HUMIDITRACTMHUMIDIFIERCONTROL
Safety
READ

COMPLETE

and Installation
INSTALLATION

Attention Installer:

Instructions
INSTRUCTIONS

AND

TEMPLATE

BEFORE

STARTING,

This product must be installed by a qualified heating and air conditioning contractor.
Failure to do so could result in serious injury from electrical shock.

THESEINSTALLATION
INSTRUCTIONSAREFORTHEHUMIDITRAC
TM HUMIDIFIERCONTROL
ONLY!
ForHumidifierinstallation,follow HumidifierInstallationInstructions,
_._A

STEP 1:Unpack the Humidifier Control Carton
Make sure all componentsare present(see FigureA):
%

A. HumidifierControl
B. OutdoorTemperatureSensor
C. SensorShield

STEP2: Disassemble the Humidifier Control

Figure A

Removeknob,then pull coveroffthe base•

STEP3: Check the Jumper Blocks
With the coverremoved, notice 5 pinscomingup from the base.Make surethe 2 sets of
jumper blocks are correctlysetfor the P/pe of humidifierbeing installed(see FigureB).

STEP4: Mount Humidifier Control
Control mustbemounted inthe ReturnDuct.Forproperoperation,the
Controlmust be at least 6 inches upstreamof anyof the following:
•
•
•

FigureB

Humidifier
Humidifier BypassDuctwork(ifapplicable)
FreshAir Intake Ductwork(if applicable)(see FigureC)

Usethe perforated HumidifierControltemplate(attachedto these instructions)to mark
the ductopeningand cut it. Use 4 sheetmetalscrews (notprovided)
to mountthe Control in the duct openingand makesure Control is sealeddghtJyto duct.

STEP5: Determine

Location for Outdoor Temperature Sensor

TheOutdoor TemperatureSensor:
1. Must be mountedon North,East orWest sideof house out ofdirect sunlight
2. Must be at least 3feet from all exhaust vents
3. Must be above expectedsnow line (Seefigure D)
Incorrect hamid_ levels will result if these requirements are not met.

STEP6: Locate Existing Access

Hole to Outside

A convenientway to get the Sensorwire outsideis to make
use ofunusedwires runningto the NC condensingunit
(if applicable).Otherwaysare to use existingholesfor
Cable TVlines,telephonelines,A/C lines, etc. Readall
equipmentinstructionsbeforehandfor possibleconflicts
andwamings.

OUCT

FigureC

STEP7:

Alternate

Location for Outdoor Temperature Sensor

The Sensor canalso be mounted in the center of either:
• 2 inchPVCfresh air intake pipeforthe furnace
OR
• 6 inchfreshair intake duct

M

<

7

,......

In bothcases,the Sensormust be nofurther than3feet fromthe outsidewall, SeeFigureE.
FigureE
a

_6,,

MAX

--

OUTSIDE

WALL

STEP8: Routethe Wire to Chosen Sensor Location
Hunwire tothe OutdoorTemperatureSensor.If sensoris outdoors,snapthe probeendof the Sensor intothe SensorShield, andattachtothe house.
l_p ofSensor mostbe completelycoveredbythe Shield.The OutdoorTemperatureSensor is notaffectedbylead length.
In eithercase,do not runOutdoorTemperatureSensorwire alongsidewires carryinghighvoltage(120VACor higher).

STEP9: Wiring
NOTE:Thecontrolwill function with eithere switchedor continuous24 VACPower source.

Fan-PoweredHumidifierWiring

BypassHumidifierWiring

DiagramA

DiagramC

Standard Furnace
Variable Speed Furnace
Variable Speed Fan Coil

For Operation during "Heat Call" only

Humid_rac
W_Hag Temminals

iq w_
HUMIOI

HUM
2
TERMINALS
C

i

]R AC

:

I

L'ON

i

I =--_ 1

I / i

_

_T_OL

/ L___

oumooe

24 Y_.
Terminals
on rmmace

H
HulioIrl_

JUMPER

_

LeedsHUmidifier

POSITION

JUMPER BLOCKS

Diagram B

DiagramD

Standard Fan Cotl

For Operation when blower is energized
HillilDIl_
AC CON IROL
_4RING TERIIIN_.$

Humid_ra_ Cord_ol
Wit_n9Tenmnals

,r---i + T_-I
OUTDOOR
--

SENS(3#_

.,<...,+,.=
Te_ls

f_c_"
_11_

R
_TO

_

--#

I

\

IRMd Supplied)

14 v^c L£_OS

Note;Connlict
1olenold"_zltetokotwatere Famlidifier
willlie oFerat_ i_le_+_i
ol ;_ng ceUi

Hamidifier

_4Va_
dva_e
u_a_s

% Relative

Humidity

Guide

Outdoor Temperature(°F)
-10

0

10

20

30

40

1

10

10

10

15

20

25

2

10

10

15

20

25

30

3

10

15

20

30

35

4

15

20

25

35

40

5

20

11.1

40

45

6

25

30

35

40

45

45

7

30

35

40

45

45

45

As an example, if the outdoor temperature is 20° F, and, following step 3, the
humidifier turns off at "5" on the dial range, then the RH in your home is 35%,

HumidifierControlTroubleshootingGuide
SYMPTOM

TROUBLESHOOTING
PROCEDURE

Humidifierdoesnot
operatein "Test" mode

•

Make sure furnace blower is operatingandthermostatis callingfor heat.

•

Make sure the OutdoorTemperatureSensor is connectedto the "OutdoorTemperatureSensor"terminalsof the control.

•

Check mainwiring diagramfor correct HumidifierControl installation.

•

Check voltageat HumidifierControl24 VACterminals.Voltageshould he 22VACminimum- 30 VACmaximum.

•

Check HumidifierControl for correctinstallationofjumperblocks.

•

Check Current Sensing Relay(if used)for correctinstallation.Do notuse Model 50 Relayintransformercircuitor "24 VAC"
circuitof HumidifierControl. Model 50 relay is to be usedin the "A]A" circuitonly.

•

In "Test" mode,humidifier will operatefor 1 minute only.DO NOTLEAVEIN TESTMODEAS HUMIDIFIERWILL NOTOPERATE.

Humidifieroperatesonly
in "Test"mode

• If outdoor temperatureis greaterthan65°For lessthan -32°F,the HumidifierControl will
only operate in the "Test" mode.(AutomaticMode Only)
•

If the humidity level in the home is higher than the knob setting, the Humidifier Control will
not operate the Humidifier.

•

Check the resistance ofthe sensor by removing the leads of the OutdoorTemperature
Sensorfrom the terminals and measuringthe resistance across the wires with an ohmmeter.
Confrm reading to outdoor temperature in Table 1.

•
•
•

Make sure the Outdoor TemperatureSensor is mounted completely outside the house on
the North, East,or West side of the house and out of direct sunlight.
If OutdoorTemperature Sensor is mounted in fresh air intake duct, make surethe probe
is no further than 36 inchesfrom the outsidewall.
MakesuretheOutdaorTemperatureSensorislocatedatleast3feetawayfroma]l
exhaustvents.

TABLE 1
Outdoor
Temperature

Resistance

100=F

6,000 OHMS

90° F

7,5_ OHMS

80° F

9,500 OHMS

70°F

12,000OHMS

60°F

15.500OHMS

50_F

20,0000HMS

4OOF

26,0000HMS

30=F

34,500OHMS

20"F

46,000OHMS

10=F

62.000OHMS

0=F
-1O'F

84,500OHMS
116,5000HMS

-20"F
-_°F

162,500OHMS
229,500OHMS

HumidifierControlTroubleshootingGuide
TROUBLESHOOTING
PROCEDURE

SYMPTOM

If the humiditylevelin the homeislessthan the knobsetting,the HumidifierControlwig
operatethe Humidifieruntilthe humiditylevel is higherthan the knobsetting.

Humidiferoperates
constantly

In the "Test" mode,verifyunitwill operate for approximatelyone minute.
Checkthe resistanceof the sensorbyremovingthe wires ofthe OutdoorTemperature
Sensorand measuringthe resistanceacrossthe wires with anohmmeter.Compare
measurementto outdoor temperaturein Table 1.
Make surethe OutdoorTemperatureSensor ismountedcompletelyoutsidethe houseon
the North,East,orWest sideofthe houseandoutofdirectsunlight..
Rotatethe HumidifierControlknobcounterclockwiseto the "Off"position,and observe
whetherthe humidifierturnsoff.If the humidifierstill operatesin the "Off" position,
performthe following:
1. Checksummarywiring diagramfor correctHumidifier ControlInstallation.
2. Removewires from HumidifierCoutrol's"NA" terminals.If Humidifier continues
to operate, replacesolenoidvalve.

Humidifier or Humidifier
Control "chatters"or
clicksON andOFFrapidly

•
•

Checkfor steady 22VAC- 30VACwith voltmeter.
Make sure OutdoorTemperatureSensor wiringis notrunalongsidewires carryinghighvoltage(120VACor higher).

.......................................................................................................................................

WARNING
Sharp edgeson the openingmay cause cuts.Use carewhen cuttingthe plenumopening
and installingthe HumidifierControl
CAUTION
• Do notmount HumidifierControlon supplyplenumor duct.The unitwill notwithstand
supplytemperaturesandwill malfunction!
• When installingHumidifier ContToIon counterflowfurnaces, ensureblowercontinues
to run after a heatcall issatisfiedto eliminatehightemperaturesfrom damagingthe
HumidifierControl.
• Do not mount HumidifierControl downstreamof the bypassouttet. Falsehumidity
conditionswigcausehumidifierto operate incorrectly.
1.

CUTOUTTEMPLATEALONGEDGES.

2.

PLACETHIS TEMPLATEONTHE RE1URNPLENUMUPSTREAMOF(BEFORE)THE
HUMIDIFIERCONNECTION.

3.

TRACETHEOUTSIDEEDGESOFTHIS 1TJMPLATE.

4.

REMOVETEMPLATEAND ACCURATELY
CUTTHE PLENUMOPENING.

5.

USING 4 SHEETMETALSCREWS,INSTALLHUMIDIRERCONTROL
IN pLENUMOPENING.

Form:AG - UAWC- 01
Catalog:63UA- WC0
© 2002CAC/BDP
7310W. Morris St.
DP #10005688

1500.4.02

Indianapolis, IN 48231



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 4
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 12:53:41 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu