CARRIER Ventilator Manual L0211027
User Manual: CARRIER CARRIER Ventilator Manual CARRIER Ventilator Owner's Manual, CARRIER Ventilator installation guides
Open the PDF directly: View PDF
.
Page Count: 24
| Download | |
| Open PDF In Browser | View PDF |
HRVCCLHU, HRVCCSVU, HRVCCLVU Heat Recovery Ventilator HEATING & COOLING Visil www.camer.com Installation, Start-Up, and Operating Instructions Sizes 1150, 1200, 1250, and 1330 NOTE: Read installation. the entire instruction manual before starting Index the Page SAFETY CONSIDERATIONS INTRODUCTION LOCATION ..................................................... UNIT INSTALLATION ............................................................. Mount Unit ................................................................................ Locate COMPONENT WALL .............................................. Exterior Hoods ........................................ DESCRIPTION .................................................... CONTROL Location Basic ..................................................................... 2 3 3 Control Operation Control Automatic 5 Operation 6 ................................................... 6 7 7-8 ......................................................................... 7 12-vdc Wiring ........................................................................... ACCESSORIES .......................................................................... 8 8-9 Interlock Relay .......................................................................... 20 Minute Timer ....................................................................... 8 8 60 Minute BALANCING Adjustable Timer .................................................... HRV ................................................................ Balancing Dampers ................................................................. Flow Collars ...................................................................... VENTILATION EVALUATION ........................................... 8 lO-I 1 10 10-11 12-13 Method i ................................................................................. 13 Method 2 ................................................................................. 13 CONTROL BOARD OPERATION ............................................ Board Function ........................................................................ Defrost ..................................................................................... Off and Intermittent/Off 13 13 Low-Speed Air Exchange ....................................................... CARE AND MAINTENANCE .............................................. 13 13-14 Door ......................................................................................... Filter ........................................................................................ 13 14 Blower Motor and Wheel ....................................................... Cleaning'the Core ................................................................... 14 14 TROUBLESHOOTING .......................................................... 14 Control Board .......................................................................... 14 Blower Motor .......................................................................... 14 Blower Speed Selection .......................................................... Defrost ................................................................................ Module Manufacturer _2 a Jumpers ........................................................ reserves PC 101 the right to discontinue, Catalog NO. 03HR-VC3 Compact Unit \j 14-17 Wall Control ............................................................................ Control Fig. 2--HRVCCSVU 13 ...................................................... Air Exchange A92268 13 13 Mode ............................................... High-Speed Conventional Unit 7 Humidity Selector ..................................................................... ELECTRICAL CONNECTIONS ............................................... Wiring Fig. 1--HRVCCLHU 6 ...................................................... Wiring ........................................................................................ 115-vac A99271 6-7 ........................................................... Operation Control 3 3-4 4-6 ................................................................................. Standard 20-22 2-3 2 Drain ...................................................................... and Install .............................................. 2 2 Forced-Air Application ............................................................. Connect Ducts to HRV ............................................................. Condensate DRAWINGS 2 Inspect Equipment .................................................................... Select Location .......................................................................... Application DIMENSIONAL 16-17 18-19 2 .................................................................................... System Signaling .................................................................. DIAGRAMS ........................................................... 2 .......................................................................... Independent Error WIRING A92377 Fig. 3_HRVCCLVU High Efficiency Unit 14 14-16 16 or change at any time, specifications Printed in U.S.A. Form or designs HRV-2SI without notice and without Pg 1 5-00 incurring obligations. Replaces: HRV-1SI SAFETY CONSIDERATIONS UNIT INSTALLATION Installation and servicing of this equipment can be hazardous due to mechanical and electrical components. Only trained and qualified personnel should install, repair, or service this equipment. Do not install HRV in a corrosive or contaminated sphere. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed bytrained service personnel. When working on this equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. Step The 1--Mount HRV springs. Unit can be suspended Attach atmo- from metal hanging Fig. 4.1 Unit should always floor joists bracket using chains and 4 to all 4 sides of cabinet. be installed (See as level ,as possible. Follow all safety codes. Installation must be in compliance with local and national building codes. Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls. Recognize safety information. This is the safety-alert symbol Z_x• When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. INTRODUCTION A92269 Fig. 4---Chain Spring Installation The Heat Recovery Ventilator (HRV) is used to exchange indoor stale air with outside fresh air. The HRV unit is equipped with a special heat recovery core which transfers sensible heat between the fresh incoming air and stale exhaust air. Step It is recommended, but not required to locate the HRV in a conditioned space. Special attention should be given to condensate drain, duct application, balancing HRV, and locating unit for easy access and routine maintenance. 2_lndependent System In the absence layout, the HRV can be applied of a forced-Mr unit. To ensure both fresh-air, throughout comfort, Application system and a typical as an independent this type of application and remm-air duct system or stand alone involves running registers (or stale-Mr pickup registers) the home. The cross-flow design core allows entering and leaving Mr streams to transfer heat energy without mixing. (See Fig. 15, and 18 through 25.) LOCATION Step l_lnspect Equipment Fresh-Mr living Move carton to final installation location. Remove HRV from carton taking care not to damage unit. Remove all packaging and inspect unit for damage. Remove parts bag from inside unit. File claim with shipping company if shipment is damaged or incomplete. Check to make sure HRV unit matches Fig. 1 through 3 and 7 through 9. Step 2-_Select Location The HRV should be located in a conditioned proximity to a fused power source. for routine maintenance. If HRV is installed be located installed located independent It should of a forcod-air near the center of the air distribution in conjunction with a forced-air next to (or close to) the indoor space and in close be easily accessible system, unit should system. system, are normally and basement. located in bedrooms, It is recommended dining room, that registers be placed 6 to 12 in. from the ceiling on an interior wall and airflow directed toward ceiling. If registers are floor installed, airflow should be directed toward the wail. Retxu_-air (or stale-Mr pickup draw from kitchen, bathroom, stale-Mr can exist. registers) are normally located to basement, or other rooms where Proper size and type of registers drop. The velocity 400 ft/minute. of airflow Maximum of duct according If HRV is unit should registers room, listed be equipment. 2 length to the highest in unit Product must be used to minimize through register for the speed system should should of the unit. Refer Data Digest for ventilation pressure not be above be designed to specifications capacities. Step 3--Forced-Air or existing Step 6_Locate Application Most HRV applications will be installed forced-air system. To in conjunction operate properly, the fresh-air stale air from installations, operate furnace inside of building. whenever Interlock relay designed kit Part to interlock HRV is energized. (See Fig. 7.) For these or fan coil blower continuously HRV No. HRV must be interlocked with indoor R and G circuit equipment The fresh air from HRV connection fresh-air should be direct. to mix before Step 4JConnect blower. inside of furnace kit is introduced at a point no less than 6 ft upstream Ducts and _ent, furnace insulated flex- HRV and exterior exhaust must be separated must be positioned exhaust, driveway, intake must be positioned outlet wail. at least by at least 10 ft from nearest g_s meter, or oil fill pipe. as far as possible from garbage containers and potential chemical fumes. When possible, it is advised to locate the intake and exhaust hoods on same side of When house for located on interior corners intake and exhaust hoods additional into return-air of furnace indoor air intake and stale-air dryer between or fan coil will or building. 12 in. above duct After or fan coil. This (See Fig. 7.) This is to allow entering Fresh Fresh-air is available energize. See Fig. 13 and interlock relay information and Installation Instructions. NOTE: and Hoods problems, on both fresh air inlet and exhaust-air connecting intake Exterior condensation ducts 6 ft. Fresh-air is energized. KVAACOI01F1R To prevent ible ducts are required supply and stale-air return from HRV connect directly to return-air duct system. This is how the HRV distributes fresh air and removes and Install IMPORTANT: with new hood equipment. anticipated selecting through incoming hoods must be 18 in. from hood wall. tube into duct. and exhaust or in dead air pockets. snow proper exterior tube and insert To HRV The intake Tape never be ground and at lea,st level. locations pass flexible assembly should (See Fig. 7. ) Both make appropriate duct through duct vapor barrier size hole hole and insert tightly around hood back into wall and fasten securely. FLEXIBLE \ DUCT I // Insulated flexible exhaust-alr duct outlet using insulated flexible must very be taped reduce pressure proper manner When connecting is required ducts tight drop, the HRV applied use approximately and stale=air supply to system from Balancing and fresh ducts in the HRVCCLHU units. units Step 5--Condensate To connect 1. Insert washer be eliminate transmission balancing in stale air exhaust to the HRVCCSVU dampers HRV are provided section). drain, grommets proceed into as follows: bottom of unit using the gasket and nut. (see Fig. 6). 3. Join the connector tubing, about 12" long and attach two short sections of play, tic and the main tube as shown. 4. Make a loop in the tubing below to prevent system. duct from duct should when cormecting be installed (see balancing 2. Cut two sections of plastic them to each drain. 5. Connect Duct Fit-Up duct system. connecting The Fig. 5--Flexible Drain condensate sleeved should before A98382 are ports for using metal the metal to main TO insulated duct at HRV This should unit dampers air intake and the HRVCCLVU trap duct system, When work, DUCTS CONNECTING RETURN-AIR DUCT SYSTEM when metal or rigid ducts return. duct duct system. of noise or vibration To it in a \_ (See Fig. 5.) This can act as a silencer ducts to return-air RETURN ducLs problems. support STALE-AIR airflow. 18-in. of flexible supply, and When of the flexible duct and to a return-air fresh-air inlet wail. condensation flex However, fresh-air NOTE: the to avoid reduced duct can be used. barrier to prevent stretch fresh-air to exterior duct, the vapor flexible insulated. on both connecting sewer g;xses tubing to the "T" connector from entering the the "T" to create a A99268 ventilation Fig. _---_ondensate (See Fig. 6.1 unit slope from drain to building's main drain. Provide slight unit for run-off. 3 Drain With Loop Trap 6 FEET FURNACE 6IN. 6IN. HRV DUCT CONNECTING FRESH AIR & EXHAUST TO OUTSIDE NOTE: SUPPLY & EXHAUST DUCTSTO HAVE BALANCING DAMPERS (ON COLD SIDES) (SEE STEP 4-CONNECT DUCTS TO HRV) REAR INLET HOOD 6 FEET EXHAUST HOOD 18 IN. NOTE: ALL DUCT WORK TO BE FIELD SUPPLIED. A99265 Fig. 7--Exhaust Ventilation A99283 Fig. 8_HRVCCLHU Conventional Horizontal Unit Cy A98408 Fig. 9---HRVCCSVU COMPONENT Compact DESCRIPTION The following listed items are components of HRVCCLHU. Fig. 8) I. Stale air return from building connected system. Fig. 10---HRVCCLVU High-Efficiency Unit (See to return-air duct Compact Unit The following listed items are components and HRVCCLVU. (See Fig. 9 and 10) I. Stale air return from building connected system. 2. Fresh air intake connected of HRVCCSVU to return-air duct to outdoor air inlet hood. 2. Fresh air intake connected to outdoor air inlet hood. 3. Exhaust air connected 3. Exhaust air connected to outdoor air exhaust hood. 4. Dampers are used to control air exchange with outdoor air during defrost mode. 4. Mechanical filters trap dust contained in the air. 5. Heat recovery core is either a cross-flow type for compact models+ or a counter-flow type for high efficiency models. The core transfers heat between the 2 air streams. 6. Blowers bring in fresh air from outside and exhaust stale air to outside. 7. Electronic control circuit ensures proper unit operation. 8. Fresh air supply from HRV connected to return air duct of forced air system. 9. Terminal connector block for wiring wall and timer controls. 10. Electrical cord connects to standard I 15-v outlet. 5. Mechanical to outdoor air exhaust hood. filters trap dust contained in the air. 6. Heat recovery core is either a cross-flow type for compact models, or a counter-flow type for high efficiency models. The core transfe_ heat between the 2 air streams. 7. Blowers bring in fresh air from outside and exhaust stale air to ouLside. 8. Capacitor required 9. Condensation for motor operation. tray collects condensate from heat recovery core. I0. Drainage tubes connects to sleeved grommets 1 I. Electronic control circuit ensures proper unit operation. 12. Fresh air supply from HRV connected to return air duct of forced air system. 13. Terminal connector 14. Electrical cord block for wiring wall and timer controls. connects to standard 115-v outlet. WALL CONTROL Step 4_Automatic Step 1---Location The HRV wall controls are unique to HRV and must be installed for proper unit operation. Three wall control options are available: NOTE: This control is designed to be used primarily with installations which are independent of a forced air system (models HRVCCSVU and HRVCCLVU only). I. Basic Control 2. Standard Control 1. Initially the switch is off. All LEDs are off and HRV is inoperative. 3. Automatic Control Step 2IBasic Control Operation 2. First push of mode button puts HRV into intermittent mode. The HRV operates at high speed when there is a call for dehumidification. Intermittent and exchange LEDs are illuminated. When dehumidistat is satisfied, HRV shuts down and exchange LED goes out. The b_sic control contains a 3 position slide switch which is used to manually select OFF, LOW. and HIGH speed blower operation. The unit operates continuously when LOW or HIGH is selected. tSee Table 1.) Step 3iStandard Control Operation 3. Next push of mode button puts system in continuous mode. Continuous and exchange LEDs remain on. The HRV operates at high-speed blower during calls for dehumidification and low speed when dehumidistat is satisfied. The standard control contains an adjustable dehumidistat, and a 3 position slide switch which is used to manually select between OFF. LOW, and INTERMFIq_NT modes. There are 2 LEDs on the control to indicate operating mode. (See Table 2.) This control offers 2 modes of operation: I. With switch off, HRV is inoperative (See Fig. 14.) Control Operation This control contains an adjustable dehumidistat and push button switch to cycle between 3 modes of operation. There are 5 LEDs to indicate mode of operation. (See Table 3.) 4. Next push of mode button puts system in circulation mode. HRV operates in high speed at all times. Circulation LED remains on. When there is a call for dehumidification, exchange LED is on and HRV exchanges air with outside. When dehumidistat is satisfied, HRV dampers close which recirculates indoor air. The exchange LED goes off. and both LEDs are out. 2. With switch on LOW, HRV continuously exchanges air with outside. If dehumidistat is satisfied, blower will run in low speed, otherwise, blower will run on high speed. Both LEDs are illuminated all the time. 5. The maintenance light illuminates every 3 months to indicate filter should be cleaned. It is reset by opening the door to the HRV. 3. With switch on INTERMIq'I'ENT, the HRV exchanges air with outside on high-speed blower, and unit shuts down when dehumidistat is satisfied. The ON LED is illuminated all the time, and AIR EXCHANGE LED is illuminated only when unit is running. This mode is ideal for maintaining proper humidity, levels when no one is home. NOTE: The standard and automatic controls sense humidity not temperature. Either control must be located in an area where it will continually monitor fresh air circulating within the home. Install HRV wall control as close as possible to main system thermostat and follow same guidelines as installing a thermostat, (locate approximately 5 ft. [60 in.] above floor, mount on an inside partitioning wall, ete). 6 Table 1--Basic MODE Control DAMPER POSITION FAN SPEED Off OPERATION Off Closed TO Outside Off Low Air Exchange With Outside Open To Outside Low High Air Exchange With Outside Open TO Outside High Table 2_tandard MODE DEHUMIDISTAT Off POSITION Call for dehumidification Satisfied Intermittent Call for dehumidification DEHUMIDISTAT Off Intermittent Continuous Recirculation ON LED AIR EXCHANGE LED Closed to outside Off Off Off Open to outside Low On Off Open to outside High On On DAMPER POSITION Off Off Air exchange with outside Air exchange with outside Closed to outside Off On Off Air Exchange with Outside Open to outside High On On Table 3_Automatic MODE FAN SPEED OPERATION Any Satisfied Low Control POSITION OPERATION Control DAMPER POSITION INDICATOR LEDS FAN SPEED Any off Closed to Outside Off OFF Satisfied Air exchange with outside Open to outside Off Intermittent ON Call for dehumidification Air exchange with outside Open to outside Air exchange with outside Open to outside High Low Intermittent and Exchange ON Satisfied Call for dehumidification Open to outside Closed to outside High Satisfied Air exchange with outside Recirculation High Continuous and Exchange ON Recirculation ON Call for dehumidification Air exchange with outside Open to outside High Recitculation and Exchange ON Any Any Any Maintenance (open door) Any Table OUTSIDE 4--Recommended TEMPERATURE Humidity Continuous and Exchange ON Levels DOUBLE-PANE WINDOWS TRIPLE-PANE WINDOWS 65 percent 50 = F 10° C 55 percent 32 ° F 0° C 45 percent 55 percent 14 ° F -10 ° C 35 percent 45 percent -4 ° F -20 ° C 30 percent 45 percent -22 ° F -30 ° C 25 percent 35 percent If the level of humidity falls too low in the winter months while operating in the continuous exchange mode, a humidifier may be integrated into the system. Intermittent exchange mode may also be selected for short peedds of time to increase the level of humidity. Step 5---Wiring Remove top cover assembly wire through wall. Connect between code. wall control wall control on back Y, R, G, and and B (yellow, HRV NOTE: HRV wall control humidity circuit and circuit Table selector Thks control where is not indoor to and black) Following color assembly. operate dehumidistat on 12vdc. humidity humidity to control levels designed to in the house during the condensation problems in to be confused months ELECTRICAL Step 1--115-vac board. board is a built-in the summer 4 recommends green Selector upper northern regions the winter season. used during humidity. before attaching red, top cover properly control the level of humidity winter months. This control helps avoid NOTE: and pass thermostat of control (See Fig. I l and 12.) Replace Step 6--Humidity The from hole located to avoid is a problem during with a dehumidistat RED high GREEN relative indoor condensation. CONNECTIONS BLACK _..,,=__..__ ELLOW Wiring The HRV operates on 115vat, It comes with a power cord attached to unit and ready to plug into a fused outlet. Unit must be grounded for proper operation. A98383 Fig. 11--Typical Wall Control WALL CONTROL Iooo ] o CONTROL o A98410 Fig. 12---Control Step 2--20 Minute Timer All electrical connections must comply with National and Local Electrical Codes, or other ordinances that might apply. A push button timer can be used to override the wall control and put the HRV into high speed for 20 minutes. Connect switches in parallel and connect leads to HRV terminals 1, OC, and OL. (gee Fig. 14.) Push button locations are ideal in special activity areas, such as, bathrooms or kitchen, where high-speed exhaust operation is needed for a short period of time. l'y_[R'_lyi[0]_l Do not use an extension cord as a power source for operating the HRV. Step 2--12-vdc Wiring NOTE: The 20 minute timer will not function properly unless HRV wall control is applied and working correctly. Timing function is internal to electronic circuit board, it is activated by a momentary contact between OC and OL. The 1 connection is to illuminate the push button. The maximum number of push button timers that can be applied is 5. The HRV circuit board, wall control, and accessories operate on 12vdc. See Wall Control section, item Wiring and Fig. l I and 12 for more information. ACCESSORIES Step l_nterlock Connections Relay Step 3--60 The interlock relay kit, Part No. KVAAC0101FIR is required when installing HRV into a forced-air heating and cooling system. (See Fig. 13.) For additional information, refer to Installation Iustructions supplied with interlock relay kit. Minute Adjustable Timer A 60 minute adjustable timer can also be used to override wall control and put HRV into high-speed operation for a select amount of time. Connect timer in parallel with push button timers, or to HRV terminals OC and OL. (See Fig. 14.) The purpose of interlock relay kit is to energize indoor system equipment (furnace or fan coil) blower whenever HRV is calling. If HRV is energized, and indoor system equipment is not, interlock relay will energize and make R and G at indoor equipment. This will insure fresh air distribution throughout the building via the central duct system. The 60 minute timer will provide a minimum of 30 minutes, and a maximum of 80 minutes of ventilation at high speed. When adjustable timer expires, an additional 20 minutes will remain as a result of the internal timer of HRV electronic circuit board. 8 9-PIN THERMOSTAT TERMINALS i HN61KK04' _ ONLY i _ i _ i i; ........ '.. 115V FIELD _ I _ .............. SUPPLIEDAUXILIARY II _ FUSED J-BOX • RELAY t vI 125V =. __ , "LTWO I FURNACE 24V TERMINAL HONEYWELLI DUTY .,l,II ..... I r_ ....... ,1 _. L__ DISCONNECT NOTE: Connect Y-terminal as shown for proper operation. PILOT Ii...... ",----GNO/ ",--,_GND, , _ PLUG I TWO-WIRE__ HEATING AMP : i I UNIT CONDENSING WIRE BLOCK A92460 Fig. 13_lnterlock Relay Wiring Layout J3 ELECTRONIC CONI_OL eO_RO -- : TH E WIRES FROM 33dE SWITCH 90 YELLOW 80 70 60 BLACK RED - INDICATOR - COMMON. - SWITCH, ` (J3-3) (J34} (J3.5) OL ,sO I oc40 i 30-- / / .... I_l..... J1 I I I I I I I I '_ ..... - __lill- _- Q®® RED BLACK - YELLOW ) [] ®®® ®®® ) (OPTIONAt._ 60 MINUTE _ TIMER (OPTIONAL) BUTTON SWITCHES PUSH (5 SWITCHES MAXIMUM) © (oc) BLACK - (J3-4) COMMON TERMINAL S13RIp __ _RED o (i)- (J3-3) YELLOW INDICATOR TERMINAL STRIP - (J3-5) SWITCH TERMINAL STRIP (OL) BACK OF PUSH eUTTON SWITCH A98386 Fig. 1C--Push Button Timer Wiring Layout 9 TEMPORARY BALANCING BALANCING DAMPER / _lll i LOW " DAMPER COLLAR STALE AIR TO OUTSIDe- FROM OUTSinE f FRESH AIR SUPPLY _ TO BUILDING IIII [ \ _ I _/' FROM BU'L° NG _ STALE AIR RETURN A99266 Fig. 15--Balancing HRVCCLHU FRESHAIR FROMOUTSIDE STALE AIR TO OUTSIDE °°F'°W FRESH AIR FROM OUTSIDE STALE AIR TO OUTSIDE --12" (300turn) (30Omrn) 30" (760turn) _B_A_N 2" CIN G DAMPER DAMPER TEMPORARY -- FLOW COLLAR TEMPORARY FLOW COLLAR- TEMPORARY FRONT-_ FRONT_ RIGHT SIDE VIEW RIGHT SIDE VIEW A98425 Fig, 16_Balancing BALANCING HRVCCSVU and HRVCCLVU HRV range top exhausts, dryer exhaust, fume hoods, bath or roof fans should be in operation. The forced-air furnace (if used for circulation) should be operating in continuous fan mode for normal operating speed. Balancing intake and exhaust airflow is very important for proper system operation and optimum performance when applying an HRV. Unit balancing prevents a positive and/or negative pressure within the home. Balancing the HRV is done by applying temporary flow collars and permanent balancing dampers to the fresh air intake and stale air exhaust ducts. (See Fig. 15 and 16.) Airflow is determined by connecting a magnehelic gage to the temporary flow collar. (See Fig. 17.) Both flow collars and magnehelic gage are included in the accessory start-up balancing kit. If supply-air house, from outside an imbalance can is greater result over than exhaust-air pressurizing the from Step Balancing Dampers dampers (some times called butterfly dampers) are provided with the HRVCCLHU. The dampers for the HRVCCSVU and HRVCCLVU are field supplied and should be permanently between located HRV modification the home. 1--Balancing balancing If these may dampers dampers in fresh-air and exterior be intake wall. required while to ensure located is strongly and stale-air exhaust (See Fig. 15 and 16) Some proper in flexible recommended duct. after installation Insulating balancing ducts field of over is com- exhanst-air backdraft, is greater than supply-air, combustion appliances may bringing exhaust fumes into the house. A balanced plete to prevent condensation condition will satisfied Step 2_low Collar customers, and avoid and fire- Flow Collars are temporary, and should be installed as close to HRV as possible and in straightest sections of duct to ensure accuracy. (See Fig. 15.1 If only I flow collar is available, install Before place ensure proceeding flues should optimum expensive performance, with balancing, be tightly provide callbacks. closed. all windows, No exhaust doors, systems such as 10 problems. collar in stale-air duct of HRV, coil,u- in the fresh-air available, to balance speed at maximum air exchange flow collar Next, and properly speed occurring (high-speed with nature to a magnehelic exhaust of system gage. is higher is same. If reading obtain same static pressure Once HRV air first, it is typically and ductwork. reading (See than exhaust is lower, reading. reading, and connect Fig. hoses 17.) The the lowest Next, measure gage If needle pressure due to fresh air. If fresh air adjust damper until reading return to exhaust damper and adjust You can use label on flow collar A98400 to Fig. 17--Magnehelic is balanced and dampers use tape or drive screws moving. Remove be repeated flow collars to ensure are adjusted to prevent NOTE: The flow collar directional arrow !on flow collar1 must be oriented in the airflow direction of unit. and secure unit is balanced ducts. blades This from NOTE: Some field modification may be required to ensure proper temporary installation of flow collar during balancing when insulated flexible duct is used. procedure properly. FRESH AIR FROM OUTSIDE 0°C STALE AIR TO OUTSIDE 6oc i-_-_ to equalize damper _._-_,/' Gage to convert into airflow. airflow, should are adjust operation) outside, must be leveled and zeroed before use to read accurately. falls below zero, reverse hose connections. Measure install If 2 flow collars unit. control continuous from airflow. airflow. it will be much easier to read airflow dampers With and record duct and record FRESH AIR FROM OUTSIDE 0oc 32°F TO OUTSIDE 2oc 36°F STALE AIR _ 32°F EROMBUILDLNG 22oc 2OF TALE AIR > FRESH AIR TO BUILDING 16°C 61°F STALE AIR FROM BUILDING 22°C 72°F FRESHAIR TO BUILDING 20°C 68°F A98403 Fig. 18---HRVCCLHU and HRVCCSVU Cross Flow STALE AIR TO OUTS_E ,=o. FRESH AIR TO BUILDING A98404 Fig. 19---HRVCCLVU • .o.. FRESH AIR FROM OUTSIDE b""" STALE AIR FROM BUILDING Counterflow E " ERE STALE AIR FROM BUILDING TO BUILDING A99269 A99270 Fig. 20--HRVCCLHU Airflow During Air Exchange Fig. 21 --HRVCCLHU Airflow During Defrost 11 FRESH AIR FRESH AIR FROM OUTSIDE FILTERED AIR TO BUILDING TO BUILDING STALE AIR BUILDING STALE AIR FROM BUILDING STALE AIR TO OUTSIDE A92383 A92382 Fig. 23---HRVCCSVU Airflow During Recirculation and Defrost Fig. 22_HRVCCSVU Airflow During Air Exchange FRESH AIR TO BUILDING FILTERED A_R TO BUILDING STALE AIR FROM BUILDING STALE AIR FROM BUILDING STALE AIR FROM OUTSIDE "5 A92385 A92384 Fig. 24---HRVCCLVU Airflow During Air Exchange VENTILATION Fig. 25--HRVCCLVU Recirculation EVALUATION The ventilation capacity of an HRV unit while at maximum speed is defined according to greatest total airflow required. These methods are derived from the Canadian National Building Code 1995 version and the CSA F326.1 revision. DO NOT use HRV during construction of a house or when sanding drywall. This type of dust may damage system. When ventilation requirement is determined, use Product Sheets to reference unit airflow delivery and performance. Airflow During and Defrost The following 2 methods can be used to evaluate the approximate ventilation needs of a house. Accuracy of calculations are dependent upon the information available and knowing critical measuremenU; of the structure. (See Fig. 26.) Data 12 WASHROOM #1 MASTER BEDROOM WASH* W_'_ #3 BEDROOM KITCHEN IJ'UN DARY LIVING ROOM #6 I #5 BEDROOM BEDROOM #4 DINING ROOM #11 FAMILY ROOM #10 I 1320 sq ft (125 sq m) 1320 sq ft (125 sq m) BASEMENT t320 sq ft (125 sq m) A98388 Fig. 26_Floor Method Plan Example 1 Step :)--OFF To calculate approximate ventilation: NOTE: 11 rooms The X 10 CFM master bedroom first part of this equation, Method + 2 X 20 CFM and basement but figured = 150 CFM. Step 4_High-Speed are not included in at second approximate Referencing same example. When high-speed air exchange occurs, KI and K2 relays are energized and K5 relay is de-energized. This opens low-speed contacts, and closes high-speed contacts on K2 relay. This also opens contacts on K5 relay which opens outside air damper. Then, 115vac is applied between orange and gray wires on Molex plug (pins 1 and 6) and blower motor runs in high-speed operation. Also. l l5vac is applied across pins 5 and 7, this energizes interlock relay. (See Logic Diagram in Fig. 27 and 28.) part of equation. ventilation: (See Fig. 26.) Total cuft = total. X 0.3 per hr Take total and divide Air Exchange in 2 To calculate by 60 to get CFM. Example: Step 5---Low-Speed Air Exchange 1320 st] ft X 8 ft in height = 10560 cuft per floor 10560 cu ft X 3 floors = 31680 total cuft in house When 31680 which closes the contacts. K2 and I<5 relays keeps closed cuft X 0.3 air change 9500 cuft Conclusion: airflow 1--Board board encounter on Fig. 27 and 28 under set and do not require is replaced. unusual they are located Step shown are factory control size unit. blower OPERATION start-up properly. If control operation, exchange contacts opens Red and Gray occurs, Jumper is replaced, check jumpers KI Relay air wires on Molex contacts damper. plug operation. is energized are de-energized. and high-speed outdoor motor runs in low-speed jumpmatch 120vac (pins Also, This open on is applied 1 and 4) and 115vae is applied interlock relay. (See Logic CARE AND MAINTENANCE Table. any changes board and air across pins 5 and 7, this energizes Diagram in Fig. 27 and 28.) Function setup low-speed between To ensure proper operation of HRV, configuration located on electronic control board and must configuration Jumpers BOARD low-speed K2 relay, is 160 CFM. This range of a HRVCCLHU1150 CONTROL NOTE: ers are cuft + 60 minimum per hr = 160 CFM The total amount of airflow needed falls within Step per hr = 9500 Mode When HRV is Off, KI relay is open, and K5 relay is energized which closes outside air damper. (See Logic Diagram in Fig. 27 and 28.1 The sum of rooms X 10 CFM per room, plus 20 CFM for a master bedroom or basement. Example: and INTERMITTENT/OFF unless or you to make sure (See Fig. 27 and 28.) 