.0 151.0 164.0
SHC 118.0 105.0 89.5 73.4 130.0 121.0 102.0 81.2 138.0 135.0 113.0 88.1
kW9.66 9.72 9.75 9.81 9.72 9.72 9.77 9.87 9.75 9.75 9.80 9.89
95
TC 115.0 122.0 134.0 146.0 126.0 130.0 141.0 154.0 134.0 136.0 146.0 158.0
SHC 115.0 103.0 87.7 71.7 126.0 119.0 99.9 79.3 134.0 132.0 111.0 86.3
kW10.90 10.90 11.00 11.00 10.90 10.90 11.00 11.10 11.00 11.00 11.00 11.10
100
TC 113.0 120.0 131.0 144.0 124.0 128.0 139.0 151.0 132.0 133.0 143.0 156.0
SHC 113.0 102.0 86.7 70.8 124.0 118.0 98.9 78.4 132.0 131.0 110.0 85.3
kW11.60 11.60 11.60 11.70 11.60 11.60 11.60 11.70 11.60 11.60 11.70 11.80
105
TC 111.0 118.0 129.0 141.0 122.0 125.0 136.0 148.0 130.0 131.0 140.0 153.0
SHC 111.0 101.0 85.7 69.8 122.0 117.0 97.9 77.5 130.0 129.0 109.0 84.3
kW12.20 12.30 12.30 12.40 12.30 12.30 12.30 12.40 12.30 12.30 12.40 12.40
115
TC 108.0 114.0 124.0 136.0 118.0 121.0 131.0 143.0 126.0 126.0 135.0 147.0
SHC 108.0 99.0 83.7 67.8 118.0 114.0 95.8 75.4 126.0 126.0 107.0 82.3
kW13.70 13.70 13.80 13.90 13.70 13.80 13.80 13.90 13.80 13.80 13.80 13.90
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
46
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
LEGEND
566E150/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 139.0 145.0 158.0 172.0 152.0 154.0 165.0 180.0 161.0 161.0 170.0 185.0
SHC 139.0 127.0 107.0 86.2 152.0 148.0 123.0 96.1 161.0 161.0 138.0 105.0
kW9.18 9.21 9.27 9.38 9.25 9.24 9.33 9.48 9.29 9.31 9.37 9.54
85
TC 137.0 143.0 155.0 169.0 150.0 151.0 163.0 177.0 159.0 159.0 168.0 182.0
SHC 137.0 126.0 106.0 85.3 150.0 146.0 122.0 95.1 159.0 159.0 137.0 104.0
kW9.74 9.76 9.84 9.95 9.80 9.82 9.90 10.00 9.86 9.87 9.93 10.10
95
TC 133.0 138.0 150.0 164.0 146.0 147.0 157.0 171.0 154.0 154.0 162.0 175.0
SHC 133.0 124.0 104.0 83.3 146.0 144.0 120.0 93.1 154.0 154.0 134.0 102.0
kW11.00 11.00 11.10 11.20 11.00 11.00 11.10 11.20 11.10 11.10 11.10 11.30
100
TC 131.0 136.0 148.0 161.0 143.0 144.0 154.0 168.0 152.0 152.0 159.0 172.0
SHC 131.0 123.0 103.0 82.2 143.0 142.0 119.0 92.1 152.0 152.0 133.0 101.0
kW11.60 11.60 11.70 11.80 11.70 11.70 11.80 11.90 11.70 11.70 11.80 11.90
105
TC 129.0 133.0 145.0 158.0 141.0 142.0 152.0 165.0 149.0 149.0 156.0 169.0
SHC 129.0 121.0 102.0 81.1 141.0 140.0 118.0 90.9 149.0 149.0 132.0 100.0
kW12.30 12.30 12.40 12.50 12.40 12.40 12.50 12.60 12.40 12.40 12.50 12.60
115
TC 125.0 128.0 139.0 152.0 136.0 136.0 145.0 158.0 144.0 144.0 150.0 162.0
SHC 125.0 119.0 99.4 78.9 136.0 136.0 115.0 88.7 144.0 144.0 129.0 97.9
kW13.80 13.80 13.90 14.00 13.80 13.90 13.90 14.00 13.90 13.90 13.90 14.10
566E150/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 130.0 137.0 150.0 163.0 143.0 145.0 157.0 171.0 151.0 151.0 162.0 176.0
SHC 130.0 120.0 101.0 81.6 143.0 138.0 115.0 90.5 151.0 151.0 128.0 98.5
kW9.14 9.18 9.22 9.32 9.20 9.20 9.27 9.38 9.24 9.23 9.30 9.43
85
TC 129.0 135.0 147.0 161.0 141.0 143.0 154.0 168.0 149.0 149.0 159.0 173.0
SHC 129.0 119.0 100.0 80.7 141.0 137.0 114.0 89.5 149.0 149.0 127.0 97.5
kW9.70 9.73 9.78 9.88 9.76 9.76 9.82 9.93 9.79 9.79 9.85 9.98
95
TC 125.0 131.0 143.0 156.0 137.0 138.0 149.0 162.0 145.0 145.0 154.0 167.0
SHC 125.0 117.0 98.0 78.7 137.0 134.0 112.0 87.5 145.0 145.0 125.0 95.6
kW10.90 11.00 11.00 11.10 11.00 11.00 11.00 11.10 11.00 11.00 11.10 11.20
100
TC 123.0 128.0 140.0 153.0 135.0 136.0 146.0 160.0 143.0 143.0 151.0 164.0
SHC 123.0 115.0 97.0 77.7 135.0 132.0 111.0 86.5 143.0 143.0 124.0 94.5
kW11.60 11.60 11.70 11.70 11.60 11.70 11.70 11.80 11.70 11.70 11.70 11.80
105
TC 122.0 126.0 137.0 150.0 132.0 133.0 144.0 157.0 140.0 140.0 148.0 161.0
SHC 122.0 114.0 95.9 76.7 132.0 131.0 110.0 85.4 140.0 140.0 123.0 93.5
kW12.30 12.30 12.30 12.40 12.30 12.30 12.40 12.50 12.30 12.40 12.40 12.50
115
TC 118.0 121.0 132.0 144.0 128.0 128.0 138.0 150.0 135.0 135.0 142.0 154.0
SHC 118.0 112.0 93.6 74.5 128.0 128.0 108.0 83.3 135.0 135.0 120.0 91.3
kW13.80 13.80 13.80 13.90 13.80 13.80 13.90 14.00 13.80 13.80 13.90 14.00
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
47
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E150 (cont)
LEGEND
566E150/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 152.0 156.0 169.0 183.0 166.0 166.0 176.0 190.0 175.0 175.0 181.0 195.0
SHC 152.0 145.0 121.0 95.4 166.0 166.0 140.0 107.0 175.0 175.0 157.0 119.0
kW9.24 9.26 9.35 9.53 9.33 9.33 9.43 9.63 9.42 9.43 9.49 9.69
85
TC 150.0 154.0 166.0 181.0 164.0 164.0 173.0 187.0 173.0 173.0 178.0 191.0
SHC 150.0 144.0 120.0 94.4 164.0 164.0 139.0 106.0 173.0 173.0 156.0 118.0
kW9.80 9.82 9.92 10.10 9.89 9.89 9.99 10.20 9.98 9.99 10.00 10.20
95
TC 146.0 148.0 161.0 175.0 159.0 159.0 167.0 181.0 167.0 167.0 172.0 185.0
SHC 146.0 141.0 117.0 92.2 159.0 159.0 136.0 104.0 167.0 167.0 154.0 115.0
kW11.00 11.10 11.10 11.30 11.10 11.10 11.20 11.40 11.20 11.20 11.20 11.40
100
TC 144.0 146.0 158.0 171.0 156.0 156.0 164.0 178.0 165.0 165.0 169.0 181.0
SHC 144.0 140.0 116.0 91.1 156.0 156.0 135.0 103.0 165.0 165.0 152.0 114.0
kW11.70 11.70 11.80 11.90 11.80 11.80 11.90 12.00 11.80 11.90 11.90 12.10
105
TC 141.0 143.0 155.0 168.0 154.0 154.0 161.0 174.0 162.0 162.0 165.0 178.0
SHC 141.0 138.0 115.0 90.0 154.0 154.0 134.0 102.0 162.0 162.0 151.0 113.0
kW12.40 12.40 12.50 12.60 12.50 12.50 12.50 12.70 12.50 12.50 12.60 12.80
115
TC 137.0 138.0 148.0 162.0 148.0 148.0 154.0 167.0 156.0 156.0 159.0 170.0
SHC 137.0 135.0 112.0 87.6 148.0 148.0 131.0 99.5 156.0 156.0 148.0 111.0
kW13.90 13.90 13.90 14.10 13.90 14.00 14.00 14.20 14.00 14.00 14.00 14.20
566E150/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 143.0 147.0 160.0 174.0 155.0 156.0 166.0 180.0 164.0 164.0 171.0 185.0
SHC 143.0 136.0 113.0 89.9 155.0 155.0 130.0 100.0 164.0 164.0 146.0 110.0
kW9.19 9.22 9.28 9.42 9.27 9.26 9.34 9.49 9.31 9.33 9.37 9.54
85
TC 141.0 145.0 157.0 171.0 153.0 153.0 164.0 178.0 162.0 162.0 168.0 182.0
SHC 141.0 134.0 112.0 89.0 153.0 153.0 129.0 99.5 162.0 162.0 144.0 109.0
kW9.75 9.77 9.85 9.98 9.82 9.82 9.90 10.00 9.87 9.89 9.93 10.10
95
TC 137.0 140.0 152.0 165.0 149.0 149.0 158.0 172.0 157.0 157.0 162.0 175.0
SHC 137.0 132.0 110.0 86.9 149.0 149.0 127.0 97.4 157.0 157.0 142.0 107.0
kW11.00 11.00 11.10 11.20 11.00 11.00 11.10 11.20 11.10 11.10 11.10 11.30
100
TC 135.0 138.0 149.0 162.0 146.0 146.0 155.0 168.0 154.0 154.0 159.0 172.0
SHC 135.0 131.0 109.0 85.8 146.0 146.0 126.0 96.3 154.0 154.0 141.0 106.0
kW11.60 11.60 11.70 11.80 11.70 11.70 11.80 11.90 11.70 11.80 11.80 11.90
105
TC 133.0 135.0 146.0 159.0 144.0 144.0 152.0 165.0 152.0 152.0 156.0 169.0
SHC 133.0 129.0 108.0 84.7 144.0 144.0 125.0 95.2 152.0 152.0 139.0 105.0
kW12.30 12.30 12.40 12.50 12.40 12.40 12.50 12.60 12.40 12.50 12.50 12.60
115
TC 129.0 130.0 140.0 153.0 139.0 139.0 146.0 158.0 146.0 146.0 150.0 162.0
SHC 129.0 126.0 106.0 82.5 139.0 139.0 122.0 92.9 146.0 146.0 137.0 103.0
kW13.80 13.80 13.90 14.00 13.90 13.90 13.90 14.10 13.90 13.90 13.90 14.10
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
48
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180
LEGEND
566E180/524A-C150 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 163.0 175.0 190.0 206.0 179.0 186.0 201.0 217.0 191.0 194.0 208.0 224.0
SHC 161.0 142.0 121.0 99.8 179.0 164.0 138.0 110.0 191.0 184.0 153.0 119.0
kW12.60 12.80 13.20 13.60 12.90 13.10 13.40 13.80 13.20 13.30 13.60 14.00
85
TC 160.0 172.0 187.0 203.0 176.0 183.0 198.0 214.0 188.0 190.0 204.0 220.0
SHC 159.0 141.0 120.0 98.5 176.0 163.0 136.0 109.0 188.0 182.0 151.0 118.0
kW13.10 13.40 13.80 14.20 13.50 13.70 14.00 14.40 13.80 13.80 14.20 14.60
95
TC 155.0 166.0 180.0 196.0 170.0 176.0 190.0 206.0 181.0 183.0 196.0 212.0
SHC 155.0 138.0 117.0 95.6 170.0 159.0 133.0 106.0 181.0 178.0 148.0 115.0
kW14.30 14.60 15.00 15.40 14.70 14.80 15.20 15.70 15.00 15.00 15.40 15.80
100
TC 152.0 163.0 177.0 192.0 167.0 172.0 186.0 201.0 178.0 180.0 192.0 208.0
SHC 152.0 136.0 115.0 94.0 167.0 158.0 131.0 104.0 178.0 176.0 146.0 113.0
kW14.90 15.20 15.60 16.00 15.30 15.50 15.80 16.30 15.60 15.60 16.00 16.50
105
TC 150.0 159.0 173.0 188.0 164.0 168.0 182.0 197.0 175.0 176.0 188.0 203.0
SHC 150.0 134.0 114.0 92.4 164.0 156.0 130.0 102.0 175.0 173.0 145.0 112.0
kW15.60 15.80 16.20 16.60 16.00 16.10 16.50 16.90 16.30 16.30 16.60 17.10
115
TC 144.0 152.0 165.0 179.0 158.0 161.0 173.0 188.0 168.0 168.0 178.0 193.0
SHC 144.0 131.0 110.0 89.1 158.0 152.0 126.0 99.0 168.0 167.0 141.0 108.0
kW16.90 17.10 17.50 18.00 17.30 17.40 17.80 18.20 17.60 17.60 17.90 18.40
566E180/524A-B150 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 154.0 166.0 181.0 196.0 168.0 176.0 191.0 206.0 179.0 183.0 197.0 213.0
SHC 152.0 134.0 115.0 94.7 168.0 154.0 129.0 104.0 179.0 171.0 143.0 112.0
kW12.40 12.60 13.00 13.30 12.70 12.90 13.20 13.60 12.90 13.00 13.40 13.70
85
TC 152.0 163.0 178.0 193.0 166.0 173.0 188.0 203.0 176.0 180.0 194.0 210.0
SHC 150.0 133.0 113.0 93.4 166.0 153.0 128.0 102.0 176.0 169.0 141.0 111.0
kW12.90 13.20 13.50 13.90 13.20 13.40 13.80 14.20 13.50 13.60 13.90 14.30
95
TC 147.0 157.0 171.0 186.0 160.0 167.0 180.0 196.0 171.0 173.0 187.0 202.0
SHC 146.0 130.0 111.0 90.6 160.0 149.0 125.0 99.7 171.0 166.0 138.0 108.0
kW14.10 14.40 14.70 15.10 14.40 14.60 15.00 15.40 14.70 14.80 15.10 15.50
100
TC 144.0 154.0 168.0 182.0 158.0 163.0 177.0 191.0 167.0 170.0 182.0 197.0
SHC 144.0 128.0 109.0 89.1 158.0 148.0 123.0 98.1 167.0 163.0 137.0 106.0
kW14.80 15.00 15.30 15.70 15.10 15.20 15.60 16.00 15.30 15.40 15.70 16.20
105
TC 141.0 151.0 164.0 179.0 155.0 160.0 173.0 187.0 164.0 166.0 178.0 193.0
SHC 141.0 127.0 107.0 87.6 155.0 146.0 122.0 96.5 164.0 161.0 135.0 105.0
kW15.40 15.60 16.00 16.40 15.70 15.80 16.20 16.60 16.00 16.00 16.40 16.80
115
TC 136.0 144.0 157.0 170.0 149.0 152.0 165.0 178.0 158.0 159.0 170.0 183.0
SHC 136.0 124.0 104.0 84.4 149.0 142.0 118.0 93.3 158.0 156.0 132.0 101.0
kW16.80 16.90 17.30 17.70 17.10 17.20 17.50 17.90 17.30 17.30 17.70 18.10
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
49
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
LEGEND
566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 180.0 190.0 206.0 223.0 197.0 201.0 216.0 233.0 209.0 210.0 222.0 239.0
SHC 180.0 162.0 136.0 110.0 197.0 188.0 156.0 122.0 209.0 208.0 174.0 134.0
kW12.90 13.20 13.60 14.00 13.30 13.40 13.80 14.20 13.60 13.70 14.00 14.40
85
TC 177.0 187.0 203.0 220.0 194.0 198.0 212.0 229.0 206.0 206.0 219.0 235.0
SHC 177.0 160.0 135.0 109.0 194.0 186.0 154.0 121.0 206.0 206.0 173.0 132.0
kW13.50 13.80 14.20 14.60 13.90 14.00 14.40 14.80 14.20 14.20 14.60 15.00
95
TC 172.0 180.0 195.0 212.0 188.0 190.0 204.0 221.0 199.0 199.0 210.0 226.0
SHC 172.0 157.0 132.0 106.0 188.0 182.0 151.0 118.0 199.0 199.0 169.0 129.0
kW14.70 14.90 15.40 15.80 15.20 15.20 15.60 16.10 15.50 15.50 15.80 16.20
100
TC 169.0 176.0 191.0 207.0 184.0 186.0 200.0 216.0 195.0 195.0 205.0 221.0
SHC 169.0 155.0 130.0 104.0 184.0 180.0 149.0 116.0 195.0 195.0 168.0 128.0
kW15.40 15.60 16.00 16.40 15.80 15.80 16.20 16.70 16.10 16.10 16.40 16.90
105
TC 166.0 172.0 187.0 203.0 181.0 182.0 195.0 211.0 191.0 191.0 201.0 216.0
SHC 166.0 153.0 128.0 102.0 181.0 178.0 147.0 115.0 191.0 191.0 166.0 126.0
kW16.00 16.20 16.60 17.10 16.40 16.50 16.90 17.40 16.70 16.80 17.00 17.50
115
TC 159.0 164.0 178.0 193.0 173.0 174.0 185.0 201.0 183.0 183.0 191.0 205.0
SHC 159.0 149.0 124.0 98.8 173.0 172.0 144.0 111.0 183.0 183.0 162.0 122.0
kW17.30 17.50 17.90 18.40 17.80 17.80 18.10 18.60 18.10 18.10 18.30 18.80
566E180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 169.0 180.0 195.0 211.0 185.0 190.0 204.0 221.0 196.0 197.0 211.0 227.0
SHC 169.0 152.0 128.0 104.0 185.0 175.0 146.0 115.0 196.0 193.0 162.0 125.0
kW12.70 12.90 13.30 13.70 13.10 13.20 13.50 13.90 13.30 13.30 13.70 14.10
85
TC 167.0 177.0 192.0 208.0 182.0 186.0 201.0 217.0 193.0 194.0 207.0 223.0
SHC 167.0 151.0 127.0 103.0 182.0 173.0 144.0 113.0 193.0 191.0 160.0 123.0
kW13.30 13.50 13.90 14.30 13.60 13.70 14.10 14.50 13.90 13.90 14.30 14.70
95
TC 161.0 170.0 184.0 200.0 176.0 179.0 193.0 209.0 186.0 187.0 199.0 215.0
SHC 161.0 147.0 124.0 99.8 176.0 169.0 141.0 111.0 186.0 186.0 157.0 120.0
kW14.50 14.70 15.10 15.50 14.80 14.90 15.30 15.70 15.10 15.10 15.50 15.90
100
TC 159.0 166.0 181.0 196.0 173.0 176.0 189.0 204.0 183.0 183.0 194.0 210.0
SHC 159.0 145.0 122.0 98.2 173.0 167.0 139.0 109.0 183.0 183.0 155.0 119.0
kW15.10 15.30 15.70 16.10 15.50 15.50 15.90 16.40 15.70 15.70 16.10 16.50
105
TC 156.0 163.0 177.0 192.0 169.0 172.0 185.0 200.0 179.0 179.0 190.0 205.0
SHC 156.0 144.0 120.0 96.6 169.0 165.0 138.0 107.0 179.0 179.0 153.0 117.0
kW15.70 15.90 16.30 16.80 16.10 16.20 16.50 17.00 16.40 16.40 16.70 17.20
115
TC 150.0 155.0 168.0 183.0 163.0 164.0 175.0 190.0 172.0 172.0 180.0 195.0
SHC 150.0 140.0 117.0 93.2 163.0 160.0 134.0 104.0 172.0 172.0 150.0 114.0
kW17.10 17.20 17.60 18.10 17.50 17.50 17.80 18.30 17.70 17.70 18.00 18.50
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
50
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
LEGEND
566E180/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 201.0 205.0 220.0 238.0 217.0 217.0 229.0 246.0 228.0 228.0 234.0 251.0
SHC 201.0 191.0 159.0 125.0 217.0 217.0 184.0 140.0 228.0 228.0 207.0 155.0
kW13.40 13.50 13.90 14.40 13.80 13.80 14.10 14.60 14.10 14.10 14.30 14.70
85
TC 198.0 202.0 216.0 234.0 214.0 214.0 225.0 242.0 225.0 225.0 230.0 247.0
SHC 198.0 190.0 157.0 123.0 214.0 214.0 182.0 139.0 225.0 225.0 205.0 154.0
kW14.00 14.10 14.50 15.00 14.40 14.40 14.70 15.20 14.70 14.70 14.90 15.30
95
TC 191.0 194.0 208.0 225.0 207.0 207.0 216.0 232.0 217.0 217.0 221.0 237.0
SHC 191.0 186.0 154.0 120.0 207.0 207.0 179.0 136.0 217.0 217.0 201.0 150.0
kW15.30 15.30 15.70 16.20 15.70 15.70 15.90 16.40 16.00 16.00 16.10 16.60
100
TC 188.0 190.0 204.0 220.0 202.0 203.0 211.0 227.0 213.0 213.0 216.0 232.0
SHC 188.0 183.0 152.0 118.0 202.0 203.0 177.0 134.0 213.0 213.0 199.0 149.0
kW15.90 15.90 16.30 16.80 16.30 16.30 16.60 17.10 16.60 16.60 16.70 17.20
105
TC 184.0 185.0 199.0 215.0 198.0 198.0 206.0 222.0 208.0 208.0 211.0 226.0
SHC 184.0 181.0 150.0 117.0 198.0 198.0 175.0 132.0 208.0 208.0 197.0 147.0
kW16.50 16.60 17.00 17.50 17.00 17.00 17.20 17.70 17.30 17.30 17.40 17.80
115
TC 176.0 177.0 189.0 205.0 190.0 190.0 196.0 211.0 199.0 199.0 201.0 214.0
SHC 176.0 176.0 146.0 113.0 190.0 190.0 171.0 128.0 199.0 199.0 192.0 143.0
kW17.90 17.90 18.30 18.80 18.30 18.30 18.50 19.00 18.60 18.60 18.70 19.10
566E180/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 190.0 194.0 209.0 226.0 205.0 205.0 217.0 233.0 215.0 215.0 222.0 238.0
SHC 190.0 181.0 150.0 118.0 205.0 204.0 173.0 132.0 215.0 215.0 193.0 145.0
kW13.20 13.30 13.60 14.00 13.50 13.50 13.80 14.20 13.80 13.80 14.00 14.40
85
TC 187.0 191.0 205.0 222.0 202.0 202.0 213.0 229.0 211.0 211.0 218.0 234.0
SHC 187.0 179.0 149.0 117.0 202.0 201.0 171.0 131.0 211.0 211.0 191.0 144.0
kW13.80 13.90 14.20 14.60 14.10 14.10 14.40 14.80 14.40 14.40 14.50 15.00
95
TC 181.0 184.0 197.0 213.0 195.0 195.0 204.0 220.0 204.0 204.0 209.0 225.0
SHC 181.0 175.0 146.0 114.0 195.0 195.0 168.0 128.0 204.0 204.0 187.0 141.0
kW15.00 15.00 15.40 15.90 15.30 15.30 15.60 16.10 15.60 15.60 15.80 16.20
100
TC 178.0 180.0 193.0 209.0 191.0 191.0 200.0 216.0 200.0 200.0 205.0 220.0
SHC 178.0 173.0 144.0 112.0 191.0 191.0 166.0 126.0 200.0 200.0 185.0 139.0
kW15.60 15.70 16.00 16.50 16.00 16.00 16.20 16.70 16.20 16.20 16.40 16.80
105
TC 174.0 176.0 188.0 204.0 187.0 187.0 195.0 210.0 196.0 196.0 200.0 215.0
SHC 174.0 171.0 142.0 110.0 187.0 187.0 164.0 124.0 196.0 196.0 183.0 137.0
kW16.20 16.30 16.60 17.10 16.60 16.60 16.90 17.30 16.90 16.90 17.00 17.50
115
TC 167.0 168.0 179.0 194.0 179.0 179.0 185.0 200.0 187.0 187.0 190.0 203.0
SHC 167.0 166.0 138.0 107.0 179.0 179.0 160.0 121.0 187.0 187.0 178.0 133.0
kW17.60 17.60 18.00 18.40 17.90 17.90 18.10 18.60 18.20 18.20 18.30 18.70
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
51
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240
LEGEND
566E240/524A-C240 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 228.0 239.0 258.0 279.0 248.0 252.0 269.0 290.0 262.0 262.0 277.0 297.0
SHC 228.0 207.0 174.0 139.0 248.0 240.0 199.0 155.0 262.0 262.0 222.0 169.0
kW17.60 18.00 18.70 19.40 18.30 18.40 19.10 19.80 18.80 18.80 19.30 20.10
85
TC 225.0 235.0 254.0 274.0 245.0 248.0 265.0 285.0 258.0 258.0 272.0 291.0
SHC 225.0 205.0 172.0 137.0 245.0 237.0 197.0 153.0 258.0 258.0 220.0 167.0
kW18.40 18.70 19.40 20.10 19.10 19.20 19.80 20.60 19.60 19.60 20.10 20.80
95
TC 218.0 227.0 244.0 263.0 236.0 238.0 254.0 274.0 249.0 249.0 261.0 280.0
SHC 218.0 201.0 168.0 134.0 236.0 232.0 193.0 149.0 249.0 249.0 216.0 163.0
kW20.00 20.30 21.00 21.70 20.70 20.70 21.30 22.10 21.10 21.10 21.60 22.40
100
TC 214.0 222.0 239.0 258.0 232.0 234.0 249.0 268.0 245.0 245.0 255.0 274.0
SHC 214.0 199.0 166.0 132.0 232.0 229.0 190.0 147.0 245.0 245.0 213.0 161.0
kW20.90 21.10 21.70 22.50 21.50 21.50 22.10 22.90 22.00 22.00 22.40 23.10
105
TC 211.0 217.0 234.0 252.0 228.0 229.0 243.0 262.0 240.0 240.0 249.0 267.0
SHC 211.0 196.0 163.0 130.0 228.0 226.0 188.0 145.0 240.0 240.0 211.0 159.0
kW21.70 22.00 22.60 23.30 22.40 22.40 22.90 23.70 22.80 22.80 23.20 23.90
115
TC 203.0 207.0 223.0 241.0 219.0 219.0 231.0 249.0 230.0 230.0 237.0 254.0
SHC 203.0 192.0 159.0 125.0 219.0 219.0 184.0 140.0 230.0 230.0 206.0 155.0
kW23.50 23.70 24.30 25.00 24.10 24.10 24.60 25.40 24.60 24.60 24.90 25.60
566E240/524A-B240 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 8,000 10,000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 219.0 229.0 248.0 267.0 237.0 241.0 259.0 278.0 250.0 251.0 265.0 285.0
SHC 219.0 199.0 167.0 134.0 237.0 228.0 190.0 148.0 250.0 250.0 211.0 161.0
kW17.30 17.70 18.30 19.00 17.90 18.10 18.70 19.40 18.40 18.40 18.90 19.60
85
TC 216.0 226.0 243.0 263.0 234.0 237.0 254.0 273.0 246.0 247.0 261.0 280.0
SHC 216.0 197.0 165.0 132.0 234.0 226.0 188.0 146.0 246.0 246.0 209.0 159.0
kW18.10 18.40 19.00 19.70 18.70 18.80 19.40 20.10 19.10 19.10 19.70 20.40
95
TC 209.0 217.0 234.0 253.0 226.0 228.0 244.0 263.0 238.0 238.0 250.0 269.0
SHC 209.0 192.0 161.0 128.0 226.0 221.0 184.0 142.0 238.0 238.0 205.0 155.0
kW19.70 20.00 20.60 21.30 20.30 20.40 20.90 21.70 20.70 20.70 21.20 21.90
100
TC 206.0 213.0 230.0 248.0 222.0 224.0 239.0 257.0 234.0 234.0 245.0 263.0
SHC 206.0 190.0 159.0 126.0 222.0 218.0 182.0 140.0 234.0 234.0 202.0 153.0
kW20.60 20.80 21.40 22.10 21.10 21.20 21.70 22.50 21.50 21.50 22.00 22.70
105
TC 202.0 209.0 225.0 242.0 218.0 219.0 233.0 251.0 229.0 229.0 239.0 257.0
SHC 202.0 188.0 157.0 124.0 218.0 215.0 180.0 138.0 229.0 229.0 200.0 151.0
kW21.40 21.70 22.20 22.90 22.00 22.00 22.60 23.30 22.40 22.40 22.80 23.50
115
TC 195.0 200.0 215.0 232.0 210.0 210.0 223.0 239.0 220.0 220.0 228.0 244.0
SHC 195.0 184.0 153.0 120.0 210.0 209.0 175.0 134.0 220.0 220.0 196.0 147.0
kW23.30 23.40 24.00 24.60 23.80 23.80 24.30 25.00 24.20 24.20 24.50 25.20
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
52
PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E240 (cont)
LEGEND
566E240/524A-C300 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500 10,000 12,500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 249.0 254.0 272.0 293.0 268.0 268.0 282.0 303.0 281.0 281.0 289.0 309.0
SHC 249.0 236.0 196.0 154.0 268.0 268.0 226.0 172.0 281.0 281.0 253.0 190.0
kW18.30 18.50 19.20 19.90 19.00 19.00 19.50 20.30 19.50 19.50 19.80 20.50
85
TC 245.0 249.0 267.0 288.0 263.0 263.0 277.0 297.0 276.0 276.0 283.0 303.0
SHC 245.0 234.0 194.0 152.0 263.0 263.0 224.0 170.0 276.0 276.0 251.0 188.0
kW19.10 19.20 19.90 20.70 19.80 19.80 20.30 21.00 20.20 20.20 20.50 21.30
95
TC 237.0 240.0 257.0 277.0 254.0 254.0 266.0 285.0 266.0 266.0 272.0 290.0
SHC 237.0 229.0 190.0 148.0 254.0 254.0 220.0 166.0 266.0 266.0 246.0 184.0
kW20.70 20.80 21.40 22.20 21.30 21.30 21.80 22.60 21.80 21.80 22.00 22.80
100
TC 232.0 235.0 251.0 271.0 249.0 250.0 260.0 279.0 261.0 261.0 266.0 284.0
SHC 232.0 226.0 187.0 145.0 249.0 250.0 217.0 164.0 261.0 261.0 244.0 182.0
kW21.50 21.60 22.20 23.00 22.20 22.10 22.60 23.40 22.60 22.60 22.80 23.60
105
TC 228.0 230.0 246.0 265.0 244.0 245.0 254.0 272.0 256.0 256.0 260.0 277.0
SHC 228.0 223.0 185.0 143.0 244.0 245.0 215.0 162.0 256.0 256.0 241.0 180.0
kW22.30 22.40 23.00 23.80 23.00 23.00 23.40 24.20 23.50 23.40 23.60 24.40
115
TC 219.0 219.0 234.0 252.0 234.0 234.0 241.0 259.0 244.0 244.0 247.0 263.0
SHC 219.0 217.0 180.0 139.0 234.0 234.0 210.0 157.0 244.0 244.0 235.0 175.0
kW24.10 24.10 24.70 25.50 24.70 24.70 25.00 25.80 25.20 25.20 25.30 26.00
566E240/524A-B300 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7,500 10,000 12,500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 236.0 242.0 260.0 280.0 254.0 254.0 269.0 290.0 266.0 266.0 276.0 296.0
SHC 236.0 223.0 185.0 146.0 254.0 252.0 212.0 162.0 266.0 266.0 236.0 178.0
kW17.90 18.10 18.70 19.50 18.50 18.50 19.10 19.80 18.90 18.90 19.30 20.00
85
TC 233.0 238.0 256.0 275.0 250.0 250.0 265.0 285.0 262.0 262.0 271.0 290.0
SHC 233.0 221.0 184.0 144.0 250.0 249.0 210.0 161.0 262.0 262.0 234.0 176.0
kW18.70 18.80 19.50 20.20 19.30 19.30 19.80 20.60 19.70 19.70 20.00 20.80
95
TC 225.0 229.0 246.0 265.0 242.0 242.0 255.0 273.0 253.0 253.0 260.0 279.0
SHC 225.0 216.0 179.0 140.0 242.0 242.0 206.0 157.0 253.0 253.0 230.0 172.0
kW20.30 20.40 21.00 21.80 20.90 20.90 21.40 22.10 21.30 21.30 21.60 22.30
100
TC 221.0 225.0 241.0 260.0 237.0 237.0 249.0 268.0 248.0 248.0 255.0 273.0
SHC 221.0 214.0 178.0 138.0 237.0 237.0 204.0 155.0 248.0 248.0 227.0 170.0
kW21.10 21.20 21.80 22.50 21.70 21.70 22.10 22.90 22.10 22.10 22.40 23.10
105
TC 217.0 220.0 236.0 254.0 233.0 233.0 243.0 262.0 243.0 243.0 249.0 266.0
SHC 217.0 211.0 175.0 136.0 233.0 233.0 202.0 153.0 243.0 243.0 225.0 168.0
kW22.00 22.10 22.60 23.40 22.50 22.50 23.00 23.70 22.90 22.90 23.20 23.90
115
TC 209.0 211.0 225.0 242.0 223.0 223.0 232.0 249.0 233.0 233.0 237.0 253.0
SHC 209.0 206.0 171.0 132.0 223.0 223.0 197.0 148.0 233.0 233.0 219.0 164.0
kW23.80 23.80 24.40 25.10 24.30 24.30 24.60 25.40 24.70 24.70 24.90 25.60
Edb Entering Dry Bulb
Ewb — Entering Wet Bulb
kW—Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240
53
ELECTRICAL DATA
566D150-240
LEGEND *Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
566E150-240
LEGEND *Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-
installed accessory and is 115-v, 1ph, 60 Hz.
UNIT
SIZE
NOMINAL
VOLTAGE
(3-Ph, 60 Hz)
VO LTAGE
RANGE*
COMPRESSOR FAN MOTORS (Qty 2) POWER SUPPLY
RLA LRA
FLA (ea)
Fan No. kW MCA MOCP† ICF
Min Max 1 2
566D
150
208/230 187 253 49.3 191 4.3 3.7
1.41
69.6 100 199
460 414 528 22.1 80 2.3 1.9 31.7 50 84
575 518 660 17.9 69 1.8 1.8 25.6 40 73
180
208/230 187 253 63.6 266 4.3 3.7
1.41
87.5 125 274
460 414 528 29.3 120 2.3 1.9 40.7 60 124
575 518 660 23.8 96 1.8 1.8 33.0 50 100
240
208/230 187 254 67.9 345 4.3 3.7
1.41
93.4 150 353
460 414 508 34.7 173 2.3 1.9 48.1 80 177
575 518 632 28.8 120 1.8 1.8 40.1 60 124
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
ICF Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW—Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC,
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE* COMPRESSOR 1 COMPRESSOR 2
FAN MOTORS
Qty 2) POWER
SUPPLY
FLA (ea)
Fan No. kW
Min Max RLA LRA RLA LRA 1 2 MCA MOCP† ICF
566E
150
NONE OR DISCONNECT
CONVENIENCE OUTLET 208/230 187 253 20.7 156 20.7 156 4.3 3.7 1.41 55.6 70 186
63.5 80 194
NONE OR DISCONNECT
CONVENIENCE OUTLET 460 414 528 10.0 75 10.0 75 2.3 1.9 1.41 27.7 35 90
31.3 40 94
NONE OR DISCONNECT
CONVENIENCE OUTLET 575 518 660 8.2 54 8.2 54 1.8 1.8 1.41 23.1 30 67
25.9 30 70
180
NONE OR DISCONNECT
CONVENIENCE OUTLET 208/230 187 253 32.1 195 32.1 195 4.3 3.7 1.41 81.2 100 236
89.2 100 244
NONE OR DISCONNECT
CONVENIENCE OUTLET 460 414 528 16.4 95 16.4 95 2.3 1.9 1.41 42.1 50 117
45.7 60 120
NONE OR DISCONNECT
CONVENIENCE OUTLET 575 518 660 12.0 80 12.0 80 1.8 1.8 1.41 31.6 40 97
34.5 40 99
240
NONE OR DISCONNECT
CONVENIENCE OUTLET 208/230 187 253 37.8 239 37.8 239 4.3 3.7 1.41 94.1 125 286
102.0 150 294
NONE OR DISCONNECT
CONVENIENCE OUTLET 460 414 528 19.2 125 19.2 125 2.3 1.9 1.41 48.4 60 149
52.0 70 153
NONE OR DISCONNECT
CONVENIENCE OUTLET 575 518 660 13.8 80 13.8 80 1.8 1.8 1.41 35.7 45 98
38.5 50 101
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
ICF Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW—Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC,
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)
50TFQ004-012
566D/E150-240
54
APPLICATION DATA — 566D150-240, 566E150-240
1. INSTALLATION — Select equipment to match or to be
slightly less than peak load. This provides better humidity
control, less unit cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evalu-
ated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor unit
is operating.
Ductwork should be sized according to unit size, not build-
ing load.
To minimize the possibility of air recirculation, avoid the use
of concentric supply/return grilles.
Indoor equipment should be selected at no less than
300 cfm/ton.
OPERATING LIMITS
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566D150-240 UNITS
*Requires field-installed unloader.
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE — 566E150-240 UNITS
LIQUID LINE DATA — 566D150-240 UNITS
NOTE:Data above is for units operating at 45 F saturated suction and
95 F entering air.
LIQUID LINE DATA — 566E150-240 UNITS
2. REFRIGERANT PIPING — It is recommended that the
refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.
REFRIGERANT SPECIALTIES PART NUMBERS
*Bushings required.
Maximum Outdoor 115 F
Minimum Outdoor Ambient
See Minimum Outdoor-Air
Operating Temperature
table below.
Minimum Return-Air
Temperature 55 F
Maximum Return-Air
Temperature 95 F
Normal Acceptable Saturation
Suction Temperature Range 25 to 55 F
Maximum Discharge
Temperature 295 F
Minimum Discharge Superheat 60 F
UNIT
566D
NO. OF
CYLINDERS
FULL LOAD
CAPACITY
(%)
MINIMUM
OUTDOOR-AIR
OPERATING
TEMPERATURE (F)
Base
Unit
With
Low-Ambient
Control
150
6 100 20
–20
46731
2* 33* 40
180
6 100 20
46733
2* 33* 47
240 4 100 15
25020
UNIT
566E
FULL LOAD
CAPACITY
(%)
SATURATED COND
TEMPERATURE (F)
MINIMUM
OUTDOOR-AIR
TEMPERATURE (F)
Base
Unit
With
Low-Ambient
Control
150
100/50 90 50 –20180
240
UNIT
566D
MAX
ALLOW.
LIFT
(ft)
LIQUID LINE
Max Allow.
Pressure
Drop
(psi)
Max Allow.
Temp
Loss
(°F)
150 67 72
180 82
240 87
UNIT
566E
MAX
ALLOW.
LIFT
(ft)
LIQUID LINE
Max Allow.
Pressure
Drop
(psi)
Max Allow.
Temp
Loss
(°F)
150 60 7 2
180
240
UNIT LIQUID LINE
SIZE(in.)
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
566D150
1/2200RB7T4M AMG/24V AMI-1TT4 P502-8757S* S-7063
5/8200RA8T5M AMG/24V AMI-1TT5 P502-8757S* S-7063
566D180
1/2200RB7T4M AMG/24V AMI-1TT4 P502-8757S* S-7721
5/8200RA8T5M AMG/24V AMI-1TT5 P502-8757S* S-7721
7/8200RA8T7M AMG/24V AMI-1TT7 P502-8757S S-7721
566D240
5/8200RA9T5M AMG/24V AMI-1TT5 P502-8757S* S-7721
7/8200RA9T7M AMG/24V AMI-1TT7 P502-8757S S-7721
566E150 1/2200RB5T4M Qty 2 AMG/24V Qty 2 AMI-1TT4 Qty 2 P502-8304S Qty 2 S-7063S* Qty 2
566E180
1/2200RB5T4M Qty 2 AMG/24V Qty 2 AMI-1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
5/8200RB5T5M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
566E240
1/2200RB6T4M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8307S* S-7063S Qty 2
5/8200RB6T5M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8307S* S-7063S Qty 2
50TFQ004-012
566D/E150-240
55
APPLICATION DATA — 566D150-240, 566E150-240 (cont)
REFRIGERANT PIPING SIZES
LEGEND
Close-coupled.
*Requires a double suction riser if 2 unloaders are used and the evaporator is
below the condensing unit. See Refrigerant Piping Sizes — Double Suction Ris-
ers table and Suction Line Piping figure below for more information.
NOTES:
1. Pipe sizes are based on a 2° F loss for liquid lines and a 1.5° F loss for suc-
tion lines.
2. Pipe sizes are based on an equivalent length equal to the maximum length
of interconnecting piping plus 50% for fittings. A more accurate estimate
may result in smaller sizes.
REFRIGERANT PIPING SIZES —
DOUBLE SUCTION RISERS
NOTES:
1. See Suction Line Piping figure below for “A,” “B,” and “C” dimensions.
2. No double suction risers are needed for unit size 240.
UNIT
566D
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-15 16-25 26-50 51-75 76-100
Line Size (in. OD)
LSLSLSL S L S
150 1/211/81/213/85/813/85/815/8*7/815/8*
180 1/213/85/813/85/815/87/815/87/821/8*
240 5/815/85/815/87/815/87/821/87/821/8
UNIT
566E
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
0-25 25-50 50-75 75-100
Line Size (in. OD)
LSLSLSLS
150 1/211/81/211/81/211/81/211/8
180 1/213/81/213/81/213/85/813/8
240 1/213/81/213/85/813/85/813/8
L—Liquid
S—Suction
UNIT
566D
LINEAR LENGTH OF INTERCONNECTING PIPING (FT)
51-75 76-100
Line Size (in. OD)
ABCABC
150 11/813/815/811/813/815/8
180 ———1
3/815/821/8
Location ofOne Liquid Line Solenoid
Valve Serving 2 Coil Circuits
(Solenoid Drop Control)
TXV—Thermostatic
Expansion Valve
TXV—Thermostatic
Expansion Valve
Face-Split Coil Suction and
Liquid Line Piping
LEGEND
Suction Riser
Without
Tra p
Suction Riser
With
Tra p
Suction Line to Condensing Unit
Short Vertical Riser Into Condensing Unit:
566D150,180 — 13/8in. OD
A
B
C
D
Suction Line Piping
50TFQ004-012
566D/E150-240
56
APPLICATION DATA — 566D150-240, 566E150-240 (cont)
MULTIPLE CONDENSING UNIT ARRANGEMENTS*
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
566D,566E DIMENSIONS (ft)
150-240 AB
44
566D, 566E150-240 566D, 566E150-240
566D, 566E150-240
50TFQ004-012
566D/E150-240
57
TYPICAL PIPING AND WIRING
LEGEND
*Field supplied.
NEC National Electrical Code
TXV—Thermostatic Expansion Valve
Piping
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recom-
mended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Rooftop Installation — 566D150-240
50TFQ004-012
566D/E150-240
58
TYPICAL PIPING AND WIRING (cont)
LEGEND
*Field supplied.
NEC National Electrical Code
TXV—Thermostatic Expansion Valve
Piping
NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for, a
specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recom-
mended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
Ground Level Installation — 566D150-240
50TFQ004-012
566D/E150-240
59
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240
COMMERCIAL AIR-COOLED CONDENSING UNITS
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 121/2TO 20 TONS, NOMINAL
BRYANT MODEL NUMBER: 566D, SIZES 150-240
566E, SIZES 150-240
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for
on-the-ground or rooftop installation. Unit shall consist of a
semi-hermetic reciprocating compressor (566D) or scroll
compressor (566E), an air-cooled coil, propeller-type con-
denser fans, and a control box. Unit shall discharge supply
air upward as shown on contract drawings. Unit shall be
used in a refrigeration circuit to match a packaged fan coil
unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI latest revisions
and shall be certified and listed in the latest ARI directory.
B. UnitshallbemanufacturedinafacilityregisteredtoISO
9001:2000 manufacturing quality standard.
C. Unit construction shall comply with latest edition of ANSI/
ASHRAE and with NEC.
D. Unit shall be constructed in accordance with UL
standards and shall carry the UL and UL, Canada label.
E. Unit cabinet shall be capable of withstanding 500-hour
salt spray exposure per ASTM B117 (scribed specimen).
F. Air-cooled condenser coils shall be leak tested at
150 psig and pressure tested at 480 psig.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as a single package only, and
shall be stored and handled per manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
PART 2 — PRODUCTS
2.01 EQUIPMENT
A. General:
Factory assembled, single piece, air-cooled condensing
unit. Contained within the unit enclosure shall be all
factory wiring, piping, controls, compressor, holding
charge (R-22), and special features required prior to field
start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-90 galvanized
steel, bonderized and coated with a prepainted, baked
enamel finish.
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser-fan motor no. 1 shall be ball bearing type
compatible with accessory low-ambient control.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. 566D150-240 Units:
a. Compressor shall be serviceable, reciprocating,
semi-hermetic type.
b. Compressor shall be equipped with an automati-
cally reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
c. Compressor shall be mounted on spring vibration
isolators with an isolation efficiency of no less
than 95%.
d. Compressor speed shall not exceed 1750 rpm.
e. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
f. Compressor shall include overload protection.
g. Compressor shall be equipped with internal high
discharge temperature protection (566E180 and
240 only).
2. 566E150-240 Units:
a. Compressors shall be of the hermetic scroll type.
b. Compressors shall be mounted on vibration
isolators.
c. Compressors shall include overload protection.
d. Compressors shall be equipped with a crankcase
heater.
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for inte-
gral subcooler.
2. Coil shall be constructed of aluminum fins mechani-
cally bonded to copper tubes which are then
cleaned, dehydrated, and sealed. Copper fins shall
be available as an option.
F. Refrigeration Components:
1. Refrigeration circuit components for 566D units shall
include hot gas muffler, high-side pressure relief
device, liquid line shutoff valve, suction and dis-
charge shutoff valves, holding charge of refrigerant
R-22, and compressor oil.
2. Refrigeration circuit components for 566E units shall
include liquid line service valve, suction line service
valve, a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Compressor cycle delay protection prevents the
compressor from restarting for a minimum of
5 minutes after shutdown.
c. Capacity control on the compressor shall be by
suction cutoff unloader in response to compres-
sor suction pressure. Electric solenoid unloading
shall be available as an accessory (566D unit).
d. Head pressure control by fan cycling. One con-
denser fan shall be cycled by discharge pressure
to maintain proper head pressure.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat)
a. High discharge-pressure cutout.
b. Low suction pressure cutout.
c. Condenser-fan motors to be protected against
overload condition by internal overloads.
50TFQ004-012
566D/E150-240
60
GUIDE SPECIFICATIONS — 566D150-240, 566E150-240 (cont)
Manual reset at the unit
Electrical overload protection through the use of def-
inite-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers. Circuit
breakers shall open all 3 phases in the event of an
overload in any one of the phases or a single-phase
condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
exceed_____Btuh at a suction temperature of_____ F.
The power consumption at full load shall not
exceed_____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net cool-
ing capacity of _____ Btuh or greater at conditions of
_____ cfm entering-air temperature at the evaporator
at _____ F wet bulb and _____ F dry bulb, and air
entering the condensing unit at _____ F.
3. The system shall have an EER of _____ Btuh/Watt or
greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be _____ v,
3-ph, 60 Hz. The unit shall be capable of satisfactory
operation within voltage limits of _____ v to _____ v.
2. Unit electrical power shall be single point connection.
3. Unit control circuit shall contain a 24-v transformer
for unit control, with capacity to operate an indoor fan
interlock.
J. Special Features:
1. Low-Ambient Temperature Control (Factory-Installed
Option or Field-Installed Accessory):
Control shall regulate fan motor speed in response
to the saturated condensing temperature of the unit.
The control shall allow the unit to operate down to an
ambient temperature of –20 F.
2. Electric Solenoid Unloader Accessory:
Unloader valve piston, coil, and hardware shall be
supplied to convert the pressure-operated compres-
sor unloader to electric unloading.
3. Hail Guard Package:
Hail guard package shall protect coil against hail and
other flying debris.
4. Condenser Coil Grille Package:
Grilles shall protect the condenser coils after unit
installation.
5. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating to
provide protection in mildly corrosive coastal envi-
ronments. Coating shall be applied to the alumi-
num fin stock prior to the fin stamping process to
create an inert barrier between the aluminum fin
and copper tube. Epoxy-phenolic barrier shall
minimize galvanic action between dissimilar
metals.
b. E-Coated Aluminum-Fin Coils:
Shall have a flexible epoxy polymer coating uni-
formly applied to all coil surface areas without
material bridging between fins. Coating process
shall ensure complete coil encapsulation. Color
shall be high gloss black with gloss requirements
of 60°of 65-90% per ASTM D523-89. Uniform dry
film thickness from 0.8 to 1.2 mil on all surface
areas including fin edges. Superior hardness
characteristics of 2H per ASTM D3363-92A and
cross hatch adhesion of 4B-5B per ASTM D3359-
93. Impact resistance shall be up to 160 in./lb
(ASTM D2794-93). Humidity and water immersion
resistance shall be up to a minimum of 1000 and
250 hours respectively (ASTM-D2247-92 and
ASTM D870-92). Corrosion durability shall be
confirmed through testing to no less than 1000
hours salt spray per ASTM B117-90. Coil con-
struction shall be aluminum-fins mechanically
bonded to copper tubes.
6. Thermostat Control Accessory:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
7. Unit-Mounted, Non-Fused Disconnect Switch:
Shall be factory-installed, internally mounted. NEC
and UL approved non-fused switch shall provide unit
power shutoff. Shall be accessible from outside the
unit and shall provide power off lockout capability.
Not to be used when rooftop electrical rating
exceeds 80 amperes.
8. Convenience Outlet:
Shall be factory-installed and internally mounted
with easily accessible 115-v female receptacle. Shall
include 15 amp GFI receptacle with independent
fuse protection. Voltage required to operate conve-
nience outlet shall be provided by a factory-installed
step-down transformer. Shall be accessible from out-
side the unit.
50TFQ004-012
566D/E150-240
61
MODEL NUMBER NOMENCLATURE
524A P B 120 000 GC
524A Fan Coil
Voltage
E460-3-60
J208/230-1-60 (Sizes 072, 090 Only)
P208/230-3-60
T575-3-60
Coil Option
BDX Cooling Coil With TXVs
CDX High Capacity Cooling Coil With TXVs
Nominal Cooling (Tons)
072 6
090 7-1/2
120 10
150 12-1/2
180 15
240 20
300 25
Factory-Installed Options
GC Unpainted, Standard Motor
and Standard Drive
HC Unpainted, Standard Motor
and Medium-Static Drive
(not available for 300 sizes)
TC Unpainted, Alternate Motor
and Medium-Static Drive
(300 size only)
YC Unpainted, Alternate Motor
and High-Static Drive*
ED Painted, Standard Motor
and Standard Drive
FD Painted, Standard Motor
and Medium-Static Drive
(not available for 300 size)
RD Painted, Alternate Motor
and Medium-Static Drive
(300 size only)
WD Painted, Alternate Motor
and High-Static Drive*
Nominal Heating (Btuh)
000 Not applicable (524A-B and 524A-C Cooling-Only Units)
LEGEND
*The YC and WD option codes for all 090 size units with 208/230-1-60 voltage designate standard motor and high-static drive.
†All 524A072-150 units with an “E” voltage designation are triple voltage (i.e., 208/230/460-3-60). Size 524A180 is also triple voltage in the “E” con-
figuration unless the alternate motor (YC or WD) option is used.
DXDirect Expansion
TXV—Thermostatic Expansion Valve
Certified to ISO 9001:2000
Quality Assurance
50TFQ004-012
524A072-300
62
PHYSICAL DATA
524A-B,C UNITS
LEGEND
*Refer to Alternate Fan Motor Data table, page 80, for alternate motor data.
†Units are shipped without refrigerant charge.
UNIT 524A 072 090 120 150 180 240 300
NOMINAL CAPACITY (Tons) 67
1/210 121/215 20 25
OPERATING WEIGHT (lb)
Base Unit with TXV (3 Row/4 Row) 381/399 385/404 405/425 670/695 685/713 690/730 1020/1050
Plenum 175 175 175 225 225 225 325
Economizer 185 185 185 340 340 340 340
Hot Water Coil 195 195 195 285 285 285 345
Steam Coil 215 215 215 340 340 340 405
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8000 10,000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500
Nominal Motor Hp (Standard Motor)*
208/230-1-60 1.3 2.4
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5
575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5
Motor Speed (rpm)
208/230-1-60 1725 1725
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755
REFRIGERANT R-22
Operating charge (lb)
(approx per circuit)† 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sqft) 6.67 8.33 10.01 13.25 17.67 19.88 24.86
No. ofSplits 11222 2 2
Split Type...Percentage —— Face...50/50
No. ofCircuits per Split (3 Row/4 Row) 12/12 15/15 9/9 9/12 12/16 13/18 15/20
Fins/in. 15 15 17 15 15 17 15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sqft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sqft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5
Water Volume
(gal) 8.3 13.9 14.3
(ft3)1.1 1.85 1.90
PIPING CONNECTIONS
Quantity...Size (in.)
DXCoil — Suction (ODF) 1...11/81...11/82...11/82...11/82...11/82...1 1/82...13/8
DXCoil — Liquid Refrigerant (ODF) 1...5/82...5/8
Steam Coil, In (MPT) 1...21/21...21/2
Steam Coil, Out (MPT) 1...11/21...11/2
Hot Water Coil, In (MPT) 1...11/21...11/21...2
Hot Water Coil, Out (MPT) 1...11/21...11/21...2
Condensate (PVC) 1...11/4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2
4...16 x 24 x 2
4...20 x 24 x 2
4...20 x 25 x 2
Access Location Right or Left Side
DXDirect Expansion
TXV—Thermostatic Expansion Valve
50TFQ004-012
524A072-300
63
DIMENSIONS
524A-B,C072-120
UNIT UNIT WEIGHT
(lb)
524A-B072 381
524A-B090 385
524A-B120 405
524A-C072 399
524A-C090 404
524A-C120 425
LEGEND
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3(76.2 mm) (2-6[762 mm]
with electric heat accessory)
Front: 2-6(762 mm)
Right Side: 2-6(762 mm)
Left Side: 2-6(762 mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
TXV—Thermostatic Expansion Valve
50TFQ004-012
524A072-300
64
DIMENSIONS (cont)
524A-B,C150-240
.
UNIT
524A
UNIT
WEIGHT
(lb)
B150 670
B180 685
B240 690
C150 695
C180 713
C240 730
LEGEND
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3(76.2 mm) (2-6[762 mm]
with electric heat accessory)
Front: 2-6(762 mm)
Right Side: 2-6(762 mm)
Left Side: 2-6(762 mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
TXV—Thermostatic Expansion Valve
50TFQ004-012
524A072-300
65
DIMENSIONS (cont)
524A-B,C300
CONTROL BOX
CONTROL BOX
ALTERNATE
ACCESS
FOR FILTERS
RETURN AIR
OPENING
ALTERNATE
ACCESS FOR
MOTOR/BELT
UNIT
524A
UNIT
WEIGHT
(lb)
B300 1020
C300 1050
LEGEND
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3(76.2 mm) (2-6[762 mm]
with electric heat accessory)
Front: 2-6(762 mm)
Right Side: 2-6(762 mm)
Left Side: 2-6(762 mm)
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Bryant.
5. Duct flange is factory supplied and field
installed.
TXV—Thermostatic Expansion Valve
50TFQ004-012
524A072-300
66
PERFORMANCE DATA
524A-B FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP
See Legend and Notes on page 67.
UNIT
524A-B
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
072
1,800 399 0.19 454 0.24 548 0.35 634 0.47 713 0.60 785 0.74 850 0.89
2,100 446 0.28 497 0.34 583 0.46 660 0.59 733 0.73 802 0.88 867 1.05
2,400 498 0.40 541 0.47 622 0.60 693 0.74 760 0.89 824 1.05 885 1.22
2,700 544 0.55 588 0.63 663 0.78 730 0.93 792 1.09 851 1.26 909 1.44
3,000 594 0.73 635 0.82 707 0.99 770 1.15 828 1.32 883 1.50 937 1.69
090
2,250 273 0.08 493 0.37 580 0.49 656 0.62 727 0.76 794 0.92 858 1.08
2,600 322 0.15 540 0.52 622 0.66 693 0.81 757 0.96 819 1.12 878 1.29
3,000 552 0.65 595 0.73 673 0.91 740 1.07 800 1.24 856 1.41 910 1.60
3,400 615 0.91 653 1.01 726 1.21 789 1.40 846 1.59 899 1.78 950 1.97
3,750 671 1.20 706 1.31 773 1.53 834 1.74 889 1.95 940 2.16 988 2.37
120
3,000 399 0.29 573 0.69 654 0.86 722 1.03 784 1.19 841 1.37 896 1.55
3,500 604 0.92 641 1.02 714 1.22 780 1.42 838 1.61 892 1.81 942 2.01
4,000 680 1.33 713 1.45 778 1.68 839 1.91 896 2.14 947 2.36 995 2.58
4,500 756 1.86 787 1.99 845 2.26 901 2.52 955 2.78 1005 3.03 1051 3.28
5,000 834 2.51 861 2.67 914 2.96 966 3.25 1180 3.54 1064 3.82 1109 4.11
150
3,750 394 0.40 453 0.52 558 0.80 643 1.10 717 1.39 785 1.71 848 2.04
4,300 436 0.57 487 0.70 586 1.00 670 1.34 742 1.67 806 2.01 867 2.36
5,000 492 0.86 535 0.99 623 1.31 704 1.69 775 2.08 838 2.47 896 2.86
5,700 550 1.23 587 1.37 664 1.71 740 2.11 809 2.55 872 2.99 929 3.43
6,250 596 1.59 630 1.74 700 2.09 770 2.51 837 2.97 899 3.45 955 3.94
180
4,500 428 0.59 475 0.70 570 0.99 656 1.33 730 1.68 796 2.02 856 2.38
5,300 488 0.92 528 1.04 609 1.34 689 1.71 762 2.11 827 2.51 886 2.92
6,000 542 1.29 578 1.43 649 1.74 721 2.11 791 2.55 855 3.00 914 3.46
6,800 604 1.83 637 1.99 700 2.32 763 2.70 826 3.15 888 3.64 946 4.15
7,500 660 2.42 690 2.59 747 2.95 804 3.34 861 3.79 919 4.29 975 4.83
240
6,000 532 1.25 569 1.39 639 1.69 711 2.06 781 2.48 846 2.93 905 3.39
7,000 608 1.93 641 2.09 702 2.42 763 2.80 824 3.23 885 3.71 943 4.23
8,000 686 2.83 716 3.01 770 3.38 823 3.77 876 4.21 930 4.70 983 5.24
9,000 764 3.97 791 4.18 841 4.59 888 5.02 935 5.47 982 5.96 1030 6.51
10,000 843 5.38 868 5.62 914 6.09 957 6.55 1000 7.02 1042 7.53 1084 8.08
300
7,500 456 1.29 490 1.47 556 1.85 621 2.25 678 2.64 729 3.06 778 3.60
8,750 521 1.98 551 2.18 608 2.61 664 3.07 720 3.53 770 3.99 816 4.45
10,000 587 2.88 614 3.11 664 3.59 714 4.09 763 4.62 812 5.15 857 5.68
11,250 653 4.03 678 4.29 724 4.82 768 5.37 812 5.95 856 6.54 899 7.14
12,500 720 5.46 743 5.75 785 6.33 825 6.93 865 7.55 904 8.20 944 8.86
50TFQ004-012
524A072-300
67
PERFORMANCE DATA (cont)
524A-B FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.
UNIT
524A-B
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
072
1,800 910 1.04 965 1.20 1180 1.36 1065 1.52 1111 1.69 1155 1.86
2,100 927 1.21 983 1.38 1035 1.56 1084 1.74 1131 1.92 1175 2.11
2,400 944 1.41 999 1.59 1052 1.78 1101 1.98 1149 2.18 1193 2.38
2,700 964 1.63 1018 1.82 1069 2.03 1118 2.24 1165 2.45 ——
3,000 989 1.89 1039 2.10 1089 2.31 1136 2.53 1183 2.76 ——
090
2,250 918 1.26 975 1.43 1029 1.62 1079 1.80 1126 1.99 1172 2.18
2,600 936 1.48 991 1.67 1044 1.87 1094 2.07 1142 2.28 1188 2.49
3,000 963 1.79 1150 1.99 1064 2.20 1113 2.42 1159 2.64 ——
3,400 998 2.18 1045 2.39 1092 2.61 1137 2.83 1182 3.07 ——
3,750 1360 2.58 1078 2.80 1122 3.03 1164 3.27 ———
120
3,000 949 1.74 1000 1.93 1050 2.14 1099 2.36 1147 2.58 1192 2.81
3,500 990 2.21 1037 2.42 1083 2.64 1128 2.86 1172 3.10 ——
4,000 1040 2.80 1084 3.03 1126 3.26 1167 3.50 ———
4,500 1094 3.53 1136 3.78 1176 4.03 —————
5,000 1151 4.39 1191 4.66 ———————
150
3,750 909 2.37 968 2.74 1026 3.12 1080 3.51 1131 3.92 1181 4.32
4,300 925 2.73 980 3.11 1360 3.52 1084 3.92 1135 4.35 1184 4.78
5,000 950 3.26 1002 3.67 1052 4.09 1101 4.53 1148 4.98 1190 5.44
5,700 981 3.88 1031 4.33 1079 4.79 1125 5.25 1169 5.73 ——
6,250 1072 4.42 1057 4.91 1103 5.40 1148 5.90 1191 6.40 ——
180
4,500 912 2.75 967 3.13 1019 3.52 1070 3.92 1120 4.35 1168 4.79
5,300 940 3.33 992 3.75 1041 4.18 1088 4.61 1134 5.06 1179 5.52
6,000 968 3.92 1018 4.38 1066 4.85 1112 5.32 1156 5.80 1198 6.29
6,800 1000 4.67 1050 5.19 1097 5.71 1142 6.23 1185 6.76 ——
7,500 1300 5.39 1078 5.97 1125 6.54 1170 7.11 ———
240
6,000 954 3.83 1005 4.27 1052 4.72 1098 5.22 1142 5.67 ——
7,000 990 4.74 1040 5.24 1090 5.80 1135 6.30 1176 6.84 ——
8,000 1300 5.79 1078 6.38 1130 7.00 1173 7.60 ———
9,000 1073 7.11 1120 7.72 1169 8.37 —————
10,000 1126 8.75 1166 9.37 ———————
300
7,500 831 4.41 870 5.10 913 5.90 950 6.88 985 7.70 ——
8,750 859 4.97 901 5.59 944 6.42 980 7.20 1020 8.10 ——
10,000 900 6.20 939 6.74 976 7.33 1013 8.00 1050 8.82 ——
11,250 941 7.73 980 8.32 1017 8.90 1052 9.51 1086 10.16 ——
12,500 984 9.53 1022 10.19 1058 10.84 1093 11.49 ———
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
50TFQ004-012
524A072-300
68
PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C WITH HIGH CAPACITY COIL —
0.0-1.2 in. wg ESP
See Legend and Notes on page 69.
UNIT
524A-C
(High-Capacity
4-Row Coil)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
072
1,800 419 0.21 471 0.26 564 0.37 649 0.49 727 0.63 797 0.77 862 0.92
2,100 471 0.31 519 0.37 602 0.49 679 0.62 751 0.77 819 0.92 882 1.09
2,400 524 0.44 568 0.51 645 0.64 715 0.79 781 0.94 844 1.11 905 1.28
2,700 578 0.61 619 0.69 690 0.84 755 0.99 816 1.15 875 1.33 932 1.51
3,000 633 0.81 671 0.90 738 1.07 799 1.24 856 1.41 910 1.60 963 1.79
090
2,250 290 0.10 510 0.39 594 0.51 669 0.65 739 0.79 806 0.95 870 1.12
2,600 349 0.19 561 0.55 640 0.70 709 0.84 773 1.00 834 1.16 893 1.34
3,000 579 0.70 621 0.79 695 0.96 759 1.12 818 1.30 874 1.47 928 1.66
3,400 646 0.99 683 1.09 752 1.29 813 1.48 869 1.67 920 1.86 970 2.06
3,750 705 1.31 739 1.42 804 1.63 862 1.85 915 2.05 964 2.26 1011 2.48
120
3,000 421 0.35 592 0.73 670 0.90 737 1.06 797 1.23 854 1.41 908 1.59
3,500 626 0.98 664 1.08 735 1.28 798 1.48 855 1.67 908 1.87 958 2.07
4,000 706 1.42 738 1.54 803 1.77 862 2.00 917 2.23 967 2.45 1150 2.67
4,500 786 1.99 815 2.12 873 2.39 929 2.65 980 2.90 1300 3.16 1073 3.41
5,000 867 2.70 893 2.84 946 3.14 997 3.43 1046 3.72 1092 4.00 1135 4.28
150
3,750 410 0.43 467 0.55 567 0.83 649 1.12 721 1.41 788 1.72 851 2.05
4,300 455 0.62 504 0.74 599 1.05 679 1.38 748 1.70 811 2.04 871 2.39
5,000 514 0.92 556 1.06 641 1.39 718 1.76 786 2.14 847 2.52 903 2.91
5,700 575 1.32 612 1.47 686 1.82 759 2.23 825 2.66 884 3.09 939 3.52
6,250 624 1.71 657 1.87 725 2.24 793 2.66 856 3.12 915 3.59 969 4.06
180
4,500 437 0.61 483 0.72 576 1.01 660 1.35 732 1.69 797 2.03 856 2.38
5,300 499 0.95 538 1.07 617 1.37 696 1.74 767 2.13 830 2.53 888 2.94
6,000 555 1.34 590 1.48 659 1.79 730 2.17 798 2.59 860 3.04 918 3.49
6,800 620 1.91 651 2.06 712 2.39 774 2.78 836 3.22 896 3.71 952 4.21
7,500 677 2.52 706 2.69 761 3.04 817 3.44 873 3.89 929 4.39 984 4.93
240
6,000 542 1.29 577 1.42 646 1.72 716 2.09 785 2.51 849 2.95 907 3.40
7,000 620 1.99 652 2.15 711 2.48 771 2.85 831 3.28 890 3.76 947 4.27
8,000 700 2.92 728 3.10 781 3.46 833 3.85 885 4.29 938 4.78 990 5.32
9,000 781 4.10 806 4.30 854 4.71 900 5.13 946 5.58 993 6.08 1039 6.62
10,000 862 5.56 885 5.79 929 6.24 971 6.70 1120 7.18 1054 7.69 1096 8.24
300
7,500 476 1.39 510 1.58 579 1.99 644 2.40 701 2.81 752 3.29 804 3.96
8,750 545 2.14 574 2.35 633 2.81 691 3.29 747 3.77 797 4.25 842 4.76
10,000 615 3.12 641 3.36 692 3.87 743 4.41 794 4.96 843 5.51 888 6.05
11,250 685 4.37 709 4.64 754 5.20 800 5.79 845 6.40 891 7.02 935 7.64
12,500 756 5.92 778 6.22 819 6.83 860 7.47 901 8.14 942 8.83 983 9.52
50TFQ004-012
524A072-300
69
PERFORMANCE DATA (cont)
FAN PERFORMANCE DATA — 524A-C
WITH HIGH CAPACITY COIL — 1.4-2.4 in. wg ESP
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 79-81, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit size 300;
1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table on page 70 for factory-supplied
filter pressure drop.
3. The medium-static drive and standard motor combination is not
available for 300 size. Use alternate motor if medium-static drive is
required for these sizes.
UNIT
524A-C
(High-Capacity
4-Row Coil)
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0 2.2 2.4
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
072
1,800 921 1.07 975 1.23 1026 1.39 1074 1.55 1120 1.72 1164 1.90
2,100 942 1.26 997 1.43 1048 1.61 1097 1.79 1143 1.97 1186 2.16
2,400 963 1.47 1017 1.66 1069 1.85 1118 2.05 1164 2.25 ——
2,700 987 1.71 1039 1.91 1090 2.12 1138 2.33 1185 2.55 ——
3,000 1015 1.99 1065 2.20 1113 2.42 1161 2.65 ————
090
2,250 930 1.29 986 1.47 1039 1.65 1089 1.84 1136 2.03 1181 2.22
2,600 950 1.53 1005 1.72 1057 1.92 1107 2.13 1154 2.33 ——
3,000 980 1.86 1031 2.06 1081 2.27 1129 2.49 1175 2.72 ——
3,400 1018 2.26 1065 2.48 1111 2.70 1156 2.93 ————
3,750 1057 2.69 1101 2.92 1144 3.15 1186 3.39 ————
120
3,000 961 1.78 1120 1.98 1062 2.19 1111 2.41 1158 2.64 ——
3,500 1005 2.27 1052 2.49 1098 2.71 1142 2.94 1186 3.18 ——
4,000 1058 2.90 1101 3.13 1143 3.36 1184 3.60 ————
4,500 1116 3.66 1157 3.91 1196 4.16 ———
5,000 1176 4.56 ———————
150
3,750 912 2.39 971 2.76 1300 3.14 1083 3.54 1135 3.95 1185 4.36
4,300 928 2.75 982 3.13 1036 3.53 1087 3.94 1138 4.37 1187 4.81
5,000 956 3.30 1072 3.71 1056 4.13 1104 4.56 1151 5.00 1196 5.46
5,700 990 3.96 1039 4.40 1086 4.85 1130 5.31 1174 5.78 ——
6,250 1019 4.54 1067 5.02 1112 5.50 1156 5.99 1198 6.49 ——
180
4,500 912 2.75 967 3.12 1019 3.52 1070 3.92 1120 4.35 1168 4.79
5,300 942 3.34 992 3.76 1041 4.18 1088 4.61 1134 5.06 1179 5.52
6,000 971 3.95 1020 4.40 1067 4.86 1112 5.33 1156 5.81 1198 6.29
6,800 1005 4.72 1054 5.23 1101 5.75 1145 6.27 1187 6.79 ——
7,500 1036 5.48 1084 6.04 1131 6.61 1174 7.17 ————
240
6,000 961 3.86 1011 4.31 1058 4.77 1104 5.24 1147 5.71 ——
7,000 1000 4.79 1050 5.32 1097 5.85 1142 6.38 1184 6.91 ——
8,000 1041 5.88 1090 6.47 1137 7.07 1181 7.67 ————
9,000 1086 7.21 1133 7.82 1178 8.47 ———
10,000 1138 8.83 1240 9.46 —————
300
7,500 874 5.33 897 5.91 940 6.80 990 7.50 ————
8,750 886 5.36 930 6.13 982 7.32 1020 8.10 ————
10,000 930 6.60 969 7.20 1072 7.89 1045 8.71 ————
11,250 976 8.25 1150 8.86 1051 9.49 1086 10.17 ————
12,500 1023 10.20 1061 10.88 1097 11.56 ———
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
50TFQ004-012
524A072-300
70
PERFORMANCE DATA (cont)
FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATA
Throw distances shown are for 75 fpm terminal velocity. Use the follow-
ing multipliers to determine throw values for other terminal velocities.
ACCESSORY PRESSURE DROP (in. wg)
UNIT
524A-B
524A-C
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
072
1,800
2,400
3,000
0.05
0.08
0.11
090
2,250
3,000
3,750
0.07
0.11
0.15
120
3,000
4,000
5,000
0.11
0.17
0.23
150
3,750
5,000
6,250
0.06
0.10
0.13
180
4,500
6,000
7,500
0.08
0.12
0.17
240
6,000
8,000
10,000
0.12
0.19
0.26
300
7,500
10,000
12,500
0.15
0.22
0.30
UNIT
524A
AIRFLOW
(Cfm)
VANE DEFLECTION
Straight 21½° 45°
072 2,400 39 33 24
090 3,000 45 38 28
102 3,400 49 41 30
120 4,000 55 46 33
150 5,000 45 38 28
180 6,000 50 43 31
240 8,000 60 51 37
300 10,000 76 65 47
TERMINAL VELOCITY
(Fpm) THROW FACTOR
50 X1.50
100 X0.75
150 X0.50
UNIT
524A
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
HEATING COILS ECONOMIZER
Hot Water Steam Electric
072
1,800
2,400
3,000
0.06
0.10
0.14
0.01
0.01
0.02
0.10
0.16
0.23
0.10
0.16
0.23
0.04
0.06
0.10
0.05
0.07
0.09
090
2,250
3,000
3,750
0.09
0.14
0.21
0.01
0.02
0.03
0.15
0.23
0.35
0.15
0.23
0.35
0.06
0.10
0.15
0.06
0.09
0.15
102
2,550
3,400
4,250
0.11
0.17
0.24
0.02
0.03
0.04
0.18
0.28
0.41
0.18
0.28
0.41
0.07
0.12
0.19
0.07
0.13
0.19
120
3,000
4,000
5,000
0.14
0.22
0.32
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
150
3,750
5,000
6,250
0.07
0.12
0.17
0.01
0.02
0.02
0.11
0.17
0.25
0.11
0.17
0.25
0.04
0.07
0.11
0.05
0.07
0.11
180
4,500
6,000
7,500
0.10
0.16
0.23
0.01
0.02
0.03
0.15
0.23
0.33
0.15
0.23
0.33
0.06
0.10
0.15
0.06
0.09
0.15
240
6,000
8,000
10,000
0.16
0.26
0.37
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
300
7,500
10,000
12,500
0.15
0.24
0.34
0.02
0.03
0.05
0.28
0.44
0.63
0.28
0.44
0.63
0.09
0.16
0.24
0.06
0.09
0.14
50TFQ004-012
524A072-300
71
PERFORMANCE DATA (cont)
HYDRONIC HEATING CAPACITIES
LEGEND
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
†Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.
2. Leaving db =ent db (F) +
3. See Heating Correction Factors table.
HEATING CORRECTION FACTORS
NOTE:Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually
operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.
UNIT
524A-B
524A-C
AIRFLOW
(Cfm)
1-ROW
STEAM*
2-ROW
HOT WATER COIL†
Cap. Ldb Cap. Ldb
Water
Flow
(Gpm)
PD
072
1,800
2,400
3,000
146
173
209
134
126
123
156.0
183.0
206.0
140
131
124
15.6
18.3
20.6
3.4
4.3
5.2
090
2,250
3,000
3,750
168
209
240
129
123
117
174.0
206.0
238.0
133
124
118
17.4
20.6
23.8
4.0
5.2
6.5
120
3,000
4,000
5,000
209
243
279
123
115
111
299.0
275.0
316.0
152
124
119
29.9
27.5
31.6
5.0
6.6
8.2
150
3,750
5,000
6,250
370
425
465
150
137
128
362.0
409.0
456.0
149
136
128
36.2
40.9
45.6
4.2
5.1
6.0
180
4,500
6,000
7,500
402
458
479
141
129
118
412.0
471.0
529.0
145
133
125
41.2
47.1
52.9
4.5
5.5
6.6
240
6,000
8,000
10,000
458
487
499
129
115
105
506.0
584.0
652.0
138
128
120
50.6
58.4
65.2
5.1
6.3
7.5
300
7,500
10,000
12,500
511
575
626
122
112
106
649.0
752.0
842.0
140
130
122
64.9
75.2
84.2
5.7
7.1
8.5
Cap. — Capacity (Btuh in thousands)
Lab — Leaving-Air Dry-Bulb Temp (F)
PD Pressure Drop (ft water)
Capacity (Btuh)
1.1 x cfm
HOT WATER COIL
Water Temp
Drop
(F)
Ent Water
Temp
(F)
Entering-Air Temp (F)
40 50 60 70 80
10
140 0.72 0.64 0.57 0.49 0.41
160 0.89 0.81 0.74 0.66 0.58
240 1.06 0.98 0.90 0.83 0.75
200 1.22 1.15 1.07 1.00 0.92
220 1.39 1.32 1.24 1.17 1.09
20
140 0.64 0.57 0.49 0.41 0.33
160 0.81 0.74 0.66 0.58 0.51
240 0.98 0.91 0.83 0.75 0.68
200 1.15 1.08 1.00 0.93 0.85
220 1.32 1.25 1.17 1.10 1.02
30
140 0.56 0.49 0.41 0.33 0.24
160 0.74 0.66 0.58 0.51 0.43
240 0.91 0.83 0.76 0.68 0.60
200 1.08 1.00 0.93 0.85 0.78
220 1.25 1.18 1.10 1.03 0.95
STEAM COIL
Steam Pressure
(psig)
Entering-Air Temp (F)
40 50 60 70 80
01.06 0.98 0.91 0.85 0.78
21.09 1.02 0.95 0.89 0.82
51.13 1.06 1.00 0.93 0.87
50TFQ004-012
524A072-300
72
ELECTRICAL DATA
524A-B,C STANDARD MOTORS
See Legend and Notes on page 73.
UNIT
524A-B
524A-C
V*-PH-Hz VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit
Amps MOCP
072
208/230-1-60 187-253 1.3 (0.97) 7.6 9.5 15
208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 15
460-3-60 414-506 2.4 (1.79) 2.6 3.3 15
575-3-60 518-632 1.0 (0.75) 1.4 1.8 15
090
208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 20
208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 15
460-3-60 414-506 2.4 (1.79) 2.6 3.3 15
575-3-60 518-632 2.0 (1.49) 2.3 2.9 15
120
208/230-3-60 187-253 2.4 (1.79) 5.2 6.5 15
460-3-60 414-506 2.4 (1.79) 2.6 3.3 15
575-3-60 518-632 2.0 (1.49) 2.3 2.9 15
150
208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15
460-3-60 414-506 2.9 (2.16) 3.4 4.3 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
180
208/230-3-60 187-253 3.7 (2.76) 10.2 12.8 20
460-3-60 414-506 3.7 (2.76) 4.8 6.0 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
240
208/230-3-60 187-253 5.0 (3.73) 14.6/12.8 18.3/16.0 30/25
460-3-60 414-506 5.0 (3.73) 6.4 8.0 15
575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
300
208/230-3-60 187-253 7.5 (5.59) 21.5/19.4 26.9/24.3 45/40
460-3-60 414-506 7.5 (5.59) 9.7 12.1 20
575-3-60 518-632 7.5 (5.59) 7.8 9.8 15
50TFQ004-012
524A072-300
73
ELECTRICAL DATA (cont)
524A-B,C ALTERNATE MOTORS
LEGEND
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in
accordance with NEC (National Electrical Code) Article 440.
2. Motor FLA values are established in accordance with UL (Under-
writers’ Laboratories) Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%
. Use the following formula to determine the per-
centage of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB =393 v
BC =403 v
AC =396 v
=397
Determine maximum deviation from average voltage.
(AB) 397 – 393 =4v
(BC) 403 – 397 =6v
(AC) 397 – 396 =1v
Maximum deviation is 6 v.
Determine percent of voltage imbalance.
% Voltage Imbalance =100 x
=1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT:If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
UNIT
524A-B
524A-C
V*-PH-Hz VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA Minimum Circuit
Amps MOCP
072
208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 20
208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15
460-3-60 414-506 2.9 (2.16) 3.4 4.3 15
575-3-60 518-632 2.0 (1.49) 2.3 2.9 15
090
208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 15
208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15
460-3-60 414-506 2.9 (2.16) 3.4 4.3 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
120
208/230-3-60 187-253 3.7 (2.76) 10.2 12.8 20
460-3-60 414-506 3.7 (2.76) 4.8 6.0 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
150
208/230-3-60 187-253 3.7 (2.76) 10.2 12.7 20
460-3-60 414-506 3.7 (2.76) 4.8 6.0 15
575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
180
208/230-3-60 187-253 5.0 (3.73) 14.6/12.8 18.3/16.0 30/25
460-3-60 414-506 5.0 (3.73) 6.4 8.0 15
575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
240
208/230-3-60 187-253 7.5 (5.59) 21.5/19.4 26.9/24.3 45/40
460-3-60 414-506 7.5 (5.59) 9.7 12.1 20
575-3-60 518-632 7.5 (5.59) 7.8 9.8 15
300
208/230-3-60 187-253 10.0 (7.46) 28.2/26.8 35.3/33.5 60/60
460-3-60 414-506 10.0 (7.46) 13.4 16.8 30
575-3-60 518-632 10.0 (7.46) 10.3 12.9 20
FLA Full Load Amps
MOCP — Maximum Overcurrent Protection
=100 x max voltage deviation from average voltage
average voltage
Average Voltage =393 +403 +396
3
=1192
3
6
397
50TFQ004-012
524A072-300
74
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA
See Legend and Notes on page 75.
HEATER PART NO. UNIT V-PH-Hz FAN M OTOR ELECTRIC HEATER(S)
MCA* MOCP*Nominal
Capacity (kW)
Actual Capacity (kW) FLA
Hp kW FLA Stage 1 Stage 2 Total
CAELHEAT001A00
524A-B072-120
524A-C072-120
208-3-60
1.3† 0.97 7.6 5 3.8 3.8 10.4 22.5 25
2.4† 1.79 11.0 5 3.8 3.8 10.4 26.8 35
2.4 1.79 5.2 5 3.8 3.8 10.4 19.5 20
2.9 2.16 7.5 5 3.8 3.8 10.4 22.4 25
3.7 2.76 10.2 5 3.8 3.8 10.4 25.8 30
240-3-60
1.3† 0.97 7.6 5 5.0 5.0 12.0 24.5 25
2.4† 1.79 11.0 5 5.0 5.0 12.0 28.8 35
2.4 1.79 5.2 5 5.0 5.0 12.0 21.5 25
2.9 2.16 7.5 5 5.0 5.0 12.0 24.4 25
3.7 2.76 10.2 5 5.0 5.0 12.0 27.8 30
CAELHEAT002A00 480-3-60 2.4 1.79 2.6 5 5.0 5.0 6.00 10.8 15
2.9 2.16 3.4 5 5.0 5.0 6.00 11.8 15
3.7 2.76 4.8 5 5.0 5.0 6.00 13.5 15
CAELHEAT003A00 575-3-60 1.0 0.75 1.4 5 5.0 5.0 5.00 8.0 15
2.0 1.49 2.3 5 5.0 5.0 5.00 9.2 15
3.0 2.24 3.8 5 5.0 5.0 5.00 11.0 15
CAELHEAT004A00
208-3-60
1.3† 0.97 7.6 10 7.5 7.5 20.8 35.6 40
2.4† 1.79 11.0 10 7.5 7.5 20.8 39.8 40
2.4 1.79 5.2 10 7.5 7.5 20.8 32.6 35
2.9 2.16 7.5 10 7.5 7.5 20.8 35.4 40
3.7 2.76 10.2 10 7.5 7.5 20.8 38.8 40
240-3-60
1.3† 0.97 7.6 10 10.0 10.0 24.1 39.6 40
2.4† 1.79 11.0 10 10.0 10.0 24.1 43.8 50
2.4 1.79 5.2 10 10.0 10.0 24.1 36.6 40
2.9 2.16 7.5 10 10.0 10.0 24.1 39.4 40
3.7 2.76 10.2 10 10.0 10.0 24.1 42.8 50
CAELHEAT005A00 480-3-60 2.4 1.79 2.6 10 10.0 10.0 12.0 18.3 20
2.9 2.16 3.4 10 10.0 10.0 12.0 19.3 20
3.7 2.76 4.8 10 10.0 10.0 12.0 21.0 25
CAELHEAT006A00 575-3-60 1.0 0.75 1.4 10 10.0 10.0 10.0 14.3 15
2.0 1.49 2.3 10 10.0 10.0 10.0 15.4 20
3.0 2.24 3.8 10 10.0 10.0 10.0 17.3 20
CAELHEAT007A00
208-3-60
1.3† 0.97 7.6 15 11.3 11.3 31.3 48.6 50
2.4† 1.79 11.0 15 11.3 11.3 31.3 52.9 60
2.4 1.79 5.2 15 11.3 11.3 31.3 45.6 50
2.9 2.16 7.5 15 11.3 11.3 31.3 48.5 50
3.7 2.76 10.2 15 11.3 11.3 31.3 51.9 60
240-3-60
1.3† 0.97 7.6 15 15.0 15.0 36.1 54.6 60
2.4† 1.79 11.0 15 15.0 15.0 36.1 58.9 60
2.4 1.79 5.2 15 15.0 15.0 36.1 51.6 60
2.9 2.16 7.5 15 15.0 15.0 36.1 54.5 60
3.7 2.76 10.2 15 15.0 15.0 36.1 57.9 60
CAELHEAT008A00 480-3-60 2.4 1.79 2.6 15 15.0 15.0 18.0 25.8 30
2.9 2.16 3.4 15 15.0 15.0 18.0 26.8 30
3.7 2.76 4.8 15 15.0 15.0 18.0 28.6 30
CAELHEAT009A00 575-3-60 1.0 0.75 1.4 15 15.0 15.0 15.1 20.6 25
2.0 1.49 2.3 15 15.0 15.0 15.1 21.7 25
3.0 2.24 3.8 15 15.0 15.0 15.1 23.6 25
50TFQ004-012
524A072-300
75
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
LEGEND
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 =Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
HEATER PART NO. UNIT V-PH-Hz FAN MOTOR ELECTRIC HEATER(S)
MCA* MOCP*
Nominal
Capacity (kW)
Actual Capacity (kW) FLA
Hp kW FLA Stage 1 Stage 2 Total
CAELHEAT010A00
524A-B072-120
524A-C072-120
208-3-60
1.3† 0.97 7.6 25 11.3 7.5 18.8 52.1 74.7 80
2.4† 1.79 11.0 25 11.3 7.5 18.8 52.1 78.9 80
2.4 1.79 5.2 25 11.3 7.5 18.8 52.1 71.7 80
2.9 2.16 7.5 25 11.3 7.5 18.8 52.1 74.5 80
3.7 2.76 10.2 25 11.3 7.5 18.8 52.1 77.9 80
240-3-60
1.3† 0.97 7.6 25 15.0 10.0 25.0 60.1 84.7 90
2.4† 1.79 11.0 25 15.0 10.0 25.0 60.1 88.9 90
2.4 1.79 5.2 25 15.0 10.0 25.0 60.1 81.7 90
2.9 2.16 7.5 25 15.0 10.0 25.0 60.1 84.6 90
3.7 2.76 10.2 25 15.0 10.0 25.0 60.1 87.9 90
CAELHEAT011A00 480-3-60 2.4 1.79 2.6 25 15.0 10.0 25.0 30.1 40.8 50
2.9 2.16 3.4 25 15.0 10.0 25.0 30.1 41.8 50
3.7 2.76 4.8 25 15.0 10.0 25.0 30.1 43.6 50
CAELHEAT012A00 575-3-60 1.0 0.75 1.4 25 15.0 10.0 25.0 25.1 33.1 35
2.0 1.49 2.3 25 15.0 10.0 25.0 25.1 34.3 35
3.0 2.24 3.8 25 15.0 10.0 25.0 25.1 36.1 40
CAELHEAT013A00
208-3-60
2.4† 1.79 11.0 35 15.0 11.3 26.3 73.0 105.0 110
2.4 1.79 5.2 35 15.0 11.3 26.3 73.0 97.7 100
2.9 2.16 7.5 35 15.0 11.3 26.3 73.0 100.6 110
3.7 2.76 10.2 35 15.0 11.3 26.3 73.0 104.0 110
240-3-60
2.4† 1.79 11.0 35 20.0 15.0 35.0 84.2 119.0 125
2.4 1.79 5.2 35 20.0 15.0 35.0 84.2 111.7 125
2.9 2.16 7.5 35 20.0 15.0 35.0 84.2 114.6 125
3.7 2.76 10.2 35 20.0 15.0 35.0 84.2 118.0 125
CAELHEAT014A00 480-3-60 2.4 1.79 2.6 35 20.0 15.0 35.0 42.1 55.9 60
2.9 2.16 3.4 35 20.0 15.0 35.0 42.1 56.9 60
3.7 2.76 4.8 35 20.0 15.0 35.0 42.1 58.6 60
CAELHEAT015A00 575-3-60 2.0 1.49 2.3 35 20.0 15.0 35.0 35.1 46.8 50
3.0 2.24 3.8 35 20.0 15.0 35.0 35.1 48.7 50
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1 — — — — —
480 — — 0.694 0.84 0.918 1 — — —
575 — — ————0.91511.089
50TFQ004-012
524A072-300
76
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
See Legend and Notes on page 77.
HEATER PART NO. UNIT V-PH-Hz FAN MOTOR ELECTRIC HEATER(S)
MCA* MOCP*
Nominal
Capacity (kW)
Actual Capacity (kW) FLA
Hp kW FLA Stage 1 Stage 2 Total
CAELHEAT016A00
524A-B150-240
524A-C150-240
208-3-60
2.9 2.16 7.5 10 7.5 7.5 20.8 35.4 40
3.7 2.76 10.2 10 7.5 7.5 20.8 38.8 40
5.0 3.73 14.6 10 7.5 7.5 20.8 41.3 50
7.5 5.59 21.5 10 7.5 7.5 20.8 52.9 60
240-3-60
2.9 2.16 7.5 10 10.0 10.0 24.1 39.4 40
3.7 2.76 10.2 10 10.0 10.0 24.1 42.8 50
5.0 3.73 12.8 10 10.0 10.0 24.1 46.1 50
7.5 5.59 19.4 10 10.0 10.0 24.1 54.4 60
CAELHEAT017A00 480-3-60
2.9 2.16 3.4 10 10.0 10.0 12.0 19.3 20
3.7 2.76 4.8 10 10.0 10.0 12.0 21.0 25
5.0 3.73 6.4 10 10.0 10.0 12.0 23.0 25
7.5 5.59 9.7 10 10.0 10.0 12.0 27.2 30
CAELHEAT018A00 575-3-60 3.0 2.24 3.8 10 10.0 10.0 10.0 17.3 20
5.0 3.73 5.1 10 10.0 10.0 10.0 19.6 20
7.5 5.59 7.8 10 10.0 10.0 10.0 22.1 25
CAELHEAT019A00
208-3-60
2.9 2.16 7.5 20 14.9 14.9 41.5 51.2 70
3.7 2.76 10.2 20 14.9 14.9 41.5 64.6 70
5.0 3.73 14.6 20 14.9 14.9 41.5 70.1 80
7.5 5.59 21.5 20 14.9 14.9 41.5 78.7 80
240-3-60
2.9 2.16 7.5 20 19.9 19.9 47.9 69.2 70
3.7 2.76 10.2 20 19.9 19.9 47.9 72.6 80
5.0 3.73 12.8 20 19.9 19.9 47.9 75.8 80
7.5 5.59 19.4 20 19.9 19.9 47.9 84.1 80
CAELHEAT020A00 480-3-60
2.9 2.16 3.4 20 20.0 20.0 24.1 34.3 35
3.7 2.76 4.8 20 20.0 20.0 24.1 36.1 40
5.0 3.73 6.4 20 20.0 20.0 24.1 39.1 40
7.5 5.59 9.7 20 20.0 20.0 24.1 43.2 50
CAELHEAT021A00 575-3-60 3.0 2.24 3.8 20 20.0 20.0 20.1 29.9 30
5.0 3.73 5.1 20 20.0 20.0 20.1 31.5 35
7.5 5.59 7.8 20 20.0 20.0 20.1 34.9 35
CAELHEAT022A00
208-3-60
2.9 2.16 7.5 30 15.0 7.5 22.5 62.5 87.5 90
3.7 2.76 10.2 30 15.0 7.5 22.5 62.5 90.9 100
5.0 3.73 14.6 30 15.0 7.5 22.5 62.5 96.4 100
7.5 5.59 21.5 30 15.0 7.5 22.5 62.5 105.0 110
240-3-60
2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100
3.7 2.76 10.2 30 20.0 10.0 30.0 72.2 103.0 110
5.0 3.73 12.8 30 20.0 10.0 30.0 72.2 106.2 110
7.5 5.59 19.4 30 20.0 10.0 30.0 72.2 114.5 125
CAELHEAT023A00 480-3-60
2.9 2.16 3.4 30 20.0 10.0 30.0 36.1 49.4 50
3.7 2.76 4.8 30 20.0 10.0 30.0 36.1 51.1 60
5.0 3.73 6.4 30 20.0 10.0 30.0 36.1 53.1 60
7.5 5.59 9.7 30 20.0 10.0 30.0 36.1 57.2 60
CAELHEAT024A00 575-3-60 3.0 2.24 3.8 30 20.0 10.0 30.0 30.1 42.4 50
5.0 3.73 5.1 30 20.0 10.0 30.0 30.1 44.0 50
7.5 5.59 7.8 30 20.0 10.0 30.0 30.1 47.4 50
50TFQ004-012
524A072-300
77
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
LEGEND
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 =Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
HEATER PART NO. UNIT V-PH-Hz FAN MOTOR ELECTRIC HEATER(S)
MCA* MOCP*
Nominal
Capacity (kW)
Actual Capacity (kW) FLA
Hp kW FLA Stage 1 Stage 2 Total
CAELHEAT025A00
524A-B180,240
524A-C180,240
208-3-60 3.7 2.76 10.2 50 22.6 15.0 37.6 104.3 143.1 150
5.0 3.73 14.6 50 22.6 15.0 37.6 104.3 148.6 150
7.5 5.59 21.5 50 22.6 15.0 37.6 104.3 157.2 175
240-3-60 3.7 2.76 10.2 50 30.0 20.0 50.0 120.3 163.1 175
5.0 3.73 12.8 50 30.0 20.0 50.0 120.3 166.4 175
7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200
CAELHEAT026A00 480-3-60 3.7 2.76 4.8 50 30.0 20.0 50.0 60.1 81.2 90
5.0 3.73 6.4 50 30.0 20.0 50.0 60.1 83.2 90
7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90
CAELHEAT027A00 575-3-60 3.0 2.24 3.8 50 30.0 20.0 50.0 50.2 67.5 70
5.0 3.73 5.1 50 30.0 20.0 50.0 50.2 69.1 70
7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80
CAELHEAT028A00
524A-B300
524A-C300
208-3-60 7.5 5.59 19.8 20 14.9 14.9 41.5 78.7 80
10.0 7.46 28.2 20 14.9 14.9 41.5 87.1 100
240-3-60 7.5 5.59 19.4 20 19.9 19.9 47.9 81.4 90
10.0 7.46 26.8 20 19.9 19.9 47.9 93.3 110
CAELHEAT029A00 480-3-60 7.5 5.59 9.7 20 20.0 20.0 24.1 42.2 50
10.0 7.46 13.4 20 20.0 20.0 24.1 46.8 50
CAELHEAT030A00 575-3-60 7.5 5.59 7.8 20 20.0 20.0 20.1 34.9 35
10.0 7.46 10.3 20 20.0 20.0 20.1 38.0 40
CAELHEAT031A00
208-3-60 7.5 5.59 19.8 40 15.0 15.0 30.0 83.4 131.1 150
10.0 7.46 28.0 40 15.0 15.0 30.0 83.4 139.5 150
240-3-60 7.5 5.59 19.4 40 20.0 20.0 40.0 96.2 144.5 150
10.0 7.46 26.8 40 20.0 20.0 40.0 96.2 153.8 175
CAELHEAT032A00 480-3-60 7.5 5.59 9.7 40 20.0 20.0 40.0 47.9 71.9 80
10.0 7.46 13.4 40 20.0 20.0 40.0 47.9 76.6 80
CAELHEAT033A00 575-3-60 7.5 5.59 7.8 40 20.0 20.0 40.0 40.2 60.0 60
10.0 7.46 10.3 40 20.0 20.0 40.0 40.2 63.1 70
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCPMaximum Overcurrent Protection (Amps)
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1
480 0.694 0.84 0.918 1
575 — — — — — 0.915 1 1.089
50TFQ004-012
524A072-300
78
ELECTRICAL DATA (cont)
ELECTRIC HEATER DATA (cont)
LEGEND
*Values shown are for single-point connection of electric heat acces-
sory and air handler.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 =Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate fac-
tory-supplied motors.
6. Approximate shipping weight for CAELHEAT001A00-015A00 is
55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.
HEATER PART NO. UNIT V-PH-Hz FAN MOTOR ELECTRIC HEATER(S)
MCA* MOCP*
Nominal Capacity (kW) Actual Capacity (kW) FLA
Hp kWFLA Stage1Stage2Total
CAELHEAT034A00
524A-B300
524A-C300
208-3-60 7.5 5.59 19.8 50 22.6 15.0 37.6 104.3 157.2 175
10.0 7.46 28.0 50 22.6 15.0 37.6 104.3 165.6 175
240-3-60 7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200
10.0 7.46 26.8 50 30.0 20.0 50.0 120.3 183.9 200
CAELHEAT035A00 480-3-60 7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90
10.0 7.46 13.4 50 30.0 20.0 50.0 60.1 91.9 100
CAELHEAT036A00 575-3-60 7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80
10.0 7.46 10.3 50 30.0 20.0 50.0 50.2 75.6 80
CAELHEAT037A00
208-3-60 7.5 5.59 19.8 70 30.0 22.6 52.6 145.9 172.8 175
10.0 7.46 28.0 70 30.0 22.6 52.6 145.9 181.2 200
240-3-60 7.5 5.59 19.4 70 40.0 30.0 70.0 168.4 192.6 200
10.0 7.46 26.8 70 40.0 30.0 70.0 168.4 201.9 225
CAELHEAT038A00 480-3-60 7.5 5.59 9.7 70 40.0 30.0 70.0 84.2 96.3 100
10.0 7.46 13.4 70 40.0 30.0 70.0 84.2 100.9 110
CAELHEAT039A00 575-3-60 7.5 5.59 7.8 70 40.0 30.0 70.0 70.3 80.0 90
10.0 7.46 10.3 70 40.0 30.0 70.0 70.3 83.2 90
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1 — — — — —
480 — — 0.694 0.84 0.918 1 — — —
575 — — ————0.91511.089
50TFQ004-012
524A072-300
79
APPLICATION DATA — 524A
1. OPERATING LIMITS
Maximum fan speed — 524A-B,C072-240 . . . . . . . .1200 rpm
Maximum fan speed — 524A-B,C300 . . . 1100 rpm (18.3 r/s)
2. GENERAL — Select equipment to match or to be slightly
less than peak load. This provides better humidity control,
less unit cycling, and less part-load operation. Equipment
should be selected to perform at no less than 300 cfm/ton.
The air handler fan must always be operating when the con-
densing unit is operating.
Ductwork should be sized according to unit size, not build-
ing load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can
be used with slight reduction in external static pressure
capability.
FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA
*Danfoss part numbers shown.
†Sporlan Valve Co. part numbers shown.
NOTE:Hot gas bypass applications require field-supplied auxiliary side
connector.
FAN MOTOR DATA
STANDARD MOTOR
LEGEND
NEMA — National Electrical Manufacturers Association
UNIT COIL
TYPE
TXV
Qty...Part No.*
DISTRIBUTOR
Qty...Part No.†
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
NOZZLE
Qty...Part No.
524A-B,C 072 3, 4 Row 1...TDEBX8 1...1116 12...1/41...E5
524A-B,C 090 3, 4 Row 1...TDEBX8 1...1126 15...1/41...C6
524A-B,C 120 3, 4 Row 2...TDEX6 2...1115 9...1/42...E4
524A-B 150 3 Row 2...TDEBX8 2...1115 9...1/42...E5
524A-C 150 4 Row 2...TDEBX8 2...1115 12...3/16 2...E5
524A-B 180 3 Row 2...TDEBX8 2...1116 12...1/42...E6
524A-C 180 4 Row 2...TDEBX8 2...1126 16...1/42...C6
524A-B 240 3 Row 2...TDEBX11 2...1116 13...1/42...E8
524A-C 240 4 Row 2...TDEBX11 2...1126 18...3/16 2...C8
524A-B 300 3 Row 2...TDEBX11 2...1126 15...1/42...C10
524A-C 300 4 Row 2...TDEBX11 2...1126 20...3/16 2...C15
UNIT SIZE 524A 072 090 120 150 180 240 300
208/230-1-60
Speed (rpm) 1725 1725
Hp 1.3 2.4
Frame (NEMA) 56Y 56Y
ShaftDia(in.) 5/85/8——— —
208/230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1745 1745
Hp 2.4 2.4 2.4 2.9 3.7 5.0 7.5
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y S184T S213T
ShaftDia(in.) 5/85/85/87/87/811/813/8
575-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1745 1755
Hp 1.0 2.0 2.0 3.0 3.0 5.0 7.5
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 184T S213T
ShaftDia(in.) 5/87/87/87/87/811/813/8
50TFQ004-012
524A072-300
80
APPLICATION DATA — 524A (cont)
FAN MOTOR DATA (cont)
ALTERNATE MOTOR
LEGEND
NEMA — National Electrical Manufacturers Association
STANDARD DRIVE DATA
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
UNIT SIZE 524A 072 090 120 150 180 240 300
208/230-1-60
Speed (rpm) 1725 1725 — — —
Hp 2.42.4———
Frame (NEMA) 56Y 56Y — — —
ShaftDia(in.) 5/85/8———
230-3-60 and 460-3-60
Speed (rpm) 1725 1725 1725 1725 1725 1745 1745
Hp 2.9 2.9 3.7 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y Y56Y Y56Y S184T S213T S215T
ShaftDia(in.) 7/87/87/87/811/813/813/8
575-3-60
Speed (rpm) 1725 1725 1725 1745 1745 1755 1750
Hp 2.0 3.0 3.0 5.0 5.0 7.5 10.0
Frame (NEMA) 56HZ 56HZ 56HZ 184T 184T S213T D215T
ShaftDia(in.) 7/87/87/811/811/813/813/8
UNIT SIZE 524A 072 090 120 150 180 240 300
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 2.4-3.4 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 3.7-4.7 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.8 8.8 9.0 9.0 9.4 11.0
Pulley Bore (in.) 1111
7/16 17/16 17/16 115/16
Belt No. — Section 1—A 1—A 1—A 1—A 1—A 1—B 2—B*
Belt Pitch (in.) 40.3 41.3 42.3 42.3 42.3 41.8 (2) 42.8
(2) 43.8
FAN SPEEDS (rpm)
Factory Settings 568 647 764 632 632 771 752
Range 470-666 549-745 666-863 537-728 537-728 679-863 682-841
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100
Change per 1/2turn of
Moveable Motor Pulley
Flange
19.6 19.6 19.7 19.1 19.1 15.3 13.1
MAXFULL TURNS FROM
CLOSED POSITION 5555566
SHAFTS CENTER DISTANCE (in.) 10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.12-
10.99
6.67-
9.43
50TFQ004-012
524A072-300
81
APPLICATION DATA — 524A (cont)
MEDIUM-STATIC DRIVE DATA
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
HIGH-STATIC DRIVE DATA
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed is 837-1096 rpm.
†It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
**575-v unit has a center distance of 9.16-10.99.
UNIT SIZE 524A 072 090 120 150 180 240 300
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.0 8.0 8.2 8.6 9.4 9.4
Pulley Bore (in.) 1111
7/16 17/16 17/16 115/16
Belt No. — Section 1—A 1—A 1—A 1—A 1—B 2—B 2—B*
Belt Pitch (in.) 42.3 40.3 40.3 41.3 41.8 41.8 (2) 38.8
(2) 39.8
FAN SPEEDS (rpm)
Factory Setting 764 841 841 820 842 881 881
Range 666-863 733-949 733-949 715-926 742-943 798-984 798-984
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100
Change per 1/2Turn of
Moveable Motor Pulley
Flange
19.7 21.6 21.6 21.1 16.7 15.3 15.3
MAXFULL TURNS FROM
CLOSED POSITION 5555666
SHAFTS CENTER DISTANCE (in.) 10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32
9.16-
10.99
6.67-
9.43
UNIT SIZE 524A 072 090 120 150 180 240 300
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 7.0 6.0* 6.0 7.4 7.9 7.4 8.6
Pulley Bore (in.) 1111
7/16 17/16 17/16 115/16
Belt No. — Section 1—A 1—A 1—A 1—B 1—B 2—B 2—B
Belt Pitch (in.) 41.3 37.3 37.3 39.8 39.8 36.8 37.8
FAN SPEEDS (rpm)
Factory Setting 961 1121 1121 979 1060 1118 1024
Range 838-
1084
978-
1200*†
978-
1200†
873-
1096
950-
1171
1014-
1200†
873-
1075
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100
Change per 1/2Tu rn of
Moveable Motor Pulley
Flange
24.6 28.7 28.7 19.4 18.4 19.4 16.7
MAXFULL TURNS FROM
CLOSED POSITION 5556666
SHAFTS CENTER DISTANCE (in.) 10.44-
12.32
10.44-
12.32
10.44-
12.32
10.44-
12.32**
9.16-
10.99
8.16-
10.02
6.67-
9.43
50TFQ004-012
524A072-300
82
GUIDE SPECIFICATIONS — 524A
COMMERCIAL PACKAGED AIR-HANDLING UNIT
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 1,800 to 12,500 CFM, NOMINAL AIRFLOW 6 TO
25 TONS, NOMINAL COOLING
BRYANT MODEL NUMBERS: 524A-B (DIRECT-EXPANSION
COIL), 524A-C (HIGH-CAPACITY 4-ROW DIRECT-EXPANSION
COIL)
PART 1 — GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial
split systems. Unit shall have a multiposition design and
shall be capable of horizontal or vertical installation on a
floor or in a ceiling, with or without ductwork. (Only verti-
cal units are to be applied without ductwork.)
B. Unit with direct-expansion coil shall be used in a refriger-
ant circuit with a matching air-cooled condensing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigeration,
latest edition.
B. Unit shall be constructed in accordance with ETL and
ETL, Canada, standards and shall carry the ETL and
ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with NFPA-90A
requirements for flame spread and smoke generation.
Insulation shall contain an EPA-registered immobilized
antimicrobial agent to effectively resist the growth of
bacteria and fungi as proven by tests in accordance with
ASTM standards G21 and 22.
D. Unit shall be manufactured in a facility registered to the
ISO 9001:2000 manufacturing quality standard.
E. Direct-expansion coils shall be burst and leak tested at
435 psi.
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s
recommendations.
PART 2 — PRODUCTS
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configuration
or a vertical configuration. Unit shall consist of forward-
curved belt-driven centrifugal fan(s), motor and drive
assembly, prewired fan motor contactor, factory-installed
refrigerant metering devices (direct-expansion coil units),
cooling coil, 2-in. disposable air filters, and condensate
drain pans for vertical or horizontal configurations.
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 1/2-in.
fire-retardant material. Insulation shall contain an
EPA-registered immobilized antimicrobial agent to
effectively resist the growth of bacteria and fungi as
proven by tests in accordance with ASTM standards
G21 and 22.
3. Unit shall contain non-corroding condensate drain
pans for both vertical and horizontal applications.
Drain pans shall have connections on right and left
sides of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right or
left side of the unit to prevent standing water from
accumulating in pans.
4. Unit shall have factory-supplied 2-in. throwaway-type
filters installed upstream from the cooling coil. Filter
access shall be from either the right or left side of the
unit.
B. Coils:
Coils shall consist of 3 rows (524A-B) or 4 rows (524A-C)
of copper tubes with sine-wave aluminum fins bonded to
the tubes by mechanical expansion. Suction and liquid
line connections or supply and discharge connections
shall be made on the same side of the coil.
1. Direct-expansion coils shall feature factory-installed
thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be capable of external
adjustment. Coil tubing shall be internally rifled to
maximize heat transfer.
2. High-Capacity Coil:
The high-capacity 4-row coil consists of 4 rows of
3/8-in. copper tubes with sine-wave aluminum fins
bonded to the tubes by mechanical expansion. Coil
tubing shall be internally rifled to maximize heat
transfer. Suction and liquid line connections shall be
made on the same side of the coil. Direct-expansion
coils shall feature factory-installed thermostatic
expansion valves (TXVs) for refrigerant control. The
TXVs shall be capable of external adjustment.
C. Operating Characteristics:
Unit shall be capable of providing cfm airflow at an
external static pressure of in. wg.
D. Motor:
Fan motor of the size and electrical characteristics speci-
fied on the equipment schedule shall be factory supplied
and installed.
Motors rated at 1.3 through 3.7 hp shall have internal
thermal overload protection. Motors rated at 5, 71/2,and
10 hp shall be protected by a circuit breaker.
E. Special Features:
1. Alternate Motor and Drive:
An alternate motor and/or medium-static or high-
static drive shall be available to meet the airflow and
external static pressure requirements specified on
the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted with
an American Sterling Gray finish.
3. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes
and aluminum plate fins bonded to the tubes by
mechanical expansion. Coil shall be mounted in a
galvanized steel housing that shall be fastened to the
unit’s fan deck for blow-thru heating operation. Coil
shall have maximum working pressure of 150 psig.
4. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with
aluminum plate fins, and shall have inner steam dis-
tributing tubes. Coil shall be mounted in a galvanized
steel housing and shall be fastened to the unit’s fan
deck for blow-thru heating operation. Coil shall have
maximum working pressure of 20 psig at 260 F.
50TFQ004-012
524A072-300
83
GUIDE SPECIFICATIONS — 524A (cont)
5. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt, 3-phase,
60 Hz power supply shall be factory-supplied for field
installation as shown on the equipment drawings.
Electric heat assembly shall be ETL and ETL, Can-
ada, agency approved, and shall have single-point
power wiring. Heater assembly shall include contac-
tors with 24-v coils, power wiring, 24-v control wiring
terminal blocks, and a hinged access panel. Electric
heaters shall not be used with air discharge plenum.
6. Air Discharge Plenum:
Plenum shall be factory supplied to provide free-blow
air distribution for vertical floor-mounted units. A
grille with moveable vanes for horizontal or vertical
airflow adjustment shall be included. Plenum shall
be field-assembled and field-installed on the unit’s
fan deck for blow-thru air distribution. Plenum shall
notbeusedwithelectricheaters.
7. Return-Air Grille:
Grille shall be factory supplied for field installation on
the units return air opening.
8. Unit Subbase:
Subbase assembly shall be factory supplied for field
installation. Subbase shall elevate floor-mounted
vertical units to provide access for correct conden-
sate drain connection.
9. Economizer:
Economizer for ventilation or “free” cooling shall be
factory provided for field installation on either return
air opening of air handler. For free cooling applica-
tions, economizer shall be compatible with separate
thermostat; economizer dampers shall open when
outdoor air enthalpy is suitable for free cooling.
Economizer shall include enthalpy control and
damper actuator. Economizer shall be compatible
with accessory CO2sensor. Economizer damper
shall open when indoor CO2level rises above prede-
termined set point.
A 2 to 10 vdc actuator adapter must be field-supplied
and installed on economizer for demand control ven-
tilation using the CO2sensor accessory.
10. Thermostat Controls:
a. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capabil-
ity, and large LCD temperature display.
b. Commercial Electronic Non-programmable Ther-
mostat with auto-changeover, multi-stage capac-
ity, and large LCD display.
11. Overhead Suspension Package:
Package shall include necessary brackets to support
units in a horizontal ceiling installation.
12. Condensate Drain Trap:
Trap shall have transparent, serviceable design for
easy cleaning. Kit shall include overflow shutoff
switchandwiringharnessforconnectiontoanalarm
if desired.
13. UV-C Germicidal Lamps:
UV-C emitters and fixtures shall be specifically
designed for use inside an HVAC system. An ASME
nozzled test apparatus using a 45 F airstream mov-
ing at not less than 400 fpm shall measure individual
lamp output. Lamp output at 253.7 nm shall not be
less than 10µW/cm2per inch of arc length measured
at a distance of one meter.
a. UV-C power supplies shall be high efficiency,
electric type which are matched to the emitters
and are capable of producing the specified output
intensity with an input power no more than
80 watts.
b. Emitters and fixtures shall be installed in sufficient
quantity and arranged so as to provide an equal
distribution of UV-C energy on the coil and drain
fan.
c. The minimum UV-C energy striking the leading
edge of the coil fins shall be not less than
820 µW/cm2at the closest point and through
placement, not less than 60% of that value at the
farthest point. Equal amounts are to strike the
drain pan, either directly or indirectly through
reflection.
d. Emitters and fixtures shall be installed at right
angles to the conforming lines of the coil fins,
such that through incident angle reflection, UV-C
energy strikes all target surfaces of the coil, drain
pan, and the available line of sight airstream.
14. CO2Sensor:
The field-installed CO2ventilation sensor measures
the amount of ventilation needed by the space and a
proportional integral derivative loop (PID) calculation
makes adjustments to the economizer minimum
position during occupied operation. The indoor CO2
will be compared to an outdoor CO2reference before
making adjustments to the economizer minimum
position.
50TFQ004-012
524A072-300
Copyright 2004 Bryant Heating & Cooling Systems Printed in U.S.A. 7/04 Catalog No. 5256-904
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
INDEX
569D/F072-120, 576C120 11-32
566D/E150-240 33-60
524A072-300 61-83
Alternate motors and drives 5, 73, 80, 81
Application data
569D/F072-120, 576C120 27
566D/E150-240 54-56
524A072-300 79-81
ARI capacity ratings 3
CO2sensor 83
Combination ratings
566D150-240/524A 40-44
566E150-240/524A 45-52
569D072-120/524A 16-21
569F120/524A 24, 25
576C/524A 22, 23
Condenser coil grille 4
Condensing unit ratings 15, 39
Controls 8
Convenience outlet 4
Dimensions
Base unit
569D/F072-120, 576C120 13, 14
566D/E150-240 36-38
524A072-300 63-65
Discharge plenum 5, 6
Dura-Shield options 4
E-coated coils 4
Economizer 5, 6
Electrical data
569D/F072-120, 576C120 26
566D/E150-240 53
524A072-300 72-78
Electric heat 5, 74-78
Fan performance tables
524A072-300 66-69
Features/Benefits 1, 2
Gage panel 4
Guide specifications
569D072-120, 576C120 29, 30
569F120 31, 32
566D/E150-240 59, 60
524A072-300 82, 83
Hail guard 4
Hot water coil 5, 6, 71
Hydronic heat 71
Indoor-air quality (IAQ) 1
Liquid line piping 27, 55
Low ambient controls 4
Maximum temperature 27, 54
Minimum ambient operating
temperature 27, 54
Minimum temperature 27, 54
Model number nomenclature
569D/E072-120, 576C120 11
566D/E150-240 33
524A072-300 61
Motormaster® options 4
Operating sequence 8
Options and accessories 4-6
569D/F, 576C, 566D/E 4
524A 5, 6
Performance data
569D/F072-120, 576C120 15-25
566D/F150-240 39-52
524A072-300 66-71
Physical data
569D/F072-120, 576C120 12
566D/E150-240 34, 35
524A072-300 62
Piping and wiring
569D072-120, 576C120 28
566D150-240 57, 58
Refrigerant charge 27
Refrigerant piping 27, 54, 55
Return-air grille 5, 6
Selection procedure 7
Sound data 3
Static pressure drop
Filter 70
Economizer 70
Heating coil 70
Plenum 70
Steam coil 5, 6, 71
Subbase 5, 6
Thermostat 4, 5
Thermostatic expansion
valve (TXV) 79
Unloader package 4
Unit-mounted non-fused disconnect 4
UV-C germicidal lamps 5
Wiring 9, 10