Burnham Pf 3 Series Installation And Operation Manual
2015-06-08
: Burnham Burnham-Pf-3-Series-Installation-And-Operation-Manual-738091 burnham-pf-3-series-installation-and-operation-manual-738091 burnham pdf
Open the PDF directly: View PDF
.
Page Count: 16
| Download | |
| Open PDF In Browser | View PDF |
INSTALLATION AND OPERATING INSTRUCTIONS FOR PF-3 FORCED DRAFT BOILER - BURNER UNITS SECTION I - GENERAL INFORMATION - Page 3 SECTION I1 - INSTALLATION INSTRUCTIONS - Page 4 SECTION I11 - OPERATING AND SERVICE INSTRUCTIONS - Page 13 NOTE : For optimum performance and serviceability from this unit adhere to the following recommendations: \ 1-Clean Flueways a t least once a year-preferably a t the end of heating season to remove soot and scale. Inside of Firebox should also be cleaned a t the same time. 2-Have Oil Burner and Controls checked a t least once a year o r as may be necessitated. 3-Retain your contractor o r a competent serviceman to assure that the unit is properly adjusted and main,tained. IMPORTANT: BEFORE STARTING TO INSTALL THIS OIL HEATING UNIT, READ THESE INSTRUCTIONS CAREFULLY. KEEP INSTRUCTIONS NEAR OIL HEATING UNIT FOR REFERENCE BY OWNER AND SERVICEMAN. F o r service and repairs to the heating plant, call your Heating Contractor. provide series and size designation shown on rating plate. Boiler Number When seeking information on the boiler, Type Firing Type System Heating Contractor Address - .- --Phone BURNHAM CORPORATION HYDRONICS DIVISION Laneaster, Pennsylvania 17604 Wrm No. 62008E-1/81-1200f No ,- -. FRONT VlEW FLUSH JACKET MODEL 'URN 1 A /3" \ SUPPLY 1 LE LF 8" DIA. VENT VENT SIZE DIAM. 1 DRAIN VALVE PANEL --- REMOVABLE / 1 SIDE VlEW EXTENDED JACKET 8" / 8" K.O. OPENING, Figure 1 Dimensional Data NO. OF SECTIONS 4 $ X 18 L-LF ---d REAR VIEh' % -1 TAPPING BELOW WATER LINE ON STEAM BOILERS - 3411 UTILITY DAMPER SECTION THRU BOILER WITH FLUSH JACKET DRAIN VALVE 2 vzrl ALTERNATE RETURN DAMPER POSITIONIN BRACKET &k r FLUE OUTLET SECTION I GENERAL INFORMATION I N S P E C T SHIPMENT carefully for any signs of dam@ PROVIDE CLEARANCE of a t least on the right side and back of the unit f o r cleaning of flues. Proage. All equipment is carefully masufactured, inspected 24" and packed by experienced workmen. Our responsibility ceases upon delivery of boiler to the carrier in good condition. Any claims f o r damage in shipment must be filed immediately against the carrier by the consignee. No claims for variances from, o r shortage in orders, will be allowed by the manufacturer, unless presented within sixty (60) days a f t e r receipt of goods. vide a minimum of 20" clearance in front f o r servicing of equipment, 30" if boiler is equipped with jacket extension. If boiler is equipped with tanldess heater, additional allowance may have to be made for installation and servicing of heater, see table below: a LOCATE BOILER so that smoke pipe connection to chimney is short and direct. Floor construction should have adequate load bearing characteristics to bear the weight of the boiler filled with water. See table below. ASSEMBLED SECTION WEIGHT (LBS.) BOILER N 0. WATER CONTENT FULL (LBS.) HEATER CLEARANCE INCHES HEATER N 0. TOTAL WEIGHT (LBS.) 226 23 232 29 445 35 Table "B" P F-34 800 276 1076 Distances a r e measured from front of flush jacket. P F-35 1000 335 1335 P F-36 1200 402 1602 @ CHIMNEY OR VENT. The P F - 3 series boiler is designed for forced-draft firing and may be used with a P F-37 1400 465 1865 conventional natural d r a f t stack o r a stub vent (see Figure 3 ) . See Fig. 1 for the proper vent size. Draft controls a r e not normally required, although they may be used on installations where a natural d r a f t stack is used or on multiple boiler installations with a common stack. The boiler is provided with a breeching damper which should be secured in the open position unless high breeching d r a f t makes burner adjustment difficult. Table "A" A boiler foundation similar to the one shown in Figure 2 is recommended if the boiler room floor is not Perfectly level, weak, uneven o r if a water condition exists. If t h e boiler is s e t on a combustible floor, a 1" thick layer of foil-faced insulation or equivalent should be placed beneath the boiler foil side up. rl 44. @ AIR FOR COMBUSTION AND VENTILATION must be provided. If natural ventilation is inadequate, provide a screened opening from the boiler room to the outside, which is based on one square inch free afea per 3000 btuh input. If other a i r consuming appliances are near the boiler the a i r inlet should be larger. Consult respective manufacturers. 50. 114 X 4 STEEL PLATE / Figure 2 - SUGGESTED BOILER FOUNDATION 3 Figure 3 - ARRANGEMENT FOR STUB VENT SECTION I1 INSTALLATION INSTRUCTIONS a ket to the lower nipple port in Front Section using Place boiler assembly on foundation provided. Shim if necessary. The tie rod nuts should then be loosened until finger tight. 3/8" Hex Hd. Cap Screws and Flat Washers (if furnished). Snug all screws before final tightening. b. Attach the Tapped Heater Cover Plate with Rubber Gasket to the upper nipple port in Front Section using 3/8" Hex Hd. Cap Screws and Flat Washers (if furnished). Snug all screws before final tighting. "INSTALLATION OF BUILT-IN HEATERS AND HEATER OPENING COVER PLATES" @ INSTALLATION OF BUILT-IN DOMESTIC WATER HEATER if furnished. a. Slip Rubber Gasket over Heater Coil and place against Heater Mounting Plate so that holes in Gasket are in line with holes in Heater Mounting Plate. b. Install Built-in Heater Coil through openihg in Front Section into the upper nipple port for water boilers or the lower nipple port for steam boilers. (See Fig. 4). c. Secure the Heater Mounting Plate with 3 / 8 Hex Head Cap Screws and Flat Washers (if furnished). Snug all screws before final tightening. d. Attach the Tapped Heater Cover Plate with Rubber Gasket to the remaining opening in the Front Section. Secure with 3/8" Hex Hd. Cap Screws and Flat Washers (if furnished). Snug all screws before tightening. @ TEST BOILER FOR LEAKS before installing controls, trim, and jacket, and before connecting to heating system. a. Install Pressure Gauge ( a t least 30 P.S.I. capacity), a hose to the City Water and a valve in one of the supply tappings. Plug remainder of tappings. b. Fill Boiler with water and apply a pressure of a t least 10 pounds but no more than 50 pounds gauge pressure. c. Examine Boiler carefully inside and outside for leaks or damage due to shipment or handling. DRAIN WATER FROM BOILER. Remove gauge, valve and plugs from those tappings to be used. Leave other tappings plugged or bushed according to Figure 4. @ INSTALLMENT O F HEATER OPENING COVER PLATES if Built-in Domestic Water Heater is not fur- @ INSPECT JOINTS BETWEEN SECTIONS. All joints are factory sealed. If there are any spaces due to nished. (Steam and Water Boilers). See Figure l. a. Attach Blank Heater Cover Plate with Rubber Gas- LOCATION ON BOILER A SIZE (INCHES) shipment or handling, seal them with silastic sealant. WATER 'ONTRoL 1 SAFETY RELIEF USED Iml LlMlT CONTROL OR COMBINATION HlGH LlMlT AND CIRCULATOR CONTROL (FOR INSTALLATIONS WITHOUT TANKLESS WATER H E A T E R ) 1 1 COMBINATION HlGH LIMIT, LOW LlMlT AND CIRCULATOR CONTROL (FOR INSTALLATIONS WITH TANKLESS HEATER) COMBINATION PRESSURE AND TEMPERATURE GAUGE D I 1 AUXILIARY LlMlT CONTROL (WHEN NEEDED-TEQUIRES ADDITIONAL TAPPED HEATER OPENING COVER P ~ O TANKLESS HEATER) BUSH TO 1/4" - PRESSURETROL- OR OPTIONAL CONTROLS WATER HEATER (OPTIONAL)= d (11/2 1/2 NOT USED H 3/4 AUXILIARY TAPPING ,3' SUPPLY STEAM PRESSURE GAUGE U IN BACK SECTION T 1nw OR9UI V U k E r n w ~ A m w s ~ w NOT USED F G A STEAM BOILER GAUGE GLASS AND LOW WATER CUT-OFF - - AUXILIARY TAPPING-BELOW NORMAL WATER LINE I Fig. 4 4 WATER BOILER (1) INSTALL CAST IRON CLEANOUT COVERS to x 2%'' long bolts provided. The bolts the boiler with should be anchored to the slots in the cleanout openings of the sections with the head of the bolt and a washer inside and a washer and n u t outside. See Figure 5. The covers a r e placed on the bolts.and secured with washers and nuts. CLEANOUT x" COVER 7 r COVER GASKET INSULATION CLEANOUT NUT AND WASHER WASHERS TOP VIEW CLEANOUT COVER ASSEMBLY '@ Fig. 5 F L U E COLLAR should be assembled next. Clean the ground surface on the flue collar and the mating ground surface on the back section with a wire brush. Then using a cartridge of silastic sealant provided, apply a smooth 1/4" diameter bead of sealant to the ground surface on the back section. Place the collar on the back section and position the damper bracket on the collar as, shown in Figure 1. Secure the collar with the 5/16" bolts provided. @ INSTALL BURNER PLATE a s follows: @) CONNECT SUPPLY AND RETURN P I P I N G TO HEATING SYSTEM. NOTE-If jacket extension (special order only) is to be installed now or in the future, return piping connected to front section must pass thru opening provided in extension, see Fig. 1. In addition, fittings used to connect circulator in this return (water boiler) must be selected so t h a t circulator does not extend beyond sides of flush jacket. a. If boiler is equipped with tankless heater, hot and cold water lines must be routed thru opening provided in Jacket Extension Top Panel. Refer to FIG. 18 f o r Tankless Heater Piping. b. All Piping must be installed so a s to provide clearance f o r running the Smokepipe a s direct a s possible between the Boiler and Chimney. c. With Forced Circulation HOT WATER HEATING, consult I-B-R Installation and Piping Guide No. 200. N O T E : When Hot Water Heating Boilers are connected to Heating Coils located in Air Handling Units where they may be exposed to refrigerated a i r circulation, the Boiler Piping System must be equipped with Flow Control Valve or other automatic means to prevent gravity circulation of the Boiler Water during Cooling Cycle. d. With STEAM HEATING, see Figures 7 and 8. Consult I-B-R Piping Guide No. 200. e. With COMBINATION HEATING AND COOLING (REFRIGERATION) SYSTEMS having the same Distributing Units, Piping and Circulator, see Figure 6. NOTE: Valves must be installed in each Supply and Return Branch to the Heating Boiler and Water Chiller so a s to prevent circulation of Chilled Water through the Boiler o r Heated Water through the Chiller. Hm ARE CLOSED IN WINTER AND OPEN IN SUMMER ARE OPEN IN WINTER AND CLOSED IN SUMMER n I WATER I c CHILLER - I rSHUT- SHUT- OFF OFF VALVE Clean the ground surface on the burner plate and the mating surface on the front section with a wire brush. Then using a cartridge of sealant provided, apply a smooth diameter bead of sealant to the ground surface of the front section. Secure the burner plate to the f r o n t section with the 5 / 1 6 x 1" long bolts provided. Draw-up the bolts until the burner plate makes contact with the front section. HEATING A s" SUPPLY MAIN TO COMBINED HEATING 8 COOLING SYSTEM I d [AIR I f" '1 BOILER CUSHION TANK I , , .;;;;; RETURN MAIN CIRCULATOR FROM COMBlNECl H F A T I NM G - I3 COOLING RECOMMENDED PIPING FOR COMBINATION HEATING 8 COOLING IREFRIGERATION) SYSTEMS IMPORTANT-THIS BOILER DOES NOT REQUIRE A COMBUSTION CHAMBER OR SEPARATE SMOKEHOOD. Fig. 6 STEAM SUPPLY MAIN -SLOPE DOWN FROM HIGH POINT ABOVE BOILER AN0 DRIP ENDS OF MCllNS INTO WET RETURN LOW POINT OF SUPPLY MAIN TO BE NOT LESS THAN 2 9 ' ABOVE WATER LlNE PIPE DISCHARGE TO DRAIN CLOSE KEEP STEAM BOILERS FILLED T O NORMAL WATER LlNE 1 W 2" 4" - . OR SHOULOER NIPPLE L PREFERRED HARTFORO RETURN CONNECTION ' GRAVITY RETURN GRAVITY RETURN PUMP RETURN STEAM - WET RETURN PITCH DOWN TO BOILER Fig. 7 Minimum P i p i n g Recommendations 4 and 5 Section Steam B o i l e r s 4" SUPPLY MAIN TO B E TAKEN WADER VERTICALLY OR AT 45' 4" HEADER -24. MIN. ABOVE WATERLINE PREFERRED - HARTFORD RETURN CLOSE OR SHOULDER NIPPLE KEEP STEAM BOILERS FILLED TO NORMAL WATER LlNE 2" 4. OFF TOP ANGLE. + PREFERRED HARTFORD RETURN CONNECTION - GRAVITY RETURN GRAVITY RETURN PUMP RETURN STEAM - W E T RETURN PITCH DOWN TO BOILER PROVIDE DRAIN COCKS FOR FLUSHING BOILER AND SYSTEM Fig. 8 Minimum P i p i n g Recommendations 6 and 7 Section Steam B o i l e r s 6 OF @ @. I D FRONT PANEL FILLER PIECE @) PANEL 1 RlGHT HAND '% LUWtK PANEL UPPER RlGHT HAND ATTACH RATING PLATE HERE USING S.M.S. TOP PANEL Fig. 9 FLUSH JACKET ASSEMBLY 3 ' @ INSTALL UPPER RlGHT HAND SlDE PANEL BY SLIDING DOWN UNTIL BOTTOM FLANGE IS FULLY SEATED BEHIND LOWER RlGHT HAND SlDE PANEL. ATTACH TO FLANGES ON FRONT AND REAR PANELS WITH S.M.S. LEAVING UPPER FRONT HOLE VOlD UNTIL INSTALLATION OF TOP PANEL. REAR PANEL IN POSITION AND ATTACH LEFT AND LOWER RlGHT HAND SlDE PANELS TO FLANGES ON REAR PANEL WlTH S.M.S. @ PLACE @ FLANGE ASSEMBLE LOWER RIGHT HAND SlDE PANEL ON FRONT PANEL WITH S.M.S. REAR PANEL S-. INSTALL TOP PANEL WlTH FLANGES POSITIONED OUTSIDE REAR AND SlDE PANELS. SECURE WlTH S.M.S. -----k? INSTALL FRONT PANEL FILLER PIECE BELOW BURNER PLATE POSITIONING BEHIND FLANGE. PLACE FRONT PANEL IN POSITION BY SLIDING DOWN BEHIND BURNER PLATE FLANGE. ASSEMBLE TO FRONT PANEL FILLER & PIECE WITH S.M.S. WATER PLATE USING S.M.S. @IATTACH LOWEST @ASSEMBLE LEFT HAND SIDE PANEL TO FLANGE ON FRONT PANEL WITH S.M.S. LEAVING UPPER HOLE VOlD UNTIL INSTALLATION OF TOP PANEL. I" BLOCKS UNDER REAR OF SlDE PANELS WILL FACILITATE ASSEMBLY. NECESSARY KNOCKOUTS. DO NOT TIGHTEN ANY S.M.S. UNTIL ALL PANELS HAVE BEEN INSTALLED. @ REMOVE INSTALL FLUSH JACKET in accordance with Fig. 9. Refer to Figure 4 for knockouts to be removed. @) @ INSTALLATION O F TRIM AND CONTROLS FOR WATER BOILERS. (See Figure 4 for Control Locations.) a. Screw COMBINATION ALTITUDE GAUGE AND THERMOMETER into %" tapping. Tighten by wrench applied to square shank back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may destroy calibration of gauge. b. R E L I E F VALVE-Install in 1" Tapping next to 3" Supply Tapping in Front Section using fittings provided. CAUTION : Safety Relief Valve should be piped to and open drain-full size of discharge outlet on Relief Valve and without any provision of "shut-off" between the Relief Valve and discharge into drain. c. Install Hydronic Controls in their designated tappings. @ INSTALLATION O F TRIM AND FOR STEAM BOILERS. (See Figure CONTROLS 4 for control locations.) a. Screw Combination Pressure Vacuum Gauge into designated $" tapping. Tighten by wrench applied to square shank on back of gauge. Do not apply pressure on gauge case since this may destroy calibration of gauge. b. SAFETY VALVE. Install in 1" Tapping next to 3" Supply Tapping in Front Section. CAUTION: Safety Valve should be piped to a n open drain-full size of discharge outlet on Safety Valve and without any provision of "shut-off" between the Safety Valve and discharge into drain. c. Install Pressure Limit Control with 1/4" Pig Tail Syphon into Heater Cover Plate Tapping bushed 3/4" to G". d. Install Operating Control (supplied with Tankless Heater equipped boilers only) in designated tapping. e. Install Gauge Glass and Low Water Cut-off (if furnished) in y2" tappings on left side of Front Section. @) INSTALL SMOKEPIPE so t h a t connection to Chimney or vent is short and direct. a. Install in accordance with LOCAL F I R E ORINANCES. b. Smokepipe must not be smaller than the 8" dia. flue collar. See Fig. 1. For Stub Vent installation see Fig. 3, if connected to chimney. c. Do not connect into same leg of Chimney serving an open fireplace. d. Inspect Chimney for obstructions o r restrictions which should be removed. Clean Chimney if necessary. e. Smokepipe should slope upward from Boiler to Chimney not less than one inch in four feet. Smokepipe must be securely supported so a s to maintain, proper clearances from combustible materials and to prevent separation of joints. f. Insert Smokepipe into but not beyond inside wall of Chimney Flue Lining. Pipe should be installed above the extreme bottom of Chimney so as to prevent stoppage. y. Seal between Smokepipe and Chimney connection to prevent draft leakage. . 0 INSTALL ROOM THERMOSTAT on an inside wall about four feet above floor. Never install Thermos t a t on an outside wail or where i t will be influenced by drafts, hot or cold water pipes, lighting fixtures, television, rays of the sun, or near a fireplace. Keep large furniture away from Thermostat so there will be free movement of room a i r around this Control. @ OIL BURNER INSTALLATION. Bolt burner to mounting plate with nuts and washers packed in boiler parts carton. R E F E R TO BURNER INSTALLATION and SERVICE MANUAL form No. 52004. @) BOILER with JACKET EXTENSION refer to Figure 10 for assembly instructions. h INSTALL ELECTRIC WIRING in accordance with NATIONAL ELECTRICAL CODE and Local Regulations. a. A separate ELECTRICAL CIRCUIT should be run from Meter with a Fused Disconnect Switch in this Circuit. See Figures 11 thru 17 for appropriate wiring diagram. I \ BOTTOM FRONT TIE THE BOTTOM FRONT TIE PANEL TO THE EXTENSION SIDE PANELS WITH THE FOUR LONG SHEET METAL SCREWS. @ ASSEMBLE TO INSTALL THE FRONT DOOR 'PANEL ,ENGAGE THE BOTTOM FLANGE FIRST, FULLY SEAT THE TOP OF PANEL WHILE HOLDING DOWN THE DOOR LATCH AND RELEASE LATCH TO SECURE PANEL IN POSITION. PANEL THE EXTENSION TOP PANEL IN POSITION WlTH THE FLANGES EXTENDING DOWN OVER THE EXTENSION SlDE PANELS. SECURE WlTH THE SIX SHORT S.M.S. @ PLACE Fig. 10 THE TWO EXTENSION SlDE PANELS WlTH THE NOTCHED EDGE INSERTED BETWEEN THE FLUSH JACKET SlDE AND FRONT PANELS. TIGHTEN SCREWS TO HOLD PANELS IN PLACE. @ ASSEMBLE FLUSH JACKET - Jacket Extension Assembly 8 RIGHT HAND SlDE PANEL ALL FLUSH JACKET SCREWS ATTACHING SlDE PANELS TO THE FRONT PANEL MUST BE LOOSENED. LOW WATER CUTOFF HOT LlNE NEUTRAL n HONEYWELL PA 4 0 4 A PRESSURE L I M I T CONTROL = 1 ' E$go'S:D I 0 - V I I ?o TFOI. ; W- SWITCH THERMOSTAT O - FO HONEYWELL R 8 1 8 4 PRIMARY CONTROL ', 1 I,(/I .,-...a,.-. ... IMC U t L A T IGNITIONTRANSFORMER VALVE Fig. 11 O I L BURNER SEQUENCE OF OPERATION When the thermostat calls for heat, i t energizes the cad cell protectorelay, bringing on the burner. The burner will operate until the thermostat is satisfied or the limit setting on ,the high limit is reached. When the high limit control restores the circuit on a drop in pressure, the burner will start if the thermostat is still calling for heat. The low water cut-off will stop the burner if the water level in the boiler drops too low. On burner start, if the cad cell does not see flame within approximately 45 seconds, protectorelay will lock out on safety and must be reset before burner can be restarted. No. 1 Wiring Diagram for Steam Boilers Less Heater LOW WATER CUTOFF HONEYWELL PA 4 0 4 A PRESSURE L I M I T CONTROL b THERMOSTAT - Q ? HOT LlNE NEUTRAL - I 0 - E~~oS
Source Exif Data:File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 16 Has XFA : No XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:d6b2e9c4-6eef-4c7d-a96b-187051432d92 Producer : Adobe Acrobat 6.0 Paper Capture Plug-in Create Date : 2004:08:06 14:55:33-04:00 Creator Tool : Adobe Acrobat 6.0 Modify Date : 2004:08:09 15:52:38-04:00 Metadata Date : 2004:08:09 15:52:38-04:00 Document ID : uuid:e8357301-04c2-442d-8bf3-a11654d4315b Format : application/pdf Creator : Adobe Acrobat 6.0EXIF Metadata provided by EXIF.tools