2--Defrost The HRV continually monitors the outside air temperature. If the ouLside air is at or below 23°F(-5°C), the HRV will initiate a defrost cycle warm indoor approximately by closing air through every the outside the heat hr with air damper recovery 5 minute and re-circulating core. defrost This cycle. happens During this process, core is defrosted without the use of electric strip heat. At 5°F(-15°C), unit will defrost for 5 minutes every half hr. At Step -22°F(-30°C), the unit will minutes with a 5 minute cycle. a control logic explanation. sense a need to defrost See the Troubleshooting 1--Door every 20 HRV door can be removed section for then slide door to the right and remove it from be in place operation. 13 and secured by unlatching shut for proper brief case style latches, hinges. Door must Step 3---Blower Motor Step 2--Filter Filters in months. HRV Use are washable a vacuum accumulated dust, and cleaner then wash should to remove in lukewarm completely dry before reinstalling. excessive strain on blower motor. filter. Vacuum out debris. In addition, regularly and exhaust hoods check when be cleaned heaviest water. every, portion Allow The HRV blower motor operates on 115vac, with 2-speed operation. 3 of filter to The easiest way to check blower speed operation is to use the wall control and initiate a low-speed blower and high-speed blower operation. A dirty air filter will cause Never operate unit without a and clean screens on exterior NOTE: If there is a short circuit or an open circuit at thermistor, CPU will go into a 5 minute defrost cycle every 20 minutes. This feature is not there on older board versions with 3pin jumpers. intake necessary. Override Test V!_[,TLI1Fff,]21 DO NOT clean filters with a heating appliance Step 3---Blower HRV blower beatings Motor motors is not accumulated in a dishwasher or permanent and dirt and damage HIGH SPEED lubricated for life. Lubricating However, grease will result. Wheel are factory recommended. To use override test function, a thermistor must be connected to the control board. Unit must not be in defrost mode during an override test. and DO NOT dry them from inspect blower and clean motor and I. Disconnect HRV from llSvac. any 2. Unplug wall control wires at control module terminal block inside HRV. wheel annually. Step 4_Cleaning The HRV unit is equipped handled with care. following the maximum efficiency Allow heat 3. Plug HRV back to ll5vac. Core with special heat recovery We recommend season of most of the plastic recovery core that it be washed intense This within once a year will Rinse under heavy and strong will damage stream 5. Push in door switch, this will initiate a high-speed exchange. ensure the core. to soak for 3 hr in a solution water and mild soap. detergent use. partitions 4. Attach a wire across J3-8 and J3-9 (B and G) on control module terminal block. core and must be LOW SPEED of warm 1. Unplug HRV from 115vac. of water. Hot water core and should 2. Disconnect wall control block inside HRV. NOT be used. TROUBLESHOOTING Before installing power to system. switch. Electrical or servicing There shock may system, can cause turn off main than personal 4. Connect a 3.9 Kohm resistor between J3-8 and J3-9 (B and G) on control module terminal block. 5. Push in door switch, this will initiate a low-speed exchange. l disconnect injury or death. Step 4_Blower Although special care has been taken to minimize shalp edges in the construction of your unit, be extremely careful when handling parts or reaching into unit. Table 5 Troubleshooting To change low speed to medium speed, proceed msfollows: Chart I. Unplug unit from 115vac. This can be a quick guide in resolving unit problems. It is also recommended to review and understand Wall Control Board Operation and Care and Maintenance sections before continuing. There are 3 main parts to focus on when troubleshooting HRV unit: 2. Locate blower assembly. 3. Locate red wire and blue wire coming from blower assembly. 4. Unplug red wire from quick connect. 5. Unplug protecting cap quick connection from blue wire and put on red wire coming from blower. The cap is a safety insulator. 1. Wail control 2. Electronic control board 3. Blower motor Step 1--Wall 6. Connect red wire of main harness to blue wire. Control 7. Replace wires. Typically the wall control is either good, or it is bad. Use Table 1, 2, or 3 to determine if wall control is operating correctly. Use Fig. 12 to check control wire connections. NOTE: The electronic 12vdc. Step 2_ontrol Speed Selection Three-speed blowers are factory connected to electronic control board on HIGH- and LOW-speed taps of blowers. Installer can easily change low-speed tap to medium-speed tap so electronic control will select between high and medium speed. Connections can be changed at motor location. (See Tables 7 and 8.) V!_["7_'XljII[O]='i NOTE: Reference module terminal 3. Plug HRV back to ll5vac. always be more wires at control Step 5--Defrost Defrost cycle is controlled by a thermistor which is located in the fresh-air intake passage (the thermistor unit is connected to J4 of control module. See Fig. 27 and 28). When defrost temperature _nsor detects the need for defrost, K5 relay will close for 6 minutes while KI and K2 remain energized. control board and wall control operate on Board Electronic control board must have wall control attached before unit will function properly. Also, configuration jumpers located on control board must match configuration setup shown on Fig. 28 under Jumper Table. In addition, outside air thermistor must be connected to control board for it to operate properly. See Table 6, Temperature -vs- Ohm Chart, for valid temperature range. This closes the outdoor air damper while running HRV blower on high-speed. This process recirculates warm indoor air through heat recovery core which melts any frost that has formed. Water created in this process is collected by HRV and drained away. Frequency of the defrost cycle depends on outdoor temperature (see Table 10). 14 Table 5_Troubleshooting Chart SYMPTOMS CAUSES SOLUTIONS Air too humid Continuous exchange mode used in small houses Use Intermittent Mode Check humidity level settings Defrost condition is in effect Outdoor temperatue is below 23°F Unit will operate when not in defrost mode. Defrost cycle is based on outdoor ambient (see Table 10) Broken controlwire Test wall control Check connectior_s Check thermistor Unit not responding to wall control Unit stops momentarily Air from distribution register Unit makes annoying too cold noise Improper calibration Ventilation Noise level too high at distribution registers when in high speed Table 6_Temperature/Ohrn TEMPF ° Check units circuit breaker Electncal supply interrupted Check calibration of flow rates of air flow Remove the motor and screw wheel on propedy wheel out of adjustment install a duct silencer Air duCt system too short Table 7--Factory Relationship Set Blower Connection LOW Speed OHMS HIGH or 30 34,480 32 32,630 34 30,760 J1-6 Orange Orange 36 29,220 No Connection 38 27,470 J1-4 NO Connection Red Blue + Cap Red 40 26,020 42 24,680 44 23,320 46 22,070 48 20,910 CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE 50 19,830 Jl_ Orange Orange 52 18,820 J1-4 Red Blue High Medium 54 17,870 No Connection NO Connection Red + Cap Low 56 16,920 58 16,160 60 15,260 62 14,530 64 13,790 66 13,090 68 12,480 70 11,860 72 11,270 74 10.750 76 10,250 CONTROL MODULE MAIN ELECTRICAL HARNESS CABLE BLOWER WIRE SPEED High Me_um Low Table 8--Modify Blower Connection HIGH or MEDIUM Speed Table 9_Temperature TEMPERATURE °F (oc) SPEED and Voltage VOLTAGE DC -22 (-30) VOLTS (J4) 3.5 -4 (-20) 2.7 8 (-16) 2.3 14 (-10) 2.0 32 (O) 1.4 41 (5) 1.1 50 (10) 0.9 68 (20) 0.6 78 9,750 80 9,300 62 8,840 84 8,432 86 8,042 88 7,668 90 7,310 Safety Feature 92 6,993 94 6,661 96 6,368 This new control has an added safety feature. If microprocessor does not detect the thermistor or detects a short circuit, unit will automatically go into a 6 minute defrost cycle every 20 minutes. 98 6,085 100 5,811 102 5,571 , 104 5,313 106 5,088 108 4,869 110 4,660 112 4,450 114 4,268 116 4,019 118 120 3,918 3,750 If defrost is not working properly, check for proper damper operation. To do this, turn unit to OFF position. Damper should close. DEFROST CHECK 1. Make sure defrost cable is properly connected into J4. 2. Make sure thermistor assembly is correct. Measure thermistor temperature reading with muhimeter. Select multimeter DC measurement scale 0-20v. At connector J4 (without removing thermistor cable), measure voltage between pins of thermistor cable. Depending on temperature of outside air intake, values should correspond with those in Table 9. If reading is not correct (reading llv for short circuit or 5v for open circuit), change thermistor assembly. 3. If thermistor is good, do a RESET and ,see if defrost works. If defrost still does not work, change circuit board. 15 Table 10---Defrost Cycle OUTSIDE TEMPERATURE No Defrost Above 23°F 4°F to -17°F Below -18°F Table 11_U1 JU1B _ JUIC J JUIE JUIF Reverse Damper Operation In = Normal Out = Inverse Factory Set Always In JUID Table 12_umper JUIG Factory Set Always In Locations JUMPER TABLE MODEL JU1A JU1B JU1C JU1D JUIE JU1F JU1G HRVCCLHU1150 OUT IN IN OUT IN IN IN HRVCCLHU1250 OUT IN IN OUT IN IN IN HRVCCSVU1150 IN OUT OUT OUT IN IN IN HRVCCSVU1250 iN OUT OUT OUT IN IN iN HRVCCLVU1150 IN OUT OUT OUT IN iN IN HRVCCLVU1200 IN OUT OUT OUT JN IN IN IN OUT OUT OUT IN IN IN HRVCCLVU1330 ADVANCED Defrost : unit from 2. Disconnect 3. Replug 4. Defrost 5. After should from and select within unit high-speed 2 minutes exchange. after high-speed ex- jumper to J4. module selection occurs, will enable you to properly l_Loss of Memory flash rapidly Replace give exact unit configuration in the jumper operation. mode. Jumper of jumper reset component. is a mistake at specific This selection location The to HRV control has defective working replaced configuraa is done by the (See Tables unit from 115vac prior If unit is not disconnected, to making will (Auto position. Model Only) (rate of about and check once every if problem check red wire for shorting wall control sec). When still exists. this warning 16 If on another has lost its memory. still works even mode. Original modes mode. (See Table 13.) when of flashing, wall control Table 13---Back Mode any This problems. 11 micro-controller will never see jumper change. Failure to follow could result in electrical shock or death. wall control in backup by backup MODES disconnect change. power at 80 percent troubleshoot If en'or still exists, 1 Always (automatic on wall control wall contlol. OFF jumper by the wall control .set dehumidistat indicators are still flashing, Jumpers improper presence or absence and 12.) When error this occurs, Module cause In case of error, indicators only). All indicators cable If there can be signaled wall control flash. Type back in 115vac. on the control Signaling Two types of error J4. unit. thermistor micro-controller. simplified assembly start 6--Control can procedures: has been initiated. 6. Connect Jumpers the following 115vac. thermistor test unplug 7. Replug using unit in 115vac change Step 7--Error DEBUGGING can be simulated 1. Unplug tion,it 10 Minute Defrost/20 Minute Exchange 10 Minute Defrost]15 Minute Exchange Jumper Definition UNITIDENTIFICATION Step 10 Minute Defrost/30 Minute Exchange 6 Minute DefrosU60Minute Exchange 6 Minute DefrostJ32 Minute Exchange 6 Minute DefrosU20 Minute Exchange 23°F to 5°F JUIA EXTENDED DEFROST (JUMPER JUI-F REMOVED) NO Defrost STANDARD DEFROST (AS SNIPPED) °F WALL CONTROL BACKUP MODE OFF INTERMITTENT 2 LOW-SPEED EXCHANGE 3 HIGH-SPEED EXCHANGE it is are Table 14---System Wiring CONTROL Terminal Colors Terminal Block Identificahon MOdel WALL CONTROL Color Terminal NO. Terminal Identification J3-9 B Black J1-4 B J3-8 G Green J1-3 G J3-7 R Red J1-2 R J3-6 y Yellow J 1-4 Y CASE Type Connections WALL CONTROL WIRE MODULE Block No. and 2--42ommunication Problem Or Unsupported Mode (Auto unly_ All indicators flashing at a rate of about once every 8 sec, Communication is not properly entered or is not working. 2 User changes flash at a rate of about the mode but, once green HRV every control particularly control control with 5 ft of wire from module inside HRV. wire. RESET To reset changes command control the mode (OFF, particularly LOW, on wall control or HIGH speed). red wire. (See Table and HRV Check responds to HRV, l. Unplug all wires to wall proceed HRV 2. Wait 15 sec. 3. Plug HRV from as follows: 115vac. 14-.) 17 into 115vac. respond. If problem HRV. CASE 1 User does 8 sec. Check If this All indicators all wires to wall still exists, works, test wall change wall CONNECTION ........ DIAGRAM BLK I q..... =....... I = =] i I= , I R G Y ............ WALL CONTROL ............... WALL WALL WALL CONTROL CONTROL CONTROL__ q l iil I ' , , LOGIC DIAGRAM OVERRIOE OVERRIDE SWITCH 1 NOTE 1 5 -- OPTIONAL 5 2ov6o., OVERR'OE SW_TCH LED 1NOTE ......... ...................................... : J_3 ! .._ J=l Jl 4 RELAY 'I: DEFROST TEMPERATURE SENOR -- _ , ; MED INC ; HIGH 6 ! RELAY M1 _ 1 NEUTRAL j1 ,ow Pi I i _ 1 I L , _ i q , i , i i = i , q , I NOTE 4 i I I _ --. ELECTRONIC ASSEMBLY ........... T1 jUI OE FROST JUMPER TABLE i I _ TIME _NUTE$ l'_p£ ELECTRONIC JUrA Ju_8 OJT OUT JUIC JUlD _UIE JUIF JU_ OUT 5,C HRVCCLHUt _BO A &_ _O,C 532 _20 _0._0 _0_S ASSEMBLY _,VJ_E C._ :.AN_E CH_,SE ._rK_E oU_ RJNCTION A TABLE _LL_,pES MODE K1 K2 K4 K5 intlrrr_tent 0 0 O 0 1 0 _ Exchange High 1 1 1 Circulation low 0 1 0 CirCulation hKjh 1 1 1 0 1 1 I 0 0 0 0 0 Defrosl NOTES I CONTROLS/_VAIt J_BLE. SEE _NSTALL_TION MANUAL ( LOW VCLTAGE ONLY 12 VOC } C_S Ir')a RELAY Exchat_ge LOW Cycle Off I 0 = Relay coil m d_energized 1 = Relay coil ts energized F_CTORY _ET WI RING FOR S_OWER SPEED SEL_C13_N 18 HIgH A N( LOW MEOlUM SPEED CAN 8E SELEC_rED INff_D OF LCW Sp_ED DISCONNECT RED WIRE FROM THE MOTOR REO TAR AND CONNECT _ TRE M_TOR BLUE _p 3 15C fF ANY OF THE ORI_tN_L WIRE¸ AS _UPt' LIEO, MUST OE REPLIED USE TI4E SAME OR E_IVALENT WIRE • U_E F_C_DRy 5UPPLIE_ 5 FILL9 WlRtNG MUST ¢_pkY WqTHA_UCABLE ORDiNAtE8 AND REGU_T_& NS = Not supported COLORCODE -- LINE VOLTAGE ..... LOW VOLTAGE AND F_ELOWIRE p_tOTECTIVE Tt,_lNn _Dt_& R V w y BN NC RED VIOLET WHIT_ YELLOW BROWN NO CONNECTION BK BL GY 0 G BLACK 8LACK GR_Y ORANGE GREEN A00031 Fig, 27--Wiring Diagram for Models: HRVCCLHU1150, and HRVCCLHU1250 CONNECTION DIAGRAM LOGIC DIAGRAM 120VAC _m m LOW NEUTRAL _R INTERLOCK $_TCH i--.. JI I iJ1_ RELAY I r i ' i .................. REU_Y ¢ONT_ i fiO_RD ............. f FUNCTION A _M_-R JUIA _IB ,, JUl ,, _ _BCOE_ TA_-E JglC _ID _JIE OUT OUT OUT OUT OUT O_T OUT OUT OUT IN _JT OUT iN OUT IN _IF IN IN 2 I G _OO_L O_ Z_ #J_G IN HRV¢CSVU11_ A _ HRVCCSVU12_ A IN H_VCCLVU_I_ TABLE RELAy MOOE K1 K2 K5 Inlarmittent 0 0 1 i 0 O I O C_¢ul_t _n low I 0 1 Cin:u_ation high 1 1 1 D_frosl 1 _ 1 0 0 1 Exchange Low Exchange High Cycle Off 0 • Relay coil _s d_, energized IN C_T I OUT I OUT I _ HRVCCLVUI_ IN 1 = Relay ¢oil _s energized NS = Noi supported H_VCCLVUI_0 NOTES I"THREECONTROL_AVAI_BL£S££THEINSTALLATIONM_NUAL ILOWVOLTAG_ O_LYI2V_C) 2. FAN MOTOR 2 I$ USED ONLY WITH HRVCCLHU125O AND HR_¢CLVU_330 30Ak_PER MOTOR 2 IS USED ONLY WlTHRV¢¢_V_ HRVCC_VU 1330 --LINEVOLTAGE - --LC_qVOLTAGE AND FIELD WIRE ----OPTIONAL R V W Y BN N¢ RED BK VIOLET BL WHITE GY YELLOW O BROWN G COLOR CODE NO CONNECTION BLACK BLACK GREY ORANGE GREEN _RVCCLVUI _C_ 200 AN D 4. IF ANY OF THE ORIGINAL WIRE _S SUPPLIED. MUST BE REPLA¢£0_ U_E TH_ SAM_ OR EOUtVALENT WIRE I S • FACTORY S_T WIRING _OR BLOWER SpEE_ SELECTION IS HIGH AND L_W M£OIUM SPE_D C_N BE S_LECTED IN_TE_D OF LOW $_EED DISCONNECT RED WIRE FROM MOTORIS I RED TAP AND CONNECT TO M<_TOR_$) BLUE TA_ A00089 Fig. 28--Wiring Diagram for Models: HRVCCSVU1150, HRVCCSVU1200, and HRVCCLVU1330 HRVCCLVU1150, HRMCCLMU1200, 2 3/16t--,-I (56.2) 4 PLCS-_- 2 s/16t (25.4) 2 PLCS (120.6) (56.7) ,/_5 1 (460_') O (608.0) 1 D I 16 7/8, _ 7/8t DIA Ill (381.0) 15t 30 1/4t (768.3) NOTES: 1. FRESH AIR FROM OUTSIDE TO HRV 2. FRESH AIR FROM HRVTO HOUSE 3. STALE AIR FROM HOUSE TO HRV 4. STALE AIR FROM HRV TO OUTSIDE A99263 MODEL NO. HRVCCLHU1150 HRVCCLHU1250 jmm 196.9 236.6 Fig. 29--Dimensional Drawing HRVCCLHU // 4 9/_e_ [115.9)} --b 57/e" DIA [149.2] 2 PLCS L._ // // ji S / _ s I WALL CONTROL WIRING (_ / _ 3/a"DIA q_ [9.5] 3¾6 [81.o] C i t -- 1 15/16" [23.8] __193/4" 2 3/16" -- [55.6] [5ol.7] -4 , r_q, _- PLCS T 1 l"J [25.4] 2 PLCS NOTES: 1. FRESH AIR FROM OUTSIDE TO HRV 2. FRESH AIR FROM HRV TO HOUSE 27" [685,8] FJ 3. STALE AIR FROM HOUSE TO HRV 4. STALE AIR FROM HRV TO OUTSIDE 221/16 _ [560.4] _1511/! 6" [398,5]_ __ 2 PLCS E ._..--,-.-.-- G ..-.-----_ A98003 A MODEL NO. B C D E F G in. mm in. mm in. mm in. mm in. mm in. mm in. mm HRVCCSVU1150 18-1/2 469.9 4-11/16 119.1 13-5/16 388.2 15-7/16 392.1 13-9/16 344.5 5-7/8 149.2 19-15/16 506.2 HRVCCSVU1200 HRVCCLVU1150 24-1/2 622.2 8-3/16 208.0 19-5/16 490.6 14-9/16 369.9 16-15/16 430.2 6-7/8 174.6 19-15/16 506.2 Fig. 30--Dimensional Drawing HRVCCSVU and HRVCCLVU NOTES: 1. FRESH AIR FROM OUTSIDE TO HRV 13/t6" 8 1/8" [206.4] 2 PLCS_', 2. FRESH AIR FROM HRV TO HOUSE '[147.6] 3. STALE AIR FROM HOUSE TO HRV 4. STALE AIR FROM HRV TO OUTSIDE .151/2. 6 185/16" C148.2] 2 PLCS _ 15/16" [176.2] [465.1 ] 1 " 125.4] 1 1/2" [38.1] 2 PLCS q !_'---2 PLGS 2 3/16" [55.6] F2 PLCS T t b_ 7 1/_,, ,_--[181.0] (_ _ ....... //// 43" (1092.2) L 123/4" [323.91 41" [1041.4] ........ / WALL _-_/ _ / WIRING 3/8" DIA CONTROL \ \ 1%6"DIA. [17.5] 2 PLCS t 19 1/16" [48i'2] /' "I I 23 WW' .,,.--- [608.0]--_. 24 1/16"'_" [611.2] -..11---- POWER CORD [208.0] [182.6] A98001 Fig. 31--Dimensional Drawing HRVCCLVU1200 or HRVCCLVU1330 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: * Unit FamiliarizaUon ° Maintenance • Instaila'don Overview • Operating Sequence A large seleclion of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshoo_ng, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG [ ] Packaged Service Training 1-800-962-9212 [ ] Classroom Service Training A94328 23 Copyright 2000 CARRIER Manufacturer "i_12 reserves a PC 101 Corp. • 7310 W, Morns St. • Indianapolis, IN 46231 the right to discontinue, Catalog NO. 03HR-VC3 hrvlsi or change at any time, specifications Printed in U.S.A, or designs without notice and without Form HRV-2SI Pg 24 5-00 incurring obligations. Replaces: HRV-1SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Mon Apr 02 19:12:02 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools