CARRIER Package Units(both Units Combined) Manual L0520534
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 55
Download | |
Open PDF In Browser | View PDF |
48HJ004-007 Single-Package Rooftop Heating/Cooling Standard and Low NOx Units Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS ...................... 1 INSTALLATION ................................ 1-36 Step 1 -- Provide Unit Support ................... 1 • ROOF CURB • SLAB MOUNT • ALTERNATE UNIT SUPPORT Step 2 -- Field Fabricate Ductwork ............... 2 Step 3 -- Install External Trap for Condensate Drain .............................. 4 Step 4 -- Rig and Place Unit ..................... 4 • POSITIONING Step 5 -- Install Flue Hood ....................... 5 Step 6 -- Install Gas Piping ...................... 5 Step 7 -- Make Electrical Connections ........... 5 • FIELD POWER SUPPLY • FIELD CONTROL WIRING • HEAT ANTICIPATOR SETTINGS Step 8 -- Adjust Factory-Installed Options ...... 13 • COBRA TM ENERGY RECOVERY UNITS • HUMIDI-MIZER TM ADAPTIVE DEHUMIDIFICATION SYSTEM • MANUAL OUTDOOR-AIR DAMPER • CONVENIENCE OUTLET • NOVAR CONTROLS • PREMIERLINK TM CONTROL • OPTIONAL ECONOMISER IV AND ECONOMISER2 • ECONOMISER IV STANDARD SENSORS • ECONOMISER IV CONTROL MODES Step 9 -- Adjust Evaporator-Fan Speed ......... 25 PRE-START-UP .................................. 37 START-UP .................................... 37-42 SERVICE ..................................... 42-48 TROUBLESHOOTING ......................... 49-53 INDEX ........................................... 54 START-UP CHECKLIST ........................ CL-I SAFETY Disconnect gas piping from unit when leak testing at pressure greater than 1/2psig. Pressures greater than ]h psig will cause gas valve damage resulting in haz_u'dous condition. If gas valve is subjected to pressure greater titan 1h psig, it mustbe replaced before use. When _ressure testing field-supplied gas piping at _ressures of I/2 psig or less, a unit connected o such piping must be isohtted by manu_dly closing the gas valve(s). INSTALLATION Unit is shipped in the vertical dischtuge configuration. To convert to horizontal discharge application, remove duct opening coveLs. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around openings must be tight. See Fig. 1. Step 1 -- Provide I critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. hnproperly applied gasket can IMPORTANT: The gasketing of the unit to the roof curb is ] result in air leaks and poor unit performance. Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to lhnction properly. Refer to Accessory Roof Curb [nstalhttion Instructions for additional infomtation as required. reserves the right to discontinue, or change at any time, specifications Catalog Unit Support ROOF CURB -- Assemble and install accessory roof curb in accor&mce with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If electric control power or gas service is to be routed through the basepan, attach the accessory thin-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be inst_dled before unit is set on roof curb. CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electric_d components. Only trained and qualifed service personnel should install, repair, or service ai>conditioning equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on ai>conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers avaihtble for all brazing operations. Manufacturer Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating phtte. Electricgd shock could cause personal injury. No. 04-53480013-01 Printed in U,S.A. or designs without notice and without incurring obligations. Form 48HJ-33SI Pg 1 9-05 Replaces: 48HJ-29SI SLAB MOUNT (Horizontal Units Only) -- Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to plevent grass and foliage from obstructing airflow. NOTE: Horizontal units may be installed on a roof curb if required. Ducts passing through an unconditioned space must be insulated and covered with a vapor barriel: If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg with economizer or 0.45 in. wg without economizeE ALTERNATE UNIT SUPPORT -- When the curb or adapter cannot be used, suppoll unit with sleeper rails using unit curb or adapter suppoll area. If sleeper rails cannot be used, suppoll the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side. These units are designed for a minimum continuous returnair temperature in heating of 50 F (di_ bulb), or an intermittent operation down to 45 F (di_ bulb), such as when used with a night setback thermostat. Step 2 -- Field Fabricate Ductwork -- Secure _fll ducts to roof curb and building structure on veltical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizont_d discharge openings and _11ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accor&mce with applicable codes. To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45 F. Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise. REMOVABLE HORIZONTAL RETURN DUCT OPENING COVER '_k k \ \ \ \ \ \ _ REMOVABLE HORIZONTAL SUPPLY DUCT OPENING COVER Fig. 1 -- Horizontal Conversion Panels CONNECTOR PKG. ACCY. B D ALT DRAIN HOLE C CRBTMPWROO1A01 CRBTMPWROO2A01 CRBTMPWROO3A01 1'-911/16" [551] 1'-4" [406] 13/4', [44.5] CRBTMPWROO4A01 GAS POWER CONTROL 3/41' [19] NPT 3/4" [19] NPT 11/4" [31.7] 1/2"NPT [12.7] 3/4"1119]NPT [19]3/4"NPT 11/4" [31.7] ROOF CURB ACCESSORY ACCESSORY POWER /_ _" / ",\ ' 1 I 004-007 NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance: 4 ft on each side. 7. I_ ",,\ J _ I \\ I [610] 2'-0" 48HJ 1/2" [12.7] I C ] CRRFCURB002A01 1/21' [12.7] I jl UNIT SIZE CRRFCURBOOIA01 C '_4I A Direction of airflow. 8. Connector packages CRBTMPWROO1A01 and 002A01 are for thru-the-curb type gas. Packages CRBTMPWROO3A01 and 004A01 are for thru-the-bottom type gas connections. IX I iI \1 i I B o' 3" 1753 GASKET TYPICAL (SUPPLIED I (FIELD WITH CURS) O" (4) SIDES 7/16" DUCT DUPPLIED) FLASHING SUPPLIED) (FIELD I I O" 3" [76] I I (APPROXD _B I I I I 2" (FIELD 7 5/D" [803] 5TRIP SUPPLIED) MATERIAL (FIELD 5UPPL[ED) o. 0 I SUPPLY I I 1 7/16" E341 ] AIR OPENING C "C C" SECTION Y O 7116" nl] (DOLT HEAD5) SCALE -1 O" _ O" 1" 0 7116" [II] (BOLT HEADD) 7[504] 13/1D3._ O' E7B] RIGID (FIELD INSULATION DUPPLIED) 1:4 o I + I 1" .. # I # # O' 0 7/16" 3' O" [914] O' 0 7/15" OPENING FOR SERVICE. HEADS) n. _A O' O' BADEPAN (SEE # (BOLT 2 ENTRY NOTE #D) 1/2" 3 1/4" [83]_ O" 9" DEE NOTE #2 # O' 0 1/4"[73 GAD • (SEE $ E 8 SUPPLY AIR VIEW 5ERVICE PLATE 1' 4 13/15" [427] (INSIDE) " 6" [152] :IND[DE) I I RETURN AIR•• "A-A" 2 3/8 ° [Bl] I I HEAD OF DOLT TO BE ON INDIDE OF FLANGE I I I 1/8" E1705] NOTE: CAMBRIDGEPORT FASTENING ALTERNATE Fig. 2 -- Roof Curb Details "SURE LOCK" CORNER DEVICE IS ACCEPTABLE CONSTRUCTION. All panels must be in place when rigging and lifting. POSITIONING -- Maintain clefuance around find above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 7. UM ALLOWABLE DIFFERENCE (in.) B OlOCl C 0.5 1.0 1.0 Fig. 3 -- Unit Leveling Tolerances Step 3 -- Install External Trap for Condensate Drain -- The unit's 3h-in. condensate drain connections am located on the bottom and side of file unit. Unit discharge connections do not determine the use of drain connections; either &ain connection can be used with vertic_d or horizontal applications. When using the standard side &ain connection, ensure the plug (Red) in the ;alternate bottom connection is tight before installing the unit. To use the bottom &ain connection for a roof curb installation, relocate the factory-inst;dled plug (Red) from the bottom connection to the side connection. Tile center drain plug looks like a star connection, however it can be removed with a m/2-in. socket drive extension. See Fig. 4. The piping for the condensate &ain find external trap can be completed after the unit is in place. All units must have fin external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit fit 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.). See Fig. 5. Step 4 -- Rig and Place Unit-Inspect unit for transportation dmnage, and tile any claim with transpollation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit fl_lme as a reference. See Table 1 and Fig. 6 for additional information. Operating weight is shown in Table 1 and Fig. 6. Lifting holes m'e provided in base rfdls as shown in Fig. 7. Refer to rigging instructions on unit. Position unit on roof curb so that file following clearances are 1/4 in. clearance between the roof curb find the base rail inside the front and refu'. 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on file condenser end of the unit being approximately equal to Fig. 2, section C-C. Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contmninated air maintained: Be sure flint unit is installed such that snow will not block the combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used. Although unit is weafllerproof, higher level runoff and overhangs. guard against water from Ix>cate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible materiffl. When unit is located adjacent to public walkways, flue assembly must be fit least 7 fl above grade. NOTE: When unit is equipped with an accessory chmge deflector, allowable clearance is 18 inches. Flue gas can deteriorate building materials. that flue gas will not affect building materials. flue dis- Orient unit such Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion find Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 find addendum Z223.1a-1987. In Canada, installation must be in accordance with the CANI.BI49.1 and CANI.BI49.2 installation codes for gas burning appliances. Flue vent dischmge must have a minimum horizontal clearance of 4 fl from electric and gas meters, gas regulators, find gas relief equipment. After unit is in position, remove shipping materials ging skids. \ OPEN I IIII / I I IIII 2" MINI VENT and rig- SEE NOTE _L_ HORIZONTAL DRAIN OUTLET NOTE: Drain plug is shown in factory-installed position. Fig. 4- .,,_ROOF CURB DRAIN PLUG Condensate Drain Pan NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended. Fig. 5 -- Condensate Drain Piping Details 36"- 54" (914-1371) POSITION ALL SEAL STRIPS IN PLACE BEFORE POSITIONING UNIT ON ROOF CURB, DETAIL "A" DUCT END SEE "A_DETAIL PLACE UNIT ON CURB AS CLOSE TO DUCT END AS POSSIBLE NOTES: 1. Place unit on curb as close as possible to the duct end. 2. Dimension in ( ) is in millimeters. 3. Hook rigging shackles through holes in base rail as shown in detail "A." Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. 4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer. 6. Weights include base unit without the Humidi-MiZer TM adaptive dehumidification system. See Table 1 for unit operating weights with the Humidi-MiZer system. All panels must be in place when rigging. UNIT 48HJ OPERATING WEIGHT 004 Ib 530 kg 240 005 540 245 006 560 254 007 635 288 "A" in. 73.69 73.69 73.69 73.69 "g" mm 1872 1872 1872 1872 in. 35.50 35.50 35.50 35.50 "C" mm 902 902 902 902 in. 33.31 33.31 33.31 33.31 mm 847 847 847 847 Fig. 6 -- Rigging Details Step 5 -- Install Flue Hood -- Flue hood is shipped screwed to the burner comp;utment access panel. Remove from shipping location and, using screws provided, inst;dl flue hood in location shown in Fig. 7 and 8. For units being installed in California Air Quality Management Districts which require NOx emissions of 40 nanogrmns/ joule or less, a low NOx unit must be installed. NOTE: Low NOx units are available for 3 to 5 ton units. Install Gas Piping -- Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223. IA- 1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CANI .B149.1 and CANI .B149.2 installation codes for gas burning appliances. For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 48HJ005-007 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection. Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe sm_dler than unit gas connection. Support gas piping as shown in the table in Fig. 9. For example, a 3/4-in. gas pipe must have one field-fabricated support bemn every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams. See Fig. 9 for typical pipe guide and locations of extermd manual gas shutoff valve. piping can be routed through field-drilled holes in the basepan. The basepan is speci_dly designed and dimpled for drilling the access connection holes. When connecting the gas line to the unit gas v_dve, the installer MUST use a backup wrench to prevent damage to the v_dve. Step 6 -- NOTE: If accessory thin-the-bottom connections and roof curb are used, refer to the Thin-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas Step 7 -- Make Electrical Connections Unit cabinet must have an unintenupted, unbroken electric_d ground to minimize the possibility of pel.sonal injury if an electrical fault should occm: This ground may consist of electric_d wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (Natiomd Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground Failure to follow this warning could result in the installer being liable for personal injury of others. FIELD POWER SUPPLY -- All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformel: Refer to unit label diagram for additional information. Pigtails me provided for field service. Use factory-supplied splices or UL (Underwriters' Laboratories) approved copper connectoE STD. UNIT WEIGHT LB KG UNIT 530 240 4BHJ_OO5 540 560 4BHJ_O07 G35 48HJ_004 !CONOMI_ERI_ VERT. ECONIV (A) (SI (C) (D) WEIGHT W/P.E. WEIGHT CORNER WEIGHT CORNER WEIGHT CORNER WEIGHT CORNER WEIGHT LB KG LB KG LB KG LB KG LB KG LB KG 50 22,7 go 40,S 127 57,G 122 55,3 138 62.8 143 84,9 245 254 129 134 SS.5 60.8 124 129 55.2 58.5 141 148 54.0 66.2 145 151 55.2 88.5 288 152 68.S 147 55.7 1S5 74.8 171 77.5 2" iN. MM S 5/16" 84G.5 4BHJ_OO5 ; 3" ; 5 5/15" CONNECTION BOTTOM POWER CHART: THE5E HOLE5 REG'D FOR U5E WITH ACCE550RY PACKAGES CRBTMPWROO1A01, 2A01, 3A01, OR 4A01 "J" FT 1050 THREADED CONDUIT 5]ZE WIRE USE 1/2" 1/2" 3/4" (001,003) 1/4" (O02,004) (003) 1/2"FPT ACC. 24V DOWER_ DOWER_ GA5 1 2" 3/8" SIZES DIA. DIA. [3B] [51] FIELD POWER POWER SUPPLY SUPPLY KNOCK HOLE OUT REQ'D HOLE SIZES (MAX.) 7/8"[22.2] 7/B'[22.2] 1 1/8"[28.4] 1 3/4"[44,4] 1 1/4"[31.8] NOTES= 1. DIMENSIONS 2. _CENTER IN [ ] ARE IN MILLIMETERS. 3. _ 4. ON VERTICAL DISCHARGE UNITS, DUCTWORK TO BE ATTACHED TO ACCESSORY ROOF CURB ONLY. FOR HORIZONTAL DISCHARGE UNITS FIELD SUPPLIED FLANGES SHOULD BE ATTACHED TO HORIZONTAL DISCHARGE OPENINGS, AND ALL DUCTWORK SHOULD BE ATTACHED TO THE FLANGES. CORNER MINIMUM CLEARANCE (LOCAL CODES OR JURISDICTION MAY PREVAIL): BETWEEN UNIT, FLUE SIDE AND COMBUSTIBLE SURFACES, 35 IN.,18 IN. WHEN USING ACCESSORY FLUE DISCHARGE DEFLTR. BOTTOM OF UNIT TO COMBUSTIBLE SURFACES (WHEN NOT USING CURB) 1 INCH. BOTTOM OF BASE RAiL TO COMBUSTIBLE SURFACES (WHEN NOT USING CURB) O INCHES. CONDENSER COIL, FOR PROPER AiR FLOW, 3B iNCHES ONE SIDE, 12 iNCHES THE OTHER. THE SIDE GETTING THE GREATER CLEARANCE IS OPTIONAL. OVERHEAD, SO iNCHES TO ASSURE PROPER CONDENSER FAN OPERATION. 3" REAR OF GRAVITY. (DISPOSABLE S. a. b. c. d. DIRECTION OF AIR F [ LTER/ECONOM FLOW. e. F. BETWEEN UNITS, CONTROL BOX SIDE, 42 IN. PER NEC. BETWEEN UNIT AND UNGROUNDED SURFACES, CONTROL BOX SIDE, 38 IN. PER NEC. g. BETWEEN UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, CONTROL BOX SIDE, 42 IN. PER NEC. HORIZONTAL SUPPLY AND RETURN END, 0 INCHES WHEN THE ALTERNATE CONDENSATE DRAIN IS USED. h. B. WITH THE EXCEPTION COIL AND COMBUSTION AND c, A REMOVABLE CLEARANCE. 7. UNITS MAY BE INSTALLED FROM WOOD OR CLASS A, IF SET ON BASE RAIL. 8. [ ZER ICONDENSER _L (BO_#" _4_f 4 9 UP 71"7 _O' c ft COIL RETURN AIR ALTI OPENING O' I0 1S/1B" [278] I SUPPLY 1S/1B" [4S] O" 3 SW1B" [99.4] _ AIR l I 2"11 O" [BOB] 3" O" [gl 4] G" 3 13/1B" [97] FLUE HOOD 3 O" SUPPLY AIR _ S 7/1B" 1" O' 7 1/4" _[1B4] O" lO 13/15" l' 1 11/1G" [1872] O' S SW1B" [439.7] // O" 0 7/IS'Ell.l] L _ ECONOM[$ER O' IV 4 1/1B" W/ POWER EXHAUST O 3/8" h FAN MOTOR ACCESS PANEL x 3 5/IB" Egl.O] 1" 2 7/8" [375.B] SUPPLY AIR HOR[ h Nh ZONTAL h Nil 7" h III HORIZONTAL II h IlL Ill h 2" 1 ll/1G" [852.5] l' OUTSIDE O" OPENING _®1 8 1/4" AIR 0 7/8" j 5 3/8 [74B. 2] _0' S ll/1B" [144.3] "FORK TRUCK SLOTSo, 2 1/4"DIA O' 5 [14B]3/4" OUT_J_L'y[BSB'B]lAIR15/1B" RETURN BISGONNEGTLooATION [Sl4] h O" [2141B 7/1B SIDE 1/4" ,£4 "C" lli 2" S //4/` _[81] 4 5/16" [414.5] [104B] [470] 1 'G 1/2"_ [13B] 1/16" [78]_ O' B S/B" [168.23 EG5_ LEFT _ CONTROL BOX/COMPRESSOR/ BURNER ACCESS PANEL _0" TYP 8/1 G" AIR _°'2Ss_G'EBs III IllS.B] RETURN 3/8" L__IJ INDOOR SLOWER l" S [137] 1'53/4"[451] FRONT FACTORY SIDE _.____j O" CONDENSATE , DRAIN OPENING IN SASEPAN FROM RIGHT S3Zl@" ' E/' I----i 9" [1144] O' r---1 [81] EVAPORATOR I I VERTIGAL I, CORNER G'[457] DO VIEW 5 5 ON COMBUSTIBLE FLOORS MADE S, OR C ROOF COVERING MATERIAL 1' BLOCKOFF PANEL 1" S 1/4" [438] FOR ECONOM]$ER [V PANEL_ OF THE CLEARANCE FOR THE CONDENSER SIDE AS STATED IN NOTE #Sa, b, FENCE OR BARRICADE REQUIRES NO THE VERTICAL CENTER OF GRAVITY IS FROM THE BOTTOM OF THE BASE RAIL. FILTERS) ACCESS [573 FRONT (TYP s PLACES) Fig. 7 -- Base Unit Dimensions OF AIR BAROMETRIC PANEL R IGHT S IDE E STD. CONDENSATE DRAIN RELIEF DISCHARGE [5143 When installing All field requirements. \ Fig. 8-- i= FLUE OPENING Flue Hood Details 9" MINIMUM must comply with per NEC. NEC and local Install conduit through side panel openings indicated in Fig. 7. Route power lines through connector to terminal connections as shown in Fig. 10. k -41 INTAKE LOUVERS units, provide a disconnect wiring X CLEARANCE Voltage to compressor terminals during operation must be within voltage range indicated on unit nmneplate (also see Tables 2A-2D). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A-2D, Note 3 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause &image to electric_d components. Such operation would inv_di&_te any applicable Carrier warranty. NOTE: If accessory thin-the-bottom connections and roof curb tu'e used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the baseptm. The basepan is specially designed and dimpled for drilling the access connection holes. See Fig. 2. FIELD CONTROL WIRING -- Install a Carrier-approved accessory thermostat assembly according to inst_dlation instructions included with the accessory. Ix)cate thermostat assembly on a solid wail in the conditioned space to sense average temperature in accor&mce with thermostat installation instructions. 4 FROM GAS METER SUPPORT* LEGEND NFGC -- National Fuel Gas Code Connect low-voltage *Field supplied, NOTE: Follow all local codes. SPACING OF SUPPORTS STEEL PIPE NOMINAL DIAMETER 1/2 a/4or I 1V4 or larger (in.) Route thermostat cable or equivalent single leads of colored wire from subbase termin_ds through connector on unit to lowvoltage connections (shown in Fig. 11A and 11B). SPACING OF SUPPORTS X DIMENSION (ft) 6 8 10 Fig. 9 -- Gas Piping Guide (With Accessory Thru-the-Curb Service Connections) thermostat wires to matching screw termimds connection bozud. See Fig. 11A and I lB. of NOTE: For wire runs up to 50 fl, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 It, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Pass the control wires through the hole provided in corner post; then feed wires through the raceway built into corner post to the 24-v barrier located on the left side of control box. See Fig. 12. The raceway provides the UL quired cle_u'ance between high and low-voltage wiring. the the the re- HEAT ANTICIPATOR SETTINGS -- Set heat anticipator settings at 0.14 amp for first stage and 0.14 for second stage heating, when available. Table 1 -- Physical Data BASE UNIT 48 NOMINAL CAPACITY HJE/F/H/K]M/NO04 3 OPERATING WEIGHT (Ib) Unit Humidi-MiZer TM Adaptive EconoMi$er IV Roof Curb Dehumidification 530 15 50 115 System COMPRESSOR ouontity 1 Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (Ib-oz) Standard Unit With Unit Humidi-Mizer CONDENSER 42 Adaptive Dehumidification 5-8 12-5 System 3500 V4 ,825 180 Scroll 1 53 TM I R-22 Metering 10-2 16-8 635 29 50 115 1 I 1 50 60 Device I 10-0 20-5 I 4100 V4_1100 320 Enhanced Copper Tubes, Aluminum 1_,17 146 Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter Dehumidification 12-8 23-14 Fan Pulley Pitch Diameter Belt -- Type,.,Length (in,) (in,) (in.) Pulley Center Line Distance (in.) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns from Closed Position Factory Setting -- Full Turns Open Speed Setting 2_.17 165 I (rpm) 4100 V4_1100 320 Lanced Fins 2_,17 165 Double-Wavy I 2.17 21 3 Fins 2._15 5,5 2_15 5.5 4_15 5.5 4_,15 73 1_,17 3,9 2...17 3.9 2_.17 3.9 2_17 5.2 System Std Hi-Static Std Hi-Static Std Hi-Static A/B (in.) Motor Shaft Diameter I Enhanced Copper Tubes, Aluminum Fan Rpm Range Fan Shaft Diameter 560 25 50 115 3500 V4 ..825 180 COIL Motor Frame Size Std Hi-Static Std Hi-Static Std Hi-Static Std Hi-Static Std Hi-Static Std Hi-Static Std Hi-Static Std Hi-Static 1...10 x 10 1200 1.20 2.40 48 56 680-1044 1075-1455 Ball 2100 1.9/2.9 2.8/3.8 l& % 4.5 4.5 1 ...A...36 1 _.A_.39 10.0-12.4 65 65 5 6 3 at Pulley (in.) LEGEND Bhp-- I HJD/E/FO07 6 Propeller EVAPORATOR COIL Standard Unit Rows.,,Finslin, Total Face Area (sq ft) Unit with Humidi-Mizer Adaptive Rows,..Finslin, Total Face Area (sq ft) EVAPORATOR FAN °uantity..,Size (in.) Nominal Cfm Maximum Continuous Bhp Factory I FAN Rows...Fins/in, Total Face Area (sq ft) Nominal HJD/E/F/G/H/K]L/M/NO06 5 540 23 50 115 Acutrol Nominal Cfm Motor Hp...Rpm Watts Input (Total) CONDENSER HJD/E/F/G/H/K]L/M/NO05 4 Brake Horsepower *Single phase/three phase, tlndicates automatic reset, **60,000 and 72,000 Btuh heat input units have 2 burners, 90,000 and 120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners. l-tAn LP kit is available as an accessory. Kit may be used at elevations as high as 2000 ft, If an LP kit is used with Low NOx units, the Low N©x baffle must be removed and the units will no longer be classified as Low N©x units. 31/2 826 1233 % Centrifugal Type, Belt Drive 1...10 x 10 1,.,10 x 10 1600 2000 1.20 1.30/2.40" 2,40 2,90 48 48/56" 56 56 770-1185 1035-1460 1075-1455 1300-1685 Ball Ball 2100 2100 1.9/2.0 2.4/3.4 2.8/3.8 3.4/4,4 1/2 % 5/s 5/8 4.0 4.0 4.0 4.5 1..,A.,.36 1 ..-4-.40 1,_A_.39 1,..A-.40 10.0-12.4 14.7-15.5 7O 75 65 6O 5 6 6 5 3 3 31/2 31/2 936 1248 1233 1396 5/s 5/8 1..,10 x 10 2400 2,40 2,90 56 56 1119-1585 1300-1685 Ball 2100 2,4/3,4 3,4/3,4 5/8 7& 4.0 4.5 1 ..,A,..38 1..,A_.40 14.7-15.5 95 60 5 5 3 1305 1396 5/8 IIThree-phase standard models have heating inputs as shown, Singlephase standard models have one-stage heating with heating input values as follows: HJD005-006,HJE004 -- 72,000 Btuh HJE005-006,HJF004 -- 115,000 Btuh HJF005-006 -- 150,000 Btuh ***California compliant three-phase models. tttCalifornia SCAQMD compliant low NO× models have combustion products that are controlled to 40 nanograms per joule or less, Table 1 -- Physical Data (cont) BASE UNIT 48 HJE/F/H/K]M/N004 FURNACE SECTION Rollout Switch Cutout Temp (F)t Burner Orifice Diameter (in, ..,drill size)** Natural Gas -- Std Liquid Propane -- Alttt Thermostat Heat Anticipator 208/230/460/575 v First Stage Second Stage Gas Input (Btuh) First Stage/Second Stage Efficiency Rise Range Manifold Pressure (in. wg) Natural Gas -- Std Liquid Propane -- Alttt Maximum Static Pressure (in, wg) Field Gas Connection Size (in.) 195 195 HJD.113...33 HJE .113...33 HJF.129-.30 HJD.113.-33 HJE .113.-33 HJF.129-.30 HJH,113-.33 HJK,113-.33 HJG .113...33 HJH.113...33 HJK.129...30 HJG .113...33 HJH .113...33 HJK.129.-30 HJM .102,,.38 HJN.102-.38 HJL.102...38 HJM ,102,..38 HJN.116...32 HJL.102.-38 HJM .102...38 HJN.116-.32 HJE,089.,.43 HJF,089..,43 HJD.089...43 HJE .089...43 HJF.104...37 HJD.089.-43 HJE .089...43 HJF.104...37 HJH,089.,.43 HJK,089-.43 HJG .089...45 HJH .089...45 HJK.102...38 HJG .089...43 HJH .089...43 HJK.104.-37 HJM HJN HJL.082-.45 HJM .082.,.45 HJN.094...42 HJL.082-.45 HJM.082...45 HJN .094.,.42 .082,.,45 ,082,,.45 HJD/E/F007 195 HJE.113...33 HJF,113..,33 ,14 .14 .14 .14 195 HJD,113-,33 HJE ,113-.33 HJF,129.-30 HJD .089_.43 HJE ,089-.43 HJF.104.-37 .14 .14 HJEll50,000/ 72,000 HJFI182,000/115,000 HJDll 50,000/ 72,000 HJEII 82,000/115,000 HJFl1120,000/150,000 HJDII 50,000/ 72,000 HJEII 82,000/115,000 HJFI1120,000/150,000 HJH***--/ 72,000 HJK***--/115,000 HJG***--/ 72,000 HJH*** --/115,000 HJK*** --/150,000 HJG***--/ 72,000 HJH*** --/115,000 HJK*** --/150,000 HJMTTT--/ HJNttt--/ HJLttt --/ 60,000 HJMttt--/ 90,000 HJNttt --/120,000 HJD 82.8 HJE 81 HJF 80.4 HJLttt--/ 60,000 HJMftt--/ 90,000 HJNttt --/120,000 HJD 82.8 HJE 81 HJF 80.4 HJH 82 HJK 80 HJG 82 HJH 81 HJK 80 HJG 82 HJH 81 HJK 80 HJM 80.2 HJN 81 HJL 80.2 HJM 81 HJN 80.7 HJL 80.2 HJM 81 HJN 80.7 HJE 25-55 HJF 55-85 HJD 25-25 HJE 35-65 HJF 50-80 HJD 25-55 HJE 35-65 HJF 50-80 HJH 25-55 HJK 55-85 HJG 25-55 HJH 35-85 HJK 50-80 HJG 25-55 HJH 35-65 HJK 50-80 HJM 20-50 HJN 30-60 HJL 20-50 HJM 30-60 HJN 40-70 RJL 20-50 HJM 30-60 HJN 40-70 60,000 90,000 HJE 82,8 HJF80 3.5 3.5 1.0 3.5 3.5 1.0 RETURN-AIR FILTERS Quantity...Size (in.) LEGEND Brake Horsepower *Single phase/three phase. tlndicates automatic reset. **60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners. ttAn LP kit is available as an accessory. Kit may be used at elevations as high as 2000 ft. If an LP kit is used with Low NOx units, the Low NOx baffle must be removed and the units will no longer be classified as Low N©x units. .14 .14 HJD 50,000/ 72,000 HJE 82,000/115,000 HJF 120,000/150,000 HJD 82 HJE 81 HJF 80 HJD 25-55 HJE 35-65 HJF 50-80 3.5 3.5 1.0 l& 1/2 HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief Cutout Reset (Auto.) LOSS-OF-CHARGE SWITCH/LOW=PRESSURE SWITCH (Liquid Line) (psig) Cutout Reset (Auto.) FREEZE PROTECTION THERMOSTAT Opens (F) Closes (F) OUTDOOR-AIR INLET SCREENS Bhp-- HJD/EIF/GIH/K/LIM/NO06 Setting (amps) (Steady State) (%) Temperature HJD/E/FIGIHIK/L/M/NO05 3.5 3.5 1.0 1/2 450 _+50 428 32O 7_+3 22 _+5 30_+5 45_+5 Cleanable. Screen quantity and size varies with option selected. Throwaway 2._16x25x2 I 4_.16x 16x2 IIThree-phase standard models have heating inputs as shown. Singlephase standard models have one-stage heating with heating input values as follows: HJD005-006,HJE004 -- 72,000 Btuh HJE005-006,HJF004115,000 Btuh HJF005-006150,000 Btuh ***California compliant three-phase models. tttCalifornia SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanegrams per joule or less. BLK _ BLK TO COMP BLK _ TO COMP I ,, 1 YEL I;%F'i' [;% EQUIP GND F--t_I i 1 PI ELD POWER SUPPLY _ .L .L L __ FDISOON.EDT 7 PER NEC 208/230-1-60 L* .... (SIZES 48HJ004-006) BLK i _ I ii J TO COMP ' , 575-3-60 (SIZES 48HJ004, FIELD POWERSUPPLY _ .L.L .L -208/230-3-60460-3-60 _F-DISCONNEcT 7 (SIZES 48HJ004, 005) L.. PERNEC ,{ BLK ---_J ! I TO I TB2 I®®1 LEGEND 1 I 575-3-50 (SIZES48HJ006, FIELD POWER SUPPLY _ ,.L_ .L -,r-D ISCONNECT 7 208/230-3-50 460-3-80 (SIZES 48HJ006, 007) FIELD POWER SUPPLY _I.LL__ [-DI SCONNECT 7 L PE?NEC j L ZE._"_"EC_ : 007) 005) I I I FIELD POWERSUPPLY r -- a-.L L--7 _ DISCONNECT I L .....PER NEC J C COMP EQUIP GND IFC ------ NEC TB --- Contactor Compressor Equipment Ground Indoor (Evaporator) Fan Contactor National Electrical Code Terminal Block Fig. 10 -- Power Wiring Connections m COOL STAGE 1 CONTROL R FAN THERMOSTAT CONNECTION BOARD G CONTROL CONNECTION BOARD Y1 HEAT STAGE 1 COOL STAGE 2 Y/Y2 HEAT STAGE 2 O/W2 24 VAC HOT - • ] f- - I F__J Y2 W1 WIRE CONNECTIONS TO LOW-VOLTAGE SECTION {_ RMTOCC T_i CMPSAFE1 !_ *_1_'- _YY11/_ {£_i '_ {:_) /'W2_ (W2} W2 R (Wl_, SFS 4 NOT USED i , = C 24 VAC COM IPD/X \ / 7 G \ \ / N/A OUTDOOR AIR ( %?x $1 SENSOR Fig. 11 B -- Low Voltage Connections (Units with PremierLink TM Controls) $2 4 THERMOSTAT DIPSWITCH {:::_} SETTINGS ON A B C D RACEWAY LEGEND LOW VOLTAGE INTEGRATED CONNECTIONS CONTROLLER GAS UNIT (IGC) Field Wiring NOTE: Underlined letter indicates active thermostat configured for A/C operation. output when Fig. 11A -- Low-Voltage Connections With or Without Economizer or Two-Position Damper HOLE IN END Fig. 1210 PANEL (HIDDEN) Field Control Wiring Raceway Table 2A -- Electrical Data -- Standard Motor Units Without Electrical Convenience Outlet UNIT 48HJ NOMINAL VOLTAGE (V-Ph-Hz) 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 OO4 (3 Tons) 005 (4 Tons) 006 (5 Tons) 0O7 (6 Tons) VOLTAGE RANGE Min Max 187 254 187 254 414 508 518 632 187 284 187 254 414 508 518 632 187 254 187 284 414 508 518 632 187 254 414 508 518 632 COMPRESSOR (each) Qty RLA LRA 16.0 88.0 10.3 77.0 1 8.1 39.0 4.2 31.0 23.7 126.0 13.5 93.0 1 6.4 46.5 6.4 40.0 28.8 169.0 17.3 123.0 1 9.0 62.0 7.1 50.0 20.5 186.0 1 9.6 75.0 7.7 56.0 OFM (each) FLA 0.7 0.7 0.4 0.4 0.7 0.7 0.4 0.4 1.5 1.5 0.8 0.8 1.4 0.6 0.6 IFM FLA 4.9 4.9 2.2 2.2 4.9 4.9 2.2 2.2 8.8 5.8 2.6 2.6 5.8 2.6 2.6 COMBUSTION FAN MOTOR FLA .60 .60 .30 .30 .60 .60 .30 .30 .60 .60 .30 .30 .60 .30 .30 POWER SUPPLY* MCA 25.6/25.6 18.5/18.5 9.0 7.3 35.2/35.2 22.5/22.8 10.6 10.1 46.3/46.3 28.9/28.9 14.7 11.6 32.8/32.8 15.2 12.2 MINIMUM UNIT DISCONNECT SIZEt FLA LRA 25/25 101/101 18/18 90/90 9 46 7 37 34/34 139/139 22/22 106/106 10 54 10 46 45/45 216/216 28/28 168/168 14 84 12 68 32/32 200/200 15 97 12 74 MOCP** 30/30 25/25 20 20 45/45 30/30 20 20 60/60 38/35 20 20 40/40 20 20 Table 2B -- Electrical Data -- Standard Motor Units With Electrical Convenience Outlet UNIT 48HJ NOMINAL VOLTAGE (V-Ph-Hz) 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 004 (3 Tons) 005 (4 Tons) 006 (5 Tons) 007 (6 Tons) VOLTAGE RANGE Min Max 187 254 187 254 414 508 818 632 187 284 187 254 414 508 518 632 187 284 187 254 414 508 518 632 187 284 414 508 518 632 COMPRESSOR (each) Qty RLA LRA 16.0 88.0 10.3 77.0 1 5.1 39.0 4.2 31.0 23.7 126.0 13.5 93.0 1 6.4 46.5 6.4 40.0 28.8 169.0 17.3 123.0 1 9.0 62.0 7.1 50.0 20.5 156.0 1 9.6 75.0 7.7 56.0 OFM (each) FLA 0.7 0.7 0.4 0.4 0.7 0.7 0.4 0.4 1.5 1.5 0.8 0.8 1.4 0.6 0.6 IFM FLA 4.9 4.9 2.2 2.2 4.9 4.9 2.2 2.2 8.8 5.8 2.6 2.6 8.8 2.6 2.6 LEGEND FLA HACR --- IFM LRA MCA MOCP NEC OFM RLA UL --------- *The right tUsed **Fuse COMBUSTION FAN MOTOR FLA .60 .60 .30 .30 .60 .60 .30 .30 .60 .60 .30 .30 .60 .30 .30 Determine maximum (AB) 457 - 482 = (BC) 464 - 487 = (AC) 487 -488 = Maximum deviation Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps Underwriters' Laboratories Determine = 1.83% This amount of phase imbalance mum allowable 2%. I _) as it is below the maxi- 2%, contact your local electric utility phase company immediately. MPORTANT: If the supply voltage imbalance is more than POWER EXHAUST PART NO. CRPWREXH021A01 CRPWREXH022A01 CRPWREXH023A01 CRPWREXH028A01 CRPWREXH029A01 CRPWREXH030A01 N/A -- max voltage deviation from average voltage average voltage EXHAUST ELECTRICAL DATA MCA MCA MCA (230 v) N/A 3.3 N/A 1.7 N/A 1.6 (460 v) 0.9 N/A 1.8 N/A 1.0 N/A (575 v) N/A 1.32 N/A 0.68 N/A 0.64 MOCP (for separate power source) 15 15 15 15 15 15 Not available NOTE: If a single power source is to be used, size wire to include power exhaust MCA and M©CR Example: Supply voltage is 460-3-60. C is satisfactory See table at NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker. 2. Electrical data based on 95 F ambient outdoor-air temperature _+10% voltage. 3, Unbalanced 3-Phase Supply Voltage Never operate a motor where pbase imbalance in supply voltage is greater than 2%. Use the following formula to determine the pereent voltage imbalance. % Voltage Imbalance B deviation from average voltage. 5v 7 v 2 v is 7 v. percent of voltage imbalance. 7 = 100x POWER A MINIMUM UNIT DISCONNECT SIZEt FLA LRA 30/30 106/106 24/24 98/98 11 48 9 38 39/39 144/144 27/27 111/111 13 56 12 47 50/50 221/221 34/34 173/173 17 87 13 70 37/37 205/205 17 99 14 75 % Voltage Imbalance values listed in this table do not include power exhaust. for power exhaust requirements. to determine minimum disconnect per NEC. or HACR circuit breaker. = 100 x POWER SUPPLY WITH OUTLET* MCA MOCP** 31.6/31.6 38/38 24.5/24.5 30/30 11.7 20 9.5 20 41.2/41.2 50/80 28.8/28.5 35/35 13.3 20 12.2 20 52.3/52.3 60/60 34.9/34.9 40/40 17.4 20 13.8 20 38.8/38.8 45/45 17.9 20 14.3 20 Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: AB = 452 V BC = 464 v Average Voltage = AC = 455 v MCA New = MCA unit only + MCA of Power Exhaust For example, using a 48HJD006---5 unit with MCA = 28.9 and MOCP = 35. with CRPWREXH030A01 power exhaust. MCA New = 28.9 amps + 1.6 amps = 30.5 amps If the new MCA does not exceed the published MOCE then M©CP would net change. The MOCP in this example is 35 amps and the MCA New is below 35; therefore the MOCP is acceptable. If "MCA New" is larger than the published MOCE raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC. 452 + 464 + 455 3 1371 3 = 457 )) II Table 20 -- Electrical Data -- High-Static Motor Units Without Electrical Convenience Outlet NOMINAL VOLTAGE UNIT 48HJ (V-Ph-Hz) Min Max 208/230-3-60 187 284 460-3-60 414 508 575-3-60 518 632 208/230-3-60 187 254 460-3-60 414 508 875-3-60 818 632 208/230-3-60 187 254 460-3-60 414 508 575-3-60 518 632 208/230-3-60 187 254 460-3-60 414 508 575-3-60 518 632 O04 005 006 007 COMPRESSOR (each) VOLTAGE RANGE Qty RLA 10.3 5.1 4.2 13.5 6.4 6.4 17.3 9.0 7.1 20.5 9.6 7.7 1 1 1 1 OFM (each) LRA 77.0 39.0 31.0 93.0 46.5 40.0 123.0 62.0 50.0 156.0 75.0 56.0 FLA 0.7 0.4 0.4 0.7 0.4 0.4 1.5 0.8 0.8 1.4 0.6 0.6 IFM COMBUSTION FAN MOTOR FLA 5.8 2.6 2.6 5.8 2.6 2.6 7.5 3.4 3.4 7.5 3.4 3.4 MINIMUM UNIT DISCONNECT SIZEt FLA LRA 19 120 9 60 8 48 23 136 11 68 10 57 30 187 15 94 12 76 34 219 16 107 13 81 POWER SUPPLY* RLA 0.6 0.3 0.3 0.6 0.3 0.3 0.6 0.3 0.3 0.6 0.3 0.3 MCA 19.4 9.4 7.7 23.4 11.0 10.4 30.6 15.5 12.2 34.8 16 12.8 MOCP** 28 20 20 30 20 20 35 20 20 40 20 20 Table 2D -- Electrical Data -- High-Static Motor Units With Electrical Convenience Outlet UNIT 48HJ VOLTAGE RANGE NOMINAL VOLTAGE (V-Ph-Hz) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 004 005 006 007 FLA HACR --- IFM LRA --- MOCP NEC OFM MCA RLA UL ------- Min 187 414 518 187 414 518 187 414 518 187 414 518 COMPRESSOR (each) Max 254 508 632 254 508 632 254 508 632 254 508 632 Qty RLA 10.3 5.1 4.2 13.8 6.4 6.4 17.3 9.0 7.1 20.5 9.6 7.7 1 1 1 1 LRA 77.0 39.0 31.0 93.0 46.5 40.0 123.0 62.0 50.0 156.0 75.0 56.0 OFM (each) IFM FLA 0.7 0.4 0.4 0.7 0.4 0.4 1.5 0.8 0.8 1.4 0.6 0.6 FLA 5.8 2.6 2.6 5.8 2.6 2.6 7.5 3.4 3.4 7.5 3.4 3.4 LEGEND Maximum Determine = 1.53% C @ I1__ ,w_,la I See table at is satisfactory as it is below the maxi- 2%, contact your local electric utility phase company immediately. MPORTANT: If the supply voltage imbalance is more than POWER POWER EXHAUST PART NO, CRPWREXH021A01 CRPWREXH022A01 CRPWREXH023A01 CRPWREXH028A01 CRPWREXH029A01 CRPWREXH030A01 EXHAUST ELECTRICAL DATA MCA (230 v) MCA (460 v) MCA (875 v) N/A 3.3 N/A 1.7 N/A 1.8 0.9 N/A 1.8 N/A 1.0 N/A N/A 1.32 N/A 0.88 N/A 0.84 MOCP (for separate power source) 15 15 15 15 15 15 N/A -- Not available NOTE: If a single power source is to be used, size wire to include power exhaust MCA and MOCR Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the following formula: max voltage deviation from average voltage average voltage Example: Supply voltage is 460-3-60. c MOCP** 30 20 20 35 20 20 40 20 20 45 25 20 deviation is 7 v. This amount of phase imbalance mum allowable 2%. NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The UL. Canada units may be fuse or circuit breaker. 2. Electrical data based on 95 F ambient outdoor-air temperature _+10% voltage. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the pement voltage imbalance. % Voltage Imbalance B MCA 28.4 12.1 9.8 29.4 13.7 12.6 36.6 18.2 14.4 40.5 18.7 15.0 percent of voltage imbalance. 7 % Voltage Imbalance = 100 x 4_ Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Minimum Circuit Rated Load AmpsAmps Underwriters' Laboratories = 100 x MINIMUM UNIT DISCONNECT SIZEt FLA LRA 28 124 12 63 10 50 29 140 13 70 12 59 36 192 18 96 14 77 39 224 18 109 15 83 POWER SUPPLY* RLA 0.6 0.3 0.3 0.6 0.3 0.3 0.6 0.3 0.3 0.6 0.3 0.3 Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps *The values listed in this table do not include power exhaust. right for power exhaust requirements. l-Used to determine minimum disconnect per NEC. **Fuse or HACR circuit breaker. A COMBUSTION FAN MOTOR MCA New = MCA unit only + MCA of Power Exhaust For example, using a 48HJD006---5 unit with MCA = 28.9 and MOCP = 38, with CRPWREXH030A01 power exhaust. AB = 452 v BC = 464 v MCA New = 28.9 amps + 1.6 amps = 30.5 amps (_ Average Voltage = AC = 455 v 452 + 464 + 458 3 If the new MCA does not exceed the published MOCE then MOCP would not change. The M©CP in this example is 35 amps and the MCA New is below 35; therefore the M©CP is acceptable. If "MCA New" is larger than the published MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for the power exhaust will be 15 amps per NEC. 1371 3 = 457 Determine maximum deviation from average voltage. (AB) 457 - 482 = 8 v (BC) 464 - 457 = 7 v (AC) 487 - 488 = 2 v )2 I I Step 8 -- Adjust Factory-Installed Options COBRA TM ENERGY RECOVERY UNITS -- Please lefer to the supplement provided for information on installing and operating the factory optional COBRA Energy Recovery Units. These units are equipped with a factou-installed energy recove U unit and have different installation and operation procedums than the stan&u'd unit. HUMIDI-MIZER TM ADAPTIVE DEHUMIDIFICATION SYSTEM--Humidi-MiZer system operation can be controlled by field installation of a Carrie>approved humidistat (Fig. 13). NOTE: A light commercial Thermidistat TM device (Fig. 14) can be used instead of the humidistat if desimdi The Thermidistat device includes a thermostat and a humidistat. The humidistat is norm',flly used in applications where a temperature sensor is already provided (units with PremierLink TM control). To install the humidistat: Fig. 13- Accessory Field-Installed Humidistat 1. Route humidistat cable through hole provided in unit comer post. 2. Feed wires through the raceway built into the corner post to the 24-v bamer located on the left side of the control box. See Fig. 12. The raceway provides the UL-mquimd clemance between high-voltage and low-voltage wiring. 3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 15. To install Thermidistat device: 1. Route Thermidistat cable through hole provided in unit corner post. 2. Feed the wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 12. The raceway provides the UL-required clearance between high and low voltage wiring. Fig. 14 -- Light Commercial Thermidistat Device 3. Remove evaporator coil access panel. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws. 4. Replace ewtporator coil access panel. 5. Place hood on front of outdoor air opening panel. See Fig. 18 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 19. 6. Remove and save 6 screws (3 on each side) from sides of the manual outdoo>air &_mpel: 7. Align screw holes on hood with screw holes on side of manual outdoo>air dampel: See Fig. 18 and 19. Secure hood with 6 screws from Step 6. 8. Adjust minimum position setting of the damper blade by adjusting the manual outdoo>air adjustment screws on the fiont of the dmnper blade. See Fig. 17. Slide blade vertically until it is in the appropriate position determined by Fig. 20. Tighten screws. 9. Remove and save screws cunently on sides of hood. Insert screen. Secure screen to hood using the screws. See Fig. 19. 3. A field-supplied relay must be installed between the thermidistat and the Humidi-Mizer circuit (recommended relay: HN612KK324). See Fig. 16. The relay coil is connected between the DEHUM output and C (common) of the unit. The relay controls the Humidi-MiZer solenoid valve and must be wired between the Humidi-MiZer fuse and the low-pressure switch. Refer to the installation instructions included with the Carrier Light Commercial Thermidistat device for more information. MANUAL OUTDOOR-AIR DAMPER -- The outdoor-air hood and screen me attached to the basepan at the bottom of the unit for shipping. Assemb122: 1. Determine quantity of ventilation required for building. Record amount for use in Step 8. 2. Remove and save outdoor air opening panel and screws. See Fig. 17. 13 BIU BLK _TRAN 3.2 AHPS _REO I LSV] PNK •_1_" CB CR DHR DSV HR LPS LSV LTLO --------- L ILO P NK"O-_-.,,_OP NK Circuit Breaker LEGEND Cooling Relay Dehumidify Relay Discharge Solenoid Valve Heater Relay Low Pressure Switch Liquid Solenoid Valve Low Temperature Lockout O IIR1 "I CRI Term,ha, (_-n:]: d_LPN<'_ BLU_LBLK'E_BLK"_LBV2 I'm _ OR2 Splice Factory BRN--_ 1 P _LPS1 K ke • BLK _BLK I--.Z.J BRN __ _ Wiring Field Control i,_ BL U,_ _'_ I _ 0RN "_3L DSV2 p LPS2 / 6"E_BLU'_O_BLUJ Wiring ..T--BRN-*, 0R"; TB Field Power Wiring I_:x_-- Field Splice Fig. 15- Typical Humidi-MiZer TM Adaptive Dehumidification Humidistat Wiring (208/230-V Unit Shown) LCT System ROOFTOPUNIT //7-- -- ...... EE]- TSTATWIRES PINK _RE_D_ 24V R1 PINK_ . FROM LEGEND CB LCT LLSV LTLO -i i i Circuit Breaker Light Commercial Thermidistat Liquid Line Solenoid Valve Low Temperature Lockout HUMIDI-MIZER LLSV TM Device HUMIDI-MIZER SYSTEM Fig. 16- Typical Rooftop Unit with Humidi-Mizer Adaptive Dehumidification System with Thermidistat Device OUTDOOR AIR OPENING PANEL HOOD TOP SCREWS 3 SCREWS (HIDDEN) (SIDE) _ _ MANUAL OUTDOOR-AtR ADJUSTMENT SCREWS SCREWS (SCREEN HOLDERS) _/ POSITION SCALE SE_ING HOOD SIDES AND TOPASSEMBLED DAMPER BLADE Fig. 17 -- Damper Panel with Manual Outdoor-Air Damper Installed HOOD SIDE Fig. 18 -- Outdoor-Air Hood Details 14 SYSTEM unoccupied). No sensors are supplied with the field-mounted PremierLink control. The factory-installed PremierLink control includes only the supply-air temperature (SAT) sensor and file outdoor air temperature (OAT) sensor as stan&lrd. An indoor air quality (CO2) sensor can be added as an option. Refer to Table 3 for sensor usage. Refer to Fig. 22 for PremierLink controller wiring. The PremierLink control may be mounted in the control panel or tin mea below the control panel. NOTE: PremierLink controller versions 1.3 and later are shipped in Sensor mode. If used with a thermostat, the PremierLink controller must be configured to Thermostat mode. SCREW HOLES (TOP) HOOD_ SCREEN LOCATIOK (SCREEN NOT SHOWN) Insttfll file Supply Air Temperature (SAT) Sensor -- When the unit is supplied with a factory-mounted PremierLink control, the supply-air temperature (SAT) sensor (33ZCSENSAT) is factory-supplied and wired. The wiring is routed from the PremierLink control over the control box, flirough a grommet, into the fan section, down along the back side of the fan, and along the fan deck over to the supply-air opening. Fig. 19 -- Outdoor-Air Damper with Hood Attached 0.6 The SAT probe is wire-tied to file supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of file supply-air opening or in the supply air duct (as required by local codes). Drill or punch a l/2-in, hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. 0.5 _" 0,4 UI o3 NOTE: The sensor must be mounted in the dischmge airstream downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with tiny of the unit or heat surfaces. 03 LU m 13. LU 0.3 > 0.2 Outdoor Air Temperature (OAT) Sensor -- When the unit is supplied with a factoly-mounted PremierLink control, the outdoor-air temperature (OAT) sensor is factory-supplied and wired. Z Install the Indoor Air Quality (COe) Sensor -optional indoor air quality (CO2) sensor according turer specifications. o o 1 2 3 4 5 6 7 A separate field-supplied er the CO2 sensoc OUTDOOR AIRFLOW (cfm x 100) Fig. 20 -- Outdoor-Air CONVENIENCE OUTLET let provides power for rooftop safety, the convenience outlet connect is off. Adjacent unit tool s. Damper Position Setting transformer Mount the to manufac- must be used to pow- Wire the CO2 sensor to the COM and IAQI terminals of J5 on the PremierLink controllec Refer to the PremierLink Installation, Start-up, and Configuration Instructions for detailed wiring and configuration information. Enthalpy Sensors and Control -- The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the EconoMiSer2 damper control option. The outdoor air enthalpy sensor is part of the enthalpy control. The septu'ate field-installed accessory return air enthalpy sensor (HH57AC078) is required for differentkd enthalpy control. -- An optiomfl convenience outuse. For maintenance personnel power is off when the unit disoutlets may be used for service NOVAR CONTROLS -- Optiomd Novar controls (ETM 3051 ) me available for replacement or new construction jobs. PREMIERLIN K TM CONTROL -- The PremierLink controller is compatible with Carrier Comfort Network® (CCN) devices. This control is designed to tdlow users the access and ability to change factory-defined settings, thus expanding the function of file standmd unit control board. Carder's diagnostic standard tier display tools such as Navigato( r_'_ or Scrolling Marquee can be used wifli the PremierLink controllec The PremierLink controller (see Fig. 21A and 21B) requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessmy for broadcast of time of &ty functions (occupied/ NOTE: The enthalpy control must be set to the "D" setting for differential enthalpy control to work properly. The enthtdpy control receives the indoor and return enthalpy from the outdoor and return air enthtdpy sensors and provides a @ contact switch input to the PremierLink controllec Locate the controller in place of an existing economizer controller or near the actuatoc The mounting plate may not be needed if existing bracket is used. A closed contact indicates that outside air is preferred to the return aic An open contact indicates that the economizer should remain tit minimum position. 15 Table 3OUTDOOR TEMPERATURE APPLICATION Differential AIR SENSOR PremierLink RETURN TEMPERATURE TM Sensor Usage AIR SENSOR OUTDOOR AIR ENTHALPY SENSOR RETURN AIR ENTHALPY SENSOR -- -- Dry Bulb Temperature with PremierLink* (PremierLink requires 4-20 mA Actuator) Required -33ZCT55SPT Included -CRTEMPSN001A00 or Equivalent Single Enthalpy with PremierLink* (PremierLink requires 4-20 mA Actuator) Included -Not Used -- orHH57AC077Equivalent Differential Enthalpy with PremierLink* (PremierLink requires 4-20 mA Actuator) Included -Not Used -- Required -HH57AC077 or Equivalent Required --- Required -HH57AC078 or Equivalent *PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature sensor CRTEMPSN001A00 -- Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control. NOTES: 1. CO2 Sensors (Optional): 33ZCSENCO2 -- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 -- Aspirator box used for duct-mounted CO2 room sensor. 33ZCT55CO2 -- Space temperature and CO2 room sensor with override. 33ZCT56CO2 -- Space temperature and CO2 room sensor with override and set point. 2. All units include the following Standard Sensors: Outdoor-Air Sensor -- 50HJ540569 -- Opens at 67 F, closes at 52 F, not adjustable. Mixed-Air Sensor -- HH97AZ001 -- (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature Sensor CRTEMPSN001A00) Compressor Lockout Sensor -- 50HJ540570 -- Opens at 35 F, closes at 50 E HVAC SENSOR INPUTS 0 0 ( SL DUAL MODE SENSOR/STAT REMOTE OCCUPANCY COMP SAFETY (Y1) ._ FIRE SHUTDOWN (Y2) Z SUPPLY FAN STATUS (Wl) NOT USED ENTHALPY STATUS (ENTk / CCN/LEN PORT NAVIGATOR PORT ,/ 4-20MA ECONOMIZER t INDOOR FAN MOTOR "4 "-4 "-.. COMPR 1& 2 OUTPUTS Fig. 21A -- PremierLink Controller 16 HEAT LOW/HIGH EXHAUST RVSVALVE ©© PREMIERLINK CONTROL HINGED DOOR PANEL PREMIERLINK COVER Fig. 21B -- PremierLink OUTD_R AiR i ' GRAY SENSOR Comm [ : • BLK i i RED, Economi$er2 4 - 20mA Controller (Installed) ' CCN ENTHALPY TM [ 7F" _ \L_ 6(]t G w_ WHT 8_[).............. .... BLK 7 ",C '_(][j ............................................................................................................. 8 _-lhX LEGEND : [ ::::::::Q 0 0 _" RETURN AIR ENTHALPY SENSOR COMMS OAT PWR RTU SAT TB ------- \ Communications Outdoor Air Temperature Sensor Power Rooftop Unit Supply Air Temperature Sensor Terminal Block Fig. 22 -- Typical PremierLink Controls ]7 / RTU Terminal Board Wiring Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) -- To wire the outdoor tfir enthalpy sensor. perform the following (see Fig. 23 and 24): NOTE: The outdoor air sensor can be removed from the back of the enth_dpy controller and mounted remotely. 1. Use a 4-conductor. 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power tmnsformec 2. 2. Connect the following 4 wires from the wire hmness located in rooftop unit to the enthalpy controller: a. Connect the BRN wire to the 24 vac terminal (TRI) on enthalpy control and to pin 1 on 12-pin harness. b. Connect the RED wire to the 24 vac GND terminal (TR) on enth_dpy sensor and to pin 4 on 12-pin hmness. c. Connect the GRAY/ORN wire to J4-2 on PremierLink controller and to terminal (3) on enthalpy sensoc d. Connect the GRAY/RED wire to J4-1 on PremierLink controller and to terminal (2) on enthalpy sensoc The box with the economizer hood components is shipped in the compartment behind the economizer The EconoMiSer IV controller is mounted on top of the EconoMiSer [V in the position shown in Fig. 25. The optiomd EconoMiSer2 with 4 to 20 mA actuator signal control does not include the EconoMi$er IV controllec To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizec Slide the hood box out of the unit. See Fig. 28. HH57AC077 ENTHALPY CONTROL AND OUTDOOR AIR ENTHALPYSENSOR HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION) NOTE: [f installing in a Carrier rooftop, use the two gray wires provided from the control section to the economizer to connect PremierLink controller to terminals 2 and 3 on enth_dpy sensoc Return Air Enthalpy Sensor -- Mount the return-air enthalpy sensor (HH57AC078) in the return-air duct. The return air sensor is wired to the enth_dpy controller (HH57AC077). The outdoor enth_dpy changeover set point is set at the controller. To wire the return air enthalpy sensor perform the following (see Fig. 23): 1. Use a 2-conductor, 18 or 20 AWG. twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller. 2. At the enthalpy control remove the factory-installed resistor from the (SR) and (+) termimds. 3. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enth_dpy controllel: Connect the BLK wire to (S) spade connector on the return air enthalpy sensor and the (SR) terminal on the enthalpy controller OPTIONAL ECONOM[$ER IV AND ECONOM[$ER2 -See Fig. 25 for EconoMiSer IV component locations. See Fig. 26 for EconoMiSer2 component locations. MOUNTING PLATE Fig. 24 -- Differential Enthalpy Control, Sensor and Mounting Plate (33AMKITENT006) EOOv Oo E OUTSIDE TEMPERATURE ........ g ACTUATOR AIR AI / / LOWAMO,ENT HARNESS _ ,_ _r,_ Y ,_= / SENSOR SENSOR / NOTE: These instructions are for installing the optiomd EconoMiSer IV and EconoMi$er2 only. Refer to the accessory EconoMiSer IV or EconoMiSer2 inst_dlation instructions when field installing an EconoMiSer [V or EconoMi$er2 accessory. 1. To remove the existing unit filter access panel, rgfise the panel and swing the bottom outwmd. The panel is now disengaged from the track and can be removed. See Fig. 27. BRN RED SRCq+D- ---q Fig. 25 -- EconoMi$er 0 IV Component _ -/ Locations OUTDOOR AIR HOOD A6O soO +13-- TRra']TRI__ ENTHALPYCONTROLLER x_ BLK r_ t ENTHALPY (OUTDOORAIR SENSOR) RED ' FIs (RETURNAIRI FI + -- ECONOMI$ER2_ HOOD ENTHALPY SENSOR BRACKET GRAY/ORN PWO ,,.WIRE HARNESS LED GRAY/RED jIN UNIT NOTES: 1. Remove factory-installed jumper across SR and + wires from return air sensor. 2. Switches shown in high outdoor air enthalpy state. close on low outdoor air enthalpy relative to indoor air 3. Remove sensor mounted on back of control and airstream. before connecting Terminals 2 and 3 enthalpy. locate in outdoor / BAROMETRIC RELIEF DAMPER Fig. 23 -- Outdoor and Return Air Sensor Wiring Connections for Differential Enthalpy Control GEAR DRIVEN DAMPER Fig. 26 -- EconoMi$er2 Component Locations 18 FILTER ACCESS PANEL SIDE PANEL _COMPRESSOR ACCESS PANEL OUTDOOR-AIR INDOOR COIL Fig. 27- Typical Access OPENING AND ACCESS PANEL TOP SIDE PANEL Panel Locations N INDOOR COIL ACCESS PANEL INDOOR COIL ", "', PANEL Fig. 29 -- Indoor Coil Access Panel Relocation HOOD BOX BRACKET i I ii 11 II TOP PANEL iI I I I INDOOR ACCESS I / 0 COIL PANEL 1I i I Fig. 28- LEFT Hood Box Removal SIDE installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter I IMPORTANT: If the power exhaust accessory is to be for use in the power exhaust hood assembly. 3. 4. 5. 6. 7. 8. 9. 10. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 29. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the sclews provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 30. HOOD Fig. 30 -- DIVIDER Outdoor-Air Hood Construction 17 1/4" Remove the shipping tape holding the economizer barometric relief &_mper in place. Insert the hood divider between the hood sides. See Fig. 30 and 31. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom tilter rock for file aluminum filter. Open the tilter clips which are located underneath the hood top. Insert the aluminum tilter into the bottom tilter rack (hood divider). Push the tilter into position past the open filter clips. Close the filter clips to lock the tilter into place. See Fig. 31. Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 29. Replace the filter access panel. Install all EconoMi$er IV accessories. wiring is shown in Fig. 32. EconoMi$er2 in Fig. 33. HOOD ALUMINUM FI_ER EconoMi$er IV wiring is shown BAROMETRIC RELIEF FILTER CLIP Barometric flow capacity is shown in Fig. 34. Outdoor air leakage is shown in Fig. 35. Return air pressure drop is shown in Fig. 36. Fig. 31 -- Filter Installation 19 FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK / 8LK ECONO_I ZZR MOTOR (F]ELD ACCESSORY) REMOTE MI_ POSiI[O_ POT WHT_ REO IR_M0_FOT 71_ 0_-m}-- PL6-R FOR STD UNIT IAO SEICSOR FIELD ]ICSTALLED _ _ --GRyJ (R0f OAr TEMPI E_T_AL_Y DE_SOR USED} RED L_ -/FIELD ACCESDORYI RAT/ENrHAIPY SE_DOR 2_ BLU FIELD FIELD SPLICE, 3_ E SPLICE BRN 4< IROT gSEOl TAN 5_ GRY 9_ ORG TO LEGEND DCV-IAQ -LA -OAT-POT-RAT-- Demand Controlled Ventilation Indoor Air Quality Low Ambient Lockout Device Outdoor-Air Temperature Potentiometer Return-Air Temperature PWR EXHAUST ACCESSORY Potentiometer Defaults Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting (_of USED} !_ NOTES: 1. 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb. 2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded. 3. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position. Fig. 32 -- EconoMi$er IV Wiring BLACK 4 3 5 f 2 500 OHM _[_>1 8 RESISTOR? J NOTE 1 T o I I '_RUN - e--II NOTE3 J -{- III-- I .... _ I I I i I VIOLET 7 RED 1 J 10 I I 50HJ540573 ACTUATOR ASSEMBLY 6 PINK s OPTIONAL CO2 SENSOR 4 - 20 mA OUTPUT 11 W >- 9 WHITE DIRECT DRIVE ACTUATOR 12 ECONOMIZER2 NOTES: 1. Switch on actuator must be in run position for economizer to operate, 2. PremierLink TM control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 enthalpy sensor. 3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor, Fig. 33 -- EconoMi$er2 with 4 to 20 mA Control Wiring 20 PLUG dry bulb sensor or HH57A077 2500 W z 2000 w 1500 W m SUPPLY AIR TEMPERATURE SENSOR MOUNTING f 1000 o I 500 LOCATION 0 Z 0.05 0] 15 STATIC 0.25 PRESSURE SUPPLY AIR TEMPERATURE SENSOR (in. wg) Fig. 34 -- Barometric Flow Capacity v Fig. 37 -- Supply Air Sensor Location "5 30 LU h- z_ 25 cc 20 Table 4 -- Supply Air Sensor Temperature/ Resistance Values LU D_ I-- 15 LU LU EL 10 Ca 5 © z 0 D TEMPERATURE -58 0.13 0.20 0.22 0.25 STATIC LL 0.30 0.35 PRESSURE Fig. 35 -- Outdoor-Air 0.40 0.45 0.50 (in. wg) Damper Leakage 6ooe w 500_ Z m 400_ w 3000 w w L © 2000 100_ Z 0 S RESISTANCE (ohms) 200,250 -40 -22 q D (F) 0.05 0.10 0.15 0.20 0.25 0.30 0.35 L STATIC PRESSURE (in. wg) Fig. 36 -- Return-Air Pressure Drop ECONOMI$ER IV STANDARD SENSORS ECONOMISER Outdoor Air Temperature (OAT) Sensor -- The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMiSer IV can be used for free cooling. The sensor is factory-installed on the EconoMiSer IV in the outdoor airstream. See Fig. 25. The operating range of temperature measurement is 40 to 100 E -4 14 29,091 16,590 32 50 68 9,795 5,970 3,747 77 86 3,000 2,416 104 122 140 1,597 1,080 746 158 176 525 376 185 194 321 274 212 230 203 153 248 257 116 102 266 284 89 70 302 55 IV CONTROL MODES IMPORTANT: The optional EconoMiSer2 does not include a controllel: The EconoMiSer2 is operated by a 4 to 20 mA signN from (such as PremierLink information. an existing TM control). field-supplied See Fig. 33 controller for wiring Determine fl3e EconoMiSer IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 5. The EconoMiSer IV is supplied from the factory with a supply air temperature sensor and an outdoor air temperature sensol: This allows for operation of the EconoMiSer IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for diffelent types of changeover control and operation of the EconoMiSer IV and unit. Supply Air Temperature (SAT) Sensor -- The supply air temperature sensor is a 3 K themristor located at the inlet of the indoor fan. See Fig. 37. This sensor is factory installed. The operating range of temperature measurement is 0 ° to 158 E See Table 4 for sensor temperature/resistance v_dues. The temperature sensor looks like an eyelet terminal wires running to it. The sensor is located in the "crimp and is sealed fi_m moisture. 100,680 53,010 with end" Outdoor Air Lockout Sensor -- The EconomiSer IV is equipped with an mnbient temperature lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42 F ambient temperature. See Fig. 25. Outdoor DLy Bulb Changeover -- The standard controller is shipped from the facto q configured for outdoor dlT bulb changeover control. The outdoor air and supply air temperature sensors tue included as stan&ud. For this control mode, the 21 outdoor temperature is comptu'ed to anadjustable setpoint selected onthecontrol. If theoutdoor-air temperature isabove thesetpoint,theEconoMiSer IV will adjusttheoutside air dmnpers tominimum position. If theoutdoor-air temperature is below thesetpoint,theposition oftheoutdoor airdampers will becontrolled toprovide fleecooling usingoutdoor air.When inthismode, theLEDnexttofilefreecooling setpointpotentiometer will beon.Thechangeover temperature setpointis controlled bythefreecooling setpointpotentiometer located onthecontrol. See Fig.38.Thescale onthepotentiometer isA, B,C,andD. SeeFig.39fortheconesponding temperature changeover values. 19 ,, i [ 17 16- _ LED ON -LED OF[ 15 _LED ON 13 _m. 12 LED ON-- -- 11 10 LED OFF I 9 Differential Dry Bulb Control -- For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number CRTEMPSN002A00). Tile accessory sensor must be mounted in the return ailstream. See Fig. 40. Wiring is provided in the EconoMiSer IV wiring harness. See Fig. 32. 4O 46 5O 55 60 65 70 75 80 85 90 Accessories Outdoor Air Dry Bulb Differential Dry Bulb Single ECONOMI$ER _ CONTROLLER / AIR _ GROMMET I , I I HH57AC078 HH57AC078 and CRENTDIF004A00* SENSOR _f_- RETURNAIR RETURN DUCT (FIELD-PROVIDED) CO2 for DCV Control using a Wall-Mounted CO2 Sensor 33ZCSENCO2 Fig. 40 -- Return Air Temperature or Enthalpy Sensor Mounting Location and 33ZCASPCO2** 33ZCSENCO2t CRCBDIOX005A00tt I_ I Outdoor Enthalpy Changeover -- For enthalpy control, accessory enthalpy sensor (p_u-t number HH57AC078) is required. Replace the standard outdoor @ bulb temperature sensor with file accessory enthalpy sensor in the same mounting location. See Fig. 25. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoorair damper moves to its minimum position. Tile outdoor enthalpy changeover set point is set with the outdoor enth_dpy set point potentiometer on file EconoMiSer IV controllel: The set points are A, B, C, and D. See Fig. 41. The factory-installed 620-ohln jumper must be in place across terrainals SR and SR+ on file EconoMiSer IV controllel: See Fig. 25 and 42. *CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. t33ZCSENCO2 is an accessory CO2 sensor. **33ZCASPCO2 is an accessory aspirator box required for ductmounted applications. ttCRCBDiOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories. EXHAUST FAN SET POINT LED LIGHTS WHEN EXHAUST CONTACT IS MADE Differential Enthalpy Control -- For differential enthalpy control, the EconoMiSer IV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return air duct. The EconoMiSer IV controller compmes file outdoor air enthalpy to the return air enthalpy to determine EconoMi$er IV use. Tile controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when file outdoor air has a lower enthalpy than the return air. the EconoMi$er IV opens to bring in outdoor air for free cooling. MINIMUM DAMPER POSITION SETTING MAXIMUM DAMPER _ DEMAND CONTROL VENTILATION SET POINT LED LIGHTS WHEN_ DEMAND CONTROL VENTILATION INPUT ISABOVE SET POINT DEMAND CONTROL VENTILATION SET POINT LED LIGHTS WHEN Replace the standard outside air dry bulb temperature sensor with file accessory enthalpy sensor in the same mounting location. See Fig. 25. Mount the return air enthalpy sensor in the return air duct. See Fig. 40. Wiring is provided in the EconoMiSer IV wiring harness. See Fig. 32. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMiSer IV controllel: When AIR IS FREE COOLING SUITABLE FOR CHANGEOVER Fig. 38 -- 7 Required CRTEMPSN002A00* Differential Enthalpy OUTDOOR ]_ ECONOMI$ER None. The outdoor air dry bulb sensor is factory installed. Enthalpy CO2 for DCV Control using a Duct-Mounted CO2 Sensor 100 Fig. 39 -- Outside Air Temperature Changeover Set Points Table 5 -- EconoMi$er IV Sensor Usage ECONOMI$ER IV WITH OUTDOOR DRY BULB SENSOR "% DEGREES FAHRENHEIT In this mode of operation, the outdoor-air temperatme is compared to the return-air temperature and the lower temperature airsheam is used for cooling. When using this mode of changeover control, turn the enthalpy setpoint potentiometer fully clockwise to the D setting. See Fig. 38. APPLICATION 95 ENTHALPY SET POINT EconoMiSer IV Controller and LED Locations Potentiometer 22 usingthismode of changeover control, turntheenthalpy setpointpotentiometer fullyclockwise totheD setting. AQI terminals of file controller Adjust the DCV potentiometers to correspond to the DCV voltage output of file indoor air quality sensor at the user-determined set point. See Fig. 43. Indoor Air Quality (IAQ) Sensor Input -- The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged. Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and CONTROL CURVE CONTROL 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) POINT APPROXI°F(°C) AT 50% RH A 73123) B 70121) C D 67119 ) 63(17) \ \ \ \ \ HIGH 35 40 45 50 55 60 65 70 75 80 85 90 95 100 \ 105 (2) (4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) APPROXIMATE DRY BULB TEMPERATURE-- Fig. 41 -- Enthalpy LIMIT CURVE 110 (43) °F (°C) Changeover Set Points CO 2 SENSOR MAX RANGE SETTING TRIP-1 6000 T_ 5000 Vac 24T_24 HO ...... z COM Vac 2 4000 +800 +900 @ ppm ppm 3000 Z 2 z 5 ...... _ < 4 EF1 Fig. 43 .................................................. J EconoMi$er ppm o 2 Fig. 42 -- ppm _1000 1000 3 4 5 6 7 DAMPER VOLTAGE FOR MAX VENTILATION EF_ +1100 2000 W IV Control 23 -- CO2 Sensor Maximum 8 RATE Range Setting Damper Movement -- Damper movement trom full open to full closed (or vice versa) takes 2112minutes. Thermostats -- The EconoMi$er IV control works with conventiomd thermostats that have a YI (cool stage 1), Y2 (cool stage 2), Wl (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control does not support space temperature sensors. Connections are made at the thermostat termimd connection board located in the main control box. Exhaust Set Point Adjustment -- The exhaust set point will determine when the exhaust fan runs based on dmnper position (if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer See Fig. 38. The set point represents the damper position above which the exhaust fans will be turned on. When there is a call for exhaust, the EconoMiSer IV controller provides a 45 _+15 second delay before exhaust fan activation to allow the dampers to open. This delay _fllows file damper to reach the appropriate position to avoid unnecessary fan overload. Occupancy Control -- The facto U default configuration for the EconoMi$er IV control is occupied mode. Occupied status is provided by the black jumper fiom terminal TR to terminal N. When unoccupied mode is desired, install a field-supplied time clock function in place of the jumper between TR and N. See Fig. 32. When the time clock contacts me closed, the EconoMi$er IV control will be in occupied mode. When the time clock contacts are open (removing the 24-v signal from terminal N), the EconoMi$er IV will be in unoccupied mode. Minimum Position Control -- There is a minimum damper position potentiometer on the EconoMiSer [V controllel: See Fig. 38. The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventihttion, the minimum dmnper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The maximum demand ventilation position is used for fully occupied ventilation. When demand minimum position cupied ventilation position should be Demand Controlled Ventilation (DCV) -- When using the EconoMi$er IV for demand controlled ventilation, them are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rote must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh air Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfin required per person, using normal outside air design criteria. ventilation control is not being used, the potentiometer should be used to set the ocposition. The maximum demand ventilation turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum mnount of outdoor aik as required by local codes, to enter the building. Make minimum position adjustments with at least 10 F temperature difference between the outdoor and return-air temperatures. To determine the minimum following procedure: position setting, perform 1. Calculate the appropriate mixed air temperature following formula: OA RA (To x l---ff_ ) + (TR x _ = TM A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy. A proportional-anticipato U strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO2 level roaches the set point, the damper will be at maximum ventilation and should maintain the set point. In order to have the CO2 sensor control the economizer damper in this manner, fil.'stdetermine the damper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contmninants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures. the using the To = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor during occupied conditions, outdoor-air temperature 60 E and return-air temperature is 75 E (60 x .10) + (75 x .90) =73.5 air is F 2. Disconnect TI. the supply air sensor 3. Ensure that terminals P used, make Fig. 32 and turned fully Connect 24 the factory-installed jumper is in place across and PI. If remote damper positioning is being sure that the terminals are wired according to that the minimum position potentiometer is clockwise. vac across terminals TR and TRI. 4. 5. from terminals T and OA RA (To x l---ff_-) + (TR x _ To = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air Carelhlly adjust the minimum position potentiometer until the measured supply air temperature matches the calculated value. TM = Mixed-Air Temperature Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to deterlnine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 43 to determine the maximum setting of the CO2 sensol: For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 43 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The 6. Reconnect the supply air sensor to termimfls T and TI. Remote control of the EconoMiSer IV damper is desirable when requiring additiomfl tempormy ventilation. If a field-supplied remote potentiometer (Honeywell part number $963B1128) is wired to the EconoMiSer IV controllek the minimum position of the damper can be controlled from a remote location. To control the minimum damper the factory-installed jumper on the EconoMiSer IV controllel: Wire the ter to the P and PI terminals on the See Fig. 42. = TM position remotely, remove P and PI terminals on the field-supplied potentiomeEconoMi$er IV controller. 24 EconoMiSer IV controller will outputthe6.7voltsfiomthe CO2sensor totheactuator whentheCO2concentration inthe space isfit1100ppm.TheDCVsetpointmaybeleftfit2volts sincethe CO2sensorvoltagewill be ignoredby the EconoMiSer IV controller untilitrisesabove the3.6voltsettingoftheminimum position potentiometer Oncethefullyoccupied dmnper position hasbeendetermined, setfilemaximum damper demand controlventilation potentiometer tothisposition. Donotsettofilemaximum positionasfliiscanlesultinover-ventilation tothespace findpotentialhigh-humidity levels. heating and cooling processes are morn than adequae to mmove the humidity loads for most commemial applications. If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, fin energy recovery unit and/or a dehumidification option should be considered. Step 9- Adjust Evaporator-Fan evaporator-fan Speed --Adjust speed to meet jobsite conditions. Tables 7 and 8 show fan rpm fit motor pulley settings. Tables 9 and 10 show maximum amp draw of belt-di'ive motol: Table 11 shows sound data. Refer to Tables 12-29 for performance data. See Table 30 for accessory static pressure drop. See Fig. 44 for the Humidi-MiZer r_q system static pressure diops. C02 Sensor Configuration -- The CO2 sensor has preset standard voltage settings flint can be selected anytime after the sensor is powered up. See Table 6. Use setting 1 or 2 for Carrier equipment. See Table 6. 1. Pless Clear and Mode buttons. Hold fit least 5 seconds until the sensor enters the Edit mode. BELT-DRIVE MOTORS -- Fan motor pulleys are facto q set for speed shown in Table 1. Check pulley alignment find belt tension prior to start-up. 2. Pless Mode twice. The STDSET 3. Use file Up/Down Table 6. NOTE: Befole adjusting fan speed, make sure the new fan speed will provide an air temperature rise range as shown in Table 1. 4. Pless Enter to lock in the selection. 5. Pless Mode to exit and resume normal operation. Menu will appem: button to select the pleset numbel: See To change fan speed: 1. Shut off unit power supply, tag disconnect. The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change file non-stan&trd settings: 1. Pless Clear and Mode buttons. Hold fit least 5 seconds until the sensor enters the Edit mode. 2. Pless Mode twice. The STDSET 3. Use the Up/Down and press Entec 4. Use the Up/Down button to toggle through each of the nine variables, stinting with Altitude, until the desired setting is reached. 5. 6. button to toggle to the NONSTD menu Table OUTPUT 6 -- 002 (cfm/Peraon) 1 2 3 4 5 3. Ix_osen movable 4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motol: Do not exceed maximum speed specified in Table 1. 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each lull turn of pulley flange.) 1. Ix_osen fan motor mounting Slide motor mounting plate away from fan scroll for proper belt tension (1/2-in. deflection wifli 8 to 10 lb of force) and tighten mounting nuts. 3. Adjust lock bolt and nut on mounting motor in fixed position. Standard ANALOG OUTPUT 002 CONTROLRANGE (ppm) 1000 5O Proportional Any 0-2000 1000 5O Exponential Any 0-10V 4-20 mA 0-2000 1100 5O Proportional 15 0-10V 4-20 mA 0-1100 1100 5O Proportional 20 0-10V 4-20 mA 0- 900 900 5O 0-1100 1100 5O 900 5O 5000 5OO 15 7 Exponential 2O 0-10V 4-20 mA 0- 900 Proportional 0-10V 4-20 mA 0-9999 Proportional 0-10V 4-20 mA 0-2000 Parking/Air Intakes/ Loading Docks RELAY HYSTERESIS (ppm) 0-2000 Exponential 9 OPTIONAL RELAY SETPOINT (ppm) 2-10V 7-20 mA 6 & Safety plate to secure Settings 0-10V 4-20 mA Health nuts. 2. 0-10V 4-20 mA Economizer 8 pulley flange setscrew (see Fig. 46). Any Proportional Interface w/Standard Building Control System nuts. See To adjust belt tension: Sensor VENTILATION RATE fan motor mounting To align fan and motor pulleys, loosen fan pulley setscrews find slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting. Dehumidification of Fresh Air with DCV Control -- Information from ASHRAE indicates that the largest humidity load on any zone is the fresh air introduced. For some applications, a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when file enthalpy is high. In most cases, the normfd EQUIPMENT Ix_osen belt by loosening Fig. 45. Menu will appem: Press Mode to move through the variables. Press Enter to lock in the selection, then press Mode to continue to the next vmiable. SETTING 2. LEGEND ppm -- Parts Per Million 25 7OO 5O 0.35 0.25 - 0.1 4&5ton 6 ton 0.05 3 ton 0 0 i i i i [ 1000 2000 3000 4000 5000 Fig. 44 -- Humidi-MiZer Adaptive Dehumidification TM 6000 System Static Pressure Drop (in. wg) MOVABLE FLANGE STRAIGHT EDGE MUST WITH BELT MOTOR AND FAN SHAFTS MUST BE PARALLEL SETSCREW£__'_ MOTOR MOUNTING PLATE NUTS Fig. 45 -- Belt-Drive FIXED FLANGE SINGLE-GROOVE Motor Mounting Fig. 46 -- Evaporator-Fan Pulley Adjustment Table 7 -- 48HJ Fan Rpm at Motor Pulley Setting With Standard Motor* UNIT 48HJ 0 l& 1 004 1044 1008 971 935 898 005 1185 1144 1102 1061 1019 978 936 895 853 812 770 -- -- 006 1460 1425 1389 1354 1318 1283 1248 1212 1177 1141 1106 1070 1035 007 1585 1538 1492 1445 1399 1352 1305 1259 1212 1166 1119 -- -- 11_ 2 MOTOR PULLEY TURNS OPEN 2_& 3 3 l& 862 826 789 4 4_ 753 716 5 5 l& 6 680 -- -- *Approximate fan rpm shown (standard motor/drive). Table 8 -- 48HJ Fan Rpm at Motor Pulley Setting With High-Static Motor* MOTOR PULLEY TURNS OPEN UNIT 48HJ O l& 1 1 l& 2 21& 3 3 l& 4 4 l& 5 5 l& 6 004 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 005 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 006 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 -- -- 007 1685 1589 1557 1525 1493 1460 1428 1396 1364 1332 1300 -- -- *Approximate fan rpm shown (high-static motor/drive). 26 Table 9 -- Evaporator-Fan UNIT 48HJ Motor Data -- Standard Motor UNIT PHASE MAXIMUM CONTINUOUS BHP* MAXIMUM OPERATING WATTS* UNIT VOLTAGE Single 1.20 1000 208_30 4.9 208_30 4.9 O04 Three 1.20 1.20 Single 005 1000 Three 1000 1.20 1000 MAXIMUM AMPDRAW 460 2.2 575 2.2 208_30 4.9 208_30 4.9 460 2.2 575 Single 1.30 1650 Three 2.40 2120 006 2.2 208_30 10.1 208_30 6.7 460 3.0 575 3.0 208_30 007 Three 2.40 2120 LEGEND Bhp i Table 10- Evaporator-Fan Motor Data- UNIT PHASE MAXIMUM CONTINUOUS BHP* MAXIMUM OPERATING WATTS* 004 Three 2.40 2120 Three 2.40 Three 007 2120 2.90 Three 2615 2.90 2615 LEGEND Bhp -- Table 11 -- Outdoor ARI RATING (decibels) UNIT VOLTAGE MAXIMUM AMP DRAW 208/230 6.7 460 3.0 575 3.0 208/230 6.7 460 3.0 575 3.0 208/230 8.6 460 3.9 575 3.9 208/230 8.6 460 3.9 575 3.9 *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Brake Horsepower UNIT 48HJ 3.0 High-Static Motors UNIT 48HJ 006 3.0 575 *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Brake Horsepower 005 6.7 460 Sound Power (Total Unit) OCTAVE BANDS 63 125 250 500 1000 2000 4000 8000 004,005 76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3 006,007 80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0 LEGEND ARI -- Air Conditioning and Refrigeration Institute GENERAL FAN PERFORMANCE NOTES 1. Values include losses for filters, unit casing, and wet coils. See Table 30 and Fig. 44 for accessory/FlOP static pressure information. 2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Tables 9 and 10 on this page for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 4. Interpolation is permissible. Do not extrapolate. 27 Table 12 -- Fan Performance 48HJ004 -- Vertical Discharge Units; Standard EXTERNAL AIRFLOW CFM 900 1000 1100 1200 1300 1400 1500 0.2 Rpm 567 599 632 666 701 737 773 Watts 145 177 215 257 306 361 422 Rpm 688 717 747 778 810 842 875 Bhp 0.22 0.27 0.31 0.37 0.43 0.49 0.57 Watts 222 265 313 367 426 491 564 1.2 Rpm 1016 1041 1066 1093 1119 1147 1175 Bhp 0.51 0.59 0.68 0.77 0.87 0.98 1.09 1.4 Watts 505 587 674 767 866 972 1086 Rpm 1080 1104 1129 1155 1181 1208 ............ Bhp 0.57 0.67 0.76 0.87 0.98 1.09 Watts 572 662 759 861 970 1086 STATIC PRESSURE (in. wg) 0.6 Rpm 786 814 842 871 901 931 963 EXTERNAL AIRFLOW CFM 90O 1000 1100 1200 1300 1400 1500 Bhp 0.15 0.18 0.22 0.26 0.31 0.36 0.42 0.4 --- Watts 296 349 407 471 540 616 699 Rpm 871 897 925 952 981 1010 1040 STATIC PRESSURE (in. wg) 1.6 Rpm 1139 1163 1188 1213 1239 ......... LEGEND Bhp Watts Bhp 0.30 0.35 0.41 0.47 0.54 0.62 0.70 Bhp 0.64 0.74 0.85 0.96 1.08 Watts 637 737 843 955 1073 Rpm 1195 1219 1243 1268 1294 Motor (Belt Drive)* 0.8 Bhp 0.37 0.43 0.50 0.57 0.65 0.74 0.84 1.0 Watts 368 430 498 572 651 738 831 Rpm 947 972 999 1025 1053 1081 1110 Bhp 0.44 0.51 0.59 0.67 0.76 0.86 0.96 Watts 702 811 925 1047 1175 Rpm 1249 1272 1296 1321 -- Bhp 0.77 0.89 1.01 1.14 -- 1.8 Bhp 0.71 0.81 0.93 1.05 1.18 Watts 437 509 587 670 760 856 960 2.0 Watts 765 883 1007 1137 -- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 1.20. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 680 to 1044 rpm. All other rpms require fieldsupplied drive. Table 13 -- Fan Performance 48HJ004 --Vertical EXTERNAL AIRFLOW CFM 90O 1000 1100 1200 1300 1400 1500 0.2 Rpm 567 599 632 666 701 737 773 Watts 145 177 215 257 306 361 422 Rpm 688 717 747 778 810 842 875 Bhp 0.22 0.27 0.31 0.37 0.43 0.49 0.57 Watts 222 265 313 367 426 491 564 1.2 Rpm 1016 1041 1066 1093 1119 1147 1175 Bhp 0.51 0.59 0.68 0.77 0.87 0.98 1.09 1.4 Watts 505 587 674 767 866 972 1086 Rpm 1080 1104 1129 1155 1181 1208 1235 Bhp 0.57 0.67 0.76 0.87 0.98 1.09 1.22 Watts 572 662 759 861 970 1086 1209 STATIC PRESSURE (in. wg) 0.6 Rpm 786 814 842 871 901 931 963 EXTERNAL AIRFLOW CFM 90O 1000 1100 1200 1300 1400 1500 Bhp 0.15 0.18 0.22 0.26 0.31 0.36 0.42 0.4 Discharge Units; High-Static Motor (Belt Drive)* --- Watts 296 349 407 471 540 616 699 Rpm 871 897 925 952 981 1010 1040 STATIC PRESSURE (in. wg) 1.6 Rpm 1139 1163 1188 1213 1239 1265 1292 LEGEND Bhp Watts Bhp 0.30 0.35 0.41 0.47 0.54 0.62 0.70 Bhp 0.64 0.74 0.85 0.96 1.08 1.21 1.34 Watts 637 737 843 955 1073 1199 1332 Rpm 1195 1219 1243 1268 1294 1320 1346 0.8 Bhp 0.37 0.43 0.50 0.57 0.65 0.74 0.84 1.0 Watts 368 430 498 572 651 738 831 Rpm 947 972 999 1025 1053 1081 1110 Bhp 0.44 0.51 0.59 0.67 0.76 0.86 0.96 Watts 702 811 925 1047 1175 1310 1452 Rpm 1249 1272 1296 1321 1346 1371 1397 Bhp 0.77 0.89 1.01 1.14 1.28 1.43 1.58 1.8 Bhp 0.71 0.81 0.93 1.05 1.18 1.32 1.46 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive. 28 Watts 437 509 587 670 760 856 960 Watts 765 883 1007 1137 1275 1419 1572 Table 14 -- Fan Performance 48HJ005 -- Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 0.2 Rpm 666 701 737 773 810 847 885 923 962 Watts 257 306 361 422 491 567 652 745 847 Rpm 778 810 842 875 909 943 978 1014 1049 Bhp 0.37 0.43 0.49 0.57 0.65 0.73 0.83 0.94 1.05 Watts 367 426 491 564 643 730 826 930 1043 1.2 Rpm 1093 1119 1147 1175 Bhp 0.77 0.87 0.98 1.09 1.4 Watts 767 866 972 1086 Rpm 1155 1181 1208 ............ Bhp 0.87 0.98 1.09 Watts 861 970 1086 STATIC PRESSURE 0.6 Rpm 871 901 931 963 994 1027 1060 1093 ......... EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Bhp 0.26 0.31 0.36 0.42 0.49 0.57 0.66 0.75 0.85 0.4 --- Watts 471 540 616 699 790 888 994 1109 STATIC PRESSURE 1.6 Rpm 1213 1239 ......... LEGEND Bhp Watts Bhp 0.47 0.54 0.62 0.70 0.79 0.89 1.00 1.11 Bhp 0.96 1.08 Watts 955 1073 (in. wg) 0.8 Rpm 952 981 1010 1040 1070 1101 1133 ...... Bhp 0.57 0.65 0.74 0.84 0.94 1.05 1.16 1.0 Watts 572 651 738 831 932 1040 1157 Rpm 1025 1053 1081 1110 1140 1170 -- Bhp 0.67 0.76 0.86 0.96 1.08 1.20 -- Watts 1047 1175 Rpm 1321 -- Bhp 1.14 -- Watts 670 760 856 960 1070 1189 -- (in. wg) 1.8 Rpm 1268 1294 Bhp 1.05 1.18 2.0 Watts 1137 -- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 1.20. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 770 to 1185 rpm. All other rpms require fieldsupplied drive. Table 15 -- Fan Performance 48HJ005 -- Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 0.2 Rpm 666 701 737 773 810 847 885 923 962 Watts 257 306 361 422 491 567 652 745 847 Rpm 778 810 842 875 909 943 978 1014 1049 Bhp 0.37 0.43 0.49 0.57 0.65 0.73 0.83 0.94 1.05 Watts 367 426 491 564 643 730 826 930 1043 1.2 Rpm 1093 1119 1147 1175 1204 1233 1262 1293 1323 Bhp 0.77 0.87 0.98 1.09 1.21 1.34 1.48 1.63 1.79 1.4 Watts 767 866 972 1086 1207 1336 1473 1620 1776 Rpm 1155 1181 1208 1235 1263 1292 1321 1350 1380 Bhp 0.87 0.98 1.09 1.22 1.35 1.49 1.64 1.79 1.96 Watts 861 970 1086 1209 1340 1480 1627 1784 1950 STATIC PRESSURE 0.6 Rpm 871 901 931 963 994 1027 1060 1093 1127 EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Bhp 0.26 0.31 0.36 0.42 0.49 0.57 0.66 0.75 0.85 0.4 --- Watts 471 540 616 699 790 888 994 1109 1233 STATIC PRESSURE 1.6 Rpm 1213 1239 1265 1292 1320 1348 1376 1405 1434 LEGEND Bhp Watts Bhp 0.47 0.54 0.62 0.70 0.79 0.89 1.00 1.11 1.24 Bhp 0.96 1.08 1.21 1.34 1.48 1.63 1.79 1.96 2.13 Watts 955 1073 1199 1332 1472 1622 1779 1946 2123 (in. wg) 0.8 Rpm 952 981 1010 1040 1070 1101 1133 1165 1198 Bhp 0.57 0.65 0.74 0.84 0.94 1.05 1.16 1.29 1.42 1.0 Watts 572 651 738 831 932 1040 1157 1283 1417 Rpm 1025 1053 1081 1110 1140 1170 1200 1231 1263 Bhp 0.67 0.76 0.86 0.96 1.08 1.20 1.32 1.46 1.61 Watts 1047 1175 1310 1452 1603 1762 1930 2106 2293 Rpm 1321 1346 1371 1397 1424 1451 1479 1506 -- Bhp 1.14 1.28 1.43 1.58 1.74 1.91 2.09 2.28 -- (in. wg) 1.8 Rpm 1268 1294 1320 1346 1373 1401 1428 1457 1486 Bhp 1.05 1.18 1.32 1.46 1.61 1.77 1.94 2.12 2.31 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40, 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive. 29 Watts 670 760 856 960 1070 1189 1316 1453 1598 Watts 1137 1275 1419 1572 1732 1901 2078 2265 -- Table 16 -- Fan Performance 48HJ006, Single-Phase -- Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 0.2 Rpm 848 887 927 967 1007 1048 1090 1131 1173 Watts 371 433 502 579 663 757 859 970 1091 Rpm 968 1004 1040 1077 1115 1153 1191 1230 ............ Bhp 0.55 0.63 0.71 0.81 0.91 1.03 1.15 1.29 Watts 486 556 633 718 811 913 1023 1143 1.2 Rpm 1312 1342 1374 Bhp 1.07 1.18 1.30 1.4 Watts 948 1047 1153 Rpm Bhp 1380 1.20 ............ ............ Watts 1067 STATIC PRESSURE (in. wg) 0.6 Rpm 1069 1103 1137 1172 1208 1244 ......... ......... EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Bhp 0.42 0.49 0.57 0.65 0.75 0.85 0.97 1.09 1.23 0.4 --- Watts 600 678 763 856 957 1066 Rpm 1158 1190 1223 1257 1291 ...... STATIC PRESSURE (in. wg) 1.6 Rpm ......... Bhp Watts Rpm 0.8 Bhp 0.80 0.90 1.00 1.12 1.24 1.0 Watts 715 800 892 993 1101 Rpm 1238 1269 1302 1334 -- Bhp 0.94 1.04 1.15 1.27 -- Watts Rpm Bhp 1.8 Bhp Watts 831 922 1022 1130 -- 2.0 .............. .............. .............. .............. .............. .............. Watts m m m m m m LEGEND Bhp Watts Bhp 0.68 0.76 0.86 0.96 1.08 1.20 NOTES: Brake Horsepower Input Watts to Motor 1. Boldface indicates field-supplied drive is required, 2. Maximum continuous bhp is 1.30. 3. See page 27 for general fan performance notes. *Motor drive range: 1035 to 1460 rpm. All other rpms require fieldsupplied drive. Table 17 -- Fan Performance 48HJ006, Three-Phase -- Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 0.2 Rpm 848 887 927 967 1007 1048 1090 1131 1173 1215 1258 Watts 371 433 502 579 663 757 859 970 1091 1223 1365 Rpm 968 1004 1040 1077 1115 1153 1191 1230 1269 1309 1349 Bhp 0.55 0.63 0.71 0.81 0.91 1.03 1.15 1.29 1.43 1.59 1.76 Watts 486 556 633 718 811 913 1023 1143 1273 1413 1564 1.2 Rpm 1312 1342 1374 1406 1438 1471 1504 1538 1572 Bhp 1.07 1.18 1.30 1.43 1.57 1.72 1.87 2.04 2.23 1.4 Watts 948 1047 1153 1268 1391 1523 1665 1816 1978 Rpm 1380 1411 1441 1473 1504 1536 1569 1602 ............ Bhp 1.20 1.32 1.45 1.58 1.73 1.89 2.06 2.23 Watts 1067 1173 1286 1407 1537 1677 1825 1984 STATIC PRESSURE (in. wg) 0.6 Rpm 1069 1103 1137 1172 1208 1244 1281 1318 1355 1393 1431 EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Bhp 0.42 0.49 0.57 0.65 0.75 0.85 0.97 1.09 1.23 1.38 1.54 0.4 Watts 600 678 763 856 957 1066 1185 1313 1451 1600 1759 Rpm 1158 1190 1223 1257 1291 1326 1361 1397 1433 1470 1506 STATIC PRESSURE (in. wg) 1.6 Rpm 1445 1474 1505 1535 1567 1598 1630 ......... LEGEND Bhp Wa_s Bhp 0.68 0.76 0.86 0.96 1.08 1.20 1.33 1.48 1.63 1.80 1.98 Bhp 1.34 1.46 1.60 1.74 1.90 2.06 2.24 Watts 1189 1300 1420 1548 1685 1831 1986 Rpm 1506 1535 1565 1595 1626 1657 ...... 0.8 Bhp 0.80 0.90 1.00 1.12 1.24 1.37 1.51 1.67 1.83 2.01 2.20 1.0 Watts 715 800 892 993 1101 1219 1345 1481 1627 1784 1951 Rpm 1238 1269 1302 1334 1368 1401 1435 1470 1505 1540 -- Bhp 0.94 1.04 1.15 1.27 1.40 1.54 1.69 1.86 2.03 2.21 -- Watts 1312 1429 1555 1690 1833 1986 Rpm 1564 1593 1622 1652 1682 -- Bhp 1.62 1.76 1.91 2.06 2.23 -- 1.8 Bhp 1.48 1.61 1.75 1.90 2.06 2.24 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2,40. 3. See page 27 for general fan performance notes. -- Brake Horsepower -- Input Watts to Motor *Motor drive range: 1035 to 1460 rpm. All other rpms require fieldsupplied drive. 3O Watts 831 922 1022 1130 1246 1371 1505 1649 1803 1967 -- Watts 1437 1560 1692 1833 1983 -- Table 18 -- Fan Performance 48HJ006 -- Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 0.2 Rpm 848 887 927 967 1007 1048 1090 1131 1173 1215 1258 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Watts 371 433 502 579 663 757 859 970 1091 1223 1365 Rpm 968 1004 1040 1077 1115 1153 1191 1230 1269 1309 1349 Bhp 0.55 0.63 0.71 0.81 0.91 1.03 1.15 1.29 1.43 1.59 1.76 Watts 486 556 633 718 811 913 1023 1143 1273 1413 1564 1.2 Rpm 1312 1342 1374 1406 1438 1471 1504 1538 1572 1607 1642 Bhp 1.07 1.18 1.30 1.43 1.57 1.72 1.87 2.04 2.23 2.42 2.63 1.4 Watts 948 1047 1153 1268 1391 1523 1665 1816 1978 2150 2333 Rpm 1380 1411 1441 1473 1504 1536 1569 1602 1635 1669 1704 Bhp 1.20 1.32 1.45 1.58 1.73 1.89 2.06 2.23 2.42 2.63 2.84 Watts 1067 1173 1286 1407 1537 1677 1825 1984 2153 2332 2523 STATIC PRESSURE 0.6 Rpm 1069 1103 1137 1172 1208 1244 1281 1318 1355 1393 1431 EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Bhp 0.42 0.49 0.57 0.65 0.75 0.85 0.97 1.09 1.23 1.38 1.54 0.4 --- Watts 600 678 763 856 957 1066 1185 1313 1451 1600 1759 STATIC PRESSURE 1.6 Rpm 1445 1474 1505 1535 1567 1598 1630 1663 1695 1729 ......... LEGEND Bhp Watts Bhp 0.68 0.76 0.86 0.96 1.08 1.20 1.33 1.48 1.63 1.80 1.98 Bhp 1.34 1.46 1.60 1.74 1.90 2.06 2.24 2.42 2.62 2.83 Watts 1189 1300 1420 1548 1685 1831 1986 2152 2328 2515 (in. wg) 0.8 Rpm 1158 1190 1223 1257 1291 1326 1361 1397 1433 1470 1506 Bhp 0.80 0.90 1.00 1.12 1.24 1.37 1.51 1.67 1.83 2.01 2.20 1.0 Watts 715 800 892 993 1101 1219 1345 1481 1627 1784 1951 Rpm 1238 1269 1302 1334 1368 1401 1435 1470 1505 1540 1576 Bhp 0.94 1.04 1.15 1.27 1.40 1.54 1.69 1.86 2.03 2.21 2.41 Watts 831 922 1022 1130 1246 1371 1505 1649 1803 1967 2142 (in. wg) 1.8 Rpm 1506 1535 1565 1595 1626 1657 1688 1720 1753 ...... Bhp 1.48 1.61 1.75 1.90 2.06 2.24 2.42 2.61 2.82 2.0 Watts 1312 1429 1555 1690 1833 1986 2149 2321 2504 Rpm 1564 1593 1622 1652 1682 1713 1744 1775 -- Bhp 1.62 1.76 1.91 2.06 2.23 2.41 2.60 2.81 -- Watts 1437 1560 1692 1833 1983 2142 2312 2491 -- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.90. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive. Table 19 -- Fan Performance 48HJ007 -- Vertical Discharge Units; Standard EXTERNAL AIRFLOW CFM 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 0.2 Rpm 967 1008 1049 1091 1133 1176 1216 1261 1305 1348 1392 1435 1479 Watts 563 643 731 827 933 1047 1170 1304 1448 1602 1768 1945 2135 Rpm 1075 1112 1151 1189 1229 1268 1308 1349 1390 1431 1472 ............ ............ Bhp 0.80 0.91 1.02 1.14 1.26 1.40 1.55 1.72 1.89 2.07 2.27 Watts 715 805 903 1008 1123 1247 1380 1523 1677 1841 2016 1.2 Rpm 1406 1438 1470 1502 1535 1569 Bhp 1.43 1.58 1.73 1.89 2.06 2.25 1.4 Watts 1273 1401 1537 1681 1834 1996 Rpm 1475 1505 1537 1568 1600 ............ Bhp 1.58 1.73 1.90 2.07 2.25 Watts 1403 1541 1686 1840 2002 STATIC PRESSURE 0.6 Rpm 1170 1205 1241 1276 1315 1352 1390 1429 1468 1507 ......... EXTERNAL AIRFLOW CFM 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Bhp 0.63 0.72 0.82 0.93 1.05 1.18 1.32 1.47 1.63 1.80 1.99 2.19 2.40 0.4 --- Watts 861 960 1068 1183 1308 1441 1584 1736 1900 2073 STATIC PRESSURE 1.6 Rpm 1540 1569 1600 1631 ......... LEGEND Bhp Watts Bhp 0.97 1.08 1.20 1.33 1.47 1.62 1.78 1.96 2.14 2.33 Bhp 1.72 1.89 2.06 2.25 Watts 1531 1678 1833 1996 Motor (Belt Drive)* (in. wg) 0.8 Rpm 1255 1289 1323 1358 1393 1429 1466 1503 1540 ...... Bhp 1.13 1.25 1.38 1.52 1.67 1.84 2.01 2.19 2.38 1.0 Watts 1002 1111 1228 1353 1487 1630 1782 1945 2117 Rpm 1333 1366 1399 1433 1467 1501 1537 --- Bhp 1.28 1.42 1.56 1.71 1.67 2.04 2.23 --- Watts 1657 1813 1977 Rpm 1660 1689 1718 Bhp 2.00 2.19 2.38 (in. wg) 1.8 Rpm 1601 1630 1660 -- Bhp 1.87 2.04 2.23 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1119 to 1585 rpm. All other rpms require fieldsupplied drive. 3! Watts 1139 1258 1384 1519 1662 1815 1977 --- Watts 1780 1945 2118 Table 20 -- Fan Performance 48HJ007 -- Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 0.2 Rpm 967 1008 1049 1091 1133 1176 1218 1261 1305 1348 1392 1435 1479 Watts 563 643 731 827 933 1047 1170 1304 1448 1602 1768 1945 2135 Rpm 1075 1112 1151 1189 1229 1268 1308 1349 1390 1431 1472 1514 1556 Bhp 0.80 0.91 1.02 1.14 1.26 1.40 1.55 1.72 1.89 2.07 2.27 2.48 2.70 Watts 715 805 903 1008 1123 1247 1380 1523 1677 1841 2016 2203 2402 1.2 Rpm 1406 1438 1470 1502 1535 1569 1603 1638 1673 Bhp 1.43 1.58 1.73 1.89 2.06 2.25 2.44 2.64 2.86 1.4 Watts 1273 1401 1537 1681 1834 1996 2167 2349 2541 Rpm 1475 1505 1537 1568 1600 1633 1666 1700 ............ Bhp 1.58 1.73 1.90 2.07 2.25 2.45 2.65 2.87 Watts 1403 1541 1686 1840 2002 2174 2355 2546 STATIC PRESSURE (in. wg) 0.6 Rpm 1170 1205 1241 1278 1315 1352 1390 1429 1468 1507 1547 1587 ......... EXTERNAL AIRFLOW CFM 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Bhp 0.63 0.72 0.82 0.93 1.05 1.18 1.32 1.47 1.63 1.80 1.99 2.19 2.40 0.4 --- Watts 861 960 1068 1183 1308 1441 1584 1736 1900 2073 2258 2455 Rpm 1255 1289 1323 1358 1393 1429 1466 1503 1540 1578 1616 ...... STATIC PRESSURE (in. wg) 1.6 Rpm 1540 1569 1600 1631 1662 1694 1727 ......... LEGEND Bhp Watts Bhp 0.97 1.08 1.20 1.33 1.47 1.62 1.78 1.96 2.14 2.33 2.54 2.76 Bhp 1.72 1.89 2.06 2.25 2.44 2.64 2.86 Watts 1531 1678 1833 1996 2167 2348 2539 Rpm 1601 1630 1660 1690 1721 1752 ...... 0.8 Bhp 1.13 1.25 1.38 1.52 1.67 1.84 2.01 2.19 2.38 2.59 2.81 1.0 Watts 1002 1111 1228 1353 1487 1630 1782 1945 2117 2301 2495 Rpm 1333 1366 1399 1433 1467 1501 1537 1572 1608 1645 -- 1.8 Bhp 1.87 2.04 2.23 2.42 2.62 2.84 Bhp 1.28 1.42 1.56 1.71 1.87 2.04 2.23 2.42 2.62 2.84 -- Watts 1139 1258 1384 1519 1662 1815 1977 2149 2331 2524 -- 2.0 Watts 1657 1813 1977 2149 2330 2520 Rpm 1660 1689 1718 1747 1778 -- Bhp 2.00 2.19 2.38 2.59 2.80 -- Watts 1780 1945 2118 2300 2490 -- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.90. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive. Table 21 -- Fan Performance 48HJ004 -- Horizontal Discharge Units; Standard EXTERNAL AIRFLOW CFM 90O 1000 1100 1200 1300 1400 1500 0.2 Rpm 553 582 612 643 675 707 740 Watts 134 163 196 234 277 326 382 Rpm 681 707 734 762 790 819 849 Bhp 0.22 0.26 0.30 0.34 0.40 0.45 0.52 Watts 221 257 297 343 394 452 515 1.2 Rpm 1019 1042 1065 1089 1113 1138 1163 Bhp 0.64 0.70 0.77 0.84 0.92 1.01 1.10 1.4 Watts 640 700 765 837 915 1000 1092 Rpm 1084 1107 1130 1153 1177 1201 ............ Bhp 0.76 0.83 0.90 0.98 1.06 1.15 Watts 760 825 896 974 1058 1149 STATIC PRESSURE (in. wg) 0.6 Rpm 782 807 833 859 886 913 941 EXTERNAL AIRFLOW CFM 90O 1000 1100 1200 1300 1400 1500 Bhp 0.14 0.16 0.20 0.23 0.28 0.33 0.38 0.4 --- Watts 316 358 405 458 517 581 653 Rpm 870 894 919 944 969 996 1023 STATIC PRESSURE (in. wg) 1.6 Rpm 1146 1168 1190 1213 ......... ......... LEGEND Bhp Watts Bhp 0.32 0.36 0.41 0.46 0.52 0.58 0.66 Bhp 0.89 0.96 1.04 1.12 Watts 885 956 1032 1115 Rpm 1203 1225 1247 ...... Motor (Belt Drive)* 0.8 Bhp 0.42 0.47 0.52 0.58 0.65 0.72 0.80 1.0 Watts 417 466 519 579 644 716 795 Rpm 948 971 995 1020 1044 1070 1096 1.8 Bhp 1.02 1.10 1.18 *Motor drive range: 680 to 1044 rpm. All other rpms require fieldsupplied drive. 32 Watts 526 580 639 705 777 855 941 2.0 Watts 1016 1091 1173 Rpm 1258 --- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 1.20. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor Bhp 0.53 0.58 0.64 0.71 0.78 0.86 0.95 Bhp 1.16 --- Watts 1152 --- Table 22 i 0.2 Rpm 553 582 612 643 675 707 740 Bhp 0.14 0.16 0.20 0.23 0.28 0.33 0.38 0.4 Watts 134 163 196 234 277 326 382 Rpm 681 707 734 762 790 819 849 Bhp 0.22 0.26 0.30 0.34 0.40 0.45 0.52 Watts 221 257 297 343 394 452 515 1.2 Rpm 1019 1042 1065 1089 1113 1138 1163 Bhp 0.64 0.70 0.77 0.84 0.92 1.01 1.10 1.4 Watts 640 700 765 837 915 1000 1092 Rpm 1084 1107 1130 1153 1177 1201 1226 Bhp 0.78 0.83 0.90 0.98 1.08 1.15 1.25 Watts 780 825 896 974 1058 1149 1247 STATIC PRESSURE 0.6 Rpm 782 807 833 859 886 913 941 EXTERNAL AIRFLOW CFM 900 1000 1100 1200 1300 1400 1500 Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 900 1000 1100 1200 1300 1400 1500 Fan Performance 48HJ004 i --- Watts 316 358 405 458 517 581 653 STATIC PRESSURE 1.6 Rpm 1146 1168 1190 1213 1237 1261 1285 LEGEND Bhp Watts Bhp 0.32 0.36 0.41 0.46 0.52 0.58 0.66 Bhp 0.89 0.96 1.04 1.12 1.21 1.31 1.41 Watts 885 958 1032 1115 1205 1303 1407 (in. wg) 0.8 Rpm 870 894 919 944 969 996 1023 Bhp 0.42 0.47 0.52 0.58 0.65 0.72 0.80 1.0 Watts 417 466 519 579 644 716 795 Rpm 948 971 995 1020 1044 1070 1096 Bhp 0.53 0.58 0.64 0.71 0.78 0.86 0.95 Watts 1018 1091 1173 1262 1358 1461 1571 Rpm 1258 1279 1301 1324 1347 1370 1394 Bhp 1.18 1.24 1.33 1.42 1.52 1.63 1.75 Watts 526 580 639 705 777 855 941 (in. wg) 1.8 Rpm 1203 1225 1247 1270 1293 1317 1341 Bhp 1.02 1.10 1.18 1.27 1.36 1.47 1.58 2.0 Watts 1152 1232 1319 1413 1514 1623 1740 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive. Table 23 i 0.2 Rpm 643 675 707 740 773 807 841 875 910 Bhp 0.23 0.28 0.33 0.38 0.45 0.52 0.59 0.68 0.77 0.4 Watts 234 277 326 382 444 513 589 674 767 Rpm 762 790 819 849 879 910 942 974 1006 Bhp 0.34 0.40 0.45 0.52 0.59 0.87 0.75 0.85 0.95 Watts 343 394 452 515 586 683 749 842 944 1.2 Rpm 1089 1113 1138 1163 1189 Bhp 0.84 0.92 1.01 1.10 1.20 1.4 Watts 837 915 1000 1092 1191 Rpm 1153 1177 1201 ............ ............ Bhp 0.98 1.06 1.15 Watts 974 1058 1149 STATIC PRESSURE 0.6 Rpm 859 886 913 941 970 999 1029 1059 1090 EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Horizontal Discharge Units; Standard EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Fan Performance 48HJ005 i --- Watts 458 517 581 653 731 817 910 1012 1122 STATIC PRESSURE 1.6 Rpm 1213 ......... ......... LEGEND Bhp Watts Bhp 0.48 0.52 0.58 0.66 0.73 0.82 0.91 1.02 1.13 Bhp 1.12 Watts 1115 Motor (Belt Drive)* (in. wg) 0.8 Rpm 944 989 996 1023 1050 1078 1106 1135 ...... Bhp 0.58 0.65 0.72 0.80 0.88 0.98 1.08 1.19 1.0 Watts 579 644 716 795 880 973 1074 1184 Rpm 1020 1044 1070 1096 1123 1150 --- Bhp 0.71 0.78 0.86 0.95 1.04 1.14 --- Watts Rpm Bhp (in. wg) 1.8 Rpm ...... Bhp 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 1.20. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 770 to 1185 rpm. All other rpms require fieldsupplied drive. 33 Watts 705 777 855 941 1034 1134 --- Watts Table 24 i 0.2 Rpm 643 675 707 740 773 807 841 875 910 Bhp 0.23 0.28 0.33 0.38 0.45 0.52 0.59 0.68 0.77 0.4 Watts 234 277 326 382 444 513 589 674 767 Rpm 762 790 819 849 879 910 942 974 1006 Bhp 0.34 0.40 0.45 0.52 0.59 0.67 0.75 0.85 0.95 Watts 343 394 452 515 586 663 749 842 944 1.2 Rpm 1089 1113 1138 1163 1189 1216 1242 1270 1297 Bhp 0.84 0.92 1.01 1.10 1.20 1.31 1.42 1.55 1.68 1.4 Watts 837 915 1000 1092 1191 1299 1414 1538 1672 Rpm 1153 1177 1201 1226 1252 1277 1303 1330 1357 Bhp 0.98 1.06 1.15 1.25 1.36 1.48 1.60 1.73 1.87 Watts 974 1058 1149 1247 1353 1468 1590 1721 1862 STATIC PRESSURE (in. wg) 0.6 Rpm 859 886 913 941 970 999 1029 1059 1090 EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1200 1300 1400 1500 1600 1700 1800 1900 2000 Fan Performance 48HJ005 i --- Watts 458 517 581 653 731 817 910 1012 1122 Rpm 944 969 996 1023 1050 1078 1106 1135 1185 STATIC PRESSURE (in. wg) 1.6 Rpm 1213 1237 1261 1285 1310 1335 1361 1387 1414 LEGEND Bhp Watts Bhp 0.46 0.52 0.58 0.66 0.73 0.82 0.91 1.02 1.13 Bhp 1.12 1.21 1.31 1.41 1.53 1.65 1.78 1.92 2.07 Watts 1115 1205 1303 1407 1520 1640 1770 1908 2055 Rpm 1270 1293 1317 1341 1365 1390 1415 1441 1467 0.8 Bhp 0.58 0.65 0.72 0.80 0.88 0.98 1.08 1.19 1.31 1.0 Watts 579 644 716 795 880 973 1074 1184 1302 Rpm 1020 1044 1070 1096 1123 1150 1177 1205 1234 Bhp 0.71 0.78 0.86 0.95 1.04 1.14 1.25 1.37 1.49 Watts 1262 1358 1461 1571 1690 1817 1953 2098 2252 Rpm 1324 1347 1370 1394 1418 1442 1467 1493 -- Bhp 1.42 1.52 1.63 1.75 1.87 2.01 2.15 2.30 -- 1.8 Bhp 1.27 1.36 1.47 1.58 1.70 1.83 1.96 2.11 2.26 Watts 705 777 855 941 1034 1134 1242 1360 1485 2.0 Watts 1413 1514 1623 1740 1865 1998 2140 2292 -- NOTES: 1. Boldface indicates field-supplied drive is required, 2. Maximum continuous bhp is 2,40. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive. Table 25 i EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 0.2 Rpm 800 839 879 919 960 1001 1043 1085 1127 Bhp 0.39 0.46 0.54 0.63 0.73 0.84 0.96 1.09 1.23 0.4 Watts 350 412 483 561 648 744 850 966 1092 Rpm 904 938 974 1010 1047 1085 1123 1162 ............ Bhp 0.49 0.57 0.65 0.75 0.85 0.96 1.09 1.22 Watts 438 505 580 663 754 855 965 1086 1.2 Rpm 1247 1270 1295 1321 Bhp 0.98 1.07 1.17 1.28 1.4 Watts 873 952 1040 1137 Rpm 1320 1342 ......... ......... Bhp 1.13 1.22 Watts 1002 1083 STATIC PRESSURE (in. wg) 0.6 Rpm 999 1030 1062 1095 1129 1163 1199 ......... EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Fan Performance 48HJ006, Single-Phase i Horizontal Discharge Units; Standard Motor (Belt Drive)* --- Watts 535 605 684 771 867 972 1086 Rpm 1087 1115 1144 1174 1206 1238 ...... STATIC PRESSURE (in. wg) 1.6 Rpm 1390 ...... Bhp 1.28 Watts 1137 Rpm -- 0.8 Bhp 0.72 0.80 0.90 1.00 1.11 1.23 1.0 Watts 640 714 796 886 986 1095 Rpm 1169 1195 1221 1250 1279 -- Bhp 0.85 0.93 1.03 1.14 1.25 -- Watts -- Rpm Bhp Watts m m m m m m m m m m m m 1.8 Bhp -- Watts 753 829 914 1008 1111 -- 2.0 m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m m LEGEND Bhp Watts Bhp 0.60 0.68 0.77 0.87 0.98 1.09 1.22 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 1.30. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1035 to 1460 rpm. All other rpms require fieldsupplied drive. 34 Table 26 -- Fan Performance 48HJ006, Three-Phase -- Horizontal Discharge Units; Standard Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 0.2 Rpm 800 839 879 919 960 1001 1043 1085 1127 1169 1212 Watts 350 412 483 561 648 744 850 986 1092 1229 1378 Rpm 904 938 974 1010 1047 1085 1123 1162 1201 1241 1281 Bhp 0.49 0.57 0.65 0.75 0.85 0.98 1.09 1.22 1.37 1.53 1.70 Watts 438 505 580 663 754 855 985 1086 1217 1359 1513 1.2 Rpm 1247 1270 1295 1321 1348 1377 1406 1437 1468 1500 1533 Bhp 0.98 1.07 1.17 1.28 1.40 1.53 1.67 1.83 1.99 2.17 2.36 1.4 Watts 873 952 1040 1137 1243 1359 1485 1621 1769 1928 2098 Rpm 1320 1342 1365 1390 1415 1442 1470 1499 1529 1559 ............ Bhp 1.13 1.22 1.32 1.43 1.58 1.69 1.83 1.99 2.16 2.35 Watts 1002 1083 1173 1273 1381 1500 1629 1769 1920 2083 STATIC PRESSURE 0.6 Rpm 999 1030 1062 1095 1129 1163 1199 1235 1272 1310 1348 EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Bhp 0.39 0.46 0.54 0.63 0.73 0.84 0.98 1.09 1.23 1.38 1.55 0.4 --- Watts 535 605 684 771 887 972 1086 1211 1347 1493 1652 STATIC PRESSURE 1.6 Rpm 1390 1411 1432 1455 1479 1505 1531 1559 1587 ......... LEGEND Bhp Watts Bhp 0.60 0.68 0.77 0.87 0.98 1.09 1.22 1.36 1.52 1.68 1.88 Bhp 1.28 1.37 1.48 1.59 1.72 1.86 2.00 2.16 2.34 Watts 1137 1221 1313 1415 1526 1648 1780 1923 2077 (in. wg) 0.8 Rpm 1087 1115 1144 1174 1206 1238 1271 1305 1340 1375 1412 Bhp 0.72 0.80 0.90 1.00 1.11 1.23 1.37 1.51 1.67 1.84 2.02 1.0 Watts 640 714 796 886 986 1095 1213 1342 1482 1633 1796 Rpm 1169 1195 1221 1250 1279 1309 1340 1372 1405 1439 1473 Bhp 0.85 0.93 1.03 1.14 1.25 1.38 1.52 1.67 1.83 2.00 2.19 Watts 1280 1365 1459 1563 1677 1801 1936 2082 Rpm 1522 1540 1559 1579 1601 1624 1648 -- Bhp 1.61 1.71 1.82 1.93 2.06 2.21 2.36 -- Watts 753 829 914 1008 1111 1224 1348 1479 1623 1778 1945 (in. wg) 1.8 Rpm 1457 1476 1497 1518 1541 1565 1591 1617 ...... Bhp 1.44 1.54 1.64 1.76 1.89 2.03 2.18 2.34 2.0 Watts 1430 1517 1612 1718 1834 1961 2098 -- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40, 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1035 to 1460 rpm. All other rpms require fieldsupplied drive. Table 27 -- Fan Performance 48HJ006 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 0.2 Rpm 800 839 879 919 960 1001 1043 1085 1127 1169 1212 Watts 350 412 483 561 648 744 850 966 1092 1229 1378 Rpm 904 938 974 1010 1047 1085 1123 1162 1201 1241 1281 Bhp 0.49 0.57 0.65 0.75 0.85 0.96 1.09 1.22 1.37 1.53 1.70 Watts 438 505 580 663 754 855 965 1086 1217 1359 1513 1.2 Rpm 1247 1270 1295 1321 1348 1377 1406 1437 1488 1500 1533 Bhp 0.98 1.07 1.17 1.28 1.40 1.53 1.67 1.83 1.99 2.17 2.36 1.4 Watts 873 952 1040 1137 1243 1359 1485 1621 1769 1928 2098 Rpm 1320 1342 1365 1390 1415 1442 1470 1499 1529 1559 1591 Bhp 1.13 1.22 1.32 1.43 1.58 1.69 1.83 1.99 2.16 2.35 2.54 Watts 1002 1083 1173 1273 1381 1500 1629 1769 1920 2083 2257 STATIC PRESSURE 0.6 Rpm 999 1030 1062 1095 1129 1163 1199 1235 1272 1310 1348 EXTERNAL AIRFLOW CFM 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 Bhp 0.39 0.46 0.54 0.63 0.73 0.84 0.96 1.09 1.23 1.38 1.55 0.4 --- Watts 535 605 684 771 867 972 1086 1211 1347 1493 1652 STATIC PRESSURE 1.6 Rpm 1390 1411 1432 1455 1479 1505 1531 1559 1587 1616 1647 LEGEND Bhp Watts Bhp 0.60 0.68 0.77 0.87 0.98 1.09 1.22 1.36 1.52 1.68 1.86 Bhp 1.28 1.37 1.48 1.59 1.72 1.88 2.00 2.16 2.34 2.53 2.73 Watts 1137 1221 1313 1415 1528 1648 1780 1923 2077 2243 2421 (in. wg) 0.8 Rpm 1087 1115 1144 1174 1206 1238 1271 1305 1340 1375 1412 Bhp 0.72 0.80 0.90 1.00 1.11 1.23 1.37 1.51 1.67 1.84 2.02 1.0 Watts 640 714 796 886 986 1095 1213 1342 1482 1633 1798 Rpm 1169 1195 1221 1250 1279 1309 1340 1372 1405 1439 1473 Bhp 0.85 0.93 1.03 1.14 1.25 1.38 1.52 1.87 1.83 2.00 2.19 Watts 1280 1365 1459 1563 1677 1801 1938 2082 2239 2408 Rpm 1522 1540 1559 1579 1601 1624 1648 1673 1699 1726 Bhp 1.61 1.71 1.82 1.93 2.08 2.21 2.36 2.53 2.71 2.90 (in. wg) 1.8 Rpm 1457 1476 1497 1518 1541 1565 1591 1617 1644 1672 ...... Bhp 1.44 1.54 1.64 1.78 1.89 2.03 2.18 2.34 2.52 2.71 2.0 NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.90. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive. 35 Watts 753 829 914 1008 1111 1224 1346 1479 1623 1778 1945 Watts 1430 1517 1612 1718 1834 1961 2098 2246 2406 2579 Table 28 -- Fan Performance 48HJ007 -- Horizontal Discharge Units; Standard Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 0.2 Rpm 913 952 992 1032 1073 1114 1155 1196 1238 1280 1322 1364 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Bhp 0.64 0.73 0.84 0.95 1.07 1.21 1.36 1.51 1.69 1.87 2.07 2.28 0.4 Watts 569 652 744 844 954 1074 1204 1345 1497 1660 1835 2023 Rpm 1010 1046 1083 1120 1158 1196 1234 1273 1312 1352 1392 ............ Bhp 0.80 0.91 1.02 1.14 1.27 1.41 1.57 1.73 1.91 2.10 2.31 Watts 715 805 903 1010 1127 1254 1391 1538 1697 1867 2050 Rpm 1098 1131 1166 1200 1236 1272 1308 1348 1382 1420 ......... EXTERNAL AIRFLOW CFM 1.2 Rpm 1322 1351 1380 1411 1441 1473 ............... ............... ............... ............... ............... ............... ............... 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Bhp 1.56 1.68 1.82 1.97 2.13 2.30 1.4 Watts 1382 1495 1617 1748 1890 2041 Rpm 1388 1416 1444 1473 1503 ............ Bhp 1.77 1.90 2.04 2.20 2.36 Watts 1568 1686 1814 1950 2097 STATIC PRESSURE(in. 0,6 --- Watts 869 965 1070 1184 1307 1440 1584 1738 1904 2081 STATIC PRESSURE 1.6 Rpm 1451 1477 1505 ......... ......... LEGEND Bhp Watts Bhp 0.98 1.09 1.21 1.33 1.47 1.62 1.78 1.96 2.14 2.34 Bhp 1.98 2.12 2.27 wg) 0,8 Rpm 1178 1210 1242 1275 1308 1343 1377 1412 1448 ...... Bhp 1.16 1.28 1.40 1.54 1.68 1.84 2.01 2.19 2.38 1,0 Watts 1032 1134 1245 1365 1495 1634 1784 1945 2117 Rpm 1252 1282 1313 1348 1377 1409 1443 --- Bhp 1.35 1.48 1.61 1.75 1.90 2.07 2.24 --- Watts 1962 2090 Rpm --- Bhp --- Watts 1203 1311 1427 1553 1689 1834 1990 --- (in. wg) 1.8 Watts 1762 1885 2017 Rpm 1510 1536 -- Bhp 2.21 2.35 ..... 2.0 Watts --- NOTES: 1. Boldface indicates field-supplied drive is required. 2. Maximum continuous bhp is 2.40. 3. See page 27 for general fan performance notes. Brake Horsepower Input Watts to Motor *Motor drive range: 1119 to 1585 rpm. All other rpms require field-supplied drive. Table 29 -- Fan Performance 48HJ007 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL AIRFLOW CFM 0.2 Rpm 913 952 992 1032 1073 1114 1155 1196 1238 1280 1322 1364 1406 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 Bhp 0.64 0.73 0.84 0,95 1.07 1.21 1.36 1,51 1,69 1.87 2.07 2.28 2.50 0.4 Watts 569 652 744 844 954 1074 1204 1345 1497 1660 1835 2023 2224 Rpm 1010 1046 1083 1120 1158 1196 1234 1273 1312 1352 1392 1432 1472 Bhp 0.80 0.91 1.02 1.14 1.27 1.41 1.57 1.73 1.91 2.10 2.31 2.53 2.76 Watts 715 805 903 1010 1127 1254 1391 1538 1697 1867 2050 2245 2452 Rpm 1098 1131 1166 1200 1236 1272 1308 1348 1382 1420 1458 1496 ......... EXTERNAL AIRFLOW CFM 1.2 1.4 2000 2100 2200 2300 Rpm 1322 1351 1380 1411 1441 1473 Bhp 1,58 1.68 1.82 1.97 2.13 2.30 Watts 1382 1495 1617 1748 1890 2041 2400 2500 2600 1505 1537 1571 2,48 2.68 2.88 2203 2376 2560 1800 1900 2700 2800 2900 3000 Rpm 1388 1416 1444 1473 1503 1533 Bhp 1.77 1,90 2.04 2.20 2.36 2.54 Watts 1568 1686 1814 1950 2097 2254 1564 ............ ............ 2.73 2422 STATIC PRESSURE(in. 0,6 Watts 869 965 1070 1184 1307 1440 1584 1738 1904 2081 2270 2472 STATIC PRESSURE 1.6 Rpm 1451 1477 1505 1533 1562 1591 Bhp 1.98 2,12 2.27 2.43 2.60 2.79 0,8 Rpm 1178 1210 1242 1275 1308 1343 1377 1412 1448 1484 1521 ...... Bhp 1.16 1,28 1.40 1,54 1.68 1.84 2.01 2.19 2.38 2.59 2.81 1.0 Watts 1032 1134 1245 1365 1495 1634 1784 1945 2117 2300 2496 Rpm 1252 1282 1313 1345 1377 1409 1443 1477 1511 1546 -- Bhp 1.35 1,48 1.61 1.75 1.90 2.07 2.24 2.43 2.63 2.84 -- Watts 1203 1311 1427 1553 1689 1834 1990 2157 2335 2526 -- Watts 1962 2090 2227 2374 2532 Rpm 1568 1593 1619 --- Bhp 2,44 2.59 2.75 Watts 2169 2302 2443 --- --- (in. wg) 1.8 Watts 1762 1885 2017 2159 2311 2474 Rpm 1510 1536 1563 1590 1618 -- Bhp 2,21 2.35 2.51 2.67 2.85 2.0 ..... ......... ............... ............... ............... ............... LEGEND Bhp Watts Bhp 0.98 1.09 1,21 1,33 1.47 1.62 1.78 1.96 2.14 2.34 2.56 2.78 wg) --- NOTES: 1. Boldface 2. Maximum 3. See page Brake Horsepower Input Watts to Motor indicates field-supplied drive is required. continuous bhp is 2.90. 27 for general fan performance notes. *Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied drive. Table 30 -- Accessory/FlOP COMPONENT Vertical EconoMi$er2 and EconoMi$er IV Horizontal EconoMi$er2 and EconoMi$er IV I EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) 1250 1500 1750 2000 2250 0.045 -- 0,065 -- 0.08 0.1 0.12 0.125 0.145 0.15 LEGEND FlOP -- Factory-Installed I I 2500 2750 0.175 0.18 0,22 0.225 I 0.255 3000 0.275 *The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts. Option 36 START-UP PRE-START-UP Unit Preparation--Make installed in accordance cable codes. Failure to observe the following warnings could result in serious pel.sonal injuu: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refi'igerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 3. Do not remove complessor terminal cover until all electrical sources +ue disconnected. 4. 5. 6. c. d. that unit instructions lms been and appli- Gas Piping -- Check gas piping for leaks. Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing fieldsupplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manu_dly closing the gas valve. Relieve all pressure from system before touching or disturbing anything inside terminal box if refiigerant leak is suspected around complessor terminals. Never attempt to repair soldered connection while refiigemnt system is under pressure. Do not use torch to remove any component. System cont+fins oil and refiigerant under pressure. To mauve a component, wear protective goggles and proceed as follows: a. b. sure with installation Return-Air Filters--Make sure correct installed in unit (see Table 1). Do not operate return-air filte_.s. Shut off electrical power and then gas to unit. Recover refrigerant to relieve all pressure from system using both high-pressure and lowpressure ports. Cut component connection tubing with tubing cutter and remove component from unit. Carefully unsweat remaining tubing stubs when necessa U. Oil can ignite when exposed to torch flame. Outdoor-Air Inlet Screens- must be in place before operating Outdoor-air filters am unit without inlet screen unit. Compressor Mounting -- Compressorsme internally spring mounted. down bolts. Do not loosen or remove Internal Wiring- Check all electrical unit control boxes. Tighten as required. compressor hold- connections in Refrigerant Service Ports--Each unit system has 4 Schrader-type service ports: one on the suction line, one on the liquid line, and 2 on the compressor discharge line. Be sum that caps on the ports are tight. Two additional Schmder valves ;ue located under the high-pressure and low-pressure switches, respectively. Proceed as follows to inspect and prepare the unit for initial start-up: 1. Remove all access panels. 2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to, or shipped with, unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires, etc. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. c. Inspect all field-wiring and factou-wiring connections. Be sure that connections are completed and tight. Be sure that wires are not in contact with refiigerant tubing or sharp edges. d. Inspect coil tins. If damaged during shipping and handling, carefully straighten fins with a fin comb. 4. Verify the following conditions: a. Make sure that condenser-fan blade are correctly positioned in fan orifice. See Condenser-Fan Adjustment section on page 43 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed. High Flow Refrigerant Valves -- Two high flow valves ;u'e located on the hot gas tube coining out of the colnpressor and the suction tube going into the compressol: Large black plastic caps identify these valves. These valves have O-rings inside which screw the cap onto a brass body to prevent leaks. No field access to these valves is available at this time. Ensure the plastic caps remain on the valves and are tight or the possibility of refrigerant leakage could occm: Compressor Rotation -- On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gages to suction and disch;uge pressure fittings. 2. Energize the compressoc 3. The suction pressure should drop and the disch;uge pressure should rise, as is normal on any st;u't-up. If the suction pressure does not diop and the discharge sure does not rise to normal levels: pres- 1. Note that the evaporator fan (size 006 and 007 only) is probably also rotating in the wrong direction. 2. Turn off power to the unit and install lockout tag. 3. Reverse any two of the unit power leads. 4. Reenergize to the compressol: Check pressures. 37 Thesuction anddischm'ge pressure levels should nowmove totheirnorm_fl start-up levels. NOTE:Whenthecompressor is rotating in thewrongdirection,fileunitwill makeanelevated levelofnoiseandwill not provide cooling. Cooling -- Setspace thermostat toOFFposition. Tostmt unit,turnonmainpowersupply. Setsystem selector switchat COOLposition andfanswitch atAUTO.position. Adjustthermostat toasetting belowroomtemperature. Compressor starts onclosure ofcontacto_: Check unitcharge. RefertoRefrigerant Charge section on page 43. Resetthermostat at a position aboveroomtemperature. Compressor will shutoff.Evaporator fanwill shutoffaftera 30-second delay. TOSHUTOFFUNIT-- Setsystem selector switchatOFF position. Resetting thermostat ata position above roomtemperature shuts unitofftemporarily untilspace temperature exceedsthermostat setting.Unitsmeequipped with CycleLOCTM protection device. Unit shuts down on any safety trip, and indicator light on thermostat all safety trips. -require no adjustment. ELEVATION (ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 comes on. Check reason for Main burnel_ me factory set and should 3. 4. 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 Natural Gas Orifice Sizet 33 36 Liquid Propane Orifice Size]43 44 36 37 Natural Gas Orifice Size]- BTUH INPUT Liquid Propane Orifice Size]- 3O 37 31 39 45 45 31 40 32 41 38 40 46 47 32 42 34 43 41 42 48 49 35 43 36 44 43 44 50 50 37 45 39 46 45 46 51 52 41 47 42 48 47 48 52 53 43 49 44 50 Liquid Propane Orifice Size]45 Natural Gas Orifice Size 32 Liquid Propane Orifice Size]42 40 41 47 48 33 35 43 43 42 43 49 49 36 37 44 45 43 44 50 50 38 39 45 46 45 46 51 52 41 42 47 48 47 48 52 53 43 44 49 50 49 50 53 54 44 46 51 52 51 54 47 52 Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature. The induced-draft motor will start. 5. After a call for heating, the main burnel_ should light wifllin 5 seconds. If the burner does not light, then fllere is a 22-second delay before anofller 5-second try. If the burner still does not light, file time delay is repeated. If the burner does not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to WI. 6. The evaporator-fan motor will turn on 45 seconds after burner ignition. The evaporator-fan motor will turn off in 45 seconds after the fllermostat temperature is satisfied. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate. Table 31A -- Altitude Compensation* -48HJ004-007 Standard Units ELEVATION (ft) Natural Gas Orifice Size]38 1. Purge gas supply line of air by opening union ahead of the gas valve. If gas odor is detected, tighten union and wait 5 minutes before proceeding. 2. Turn on electrical supply and manual gas valve. Refer to Tables 3 IA and 31B for the correct orifice to use at high altitudes. 150,000 NOMINAL 120,000 BTUH NOMINAL INPUT Heating TO CHECK ignition of main burners and heating controls, move thermostat set point above room temperature and verify that the burners light and evaporator fan is energized. Check heating effect, fllen lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off. 72,000 AND 115,000 BTUH NOMINAL INPUT 60,000 AND 90,000 BTUH NOMINAL INPUT -- *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, the input rate should be reduced at higher altitudes. 1-Orifices are available through your local Carrier distributor. Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF and then to ON position. Main Burners Table 31 B -- Altitude Compensation* 48HJ004-006 Low NOx Units 7. 8. NOTE: The default value for the evaporator-fan motor on/off delay is 45 seconds. The Integrated Gas Unit Controller (IGC) modifies this v_flue when abnormal limit switch cycles occm: Based upon unit operating conditions, the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds. When one flash of the LED (light-emitting diode) is observed, the evaporator-fan on/off delay has been modified. If the limit switch trips at the st_ut of the heating cycle during the evaporator on delay, the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan on delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second leduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating. *As the height above sea level increases, there is less oxygen per cubic foot of air. Therefore, heat input rate should be reduced at higher altitudes. 1-Orifices available through your Carrier distributor. 38 Theevaporator-fan offdelaycanalsobemodified. Once the callforheating hasended, thereisa 10-minute periodduring whichthemodification canoccm: If thelimitswitch tripsduringthisperiod, theevaporator-fan off delaywill increase by 15seconds. A maximum of9 tripscanoccm:extending the evaporator-fan offdelayto180seconds. Torestore theoriginal default value, resetthepowertothe unit. TOSHUTOFFUNIT--Set system selector switchat off position. Resetting heating selector leverbelowroomtemperaturewill temponuily shutunitoffuntilspace temperature falls belowthermostat setting. Safety Relief --A soft-solder joint at the suction service Schmder port provides pressure relief under abnorm_fl temperature and pressure conditions. Ventilation (Continuous Fan)- Set fan and system selector switches at ON and OFF positions, lespectively. Evaporator ftm operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off. Operating Sequence be proportionally closed. Damper position will follow the higher demand condition from DCV mode or free cooling mode. Damper movement from full closed to full open (or vice versa) will take between 11/2and 21/2 minutes. If free cooling can be used as determined fi_m the appropriate changeover command (switch, dry bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a c;dl for cooling (YI closes at the thermostat) will cause the control to modulate the dmnpers open to maintain the supply air temperature set point at 50 to 55 E As the supply air temperature drops below the set point range of 50 to 55 H the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature. HEATING. UNITS WITH ECONOMISER IV -- When the room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the thermostat is satisfied, the economizer damper moves to the minimum position. COOLING. UNITS WITH ECONOMISER2, PREMIERLINK TM CONTROL AND A THERMOSTAT -- When free cooling is not available, the compressors will be controlled by the PremierLink control in response to the YI and Y2 inputs fi_m the thermostat. The PremierLink control will use the following information determine if free cooling is available: Indoor fan has been on for at least 30 seconds. The SPT. SAT. and OAT inputs must have valid readings. OAT must be less than 75 E OAT must be less than SPT. Enthalpy must be LOW (may be jumpered if an enthalpy sensor not available). • Economizer position is NOT forced. Pre-cooling occurs when the is no call from the thermostat except G Pre-cooling is defined as the economizer modulates to provide 70 F supply all: When free cooling is available the PremierLink control will control the compressors and economizer to provide a supplyair temperature determined to meet the YI and Y2 calls from the thermostat using the following three routines. The three control routines are based on OAT. COOLING. UNITS WITHOUT ECONOMIZER -- When thermostat c',_ls for cooling, terminals G and YI me energized. The indoor-fan contactor (IFC) and complessor contactor tue energized and indoor-fan motol: complessol: and outdoor fan start. The outdoor fan motor runs continuously while unit is cooling. HEATING. UNITS WITHOUT ECONOMIZER --When the thermostat calls for heating, terminal WI is energized. To prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when WI is energized. The induced-draft motor is energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additiomfl heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the therlnostat is satisfied and WI is deenergized, the [FM stops after a 45-second time-off dek% COOLING. UNITS WITH ECONOMISER IV -- When free cooling is not available, the compressoLs will be controlled by the zone thermostat. When fiee cooling is available, the outdoor-air damper is modulated by the EconoMiSer IV control to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperatme fluctuates above 55 or below 50 H the dampeLs will be modulated (open or close) to bring the supply-air temperatme back within the set points. Integrated EconoMiSer IV operation on single-stage units requires a 2-stage thermostat (YI and Y2). For EconoMiSer IV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode. to • • • • • The 3 routines are based on OAT where: SASP = Supply Air Set Point DXCTLO = Direct Expansion Cooling Lockout Set Point PID = Proportional Integral Routine 1 (OAT < DXCTLO) • • YI energized (SATLOI + 3). Y2 energized (SATLO2 + 3). Routine 2 (DXCTLO • If the increase in cooling capacity causes the supply-air temperature to drop below 45 F, then the outdoor-air damper position will be fi._lly closed. If the supply-air temperature continues to frill, the outdoor-air dmnper will close. Control returns to norm_d once the supply-air temperature rises above 48 E • • • • If optional power exhaust is inst_dled, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. • If field-installed accessory CO2 sensors are connected to the EconoMiSer IV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the inoease in fresh ail: the outdoor-air damper will • 39 economizer maintains a SASP = economizer maintains a SASP = < OAT < 68 F) If only YI energized, the economizer maintains a SASP = (SATLOI + 3). If SAT > SASP + 5 and economizer position > 80%, economizer will go to minimum position for 3 minutes or until SAT > 68 E First stage of mechanical cooling will be energized. Integrator resets. Economizer opens again and controls to current SASP after stage one on for 90 seconds. With YI and Y2 energized Economizer maintains an SASP = SATLO2 + 3. If SAT > SASP + 5 and economizer position >80%. economizer will go to minimum position for 3 minutes or until SAT > 68 E • • • • • If compressor one is on then second stage of mechanical cooling will be energized. Otherwise the first stage will be energized. Integrator resets. Economizer opens again and controls to SASP after stage one on for 90 seconds. Routine 3 (OAT > 68) The high space set point is used for DX (direct expansion) cooling control, while the economizer space set point is a calculated value between the heating and cooling set points. The economizer set point will always be at least one degree below the cooling set point, allowing for a smooth transition fi'om mechanical cooling with economizer assist, back to economizer cooling as the cooling set point is achieved. The compressors may be used for initial cooling then the PremierLink controller will modulate the economizer using an error reduction calculation to hold the space temperature between the heating and cooling set points. See Fig. 48. Economizer is opened 100%. Compressors 1 and 2 are cycled based on YI and Y2 using minimum on and off times and watching the supply air temperature as compared to SATLOI and SATLO2 set points. The controller uses the following economizer cooling: If optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. • • • • • • If field-installed accessoly CO2 sensors ale connected to the PremierLink TM control, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the dmnper will be increased proportionally. As the CO2 level decreases because of the increase in fresh aik the outdoor-air dmnper will be proportionally closed. HEATING, UNITS WITH ECONOMISER2, PREMIERLINK CONTROL AND A THERMOSTAT -- When the thermostat calls for heating, terminal Wl is energized. The PremierLink control will move the economizer damper to the minimum position if there is a call for G and closed if there is a call for WI without G In order to prevent thermostat from short cycling, the unit is locked into the heating mode for at least 10 minutes when WI is energized. The induced-draft motor is then energized and the burner ignition sequence begins. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and WI is deenergized, the IFM stops after a 45-second time-off delay unless G is still maintained. COOLING. UNITS WITH ECONOMI$ER2, PREMIERLINK CONTROL AND A ROOM SENSOR -- When free cooling is not available, the compressors will be controlled by the PremierLink controller using a PID Error reduction calculation as indicated by Fig 47. conditions to determine Enthalpy is Low SAT reading is available OAT reading is available SPT reading is available OAT < SPT Economizer Position is NOT forced If any of the above conditions are not met, the economizer submaster reference (ECSR) is set to maximum limit and the damper moves to minimum position. The operating sequence is complete. The ECSR is recalculated evely 30 seconds. If an optional power exhaust is installed, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessoly CO: sensors me connected to the PremierLink TM control, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO: set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in flesh aik the outdoor-air damper will be proportionally closed. TEMPERATURE LU CONTROL 75_ ; .................. 741 '_ 73 Lu The PremierLink controller will use the following information to determine if fiee cooling is available: • Indoor fan has been on for at least 30 seconds. • The SPT, SAT, and OAT inputs must have valid readings. • OAT must be less than 75 E • OAT must be less than SPT. • Enthalpy must be LOW (may be jumpered if an enthalpy sensor is not available). • Economizer position is NOT forced. ...... SET m_'_"71 ua -- POINT TEMPERATURE 70 o 694 CO 68J TIME NOTE: PremierLink control performs smart staging of 2 stages of DX cooling and up to 3 stages of heat. Fig. 47 -- When flee cooling is available, the outdoor-air damper is positioned through the use of a Proportional Integral (PID) control process to provide a calculated supply-air temperature into the zone. The supply air will maintain the space temperature between the heating and cooling set points as indicated in Fig. 48. DX Cooling Temperature Control Example TEMPERATURE LU ££ The PmmierLink control will integrate the compressol.s stages with the economizer based on similm logic as the three routines listed in the previous section. The SASP will float up and down based on the error reduction calculations that compme space temperature and space set point. £[2 LU 0. LU pLU © When outside-air temperature conditions require the economizer to close for a compressor stage-up sequence, the economizer control integrator is reset to zero after the stage-up sequence is completed. This prevents the supply-air temperature fiom dropping too quickly and creating a fieeze condition that would make the compressor turn off prematurely. 75 73 741_" 72 ......... _ 71 I _ 70Ji - ....... 69 O3 CONTROL 68 J // _ .................................... ------ COOL SETPOINT X_.,__ __ TEMPERATURE --- HEAT SETPOINT .......................... TIME Fig. 48 -- Economizer Control 4O Temperature Example HEATING. UNIT WITH ECONOMISER2, PREMIERLINK CONTROL AND A ROOM SENSOR -- Every 40 seconds the controller will calculate the required heat stages (maximum of 3) to maintain supply-air temperature (SAT) if the following qu_flifying conditions ale met: • Indoor fan has been on for at least 30 seconds. • COOL mode is not active. • OCCUPIED, TEMRCOMPENSATED START or HEAT mode is active. • SAT reading is available. • Fire shutdown mode is not active. / If all of the above conditions are met, the number of heat stages is c_dculated; otherwise file required number of heat stages will be set to 0. If the PremierLink controller determines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied. Staging should be as follows: Fig. 49 -- Humidi-MiZer Normal Design Cooling Operation If Heating PID STAGES=2 • • HEAT STAGES=I HEAT STAGES=2 (50% capacity) will energize HSI (100% capacity) will energize HS2 If Heating PID STAGES=3 and AUXOUT = HS3 • • • HEAT STAGES=I (33% capacity) will energize HSI HEAT STAGES=2 (66% capacity) will energize HS2 HEAT STAGES=3 (100% capacity) will energize HS3 In order to prevent short cycling, the unit is locked into the Heating mode for at least 10 minutes when HS 1 is deenergizedi When HSI is energized the induced-&aft motor is then energized and the burner ignition sequence begins. On units equipped for two stages of heat, when additional heat is needed, HS2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the space condition is satisfied and HSI is deenergized file IFM stops after a 45-second time-off delay unless in the occupied mode. The fan will mn continuously in the occupied mode as required by natiomfl energy and fresh _fir standards. UNITS WITH HUMIDI-MIZER TM ADAPTIVE DEHUMIDIFICATION SYSTEM Normal Design Cooling Operation -- When the rooftop operates under the normal sequence of operation, the compressors will cycle to maintain indoor conditions. See Fig. 49. Fig. 50 -- Humidi-MiZer Subcooling Mode Operation The Humidi-MiZer a&tptive dehumidification system includes a factory-installed Motormastel@ low ambient control to keep the head and suction pressure high, allowing normal design cooling mode operation down to 0 ° E Subcooling mode operates only when the outside air temperature is winmet than 40 E A factory-installed temperature switch located in the condenser section will lock out subcooling mode when the outside temperature is cooler than 40 IF. Subcooling Mode -- When subcooling mode is initiated, this will energize (close) file liquid line solenoid valve (LLSV) forcing the hot liquid refiigemnt to enter into the subcooling coil (see Fig. 50). The scroll compressors are equipped with crankcase heaters to provide protection for the compressors due to the additional refrigerant charge required by the subcoolin_reheat coil. As the hot liquid refrigerant passes through the subcooling/ reheat dehumidification coil, it is exposed to the cold supply airflow coming through the evaporator coil. The liquid is runlet subcooled to a temperature approaching the evaporator leaving-air temperature. The liquid then enters a thermostatic expansion valve (TXV) where the liquid drops to a lower pressure. The TXV does not have a pressure drop great enough to change the liquid to a 2-phase fluid, so the liquid then enters the Acutrol TM device at the evaporator coil. When in subcooling mode, there is a slight decrease in system total gross capacity (5% less), a lower gross sensible capacity (20% less), and a greatly increased latent capacity (up to 40% more). The liquid entel_ file evaporator coil at a temperature lower than in standard cooling operation. This lower temperature increases the latent capacity of the rooftop unit. The refrigerant passes through the evaporator and is turned into a vapol: Tile air passing over the evaporator coil will become colder than during normal operation. However. as this same air passes over the subcooling coil, it will be slightly warmed, parti_flly reheating the air. This hot gas will mix with liquid refrigerant leaving file condenser coil and flow to the subcoolin_reheat dehumidification coil. Now the conditioned air coming off the evaporator will be cooled and dehumidified, but will be warmed to neutral conditions (72 F to 75 F) by the subcooling/reheat dehumidification coil. Hot Gas Reheat Mode -- When the humidity levels in the space require humidity control, a hot gas solenoid valve (specific to hot gas reheat mode only) will open to bypass a portion of hot gas lefiigerant mound the condenser coil (see Fig. 51). 41 Theneteffectoftherooftop wheninhotgasreheat mode is toprovide nearly_dllatentcapacity lemoval fiomthespace whensensible loadsdiminish (when outdoor temperatme conditionsaremoderate). Whenin hotgasreheat mode, fileunit will operate toprovide mostlylatentcapacity andextremely lowsensible heatratiocapability. Similar tothesubcooling mode ofoperation, hotgasreheat mode operates onlywhentheoutside airtemperature iswanner than40E Belowthistemperature, a factory inst_flled outside airtemperature switch willlockout thismode ofoperation. SeeTable 32fortheHumidi-Mizer a&tptive dehumidificationsystem sequence ofoperation. 2. 3. 4. [f economizer or two-position dmnper is installed, remove economizer by disconnecting Molex plug and removing mounting screws. Slide filters out of unit. 5. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean watel: For best results, back-flush towmd return-air section to remove foreign material. Flush condensate pan after completion. Reinst_dl economizer and filters. 6. Reconnect wiring. 7. Replace access panels. CONDENSER COIL--Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoor air conditions. One-Row Coil -- Wash coil with commercial is not necessary to remove top panel. 2-Row Coils Clean coil as follows: LPS coil cleanel: It 1. Turn offunit powel: tag disconnect. 2. Remove top panel screws on condenser end of unit. 3. Remove condenser coil corner post. See Fig. 52. To hold top panel open, place coil corner post between top panel and center post. See Fig. 53. 4. Remove screws securing coil to complessor plate and compressor access panel. 5. Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 54. j Fig. 51 -- Humidi-Mizer TM Hot Gas Reheat Mode Operation SERVICE 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the norm_d mannel: 7. Secure inner and outer coil rows together supplied fastenel: Reposition the outer coil section and remove ner post fiom between the top panel and Reinstall the coil corner post and replace all 8. When servicing unit, shut off all electrical power to unit and inst',_l lockout tag to avoid shock hazard or injury from rotating parts. at FILTERS -- Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be stone dimensions as origimd filters. OUTDOOR-AIR INLET SCREENS -- Clean screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screen. -- Inspect unit interior at the beginning of heating and cooling season and as operating conditions requile. EVAPORATOR CO[L Remove the coil corcenter post. screws. CONDENSATE DRAINCheck and clean each year start of cooling season. In wintel: protect against freeze-up. Cleaning 1. Turn unit power off. tag disconnect. coil access panel. with a field- evaporator Table 32 -- Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and System Response -- Single Compressor Unit (48HJ004-007) THERMOSTAT H Off On On On On On INPUT Y1 Y2 On On On On Off On Off On Off Off ECONOMIZER OAT. < Economizer FUNCTION Set Point I 48HJ Economizer No Off No Yes Yes Off On On No Off LEGEND OAT -- Outdoor AirTemperature Comp. 1 I Normal Operation On On On On On NOTE: be off. 42 Subcooling On a thermostat UNIT OPERATION Mode I Hot Gas Reheat Yes No Yes Yes No No No Yes No call for W1, all cooling Mode Yes and dehumidification will Lubrication COMPRESSORS -- Each compressor amount of oil at the factory. NO CHARGEUse standard evacuating techniques. After evacuating system to 500 microns, weigh in the specified mnount of refrigerant. (Refer to Table 1 and unit information plate.) is chmged with correct FAN MOTOR BEARINGS -- Fan motor bemings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser-fan or evaporator-fan motors is required. Condenser-Fan Adjustment (Fig. 55) -- LOW CHARGE COOLING -- Using Cooling Charging Ch;uts, Fig. 56-59, vary refrigerant until the conditions of the chmls are met. Note the charging charts are different from type normally used. Chmls are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit. Shut off unit power supply. Relnove condenser-fan assembly (grille, motol: motor cover, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 55. Tighten setsclews and replace condenser-fan assembly. EconoMi$er EconoMi$er IV Adjustment-- IV and EconoMi$er2 Refer to Optional section on page 18. COIL CORNER POST Evaporator Fan Belt Inspection dition of evaporator belt or tension during inspections or as conditions necessary. lequile. -Check conheating and cooling Replace belt or adjust as CENTER BAFFLE TOP PANEL High-Pressure Switch -- The high-pressure switch contains a Schrader core depressor, and is located on the compressor hot gas line. This switch opens at 428 psig and closes at 320 psig. No adjustments are necessary. Loss-of-Charge Switch -- The loss-of-charge switch contains a Schrader core depressor, and is located on the compressor liquid line. This switch opens at 7 psig and closes at 22 psig. No adjustments me necessary. COMPRESSOR ACCESS PANEL Freeze-Stat -- _n_e freeze-stat is a bimetal temperaturesensing switch that is located on the "hair-pin" end of the evaporator coil. The switch protects the evaporator coil from fleeze-up due to lack of airflow. The switch opens at 30 F and closes at 45 E No adjustments are necessary. CONDENSER COIL Fig. 53 -- Propping Up Top Panel TOP VIEW PANEL Refrigerant Charge--Amount of refrigerant charge is listed on unit namepkite (also refer to Table 1). Refer to HVAC Servicing Procedures literature available at your local distributor and the following procedures. ENTER Unit panels must be in place when unit is operating during chm'ging procedure. Unit must operate a minimum of 10 minutes before checking or adjusting refrigerant charge. CONDENSER COIL An accurate superheat, themlocouple-type or thermistortype thermometer, and a gage manifold are required when using the supeflleat charging method for evaluating the unit chage. Do not use menuiw or small dia/-_'pe thermometers be_ztu.w they am not adequaW _br this 0)')e qf measurement. REMOVE SCREWS TOP PANEL REMOVE SCREWS INNERCOIL REMOVE CONDENSER OUTER COILSECTION CONTROL POST CORNER POST 102 mm (4") MAX \ / HAIRPIN END CLEAN Fig. 54 -- Separating COILCENTER POST ACCESS PANEL BAFFLE REMOVE SCREWS CONDENSER COIL UNIT 48HJ 004-006 and 007 (208/230 V) 007 (460 and 575 V) REMOVE COIL CORNER POST Fig. 52 -- Cleaning Condenser Coil Fig. 5543 Condenser-Fan Coil Sections FAN HEIGHT-- "A" (in.) 2.75 3.50 Adjustment HUMIDI-MIZER TM SYSTEM CHARGING -- The system charge for units wifll the Humidi-MiZer a&tptive dehumidification system is greater than that of the standard unit _flone. The charge for units with this option is indicated on the unit nmneplate &awing. Also lefer to Fig. 60-63. To charge systems using the Humidi-MiZer a&tptive dehumidification system, fully evacuate, recoven and recharge the system to the nmneplate specified charge level. To check or adjust refrigerant chalge on systems using the Humidi-MiZer adaptive dehumidification system, charge per Fig. 60-63. use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. The chin-Is reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooling/ reheat dehumidification coil. A tap is provided on the unit to measure liquid pressure entering the subcooling/reheat dehumidification coil. IMPORTANT: The subcooling mode charging ch_u-ts (Fig. 60-63) me to be used ONLY with units having the Humidi-MiZer adaptive dehumidification system. IN) NOT use stan&Lrd chm'ge (Fig. 56-59) for units with HumidiMiZer system, and DO NOT use Fig. 60-63 for standmd units. NOTE: When using the charging chin-Is, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to !!!!! 75[ : : : 68_ : :: ; ;; IIIIIIII 68£ : : ; : I00- I I I I I [ | ! i12_ _621 90 -- 125 52 65 18 55 13 I L--Ill I. 55; u w _ w IIIIIIII IIIIIIII iiiii Ill [A- _621 o 1.3 < o B vsE11_ : : !!!!! iiiii IIIFI lJ._ IJlrl Atrt I_l.- 48." r I £...t,q _'gl uJ _41, z o 34 _, 48: _BO- F_-.-rqI_t-- _70- _ "i I I 3_"- _P'_.. ! ! _ :::11 ::::1 o=6°- _iiiii _iiiii s 45 _ ? llllll it_Jl 1I IIIIIllt ::::: _llll ::::: llllllll i!!ii! 27( :::::: llllllll IIIIIIII IIIIIIII !ll]lI IIIIIIII iiiiii 40 I 80 SUCTION LINE I I 4 10 TEMPERATURE (*F) I 16 211 SUCTION _7 SUCTION LINE TEMPERATURE ('C) Fig. 56 -- Cooling Charging Standard 48HJ004 LINE TEMPERATURE ('F) I 312 SUCTION LINE TEMPERATURE Chart, ('C) Fig. 58 -- Cooling Charging Standard 48HJ006 758 IIIIIIIIIIIIIIIIIII IIIIIIIIIIItll 110 IIIII lllllllll]llllllllll 'Ill 68_ 100 Chart, I IIIIIII , IIIIIIIII llllll'lll IIIIIIIIIII 5 °' , IIIII1,,,,,_-. IIIII llllll[ IIIIIIlIL-'VL--'r/ , _n g I I I I t I I i[lllllllll_lII_I I I I L_M_J/1 iiiIfli/_i/rl/f g !!llllll_A_l_ll1_Ifllll,_ I I I I I 11_ IIF I _I I II I I I I'IA_I I_ 48: N?O $ o_ ill ii g I I I_I llllll_l I I I I_I I I I I I I I Y_XI IIIIIIIII/IVII I_I I ll,x,,,,,,,l,,, ,,,,,,, I I IA IN I I z,_,,, ,,Aq_ll, lllllllIIIlIIIIIl/lllII 34. _ g50 lllllllllllllllll IIllllllllllll Illl!l Illlllllll!, lllllll]llllllllllll IIIIIIIIIIIIII 27f IIIIIIIIIIIII Ul 40 iI I I I I IYl/ / !'l,,_,,llllt, Z .l_1 _M t_11111/ I ,,iii I I ,, iiii" ' IIIII lllll l',IIl II I llllllllIlllllll I I I iiiii llllllllllll,,lllll, IIIIIIIIIIIIIIIIIIII llllllllllllIlllllllll IIIIIIIIIIIIIIIIIIIIII SUCTION LINE TEMPERATURE IIIIII (*F) SUCTION ,CTiON LIRE TEMPERATURE Fig. 57 -- Cooling Charging Chart, Standard 48HJ005 1_ _CTIOM LINE TENPERAT_E Fig. 59- 44 LINE TEM_RATURE _ l 116 70 ('F) 211 OC) Cooling Charging Chart, Standard 48HJ007 I TO USE COOLING CHARGING CHART, STANDARD UNIT--Take the outdoor ambient temperature trod mad the suction pressure gage. Refer to ch_uts to detennine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low. carefully recover some of file charge. Recheck the suction pressure as charge is adjusted. Exmnple (Fig. 58): Outdoor Temperature ............................... 75 F Suction Pressure ................................ 70 psig Suction Temperature should be ....................... 48 F (Suction temperature may vtu'y _+5 ° E) TO USE COOLING CHARGING CHARTS, UNITS WITH HUMIDI-MIZER TM ADAPTIVE DEHUMIDIFICATION SYSTEM--Refer to charts (Fig. 60-63) to determine the proper leaving condenser pressure and temperature. Exmnple (Fig. 60): Leaving Condenser Pressure ..................... 250 psig Leaving Condenser Temperature ................... 105 F NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. If a charging device is used, temperature and pressure readings must be accomplished using the charging charts. CAIN N CHARGING CHART 3 TON - 60HZ (APPI ICABLE ONLY WHEN CO!l 15IN SUBCOOLING'P_30E) 680LIN6 OUTOOORFAN MUST_ PRESSUR_L_AVING CO_DENS_R(PSIG) MODE CHARSINt'3 CHART 4 TON 50HZ ONLY WHEN COIL IS IN 5UBOOOLING MODE) 1so _ 2_ _o i_ 1so COOLING (APPLICABLE COIL IS IN SUBCOOLiNG MODE ) 2oo 2so _oo 3so 4oo ONLY _ CHkR61_ CHi_T 6 TON 60HZ WHEN COIL ISIN SUBCOOLING MODE ) oumooRFANMUSTaE OPERATING OUTOOOR FAN MUSTBE OPERATING LIgtllD CHART GOHZ WHEN Fig. 62 -- Cooling Charging Chart, 48HJ006 with Optional Humidi-MiZer Adaptive Dehumidification System CODLIN8 mo C_IIR6Itl6 tON NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. Fig. 60 -- Cooling Charging Chart, 48HJ004 with Optional Humidi-MiZer Adaptive Dehumidification System SD ONLY Lt_UID PRESSURE LEAVING CONOE_SER _SIS) NOTE: When using the charging charts, it is important that only the subcoolin( _reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidification coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. (APPLICABLE ICABLE OPERATIN6 _o LI_UI_ _ 5 (APPL _o 4Do 4_ PRESSURE LEAVIN6 CONDENSER (PSIG) NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidgication coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. NOTE: When using the charging charts, it is important that only the subcooling/reheat dehumidification coil liquid line solenoid valve be energized. The subcoofing/reheat dehumidgication coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed. Fig. 61 -- Cooling Charging Chart, 48HJ005 with Optional Humidi-MiZer Adaptive Dehumidification System Fig. 63 -- Cooling Charging Chart, 48HJ007 with Optional Humidi-MiZer Adaptive Dehumidification System 45 Main Burners -- At the beginning of each heating sea- Flue Gas Passageways -- To inspect the flue collector box and upper areas of the heat exchanger: son, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust, if necessary. 1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section below. 2. Remove the 3 screws holding the blower housing flue coveg 3. Remove the flue cover to inspect the heat exchangel: 4. Clean all surfaces as required using a wire blush. Combustion-Air to the When servicing gas train, do not hit or plug orifice spuds. REMOVAL AND REPLACEMENT (See Fig. 64 and 65) Blower-- sure proper airflow wheel every fall and fil.st heating season, mine proper cleaning Clean periodically to enand heating eft]ciency. Inspect blower periodically during heating season. For the inspect blower wheel bimonthly to deterfrequency. 3. induced-draft 5. To reinstall, reverse the procedure Remove compressor 4. Slide out burner compartment 5. Disconnect 6. Remove wires connected 7. Remove induced-draft motol, ignitor, and sensor wires at the Integrated Gas Unit Controller (IGC). Remove the 2 screws that attach the burner rack to the vestibule plate. 8. 9. 10. access panel. side panel. gas piping at unit gas valve. to gas valve. Mark each wire. Remove the gas valve bracket. Slide the burner tray out of the unit (Fig. 65). 11. To reinstall, reverse the procedure To remove motor, remove the 4 screws that hold the motor to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate. 6. TRAIN 3. motor Slide the motor and blower wheel assembly out of the blower housing. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5. To remove blower from the motor shaft, remove 2 setscrews. 4. GAS 1. Shut offmanual gas valve. 2. Shut off power to unit, tag disconnect. To inspect blower wheel, remove draft hood and screen. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows: 1. Slide burner access panel out. 2. Remove the 5 screws that altach assembly to the vestibule covel: OF outlined above. INDUCEDDRAFT MOTOR ROLLOUT SWITCH outlined above. PLATE Limit Switch- Remove blower access Limit switch is located on the fan deck. panel (Fig. 7). Burner Ignition -- Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 12). A single LED on the [GC provides a visual display of operational or sequentkd problems when the power supply is uninterrupted. The LED can be observed through the viewport. When a break in power occurs, the IGC will be reset (resulting in a loss of fault history) and the evaporator fan on/off times delay will be reset. Dnring servicing, refer to the label on the control box cover or Table 33 for an explanation of LED error code descriptions. If lockout occurs, unit may be reset by interrupting power supply to unit forat least 5 seconds. Table 33 -- SECTION EXHAUST - VESTIBULE PLATE DRAFT MOTOR "BLOWER HOUSING PRESSURE TAP "GAS VALVE Fig. 64 -- Burner Section Details LED Error Code Description* LED INDICATION ERROR CODE DESCRIPTION ON OFF Normal Operation Hardware Failure 1 Flasht 2 Flashes 3 Flashes 4 Flashes Evaporator Fan On/Off Delay Modified Limit Switch Fault Flame Sense Fault 4 Consecutive Limit Switch Faults 5 6 7 8 9 Ignition Lockout Fault Induced-Draft Motor Fault Rollout Switch Fault Internal Control Fault Software Lockout Flashes Flashes Flashes Flashes Flashes S MANIFOLD PRESSURE f-_ TAP _ LEGEND LED-Light-Emitting Diode *A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence. ]-Indicates a code that is not an error. The unit will continue to operate when this code is displayed, information. IMPORTANT: Refer to Troubleshooting Tables 34-38 for additional GAS VALVE BURNERS Fig. 65 -- Burner Tray Details I_ 46 F¸ CLEANING AND ADJUSTMENT Replacement 1. Remove burner rack from unit as described Parts -- A complete list of replacement parts may be obtained froln any Carrier distributor upon request. Refer to Fig. 67 for a typical unit wiring schelnatic. above. 2. Inspect burners and, if dirty, remove burners from rack. 3. Using a soft blush, clean burners and cross-over required. 4. 5. Adjust spark gap. See Fig. 66. Reinst_dl burners on rack. 6. Reinst_dl burner rock as described port as above. SEE DETAIL"(3" / / SEEDETAIL "E" LOW H EAT 48HJE/H004, 48HJD/G005-00772,000 BTUH INPUT 48HJM004, 48HJL005,006 -- 60,000 BTUH INPUT L 2 L t" \ ./ "F \ SEE DETAIL _" L MEDIUM AND HIGH HEAT 48HJE/H005-007, 48HJF/K004 -- 115,000 BTUH INPUT 48HJF/K005-007 -- 150,000 BTUH INPUT 48HJM005,006; 48HJN004 -- 90,000 BTUH INPUT 48HJN005,006120,000 BTUH INPUT SPARK GAP .120/.141 IN. (3.05/3.56 mm) DETAIL SPARK GAP MUST BE POSITIONED IGNITE ON FIRST TRY. (PLACE SPARK GAP WITHIN BURNER CIRCUMFERENCE AS SHOWN) TO *C* ,yN. DETAIL Fig. 66 -- Spark Gap Adjustment 47 (4.60 ram) "E" SCHEHATIC 208/230 3 BO CLO SEE NOTE *3 _ EQUP GND i i GRN/YELI_ I ONNECTIOI BOARD PL6 R FOR STD UNIT PL6 ECONOMI*ER I_ --PNK RED --<_l- .YEL* .BLU. -BLK- --BRN. --RED° Y --GRA. --pNKI o iovoc/420MA CONTROLLER J CONNECTIONFOR ECONOMIZER FACTORYOR FIELD L INSTALLED NOTES: 1, If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 2, Three phase motors are protected under primary single phasing conditions. 3, Use copper conductors only. 4, TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from 230 v tap (ORN) and connect to 208 v tap (RED). Insulate end of 230 v tap. O@ COMPOIENTARRANGEMENT LEGEND C CAP CLO COMP EQUIP FPT FU GND HPS HS ----------- Contactor, Compressor Capacitor Compressor Lockout Compressor Motor Equipment Freeze Up Protection Thermostat Fuse Ground High-Pressure Switch Hall-Effect Sensor IIDM IFC IFM IGC LPS LS MGV --------- Ignitor Induced-Draft Motor Indoor Fan Contactor Indoor Fan Motor Integrated Gas Unit Controller Low-Pressure Switch Limit Switch Main Gas Valve OFM OLR P PL QT RS SAT TRAN --------- _ _ O Fig. 67 -- Typical Wiring Schematic Outdoor (Condenser) Fan Motor Overload Relay Plug Plug Assembly Quadruple Terminal Rollout Switch Supply Air Temperature Sensor Transformer _ Field Splice _ Field Power Wiring Marked Wire ----- Accessory _ To indicate common potential only; not to represent wiring. Terminal (Marked) O Splice Splice (Marked) Factory Wiring Field Control Wiring or Optional Wiring Terminal (Unmarked) Terminal Block and Component 48 Arrangement (208/230-3-60 Shown) TROUBLESHOOTING Unit Troubleshooting troubleshooting -- Refer to Tables 34-38 for unit details. Table 34 -- LED Error Code Service Analysis SYMPTOM CAUSE REMEDY Hardware Failure. (LED OFF) Loss of power to control module (IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. Fan ON/OFF Delay Modified (LED/FLASH) High limit switch opens during heat exchanger warm-up period before fan-on delay expires. Ensure unit is fired on rate and temperature Limit switch opens within three minutes after blower-oft delay timing in Heating mode Ensure units' external static pressure is within application Limit Switch Fault. (LED 2 Flashes) High temperature Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate. Flame Sense Fault. (LED 3 Flashes) The IGC sensed flame that should not be )resent. Reset unit. If problem persists, replace control board. 4 Consecutive Limit Switch Faults. (LED 4 Flashes) Ignition Lockout. (LED 5 Flashes) Inadequate airflow to unit. Check operation of indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unit nameplate information. Unit unsuccessfully 15 minutes. Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas. Induced-Draft Motor (LED 6 Flashes) Fault. limit switch is open. attempted ignition for rise is correct. guidelines. IGC does not sense that induced-draft motor is operating, Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1-- White, PIN 2 -- Red, PIN 3-- Black. Rollout Switch Fault. (LED 7 Flashes) Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect. Internal Control Fault. (LED 8 Flashes) Temporary Software Lockout (LED 9 Flashes) Microprocessor has sensed an error in the software or hardware. Electrical interference is impeding the IGC software, If error code is not cleared by resetting unit power, replace the IGC. Reset 24-v to control board or turn thermostat off and then on. Fault will automatically reset itself in one hour. heating section Refer troubleshooting IMPORTANT: to heatinginformation. troubleshooting If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken. LEGEND IGC LED 49 --- Integrated Gas Unit Controller Light-Emitting Diode for additional I I Table 35 -- Heating Service Analysis CAUSE REMEDY electrodes. Check flame ignition and sensor electrode positioning. Adjust as needed. Check gas line for air purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes before attempting to relight unit. Check gas valve. PROBLEM Burners Ignite. Will Not Misaligned spark No gas at main burners. Water in gas line. No power to furnace. Drain water and install drip leg to trap water. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection require a cool-down period before resetting. Check 24-v circuit breaker; reset if necessary. Miswired or loose connections. Check all wiring and wirenut connections. Replace thermostat. Burned-out heat anticipator in thermostat. Broken thermostat wires. Inadequate Heating, Poor Flame Characteristics. Dirty air filter. Run continuity check. Replace wires, if necessary. Clean or replace filter as necessary. Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input, if too low, increase manifold pressure or replace with correct orifices. Unit undersized for application. Restricted airflow. Replace with proper unit or add additional unit. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units, Adjust pulley. Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. Too much outdoor air. Adjust minimum position. Check economizer operation. Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO (carbon monoxide), sooting flame, or floating flame. Check all screws around flue outlets and burner compartment. Tighten as necessary. Cracked heat exchanger. Overtired unit -- reduce input, change orifices, or adjust gas line or manifold )ressure. Check vent for restriction. Clean as necessary. Burners Will Not Turn Off. Unit is locked into Heating one minute minimum. Table 36 -- Humidi-MiZer TM Adaptive Dehumidification Low System Capacity, Table 37 -- Humidi-MiZer PROBLEM Mode Will Not Energize. Liquid line solenoid valve will not operate. Liquid line solenoid valve will not open. Low refrigerant TM charge or frosted evaporator Thermostatic expansion Adaptive Dehumidification coil. valve (TXV). Check power source and evaporator-fan wire connections are tight. relay. Ensure all 1. Fuse open; check fuse. Ensure continuity of wiring. 2. Low-pressure switch open. Cycle unit off and allow lowpressure switch to reset. Replace switch if it will not close. 3. Transformer bad; check transformer. 1. Solenoid coil defective; replace. 2. Solenoid valve stuck open; replace. Valve is stuck closed; replace valve. 1. Check charge amount. Charge per Fig. 60-63. 2. Evaporator coil frosted; check and replace low-pressure switch if necessary. 1. Check TXV bulb mounting, and secure tightly to suction line. 2. Replace TXV if stuck open or closed. System Hot Gas Reheat Mode Service Analysis CAUSE No power to control transformer from evaporator-fan motor. No power from control transformer to hot gas line solenoid valve REMEDY Check power source and evaporator-fan relay. Ensure all wire connections are tight. 1. Fuse open; check fuse. Ensure continuity of wiring. 2. Low-pressure switch open. Cycle unit off and allow lowpressure switch to reset. Replace switch if it will not close. 3. Transformer bad; check transformer. Hot gas line solenoid valve will not operate. 1. Solenoid 2. Solenoid Low refrigerant charge or frosted evaporator coil. 1. Check charge amount. Charge per Fig. 60-63. 2. Evaporator coil frosted; check and replace low-pressure switch if necessary. 1. Check TXV bulb mounting, and secure tightly to suction line. 2. Replace TXV if stuck open or closed. Loss of Compressor Superheat Conditions with Subcooling/Reheat Dehumidification Coil Energized, Thermostatic expansion valve (TXV). Excessive Liquid line solenoid valve will not operate. Hot gas line solenoid valve will not close. Superheat, Mode Service Analysis REMEDY No power to control transformer from evaporator-fan motor. No power from control transformer to liquid line solenoid valve. Reheat) Loss of Compressor Superheat Conditions with Subcooling/Beheat Dehumidification Coil Energized. Reheat System Subcooling CAUSE PROBLEM Subcooling Mode (Liquid Will Not Energize. Check orifice to burner alignment. Wait until mandatory one-minute time period has elapsed or reset power to unit. mode for a 50 coil defective; replace. valve stuck closed; replace. Valve is stuck, Valve is stuck; replace replace valve. valve. Table 38 -- Cooling PROBLEM Compressor and Condenser Will Not Start. Service Analysis CAUSE Fan Call power company. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Replace fuse or reset circuit breaker. Insufficient line voltage. Determine cause and correct. Incorrect or faulty wiring. Check wiring diagram and rewire correctly. Thermostat Compressor Will Not Start But Condenser Fan Runs. Compressor Cycles (Other Than Normally Satisfying Thermostat). REMEDY Power failure. setting too high. Faulty wiring or loose connections pressor circuit. Lower thermostat setting below room temperature. in com- Determine cause. Replace compressor. Defective run/start capacitor, overload, start relay. Determine cause and replace. One leg of 3-phase power dead. Replace fuse or reset circuit breaker. Determine cause. Refrigerant Recover refrigerant, evacuate system, and recharge to nameplate. overcharge or undercharge. Replace and determine cause. Determine cause and correct. Insufficient line voltage. Blocked condenser. Determine cause and correct. Defective run/start capacitor, overload, or start relay. Defective thermostat. Determine cause and replace. Faulty condenser-fan Replace. Locate restriction and remove. motor or capacitor. Restriction in refrigerant Operates Continuously. system. Head Pressure. Replace filter. Decrease load or increase unit size. Thermostat Reset thermostat. set too low. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Clean coil or remove restriction. Dirty air filter. Dirty condenser Refrigerant Replace filter. Clean coil. coil. overcharged. Recover excess refrigerant. Air in system. Head Pressure Too Low. Excessive Suction Pressure. Suction Pressure Too Low. Condenser air restricted or air short-cycling. Recover refrigerant, evacuate system, and recharge. Determine cause and correct. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Restriction in liquid tube. Replace compressor. Remove restriction. High heat load. Check for source and eliminate. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Dirty air filter. Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Remove source of restriction. Metering device or low side restricted. Insufficient evaporator airflow. Temperature too low in conditioned Outdoor ambient below 25 E Evaporator Fan Will Not Shut Off. Replace thermostat. Dirty air filter. Unit undersized for load. Condenser coil dirty or restricted. Excessive Check wiring and repair or replace. Compressor motor burned out, seized, or internal overload open. Defective compressor. Compressor Replace component. Time off delay not finished. 5! area. Increase air quantity. Check filter and replace if necessary. Reset thermostat. Install low-ambient kit. Wait for 30-second off delay. EconoMiSer IV Troubleshooting for EconoMi$er IV logic. -- See Table 39 3. A functional view of the EconoMi$er is shown in Fig. 68. Typical settings, sensor ranges, and jumper positions tue also shown. An EconoMi$er IV simulator program is available fiom Ctmier to help with EconoMi$er IV muning and troubleshooting. Connect a 9-v battery to AQ (positive node) and AQl (negative node). The LED for both DCV and Exhaust should turn on. The actuator should chive to between 90 and 95% open. 4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should remain in position. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9-v. The actuator should drive fully closed. ECONOMI$ER IV PREPARATION -- This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedme. 5. NOTE: This procedure requires a 9-v battely, 1.2 kilo-ohm resistol: and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV. 6. IMPORTANT: Be sure to record the positions of all poten- ] tiometers before starting troubleshooting. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on. 7. Return EconoMi$er IV settings and wiring to normal after completing troubleshooting. DCV MINIMUM AND MAXIMUM POSITION -- To check the DCV minimum and maximum position: 1 1. Disconnect power at TR and TRI. All LEDs should be off. Exhaust fan contacts should be open. 2. Disconnect device at P and PI. 1. Make sure EconoMiSer been performed. IV prep_uation procedure has 3. 4. Jumper P to PI. Disconnect wires at T and TI. Place 5.6 kilo-ohm resistor across T and TI. 2. Connect a 9-v battery to AQ (positive node) and AQI (negative node). The DCV LED should turn on. The actuator should chive to between 90 and 95% open. 5. Jumper TR to 1. 3. 6. 7. Jumper TR to N. If connected, remove Connect 1.2 kilo-ohm terminals So and +. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. Turn the DCV Maximum Position potentiometer to lhlly CCW. The actuator should drive fully closed. Turn the Minimum Position potentiometer to midpoint. The actuator should chive to between 20 and 80% open. 8. Put 620-ohm 9. Set minimum potentiometers 10. resistor across terminals position potentiometer 4. 5. SR and +. position, DCV set point, and fully CCW (counterclockwise). Set DCV maximum (clockwise). 11. Set enthalpy sensor from terminals So and +. 4074EJM checkout resistor across potentiometer exhaust Turn the Minimum Position Potentiometer actuator should drive fully open. 7. Remove the jumper from TR and N. The actuator drive fully closed. 8. Return EconoMiSer IV settings after completing troubleshooting. fully CW to D. 12. Apply power (24 vac) to terminals TR and TRI. DIFFERENTIAL ENTHALPY-To check differential enthalpy: 1. Make sure EconoMiSer IV preparation procedure has been performed. 2. Place 620-ohm resistor across So and +. 3. Place 1.2 kilo-ohm resistor across Cool LED should be lit. SR and +. The Free 4. Remove 620-ohm resistor Cool LED should turn off. So and +. The Free 5. Return EconoMiSer IV settings after completing troubleshooting. across and wiring Set the enth_dpy potentiometer Cool LED should turn off. SUPPLY-AIR 2. 3. has The DCV (DEMAND CONTROLLED VENTILATION) AND POWER EXHAUST -- To check DCV and Power Exhaust: 4. 1. Make sure EconoMiSer been performed. 2. IV preparation procedure to norm_d -- To check supply-air input: IV prepmation procedure has Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open. Remove the 5.6 kilo-ohm lesistor and jumper T to TI. The actuator should chive lhlly open. 1. Disconnect to normal and wiring and wiring should Remove the jumper across T and TI. The actuator should drive fully closed. 5. Return EconoMiSer IV settings and wiring to norm;d after completing troubleshooting. ECONOMISER IV TROUBLESHOOTING COMPLETION -- This procedure is used to return the EconoMiSer IV to operation. No troubleshooting or testing is done by performing the following procedure. to D (fully CW). The Free Return EconoMiSer IV settings after completing troubleshooting. lhlly CW. The 4. 2. 3. 4. INPUT 1. Make sure EconoMi$er been performed. to normal SINGLE ENTHALPY -- To check single enthalpy: 1. Make sure EconoMiSer IV preparation procedure been performed. 2. Set the enthalpy potentiometer to A (fully CCW). Free Cool LED should be lit. 3. 6. has 5. 6. Ensure terminals AQ and AQI _ue open. The LED for both DCV and Exhaust should be off. The actuator should be lhlly closed. +. 52 power at TR and TRI. Set enthalpy potentiometer to previous setting. Set DCV maximum position potentiometer to previous setting. Set minimum position, DCV set point, and exhaust potentiometers to previous settings. Remove 620-ohm resistor from terminals SR and +. Remove 1.2 kilo-ohm checkout resistor from terminals So and +. If used, reconnect sensor from terminals So and 7. Remove jumper flom TR to N. 8. Remove jumper fiom TR to 1. 9. Remove 5.6 kilo-ohm resistor from T and TI. Reconnect wiles tit T and TI. l 0. Remove jumper PI. 11. Apply power (24 vac) to terminals Table 39 -- EconoMi$er IV Input/Output Below set (DCV LED Off) Above set (DCV LED On) device a P and TR and TRI. Logic INPUTS Demand Control Ventilation (DCV) fiom P to Pl. Reconnect OUTPUTS Enthalpy* Outdoor Return High (Free Cooling LED Off) Low Low (Free Cooling LED On) High High (Free Cooling LED Off) Low Low (Free Cooling LED On) N Terminalt Compressor High *For single enthalpy control, the module compares enthalpy to the ABCD set point. 1-Power at N terminal determines Occupied/Unoccupied 24 vac (Occupied), no power (Unoccupied). **Modulation is based on the supply-air sensor signal. 1-1-Modulation is based on the DCV signal. Y1 Y2 Stage 1 Stage 2 On On On Off On On On Off Off Off Off Off On On On Off On Off Off Off On On On Off Off Occupied Unoccupied Damper Minimum position Closed Off Off Modulating** (between rain. 3osition and full-open) Modulating** (between closed and full-open) Off Off Minimum position Closed On On On Off Modulating1-1- (between rain. 3osition and DCV maximum) Off Off Off Modulating1-1- (between closed and DCV maximum) On On On Off On Off Off Off Modulating*** Modulating1-1-1- Off Off Off Off ***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal). I-I-I-Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal). outdoor setting: Fig. 68 -- EconoMi$er IV Functional View 53 INDEX Access panels 19 Altitude compensation 38 Barometric flow capacity 21 Burner ignition 46 Burner rack 46 Burner section 46 Burner spark gap 47 Carrier Comfort Network 15 ChaEzing chart, ret_igerant 44, 45 Clearance 6 CO2 sensor Configuration 25 Settings 23, 25 Combustion blower wheel 46 Compressor Lubrication 43 Mounting 37 Rotation 37 Condensate drain Cleaning 42 Location 4 Condenser coil 8 Cleaning 42 Condenser fan 8 Adjustment 43 Control circuit Wiring 7 Wiring raceway 10 Convenience outlet 15 Demand control ventilation 24 Dehunfidification 25 Dimensions 3, 6 Ductwork 2 EconoMi$er2 11_ 4to 20 mAcontrol 20 Wiring 20 EconoMi$er IV 18-25 Control mode 21 Damper movement 24 Troubleshooting .52,53 Wiring 20 Electrical connections 5 Electrical data 11, 12 Enthalpy changeover set points 23 Evaporator coil 8 Cleaning 42 Evaporator fan motor Lubrication 43 Motor data 27 Performance 28-36 Pulley adjustment 2.5,26 Pulley setting 8, 26 Speed 8 Factory-installed options Convenience outlet 15 EconoMiSer IV 18-25 EconoMiSer2 18 Humidistat 13 Humidi-MiZer TM dehumidification system 14 Manual outdoor air damper 13 Novar controls 15 PremierLink TM controls 15-17 Filter Cleaning 42 Installation 19 Size 9 Flue gas passageways 46 Flue hood .5,7 Freeze protection thermostat 9, 43 Gas connection 9 Gas input 9 Gas piping .5,Z 37 Gas pressure 1, 9 Heat anticipator settings Z 9 Heat exchanger 9 High flow valves 37 High pressure switch 9, 4.? Horizontal units 1, 2 Humidistat 13 Humidi-MiZeradaptive dehumidification system 13, 26, 41, 42, 44, 4.5,50 Indoor-airquality (IAQ) sensor 15, 23 Integrated gas controller 46 Error codes 46, 49 Leak test 37 Limit switch 46 Liquid propane 9 Low pressure switch 9, 43 Main burners 3&46 Manual outdoor air damper 13 Mounting Compressor 37 Unit 4 Natural gas 9 Novar controls 15 Operating limits 2 Operating sequence 39-42 Cooling 39 EconoMi$er IV 39 EconoMi$er2 39-41 Heating 39 Hunfidi-MiZer adaptive dehumidification system 41, 42 Outdoor air hood 14, 1.5,19 Outdoor air inlet screens 9, 3Z 42 Outdoor-air temperature sensor 15, 21 Physical data 8, 9 Power supply 5 Wiring 10 PremierLink controls 15-17 Pressure, drop EconoMiSer IV 36 EconoMiSer2 36 Humidi-MiZer adaptive dehumidification system 26 Pro-Start-Up 37 Pressure switches High pressure 9 Low pressure 9 Refrigerant Charge 8, 43 Type 8 Refrigerant selwice ports 37 Replacement parts 47 Return air filter 9, 37 Return-air temperature sensor Rigging unit 4, 5 Roof curb Assembly 1 Dimensions 3 Connector package 3 Leveling tolerances 4 Weight 8 Safety considerations 1 Safety relief 39 Service 42-48 Sel_.ice ports 37 Slab mount 2 Start-up 37-42 Start-up checklist (_'L-I Supply-air temperature sensor Thermostat 10 Troubleshooting 40-53 Ventilation 39 Weight Comer 6 EconoMiSer IV 6, 8 Unit .5,6,8 Wiring 4 to 20 mA control 20 Differential enthalpy 18 Humidistat 14 EconoMiSer2 20 EconoMiSer IV 20 Power connections 10 PremierLink control 10, 17 Thermostat 10 Unit 48 22 1.5,21 Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53480013-01 Printed in U.S.A. or designs without notice and without incurring obligations. Form 48HJ-33SI Pg 54 9-05 Replaces: 48HJ-29SI START-UP (Remove I. PRELIMINARY MODEL CHECKLIST and Store in Job File) INFORMATION NO.: SERIAL DATE: NO.: TECHNICIAN: II. PRE-START-UP (insert checkmark VOLTAGE in box as each item is completed) [] VERIFY THAT JOBSITE [] VERIFY THAT ALL PACKING [] REMOVE [] VERIFY [] CHECK ALL ELECTRICAL [] CHECK GAS PIPING FOR LEAKS [] CHECK THAT RETURN [] VERIFY [] CHECK FAN WHEELS [] CHECK TO ENSURE THAT ELECTRICAL OR SHARP METAL EDGES ALL SHIPPING AGREES WITH VOLTAGE MATERIALS HOLDDOWN THAT CONDENSATE LISTED ON RATING PLATE HAVE BEEN REMOVED BOLTS AND BRACKETS CONNECTION CONNECTIONS FROM UNIT PER INSTALLATION IS INSTALLED PER INSTALLATION AND TERMINALS FOR TIGHTNESS INSTRUCTIONS INSTRUCTIONS LU 2: m (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE c_ LU THAT UNIT INSTALLATION I-- IS LEVEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS rm Z [] III. CHECK PULLEY ALIGNMENT WIRING IS NOT IN CONTACT WITH REFRIGERANT o, LINES < I- AND BELT TENSION PER INSTALLATION o INSTRUCTIONS START-UP ELECTRICAL SUPPLY VOLTAGE L 1-L2 L2-L3 L3-L 1 COMPRESSOR LI L2 L3 LI L2 L3 INDOOR-FAN AMPS AMPS TEMPERATURES OUTDOOR-AIR RETURN-AIR COOLING TEMPERATURE DB TEMPERATURE SUPPLY GAS HEAT SUPPLY LU 2: m DB AIR WB rm LU DB AIR I- DB c_ Z o, PRESSURES GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE < Io REFRIGERANT SUCTION IN. WG (HIGH FIRE) PSIG REFRIGERANT DISCHARGE PSIG [] VERIFY REFRIGERANT CHARGE [] VERIFY THAT 3-PHASE SCROLL USING CHARGING COMPRESSOR TABLES ROTATING IN CORRECT DIRECTION Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Book 1 14 Tab 1a 16a Catalog No. 04-53480013-01 Printed in U.S,A. or designs without notice and without incurring obligations. Form 48HJ-33SI Pg CL-1 9-05 Replaces: 48HJ-29SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 55 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 12:41:40 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools