CARRIER Air Handler (indoor Blower&evap) Manual L0501315
User Manual: CARRIER CARRIER Air Handler (indoor blower&evap) Manual CARRIER Air Handler (indoor blower&evap) Owner's Manual, CARRIER Air Handler (indoor blower&evap) installation guides
Open the PDF directly: View PDF .
Page Count: 116
Download | |
Open PDF In Browser | View PDF |
39MN,MW03-61 Indoor and Weathertight Outdoor Air Handlers Installation, Start-Up and Service Instructions CONTENTS Page INTRODUCTION ..................................... 1 SAFETY CONSIDERATIONS ......................... 2 UNIT AND COMPONENT IDENTIFICATION ........ 2-10 PRE-INSTALLATION ............................. 10-38 Inspection .......................................... 10 Rigging and Handling .............................. 10 Long-Term Storage ................................. 35 Service Clearance .................................. 35 Drain Positioning ................................... 35 Unit Suspension .................................... 35 Internal Vibration Isolation ......................... 35 External Vibration Isolation ......................... 36 Roof Curb .......................................... 36 Pier or Beam Mount ................................ 37 INSTALLATION .................................. 38-85 Indoor Unit/Section Connection .................... 38 Outdoor Unit ....................................... 39 Duct Connections .................................. 40 Panel Cutting ....................................... 42 Zone Damper Section .............................. 42 Face and Bypass Dampers ......................... 42 Mixing Box/Filter Mixing Box Damper Linkage ...... 45 Mixing Box Damper Actuators ...................... 45 Vertical Draw-Thru Units ............................ 47 Fan Sled Disassembly .............................. 48 Fan Sled Dimensions ............................... 49 Fan Motors and Drives ............................. 50 Motor Power Wiring ................................ 50 Sheaves ............................................ 50 V-Belts ............................................. 51 Outdoor Hoods and Louvers ....................... 52 Coil Connection Housing ........................... 52 Humidifier Installation .............................. 54 Assembly of Vertical Manifolds ..................... 58 Coil Installation ..................................... 59 Water and Steam Coil Piping Recommendations ............................... 61 Coil Freeze-Up Protection .......................... 63 Refrigerant Piping, Direct-Expansion Coils ......... 64 Hot Gas Piping and Wiring ......................... 68 • INSTALL PIPING Condensate Drain .................................. 69 Fan Motor Wiring Recommendations ............... 69 Motor Electrical Data ............................... 70 Fan Motor Starter ................................... 71 Disconnect ......................................... 71 VFD ................................................ 71 VFD with Bypass ................................... 72 VFD Configuration .................................. 78 VFD Modes ......................................... 78 Manufacturer Page Electric Heaters .................................... 79 Energy Recovery Ventilation Sections .............. 84 • RECEIVING AND INSPECTION • RIGGING AND STACKING • ERV WHEEL MOTOR WIRING START-UP ....................................... 85-87 Checklist ........................................... 85 Energy Recovery Wheel ............................ 87 SERVICE ....................................... 88-110 General ............................................ 88 Electric Heaters .................................... 88 Fan Motor Replacement ............................ 88 Energy Recovery Ventilation ....................... 88 • CLEANING • CASSETTE REPLACEMENT • ADJUSTING AIR SEALS • SEGMENT INSTALLATION AND REPLACEMENT • WHEEL DRIVE MOTOR AND PULLEY REPLACEMENT • SOLID BELT REPLACEMENT • LINK BELT REPLACEMENT • OTHER MAINTENANCE Cleaning Unit Interior/Exterior ...................... 91 Coil Cleaning ....................................... 92 Winter Shutdown ................................... 92 Coil Removal ....................................... 93 Changing Coil Hand ................................ 94 Filters .............................................. 95 Magnehelic Gage Maintenance .................... 108 Fan Shaft Bearing Removal ....................... 108 Fan and Shaft Removal ............................ 108 Motor Location .................................... 109 Lubrication ........................................ 109 Motor and Drive Package Data .................... 109 Variable Frequency Drive .......................... 109 TROUBLESHOOTING .......................... 110-116 Steam Coil Performance Problems ................ 110 Steam Failure Modes .............................. 110 VFD Diagnostics .................................. 110 INTRODUCTION The 39M series central staion air handlers me usually installed with ductwork; they provide air conditioning at nominal capacities of 1500 to 30,500 cfin. The 39M air handler design allows hundreds of diffelent configuration possibilities. Each unit is assembled to meet specific job requirements and can be shipped in sections or as a single assembly. These instructions describe how to install, start up, and service 39M air handlel_. reserves the right to discontinue, or change at any time, specifications PC 201 Catalog No, 533-952 Printed in U,S.A. or designs without notice and without incurring obligations. Form 39M-6SI Pg 1 12-04 Replaces: 39M-5SI SAFETY CONSIDERATIONS 39M air-handling equipment (see Fig. 1) is designed to provide safe and reliable service when installed and operated within design specifications. To avoid injury to personnel and dmnage to equipment or property when operating this equipment, use good judgment and follow safe practices as outlined below. SECURE fan drive sheave with a rope or strap before working on a fan to ensure that rotor cannot freewheel. DO NOT restole power to unit until all temporary ways inside components have been removed. NEVER pressurize pressures. NEVER enter an enclosed while the fan is running. fan cabinet or reach into a unit LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses with you and note removal on tag. LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near heateLs. CHECK the assembly and component weights to be sure that the rigging equipment can handle them safely. Note also the centers of gravity and any specific rigging instructions. CHECK for adequate ventilation so that fumes will not migrate through ductwork to occupied spaces when welding or cutting inside air-handling unit cabinet or plenum. WHEN STEAM CLEANING COILS be sure that the area is cle_u of personnel. DO NOT lemove pletely stopped. access panel fasteners until fan is com- Pressme developed by a moving fan can cause excessive force against the panel and toward personnel. DO NOT work disconnected. on dampeLs until their operators BE SURE that fans m'e properly grounded on them. m'e before working equipment in excess walk- of specified test PROTECT adjacent flammable material when welding or flame cutting. Have a fire extinguisher at hand and ready for immediate use. PREVENT unauthorized entry into the unit; leave safety latches in place on access doors except during installation or service procedures. After accessing a section, replace and tighten the safety latch. FIELD SUPPLIED MOTORS should be Underwriters' Laboratories (UL) or Canadian Standmds Association (CSA) approved. FIELD WIRING must comply with Natiomfl Code (NEC) and all local requirements. DO NOT ground equipment to fan assembly ing. Damage to fan bezu'ings could result. UNIT AND COMPONENT Electric_fl when weld- IDENTIFICATION The 39M air handler comes in two basic configurations; horizontal and vertical. Using appropriate sections, it is possible to design many unit variations, including blow-thru units and plenum fan units with multiple discharges. Fig. 2A-2H show an exmnple of the model number used for 39M unit sections and components. Each unit's model number is listed on a label affixed to the fan section. Section and major component level part numbers are listed and affixed to each individual component section. For further information on unit and component identification refer to Fig. 3A-3B and contact your Carrier representative for the AHUBuilder® program. Refer to the 39M Product Data cat,dog for more information on individual component sections. Fig. 1 -- Typical 39M Air Handler (Indoor Unit Shown) 39M N 03 000001 12 S X S m S - Standard Q - Quick Ship 39M-Air Handle I T N - Indoor Unit W - Outdoor Unit f Shipping X - Always Option Unit Crating Option S - Skid only C - Protective cover skid B - Export with protective cover E - Export without protective cover Unit Size 03 06 08 10 12 14 17 21 25 30 36 4O 50 61 Shipping No. of Pieces Example: 12 = 1 of 2 22=2of2 Odometer Number Revision Level Fig. 2A -- 39M Unit Nomenclature 28M0 28M0 28MH - 1/2in. Chilled Water 1/2in. Hot Water V T Coil Position H - Horizontal V - Vertical Rows 1 2 4 6 8 O - - 44 * A 020 A R N X X - Always -- -T Coating N - Non-Coated E - E-Coated Unit Size DBTSt(in.) 03 020 21 06 034 25 08 040 30 10 052 36 12 052 40 14 059 50 17 065 61 B S 12 N/A 12 12 14 12 14 12 20 14 20 14 22 16 28 18 28 18 28 18 30 24 36 24 36 28 44 34 065 074 092 096 096 104 104 Tube Wall and Hairpin Type 1/2 in.O.D. Copper Tube A - .016 Std. Hairpin B - .025 Std. Hairpin Fin Material Fins Per Inch Casing Material AAL 8 GALV. D - AL 11 GALV. F - AL 14 GALV. G - AL 8 ST. STL. K - AL 11 ST. STL. MAL 14 ST. STL. N - CU 8 ST. STL. R - CU 11 ST. STL. T - CU 14 ST. STL. LEGEND ----- D Header Style A - MPT Std B - MPT-Non Ferrous NOTE: If positions 7-8 are _>30, then position 15 cannot = B. Circuiting H - Half Circuit F - Full Circuit D - Double Circuit B L M S 20 Hand R - Righthand L - Leffhand 1 Row 2 Row 4 Row 8 Row 8 Row 10 Row Tubes In Face 12 39M Unit Size L M 03 20 14 06 20 14 08 22 16 10 22 16 12 28 22 14 28 24 17 30 24 21 38 32 25 38 32 30 38 32 36 44 36 40 24/24 44 50 28/28 44 61 34/34 28/28 6 Bypass Large Medium Small *Multiple values indicate that two coils must be ordered. 1-Distance between tube sheets. Fig. 2B -- 28MC,28MH (1/2-in. Water Coil) Nomenclature 28MZ 28MZ - H 26 IDT Steam 074 A X N - l - - Coil Revision Header Style A - MPT Std 2 Row Tubes In Face* If position 11 = S 1in. 39M Unit Size L M B 03 08 05 05 06 08 05 05 08 09 06 05 10 09 06 05 12 11 09 08 14 11 10 08 17 12 10 09 21 15 13 11 25 15 13 11 30 15 13 11 36 18 15 12 40 10/10 18 15 50 12/11 18 15 61 14/14 12/11 18 T X - Always Rows 1 - 1 Row - B Coating N - Non-Coated E - E-Coated Coil Position H - Horizontal V - Vertical 2 F If position 11 = T 5/8 in. S N/A 05 05 05 05 05 06 07 07 07 10 10 11 14 L 16 16 18 18 22 22 24 30 30 30 36 20/20 24/22 28/28 M 10 10 12 12 18 20 20 26 26 26 30 36 36 24/22 B S 10 N/A 10 10 11 10 11 10 16 10 16 10 19 12 22 14 22 14 22 14 24 20 30 20 30 22 36 28 Circuiting F - Full Fin Material Fins Per Inch Casing Material B - AL 6 GALV. E - AL 9 GALV. C - AL 12 GALV. H - AL 6 ST. STL. L - AL 9 ST. STL. J - AL 12 ST. STL. P - CU 6 ST. STL. S - CU 9 ST. STL. Q - CU 12 ST. STL. Header Note: Pos. 11 (Type 'S') Supply = 2 1/2 in. MPT Condensate = 2 1/2 in. MPT Pos. 11 (Type 'T') (1) Row 10-28TF = 2 in. MPT (Supply and Return) 29-40 = 2 1/2 in. MPT (Supply) = 2 in. MPT (Return) (2) Row 10-28TF = 2 t/2 in. MPT (Supply and Return) 29-40TF = 3 in. MPT (Supply) = 2 1/2in. MPT (Return) TF-Tubes in face Unit Size 03 06 08 10 12 14 17 21 28 30 36 48 50 61 Tube Size and Copper Wall S - 1 in. O.D.x. 030 Wall Outer Tube 5/8 in. O.D.x. 020 Wall Inner Tube T - 5/8 in. O.D. x .035 Wall Outer Tube 3/8 in. O.D. x .020 Wall Inner Tube LEGEND B L M S ----- DBTSt (in.) 020 034 040 052 052 059 065 065 074 092 096 096 104 104 Bypass Large Medium Small *Multiple values indicated that two coils must be ordered. 1-Distance between tube sheets. Fig. 2C -- 28MZ (Steam Coil) Nomenclature 28ME 28ME - V 4 32 B A A 065 Z R N X -- l Direct Expansion X - Always Coil Position V - Vertical Coating N - Non-Coated E - E-Coated Rows 4 4 Row 6 8 Row 8 8 Row Hand R - Righthand L - Lefthand Header Style Z - Standard (Copper) Varies with Coil Tubes In Face 14 - 44* 39M Unit Size L M 03 20 14 06 20 14 08 22 16 10 22 16 12 28 22 14 28 24 17 30 24 21 38 32 25 38 32 30 38 32 36 44 36 40 24/24 44 50 28/28 44 61 34/34 28/28 Unit Circuiting A - Face Split Quarter B - Face Split Half C - Face Split Full D - Double E - Quarter Circuit - Single Distributor J - Half Circuit - Single Distributor G - Row Split Full K - Row Split Quarter M - Row Split Half Size 03 06 08 10 12 14 17 21 25 30 36 40 50 61 Tube Wall and Hairpin Type 1/2 in.O.D. Copper Tube A - .016 Std. Hairpin B - .025 Std. Hairpin Fin Material Fins Per Inch Casing Material AAL 8 GALV. D - AL 11 GALV. F - AL 14 GALV. G - AL 8 ST. STL. K - AL 11 ST. STL. M - AL 14 ST. STL. N - CU 8 ST. STL. R - CU 11 ST. STL. T - CU 14 ST. STL. LEGEND L M --- DBTSt(in.) 020 034 040 052 052 059 065 065 072 092 096 096 104 104 Large Medium *Multiple values indicated that two coils must be ordered. 1-Distance between tube sheets. Fig. 2D -- 28ME (Direct Expansion Coil) Nomenclature 28MG 28MG - Integral Face and Bypass Unit Size Code Size B 03 C 06 D 08 F 10 G 12 H 14 J 17 K 21 L 25 M 3O N 36 p 40 Q 50 R 61 M T H S 2 04 G N H XX m 1 l Revision Level XX - Always Tube Orientation H - Horizontal V - Vertical Hand R - Righthand L - Lefthand Actuator Y - Yes N - No Casing Material G - Galvanized S - Stainless Steel Coil Position H - Horizontal Coil Type H - Hot water S - Steam Fins per Inch 04 - 4 05- 5 06- 6 07- 7 08- 8 09- 9 10- 10 11- 11 12- 12 13- 13 14- 14 Rows 1 -1row 2 - 2 row 3 - 3 row Fig. 2E -- 28MG (Integral Face and Bypass Coil) Nomenclature 28MKM R S XXXXXXXXXX - Revision Level 28MK- Humidifer XXXXXXXXXX - Always Unit Size Code Size B 03 C 06 D O8 F 10 G 12 H 14 J 17 K 21 L 25 M 30 N 36 P 40 Q 50 R 61 Frame Material G - Galvanized (g90) S - Stainless Steel Hand R - Righthand L - Lefthand Fig. 2F -- 28MK (Humidifier) Nomenclature 28MD 28MD 28MJ - 5/8 in. Chilled Water 5/8in. Hot Water Coil Position H - Horizontal V - Vertical Rows 1 2 4 6 8 - 1 2 8 6 8 Row Row Row Row Row Tubes In Face 10 - 36 Circuiting H - Half Circuit F - Full Circuit D- Double Circuit Fin Material Fins Per Inch Casing Material AAL 8 GALV. C - AL 12 GALV. F - AL 14 GALV. G - AL 8 ST. STL. J - AL 12 ST. STL. MAL 14 ST. STL. N - CU 8 ST. STL. Q - CU 12 ST. STL. T - CU 14 ST. STL. V 4 30 F A C 092 A R N A / 1 T,-Always Coating N - Non-Coated E - E-Coated Hand R - Righthand L - Lefthand Header Style A - MPT Standard B - MPT-Non Ferrous 39M Unit Size 03 06 08 10 12 14 17 21 25 30 36 40 50 61 DBTS* (in.) 020 034 040 052 052 059 065 065 074 092 096 096 104 104 Tube Wall and Hairpin Type 5/8 in. O.D. Copper Tube C - .020 Std. Hairpin D - .035 Std. Hairpin *Distance between tube sheets. Fig. 2G -- 28MD,28MJ (5/8-in. Water Coil) Nomenclature 93 Fan Motor MRMS- High Efficiency Premium Efficiency Horsepower* 01 1/2 02 3/4 03 1 041 1/2 05 2 06 3 07 5 08 7 1/2 0910 1015 11 20 121314 1516 17 18 19 2021 - MR 01 18 mT B A 02 0 0 3 S - 1' 25 30 40 50 60 75 100 125 150 200 Fan Application R - Return/Exhaust S - Supply Supplier Designation Not Used (Always 0) Application Mounting 1 - Fl12 - F213 - F3** Voltage 02 115/230-1-60 03 230-1-60 07 575-3-60 18 460-3-60 27 200/230/460-3-60 28 200/400-3-50 (190/380-3-50) Insulation Class 0 - Vendors (Std.) Frame 01 0225 26 27 28 29 30 31 32 33 34 35 36 37 - RPM Synchronous B- 1800 60Hz C - 3600 60 Hz E -150050Hz F - 3000 50 Hz Type A - Open Drip Proof C - Totally Enclosed - Fan Cooled *Not all horsepower values shown are applicable to 39M units. 1"F3 Box location may be substituted for either F1 or F2. **F3 Mounting may only be available on ODP Motors. Mounting numbers apply when facing Motor Shaft end. F1 Revision Level F2 F3 Fig. 2H -- Motor Nomenclature 48 56 143T 145T 182T 184T 213T 215T 254T 245T 284T 286T 324T 326T 364T 383940 41 42 43 44 45 46 47 48 51 52 53 54 - 365T 404T 405T 444T 445T 286TS 324TS 326TS 364TS 365TS 405TS 404TS 444TS 445TS 284TS _F Carrier O Model39MN08B0053Xl12SXS Odometer 0053X1 SLP $LP Serial Size 1 39MDSTD01DFPKFXJHH 4 39MDSTDO1DJZZZXJBH SLP 008 2 39MCSTDO1DGBXXXOHX 3WHSTD01DGHXFXGeF _LP 10 SLP# 1504F26765 Odometer Piece 1 of 2 SLP 3 SLP 6 Carrier 39MHSTD01DGHXFXGBF Fan Motor Drive 39MHSTD01DPPXFXJBA SLP 12 Serial Size 0053X1 Coil 1 Coil 2 1504F26765 008 28MCV614HAAO4OARNX Tag i 39M ! 594 A_Se_bJe0 _n LI_O_A PoaoMA5GOZ50C_ _OM ! 594A Assembled in U,S,A PN3OMA5C_Z5002 Fig. 3B -- Section Nameplate Label (Each Component Section will have a Section Nameplate Label) Fig. 3A -- Unit Nameplate Label (Found on Each Component Section Shipped Separately) using the lifting brackets, unit. PRE-INSTALLATION Inspection -- Inspect the unit; file a claim with the shipping company if the unit is &_maged, Check the packing list to ensure that the correct items have been received and notify your CatTier representative of any discrepancy, as shown on the rigging label on the Aero connect hitches or screws are provided at specified sections to separate component sections: 1. Undo till fasteners (with red hex heads) on vertical and horizontal (side and top) semns. Rigging and Handling -- To transfer the unit fiom the shipping platform to the storage or installation site, refer to the rigging label on the unit and these instructions, 2. Remove brackets togethet: the and large through-bolts in adjacent lifting smaller bolts that hold lifting brackets 3. Lift the unit with slings and header bars, using clevises and pins in the large round holes in the unit's lifting brackets. When the unit is in its final location, do not remove the caps fiom the coil connections until the coil is ready for piping. Do not remove grease fiom the fan shaft until the drive sheave is ready for instalhttion. You can use a forklift truck to move units or components only if they have full skids, Lift fiom the heavy end of the skid, Minimum recommended fork length is 48 inches, Base units are shipped fully assembled, except when sections me separately ordered or when the unit height exceeds 108 in. or length exceeds 30 feet. All 39M units can be rigged Refer to Fig. 4 and 5 and Tables 1- 17 for component 10 &tta. 39MN Indoor Unit Dimensions 39MN UNIT SIZE UNIT H (in.) CASING W (in.) O3 39 33 06 39 46 O8 42 54 10 42 67 12 49 67 14 49 72 17 52 79 21 62 79 25 62 86 3O 62 104 36 73 109 40 79 109 5O 89 117 61 104 117 H AWL 39MW Outdoor Unit Dimensions 39MN UNIT SIZE UNIT CASING H (in.) W (in.) O3 43 36 06 43 49 O8 46 57 10 46 70 12 53 70 14 53 75 17 56 82 21 66 82 25 66 89 3O 66 107 36 77 112 40 83 112 5O 93 120 61 108 120 AWL NOTES: 1. Weights and dimensions are approximate. For more exact dimensions, consult with your local Carrier Sales Engineer or select your desired unit using AHUBuilder¢) software. 2. All dimensions in inches unless otherwise noted. LEGEND AWL H W Fig. 4- Base Unit Dimensions 1! --- Airway Length Height Width Air Distribution _ Mixing box Plenum Components _2_ Mixing box v (side inlet) & Filtration @ Plenum section _3_ Filter Mixing box (_ Heat Transfer (_) External bypass return section Horizontal, bag/side loading cartridge filter section Sections (_ Cooling coil section with drain pan Air mixer _ Exhaust box (side outlet) Exhaust box (_) Internal face and bypass heating coil section (_ Internal face @ External face and bypass and bypass damper section damper section Sections @ Humidifier section (_) Horizontal, angle filter section _ Extended length cooling coil section (_ (_) Vertical short bag/side loading cartridge filter section @ Heating coil section (_ Blow-thru plenumsection (_ with drain pan _ -- Vertical blow-thru plenum section discharge Horizontal, bag/front loading cartridge section Extended length heating _ -- _ _ Horizontal, flat filter section Horizontal, blow-thru front loading HEPA filter section @ Extended length -- heating coil section coil section _ with drain pan Dual coil section with drain pan D LEGEND c (_ Electric heat section _ -- Horizontal blow-thru coil section with drain pan _ -- C N Cooling/Heating blow-thru coil section with drain pan @ Multizone damper section --- Cooling Heating (_) Vertical cooling coil section with drain pan Fan Motor Sections A B Fan Configurations Available ContlguraUons Section _e F E Horizontal fan with rear inlet fan section @Draw-thru exhaust fan section A B Blow-thru supply fan section with rear inlet and diffuser BYPASS be field-fabricated Fan Section Access Hinged Door on Hand Side Removable Panels INLET _ X = Standard configuration Hinged Access on Both Sides INLET Blow-thru supply section with rear inlet, diffuser and external bypass return Vertical fan section with bottom inlet Fig. 5 -- Component @ Plenum fan Drawings 12 (Refer to Table 1) XXXXXX XXXXXX XXXXXX Number Table 1 -- 39MN,MW Component Nominal cfm at 500 fpm Unit Size 1500 Weights and Lengths SECTION 3000 03 DIMENSIONS lin,! 4000 AND WEIGHTS 5000 06 08 10 Indoor 39 42 42 Outdoor 43 45 45 !lb) 6000 7OOO 12 14 8500 17 79 H (in.) Refer Mixing 2 Side inlet 3 Filter 4 Air 5 Exhaust 46 54 67 67 72 Outdoor 36 49 57 70 70 75 AWL (in.) (Indoor/Outdoor / Weight box mixing mixing (Ih / box box mixer box Side outlet 7 33 to Fig. 5 1 6 W (in,) Indoor Integral exhaust face and box bypass heating coil section 21 330/450 21 370/510 21 420/570 21 460/610 24 520/590 24 570/750 21 300/410 27 350/490 27 390/540 33 470/650 33 510/690 39 580/780 39 640/860 36 320/450 36 380/530 36 430/590 36 490/680 35 540/730 36 570/770 36 630/840 18 170/270 18 190/310 18 210/340 24 270/430 24 290/450 24 300/470 30 380/570 18 160/260 21 190/310 21 210/350 21 230/380 21 250/400 24 250/450 24 300/480 21 300/410 27 360/490 27 390/540 33 470/650 33 510/690 39 580/780 39 640/860 48 250/400 48 280/450 48 310/500 48 340/560 48 360/580 48 380/510 48 410/650 18 130/230 18 150/270 18 170/300 18 190/340 18 200/350 18 210/360 18 230/390 8 Internal 9 External face 18 140/-- 21 160/-- 21 180/-- 21 190/-- 21 200/-- 24 220/-- 24 240/-- Plenum section -- 12 in. 12 120/210 12 140/250 12 150/270 12 170/300 12 180/310 12 190/330 12 200/350 Plenum section -- 24 in. 24 170/280 24 190/320 24 210/350 24 230/390 24 240/400 24 250/420 24 270/450 36 in. 36 210/340 36 240/390 36 260/420 36 280/470 36 300/490 36 310/510 36 340/550 in. 48 250/400 48 280/450 48 310/500 48 340/550 48 360/580 48 380/610 48 410/650 face and bypass and damper bypass section damper section 10 Plenum section Plenum 12 -- section --48 Humidifier section -- 24 in. 24 247/360 24 290/420 24 330/470 24 370/530 24 410/570 24 420/590 24 470/650 Humidifier section -- 36 in. 36 287/410 36 340/490 36 380/540 36 420/610 36 460/650 36 490/690 36 540/750 Humidifier section -- 48 in. 48 327/470 48 380/550 48 430/620 48 480/700 48 520/740 48 550/780 48 600/840 18 140/-- 18 160/-- 18 170/-- 18 180/-- 18 190/-- 24 220/-- 24 240/-- 24 170/280 24 200/330 24 220/360 24 240/400 24 260/420 24 270/440 24 300/480 FC 24 150/-- 30 190/-- 36 230/-- 36 260/-- 42 320/-- 46 360/-- 48 410/-- AF 42 210/-- 42 240/-- 36 250/-- 36 280/-- 42 340/-- 48 380/-- 48 420/-- Fan 25 150/-- 28 180/-- 22 180/-- 22 200/-- 25 230/-- 25 240/-- 25 260/-- 12 190/280 12 230/340 12 260/380 12 300/430 12 330/460 12 340/480 12 380/530 24 230/340 24 270/400 24 310/450 24 350/510 24 390/550 24 400/570 24 450/630 24 230/340 24 270/400 24 310/450 24 350/510 24 390/550 24 400/570 24 450/630 42 300/440 42 350/510 42 390/570 42 440/540 42 480/680 42 500/710 42 560/780 33 300/-- 33 340/-- 36 380/-- 36 420/-- 48 490/-- 48 520/-- 48 550/-- 48 320/470 48 370/540 48 420/610 48 470/690 48 510/730 48 540/770 48 590/830 48 320/470 48 370/540 48 420/610 48 470/690 48 510/730 48 540/770 48 590/830 pan 24 170/280 24 190/320 24 210/350 24 230/390 24 240/400 24 250/420 24 270/450 section 42 230/370 42 260/420 42 290/470 42 310/510 42 340/540 42 350/560 42 380/600 12 120/210 12 140/250 12 150/270 12 170/300 12 180/310 12 190/330 12 200/350 24 170/280 24 190/320 24 210/350 24 230/390 24 240/400 24 250/420 24 270/450 36 200/-- 35 230/-- 36 250/-- 35 270/-- 42 310/-- 42 320/-- 42 350/-- 36 210/340 35 240/390 36 260/420 35 280/470 36 300/490 36 310/510 36 340/550 24/30 180/300 30135 240/390 30136 280/440 30136 320/510 30136 350/540 30136 370/570 30135 410/620 36/42 180/320 35142 220/380 42/48 290/480 42/48 340/560 42148 380/600 42148 400/530 42148 450/690 30 200/320 30 220/360 30 250/400 30 270/440 36 320/510 36 330/530 36 370/580 61 48 570/-- 64 48 620/-- 64 48 690/-- 71 50 820/-- 71 50 850/-- 74 60 920/-- External 13 Horizontal 14 Vertical _lenum bypass return blow-thru section discharge blow-thru section plenum section discharge Plenum 15 Horizontal 16 2 in. or 4 in. side Horizontal angle 17 2 in. or 4 in. side Ioadin_l Horizontal bag/cartridge filter section, SL 6 in. or 12 in. media with 2 in. pre-filter track flat filter section Ioadin_ filter section Horizontal bag/cartridge filter section, 15 in. or 30 in. media with 2 in. pre-filter SL track Vertical bag/cartridge filter section, SL 6 in. or 12 in. media with 2 in. pre-filter track Horizontal bag/cartridge filter section, EL Face loading media with or without header 18 19 20 Horizontal 21 Cooling 22 coil Extended box HEPA section length Heating 24 blow-thru coil Extended 23 cooling heating length heating 25 Dual section with Electric control drain coil Extended 27 section, with FL drain pan section length coil filter with 25 heat box section coil section coil drain section and with electric heat 28 Horizontal blow 29 Multizone/dual heating/cooling 30 MuIBzone 31 Vertical 32_ 33_ 34_ 35_ 36 duct coil damper coil section coil (indoor with ducted section Low Amp (in.) / Outdoor / lib} High Amp (in.) / Outdoor) (Ib) discharge H (in,) AWL (in.) Indoor / Outdoor section with remote pan with thru with EBR (indoor / Weight lib/ Number drain 11 7 11 10 11 10 11 10 11 12 42 290/-- 36 290/-- 36 320/-- 42 370/-- 48 420/-- 48 460/-- EC 24 480/590 30 550/690 36 640/800 36 700/890 42 810/1010 48 910/1140 48 990/1230 AF 42 550/690 42 620/780 36 640/800 36 700/890 42 810/1010 48 900/1130 48 990/1230 AF 42 550/690 42 620/780 42 570/550 42 740/940 48 850/1070 54 940/1180 54 1030/1290 42 560/-- 42 630/-- 36 660/-- 36 720/-- 42 840/-- 48 940/-- 48 1030/-- 48 600/770 54 720/900 42 720/900 42 800/1000 48 940/1160 48 980/1210 48 1080/1320 pan Fan sections Vertical 37 11 6 42 250/-- AWL of Zones Downblast Plenum fan section FC/AF LEGEND AF AWL EBR FC FL H SL W 82 18 270/370 --------- NOTES: Airfoil Aint_ayLength External Bypass Return Forward Curved Face Load Height Side Lead Width 1. • 3. 4. 13 Refer to Section weights• Section All bold the Aero Product Data weights do not include Catalog for additional application information• coils or motors• Refer to the product data catalog height is the same except as noted• numbers are inches, non-hold are pounds unless otherwise noted• for additional Table 1 -- 39MN,MW Component 10,500 Weights and Lengths (cont) SECTION DIMENSIONS lin.! AND WEIGHTS !lb) 12,500 15,000 18,000 21 Refer Mixing 2 Side inlet 3 Filter mixing 4 Air mixer 5 Exhaust 6 Side 7 and face and heating bypass 73 79 66 77 83 104 108 Outdoor 82 89 107 112 112 120 27 710/900 27 760 / 960 27 870 / 1090 1320 36 / 1580 39 1520/1700 42 1920/2220 51 2650/2080 39 710/930 45 830 / 1080 1050 51 / 1350 1300 57 / 1690 57 1460/1700 63 1870/2240 63 2140/2510 36 720 / 930 36 760 / 980 36 880 / 1130 1260 45 / 1550 48 1430/1730 51 1790/2120 60 2390/2750 30 430 / 620 30 460 / 060 36 600 / 850 36 720 / 080 42 870/1150 42 1030/1330 48 1330/1650 27 370 / 560 27 390 / 590 27 440 / 060 36 650 / 010 59 750/1020 42 930/1230 51 1270/1600 39 710/930 45 830 / 1080 51 1050 / 1350 57 1360 / 1690 57 1460/1790 63 1870/2240 63 2140/2510 coil section 48 450 / 600 48 470 / 720 48 530 / 820 48 620 / 920 48 650/950 48 750/1070 48 850/1170 section 18 250/410 18 270 / 440 18 300 / 500 18 350 / 550 18 380/580 18 440/650 18 490/700 lib} 117 120 8 Internal 9 External face 27 300 / -- 27 330 / -- 33 450 / -- 53 470/-- 39 630/-- 45 810/-- Plenum section -- 12 in. 12 220 / 370 12 230 / 380 12 260 / -- 12 310 / 490 12 320/500 12 370/560 12 420/610 Plenum section -- 24 in. 24 300 / 480 24 320/510 24 350 / -- 24 410 / 630 24 430/650 24 490/730 24 550/790 36 in. 36 380 / 500 36 400 / 020 36 440 / 690 56 510 / 770 36 540/800 35 020/900 36 700/980 48 in. 48 450 / 690 48 470 / 720 48 530 / 820 48 620 / 020 48 650/950 48 750/1070 48 850/1170 24 / 860 and damper 62 66 117 box bypass 62 109 box face 61 109 box Integral 50 104 box exhaust 40 86 AWL (in.) /IndooUOutdoor} Wei_lht outlet 30,500 36 79 box mixing 25,000 30 Indoor to Fig. 5 1 20,000 25 bypass damper section 280 10 Plenum section Plenum 11 12 -- section -- Humidifier section -- 24 in, 24 530/710 24 560 / 750 644 24 770 / 000 24 820/1040 24 950/1190 24 1090/1330 Humidifier section -- 36 in, 35 600/810 36 640 / 860 36 734 / 990 36 570 / 1130 36 930/1190 35 1080/1360 36 1230/1510 Humidifier section --48 48 680 / 920 48 720 / 970 48 824 / 1120 48 070 / 1270 48 1040/1340 48 1210/1530 48 1380/1700 24 270 / -- 24 280 / -- 27 420/-- 30 520/-- 33 630/-- External 13 Horizontal 14 Vertical _lenum bypass in, return b]ow-thru section discharge plenum 30 380 / 570 section FC blow-thru section 15 Horizontal flat filter section 2 in. or 4 in. side loading 16 Horizontal angle filter section 2 in. or 4 in. side Ioadin_ Horizontal bag/cartridge filter section, Vertical bag/cartridge filter section, 0 in. or 12 in. media with 2 in. pre-filter 53 590 / 840 33 630/880 36 790/1070 36 000/1180 50 700 / -- 60 860 / -- 60 920/-- 66 1200/-- 66 1400/-- 60 610/-- 60 700 / -- 60 850 / -- 66 990/-- 72 1270/-- 78 15801-- Far 28 320 / -- 28 340 / -- 28 380 / -- 40 600 / -- 40 050/-- 40 770/-- 45 1000/-- 12 630/810 12 680/860 12 800/990 12 910/1100 SL 48 / -- 30 460 / 690 50 600 / -- 6 in. or 12 in. media with 2 in. pre-filter track Horizontal bag/cartridge filter section, SL 15 in. or 30 in. media wBth 2 in. pre-filter track 18 30 410/610 24 360/-- 48 480 / -- discharge Plenum 24 310/-- AF 470 17 27 / -- 12 430 / 580 12 460/010 12 530/710 24 510/600 24 540 / 730 620 24 / 830 24 740 / 960 24 790/1010 24 920/1160 24 1060/1300 24 510/600 24 540 / 730 24 620 / 830 24 740 / 960 24 790/1010 24 920/1160 24 1060/1300 42 630 / 850 42 670/910 42 700 / 1030 42 900 / 1180 42 960/1240 42 1120/1420 42 1270/1570 72 910/-- 84 1090/-- 96 1210/-- 60 630 / -- SL track 60 670 / -- 60 760/-- 72 910/-- Horizontal bag/cartridge filter section, FL Face loading media with or without header 48 070/910 48 710/960 48 810 / 11 O0 48 960 / 1260 48 1020/1320 48 1190/1510 48 1360/1680 20 Horizontal 48 670/910 48 710/960 48 810 / 11 O0 48 960 / 1260 48 1020/1320 48 1190/1510 48 1360/1680 21 Cooling pan 24 300 / 480 24 320/510 350 24 / 560 24 410 / 630 24 430/650 24 490/730 24 550/790 section 48 450 / 690 48 480 / 730 48 540 / 830 48 630 / 930 54 730/1050 60 930/1290 72 1230/1630 12 220 / 370 12 230 / 380 12 260 / 440 12 310 / 400 12 320/500 12 370/560 12 420/010 24 300 / 480 24 320/510 24 350 / 560 24 410 / 630 24 430/650 24 490/730 24 550/700 60 890/-- 72 1180/-- 19 22 blow-thru coil Extended 23 24 coil Extended box 25 Extended 26 Dual 27 with cooling filter drain coil section, FL with drain heating length heating section heat box with section coil section coil drain and section with electric Horizontal blow Multizone/dua] 29 heating/cooling 30 Multizone 31 Vertical ndoo 32, 33, 34_ 35_ 36 with ducted coil section section Indoor section with remote 48 450 / -- 36 380 / 590 36 400 / 620 440 36 / 690 36 510 / 770 30135 470 / 080 30136 500 / 720 30135 580 / 830 30 / 42 700 / 980 30142 740/1020 30142 880/1180 30142 1010/1310 42148 530 / 770 42148 560/810 42148 660 / 950 42 / 54 800 / 1120 42/54 860/1180 42154 1020/1360 42154 1180/1520 42 460 / 080 42 490 / 730 42 550 / 820 48 740 / 1040 54 840/1160 60 1080/1440 72 1420/1820 90 72 1180/-- 90 72 1250/-- 90 72 1430/-- 107 90 2030/-- 119 102 2630/-- 140 120 3500/-- 11 12 11 13 11 16 11 17 11 17 11 18 11 18 48 510/-- 60 630/-- 60 722/-- 60 860/-- 66 980/-- 72 1240/-- 78 1520/-- FC 48 1100/1340 60 1360/1650 60 1560/1890 60 1840/2180 60 1960/2300 65 2480/2860 66 2830/3210 AF 48 1100/1340 60 1360/1650 60 1560/1890 60 1840/2180 65 2120/2480 72 2670/3070 78 3270/3700 AF 54 1150/1410 66 1400/1700 56 1600/1950 60 1750/2000 65 2010/2370 72 2520/2020 78 3080/3510 48 1160/-- 60 1440/-- 60 1650/-- 60 1950/-- 65 2250/-- 72 2840/-- 78 3500/-- 54 1400/1670 54 1610/1920 65 2240/2600 72 2580/2960 72 3040/3440 78 3740/4170 Low Amp AWL (in.', /Oudoo Wegh High Amp AWL / Outdoor) Weight (b' (in., (Ib', H (in,) AWL (in,) / Ou door / Wei{lh Number drain (Ib / AWL (in, I of Zones pan Fan sections Downblast Vertical 37 48 430 / -- discharge duct damper coil coil with pan with thru heat EBR (indoor 28 pan section length coil Electric control section length Heating HEPA Plenum fan section FC/AF 54 1320 / 1580 LEGEND AF AWL EBR FC FL ----- Airfoil Airway Length External Bypass Forward Curved Face Load H SL W ---- Height Side Load Width 48 510/-- 48 600/-- 54 700 / -- 101 84 18401-- 0 0 0 NOTES: . • Return 3. 4. 14 Refer to Section weights• Section All bold the Aero Product Data weights do not include Catalog for additional application information• coils or motors. Refer to the product data catalog height is the same except as noted• numbers are inches, non-bold are pounds unless otherwise noted• for additional Table 2A -- Physical Data -- Airfoil Fans (Supply, Return and Exhaust) 39M UNIT SIZE WHEEL TYPE..SIZE WHEEL DIAMETER (in.) AIl...Std All...Std 10 3 6.13 I MIN INLET CONE DIAMETER (in.) 121/4 06 7.5 AIhStd AIl...Std AlhStd AIl...Std AIl...Std All...Std AIl...Std AIl...Std 131/2 10 8.38 161/2 12 10.13 161/2 14 10.13 181/4 17 11.00 20 21 12.44 221/4 25 13.88 221/4 30 13.88 131/2 08 8.38 MAX SPEED (rpm) Class I 1872 Class II 2442 FAN SHAFT DIAMETER Class I (in.) 115/16 Class II 23/16 FAN WHEEL WEIGHT (Ib) Class I Class II 73.0 73.0 No. Fan Blades 9 MOTOR FRAME SIZE Maximum (ODP/TEFC) 324T Minimum (ODP/TEFC) MOTOR HP 182T Maximum 4O Minimum 3 36 WHEEL TYPE..SIZE 3gM UNIT SIZE Supply...Std WHEEL DIAMETER (in.) MIN INLET CONE DIAMETER (n.) MAX SPEED (rpm) Class I Class II FAN SHAFT DIAMETER Class I Ret/Exh...Std 27 1613/le Supply...Std 27 61 50 Ret/Exh...Std 3O Supply...Std Ret/Exh...Std Supply...Stc Ret/Exh...Std 30 33 33 361/2 209/16 209/1G 231/8 1613/le 1813/le 1813/le 1700 I 2123 1910 1910 1715 1715 1202112o211 1568 1568 1378 27/16 27/lC 2Z/lc 211/16 211/16 23/16 23/lC 23/lC (in.) Class II FAN WHEEL WEIGHT Class I 241/2 15/8 40 (Ib) 88 Class II 91 No. Fan Blades 18 11o411o4 106 106 148 145 176 176 233 18 18 18 18 18 18 18 182T 184T 182T 213T 184T 213T 184T 3 3 3 71/2 5 71/2 5 MOTOR FRAME SIZE Maximum (ODP/TEFC) Minimum (ODP/TEFC) MOTOR HP 184T Maximum 50 Minimum 5 i LEGEND ODP Ret/Exh TEFC -- Open Dripproof -- Return Exhaust -- Totally Enclosed Fan Cooled NOTE: Data is for 50 Hz and 60 Hz motors. 15 0tl 0 tl 0t 18160 2o17812o Table 2B -- Physical Data -- Plenum Fans (Supply, Return and Exhaust) 3gM UNIT SIZE WHEEL TYPE...SIZE WHEEL DIAMETER (in.) MIN INLET CONE DIAMETER (in,) MAX SPEED (rpm) I 03 AlhStd 06 AIl...Std 08 AIL..Std 10 AIl...Std 12 AIl...Std 14 AIl...Std 17 AIl...Std 21 AIL..Std 25 AIL..Std 121/4 16 161/2 181/4 221/4 221/4 241/2 27 30 7.5 9.25 10.13 11.88 12.14 12.14 15.81 17.5 19.69 3O AIl...Std 33 21.49 Class I 1202 Class II 1568 FAN SHAFT DIAMETER (in,) Class I 111/1G Class II 111/16 FAN WHEEL WEIGHT (Ib) Class I Class II 135 135 No. Fan Blades 12 MOTOR FRAME SIZE Maximum (ODP/TEFC) 286T Minimum (ODP/TEFC) MOTOR HP 182T Maximum 30 Minimum 3 39M UNIT SIZE WHEEL TYPE._SIZE WHEEL DIAMETER (in,) 36 AIl...Std 361/2 40 50 Supply...Std Ret/Exh...Std 361/2 401/4 24 24 265/8 1055 1378 1055 1378 955 1249 111/1G 111/16 111/1G 111/16 MIN INLET CONE DIAMETER (in.) Supply...Std 401/4 61 Ret/Exh...Std Supply...Std 441/2 441/2 265/8 291/2 I 955 1249 865 1131 115/1G I 115/16 115/1G I 115/16 Ret/Exh...Std 49 291/2 321/2 I 865 1131 808 1050 23/16 I 23/16 211/16 23/16 I 23/16 211/16 MAX SPEED (rpm) Class I Class II FAN SHAFT DIAMETER (in.) Class I Class II FAN WHEEL WEIGHT (Ib) Class I 171 171 203 203 277 277 366 171 171 203 203 277 277 366 12 12 12 12 12 12 12 3247 162T 324T 184T 213T 2867 184T Maximum 40 40 20 I 50 25 I 60 30 Minimum 3 5 3 I 71/2 5 I 71/2 6 Class II No. Fan Blades MOTOR FRAME SIZE Maximum (ODP/TEFC) (ODP/TEFC) Minimum MOTOR HP 256713267 182T LEGEND ODP Ret/Exh TEFC ---- Open Dripproof Return Exhaust Totally Enclosed Fan Cooled NOTE: Data is for 50 Hz and 60 Hz motors. 16 213T 284713647 184T Table 2C -- Physical Data -- Forward-Curved 39M UNIT SIZE WHEEL SIZE WHEEL DIAMETER (in.) MIN INLET CONE DIAMETER MAX SPEED (rpm) Class I Class II FAN SHAFT DIAMETER Class I (in.) I 03 06 Std Std 91/2 7.81 1OS/s 8.81 08 Std 10 I Small 12s/8 ] 10.38 1OS/8 8.81 Fans (Supply) 12 14 17 21 Std Small Std Small Std I Small Std I Small Std Small 15 12.12 12s/s 10.38 15 12.62 12s/s 10.38 18 15.5 ] 12.62 15 18 15.5 ] 12.62 15 20 16.25 15 12.62 1262 1639 (in.) 111/16 Class II 111/16 12.8 Fan Shaft Weight (Ib) Class II FAN WHEEL WEIGHT (Ib) Class I Class II No. Fan Blades MOTOR FRAME SIZE Maximum (ODP/TEFC) Minimum (ODP/TEFC) MOTOR HP Maximum Minimum 16.2 16.9 51 184T 184T 213T1 213T 56 143T 143T 182T ]213TI215T 145T 184T 1213T1 254T 1213T1 254T 1215T1 254T ]254TI284T 145T 184T 145T 184T 182T 213T 182T 25 10 39M UNIT SIZE WHEEL SIZE WHEEL DIAMETER 61 Std (in.) MIN INLET CONE DIAMETER MAX SPEED (rpm) Class I Class II FAN SHAFT DIAMETER Class I 215T (in.) Small Std 20 2i 20 I 1625 1625 Small Std Small Std Small 20 30 20 1625 1625 25 36 223/8 25 25 215/16 181/16 40 215/16 Std 275/8 50 215/16 2315/16 Small Std 27s/s 231_16 301/4 275/8 263/8 2315/16 Small 656 865 (in.) 111/16 Class II 27/16 71,8 Fan Shaft Weight (Ib) Class II FAN WHEEL WEIGHT (Ib) Class I Class II No. Fan Blades MOTOR FRAME SIZE Maximum (ODP/=rEFC) Minimum (ODP/TEFC) MOTOR HP Maximum Minimum 111.0 111.0 37 254T 284T 184T 215T ] 256T 184T ] 286T ] 256T ] 286T ] 284T 215T 182T 254T 184T 286T 254T ] 286T 184T ] 324T ] 324T 254T 184T ] 326T 256T 5O 2O LEGEND ODP -TEFC -- ] Open Dripproof Totally Enclosed Fan Cooled NOTE: Data is for 50 Hz and 60 Hz motors. 17 Table 2D -- Physical Data -- Forward-Curved 39M UNIT SIZE WHEEL SIZE WHEEL DIAMETER (in.) MIN INLET CONE DIAMETER MAX SPEED (rpm) Class I Class II FAN SHAFT Class I DIAMETER I (in,) Std 08 Std 10 Std 12 Std Fan Shaft Weight (Ib) Class II FAN WHEEL WEIGHT (Ib) Class I Class II No. Fan Blades MOTOR FRAME SIZE Maximum (ODP/TEFC) Minimum (ODPFrEFC) MOTOR HP Maximum Minimum 91/2 03 7.81 105& 8.81 12_s 10.38 15 12.62 2132 2749 1806 2347 1533 1986 1262 1639 1 13/16 1!9 39M UNIT SIZE 13/16 1 13/16 4.2 7.7 13/16 8.7 3,8 3,8 43 5,8 5,8 48 10,0 10,4 43 16.2 16.9 51 184T 86 184T 56 213T 56 213T 143T 30 17 Std 18 15.50 21 Std 20 16.25 25 Std 20 16.25 1262 1639 1097 1378 1097 1378 952 1237 952 1237 I 13/16 13/16 13/16 13/16 8.7 Std I I FAN SHAFT DIAMETER Class I 20 16.25 960 1217 25 215/16 I 751 960 _ 17/16 15.2 15.2 16.2 16.9 51 32.0 34.2 48 32.0 34.2 48 42.0 44.9 51 42.0 44.9 51 213T 145T 213T 145T 215T 254T 145T 145T t 145T 18 2 50 275/8 2315/16 254T i 71/2 11/2 Std 25 215/16 I I 61 Std Small I 27s/8 2315/16 _ Small 301_ 275/8 263/8 231_16 618 793 } 656 865 (in,) Class II Fan Shaft Weight (Ib) Class II FAN WHEEL WEIGHT (Ib) Class I Class II No. Fan Blades MOTOR FRAME SIZE Maximum (ODP/TEFC) Minimum (ODP/TEFC) MOTOR HP Maximum Minimum 111/16 111/16 111/16 111/16 111/16 27/16 23/16 27/16 27/16 27/16 27/16 23.5 61.1 42.4 60.3 53.3 71.8 64,5 53,0 81 .O 63.0 53,0 81 .O 63.0 81.0 81.0 37 73.0 73.0 37 111.0 111.0 37 101.0 101.0 37 37 I 17/16 I I 111/16 37 37 256T 256T 286T 182T 182T 254T 284T 184T 286T 254T 286T 184T 20 20 30 25 30 30 3 3 15 5 15 5 LEGEND Open Dripproof Totally Enclosed 17/16 14.9 Small 25 215/16 223/8 181/16 I 14,9 (in,) (in,) 17/16 17/16 40 Std Small 13/16 13/16 71/2 11/2 36 Std MIN INLET CONE DIAMETER MAX SPEED (rpm) Class I Class II --- I 3/4 WHEEL SIZE ODP TEFC 15 12.62 14 Std 18 15.50 (in.) Class II WHEEL DIAMETER Fans (Return and Exhaust) 06 Std I NOTE: Dataisfer50 Fan Cooled 18 Hzand I I 111/16 324T 254T 60 Hz motors. I I 111/16 1 _1/16 211/16 90.1 27/16 71.8 128.0 128.0 37 111.0 111.0 37 324T 184T I I 326T 256T 40 40 I 50 15 5 I 20 Table 339M UNIT SIZE 1/2-in. CHILLED WATER/DIRECT 03 08 08 10 Coil Data 12 14 17 21 25 30 38 40 50 81 EXPANSION Large Face Area Nominal 1,736 2,951 3,819 4,965 6,319 7,170 8,464 10,720 12,205 15,174 18,333 20,000 25,278 30,694 Lower Coil Height (in,) 25 25 27.5 27.5 35 35 37.5 47.5 47.5 47.5 55 30 35 42.5 Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 35 42.5 Length (in,) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) 3.5 5.9 7.6 9.9 12.6 14.3 16.9 21.4 24.4 30.3 36.7 40.0 50.6 61.4 Medium Capacity (cfm) at 500 fpm Face Area 1,215 2,066 2,778 3,611 4,965 6,146 6,771 9,028 10,278 12,778 15,000 18,333 19,861 25,278 Lower Coil Height (in,) 17.5 17.5 20 20 27.5 30 30 40 40 40 45 55 55 35 Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 35 Length (in,) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.4 4.1 5.6 7.2 9.9 12.3 13.5 18.1 20.6 25.6 30.0 36.7 39.7 58.6 19,861 Nominal Capacity (cfm) at 500 fpm Total Face Area (sq ft) Bypass Only) Face Area (Internal Chilled Water 1,042 1,771 2,431 3,160 4,514 5,122 6,207 7,899 8,993 11,181 12,500 15,000 16,250 Height (in,) 15 15 17.5 17.5 25 25 27.5 35 35 35 37.5 45 45 55 Length (in.) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) 2.1 3.5 4.9 6.3 9.0 10.2 12.4 15.8 18.0 22.4 25.0 30.0 32.5 39.7 Nominal Capacity (cfm) at 500 fpm 1/2-in. HOT WATER HEATING Large Face Area Nominal 2,431 4,132 5,347 6,951 8,847 10,038 11,849 15,009 17,087 21,243 25,667 28,000 35,389 42,972 Lower Coil Height (in.) 25 25 27.5 27.5 35 35 37.5 47.5 47.5 47.5 55 30 35 42.5 Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 35 42.5 Length (in,) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) 3.5 5.9 7.6 9.9 12.6 14.3 16.9 21.4 24.4 30.3 36.7 40.0 50.6 61.4 Medium Capacity (cfm) at 700 fpm Face Area 1,701 2,892 3,889 5,056 6,951 8,604 9,479 12,639 14,389 17,889 21,000 25,667 27,806 35,389 Lower Coil Height (in,) 17.5 17.5 20 20 27.5 30 30 40 40 40 45 55 55 35 Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 35 Length (in,) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) 2.4 4.1 5.6 7.2 9.9 12.3 13.5 18.1 20.6 25.6 30.0 36.7 39.7 58.6 2,917 3,792 Nominal Capacity (cfm) at 700 fpm Small Face Area -- 2,479 4,424 5,019 6,319 7,109 8,094 10,063 14,000 14,000 17,694 21,486 Height (in,) -- 15 15 15 17.5 17.5 20 22.5 22.5 22.5 30 30 35 42.5 Length (in,) -- 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) -- 3.5 4.2 5.4 6.3 7.2 9.0 10.2 11.6 14.4 20.0 20.0 25.3 30.7 27,806 Nominal Capacity (cfm) at 700 fpm Bypass Face Area (Internal) 1,458 2,479 3,403 4,424 6,319 7,170 8,689 11,059 12,590 15,653 17,500 21,000 22,750 Height (in,) 15 15 17.5 17.5 25 25 27.5 35 35 35 37.5 45 45 55 Length (in,) 20 34 40 52 52 59 65 65 74 92 96 96 104 104 Total Face Area (sq ft) 2.1 3.5 4.9 6.3 9.0 10.2 12.4 15.8 18.0 22.4 25.0 30.0 32.5 39.7 Nominal 5/8-in. STEAM Capacity (cfm) at 700 fpm HEATING Large Face Area Nominal 2,333 3,967 5,250 6,825 8,342 9,465 11,375 14,219 16,188 -- Lower Coil Height (in,) 24 24 27 27 33 33 36 45 45 -- Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A -- Length (in,) 20 34 40 52 52 59 65 65 74 -- Total Face Area (sq ft) 3.3 5.7 7.5 9.8 11.9 13.5 16.3 20.3 23.1 -- 3,500 4,550 Medium Capacity (cfm) at 700 fpm Face Area Nominal 1,458 2,479 6,825 8,604 9,479 12,323 14,029 -- Lower Coil Height (in,) Capacity (cfm) at 700 fpm 15 15 18 18 27 30 30 39 39 -- Upper Coil Height (in,) N/A N/A N/A N/A N/A N/A N/A N/A N/A -- Length (in.) 20 34 40 52 52 59 65 65 74 -- Total Face Area (sq ft) 2.1 3.5 5.0 6.5 9.8 12.3 13.5 17.6 20.0 -- 2,917 3,792 3,792 4,302 5,688 Small Face Area -- 2,479 6,635 7,554 Height (in.) -- 15 15 15 15 15 18 21 21 Length (in,) -- 34 40 52 52 59 65 65 74 Total Face Area (sq ft) -- 3.5 4.2 5.4 5.4 6.1 8.1 9.5 10.8 2,917 3,792 Nominal Capacity (cfm) at 700 fpm Bypass Face Area (Internal) 1,458 2,479 6,067 6,883 8,531 10,427 11,871 Height (in,) 15 15 15 15 24 24 27 33 33 Length (in,) 20 34 40 52 52 59 65 65 74 Total Face Area (sq ft) 2.1 3.5 4.2 5.4 8.7 9.8 12.2 14.9 17.0 Nominal Capacity (cfm) at 700 fpm 19 Table 3 -- Coil Data (cont) 39M UNIT SIZE s&-In. CHILLED 03 08 08 10 12 14 17 21 28 30 38 40 50 81 WATER Large Face Area Nominal Capacity 1,667 2,833 3,750 5,958 6,760 8,125 10,156 11,563 14,375 18,000 20,000 24,917 30,333 Lower Coil Height (in.) 24 24 27 27 33 33 36 45 45 45 54 30 36 42 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 33 42 20 34 40 52 52 59 65 65 74 92 96 96 104 104 3.3 5.7 7.5 9.8 11.9 13.5 16.3 20.3 23.1 28.8 36.0 40.0 49.8 60.7 2,500 3,250 Length (cfm) at 500 fpm (in.) Total Face Area (sq It) Medium 4,875 Face Area 1,042 1,771 4,875 6,146 6,771 8,802 10,021 12,458 15,000 18,000 19,500 24,917 Lower Coil Height (in.) 15 15 18 18 27 30 30 39 39 39 45 54 54 36 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 33 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 5.0 6.5 9.8 12.3 13.5 17.6 20.0 24.9 30.0 36.0 39.0 49.8 2,083 2,708 19,500 Nominal Length Capacity (cfm) at 500 fpm (in.) Total Face Area (sq It) Bypass Face Area (Internal Chilled Water Only) Nominal Capacity (cfm) at 500 fpm 1,042 1,771 4,333 4,917 6,094 7,448 8,479 10,542 12,000 15,000 16,250 Height (in.) 15 15 15 15 24 24 27 33 33 33 36 45 45 54 Length 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 4.2 5.4 8.7 9.8 12.2 14.9 17.0 21.1 24.0 30.0 32.5 39.0 2,333 6,825 (in.) Total Face Area (sq It) 5&-In. HOT WATER HEATING Large Face Area 3,967 5,250 8,342 9,465 11,375 14,219 16,188 20,125 25,200 28,000 34,883 42,467 Lower Coil Height (in.) 24 24 27 27 33 33 36 45 45 45 54 30 36 42 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 33 42 20 34 40 52 52 59 65 65 74 92 96 96 104 104 3.3 5.7 7.5 9.8 11.9 13.5 16.3 20.3 23.1 28.8 36.0 40.0 49.8 60.7 3,500 4,550 Nominal Length Capacity (cfm) at 700 fpm (in.) Total Face Area (sq It) Medium Face Area Nominal Capacity 1,458 2,479 6,825 8,604 9,479 12,323 14,029 17,442 21,000 25,200 27,300 34,883 Lower Coil Height (in.) 15 15 18 18 27 30 30 39 39 39 45 54 54 36 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 33 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 5.0 6.5 9.8 12.3 13.5 17.6 20.0 24.9 30.0 36.0 39.0 49.8 2,917 3,792 3,792 4,302 21,233 Length (cfm) at 700 fpm (in.) Total Face Area (sq It) Small Face Area -- 2,479 5,688 6,635 7,554 9,392 14,000 14,000 16,683 Height (in.) -- 15 15 15 15 15 18 21 21 21 30 30 33 42 Length -- 34 40 52 52 59 65 65 74 92 96 96 104 104 -- 3.5 4.2 5.4 5.4 6.1 8.1 9.5 10.8 13.4 20.0 20.0 23.8 30.3 2,917 3,792 27,300 Nominal Capacity (cfm) at 700 fpm (in.) Total Face Area (sq It) Bypass Face Area (Internal) Nominal Capacity (cfm) at 700 fpm 1,458 2,479 6,067 6,883 8,531 10,427 11,871 14,758 16,800 21,000 22,750 Height (in.) 15 15 15 15 24 24 27 33 33 33 36 45 45 54 Length 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 4.2 5.4 8.7 9.8 12.2 14.9 17.0 21.1 24.0 30.0 32.5 39.0 2,333 6,825 (in.) Total Face Area (sq It) l-In. STEAM HEATING Large Face Area Nominal Capacity 3,967 5,250 8,342 9,465 11,375 14,219 16,188 20,125 25,200 28,000 34,883 42,467 Lower Coil Height (in.) 24 24 27 27 33 33 36 45 45 45 54 30 36 42 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 33 42 20 34 40 52 52 59 65 65 74 92 96 96 104 104 3.3 5.7 7.5 9.8 11.9 13.5 16.3 20.3 23.1 28.8 36.0 40.0 49.8 60.7 3,500 4,550 Length (cfm) at 700 fpm (in.) Total Face Area (sq It) Medium Face Area 1,458 2,479 6,825 8,604 9,479 12,323 14,029 17,442 21,000 25,200 27,300 34,883 Lower Coil Height (in.) 15 15 18 18 27 30 30 39 39 39 45 54 54 36 Upper Coil Height (in.) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 33 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 5.0 6.5 9.8 12.3 13.5 17.6 20.0 24.9 30.0 36.0 39.0 49.8 2,917 3,792 3,792 4,302 21,233 Nominal Length Capacity (cfm) at 700 fpm (in.) Total Face Area (sq It) Small Face Area -- 2,479 5,688 6,635 7,554 9,392 14,000 14,000 16,683 Height (in.) -- 15 15 15 15 15 18 21 21 21 30 30 33 42 Length -- 34 40 52 52 59 65 65 74 92 96 96 104 104 -- 3.5 4.2 5.4 5.4 6.1 8.1 9.5 10.8 13.4 20.0 20.0 23.8 30.3 2,917 3,792 27,300 Nominal Capacity (cfm) at 700 fpm (in.) Total Face Area (sq It) Bypass Face Area (Internal) Nominal Capacity (cfm) at 700 fpm 1,458 2,479 6,067 6,883 8,531 10,427 11,871 14,758 16,800 21,000 22,750 Height (in.) 15 15 15 15 24 24 27 33 33 33 36 45 45 54 Length 20 34 40 52 52 59 65 65 74 92 96 96 104 104 2.1 3.5 4.2 5.4 8.7 9.8 12.2 14.9 17.0 21.1 24.0 30.0 32.5 39.0 30,500 (in.) Total Face Area (sq It) 5/_-In. HOT WATER IFB Integral Face and Bypass -- 3,000 4,000 5,000 6,000 7,000 8,500 10,500 12,500 15,000 18,000 20,000 25,000 Coil Height (in.) -- 22.9 30.6 30.6 30.6 30.6 24 33 33 33 45 51 60 75 Length -- 24 30 39 39 45 59.4 59.4 59.4 81.4 81.4 81.4 92.4 92.4 -- 3.3 5.7 7.4 7.4 8.5 9.2 12.6 12.6 17.6 24.1 27.3 36.7 45.8 30,500 Nominal Capacity (cfm) (in.) Total Face Area (sq It) s/_-In. STEAM IFB Integral Face and Bypass Nominal -- 3,000 4,000 5,000 6,000 7,000 8,500 10,500 12,500 15,000 18,000 20,000 25,000 Coil Height (in.) Capacity (cfm) -- 22.88 30.56 30.56 30.56 30.56 24 33 33 33 45 51 60 75 Length -- 24 30 39 39 45 59.38 59.38 59.38 81.38 81.38 81.38 92.38 92.38 -- 3.3 5.7 7.4 7.4 8.5 9.2 12.6 12.6 17.6 24.1 27.3 36.7 45.8 (in.) Total Face Area (sq It) LEGEND IFB -- Integral Face and Bypass 20 Table 4- 39M UNIT SIZE CIRCUITING Direct-Expansion Circuiting Data Medium Face Area Coils 03 06 08 10 12 14 au_rterI N_lf I Fu, Ouarteq Half I Fu, OuarterI N_lfI Full auarted N_lfI Fu, aoarterI N_lf I Fu, OuarteqHalfI Full TYPE _.lrtlow (cfm) at 500 fpm Total Face Area (sq It) Tubes In Face 14 Tube Length (in.) _1o. of Circuits - Total 20 4 1,215 2.4 14 2,066 4.1 2,778 5.6 270 20 34 144141137 14 2 7/8 2 % % G-1.5 2 % % G-2._G-2 2 7/8 7/8 G-1.5 _ 34 114 14 3,611 7.2 16 4,965 9.9 6,146 12.3 I 16 22 52 16 52 6 52 22 11 52 22 22 2412424 59 12 59 24 2 1_ 2 13/8 I 40 16 52 16 4 2 7/8 7/8 G-2.5 __ __ _ -- 2 7/8 % G-1.5 2 ¼ __ __ 2 7/8 2 1% 2 13/8 2 _8 % G-2.5 --- 7/s G-2 ¼ G-4/G-3 1% E-12 U8 G-2 7/8 G-4 2 7/s % G-1.5 2 ¼ % G-2.5 ----- 2 7/8 7/s G-2 2 1% ¼ G-4/G-3 ----- 2 7/8 7/8 G-2 2 1 V8 7/8 G-4 1611616 82 d-Row Coil Face Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* 2 7/8 7/8 G-1.5 % G-2.5/G-2 _ __ --- Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* 2 7/8 7/s G-1.5 2 7/8 % G-2.5/G-2 ----- 2 % % G-1.5 2 % % G-2.5/G-2 2 7/8 7/8 G-1.5 2 7/8 7/8 G-2.5 -__ --- 1 1% --- 1 7/8 1 1vs 1 7/_ 1 1V8 --- 1 7/8 1 1V8 --- 1 1Vs 1 13/8 --- 1 1% 1 13/8 % G-6 --- % G-2.5 % G-6 7/8 G-2.5 7/8 G-8 --- ¼ G-2.5 ¼ G-8 --- 7/s G-4 1% E-12 --- 7/8 G-4 13/8 C-12 2 2 2 1% 2 7/8 2 7/8 2 1I/8 2 7/s __ 2 2 % % G-2.5/G-2 2 7/8 2 % % G-1.5 2 7/8 2 _ _ -- 7/8 G-1.5 7/8 G-2.5 % G-8 % G-1.5 % G-2.5 7& G-8 7/s G-2 1% ¼ G-4/G-3 18/8 1V8 E-12 __ --- 1 _/8 7/8 G-4 13/8 13/8 C-12 ----- 2 % % G-1.5 2 % % G-2.5/G-2 2 2 -- 2 2 -- 2 2 2 -- 2 2 7/8 % G-1.5 7/8 7/8 G-2.5 __ __ -- 7/s 7/8 G-1.5 ¼ ¼ G-2.5 -_ -- 7/8 7& G-2 1% ¼ G-4/G-3 13/8 1% E-12 ---- 1% 7/8 G-4 13/8 13/8 C-12 Single-Circuit Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size D-Row Coil Face Split Coils No. of TXVs 1 7/8 7/s G-2.5 2 Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) 7/s 7/8 G-1.5 2 7/8 7/8 G-2.5/G-2 2 2 (in. OD) 7/8 7& G-1.5 1 1 -- 1 1 1 1 -- 1 1 -- 1 1 Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size 7/8 7/s G-2.5 11/8 % G-6 ---- 7/8 % G-2.5 1vs % G-6 7/8 7/8 G-2.5 1V8 7/8 G-8 ---- 7/8 ¼ G-2.5 11/8 ¼ G-8 ---- 11/8 7/s G-4 13/8 1% E-12 -__ 2 7/8 2 1_/8 % G-6 ----- 2 7/8 % G-2.5/G-2 2 1V8 % G-6 __ 2 2 -- 2 2 -- -__ -- 7/8 7/s G-2.5 1% % G-8 ---- 7/8 ¼ G-2.5 11/8 7/8 G-8 __ --- 2 -- 2 2 -- 2 2 -- -- 2 % % G-2.5/G-2 1V8 % G-6 -__ -- 7/8 7/s G-2.5 1% % G-8 ---- 7/8 ¼ G-2.5 11/8 7/8 G-8 ---- Distributor Connections Distributor Nozzle Size* Single-Circuit Coils No. of TXVs D-Row Coil Face Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Single-Circuit Coils No. of TXVs Suction Connections Distributor Distributor (in. OD) Connections Nozzle Size (in. OD) --- 7/8 % G-2.5/G-2 7/8 G-2.5/G-2 ----- 2 7/8 7/8 G-2.5/G-2 -- - *When 2 nozzle distributor. Expansion 2 -- 2 13/8 1% E-12 __ --- 1% 7/8 G-4 2 2 -- 2 2 1% % G-4/G-3 13/8 1% E-12 ---- 1% 7& G-4 13/8 13/8 C-12 ¼ G-4/G-3 2 13/8 13/8 C-12 1 1 1 1 1 1 1 -- 11/8 7_ G-6 1vs % G-6 1v8 7/8 G-8 1V8 % G-8 13/8 1% E-12 1% 13/8 0-12 ---- NOTE: Factory-supplied distributors have factor, -selected nozzle sizes as shown. If necessary, replace factory-supplied nozzles with field-supplied and installed nozzles. Consult AHUBulIder@ software selection program for correct nozzle selection. Valve (Field Supplied) sizes are listed, 1 1% 13/8 0-12 7/8 7/s G-2.5 LEGEND TXV -- Thermostatic 2 1% 13/8 C-12 the smaller nozzle should be located on the upper 21 Table 4 -- Direct-Expansion Circuiting Data (cont) Medium Face Area Coils (cont) 39M UNIT SIZE CIRCUITING 17 TYPE 21 Half I Full 6,771 13.5 Airflow (cfm) at 500 tpm Total Face Area (sq It) Tubes In Face Tube Length (in.) No. of Circuits - Total 25 Half I Full IDouble 9,028 18.1 Half I Full IDouble 10,276 20.6 24 24 32 32 32 32 32 I 32 65 12 65 24 65 16 65 32 65 64 72 16 32 72 I 72 64 2 2 2 2 -- 2 11/8 13/8 11/s 7/8 G-4 13/8 C-12 7/8 G-8 15/8 13/8 C-17 __ _ 2 2 2 2 -- 30 36 40 HalfIFuIIIDouble 12,778 25.6 FulIIDouble 15,000 30.0 FuIllDouble 18,333 36.7 FuIIIDouble 19,861 39.7 96 36 60 44 44 92 16 92 32 92 64 96 72 50 "'l" 60 88 61 " 104 88 4-Row Coil Face Split Coils No. of TXVs Suction Connections (In. OD) Distributor Connections (In. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs Suction Connections (In. OD) Distributor Connections (In. OD) Distributor Nozzle Size* 11/8 13/8 7/8 13/8 G-4 C-12 Single-Circuit Coils NO. of TXVs 11/s 15/8 7/8 13/o G-8 C-17 ---- 2 11/8 15/8 7/8 lS/a G-6 C-17 2 2 1V8 15/8 7/8 1% G-8 C-17 -__ --- 2 ---- 2 11/_ 15/8 % lS/a G-8 C-17 I Full Double 25,278 56.6 104 28 104 28 104 56 104 56 Upper Lower Upper Lower -- 2 -- 4 -- 4 -- 2 2 ---- 15/8 lS/8 C-17 ---- 1% 1V8 E-12 ---- 1% 1V8 E-12 ---- 15/8 lS/8 C-15 15/8 2 2 -- 2 -- 4 -- 4 -- 2 7/8 G-8 15/8 1% C-17 ---- 15/8 1% C-17 ---- 1% 1Vo E-12 ---- 13/8 1V8 E-12 ---- 15/8 1% C-15 1% O-15 2 1% 13/o C-15 1 Suction Connections (In. OD) Distributor Connections (In. OD) Distributor Nozzle Size 1% lS/8 O-12 6-Row Coil Face Split Coils No. of TXVs Suction Connections 2 11/8 2 13/8 2 11/s Distributor Connections (In. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs 7/8 G-4 13/8 C-12 7/8 G-8 2 2 Suction Connections (In. Distributor Connections Distributor Nozzle Size* Single-Circuit Coils NO. of TXVs Suction Connections (In. Distributor Connections Distributor Nozzle Size 11/8 13/8 7/o 13/8 G-4 C-12 (in. OD) OD) (In. OD) OD) (In. OD) 1 1% lS/o O-12 2 2 Suction Connections (in. OD) Distributor Connections (In. OD) Distributor Nozzle Size* 1V8 7/8 G-4 13/8 13/8 C-12 2 2 2 -- -- 2 2 -- 2 -- 4 -- 4 -- 2 15/8 13/8 C-17 ---- 1V8 15/8 7/8 lS/8 G-8 C-17 2 2 -__ -- 1Ve 7/8 G-8 15/8 1% C-17 __ --- 15/8 lS/8 C-17 __ --- 13/8 1V8 E-12 __ --- lS/s 1V8 E-12 __ --- 15/8 lS/8 C-15 2 2 11/s 15/8 7/8 13/8 G-8 C-17 --- 2 1V8 2 15/8 --- 2 1Ve 2 15/8 --- 2 15/8 --- 4 1% --- 4 13/8 --- 2 15/8 --- 7/8 1% G-8 C-17 --- 7/8 G-8 1% C-17 --- 1% C-17 --- 1V8 E-12 --- 1V8 E-12 --- 1% C-15 2 2 1Vs 15/8 7/8 13/8 G-8 C-17 4 15/8 2 1V8 2 15/8 4 15/8 2 1Ve 7/8 lS/8 G-8 C-17 13/8 C-17 7/8 G-8 2 1% 1% O-15 2 1% 1% O-15 8-Row Coil Face Split Coils No. of TXVs Intertwined Row Split Coils No. of TXVs Suction Connections (In. OD) Distributor Connections (in. OD) Distributor Nozzle Size* 11/8 13/8 7/8 13/8 G-4 C-12 Single-Circuit Coils NO. of TXVs 1% C-17 *When 2 nozzle distributor. Expansion sizes are 2 4 4 8 4 8 2 15/8 lS/8 C-17 15/8 lS/8 C-17 13/8 1V8 E-12 13/8 1V8 E-12 13/8 1V8 E-12 13/8 1V8 E-12 15/8 lS/8 C-15 -- 2 4 -- 2 4 -- 2 4 2 4 4 8 4 8 2 -- 15/8 1% C-17 15/8 1% C-17 ---- 15/8 1% C-17 15/8 13/8 O-17 ---- 15/8 1% C-17 15/8 1% C-17 15/8 1% C-17 15/8 1% C-17 1% 1V8 E-12 13/8 1V8 E-12 1% 1V8 E-12 1% 1V8 E-12 15/8 1% C-15 --- 2 1% 1% O-15 4 4 15/8 1% 0-15 15/8 1% 0-15 2 1% 13/8 O-15 4 4 15/8 1% 0-15 15/8 1% 0-15 1% 1% C-12 LEGEND Thermostatic 4 15/8 1% C-17 1 SucUon Connections (In. OD) Distributor Connections (In. OD) Distributor Nozzle Size TXV- 2 15/8 1% C-17 NOTE: Factory-supplied distributors have factory-selected nozzle sizes as shown. If necessary, replace factory=supplied nozzles with field-supplied and installed nozzles. Consult AHUBullder® software selection program for correct nozzle selection. Valve (Field Supplied) listed, the smaller nozzle should be located on the upper 22 Table 4-39M UNIT SIZE CIRCUITING _.irflow Direct-Expansion Circuiting Large Face Area Coil 03 06 Data (cont) 08 10 12 auarterlNal11Fu"auarterlNalflFu" auarterl Nail IFu" euarterl Half IFull TYPE (cfm) at 500 fpm 1,736 3.5 Total Face Area (sq it) Tubes In Face 2,951 5.9 3,619 7.6 4,965 9.9 auarterINalflFull 6,319 12.6 22 I 22 26 20 4 20 10 20 20 34 4 34 10 34 20 40 6 40 11 40 22 62 6 52 11 J 22 52 52 7 Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* 2 7/8 % G-1.5 2 1V8 % G-3 ---- 2 7/8 7/8 G-1.5 2 1V8 7& G-3 --__ -- 2 7/8 % G-2 2 1_/8 % G-4/G-3 ---- 2 _8 V8 G-2 2 1% ¼ G-4/G-3 -__ -- Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* 2 7/8 % G-1.5 2 lV8 % G-3 ----- 2 7/8 7& G-1.5 2 1V8 7& G-3 --__ -- 2 7/8 % G-2 2 1_/8 % G-4/G-3 ----- 2 V8 _8 G-2 2 1% ¼ G-4/G-3 ----- 1 11/8 7/8 G-3 1 13/8 1_/8 E-10 ----- 1 1V8 7/8 G-3 1 13/8 1V8 E-10 ----- 1 1_/8 7/8 G-4 1 13/8 1_/8 E-12 ----- 1 11/8 q8 G-4 1 1% 1% E-12 ----- 2 7/8 % G-1.5 2 1_/8 % G-3 ----- 2 7/8 7/8 G-1.5 2 1V8 7& G-3 --__ -- 2 7/8 7/8 G-2 2 11/8 7/8 G-4/G-3 2 13/8 11/8 E-12 2 _8 _8 G-2 2 1V8 7/8 G-4/G-3 2 7/8 % G-1.5 2 1_/8 % G-3 ----- 2 7/8 7/8 G-1.5 2 1V8 7/8 G-3 --__ -- 2 7/8 7/8 G-2 2 11/8 7/8 G-4/G-3 2 13/8 11/8 E-12 2 _8 q8 G-2 1 1 -- 1 1 -- 1 1 -- 1_/s 7/8 G-3 1% lV8 E-10 ---- 1V8 7/8 G-3 13/8 1V8 E-10 ---- 1_/8 7/8 G-4 13/8 1_/8 E-12 ---- Tube Length (in.) No. of Circuits _ Total 14 euarterINalflFull 7,170 14.3 62 14 62 28 59 7 59 14 69 28 2 7/8 7/8 G-2.5/G-2 2 1% 7/8 G-6 2 1_/8 13/8 0-15 2 7/8 7/8 G-2.5/G-2 2 1% % G-6 2 1% 1% 0-15 2 7/0 7/8 G-2.5/G-2 2 1% ¼ G-6 --__ -- 2 7/8 7& G-2.5/G-2 2 1% % G-6 1 1V8 7/8 G-6 1 15/8 13/8 C-15 ----- 1 1V8 7/8 G-6 2 13/8 1V8 E-12 ----- 2 1% ¼ G-6 2 15/8 13/8 0-15 ----- 2 1% % G-6 2 1% 1% 0-15 2 1V8 7/8 G-4/G-3 2 13/8 1% E-12 ----- 2 1% 2 15/8 --- G-6 0-15 -- 2 1% % G-6 2 15/8 1% 0-15 1 1 -- -- 1 -- -- 11/8 q8 G-4 13/8 1% E-12 ---- __ --- 1-5/8 13/8 C-15 ---- __ _-Row Coil Face Split Coils No. of TXVs Single-Circuit Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size _-Row Coil Face Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections Distributor Nozzle Size* Single-Circuit Coils No. of TXVs (in. OD) Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size D-Row Coil Face Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Intertwined Row Split Coils No. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size* Single-Circuit Coils No. of TXVs Suction Connections Distributor Distributor (in. OD) Connections Nozzle Size (in. OD) *When 2 nozzle distdbutor. Expansion 2 2 -- 2 2 -- 2 2 -- 2 2 -- 2 2 ---- 11/8 7/8 G-3 13/8 1V8 E-10 -__ -- 1_/8 7/8 G-3 13/8 1_/8 E-10 ---- 11/8 7/8 G-4/G-3 13/8 11/8 E-12 ---- 1V8 7/8 G-4/G-3 13/8 1V8 E-12 ---- 1% ¼ G-6 15/8 13/8 0-15 ---- 2 1% % G-6 2 1% 1% 0-15 --- 2 1% 2 1V8 2 13/8 --- 2 1% 2 13/8 --- 2 1V8 2 1% --- 2 1% 2 1% -- --- 7/8 G-3 7/8 G-3 1_/8 E-10 --- 7/8 G-4/G-3 1V8 E-12 --- 7/8 G-4/G-3 1% E-12 --- ¼ G-6 1% 0-15 --- 2 1% % G-6 2 1% 1% 0-15 ----- 1 13/8 1V8 E-10 1 13/8 1V8 E-10 1 13/8 1% E-12 ----- -__ --- 1 15/8 1% 0-15 ----- -_ --- 1 15/8 1% 0-15 ----- 1 13/8 1V8 E-12 NOTE: Factory-supplied distributors have factor, -selected nozzle sizes as shown. If necessary, replace factory-supplied nozzles with field-supplied and installed nozzles. Consult AHUBulIdeI1_ software selection program for correct nozzle selection. Valve (Field Supplied) sizes are listed, the smaller 1 1% 13/8 0-15 -- LEGEND TXV -- Thermostatic 1 1% 13/8 0-15 nozzle should be located on the upper 23 Table 4 -- Direct-Expansion Circuiting Data (cont) Large Face Area Coil (cont) 39M UNIT SIZE CIRCUITING 17 TYPE Half I Full 21 IDouble Airflow (cfm) at 500 tpm Total Face Area (sq ft) Tubes in Face 30 30 I 30 Tube Length (in,) No. of Circuits - Total 65 15 65 30 I 65 60 &Row Half 8,464 16.9 25 I Full IDoubl, Half 10,720 21.4 38 65 19 65 65 76 30 I Full IDoubie 12,205 24.4 38 38 I 38 72 19 72 38 I 72 76 Half 36 I FulllDouMe 15,174 30.3 40 FulllDouble 18,333 36.7 Full 3838138 : 44 92 19 92 38 92 76 96 96 88 Coil 5O I Double 20,000 40.0 24 24 I 24 24 96 24 96 24 I 96 48 96 48 Upper Lowe Jppe_ Lower Full 28 Full I Double 25,278 50.6 28 28 28 ,o ,o4 lO2lO 2 28 Upper Lowe JppeJ 13/8 C-15 13/8 C-15 -- 611 DouMe 30,694 61.4 104 34 34 104 68 104 68 dppe .owel .owe[ Upper Lowe -- 13/8 C-17 13/8 C-17 Face Split Coils NO. of TXVs Suction Connections (in, OD) Distributor Connections (in. OD) Distributor Nozzle Size * 7/8 G-8/G-6 13/8 C-1! --- 1Ve E-IO/E-I 13/8 _,-20 --- 11/8 E-IO/E-8 1_/8 C-2( --- 11/8 E-IOIE-8 13/8 3-20 __ -- 11/8 E-12 --- 13/8 C-12 13/8 C-12 Intertwined Row Split Coils No. of TXVs Suction Connections (in, OD) Distributor Connections (in. OD) Distributor Nozzle Size* 7/8 G-8/G-6 13/8 C-1[ _ 11/8 E-IOIE-I 13/8 2,-20 -- 1V_ E-10/E-8 13/8 C-2( -- 1118 E-IOIE-8 13/s 3-20 -- 11/8 E-12 __ 13/8 C-12 13/8 C-12 13/8 C-15 13/8 C-15 13/8 C-17 13/8 C-17 7/8 G-8/G-6 13/8 C-1! -- 1118 E-IOIE-I 13/8 2,-20 -- 1Va E-IOIE-8 13/8 0-2( -- 11/8 E-IOIE-8 13/s 3-20 -- 11/8 E-12 __ 13/8 C-12 13/8 C-12 13/8 C-15 13/8 C-15 13/8 C-17 13/8 C-17 7/8 G-81G-6 13/8 C-1! --- 11/6 E-IOIE-I 13/8 2,-20 --- 1Va E-IOIE-8 13/8 0-2( --- 1 U8 E-IOIE-8 13/8 3-2C --- 1 V_ E-12 --- 13/8 C-12 13/8 C-12 13/B C-15 13/8 C-15 13/8 C-17 13/8 C-17 Single-Circuit No. of TXVs -- - -- - Coils Suction Connections (in, OD) Distributor Connections (in. OD) Distributor Nozzle Size 13/8 0-15 6-Row Cog Face Split Coils NO. of TXVs Suction Connections (in, OD) Distributor Connections (in, OD) Distributor Nozzle Size* Intertwined Now Split No. of TXVs Coils Suction Connections (in, OD) Distributor Connections (in. OD) Distributor Nozzle Size* Single-Circuit NO, of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size 8-Row Coil Nozzle Size* 7/8 13/8 13/8 11/8 13/8 13/8 1Va G-81G-6 C-1! C-15 E-IO/E-I _,-20 C-20 E-IOIE-8 Intertwined Now Split Coils No, of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Single-Circuit No. of TXVs Cogs Size* 7/8 13/8 13/8 G-81G-6 C-1! C-15 Suction Connections (in. OD) Distributor Connections (in. OD) Distributor Nozzle Size TXV -- Thermostatic _When 2 nozzle - -- -- - -- 13/8 C-15 Face Split Coils NO. of TXVs Suction Connections (in. OD) Distributor Connections (in. OD) Distributor -- Coils LEGEND Expansion sizes are li_ed, 1Ve E-IO/E-I 13/8 13/e 1Va _,-20 C-20 E-IOIE-8 13/8 0-2( 13/8 0-2( 13/8 0-20 13& 0-20 11/8 E-IOIE-8 1 V8 E-IOIE-8 13/8 11/8 11/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 13/8 3-20 C-20 E-12 E-12 C-12 C-12 C-12 C-12 C-15 C-15 C-15 C-15 C-17 C-17 C-17 C-17 13/s 13/8 1 l& 1 V8 13/8 13/8 13/8 13/8 13/_ 13/8 13/8 13/8 13/8 13/8 13/8 13/8 3-20 C-20 E-12 E-12 C-12 C-12 C-12 C-12 C-15 C-15 C-15 C-15 C-17 C-17 C-17 C-17 13/8 C-15 NOTE: Factory-supplied distributors have factory-supplied nozzles with fteld-supplied program for correct nozzle selection. Valve (Field Supplied) tbe smaller 13/8 nozzle should be located on the upper di_ributor. 24 factory-selected nozzle sizes and installed nozzles. Consult as shown, g necessary, replace AHUBuildet@ software selection Table 5 -- 1/2-in. Water Coil Connection Sizes 3gM UNIT SIZE FACE AREA ROWS CIRCUIT TYPE 0a10610811011211411712112s1301a61 4o I so I 61 Nozzle Size (in. MPT) 1,2 4 LARGE 6,8,10 1,2 4 MEDIUM 6,8,10 1,2 4 BYPASS 6,8,10 1,2 SMALL 4 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 (2) 1.5 (2) 1.5 (2) 2.5 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 (2) 1.5 (2) 1.5 (2) 2.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2.5 (2) 2.5 (2) 2.5 HAL_FULL 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 3 (2) 1.5 (2) 2.5 (2) 2.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 3 3 (2) 2.5 (2) 2.5 (2) 3 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 1.5 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 1.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2.5 HAL_FULL DOUBLE 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 3 3 (2) 2.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 3 1.5 3 1.5 3 1.5 3 2.5 3 2.5 3 2.5 (2) 2.5 2.5 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 HAL_FULL 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 3 HAL_FULL -- 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 HAL_FULL -- 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 DOUBLE -- 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 HAL_FULL Table 6 -- 5/8-in. Water Coil Connection Sizes 3gM UNIT SIZE FACE AREA ROWS CIRCUIT TYPE 1 HALF 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 (2) 1.5 (2) 1.5 HALF 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 (2) 1.5 (2) 1.5 (2) 2 FULL 2 2 2 2 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2 (2) 2.5 (2) 2.5 Nozzle Size (in. MPT) LARGE 2,4 6,8 1 MEDIUM 2,4 6,8 1 BYPASS 2,4 6,8 1 SMALL 2 (2) 1.5 FULL 2 2 2 2 2.5 2.5 2.5 3 3 3 3 (2) 2 (2) 2.5 (2) 2.5 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 3 (2) 2.5 (2) 2.5 (2) 2.5 HALF 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 (2) 1.5 HALF 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 (2) 1.5 FULL 1.5 1.5 2 2 2 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2 FULL 1.5 1.5 2 2 2 2.5 2.5 2.5 2.5 2.5 3 3 3 (2) 2.5 DOUBLE HALF 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 2.5 1.5 3 1.5 3 1.5 3 1.5 (2) 2.5 1.5 HALF 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 2 2 FULL 1.5 1.5 1.5 1.5 2 2 2 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 FULL 1.5 1.5 1.5 1.5 2 2 2 2.5 2.5 2.5 2.5 3 3 DOUBLE 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 HALF -- 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 HALF -- 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 FULL -- 1.5 1.5 1.5 1.5 1.5 2 2 2 2 2 2 2 2 Table 7 -- 1-in. Steam Coil Connection Sizes 3gM UNIT SIZE FACE AREA ROWS CONNECTION Nozzle Size (in. MPT) 2.5 ALL* ALL OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 *Large face area sizes 40, 50 and 61 and medium face area size 61 units have 2 sets of steam coil connections. 25 2.5 2.5 2.5 2.5 2.5 Table 8 -- 5/8-in. Steam Coil Connection Sizes 39M UNIT ROWS FACE AREA SIZE o31061osIto1121t41t712112s1301361 CONNECTION Nozzle 4o I so I 61 Size (in. MPT) INLET 2 2 2 2 2 2 2 2.5 2.5 2.5 2.5 (2) 2 (2) 2 (2) 2 OUTLET 2 2 2 2 2 2 2 2 2 2 2 (2) 2 (2) 2 (2) 2 INLET 2 2 2 2 2 2 2 2 2 2 2.5 2.5 2.5 (2) 2 OUTLET 2 2 2 2 2 2 2 2 2 2 2 2 2 (2) 2 BYPASS INLET OUTLET 2 2 2 2 2 2 2 2 2 2 2 2.5 2.5 2.5 2 2 2 2 2 2 2 2 2 2 2 2 2 2 SMALL INLET OUTLET 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 INLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 3 (2) 2.5 (2) 2.5 (2) 2.5 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2.5 (2) 2.5 (2) 2.5 INLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 (2) 2.5 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 (2) 2.5 INLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 3 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 INLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 LARGE MEDIUM LARGE MEDIUM BYPASS SMALL Table 9 -- Hot Water -- Integral Face and Bypass Coil Connection Sizes 39M UNIT ROWS 1 2 3 CONNECTION INLET 2.5 2.5 2.5 2.5 NozzleSize(in. 2.5 2 2 2 2 2 2 2 OUTLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2 2 2 2 2 INLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2.5 2.5 2.5 2.5 2.5 OUTLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2.5 2.5 2.5 2.5 2.5 INLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2.5 2.5 2.5 2.5 2.5 OUTLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2.5 2.5 2.5 2.5 2.5 Table 10 --Steam CONNECTION MPT) -- Integral Face and Bypass Coil Connection 39M UNIT ROWS SIZE 03 I 68 I 08 I tO I t2 I 14 I t7 I 21 I 2SI 30 I 36 I 40 I SOI 61 2 3 Sizes SIZE 03 I 66 I 08 I t0 112 114 I 17 I 21 I 25 I 3OI 36 I 40 I SOI 61 NozzleSize(in. 1 2 MPT) INLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3 3 OUTLET 2.5 2.5 2.5 2.5 2.5 2 2 2 2 2 2 2.5 2.5 INLET 2.5 2.5 2.5 2.5 2.5 3 3 3 3 3 3 3 3 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 INLET 2.5 2.5 2.5 2.5 2.5 3 3 3 3 3 3 3 3 OUTLET 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Table 11 -- Operating Charge (Approximate) -- Direct-Expansion Coil 39M UNIT SIZE ROWS CONNECTION o3 Io8 108 I to It2 I t4 I t7 121 I 2s 130 138 140 I so I 6t Refrigerant 4 6 8 R-22 (Ib) Large 1 3 4 4 5 6 7 9 11 13 16 18 22 27 Medium 1 2 3 3 4 5 6 7 8 10 12 13 17 20 Large 2 4 6 7 9 10 12 15 18 22 26 29 37 45 Medium 2 3 4 5 7 8 9 11 14 16 20 22 27 33 Large 3 6 8 10 12 15 18 22 26 31 37 42 52 63 Medium 2 5 6 8 9 11 13 16 20 23 28 31 39 48 26 Table 12 -- Coil Volume (Gal. Water) 39M UNIT SIZE 03 06 08 10 12 14 17 21 25 30 36 40 50 61 1.4 2.0 2.7 3.4 2.2 3.3 4.4 5.5 2.8 4.3 5.7 7.1 3.7 5.5 7.3 9.1 4.7 7.0 9.3 11.6 5.3 7.9 10.5 13.1 6.2 9.3 12.4 15.5 7.8 11.8 15.7 19.6 8.9 13.3 17.8 22.2 11.0 16.5 22.0 27.5 13.3 19.9 26.5 33.2 14.5 21.7 29.0 36.2 18.3 27.4 36.5 45.7 22.2 33.3 44.4 55.5 Medium Face Area 4-Row 6-Row 8-Row 1O-Row 0.9 1.4 1.9 2.4 1.5 2.3 3.1 3.9 2,1 3.1 4,1 5.2 2.7 4.0 5.3 6.6 3.7 5.5 7,3 9.1 4.5 6.8 9.0 11.3 4.9 7.4 9.9 12.4 6.6 9.9 13.2 16.5 7.5 11.2 15.0 18.7 9.3 13.9 18.5 23.1 10.9 16.3 21.7 27.1 13.3 19.9 26.5 33.2 14.4 21.5 28.7 35.9 18.3 27.4 36.5 45.7 Small Face Area 4-Row -- 1.3 1.5 2.0 2.3 2.6 3.3 3.7 4.2 5.2 7.2 7.2 9.1 11.1 Bypass Face Area 4-Row 6-Row 8-Row 1O-Row 0.8 1.2 1.6 2.0 1.3 2.0 2.7 3.3 1.8 2.7 3.6 4.5 2.3 3.5 4.7 5.8 3.3 5.0 6.6 8.3 3.8 5.6 7.5 9.4 4.5 6.8 9.1 11.3 5.8 8.7 11.5 14.4 6.5 9.8 13.1 16.4 8.1 12.2 16.2 20.3 9.0 13.6 18.1 22.6 10.9 16.3 21.7 27.1 11.7 17.6 23.5 29.4 14.4 21.5 28.7 35.9 0,3 0.7 0.6 1.1 0.7 1.4 0.9 1.8 1.2 2.3 1.3 2.6 1.5 3.1 2.0 3.9 2.2 4.4 2.7 5.5 3.3 6.6 3.6 7.2 4.6 9.1 5.5 11.1 Medium Face Area 1 -Row 2-Row 02 0.5 0.4 0.8 0.5 1.0 0.7 1.3 0.9 1.8 1.1 2.3 1.2 2.5 1.6 3.3 1.9 3.7 2.3 4.6 2.7 5.4 3.3 6.6 3.6 7.2 4.6 9.1 Small Face Area 1 -Row 2-Row --- 0.3 0.7 0.4 0.8 0.5 1.0 0.6 1.2 0.7 1.3 0.8 1.6 0.9 1.9 1.1 2.1 1.3 2.6 1.8 3.6 1.8 3.6 2.3 4.6 2.8 5.5 Bypass Face Area 1-Row 2-Row 0.2 0.4 0.3 0.7 0.5 0.9 0.6 1.2 0.8 1.7 0.9 1.9 1.1 2.3 1.4 2.9 1.6 3.3 2.0 4.1 2.3 4.5 2.7 5.4 2.9 5.9 3.6 7.2 Integral Bypass 1-Row 2-Row 3-Row ---- 0.3 0.6 0.8 0.5 0.9 1.4 0.6 1.2 1.8 1.6 3.2 4.7 1.8 3.6 5.3 2.4 4.8 7.1 3.0 5.9 8.9 CHILLED WATER Large Face Area 4-Row 6-Row 8-Row 1O-Row HOT WATER Large Face Area 1-Row 2-Row Face Area NOTE: One gallon of water weighs 0.6 1.2 1.8 0.7 1.4 2.0 8.33 lb. 27 0.6 1.2 1.9 0.8 1.7 2.5 0.8 1.7 2.5 1.2 2.3 3.5 Table 13 -- Dry Coil Weights (Ib) COIL TYPE 8 11 14 6 11 14 6 11 14 6 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 8 11 14 03 50 52 54 70 73 76 90 94 98 107 111 116 35 36 38 49 51 53 63 66 68 75 78 81 ---30 31 33 42 44 46 54 56 59 64 67 69 17 17 18 23 24 25 12 12 13 16 17 18 ------10 10 11 14 15 15 06 85 89 92 120 124 129 154 160 166 182 190 197 60 62 64 83 87 90 107 112 116 127 132 136 51 53 55 51 53 55 71 74 77 92 96 99 109 113 118 28 30 31 40 41 43 20 21 21 28 29 30 17 18 18 24 26 26 17 18 18 24 26 26 08 110 115 119 154 160 167 196 206 215 235 244 254 80 83 87 112 117 121 144 150 156 171 178 185 60 63 65 70 73 76 98 102 106 126 131 137 149 156 162 37 38 40 51 53 56 27 28 29 37 39 40 20 21 22 28 29 30 23 24 26 33 34 35 10 143 149 155 200 209 217 258 268 279 305 318 331 104 108 113 146 152 158 187 195 203 222 231 240 78 81 85 91 95 99 127 133 138 164 171 177 194 202 210 48 50 52 67 70 72 35 36 38 49 51 53 26 27 28 36 38 39 30 32 33 42 44 46 12 182 190 197 255 265 276 328 341 355 388 404 421 143 149 155 200 209 217 257 268 279 305 318 330 91 95 99 130 135 141 182 190 197 234 244 254 277 289 300 61 63 66 85 88 92 48 50 52 67 70 72 30 32 33 42 44 46 43 45 47 61 63 66 14 207 215 224 289 301 313 372 387 403 441 459 477 177 184 192 246 256 266 319 332 345 378 393 409 103 108 112 148 154 160 207 215 224 266 277 288 315 328 341 69 72 75 96 100 104 59 61 64 83 86 89 34 36 37 48 50 52 49 51 63 69 72 75 39M 17 244 254 264 341 355 370 439 457 475 520 542 563 195 203 211 273 284 296 351 366 360 416 433 451 130 135 141 179 186 194 250 261 271 322 335 349 381 397 413 81 85 88 114 118 123 65 68 70 91 95 99 43 45 47 61 63 66 60 62 65 83 87 90 UNIT 21 309 322 335 432 450 466 556 579 602 659 686 714 260 271 282 364 379 394 468 468 507 555 578 601 146 152 158 228 237 246 319 332 345 410 427 444 485 506 526 103 107 112 144 150 156 87 90 94 121 126 131 49 51 53 68 71 74 76 79 82 106 111 116 SIZE 25 353 367 382 494 514 535 635 661 686 753 784 815 296 308 321 414 432 449 533 555 577 631 658 684 167 173 180 259 270 281 363 378 393 466 486 505 553 576 599 118 122 127 165 171 178 99 103 107 138 144 150 56 58 60 78 81 84 86 90 94 121 126 131 30 437 455 473 612 637 663 767 819 652 932 971 1010 366 383 399 515 537 556 662 690 718 785 818 850 207 216 224 322 335 349 461 470 488 580 604 628 687 716 744 146 152 158 204 212 221 123 128 133 172 179 186 69 72 75 97 101 105 107 112 116 150 157 163 36 528 550 572 739 770 801 950 990 1030 1126 1173 1220 432 450 468 605 630 655 778 810 842 922 960 998 288 300 312 360 375 390 504 525 546 648 675 702 768 800 832 176 183 191 246 257 267 144 150 156 202 210 218 96 100 104 134 140 146 120 125 130 168 176 182 40 576 600 624 606 640 874 1037 1080 1123 1229 1280 1331 528 550 572 739 770 601 950 990 1030 1126 1173 1220 288 300 312 432 450 468 605 630 655 778 810 842 922 960 998 192 200 208 269 280 291 176 183 191 246 257 267 96 100 104 134 140 146 144 150 156 202 210 218 50 728 758 789 1019 1062 1104 1310 1365 1420 1553 1618 1682 572 596 620 801 634 668 1030 1073 1115 1220 1271 1322 364 379 394 468 488 507 655 683 710 842 878 913 998 1040 1082 243 253 263 340 354 368 191 199 207 267 278 289 121 126 131 170 177 184 156 163 169 218 228 237 61 884 921 956 1236 1289 1341 1591 1656 1724 1886 1964 2043 726 758 789 1019 1062 1104 1310 1365 1420 1553 1618 1682 442 460 479 572 596 620 801 834 868 1030 1073 1115 1220 1271 1322 295 307 319 413 430 447 243 253 263 340 354 368 147 153 160 206 215 223 191 199 207 267 278 289 LARGE 6 9 12 23 24 25 40 41 43 51 53 56 67 70 72 86 88 92 96 100 104 114 118 123 144 150 156 165 171 178 204 212 221 246 267 267 269 280 291 340 354 368 413 430 447 MEDIUM 6 9 16 17 28 29 37 39 49 51 67 70 83 86 91 95 121 126 138 144 172 179 202 210 246 257 267 278 340 354 SMALL 12 6 9 12 18 ---- 30 24 26 26 40 28 29 30 53 36 38 39 72 42 44 46 89 48 50 52 99 61 63 66 131 68 71 74 150 78 81 84 186 97 101 105 218 134 140 146 267 134 140 146 289 170 177 184 368 206 215 223 BYPASS 6 9 12 14 15 15 24 26 26 33 34 36 42 44 46 61 63 66 69 72 75 83 87 90 106 111 115 121 126 131 150 157 163 168 176 182 202 210 218 218 228 237 267 278 289 FACE AREA ROWS 4 6 LARGE 8 10 4 6 CHILLED WATER OR DIRECT EXPANSION MEDIUM 8 10 SMALL 4 4 6 BYPASS 8 10 1 LARGE 2 1 MEDIUM 2 HOT WATER 1 SMALL 2 1 BYPASS 2 1 1-in, IDT STEAM FPI LEGEND FPI IDT --- Finperlnch Inner Distributing NOTES: 1. Weights shown include 2. Coils are full length. 3, Weights shown are for 4. Weights shown are for 5, Weights shown are for 6. Weights shown are for Tube headers and are the sum of two coils where applicable. aluminum fin coils; 1/2-in., .016 in. wall 1/2-in., .016-in. wall 1/2-in., .016-in. wall for copper tubes; for tubes; for tubes; for fin coils, multiply by 1.20. 1/2-in., .025-in. wall tubes, multiply by 1.15. s/8-in., .020-in. wall tubes, multiply by 1.15. s/s-in., .035-in. wall tubes, multiply by 1.50. 28 Table 13 -- Dry Coil Weights (Ib) (cont) COIL TYPE FACE AREA ROWS 1 LARGE 2 1 MEDIUM 2 5/8-1N, IDT STEAM 1 SMALL 2 1 BYPASS 2 1 INEGRAL FAC E AND BYPASS HOT WATER OR STEAM 2 3 FPI 03 19 19 20 23 24 25 13 14 14 16 17 18 ------11 12 12 14 15 15 ---------- 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 6 9 12 06 32 33 35 40 41 43 22 23 24 28 29 30 19 20 21 24 25 26 19 20 21 24 25 26 146 152 158 152 158 164 158 165 172 08 41 43 44 51 53 56 30 31 32 37 39 40 22 23 24 28 29 30 26 27 28 33 34 35 207 216 225 220 229 238 231 241 251 10 53 56 58 67 70 72 39 40 42 49 51 53 29 30 32 36 38 39 34 35 37 42 44 46 216 225 234 228 238 248 241 251 261 12 68 71 74 65 68 92 53 56 58 67 70 72 34 35 37 42 44 46 49 51 53 61 63 66 216 225 234 228 238 248 241 251 261 14 77 80 64 96 100 104 66 69 72 83 86 89 39 40 42 48 50 52 55 57 60 69 72 75 231 241 251 246 256 266 259 270 281 39M UNIT SIZE 17 21 91 115 95 120 99 125 114 144 118 150 123 156 73 97 76 101 79 105 91 121 95 126 99 131 49 55 51 57 53 59 61 68 63 71 66 74 67 85 70 88 72 92 83 106 87 111 90 115 507 567 528 590 550 615 536 607 559 633 582 659 585 668 610 696 635 725 25 132 137 143 165 171 178 111 115 120 138 144 150 62 65 67 78 81 84 97 101 105 121 126 131 567 590 615 607 633 659 668 696 725 30 163 170 177 204 212 221 137 143 149 172 179 186 77 81 84 97 101 105 120 125 130 150 187 163 723 754 785 779 811 845 863 899 936 36 197 205 214 246 257 267 161 168 175 202 210 218 108 112 116 134 140 146 134 140 146 168 175 182 828 862 898 904 1007 1049 1008 1050 1094 40 215 224 233 269 280 291 197 205 214 246 257 267 108 112 116 134 140 146 161 168 175 202 210 218 880 917 955 967 1007 1049 1081 1126 1173 50 272 283 294 340 354 368 214 222 231 267 278 289 136 142 147 170 177 184 175 182 189 218 228 237 1064 1108 1154 1180 1229 1280 1327 1382 1440 61 330 344 358 413 430 447 272 283 294 340 384 368 165 172 179 206 215 223 214 222 231 267 278 289 1210 1260 1313 1355 1411 1470 1532 1596 1662 LEGEND FPI IDT --- Fin per Inch Inner Distributing NOTES: 1. Weights shown include 2. Coils are full length. 3. Weights shown are for 4. Weights shown are for 5. Weights shown are for 6. Weights shown are for Tube headers and are the sum of two coils where applicable, aluminum fin coils; 1/2-in., ,016 in, wall 1/2-in., .016-in, wall 1/2-in., ,016-in, wall for copper tubes; for tubes; for tubes; for fin coils, multiply by 1.20, 1/2-in., ,025-in, wall tubes, multiply by 1.15, s/8-in., .020-in, wall tubes, multiply by 1.15. s/8-in., ,035-in, wall tubes, multiply by 1.50, Table 14 -- Motor Weights (Ib) 20_400-3-50" 200-230,460-3-60 HP ODP E+ TEFC E+3 E+ ODP E+3 575-3-60 TEFC ODP TEFC E+ E+/E+3 16 36 40 60 68 29 34 37 60/ 68 3/4 1 36 40 40 60 60 68 68 29 29 34 34 37 37 60/ 68 60/ 68 116 2 42 46 54 60 65 66 66 36 41 41 47 48 50 60/ 66 65/ 66 3 5 67 87 94 81 89 92 99 73 102 62 72 70 88 142 154 158 200 121 139 105 128 89 119 142/158 154/200 36 42 78 716 10 87 89/ 99 118 130 126 15 170 217 250 259 170 210 170 250/259 20 25 212 240 250 309 287 394 290 358 205 273 254 363 212 240 287/290 394/368 30 283 300 436 436 283 414 284 436/436 40 372 415 661 661 416t 470t 370 661/661 50 440 414 686 686 403t 527t 440 686/686 60 591 652** 790 799 545 790t 591 799 75 620 706** 840 850** 651t 884t 670 850 106 *Both ODP and TEFC 50 Hz motors available in standard models only. 1-Availability unconfirmed. **460 volt only. LEGEND ODP TEFC E+ E+3 ----- Open Drip Proof Totally Enclosed Fan Cooled High Efficiency Premium Efficiency NOTE: Multiply motor weight by 0.10 to estimate drive weight. 29 Table 1539M UNIT SIZE SUPPLY Forward-Curved RETURN/ EXHAUST 03 REAR MOUNT MOTOR Std N/A 03 SIDE MOUNT MOTOR Std Std 06 REAR MOUNT MOTOR Std N/A 06 SIDE MOUNT MOTOR Std Std Std Std Small N/A Std Std Small N/A Std Std Small N/A Std Std Small N/A Std Std Small N/A Fan Drive Centerline Distances In Inches MOTOR FRAME 56 143T 145T 182T 164T 56 143T 145T 162T 164T 56 143T 145T 162T 164T 56 143T 145T 162T 164T 56 143T 145T 162T 164T 213T 162T 164T 213T 143T 145T 162T 164T 213T 164T 213T 215T 145T 162T 164T 213T 164T 213T 215T 254T 145T 162T 164T 213T 164T 213T 215T 254T 145T 162T 184T 213T 215T 213T 215T 254T O8 12 14 17 BHF/BHR Min Max 19.0 20,6 19.0 20,6 19.0 20,6 18.6 20,3 18.6 20.3 8,0 8,4 8,0 8,4 8.0 8,4 7,0 7,4 7,0 7.4 18,9 20.4 18.9 20,4 18.9 20,4 18.4 20,0 18.4 20,0 10.6 11.6 10.6 11,6 10.6 11,6 9.8 10.8 9,8 10.8 14,4 15.6 14,4 15,6 14,4 15,6 13.6 14,9 13,6 14,9 13.1 14,4 13,3 14.7 13,3 14,7 12,8 14.3 15,2 16,2 15,2 16,2 14.3 15.4 14.3 15,4 13.7 14.8 13.6 14,9 13.1 14,4 13.1 14,4 18.3 19,5 17.6 18.9 17.6 18,9 17.1 18.4 17.4 18,9 17.0 18,5 17.0 18,5 16.5 18,1 23.1 24,5 22.5 23,8 22.6 23,8 22.0 23,4 22.4 23.9 22.0 23,5 22.0 23.5 21.5 23,1 23.1 24,5 22.5 23.8 22.6 23,8 22.0 23.4 22.0 23.4 22.0 23,5 22.0 23,5 21.5 23,1 LEGEND BHF BHR DBF DBR ----- Bottom Horizontal Front Bottom Horizontal Rear Downblast Front Downblast Rear THF THR UBF UBR ----- Top Horizontal Top Horizontal Upblast Front Upblast Rear Front Rear .30 DBF/DBR Min Max N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 5,7 6.3 5,7 6.3 5.7 6.3 4,7 5.4 4,7 5.4 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 6.8 8.9 6.8 8.9 6.8 8.9 6.0 8.3 6.0 8.3 9.5 11.0 9.5 11.0 9.5 11.0 9.0 10.7 9.0 10.7 8.8 10.5 9.8 11.5 9.8 11.5 9.7 11.4 8.8 10.1 8.8 10.1 8.1 9.6 8.1 9.6 7.7 9.3 9.0 10.7 8.8 10.5 8.8 10.5 12.9 14.5 12.5 14.1 12.5 14.1 12.2 13.9 13.8 15.5 13.6 15.3 13.6 15.3 13.5 15.2 17.2 18.7 16.7 18.4 16.7 18.4 16.5 18.1 18.2 19.9 18.0 19.7 18.0 19.7 17.8 19.5 17.2 18.7 16.7 18.4 16.7 18.4 16.5 18.1 16.5 18.1 18.0 19.7 18.0 19.7 17.8 19.5 THFFFHR Min Max 17.6 19.4 17.6 19.4 17.6 19.4 17.5 19.2 17.5 19.2 5,5 6,0 5,5 6,0 5.5 6,0 4,5 5,1 4,5 5.1 17.1 18.8 17.1 18.8 17.1 18.8 16.9 18.6 16.9 18.6 8,0 10.2 8,0 10.2 8.0 10.2 7.3 9,6 7,3 9,6 10.9 12.4 10.9 12.4 10.9 12.4 10.4 12.0 10.4 12.0 10.1 11.8 11.0 12.7 11.0 12.7 10.9 12.6 10.8 12.2 10.8 12.2 10.2 11.6 10.2 11.6 9,7 11.2 10.4 12.0 10.1 11.8 10.1 11.8 14.9 16.4 14.4 16.0 14.4 16.0 14.1 15.7 15.1 16.8 14.9 16.6 14.9 16.6 14.7 16.4 19.5 21.1 19.1 20.6 19.1 20.6 18.7 20.4 20.0 21.7 19.8 21.5 19.8 21.5 19.5 21.2 19.1 20.6 18.3 19.9 17.9 19.6 17.5 19.2 17.5 19.2 19.8 21.5 19.8 21.5 19.5 21.2 UBF/UBR Min Max 15.5 17.2 15.5 17.2 15.5 17.2 15.2 17.0 15.2 17.0 7.4 7.9 7.4 7.9 7.4 7.9 6.4 7.0 6.4 7.0 14.8 16.4 14.8 16.4 14.8 16.4 14.4 16.1 14.4 16.1 8.3 10.1 8.3 10.1 8.3 10.1 7.4 9.4 7.4 9.4 10.8 12.2 10.8 12.2 10.8 12.2 10.2 11.7 10.2 11.7 9.8 11.4 10.4 12.1 10.4 12.1 10.2 11.8 10.9 12.1 10.9 12.1 10.2 11.4 10.2 11.4 9.6 10.9 10.2 11.7 9.8 11.4 9.8 11.4 14.5 15.9 13.9 15.4 13.9 15.4 13.5 15.0 14.6 16.2 14.3 16.0 14.3 16.0 14.0 15.7 19.0 20.4 18.4 19.9 18.4 19.9 18.0 19.5 19.2 20.8 18.9 20.5 18.9 20.5 18.5 20.2 19.0 20.4 18.4 19.9 18.4 19.9 18.0 19.5 18.0 19.5 18.9 20.5 18.9 20.5 18.5 20.2 Table 1539M UNIT SIZE Forward-Curved RETURN/ EXHAUST SUPPLY Std Std 21 Small N/A Std Std 25 Small N/A Std Std 3O Small N/A Std Std 36 Small N/A Std Std 4O Small N/A Std Std 5O Small N/A Std Std Small N/A Fan Drive Centerline MOTOR BHF/BHR ----- Bottom Horizontal Front Bottom Horizontal Rear Downblast Front Downblast Rear THF THR UBF UBR ----- Top Horizontal Top Horizontal Upblast Front Upblast Rear DBF/DBR THF/THR UBF/UBR FRAME Min Max Min Max Min Max Min Max 145T 24.7 26.0 14,6 16.4 17,4 19.1 18.6 20.0 182T 23.9 25.1 14.0 15,8 16.7 18,5 17.8 19.2 184T 23.9 25.1 14,0 15,8 16,7 18,5 17.8 19.2 213T 23.2 24.6 13,5 15,4 16,2 18,1 17.2 18.7 215T 23.2 24.6 13,5 15,4 16,2 18,1 17.2 18.7 254T 22.4 23.8 13.0 14,9 16.6 17,5 16.4 18.0 216T 19.9 21.3 15,6 17,3 17,4 19,0 16.6 18.2 254T 19.3 20.8 15,4 17,1 17,1 18,8 16.2 17.8 256T 19.3 20.8 15.4 17,1 17.1 18,8 16.2 17.8 284T 18.9 20.5 15,2 17.0 16,9 18.6 15.9 17.6 145T 32.4 34.1 24,1 26.2 27,4 29.5 26.6 28.5 182T 31.7 33.5 23,7 25,9 27,0 29,1 26.1 28.0 184T 31.7 33.5 23.7 25,9 27.0 29,1 26.1 28.0 213T 31.3 33.1 23.5 25,6 26.7 28,8 25.7 27.7 215T 31.3 33.1 23,5 25.6 26,7 28.8 25.7 27.7 254T 30.7 32.6 23,2 25,4 26,4 28,5 25.2 27.2 216T 31.3 33.1 23,5 25,6 26,7 28,8 25.7 27.7 254T 30.7 32.5 23,2 25.4 26,4 28.5 25.2 27.2 256T 30.7 32.6 23,2 25,4 26,4 28,5 25.2 27.2 284T 30.2 32.1 23,0 25,2 26,1 28,3 24.9 26.9 182T 31.7 33.5 23,7 25,9 27,0 29,1 26.6 28.5 184T 31.7 33.5 23,7 25.9 27,0 29.1 26.1 28.0 213T 31.3 33.1 23,5 25.6 26,7 28.8 26.1 28.0 215T 31.3 33.1 23,5 25,6 26,7 28,8 25.7 27.7 254T 30.7 32.6 23,2 25,4 26,4 28,5 25.7 27.7 256T 30.7 32.5 23,2 25.4 26,4 28.5 25.2 27.2 215T 31.3 33.1 23.5 25,6 26.7 28,8 25.7 27.7 254T 30.7 32.6 23,2 25,4 26,4 28,5 25.2 27.2 256T 30.7 32.6 23,2 25,4 26,4 28,5 25.2 27.2 284T 30.2 32.1 23.0 25,2 26.1 28,3 24.9 26.9 286T 30.2 32.1 23,0 25.2 26,1 28.3 24.9 26.9 182T 31.1 33.3 23,0 25,7 25,6 28,2 27.0 29.4 184T 31.1 33.3 23,0 25,7 25,6 28,2 27.0 29.4 213T 30.4 32.6 22,5 25.3 25,0 27.7 26.4 28.8 215T 30.4 32.6 22.5 25,3 25.0 27,7 26.4 28.8 254T 29.7 31.9 22,1 24.9 24,5 27.2 25.7 28.2 256T 29.7 31.9 22,1 24,9 24,5 27,2 25.7 28.2 254T 28.8 31.3 23.6 26,5 24.9 27,7 26.0 28.7 256T 28.8 31.3 23,6 26,5 24,9 27,7 26.0 28.7 284T 28.4 30.9 23.3 26,3 24.6 27,4 25.7 28.4 286T 28.4 30.9 23,3 26.3 24,6 27.4 25.7 28.4 184T 31.1 33.3 23,0 25.7 25,6 28.2 27.0 29.4 213T 30.4 32.6 22,5 25,3 25,0 27,7 26.4 28.8 215T 30.4 32.6 22,5 25.3 25,0 27.7 26.4 28.8 254T 29.7 31.9 22.1 24,9 24.5 27,2 25.7 28.2 256T 29.7 31.9 22,1 24.9 24,5 27.2 25.7 28.2 284T 29.2 31.5 21,8 24,7 24,1 26,9 25.3 27.8 254T 29.7 31.9 22,1 24,9 24,5 27,2 25.7 28.2 256T 29.7 31.9 22,1 24.9 24,5 27.2 25.7 28.2 284T 29.2 31.5 21,8 24,7 24,1 26,9 25.3 27.8 286T 29.2 31.5 21,8 24,7 24,1 26,9 25.3 27.8 184T 33.5 35.5 24,2 26,8 27,1 29,6 28.9 31.1 213T 32.7 34.8 23.7 26,3 26.5 29,1 28.2 30.5 215T 32.7 34.8 23,7 26.3 26,5 29.1 28.2 30.5 254T 31.9 34.1 23,2 25,9 26,0 28,5 27.5 29.8 256T 31.9 34.1 23,2 25,9 26,0 28,5 27.5 29.8 284T 31.4 33.6 22,8 25.6 25,5 28.2 27.0 29.4 286T 31.4 33.6 22.8 25,6 25.5 28,2 27.0 29.4 254T 31.9 34.1 23,2 25,9 26,0 28,5 27.5 29.8 256T 31.9 34.1 23,2 25,9 26,0 28,5 27.5 29.8 284T 31.4 33.6 22.8 25,6 25.5 28,2 27.0 29.4 286T 31.4 33.6 22,8 25.6 25,5 28.2 27.0 29.4 324T 30.7 32.9 22,4 25,2 25,0 27,7 26.3 28.8 213T 35.6 37.6 25,3 28,0 29,1 31,6 30.4 32.7 215T 35.6 37.6 25,3 28.0 29,1 31.6 30.4 32.7 254T 34.8 36.9 24.8 27,5 28.5 31,0 29.7 32.0 256T 34.8 36.9 24,8 27,5 28,5 31,0 29.7 32.0 284T 34.3 36.4 24,4 27,2 28,0 30,6 29.2 31.6 286T 34.3 36.4 24.4 27,2 28.0 30,6 29.2 31.6 324T 33.5 35.7 24,0 26.8 27,5 30.1 28.6 30.9 256T 34.0 36.3 25,8 28,6 28,5 31,2 29.8 32.2 284T 33.5 35.8 25,5 28,4 28,1 30,8 29.3 31.8 286T 33.5 35.8 25,5 28.4 28,1 30.8 29.3 31.8 324T 32.8 35.2 25.1 28,0 27.6 30,4 28.7 31.3 326T 32.8 35.2 25,1 28,0 27,6 30,4 28.7 31.3 LEGEND BHF BHR DBF DBR Distances In Inches (cont) Front Rear 31 Table 16 --Airfoil 39M UNIT SIZE SUPPLY O3 RETURN/ EXHAUST STD O6 12 14 17 Max Min Max 56 16.3 17,6 14.0 15.5 15.0 16.5 14.8 16.2 143T 145T 16.3 16.3 17,6 17,6 14.0 14.0 15.5 15.5 15.0 15.0 16.5 16.5 14.8 14.8 16.2 16.2 182T 164T 15.8 15.8 17.2 17,2 13.6 13.6 15.1 15.1 14.6 14.6 16.2 16.2 14.3 14.3 15.8 15.8 56 143T 19.5 19.5 20,3 20,3 15.0 15.0 15.5 15.5 17.3 17.3 18.2 18.2 19.1 19.1 19.9 19.9 145T 162T 19.5 19.0 20.3 19,8 15.0 14.5 15.5 15.0 17.3 17.0 18.2 18.0 19.1 18.6 19.9 19.4 164T 143T 19.0 11.1 19,8 12,4 14.5 8.5 15.0 9.8 17.0 8,2 18.0 9,5 18.6 10.3 19.4 11.6 145T 162T 11.1 10.0 12.4 11,5 8.5 7.6 9.8 9.1 8,2 7,2 9.5 8,7 10.3 9.3 11.6 10.8 164T 213T lO.O 9,4 11,5 11 .O 7.6 7.0 9.1 8.6 7.2 6,7 8,7 8,3 9.3 8.6 10.8 10.2 215T 145T 9.4 13.8 11 .O 14,3 7.0 10.3 8.6 10.9 6.7 9,8 8,3 10.6 8.6 12.9 10.2 13.5 162T 164T 12.9 12.9 13,5 13,5 9.5 9.5 10.2 10.2 9.0 9,0 9,9 9,9 12.0 12.0 12.6 12.6 213T 215T 12.2 12.2 12,9 12,9 8.9 8.9 9.7 9.7 8.4 8,4 9,4 9,4 11.3 11.3 12.0 12.0 254T 145T 11.3 17.2 12.0 17,8 8.1 14.1 9.0 14.9 7,7 13.4 8.7 14.4 10.4 17.2 11.1 17.8 162T 164T 16.4 16.4 17.0 17,0 13.3 13.3 14.1 14.1 12.7 12.7 13.7 13.7 16.4 16.4 17.0 17.0 213T 215T 15.7 15.7 16.4 16,4 12.7 12.7 13.7 13.7 12.1 12.1 13.1 13.1 15.7 15.7 16.4 16.4 254T 145T 14.9 21.2 15,7 22,2 12.0 18.7 13.0 20.0 11.4 18.2 12.5 19.5 14.9 21.2 15.7 22.2 162T 164T 213T 20.5 20.5 20.0 21,5 21,5 21,0 18.1 18.1 17.7 19.5 19.5 19.1 17.7 17.7 17.3 19.0 19.0 18.7 20.5 20.5 20.0 21.5 21.5 21.0 215T 20.0 21,0 17.7 19.1 17.3 18.7 20.0 21.0 254T 256T 19.3 19.3 20.5 20,5 17.2 17.2 18.7 18.7 16.8 16.8 18.2 18.2 19.3 19.3 20.5 20.5 145T 162T 164T 21.2 20.4 20.4 22,1 21,3 21,3 18.3 17.6 17.6 19.3 18.6 18.6 17.5 16.8 16.8 19.0 18.5 18.5 21.2 20.4 20.4 22.0 21.3 21.3 213T 19.9 20,7 17.1 18.2 16.3 18.0 19.9 20.7 215T 254T 19.9 19.1 20,7 20.1 17.1 16.4 18.2 17.6 16.3 15.7 18.0 17.5 19.9 19.1 20.7 20.1 256T 145T 162T 19.1 22.3 21.5 20,1 22,9 22.2 16.4 18.8 18.0 17.6 19.7 18.9 15.7 18.7 17.9 17.5 19.6 18.8 19.1 22.3 21.5 20.1 22.9 22.2 164T 21.5 22,2 18.0 18.9 17.9 18.8 21.5 22.2 213T 215T 254T 20.9 20.9 20.0 21,5 21,5 20,7 17.4 17.4 16.7 18.4 18.4 17.8 17.3 17.3 16.6 18.3 18.3 17.7 20.9 20.9 20.0 21.5 21.5 20.7 256T 284T 20.0 19.4 20,7 20.3 16.7 16.2 17.8 17.3 16.6 16.1 17.7 17.2 20.0 19.4 20.7 20.3 145T 28.8 29.6 25.7 26.8 25.5 26.6 28.8 29.6 162T 164T 213T 28.0 28.0 27.5 29,0 29,0 28.5 25.0 25.0 24.6 26.2 26.2 25.8 24.9 24.9 24.4 25.9 25.9 25.6 28.0 28.0 27.5 29.0 29.0 28.5 215T 254T 27.5 26.8 28,5 27,8 24.6 24.0 25.8 25.3 24.4 23.8 25.6 25.1 27.5 26.8 28.5 27.8 256T 284T 26.8 26.3 27.8 27.4 24.0 23.6 25.3 25.0 23.8 23.4 25.1 24.7 26.8 26.3 27.8 27.4 286T 26.3 27,4 23.6 25.0 23.4 24.7 26.3 27.4 STD STD 25 Min STD STD 21 Max STD STD STD STD STD LEGEND BHF BHR DBF DBR ----- Bottom Horizontal Bottom Horizontal Downblast Front Downblast Rear Front Rear THF THR UBF UBR ----- UBF/UBR Min STD STD THFFFHR Max STD STD DBF/DBR Min STD STD BHF/BHR MOTOR FRAME STD STD O8 Fan Drive Centerline Distances In Inches Top Horizontal Top Horizontal Upblast Front Upblast Rear Front Rear 32 Table 1639M UNIT SIZE MOTOR FRAME RETURN EXHAUST SUPPLY 30 Airfoil Fan Drive Centerline STD STD STD N/A 36 N/A STD STD N/A 40 N/A STD STD N/A 50 N/A STD STD N/A 61 N/A STD BHF/BHR MIn Max MIn Max MIn Max UBF/UBR MIn Max 182T 27.4 28.9 24.2 25.8 24.1 25.7 27.4 28.9 184T 27.4 28.9 24.2 25.8 24.1 25.7 27.4 28.9 213T 26.9 28.4 23.7 25.5 23.7 25.5 26.9 28.4 215T 26.9 28.4 23.7 25.5 23.7 25.5 26.9 28.4 254T 26.1 27.7 23.1 25.0 23.1 24.9 26.1 27.7 256T 26.1 27.7 23.1 25.0 23.1 24.9 26.1 27.7 284T 25.6 27.3 22.7 24.5 22.6 24.6 25.6 27.3 286T 25.6 27.3 22.7 24.5 22.6 24.6 25.6 27.3 324T 24.9 26.7 22.1 24.0 22.1 24.2 25.0 26.7 184T 26.0 27.3 20.2 22.9 20.2 22.0 24.3 25.7 213T 25.4 26.7 19.7 22.5 19.7 21.6 23.7 25.2 215T 25.4 26.7 19.7 22.5 19.7 21.6 23.7 25.2 254T 24.6 25.9 19.0 21.9 19.0 21.0 22.9 24.4 256T 24.6 25.9 19.0 21.9 19.0 21.0 22.9 24.4 284T 23.9 25.4 18.5 21.4 18.5 20.5 22.3 23.9 286T 23.9 25.4 18.5 21.4 18.5 20.5 22.3 23.9 324T 23.1 24.6 17.8 20.9 17.8 20.0 21.5 23.2 326T 23.1 24.6 17.8 20.9 17.8 20.0 21.5 23.2 182T 28.6 29.7 N/A N/A 22.2 23.9 27.0 28.1 184T 28.6 29.7 N/A N/A 22.2 23.9 27.0 28.1 213T 27.9 29.1 N/A N/A 21.6 23.4 26.4 28.5 215T 27.9 29.1 N/A N/A 21.6 23.4 26.4 28.5 254T 27.1 28.3 N/A N/A 20.9 22.7 25.5 27.7 184T 30.5 32.3 24.6 26.8 24.6 26.8 24.6 27.0 213T 29.9 31.7 24.1 26.3 24.1 26.3 24.1 26.5 215T 29.9 31.7 24.1 26.3 24.1 26.3 24.1 26.5 254T 29.1 31.0 23.5 25.8 23.5 25.8 23.5 25.9 256T 29.1 31.0 23.5 25.8 23.5 25.8 23.5 25.9 284T 28.5 30.4 23.0 25.3 23.0 25.3 23.0 25.1 286T 28.5 30.4 23.0 25.3 23.0 25.3 23.0 25.1 324T 27.7 29.7 22.4 28.8 22.4 24.8 22.4 25.0 326T 27.7 29.7 22.4 24.8 22.4 24.8 22.4 25.0 182T 30.9 32.1 N/A N/A 24.3 26.0 30.1 31.3 184T 30.9 32.1 N/A N/A 24.3 26.0 30.1 31.3 213T 30.3 31.4 N/A N/A 23.7 25.5 29.4 30.7 215T 30.3 31.4 N/A N/A 23.7 25.5 29.4 30.7 254T 29.4 30.6 N/A N/A 23.0 24.8 28.5 29.8 213T 32.9 34.5 24.5 27.0 27.0 29.1 32.1 33.8 215T 32.9 34.5 24.5 27.0 27.0 29.1 32.1 33.8 254T 32.1 33.8 24.0 26.4 26.3 28.5 31.3 33.0 256T 32.1 33.8 24.0 26.4 26.3 28.5 31.3 33.0 284T 31.5 33.2 23.6 26.1 25.8 28.1 30.7 32.4 286T 31.5 33.2 23.6 26.1 25.8 28.1 30.7 32.4 324T 30.7 32.5 23.0 25.6 25.2 27.5 29.9 31.8 326T 30.7 32.5 23.0 25.6 25.2 27.5 29.9 31.8 364T 30.4 31.8 22.5 25.2 24.6 27.0 29.2 31.1 184T 34.8 36.0 N/A N/A 27.3 29.0 33.9 35.1 213T 34.1 35.3 N/A N/A 26.7 28.4 33.3 34.5 215T 34.1 35.3 N/A N/A 26.7 28.4 33.3 34.5 254T 33.2 34.5 N/A N/A 25.9 27.7 32.4 33.7 256T 33.2 34.5 N/A N/A 25.9 27.7 32.4 33.7 213T 37.4 39.0 28.1 29.1 30.9 33.0 35.8 38.4 215T 37.4 39.0 28.1 29.1 30.9 33.0 35.8 38.4 254T 36.6 38.3 27.5 28.5 30.2 32.3 35.0 37.6 256T 36.6 38.3 27.5 28.5 30.2 32.3 35.0 37.6 284T 36.1 37.8 27.1 28.1 29.7 31.9 34.4 37.1 286T 36.1 37.8 27.1 28.1 29.7 31.9 34.4 37.1 324T 35.3 37.0 26.5 27.6 29.0 31.3 33.6 36.3 326T 35.3 37.0 26.5 27.6 29.0 31.3 33.6 36.3 364T 34.5 36.3 26.0 27.1 28.4 30.8 32.9 35.6 365T 34.5 36.3 26.0 27.1 28.4 30.8 32.9 35.6 184T 40.0 41.4 N/A N/A 31.0 33.2 38.3 39.5 213T 39.1 40.7 N/A N/A 30.3 32.7 37.4 38.6 215T 39.1 40.7 N/A N/A 30.3 32.7 37.4 38.6 254T 38.2 39.9 N/A N/A 29.5 33.0 36.5 37.8 256T 38.2 39.9 N/A N/A 29.5 33.0 36.5 37.8 LEGEND BHF BHR DBF DBR ----- Bottom Horizontal Bottom Horizontal Downblast Front Downblast Rear Front Rear THF THR UBF UBR ----- Top Horizontal Top Horizontal Upblast Front Upblast Rear Distances In Inches (cont) Front Rear 33 DBF/DBR THFFrHR Table 17 -- Plenum Fan Drive Centerline Distances In Inches 39M UNIT SIZE 03 06 08 10 12 14 17 SUPPLY STD STD STD STD STD STD STD STD 25 STD RETURN/ EXHAUST STD STD STD STD STD STD STD STD STD 39M UNIT SIZE RETURN/ EXHAUST MOTOR FRAME MIN MAX 7.5 182T 38.1 39.6 6.7 7.5 184T 38.1 39.6 145T 6.7 7.5 213T 37.8 39.4 182T 5.5 6.5 215T 37.8 39.4 184T 5.5 6.5 254T 37.3 39.0 56 12.0 13.2 256T 37.3 39.0 143T 12.0 13.2 284T 37.0 36.7 145T 12.0 13.2 286T 37.0 38.7 182T 11.3 12.6 182T 42.8 47.2 184T 11.3 12.6 184T 42.8 47.2 213T 10.9 12.2 213T 42.5 46.9 56 21.2 22.4 215T 42.5 46.9 143T 21.2 22.4 254T 42.0 46.5 145T 21.2 22.4 256T 42.0 46.5 182T 20.8 22.0 284T 41.7 46.2 184T 20.8 22.0 286T 41.7 46.2 213T 20.5 22.0 324T 41.2 45.8 215T 20.5 22.0 184T 42.9 47.2 143T 25.0 26.5 213T 42.5 46.9 145T 25.0 26.5 215T 42.5 46.9 182T 24.6 26.0 254T 42.0 46.5 184T 24.6 26.0 256T 42.0 46.5 213T 24.3 25.8 284T 41.7 46.2 215T 24.3 25.8 286T 41.7 46.2 254T 23.9 25.5 324T 41.3 45.8 143T 28.1 29.6 182T 52.0 56.5 145T 28.1 29.6 184T 52.0 56.5 182T 27.6 29.1 213T 51.7 56.2 184T 27.6 29.1 215T 51.7 56.2 213T 27.3 28.8 264T 51.3 55.8 215T 27.3 28.8 266T 51.3 55.8 254T 26.8 28.5 213T 51.7 56.2 145T 28.1 29.6 215T 51.7 56.2 182T 27.6 29.1 264T 51.3 55.8 184T 27.6 29.1 266T 51.3 55.8 213T 27.3 28.8 284T 51.0 55.5 215T 27.3 28.8 286T 51.0 55.5 254T 26.8 28.5 324T 50.5 55.1 256T 26.8 28.5 326T 50.5 55.1 145T 31.3 32.8 184T 49.2 53.3 182T 30.8 32.3 213T 48.8 51.9 184T 30.8 32.3 215T 48.8 51.9 213T 30.5 32.0 254T 48.3 52.4 215T 30.5 32.0 256T 48.3 52.4 254T 30.1 31.8 284T 47.9 52.1 256T 30.1 31.8 213T 48.7 51.9 145T 32.4 33.8 215T 48.7 51.9 182T 31.9 33.4 254T 48.2 52.5 184T 31.9 33.4 256T 48.2 52.5 213T 31.6 33.1 284T 47.9 52.1 215T 31.6 33.1 286T 47.9 52.1 254T 31.2 32.9 324T 47.4 51.7 256T 31.2 32.9 326T 47.4 51.7 284T 30.9 32.6 364T 46.9 51.2 145T 35.3 36.8 184T 51.9 55.9 182T 34.8 36.3 213T 51.5 55.5 184T 34.8 36.3 215T 51.5 55.5 213T 34.4 36.0 254T 50,9 55.0 215T 34.4 36.0 256T 50.9 55.0 254T 34.0 35.6 284T 50,5 54.6 256T 34.0 35.6 286T 50.5 54.6 284T 33.6 35.3 MOTOR FRAME MIN MAX 56 6.7 143T 30 36 SUPPLY STD STD STD STD STD N/A 40 N/A STD STD N/A 50 N/A STD N/A 34 STD N/A STD Long-Term Storage -- If stoting the unit before installation, observe the following precautions: 1. Tile storage site should be level, rigid, and flee of debtis. If the site is in a heavy rain ;uea, set the unit off of the ground. suspending the unit from cross-beams at the joint between each unit component. Ensure that suspension rods are secured to adequately support the unit and that the rods extend entirely through their associated fasteners. 2. Internal 3. 4. Do not stole the unit in a heavy traffic area or on a vibrating surface. Vibration can &Lmage stationary beatings. Ensure that all coil connections have shipping caps in place. Cover the entire unit with a waterproof t;upaulin or plastic coverall; if the unit is stored on file ground, extend the cover underneath the unit. Secme the cover with tiedowns. Do not remove cover or coil end caps until unit is ready for final installation. Isolation -- Units equipped with in 1. Open the fan access dooc 2. Remove the bolts that fasten the fan sled to the holddown bracket. (Fig. 7). Remove "S" shaped brackets. Service Clearance -- When planning the placement of the unit, ensure adequate space for service access. Typical service operations can require removing the coils and filters and accessing the motor and &tmper linkage. Refer to AHUBuilder® progrmn for recommended clearances. 3. Repeat Steps 1 and 2 on the opposite side of the fan section. Fan sled assembly should float on isolator springs when done. ADJUSTING ISOLATOR SPRINGS -- Units with factorysupplied motors and diives are preset to 13/16 -I- Us-in. clemance between the base frame assembly and the bottom panels; field adjustment of the isolator springs is not normally required. -- To prevent build-up of conden- sate in file drain pan and ensure proper operation of the &ain system, position the unit so that condensate is properly trapped. Refer to the Condensate Drain section on page 69 in the Installation section. Unit Suspension -- Unit suspension methods are shown in Fig. 6. A field-supplied platfoml mount is recommended, especially for larger unit sizes. An iniine twin-bemn mount is also recommended. Units can also be supported by attaching suspension rods to all of the lifting brackets on ;dl of the unit sections that have more than 15 in. of airway length, or by When adjusting fan isolation components, DO NOT enter or reach into the fan cabinet while fan is running. Serious injury can result. Be sure to disconnect power and tag controls before making adjustments. LOCATE SUSPENSION RODS SO THEY DO NOT INTERFERE WITH ANY ACCESS DOOR/PANEL (FIELD SUPPLIED) MOUNT UNIT TO FIELD SUPPLIED PLATFORM as described For applications that do not require internal fan isolation, leave the holddown bracket screwed or bolted in place. Otherwise, the combination of internal and external unit isolation could lead to unwanted oscillation magnification. REMOVING HOLDDOWN BOLTS, AIRFOIL, PLENUM AND FORWARD-CURVED FANS -- Remove the holddown bolts (Fig. 7) as follows: Monthly -- Move the coverall, enter the fan section through the access door or fan inlet, and slowly rotate the fan and motor by hand. This operation prevents be;uing corrosion by redisttibuting the bearing grease. Drain Positioning Vibration internal vibration isolation must be prepared this section before they tue inst_dled. THROUGH 11/16-1N. DIAM HOLE PROVIDED BASE RAIL. REMOVE LIFTING BRACKETS AS REQUIRED. IN CEILING -- RECOMMENDED PLATFORM MOUNT CEILING --ALTERNATE CROSSBEAM MOUNT MOUNT UNIT TO FIELD SUPPLIED BEAMS THROUGH DIAM HOLE PROVIDED IN BASE RAIL. REMOVE LIFTING BRACKETS AS REQUIRED. CEILING -- ALTERNATE LIFTING BRACKET MOUNT CEILING -- RECOMMENDED IN-LINE BEAM MOUNT Fig. 6 -- Unit Suspension 35 When field-supplied motors and &ives have been installed, adjust the isolator spdngs as shown in Fig. 7 and described as follows: _,DJUSTING 1. Ix_osen the locknut on adjusting stem. SLED 2. Turn the adjusting stem until the specified clearance of 13/l<,+ l&-in, is obtained. (Turn clockwise to decrease clearance or counterclockwise to increase clearance.) 3. Tighten the locknut. 4. Repeat for each of the isolator springs and ensure that the fan sled is floating on the springs. External Vibration Isolation -- Install external vibration isolators per certified drawings, job specifications, and the instructions of the isolator manufacturer. For applications that do not require internal fan isolation, leave the holddown bracket screwed or bolted in place. Otherwise, the combination of internal and external unit isolation could lead to unwanted oscillation magnification. The coil piping must also be isolated or have flexible connectors to avoid coil header damage due to motion or vibration. Flexible connections should also be installed at the fan inlet (if ducted) and at the dischm'ge. HOLDDOWN BOLT SPRING HOLDDOWN BOLT Fig. 7 -- Spring Isolator and Holddown Bracket Roof Curb -- Roof curbs can be field supplied for 39MW units and should be installed according to the manufacturer's instructions. Curbs am typically shipped knocked down and require field assembly as follows: 1. Curbs greater than 12 ll in ailway length will be split and joined together by a splice plate. Butt the two sections and bolt together with the splice plate as shown in Fig. 8. 2. Arrange sides and ends together at right angles and bolt together using the corner bracket as shown in Fig. 9. 3. Fasten cross supports, when required, per the diawings with supplied screws as shown in Fig. 10. Before installing roof curb, check overall unit length. Figure 11 shows AHU (air-handling unit) curb pocket dimensions. CURB GASKET (OPTIONAL) \ \ \ \ \ \ \ \, CURB SPLICE PLATE \ I IMPORTANT: attempting to rigVedly the unitinstalled and install curb it ondimensions the curb. before ] Fig. 8 -- Splice Plate Usage - FLAT WASHER HEX HEAD BOLT SEAL STRIP \\ END \ \ \ HEX NUT J LOCK WASHER \ \ \ \ UNIT CURB CORNER BRACKET Fig. 9 -- Corner Bracket 36 Due to the pressure capabilities of the 39 sedes air handlers, duct connections must be gasketed and screwed to the unit to prevent leakage. No provisions have been made to attach the ductwork to the curb. Fabricate inlet and discharge according to the unit configuration. Dimensions for inlet and disch_uge locations ale shown in diawings produced in AHUBuilder® program. \ The return and supply ducts must be supported independently from the unit. Do not exert weight or downw_ud force on the unit other than minimal force required to attach ductwoN. UNIT CURB Before the unit is installed, gasketing must be installed between the curb and unit as shown in Fig. 12. This gasket material is supplied by the curb manufacturel: If gasket is not supplied with the curb, recommended field-supplied gasket matedal is 1/2-in. thick by 2-in. wide closed cell neoprene. \ \ \\\\\\\\\\ When curb is installed, place gasket on curb without stretching or overlapping the material, which can cause gaps or leaks. Butt _dljoints evenly and avoid creating gaps where water can leak into the curb. Make sum semns in gasket matedal overlap seams in the curb rail. See Fig. 12 for installation details. CURB CHANNEL Fig. 10- Fasten Cross Supports After gasket is in place, rig unit into position as described in Rigging and Handling section. Ix_cate unit on curb so it is conectly oriented with respect to curb inlet and disch_uge locations. On curb installations, lower unit directly into place, ensuring that the roof curb gasket does not shill or curl. Pier or Beam Mount--As an _dternative to curb mounting, units can also be mounted on I-bemns or piers. For units mounted on I-beams, the beams must run the continuous length of the unit. If seismic criteria apply, crosspieces must be added between the beams according to seismic calculations. For pier-mounted units, one pier must be installed in each corner of the unit at the junction of the baserail comers. A minimum of 4 piers can be used for size 03-61 units up to 8 II long. o4 Fig. 11 -- Curb Pocket Dimensions (Size 03-30 Typical) BUTT JOINTS, DO For each additional 8 II of length for size 03-61 units, inst_dl one additional pier on each side of the unit underneath the basemils. See Fig. 13 for a typical installation. GASKET SEAM / WRONG METHOD RAIL SEAM /GASKET SEAM RIGHT METHOD / RAIL SEAM Fig. 12 -- Install Gasketing 37 BEAM MOUNT PIERMOUNT* ( 7 r QUANTITY OF PIERS REQUIRED *Minimum number of piers shown for pier-mounted unit. See table on right for number of equally spaced piers required. For each additional 8 ft of unit length, add 2 piers. UNIT LENGTH "L", FT 0-8 I 9-16 17-24 4 I 6 8 Fig. 13 -- Pier or Beam Mounting INSTALLATION 4. This section describes how to install 39M units, components, and component p_uts. Units specified on a single order are shipped with most components assembled in the specified airflow direction. The assembled unit is attached to a single shipping skid (30-ft maximum length). When an upper component exceeds the 108-in. maximum height limit, it is shipped out of its operating position on the unit skid or on a separate skid. Some component paris also require assembly or adjustment; see the section on each component type for specific instructions. Do not overtighten, damage to latch could occm: The latch is not intended to pull units together over a distance. Latch is designed for retention after units have been positioned properly and only after base lails have been secured. Indoor Unit/Section Connection -- Indoor units _u'e connected together using 2 different methods -- screws and "T' latch cam latches. Refer to Fig. 14 and 15 for T-latch assembly details. Connect units as follows: NOTE: [f T-latch becomes &_maged o1"inoperable, fasten section frmnes using clearance and engagement holes located below latch. 1. Remove shipping plates from entering and leaving face of sections. Replace 2 screws in baserail directly under corner feet only. otherwise 2 inboard screws will not allow a flush connection. See Fig. 16. 2. Rig and align units so that sides and tops are flush and holes are aligned. 3. Fasten base rails together supplied h_udware. at the lifting brackets Indoor units secured with "T" latches: Turn "T" latch (indicated by red hex socket access) clockwise using a 5/16-in. hex wrench until latch fully engages. The latch rotates 270 degrees. The first 90 degrees of rotation positions the T-latch into a se;ding position on the fralne. The second 180-degree rotation pulls the T-latch tight, compressing the gasket which creates the frmne se_d. 5. Units secured with screws: Remove side and top panels flom unit by turning panel latches (indicated by black hex socket access with arrow indicator). Fasten and secure base rails. NOTE: Upstream sections have a l-in. cle_uance hole on the inner surface of the frame member to provide access to the 5/l(,-in. fastening screw hole. using 38 6. Insertscrew through these holestoengage mating hole. Followperimeter ofunitandsecure. 7. Re-inst_fll panelsandsecure panellatches. Thepanel latchincorporates camactionon eachedge(topand bottom) tosecure thepanel. SeeFig.17.Thepanellatch assembly hasa 90degree rotation witha clickdetent feature thatdetents at0and90degrees. Thearrowindicator displays the latch position. COMPONENT SECTION A COMPONENT SECTION B I DETAIL A Fig. 14 -- T-Latch Fig. 17- Panel Latch Assembly Assembly NOTE: Panel latches have an indicator anow highlighted in the face of the latch and that arrow must point tow_ud the panel to assure that panel is fully secured. Ensure the latch arrow is in its proper position prior to unit start-up. Outdoor Unit -- Outdoor units are either shipped in one piece or with minimal shipping splits. Refer to the shipping split label attached to the unit. _ 'ENGAGEMENT HOLE Fig. 15 -- T-Latch Receptacle (End View) DETAIL B SEE FIG. 17 DETAIL B SIDE PANEL FRAME MEMBER DETAIL DETAI L C jSHIPPING PLATE Fig. 16 -- Section Frame Assembly 39 Duct Connections • MIXING BOX/INLET PLENUM/DISCHARGE PLENUM --Attach the ductwork to the box fi'alne rails with sheet metal screws as shown in Fig. 18. Ductwork should be flanged out as close to the dmnper frmned opening as possible. Screws with weatherproof washers and a bead of silicone around the duct flange must be used for outdoor applications. Do not remove the screws retaining the c_kLmper fi:Lme; the dmnper will fall out. MIXING BOX/INLET PLENUM (Bottom) -- Bottom damper equipped air-handling units have tin insulated dmnper duct connection sleeve fllat extends to the bottom of the basenill on 39MN indoor units and to the cm_o pocket on 39MW outdoor units. Sizes 36-61 include intermediate frame members. When cutting the discharge opening for the plenum fan, do not cut through any intermediate frame membec Typical duct locations are shown in Fig. 21. Once the discharge locations are selected and cut, the duct connections can be fabricated. Install field-supplied duct flanges and frmning channels to smooth the airflow leaving the discharge opening. Two of the channels should extend the width or height of file cabinet to provide additional cabinet support. For indoor units, apply I/2 in. thick by 1 I/2 in. wide closed cell neoprene gasketing or run a bead of silicone to the damper duct flange. Flange the ductwork out no more than 11/4 in. and screw file flanged ductwork to the &tmper duct flange under the unit. For curb mounted outdoor units, refer to the curb submitttd drawings. Return ductwork may be flanged outward and attached to the roof curb. Field-supplied stiffeners may be required to properly support the long edges of the duct. Apply 1/2in. flfick by 11/2in. wide closed cell neoprene gasketing or run a bead of silicone to the damper duct flange. FAN DISCHARGE CONNECTIONS (Except Plenum Fans)--Dischm'ge tfir ducts must be attached directly to the discharge side of the unit. This applies to both indoor and outdoor units! Use care when making turns and transitions in ductwork to avoid excessive air fiiction. Duct elbows should contain turning vanes. See Fig. 19. Fig. 18- T______URNIN G Dnctwork connected to the fan discharge should run in a straight line for at least 2.5 times the outlet diameter dimensions and should not be reduced in cross-section. See Fig. 20. Duct turns should be in file salne direction as fan rotation to minimize any negative system effects. Apply 1/2 in. thick by 11/2 in. wide closed cell neoprene gasketing or run a bead of silicone mound the fan discharge. Fltmge the ductwork out no more than 11/4 in. and screw the flanged ductwork to the fan discharge. BOTTOM RETURN FAN CONNECTIONS -- Return tfir ducts must be attached directly to the return side of the unit. This applies to both indoor and outdoor units! Use care when making turns and transitions in ductwork to avoid excessive tfir friction. Duct elbows should contain turning vanes. See Fig. 19. PLENUM FAN DUCT CONNECTIONS -- Plenum fans tue designed for draw-thru or blow-thru operation. Draw-thru fan sections have closed panels on _dl sides except for the fan inlet side. On blow-thru fan sections, the panel on file end opposite the inlet is omitted so that components such as coil or filter sections can be added downstremn fiom the plenum fan. DRAW-THRU PLENUM FAN DISCHARGE FABRICATION -- Duct openings for draw-thru plenum fans must be field fabricated. They should be located in the plenum fan section according to the following guidelines: • • • Mixing Box Ductwork Attachment I NOTLESS THAN 2-1/2 FAN DIA. l _--i ,,.%1 J / I I I I I I I I _ VANES AIRFLOW NOTE: Make turns in the same direction as fan rotation. Fig. 19- Recommended Discharge Duct Arrangement When Turns are Required NOT LESS THAN 2-1/2 FAN DIA. SUPPLY DUCT Locate discharge openings in side or top panels; the end panel opposite the inlet will have a higher pressure drop per the explanation in the 39M Product Data manual. Locate discharge openings on the side or top panels between the fan wheel and end panel opposite the inlet. Do not locate discharges in the direct path of airflow flom the wheel. Avoid locating the discharge opening on the motor side of the fan section. If a discharge on the motor side is necessary, locate the opening near the top of the cabinet. DUCT TRANSITION 30° MAXIMUM Fig. 20 -- Duct Connections 40 FIELD _SUPPLIED DUCTWOR t J / A _.A FIELD FABRICATED ANGLES FOR DUCTWORK FIELD FABRICATED SUPPORT CHANNELS AS REQUIRED PER OPENING SIZE OR LOCATION CONNECTION UNIT OUTER CASING INSULATION /' AIRFLOW INTERNAL DOUBLE WALL PANEL SECTION A-A Fig. 21 -- Discharge Fabrication, 41 Draw-Thru Plenum Fans Panel Cutting -- The 39M unit's double-wall foam-filled panels require speci_d attention when cutting and or penetrating. 1. Take ctu'e in planning before penetrating any panel with electrical conduit, hydionic piping, sensor pickups or wiring. Once these are routed through a panel, for _dl practiced purposes, it becomes a fixed panel that is not easily removed for service access. 2. In some cases it will be possible for smaller conduits (l/2-in. or 3/4-in.) to enter the cabinet where individual sections are joined togethel: Inspect the selected area ctuefully to be certain that you do not encounter panel kitches, "T-kitches," or section joining screws. Once the conduit is in place, it must be securely sealed, watertight and airtight, to prevent ANY infiltration. Penetrations tu'e typic_dly located in one of the existing "fixed" panels, such as the fan discharge panel, or the coil connection panel to maximize the number of removable/ service panels. When it is necessary to penetrate the panel for wiring or piping entry, make certain that the entry point will not interfere with future component servicing, block access doors, or obstruct airflow. 3. 4. Rig the zone damper section and lift it into position on (vertical discharge) or next to (horizontal discharge) the gasketed cooling and heating coil sections. 4. Fasten the &_mper section to the coil sections supplied I14-14 x 314-in. sheet meted screws. 5. Install control shaft and bearing for each individual zone after cutting linkage (for the job specific zone application). using the be split for equal airflow through Dampers -- All face and bypass damper sections are shipped fully asselnbledi Hat channels are necessary for damper support. DO NOT remove (see Fig. 23). Unit sizes 03-12 are built with a single damper assembly, sizes 14-61 have two dmnper assemblies linked via a jackshaft. Damper cmnkarms have 90 degrees of travel from fully open to fully closed positions and are adjustable to suit conditions. Refer to Fig. 24 and 25 for details. Actuators must be mounted directly to the &_mper shaft. Removed of crankarms is necessary for direct connection actuator use. Refer to Table 18 for operating torque requirements. Facto U duct colku's and damper assemblies are for attaching ductwork only and must NOT be used to support the duct's weight. Weight beguing deflection can increase torque necessgu-y to operated dmnpers, or bind them pro_ venting aW movement. NOTE: Small quantities of locally available commerci;d canned foam may be used, if necess;uy, to complete minor repairs. Significant patching may justify ordering replacement panels instead. Refer to Fig. 22 and install the section as follows: 1. Remove the screws holding the zone damper section to the heating coil section and remove the lag screws holding the damper to the shipping skid. ZONE DAMPER ASSEMBLY, ...... VERTICAL _._ ..... POSITION COIL DISCHARGE --_--,-_..r,-----_ _ 7.---", '1 ' HOT/COLD PARTITION DECK PANEL CUT BAR TO SEPARATE ZONES ZONE DAMPER ASSEMBLY HORIZONTAL D SCHARGE POSITION SECTION _ FAN SECTION __ DUCT WORK DUCT CLIP ZONE DIVIDER ATTACH FOR EACH ZONE (RUSKIN PART NO. 10-020569-00B) "W" TO ATFACH ZONESTRIP DUCTWORK-SEE [ DETAIL "W"STRIP DETAIL Fig. 22 -- Zone Damper Assembly each Face and Bypass Camlully remove the foam. The hole should be lined or sleeved to confine the foam, and the penetration should be sealed, both inside and out, to eliminate all possibility of infiltration or leakage. -- 3. 6. Zones should dampel: Drill a small pilot hole completely through the panel. Use of a sharp hole saw or, if appropriate, a Unishea( r_'_ cutting tool or sheet metal nibbler to cut the hole or opening from each side. Zone Damper Section Place the supplied I/4-in. thick x 1l/:-in, gley fomn gasket around the perimeter of the cooling and heating coil section discharges. Use two gasket strips on partition panels to obtain double width. Control shaft extensions gue bagged and wrapped to the inside of the zone dmnper blades. Additional fieldsupplied shaft extensions may be ordered from local Ruskin suppliek Dut no. 10-020569-00B. Do not use a cutting torah or open flmne on or near the fan. Dmnage to the panel may occm: 5. 2. Details 42 (Horizontal Discharge Shown) HAT CHANNEL Fig. 23 -- Face and Bypass Section Detail ZONE 39M UNIT SIZE A DIMENSIONS(In.) B DAMPER DETAILS OTY OF ZONES C 06 28.50 41.50 12 08 28.50 49.50 10 28.50 62.50 12 34.50 14 OTY OF EXTENSION S 4 12 7 4 12 10 6 62.50 15 10 6 34.50 67.50 15 10 6 17 34.50 74.50 15 12 7 21 40.50 74.50 18 12 7 25 40.50 81.50 18 13 8 30 40.50 99.50 18 16 10 36 52.50 104.50 24 17 10 40 52.50 104.50 24 17 10 50 56.50 112.50 26 18 12 61 68.50 112.50 32 18 12 SHAFT AIR FLOW FACE VIEW END VIEW 7 q t pIZ BLANK OFF TOP VIEW PLATE SECTION A-A NOTE: All dimensions in inches unless otherwise noted, Fig. 24 -- Zone Damper Section 43 Details KITS MIXING BOX,EXHAUST BOX,ANDEXTERNAL BYPASS DAMPER DETAILS UNIT SIZE DETAIL (SECTIONS) JACKSHAFT 03 1 25.75 06 1 38.75 08 1 46.75 10 1 12 DIAMETER SIDE DAMPER DETAILS UNIT SIZE DETAIL (SECTIONS) (In.) JACKSHAFT DIAMETER 1/2 03 1 14 18 V2 14 1/2 06 1 20 26 V2 14 1/2 08 1 20 29 V2 59.75 14 1 10 1 26 29 1 1 59.75 14 1 12 1 26 36 1 14 2 64.75 16.75 1 14 1 32 36 1 17 2 71.75 16.75 1 17 2 32 39 1 21 2 71.75 20 1 21 2 32 49 1 25 2 78.75 20 1 25 2 38 49 1 30 2 96.75 20 1 30 2 44 49 1 36 3 101.75 29 1 36 2 50 60 1 40 3 101.75 32 1 40 2 50 66 1 50 3 109.75 35 1 50 2 56 76 1 61 3 109.75 44 1 61 3 56 91 1 10.75 A A Aq • ° • ° • * I A _' / (j 2, AJ-J A i -u j! DETAIL 1 FACE VIEW DETAIL 2 FACE VIEW A _ [] " .... !O. i_ .I --_d _1..i [] ,o ..... []' .I,_I..44"I u .I,H, .. 7_i o ° ° _llP_°_'° [] [] [] [] [] ° DETAIL 3 FACE VIEW B 1 1/2 --T AIRFOIL AIRFOIL -BLADES /TO OPEN °_ ¢ TO OPEN C_ BLADES BRA AIR SECTION A-A 1/2-in, JACKSHAFT PREMIUM DAMPER I--5"'--1_ SECTION A-A 1-in, JACKSHAFT PREMIUM DAMPER FLOW L STANDARD f % If BLADES RIGHT SIDE VIEW / °_] /TO OPEN NOTE: All dimensions in inches unless otherwise noted. TO OPEN B SECTION A-A 1/2-in, JACKSHAFT STANDARD DAMPER SECTION A-A 1-in, JACKSHAFT STANDARD DAMPER Fig. 25 -- Mixing Box, Filter Mixing Box, Exhaust Box and External Bypass Damper Details 44 (In.) Mixing Box/Filter Mixing Box Damper Linkage linkages, determine the rotation required to open the outdoortdr dampel: Ensure the actuator spring return fully closes the outdoor-air dampel: If more than 2 actuators are used, they must be installed in equal numbers on each jackshaft. To properly set these dampers, determine the rotation required for each damper and mount the actuatol_ so that the spring feature will open the return air damper and close the outdoor-air dampel: Ix)ck each damper actuator to the jackshaft. Remove any factory-supplied connecting linkage between the outdoor air and return-tdr dampers. Failure to do so will damage the actuatol_. No additional linkages are required for these applications. Exhaust damper boxes me shipped with dampers in the closed position. All dmnper cmnkarms have 90 degrees travel from open to closed. They may be adjusted to suit actuator location. DO NOT mount damper actuators on the unit panels, actuators me shaft mount only. See Table 18 for operating torque requirements. It is important to properly link the outdoor air and return air dampel_. Failure to do so may cause mixing problems, stratification, or coil freezing under some conditions, especially in combination type filter mixing boxes. Refer to Fig. 26 for typical damper necting rod position. _m'angement and con- CONTROL DAMPERS -- Control dampers may be operated with pneumatic or electric actuators. These items should be set up in accordance with the control manufactmers installation instructions. DAMPER LINKAGE ADJUSTMENT-After the airhandling unit has been powered, the dampers should be checked to ensure they move freely and close tightly, adjustment of the linkage may be required. LINKAGE ADJUSTMENT ZONE DAMPER LINKAGE (Fig. 22 and 24) -- Note that damper control levers and a common operating bin are factoly installed on upper end of damper shafts on top of zoning damper assembly. To facilitate the installation of field-supplied damper operators, the operating bar may be cut and the control levers repositioned as follows: 1. With the damper actuator unpowered and the damper linkage disconnected, rotate the outdoor air dmnper so that it is fully closed. Make sure the spring return actuator has completed its stroke (with power disconnected this will be achieved). The return air damper should be lidly open at this point. 2. Tighten the actuator on the damper jackshaft, ensure all linkage is connected, secure and moves freely. 3. With power applied to the actuatol: check for a complete stroke and free movement in the dampers and damper linkage. Damper operation may supported by the unit. one damper impaired must be lidly Top and rear dampers me shipped with both dampers in closed position. Ix)osen the swivel on the interconnecting linkage bar and fully open rear dmnper, leaving top dmnper closed. Retighten the swivel. Mixing Box Damper Actuators-- Table 18 -- Damper Operating Torque (Ib) 39M UNIT SIZE 03 Zone Damper Mixing orExhaustBox Side MixingorExhaustBox Airflow Measuring Damper 06 08 10 12 4 4 4 5 5 5 5 5 5 7 7 8 10 13 26 32 41 41 53 58 70 77 94 143 158 187 235 12 25 -- ductwork is The 39M mixing boxes can be supplied with direct mounted dmnper actuators. Refer to Fig. 27 for typical actuator mounting. Actuators me also available for field installation. See Field Supplied and Inst_flled Actuators section for more information. Refer to Table 18 for damper operating torque. To ensure torque is transmitted equally to both damper sections, actuator must be connected to the jackshaft that diives the interconnecting linkage bin: Connection to any other shaft is not lecommendedi Certain dmnper combinations require that dual actuators or bellcrank linkages be field-provided when jack shafts are 90 degree opposed. This may occur when there is a combination of end dampers with either top or bottom dampers. FIELD SUPPLIED AND INSTALLED ACTUATORS -If one or two actuators are used, they must be mounted to the outdoor-air damper jackshaft. To properly set the connecting COMPONENT if 1. Check job prints to determine number and size of zones required and damper operator locations. 2. Cut and remove portion of operating bar between zones as required. 3. Inst_fll actuators on field-fabricated support brackets. Connect actuator linkage to the center axle of interconnecting zones. 4. Adjust actuator for correct damper operation. Be sure actuatol: linkage, and dampel_ operate fieely. See Table 18 for operating torque requirements. Dampers and linkage must be checked prior to applying powel: Make certain that there are no obstructions that could interfere with the operation of the dampers. NOTE: While adjusting linkage, open and the other fully closed. be 14 17 21 25 30 36 40 50 61 28 37 46 56 61 76 91 105 146 160 207 248 5 9 9 9 16 16 16 29 29 29 N/A N/A N/A N/A Internal Face and Bypass 21 32 45 57 78 85 103 129 142 174 195 232 251 304 External Face and Bypass 29 44 59 76 96 104 126 161 176 217 282 312 390 470 NOTES: 1. Damper shaft moves 90 degrees from open to close. 2. Operating torques is shown for one damper. Multiply the value shown by the number of dampers for total with one actuator. 45 DIRECT COUPLED ACTUATOR (SIDE MIXING BOX) ACTUATOR AND JACKSHAFT ARE REPRESENTATIVE ONLY (TYPICAL) ONE ACTUATOR ONLY WHEN USED WITH LINKAGE -_ AIR ROTATIO TO OPEN AIR FLOW LINKAGE ASY '_ LINKAGE ASY ROTATI( [ .TO OPE .__.. LINKAGE ASY LOCATION TYPICAL TOP & REAR OR SIDE & REAR TOP & BOTTOM OR SIDE & SIDE REAR & BOTTOM . >ROTAT'O ROTATION TO OPEN TO OPEN AIR AIR AIR ROTATION TO OPEN REAR ONLY BOTTOM ONLY TOP ONLY Fig. 26 -- Mixing Box/Filter Mixing Box, Typical Damper Arrangements [ i-=-_r_ zr _ I DIA JACKSHAFT BNLY ! Fig. 27 -- Typical Mixing Box Actuator Mounting 46 (Size 14 Shown) Vertical Draw-Thru Units 4. Rig the fan section using the lilting brackets and place it on top of the coil section. NOTE: For units with basemil, the 4 brackets that were repositioned emlier should be aligned with the appropriate slots in the base rail of the fan section. Before setting the fan section on the coil section, remove right and left side panels from coil section. NOTE: Size 21-61 vertical units that exceed the 108-in. maximum height or units with a vertical fan shipping split are shipped with the fan out of its operating position, separate from the vertical coil section. See Fig. 28A and 28B. The unit is secured to a wooden skid with lag screws. Remove screws before lifting the unit. NOTE: Do not remove the fan holddown bolts until the section is instaUed on the coil section. 5. For units without baserail, locate 1-in. tool clearance hole in underside of top rail of coil section on each side. 6. Insert a pin or punch to assist alignment of corresponding holes of fan section while lowering fan section, if needed. 7. Secure the fan and coil sections together using the supplied I14x 314-in.long sheet metal screws. The securing points will be on the bottom of each side and front top rail of the coil section for units without baserail (Fig. 28B). For units with baserail, securing points me located in the side of the baserail (Fig. 28A). NOTE: Do not remove the front panel of the coil section until the side panels _uereinstalled. Secure brackets from top of coil section to fan section base rail using 2 screws each. 1. For units with baserail, remove the 4 brackets securing the top panel of file cooling section and reposition them to the existing holes with the long flange in a vertical position flush with the outer panel. 2. Attach the I/8-in. thick by 3/4-in. wide gray gasket supplied with the unit to the top perimeter opening of the vertical coil section. 3. For units with baseraU, attach joining wifll unit) to top dischmge opening included with unit. collar (supplied using hardware VERTICAL FAN SECTION "_BRACK[T I)ETAIL Y SCALE: {:4 ASSEMBLEDPOSITION OF BRACKET WHEN UNIT IS SN{PPgO Ok ASSEMBLED STACK{D _BASE SEE DEFA}L RA{ ASS[MB Y ys _JOINING COLLAR FOR VERIICAL SUPPLY _AN ....... VERTICA{ COl/ SECT{ON BE]AIL X SCALE 1:4 ASSEMBLED_OSII}ON OF BRACKEF WHEN VERIICAL FAN SECTION IS SNIPPE_ SEPARATE \ _ Fig. 28A -- Vertical Fan Installation 47 with Baserail BASE RAI{ ASSEmBlY REMOVE LIFTING BRACKETS AFTER ASSEMBLING THE UPPER SECTION TO THE LOWER SECTION USE PLUG BUTTONS (BAG ASSEMBLY 39MA42000901 ) TO FILL SCREW HOLES IN FRAME. PLACE GASKET ON LOWER SECTION BEFORE SETTING UPPER SECTION UNTO LOWER SECTION _" / USE 1/4-14 X 3/4 LG SHEET METAL SCREWS TO FASTEN UPPER Fig. 28B -- Vertical Fan Installation without Baserail Fan Sled Disassembly -- In some necessary to remove the fan sled fiom the down into smaller components. See Tables for maximum complete fan sled dimensions dimensions. To remove 1. the fan sled: Remove all of the panels the fan discharge panel. from the fan section except for 2. Disconnect unscrewing fan housing. 3. On larger units, the fan sled may be extremely heavy. Remove file top and vertical frame members of the fan section by removing the 4 screws from each frame to corner piece connection. 4. 5. cases, it may be unit and break it 19-21 and Fig. 29 and housing only the vibration absorbent discharge seal by the seal channels fl'om the discharge of the Remove the fan discharge panel. If complete fan sled removal is required, unscrew holding the isolator base to the bottom of the unit. Disassemble fan and fan housing in place and/or affix appropriate rigging to remove tile required components noting diagrammatically where each component is attached. Components should be removed in the following order: a. Belts and sheaves b. Motor c. Fan shall d. Fan wheel (forward curved fan wheels are removed through the fan discharge opening, airfoil wheels are removed through the side of the housing after removal of the drive side inlet volute) e. Fan housing NOTE: Install the preceding components bolts 48 in the reverse ordel: Fan Sled Dimensions -- Table 21 -- Plenum Fan Dimensions (in.) See Tables 19-21 and Fig. 29 for Fan Sled dimensions. UNIT SIZE 39M Table 19 -- Airfoil Fan Dimensions (in.) UNIT SIZE 39M ARRANGEMENT FAN SLED ASSEMBLY (See Fig. 29) Len_lth Width 18.6 21.0 03 All Length 41 .O Width 26.4 Height 23.7 06 All 42.5 36.0 26.2 Hei_lht 21.9 08 All 24.8 46.5 29.1 10 All 26.3 53.3 31.3 03 All 06 All 36.5 33.5 28.7 22.4 24.0 26.8 12 All 30.1 58.3 36.7 08 10 All All 29.8 29.8 45.5 58.5 31.8 31.8 24.6 24.6 26.3 26.3 29.3 29.3 14 All 30.1 58.3 36.7 17 All 32.6 62.5 40.1 12 All 35.8 58.5 38.8 29.6 30.3 36.0 21 All 38.3 66.3 41.4 14 All 41.8 63.5 38.8 29.6 30.3 36.0 25 All 42.3 70.3 45.4 17 All 41.8 70.5 41.8 32.5 33.8 39.6 30 All 41.0 75.8 48.9 21 All 41.7 72.0 51.8 35.9 36.5 43.6 36 All 48.9 91.4 54.4 25 All 53.8 77.5 51.8 39.5 39.8 48.1 91.4 54.4 All 53.8 95.5 51.8 39.5 39.8 48.1 40 48.9 30 Supply Std Ret/Exh Std 48.9 91.4 58.3 36 Supply Std Ret/Exh Std 56.3 56.3 100.5 100.5 62.8 62.8 43.8 47.8 43.3 48.5 52.8 58.1 5O Supply Std Ret/Exh Std 57.4 99.4 58.4 57.4 99.4 64.0 Supply Std Ret/Exh Std 62.3 62.3 100.5 100.5 68.8 68.8 47.8 52.9 48.5 53.0 58.1 64.9 61 Supply Std Ret/Exh Std 57.4 99.4 64.0 57.4 99.4 70.0 Supply Std Ret/Exh Std 68.3 68.3 108.5 108.5 78.8 78.8 52.9 57.9 53.0 57.5 64.9 71.0 Supply Std Ret/Exh Std 74.3 74.3 108.5 108.5 93.8 93.8 57.9 65.9 57.5 62.8 71.0 78.8 5O Hei_lht 28.8 FAN SLED ASSEMBLY (See Fig. 29) Length 35.5 40 Width 23.5 FRAMED BLOWER WITHOUT SLED ARRANGEMENT NOTE: Different fan discharge positions have different dimensions. The values shown are for the largest overall dimensions. Table 20 -- Forward Curve Fan Dimensions (in.) UNIT SIZE 39M 03 06 08 10 12 14 17 21 25 30 36 40 5O 61 ARRANGEMENT FAN SLED ASSEMBLY (See Fig. 29) All - Horizontal Length 17.5 Width 26.0 FRAMED BLOWER WITHOUT SLED Height 20.2 Length 16.7 Width 15.1 Height 16.7 All - Vertical 34.0 25.0 20.2 16.7 15.1 16.7 All - Horizontal 23.5 39.0 22.6 18.6 18.8 18.6 All-Vertical 34.0 25.0 22.1 18.6 18.8 18.6 Sup/Ret Std 28.5 47.0 25.1 21.6 23.9 21.6 Supply Small 28.5 47.0 20.6 18.6 18.8 18.6 Sup/Ret Std 28.5 60.0 29.0 25.5 27.9 25.5 Supply Small 28.5 60.0 23.6 21.6 23.9 21.6 Sup/Ret Std 34.5 60.0 30.2 25.5 27.9 25.5 Supply Small 34.5 60.0 25.8 21.6 22.9 21.6 Sup/Ret Std 40.5 65.0 35.1 30.4 32.5 30.4 Supply Small 40.5 65.0 30.2 25.5 27.9 25.5 Sup/Ret Std 40.5 72.0 35.1 30.4 32.5 30.4 Supply Small 40.5 72.0 30.2 25.5 27.9 25.5 Sup/Ret Std 40.5 72.0 42.7 38.0 33.3 38.0 Supply Small 40.5 72.0 30.2 25.5 27.9 25.5 Sup/Ret Std 52.5 79.0 43.2 38.0 33.3 38.0 Supply Small 52.5 79.0 43.2 38.0 30.3 38.0 Sup/Ret Std 52.5 97.0 43.2 38.0 37.3 38.0 Supply Small 52.5 97.0 43.2 38.0 35.3 38.0 Sup/Ret Std 53.8 100.5 62.8 46.8 43.5 46.8 Supply Small 53.8 100.5 62.8 41.5 39.8 41.5 Sup/Ret Std 53.8 100.5 68.8 46.8 43.5 46.8 Supply Small 53.8 100.5 68.8 46.8 38.5 46.8 Sup/Ret Std 58.3 108.5 78.8 51.5 52.3 51.5 Supply Small 58.3 108.5 78.8 51.5 46.8 51.5 Sup/Ret Std 56.8 108.5 93.8 55.5 54.3 55.5 Supply Small 56.8 108.5 93.8 51.5 52.3 51.5 Fig. 29 -- Fan Sled 49 Fan Motors and Drives -- When installing motors in the field, locate the electrical junction box tow;ud file center of the unit. This ammgement is required for correct belt tension. Use the smallest mounting holes in the mounting base that will accommodate the motor and provide minimum oveflmng. SHAFT BEARING / DRIVEN SHEAVE Tighten the motor holddown bolts. Refer to Tables 2A-2D for fan scroll inlet cone dimensions. FAN SHAFT ,d -'11 OVERHAHG JUNCTION BOX CONDENSATE PREVENTION -When air handlers ale installed outdoors in a high humidity environment or indoors whele the apparatus room is used as a fi'esh air plenum, precautions must be taken to prevent condensation from forming inside the junction box of the internally mounted motor. SHEAVE Stan&ud installation practice is to mount the motor starter or fused disconnect box adjacent to the air handler and enclose the power wiring to the motor in flexible conduit. D_VE -_ EXCESSIVE OVERHANG The sheet metal housing of the disconnect switch or motor strutter is not airtight (even when a box meeting NEMA [National Electrical Manufacturel_ Association] IV stan&uds is used). Thus, warm moist air can migrate through the flexible conduit to the junction box on the motol: With the motor located inside the unit, the motor temperature is that of the cool supply air; thus, condensate can form inside the junction box and, possibly, on the live terminal lugs. ! - MINIMUM OVERHANG Use a nonconductive, non-hmdening sealant. Permagum 0nanufactuled by Schnee Morehead) or sealing compound, thumb grade 0nanufactured by Calgon), tue acceptable materials. FLEXIBLE / POOR INSTALLATION To prevent the moist air from migrating through the conduit to the motor, seal the power wires inside the flexible conduit at the motor starter or fused disconnect (Fig. 30). SEAL AIRTIGHT MOTOR / CONDUIT r--] MOTOR MINIMUM OVERHANG 1 _- ,= DUIT FUSED DISCONNECT TYPICAL MOTORS BETTER INSTALLATION Fig. 30 -- Sealing Power Wires in Flexible Conduit Motor Power Wiring--The Fig. 31 -- Determining Sheave-Shaft Overhang After 24 hours of unit operation, the &'ive belts may stretch. Check the belt tension after 24 hours of operation and adjust if necessary. Periodically check belt tension throughout the run-in period, which is normally the initial 72 hours of operation. ALIGNMENT -- Make sure that fan shafts and motor shafts are pmallel and level. The most common causes of misalignment are nonparallel shafts and improperly located sheaves. Where shafts me not pmallel, belts on one side are drawn tighter and pull more than their share of the load. As a result, these belts wear out faster, requiring the entire set to be replaced before it has given maximum service. If misalignment is in the sheave, belts enter and leave the grooves at an angle, causing excessive belt and sheave weal: fan section is provided with a decal indicating the recommended location to drill or punch hole(s) to accommodate an electrical conduit for the fan-motor wiring. The decal is located on file motor side, approximately 4-in. in fiom the side and 4-in. down fi_)m the top of the corner above where the motor will be installed. Where possible, the conduit should be installed in a panel which will not be removed, such as the discharge panel. MOTOR OVERLOAD PROTECTION -- Fan-motor starters and overload protectors me field-supplied and installed. A label on the fan motor indicates the correct size of the overload protectors required to be installed in file motor startel: SheavesFactory-supplied drives are pre-aligned and tensioned, however. Carrier recommends checking the belt tension and alignment before staffing the unit. Always check the drive alignment after adjusting belt tension. To install sheaves on the fan or motor shaft, remove any rust-prevenfive coating on the shaft. Make sure the shaft is clean and fi'ee of burrs. Add grease or lubricant to bore of sheave before installing. Mount sheave on the shaft; to prevent bearing damage, do not use excessive force (i.e., a hmnmer). Place sheaves for minimum overhang (see Fig. 31 ). Each factory-assembled fan, shaft, and chive sheave assembly is precision aligned and balanced. If excessive unit vibration occm_ after field replacement of sheaves, the unit should be rebalanced. To change the drive ratio, reselect and replace the motor sheave, not the fan sheave. 1. Shaft alignment can be checked by measuring the distance between the shafts at 3 or mole locations. If the distances are equal, then the shafts ale parallel. 2. Sheave Alignment: Fixed sheaves -- To check the location of the fixed sheaves on the shafts, a straightedge or a piece of string can be used. If the sheaves are properly aligned, the string will touch them at the points indicated by the mTOWS in Fig. 32. Adjustable sheaves -- To check the location of adjustable sheave on shaft, make sure that the centerlines of both sheaves are in line and palallel with the beming suppofl channel. See Fig. 32. Adjustable pitch drives me installed on the motor shaft. 5O 3. Tighten belts by turning motor-adjusting jackscrews. Turn each jackscrew an equal number of turns. 4. Equalize belt slack so that it is on the same side of belt for _dl belts. Failure to do so may result in uneven belt stretching. 5. Tension new drives at the maximum deflection force recommended (Fig. 33). 6. On current production, the correct tension information is listed on the fan diive label. For older equipment or for units with field-modified diives, use the deflection formula given in the example below and the tension data from Fig. 33. EXAMPLE: Do not exceed maxilnum fan speed rpm with adjustable sheave. 3. Rotate each sheave one-half whether the sheave is wobbly Correct any misalignment. revolution to determine or the diive shaft is bent. 4. With sheaves aligned, tighten cap screws evenly and progressively. NOTE: There should be a I/s-in. to l/4-in, gap between the mating part hub and the bushing flange. If gap is closed, the bushing is probably the wrong size. Given: 5. With tapeMock bushed hubs, be sure the bushing bolts are tightened evenly to prevent side-to-side pulley wobble. Check by rotating sheaves and rechecking sheave alignlnent. When substituting field-supplied sheaves for factory-supplied sheaves, consider that fan shaft sheave has been facto q balanced with fan and shaft as an assembly. For this reason, substitution of motor sheave is preferable for final speed adjustment. Belt Span 16 in. Belt Cross-Section Small Sheave PD Deflection Solution: a. 5 in. = Belt Span/64 From Fig. 33 find that deflection force for type A, super belt with 5-in. small sheave PD is 4 to 51/2 lb. Deflection = 16/64 b. CENTER LINES MUST COINCIDE A, Super Belt = l/4-in. LINES MUST BE PARALLEL STRI NG c. Increase or decrease belt tension until force required for l/4-in, deflection is 5 lb. Check belt tension at least twice during first operating day. Readjust as required to maintain belt tension within the recommended range. With correct belt tension, belts may slip and squeal momentarily on strut-up. This slippage is notated and disappe_u's after unit roaches operating speed. Excessive belt tension shortens belt life and may cause bearing and shaft damage. After run-in, set belt tension at lowest tension at which belts will not slip during operation. BEARING SUPPORT CHANNEL LINES MUST BE PARALLEL FIXED SHEAVE BELT CROSS SECTION ADJUSTABLE SHEAVE Fig. 32 -- Sheave Alignment A B V-Belts -- When inst_dling or replacing belts, always use a complete set of new belts. Mixing old and new belts will result in the premature wetu or breakage of the newer belts. Refer to label on inside of fan access door for information on factory-supplied diive. 1. Always adjust the motor position so that V-belts can be installed without stretching over grooves. Forcing belts can result in uneven stretching and a mismatched set of belts. 2. Do not allow belt to bottom out in sheave. C 5V 8V SMALL SHEAVE PD RANGE (in.) 3.0- 3.6 3.8- 4.8 5.0- 7.0 3.4- 4.2 4.4- 8.6 5.8- 8.6 7.0- 9.4 9.6-16.0 4.4- 6.7 7.1-10.9 11.8-16.0 12.5-17.0 18.0-22.4 DEFLECTION FORCE (Ib) Super Belts Notch Belts Steel Cable Belts Min Max Min Min 3 4% 37/8 51/2 31/4 4 31/2 5 41/2 61/4 33/4 43/4 4 5V2 5 67/8 4V4 51/4 4 81/2 83/4 8 41/2 81/2 51/8 71/8 61/2 91/8 83/4 71/4 63/8 83/4 73/8 1 01/8 7 83/4 Max 111/4 141/8 143/8 181/2 133/4 151/4 177/8 201/4 -1 01/2 -183/4 10 127/8 15 1 8a/4 13 191/2 15 27 401/2 .... 30 45 .... 111/4 141/4 14 173/4 --- --- -- -- 22 LEGEND PD -- Pitch Diameter, inches Fig. 33 -- Fan Belt Tension Data 51 Max Outdoor Hoods and Louvers -- There are three options available: fixed rein intake hoods, intake louvers, and collapsible exhaust box hoods. All hoods and louvers have an intake screen to prevent unwanted ent U of birds and debris. The intake hoods have easily serviceable demisters via small hinged doors. Intake louvers are a wind driven rain design that will _dlow no more than .01 oz. per sq. fi of fiee area water penetration at 1250 fpm. This is the maximum velocity required by AMCA (Air Movement and Control Association) 511. Higher velocities tue possible without significant water intrusion. _GUTTER HOOD .... ANGLE j J Fixed rear hoods (Fig. 34) and int_,e louvel_ (Fig. 35) ship installed and should lequile no further assembly. PANEL Collapsible exhaust box hoods ship covering the exhaust outlet of the unit and require some basic assembly. Fasteners, washers and gasket material for installation of the hood come taped inside the exhaust section. Fig. 36 shows an exploded view of the assembly in its shipping position. Fig. 37 shows how the various parts assemble to form the hood and a view of the completed assembly. IMPORTANT: Hoods for power exhaust fans must be field supplied based on local code requirements. BRACKET MOUNT BELOW HOOD BRACKET CAN BE THROWN AWAY AFTER HOOD IS INSTALLED ON THE UNIT. _ "/" SCREW _PANEL Fig. 36 -- Collapsible Exhaust Box Hood (Shipping Position) ] I SCREW _ HOOD_ UNIT '_//_ GUTTER "q/'__ _ O/# SCREW TYPICAL ENTIRE PERIPHERY -- INTAKE HOOD _PANEL OPEN DOORTO REMOVE DEMISTERS WASHER I _'_SCREW t SCREEN TO BE INSTALLED BETWEEN THE AND THE HOOD PANEL FLANGE.FLANGE Fig. 34 -- Rear Intake Hood (Size 30 Shown) Fig. 37 -- Collapsible Exhaust Box Hood (Assembly) GASKET .125 THICK x 1.25 WIDE, Coil Housing (Outdoor Unit -- Coil connection housings are used to house piping fi'om inside the building to its connections to the coil on the unit. Piping must be insulated to building code standards or job specifications (whichever is greater) for the area that the unit is inst_flled to prevent excessive condensation within the housing otherwise, water &tmage to floors below could result. Install as follows: \\\\\\\\\\\\ LOUVER ASY Connection Only) \\ \.. SCREW 1/4-14 x 3/4 SNS X 1. Coil connection housing (CCH) will be shipped to the job site on its own skid, separate from the air-handling unit as shown in Fig. 38. NOTE: All dimensions in inches unless otherwise noted. Fig. 35 -- Louver Intake 52 2. Before removing the coil connection housing from its skid, remove panels and reposition shipping brackets/ lifting lugs as shown in Fig. 39. 3. Apply seal strip to roof as shown on the coil connection housing roof gasketing detail in Fig. 40. COIL CONNECTION HOUSING 4. Assemble seal strip to back side of the coil connection housing frame as shown in Fig. 41 and 42. Remove panel retainers from unit as shown in Fig. 43. If file coil connection housing spans more than one section DO NOT remove panel retainers that do not interfere with the coil connection housing mounting. \ 5. 6. Apply l/2-in, thick by 2-in. thick closed cell neoprene gasket to the top of the CCH curb. Tile CCH will sit directly on top of the curb. Ensure that thele is a tight seal between the CCH and AHU. SKID 7. Fig. 38 -- Coil Connection Housing CCH END PANEL Secure the coil connection housing roof to air-handling unit roof using the panel letainers and retainer screws as shown in Fig. 44. Note that the view is fiom underneath the roof. The retainers me rotated 180 degrees and hold the coil connection housing roof to the side of the airhandling unit. These _ue the same style retainers used to hold the air-handling unit panel in place during shipment. SEAL STRIP 1.50" WIDE X 0.375" THICK APPLY TO TOP OF CCH FRAME BEHIND CCH ROOF TO ROOF OF AHU ROOF. REPOSITION SHIPPING BRACKETS / LIFTING LUGS TO FRAME AS SHOWN CCH ROOF_ CCH FRAME_ CCH FACE PANEL SINGLE WALLVERSION SHOWN CCH END PANEL SINGLE WALL VERSION SHOWN 0.75" WIDE X 0.125" THICK APPLY TO OUTSIDE EDGE OF CCH FRAME REAR PERIMETER TO SEAL AGAINST SIDE OF AHU. USE SCREWS FROM PANEL RETAINERS TO MOUNT CCH FRAME TO AHU FRAME. CCH -- CoilConnection Housing LEGEND Fig. 39 -- Reposition to Upright and Remove Panels AHU CCH --- Air-Handling Unit Coil Connection Housing Fig. 41 -- Detailed View of Seal Strip SEAL STRIP 1.50" WIDE X 0.375" THICK CCH ROOF DO NOT DIS-ASSEMBLE ROOF FROM CCH FRAME. ROOF SHOWN THIS WAY FOR CLARITY BEHIND CCH ROOF TO SEAL AGAINST BOTTOM OF AHU ROOF SEAL STRIP 0.75" WIDE X 0.125" THICK USED TO SEAL BETWEEN CCH ROOF AND AHU ROOF SEAL STRIP USED TO SEAL BETWEEN CCH AND AHU SEAL STRIP 1.50" WIDE X 0.125" THICK USED TO SEAL BETWEEN LEGEND CCH ROOF AND ROOF CCH --Coil Connection AHU CCH Housing Fig. 40 -- Apply Seal Strip --- Air-Handling Unit CoiIConnection Housing Fig. 42 -- Assembled Seal Strip 53 _AHU ROOF CCHROOF_ AHUPANEL_ \ \ 1/4 - 20 X 7/8 in. LEGEND AHU CCH -- Air-Handling Air-Handling Unit Coil Connection Housing Fig. 45 -- Secure LEGEND AHU --- Using Self-Drilling Screws Unit Fig. 43 -- Remove Panel Retainers CCH ROOF ROOF RETAINER _AHU ROOF SEALING SCREW / 1/4-14 X 3/4 in. CCH CURB LEGEND AHU CCH --- CCHn _._::_AI. Air-Handling Unit Coil Connection Housing CCH CURB W-_W Fig. 44 -- Secure the Coil Connection Roof to the Air Handler Roof 8. 9. 10. SEAL GAPS BETWEEN CCH CURB, AHU, & AHU CURB Also secure the coil connection housing roof to airhandling unit with self-&illing screws as shown in Fig. 45. Remove screws from the air-handling unit roof if they interfere with flush mounting of the coil connection housing to air-handling unit roof. When file coil connection housing is located on the low side roof. cut the seal strip at the slit and bend the tab in to create a better seal. Remove shipping brackets and lifting lugs. Reassemble panels. See Fig. 46 for view of assembled coil connection housing. AHU OD NAILER HU CURB LEGEND AHU CCH --- Air-Handling Unit Coil Connection Housing Fig. 46 -- Reassembled Coil Connection with Panels Humidifier Housing Installation ASSEMBLE CONTROL VALVE ASSEMBLY (Fig. 47Fig. 50) -- V;flve kits m'e sold as separate items through your loc_fl Creel representative (shipped unassembled). the 11. Seal any gaps between the main unit base rail and the cut out in the CCH curb with tield-supplied flashing and sealec 54 CAREL PART NUMBER DESCRIPTION COMPONENTS 599-02000CKIT 1/2-in. valve size Cv= 0.4 599-02002CKIT 1/2-in. valve size Cv= 0.63 599-02004CKIT 1/2-in. valve sizes Cv= 1 599-02006CKIT 1/2-in. valve sizes Cv= 1.6 599-02008CKIT 1/2-in. valve sizes Cv= 2.5 (2) 1/2-in. MPT x 3-in. nipples (2) 1/2-in. FPT x 1-in. MPT hex bushings 1-in. union 599-02010CKIT 1/2-in. valve sizes Cv= 4 599-02012CKIT 3/4-in. valve size Cv= 6.3 Cv -- Flow Coefficient 1/2 in. or 3/4 in. valve body 1/2 in. or3/4 in. x 3 in. nipples (2) 1 in. union 1/2 in. or 3/4 in. FPT x 1 in. MPT hex bushing (2) Fig. 47 -- 1/2-in. and 3/4-in. Valve Assemblies 55 CAREL PART NUMBER DESCRIPTION 599-02014CKIT 1 in. valve size Cv=10 (2) 1 in. MPT x 3 in.COMPONENTS nipples 1 in. union Cv -- Flow Coefficient 1 in. union 1 in. x 3 in. nipple Fig. 48 -- 1 in. Valve Assembly CAREL PART NUMBER 590-03024KIT 590-03025KIT I DESCRIPTION 11/4-in. valve size Cv= 16 11/2-in. valve size Cv= 25 COMPONENTS (2) 11/4-in. MPT x 3 in. nipples (2) 11/4-in. FPT x 2 in. MPT hex bushings 2 in. union Cv -- Flow Coefficient 1-1/4 in. or 1-1/2 in. valve body 1-1/4 in. or 1-1/2 in. x 3 in. nipples 2 in. union 1-1/4 in. FPT x 2 in. MPT hex bushings (2) Fig. 49 -- 11/4-in. and 11/2-in. Valve Assemblies CAREL PART NUMBER 590-03026KIT I DESCRIPTION 2 in. valve size Cv=40 COMPONENTS (2) 2 in. MPT x 3 in. nipples 2 in. union Cv -- Flow Coefficient - v Fig. 50 -- 2 in. Valve Assemblies 56 2 in.unlon ASSEMBLE STRAINER AND TRAP ASSEMBLY AND VALVE ASSEMBLY (Fig. 51 and 52) -- Strainer and trap assemblies are sold as separate items through your local Carel representative (shipped unassembled). 2 in. Strainer and Trap Assembly CAREL PART NUMBER 1 in. Strainer and Trap Assembly CAREL PART NUMBER DESCRIPTION 1 in. Steam trap and strainer with plumbing kit US'I-r&SKIT1 DESCRIPTION COMPONENTS 2 in, Steam trap and strainer with plumbing kit 2 in. Y-strainer 2 in. x 6 nipple 2 in. x 90 degree FPT elbow 2 in. x 3 in, nipple 2 in. FPT tee 2 in. x s/4-in,hex bushing (2) 3/4-in. x 6 in. nipples 3/4-in, FPT union 3/4-in, 90 degree street elbow 3/4-in. float and thermostatic trap COMPONENTS USTT&SKIT2 1 in, Y-strainer 1 in, x 6 nipple 1 in, x 90 degree FPT elbow 1 in, x 3 in. nipple 1 in, FPT tee 3/4-in. x 1 in, hex bushing 2) 3/4-in, x 6 in, nipples 4-in. FPT union a/4-in. 90 degree street elbow a/4-in, float and thermostatic trap 2 X 90 FPT ELBOW 2 x 6 NIPPLE 2 Y-STAIN ER 2 x 3 NIPPLE 1 X 6 NIPPLE 1 Y-STAINER X 90 '_FPT X 3 ELBOW 2 X 3/4 HEX BUSHING NIPPLE 3/4 FPT UNION HEX BUSHING _ 3/4 X 6 NIPPLES (2), 3/4 STREET ELBOW UNION FLOATAND THERMOSTATIC STEAM TRAP NOTE: All dimensions Fig. 53 -- 2 in. Steam Trap and Strainer with Plumbing Kit THERMOSTATIC STEAM TRAP NOTE: All dimensions in inches. in inches. Fig. 51 -- 1 in. Steam Trap and Strainer with Plumbing Kit 57 CONNECT CONTROL VALVE AND TRAP TO STEAM SUPPLY AND MANIFOLD (Fig. 53 and 54) STEAM IN 24 in. DROF in. NPT WATER DRAIN OUT 1/2 in. NPT Fig. 53 -- Control Valve and Trap Connected to Supply and Manifold of Humidifier Sizes 03-14 (Size 14 Shown) 2 in. NPT LIVE I1_ STEAM IN WATER DRAIN OUT Fig. 54 -- Control Valve and Trap Connected to Supply and Manifold of Humidifier Sizes 17-61 (Size 17 Shown) Assembly of Vertical Manifolds -- Tile vertical distribution manifolds are inserted into the bottom feed header by hand (slip fit) and then into file top header if any. See Fig. 55. • • • • • INSERT Vertical slotted discharge manifolds must be installed with the internal fishbone wick ends sloping up as in a ,,y,, Do not force the vertical manifolds into the headers beyond the insulation. Do not use any lubricants. Manually reform the ends slightly if necessary. Ensure discharge slots are perpendicular to the air flow. On top fed 17-61 sizes, run a bead of RTV silicone caulk around the junction of the vertical manifolds and top headec INSUL Fig. 55 -- Vertical Manifold 58 Coil Installation 1. Ix)ck open and tag all power supplies to unit fan motor and electric heaters if present. 2. a. Identify the unit service panel latches and disengage them (1/4 turn) with a 5/l(-,-in. or 8-mm hex wrench. NOTE: If installing a replacement coil, refer to Coil Removal section, page 93 for instructions on removing existing coil. INSTALLATION OF SINGLE HEIGHT COILS (sizes 03- 36) 1. Lock open and tag all power supplies to unit fan motor and electric heatel_ if present. 2. a. b. 3. b. Identify the unit service panel latches and disengage them (1/4 turn) with a 5h(-,-in. or 8-mm hex wrench. 3. Remove service panel/coil connection panel and the upstream service panel and set aside in a safe place. a. Remove the flat corner plug from each end piece of the top rail. b. Extract the Torx T25 screw visible within the exposed cavity. (Do not mix these screws with others; they are specific for this location. Set screws aside for reinstallation of the top rail.) c. Remove the top rail by pulling out fit a 45 degree angle. Set top rail aside. 5. 7. Install the first coil in the section. Access the upstream face of the coil and install the screws holding the coil to the mounting baffles around the entire perimetel: This may require reaching through an opened damper assembly or through the filter track after filters _ue removed. 8. Replace the top rail by reinstfdling and flat corner plugs. 9. Replace latches. the Torx T25 screws all service panels and engage INSTALLATION IMPORTANT: intermediate with Carrier turer's coils ponents be _'itkout coils OF STACKED COILS Remove the top rail by pulling angle. Set top rail aside. out fit a 45-degree 4. Slip the foam sealing sleeves on the connection before installing the coil. 5. Before placing file coils inside the unit, apply the adhesive backed gasket to the lower baffle, spanning the entire unit, on the surface that will contact the coil (see Fig. 56). 6. a. Place the lower coil on the coil supports, sliding the coil against the upstream baffle and aligning the mounting holes so that the connection nipple will extend approximately 3 in. outside the unit casing. The coil may now be hoisted in through the top opening, or it may be slid in through either side, taking care to avoid tipping or &opping the coil. Some lower stacked unit sections may require slightly tipping the coil from the vertical position in order to clear the upper frame rail and seffl, which is not readily removed. Loosely secure the coil at the top using the 3/s-in. dia]neter hoisting holes located in the side channel/tube sheet juncture fit each end. the flat corner plug from each end piece of rail. the Torx T25 screw visible within the cavity. (Do not mix these screws with they are specific for this location. Set aside for reinstallation of the top rail.) Do not handle the coil by the headers or connection nipples, as irreparable damage might occur that is NOT covered by warianty. Protect the finned surface from &image during all handling and shipping. nipples 6. a. Remove the top b. Extract exposed others; screws c. Do not handle the coil by the headers or connection nipples, as irreparable damage might occur that is NOT covered by WtuTanty. Protect the finned surface from damage during all handling and shipping. 4. Slip the foam sealing sleeves on the connection before installing the coil. Remove service panel/coil connection panel and the upstream service panel and set aside in a safe place. nipples b. Place the heavy vertical angle (which is full height of the finished coil bank) along the upstream right and left side of the mounting baffles (see Fig. 56). Install screws through this angle first and then into the baffles, engaging the coil tube sheet mounting holes and securing the coil within the unit. c. Secure the lower side lower horizontal baffle, between. casing of the coil to the sandwiching the gasket in 7. For coil sections that do not have a &'ain pan within the section, go to Step 10. 8. Secure the spacer (hat channel) lower coil casing (see Fig. 57). to the top center of the all I/4-turn panel (40, 50 and 61 ) Do not penetrate through the coil casing into the fin pack. Tube damage may occur. The lengths of the coil supports and pans and channels are designed to work coils. Substitution of other manufacmay require that custom mounting comfield fabricated. Coil sections ordered _'ill come _4'ith tke refi, l_,nced parts in kit Secure two spacers (hat channels) to each end of the bottom of the upper coil casing before placing the coil in position (refer to Fig. 56). 10. NOTE: The length that the intermediate &'ain pan extends downstremn from the coil face has been designed for use with Cturier manufactured coils, and may prove insufficient for other maker's coils. 59 Place the intermediate condensate &ain pan on the lower coil, centering the drain pan between the sides of the unit, with the condensate outlet holes along the downstream edge. (It may be helpful to temporarily secure the drain pan by a strip of double-stick tape on the center hat channel.) BAFFLE, BAFFLE, TOP HEADER_ CHANNEL, _ BAFFLE, HAIRPIN ATTACHED TO COILS BOTH SIDES CENTERED IMPORTANT: ADHESIVE APPLIED TO THE FULL PAN, CONDENSATE_, WITHIN SECTION GASKET LENGTH THE COIL SIDE CASING AND SEE ILLUSTRATION BELOW. APPLY GASKET, ....BAFFLE, FLUSH TO THIS ADHESIV BOTTOM MUST BE OF THE BOTTOM THE BAFFLE. EDGE_ E--__ _/ _ BOTTOM BAFFLE Fig. 56 -- Apply Gasket 11. Lift the upper coil (with spacer hat channels on the bottom of each end) into place, aligning the upper coil with the lower coil. When the upper coil is lowered into place, it will deflect the intermediate condensate pan downwmd on each end, providing for positive drainage. 12. Install factory-supplied screws around the ends and top of the coil. 13. 14. 15. On the upstremn side of the stacked coils, attach center baffle (see Fig. 56), spanning the two coils with crease in the baffle away from the coils, centering between file side baffles, and aligning the baffle with holes in the coil casings. Install the drain fittings into the pan. Route and secure hoses as shown in Fig. 58. For sections sections): a. CHANNEL, that do not have a drain pan (heating b. 16. Place the upper coil into position directly above the lower coil, resting on these hat channels. Secure the uppermost coil frDm the upstream side, so that the fastening screws provided pass through the vertical angle and the baffles and engage the coil casing. See Fig 56. the the it the the --GASKET -_- DRAIN only \\ CONDENSATE After the lower coil has been secured in position, fasten the three hat channel spacer supports to the top of the coil. HAT ,\ ATTACH ...... TO COIL WITH 4 SCREWS CASING \ \ \ _HOSE \ J "ATTACHED TO COIL TUBE SHEET Fig. 58 -- Install Drain Fittings Fig. 57 -- Secure Spacer 6O PAN Water and Steam Coil Piping Recommendations Figure 60 illustrates the normal piping components and the suggested locations for high, medium, or low-pressure steam coils. The low-pressure application (zero to 15 psig) can dispense with the 1/4-in. petcock for continuous venting located above the vacuum breaker (check valve). GENERAL -- Use straps around the coil casing or the lifting holes (see Fig. 59) to lift and place file coil. Note the horizontal location of the 15-degree check valve, and the orientation of the gate/pivot. This valve is intended to relieve any vacuum forming in the condensate outlet of a condensing steam coil, and to seal this port when steam pressure is again supplied to the coil. It must not be installed in tiny other position, and should not be used in the supply line. For coils used in tempering service, or to preheat outside aik install an immeLsion thermostat in the condensate line ahead of the trap. This will shut down the supply fan and close the outdoor &tmper whenever the condensate falls to a predetermined point, perhaps 120 E NOTE: Do NOT use tin immersion thermostat to override a duct thermostat and open the steam supply valve. To prevent damage to the coil or coil headers: Do not use the headers to lift file coil. Support the piping trod coil connections independently. Do not use the coil connections to support piping. When tightening coil connections, use a backup wrench on the nozzles. Piping practices ale outlined in the Carrier System Manual, Pall 3, Piping Design. Design WATER COILSTypically, coils me piped by connecting the supply at the bottom and the return at file top. See Fig. 59. This is not always the case, especially if the coil hand has been changed in the field. Coils must be piped for counterflow; otherwise, a capacity reduction of 5% for each coil row will result. To ensure counterllow, chilled water coils me piped so that the coldest water meets file coldest air Hot water coils are piped so that the warmest water meets the warmest all: For vacuum return systems, the vacuum breaking check valve would be piped into the condensate line between the trap and the gate valve instead of open to the atmosphere. Figure 61 illustrates the typical piping fit the end of every steam supply main. Omitting this causes many field problems and failed coils. STEAM COILS -- Position the steam supply connection fit the top of the coil, and the return (condensate) connection at the bottom. The coil tubes must incline downwfuds toward the return header connection for condensate di'ainage. See Fig. 60-65. Figure 62 shows the typical field piping of multiple coils. Use this only if the coils are the same size and have the same pressure drop. If this is not the case, tin individual trap must be provided for each coil. Figure 63 shows a multiple coil arrangement applied to a gravity return, including the open air relief to the atmosphere, which DOES NOT replace the vacuum breakers. LIFTING HOLES Figure 64 illustrates the basic condensate lift piping. Following the piping diagrams in Fig. 60-64, make all connections while observing the following precautions: • (VENT_ • • • • • • (DRAIN) HEADER END VIEW Fig. 59 -- Coil Connections and Lifting • Points • 61 Install a drip line and trap on the pressure side of the inlet control valve. Connect the drip line to the return line downstream of the return line trap. To prevent scale or foreign matter from entering the control valve and coil, install a 3132-in. mesh strainer in the steam supply line upstream from the control valve. Provide air vents for the coils to eliminate noncondensable gases. Select a control valve according to the steam load, not the coils supply connection size. Do not use an oversized control valve. Do not use bushings that reduce the size of the header return connection. The return connection should be the same size as the return line and reduced only fit the downstream trap. To lift condensate above the coil return line into overhead steam mains, or pressurized mains, install a pump and receiver between the condensate trap and the pressurized main. Do not try to lift condensate with modulating or on-and-off steam control valves. Use only 15-degree check valves, as they open with a lower water head. Do not use 45-degree or vertical-lift check valves. Use float and thermostatic traps. Select the trap size according to the pressure difference between the steam supply main and the return main. Load variations can be caused by uneven inlet air distribution or temperature stratification. Drain condensate out of coils completely fit the end of the heating season to prevent the formation of acid. NOTE _-CONTROL NOTE VALVE _ I-_ CONTROL .- _- STRAINER I -__ _" \_'_ /GATE VALVE 28_3) 5) (NOTE STRAINER VALVE 7/ ¼ iN. PET COCK "_ GATE VALVE _,,_ STEAM SUPPLY UNIT UNIT FOR CONTINUOUS _STA_ STEAM 111 LWHEN ". END MAIN,SEE SUPPLY _r'\REFER OF SUPPLY FIG. 61 FIG, TO WHEN SUPPLY RMOSTATIC _-15 ° CHECK VALVE FOR BREAKING VACUUM GI DRIPPING TO RETURN. TRAP (½IN.) UNIT IN, LINE _'NOTEI MIN, GIRT LEG VALVE (61N.) " 15° CHECK VALVE OPEN AIR RELIEF /T0 ATMOSPHERE - FLOAT BUCKET (NOTE OR TRAP 2) -j DIRT LEG ( 6 IN.)- / 15 _ CHECK CONDENSATE RETURN MAIN NOTES: 1. Flange or union is located to facilitate coil removal. 2. Flash trap may be used if pressure differential between steam and condensate return exceeds 5 psi. 3. When a bypass with control is required. 4. Dirt leg may be replaced with a strainer. If so, tee on drop can be replaced by a reducing ell. 5. The petcock is not necessary with a bucket trap or any trap which has provision for passing air. The great majority of high or medium pressure returns end in hot wells or deaerators which vent the air. VALVE FLOAT OR TRAP (NOTE _/ BUCKET -: 4) L_. NOTE !'_', I GATE VALVE /._ 4co _ NDENSATE NOTES: RETURN 1. Flange or union is located to facilitate coil removal. 2. When a bypass with control is required. 3. Flash trap can be used if pressure differential between supply and condensate return exceeds 5 psi. 4. Coils with different pressure drops require individual traps. This is often caused by varying air velocities across the coil bank. 5. Dirt leg may be replaced with a strainer. If so, tee on drop can be replaced by a reducing ell. 6. The petcock is not necessary with a bucket trap or any trap which has provision for passing air. The great majority of high pressure return mains terminate in hot wells or deaerators which vent the air. Fig. 60 -- Low, Medium or High Pressure Coil Piping Fig. 62 -- Multiple Coil High Pressure Piping .... CONTROL _j (NOTES VALVE 2 6 3) 'STRAINER / STEAM SUPPLY TO UN / FGATE VALVE 15_CHECK VALVE STEAM SUPPLY UNIT WHEN DRIPPING SUPPLY STEAM SUPPLY TO STATIC RETURN. TRAP (½IN.) MAIN / DIRT LEG j--FLOAT TRAP _--GATE GLOBE VALVE (PLUG TYPE) /_ _ / "_ _i _" ! B THERMOSTATIC UNIT VALVE ./-OPEN AIR RELIEF TO ATMOSPHERE CLOSE TO UNIT. REQUIRED ON DRIP /OPEN TO LOW PRESSURE GRAVITY RETURN SYSTEMS, LINE=-_ CONDENSATE RETURN FROM UNIT AIR RELIEF ATMOSPHERE DIRT LEG ( 6 IN.)_ I 5° C GATE VA VEI J ._-- J FLOAT OR BUCKET TRAP (NOTE CONDENSATE RETURN _/ 4) GATEI NOTE MAIN '_ VALVE '_CO NDENSATE RETURN NOTES: 1. A bypass is necessary around trap and valves when continuous operation is necessary. 2. Bypass to be the same size as trap orifice but never less than 1/2inch. NOTES: 1. Flange or union is located to facilitate coil removal. 2. When control valve is omitted on multiple coils in parallel air flow. 3. When a bypass with control is required. 4. Coils with different pressure drops require individual traps. This is often caused by varying air velocities across the coil bank. Fig. 61 -- Dripping Steam Supply to Condensate Return Fig. 63 -- Multiple Coil Low Pressure Piping Gravity Return 62 STEAM condensate header The slanting of the assembly ensures that condensate will flow towmd the drains. This condensate must be removed fllrough the mtum piping to prevent premature fiulure of the coil. The fin/tube bundle is slanted vertically for horizontal airflow coils, and hofizonttdly for vertical airflow coils. SUPPLY Y GATE VALVE_ _¢_OVERHEAD _'_ IDT Steam Coil Piping -- The following piping guidelines will contribute to eft]cient coil operation and long coil life: CONDENSATE RETURN MAIN 1. Use full size coil outlets and return piping to the steam trap. Do not bush return outlet to the coil. Run full size to file trap, reduce tit the trap. UNiT 2. Use float and thermostatic (F & T) traps only for condensate removal. Trap size selection should be based on the difference in pressure between the steam supply main and file condensate return main. It is good practice to select a trap with 3 times the condensate rating of the coil to which it is connected. 3. Use themlostatic 4. Use only 1/2-in., 15-degree swing check valves installed horizontally, piped open to atmosphere, and located tit least 12 in. above die condensate outlet. Do not use 45-degree, vertictfl lift and ring check valves. 5. The supply valve must be sized for the maximum pated stemn load. 6. Do not drip stealn mains into coil sections. Drip them on file pressure side of the control valve and trap them into the return main beyond the trap for the coil. Do not use a single trap for two or more coils installed in series. Where two or more coils are installed in a single bank, in parallel, the use of a single trap is permissible, but only if the load on each coil is equal. Where loads in file same coil bank vmy, best practice is to use a separate trap for each coil. VALVE 12IN. MIN. ( LOCATED DRAIN BELOW COIL OUTLET) VALVE (GATE,NOTE2 NOTES: 1. Flange or union is located to facilitate coil removal. 2. To prevent water hammer, drain coil before admitting steam. 3. Do not exceed one foot of lift between trap discharge and return main for each pound of pressure differential. 4. Do not use this arrangement for units handling outside air. Fig. 64 -- Condensate Lift to Overhead Return Coil Freeze-Up 7. Protection WATER CO[LS -- If a chilled water coil is applied with outside air. provisions must be made to prevent coil fieeze-up. Install a coil fieeze-up thermostat to shut down the system if any air temperature below 36 F is encounteled entering the water coil. Follow thermostat manufacturer's instructions. 8. For outdoor-air application where intermittent chilled water coil operation is possible, one of the following steps should be taken: Install an auxiliary blower heater in cabinet to maintain above-freezing temperature around coil while unit is shut down. • Drain coils and fill with an ethylene glycol solution suitable for the expected cold weather operation. Shut down the system and drain coils. See Service section, Winter Shutdown, page 92. antici- Variation in load on different coils in the same bank may be caused by sever_fl factors. Two of the most common me uneven airflow distribution across file coil and stratification of inlet air across the coil. When a water coil is applied downstremn of a directexpansion (DX) coil, a freeze-up thermostat must be installed between the DX and water coil and electrically interlocked to turn off the cooling to prevent fieeze-up of the water coil. • traps for venting only. 9. Do not try to lift condensate above the coil return into an ovefllead main, or drain into a main under pressure with a modulating or on/off steam control valves. A pump and receiver should be installed between the coil condensate traps and ovefllead mains and return mains under pressure. Use a strainer (3/32-in. mesh) on the steam supply side, as shown in the piping diagrams, to avoid collection of scale or other foreign matter in file inner tube distributing orifices. NOTE: IDT coils must be installed with the tubes draining toward the header end of the coil. Carrier's IDT steam coils are pitched toward the header end as installed in the unit. 10. Ensure the AHU is installed level to maintain the inherent slope. Also ensure the unit is installed high enough to tfllow the piping to be installed conectly, especially the traps which require long drip legs. 11. Do not fail to provide all coils wifll the proper air vents to eliminate noncondensable gasses. STEAM COILS -- When used for preheating outdoor air in pressure or vacuum systems, an immersion thermostat to control outdoor-air damper and fan motor is recommended. This control is actuated when steam supply fails or condensate temperature drops below an established level, such as 120 to 150 IF. A vacuum breaker should also be used to equalize coil pressure with the atmosphere when stemn supply throttles close. Steam should not be modulated when outdoor air is below 40 E On low-pressure and vacuum steam-heating systems, the thermostat may be replaced by a condensate drain with a thermal element. This element opens and drains the coil when condensate temperature drops below 165 E Note that condensate dndns are limited to 5 psig pressure. INNER DISTRIBUTING TUBE STEAM COILS -The inner distributing tube (IDT) steam coil used in the Carrier 39M _fir-handling units has an inner tube pierced to facilitate the distribution of the steam along the tube's length. The outer tubes me expanded into plate fins. The completed assembly includes the supply and condensate header and side casings which are built to slant the fin/tube bundle back toward the 12. Do not support steam piping fiom the coil units. Both mains and coil sections should be supported sepmately. IDT Steam Coil [nstallafion -- Refer to drawings to position the coils properly with regard to the location of the supply and return connections. Ensure that the IDT coil is pitched with the tubes draining towmd the headel: Carrier's AHUs provide proper coil pitch when the AHU is insttflled level. Refer to schematic piping diagrams and piping connection notes for the recommended piping methods. 63 Refrigerant Piping, Direct-Expansion Coils- Direct-expansion (DX) coils me divided into 2 or4 splits depending upon file unit size and coil circuiting. Each split lequires its own distributor nozzle, expansion valve, and suction piping. Suction connections ;ue on the air entering side when the coil is properly installed. Matching distributor connections for each coil split m'e on file air leaving side. See unit label or certified drawing to assme connection to matching suction and liquid connections. NOTE: Distlibutor nozzles are factory selected trod installed for adequate performance in many unit applications. For best performance, use Carrier's AHUBuilderQ program to select nozzle sizes for each unit and replace the factory-installed nozzles as required. See file Thermostatic Expansion Valve Piping section below for further details. 2. Clean off any remaining 3. Remove nozzle retaining ring with screwdriver nosed pliers. solder 4. Remove nozzle from distributor by inserting 2 no. 6-32 threaded rods (at least 4-in. long) into the thleaded holes provided in the nozzle. See Fig. 69. 5. Insert correct nozzle into distributor 6. Re-insert nozzle retainer ring into distributol: COIL CASING To prevent &_mage to file coil or coil headers: Do not use the headers to lift the coil. Support the piping and coil connections independently. Do not use the coil connections to support piping. When tightening coil connections, use a backup wlench on the stub outs. UPPER TXV SPLIT SENSING or needle- body. UNIT CASING BULB AIRFLOW Direct-expansion coils am shipped pressurized with diy ail: Release pressure from each coil split through v_flves in protective caps before removing caps. Do not leave piping open to the atmosphere unnecessarily. Water and water vapor me detrimental to the refrigertmt system. Until tile piping is complete, lecap the system and charge with nitrogen at the end of each workday. Clean all piping connections before soldering joints. The lower split of face split coils should befirst-on, last-o_i Row split coils utilize special intertwined circuits; either split of these row split coils can befirst-on, last-q_i LOWER SPLIT SUCTION PIPINGConnect suction piping as shown in Fig. 65 for face split coil or Fig. 66 for row split coil. Suction line from coil connection to end of the 15-diameterlong riser should be salne tube size as coil connection to ensure proper refrigerant velocity. Refer to Carrier System Design Manual, Part 3, and size remaining suction line to compressor for a pressme diop equivalent to 2.0 E This will provide a total suction line header pressure diop equivalent to approximately 2.7 E Refer to Fig. 67 for piping risels to the complessor. To minimize the possibility of flooded starts and compressor damage during prolonged light load operation, an accumulator can be used in the suction line offirst-on, last-o_circuit. Thefirst-on, last-o_ circuits shown in Fig. 65 and 66 assume a single condensing unit. Note that in both figures the last-on, Iil_t-off circuit is looped above the common return line to prevent oil entrapment in the non-operating coil at partkfl load. THERMOSTATIC EXPANSION VALVE PIPING -- Distributor nozzles me factory supplied. Thermostatic expansion valves (TXVs) are field supplied. Be sure that correct nozzle is installed in each distributor before installing expansion valve. See Table 4 for factory-installed distributor nozzle sizes. Use AHUBuilder program to select nozzles for best performance; replacement nozzles must be field inst_dled. Perform follows: nozzle change-out procedure (if necessmy) EVAPORATOR COIL FIRST-ON, LAST-OFF LEGEND TXV -- Thermostatic Expansion Valve Fig. 65 -- Face-Split Coil Suction-Line Piping UNIT COIL CASING TXV SENSING BULBS AIRFLOW 15 DIAMS MIN 31GHT 15 DIAMS MIN 3LASS FILTER 10 DIAMS DRIER as (TYP) 1. Unsweat distributor cap and Schmder valve (see Fig. 68). Cap is sweat on from facto U with 95.5 tin-antimony soft solder EVAPORATOR COIL FIRST-ON, LAST-OFF LEGEND TXV -- Thermostatic Expansion Valve Fig. 66 -- Row-Split Coil Suction-Line Do not overheat distributoc Overheating cap and distributor will hmden solder and make cap impossible to remove. 64 Piping I PYL_ :Oo 5. Inst¢dl filter drier ahead of expansion satisfactory valve operation. 6. If hot gas bypass Bypass section. is required, valve to ensure see the following Hot Gas requires between Install auxilituy hot gas bypass side connector (fieldsupplied) in coil split that isfirst-on, last-qffi NOTE: See Table 22 for auxiliary side connector sizes. Do not attempt to use a valve that is smaller or larger than distributor size. Inserting a bushing at the outlet will defeat the purpose of the internal nozzle tube extension. Inst_dl the side connector as follows: COMPRESSORABOVE DOUBLERISER Fig. 67 -- Suction-Line Insulate expansion valve body, diaphragm assembly, and control bulb ;uea to prevent charge migration and excessive condensation. HOT GAS BYPASS--When low-load operation use of hot gas bypass, hot gas must be introduced expansion v_dve and distributor COMPRESSOR ELBOWS COMPRESSOR ABOVE SINGLERISER 4. Riser Piping 1. Remove distributor nozzle and letainer ring (area A) from distributor and reinst;dl in inlet (area B) of side connectoc See Fig. 70. 2. Solder field-supplied extension nipple to coupling on distributor, then to side connector outlet, using a silver solder or equivalent with a melting point of 1300 to 1500E Extension nipple should be as short as possible. DISTRIBUTOR / 3. Solder expansion 95-5 tin-antimony 4. If lequired, install field-supplied adapter bushing or coupling to connector inlet before soldering to expansion valve outlet. DISCARD CAP WITH TESTPORT Fig. 68 -- Distributor and Cap SPECIAL BODY TUBING PIPING valve outlet to side connector soft solder, for easy removal. WITH 4 SPLITS using PER COIL Manifolding for 2-Face Splits -- Refer to Fig. 71 and externally manifold as follows: NOZZLE 1. Connect the 4 expansion valves to the 4 distributors on each coil and connect the 4 suction lines to the 15-diameter-long risers as outlined in previous piping instructions. RETAINER _\ RING 2. Inst:dl common liquid line for upper face split to first (upper) and second expansion valves. Also, install a common suction line flom suction lines attached to first (upper) and second suction header connections. 3. Repeat step 2 for lower face split using third and fourth distributor and suction connections. \ \ \ \ 1 SIMPLIFIED NOZZLE REMOVAL I I Manifolding for2-RowSplits externally manifold as outlined following exceptions: -- Refer to Fig. 72 and for the 2-face splits with the 1. Manifold in pairs, the first and third coil connections one split. 2. for Manifold the second and fourth pairs of coil connections for the other split. NOTE: Split section using first and third pairs of coil connections should be fil_t-on, last-qffi NO. 6-32 THREADED PULLER HOLES Hot Gas Bypass Connection with 4 Splits per Coil -For either face or row splits connect a hot gas bypass auxiliary side connector to each distributor of coil split that is first-on, last-qff_ Refer to installation instructions for Hot Gas Bypass. SPECIAL PIPING FOR DOUBLE-CIRCUIT COILS -All 8-row coils that are double circuited requile special piping to manifold suction and liquid lines. See Tables 3 and 4 for detailed coil data. THREADED PULLER RODS Fig. 69 -- Nozzle Change-Out Install expansion valve as follows: 1. Wrap wet cloths around valve body to plevent excesswe heat from reaching diaphragm and internal palts. Do not allow water to enter system. Disassemble expansion valve before soldering, if accessible, for easy reassembly. _Z_e9_5-5 tin-antimony soft soldel: 2. Solder expansion 3. Solder expansion v_dve equalizer line to suction line and locate control bulb on suction line as in Fig. 65 or66. Manifolding for 2-Face Splits -- Refer to Fig. 71 for coils with less than 34 tubes in face. Externally manifold as follows: 1. Coils with less than 34 tubes: Connect the 4 expansion valves to the 4 distributors on each coil and connect the 4 suction lines to the 15-diameter-long riseLs as outlined in previous piping instructions. Refer to Fig. 71. valve to distributoc 65 2. [nstallcommon liquidlineforupperfacesplitto first (upper)andsecond expansion wdves. Also,installa common suction linefromsuction linesattached tofirst (upper) andsecond suction header connections. 3. Repeat Step2forlowerfacesplitusingthirdandfourth distributor andsuction connections. 4. Forunitswithtwocoilsrepeat procedmes of steps1,2 and3forsecond coil. 2. Manifold file second and fourth pairs of coil connections for the other split. NOTE: Split section using first and third pairs of coil connections should be first-on, last-oj/i Hot Gas Bypass Connection for Double-Circuited Coils -For either face or row splits connect a hot gas bypass auxilimy side connector to each distributor of coil split that is first on, last off. Refer to installation instructions for Hot Gas Bypass. Manifolding for 2-Row Splits -- Refer to Fig. 71 for coils with less than 34 tubes in face. Externally manifold as outlined for the 2-face splits with the following exceptions: 1. Manifold in pails, the filst and third coil connections one split. REINSTALL DISTRIBUTOR NOZZLE for HERE ! 1 I OUST \ RETAINER INLET DISCARD RETAINER RING SIDE CONNECTOR AREAA _ WITH CAP TESTPORT SIDE CONNECTOR AREAB Fig. 70 -- Distributor and Hot Gas Bypass Auxiliary Side Connector SIGHT GLASS (TYP) f 1 .__ TXV SENSING SOLENOID BULBS VALVE (TYP) DRIER /FILTER AIRFLOW LIQUID _@_J " /, / SUCTION LINE / FOR COIL CONNECTIONS 1 AND 2 TXV LINE FOR 1 AND 2 INSIDE _DISTRIBUTOR CASING (TYP) (TYP) TXV SENSING FILTER RIER _ LIQUID LINE FOR 3 AN D 4 / / SUCTION LINE FOR COIL CONNECTIONS 3AND4 LEGEND TXV -- Thermostatic Expansion Valve Fig. 71 -- Face-Split Coil Manifolding (Typical) 66 Table 22 -- Auxiliary Side Connector SPORLAN TYPE CARRIER PART NO. CONNECTION Inlet -- ODM Solder Outlet -- ODF (Hot Gas Bypass) Data SIZES (in.) Solder Auxiliary -- USED WITH SPORLAN DISTRIBUTOR TYPE ODF Solder NOZZLE SIZE J EA19BA504 % 7/8 1620,1622 ASC-7-4 7/8 _/2 1112,1113 G ASC-9-5 EA19BA705 11/s 11/8 5/s 1115,1116 E ASC-11-7 EA19BA905 1 s/s 1 s/8 7/s 1117,1126 C 15/s 15/8 11/s ASC-5-4 ASC-13-9 DIMENSIONS SPORLAN TYPE ASC-5-4 ASC-7-4 (in.) A B C D E F 5/80DM 5/80DF 1.88 0.95 1,25 1/2ODF 2.25 1.06 1,38 ASC-9-5 11/80DM 11/8ODF 2.81 1.47 1,62 5/8ODF ASC-11-7 lS/8 ODM lS/80DF 3.53 1.89 2,19 7/80DF ASC-13-9 7/8 ODM 15/80DM 7/80DF 15/8ODF 3.72 1.83 2,75 OUTLET 1/20DF --- Outside Outside Diameter, Diameter, t T TO ..... -- E×£°2'°NVA v E HOTGAS BYPASS INLET 11/8ODF INLET B DISTRIBUTORJL LEGEND ODF ODM A 1125,1127,1143 CONNECTION Female Male _ SIGHT GLASS - SOLENOID TXV SENSING BULBS (TYP) VALVE (TYP) AIRFLOW \ FILTER DRIER LIQUID LINE J_ FOR 1 AND 3 SUCTION LINE FOR COIL CONNECTIONS 1 AND 3 FOR 2 AND 4 " TXV INSIDE DISTRIBUTOR / SUCTION LINE FOR COIL CONNECTIONS 2AND4 LEGEND TXV -- ThermostaticExpansionValve Fig. 72 -- Row-Split Coil Manifolding (Typical) 6? CASING (TYP) (TYP) Hot Gas Piping and Wiring INSTALL PIPING 3. Sweat the pilot solenoid valve supplied in the hot gas accessary package directly to the hot gas bypass valve on the 3/8-in.ODF external equalizer port. 4. Install field-supplied I/4-in.copper tube (flared with a nut on each end) between the compressor suction valve and the hot gas pilot solenoid valve. 5. Connect a field-supplied 5/8-in. OD copper tube between the dischmge line process tube (hot gas stub) and a fieldsupplied manu_d shutoff service v_flve,avoiding any traps in piping. 6. Connect another field-supplied 5Is-in.OD copper tube between the manual shutoff valve outlet and the hot gas bypass valve inlet. 7. Connect a field-supplied 5/s-in. OD copper tube between the leaving side of the hot gas bypass valve and the Sporlan auxiliaq side connector (distributo>side connector). (See Fig. 73) Shut offall power to tfie unit and remove refiigerant charge using an approved refrigelant recovely device before proceeding with inst;dlation. 1. [n applications where the air handler refrigerant distributor is not equipped with a side outlet connection, it is recommended that a Spodan in-line auxiliary side connector with standard distributor be used. Refer to the installation instructions for the indoor fan coil to obtain nozzle size and distributor connection size. Select the auxilialy side connector based on this information. The side connector must be installed on refrigerant circuit no. 1 (fil3t stage of cooling) of the fan coil being used. 2. 8. Refer to Hot Gas Bypass installation instructions for wiring information. Install a field-supplied l/4-in. NPT to l/4-in, flare fitting on the gage connection port of the compressor suction service valve. CONDENSING UNIT EVAPORATOR COIL 1SUCTION _'1_ _ ---I:L_ m -., . HOT GAS PI LOT \, SOLENOID VALVE \ BYPASS SHUT-OFF SERVICE._ VALVE EXTERNAL EQUALIZER PORT HOT GAS 5/8" P, TUBE DISCHARGE_ EQUALIZER I SOLENOID I VALVE I I I i CIRCUITI EVAPORATOR TXV /_ I BYPASS I HOT GAS i LINE _ COMPRESSOR I EXTERNAL I I \\ r_ TUBEI/4" "l I LINE I _NDENSER __ j LIQUID LINE TO COMPRESSOR SUCTION SERVICE VALVE II 1/40D--_! I1 SOLENOID r--_r._.-_ [L_ ::_1_-'--- 5--_ PILOT VALVE OUTLET 318' sw EAT CON N ECTION BY PASS VALVE (5/8" OD CONN I DISTRIBUTOR FROM TXV =_._ FIELD-SUPPLIED SKETCH BYPASS LINE A AUXILIARY S IDE CONNECTOR LEGEND TXV -- Thermostatic Expansion Valve *Pilot valve connects directly to bypass valve per sketch A. Fig. 73 -- Hot Gas Bypass 68 Piping AUXILIARY {HOT GAS IN) Condensate Drain -- Install a condensate-trapping di'ain line at the units di'ain connection; use I q2-in, standard pipe. See Fig. 74A and 74B for correct diain layout. The lowest point of the di'ain pan is a minimum higher than the bottom of the baserail. of 73/8-in. When calculating trap depth on draw-thin or blow-thru applications, remember that it is not the total static pressure but the upstream or downstream static resistance that is trapped against. For instance, when c;dculating the trap depth for a cooling coil condensate pan on the draw-thin side, trap against the coil pressure drop in that coil section and any other pressure drops upstream of it. 1/2 P1 MINIMUM Fig. 74ACondensate Drain, Draw-Thru Trapping Example: • Return duct -- 0.5 in. static • Mixing box-0.4 in. static • Filters-0.2 in. static • Heating coil -- 0.2 in. static • Cooling coil -- 1.2 in. static • Fan-2.3 in. external static 0.5" MINIMUM L If calculating the trap depth for the cooling coil, the total trap static would be 2.5 in. plus 1 in. (Pl = negative static pressure + 1 in.), as shown in Fig. 74A. Traps on draw-thin units must store enough condensate prevent losing the drain seal at strut-up. The "minimum 1/2 dimension ensures that enough condensate is stored. r pl to Pl" Fig. 74B -- Condensate Drain, Blow-Thru Trapping To determine the trap dimensions for blow-thru units, lind the coils maximum positive pressure (PI in Fig. 74B) and add I/2 inch. This figure is normally the fan total static pressure (Pl = fan toted static pressure). NOTE: Trapping to 5 in. static pressure on blow-thru and 3 in. static pressure on draw-thin units is possible with the stan&_rd 6 in. baserail. Fan Motor For all units, provide condensate freeze-up protection as required. On units with internal spring isolators, be sum the unit is mounted to allow sufficient clearance for the required drain trap depth. TYPE Forward-Curved (FC) Side View Airfoil (AF) Side View Wiring Recommendations -- Motors ;u'e rated for use with variable frequency drives. Full load amp (FLA) efficiency and power factoL's are listed in Tables 23A and 23B. Refer to Fig. 75 for fan type and application. CHARACTERISTICS APPLICATION • Double-width, double-inlet (DWDI) construction. • Best at low or medium pressure (approximately 0 to 5 in. wg). • Horsepower increases continuously with increase in air quantity (overloads) as For low to medium pressure static pressure decreases. air-handling applications. • Less expensive than AF fans. • Runs at relatively low speed, typically 400 to 1200 rpm. • Blades curve toward direction of rotation. • • • • • Double-width, double-inlet (DWDI) construction. Best in high capacity and high-pressure applications (4 to 8 in. wg). Horsepower peaks at high capacities. Most expensive of centrifugal fans. For medium to high air capacity Operates at high speeds, typically 1200 to 2800 rpm. About double the speed of and pressure applications. FC fan for similar air quantity. • Blades have aerodynamic shape similar to airplane wing and are curved away from direction of rotation. Plenum (PAF) End View • Single-width, single-inlet (SWSI) construction. • Characteristics similar to DWDI airfoil fan. • Blades have aerodynamic shape similar to airplane wing and are curved away from direction of rotation. Fewer blades and wider blade spacing than AF fans. Fig. 75 -- Fan Type and Application 69 Best in applications with limited space or multiple ducts. Motor Electrical Data -- See Tables 23A and 23B for Motor Electric;d Data. Table 23A -- ODP 60 Hz Motor Data HIGH MOTOR PREMIUM EFFICIENCY EFFICIENCY FLA HP 200v 230v 460v MOTOR HP FLA EFF. P.F. 575v (%) (%) N/A N/A 1/2 I 460v N/A 200v I 230v I 575v EFF. P.F. (%) N/A (%) N/A 1/2 2.2 1.8 1.1 0.9 3/4 2.6 2.5 1.3 1.0 N/A N/A 3/4 N/A N/A N/A 1 3.2 3.0 1.5 1.1 82.5 84 1 N/A N/A N/A 11/2 4.5 3.9 1.9 1.6 84.0 85.7 N/A N/A N/A 2 6.0 5.2 2.6 2.1 84.0 85.7 1112 2 N/A N/A N/A 3 9.4 8.6 4.3 3.4 86.5 76.0 3 9.0 8.0 4.0 N/A 88.5 79.5 5 15.3 12.8 6.4 5.1 87.5 83.3 5 14.5 71/2 25.0 19.2 9.6 7.8 88.5 81.5 10 29.3 26.8 13.4 10.3 89.5 15 43.2 38.6 19.3 15.4 20 56.0 49.6 24.8 25 70.5 60.6 30 85.0 40 13.6 6.8 N/A 89.5 76.8 21.5 19.4 9.7 N/A 91.7 79.0 80.0 7112 10 28.0 25.2 12.6 N/A 91.7 81.0 91.0 83.1 15 42.5 37.8 18.9 N/A 93.0 80.0 19.8 91.0 84.0 20 56.0 49.0 24.5 N/A 93.6 81.5 30.3 24.3 91.7 81.0 25 69.5 61.0 30.5 N/A 93.6 82.3 75.0 37.5 30.0 92.4 79.0 30 82.5 72.4 36.2 N/A 93.6 82.8 110.0 95.0 47.5 41.0 93.0 84.0 40 105.0 96.0 48.0 N/A 94.5 83.5 50 138.0 120.0 60.0 48.0 93.0 90.0 50 137.0 120.0 60.0 N/A 94.5 83.0 60 154.0 134.0 67.0 53.5 93.6 90.0 60 154.0 134.0 67.0 N/A 95.4 87.7 75 189.0 164.0 82.0 65.5 94.1 91.0 75 191.0 166.0 83.0 N/A 95.4 87.0 LEGEND EFF. FLA ODP P.F. ----- Efficiency Full Load Amps Open Dripproof Power Factor Table 23B -- TEFC 60 Hz Motor Data HIGH EFFICIENCY MOTOR HP PREMIUM EFFICIENCY FLA 208v 230v 460v 575v EFF. (%) P.F. (%) MOTOR HP 1/2 1.8 1.6 0.9 0.7 N/A N/A 1/2 3/4 1 2.4 4.0 2.4 3.2 1.2 1.6 0.8 1.3 N/A 82.5 N/A 72.0 3/4 1 11/2 2 5.5 7.0 4.4 5.8 2.2 2.9 1.6 2.1 84.0 84.0 72.0 76.0 1112 2 3 10.0 8.2 4.1 3.3 87.5 78.0 5 17.0 13.2 6.6 5.2 87.5 81.5 71/2 10 24.0 31.0 19.2 24.4 9.6 12.2 7.6 9.6 89.5 89.5 83.0 85.5 15 47.0 35.0 17.5 14.5 91.0 20 61.0 47.0 23.5 18.8 25 74.0 57.0 28.5 30 82.0 69.0 40 115.0 50 60 75 ----- I 230v I 460v N/A 1575v N/A EFF. P.F. (%) (%) N/A N/A N/A N/A 4.0 3.0 1.5 1.2 84.5 72.0 5.5 4.2 2.1 N/A 85.5 72.0 7.0 5.6 2.8 2.2 86.5 77.5 3 10.0 8.2 4.1 3.3 88.5 78.0 5 17.0 13.0 6.5 5.2 88.5 84.5 7112 10 24.0 19.2 9.6 7.6 90.2 81.5 31.0 24.0 12.0 9.6 90.2 85.0 85.0 15 47.0 35.0 17.5 14.0 91.7 86.0 91.0 87.0 2O 61.0 47.0 23.5 18.8 92.4 87.0 22.8 92.4 88.0 25 74.0 57.0 28.5 22.8 93.0 88.0 34.5 27.6 92.4 88.0 3O 95.0 47.5 37.6 93.0 85.0 4O 82.0 115.0 69.0 90.0 34.5 45.0 27.6 37.0 93.0 94.1 88.0 88.5 142,0 118.0 59.0 47.2 93.0 85.0 50 147.0 115.0 57.5 46.0 9.41 86.4 N/A 140.0 70.0 N/A 93.6 85.5 6O N/A 140.0 70.0 56.0 94.1 89.0 N/A 170.0 85.0 N/A 94.1 86.5 75 N/A 172,0 86.0 69.0 95.4 86.0 LEGEND EFF. FLA P.R TEFC FLA 208v Efficiency Full Load Amps Power Factor Totally Enclosed Fan Cooled 70 Fan Motor Starter -- When starter is factory-installed, it is wired to the motol: and fully tested before shipping. Before proceeding, open the starter cover and fan section access door to check for any &tmage. WIRING 1. Select a suitable location source; top is prefened. for the field power Set the HOA switch in the HAND position and verify that the fan operates. Place the switch back in the OFF position open the fan access dooc supply 2. Before drilling any hole, be sure the hole and any fieldsupplied conduit fittings will not interfere with the door or components inside the enclosme. 3. Drill the appropriate size hole and connect supplied conduit to the enclosure. 4. Refer to the wiring diagrmn supplied with the starter and connect the line voltage power source to the line voltage terminals (LI, L2, L3) as shown. 5. Refer to the factory-supplied voltage warning verify that the power source is correct. 6. Connect the grounding wire to the grounding ed on the bottom of the starto: equipment in both HAND and AUTO either a fire/smokeThisor coil condition IMPORTANT: starterfreeze is designed Apply power to the stmter 5. For 3-phase motor: 6. With the fan operating and the starter in the HAND position, verify that each safety or limit switch functions properly. 7. Repeat Step 6 with the switch in the AUTO position and the remote contact energized. the field- Disconnect- When disconnect is factory-inst_dled, it is wired to the motol: and thlly tested befole shipped. Open the disconnect cover and fan section access door to check for &_mage before proceeding. DISCONNECT WIRING label and lug provid- 1. Connect the field line voltage power source to the top of the disconnect (knockouts are provided). positions if is detected. to stop the 7. Select a location at the bottom control terminal block. 8. Before drilling any hole, be sure the hole and any fieldsupplied conduit fittings will not interfere with the door or components inside the enclosme. 9. Drill the appropriate size hole and connect supplied conduit to the enclosure. and carefully Verify that the fan wheel is rotating in the proper dilection. If it is not, remove power and reverse any two of the line voltage connections at the starter termimds (LI, L2, L3). NOTE: For remote control operation (AUTO position), fire/ smoke shutdown, or shutdown on coil freeze protection, a second conduit should be used to connect these control functions. I 4. of the starter near the 2. Remove the knockouts field-supplied conduit. 3. Refer to the wiring diagraln supplied with the unit and connect the line voltage power source to the line voltage terminals (LI, L2, L3) as shown. 4. Refer to the factory-supplied voltage w;uning verify that the power source is correct. 5. Connect the ground wire to the grounding the disconnect. START-UP the field- as required to accommo&tte the label and lug provided in AND TEST 1. Set the disconnect switch to the OFF position. If a smoke detector or remote fire shut down is provided (field-supplied), remove the factory-supplied jumper between terminals 1 and 2 in the starter Connect the norm_dly closed, isolated &y contact from the smoke detector or fire system to these terminals. 2. Verify that the fan can fi'eely rotate and remove any loose items inside the fan section. 3. Close and secme the fan access door and the disconnect door covel: 4. Apply powec 11. If a coil fieeze detection thermostat is provided, remove the factory-supplied jumper between termimds 1 and 2 in the stmtec Connect the normally closed contact from the low temperatme thermostat to these terminals. 5. Set the disconnect switch to the ON position that the fan operates. 10. 12. For 3-phase NOTE: For lused type disconnects, blown luses MUST replaced with the stone type and size originally supplied. When variable frequency diive (VFD) is factoryinstalled, it is wired to the motor and frilly tested before shipment. Drive programming is also done at the factory, including electronic overload, which is programmed for the motor FLA. Refer to Tables 24 and 25. Open the VFD front cover and the fan section access door to check for any &tmage before proceeding. WIRING 1. Select a suitable location in the bottom connect field-supplied power source. 1. Set the HOA switch on the front of the starter to the OFF position. 3. Close and secure the fan access door or panel and the starter door coveg be VFD- IMPORTANT: Many starters contain a multi-tap control transformer. The line voltage tap on the control transformer must be set in the field. For starters operating at 200/230-50 Hz, 208/230-60 Hz, or 380/400/ 415-50 Hz, the line voltage tap on the control transformer must be set to the appropriate line input voltage. Verify that the fan can freely rotate and remove items inside the fan section. and carefully Verify that the fan wheel is rotating in the proper direction. If it is not, remove power and reverse any two of the line voltage connections at the starter termimds (LI, L2, L3). START-UP AND TEST -- Before applying power to the starter, verify that the motor overload inside the starter is set to the lhll load mnperage (FLA or RLA) specified on the motor nameplate. 2. motor: Place the switch back in the OFF position open the fan access dool: For remote st_ut/stop operation (when the HOA [hand/ auto/off] switch is placed in the AUTO position), connect a field-supplied, normally open isolated dry contact between terminals 3 and 4. This contact must be suitable for at least 3 amps at 120 vac. and verify 2. Remove the appropriate size knockout using a suitable knockout punch tool. Do NOT use a drill; metal shavings will &tmage the chive. 3. Connect the field-supplied any loose 71 of the VFD to conduit to the VFD enclosure. 4. Referto thewiringdiagram supplied withtheVFD connect thelinevoltage powersource tothelinevoltage terlninal s(U1,V1,W1)asshown. 5. Refertothefactory-supplied voltage warning labeland verifythat the power source is correct. 3. 6. 5. Refer to the factory-supplied voltage warning verify that the power source is correct. 6. Connect the ground wire to the grounding on rite bottom of the Bypass box. lug provided 7. Refer to the VFD Steps 7 and 8 to connect wiring. VFD control Connect the ground wire to the grounding on the bottom of the VFD. 4. Drill the appropriate size hole and connect the fieldsupplied conduit to the enclosure. Refer to the wiring diagram supplied with rite bypass and connect the line voltage power source to the line voltage terlninals iLl, L2, L3) as shown. lug provided 7. Select another suitable location on the bottom of the VFD to connect file field-supplied control wiling. 8. Ix_cate and use one of the unused knockouts on file VFD housing and connect the control wiring conduit. Refer to Fig. 76-79 for field control wiring connections. NOTE: Ifa 0 to 10 or 2 to 10 vdc signal is used to control the drive speed, refer to page 16 of the ABB ACH-550 manu_d shipped with the &ive to reset the dipswitch to the voltage or V position. Verify that the AI switch is set to the voltage position. DO NOT reprogram the &ive. START-UP AND TEST label and START-UPAND TEST-Before applying power to the VFD Bypass and VFD, verify that the motor overload inside the bypass has been set to the full load amperage (FLA or RLA) as specified on the motor nameplate. IMPORTANT: Some bypass assemblies (208/230-60, 200/230-50, 380/400/415-50) contain a multi-tap control transformel: The line voltage tap on the control transformer must be adjusted to the appropriate line voltage. 1. Close and secure rite fan access door trod the VFD covel: 2. Apply power and allow &ive to initialize. 3. Press the HAND button and verify that rite drive operates at 8Hz. I. Set rite switch position. 4. Press Up arrow to increase decrease speed. 2. Verify that the fan freely rotates and remove items inside the fan section. 5. Press the Offbutton 3. 6. Press the Auto button to operate the drive from the Energy Management System (EMS) interface. Verify that all VFD interface functions are working (start/stop, speed controls, fire/smoke, shutdown, etc.) between the VFD and the EMS. Close and secure the fan access door and the bypass and VFD covers. 4. Apply pewee 5. Set the switch to rite LINE position and verify that the fan operates. For 3-phase motors: speed and Down turow to and verify that the fan stops. Refer to Tables 24 and 25 for additional VFD information. -- When the VFD and bypass m'e factory-installed, they ;u'e wired to the motor and fully tested before shipped. The VFD is programmed at the factory as ordered, including electronic overload, which is progralnmed for the motor FLA (full load amps) as supplied. 6. 7. and loose 8. 2. 9. Set the switch to the DRIVE position and verify that the VFD operates. Press the Hand button and verify that the fan operates. 1. Select a suitable location in the bottom panel of the bypass box to connect field-supplied power source. Before drilling any hole, be sure the hole and any fieldsupplied conduit fittings will not interfere with the door or components inside the enclosure. to rite OFF Place the switch back in the OFF position and carefully open the fan access dool: Verify that the fan wheel is rotating in the proper direction. If it is not, remover power and revel_e any two of the line voltage connections in the bypass box (Ll, L2, L3). DO NOT swap the motor leads; this will cause the fan to rotate in the reverse direction when operating from the VFD. Make sure the bypass cover is closed then apply power VFD With Bypass Open the bypass box cover and rite fan section access door to check for any damage before proceeding. WIRING on the front of rite bypass Press the Auto button and verify that the drive operates fi_m the EMS interface. Verify that all VFD interface l'unctions between the VFD and the EMS system are working. Table 24 -- VFD Data MOTOR HP ABB PART NO. ACH550-UH- l& 3/4 1 1V2 2 3 5 7V2 10 15 20 25 30 40 04A6-2 04A6-2 04A6-2 06A6-2 07A5-2 012A-2 017A-2 024A-2 031A-2 046A-2 059A-2 075A-2 088A-2 114A-2 80MI MAX. CONTINUOUS OUTPUT AMPS FUSE AMPS 208-230 Volt / 3 Phase / 60 Hz (Programmed 4.6 10 4.6 10 4.6 10 6.6 10 7.5 10 11,8 15 16,7 25 24.2 30 30.8 40 46,2 60 59,4 80 74,8 100 88,0 110 114,0 150 LEGEND MCCB -- Molded-Case Circuit Breaker NOTE: Two-pole motors operate at a nominal 3600 rpm for 60 Hz and 3000 rpm for 50 Hz; 4-pole motors operate at a nominal 1800 rpm for 60 Hz and 1500 rpm for 50 Hz, 72 MCCB RATED AMPS PROGRAMMED Overload Trip Ampe 4 pole / 2 pole to Operate at 208 volts) 15 1.8/ 1,7 15 2.6/ 2,5 15 3.5/ 3,2 15 5.2/ 4,2 15 6.7/ 5,9 15 9.0/ 8,5 25 14.5/ 13,6 30 21.4/ 20,7 40 27.4/ 27,4 60 40.5/ 40,5 80 53.0/ 52,2 100 67.0/ 66,0 110 82.0/ 78,0 150 92.0/107,0 SETTINGS I I Max. Output Ampe 4 pole / 2 pole 3.0/ 2,2 3.2/ 3,0 3.8/ 3,8 5.8/ 5,8 7.2/ 7,0 10.0/ 9,5 16.7/ 16,0 24.0/ 23,0 30.8/ 3O,O 46.2/ 43,0 59.4/ 57,0 74.0/ 71,0 85.0/ 82,0 114.0/110,0 Table 24 -- VFD Data (cont) 39M MOTOR HP ABB PART NO, ACH550-UH- MAX. CONTINUOUS OUTPUT AMPS FUSE AMPS I I Overload PROGRAMME Trip Amps 4 pole / 2 pole to Operate at 230 volts) I Max. Output Amps i SETTINGS 4 pole / 2 pole 143A2143,200, 200,12 0/1300,14 208-230 Volt / 3 Phase / 60 Hz (Programmed 60 75 178A-2 221A-2 178 221 l 250 300 l 1/2 3/4 1 11/2 2 3 5 71/2 10 15 20 25 30 40 50 60 75 100 03A3-4 03A3-4 03A3-4 03A3-4 03A3-4 05A4-4 06A9-4 012A-4 015A-4 023A-4 031A-4 031A-4 038A-4 059A-4 072A-4 077A-4 096A-4 124A-4 460 Volt / 3 Phase / 60 Hz (Programmed 3.3 10 3.3 10 3.3 10 3.3 10 3.3 10 5.4 10 6.9 10 11.9 15 15.4 20 23 30 31 40 31 40 38 50 59 80 72 90 77 100 96 125 124 175 1 11/2 2 3 5 71/2 10 15 20 25 30 40 50 60 75 04A6-2 06A6-2 07A5-2 012A-2 017A-2 024A-2 031A-2 046A-2 059A-2 075A-2 088A-2 114A-2 143A-2 178A-2 221A-2 200-230 Volt / 3 Phase / 50 Hz (Programmed 4.6 10 6.6 10 7.5 10 11.8 15 16.7 25 24.2 30 30.8 40 46.2 60 59.4 80 74.8 100 88 110 114 150 143 200 178 250 221 300 1 03A3-4 03A3-4 04A1-4 05A4-4 08A8-4 012A-4 015A-4 023A-4 031A-4 038A-4 044A-4 059A-4 077A-4 096A-4 124A-4 157A-4 380 Volts / 3 Phase / 50 Hz (Programmed 3.3 10 3.3 10 4.1 10 5.4 10 8.8 15 11.9 15 15.4 20 23 30 31 40 38 50 44 60 59 80 77 100 96 125 124 175 157 200 11/2 2 3 5 71/2 10 15 20 25 30 40 5O 6O 75 100 LEGEND MCCB -- MCCB RATED AMPS Molded-Case Circuit Breaker NOTE: Two-pole motors operate at a nominal 3600 rpm for 60 Hz and 3000 rpm for 50 Hz; 4-pole motors operate at a nominal 1800 rpm for 60 Hz and 1500 rpm for 50 Hz. 73 250 300 l to Operate at 460 volts) 15 15 15 15 15 15 15 15 20 30 40 40 50 80 90 100 125 175 to Operate 15 15 15 15 25 30 40 60 80 100 110 150 200 250 300 to Operate 15 15 15 15 15 15 20 30 40 50 60 80 100 125 175 200 154.0/135.0 186.0/166,0 T 172.0/145.0 221.0/172,0 0.9/ 1.0 1.3/ 1.2 1.6/ 1.5 2.2/ 2.0 2.7/ 2.7 4.0/ 3.8 6.2/ 6,0 9.0/ 8,8 12.0/ 11.6 17.6/ 16.5 23.0/ 23.0 29.0/ 28.0 34.5/ 34.0 46.0/ 44.0 58.0/ 55.0 73.0/ 68,0 90.0/ 85.0 118.0/110,0 1.5/ 1.2 1.7/ 1.5 1.9/ 1.7 2.8/ 2.3 3.0/ 3.0 4.5/ 4.2 6.9/ 6,5 10.0/ 9,5 13,6/ 12.8 19.3/ 19.0 25,0/ 25.0 31.0/ 30.0 38.0/ 38.0 48.0/ 50.0 60.0/ 60.0 77.0/ 72,0 94.0/ 90.0 124.0/114,0 3.3/ 3.3 4.9/ 4.9 6.3/ 6,3 8.7/ 8,7 14.0/ 14.0 21.2/ 20.2 27.2/ 27.4 41.4/ 40.5 53.4/ 49.0 65.4/ 66.0 78.0/ 78.0 107.0/107,0 135.0/135,0 169.0/169.0 210.0/210.0 3.9/ 3.9 5.8/ 5.8 7.1/ 7.1 10.0/ 10,0 16,7/ 16.7 24.2/ 24.2 30.8/ 30.8 46,2/ 46.2 59.4/ 56.0 74.0/ 74.8 86.0/ 86.0 114.0/114,0 135.0/135,0 169.0/169.0 210.0/210.0 1.7/ 1,7 2.5/ 2.5 3.2/ 3,2 4.5/ 4,5 7.0/ 7.0 10.6/ 8,9 13.6/ 11.6 20.7/ 17.0 26.7/ 24.5 32.7/ 29.5 39.0/ 39.0 53.5/ 45.5 67.5/ 67,5 84.5/ 84,5 105.0/105,0 134.0/134,0 2.3/ 2,3 3.3/ 3.3 3.8/ 3,6 5.4/ 5,3 8.5/ 8.0 11.9/ 11,0 15,4/ 14.6 22.6/ 21.0 29,3/ 29.0 37,0/ 36.0 44.0/ 44.0 57.0/ 55.0 70.0/ 70,0 88.0/ 88,0 105.0/105,0 134.0/134,0 at 200 volts) at 400 volts) Table 25 -- Air Handler Factory-Set Parameters GROUP NUMBER 99 10 11 12 13 14 16 20 21 22 26 30 31 34 40 PARAMETER NUMBER DESCRIPTION VALUE 9902 9904 Application Macro Motor Control Mode Supply Fan Scalar 9905 9906 9907 9908 9909 1001 1002 1003 1104 1105 Motor Nominal Voltage Motor Nominal Current Motor Nominal Frequency Motor Nominal Speed Motor Nominal Power EXT1 Commands EXT2 Commands Direction REF1 Minimum REF1 Maximum t 60 Hz or 50 Hz Nameplate rpm at Load Nameplate Hp DI-1 Start / Stop (O) N/A Forward 9.33 Hz at 60 Hz/7.78 Hz at 50 Hz 62.7 Hz at 60 Hz / 52.2 Hz at 50 Hz 1201 1202 1301 1302 1303 1304 1305 1306 Constant Speed Select Constant Speed Value Minimum AI-1 Maximum AI-1 Filter AI-1 Minimum AI-2 Maximum AI-2 Filter AI-2 DI-3 Field Program (8 Hz - Motor Nominal Freq.) 0% 100% 1 sec 0% 100% 1 sec 1401 1402 1403 1601 1608 1609 2003 Relay Output 1 Relay Output 2 Relay Output 3 Run Enable Start Enable 1 Start Enable 2 Maximum Current Started Run Fault (Inverted) DI-2 DI-4 DI-5 ** 2007 2008 2101 2102 2202 2203 Minimum Frequency Maximum Frequency Start Function Stop Function Accelerate Time Decelerate Time 8 Hz 60 Hz / 50 Hz FlyStart Coast 60 Seconds 60 Seconds 2605 2606 2607 3006 3007 Volt/Freq Ratio Switching Frequency Switching Frequency Control Motor Thermal Time Motor Load Curve Linear 8 KHz ON 1050 105% 3008 3009 3010 Zero Speed Load Break Point Frequency Stall Function 70% 35 Hz Fault 3011 3012 3017 3101 3102 Stall Frequency Stall Time Earth Fault Number of Retries Trial Time 20 Hz 20 sec Fault 2 600 sec 3103 3104 Delay Time AR Overcurrent 5 sec Enable 3105 3106 3107 AR Overvoltage AR Undervoltage AR AI< Minimum Enable Enable Disable 3108 3415 3416 3417 3418 3419 3420 3421 4001 AR External Fault Signal Parameter 3 Signal 3 Minimum Signal 3 Maximum Output 3 DSP Form Output 3 DSP units Output 3 Minimum Output 3 Maximum Gain (O) Disable SPEED O 30000 O rpm O 30000 0.7 4002 4005 4006 Integration Time Error Value Invert Units 30 sec NO Volts 4007 401 O 4011 4012 4013 4016 4027 Display Format Setpoint Select Internal Setpoint Setpoint Minimum Setpoint Maximum ACT 1 Input PID 1 Parameter Set x.xxx Internal Field Program (O.Ov - lO.O v) O.O v 10.O v AI-2 SET 1 *Factory Programmed as follows: For 208-230v / 60 Hz = 208,460v / 60 Hz = 460,200-230v / 50 Hz = 200, 380 / 50 Hz = 400. tMotor Nameplate Amps. Factory programmed per Table 24. This value should always be compared to the actual motor nameplate **Maximum Output Amps -- Factory programmed per Table 24. 74 value before start-up. , 4-20 ma ,.o° AI-1 Cable Shield Ground ,o°°**°° Speed/ --- AI-t VFD SPEED Signal (+) 4-20 ma // IControl Signal _T - - AI-I VFD SPEED Signal (-) ground - Field-Supplied Input Connections 24 Vdc Ground -° DC Common Jumper E Digital Input Common N.O. Start / StopContact _= = H. = ° .ll.,. ° =_,_""_O=.H =... DI-1 Start/Stop j, o.°..,, _..._ c:V_._ ./&_.D..%C?.,._._t .... •: DI-2 Run Enable N,C. Low Limit Thermostat DI-4 Start Enable 1 i.......N.cA!i.g._e.Swi!_.!: ...... DI-5 Start Enable 2 NOTES: 1. All conductors are no. 18 AWG (American Wire Gage) minimum. 2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required. Fig. 76 -- Field-Supplied Control Wiring for VFD Output Adapter :() Shielded Cable (_'!'_=!'" i I AI-I Cable Shield Ground 2 AI-I VFD SPEED Signal (+) 4-20 ma 3 AI-I VFD SPEED Signal (-) ground corn 4 5 6 7 8 TB3 l 9 -°, w°,_l_==*=mwH,*°,°,°mmmmm_**_°==_*m,,,°m*,_ I r 2 3 ,.., 4 ... 5 I I Jumper E Jw==,=|_=m=,**J===°°°°,=°°,=°°°°,°,,,,,,=====°=°=, I.. N.C,; F._ire_Det. Contact I0 24 Vdc 11 Ground - DC Common --i7- Digital Input Common 13 DI- l Start / Stop I"'7 DI-2 Run Enable 15 6 DI-4 Start Enable 1 7 --5- 8 DI-5 Start Enable 2 18 9 10 ABB VFD Drive Air Manager Air Manager Input Drive Connections NOTES: 1. All conductors are no. 18 AWG (American Wire Gage) minimum. 2. Install jumper wire if fire/smoke detector, is not required. Fig. 77 -- Field Wiring the VFD to the AirManager 75 TM Control AI-1 Cable ,.... Shielded Cable ?-;?; I I I _ TB3 I I -T- | I 2 I | I :3 4 Ground AI-I VFD SPEED Signal (+) 4-20 AI-I VFD SPEED Signal (-) ground ma 24 Vdc Ground I I iJ._,* Jumper E ,.=...l............m= i _ --TI-- Shield L Digital DI-I J= J J,m•Jllo°°o..°,,J=*,w,*,= N.C_ Fire/m..__m_Det. - DC Common Input Common Start/Stop DI-2 Run Enable Con.tact . 6 i-._--7- DI-4 Start Enable 1 DI-5 Start Enable 2 8 9 10 ABBVFD Drive CC6400 Drive CC6400 Control Box Input Connections NOTES: 1. All conductors are no. 18 AWG (American Wire Gage) minimum. 2. Install jumper wire if fire/smoke detector, is not required. Fig. 78 -- Field Wiring the VFD to the CC6400 Comfort Control 1 2 3 4 5 d Field-Supplied Input Connections 7 8 9 _,,=,,,,.,=l==m====_**_=======***==°°,,°.**J : "_ Jumper E N.O. Start / Stop Contact ............... o.--/o 10 24 Vdc 11 Ground - DC Common -57- ................. _,..._,c:._!r_./&_bP.e.t,.C.'o".:_.%.. --7ZN.C. Low Limit Thermostat ............... _ ................ 16 !......,N.-.c..._.t_ ._.Swi_.c..h. ...... --?7- Digital Input Common DI-I Start/Stop DI-2 Run Enable DI-3 Fixed Speed Enable DI-4 Start Enable 1 DI-5 Start Enable 2 18 NOTES: 1. All conductors are no. 18 AWG (American Wire Gage) minimum. 2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required. 3. Program desired speed setpoint in Hz using parameter 1202. Fig. 79 -- Field Wiring for High Inertia/Low Horsepower Applications Using VFD as a Starter 76 VFD Configuration- The VFD keypad is shown in Fig. 80. Tile flmction of SOFT KEYS 1 and 2 change depending on what is displayed on the screen. The function of SOFT KEY 1 matches the word in the lower left-hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower right-hand box on the display screen. If the box is empty, then the SOFT KEY does not have a function on that specific screen. The UP and DOWN keys am used to navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the drive to automatic control. The HAND key is used to change control of the drive to local (hand held) control. The HELP button is used to access the help screens. NOTE: The current parameter value appem.s above the highlight parameter. To view the default pm'ameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the application macro "HVAC Default." VFD Modes -- The VFD has several different modes for configuring, operating, find diagnosing the VFD. The modes ale: • • • • START UP WITH ASSISTANT-The initial start-up has been performed at the factory. To stm_ up the VFD with the Stml-Up Assistant, perform the following procedure: • • • 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight ASSISTANTS on the display screen find press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight Commission Drive and press SEL (SOFT KEY 2). 4. The Stml-Up Assistant will display the parameters that need to be configured. Select file desired values and press SAVE (SOFT KEY 2) after every change. Tile process will continue until all the parameters am set. START UP BY CHANGING PARAMETSERS INDIVIDUALLY -- Initial start-up is performed at the factory. To start up the VFD with by changing individual parameters, perform the following procedure: standard display mode-shows drive status information and operates the drive parameters mode-edits parameter values individually start-up assistant mode -- guides the start up and configuration changed parameters mode -shows all changed parameters drive parameter backup mode -- stores or uploads the parameters clock set mode -- sets the time and date for the drive 1/O settings mode -- checks and edits the I/O settings Standard Display read information reach the stan&trd play shows status MODE _ / 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP and DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2). 5. Use the UP or DOWN keys to change the value of the Du'ameteb: 6. Press SAVE (SOFT KEY 2) to store the modified vfflue. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that am not saved will not be changed. 7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the Duameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu. Mode -- Use the standtud display mode to on the diive status and operate the diive. To display mode, press EXIT until the LCD disinformation as described below. See Fig. 81. j4,._SET I ""=AUTO'_ . 30.0 / 3.7A | 838 Fig. 81 -- Standard 15.8Hz'"- Hz / POINT I / RPM / Display Example The top line of the LCD display shows the basic status information of the diive. The HAND icon indicates that the diive control is local from file control panel. The AUTO icon indicates that the drive control is in remote control mode flnough the I/O. The anow icon indicates the drive and motor rotation status. A rotating arrow (clockwise or counterclockwise) indicates fllat the diive is running. A rotating blinking rerow indicates flint the diive is running but not at set point. A stationary arrow indicates that the diive is stopped. For Carrier air handler units, the rotation is always forward. Using parameter group 34, the middle of the LCD display can be configured to display 3 pmameter values. The default display shows parameters 0103 (OUTPUT FREQ) in Hz, 0104 (CURRENT) in amperes, and AII (Amflog Input 1) in revolutions per minute. The upper right hand corner shows the frequency set point that the drive will maintain. The bottom comers of the LCD display show the functions currently assigned to the two soft keys. Tile lower middle displays the current time (if configured to show the time). The fib.st time the drive is powered up, it is in the OFF mode. To switch to local hand-held control find control the diive using the control pane, press the HAND or AUTO buttons. Pressing the HAND button switches the drive to hand control while keeping the drive running. Pressing the AUTO button switches the diive to remote input control. The OFF button stops the drive. To beturn to auto control, press the AUTO button. To start the diive press the HAND or AUTO button, to stop the drive press the OFF button. To adjust the speed set point while in HAND mode, press file UP or DOWN buttons (the reference changes immediately). The reference can be modified in the local control (HAND) mode, and can be pfuameterized (using Group 11 reference select) to also allow modification in the bemote control mode. STAJUS LED {GREEN WHEN NORMA , IF FI ASH NG RED, SEE DIAGNOSTICS.) SOFT SOFT KEY 2 HELP (ALWAYS AVAILABLE) OFf Fig. 80 -- VFD Keypad 77 Parameters Mode -- The Parameters mode is used to change the pm'ameters on the &ive. To change parameters, perform the following procedure: 1. Select MENU displayed. 3. 4. (SOFT KEY 2). The Mtdn menu will be Use the UP or DOWN keys to highlight UPLOAD TO PANEL and press SEL (SOFT KEY 2). The text "Copying Parmneters" will be displayed with a progress indicator To stop the process, select ABORT (SOFT KEY 1). 2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2). 5. When the upload is complete, successlul" will be displayed. 3. Use the UP or DOWN keys to highlight the desired p_u'ameter group and press SEL (SOFT KEY 2). 6. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu. 4. Use the UP or DOWN keys to highlight p_u'ametel_ and press EDIT (SOFT KEY 2). 7. The control drive. 5. Use the UP or DOWN ptuameters. 6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous v_due. Any modifications that are not saved will not be changed. 7. keys to change the desired the value of the 1. Install the control panel with the conect the leplacement VFD. NOTE: The current parmneter value appears above the highlight pammetel: To view the default parmneter vMue, press the UP and DOWN keys simultaneously. To restore the default factory settings if a drive fails, download the pm'ameters to the VFD from the control panel. Parameters can also be changed individually. 3. Use file UP or DOWN keys to highlight p_u'ameter group and press EDIT (SOFT change the p_uameters if desired. 4. Press EXIT (SOFT KEYI ) to exit the Changed ters mode. onto Select MENU displayed. KEY 2). The Main menu will be 3. Use the UP or DOWN keys to highlight PAR BACKUP on the display scleen and press ENTER (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight DOWNLOAD TO DRIVE ALL and press SEL (SOFT KEY 2). 5. The text "Restoring Parmneters" will be displayed with a progress indicatol: To stop the plecess, select ABORT (SOFT KEY 1). is complete, the text "Pmameter will be displayed. 7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu. 8. The control drive. panel can now be disconnected from the To set the clock, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. the desired KEY 2) to Parmne- 2. 3. Each diive is custom progralnmed at the factory. The first option is to download all parameters. This copies both application and motor parameters to the drive from the control panel. This is recommended to create a backup of the pm'ameters group for the diive. The second option downloads only the application parameters to the di'ive. Parameters 9905, 9906, 9907, 9908, 9909, 1605, 1607, 5201, and group 51 ptuameters and internal motor pm'ameters are not copied. (SOFT KEY 2). The Main menu will be Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2). 78 Use the UP or DOWN keys to highlight CLOCK SET on the display screen and press ENTER (SOFT KEY 2). The clock set pmameter list will be displayed. Use the UP or DOWN keys to highlight CLOCK VISIBILITY and press SEL (SOFT KEY 2). This pm'ameter is used to display or hide the clock on the screen. Use the UP or DOWN keys to change the parameter setting. Pless OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 4. Use the UP or DOWN keys to press SEL (SOFT KEY 2). Use change the hours and minutes. to save the configuration and menu. 5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP and DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 6. Use the UP or DOWN keys to highlight SET DATE and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the day, month, and yem: Pless OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. Upload All Parameters -- To upload and store _dl parametel_ to the control panel from the VFD, perform the following procedure: 2. (SOFT parameters Clock Set Mode -- The clock set mode is used for setting the date and time for the internal clock of the VFD. In order to use the timer functions of the VFD control, the internal clock must be set. The date is used to determine week&tys and is visible in the fault logs. Drive Parameter Backup Mode -- The diive parameter back up mode is used to store the drive parameters. The pammetel_ can be uploaded from a VFD to the removable control panel. If a drive failure occurs, the control panel can then be transferred to the new drive and the parameters downloaded into memory. 1. Select MENU displayed. from the 2. 6. When the download download successful" Changed Parameters Mode -The Changed ParametelN mode is used to views and edit recently changed parametel_ on the drive. To view the changed parametelN, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. Use the UP or DOWN keys to highlight CHANGED PAR on the display screen and press ENTER (SOFT KEY 2). A list of the recently changed parameters will be displayed. panel can now be disconnected upload Download All Parameters -- To download all parameters from the control panel to the VFD, perform the following procedure: Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of pmameter groups. Continue until all the parametelN have been configured and then press EXIT (SOFT KEY 1) to return to file main menu. 2. the text "Parameter highlight SET TIME and the UP or DOWN keys to Press OK (SOFT KEY 2) return to the Clock Set 7. UsetheUPorDOWNkeysto highlight DATEFORMATandpressSEL(SOFTKEY2).UsetheUPor DOWNkeystochange thep_uameter setting. Press OK (SOFT KEY2)tosave theconfiguration andreturn tothe ClockSetmenu. 8. Press EXIT(SOFTKEY1)twicetoreturntothemain menu. othel.s, as they me specific for fllen be separated, lifting the from the unit at approximately not to damage the double bulb 8. I/O Settings Mode -- The I/O Settings mode is used for viewing and editing the I/O settings. To configure the I/O settings, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use file UP or DOWN keys to highlight I/O SETHNGS on the display screen and press ENTER (SOFT KEY 2). The I/O Settings parameter list will be displayed. 3. Use the UP or DOWN keys to highlight setting and press SEL (SOFT KEY 2). 4. Use the UP or DOWN keys to select file palameter view. Press OK (SOFT KEY 2). 5. Use the UP or DOWN keys to change the parameter setting. Press SAVE (SOFT KEY 2) to save the configuration. Press CANCEL (SOFT KEY 1) to keep file previous value. Any modifications that are not saved will not be changed. Press EXIT (SOFT KEY 1) twice to return to the main menu. 6. 9. Electric Heaters -If circumstances require it can only be installed Heat section). Installation an EHS section will void 10. the desired I/O to Use copper power supply wires rated for 75 C minimum. On 250 v or greater applications, use 600 v rated wiring. Size wires to carry 125% of current load on each set of terminals. Use file following formulas as required: 1. Identify ALL electrical power supplies serving the unit, lock off and tag each before woNing on the unit. 2. Locate the electric heat section mounted on the unit and remove the protective shipping cover Identify file electric heater and verify the heater matches the unit. Unit hand and heater hand must also agree. 4. Properly sized power wiring and control wiring entry holes are provided in the upstrealn sidewall of the heater control box. The heater has lifting hook openings on each end. When file heater is within 3 in. of its final position, reinstall the crossrail, with the box-seal facing down, and panel seal towmd the top. Secure the heater to the section posts and mils with the lurnished screws, drawing it the last 3/s in. into final sealed position against the framework, by alternately cross tightening the screws. The opposite end of the heater rests on lateral spacel.s provided on the floor panel, and is retained by a screw through an angle clip on the last one or by tin upright corner flange. Replace the top panel, and proceed to complete the wiring in accord with all applicable codes and ordinances. The wiring diagram is fastened inside the control box, with a spare, loose copy provided as a convenience for maintenance manual pmpmafion. Do not mix the wiring diagrams, as they are specific for each unit. 11. Connect power and control wiring according to the wiring diagram supplied (see Fig. 82 for typicfd wiring details). CONNECT POWER AND CONTROL WIRES -- Heater wiring schematic is located on control box panel. Verify minimum airflow requirement (minimum coil face velocity, fpm) will be met, especially on applications where vguiable air volume is supplied. Electric heaters are facto]y installed. field installation of an electric heater. in a factory-supplied EHS (Electric of electric heat in a section other than file UL listing of the product. 3. this location.) The corners may rail and corner segments away a 45 degree angle, taking cam seal. Single-phase line cunent = Three-phase line current = (kW per set of termimds) (1000) voltage (kW per set of termimds) (voltage) (1000) (1.73) Note that if the heater is rated fit 50 kW (or morn) and is controlled by a cycling device such as a multi-stage thermostat. or a step controller, conductors may be sized fit 100% of load mnperes (see Table 26) per NEC Section 424-22. Heater construction and application information are based upon Space Heating Standard UL No. 1096 and the requirements of file NEC. Installer is responsible for observing locffl code requirements. Install a disconnect switch or main circuit breaker in accordance with NEC and other applicable codes. Locate so that it is easily accessible and within sight of heater control box (per NEC Article 424-19 and 424-65). Weatherproof junction boxes have no knockouts for wire entrance. Provide knockouts for all wiring using field-supplied grommets of correct size and type of conduit as required. Where field-supplied thermostats are used, isolate circuits to prevent possible interconnection of control circuit wiring. Where field-supplied step controller is used, connect steps to terminals as mmked on wiring schematic. When connecting multi-stage heaters, wire stage no. 1 so that it is first stage on, last stage off. Provide suMcient clearance for convection cooling of heaters wifll solid-state controllel.s. Provide at least 5-in. of free air space above and below cooling fins extending from heater terminal box. Be sure to connect interlock terminals FI and F2 to auxiliary contacts on fan starter A narrow, fixed upstream panel is provided for electricfd power ent U from the outside. Power may also enter the unit from below, penetrating the floor of the unit. Carefulfy seal all entries, weathertight where necessary. Control wiring may enter the same way as electrical wiring. Take future service requirements into account when locating field power entU holes in the unit casing. 5. Sleeve these holes and seal around the conduit to preserve the integrity of the casing. In some cases, it might be preferable for the power to actufdfy enter the cabinet through an adjacent section, or enter the control box from another angle, which is acceptable. 6. If the original holes am not used, they must be appropriately plugged. 7. Insert the electric heater into the section (the heater element rack will be located along the leaving air side of the section). NOTE: If the heater must be hoisted into position, once the top panel has been removed to a safe place, the horizontal top rail may be removed by carefully removing the fiat corner plug from the end corner pieces and extracting the screw visible within the exposed cavity. (Do not mix these screws with 79 Each heater has 2 different types of factory-installed thermal cutouts for over temperature protection; an automatic reset thermal cutout for primaly protection and a manual reset thermal cutout to protect against failure of the primary system. Also provided is an airflow pressure differential switch to plevent the heater from operating when file fan is not in opelation or airflow is restricted or insufficient. The primary automatic reset cutout is a bi-metal disk-type cutout. It is wired into the control circuit which operates the magnetic disconnecting contactors (the stone contactors which also switch on and off the vtuious steps of file coil). The secondary manu_fl reset cutout is a bi-met_fl disk-type cutout. This secondmy therm_fl cutout is load cmrying and is inst_dled in each heater subcircuit. The primmy and secondary overtempemture protection systems me independent of each other The secon&try system is designed to protect agtfinst possible fifilure of the primmy system to deenergize the heate_: Table 26 -- Field Wiring for Incoming Conductors Sized for 125% of Heater Load Subcircuits in the heaters are designed in complkmce with pm'agmph 424-22 of the NEC. The coil is subdivided into circuits that di'aw no more than 48 amps each and is fused for at least 125% of the circuit rating. *Values are based on Table 310-16 of the NEC for 75 C insulated copper wire. Not more than 3 conductors in a raceway. NOTES: 1. Be sure to consider length of wiring run and possible voltage drops when sizing wires. 2. Field power wiring -- Heaters are furnished with a terminal block sized for incoming copper conductors with 75 C insulation rated to carry at least 125% of the heater load. However, conductors can be sized to carry 100% of the heater load if the heater is rated at 50 kW or more, and the heater is controlled by a cycling device such as a multi-stage thermostat, step controller, or SCR (silicon control rectifier) power controller. Terminal blocks and knockouts are sized to handle either 100% or 125% conductors. Pilot tube is to be positioned so that the airflow switch actuated by a minimum negative pressure of 0.07 in. wg. Refer to Table 27 for heater electric_fl data. WIRE SIZE (AWG or kcmil) 14 12 10 8 6 4 3 2 1 LOAD AMPS* Copper 12 16 24 40 52 68 80 92 104 WIRE SIZE (AWG or kcmil) 1/0 2/0 3/0 4/0 250 300 350 400 500 LOAD AMPS* Copper 120 140 160 184 204 228 248 268 304 LEGEND AWG kcmil NEC is 8O ---- American Wire Gage Thousand Circular Mils National Electrical Code Table 27 -- Electric Heater Data 39M UNIT SIZE HEATER AREA (sq ft) NO. OF CONTROL STEPS* HEATER COIL kW 5 03 3 06 5.2 3 3 3 06 7.4 6 oo 10 9.9 12 12,4 14 13.6 NOMINAL COIL FACE VELOCITY (fpm) 500 208/3/60 TEMP RISE (F) Total FLA MCAt VOLTS No. Sub Ckt 240/3/60 VOLTS No. Sub Ckt Total FLA MCAt MOCP 480/3/60 MOCP Total MCAt FLA VOLTS No. Sub Ckt 600/3/60 MOCP Total MCAt FLA VOLTS No. Sub Ckt --- MOCP MCAt FLA VOLTS No. Sub Ckt MOCP 11 14 17 1 20 12 15 1 20 6 8 1 20 5 6 1 20 8 10 1 20 10 500 21 28 35 1 35 24 30 1 35 12 15 1 20 10 12 1 20 15 19 1 20 15 500 32 42 52 1 60 36 45 1 50 18 23 1 25 14 18 1 20 23 29 1 30 20 25 500 500 43 56 69 2 70 48 60 2 70 24 30 1 35 19 24 1 25 30 38 1 40 53 69 87 2 90 60 75 2 80 30 38 1 40 24 30 1 35 38 48 1 50 30 500 64 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 35 500 75 97 122 3 125 84 105 2 110 42 53 1 60 34 42 1 45 53 67 2 70 10 500 12 28 35 1 35 24 30 1 35 12 15 1 20 10 12 1 20 15 19 1 20 15 500 18 42 52 1 60 36 45 1 50 18 23 1 25 14 18 1 20 23 29 1 30 20 500 25 56 69 2 70 48 60 2 70 24 30 1 35 19 24 1 25 30 38 1 40 30 500 37 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 40 500 49 111 139 3 150 96 120 3 125 48 60 2 70 39 48 1 50 61 76 2 80 50 500 61 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 74 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 20 500 17 56 69 2 70 48 60 2 70 24 30 1 35 19 24 1 25 30 38 1 40 30 500 26 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 40 500 35 111 139 3 150 96 120 3 125 48 60 2 70 39 48 1 50 61 76 2 80 50 500 43 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 52 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 70 500 60 195 243 5 250 169 211 4 225 84 105 2 110 67 84 2 90 106 133 3 150 80 500 69 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 20 500 13 56 69 2 70 48 60 2 70 24 30 1 35 19 24 1 25 30 38 1 40 30 500 19 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 40 500 26 111 139 3 150 96 120 3 125 48 60 2 70 39 48 1 50 61 76 2 80 50 500 32 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 39 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 75 500 48 208 261 5 300 181 226 4 250 90 113 2 125 72 90 2 100 114 143 3 150 90 500 58 250 313 6 350 217 271 5 300 108 135 3 150 87 108 2 110 137 171 3 175 100 500 65 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 20 500 10 56 69 2 70 48 60 2 70 24 30 1 35 19 24 1 25 30 38 1 40 30 500 15 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 40 500 21 111 139 3 150 96 120 3 125 48 60 2 70 39 48 1 50 61 76 2 80 50 500 26 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 31 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 80 500 41 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 52 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 115 500 ......... 138 173 3 175 111 138 3 150 175 219 4 225 130 500 ......... 157 196 4 200 125 157 3 175 198 247 5 250 30 500 14 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 60 45 500 21 125 156 3 175 108 135 3 150 54 68 2 70 43 54 1 60 68 86 2 90 60 500 28 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 80 500 38 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 47 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 115 500 54 ........ 138 173 3 175 111 138 3 150 175 219 4 225 130 500 61 ........ 157 196 4 200 125 157 3 175 198 247 5 250 150 500 70 ........ 181 226 4 250 145 181 4 200 228 -- 5 300 LEGEND ARI AWG 380/3/50 Total Air Conditioning and Refrigeration American Wire Gage Institute FLA kW -- Full Load Amps -- Kilowatts MCA MOCP -- Minimum -- Maximum *Standard control steps are listed under the Control Step heading. "Free" additional steps of control are optionally I-MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC (National Electrical Code). NOTES: 1 Subcircuits are internal heater circuits of 48 amps or less. 2. Electric heat performance is not within the scope of ARI standard 430 certification. 3. To avoid damage due to overheating, minimum face velocity cannot fall below 350 fpm. 4. Heaters up to (and including) 60 kW have 3 control steps; beyond 60 kW, 6 steps are standard. Circuit Amps Overcurrent available Protection when the number of subcircuits exceeds the standard number of control steps. Table 27 -- Electric Heater Data (cont) 39M UNIT SIZE HEATER AREA (sq ft) NO. OF CONTROL STEPS* HEATER COIL kW NOMINAL COIL FACE VELOCITY TEMP RISE (F) Total FLA 208/3/60 VOLTS MCAt No. Sub Ckt (fpm) 3 17 16.6 6 21 21 6 Go =_ 25 23.3 30 2g.3 MOCP Total FLA 240/3/60 VOLTS MCAt No. Sub Ckt MOCP 480/3/60 VOLTS Total FLA MCAt No. Sub Ckt 600/3/60 MOCP Total FLA MCAt VOLTS No. Sub Ckt --- Total FLA MCAt No. Sub Ckt MOCP 500 12 83 104 2 110 72 90 2 100 36 45 1 50 29 36 1 40 46 57 1 45 500 17 125 156 3 175 108 135 3 150 54 68 2 70 43 54 1 60 68 86 2 g0 60 500 23 167 208 4 225 145 181 4 200 72 g0 2 100 58 72 2 80 gl 114 2 125 75 500 29 208 261 5 300 181 226 4 250 90 113 2 125 72 90 2 100 114 143 3 150 80 500 31 222 278 5 300 103 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 38 278 347 6 350 241 301 6 350 120 151 3 175 g6 120 3 125 152 190 4 200 125 500 48 ........ 151 188 4 200 120 151 3 175 100 238 4 250 150 500 58 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 67 ........ 211 263 5 300 16g 211 4 225 266 333 6 350 40 500 12 111 13g 3 150 g6 120 3 125 48 60 2 70 3g 48 1 50 61 76 2 80 50 500 15 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 18 167 208 4 225 145 181 4 200 72 g0 2 100 58 72 2 80 gl 114 2 125 80 500 24 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 30 278 347 6 350 241 301 6 350 120 151 3 175 g6 120 3 125 152 190 4 200 125 500 38 ........ 151 188 4 200 120 151 3 175 100 238 4 250 150 500 46 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 53 ........ 211 263 5 300 169 211 4 225 266 333 6 350 200 500 61 ........ 241 301 6 350 193 241 5 250 304 380 7 400 220 500 67 ........ 265 331 6 350 212 265 5 300 335 418 7 450 40 500 11 111 13g 3 150 g6 120 3 125 48 60 2 70 3g 48 1 50 61 76 2 80 50 500 14 13g 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 g5 2 100 60 500 16 167 208 4 225 145 181 4 200 72 g0 2 100 58 72 2 80 gl 114 2 125 80 500 22 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 27 278 347 6 350 241 301 6 350 120 151 3 175 g6 120 3 125 152 190 4 200 125 500 34 ........ 151 188 4 200 120 151 3 175 190 238 4 250 150 500 41 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 48 ........ 211 263 5 300 169 211 4 225 266 333 6 350 200 500 55 ........ 241 301 6 350 193 241 5 250 304 380 7 400 225 500 62 ........ 271 339 6 350 217 271 5 300 .... 250 500 69 301 376 7 400 241 301 6 350 .... 40 500 g 111 13g 3 150 g6 120 3 125 48 60 2 70 3g 48 1 50 61 76 2 80 50 500 11 139 174 3 175 120 151 3 175 60 75 2 80 48 60 2 70 76 95 2 100 60 500 13 167 208 4 225 145 181 4 200 72 g0 2 100 58 72 2 80 gl 114 2 125 80 500 17 222 278 5 300 193 241 5 250 g6 120 3 125 77 g6 2 100 122 152 3 175 100 500 22 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 125 500 27 347 434 8 450 301 376 7 400 151 188 4 200 120 151 3 175 100 238 4 250 150 500 33 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 38 ........ 211 263 5 300 169 211 4 225 266 333 6 350 200 500 44 ........ 241 301 6 350 193 241 5 250 304 380 7 400 225 500 4g ........ 271 33g 6 350 217 271 5 300 .... 250 500 54 ........ 301 376 7 400 241 301 6 350 .... 275 500 60 ........ 331 414 7 450 265 331 6 350 .... ........ Air Conditioning and Refrigeration American Wire Gage Institute FLA kW --- Full Load Amps Kilowatts MCA MOCP --- Minimum Maximum *Standard control steps are listed under the Control Step heading. "Free" additional steps of control are optionally 1-MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC (National Electrical Code). NOTES: 1. 2. 3. 4. MOCP VOLTS 30 LEGEND ARI AWG 380/3/50 Subcircuits are internal heater circuits of 48 amps or less. Electric heat performance is not within the scope of ARI standard 430 certification. To avoid damage due to overheating, minimum face velocity cannot fall below 350 fpm. Heaters up to (and including) 60 kW have 3 control steps; beyond 60 kW, 6 steps are standard. Circuit Amps Overcurrent available Protection when the number of subcircuits exceeds the standard number of control steps. 60 Table 27 -- Electric Heater Data (cont) 39M UNIT SIZE 36 40 HEATER AREA (sq _) 38 41.g NO. OF CONTROL STEPS* 6 6 oo 50 61 52.6 63.1 6 6 HEATER COIL kW NOMINAL COIL FACE VELOCITY (fpm) 208/3/60 VOLTS 240/3/60 VOLTS 480/3/60 VOLTS 600/3/60 VOLTS RISE (F) Total FLA MCAt No. Sub MOCP Total FLA MCAt Ckt No. Sub MOCP Total FLA MCAt Ckt No. Sub MOCP Total FLA MCAt Ckt No. Sub VOLTS MCAt No. Sub MOCP Ckt 60 500 10 167 208 4 225 145 181 4 200 72 g0 2 100 58 72 2 80 gl 114 2 80 500 13 222 278 5 300 103 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 17 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 125 500 21 ........ 151 188 4 200 120 151 3 175 190 238 4 250 150 500 25 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 200 500 500 2g 34 ........ ........ 211 241 263 301 5 6 300 350 16g 193 211 241 4 5 225 250 266 304 333 380 6 7 350 400 225 500 38 ........ 271 33g 6 350 217 271 5 300 342 428 8 450 250 500 42 ........ 301 376 7 400 241 301 6 350 380 475 8 500 300 500 50 ........ 361 452 8 500 289 361 7 400 .... 350 500 59 421 527 9 600 337 421 8 450 .... 60 500 9 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 80 500 12 222 278 5 300 193 241 5 250 96 120 3 125 77 96 2 100 122 152 3 175 100 500 15 278 347 6 350 241 301 6 350 120 151 3 175 g6 120 3 125 152 190 4 200 125 500 lg ........ 151 188 4 200 120 151 3 175 190 238 4 250 150 500 23 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 27 ........ 211 263 5 300 16g 211 4 225 266 333 6 350 200 500 30 ........ 241 301 6 350 103 241 5 250 304 380 7 400 250 500 38 ........ 301 376 7 400 241 301 6 350 380 475 8 500 300 500 46 ........ 361 452 8 500 289 361 7 400 .... 350 500 53 ........ 421 527 9 600 337 421 8 450 .... 400 500 61 ........ 482 602 11 700 385 482 g 500 .... 60 500 7 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 80 500 10 222 278 5 300 193 241 5 250 g6 120 3 125 77 g6 2 100 122 152 3 175 100 500 12 278 347 6 350 241 301 6 350 120 151 3 175 96 120 3 125 152 190 4 200 125 500 15 ........ 151 188 4 200 120 151 3 175 100 238 4 250 150 500 18 ........ 181 226 4 250 145 181 4 200 228 285 5 300 175 500 21 ........ 211 263 5 300 169 211 4 225 266 333 6 350 200 500 24 ........ 241 301 6 350 193 241 5 250 304 380 7 400 250 500 30 ........ 301 376 7 400 241 301 6 350 380 475 8 500 300 500 36 ........ 361 452 8 500 289 361 7 400 .... 350 500 42 ........ 421 527 g 600 337 421 8 450 .... 400 500 49 ........ 482 602 11 700 385 482 9 500 .... 450 500 55 ............ 434 542 10 600 .... 500 500 61 ............ 482 602 11 700 .... 60 500 6 167 208 4 225 145 181 4 200 72 90 2 100 58 72 2 80 91 114 2 125 80 500 8 222 278 5 300 193 241 5 250 g6 120 3 125 77 g6 2 100 122 152 3 175 100 500 10 278 347 6 350 241 301 6 350 120 151 3 175 g6 120 3 125 152 190 4 200 125 150 500 500 13 15 ........ ........ 151 181 188 226 4 4 200 250 120 145 151 181 3 4 175 200 100 228 238 285 4 5 250 300 175 500 18 ........ 211 263 5 300 169 211 4 225 266 333 6 350 200 500 20 ........ 241 301 6 350 103 241 5 250 304 380 7 400 250 500 25 ........ 301 376 7 400 241 301 6 350 380 475 8 500 300 500 30 ........ 361 452 8 500 289 361 7 400 .... 350 500 35 ........ 421 527 g 600 337 421 8 450 .... 400 500 40 ........ 482 602 11 700 385 482 g 500 .... 450 500 500 500 46 51 ............ ............ 434 482 542 602 10 11 600 700 .... .... ........ -- Air Conditioning and Refrigeration -- American Wire Gage Institute FLA kW --- Full Load Amps Kilowatts MCA MOCP --- Minimum Maximum *Standard control steps are listed under the Control Step heading. "Free" additional steps of control are optionally 1-MCA = 1.25 x FLA; for proper wire sizing_ refer to Table 310-16 of the NEC (National Electrical Code). NOTES: 1. 2. 3. 4. MOCP Total FLA C_ LEGEND ARI AWG 380/3/50 TEMP Subcircuits are internal heater circuits of 48 amps or less. Electric heat performance is not within the scope of ARI standard 430 certification. To avoid damage due to overheating_ minimum face velocity cannot fall below 350 fpm. Heaters up to (and including) 60 kW have 3 control steps; beyond 60 kW, 6 steps are standard. Circuit Amps Overcurrent available Protection when the number of subcircuits exceeds the standard number of control steps. 125 FAN STARTER _ CLASS 1 TRANSFORMER TRANSFORMER FUSING _wooooooooo_ 24 V AUTOMATIC CUTOUT (S) AIRFLOW SWITCH FIELD WIRING (BY CUSTOMER) FIELD-SUPPLIED I &INSTALLED STEP CONTROLLERS STAGE STAGES 2-5 (NOT SHOWN) ARE THE SAME AS STAGES 1 & 6. _.._ THREE-PHASE .............................................. c_.o i FUSING i J AS REQUIRED 1 STAG E 6 A _ PER CIRCUIT CONTROLLING BY N E C CONTACTOR . MANUAL (S) CUTOUT(S) DELTA OR WYE CONNECTED NOTE: All wiring must be copper and must conform to the NEC (National Electrical Code), Fig. 82 -- Electrical Heater Wiring Schematic Energy Recovery Ventilation (Typical) (ERV) Sections The upper sections MUST be rigged and lifted one at a time or injury or unit damage may occm: The assembled sections will result in a unit center of gravity (CG) higher than the horizontal centerline. Exercise proper care when rigging, lifting and transpolling. Units with a high CG will tip over more easily during installation than those with a lower CG Rigging and lifting upper sections: 1. Use the 4 lifting/holddown brackets (Fig. 84) holding the row of sections to the skid, and/or a second set of brackets shipped loose with the unit. For 12-in. airway length sections, use the bracket shown in Fig. 85. RECEIVING AND INSPECTION -- Inspect the section for freight damage upon receipt. Inspect the cassette that is mounted inside the section. The cassette consists of a flmne, wheel assembly and segments. Verify that the wheel turns freely by hand (clockwise when viewed from the pulley side). Report any damage immediately to the freight company. RIGGING AND STACKING-The ERV section sizes 03-17 me shipped lully assembled. These units can be stacked and unstacked, as required, during installation by following the same procedure as for lmger units described below. 2. Separate each section one at a time (T-latches) and install brackets at each corner using the screws provided. Be carelul not to strip out the holes in the section frame. Lift and set the section on top of the lower sections. For sizes 21-30, upper sections should be stacked onto the lower sections starting with the upper wheel section, and then moving outward to each end of the unit. 3. NOTE: If an ERV section (size 08-17) does not fit through a doorway, it may be taken apart by removing the top of the section frmne. This will expose the ERV wheel; take plecautions not to &_mage the wheel while moving the section. Once the section is in place, put the top of the section flmne back on. Once the upper wheel section is in place and fastened down to the lower section, subsequent sections should be placed close to the side of the upper wheel section. Lifting brackets may make it difl]cult to butt sections tight together at this point. With rigging still in place, but strap/chain tension relieved, remove the 2 lifting brackets interfering with the inst_dled section, then place tension back onto the rigging to assist in sliding sections togethel: Fasten upper sections together tightly first, then tighten screws downward into the lower section frame. The ERV section sizes 21-30 are shipped unstacked due to shipping height limitations. The lower sections me all assembled on baserails and all fastened together on a single skid. The upper sections me on a separate skid and fastened together (all fasteners are T-kitches). Rigging and setting the lower sections is the stone as for a standmd 39M indoor base unit. Refer to Fig. 83. Repeat this process for the remaining 84 ERV sections. Table 28 -- Electrical Requirements for Energy Wheel Motor RIGGING INFORMATION CAUTION: Stacked Rig and lift carefully For units Units sides 8 feet units have to prevent or longer, a high CG (center of gravity). unit from tipping over. handle by crane only. under 8 feet long may be forked frorn and ends in fork pockets (if provided) in b ..... when il ....... d ..... den available skids _ _- _ MOTR VOLTS-PHASE-Hz _ _. _ _ ._ _ | _ 115-1-50/60 3gM UNIT SIZES 03, 06 MOTOR HP 80 w 08, 10 1/6 1.03-1.04/0.52 200-230/460-3-60 12, 14, 17, 21 1/6 0.60-0.75/0.38 25, 30 1/4 2.3-2.5/1.2 06, 10 1/6 1.04/0.52 200/400-3-50 12, 14, 17, 21 1/6 0.80/0.40 25, 30 1/3 3.4/1.8 1/6 0.3 575-3-60 08, 10, 12,14 17, 21 25, 30 1/3 1.4 _" _ p,aceb°forer+ngun.' '= ,, / vertical Lifting from See lift at all lifting angles greater points, than 15 vertical will damage view at right. o& _/.._ _b unit. than the minimum Some units channels number Of _ _ +gun,wgh ,-....... herof,ft+g cables shown in table. may have more lifting L _. _ _ VERTICALU_ _ _4_ _'S_" START-UP _/_ _,/ Checklist- Remove all construction debris from unit interior Verify that all &ains are free of debris. Prime all condensate traps. FILTERS -- Inst;dl unit filters in all filter sections. MAXIMUM length cables for each side UptoSfL cables shown in the table at right. @ 3 Unit Minimum # of lifting 8to 12ft. 3 12+ ft. 4 AIRFOIL AND FORWARD-CURVED FANS 1. Release the holddown that fastens the fan sled to the section base on isolated units. Fig. 83 -- Rigging Information 2. Fig. 84- Lifting/Holddown MOTOR AMPS (a) 0.7 Check lubrication of fan, motor bearings, and linkages. a. Note that bearings are shipped completely full of grease for corrosion protection and may run warm temponuily on start-up until excess grease has discharged. b. Hand operate all linkages, such as damper and guide vanes, to check for freedom of movement. 3. Check tightness of bearing setscrews or locking coll_us (Fig. 86). Also, check tightness of setscrews on fan wheels and sheaves. 4. Check tightness Fig. 86. 5. Recheck sheave _dignment and belt tension. (Refer to Fig. 32 and 33.) Hand turn fan to make certain fan wheel does not rub in housing. Brackets 6. 7. of fan-shaft bearing Check fan speed with a strobe-type following formula: mounting. tachometer See or use the Obtain the motor rpm from the fan motor nameplate and read sheave pitch diameters marked on the fan and motor pulleys, or approximate the pitch diameters by using the pulley ODs. Then: Motor Rpm x Motor Sheave Pitch Diameter (in.) Fan RPM = Fan Sheave Pitch Diameter Example: Fig. 85- 12-in. Airway Bracket ERV WHEEL MOTOR WIRING -- All ERV wheel motors have stripped back power leads. For units with 3-phase wheel motors, install and route the proper wire type and size directly to the motor junction box provided. Approximate Nameplate Motor RPM = 1760 1760 Motor Sheave Pitch Diameter = 8.9 9.0 (OD) Fan Diameter Sheave Pitch = 12.4 12.5 (OD) = = 1760 x 8.9 12.4 1263 RPM 1760 x 9.0 12.5 = 1267 RPM Fan RPM For units with single-phase wheel motors connections must be made in a separate, field-installed junction box. This junction box must be installed in the ERV section close to the motor. Actual (in.) Refer to Tables 2A-2D for maximum allowable fan speeds for fan wheels. Excessive fan speed may result in condensate carryover from cooling coil or fan motor overload and wheel failure. Refer to Table 28 for motor electrical &tta. 85 SETSCREWS CAPSCREW SQUEEZE-TYPE ROLLER -- EXTENDED TORQUE TABLE RACE, ONE OR BOTH SIDES CAPSCREW AND SETSCREW SIZE (No./in.) 10 1/4 DRIVE PULLEY NOMINAL SCREW SIZE No. 6 No. 8 No. 10 1/4 5/16 3/6 LOCKING COLLAR TORQUE (in.-Ib) 9 16 30 70 140 216 HEX HEAD ACROSS FLATS (in.) SQUARE HD ACROSS FLATS (in.) TORQUE 25 60 10 17 25 40 90 125 3/32 1/8 5/16 5/32 3/6 3/16 7/16 7/32 1/2 % 3/4 1/4 5/16 1/2 3/8 BEARING HOLDDOWN BOLT SIZE (in.) 3/8 - 16 1/2 - 13 6/8-11 3/4-10 in.-Ib in.-Ib ft-lb ft-lb ft-lb ft-lb ft-lb ftqb BOLT TORQUE TORQUE (ft-lb) 3O 63 100 165 Fig. 86 -- Fan, Shaft and Bearing Details 8. Check direction of rotation (see Fig. 75). Anow on drive side of fan housing indicates correct direction of rotation. Drive ratios of l:l may cause excessive possible. 9. Check vibration. the following: a. b. c. d. e. f. g. h. i. j. k. If excessive vibration. vibration occurs, Installation, Operation, and Maintenance instructions shipped with the plenum fan section for ihrther details. HUMIDIFIER INSTALLATION CHECKLIST -- Ensure: 1. Humidifier is properly assembled with all discharge slots facing the proper direction. (Multipipe systems have the vertical slots in line with the manifolds, 90 degrees to the air flow.) 2. Humidifier headers are secured and level. Avoid if check for Variable sheave (if air balance of system has been accomplished; replace sheave with fixed sheave for continuous application). Drive mis_dignment. Mismatched, worn, or loose belts. Wheel or sheaves loose on shaft. Loose bearings. Loose mounting bolts. Motor out of b_flance. Sheaves eccentric orout ofb_flance. Vibration isolatol_ improperly adjusted. Out-of-bahmce or corroded wheel (rebalance or replace if necesstu-y). Accumulation of materi_fl on wheel (remove excess material). 3. Humidifier 4. Vtflve and trap assembly is properly assembled nected to the humidifier header. 5. P-trap is installed on discharge 6. upright discharge manifolds tue plumb. and con- of each headel: Stemn feed line is properly run, sloped and connected the valve and trap assembly inlet. 7. Controls are properly wired. HUMIDIFIER START-UP to 1. Slowly open the steam isolation valve from the steam supply line. You should be able to hear steam running through the valve. Wkdt a few minutes for the steam to heat up the entire line to the humidifier and for all condensate to clear through the trap. 2. PLENUM FANS -- Start-up procedures for plenum fans tue similtu to those for airfoil or forward-curved fans described in the preceding section. Also refer to the fan manufacturer's 86 Verify that the stemn trap on the valve/trap assembly of the humidifier is working properly -- condensate discharge line should be hot. 3. Withairflowingin the 4. 4. The valve on the humidifier should begin to open and steam should enter the humidifier manifolds. 5. 6. 7. Stmt up base unit fans. Check airflow and switches. Refer to base unit instructions as required. Set thermostats so that heater contactors will operate. Shut off unit power Reinstall fuses. 5. [nitially most of the steam will condense as it heats the manifolds. Ensure that the P-traps on the manifolds are clem and running to diain without leaking steam. 8. Turn on unit power and heater powel: duct or air handler, create a humidification demand by increasing the humidity control set point until it exceeds the actual humidity reading. Energy Recovery Wheel NOTE: On first stall-up, some steam may leak flom the P-tlaps on the manifolds if they have not been primed (filled with water). Keep hands away from rotating wheel. Contact ing wheel can cause physic_d injury. 6. Stemn should begin exiting the humidifier manifolds. 7. Return the humidity control set point to the desired level. CO[LS 1. By hand, turn the wheel clockwise (as viewed from the pulley side), to veril_ that the wheel turns freely through a lhll 360-degree rotation. Water Coil -- Typical coil vents, drains, and lifting points are shown in Fig. 59. Open the vent plug, partially turn on the water supply until air is exhausted, and replace the vent plug. Fully turn on the water supply. Direct Expansion Coil -- Charge with refrigerant. Condensing Unit instructions. Refrigerant operating shown in Table 11, page 26. Steam Coil Before applying power to the drive motol; confirm that the wheel segments are fully engaged in the wheel frame and that the segment rettdnel_ me completely fastened. (,See Fig. 87). 3. With hands and objects away from moving parts, activate the unit and confirm wheel rotation. The wheel rotates clockwise (as viewed from the pulley side). 4. If the wheel has difl]culty starting, turn the power off and inspect for excessive interference between the wheel surface and each of the four (4) diameter seals. To correct, loosen the diameter se:d adjusting screws and back adjustable diameter seals away from the surface of the wheel, apply power to conthm that file wheel is free to rotate, then re-adjust and tighten the hub and diameter seals according to the instructions in the Service section. 5. Stmt and stop the wheel sevend times to confirm seal adjustment and to confirm that the belt is tracking properly on the wheel rim (approximately I/4-in. from outer edge of rim). ZEROING THE MAGNEHELIC GAGE BEFORE STARTUP -- While power is off, set the indicating pointer exactly on the zero mark using the external zero adjust sclew on the cover at the bottom. Note that the zero check or adjustment can only be made while the high and low plessure taps are both open to atmosphere. On start-up, the steam or hot water supply will be lully expanded prior to start of airflow. Allow time for 'all air to be purged from the system and for the heating surface to lully wm'm up in order to avoid heating lag. ROTATE AWAY FROM WHEEL RIM SEGMENT RETAINER. Preheating a cold system will avoid excessive steam condensate loading at the start of operation of a steam heating system. It also protects steam and hot water units against freezing up when subject to sub-freezing air temperatures. After preheating, fully open the dampers for full-face exposure (bypass closed). Start airflow. Set thermostat for desired air temperature. ELECTRIC HEATERS 3. 2. Refer to charge is 1. Generate steam in the stemn main and open the supply (gate) valve to the coil. 2. Thoroughly preheat file coil with steam before starling fans, especi_dly when inlet air temperature is below fleezing. If water hammer occurs, turn off fans until condensate trapped in coils is reduced by heat and steam pressure. 3. Ensure continuous-vent petcock is open; also check operation of gate v_dves, control valve, and check valves. 4. After operating coil for 50 hom_, check strainer and remove any foreign mattel: Check traps and drip lines for conect condensate removal. Where necesstuy, increase the pitch of lines to increase condensate di'ainage. (Recheck operation after 50 hom_ and repeat if necessary.) INTEGRAL FACE AND BYPASS COIL START-UP -- Ensure that the damper operator allows the &tmpers to fully close the face and reverses to fully close the bypass. Set the thermostat so that the face opens and bypass closes when heat is required. 1. Check tightness of _dlelectrical 2. Remove heater circuit fuses. with rotat- CATCH PUSH TOWARD CENTER connections. WHEEL RIM Fig. 87 -- Segment Turn on power to activate transformel: 87 CENTER WHEEL Retainer OF SERVICE CLEANINGPeriodic cleaning of the energy recovery wheel will depend on operating schedule, climate and contaminants in the indoor air exhausted and the outdoor air supplied to the building. Electric shock haz_ud. Disconnect power before entering or servicing. More than one disconnect switch may be required to deenergize the equipment. The wheel is "self-cleaning" with respect to din particles due to its laminar flow characteristics. Smaller particles pass through; larger particles land on the surface and are blown clear as the flow direction is reversed. Any material that builds up on the face of the wheel can be removed with a brash or vacuum. All sizes can be vacuumed. General I. Review Safety Considerations at beginning of these instructions. Good safety habits are important tools when performing service procedures. 2. To make speed measurements, use a strobe-style tachometer or calculate per Step 7 of Start-Up, Checklist for Airfoil and Forward-Curved Fans. Cleaning the removable segments (size 08-30) or the entire wheel (size 03-06) will remove oil-based aerosols that have condensed on energy transfer surfaces. To clean removable segments (size 08-30): 1. Access the wheel from the exhaust fan side. This may be easiest fiom the adjoining section, depending on the type of section installed. If it is necessary to access from the side of the wheel section, remove side baffle as shown in Fig. 88. This requires removing the screws (1) and (2) shown. 2. Unlock two segment retainers, one on each side of the selected segment opening. Electric Heaters -- At least once a year at start of operating season or whenever unit is serviced, check field and factory-made electric_fl connections for tightness. Also periodically clean filteLs, fan, airways, ductwoN, grilles, and registers as required. Differential air pressure switch is factory set to open at 0.07 in. wg, close at 0.05 in. wg and requires no adjustment. Refer to the Troubleshooting section for more information. Heater electrical data is shown in Table 27. 3. Use the tip of a flat screw diiver to pop the segment out of the wheel. Repeat for each segment. 4. Brush foreign material from the face of the wheel. Wash the segments (or sm_fll wheels) in a 5% solution of nonacid based coil cleaner (such as Acti-Klean) or an alkaline detergent and warm watel: Soak the segments in the solution until grease and tar deposits are loosened. (NOTE: some staining of the desiccant may remain and is not htumful to performance.) For better cletming action, rapidly run a finger across the segment's surface to separate polymer strips. Rinse dirty solution from segments and remove excess water before reinstalling the segments in the wheel. Fan Motor Replacement I. Shut offlnotor 2. Disconnect powel: 5. 3. Ix)osen motor brace-to-mounting-rail attaching bolts. Ix)osen belt tensioning bolts to adjust the motor position so V-belts can be removed without stretching over grooves. 6. 4. 5. Mark belt as to position. Remove and set aside belts. Remove motor to motor bracket holddown bolts. 7. 6. 7. Remove motor pulley and set aside. Remove motol: and tag power wires at motor termimfls. Installation To clean wheels (size 03-06) use the procedure Fig. 89: NOTE: It may be necessary to remove the end panel to remove larger motors for some unit sizes. 8. Install new motol: Reassemble by reversing Steps 3-7. Be sure to reinstall multiple belts in their origimfl positions. Use a complete new set if required. Do not stretch belts over sheaves. Review the sections on motor and sheave installation, sheave alignment, and belt tensioning on pages 50 and 51. 9. Replace the segments using the Segment Replacement procedure on page 90. and refer to 1. Remove the ERV section side access panel. 2. Remove wheel center partition holddown 3. 4. Lift and Remove wheel center ptutition (2). Remove the upper (3) and lower (4) wheel retainer angles, being carelhl wheel does not tip and ftfll out. Slide wheel cassette out of frame (toward main AHU), and out the side of the unit (5). 5. Reconnect motor leads, remove tags, and restore powec Check fan for proper rotation as described in Start-Up, Checklist. bracket (1). 6. Follow steps 2 through 4 of the cleaning procedure movable segments. 7. Reinstall the wheel into the section by reversing Steps 1-5. Energy Recovery Ventilation -- Routine m_dntenance of the Energy Recovery Cassettes includes inspection and cleaning. On occasion, a p_u't may need to be completely replaced. IMPORTANT: This unit contains an Energy Recovery Wheel heat transfer device. Proper service and maintenance must be conducted as outlined below, or loss of heat transfer and overall system performance will occur, 1. Remove and clean or replace filters in adjoining section to the ERV wheel every 6 months or sooner, as required. 2. and Remove and wash ERV wheel (or individual segments, if so equipped) every 6 months, or every 3 months max. for smoky or polluted environments. See instructions for removal and cleaning details. Fig. 88 -- Remove Side Baffles 88 for re- 2. 3. Rotate the wheel clockwise until two opposing spokes am hidden behind the beating support beam. Using a folded piece of paper as a feeler g_mge, position file paper between the wheel surface find the diameter seals. 4. Adjust the seals towards file wheel surface until a slight fiiction on the feeler gauge (paper) is detected when the gauge is moved along the length of the spoke. 5. Retighten the adjusting with the feeler gauge. screws and recheck clem'ance Fig. 89 -- Remove Wheel for Cleaning (Sizes 03-06 Only) CASSETTE REPLACEMENT [] 1. Inspect the replacement cassette for fieight damage upon receipt. Inspect the cassette fi'ame, wheel assembly find segments fGr damage and verify that the wheel turns fieely by hand (clockwise when viewed from pulley side). Report any &image immediately to the freight company. 2. Handle ERV cassettes with care. Lift by file beming support beam. Holes are provided on both sides of the befuing support beams to facilitate rigging (Fig. 90). 3. Remove the ERV section side access panel. 4. Refer to Fig. 89. Remove down bracket (1). 5. Lift and Remove wheel center pmtition (2). 6. Remove the upper (3) and lower (4) wheel retfdner angles, being carelhl wheel does not tip find fall out. 7. Slide wheel cassette out of frame (toward and out side of unit (5). 8. The new ERV section may be mounted in any orientation. HoweveL make certain that the ,frame remains ,flat and the bearing beams am not rocked as showll in Fig. 91. TG ensure that the bemns are not racked, check that the distance between the wheel rim find bearing beam is the same at each end of the bearing beam, to within 1/4 of an inch (dimension A and B in Fig. 91 ). Beming beam racking of as little as .040 inches (Dim C in Fig. 91 ) will cause the wheel to tilt 3/1_ in. fit the rim. Adjusting the diameter seffls (Fig. 92) will compensate for up to 1/4 in. of racking. 9. wheel center / HORIZONTAL BEARING BEAM (2) Fig. 90 -partition -- Lifting Hole VERTICAL BEARING BEAM (2) Locations hold_ FRAME \ A _ BEARING BEAM _. "_, SHOWN RACKED / , 1 I i main AHU), ,f--WHEEL !!i, f / BEAMS (2) I I, , , i L i FLAT SURFACE "'_ c BI.-Fig. 91 -- Avoid Racking of Frame NOTE: If racking is greater than 1/4 in., it must be corrected to ensure that the drive belt will not disengage from the wheel. 10. Wheel sections installed fit angles greater than 30 degrees from vertical will require seal adjustment (Fig. 92). Adjust the diameter seals to avoid excessive wheel diag. A final check of seal adjustment is recommended for all designs. ADJUSTING AIR SEALS -- Four adjustable diameter seals are provided on each cassette to minimize air transfer between the counterflowing airstreams. TG adjust diameter ADJUSTING SCREWS FEELER GAUGE Fig. 92 -- Diameter Seal Adjustment sefds: 1. Loosen the diameter sefd adjusting screws find back seals away fi_m wheel surface (Fig. 92). 89 SEGMENT INSTALLATION AND REPLACEMENT -Wheel segments are secured to the wheel franle by a segment retainer, which pivots on the wheel rim and is held in pkice by a segment retaining catch (Fig. 93). To inst_dl wheel segments to Fig. 93. 5. Form a small loop of belt and pass it through the hole in the bearing support beam. Grasp the belt at the wheel hub and pull file entire belt down. Loop the trailing end of the belt over the shaft (Fig. 95 shows the solid belt partially through the opening). 6. Reinstall the bearing onto the wheel shaft, being careful to engage the two locating pins into file holes in the bearing support beam. Secure the bearing with the two self locking nuts. 7. Install the belts around the wheel and pulley according the instructions provided with the belt. 8. Reinst_dl the diameter seals and tighten the retaining screws (see page 89 for seal adjustment). Rotate the wheel clockwise to determine that it rotates freely with slight drag on the seals. follow the steps below and refer 1. Unlock two segment retainels, selected segment opening. one on each side of the 2. With the embedded stiffener facing the motor side, insert the nose of the segment between the hub pkites. 3. Holding segment by the two outer corners, press the segment towards file center of the wheel and inwards against the spoke flanges. If hand pressure does not fully seat the segment, insert the flat tip of a screw &iver between the wheel rim and the outer corners of the segment and apply downwmd force while guiding the segment into place. 4. Close and latch each segment retainer under the segment retaining catch. 5. Slowly rotate the wheel 180 degrees. Install the second segment opposite the first for counterbalance. Rotate the two inst_dled segments 90 degrees to balance file wheel while the third segment is installed. Rotate the wheel 180 degrees again to inst_fll the fourth segment opposite the third. Repeat this sequence with the lemaining four segments. WHEEL DRIVE MOTOR AND PULLEY REPLACEMENT 1. Disconnect power to the wheel drive motoc 2. Remove the belt from the pulley and position r;u'ily around the wheel rim. it tempo- 3. Ix_osen the set screw in the wheel drive pulley using an Allen wrench and remove file pulley from the motor drive shaft. 4. While supporting the drive motor's weight loosen and remove the four mounting bolts. 5. Install the replacement supplied. Fig. 93 -- Segment Installation lNSULATION 6. 7. 8. motor using in one hand, the hmdwme ![ Install the pulley to the dimension shown in Fig. 94 and secure the set screw to the drive shaft. Stretch the belt over the pulley and engage groove. Follow the start-up procedure on page 85. SOLID BELT REPLACEMENT 3. DIM A 25-52 1/4" 58-68 7/16" it in the A --I1_ (Fig. 95) Fig. 94 -- Pulley Location LOCKING _- COLLAR SEARING Using a hex wrench, loosen file set screw in the bearing locking collm: Using a light hammer and &ift (in drift pin hole), tap the collar in the direction of wheel rotation to unlock the collm. Remove the collm: LOCKING NUTS (2) SEARING BEAM SUPPORT TAPER-LOCK Using a socket wrench with extension, remove the two nuts that secure file bearing housing to the bearing support beam. Slide the bearing from file shaft. SET DRITH HOLE NOTE: Slight hand pressure against wheel rim will lift the wheel's weight from the inner race of the bearing to assist bearing removal and installation. If not removable by hand, use a bearing pullel: 4. WHEEL DRIVE MOTOR pULEyj_ ''v 1. Obtain access to the pulley side beming access plate. Bearing access plates m'e not provided on 25 to 36-in. cassettes. Remove the two bearing access pkite retaining screws and the access pkite. 2. WHEEL MODEL NO. kit PULL Using a wrench, remove the diameter seM retaining screws (25 to 68-in. cassettes). Remove diameter seals (25 to 68-in. cassettes) from the beming bemn. PULLEY SIDE Protect hands and belt fiom possible shtup edges of hole in Bearing Support Beam. MOTOR SIDE Fig. 95 -- Solid Belt Replacement 9O to 9. 10. Reinst;dl the bearing locking collm- Rotate the collm by hand in the direction the wheel rotates (see label provided on each cassette for wheel rotation). Dock the collar in position by tapping the drift pin hole with a hammer and drift. Secure in position by tightening the set screw. Reinstall the bearing access covel: 11. Apply power to the wheel motor and ensure wheel rotates freely without interference. LINK BELT REPLACEMENT that the Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Fig. 96 -- Belt Attached to Wheel Rim 1. Confirm the model number on the replacement belt kit matches the model number on the energy recovery cassette label. 2. Remove any remnant of old belt from cassette. 3. At location near pulley, attach the hook end of belt to wheel rim with tape, making sure that nmrow side of "V" belt is positioned against rim and link is covered by the tape (see Fig. 96). 4. Rotate the wheel clockwise while feeding belt onto wheel rim (be caleful not to twist belt) until taped end returns to pulley location. Remove tape from wheel. 5. Link belt ends together with belt wrapped (Fig. 97). 6. Rotate wheel clockwise to position connector mately 180 degrees fi_m pulley location. 7. At pulley location, insert the right angle belt retaining clip ne_u spoke and between segment retainer latch and wheel rim as shown in Fig. 98. mound wheel approxi- Fig. 97- latch, do not insertTo retaining clip on ofother side of retainer spoke. IMPORTANT: avoid release segment 8. 9. 10. SEGMENT RETAINER LATCH Rotate wheel counterclockwise until belt retaining clip is within a few inches of the wheel bearing beam (see Fig. 99). Lit) and remove the belt from the wheel rim between a point opposite the pulley and belt retaining clip and stretch over pulley (see Fig. 100). Rotate wheel clockwise until the belt is fully stretched onto pulley and wheel rim. 11. Remove belt retaining clip rotations while observing enters pulley. Also ensure between outer edge of rim channel where provided. 12. Belts Linked Together BELT RETAINING CLIP and rotate wheel by hand two that belt is not twisted as it that belt is tracking midway and seal plate, or in belt guide Apply power to cassette and observe power. OTHER MAINTENANCE belt tracking under Fig. 98 -- Detail of Belt Retailing Clip and Segment Retained Latch Cleaning Unit Interior/Exterior -- Unit interior/exterior panels should be wiped down using a dmnp soft cloth or sponge with a mixture of waml water and a mild detergent. Avoid using an abrasive cleanel; as &tmage to the paint could occur resulting in rest and con'osion. Chemicals such as paint thinners can dalnage the ptfinted panels and should be avoided. Wheel Drive Motor Bearings gue pro-lubricated and no further lubrication is necessary. The Wheel Drive Pulley is secured to the &ive motor shaft by a combination of either a key or D-slot grad set screw, The set screw is secured with removable locktite to prevent loosening. Annually confirm that the set screw is secure, The Wheel Drive Belt is a umthane stretch belt designed to provide constant tension through the life of the belt. No adjustment is required. Inspect the drive belt annu_flly for proper tracking and tension. A properly tensioned belt will turn the wheel immediately after power is applied with no visible slippage during start-up. Avoid washing unit electrical devices such as motors, starters, electric heater control boxes, damper/valve actuators, sensors, switches, relays, etc. as serious pel_onal injury or &tmage to the device could result. 91 Fig. 99 -- Detail of Belt Retaining 3. Ensure there is sufficient access to the coil. 4. Use a vacuum with a soft tip brush to remove and loose debris from both sides of the coil. 5. Clean the leaving airside of the coil first, then the entering ail_ide, starting fi_)m the top of the coil and working downwmd. Apply a mild non-fomning commercial coil cleaner or detergent using a gmden type sprayel: Rinse coil gently with clean wm'm water, avoiding high-pressure sprays, which can cause dmnage to coil fins. Use a blockoff plate to prevent the water or chemical cleaner from blowing through the coil and into a clean, @ section of the unit. Confirm that the condensate diain line is fiee of debris during and following the coil cleaning process. Excess water from cleaning may result in flooding the unit as well as causing &Lmage to the building if diain is plugged. If coil section does not have a divin pan, it is recommended that the coil be removed prior to cleaning. Repeat steps 1 through 5 as necessary. Allow the coil to dry thoroughly before placing the system back into operation. A clean @ cloth may be used to wipe down the interior panels before placing the unit in operation. 6. 7. Clip Location 8. 9. 10. any dust Straighten any coil fins that may have been bent or damaged during the cleaning process with a fin rake. Replace all panels and parts that may have been removed prior to cleaning and restore electrical power to the unit. Use caution to assure that no contaminated materials contact other meas of the unit or building. Properly dispose of any polluted materi_ds and cleaning fluids. Winter Shutdown -- It is recommended that auxilim'y drain piping be added to coil piping if yearly winterizing of coils is anticipated. This auxiliary piping should be located at the highest and lowest point on the respective header connection for each coil. ANTIFREEZE METHODS OF COIL PROTECTION 1. Close coil water supply and return valves. 2. Drain coil as follows: Fig. 100 -- Belt Removal Method I -- 'Break' flange of coupling at each header location. Sepm'ate flange or coupling connection to facilitate coil di'aining. Method II-- Open both v;dves to auxiliary drain piping. 3. After coil is di'ained, Method I, connect line with a service valve and union from upper nozzle to an antifreeze reservoir Connect a self-priming reversible pump between the low header connection and the reservoil: Method fl, make connection to auxilimy di'ain Coil Cleaning --Chilled water, hot water, steam, and direct expansion coils must be cleaned regularly to m;fintain peak performance. Dirty coils can contribute to loss of cooling or heating capacity and efficiency, increased operating costs, and compressor problems on direct expansion systems. Dirt, grease, and other oils can also reduce the wettability of the coil surfaces, which can result in moisture blow-off from cooling coils and resulting water leakage problems. If the grime on the surface of the coils becomes wet, which commonly occurs with cooling coils, microbial growth (mold) can result, causing foul odors trod health related indoor air quality problems. valves. 4. Coils can become dirty over a period of time, especi;dly if air filter maintenance is neglected. Coils should be inspected regularly and cleaned when necessm-y. If coil fins become dirty. pressure clean with hot water and detergent or a commercial coil cleanel: Ensure to rinse coils thoroughly after cleaning with chemical cleaners. 5. 6. 7. 8. Follow all directions provided with the chemical cleaners to avoid personal inju U, inju U to others, and/or coil damage. Chemical coil cleaners may contain corrosive or harmfiJl agents. 9. Fill reservoir with any inhibited antifreeze acceptable to code and undelwriter authority. Open service valve and cimulate solution for 15 minutes; then check its strength. If solution is too weak, add more antifreeze until desired strength is reached, then circulate solution through coil for 15 minutes or until concentration is satisfactory. Remove upper line from reservoir to reversible pump. Drain coil to reservoir and then close service valve. Break union and remove reservoir and its lines. Leave coil flanges or coupling valves open until spring. open and auxiliary AIR-DRYING METHOD OF COIL PROTECTION and coil must be level for this method.) 1. Disconnect all electrical power to the ;fir-handling unit, including any separate power supplies for unit mounted controls (actuatol_, sensors, etc .... ). 2. Wear the appropriate protective clothing (eyewear. gloves, etc....). diain (Unit 1. Close coil water supply and return main valves. 2. Drain coil as described in procedures for Antifreeze Methods of Coil Protection, preceding. 3. Connect air supply or air blower to inlet header connection and close its drain connection. 92 4. Circulate airandcheckforair-dryness byholding mirror in front of open vent in outlet header drain connection. Min_or will fog if water is still present. 5. Allow coil to stand for a few minutes; repeat Step 4 until coil is dry. 3. Coil Removal NOTE: To reinstall coils, refer to Coil Installation section on page 59. a. Remove the top rail by pulling angle. Set top rail aside. out at a 45-degree 4. Remove the fastening screws of the uppermost coil from the upstream side. Note that the fastening screws pass through the vertical angle, baffles, and coil casing. See Fig 101. Removal of the fastening screws may require reaching through an opened &tmper assembly, reaching through a filter track after filters are removed, or removing a coil immediately upstream. 2. Identify the unit service panel latches and disengage them (1/4 turn) with a 5/l_-in. or 8-ram hex wrench. Remove service panel/coil connection panel and the upstremn service panel and set aside in a safe place. 3. a. On horizontal coil sections without another unit section stacked on top, remove the flat corner plug from each end piece of the top rail. b. Extract the Torx T25 screw visible within the exposed cavity. (Do not mix these screws with others; they are specific for this location. Set screws aside for reinstallation of top rail.) Do not handle the coil by the headel.s or connection nipples, as ineparable damage might occur that is NOT covered by warranty. Protect the finned surface from damage during all handling and shipping. out at a 45-degree IMPORTANT: Properly support the coil to assure stability before continuing with this procedure. 5. Slip the foam sealing sleeves off the connection nipples before removing the coil and set the sleeves aside. its 6. The upper coil may now be hoisted out through the top opening, or cguefully slid out either side of the cabinet. Sections where the top frame nfil cannot be removed may require slightly tipping of the coil fiom the vertical position, to cle_u the upper frmne rail and se_d. Remove the fastening screws fiom the upstremn perimeter face of the coil that attach the coil to the coil baffles. This may require reaching through an opened &lmper assembly, reaching through a filter track after filters are removed, or removing a coil immediately upstream. Do not nipples, covered &image Remove the top rail by pulling out at a 45-degree angle. Set top rail aside. On horizontal coil sections without another unit section stacked on top, remove the flat corner plug from each end piece of the top rail. Extract the Torx T25 screw visible within the exposed cavity. (Do not mix these screws with others; they are specific for this location. Set screws aside for reinstallation of top rail.) IMPORTANT: ity before continuing Properly withsupport this procedure. the coil to assure its staND 1. Lock open and tag all power supplies to unit fan motor and electric heaters if present. 4. c. c. NOTE: Refer to Table 13 (DU Coil Weights) in the fi_ont of this manual before attempting to remove a coil from the unit. Remove the top rail by pulling angle. Set top rail aside. Remove service panel/coil connection panel and the upstream service panel and set aside in a safe place. b. REMOVAL OF SINGLE HEIGHT COILS (sizes 0336) -- The coils in horizontal coil sections may be removed from the top of the unit or either end. Once the extern_fl panels are removed from the unit, the horizontal upper coil section frame members are easily removable from the frmnework, to allow hoisting the coil up and out of the unit. c. b. 7. On the upstream side of the stacked coils, remove and set aside the center baffle spanning the two coils (see Fig. 101). 8. For sections that do not have a drain pan (heating only sections), remove the three hat channel spacer supports fastened to the top of the lower coil, and set aside. handle the coil by the headers or connection as irrepgu'able damage might occur that is NOT by wammty. Protect the finned surface fi'om during all handling and shipping. 9. For sections that do have a drain pan, remove the two hat channel spacer supports from the bottom of the coil section and set aside. 10. Remove 5. Slip the foam sealing sleeves off the connection nipples before removing the coil and set the sleeves aside. 6. The coil may now be hoisted out through the top opening or carefully slid out either side of the cabinet. Sections where the top frame rail cannot be removed may require slightly tipping of the coil from the vertical position, to cle_u the upper frame rail and seal. REMOVAL OF STACKED COILS (sizes 40, 50 and 61 )- The coils in horizontal coil sections may be removed from the top of the unit or either end. Once the external panels are removed from the unit, the horizontal upper coil section fiame members are easily removable fiom the fialnework, to allow hoisting the coil up and out of the unit. 1. Lock open, and tag all power supplies to unit fan motor and electric heaters if present. 2. a. Identify the unit service panel latches and disengage them (114turn) with a 5/ls-in. or 8-mm hex wrench. the intemlediate condensate &ain pan. 11. Remove the spacer (hat channel) secured to the top center of the lower coil casing (see Fig. 102) and set aside. 12. Remove the fastening screws of the lowermost coil from the upstream side. Note that the fastening screws pass through the vertical angle, baffles, and coil casing. See Fig. 101. Removal of the fastening screws may require reaching through an opened &tmper assembly, reaching through a filter track after filters are removed, or removing a coil immediately upstream. Do not handle the coil by the headers or connection nipples, as irreparable damage might occur that is NOT covered by warranty. Protect the finned surface from damage during all handling and shipping. 13. Slip the foam sealing sleeves off the connection nipples before removing the coil and set the sleeves aside. 93 BAFFLE _- BAFFLE, HEADER_ COIL FRAMES BAFFLE, HARPIN CHANNEL, HAT_ ANGLE \ BOTH SIDES PAN, CONDENSATE ...... CENTERED WITHIN SECTION IMPORTANT: ADHESIVE GASKET MUST BE APPLIED TO THE FULL LENGTH OF THE BOTTOM BAFFLE MATING FLANGE TO CREATE SEAL BETWEEN THE COIL SIDE CASING AND THE BAFFLE. SEE ILLUSTRATION BELOW, BOTTOM APPLY FLUSH TO THIS EDGE ........ GASKET, ADHESIVE ..... _OM BAFFLE Fig. 101 -- Apply Gasket 14. Tile lower coil may now be hoisted out through the top opening, or carefully slid out either side of the cabinet. 15. Inspect the adhesive backed gasket applied to the lower baftle, spanning the entire unit, on the surface that contacts the coil (see Fig. 101). If &imaged, remove the remainder of the old gasket and replace. Changing As a general rule, a change from counterflow circuiting to parallel flow for sensible heating and cooling applications will result in a 5% drop in net capacity per row of coil. In one and two row heating coils, the actual drop may not be measurable, thus of insignificant consequence. It is important that the airflow direction of the NuFin coil be adhered to when latent cooling is possible. Significant moisture carryover fiom the face of the dehumidifying coil will result if this rule is violated, even at very low face velocities. The stone result is often experienced if after-mmket tin coatings are applied. Coil Hand NOTE: Electric heat coil hand cannot be changed. NOTE: The coil cover panel is not pm't of the coil. Remove cover panel fiom end of unit. New holes must be cut in coil cover panel. Original holes must be plugged and insulated. New side panels may be necessaly when changing coil hand. NUFIN COILS -- The NuFin coil is airflow direction sensitive, especially when used in dehumidifying applications. Hy&onic versions are counterflow circuited for full gravity draining when installed level. Correct installation will result in file typical bottom inlet on leaving air face _md top outlet on entering air face of coil, a self-venting design. This will ensure cold air contact with cold water, and warm air with hot watec Ira NuFin hydionic coil is installed with correct airflow, but opposite piping hand, and counterflow is maintained, steps must be taken to ensure that the coil is continuously vented, and that the water velocity is maintained to prevent the coil from air-binding. Hot or cold areas of file coil face (or otherwise broad temperature differences and stratification) me usually indications that one or more circuits are air-locked internally. This can result in coil freeze-up (a condition NOT covered by warranty). Refiigemnt coils may be rotated for opposite hand applications, maintaining the proper airflow direction. Coil repositioning for opposite hand application will compromise one or more of these characteristics. Howevek there will be those situations where this may prove acceptable. Do not reposition the distributor(s), they will perform equally well in upflow or downflow positions. When soldering expansion valves to up-feed distributors, use the minimum satisfactoly amount of solder to prevent dmnaging the valve or plugging passages. DIRECT EXPANSION COILS -- Rotate the coil in vertical plane and reinstall. Distributor must be on downstremn side of coil. (Refer to Fig. 103). CHILLED WATER AND HOT WATER COILS -- These coils can be rotated. If coil is rotated in vertical plane and reinstalled with countertlow maintained, supply will be at the top of file coil and return will be at the bottom. Ensure coil is continuously vented and water velocity is maintained to prevent air binding. CHANNEL, Fig. 102 -- Secure Spacer 94 Chilled and hot water coils must not be rotated horizont_dly. If coils are rotated horizontally, severe water blow-off will result. STEAM INNER DISTRIBUTING TUBE COILS in horizontal plane and reinstall. See Fig. 103. -- To determine intervals for cleaning coils in contaminated air operations, pressure taps should be inst_flled across the coils and checked periodically. Abnormal air pressme diop will indicate a need for cleaning the coils. Annual maintenance should include: Blow down the dirt leg. 3. Clean and check operation of steam traps. 4. Check operation 5. Check the operation sate flowback. 6. Check operation of thermostatic air vents, if used. A float and thermostatic trap will contain a thermostatic air vent. When the bellows is raptured, it will fail closed. 7. Check operation 8. Check operation of the thermal protection devices used for freeze-up protection. Stemn or condensate should not be allowed to remain in the coil during the off season.This will prevent the formation and build up of acids. returns from the coil. A floodback 4. An immersion themlostat to control outdoor-air dampers and the fan motor is lecommended. This control is activated when the steam supply fails or the condensate temperature drops below a predetermined temperature, usu_dly 120 E 5. On low pressme and vacuum systems, the immersion thermostat may be replaced by a condensate drain with a thermal element. This element opens and drains the coil when the condensate temperature &ops below 165 E Note the thermal condensate drtdn is limited to 5 psig pressure. At greater coil plessures they will not open. In spite of the precautions listed above, a coil may still fieeze up. An ovel.size capacity coil, at partial load, with a modulating stealn control valve will occasionally freeze. Freezing occurs in the 20 F to 35 F range of entering-air temperatures. A better installation would be an undersize coil, with an on/off control wtlve with thermostatic control in the outside all: set at 35 F air temperature, installed downstream of the fil.st coil; or setting the minimum stemn pressure at 5 psig. 1. Clean file line strainers. 2. 9. Do not use overhead can occuE Rotate PIPINGDirect expansion, chilled watel; and hot water coils should always be piped for counterflow. (Fluid should enter the coil at the leaving-air side.) Steam coils must have the condensate connection at bottom of coil. Filters -- See Table 29 for filter data for flat filter section, angle filter section, bag-cmtridge filter section, and filter mixing box section. Filters are field supplied. Air filtel.s should be inspected regularly and changed when dirty. Filter life can vmy greatly from one unit to anothel: depending upon the application and the mnount of contaminants in the leturn and ventilation air entering the air handlel: Each job should be evaluated and maintenance schedules established accordingly. At a minimum, the filters should be changed at the beginning of the cooling and heating seasons. Although not a dilect part of the air handler, outdoor air inlet screens and/or grilles that may be present should _dso be checked regularly and cleaned as necessmy. They can easily become plugged with debris, grease, or other contaminants, depending upon their location.This reduces the availability of ventilation air. which can contribute to indoor air quality problems. All filter sections use adjustable blank-off plates to close off any airway area not filled with filter media. Check blank-off plates to plevent unfiltered air from bypassing the filtel_. Blank-off plates must be on door side of unit. of control v_dves. of check v_flves to prevent 3. conden- of vacuum bre',_ers. There me additional precautions and control strategies, as found in various catalogues and in the ASHRAE Fundamentals Handbook and in the Carrier System Design Guide -- Piping Section, when the entering-;dr temperature to the coil falls below 35 E These conditions occur when IDT coils me used for pre-heat and/or face and bypass applications. Freeze up protection: 1. Use a strainer in the supply line and the dirt leg ahead of the trap. 2. Use a vacuum breaker in the return. BAG-CARTRIDGE FILTERS -- Side loading bag-cartridge filter section can use either bag or rigid filters, 6-in. to 30-in. deep, with 7/s-in. headel: They will not accept headerless rigid filters. Face loading bag-c_utridge filter sections can use either bag or rigid filters and tue loaded fi_)m the front of the section. These sections use Purolator holding frames located at the downstream edge of the filter section for prefilters and bag/ cartridge filters. Cartridge filtel.s without headers can extend upstream of the holding frame by 24 inches. Cartridge and bag filters with 7/u-in. header extend downstream of the filter section with filter length limited only by the length of the plenum following the filter section. Filter elements are retained in fralnes by wire fastener clips. To replace filter elements, remove clips, insert elements with bag or cartridge downstream and reinstall clips. See Fig. 104. See Fig. 105 for typical track for bag-cartridge filter section used on di'aw-thru unit. IN-TRACK BAFFLESFilter sections are shipped with adjustable in-track baftles. When installed properly as shown in Fig. 106, the baffles close off empty space in the track preventing air from bypassing the filtel.s. Remove the baffles to install filter elements, and leplace the adjustable baffles aller the filters tue in place. The adjustable baffles should be spread ftu enough apart to ensure slight compression in the foam gasket when closing the section door. Fig. 103 -- Coil Rotation 95 FLATANDANGLEFILTERS -- Flatfilterandanglefilter sections accommo&tte 2-in.or4-in.thickfiilters. Thesection as shipped accepts 2-in.filters. Remove angle spacer ineach track toprovide thespace required toaccommodate 4-in.filters. HEPAFILTERS-ThePuro-Frame, HEPAholdingflame will accommodate 12-in.deepfiltel_.HEPAfiltersections usedin blow-flnuapplications areloadedfiom thefiont, through the access door or removable panel. The HEPA filters are retained in the fralne with retaining brackets. RTV sealant should be used to seal between the filter frame and the filter media's neoprene gasket to ensure a leaktight installation. Refer to Fig. 107 for details. Downstream edge of fralne to fiame and fi:tme to baffle shall be sealed with RTV sealant. Filter arrangements are shown in Fig. 108-112. 3/4" x 3/4" FOAM GASKET m FILTER \ FILTER RETAINING CLIPS GASKET'_,._ \ ADJUSTABLEIN-TRACK BAFFLE • / [ # 4;, - 4¢ N Fig. 104 -- Puro-Frame Holding Frame and Filter Retaining Clips Fig. 106 -- In-Track Baffle for Flat, Angle and Sideloading Bag/Cartridge Filter Sections Fig. 105 -- Track for Draw-Thru Bag Cartridge Filter Section 12.625" HEPA Height I Width I Height I Width I 24" 124 / "124%" ] 12" ] 24_/8"]12_/_ " FILTER HEPA FRAMER_ FILTER FILTER RETAINING BRACKET QTY. 4 SUPPLIED WITH EACH FRAME INSTALL BY LATCHING OVER FRAME TABS [ \\\ ........... 24" X 24" \ FRAME TABS RETAINING 24.625" AIR FLOW + NOTES: 1. Filter sizes are 5/8-in. smaller than frame sizes. 2. 12-in. x 24-in. frame may be rotated for 24-in. x 12 in. arrangement. 3. Recommended RTV sealant: GE128. i I ;-,' BRACKET 8,0" - Fig. 107- Puro-Frame, HEPA Holding Frame 96 Table 29 -- Filter Data FILTER SIZE I 3gM UNIT SIZE 03 06 Fiat Filter Arrangement(2-in. or 4-in.) 08 10 12 14 17 21 16x20 16x25 3 Face Area (sq ft) ....... -- 3 6 ....... 61 14 .... -- -- -- 6 8 -- 10 -- .... 12 13 15 -- 3.5 6.9 8.3 10.4 13.3 15.0 16.7 20.8 26.7 33.3 41.7 45.1 52.1 70.0 03 06 08 Filter Arrangement(2-in. or4-in.) 10 12 14 17 21 25 30 36 40 50 61 -2 4 -- -4 6 -- 21 14 6 2 ........ 20x24 -- 4 ........ 20x25 .......... 5.6 03 8.9 11.1 06 Filter Mixing 08 10 13.3 12x24 16.7 -- 4 -- 6 16x25 20x20 2 -- 4 .... 18.9 25.0 Box Arrangement(2-in. 12 14 17 -- 16x20 -- 12 2 ........ 20x24 -- 4 ........ 20x25 ...... 11.1 13.3 12 12 16 20 20 18 12 33.3 33.3 44.4 55.6 55.6 73.3 85.6 or4-in.) 21 25 30 36 40 50 61 18 24 12 12 16 -- 24 12 16 16 -- -- -- 33.3 33.3 44.4 55.5 66.7 73.3 97.8 61 ....... ........ 6 5.6 8.9 16.7 18.9 03 06 30 36 40 50 -- 1 -- 1 3 3 3 -- -- -- 4 4 3 7 3 6 6 8 8 8 12 12 18 24 24 32 40 40 54 62 Filter Arrangement 17 21 25 30 36 40 50 61 -- 4 4 3 7 Short Side Load Bag/Cartridge 08 10 12 14 24x24 1 1 2 2 2 2 Face Area (sq ft) 4 6 8 10 14 14 24.0 Filter Arrangement 17 21 25 03 Long Side Load Bag/Cartridge 06 08 10 12 14 -- 1 -- 1 3 3 3 3 6 6 8 8 8 12 12 18 24 24 32 40 40 54 62 Filter Arrangement 17 21 25 30 36 40 50 61 -- 4 4 3 7 24x24 1 1 2 2 2 2 Face Area (sq ft) 4 6 8 10 14 14 12x24 50 3 20x20 12x24 40 -- 9 12x24 36 2 -- Face Area (sq ft) 30 14 ........ -- Face Area (sq ft) 25 1 Angle 16x20 16x25 3 .......... 20x20 20x24 20x25 6 -- -- 03 Face Load Bag/Cartridge/HEPA 06 08 10 12 14 -- 1 -- 1 2 3 3 3 6 6 8 8 8 12 12 18 24 24 32 40 40 54 62 24x24 1 1 2 2 2 2 Face Area (sq ft) 4 6 8 10 12 14 NOTES: 1. Do not exceed filter manufacturer's velocity limits when selecting filters. 2. There are two dedicated filter sections for 2 in. or 4 in. flat filters. 3. Angle filter or filter mixing box sections can be configured to accept either 2 in. or 4 in. filters. 4. Draw-thru bag/cartridge filter sections accept 2 in. pre-filters. Filters must be a combination of bag filters in the sizes shown or 6 in. or 12 in. deep rigid media with 7/8 in. header. -- -- 5. The draw-thru bag/cartridge filter section is designed for side loading of filter media with a header for a 1 in. slide in track. 6. The blow-thru bag/cartridge/HEPA filter section is designed for face loading of filters ONLY (no side loading). 7. The blow-thru filter section requires filter media with spring clips, wire brackets, or retainers for use in a Puro-Frame holding frame. 97 1125 2O 20 20 16 20 20 Unit Size 03 Flat Filter Section Unit Size 06 Flat Filter Section Unit Size 08 Flat Filter Section Unit Size 10 Flat Filter Section (1) 25x20 (2) 25 x 20 (3) 25 x 16 (3) 25 x 2O 20 1 20 20 20 20 20 20 20 20 20 16 2O 2O 2O Unit Size 12 Flat Filter Section Unit Size 14 Flat Filter Section Unit Size 17 Flat Filter Section (6) 16 x 20 (3) 16 x 20, (3) 20 x 20 (6) 20 x 20 25 25 20 25 20 20 20 2O 24 2O 24 Unit Size 21 Flat Filter Section Unit Size 25 Flat Filter Section (6) 20 x 25 (8) 24 x 20 20 20 20 20 25 20 25 25 25 2O 24 2O 24 Unit Size Flat Filter (10) 24 x 20 2O 30 Section Unit Size Flat Filter (12) Shaded area represents filter section 36 Section 20 x 25 blankoff. Fig. 108 -- Flat Filter Arrangement -- 2-in. or 4-in. 98 25 25 25 25 2O 2O 25 2O 2O 20 20 20 Unit Size 40 Flat Filter Section (8) 20 x 25, (5) 25 x 20 20 20 20 20 20 25 25 25 Unit Size 50 Flat Filter Section (15) 25 x 20 16 16 16 16 16 16 16 2O 2O 25 25 Unit Size Flat Filter (14) 61 Section 20 x 16, (14) 25 x 16 Fig. 108 -- Flat Filter Arrangement -- 2-in. or 4-in. (cont) 99 25 20 20 25 16 I 25 20 16 16 16 16 16 Unit Size 06 Unit Size 08 Unit Angle Filter Section (2) 16 x 25 Angle Filter Section (4) 16 x 20 Angle Filter Section (4) 16 x 25 Angle 20 24 20 I 20 16 Unit Size 03 20 20 24 Size 10 Filter Section (6) 16 x 20 20 25 2O 2O 2O 2O 25 25 16 16 16 Unit Size 12 Unit Size 14 Angle Filter Section (6) 20 x 2O Angle Filter Section (4) 20 x 24, (2) 20 x 20 Unit Size 17 Angle Filter Section (9) 16 x 25 25 Unit Angle (12) Size 25 Angle (16) 16 16 16 16 16 16 16 Unit Section Angle 16 x 25 (12) Size 25 25 25 25 16 21 Filter 25 Unit 25 25 Size 25 Filter Section 16 x 25 25 25 25 25 16 16 16 16 16 16 16 16 16 30 Filter 25 Section 16 x 25 Unit Size 36 and 40 Shaded area represents filter section blankoff. Angle Filter Section (20) 16 x 25 Fig. 109 -- Angle Filter Arrangement -- 2-in. or 4-in. 1 O0 25 25 20 20 20 16 16 16 16 16 16 Unit Size 50 Angle Filter Section (12) 16 x 25, (18) 25 16 x 20 25 20 20 20 16 16 16 16 16 16 16 Unit Size 61 Angle Filter Section (14) 16 x 25, (21) 16 x 20 Fig. 109 -- Angle Filter Arrangement -- 2-in. or 4-in. (cont) 101 25 20 I 25 20 25 20 11 20 16 16 16 16 Unit Size 03 Unit Size 06 Unit Size 08 Unit Size 10 Filter Mixing Box Section (2) 16 x 25 Filter Mixing Box Section (4) 16 x 20 Filter Mixing Box Section (4) 16 x 25 Filter Mixing Box Section (6) 16x20 20 20 20 24 24 20 20 20 I 20 2O UnitSize12 Unit Size 14 Filter Mixing Box Section (6) 20 x 2O Filter Mixing Box Section (4) 20 x 24, (2) 20 x 20 24 24 24 25 25 25 12 16 12 16 12 16 12 16 Unit Size 17 Filter Mixing Box Section (12) 12 x 24 Unit Size 21 Filter Mixing Box Section (12) 16 x 25 25 25 25 25 16 16 16 16 16 16 Unit Size 30 Filter Mixing Box Section (16) 16 x25 filter section 25 16 Filter Mixing Box Section (12) 16 x25 area represents 25 16 Unit Size 25 Shaded 25 blankoff. Fig. 110 -- Filter Mixing Box Arrangement -- 2-in. or 4-in. 102 25 25 25 25 25 25 25 25 16 2O 16 2O 16 2O 16 2O 16 Unit Size 36 Filter Mixing Box Section (16) 20 x 25 16 Unit Size 40 Filter Mixing Box Section (24) 16 x 25 25 25 20 20 25 25 20 20 16 16 16 16 16 16 Unit Size 50 Filter Mixing Box Section 16 (12) 16 x 25, (18) 16 x 20 16 Unit Size 61 Filter Mixing Box Section (16) 16 x 25, (24) 16 x 20 Fig. 110 -- Filter Mixing Box Arrangement- 103 2-in. or 4-in. (cont) 24 I 24 12 24 24 24 24 12 24 24 Unit Size 03 Bag/Cartridge Pre-filter Section (1)24 x 24 Unit Size 06 Bag/Cartridge Pre-filter Section (1) 24 x 24, (1) 24 x 12 I Unit Size 08 Bag/Cartridge Pre-filter Section (2) 24 x 24 24 Unit Size 10 Bag/Cartridge Pre-filter Section (2) 24 x 24, (1) 24 x 12 24 24 1[ 12 12 24 24 12 12 Unit Size 12 Bag/Cartridge Pre-filter Section (3) 12 x 24, (2) 24 x 24 24 Unit Size 14 Bag/Cartridge Pre-filter Section (3) 12 x 24, (2) 24 x 24 24 24 24 24 24 12 24 24 24 Unit Size 17 Bag/Cartridge Pre-filter Section (3) 12 x 24, (3) 24 x 24 24 Unit Size 21 Bag/Cartridge Pre-filter Section (6) 24 x 24 24 24 24 24 24 24 24 24 24 24 Unit Size 25 Bag/Cartridge Pre-filter Section (6) 24 x 24 Unit Size 30 Bag/Cartridge Pre-filter Section (8) 24 x 24 Shaded area represents filter section blankoff. Fig. 111 --Side Load Bag/Cartridge 104 Filter Arrangement 24 24 24 24 12 24 24 Unit Size 36 and 40 Bag/Cartridge Pre-filter Section (4) 12 x 24, (8) 24 x 24 24 24 24 24 12 24 24 24 Unit Size 50 Bag/Cartridge Pre-filter Section (12) 24 x 24, (3) 24 x 12 SUPPORT 12 24 24 24 24 BAFFLE_ 12 24 24 24 Unit Size 60 Bag/Cartridge Pre-filter Section (12) 24 x 24, (7) 24 x 12 Fig. 111 -- Side Load Bag/Cartridge 105 Filter Arrangement (cont) 24 24 12 24 24 24 24 12 24 24 Unit Size 03 Bag/Cartridge/HEPA Pre-filter Section (1) 24 x 24 24 Unit Size 06 Bag/Cartridge/HEPA Pre-filter Section (1) 24 x 24, (1) 24 x 12 Unit Size 08 Bag/Cartridge/HEPA Pre-filter Section (2) 24 x 24 Support_ 24 12 24 Unit Size 10 Bag/Cartridge/HEPA Pre-filter Section (2) 24 x 24, (1) 24 x 12 24 24 12 12 24 24 Unit Size 14 Bag/Cartridge/HEPA Pre-filter Section (3) 12 x 24, (2) 24 x 24 Unit Size 12 Bag/Cartridge/HEPA Pre-fiiter Section (2) 12 x 24, (2) 24 x 24 24 24 24 24 24 24 12 24 24 24 Unit Size 17 Bag/Cartridge/HEPA Pre-fiiter Section (3) 12 x 24, (3) 24 x 24 24 Unit Size 21 Bag/Cartridge/HEPA Pre-filter Section (6) 24 x 24 24 24 24 24 24 24 24 24 24 Unit Size 25 Bag/Cartridge/HEPA Pre-fiiter Section (6) 24 x 24 24 Unit Size 30 Bag/Cartridge/HEPA Pre-fiiter Section (8) 24 x 24 Fig. 112- Face Load Bag/Cartridge/HEPA 106 Filter Arrangement 24 24 24 24 12 24 24 Unit Size 36 and 40 Bag/Cartridge/HEPA Pre-filter Section (4) 12 x 24, (8) 24 x 24 24 24 24 24 12 24 24 24 Unit Size 50 Bag/Cartridge/HEPA Pre-filter Section (12) 24 x 24, (3) 24 x 12 SUPPORT 12 24 24 24 24 BAFFLE\ 24 24 24 Unit Size 60 Bag/Cartridge/HEPA Pre-filter Section (12) 24 x 24, (7) 24 x 12 Fig. 1 12 -- Face Load Bag/Cartridge/HEPA 107 Filter Arrangement (cont) Magnehelic Gage Maintenance -- No lubrication or periodic servicing is required. Keep case exterior and cover clean. Occasionally disconnect pressure lines to vent both sides of gage to atmosphere and le-zero. 7. NOTE: To facilitate easy removal of setscrew fastened wheels, sheaves, or bearings, remove the setscrew completely. Taking care not to damage threads, insert a flat ended drift or punch, tap lightly and carefully return the materi_fl displaced on the shaft by the setscrew to its original place. CALIBRATION CHECK -- Select a second gage or manometer of known accuracy and in an appropriate range. Using short lengths of lubber or vinyl tubing, connect the high pressme side of the Magnehelic gage and the test gage to two legs of a tee. Very slowly apply pressure through the third leg. Allow a few seconds for pressure to equalize, fluid to drain, etc., and compare leadings. If accuracy unacceptable, gage may be returned to factory for recalibration. To calibrate in the field, use the following procedure. 8. Attempted field rep_ir may void your warranty. Recalibration or repair by the user is not recommended. 10. For best results, return gage to the factory. Ship prepaid to: Dwyer Instruments, Inc. Attn: Repair Dept. 102 Indiana Highway 212 Michigan City, IN 46360 Calibration: Remove scale sclews and scale assembly. to damage pointel: 4. The calibration is changed by moving the clamp. Ix_osen the clamp screw(s) and move slightly towmd the helix if gage is reading high; move away if gage is low. Tighten clmnp sclew and install scale assembly. Place cover and O-ring in position. Make sure the hex shaft on inside of cover is properly engaged in zero adjust screw. 6. Secure cover in place by screwing bezel tightly. Note that the alva under the cover is pressurized in operation and therefore gage will leak if not properly tightened. 7. Zero gage and compare to test instrument. adjustments as necesstuy. Fan Shaft Bearing Check fan shaft diameter at beming mount, ff worn by more than 0.001-in. below nominal, shaft should be replaced. [nstall new bearing, tighten holddown bolts, tighten bearing locking collm or setscrews. and then 12. Recoat fan shaft with a rust inhibitor or grease. 13. Replace sheave and belts. Adjust and align as described in Installation, Sheaves and V-Belts sections. 14. Replace access panels. 15. Restore electrical power Fan and Shaft Removal -- On airfoil fans, the fan wheel and shaft may be removed through inlet side of fan housing. See Fig. 113. On plenum fans, remove side, top, or end panel opposite inlet, wherever ductwork is not connected. After removing panel, proceed as follows. Be ctueful not 5. of shaft end. 11. Make ceflain fan wheel does not rub sides of fan housing after installing new be_uings. 1. With gage case, held firmly, loosen bezel, by turning counterclockwise. To avoid &_mage, canvas strap wrench or similar tool should be used. 3. Add a few drops ofoil after cleanup It should not be necesstuy to drive a new bearing onto shaft, ff light tapping is needed, do not tap against outer race. 9. Lift out plastic cover and "O" ring. Remove bearing while observing the following precautions: a. Make certain fan shaft surface is not rough or scored. If so, clean up surface with fine emery cloth. b. If bezel binds when installing, lubricate threads sparingly with light oil or molybdenum disulphide compound. 2. Loosen bearing setsclews and locking collm, and remove holddown bolts. 1. Remove drive belts as described Remov;d section above. Make further in Fan Shaft Beming 2. Block up fan wheel within housing when bearing bolts ale removed. to prevent diopping 3. Loosen beming holddown 4. Loosen bearing setscrews and locking collm, and remove holddown bolts. On forwmd-curved fans, remove cutoff plate. Remove fan wheel through discharge opening. bolts, block shaft up. NOTE: To facilitate easy removal of setscrew fastened wheels, sheaves or bearings, remove the setscrew completely. Taking care not to &_mage threads, insert a flat ended drift or punch, tap lightly and carefully return the materi;d displaced on the shaft by the setscrew to its original place. Removal 1. Isolate the unit from the system by closing &unpers to plevent "pin wheeling." Tie off the fan wheel to prevent rotation. 5. Remove bearing support channels and inlet ring fiom one side. 6. Remove fan shaft and fan wheel fi'om unit. 7. Remove fan shaft fi'om fan wheel. 2. Ix_ck open and tag electrical disconnect. 3. Enter through fan section access door or lemove panels as required. 4. Ix_osen motor base to frame bolts. Adjust motor to release belt tension and remove belts. Do not stwtch bel_ over sheaves. Damage to belts c_m result. 8. Replace shaft and wheel into fan in the reverse order of their removal. 9. Inspect bearings and if sel-¢iceable, replace on shall. 5. Remove bolts on bushing of fan shaft sheave, insert bolts in jacking hole provided on bushing and slowly jack bushing fi_m sheave. Remove bushing and sheave. 10. 6. Ix_osen bearing holddown bolts, block shaft up. 108 For airfoil and forward-curved fans, align fan wheel and shaft assembly in fan scroll. Check cutoff location if wheel failure damaged cutoff pkite. For plenum fan, align wheel and shaft assembly per manufacturer's directions supplied with fan. Table 31 -- Maintenance Intervals MAINTENANCE Heat sink temperature INTERVAL check and cleaning Every 12 months (more often if operating in a dusty environment) Main cooling fan replacement Capacitor change (frame size R5 and R6) Every five years Every ten years HVAC Control Every ten years panel battery change HEAT SINK -- The heat sink fins accumulate dust from the cooling air. Since a dusty heat sink is less efficient at cooling file drive, over temperature faults become more likely. In a normal environment check the heat sink annually, in a dusty environment check more often. Check the heat sink as follows (when necessary): 1. Remove power from drive. J Fig. 113 -- Fan Shaft 11. Tighten bearing shaft setscrews. 12. and Bearing holddown Removal bolts, beating setscrews, Motor Location -- The motor and motor base must be moved to place the motor at the front or re;u of unit. The proper location is the one that results in the longest &ive centerline distance. The motor may need to be replaced since the conduit box may need to be reversed: Tile conduit box (if not on top) should always be under the fan shaft for maximum centerline distance and motor adjustment. Fan failure can be predicted by the increasing noise from fan bearings and the gradual rise in the heat sink temperature in spite of heat sink cleaning, ff file drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are avtdlable from C_u'riec INTERNALLY ISOLATED UNIT -- When fan discharge is altered the motor is moved, then all isolators must be readjusted to assure proper unit isolation. To replace the main fan for frame sizes RI through R4, perform the following (see Fig. 114): 1. Remove power from drive. 2. Remove drive covel: of the unit is recommended. Lubrication with nameplate recommendations 3. Fan Bearings -- Lubricate fan bearings every 3 months with suitable betuing grease. Typic_d lubricants are given in Table 30. Porous Bronze Bearings -- These bearings are oil impregnaed. Annually lubricate with a few drops of non-detergent SAE 20 oil. Table OPERATING CONDITIONS 30 -- Lubrication BEARING TEMPERATURES 32 to 120 Clean Dirty 120 to 150 150 to 200 32 to 150 6 to 10 1 to 3 1 to 4 1 to 4 Motor and Drive Package give motor &_ta for forward-curved, Data -- 5. Install file new fan by reversing 6. Restore powel: Steps 2 to 4. 1. Remove power from drive. RECOMMENDED LUBRICANT months months weeks weeks 4. For frame sizes RI and R2, press together the retaining clips on the fan cover and lift. For frame sizes R3 and R4, press in on the lever located on the left side of the fan mount, and rotate the fan up and out. Disconnect the fan cable. To replace the main fan for frmne sizes R5 and R6, perform file following (see Fig. 115): Guide GREASE INTERVAL (F) Blow clean compressed air (not humid) fiom bottom to top and simultaneously use a vacuum cleaner at the air outlet to trap the dust. If there is a risk of the dust entering adjoining equipment, perform the cleaning in another room. 4. Replace file cooling fan. 5. Restore powel: MAIN FAN REPLACEMENTTile main cooling fan of the VFD has a life span of about 60,000 operating hours at maximum rated operating temperature and drive load. The expected life span doubles for each 18 F drop in the fan temperature (fan temperature is a function of ambient temperaturns and drive loads). eter tolerance at bearing mount of +.0000 in./-.001 in. IMPORTANT: must have a diamnominal. Carrier Replacement specified partsshafts are recommended. MOTORS -- Lubricate in accor&mce attached to motor or with manufacturer's included with motol: BEARINGS Remove the cooling fan. 3. and Field balancing of shaft and wheel is recommended. Rebalancing 2. Shell Alvanina #2 Texaco Multifak #2 Mobil Mobilus #2 2. 3. Remove the screws attaching Disconnect the fan cable. 4. Install the fan in reveLse ordec 5. Restore powel: file fan. CONTROL PANEL CLEANINGUse a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window. Tables 2A-2D BATTERY REPLACEMENT -- A batlery is only used in assistant control panels that have the clock limction available and enabled. The battery keeps the clock operating in memory during power interruptions. Tile expected life for the battery is greater than ten yeaLs. To remove the battery, use a coin to rotate the battery holder on the back of file control panel. Replace the battery with type CR2032. airfoil, and plenum fans. Variable Frequency Drive -- If installed in an appropriate environment, the VFD requires very little maintenance. Table 31 lists the routine maintenance intervals recommended by Carrier 109 with the coils operating tit partkd load without a vacuum breaking device. Problems with temperature control can occur when a thermostatic controller or stemn control valve is not functioning properly. Temperature control problems will also occur when the steam controls valve is oversized. Consider 1/3 to 2/3 Valve arrangements for full range control. Problems with "water logging" of the condensate tubes can occur when a coil with over 6 foot tubes is selected tit high air velocities, low steam pressures (below 5 psig) and high density fin spacing (9 fins per inch or more). This high density fin spacing, while producing high levels of heating capacity, also promotes excessive condensate. Given the length of the tubes and the low steam supply pressure, condensate can build up faster than the drain system can cmry it away. Considerations should be given for using two coils in series for this application. Steam Failure Modes -- The following failure modes could take as little as a weekend to &image a coil, or much longel: Problems occur quickly in coils using low pressure steam (<3 psig). Water hammer can develop inside the coil at the header end because the steam has already condensed and the low steam pressure does not adequately cletu it from the coil. This condensate re-boils and starts up water hammer inside the tubes. The action of this type of water hammeL which sounds like crackling inside the coil, is many tiny bubbles impinging on the inner and outer tubes. One result is the inner tube gets work htudened and eventually shatters. Another result is the eventual erosion of the outer tube causing pinhole leaks. Fig. 114Main Fan Replacement (Frame Sizes R1 - R4) BOTTOM VIEW (R5) Q Coils which are not properly vented will eventually load up wifll noncondensable gases. Coil performance (temperature rise) drops off as file noncondensables act as insulation inside the tubes. The coils may also fill with condensate. The collapsing steam causes a vacuum inside the coil when the supply valve closes. The trapped condensate will then freeze causing the tubes to rupture after it melts. The use of a vacuum breaker tit the condensate discharge will aid in relieving the vacuum in the coil and promote condensate drainage. BOTTOM VIEW (R6) _3 Refer to Tables 32-34 for 39M troubleshooting information. Disconnect power and allow all rotating equipment to stop before selwicing unit. Physically secure all fans before performing unit service. Failure to do so may result in serious personal injury or death. Water coil performance (when piped in ptuallel flow), will be reduced by approximately 5% for each coil row on coils 2 rows deep and deepo: Coils should always be piped with the water inlet on the leaving air side of the coil, regardless of water connection vertical position. Fig. 115Main Fan Replacement (Frame Sizes R5 and R6) TROUBLESHOOTING VFD DiagnosticsThe &'ive detects enor situations and reports them using: • the green and red LEDs on the body of the drive (located under the keypad) • the status LED on the control panel • the control panel display • The Fault W\_rd and Alarm Word parameters bits (parameters 0305 to 0309) The form of the display depends on the severity of the errol: The user can specify the severity for ma W enors by directing the drive to ignore the enor situation, report the situation as an alarm, or report the situation as a fault. Steam Coil Performance Problems -- Coil capacity is nommlly not a probleln with stemn coils. Low capacity can result from blocked or plugged air side surface, an tfir bound coil, or a coil which is filled with condensate because of a non-functioning steam trap. The CtuTier steam coils with the 1-in. OD outer tube have at least twice the condensate loading capacity of a coil with 5/8-in. OD outer tubes. Water hammer can &image the coil and cause leaks. It is typically caused by improper piping of the stemn supply, allowing condensate to enter the coil with the steam supply; or by accumulation of condensate in the coil which can occur llO CORRECTING FAULTS -- The recommended corrective fiction for faults is shown in the Fault Listing Table 35. The VFD can also be reset to remove the fault. If fin external source for a stmt command is selected find is active, the VFD may start immediately after fault reset. FAULTS (RED LED LIT)The VFD signals that it has detected a severe errok or fault, by: • enabling the red LED on the drive (LED is either steady or flashing) • setting an appropriate bit in a Fault Word parameter (0305 to 0307) • overriding the control panel display with the display of a fault code • stopping the motor (if it was on) • sets an appropriate bit in Fault Word parameter 0305 to 0307 To reset a fault indicated by a flashing red LED, turn off the power for 5 minutes. To reset a fault indicated by a red LED (not flashing), press RESET from the control panel or turn off the power for 5 minutes. Depending on the value of parameter 1604 (FAULT RESET SELECT), digital input or serial communication could also be used to reset the diive. When the fault has been corrected, the motor can be started. The fault code on the control panel display is tempormy. Pressing the MENU, ENTER, UP button or DOWN buttons removes the fault message. The message reappefu's after a few seconds if the control panel is not touched and the fault is still active. HISTORYFor reference, the last throe fault codes am stored into pmameters 0401, 0412, 0413. For the most recent fault (identified by parameter 0401), the drive stores additional &tta (in parameters 0402 through 0411) to aid in troubleshooting a problem. For example, a pfuameter 0404 stores the motor speed fit the time of the fault. To clem" the fault history (all of Group 04, Fault History parmneters), follow these steps: ALARMS (GREEN LED FLASHING)-For less severe errors, called akums, the diagnostic display is advisory. For these situations, the drive is simply reporting that it had detected something unusual. In these situations, the drive: • • • 1. In the control 0401. flashes the green LED on the drive (does not apply to alarms that arise from control panel operation errors) sets an appropriate bit in an Alarm Word parameters (0308 or 0309) overrides the control panel display with the display of an alarm code and/or name panel, Parameters 2. Press EDIT. 3. 4. Press the UP find DOWN Press SAVE. mode, select parameter button simultaneously. CORRECTING ALARMSTo correct aimms, first determine if the Alarm requires any corrective action (fiction is not fdways required). Use Table 36 to lind and addi'ess the root cause of the problem. Alarm messages disappear from the control panel display after a few seconds. The message returns periodically as long as the alarm condition exists. Table 32 -- Magnehelic Gage Troubleshooting SYMPTOM CAUSE Gage will not Indicate or is Sluggish. Duplicate pressure port is not plugged, Plug duplicate pressure port. Diaphragm _ressure. Replace gage. is ruptured Fittings or sensing or leaking. Pointer Stuck-- Gage Cannot be Zeroed, REMEDY due to excessive lines are blocked, pinched, Repair lines and fittings. Cover is loose or "0" ring is damaged or missing. Tighten cover and/or replace "0" ring. Pressure sensor (static tips, Pitot tube, etc.) is improperly located. Relocate pressure sensoK Ambient temperature For operation below 20 E order gage with low temperature (LT) option. is too low. Metallic particles are clinging to the magnet and interfering with helix movement. Scale is touching pointer. Spring/magnet assembly has shifted and is touching helix. Cover zero adjust shaft is broken or not properly engaged in adjusting screw. III Parts used in various sub-assemblies vary from one range of gage to another, and use of incorrect components may cause improper operation. Gages needing repair should be returned to: Dwyer Instruments Inc. Attn: Repair Dept. 102 Indiana Highway 212 Michigan City, IN 46360 Table 33 -- Humidifier Troubleshooting SYMPTOM CAUSE Water is Spitting from the Discharge Manifolds The steam the bottom not sloped The steam Steam does not Discharge from the Manifolds when the Valve is Open Steam Valve will not Open REMEDY Steam trap is not functioning properly. The header P-traps are not draining, Clean or replace non-functioning steam trap on the valve/trap assembly. Clean and check that plumbing runs to gravity drain. Check that trap height exceeds the static pressure of the duct/AHU, especially if it is under negative _ressure. Change line to take off from the top and check proper slopes. line has been taken from of the steam source or is properly. main is overloaded with water. Locate cause and correct problem. Vertical discharge manifolds are not plumb. Horizontal headers are not level. Make manifolds plumb. Make headers level. Vertical discharge manifolds installed upside down. Reinstall correctly. are Check valve sizing to maximum manifold capacity. Resize valve within manifold capacity. Valve is not open. There is no steam available. Open valve. Verify that steam is available. Verify that the steam pressure has not changed. jam the valve. There is a change in steam pressure. Steam Valve is Leaking Carefully place a mirror or metal object close to one of the steam discharge slots. If it fogs, steam is discharging, but evaporating very quickly. This is not a problem. DO NOT EVER PLACE YOUR HAND OVER OR NEAR THE STEAM DISCHARGE SLOTS. Y-strainer may be clogged, Clean or replace Y-strainer. There is no power. There is no control signal, Verify and, if necessary, correct power or air pressure to the valve actuator. Verify and, if necessary, correct control signal or pressure range to the valve actuator. Control polarity has been reversed, Verify and, if necessary, correct control signal polarity to the valve actuator. Actuator is not working, There is high steam pressure. Remove actuator to verify that it is operational. Clean or replace jammed valve. Verify that the steam pressure has not changed. Excessively high pressure could jam the valve. Verify proper valve orientation. Electric valves must face upward. There is no control signal, Control polarity has been reversed, Actuator is not working. There is high steam pressure. Verify and, if necessary, correct control signal to the valve actuator. Verify and, if necessary, correct control signal polarity to the valve actuator. Remove actuator to verify that it is operational. Clean or replace jammed valve. Verify that the steam pressure has not changed. Excessively high pressure could jam the valve. Valve has been installed incorrectly. Control signal is not at full range, Control polarity has been reversed, Verify proper valve orientation. Electric valves must face upward. Verify and, if necessary, correct full-range control signal to the valve actuator. Verify and, if necessary, correct control signal polarity to the valve actuator. Actuator is not working, Remove actuator and test to verify that it is operational. If not, clean or replace jammed valve. Verify that the steam pressure has not changed. Excessively high pressure could am the valve. There is high steam pressure, Humidity Exceeds Set Point Control signal is not at full range, Verify and, if necessary, correct compatibility valve actuator. There is no control signal. The controller is out of calibration. Verify and, if necessary, correct control signal polarity to the valve actuator. Check and, if necessary, correct calibration of controller. Ensure that humidity sensors are installed correctly and not located in drafts (wall). If necessary, correct sensor installation. Remove actuator and test to verify that it is operational. If not, clean or replace jammed valve. Verify that the steam pressure has not changed. Excessively high pressure could jam the valve. Verify stable boiler pressure. Wide swings in pressure could affect the humidity controls. Humidity sensor is not installed properly. Actuator is not working, There is high steam pressure, Boiler is not operating correctly. Humidity Remains Set Point Below Verify and, if necessary, correct compatibility valve actuator. Control polarity has been reversed, Controller is out of calibration, Verify and, if necessary, correct control signal polarity to the valve actuator. Check and, if necessary, correct calibration of controller. Ensure that humidity sensors are installed correctly and not located in drafts (wall). If necessary, correct sensor installation. Actuator is not working, Steam leaks from P-traps Boiler is not operating correctly. Verify stable boiler pressure. Wide swings in pressure could affect the humidity controls. There is an airflow switch fault. Ensure that airflow switch is not fluttering. switch. The high limit controller is not in the correct location, The humidifier is too small, Verify that high-limit controller is not located too close to steam discharge folds. If necessary, correct location of controller. Humidifier is undersized. Check humidity load calculations. The humidifier is too large, There is a high limit controller Verify humidifier capacity versus air volume. Verify that high limit controller is working. If necessary, correct problem. fault, Air-Handling airflow mani- Verify and, if necessary, correct evaporation distance to obstructions or elbows. Verify steam valve is not leaking. If necessary, correct leaking steam valve. The trap height is incorrect, Ensure that height of trap exceeds the static pressure of the duct/AHU, especially if under negative pressure. Check valve sizing to maximum manifold capacity. If necessary, resize valve within manifold capacity. Check that inlet steam pressure does not exceed humidifier capability. There is excessively -- If necessary, correct fluttering Evaporation distance is too short. Steam valve is leaking. Valve sizing is incorrect. AHU of the full range control signal to the Remove actuator and test to verify that it is operational. If not, clean or replace jammed valve. Verify that the steam pressure has not changed. Excessively high pressure could jam the valve. There is high steam pressure, in unit of the full range control signal to the Control signal is not at full range, Humidity sensor is not installed properly. Condensate high pressure could Steam is not visible. Valve has been installed incorrectly. Steam Valve will not Close Excessively high steam pressure. Unit 112 Table 34 -- Troubleshooting SYMPTOM CAUSE REMEDY Motor Fails to Start Power line open Improper wiring or loose connections Overload trip Mechanical failure Improper current supply Reset circuit breaker. Check wiring and connections. Check and reset overload, Inspect motor and drive for operation and/or damage, Check rating plate against actual supply voltage, Contact power provider for adjustments if needed, Motor Stalls Open Phase Overloaded motor Low line voltage Check line for open phase, Reduce motor load or replace with larger motor. Check supply line, correct voltage, Excessive Vibration Bearing/shaft misalignment Shipping blocks/spacers not removed Excessive belt tension Drive misaligned Check and align bearing set screws, Remove shipping blocks/spacers. Adjust belt tension, Align drive. Bearing(s) is Hot Grease not evenly distributed Over-lubrication No lubricant Misaligned bearing Allow Clean Check Check after lubrication Motor Does Not Run at Full Speed Low voltage at motor terminals Supply wiring to motor too small Motor Overheats Overloaded motor Motor fan is clogged, preventing Excessive Motor Noise unit to cool down and restart, and purge excess grease, bearings for damage and apply lubricant. shaft level and reset alignment. Check supply voltage and correct voltage loss, Rewire with properly sized wire, motor cooling Reduce motor load or replace with larger motor. Clean motor fan. Mounting bolts loose Rigid coupling connectors Worn motor bearings Fan rubbing on housing Tighten bolts, Replace with flexible connectors, Replace bearings and seals, Adjust housing, Motor Runs and Then Slows Partial supply voltage loss Check for loose/dirty connections. Verify supply voltage, Excessive High load due to over-tensioned drive Excessive overhung load caused by a small diameter motor sheave Check belt tension and load. Replace with larger sheave, Loose Fan Belt Improper motor position Worn sheaves Worn or damaged belt Adjust tension, Replace sheaves. Check sheave alignment and replace belt(s). Drive Noise Sheave(s) not tight on fan/motor shaft(s) Belts contacting guard(s) Belts too loose or too tight Belts and sheaves mismatched Belts not length matched (multiple belt set-up) Misaligned sheaves Belts worn Belts dirty or oily Tighten sheaves, Adjust or tighten belt guard mounts. Adjust belt tension. Install proper belts. Install matched belts. Align sheaves. Replace belts. Replace belts. Bearing Defective bearing Lack of lubrication Loose bearing Bearing misaligned Foreign material/dirt inside bearing Corrosion between bearing and shaft Repair/replace bearing. Lubricate bearing, Adjust bearing support or bearing on shaft, Align bearing properly. Inspect and clean bearing. Clean or replace bearing as required, Fan speed too high Ductwork too restrictive Low static pressure Registers and grilles too restrictive Check fan speed. Increase duct size for proper air velocity. Decrease fan speed to obtain proper pressure. Replace with correctly sized registers and grilles, Rattling or Whistling Noise in Airstream Loose dampers, grilles, or splitters Obstructed dampers or grilles Sharp elbows in ductwork Sudden expansion/contraction of ductwork Turning vanes loose or not properly installed Adjust as needed. Remove obstruction(s), Install larger radius elbows, Install proper ductwork transitions. Tighten or adjust as needed. CFM Lower than System Requirements Fan rotating backwards Fan speed too slow Duct system has more resistance Diffusers closed Reverse any two power leads to the fan motor, Check fan RPM. Enlarge ductwork to match system requirements. Open diffusers. Motor Bearing Noise High Velocity High Current (Motor) Electric Air Noise Draw Heat Inoperative Wear than designed Motor overload Low line voltage Electric heater manual reset tripped Broken heating element Electric heater fuses blown Inoperative electric heating circuit contactor Airflow switch interlock not closed Heater Cycles Airflow marginally Improper Temperature Regulation Intermittent installation insufficient Airflow switch may chatter and cycle heater circuits off and on. Or, automatic reset may open and close, causing a similar situation. Check unit airflow requirements and clean the system, power supply due to improper Erratic thermostat operation due to improper location or frequent resetting Air system characteristics with the job requirements No Hot Water or Steam Heat Reduce system load or use larger motor, Consult power company about increasing line voltage, Determine cause of cutout and reset switch, Replace element, Replace fuses, Repair/replace as needed. Check airflow sensing tube location and operation in airstream. Repair/replace as needed, are not in accordance Defective hot water or steam valve actuator motor Broken control linkage from actuator to valve assembly Defective hot water or steam control valve 113 Recheck installation procedure. Check contactor operation and safety cutout switches, Refer to heater wiring diagram, Check thermostat installation instructions. Be certain that the thermostat location is not subjected to adverse temperature changes, such as those caused by opening doors or windows. Check for thermostat tampering. Check the supply-air fan is delivering adequate volume and velocity. Check air system balance, Be certain that heating coils are operating, Repair/replace Repair/replace Repair/replace as needed. as needed. as needed. Table 35 -- Fault Codes FAULT CODE FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION 1 OVERCURRENT Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters 2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections. 2 DC OVERVOLT Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds), or undersized brake chopper (if present). 3 DEV OVERTEMP Drive heat sink is overheated. Temperature is at or above 115 C (239 F). Check for fan failure, obstructions in the airflow, dirt or dust coating on the heat sink, excessive ambient temperature, or excessive motor load. 4 SHORT CIRC 5 OVERLOAD 6 DC UNDERVOLT 7 All LOSS Analog input 1 loss. Analog input value is less than All FLT LIMIT (3021). Check source and connection for analog input and parameter settings for AI 1 FLT LIMIT (3021) and 3001 AI1305 AI 2 MAX. 1301 AI MIN > 1302 AI 1 MAX and 1004 PAR AO SCALE Parameter values are inconsistent. Check that parameter and that parameter 1510 AO 2 MIN > 1511 AO 2 MAX. 1504 AO 1 MIN > 1505 AO 1 MAX 1005 PAR PCU 2 1006 PAR EXT RO 1007 PAR FBUS Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g. 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0. 1008 PAR PFA MODE Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must be = 3 (SCALAR SPEED), when 8123 PFA ENABLE is activated. 1009 PAR PCU 1 1010 OVERRIDE/PFA CONFLICT Parameter values 2001 MINIMUM 2007 MINIMUM 2001 MINIMUM 2002 MAXIMUM 2007 MINIMUM 2008 MAXIMUM are inconsistent. Check for any of the following: SPEED > 2002 MAXIMUM SPEED FREQ > 2008 MAXIMUM FREQ SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128 to +128 SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128 to +128 FREQ / 9907 MOTOR NOM FREQ is outside ef the range: -128 te +128 FREQ / 9907 MOTOR NOM FREQ is outside ef the range: -128 te +128 Check that 2007 MINIMUM FREQ is negative, when Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check the following parameters: 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6 Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g., in US) Parameter values are inconsistent. Check the extension relay module for connection 1410 through 1412 RELAY OUTPUTS 4 through 6 have non-zero values. and Parameter values for power control are inconsistent or improper motor nominal frequency or speed. Check for both of the following: 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992 Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA interlocks cannot be observed in the override mode. 115 Table 36 -- Alarm Codes ALARM CODE 2001 ALARM NAME IN PANEL I Reserved DESCRIPTION 2002 -- Reserved 2003 I Reserved AND RECOMMENDED CORRECTIVE ACTION 2004 DIR LOCK The change in direct being attempted is not allowed. Do not attempt to change the direction of motor rotation, or Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe). 2005 I/O COMM Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line. 2006 All LOSS Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001). 2007 AI2 LOSS Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check the parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001). 2008 PANEL LOSS Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the VFD is in remote control mode (AUTO) and is parametrized to accept start/stop, direction or reference from the control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM). Reserved 2009 I 2010 MOT OVERTEMP Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload fault trip may be near. Check for overloaded motor. Adjust the )arameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters. 2011 UNDERLOAD Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to 3015. 2012 MOTOR STALL 2013" AUTORESET This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To control automatic reset, use parameter group 31 (AUTOMATIC RESET). 2014" AUTOCHANGE 2015 PFA INTERLOCK This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the Pump Alternation macro. This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when Autochange is used), or a speed regulated motor (when Autochange is not used). Reserved Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near. 2016 I 2017* OFF BUTTON 2018" PID SLEEP This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126. 2019 2020 ID RUN OVERRIDE The VFD is performing an ID run. Override mode is activated. This alarm indicates that the OFF button has been pressed. 2021 START ENABLE 1 MISSING This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To correct, check the digital input configuration and the communication settings. 2022 START ENABLE 2 MISSING This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter 1609. To correct, check the digital input configuration and the communication settings. 2023 EMERGENCY STOP Emergency stop is activated. *This alarm is not indicated by a relay output, even when the relay output is configured conditions (parameter 1401 RELAY OUTPUT = 5 [ALARM] or 16 [FLT/ALARM]). to indicate alarm Copyright 2004 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications PC 201 Catalog No. 533-952 Printed in U.S.A. or designs without notice and without incurring obligations. Form 39M-6Sl Pg 116 12-04 Replaces: 39M-5Sl
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 116 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 15:49:51 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools