CARRIER Evaporator Coils Manual L0521268
AQUAFORCE 30XA080-500 L0521268
User Manual: CARRIER CARRIER Evaporator Coils Manual CARRIER Evaporator Coils Owner's Manual, CARRIER Evaporator Coils installation guides
Open the PDF directly: View PDF
.
Page Count: 44
| Download | |
| Open PDF In Browser | View PDF |
AQUAFORCE
TM
30XA080-500
Air-Cooled Liquid Chillers
Installation Instructions
CONTENTS
SAFETY
Page
SAFETY CONSIDERATIONS ......................
1
INTRODUCTION ..................................
1
INSTALLATION ................................
2-42
Storage ..........................................
2
Step 1 -- Inspect Shipment ......................
2
Step 2 -- Place, Mount and Rig Unit .............
2
• PLACING UNIT
• MOUNTING UNIT
• RIGGING UNIT
Step 3 -- Cooler Fluid and Drain Piping
Connections ..................................
29
• GENERAL
• DUAL CHILLER CONTROL
• COOLER FLUID, VENT. AND DRAIN
• COOLER PUMP CONTROL
• BRINE UNITS
• WATER TREATMENT
• PREPARATION FOR YEAR-ROUND OPERATION
• PREPARATION FOR WINTER SHUTDOWN
Step 4 -- Make Electrical Connections ..........
34
• POWER SUPPLY
• FIELD POWER CONNECTIONS
• FIELD CONTROL POWER CONNECTIONS
• CARRIER COMFORT NETWORK
COMMUNICATION BUS WIRING
• NON-CCN COMMUNICATION WIRING
• FIELD CONTROL OPTION WIRING
• DUAL CHILLER LEAVING WATER SENSOR
Step 5 -- Install Accessories ....................
41
• ENERGY MANAGEMENT MODULE
• REMOTE ENHANCED DISPLAY
• LOW AMBIENT TEMPERATURE OPERATION
• MINIMUM LOAD ACCESSORY
• UNITSECURITY/PROTECTION
ACCESSORIES
• COMMUNICATION ACCESSORIES
• SERVICE OPTIONS
• CONTROL TRANSFORMER
Step 6 -- Leak Test Unit .........................
41
Step 7 -- Refrigerant Charging ..................
41
• DEHYDRATION
• REFRIGERANT CHARGE
Manufacturer
Installing, starting up, and servicing this equipment can be
haz_u'dousdue to system pressures, electric_d components, and
equipment location. Only trained, qu_difiedinst_dlers and service
mechanics should inst_dl,stall up, and service this equipment.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky equipment.
Electfic_d shock can cause persomd injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Ntg all disconnect locations to _dert others not to restore power until work
is completed.
IMPORTANT:
This equipment generates, uses, and
can radiate radio frequency energy and if not installed
and used in accordance with these instructions may
cause radio interference. It has been tested and found
to comply with the limits of a Class A computing
device as defined by FCC (Federal Communications
Commission, U.S.A.) regulations, Subpart J of Part 15,
which are designed to provide reasonable protection
against such interference when operated in a commercial environment.
INTRODUCTION
These instructions cover installation of 30XA080-500
aircooled liquid chillers with electronic controls and units with
factory-installed options (FIOPs). See Fig. 1.
reserves the right to discontinue, or change at any time, specifications
PC 903
Catalog No. 533-00068
Printed in U.S.A.
CONSIDERATIONS
or designs without notice and without incurring obligations.
Form 30XA-1SI
Pg 1
6-05
Replaces:
New
INSTALLATION
Storage
-- If the unit is to be stored for a period of time before installation or start-up, be sure to protect file machine
from construction
dirt. Keep protective shipping covers in
place until file machine is ready for installation.
Step 1 -- Inspect Shipment -- Inspect unit
for &image upon arrival. If &image is found, immediately file a claim
with the shipping company.
Step
2 --
Place,
Mount,
and Rig the Unit --
When considering a location for the unit, be sure to consult
NEC (National Electrical Code, U.S.A.) and/or local code
requirements. Allow sufficient space for airtlow, wiring, piping, and service. See Fig. 2-10.
NOTE: To facilitate refrigerant vent piping, all units have fusible plugs with 1/4 in. SAE (Society of Automotive Engineers)
flares and pressure reliefs with 3/4 in. NPT fittings (if required
by locfd codes).
PLACING UNIT--Ix_cate
the unit so that the condenser
airtlow is unrestricted both above fred on the sides of the unit.
Airflow find service clefuances me 6 fl (1.8 m) around file unit.
Acceptable clearance on the cooler connection side or sides or
ends without control boxes can be reduced to 3 ft (1 m) without
sacrificing
performance
as long as the remaining
three
sides me
unrestricted.
Acceptable
clearance
on the side wifll a control box
cfm be reduced
to 4 fl (1.3 m) due to NEC regulations,
without
sacrificing
performance
as long as the remaining
three sides am
unrestricted.
Provide ample room for servicing find removing
file
cooler
See Fig. 2-10 for lequimd
clemances.
Ix)cffl codes for
clem'ances
take precedence
over the manufacturer's
mcommenc_kLtions when locfd codes cfdl for greater clearances.
If multiple
units am installed
10 fl (3 m) between
the sides
maintain
proper airflow
er air recimulation.
at the stone site, a separation
of the machines
is required
and minimize
the chances
of
to
of condens-
MOUNTING
UNIT -- The unit may be mounted
on a level
pad directly
on the base rails, on a raised mounting
rail m'ound
the unit, or on vibration
isolation
springs.
For all units, ensure
placement
area is strong enough
to suppori
unit operating
weight. See Tables IA and lB. Mounting
holes are provided
for securing
the unit to the pad, mounting
rail or vibration
isolation
springs. Bolt the unit securely
to pad or rails. [f vibration isolatol.'s
(field-supplied)
are required
for a particular
instffllation,
refer to unit weight distribution
in Fig. 11 to aid in
the proper
selection
of isolators.
The 30XA
units can be
mounted
directly
on spring
isolators.
30XA
T
30XA - Air-Cooled
AquaForce
TM
Chiller
A
200
/
Packaging/Security Options
L - Coil Face Shipping Protection (CFSP)
- CFSP, Skid
- Skid, Top Crate, Bag
- CFSP, Coil Tdm Panels
- CFSP, Skid, Coil Trim Panels, Shipping
Skid, Top Crate, Bag, Coil Trim Panels
,1
Design Series
Unit
080
090
f00
110
120
Sizes
140 240
160 260
180 280
200 300
220 325
350
400
450
500
Controls/Communication
Options
- - None
0 - EMM
I - Remote Service Ports, GFI-CO
2 - EMM. Remote Service Port, GFI-CO
7 - BACnet
Tianslator
8 - BACnet Translator. EMM
9 - BACnet Translator, Remote Service Port, GFI-CO
B - BACnet Translator. EMM, Remote Service Port, GFI-CO
H - LON Tlanslator
J - LON Translator. EMM
K - LON Tianslator, Remote Sewice Port, GFI-CO
L LON Translator, EMM, Remote Service Port, GFI-CO
Voltage
1 - 575-3-60
2 - 380-3-60
4 - 230-3-60
6 - 460-3-60
7
200-3-60
TM
Condenser Coil/High Ambient Options
6 Aluminum Fin/Copper Tube, High Ambient Temperature,
Compressor Enclosures
8 Aluminum Pie-Coat Fin/Coppel Tube, High Ambient Tempelatule,
Compressor Enclosures
9 Alumint.lm E-Coat Fin/Coppel Tube, High Ambient Temperature,
Compressor Enclosures
F Aluminum Fin/Copper Tube, Standard Ambient Temperature,
Compressor Enclosures
H Aluminum Pie-Coat Fin/Coppel Tube, Standard Ambient
Temperature, Compressor Enclosures
J - Aluminum E-Coated Fin/Copper Tube, Standard Ambient
Temperature, Compressor Enclosures
Electrical Options
- - Single Point Power, XL Terminal Block, No Control Transformer
o - Single Point Power, Wye-Delta, Telminal Block, No Contlol Transformel
3 - Dual Point Power, XL Terminal Block, No Contlol Transformel
4 - Dual Point Poweh Wye-Delta, Terminal Block, No Conhol Tlansformel
7 - Single Point Power, XL Disconnect, No Control Transformer
8 - Single Point Power, Wye-Delta. Disconnect, No Control Tlansformer
C - Dual Point Powel, XL Disconnect, No Contlol Transformer
D - Dual Point Power, Wye-Delta, Disconnect No Contlol Transformel
R - Single Point Power, XL Telminal Block, Control Transformer
J - Single Point Power, Wye-Delta, Telmina] Block, Control Tlansformer
M - Dual Point Power, XL Terminal Block, Control Transformer
R - Dual Point Poweh Wye-Delta, Terminal Block, Contlol Transformer
B - Single Point Power, XL Disconnect, Contlol Transformer
S - Single Point Power, Wye-Delta. Disconnect, Control Tlansformel
W- Dual Point Powel, XL Disconnect, Control Transformer
Not Used
Cooler/Brine
O- Integral
3 - Integral
5 Integral
B - Integral
F - Integral
H - Integral
Options
Coolel
Coolel, Minus One Pass
Coolel, Plus One Pass
Cooler, Brine
Cooler, Minus One Pass, Brine
Cooler. Plus One Pass. Brine
X
-----
Energy Management Module
Ground Fault Interrupting Convenience
Local Operating Network
Across-the-Line Starter
Outlet
Fig. 1 -- AquaForce
Control Transformer
Refrigeration Circuit Options
- - None
I - Suction Service Valves
2 - Low Ambient Temperature Head Pressure Contlol
5
Suction Service Valves, Low Ambient Tempelatule
LEGEND
EMM
GFI-CO
LON
XL
Dual Point Power, Wye-Delta, Disconnect
TM
Chiller Model Number Designation
Head Pressure Control
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each cooler head at each
end of cooler.
4. Drawing depicts unit with single-point power and standard twopass cooler. Refer to the Packaged Chiller Builder program for
other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in
millimeters.
1.50
DIA.
RIGGING
HOLE
Control
Box All Voltages_
3.35
/_(_._'8k_koLts]
fhOor
lemaipnPiOg_r entry
1.75
DETAIL "A"
[4il
MOUNTING PLATE
0.875
CONTACT SURFACE
TYPICAL 4 PLACES
DIA.[22.2]
MOUNTING
HOLE
\
_
I
I
I
1;1
oR
- Cooler Tube
__
.... L...........
,,_
4_
5.0
MOUNT'NG
PLATE__
_--
"_1
--
I!1
t
[127]
/
--
I-...............................
_
I
109.0.
II
II
88.04
[2236]
/
5.83
I
_
II
L ....................................
3.93
[1oo]
!
[141
'_
_
[1670]
.....
//J
I
7.88
[200]
Piping Entrance
TOP VIEW
Fig. 2 -- 30XA080 Air-Cooled
Liquid Chiller Dimensions
Optional
Non-fused
Control Box
All Voltages_
90.55
[2300]
DisplayLocation
(380,460_575v)
90.55
5" Victaulic
5" Victaulic
41.1
[_[1044
©
t-
Leaving
Entering
Water_
Water
_
I
[2OO]
19.06
[1729]
68.06
88.04
[2236]
88.04
[2236]
RIGHT END VIEW
LEFT END VIEW
8.9
[226]
Control
Box All Voltages
90.55
3/8 NPT
[
I
Cooler
Drain
_____
3/8 NPT
H
--!_
[2714]
19.06
[484t
[2i001
1
109.03
Mounting Holes_
Rigging Holes
(See Detail A)
121.17
[3078]
[409]
[2769]
141.22
5" Victaulic
g Water
[3587]
Entering
[85]
Water
FRONT VIEW
3/4 NPT Relief
Conn. Female
Fig. 2 -- 30XA080 Air-Cooled Liquid Chiller Dimensions (cont)
1.50 DIA. [38.1]_
RIGGING HOLE
Control
Box All Voltages_
\
\
1.75
DETAIL
MOUNTING
"A"
PLATE
\
3.35
7/8"
\
T
I
for main
power
entry
I
23.72
/_
0.875 DIA.[22.2] _
MOUNTING
HOLE
knockouts
CONTACT
SURFACE
TYPICAL 4 PLACES
(7,48" [190mm]
hole spacing)
[6_21
A
1.31
68.06
[331
I
I
1
Cooler
-Service
[- ......
MLOA_NTING ___
\
_
5.0
[127I
.........
--
3.93
[100]
--
_
1
I
Area
[1729]
,
Tube
88.04
[2236]
_.J
._-/ ..........................
................
iiii
.....•
///,
B
[2769]
120.85
[3070]
7.88
188.2
[200]
[4780]
_Piping
TOP VIEW
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection.
3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler.
4. Drawing depicts unit with single-point power and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
Fig. 3 -- 30XA090-120 Air-Cooled
30XA090UNIT
100
110
120
Liquid Chiller Dimensions
44.11Al120)(
44.11 (1120)
44.11 (1120)
44.11 (1120)
86,83
87.22
87.62
87.12
B(2208)
(2215)
(2226)
(2213)
Entrance
0 ptional
Non-fused
Disconnect
Handle
5" Victaulic
Leaving Water
Control
Box
All Voltages
90.55
Displa_
Location
{380,480,575v)
5" Victaulic
[2300]
99.55
©
19.05
[17291
L
88.04
[2236]
88.04
[2236]
RIGHT
LEFT END VIEW
END VIEW
Female
8.9
[226]
--4
Control
Box All Voltages
90.55
3/8 NPT
3/8 NPT
]
19.06 [2i00]
[4841
Mounting
Rigging Holes
(See Detail A)
[1982]
[3070]
188.2
[4780]
FRONT VIEW
Fig. 3 -- 30XA090-120
Air-Cooled Liquid Chiller Dimensions (cont)
5" Victaulic
Leaving Water
5" Victaulic
Entering Water
NOTES:
1. Unit must have clearances as fellows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on liquid line
and economizer assemblies and have t/4-in, flare
connection.
3. 8/8-in. NPT vents and drains located in each cooler
head at each end of cooler.
4. Drawing depicts unit with single-point
power, or
dual-point power on a 30XA160 (200, 230 v) unit
with standard condenser fans, and standard twopass cooler. Refer to the Packaged Chiller Builder
program for other configurations.
5. Dimensions are shown in inches; dimensions in
brackets are in millimeters.
7.23 [182]
/
Control Box, incoming
power supply
(380,460,575v)
/
Control Box, incoming
power supply
(200,280v)
/
__/
1
40
/i
_"
[1017]
it .................
/
i
J
F ...........
i/
"--'1
"
161 8 04
Cooler Tube
Service
Area
2.48 [63] J
(Zyp,cal)
\
I- .............
_
_ircuit
_
[2286]
1
_
O_rou_t
2
(30XA_
60
on
_y)
--'_-- ..............
i
i ...............................
30XA140UNIT
160
44.63A1(134)
44.61 (1133)
5.84 [148]--
115.88 B(2943)
115.64(2937)
--
[2769]
121.49
[3086]
235.24
[5975]
_Piping
Entrance
TOP VIEW
co
Control Box
(all voltages)
7/8" knockouts for main
for 380.460.575v
4
spacing)
f'fi\
5" Victaulic
Leaving Water.
/'fi-\
/
/ "Kl'_
/
/'r<\
90.55
90.55
[2800]
[2300]
/-
Entering Water
21.28
10.58
, [269]
23.62
5" Victaulic
i
j
o
i
69.14
[1756]
i-o_l _
88.04
[2236]
RIGHT
on,y
,J
Display
Disconnect
--Non-fused
"
[600]
[541]
i
J
_"
o
o
111.58
[2834]
Box
(200/230V)
235.24
[5975]
74
Location
BACK VIEW
Fig. 4 -- 30XA140,160 Air-Cooled
-'_
¢
J
END VIEW
Handle
Liquid Chiller Dimensions
[188o]
7 3/4NPT
Relief
Conn.
Female
8,9
[226]
$5"
Victaulic
/-5"
Leaving
Victaulic
Water
Entering
Water
Control Box
incoming power"-.
supply (200,230v)
(200,230v)
90.55
7/8"knockoutsfor
90.55
[2300]
(5,55" [141 mm]
hole spacing)
3/8 NPT
41,1
[--[1C
22,2
[565]
O
[2i00t
3/8 NPT
1
Control Box
(200,230,380,
460,575v)
109.03
[2769]
Mounting
88.04
[2236]
Rigging Holes
(See Detail A)
[3,23] LEFT END VIEW
33.96
[863]
121.49
[3086]
235.24
[5975]
FRONTVIEW
7,2
[182]
1.50 DIA.[38.1]_
RIGGING HOLE
1.75
4i]
DETAIL
MOUNTING
CONTACT
0.875 DIA.[22.2]
MOUNTING
HOLE
\
\
l
I
I
TYPICAL
"A"
PLATE
SURFACE
4 PLACES
1,31
[33]
!
1
5.0
[127]
--
3,93
[100]
7,88
[200]
Fig. 4 -- 30XA140,160
Air-Cooled Liquid Chiller Dimensions (cont)
58.08
[1475]
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts
unit with single-point
power,
or
dual-point
power
on
a
30XA180,200 (200, 230 v) unit with standard condenser fans, and standard twopass cooler. Refer to the Packaged Chiller
Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
S
power supply
(200,230v)
7.23
[1821
Control
_83
I
4O
[10171
I
2.48 [63] I1
(Typical)
\
_
[72]
/
/
!....................
Y
T_
575v)
Box, incoming
/
°
J
Circuit 1
Circuit 2 (30XA160
only)
I
.r
[2236]
[_°8126[88.04
777777
I
i
Control Box, incoming
power supply (380,460
61.6
..............
[1666] --
30XA UNIT
A
B
180
200
46.12 (1171)
46.15 (1172)
143.04(3633)
142.97 (3631)
[2779]
B
177.65
[4512]
_
282.22
[71681
Piping
Entrance
TOP VIEW
7 Control Box
(all voltages)
7/8" knockouts for main power entry 380, 460, 575v
(5.55" [141 ram[ hole spacing)
\
\
I_TT]
IIII II_111
II
/"4"\
-Control
power entry
(all voltages)
/
Display
Location
/
/ "K \_
4"fi-\
/ /"K \
/
! "K \
90.55
6" Victaulic
Leaving Water--
[2300[
6" Victaulic
Entering Water-
I
......
23.62
22148.
, [12183
[5_1I
r_
1
70.16
[6iO]
__
Control Box
[1782[
88.04
[22361
RIGHT
END VIEW
OptionalNon-fused
DisconnectHandle
158.6
[4028[
(380,460,575v)
282.2
[7168]
12.7
[323[
BACK VIEW
Fig. 5 -- 30XA180,200 Air-Cooled Liquid Chiller Dimensions
Control
Box
(200,230v incoming
] power supply connection)
122
[3099[
g Water
Cooler Vent3/8 NPT
--
3/4 NPT Relief
Conn. Female
g Water
Optional Non-fused
Disconnect Handle
Control Box,
incoming Power
Supply (200,
230v)
Control Box
(200,230v)
7/8'.' knockouts for_
main power entry
90.55
(5.55" [141 mm]
hole spacing)
[2300]
\1
©
41.1
22171044i
[8_81
90.55
[2300]
I
'°_
/
J.___F
Mountin(
Rigging
(See Detail A)
Control Box _
(200,230,380,
460,575v)
12.7
[323]
[489]
/
58.08 __.
[1475]
i
177.65
i
33.97
78.0___
[863]
[1982]
[4512]
/
%
/\//
€,
28222
[7168]
LEFT END VIEW
FRONT VIEW
1,50 DIA.[3&I
RIGGING HOLE
1.75
[4 i]
DETAIL "A"
MOUNTING
CONTACT
0.875 DIA.[22.2]
_
I
MOUNT,
NGHO_
_
MOUNTING
PLATE__
I
____.__'___..................
TYPICAL
PLATE
SURFACE
4 PLACES
1.31
[33]
I
F
[127]
5.0
7.88
[2OO]
Fig. 5 -- 30XA180,200 Air-Cooled
Liquid Chiller Dimensions (cont)
/
[571]
78.02
[1982]
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have
1/4-in. flare connection.
3. 3/6-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with single-point power,
or dual-point
power on a 30XA200,240
(200, 230 v) unit and standard condenser
fans, and standard two-pass cooler. Refer to
the Packaged Chiller Builder program for other
configurations.
5. Dimensions are shown in inches; dimensions
in brackets are in millimeters.
_
/_Control
/p
Box, incoming
......
r-'_ .............
! r-.............
i
ii
/
Control Box, incoming
power supply (200,230,
380,460,575v)
pply (200,23_"
"-'f
i
@
70.16
[1762]
8_
....
[2; 36]
c°r%T2r
=
108.6
/////o/
[2758]
B
224.65 [5706]
30XA UNIT
A
B
220
240
46.17 (1173)
46.23 (1174)
171.42 (4354)
170.83 (4339)
_o_
o_ [8363]
Piping Entrance
TOP VIEW
7/8" knockouts for main power entry(5.55" [141 mm] hole spacing)
=Control Box
(200/230v only)
Display Location
Control Box460,575v)
9C!55
6" Victaulic
Leavinc
6" Victaulic
Enterin(
f--
22.46
[2}00]
[5
140.14[3560]
Box
Incoming power, 380,460.575v
[2236]
Circuit 11(200.230v)
329.26
205.6
[5222]
[8363]
170 [4318]
RIGHT END VIEW
BACK VIEW
Fig. 6 -- 30XA220,240 Air-Cooled Liquid Chiller Dimensions
3/4NPT
Relief
Conn.
Female
3/8NPT
90.55
[2300]
©
I
....
.....
6"Victaulic
Entering
Water
90.55
[2300]
Control_
i
Boxes ......
o i
i
U
[1475]
88,04
- 33,97 [863]-
[2236]-
224.65
(See Detail
gWater
,
109.03
[2769]
329.26
[8363]
33,96 [863]
[5706]
A)
LEFT END VIEW
FRONT VIEW
1,50 DIA. [38.1]_
RIGGING HOLE
\
\
1.75
DETAIL
MOUNTING
CONTACT
0.875 DIA.[22.2]
\
MOUNTING
HOLE
TYPICAL
_
"A"
PLATE
SURFACE
4 PLACES
I
1
5.0
MOU NT'N G PLATE _---__
-_
"_!_-iI
[
--1
[127]
_t /
--
3,93
[100]
7.88
[200]
Fig. 6 -- 30XA220,240 Air-Cooled Liquid Chiller Dimensions (cont)
--
58.08 [1475]--
NOTES:
1, Unit must have clearances as
follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid
surface,
2. Temperature
relief devices are
located on liquid line and economizer assemblies and have t/4-in.
flare connection.
3. 3/8-in. NPT vents and drains
located in each cooler head at
each end of cooler.
4. Drawing depicts unit with singlepoint power standard condenser
fans
and standard
two-pass
cooler. Refer to the Packaged
Chiller Builder program for other
configurations.
5. Dimensions are shown in inches;
dimensions
in brackets are in
millimeters.
iCc°o%i?,#
supp,y
wer
r
................
i
...................
J
i
........................
°
@
i
[2286]
ce°°'ie et r ee
J
_777771
////8
/
188.35 [4784]
B
304.71
[7740]
\
30XA UNIT
A
B
260
280
300
44,22 (1123)
44.30 (1125)
44.32 (1126)
216,16 (5490)
215.86 (5483)
216.18 (5491)
TOP VIEW
Piping
Entrance
Control
7/8" knockouts for main power
(5.55" [141 mini hole spacing)
8" Victaulic
Leaving Water
entry
Control
Power Entry
8" Victaulic
\
[2;
\
/
'\
i
/
/
Water\
28!o8
_
[6ool --
!
\X
r-_
_
_Optional
Non-fused
I
o o
L .....
Disconnect
Handle
/
199.7 [5072[
C_ontrol Box
---
71.06 [1805) -88.04
RIGHT
Incoming power
(all voltages)
245.52
[2236]
END VIEW
(all voltages)
\
90.55
[2300]
\
Entering
Box (all voltages)
BACK VIEW
Fig. 7 -- 30XA260-300 Air-Cooled Liquid Chiller Dimensions
[6236]
55
)O]
-3/4
NPT Relief Conn.
Female
Victaulic
Leaving
Water
Victaulic
Entering
Water
3/8 NPT
Control
/All
Box
Voltages
90.55
90.55
[2300]
[2300]
_,q
,
!
i
i
X
,'1
_,_
78,02
15.77 [401]
88.04 [2236]
Mounting,o, ses78°2 t888I
[1982]
--
304.71
31,96
J
o
[812£ -_-
78,02 [1982]
[7740]
_
_ [9555]
Rigging Holes
(See Detail A)
FRONT VIEW
LEFT END VIEW
L_
1,50 DIA. [38.1]_
RIGGING HOLE
_,
1.75
DETAIL
MOUNTING
CONTACT
0.875 DIA.[22.2]
TYPICAL
"A"
PLATE
SURFACE
4 PLACES
1,31
MOUNTING
MOUNTING
HOLE
_
[33]
!
PLATE_
_._
......
_____L...........
5.0
[127]
--1
--
3.93
I
[1OO]
7.88
[2OO]
Fig. 7 -- 30XA260-300 Air-Cooled
Liquid Chiller Dimensions (cont)
'8,02
[1982]-
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have t/4-in, flare connection.
3. 3/84n. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with single-point power,
and dual-point power (380 v), standard condenser fans and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
30XA
UNIT
A
325
350
42.92
42.92
Control
246.16
246.72
....
I
power
"
supply
@
A
l
__
...........................
--"_""
--'--
-- _C--e°
! i_c[e_" reL'-e_
............
I
-:...................
:::i:::
.....
:.............
348.02
)81
71 06
[1_
88.04
_
J
B
(1090)
(1090)
Box, incoming
r
[2i361
[8865]
(6252)
(6267)
423.24
[107501
_-Piping
Entrance
TOP VIEW
(_5.85'k'1}(_,_k°l_s f]°hrolmeaislpaPc°
nWge)r
e ntrY _.
f
_,
8" Victaulic
Leaving Wate[
------
/
tVer
23.63
_ [310t
[6oot
_
L
--
/
\
/
"_
"_
/
_0r Di°_plBa(yLocation
/
_-Control
/
(
power
\
entry
/
"_
_'C
t
_90.55
71.06
[1805,
88.04 [2236]
_
_
RIGHT END VIEW
Control
J
Box
Circuit
"
"
1 all vo_es,
(
g
d'_
} Circuit
t p t'_A!_
2 (380v
_
-_992'_3_41362187]
only)
423.24
[10750]
BACK VIEW
Fig. 8 -- 30XA325,350 Air-Cooled Liquid Chiller Dimensions
Cooler Vent3/8 NPT
-8 '_Victaulic
Leaving
8'_Victaulic
Control
Box
Cooler Drain
3/8 NPT
_-----
-_
I =
16._]_9_
40
109.03
[27691
.L
_83691 --L
58.0811475[
349.02
[8865]
i
423.24
[10750]
LEFT END VIEW
Entering
Water
90.55
[2300[
_5177
[40_
]804[2236]-
Water
_- Mounting Holes
Rigging Holes
(See Detail A)
FRONT VIEW
1 50 DIA
RIGGING
HOLE
1.75
I4i,
DETAIL
MOUNTING
CONTACT
TYPICAL
"A"
PLATE
SURFACE
4 PLACES
1
5.0
[127]
Fig. 8 -- 30XA325,350
Air-Cooled Liquid Chiller Dimensions (cont)
NOTES:
1, Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface,
2. Temperature relief devices are located on liquid line and economizer assemblies and have
t/4-in, flare connection.
3. 3/8-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with dual-point power
standard condenser fans and standard onepass cooler. Refer to the Packaged Chiller
Builder program for other configurations.
5. Actual cooler consists of two separate coolers
piped in series at the factory, Piping may be
split for rigging.
6. Dimensions are shown in inches; dimensions
in brackets are in millimeters.
Cooler
ontrol
Box #1
Control Box #2_
Piping
Tube
Entrance-
...........
q •
I
/
304 1_
[22361 [
7, 02
-
&_\%_
......
'
_-_-.;,_,_'
_5.a??.[f?s41
6091
240.69
470.22
119.0,7 [302,
[6114]
--
[11944]
TOP VIEW
7/8" Knockouts
(5.55" between
for Ckt 1 power_
holes)
\
\
Optional
_-
Control
Box #1_
_
Disconnect
Handles_
/
_
i-7/8"
/(5.55"
/
Non-fused
/
\
/
Control
/
\
/
Knockouts
between
l_Display
//
for Ckt 2 power
holes)
Box #2
Location
7
C°ntr°l
p°wer
entry
8" Victaulic
90,55
Entering
[2300]
_
©
F°
_6i0_ ,
i.._.
dControl
,
,/_
/r
/
---
72.1 [1831]--
Box
Circuit Jll
i
,
]
L
RIGHT END VIEW
BACK VIEW
Liquid Chiller
_
/,
, __
I_-_v_ _:05.7_96_4_
.
_
A ...........
88.04 [2236]-
Fig. 9 -- 30XA400 Air-Cooled
i
Dimensions
331.58
[8422]
151'5138481
Ci c_uit 2
Cooler
'/
located
Cooler
NPT Relief
8" Victaulic
Control
Boxes
Leaving
Conn.
Female_
Water-
_
Vent 3/8 NPT
incoolerheads
Drain
located
3/8 NPT
in cooler
heads
g Water
90.55
90.55
[2300]
[2i0O]
ii
i
[455],
b7714°,,
I
8"
I'-L--
70,02 [1779]
88.04 [2236]
Victaulic
Leaving
Water
-Mounting
Rigging Holes
(See Detail A)
LEFT END VIEW
FRONT VIEW
1.50 DIA. [38,1]_
RIGGING
HOLE
1.75
DETAIL
[4 i]
MOUNTING
PLATE
CONTACT
0.875 DIA.[22.2]
MOUNTING
HOLE
1
\
I
I
TYPICAL
"A"
SURFACE
4 PLACES
[33]
MOUNTING
PLATE
_X____._I
1.31
p o
[1271
[1001
7.88
[2OO]
Fig. 9 -- 30XA400 Air-Cooled Liquid Chiller Dimensions (cont)
NOTES:
1. Unit must have clearances as follows:
Top -- Do not restrict
Sides and Ends -- 6 ft from solid surface,
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have t/4-in, flare connection.
3. 3/sqn. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with dual-point power
standard condenser fans and standard
one-pass cooler. Refer to the Packaged
Chiller Builder program for other configurations,
5. Actual cooler consists of two separate
coolers piped in series at the factory. Piping may be split for rigging.
6. Dimensions are shown in inches; dimensions in brackets are in millimeters,
Control
Piping
Box #1 _,
Control
\
Box #2 _,
\
450
500
A
L
Piping
I.........
._
i ...........
Entrance
Area\
,_
\
._
\
A
'_
73.0
\
71.06
88.04[1854] 1
[18051
[2136]
....
; ........
I
89.62 [21241-•
B
I 44.78
44,71 (1137)
(1136)
Tuber
Service
Entrance
426.0
30XA UNIT I
Cooler
517.26
129.1
[32791
[10820]
[13138]
264.7 (6705)
(6723)
263.99
TOP VIEW
(_.8_'5,K_o_,_o_ts _OrleCs_t1 power_
$(_._'5,K_o_ouls
$
Non-fused
Disconnect
Handles
fO_eC_t 2 power
/
o
_
Control
Box #1_
/
_
/
/
/
_
/
$
//
//
Control
Display
/
Box #2
Location
Control
power
entry
8" Victaulic
90.55
Entering
Water_
[2300]
N
' 17.92
23.62
[455]
[6_]
L
73.0 [1854]
--
x
[2236]
_-_°netr°l
Circuit
'_..
•
'_7£_0 [a_t 71
-517.26
RIGHT END VIEW
/
I
28.81
[732]
UJ_
88.04
(
_
L90 O
Circ
--
I
[13138]
BACK VIEW
Fig. 10 -- 30XA450,500 Air-Cooled Liquid Chiller Dimensions
2
198.54
[5043]
162._ [38791
- Cooler Vent 3/8 NPT
located in cooler heads
NPT
located in cooler heads
Mountinc
Rigging Holes
(See Detail A)
8" Victaulic
Leaving
Water
Victaulic
Entering
Water
90.55
Control
Boxes
90.55
\
\
[2300]
[2i00l
ii
58.08
15.77
_
[401]
71 06 [1805]
88,04 [2236]
i
9" Victaulic
Leaving
109.03
[2769]
Water
83.62
h
33.96
[_
[863] _
_J_
33.97
[863]
[2124]
"
426.0
[10820]
517.26
LEFT END VIEW
I",3
58.08
[1475]
[13138]
FRONT VIEW
1.50 DIA.
RIGGING
HOLE
1.75
DETAIL
MOUNTING
CONTACT
0.875 DIA.[22.2]
_
MOUNTING
HOLE
\
l
_
I
I
TYPICAL
"A"
PLATE
SURFACE
4 PLACES
1,331,
5.0
[127]
I
[1 O0]
--1
_
3.93
7.88
[200]
Fig. 10 -- 30XA450,500 Air-Cooled
Liquid Chiller Dimensions (cont)
78,02
[1982]
78.02
[1982]
Unit Weights -- Standard Units
Unit Weights -- English
MOUNTING
30XA
UNIT SIZE
WEIGHT
_
otal
7674
WEIGHT (Ib)
080
30XA
UNIT SIZE
(Ib)
MOUNTING
A I B I c I D I E I F ITota'
I 2188 I 822 I 1023 I 2127 I 1271 I 8704
1299I 2244 I 863 I 1064I 2184 I 1297I 8931
1312
2284 I 872 I 1079I 2222 I 1303 I 9071
090
100
110
120
1273
1346
30XA
UNIT SIZE
2322
874
1082
2255
1337
MOUNTING WEIGHT (Ib)
A i B i c i o i E i F i G i H ITota,
140
160
2007
2061
30XA
UNIT SIZE
1554
1581
I
938
953
I
1254
1281
I
1998
2020
I
_I_IcloIEIFIGIHI
180
2OO
979
984
1558
1574
I
1239
1263
I
1291 I 957 I 1695
1321
974
1715
MOUNTING WEIGHT (Ib)
I
1809
1862
I
1298 I 2016 I 916
1308
2029
923
MOUNTING WEIGHT (Ib)
1261
1267
30XA
UNIT
9216
111506
11748
I
'
I J
1363
1375
I
962
968
ITota'
113690
13712
SIZE
Total
220
240
260
280
300
14,727
14,887
16,853
17,022
17,362
MOUNTING
30XA
WEIGHT
325
35O
856
860
866
860
I 1054
1059
I 1607
1623
I
859
869
I 2697
2752
I
1143
1153
30XA
UNIT SIZE
A
B
C
D
E
F
G
40O
450
5O0
924
933
921
1311
1256
1314
1588
2276
2325
3119
2398
2452
1332
982
987
866
1134
1139
2368
2184
2194
NOTE: Condenser
Coil; Aluminum
Fins/Copper
I 1639 I 2485 I 880 I 1722
1666
2539
885
1727
MOUNTING WEIGHT (Ib)
H
I
J
K
1148
2207
2217
1643
2866
2875
30XA
UNIT SIZE
MOUNTING
_
O8O
30XA
UNIT SIZE
A
B
090
100
110
120
578
589
595
611
992
1018
1036
1053
30XA
UNIT SIZE
WEIGHTS
824
1629
1633
I
856
860
I
856
860
118,834
19,040
L
M
N
O
P
Total
1342
1343
1348
2306
1556
1575
1069
1501
1519
1354
1293
1357
945
953
941
24578
26600
26894
428
432
P
427
11 149
12
066
Total
12 199
-- SI
(kg)
otal
3481
MOUNTING WEIGHT (kg)
C
D
E
373
387
396
397
2440
2089
2098
I 1322
1326
Tubing.
Unit Weights
464
478
489
491
F
Total
576
588
591
607
3948
4061
4116
4181
965
991
1008
1023
MOUNTING
WEIGHT
(kg)
A i _ i c i o i E i F i G i H iTot°,
140
160
910
935
30XA
UNIT SIZE
705
717
I
425
432
I
569
581
I
686 I 434 I 769 I
599
442
778
MOUNTING WEIGHT (kg)
821
846
16219
5329
_I_IcloIEIFIGIHI
180
2OO
444
446
707
714
I
562
573
I
906
916
I
572
575
30XA
UNIT SIZE
A
B
C
D
E
220
24O
260
28O
30O
401
408
257
258
262
574
584
713
723
734
770
782
772
787
799
727
738
378
382
391
407
409
1182
1197
1234
' IJI
I
589 I 915 I 415 I
593
920
419
MOUNTING WEIGHT (kg)
F
G
H
583
585
492
493
501
603
604
725
726
741
416
418
1144
1149
1182
MOUNTING
30XA
UNIT SIZE
618
624
I
436
439
Total
I 6164
6220
I
J
K
L
Total
666
670
395
397
402
530
535
637
648
655
693
604
693
703
712
409
417
257
258
262
6680
6753
7644
7721
7876
WEIGHT
(kg)
A I B I c I o I E I F I G I H I ' I J I K I ' I M I N ITota'
325
35O
388
390
388
390
419
423
A
418
595
570
B
596
I
478
480
I
729
736
I
390
394
112241
1248
604
446
E
448
393
514
F
516
618
523
30XA
UNIT SIZE
40O
45O
5OO
(Ib)
_ I _ I c I _ I E I F I G I H I ' I J I K I ' I M I N ITota'
UNIT SIZE
I
NOTE: Condenser
Coil: Aluminum
720
1032
C
1055
1415
1088
D
1112
Fins/Copper
1074
991
G
995
I
744 111271
399 I
756
1152
401
MOUNTING WEIGHT (kg)
521
1001
H
1005
745
1300
I
1304
1107
948
J
952
781
784
374
739
K
741
Tubing.
Fig. 11 -- Unit Mounting Weights
22
I
600
601
609
609
L
611
I
388
390
1046
706
M
714
I
388
390
18648
8636
485
681
N
689
614
586
O
616
30XA080
30XA220-300
EDC
Compressors
B
Compressors
G
H
I
F
B
E
I
G
B
Compressors
J
G
C
B
J
K
L
M
F
E
D
C
B
N
0
Compressors
30XA180-200
D
C
30XA400-450
30XA140-160
E
D
Compressors
Compressors
F
K
30XA325-350
30XA090-120
c
J
B
Compressors
I
Fig. 11 -- Unit Mounting Weights (cont)
23
K
L
M
P
Table 1AUNIT 30XA
OPERATING WEIGHT (Ib)
AI-Cu Condenser Coils
REFRIGERANT
TYPE
Refrigerant Charge (Ib) Ckt A/Ckt B/Ckt C
COMPRESSORS
Quantity
Speed (rpm)
(Qty) Compressor
Nominal Capacity
(Qty) Compressor
Nominal Capacity
(Oty) Compressor
Nominal Capacity
Oil Charge (gal), Ckt A/Ckt B/Ckt C
Minimum Capacity Step (%)
Standard
Optional
(tons) Ckt A
(tons) Ckt B
(tons) Ckt C
Ambientt
DIMENSIONS
100
110
120
140
160
180
200
220
8,931
9,071
9,216
11,505
11,748
13,590
13,712
14,727
2
I
(1)45" I
1140 rpm
2
I
I
2
135002
(1)60
5.5/5.5/--
5.5/5.5/--
5.5/5.5/--
5.5/5.5/-(1)
1560
N/A
10
I
I
2
I
2
(1)90
(1)100
(1)90
N/A
6.25/5.5/--
N/A
6.25/5.5/--
N/A
6.25/6.25/--
I
I
I
I
2
(1)120
N/A
6.25/6.25/--
I
(1)15
100
1O
I
(1)14
100
10
16.5
I
16.5
18.5
20.0
31.5
34.0
37.0
220
300
I
220
300
220
300
220
300
220
300
I
220
300
220
300
220
300
220
300
220
300
3/s
3/8
3/s
3/s
3/s
I
3/s
3/8
3/s
3/s
3/s
2
5
1
5
4
3
2
5
1
5
4
3
2
5
1
5
4
3
2
5
1
5
4
3
2
5
1
45
3
2
5
1
5
3
2
5
1
5
3
2
6
1
6
3
2
8
1
6
3
2
6
1
6
3
850/1140
850/1 140
650/1 140
6/6/-111,600
9...30
148,800
6/6/-111,600
9...30
148,800
7/6/-120,900
9...30
161,200
650/--
850/--
650/--
I
4/4/-74,400
9...30
4/4/-74,400
9...30
4/4/-74,400
9...30
3/3/--
4148/_
I
4_48/_
I
Shell and Tube Type
I
25.5
27.5
I
Shrouded Axial Type, Vertical
650/-I 650/1 140
4/4/-74,400
9...30
I
4_
(1)15
10e0
N/A
6.75/6.25/--
(1)
1450
N/A
8
I
(1)11
860
2
(1) 100
(1)
1550
N/A
9
Flooded,
23.0
(1)11
750
I
6/4/-93,000
9...30
124,000
I
I
4_
Discharge
850/1 140
6/4/-93,000
9...30
124,000
I
6/43/_-
6/43/_-
I 281I
6/6/--
6_6_-
I 3O5
7/6/--
(ft-ln.)
UNIT 30XA
REFRIGERANT
TYPE
Refrigerant Charge (Ib) Ckt A/Ckt B/Ckt C
COMPRESSORS
Quantity
Speed (rpm)
(Qty) Compressor
Nominal Capacity
(Qty) Compressor
Nominal Capacity
(Oty) Compressor
Nominal Capacity
OII Charge (gal), Ckt A/Ckt B/Ckt C
Minimum Capacity Step (%)
Standard
Optional
15-9
I
7=425/3_
7-67/_6
Ckt A
Ckt B
Ckt C
I
23-7
240
260
280
300
325
350
400
16,853
17,022
17,362
18,834
19,040
24,578
27_270/--
_ 375/22_--
I 375/27_--
R-134a, EXV Controlled System
I 415/270/-I 375_7_-I 415/37_--
(1) 120
(1) 120
N/A
I
2
I
(1) 165
(1) 100
N/A
6.75/6.75/--
7.5/6.75/--
15
10
I
I
2
(1) 165
(1) 120
N/A
7.5/6.75/--
I
I
2
I
(1) 185
(1) 120
N/A
I
7.5/6.75/--
10
8
13
9
12
7
2
3500
(1) 165
(1) 165
N/A
7.5/7.5/--
Flooded,
I 27_27_375
I
27-6
450
500
26,600
I 41_205_15
26,894
I 41_270/415
Twin Rotary Screws
I
2
I
(1) 185
(1) 165
N/A
3
3
(1) 120
(1) 120
(1)165
7.5/7.5/--
15
10
(1)90
(1) 185
(1) 185
7.5/6.25/7.5
6.75/6.75/7.5
14
10
ShellandTubeType
50.5
53.4
3
(1) 120
(1) 185
(1) 185
7.5/6.75/7.5
6
4
7
5
39.0
I
42.0
44.0
48.5
68.0
75.0
83.0
220
300
I
220
300
220
300
220
300
220
300
220
300
220
150
220
150
220
150
3&
I
3/s
3/s
3/s
3/s
3/s
3/s
2
6
1
6
3
2
8
1
8
3
2
8
1
8
3
2
6
1
6
3
2
6
1
6
3
1
----8
--
%
6
1
¾
8
1
850/1140
911130
6/6/8
204,600
272,800
650/1140
9...30
8/6/8
204,600
272,800
2
8
1
6
3
I
Shrouded
Amblentt
19-8
14,887
2
(tons)
(tons)
(tons)
WATER CONNECTIONS
Drain (NPT, In.)
Standard,
Inlet and Outlet, Vlctaullc (in.)
Number of passes
Minus 1 Pass, Inlet and Outlet, Vlctaullc
(in.)
Number of passes
Plus 1 Pass, Inlet and Outlet, Vlctaullc
(in.)
Number of Passes
CONDENSER
FANS
Fan Speed (rpm) Standard/High
No. Blades...Dlameter
(in.)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (cfm) 850 rpm
Total Airflow (cfm) 1140 rpm
I
Semi-Hermetic
COOLER
Net Fluid Volume (gal.)
Maximum Refrigerant Pressure (pslg)
Maximum Fluid Side Pressure (pslg)
850/1140
9...30
7/6/-120,900
161,200
CONDENSER
COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq ft)
9...30
9/6/-139,500
I 850/1140
186,000
9...30
10/6/-148,600
850/1140
198,400
Axial Type, Vertical
9...30
10/6/-148,600
850/1140
196,400
9...30
9/9/-167,400
850/1140
223,200
Discharge
9...30
9/9/-186,000
850/1140
223,200
9...30
6/6/8
186,000
650/1140
248,000
i 9/6/1352375
i 10/6/i 10/6/375i 9/9/422i 9/9/4226/6/8469
I 6/6/6516
I 6/6/8516
(ft-ln.)
27-6
I
31-5
LEGEND
Cu -AI
-EXV-N/A --
2
(1)60
(1)
1545
N/A
9
11-10
DIMENSIONS
2
(1)50
141I
R/Ckt C)
I
(1)45
I
3/3/-55,800
9...30
.....
OPERATING WEIGHT (Ib)
AI/Cu Condenser Coils
CHASSIS
Length
Width
Height
System
(1)N/A
1545*
9
650/--
Tota,
FaceArea(sg.)
No. Coils (Ckt A/Ckt
090
8,704
5.5/5.5/--
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (cfm) 850 rpm
CHASSIS
Length
Width
Height
080
7,674
R-134a, EXV Controlled
WATER CONNECTIONS
Drain (NPT, In.)
Standard,
Inlet and Outlet, Vlctaullc (in.)
Number of passes
Minus 1 Pass, Inlet and Outlet, Victaullc (in.)
Number of passes
Plus 1 Pass, Inlet and Outlet, Victaullc (in.)
Number of Passes
Total Airflow !cfm!
CONDENSER
COILS
English
66/66/-I 97/97/-11°6/1°6/-I135/1°6/-I135/135/-12°22115/-I
225/135/I 205/205/-I 225/225/I 270/225/Semi-Hermetic
Twin Rotary Screws
COOLER
Net Fluid Volume (gal.)
Maximum Refrigerant Pressure (pslg)
Maximum Fluid Side Pressure (psig)
CONDENSER
FANS
Fan Speed (rpm) Standard/High
No. Blades...Diameter
(in.)
Physical Data, 30XA080-500-
Copper
Aluminum
Electronic Expansion
Not Applicable
Valve
*30XA080 unit does not have an economizer.
tThe high ambient temperature option is not available
on 30XA080-120
units.
24
I
35-4
743/4
7=67/16
I
39-3
I
43-2
Table 1B -- 30XA080-500 -- SI
UNIT 3OXA
OPERATING WEIGHT (kg)
AI-Cu Condenser Coils
REFRIGERANT
TYPE
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C
COMPRESSORS
QuanUty
Speed (r/s)
(Qty) Compressor
(Qty) Compressor
(Oty) Compressor
Oil Charge (liters),
Minimum Capacity
Standard
OpUonal
080
090
100
110
120
140
160
160
200
220
3 481
3 948
4 051
4 115
4 181
5 219
5 329
6 164
6 220
6 660
39/39/- I
44/44/-
R-1 64a, EXV Controlled System
149/44/-1102/10"2/-191.6/62.2/-1102/61.2/-
149/49/-
SembHermetic
2
Nominal Capacity (tons)
Nominal Capacity (tons)
Nominal Capacity (tons)
Ckt A/Ckt B/Ckt C
Step (%)
Ckt A
Ckt B
Ckt C
(1) 45"
(1)45"
N/A
20.6/20.8/--
I
I
2
(1)45
I
(1)45
N/A
20.8/20.6/--
9
15
I
2
(1)50
I
(1)50
N/A
20.6/20.6/--
v
15
I
2
(1)60
I
(1)50
N/A
20.6/20.8/--
v
15
6
14
CHASSIS
Length
Width
Height
DIMENSIONS
1102/102-1122.5/102/--
5_.3v
I
2
(1)90
I
(1)50
N/A
23.7/20.8/--
10
15
2
(1) 100
I
(1)60
N/A
23.7/23.7/--
I
I
7
11
2
(1)90
I
(1)90
N/A
23.7/23.7/--
8
11
I
2
(1) 100
I
(1)100
N/A
23.7/23.7/--
10
15
2
(1) 120
I
(1)100
N/A
26.6/23.7/--
10
15
10
14
Flooded, Shell and Tube Type
140.1
1516.8
2 068
WATER CONNECTIONS
Drain (NPT, In.)
Standard, Inlet and Outlet, Victaullc (in.)
Number of passes
Minus 1 Pass, Inlet and Outlet, Victaullc (in.)
Number of passes
Plus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
CONDENSER
FANS
Fan Speed (r/s) Standard/High
No. Blades._Diameter
(ram)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (L/s) 14.2 r/s
Total Airflow IL/s! 19.0 r/s
CONDENSER
COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sg m)
2
(1)60
I
(1)60
N/A
20.8/20.6/--
COOLER
Net Fluid Volume (liters)
Maximum Refrigerant Pressure (kPa)
Maximum Fluid Side Pressure (kPa)
193/93/-
Twin Rotary Screws
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
6
2
6
1
6
3
14.2/-9...762
3/3/-26335
14.2/-9_.762
4/4/-35113
14.2/-9...762
4/4/-35113
Shrouded
Ambientt
13 I
3/3/--
4/_--
I
9...762
4/4/-35113
14.2/---
I
I 17 I
4/_--
4/4/--
6
2
8
1
6
3
Axial Type, Vertical Discharge
9...762
4/4/-35113
14.2/---
9...762
6/4/-43891
14.2/19.0
58 522
I
9...762
6/4/-43891
14.2/19.0
58 522
I
9...762
6/6/-52669
14.2/19.0
70 226
14.2/19.0
9...762
7/_-57 059
76 078
9...762
6/6/-52669
14.2/19.0
70 226
I 22 I 22 I 26 I 26 I 26
4/_--
6/4/--
6/4/--
6/6/--
6/6/--
7/6/--
(ram)
3 606
I
4 800
2455
5 994
I
7 188
I
8 382
2296.9
UNIT 30XA
240
6753
OPERATING WEIGHT (kg)
AI/Cu Condenser Coils
260
7644
280
7721
300
7676
REFRIGERANT
TYPE
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C
R-134a,
122.6/122.6/1170.1/99.6/1170.1/122.6/I_
COMPRESSORS
OuanUty
Speed (r/s)
(Qty) Compressor
Nominal Capacity (tons)
(Qty) Compressor
Nominal Capacity (tons)
(Qty) Compressor
Nominal Capacity (tons)
OII Charge (liter), Ckt A/Ckt B/Ckt C
Minimum Capacity Step (%)
Standard
OpUonal
325
8543
2
(1) 120
(1) 120
N/A
I
2
I
2
I
2
I
(1) 165
(1) 100
N/A
I
(1) 165
(1) 120
N/A
I
(1) 185
(1) 120
N/A
25.6/26.6/-10
15
26.4/25.6/-8
10
26.4/26.6/-9
13
WATER CONNECTIONS
Drain (NPT, In.)
Standard, Inlet and Outlet, Vlctaullc (in.)
Number of passes
Minus 1 Pass, Inlet and Outlet, Vlctaullc (in.)
Number of passes
Plus 1 Pass, Inlet and Outlet, Vlctaullc (in.)
Number of Passes
Amblentt
CONDENSER
COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq m)
CHASSIS
Length
Width
Height
DIMENSIONS
(ram)
Copper
Aluminum
Electronic Expansion
Not Applicable
I
26.4/28.4/-10
15
2
(1) 185
(1) 165
N/A
I
3
I
(1) 120
(1) 120
(1) 166
28.4/28.4/-10
14
5166.3/102/186.3/188.3/
I
3
I
(1) 90
(1) 185
(1)166
26.6/25.6/28.4
6
9
28.4/23.7/28.4
4
6
I
3
I
(1) 120
(1) 185
(1)185
28.4/25.6/28.4
5
7
257.4
I
283.9
314.2
1516.8
1034
I
1516.8
1034
1516.8
1034
3/s
3/s
3/s
3/s
3/s
3/s
3/8
2
6
1
6
3
2
6
1
6
3
2
8
1
8
3
2
8
1
8
3
2
8
1
8
3
2
8
1
8
3
1
----8
--
14.2/19.0
14.2/19.0
14.2/19.0
7/6/-57059
9...762
76078
9/6/-65837
9...762
87762
10/6/-70226
9...762
93634
Shrouded
14.2/19.0
Axial Type, Vertical Discharge
14.2/19.0
14.2/19.0
10/6/-70226
9...762
93634
9/9/-79004
9...762
93634
14.2/19.0
9/9/-79004
9...762
105339
6/6/8
87782
9...762
117043
I
I
I
I
3/s
3/8
1
----8
--
1
----8
--
14.2/19.0
14.2/19.0
8/6/8
96561
9...762
128747
8/6/8
96561
9...762
128747
7/6/-19/6/-11°/6/-11°/6/-19/9/-19/9/-I
26 33 36 36 39 39 6/6/616/6/616/6/8
44
48
46
8362
I
9576
Valve
*30XA080 unit does not have an economizer.
tThe high ambient temperature option is not available
500
12199
Twin Rotary Screws
(1) 165
(1) 165
N/A
I
450
12066
Flooded, Shell and Tube ]
LEGEND
CU -AI
-EXV-N/A --
I
I
System
23500I
I
28.4/26.6/-_
12
COOLER
Net Fluid Volume (liters)
Maximum Refrigerant Pressure (kPa)
Maximum Fluid Side Pressure (kPa)
CONDENSER
FANS
Fan Speed (r/s) Standard/High
No. Blades...Dlameter
(mm)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (L/s) 14.2 r/s
Total Airflow (L/s) 19.0 r/s
EXV Controlled
400
11149
188.3/122.6/1170.1/170.1/1168.3/170.1/1122.5/122.5/170.11168.31122.
SembHermetic
Ckt A
Ckt B
Ckt C
350
6636
on 30XA080-120
units.
25
I
10770
2 255
2 300
I
11964 I
13168
RIGGING UNIT (See Fig. 12-14) --The
30XA080-500 units
are designed for overhead rigging and it is impollant that this
method be used. Holes are provided in frame base channels,
marked for rigging (see rigging label on unit). Field-supplied
shackles tue required to facilitate lifting. Secure the shackles
to the base rails at the points noted on the rigging label. See
Table 2 for the number of lifting points for each unit.
Do not use a forklift truck to move the units.
See Fig. 12-14 for rigging centers of gravity.
For shipping, some domestic units and all export units are
mounted on a wooden skid under entire base of unit. Skid can
be removed before unit is moved to installation site. Lift the
unit from above to lemove skid. See Fig. 12-14 for rigging
center of gravity. On export units, the top skid can be used as
the spreader baLs. If the unit was shipped with a shipping bag,
the bag must be removed to gain access to the rigging holes in
the base mil.
Table 2 -- Number of Lifting Points for 30XA080-500
30XA
UNIT SIZE
NUMBER
OF LIFTING
080
If overhead rigging is not available, the unit can be moved
on rollers or dragged. When unit is moved on rollers, the unit
skid, if equipped, must be removed. To lift the unit, use jacks at
the rigging points. Use a minimum number of rollers to distribute the load such that the rollers are no more than 6 ll (1.8 m)
apart. If the unit is to be dragged, H1l the unit as described
above, and place unit on a pad. Apply moving force to the pad,
and not the unit. When in its I]mfl location, raise the unit and
remove the pad. If the unit was shipped with coil protection, it
must be removed before start-up. The shipping bag for export
units must be removed before start-up.
POINTS
4
090-120
6
140, 160
8
180, 200
220-400
10
12
450, 500
14
Use spreader b_us to keep cables or chains clear of unit sides.
As further protection plywood sheets may be placed against
sides of unit, behind cables or ch_dns. Run cables or chains to a
central suspension point so that angle from horizontal is not less
than 45 degrees. Rtdse and set unit down cmefully.
13' MIRINUM
(398Rmm}
AR
A1
CAUTION- NOTICE TO RIGGERS:
ALL
PANELS MUST BE IN
PLACE WHEN RIGGING
DO NOT ATTEMPT TO FORK THESE UMTS
IF NO SKID
IS
SUPPLIED,
NOTES
I 5D IN DIA IBB Fm_) LIFTING
HOLES PROVIDED FOR FIELD SUPPLIED CLEVIS
RIG WITH A _INIIIBM OR BSFT (TBZOmm) LENGTH CIAINS OR CABLES
IF CENTRAL LIFTING POINT IS USED, IT RUST BE A NINIMUN OF 13FT (39RBmm) ABOVE THE TOP OF THE UNIT
SPREAD R BARS BADE IROM SIEEL OR DOBBL NAILER,
AND NOICHED R×6'S ARPROXIMAIELY B FT (B43Bmm) LONG MUST BE
PLACED
IF
JUST
ABOVE
THE
OVERHEAR RIGGING
THE
UNIT
S_ID,
[g
TOP
IS
OF
THE
MDST
ONE ROLLER EVERY 6FT (IBZRmm)
ABOVE,
AND
PLACE
UNIT
UNIT
(AND
NO1 AVAILABLE,
EQDIPI_ED,
ON
BE
STACKS1
THE UNIT
REMOV
D
IO DISIRIBUIE
A PAD
APP
T
IHE
MOVING
TO
REDUCE
THE
RISK
OF
DAMAGE
TO
TI_E
TOP
OF
BAN BE MOVER ON ROLLERS OR BRAGGED WHEN UNII
TO
lIFT
THE
l_
LOAD
FORCE
_RIT,
TO
USE
THE UNIT
THE
PAD,
JACKS
IS
lO
NOT
THE
%1_G
OLES
AT
THE
RIGGING
BE DRAGGER, LIFE
UNIT
WHEN
IN
THE
(Tg
UNIT
AND
COILS
IS MOVED ON ROE ERS,
POINTS
_SE
THE UNIT
FINAl
A MINIMUM
OF
AS DESCRIBED
LOCATION,
RAISE
T_E UNIT AND BEHOVE THE PAD
BHECI<
BILL
OF
LADING
FOR
SH
PPING
WEIGHT
DE
THE
UNIT
LI
.U.BER%c"_'/g{¢d
_"A'CKA"d_'_2
"_"
30XA08O
t2o ;',_ 2, 2L I....
3OXAO9O
8611
4
)OXAIO0
8837
E_E_!!D .........................
Z
4
391_
9_0_
4017
9907
_
4400
4503
45r_
_OB9
10903
27693
161
6118
4775187
_
Fig. 12 -- Unit
GRAVITY
_0B9
7802
19817
T802
1981
19817
7802
19817
7
...............
_01
3
2573
44)
1120
[39
_
3538
16
1172
16l 4089
o!Lt_D_
9
........................
9102
4137
O72
4524
i]iii_i
16 !it
i 408
ibx;_d;_
........................
iJbd-do?
13525
OF
,....
_61
)OXA120
30_A200
CENTER
._2.
16
I 1089
9
78
Rigging
O_
Label
26
3_ O0
Detail
81Z
7
_2 02
15753
30XA080-200
CAUTION- NOTICE TO RIGGERS:
ALL
PANELS
MUST
BE
IN
PLACE
WHEN
RIGGING
DO
NOT
ATTEMPT
TO
FORK
THESE
UNITS
IF
NO
SKID
_S
SUPPLIED
NOTES:
1
150 IN DIAIBB1n_I
LIFTINB
HOLES PROVIDED
FOR FIELD SUPPLIED CLEVIS
R
RIG WITH A MINIMUM OF 25FT (7SROmm) LENGTH CHAINS OR CABLES
3
IF BEN[RAL LIFIING
POINT IS USED, II MUSI BE A MINIMUM Ol 13Fl
(SRSRmm) ABOVE F_E lOP OF DIE UNII
4
SPREADER BARS MADE PROM STEEL OR DOUBLE NAILED, AND NOTCNRN 2X6'S APPROXIMATELY
8 IT 12438mm) LONG MUST BE
PLACED JUST ABOVE THE TOP OF THE UNIT (AND STACKS} TO REDUCE THE RISN OF DAMAGE TO TNE TOP OF TIE UNIT AND COILS
R
IF OVERHEAD RIBGING
IS NO[ AVAILABLE,
[HE UNI[
CAN DE MOVED ON ROLLERS OR DRAGGED WHEN UNI[
IS MOVED ON ROLLERS,
THE UNIT SKIS,
IF EQUIPPED,
MUST DE REMOVED TO LIFT
TNE UNIT, USE JACNS AT THE RIGGING POINTS
USE A MINIMUM OF
ONE ROILER EVERY BFT (IRRRmml TO DISTRIBUTE
THE LOAD
IF THE UNIT IS TO BZ DRABBED,
LIFT TNE UNIT AS DESCRIDEB
ABOVE, ANU PLACE UNIT ON A RAG
APPLY MOVING FORCE TO THE PAR, NOT THE UNIT
8H[N !NIPS
FINAL LOCATION,
RAISE
THE UNIT AND REMOVE THE PAD
6. CHECK DILL O_ LADINB FOR SHIRRING WEIGNT OF THE UNII
N_
_OMDBE[_
MAX SHIPPING MAX SNIPPING
tVI WITHOUT
WI WITH
PACKAGING
PAC{iAGING
30XA220
SOXA240
14668
SOXA260
30XA280
15515
16769
30XA325
18539
6667
5862
I600D
7276
7552
7622
18045
1899
8202
8272
8427
20059
918
LIFTING
_AI "
"AN ....
161
4
9 6NO_
4069
6ZS_
15753
161
6
408 9
408 9
780_
780_
198I
9817
1S 1
4089
780_
19817
BNSS
7
7802
7802
110
Fig. 13 -- Unit Rigging
81
7
D127
19817
987
O_ 27945
CENIER OF GRAVHY
HOLES
A3"
'A4"
I09 03
10903
'AS"
0
S?6UB
_?00
6SOZ
1SISB
1585
4025
46 2
462
3200
3200
812
812
7802
7802
19817
987
7802
7802
19D1 7 1601
19817
604
4066
4074
44 2
443
1123
1125
62 02
15753
32 O0
8127
0903
2769
4499
429
1090
7
7
N
'C'r
81
7
D121
Label Detail 30XA220-350
2?
'D'r
'AS"
3 177
]
1173
1174
13' MINIMUH
13982mm}
CAUFION
ALL
PANELS
NOTES:
150
il
N
5
MODEL
NUMBER
30XA40O
30XA450
30XA508
MUST
8E
!NBIA{B81mm)
IN
PLACE
LIFTING
WHEN
HOLES
RIGGING
PROVIDEB
NOFZ]E lO RIGGERS:
DO
FOR FIELB
NOT
AI]EMP]
SUPPLIED
[0
FORK
]NESE
UNI[S
IF
NO
SHED
IS
SUPPLIED
CIEVIS
RIG WlIN
A MINIMUM OF RSET (TBBOmml LENGTH CHAINS ON CABLES
IF CENTRAL LIFTING
POINT IS USED, iT MUST BE A MINIMUM OF 13PP (3862_}
ABOVE THE POP OF THE UNIT
SPREADER BARS MAKE FROM STEEL OR BOM_LE NAILEB,
ANB NOTCHED 2X6'S
APPROXIMATELY 8 FT (2438mm)
LONG MUST BE
PLACED JUST ABOVE THE TOP OF THE UNIT IAHD STACKS} TO REBUCE THE RISK OT DAMAGE TO THE TOP OF THE UNIT AND COILS
IF OVERNEAB RIGGING [S NOT AVAILABLE,
THE UNIT CAN 8E MOVED ON ROLIERS OR DRAGGED WHEN UNIT IS MOVED ON ROllERS,
INE UNIt
SN]B,
iF EQN]PPEB,
MUSE BE REMOVED TO LIEI
!HE UNIT,
USE JACHS Ar THE RIGGING POIH[S
USE A MINIMUM O_
ONE ROLLER EVERY 6PT (1829_I
TO DISPRIBUPE
THE LOAN
IP PHE UNIT IS TO _E DNAGGEB,
LIPP THE UNIT AS DESCRIBED
ABOVE, ANB PLACE UNIT ON A PAD APHIY MOVING FORCE TO THE PAB, NOT THE NNIP
WHEN IN ITS FINAL lOCATION,
RAISE
TN_ UNIT AHD REMOVE THE RAD
_AX SHIRgING MAX SHIPPING
WT WITHOUT
W_ WIT_
PACNAGIMG
PACNAG[NG
11005
25175
2LN3554 11898
KS
24214
120_7
25824
27875
LB
28136
11738
12671
NG
12789
LIFTING NOLSS
_AI ....
151
151
[N
151
408_
4089
MM
4089
Fig. 14-
AR_¸
7802
7802
[N
7802
"AS"
CEMTSR OF GRAVITY
"A4 ....
19817
19817
MM
19817
AS"
IN
flOOR
32 O0
MM
2794¸5
81R7
B280
812¸7
"AT"
"AT....
B"
"C'_
IN
MM
[N
MM
i IN
_M i IN
_M
52¸02 IS753
......
i!R95
5831i4S8
11531
lO_OS 2759¸3 94¸02 RSBB Ii SR 5 5416i447
1136i
I090K
2759¸3 9402
Unit Rigging Label Detail 30XA400-500
2g
RB8811!533
54B4
448
IIBTI
Step 3 -- Cooler Fluid and Drain Piping
nections -- See Fig. 15-18 for piping applications.
Con-
leaving water temperature stability for comfort cooling applications, a minimum of 3 gallons per ton (3.25 liters per kW) is
required on all unit sizes. For process cooling applications, applications where high stability is critical, or operation at mnbient temperatures below 32 F (0 ° C) is expected, the loop volume should be increased to 6 to 10 gallons per ton (6.46 to
10.76 liters per kW) of cooling. In order to achieve tiffs volume, it may be necessary to add a water storage tank to the water loop. If a storage tank is added to the system, it should be
properly vented so that the tank can be completely filled and all
air eliminated. Failure to do so could cause lack of pump stability and poor system operation. Any storage tank that is placed
in the water loop should have internal baffles to allow fllorough
mixing of the fluid. See Fig. 20.
Remove file chilled water flow switch, entering and leaving
water thermistors before welding connecting piping. Reinstall flow switch and thermistors after welding is complete.
Failure to remove these devices may cause unit &image.
GENERAL -- The factory-installed
victaulic connections _dlow clamp-on connection of water lines to file coolel_ in all
30XA units. A flow sensor is factory-installed in the side of the
entering fluid nozzle. See Fig. 19. See Table 3 for 30XA unit
operating range. See Fig. 16 for cooler option dimensions.
System Piping -- Proper system design and installation procedures should be followed closely. The system must be
constructed with pressure tight components
and thoroughly
tested for installation leaks.
DUAL CHILLER CONTROL -- The Co171/i_tTLinkTM controller allows 2 chillers (piped in parallel or series) to operate as
a single chilled water plant with standard control functions
coordinated through the master chiller controllec This stan&trd
Co_71ibrtLink feature requires a communication
link between
the 2 chillers.
There me severtd advantages
•
•
•
•
Installation of water systems should follow sound engineering practice as well as applicable local and industry standards.
Improperly designed or inst_dled systems may cause unsatisfactory operation and/or system failure. Consult a water
treatment specialist or appropriate literature for information
regarding filtration, water treatment, and control devices.
to this type of control:
redundancy (multiple circuits)
better low load control, (lower tonnage capability)
lower rigging lift weights (2 machines rather than one
large machine)
chiller lead-lag operation (evens the wear between the
two machines)
Parallel Dual Chiller Operation
-- Pm'allel chiller operation
is the recommended option for dual chiller control. In this case,
each chiller must control its own dedicated pump or isolation
valve. Balancing v_dves are recommended
to insure proper
flow in each chillec Two field-supplied and inst_dled dual chiller leaving water temperature sensors ale required, one for each
module for this function to operate properly.
Dual Chiller Leaving Water Sensor --If the Dual Chiller algorithm is used, and the machines me installed in parallel, a
dual chilled water sensor must be installed for each module. Install the well in the common leaving water headec See Fig. 17.
Consider adding additional isolation valves to isolate each
chiller to allow for service on a machine, and still allow for partied capacity from the other chillec See Fig 17.
Minimum Loop Volume -- The preferred minimum loop volume is dependent on the type of application. In order to obtain
AIR FLOW
POWER
FD
FD
CONTROL
BALANCIN(
SHUTOFF*
VIBRATI(
ELIMINATORS*
_,
DRAIN
SHUTOFF
VALVE
LEGEND
FD
--
Fused Disconnect
Airflow Through Condenser
c====_
Chilled Water Piping
Power Wiring
*Field-installed.
PRESSURE/
TEMPERATURE
TAPS*
NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
2. Piping shown are general points-of-connection
guides only and are not
intended for a specific installation. Wiring and piping shown are for a quick
overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System
Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) handbook for details.
Fig. 15 -- 30XA Typical Piping and Wiring
29
Table 3 -- 30XA Minimum and Maximum Cooler Flow Rates*
ITEM
MINIMUM
Cooler Leaving Water Temperaturet
Cooler Enterin_l Water Temperature**
30XA
Number of
Cooler
UNIT SIZE
Passes
Standard
080
Plus one pass
Minus
one pass
Standard
090
Plus one pass
Minus one pass
Standard
100
Plus one pass
Minus
one pass
Standard
110
Plus one pass
Minus
one pass
Standard
120
Plus one pass
Minus
one pass
Standard
140
Plus one pass
Minus one pass
Standard
160
Plus one pass
Minus
one pass
Standard
180
Plus one pass
Minus
one pass
Standard
200
Plus one pass
Minus
one pass
Standard
220
Plus one pass
Minus one pass
Standard
24O
Plus one pass
Minus
one pass
Standard
260
Plus one pass
Minus
one pass
Standard
28O
Plus one pass
Minus
one pass
Standard
3OO
Plus one pass
Minus one pass
Standard
325
Plus one pass
Minus
one pass
Standard
35O
Plus one pass
Minus
one pass
Standard
4OO
Flow
70F(21.1
C)
Rate
Maximum
(_Ipm)
IUs)
95
6.0
(_lpm)
379
Rate
(Us)
Nominal
(?pm)
Flow Rate
(us)
23.9
43
2.7
192
12.1
198
12.4
782
49.3
101
8.4
403
25.4
43
2.7
200
12.6
229
14.4
917
57.9
101
8.4
403
25.4
43
2.7
200
12.6
229
14.4
917
57.9
125
7.9
5Ol
31.6
61
3.8
244
15.4
254
18.0
1014
84.0
125
7.9
501
31.6
73
4.8
293
18.5
281
17.7
1124
70.9
134
8.5
538
33.9
73
4.8
293
18.5
324
20.4
1298
81.8
165
10.4
860
41.6
98
8.2
391
24.7
354
22.3
1418
89.5
202
12.7
807
50.9
73
4.8
391
24.7
418
28.2
1862
104.9
223
14.1
892
56.3
98
8.2
391
24.7
458
28.9
1833
115.6
235
14.8
941
59.4
122
7.7
489
30.9
501
31.8
2004
126.4
268
18.8
1063
87.1
147
9.3
587
37.0
538
33.9
2151
135.7
257
18.2
1027
84.8
141
8.9
562
35.5
584
38.8
2334
147.3
293
18.5
1173
74.0
141
8.9
562
35.5
820
39.1
2481
156.5
327
20.8
1308
82.5
174
11.0
897
44.0
887
43.3
2750
173.5
361
22.8
1442
91.0
211
13.3
843
53.2
724
45.7
2897
182.8
379
23.9
1518
95.6
244
15.4
978
81.7
767
48.4
3068
193.6
501
31.8
2004
126.4
1
501
180.4
11.4
201.9
12.7
225.5
14.2
244.9
15.5
264.8
16.7
317.8
20.1
365.1
23.0
409.8
25.8
463.9
29.3
505.9
31.9
545.8
34.4
800.3
37.9
842.2
40.5
887.5
43.4
733.4
46.3
775.4
48.9
--
917.8
57.9
--
1019.3
84.3
--
1092.8
88.9
2004
Plus one pass
Minus one pass
Standard
1
501
2004
m
Plus one pass
Minus
Flow
one pass
Standard
5OO
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
1
45F17.2
c!
Minimum
NOMINAL
60 F (15 C)
Plus one pass
Minus
45O
MAXIMUM
40 F (4.4 C)
m
one pass
NOTES:
*Maximum
ambient temperature
and percent of unit capacity
will vary based on
unit load and return water temperature.
All models are qualified for use at 125 F
(48 C). Some models
may require the high ambient fan option. Contact a local
Carrier
representative
to obtain performance
data using the Carrier
electronic
catalog.
1-For applications
requiring cooler leaving water temperature
operation
at less than
40 F (4.4 C, the units require the use of antifreeze
and application
may require
one of the spec a order br ne opt on. Contact
a oca Carrier representat
ve for
more information.
**For applications
requiring
cooler entering
water temperature
operation
at less
than 45 F (7.2 C, contact
a local Carrier
representative
for unit selection
using
the Cart ere ectron c cata og.
1. The 30XA units will start with loop temperatures
up to 95 F (35 C.
2. Nominal flow rates required
at ARI conditions
44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water temperature,
95 F (35 C) ambient.
Fouling factor
0.00010 ft2-h r-F/Btu (0.000018
m2-K/kW).
3. To obtain proper temperature
control,
cooler loop fluid volume
must be at least
3 gal/ton
3.23 L/kW
of chiller nominal capacity for air conditioning
and at least
6 gal/ton (6.5 L/kW) for process applications
or systems that must operate in low
ambient temperatures
(below 32 F 0 ° C .
4. Where winds of 5 mph (2.2 m/s) or greater are anticipated
at outdoor
ambient
temperatures
below 32 F (O° C), wind baffles are required.
5. Requires optional or accessory
low ambient kit for operation
below 32 F (0 ° C).
30
ENGLISH
STANDARD
30XA
UNIT
SIZE*
080
090
100
110
120
140
160
180
200
220
240
260
280
300
328
380
Distance to
Leaving/
Entering
Water
Distance to
Leaving
Water
Connection
Height
Leaving
Water
Connection
(in.)
(in.)
Connection
(in.)
121.2
120.9
120.9
120.9
120.9
121.5
121.5
177.7
177.3
224.7
224.7
304.7
304.7
304.7
349.0
349.0
19.1
19.1
19.1
19.1
19.1
21.3
21.3
22.5
22.5
22.5
22.5
23.6
28.6
28.6
23.6
23.6
68.1
68.1
68.1
66.1
68.1
69.1
69.1
70.2
70.2
70.2
70.2
71.1
71.1
71.1
71.1
71.1
COOLER
Distanceto
Entering
Water
Connection
PLUS ONE PASS COOLER
Height
Entering
Water
Connection
(in.)
(in.)
121.2
120.9
120.9
120.9
120.9
121.5
121.5
177.7
177.3
224.7
224.7
304.7
304.7
304.7
349.0
349.0
10.8
10.8
10.8
10.6
10.6
10.6
10.6
11.3
11.3
11.3
11.3
12.2
12.2
12.2
12.2
12.2
Vlctaullc
Connection
Size
(in.)
(in.)
(in.)
Distance to
Leaving/
Entering
Water
ConnecUon
(in.)
1.5
1.2
1.2
1.2
1.2
1.2
1.2
53.6
53.2
100.6
100.6
180.3
160.3
160.3
224.7
224.7
19.6
19.6
19.6
19.6
19.6
21.3
21.3
22.4
22.4
22.4
22.4
23.4
23.4
23.4
23.4
23.4
68.1
68.1
68.1
66.1
68.1
69.1
69.1
70.2
70.2
70.2
70.2
71.1
71.1
71.1
71.1
71.1
Distance
to
Leaving
Water
Connection
5.0
5.0
5.0
5.0
5.0
5.0
5.0
6.0
6.0
6.0
6.0
8.0
8.0
8.0
8.0
8.0
Height
Leaving
Water
Connection
Distance
to
Entering
Water
Connection
(in.)
121.2
120.9
120.9
120.9
120.9
121.5
121.5
180.6
180.2
227.6
227.6
310.3
310.3
310.3
354.7
354.7
MINUS ONE PASS COOLER
Height
Entering
Water
Connecttan
(in.)
10.8
10.3
10.3
10.3
10.3
10.6
10.6
11.4
11.4
11.4
11.4
12.5
12.5
12.5
12.5
12.5
Vlctaullc
Connection
Size
(in.)
4.0
4.0
4.0
4.0
4.0
5.0
5.0
6.0
6.0
6.0
6.0
8.0
8.0
8.0
8.0
8.0
Distance to
Leaving
Water
Connection
(in.)
-2.2
-2.5
-2.5
-2.5
-2.5
-2.2
-2.2
53.6
53.2
100.6
100.6
180.3
180.3
180.3
224.7
224.7
Height
Leaving
Water
Connection
(in.)
14.9
14.9
14.9
14.9
14.9
15.9
15.9
13.2
13.2
13.2
13.2
16.3
16.3
16.3
16.3
16.3
Distance to
Leaving/
Entering
Water
Connection
(in.)
68.1
66.1
68.1
66.1
66.1
69.1
69.1
70.2
70.2
70.2
70.2
71.1
71.1
71.1
71.1
71.1
Distance to
Entering
Water
Connection
(in.)
124.8
124.5
124.5
124.5
124.5
124.8
124.6
160.6
180.2
227.6
227.6
310.3
310.3
310.3
354.7
354.7
Height
Entering
Water
Connection
(in.)
14.9
14.9
14.9
14.9
14.9
15.9
15.9
13.2
13.2
13.2
13.2
16.3
16.3
16.3
16.3
16.3
Vlctaullc
Connection
Size
(in.)
5.0
5.0
5.0
5.0
5.0
6.0
6.0
8.0
8.0
6.0
8.0
8.0
8.0
8.0
8.0
8.0
SI
STANDARD
30XA
UNIT
SIZE*
'._
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
Distanceto
Leaving
Water
Connection
Height
Leaving
Water
Connection
(ram)
(ram)
3077.8
3069.6
3069.6
3069.6
3069.6
3085.8
3085.8
4512.3
4502.4
5706.2
5706.2
7739.6
7739.6
7739.6
8865.1
8865.1
484.0
484.0
484.0
484.0
484.0
540.6
540.6
571.0
571.0
571.0
571.0
600.2
600.2
600.2
600.2
600.2
Distance to
Leaving/
Entering
Water
Connection
(ram)
1728.7
1726.7
1728.7
1728.7
1726.7
1756.2
1756.2
1782.1
1782.1
1782.1
1762.1
1804.9
1804.9
1604.9
1804.9
1804.9
COOLER
PLUS ONE PASS COOLER
Distance to
Entering
Water
Connection
Height
Entering
Water
Connection
(ram)
(ram)
3077.8
3069.6
3069.6
3069.6
3069.6
3086.8
3085.8
4512.3
4502.4
5706.2
5706.2
7739.6
7739.6
7739.6
8865.1
8865.1
274.2
274.2
274.2
274.2
274.2
268.7
268.7
287.0
287.0
287.0
287.0
310.1
310.1
310.1
310.1
310.1
Vlctaullc
Connection
Size
(ram)
127.0
127.0
127.0
127.0
127.0
127.0
127.0
152.4
152.4
152.4
152.4
203.2
203.2
203.2
203.2
203.2
"30XA400-500
units are eq uipped wi_ standard coolers one!, Refer to unit dimensional
NOTE: Refer to dimensional drawings for all oth er unit dimensions.
Distanceto
Leaving
Water
Connection
Distance to
Leaving/
Entering
Water
Height
Leaving
Water
Connection
(ram)
(ram)
37.9
29.7
29.7
29.7
29.7
30.1
30.1
1361.4
1351.6
2555.3
2555.3
4580.8
4580.8
4580.8
5706.4
5706.4
497.2
497.2
497.2
497.2
497.2
540.6
540.5
569.5
569.5
569.5
569.6
593.9
593.9
593.9
593.9
593.9
Connection
(mm)
1728.7
1728.7
1728.7
1728.7
1726.7
1756.2
1756.2
1782.1
1782.1
1782.1
1762.1
1804.9
1804.9
1804.9
1804.9
1804.9
DIstanceto
Entering
Water
Connection
(ram)
3077.8
3069.6
3069.6
3069.6
3069.6
3086.8
3085.8
4587.2
4577.4
5781.1
5781.1
7882.8
7882.8
7682.8
9008.4
9008.4
MINUS ONE PASS COOLER
Height
Entering
Water
Connection
(ram)
261.0
261.0
261.0
261.0
261.0
268.7
268.7
288.5
288.5
288.5
286.5
316.5
316.5
316.5
316.5
316.5
Vlctaullc
Connection
Size
(ram)
101.6
101.6
101.6
101.6
101.6
127.0
127.0
152.4
152.4
152.4
152.4
293.2
203.2
208.2
203.2
203.2
Distance to
Leaving
Water
Connection
(ram)
=55.1
43.2
43.2
43.2
43.2
-55.0
-55.0
1361.4
1351.6
2555.3
2555.3
4580.8
4580.8
4580.8
5706.4
5706.4
drawings for cooler dimensions.
Side View
Cooler
ql
L
I
[ Entering/Leaving ]
Water Length J
Fig. 16 -- Cooler Option Dimensions
Height
Leaving
Water
Connection
(ram)
379.1
379.1
379.1
379.1
379.1
404.6
404.6
336.0
336.0
336.0
336.0
413.3
413.3
418.3
413.3
413.3
Distance to
Leaving/
Entering
Water
Connection
(ram)
1728.7
1728.7
1728.7
1728.7
1726.7
1756.2
1766.2
1782.1
1782.1
1782.1
1762.1
1804.9
1804.9
1804.9
1804.9
1804.9
Dlstanceto
Entering
Water
Height
Entering
Water
Connection
(ram)
Connection
(ram)
3170.7
3162.6
3162.6
3162.6
3162.6
3170.8
3170.8
4587.2
4577.4
5781.1
5781.1
7862.8
7862.8
7682.8
9008.4
9008.4
379.1
379.1
379.1
379.1
379.1
404.6
404.6
336.0
336.0
336.0
336.0
413.3
413.3
418.3
413.3
413.3
Vlctaullc
Connection
Size
(ram)
127.0
127.0
127.0
127.0
127.0
152.4
152.4
208.2
203.2
203.2
203.2
203.2
203.2
208.2
203.2
203.2
-I
I
CO.T_
L
MASTER
I
CHILLER
PUMP
& CHECK
VALVE
#
I
-4>r
I
I
OR
ISOLATION
VALVE
I
_l
SLAVE
CHILLER
PUMP
& CHECK
VALVE
-bTq-
I
OR
ISOLATION
LEGEND
LWT
--
VALVE
Leaving Water Temperature
Field-Installed Communication
Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
Twisted Pair
DUAL SENSORS
CHILLER
LWT
& WELLS
Fig. 17 -- Parallel Dual Chiller Operation
I
I
SLAVE
CH,LLER OONT#oO_
l
I
I
PUMP
I
,q
I
I
I
I=
I
I
LEGEND
CONTROL
BOX _.
MASTER
CHILLER
LWT
Fig. 18-
Series Dual Chiller Operation
32
--
Leaving Water Temperature
Field-Installed Communication Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
Twisted Pair
the cooler head for maintenance.
[nst_dl pipe hangers where
needed. Make sum no weight or stress is placed on the water
nozzle.
Provide openings in fluid piping for pressure gages and
thermometel_ (if used). These openings should be 5 to 10 pipe
diameters from the unit leaving water nozzle. For thorough
mixing and temperature stabilization, wells in the leaving fluid
pipe should extend at least 2 in. (50 mm) into the pipe.
Although the cooler has an air vent, it is recommended
that
a field-supplied air vent be installed in the system to facilitate
servicing. Field-supplied shut-off and balancing v_dves should
also be installed to facilitate servicing and flow balancing.
Ix_cate valves in return and supply fluid lines as close to the
chiller as possible. Ix)cate air vent at highest point of the cooler
fluid system. See Fig. 15.
_
Provide diain connections at all low points to permit complete di'ainage of the system.
COOLER PUMP CONTROL--It
is recommended
that
cooler pump control be utilized on all chillers unless the chilled
water pump runs continuously or the chilled water system contains a suitable antifieeze solution. Proper configuration of the
cooler pump control is required to prevent possible cooler
fieeze-up. A thermal flow sensor is facto q inst_dled in the
entering fluid nozzle to prevent operation without flow through
the coolec See Fig. 21. The sensor contacts am facto U wired.
The factou-installed
flow sensor and cooler interlock must be
wired in series. Install TBS-I and TBS-2 if using a cooler pump
interlock and connect it to these terminals. It is also recommended that the chiller be interlocked with the chiller water
pump starter to provide additional freeze protection. See the
Field Control Power Connections section on page 34 for proper
connection of the cooler pump interlock. The cooler pump relay will remain energized for 30 seconds after all compressors
stop due to an off command. In the event a freeze protection
_flarm is generated, the cooler pump relay will be energized
whether the cooler pump control is configured to "ON" or
"OFF". The cooler pump relay is also energized anytime a
compressor is started and when certain _dmms are generated.
The cooler pump relay should be used as an override to the external pump control if cooler pump control is not utilized.
FLOW SWITCH
Fig. 19 -- Flow Switch
-[_F
BAD
GOOD
BAD
GOOD
I
IMPORTANT:
Chilled
water pump control
and cooler
pump interlock
wiring
are required
to prevent
possible
cooler
fieeze up due to loss of fluid flow. Refer to field
wiring diagram
for installation
details.
Fig. 20 -- Tank Baffling
Series Dual Chiller
Operation
-- Series chiller operation
is an
alternate
control
method
supported
by the Con_/ortLink
TM
control
chillers
cooler
reduce
system. Certain applications
might require that the two
be connected
in series. For nomimfl
10 ° F (5.6 ° C)
ranges,
use the Minus
1 Pass cooler
mTangements
to
the fluid-side
pressure
diop. Use the standard
cooler
pass mmngement
for low flow, high cooler
temperature
rise
applications.
Two field-supplied
and installed
dual
chiller
leaving
water temperature
sensors me required,
one for each
module
for this function
Consider
isolate each
allow
to operate
properly.
adding
additional
piping
chiller to allow for service
for partial
capacity
fiom the other
and isolation
valves to
on a machine,
and still
chillel:
See Fig.
@
18.
COOLER
FLUID,
VENT. AND DRAIN
-- The inlet (return)
fluid connection
is always
the lower of the 2 cooler
connections. See Fig. 2-10 for locations.
A screen strainer with a minimum size of 20 mesh must be installed
a maximum
of 10 ft
fi'om the unit to prevent debris from dmnaging
internal
tubes of
the coolel:
Outlet
(supply)
fluid
connection
is the upper
connection
of the 2 cooler connections.
The cooler has victaulic connections
to connect
the field-supplied
piping. Plan the
piping arrangement
in accor&mce
with good piping practices
and ensure that the piping does not cross in front of the cooler
head. Use flexible
connections
on cooler
piping
to reduce
vibration
transmission.
Offset the piping to permit remover
of
Fig. 21 -- Thermal Flow Sensor
33
[
I
BRINE UNITSSpecial factory modifications
to the units
are required to _dlow them to operate at fluid temperatures less
than 34 F (1.1 C). Be sure that the fluid has sufficient inllibited
glycol or other suitable corrosion-lesistant
antitYeeze solution
to prevent cooler freeze-up.
Mount the smaller height baffle on units with a control box
located on the end of the unit. It is recommended that the upper
notches be used for mounting the baffles. This reduces the risk
of dmnaging the coil while drilling a mounting hole. Ix_osen
the upper comer post bolts and slide the baffle under the bolt
and washel: Tighten the bolt. Drill holes in the bottom of the
flange of the baffle and mount with two sclews to secure the
bottom of the baffle to the comer post. Repeat the process for
the opposite end. See Fig. 22.
WATER TREATMENTUntleated or improperly tleated
water may result in corrosion, sc_ding, erosion, or algae. The
services of a qu_dified water tleatment specialist should be
obtained to develop and monitor a treatment program.
PREPARATION
FOR WINTER SHUTDOWN
-- If the unit
is not operatiomfl during the winter months, at the end of cooling season complete the following steps.
Water must be within design flow limits, clean, and treated
to ensure proper chiller performance and reduce the potential of tube damage due to corrosion, scaling, erosion, and
algae. Cmrier assumes no responsibility for chiller &_mage
resulting from untreated or improperly treated watel:
Failure to remove power before draining heater equipped
coolers can result in heater tape and insulation damage.
1. [f the cooler will not be dndned do not shut off power
disconnect during off-season shutdown. If the cooler is
drained, open the circuit breaker for the heater. CB-HT
(circuit breaker heater) or shut off power during offseason shutdown.
NOTE: Do not use automobile anti-freeze, or any other fluid
that is not approved for heat exchanger duty. Only use appropriately inhibited glycols, concentrated
to provide adequate
protection for the temperature considered.
PREPARATION
FOR YEAR-ROUND
OPERATION
-- In
areas where the piping or unit is exposed to 32 F (0 ° C) or
lower ambient temperatures,
freeze-up protection is required
using inhibited glycol or other suitable corrosion-resistant
antifleeze solution and electric heater tapes. Heater tapes on piping
should have a rating for ;u'ea mnbient temperatures and be covered with a suitable thickness of closed-cell insulation. Route
power for the heater tapes from a sepm'ately fused disconnect.
Mount the disconnect within sight from the unit per local or
NEC (National Electric Code) codes. Identify disconnect at
heater tape power source with a warning that power must not
be turned off except when servicing unit.
2.
Draining the fluid from the system is highly recommended.
3.
Isolate the cooler from the rest of the system with water
shutoff v_dves.
4.
Completely fill the cooler with a mixture of half water
and half inhibited glycol solution (or other suitable conosion-inhibitive
antifreeze) for 15 ° F (8.3 ° C) below the
expected low ambient temperature conditions.
Leave the cooler filled with the antifreeze solution for the
wintel: or drain if desired. Be sure to deenergize heaters
(if installed) as explained in Step 1 to plevent damage.
Use an approved method of disposal when lemoving antifreeze solution.
5.
IMPORTANT:
Adding antifreeze solution is the only
certain means of protecting the unit flom freeze-up if
heater fails or electrical power is interrupted
or lost
while temperatures
are below 32 F (0 ° C).
6. At the beginning of the next cooling season, be sure that
there is refrigerant
pressure on each circuit before
refilling coolel: add recommended inhibitol: trod reset the
CB-HT (circuit breaker heater) (if opened) or restore
powel:
IMPORTANT:
Before starting the unit, be sure all of
the air has been purged from the system.
Step 4 --
A di'ain connection is located at the bottom of the cooler
head. See Fig. 2-10 for connection location. Install shut-off
v_dves to the drain line before filling the system with fluid.
Make Electrical
Connections
Electrical shock can cause personal injury and death. Shut
off _fll power to this equipment during inst_fllation. There
may be more than one disconnect switch. Tag all disconnect locations to alert othel_ not to restore power until work
is completed.
Low Ambient Temperature
Head Pressure Control -- If the
unit is equipped with the low ambient temperature head pressure control option, field-fabricated
and field-installed
wind
baffles are required if the wind velocity is anticipated to be
gleater than 5 mph (8 km/h). Two different baffles may be required, facing the control box. Wind baffles should be constmcted with minimum 18-gage g_dvanized sheet metal or other suitable corrosion-resistance
material with cross breaks for
strength. See Fig. 22. Use field-supplied screws to attach baffles to the corner posts of the machine. Be sure to hem or turn a
flange on _dl edges to eliminate sharp edges on the baffles.
POWER SUPPLY --The
electrical ch_u'acteristics
of the
available power supply must agree with the unit nameplate
rating. Supply voltage must be within the limits shown. See
Tables 4-6 for electric_d and configuration &tta.
To avoid possibility of electric_d shock, open all disconnects before installing or servicing this accessory.
FIELD POWER CONNECTIONS
(See Fig. 23) -- All power wiring must comply with applicable
local and national
codes. Install field-supplied, branch circuit lhsed disconnect(s)
of a type that can be locked off or open. Disconnect(s) must be
located within sight and readily accessible from the unit in
compliance with NEC Article 440-14 (U.S.A.). See Tables 4
and 5 for unit electrical &_ta. See Table 6 for compressor and
fan electrical &tta.
To avoid dmnage to the refl'igerant coils and electrical components, use extreme ctue when drilling screw holes and
screwing in fasteners.
IMPORTANT:
The 30XA units have a factory-inst_dled
option available for a non-fused disconnect for unit power
supply. If the unit is equipped with this option, all field
power wiring should be made to the non-fused disconnect
since no terminal blocks are supplied.
34
Cross break these faces.
Hem these 3 edges both top
and bottom.
305 [12.0]
4
See Detail A
\
1880 [74.0]
BAFFLE HEIGHT (X)
RIGHT END LEFT END
POSITION
30XA080-120
(Facing the control box end I
30XA140-500
(Facing the control box end)
1040 [41.0]
635 [25.0]
1040 [41.0]
1040 [41.0]
NOTES:
1. Material: 18 ga. Corrosion Resistant Sheet Metal.
2. Dimensions are in mm [inches],
18 [0.75] _'_
_Z0 [2"7
t
..............
L_SDetailA
1--18
es_
[0.75]
_*_31
[1.25]
_21
[0.88]
Typical Both Flang
Fig. 22 -- Field-Fabricated
Maximum wile size that the unit terminal
fused disconnect will accept is 500 kcmil.
and Field-Installed Wind Baffles
block or non-
The 30XA units require 1 or 2 power supplies, depending
on the unit and circuit voltage. See Tables 4 and 5 for the number of power supplies required for each unit.
Do not use interlocks or other safety device contacts
connected between TB5-9 and TB5-10 as remote on-off.
Connection of safeties or other interlocks between these
2 terminals will result in an electrical bypass if the
ENABLE-OFF-REMOTE
contact
switch
is in the
ENABLE position. If remote on-offunit control is required,
a field-supplied lelay must be installed in the unit control
box and wired as shown in Fig. 22. Failure to wire the
remote on-off as recommended
may result in tube freeze
&tmage.
FIELD CONTROL POWER CONNECTIONS
(See Fig. 23) -Units with a power supply of all voltages require 115-1-60
control circuit power, unless the control option is installed.
Terminals TB5-1 and TB5-2 ale provided for field installation of a chilled water (fluid) pump interlock (CWPI). Tile
chilled water (fluid) flow sensor (CWFS) is factory installed.
These devices ale to be installed in series. Contacts must be
rated for dry-circuit applications capable of handling a 24-vac
at 50 mA load.
Terlninals 11 and 13 of TB5 me for control of the chilled
water pump 1 (PMPI) startel: Terminals 13 and 15 of TB5 me
for control of the chilled water pump 2 (PMP2) startel:
An accessory remote on-off switch c:m be wired into TB5-9
and TB5-10. To use this feature, remove the factory-installed
jumper and install the device in series. Contacts must be rated
for dry-circuit applications capable of handling a 24-vac at
50 mA load.
35
iO
T_A
.:.=_
iO
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
FIELO
,_
_
_
_
_
_ _ _ _
POW[R
SUPPLT
,-
ACCESSORY
&Be
{SEE NOTE_2_
TERMINAL BLOCK
i
i_l i_l _l
I
I I
I
I
I
I
I_1 I:
i Iiili
LI
LI_LI_
C81A
DA_A_OMFORT
I
I
I
I
I
I
I
I
M-L
I
I
_]_LO
I _o_
I
I
I
f. ....
I
!..
!..
I
i
suP,_
I
I
!
I
L..a
--
I
DISCONNECT/BRANCH CIRCUIT
PRO_C'nO_
_
BEG
I
J
(SEE NOTE _2_
NON-FUSED DISCONNECT
NOTES:
1. Factory
2. _iCegltohr
Incoming
Incoming
Incoming
LEGEND
wiring
is in accordance
with UL 1995 standard&
Field
a_ll_,P fPilie_bslepCp_d_-_ustbe rated 75 C ,'ninimurn.
wire size range
wire size range
wire size range
for units 080-120,
for units 140-240,
for units 140-240,
modifications
Use copper
or additions
must be in compli-
for allunits.
all voltages is 4-500 kcmil.
200/230 v is 1/0-500
kcrnil.
380,460,
575 v is 4%00 kcmil.
3. [ peCr
°/_1iliads_ rell_i Zleora_l_-_ _° r UenitoSr2ieOd500_ 380,4o610 ,eSc
tTiSlvsi;lr/O-m500
koOnm(Hif,
The contacts
must
be rated
A
--
Alarm
EMM
MLV
NEC
PMP
PMPI
TB
-I
--I
I
Energy Management
Minimum
Load Valve
National
Electric Code
Chilled Water Pump
Chilled Water Pump Interlock
Terminal
Block
iiii
iiii
4. _errdrl_nci_c_ita_jP_Co_tl_B_aPeabloer
be rated for dry circuit application
°fxthea_ldallll_gonal2e4ctVoa,_
capable
of handling
50alt_rApump
a 24 vac
interlock.
The
contacts
must
load up to 50 mA.
5. Ter_'ninals
TB5 are for 11control
and 13
of of
chilled
TB5 _et fOrpCOn_r_l ofc_Hedtwa_rr
,_,_
_---_-_- J_umpl
Field
Power
....
Field
Control
--
Factory
[,,P,M,,Pll)starr
_
_-_,
tller:,,Ter,'ni!la/s
,_,_ Ofchille
13 andwater15
d
6. _UmcPo[_lra_ i_ c5_lesde_lletd,r 10Vapin, raUShe_to24oV_mFi_llyd
oPpeWecrSUtPaPcltYs
iSal]eOc_
_eq_irrydcircui t application
must
be
supplied from field-supplied
pump starter relay. Connect contacts to violet and pink wires in harness
from
main base board channel l& Wires in harness are marked PMP1-13 and PMP1-14.
7. Terminals
12 and 13 of TB5 are for an alarm relay. The maximum
load allowed for the alarm relay is 10 va
8,
_/_
E_l__al_edapproprIiateScont,#ctions_o
&
;"*11
_"
"
'34
"
board
-_'"_*_''1"
*_"";*_'4_Be_ss_oH_°foIrei_,_gy_anagernent
;_ "_÷
_CC_liagCaY_,_e_icd&ddeumpal_d/_imt,_l]d
ice done options
must
options.
be rated for dry circuit
The
application
contacts
capable
for
of
Fig. 23 -- Control and Power Wiring Schematic, 30XA080-500
36
Wiring
Wiring
Installed
Wiring
Table 4 -- 30XA080-500
Electrical Data (Standard Condenser Fan Motors)
(3 Ph, 80 Hz)
MIn
Max
MAIN POWER
SUPPLY
OTY REOD
080
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
1
1
1
1
1
347.6
315.5
183.5
157.7
121.2
090
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
1
1
1
1
1
1O0
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
11o
200
230
380
460
575
187
207
342
414
518
120
200
230
380
460
575
140
UNIT
30XA
VOLTAGE
VOLTAGE RANGE
ICF
XL
WD
RED FUSE
SIZE
450
400
250
200
150
1257.6
1100.2
662.7
550.1
437.9
521.6
460.2
275.7
230.1
181.9
368.0
334.0
194.5
167.0
128.5
500
450
250
225
175
1274.0
1115.1
671.6
557.6
443.8
1
1
1
1
1
401.3
364.6
212.7
182.3
139.5
500
500
250
250
175
220
253
418
506
633
1
1
1
1
1
446.2
405.7
236.4
202.4
155.5
187
207
342
414
518
220
253
418
506
633
1
1
1
1
1
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
1
1
1
1
1
200
230
380
460
575
200
230
380
460
575
187
207
342
414
518
187
207
342
414
518
220
253
418
506
633
220
253
418
506
633
2
2
1
1
1
2
2
1
1
1
465.6/264.9
423.5/241.0
361.1
309.7
238.1
407.2/407.2
370.0/370.0
391.5
336.6
258.3
800/450
700/400
500
450
350
700/700
600/600
500
450
350
--/---/-1564.9
1296.4
1034.3
--/---/-1336.2
1109.6
882.8
902.8/463.5
786.0/404.0
590.9
491.4
390.3
729.8/729.8
636.0/636.0
561.2
469.6
370.8
200
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
2
2
1
1
1
465.6/465.6
423.5/423.5
447.2
383.9
294.8
800/800
700/700
600
500
400
--/---/-1651.0
1370.6
1091.0
220
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
2
2
1
1
1
554.7/548.0
504.2/423.5
494.5
424.7
326.3
800/800
800/700
700
600
450
240
200
230
380
460
575
187
207
342
414
518
220
253
418
506
633
2
2
1
1
1
554.7/548.0
504.2/498.2
529.5
455.0
349.6
800/800
800/800
700
600
450
260
380
460
575
342
414
518
418
506
633
1
1
1
600.2
516.5
396.4
800
700
500
2376.9
1969.6
1570.2
917.9
764.6
606.2
280
380
460
575
342
414
518
418
506
633
1
1
1
638.2
549.8
422.0
800
800
600
2414.9
2002.9
1595.9
300
380
460
575
342
414
518
418
506
633
1
1
1
710.3
610.9
468.7
1000
800
600
2415.4
2002.9
1595.9
325
380
460
575
342
414
518
418
506
633
2
1
1
426.0/426.0
624.3
479.1
700/700
800
600
2202.7/2202.7
2077.5
1652.9
743.7/743.7
872.5
688.9
350
380
460
575
342
414
518
418
506
633
2
1
1
497.6/426.0
685.5
525.7
800/700
800
700
2202.7/2202.7
2077.5
1652.9
400
380
460
575
342
414
518
418
506
633
2
2
2
419.4/561.9
340.9/452.0
261.4/347.2
700/700
500/600
450/450
450
380
460
575
342
414
518
418
506
633
2
2
2
490.9/685.4
402.0/553.6
308.0/424.4
500
380
460
575
342
414
518
418
506
633
2
2
2
490.9/745.1
402.0/604.9
308.0/463.9
160
180
MCA
MOCP
----
Instantaneous
Current Flow
Minimum Circuit Amps
Maximum Overcurrent
Protection
WD
--
Wye=Dega
Across-the-Line
CIRCUIT
MCA and
MOCP
400
35O
225
175
15O
538.0
475.1
284.6
237.6
187.8
45O
400
225
200
15O
115
115
115
115
115
3O
3O
3O
3O
3O
1564.8
1368.7
824.7
684.4
544.7
644.8
568.7
340.7
284.4
224.7
45O
400
250
200
175
115
115
115
115
115
3O
3O
3O
3O
3O
600
500
300
250
200
--824.7
684.4
544.7
644.8
568.7
340.7
284.4
224.7
5OO
45O
3OO
225
175
115
115
115
115
115
3O
3O
3O
3O
3O
482.2
438.6
255.3
218.4
168.4
600
600
350
300
225
--843.6
700.4
557.5
680.8
601.6
359.6
300.4
237.5
6OO
5OO
3OO
25O
2OO
115
115
115
115
115
3O
3O
3O
3O
3O
588.5
534.7
311.2
800
800
450
1255.9
267.3
205.0
400
300
1040.4
829.5
911.1
800.7
480.9
400.4
317.5
7OO
7OO
35O
35O
25O
115
115
115
115
115
3O
3O
3O
3O
3O
600/350
600/300
45O
35O
3OO
500/500
450/450
45O
4OO
3OO
115
115
115
115
115
115
115
115
115
115
3O
3O
3O
3O
3O
3O
3O
3O
3O
3O
902.8/902.8
786.0/786.0
677.0
565.6
447.0
600/600
600/600
5OO
45O
35O
115
115
115
115
115
3O
3O
3O
3O
3O
--/---/-1654.6
1373.6
1093.4
909.4/902.8
792.0/786.0
680.6
568.6
449.4
700/600
600/600
6OO
5OO
4OO
115
115
115
115
115
3O
3O
3O
3O
3O
--/---/-1689.5
1403.9
1116.7
909.4/902.8
792.0/786.0
715.5
598.9
472.7
700/700
600/600
6OO
6OO
4OO
115
115
115
115
115
30
3O
3O
3O
3O
7OO
6OO
45O
115
115
115
3O
3O
3O
955.9
797.9
631.9
8OO
7OO
5OO
115
115
115
3O
3O
3O
956.4
797.9
631.9
8OO
7OO
6OO
115
115
115
3O
3O
3O
500/500
7OO
6OO
115
115
115
3O
3O
3O
743.7/743.7
872.5
688.9
600/500
8OO
6OO
115
115
115
3O
3O
3O
2196.1/1722.0
1794.0/1400.9
1435.2/1114.3
737.1/748.0
589.0/595.9
471.2/470.3
500/700
450/500
350/400
115
115
115
5O
5O
5O
800/1000
700/ 800
500/ 600
2196.1/2390.5
1794.0/1945.6
1435.2/1551.6
737.1/931.5
589.0/740.6
471.2/587.6
600/500
500/700
400/500
115
115
115
5O
5O
5O
800/1000
700/ 800
500/ 600
2196.1/2450.2
1794.0/1996.9
1435.2/1591.1
737.1/991.2
589.0/791.9
471.2/627.1
600/1000
500/ 700
400/ 600
115
115
115
5O
5O
5O
LEGEND
ICF
MCA
MOCP
CONTROL
Voltage
(1 Ph, 80 Hz)
115
115
115
115
115
--
3O
3O
3O
3O
3O
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range o1non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500 kcmiL
5. Data provided circuit I/circuit 2 where there are two circuits.
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals
is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761 -1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors
required is based on 75 C copper wire.
37
Table 5 -- 30XA140-500
UNIT
30XA
VOLTAGE
VOLTAGE
RANGE
MAIN POWER
SUPPLY
GTY REQD
Electrical Data (High Ambient Temperature
Option)
ICF
MCA
MOCP
618.8
561.9
327.9
282.0
216.2
800
800
450
400
300
(3 Ph, 60 Hz)
MIn
Max
140
200
230
380
460
575
187
207
342
414
518
220
263
418
506
633
1
1
1
1
1
160
200
230
380
460
575
187
207
342
414
518
220
263
418
506
633
2
2
1
1
1
477.9/273.7
434.8/249.1
374.5
321.5
247.0
180
200
230
380
460
575
187
207
342
414
518
220
263
418
506
633
2
2
1
1
1
200
200
230
380
460
575
187
207
342
414
518
220
263
418
506
633
220
200
230
380
460
575
187
207
342
414
518
240
200
230
380
460
575
260
XL
REC FUSE SIZE
MCA and MOCP
957.8
842.9
506.3
422.5
334.3
800/450
760/406
500
450
350
--/---/-1588.4
1317.0
1049.9
934.4/484.6
614.8/423.2
614.4
512.0
405.9
600/350
600/300
45O
400
300
115
115
115
115
115
30
30
30
30
30
422.4/422.4
383.8/383.8
416.3
353.1
271.0
760/700
660/600
500
450
350
--/---/-1363.7
1133.6
901.1
761.4/761.4
664.6/664.8
588.7
493.6
389.1
500/500
450/450
45O
4OO
3OO
115
115
115
115
115
30
30
30
30
30
2
2
1
1
1
477.9/477.9
434.8/434.8
463.4
398.1
305.6
800/800
760/706
600
500
400
--/---/-1677.3
1393.6
1108.5
934.4/934.4
614.6/814.8
703.3
588.6
464.5
600/600
600/600
6OO
45O
35O
115
115
115
115
115
30
30
30
30
30
220
263
418
506
633
2
2
1
1
1
567.4/477.9
516.0/434.8
511.0
439.3
337.3
800/860
800/700
700
600
450
--/---/-1683.8
1399.1
1112.8
946.8/934.4
625.6/814.8
709.8
694.1
468.8
700/600
700/600
6OO
5OO
4OO
115
115
115
115
115
30
30
30
30
30
187
207
342
414
518
220
263
418
506
633
2
2
1
1
1
567.4/555.5
516.0/505.2
543.9
467.8
359.2
800/800
800/800
700
600
450
--/---/-1716.7
1427.6
1134.7
946.8/934.4
625.6/814.8
742.7
622.6
490.7
700/700
700/600
6OO
6OO
4OO
115
115
115
115
115
30
30
30
30
30
380
460
575
342
414
518
418
506
633
1
1
1
616.2
530.6
407.0
800
700
500
2411.8
2000.1
1593.4
952.8
795.1
629.4
7OO
6OO
5OO
115
115
115
30
30
30
280
380
460
575
342
414
518
418
506
633
1
1
1
649.1
559.1
428.9
800
700
600
2444.7
2028.6
1615.3
985.7
823.6
651.3
86O
7OO
5OO
115
115
115
30
30
30
300
380
460
575
342
414
518
418
506
633
1
1
1
721.7
621.2
476.3
1000
800
600
2451.2
2034.1
1619.6
992.2
829.1
655.6
1000
7OO
6OO
115
115
115
30
30
30
325
380
460
575
342
414
518
418
506
633
2
1
1
405.9/406.9
639.9
496.7
600/600
800
600
2201.5/2201.5
2109.4
1677.1
742.6/742.5
904.4
713.1
500/500
8OO
6OO
115
115
115
30
30
30
350
380
460
575
342
414
518
418
506
633
2
1
1
472.0/405.9
696.4
533.8
860/600
800
700
2201.5/2201.5
2109.4
1677.1
742.6/742.5
904.4
713.1
600/500
8OO
6OO
115
115
115
30
30
30
400
380
460
575
342
414
518
418
506
633
2
2
2
399.4/537.4
344.5/462.3
264.0/354.9
660/700
500/600
400/450
2195.0/1710.2
1814.0/1422.2
1450.4/1130.4
736.0/736.2
609.0/617.2
486.4/486.4
500/600
450/600
350/400
115
115
115
50
50
50
380
460
575
380
460
575
342
414
518
342
414
518
418
606
633
418
506
633
2
2
2
2
2
2
465.5/652.2
401.0/561.6
307.2/430.5
465.6/706.7
401.0/610.2
307.2/467.7
760/800
660/800
560/600
700/1000
600/ 800
500/ 600
2195.0/2381.7
1814.0/1974.6
1456.4/1573.7
2195.0/2438.2
1814.0/2023.2
1450.4/1611.0
736.0/922.7
609.6/769.6
486.4/609.7
736.0/979.2
609.0/818.2
486.4/647.0
600/600
600/700
400/500
600/600
500/700
400/600
115
115
115
115
115
115
50
50
50
50
50
50
500
LEGEND
ICF
MCA
MOCP
WD
XL
------
700
700
400
350
250
CIRCUIT
Voltage
(1 Ph, 60 Hz)
115
115
115
115
115
12_.3
1062.5
846.3
450
--
CONTROL
WD
30
30
30
30
30
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-766 amps, 6 conductors are required.
For MCA between 761 -1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation o1 conductors required is based on 75 C copper wire.
5. Wiring for r'_lainfield supply r'_lustbe rated 75 C minirnur'_l. Use copper for all units.
a. Incor'_ling wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcrniL
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 arnps is
3/0 to 500 kcmiL
c. Incoming wire size range of non-fused disconnect with MCA from 600 k) 799.9 arnps
is 1/0 to 500 kcmiL
d. Incoming wire size range of non-fused disconnect with MCA from 600 to 1199.9 amps
is 250 kcrnil to 500 kcmil.
6. Data priwided circuit I/circuit 2 where there are two circuits.
Instantaneous
Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
NOTES:
1. The high ambient option is not available on 30XA080-126 units.
2. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minir'_lum and maximum limits. Maximum
allowable phase ir'_lbalance is: voltage, 2%; amps 10%.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
38
Table 6 -- Compressor and Fan Electrical Data
COMPRESSOR
UNIT
VOLTAGE
V-Hz
30XA
UNIT
SIZE
090
100
110
120
140
160
180
200
220
240
260
280
300
328
380
400
480
800
A
LRA (All Units)
NUMBER
OF COND
B
RLA
LRA (All Units)
---
*Quantity
LRA (All Units)
Standard
Dond. Fans
(080 rpm)
XL
WD
High
Ambient
Temp
Cond. Fans
(1140 rpm)
6.6
6.0
1081.0
940.0
345.0
300.0
130.9
118.9
WD
High
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(850 rpm)
XL
1081.0
940.0
345.0
300.0
130.9
118.9
136.8
124.2
....
....
200
230
6
6
380
6
6.5
3.6
569.0
182.0
68.8
71.9
569.0
182.0
68.8
71.9
....
460
575
6
6
5.5
4.3
3.0
2.4
470.0
376.0
150.0
120.0
59.4
45.4
62.1
47.5
470.0
376.0
150.0
120.0
59.4
45.4
62.1
47.5
....
....
200
8
11.9
6.6
1081.0
345.0
134.3
140.0
1081.0
345.0
134.3
140.0
....
230
380
460
8
8
8
10.8
6.5
5.5
6.0
3.6
3.0
940.0
569.0
470.0
300.0
182.0
150.0
122.0
70.6
61.0
127.1
73.5
63.6
940.0
569.0
470.0
300.0
182.0
150.0
122.0
70.6
61.0
127.1
78.5
63.6
....
....
....
575
8
4.3
2.4
376.0
120.0
46.6
48.6
376.0
120.0
46.6
48.6
....
200
230
8
8
11.9
10.8
6.6
6.0
1357.0
1180.0
437.0
380.0
148.4
134.9
154.8
140.7
1357.0
1180.0
437.0
380.0
148.4
134.9
154.8
140.7
....
....
380
460
8
8
6.5
5.5
3.6
3.0
714.0
590.0
230.0
190.0
78.3
67.5
81.6
70.4
714.0
590.0
230.0
190.0
575
200
8
8
4.3
11.9
2.4
6.6
472.0
1357.0
152.0
437.0
51.3
180.9
53.5
190.7
472.0
1357.0
152.0
437.0
230
380
8
8
10.8
6.5
6.0
3.6
1180.0
714.0
380.0
230.0
164.7
95.4
173.6
100.6
1180.0
714.0
460
8
5.5
3.0
590.0
190.0
82.0
86.4
575
200
8
8
4.3
11.9
2.4
6.6
472.0
1357.0
152.0
437.0
62.9
180.9
230
380
8
8
10.8
6.5
6.0
3.6
1180.0
714.0
380.0
230.0
460
575
8
8
5.5
4.3
3.0
2.4
590.0
472.0
190.0
152.0
200
10
11.9
6.6
2162.0
230
380
10
10
10.8
6.5
6.0
3.6
1880.0
1138.0
460
575
10
10
5.5
4.3
3.0
2.4
200
230
6/4
6/4
11.9
10.8
380
460
10
10
6.5
5.5
FANS*
RLA
FLA
Standard
Cond. Fans
(880 rpm)
XL
136.8
124.2
78.8
81,6
....
67.5
70.4
....
51.3
148.4
53.5
154.8
....
....
380.0
230.0
134.9
140.7
....
78.8
81,6
....
590.0
190.0
67.5
70.4
....
66.3
190.7
472.0
1357.0
152.0
437.0
51.3
180.9
53.5
190.7
....
....
164.7
95.4
173.6
100.6
1180.0
714.0
380.0
230.0
164.7
95.4
173.6
100.6
....
....
82.0
62.9
86.4
66.3
590.0
472.0
190.0
152.0
82.0
62.9
86.4
66.3
....
....
690.0
280.8
293.9
1357.0
437.0
148.4
154.8
....
600.0
363.0
255.2
147.7
267.2
154.6
1180.0
714.0
380.0
230.0
134.9
140.7
....
78.8
81,6
....
940.0
752.0
300.0
240.0
127.6
97.5
133.6
102.0
590.0
472.0
190.0
152.0
67.5
51.3
70.4
53.5
....
....
6.6
6.0
2714.0
2360.0
863.0
750.0
325.2
296.0
340.6
310.0
1357.0
1180.0
437.0
380.0
180.9
164.7
190.7
173.6
....
....
3.6
3.0
1428.0
1180.0
454.0
375.0
171.3
147.6
179.4
154.6
714.0
590.0
230.0
190.0
95.4
82.0
100.6
86.4
....
....
575
10
4.3
2.4
944.0
300.0
112.9
118.2
472.0
152.0
62.9
66.3
....
200
230
6/6
6/6
11.9
10.8
6.6
6.0
2162.0
1880.0
690.0
600.0
280.8
255.2
293.9
267.2
2162.0
1880.0
690.0
600.0
280.8
255.2
293.9
267.2
....
....
380
460
12
12
6.5
5.5
3.6
3.0
1138.0
940.0
363.0
300.0
147.7
127.6
154.6
133.6
1138.0
940.0
363.0
300.0
147.7
127.6
154.6
138.6
....
....
575
200
12
6/6
4.3
11.9
2.4
6.6
752.0
2714.0
240.0
863.0
97.5
325.2
102.0
340.6
752.0
2714.0
240.0
863.0
102.0
....
325.2
340.6
....
230
6/6
10.8
6.0
2360.0
750.0
296.0
310.0
2360.0
750.0
296.0
310.0
....
380
460
12
12
6.5
5.5
3.6
3.0
1428.0
1180.0
454.0
375.0
171.3
147.6
179.4
154.6
1428.0
1180.0
454.0
375.0
171.3
147.6
179.4
154.6
....
....
575
200
12
7/6
4.3
11.9
2.4
6.6
944.0
2714.0
300.0
863.0
112.9
387.3
118.2
406.6
944.0
2714.0
300.0
863.0
112.9
325.2
118.2
340.6
....
....
230
380
7/6
13
10.8
6.5
6.0
3.6
2360.0
1428.0
750.0
454.0
352.3
204.2
369.8
214.3
2360.0
1428.0
750.0
454.0
296.0
171.3
310.0
179.4
....
....
97.6
WD
High
Ambient
Temp
Cond. Fans
(1140 rpm)
Standard
Cond. Fans
(080 rpm)
460
575
13
13
5.5
4.3
3.0
2.4
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
1180.0
944.0
375.0
300.0
147.6
112.9
154.6
118.2
....
....
200
7/6
11.9
6.6
2714.0
863.0
387.3
406.6
2714.0
863.0
387.3
406.6
....
230
380
7/6
13
10.8
6.5
6.0
3.6
2360.0
1428.0
750.0
454.0
352.3
204.2
369.8
214.3
2360.0
1428.0
750.0
454.0
352.3
204.2
369.8
214.3
....
....
460
575
13
13
5.5
4.3
3.0
2.4
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
....
....
380
460
15
15
6.5
5.5
3.6
3.0
2143.0
1770.0
684.0
565.0
277.9
240.4
293.0
253.5
1428.0
1180.0
454.0
375.0
171.3
147.6
179.4
154.6
....
....
575
15
4.3
2.4
1416.0
452.0
183.7
193.7
944.0
300.0
112.9
118.2
....
380
460
16
16
6.5
5.5
3.6
3.0
2143.0
1770.0
684.0
565.0
277.9
240.4
293.0
253.5
1428.0
1180.0
454.0
375.0
204.2
176.1
214.3
184.9
....
....
575
380
16
16
4.3
6.5
2.4
3.6
1416.0
2143.0
452.0
684.0
183.7
330.8
193.7
350.3
944.0
1428.0
300.0
454.0
134.8
204.2
141.5
214.3
....
....
460
575
16
16
5.5
4.3
3.0
2.4
1770.0
1416.0
565.0
452.0
285.6
218.2
302.4
231.0
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
....
....
380
460
9/9
18
6.5
5.5
3.6
3.0
2143.0
1770.0
684.0
565.0
277.9
240.4
293.0
253.5
2143.0
1770.0
684.0
565.0
277.9
240.4
293.0
253.5
....
....
575
18
4.3
2.4
1416.0
452.0
183.7
193.7
1416.0
452.0
183.7
193.7
....
380
460
9/9
18
6.5
5.5
3.6
3.0
2143.0
1770.0
684.0
565.0
330.8
285.6
350.3
302.4
2148.0
1770.0
684.0
565.0
277.9
240.4
293.0
253.5
....
....
575
380
18
8/12
4.3
6.5
2.4
3.6
1416.0
1428.0
452.0
454.0
218.2
204.2
231.0
214.3
1416.0
1428.0
452.0
454.0
183.7
204.2
193.7
214.3
....
293.0
2143.0
277.9
293.0
460
575
8/12
8/12
5.5
4.3
3.0
2.4
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
1180.0
944.0
375.0
300.0
176.1
134.8
184.9
141.5
253.5
193.7
1770.0
1416.0
240.4
183.7
253.5
193.7
380
8/14
6.5
3.6
1138.0
363.0
147.7
154.6
2143.0
684.0
330.8
350.3
2143.0
684.0
330.8
350.3
460
575
8/14
8/14
5.5
4.3
3.0
2.4
940.0
752.0
300.0
240.0
127.6
97.5
133.6
102.0
1770.0
1416.0
565.0
452.0
285.6
218.2
302.4
231.0
1770.0
1416.0
565.0
452.0
285.6
218.2
302.4
231.0
380
460
8/14
8/14
6.5
5.5
3.6
3.0
1428.0
1180.0
454.0
375.0
204.2
176.1
214.3
184.9
2148.0
1770.0
684.0
565.0
330.8
285.6
350.3
302.4
2143.0
1770.0
684.0
565.0
330.8
285.6
350.3
302.4
575
8/14
4.3
2.4
944.0
300.0
134.8
141.5
1416.0
452.0
218.2
231.0
1416.0
452.0
218.2
231.0
LEGEND
LRA
RLA
C
RLA
High
Ambient
Temp
Cond. Fans
!1140 rpm !
11.9
10.8
(3 Ph,
60 Hz)
080
CONDENSER
FANS
Locked Rotor Amps
Rated Load Amps
of fan motors for incoming
WD
XL
--
NOTES:
1.
For 30XA080-350
units with dual power supply, main power supply 1 uses refrigerant
circuit A components to calculate MCA and MOOR Main power supply 2 uses refrigerant circuit B components to calculate MCA and MOOR
2.
30XA400-500 units have dual power supplely..Main power supply 1 uses refrigerant circuit C components to calculate MCA and MOOR Main power supply 2 uses refrigerant
circuit A and B components to calculate MCA and MOOR
Wye Delta
Across-the-Line
power supply Circuit 1/Circu9
2.
39
CARRIER COMFORT
NETWORK@
COMMUNICATION
BUS WIRING (See Fig. 24) -- The communication
bus wiring
is a shielded, 3-conductor cable wifll &'ain wire and is field
supplied and instCdled in the field.
3. Connect the red wire to (+) terminal on TB3 of the plug,
the white wire to COM terminal, and the black wire to the
(-) terminal.
4. The RJI 4 CCN connector on TB3 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running service tool).
The system elements tue connected to the communication
bus in a &fisy chain arrangement.
The positive pin of each
system element communication
connector must be wired to the
positive pins of the system elements on either side of it. This is
also required for the negative and signal ground pins of
each system element. Winng connections for CCN (Carrier
Comfort Network) should be made at TB (terminal block) 3.
Consult the CCN Contractor's Manual for further information.
See Fig. 24.
NOTE: Conductors
and &'ain wire must be 20 AWG
(American Wire Gage) minimum
stranded, tinned coppel:
Individual conductors
must be insulated with PVC, PVC/
nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester
100% foil shield and an outer jacket of PVC, PVC/nylon,
chrome vinyl, or Teflon with a minimum opemfing temperature range of-4 F (-20 C) to 140 F (60 C) is required. See
Table 7 for a list of manufacturers
that produce CCN bus
wiring that meet these requirements.
Table 7 -- CON Communication
IMPORTANT:
A shorted CCN bus cable will prevent
some routines from running and may prevent the unit
from starting. If abnormal conditions occur, disconnect
the machine from the CCN. If conditions
return to
normal, check the CCN connector and cable. Run new
cable if necessary. A short in one section of the bus
can cause problems with all system elements on the
bus.
NON-CCN COMMUNICATION
WIRING -- The 30XA units
offer severtd non-CCN translatoL's. Refer to the separate installation instructions for additional wiring steps.
FIELD CONTROL
OPTION WIRING -- Install field control
wiring options. Some options, such as 4 to 20 mA demand
limit that requires the Energy Management
Module, may
require that accessories
be installed first (if not factory
installed) for terminal connections.
DUAL CHILLER LEAVING WATER SENSOR --If the dual
chiller algorithm is used and the machines are installed in parallel, an additional chilled water sensor must be installed for
each chillec Install the wells in the common leaving water
header See Fig 25. DO NOT relocate the chiller's leaving
water thermistoLs. They must remain in place for the unit to
operate properly.
The thermistor well is a 1/4 in. NPT fitting for securing the
well in the piping. The piping must be drilled and tapped for
the well. Select a location that will allow for removal of the
thermistor without any restrictions.
Bus Wiring
PART NUMBER
MANUFACTURER
Regular Wiring
1895
A21451
8205
D6451
M13402
6130
Alpha
American
Belden
Columbia
Manhatten
Quabik
Plenum Wiring
A48301
884421
M64430
it is important when connecting to a CCN communication
bus that a color coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables containing different colored wires. At each system element, the shields
of its communication
bus cables must be tied togethel: If the
communication
bus is entirely within one building, the resulting continuous shield must be connected to a ground at one
point only. If the communication
bus cable exits from one
building and enters another, the shields must be connected to
grounds at the lightning suppressor in each building where the
cable enters or exits the building (one point per building only).
To connect the unit to the network:
Once the well is inserted, install the thermistors. Insert the
thermistor into the well until the o-ring reaches the well body.
Use the nut on the thermistor to secure the thermistor in place.
Once the thermistor is in place, it is recommended
that a
thermistor wire loop be made and secured with a wire tie to the
chilled water pipe. See Fig. 26.
For dual chiller control a CCN bus must be connected
between the two modules. See the Carrier Comfort Network
Communication
Bus Wiring section for additional information.
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (-) conductors. Substitute appropriate colors for different colored cables.
--MZZZ3
o[21121
LEN
CCN
oE3E3
LEN
CCN
TO NEXT
DEVICE
LEGEND
CCN
LEN
---
Carrier Comfort Network
Local Equipment Network
Fig. 24 -- TB3 -- CON Wiring
4O
2.315 in._
REMOVAL
Fig. 25 -- Dual Leaving
Water
WELL
BODY.
WIRE TIE\
\
The GFI-CO
receptacle.
LOOP
THERMISTOR
WIRE
AND SECURE
TO CHILLED
WATER
Well
UNIT SECURITY/PROTECTION
ACCESSORIES
-- For
applications
with unique security and/or protection requirements, several options are available
for unit protection.
Security grilles and hail guards are available. Contact a local
Carrier representative for more details. For inst_fllation details,
refer to separate inst_dlation instructions
supplied with the
accessory package.
COMMUNICATION
ACCESSORIES
-- A number of communication
options are available to meet any requirement.
Contact a local Carder representative
for more details. For
installation details, refer to sep_u'ate installation instructions
supplied with the accessory package.
SERVICE OPTIONS -- Two accessories are available to aid
in servicing 30XA units: a ground fault convenience
outlet
(GFI-CO) and a remote service port.
INSERT THERMISTOR
UNTIL
O-RING MEETS THE
THERMISTOR
Thermistor
is a convenience
outlet with a 4-amp
The remote service port is housed in a weather-proof enclosure with a communication
port to plug in the Navigato( TM
device.
PIPE
Step 5 -- Install Accessories -- A number of accessories are available to provide the following optional features
Contact a local Carrier representative
for more
installation details, refer to sepm'ate installation
supplied with each accessory package.
CONTROL
TRANSFORMER
-- The control
accessory eliminates the need for a separate power
(for details, refer to file Controls
shipped with the unit).
Step 6 -- Leak Test Unit -- The
Fig. 26 -- Dual Leaving Water Thermistor
and Troubleshooting
•
•
•
dettfils. For
instructions
transformer
supply.
guide
30XA
units
are
shipped with a complete operating charge of R-134A (see
Tables IA and IB) and should be under sufficient pressure to
conduct a leak test.
ENERGY MANAGEMENT
MODULE -- The Energy Management Module is used for any of the following types of
temperatme reset, demand limit and ice features:
•
GFI
=
4 to 20 mA inputs for cooling set point reset and capacity
limit 0equires field-supplied
4 to 20 mA generator)
0 to 10 v output for percentage total capacity running
24 v discrete outputs for shutdown and running relays
10k space temperature
input
I
R-134a only. DO NOT USE ANY OTHER refrigerIMPORTANT:
ant
in these units.These units are designed for use with
Pedorm a leak test to ensure that leaks have not developed
during unit shipment. Dehydration of the system is not required
unless the entire refrigerant charge has been lost. There are
several O-ring face seal fittings utilized in the oil line piping. If
a leak is detected at any of these fittings, open the system and
inspect the O-ring sudace for foreign matter or damage. Do not
reuse O-rings. Repair any leak found following good lefrigeration practice.
Discrete inputs for occupancy
override, demand limit
switch 2 (step 1 demand limit is wired to the base board,
requires field-supplied
dry contacts), remote lockout switch
and ice done switch (requires field-supplied dlT contacts)
REMOTE ENHANCED
DISPLAY -- For applications where
remote monitoring of the equipment is required; the remote
enhanced display provides an indoor display, capable of monitoring any equipment
on the Carrier Comfort Network®
(CCN) bus. A CCN bus is required.
LOW AMBIENT TEMPERATURE
OPERATION -- If outdoor ambient operating temperatures below 32 F (Oo C) are
expected, refer to separate installation instructions for lowambient operation using the low ambient temperature head
pressure control accessory.
M[NIMUM LOAD ACCESSORY
-- Contact a loc_fl Carrier
representative for more details if a minimum load accessory is
required for a specific application. For installation details, refer
to sepm'ate inst_fllation instructions supplied with the accessory
package.
DO NOT OVERTIGHTEN
THESE FITFINGS.
tightening will result in O-ring dmnage.
Step 7 -- Refrigerant
Over-
Charging
DEHYDRATION
-- Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for
details. Do not use compressor to evacuate system.
41
I
I
REFRIGERANT
CHARGE
IMPORTANT:
Theseunitsm'edesigned
for usewith ]
R-134a only. DO NOT USE ANY OTHER
these units.
The liquid chmging method is recommended
charging or when additional charge is required.
refrigerant
in
I
DO NOT OVERCHARGE system. Overcharging results in
higher discharge pressure with higher cooling fluid consumption, possible compressor damage, and higher power
consumption.
for complete
The 30XA units ale shipped fiom the factory with a full
chmge of R-134a. The unit should not need to be charged at
installation unless a leak was detected in Step 6 -- Leak Test
Unit section. If dehydration and recharging is necessmy, use
industry standard practices or refer to Carrier Standard Service
Techniques Manual as required.
When charging, circulate water through the cooler at all
times to prevent freezing. Freezing damage is considered
abuse and may void the Carrier warranty.
42
Copyright 2005 Carrier Corporation
Manufacturer reserves the right to discontinue,
PC 903
Catalog
No. 533-00068
or change at any time, specifications
Printed in U.S.A.
or designs without notice and without incurring obligations.
Form 30XA-1SI
Pg 44
6-05
Replaces:
New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 44 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 13:06:02 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools