CARRIER Evaporator Coils Manual L0521268
AQUAFORCE 30XA080-500 L0521268
User Manual: CARRIER CARRIER Evaporator Coils Manual CARRIER Evaporator Coils Owner's Manual, CARRIER Evaporator Coils installation guides
Open the PDF directly: View PDF .
Page Count: 44
Download | |
Open PDF In Browser | View PDF |
AQUAFORCE TM 30XA080-500 Air-Cooled Liquid Chillers Installation Instructions CONTENTS SAFETY Page SAFETY CONSIDERATIONS ...................... 1 INTRODUCTION .................................. 1 INSTALLATION ................................ 2-42 Storage .......................................... 2 Step 1 -- Inspect Shipment ...................... 2 Step 2 -- Place, Mount and Rig Unit ............. 2 • PLACING UNIT • MOUNTING UNIT • RIGGING UNIT Step 3 -- Cooler Fluid and Drain Piping Connections .................................. 29 • GENERAL • DUAL CHILLER CONTROL • COOLER FLUID, VENT. AND DRAIN • COOLER PUMP CONTROL • BRINE UNITS • WATER TREATMENT • PREPARATION FOR YEAR-ROUND OPERATION • PREPARATION FOR WINTER SHUTDOWN Step 4 -- Make Electrical Connections .......... 34 • POWER SUPPLY • FIELD POWER CONNECTIONS • FIELD CONTROL POWER CONNECTIONS • CARRIER COMFORT NETWORK COMMUNICATION BUS WIRING • NON-CCN COMMUNICATION WIRING • FIELD CONTROL OPTION WIRING • DUAL CHILLER LEAVING WATER SENSOR Step 5 -- Install Accessories .................... 41 • ENERGY MANAGEMENT MODULE • REMOTE ENHANCED DISPLAY • LOW AMBIENT TEMPERATURE OPERATION • MINIMUM LOAD ACCESSORY • UNITSECURITY/PROTECTION ACCESSORIES • COMMUNICATION ACCESSORIES • SERVICE OPTIONS • CONTROL TRANSFORMER Step 6 -- Leak Test Unit ......................... 41 Step 7 -- Refrigerant Charging .................. 41 • DEHYDRATION • REFRIGERANT CHARGE Manufacturer Installing, starting up, and servicing this equipment can be haz_u'dousdue to system pressures, electric_d components, and equipment location. Only trained, qu_difiedinst_dlers and service mechanics should inst_dl,stall up, and service this equipment. When working on the equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment. • Follow all safety codes. • Wear safety glasses and work gloves. • Use care in handling, rigging, and setting bulky equipment. Electfic_d shock can cause persomd injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Ntg all disconnect locations to _dert others not to restore power until work is completed. IMPORTANT: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with these instructions may cause radio interference. It has been tested and found to comply with the limits of a Class A computing device as defined by FCC (Federal Communications Commission, U.S.A.) regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment. INTRODUCTION These instructions cover installation of 30XA080-500 aircooled liquid chillers with electronic controls and units with factory-installed options (FIOPs). See Fig. 1. reserves the right to discontinue, or change at any time, specifications PC 903 Catalog No. 533-00068 Printed in U.S.A. CONSIDERATIONS or designs without notice and without incurring obligations. Form 30XA-1SI Pg 1 6-05 Replaces: New INSTALLATION Storage -- If the unit is to be stored for a period of time before installation or start-up, be sure to protect file machine from construction dirt. Keep protective shipping covers in place until file machine is ready for installation. Step 1 -- Inspect Shipment -- Inspect unit for &image upon arrival. If &image is found, immediately file a claim with the shipping company. Step 2 -- Place, Mount, and Rig the Unit -- When considering a location for the unit, be sure to consult NEC (National Electrical Code, U.S.A.) and/or local code requirements. Allow sufficient space for airtlow, wiring, piping, and service. See Fig. 2-10. NOTE: To facilitate refrigerant vent piping, all units have fusible plugs with 1/4 in. SAE (Society of Automotive Engineers) flares and pressure reliefs with 3/4 in. NPT fittings (if required by locfd codes). PLACING UNIT--Ix_cate the unit so that the condenser airtlow is unrestricted both above fred on the sides of the unit. Airflow find service clefuances me 6 fl (1.8 m) around file unit. Acceptable clearance on the cooler connection side or sides or ends without control boxes can be reduced to 3 ft (1 m) without sacrificing performance as long as the remaining three sides me unrestricted. Acceptable clearance on the side wifll a control box cfm be reduced to 4 fl (1.3 m) due to NEC regulations, without sacrificing performance as long as the remaining three sides am unrestricted. Provide ample room for servicing find removing file cooler See Fig. 2-10 for lequimd clemances. Ix)cffl codes for clem'ances take precedence over the manufacturer's mcommenc_kLtions when locfd codes cfdl for greater clearances. If multiple units am installed 10 fl (3 m) between the sides maintain proper airflow er air recimulation. at the stone site, a separation of the machines is required and minimize the chances of to of condens- MOUNTING UNIT -- The unit may be mounted on a level pad directly on the base rails, on a raised mounting rail m'ound the unit, or on vibration isolation springs. For all units, ensure placement area is strong enough to suppori unit operating weight. See Tables IA and lB. Mounting holes are provided for securing the unit to the pad, mounting rail or vibration isolation springs. Bolt the unit securely to pad or rails. [f vibration isolatol.'s (field-supplied) are required for a particular instffllation, refer to unit weight distribution in Fig. 11 to aid in the proper selection of isolators. The 30XA units can be mounted directly on spring isolators. 30XA T 30XA - Air-Cooled AquaForce TM Chiller A 200 / Packaging/Security Options L - Coil Face Shipping Protection (CFSP) - CFSP, Skid - Skid, Top Crate, Bag - CFSP, Coil Tdm Panels - CFSP, Skid, Coil Trim Panels, Shipping Skid, Top Crate, Bag, Coil Trim Panels ,1 Design Series Unit 080 090 f00 110 120 Sizes 140 240 160 260 180 280 200 300 220 325 350 400 450 500 Controls/Communication Options - - None 0 - EMM I - Remote Service Ports, GFI-CO 2 - EMM. Remote Service Port, GFI-CO 7 - BACnet Tianslator 8 - BACnet Translator. EMM 9 - BACnet Translator, Remote Service Port, GFI-CO B - BACnet Translator. EMM, Remote Service Port, GFI-CO H - LON Tlanslator J - LON Translator. EMM K - LON Tianslator, Remote Sewice Port, GFI-CO L LON Translator, EMM, Remote Service Port, GFI-CO Voltage 1 - 575-3-60 2 - 380-3-60 4 - 230-3-60 6 - 460-3-60 7 200-3-60 TM Condenser Coil/High Ambient Options 6 Aluminum Fin/Copper Tube, High Ambient Temperature, Compressor Enclosures 8 Aluminum Pie-Coat Fin/Coppel Tube, High Ambient Tempelatule, Compressor Enclosures 9 Alumint.lm E-Coat Fin/Coppel Tube, High Ambient Temperature, Compressor Enclosures F Aluminum Fin/Copper Tube, Standard Ambient Temperature, Compressor Enclosures H Aluminum Pie-Coat Fin/Coppel Tube, Standard Ambient Temperature, Compressor Enclosures J - Aluminum E-Coated Fin/Copper Tube, Standard Ambient Temperature, Compressor Enclosures Electrical Options - - Single Point Power, XL Terminal Block, No Control Transformer o - Single Point Power, Wye-Delta, Telminal Block, No Contlol Transformel 3 - Dual Point Power, XL Terminal Block, No Contlol Transformel 4 - Dual Point Poweh Wye-Delta, Terminal Block, No Conhol Tlansformel 7 - Single Point Power, XL Disconnect, No Control Transformer 8 - Single Point Power, Wye-Delta. Disconnect, No Control Tlansformer C - Dual Point Powel, XL Disconnect, No Contlol Transformer D - Dual Point Power, Wye-Delta, Disconnect No Contlol Transformel R - Single Point Power, XL Telminal Block, Control Transformer J - Single Point Power, Wye-Delta, Telmina] Block, Control Tlansformer M - Dual Point Power, XL Terminal Block, Control Transformer R - Dual Point Poweh Wye-Delta, Terminal Block, Contlol Transformer B - Single Point Power, XL Disconnect, Contlol Transformer S - Single Point Power, Wye-Delta. Disconnect, Control Tlansformel W- Dual Point Powel, XL Disconnect, Control Transformer Not Used Cooler/Brine O- Integral 3 - Integral 5 Integral B - Integral F - Integral H - Integral Options Coolel Coolel, Minus One Pass Coolel, Plus One Pass Cooler, Brine Cooler, Minus One Pass, Brine Cooler. Plus One Pass. Brine X ----- Energy Management Module Ground Fault Interrupting Convenience Local Operating Network Across-the-Line Starter Outlet Fig. 1 -- AquaForce Control Transformer Refrigeration Circuit Options - - None I - Suction Service Valves 2 - Low Ambient Temperature Head Pressure Contlol 5 Suction Service Valves, Low Ambient Tempelatule LEGEND EMM GFI-CO LON XL Dual Point Power, Wye-Delta, Disconnect TM Chiller Model Number Designation Head Pressure Control NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection. 3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power and standard twopass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. 1.50 DIA. RIGGING HOLE Control Box All Voltages_ 3.35 /_(_._'8k_koLts] fhOor lemaipnPiOg_r entry 1.75 DETAIL "A" [4il MOUNTING PLATE 0.875 CONTACT SURFACE TYPICAL 4 PLACES DIA.[22.2] MOUNTING HOLE \ _ I I I 1;1 oR - Cooler Tube __ .... L........... ,,_ 4_ 5.0 MOUNT'NG PLATE__ _-- "_1 -- I!1 t [127] / -- I-............................... _ I 109.0. II II 88.04 [2236] / 5.83 I _ II L .................................... 3.93 [1oo] ! [141 '_ _ [1670] ..... //J I 7.88 [200] Piping Entrance TOP VIEW Fig. 2 -- 30XA080 Air-Cooled Liquid Chiller Dimensions Optional Non-fused Control Box All Voltages_ 90.55 [2300] DisplayLocation (380,460_575v) 90.55 5" Victaulic 5" Victaulic 41.1 [_[1044 © t- Leaving Entering Water_ Water _ I [2OO] 19.06 [1729] 68.06 88.04 [2236] 88.04 [2236] RIGHT END VIEW LEFT END VIEW 8.9 [226] Control Box All Voltages 90.55 3/8 NPT [ I Cooler Drain _____ 3/8 NPT H --!_ [2714] 19.06 [484t [2i001 1 109.03 Mounting Holes_ Rigging Holes (See Detail A) 121.17 [3078] [409] [2769] 141.22 5" Victaulic g Water [3587] Entering [85] Water FRONT VIEW 3/4 NPT Relief Conn. Female Fig. 2 -- 30XA080 Air-Cooled Liquid Chiller Dimensions (cont) 1.50 DIA. [38.1]_ RIGGING HOLE Control Box All Voltages_ \ \ 1.75 DETAIL MOUNTING "A" PLATE \ 3.35 7/8" \ T I for main power entry I 23.72 /_ 0.875 DIA.[22.2] _ MOUNTING HOLE knockouts CONTACT SURFACE TYPICAL 4 PLACES (7,48" [190mm] hole spacing) [6_21 A 1.31 68.06 [331 I I 1 Cooler -Service [- ...... MLOA_NTING ___ \ _ 5.0 [127I ......... -- 3.93 [100] -- _ 1 I Area [1729] , Tube 88.04 [2236] _.J ._-/ .......................... ................ iiii .....• ///, B [2769] 120.85 [3070] 7.88 188.2 [200] [4780] _Piping TOP VIEW NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection. 3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power and standard two-pass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. Fig. 3 -- 30XA090-120 Air-Cooled 30XA090UNIT 100 110 120 Liquid Chiller Dimensions 44.11Al120)( 44.11 (1120) 44.11 (1120) 44.11 (1120) 86,83 87.22 87.62 87.12 B(2208) (2215) (2226) (2213) Entrance 0 ptional Non-fused Disconnect Handle 5" Victaulic Leaving Water Control Box All Voltages 90.55 Displa_ Location {380,480,575v) 5" Victaulic [2300] 99.55 © 19.05 [17291 L 88.04 [2236] 88.04 [2236] RIGHT LEFT END VIEW END VIEW Female 8.9 [226] --4 Control Box All Voltages 90.55 3/8 NPT 3/8 NPT ] 19.06 [2i00] [4841 Mounting Rigging Holes (See Detail A) [1982] [3070] 188.2 [4780] FRONT VIEW Fig. 3 -- 30XA090-120 Air-Cooled Liquid Chiller Dimensions (cont) 5" Victaulic Leaving Water 5" Victaulic Entering Water NOTES: 1. Unit must have clearances as fellows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection. 3. 8/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power, or dual-point power on a 30XA160 (200, 230 v) unit with standard condenser fans, and standard twopass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. 7.23 [182] / Control Box, incoming power supply (380,460,575v) / Control Box, incoming power supply (200,280v) / __/ 1 40 /i _" [1017] it ................. / i J F ........... i/ "--'1 " 161 8 04 Cooler Tube Service Area 2.48 [63] J (Zyp,cal) \ I- ............. _ _ircuit _ [2286] 1 _ O_rou_t 2 (30XA_ 60 on _y) --'_-- .............. i i ............................... 30XA140UNIT 160 44.63A1(134) 44.61 (1133) 5.84 [148]-- 115.88 B(2943) 115.64(2937) -- [2769] 121.49 [3086] 235.24 [5975] _Piping Entrance TOP VIEW co Control Box (all voltages) 7/8" knockouts for main for 380.460.575v 4 spacing) f'fi\ 5" Victaulic Leaving Water. /'fi-\ / / "Kl'_ / /'r<\ 90.55 90.55 [2800] [2300] /- Entering Water 21.28 10.58 , [269] 23.62 5" Victaulic i j o i 69.14 [1756] i-o_l _ 88.04 [2236] RIGHT on,y ,J Display Disconnect --Non-fused " [600] [541] i J _" o o 111.58 [2834] Box (200/230V) 235.24 [5975] 74 Location BACK VIEW Fig. 4 -- 30XA140,160 Air-Cooled -'_ ¢ J END VIEW Handle Liquid Chiller Dimensions [188o] 7 3/4NPT Relief Conn. Female 8,9 [226] $5" Victaulic /-5" Leaving Victaulic Water Entering Water Control Box incoming power"-. supply (200,230v) (200,230v) 90.55 7/8"knockoutsfor 90.55 [2300] (5,55" [141 mm] hole spacing) 3/8 NPT 41,1 [--[1C 22,2 [565] O [2i00t 3/8 NPT 1 Control Box (200,230,380, 460,575v) 109.03 [2769] Mounting 88.04 [2236] Rigging Holes (See Detail A) [3,23] LEFT END VIEW 33.96 [863] 121.49 [3086] 235.24 [5975] FRONTVIEW 7,2 [182] 1.50 DIA.[38.1]_ RIGGING HOLE 1.75 4i] DETAIL MOUNTING CONTACT 0.875 DIA.[22.2] MOUNTING HOLE \ \ l I I TYPICAL "A" PLATE SURFACE 4 PLACES 1,31 [33] ! 1 5.0 [127] -- 3,93 [100] 7,88 [200] Fig. 4 -- 30XA140,160 Air-Cooled Liquid Chiller Dimensions (cont) 58.08 [1475] NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection. 3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power, or dual-point power on a 30XA180,200 (200, 230 v) unit with standard condenser fans, and standard twopass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. S power supply (200,230v) 7.23 [1821 Control _83 I 4O [10171 I 2.48 [63] I1 (Typical) \ _ [72] / / !.................... Y T_ 575v) Box, incoming / ° J Circuit 1 Circuit 2 (30XA160 only) I .r [2236] [_°8126[88.04 777777 I i Control Box, incoming power supply (380,460 61.6 .............. [1666] -- 30XA UNIT A B 180 200 46.12 (1171) 46.15 (1172) 143.04(3633) 142.97 (3631) [2779] B 177.65 [4512] _ 282.22 [71681 Piping Entrance TOP VIEW 7 Control Box (all voltages) 7/8" knockouts for main power entry 380, 460, 575v (5.55" [141 ram[ hole spacing) \ \ I_TT] IIII II_111 II /"4"\ -Control power entry (all voltages) / Display Location / / "K \_ 4"fi-\ / /"K \ / ! "K \ 90.55 6" Victaulic Leaving Water-- [2300[ 6" Victaulic Entering Water- I ...... 23.62 22148. , [12183 [5_1I r_ 1 70.16 [6iO] __ Control Box [1782[ 88.04 [22361 RIGHT END VIEW OptionalNon-fused DisconnectHandle 158.6 [4028[ (380,460,575v) 282.2 [7168] 12.7 [323[ BACK VIEW Fig. 5 -- 30XA180,200 Air-Cooled Liquid Chiller Dimensions Control Box (200,230v incoming ] power supply connection) 122 [3099[ g Water Cooler Vent3/8 NPT -- 3/4 NPT Relief Conn. Female g Water Optional Non-fused Disconnect Handle Control Box, incoming Power Supply (200, 230v) Control Box (200,230v) 7/8'.' knockouts for_ main power entry 90.55 (5.55" [141 mm] hole spacing) [2300] \1 © 41.1 22171044i [8_81 90.55 [2300] I '°_ / J.___F Mountin( Rigging (See Detail A) Control Box _ (200,230,380, 460,575v) 12.7 [323] [489] / 58.08 __. [1475] i 177.65 i 33.97 78.0___ [863] [1982] [4512] / % /\// €, 28222 [7168] LEFT END VIEW FRONT VIEW 1,50 DIA.[3&I RIGGING HOLE 1.75 [4 i] DETAIL "A" MOUNTING CONTACT 0.875 DIA.[22.2] _ I MOUNT, NGHO_ _ MOUNTING PLATE__ I ____.__'___.................. TYPICAL PLATE SURFACE 4 PLACES 1.31 [33] I F [127] 5.0 7.88 [2OO] Fig. 5 -- 30XA180,200 Air-Cooled Liquid Chiller Dimensions (cont) / [571] 78.02 [1982] NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection. 3. 3/6-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power, or dual-point power on a 30XA200,240 (200, 230 v) unit and standard condenser fans, and standard two-pass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. _ /_Control /p Box, incoming ...... r-'_ ............. ! r-............. i ii / Control Box, incoming power supply (200,230, 380,460,575v) pply (200,23_" "-'f i @ 70.16 [1762] 8_ .... [2; 36] c°r%T2r = 108.6 /////o/ [2758] B 224.65 [5706] 30XA UNIT A B 220 240 46.17 (1173) 46.23 (1174) 171.42 (4354) 170.83 (4339) _o_ o_ [8363] Piping Entrance TOP VIEW 7/8" knockouts for main power entry(5.55" [141 mm] hole spacing) =Control Box (200/230v only) Display Location Control Box460,575v) 9C!55 6" Victaulic Leavinc 6" Victaulic Enterin( f-- 22.46 [2}00] [5 140.14[3560] Box Incoming power, 380,460.575v [2236] Circuit 11(200.230v) 329.26 205.6 [5222] [8363] 170 [4318] RIGHT END VIEW BACK VIEW Fig. 6 -- 30XA220,240 Air-Cooled Liquid Chiller Dimensions 3/4NPT Relief Conn. Female 3/8NPT 90.55 [2300] © I .... ..... 6"Victaulic Entering Water 90.55 [2300] Control_ i Boxes ...... o i i U [1475] 88,04 - 33,97 [863]- [2236]- 224.65 (See Detail gWater , 109.03 [2769] 329.26 [8363] 33,96 [863] [5706] A) LEFT END VIEW FRONT VIEW 1,50 DIA. [38.1]_ RIGGING HOLE \ \ 1.75 DETAIL MOUNTING CONTACT 0.875 DIA.[22.2] \ MOUNTING HOLE TYPICAL _ "A" PLATE SURFACE 4 PLACES I 1 5.0 MOU NT'N G PLATE _---__ -_ "_!_-iI [ --1 [127] _t / -- 3,93 [100] 7.88 [200] Fig. 6 -- 30XA220,240 Air-Cooled Liquid Chiller Dimensions (cont) -- 58.08 [1475]-- NOTES: 1, Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface, 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in. flare connection. 3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with singlepoint power standard condenser fans and standard two-pass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. iCc°o%i?,# supp,y wer r ................ i ................... J i ........................ ° @ i [2286] ce°°'ie et r ee J _777771 ////8 / 188.35 [4784] B 304.71 [7740] \ 30XA UNIT A B 260 280 300 44,22 (1123) 44.30 (1125) 44.32 (1126) 216,16 (5490) 215.86 (5483) 216.18 (5491) TOP VIEW Piping Entrance Control 7/8" knockouts for main power (5.55" [141 mini hole spacing) 8" Victaulic Leaving Water entry Control Power Entry 8" Victaulic \ [2; \ / '\ i / / Water\ 28!o8 _ [6ool -- ! \X r-_ _ _Optional Non-fused I o o L ..... Disconnect Handle / 199.7 [5072[ C_ontrol Box --- 71.06 [1805) -88.04 RIGHT Incoming power (all voltages) 245.52 [2236] END VIEW (all voltages) \ 90.55 [2300] \ Entering Box (all voltages) BACK VIEW Fig. 7 -- 30XA260-300 Air-Cooled Liquid Chiller Dimensions [6236] 55 )O] -3/4 NPT Relief Conn. Female Victaulic Leaving Water Victaulic Entering Water 3/8 NPT Control /All Box Voltages 90.55 90.55 [2300] [2300] _,q , ! i i X ,'1 _,_ 78,02 15.77 [401] 88.04 [2236] Mounting,o, ses78°2 t888I [1982] -- 304.71 31,96 J o [812£ -_- 78,02 [1982] [7740] _ _ [9555] Rigging Holes (See Detail A) FRONT VIEW LEFT END VIEW L_ 1,50 DIA. [38.1]_ RIGGING HOLE _, 1.75 DETAIL MOUNTING CONTACT 0.875 DIA.[22.2] TYPICAL "A" PLATE SURFACE 4 PLACES 1,31 MOUNTING MOUNTING HOLE _ [33] ! PLATE_ _._ ...... _____L........... 5.0 [127] --1 -- 3.93 I [1OO] 7.88 [2OO] Fig. 7 -- 30XA260-300 Air-Cooled Liquid Chiller Dimensions (cont) '8,02 [1982]- NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface. 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection. 3. 3/84n. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with single-point power, and dual-point power (380 v), standard condenser fans and standard two-pass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Dimensions are shown in inches; dimensions in brackets are in millimeters. 30XA UNIT A 325 350 42.92 42.92 Control 246.16 246.72 .... I power " supply @ A l __ ........................... --"_"" --'-- -- _C--e° ! i_c[e_" reL'-e_ ............ I -:................... :::i::: ..... :............. 348.02 )81 71 06 [1_ 88.04 _ J B (1090) (1090) Box, incoming r [2i361 [8865] (6252) (6267) 423.24 [107501 _-Piping Entrance TOP VIEW (_5.85'k'1}(_,_k°l_s f]°hrolmeaislpaPc° nWge)r e ntrY _. f _, 8" Victaulic Leaving Wate[ ------ / tVer 23.63 _ [310t [6oot _ L -- / \ / "_ "_ / _0r Di°_plBa(yLocation / _-Control / ( power \ entry / "_ _'C t _90.55 71.06 [1805, 88.04 [2236] _ _ RIGHT END VIEW Control J Box Circuit " " 1 all vo_es, ( g d'_ } Circuit t p t'_A!_ 2 (380v _ -_992'_3_41362187] only) 423.24 [10750] BACK VIEW Fig. 8 -- 30XA325,350 Air-Cooled Liquid Chiller Dimensions Cooler Vent3/8 NPT -8 '_Victaulic Leaving 8'_Victaulic Control Box Cooler Drain 3/8 NPT _----- -_ I = 16._]_9_ 40 109.03 [27691 .L _83691 --L 58.0811475[ 349.02 [8865] i 423.24 [10750] LEFT END VIEW Entering Water 90.55 [2300[ _5177 [40_ ]804[2236]- Water _- Mounting Holes Rigging Holes (See Detail A) FRONT VIEW 1 50 DIA RIGGING HOLE 1.75 I4i, DETAIL MOUNTING CONTACT TYPICAL "A" PLATE SURFACE 4 PLACES 1 5.0 [127] Fig. 8 -- 30XA325,350 Air-Cooled Liquid Chiller Dimensions (cont) NOTES: 1, Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface, 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection. 3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with dual-point power standard condenser fans and standard onepass cooler. Refer to the Packaged Chiller Builder program for other configurations. 5. Actual cooler consists of two separate coolers piped in series at the factory, Piping may be split for rigging. 6. Dimensions are shown in inches; dimensions in brackets are in millimeters. Cooler ontrol Box #1 Control Box #2_ Piping Tube Entrance- ........... q • I / 304 1_ [22361 [ 7, 02 - &_\%_ ...... ' _-_-.;,_,_' _5.a??.[f?s41 6091 240.69 470.22 119.0,7 [302, [6114] -- [11944] TOP VIEW 7/8" Knockouts (5.55" between for Ckt 1 power_ holes) \ \ Optional _- Control Box #1_ _ Disconnect Handles_ / _ i-7/8" /(5.55" / Non-fused / \ / Control / \ / Knockouts between l_Display // for Ckt 2 power holes) Box #2 Location 7 C°ntr°l p°wer entry 8" Victaulic 90,55 Entering [2300] _ © F° _6i0_ , i.._. dControl , ,/_ /r / --- 72.1 [1831]-- Box Circuit Jll i , ] L RIGHT END VIEW BACK VIEW Liquid Chiller _ /, , __ I_-_v_ _:05.7_96_4_ . _ A ........... 88.04 [2236]- Fig. 9 -- 30XA400 Air-Cooled i Dimensions 331.58 [8422] 151'5138481 Ci c_uit 2 Cooler '/ located Cooler NPT Relief 8" Victaulic Control Boxes Leaving Conn. Female_ Water- _ Vent 3/8 NPT incoolerheads Drain located 3/8 NPT in cooler heads g Water 90.55 90.55 [2300] [2i0O] ii i [455], b7714°,, I 8" I'-L-- 70,02 [1779] 88.04 [2236] Victaulic Leaving Water -Mounting Rigging Holes (See Detail A) LEFT END VIEW FRONT VIEW 1.50 DIA. [38,1]_ RIGGING HOLE 1.75 DETAIL [4 i] MOUNTING PLATE CONTACT 0.875 DIA.[22.2] MOUNTING HOLE 1 \ I I TYPICAL "A" SURFACE 4 PLACES [33] MOUNTING PLATE _X____._I 1.31 p o [1271 [1001 7.88 [2OO] Fig. 9 -- 30XA400 Air-Cooled Liquid Chiller Dimensions (cont) NOTES: 1. Unit must have clearances as follows: Top -- Do not restrict Sides and Ends -- 6 ft from solid surface, 2. Temperature relief devices are located on liquid line and economizer assemblies and have t/4-in, flare connection. 3. 3/sqn. NPT vents and drains located in each cooler head at each end of cooler. 4. Drawing depicts unit with dual-point power standard condenser fans and standard one-pass cooler. Refer to the Packaged Chiller Builder program for other configurations, 5. Actual cooler consists of two separate coolers piped in series at the factory. Piping may be split for rigging. 6. Dimensions are shown in inches; dimensions in brackets are in millimeters, Control Piping Box #1 _, Control \ Box #2 _, \ 450 500 A L Piping I......... ._ i ........... Entrance Area\ ,_ \ ._ \ A '_ 73.0 \ 71.06 88.04[1854] 1 [18051 [2136] .... ; ........ I 89.62 [21241-• B I 44.78 44,71 (1137) (1136) Tuber Service Entrance 426.0 30XA UNIT I Cooler 517.26 129.1 [32791 [10820] [13138] 264.7 (6705) (6723) 263.99 TOP VIEW (_.8_'5,K_o_,_o_ts _OrleCs_t1 power_ $(_._'5,K_o_ouls $ Non-fused Disconnect Handles fO_eC_t 2 power / o _ Control Box #1_ / _ / / / _ / $ // // Control Display / Box #2 Location Control power entry 8" Victaulic 90.55 Entering Water_ [2300] N ' 17.92 23.62 [455] [6_] L 73.0 [1854] -- x [2236] _-_°netr°l Circuit '_.. • '_7£_0 [a_t 71 -517.26 RIGHT END VIEW / I 28.81 [732] UJ_ 88.04 ( _ L90 O Circ -- I [13138] BACK VIEW Fig. 10 -- 30XA450,500 Air-Cooled Liquid Chiller Dimensions 2 198.54 [5043] 162._ [38791 - Cooler Vent 3/8 NPT located in cooler heads NPT located in cooler heads Mountinc Rigging Holes (See Detail A) 8" Victaulic Leaving Water Victaulic Entering Water 90.55 Control Boxes 90.55 \ \ [2300] [2i00l ii 58.08 15.77 _ [401] 71 06 [1805] 88,04 [2236] i 9" Victaulic Leaving 109.03 [2769] Water 83.62 h 33.96 [_ [863] _ _J_ 33.97 [863] [2124] " 426.0 [10820] 517.26 LEFT END VIEW I",3 58.08 [1475] [13138] FRONT VIEW 1.50 DIA. RIGGING HOLE 1.75 DETAIL MOUNTING CONTACT 0.875 DIA.[22.2] _ MOUNTING HOLE \ l _ I I TYPICAL "A" PLATE SURFACE 4 PLACES 1,331, 5.0 [127] I [1 O0] --1 _ 3.93 7.88 [200] Fig. 10 -- 30XA450,500 Air-Cooled Liquid Chiller Dimensions (cont) 78,02 [1982] 78.02 [1982] Unit Weights -- Standard Units Unit Weights -- English MOUNTING 30XA UNIT SIZE WEIGHT _ otal 7674 WEIGHT (Ib) 080 30XA UNIT SIZE (Ib) MOUNTING A I B I c I D I E I F ITota' I 2188 I 822 I 1023 I 2127 I 1271 I 8704 1299I 2244 I 863 I 1064I 2184 I 1297I 8931 1312 2284 I 872 I 1079I 2222 I 1303 I 9071 090 100 110 120 1273 1346 30XA UNIT SIZE 2322 874 1082 2255 1337 MOUNTING WEIGHT (Ib) A i B i c i o i E i F i G i H ITota, 140 160 2007 2061 30XA UNIT SIZE 1554 1581 I 938 953 I 1254 1281 I 1998 2020 I _I_IcloIEIFIGIHI 180 2OO 979 984 1558 1574 I 1239 1263 I 1291 I 957 I 1695 1321 974 1715 MOUNTING WEIGHT (Ib) I 1809 1862 I 1298 I 2016 I 916 1308 2029 923 MOUNTING WEIGHT (Ib) 1261 1267 30XA UNIT 9216 111506 11748 I ' I J 1363 1375 I 962 968 ITota' 113690 13712 SIZE Total 220 240 260 280 300 14,727 14,887 16,853 17,022 17,362 MOUNTING 30XA WEIGHT 325 35O 856 860 866 860 I 1054 1059 I 1607 1623 I 859 869 I 2697 2752 I 1143 1153 30XA UNIT SIZE A B C D E F G 40O 450 5O0 924 933 921 1311 1256 1314 1588 2276 2325 3119 2398 2452 1332 982 987 866 1134 1139 2368 2184 2194 NOTE: Condenser Coil; Aluminum Fins/Copper I 1639 I 2485 I 880 I 1722 1666 2539 885 1727 MOUNTING WEIGHT (Ib) H I J K 1148 2207 2217 1643 2866 2875 30XA UNIT SIZE MOUNTING _ O8O 30XA UNIT SIZE A B 090 100 110 120 578 589 595 611 992 1018 1036 1053 30XA UNIT SIZE WEIGHTS 824 1629 1633 I 856 860 I 856 860 118,834 19,040 L M N O P Total 1342 1343 1348 2306 1556 1575 1069 1501 1519 1354 1293 1357 945 953 941 24578 26600 26894 428 432 P 427 11 149 12 066 Total 12 199 -- SI (kg) otal 3481 MOUNTING WEIGHT (kg) C D E 373 387 396 397 2440 2089 2098 I 1322 1326 Tubing. Unit Weights 464 478 489 491 F Total 576 588 591 607 3948 4061 4116 4181 965 991 1008 1023 MOUNTING WEIGHT (kg) A i _ i c i o i E i F i G i H iTot°, 140 160 910 935 30XA UNIT SIZE 705 717 I 425 432 I 569 581 I 686 I 434 I 769 I 599 442 778 MOUNTING WEIGHT (kg) 821 846 16219 5329 _I_IcloIEIFIGIHI 180 2OO 444 446 707 714 I 562 573 I 906 916 I 572 575 30XA UNIT SIZE A B C D E 220 24O 260 28O 30O 401 408 257 258 262 574 584 713 723 734 770 782 772 787 799 727 738 378 382 391 407 409 1182 1197 1234 ' IJI I 589 I 915 I 415 I 593 920 419 MOUNTING WEIGHT (kg) F G H 583 585 492 493 501 603 604 725 726 741 416 418 1144 1149 1182 MOUNTING 30XA UNIT SIZE 618 624 I 436 439 Total I 6164 6220 I J K L Total 666 670 395 397 402 530 535 637 648 655 693 604 693 703 712 409 417 257 258 262 6680 6753 7644 7721 7876 WEIGHT (kg) A I B I c I o I E I F I G I H I ' I J I K I ' I M I N ITota' 325 35O 388 390 388 390 419 423 A 418 595 570 B 596 I 478 480 I 729 736 I 390 394 112241 1248 604 446 E 448 393 514 F 516 618 523 30XA UNIT SIZE 40O 45O 5OO (Ib) _ I _ I c I _ I E I F I G I H I ' I J I K I ' I M I N ITota' UNIT SIZE I NOTE: Condenser Coil: Aluminum 720 1032 C 1055 1415 1088 D 1112 Fins/Copper 1074 991 G 995 I 744 111271 399 I 756 1152 401 MOUNTING WEIGHT (kg) 521 1001 H 1005 745 1300 I 1304 1107 948 J 952 781 784 374 739 K 741 Tubing. Fig. 11 -- Unit Mounting Weights 22 I 600 601 609 609 L 611 I 388 390 1046 706 M 714 I 388 390 18648 8636 485 681 N 689 614 586 O 616 30XA080 30XA220-300 EDC Compressors B Compressors G H I F B E I G B Compressors J G C B J K L M F E D C B N 0 Compressors 30XA180-200 D C 30XA400-450 30XA140-160 E D Compressors Compressors F K 30XA325-350 30XA090-120 c J B Compressors I Fig. 11 -- Unit Mounting Weights (cont) 23 K L M P Table 1AUNIT 30XA OPERATING WEIGHT (Ib) AI-Cu Condenser Coils REFRIGERANT TYPE Refrigerant Charge (Ib) Ckt A/Ckt B/Ckt C COMPRESSORS Quantity Speed (rpm) (Qty) Compressor Nominal Capacity (Qty) Compressor Nominal Capacity (Oty) Compressor Nominal Capacity Oil Charge (gal), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard Optional (tons) Ckt A (tons) Ckt B (tons) Ckt C Ambientt DIMENSIONS 100 110 120 140 160 180 200 220 8,931 9,071 9,216 11,505 11,748 13,590 13,712 14,727 2 I (1)45" I 1140 rpm 2 I I 2 135002 (1)60 5.5/5.5/-- 5.5/5.5/-- 5.5/5.5/-- 5.5/5.5/-(1) 1560 N/A 10 I I 2 I 2 (1)90 (1)100 (1)90 N/A 6.25/5.5/-- N/A 6.25/5.5/-- N/A 6.25/6.25/-- I I I I 2 (1)120 N/A 6.25/6.25/-- I (1)15 100 1O I (1)14 100 10 16.5 I 16.5 18.5 20.0 31.5 34.0 37.0 220 300 I 220 300 220 300 220 300 220 300 I 220 300 220 300 220 300 220 300 220 300 3/s 3/8 3/s 3/s 3/s I 3/s 3/8 3/s 3/s 3/s 2 5 1 5 4 3 2 5 1 5 4 3 2 5 1 5 4 3 2 5 1 5 4 3 2 5 1 45 3 2 5 1 5 3 2 5 1 5 3 2 6 1 6 3 2 8 1 6 3 2 6 1 6 3 850/1140 850/1 140 650/1 140 6/6/-111,600 9...30 148,800 6/6/-111,600 9...30 148,800 7/6/-120,900 9...30 161,200 650/-- 850/-- 650/-- I 4/4/-74,400 9...30 4/4/-74,400 9...30 4/4/-74,400 9...30 3/3/-- 4148/_ I 4_48/_ I Shell and Tube Type I 25.5 27.5 I Shrouded Axial Type, Vertical 650/-I 650/1 140 4/4/-74,400 9...30 I 4_ (1)15 10e0 N/A 6.75/6.25/-- (1) 1450 N/A 8 I (1)11 860 2 (1) 100 (1) 1550 N/A 9 Flooded, 23.0 (1)11 750 I 6/4/-93,000 9...30 124,000 I I 4_ Discharge 850/1 140 6/4/-93,000 9...30 124,000 I 6/43/_- 6/43/_- I 281I 6/6/-- 6_6_- I 3O5 7/6/-- (ft-ln.) UNIT 30XA REFRIGERANT TYPE Refrigerant Charge (Ib) Ckt A/Ckt B/Ckt C COMPRESSORS Quantity Speed (rpm) (Qty) Compressor Nominal Capacity (Qty) Compressor Nominal Capacity (Oty) Compressor Nominal Capacity OII Charge (gal), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard Optional 15-9 I 7=425/3_ 7-67/_6 Ckt A Ckt B Ckt C I 23-7 240 260 280 300 325 350 400 16,853 17,022 17,362 18,834 19,040 24,578 27_270/-- _ 375/22_-- I 375/27_-- R-134a, EXV Controlled System I 415/270/-I 375_7_-I 415/37_-- (1) 120 (1) 120 N/A I 2 I (1) 165 (1) 100 N/A 6.75/6.75/-- 7.5/6.75/-- 15 10 I I 2 (1) 165 (1) 120 N/A 7.5/6.75/-- I I 2 I (1) 185 (1) 120 N/A I 7.5/6.75/-- 10 8 13 9 12 7 2 3500 (1) 165 (1) 165 N/A 7.5/7.5/-- Flooded, I 27_27_375 I 27-6 450 500 26,600 I 41_205_15 26,894 I 41_270/415 Twin Rotary Screws I 2 I (1) 185 (1) 165 N/A 3 3 (1) 120 (1) 120 (1)165 7.5/7.5/-- 15 10 (1)90 (1) 185 (1) 185 7.5/6.25/7.5 6.75/6.75/7.5 14 10 ShellandTubeType 50.5 53.4 3 (1) 120 (1) 185 (1) 185 7.5/6.75/7.5 6 4 7 5 39.0 I 42.0 44.0 48.5 68.0 75.0 83.0 220 300 I 220 300 220 300 220 300 220 300 220 300 220 150 220 150 220 150 3& I 3/s 3/s 3/s 3/s 3/s 3/s 2 6 1 6 3 2 8 1 8 3 2 8 1 8 3 2 6 1 6 3 2 6 1 6 3 1 ----8 -- % 6 1 ¾ 8 1 850/1140 911130 6/6/8 204,600 272,800 650/1140 9...30 8/6/8 204,600 272,800 2 8 1 6 3 I Shrouded Amblentt 19-8 14,887 2 (tons) (tons) (tons) WATER CONNECTIONS Drain (NPT, In.) Standard, Inlet and Outlet, Vlctaullc (in.) Number of passes Minus 1 Pass, Inlet and Outlet, Vlctaullc (in.) Number of passes Plus 1 Pass, Inlet and Outlet, Vlctaullc (in.) Number of Passes CONDENSER FANS Fan Speed (rpm) Standard/High No. Blades...Dlameter (in.) No. Fans (Ckt A/Ckt B/Ckt C) Total Airflow (cfm) 850 rpm Total Airflow (cfm) 1140 rpm I Semi-Hermetic COOLER Net Fluid Volume (gal.) Maximum Refrigerant Pressure (pslg) Maximum Fluid Side Pressure (pslg) 850/1140 9...30 7/6/-120,900 161,200 CONDENSER COILS No. Coils (Ckt A/Ckt B/Ckt C) Total Face Area (sq ft) 9...30 9/6/-139,500 I 850/1140 186,000 9...30 10/6/-148,600 850/1140 198,400 Axial Type, Vertical 9...30 10/6/-148,600 850/1140 196,400 9...30 9/9/-167,400 850/1140 223,200 Discharge 9...30 9/9/-186,000 850/1140 223,200 9...30 6/6/8 186,000 650/1140 248,000 i 9/6/1352375 i 10/6/i 10/6/375i 9/9/422i 9/9/4226/6/8469 I 6/6/6516 I 6/6/8516 (ft-ln.) 27-6 I 31-5 LEGEND Cu -AI -EXV-N/A -- 2 (1)60 (1) 1545 N/A 9 11-10 DIMENSIONS 2 (1)50 141I R/Ckt C) I (1)45 I 3/3/-55,800 9...30 ..... OPERATING WEIGHT (Ib) AI/Cu Condenser Coils CHASSIS Length Width Height System (1)N/A 1545* 9 650/-- Tota, FaceArea(sg.) No. Coils (Ckt A/Ckt 090 8,704 5.5/5.5/-- No. Fans (Ckt A/Ckt B/Ckt C) Total Airflow (cfm) 850 rpm CHASSIS Length Width Height 080 7,674 R-134a, EXV Controlled WATER CONNECTIONS Drain (NPT, In.) Standard, Inlet and Outlet, Vlctaullc (in.) Number of passes Minus 1 Pass, Inlet and Outlet, Victaullc (in.) Number of passes Plus 1 Pass, Inlet and Outlet, Victaullc (in.) Number of Passes Total Airflow !cfm! CONDENSER COILS English 66/66/-I 97/97/-11°6/1°6/-I135/1°6/-I135/135/-12°22115/-I 225/135/I 205/205/-I 225/225/I 270/225/Semi-Hermetic Twin Rotary Screws COOLER Net Fluid Volume (gal.) Maximum Refrigerant Pressure (pslg) Maximum Fluid Side Pressure (psig) CONDENSER FANS Fan Speed (rpm) Standard/High No. Blades...Diameter (in.) Physical Data, 30XA080-500- Copper Aluminum Electronic Expansion Not Applicable Valve *30XA080 unit does not have an economizer. tThe high ambient temperature option is not available on 30XA080-120 units. 24 I 35-4 743/4 7=67/16 I 39-3 I 43-2 Table 1B -- 30XA080-500 -- SI UNIT 3OXA OPERATING WEIGHT (kg) AI-Cu Condenser Coils REFRIGERANT TYPE Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C COMPRESSORS QuanUty Speed (r/s) (Qty) Compressor (Qty) Compressor (Oty) Compressor Oil Charge (liters), Minimum Capacity Standard OpUonal 080 090 100 110 120 140 160 160 200 220 3 481 3 948 4 051 4 115 4 181 5 219 5 329 6 164 6 220 6 660 39/39/- I 44/44/- R-1 64a, EXV Controlled System 149/44/-1102/10"2/-191.6/62.2/-1102/61.2/- 149/49/- SembHermetic 2 Nominal Capacity (tons) Nominal Capacity (tons) Nominal Capacity (tons) Ckt A/Ckt B/Ckt C Step (%) Ckt A Ckt B Ckt C (1) 45" (1)45" N/A 20.6/20.8/-- I I 2 (1)45 I (1)45 N/A 20.8/20.6/-- 9 15 I 2 (1)50 I (1)50 N/A 20.6/20.6/-- v 15 I 2 (1)60 I (1)50 N/A 20.6/20.8/-- v 15 6 14 CHASSIS Length Width Height DIMENSIONS 1102/102-1122.5/102/-- 5_.3v I 2 (1)90 I (1)50 N/A 23.7/20.8/-- 10 15 2 (1) 100 I (1)60 N/A 23.7/23.7/-- I I 7 11 2 (1)90 I (1)90 N/A 23.7/23.7/-- 8 11 I 2 (1) 100 I (1)100 N/A 23.7/23.7/-- 10 15 2 (1) 120 I (1)100 N/A 26.6/23.7/-- 10 15 10 14 Flooded, Shell and Tube Type 140.1 1516.8 2 068 WATER CONNECTIONS Drain (NPT, In.) Standard, Inlet and Outlet, Victaullc (in.) Number of passes Minus 1 Pass, Inlet and Outlet, Victaullc (in.) Number of passes Plus 1 Pass, Inlet and Outlet, Victaulic (in.) Number of Passes CONDENSER FANS Fan Speed (r/s) Standard/High No. Blades._Diameter (ram) No. Fans (Ckt A/Ckt B/Ckt C) Total Airflow (L/s) 14.2 r/s Total Airflow IL/s! 19.0 r/s CONDENSER COILS No. Coils (Ckt A/Ckt B/Ckt C) Total Face Area (sg m) 2 (1)60 I (1)60 N/A 20.8/20.6/-- COOLER Net Fluid Volume (liters) Maximum Refrigerant Pressure (kPa) Maximum Fluid Side Pressure (kPa) 193/93/- Twin Rotary Screws 5 2 5 1 4 3 5 2 5 1 4 3 5 2 5 1 4 3 6 2 6 1 6 3 14.2/-9...762 3/3/-26335 14.2/-9_.762 4/4/-35113 14.2/-9...762 4/4/-35113 Shrouded Ambientt 13 I 3/3/-- 4/_-- I 9...762 4/4/-35113 14.2/--- I I 17 I 4/_-- 4/4/-- 6 2 8 1 6 3 Axial Type, Vertical Discharge 9...762 4/4/-35113 14.2/--- 9...762 6/4/-43891 14.2/19.0 58 522 I 9...762 6/4/-43891 14.2/19.0 58 522 I 9...762 6/6/-52669 14.2/19.0 70 226 14.2/19.0 9...762 7/_-57 059 76 078 9...762 6/6/-52669 14.2/19.0 70 226 I 22 I 22 I 26 I 26 I 26 4/_-- 6/4/-- 6/4/-- 6/6/-- 6/6/-- 7/6/-- (ram) 3 606 I 4 800 2455 5 994 I 7 188 I 8 382 2296.9 UNIT 30XA 240 6753 OPERATING WEIGHT (kg) AI/Cu Condenser Coils 260 7644 280 7721 300 7676 REFRIGERANT TYPE Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C R-134a, 122.6/122.6/1170.1/99.6/1170.1/122.6/I_ COMPRESSORS OuanUty Speed (r/s) (Qty) Compressor Nominal Capacity (tons) (Qty) Compressor Nominal Capacity (tons) (Qty) Compressor Nominal Capacity (tons) OII Charge (liter), Ckt A/Ckt B/Ckt C Minimum Capacity Step (%) Standard OpUonal 325 8543 2 (1) 120 (1) 120 N/A I 2 I 2 I 2 I (1) 165 (1) 100 N/A I (1) 165 (1) 120 N/A I (1) 185 (1) 120 N/A 25.6/26.6/-10 15 26.4/25.6/-8 10 26.4/26.6/-9 13 WATER CONNECTIONS Drain (NPT, In.) Standard, Inlet and Outlet, Vlctaullc (in.) Number of passes Minus 1 Pass, Inlet and Outlet, Vlctaullc (in.) Number of passes Plus 1 Pass, Inlet and Outlet, Vlctaullc (in.) Number of Passes Amblentt CONDENSER COILS No. Coils (Ckt A/Ckt B/Ckt C) Total Face Area (sq m) CHASSIS Length Width Height DIMENSIONS (ram) Copper Aluminum Electronic Expansion Not Applicable I 26.4/28.4/-10 15 2 (1) 185 (1) 165 N/A I 3 I (1) 120 (1) 120 (1) 166 28.4/28.4/-10 14 5166.3/102/186.3/188.3/ I 3 I (1) 90 (1) 185 (1)166 26.6/25.6/28.4 6 9 28.4/23.7/28.4 4 6 I 3 I (1) 120 (1) 185 (1)185 28.4/25.6/28.4 5 7 257.4 I 283.9 314.2 1516.8 1034 I 1516.8 1034 1516.8 1034 3/s 3/s 3/s 3/s 3/s 3/s 3/8 2 6 1 6 3 2 6 1 6 3 2 8 1 8 3 2 8 1 8 3 2 8 1 8 3 2 8 1 8 3 1 ----8 -- 14.2/19.0 14.2/19.0 14.2/19.0 7/6/-57059 9...762 76078 9/6/-65837 9...762 87762 10/6/-70226 9...762 93634 Shrouded 14.2/19.0 Axial Type, Vertical Discharge 14.2/19.0 14.2/19.0 10/6/-70226 9...762 93634 9/9/-79004 9...762 93634 14.2/19.0 9/9/-79004 9...762 105339 6/6/8 87782 9...762 117043 I I I I 3/s 3/8 1 ----8 -- 1 ----8 -- 14.2/19.0 14.2/19.0 8/6/8 96561 9...762 128747 8/6/8 96561 9...762 128747 7/6/-19/6/-11°/6/-11°/6/-19/9/-19/9/-I 26 33 36 36 39 39 6/6/616/6/616/6/8 44 48 46 8362 I 9576 Valve *30XA080 unit does not have an economizer. tThe high ambient temperature option is not available 500 12199 Twin Rotary Screws (1) 165 (1) 165 N/A I 450 12066 Flooded, Shell and Tube ] LEGEND CU -AI -EXV-N/A -- I I System 23500I I 28.4/26.6/-_ 12 COOLER Net Fluid Volume (liters) Maximum Refrigerant Pressure (kPa) Maximum Fluid Side Pressure (kPa) CONDENSER FANS Fan Speed (r/s) Standard/High No. Blades...Dlameter (mm) No. Fans (Ckt A/Ckt B/Ckt C) Total Airflow (L/s) 14.2 r/s Total Airflow (L/s) 19.0 r/s EXV Controlled 400 11149 188.3/122.6/1170.1/170.1/1168.3/170.1/1122.5/122.5/170.11168.31122. SembHermetic Ckt A Ckt B Ckt C 350 6636 on 30XA080-120 units. 25 I 10770 2 255 2 300 I 11964 I 13168 RIGGING UNIT (See Fig. 12-14) --The 30XA080-500 units are designed for overhead rigging and it is impollant that this method be used. Holes are provided in frame base channels, marked for rigging (see rigging label on unit). Field-supplied shackles tue required to facilitate lifting. Secure the shackles to the base rails at the points noted on the rigging label. See Table 2 for the number of lifting points for each unit. Do not use a forklift truck to move the units. See Fig. 12-14 for rigging centers of gravity. For shipping, some domestic units and all export units are mounted on a wooden skid under entire base of unit. Skid can be removed before unit is moved to installation site. Lift the unit from above to lemove skid. See Fig. 12-14 for rigging center of gravity. On export units, the top skid can be used as the spreader baLs. If the unit was shipped with a shipping bag, the bag must be removed to gain access to the rigging holes in the base mil. Table 2 -- Number of Lifting Points for 30XA080-500 30XA UNIT SIZE NUMBER OF LIFTING 080 If overhead rigging is not available, the unit can be moved on rollers or dragged. When unit is moved on rollers, the unit skid, if equipped, must be removed. To lift the unit, use jacks at the rigging points. Use a minimum number of rollers to distribute the load such that the rollers are no more than 6 ll (1.8 m) apart. If the unit is to be dragged, H1l the unit as described above, and place unit on a pad. Apply moving force to the pad, and not the unit. When in its I]mfl location, raise the unit and remove the pad. If the unit was shipped with coil protection, it must be removed before start-up. The shipping bag for export units must be removed before start-up. POINTS 4 090-120 6 140, 160 8 180, 200 220-400 10 12 450, 500 14 Use spreader b_us to keep cables or chains clear of unit sides. As further protection plywood sheets may be placed against sides of unit, behind cables or ch_dns. Run cables or chains to a central suspension point so that angle from horizontal is not less than 45 degrees. Rtdse and set unit down cmefully. 13' MIRINUM (398Rmm} AR A1 CAUTION- NOTICE TO RIGGERS: ALL PANELS MUST BE IN PLACE WHEN RIGGING DO NOT ATTEMPT TO FORK THESE UMTS IF NO SKID IS SUPPLIED, NOTES I 5D IN DIA IBB Fm_) LIFTING HOLES PROVIDED FOR FIELD SUPPLIED CLEVIS RIG WITH A _INIIIBM OR BSFT (TBZOmm) LENGTH CIAINS OR CABLES IF CENTRAL LIFTING POINT IS USED, IT RUST BE A NINIMUN OF 13FT (39RBmm) ABOVE THE TOP OF THE UNIT SPREAD R BARS BADE IROM SIEEL OR DOBBL NAILER, AND NOICHED R×6'S ARPROXIMAIELY B FT (B43Bmm) LONG MUST BE PLACED IF JUST ABOVE THE OVERHEAR RIGGING THE UNIT S_ID, [g TOP IS OF THE MDST ONE ROLLER EVERY 6FT (IBZRmm) ABOVE, AND PLACE UNIT UNIT (AND NO1 AVAILABLE, EQDIPI_ED, ON BE STACKS1 THE UNIT REMOV D IO DISIRIBUIE A PAD APP T IHE MOVING TO REDUCE THE RISK OF DAMAGE TO TI_E TOP OF BAN BE MOVER ON ROLLERS OR BRAGGED WHEN UNII TO lIFT THE l_ LOAD FORCE _RIT, TO USE THE UNIT THE PAD, JACKS IS lO NOT THE %1_G OLES AT THE RIGGING BE DRAGGER, LIFE UNIT WHEN IN THE (Tg UNIT AND COILS IS MOVED ON ROE ERS, POINTS _SE THE UNIT FINAl A MINIMUM OF AS DESCRIBED LOCATION, RAISE T_E UNIT AND BEHOVE THE PAD BHECI< BILL OF LADING FOR SH PPING WEIGHT DE THE UNIT LI .U.BER%c"_'/g{¢d _"A'CKA"d_'_2 "_" 30XA08O t2o ;',_ 2, 2L I.... 3OXAO9O 8611 4 )OXAIO0 8837 E_E_!!D ......................... Z 4 391_ 9_0_ 4017 9907 _ 4400 4503 45r_ _OB9 10903 27693 161 6118 4775187 _ Fig. 12 -- Unit GRAVITY _0B9 7802 19817 T802 1981 19817 7802 19817 7 ............... _01 3 2573 44) 1120 [39 _ 3538 16 1172 16l 4089 o!Lt_D_ 9 ........................ 9102 4137 O72 4524 i]iii_i 16 !it i 408 ibx;_d;_ ........................ iJbd-do? 13525 OF ,.... _61 )OXA120 30_A200 CENTER ._2. 16 I 1089 9 78 Rigging O_ Label 26 3_ O0 Detail 81Z 7 _2 02 15753 30XA080-200 CAUTION- NOTICE TO RIGGERS: ALL PANELS MUST BE IN PLACE WHEN RIGGING DO NOT ATTEMPT TO FORK THESE UNITS IF NO SKID _S SUPPLIED NOTES: 1 150 IN DIAIBB1n_I LIFTINB HOLES PROVIDED FOR FIELD SUPPLIED CLEVIS R RIG WITH A MINIMUM OF 25FT (7SROmm) LENGTH CHAINS OR CABLES 3 IF BEN[RAL LIFIING POINT IS USED, II MUSI BE A MINIMUM Ol 13Fl (SRSRmm) ABOVE F_E lOP OF DIE UNII 4 SPREADER BARS MADE PROM STEEL OR DOUBLE NAILED, AND NOTCNRN 2X6'S APPROXIMATELY 8 IT 12438mm) LONG MUST BE PLACED JUST ABOVE THE TOP OF THE UNIT (AND STACKS} TO REDUCE THE RISN OF DAMAGE TO TNE TOP OF TIE UNIT AND COILS R IF OVERHEAD RIBGING IS NO[ AVAILABLE, [HE UNI[ CAN DE MOVED ON ROLLERS OR DRAGGED WHEN UNI[ IS MOVED ON ROLLERS, THE UNIT SKIS, IF EQUIPPED, MUST DE REMOVED TO LIFT TNE UNIT, USE JACNS AT THE RIGGING POINTS USE A MINIMUM OF ONE ROILER EVERY BFT (IRRRmml TO DISTRIBUTE THE LOAD IF THE UNIT IS TO BZ DRABBED, LIFT TNE UNIT AS DESCRIDEB ABOVE, ANU PLACE UNIT ON A RAG APPLY MOVING FORCE TO THE PAR, NOT THE UNIT 8H[N !NIPS FINAL LOCATION, RAISE THE UNIT AND REMOVE THE PAD 6. CHECK DILL O_ LADINB FOR SHIRRING WEIGNT OF THE UNII N_ _OMDBE[_ MAX SHIPPING MAX SNIPPING tVI WITHOUT WI WITH PACKAGING PAC{iAGING 30XA220 SOXA240 14668 SOXA260 30XA280 15515 16769 30XA325 18539 6667 5862 I600D 7276 7552 7622 18045 1899 8202 8272 8427 20059 918 LIFTING _AI " "AN .... 161 4 9 6NO_ 4069 6ZS_ 15753 161 6 408 9 408 9 780_ 780_ 198I 9817 1S 1 4089 780_ 19817 BNSS 7 7802 7802 110 Fig. 13 -- Unit Rigging 81 7 D127 19817 987 O_ 27945 CENIER OF GRAVHY HOLES A3" 'A4" I09 03 10903 'AS" 0 S?6UB _?00 6SOZ 1SISB 1585 4025 46 2 462 3200 3200 812 812 7802 7802 19817 987 7802 7802 19D1 7 1601 19817 604 4066 4074 44 2 443 1123 1125 62 02 15753 32 O0 8127 0903 2769 4499 429 1090 7 7 N 'C'r 81 7 D121 Label Detail 30XA220-350 2? 'D'r 'AS" 3 177 ] 1173 1174 13' MINIMUH 13982mm} CAUFION ALL PANELS NOTES: 150 il N 5 MODEL NUMBER 30XA40O 30XA450 30XA508 MUST 8E !NBIA{B81mm) IN PLACE LIFTING WHEN HOLES RIGGING PROVIDEB NOFZ]E lO RIGGERS: DO FOR FIELB NOT AI]EMP] SUPPLIED [0 FORK ]NESE UNI[S IF NO SHED IS SUPPLIED CIEVIS RIG WlIN A MINIMUM OF RSET (TBBOmml LENGTH CHAINS ON CABLES IF CENTRAL LIFTING POINT IS USED, iT MUST BE A MINIMUM OF 13PP (3862_} ABOVE THE POP OF THE UNIT SPREADER BARS MAKE FROM STEEL OR BOM_LE NAILEB, ANB NOTCHED 2X6'S APPROXIMATELY 8 FT (2438mm) LONG MUST BE PLACED JUST ABOVE THE TOP OF THE UNIT IAHD STACKS} TO REBUCE THE RISK OT DAMAGE TO THE TOP OF THE UNIT AND COILS IF OVERNEAB RIGGING [S NOT AVAILABLE, THE UNIT CAN 8E MOVED ON ROLIERS OR DRAGGED WHEN UNIT IS MOVED ON ROllERS, INE UNIt SN]B, iF EQN]PPEB, MUSE BE REMOVED TO LIEI !HE UNIT, USE JACHS Ar THE RIGGING POIH[S USE A MINIMUM O_ ONE ROLLER EVERY 6PT (1829_I TO DISPRIBUPE THE LOAN IP PHE UNIT IS TO _E DNAGGEB, LIPP THE UNIT AS DESCRIBED ABOVE, ANB PLACE UNIT ON A PAD APHIY MOVING FORCE TO THE PAB, NOT THE NNIP WHEN IN ITS FINAL lOCATION, RAISE TN_ UNIT AHD REMOVE THE RAD _AX SHIRgING MAX SHIPPING WT WITHOUT W_ WIT_ PACNAGIMG PACNAG[NG 11005 25175 2LN3554 11898 KS 24214 120_7 25824 27875 LB 28136 11738 12671 NG 12789 LIFTING NOLSS _AI .... 151 151 [N 151 408_ 4089 MM 4089 Fig. 14- AR_¸ 7802 7802 [N 7802 "AS" CEMTSR OF GRAVITY "A4 .... 19817 19817 MM 19817 AS" IN flOOR 32 O0 MM 2794¸5 81R7 B280 812¸7 "AT" "AT.... B" "C'_ IN MM [N MM i IN _M i IN _M 52¸02 IS753 ...... i!R95 5831i4S8 11531 lO_OS 2759¸3 94¸02 RSBB Ii SR 5 5416i447 1136i I090K 2759¸3 9402 Unit Rigging Label Detail 30XA400-500 2g RB8811!533 54B4 448 IIBTI Step 3 -- Cooler Fluid and Drain Piping nections -- See Fig. 15-18 for piping applications. Con- leaving water temperature stability for comfort cooling applications, a minimum of 3 gallons per ton (3.25 liters per kW) is required on all unit sizes. For process cooling applications, applications where high stability is critical, or operation at mnbient temperatures below 32 F (0 ° C) is expected, the loop volume should be increased to 6 to 10 gallons per ton (6.46 to 10.76 liters per kW) of cooling. In order to achieve tiffs volume, it may be necessary to add a water storage tank to the water loop. If a storage tank is added to the system, it should be properly vented so that the tank can be completely filled and all air eliminated. Failure to do so could cause lack of pump stability and poor system operation. Any storage tank that is placed in the water loop should have internal baffles to allow fllorough mixing of the fluid. See Fig. 20. Remove file chilled water flow switch, entering and leaving water thermistors before welding connecting piping. Reinstall flow switch and thermistors after welding is complete. Failure to remove these devices may cause unit &image. GENERAL -- The factory-installed victaulic connections _dlow clamp-on connection of water lines to file coolel_ in all 30XA units. A flow sensor is factory-installed in the side of the entering fluid nozzle. See Fig. 19. See Table 3 for 30XA unit operating range. See Fig. 16 for cooler option dimensions. System Piping -- Proper system design and installation procedures should be followed closely. The system must be constructed with pressure tight components and thoroughly tested for installation leaks. DUAL CHILLER CONTROL -- The Co171/i_tTLinkTM controller allows 2 chillers (piped in parallel or series) to operate as a single chilled water plant with standard control functions coordinated through the master chiller controllec This stan&trd Co_71ibrtLink feature requires a communication link between the 2 chillers. There me severtd advantages • • • • Installation of water systems should follow sound engineering practice as well as applicable local and industry standards. Improperly designed or inst_dled systems may cause unsatisfactory operation and/or system failure. Consult a water treatment specialist or appropriate literature for information regarding filtration, water treatment, and control devices. to this type of control: redundancy (multiple circuits) better low load control, (lower tonnage capability) lower rigging lift weights (2 machines rather than one large machine) chiller lead-lag operation (evens the wear between the two machines) Parallel Dual Chiller Operation -- Pm'allel chiller operation is the recommended option for dual chiller control. In this case, each chiller must control its own dedicated pump or isolation valve. Balancing v_dves are recommended to insure proper flow in each chillec Two field-supplied and inst_dled dual chiller leaving water temperature sensors ale required, one for each module for this function to operate properly. Dual Chiller Leaving Water Sensor --If the Dual Chiller algorithm is used, and the machines me installed in parallel, a dual chilled water sensor must be installed for each module. Install the well in the common leaving water headec See Fig. 17. Consider adding additional isolation valves to isolate each chiller to allow for service on a machine, and still allow for partied capacity from the other chillec See Fig 17. Minimum Loop Volume -- The preferred minimum loop volume is dependent on the type of application. In order to obtain AIR FLOW POWER FD FD CONTROL BALANCIN( SHUTOFF* VIBRATI( ELIMINATORS* _, DRAIN SHUTOFF VALVE LEGEND FD -- Fused Disconnect Airflow Through Condenser c====_ Chilled Water Piping Power Wiring *Field-installed. PRESSURE/ TEMPERATURE TAPS* NOTES: 1. Chiller must be installed level to maintain proper compressor oil return. 2. Piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards. 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details. Fig. 15 -- 30XA Typical Piping and Wiring 29 Table 3 -- 30XA Minimum and Maximum Cooler Flow Rates* ITEM MINIMUM Cooler Leaving Water Temperaturet Cooler Enterin_l Water Temperature** 30XA Number of Cooler UNIT SIZE Passes Standard 080 Plus one pass Minus one pass Standard 090 Plus one pass Minus one pass Standard 100 Plus one pass Minus one pass Standard 110 Plus one pass Minus one pass Standard 120 Plus one pass Minus one pass Standard 140 Plus one pass Minus one pass Standard 160 Plus one pass Minus one pass Standard 180 Plus one pass Minus one pass Standard 200 Plus one pass Minus one pass Standard 220 Plus one pass Minus one pass Standard 24O Plus one pass Minus one pass Standard 260 Plus one pass Minus one pass Standard 28O Plus one pass Minus one pass Standard 3OO Plus one pass Minus one pass Standard 325 Plus one pass Minus one pass Standard 35O Plus one pass Minus one pass Standard 4OO Flow 70F(21.1 C) Rate Maximum (_Ipm) IUs) 95 6.0 (_lpm) 379 Rate (Us) Nominal (?pm) Flow Rate (us) 23.9 43 2.7 192 12.1 198 12.4 782 49.3 101 8.4 403 25.4 43 2.7 200 12.6 229 14.4 917 57.9 101 8.4 403 25.4 43 2.7 200 12.6 229 14.4 917 57.9 125 7.9 5Ol 31.6 61 3.8 244 15.4 254 18.0 1014 84.0 125 7.9 501 31.6 73 4.8 293 18.5 281 17.7 1124 70.9 134 8.5 538 33.9 73 4.8 293 18.5 324 20.4 1298 81.8 165 10.4 860 41.6 98 8.2 391 24.7 354 22.3 1418 89.5 202 12.7 807 50.9 73 4.8 391 24.7 418 28.2 1862 104.9 223 14.1 892 56.3 98 8.2 391 24.7 458 28.9 1833 115.6 235 14.8 941 59.4 122 7.7 489 30.9 501 31.8 2004 126.4 268 18.8 1063 87.1 147 9.3 587 37.0 538 33.9 2151 135.7 257 18.2 1027 84.8 141 8.9 562 35.5 584 38.8 2334 147.3 293 18.5 1173 74.0 141 8.9 562 35.5 820 39.1 2481 156.5 327 20.8 1308 82.5 174 11.0 897 44.0 887 43.3 2750 173.5 361 22.8 1442 91.0 211 13.3 843 53.2 724 45.7 2897 182.8 379 23.9 1518 95.6 244 15.4 978 81.7 767 48.4 3068 193.6 501 31.8 2004 126.4 1 501 180.4 11.4 201.9 12.7 225.5 14.2 244.9 15.5 264.8 16.7 317.8 20.1 365.1 23.0 409.8 25.8 463.9 29.3 505.9 31.9 545.8 34.4 800.3 37.9 842.2 40.5 887.5 43.4 733.4 46.3 775.4 48.9 -- 917.8 57.9 -- 1019.3 84.3 -- 1092.8 88.9 2004 Plus one pass Minus one pass Standard 1 501 2004 m Plus one pass Minus Flow one pass Standard 5OO 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 1 45F17.2 c! Minimum NOMINAL 60 F (15 C) Plus one pass Minus 45O MAXIMUM 40 F (4.4 C) m one pass NOTES: *Maximum ambient temperature and percent of unit capacity will vary based on unit load and return water temperature. All models are qualified for use at 125 F (48 C). Some models may require the high ambient fan option. Contact a local Carrier representative to obtain performance data using the Carrier electronic catalog. 1-For applications requiring cooler leaving water temperature operation at less than 40 F (4.4 C, the units require the use of antifreeze and application may require one of the spec a order br ne opt on. Contact a oca Carrier representat ve for more information. **For applications requiring cooler entering water temperature operation at less than 45 F (7.2 C, contact a local Carrier representative for unit selection using the Cart ere ectron c cata og. 1. The 30XA units will start with loop temperatures up to 95 F (35 C. 2. Nominal flow rates required at ARI conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft2-h r-F/Btu (0.000018 m2-K/kW). 3. To obtain proper temperature control, cooler loop fluid volume must be at least 3 gal/ton 3.23 L/kW of chiller nominal capacity for air conditioning and at least 6 gal/ton (6.5 L/kW) for process applications or systems that must operate in low ambient temperatures (below 32 F 0 ° C . 4. Where winds of 5 mph (2.2 m/s) or greater are anticipated at outdoor ambient temperatures below 32 F (O° C), wind baffles are required. 5. Requires optional or accessory low ambient kit for operation below 32 F (0 ° C). 30 ENGLISH STANDARD 30XA UNIT SIZE* 080 090 100 110 120 140 160 180 200 220 240 260 280 300 328 380 Distance to Leaving/ Entering Water Distance to Leaving Water Connection Height Leaving Water Connection (in.) (in.) Connection (in.) 121.2 120.9 120.9 120.9 120.9 121.5 121.5 177.7 177.3 224.7 224.7 304.7 304.7 304.7 349.0 349.0 19.1 19.1 19.1 19.1 19.1 21.3 21.3 22.5 22.5 22.5 22.5 23.6 28.6 28.6 23.6 23.6 68.1 68.1 68.1 66.1 68.1 69.1 69.1 70.2 70.2 70.2 70.2 71.1 71.1 71.1 71.1 71.1 COOLER Distanceto Entering Water Connection PLUS ONE PASS COOLER Height Entering Water Connection (in.) (in.) 121.2 120.9 120.9 120.9 120.9 121.5 121.5 177.7 177.3 224.7 224.7 304.7 304.7 304.7 349.0 349.0 10.8 10.8 10.8 10.6 10.6 10.6 10.6 11.3 11.3 11.3 11.3 12.2 12.2 12.2 12.2 12.2 Vlctaullc Connection Size (in.) (in.) (in.) Distance to Leaving/ Entering Water ConnecUon (in.) 1.5 1.2 1.2 1.2 1.2 1.2 1.2 53.6 53.2 100.6 100.6 180.3 160.3 160.3 224.7 224.7 19.6 19.6 19.6 19.6 19.6 21.3 21.3 22.4 22.4 22.4 22.4 23.4 23.4 23.4 23.4 23.4 68.1 68.1 68.1 66.1 68.1 69.1 69.1 70.2 70.2 70.2 70.2 71.1 71.1 71.1 71.1 71.1 Distance to Leaving Water Connection 5.0 5.0 5.0 5.0 5.0 5.0 5.0 6.0 6.0 6.0 6.0 8.0 8.0 8.0 8.0 8.0 Height Leaving Water Connection Distance to Entering Water Connection (in.) 121.2 120.9 120.9 120.9 120.9 121.5 121.5 180.6 180.2 227.6 227.6 310.3 310.3 310.3 354.7 354.7 MINUS ONE PASS COOLER Height Entering Water Connecttan (in.) 10.8 10.3 10.3 10.3 10.3 10.6 10.6 11.4 11.4 11.4 11.4 12.5 12.5 12.5 12.5 12.5 Vlctaullc Connection Size (in.) 4.0 4.0 4.0 4.0 4.0 5.0 5.0 6.0 6.0 6.0 6.0 8.0 8.0 8.0 8.0 8.0 Distance to Leaving Water Connection (in.) -2.2 -2.5 -2.5 -2.5 -2.5 -2.2 -2.2 53.6 53.2 100.6 100.6 180.3 180.3 180.3 224.7 224.7 Height Leaving Water Connection (in.) 14.9 14.9 14.9 14.9 14.9 15.9 15.9 13.2 13.2 13.2 13.2 16.3 16.3 16.3 16.3 16.3 Distance to Leaving/ Entering Water Connection (in.) 68.1 66.1 68.1 66.1 66.1 69.1 69.1 70.2 70.2 70.2 70.2 71.1 71.1 71.1 71.1 71.1 Distance to Entering Water Connection (in.) 124.8 124.5 124.5 124.5 124.5 124.8 124.6 160.6 180.2 227.6 227.6 310.3 310.3 310.3 354.7 354.7 Height Entering Water Connection (in.) 14.9 14.9 14.9 14.9 14.9 15.9 15.9 13.2 13.2 13.2 13.2 16.3 16.3 16.3 16.3 16.3 Vlctaullc Connection Size (in.) 5.0 5.0 5.0 5.0 5.0 6.0 6.0 8.0 8.0 6.0 8.0 8.0 8.0 8.0 8.0 8.0 SI STANDARD 30XA UNIT SIZE* '._ 080 090 100 110 120 140 160 180 200 220 240 260 280 300 325 350 Distanceto Leaving Water Connection Height Leaving Water Connection (ram) (ram) 3077.8 3069.6 3069.6 3069.6 3069.6 3085.8 3085.8 4512.3 4502.4 5706.2 5706.2 7739.6 7739.6 7739.6 8865.1 8865.1 484.0 484.0 484.0 484.0 484.0 540.6 540.6 571.0 571.0 571.0 571.0 600.2 600.2 600.2 600.2 600.2 Distance to Leaving/ Entering Water Connection (ram) 1728.7 1726.7 1728.7 1728.7 1726.7 1756.2 1756.2 1782.1 1782.1 1782.1 1762.1 1804.9 1804.9 1604.9 1804.9 1804.9 COOLER PLUS ONE PASS COOLER Distance to Entering Water Connection Height Entering Water Connection (ram) (ram) 3077.8 3069.6 3069.6 3069.6 3069.6 3086.8 3085.8 4512.3 4502.4 5706.2 5706.2 7739.6 7739.6 7739.6 8865.1 8865.1 274.2 274.2 274.2 274.2 274.2 268.7 268.7 287.0 287.0 287.0 287.0 310.1 310.1 310.1 310.1 310.1 Vlctaullc Connection Size (ram) 127.0 127.0 127.0 127.0 127.0 127.0 127.0 152.4 152.4 152.4 152.4 203.2 203.2 203.2 203.2 203.2 "30XA400-500 units are eq uipped wi_ standard coolers one!, Refer to unit dimensional NOTE: Refer to dimensional drawings for all oth er unit dimensions. Distanceto Leaving Water Connection Distance to Leaving/ Entering Water Height Leaving Water Connection (ram) (ram) 37.9 29.7 29.7 29.7 29.7 30.1 30.1 1361.4 1351.6 2555.3 2555.3 4580.8 4580.8 4580.8 5706.4 5706.4 497.2 497.2 497.2 497.2 497.2 540.6 540.5 569.5 569.5 569.5 569.6 593.9 593.9 593.9 593.9 593.9 Connection (mm) 1728.7 1728.7 1728.7 1728.7 1726.7 1756.2 1756.2 1782.1 1782.1 1782.1 1762.1 1804.9 1804.9 1804.9 1804.9 1804.9 DIstanceto Entering Water Connection (ram) 3077.8 3069.6 3069.6 3069.6 3069.6 3086.8 3085.8 4587.2 4577.4 5781.1 5781.1 7882.8 7882.8 7682.8 9008.4 9008.4 MINUS ONE PASS COOLER Height Entering Water Connection (ram) 261.0 261.0 261.0 261.0 261.0 268.7 268.7 288.5 288.5 288.5 286.5 316.5 316.5 316.5 316.5 316.5 Vlctaullc Connection Size (ram) 101.6 101.6 101.6 101.6 101.6 127.0 127.0 152.4 152.4 152.4 152.4 293.2 203.2 208.2 203.2 203.2 Distance to Leaving Water Connection (ram) =55.1 43.2 43.2 43.2 43.2 -55.0 -55.0 1361.4 1351.6 2555.3 2555.3 4580.8 4580.8 4580.8 5706.4 5706.4 drawings for cooler dimensions. Side View Cooler ql L I [ Entering/Leaving ] Water Length J Fig. 16 -- Cooler Option Dimensions Height Leaving Water Connection (ram) 379.1 379.1 379.1 379.1 379.1 404.6 404.6 336.0 336.0 336.0 336.0 413.3 413.3 418.3 413.3 413.3 Distance to Leaving/ Entering Water Connection (ram) 1728.7 1728.7 1728.7 1728.7 1726.7 1756.2 1766.2 1782.1 1782.1 1782.1 1762.1 1804.9 1804.9 1804.9 1804.9 1804.9 Dlstanceto Entering Water Height Entering Water Connection (ram) Connection (ram) 3170.7 3162.6 3162.6 3162.6 3162.6 3170.8 3170.8 4587.2 4577.4 5781.1 5781.1 7862.8 7862.8 7682.8 9008.4 9008.4 379.1 379.1 379.1 379.1 379.1 404.6 404.6 336.0 336.0 336.0 336.0 413.3 413.3 418.3 413.3 413.3 Vlctaullc Connection Size (ram) 127.0 127.0 127.0 127.0 127.0 152.4 152.4 208.2 203.2 203.2 203.2 203.2 203.2 208.2 203.2 203.2 -I I CO.T_ L MASTER I CHILLER PUMP & CHECK VALVE # I -4>r I I OR ISOLATION VALVE I _l SLAVE CHILLER PUMP & CHECK VALVE -bTq- I OR ISOLATION LEGEND LWT -- VALVE Leaving Water Temperature Field-Installed Communication Bus (slashes indicate number of conductor wires) Field-Installed Wiring Twisted Pair DUAL SENSORS CHILLER LWT & WELLS Fig. 17 -- Parallel Dual Chiller Operation I I SLAVE CH,LLER OONT#oO_ l I I PUMP I ,q I I I I= I I LEGEND CONTROL BOX _. MASTER CHILLER LWT Fig. 18- Series Dual Chiller Operation 32 -- Leaving Water Temperature Field-Installed Communication Bus (slashes indicate number of conductor wires) Field-Installed Wiring Twisted Pair the cooler head for maintenance. [nst_dl pipe hangers where needed. Make sum no weight or stress is placed on the water nozzle. Provide openings in fluid piping for pressure gages and thermometel_ (if used). These openings should be 5 to 10 pipe diameters from the unit leaving water nozzle. For thorough mixing and temperature stabilization, wells in the leaving fluid pipe should extend at least 2 in. (50 mm) into the pipe. Although the cooler has an air vent, it is recommended that a field-supplied air vent be installed in the system to facilitate servicing. Field-supplied shut-off and balancing v_dves should also be installed to facilitate servicing and flow balancing. Ix_cate valves in return and supply fluid lines as close to the chiller as possible. Ix)cate air vent at highest point of the cooler fluid system. See Fig. 15. _ Provide diain connections at all low points to permit complete di'ainage of the system. COOLER PUMP CONTROL--It is recommended that cooler pump control be utilized on all chillers unless the chilled water pump runs continuously or the chilled water system contains a suitable antifieeze solution. Proper configuration of the cooler pump control is required to prevent possible cooler fieeze-up. A thermal flow sensor is facto q inst_dled in the entering fluid nozzle to prevent operation without flow through the coolec See Fig. 21. The sensor contacts am facto U wired. The factou-installed flow sensor and cooler interlock must be wired in series. Install TBS-I and TBS-2 if using a cooler pump interlock and connect it to these terminals. It is also recommended that the chiller be interlocked with the chiller water pump starter to provide additional freeze protection. See the Field Control Power Connections section on page 34 for proper connection of the cooler pump interlock. The cooler pump relay will remain energized for 30 seconds after all compressors stop due to an off command. In the event a freeze protection _flarm is generated, the cooler pump relay will be energized whether the cooler pump control is configured to "ON" or "OFF". The cooler pump relay is also energized anytime a compressor is started and when certain _dmms are generated. The cooler pump relay should be used as an override to the external pump control if cooler pump control is not utilized. FLOW SWITCH Fig. 19 -- Flow Switch -[_F BAD GOOD BAD GOOD I IMPORTANT: Chilled water pump control and cooler pump interlock wiring are required to prevent possible cooler fieeze up due to loss of fluid flow. Refer to field wiring diagram for installation details. Fig. 20 -- Tank Baffling Series Dual Chiller Operation -- Series chiller operation is an alternate control method supported by the Con_/ortLink TM control chillers cooler reduce system. Certain applications might require that the two be connected in series. For nomimfl 10 ° F (5.6 ° C) ranges, use the Minus 1 Pass cooler mTangements to the fluid-side pressure diop. Use the standard cooler pass mmngement for low flow, high cooler temperature rise applications. Two field-supplied and installed dual chiller leaving water temperature sensors me required, one for each module for this function Consider isolate each allow to operate properly. adding additional piping chiller to allow for service for partial capacity fiom the other and isolation valves to on a machine, and still chillel: See Fig. @ 18. COOLER FLUID, VENT. AND DRAIN -- The inlet (return) fluid connection is always the lower of the 2 cooler connections. See Fig. 2-10 for locations. A screen strainer with a minimum size of 20 mesh must be installed a maximum of 10 ft fi'om the unit to prevent debris from dmnaging internal tubes of the coolel: Outlet (supply) fluid connection is the upper connection of the 2 cooler connections. The cooler has victaulic connections to connect the field-supplied piping. Plan the piping arrangement in accor&mce with good piping practices and ensure that the piping does not cross in front of the cooler head. Use flexible connections on cooler piping to reduce vibration transmission. Offset the piping to permit remover of Fig. 21 -- Thermal Flow Sensor 33 [ I BRINE UNITSSpecial factory modifications to the units are required to _dlow them to operate at fluid temperatures less than 34 F (1.1 C). Be sure that the fluid has sufficient inllibited glycol or other suitable corrosion-lesistant antitYeeze solution to prevent cooler freeze-up. Mount the smaller height baffle on units with a control box located on the end of the unit. It is recommended that the upper notches be used for mounting the baffles. This reduces the risk of dmnaging the coil while drilling a mounting hole. Ix_osen the upper comer post bolts and slide the baffle under the bolt and washel: Tighten the bolt. Drill holes in the bottom of the flange of the baffle and mount with two sclews to secure the bottom of the baffle to the comer post. Repeat the process for the opposite end. See Fig. 22. WATER TREATMENTUntleated or improperly tleated water may result in corrosion, sc_ding, erosion, or algae. The services of a qu_dified water tleatment specialist should be obtained to develop and monitor a treatment program. PREPARATION FOR WINTER SHUTDOWN -- If the unit is not operatiomfl during the winter months, at the end of cooling season complete the following steps. Water must be within design flow limits, clean, and treated to ensure proper chiller performance and reduce the potential of tube damage due to corrosion, scaling, erosion, and algae. Cmrier assumes no responsibility for chiller &_mage resulting from untreated or improperly treated watel: Failure to remove power before draining heater equipped coolers can result in heater tape and insulation damage. 1. [f the cooler will not be dndned do not shut off power disconnect during off-season shutdown. If the cooler is drained, open the circuit breaker for the heater. CB-HT (circuit breaker heater) or shut off power during offseason shutdown. NOTE: Do not use automobile anti-freeze, or any other fluid that is not approved for heat exchanger duty. Only use appropriately inhibited glycols, concentrated to provide adequate protection for the temperature considered. PREPARATION FOR YEAR-ROUND OPERATION -- In areas where the piping or unit is exposed to 32 F (0 ° C) or lower ambient temperatures, freeze-up protection is required using inhibited glycol or other suitable corrosion-resistant antifleeze solution and electric heater tapes. Heater tapes on piping should have a rating for ;u'ea mnbient temperatures and be covered with a suitable thickness of closed-cell insulation. Route power for the heater tapes from a sepm'ately fused disconnect. Mount the disconnect within sight from the unit per local or NEC (National Electric Code) codes. Identify disconnect at heater tape power source with a warning that power must not be turned off except when servicing unit. 2. Draining the fluid from the system is highly recommended. 3. Isolate the cooler from the rest of the system with water shutoff v_dves. 4. Completely fill the cooler with a mixture of half water and half inhibited glycol solution (or other suitable conosion-inhibitive antifreeze) for 15 ° F (8.3 ° C) below the expected low ambient temperature conditions. Leave the cooler filled with the antifreeze solution for the wintel: or drain if desired. Be sure to deenergize heaters (if installed) as explained in Step 1 to plevent damage. Use an approved method of disposal when lemoving antifreeze solution. 5. IMPORTANT: Adding antifreeze solution is the only certain means of protecting the unit flom freeze-up if heater fails or electrical power is interrupted or lost while temperatures are below 32 F (0 ° C). 6. At the beginning of the next cooling season, be sure that there is refrigerant pressure on each circuit before refilling coolel: add recommended inhibitol: trod reset the CB-HT (circuit breaker heater) (if opened) or restore powel: IMPORTANT: Before starting the unit, be sure all of the air has been purged from the system. Step 4 -- A di'ain connection is located at the bottom of the cooler head. See Fig. 2-10 for connection location. Install shut-off v_dves to the drain line before filling the system with fluid. Make Electrical Connections Electrical shock can cause personal injury and death. Shut off _fll power to this equipment during inst_fllation. There may be more than one disconnect switch. Tag all disconnect locations to alert othel_ not to restore power until work is completed. Low Ambient Temperature Head Pressure Control -- If the unit is equipped with the low ambient temperature head pressure control option, field-fabricated and field-installed wind baffles are required if the wind velocity is anticipated to be gleater than 5 mph (8 km/h). Two different baffles may be required, facing the control box. Wind baffles should be constmcted with minimum 18-gage g_dvanized sheet metal or other suitable corrosion-resistance material with cross breaks for strength. See Fig. 22. Use field-supplied screws to attach baffles to the corner posts of the machine. Be sure to hem or turn a flange on _dl edges to eliminate sharp edges on the baffles. POWER SUPPLY --The electrical ch_u'acteristics of the available power supply must agree with the unit nameplate rating. Supply voltage must be within the limits shown. See Tables 4-6 for electric_d and configuration &tta. To avoid possibility of electric_d shock, open all disconnects before installing or servicing this accessory. FIELD POWER CONNECTIONS (See Fig. 23) -- All power wiring must comply with applicable local and national codes. Install field-supplied, branch circuit lhsed disconnect(s) of a type that can be locked off or open. Disconnect(s) must be located within sight and readily accessible from the unit in compliance with NEC Article 440-14 (U.S.A.). See Tables 4 and 5 for unit electrical &_ta. See Table 6 for compressor and fan electrical &tta. To avoid dmnage to the refl'igerant coils and electrical components, use extreme ctue when drilling screw holes and screwing in fasteners. IMPORTANT: The 30XA units have a factory-inst_dled option available for a non-fused disconnect for unit power supply. If the unit is equipped with this option, all field power wiring should be made to the non-fused disconnect since no terminal blocks are supplied. 34 Cross break these faces. Hem these 3 edges both top and bottom. 305 [12.0] 4 See Detail A \ 1880 [74.0] BAFFLE HEIGHT (X) RIGHT END LEFT END POSITION 30XA080-120 (Facing the control box end I 30XA140-500 (Facing the control box end) 1040 [41.0] 635 [25.0] 1040 [41.0] 1040 [41.0] NOTES: 1. Material: 18 ga. Corrosion Resistant Sheet Metal. 2. Dimensions are in mm [inches], 18 [0.75] _'_ _Z0 [2"7 t .............. L_SDetailA 1--18 es_ [0.75] _*_31 [1.25] _21 [0.88] Typical Both Flang Fig. 22 -- Field-Fabricated Maximum wile size that the unit terminal fused disconnect will accept is 500 kcmil. and Field-Installed Wind Baffles block or non- The 30XA units require 1 or 2 power supplies, depending on the unit and circuit voltage. See Tables 4 and 5 for the number of power supplies required for each unit. Do not use interlocks or other safety device contacts connected between TB5-9 and TB5-10 as remote on-off. Connection of safeties or other interlocks between these 2 terminals will result in an electrical bypass if the ENABLE-OFF-REMOTE contact switch is in the ENABLE position. If remote on-offunit control is required, a field-supplied lelay must be installed in the unit control box and wired as shown in Fig. 22. Failure to wire the remote on-off as recommended may result in tube freeze &tmage. FIELD CONTROL POWER CONNECTIONS (See Fig. 23) -Units with a power supply of all voltages require 115-1-60 control circuit power, unless the control option is installed. Terminals TB5-1 and TB5-2 ale provided for field installation of a chilled water (fluid) pump interlock (CWPI). Tile chilled water (fluid) flow sensor (CWFS) is factory installed. These devices ale to be installed in series. Contacts must be rated for dry-circuit applications capable of handling a 24-vac at 50 mA load. Terlninals 11 and 13 of TB5 me for control of the chilled water pump 1 (PMPI) startel: Terminals 13 and 15 of TB5 me for control of the chilled water pump 2 (PMP2) startel: An accessory remote on-off switch c:m be wired into TB5-9 and TB5-10. To use this feature, remove the factory-installed jumper and install the device in series. Contacts must be rated for dry-circuit applications capable of handling a 24-vac at 50 mA load. 35 iO T_A .:.=_ iO I I I I I I I I I I I I I I I I I I I FIELO ,_ _ _ _ _ _ _ _ _ POW[R SUPPLT ,- ACCESSORY &Be {SEE NOTE_2_ TERMINAL BLOCK i i_l i_l _l I I I I I I I I_1 I: i Iiili LI LI_LI_ C81A DA_A_OMFORT I I I I I I I I M-L I I _]_LO I _o_ I I I f. .... I !.. !.. I i suP,_ I I ! I L..a -- I DISCONNECT/BRANCH CIRCUIT PRO_C'nO_ _ BEG I J (SEE NOTE _2_ NON-FUSED DISCONNECT NOTES: 1. Factory 2. _iCegltohr Incoming Incoming Incoming LEGEND wiring is in accordance with UL 1995 standard& Field a_ll_,P fPilie_bslepCp_d_-_ustbe rated 75 C ,'ninimurn. wire size range wire size range wire size range for units 080-120, for units 140-240, for units 140-240, modifications Use copper or additions must be in compli- for allunits. all voltages is 4-500 kcmil. 200/230 v is 1/0-500 kcrnil. 380,460, 575 v is 4%00 kcmil. 3. [ peCr °/_1iliads_ rell_i Zleora_l_-_ _° r UenitoSr2ieOd500_ 380,4o610 ,eSc tTiSlvsi;lr/O-m500 koOnm(Hif, The contacts must be rated A -- Alarm EMM MLV NEC PMP PMPI TB -I --I I Energy Management Minimum Load Valve National Electric Code Chilled Water Pump Chilled Water Pump Interlock Terminal Block iiii iiii 4. _errdrl_nci_c_ita_jP_Co_tl_B_aPeabloer be rated for dry circuit application °fxthea_ldallll_gonal2e4ctVoa,_ capable of handling 50alt_rApump a 24 vac interlock. The contacts must load up to 50 mA. 5. Ter_'ninals TB5 are for 11control and 13 of of chilled TB5 _et fOrpCOn_r_l ofc_Hedtwa_rr ,_,_ _---_-_- J_umpl Field Power .... Field Control -- Factory [,,P,M,,Pll)starr _ _-_, tller:,,Ter,'ni!la/s ,_,_ Ofchille 13 andwater15 d 6. _UmcPo[_lra_ i_ c5_lesde_lletd,r 10Vapin, raUShe_to24oV_mFi_llyd oPpeWecrSUtPaPcltYs iSal]eOc_ _eq_irrydcircui t application must be supplied from field-supplied pump starter relay. Connect contacts to violet and pink wires in harness from main base board channel l& Wires in harness are marked PMP1-13 and PMP1-14. 7. Terminals 12 and 13 of TB5 are for an alarm relay. The maximum load allowed for the alarm relay is 10 va 8, _/_ E_l__al_edapproprIiateScont,#ctions_o & ;"*11 _" " '34 " board -_'"_*_''1" *_"";*_'4_Be_ss_oH_°foIrei_,_gy_anagernent ;_ "_÷ _CC_liagCaY_,_e_icd&ddeumpal_d/_imt,_l]d ice done options must options. be rated for dry circuit The application contacts capable for of Fig. 23 -- Control and Power Wiring Schematic, 30XA080-500 36 Wiring Wiring Installed Wiring Table 4 -- 30XA080-500 Electrical Data (Standard Condenser Fan Motors) (3 Ph, 80 Hz) MIn Max MAIN POWER SUPPLY OTY REOD 080 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 1 1 1 1 1 347.6 315.5 183.5 157.7 121.2 090 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 1 1 1 1 1 1O0 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 11o 200 230 380 460 575 187 207 342 414 518 120 200 230 380 460 575 140 UNIT 30XA VOLTAGE VOLTAGE RANGE ICF XL WD RED FUSE SIZE 450 400 250 200 150 1257.6 1100.2 662.7 550.1 437.9 521.6 460.2 275.7 230.1 181.9 368.0 334.0 194.5 167.0 128.5 500 450 250 225 175 1274.0 1115.1 671.6 557.6 443.8 1 1 1 1 1 401.3 364.6 212.7 182.3 139.5 500 500 250 250 175 220 253 418 506 633 1 1 1 1 1 446.2 405.7 236.4 202.4 155.5 187 207 342 414 518 220 253 418 506 633 1 1 1 1 1 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 1 1 1 1 1 200 230 380 460 575 200 230 380 460 575 187 207 342 414 518 187 207 342 414 518 220 253 418 506 633 220 253 418 506 633 2 2 1 1 1 2 2 1 1 1 465.6/264.9 423.5/241.0 361.1 309.7 238.1 407.2/407.2 370.0/370.0 391.5 336.6 258.3 800/450 700/400 500 450 350 700/700 600/600 500 450 350 --/---/-1564.9 1296.4 1034.3 --/---/-1336.2 1109.6 882.8 902.8/463.5 786.0/404.0 590.9 491.4 390.3 729.8/729.8 636.0/636.0 561.2 469.6 370.8 200 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 2 2 1 1 1 465.6/465.6 423.5/423.5 447.2 383.9 294.8 800/800 700/700 600 500 400 --/---/-1651.0 1370.6 1091.0 220 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 2 2 1 1 1 554.7/548.0 504.2/423.5 494.5 424.7 326.3 800/800 800/700 700 600 450 240 200 230 380 460 575 187 207 342 414 518 220 253 418 506 633 2 2 1 1 1 554.7/548.0 504.2/498.2 529.5 455.0 349.6 800/800 800/800 700 600 450 260 380 460 575 342 414 518 418 506 633 1 1 1 600.2 516.5 396.4 800 700 500 2376.9 1969.6 1570.2 917.9 764.6 606.2 280 380 460 575 342 414 518 418 506 633 1 1 1 638.2 549.8 422.0 800 800 600 2414.9 2002.9 1595.9 300 380 460 575 342 414 518 418 506 633 1 1 1 710.3 610.9 468.7 1000 800 600 2415.4 2002.9 1595.9 325 380 460 575 342 414 518 418 506 633 2 1 1 426.0/426.0 624.3 479.1 700/700 800 600 2202.7/2202.7 2077.5 1652.9 743.7/743.7 872.5 688.9 350 380 460 575 342 414 518 418 506 633 2 1 1 497.6/426.0 685.5 525.7 800/700 800 700 2202.7/2202.7 2077.5 1652.9 400 380 460 575 342 414 518 418 506 633 2 2 2 419.4/561.9 340.9/452.0 261.4/347.2 700/700 500/600 450/450 450 380 460 575 342 414 518 418 506 633 2 2 2 490.9/685.4 402.0/553.6 308.0/424.4 500 380 460 575 342 414 518 418 506 633 2 2 2 490.9/745.1 402.0/604.9 308.0/463.9 160 180 MCA MOCP ---- Instantaneous Current Flow Minimum Circuit Amps Maximum Overcurrent Protection WD -- Wye=Dega Across-the-Line CIRCUIT MCA and MOCP 400 35O 225 175 15O 538.0 475.1 284.6 237.6 187.8 45O 400 225 200 15O 115 115 115 115 115 3O 3O 3O 3O 3O 1564.8 1368.7 824.7 684.4 544.7 644.8 568.7 340.7 284.4 224.7 45O 400 250 200 175 115 115 115 115 115 3O 3O 3O 3O 3O 600 500 300 250 200 --824.7 684.4 544.7 644.8 568.7 340.7 284.4 224.7 5OO 45O 3OO 225 175 115 115 115 115 115 3O 3O 3O 3O 3O 482.2 438.6 255.3 218.4 168.4 600 600 350 300 225 --843.6 700.4 557.5 680.8 601.6 359.6 300.4 237.5 6OO 5OO 3OO 25O 2OO 115 115 115 115 115 3O 3O 3O 3O 3O 588.5 534.7 311.2 800 800 450 1255.9 267.3 205.0 400 300 1040.4 829.5 911.1 800.7 480.9 400.4 317.5 7OO 7OO 35O 35O 25O 115 115 115 115 115 3O 3O 3O 3O 3O 600/350 600/300 45O 35O 3OO 500/500 450/450 45O 4OO 3OO 115 115 115 115 115 115 115 115 115 115 3O 3O 3O 3O 3O 3O 3O 3O 3O 3O 902.8/902.8 786.0/786.0 677.0 565.6 447.0 600/600 600/600 5OO 45O 35O 115 115 115 115 115 3O 3O 3O 3O 3O --/---/-1654.6 1373.6 1093.4 909.4/902.8 792.0/786.0 680.6 568.6 449.4 700/600 600/600 6OO 5OO 4OO 115 115 115 115 115 3O 3O 3O 3O 3O --/---/-1689.5 1403.9 1116.7 909.4/902.8 792.0/786.0 715.5 598.9 472.7 700/700 600/600 6OO 6OO 4OO 115 115 115 115 115 30 3O 3O 3O 3O 7OO 6OO 45O 115 115 115 3O 3O 3O 955.9 797.9 631.9 8OO 7OO 5OO 115 115 115 3O 3O 3O 956.4 797.9 631.9 8OO 7OO 6OO 115 115 115 3O 3O 3O 500/500 7OO 6OO 115 115 115 3O 3O 3O 743.7/743.7 872.5 688.9 600/500 8OO 6OO 115 115 115 3O 3O 3O 2196.1/1722.0 1794.0/1400.9 1435.2/1114.3 737.1/748.0 589.0/595.9 471.2/470.3 500/700 450/500 350/400 115 115 115 5O 5O 5O 800/1000 700/ 800 500/ 600 2196.1/2390.5 1794.0/1945.6 1435.2/1551.6 737.1/931.5 589.0/740.6 471.2/587.6 600/500 500/700 400/500 115 115 115 5O 5O 5O 800/1000 700/ 800 500/ 600 2196.1/2450.2 1794.0/1996.9 1435.2/1591.1 737.1/991.2 589.0/791.9 471.2/627.1 600/1000 500/ 700 400/ 600 115 115 115 5O 5O 5O LEGEND ICF MCA MOCP CONTROL Voltage (1 Ph, 80 Hz) 115 115 115 115 115 -- 3O 3O 3O 3O 3O 4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units. a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage) to 500 kcmil. b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is 3/0 to 500 kcmil. c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps is 1/0 to 500 kcmil. d. Incoming wire size range o1non-fused disconnect with MCA from 800 to 1199.9 amps is 250 kcmil to 500 kcmiL 5. Data provided circuit I/circuit 2 where there are two circuits. NOTES: 1. Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed minimum and maximum limits. Maximum allowable phase imbalance is: voltage, 2%; amps 10%. 2. Cooler heater is wired into the control circuit so it is always operable as long as the control power supply disconnect is on, even if any safety device is open. 3. For MCA that is less than or equal to 380 amps, 3 conductors are required. For MCA between 381-760 amps, 6 conductors are required. For MCA between 761 -1140 amps, 9 conductors are required. For MCA between 1141-1520 amps, 12 conductors are required. Calculation of conductors required is based on 75 C copper wire. 37 Table 5 -- 30XA140-500 UNIT 30XA VOLTAGE VOLTAGE RANGE MAIN POWER SUPPLY GTY REQD Electrical Data (High Ambient Temperature Option) ICF MCA MOCP 618.8 561.9 327.9 282.0 216.2 800 800 450 400 300 (3 Ph, 60 Hz) MIn Max 140 200 230 380 460 575 187 207 342 414 518 220 263 418 506 633 1 1 1 1 1 160 200 230 380 460 575 187 207 342 414 518 220 263 418 506 633 2 2 1 1 1 477.9/273.7 434.8/249.1 374.5 321.5 247.0 180 200 230 380 460 575 187 207 342 414 518 220 263 418 506 633 2 2 1 1 1 200 200 230 380 460 575 187 207 342 414 518 220 263 418 506 633 220 200 230 380 460 575 187 207 342 414 518 240 200 230 380 460 575 260 XL REC FUSE SIZE MCA and MOCP 957.8 842.9 506.3 422.5 334.3 800/450 760/406 500 450 350 --/---/-1588.4 1317.0 1049.9 934.4/484.6 614.8/423.2 614.4 512.0 405.9 600/350 600/300 45O 400 300 115 115 115 115 115 30 30 30 30 30 422.4/422.4 383.8/383.8 416.3 353.1 271.0 760/700 660/600 500 450 350 --/---/-1363.7 1133.6 901.1 761.4/761.4 664.6/664.8 588.7 493.6 389.1 500/500 450/450 45O 4OO 3OO 115 115 115 115 115 30 30 30 30 30 2 2 1 1 1 477.9/477.9 434.8/434.8 463.4 398.1 305.6 800/800 760/706 600 500 400 --/---/-1677.3 1393.6 1108.5 934.4/934.4 614.6/814.8 703.3 588.6 464.5 600/600 600/600 6OO 45O 35O 115 115 115 115 115 30 30 30 30 30 220 263 418 506 633 2 2 1 1 1 567.4/477.9 516.0/434.8 511.0 439.3 337.3 800/860 800/700 700 600 450 --/---/-1683.8 1399.1 1112.8 946.8/934.4 625.6/814.8 709.8 694.1 468.8 700/600 700/600 6OO 5OO 4OO 115 115 115 115 115 30 30 30 30 30 187 207 342 414 518 220 263 418 506 633 2 2 1 1 1 567.4/555.5 516.0/505.2 543.9 467.8 359.2 800/800 800/800 700 600 450 --/---/-1716.7 1427.6 1134.7 946.8/934.4 625.6/814.8 742.7 622.6 490.7 700/700 700/600 6OO 6OO 4OO 115 115 115 115 115 30 30 30 30 30 380 460 575 342 414 518 418 506 633 1 1 1 616.2 530.6 407.0 800 700 500 2411.8 2000.1 1593.4 952.8 795.1 629.4 7OO 6OO 5OO 115 115 115 30 30 30 280 380 460 575 342 414 518 418 506 633 1 1 1 649.1 559.1 428.9 800 700 600 2444.7 2028.6 1615.3 985.7 823.6 651.3 86O 7OO 5OO 115 115 115 30 30 30 300 380 460 575 342 414 518 418 506 633 1 1 1 721.7 621.2 476.3 1000 800 600 2451.2 2034.1 1619.6 992.2 829.1 655.6 1000 7OO 6OO 115 115 115 30 30 30 325 380 460 575 342 414 518 418 506 633 2 1 1 405.9/406.9 639.9 496.7 600/600 800 600 2201.5/2201.5 2109.4 1677.1 742.6/742.5 904.4 713.1 500/500 8OO 6OO 115 115 115 30 30 30 350 380 460 575 342 414 518 418 506 633 2 1 1 472.0/405.9 696.4 533.8 860/600 800 700 2201.5/2201.5 2109.4 1677.1 742.6/742.5 904.4 713.1 600/500 8OO 6OO 115 115 115 30 30 30 400 380 460 575 342 414 518 418 506 633 2 2 2 399.4/537.4 344.5/462.3 264.0/354.9 660/700 500/600 400/450 2195.0/1710.2 1814.0/1422.2 1450.4/1130.4 736.0/736.2 609.0/617.2 486.4/486.4 500/600 450/600 350/400 115 115 115 50 50 50 380 460 575 380 460 575 342 414 518 342 414 518 418 606 633 418 506 633 2 2 2 2 2 2 465.5/652.2 401.0/561.6 307.2/430.5 465.6/706.7 401.0/610.2 307.2/467.7 760/800 660/800 560/600 700/1000 600/ 800 500/ 600 2195.0/2381.7 1814.0/1974.6 1456.4/1573.7 2195.0/2438.2 1814.0/2023.2 1450.4/1611.0 736.0/922.7 609.6/769.6 486.4/609.7 736.0/979.2 609.0/818.2 486.4/647.0 600/600 600/700 400/500 600/600 500/700 400/600 115 115 115 115 115 115 50 50 50 50 50 50 500 LEGEND ICF MCA MOCP WD XL ------ 700 700 400 350 250 CIRCUIT Voltage (1 Ph, 60 Hz) 115 115 115 115 115 12_.3 1062.5 846.3 450 -- CONTROL WD 30 30 30 30 30 4. For MCA that is less than or equal to 380 amps, 3 conductors are required. For MCA between 381-766 amps, 6 conductors are required. For MCA between 761 -1140 amps, 9 conductors are required. For MCA between 1141-1520 amps, 12 conductors are required. Calculation o1 conductors required is based on 75 C copper wire. 5. Wiring for r'_lainfield supply r'_lustbe rated 75 C minirnur'_l. Use copper for all units. a. Incor'_ling wire size range for the terminal block is no. 4 AWG (American Wire Gage) to 500 kcrniL b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 arnps is 3/0 to 500 kcmiL c. Incoming wire size range of non-fused disconnect with MCA from 600 k) 799.9 arnps is 1/0 to 500 kcmiL d. Incoming wire size range of non-fused disconnect with MCA from 600 to 1199.9 amps is 250 kcrnil to 500 kcmil. 6. Data priwided circuit I/circuit 2 where there are two circuits. Instantaneous Current Flow Minimum Circuit Amps Maximum Overcurrent Protection Wye-Delta Across-the-Line NOTES: 1. The high ambient option is not available on 30XA080-126 units. 2. Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed minir'_lum and maximum limits. Maximum allowable phase ir'_lbalance is: voltage, 2%; amps 10%. 3. Cooler heater is wired into the control circuit so it is always operable as long as the control power supply disconnect is on, even if any safety device is open. 38 Table 6 -- Compressor and Fan Electrical Data COMPRESSOR UNIT VOLTAGE V-Hz 30XA UNIT SIZE 090 100 110 120 140 160 180 200 220 240 260 280 300 328 380 400 480 800 A LRA (All Units) NUMBER OF COND B RLA LRA (All Units) --- *Quantity LRA (All Units) Standard Dond. Fans (080 rpm) XL WD High Ambient Temp Cond. Fans (1140 rpm) 6.6 6.0 1081.0 940.0 345.0 300.0 130.9 118.9 WD High Ambient Temp Cond. Fans (1140 rpm) Standard Cond. Fans (850 rpm) XL 1081.0 940.0 345.0 300.0 130.9 118.9 136.8 124.2 .... .... 200 230 6 6 380 6 6.5 3.6 569.0 182.0 68.8 71.9 569.0 182.0 68.8 71.9 .... 460 575 6 6 5.5 4.3 3.0 2.4 470.0 376.0 150.0 120.0 59.4 45.4 62.1 47.5 470.0 376.0 150.0 120.0 59.4 45.4 62.1 47.5 .... .... 200 8 11.9 6.6 1081.0 345.0 134.3 140.0 1081.0 345.0 134.3 140.0 .... 230 380 460 8 8 8 10.8 6.5 5.5 6.0 3.6 3.0 940.0 569.0 470.0 300.0 182.0 150.0 122.0 70.6 61.0 127.1 73.5 63.6 940.0 569.0 470.0 300.0 182.0 150.0 122.0 70.6 61.0 127.1 78.5 63.6 .... .... .... 575 8 4.3 2.4 376.0 120.0 46.6 48.6 376.0 120.0 46.6 48.6 .... 200 230 8 8 11.9 10.8 6.6 6.0 1357.0 1180.0 437.0 380.0 148.4 134.9 154.8 140.7 1357.0 1180.0 437.0 380.0 148.4 134.9 154.8 140.7 .... .... 380 460 8 8 6.5 5.5 3.6 3.0 714.0 590.0 230.0 190.0 78.3 67.5 81.6 70.4 714.0 590.0 230.0 190.0 575 200 8 8 4.3 11.9 2.4 6.6 472.0 1357.0 152.0 437.0 51.3 180.9 53.5 190.7 472.0 1357.0 152.0 437.0 230 380 8 8 10.8 6.5 6.0 3.6 1180.0 714.0 380.0 230.0 164.7 95.4 173.6 100.6 1180.0 714.0 460 8 5.5 3.0 590.0 190.0 82.0 86.4 575 200 8 8 4.3 11.9 2.4 6.6 472.0 1357.0 152.0 437.0 62.9 180.9 230 380 8 8 10.8 6.5 6.0 3.6 1180.0 714.0 380.0 230.0 460 575 8 8 5.5 4.3 3.0 2.4 590.0 472.0 190.0 152.0 200 10 11.9 6.6 2162.0 230 380 10 10 10.8 6.5 6.0 3.6 1880.0 1138.0 460 575 10 10 5.5 4.3 3.0 2.4 200 230 6/4 6/4 11.9 10.8 380 460 10 10 6.5 5.5 FANS* RLA FLA Standard Cond. Fans (880 rpm) XL 136.8 124.2 78.8 81,6 .... 67.5 70.4 .... 51.3 148.4 53.5 154.8 .... .... 380.0 230.0 134.9 140.7 .... 78.8 81,6 .... 590.0 190.0 67.5 70.4 .... 66.3 190.7 472.0 1357.0 152.0 437.0 51.3 180.9 53.5 190.7 .... .... 164.7 95.4 173.6 100.6 1180.0 714.0 380.0 230.0 164.7 95.4 173.6 100.6 .... .... 82.0 62.9 86.4 66.3 590.0 472.0 190.0 152.0 82.0 62.9 86.4 66.3 .... .... 690.0 280.8 293.9 1357.0 437.0 148.4 154.8 .... 600.0 363.0 255.2 147.7 267.2 154.6 1180.0 714.0 380.0 230.0 134.9 140.7 .... 78.8 81,6 .... 940.0 752.0 300.0 240.0 127.6 97.5 133.6 102.0 590.0 472.0 190.0 152.0 67.5 51.3 70.4 53.5 .... .... 6.6 6.0 2714.0 2360.0 863.0 750.0 325.2 296.0 340.6 310.0 1357.0 1180.0 437.0 380.0 180.9 164.7 190.7 173.6 .... .... 3.6 3.0 1428.0 1180.0 454.0 375.0 171.3 147.6 179.4 154.6 714.0 590.0 230.0 190.0 95.4 82.0 100.6 86.4 .... .... 575 10 4.3 2.4 944.0 300.0 112.9 118.2 472.0 152.0 62.9 66.3 .... 200 230 6/6 6/6 11.9 10.8 6.6 6.0 2162.0 1880.0 690.0 600.0 280.8 255.2 293.9 267.2 2162.0 1880.0 690.0 600.0 280.8 255.2 293.9 267.2 .... .... 380 460 12 12 6.5 5.5 3.6 3.0 1138.0 940.0 363.0 300.0 147.7 127.6 154.6 133.6 1138.0 940.0 363.0 300.0 147.7 127.6 154.6 138.6 .... .... 575 200 12 6/6 4.3 11.9 2.4 6.6 752.0 2714.0 240.0 863.0 97.5 325.2 102.0 340.6 752.0 2714.0 240.0 863.0 102.0 .... 325.2 340.6 .... 230 6/6 10.8 6.0 2360.0 750.0 296.0 310.0 2360.0 750.0 296.0 310.0 .... 380 460 12 12 6.5 5.5 3.6 3.0 1428.0 1180.0 454.0 375.0 171.3 147.6 179.4 154.6 1428.0 1180.0 454.0 375.0 171.3 147.6 179.4 154.6 .... .... 575 200 12 7/6 4.3 11.9 2.4 6.6 944.0 2714.0 300.0 863.0 112.9 387.3 118.2 406.6 944.0 2714.0 300.0 863.0 112.9 325.2 118.2 340.6 .... .... 230 380 7/6 13 10.8 6.5 6.0 3.6 2360.0 1428.0 750.0 454.0 352.3 204.2 369.8 214.3 2360.0 1428.0 750.0 454.0 296.0 171.3 310.0 179.4 .... .... 97.6 WD High Ambient Temp Cond. Fans (1140 rpm) Standard Cond. Fans (080 rpm) 460 575 13 13 5.5 4.3 3.0 2.4 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 1180.0 944.0 375.0 300.0 147.6 112.9 154.6 118.2 .... .... 200 7/6 11.9 6.6 2714.0 863.0 387.3 406.6 2714.0 863.0 387.3 406.6 .... 230 380 7/6 13 10.8 6.5 6.0 3.6 2360.0 1428.0 750.0 454.0 352.3 204.2 369.8 214.3 2360.0 1428.0 750.0 454.0 352.3 204.2 369.8 214.3 .... .... 460 575 13 13 5.5 4.3 3.0 2.4 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 .... .... 380 460 15 15 6.5 5.5 3.6 3.0 2143.0 1770.0 684.0 565.0 277.9 240.4 293.0 253.5 1428.0 1180.0 454.0 375.0 171.3 147.6 179.4 154.6 .... .... 575 15 4.3 2.4 1416.0 452.0 183.7 193.7 944.0 300.0 112.9 118.2 .... 380 460 16 16 6.5 5.5 3.6 3.0 2143.0 1770.0 684.0 565.0 277.9 240.4 293.0 253.5 1428.0 1180.0 454.0 375.0 204.2 176.1 214.3 184.9 .... .... 575 380 16 16 4.3 6.5 2.4 3.6 1416.0 2143.0 452.0 684.0 183.7 330.8 193.7 350.3 944.0 1428.0 300.0 454.0 134.8 204.2 141.5 214.3 .... .... 460 575 16 16 5.5 4.3 3.0 2.4 1770.0 1416.0 565.0 452.0 285.6 218.2 302.4 231.0 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 .... .... 380 460 9/9 18 6.5 5.5 3.6 3.0 2143.0 1770.0 684.0 565.0 277.9 240.4 293.0 253.5 2143.0 1770.0 684.0 565.0 277.9 240.4 293.0 253.5 .... .... 575 18 4.3 2.4 1416.0 452.0 183.7 193.7 1416.0 452.0 183.7 193.7 .... 380 460 9/9 18 6.5 5.5 3.6 3.0 2143.0 1770.0 684.0 565.0 330.8 285.6 350.3 302.4 2148.0 1770.0 684.0 565.0 277.9 240.4 293.0 253.5 .... .... 575 380 18 8/12 4.3 6.5 2.4 3.6 1416.0 1428.0 452.0 454.0 218.2 204.2 231.0 214.3 1416.0 1428.0 452.0 454.0 183.7 204.2 193.7 214.3 .... 293.0 2143.0 277.9 293.0 460 575 8/12 8/12 5.5 4.3 3.0 2.4 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 1180.0 944.0 375.0 300.0 176.1 134.8 184.9 141.5 253.5 193.7 1770.0 1416.0 240.4 183.7 253.5 193.7 380 8/14 6.5 3.6 1138.0 363.0 147.7 154.6 2143.0 684.0 330.8 350.3 2143.0 684.0 330.8 350.3 460 575 8/14 8/14 5.5 4.3 3.0 2.4 940.0 752.0 300.0 240.0 127.6 97.5 133.6 102.0 1770.0 1416.0 565.0 452.0 285.6 218.2 302.4 231.0 1770.0 1416.0 565.0 452.0 285.6 218.2 302.4 231.0 380 460 8/14 8/14 6.5 5.5 3.6 3.0 1428.0 1180.0 454.0 375.0 204.2 176.1 214.3 184.9 2148.0 1770.0 684.0 565.0 330.8 285.6 350.3 302.4 2143.0 1770.0 684.0 565.0 330.8 285.6 350.3 302.4 575 8/14 4.3 2.4 944.0 300.0 134.8 141.5 1416.0 452.0 218.2 231.0 1416.0 452.0 218.2 231.0 LEGEND LRA RLA C RLA High Ambient Temp Cond. Fans !1140 rpm ! 11.9 10.8 (3 Ph, 60 Hz) 080 CONDENSER FANS Locked Rotor Amps Rated Load Amps of fan motors for incoming WD XL -- NOTES: 1. For 30XA080-350 units with dual power supply, main power supply 1 uses refrigerant circuit A components to calculate MCA and MOOR Main power supply 2 uses refrigerant circuit B components to calculate MCA and MOOR 2. 30XA400-500 units have dual power supplely..Main power supply 1 uses refrigerant circuit C components to calculate MCA and MOOR Main power supply 2 uses refrigerant circuit A and B components to calculate MCA and MOOR Wye Delta Across-the-Line power supply Circuit 1/Circu9 2. 39 CARRIER COMFORT NETWORK@ COMMUNICATION BUS WIRING (See Fig. 24) -- The communication bus wiring is a shielded, 3-conductor cable wifll &'ain wire and is field supplied and instCdled in the field. 3. Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the (-) terminal. 4. The RJI 4 CCN connector on TB3 can also be used, but is only intended for temporary connection (for example, a laptop computer running service tool). The system elements tue connected to the communication bus in a &fisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Winng connections for CCN (Carrier Comfort Network) should be made at TB (terminal block) 3. Consult the CCN Contractor's Manual for further information. See Fig. 24. NOTE: Conductors and &'ain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned coppel: Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum opemfing temperature range of-4 F (-20 C) to 140 F (60 C) is required. See Table 7 for a list of manufacturers that produce CCN bus wiring that meet these requirements. Table 7 -- CON Communication IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, disconnect the machine from the CCN. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus. NON-CCN COMMUNICATION WIRING -- The 30XA units offer severtd non-CCN translatoL's. Refer to the separate installation instructions for additional wiring steps. FIELD CONTROL OPTION WIRING -- Install field control wiring options. Some options, such as 4 to 20 mA demand limit that requires the Energy Management Module, may require that accessories be installed first (if not factory installed) for terminal connections. DUAL CHILLER LEAVING WATER SENSOR --If the dual chiller algorithm is used and the machines are installed in parallel, an additional chilled water sensor must be installed for each chillec Install the wells in the common leaving water header See Fig 25. DO NOT relocate the chiller's leaving water thermistoLs. They must remain in place for the unit to operate properly. The thermistor well is a 1/4 in. NPT fitting for securing the well in the piping. The piping must be drilled and tapped for the well. Select a location that will allow for removal of the thermistor without any restrictions. Bus Wiring PART NUMBER MANUFACTURER Regular Wiring 1895 A21451 8205 D6451 M13402 6130 Alpha American Belden Columbia Manhatten Quabik Plenum Wiring A48301 884421 M64430 it is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables containing different colored wires. At each system element, the shields of its communication bus cables must be tied togethel: If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network: Once the well is inserted, install the thermistors. Insert the thermistor into the well until the o-ring reaches the well body. Use the nut on the thermistor to secure the thermistor in place. Once the thermistor is in place, it is recommended that a thermistor wire loop be made and secured with a wire tie to the chilled water pipe. See Fig. 26. For dual chiller control a CCN bus must be connected between the two modules. See the Carrier Comfort Network Communication Bus Wiring section for additional information. 1. Turn off power to the control box. 2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (-) conductors. Substitute appropriate colors for different colored cables. --MZZZ3 o[21121 LEN CCN oE3E3 LEN CCN TO NEXT DEVICE LEGEND CCN LEN --- Carrier Comfort Network Local Equipment Network Fig. 24 -- TB3 -- CON Wiring 4O 2.315 in._ REMOVAL Fig. 25 -- Dual Leaving Water WELL BODY. WIRE TIE\ \ The GFI-CO receptacle. LOOP THERMISTOR WIRE AND SECURE TO CHILLED WATER Well UNIT SECURITY/PROTECTION ACCESSORIES -- For applications with unique security and/or protection requirements, several options are available for unit protection. Security grilles and hail guards are available. Contact a local Carrier representative for more details. For inst_fllation details, refer to separate inst_dlation instructions supplied with the accessory package. COMMUNICATION ACCESSORIES -- A number of communication options are available to meet any requirement. Contact a local Carder representative for more details. For installation details, refer to sep_u'ate installation instructions supplied with the accessory package. SERVICE OPTIONS -- Two accessories are available to aid in servicing 30XA units: a ground fault convenience outlet (GFI-CO) and a remote service port. INSERT THERMISTOR UNTIL O-RING MEETS THE THERMISTOR Thermistor is a convenience outlet with a 4-amp The remote service port is housed in a weather-proof enclosure with a communication port to plug in the Navigato( TM device. PIPE Step 5 -- Install Accessories -- A number of accessories are available to provide the following optional features Contact a local Carrier representative for more installation details, refer to sepm'ate installation supplied with each accessory package. CONTROL TRANSFORMER -- The control accessory eliminates the need for a separate power (for details, refer to file Controls shipped with the unit). Step 6 -- Leak Test Unit -- The Fig. 26 -- Dual Leaving Water Thermistor and Troubleshooting • • • dettfils. For instructions transformer supply. guide 30XA units are shipped with a complete operating charge of R-134A (see Tables IA and IB) and should be under sufficient pressure to conduct a leak test. ENERGY MANAGEMENT MODULE -- The Energy Management Module is used for any of the following types of temperatme reset, demand limit and ice features: • GFI = 4 to 20 mA inputs for cooling set point reset and capacity limit 0equires field-supplied 4 to 20 mA generator) 0 to 10 v output for percentage total capacity running 24 v discrete outputs for shutdown and running relays 10k space temperature input I R-134a only. DO NOT USE ANY OTHER refrigerIMPORTANT: ant in these units.These units are designed for use with Pedorm a leak test to ensure that leaks have not developed during unit shipment. Dehydration of the system is not required unless the entire refrigerant charge has been lost. There are several O-ring face seal fittings utilized in the oil line piping. If a leak is detected at any of these fittings, open the system and inspect the O-ring sudace for foreign matter or damage. Do not reuse O-rings. Repair any leak found following good lefrigeration practice. Discrete inputs for occupancy override, demand limit switch 2 (step 1 demand limit is wired to the base board, requires field-supplied dry contacts), remote lockout switch and ice done switch (requires field-supplied dlT contacts) REMOTE ENHANCED DISPLAY -- For applications where remote monitoring of the equipment is required; the remote enhanced display provides an indoor display, capable of monitoring any equipment on the Carrier Comfort Network® (CCN) bus. A CCN bus is required. LOW AMBIENT TEMPERATURE OPERATION -- If outdoor ambient operating temperatures below 32 F (Oo C) are expected, refer to separate installation instructions for lowambient operation using the low ambient temperature head pressure control accessory. M[NIMUM LOAD ACCESSORY -- Contact a loc_fl Carrier representative for more details if a minimum load accessory is required for a specific application. For installation details, refer to sepm'ate inst_fllation instructions supplied with the accessory package. DO NOT OVERTIGHTEN THESE FITFINGS. tightening will result in O-ring dmnage. Step 7 -- Refrigerant Over- Charging DEHYDRATION -- Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for details. Do not use compressor to evacuate system. 41 I I REFRIGERANT CHARGE IMPORTANT: Theseunitsm'edesigned for usewith ] R-134a only. DO NOT USE ANY OTHER these units. The liquid chmging method is recommended charging or when additional charge is required. refrigerant in I DO NOT OVERCHARGE system. Overcharging results in higher discharge pressure with higher cooling fluid consumption, possible compressor damage, and higher power consumption. for complete The 30XA units ale shipped fiom the factory with a full chmge of R-134a. The unit should not need to be charged at installation unless a leak was detected in Step 6 -- Leak Test Unit section. If dehydration and recharging is necessmy, use industry standard practices or refer to Carrier Standard Service Techniques Manual as required. When charging, circulate water through the cooler at all times to prevent freezing. Freezing damage is considered abuse and may void the Carrier warranty. 42 Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, PC 903 Catalog No. 533-00068 or change at any time, specifications Printed in U.S.A. or designs without notice and without incurring obligations. Form 30XA-1SI Pg 44 6-05 Replaces: New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 44 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 13:06:02 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools