CARRIER Package Units(both Units Combined) Manual L0520548
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF
.
Page Count: 61
| Download | |
| Open PDF In Browser | View PDF |
Single-Package
50TFF004-007
50TM004-007
Rooftop Cooling Units
Installation, Start-Up and
Service Instructions
CONTENTS
SAFETY CONSIDERATIONS
.........................
INSTALLATION
...................................
Step 1 -- Provide Unit Support ......................
• ROOF CURB
• SLAB MOUNT
• ALTERNATE UNIT SUPPORT
Step 2 -- Field Fabricate Ductwork ..................
Step 3 -- Install External Trap for
Condensate Drain .................................
Step 4 -- Rig and Place Unit .........................
• POSITIONING
Step 5 -- Make Electrical Connections
..............
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 6Adjust Factory-Installed
Options .........
• MANUAL OUTDOOR-AIR
DAMPER
• CONVENIENCE
OUTLET
• NOVAR CONTROLS
• PREMIERLINK TM CONTROL
• OPTIONAL ECONOMI$ER
IV AND ECONOMI$ER2
• ECONOMI$ER IV STANDARD SENSORS
• ECONOMI$ER IV CONTROL MODES
Step 7 -- Adjust Evaporator-Fan
Speed ............
• DIRECT-DRIVE
MOTORS
• BELT-DRIVE MOTORS
PRE-START-UP .....................................
START-UP .......................................
SERVICE ........................................
TROUBLESHOOTING
............................
INDEX ..............................................
START-UP CHECKLIST
..........................
SAFETY
Page
1
1-47
l
2
2
4
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag on disconnect. Ensure voltage listed on unit &Lta plate
agrees with electrical supply provided for the unit. Electrical shock could cause serious personal injury.
INSTALLATION
9
19
Unit is shipped in the vertical dischguge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the
insulation-side down. Seals around duct openings must be
tight. See Fig. 1.
Step 1 -- Provide
31
48
48-50
51-54
55-58
59
CL-l
Untrained personnel can pedorm basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on ah-conditioning
equipment, observe precautions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
IMPORTANT: The gasketing of
is critical for a watertight seal.
with the roof curb as shown
applied gasket can _dso result in
pedbrmance.
Printed in U,SA.
the unit to the roof curb
Install gasket supplied
in Fig. 2. Improperly
air leaks and poor unit
Curb should be level. This is necessary for unit drain to
function properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation
Instructions
for
additional infomtation as required.
reserves the right to discontinue, or change at any time, specifications
Catalog No. 04-53500010-01
Unit Support
ROOF CURB -- Assemble and install accesso U roof curb in
accor&mce with instructions shipped with curb. See Fig. 2.
Install insulation, cant strips, roofing felt, and counter flashing
as shown. Ductwork must be attached to curb, not to unit.
If electric or control power is to be routed through rite basepan,
attach the accessory thru-the-bottom
service connections to the
basepan in accor&mce with the accessory installation instructions. Connection must be installed b@re unit is set on roof
(_rb.
CONSIDERATIONS
Installation and servicing ah-conditioning
equipment can be
hazardous due to system pressure and electrical components.
Only tlained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Manufacturer
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for _dl brazing operations.
or designs
Form 50T-5SI
without notice and without incurring obligations.
Pg 1
9-05
Replaces:
50T-3SI
SLAB MOUNT (Horizontal
Units Only) -- Provide a level
conclete slab that extends a minimum of 6 in. beyond unit
cabinet. [nst_dl a gravel apron in front of condenser coil air
inlet to prevent grass and foliage from obstructing airflow.
not exceed 0.35 in. wg with economizer
economizel:
Step 3 --
-- The unit's 3/4-in. condensate drain connections are
located at the bottom and side of the unit. Unit discharge
connections do not determine the use of &'ain connections;
either drain connection can be used with vertical or horizont;fl
applications.
When using the standard side drain connection, make sure
the red plug in the alternate bottom connection is tight before
inst;dling the unit.
To use the bottom drain connection for a roof curb installation, lelocate the factory-installed
red plug from the bottom
connection to file side connection. See Fig. 4. The piping for
the condensate drain and external trap can be completed after
the unit is in place. Tile center drain plug looks like a star
connection, howevek it can be removed with a l/2-in, socket
drive extension.
Step 2 --
Field Fabricate Ductwork -- Secure _fll
ducts to roof curb and building structure on vertical discharge
units. Do not connect dm_'ork
to unit. For horizontal applications, field-supplied flanges should be attached to horizontal
discharge openings and all ductwork should be attached to the
flanges. Insulate and weatherproof
all extern_d ductwork,
joints, and roof openings with counter flashing and mastic in
accor&mce with applicable codes.
space
must
All units must have an extern;d trap for condensate drainage. Install a trap at least 4 in. deep and protect against freezeup. If drain line is installed downsneam from the external trap,
pitch the line away from the unit at 1 in. per 10 fl of run. Do not
use a pipe size sm;dler than the unit connection (3/4-in.). See
Fig. 5.
be
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not requiled around ductwoN.
Cabinet return-air static pressure (a negative condition) should
REMOVABLE
HORIZONTAL
,,,,,,%
RETURN DUCT OPENING COVER
\
\
\
\
\
\
\
\
___
Trap for Condensate
Drain
NOTE: Horizontal units may be installed on a roof curb if
required.
ALTERNATE UNIT SUPPORT -- When
file
curb
or
a&_pter cannot be used, support the unit with sleepers using the
curb or adapter support area. If sleepel.s ctmnot be used, suppoll the long sides of the unit with a minimum of 3 equally
spaced 4-in. x 4-in. pads on each side.
Ducts passing through an unconditioned
insulated and covered with a vapor b_uriel:
Install External
or 0.45 in. wg without
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
Fig. 1 -- Horizontal Conversion Panels
,
CONNECTOR
PKG. ACCY,
t
t
B
"C'RB-T_IP-W-R0-01"A_'11
"C-_'T_IP-W-R6-'O_'A_'I 1
CRBTMPWROO3A01
.........
CRBTMPWROO4A01
I
4
I
_'T 7
t
t
C
DRAIN
HOLE
-,
I
I
GAS
........
r
t
t
POWER
t CONTROL
t
I - "s/_,-I-_/_, [19] N-P_ r ....
I [19] NPT r _1_4,,T3£7 z i
I
I
1 -9 /16 1 -4
[551]
I [406]
"
" I"
"
I
1 /4
[44,5]
-RBo-P_tT_- "
ACCESSORY
IACCESSORY
I
PWR
s
-
i
[12.7]
NPT
I
I
I
[12,7]
NPT
II
7. I_
1
I
C
/
\
/
I
t
\
\
J
\\
I
i
I
I
I
\
I
/
\
r.r4
,L'b-
/
I
t
',___1
/
_
1
I
I
/
i
i
I
I
t
I
1
I
I
(SUPPLIED
WITH
I
TYPICAL
(FIELD
BUPPL]ED)
DUCT
[FIELD
I
CANT
1
I
1
I
I
I
1
I
1
I
1
BUPPLY
AIR
I
I
OPENING
I
1_
T
O 7/1B"
Ell]
HEADS)
7[504_,
13/1BB3_J
1"1
5IDES
2"
FLASHING
SUPPLIED)
BTRIP
BUPPL]ED)
(FIELD
MATERIAL
BUPPLIED)
7 518"
[8
I
I
RIGID INSULATION
(FIELD SUPPLIED)
I
I
O"
11'
(4)
I
C
I
Direction of airflow.
FELT
SUPPLIED)
[FIELD
1
J
I
O"
50TFF, TM
004-007
O" 7116"
I
[BOLT
I- L356]_1
2'@"
LI [_610---
CURB)
I
1" 1 7/15"
]41]
UNIT SIZE
8. Connector packages CRBTMPWROO1A01
and
002A01 are for thru-the-curb type gas. Packages
CRBTMPWROO3A01
and 004A01 are for thruthe-bottom type gas connections.
1
I
B"
783
i
1
I
3"
?B]
-'
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance: 4 ft on each side.
C
I
A
CRRFCURB001A01 tI" ___.-I,
CRRFCURBOO2A01
/2•1
3
I [12 7] NPT I /4" 19 NPT I
I- -'_
_ - 4, ......
I
I lOl/_lPT I 11/4•'[31.7]
I
t
[334]liB"
(BOLT
0 ?/1B"
[11]
HEADS)
OPEN(NO FOR BASEPAN ENTRY
SERVICE (SEE NOTE #8)
0' 2 1/2"
•
A
•
[7B]
0"
O 7/1B"
A
B" O"
[914]
O"
HEADS)
[11]
LT
O 7/1B"
•
E._ _A
[BOLT
I
•
O" 3 1/4"
[83]
SEE NOTE _2
t
GAB BERV[CE
PLATE
[BEE NOTE
I
•
O"
O 1/4"E7]
@
1"
4
13/1B"
6"
[152]
[INSIDE)
[427]
(]NB]DE)
I
q',l_
l/1B"
q,
O'
4 9/16"
[115.5]
1
t
I
I
I
SUPPLY
AIR
VIEW
RETURN
TYP
2 3/B °
[B1]
AIR _
"A-A"
I
I
I
I
I
HEAD OF BOLT TO BE ON
INS(DE
OF FLANGE
O" 1"
[25]
5" 7 liB"
[1705]
I
3'
J
[TYP.
VIEW
"B"
ALL CORNERS)
O 15115"
[93B]
SEE VIEW "P_S,ql-
Fig. 2 -- Roof Curb Details
NOTE:
CAMBRIBGEPORT
"SURE
IS
LOCK"
FASTENING
DEVICE
ALTERNATE
CONSTRUCTION.
CORNER
ACCEPTABLE
MINIMUM PITCH
TI
ONE IN. PER
c
IMUM
I_"""
I
I/
/
o5
I
I
--
__
//]1
....
(in.)
I A-O
10
I_],
OPEN
2'M,N
I I]
,0PTOPL,
NE\
ALLOWABLE
DIFFERENCE
A-BI
_ I
BASE
TO ROOF
DRAIN
1.0
Fig. 3 -- Unit Leveling Tolerances
SEE
NOTE
_L_
ROOF
CURB
DRAIN PLUG
NOTE: Trap should
be deep enough to offset
difference.
A 4-in. trap is recommended.
Fig. 5 -- Condensate
maximum
Drain Piping
unit static
Details
Lifting holes are provided in base rails as shown in Fig. 7A
and 7B. Refer to rigging instructions on unit.
HORIZONTAL
DRAIN OUTLET
All panels must be in place when rigging. Unit is not
designed for handling by fork truck. Dmnage to unit may
result.
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 -- Condensate
Step 4 -transportation
Rig and Place Unit-&unage.
POSITIONING
-- Maintain cletuance around and above unit
to provide proper airflow and service access. See Fig. 7A and
7B. A properly positioned unit will have the following clearances: l/4-in, cletuance between roof curb and base nfils on
each side and duct end of unit; l/4-in, clearance between roof
curb and condenser coil end of unit. (See Fig. 2, section C-C.)
Do not install unit in an indoor location. Do not locate
unit air inlets near exhaust vents or other sources of contaminated all:
Drain Pan (Side View)
File any
claim
Inspect unit for
with transpom_tion
agency. Keep unit upright and do not drop, Spreader bars are
not required if top crating is left on unit. Rollel_ may be used to
move unit across a roof. Level by using unit fi_lme as a refer-
Although unit is weatherproof,
higher level runoff and overhangs.
ence. See Tables IA and IB and Fig. 6 for additional information, Operating weight is shown in Tables IA and IB and
Fig. 7A and 7B.
POSITION
"- 54"
(914.1371)
BEFORE
After unit is in position,
crating.
ALL SEAL STRIPS
INSTALLING
AS CLOSE TO THIS
guard against
water from
remove shipping materials
and top
IN PLACE
UNIT ON ROOF CURB
DETAIL "A"
END AS POSSIBLE.
BEE T BBOT
,,
NO
-C _
NOTES:
1. Dimension in ( ) is in millimeters,
2, Hook rigging shackles through holes in base rail, as shown in detail "A,"
Holes in base rails are centered around the unit center of gravity. Use
wooden top skid when rigging to prevent rigging straps from damaging unit.
3, Weights do not include economizer, See Tables 1A and 1B for economizer
weights,
UNIT
SIZE
MAX
WEIGHT
"A ....
DIMENSIONS
B ....
C"
50TFF, TM004
Ib
415
kg
188
in,
73.69
mm
1872
in.
35.00
mm
889
in,
33,35
mm
847
50TFF, TM005
50TFF, TM006
50TFF007
50TM007
425
445
520
570
193
202
236
259
73.69
73.69
1872
1872
35,00
35.00
889
889
33,35
33,35
847
847
73.69
73.69
1872
1872
35.00
35.00
889
889
33,35
33,35
847
847
All panels must be in place when rigging. Unit is not designed for handling
by fork truck. Damage to unit may result.
Fig. 6 -- Rigging Details
STD.
UNiT
WEIGHT
LB
KO
UNiT
ECONOM[$ER[V
WEIGHT
LB
KO
VERT.
ECON IV
(A)
_/ PIEI WEIGHT CORNER
WEIGHT
LB
KG
LB
KG
(B)
CORNER
LB
WEIGHT
KO
CORNER
LB
(C)
WEIGHT
KO
CORNER
LB
(D3
WEIGHT
KG
PANEL
50T
004
365
1SSI8
126
57.2
89
40.4
111
50.3
39
17.7
I'
IO
3/B"
50T
005
375
170.1
128
58.1
90
40.8
114
51.7
43
19.5
I'
10
3/8"
SOT
008
395
179.2
132
59.9
94
42.5
120
54.4
49
22.2
0
3/8"
50TFFO07
470
50
22.7
90
40.9
213.2
148
57.1
103
45.7
155
70.3
B4
29.0
I"
l'
0
BOTTOM
POWER
CHART=
THESE
HOLE5
REQ'D
FOR USE
WiTH
ACCESSORY
PACKAGES
CRBTMPWROOIA01,
2A01
"A"
LENGTH
3/8"
E5BB.O]
[588.0]
DIMENSIONS
2.
I_CENTER
3.
IN
OF
[
]
ARE
IN
OUTSIDE
MILLIMETERS.
REAR
OF
AIR
3"
FLOW.
AIR
3/4"
1 1/4"
8
FOR
[
DUCTWORK
TO BE ATTACHED
FOR HORIZONTAL
DISCHARGE
SHOULD
BE ATTACHED
TO
AND ALL DUCTWORK
SHOULD
MINIMUM
CLEARANCE
(LOCAL
CODES
OR JURISDICTION
MAY
PREVAIL]=
a. BOTTOM
OF UNiT
TO COMBUSTIBLE
SURFACES
(WHEN
NOT USING
CURB)
I INCH.
BOTTOM
OF BASE
RAiL
TO COMBUSTIBLE
SURFACED
(WHEN
NOT USING
CURB)
0 INCHED.
d.
e.
fI
9"
ONE SIDE,
12 INCHES
THE
OTHER.
THE SIDE
GETTING
GREATER
OPTIONAL,
CONDENSER CLEARANCE
COIL,
FOR iS PROPER
AIR FLOW,
35 iNCHED
OVERHEAD,
60 INCHES
TO ASSURE
PROPER
CONDENSER
POWER
WITH
THE EXCEPTION
COIL
AS STATED
iN
AND c,
A REMOVABLE
CLEARANCE.
7.
UNITS
MAY
BE
B.
THE
THE
3/4"
DEPENDING
A,
VERTICAL
CENTER OF
BOTTOM OF THE BASE
B,
COMBUSTIBLE
OR C
ROOF
GRAVITY
RAIL.
iS
FLOORS
O"
ON
1'
4
UP
THE
ECONOMISER
I_LEFT
SEE
NOTE
_
/
_]
E
O0
_0'
\
I
RETURN
AIR OPENING
VERTICAL
I
I
3 3/16"
[81 ]
O" 10 115/15"
[27B]
VIEW
_
O"
RETURN
/
I
5 3/8"
3'
B"
[I144]
[I 37]
RIGHT
1/2"
FROM
CORNER
"D _
"D"
387113Z18"
'(21LI]
B"
TYP
B/1 B"
AIR
/
BOTTOM
OF UNIT
3' [1045]
5 BZ1S'_
EBB] LEFT
SIZE.
"B_
COIL
B B/1B"
EB4B.B]
PANEL
FILTERS)
1' 5 1/4 _ [43B]
FOR ECONOM[$ER IV
[G22]
i_0'
ACCESS
BLOCKOFF
A
LOCAT BN
CONDENSER
.
WIRE
#8_
I
/SID
IV HOOD
CORNER
8
CORNER
.
FILTER
1/4"
1/2"
MATERIAL
5"[457]
1
COIL
\
MADE
COVERING
OR
_[114]
\
2'
ON
ELECTRICAL
D I SCONNECT
2"
POWER r
EITHER
OF THE CLEARANCE
FOR THE CONDENSER
NOTE #5o,
b,
FENCE
OR BARRICADE
REQUIRES
NO
INSTALLED
FROM WOOD OR CLASS
iF SET ON BASERAIL.
(001)
(002)
EXHAUST
1 1/2"_
COMPRESSOR
ACCESS
COVER
CORNER
"A"
FAN
BETWEEN
UNITS,
CONTROL
BOX SIDE,
42 IN.
PER NEC.
BETWEEN
AND UNGROUNDED
BURFACEB,
CONTROL
BOX
OPERATION. UNIT
BIDE,
38 IN.
PER NEC.
BETWEEN
UNIT
AND BLOCK OR CONCRETE
WALLS
AND OTHER
GROUNDED
SURFACES,
CONTROL
BOX SIDE,
42 iN.
PER NEC.
HORIZONTAL
SUPPLY
AND RETURN
END,
0 INCHES
WHEN THE
ALTERNATE
CONDENSATE
DRAIN
IS USED.
5.
HOLE
(MAX.)
7/8"[22.2]
7/B'[22.2]
1 1/8"[28.4]
1 3/4"[44.4]
PANEL
CONDENSER
5.
b.
c.
REQ'D
SIZES
(OlSPOSABLE
[952.5]
ON VERTICAL
DISCHARGE
UNITS,
TO ACCESSORY
ROOF
CURB
ONLY.
UNITS
FIELD
SUPPLIED
FLANGES
HORIZONTAL
DISCHARGE
OPENINGS,
BE ATTACHED
TO THE FLANGED.
ACC.
24V
POWER_
POWER_
SELECT
GRAVITY.
DIRECTION
4.
WIRE
USE
1/2"
1/2"
[31S.O]
NOTED:
1.
THREADED
CONDUIT
SIZE
[315.0]
SIDE
Fig. 7A -- Base Unit Dimensions -- 50TFF004-007
and 50TM004-006 Units
51DE
S
S
i:O;T;IS
BOTTOM
POWER
CHART:
THE5E
HOLE5
REQ'D
FOR U5E
WITH
ACCESSORY
PACKAGES
CRBTMPWROOIAOI,
2AOl,
3AOI,
OR 4AOl
THREADED
WIRE
REQ'D
HOLE
CONDUIT
SIZE
USE
5IZE5
(MAX,]
UNIT
SOTMO0?
OUTSIOE
AIR
NOTES:
1.
DIMENSIONS
2.
_CENTER
S.
_
IN
[
]
ARE
IN
MILLIMETERS.
OF
POWER
REAR
OF GRAVITY.
DIRECTION
AIR
1/2"
ACC,
1/2"
24V
3/4"
(001,003)
"OWER_
1/4"
(O02,004)'OWER_
[003)
1/2"FPT
GAS
[004)
3/4"FPT
GAS
O'
_[114]
FLOW.
4
DIAI
[35]
[51]
DIA,
POWER SUPPLY
[44]
CHARGING
7/8"
DIA.
3/4"
14 NPT
[22]
FIELD
FIELD
POWER SUPPLY
CONTROL WIRING
CONDENSATE
HOLE
KNOCK OUT
PORT HOLE
HOLE
DRAIN
1/2"
FILTER
ACCESS
(DISPOSABLE
FILTERS)
1'
5
1/4"
FOR
_0"
7/8"[22,2]
7/8"[22.2]
1 1/8"[28,4]
1 3/4°[44.4]
1 1/4"[31.8]
1 5/8"[41.3]
1 3/8"
2" DIA.
1 3/4"
SELECT
EITHER
3/4"
OR 1 1/4"
POWER, DEPENDING
ON WIRE SIZE.
FOR
EXHAUST
A
ECONOMIZER
3 3/1B"
E_.
O'
BLOCKOFF
PANEL
[438]
oo
IV
r---1
VIEW S S
RIGHT
10 I15X16
[27B]
°
_
O'
_
SIDE
RETURN
AIR
SUPPLY
AIR
5 3/8"
[137]
_0'
2
9/16"
[BS]
1" [45115
3/4"
O"
_
5 7/16"
[138]
1'
8
1
7/1B°EllI1]
"C"
[81]
DISCONNECT
LOCATION
ELECTRICAL
_362]
I_
[S15]
O"
_I'
3
1
11/15"
2'
10"
[854]
13/15"
CONTROL
CONDENSER
5"
BOX/COMPRESSOR
PANEL
COIL
l'
4 S/IS"
[414.5]
O" 8 5/8
E168.2]
O'
4 I/IS"
[115.8]
3"
TYP
9/15"
5 3/15"
[1046]
Ess_
LEFT
°
d
SIDE
Fig. 7B -- Base Unit Dimensions -- 50TM007 Units
1"
5
5/18"
O'
? 1/4"
_ [184]
s" lO 13/16"
O'
4
1/15"
VERTICAL
ECONOMISER
IV
Table1A-80TFF UNITCAPACITY
SIZE
NOMINAL
(tons)
OPERATING WEIGHT (Ib)
Unit
AI/AI*
AI/Cu*
Cu/Cu*
EconoMl$er
IV
Root Curbt
COMPRESSOR
Quantity
No. Cylinders
(per circuit)
OII (oz)
REFRIGERANT
TYPE
Operating
Charge (Ib-oz)
Circuit 1
Circuit 2
CONDENSER
004
3
+
395
402
410
50
115
007
6
470
479
490
50
115
Scroll
1
2
54
1
2
50
R-22
6-6
Enhanced
1...17
8.36
I
6-14
Copper
2...17
8.36
Tubes, Aluminum
I
Lanced
9-0
-Fins
2...17
10.42
I
2...17
10.42
Propeller Type
8500
1 ...22.0
1/4...1100
325
(in.)
4000
1...22.0
1/4...1100
325
Enhanced
Nominal Cfm
Maximum Continuous
2...15
4.17
Bhp
Std
AIt
High-Static
Btd
AIt
High-Static
Std
AIt
High-Static
Std
AIt
High-Static
Rpm High/Low
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
MIn/Max
Motor Shaft Diameter
Fan Pulley Pitch Diameter
(in.)
Std
Air
High-Static
Std
Air
High-Static
Std
Air
High-Static
Std
Air
High-Static
Btd
Air
High-Static
(in.)
(in.)
Belt, QuanUty...Type...Length
(in.)
Line Distance
(in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum
From Closed Position
Std
Air
High-Static
Fan Shaft Diameter
Std
Air
High-Static
Std
Air
High-Static
Btd
AIt
High-Static
(rpm)
at Pulley
(in.)
HIGH-PRESSURE
SWITCH (peig)
Standard Compressor
Internal
Cutout
Reset (Auto.)
Relief
(LOW-PRESSURE)
FREEZE-PROTECTION
THERMOSTAT
Opens
Closes
OUTDOOR-AIR
INLET SCREENS
RETURN-AIR
FILTERS
QuanUty...Size (in.)
LEGEND
-- Aluminum
-- Brake Horsepower
-- Copper
Copper Tubes, Aluminum Double-Wavy
AcutroP M Metering Device
2...15
5.5
I
4000
1...22.0
V4...1100
825
Fins
3...15
5.5
I
1...10x 10
1...18 x 10
1...18 x 10
Direct
Belt
Belt
1600
.75
1.28
2.48
48
48
56
1875/970
1620
1725
1...11x 10
1...10 x 10
1...10 x 10
Direct
Belt
Belt
2000
1.20
1.30/2.48"*
2.90
48
56
56
1075/1040
1725
1725
76_
800
1075-1455
Ball
2100
83_185
1075-1455
Ball
2100
900-_300
1300-1685
Ball
2100
1_9
2_8
2.8/3.8
1/2
1/2
5/s
3.4/4.4
V2
5/8
5/8
1...10 x 10
1...10 x 10
Belt
Belt
2100
2.40
2%
56
1_6
1070-1480
1._.9
2.8/3.8
5/8
2;
2;
5%
4.6
4.5
4.5
130_
686
Ball
2100
2.8/3.8
3.4_.4
s/8
4.5
2;
1...A...39
1..._.g8
1..._.36
1...A...g9
1...A...39
1...A...40
1...A...40
10._2.4
10.0-12.4
10._2.4
10.0-12.4
14._5.5
14.7-15.5
1..._.40
14.7-15.5
14._5.5
8O
48
65
7O
65
5
6
5
6
5
6
5
T
T
T
3V2
3V2
3_/2
1233
5/8
1233
5/8
3
1226
i_o
(DifferenUal)
SWITCH
4...15
5.5
Type
1...10 x 10
1...10 x 10
1...10 x 10
Direct
Belt
Belt
1280
.34
1.20
2.40
48
48
56
860/800
1620
1725
Full Turns
Factory Setting
Factory Speed Setting
I
4000
1...22.0
1/4...1100
325
Centrifugal
Btd
AIt
High-Static
Btd
Air
High-Static
Motor Frame Size
AI
Bhp
CU
006
5
Reciprocating
1
2
50
4-4
--
Type Drive
LOBS-OF-CHARGE
Cutout
Reset (Auto.)
t
375
381
387
50
115
1
2
50
Rows...Fins/,n.
Total
Face Area (sq ft)
EVAPORATOR
FAN
QuanUty...Slze (in.)
Pulley Center
005
4
365
370
373
50
115
Rows...Flns/In.
Total
Face Area (sq ft)
Nominal
J
COIL
CONDENSER
FAN
Nominal Cfm
Quantlty...Dlameter
Motor Hp...Rpm
Watts Input (Total)
EVAPORATOR COIL
Expansion Device
Nominal
Physical Data -- 50TFF004-007
1_6
1416
5/8
5/8
450 ± 50
428
320
500 ± 50
428
320
(psig)
7±3
22±7
(F)
30±5
45±5
Cleanable.
Screen
size and quantity varies with option selected.
Throwaway
2...16 x 25 x 2
*Evaporator
coil fin material/condenser
coil fin material.
sentative 1or details about coated fins.
1-Weight of 14-in. roof curb.
**Single phase/three phase.
Contact
your local Carrier
repre-
Table 1B -- Physical Data -- 50TM004-007
50TM UNIT CAPACITY
SIZE
NOMINAL
OPERATING WEIGHT
AI/AI*
EconoMl$er
Unit
Roof Curbt
004
3
(tons)
(Ib)
365
50
115
IV
_
005
4
(per circuit)
REFRIGERANT
2
1
50
(Ib-oz)
I
Enhanced
Rows...Fins/in.
Total
Face Area (sq ft)
1...17
8.36
3500
V4...1100
1 ...22.0
325
(in.)
EVAPORATOR
COIL
Expansion Device
ROWS...F,n
TONI
Face s/,n.
Area (sq ft)
2...18
4.17
Nominal Ctm
Maximum ConUnuous
Std
AIt
High-Static
Std
AIt
High-Static
Std
AIt
High-Static
Std
AIt
High-Static
Bhp
Motor Frame Size
Rpm High/Low
Fan Rpm Range
Motor Bearing Type
Maximum Allowable Rpm
Motor Pulley Pitch Diameter
MIn/Max
Motor Shaft Diameter
Fan Pulley Pitch Diameter
(in.)
Std
AIt
High-Static
Std
AIt
High-Static
Std
AIt
High-Static
Btd
AIt
High-Static
Std
AIt
High-Static
(in.)
(in.)
Belt, Ouantlty...Type...Length
(In.)
Line Distance
(in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum
From Closed Position
Std
AIt
High-Static
Std
Air
High-Static
Std
Air
High-Static
at Pulley (in.)
(LOW-PRESSURE)
I
I
4000
4000
4100
I
1/4...1100
1...22.0
325
I
1/4...1100
1...22.0
325
1/4...1100
1...22.0
320
I
2...17
10.42
Copper Tubes, Aluminum DouHe-Wavy
AcutroP M Metering Device
2...18
5.5
I
I
SWITCH
2...17
16.50
Fins, Face Split
3...15
5.5
I
4...18
5.5
Type
1...10 x 10
1...10 x 10
1...10 x 10
Direct
Belt
Belt
1200
.34
1.20
2.40
48
48
56
860/800
1620
1725
1...10 x 10
1...10 x 10
1...10 x 10
Direct
Belt
Belt
1600
.75
1.20
2.40
48
48
56
1075/970
1620
1725
1...11 x 10
1...10 x 10
1...10 x 10
Direct
Belt
Belt
2000
1.20
1.30/2.40"*
2.90
48
56
56
1075/1040
1725
1725
68_ 045
1075-1455
Ball
2100
77_
175
1075-1455
Ball
2100
90_
300
1300-1685
Ball
2100
1.9_.9
1.9_.9
2._3.8
2.8/3.8
1/2
2.8/3.8
1/2
1/2
1/2
5/8
5/8
3.4/4.4
1/2
5/8
5/8
1...10 x 10
1...10 x 10
Belt
Belt
2100
2.40
2%
56
1_8
1070-1480
130_
685
Ball
2100
2.8/3.8
3._.4
5/8
_8
4.5
25
4.5
4.5
4.5
4.5
1 ..._.36
1 ...A...39
1..._.36
1...A...39
1..._.40
1...A...40
10._2.4
10._2.4
14._5.5
10.0-12.4
10.0-12.4
14.7-15.5
z;
1...A...39
1..._.40
14.7-15.5
14._5.5
8O
7O
65
8O
6O
5
6
6
5
5
5
6
T
T
T
31/2
3V2
3V2
829
1233
5/8
1233
5/8
;;2
1225
i_o
1_6
1416
5/8
5/8
450 ± 50
428
320
500 ± 50
428
320
(peig)
7±3
22±7
FREEZE-PROTECTION
Opens
Closes
Quantl_...Slze
Fins
Propeller Type
I
HIGH-PRESSURE
SWITCH (pelg)
Standard Compressor
Internal Relief (Differential)
Cutout
Reset (Auto.)
RETURN-AIR
9-10
Lanced
Full Turns
Factory Speed Setting (rpm)
LOSS-OF-CHARGE
Cutout
Reset (Auto.)
Tubes, Aluminum
2...17
8.36
Std
AIt
High-Static
Factory Setting
Diameter
2
1
B0
7-14
I
Copper
Centrifugal
Std
AIt
High-Static
Std
AIt
High-Static
Type Drive
Pulley Center
I
Enhanced
EVAPORATOR
FAN
Quantity...Size
(in.)
OUTDOOR-AIR
I
6-6
COIL
Motor Hp...Rpm
Quantlty...Dlameter
Watts Input (Total)
2
1
50
R-22
4-5
....
CONDENSER
FAN
Nominal Cfm
Fan Shaft
520
50
115
Scr()ll
2
1
50
I
007
6
395
50
115
TYPE
Circuit 1
Operating
Circuit 2 Charge
Nominal
t
Reciprocating
No. Cylinders
Quantity
OII (oz)
Nominal
006
8
375
50
115
I
COMPRESSOR
CONDENSER
t
THERMOSTAT
INLET SCREENS
FILTERS
!In.}
LEGEND
AI
-- Aluminum
Bhp -- Brake Horsepower
Cu
-- Copper
(F)
30±5
45±5
Cleanable.
Screen
size and quantity varies with option selected.
Throwaway
2...1B x 25 x 2
*Evaporator
coil fin material/condenser
coil fin material.
sentative for details about coated fins.
1-Weight of 14-in. roof curb.
**Single phase/three phase.
Contact your local Carrier repre-
Step 5 --
Make Electrical
Connections
supply, the transformer must be rewired by moving the black
wire from 230-v l/4-in, spade terminal and connecting it to
200-v V4-in. spade terminal of transformel_
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal inju U if
an electrical fault should occm_ This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit appl_wed for electrical gl_mnd when
installed in accordance
with NEC (National Electrical
Code),
ANSI/NFPA
(American
Natiomd
Standards
Institute/National
Fire Protection
Association),
latest
edition (in Cana&L, Canadian
Electrical
Code CSA
[Canadian Standards Association] C22.1 ), and local electrical codes. Ftdlure to follow this warning could result in the
installer being liable for pel_onal inju U of others.
FIELD POWER SUPPLY--All
units except
208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power
See Tables 2A and 2B. Refer to unit label diagram for
additional information. Pigtails are pl_wided for field wire connections. Use factou-supplied
splices or UL (Undel_ritel_'
Laboratories) approved copper/aluminum
connectol_
When inst_dling units, provide a disconnect
All field
requirements.
wiring
must comply
per NEC.
with the NEC
and
local
Inst_dl field wiring as follows:
1. Inst_dl conduit through side panel openings. For units
without electric heat, install conduit between disconnect
and contl_l box.
2.
Inst_dl power
Fig. 8.
Power wiring
panel.
lines to terminal
connections
as shown
in
leads are located inside power wiring access
L
'
BLK
TO COMP
(SIZE 007 ONLY)
208/230-1-60
FIELD
POWER SUPPLY
__ J-JL .L__
F--DISCONN ECT -I
PER NEC
I
L- .....
.J
L _R_ =_%.
BLK_
_
BLU --------_
I L 0LD---- o Op
TTBO2
I
I
I
[
I
'BLK _
575-3-60
1
F_ELD POWER
(SIZE 007 ONLY)
SUPPLY
I
[
DISCONNECT
PER NEC
, I
(SIZES
F
004-006)
[
1_
------
DISCONNECT
PER NEC
I
I
BLK_
DISCONNECT
PER NEO
FIELD POWER
480-3-80
q
(SIZES 004-006)
Contactor
Compressor
Indoor (Evaporator) Fan Contactor
National Electrical Code
Terminal Block
Fig. 8 -- Power Wiring Connections
SUPPLY
F-j- I
I
L
U
LEGEND
C
COMP
IFC
NEC
TB
_L _!.1_ L_I
I
I
I
SUPPLY
_L _L _ L
208/230-3-60
0 °P
r-
@_)_
I
FIELD POWER
(SIZES 004-006)
I
j
Q:4
FIELD POWER SUPPLY
575-3-60
r--_- ._ L q
L
DISC-ON_OTq
PER NEO
l
O_)OMP
FIELD CONTROL WIRING -- Install a CmTier-approved
accessory
thermostat
assembly
according
to installation
instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature
in accordance
with thermostat
installation
instructions. Connect thermostat wires to terminal board.
the thermostat
thermostat.
IMPORTANT:
Optiomfl
factory-installed,
_flternate
evaporator-fan
motors are not available for 50TFF,
TM007 units. Contact your local Carrier representative
for more information about field-installed motors.
m
FAN
- -I
_
L{_
"
.
RACEWAY
R
G
LOW VOLTAGE
CONNECTIONS
I
HEAT STAGE 1
w/wl--_
COOL STAGE 2
Y/Y2
HEAT STAGE 2
O/W2-
24 VAC HOT
R-
24 VAC COM
C-
_ 'r
_
i-
i_
-t-
Y1
"
Y2
.
Wl
|
1_
-
_-
W2
WIRE
CONNECTIONS
TO
= LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
_
IPD/X
N/A
OUTDOOR
AIR
$1
SENSOR
$2
THERMOSTAT
DIPSWITCH
SETTINGS
ON
A
B
C
D
HOLE IN END PANEL(HIDDEN)
LEGEND
Field Wiring
NOTES: Underlined letter indicates
configured for A/C operation.
Fig. 10active thermostat
the
the
the
UL
NOTE: If thin-the-bottom
power connections are used refer to
the accessory installation instructions for information on power
wiring. Refer to Fig. 6A and 6B for &illing holes in basepan.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wile Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 fl, use no. 14 AWG insulated wire (35 C minimum). All
wire lmger than no. 18 AWG cannot be directly connected to
Y1/W2G .....
box and splice at the
Pass the control wiles through the hole provided in
corner post; then feed wires through the raceway built into
corner post to the 24-v barrier located on the left side of
control box. See Fig. 10. The laceway provides the
required clearance between high- and low-voltage wiling.
Route thermostat cable or equiv¢dent single leads of colored
wire from subbase terminals to low-voltage connections on
unit (shown in Fig. 9).
COOL STAGE 1
and will require a junction
output when
Fig. 9 -- Low-Voltage Connections
10
Field Control Wiring Raceway
Table 2A -- Electrical Data (Without Convenience
VOLTAGE
5OTFF,TM
UNIT
SIZE
IFM
TYPE
NOMINAL
V-PH-Hz
COMPRESSOR
RANGE
Min
(ea)
Max
Oty
RLA
OFM(ea)
LRA
Qty
Hp
IFM
FLA
FLA
ELECTRIC
HEATER
MODEL
NO,
Nominal
kW
CRHEATER---A00
NONE
001
3.5
STD
208/230-1-60
--
187
254
1
16.2
96
1
1/4
1.4
ALT
4.9
208/230-3-60
ALT
187
254
1
10.2
75
1
1/4
1.4
DISCONNECT
SIZEt
MOCP*
FLA
LRA
25.2/25.2
25.2/27.3
33.7/38.2
43.6/49.7
51.8/59.1
63.0/72.1
30/30
30/30
35/40
45/50
60/60
70/80
24/24
24/25
31/35
40/46
48/54
58/66
106/106
106/106
106/106
106/106
106/106
106/106
004
NONE
O01
OO2
003
OO4
002 and 002
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
9.8/13.0
--/-15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
26.6/26.6
26.6/29.0
35.5/40.0
45.4/51.4
53.5/60.8
64.8/73.8
35/35
35/35
40/40
50/60
60/70
70/80
26/26
26/27
33/37
42/47
49/56
60/68
111/111
111/111
111/111
111/111
111/111
111/111
004
004
NONE
O01
002
0O3
004
OO5
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.2/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
17.7/17.7
17.7/17.7
21.3/23.9
27.0/30.5
31.7/35.9
46.1/52.4
25/25
25/25
25/25
30/35
35/40
50/60
17/17
17/17
20/22
25/28
29/33
42/48
85/
85/
85/
85/
85/
85/
85
85
85
85
85
85
NONE
O01
OO2
OO3
O04
OO5
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.3/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
19.1/19.1
19.1/19.4
23.1/25.7
28.8/32.3
33.5/37.7
47.8/54.2
25/25
25/25
25/30
30/35
35/40
50/60
19/19
19/19
21/24
26/30
31/35
44/50
90/
90/
90/
90/
90/
90/
90
90
90
90
90
90
NONE
O01
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.3/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
19.4/19.4
19.4/19.7
23.4/26.0
29.2/32.7
33.9/38.1
48.2/54.6
25/25
25/25
30/30
30/35
35/40
50/60
19/19
19/19
22/24
27/30
31/35
44/50
109/109
109/109
109/109
109/109
109/109
109/109
4.9
1.3
NONE
OO6
007
008
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
7.6
15.6
14.9
18.9
22.7
15
15
15
20
25
7
10
14
17
21
44
45
45
45
45
2.1
NONE
OO6
OO7
008
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
8.4
11.6
15.9
19.9
23.7
15
15
20
20
25
8
11
15
18
22
48
48
48
48
48
2.6
NONE
OO6
007
0O8
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
8.9
12.3
16.5
20.5
24.3
15
15
20
25
25
9
11
15
19
22
57
57
57
57
57
1.3
NONE
--
--
5.5
15
6
34
2.1
NONE
--
--
6.0
15
7
37
2.6
NONE
--
--
6.3
15
7
56
414
508
1
4.4
40
1
1/4
0.8
STD
ALT
518
632
1
3.7
31
1
1/4
0.8
002
OO3
004
OO5
LEGEND
Full Load Amps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fan Motor
Locked
Rotor Amps
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
ElectriealCode
Outdoor
(Condenser)
Fan Motor
Rated Load Amps
*Used to determine
minimum
disconnect
tEuse or HACR circuit breaker.
per
SINGLE
POINT
BOX PIN
CRSINGLE---AO0
--/-15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
STD
HIGH
----------
SUPPLY
5.2
HIGH
FLA
HACk
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
MCA
HIGH
ALT
575-3-60
POWER
FLA
--/-3.3/ 4.4
4.9/ 6.5
6.4/ 8.7
7.9/10.5
9.8/13.0
004
460-3-60
HEAT
002
003
004
002 and 002
3.5
STD
Outlet)
Determine
(AB) 457
(BC) 464
(AC) 457
Maximum
0Q.s
maximum
deviation
-452
= 5 v
- 457 = 7 v
- 455 = 2 v
deviation
is 7 v.
Determine
percent
of voltage
from
average
voltage.
imbalance.
7
% Voltage
Imbalance
= 100 x
--
457
= 1.53%
NEC.
This
amount
electric
utility
IMPORTANT:
I
of phase
imbalance
is satisfactory
company
immediately.
If the supply
voltage
phase
as it is below
imbalance
the maximum
is more
than
2%,
allowable
contact
2%.
your
I
local
I
NOTES:
1.
2.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overeurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
Unbalanced
3-Phase
Supply
Voltage
Never
operate a motor where a phase imbalance
in supply
voltage
ts greater
than 2% Use the
following
formula
to determine
the percent
of voltage
imbalance.
% Voltage
= 1OO x
A
Supply
B
C
New
= MCA
unit only
For example,
using
CRPWREXHO30AO0
deviation
average
voltage
from average
voltage
MCA
voltage
is 460-3-60.
Voltage
AC = 455 v
=
New
= 28.9
+ MCA
of Power
a 50TFF0O6--5
power exhaust.
amps
+ 1.6 amps
Exhaust
unit
= 30.5
size wire to include
exhaust
is powered
Determine
the new
with
MCA
=
28.9
and
MOCP
= 35,
with
amps
If the new MCA does not exceed
the published
MOCk
then MOCP
would not change.
The
MOCP in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP for the power
exhaust will be 15 amps
per NEC.
AB = 452 v
BC = 464 v
Average
(_
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA and MQCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
Imbalance
max voltage
Example:
3.
452
+ 464
3
POWER
EXHAUST
PART NO.
+ 455
MOCP
(for separate
power
source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OA00
1.6
N/A
0.54
15
CRPWREXH021AO0
N/A
0.9
N/A
15
CRPWREXHO22A00
3.3
N/A
1.32
15
CRPWREXHO23AO0
N/A
1.8
N/A
15
CRPWREXHO28AO0
1.7
N/A
0.68
15
CRPWREXHO29AO0
N/A
1.O
N/A
15
/
1371
3
= 457
11
Table 2A -- Electrical Data (Without Convenience Outlet) (cont)
VOLTAGE
50TFF,TM
UNIT
SIZE
NOMINAL
V-PH-Hz
IFM
TYPE
COMPRESSOR
RANGE
Min
(ea)
Max
Qty
RLA
OFM
LRA
Qty
(ea)
Hp
IFM
FLA
ALT
4.9
NONE
001
003
002 and 002
003 and 003
004 and 004
--/-3.3/
4.4
6.5/
8.7
9.3/13.0
13.1/17.4
15.8/21.0
--/-15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
35.4/
35.4
35.4/
35.4
45.4/
51.4
64.8/
73.8
84.7/
96.8
100.9/115.5
45/ 45
45/ 45
50/ 60
70/ 80
90/100
110/125
34/ 34
34/ 34
42/ 47
60/ 68
78/ 89
93/106
133/133
133/133
133/133
133/133
133/133
133/133
004
004
004
STD
3.5
NONE
002
003
005
004 and 004
--/-4.9/
6.5
6.5/
8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
18.1/20.9
38.4/38.4
43.8/50.5
24.2/
24.2/
27.0/
46.1/
59.1/
24.2
24.2
30.5
52.4
67.5
30/
30/
30/
50/
60/
30
30
35
60
70
23/
23/
25/
42/
54/
23
23
28
48
62
101/101
101/101
101/101
101/101
101/101
002
4.9
NONE
002
003
005
004 and 004
--/-4.9/
6.5
6.5/
8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
18.1/20.9
38.4/38.4
43.8/50.5
25.6/
25.6/
28.8/
47.8/
60.8/
25.6
25.7
32.3
54.2
69.3
30/
30/
30/
50/
70/
30
30
35
60
70
25/
25/
26/
44/
56/
25
25
30
50
64
105/105
105/105
105/105
105/105
105/105
002
5.2
NONE
002
003
005
004 and 004
--/-4.9/
6.5
6.51 8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
18.1/20.9
33.4/38.4
43.8/50.5
25.9/
25.9/
29.2/
48.2/
61.2/
25.9
26.0
32.7
54.6
69.6
30/
30/
30/
50/
70/
30
30
35
60
70
25/
25/
27/
44/
56/
25
25
30
50
64
124/124
124/124
124/124
124/124
124/124
OO2
1.8
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
13.0
13.0
19.5
23.3
36.8
20
20
20
25
40
13
13
18
21
34
51
51
51
51
51
2.1
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
13.3
13.3
19.9
23.7
37.2
20
20
20
25
40
13
13
18
22
34
53
53
53
53
53
2.6
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
13.8
13.8
20.5
24.3
37.8
20
20
25
25
40
13
13
19
22
35
62
62
62
62
62
1.8
NONE
--
--
9.2
15
10
41
2.1
2.6
NONE
NONE
---
---
9.3
9.7
15
15
10
10
42
187
187
ALT
254
1
254
414
ALT
HiGH
1
508
1
518
632
1
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
--------
Full LoadAmps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fan Motor
Locked
Rotor Amps
Minimum
CircuitAmps
Maximum
Overcurrent
Protection
National
Electrical
Code
OFM
RLA
---
Outdoor
(Condenser)
Rated Load Amps
Fan
Motor
*Used to determine
minimum
disconnect
tFuse or HACR circuit breaker.
per
23.3
15.4
118
90
1
1
1/4
1/4
1.4
1.4
8.3
45
1
1/4
0.8
6.4
36
1
1/4
0.8
Determine
maximum
(AB) 457 - 452 = 5
(BC) 464 - 457 = 7
(AC) 457 - 455 = 2
0 us
B
deviation
is 7 v.
percent
of voltage
Imbalance
average
49
voltage.
imbalance.
7
-457
= 100 x
= 1.53%
This
NEC.
amount
electric
utility
IMPORTANT:
3.
of phase
imbalance
company
immediately.
If the supply
voltage
MCA
New
= MCA
unit only
For example,
using
CRPWREXHO3OAO0
max voltage
MCA
deviation
average
from average
voltage
voltage
is satisfactory
phase
as it is below
imbalance
the maximunl
is more
than
2%,
allowable
contact
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA
and MOCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
Imbalance
C
from
v
v
v
Determine
I
A
deviation
Maximum
% Voltage
NOTES:
1.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
2.
Unbalanced
3-Phase
Supply
Voltage
Never operate
a motor where a phase imbalance
in supply
voltage
is greater
than 2%
Use the
following
formula
to determine
the percent
of voltage
imbalance.
voltage
POINT
PIN
CRSINGLE---AO0
004
004
004
LEGEND
Supply
LRA
129/129
129/129
129/129
129/129
129/129
129/129
STD
Example:
SINGLE
BOX
FLA
32/ 32
32/ 32
40/ 46
58/ 66
76/ 87
91/105
HIGH
x
MOCP*
40/ 40
40/ 40
45/ 50
70/ 80
90/100
100/125
STD
= 100
MCA
34.0/
34.0
34.0/
34.0
43.6/
49.7
63.0/
72.1
82.9/
95.0
99.2/113.8
HIGH
% Voltage
FLA
Nominal
kW
DISCONNECT
SIZE_
SUPPLY
--/-15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
O05
575-3-60
POWER
--/-3.3/
4.4
6.5/
8.7
9.3/13.0
13.1/17.4
15.8/21.0
ALT
460-3-60
CRHEATER---A00
HEAT
NONE
001
0O3
002 and 002
003 and 003
004 and 004
--
208/230-3-60
ELECTRIC
3.5
STD
208/230-1-60
FLA
HEATER NO
MODEL
New
= 28.9
+ MCA
of Power
a 50TFFO06--5
power exhaust.
amps
+ 1.6 amps
your
with
MCA
=
28.9
and
MOCP
=
35,
AB = 452 v
BC = 464v
Voltage
=
with
amps
If the new MCA does not exceed
the published
MOCP, then MOCP
would
not change.
The
MOCP
in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP
is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP
for the power
exhaust will be 15 amps per NEC.
is 460-3-60.
Average
I
local
size wire to include
exhaust
is powered
Determine
the new
Exhaust
unit
= 30.5
2%.
452
+ 464
3
POWER
EXHAUST
PART NO.
+ 455
AC = 455 v
1371
3
= 457
12
MOCP
(for separate
power source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OAO0
1.6
N/A
0.64
15
CRPWREXHO21AO0
N/A
0.9
N/A
15
CRPWREXHO22AO0
3.3
N/A
1.32
15
CRPWREXHO23AO0
N/A
1.8
N/A
15
CRPWREXHO28AO0
1.7
N/A
0.68
15
CRPWREXHO29AOO
N/A
1.0
N/A
15
Table 2A -- Electrical Data (Without Convenience Outlet) (cent)
VOLTAGE
5OTFF,TM
UNIT
SIZE
IFM
NOMINAL
V-PH-Hz
COMPRESSOR
RANGE
TYPE
Min
(ea)
Max
Qty
RLA
OFM
LRA
Qty
(ea)
Hp
IFM
FLA
HEATER
MODEL
NO,
5.9
004
004
004
ALT
6.6
NONE
OO2
OO3
002 and 002
003 and 003
004 and 004
--/-4.9/
6.5
6.5/
8.7
9.8/13.0
13.1/17.4
15.8/21.0
--/-23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
44.0/
44.0
44.0/
44.0
47.5/
53.6
66.9/
76.0
86.8/
98.9
103.0/117.6
60/ 60
60] 60
50/ 60
70) 80
90/100
110/125
42/ 42
42/ 42
44/ 49
62/ 70
80/ 91
95/108
184/184
184/184
184/184
184/184
184/184
184/184
004
004
004
NONE
0O2
STD
5.9
004
005
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
27.3/
27.3/
34.7/
49.1/
62.1/
76.4/
27.3
27.3
38.9
55.4
70.5
87.1
35/
35/
40/
50/
70
80/
35
35
40
60
80
90
27/
27/
32/
45/
57/
70/
27
27
36
51
65
80
128/128
128/128
128/128
128/128
128/128
128/128
NONE
OO2
O04
OO5
004 and 004
004 and 005
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
26.6/
26.6/
33.9/
48.2/
61.2/
75.6/
26.6
26.6
38.1
54.6
69.6
86.2
35/
35/
35/
50/
70/
80/
35
35
40
60
70
90
26/
26/
31/
44/
56/
70/
26
26
35
50
64
79
148/148
148/148
148/148
148/148
148/148
148/148
NONE
OO2
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
28.9/
28.9
36.7/
51.1/
64.1/
78.4/
28.9
28.9
40.9
57.4
72.5
89.1
35/
35/
40]
60t
70/
80/
35
35
45
60
80
90
29/
29/
34/
47/
59/
72/
29
29
38
53
67
82
174/174
174/174
174/174
174/174
174/174
174/174
187
254
1
28.8
147
1
1/4
1.4
187
254
1
16
114
1
1/4
1.4
5.2
7.5
STD
ALT
414
508
1
7.4
64
1
1/4
0.8
HIGH
STD
ALT
518
632
1
6.2
52
1
1/4
0.8
004
005
and
and
004
005
3.1
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
13.2
13.2
21.2
24.9
38.5
41.5
20
20
25
25
40
45
13
13
19
23
35
38
71
72
72
72
72
72
2.6
NONE
O06
OO8
O09
008 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
13.5
18.5
21.5
25.3
38.8
41.8
20
20
25
30
40
45
13
13
20
23
36
38
81
81
81
81
81
81
NONE
O06
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
13.5
13.5
21.5
25.3
38.8
41.8
20
20
25
30
40
45
13
13
20
23
36
38
93
94
94
94
94
94
3.4
HIGH
004
005
and
and
NONE
O06
OO8
009
008 and 008
008 and 009
008
008
008
009
and
and
008
009
3.1
NONE
--
--
9.7
15
11
58
2.6
NONE
--
--
9.9
15
11
65
3.4
NONE
--
--
9.9
15
11
75
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
--------
Full Load Amps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fan Motor
Locked
Rotor Amps
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
ElectricaICode
OFM
RLA
---
Outdoor
(Condenser)
Rated Load Amps
Determine
maximum
deviation
(AB) 457 -452
= 5 v
(BC) 464 - 457 = 7 v
(AC) 457 -455
= 2 v
Maxhnum
deviation
is 7 v.
Determine
percent
of voltage
% Voltage
Fan Motor
per
This
NEC.
A
S
3.
of phase
7
-- 457
imbalance
deviation
average
from average
voltage
MCA
voltage
is satisfactory
company
immediately.
If the supply
voltage
New
= MCA
unit only
phase
New
= 28.9
+ MCA
as it is below
imbalance
of Power
a 50TFFO06--5
power exhaust.
the maximum
is more
than
2%,
allowable
contact
amps
+ 1.6 amps
your
is 460-3-60.
Average
Voltage
I
size wire to include
exhaust
is powered
Determine
the new
with
MCA
=
28.9
and
MOCP
= 35,
with
amps
AB = 452 v
BC = 464 v
AC = 455 v
I
local
Exhaust
unit
= 30.5
2%.
If the new MCA does not exceed
the published
MOCR
then MOCP
would not change.
The
MOCP in this example
is 35 amps, the MCA New is below 35, therefore
the MQCP is acceptable. If "MCA
New" is larger than the published
MOCR
raise the MOCP
to the next larger
size. For separate
power, the MQCP for the power
exhaust will be 15 amps
per NEC.
POWER
EXHAUST
PART NO.
(_
voltage.
imbalance.
= 100 x
For example,
using
CRPWREXHO3OAO0
voltage
average
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA and MQCR
Check MCA and MQCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
hnbalance
C
amount
electric
utility
IMPORTANT:
I
NOTES:
1. In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 448}, the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
2. Unbalanced
3-Phase
Supply
Voltage
Never
operate a motor where a phase imbalance
in supply
voltage
ts greater
than 2% Use the
following
formula
to determine
the percent
of voltage
imbalance.
Supply
Imbalance
from
002
002
= 1.53%
*Used to determine
Ininknum
disconnect
tPuse or HACR circuit breaker.
Example:
SINGLE POINT
BOX _N
CRSINGLE---AOO
LRA
161/161
161/161
161/161
161/161
161/161
161/161
004
004
max voltage
FLA
42/ 42
42/ 42
43/ 48
61/ 69
79/ 90
94/107
HIGH
= 100 x
MOCP*
60/ 60
60/ 60
50/ 60
70/ 80
90/100
110/125
006
% Voltage
DISCONNECT
SlZEt
MCA
43.3/
43.3
43.3/
43.3
46.6/
52.7
66.0/
75.1
85.9/
98.0
102.2/116.8
ALT
575-3-60
FLA
--/-23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
004
004
460-3-60
POWERSUPPLV
HEAT
Nominal
kW
--/-4.9/
6.5
6.5/
8.7
9.8/13.0
13.1/17.4
15.8/21.0
--
208/230-3-60
ELECTRIC
CRHEATER---A00
NONE
OO2
O03
002 and 002
003 and 003
004 and 004
STD
208/230-1-60
FLA
=
3
452 + 464
1371
+ 455
3
= 457
13
MOCP
(for separate
power
source)
MCA
(230 v)
MCA
(460 v)
MCA
(875 v)
CRPWREXHO3OAOO
1.6
N/A
0.64
15
CRPWREXHO21AOO
N/A
0.9
N/A
15
CRPWREXHO22AOO
3.3
N/A
1.32
15
CRPWREXHO23AOO
N/A
1.8
N/A
15
CRPWREXHO28AOO
1.7
N/A
0.68
15
CRPWREXHO29AOO
N/A
1.o
N/A
15
Table 2A -- Electrical Data (Without Convenience Outlet) (cont)
VOLTAGE
50TFF, TM
UNIT
SIZE
NOMINAL
V-PH-Hz
IFM
TYPE
COMPRESSOR
RANGE
Min
(ea)
Max
Qty
RLA
OFM
LRA
Oty
(ea)
Hp
IFM
FLA
FLA
ELECTRIC
HEATER
MODEL
NO
Nominal
kW
CRHEATER---A00
NONE
002
208/230-3-60
--
187
254
1
20.6
146
1
1/4
--
508
1
9.5
73
1
1/4
STD
575-3-60
_
518
632
7.6
1
62
1
1/4
0.9
----
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
LRA
MCA
MOCP
NEC
OFM
RLA
--
Locked
Rotor Amlpss
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
Electrical
Code
Outdoor
(Condenser)
Fan Motor
Rated Load Amps
-----
_Used to determine
minimum
disconnect
tFuse or HACR circuit breaker.
per
LRA
004
005
NONE
002
004
005
004 and 004
004 and 005
--/-4.9/ 6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
34.7/34.7
34.7/34.7
36.7/40.9
51.1/57.4
64.1/72.5
78.4/89.1
40/40
40/40
40/45
60/60
70/80
80/90
34/34
34/34
34/38
47/53
59/67
72/82
205/205
205/205
205/205
205/205
205/205
205/205
NONE
006
008
009
-6.0
11.5
14.0
23.0
25.5
-7.2
13.5
16.8
27.7
30.7
15.4
15.4
20.5
24.3
37.8
41.6
20
20
25
25
40
45
15
15
19
22
35
38
90
90
90
90
90
90
3.4
NONE
006
008
009
008 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.5
-7.2
13.8
16.8
27.7
30.7
16.2
16.2
21.5
25.3
38.8
42.6
20
20
25
30
40
45
16
16
20
23
36
39
103
103
103
103
103
103
2.6
NONE
--
--
11.4
15
12
75
3.4
NONE
--
--
11.9
15
13
86
008
009
008 and
008 and
LEGEND
FLA
HACR
IFM
DISCONNECT
SIZEt
180/180
180/180
180/180
180/180
180/180
180/180
0.9
HIGH
FLA
31/31
31/31
31/35
44/50
56/64
70/79
2.8
414
MOCP*
40/40
40/40
35/40
50/60
70/70
80/90
004
005
004 and
004 and
OO7
460-3-60
SUPPLY
32.4/32.4
32.4/32.4
33.9/38.1
48.2/54.6
61.2/69.6
75.6/86.2
7.5
STD
MCA
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
1.4
HIGH
POWER
FLA
--/-4.9/ 6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
5.2
STD
HEAT
Determine
(AB) 457
(BC) 464
(AC) 457
Maximum
maximum
deviation
- 452 = 5 v
- 457 = 7 v
- 455 = 2 v
deviation
is 7 v.
Determine
percent
of voltage
from
average
SINGLE
POINT
BOX PIN
CRSINGLE---AO0
002
002
voltage.
imbalance.
7
% Voltage
imbalance
= 100 x
45_
= 1.53%
NEC.
This
amount
electric
utility
IMPORTANT:
I
of phase
imbalance
is satisfactory
company
immediately.
If the supply
voltage
phase
as it is below
imbalance
the maximum
is more
than
2%,
allowable
contact
2%.
your
I
local
I
NOTES:
1.
2.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
Unbalanced
3-Phase
Supply
Voltage
Never operate
a motor where a phase imbalance
in supply
voltage
is greater
than 2%
Use the
following
formula
to determine
the percent
of voltage
imbalance.
% Voltage
= 100
x
Example:
A
New
= MCA
unit only
For example,
using
CRPWREXHO3OAO0
max volta[le
C
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA
and MOCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
imbalance
Supply
B
3.
deviation
average
voltage
from average
voltage
MCA
voltage
New
= 28.9
AB = 452 v
BC = 464v
amps
POWER
EXHAUST
PART NO.
Average
Voltage
=
of Power
+ 1.6 amps
Exhaust
unit
= 30.5
with
MCA
=
28.9
and
MOCP
=
35,
with
amps
If the new MCA does not exceed
the published
MOCP, then MOCP
would
not change.
The
MOCP
in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP
is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP
for the power
exhaust will be 15 amps per NEC.
is 460-3-60.
AC = 455 v
+ MCA
a 50TFFO06---5
power exhaust.
size wire to include
exhaust
is powered
Determine
the new
452
+ 464
3
MOCP
(for separate
power source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OAOO
1.6
N/A
0.64
15
CRPWREXHO21AO0
N/A
0.9
N/A
15
CRPWREXHO22AOO
3.3
N/A
1.32
15
CRPWREXHO23AO0
N/A
1.8
N/A
15
CRPWREXHO28AOO
1.7
N/A
0.68
15
CRPWREXHO20AO0
N/A
1.0
N/A
15
+ 455
1371
=-3
= 457
14
Table 2B -- Electrical Data (With Convenience Outlet)
VOLTAGE
5OTFF,TM
UNIT
SIZE
IFM
TYPE
NOMINAL
V-PH-Hz
COMPRESSOR
RANGE
Min
(ea)
Max
Oty
RLA
OFM(ea)
LRA
Qty
Hp
IFM
FLA
FLA
ELECTRIC
HEATER
MODEL
NO,
Nominal
kW
CRHEATER---A00
NONE
001
3.5
STD
208/230-1-60
--
187
254
1
16.2
96
1
1/4
1.4
ALT
4.9
208/230-3-60
ALT
254
1
10.2
75
1
1/4
1.4
4.9
004
460-3-60
FLA
LRA
31.2/31.2
31.2/32.3
38.7/43.2
48.6/54.7
56.8/64.1
68.0/77.1
35/35
35/35
40/45
50/60
60/70
70/80
30/30
30/31
37/41
46/51
53/60
64/72
111/111
111/111
111/111
111/111
111/111
111/111
004
004
NONE
O01
OO2
003
OO4
002 and 002
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
9.8/13.0
--/-15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
32.6/32.6
32.6/34.0
40.5/45.0
50.4/56.4
58.5/65.8
69.8/78.8
40/40
40/40
45/45
60/60
60/70
70/80
31/31
31/32
38/42
47/53
55/61
65/73
116/116
116/116
116/116
116/116
116/116
116/116
004
004
002
0O3
004
OO5
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.2/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
22.5/22.5
22.5/23.0
27.3/29.4
33.1/36.0
37.7/42.0
52.1/57.9
30/30
30/30
30/30
35/40
40/45
60/60
23/23
23/23
25/28
30/34
35/39
48/54
90/
90
90/
90/
90/
90/
90
90
90
90
90
90
NONE
O01
OO2
OO3
O04
OO5
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.3/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
23.9/23.9
23.9/24.8
29.1/31.1
34.8/37.7
39.5/43.7
53.8/59.6
30/30
30/30
30/35
35/40
40/45
60/60
25/25
25/25
27/29
32/35
36/40
50/55
95/
95/
95/
95/
95/
95/
95
95
95
95
95
95
NONE
O01
--/-3.3/ 4.4
4.9/ 6.5
6.5/ 8.7
7.9/10.5
12.3/16.0
--/-9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.4
24.2/24.2
24.2/25.2
29.5/31.5
35.2/38.1
39.9/44.1
54.2/60.0
30/30
30/30
35/35
40/40
40/45
60/60
25/25
25/25
27/29
32/36
37/41
50/56
NONE
OO6
007
008
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
9.8
13.4
17.6
21.6
25.4
15
15
20
25
30
10
12
16
20
23
47
47
47
47
47
2.1
NONE
OO6
OO7
008
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
10.6
14.4
18.6
22.6
26.4
15
15
20
25
30
11
13
17
21
24
50
50
50
50
50
2.6
NONE
OO6
007
0O8
OO9
-6.0
8.8
11.5
14.0
-7.2
10.6
13.8
16.8
11.1
15.0
19.2
23.3
27.0
15
20
20
25
30
11
14
18
21
25
59
59
59
59
59
1.3
NONE
--
--
7.2
15
8
36
2.1
NONE
--
--
7.7
15
9
39
2.6
NONE
--
--
8.0
15
9
58
508
1
4.4
40
1
1/4
0.8
STD
ALT
518
632
1
3.7
31
1
1/4
0.8
002
OO3
004
OO5
114/114
114/114
114/114
114/114
114/114
114/114
1.3
414
LEGEND
Determine
(AB) 457
(BC) 464
(AC) 457
Maximum
Full Load Amps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fan Motor
Locked
Rotor Amps
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
ElectriealCode
Outdoor
(Condenser)
Fan Motor
Rated Load Amps
*Used to determine
minimum
disconnect
tEuse or HACR circuit breaker.
per
SINGLE
POINT
BOX PIN
CRSINGLE---AOO
--/-15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
STD
HIGH
----------
DISCONNECT
SIZEt
MOCP*
5.2
HIGH
FLA
HACk
IFM
LRA
MCA
MOCP
NEC
OFM
RLA
SUPPLY
HIGH
ALT
575-3-60
MCA
--/-3.3/ 4.4
4.9/ 6.5
6.4/ 8.7
7.9/10.5
9.8/13.0
3.5
187
POWER
FLA
002
003
004
002 and 002
NONE
O01
STD
HEAT
maximum
deviation
-452
= 5 v
- 457 = 7 v
- 455 = 2 v
deviation
is 7 v.
Determine
percent
of voltage
from
average
voltage.
imbalance.
7
% Voltage
Imbalance
= 100 x
--
457
= 1.53%
NEC.
This
amount
electric
utility
IMPORTANT:
I
of phase
imbalance
is satisfactory
company
immediately.
If the supply
voltage
phase
as it is below
imbalance
the maximum
is more
than
2%,
allowable
contact
2%.
your
I
local
I
NOTES:
1.
2.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overeurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
Unbalanced
3-Phase
Supply
Voltage
Never
operate a motor where a phase imbalance
in supply
voltage
ts greater
than 2% Use the
following
formula
to determine
the percent
of voltage
imbalance.
% Voltage
= lOO x
A
Supply
B
C
New
= MCA
unit only
For example,
using
CRPWREXHO3OAO0
deviation
average
voltage
from average
voltage
MCA
voltage
is 460-3-60.
Voltage
AC = 455 v
=
New
= 28.9
+ MCA
of Power
a 50TFFOO6--5
power exhaust.
amps
+ 1.6 amps
Exhaust
unit
= 30.5
size wire to include
exhaust
is powered
Determine
the new
with
MCA
=
28.9
and
MOCP
= 35,
with
amps
If the new MCA does not exceed
the published
MOCk
then MOCP
would not change.
The
MOCP in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP for the power
exhaust will be 15 amps
per NEC.
AB = 452 v
BC = 464 v
Average
(_
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA and MQCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
Imbalance
max voltage
Example:
3.
452
+ 464
3
POWER
EXHAUST
PART NO.
+ 455
MOCP
(for separate
power
source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OA00
1.6
N/A
0.54
15
CRPWREXH021AO0
N/A
0.9
N/A
15
CRPWREXHO22A00
3.3
N/A
1.32
15
CRPWREXHO23AOO
N/A
1.8
N/A
15
CRPWREXHO28AOO
1.7
N/A
0.68
15
CRPWREXHO29AOO
N/A
1.O
N/A
15
/
1371
3
= 457
1.5
Table 2B -- Electrical Data (With Convenience Outlet) (cont)
50TFF,TM
UNIT
SIZE
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
Min
COMPRESSOR
(ea)
Max
Qty
RLA
OFM
LRA
Qty
(ea)
Hp
FLA
ALT
4.9
--/-3.3/
4.4
6.5/
8.7
9.3/13.0
13.1/17.4
15.8/21.0
--/-15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/97.5
41.4/
41.4
41.4/
41.4
50.4/
56.4
69.8/
78.8
89.7/101.8
105.9/120.5
50/ 50
50/ 50
8(i)/ 80
70/ 80
90/110
110/125
40/ 40
40/ 40
47/ 53
65/ 73
83/ 95
98/112
138/138
138/138
138/138
138/138
138/138
138/138
004
004
004
STD
3.5
NONE
002
003
005
OO4andOO4
--/-4.9/
6.5
6.5/
8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
18.1/20.9
33.4/36.4
43.8/50.5
29.0/
29.0/
33.1/
52.1/
65.1/
29.0
29.4
36.0
57.9
73.5
35/
35
35/
60/
70/
35
35
40
60
80
29/
29/
30/
48/
60/
29
29
34
54
68
106/106
106/106
106/106
106/106
106/106
002
4.9
NONE
002
003
005
004 and 004
--/-4.9/
6.5
6.5/
8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
19.1/20.9
33.4/36.4
43.8/50.5
30.4/
30.4/
34.8/
53.8/
66.9/
30.4
31.1
37.7
59.6
75.3
35/
35/
35/
60/
70/
35
35
40
60
80
30/
30/
32/
50/
62/
30
30
35
55
69
110/110
110/110
110/110
110/110
110/110
002
5.2
NONE
002
003
005
004 and 004
--/-4.9/
6.5
6.5/
8.7
12.0/16.0
15.8/21.0
--/-13.6/15.6
18.1/20.9
33.4/38.4
43.8/50.5
30.7/
30.7/
35.2/
54.2/
67.2/
30.7
31.5
38.1
60.0
75.7
35/
35/
40/
60/
70/
35
35
40
60
80
31/ 31
31/ 31
32 /36
50/ 56
62/ 70
129/129
129/129
129/129
129/129
129/129
002
1.8
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
15.2
15.2
22.3
26.0
39.6
20
20
25
30
40
15
15
20
24
36
53
53
53
53
53
------
2.1
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
15.5
15.5
22.6
26.4
39.9
20
20
25
30
40
15
15
21
24
37
55
55
55
55
55
------
2.6
NONE
006
008
009
008 and 008
-6.0
11.5
14.0
23.0
-7.2
13.8
16.8
27.7
16.0
16.0
23.3
27.0
40.6
20
20
25
30
45
16
16
21
25
37
64
64
64
64
64
------
1.8
NONE
--
--
10.9
15
12
42
--
2.1
NONE
--
--
11.1
15
12
44
--
2.6
NONE
--
--
11.4
15
12
51
--
254
197
1
254
1
414
508
1
ALT
HIGH
518
632
1
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
--------
Full LoadAmps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fan Motor
Locked
Rotor Amps
Minimum
CircuitAmps
Maximum
Overcurrent
Protection
National
Electrical
Code
OFM
RLA
---
Outdoor
(Condenser)
Rated Load Amps
Fan
Motor
*Used to determine
mhgmum
disconnect
tFuse or HACR circuit breaker.
per
23.3
15.4
118
90
1
1
1/4
1/4
1.4
1.4
8.3
45
1
1/4
9.9
6.4
36
1
1/4
0.9
Determine
maximum
(AB) 457 - 452 = 5
(BC) 464 - 457 = 7
(AC) 457 - 455 = 2
B
deviation
is 7 v.
Determine
percent
of voltage
Imbalance
average
voltage.
imbalance.
7
-457
= 100 x
= 1.53%
This
NEC.
I
amount
IMPORTANT:
electric
utility
3.
of phase
imbalance
MCA
New
= MCA
unit only
max voltage
from average
voltage
voltage
phase
as it is below
imbalance
the maximunl
is more
than
2%,
allowable
contact
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA
and MOCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
deviation
average
is satisfactory
If the supply voltage
company
immediately.
For example,
using
CRPWREXH039A00
C
from
v
v
v
Imbalance
New
= 28.9
+ MCA
of Power
a 50TFF006---5
power exhaust.
amps
+ 1.6 amps
=
I
size wire to include
exhaust
is powered
Determine
the new
with
MCA
=
28.9
and
MOCP
=
35,
with
amps
AB = 452 v
BC = 464v
Voltage
I
local
Exhaust
unit
= 30.5
2%.
your
If the new MCA does not exceed
the published
MOCP, then MOCP
would
not change.
The
MOCP
in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP
is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP
for the power
exhaust will be 15 amps per NEC.
is 460-3-60.
Average
_)
deviation
Maximum
% Voltage
NOTES:
1.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
2.
Unbalanced
3-Phase
Supply
Voltage
Never operate
a motor where a phase imbafance
in supply
vo/tage is greater
than 2%
Use the
following
formula
to determine
the percent
of voltage
imbalance.
A
POINT
PIN
CRSINGLE---AOO
NONE
001
003
002 and 002
OO3 and 003
OO4 and 004
187
ALT
voltage
LRA
004
004
004
LEGEND
Supply
SINGLE
BOX
FLA
3.5
STD
Example:
MOCP*
134/134
134/134
134/134
134/134
134/134
134/134
HiGH
x
MCA
38/ 38
38/ 38
46/ 51
64/ 72
82/ 93
97/110
STD
= 100
FLA
Nominal
kW
DISCONNECT
SlZEf
SUPPLY
45/ 45
45/ 45
50/ 60
70/ 80
90/100
110/125
HIGH
% Voltage
POWER
40.0/
40.0
40.0/
40.0
48.6/
54.7
68.0/
77.1
97.9/100.0
104.2/118.8
005
575-3-69
HEAT
--/-15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
ALT
460-3-69
ELECTRIC
--/-3.3/
4.4
6.5/
8.7
9.3/13.0
13.1/17.4
15.8/21.0
--
208/230-3-60
HEATER
MODEL
NO
CRHEATER---A00
NONE
001
003
002 and 002
OO3 and 003
OO4 and 004
STD
208/230-1-60
IFM
FLA
452
+ 464
3
POWER
EXHAUST
PART NO.
+ 455
AC = 455 v
1371
3
= 457
16
MOCP
(for separate
power source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OAOO
1.6
N/A
0.64
15
CRPWREXHO21AOO
N/A
0.9
N/A
15
CRPWREXHO22AOO
3.3
N/A
1.32
15
CRPWREXHO23AOO
N/A
1.8
N/A
15
CRPWREXHO28AOO
1.7
N/A
0.68
15
CRPWREXHO29AOO
N/A
1 .o
N/A
15
Table 2B -- Electrical Data (With Convenience Outlet) (cont)
VOLTAGE
80TFF,TM
UNIT
SIZE
NOMINAL
V-PH-Hz
COMPRESSOR
RANGE
IFM
TYPE
Min
(ea)
Max
Qty
RLA
OFM(ea)
LRA
Qty
Hp
IFM
FLA
STD
208/230-1-60
FLA
5"9
--
187
254
1
28.8
147
1
1/4
1.4
ALT
6.6
STD
5.9
ALT
187
254
1
16
114
1
1/4
1.4
5.2
ALT
414
508
1
7.4
64
1
1/4
0.8
HIGH
STD
575-3-60
ALT
518
632
1
6.2
HIGH
52
1
1/4
0.8
--------
Full Load Amps
Heating,
Air Conditioning
and Refrigeration
Indoor (Evaporator)
Fall Motor
Locked
Rotor Amps
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
ElectricalCode
OEM
RLA
---
Outdoor
(Condenser)
Rated Load Amps
--/-4.9/
6.5
6.5/
8.7
9.8/13.0
13.1/17.4
15.8/21.0
--/-23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
5010/ 50.0
50.0/
50.0
52.5/
58.6
71.9/
81.0
91.8/103.9
108.0/122.6
60t 60
60/ 60
60/ 60
80/ 90
100/110
110/125
48/ 48
48/ 48
49/ 55
67/ 75
85/ 96
100/114
188/188
188/188
188/188
188/188
188/188
188/188
O04
O04
O04
NONE
OO2
004
005
and 004
and 005
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
32.1/
32.1/
40.7/
55.1/
68.1/
82.4/
32.1
32.4
44.4
60.9
76.5
92.5
40/ 40
40/ 40
45/ 45
60/ 70
70/ 80
90/100
32/
32/
37/
51/
63/
76/
32
32
41
57
70
86
133/133
133/133
133/133
133/133
133/133
133/133
OO2
OO2
002
NONE
0O2
OO4
0O5
004 and 004
004 and 005
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
31.4/
31.4/
39.9/
54.2/
67.2/
81.6/
31.4
31.5
43.5
60.0
75.7
91.6
40/ 40
40/ 40
40/ 45
60/ 60
70/ 80
90/100
32/
32/
37/
50/
62/
75/
32
32
41
56
70
85
153/153
153/153
153/153
153/153
153/153
153/153
OO2
OO2
NONE
OO2
--/-4.9/
6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
33.7/
33.7/
42.7/
57.1/
70.1/
84.4/
33.7
34.4
46.4
62.9
78.5
94.5
40/ 40
40/ 40
45/ 50
60/ 70
80/ 80
90/100
34/
34/
39/4
53/
65/
78/
34
34
3
58
72
87
179/179
179/179
179/179
179/179
179/179
179/179
OO2
OO2
OO2
004
005
and 004
and 005
3.1
NONE
006
008
009
008 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
15.3
15.6
23.9
27.6
41.2
44.2
20
20
25
30
45
45
15
15
22
25
38
41
74
74
74
74
74
74
2.6
NONE
006
008
009
008 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
15.6
16.0
24.3
28.0
41.6
44.6
20
20
25
30
45
45
16
16
22
26
38
41
83
83
83
83
83
83
3.4
NONE
006
008
009
008 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.0
-7.2
13.8
16.8
27.7
30.1
15.6
16.0
24.3
28.0
41.6
44.6
20
20
25
30
45
45
16
16
22
26
38
41
96
96
98
96
96
96
3.1
NONE
--
--
11.5
15
13
60
2.6
NONE
--
--
11.7
15
13
67
3.4
NONE
--
--
11.7
15
13
77
Determine
maximum
deviation
(AB) 457 -452
= 5 v
(BC) 464 - 457 = 7 v
(AC) 457 -455
= 2 v
Maximum
deviation
is 7 v.
Determine
percent
of voltage
% Voltage
A
S
C
Imbalance
deviation
average
voltage
per
This
NEC.
amount
electric
utility
IMPORTANT:
3.
of phase
average
voltage.
imbalance.
7
-- 457
imbalance
from average
voltage
phase
as it is below
imbalance
the maximum
is more
than
2%,
allowable
contact
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA and MOCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
MCA
voltage
is satisfactory
company
immediately.
If the supply
voltage
New
= MCA
unit only
New
= 28.9
+ MCA
of Power
a 50TFFOO6m5
power exhaust.
amps
+ 1.6 amps
your
size wire to include
exhaust
is powered
Determine
the new
with
MCA
=
28.9
and
MOCP
= 35,
is 460-3-60.
Average
Voltage
with
amps
AB = 452 v
BC = 464 v
AC = 455 v
I
local
Exhaust
unit
= 30.5
2%.
If the new MCA does not exceed
the published
MOCR
then MOCP
would not change.
The
MOCP in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP is acceptable. ff "MCA
New" is larger than the published
M©CP,
raise the MOCP
to the next larger
size. For separate
power, the MOCP for the power
exhaust will be 15 amps
per NEC.
POWER
EXHAUST
PART NO.
_)
from
= 100 x
For example,
using
CRPWREXHO3OAO0
max voltage
SINGLE
POINT
BOX PIN
CRSINGLE---A00
NONE
OO2
0O3
002 and 002
003 and 003
004 and 004
hnbalance
Supply
LRA
O04
OO4
OO4
I
Example:
FLA
166/166
166/166
166/186
166/166
166/166
166/166
NOTES:
1. In compliance
with NEC requirements
for muffimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
2. Unbalanced
3-Phase
Supply
Voltage
Never
operate a motor where a phase imbalance
in supply
voltage
ts greater
than 2% Use the
following
formula
to determine
the percent
of voltage
imbalance.
= 100 x
DISCONNECT
SIZEt
= 1.53%
*Used to determine
Ininknum
disconnect
tPuse or HACR circuit breaker.
% Voltage
MOCP*
47/ 47
47/ 47
48/ 54
66/ 75
85/ 96
100/113
c 0s
Fan Motor
SUPPLY
60/ 60
60/ 60
60/ 60
80/ 90
100/110
110/125
LEGEND
FLA
HACR
IFM
LRA
MCA
MOCP
NEC
MCA
49.3/
49.3
49.3/
49.3
51.6/
57.7
71.0/
80.1
90.9/103.0
107.2/121.8
004
004
460-3-60
POWER
FLA
--/-23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
7.5
STD
HEAT
--/-4.9/
6.5
6.5/
8.7
9.8/13.0
13.1/17.4
15.8/21.0
006
HIGH
Nominal
kW
NONE
OO2
OO3
002 and 002
003 and 003
004 and 004
004
004
208/230-3-60
ELECTRIC
HEATER
MODEL
NO,
CRHEATER---A00
=
3
452 + 464
1371
+ 455
3
= 457
17
MOCP
(for separate
power
source)
MCA
(230 v)
MCA
(460 v)
MCA
(875 v)
CRPWREXH03OA00
1.6
N/A
0.64
15
CRPWREXH021A00
N/A
0.9
N/A
15
CRPWREXH022A00
3.3
N/A
1.32
15
CRPWREXH023A00
N/A
1.8
N/A
15
CRPWREXH028A00
1.7
N/A
0.68
15
CRPWREXH029A00
N/A
1.0
N/A
15
Table 2B -- Electrical Data (With Convenience Outlet) (cont)
50TFF, TM
UNIT
SIZE
NOMINAL
V-PH-Hz
IFM
TYPE
VOLTAGE
RANGE
Min
COMPRESSOR
(ea)
Max
Qty
RLA
OFM
LRA
Oty
(ea)
Hp
FLA
IFM
FLA
HEATER
MODEL
NO,
CRHEATER---AOO
ELECTRIC
Nominal
kW
NONE
002
5.2
STD
208/230-3-60
--
187
254
1
20.6
146
1
1/4
1.4
HiGH
7.5
STD
2.6
004
005
004 and
OO4 and
--/-4.9/ 6.5
004
OO5
NONE
002
094
005
9O4andOO4
904 and 905
--
414
508
1
9.5
73
1
1/4
STD
575-3-60
_
518
632
7.6
1
62
1
1/4
0.9
----
Full Load Amps
Heating, Air Conditioning and Refrigeration
Indoor (Evaporator) Fan Motor
LRA
MCA
MOCP
NEC
OFM
RLA
--
Locked
Rotor Amlpss
Minimum
Circuit Amps
Maximum
Overcurrent
Protection
National
Electrical
Code
Outdoor
(Condenser)
Fan Motor
Rated Load Amps
-----
_Used to determine
minimum
disconnect
tFuse or HACR circuit breaker.
per
MCA
MOCP*
45
45
SINGLE
BOX
FLA
LRA
POINT
PIN
CRSINGLE---AOO
--/-13.6/15.6
37.2/37.2
37.2/37.2
45/
45/
21.9/25.3
33.4/39.4
43.8/50.5
55.2/63.8
37.2/39.1
54.2/60.0
67.2/75.7
81.6/91.6
40/ 45
60/ 60
70/ 80
90/100
37_7
37_7
37/41
50/56
62/70
75/85
18_184
18_184
18_184
184/184
184/184
18_184
002
002
--/-4.9/ 6.5
7.9/10.5
12.0/16.9
15.8/21.0
19.9/26.5
--/-13.6/15.6
21.9/25.3
33.4/38.4
43.8/50.5
55.2/63.8
39.5/39.5
39.5/39.5
39.5/49.9
57.1/62.9
70.1/78.5
84.4/94.5
45/ 45
45/ 45
45/ 50
60/ 70
80/ 80
90/100
39_9
39_9
39/43
53/58
65/72
78/87
21_210
21_210
210/210
210/210
21_210
21_210
902
002
002
-6.0
-7.2
17.6
17.6
20
20
908
009
13.8
16.8
27.7
30.7
20.5
27.0
49.6
44.3
25
30
45
45
17
17
21
25
37
41
92
92
92
92
92
92
3.4
NONE
006
008
009
OO9 and 008
008 and 009
-6.0
11.5
14.0
23.0
25.5
-7.2
13.9
16.8
27.7
30.7
18.4
18.4
21.5
29.0
41.6
45.3
25
25
25
30
45
50
18
18
22
26
38
42
105
105
105
105
105
105
2.6
NONE
--
--
13.1
20
14
77
--
3.4
NONE
--
--
13.7
20
15
87
--
008
009
098 and
008 and
LEGEND
FLA
HACR
IFM
FLA
DISCONNECT
SIZEf
SUPPLY
11.5
14.0
23.0
25.5
0.9
HiGH
POWER
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
NONE
006
OO7
460-3-60
HEAT
Determine
(AB) 457
(BC) 464
(AC) 457
Maximum
maximum
deviation
- 452 = 5 v
- 457 = 7 v
- 455 = 2 v
deviation
is 7 v.
Determine
percent
of voltage
from
average
-------
voltage.
imbalance.
7
% Voltage
Imbalance
= 100 x
45_
= 1.53%
NEC.
This
amount
electric
utility
IMPORTANT:
J
of phase
imbalance
is satisfactory
company
immediately.
If the supply
voltage
phase
as it is below
imbalance
the maximum
is more
than
2%,
allowable
contact
2%.
your
I
local
J
NOTES:
1.
2.
In compliance
with NEC requirements
for multimotor
and combination
load equipment
(refer to
NEC Articles
430 and 440), the overcurrent
protective
device for the unit shall be fuse or HACR
breaker.
Canadian
units may be fuse or circuit breaker.
Unbalanced
3-Phase
Supply
Voltage
Never operate
a motor where a phase imbalance
in supply
voltage
is greater
than 2%
Use the
following
formula
to determine
the percent
of voltage
imbalance.
% Voltage
= 100
x
Example:
A
New
= MCA
unit only
For example,
using
CRPWREXHO30AO0
max voltage
C
For units with power
exhaust:
If a single
power
source
is to be used,
power exhaust
MCA
and MOCR
Check MCA and MOCP
when power
through
the unit (must
be in accordance
with NEC and/or
local codes).
MCA including
the power exhaust
using the following
formula:
MCA
Imbalance
Supply
B
3.
deviation
average
voltage
from average
voltage
MCA
voltage
New
= 28.9
AB = 452 v
BC = 464v
amps
POWER
EXHAUST
PART NO.
Average
Voltage
=
of Power
+ 1.6 amps
Exhaust
unit
= 30.5
with
MCA
=
28.9
and
MOCP
=
35,
with
amps
if the new MCA does not exceed
the published
MOCP, then MOCP
would
not change.
The
MOCP
in this example
is 35 amps, the MCA New is below 35, therefore
the MOCP
is acceptable. If "MCA
New" is larger than the published
MOCP, raise the MOCP
to the next larger
size. For separate
power, the MOCP
for the power
exhaust will be 15 amps per NEC.
is 460-3-60.
AC = 455 v
+ MCA
a 50TFFO06---5
power exhaust.
size wire to include
exhaust
is powered
Determine
the new
452
+ 464
3
MOCP
(for separate
power source)
MCA
(230 v)
MCA
(460 v)
MCA
(575 v)
CRPWREXHO3OAOO
1.6
N/A
0.64
15
CRPWREXHO21AOO
N/A
0.9
N/A
15
CRPWREXHO22AOO
3.3
N/A
1.32
15
CRPWREXHO23AOO
N/A
1.8
N/A
15
CRPWREXHO28AOO
1.7
N/A
0.68
15
CRPWREXHO29AOO
N/A
1 .o
N/A
15
+ 455
1371
=-3
= 457
18
Step 6 --
Adjust
Factory-Installed
MANUAL OUTDOOR-AIR
hood and screen me attached
the unit for shipping.
Options
8.
Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 11. Slide blade
vertically until it is in the appropriate position determined
by Fig. 14. Tighten screws.
9.
Remove and save screws cunently on sides of hood.
Insert screen. Secure screen to hood using the screws. See
Fig. 13.
DAMPER -- The outdoor-air
to the basepan at the bottom of
AssemblE;.."
1. Determine quantity of ventilation
Record amount for use in Step 8.
required
opening
for building.
2.
Remove and save outdoor-air
See Fig. 11.
panel and screws.
3.
Separate hood and screen from basepan by removing
4 screws securing them. Save all screws.
4.
Replace outdoor-air
5.
Place hood on front of outdoor-air opening panel. See
Fig. 12 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 13.
6.
Remove and save 6 screws (3 on each side) fiom sides of
the manu_d outdoor-air damper assembly.
7.
Align screw holes on hood with screw holes on side of
manual outdoor-air &tmper assembly. See Fig. 12 and 13.
Secure hood with 6 screws from Step 6.
CONVENIENCE
OUTLET -- An optional convenience outlet provides power for rooftop use. For maintenance pel_onnel
safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service
tools. An optiomfl "Hot Outlet" is available from the factoly as
a special order item.
the
opening panel.
NOVAR CONTROLS
-Optional
(ETM 3051) are available for replacement
tion jobs.
SCREW
HOLES
Novar
controls
or new construc-
'_
(TOP)
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
MANUAL
OUTDOOR-AIR
ADJUSTMENT
SCREWS
SCREEN
LOCATION
(SCREEN
NOT SHOWN)
/
POSITION
SCALE
SETTING
Fig. 13 -- Outdoor-Air Damper
with Hood Attached
DAMPER
BLADE
Fig. 11 -- Damper Panel with Manual Outdoor-Air
Damper Installed
HOOD TOP SCREWS
(HIDDEN)
SCREWS
HOOD
SIDES AND TOPASSEMBLED
C
0
1
2
OUTDOOR
Fig. 14-
HOOD
SIDE
Fig. 12-
Outdoor-Air
Hood Details
19
3
4
AIRFLOW
5
6
7
(cfm x 100)
Outdoor-Air Damper Position Setting
PREMIERLINK
rM CONTROL
-- Tile PremierLink controllet is compatible
with Career Comfort Network®
(CCN)
devices. This control is designed to allow usel5 file access and
ability to change factory-defined
settings, thus expanding the
function of the stan&trd unit control board. CmTier's diagnostic
standard tier display tools such as Navigator TM or Scrolling
Marquee can be used with the PremierLink contmfler.
NOTE: The sensor must be mounted in the discharge airstream
downstream of file cooling coil and any heating devices. Be
sure the probe tip does not come in contact with any of the unit
or heat surfaces.
Outdoor Air Temperature (OAT) Sensor -- When the unit is
supplied with a factou-mounted PremierLink control, the
outdoor-air temperature sensor (OAT) is factou-supplied and
wimdi
The PremierLink contmfler (see Fig. 15A and 15B) requires
the use of a Canier electronic thermostat or a CCN connection
for time broadcast to initiate its intermfl fimeclock. This is
necessary for broadcast of time of day functions (occupied/
unoccupied). No sensors am supplied wifli the field-mounted
PremierLink control. The factory-installed
PmmierLink
control includes only file supply-air temperature (SAT) sensor and
the outdoor air temperature
((-)AT) sensor as standard. An
indoor air qutflity (CO2) sensor can be added as tin option.
Refer to Table 3 for sensor usage_ Refer to Fig. 16 for
PremierLink controller wiring. The PmmierLink control may
be mounted in the control panel or an area below the control
Install the Indoor Air Quality (CO2'_Sensor -- Mount the
optional indoor air quality (CO2) sensor according to manufacturer specifications.
A separate field-supplied transformer must be used to power the CO 2 sensol:
Wire the CO 2 sensor to the COM and IAQI terminals of J5
on the PremierLink controller Refer to the PremierLink [nstallation, Start-up, and Configuration Instructions for detailed
wiring and configuration information.
Enthalpy Sensors and Control -- The enthalpy control
(HH57AC077) is supplied as a field-installed accesso U to be
used with the economizer damper control option. The outdoor
air enthalpy sensor is part of the enthalpy control. The separate
field-installed
accessory
return
mr enthalpy
sensor
(HH57AC078) is required for differential enthalpy control.
NOTE: The enthalpy control must be set to the "D" setting for
diffemnfial enthalpy control to work properly.
The enthalpy control receives the indoor and return
enthalpy from the outdoor and return air enthalpy sensors and
provides a diy contact switch input to the PremierLink controllel: Locate the controller in place of an existing economizer
controller or near the actuatol: The mounting plate may not be
needed if existing bracket is used.
A closed contact indicates that outside air is prefened to the
return ail: An open contact indicates that the economizer
should remain at minimum position.
panel.
NOTE: PremierLink
controller versions 1.3 and later me
shipped in Sensor mode. If used with a thennostat,
the
PremierLink controller must be configured to Thermostat mode.
Install the Supply Air Temperature
(SAT) Sensor -- When
the unit is supplied with a factou-mounted
PremierLink control, the supply-air temperature (SAT) sensor (33ZCSENSAT)
is factou-supplied
and wired. The wiring is muted fl_)m the
PremierLink control over the control box, through a grommet,
into the fan section, down tflong the back side of the fan, and
along the fan deck over to file supply-air opening.
The SAT probe is wire-tied to the supply-air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re-position the sensor in the flange of
the supply-air opening or in the supply air duct (as required by
local codes). Drill or punch a I/_-in. hole in the flange or duct.
Use two field-supplied, self-diilling screws to secure the sensor
probe in a horizontal orientation.
HVAC SENSOR INPUTS
0
0
(
SPACE TEMP
SET POINT
_u
SPT
"
SUPPLY AIR TEMP
OUTDOOR
i
_
TEMP
INDOOR
AIR QUALITY
OUTDOOR
AIR QUALITY
_
Q
_-
I
t
_
.
°
Bus#
oi PremzerL_nk
..... --
DUAL MODE SENSOR/STAT
COMP SAFETY (Y1)
FIRE SHUTDOWN
(Y2)
_m .........
SUPPLY FAN STATUS (W1)
NOT USED (W2)
ENTHALPY
STATUS (ENTH) /
.......................
_,
.a
sa
_
/
CCN/LEN
PORT
NAVIGATOR
PORT
/
4-20MA
ECONOMIZER
!
t
I
I
I
INDOOR
FAN MOTOR
I
•
I
2O
I
I
•
t
I
t
I
I
I
"4 "-4 "-.,
COMPR
1 &2
OUTPUTS
Fig. 15A -- PremierLink Controller
I
HEAT
LOW/HIGH
EXHAUST
RVS VALVE
OO
PREMIERLINK
CONTROL
o
,,j
/
HINGED
DOOR
PANEL
/O
Fig. 15B -- PremierLink
l
Controller (Installed)
TM
Table 3 -- PremierLink Sensor Usage
APPLICATION
Dry Bulb
Temperature
with
PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
Differential
OUTDOOR
TEMPERATURE
AIR
SENSOR
RETURN
TEMPERATURE
AIR
SENSOR
OUTDOOR
AIR
ENTHALPY
SENSOR
RETURN AIR
ENTHALPY
SENSOR
Included -HH79NZ017
Dry Bulb
Temperature
with
PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
Included -HH79NZ017
Required -33ZCT55SPT
or Equivalent
--
--
Single Enthalpy
with
PremierLin
k*
(PremierLink
requires
4-20 mA
Actuator)
Included -Not Used
_
Required -HH57AC077
_
Differential
Enthalpy
with PremierLink*
(PremierLink
requires
4-20 mA
Actuator)
Included -Not Used
_
Required -HH57AC077
Required -HH57AC078
*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and
Outdoor Air Temperature sensor HH79NZ017 -- Included with factory-installed PremierLink control;
field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO2 Sensors (Optional):
33ZCSENCO2 -- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 -- Aspirator box used for duct-mounted CO2 room sensor.
33ZCT55CO2 -- Space temperature and CO2 room sensor with override.
33ZCT56CO2 -- Space temperature and CO2 room sensor with override and set point.
2. All units include the following Standard Sensors:
Outdoor-Air Sensor -- 50HJ540569 -- Opens at 67 F, closes at 52 F, not adjustable.
Mixed-Air Sensor -- HH97AZ001 -- (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperature Sensor HH79NZ017).
Compressor Lockout Sensor -- 50HJ540570 -- Opens at 35 E closes at 50 R
2!
rio
_.
* 3
_
.............
_/
11
"-
6
VIO
_
11
@
8
/
2
\
.........
RED
_X._J
_
2
/qT_ /
PremierLink
....
SpaceTempJ Set
4,,( _
YEL
]
BRN
•
BRN_
_z
RED
_GRN
BRN
_
_!1
Indoor Ai
_
ii
..............
Quality
6_
_BLU
Sensor
f
8
_
i i f
i I
ORN-
GRA
ll!
_
Jl
PWR
0 20 mA
PP'MP
Re ays
OOMMS
........................
..............................................
?_
.............................
,.............................
.................
.................
..........
YEL
ORN
WHT
............
'/
"
:
PNK
:1
\TR1_I
:i [[J\
/7\/
_S:_
i
_t
OUTDOOR
C
0
0
BLK
"i"
_
RED
i
8LU _
WH]
" _
4 [[1_
5_[)
................
PNK
ORN
_-"
ORN
PNK
_
[
ORN
i
nED
_.vl
l
'LL/
i
WHT
GRA
TB-1
2
3 {_Y2
..............................................
4 []DW!
....
6 _[).JSL
wm
GRAY
Co,r_r
CON
i
i
i
L
_
7 (][_,
WHT
BLK
[RED,
i
8 (1_
XC/
COMMS-RETURNAIROAT
-ENTHALPY
SENSOR PWR
-RTU
-SAT
-TB
--
8LK
"
7 rl] % C
LEGEND
Communications
Outdoor Air Temperature Sensor
Power
Rooftop Unit
Supply Air Temperature Sensor
Terminal Block
Fig. 16 -- Typical PremierLink
Outdoor
Air
Enthalpy
SensoffEnthalpy
Controller
(HH57AC077)
-- To wire the outdoor tfir enthalpy sensor.
perform the following (see Fig. 17 and 18):
NOTE: The outdoor air sensor can be removed from the back
of the enth_dpy controller and mounted remotely.
1. Use a 4-conductor.
18 or 20 AWG cable to connect the
enthalpy control to the PremierLink controller and power
tmnsformec
2.
BRN
i_
!
E....... lSer2
PNK
iGRA
3 /] _
i
AIR
!_
_
XLW
SFS
ENTHALPYSENSOR
'
l
] ....
[ 4TR)
_[_H
11_
,_,u-_
_
41
Connect the following 4 wires from the wire htuness
located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TRI)
on enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal
(TR) on enthalpy sensor and to pin 4 on 12-pin
harness.
c. Connect the GRAY/ORN
wire to J4-2 on PremierLink controller and to terminal (3) on enthalpy sensoc
d. Connect the GRAY/RED
wire to J4-1 on PremierLink controller and to terminal (2) on enthalpy sensoc
,._/
RZUt_m_i_l
Board
8#-_X
Controls Wiring
TM
2.
At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
3.
Connect the field-supplied
RED wire to (+) spade
connector on the return air enthalpy sensor and the (SR+)
terminal on the enthalpy controllec Connect the BLK
wire to (S) spade connector on the return air enthalpy
sensor and the (SR) terminal on the enthalpy controller.
ENTHALPY
CONTROLLER
RED
A6
C
TRrI'ITRII__
soi-h
+13
SRI-h
BRN
--i
+
_S
BLK
RED
I
[]
S (RETURN
rl
+
-G RAY/O
I
AIR [
ENTHALPY
SENSOR
RN
LWIRE
LED
NOTE: If installing in a Carrier rooftop, use the two gray wires
provided from the control section to the economizer to connect
PremierLink controller to terminals 2 and 3 on enth_dpy sensoc
AIR
ENTHALPY
(OUTDOOR
SENSOR)
GRAY/RED
JiN
HARNESS
UNIT
NOTES:
1. Remove factory-installed jumper across SR and + before connecting wires from return air sensor.
2, Switches shown in high outdoor air enthalpy state. Terminals 2
and 3 close on low outdoor air enthalpy relative to indoor air
enthalpy.
3. Remove sensor mounted on back of control and locate in outside airstream.
Return Air Enthalpy Sensor -- Mount the return-air enthalpy
sensor (HH57AC078)
in the return-air duct. The return air
sensor is wired to the enth_dpy controller (HH57AC077).
The
outdoor enthalpy changeover set point is set at the controller.
To wire the return air enthalpy sensor, perform the following (see Fig. 17):
1. Use a 2-conductor,
18 or 20 AWG. twisted pair cable to
connect the return air enthalpy sensor to the enthalpy
controller.
Fig. 17 -- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control
22
HH57AC077
ENTHALPY
CONTROL AND
•OUTDOOR AIR
ENTHALPY SENSOR
ECONOMI$ER
IV
-CONTROLLER
OUTSIDE AIR
HARNESS
¢
ACTUATOR-
TEMPERATURE
SENSOR
LOW AMBIENT
SENSOR
/
I '
HH57AC078 ENTHALPY
SENSOR(USED
WITH
ENTHALPY CONTROL
FOR DIFFERENTIAL
ENTHALPY OPERATION)
Fig. 195.
÷
÷
MOUNTING PLATE
6.
%
Fig. 18Differential
Enthalpy Control,
Sensor and Mounting
Plate (33AMKITENT006)
OPTIONAL
ECONOMI$ER
[V AND ECONOMISER2
See Fig. 19 for EconoMi$er
IV component
locations.
Fig. 20 for EconoMiSer2 component locations.
7.
-See
8.
NOTE: These instructions
are for installing the optional
EconoMiSer IV and EconoMiSer2 only. Refer to the accessory
EconoMi$er IV or EconoMiSer2 installation instructions when
field inst_flling an EconoMiSer IV or EconoMiSer2 accesso q.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged
from the track and can be removed. See
Fig. 21.
2. The box with the economizer
hood components
is
shipped in the compartment behind the economizel: Tile
EconoMi$er
IV controller is mounted
on top of the
EconoMiSer IV in the position shown in Fig. 19. The
optional EconoMi$er2
with 4 to 20 mA actuator signal
control does not include the EconoMi$er IV controllel:
To remove the component box from its shipping position,
remove the screw holding the hood box bracket to the top
of the economizel: Slide the hood box out of the unit. See
Fig. 22.
9.
10.
4.
Locations
Remove file shipping tape holding the economizer barometric relief damper in place.
Insert the hood divider between the hood sides. See
Fig. 24 and 25. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bottom filter rack for the aluminum filtel:
Open file filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rock (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. See Fig. 25.
Caulk the ends of the joint between the unit top panel and
the hood top. See Fig. 23.
Replace the filter access panel.
[nsmll all EconoMiSer IV accessories.
EconoMi$er IV
wiring is shown in Fig. 26. EconoMiSer2 wiring is shown
in Fig. 27.
Outdoor Air Temperature
(OAT) Sensor -- The outdoor air
temperature sensor (HH57AC074)
is a 10 to 20 mA device
used to measme the outdoor-air temperature. The outdoor-air
temperature is used to determine when the EconoMiSer IV can
be used for free cooling. The sensor is factory-installed
on the
EconoMiSer
IV in the outdoor airstream. See Fig. 19. The
operating range of temperature measurement is 40 to 100 E
Supply Air Temperature
(SAT) Sensor
-- The supply air
temperature sensor is a 3 K thermistor located at the inlet of the
indoor fan. See Fig. 31. This sensor is factory installed. The
operating range of temperature measurement is 0 ° to 158 E See
Table 4 for sensor temperatme/resistance
values.
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the "crimp end"
and is sealed from moisture.
The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 23.
Swing out indoor coil access panel and
sides under the panel (hood top). Use the
to attach the hood sides to the hood top.
vided to attach the hood sides to the unit.
IV Component
Bmometric flow capacity is shown in Fig. 28. Outdoor air
leakage is shown in Fig. 29. Return air pressure drop is shown
in Fig. 30.
ECONOMISER
IV STANDARD
SENSORS
installed on the unit, the hood shipped with the unit will not
be used and must be discarded. Save the aluminum
filter
IMPORTANT:
If the power exhaust accessory is to be
for use in the power exhaust hood assembly.
3.
EconoMi$er
Outdoor Air Lockout
Sensor
-- The EconomiSer IV is
equipped with an mnbient temperature lockout switch located
in the outdoor air stream which is used to lockout the compressors below a 42 F ambient temperature. See Fig. 19.
insert the hood
screws provided
Use screws proSee Fig. 24.
23
C22_
-_
AIR
HOOD
UTDOOR
ECONOMI$ER2
HOOD
SHIPPING
teB
BRACKET
PLUG
_'_
BAROMETRIC
RELIEF
DAMPER
DAMPER
Fig. 20 -- EconMi$er2 Component
FILTER ACCESS
GEAR DRIVEN
Locations
PANEL
SIDE
PANEL
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR
OPENING AND
INDOOR COILACCESS
PANEL
TOP
SIDE
PANEL
Fig. 21 -- Typical Access Panel Locations
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
Fig. 23 -- Indoor Coil Access Panel Relocation
TOP
HOOD BOX
BRACKET
i/
INDOORCOIL
ACCESS
PANEL
I
it
I
I
LEFT
/
I
I
I
11
SIDE
0
I
!
!
Fig. 22 -- Hood Box Removal
33 3/8"
HOOD DIVIDER
Fig. 24 -- Outdoor-Air
24
Hood Construction
Table 4 -- Supply Air Sensor
Temperature/Resistance Values
TEMPERATURE
-58
-40
(F)
/
_
17 1/4"
--
RESISTANCE (ohms)
200,250
100,680
-22
-4
53,010
29,091
14
32
16,590
9,795
50
68
5,970
3,747
77
86
3,000
2,416
104
122
140
1,597
1,080
746
158
176
525
376
185
194
321
274
212
230
203
153
248
257
116
102
266
284
89
70
302
55
HOOD
ALUMINUM
FILTER
BAROMETRIC
RELIEF
FILTER
CLIP
Fig. 25 -- Filter Installation
FOR OCCUPANCY
REPLACE
JUMPER
j-FIELD-SUPPLIED
//
_ N1
BLK
'R_O_POT_I_O_m)-
WITH
TIME CLOCK
BLK
_V
BLK
T_
BLK
WHT
!,_Oc_%
i
RED
IOV
_
EXN
_-_i_
_ _ ___ _ _
CONTROL
P.K
VlO-
#(
)EIELD
ACCESSORY)
RENOIE
NIN
POSITION
POT
,
ECONOMIIERIV
BOARS
PL6-R
pos
% 77°
OPEN
--
r
I
FIELD _S_LL_D
IAO SENSOR
,"
I
I
]
]
I I
lOV
RRD-i
RAFIENFNALPY
SENSOR
)FIELDACCZSSORY)__L
2V
SR*
(NOr USED)
,'
SENSOR
1 1
]
HAX
O
Ev
0AFFE.P,
ERTRALPY
BLK--
I I
_
{NOT USED}
<
IOV
FREE
B
C
_[]
A
--
O
FIELD
I
FIELD
<
BLU
<
<
SPLICE
SPLICE
BRN
L
)NOr USED)
TAN
6RY
ORG
TO PWR EXHAUST
ACCESSORY
LEGEND
DCV-- Demand Controlled Ventilation
IAQ -- Indoor Air Quality
LA -- Low Ambient Lockout Device
OAT-- Outdoor-Air Temperature
POT-- Potentiometer
RAT-- Return-Air Temperature
Potentiometer Defaults Settings:
Power Exhaust
Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting
(Nor
USED)
NOTES:
1, 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3, For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position,
Fig. 26 -- EconoMi$er IV Wiring
25
BLACK
4
3
5
?
2
500 OHM
_J<>l
RESISTOR-
"_
8
VIOLET
I
i-
I
I
NOTE
6
T
NOTE1
3
. ___1_
I
+_-I ....
J
PINK
7
I
I
RED
I
I
J
10
I
50HJ540573
ACTUATOR
ASSEMBLY
1
I
S
OPTIONAL CO2
SENSOR 4 - 20 rnA
OUTPUT
11
u
ku
>-
9
WHITE
DIRECT DRIVE
ACTUATOR
12
ECONOMIZER2
NOTES:
1. Switch on actuator must be in run position for econornizer to operate.
2. PremierLink TM control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00
enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
PLUG
dry bulb sensor or HH57A077
Fig. 27 -- EconoMi$er2 with 4 to 20 mA Control Wiring
_o
W
eooo
2500
w
D
5000
2000
w
1500
w
w
L
1000
4000
w
iii
i
i
i
i
ii
_,_
_iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
w
w
L
©
s'
I
500
©
z
3000
2000
1000
z
0.'05
S
0115
L
STATIC
0.'25
PRESSURE
o
S
(in. wg)
0.05
0.10
0.15
0.20
0.25
0.30
L
STATIC
PRESSURE
(in. wg)
Fig. 28 -- Barometric Flow Capacity
Fig. 30-
Return-Air
Pressure
Drop
/
LU
I--
30
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
z_ 25
13:: 20
D_
_
W
kU
U.
o
o
z
LOCATION
15
\
10
SUPPLY
AIR
TEMPERATURE
SENSOR
5
0
0.13
0.20
0.22
0.25
0.30
0.35
0.40
0.45
0.50
t_
_I
LL
STATIC
PRESSURE
(in. wg)
Fig. 29 -- Outdoor-Air Damper Leakage
s
Fig. 31 -- Supply Air Sensor Location
26
0.35
ECONOMI$ER IV CONTROL MODES
temperature airstream is used for cooling. When using this
mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. See Fig. 32.
IMPORTANT:
Tile optional
EconoMiSer2
does not
include a controllel: The EconoMiSer2 is operated by a 4 to
20 mA signal from an existing field-supplied
controller
(such as PremierLink TM control). See Fig. 27 for wiring
information.
Outdoor Enthalpy Changeover
-- For enthalpy control, accessory enthalpy sensor (part number HH57AC078)
is required. Replace the stan&_rd outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting
location. See Fig. 19. When the outdoor air enthalpy rises
above the outdoor enthalpy changeover set point, the outdoortdr dmnper moves to its minimum position. The outdoor
enthalpy changeover set point is set with the outdoor enthalpy
set point potentiometer on the EconoMiSer IV controllec The
set points are A, B, C, and D. See Fig. 35. The factory-installed
620-ohm jumper must be in place across terminals SR and SR+
on the EconoMiSer IV controllel: See Fig. 19 and 36.
Determine tile EconoMiSer IV control mode befole set up of
the control. Some modes of operation may requile diffelent sensors. Refer to Ntble 5. The EconoMiSer IV is supplied from the
factory with a supply air temperature sensor and an outdoor air
temperature
sensol: This allows
for operation
of the
EconoMiSer IV with outdoor air dry bulb changeover control.
Additional accessories c_m be added to allow for different types
of changeover control and operation of the EconoMiSer IV and
unit.
Table 5 -- EconoMi$er IV Sensor
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy
Differential
Enthalpy
Usage
ECONOMI$ER IV WITH OUTDOOR
DRY BULB SENSOR
AIR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting
location. See Fig. 19. Mount the return air enth_dpy sensor in
the return _dr duct. See Fig. 34. Wiring is provided in the
EconoMi$er IV wiring hmness. See Fig. 26. The outdoor enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer
on the EconoMiSer IV controller. When
using this mode of changeover control, turn the enthalpy set
point potentiometer fully clockwise to the D setting.
HH57AC078
HH57AC078
and
CRENTDIF004A00*
CO2 for DCV
Control using a
Wall-Mounted
CO2 Sensor
CO 2 for DCV
Control using a
Duct-Mounted
CO2 Sensor
Differential Enthalpy Control
-- For differential
enthalpy
control, the EconoMiSer IV controller uses two enthalpy sensors (HH57AC078
and CRENTDIF004A00),
one in the outside air and one in the return air duct. The EconoMiSer IV
controller compares the outdoor air enthalpy to the return air
enth_dpy to determine EconoMiSer
IV use. The controller
selects the lower enthalpy air (return or outdoor) for cooling.
For example, when the outdoor air has a lower enth_dpy than
the return ail, the EconoMiSer IV opens to bring in outdoor air
for free cooling.
33ZCSENCO2
and
33ZCASPCO2**
33ZCSENCO21-
CRCBDIOX005A001-1-
Indoor Air Quality (IAQ) Sensor Input -- The IAQ input
can be used for demand control ventilation control based on the
level of CO 2 measured in the space or return air duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQI terminals of the controller Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined
set point. See Fig. 37.
If a separate field-supplied transformer is used to power the
[AQ sensor, the sensor must not be grounded
or the
EconoMiSer IV control board will be dmnaged.
*CRENTDIF004A00
and CRTEMPSN002A00
accessories
are
used on many different base units. As such, these kits may contain parts that will not be needed for installation.
1-33ZCSENCO2 is an accessory CO2 sensor.
**33ZCASPCO2
is an accessory aspirator box required for ductmounted applications.
1-1-CRCBDIOX005A00
is an accessory
that contains
both
33ZCSENCO2 and 33ZCASPCO2 accessories.
Outdoor Dry Bulb Changeover
-- The stan&_rd controller is
shipped from the factory configured
for outdoor dry bulb
changeover control. The outdoor air and supply air temperature
sensors are included as stan&_rd. For this control mode, the
outdoor temperature is compmed to an adjustable set point
selected on the control. If the outdoor-air temperature is above
the set point, the EconoMi$er
IV will adjust the outdoor-air
dampers to minimum position. If the outdoor-air temperature is
below the set point, the position of the outdoor-air dampel.s will
be controlled to provide free cooling using outdoor all: When
in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover
temperature set point is
controlled by the free cooling set point potentiometer
located
on the control. See Fig. 32. The scale on the potentiometer is A,
B, C, and D. See Fig. 33 for the conesponding
temperature
changeover values.
FAN SET POINT
WHEN EXHAUST
CONTACT IS MADE
POSITION
SETTING
DEMAND CONTROL
VENTILATION SET POINT
DEMAND CONTROL
VENTILATION iNPUT
IS ABOVE SET POINT
VENTILATION
Differential Dry Bulb Control -- For differenti_d @ bulb
control the stan_lard outdoor dry bulb sensor is used in conjunction with an additiomd accessory @ bulb sensor (part number
CRTEMPSN002A00).
The accessory sensor must be mounted
in the return airstream. See Fig. 34. Wiring is provided in the
EconoMiSer IV wiring harness. See Fig. 26.
SET POINT
LED LIGHTS WHEN
OUTDOOR AIR IS
SUITABLE FOR
FREE COOLING
CHANGEOVER
Fig. 32 --
In this mode of operation, the outdoor-air temperature is
compared
to the return air temperature
and the lower
27
ENTHALP_
SET POINT
EconoMi$er
IV Controller
and LED Locations
Potentiometer
19.
18- _'_
ECONOMI$ER
I
LED _ON
X
]_
CONTROLLER
17LED OFF
16---
LED ON
ECONOMI$ER
]_Z
15<
E14-
LED OFF-
13"
12-
-LED
OFF_"_
LED ON-
--
1110"
I
40
45
50
55
60
65
DEGREES
70
75
80
85
90
95
100
FAHRENHEIT
SENSOR
Fig. 33 -- Outside Air Temperature
Changeover Set Points
-
RETURNAIR
RETURN DUCT
(FIELD-PROVIDED)
Fig. 34 -- Return Air Temperature or Enthalpy
Sensor Mounting Location
CONTROL
CURVE
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
A
73 (23}
B
70 (21)
C
D
67 (19}
63 (17)
85
90
95
100
105
110
(29)
(32)
(35)
(38)
(4I)
(43)
"1,,,
,,./
7-,
\
-,./
/..
\
5(
\
\
X
\
HIGH
35
(2)
40
(4)
45
(7)
APPROXIMATE
50
(10)
DRY
55
(13)
BULB
60
(16)
65
(18)
70
(21)
75
(24)
TEMPERATURE--
Fig. 35 -- Enthalpy
80
(27)
85
(29)
95
(35)
100
(38)
°F (°C)
Changeover
28
90
(32)
Set Points
\
105
(41)
CURVE
110
(43)
LIMIT
enter the building. Make minimum position adjustments with
at least 10 F temperature difference between the outdoor and
leturn-air temperatures.
m
I bll_
PU
II
24
Vac
HO_T_
_Mi0
T_
To determine the minimum
following procedure:
24 Vac
OOM
Open
2
V_l
5
T o = Outdoor-Air Temperature
OA = Percent of Outdoor Air
4
T R= Return-Air Telnperature
RA = Percent of Return Air
T M = Mixed-Air
EF1
the supply air sensor from terminals
3.
Ensure that
terminals P
used, make
Fig. 26 and
turned fully
Connect 24
the factory-installed jumper is in place across
and PI. [f remote dmnper positioning is being
sure that the terminals are wired according to
that the minimum position potentiometer
is
clockwise.
vac across terminals TR and TRI.
5000
4.
z
4000
800 pprn
z<
1000 ppm
+1100
ppm
+
9OOppm
__
Carefully adjust the minimum position potentiometer
until the measured mixed-air temperature matches the
calculated value.
6.
Reconnect
0
2
3
4
5
6
7
Fig. 37
--
CO
2
Sensor
Maximum
the supply air sensor to terminals T and TI.
Remote control of the EconoMiSer IV dmnper is desirable
when
requiring
additional
temporary
ventilation.
If a
field-supplied remote potentiometer (Honeywell Dut number
$963B1128)
is wired to the EconoMiSer
IV controller, the
minimum position of the damper can be controlled fi_m a remote location.
1000
DAMPER VOLTAGE FOR MAX VENTILATION
T and
5.
3000
E
Z
air
is
Disconnect
TI.
6000
+
Temperature
2.
CO2 SENSOR MAX RANGE SETTING
W
the
using the
As an example, if local codes require 10% outdoor
during occupied conditions, outdoor-air temperature
60 IF.and return-air temperature is 75 E
(60 x. 10) + (75 x .90) = 73.5 F
Fig. 36 -- EconoMiSer IV Control
2000
perform
2
Ma/
0V
DCV
FFr_I
8
setting,
1. Calculate the appropriate mixed air temperature
following formula:
OA
RA
(To x 1---_ ) + (TR x 1---_-_-) = T M
Pos
MEx©
T _I_]I
position
8
RATE
Range
To control the minimum damper
the factory-installed jumper on the
EconoMiSer IV controllel: Wire the
ter to the P and PI terminals on the
See Fig. 36.
Setting
Exhaust Set Point Adjustment
-- The exhaust set point will
determine when the exhaust fan runs based on &_mper position
(if accessory power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometer
See Fig. 32. The set point represents the damper position above
which the exhaust fans will be turned on. When there is a call
for exhaust, the EconoMiSer IV controller provides a 45 _+15
second delay before exhaust fan activation to allow the dampers to open. This delay allows the &tmper to reach the appropriate position to avoid unnecessary fan overload.
position remotely, remove
P and PI terminals on the
field-supplied potentiomeEconoMiSer IV controllel:
Damper Movement
-- Damper movement from full open to
lull closed (or vice versa) takes 21/2 minutes.
Thermostats
-- The EconoMiSer IV control works with conventional thermostats that have a YI (cool stage 1), Y2 (cool
stage 2), WI (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er
[V control does not support space temperature
sensors. Connections me made at the themlostat terminal connection board located in the main control box.
Occupancy Control -- The factory default configuration for
the EconoMiSer IV control is occupied mode. Occupied status
is provided by the black jumper from terminal TR to terminal
N. When unoccupied mode is desired, install a field-supplied
timeclock lunction in place of the jumper between TR and N.
See Fig. 26. When the timeclock contacts are closed, the
EconoMiSer IV control will be in occupied mode. When the
timeclock contacts are open (removing the 24-v signal from
terminal N), the EconoMiSer IV will be in unoccupied mode.
Minimum Position Control -- There is a minimum &tmper
position potentiometer on the EconoMiSer IV controllel: See
Fig. 32. The minimum dmnper position maintains the minimum airflow into the building during the occupied period.
When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC
(volatile organic compound)
ventilation requirements.
The
maximum demand ventilation position is used for fully occupied ventilation.
Demand Controlled Ventilation (DCV)
EconoMi$er
IV for demand controlled
some equipment selection criteria which
When selecting the heat capacity and
equipment, the maximum ventilation rate
design conditions. The maximum damper
culated to provide the desired fresh ail:
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the occupied ventilation position. The maximum demand ventilation
position should be turned fully clockwise.
Adjust the minimum position potentiometer
to _llow the
minimum amount of outdoor air. as requiled by local codes, to
29
-- When using the
ventilation, there me
should be considered.
cool capacity of the
must be evaluated for
position must be cal-
Typically tile maximum ventilation rate will be about 5 to
10_ , more than the typical cfm required per pe_on, using
normal outside air design criteria.
since the CO 2 sensor voltage will be ignored by the
EconoMiSer IV controller until it rises above the 3.6 volt setting of the minimum position potentiometel:
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the required ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition air at a maximum
ventilation rate that is greater than the lequired ventilation rate
for maximum occupancy. A proportional-anticipatory
strategy
will cause tile fresh air supplied to increase as the room CO2
level increases even though the CO 2 set point has not been
reached. By the time the CO 2 level reaches the set point, the
damper will be at maximum ventilation and should maintain
the set point.
In order to have the CO2 sensor control the economizer
damper in this manner, first detemfine file damper voltage output for minimum or base ventilation. Base ventilation is the
ventilation required to remove contaminants
during unoccupied periods. The following equation may be used to determine
the percent of outside-air entering the building for a given
damper position. For best results thele should be at least a
10 degree difference in outside and leturn-air temperatures.
Once the fully occupied dmnper position has been determined, set ti3e maximum dalnper demand control ventilation
potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels.
OA
1-]"_)
(Tox
+(TRx
CO, Sensor Configuration
-- The CO 2 sensor has preset
standard voltage settings timt can be selected anytime after the
sensor is powered up. See Table 6.
Use setting 1 or 2 for Carrier equipment. See Table 6.
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2.
Press Mode twice. The STDSET
3.
Use tile Up/Down
Table 6.
4.
Press Enter to lock in file selection.
5.
Press Mode to exit and resume normal operation.
RA
I'T_)=TM
T R = Return-Air Temperature
RA = Percent of Return Air
T M= Mixed-Air Temperature
Once base ventilation has been detemfined, set the minimum dmnper position potentiometer to the correct position.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate
of 5% and an output of 6.7 volts provides the maximum ventihttion rate of 20% (or base plus 15 cfln per person). Use Fig. 37
to determine the maximum setting of the CO 2 sensor For example, a 1100 ppm set point relates to a 15 cfln per person design. Use the 1100 ppm curve on Fig. 37 to find the point when
the CO 2 sensor output will be 6.7 volts. Line up the point on the
graph with the left side of the chart to determine that the range
configuration for the CO 2 sensor should be 1800 ppm. The
EconoMiSer IV controller will output the 6.7 volts from the
CO 2 sensor to the actuator when the CO 2 concentration in the
space is at 1100 ppm. The DCV set point may be left at 2 volts
2.
Press Mode twice. The STDSET
3.
Use the Up/Down
and press Entel:
4.
Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until file desired setting is reached.
5.
Press Mode to move through the variables.
6.
Press Enter to lock in the selection,
continue to the next vmiable.
Dehumidification
mation from
on any zone
a device
duce the
building
heating
move
2
Interface w/Standard
Building Control System
the humidity
commemial
applications.
Settings
1000
5O
0-2000
1100
5O
0-1100
1100
5O
0-10V
4-20 mA
0-10V
4-20 mA
0- 900
900
5O
0-1100
1100
5O
0- 900
900
5O
Proportional
0-10V
4-20 mA
0-10V
4-20 mA
0-9999
5000
5OO
Proportional
0-10V
4-20 mA
0-2000
700
5O
Proportional
20
Exponential
15
ppm --
for most
0-2000
Any
Economizer
Exponential
Parking/Air Intakes/
Loading Docks
loads
0-10V
4-20 mA
0-10V
4-20 mA
Proportional
15
9
such as a 62AQ energy recovely
unit is added to remoisture content of the fresh air being brought into the
when file enthalpy
is high. In most cases, the normal
and cooling
processes
am morn than adequate
to m-
5O
Proportional
Health & Safety
Infor-
1000
4
8
--
0-2000
Any
Any
7
Control
0-10V
4-20 mA
2-10V
7-20 mA
Proportional
Exponential
6
DCV
OPTIONAL
RELAY SETPOINT
(ppm)
3
5
Air with
ASHRAE
indicates
that the largest humidity
load
is the fresh air introduced.
For some applications,
CO2
CONTROL RANGE
(ppm)
(elm/Person)
1
of Fresh
2O
menu
then press Mode to
ANALOG
OUTPUT
OUTPUT
VENTILATION
RATE
Menu will appem:
button to toggle to the NONSTD
If normal rooftop heating
and cooling
operation
is not adequate for the outdoor humidity
level, an energy recovery
unit
and/or a dehumidification
option should be considered.
Table 6 -- CO2 Sensor Standard
EQUIPMENT
button to select the preset numbel: See
The custom settings of the CO 2 sensor can be changed anytime after the sensor is energized. Follow the steps below to
change file non-stan&trd settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
T o = Outdoor-Air Temperature
OA = Percent of Outdoor Air
SETTING
Menu will appear
LEGEND
Parts Per Million
3O
RELAY
HYSTERESIS
(pprn)
Step 7 -- Adjust Evaporator-Fan
Speed -- Adjust evaporator-fan rpnl to meet jobsite conditions. See Table 7
for fan rpm at motor pulley settings. See Table 8 for motor
performance
data. See Tables 9 and 10 for accessory trod
option static pressure drops. See Table 11 for evaporator motor
efficiency. Refer to Tables 12-41 to determine
fan speed
settings.
For units with accessory electric heating, required minimum
cfm is 900 for 50TFKTM004;
1200 for 50TFF.TM005;
1500
for 50TFETM006;
and 1800 for 50TFETM007.
DIRECT-DRIVE
MOTORS -- The evaporator-fan
motor
factory speed setting is shown on label diagram affixed to base
unit. If other than factory setting is desired, refer to label located on motor for motor reconnection. Insert wire into the speed
tap corresponding to desired speed.
ioi
MOTOR MOUNTING
NUTS AND BOLTS
iJ
Fig. 38 -- Belt-Drive Motor Mounting
BELT-DRIVE MOTORSFan motor pulleys are factory
set for speed shown in Tables IA and lB. See Fig. 38.
To change fan rpm:
1. Shut off unit power supply. Install lockout tag.
2. Loosen belt by loosening fan motor mounting nuts.
3. Loosen movable pulley fange setscrew (see Fig. 39).
4. Screw movable flange tow;ud fixed flange to inclease fan
rpm and away from fixed flange to decrease fan rpm. Increasing fan rpm increases load on motor. Do not exceed
maximum speed specified in Tables IA and lB.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Tables I A and IB for speed change
for each lidl turn of pulley flange.)
ISTRAIGHT
EDGE
BE PARALLEL
WITH
PULLEYS_
BELT
:3_ ARALLEL
[_
)_.,,i_)
SETSCREWS_F
FIXED
l
_
FLANGE
I
belt tension (1/2-in. deflection with 8 to 10 lb of force).
Tighten nuts.
Adjust bolt and tighten nut to secure motor in fixed position.
Re-inspect pulley alignment.
MOVABLE
FLANGE
MO!OR AND FAN
SHAFTS MUST BE
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angulgu" alignment by loosening motor from
mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for proper
3.
4.
5.
MUST
SINGLE-GROOVE
Fig. 39 -- Eva mrator-Fan
Pulley Adjustment
Table 7 -- Fan Rpm at Motor Pulley Settings*
UNIT
MOTOR PULLEY TURNS OPEN
0
1_
1
11&
2
50TM004t
1045
1009
973
937
901
21&
50TFF004t
1000
976
952
928
904
880
856
832
808
784
760
--
--
50TF_TM004**
1455
1423
1392
1360
1328
1297
1265
1233
1202
1170
1138
1107
1075
50TFF005t
1185
1150
1115
1080
1045
1010
975
940
905
810
835
--
--
50TM005t
1175
1135
1094
1054
1013
973
932
892
851
811
770
--
--
50TF_TM005**
1455
1423
1392
1360
1326
1297
1265
1233
1202
1170
1138
1107
1075
50TFF006t
1300
1267
1233
1200
1167
1133
1100
1067
1033
1000
967
933
900
50TM006t
1190
1164
1138
1112
1086
1060
1034
1008
982
956
930
904
878
50TF_TM006**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
--
--
50TF_TM007tt
1460
1421
1382
1343
1304
1265
1225
1187
1148
1109
1070
--
--
50TF_TM007**
1685
1647
1608
1570
1531
1493
1454
1416
1377
1339
1300
--
--
865
*Approximate fan rpm shown.
I-Indicates alternate motor and drive package.
3
31&
4
41_
5
51&
6
829
793
757
721
685
--
--
**Indicates high-static motor and drive package.
I-I-Indicates standard motor and drive package.
31
Table 8 -- Evaporator-Fan
UNIT
50TFF, TM
EVAPORATOR-FAN
MOTOR
UNIT
VOLTAGE
208/230
Standard
OO4
46O
575
MAXIMUM ACCEPTABLE
OPERATING WATTS
0.34
208/230
46O
575
Alternate
Motor Performance
MAXIMUM ACCEPTABLE
CONTINUOUS BHP*
MAXIMUM
AMP DRAW
2.8
44O
1.20
1000
2.40
2120
1.3
1.3
4.9
2.1
2.1
208/230
8.0
48O
575
High Static
208/230
48O
575
Standard
0.75
3.0
3.0
3.5
1.8
1.8
85O
208/230
005
Alternate
4.9
48O
575
208/230
1.20
1000
2.1
2.1
8.0
2.40
2120
3.0
3.0
1.20
1340
1.30/2.40t
2120
2.90
2562
48O
575
High Static
208/230
Standard
Alternate
006
5.9
48O
575
208/230
48O
575
208/230
48O
High Static
3.2
3.2
6.8/5.212.8
3.0
8.8
3.9
575
208/230
Standard
3.9
5.2
48O
575
OO7
208/230
48O
High Static
2.40
2120
2.90
2562
3.0
3.0
8.8
3.9
575
3.9
LEGEND
Bhp --
NOTES:
1. All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
2. High-static motor not available on single-phase units.
Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full
horsepower range of the motors can be utilized with confidence. Using the
fan motors up to the horsepower ratings shown in this table will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected.
tSingle phase/three-phase.
Table 9 -- Accessory Electric Heaters Static Pressure Drop (in. wg)
50HJ004-007
CFM
COMPONENT
1 Heater
Module
2 Heater
Modules
Table 10-
900
1200
1400
1600
1800
2000
2200
2400
2600
0.05
0.07
0.09
0.09
0.10
0.11
0.11
0.12
0.13
0.15
0.16
0.18
0.18
0.17
0.17
0.17
0.18
0.18
Accessory/FlOP
EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)
CFM
COMPONENT
Vertical EconoMi$er IV and EconoMi$er2
Horizontal EconoMi$er IV and EconoMiSer2
1250
1500
1750
0.045
0.065
0.08
0.1
LEGEND
FlOP
--
Factory-Installed
2000
0.12
0.125
2250
I
2500
2750
3000
0.145
0.15
I
0.175
0.18
0.22
0.225
0.255
0.275
*The static pressure must be added to external static pressure. The sum and
the evaporator entering-air cfm should be used in conjunction with the Fan
Per_rmance tables to determine indoor blower rpm and watts.
Option
Table 11 -- Evaporator-Fan
MOTOR 50TFF, TM
EFFICIENCY
75
74/84"
84
004,005
OO6
OO7
*Sin gle-phase/3-phase.
NOTE: Convert watts to bhp using the following formula:
bhp =
Motor Efficiency
watts input x motor efficiency
746
32
Table 12 -- Fan Performance 50TFF,TM004 -- Vertical Discharge Units; Standard
AIRFLOW
(Cfm)
900
1000
1100
1200
1300
1400
1500
LOW SPEED
208 v
HIGH SPEED
230, 460, 575 v
208 v
ESP
Bhp
Watts
ESP
Bhp
Watts
0.67
0.60
0.55
0.51
0.45
0.38
0.34
0.21
0.23
0.24
0.26
0.27
0.29
0.30
253
270
287
304
321
338
355
0.68
0.61
0.56
0.51
0.46
0.41
0.36
0.23
0.25
0.26
0.27
0.29
0.30
0.31
277
292
307
323
338
354
369
LEGEND
Bhp
ESP
Watts
Motor (Direct Drive)
ESP
0.69
0.61
0.57
0.52
0.48
0.43
0.38
Bhp
0.28
0.27
0.28
0.29
0.31
0.32
0.33
230, 460, 575 v
Watts
307
321
335
349
364
378
392
See general fan performance
ESP
0.69
0.63
0.58
0.53
0.47
---
Bhp
0.31
0.32
0.33
0.34
0.34
---
Watts
363
374
385
397
408
---
notes below.
-- Brake Horsepower Input to Fan
-- External Static Pressure (in. wg)
-- Input Watts to Motor
Table 13 -- Fan Performance 50TFF004 -- Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
0.2
Rpm
643
683
725
767
811
855
900
Watts
152
191
237
291
352
423
504
Rpm
768
804
842
880
920
980
1002
Bhp
0.22
0.27
0.32
0.38
0.45
0.53
0.62
Watts
222
268
321
382
451
529
617
1.2
Rpm
1110
1141
1173
1205
1239
1273
1309
Bhp
0.54
0.61
0.69
0.77
0.87
0.97
1.09
1.4
Watts
538
607
683
768
863
967
1082
Rpm
Bhp
Watts
1177
0.63
627
1207
0.70
700
1238
0.79
781
1270
0.88
872
1303
0.98
972
1337
1.09
1082
............
STATIC PRESSURE
0.6
Rpm
870
904
939
976
1013
1051
1090
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
Bhp
0.15
0.19
0.24
0.29
0.35
0.43
0.51
0.4
Watts
296
348
407
474
550
636
731
STATIC PRESSURE
1.6
Rpm
1239
1269
1300
1332
1364
.........
LEGEND
Bhp
Watts
Bhp
0.30
0.35
0.41
0.48
0.55
0.64
0.74
Bhp
0.72
0.80
0.89
0.98
1.09
Watts
718
796
883
979
1084
(in. wg)
0.8
Rpm
958
991
1025
1060
1095
1132
1169
Bhp
0.37
0.43
0.50
0.57
0.66
0.75
0.85
1.0
Watts
373
430
496
570
652
744
846
Rpm
1037
1069
1102
1136
1170
1205
1242
Bhp
0.46
0.52
0.59
0.67
0.76
0.86
0.97
Watts
813
895
987
1088
Rpm
1355
1384
1414
--
Bhp
0.92
1.00
1.10
--
(in. wg)
1.8
Rpm
1298
1328
1358
1389
......
Bhp
0.82
0.90
0.99
1.09
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See below for general fan performance notes.
-- Brake Horsepower Input to Fan
-- Input Watts to Motor
*Motor drive range: 760 to 1000 rpm. All other rpms require fieldsupplied drive.
GENERAL FAN PERFORMANCE
NOTES
1. Values include losses for filters, unit casing, and wet coils.
2. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using fan motors up to
the wattage ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. For additional information
on motor performance, refer to Table 8 on page 32.
3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative for details.
4. Interpolation is permissible. Do not extrapolate.
33
Watts
454
517
588
668
756
855
963
Watts
911
998
1094
--
Table 14 -- Fan Performance 50TM004 -- Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500
0.2
Rpm
643
683
725
767
811
855
900
Watts
152
191
237
291
352
423
504
Rpm
768
804
842
880
920
960
1002
Bhp
0.22
0.27
0.32
0.38
0.45
0.53
0.62
Watts
222
268
321
382
451
529
617
1.2
Rpm
1110
1141
1173
1205
1239
1273
1309
Bhp
0.54
0.61
0.69
0.77
0.87
0.97
1.09
1.4
Watts
538
607
683
768
863
967
1082
Rpm
1177
1207
1238
1270
1303
1337
............
Bhp
0.63
0.70
0.79
0.88
0.98
1.09
Watts
627
700
781
872
972
1082
STATIC PRESSURE(in.
0.6
Rpm
870
904
939
976
1013
1051
1090
EXTERNAL
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500
Bhp
0.15
0.19
0.24
0.29
0.35
0.43
0.51
0.4
---
Watts
296
348
407
474
550
636
731
0.8
Rpm
958
991
1025
1060
1095
1132
1169
STATIC PRESSURE (in. wg)
1.6
Rpm
1239
1269
1300
1332
1364
.........
LEGEND
Bhp
Watts
Bhp
0.30
0.35
0.41
0.48
0.55
0.64
0.74
wg)
Bhp
0.72
0.80
0.89
0.98
1.09
Watts
718
796
883
979
1084
Rpm
1298
1328
1358
1389
......
Bhp
0.37
0.43
0.50
0.57
0.66
0.75
0.85
1.0
Watts
373
430
496
570
652
744
846
Rpm
1037
1069
1102
1136
1170
1205
1242
1.8
Bhp
0.82
0.90
0.99
1.09
Bhp
0.46
0.52
0.59
0.67
0.76
0.86
0.97
Watts
454
517
588
668
756
855
963
2.0
Watts
813
895
987
1088
Rpm
1355
1384
1414
--
Bhp
0.92
1.00
1.10
--
Watts
911
998
1094
--
NOTES:
1. Boldface indicates field-supplied drive is required,
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 685 to 1045 rpm. All other rpms require fieldsupplied drive.
Table 15 -- Fan Performance 50TFF,TM004 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500
0.2
Rpm
643
683
725
767
811
855
900
Watts
152
191
237
291
352
423
504
Rpm
768
804
842
880
920
960
1002
Bhp
0.22
0.27
0.32
0.38
0.45
0.53
0.62
Watts
222
268
321
382
451
529
617
1.2
Rpm
1110
1141
1173
1205
1239
1273
1309
Bhp
0.54
0.61
0.69
0.77
0.87
0.97
1.09
1.4
Watts
538
607
683
768
863
967
1082
Rpm
1177
1207
1238
1270
1303
1337
1371
Bhp
0.63
0.70
0.79
0.88
0.98
1.09
1.21
Watts
627
700
781
872
972
1082
1204
STATIC PRESSURE (in. wg)
0.6
Rpm
870
904
939
976
1013
1051
1090
EXTERNAL
AIRFLOW
CFM
90O
1000
1100
1200
1300
1400
1500
Bhp
0.15
0.19
0.24
0.29
0.35
0.43
0.51
0.4
---
Watts
296
348
407
474
550
636
731
Rpm
958
991
1025
1060
1095
1132
1169
STATIC PRESSURE (in. wg)
1.6
Rpm
1239
1269
1300
1332
1364
1397
1430
LEGEND
Bhp
Watts
Bhp
0.30
0.35
0.41
0.48
0.55
0.64
0.74
Bhp
0.72
0.80
0.89
0.98
1.09
1.21
1.33
Watts
718
796
883
979
1084
1200
1327
Rpm
1298
1328
1358
1389
1421
1453
1486
0.8
Bhp
0.37
0.43
0.50
0.57
0.66
0.75
0.85
1.0
Watts
373
430
496
570
652
744
846
Rpm
1037
1069
1102
1136
1170
1205
1242
1.8
Bhp
0.82
0.90
0.99
1.09
1.21
1.33
1.46
*Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive.
34
Watts
454
517
588
668
756
855
963
2.0
Watts
813
895
987
1088
1199
1320
1453
Rpm
1355
1384
1414
1444
1475
1507
1540
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
Bhp
0.46
0.52
0.59
0.67
0.76
0.86
0.97
Bhp
0.92
1.00
1.10
1.21
1.32
1.45
1.59
Watts
911
998
1094
1200
1316
1443
1581
Table 16 -- Fan Performance 50TFF,TM005 -- Vertical Discharge Units; Standard Motor (Belt Drive)
LOW SPEED
AIRFLOW
(Cfm)
1200
1300
1400
1500
1600
1700
1800
1900
2000
208 v
ESP
0.93
0.86
0.78
0.70
0.61
0.51
0.40
0.29
0.25
Bhp
0.41
0.42
0.45
0.47
0.49
0.52
0.54
0.56
0.58
HIGH
230, 460, 575 v
Watts
458
471
503
536
557
584
610
629
651
ESP
0.94
0.87
0.79
0.73
0.64
0.54
0.44
0.37
0.30
Bhp
0.45
0.46
0.49
0.52
0.54
0.57
0.60
0.62
0.64
SPEED
208 v
Watts
506
521
556
593
616
646
674
696
720
ESP
Bhp
0.94
0.87
0.79
0.73
0.66
0.58
0.51
0.46
0.39
0.51
0.52
0.54
0.56
0.58
0.60
0.62
0.64
0.66
230, 460,
575 v
Watts
ESP
Bhp
Watts
572
589
616
631
654
678
698
720
744
0.99
0.92
0.87
0.80
0.76
0.68
0.63
0.56
0.50
0.56
0.58
0.60
0.62
0.64
0.66
0.68
0.70
0.73
632
651
681
698
723
750
772
796
823
See general fan performance
notes on page 33.
LEGEND
Bhp
ESP
Watts
----
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Input Watts to Motor
Table 17 -- Fan Performance 50TFF005 -- Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
666
701
737
774
811
849
887
926
965
Watts
252
300
355
417
487
565
651
746
852
Rpm
778
809
842
875
909
943
978
1014
1050
Bhp
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03
Watts
361
418
481
551
629
715
810
914
1028
1.2
Rpm
1100
1126
1152
1179
Bhp
0.85
0.94
1.03
1.13
1.4
Watts
845
930
1023
1123
Rpm
1165
1189
1215
............
Bhp
0.98
1.07
1.17
Watts
977
1069
1168
STATIC PRESSURE
0.6
Rpm
873
902
932
962
994
1026
1059
1092
.........
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86
0.4
---
Watts
476
540
610
689
774
869
972
1084
STATIC PRESSURE
1.6
Rpm
1225
.........
.........
LEGEND
Bhp
Watts
Bhp
0.48
0.54
0.61
0.69
0.78
0.87
0.98
1.09
Bhp
1.12
Watts
1112
(in. wg)
0.8
Rpm
956
983
1012
1041
1071
1101
1133
......
Bhp
0.60
0.67
0.75
0.83
0.93
1.03
1.14
1.0
Watts
594
665
744
830
923
1025
1136
Rpm
1031
1057
1085
1112
1141
1170
--
Bhp
0.72
0.80
0.89
0.98
1.08
1.19
--
Watts
Rpm
Bhp
(in. wg)
1.8
Rpm
......
Bhp
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 835 to 1185 rpm. All other rpms require fieldsupplied drive.
.3.5
Watts
718
796
881
974
1076
1185
--
Watts
Table 18 -- Fan Performance 50TM005 -- Vertical Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
666
701
737
774
811
849
887
926
965
Watts
252
300
355
417
487
565
651
746
852
Rpm
778
809
842
875
909
943
978
1014
1050
Bhp
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03
Watts
361
418
481
551
629
715
810
914
1028
1.2
Rpm
1100
1126
1152
1179
Bhp
0.85
0.94
1.03
1.13
1.4
Watts
845
930
1023
1123
Rpm
1165
1189
1215
............
Bhp
0.98
1.07
1.17
Watts
977
1069
1168
STATIC PRESSURE (in. wg)
0.6
Rpm
873
902
932
962
994
1026
1059
1092
.........
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86
0.4
---
Watts
476
540
610
689
774
869
972
1084
STATIC PRESSURE(in.
1.6
Rpm
1225
.........
.........
LEGEND
Bhp
Watts
Bhp
0.48
0.54
0.61
0.69
0.78
0.87
0.98
1.09
Bhp
1.12
Watts
1112
Rpm
956
983
1012
1041
1071
1101
1133
......
0.8
Bhp
0.60
0.67
0.75
0.83
0.93
1.03
1.14
1.0
Watts
594
665
744
830
923
1025
1136
Rpm
1031
1057
1085
1112
1141
1170
--
Bhp
0.72
0.80
0.89
0.98
1.08
1.19
--
Watts
718
796
881
974
1076
1185
--
wg)
1.8
Rpm
......
Bhp
2.0
Watts
Rpm
Bhp
Watts
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 770 to 1175 rpm. All other rpms require fieldsupplied drive.
Table 19 -- Fan Performance 50TFF,TM005 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
666
701
737
774
811
849
887
926
965
Watts
252
300
355
417
487
565
651
746
852
Rpm
778
809
842
875
909
943
978
1014
1050
Bhp
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03
Watts
361
418
481
551
629
715
810
914
1028
1.2
Rpm
1100
1126
1152
1179
1206
1235
1264
1293
1324
Bhp
0.85
0.94
1.03
1.13
1.24
1.36
1.48
1.62
1.77
1.4
Watts
845
930
1023
1123
1231
1349
1475
1611
1756
Rpm
1165
1189
1215
1241
1268
1295
1323
1352
1381
Bhp
0.98
1.07
1.17
1.28
1.40
1.52
1.66
1.80
1.96
Watts
977
1069
1168
1275
1391
1515
1649
1792
1945
STATIC PRESSURE(in.
0.6
Rpm
873
902
932
962
994
1026
1059
1092
1127
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86
0.4
---
Wa_s
476
540
610
689
774
869
972
1084
1206
0.8
Rpm
956
983
1012
1041
1071
1101
1133
1164
1197
STATIC PRESSURE (in. wg)
1.6
Rpm
1225
1249
1274
1300
1326
1352
1380
1408
1436
LEGEND
Bhp
Watts
Bhp
0.48
0.54
0.61
0.69
0.78
0.87
0.98
1.09
1.21
wg)
Bhp
1.12
1.22
1.32
1.44
1.56
1.69
1.84
1.99
2.15
Watts
1112
1211
1317
1431
1553
1685
1826
1976
2137
Rpm
1282
1306
1330
1355
1381
1407
1434
1461
1489
Bhp
0.60
0.67
0.75
0.83
0.93
1.03
1.14
1.26
1.39
1.0
Watts
594
665
744
830
923
1025
1136
1257
1387
Rpm
1031
1057
1085
1112
1141
1170
1200
1231
1262
1.8
Bhp
1.26
1.36
1.48
1.60
1.73
1.87
2.02
2.17
2.34
*Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive.
36
Watts
718
796
881
974
1076
1185
1304
1432
1570
2.0
Watts
1252
1356
1469
1590
1719
1858
2006
2163
2332
Rpm
1337
1360
1384
1408
1433
1459
1485
1512
--
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
Bhp
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58
Bhp
1.40
1.51
1.63
1.76
1.90
2.04
2.20
2.37
--
Watts
1395
1506
1625
1752
1888
2034
2189
2353
--
Table 20 -- Fan Performance 50TFF,TM006 -- Vertical Discharge Units; Standard Motor (Belt Drive)
LOW SPEED
AIRFLOW
(Cfm)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
208 v
ESP
0.88
0.68
0.51
0.35
0.26
0.18
0.08
Bhp
0.67
0.70
0.73
0.75
0.78
0.81
0.84
MEDIUM SPEED
230, 460, 575 v
Watts
750
780
810
839
873
905
940
ESP
1.20
1.04
0.89
0.73
0.58
0.42
0.27
0.19
0.11
0.03
Bhp
0.71
0.74
0.77
0.80
0.83
0.88
0.89
0.92
0.95
0.98
Watts
791
824
857
891
924
957
990
1023
1056
1096
208 v
ESP
1.19
1.04
0.89
0.74
0.59
0.44
0.29
0.19
0.11
0.04
--
Bhp
0.70
0.74
0.77
0.81
0.84
0.88
0.91
0.93
0.97
1.00
--
Watts
782
821
881
900
940
979
1018
1035
1076
1113
--
LEGEND
Bhp
ESP
Watts
----
HIGH SPEED
230, 460, 575 v
ESP
1.36
1.22
1.09
0.98
0.86
0.73
0.59
0.48
0.34
0.19
0.09
Bhp
0.76
0.79
0.83
0.86
0.90
0.93
0.96
1.00
1.03
1.07
1.10
Watts
845
883
921
959
997
1035
1073
1111
1149
1187
1225
208 v
ESP
1.38
1.25
1.13
1.00
0.88
0.78
0.63
0.49
0.41
0.22
0.12
See general fan performance
Bhp
0.79
0.82
0.85
0.89
0.92
0.95
0.99
1.02
1.06
1.09
1.12
230, 460, 575 v
Watts
875
913
950
988
1025
1063
1101
1138
1178
1213
1251
ESP
1.44
1.33
1.22
1.11
1.00
0.92
0.81
0.69
0.59
0.43
0.34
Bhp
0.85
0.89
0.92
0.98
0.99
1.03
1.08
1.10
1.13
1.17
1.20
Watts
949
988
1027
1068
1105
1144
1183
1222
1261
1300
1340
notes on page 33.
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Input Watts to Motor
Table 21 -- Fan Performance 50TFF006 -- Vertical Discharge Units; Alternate (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
807
847
887
928
989
1010
1052
1095
1137
1180
1223
Watts
369
432
501
579
688
761
888
981
1105
1241
1388
Rpm
913
948
983
1020
1057
1095
1133
1173
1212
1252
1293
Bhp
0.56
0.63
0.72
0.82
0.92
1.04
1.16
1.30
1.45
1.61
1.78
Watts
489
557
632
715
808
909
1019
1140
1271
1412
1565
1.2
Rpm
1270
1292
1315
1341
1367
1395
1424
1454
1485
Bhp
1.24
1.34
1.44
1.56
1.68
1.82
1.97
2.13
2.30
1.4
Watts
1091
1174
1267
1368
1478
1598
1728
1869
2020
Rpm
1347
1367
1389
1412
1437
1463
1490
1518
............
Bhp
1.45
1.54
1.65
1.77
1.90
2.04
2.20
2.36
Watts
1269
1356
1451
1556
1670
1794
1928
2073
STATIC PRESSURE (in. wg)
0.6
Rpm
1011
1042
1073
1106
1140
1175
1211
1247
1284
1322
1360
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.42
0.49
0.57
0.68
0.78
0.87
0.99
1.12
1.28
1.41
1.58
0.4
---
Watts
621
694
774
883
980
1088
1182
1308
1445
1592
1751
Rpm
1103
1130
1158
1188
1219
1251
1285
1319
1353
1389
1425
STATIC PRESSURE (in. wg)
1.6
Rpm
1421
1440
1459
1481
1504
1528
.........
.........
LEGEND
Bhp
Watts
Bhp
0.71
0.79
0.88
0.98
1.09
1.21
1.35
1.49
1.65
1.81
1.99
Bhp
1.66
1.76
1.88
2.00
2.13
2.28
Watts
1458
1547
1646
1753
1871
1998
Rpm
1492
1509
1527
1547
1569
......
0.8
Bhp
0.87
0.96
1.08
1.18
1.28
1.41
1.54
1.69
1.85
2.03
2.22
1.0
Watts
766
843
928
1021
1123
1234
1355
1486
1628
1781
1945
Rpm
1188
1213
1239
1288
1295
1325
1355
1387
1420
1454
--
Bhp
1.05
1.14
1.24
1.35
1.48
1.61
1.75
1.91
2.07
2.25
--
Watts
1657
1748
1849
1960
2080
Rpm
1561
1576
1593
---
Bhp
2.13
2.23
2.35
---
1.8
Bhp
1.89
1.99
2.11
2.23
2.37
Watts
923
1003
1092
1189
1296
1411
1537
1673
1820
1977
--
2.0
Watts
1865
1959
2062
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for three-phase units.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
37
Table 22 -- Fan Performance 50TM006 -- Vertical Discharge; Alternate Motor (Belt Drive)* -Single-Phase Units
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
807
847
887
928
969
1010
1052
1098
1137
Watts
369
432
501
579
666
761
866
981
1105
Rpm
913
948
983
1020
1057
1095
1133
1173
............
Bhp
0.56
0.63
0.72
0.82
0.92
1.04
1.16
1.30
Watts
489
557
632
715
808
909
1019
1140
1.2
Rpm
1270
Bhp
1.24
1.4
Watts
1091
Rpm
....
Bhp
Watts
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
STATIC PRESSURE
0.6
Rpm
1011
1042
1073
1106
1140
1175
.........
.........
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.42
0.49
0.57
0.66
0.76
0.87
0.99
1.12
1.26
0.4
---
Watts
621
694
774
863
960
1066
STATIC PRESSURE
1.6
Rpm
LEGEND
Bhp
Watts
Bhp
0.71
0.79
0.88
0.98
1.09
1.21
Bhp
Watts
(in. wg)
0.8
Rpm
1103
1130
1158
1188
1219
1251
Bhp
0.87
0.96
1.06
1.16
1.28
1.41
1.0
Watts
766
843
928
1021
1123
1234
Rpm
1188
1213
1239
----
Bhp
1.05
1.14
1.24
----
Watts
Rpm
Bhp
Watts
923
1003
1092
----
(in. wg)
1.8
Rpm
Bhp
2.0
Watts
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
Table 23 -- Fan Performance 50TM006 -- Vertical Discharge; Alternate Motor (Belt Drive)* -Three-Phase Units
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
807
847
887
928
969
1010
1052
1095
1137
1180
1223
Watts
369
432
501
579
666
761
866
981
1105
1241
1388
Rpm
913
948
983
1020
1057
1095
1133
1173
1212
1252
1293
Bhp
0.56
0.63
0.72
0.82
0.92
1.04
1.16
1.30
1.45
1.61
1.78
Watts
489
557
632
715
808
909
1019
1140
1271
1412
1565
1.2
Rpm
1270
1292
1315
1341
1367
1395
1424
1454
1485
Bhp
1.24
1.34
1.44
1.56
1.68
1.82
1.97
2.13
2.30
1.4
Watts
1091
1174
1267
1368
1478
1598
1728
1869
2020
Rpm
1347
1367
1389
1412
1437
1463
1490
1518
............
Bhp
1.45
1.54
1.65
1.77
1.90
2.04
2.20
2.36
Watts
1269
1356
1451
1556
1670
1794
1928
2073
STATIC PRESSURE
0.6
Rpm
1011
1042
1073
1106
1140
1175
1211
1247
1284
1322
1360
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.42
0.49
0.57
0.66
0.76
0.87
0.99
1.12
1.26
1.41
1.58
0.4
---
Watts
621
694
774
863
960
1066
1182
1308
1445
1592
1751
0.8
Rpm
1103
1130
1158
1188
1219
1251
1285
1319
1353
1389
1425
STATIC PRESSURE (in. wg)
1.6
Rpm
1421
1440
1459
1481
1504
1528
.........
.........
LEGEND
Bhp
Watts
Bhp
0.71
0.79
0.88
0.98
1.09
1.21
1.35
1.49
1.65
1.81
1.99
(in. wg)
Bhp
1.66
1.76
1.88
2.00
2.13
2.28
Watts
1458
1547
1646
1753
1871
1998
Rpm
1492
1509
1527
1547
1569
......
Bhp
0.87
0.96
1.06
1.16
1.28
1.41
1.54
1.69
1.85
2.03
2.22
1.0
Watts
766
843
928
1021
1123
1234
1355
1486
1628
1781
1945
Rpm
1188
1213
1239
1266
1295
1325
1355
1387
1420
1454
--
Bhp
1.05
1.14
1.24
1.35
1.48
1.61
1.75
1.91
2.07
2.25
--
Watts
1657
1748
1849
1960
2080
Rpm
1561
1576
1593
---
Bhp
2.13
2.23
2.35
---
1.8
Bhp
1.89
1.99
2.11
2.23
2.37
2.0
NOTES:
1. Boldface indicates field-supplied drive is required,
2. Maximum continuous bhp is 2,40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
38
Watts
923
1003
1092
1189
1296
1411
1537
1673
1820
1977
--
Watts
1865
1959
2062
---
Table 24 -- Fan Performance 50TFF,TM006 -- Vertical Discharge; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
807
847
887
928
969
1010
1052
1095
1137
1180
1223
Watts
369
432
501
579
666
761
866
981
1105
1241
1388
Rpm
913
948
983
1020
1057
1095
1133
1173
1212
1252
1293
Bhp
0.56
0.63
0.72
0.82
0.92
1.04
1.16
1.30
1.45
1.61
1.78
Watts
489
557
632
715
808
909
1019
1140
1271
1412
1565
1.2
Rpm
1270
1292
1315
1341
1367
1395
1424
1454
1485
1516
1549
Bhp
1.24
1.34
1.44
1.58
1.68
1.82
1.97
2.13
2.30
2.49
2.69
1.4
Watts
1091
1174
1267
1368
1478
1598
1728
1869
2020
2182
2357
Rpm
1347
1367
1389
1412
1437
1463
1490
1518
1547
1577
............
Bhp
1.45
1.54
1.85
1.77
1.90
2.04
2.20
2.36
2.54
2.73
Watts
1269
1356
1451
1558
1670
1794
1928
2073
2228
2395
STATIC PRESSURE (in. wg)
0.6
Rpm
1011
1042
1073
1106
1140
1175
1211
1247
1284
1322
1360
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.42
0.49
0.57
0.66
0.76
0.87
0.99
1.12
1.26
1.41
1.58
0.4
---
Watts
621
694
774
863
960
1066
1182
1308
1445
1592
1751
Rpm
1103
1130
1158
1188
1219
1251
1285
1319
1353
1389
1425
STATIC PRESSURE (in. wg)
1.6
Rpm
1421
1440
1459
1481
1504
1528
1554
1580
1608
.........
LEGEND
Bhp
Watts
Bhp
0.71
0.79
0.88
0.98
1.09
1.21
1.35
1.49
1.65
1.81
1.99
Bhp
1.68
1.78
1.88
2.00
2.13
2.28
2.43
2.60
2.79
Watts
1458
1547
1648
1753
1871
1998
2136
2285
2445
Rpm
1492
1509
1527
1547
1569
1591
1615
1641
......
0.8
Bhp
0.87
0.96
1.06
1.16
1.28
1.41
1.54
1.69
1.85
2.03
2.22
1.0
Watts
766
843
928
1021
1123
1234
1355
1486
1628
1781
1945
Rpm
1188
1213
1239
1266
1295
1325
1355
1387
1420
1454
1488
Bhp
1.05
1.14
1.24
1.35
1.48
1.81
1.75
1.91
2.07
2.25
2.45
Watts
1657
1748
1849
1960
2080
2212
2353
2505
Rpm
1561
1576
1593
1612
1632
1653
---
Bhp
2.13
2.23
2.35
2.48
2.62
2.77
---
1.8
Bhp
1.89
1.99
2.11
2.23
2.37
2.52
2.68
2.85
Watts
923
1003
1092
1189
1296
1411
1537
1673
1820
1977
2147
2.0
Watts
1865
1959
2062
2175
2299
2433
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive.
Table 25 -- Fan Performance 50TFF,TM007 -- Vertical Discharge Units; Standard
EXTERNAL
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
0.2
Rpm
905
944
983
1023
1063
1104
1145
1185
1227
1268
1309
1351
Watts
551
633
723
821
929
1048
1174
1311
1460
1621
1793
1977
Rpm
1001
1037
1073
1110
1147
1185
1223
1262
1301
1340
1379
............
Bhp
0.77
0.87
0.98
1.10
1.23
1.37
1.52
1.68
1.85
2.04
2.24
Watts
687
774
870
975
1089
1212
1348
1490
1646
1812
1991
1.2
Rpm
1306
1335
1364
1395
1426
1457
1489
Bhp
1.48
1.61
1.74
1.88
2.03
2.19
2.37
1.4
Watts
1318
1426
1542
1668
1804
1949
2106
Rpm
1370
1398
1427
1456
1486
............
............
Bhp
1.69
1.81
1.95
2.09
2.25
Watts
1497
1609
1730
1860
2001
STATIC PRESSURE
0.6
Rpm
1087
1120
1154
1189
1224
1260
1296
1333
1370
1407
.........
EXTERNAL
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
0.62
0.71
0.81
0.92
1.05
1.18
1.32
1.48
1.64
1.82
2.02
2.23
0.4
---
Watts
832
925
1028
1137
1258
1388
1528
1678
1837
2010
STATIC PRESSURE
1.6
Rpm
1431
1458
1486
1514
.........
LEGEND
Bhp
Watts
Bhp
0.94
1.04
1.18
1.28
1.41
1.58
1.72
1.89
2.07
2.26
Bhp
1.90
2.03
2.17
2.32
Watts
1683
1799
1925
2060
Motor (Belt Drive)*
(in. wg)
0.8
Rpm
1165
1197
1229
1262
1295
1329
1364
1399
1435
......
Bhp
1.11
1.22
1.34
1.47
1.61
1.76
1.93
2.10
2.29
1.0
Watts
985
1084
1190
1308
1431
1567
1712
1888
2035
Rpm
1238
1268
1299
1330
1362
1395
1428
1462
--
Bhp
1.29
1.41
1.53
1.67
1.82
1.98
2.15
2.33
--
Watts
1877
1997
2126
Rpm
1545
---
Bhp
2.34
(in. wg)
1.8
Rpm
1489
1515
1542
--
Bhp
2.11
2.25
2.39
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require fieldsupplied drive.
39
Watts
1148
1251
1362
1483
1614
1754
1905
2067
--
Watts
2078
m
m
m
m
Table 26 -- Fan Performance 50TFF,TM007 -- Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
0.2
Rpm
905
944
983
1023
1063
1104
1145
1185
1227
1268
1309
1351
1393
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
0.62
0.71
0.81
0.92
1.05
1.18
1.32
1.48
1.64
1.82
2.02
2.23
2.45
0.4
Watts
551
633
723
821
929
1046
1174
1311
1460
1621
1793
1977
2174
Rpm
1001
1037
1073
1110
1147
1185
1223
1262
1301
1340
1379
1419
1459
Bhp
0.77
0.87
0.98
1.10
1.23
1.37
1.52
1.68
1.85
2.04
2.24
2.46
2.69
Watts
687
774
870
975
1089
1212
1346
1490
1646
1812
1991
2181
2385
Rpm
1087
1120
1154
1189
1224
1260
1296
1333
1370
1407
1445
1483
.........
EXTERNAL
AIRFLOW
CFM
1.2
Rpm
1306
1336
1364
1395
1426
1457
1489
1522
1555
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
1.48
1.61
1.74
1.88
2.03
2.19
2.37
2.56
2.76
1.4
Watts
1318
1426
1542
1668
1804
1949
2106
2272
2451
Rpm
1370
1398
1427
1456
1486
1516
1547
1579
............
Bhp
1.69
1.81
1.95
2.09
2.25
2.42
2.60
2.80
Watts
1497
1609
1730
1860
2001
2151
2312
2484
STATIC PRESSURE (in. wg)
0.6
---
Watts
832
925
1026
1137
1256
1386
1526
1676
1837
2010
2195
2392
Rpm
1165
1197
1229
1262
1295
1329
1364
1399
1435
1470
1507
......
STATIC PRESSURE (in. wg)
1.6
Rpm
1431
1458
1486
1514
1543
1573
1603
.........
LEGEND
Bhp
Watts
Bhp
0.94
1.04
1.16
1.28
1.41
1.56
1.72
1.89
2.07
2.26
2.47
2.69
Bhp
1.90
2.03
2.17
2.32
2.48
2.66
2.84
Watts
1683
1799
1925
2060
2204
2360
2526
Rpm
1489
1515
1542
1570
1598
1627
......
0.8
1.0
Bhp
1.11
1.22
1.34
1.47
1.61
1.76
1.93
2.10
2.29
2.49
2.71
Watts
985
1084
1190
1306
1431
1567
1712
1868
2035
2214
2405
Rpm
1238
1268
1299
1330
1362
1395
1428
1462
1496
1531
--
Bhp
1.29
1.41
1.53
1.67
1.82
1.98
2.15
2.33
2.52
2.73
--
1.8
Watts
1148
1251
1362
1483
1614
1754
1905
2067
2240
2424
--
2.0
Bhp
2.11
2.25
2.39
2.55
2.72
2.90
Watts
1877
1997
2126
2265
2415
2574
Rpm
1545
1570
1596
1623
---
Bhp
2.34
2.48
2.63
2.79
---
Watts
2078
2202
2335
2478
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive.
Table 27 -- Fan Performance 50TFF,TM004 -- Horizontal Discharge Units; Standard Motor (Direct Drive)
LOW SPEED
AIRFLOW
(Cfm)
900
1000
1100
1200
1300
1400
1500
208 v
ESP
0.72
0.67
0.61
0.57
0.51
0.44
0.39
Bhp
0.21
0.23
0.24
0.26
0.27
0.29
0.30
HIGH SPEED
208 v
230, 460, 575 v
Watts
ESP
Bhp
Watts
253
270
287
304
321
338
355
0.75
0.69
0.63
0.58
0.53
0.46
0.41
0.23
0.25
0.26
0.27
0.29
0.30
0.31
277
292
307
323
338
354
369
LEGEND
Bhp
ESP
Watts
----
ESP
0.73
0.70
0.64
0.56
0.53
0.47
0.43
Bhp
0.26
0.27
0.28
0.29
0.31
0.32
0.33
230, 460, 575 v
Watts
307
321
335
349
364
378
392
See general _n performance
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Input Watts to Motor
4O
ESP
0.76
0.71
0.65
0.59
0.54
---
notes on page 33.
Bhp
0.31
0.32
0.33
0.34
0.34
---
Watts
363
374
385
397
408
Table 28 -- Fan Performance 50TFF004 -- Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
0.2
Rpm
607
640
674
708
743
780
816
Watts
142
174
212
256
307
364
428
Rpm
745
775
805
836
868
900
934
Bhp
0.22
0.26
0.31
0.36
0.42
0.49
0.56
Watts
221
261
307
359
417
483
556
1.2
Rpm
1114
1139
1165
1191
1218
1246
1274
Bhp
0.59
0.65
0.72
0.80
0.89
0.99
1.09
1.4
Watts
582
648
720
799
885
980
1083
Rpm
1186
1210
1236
1261
1288
1315
............
Bhp
0.69
0.76
0.84
0.92
1.02
1.12
Watts
684
754
832
917
1010
1111
STATIC PRESSURE
0.6
Rpm
856
884
912
941
971
1002
1033
EXTERNAL
AIRFLOW
CFM
9OO
1000
1100
1200
1300
1400
1500
Bhp
0.14
0.18
0.21
0.26
0.31
0.37
0.43
0.4
---
Watts
304
351
404
464
530
603
685
STATIC PRESSURE
1.6
Rpm
1253
1277
1302
1327
1353
.........
LEGEND
Bhp
Watts
Bhp
0.31
0.35
0.41
0.47
0.53
0.61
0.69
Bhp
0.79
0.87
0.95
1.04
1.14
Watts
789
865
948
1039
1138
(in. wg)
0.8
Rpm
952
978
1005
1033
1062
1091
1121
Bhp
0.39
0.45
0.51
0.57
0.65
0.73
0.82
1.0
Watts
393
446
506
572
645
726
815
Rpm
1037
1062
1089
1116
1143
1172
1201
Bhp
0.49
0.55
0.61
0.69
0.77
0.86
0.95
Watts
485
545
611
683
764
851
947
(in. wg)
1.8
Rpm
1316
1340
1364
1389
......
Bhp
0.90
0.98
1.07
1.17
2.0
Watts
898
979
1068
1165
Rpm
1375
1399
1423
--
Bhp
1.02
1.10
1.20
--
Watts
1010
1097
1191
--
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 760 to 1000 rpm. All other rpms require fieldsupplied drive.
Table 29 -- Fan Performance 50TM004 -- Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
0.2
Rpm
607
640
674
708
743
780
816
Watts
142
174
212
256
307
364
428
Rpm
745
775
805
836
868
900
934
Bhp
0.22
0.26
0.31
0.36
0.42
0.49
0.56
Watts
221
261
307
359
417
483
556
1.2
Rpm
1114
1139
1165
1191
1218
1246
1274
Bhp
0.59
0.65
0.72
0.80
0.89
0.99
1.09
1.4
Watts
582
648
720
799
885
980
1083
Rpm
1186
1210
1236
1261
1288
1315
............
Bhp
0.69
0.76
0.84
0.92
1.02
1.12
Watts
684
754
832
917
1010
1111
STATIC PRESSURE
0.6
Rpm
856
884
912
941
971
1002
1033
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
Bhp
0.14
0.18
0.21
0.26
0.31
0.37
0.43
0.4
---
Watts
304
351
404
464
530
603
685
STATIC PRESSURE
1.6
Rpm
1253
1277
1302
1327
1353
.........
LEGEND
Bhp
Watts
Bhp
0.31
0.35
0.41
0.47
0.53
0.61
0.69
Bhp
0.79
0.87
0.95
1.04
1.14
Watts
789
865
948
1039
1138
(in. wg)
0.8
Rpm
952
978
1005
1033
1062
1091
1121
Bhp
0.39
0.45
0.51
0.57
0.65
0.73
0.82
1.0
Watts
393
446
506
572
645
726
815
Rpm
1037
1062
1089
1116
1143
1172
1201
*Motor drive range: 685 to 1045 rpm. All other rpms require fieldsupplied drive.
4!
Watts
485
545
611
683
764
851
947
(in. wg)
1.8
Rpm
1316
1340
1364
1389
......
Bhp
0.90
0.98
1.07
1.17
2.0
Watts
898
979
1068
1165
Rpm
1375
1399
1423
--
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
Bhp
0.49
0.55
0.61
0.69
0.77
0.86
0.95
Bhp
1.02
1.10
1.20
--
Watts
1010
1097
1191
--
Table 30 -- Fan Performance 50TFF,TM004 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
0.2
Rpm
607
640
674
708
743
780
816
900
1000
1100
1200
1300
1400
1500
Bhp
0.14
0.18
0.21
0.26
0.31
0.37
0.43
0.4
Watts
142
174
212
256
307
364
428
Rpm
745
775
805
836
868
900
934
Bhp
0.22
0.26
0.31
0.36
0.42
0.49
0.56
Watts
221
261
307
359
417
483
556
Rpm
856
884
912
941
971
1002
1033
EXTERNAL
AIRFLOW
CFM
1.2
Rpm
1114
1139
1165
1191
1218
1246
1274
900
1000
1100
1200
1300
1400
1500
Bhp
0.59
0.65
0.72
0.80
0.89
0.99
1.09
1.4
Watts
582
648
720
799
885
980
1083
Rpm
1186
1210
1236
1261
1288
1315
1342
Bhp
0.69
0.76
0.84
0.92
1.02
1.12
1.23
Watts
684
754
832
917
1010
1111
1221
STATIC PRESSURE (in. wg)
0.6
Bhp
0.31
0.35
0.41
0.47
0.53
0.61
0.69
---
Rpm
952
978
1005
1033
1062
1091
1121
STATIC PRESSURE (in. wg)
1.6
Rpm
1253
1277
1302
1327
1353
1379
1406
Bhp
0.79
0.87
0.95
1.04
1.14
1.25
1.37
LEGEND
Bhp
Watts
Watts
304
351
404
464
530
603
685
Watts
789
865
948
1039
1138
1246
1362
Rpm
1316
1340
1364
1389
1414
1440
1467
0.8
1.0
Bhp
0.39
0.45
0.51
0.57
0.65
0.73
0.82
Watts
393
446
506
572
645
726
815
*Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive.
1.8
Bhp
0.90
0.98
1.07
1.17
1.28
1.39
1.51
LOW SPEED
1200
1300
1400
1500
1600
1700
1800
1900
2000
ESP
Bhp
0.93
0.86
0.78
0.73
0.67
0.60
0.51
0.40
0.32
0.41
0.42
0.45
0.47
0.49
0.52
0.54
0.56
0.58
HIGH
230, 460, 575 v
Watts
898
979
1068
1165
1270
1383
1505
----
Rpm
1375
1399
1423
1448
1473
1499
1525
Bhp
1.02
1.10
1.20
1.30
1.41
1.53
1.66
Watts
1010
1097
1191
1293
1404
1523
1652
Motor (Direct Drive)
SPEED
208 v
230,
460, 575 v
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
458
471
503
536
557
584
610
629
661
0.97
0.90
0.84
0.76
0.70
0.63
0.54
0.45
0.33
0.45
0.46
0.49
0.52
0.54
0.57
0.60
0.62
0.65
506
521
556
593
616
646
674
696
731
1.04
0.96
0.90
0.83
0,75
0.67
0.62
0.54
0.47
0.51
0.52
0.54
0.56
0.58
0.60
0.62
0.64
0.66
572
589
616
631
654
678
698
720
744
1.09
1.02
0.96
0.89
0.82
0,74
0.69
0.62
0.54
0.56
0.58
0.60
0.62
0.64
0.66
0.68
0.70
0.73
632
651
681
698
723
750
772
796
823
LEGEND
Bhp
ESP
Watts
Watts
485
545
611
683
764
851
947
2.0
Table 31 -- Fan Performance 50TFF,TM005 -- Horizontal Discharge Units; Standard
208 v
Bhp
0.49
0.55
0.61
0.69
0.77
0.88
0.95
NOTES:
1. Boldface indicates field-supplied drive is required,
2. Maximum continuous bhp is 2,40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
AIRFLOW
(Cfm)
Rpm
1037
1062
1089
1116
1143
1172
1201
See general fan performance
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Input Watts to Motor
42
notes on page 33.
Table 32 -- Fan Performance 50TFF005 -- Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
643
674
706
738
771
804
837
871
906
Watts
233
276
324
379
440
507
582
665
756
Rpm
762
791
820
849
879
910
941
972
1004
Bhp
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94
Watts
344
395
451
515
584
661
745
837
938
1.2
Rpm
1089
1114
1139
1164
1190
Bhp
0.84
0.92
1.01
1.10
1.20
1.4
Watts
835
915
1000
1093
1193
Rpm
1153
1177
1202
...........
...........
Bhp
0.98
1.06
1.15
Watts
971
1056
1149
STATIC PRESSURE
0.6
Rpm
860
887
914
942
971
1000
1029
1059
1089
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76
0.4
---
Watts
459
517
582
653
731
816
909
1010
1119
STATIC PRESSURE
1.6
Rpm
1212
........
........
LEGEND
Bhp
Watts
Bhp
0.46
0.52
0.59
0.66
0.74
0.82
0.91
1.02
1.12
Bhp
1.12
Watts
1111
(in. wg)
0.8
Rpm
944
970
997
1024
1051
1079
1107
1136
......
Bhp
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
1.0
Watts
579
645
717
796
881
974
1075
1184
Rpm
1020
1045
1071
1097
1124
1151
---
Bhp
0.71
0.78
0.86
0.95
1.04
1.14
---
Watts
705
777
857
942
1035
1136
---
(in. wg)
1.8
Rpm
.....
Bhp
2.0
Watts
Rpm
Bhp
Watts
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 835 to 1185 rpm. All other rpms require fieldsupplied drive.
Table 33 -- Fan Performance 50TM005 -- Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
9O0
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
554
583
612
643
674
706
738
771
804
837
871
906
Watts
134
163
195
233
276
324
379
440
507
582
665
756
Rpm
681
707
735
762
791
820
849
879
910
941
972
1004
Bhp
0.22
0.26
0.30
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94
Watts
222
257
298
344
395
451
515
584
661
745
837
938
1.2
Rpm
1017
1041
1065
1089
1114
1139
1164
1190
Bhp
0.64
0.70
0.77
0.84
0.92
1.01
1.10
1.20
1.4
Watts
635
696
763
835
915
1000
1093
1193
Rpm
1082
1105
1129
1153
1177
1202
............
............
Bhp
0.76
0.82
0.90
0.98
1.06
1.15
Watts
753
820
892
971
1056
1149
STATIC PRESSURE
0.6
Rpm
783
808
834
860
887
914
942
971
1000
1029
1059
1089
EXTERNAL
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.14
0.16
0.20
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76
0.4
---
Watts
316
358
406
459
517
582
653
731
816
909
1010
1119
STATIC PRESSURE
1.6
Rpm
1143
1166
1189
1212
.........
.........
LEGEND
Bhp
Watts
Bhp
0.32
0.36
0.41
0.46
0.52
0.59
0.66
0.74
0.82
0.91
1.02
1.12
Bhp
0.88
0.95
1.03
1.12
Watts
876
948
1026
1111
(in. wg)
0.8
Rpm
870
894
919
944
970
997
1024
1051
1079
1107
1136
1165
Bhp
0.42
0.47
0.52
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
.....
1.0
Watts
416
465
519
579
645
717
796
881
974
1075
1184
Rpm
947
971
995
1020
1045
1071
1097
1124
1151
---
*Motor drive range: 770 to 1175 rpm. All other rpms require fieldsupplied drive.
43
Watts
523
578
638
705
777
857
942
1035
1136
---
(in. wg)
1.8
Rpm
1200
1223
1245
......
Bhp
1.01
1.09
1.17
2.0
Watts
1004
1081
1165
Rpm
1254
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
Bhp
0.53
0.58
0.64
0.71
0.78
0.86
0.95
1.04
1.14
---
Bhp
1.14
---
Watts
1136
---
Table 34 -- Fan Performance 50TFF,TM006 -- Horizontal Discharge Units; Standard Motor (Direct Drive)*
LOW SPEED
AIRFLOW
CFM
15OO
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
208 v
ESP
1.01
0.82
0.64
0.44
0.32
0.21
0.13
0.05
Bhp
0.67
0.70
0.73
0.75
0.78
0.81
0.83
0.86
MEDIUM SPEED
230, 460, 575 v
Watts
750
780
810
839
869
899
929
959
ESP
1.25
1.09
0.97
0.81
0.66
0.47
0.32
0.19
0.08
Bhp
0.71
0.74
0.77
0.80
0.83
0.86
0.89
0.92
0.96
Watts
791
824
857
891
924
957
990
1023
1057
208 v
ESP
1.26
1.11
0.99
0.84
0.69
0.51
0.36
0.21
0.08
Bhp
0.70
0.74
0.77
0.80
0.83
0.86
0.89
0.92
0.95
230, 460, 575 v
Watts
782
821
861
900
940
979
1018
1058
1097
---
LEGEND
Bhp
ESP
Watts
----
ESP
1.46
1.32
1.22
1.09
0.96
0.80
0.64
0.50
0.34
0.24
0.15
Bhp
0.76
0.79
0.83
0.86
0.90
0.93
0.96
1.00
1.03
1.07
1.10
Watts
845
883
921
959
997
1035
1073
1111
1149
1187
1225
HIGH
SPEED
208 v
230,
460,
575 v
ESP
Bhp
Watts
ESP
Bhp
Watts
1.46
1.33
1.24
1.11
0.99
0.83
0.71
0.58
0.39
0.29
0.16
0.79
0.82
0.85
0.89
0.92
0.95
0.99
1.02
1.06
1.09
1.12
875
913
950
988
1025
1063
1101
1138
1176
1213
1251
1.52
1.41
1.33
1.22
1.11
0.97
0.86
0.76
0.57
0.49
0.34
0.85
0.89
0.92
0.96
0.99
1.03
1.06
1.10
1.13
1.17
1.20
949
988
1027
1066
1105
1144
1183
1222
1261
1300
1340
See general fan performance
notes on page 33.
Brake Horsepower Input to Fan
External Static Pressure (in. wg)
Input Watts to Motor
Table 35 -- Fan Performance 50TFF,TM005 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.2
Rpm
643
674
706
738
771
804
837
871
906
Watts
233
276
324
379
440
507
582
665
756
Rpm
762
791
820
849
879
910
941
972
1004
Bhp
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94
Watts
344
395
451
515
584
661
745
837
938
1.2
Rpm
1089
1114
1139
1164
1190
1217
1244
1271
1298
Bhp
0.84
0.92
1.01
1.10
1.20
1.31
1.42
1.55
1.68
1.4
Watts
835
915
1000
1093
1193
1301
1417
1541
1674
Rpm
1153
1177
1202
1227
1252
1278
1305
1331
1358
Bhp
0.98
1.06
1.15
1.25
1.36
1.48
1.60
1.73
1.87
Watts
971
1056
1149
1248
1355
1470
1593
1724
1865
STATIC PRESSURE (in. wg)
0.6
Rpm
860
887
914
942
971
1000
1029
1059
1089
EXTERNAL
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
Bhp
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76
0.4
---
Watts
459
517
582
653
731
816
909
1010
1119
Rpm
944
970
997
1024
1051
1079
1107
1138
1165
STATIC PRESSURE (in. wg)
1.6
Rpm
1212
1236
1261
1285
1311
1336
1362
1388
1415
LEGEND
Bhp
Watts
Bhp
0.46
0.52
0.59
0.66
0.74
0.82
0.91
1.02
1.12
Bhp
1.12
1.21
1.31
1.41
1.83
1.65
1.78
1.92
2.07
Watts
1111
1202
1301
1407
1520
1642
1772
1911
2059
Rpm
1269
1292
1316
1341
1366
1391
1416
1442
1468
0.8
Bhp
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.0
Watts
579
645
717
796
881
974
1075
1164
1301
Rpm
1020
1045
1071
1097
1124
1151
1176
1206
1234
Bhp
0.71
0.78
0.86
0.95
1.04
1.14
1.25
1.37
1.49
Watts
1256
1353
1457
1570
1690
1818
1955
2101
2256
Rpm
1322
1346
1369
1394
1418
1443
1468
1494
--
Bhp
1.41
1.82
1.63
1.75
1.87
2.01
2,15
2.31
--
1.8
Bhp
1.26
1.36
1.47
1.88
1.70
1.83
1.97
2.11
2.27
2.0
NOTES:
1. Boldface indicates field-supplied drive is required,
2. Maximum continuous bhp is 2,40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require fieldsupplied drive.
44
Watts
705
777
857
942
1035
1136
1244
1361
1488
Watts
1404
1508
1618
1736
1863
1998
2141
2294
--
Table 36 -- Fan Performance 50TFF006 -- Horizontal Discharge Units; Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
776
813
851
888
927
965
1004
1044
1084
1123
1164
Watts
340
397
461
532
610
697
792
896
1009
1132
1265
Rpm
883
916
949
984
1019
1054
1090
1127
1164
1201
1239
Bhp
0.51
0.58
0.66
0.75
0.84
0.94
1.06
1.18
1.32
1.46
1.62
Watts
454
517
586
662
747
839
940
1050
1169
1298
1437
Rpm
977
1007
1038
1069
1102
1135
1169
1203
1238
1273
1309
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.38
0.45
0.52
0.60
0.69
0.78
0.89
1.01
1.14
1.27
1.42
STATIC PRESSURE
0.6
0.4
1.2
Rpm
1210
1236
1262
1289
1317
1345
1375
1405
1435
1466
Bhp
1.14
1.23
1.33
1.44
1.55
1.68
1.81
1.96
2.12
2.29
Rpm
1278
1302
1328
1354
1380
1408
1436
1465
1494
............
Bhp
1.33
1.42
1.52
1.63
1.75
1.88
2.03
2.18
2.34
Watts
1178
1261
1351
1450
1557
1673
1798
1933
2078
Rpm
1342
1365
1390
1415
1441
1467
1494
1522
.........
LEGEND
Bhp
Watts
---
Watts
579
646
721
802
892
990
1096
1211
1336
1471
1616
STATIC PRESSURE
1.6
1.4
Watts
1014
1094
1181
1276
1379
1491
1611
1742
1882
2032
Bhp
0.65
0.73
0.81
0.90
1.00
1.11
1.23
1.36
1.50
1.66
1.82
Bhp
1.52
1.62
1.72
1.84
1.96
2.10
2.24
2.40
Watts
1350
1436
1530
1632
1743
1863
1993
2132
(in. wg)
0.8
Rpm
1061
1089
1118
1148
1179
1210
1242
1274
1308
1341
1375
Bhp
0.80
0.89
0.97
1.07
1.18
1.29
1.42
1.55
1.70
1.86
2.03
1.0
Watts
715
786
865
951
1046
1149
1260
1381
1511
1651
1801
Rpm
1138
1165
1192
1221
1250
1280
1310
1341
1373
1405
1438
Bhp
0.97
1.05
1.15
1.25
1.36
1.48
1.61
1.75
1.91
2.07
2.24
Watts
860
935
1018
1109
1208
1316
1432
1557
1693
1838
1994
(in. wg)
1.8
Rpm
1403
1425
1449
1473
1498
1524
......
......
Bhp
1.72
1.82
1.93
2.05
2.18
2.32
2.0
Watts
1530
1618
1716
1822
1937
2060
Rpm
1461
1483
1505
1529
---
Bhp
1.93
2.04
2.15
2.27
---
Watts
1717
1809
1910
2019
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30 for single-phase units and 2.40
for three-phase units.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
Table 37 -- Fan Performance 50TM006 -- Single-Phase, Horizontal Discharge Units;
Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
776
813
851
888
927
965
1004
1044
1084
1123
Watts
340
397
461
532
610
697
792
896
1009
1132
Rpm
883
916
949
984
1019
1054
1090
1127
............
............
Bhp
0.51
0.58
0.66
0.75
0.84
0.94
1.06
1.18
Watts
454
517
586
662
747
839
940
1050
Rpm
977
1007
1038
1069
1102
1135
1169
.........
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.38
0.45
0.52
0.60
0.69
0.78
0.89
1.01
1.14
1.27
STATIC PRESSURE
0.6
0.4
1.2
Rpm
1210
1236
Bhp
1.14
1.23
Rpm
1278
1302
Bhp
1.33
1.42
Watts
---
Rpm
---
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
m
LEGEND
Bhp
Watts
---
Watts
579
646
721
802
892
990
1096
STATIC PRESSURE
1.6
1.4
Watts
1014
1094
Bhp
0.65
0.73
0.81
0.90
1.00
1.11
1.23
Bhp
---
Watts
(in. wg)
0.8
Rpm
1061
1089
1118
1148
1179
1210
......
Bhp
0.80
0.89
0.97
1.07
1.18
1.29
1.0
Watts
715
786
865
951
1046
1149
Rpm
1138
1165
1192
1221
---
Bhp
0.97
1.05
1.15
1.25
---
Watts
Rpm
Bhp
(in. wg)
1.8
Rpm
Bhp
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
45
Watts
860
935
1018
1109
---
Watts
Table 38 -- Fan Performance 50TM006 -- Three-Phase, Horizontal Discharge Units;
Alternate Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
0.2
Rpm
776
813
851
888
927
965
1004
1044
1084
1123
1164
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Watts
340
397
461
532
610
697
792
896
1009
1132
1265
Rpm
883
916
949
984
1019
1054
1090
1127
1164
1201
1239
Bhp
0.51
0.58
0.66
0.75
0.84
0.94
1.06
1.18
1.32
1.46
1.62
Watts
454
517
586
662
747
839
940
1050
1169
1298
1437
1.2
Rpm
1210
1236
1262
1289
1317
1345
1375
1405
1435
1466
Bhp
1.14
1.23
1.33
1.44
1.55
1.68
1.81
1.96
2.12
2.29
1.4
Watts
1014
1094
1181
1276
1379
1491
1611
1742
1882
2032
Rpm
1278
1302
1328
1354
1380
1408
1436
1465
1494
............
Bhp
1.33
1.42
1.52
1.63
1.75
1.88
2.03
2.18
2.34
Watts
1178
1261
1351
1450
1557
1673
1798
1933
2078
STATIC PRESSURE (in. wg)
0.6
Rpm
977
1007
1038
1069
1102
1135
1169
1203
1238
1273
1309
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.38
0.45
0.52
0.60
0.69
0.78
0.89
1.01
1.14
1.27
1.42
0.4
---
Watts
579
646
721
802
892
990
1096
1211
1336
1471
1616
Rpm
1061
1089
1118
1148
1179
1210
1242
1274
1308
1341
1375
STATIC PRESSURE (in. wg)
1.6
Rpm
1342
1365
1390
1415
1441
1467
1494
1522
.........
LEGEND
Bhp
Watts
Bhp
0.65
0.73
0.81
0.90
1.00
1.11
1.23
1.36
1.50
1.66
1.82
Bhp
1.52
1.62
1.72
1.84
1.96
2.10
2.24
2.40
Watts
1350
1436
1530
1632
1743
1863
1993
2132
Rpm
1403
1425
1449
1473
1498
1524
......
......
0.8
Bhp
0.80
0.89
0.97
1.07
1.18
1.29
1.42
1.55
1.70
1.86
2.03
1.0
Watts
715
786
865
951
1046
1149
1260
1381
1511
1651
1801
Rpm
1138
1165
1192
1221
1250
1280
1310
1341
1373
1405
1438
Bhp
0.97
1.05
1.15
1.25
1.36
1.48
1.61
1.75
1.91
2.07
2.24
Watts
1530
1618
1716
1822
1937
2060
Rpm
1461
1483
1505
1529
---
Bhp
1.93
2.04
2.15
2.27
---
1.8
Bhp
1.72
1.82
1.93
2.05
2.18
2.32
Watts
860
935
1018
1109
1208
1316
1432
1557
1693
1838
1994
2.0
Watts
1717
1809
1910
2019
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 900 to 1300 rpm. All other rpms require fieldsupplied drive.
Table 39 -- Fan Performance 50TFF,TM006 -- Horizontal Units; High-Static Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
0.2
Rpm
776
813
851
888
927
965
1004
1044
1084
1123
1164
Watts
340
397
461
532
610
697
792
896
1009
1132
1265
Rpm
883
916
949
984
1019
1054
1090
1127
1164
1201
1239
Bhp
0.51
0.58
0.66
0.75
0.84
0.94
1.06
1.18
1.32
1.46
1.62
Watts
454
517
586
662
747
839
940
1050
1169
1298
1437
1.2
Rpm
1210
1236
1262
1289
1317
1345
1375
1405
1435
1466
1498
Bhp
1.14
1.23
1.33
1.44
1.55
1.68
1.81
1.96
2.12
2.29
2.47
1.4
Watts
1014
1094
1181
1276
1379
1491
1611
1742
1882
2032
2193
Rpm
1278
1302
1328
1354
1380
1408
1436
1465
1494
1524
1555
Bhp
1.33
1.42
1.52
1.63
1.75
1.88
2.03
2.18
2.34
2.51
2.70
Watts
1178
1261
1351
1450
1557
1673
1798
1933
2078
2232
2398
STATIC PRESSURE (in. wg)
0.6
Rpm
977
1007
1038
1069
1102
1135
1169
1203
1238
1273
1309
EXTERNAL
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
Bhp
0.38
0.45
0.52
0.60
0.69
0.78
0.89
1.01
1.14
1.27
1.42
0.4
---
Watts
579
646
721
802
892
990
1096
1211
1336
1471
1616
Rpm
1061
1089
1118
1148
1179
1210
1242
1274
1308
1341
1375
STATIC PRESSURE (in. wg)
1.6
Rpm
1342
1365
1390
1415
1441
1467
1494
1522
1551
1580
.........
LEGEND
Bhp
Watts
Bhp
0.65
0.73
0.81
0.90
1.00
1.11
1.23
1.36
1.50
1.66
1.82
Bhp
1.52
1.62
1.72
1.84
1.96
2.10
2.24
2.40
2.57
2.75
Watts
1350
1436
1530
1632
1743
1863
1993
2132
2280
2440
Rpm
1403
1425
1449
1473
1498
1524
1550
1578
1605
......
0.8
Bhp
0.80
0.89
0.97
1.07
1.18
1.29
1.42
1.55
1.70
1.86
2.03
1.0
Watts
715
786
865
951
1046
1149
1260
1381
1511
1651
1801
Rpm
1138
1165
1192
1221
1250
1280
1310
1341
1373
1405
1438
Bhp
0.97
1.05
1.15
1.25
1.36
1.48
1.61
1.75
1.91
2.07
2.24
Watts
1530
1618
1716
1822
1937
2060
2194
2337
2490
Rpm
1461
1483
1505
1529
1553
1579
1604
1631
--
Bhp
1.93
2.04
2.15
2.27
2.41
2.55
2.70
2.87
--
1.8
Bhp
1.72
1.82
1.93
2.05
2.18
2.32
2.47
2.63
2.80
2.0
NOTES:
1. Boldface indicates field-supplied drive is required,
2. Maximum continuous bhp is 2,90.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive.
46
Watts
860
935
1018
1109
1208
1316
1432
1557
1693
1838
1994
Watts
1717
1809
1910
2019
2137
2264
2401
2548
--
Table 40 -- Fan Performance 50TFF,TM007 -- Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
0.2
Rpm
823
857
892
927
962
997
1033
1069
1106
1142
1179
1216
1253
Watts
458
525
599
680
769
865
970
1084
1206
1338
1480
1632
1794
Rpm
924
955
986
1017
1050
1082
1115
1149
1183
1217
1251
1286
1321
Bhp
0.65
0.73
0.82
0.92
1.02
1.14
1.26
1.39
1.54
1.69
1.86
2.04
2.22
Watts
579
650
729
815
909
1010
1120
1239
1367
1503
1650
1807
1975
1.2
Rpm
1250
1273
1296
1320
1345
1371
1397
1424
1451
Bhp
1.33
1.43
1.53
1.64
1.77
1.90
2.04
2.19
2.36
1.4
Watts
1181
1266
1359
1459
1568
1686
1812
1948
2093
Rpm
1319
1341
1363
1386
1409
1434
1459
............
............
Bhp
1.53
1.63
1.74
1.85
1.98
2.11
2.26
Watts
1360
1447
1542
1646
1758
1878
2008
STATIC PRESSURE
0.6
Rpm
1015
1043
1072
1101
1131
1161
1192
1223
1255
1287
1320
1353
.........
EXTERNAL
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
0.52
0.59
0.67
0.77
0.87
0.97
1.09
1.22
1.36
1.51
1.67
1.84
2.02
0.4
---
Watts
712
787
870
960
1059
1165
1279
1403
1535
1677
1829
1991
STATIC PRESSURE
1.6
Rpm
1385
1405
1427
1448
1471
1494
.........
LEGEND
Bhp
Watts
Bhp
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58
1.73
1.89
2.06
2.24
Bhp
1.74
1.84
1.95
2.07
2.20
2.34
Watts
1549
1638
1736
1842
1956
2080
(in. wg)
0.8
Rpm
1099
1125
1151
1178
1206
1235
1264
1293
1323
1354
1385
......
Bhp
0.96
1.05
1.15
1.26
1.37
1.50
1.63
1.77
1.93
2.09
2.27
1.0
Watts
857
936
1022
1116
1218
1329
1448
1576
1713
1859
2015
Rpm
1177
1201
1226
1251
1277
1304
1332
1360
1389
1418
--
Bhp
1.14
1.23
1.33
1.44
1.56
1.69
1.83
1.98
2.14
2.31
--
Watts
1748
1839
1939
2047
Rpm
1508
1527
---
Bhp
2.20
2.31
---
Watts
1013
1096
1185
1283
1389
1503
1625
1757
1898
2049
--
(in. wg)
1.8
Rpm
1448
1467
1488
1508
......
......
Bhp
1.97
2.07
2.18
2.30
2.0
Watts
1957
2050
---
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
*Motor drive range: 1070 to 1460 rpm. All other rpms require fieldsupplied drive.
Table 41 -- Fan Performance 50TFF,TM007 -- Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
0.2
Rpm
823
857
892
927
962
997
1033
1069
1106
1142
1179
1216
1253
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Bhp
0.52
0.59
0.67
0.77
0.87
0.97
1.09
1.22
1.36
1.51
1.67
1.84
2.02
0.4
Watts
458
525
599
680
769
865
970
1084
1206
1338
1480
1632
1794
Rpm
924
955
986
1017
1050
1082
1115
1149
1183
1217
1251
1286
1321
1.2
Rpm
1250
1273
1296
1320
1345
1371
1397
1424
1451
1479
1507
Bhp
1.33
1.43
1.53
1.64
1.77
1.90
2.04
2.19
2.36
2.53
2.72
Bhp
0.65
0.73
0.82
0.92
1.02
1.14
1.26
1.39
1.54
1.69
1.86
2.04
2.22
1.4
Watts
1181
1266
1359
1459
1568
1686
1812
1948
2093
2248
2412
Rpm
1319
1341
1363
1386
1409
1434
1459
1484
1511
1537
............
Bhp
1.53
1.63
1.74
1.85
1.98
2.11
2.26
2.42
2.58
2.76
External Static Pressure (in. wg)
0.6
Watts
579
650
729
815
909
1010
1120
1239
1367
1503
1650
1807
1975
Rpm
1015
1043
1072
1101
1131
1161
1192
1223
1255
1287
1320
1353
1386
---
Watts
712
787
870
960
1059
1165
1279
1403
1535
1677
1829
1991
2163
Rpm
1099
1125
1151
1178
1206
1235
1264
1293
1323
1354
1385
1416
1448
External Static Pressure (in. wg)
1.6
Watts
1360
1447
1542
1646
1758
1878
2008
2147
2295
2454
Rpm
1385
1405
1427
1448
1471
1494
1518
1543
1568
.........
LEGEND
Bhp
Watts
Bhp
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58
1.73
1.89
2.06
2.24
2.44
Bhp
1.74
1.84
1.95
2.07
2.20
2.34
2.49
2.65
2.82
Watts
1549
1638
1736
1842
1956
2080
2213
2355
2507
Rpm
1446
1467
1488
1508
1530
1553
1576
1599
......
0.8
Bhp
0.96
1.05
1.15
1.26
1.37
1.50
1.63
1.77
1.93
2.09
2.27
2.46
2.66
1.0
Watts
857
936
1022
1116
1218
1329
1448
1576
1713
1859
2015
2182
2359
Rpm
1177
1201
1226
1251
1277
1304
1332
1360
1389
1418
1447
1477
1508
Watts
1748
1839
1939
2047
2164
2290
2425
2571
Rpm
1508
1527
1546
1566
1587
1609
---
1.8
Bhp
1.97
2.07
2.18
2.30
2.44
2.58
2.73
2.89
*Motor drive range: 1300 to 1685 rpm. All other rpms require fieldsupplied drive.
47
Watts
1013
1096
1185
1283
1389
1503
1625
1757
1898
2049
2210
2381
2563
Bhp
2.20
2.31
2.42
2.55
2.68
2.83
---
Watts
1957
2050
2151
2262
2380
2509
---
2.0
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See page 33 for general fan performance notes.
Brake Horsepower Input to Fan
Input Watts to Motor
Bhp
1.14
1.23
1.33
1.44
1.56
1.69
1.83
1.98
2.14
2.31
2.49
2.68
2.89
PRE-START-UP
START-UP
Unit Preparationstalled in accordance
ble codes.
F;filure to observe the following warnings could result in
serious personal injuu:
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is in
place and secured.
3. Do not remove compressor terminal cover until all
electrical sources are disconnected.
4.
Return-Air Filters-
Make sure correct filters ale installed in unit (see Tables IA and IB). Do not operate unit
without return-air filters.
Compressor Mountingspring mounted.
down bolts.
6.
a.
b.
c.
d.
Make the following
a.
b.
c.
d.
4.
High
Flow Refrigerant
Valves -- Two high flow
valves are located on the hot gas tube coming out of the
compressor and the suction tube going into the compressol:
L;uge black plastic caps identify these valves with O-rings
inside screwing the cap and onto a brass body. No field access
to these wdves is available at this time. Ensure the plastic caps
remain on the valves and are tight or the possibility of refrigerant leakage could occm:
Compressor
Rotation-- On 50TFF,
TM007 scroll
compressor units, it is important to be certain compressor is
rotating in the proper direction. To determine whether or not
compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressol:
3. The suction pressure should diop and the discharge
pressure should rise, as is normal on any start-up.
inspections:
Inspect for shipping and handling damages
such
as broken lines, loose parts, or disconnected
wires.
Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates
a refrigerant
leak. Leak-test all refrigerant tubing
connections
using electronic
leak detector, halide
torch, or liquid-soap solution.
Inspect all field-wiring
and factory-wiring
connections. Be sure that connections
are completed
and tight. Ensure no electrical wiring is in contact
with refrigerant tubing or sharp edges.
Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
If the suction pressure does not diop and the discharge
pressure does not rise to norlnal levels:
1. Note that the evaporator fan is probably _dso rotating
the wrong direction.
2. Turn off power to the unit. Install lock-out tag.
3. Reverse any two of the unit power leads.
4. Reapply power to the unit.
b.
c.
Make
Make
water
Make
parts
d.
sure that
sure that
to ensure
sure that
have been
in
The suction and discharge pressme levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not
provide cooling.
Cooling-
Verify the following conditions:
Make sure that condenser-fan
blades are correctly
positioned
in fan orifice. Refer to Condenser-Fan
Adjustment
section on page 52 for more details.
hold-
-- To service refrigerant
service ports, remove access panel. Each unit system has
4 Schrader-type service ports: one on the suction line, one on
the liquid line, and two on the compressor
discharge line.
Be sure that caps on the ports are tight. The Schmder-type
valve that is located under the high-pressure
switch does not
have a Schrader core.
on _dl WARNING.
labels attached to (or
a.
compressor
Refrigerant Service Ports
Proceed as follows to inspect and prepale the unit for initkd
st_ut-up:
3.
Compressors are internally
or remove
Check all electric_d connections
in
unit control boxes; tighten as requiled. Ensure wiring does not
come in contact with sharp metal edges.
Shut off electrical power to unit.
Recover refiigerant to relieve all pressure from
system using both high- and low-pressure ports.
Cut component connection
tubing with tubing
cutter, and remove component from unit.
Carefully
unsweat
remaining
tubing
stubs
when necessary. Oil can ignite when exposed
to torch flame.
1. Remove all access panels.
2. Read and follow
instructions
CAUTION,
and INFORMATION
shipped) with unit.
Do not loosen
Internal Wiring-
Relieve all pressure from system before touching or
disturbing anything inside compressor termimd box if
refiigerant leak is suspected around compressor terminals. Use accepted methods to recover refiigerant.
Never attempt to repair soldered connection while refiigerant system is under pressure.
Do not use torch to remove any component. System
contains oil and refiigerant under pressure. To remove
a component, wear protective goggles and proceed as
follows:
5.
Make sure that unit has been inwith inst;_llation instructions and applica-
Set space therlnostat
to OFF position. Set
system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Complessor st;uts on closure of contactoc
Check cooling effects at a setting below room temperature.
Check unit charge. Refer to Refrigerant
Charge section,
page 52.
Reset thermostat at a position above room temperature.
Compressor will shut off.
air filters are in place.
condensate
drain trap is filled with
proper drainage.
all tools and miscellaneous
loose
removed.
TO SHUT OFF UNIT -- Set system selector switch at OFF
position. Resetting
thermostat
at a position above room
temperature shuts unit off tempor_uily until space temperature
exceeds thermostat setting.
48
Safety
ReliefA soft solder joint in tile suction line at
the low-pressure
sel-vice port provides pressure relief under
abnormal temperature and pressure conditions.
the PremierLink control
from the thermostat.
Ventilation
to
•
•
•
•
•
(Continuous
Fan)
selector switches at ON and OFT
Evaporator fan operates continuously
circulation.
Operating
in response
to the YI and Y2 inputs
The PremierLiuk control will use the following information
determine if flee cooling is available:
Indoor fan has been on for at least 30 seconds.
The SPT. SAT. and OAT inputs must have valid readings.
OAT must be less than 75 E
OAT must be less than SPT.
Euthalpy must be LOW (may be jumpered if an euthalpy
sensor not available).
• Economizer
position is NOT forced.
-- Set fan and systeln
positions, respectively.
to provide constant air
Sequence
COOLING.
UNITS WITHOUT
ECONOMIZER
-- When
thermostat calls for cooling, terminals G and YI me energized.
The indoor-fan contactor (IFC) and compressor contactor are
energized and indoor-fan motor, compressol: and outdoor fan
starts. The outdoor-fan motor runs continuously while unit is
cooling.
Pre-cooling occurs when the is no call from the therlnostat
except (3. Pie-cooling is defined as the economizer modulates
to provide 70 F supply ;tic
When fiee cooling is available the PremierLiuk control will
control the compressors and economizer to provide a supply;fir temperature determined to meet the YI and Y2 calls from
the thermostat using the following thlee routines. The three
control routines are based on OAT.
HEATING, UNITS WITHOUT ECONOMIZER
-- Upon a
request for heating from the space therlnostat, terminal WI will
be energized with 24 v. The IFC and heater contactor (HCI)
are energized.
COOLING, UNITS WITH ECONOMISER
IV -- When free
cooling is not available, the complessors will be controlled by
the zone thermostat.
When flee cooling is available, the
outdoor-air
dmnper is modulated
by the EconoMi$er
IV
control to provide a 50 to 55 F supply-air temperatme into the
zone. As the supply-air temperatme fluctuates above 55 or below 50 E the &_mpers will be modulated (open or close) to
bring the supply-air tempemtme back within the set point limits.
The 3 routines ale based on OAT where:
•
Integrated EconoMi$er IV operation on single-stage units requires a 2-stage thennostat (YI and Y2).
For EconoMi$er
IV operation, there must be a therlnostat
call for the fan (G). This will move the damper to its minimum
position during the occupied mode.
•
If the increase in cooling capacity causes the supply-air temperature to drop below 45 E then the outdoor-air cklmper position will be lully closed. If the supply-air temperature continues to fall, the outdoor-air dmnper will close. Control returns to
normal once the supply-air temperature rises above 48 E
•
•
•
•
•
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be energized and deenergized.
•
If field-installed accesso U CO 2 sensors are connected to the
EconoMiSer IV control, a demand controlled ventilation strategy will begin to operate. As the CO,_ level in the zone increases
above the CO2 set point, the minimum position of the &_mper
will be increased proportionally. As the CO 2 level decreases
because of the inclease in fresh all: the outdoor-air damper will
be proportionally closed. Dmnper position will follow the higher demand condition from DCV mode or free cooling mode.
•
•
•
•
Damper movement from full closed to lull open (or vice
velsa) will take between 11/2and 21/2 minutes.
SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point
PID = Proportional Integral
Routine 1 (OAT < DXCTLO)
YI energized
- economizer
maintains
a SASP =
(SATLOI + 3).
Y2 energized
- economizer
maintains
a SASP =
(SATLO2 + 3).
Routine 2 (DXCTLO < OAT < 68 F)
If only YI energized, the economizer
maintains a SASP
= (SATLOI + 3).
If SAT > SASP + 5 and economizer
position > 80%,
economizer will go to minimum position for 3 minutes or
until SAT > 68 E
First stage of mechanical cooling will be energized.
Integrator resets.
Economizer
opens again and controls to current SASP
after stage one on for 90 seconds.
With YI and Y2 energized Economizer
maintains
an
SASP = SATLO2 + 3.
If SAT > SASP + 5 and economizer
position >80%,
economizer will go to minimum position for 3 minutes or
until SAT > 68 E
If compressor
one is on then second stage of mechanical
cooling will be energized. Otherwise the first stage will
be energized.
Integrator resets.
Economizer
opens again and controls
to SASP after
stage one on for 90 seconds.
Routine 3 (()AT > 68)
Economizer is opened 100%.
Compressors
1 and 2 are cycled based on YI and Y2
using minimum on and off times and watching the supply air temperature
as compared
to SATLOI
and
SATLO2 set points.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be energized and deenergized.
If field-installed accessory CO 2 sensors ;ue connected to the
PremierLink
control, a PlD-controlled
demand ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO_ set point, the minimum position of the
cklmper will be increased proportionally.
As the CO 2 level
decreases because of the increase in fresh ;fir, the outdoor-air
&_mper will be proportionally closed.
If fiee cooling can be used as determined fiom the appropriate changeover command (switch, d U bulb, enthalpy curve,
diffelential d U bulb, or differential enthalpy), a call for cooling
(YI closes at the thermostat) will cause the control to modulate
the &impels open to maintain the supply air temperature set
point at 50 to 55 E
•
•
As the supply-air temperature diops below the set point
range of 50 to 55 E the control will modulate the outdoor-air
dampers closed to maintain the proper supply-air temperature.
HEATING, UNITS WITH ECONOMISER
IV -- When the
room telnperature calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer
section. When the thermostat
is satisfied, the economizer
damper moves to the minimum position.
COOLING.
UNITS WITH ECONOMISER2,
PREMIERLINK TM CONTROL AND A THERMOSTAT
-- When free
cooling is not available, the compressols will be controlled by
49
HEATINGUNITSWITH ECONOMISER2,
PREMIERLINK CONTROL AND A THERMOSTAT -- When the
TM
thermostat calls for heating, termimfl WI is energized. The
PremierLink control will move the economizer damper to the
minimum position if there is a call for G and closed if there is a
call for W 1 without Ca.The IFC and heater contactor (HC 1) tue
energized.
When the thermostat is satisfied and WI is deenergized, the
IFM stops after a 45-second time-off delay unless G is still
maintainedi
COOLING.
UNITS WITH ECONOMI$ER2,
PREMIERLINK CONTROL
AND A ROOM SENSOR -- When free
cooling is not available, the compressors will be controlled by
the PremierLink controller using a PID Error reduction c_dculation as indicated by Fig 40.
The PremierLink controller will use the following information to deterraine if free cooling is available:
• Indoor fan has been on for at least 30 seconds.
• The SPT. SAT. and OAT inputs must have valid readings.
• OAT must be less than 75 tv.
• OAT must be less than SPT.
• Enthalpy
must be LOW (may be jumpered
if and
enthalpy sensor is not available).
• Economizer
position is NOT forced.
When free cooling is available, the outdoor-air damper is
positioned through the use of a Proportional
Integral (PID)
control process to provide a calculated supply-air temperature
into the zone. The supply air will maintain the space temperature between the heating and cooling set points as indicated in
Fig. 41.
The PremierLink controller will integrate the compressoLs
stages with the economizer based on similar logic as the three
routines listed in the previous section. The SASP will float up
and down based on the error reduction calculations that compare space temperature and space set point.
When outside-air temperature conditions require the economizer to close for a compressor stage-up sequence, the economizer control integrator is reset to zero after the stage-up sequence is completed. This prevents the supply-air temperature
from diopping too quickly and creating a freeze condition that
would make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion)
cooling control, while the economizer space set point is a
c_dculated value between the heating and cooling set points.
The economizer set point will always be at least one degree
below the cooling set point, allowing for a smooth transition
from mechanical
cooling with economizer
assist, back to
economizer
cooling as the cooling set point is achieved.
The compressors
may be used for initial cooling then the
PremierLink controller will modulate the economizer using an
error reduction calculation
to hold the space temperature
between the heating and cooling set points. See Fig. 41.
The controller uses the following conditions to determine
economizer cooling:
• Enthalpy is Low
• SAT reading is available
• OAT reading is available
• SPT reading is available
• OAT < SPT
• Economizer
Position is NOT forced
If field-installed accessory CO 2 sensors gue connected to
the PremierLink TM control, a PID-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally. As the CO2 level
decreases because of the increase in flesh aik the outdoor-air
damper will be proportionally closed.
HEATING UNIT WITH ECONOMI$ER2, PREMIERLINK
CONTROL AND A ROOM SENSOR -- Eve U 40 seconds
the controller will calculate the required heat stages (maximum
of 3) to maintain supply-air temperature (SAT) if the following
qualifying conditions am met:
• Indoor fan has been on for at least 30 seconds.
• COOL mode is not active.
• OCCUPIED, TEMP.COMPENSATED START or HEAT
mode is active.
• SAT reading is available.
• Fire shutdown mode is not active.
If all of the above conditions gue met, the number of heat
stages is c_dculated; otherwise the required number of heat
stages will be set to 0.
If the PremierLink controller determines that heat stages am
required, the economizer damper will be moved to minimum
position if occupied and closed if unoccupied.
Staging should be as follows:
If Heating PID STAGES=2
• HEAT STAGES=I (50% capacity) will energize HSI
• HEAT STAGES=2 (100% capacity) will energize HS2
If Heating PID STAGES=3 and AUXOUT = HS3
• HEAT STAGES=I (33% capacity) will energize HSI
• HEAT STAGES=2 (66% capacity) will energize HS2
• HEAT STAGES=3 (100% capacity) will energize HS3
TEMPERATURE
m
CONTROL
75,
744
'_ 734
££
724
...... SET
POINT
714
Iw
O
_TEMPERATURE
704
694
cO 68 J
TIME
NOTE: PremierLink control performs smart staging of 2 stages of DX
cooling and up to 3 stages of heat.
Fig. 40 --
DX Cooling Temperature
Control Example
TEMPERATURECONTROL
cc
74
73
__
If any of the above conditions are not met, the economizer
submaster reference (ECSR) is set to maximum limit and the
dmnper moves to minimum position. The operating sequence
is complete. The ECSR is recalculated every 30 seconds.
71 ]
m_ow
ii j
......... ....................................
F OOOLSETPOINT
/
_
I--
v
TEMPERATURE
k___ HEAT SETPOINT
TIME
If an optional power exhaust is inst_dled, as the outdoor-air
dmnper opens and closes, the power exhaust fans will be
energized and deenergized.
Fig. 41 -- Economizer Temperature
Control Example
5O
SERVICE
REMOVE
REMOVE
SCREWS
REMOVE
SCREWS
TOP
PANEL
CONDENSER
CONTROL POST
CORNER POST
\
When servicing unit, shut off all electdcCd power to unit to
avoid shock hazard or injury fiom rotating parts.
Cleaning
--Inspect unit interior at tile beginning of heating and cooling season and as operating conditions require.
EVAPORATOR
COIL
1. Turn unit power off. Install lockout tag. Remove evapolatot coil access panel.
2. If economizer
or two-position
damper
is installed,
remove economizer by disconnecting
Molex plug and
removing mounting screws.
3. Slide filtel_ out of unit.
4.
5.
Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canistel: Wash both sides
of coil and flush with clean water. For best results,
back-flush tow_ud return-air section to remove foreign
material. Flush condensate pan after completion.
Reinst_dl economizer and filters.
6.
Reconnect
7.
Replace access panels.
COILCENTER
POST
REMOVE
SCREWS
COMPRESSOR
ACCESS
PANEL
CONDENSER
COIL
Fig. 42 -- Cleaning
COILCORNER
POST
REMOVE
CORNER
Condenser
CENTER
BAFFLE
COIL
POST
Coil
TOP PANEL
wiring.
CONDENSER
COIL--Inspect
coil monthly. Clean condenser coil annually, and as required by location and outdoor
air conditions.
One-Row Coils -- Size 004 -- Wash coil with commercial
coil cleanel: It is not necessary to remove the top panel.
2-Row Coils -- Sizes 005-007
Clean coil as follows:
1. Turn offunit powel: Install lockout tag.
2. Remove top panel screws on condenser end of unit.
3.
4.
5.
6.
ACCESS
PANEL
Secure inner and outer coil rows together
supplied fastenec
8.
Reposition the outer coil section and remove the coil
comer post from between the top panel and center post.
Reinstall the coil corner post and replace all screws.
CONDENSATE
DRAINCheck
stml of cooling season. In winter,
against freeze-up.
COIL
Fig. 43 -- Propping Up Top Panel
Remove condenser coil corner post. See Fig. 42. To hold
top panel open, place coil corner post between top panel
and center post. See Fig. 43.
Remove screws securing coil to complessor plate and
compressor access panel.
Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 44.
Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal mannel:
7.
CONDENSER
TOP VIEW
...------TOP PANEL
with a field-
INNERCOIL
and clean each year at
protect condensate di'ain
OUTER
COILSECTION
FILTERS -- Clean or replace at start of each heating and cooling season, or more often if operating conditions require it.
Replacement
filters must be stone dimensions
as original
filters.
(4") MAX
HAIRPIN
OUTDOOR-AIR
INLET SCREEN
-- Clean screen with
steam or hot water and a mild detergent. Do not use disposable
filters in place of scleen.
t
END
CLEAN
Fig. 44 -- Separating
51
Coil Sections
Lubrication
COMPRESSORSEach compressor
correct amount of oil at the factory.
is charged
Manual Outdoor-Air
Damper -- If outdoor-air damper blade adjustment is required, see Manual Outdoor-Air
with the
Damper section on page 19.
EconoMiSer IV Adjustment -- Refer
FAN-MOTOR
BEARINGS
-- Fan-motor bearings are of the
permanently lubricated type. No further lubrication is required.
No lubrication
of condenser
or evaporator-fan
motors is
required.
EconoMiSer
Condenser
Fan Belt Inspection -- Check condition of evaporator belt or tension dunng heating and cooling
inspections or as conditions require. Replace belt or adjust as
necessary. Refer to Step 7 -- Adjust Evaporator-Fan Speed on
page 31 for proper adjusting procedures and belt tension.
1. Shut offunit
Adjustment
4.
Adjust fan height as shown in Fig. 45.
5.
Tighten setscrews.
6.
Replace condenser-fan
LOW CHARGE COOLING -- Use Cooling Ch;u'ging Charts,
Fig. 46-49. Vary refrigerant until the conditions of the appropriate chart am met. Note the charging chart is different from type
norm_dly used. Chmt is based on chalging the units to the correct superheat for the vtuious operating conditions. Accurate
pressure gage and temperature
sensing device ;ue required.
Connect the pressure gage to the service port on the suction
line. Mount the temperature sensing device on the suction line
and insulate it so that outdoor ambient temperature does not
affect the reading. Indoor-air cfln must be within the normal
operating range of the unit.
TO USE COOLING CHARGING
CHARTTake the outdoor ambient temperature and read the suction pressure gage.
Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If
suction temperature
is low, carelidly recover some of the
chtuge. Recheck the suction pressure as charge is adjusted.
assembly.
OUTLET GRILLE
T
2 3/4"
MAX.
FAN MOTOR
CONDENSER
__
Example:
1"
Outdoor
Suction
Suction
(Suction
f
CONDENSER
Fig. 45 -- Condenser
is
NO CHARGE -- Use standard evacuating techniques. After
ew_cuating system, weigh in the specified amount of refrigerant. (Refer to Tables IA and lB.)
(grille, motor, and fan).
_°°°°°°°°°
Condenser
coil grille
No adjustments are required.
Charge -- Amount of refrigerant charge is
listed on unit nameplate (also refer to Tables 1A and 1B). Refer
to Carrier GTAC2-5 Charging, Recovery,
Recycling,
and
Reclamation
training manual and the following procedures.
Unit panels must be in place when unit is operating during
ch_uging procedure.
(Fig. 45)
Remove condenser-fan assembly
Ix_osen fan hub setscrews.
Optional
Refrigerant
power supply. Install lockout tag.
2.
3.
to
section on page 23.
Coil Grille--
shipped factory-installedi
Evaporator
Condenser-Fan
[V and EconoMi$er2
FAN
(Fig. 48)
Temperature ..............................
Pressure ...............................
Temperature should be ......................
Temperature may v;u-y _+5 E)
Replacement
Fan Adjustment
parts may
request.
52
Parts
be obtained
85 F
80 psig
77 F
-- A complete list of replacement
flom any Canier distributor upon
3 TON UNIT CHARGING
SUCTION
-7
LINE TEMPERATURE
4
CHART
(DEG.
C)
10
16
21
OUTDOOR
TEMP
I O0
9O
--
80
w
m
7o
w
w
z
-._1
z
F
125
C
52
115
46
105
41
95
35
85
29
75
24
65
18
55
13
45
7
6o
_.q
I-_
5o
276
4o
30
207
20
30
40
50
SUCTION
Fig. 46-
60
LINE TEMPERATURE
Cooling
(DEG.
Charging
4 TON UNIT CHARGING
SUCTION
-7
4
LINE TEMPERATURE
70
80
F)
Chart; 50TFF,TMO04
CHART
(DEG.
C)
10
16
OUTDOOR
27
TEMP
I00
90
!
80
w
_
7o
w
w
z
_
z
0
_
5o
_
345
276
40
30
207
20
40
50
SUCTION
60
LINE TEMPERATURE
Fig. 47 -- Cooling
(DEG.
Charging
53
70
F)
Chart; 50TFF,TMO05
C
125
52
115
46
105
41
95
35
85
29
75
24
65
18
55
13
45
ZZ ZZ
60
F
80
-I--
7
5 TON UNIT CHARGING CHART
-7
-1
4
10
SUCTION
16
LINE TEMPERATURE
(DEG.
21
27
OUTDOOR
F TEMPc
C)
100
_-
689
-_
_'_
_._ ...- --_
69
O.
..,,.- ,,'_ ""-_
'--- ""
""
-"" -_"
621
_
_J
z
,.,,,,,,_,,,,,,,,_
_z
52
115
46
105
41
95
35
-_
-J
85
29
.,--
o
75
24
_
65
18
#J
n69
69
#J
nO.
#J
125
_
483
,,...,.., _'
414 a,,
-n
_o
FO
_
69
""_
.._,_ r_'
345 __
276
30
207
20
30
40
50
SUCTION
60
LINE TEMPERATURE
Fig. 48 -- Cooling
(DEG.
Charging
70
80
F)
Chart;
50TFF,TMO06
6 TON UNIT (60 Hz) CHARGING CHART
SUCTION
-7
-1
LINE
TEMPERATURE
4
(DEG.
C)
10
16
21
27
IO0
OUTDOOR
TEMP
F
125
115
105
95
85
75
65
55
45
414
o.
m
z
..J
z
345
10
o3
276
4O
3O
207
20
30
40
50
SUCTION
LINE
60
TEMPERATURE
Fig. 49 -- Cooling
Charging
54
(DEG.
70
F)
Chart;
50TFF,TMO07
8O
C
52
46
41
35
29
24
18
13
7
TROUBLESHOOTING
should turn on. The actuator should drive to between 90
and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
5. Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9 v. The actuator should
&'ive fully closed.
6. Turn the DCV and Exhaust potentiometers
CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns on.
7. Return EconoMiSer
IV settings and wiling to normal
after completing troubleshooting.
DCV MINIMUM AND MAXIMUM POSITION -- To check
the DCV minimum and maximum position:
Unit Troubleshooting
for unit troubleshooting
-- Refer to Fig. 50 and Table 42
information.
EconoMiSer
IV Troubleshooting
for EconoMiSer
IV logic.
--
See
Table
43
A functional view of the EconoMiSer is shown in Fig. 51.
Typical settings, sensor lunges, and jumper positions are
also shown.
An EconoMiSer
IV simukitor
proglam
is
available from Carrier to help with EconoMiSer IV training
and troubleshooting.
ECONOMISER
IV PREPARATION
-- This procedure
is
used to prepare the EconoMi$er
IV for troubleshooting.
No
troubleshooting or testing is done by performing the following
procedure.
NOTE: This procedure requires a 9-v battery. 1.2 kilo-ohm
resistok and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
l tiometers
IMPORTANT:
before Bestarting
sure totroubleshooting.
record the positions
1. Make sure EconoMiSer
IV preparation procedure has
been performed.
2. Connect a 9-v batte q to AQ (positive node) and AQI
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80%
open.
4. Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should
drive fully closed.
8. Return EconoMiSer
IV settings and wiling to normal
after completing troubleshooting.
SUPPLY-AIR INPUT -- To check supply-air input:
of all poten-
1. Disconnect power at TR and TRI. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and PI.
3. Jumper P to PI.
4. Disconnect wires at T and TI. Place 5.6 kilo-ohm resistor
across T and TI.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals So and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals S o and +.
8. Put 620-ohm resistor across terminals SR and +.
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum
position potentiometer
lillly CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to termimds TR and TRI.
DIFFERENTIAL
ENTHALPY-To check
differential
enthalpy:
1. Make sure EconoMiSer
IV preparation procedure has
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to TI.
The actuator should drive fully open.
4. Remove the jumper across T and TI. The actuator should
drive fully closed.
5. Return EconoMi$er
IV settings and wiling to normal
after completing troubleshooting.
ECONOMI$ER
IV TROUBLESHOOTING
COMPLETION -- This procedure is used to return the EconoMi$er IV
to operation. No troubleshooting or testing is done by performing the following procedure.
1. Make sure EconoMiSer
IV prepmation procedure has
been performed.
2. Place 620-ohm resistor across So and +.
3. Pkice 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
4. Remove 620-ohm resistor across S o and +. The Free
Cool LED should turn off.
5. Return EconoMi$er
IV settings and wiring to normal
after completing troubleshooting.
SINGLE
ENTHALPY
-- To check single enth_dpy:
1. Disconnect power at TR and TRI.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer
to previous
setting.
4. Set minimum position, DCV set point, and exhaust
potentiometel.s to previous settings.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor flom terminals SO
and +. [f used, reconnect sensor flom terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor fiom T and TI. Reconnect
wires at T and TI.
1. Make sure EconoMiSer
IV prepmation procedure has
been performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Flee Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMiSer
IV settings and wiring to normal
after completing troubleshooting.
DCV (Demand
Controlled
Ventilation)
AND POWER
EXHAUST -- To check DCV and Power Exhaust:
1. Make sum EconoMiSer
IV pmpmation procedure has
been performed.
2. Ensure terminals AQ and AQI are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQI
(negative node). The LED for both DCV and Exhaust
10.
Remove jumper flom P to PI. Reconnect device at P and
PI.
11. Apply power (24 vac) to terminals TR and TRI.
55
SCHEMATIC
208/230
BLK
_'BLK_
--BLK
_Z_
3 60
c
C
h -u
YEL
y EL ,_,ly _ L
I
BLU
....
.......
BLK_
QT
_
........
_BRN_
SEE NOTE_3
ELECTRIC HEAT
OPTION ONLY,
FIELB
FOR ALL 208/230V
HEATER OPTIONS
POWER
USEB OVER
WITH
WITH 17.0 KWI I
MAXIMUM WIRE
SUPPLY
51ZE 2/0 AWG
I
SEE NOTE#4
----_LKYEL_
I1
/
|
L
,
BLU[
BLuB&
_BLU
3
......
,BRNI
] TB4
,BRNI
C
C
CONNECTION
}BOARO
PL6 R
FOR 5TD
UNIT
C
PLG
ECONOMIZER
-PNK
RED
) TRAN
HC2
HCl
] TB4
.--(_
] TB4
Y
BRN-.--(_
[FC,3
) OR
IFC
IFCIFC
3
)OR
) TRAN
} Tun
CONN
BOARO
=U_
[]
[]
[]
[]
[]
LEGEND
C
I
CAP
COMP
EQUIP
FPT
FU
GND
HC
HPS
IFC
IFM
LPS
LSM
OFM
OLR
p
PL
QT
SAT
TB
TDR
TRAN
-------------
----
Contactor, Compressor
Capacitor
Compressor Motor
Equipment
Freeze Up Protection Thermostat
Fuse
Ground
Heater Contactor
High-Pressure Switch
Indoor Fan Contactor
Indoor (Evaporator) Fan Motor
Low-Pressure/Loss-of-Charge
Switch
Limit Switch (Motor)
Outdoor (Condenser) Fan Motor
Overload Relay
Plug
Plug Assembly
Quadruple Terminal
Supply Air Temperature Sensor
Terminal Block
Time Delay Relay
Transformer
Field Splice
Marked Wire
Terminal (Marked)
0
[_
Terminal (Unmarked)
Terminal
•
Block
Splice
Splice (Marked)
Factory Wiring
NOTES:
1, If any of the original wire furnished must
be replaced, it must be replaced with
type 90 C wire or its equivalent.
2, Three-phase motors are protected under
primary single-phasing conditions.
3, Use copper conductors only.
4, Use copper, copper clad aluminum or
aluminum conductors.
5, TRAN is wired for 230-v unit. If unit is to
be run with 208-v power supply disconnect BLK wire from 230-v tap (ORN) and
connect to 208-v tap (RED). Insulate end
of 230-v tap.
6, Unit will have either LSM or OLR, but not
both.
Field Control Wiring
Field Power Wiring
Accessory
i
or Optional Wiring
To indicate common potential only;
not to represent wiring.
Fig. 50 -- Typical Wiring Schematic (208/230-3-60
56
Unit Shown)
Table 42 -- Cooling Service Analysis
PROBLEM
CAUSE
Compressor
and
Condenser
Fan
Will Not Start.
Power failure.
Fuse blown or circuit
Defective
Insufficient
Incorrect
Compressor
Cycles
(Other Than Normally
Satisfying
Thermostat).
tripped.
contactor,
transformer,
or control
line voltage.
Replace
Refrigerant
or undercharge.
Recover refrigerant, evacuate system,
nameplate.
Replace and determine cause.
overcharge
Defective
compressor.
Defective
run/start
Defective
thermostat.
Dirty air filter.
Unit undersized
capacitor,
overload,
or start relay.
motor
or capacitor.
Locate
for load.
unit size.
Reset thermostat.
compressor.
Recover
refrigerant,
Condenser
Clean
coil dirty or restricted.
rotating in wrong
direction.
Reverse the 3-phase
section on page 48.
Replace
coil.
Clean
overcharged.
air restricted
or air short-cycling.
charge.
Recover
excess
Recover
refrigerant,
compressor.
Remove
restriction.
compressor.
Recover
excess
Replace
filter.
Low refrigerant
Insufficient
charge.
device or low-side
evaporator
restricted.
airflow.
Temperature
too low in conditioned
Outdoor ambient below 25 E
area.
Time off delay not finished.
57
evacuate
system,
and recharge.
repair and recharge.
Replace
Replace
overcharged.
in Start-Up
cause and correct.
Compressor
Dirty air filter.
power leads as described
refrigerant.
Check for source
valves leaking.
and recharge.
filter.
Check for leaks;
in liquid tube.
system,
coil.
Determine
valves leaking.
evacuate
coil or remove restriction.
High head load.
Metering
Evaporator
Fan Will Not
Shut Off. (Sizes 004-006
Only.)
and remove.
Replace
Refrigerant
Low.
restriction
Replace filter.
Decrease load or increase
Air in system.
Restriction
to
cause and replace.
Locate leak; repair and recharge.
Low refrigerant
cause.
and recharge
thermostat.
in compressor.
Compressor
Too
Determine
charge.
Condenser
Determine
cause and correct.
cause and correct.
Leaking valves
Refrigerant
Pressure
breaker.
Replace.
system.
Air in system.
Suction
and replace.
Low refrigerant
Dirty condenser
Pressure.
cause
fuse or reset circuit
Replace
set too low.
Dirty air filter.
Suction
Determine
Determine
Determine
in refrigerant
Excessive
Excessive
below room temperature.
power dead.
Compressor
Too Low.
and rewire correctly.
setting
One leg of three-phase
Compressor
Makes
Excessive
Noise
(50TFF, TMO07 Scroll
Only).
Head Pressure
diagram
Lower thermostat
Check wiring and repair or replace.
Determine cause. Replace compressor.
Thermostat
Pressure.
cause and correct.
Faulty wiring or loose connections
in compressor
circuit.
Compressor
motor burned out, seized, or internal overload
open.
Defective run/start capacitor, overload, start relay.
Restriction
Head
breaker.
component.
Check wiring
setting too high.
Faulty condenser-fan
Operates
Replace
Determine
Insufficient
line voltage.
Blocked condenser.
Compressor
Continuously.
relay.
or faulty wiring.
Thermostat
Compressor
Will Not Start
But Condenser
Fan Runs.
breaker
thermostat,
REMEDY
Call power company.
Replace fuse or reset circuit
and eliminate.
refrigerant.
Check for leaks;
repair and recharge.
Remove
source
of restriction.
Increase
air quantity.
Check filter and replace
Reset thermostat.
Install low-ambient
kit.
Wait for 30-second
off delay.
if necessary.
Table 43 -- EconoMi$er IV Input/Output
Logic
INPUTS
Demand Control
Ventilation (DCV)
Below set
(DCV LED Off)
Above set
(DCV LED On)
OUTPUTS
Enthalpy*
Outdoor
N Terminalt
Compressor
Return
Y1
Y2
Stage
1
High
(Free Cooling LED Off)
Low
On
On
On
Off
On
On
On
Off
Off
Off
Off
Off
Low
(Free Cooling LED On)
High
On
On
On
Off
On
Off
Off
Off
On
On
High
(Free Cooling LED Off)
Low
Low
(Free Cooling LED On)
High
*For single enthalpy control, the module compares
enthalpy to the ABCD set point.
tPower at N terminal determines Occupied/Unoccupied
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
1-tModulation is based on the DCV signal.
Stage
2
Occupied
Unoccupied
Dam )er
Minimum position
Closed
Off
Off
Modulating** (between min.
position and full-open)
Modulating** (between
closed and full-open)
Off
Off
Minimum position
Closed
On
Off
On
On
On
Off
Modulating1-1- (between min.
position and DCV maximum)
Off
Off
Off
Off
Modulatingtl(between
closed and DCV
maximum)
On
On
On
Off
On
Off
Off
Off
Modulating***
Modulatingtl-t
Off
Off
Off
Off
outdoor
***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum
position (DCV) or fully open (supply-air signal).
ttl-Modulation
is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV)
or fully open (supply-air signal).
setting:
Fig. 51 -- EconoMi$er IV Functional View
58
INDEX
Access panels 24
Barometric flow capacity 26
Carrier Comfort Network 20
Charging chart, refrigerant
53, .54
Clearance
4
CO 2 sensor
Configuration
30
Settings
29, 30
Compressor
Lubrication
.52
Mounting
48
Rotation
48
Condensate drain
Cleaning
51
Location
2, 4
Condenser coil Z 8
Cleaning
51
Condenser fan Z 8
Adjustment
.52
Control circuit
Wiring
10
Wiring raceway
10
Convenience outlet 19
Demand ventilation control 29
Dehumidification
30
Dimensions
5, 6
Dnctwork
2
EconoMiSer2
23-26
4 to 20 mA control 26
Wiring 26
EconoMiSer IV 23-30
Components
23
Control Mode 27
Damper movement
29
Troubleshooting
.5.5
Wiring 25
Electrical connections
9, 10
Electrical data
11-18
Enthalpy changeover set points 28
Evaporator coil Z 8
Cleaning
51
Ewtporator fan motor 7, 8
Lubrication
.52
Motor data 32
Performance
33-47
Pulley adjustment
31
Pulley setting Z 8, 31
Speed
7, 8
Factou-installed options
Convenience outlet 19
EconoMiSer2
23
EconoMiSer IV 23-30
Manual outdoor air damper
19
Novar controls
19
PremierLink TM controls
20-22
Filter
Cleaning
51
Installation 25
Size 7, 8
Freeze protection thermostat
Z8
High flow valves 48
High pmssnre switch
Z8
Horizontal units 1, 2
Indoor air qnality sensor 20, 27
Ix_w pressure switch
Z8
Manual outdoor air damper
19,.52
Mounting
Compressor
48
Unit 4
Nowtr controls
10
Operating sequence
Cooling
40
EconoMiSer2
49, 50
EconoMiSer IV 49
Heating 49
Ontdoor air hood 19, 24
Ontdoor air inlet screens
Cleaning
51
Ontdoor air temperature
sensor
Physical data
7, 8
Power supply
Wiring
9
PremierLink controls
20-22
Pressure switches
High pressure
7, 8
Low pressure
Z8
Pre-Start-Up
48
Refrigerant
Charge
7, 8, 52
Type
7, 8
Refrigerant ser_.ice ports
48
Replacement parts
.52
Retnrn air filter
Z 8, 48
Return air tempemtnre sensor
Rigging unit
4
Roof curb
Assembly
1
Dimensions
3
Connector package
Leveling tolerances
Weight
Z8
Safety considerations
Safety relief
49
Ser_.ice
51-.54
Service lx_rts
41_
Slab mount
2
214
3
4
1
Start-up
48-50
Start-up checklist
CL-1
Snpply-air temperature sensor
Thermostat
10
Troubleshooting
Ventilation
49
Weight
Corner
5, 6
EconoMiSer IV
Maximum
4
Unit
5-8
23
55-51_
5-8
Wiring
4 to 20 mA control
26
EconoMiSer2
26
EconoMiSer IV
25
Power connections
9
PremierLink
22
Unit
56
59
20,23
SERVICE
Packaged
discussed
Service Training programs
in this manual, including:
are an excellent
TRAINING
way to increase your knowledge
• Unit Familiarization
• Maintenance
• Installation
• Operating Sequence
Overview
A hu'ge selection of product, theory, and skills programs are available,
and materials. All include video and/or slides, plus companion book.
using popuhu
of the equipment
video-based
formats
Classroom
Service Training which includes "hands-on" experience with file products in our labs can
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course
descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-644-5544
] Packaged Service Training
[
] Classroom Service Training
Copyright 2005 Carrier Corporation
Manufacturer
reserves
the right to discontinue,
Catalog No. 04-53500010-01
or change at any time, specifications
Printed in U.S.A.
or designs
Form 50T-5SI
without
notice and without
Pg 60
9-05
incurring
obligations.
Replaces:
50T-3SI
START-UP CHECKLIST
(Remove and Store in Job File)
PRELIMINARY
MODEL
INFORMATION
NO.
SERIAL
DATE:
NO.
TECHNICIAN:
BUILDING
II. PRE-START-UP
[]
(insert
checkmark
in box as each item is completed)
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED AS SHOWN IN THE
INSTALLATION
INSTRUCTIONS
[]
CHECK ALL ELECTRICAL
[]
CHECK THAT RETURN-AIR
[]
VERIFY THAT UNIT INSTALLATION
INSTALLATION
INSTRUCTIONS
[]
LOCATION:
CHECK FAN WHEEL
TIGHTNESS
PULLEY
CONNECTIONS
AND TERMINALS
FILTERS ARE CLEAN
FOR TIGHTNESS
AND IN PLACE
IS LEVEL WITHIN
TOLERANCES
LISTED IN THE
LU
2:
m
AND PROPELLER
FOR LOCATION
IN HOUSING/ORIFICE
c_
AND SETSCREW
LU
I--
[]
CHECK
ALIGNMENT
AND BELT TENSION;
[]
CHECK TO ENSURE THAT ELECTRICAL
LINES OR SHARP METAL EDGES.
REFER
TO INSTALLATION
rm
INSTRUCTIONS
Z
WIRING
IS NOT IN CONTACT
o,
WITH REFRIGERANT
<
I(p
III. START-UP:
ELECTRICAL
SUPPLY
VOLTAGE
COMPRESSOR
AMPS
INDOOR-FAN
AMPS
LI-L2
L2-L3
L3-LI
LI
L2
L3
LI
L2
L3
TEMPERATURES
OUTDOOR-AIR
DB
TEMPERATURE
LU
2:
m
RETURN-AIR
TEMPERATURE
DB
WB
DB
WB
rm
LU
COOLING
SUPPLY
AIR
Ic_
Z
o,
REFRIGERANT
REFRIGERANT
SUCTION
PSIG
F
REFRIGERANT
DISCHARGE
PSIG
F
[]
VERIFY
REFRIGERANT
CHARGE
USING COOLING
[]
VERIFY 3-PHASE SCROLL COMPRESSOR
(50TFKTM007
SCROLL ONLY)
<
I(p
CHARGING
IS ROTATING
CHARTS
IN THE CORRECT
ON PAGES 53 AND 54
DIRECTION
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications
Book
1 [4
Tab
1b 16b
Catalog No, 04-53500010-01
Printed in U.S,A.
or designs without notice and without incurring obligations.
Form 50T-5SI
Pg CL-1
9-05
Replaces:
50T-3SI
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 61 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 12:47:00 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools