CARRIER Package Units(both Units Combined) Manual L0520543
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 62
| Download | |
| Open PDF In Browser | View PDF |
48HJD/HJE008-014
48HJ F008-012
Single-Package Rooftop
Gas Heating/Electric Cooling Units
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ......................
1
INSTALLATION ................................
1-41
Step 1 -- Provide Unit Support ...................
2
• ROOF CURB
• SLAB MOUNT
• ALTERNATE UNIT SUPPORT
Step 2 -- Field Fabricate Ductwork ...............
2
Step 3 -- Determine Location of Drain Line
and External Trap ..............................
2
Step 4 -- Rig and Place Unit .....................
4
• POSITIONING
Step 5 -- Install Flue Hood .......................
4
Step 6 -- Install Gas Piping ......................
4
Step 7 -- Make Electrical Connections ...........
9
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Step 8 -- Adjust Factory-Installed Options ......
10
• HUMIDI-MIZER TM DEHUMIDIFICATION
SYSTEM
• CONVENIENCE OUTLET
• NOVAR CONTROLS
• MANUAL OUTDOOR-AIR DAMPER
• PREMIERLINK r_'_CONTROL
• OPTIONAL ECONOMISER IV AND ECONOMISER2
• ECONOMI$ER IV STANDARD SENSORS
• ECONOMI$ER IV CONTROL MODES
Step 9 -- Adjust Evaporator-Fan Speed .........
25
PRE-START-UP ..................................
42
START-UP ....................................
42-47
SERVICE .....................................
47-53
TROUBLESHOOTING .........................
54-59
INDEX ...........................................
60
START-UP CHECKLIST ........................
CL-I
SAFETY
CONSIDERATIONS
Installation and sel-,Ticingof air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service ai>conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on ai>conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Manufacturer
Ensum voltage listed on unit data plate agmes with electric_dsupply provided for the unit.
Disconnect gas piping fi_m unit when leak
testing at pressure greater than I/2 psig. Pmssums greater than ]12psig will cause gas valve
damage resulting in haz_u'dous condition. If
gas valve is subjected to pressure greater than
1/2 psig, it must be replaced before use. When
_ressure testing field-supplied gas piping at
?ressures of 1/2 psig or less, a unit connected to
;uch piping must be isolated by manu_dly closing the gas valve(s).
Before performing service or maintenance
operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to
horizont_flapplication, remove side duct opening covers. Using
the same scmws, install coveLs on vertical duct openings with
the insulation-side down. Seals around duct openings must be
tight. See Fig. 1.
Step 1 -- Provide
ROOF CURB -- Assemble and install accesso U roof curb in
accor&mce with instructions shipped with curb. See Fig. 2.
Install insulation, cant strips, roofing felt, and counter flashing
as shown. Ductwork must be attached to curb. If electric or
control power is to be routed through the basepan, attach the
accessory thru-the-bottom
service connections to the basepan
in accordance with the accessory installation instructions. Connections must be installed befom unit is set on roof curb.
I
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 2. hnproperly applied gasket can
I IMPORTANT:
the performance.
unit to the roof curb is I
also result in airThe
leaksgasketing
and poorofunit
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances am shown in Fig. 3.
Refer to Accessory Roof Curb Installation
Instructions
for
additional infomtation as requimd.
reserves the right to discontinue, or change at any time, specifications
Catalog No. 04-53480012-01
Printed in U,S.A,
Unit Support
or designs
Form 48HJ-32SI
without notice and without incurring obligations.
Pg 1
9-05
Replaces:
48HJ-28SI
SLAB MOUNT (Horizontal
Units Only) -- Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to
plevent grass and foliage from obstructing airflow.
These units are designed for a minimum continuous returnair temperature in heating of 50 F (c_h_bulb), or an intermittent
operation down to 45 F (r_h_ bulb), such as when used with a
night set-back thermostat.
NOTE: Horizontal
required.
To operate at lower return-air temperatures, a field-supplied
outdoor-air temperature control must be used to initiate both
stages of heat when the temperature is below 45 E Indoor comfort may be compromised
when these lower air temperatures
are used with insufficient heating temperature rise.
units may be installed
on a roof curb if
ALTERNATE UNIT SUPPORT -- When the curb or adapter
cannot be used, support unit with sleepers using unit curb or
adapter support alea. If sleepel_ cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
Step 3 -- Determine
and External Trap --
Step 2 --
Location
of Drain
Line
The unit's 3/4-in. condensate &ain
connections are located on the bottom and end of the unit. Unit
discharge connections do not determine the use of c_h'ainconnections; either c_h'ainconnection can be used with vertical or
horizontal applications.
Ducts passing through an unconditioned
insulated and covered with a vapor b_uriel:
When using the standard end c_h'_dnconnection, make sure
the plug in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, lelocate the factory-installed
plug from the bottom connection to the end connection. The center c_hainplug looks like
a star connection, however it can be removed with a l/2-in.
socket c_hive extension. See Fig. 4. The piping for the condensate c_h'ainand external trap can be completed after the unit is in
place.
Field Fabricate Ductwork -- On vertical
units, secure all ducts to roof curb and building structure. Do
not connect duct_'ork to unit. For horizont_fl applications, fieldsupplied flanges should be attached to horizontal discharge
openings and all ductwoN secured to the flanges. Insulate and
weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
space
must
be
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not requiled around ductwork.
Cabinet return-air static pressure (a negative condition) shall
not exceed 0.35 in. wg with economizer or 0.45 in. wg without
economizel:
All units must have an extern_fl trap for condensate &'ainage. Inst_dl a trap at least 4 in. deep and protect against freezeup. See Fig. 5. If drain line is installed downsheam from the
extern_fl trap, pitch the line away from the unit at 1 in. per 10 ft
of run. Do not use a pipe size smaller than the unit connection.
REMOVABLE HORIZONTAL
RETURN DUCT OPENING
COVER
\
\
\
\
\
\
\
\
'\
__
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
Fig. 1 --
Horizontal
Conversion
Panels
CONNECTOR
PKG. ACCY,
B
D ALT
DRAIN
HOLE
C
GAS
CRBTMPWR001A01
CRBTMPWR002A01
POWER
3/4"
[19] NPT
2'-87/16
CRBTMPWROO3A01
"
1'-1015/16"
[827]
[583]
3/4" [19] NPT
11/4" [31.7]
1s/4"
1/2"
[44,5]
[12,7] NPT
3/4" [19] NPT
3/4"
11/4" [31.7]
CRBTMPWROO4A01
[19] NPT
ROOF CURB
CONTROL
1/2"
[12.7] NPT
/
[12.7] NPT
",,
<_
----I
""-'"
\
".'4
/5UPPLIED
I- D-
I-
I
I
I
I
of airflow,
NAIL
(4)
SIDES
FLASHING
(FIELD
I
I
AIR
OPENING
Direction
O"
BESS/lOB3"
.....
3"
5UPPL IEB]
STRIP
(FIELD5UFELTPPLIEB)
SUPPLIED)
3 5/8"
I
I
48HJ008-014
CURB)
I
I
31/4"
[3873
GA5KET
WITH
TYPICAL
I
'1
I
,/RETURN
AI
OPENING
l"
610
DUCT
SUPPLIED)
(FIELD
I
SUPPLY
2-0
8. Connector packages CRBTMPWROO1A01 and
2A01 are for thru-the-curb gas type, Packages
CRBTMPWROO3A01
and 4A01 are for thruthe-bottom type gas connections.
O'
3"
[75]
O' 3"
[TB]
CRRFCURB004A01
7. [_
"\
UNIT SIZE
1'-2" [356]
NOTES:
1. Roof curb accessory is shipped disassembled,
2. Insulated panels: 1-in, thick polyurethane foam,
lS/4 Ib density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel,
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft on each side.
1/2"
|
err_
"A"
ACCESSORY
CRRFCURB003A01
(FIELD
El BOB]
,_(A_O_
MATERIAL
SUPPLIED)
0
SECT(ON
"C
C"
I
"C"
SCALE
I
1: 4
I
4_
/
0 7/]B"
[11]
(BOLT
HEADS)
RIGID
(FIELD
O'
O"
22"
B[TBG]
15/163._
O"
[7B]
O' 0 7/lS"
1113
4"
0
mm
INSULATION
SUPPLIED)
0 7/1B"
[11]
HEADS)
OPENING
FOR BASEPAN
ENTRY SERVICE
(SEE
(BOLT
O"
O 13/16"
[1240]
O'
(BDLTA_ADS)
NOTE #B)
O 7/1B"
2 1/8"
[54]
A HEADS)
NOTE _2
:290]
GAS SERVICE
PLATE
(SEE NOTE
O"
1"
O I/4"[7]
8 3/16"
[513]
(IN5]DE)
I
O" 4 5/15"
[110]
:INSIDE)
B/1B"
%Is
I
SUPPLY
AIR
RETURN
TYP
2 3/8"
[61]
AIR%
E75]
VIEW
HEAD OF
INSIDE
"A-A"
I
I
I
I
I
BOLT TO BE ON
OF FLANGE
"A"
O' 1"
[25]
O" 1 7/8"
[4B]
4"
|
1 3/4"
[1284]
NOTE:
[7B]
y_EW"B"
:
(TYP.
ALL
CORNERS)
SEE
V]EW
"B_
_
_"
Fig. 2 -- Roof Curb Details
CAMBRIDGEPORT
"5URE
LOCK"
FA5TENING
DEVICE
ALTERNATE
CONSTRUCTION.
15
CORNER
ACCEPTABLE
Do not instull unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contaminated
all:
Be sure that unit is installed so that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on
Class A, B, or C roof-covering material when roof curb is used.
C
UM ALLOWABLE
DIFFERENCE On.)
8
A-B
0.5
Fig. 3 -- Unit
I
I
Leveling
B-C
1.0
A-C
1.0
Tolerances
Although unit is weatherproof,
higher level runoff and overhangs.
guard against
water fiom
Position unit on roof curb so that the following clearances
are maintained: l/4-in, clearance between the roof curb and the
base rail inside the front and real: 0.0 in. clearance between the
roof curb and the base rail inside on the duct end of the unit.
This will result in the distance between the roof curb and the
base rail inside on the condenser end of the unit being approximately equal to Fig. 2, section C-C.
Ix_cate mechanical draft system flue assembly at least 48 in.
from an adjacent building o1 combustible material. Units having accessory flue dischmge deflector lequire only 18 in. clearance. When unit is located adjacent to public walkways, flue
assembly must be at least 7 ft above grade.
Flue gas can deteriorate building materi_ds. Orient unit so
that flue gas will not affect building materials.
HORIZONTAL
DRAIN PLUG
Adequate combustion and ventilation air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for
Combustion and Ventilation per NFGC (Natiomd Fuel Gas
Code), ANSI (American National Standards Institute) Z223.1 latest year and addendum Z223.1A-latest
yem: In Canada, installation must be in accordance with the CANI.BI49.1
and
CAN 1.B 149.2 installation codes for gas burning appliances.
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 --
Condensate
Drain Pan
Flue vent dischmge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
MINIMUM PITCH
_-_-_
After unit is in position, remove shipping materials
ging skids.
_
and rig-
Step 5 --
\
\
OPEN z' MINI I
VENT'N4_
Install Flue Hood -- Flue hood is shipped
screwed to the burner compartment
access panel. Remove
fiom shipping location and, using screws provided, inst_dl flue
hood and screen in location shown in Fig. 7 and 8.
III
III //I
Step 6 -- Install
NOTE
,_,.ROOF
CURB
1==4
DRAIN
PLUG
NOTE: Trap should be deep enough to offset maximum
difference. A 4-in. trap is recommended.
Fig. 5 -- Condensate
unit static
Drain Piping Details
Step 4 --
Rig and Place Unit -- Inspect unit for
transportation
&unage. File any clainl with transpoltation
agency. Keep unit uptight and do not drop. Spreader bars are
not required if top crating is left on unit. Rollel_ may be used to
move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 6 for additional information. Operating weight is shown in Table 1 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 6
and 7. Refer to rigging instructions on unit.
POSITIONING
-- Maintain clearance around and above unit
to provide minimum distance fiom combustible
materi_ds,
proper airflow, and service access. See Fig. 7.
Gas Piping -- Unit is equipped for
use with type of gas shown on nameplate.
Refer to local
building
codes, or in the absence
of local codes, to
ANSI Z223.l-latest
year and addendum Z223. l A-latest year
entitled NFGC. In Cana&t, installation must be in accordance
with the CANI .B149.1 and CANI .B149.2 installation codes
for gas burning appliances.
For natund gas applications,
gas pressure at unit
connection must not be less than 4.0 in. wg or greater
13.0 in. wg while unit is operating. For liquid propane and
heat applications,
the gas pressure must not be less
5.0 in. wg or greater than 13.0 in. wg at the unit connection.
gas
than
high
than
Size gas supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe sm_fller than unit gas connection.
Support gas piping as shown in the table in Fig. 9. For example, a 3/4-in. gas pipe must have one field-fabricated
support
beam every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams. See Fig. 9 for typic_d pipe guide
and locations of external manual gas shutoff valve.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent valve
&_mage.
SECUREALL STRIPS
BEFORE PLACING
UNIT ON ROOF CURB.
36"-54"
"DETAIL
(91 4-1 371)
/
I
SEE
A"
DETAIL
.<.
NOTES:
1, Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail as shown in
detail "A." Holes in base rails are centered around the unit center of gravity, Use wooden top skid when rigging to prevent rigging straps from damaging unit,
3. Weights include base unit without economizer, See Table 1 for
unit operating weights with accessory economizer.
4. Weights include base unit without the Humidi-MiZer TM adaptive
dehumidification system. See Table 1 for unit operating weights
with the Humidi-MiZer system.
48HJ
008
00g
012
014
All panels must be in place when rigging.
Fig. 6 --
Rigging
Details
OPERATING
WEIGHT
"A"
"a"
"C"
in.
mm
in.
mm
in.
mm
Ib
870
kg
395
77.42
1967
41.5
1054
42.12
1070
1015
460
77.42
1967
41.5
1054
42.12
1070
1035
469
77.42
1967
41.5
1054
50.12
1273
1050
476
77.42
1967
41.5
1054
50.12
1273
STD UNIT
WEGH
(;NI
4/ iJ÷O08
48_,_;_0i
NOTES
i.
[} dN
2
ON
]\
8r'O
:oi
1035
469
} AR
]
Mi
'/
4
RI
P,E<
_45
0
CENTER OF¸ GR4ViTY
_
DIRECTION
4
ON VER[]CAL
OiSCHARGE dN/;S,
{}.PL]ED FLANGES SOOdLO BE AiiACHED
i0
HOR[ZONiAL D:SCH_G_
OPENINGS, AND ALL DUCiWORK 5HObLD
BE A! :ACMED I0 :HE FLANOES.
HfN[MUM CLEARANCE (LOCAL COOE[_ OR JtJRiS[?f¢:
;ON HAY
o
b
c
d
e
?
g
h
6
7
8
GS,g
WEIGH
(A)CORNEi
_E
OH
(B
C,')INER
,_E
(H
(C}
ORNE
dE([
(D
"14 _
iB9
{76
/6_
?:7
239
log
280
127¸
2'
22_
_02
/g2
87
_8_
/2_
333
IS_
/'
2_
iO_l
1!_
88
289
1_i
3_8
i_
_-2
0
2
7/8"
_J8 _
"i_J_"
"J"
"K _
S S/]{_=
MM
i=T¸
IN.
1050
i2 > g
/i/16
632
3'
3_8
4 _ I S/18 _
_2_
i
_'
_78
4"-i
i2_i
i
3"-,0
_/i_
_
"1 _
MM
_
FT
IN.
2"v2
?/IB"
856
i
0 3/8 _
g24
i 2"
iO
_/_i _
9J4
i2"
_0 7/1_
6?2
"_/1E__
_7_
_
87_
fIL 7ER ACC{S
}#NIt
':D;SPOS_S: E F]LTE_S)
/
3
5
CORNER
[M / RJ
2
OF AIR
CON
_EiGItT
FLOW
[L_Cr
B_FWEEN UNfT, FLtJE 5:0E _NO COMBUSTIBLE StJRF/_C[:5,
_8 INCHES !8 iN(}I:E_ W_:N USfNG ACCESSORY FLtJE Of SClI_i_GE DEFLECTOR
BOTTOM OF: uN[r
ro COMBUSTIBLE SdRFAC_:5 (WHEI'_ NO: t'S!NC; CtJRt_)
/ :NCiL
BOTTOM OF¸ BASE RA[t
TO COMBbS: ISLE 5tJRF/_CES (WHEN NO: tiSiN6
CURB) 0 ]NCHES
CONDENSER CO:{,
FOR PROPER AIR FLOW, 36 :NC}i_S
ONE SfDE,
12 INCHES T_tE OTilER
THE SIDE GETTING THE
GRE#TER CLE_RANC_ 19 OPTIONAL¸
OVERHEAD, 80 INCHES TO ASSdRE PROPER CONDeNSeR FAN
OPERAT ] ON
B:TNEEN UNfTS, CONTROt _OX SIDE_ 42 ]N
PER NEC
BETNEEN UNIT AND UNGROONOEOSURFACOS, OONTqO: BOX
SIDE, 36 iN,
PER NEC,
3.:TNEEN UNIT _ND Bi OCK OR CONCRETE WALl S AND OTHER
GROUND:D SURFACES, CONTROl BOX SiC.E, 47_ iN
PER N:C
iiORIZONTAL 5bPPl Y AND RETt;R_ END, 0 ]NCqES dOEN THE
AI TERNATE CONDENSATE DRAIN IS dSE8
WIYM :_E EXCEPflON OF Y_E CLEARANCE FOR ;ME CONDENSER
COiL ANO OOMBUSiIOh ST:]E A2 SLATED IN NO:E #_,
b,
,_f'@ c, A i_EMOVABb+ FENCE OR BARRICADE REOUIRES NO
¢i :AR,tNCE
FOR
F/
[!CONObI/!S[i
[[T{fR
POWER,
DEPEND[qG
3/4"
04
OR
1
is4"
S]Z
WiRE
IV
V{Td
LEFT
SIDE
UN: T5 MAY _E :NSrA[[ El} ON CO_I_US: :f_: E FLOOR5 MADE
FROM WOODOR Ci AS5 A, 8, OR ¢ ROOF COt'ER:NG MATERIAl
IF SEI ON BA_E R_IL
:i_E k'_RT[CAL CENrER or: GRA_iT _' :5 / ¸ 7"[¸4837
FOR OO8,
_" 11_1S84]
FOR HJO09, 012 AND 0i4
UP FROM T:I[_ BOITOM Or' ]_f! BASE RA:I
..... 2"
SUPPLY
<
0"3
[;9]
_3'
@
O'
NSER
'
3 /["
[221 c{]
tC [07Y
FlUE
_ os
[138]
i/8
.....
(}0RE
C
i
[iOS]
i
m
CON I RO
fOX/
CO >ROSSOR/
BU NE/ ACCESS
PANS
COil
"t _
80T:O_
SF UNIT
rim
?
o"
3/4 _
3•0"
[9!44
S!DE
Iil_
/
OK
\
LEFT
1::::;=3
--
O"
' _LECTRiCAL
D]SCONN!_CT [ OCA: :0_
8 /!g"
2i4
TRUCK ilOF
//
'
(I
2
/ " I
P ;! P A_
FRONT
)
UPPLY
AiR
/
£E
Fig. 7
i
Base Unit Dimensions
.....
1{7[]
} )
S!P&
ECONO v SER q
_,/ PON[
EXIJA JSI
fiO]}
ILTFiR
UPP[ lEO
OOD
[5t0]
"<-.
O" 0 3'8"
[10]
3 1Z/It
{973
_{
)l
4 //4=_J
[1022]
2"
AR
[208]
CON
{
pANEL
RTTURN
STO,
COND
AIR
NSAT£
©RA[N
4CCESS
PANEL
Table1 -UNIT SIZE 48HJ
NOMINAL
CAPACITY
D/E/F008
(tons)
OPERATING WEIGHT (Ib)
Unit
Humidi-MiZer TM Adaptive
EconoMi$er IV
Roof Curb
COMPRESSOR
Dehumidification
System
ouantity
Oil (oz) (each compressor)
REFRIGERANT TYPE
Expansion Device
Operating Charge (Ib-oz)
Standard Unit
Circuit I
Circuit 2
Unit with Humidi-MiZer
Adaptive
Circuit 1
Circuit 2
CONDENSER FAN
Quantity...Diameter
(in,)
Nominal Cfm
Motor Hp.,.Rpm
Watts Input (Total)
CONDENSER COIL
Rows.,,Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Size (in,)
Type Drive
Nominal Cfm
Maximum Continuous
Bhp
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting -- Full Turns Open
Factory Speed Setting (rpm)
Fan Shaft Diameter at Pulley (in.)
EVAPORATOR COIL
Standard Unit
Rows...Fins/in,
Total Face Area (sq ft)
Unit with Humidi-MiZer Adaptive Dehumidification
Rows...Fins/in,
Total Face Area (sq ft)
LEGEND
--
Brake Horsepower
121/2
870
44
75
143
1015
51
75
143
1035
51
75
143
1050
51
75
143
I
Scroll
2
I
50
TM
2
I
50
R-22
Metering
2
60
Device
7-10
8- 2
9- 8
8-13
9-6
10-9
17-0
18-3
19- 2
19-10
19-14
20- 3
9-8
9-5
System
19-6
19-0
Propeller
2-.22
2-.22
114,.,1100
6500
650
2.-22
114,.,1100
6500
650
Std
Hi-Static
Std
Hi-Static
15x15
Belt
3000
2,90
4,20
56
840-1085
860-1080
Ball
2100
3.4/4,4
4.0/5,0
I
25.0
2.,.17
I
Centrifugal
Std
Hi-Static
Std
Hi-Static
Std
Hi-Static
Std
Hi-Static
7.0
8.0
A.-48
A.-55
16.75-19.25
50
60
5
5
5
5
840
860
1
15x15
Belt
3400
2,90
4,20
56
840-1085
860-1080
Ball
2100
3,4/4.4
4,0/5.0
15x15
Belt
4000
3,70
5,25
56
860-1080
830-1130
Ball
2100
4.0/5.0
2,8/3.8
7.0
8.0
A...51
A.-55
16.75-19,25
50
60
5
5
5
5
840
860
1
8,0
5,8
A...51
BX..,46
15,85-17,50
45
60
5
6
5
5
860
890
1
]
114.,,1100
7000
650
I
25,0
2..,17
15x15
Belt
5000
5.25
56
830-1130
Ball
2100
2.8/3.8
7&
Enhanced Copper Tubes, Aluminum
2.-22
Lanced Fins
25.0
2.,.17
7/8
Std
Hi-Static
Std
Hi-Static
I
114.,,1100
7000
650
Enhanced Copper Tubes, Aluminum
20.5
2,.,17
Std
Hi-Static
(in,)
D/E014
10
Acutrel
Dehumidification
D/E/F012
81/2
2
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter
A/B (in.)
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Bhp
D/E/F009
71/2
53
Motor Frame
Fan Rpm Range
Belt -- Type,,.Length
Physical Data
Double-Wavy
7&
5.8
BX.-46
15.85-17.50
6O
6
5
887
1
Fins, Face-Split
3,,,15
8,9
4_.15
11.1
4._15
11.1
4_,15
11.1
2...17
6.3
2,_17
8.4
2...17
8.4
2-,17
8.4
System
*Indicates automatic reset,
tAn LP kit is available as an accessory.
as 2000 ft.
Kit may be used at elevations as high
Table 1 -- Physical Data (cont)
UNIT SIZE 48HJ
FURNACE SECTION
Rollout Switch Cutout Temp (F)*
Burner Orifice Diameter (in, .,.drill size)
Natural Gas -- Std
D/E/F008
Heat Anticipator Setting (amps)
Stage 1
Stage 2
Gas Input (Btuh)
Stage 1
Stage 2
Efficiency
(Steady State) (%)
Temperature
Rise Range
Manifold Pressure (in, wg)
Natural Gas -- Std
Liquid Propane -- Altt
Field Gas Connection Size (in,)
HIGH-PRESSURE
SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto,)
LOSS-OF-CHARGE
SWITCH/LOW-PRESSURE
SWITCH (Liquid Line) (psig)
Cutout
Reset (Auto,)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
OUTDOOR-AIR
INLET SCREENS
RETURN-AIR FILTERS
Ouantity..,Size (in.)
---
D/E014
195
195
HJD.120-.31
HJE.120-.31
HJF.120-.31
HJD.096-.41
HJE.096...41
HJF.096-.41
HJD .120...31
HJE.120-.31
HJF.120.-31
HJD.096...41
HJE.096-.41
HJF.096.-41
HJD .120-.31
HJE.120...31
HJF.129-.30
HJD .096-.41
HJE.096.-41
HJF.102-.38
HJD.120...31
HJE.129-.30
HJD.14
HJE.14
HJF.14
HJD.14
HJE.20
HJF.20
HJD 90,000
HJE 120,000
HJF160,000
HJD 125,000
HJE 180.000
HJF 224,000
HJD 82
HJE 62
HJF 82
HJD 20-50
HJE 35-65
HJF 45-75
HJD.14
HJE.14
HJF.14
HJD.14
HJE.20
HJF.20
HJD 90,000
HJE 120,000
HJF 160,000
HJD 125,000
HJE 180,000
HJF 224,000
HJD 82
HJE 82
HJF 82
HJD 20-50
HJE 35-65
HJF 45-75
HJD.14
HJE.14
HJF.14
HJD.20
HJE.20
HJF.20
HJD 120,000
HJE 180,000
HJF 200.000
HJD 160,000
HJE 224,000
HJF 250,000
HJD 82
HJE 62
HJF 80
HJD 35-65
HJE 35-65
HJF 40-70
HJD.14
HJE.14
3.5
3.5
HJD .50
HJE .75
HJF .75
3.5
3.5
HJD .50
HJE .75
HJF .75
3.5
3.5
HJD .75
HJE .75
HJF .75
3.5
3.5
HJD .75
HJE .75
HJD .096-.41
HJE.102.-38
HJD.20
HJE.20
HJD 180,000
HJE 200.000
HJD 224,000
HJE 250.000
HJD 82
HJE 60
HJD 35-65
HJE 40-70
450 _+50
428
32O
7_+3
22_+7
30_+5
45_+5
Cleanable.
4_.16 x20
LEGEND
Bhp
LP
D/E/F012
195
195
Liquid Propane -- Altt
Thermostat
D/E/F009
x2
I
Screen quantity and size varies with option selected.
Throwaway
4._20 x 20 x 2
I
4._20 x 20 x 2
*Indicates automatic reset.
tAn LP kit is available as an accessory.
as 2000 ft.
Brake Horsepower
Liquid Propane
I
Kit may be used at elevations as high
.,
x
"l
9" MINIMUM CLEARANCE
FOR PANEL REMOVAL
GAS
REGULATOR
*-- -- MANUALGAS
,SHUTOFF
Ii
L-._._ ROOF CURB
I
I
_
VALVE*
I
I
IP LEG PER NFGC * _'r£b
BASE RAIL
4...20 x 20 x 2
J_
/
FIELD-FABRICATED
SUPPORT*
FROM GAS METER
LEGEND
NFGC
--
National
Fuel Gas Code
• Field supplied.
NOTE: Follow all local codes.
STEEL PIPE
NOMINAL
DIAMETER
FLUE
HOOD SHIPPING
POSITION
(BEHIND
PANEL)
Fig. 8--
Flue Hood Details
SPACING
OF SUPPORTS
X DIMENSION
(in.)
(ft)
1/2
3/4 or 1
11/4 or larger
6
8
10
Fig. 9 -- Gas Piping Guide (With Accessory
Thru-the-Ourb Service Connections)
Step 7 --
Make Electrical
Connections
On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the fommla
shown in Note 3 under Tables 2A-2D to determine the percentage of voltage imbalance. Operation on improper line voltage
or excessive phase imbalance constitutes abuse and may cause
&image to electric_fl components. Such operation would inv_fli&tte any applicable Carrier warranty.
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal inju U if
an electrical fault should occm: This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit appl_)ved for electrical ground when
installed in accordance
with NEC (National Electrical
Code), ANSI/NFPA
(National File Protection Association), latest edition, and local electrical codes. Do not use
gas piping as an electrical ground. Failure to follow this
warning could result in the inst_dler being liable for persomd inju U of others.
NOTE: If thru-the-bottom
accesso U connections are used,
refer to the thin-the-bottom
accessol T installation instructions
for power wiring. Refer to Fig. 7 for location to &ill holes in
basepan.
FIELD CONTROL WIRING -- Install a Carrier-approved
accesso U thermostat assembly according to inst_dlation instructions included with the accesso U. Ix)cate thermostat
assembly on a solid wall in the conditioned space to sense
average temperature in accordance with thermostat installation
instructions.
FIELD POWER SUPPLY -- All units except
208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power
supply, the transformer must be rewired by moving the black
wire fiom the 230-v orange wile on the transformer
and
connecting it to the 200-v red wire fiom the transformer The
orange wire then must be insulated.
Route thermostat cable or equivalent single leads of colored
wire from thermostat subbase terminals to low-voltage connections on unit (shown in Fig. IIA and lIB) as described in
Steps 1-4 below.
1. ff unit is mounted on roof curb and accesso U thru-thebottom connections are used, route wire through connection plate.
Refer to unit label diagram for additional
infommtion.
Pigtails are provided for field service. Use factou-supplied
splices or UL (Undelwriters'
Laboratories) approved copper
connectoL
When installing
units, provide a disconnect
per NEC.
All field wiring must comply with NEC and local requirements. In Canada, electrical connections must be in accordance
with CSA (Canadian Standads
Associaion)
C22.1 Canadian
Electrical Code Part One.
2.
Pass control wires through the hole provided on unit (see
connection D, Connection Sizes table, Fig. 7).
3.
Feed wires through the raceway built into the corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 12. The raceway provides the UL-required
clearance between high-voltage and low-voltage wiring.
Connect thermostat wires to screw terminals of lowvoltage connection boad (see Fig. 11A and 11B).
4.
Install conduit through side panel openings indicaed in
Fig. 7. Route power lines through connector to terminal connections as shown in Fig. 10.
BLK--_-_J_
TO COMPS
5'
BLU
®
®
FIELD POWER
SUPPLY
j __L_/
F--
D IS_NEC
I
I
----1
T
PERNEC
48HJ008-014,
I
J
208/230-3-60
AND 460-3-60
LEGEND
BLK-_iii_
TO COMPS
TB2
BLU_
®
I
I
I
FIELD POWER
F
I
L
--
_L
SUPPLY
/
-- _L_.7
DISCONNECT
PER NEC
__J
48HJ008-014,
I
575-3-60
Fig. 10-
Power Wiring Connections
C
COMPS
IFC
----
NEC
TB
--@
Contactor
Compressors
Indoor (Evaporator) Fan
Contactor
National Electrical Code
Terminal Block
Terminal
ConnectionBlock
Field Wiring
Factory Wiring
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wile Gage) insulated wire (35 C minimum). For 51 to 75 fl,
use no. 16 AWG insulated wire (35 C minimum). For over
75 fl, use no. 14 AWG insulated wire (35 C minimum).
INTEGRATED
GAS UNIT
CONTROLLER
UNIT
CONNECTION
BOARD
RACEWAY
NOTE: All wile larger than no. 18 AWG cannot be directly
connected to the thermostat and will require a junction box and
splice at the thermostat.
HEAT ANTICIPATOR SETTINGS -- On 48HJ008 and 009
units, set heat anticipator settings at 0.14 mnp for both first and
second stage heating for low heat. For all other stages and unit
sizes, set heat anticipator settings at 0.14 amp for fil.st stage and
0.20 amp for second-stage heating.
m
COOL STAGE 1
Y1/W2-
-
- i
-
--
-
R
[
[
FAN
G...........................
F
G
HEAT STAGE 1
W/W1-
Y1
COOL STAGE 2
Y/Y2
HEAT STAGE 2
O/W2-
24 VAC HOT
R-
24 VAC COM
C-
-
q -
- r- -
V -
Y2
k
-
_
_ E
___ _ W1
WIRE
CONNECTIONS
- TO
LOW-VOLTAGE
SECTION
" W2
_
IPD/X
N/A
OUTDOOR
AIR
COMPRESSOR
S1
SENSOR
Fig. 12-
S2
THERMOSTAT
DIPSWITCH
2
COMPRESSOR
Field
Control
1
Wiring
Raceway
SETTINGS
ON
A
B
C
Step 8 --
D
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when
configured for A/C operation.
Fig. 11A-
Standard
Low-Voltage
VAC .... -,--,--,
__,,
@-RMTOCC---'
',,
i"
CMPSAFE-,r
..........
Options
1. Route humidistat
cable through hole provided in unit
corner post.
2. Feed wires through the raceway built into the corner post
to the 24-v barrier located on the left side of the control
box. See Fig. 12. The laceway provides the UL-required
cle_uance between high-voltage and low-voltage wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 15.
To install a Thermidistat device:
1. Route Thermidistat
cable through the hole provided in
unit corner post.
2. Feed the wires through the raceway built into file corner
post to the 24-v barrier located on the left side of the control box. See Fig. 12. The raceway provides the ULrequired clearance between high and low voltage wiling.
3. A field-supplied relay must be installed between the thermidistat and the Humidi-MiZer
circuit (recommended relay: HN612KK324).
The relay coil is connected between
the DEHUM output and C (common) of the unit. Refer to
Fig. 16. The relay controls the Humidi-MiZer
solenoid
valve and must be wired between the Humidi-MiZer fuse
and the low-pressure switch. Refer to the installation instructions included with the Carrier LigN Commercial
Thermidistat device for more information.
@-24
@-FSD
Factory-Installed
NOTE: A light commercial
Thermidistat TM device (Fig. 14)
can be used instead of the humidistat
if desired. The
Thermidistat
device includes a thermostat and a humidistat.
The humidistat is norm_dly used in applications where a temperature sensor is aheady provided (units with PremierLink TM
control).
To install the humidistat:
Connections
THERMOSTAT CONTROL
CONN ECTION
BOARD
CONTROL
CONN ECTION
BOARD
Adjust
HUMIDI-MIZER
TM
ADAPTIVE
DEHUMIDIFICATION
SYSTEM -- Humidi-MiZer
a&_ptive
dehumidification
system operation can be controlled by field installation of
a Carrier-approved humidistat (Fig. 13).
"
@-SFS
NOT USED
@-C
@-X-
Fig. 11 B -- Low Voltage Connections
(Units with PremierLink TM Controls)
10
4O
c_
C_
Elm
lED
[ZD
Fig. 13-
Accessory
Field-Installed
Humidistat
Fig. 14 -- Light Commercial Thermidistat
BLK
OB
I
HR1
BLU
_BRN
3.2 AHPS
.b-_-_-- RED,__
PNK
Device
TM
GRN-YEL
t
_
_J-,
._
PNK
LSV1
BLK_BLK-I
LTLO
CR1
i_uA, I
L_N
_
•
I
Field Splice
|
_'--N,_)_
Unmarked
Splice
0-
BLU-'_I
DSVI
_I_'ORN'E_ORN-I
I_Zl0RN.{_.
_BLU._I
/
°'_--
I_
'PS2
BLU--O_
Field Control
both LLSV1
and LLSV2
RN
0RN.._
B
-N
OSV2
I
0"-"
BLU'-'_
TB
Factory Wiring
is active when
Fig. 15-
|
Lsv2
LPS1
P!!K _J--BLU_
Transformer
Terminal
Lockout
circuit
I r--vlcS
BRN--_
166<34.-Wiring
are energized.
Typical Humidi-MiZer TM Adaptive Dehumidification
Humidistat Wiring (208/230-v Unit Shown)
LCT
System
ROOF TOP UNIT
....--I..............®......
TSTATWIRES
PINK
_ _]-
_/___
_RE_D_ 24V
R1
FROM
HUMIDI-MIZER
LLSV
LEGEND
CB
--
Circuit
Breaker
LCT
LLSV
LTLO
----
Light Commercial
Thermidistat
Liquid Line Solenoid
Valve
Low Temperature
Lockout
TM
Device
PINK
__PI_NK_
HUMIDI-MI7ER
Fig. 16-
.
SYSTEM
Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification
Wiring with Thermidistat Device
11
System
SYSTEM
Table 2A -- Electrical Data (Standard Motor Units Without Electrical Convenience Outlet)
VOLTAGE
UNIT
48HJ
COMPRESSOR
NOMINAL(v.Ph.Hz)VOLTAGE RANGE
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
O08
(71_Tons)
009
(81/2Tons)
012
(10 Tons)
014
(121_Tons)
Min
187
414
518
187
414
518
187
414
518
187
414
518
Max
254
508
632
254
508
632
254
508
632
254
508
632
(each)
Qty
2
2
2
2
RLA
12.4
6.4
4.8
13.4
7.4
6.4
17.6
8.3
6.3
19.0
9.0
7.4
OFM
COMBUSTION
(each)
IFM
FAN MOTOR
FLA
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
FLA
7.5
3.4
3.4
7.5
3.4
3.4
10.6
4.8
4.8
15.0
7.4
7.4
FLA
.60
.30
.30
.60
.30
.30
.60
.30
.30
.60
.30
.30
LRA
88.0
44.0
34.0
105.0
55.0
44.0
125.0
62.5
50.0
156.0
75.0
54.0
POWER
SUPPLY*
MCA
MOCP**
38.2_8.2
45/45
19.2
25
14.6
20
40.2_0.2
45/45
21.5
25
18.2
20
5_53
60/60
24.9
30
19.1
25
MINIMUM UNIT
DISCONNECT
SIZEt
FLA
LRA
40/40
242/242
20
121
15
95
42/42
276/276
23
143
19
115
56/56
341/341
26
171
20
136
60.6/60.6
29.1
23.7
64/64
31
25
70/70_t
35
30
426/426
207
154
Table 2B -- Electrical Data (Standard Motor Units With Electrical Convenience Outlet)
UNIT
48HJ
NOMINAL VOLTAGE
(V-Ph-Hz)
008
(71_Tons)
009
(81/2Tons)
012
(10 Tons)
014
(121/2 Tons)
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
VOLTAGE
RANGE
Min
187
414
518
187
414
518
187
414
518
187
414
518
Max
254
508
632
254
508
632
254
508
632
254
508
632
COMPRESSOR
(each)
Qty
2
2
2
2
RLA
12.4
6.4
4.8
13.4
7.4
6.4
17.6
8.3
6.3
19.0
9.0
7.4
IFM
FLA
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
FLA
7.5
3.4
3.4
7.5
3.4
3.4
10.6
4.8
4.8
15.0
7.4
7.4
FLA
.60
.30
.30
.60
.30
.30
.60
.30
.30
.60
.30
.30
Maximum
deviation is 7 v.
LRA
88.0
44.0
34.0
105.0
55.0
44.0
125.0
62.5
50.0
156.0
75.0
54.0
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
UL
*The
right
tUsed
**Fuse
ttFuse
-- Full Load Amps
--Heating,
Air Conditioning and
Refrigeration
--Indoor (Evaporator) Fan Motor
--Locked
Rotor Amps
--Minimum
Circuit Amps
-- Maximum Overcurrent Protection
--National
Electrical Code
--Outdoor
(Condenser) Fan Motor
--Rated Load Amps
-- Underwriters' Laboratories
COMBUSTION
FAN MOTOR
59/59
27.6
21.3
66.6/66.6
31.8
25.9
MINIMUM UNIT
DISCONNECT
SIZEt
FLA
LRA
46/46
247/247
23
123
17
95
48/48
281/281
25
145
21
116
70/701-_
30
25
61/61
29
22
345/345
173
138
70/70tt
35
30
70/70
33
27
431/431
209
156
Determine
percent of voltage imbalance,
7
% Voltage Imbalance = 100 x 45_
= 1,53%
This amount of phase imbalance is satisfactory
allowable 2%.
as it is below the maximum
IMPORTANT: If the supply voltage phase imbalance
tact your oca e ectr cut ty company turned ate y.
values listed in this table do not include power exhaust.
for power exhaust requirements.
to determine minimum disconnect per NEC.
or HACR circuit breaker.
only.
is more than 2%, con-
POWER EXHAUST ELECTRICAL
See table at
POWER EXHAUST
PART NO.
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
CRPWREXH030A01
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature _+ 10%
voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where, a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of voltage imbalance.
DATA
MCA
MCA
MCA
(230 v)
N/A
3.3
N/A
1.7
N/A
1.6
(460 v)
0.9
N/A
1.8
N/A
1.0
N/A
(575 v)
N/A
1.32
N/A
0.68
N/A
0.84
MOCP
(for separate
power source)
15
15
15
15
15
15
N/A -- Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCR
% Voltage Imbalance
= 100 x
POWER
SUPPLY
WITH OUTLET*
MCA
MOCP**
44.2/44.2
50/50
21.9
25
16.8
20
46.2/46.2
50/50
24.2
30
20.4
25
OFM
(each)
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
max voltage deviation from average voltage
average voltage
MCA New = MCA unit only + MCA of Power Exhaust
Example: Supply voltage is 460-3-60.
A
B
C
For example, using a 48HJD008 unit with MCA = 38.2 and MOCP = 45, with
CRPWREXH030A01
power exhaust.
AB = 452 v
BC = 464 v
Average Voltage =
AC =455v
MCA New = 38.2 amps + 1.6 amps = 39.8 amps
If the new MCA does not exceed the published MOCE then MOCP would not
change. The M©CP in this example is 45 amps and the MCA New is below
45; therefore the MOCP is acceptable. If MCA New" is larger than the published M©CP, raise the MOCP to the next larger size. For separate power, the
MOCP for the power exhaust will be 15 amps per NEC.
452 + 464 + 455
3
1371
3
457
Determine maximum deviation from average voltage.
(AB) 457 -452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v
12
Table 2C -- Electrical Data (High-Static Motor Units Without Electrical Convenience Outlet)
NOMINAL
VOLTAGE
UNIT
48HJ
(V-Ph-Hz)
208/230-3-60
460-3-60
578-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
578-3-60
008
009
012
VOLTAGE
RANGE
Min
187
414
632
187
414
518
187
414
518
Max
254
508
518
254
508
632
254
508
632
COMPRESSOR
(each)
Qty
RLA
12.4
6.4
4.8
13.4
7.4
6.4
17.6
8.3
6.3
2
2
2
LRA
88.0
44.0
34.0
105.0
55.0
44.0
125.0
62.5
50.0
OFM
(each)
IFM
FLA
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
FLA
10.6
4.8
4.8
10.6
4.8
4.8
15.0
7.4
7.4
COMBUSTION
FAN MOTOR
MINIMUM UNIT
DISCONNECT
SIZEt
FLA
LRA
44
267
22
134
17
104
46
301
24
186
19
115
POWER
SUPPLY*
MCA
MOCP**
41.3
45
20.6
28
15.8
20
43.3
50
22.9
25
18.2
20
RLA
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
87.4
27.5
21.7
70tt
30
25
61
29
23
364
182
146
Table 2D -- Electrical Data (High-Static Motor Units With Electrical Convenience Outlet)
NOMINAL
VOLTAGE
UNIT
48HJ
(V-Ph-Hz)
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
875-3-60
208/230-3-60
460-3-60
578-3-60
008
009
012
VOLTAGE
RANGE
Min
187
414
518
187
414
518
187
414
518
Max
254
808
632
254
508
632
254
508
632
COMPRESSOR
(each)
Qty
2
2
2
RLA
12.4
6.4
4.8
13.4
7.4
6.4
17.6
8.3
6.3
LRA
88.0
44.0
34.0
105.0
55.0
44.0
125.0
62.5
50.0
OFM
(each)
IFM
FLA
1.4
0.7
0.7
1.4
0.7
0.7
1.4
0.7
0.7
FLA
10.6
4.8
4.8
10.6
4.8
4.8
15.0
7.4
7.4
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
UL
MINIMUM UNIT
DISCONNECT
SIZEt
FLA
LRA
49
271
24
136
19
104
51
308
27
188
22
126
SUPPLY*
MCA
MOCP**
47.3
80
23.3
25
17.9
20
49.3
60
25.6
30
21.5
25
RLA
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
63.4
30.2
23.4
70t1"
35
25
66
32
25
369
184
148
Maximum deviation is 7 v.
-- Full Load Amps
-- Heating, Air Conditioning and
Refrigeration
-- Indoor (Evaporator) Fan Motor
-- Locked Rotor Amps
--Minimum
Circuit Amps
--Maximum
Overcurrent Protection
--National
Electrical Code
--Outdoor
(Condenser) Fan Motor
-- Rated Load Amps
-- Underwriters' Laboratories
Determine
percent of voltage imbalance.
7
= 100 x 457
% Voltage Imbalance
0Q0s
= 1.53%
This amount of phase imbalance
allowable 2%.
is satisfactory
as it is below the maximum
IMPORTANT: If the supply voltage phase imbalance
tact your local electric utility company immediately.
*The values listed in this table do not include power exhaust.
right for power exhaust requirements.
l-Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker.
ttFuse only.
POWER
See table at
POWER EXHAUST
PART NO,
CRPWREXHO21A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
CRPWREXH030A01
NOTES:
1. In compliance with NEC requirements for multirnotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker,
2. Electrical data based on 95 F ambient outdoor-air temperature _+ 10%
voltage,
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where, a pbase imbalance in supply voltage is
o
greater than 2_,
Use the following formula to determine the percent of voltage imbalance.
N/A --
EXHAUST
MCA
(230 v)
N/A
3.3
N/A
1.7
N/A
1.6
ELECTRICAL
MCA
(460 v)
0.9
N/A
1.8
N/A
1.0
N/A
is more than 2%, con- I
I
DATA
MCA
(575 v)
N/A
1.32
N/A
0.68
N/A
0.64
MOCP
(for separate
power source)
15
15
15
15
15
15
f
Not available
NOTE: If a single power source is to be used, size wire to include power
exhaust MCA and MOCR
% Voltage Imbalance
= 100 x
POWER
COMBUSTION
FAN MOTOR
Check MCA and MOCP when power exhaust is powered through the unit.
Determine the new MCA including the power exhaust using the following
formula:
max voltage deviation from average voltage
average voltage
MCA New = MCA unit only + MCA of Power Exhaust
Example: Supply voltage is 460-3-60.
A
B
c
For example, using a 48HJD008 unit with MCA = 38.2 and MOCP = 45, with
CRPWREXH030A01
power exhaust.
AB = 452 v
BC = 464 v
Average Voltage AC = 455 v
MCA New = 38.2 amps + 1.6 amps = 39.7 amps
If the new MCA does net exceed the published MOCE then MOCP would net
change. The MOCP in this example is 48 amps and the MCA New is below
45; therefore the MOCP is acceptable. If "MCA New" is larger than the published MOCE raise the MOCP to the next larger size. For separate power, the
MOCP for the power exhaust will be 15 amps per NEC.
482 + 464 + 455
3
1371
3
457
Determine maximum deviation from average voltage.
(AB) 487 - 482 = 5 v
(BC) 464 - 487 = 7 v
(AC) 457 - 488 = 2 v
13
CONVENIENCE
OUTLET -- An optional convenience outlet provides power for rooftop use. For maintenance personnel
safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service
tools. An optional "Hot Outlet" is available from the factory as
a special order item.
NOVAR
CONTROLS
-Optional
Novar
controls
(ETM 3051) are available for replacement or new constructions jobs.
MANUAL OUTDOOR-AIR
DAMPER -- The outdoor-air
hood and screen are attached to the basepan at the bottom of
the unit for shipping.
HOOD TOP SCREWS
(HIDDEN)
SCREWS
AssemblE;.."
1. Determine quantity of ventilation
Record amount for use in Step 8.
required
for building.
HOOD
2.
Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are lequiled to remove the filter
access panel. Remove outdoor-tfir opening panel. Save
panels and screws. See Fig. 17.
3.
Sepmate hood and screen from basepan by removing the
screws and brackets securing them. Save all screws and
discard brackets.
Fig. 18-
Replace outdoor
from Step 2.
5.
Place hood on front of outdoor-air opening panel. See
Fig. 18 for hood details. Secure top of hood with the 6
screws removed in Step 3. See Fig. 19.
SCREW
Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air dmnpel:
Align screw holes on hood with screw holes on side of
manual outdoor-air dampel: See Fig. 18 and 19. Secure
hood with 6 screws from Step 6.
(TOP)
HOOD
Adjust minimum position setting of the damper blade by
adjusting the manu_d outdoor-air adjustment screws on
the front of the damper blade. See Fig. 17. Slide blade
vertically until it is in the appropriate position determined
by Fig. 20. Tighten screws.
SCREEN
7.
8.
9.
10.
panel with screws
HOOD
SIDE
4.
6.
air opening
SlDESANDTOPASSEMBLED
Outdoor-Air
Hood Details
saved
HOLES
-_
::::::_
IJ
\i
ocd,oN
i
NOT
SHOWN)
Remove and save screws currently on sides of hood.
Insert screens. Secure screens to hood using the screws.
See Fig. 19.
Replace filter access panel. Ensure filter access
slides _dong the tracks and is securely engaged.
panel
Fig. 19-
Optional Manual Outdoor-Air Damper
with Hood Attached
1.0
OUTDOOR
AIR OPENING
PANEL
t3b
///
0.8
w
0.6
3 SCREWS
(SIDE)
/
w
n_
7./
w
>
oI11
/
z
MANUAL
ADJUSTMENT
SCREWS
0.2
POSITION SETTING
SCALE
DAMPER
BLADE
0
_
2
..i
4
OUTDOOR
Fig. 17 -- Damper Panel with Manual
Outdoor-Air Damper Installed
"
8
AIRFLOW
10
(cfm x 100)
Fig. 20 -- Outdoor-Air Damper Position Setting
14
12
PREMIERLINK
CONTROL
TM
--
The
PremierLink
control-
into the fan section, down along the back side of the fan, and
_flong the fan deck over to the supply-air opening.
The SAT probe is wire-tied to file supply-air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re-position the sensor in the flange of
the supply-air opening or in the supply air duct (as required by
local codes). Drill or punch a l/2-in, hole in the flange or duct.
Use two field-supplied, self-drilling screws to secme the sensor
probe in a horizontal orientation.
let is compatible
with Carrier Comfoll
Network®
(CCN) devices. This control is designed
to allow users file access and
ability to change
factory-defined
settings,
thus expanding
the
function
of file standiu'd unit control board. Career's
diagnostic
standard
tier display tools such as Navigator
or Scrolling
quee can be used wifll the PmmierLink
controflel:
The PremielLink
the use of a Carrier
for time broadcast
Mar-
controller
(see Fig. 21A and 21 B) requires
electronic
thermostat
or a CCN connection
to initiate
its internal
timeclock.
This is
NOTE: The sensor must be mounted in the dischmge airstream
downstream of the cooling coil and any heating devices. Be
sure the probe tip does not come in contact with any of the unit
or heat surfaces.
necessmy
for broadcast
of time of &ty functions
(occupied/
unoccupied).
No sensors
me supplied
with the field-mounted
PremierLink
control.
The factory-installed
PremierLink
control includes
only the supply-air
sensor (SAT) and the outdoor
air temperature
(CO2) sensor
sensor
usage.
sensor ((-)AT) as stan&trd. An indoor air quality
can be added as an option. Refer to Table 3 for
Refer to Fig. 22 for PremierLink
controller
wiring.
control
PmmierLink
control
may
or an area below the control
The
panel
NOTE:
PmmierLink
shipped
mierLink
in Sensor
controller
Install the Supply
the unit is supplied
controller
be mounted
panel.
versions
mode.
If used with
must be configured
1.3
and
in
file
later
am
a fllermostat,
to Themlostat
Air Temperature
(SAT)
with a factory-mounted
Outdoor
Air Temperature
(OAT) Sensor
-- When the unit is
supplied
with a factory-mounted
PmmierLink
control,
the
outdoor-air
temperature
(OAT) sensor is factory-supplied
and
wimdi
Install the Indoor Air Quality
(CO2.) Sensor
-optional
indoor air quality (CO2) sensor according
turer specifications.
the Premode.
Sensor
-PremierLink
A separate field-supplied
er the CO2 sensor
When
con-
must
be used
trol
[nstallation,
detailed
wiring
Start-Up,
and
and configuration
Configuration
[nstructions
information.
O
INPUTS
¢
SPACE TEMP -_
SET POINT -_
n_
SUPPLY AIR TEMP
OUTDOOR
OUTDOOR
DUAL MODE
plm _
33CSF'RE,_I_
-_
AIR QUALITY
SENSOR/STAT
REMOTE OCCUPANCY
(G)
COMP SAFETY (Y1)
FIRE SHUTDOWN
t|'l/'l-I
i
(Y2)
SUPPLY FAN STATUS (W1)
................
_......_.J
NOT USED (W2)
ENTHALPY
•
TEMP
INDOOR AIR QUALITY
'/ill
_
_
...............
1"] q 7 I-?']
& .............
STATUS (ENTH) /
CCN/LEN
PORT
/
NAVIGATOR
PORT
to pow-
Wire file CO_ sensor to the COM and IAQI terminals
on the PremierI_ink
controllel:
Refer to the PremierLink
trol, the supply-air
temperature
(SAT) sensor (33ZCSENSAT)
is factory-supplied
and wired. The wiring
is routed from the
PmmierLink
control over the control box, through a grommet,
HVAC SENSOR
transformer
Mount
the
to manufac-
4-20MA
ECONOMIZER
/
15
"4 "-4 "-,,
COMPR
1 & 2
OUTPUTS
-
Fig. 21A -- PremierLink
t
INDOOR
FAN MOTOR
Controller
HEAT
LOW/HIGH
EXHAUST
RVS VALVE
of J5
confor
©O
PREMIERLINK
CONTROL
HINGED
DOOR
PANEL
PREMIERLINK
COVER
Fig. 21B -- PremierLink
TM
Controller (Installed)
Table 3 -- PremierLink Sensor Usage
APPLICATION
Differential
Dry Bulb
Temperature
with
PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
OUTDOOR
TEMPERATURE
Included
AIR
SENSOR
--
CRTEMPSN001A00
RETURN
TEMPERATURE
AIR
SENSOR
Required -33ZCT55SPT
OUTDOOR
AIR
ENTHALPY
SENSOR
RETURN AIR
ENTHALPY
SENSOR
--
--
or Equivalent
Single Enthalpy
with
PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
Included -Not Used
--
Required -HH57AC077
or Equivalent
--
Differential
Enthalpy
with PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
Included -Not Used
--
Required -HH57AC077
or Equivalent
Required -HH57AC078
or Equivalent
*PremierLink
control requires Supply Air Temperature
sensor 33ZCSENSAT
and
Outdoor Air Temperature
sensor HH79NZ017
-- included with factory-installed
PremierLink
control;
field-supplied
and field-installed
with field-installed
PremierLink control.
NOTES:
1. CO2 Sensors (Optional):
33ZCSENCO2
-- Room sensor (adjustable).
Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2
-- Aspirator box used for duct-mounted
CO2 room sensor.
33ZCT55CO2
-- Space temperature
and CO2 room sensor with override.
33ZCT56CO2
-- Space temperature
and CO2 room sensor with override and set point.
2. All units include the following Standard Sensors:
Outdoor-Air Sensor -- 50HJ540569
-- Opens at 67 F, closes at 52 F, not adjustable.
Mixed-Air SensorHH97AZ001
-- (PremierLink
control requires Supply Air Temperature
sensor 33ZCSENSAT
and Outdoor Air Temperature
Sensor HH79NZ017)
Compressor
Lockout Sensor -- 50HJ540570
-- Opens at 35 F, closes at 50 E
16
HK50AA039
I
......
:F-<
PremierLink
VJO
PNK
YEL
£LU
.............
_
_BLK
RED
£LU
YEL
ii
WHT
3 (/15
i
ORN
i
PNK
ORN ...................................................
ilL/'
RED
_,
PN_
CON
Comm
i
Economi$er2
[ RED
4- 20mA
-
L
BLK
,
i
{
i
i
J
8ql --
URN
SENSOR
COMMS -OAT
-PWR
-RTU
-SAT
-TB
--
LEGEND
Communications
Outdoor Air Temperature Sensor
Power
Rooftop Unit
Supply Air Temperature Sensor
Terminal Block
TM
W_T
\jjj_
_\
Fig. 22 -- Typical PremierLink
7 r/i-,
C
ILl
8 /r_,X
RTU Terminal
Board
Controls Wiring
b. Connect the RED wire to the 24 vac GND terminal
(TR) on enthalpy sensor and to pin 4 on 12-pin
harness.
c. Connect the GRAY/ORN wire to J4-2 on PremierLink controller and to terminal (3) on enthalpy sensol:
d. Connect the GRAY/RED wire to J4-1 on PremierLink controller and to terminal (2) on enthalpy sensol:
NOTE: If installing in a Carrier rooliop, use the two gray wiles
provided from the control section to the economizer to connect
PremierLink controller to termimds 2 and 3 on enthalpy sensol:
Enthalpy
Sensors and Control
-- The enthfflpy control
(HH57AC077)
is supplied as a field-instfdled accessory to be
used with the EconoMi$er2
damper control option. The outdoor air enthalpy sensor is pall of file enfllalpy control. The
separate field-installed
accessory return air enthalpy sensor
(HH57AC078)
is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the "D" setting for
differential enthalpy control to work properly.
The enthalpy
control receives
the indoor and return
enthalpy fiom the outdoor find return air enthalpy sensors and
provides a dry contact switch input to the PremierLink
controllel: Ix_cate the controller in place of an existing economizer controller or near the actuatol: The mounting plate may
not be needed if existing bracket is used.
ENTHALPY
CONTROLLER
RED
A closed contact indicates that outside air is preferred to the
return ail: An open contact indicates that file economizer
should remfdn fit minimum position.
A(_C
sorh +[3TR Fa"ITR 1[_-
BRN
SRI-h+H- -q
Outdoor
Air
Enthalpy
Sensor/Enthalpy
Controller
(HH57AC077)
-- To wire the outdoor air enthalpy sensok
perform file following (see Fig. 23 and 24):
NOTE: The outdoor air sensor can be removed from the back
of file enthalpy controller and mounted remotely.
1. Use a 4-conductor, 18 or 20 AWG cable to connect the
enthalpy control to the PremierLink controller and power
transforme£
2.
6 (]]_G
BLK
i
ENTHALPY
REDBR N
7 (][) .............
WHT............................................................................................................
AIR
ENTHALPY
SENSOR)
lOUTOOOR
I
BLK
RED
I
[]
S (RETURN
[]
+ ENTHALPY
AIR
SENSOR)
GRAY/ORN
_WIRE
LED
GRAY/RED
JlN
HARNESS
UNIT
NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy,
3. Remove sensor mounted on back of control and locate in outdoor
airstream.
Connect the following 4 wires from the wire harness
located in rooftop unit to the enthzdpy controller:
a. Connect the BRN wire to file 24 vac terminal (TRI)
on enth_dpy control and to pin 1 on 12-pin harness.
Fig. 23 -- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
17
HH57AC077
ENTHALPY
CONTROL AND
OUTDOOR AIR
ENTHALPY SENSOR
ECONOMI$ER
IV
-CONTROLLER
OUTSIDE
AIR
ACTUATOR-
o
o
HH57AC078
ENTHALPY
SENSOR (USED WITH
ENTHALPY
CONTROL
FOR DIFFERENTIAL
ENTHALPY
OPERATION)
Fig. 25 --
EconoMi$er
IV Component
Locations
OUTDOOR
AIR HOOD
MOUNTING
PLATE
ECONOMI
Fig. 24 -- Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)
PLUG
-SHIPPING
BRACKET
Return Air Enthalpy Sensor -- Mount the return-air enthalpy
sensor (HH57AC078)
in the return-air duct. The return air
sensor is wired to the enthalpy contrDller (HH57AC077).
The
outdoor enthalpy changeover set point is set at the contrDller.
To wire the return air enthalpy
ing (see Fig. 23):
sensol: perform
the follow-
1. Use a 2-conductor,
18 or 20 AWG. twisted pail cable to
connect the return air enthalpy sensor to the enthalpy
controller.
2.
At the enthalpy control remove the
resistor from the (SR) and (+) termimds.
GEAR DRIVEN
DAMPER
BAROMETRIC
RELIEF
DAMPER
Fig. 26 --
factory-installed
FILTER
EconoMi$er2
ACCESS
Component
Locations
PANEL
3.
Connect the field-supplied
RED wire to (+) spade
connector on the return air enthalpy sensor and the (SR+)
terminal on the enthalpy contrDllel: Connect the BLK
wire to (S) spade connector on the return air enthalpy
sensor and the (SR) terminal on the enthalpy contrDllel:
OPTIONAL
ECONOMISER
IV AND ECONOMISER2
-See Fig. 25 for EconoMiSer
IV component
locations. See
Fig. 26 for EconoMi$er2 component locations.
NOTE: These instructions
are for insUdling the optional
EconoMi$er IV and EconoMiSer2 only. Refer to the accessory
EconoMiSer IV or EconoMiSer2 inst_dlation instructions when
field installing an EconoMiSer IV or EconoMiSer2 accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outw;ud. The panel is now
disengaged
from the track and can be removed. See
Fig. 27.
2.
INDOOR
Fig. 27 -- Typical
Access
COILACCESS
The box with the economizer
hood components
is
shipped in the compartment behind the economizel: The
EconoMiSer
IV contrDller is mounted on top of the
EconoMi$er IV in the position shown in Fig. 25. The optional EconoMiSer2 with 4 to 20 mA actuator signal control does not include the EconoMiSer IV contrDllel: To lemove the component box from its shipping position, remove the screw holding the hood box bracket to the top
of the economizel: Slide the hood box out of the unit. See
Fig. 28.
IMPORTANT:
If the power exhaust accessory is to be I
inst_dled on the unit, the hood shipped with the unit will not
be used and must be discarded. Save the aluminum
filter
for use in the power exhaust hood assembly.
iI
I
111
11
/
i I
/
0
i I
I1
111/_
i I
/
Fig. 28 -- Hood Box Removal
18
PANEL
Panel Locations
3.
4.
5.
6.
7.
8.
9.
10.
The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 29.
Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the sclews provided
to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 30.
Remove the shipping tape holding the economizer barometric relief damper in phtce.
Insert the hood divider between the hood sides. See
Fig. 30 and 31. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bottom filter rock for file aluminum filter.
Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push file filter into position past the
open filter clips. Close the filter clips to lock the tilter into
place. See Fig. 31.
Caulk the ends of the joint between the unit top panel and
the hood top. See Fig. 29.
Replace the filter access panel.
Install all EconoMi$er
IV accessories. EconoMiSer
IV
wiling is shown in Fig. 32. EconoMi$er2 wiling is shown
in Fig. 33.
ALUMINUM
FILTER
BAROMETRIC
RELIEF
FILTER
CLIP
Fig. 31 -- Filter Installation
ECONOMISER
Barometric flow capacity is shown in Fig. 34. Outdoor air
leakage is shown in Fig. 35. Return air pressure drop is shown
in Fig. 36.
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the "crimp end"
and is sealed from moisture.
Outdoor Air Lockout Sensor
-- The EconomiSer
IV is
equipped with an mnbient temperature lockout switch located
in the outdoor airstream which is used to lockout the compressors below a 42 F ambient temperature. See Fig. 25.
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
',
INDOOR
COIL
"',
Table
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SIDE
DIVIDER
Fig. 30 -- Outdoor-Air
Hood Construction
19
(F)
RESISTANCE (ohms)
200,250
-40
-22
-4
14
100,680
53,010
29,091
16,590
32
50
68
77
9,795
5,970
3,747
3,000
86
104
122
140
158
176
185
194
212
230
248
257
266
284
302
LEFT
HOOD
4 -- Supply Air Sensor Temperature/
Resistance
Values
TEMPERATURE
-58
Fig. 29 -- Indoor Coil Access Panel Relocation
j
SENSORS
Supply Air Tempelature
(SAT) Sensor
-- The supply air
temperature sensor is a 3 K thermistor located at the inlet of the
indoor fan. See Fig. 37. This sensor is factory installed. Tile operating range of temperature measurement is 0 ° to 158 F. See
Table 4 for sensor temperature/resistance
values.
\
_.
IV STANDARD
Outdoor Air Temperature
(OAT) Sensor -- The outdoor air
temperature sensor (HH57AC074)
is a 10 to 20 mA device
used to measure the outdoor-air temperature. The outdoor air
temperature is used to determine when the EconoMiSer IV can
be used for free cooling. The sensor is factory-installed
on the
EconoMi$er IV in the outdoor airstream. See Fig. 25. Tile operating range of temperature measurement is 40 to 100 E
SIDE
PANEL
\
,
2,416
1,597
1,080
746
525
376
321
274
203
153
116
102
89
70
55
.,
/
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED
TIME CLOCK
(_L}(
ECONOMIZER
MOTOR
BLf(
PL6"R
--GRYJ
(_OT USEO)
I_
(NOT USED)
I_
<
BLU
mELD
FIELD
<
SPLICE
SPLICE
BRN
L
_
(_0f
USES)
4
TAN
GRY
ORG
TO
LEGEND
DCV-IAQ -LA -OAT-POT-RAT--
Demand Controlled Ventilation
Indoor Air Quality
Low Ambient Lockout Device
Outdoor-Air Temperature
Potentiometer
Return-Air Temperature
PWR
EXHAUST
ACCESSORY
Potentiometer Defaults Settings:
Power Exhaust
Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting
(_01USEO}
:t
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed
remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
Fig. 32 -- EconoMi$er IV Wiring
BLACK
4
3
5
2
500 OHM
8
RESISTOR-'?
VIOLET
6
NOTE 1
PINK
RUN
r
7
i
I
RED
1
-e_l_
NOTE3
I
J
+'-I
10
i
I
50HJ540573
ACTUATOR
ASSEMBLY
S
OPTIONAL CO2
SENSOR 4 - 20 mA
OUTPUT
11
W
>-
9
WHITE
DIRECT DRIVE
ACTUATOR
12
ECONOMIZER2
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink TM control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00
enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohrn resistor.
Fig. 33 -- EconoMi$er2 with 4 to 20 mA Control Wiring
20
PLUG
dry bulb sensor or HH57A077
ECONOMISER IV CONTROL MODES
2500
z
I
a controllec The EconoMiSer2 is operated by a 4 to 20 mA
signal from an existing field-supplied controller (such as
I IMPORTANT:
optional
doesinformation.
not include ]
PremierLink TM The
control).
See EconoMiSer2
Fig. 33 for wiring
2000
tiff
1500
1000
Determine the EconoMiSer W control mode before set up of
the contl_ol. Some modes of operation may lequire different sensors. Refer to Table 5. The EconoMiSer IV is supplied from file
factory with a supply air temperature sensor and an outdoor air
temperature sensoc This allows for operation of the EconoMi$er
IV with outdoor air chy bulb changeover control. Additiomd accessories can be added to _dlow for different types of changeover
control and operation of the EconoMiSer IV and unit.
LL
O
500
0
_z
0.05
S
0.15
LL
0.25
STATIC PRESSURE
(in. wg)
Fig. 34 -- Barometric Relief Flow Capacity
Table 5 -- EconoMi$er IV Sensor Usage
30-
"xzzzzzzzzzzzzzzzzzzzzzz
APPLICATION
z!
25
Accessories
_
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy
2o
o_
15
w
LL
10
_o
m 5
Differential
Enthalpy
O
_z
0
0.13
0.20
0.22
_I
0.25
STATIC
LL
0.30
0.35
PRESSURE
0.40
0.45
0.50
CO2 for DCV
Control using a
Wall-Mounted
CO2 Sensor
CO2 for DCV
Control using a
Duct-Mounted
CO2 Sensor
(in. wg)
Fig. 35 -- Outdoor Air Damper Leakage
_o
None. The outdoor
is factory
AIR
Required
air dry bulb sensor
installed.
CRTEMPSN002A00*
HH57AC078
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
and
33ZCASPCO2**
33ZCSENCO21-
CRCBDIOX005A001-1-
*CRENTDIF004A00
and CRTEMPSN002A00
accessories
are used on
many different base units. As such, these kits may contain parts that
will not be needed for installation.
1-33ZCSENCO2
is an accessory CO 2 sensor.
**33ZCASPCO2
is an accessory
aspirator
box required
for ductmounted applications.
1-1-CRCBDIOX005A00
is an accessory that contains both 33ZCSENCO2
and 33ZCASPCO2
accessories.
600C_
5000
4000
o
ECONOMI$ER
IV WITH OUTDOOR
DRY BULB SENSOR
2005
Outdoor DLy Bulb Changeover
-- The standald controller is
shipped from the factory configured for outdoor dry bulb
changeover control. The outdoor air and supply air temperature
sensors tue included as stan&u'd. For this control mode, file outdoor temperature is compared to an adjustable set point selected
on file control. If the outdoor-air temperature is above the set
point, the EconoMi$er IV will adjust file outdoor-air dampers to
minimum position. If the outdoor-air temperature is below the
set point, the position of the outdoor-air &unpel.s will be controlled to provide free cooling using outdoor aic When in this
mode, file LED next to file free cooling set point potentiometer
will be on. The changeover temperature set point is controlled
by the free cooling set point potentiometer located on file control. See Fig. 38. The sc_de on the potentiometer is A, B, C, and
D. See Fig. 39 for the conesponding
temperature changeover
values.
lOOO
z
0
'
O
LL
i
0.05
,
0.10
r
,
0.15
i
,
0.20
STATIC PRESSURE
i
,
0.25
r
,
0.30
i
,
i
0.35
(in. wg)
Fig. 36 -- Return Air Pressure Drop
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
Differential Dry Bulb Control -- For differential dry bulb
control file standard outdoor chy bulb sensor is used in conjunction with an additional accessory dry bulb sensor (part number
CRTEMPSN002A00).
The accessoq sensor must be mounted
in the return airstream. See Fig. 40. Wiring is provided in the
EconoMi$er IV wiring htuness. See Fig. 32.
LOCATION
\
SUPPLY AIR
TEMPERATURE
SENSOR
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower temperature air stremn is used for cooling. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer
fully clockwise to the D setting. See Fig. 38.
_
Fig. 37 -- Supply Air Sensor Location
21
Outdoor Enthalpy Changeover
-- For enthalpy control, accessory enthalpy sensor (p_ut number HH57AC078)
is required. Replace the standard outdoor @ bulb temperature sensor with file accessory enthalpy sensor in the same mounting
location. See Fig. 25. When the outdoor air enfllalpy rises
above the outdoor enthalpy changeover set point, file outdoorair damper moves to its minimum position. Tile outdoor
enthalpy changeover set point is set with the outdoor enth_dpy
set point potentiometer on the EconoMi$er IV controllel: The
set points are A, B, C, and D. See Fig. 41. The factory-installed
620-ohln jumper must be in place across terminals SR and SR+
on the EconoMiSer IV controllel: See Fig. 25 and 42.
EXHAUST
FAN SET POINT
LED LIGHTS
WHEN EXHAUST
CONTACT IS MADE
MINIMUM
POSITION
DAMPER
SETTING
MAXIMUM DAMPER
DEMAND CONTROL
VENTILATION SET POINT
LED LIGHTS WHEN_
DEMAND CONTROL
VENTILATION
INPUT
tS ABOVE SET POINT
Differential Enthalpy Control
-- For differential
enth_dpy
control, the EconoMiSer IV controller uses two enthalpy sensors (HH57AC078
and CRENTDIF004A00),
one in the outside air and one in the return air duct. The EconoMiSer IV
controller compmes file outdoor air enthalpy to the return air
enthalpy to determine
EconoMiSer
IV use. The controller
selects the lower enthalpy air (return or outdoor) for cooling.
For example, when the outdoor air has a lower enthalpy than
the return air. the EconoMiSer IV opens to bring in outdoor air
for free cooling.
DEMAND CONTROL
VENTILATION SET POINT
LED LIGHTS WHEN
OUTDOOR AiR IS
FREE
COOLING
SUITABLE
FOR
CHANGEOVER
Fig. 38 --
ENTHALPY
SET POINT
EconoMi$er
IV Controller
and LED Locations
Potentiometer
Replace the standard outside air din bulb temperature sensor with the accessory enthalpy sensor in the same mounting
location. See Fig. 25. Mount the return air enthalpy sensor in
the leturn air duct. See Fig. 40. Wiring is provided in the
EconoMiSer IV wiring harness. See Fig. 32. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer
on the EconoMiSer IV controllel: When
using this mode of changeover control, turn the enth_flpy setpoint potentiometer fully clockwise to the D setting.
19.
1716- --
LED ON
- LED OFF
15<
E14-
LED OFF-
,
LED O;
13"
I
LED ON-- --
12-
Indoor Air Quality (IAQ) Sensor Input -- The IAQ input
can be used for demand control ventilation control based on the
level of CO 2 measured in the space or return air duct.
11-
LED_oFAF
'_...,
10-
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQI terminals of the controllel: Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air
qu_dity sensor fit the user-determined
set point. See Fig. 43.
I
9-i
4O
45
50
55
60
65
DEGREES
70
75
80
85
90
95
100
FAHRENHEIT
Fig. 39 -- Outdoor Air Temperature
Changeover Set Points
ECONOMI$ER
If a separate field-supplied transformer is used to power the
IAQ sensol: the sensor must not be grounded
or the
EconoMiSer IV control bo_ud will be &imaged.
T_7
Fig. 40 -- Return Air Temperature or
Enthalpy Sensor Mounting Location
22
CONTROL
CONTROL
POINT
CURVE
APPROX. °F (°C)
AT 50% RH
A
73 (23)
B
70 (21)
C
D
67 (19)
63 (17)
HIGH
35
40
45
50
55
60
65
70
75
80
85
90
95
180
\
105
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
(27)
(29)
(32)
(35)
(38)
(41)
APPROXIMATE
DRY
BULB
TEMPERATURE
Fig. 41 -- Enthalpy
i
Set
OV
2
110
(43)
o
o
F (C)
Changeover
Set Points
CO2
N
LIMIT
CURVE
SENSOR
MAX
RANGE
SETTING
6000
.
5000
P1
r_EX_
P _l_Jl
(_'_
Vac
24T_24
HO
Min
z
COM
Va_
_o
T1 E-] _.os
T _l_Jl
3000
Open
LT_
Z
q-b,
11 2
6
1/,/
Aol IT]oov_
_AQ _l_Jl
--
s°+ N
DCV
E sRur oo,©
_lb-_c
8
2000
LU
(D
Z
<
CC
1000
0
4
2v_ov e'
so _l_JI
SR+
4000
cc
2
DAMPER
3
VOLTAGE
4
5
FOR
MAX
6
7
VENTILATION
8
RATE
Free
EF B
Fig. 43 -- C02 Sensor
EF1
¢
Fig. 42 -- EconoMi$er IV Control
23
Maximum
Range Setting
Damper Movement -- Damper movement trom full open to
full closed (or vice versa) takes 2112minutes.
Thermostats -- The EconoMi$er IV control works with conventiomd thermostats that have a YI (cool stage 1), Y2 (cool
stage 2), Wl (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat termimd connection board located in the main control box.
Exhaust Set Point Adjustment
-- The exhaust set point will
determine when the exhaust fan runs based on dmnper position
(if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer
See Fig. 38. The set point represents the damper position above
which the exhaust fans will be turned on. When there is a call
for exhaust, the EconoMiSer IV controller provides a 45 _+15
second delay before exhaust fan activation to allow the dampers to open. This delay _fllows file damper to reach the appropriate position to avoid unnecessary fan overload.
Occupancy Control -- The facto U default configuration for
the EconoMi$er IV control is occupied mode. Occupied status
is provided by the black jumper fiom terminal TR to terminal
N. When unoccupied mode is desired, inst_dl a field-supplied
timeclock function in place of the jumper between TR and N.
See Fig. 32. When the timeclock contacts are closed, the
EconoMi$er IV control will be in occupied mode. When the
timeclock contacts are open (removing the 24-v signal from
terminal N), the EconoMi$er IV will be in unoccupied mode.
Minimum Position Control -- There is a minimum damper
position potentiometer on the EconoMiSer [V controllel: See
Fig. 38. The minimum damper position maintains the minimum airflow into the building during the occupied period.
When using demand ventihttion, the minimum dmnper position represents the minimum ventilation position for VOC
(volatile organic compound)
ventilation requirements.
The
maximum demand ventilation position is used for fully occupied ventilation.
When demand
minimum position
cupied ventilation
position should be
Demand Controlled Ventilation (DCV) -- When using the
EconoMi$er IV for demand controlled ventilation, them are
some equipment selection criteria which should be considered.
When selecting the heat capacity and cool capacity of the
equipment, the maximum ventilation rote must be evaluated for
design conditions. The maximum damper position must be calculated to provide the desired fresh air
Typically the maximum ventilation rate will be about 5 to
10% morn than the typical cfin required per person, using normid outside air design criteria.
ventilation control is not being used, the
potentiometer should be used to set the ocposition. The maximum demand ventilation
turned fully clockwise.
Adjust the minimum position potentiometer
to allow the
minimum mnount of outdoor aik as required by local codes, to
enter the building. Make minimum position adjustments with
at least 10 F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum
following procedure:
position
setting,
perform
1. Calculate the appropriate mixed air temperature
following formula:
OA
RA
(To x l-Tiff) + (TR x l-Tiff) = T M
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum
ventilation rate that is greater than the required ventilation rate
for maximum occupancy. A proportional-anticipato U strategy
will cause the fresh air supplied to increase as the room CO2
level increases even though the CO2 set point has not been
reached. By the time the CO 2 level roaches the set point, the
damper will be at maximum ventilation and should maintain
the set point.
In order to have the CO 2 sensor control the economizer
damper in this manner, fil.'stdetermine the damper voltage output for minimum or base ventilation. Base ventilation is the
ventilation required to remove contmninants during unoccupied periods. The following equation may be used to determine
the percent of outside-air entering the building for a given
damper position. For best results there should be at least a
10 degree difference in outside and return-air temperatures.
the
using the
T o = Outdoor-Air Temperature
OA = Percent of Outdoor Air
T R = Return-Air Temperature
RA = Percent of Return Air
T M = Mixed-Air
Temperature
As an example, if local codes require 10% outdoor
during occupied conditions, outdoor-air temperature
60 E and return-air temperature is 75 E
(60 x .10) + (75 x .90) =73.5
_dr
is
F
2.
Disconnect
TI.
the supply air sensor
3.
Ensure that
terminals P
used, make
Fig. 32 and
turned fully
Connect 24
the factory-installed jumper is in place across
and PI. If remote damper positioning is being
sure that the terminals are wired according to
that the minimum position potentiometer
is
clockwise.
vac across terminals TR and TRI.
4.
5.
from terminals
T and
OA
(To x l-Tiff)
To = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
Carelhlly adjust the minimum position potentiometer
until the measured supply air temperature matches the
calculated value.
TM = Mixed-Air Temperature
Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position.
The same equation can be used to deterlnine the occupied or
maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate
of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm per person). Use Fig. 43
to determine the maximum setting of the CO 2 sensol: For example, a 1100 ppm set point relates to a 15 cfm per person design. Use the 1100 ppm curve on Fig. 43 to find the point when
the CO2 sensor output will be 6.7 volts. Line up the point on the
graph with the left side of the chart to determine that the range
configuration for the CO 2 sensor should be 1800 ppm. The
6. Reconnect the supply-air sensor to terminals T and Tl.
Remote control of the EconoMiSer IV damper is desirable
when requiring
additiomfl
tempormy
ventilation.
If a
field-supplied remote potentiometer (Honeywell part number
$963B1128)
is wired to the EconoMiSer IV controllek the
minimum position of the damper can be controlled from a remote location.
To control the minimum damper
the factory-installed jumper on the
EconoMiSer IV controllel: Wire the
ter to the P and PI terminals on the
See Fig. 42.
RA
+ (TR x l-Tiff) = TM
position remotely, remove
P and PI terminals on the
field-supplied potentiomeEconoMi$er IV controller.
24
EconoMiSer
IV controller
will outputthe6.7voltsfiomthe
COesensor
totheactuator
whentheCO2concentration
inthe
space
isat1100ppm.TheDCVsetpointmaybeleftat2volts
sincethe CO2 sensorvoltagewill be ignoredby the
EconoMiSer
IV controller
untilitrisesabove
the3.6voltsettingoftheminimum
position
potentiometer
Oncethefullyoccupied
dmnper
position
hasbeendetermined,
setfilemaximum
damper
demand
controlventilation
potentiometer
tothisposition.
Donotsettothemaximum
positionasthiscanresult
inover-ventihttion
tothespace
andpotentialhigh-humidity
levels.
If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification
option should be considered.
Step 9 -- Adjust Evaporator-Fan
Speed -- Adjust evaporator-fan speed to meet jobsite conditions. Tables 7A
and 7B show fan rpm at motor pulley settings for standard and
_flternate motors. See Table 8 and Fig. 44 for accessory and option static pressure diops. See Tables 9A and 9B for evaporator
fan motor performance. Refer to Tables 10-23 to determine fan
speed settings. Fan motor pulleys are factory set for speed
shown in Table 1.
CO__, Sensor Configuration
-- The CO e sensor has preset
standard voltage settings that can be selected anytime after the
sensor is powered up. See Table 6.
NOTE: Befole adjusting fan speed, make sure the new fan
speed will provide an acceptable air temperature rise range on
heating as shown in Table 1.
To change fan speed:
1. Shut offunit power supply.
2. Ix_osen belt by loosening fan motor mounting nuts. See
Fig. 45 and 46.
3. Ix_osen movable pulley flange setscrew (see Fig. 47).
4. Screw movable flange toward fixed flange to increase fan
speed and away from fixed flange to decrease fan speed.
Increasing fan speed increases load on motol: Do not exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
lull turn of pulley flange.)
To align fan and motor pulleys:
1. Ix_osen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make anguhu" alignment by loosening motor from
mounting plate.
To adjust belt tension:
1. Ix_osen fan motor mounting nuts.
2. Si'..e 008 -- Slide motor mounting plate away from fan
scroll for proper belt tension (l/2-in. deflection with one
linger) and tighten mounting nuts (see Fig. 45).
Sizes 009-014 -- Slide motor mounting plate downward
to tighten belt tension. Secure motor mounting plate nuts.
See Fig. 46.
3. Adjust bolt and nut on mounting plate to secure motor in
fixed position.
Use setting 1 or 2 for Carrier equipment. See Table 6.
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2.
Press Mode twice. The STDSET
3.
4.
Use the Up/Down button to select the preset numbel: See
Table 6.
Press Enter to lock in the selection.
Menu will appem:
5.
Pleas Mode to exit and resume norm_d operation.
The custom settings of the CO e sensor can be changed anytime after the sensor is energized. Follow the steps below to
change the non-stan&_rd settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2.
3.
4.
5.
6.
Press Mode twice. The STDSET Menu will appem:
Use the Up/Down button to toggle to the NONSTD menu
and press Entel:
Use the Up/Down button to toggle through each of the
nine variables, stinting with Altitude, until the desired setting is reached.
Press Mode to move through the variables.
Press Enter to lock in the selection,
continue to the next v;uiable.
then press Mode to
Dehumidification
of Fresh Air with DCV Control -- Information from ASHRAE indicates that the largest humidity load
on any zone is the fresh air introduced. For some applications,
a device such as a 62AQ energy recovery unit is added to reduce the moisture content of the fresh air being brought into the
building when the enthalpy is high. [n most cases, the norln_fl
heating and cooling processes are morn than adequate to remove the humidity loads for most commerci_fl applications.
Table
SETTING
EQUIPMENT
OUTPUT
6
--
CO
2
Sensor
VENTILATION
RATE
(cfm/Person)
1
2
3
4
7
Health
9
Parking/Air
Intakes/
Loading Docks
& Safety
1000
5O
Proportional
Any
0-2000
1000
5O
Exponential
Any
0-10V
4-20 mA
0-2000
1100
5O
15
0-10V
4-20 mA
0-1100
1100
5O
Proportional
20
0-10V
4-20 mA
0- 900
900
5O
Exponential
15
0-10V
4-20 mA
0-1100
1100
5O
2O
0-10V
4-20 mA
0- 900
900
5O
Proportional
0-10V
4-20 mA
0-9999
5000
5OO
Proportional
0-10V
4-20 mA
0-2000
700
5O
LEGEND
ppm
--
RELAY
HYSTERESIS
(ppm)
0-2000
Exponential
8
OPTIONAL
RELAY SETPOINT
(ppm)
2-10V
7-20 mA
Economizer
6
002
CONTROLRANGE
(ppm)
0-10V
4-20 mA
Proportional
5
ANALOG
OUTPUT
Settings
Any
Proportional
Interface w/Standard
Building Control System
Standard
Parts Per Million
25
0.35
0.3
0.25 -
(_5
0.2
7;
Q0.15
IJJ
C3
0.1
•
0,05
7.5 ton
"-X"
0
0
_1
_
;
1000
2000
3000
_
8,5, 10 & 12,5 ton
"i
4000
5000
6000
CFM
Fig. 44 -- Humidi-MiZer
TM
Adaptive Dehumidification
System Static Pressure Drop (in. wg)
_::_
PULLEYS
ST%AIGHT EDGE MUST
MOVABLE
MOTOR AND FAN
_=====L_
SHAHS
_/_.._1
MUS[
BE
:3_ ARALLEL
MOTOR MOUNTING
PLATE NUTS
SETSCREWS'_
FIXED
FLANGE
i
I
Fig. 45 -- Typical Belt-Drive Motor Mounting
for Size 008
_
Fig. 47 -- Evaporator-Fan
MOTOR
MOUNTING
PLATE NUTS
(HIDDEN)
Fig. 46 -- Typical Belt-Drive Motor Mounting
for Sizes 009-014
26
SINGLE-GROOVE
Pulley Adjustment
Table 7A -- Fan Rpm at Motor Pulley Setting (Standard
Motor)*
MOTOR PULLEY TURNS OPEN
UNIT 48HJ
0
008,009
012
1085
1080
014
1130
*Approximatefan
1_
1060
1
1035
11_
1010
1060
1035
1015
1112
1087
1062
2
985
21_
960
3
935
31_
910
4
890
41_
865
5
840
51_
--
6
--
990
970
950
925
905
880
860
--
--
1037
1212
987
962
937
912
887
962
830
rpm shown.
Table 7B -- Fan Rpm at Motor Pulley Se_ing (High-Static
Motor)*
MOTOR PULLEY TURNS OPEN
UNIT 48HJ
0
008
1080
1_
1025
1
1007
11_
988
2
970
21_
952
3
933
31_
915
4
897
41_
878
5
860
51_
--
6
--
009
012
1080
1130
1025
1112
1007
1087
988
1062
970
1037
952
1212
933
987
915
962
897
937
878
912
860
887
-962
-830
*Approximatefan
rpm shown.
Table 8 -- Accessory/FlOP
EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)
COMPONENT
Vertical EconoMi$er
IV and EconoMi$er2
Horizontal EconoMi$er
6250__
IV and EconoMi$er2
LEGEND
FlOP -- Factory-Installed
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should be used in conjunction with the Fan Performance tables to determine indoor
blower rpm and watts.
Option
Table 9A -- Evaporator-Fan
Motor Performance -- Standard
UNIT
48HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
008,009
Three
2.90
2615
012
014
Three
Three
3.70
UNIT VOLTAGE
MAXIMUM
AMP DRAW
208/230
8.6
48O
3.9
575
3.9
208/230
12.2
48O
5.5
575
208/230
17.3
3775
440O
5.25
Motor
5.5
48O
8.5
575
8.5
LEGEND
Bhp -- Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of
the motors can be utilized with confidence, Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 9B -- Evaporator-Fan
Motor Performance -- High-Static Motors
UNIT
48HJ
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
008,009
Three
4.20
3775
012
Three
5.25
UNIT VOLTAGE
MAXIMUM
AMP DRAW
208/230
12.2
46O
5.5
575
208/230
17.3
46O
8.5
575
8.5
44OO
LEGEND
Bhp -- Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of
the motors can be utilized with confidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
27
5.5
Table 10 -- Fan Performance 48HJ008 -- Vertical Discharge Units; Standard
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
0.2
Rpm
513
521
535
551
558
566
582
597
613
629
645
662
678
694
711
727
744
752
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Bhp
0.54
0.57
0.63
0.69
0.72
0.76
0.83
0.90
0.98
1.07
1.16
1.26
1.36
1.47
1.59
1.71
1.84
1.91
0.4
Watts
505
531
584
642
673
705
771
842
918
999
1085
1176
1272
1374
1482
1596
1716
1778
1.2
Rpm
839
844
854
865
870
875
886
897
908
920
931
943
-------
Bhp
1.86
1.90
1.99
2.08
2.13
2.18
2.28
2.39
2.50
2.62
2.75
2.88
-------
Rpm
595
601
615
628
635
642
656
670
684
699
713
728
743
758
773
789
804
812
Bhp
0.76
0.79
0.86
0.93
0.97
1.00
1.08
1.16
1.25
1.35
1.45
1.55
1.66
1.78
1.90
2.03
2.17
2.24
1.4
Watts
1735
1773
1855
1940
1985
2031
2126
2227
2333
2443
2560
2682
Rpm
Bhp
889
2.18
893
2.22
903
2.32
913
2.41
918
2.46
923
2.51
934
2.62
944
2.73
955
2.85
............
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
713
741
802
866
900
935
1008
1086
1169
1256
1349
1448
1551
1660
1775
1896
2023
2089
Rpm
665
671
684
696
702
709
721
734
748
761
775
788
802
816
831
845
860
867
---
Watts
940
972
1038
1109
1146
1183
1263
1347
1436
1530
1630
1734
1845
1961
2082
2210
2343
2413
Rpm
728
734
745
757
763
769
781
793
805
818
831
844
857
870
884
897
911
......
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
2032
2073
2159
2249
2296
2344
2445
2550
2661
Rpm
935
940
950
959
964
969
.........
.........
.........
LEGEND
Bhp
Watts
Bhp
1.01
1.04
1.11
1.19
1.23
1.27
1.35
1.44
1.54
1.64
1.75
1.86
1.98
2.10
2.23
2.37
2.51
2.59
Bhp
2.52
2.56
2.66
2.76
2.81
2.87
Watts
2345
2389
2478
2573
2622
2673
Rpm
980
......
......
......
......
......
Motor (Belt Drive)*
0.8
Bhp
1.27
1.31
1.39
1.47
1.51
1.55
1.65
1.74
1.84
1.95
2.06
2.18
2.31
2.44
2.58
2.72
2.87
1.0
Watts
1187
1222
1293
1369
1409
1450
1535
1625
1720
1820
1925
2036
2152
2275
2402
2537
2677
Rpm
786
791
802
813
818
824
835
847
859
871
883
895
908
920
----
Bhp
1.56
1.60
1.68
1.77
1.81
1.86
1.95
2.06
2.16
2.28
2.40
2.52
2.65
2.79
----
Watts
2673
Rpm
--
Bhp
--
1.8
Bhp
2.87
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require fieldsupplied drive.
28
Watts
1453
1489
1566
1647
1689
1732
1823
1917
2019
2125
2235
2352
2475
2603
----
Watts
--
Table 11 -- Fan Performance 48HJ008 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
0.2
Rpm
513
521
535
551
558
566
582
597
613
629
645
662
678
694
711
727
744
752
Watts
505
531
584
642
673
705
771
842
918
999
1085
1176
1272
1374
1482
1596
1716
1778
Rpm
595
601
615
628
635
642
656
670
684
699
713
728
743
758
773
789
804
812
Bhp
0.76
0.79
0.86
0.93
0.97
1.00
1.08
1.16
1.25
1.35
1.45
1.55
1.66
1.78
1.90
2.03
2.17
2.24
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
713
741
802
866
900
935
1008
1086
1169
1256
1349
1448
1551
1660
1775
1896
2023
2089
Rpm
665
671
684
696
702
709
721
734
748
761
775
788
802
816
831
845
880
867
EXTERNAL
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Bhp
0.54
0.57
0.63
0.69
0.72
0.76
0.83
0.90
0.98
1.07
1.16
1.26
1.36
1.47
1.59
1.71
1.84
1.91
0.4
1.2
Rpm
839
844
854
865
870
875
886
897
908
920
931
943
955
967
980
992
1005
1011
Bhp
1.86
1.90
1.99
2.08
2.13
2.18
2.28
2.39
2.50
2.62
2.75
2.88
3.01
3.16
3.31
3.46
3.63
3.71
STATIC
1.4
Watts
1735
1773
1855
1940
1985
2031
2126
2227
2333
2443
2560
2682
2810
2945
3084
3230
3383
3462
Rpm
889
893
903
913
918
923
934
944
955
968
977
989
1000
1012
1024
1036
1048
1054
Bhp
2.18
2.22
2.32
2.41
2.46
2.51
2.62
2.73
2.85
2.98
3.11
3.25
3.39
3.54
3.69
3.86
4.03
4.11
Watts
2032
2073
2159
2249
2298
2344
2445
2550
2661
2777
2899
3026
3159
3299
3445
3596
3755
3836
Rpm
935
940
950
959
964
969
979
989
1000
1010
1021
1032
1043
1055
1066
.........
.........
.........
LEGEND
Bhp
-Watts --
Bhp
1.01
1.04
1.11
1.19
1.23
1.27
1.35
1.44
1.54
1.64
1.75
1.86
1.98
2.10
2.23
2.37
2.51
2.59
Watts
940
972
1038
1109
1146
1183
1263
1347
1436
1530
1630
1734
1845
1961
2082
2210
2343
2413
PRESSURE(in.
1,6
Bhp
2.52
2.58
2.68
2.78
2.81
2.87
2.98
3.10
3.22
3.35
3.49
3.63
3.78
3.93
4.09
Watts
2345
2389
2478
2573
2622
2673
2777
2888
3003
3123
3250
3383
3521
3667
3817
Rpm
728
734
745
757
763
769
781
793
805
818
831
844
857
870
884
897
911
918
0.8
Bhp
1.27
1.31
1.39
1.47
1.51
1.55
1.65
1.74
1.84
1.95
2.06
2.18
2.31
2.44
2.58
2.72
2.87
2.95
1.0
Watts
1187
1222
1293
1369
1409
1450
1535
1625
1720
1820
1925
2036
2152
2275
2402
2537
2677
2750
Rpm
786
791
802
813
818
824
835
847
859
871
883
695
908
920
933
946
959
966
Bhp
1.56
1.60
1.68
1.77
1.81
1.86
1.95
2.06
2.16
2.28
2.40
2.52
2.65
2.79
2.93
3.09
3.24
3.32
Watts
2673
2718
2812
2911
2962
3014
3123
3238
3358
3484
3615
3752
3896
Rpm
1022
1027
1035
1044
1049
1054
1063
1073
1083
1093
----
Bhp
3.23
3.28
3.39
3.50
3.55
3.61
3.74
3.86
4.00
4.14
----
wg)
1,8
Rpm
980
984
993
1003
1008
1012
1022
1032
1042
1052
1063
1074
1084
......
......
Bhp
2.87
2.91
3.02
3.12
3.18
3.23
3.35
3.47
3.60
3.74
3.88
4.02
4.18
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
29
Watts
1453
1489
1566
1647
1689
1732
1823
1917
2019
2125
2235
2352
2475
2603
2737
2877
3023
3100
Watts
3015
3062
3159
3261
3315
3370
3483
3601
3725
3856
----
Table 12 -- Fan Performance 48HJ009 -- Vertical Discharge Units; Standard
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
0.2
Rpm
541
556
571
586
601
616
632
648
663
679
695
711
728
744
760
777
793
810
826
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
Bhp
0.50
0.55
0.60
0.66
0.72
0.79
0.85
0.93
1.00
1.09
1.17
1.26
1.36
1.46
1.57
1.68
1.79
1.92
2.04
0.4
Watts
467
513
562
615
672
732
796
864
936
1012
1092
1177
1266
1361
1460
1563
1672
1786
1906
1.2
Rpm
900
907
914
922
931
939
948
957
967
977
987
998
1008
1019
1031
Bhp
1.38
1.46
1.53
1.61
1.70
1.79
1.88
1.98
2.08
2.19
2.30
2.41
2.54
2.66
2.79
Rpm
624
637
650
663
676
689
703
717
731
745
760
774
789
804
819
834
850
865
880
Bhp
0.66
0.71
0.77
0.83
0.90
0.97
1.04
1.12
1.20
1.29
1.38
1.48
1.58
1.69
1.80
1.91
2.04
2.16
2.30
1.4
Watts
1289
1357
1429
1505
1584
1667
1753
1844
1939
2039
2143
2251
2364
2482
2605
Rpm
Bhp
959
1.58
965
1.66
972
1.74
979
1.83
986
1.92
994
2.01
1002
2.11
1011
2.21
1020
2.32
1029
2.43
1038
2.54
1048
2.66
1058
2.79
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
614
665
720
777
839
904
972
1045
1122
1203
1288
1379
1473
1572
1676
1785
1899
2018
2142
Rpm
701
711
722
734
745
757
769
782
795
808
821
834
848
861
875
889
904
918
932
---
Watts
771
827
885
948
1014
1083
1157
1235
1316
1402
1492
1587
1686
1790
1899
2012
2132
2255
2385
Rpm
771
781
790
800
811
821
832
843
855
867
879
891
904
918
929
942
956
969
983
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
1476
1548
1824
1704
1787
1874
1965
2060
2160
2264
2372
2485
2602
Rpm
1015
1021
1027
1033
1040
1047
1054
1062
1070
1079
1088
.........
.........
LEGEND
Bhp
Watts
Bhp
0.83
0.89
0.95
1.02
1.09
1.16
1.24
1.32
1.41
1.50
1.60
1.70
1.81
1.92
2.04
2.16
2.29
2.42
2.56
Bhp
1.79
1.87
1.96
2.05
2.14
2.24
2.34
2.45
2.56
2.67
2.80
Watts
1669
1745
1825
1909
1996
2087
2183
2283
2386
2494
2607
Rpm
1069
1074
1079
1085
1091
1098
1105
1112
1119
......
......
Motor (Belt Drive)*
0.8
Bhp
1.00
1.07
1.14
1.21
1.28
1.36
1.45
1.53
1.63
1.72
1.83
1.93
2.04
2.16
2.28
2.41
2.54
2.68
2.82
1.0
Watts
936
996
1059
1126
1197
1271
1349
1431
1517
1608
1703
1802
1908
2015
2128
2247
2371
2499
2633
Rpm
837
845
854
863
872
882
892
902
912
923
934
945
957
969
981
993
1006
---
Bhp
1.19
1.26
1.33
1.41
1.49
1.57
1.66
1.75
1.85
1.95
2.06
2.17
2.29
2.41
2.53
2.67
2.80
---
Watts
1868
1948
2032
2120
2211
2307
2406
2510
2618
Rpm
1121
1125
1130
1135
1141
1147
1153
---
Bhp
2.22
2.31
2.41
2.51
2.61
2.71
2.83
---
1.8
Bhp
2.00
2.09
2.18
2.27
2.37
2.47
2.58
2.69
2.81
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require fieldsupplied drive.
3O
Watts
1109
1173
1241
1312
1387
1465
1548
1635
1725
1820
1920
2024
2132
2246
2364
2487
2615
---
Watts
2073
2158
2245
2337
2432
2532
2635
---
Table 13 -- Fan Performance 48HJ009 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
0.2
Rpm
541
556
571
586
601
616
632
648
663
679
695
711
728
744
760
777
793
810
826
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
Bhp
0.50
0.55
0.60
0.66
0.72
0.79
0.85
0.93
1.00
1.09
1.17
1.26
1.36
1.46
1.57
1.68
1.79
1.92
2.04
0.4
Watts
467
513
562
615
672
732
796
864
936
1012
1092
1177
1266
1361
1460
1563
1672
1786
1906
Rpm
624
637
650
663
676
689
703
717
731
745
760
774
789
804
819
834
850
865
880
1.2
Rpm
900
907
914
922
931
939
948
957
967
977
987
998
1008
1019
1031
1042
1054
1066
1078
Bhp
1.38
1.46
1.53
1.61
1.70
1.79
1.88
1.98
2.08
2.19
2.30
2.41
2.54
2.66
2.79
2.93
3.07
3.22
3.38
Bhp
0.66
0.71
0.77
0.83
0.90
0.97
1.04
1.12
1.20
1.29
1.38
1.48
1.58
1.69
1.80
1.91
2.04
2.16
2.30
1,4
Watts
1289
1357
1429
1505
1584
1667
1753
1844
1939
2039
2143
2251
2364
2482
2605
2733
2866
3004
3148
Rpm
959
965
972
979
986
994
1002
1011
1020
1029
1038
1048
1058
1068
1079
1090
1101
1112
1123
Bhp
1.58
1.66
1.74
1.83
1.92
2.01
2.11
2.21
2.32
2.43
2.54
2.66
2.79
2.92
3.06
3.20
3.35
3.50
3.66
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
614
665
720
777
839
904
972
1045
1122
1203
1288
1379
1473
1572
1676
1785
1899
2018
2142
Rpm
701
711
722
734
745
757
769
782
795
808
821
834
848
861
875
889
904
918
932
Watts
771
827
885
948
1014
1083
1157
1235
1316
1402
1492
1587
1686
1790
1899
2012
2132
2255
2385
Rpm
771
781
790
800
811
821
832
843
855
867
879
891
904
916
929
942
956
969
983
EXTERNAL STATIC PRESSURE (in. wg)
1,6
Watts
1476
1548
1624
1704
1787
1874
1965
2060
2160
2264
2372
2485
2602
2725
2852
2984
3122
3264
3413
Rpm
1015
1021
1027
1033
1040
1047
1054
1062
1070
1079
1088
1097
1106
1116
1126
1136
1146
1157
1167
LEGEND
Bhp
-Watts --
Bhp
0.83
0.89
0.95
1.02
1.09
1.16
1.24
1.32
1.41
1.50
1.60
1.70
1.81
1.92
2.04
2.16
2.29
2.42
2.56
Bhp
1.79
1.87
1.96
2.05
2.14
2.24
2.34
2.45
2.56
2.67
2.80
2.92
3.05
3.19
3.33
3.48
3.63
3.79
3.95
Watts
1669
1745
1825
1909
1996
2087
2183
2283
2386
2494
2607
2724
2846
2972
3104
3241
3383
3530
3683
Rpm
1069
1074
1079
1085
1091
1098
1105
1112
1119
1127
1135
1144
1152
1162
1171
1180
1190
1200
......
0.8
Bhp
1.00
1.07
1.14
1.21
1.28
1.36
1.45
1.53
1.63
1.72
1.83
1.93
2.04
2.16
2.28
2.41
2.54
2.68
2.82
1.0
Watts
936
996
1059
1126
1197
1271
1349
1431
1517
1608
1703
1802
1906
2015
2128
2247
2371
2499
2633
Rpm
837
845
854
863
872
882
892
902
912
923
934
945
957
969
981
993
1006
1018
1031
Bhp
1.19
1.26
1.33
1.41
1.49
1.57
1.66
1.75
1.85
1.95
2.06
2.17
2.29
2.41
2.53
2.67
2.80
2.95
3.10
Watts
1868
1948
2032
2120
2211
2307
2406
2510
2618
2730
2847
2968
3094
3226
3362
3503
3649
3801
Rpm
1121
1125
1130
1135
1141
1147
1153
1160
1167
1174
1181
1189
1198
1206
1215
1224
1233
--
Bhp
2.22
2.31
2.41
2.51
2.61
2.71
2.83
2.94
3.06
3.19
3.32
3.45
3.59
3.74
3.89
4.04
4.20
--
1,8
Bhp
2.00
2.09
2.18
2.27
2.37
2.47
2.58
2.69
2.81
2.93
3.05
3.18
3.32
3.46
3.61
3.76
3.91
4.08
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
3!
Watts
1109
1173
1241
1312
1387
1465
1548
1635
1725
1820
1920
2024
2132
2246
2364
2487
2615
2748
2888
Watts
2073
2158
2245
2337
2432
2532
2635
2743
2855
2971
3092
3218
3348
3484
3624
3770
3921
--
Table 14 -- Fan Performance 48HJ012 -- Vertical Discharge Units; Standard
AIRFLOW
(Cfm)
3O00
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
0.2
Rpm
616
632
648
663
679
695
711
728
744
760
777
793
810
826
843
860
878
893
910
927
944
AIRFLOW
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Bhp
0.79
0.85
0.93
1.00
1.09
1.17
1.26
1.36
1.46
1.57
1.68
1.79
1.92
2.04
2.18
2.32
2.46
2.62
2.77
2.94
3.11
0.4
Watts
732
796
864
936
1012
1092
1177
1266
1361
1460
1563
1672
1786
1906
2031
2161
2297
2439
2587
2741
2901
1.2
Rpm
939
948
957
967
977
987
998
1008
1019
1031
1042
1054
1066
1078
1090
1103
Bhp
1.79
1.88
1.98
2.08
2.19
2.30
2.41
2.54
2.66
2.79
2.93
3.07
3.22
3.38
3.54
3.70
Rpm
689
703
717
731
745
760
774
789
804
819
834
850
865
880
898
912
927
943
959
975
991
Bhp
0.97
1.04
1.12
1.20
1.29
1.38
1.48
1.58
1.69
1.80
1.91
2.04
2.16
2.30
2.44
2.58
2.73
2.89
3.06
3,23
3.40
1.4
Watts
1667
1753
1844
1939
2039
2143
2251
2364
2482
2605
2733
2866
3004
3148
3297
3451
Rpm
Bhp
994
2.01
1002
2.11
1011
2.21
1020
2.32
1029
2.43
1038
2.54
1048
2.66
1058
2.79
1068
2.92
1079
3.06
1090
3.20
1101
3.35
1112
3.50
1123
3.66
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
904
972
1045
1122
1203
1288
1379
1473
1572
1676
1785
1899
2018
2142
2272
2408
2549
2696
2849
3008
3173
Rpm
757
769
782
795
808
821
834
848
861
875
889
904
918
932
947
982
977
992
1007
1022
1037
---
Watts
1083
1157
1235
1316
1402
1492
1587
1686
1790
1899
2012
2132
2255
2385
2520
2660
2807
2958
3116
3280
3451
Rpm
821
832
843
855
867
879
891
904
918
929
942
956
969
983
998
1010
1024
1038
1053
......
......
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
1874
1965
2060
2160
2264
2372
2485
2602
2725
2852
2984
3122
3264
3413
Rpm
1047
1054
1062
1070
1079
1088
1097
1106
1116
1126
1136
1146
.........
.........
LEGEND
Bhp
Watts
Bhp
1.16
1.24
1.32
1.41
1.50
1.60
1.70
1.81
1.92
2.04
2.16
2.29
2.42
2.56
2.70
2.85
3.01
3.17
3.34
3,52
3.70
Bhp
2.24
2.34
2.45
2.56
2.87
2.80
2.92
3.05
3.19
3.33
3.48
3.63
Watts
2087
2183
2283
2386
2494
2607
2724
2846
2972
3104
3241
3383
Rpm
1098
1105
1112
1119
1127
1135
1144
1152
1162
1171
......
......
Motor (Belt Drive)*
0.8
Bhp
1.36
1.45
1.53
1.63
1.72
1.83
1.93
2.04
2.16
2.28
2.41
2.54
2.68
2.82
2.97
3.13
3.29
3.46
3.63
1.0
Watts
1271
1349
1431
1517
1608
1703
1802
1908
2015
2128
2247
2371
2499
2633
2773
2918
3070
3226
3390
Rpm
882
892
902
912
923
934
945
957
989
981
993
1006
1018
1031
1044
1057
1070
---
Bhp
1.57
1.66
1.75
1.85
1.95
2.06
2.17
2.29
2.41
2.53
2.67
2.80
2.95
3.10
3.25
3.41
3.58
---
Watts
2307
2406
2510
2618
2730
2847
2968
3094
3226
3362
Rpm
1147
1153
1160
1167
1174
1181
1189
1198
---
Bhp
2.71
2.83
2.94
3.06
3.19
3.32
3.45
3.59
---
1.8
Bhp
2.47
2.58
2.69
2.81
2.93
3.05
3.18
3.32
3.46
3.61
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
32
Watts
1465
1548
1635
1725
1820
1920
2024
2132
2246
2364
2487
2615
2748
2888
3032
3182
3338
---
Watts
2532
2635
2743
2855
2971
3092
3218
3348
---
Table 15 -- Fan Performance 48HJ012 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
3O0O
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
0.2
Rpm
616
632
648
663
679
695
711
728
744
760
777
793
810
826
843
860
876
893
910
927
944
AIRFLOW
(Cfm)
300O
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Bhp
0.79
0.85
0.93
1.00
1.09
1.17
1.26
1.36
1.46
1.57
1.68
1.79
1.92
2.04
2.18
2.32
2.46
2.62
2.77
2.94
3.11
0.4
Watts
732
796
864
936
1012
1092
1177
1266
1361
1460
1563
1672
1786
1906
2031
2161
2297
2439
2587
2741
2901
Rpm
689
703
717
731
745
760
774
789
804
819
834
850
865
880
896
912
927
943
959
975
991
1.2
Rpm
939
948
957
967
977
987
998
1008
1019
1031
1042
1054
1066
1078
1090
1103
1115
1128
1141
1154
1167
Bhp
1.79
1.88
1.98
2.08
2.19
2.30
2.41
2.54
2.66
2.79
2.93
3.07
3.22
3.38
3.54
3.70
3.87
4.05
4.24
4.43
4.63
Bhp
0.97
1.04
1.12
1.20
1.29
1.38
1.48
1.58
1.69
1.80
1.91
2.04
2.16
2.30
2.44
2.58
2.73
2.89
3.06
3.23
3.40
1.4
Watts
1667
1753
1844
1939
2039
2143
2251
2364
2482
2605
2733
2866
3004
3148
3297
3451
3612
3778
3951
4130
4314
Rpm
994
1002
1011
1020
1029
1038
1048
1058
1068
1079
1090
1101
1112
1123
1135
1147
1159
1171
1183
1196
1209
Bhp
2.01
2.11
2.21
2.32
2.43
2.54
2.66
2.79
2.92
3.06
3.20
3.35
3.50
3.66
3.82
4.00
4.17
4.36
4.55
4.74
4.95
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
904
972
1045
1122
1203
1288
1379
1473
1572
1676
1785
1899
2018
2142
2272
2408
2549
2696
2849
3008
3173
Rpm
757
769
782
795
808
821
834
848
861
875
889
904
918
932
947
962
977
992
1007
1022
1037
Watts
1083
1157
1235
1316
1402
1492
1587
1686
1790
1899
2012
2132
2255
2385
2520
2660
2807
2958
3116
3280
3451
Rpm
821
832
843
855
867
879
891
904
916
929
942
956
969
983
996
1010
1024
1038
1053
1067
1082
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
1874
1965
2060
2160
2264
2372
2485
2602
2725
2852
2984
3122
3264
3413
3566
3726
3891
4062
4239
4422
4611
Rpm
1047
1054
1062
1070
1079
1088
1097
1106
1116
1126
1136
1146
1157
1167
1179
1190
1201
1213
1225
1237
.........
LEGEND
Bhp
-Watts --
Bhp
1.16
1.24
1.32
1.41
1.50
1.60
1.70
1.81
1.92
2.04
2.16
2.29
2.42
2.56
2.70
2.85
3.01
3.17
3.34
3.52
3.70
Bhp
2.24
2.34
2.45
2.56
2.67
2.80
2.92
3.05
3.19
3.33
3.48
3.63
3.79
3.95
4.12
4.29
4.48
4.67
4.86
5.06
Watts
2087
2183
2283
2386
2494
2607
2724
2846
2972
3104
3241
3383
3530
3683
3841
4005
4175
4350
4532
4720
Rpm
1098
1105
1112
1119
1127
1135
1144
1152
1162
1171
1180
1190
1200
1210
1221
1232
1243
1254
1265
......
0.8
Bhp
1.36
1.45
1.53
1.63
1.72
1.83
1.93
2.04
2.16
2.28
2.41
2.54
2.68
2.82
2.97
3.13
3.29
3.46
3.63
3.82
4.00
1.0
Watts
1271
1349
1431
1517
1608
1703
1802
1906
2015
2128
2247
2371
2499
2633
2773
2918
3070
3226
3390
3558
3733
Rpm
882
892
902
912
923
934
945
957
969
981
993
1006
1018
1031
1044
1057
1070
1084
1098
1111
1125
Bhp
1.57
1.66
1.75
1.85
1.95
2.06
2.17
2.29
2.41
2.53
2.67
2.80
2.95
3.10
3.25
3.41
3.58
3.75
3.93
4.12
4.31
Watts
2307
2406
2510
2618
2730
2847
2968
3094
3226
3362
3503
3649
3801
3958
4121
4289
4464
4644
4830
Rpm
1147
1153
1160
1167
1174
1181
1189
1198
1206
1215
1224
1233
1243
1252
1262
1273
1283
---
Bhp
2.71
2.83
2.94
3.06
3.19
3.32
3.45
3.59
3.74
3.89
4.04
4.20
4.37
4.54
4.72
4.91
5.10
---
1.8
Bhp
2.47
2.58
2.69
2.81
2.93
3.05
3.18
3.32
3.46
3.61
3.76
3.91
4.08
4.24
4.42
4.60
4.79
4.98
5.18
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require fieldsupplied drive.
.3.3
Watts
1465
1548
1635
1725
1820
1920
2024
2132
2246
2364
2487
2615
2748
2888
3032
3182
3338
3500
3668
3841
4021
Watts
2532
2635
2743
2855
2971
3092
3218
3348
3484
3624
3770
3921
4077
4238
4405
4578
4757
---
Table 16 -- Fan Performance 48HJ014 -- Vertical Discharge Units; Standard
AIRFLOW
(Cfm)
37OO
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
0.2
Rpm
728
744
760
777
793
810
826
843
860
876
893
910
927
944
961
978
995
1012
1029
1046
1063
1080
1098
1115
AIRFLOW
(Cfm)
37O0
3800
3g00
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
Bhp
1.36
1.46
1.57
1.68
1.79
1.92
2.04
2.18
2.32
2.46
2.62
2.77
2.94
3.11
3.29
3.48
3.67
3.87
4.07
4.29
4.51
4.74
4.98
5.22
0.4
Watts
1266
1361
1460
1563
1672
1786
1906
2031
2161
2297
2439
2587
2741
2901
3068
3241
3420
3606
3799
3999
4207
4420
4642
4872
Rpm
Bhp
789
1.58
804
1.69
819
1.80
834
1.91
850
2.04
865
2.16
880
2.30
896
2.44
912
2.58
927
2.73
943
2.89
959
3.06
975
3.23
991
3.40
1007
3.59
1024
3.78
1040
3.98
1056
4.18
1073
4.39
1089
4.61
1105
4.84
1122
5.08
............
............
1,2
Rpm
1008
1019
1031
1042
1054
1068
1078
1090
1103
1115
1128
1141
1154
1167
1181
1194
Bhp
2.54
2.68
2.79
2.93
3.07
3.22
3.38
3.54
3.70
3.87
4.05
4.24
4.43
4.63
4.83
5.04
1,4
Watts
2364
2482
2605
2733
2868
3004
3148
3297
3451
3612
3778
3951
4130
4314
4505
4703
Rpm
1058
1068
1079
1090
1101
1112
1123
1135
1147
1159
1171
1183
1196
1209
1221
--
Bhp
2.79
2.92
3.06
3.20
3.35
3.50
3.66
3.82
4.00
4.17
4.36
4.55
4.74
4.95
5.16
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
1473
1572
1676
1785
1899
2018
2142
2272
2408
2549
2696
2849
3008
3173
3345
3523
3707
3899
4097
4302
4515
4734
Rpm
848
861
875
889
904
918
932
947
962
977
992
1007
1022
1037
1053
1068
1084
1099
1115
1131
1146
.........
---
Watts
1686
1790
1899
2012
2132
2255
2385
2520
2660
2807
2958
3116
3280
3451
3627
3811
4000
4196
4400
4610
4827
Rpm
904
916
929
942
956
969
983
996
1010
1024
1038
1053
1067
1082
1096
1111
1126
1141
1156
......
......
EXTERNAL STATIC PRESSURE (in, wg)
1,6
Watts
2602
2725
2852
2984
3122
3264
3413
3566
3726
3891
4062
4239
4422
4611
4808
Rpm
1106
1116
1128
1136
1146
1157
1167
1179
1190
1201
1213
1225
1237
---
Bhp
3.05
3.19
3.33
3.48
3.63
3.79
3.95
4.12
4.29
4.48
4.67
4.86
5.06
---
Watts
2846
2972
3104
3241
3383
3530
3683
3841
4005
4175
4350
4532
4720
Rpm
1152
1162
1171
1180
1190
1200
1210
1221
1232
1243
1254
1265
--
0.8
Bhp
2.04
2.16
2.28
2.41
2.54
2.68
2.82
2.97
3.13
3.29
3.46
3.63
3.82
4.00
4.20
4.40
4.61
4.82
5.05
1.0
Watts
1906
2015
2128
2247
2371
2499
2633
2773
2918
3070
3226
3390
3558
3733
3915
4103
4298
4499
4707
Rpm
957
969
981
993
1006
1018
1031
1044
1057
1070
1084
1098
1111
1125
1139
1153
1168
1182
--
Bhp
2.29
2.41
2.53
2.67
2.80
2.95
3.10
3.25
3.41
3.58
3.75
3.93
4.12
4.31
4.51
4.72
4.93
5.15
--
Watts
3094
3226
3362
3503
3649
3801
3958
4121
4289
4464
4644
4830
Rpm
1198
1206
1215
1224
1233
1243
1252
1262
1273
1283
---
Bhp
3.59
3.74
3.89
4.04
4.20
4.37
4.54
4.72
4.91
5.10
---
1,8
Bhp
3.32
3.46
3.61
3.76
3.91
4.08
4.24
4.42
4.60
4.79
4.98
5.18
--
m
m
m
m
m
m
m
m
m
m
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 630 to 1130 rpm. All other rpms require fieldsupplied drive.
34
Watts
2132
2246
2364
2487
2615
2748
2888
3032
3182
3338
3500
3668
3841
4021
4208
4400
4600
4806
--
2,0
m
LEGEND
Bhp
Watts
Bhp
1.81
1.92
2.04
2.16
2.29
2.42
2.56
2.70
2.85
3.01
3.17
3.34
3.52
3.70
3.89
4.09
4.29
4.50
4.72
4.94
5.18
Motor (Belt Drive)*
Watts
3348
3484
3624
3770
3921
4077
4238
4405
4578
4757
Table 17 -- Fan Performance 48HJ008 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
0.2
Rpm
505
513
527
543
550
558
574
589
605
621
637
654
670
686
703
720
736
745
Watts
484
509
561
617
647
677
742
811
885
963
1046
1135
1228
1328
1433
1543
1660
1721
Rpm
586
592
605
618
625
632
645
659
673
688
702
717
732
747
762
777
793
801
Bhp
0.73
0.76
0.82
0.89
0.92
0.96
1.03
1.11
1.20
1.29
1.39
1.49
1.60
1.71
1.83
1.95
2.09
2.15
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
681
708
766
828
860
894
964
1039
1119
1204
1293
1388
1488
1593
1705
1822
1944
2008
Rpm
657
663
674
686
692
698
710
723
736
749
762
776
789
803
817
832
846
853
EXTERNAL
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Bhp
0.52
0.55
0.60
0.66
0.69
0.73
0.80
0.87
0.95
1.03
1.12
1.22
1.32
1.42
1.54
1.66
1.78
1.85
0.4
1.2
STATIC
1.4
Rpm
838
842
Bhp
1.81
1.84
Watts
1683
1719
Rpm
891
895
Bhp
2.12
2.17
Watts
1981
2019
851
860
865
869
879
889
899
910
921
932
943
1.92
2.01
2.05
2.10
2.19
2.29
2.40
2.51
2.63
2.75
2.88
1793
1873
1914
1957
2046
2140
2239
2343
2453
2569
2690
903
2.25
911
2.34
916
2.38
920
2.43
929
2.53
938
2.64
948
2.75
958
2.86
............
............
............
2097
2180
2223
2267
2360
2458
2561
2670
Rpm
941
944
952
960
964
968
976
.........
.........
.........
LEGEND
Bhp
Watts
---
Bhp
0.97
1.00
1.07
1.14
1.17
1.21
1.29
1.38
1.47
1.57
1.67
1.78
1.89
2.01
2.14
2.27
2.41
2.48
Watts
901
931
993
1060
1095
1131
1207
1287
1372
1463
1558
1658
1764
1876
1993
2116
2245
2312
PRESSURE
1,6
Bhp
2.46
2.51
Watts
2297
2336
2.59
2.68
2.73
2.78
2.88
2416
2502
2547
2593
2689
Rpm
722
727
738
748
754
759
770
782
794
806
818
831
843
856
870
883
896
903
0.8
Bhp
1.22
1.26
1.33
1.41
1.45
1.49
1.58
1.67
1.76
1.87
1.97
2.09
2.21
2.33
2.46
2.60
2.75
2.82
1.0
Watts
1142
1174
1241
1312
1349
1388
1469
1554
1644
1740
1840
1946
2057
2174
2297
2425
2560
2630
Rpm
782
787
796
806
811
816
826
837
848
859
871
882
894
907
919
----
Bhp
1.50
1.54
1.62
1.70
1.74
1.78
1.88
1.97
2.07
2.18
2.29
2.41
2.54
2.67
2.81
----
Watts
2629
2669
Rpm
---
Bhp
Watts
m
m
m
m
(in. wg)
1,8
Rpm
988
992
Bhp
2.82
2.86
2,0
......
......
......
......
......
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require fieldsupplied drive.
.3.5
Watts
1403
1437
1508
1583
1623
1664
1749
1839
1933
2033
2139
2249
2365
2488
2616
----
Table 18 -- Fan Performance 48HJ008 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
0.2
Rpm
505
513
527
543
550
558
574
589
605
621
637
654
670
686
703
720
736
745
Watts
484
509
561
617
647
677
742
811
885
963
1046
1135
1228
1328
1433
1543
1660
1721
Rpm
586
592
605
618
625
632
645
659
673
688
702
717
732
747
762
777
793
801
Bhp
0.73
0.76
0.82
0.89
0.92
0.96
1.03
1.11
1.20
1.29
1.39
1.49
1.60
1.71
1.83
1.95
2.09
2.15
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
681
708
766
828
860
894
964
1039
1119
1204
1293
1388
1488
1593
1705
1822
1944
2008
Rpm
657
663
674
686
692
698
710
723
736
749
762
776
789
803
817
832
846
853
EXTERNAL
AIRFLOW
(Cfm)
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Bhp
0.52
0.55
0.60
0.66
0.69
0.73
0.80
0.87
0.95
1.03
1.12
1.22
1.32
1.42
1.54
1.66
1.78
1.85
0.4
1.2
Rpm
838
842
851
860
865
869
879
889
899
910
921
932
943
954
966
978
990
996
Bhp
1.81
1.84
1.92
2.01
2.05
2.10
2.19
2.29
2.40
2.51
2.63
2.75
2.88
3.02
3.16
3.31
3.47
3.55
STATIC
1,4
Watts
1683
1719
1793
1873
1914
1957
2046
2140
2239
2343
2453
2569
2690
2816
2950
3088
3233
3308
Rpm
891
895
903
911
916
920
929
938
948
958
968
978
989
1000
1011
1022
1034
1040
Bhp
2.12
2.17
2.25
2.34
2.38
2.43
2.53
2.64
2.75
2.86
2.98
3.11
3.25
3.39
3.54
3.69
3.85
3.93
Watts
1981
2019
2097
2180
2223
2267
2360
2458
2561
2670
2783
2903
3029
3159
3297
3442
3591
3669
Rpm
941
944
952
960
964
968
976
985
994
1004
1013
1023
1033
1044
1054
1065
.........
.........
LEGEND
Bhp
Watts
---
Bhp
0.97
1.00
1.07
1.14
1.17
1.21
1.29
1.38
1.47
1.57
1.67
1.78
1.89
2.01
2.14
2.27
2.41
2.48
Watts
901
931
993
1060
1095
1131
1207
1287
1372
1463
1558
1658
1764
1876
1993
2116
2245
2312
PRESSURE
1.6
Bhp
2.46
2.51
2.59
2.68
2.73
2.78
2.88
2.99
3.11
3.23
3.35
3.49
3.63
3.77
3.92
4.08
Watts
2297
2336
2416
2502
2547
2593
2689
2791
2898
3011
3128
3252
3382
3518
3660
3808
Rpm
722
727
738
748
754
759
770
782
794
806
818
831
843
856
870
883
896
903
0.8
Bhp
1.22
1.26
1.33
1.41
1.45
1.49
1.58
1.67
1.76
1.87
1.97
2.09
2.21
2.33
2.46
2.60
2.75
2.82
1.0
Watts
1142
1174
1241
1312
1349
1388
1469
1554
1644
1740
1840
1946
2057
2174
2297
2425
2560
2630
Rpm
782
787
796
806
811
816
826
837
848
859
871
882
894
907
919
932
944
951
Bhp
1.50
1.54
1.62
1.70
1.74
1.78
1.88
1.97
2.07
2.18
2.29
2.41
2.54
2.67
2.81
2.95
3.10
3.18
Watts
2629
2669
2752
2842
2888
2935
3035
3140
3250
3366
3488
3616
3749
3889
Rpm
1033
1037
1043
1051
1054
1058
1066
1073
1082
1090
1099
----
Bhp
3.19
3.24
3.33
3.43
3.48
3.53
3.64
3.76
3.88
4.01
4.14
----
(in, wg)
1,8
Rpm
988
992
999
1006
1010
1014
1022
1030
1039
1048
1057
1066
1076
1086
......
......
Bhp
2.82
2.86
2.95
3.05
3.10
3.15
3.25
3.37
3.49
3.61
3.74
3.88
4.02
4.17
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
36
Watts
1403
1437
1508
1583
1623
1664
1749
1839
1933
2033
2139
2249
2365
2488
2616
2750
2889
2962
Watts
2976
3018
3104
3196
3243
3292
3395
3503
3616
3736
3861
----
Table 19 -- Fan Performance 48HJ009 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
0.2
Rpm
513
526
539
552
565
579
592
606
620
634
648
662
676
690
705
719
734
748
763
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
Bhp
0.45
0.50
0.54
0.59
0.64
0.70
0.76
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.45
1.55
1.66
1.76
0.4
Watts
423
463
505
551
599
651
706
764
825
890
958
1030
1106
1185
1269
1357
1449
1545
1646
1.2
Rpm
877
885
892
900
908
917
925
934
943
952
961
971
981
990
1000
1011
1021
Bhp
1.31
1.38
1.46
1.54
1.62
1.70
1.79
1.88
1.98
2.08
2.18
2.29
2.40
2.52
2.64
2.76
2.89
Rpm
603
614
625
637
648
660
672
684
696
709
721
734
747
760
773
786
799
813
826
Bhp
0.62
0.67
0.72
0.77
0.83
0.89
0.96
1.03
1.10
1.17
1.25
1.34
1.42
1.52
1.61
1.71
1.82
1.93
2.04
1,4
Watts
1222
1289
1359
1432
1508
1587
1670
1756
1845
1939
2035
2135
2240
2348
2459
2576
2697
Rpm
Bhp
933
1.49
940
1.57
948
1.65
955
1.74
963
1.82
970
1.91
979
2.01
987
2.10
995
2.21
1004
2.31
1013
2.42
1022
2.53
1031
2.65
1040
2.77
1050
2.90
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
576
621
670
721
775
832
893
957
1024
1095
1169
1246
1328
1414
1503
1597
1695
1797
1903
Rpm
682
692
702
712
722
732
743
754
765
777
788
800
811
823
835
848
860
872
885
---
Watts
732
783
837
894
954
1017
1083
1153
1225
1302
1381
1465
1552
1644
1739
1838
1942
2050
2162
Rpm
753
761
770
780
789
799
808
818
829
839
850
860
871
882
894
905
917
928
940
EXTERNAL STATIC PRESSURE (in. wg)
1,6
Watts
1392
1464
1540
1618
1699
1784
1872
1963
2057
2156
2258
2364
2473
2587
2705
Rpm
986
993
1000
1007
1014
1021
1029
1037
1045
1053
1062
1070
.........
.........
.........
LEGEND
Bhp
Watts
Bhp
0.78
0.84
0.90
0.96
1.02
1.09
1.16
1.24
1.31
1.40
1.48
1.57
1.66
1.76
1.86
1.97
2.08
2.20
2.32
Bhp
1.68
1.76
1.85
1.94
2.03
2.13
2.23
2.33
2.44
2.55
2.66
2.78
Watts
1565
1643
1723
1807
1893
1983
2076
2172
2272
2376
2483
2595
Rpm
1037
1043
1049
1056
1063
1070
1077
1085
1092
1100
......
......
0.8
Bhp
0.96
1.02
1.08
1.15
1.22
1.29
1.37
1.45
1.53
1.62
1.71
1.81
1.91
2.01
2.12
2.23
2.35
2.47
2.60
1.0
Watts
892
948
1008
1070
1136
1204
1276
1351
1429
1511
1597
1686
1779
1876
1977
2082
2192
2305
2423
Rpm
817
825
834
842
851
860
869
878
888
897
907
917
927
938
948
959
970
981
992
Bhp
1.13
1.20
1.27
1.34
1.42
1.50
1.58
1.66
1.75
1.85
1.95
2.05
2.15
2.26
2.38
2.50
2.62
2.75
2.88
Watts
1742
1824
1909
1998
2089
2185
2283
2384
2490
2599
Rpm
1085
1091
1097
1103
1110
1117
1123
1131
---
Bhp
2.06
2.15
2.25
2.35
2.45
2.56
2.67
2.79
---
1,8
Bhp
1.87
1.96
2.05
2.14
2.24
2.34
2.45
2.56
2.67
2.79
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require fieldsupplied drive.
37
Watts
1055
1117
1182
1250
1321
1395
1471
1552
1636
1723
1815
1909
2008
2111
2217
2328
2443
2562
2686
Watts
1921
2008
2099
2192
2289
2389
2492
2599
---
Table 20 -- Fan Performance 48HJ009 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
0.2
Rpm
513
526
539
552
565
579
592
606
620
634
648
662
676
690
705
719
734
748
763
AIRFLOW
(Cfm)
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
Bhp
0.45
0.50
0.54
0.59
0.64
0.70
0.76
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.45
1.55
1.66
1.76
0.4
Watts
423
463
505
551
599
651
706
764
825
890
958
1030
1106
1185
1269
1357
1449
1545
1646
Rpm
603
614
625
637
648
660
672
684
696
709
721
734
747
760
773
786
799
813
826
1,2
Rpm
877
885
892
900
908
917
925
934
943
952
961
971
981
990
lOOO
1011
1021
1031
1042
Bhp
1.31
1.38
1.46
1.54
1.62
1.70
1.79
1.88
1.98
2.08
2.18
2.29
2.40
2.52
2.64
2.76
2.89
3.03
3.16
Bhp
0.62
0.67
0.72
0.77
0.83
0.89
0.96
1.03
1.10
1.17
1.25
1.34
1.42
1.52
1.61
1.71
1.82
1.93
2.04
1,4
Watts
1222
1289
1359
1432
1508
1587
1670
1756
1845
1939
2035
2135
2240
2348
2459
2576
2697
2822
2951
Rpm
933
940
948
955
963
970
979
987
995
1004
1013
1022
1031
1040
1050
1059
1069
1079
1089
Bhp
1.49
1.57
1.65
1.74
1.82
1.91
2.01
2.10
2.21
2.31
2.42
2.53
2.65
2.77
2.90
3.03
3.17
3.31
3.45
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
576
621
670
721
775
832
893
957
1024
1095
1169
1246
1328
1414
1503
1597
1695
1797
1903
Rpm
682
692
702
712
722
732
743
754
765
777
788
800
811
823
835
848
860
872
885
---
Watts
732
783
837
894
954
1017
1083
1153
1225
1302
1381
1465
1552
1644
1739
1838
1942
2050
2162
Rpm
753
761
770
780
789
799
808
818
829
839
850
860
871
882
894
905
917
928
940
EXTERNAL STATIC PRESSURE (in, wg)
1.6
Watts
1392
1464
1540
1618
1699
1784
1872
1963
2057
2156
2258
2364
2473
2587
2705
2826
2953
3083
3218
Rpm
986
993
1000
1007
1014
1021
1029
1037
1045
1053
1062
1070
1079
1088
1097
1106
1116
1125
1135
LEGEND
Bhp
Watts
Bhp
0.78
0.84
0.90
0.96
1.02
1.09
1.16
1.24
1.31
1.40
1.48
1.57
1.66
1.76
1.86
1.97
2.08
2.20
2.32
Bhp
1.68
1.76
1.85
1.94
2.03
2.13
2.23
2.33
2.44
2.55
2.66
2.78
2.91
3.03
3.17
3.30
3.44
3.59
3.74
Watts
1565
1643
1723
1807
1893
1983
2076
2172
2272
2376
2483
2595
2709
2828
2951
3079
3210
3347
3487
Rpm
1037
1043
1049
1056
1063
1070
1077
1085
1092
1100
1108
1116
1125
1133
1142
1151
1160
1169
1179
0.8
Bhp
0.96
1.02
1.08
1.15
1.22
1.29
1.37
1.45
1.53
1.62
1.71
1.81
1.91
2.01
2.12
2.23
2.35
2.47
2.60
1.0
Watts
892
948
1008
1070
1136
1204
1276
1351
1429
1511
1597
1686
1779
1876
1977
2082
2192
2305
2423
Rpm
817
825
834
842
851
860
869
878
888
897
907
917
927
938
948
959
970
981
992
Bhp
1.13
1.20
1.27
1.34
1.42
1.50
1.58
1.66
1.75
1.85
1.95
2.05
2.15
2.26
2.38
2.50
2.62
2.75
2.88
Watts
1742
1824
1909
1998
2089
2185
2283
2384
2490
2599
2711
2827
2948
3073
3201
3334
3471
3612
3758
Rpm
1085
1091
1097
1103
1110
1117
1123
1131
1138
1145
1153
1161
1169
1177
1186
1194
1203
1212
--
Bhp
2.06
2.15
2.25
2.35
2.45
2.56
2.67
2.79
2.91
3.03
3.15
3.29
3.42
3.56
3.70
3.85
4.00
4.16
--
1,8
Bhp
1.87
1.96
2.05
2.14
2.24
2.34
2.45
2.56
2.67
2.79
2.91
3.03
3.16
3.30
3.43
3.58
3.72
3.87
4.03
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
38
Watts
1055
1117
1182
1250
1321
1395
1471
1552
1636
1723
1815
1909
2008
2111
2217
2328
2443
2562
2686
Watts
1921
2008
2099
2192
2289
2389
2492
2599
2710
2824
2942
3063
3189
3319
3452
3591
3733
3880
--
Table 21 -- Fan Performance 48HJ012 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
3O0O
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
0.2
Rpm
579
592
606
620
634
648
662
676
690
705
719
734
748
763
778
792
807
822
837
852
867
AIRFLOW
(Cfm)
300O
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Bhp
0.70
0.76
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.45
1.55
1.66
1.76
1.88
1.99
2.12
2.25
2.38
2.52
2.66
0.4
Watts
651
706
764
825
890
958
1030
1106
1185
1269
1357
1449
1545
1646
1751
1860
1975
2094
2218
2347
2482
1.2
Rpm
917
925
934
943
952
981
971
981
990
1000
1011
1021
1031
1042
1053
1064
1075
Bhp
1.70
1.79
1.88
1.98
2.08
2.18
2.29
2.40
2.52
2.64
2.76
2.89
3.03
3.16
3.31
3.46
3.61
Rpm
660
672
684
696
709
721
734
747
760
773
786
799
813
826
840
853
667
881
895
909
923
Bhp
0.89
0.96
1.03
1.10
1.17
1.25
1.34
1.42
1.52
1.61
1.71
1.82
1.93
2.04
2.16
2.28
2.41
2.55
2.69
2.83
2.98
1,4
Watts
1587
1670
1756
1845
1939
2035
2135
2240
2348
2459
2576
2697
2822
2951
3085
3224
3367
Rpm
Bhp
970
1.91
979
2.01
987
2.10
995
2.21
1004
2.31
1013
2.42
1022
2.53
1031
2.65
1040
2.77
1050
2.90
1059
3.03
1069
3.17
1079
3.31
1089
3.45
1100
3.60
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
832
893
957
1024
1095
1169
1246
1328
1414
1503
1597
1695
1797
1903
2014
2130
2250
2375
2505
2640
2781
Rpm
732
743
754
765
777
788
800
811
823
835
848
860
872
885
898
910
923
936
949
963
976
---
Watts
1017
1083
1153
1225
1302
1381
1465
1552
1644
1739
1838
1942
2050
2162
2279
2401
2527
2858
2794
2935
3081
Rpm
799
808
818
829
839
850
860
671
882
894
905
917
928
940
952
964
976
989
1001
1014
1026
EXTERNAL STATIC PRESSURE (in. wg)
1,6
Watts
1784
1872
1963
2057
2156
2258
2364
2473
2587
2705
2826
2953
3083
3218
3357
Rpm
1021
1029
1037
1045
1053
1062
1070
1079
1088
1097
1106
1116
1125
.........
.........
LEGEND
Bhp
Watts
Bhp
1.09
1.16
1.24
1.31
1.40
1.48
1.57
1.66
1.76
1.86
1.97
2.08
2.20
2.32
2.44
2.57
2.71
2.85
3.00
3.15
3.30
Bhp
2.13
2.23
2.33
2.44
2.55
2.68
2.78
2.91
3.03
3.17
3.30
3.44
3.59
Watts
1983
2076
2172
2272
2376
2483
2595
2709
2828
2951
3079
3210
3347
Rpm
1070
1077
1085
1092
1100
1108
1116
1125
1133
1142
1151
......
......
0.8
Bhp
1.29
1.37
1.45
1.53
1.62
1.71
1.81
1.91
2.01
2.12
2.23
2.35
2.47
2.60
2.73
2.87
3.01
3.15
3.31
3.46
3.63
1.0
Watts
1204
1276
1351
1429
1511
1597
1686
1779
1876
1977
2082
2192
2305
2423
2546
2673
2805
2942
3083
3230
3383
Rpm
860
869
878
888
897
907
917
927
938
948
959
970
981
992
1004
1015
1027
1038
1050
---
Bhp
1.50
1.58
1.66
1.75
1.85
1.95
2.05
2.15
2.26
2.38
2.50
2.62
2.75
2.88
3.02
3.16
3.31
3.46
3.82
---
Watts
2185
2283
2384
2490
2599
2711
2827
2948
3073
3201
3334
Rpm
1117
1123
1131
1138
1145
1153
1161
1169
1177
1186
--
Bhp
2.56
2.67
2.79
2.91
3.03
3.15
3.29
3.42
3.56
3.70
--
1,8
Bhp
2.34
2.45
2.56
2.67
2.79
2.91
3.03
3.16
3.30
3.43
3.58
2,0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require fieldsupplied drive.
39
Watts
1395
1471
1552
1636
1723
1815
1909
2008
2111
2217
2328
2443
2562
2686
2814
2947
3085
3227
3375
---
Watts
2389
2492
2599
2710
2824
2942
3063
3189
3319
3452
--
Table 22 -- Fan Performance 48HJ012 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
(Cfm)
3O00
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
0.2
Rpm
579
592
606
620
634
648
662
676
690
705
719
734
748
763
778
792
807
822
837
852
867
AIRFLOW
(Cfm)
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
Bhp
0.70
0.76
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.45
1.55
1.66
1.76
1.88
1.99
2.12
2.25
2.38
2.52
2.66
0.4
Watts
651
706
764
825
890
958
1030
1106
1185
1269
1357
1449
1545
1646
1751
1860
1975
2094
2218
2347
2482
Rpm
660
672
684
696
709
721
734
747
760
773
786
799
813
826
840
853
867
881
895
909
923
1.2
Rpm
917
925
934
943
952
961
971
981
990
1000
1011
1021
1031
1042
1053
1064
1075
1086
1097
1109
1120
Bhp
1.70
1.79
1.88
1.98
2.08
2.18
2.29
2.40
2.52
2.64
2.76
2.89
3.03
3.16
3.31
3.46
3.61
3.77
3.93
4.10
4.28
Bhp
0.89
0.96
1.03
1.10
1.17
1.25
1.34
1.42
1.52
1.61
1.71
1.82
1.93
2.04
2.16
2.28
2.41
2.55
2.69
2.83
2.98
1,4
Watts
1587
1670
1756
1845
1939
2035
2135
2240
2348
2459
2576
2697
2822
2951
3085
3224
3367
3515
3668
3826
3990
Rpm
970
979
987
995
1004
1013
1022
1031
1040
1050
1059
1069
1079
1089
1100
1110
1121
1131
1142
1153
1164
Bhp
1.91
2.01
2.10
2.21
2.31
2.42
2.53
2.65
2.77
2.90
3.03
3.17
3.31
3.45
3.60
3.76
3.91
4.08
4.25
4.43
4.61
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
832
893
957
1024
1095
1169
1246
1328
1414
1503
1597
1695
1797
1903
2014
2130
2250
2375
2505
2640
2781
Rpm
732
743
754
765
777
788
800
811
823
835
848
860
872
885
898
910
923
936
949
963
976
---
Watts
1017
1083
1153
1225
1302
1381
1465
1552
1644
1739
1838
1942
2050
2162
2279
2401
2527
2658
2794
2935
3081
Rpm
799
808
818
829
839
850
860
871
882
894
905
917
928
940
952
964
976
989
1001
1014
1026
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
1784
1872
1963
2057
2156
2258
2364
2473
2587
2705
2826
2953
3083
3218
3357
3502
3650
3805
3963
4128
4296
Rpm
1021
1029
1037
1045
1053
1062
1070
1079
1088
1097
1106
1116
1125
1135
1145
1155
1165
1175
1186
1196
1207
LEGEND
Bhp
Watts
Bhp
1.09
1.16
1.24
1.31
1.40
1.48
1.57
1.66
1.76
1.86
1.97
2.08
2.20
2.32
2.44
2.57
2.71
2.85
3.00
3.15
3.30
Bhp
2.13
2.23
2.33
2.44
2.55
2.66
2.78
2.91
3.03
3.17
3.30
3.44
3.59
3.74
3.90
4.06
4.22
4.39
4.57
4.75
4.94
Watts
1983
2076
2172
2272
2376
2483
2595
2709
2828
2951
3079
3210
3347
3487
3632
3782
3937
4096
4260
4430
4604
Rpm
1070
1077
1085
1092
1100
1108
1116
1125
1133
1142
1151
1160
1169
1179
1188
1198
1208
1217
1228
1238
......
0.8
Bhp
1.29
1.37
1.45
1.53
1.62
1.71
1.81
1.91
2.01
2.12
2.23
2.35
2.47
2.60
2.73
2.87
3.01
3.15
3.31
3.46
3.63
1.0
Watts
1204
1276
1351
1429
1511
1597
1686
1779
1876
1977
2082
2192
2305
2423
2546
2673
2805
2942
3083
3230
3383
Rpm
860
869
878
888
897
907
917
927
938
948
959
970
981
992
1004
1015
1027
1038
1050
1062
1074
Bhp
1.50
1.58
1.66
1.75
1.85
1.95
2.05
2.15
2.26
2.38
2.50
2.62
2.75
2.88
3.02
3.16
3.31
3.46
3.62
3.78
3.95
Watts
2185
2283
2384
2490
2599
2711
2827
2948
3073
3201
3334
3471
3612
3758
3909
4064
4224
4389
4559
4734
Rpm
1117
1123
1131
1138
1145
1153
1161
1169
1177
1186
1194
1203
1212
1221
1230
1239
1249
1258
1268
--
Bhp
2.56
2.67
2.79
2.91
3.03
3.15
3.29
3.42
3.56
3.70
3.85
4.00
4.16
4.32
4.49
4.66
4.84
5.02
5.21
--
1,8
Bhp
2.34
2.45
2.56
2.67
2.79
2.91
3.03
3.16
3.30
3.43
3.58
3.72
3.87
4.03
4.19
4.36
4.53
4.71
4.89
5.08
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See page 41 for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require fieldsupplied drive.
40
Watts
1395
1471
1552
1636
1723
1815
1909
2008
2111
2217
2328
2443
2562
2686
2814
2947
3085
3227
3375
3528
3685
Watts
2389
2492
2599
2710
2824
2942
3063
3189
3319
3452
3591
3733
3880
4031
4187
4348
4514
4684
4860
--
Table 23 -- Fan Performance 48HJ014 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
(Cfm)
37OO
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
0.2
Rpm
676
690
705
719
734
748
763
778
792
807
822
837
852
867
882
897
912
927
943
958
973
988
1004
1019
1034
1050
1065
AIRFLOW
(Cfm)
370O
3800
3g00
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
Bhp
1.19
1.27
1.36
1.45
1.55
1.66
1.76
1.88
1.99
2.12
2.25
2.38
2.52
2.66
2.81
2.97
3.13
3.30
3.47
3.65
3.83
4.03
4.22
4.43
4.64
4.86
5.09
0.4
Watts
1106
1185
1269
1357
1449
1545
1646
1751
1860
1975
2094
2218
2347
2482
2622
2766
2917
3073
3234
3402
3575
3754
3939
4131
4329
4533
4744
1.2
Rpm
981
990
1000
1011
1021
1031
1042
1053
1084
1075
1086
1097
1109
1120
1132
1144
1155
1167
1179
Bhp
2.40
2.52
2.64
2.76
2.89
3.03
3.16
3.31
3.46
3.61
3.77
3.93
4.10
4.28
4.46
4.65
4.84
5.04
5.24
Rpm
Bhp
747
1.42
760
1.52
773
1.61
786
1.71
799
1.82
813
1.93
826
2.04
840
2.16
853
2.28
867
2.41
881
2.55
895
2.69
909
2.83
923
2.98
937
3.14
951
3.30
968
3.47
980
3.64
994
3.82
1009
4.01
1023
4.20
1038
4.40
1052
4.60
1067
4.81
1082
5.03
............
............
1.4
Watts
2240
2348
2459
2576
2697
2822
2951
3085
3224
3367
3515
3688
3826
3990
4159
4333
4512
4697
4889
Rpm
Bhp
1031
2.65
1040
2.77
1050
2.90
1059
3.03
1069
3.17
1079
3.31
1089
3.45
1100
3.60
1110
3.76
1121
3.91
1131
4.08
1142
4.25
1153
4.43
1164
4.61
1175
4.79
1187
4.99
1198
5.19
............
............
EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
1328
1414
1503
1597
1695
1797
1903
2014
2130
2250
2375
2505
2640
2781
2928
3077
3233
3395
3563
3738
3915
4100
4292
4489
4693
Rpm
811
823
835
848
860
872
885
898
910
923
936
949
963
976
989
1003
1016
1030
1044
1057
1071
1085
1099
1113
.........
---
Watts
1552
1644
1739
1838
1942
2050
2162
2279
2401
2527
2658
2794
2935
3081
3232
3389
3551
3719
3892
4071
4256
4447
4645
4848
Rpm
671
882
894
905
917
928
940
952
984
976
989
1001
1014
1026
1039
1052
1065
1078
1091
1104
1117
1130
......
......
EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
2473
2587
2705
2826
2953
3083
3218
3357
3502
3650
3805
3963
4128
4296
4471
4651
4836
Rpm
1079
1088
1097
1106
1116
1125
1135
1145
1155
1165
1175
1186
1196
1207
1218
---
LEGEND
Bhp
Watts
Bhp
1.66
1.76
1.86
1.97
2.08
2.20
2.32
2.44
2.57
2.71
2.85
3.00
3.15
3.30
3.47
3.63
3.81
3.99
4.17
4.37
4.56
4.77
4.98
5.20
Bhp
2.91
3.03
3.17
3.30
3.44
3.59
3.74
3.90
4.06
4.22
4.39
4.57
4.75
4.94
5.13
---
Watts
2709
2828
2951
3079
3210
3347
3487
3632
3782
3937
4096
4260
4430
4604
4784
Rpm
1125
1133
1142
1151
1160
1169
1179
1188
1198
1208
1217
1228
1238
---
0.8
Bhp
1.91
2.01
2.12
2.23
2.35
2.47
2.60
2.73
2.87
3.01
3.15
3.31
3.46
3.63
3.80
3.97
4.15
4.34
4.53
4.73
4.93
5.14
1.0
Watts
1779
1876
1977
2082
2192
2305
2423
2546
2673
2805
2942
3083
3230
3383
3540
3702
3870
4044
4223
4408
4599
4796
Rpm
927
938
948
959
970
981
992
1004
1015
1027
1038
1050
1062
1074
1088
1099
1111
1123
1136
1149
---
Bhp
2.15
2.26
2.38
2.50
2.62
2.75
2.88
3.02
3.16
3.31
3.46
3.62
3.78
3.95
4.13
4.31
4.49
4.69
4.88
5.09
---
Watts
2948
3073
3201
3334
3471
3612
3758
3909
4064
4224
4389
4559
4734
Rpm
1169
1177
1186
1194
1203
1212
1221
1230
1239
1249
1258
1268
--
Bhp
3.42
3.56
3.70
3.85
4.00
4.16
4.32
4.49
4.66
4.84
5.02
5.21
1.8
Bhp
3.18
3.30
3.43
3.58
3.72
3.87
4.03
4.19
4.36
4.53
4.71
4.89
5.08
Watts
2008
2111
2217
2328
2443
2562
2686
2814
2947
3085
3227
3375
3528
3685
3849
4017
4191
4370
4555
4746
---
2,0
m
Watts
3189
3319
3452
3591
3733
3880
4031
4187
4348
4514
4684
4860
m
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
3. See this page for General Fan Performance Notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require fieldsupplied drive.
GENERAL NOTES FOR FAN PERFORMANCE
1. Values include losses for filters, unit casing, and wet coils. See Table 8 and
Fig. 44 for accessory/FlOP
static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using the fan motors up
to the wattage ratings shown will not result in nuisance tripping or premature
DATA TABLES
motor failure. Unit warranty will not
Performance data in Tables 9A and
3. Use of a field-supplied motor may
representative for details.
4. Interpolation is permissible. Do not
4!
be affected. See Evaporator-Fan Motor
9B for additional information.
affect wire sizing. Contact your Carrier
extrapolate.
PRE-START-UP
START-UP
Unit Preparation--Make
sure that unit has been
installed in accordance
with inst;dlation
instructions
and
applicable codes. Complete the Start-Up Checklist, located on
the back page of this booklet.
F;filure to observe the following warnings could result in
serious personal injury.
1. Follow recognized safety practices and we;u protective
goggles when checking or the servicing refrigerant
system.
2. Do not operate the compressor or provide any electric
power to the unit unless the compressor terminal cover
is in place and secured.
3. Do not remove the compressor terminal cover until all
electrical sources _ue disconnected.
4. Relieve all pressure from file system before touching or
disturbing anything inside the compressor terminal box
if refrigerant leak is suspected around the compressor
termimds.
5. Never attempt to repair a soldered connection while the
refrigerant system is under pressure.
6. Do not use torch to remove any component. The system cont_dns oil and refrigerant under pressure. To
remove a component, wear protective goggles and proceed as follows:
Return-Air
Filters--Make
sure correct
filters are
inst_dled in tilter tracks (see Table 1). Do not operate unit without return-air filters.
Outdoor-Air Inlet Screens -- Outdoor-;dr inlet screen(s)
must be in place befole operating unit.
Compressor Mountingspring mounted.
down bolts.
3.
4.
Make the following
b.
Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a
refrigerant leak. Leak-test all refiigemnt tubing connections using an electronic leak detectol: halide
torch, or liquid-soap solution.
c.
Inspect all tield-wiring
and factoly-wiring
connections. Be sure that connections are completed and
tight.
d.
Inspect coil fins. If damaged
handling, carefully straighten
comb.
connections
in
Disconnect gas piping fiom unit when leak
testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas
valve damage resulting in hazardous condition. If gas valve is subjected to pressure
greater than I/2 psig, it must be replaced
before use. When pressure testing fieldsupplied gas piping at pressures of 1/2 psig
or less, a unit connected to such piping must
be isolated by manually
closing the gas
v_dve.
Refrigerant Service Ports--
To service refiigerant
service pofls, remove compressor access panel. Each unit system has 4 Schrader-type
service gage ports: one on the suction
line, one on the liquid line, one on the compressor discharge
line and one on the discharge line underneath the high-pressure
switch. Be sure that caps on the ports are tight. The Schradertype valve on the discharge line is located under the lowpressure switch.
inspections:
Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
hold-
Gas Piping -- Check gas piping for leaks.
CAUto, or
a.
compressor
Check all electric_d
unit control boxes. Tighten as required.
Proceed as follows to inspect and plepale the unit for initi_d
st_ut-up:
on all WARNING
labels attached
or remove
Internal Wiring-
a. Shut off gas and then electrical power to the unit.
Install lockout tag.
b. Relieve all pressure from the system using both
high-pressure and low-pressure ports.
c. Cut the component connection tubing with a tubing
cuttel: and remove the component from the unit.
d. Carefully unsweat the remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flalne.
1. Remove all access panels.
2. Read and follow instructions
TION, and INFORMATION
shipped with, the unit.
Compressorsare internally
Do not loosen
High Flow Valves-
High flow refrigerant
valves are
located on the compressor hot gas and suction tubes. Large
black plastic caps distinguish these wdves with O-rings located
inside the caps. These v;dves cannot be accessed for service in
the field. Ensure that the plastic caps me in place and tight or
the possibility of refrigerant leakage could occm:
Compressor Rotation
-- It is important to be certain
that the compressors me rotating in the proper direction. To determine whether or not compressors are rotating in the proper
direction:
during shipping and
the fins with a tin
1. Connect service gages to the suction and dischmge
sure fittings.
pres-
Verify the following conditions:
2.
Energize the compressol:
a.
Make sure that condenser
fan blade is correctly
positioned in the fan orifice. See Condenser-Fan
Adjustment section on page 48 for more details.
3.
The suction pressure should diop and the discharge
sure should rise, as is normal on any start-up.
pres-
M_e
If the suction pressure does not drop and the discharge
sure does not rise to normal levels:
pres-
b.
c.
Make sure that condensate drain trap is filled with
water to ensure proper di'ainage.
1. Note that the evaporator
the wrong direction.
d.
Make sure that all tools and miscellaneous
have been removed.
2.
Turn off power to the unit and install lockout tag.
3.
Reverse any two of the unit power leads.
4.
Reapply powerto
sure that air filter(s) is in place.
loose parts
42
fan is probably
the compressol:
also rotating
in
Thesuction
anddischarge
pressure
levels
should
nowmove
totheirnormal
start-up
levels.
2.
3.
4.
When the compressors
am rotating
in the wrong direction,
the unit will have increased
noise levels and will not provide heating and cooling.
Compressor
failure will occur if
the unit continues
to operate in this condition.
Cooling -- To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
tempemtum. Compressor starts on closum of contactors.
Check unit charge. Refer to Refrigerant Ch_uge section on
page 48.
Reset thermostat at a position above room temperatum.
Compressor will shut off. Evaporator fan will shut off after
30-second delay.
TO SHUT OFF UNIT -- Set system switch at OFF position.
Resetting thermostat at a position above room temperatum
shuts unit off temponuily until space temperatum exceeds thermostat setting. Units zue equipped with Cycle-LOC TM protection device. Unit shuts down on any safety trip and remains off;
an indicator light on the thermostat comes on. Check reason for
safety trip.
Compressor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF position and
then to ON position.
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13_000
14,000
7.
The evaporator fan will turn off45
mostat temperatum is satisfied.
8.
Adjust airflow to oNain a temperatum rise within
range specified on the unit nmneplate and Table 1.
fan will turn on 45 seconds after a call for
seconds after the therthe
the original
default
value, reset the power
to
TO SHUT OFF UNIT -- Set system selector switch at OFF
position. Resetting heating selector lever below room temperaturn will temporarily shut off unit until space temperature ftdls
below thermostat setting.
250,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Sizet
30
30
31
32
33
34
35
36
37
38
39
40
41
42
The evaporator
heating.
To restore
the unit.
Table 24 -- Altitude Compensation*
Liquid
Propane
Orifice
Sizet
41
42
42
42
43
43
44
44
45
46
47
47
48
48
6.
The evaporator-fan off delay can also be modified. Once the
call for heating has ended, them is a 10-minute period during
which the modification can occm: If the limit switch trips during this period, the evaporato>fan
off delay will incmase by
15 seconds. A maximum of 9 trips can occur, extending the
evaporator-fan off delay to 180 seconds.
NOTE: Upon a call for heat the main burners will remain on
for a minimum of 60 seconds.
Natural
Gas
Orifice
Sizet
31
32
32
32
33
34
35
36
37
38
39
40
41
42
After a call for heating, the main burners should light
within 5 seconds. If the burners do not light, then there is
a 22-second delay befom another 5-second try. If the
burners still do not light, the time delay is repeated. If the
burners do not light within 15 minutes, there is a lockout.
To reset the control, bmak the 24 v power to WI.
If the limit switch trips at the stm-t of the heating cycle during the evaporator on delay, the time period of the on delay for
the next cycle will be 5 seconds less than the time at which the
switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporato>fan on delay for the next cycle will occur
at 25 seconds.) To prevent shori-cycling, a 5-second reduction
will only occur if a minimum of 10 minutes has elapsed since
the last call for heating.
requim no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperatum and verily
that the burners light and evaporator fan is energized. After
ensuring that the unit continues to heat the building, lower the
thermostat setting below room tempemtum and verily that the
burners and evaporator fan turn off.
Refer to Table 24 for the con'ect orifice to use at high
altitudes.
ELEVATION
(Ft)
5.
NOTE: The default value for the evaporator-fan motor on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occm:
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to
180 seconds. When one flash of the LED is observed, the
evaporator-fan on/off delay has been modified.
Main Burners -- Main burners are factory set and should
90,000-224,000
BTUH
NOMINAL INPUT
Turn on electrical supply and open manu_fl gas valve.
Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temperature
lever above room temperature.
The induced-draft
motor will start.
Safety Relief--A
soft-solder joint at the suction-line
Schmder port provides pressure relief under abnormal temperatum and pressure conditions.
Liquid
Propane
Orifice
Sizet
38
39
40
41
42
43
43
44
44
45
45
46
47
47
Ventilation (Continuous
Fan)-
Set fan and system
selector switches at ON and OFF positions, respectively.
Evaporator fan operates continuously to provide constant air
circulation. When the evaporator fan selector switch is turned
to the OFF position, there is a 30-second delay befom the fan
turns off.
Operating
Sequence
COOLING,
UNITS WITHOUT
ECONOMIZER
-- When
thermostat calls for cooling, terminals G and YI are energized.
The indoor-fan contactor (IFC) and compressor contactor am
energized and indoor-fan motor, compressor, and outdoor fan
starts. The outdoor fan motor runs continuously while unit is
cooling.
HEATING, UNITS WITHOUT
ECONOMIZER
-- When
the thermostat calls for heating, terminal Wl is energized. In
order to prevent thermostat short-cycling, the unit is locked
into the Heating mode for at least 1 minute when Wl is energized. The induced-draft motor (IDM) is then energized and
the burner ignition sequence begins. The indoor (evaporator)
*As the height above sea level increases, there is less oxygen per cubic foot
of air. Therefore, heat input rate should be reduced at higher altitudes.
tOrifice available through your local Carrier distributor.
Heating
1. Purge gas supply line of air by opening union ahead of
gas valve. When gas odor is detected, tighten union and
wait 5 minutes befom proceeding.
43
fanmotor(IFM)is energized
45 seconds
ariela flalneis
ignited.Onunitsequipped
for two stages
of heat,when
additional
heatisneeded,
W2is energized
andthehigh-fire
solenoid
onthemgfin
gasvalve(MGV)isenergized.
Whenthe
thermostat
is satisfied
andWI andW2aredeenergized,
the
IFMstops
aftera45-second
time-off
delay.
•
position
is NOT forced.
Pro-cooling occurs when there is no call from the therlnostat
except G Pre-cooling is defined as the economizer modulates
to provide 70 F supply all:
When free cooling is available the PremierLink control will
control the compressors and economizer to provide a supplyair temperature determined to meet the YI and Y2 calls from
the thermostat using the following three routines. The three
control routines are based on OAT.
COOLING. UNITS WITH ECONOMISER
IV -- When free
cooling is not available, the compressors will be controlled by
the zone thermostat.
When free cooling is available, the
outdoor-air &unper is modulated by tile EconoMiSer IV control to provide a 50 to 55 F supply-air temperature into the
zone. As the supply-air temperature fluctuates above 55 or below 50 L the dampers will be modulated (open or close) to
bring the supply-air temperature back within the set points.
The 3 routines me based on OAT where:
SASP = Supply Air Set Point
DXCTLO
= Direct Expansion
PID = Proportional
Integrated EconoMiSer IV operation on single-stage units
requires a 2-stage thermostat (YI and Y2).
For EconoMiSer IV operation, there must be a therlnostat
call for the fan (G). This will move the dmnper to its minimum
position during the occupied mode.
Routine
•
•
Above 50 F supply-air temperature, the &tmpers will modulate from 100% open to the minimum open position. From 50 F
to 45 F supply-air temperature, the &_mpers will maintain at
the minimum open position. Below 45 F the dampers will be
completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open position once
the supply-air temperature rises to 48 E
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be energized and deenergized.
•
•
•
•
•
•
Damper movement from full closed to full open (or vice
versa) will take between 1I/2 and 21/2 minutes.
•
•
If free cooling can be used as determined from the appropriate changeover command (switch, @ bulb, enth_dpy curve,
differenti_d dry bulb, or differential enth_dpy), a call for cooling
(YI closes at the thermostat) will cause the control to modulate
the dampers open to maintain the supply air temperature set
point at 50 to 55 E
•
•
•
•
As the supply air temperature drops below the set point
range of 50 to 55 E the control will modulate the outdoor-tdr
dmnpers closed to maintain the proper supply-air temperature.
HEATING. UNITS WITH ECONOMI$ER
IV -- When the
room temperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer
section. When the thermostat
is satisfied, the economizer
dmnper moves to the minimum position.
COOLING.
UNITS WITH ECONOMI$ER2,
PREMIERLINK TM CONTROL AND A THERMOSTAT
-- When free
cooling is not available, the compressors will be controlled by
the PremierLink control in response to the YI and Y2 inputs
from the thermostat.
Cooling Lockout Set Point
Integral
1 (OAT < DXCTLO)
YI energized
(SATLOI + 3).
Y2 energized
(SATLO2 + 3).
Routine
If field-inst_dled accessory CO 2 sensors me connected to the
EconoMi$er IV control, a demand controlled ventilation strategy will begin to operate. As the CO 2 level in the zone increases
above the CO 2 set point, the minimum position of the damper
will be increased proportionally.
As the CO2 level decreases
because of the increase in fresh air. the outdoor-air damper will
be proportionally closed. Damper position will follow the higher demand condition fiom DCV mode or free cooling mode.
to
•
•
•
•
•
Economizer
2 (DXCTLO
economizer
maintains
a
SASP
=
economizer
maintains
a
SASP
=
< OAT < 68 F)
If only YI energized, the economizer maintains a SASP
= (SATLOI + 3).
If SAT > SASP + 5 and economizer
position > 80%,
economizer will go to minimum position for 3 minutes or
until SAT > 68 IF.
First stage of mechanical
cooling will be energized.
Integrator resets.
Economizer
opens again and controls to current SASP
after stage one on for 90 seconds.
With YI and Y2 energized economizer
maintains
an
SASP = SATLO2 + 3.
If SAT > SASP + 5 and economizer
position >80%,
economizer will go to minimum position for 3 minutes or
until SAT > 68 IF.
If compressor
one is on then second stage of mechanical
cooling will be energized. Otherwise
the first stage will
be energized.
Integrator resets.
Economizer
opens again and controls
to SASP after
stage one on for 90 seconds.
Routine 3 (OAT > 68)
Economizer is opened 100%.
Compressors
1 and 2 are cycled based on YI and Y2
using minimum on and off times and watching the supply air temperature
as compared
to SATLOI
and
SATLO2 set points.
If optional power exhaust is inst:dled, as the outdoor-air
damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO 2 sensors are connected to the
PremielLink
control, a PID-controlled
demand ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally.
As the CO 2 level
decreases because of the increase in fresh ail: the outdoor-air
damper will be proportionally closed.
HEATING. UNITS WITH ECONOMISER2,
PREMIERLINK
CONTROL AND A THERMOSTAT -- When the thermostat
calls for heating, terminal WI is energized. The PremierLink
control will move the economizer damper to the minimum position if there is a c_dl for G and closed if there is a call for WI
without G. In order to prevent thermostat from short cycling,
the unit is locked into the heating mode for at least 10 minutes
when WI is energized. The induced-&aft motor is then energized and the burner ignition sequence begins.
The PremierLink control will use the following information
determine if free cooling is available:
Indoor fan has been on for at least 30 seconds.
The SPT, SAT, and OAT inputs must have valid readings.
OAT must be less than 75 E
OAT must be less than SPT.
Enthalpy must be LOW (may be jumpered if an enthalpy
sensor not available).
44
Onunitsequipped
fortwostages
ofheat,whenadditional
heatisneeded,
W2isenergized
andthehigh-fire
solenoid
on
themaingasvalve(MGV)isenergized.
Whenthethennostat
is satisfied
andWI is deenergized,
the[FM stopsaftera
45-second
time-off
delayunless
Gisstillmaintained.
TEMPERATURE
LU 75
74
_:
73
el:
72
COOLING.
UNITS WITH ECONOMI$ER2,
PREMIERLINK TM CONTROL AND A ROOM SENSOR -- When
free cooling is not available, the compressors will be controlled
by the PremierLink controller using a PIE) Error reduction calculation as indicated by Fig. 48.
...... SET
,,=, 71
b-
tu
--
POINT
TEMPERATURE
70
o
69
09
The PremierLink controller will use the following information to determine if free cooling is available:
• Indoor fan has been on for at least 30 seconds.
• The SPT. SAT. and OAT inputs must have valid readings.
• OAT must be less than 75 F.
• OAT must be less than SPT.
• Enthalpy
must be LOW (may be jumpered
if and
enthalpy sensor is not available).
• Economizer
position is NOT forced.
When free cooling is available, the outdoor-air dmnper is
positioned through the use of a Proportional
Integral (PID)
control process to provide a calculated supply-air temperature
into the zone. The supply air will maintain the space temperature between the heating and cooling set points as indicated in
Fig. 49.
The PremierLink
control will integrate the compressors
stages with the economizer based on similar logic as the three
routines listed in the previous section. The SASP will float up
and down based on the error reduction calculations that compare space temperature and space set point.
68
TIME
NOTE: PremierLink control performs smart staging of 2 stages of DX
cooling and up to 3 stages of heat,
Fig. 48 i
DX Cooling
Temperature
Control
Example
TEMPERATURE
CONTROL
75
73
741_
"
71 ]
_
72
......... _
704 ........
69
68
J
//
_
....................................
------COOL SETPOINT
_
--
TEMPERATURE
---
HEAT
..........................
SETPOINT
TIME
When outside-air temperature conditions require the economizer to close for a compressor stage-up sequence, the economizer control integrator is reset to zero aller the stage-up sequence is completed. This prevents the supply-air temperature
from dropping too quickly and creating a freeze condition that
would make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion)
cooling control, while the economizer
space set point is a
calculated value between the heating and cooling set points.
The economizer set point will always be at least one degree
below the cooling set point, allowing for a smooth transition
from mechanical
cooling with economizer
assist, back to
economizer
cooling as the cooling set point is achieved.
The compressors
may be used for initial cooling then the
PremierLink controller will modulate the economizer using an
error reduction calculation to hold the space temperature
between the heating and cooling set points. See Fig. 49.
The controller uses the following conditions
economizer cooling:
• Enthalpy is Low
• SAT reading is available
• OAT reading is available
• SPT reading is available
• OAT < SPT
• Economizer Position is NOT forced
CONTROL
Fig. 49 --
Economizer
Temperature
Control Example
HEATING. UNIT WITH ECONOMISER2,
PREMIERLINK
CONTROL AND A ROOM SENSOR -- Every 40 seconds
the controller will calculate the required heat stages (maximum
of 3) to mtfintain Supply-Air Temperature (SAT) if the following qualifying conditions are met:
• Indoor fan has been on for at least 30 seconds.
• COOL mode is not active.
• OCCUPIED,
TEMR
COMPENSATED
START
or
HEAT mode is active.
• SAT reading is available.
• Fire shutdown mode is not active.
If all of the above conditions are met, the number of heat
stages is calculated; otherwise the required number of heat
stages will be set to 0.
If the PremierLink controller determines that heat stages are
required, the economizer damper will be moved to minimum
position if occupied and closed if unoccupied.
to determine
Staging should be as follows:
If Heating PIE) STAGES=2
• HEATSTAGES=I
(50% capacity) will energize HSI
• HEAT STAGES=2 (100% capacity) will energize HS2
If any of the above conditions are not met, the economizer
submaster reference (ECSR) is set to maximum limit and the
damper moves to minimum position. The operating sequence
is complete. The ECSR is rec;dculated every 30 seconds.
If an optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
If field-installed
accessory CO 2 sensors are connected to
the PremierLink control, a PID-controlled
demand ventilation
strategy will begin to operate. As the CO 2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally.
As the CO 2 level
decreases because of the increase in flesh air. the outdoor-air
damper will be proportionally closed.
If
•
•
•
Heating PID STAGES=3 and AUXOUT = HS3
HEAT STAGES=I
(33% capacity) will energize HSI
HEAT STAGES=2 (66% capacity) will energize HS2
HEAT STAGES=3 (100% capacity) will energize HS3
In order to prevent short cycling, the unit is locked into the
Heating mode forat least 10 minutes when HSI is deenergized.
When HSI is energized the induced-draft motor is then
energized and the burner ignition sequence begins. On units
equipped for two stages of heat, when additiomfl heat is needed, HS2 is energized and the high-fire solenoid on the main gas
valve (MGV) is energized. When the space condition is satistied and HSI is deenergized the IFM stops after a 45-second
45
time-off
delayunless
in theoccupied
mode.
Tilefanwill run
continuously
in theoccupied
modeasrequired
by national
energy
andfreshairstandards.
UNITS WITH THE HUMIDI-MIZER
TM
ADAPTIVE
DEHUMIDIFICATION
outside air temperature switch will lock out this mode of
operation.
See Table 25 for file Humidi-MiZer a&tptive dehumidification system sequence of operation.
SYSTEM
Normal Design Cooling Operation -- When the rooftop operates under the normal sequence of operation, the compressol_
will cycle to maintain indoor conditions. See Fig. 50.
The Humidi-MiZer
adaptive dehumidification
system includes a factory installed Motormastel®
low ambient control
to keep the head and suction pressure high, tallowing normal
design cooling mode operation down to 0 ° IF.
Subcooling Mode -- When subcooling mode is initiated, this
will energize (close) the liquid line solenoid valve (LLSV)
forcing the hot liquid refrigerant to enter the subcooling coil
(see Fig. 51 ).
As the hot liquid refrigerant passes through the subcoolinJ
reheat dehumidification
coil, it is exposed to the cold supply
airflow coming fllrough the evaporator coil. The liquid is further subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then entel_ a thermostatic
expansion valve (TXV) where the liquid drops to a lower pressure. The TXV does not have a pressure drop great enough to
change the liquid to a 2-phase fluid, so the liquid then enters
the Acutrol TM device tit the evaporator coil.
Fig. 50 -- Humidi-MiZer Normal Design
Cooling Mode Operation
The liquid enters the evaporator coil tit a temperature lower
than in standard cooling operation. This lower temperature
increases the latent capacity of the rooftop unit. The refrigerant
passes through the evaporator and is turned into a vapor. The
air passing over the evaporator coil will become colder than
during normal operation. Howevel: as this same air passes over
the subcooling coil, it will be slightly warmed, pmtially reheating the ail:
Subcooling mode operates only when the outside-air temperature is wmmer than 40 E A factory-installed
temperature
switch located in the condenser section will lock out subcooling mode when the outside temperature is cooler than 40 E
The scroll compressors are equipped with crankcase heaters
to provide protection for the compressors due to the additiomd
refrigerant charge required by the subcoolinJleheat
coil.
When in subcooling mode, there is a slight decrease in
system total gross capacity (5% less), a lower gross sensible
capacity (20% less), and a greatly increased latent capacity (up
to 40% more).
VALVE
Fig. 51 -- Humidi-MiZer
Subcooling
Operation
Hot Gas Reheat Mode -- When the humidity levels in the
space require humidity control, a hot gas solenoid valve (specific to hot gas leheat mode only) will open to bypass a portion
of hot gas refrigerant around the condenser coil (see Fig. 52).
This hot gas will mix wifll liquid refrigerant leaving the condenser coil and flow to the subcooling/reheat
dehumidification
coil. Now the conditioned air coming off the evaporator will be
cooled and dehumidified, but will be wmmed to neutral conditions (72 F to 75 F) by the subcooling/reheat
dehumidification
coil.
NOTE: The 48HJ008-014 rooftop units can operate one circuit
in subcooling mode and one circuit in hot gas reheat mode or
both circuits in hot gas reheat mode, or both in normal design
cooling mode.
The net effect of the rooftop when in hot gas reheat mode is
to provide nearly tdl latent capacity removal from the space
when sensible loads diminish (when outdoor temperature conditions are moderate). When in hot gas reheat mode, the unit
will operate to provide mostly latent capacity and extremely
low sensible heat ratio capability.
Similar to the subcooling mode of operation, hot gas reheat
mode operates only when the outside-air temperature
is
warmer than 40 E Below this temperature, a factory-installed
L_5
/'_
LLSV
CLOSE_)
SO .3_ VAVE_
_ulB [NE
Mode
/
Fig. 52 -- Humidi-MiZer Hot Gas Reheat Mode
Operation
46
Table 25 -- Humidi-MiZer TM Adaptive Dehumidification System Sequence of Operation
and System ResponseDual Compressor Units (48HJ008-14)
THERMOSTAT
INPUT
ECONOMIZER
48HJ UNIT OPERATION
FUNCTION
First Stage
H
OAT <
Economizer
Set Point
Economizer
Y1
Y2
On
On
-On
No
Off
Unit Operates
On
On
On
Off
No
Off
On
Yes
On
On
On
Yes
On
On
On
On
Off
Yes
On
On
On
Off
Off
No
Off
On
Off
Compressor
1
Second Stage
Hot Gas
Reheat
Mode
Subcooling
Mode
Compressor
2
Hot Gas
Reheat
Mode
Subcooling
Mode
Under Normal Sequence of Operation
Yes
No
On
Yes
No
No
On
No
Yes
Yes
No
On
No
Yes
No
Yes
On
No
Yes
No
Yes
On
No
Yes
LEGEND
OAT
--
Outdoor Air Temperature
NOTE: On a thermostat
call for W1, all cooling and dehumidification
will be off.
SERVICE
8. Reposition the outer coil section, and remove the coil corner post from between the top panel and center post.
9. Reinstall the coil comer post, and replace all screws.
CONDENSATE DRAINCheck and clean each year at
start of cooling season. In winter, protect against freeze-up.
FILTERS -- Clean or replace at stm-tof each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS -- Cle;m screens with
steam or hot water and a mild detergent. Do not use disposable
filters in place of screens.
When servicing unit, shut off all electrical power to unit
and install lockout tag to avoid shock hazard or injury fiom
rotating p_uts.
Cleaning --Inspect the unit interior at the beginning of
each heating and cooling season and as operating conditions
require.
EVAPORATOR COIL
1. Turn unit powel: Install lockout tag. Remove evaporator
coil access panel.
2. If economizer or two-position damper is installed,
remove economizer or two-position damper by disconnecting Molex plug and removing mounting screws. Refer to Accesso U Economizer or Two-Position Damper
Installation Instructions for morn details.
3. Slide flltel.s out of unit.
TOP
PANEL
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canistel: Wash both sides
of coil and flush with clean watel: For best results, backflush toward the return-air section to remove foreign
material.
5. Flush condensate pan after completion.
6. Reinstall economizer or two-position &_mper and filters.
7. Reconnect wiring.
8. Replace access panels.
CONDENSER COIL
REMOVE
SCREWS
\
CONDENSER
FAN
CONTROLBOX
CORNERPOST
REMOVE
SCREWS
COIL CENTER
POST
CONDENSER
COIL
Fig. 53 -- Cleaning
1. Turn off unit powel: Install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 53. To hold
top panel open, place coil corner post between top panel
and center post. See Fig. 54.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 55.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal mannel:
COILCORNER
POST
7. Secure inner and outer coil rows together with a fieldsupplied fastenel:
REMOVE COIL
CORNER POST
Condenser
CENTER
CONDENSER
BAFFLE
Coil
TOP PANEL
COIL
Fig. 54 -- Propping Up Top Panel
47
pressure gage and temperature
sensing device ;ue required.
Connect the pressure gage to the service port on the suction
line. Mount the temperature sensing device on the suction line
and insulate it so that outdoor ambient temperature does not
affect the reading. Indoor-air cfln must be within the normal
operating range of the unit.
HUMIDI-MIZER
TM
ADAPTIVE
DEHUMIDIFICATION
SYSTEMThe system charge for units with the HumidiMiZer adaptive dehumidification
system is greater than that of
the standard unit alone. The charge for units with this option is
indicated on the unit nameplate
drawing. Also refer to
Fig. 61-63. To chmge systems using the Humidi-MiZer
a&tptive dehumidification
system, lhlly evacuate,
recovel: and
rechmge the system to the nmneplate specified charge level. To
check or adjust refrigerant
charge on systems using the
Humidi-MiZer
a&tptive dehumidification
system, charge per
Fig. 61-63.
TOP VIEW
TOP PANEL
CONDENSER
(
,L
II
.,.I I \ L.-
[ t___
[1
..--LL_
INNER COIL
__I"_l
SECTION
CENTER
_
_)
BAFFLE
4'_OUTER
COIL
/,
\CLEAN
SECTION
NOTE: When using the charging charts, it is important that
only the subcooling/reheat
dehumidification
coil liquid line
solenoid valve be energized. The subcooling/reheat
dehumidification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller
jumpered to run the fan at full speed.
The ch;uts reference a liquid pressure (psig) and temperature at a point between the condenser coil and the subcooling/
reheat dehumidification
coil. A tap is provided on the unit to
measure liquid pressure entering the subcooling/reheat
dehumidification coil.
RETURN END
Fig. 55 -- Separating
Coil Sections
Lubrication
COMPRESSORS
-- Each compressor
amount ofoil at the factory.
is charged with correct
FAN MOTOR BEARINGS
-- Fan motor bearings am of the
permanen@ lubHcawd type. No /_u_ther lubrication is wquiwd
No lubrication of condenser
or evaporator
fan motors is
required.
Condenser-Fan
Adjustment
(Fig. 56)
I.
Shut off unit power supply. Install lockout tag.
2.
3.
Remove condenser-fan
assembly (grille, motor,
cover, and fan) and loosen fan hub setscrews.
Adjust fan height as shown in Fig. 56.
4.
Tighten setscrews and replace condenser-fan
3.50
in.
IMPORTANT:
The subcooling
mode charging
charts
(Fig. 61-63) am to be used ONLY with units having the
optional Humidi-MiZer
subcooling option. DO NOT use
standard chmls (Fig. 57-60) for units with Humidi-MiZer
option, and DO NOT use Fig. 61-63 for standard units.
motor
TO USE COOLING
CHARGING
CHART. STANDARD
UNIT -- Take the outdoor ambient temperature and read the
suction pressure gage. Refer to chart to determine what the suction temperature should be. If suction temperature is high, add
refrigerant. If suction temperature
is low. carefully recover
some of the charge. Recheck the suction pressure as charge is
adjusted.
assembly.
__LL_LLLLLLLLLLLLLLLLLU
\J
Example:
z
/
Fig. 56 --
Economizer
Outdoor
Suction
Suction
(Suction
Condenser-Fan
Adjustment
--
Adjustment
Refer to optional
(Fig. 57, Circuit 1)
Temperature ..............................
Pressure ................................
Temperature should be ......................
Temperature may v_u'y _+5 ° E)
85 F
70 psig
48 F
If charging device is used, temperature and pressure readings must be accomplished using the charging charts.
TO USE COOLING
CHARGING
CHART. UNITS WITH
HUMIDI-MIZER
ADAPTIVE DEHUMIDIFICATION
SYSTEM--Refer
to charts (Fig. 61-63) to determine the proper
leaving condenser pressure and temperature.
econo-
mizer section on page 18.
Refrigerant
Charge -- Amount of refrigerant chmge is
listed on unit nameplate (also refer to Table 1). Refer to Carrier
GI'AC2-5 Charging, Recovery. Recycling, and Reclamation
training manu;fl and the following procedures.
Example
(Fig. 61, Circuit 1):
Leaving Condenser
Leaving Condenser
Unit panels must be in place when the unit is operating
during chm'ging procedure.
Pressure .....................
Temperature ...................
300 psig
117 F
NOTE: When using the charging charts, it is important that
only the subcooling/reheat
dehumidification
coil liquid line
solenoid valve be energized. The subcooling/reheat
dehumidification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller
jumpered to run the fan at full speed.
NO CHARGE -- Locate and repair any refrigerant leak. Use
standard evacuating
techniques.
Aller evacuating
system,
weigh in the specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING -- Use Cooling Charging Charts,
Fig. 57-60, vmy refrigerant until the conditions of the charts are
met. Note the chmging charts me different from type normally
used. Charts are based on charging the units to the correct
superheat
for the various operating conditions.
Accurate
48
CIRCUIT NO. 2
iiii
::i:
::!!
iiii
20?
!!!!
llll
4
5/,JCTION
I
5_JCTION
LINE
TEMPERATURE
C° F)
!
16
LINE
TEMPERATURE
SUCTION LINE TEMPERATURE(-F)
]
I
I
!
-1
4
10
16
SUCTION LINE TERPERkTU(_ CoG)
i
I
21
-6
CoC)
Fig. 57 -- Cooling
Charging
Charts, Standard
48HJ008 Units
75E
68;
b_
621
o
CL
J55;
4B:
IiJ
_.z41z
J
z
Q
34E
m
27E
I
-6
30
SUCTION
I
-1
SUCTION
40
50
60
LINE TEMPERATURE ('F)
I
I
I
4
10
16
LINE TEMPERATURE('C)
Fig. 58 -- Cooling Charging
Chart, Standard
49
70
BO
J
21
I
27
48HJ009 Units
!
21
CIRCUIT
NO.1
CIRCUIT NO. 2
??!?
???!
9O
iiii
iiii
::::
::::
iiii
iiii
::;:
iii_
iiiii
i I I_
I L..,I-.-F
!! !? !
!_-.r
::::
::::
4O
3O
!iiii
i
0
I
I
-1
4
10
16
SUCTION LINE TEHPERATURE('C]
I
21
27
Charging
,0
I
I
-6
-1
5UCTI_
Fig. 59 -- Cooling
!!ii
........
Charts, Standard
4
16
LI_TEHPERATURE('_
48HJ012 Units
CIRCUIT NO. 1
CIRCUIT NO, 2
!!!!
6891 10C
10
IIIII
_!?!?
!!!!!
6211 90
i i.,F-]-
u_
•-'4e3130
;;1!
iiii
i=_
iiii
:
:
: "=
;
:
: ="
: :
: ="
:
! !
III[
III:
2071 30
!!!!
i!ii
I
-6
SUCTION
t
-1
LINE
I
4
TENPERATURE
I
10
('F)
16
70
80
I
I
21
27
bg
!
-6
_dCTll
-1
4
10
16
SUCTION LINE TEHPERATUNE
('C)
SUCTION LINE TE,VPERATURE('C)
Fig. 60 -- Cooling Charging
!
Charts, Standard
5O
48HJ014 Units
I
21
I
27
MODE CHARGING
CHART
7,B ]ON - BOHZ
ONLY WHEN COIL IS IN SUBCOOLING
COOLING
COOLING
(APPLICABLE
OUTDOOR
140
2
9 _so
z
FAN MUST
BE
MODE)
(APPI !BAB
MODE CHARGING
CHART
!2,B 70N
BOHZ
} ONLY WIEN ¢0!I 15 ]N UBCOOLING
OUTDOOR
OPERATING
HHHHHHHIq
HHHHHHIq '
FAN
MU51
MBDE)
BE OPERAIING
9
$
13o
o
o
_2o
He
HHHHIeM HH
w
I_O
ioc
i_- 9c
IOC9_
_c
?o
so
i00
150
2oo
PRESSURE AV!NG
lIQUID
25o
soo
CONI]INSER
35o
too
40o
_5o
LIQUID
(PS8)
2oo
PRESSURE LEAVING
25o
CONDENSER
3oo
sso
(PSIG)
NOTE: When using the charging charts, it is important
that only the
subcooling/reheat
dehumidification
coil liquid line solenoid
valve be
energized. The subcooling/reheat
dehumidification
coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed.
NOTE: When using the charging
charts, it is important that only the
subcooling/reheat
dehumidification
coil liquid line solenoid
valve be
energized.
The subcooling/reheat
dehumidification
coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed.
Fig. 61 -- Cooling Charging Chart, 48HJ008
With Optional Humidi-MiZer TM Adaptive
Dehumidification
System
Fig. 63 -- Cooling Charging Chart, 48HJ014
With Optional Humidi-MiZer Adaptive
Dehumidification System
Main Burners
COOLIN6
(APPI CAIIL
8,5
ONLY
ROOE
CI_II_
F. 10 F0N
WHN
COIL 15
OUTDOOR
FAN MUST
-- At tile beginning of each heating season, inspect for deterioration or blockage due to corrosion or
other causes. Observe the main burner flames and adjust if
necessary.
CflART
60HZ
IN BUBCO01
ING MOB
)
BE OPERATING
When working
spuds.
on gas train, do not hit or plug orifice
Flue Gas Passageways
-- To inspect the flue collector box and upper meas of the heat exchanger:
1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air
Blower
section below.
2.
Remove the 5 screws holding the blower housing
vestibule covet
to the
3.
Remove the vestibule cover to inspect the heat exchangec
4.
Clean all surfaces as required using a wire brush.
Combustion-Air
Blower-Clean periodically to assure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodic;ally during heating season. For the
first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency.
I IQUII) PR 5iURE
lEAVING
CONI)ENSVR
To inspect blower wheel remove diaft hood and screen.
Shine a flashlight into opening to inspect wheel. If cleaning is
required, remove motor and wheel as follows:
(PS!G}
NOTE: When using the charging charts, it is important
that only the
subcooling/reheat
dehumidification
coil liquid line solenoid
valve be
energized. The subcooling/reheat
dehumidification
coil liquid line solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed.
1. Slide burner access panel out.
2. Remove the 5 screws that attach induced-diaft
motor
assembly to the vestibule covet
3. The blower wheel can now be cleaned. If additional
cleaning is required, continue with Steps 4 and 5.
4. Remove blower by removing 2 setscrews.
Fig. 62 -- Cooling Charging Chart, 48HJ009,012
With Optional Humidi-MiZer Adaptive
Dehumidification System
51
5. Remove
motorbyremoving
4 screws
thatholdblower
housing
tomounting
plate.
Remove
themotorcooling
fan
byremoving
onesetscrew.
Thenremove
nutsthathold
motortomounting
plate.
6. Toreinstall,
reverse
theprocedure.
Table 26 -- LED Error Code Description*
LED INDICATION
ON
OFF
Limit Switch
-- Remove blower access panel (see Fig. 7).
Limit switch is located on the fan deck.
Burner Ignition
-- Unit is equipped with a direct-spark
ignition 100% lockout system. Integrated Gas Unit Controller
(IGC) is located in the control box (Fig. 12). The [GC contains
a self-diagnostic
LED (light-emitting
diode) that can be
observed through the viewport. During service, refer to the
label on the control box cover or Table 26 for an explanation of
LED error code descriptions.
Flame Sense Fault
4 Flashes
5 Flashes
4 Consecutive
Limit Switch Faults
6 Flashes
Ignition Lockout Fault
Induced-Draft Motor Fault
7 Flashes
Rollout Switch Fault
8 Flashes
Internal Control Fault
9 Flashes
Software Lockout
I
tional
information, to Troubleshooting Tables 27-31 for addiIMPORTANT:Refer
SWITCH
Shut offpowerto
3.
Remove compressor
4.
Slide out burner compartment
5.
Disconnect
6.
Remove wires connected
7.
Remove induced-draft motol: ignitor, and sensor wires at
the Integrated Gas Unit Controller (IGC).
Remove the 2 screws that attach the burner rack to the
vestibule plate.
9.
3 Flashes
gas valve.
2.
10.
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
LED -- Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence,
lqndicates a code that is not an error. The unit will continue to operate when this code is displayed.
If lockout occuLs, unit may be reset by interrupting the
power supply to unit for at least 5 seconds.
REMOVAL
AND REPLACEMENT
OF GAS TRAIN
(See Fig. 64 and 65)
8.
1 Flasht
2 Flashes
LEGEND
A single LED on the Integrated Gas Unit Controller (IGC)
provides a visual display of opemtiomd or sequential problems
when the power supply is uninterrupted. When a break in power occurs, the IGC will be reset (resulting in a loss of fault
history). The ew_porator fan on/off time delay will also be
reset. Refer to Start-Up, Heating section on page 43 for additional information.
1. Shut offmanual
ERROR CODE DESCRIPTION
Normal Operation
Hardware Failure
unit.
access panel.
BURNER
SECTION
side panel.
gas piping at unit gas valve.
FLUE
EXHAUST
to gas valve. MaN each wire.
INDUCED-DRAFT
MOTOR
MOUNTING
PLATE
Remove the gas valve bracket.
Slide the burner tray out of the unit (see Fig. 65).
INDUCED-DRAFT
MOTOR
11. To reinstall, reverse the procedure.
CLEANING
AND ADJUSTMENT
1. Remove burner rack from unit as described in Removed
and Replacement of Gas Train section above.
2.
Inspect burners,
3.
Using a soft brush, clean burners
required.
Fig. 64 -- Burner Section Details
and if dirty, remove burners from rock.
4.
5.
Adjust spmk gap. See Fig. 66.
Reinstall burners on rock.
6.
Reinstall burner rack as described
and crossover
port as
REGULATOR
(LOCATED
ADJUSTMENT
UNDER
METAL
. MANIFOLD
SCREW
PLUG
BUTTON)
PRESSURE
TAP
above.
Replacement Parts
parts may be obtained
request.
-- A complete list of replacement
from your Carrier distributor
upon
GAS
VALVE
BURNERS
Fig. 65 -- Burner Tray Details
52
II
48HJ D008,009
125,000/90,000 BTUH INPUT
SEE
DETAIL
/
48HJD012, 48HJE008,009
180,000/120,000 BTUH INPUT
SEE
DETAIL
48HJF008,009; 48HJE012; 48HJD014
224,000/180,000 BTUH INPUT
48HJ F012; 48HJE014
250,000/200,000 BTUH INPUT
SPARK GAP,120"TO
,140"
_K
GAP .181"
!!-,c C:
DETAIL "C"
Fig. 66 -- Spark Gap Adjustment
53
TROUBLESHOOTING
Unit Troubleshooting-
Refer to Tables 27-32 and
Fig. 67 for unit troubleshooting.
Table 27 -- Cooling
PROBLEM
Compressorand
CondenserFan
Will NotStart.
Compressor Will Not Start
But Condenser Fan Runs.
Compressor Cycles (Other Than
Normally Satisfying Thermostat).
Service Analysis
CAUSE
REMEDY
Power failure.
Call power company.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer, or control relay.
Replace fuse or reset circuit breaker.
Replace component.
Insufficient
Determine cause and correct.
line voltage.
Incorrect or faulty wiring.
Check wiring diagram and rewire correctly.
Thermostat setting too high.
Faulty wiring or loose connections in compressor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective overload.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
One leg of 3-phase power dead.
Replace fuse or reset circuit breaker.
Determine cause.
Refrigerant
Recover refrigerant, evacuate system, and
recharge to nameplate.
overcharge or undercharge.
Defective compressor.
Determine cause and correct.
Defective overload.
Determine cause and replace.
Defective thermostat.
Compressor
Operates Continuously.
Replace thermostat.
Replace.
Locate restriction and remove.
motor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat
Replace filter.
Decrease load or increase unit size.
set too low.
Reset thermostat.
Low refrigerant charge.
Locate leak, repair, and recharge.
Leaking valves in compressor.
Replace compressor.
Air in system.
Recover refrigerant, evacuate system, and
recharge.
Clean coil or remove restriction.
Condenser coil dirty or restricted.
Excessive
Head Pressure.
Dirty air filter.
Replace filter.
Clean coil.
Dirty condenser coil.
Refrigerant overcharged.
Recover excess refrigerant.
Air in system.
Head Pressure Too Low.
Excessive
Suction Pressure.
Suction Pressure Too Low.
Condenser air restricted or air short-cycling.
Recover refrigerant, evacuate system, and
recharge.
Determine cause and correct.
Low refrigerant charge.
Check for leaks, repair, and recharge.
Compressor valves leaking.
Replace compressor.
Remove restriction.
Restriction in liquid tube.
High heat load.
Check for source and eliminate.
Compressor valves leaking.
Replace compressor.
Refrigerant
Recover excess refrigerant.
overcharged.
Dirty air filter.
Replace filter.
Low refrigerant charge.
Metering device or low side restricted.
Check for leaks, repair, and recharge.
Remove source of restriction.
Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if
necessary.
Reset thermostat.
Temperature too low in conditioned
Field-installed filter drier restricted.
Compressor
No. 2 Will Not Run.
Determine cause and replace.
Replace and determine cause.
Determine cause and correct.
Insufficient line voltage.
Blocked condenser.
Faulty condenser-fan
Determine cause. Replace compressor.
Unit in economizer mode.
54
area.
Replace.
Proper operation; no remedy necessary.
Table 28 -- Heating Service Analysis
PROBLEM
Burners Will Not
Ignite.
CAUSE
REMEDY
Misaligned spark electrodes.
Check flame ignition and sensor electrode positioning.
Adjust as needed.
No gas at main burners.
Check gas line for air; purge as necessary. After purging gas line of
air, allow gas to dissipate for at least 5 minutes before attempting to
relight unit.
Check gas valve.
Inadequate
Heating,
Water in gas line.
Drain water and install drip leg to trap water.
No power to furnace.
Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.
Check transformer. Transformers with internal overcurrent protection
require a cool-down period before resetting. Check 24-v circuit
breaker; reset if necessary.
Miswired or loose connections.
Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.
Broken thermostat wires.
Replace thermostat.
Dirty air filter.
Clean or replace filter as necessary.
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input. If too low,
increase manifold pressure, or replace with correct orifices.
Unit undersized for application.
Restricted airflow.
Replace with proper unit or add additional
Blower speed too low.
Install alternate motor, if applicable,
speed.
Limit switch cycles main burners.
Check rotation of blower, thermostat heat anticipator
temperature rise of unit. Adjust as needed.
Too much outdoor air.
Adjust minimum position.
Run continuity check. Replace wires, if necessary.
Check economizer
Poor Flame
Characteristics.
Incomplete combustion
results in:
unit.
Clean filter, replace filter, or remove any restrictions.
(lack of combustion
or adjust pulley to increase fan
settings, and
operation.
air', Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Aldehyde odors, CO, sooting flame, or floating
flame.
Cracked heat exchanger.
Overtired unit -- reduce input, change orifices, or adjust gas line or
manifold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners Will Not
Turn Off.
Unit is locked into Heating mode for a one
minute minimum.
Table 29 -- Humidi-MiZer
TM
Adaptive Dehumidification
PROBLEM
Subcooling
Mode (Liquid
Will Not Energize.
Wait until mandatory one minute time period has elapsed or
power to unit.
CAUSE
Reheat)
No power to control transformer
evaporator-fan
motor.
Capacity,
Loss of Compressor
Superheat
Conditions
with Subcooling/Reheat
Dehumidification
Coil Energized,
valve will not operate.
Liquid line solenoid
valve will not open.
Thermostatic
charge
expansion
or frosted
Check power source and evaporator-fan
wire connections
are tight.
to liquid line
Liquid line solenoid
Low refrigerant
Mode Service Analysis
REMEDY
from
No power from control transformer
solenoid valve.
Low System
System Subcooling
evaporator
valve (TXV).
55
coil.
relay. Ensure
all
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure
switch open. Cycle unit off and allow lowpressure switch to reset. Replace switch if it will not
close.
3. Transformer
bad; check transformer.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck open; replace.
Valve is stuck closed; replace valve.
1. Check charge amount. Charge per Fig. 61-63.
2. Evaporator coil frosted; check and replace lowpressure switch if necessary.
1. Check TXV bulb mounting, and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Table 30 -- Humidi-MiZer
TM
Adaptive Dehumidification
PROBLEM
Hot Gas Reheat Mode Service Analysis
CAUSE
Reheat Mode Will Not Energize.
REMEDY
No power to control transformer from
evaporator-fan motor.
No power from control transformer to hot gas
line solenoid valve.
Check power source and evaporator-fan
wire connections
are tight.
Hot gas line solenoid valve will not operate.
1.
2.
1.
2.
Low refrigerant charge or frosted evaporator coil.
Thermostatic expansion valve (TXV).
Loss of Compressor
Superheat
Conditions
with Subcooling/Reheat
Dehumidification
Coil Energized.
Excessive Superheat,
Liquid line solenoid valve will not operate.
Hot gas line solenoid valve will not close.
relay. Ensure
all
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure
switch open. Cycle unit off and allow lowpressure switch to reset. Replace switch if it will not
close.
3. Transformer
bad; check transformer.
Solenoid coil defective;
replace.
Solenoid valve stuck closed; replace.
Check charge amount. Charge per Fig. 61-63.
Evaporator coil frosted; check and replace lowpressure switch if necessary.
1. Check TXV bulb mounting, and secure
tion line.
2. Replace TXV if stuck open or closed.
Valve is stuck; replace valve.
Valve is stuck;
replace
tightly to suc-
valve.
Table 31 -- LED Error Code Service Analysis
SYMPTOM
CAUSE
REMEDY
Hardware Failure.
(LED OFF)
Loss of power to control module (IGC).
Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Limit Switch Fault.
(LED 2 flashes)
High temperature
Check the operation of the evaporator-fan motor. Ensure that the
supply-air temperature rise is in accordance with the range on the
unit nameplate.
Flame Sense Fault.
(LED 3 flashes)
The IGC sensed flame that should not be Reset unit. If problem persists, replace control board.
)resent.
4 Consecutive Limit
(LED 4 flashes)
Switch Trips.
Ignition Lockout.
(LED 5 flashes)
Inadequate airflow to unit.
Unit unsuccessfully
15 minutes.
Induced-Draft
Motor
(LED 6 flashes)
Check operation of evaporator-fan motor and that supply-air temperature rise agrees with range on unit nameplate information.
attempted ignition for Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly terminated. Verify that unit is obtaining proper amount of gas.
IGC does not sense that induced-draft
motor is operating,
Check for proper voltage. If motor is operating, check the speed
sensor plug/IGC Terminal J2 connection. Proper connection: PIN
1-- White, PIN 2 -- Red, PIN 3 -- Black.
Rollout Switch Fault.
(LED 7 flashes)
Rollout switch has opened.
Rollout switch will automatically reset, but IGC will continue to
lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft. Reset unit
at unit disconnect.
Internal Control
(LED 8 flashes)
Microprocessor has sensed an error in
the software or hardware.
If error code is not cleared by resetting unit power, replace the
IGC.
Microprocessor has sensed an error in
the redundant software comparison.
If error code is not cleared by resetting unit power, replace the
IGC.
Internal Software
(LED 9 flashes)
Fault.
limit switch is open.
Fault.
Fault.
LEGEND
IGC
LED
---
Integrated Gas Unit Controller
Light-Emitting Diode
If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling
new control board. The IGC is sensitive to static electricity and
may be damaged if the necessary precautions are not taken.
I additional
IMPORTANT:
heating
Refersection
to Table
troubleshooting
28 -- Heatinginformation.
Service Analysis for I
56
NOTES:
1. If any of the original wire furnished
must be
replaced, it must be replaced with type 90 C wire
or its equivalent.
2. Three phase motors are protected under primary
single phasing conditions.
3. Use copper conductors only.
4. TRAN is wired for 230 v unit. If unit is to be run with
208 v power supply, disconnect
BLK wire from
230 v tap (ORN) and connect to 208 v tap (RED).
Insulate end of 230 v tap.
I
_ONNECTIOB
BOARD
0FC
_CONNECTION
BOARD
_0FC
I_C
:::
.VlO-.VIO--
LB Bi:
L
SVR
_lh
i
I
•_@
O,
GRN/YEL_
--BRr]
I
6
"_I.
BRN--
GRN/YEL._I.
GROUNBED
THRU STANDOFF
TRAN
_'IFC
CONNECTION
BOARD
Outdoor Fan Motor
Plug
Plug Assembly
Quadruple Terminal
Rollout Switch
Supply Air Temperature
Transformer
Sensor
Field Splice
[]
ml
c2
Marked Wire
Terminal (Marked)
TRAN
Terminal (Unmarked)
BOARB
COMPONENT
C
CAP
CB
CLO
COMP
EQUIP
FPT
GND
HPS
HS
-----------
Terminal Block
ARRANGEMENT
Contactor, Compressor
Capacitor
Circuit Breaker
Compressor Lockout
Compressor Motor
Equipment
Freeze Up Protection Thermostat
Ground
High-Pressure
Switch
Hall-Effect Sensor
LEGEND
Splice
I
IDM
IFC
IFM
IFMOVL
IGC
LPS
LS
MGV
OFC
Fig. 67 i
-----------
Ignitor
Induced-Draft
Motor
Indoor Fan Contactor
Indoor Fan Motor
Indoor Fan Motor Overload Switch
Integrated Gas Unit Controller
Low-Pressure
Switch
Limit Switch
Main Gas Valve
Outdoor Fan Contactor
Typical Schematic
57
(208/230-3-60
Splice (Marked)
--
Factory Wiring
....
Field Control Wiring
Field Power Wiring
--
- --
Accessory
or Optional
Wiring
To indicate cortlmon potential
not to represent wiring.
Shown)
only;
EconoMiSer
IV Troubleshooting
-- See Table 32
for EconoMi$er IV logic.
A functional view of the EconoMi$er
IV is shown in
Fig. 68. Typic:d settings, sensor ranges, and jumper positions
are also shown. An EconoMi$er IV simulator program is available fiom Carrier to help with EconoMi$er
W muning and
troubleshooting.
ECONOMI$ER
IV PREPARATION
-- This procedure
is
used to prepare the EconoMi$er
IV for troubleshooting.
No
troubleshooting or testing is done by performing the following
procedme.
3.
Connect a 9-v battery to AQ (positive node) and AQl
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should chive to between 90
and 95% open.
4.
Turn the Exhaust potentiometer
CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately
9 v. The actuator should
drive fully closed.
5.
NOTE: This procedure requires a 9-v battely, 1.2 kilo-ohm
resistol: and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
6.
IMPORTANT: Be sure to record the positions of all poten- ]
tiometers before starting troubleshooting.
Turn the DCV and Exhaust potentiometers
CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns on.
7.
Return EconoMi$er
IV settings and wiring to normal
after completing troubleshooting.
DCV MINIMUM AND MAXIMUM POSITION -- To check
the DCV minimum and maximum position:
1
1. Disconnect power at TR and TRI. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and PI.
1. Make sure EconoMiSer
been performed.
IV prep_uation
procedure
has
3.
4.
Jumper P to PI.
Disconnect wires at T and TI. Place 5.6 kilo-ohm resistor
across T and TI.
2.
Connect a 9-v battery to AQ (positive node) and AQI
(negative node). The DCV LED should turn on. The
actuator should chive to between 90 and 95% open.
5.
Jumper TR to 1.
3.
6.
7.
Jumper TR to N.
If connected, remove sensor from terminals So and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals So and +.
Put 620-ohm resistor across terminals SR and +.
4.
Set minimum
potentiometers
Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80%
open.
Turn the DCV Maximum Position potentiometer to lhlly
CCW. The actuator should drive fully closed.
Turn the Minimum Position potentiometer
to midpoint.
The actuator should chive to between 20 and 80% open.
6.
Tnrn the Minimum Position Potentiometer
actuator should drive fully open.
7.
Remove the jumper from TR and N. The actuator
drive fully closed.
8.
Return EconoMiSer IV settings
after completing troubleshooting.
8.
9.
10.
position, DCV set point, and
fully CCW (counterclockwise).
Set DCV maximum
(clockwise).
11. Set enthalpy
position
potentiometer
potentiometer
5.
exhaust
fully CW
to D.
12. Apply power (24 vac) to terminals TR and TRI.
DIFFERENTIAL
ENTHALPY-To check
differential
enthalpy:
1. Make sure EconoMiSer
IV preparation procedure has
been performed.
2. Place 620-ohm resistor across So and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
4.
Remove 620-ohm resistor
Cool LED should turn off.
across
5.
Return EconoMiSer
IV settings
after completing troubleshooting.
and wiring
4.
Set the enth_dpy potentiometer
Cool LED should turn off.
and wiring
DCV (Demand
Controlled
Ventilation)
AND
EXHAUST -- To check DCV and Power Exhaust:
1. Make sure EconoMiSer
been performed.
2.
2.
3.
IV preparation
to norm_d
-- To check supply-air input:
IV prepmation
procedure
has
Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
Remove the 5.6 kilo-ohm lesistor and jumper T to TI.
The actuator should chive lhlly open.
Remove the jumper across T and TI. The actuator should
drive fully closed.
5. Return EconoMiSer IV settings and wiring to norm;d
after completing troubleshooting.
ECONOMISER
IV TROUBLESHOOTING
COMPLETION -- This procedure is used to return the EconoMiSer IV
to operation. No troubleshooting or testing is done by performing the following procedure.
has
The
1. Disconnect
to normal
2.
3.
POWER
4.
procedure
and wiring
should
4.
to normal
to D (fully CW). The Free
Return EconoMiSer
IV settings
after completing troubleshooting.
INPUT
1. Make sure EconoMi$er
been performed.
So and +. The Free
SINGLE ENTHALPY
-- To check single enthalpy:
1. Make sure EconoMiSer
IV preparation procedure
been performed.
2. Set the enthalpy potentiometer
to A (fully CCW).
Free Cool LED should be lit.
3.
SUPPLY-AIR
lhlly CW. The
has
5.
6.
Ensure terminals AQ and AQI _ue open. The LED for
both DCV and Exhaust should be off. The actuator
should be lhlly closed.
+.
58
power at TR and TRI.
Set enthalpy potentiometer to previous setting.
Set DCV maximum position potentiometer
to previous
setting.
Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
Remove 620-ohm resistor from terminals SR and +.
Remove 1.2 kilo-ohm checkout resistor from terminals
So and +. If used, reconnect sensor from terminals So and
7. Remove jumper flom TR to N.
8. Remove jumper fiom TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and TI. Reconnect
wiles tit T and TI.
l 0.
Remove jumper
PI.
11. Apply power (24 vac) to terminals
Table 32 -- EconoMi$er IV Input/Output
Below set
(DCV LED Off)
Above set
(DCV LED On)
device a P and
TR and TRI.
Logic
INPUTS
Demand Control
Ventilation (DCV)
fiom P to Pl. Reconnect
OUTPUTS
Enthalpy*
Outdoor
Return
High
(Free Cooling LED Off)
Low
Low
(Free Cooling LED On)
High
High
(Free Cooling LED Off)
Low
Low
(Free Cooling LED On)
N Terminal1-
Compressor
High
*For single enthalpy control, the module compares
enthalpy to the ABCD set point.
1-Power at N terminal determines Occupied/Unoccupied
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
1-1-Modulation is based on the DCV signal.
Y1
Y2
Stage
1
Stage
2
On
On
On
On
On
Off
On
Off
Off
Off
Off
Off
On
On
On
Off
On
Off
Off
Off
On
On
On
Off
Off
Occupied
Unoccupied
Damper
Minimum position
Closed
Off
Off
Modulating** (between min.
3osition and full-open)
Modulating** (between
closed and full-open)
Off
Off
Minimum position
Closed
On
On
On
Off
Modulating1-1- (between rain.
3osition and DCV maximum)
Off
Off
Off
Modulating1-1- (between
closed and DCV
maximum)
On
On
On
Off
On
Off
Off
Off
Modulating***
Modulating1-1-1-
Off
Off
Off
Off
***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum
position (DCV) or fully open (supply-air signal).
I-I-I-Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV)
or fully open (supply-air signal).
outdoor
setting:
Fig. 68 -- EconoMi$er IV Functional View
59
INDEX
Access panels
18
Altitude compensation
43
Barometric flow capacity
21
Burner ignition
.52
Burner rack
.52
Burner section
.52
Burner spark gap
53
Carrier Comfort Network
15
ChaNing chart, refrigerant
Clearance
4
CO, sensor
Configuration
25
Settings
23, 25
Combustion blower wheel
Compressor
Lubrication
48
Mounting
Rotation
Condensate
Cleaning
Location
Condenser
Cle_ming
Condenser
49-51
51
42
42
drain
47
2, 4
coil
7
47
fan
7
Adjustment
48
Control circuit
Wiring
9
Wiring raceway
10
Convenience outlet
14
Demand control ventilation
24
Dehumidification
25
Dimensions
3, 6
Ductwork
2
EconoMi$er2
18-20
4 to 20 mA control
20
EconoMi$er IV
18-2.5, 57, 58
Adjustment
48
Components
18
Control mode
21
Damper movement
24
Dry bulb changeover
21
Wiring
20
Electrical connections
9
Electrical data
12, 13
Enthalpy changeover set points
Enthalpy sensor
17
Evaporator coil
7
Cleaning
47
Evaporator fan motor
Lubrication
48
Motor data
27
Performance
28-41
23
Pulley adjustment
26
Pnlley setting
Z 27
Speed
7
Factory-installed
options
Convenience outlet
14
EconoMi$er IV
18-25
EconoMi$er2
18-20
Humidistat
11
Manual outdoor air damper
14
Novar controls
14
PremierLink TM controls
15-17
Filter
Cleaning
Installation
Size
8
47
19
Flue gas passageways
51
Flue hood
4,8
Freeze protection thermostat
Gas connection
8
8
Horizontal units 1, 2
Humidi-MiZer TM adaptive dehumidification
system
10, 11,26, 46, 47, 51, .5.5,56
Humidistat
11
Indoor air quality sensor
15, 22
Integrated gas controller 56
Error codes .52,56
Leak test 42
Limit switch 52
Liquid propane
8
Low pressure switch
8
Main burners
43, 51
Manual outdoor air damper
14
Mounting
Compressor
42
Unit 4
Natural gas 8
Novar controls
14
Operating limits 2
Operating sequence
43-47
Cooling
43
EconoMi$er2
44
EconoMiSer IV 44-46
Heating 43
Humidi-MiZer system 46,47
Outdoor air hood 14, 19
Outdoor air inlet screens 42, 47
Outdoor air temperature sensor 15, 19
Physical data 7, 8
Potentiometers
22
Power supply 9
Wiring 9
PremierLink controls
15-17
Pressure, drop
EconoMi$er IV 27
EconoMi$er2
27
Humidi-MiZer system 26
Pre-Start-Up
42
Pressure switches
High pressure 8
Low pressure
8
Refrigerant
Charge 7, 48
Type 7
Refrigerant selwice ports 42
Replacement parts .52
Return air filter 8, 42
Return-air temperature sensor 22
Rigging unit 4, 5
Roof curb
Assembly
1
Dimensions
3
Connector package 3
Leveling tolerances
4
Weight
7
Safety considerations
1
Safety relief 43
Sel_.'ice 47-53
Selwice ports 42
Slab mount 2
Start-up 42-47
Start-up checklist
CL-I
Supply-air temperature sensor
1.5,19
Thermostat
9, 10
Troubleshooting
.54-59
EconoMiSer IV unit 5Z .58
Ventilation 43
Weight
Comer
6
EconoMi$er IV 6, 7
Unit 5-7
Gas input
8
Gas piping
4, 8, 42
Gas pressure
1,8
Heat anticipator settings
8, 10
Heat exchanger
8
High flow valves
42
High pressure switch
8
6O
Wiring
4 to 20 mA control
20
Differential enthalpy
17
EconoMiSer2
20
EconoMiSer IV
20
Humidistat
11
Power connections
9
PremierLink control
10, 17
Thermostat
10
Unit
59
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications
Catalog No. 04-53480012-01
Printed in U.S.A.
or designs without notice and without incurring obligations.
Form 48HJ-32SI
Pg 62
9-05
Replaces:
48HJ-28SI
START-UP
(Remove
I. PRELIMINARY
MODEL
CHECKLIST
and Store in Job File)
INFORMATION
NO.:
SERIAL
DATE:
NO.:
TECHNICIAN:
II. PRE-START-UP
(insert
checkmark
VOLTAGE
in box as each item is completed)
[]
VERIFY
THAT JOBSITE
[]
VERIFY
THAT ALL PACKING
[]
REMOVE
[]
VERIFY
[]
CHECK ALL ELECTRICAL
[]
CHECK GAS PIPING FOR LEAKS
[]
CHECK THAT RETURN
[]
VERIFY
[]
CHECK FAN WHEELS
[]
CHECK TO ENSURE THAT ELECTRICAL
OR SHARP METAL EDGES
ALL SHIPPING
AGREES WITH VOLTAGE
MATERIALS
HOLDDOWN
THAT CONDENSATE
LISTED ON RATING PLATE
HAVE BEEN REMOVED
BOLTS AND BRACKETS
CONNECTION
CONNECTIONS
FROM UNIT
PER INSTALLATION
IS INSTALLED
PER INSTALLATION
AND TERMINALS
FOR TIGHTNESS
INSTRUCTIONS
INSTRUCTIONS
LU
2:
m
(INDOOR)
AIR FILTERS ARE CLEAN
AND IN PLACE
d3
LU
THAT UNIT INSTALLATION
I--
IS LEVEL
AND PROPELLER
FOR LOCATION
IN HOUSING/ORIFICE
AND SETSCREW
TIGHTNESS
rm
Z
[]
III.
CHECK PULLEY
ALIGNMENT
WIRING
IS NOT IN CONTACT
WITH REFRIGERANT
o,
LINES
<
I-
AND BELT TENSION
PER INSTALLATION
o
INSTRUCTIONS
START-UP
ELECTRICAL
SUPPLY VOLTAGE
L l -L2
L2-L3
L3-L 1
COMPRESSOR
AMPS
LI
L2
L3
COMPRESSOR
AMPS
LI
L2
L3
LI
L2
L3
INDOOR-FAN
AMPS
TEMPERATURES
LU
2:
m
OUTDOOR-AIR
RETURN-AIR
COOLING
TEMPERATURE
DB
TEMPERATURE
SUPPLY
GAS HEAT SUPPLY
rm
LU
DB
AIR
AIR
I--
WB
DB
d3
DB
Z
o,
<
I-
PRESSURES
o
IN. WG
IN. WG
PSIG
PSIG
GAS INLET PRESSURE
GAS MANIFOLD
PRESSURE
REFRIGERANT
SUCTION
REFRIGERANT
DISCHARGE
[]
VERIFY
REFRIGERANT
CHARGE
[]
VERIFY
THAT 3-PHASE SCROLL
CIRCUIT NO. l
CIRCUIT NO. l
USING CHARGING
COMPRESSOR
PSIG
CIRCUIT
NO. 2
PSIG
PSIG
CIRCUIT
NO. 2
PSIG
TABLES
ROTATING
IN CORRECT
DIRECTION
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications
Catalog No, 04-53480012-01
Printed in U.S,A,
or designs without notice and without incurring obligations.
Form 48HJ-32SI
Pg CL-1
9-05
Replaces:
48HJ-28SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 62 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 12:44:25 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools