CARRIER Package Units(both Units Combined) Manual L0522671
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 148
Download | |
Open PDF In Browser | View PDF |
Hermetic Start-Up, Operation, and Maintenance SAFETY DO NOT VENT refrigerant relief valves within a buikting. Outlet from rupture disc or relief valve must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE 15 (American National Standards Institute/American Society of Heating, Refrigeration, and Air Conditioning Engineers). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. PROVIDE adequate ventilation in accordance with ANSI/ASHRAE 15, especially for enclosed and low overhead spaces. Inhalation of high concentrations of vapor is hamlfill and may cause heart irregularities, nnconsciousness, or death. Misuse can be fatal. Vapor is heavier than air and rednces the amonnt of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous. DO NOT USE OXYGEN to purge lines or to pressurize a chiller for any purpose. Oxygen gas reacts violently with oil, grease, and other COlnlllOn substances. NEVER EXCEED specified test pressures, VERIFY the allowable test pressure by checking the instruction literature and the design pressures on the equipment nameplate. USE air for leak testing. Use only refrigerant Instructions CONSIDERATIONS Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage to equipment and property or injury to personnel. Be sure you understand and follow the procedures and safety precautions contained in the chiller instructions as well as those listed in this guide. DO NOT nitrogen. 19X RV Centrifugal Liquid Chillers with PIC III Controls 50/60 Hz HFC-134a or dry soap and water. If liqnid refrigerant enters the eyes, IMMEDIATELY FLUSH EYES with water and consult a physician. NEVER APPLY an open flame or live steam to a refrigerant cylinder. Dangerous over pressure can result. When it is necessary to heat refrigerant, use only warm (110 F D3 C]) water. DO NOT REUSE disposable (nonreturnable) cylinders or attempt to refill them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, evacuate remaining gas pressure, loosen the collar and unscrew and discard the valve stem. DO NOT INCINERATE. CHECK THE REFRIGERANT TYPE before adding refrigerant to the chiller. The introdnction of the wrong refrigerant can cause damage or malfunction to this chiller. Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE 15 (latest edition). Contact Carrier for timber information on use of this chiller with other refrigerants. DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while chiller is under pressure or while chiller is running. Be sum pressure is at 0 psig C0kPa) before breaking any refrigerant connection. CAREFULLY INSPECT all relief devices, rupture discs, and other relief devices AT LEAST ONCE A YEAR. If chiller operates in a corrosive atmosphere, inspect the devices at morn frequent intervals. DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief device when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is found within the valve body or mechanism. Replace the device. DO NOT install relief devices in series or backwards. USE CARE when working near or in line with a compressed spring. Sudden release of the spring can cause it and objects in its path to act as projectiles. DO NOT VALVE OFF any safety device. BE SURE that all pressure fimctioning before operating relief devices any chiller. are properly installed and THERE IS A RISK OF INJURY OR DEATH by electrocution. High voltage may be present on the motor leads even though the motor is not running. Open the power supply disconnect before touching motor leads or terminals. DO NOT WELD OR FLAMECUT any refrigerant line or vessel until all refrigerant (liquM atM V'al)or) has been removed from chiller. Traces of vapor should be displaced with dry air or nitrogen and the work area should be well ventilated. R@'ixemm in contact _Hth an o!)et_flame prodHc_,s toxic gaxes. DO NOT USE eyebolts entire assembly. or eyebolt DO NOT work on high-voltage electrician. holes to rig chiller sections equipment or the unless yon are a qualified DO NOT WORK ON electrical components, including control panels, switches, starters, or oil heater until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid-state components. LOCK OPEN AND TAG WORK IS INTERRUPTED, before resuming work. AVOID SPILLING eyes. USE SAFETY Manufacturer electrical circuits during servicing. IF confirm that all circuits are deenergized DO NOT STEP on refrigerant lines. Broken lines can whip about and release refrigerant, causing personal injury. DO NOT climb over a chiller. Use platform, catwalk, or staging. Follow safe practices when using ladders. USE MECHANICAL EQUIPMENT (crone, hoist, etc.) to lilt or move inspection covers or other heax.y components. Even if components are light, use mechanical equipment when there is a risk of slipping or losing your balance. BE AWARE that certain automatic start arrangements CAN ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead of the starter, tower fans, or pumps. USE only repair or replacement parts that meet the code requirements of the original equipment. DO NOT VENT OR DRAIN waterboxes containing industrial brines, liquid, gases, or semisolids withont the permission of your process control group. DO NOT LOOSEN waterbox cover bolts until the waterbox has been completely drained. DO NOT LOOSEN a packing gland nut before checking that the nut has a positive thread engagement. PERIODICALLY INSPECT all valves, fittings, and piping for corrosion, rest, leaks, or damage. PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain watec liquid refrigerant on skin or getting it into the GOGGLES. Wash any spills from the skin with reserves the right to discontinue, or change at any time, specifications PC 211 Catalog No. 531-986 Printed in U.S.A. or designs without notice and without incurring obligations. Form 19XRV-1SS Pg 1 4-05 Replaces: New CONTENTS Page SAFETY CONSIDERATIONS ...................... 1 INTRODUCTION .................................. 4 ABBREVIATIONS AND EXPLANATIONS ........ 4,5 CHILLER FAMILIARIZATION .................... 5,6 Chiller Information Nameplate .................... 5 System Components ............................. 5 Cooler ............................................ 5 Condenser ....................................... 5 Motor-Compressor ............................... 5 Control Panel ..................................... 5 Variable Frequency Drive ......................... 5 Storage Vessel (Optional) ........................ 5 REFRIGERATION CYCLE ......................... 7 MOTOR AND LUBRICATING OIL COOLING CYCLE .............................. 7 VFD COOLING CYCLE ............................ 8 LUBRICATION CYCLE .......................... 8,9 Summary ......................................... 8 Details ............................................ 8 Oil Reclaim System ............................... 8 • PRIMARY OIL RECOVERY MODE • SECONDARY OIL RECOVERY METHOD Bearings ......................................... 8 STARTING EQUIPMENT ....................... 9-ll Unit-Mounted VFD ................................ 9 CONTROLS ................................... l 1-49 Definitions ...................................... ll • ANALOG SIGNAL • DISCRETE SIGNAL General .......................................... 11 PIC III System Components ..................... ]] • INTERNATIONAL (;;HILLER VISUAL CONTROLLER (ICVC) • CHILLER CONTROL MODULE (CCM) • OIL HEATER CONTACTOR (lC) • OIL PUMP CONTACTOR (2C) • HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) • CONTROL TRANSFORMERS (TI, T2) • OPTIONAL TRANSFORMER (T3) • SENSORS • FLOW DETECTION ICVC Operation and Menus ...................... 16 • GENERAL • ALARMS AND ALERTS • ICVC MENU ITEMS • BASIC [CVC OPERATIONS (Using the Softkeys) • TO VIEW STATUS • FORCING OPERATIONS • TIME SCHEDULE OPERATION • TO VIEW AND CHANGE SET POINTS • SERVICE OPERATION PIC III System Functions ........................ 34 • CAPACITY CONTROL • ECW CONTROL OPTION • CONTROL POINT DEADBAND • DIFFUSER CONTROL • PROPORTIONAL BANDS AND GAIN • DEMAND LIMITING • CHILLER TIMERS AND STARTS COUNTER • OCCUPANCY SCHEDULE Safety Controls .................................. 36 Shunt Trip (Option) .............................. 36 Default Screen Freeze ........................... 36 Ramp Loading ................................... 39 Capacity Override ............................... 39 Page High Discharge Temperature Control ............ 39 Oil Sump Temperature and Pump Control ....... 39 Oil Cooler ....................................... 39 Remote Start/Stop Controls ..................... 40 Spare Safety and Spare Temperature Inputs ..... 40 Alarm (Trip) Output Contacts .................... 40 Kilowatt Output .................................. 41 Remote Reset of Alarms ......................... 41 Condenser Pump Control ....................... 41 Condenser Freeze Prevention ................... 41 Evaporator Freeze Protection ................... 41 Tower Fan Relay Low and High .................. 41 Auto. Restart After Power Failure ................ 42 WaterlBrine Reset ............................... 42 • RESET TYPE 1: 4 TO 20 mA TEMPERATURE RESET • RESET TYPE 2: REMOTE TEMPERATURE RESET • RESET TYPE 3 Surge Prevention Algorithm ..................... 42 Surge Protection ................................ 43 Head Pressure Reference Output ................ 44 Lead/Lag Control ................................ 44 • COMMON POINT SENSOR USAGE AND INSTALLATION • CHILLER COMMUNICATION WIRING • LEAD/LAG OPERATION • FAULTED CHILLER OPERATION • LOAD BALANCING • AUTO. RESTART AFTER POWER FAILURE Ice Build Control ................................ 46 • ICE BUILD INITIATION • START-UP/RECYCLE OPERATION • TEMPERATURE CONTROL DURING ICE BUILD • TERMINATION OF ICE BUILD • RETURN TO NON-ICE BUILD OPERATIONS Attach to Network Device Control ............... 47 • ATTACHING TO OTHER CCN MODULES Service Operation ............................... 48 • TO ACCESS THE SERVICE SCREENS • TO LOG OUT OF NETWORK DEVICE • TIME BROADCAST ENABLE • HOLIDAY SCHEDULING • DAYLIGHT SAVING TIME CONFIGURATION START-U P/SH UTDOWN/R ECYCLE SEQUENCE ................................ 50-52 Local Start-Up ................................... 50 Shutdown Sequence ............................ 51 Automatic Soft Stop Amps Threshold ........... 51 Chilled Water Recycle Mode ..................... 51 Safety Shutdown ................................ 52 BEFORE INITIAL START-UP .................. 52-67 Job Data Required .............................. 52 Equipment Required ............................ 52 Using the Optional Storage Tank and Pumpout System ......................... 52 Remove Shipping Packaging .................... 52 Open Oil Circuit Valves .......................... 52 Oil Charge ....................................... 52 Tighten All Gasketed Joints and Guide Vane Shaft Packing ..................... 52 Check Chiller Tightness ......................... 53 Refrigerant Tracer ............................... 53 Leak Test Chiller ................................ 55 Standing Vacuum Test ........................... 55 Chiller Dehydration .............................. 58 Inspect Water Piping ............................ 58 Check Optional Pumpout Compressor Water Piping .................................. 58 CONTENTS(cont) Page Check Relief Valves ............................. 58 Identify the VFD ................................. 58 Input Power Wiring .............................. 59 Checking the Installation ........................ 59 Inspect Wiring ................................... 60 Ground Fault Troubleshooting .................. 60 Carrier Comfort Network Interface ............... 60 Power Up the Controls and Check the Oil Heater .......................... 61 • SOFTWARE VERSION Software Configuration ......................... 61 Input the Design Set Points ..................... 61 Input the Local Occupied Schedule (OCCPC01S) .................................. 61 Input Service Configurations .................... 61 • PASSWORD • INPUT TIME AND DATE • CHANGE ICVC CONFIGURATION IF NECESSARY • TO CHANGE THE PASSWORD • TO CHANGE THE ICVC DISPLAY FROM ENGLISH TO METRIC UNITS • CHANGE LANGUAGE • MODIFY CONTROLLER IDENTIFICATION IF NECESSARY • INPUT EQUIPMENT SERVICE PARAMETERS IF NECESSARY • VERIFY VFD CONFIGURATION AND CHANGE PARAMETERS IF NECESSARY • VFD CHILLER FIELD SET UP AND VERIFICATION • CONFIGURE DIFFUSER CONTROL IF NECESSARY • MODIFY EQUIPMENT CONFIGURATION IF NECESSARY Perform a Control Test .......................... 64 • PRESSURE TRANSDUCER CALIBRATION Check Optional Pumpout System Controls and Compressor ..................... 65 High Altitude Locations ......................... 65 Charge Refrigerant Into Chiller .................. 65 • CHILLER EQUALIZATION WITHOUT A PUMPOUT UNIT • CHILLER EQUALIZATION WITH PUMPOUT UNIT • TRIMMING REFRIGERANT CHARGE INITIAL START-UP ............................. 67,68 Preparation ..................................... 67 Check Motor Rotation ........................... 67 Check Oil Pressure and Compressor Stop ...... 67 To Prevent Accidental Start-Up .................. 67 Check Chiller Operating Condition .............. 68 Instruct the Customer Operator ................. 68 • COOLER-CONDENSER • OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM • MOTOR COMPRESSOR ASSEMBLY • MOTOR COMPRESSOR LUBRICATION SYSTEM • CONTROL SYSTEM • AUXILIARY EQUIPMENT • DESCRIBE CHILLER CYCLES • REVIEW MAINTENANCE • SAFETY DEVICES AND PROCEDURES • CHECK OPERATOR KNOWLEDGE • REVIEW THE START-UR OPERATION, AND MAINTENANCE MANUAL Page OPERATING INSTRUCTIONS ................. 68-70 Operator Duties ................................. 68 Prepare the Chiller for Start-Up ................. 68 To Start the Chiller .............................. 68 Check the Running System ..................... 68 To Stop the Chiller .............................. 69 After Limited Shutdown ......................... 69 Preparation for Extended Shutdown ............ 69 After Extended Shutdown ....................... 69 Cold Weather Operation ......................... 69 Manual Guide Vane Operation ................... 69 Refrigeration Log ............................... 69 PUMPOUT AND REFRIGERANT TRANSFER PROCEDURES ............................. 71-74 Preparation ..................................... 71 Operating the Optional Pumpout Unit ........... 71 • TO READ REFRIGERANT PRESSURES • POSITIVE PRESSURE CHILLERS WITH STORAGE TANKS • CHILLERS WITH ISOLATION VALVES • DISTILLING THE REFRIGERANT GENERAL MAINTENANCE .................... 74,75 Refrigerant Properties .......................... 74 Adding Refrigerant .............................. 74 Removing Refrigerant ........................... 74 Adjusting the Refrigerant Charge ............... 74 Refrigerant Leak Testing ........................ 74 Leak Rate ....................................... 74 Test After Service, Repair, or Major Leak ........ 74 • TESTING WITH REFRIGERANT TRACER • TESTING WITHOUT REFRIGERANT TRACER • TO PRESSURIZE WITH DRY NITROGEN Repair the Leak, Retest, and Apply Standing Vacuum Test ........................ 75 Checking Guide Vane Linkage .................. 75 Trim Refrigerant Charge ......................... 75 WEEKLY MAINTENANCE ........................ 75 Check the Lubrication System .................. 75 SCHEDULED MAINTENANCE ................ 75-78 Service Ontime .................................. 75 Inspect the Control Panel ....................... 76 Check Safety and Operating Controls Monthly ....................................... 76 Changing Oil Filter .............................. 76 Oil Specification ................................ 76 Oil Changes ..................................... 76 • TO CHANGE THE OIL Refrigerant Filter ................................ 76 Oil Reclaim Filter ................................ 76 VFD Refrigerant Strainer ........................ 77 Inspect Refrigerant Float System ............... 77 Inspect Relief Valves and Piping ................ 77 Compressor Bearing and Gear Maintenance .................................. 77 Inspect the Heat Exchanger Tubes and Flow Devices ............................. 77 • COOLER AND OPTIONAL FLOW DEVICES • CONDENSER AND OPTIONAL FLOW DEVICES Water Leaks ..................................... 77 Water Treatment ................................. 78 Inspect the VFD ................................. 78 Recalibrate Pressure Transducers .............. 78 CONTENTS (cont) Optional Pumpout System Maintenance ......... • OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE • OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS Ordering Replacement Chiller Parts ............. TROUBLESHOOTING GUIDE Overview ........................................ Checking Checking • • • • ................ Page 78 78 79-I 26 79 Display Messages ..................... Temperature Sensors ................. 79 79 RESISTANCE CHECK VOLTAGE DROP CHECK SENSOR ACCURACY DUAL TEMPERATURE SENSORS Checking Pressure Transducers ................. 79 • COOLER CONDENSER PRESSURE TRANSDUCER AND OPTIONAL WATERSIDE FLOW DEVICE CALIBRATION • TRANSDUCER REPLACEMENT Control Algorithms Checkout Procedure ........ 80 Control Test ..................................... Control Modules ................................. • • 81 97 RED LED (Labeled as STAT) GREEN LED (Labeled as COM) Notes on Module Operation ..................... 97 Chiller Control Module (CCM) ................... 97 • INPUTS • OUTPUTS Replacing Defective Processor Modules ........ 98 • INSTALLATION Gateway Status LEDs ........................... 99 • DRIVE STATUS INDICATOR • MS STATUS INDICATOR • NET A STATUS INDICATOR • NET B STATUS INDICATOR Physical Data ................................... 100 APPENDIX -- 19XRV LIQUlFLO TM 2 ICVC PARAMETER INDEX ...................... 127-135 INDEX .......................................... 136 INITIAL START-UP CHECKLIST FOR 19XRV HERMETIC CENTRIFUGAL LIQUID CHILLER .................... CL-I to CL-12 INTRODUCTION Prior to initial start-up of the 19XRV unit, those involved in the stall-up, operation, and maintenance should be thoroughly familiar with these instructions and other necessary job data. This book is outlined to fmnili;uize those involved in the stmt-up, operation and maintenance of the unit with the control system before performing stmt-up procedures. Procedures in this manual ;ue arranged in the sequence required for proper chiller start-up and operation. This unit uses a microprocessor control system. Do not shol_t or jumper between terminations on circuit bo;uds or modules; control or board failure may result. Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dissipate body electrostatic charge before working inside control centel: Use extreme c;ue when handling tools near bo;uds and when connecting or disconnecting terminal plugs. Circuit boards can easily be &_maged. Always hold boards by the edges and avoid touching components and connections. This equipment uses, and can radiate, radio frequency energy. If not installed and used in accor&mce with the instruction manu;fl, it may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Pall 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the usel: at his own expense, will be required to take whatever measures may be required to correct the interference. Always store and transport replacement in anti-static shipping bag. ABBREVIATIONS or defective boards AND EXPLANATIONS Frequently used abbreviations in this manual include: CCM -- Chiller Control Module CCN CCW CW ECDW ECW EMS HGBP I/O ICVC LCD LCDW LCW LED OLTA PIC III RLA SCR Sl TXV VFD --------------------- Carrier Comfort Network Counterclockwise Clockwise Entering Condenser Water Entering Chilled Water Energy Management System Het Gas Bypass Input/Output International Chiller Visual Controller Liquid Crystal Display Leaving Condenser Water Leaving Chilled Water Light-Emitting Diode Overload Trip Amps Product Integrated Controls III Rated Load Amps Silicon Controlled Rectifier International System of Units Thermostatic Expansion Valve Variable Frequency Drive Words printed in all capital lettel_ or in italics may be viewed on the International Chiller Visual Controller (ICVC) (e.g., LOCAL, CCN, ALARM, etc.). W_rds printed in both all capital letters and italics can also be viewed on the ICVC and are parmneters (e.g., CONTROL MODE, COMPRESSOR START RELAY, ICE BUILD OPTION, etc.) with associated values (e.g., modes, temperatures, percentages, pressures, on, off. etc.). W_rds printed in all capital lettel_ and in a box represent softkeys on the ICVC control panel (e.g., _, _, [INCREASE[, _, etc.). Control Panel -- The control panel is the user interface for controlling the chiller It regulates the chiller's capacity as lequiled to maintain proper leaving chilled water temperature. The control panel: FactolT-installed additional components tue refen_ed to as options in this manual; factou-supplied but field-installed additional components are referred to as accessories. The chiller software pall number located on the back of the ICVC. CHILLER unit is • FAMILIARIZATION (Fig. 1 and 2) Chiller Information nameplate panel. of the 19XRV is located Nameplate • • • -- The information on the right side of the chiller control • • System Components -- The components include the cooler and condenser heat exchangers in separate vessels, compressor-motor, lubrication package, control panel, and motor sttutel: All connections fiom pressure vessels have external threads to enable each component to be plessure tested with a thleaded pipe cap during factory assembly. • • Variable Frequency Drive (VFD) -- The VFD allows for the proper st_ut and disconnect of electrical energy for Cooler- This vessel (also known as the evaporator) is located underneath the compressol: The cooler is maintained at lower temperature/pressme so evaporating refrigerant can remove heat fiom water flowing through its internal tubes. Condenser--The temperature/pressure through its internal refrigerant. the compressor-motor, Vessel (Optional)--There are 2 sizes of storage vessels available. The vessels have double relief valves, a magnetically-coupled dial-type refrigerant level gage, a one-inch FPT drain valve, and a l/2-in, male flare vapor connection for the pumpout unit. NOTE: If a storage vessel is not used at the jobsite, factoryinstalled isolation valves on the chiller may be used to isolate the chiller charge in either the cooler or condenser. An optional pumpout system is used to transfer refrigerant from vessel to vessel. Motor-Compressor- This component mainttfins system temperature and pressure differences and moves the heat-carrying refrigerant from the cooler to the condenser 19XRV -- Cooler Size 10-12 (Frame 15-17 (Frame 20-22 (Frame 30-32 (Frame 35-37 (Frame 40-42 (Frame 45-47 (Frame 50-52 (Frame 5A (Frame 5 5B (Frame 5 50 (Frame 5 Condenser 10-12 15-17 20-22 30-32 35-37 40-42 45-47 50-52 55-57 60-62 65-67 70-72 1 XR) 1 XR) 2 XR) 3 XR) 3 XR) 4 XR) 4 XR) 5 XR) XR) XR) XR) 51 473 DG 64 - Special Order Indicator - -- Standard S -- Special Order Motor Code 62 63 64 52 55-57 (Frame 5 XR) 5F (Frame 5 XR) 5G (Frame 5 XR) 5H (Frame 5 XR) 60-62 (Frame 6 XR) 65-67 (Frame 6 XR) 70-72 (Frame 7 XR) 1 1 2 3 3 4 4 5 5 6 6 7 Voltage Code Volts-Phase-Hertz 380-3-60 416-3-60 460-3-60 400-3-50 Motor BD BE BF BG BH BJ XR / XR) XR) XR) XR) XR) XR) XR) XR) XR) XR) Code Indicates ----- Motor Efficiency Code H -- High Efficiency S -- Standard Efficiency Size (F .... (Frame (Frame (Frame (Frame (Frame (Frame (Frame (Frame (Frame (Frame (Frame Compressor (First Digit / High Efficiency Hermetic Centrifugal Liquid Chiller with Variable Frequency Drive Unit-Mounted 52 oil pump, oil heater, and control panel. Storage condenser operates at a higher than the cooler and has water flowing tubes in order to remove heat fi_)m the 19XRV registers cooler, condenser, and lubricating system pressures shows chiller operating condition and alarm shutdown conditions records the total chiller operating hours sequences chiller start, stop, and recycle under microprocessor control displays status of motor starter provides access to other CCN (Carrier Comfort Network) devices and energy management systems Languages pre-installed at factory include: English, Chinese, Japanese, and Korean. International language translator (ILT) is available for conversion of extended ASCII characters. Compressor Frame Size) _ *Second digit will be a letter (example 4G3) on units equipped with split ring diffuser. MODELNUMBERNOMENCLATURE 27 99 Q 59843 Year of Manufacture SERIAL Place of Manufacture NUMBER Fig. 1 -- 19XRV BREAKDOWN Identification Code CD CE CL CM ON CP CQ OR DB DC DD DE DF DG DH DJ DK LB LC LD LE LF LG LH FRONT VIEW 5 LEGEND 6 1 2 3 4 5 6 7 8 --------- 10 11 12 13 14 15 16 17 --------- Guide Vane Actuator Suction Elbow International Chiller Visual Control (ICVC) Chiller Identification Nameplate Cooler, Auto Reset Relief Valve Cooler Pressure Transducer Condenser In/Out Temperature Thermistors Condenser Waterflow Device (Optional ICVC Inputs available) Cooler Waterflow Device (Optional ICVC Inputs available) Cooler In/Out Temperature Thermistors Liquid Line Service Valve Typical Flange Connection Oil Level Sight Glasses Refrigerant Oil Cooler (Hidden) Oil Drain Charging Valve (Hidden) Power Panel Compressor Motor Housing 18 19 20 21 22 23 24 25 26 27 28 29 3O ------------------ Condenser Auto. Reset Relief Valves VFD Circuit Breaker VFD Meter Package (Optional) Unit-Mounted VFD Motor Sight Glass Cooler Waterbox Cover ASME Nameplate (One Hidden) Typical Waterbox Drain Port Condenser Waterbox Cover Refrigerant Moisture/Flow Indicator Refrigerant Filter/Drier Liquid Line Isolation Valve (Optional) Linear Float Valve Chamber Vessel Take-Apart Connector Discharge Isolation Valve (Optional) Refrigerant Charging Valve Condenser Pressure Transducer (Hidden) 9 -- 144 13 10 REAR VIEW 19 2O 21 22 18 23 32 29 24 27 26 31 Fig. 2 --Typical LEGEND 31 32 33 34 19XRV Components REFRIGERATION CYCLE The compressor continuously draws refrigerant vapor from the cooler at a rate set by the amount of guide vane opening or compressor speed. As the compressor suction reduces the pressure in the coolel: the remaining refrigerant boils at a fairly low temperature (typically 38 to 42 F [3 to 6 C]). Tile energy required for boiling is obtained from the water flowing through the cooler tubes. With heat energy removed, the water becomes cold enough to use in tin air conditioning circuit or for process liquid cooling. After taking heat from the water, the compressed. Compression adds still more refrigerant is quite wmm (typic_flly 98 to when it is discharged t]om the compressor refrigerant vapor is heat energy, and the 102 F [37 to 40 C]) into the condensel: Relatively cool (typically 65 to 90 F [18 to 32 C]) water flowing into the condenser tubes removes heat from the refrigerant and the vapor condenses to liquid. The liquid refi'igerant passes through orifices into the FLASC (Flash Subcooler) chamber (Fig. 3). Since the FLASC chamber is at a lower plessure, part of the liquid refrigerant flashes to vapol: thereby cooling the lemaining liquid. The FLASC vapor is recondensed on the tubes which are cooled by entering condenser watel: The liquid drains into a float chamber between the FLASC chamber and cooler Here a float v_dve forms a liquid seal to keep FLASC chamber vapor from entering the coolel: When liquid refrigerant passes through the vMve, some of it flashes to vapor in the reduced pressure on the cooler side. In flashing, it removes heat from the remaining liquid. The refrigerant is now at a temperature and plessure at which the cycle began. MOTOR AND LUBRICATING COOLING CYCLE OIL The motor and the lubricating oil are cooled by liquid refrigerant taken from the bottom of the condenser vessel (Fig. 3). Refrigerant flow is maintained by the pressure differential that exists due to compressor operation. After the refrigerant flows past an isolation valve, tin in-line filtel: and a sight glass/moisture indicatol: the flow is split between the motor cooling and oil cooling systems. Flow to the motor cooling system passes through an orifice and into the motor. Once past the orifice, the refrigerant is directed over the motor by a spray nozzle. The refrigerant collects in the bottom of the motor casing and is then drained back into the cooler through the motor refrigerant di'ain line. An orifice (in the motor shell) maintains a higher pressure in the motor shell than in the coolel: The motor is protected by a temperature sensor imbedded in the stator windings. An increase in motor winding temperature past the motor override set point overrides the temperatme capacity control to hold, and if the motor temperature rises 10 ° F (5.5 ° C) above this set point, closes the inlet guide vanes. If the temperature rises above the safety limit, the compressor shuts down. Refrigerant that flows to the oil cooling system is regulated by thermostatic expansion valves (TXVs). The TXVs regulate flow into the oil/lefrigerant plate and fralne-type heat exchanger (the oil cooler in Fig. 3). The expansion valve bulbs control oil temperature to the bemings. The refrigerant leaving the oil cooler heat exchanger returns to the chiller coolel: FLASC CHAMBER CONDENSER Ii WATER FLOATVAWE. CHAMBER VALVE (OPTION) DRIER DIFFUSER VANE MOISTURE/ FLOW INDICATOR MOTOR ORIFICEFITTING REFRIGERANT LIQUID VFD' COOLING ISOLATION VALVE REFRIGERANT VAPOR THERMOSTATIC EXPANSION VALVE _ EFRIGERANT LIQUID/VAPOR F_ OIL (TXV) UNIT MOUNTED VFD (VARIABLE FREQUENCY DRIVE) HEAT EXCHANGER CHILLED WATER COOLER ISOLATION VALVE (OPTION) SOLENOID Fig. 3 -- Refrigerant Motor Cooling and Oil Cooling Cycles VFD COOLING CYCLE The unit-mounted variable frequency drive (VFD) is cooled in a manner similar to the motor and lubricating oil cooling cycle (Fig. 3). If equipped with a unit-mounted VFD, the refrigerant line that feeds the motor cooling and oil cooler also feeds the heat exchanger on the unit-mounted VFD. Refrigerant is metered through a thermostatic expansion valve (TXV). To maintain proper operating temperature in the VFD, the TXV bulb is mounted to the heat exchanger to regulate the flow of refdgerant. The refdgerant leaving the heat exchanger returns to the coolel: LUBRICATION CYCLE Summary -- The oil pump, oil filtel; and oil cooler make up a package located p_utially in the transmission casing of the compressor-motor assembly. The oil is pumped into a filter assembly to remove foreign particles and is then forced into an oil cooler heat exchanger where the oil is cooled to proper operational temperatures. After the oil cooler, part of the flow is directed to the gems and the high speed shaft bearings; the remaining flow is directed to the motor shaft bearings. Oil drains into the transmission oil sump to complete the cycle (Fig. 4). Details -- Oil is charged into the lubrication system through a hand valve. Two sight glasses in the oil reservoir permit oil level observation. Normal oil level is between the middle of the upper sight glass and the top of the lower sight glass when the compressor is shut down. The oil level should be visible in at least one of the 2 sight glasses during operation. Oil sump temperature is displayed on the ICVC (International Chiller Visual Controller) default screen. During compressor operation, the oil sump temperature ranges between 125 and 150 F (52 and 66 C). The oil pump suction is fed from the oil reservoil: An oil pressure relief valve maintains 18 to 30 psid (124 to 207 kPad) differential pressure in the system at the pump discharge. The normal oil pressme on compressors equipped with rolling element bearings is between 18 and 40 psid (124 and 276 kPad). This diffelential pressure can be read directly from the [CVC default scleen. The oil pump discharges oil to the oil filter assembly. This filter can be closed to permit removal of the filter without dnfining the entire oil system (see Maintenance sections, pages 75 to 78, for details). The oil is then piped to the oil cooler heat exchangel: The oil cooler uses refrigerant from the condenser as the coolant. The refrigerant cools the oil to a temperature between 120 and 140 F (49 and 60 C). As the oil leaves the oil cooler, it passes the oil pressure transducer and the thermal bulb for the refrigerant expansion vNve on the oil cooler The oil is then divided. Pro1 of the oil flows to the thrust bearing, %rward pinion bearing, and gear spray. The rest of the oil lubricates the motor shaft bearings and the rear pinion beming. The oil temperature is measured in the bearing housing as it leaves the thrust and forwaN journal bearings. The outer bearing race temperature is measured on compressors with rolling element bemings. The oil then drains into the oil reservoir at the base of the compmssol: The PIC III (Product Integrated Control III) measures the temperature of the oil in the sump and maintNns the temperature during shutdown (see Oil Sump Temperature and Pump Control section, page 39). This temperature is mad on the ICVC default screen. Dudng chiller stmt-up, the PIC Ill energizes the oil pump and provides 45 seconds of pro-lubrication to the be_uings after pressure is verified before starting the compressor During shutdown, the oil pump will mn for 60 seconds to postlubricate after the compressor shuts down. The oil pump can also be energized for testing purposes during a Control Test. Ramp loading can slow the rate of guide vane opening to minimize oil foaming at st_ut-up. If the guide vanes open quickly, the sudden drop in suction pressure can cause any refrigerant in the oil to flash. The resulting oil foaln cannot be pumped efficiently; therefore, oil pressure falls off and lubrication is pool: If oil pressure falls below 15 psid (103 kPad) differential, the PIC III will shut down the compressol: If the controls me subject to a power failure that lasts more than 3 hours, the oil pump will be energized periodically when the power is restored. This helps to eliminate lefrigerant that has migrated to the oil sump during the power failure. The controls energize the pump for 30 seconds every 30 minutes until the chiller is started. Oil Reclaim System -- The oil reclaim system returns oil lost from the compressor housing back to the oil reservoir by recovering the oil from 2 meas on the chillel: The guide vane housing is the primary area of recovery. Oil is also recovered by skimming it from the operating refrigerant level in the cooler vessel. PRIMARY OIL RECOVERY MODE -- Oil is normally recovered through the guide vane housing on the chillel: This is possible because oil is normally entrained with refrigerant in the chillel: As the compressor pulls the refrigerant up from the cooler into the guide vane housing to be compressed, the oil norm_dly drops out at this point and falls to the bottom of the guide vane housing where it accumulates. Using discharge gas pressure to power an eductol: the oil is diawn from the housing and is dischmged into the oil reservoil: SECONDARY OIL RECOVERY METHOD -- The secon&try method of oil recovery is significant under light load conditions, when the refrigerant going up to the compressor suction does not have enough velocity to bring oil along. Under these conditions, oil collects in a greater concentration at the top level of the refrigerant in the coolel: This oil and refrigerant mixture is skimmed from the side of the cooler and is then drawn up to the guide vane housing. There is a filter in this line. Because the guide vane housing pressure is much lower than the cooler pressure, the refrigerant boils off. leaving the oil behind to be collected by the primary oil recovery method. Bearings -- The 19XRV compressor assemblies include four radi_d bemings and four thrust bearings. The low speed shaft assembly is suppolled by two journal bemings located between the motor rotor and the bull gem: The bearing closer to the rotor includes a babbitted thrust face which opposes the normal axial forces which tend to pull the assembly towmds the transmission. The beming closer to the bull gear includes a smaller babbitted thrust face, designed to handle counterthmst forces. For most 19XRV compressors the high speed shaft assembly is supported by two journal bearings located at the transmission end and mid-span, behind the labyrinth seal. The transmission side of the midspan bearing _dso contains a tilting shoe type thrust beming which opposes the main axkd forces tending to pull the impeller towards the suction end. The impeller side face of the midspan bearing includes a babbitted thrust face, designed to handle counterthrust forces. For 19XRV Frmne 3 compressors built since mid-2001, the high speed shaft assembly has been redesigned to utilize rolling element bearings (radial and thrust). Machines employing the rolling element bearings can be expected to have higher oil pressure and thrust beming temperatures than those compressors using the alternate bearing design. REAR MOTOR FWD MOTOR OIL SUPPLY TO FORWARD HIGH SPEED LABYRINTH GAS LINE BEARING I ( MOTOR COOLING LINE ISOLATION VALVE PRESSURE TRANSDUCER OIL PUMP ISOLATION VALVES OIL COOLER OIL HEATER GLASS OILPUMP MOTOR FILTER ISOLATION VALVE SIGHT GLASS t Fig. 4- STARTING LINE Lubrication System EQUIPMENT All 19XRV units am equipped with a VFD to operate the centrifugal hermetic compressor motoc A power panel controls the oil pump, and various auxiliary equipment. The VFD and power panel m'e the main field wiring interfaces for the contractol: The VFDs are mounted directly on the chillel: Three separate circuit breakers ale inside the st_utel: Circuit breaker CBI is the VFD circuit breaker The disconnect switch on the stmler fiont cover is connected to fills breakel: Circuit breaker CBI supplies power to the VH). The main circuit breaker (CBI) on the front of the starter disconnects the main VFD current only. Power is still energized for the other circuits. Two more circuit breakers inside the VH) must be turned off to disconnect power to the oil pump, PIC III controls, and oil heatel: Circuit breaker CB2 supplies l15-v power to the control panel, oil heater, and portions of the starter controls. Circuit breaker CB3 supplies power at line voltage to the oil pump. Both CB2 and CB3 are wired in pm'allel with CBI so that power is supplied to them if the CBI disconnect is open. Do not touch the power wiring or motor terminals while voltage is present, or serious injury will result. Unit-Mounted VFD -- The 19XRV chiller is equipped with a variable frequency drive motor controller mounted on file condensel: See Fig. 5-7. This VFD is used wifll low voltage motors between 380 and 480 wtc. It reduces the starting current inrush by controlling the voltage and fiequency to the compressor motol: Once the motor has accelerated to minimum speed the PIC IIl modulates the compressor speed and guide vane position to control chilled water temperature. The VFD is further explained in the Controls section and Troubleshooting Guide section, pages 11 and 79. Operational p_uameters and fault codes are displayed relative to the drive. Refer to specific (hive literatme along with troubleshooting sections. The display is _dso the interface for entering specific chiller operational p_u'ametel_. These ptuameters have been preprogrammed at the factory. An adhesive backed label on the inside of the drive has been provided for verification of the specific job paralneters. See Initial St_ut-Up Checklist section for details. [] I OPTIONAL METER PACKAGE II II {t o./o n 11 I . OPTIONAL METER PACKAGE /0o0 o o STANDARD 65 - KILO AMPS INTERRUPT CAPACITY CIRCUIT BREAKER OPTIONAL 100 - KILO AMPS INTERRUPT CAPACITY CIRCUIT BREAKER Fig. 5 -- Variable Frequency Drive (VFD) 3 5 LEGEND 17 14,15 13 12 10,11 9 Fig. 6 -- Variable Frequency Drive Internal 10 1 m 2 3 4 5 ----- 6 7 8 9 10 11 12 13 14 15 16 17 18 19 --------------- Input Inductor Assembly Capacitor Bank Assembly Pre-Charge Resistor Assembly AC Contactor Fuse Block, 30A, 600 v, Class CC, 3-Line Ground Cable Power Module Assembly Power Module Nameplate Terminal Block, 10-Position Line Synch PC Board Assembly Line Synch Board Cover Fuse, Class CC, 600 v, 1 A Fan, 115 v Fuse, Class CC, 600 v, 15 A Fuse, Class CC, 600 v, 4 A Transformer, 3 kVA Control Power Circuit Breaker Circuit Breaker, 600 v Lug, Ground, 2-600 MCM COOLER CHARGING CONTROL PANEL GUIDE VANE ACTUATOR CABLE POWER PANEL CABLE VALVE (HIDDEN) WATER CABLES WATER SEN_ CABLES j COOLER PRESSURE TRANSDUCER CONNECTION cO2?s s'S 2 CABLE / SCHRADER FITTING(HIDDEN) CONDENSER PRESSURE TRANSDUCER CONNECTION CONDENSER 3-WAY SHUTOFF VALVE CONDENSER CHARGING VALVE (HIDDEN) COMPRESSOR DISCHARGE ELBOW JOINTS Fig. 7 -- Chiller Controls and Sensor Locations CONTROLS with auxiliary equipment such as pumps and cooling tower fans to turn them on when required. It continually checks all safeties to prevent any unsafe operating condition. It also regulates the oil heater while the compressor is off and regulates the hot gas bypass valve, if installed. The PIC III controls provide critical protection for the compressor motor and controls the motor stmlel: The PIC III can interface with the Carrier Comfort Network (CCN) if desired. It can communicate with other PIC I, PIC II or PIC III equipped chillers and other CCN devices. Definitions ANALOG SIGNAL -- An analog signal varies in proportion to the monitored source. It quantifies values between operating limits. (Example: A temperature sensor is an analog device because its resistance changes in proportion to the temperature, generating many values.) DISCRETE SIGNAL --A discreW signal is a 2-position representation of the value of a monitored source. (Example: A switch produces a discrete signal indicating whether a value is above or below a set point or boun&uy by generating an on/off. high/low, or open/closed signed.) The PIC [II consists of 3 modules housed inside 3 major components. The component names and corresponding control voltages are listed below (also see Table 1): • General -- The 19XRV herlnetic centrifuged liquid chiller contains a microprocessor-based control panel that monitors and controls all operations of the chiller (see Fig. 7). The microprocessor control system matches the cooling capacity of the chiller to the cooling load while providing state-of-the-art chiller protection. The system controls cooling load within the set point plus the deadband by sensing the leaving chilled water or brine temperature and regulating the inlet guide vane via a mechanically linked actuator motol: The guide vane is a variable flow pre-whifl assembly that controls the refrigeration effect in the cooler by regulating the amount of refrigerant vapor flow into the compressor. An increase in guide vane opening increases capacity. A decrease in guide vane opening decreases capacity. The microprocessor-based control center protects the chiller by monitoring the digital and analog inputs and executing capacity overrides or safety shutdowns, if required. PIC III System Components -- • • control panel -- all extra low-voltage wiring (24 v or less) power panel -- 115 vac control voltage (per job requirement) -- 115 vac power for oil heater and actuators -- up to 480 vac for oil pump power starter cabinet -- chiller power wiring (per job requirement) Table 1 -- Major PIC III Components Panel Locations* PIC III COMPONENT The chiller control system is called the PIC 1II (Product Integrated Control [II). See Table 1. The PIC III controls the operation of the chiller by monitoring all operating conditions. The PIC III can diagnose a problem and let the operator know what the problem is and what to check. It promptly positions the guide vanes to m_fint_fin leaving chilled water temperature. It can interface PANEL LOCATION International Chiller Visual Controller (ICVC) and Display Control Panel Chiller Control Module (CCM) Control Panel Oil Heater Contactor Power Panel (1C) Oil Pump Contactor (2C) Power Panel Hot Gas Bypass Relay (3C) (Optional) Power Panel Power Panel Control Transformers Temperature Sensors Pressure Transducers *See Fig, 5-10. 11 and (T1, T2, T3) See Fig, 7. See Fig, 7. INTERNATIONAL CHILLER VISUAL CONTROLLER (ICVC) -- The ICVC is the "brain" of the PIC HI. This module contains all the operating software needed to control the chillel: The ICVC is mounted to the control panel (Fig. 9) and is the input center for all local chiller set points, schedules, configurable functions, and options. The [CVC has a stop button, an alarm light, four bnttons for logic inputs, and a backlight display. The backlight will automatically turn off after 15 minutes of non-use. The lhnctions of the four buttons or "softkeys" me menu driven and are shown on the display directly above the softkeys. NOTE: Plessing vate the function. backlight any one of the four display without softkey buttons will implementing The [CVC may be identified by viewing the back of the plate on which the display is mounted. (Open the control panel door to view.) Note any of the following distinguishing features in Table 2. Table 2 -- Identification CONTROLLER The viewing angle of the ICVC can be adjusted for optimum viewing. Remove the 2 bolts connecting the control panel to the brackets attached to the coolec Place them in one of the holes to pivot the control panel forw_ud to backward to change the viewing angle. See Fig. 9. To change the contrast of the display, access the adjustment on the back of the ICVC. See Fig. 9. The ICVC features 4 factory progrmnmed languages: ICVC COLOR OF PLATE Metallic Features of the ICVC CEPL No. (hardware) CEPL 130445-02 SOFTWARE OTHER MARKINGS CESR 131350-0X "PIC IIr' Marking on back of green circuit board English (default) Chinese Japanese Kolean MOTOR TEMPERATURE COMPRESSOR OIL DISCHARGE PRESSURE CABLE OIL RECLAIM SIGHT GLASS_ BEARING TEMPERATURE CABLE COMPRESSOR AND DIFFUSER OIL SUMP ACTUATOR CABLE (FRAME 4 & 5 COMPRESSOR ONLY) GUIDE ACTUATOR acti- a softkey COMPRESSOR OIL SUMP CABLE FROM CONTROL PANEL CABLE COMPRESSOR DISCHARGE TEMPERATURE SENSOR CABLE OIL COOLER HIGH PRESSURE SWITCH LOCATION EXPANSION THERMOSTATIC VALVE (TXV) OIL COOLER THERMOSTATIC EXPANSION VALVE (TXV) BULB OIL HEATER TERMINAL BOX Fig. 8 -- 19XRV Compressor Controls and Sensor Locations 12 CHILLER CONTROL MODULE (CCM) -- This module is located in file control panel. Tile CCM provides the input and outputs necessa U to control the chillel: This module monitors refiigerant pressure, entering and leaving water temperatures, and outputs control for the guide vane actuator, oil heaters, and oil pump. The CCM is the connection point for optional demand limit, chilled water reset, remote temperature reset, refi'igerant leak sensor and motor kilowatt output. OIL HEATER CONTACTOR (IC) -- This contactor is located in the power panel (Fig. 10) and operates the heater tit 115 v. It is controlled by the PIC III to maintain oil temperature during chiller shutdown. Refer to the control panel wiring schematic. For this type the sensor cable can be easily disconnected fiom the sensok which is in direct contact with the fluid. Figure 12 shows a typictd temperature sensor for which sensor wells am used, in systems having an ICVC controllel: For this type the sensor cable cannot be separated from the sensor itself, but the sensor can be readily removed from the well without breaking into the fluid boun&u-y. The third type of temperature sensor is a thermistok which is installed either in the motor windings or tit the thrust bearing within the compressol: Both of these have redun&mt sensors such flint if one fails, the other can be connected external to the machine. See NiNe 3 for a list of stan&trd instrumentation sensors. OIL PUMP CONTACTOR (2C) -- This contactor is located in the power panel. It operates all 380 to 480-v oil pumps. The PIC HI energizes the contactor to turn on the oil pump as necessm-y. HOT GAS BYPASS CONTACTOR RELAY (3C) (Optional) -- This relay, located in the power panel, controls the opening of the hot gas bypass valve. The PIC III energizes the relay during low load, high lill conditions. CONTROL TRANSFORMERS (TI, T2)- These transformers convert incoming control voltage to 24 vac power for the 3 power panel contactor relays, CCM, and ICVC. The PIC [II control determines refrigerant temperature in the condenser and evaporator fi_m pressure in those vessels, mad fi_m the conesponding pressure transducers. See Fig. 13. The pressure values are converted to the equivtdent saturation temperatures for R-134a refrigerant. When the chiller is running, if the computed value for EVAPORATOR REFRIG TEMP is greater than, or within 0.6° F (0.33 ° C) of the LEAVING CHILLED WATER temperature, its value is displayed as 0.6° F (0.33° C) below LEAVING CHILLED WATER tempe> atum. When the chiller is running, if the computed value for CONDENSER REFRIG TEMP is less than, or within 1.2° F (0.67 ° C) of the LEAVING COND WATER temperature, its value is displayed as 1.2° F (0.67 ° C) above LEAVING COND WATER temperature. OPTIONAL TRANSFORMER (T3)--This transformer provides control power to DataPort'rWDataLINK TM modules. SENSORS -- Throe types of temperature sensors am used: Figure 11 shows a typictd temperature sensor with which sensor wells am not used, in systems having a ICVC controllel: Table 3 -- Standard Instrumentation TYPE LOCATION Temperature Pressure Angular Position Pressure Temperature Switch Switch Sensors MONITORED REMARKS Entering chilled water Cooler inlet nozzle Leaving chilled water Cooler outlet nozzle Entering condenser water Condenser inlet nozzle Leaving condenser water Evaporator saturation Condenser outlet nozzle Sensor well on bottom of evaporator Compressor discharge Compressor volute Oil sump Compressor oil sump Compressor thrust bearing Redundant sensor provided Motor winding Redundant sensor provided Evaporator Condenser Relief valve tee Relief valve tee Oil sump Compressor Oil sump discharge Oil pump discharge line Diffuser (Compressor internal) oil sump Only in machines equipped with split ring diffusers Entering chilled water (Optional) Cooler inlet nozzle Leaving chilled water (Optional) Cooler outlet nozzle Entering condenser water (Optional) Condenser inlet nozzle Leaving condenser water (Optional) Condenser outlet nozzle Guide vane actuator Potentiometer High condenser Compressor (discharge) pressure Oil pump motor winding temperature inside of actuator volute, wired into the starter control circuit Wired into the oil pump control circuit 13 CARRIER CONTROL COMFORT CONTROL NETWORK (CCN) INTERFACE PANEL CIRCUIT POWER BREAKERS DISPLAY (FRONT VIEW) r fo_m_, INTERNATIONAL CHILLER VISUAL CONTROLLER (ICVC) FRONT VIEW 0000 OPTIONAL DATAPORT/DATAU >CIRCUIT BREAKERS HUMIDITY SENSOR @GG ( ( ............. SURGE/HGBP _÷ CHILLER MODULE PARAMETER LABEL CONTROL (CCM) CONTROL PANEL INTERNAL VIEW CONTROL PANEL SIDE VIEW CONTROl. REMOVABLE BOLT DIFFUSER SCHEDULE SETTINGS HINGE (FRAME 5 COMPRESSOR ONLY) INTERNATIONAL VISUAL OONTRO_ER REAR VIEW CONTRAST CHILLER Fig. 9- T1-24 FOR VAC POWER HOT GAS OIL PUMP OIL HEATER IDENTIFICATION NAMEPLATE Control Panel TRANSFORMER BYPASS CONTACTOR, RELAY, AND T2-24 VAC POWER TRANSFORMER FOR ICVC AND CCM CONTACTOR T3-20 VAC POWER TRANSFORMER FOR DATAPORT/DATALINK (OPTIONAL) 3C HOT GAS OIL HEATER CONDUIT CONTROL PANEL POWER CONDUIT Fig. 10 -- Power Panel 14 OPTIONAL BYPASS HOT CONDUIT GAS BYPASS NK L,_ 3 00in _-_-_ _i6,35" mm)(762 mm) ............ _-J _---- , .- RECEPTACLE NPT Fig. 11 -- Control than the EVAP REFRIG TRIPPOINT. (If the unit is in Pumpdown or Lockout mode, conditions (1) and (2) ;ue not required to establish flow.) On the condenser side, positive detemrination of flow is made if the following conditions are tree: (1) the CONDENSER PRESSURE is less than 165 psig (1139 kPa), and (2) CONDENSER PRESSURE is less than the configured COND PRESS OVERRIDE threshold by more than 5 psi (34.5 kPa). In addition, if the waterside differentkd pressure measurement option is enabled, the watel_ide pressure differentials (cooler and condenser) must exceed their respective configured cutout thresholds. CONNECTOR WATERPROOF SEAL Sensors (Temperature) A No Flow determination is made on the evaporator side if (1) the EVAP SATURATION TEMP reads lower than 1° F (0.6 ° C) below the EVAP REFRIG TRIPPOINT. or (2) EVAP REFRIG TEMP (determined from the Evaporator Pressure sensor) is less than the EVAP REFRIG TRIPPOINT and the EVAPORATOR APPROACH exceeds the configured EVAP APPROACH ALERT threshold. On the condenser side, a No Flow determination is also made if the CONDENSER APPROACH exceeds the configured COND APPROACH ALERT threshold and either (1) CONDENSER PRESSURE exceeds 165 psig (1139 kPa) or (2) CONDENSER PRESSURE exceeds the configured COND PRESS OVERRIDE threshold by more than 5 psi (34.5 kPa). In addition, if the water side differential pressure measurement option is enabled, a differential below the configured EVAP or COND FLOW DELTA P CUTOUT v_due is sufficient to establish No Flow in either heat exchangel: (90MM) 3.6" TUBE LENGTH \EATSHR,NK\ 2-CONDUCTOR CABLE Fig. 12 -- Temperature Sensor Used With Thermal Well 1/4" SAE FEMALE INTEGRAL FLARE SCHRADER WITH DEFLATOR If No Flow (for either cooler or condenser) has been determined, and subsequently conditions change such that neither conditions for Flow nor No Flow are _dl satisfied, the determination will remain No Flow. In the standard [CVC setup, waterside differential pressure indication is disabled by default. The displays for CHILLED WATER DELTA P and CONDENSER WATER DELTA P in the HEAT_EX screen will show "*****". In order to enable the option and display a value, change FLOW DELTA P DISPLAY to ENABLE in the SETUPI scleen. Pairs of pressure transducers may be connected to the CCM at temrinals J3 13-24 in place of the standard resistors and jumpers to determine water-side pressme differentials as in the standard ICVC configuration. (NOTE: If the FLOW DELTA P DISPLAY is enabled but the standard CCM connection is retained, a differential value of approximately 28.5 psi (197 kPa) will _flways be displayed.) Fig. 13 -- Control Sensors (Pressure Transducers, Typical) A Refrigerant Saturation Temperature sensor (thermistor) is located in the base of the evaporator, sensing refrigerant temperature directly. Evaporator and condenser water side differential pressure transducers _u'e not stan&trd and are not required. The [CVC software uses the evaporator saturation refrigerant temperature in place of diffferential pressure flow detection to provide evaporator fieeze protection. If watel_ide diffelential plessure transducel_ me used, flow is detected fi_m differential pressure between sensors (pressure transducers) located in water inlet and outlet nozzles, for earl1 heat exchangeE The thresholds for flow determination (EVAP FLOW DELTA P CUTOUT. COND FLOW DELTA P CUTOUT) are configured in the SETUPI screen. If the measured differential is less than the corresponding cutout value for 5 seconds, the determination is that flow is absent. If no flow is detected after W_TER FLOW VERIFY TIME (configured in the SETUPI screen) after the pump is commanded to start by the PIC, a shutdown will result, and the corresponding loss-offlow _dmm (alarm state 229 or 230) will be declared. If the measured differenti_d exceeds the Flow Delta P cutout value, flow is considered to be present. Approach temperatures are shown in the HEAT_EX scleen. EVAPORATOR APPROACH is defined as LEAVING CHILLED WATER temperature minus EVAP SATURATION TEMP (from the temperature sensor). CONDENSER APPROACH is defined as CONDENSER REFRIG TEMP (derived from condenser pressure) minus LEAVING CONDENSER WATER temperature. When the chiller is running, the displayed v_due for either approach will not be less than 0.2 ° F (0.1 o C). If either approach value exceeds the value configured in the SETUPI screen, the corresponding Approach Alert message will be entered into the Alert Histo U table. FLOW DETECTIONFlow detection for the evaporator and condenser is a required condition for stm-t-up and used in the freeze protection safety. Flow and no flow conditions are detected from a combination of several measurements. The usage of waterside diffelential pressme measmements is not standard or required. Alternatively. norm_dly open flow switches may be used for flow indication. In this case, inst_dl an evaporator side flow switch in parallel with a 4.3k ohm resistor between CCM terminals J3 17-18, replacing the jumpel: See page 114. For a condenser side flow switch do the same between CCM terminals J3 23-24. If this type of flow switch circuit is used, it is important to perform a zero point calibration (with the flow switch open). Positive detemrination of flow on the evaporator side is made if the following conditions ale true: (1) the EVAP SATURATION TEMP reads higher than 1° F (0.6 ° C) above the EVAP REFRIG TRIPPOINT. and (2) EVAP REFRIG TEMP (determined from the Evaporator Pressure sensor) is greater 15 ICVC Operation and Menus (Fig. 14-20) PRIMARY STATUS COMPRESSOR ON TIME GENERAL STATUS MESSAGE • The [CVC display automatically reverts to the default screen after 15 minutes if no softkey activity takes place and if the chiller is not in the pump down mode (Fig. 14). • If a screen other than the default screen is displayed on the ICVC, the name of that screen is in the top line (Fig. 15). • The ICVC may be set to display either English or SI units. Use the ICVC configuration screen (accessed from the Service menu) to change the units. See the Service Operation section, page 48. NOTE: The date format on the default screen is MM-DD-YY for English units and DD-MM-YY (ILLUMINATED WHEN POWER ON) • BLINKS CONTINUOUSLY ON FOR AN ALARM • BLINKS ONCE TO CONFIRM A STOP mmmm / • HOLD FOR ONE SECOND TO STOP / SOFT KEYS for SI metric units. EACH KEY'S FUNCTION IS DEFINED BY THE MENU DESCRIPTION • Local Operation -- In LOCAL mode the PIC III accepts commands fiom the ICVC only and uses the local time occupancy schedule to determine chiller start and stop times. The PIC III can be placed in the local operating mode by pressing the LOCAL softkey. When RUN STATUS is READY. the chiller will attempt to start up. • CCN Opelation --In CCN mode the PIC III accepts input from any CCN interface or module (with the proper authority) as well as from the local ICVC. The PIC III uses the CCN time occupancy schedule to determine start and stop times. The PIC III can be placed in the local operating mode by pressing the CCN softkey. When RUN STATUS is READY. the chiller will attempt to start up. • OFF -- The control is in OFF mode when neither the LOCAL nor CCN softkey cue is highlighted. Pressing the STOP key or an alarm will place the control in this mode. The PIC III control must be in this mode for certain operations, such as performing a Control Test or accessing VFD Configuration parameters. ALARMS AND ALERTS -- An altu'm shuts down the compressor An alert does not shut down the compressol: but it notifies the operator that an unusual condition has occurred. An alarm (*) or alert (!) is indicated on the STATUS screens on the far right field of the ICVC display screen. ON MENU Fig. 14-- • • the operator to view the chiller conditions at the time of alarm. The STATUS tables will show the updated information. Once soft- key), the default ICVC screen will return to normal operation. be ICVC MENU ITEMS -- To perform any of the operations described below, the PIC III must be powered up and have successfully completed its self test. The self test takes place automatically, after power-up. tures: _, LSETPOINT], [SERVICE]. ISCHEDULEI,[SE OINTI, or _ To view or change parmneters use the _ within any of these and [PREVIOUS[ softkeys to scroll down to the desired item or table. Use the softkey to select that item. The softkey choices that appear next depend on the selected table or menu. The softkey choices and their functions are described below. and [SERVICEI. • viewed: menu structures, softkey to view the list of menu struc[SCHEDULE], The SCHEDULE menu allows viewing and modification of the local and CCN time schedules and Ice Build time schedules. The SETPOINT menu allows set point adjustments, such as the entering chilled water and leaving chilled water set points. The SERVICE menu can be used to view or modify information on the Alarm History, Control Test, Control Algorithm Status, Equipment Configuration, VFD Configuration data, Equipment Service, Time and Date, Attach to Network Device, Log Out of Network Device, and ICVC Configuration screens. For more information on the menu structures, refer to Fig. 17. Press the softkey that corresponds to the menu structure to An alarm condition must be rectified before a RESET will be processed. However. an _dert will clear automatically as soon as the associated condition is rectified. Press the _ SCREEN NAME Fig. 15 -- ICVC Service Screen When an alarm is detected, the ICVC default screen will fieeze (stop up&_ting) at the time of alarm. The freeze enables the _ Screen mmm • (by pressing MENU LINE LINE ABOVE ICVC Default DEVICE NAME Alarms are indicated when the control center _darm light (!) flashes. The primtuy alarm message is displayed on the default screen. An additional, secondary message and troubleshooting information are sent to the ALARM HISTORY table. all aimms have been cleared DATE BASIC ICVC OPERATIONS (Using the Softkeys) -- To perform any of the operations described below, the PIC III must be powered up and have successfully completed its self test. The STATUS menu allows viewing and limited calibration or modification of control points and sensors, relays and contacts, and the options board. 16 Press _ to leave tile selected decision or field without saving any changes. _, INCREASE DECREASE QUIT ENTER Press _ or IPREVIOUSI to highlight status table. The list of tables is: • • J D Press _ save changes. to leave tile selected INCREASE l DECREASE decision QUIT MAINSTAT-Overall chiller status STARTUP-Status required to perform start-up of chiller COMPRESS -- Status of sensors related to the compressor HEAT_EX -- Status of sensors related to the heat exchangers POWER -- Status of motor input power VFD_STAT-Status of motor starter ICVC PSWD -- Service menu password fDrcing access screen • or field and ENTER • • • • J 71QD the desired _, NEXT PREVIOUS SELECT ENTER ,_ Press _ to scroll tile cursor bar down in order to highlight a point or to view more points below the current screen. Press _ _, NEXT PREVIOUS to view the desired point status table. SELECT t NEXT PREVIOUS SELECT ENTER ,_ D Press [PREVIOUS[ to scroll tile cursor bar up in order to highlight a point or to view points above tile current screen. NEXT PREVIOUS On the point status table, press _ or [PREVIOUS] until tile desired point is displayed L SELECT NEXT PREVIOUS on tile screen. SELECT ENTER ,J Q7! Q Press _ to view tile next screen level (highlighted with the cursor bar), or to override (if allowable) the highlighted point value. _, NEXT PREVIOUS SELECT 7] Q Press _ / ) EXIT D to return to tile previous screen level. mmmm NEXT PREV,OUS SELECT EX,T ) Press ]INCREASE] or IDECREASEI lighted point value. INCREASE DECREASE QUIT to change tile high- Fig. 16 -- Example of Status Screen FORCING ENTER N] 7! OPERATIONS TD Force (manually I. From any [PREVIOUS] l NEXT ovelTide) a Value or Status point status PREVIOUS TO VIEW STATUS (Fig. 16) -- The status table shows the actual v_flue of overall chiller status such as CONTROL MODE, RUN STATUS, AUTO CHILLED WATER RESET. and REMOTE RESET SENSOR. I. On tile menu screen, press _ point status tables. STATUS SCHEDULE to view tile list of SETPOINT SERVICE press _ SELECT EXIT QD Press _ to select tile highlighted NEXT / screen, PREVIOUS SELECT v_due. EXIT 7] J 17 or to highlight the desired value. ) DEFAULT SCREEN I CCN][ LOCAL __IStart Chiller In CCN Control Start Chiller in Local Control ] [ II RESET MENU ] (SOFTKEYS) / Clear Alarms _ T [ STATUS ][SCHEDULE] I Access Main Menu Es l I SERVICE List the Status Tables • • • • • • • ] -'_ ...... (ENTER A 4-DIGIT PASSWORD) Display The Setpoint MAINSTAT STARTUP COMPRESS HEAT EX POWER VFD STAT ICV(_PSWD • • • • • ]1 PREVIOUS] Select a Modification NEXT ][ Base Demand Limit LCW Setpoint ECW Setpoint Ice Build Setpoint Tower Fan High Setpcint [ SELECT ] [ EXIT Select the Setpoint [ N_ ][_-EVIOUS] [ SELECT ] E EXIT [INCREASE I[DECREASEII ] [ ENTER Point PREVIOUS] Table List the Schedules Select a Statue Table NEXT (VALUES SHOWN AT FACTORY DEFAULT) List the Service Tables ! [ SELECT I [ EXIT ] ENTER ] Modify the Setpoint QUIT ] [ Modify a Discrete Point _,_ START ON ] STOP OFF ] [ RELEASE Modify an Analog Point INCREASE] IDECREASE] Modify Control ENABLE 11 [ RELEASE ] E ENTER Options DISABLE ] [ QUIT I [ ENTER • OCCPC01S - LOCAL TIME SCHEDULE • OCCPC02S - ICE BUILD TIME SCHEDULE • OCCPC03S - CCN TIME SCHEDULE Select a Schedule 1[ NEXT ][ PREVIOUS] I SELECT ] [ EXIT 1 2 3 4 5 6 7 8 Override Select a Time Period/Override NEX T SELECT e@ ][ I ENTER ][ EXIT ] EXIT ] (ANALOG VALUES) EXIT ] (DISCRETE VALUES) aDay [ DISABLE ]1 ENTER 1[ ALARM HISTORY ALERT HISTORY CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION VFD CONFIG DATA EQUIPMENT SERVICE TIME AND DATE ATTACH TO NETWORK DEVICE LOG OUT OF DEVICE ICVC CONFIGURATION [ NEXT ]I PREVIOUS][ SELECT I _ SEE FIGURE 18 Fig. 17 -- 19XRV Chiller Display Menu Structure 18 (ICVC) SERVICE TABLE [ NEXT ][ PREVIOUS] ALARM [ SELECT ] [ EXIT I ALERT HISTORY ! HISTORY Alert History (The table holds up to 25 alarms and alerts with the most recent alarm at the top of the screen,) Display Alarm History (The table holds up to 25 alarms and alerts with the most recent alarm at the top of the screen.) CONTROL TEST CONTROL ALGORITHM List the Control Tests STATUS List the Control Algorithm Status Tables • CAPACITY (Capacity Control) • OVERRIDE (Override Status) • LL MAINT (Lead Lag Status) • VFD HIST (VFD Alarm History) • LOADSHED • CURALARM (Current Alarm State) • WSMDEFME (Water System Manager Control Status) • OCCDEFCM (Time Schedule Status) Select a Table [NEXT ]EPREVIOUS]I ][ EXIT ][PREVIOus]E SELECT I OCCPC01S OCCPC02S OCCPC03S EQUIPMENT SELECT][ EXIT (Time Schedule Status) • • • • Data Select Table NEXT I[PREVIOus]E NEXT ] / I a Test CCM Thermistors CCM Pressure Transducers Pumps Discrete Outputs IGV and SRD Actuator Head Pressure Output Diffuser Actuator Pumpdown/Lockout Terminate Lockout Guide Vane Calibration I I OCCDEFM SELECT Select ] • • • • • • • • • • CONFIGURATION ] [ EXIT ] (Local Status) (CCN, ICE BUILD Status) (CCN Status) List the Equipment CAPACITY (Capacity Control Algorithm) OVERRIDE (Override Status) LLMAINT (LEADLAG Status) WSMDEFM2 (Water System Manager Control Status) Maintenance Configuration Table Data Tables • • • • • • NET OPT BRODEF OCCDEFCS HOLIDAYS CONSUME RUNTIME Select a Table E NEXT ][ PREVIOUS][ SELECT ] [ EXIT ] Select a Parameter [ NEXT ][PREVIOUS] Modify a Parameter [INCREASE] [DECREASE] [ ENABLE CONTINUED ON NEXT PAGE ][ DISABLE ] ] EXIT [ QUIT ] ENTER ](ANALOG [ QUIT ] ENTER I (DISCRETE SELECT (USE ENTER) TO SCROLL DOWN Fig. 18 -- 19XRV Service Menu Structure 19 I [ SELECT VALUES) VALUES) ] SERVICE MENU CONTINUED FROM PREVIOUS PAGE EQUIPMENT VFD CONFIG DATA SERVICE --_ (ENTER A 4-DIGIT PASSWORD) (VALUES SHOWN AT FACTORY DEFAULT) Service Tables: • OPTIONS • SETUPt • SETUP2 • LEADLAG • RAMP DEM • TEMP CTL Service Tables: • VFD (STARTER) • VFD CONF CONFIG PASSWORD Select a Service Table [NEXT ] I PREVIouslI SELECTI E Select a Service Table Parameter [NEXT ] I PREVIOUS] I SELECT I E vice Table Parameter I_AS_] I QUIT [ ENABLE ] E DISABLE ] I ] [ QUIT EXIT l EXit ] ENTER ] E ENTER ] (ANALOG VALUES) ](DISCRETE VALUES) TIME AND DATE A'I-rACH TO NETWORK DEVICE List NetJrk • • • • • • Display Time and Date Table: • To Modify -- Current Time -- Current Date Local Device Device Device Device Device [INCREASE I [DECREASE] I ENTER [ YES I [ NO ] I ENTER Devices • • • • 1 2 3 4 5 Device Device Device Attach 6 7 8 to any Device --- Day of Week Holiday Today ] I EXIT I(ANALOG ] I EXIT I(DISCRETE VALUE) VALUE) Select a Device [ NEXT ]1 PREVIOUS I[ Modify Device Address II SELECT _ ATTACH ] [ [INCREASE]IDECREASE]I ENTER I E EXIT • Use to attach ICVC to another CCN network or device/ • Attach to "LOCAL" to enter this machine • To upload new tables ] / LOG OUT OF DEVICE Default Screen [ CON ]1 LOCAL ICVC Configuration Table I I[ RESET II MENU l ICVC CONFIGURATION [ LEGEND CCN ICVC PIC III VFD ----- • To Modify ------ ENTER ] [ EXIT ICVC CCN Address • To View -Baud Rate (Do not change this) English (U.S. IMP.) or S.I. Metric Units Password LID Language Carrier Comfort Network International Chiller Visual Controller Product Integrated Control III Variable Frequency Drive Fig. 18 -- 19XR Service Menu Structure (cont) 20 ] ICVC Software Version (last 2 digits of part number indicate software version) For Discrete Poin_ -- Press _ lect the desired state. or _ OCCPC03S to se- -- CCN Time Schedule NEXT START l STOP RELEASE ENTER _, Poin_ -Press IINCREASEI to select tile desiled value. INCREASE DECREASE RELEASE ENTER SELECT EXIT ) Press _ For Analog [DECREASE] PREVIOUS or _, to view the desired time schedule. NEXT PREVIOUS SELECT EXIT D ) Press _ or IPREVIOUSI to highlight period or oveMde to change. 3. Press _ to legister the new value. INCREASE DECREASE RELEASE [, On tile point status table press _ to highlight the desired value. l NE_ NEXT Press _ OVERRIDE. _, NEXT PREVIOUS SELECT EX. to access tile highlighted NEXT PREVIOUS SELECT INCREASE DECREASE RELEASE DD PREVIOUS SELECT PERIOD EXIT ENTER DECREASE ENTER EXIT t IDISABLEI to eliminate ENABLED,SA_LEENTER EXIT ) On tile Menu screen, press ]SCHEDULE]. SETPOINT SERVICE D 2. Pless _ schedule. .J days from the D (Fig. 19) SCHEDULE .J to select days in the day-of-week ,] TIME SCHEDULE STATUS or up to 4 hours. [ENABLE] fields. Press period. value is indicated by fla. hmg next to the point I. INCREASE b. Press Force Indication -A forced "SUPVSR," "SERVC," or BEST value on the STATUS table. OPERATION to access tile highlighted EXIT Pless [RELEASE] to remove tile force and return tile point to the PIC III's automatic control. t .) value. D 3. EXIT Press IINCREASE I or [DECREASE] to change tile time values. OVERRIDE values are in one-hour ) _ Pless _ SELECT or IPREVIOUS] increments, 2. PREVIOUS the desired ENTER NOTE: When forcing or changing metric values, it is necessalT to hold down the sollkey for a few seconds in order to see a value change, especially on kilopascal values. To Remove a Force I. .) or [PREVIOUS] to highlight tile desired Fig. 19 -- Example of Time Schedule Operation Screen OCCPC01S -- LOCAL Time Schedule OCCPC02S -- ICE BUILD Time Schedule 21 Press _ to register tile values and to move holi- 2. There are 5 set points on this screen: BASE DEMAND LIMIT. LCW SETPOINT (leaving chilled water set point), ECW SETPOINT (entering chilled water set point), ICE BUILD SETPOINT, and TOWER FAN HIGH SETPOINT. Only one of the chilled water set points can be active at one time. The set point that is active is determined from the SERVICE menu. See the Service Operation section, page 48. The ice build (ICE BUILD) function is _flso activated and configured from the SERVICE menu. 3. Press _ or [PREVIOUS] set point entry. zontally (left to right) within a pedod. ENABLE DISABLE ENTER EXIT 7] Press _ to leave the PERIOD NEXT PREVIOUS or OVERRIDE. SELECT EXIT DQQ NEXT PREVIOUS to highlight SELECT the desired EXIT ) Either return to Step 4 to select another PERIOD or OVERRIDE, or press _ again to leave the current time schedule screen and save the changes. 4. t NEXT PREVIOUS SELECT EXIT Press _ to modify the highlighted set point. ,J t PREV,OUS SELECT EX,T ) D 10. The Holiday Designation (HOLIDEF table) may be found in the Service Operation section, page 48. The month, day, and duration for the holiday must be assigned. The Broadcast function in the BRODEF table also must be enabled for holiday periods to function. TO VIEW AND CHANGE SET POINTS (Fig. 20) I. To view the SETPOINT table, fiom the MENU pless ISETPOINT 1. STATUS SCHEDULE SETPOINT SERVICE 5. Press IINCREASEI ed set point value. _, INCREASE or IDECREASEI DECREASE QUIT to change the select- ) ENTER screen 6. Press _ vious screen. ) D _, INCREASE to save the changes and return to the pre- DECREASE QUIT ENTER ) SERVICE OPERATIONTo view the menu-&iven programs available for Service Operation, see Service Operation section, page 48. For examples of ICVC display screens, see Table 4. mmmm Fig. 20 -- Example of Set Point Screen 22 Table 4 -- ICVC Display Data I examples. IMPORTANT: The following 1. Only 12 lines of information notes apply to all 6. Reference Point Names shown in these tables in all capital letters can be read by CCN and BS software. Of these capitalized names, those preceded by a dagger can also be changed (that is, written to) by the CCN, BS, and the ICVC. Capitalized Reference Point Names preceded by two asterisks can be changed only from the ICVC. Reference Point Names in lower case type can be viewed by CCN or BS only by viewing the whole table. Table 4 appear on the chiller display screen at any one time. Press the _ or I PREVlOUS I softkey to highlight a point or to view items below or above the current screen. Double click the _ the IPREVIOUS] 7. Alarms and Alerts: An asterisk in the far right field of a ICVC status screen indicates that the chiller is in an alarm state; an exclamation point in the far right field of the ICVC screen indicates an alert state. The asterisk (or exclamation point) indicates that the value on that line has exceeded (or is approaching) a limit. For more information on alarms and alerts, see the Alarms and Alerts section, page 16. LEGEND softkey to page forward; press softkey twice to page back. 2. To access the information shown in Examples 10 through enter a 4-digit password after pressing the _ 22, softkey. If no softkeys are pressed for 15 minutes, the ICVC automatically logs off (to prevent unrestricted access to PIC III controls) and reverts to the default screen. If this happens, re-enter the pass- word to access the tables shown in Examples 10 through 22. CCN CHW CHWR CHWS CT ECW HGBP ICVC LOW LRA mA P PIC III SS T VFD WSM 3. Terms in the Description column of these tables are listed as they appear on the chiller display screen. 4. The ICVC may be configured in English or Metric (Sl) units using the ICVC CONFIGURATION screen. See the Service Operation section, page 48, for instructions on making this change. 5. The items in the Reference Point Name column do not appear on the chiller display screen. They are data or variable names used in CCN or Building Supervisor (BS) software. They are listed in these tables as a convenience to the operator if it is necessary to cross reference CCN/BS documentation or use CCN/BS programs. For more information, see the 19XRV CCN literature. EXAMPLE ------------------ Carrier Comfort Network Chilled Water Chilled Water Return Chilled Water Supply Current Transformer Entering Chilled Water Hot Gas Bypass International Chiller Visual Controller Leaving Chilled Water Locked Rotor Amps Milliamps Pressure Product Integrated Controls III Solid State Temperature Variable Frequency Drive Water System Manager 1 -- CHILLER DISPLAY DEFAULT SCREEN The following data is displayed in the Default screen. DESCRIPTION (PRIMARY MESSAGE) (SECONDARY MESSAGE) (DATE AND TIME) Compressor Ontime Entering Chilled Water Leaving Chilled Water Evaporator Temperature Entering Condenser Water Leaving Condenser Water Condenser Temperature Oil Pressure Oil Sump Temp Average Line Current STATUS UNITS 0-500000.0 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 0-420 40-245 0-999 0-1 0-1 0-1 HOURS DEG F DEG F DEG F DEG F DEG F DEG F PSI DEG F % REFERENCE POINT NAME (ALARM HISTORY) C HRS ECW LCW ERT ECDW LCDW CRT OILPD OILT AMPS_% CCN LOCAL RESET NOTE: The last three entries are used to indicate operating mode to the PIC Ill. These values may be forced by the ICVC only. 23 DISPLAY CHW IN CHW OUT EVAP REF CDW IN CDW OUT COND REF OILPRESS OIL TEMP AMPS% Table 4 -- ICVC Display Data (cont) EXAMPLE 2 -- MAINTSTAT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MEffO_. 2. Press _ (IMAINSTAT] will be highlighted). 3. Press _. DESCRIPTION STATUS Control Mode Run Status Start Inhibit Timer Occupied'?. System Alert/Alarm *Chiller Start/Stop *Remote Start Contact Temperature Reset *Control Point Chilled Water Temp *Active Demand Limit Percent Line Current Percent Line Kilowatts Auto Demand Limit Input Auto Chilled Water Reset Remote Reset Sensor Total Compressor Starts Starts in 12 Hours Compressor Ontime *Service Ontime Ice Build Contact Emergency Stop NOTE 2 NOTE 3 0-15 0/1 0-2 0/1 0/1 -30-30 10-120 -40-245 40-100 0-999 0-999 4-20 4-20 -40-245 0-99999 0-8 0-500000.0 0-32767 UNITS POINT NOTE 2 NOTE 3 rain NO/YES NOTE 4 STOP/START OPEN/CLOSE DEG F DEG F DEG F % % % mA mA DEG F MODE STATUS T START O-CO SYS_ALM CHIL_S_S REMCON T RESET LCW STPT CHW_TMP DEM LIM LNAMPS P LINEKW P AUTODEM AUTORES R RESET c starts S-TARTS c hrs S-HRS lEE CON EMSTOP HOURS HOURS OPEN/CLOSE ENABLE/EMSTOP 0-1 0/1 NOTES: 1. Numbers in parenthesis indicate the equivalent CCN index for BEST programming or BACnet TM Translator use. 2. Off (0), Local (1), CCN (2), Reset (3) 3. Timeout (0), Ready (1), Recycle (2), Startup (3), Running (4), Demand (5), Ramping (6), Tripout (7), Override (6), Tripout (9), Ctl Test (10), Lockout (11), Pumpdown (12), Prestart (13) 4. Normal, Alert, Alarm 5. All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN devices. EXAMPLE 3 -- STARTUP DISPLAY SCREEN To access this display from the IOVC default screen: 1. Press _MENO]. 2. Press ISTATOS]. 3. Scroll down to highlight [STARTUP]. 4. Press _SEEECT]. DESCRIPTION Actual Guide Vane Pos **Chilled Water Pump Chilled Water Flow **Condenser Water Pump Condenser Water Flow Oil Pump Relay **Oil Pump Delta P Oil Sump Temp VFD Start Start Complete Stop Complete Target VFD Speed **Tower Fan Relay Low **Tower Fan Relay High Spare Safety Input Shunt Trip Relay STATUS UNITS 0-100 0-1 0-1 0-1 0-1 0-1 -6.7-200 -6,7-200 0-1 0-1 0-1 0,0-100.0 0-1 0-1 0-1 0-1 % OFF/ON NO/YES OFF/ON NO/YES OFF/ON ^PSI DEG F NO/YES FALSE/TRUE FALSE/TRUE % OFF/ON OFF/ON ALARM/NORMAL OFF/ON POINT GV POS CH_/P CHW FLOW CDP CDW_FLOW OILR OILPD OILT VFDSTART START OK STOP ()K VFD_OUT TFR_LOW TFR HIGH SAFETY TRIPR NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the ICVC only. 24 Table 4 -- ICVC Display Data (cont) EXAMPLE 4 -- COMPRESS DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press _MEN0]. 2. Press [S_TOS]. 3. Scroll down to highlight ICOMPRESS I . 4. Press [SELECt. DESCRIPTION STATUS 0.0-100.0 0.0-100.0 0-100 0-100 0-100 -40-245 -6.7-200 -40-245 -40-245 -40-245 -40-245 -40-245 0/1 0-100 0-5 Actual VFD Speed **Target VFD Speed Actual Guide Vane Pos Guide Vane Delta **Target Guide Vane Pos Oil Sump Temp **Oil Pump Delta P Comp Discharge Temp Comp Thrust Brg Temp Comp Motor Winding Temp Spare Temperature 1 Spare Temperature 2 Oil Heater Relay Diffuser Actuator Surge Protection Counts NOTE: All variables with CAPITAL LETTER for the ICVC only. UNITS POINT % % % % % DEG F ^PSI DEG F DEG F DEG F DEG F DEG F OFF/ON % VFD_ACT VFD OUT GV POS GV DELTA GV TRG OIL_OILPD CMPD MTRB MTRW SPARE_T1 SPARE T2 OILHE/_T DIFF ACT SPC )oint names are available for CCN read operation. Those shown with (**) shall support write operations EXAMPLE 5 -- HEAT_EX DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press _MEN0]. 2. Press [STATOS]. 3. Scroll down to highlight _. 4. Press [SEL_T]. DESCRIPTION **Chilled Water Delta P Entering Chilled Water Leaving Chilled Water Chilled Water Delta T Chill Water Pulldown/Min Evaporator Refrig Temp **Evaporator Pressure Evaporator Approach **Condenser Water Delta P Entering Condenser Water Leaving Condenser Water Condenser Refrig Temp **Condenser Pressure Condenser Approach VFD Coolant Flow Hot Gas Bypass Relay Surge / HGBP Active? Active Delta P Active Delta T Surge / HGBP Delta T Head Pressure Reference Evaporator Saturation Temp STATUS UNITS PSI DEG F DEG F ^F ^F DEG F PSI ^F PSI DEG F DEG F DEG F PSI ^F % OFF/ON NO/YES PSI ^F ^F % DEG F -6.7-420 -40-245 -40-245 -40-245 -20-20 -40-245 -6.7-420 0-99 -6.7-420 -40-245 -40-245 -40-245 -6.7-420 0-99 0.0-I00.0 0/I 0/I 0-200 0-200 0-200 0-100 -40-245 POINT CHWPD ECW LCW CHW_DT CHW_PULL ERT ERP EVAP APP CDWPD ECDW LCDW CRT CRP COND APP VFD F-OUT HGB-YPASS SHG ACT dp a dt a dt c hpr EST NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the ICVC only. 2.5 Table 4 -- ICVC Display Data (cont) EXAMPLE 6 -- POWER DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MEN0]. 2. Press ISTATOS]. 3. Scroll down to highlight _P6WER]. 4. Press _SE_CT]. DESCRIPTION Percent Line Current Average Line Current Percent Line Voltage Average Line Voltage Line Power Factor Line Kilowatts Percent Line Kilowatts Percent Load Current Average Load Current Motor Power Factor Motor Kilowatts Percent Motor Kilowatts Motor Kilowatt Hours Demand Kilowatts Line Current Phf(R) Line Current Ph2 (S) Line Current Ph3 (T) Load Current Phl (U) Load Current Ph2 (V) Load Current Ph3 (W) Line Voltage Phl (RS) Line Voltage Ph2 (ST) Line Voltage Ph3 (TR) Ground Fault Current Line Frequency Rectifier Overload Inverter Overload Motor Overload Line Current Imbalance Motor Current Imbalance Line Voltage Imbalance Line Active Current Line Reactive Current Line Active Voltage Line Reactive Voltage DC Bus Voltage Reference DC Bus Voltage Flux Current Torque Current Inverter Temperature Rectifier Temperature VFD Enclosure Temp VFD Cold Plate Temp Humidity Sensor Input Relative Humidity VFD Coolant Flow Actual VFD Speed STATUS UNITS % AMPS % VOLTS 0.0-999.0 0.0-99999.0 0.0-999.0 0.0-99999.0 0.00-2.00 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.00-2.00 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0.0-999.0 0.0-99.0 0.0-100.0 0.0-100.0 0.0-100.0 0.0-100.0 0.0-100.0 0.0-100.0 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0-99999 0.0-300.0 0.0-300.0 0.0-300.0 0.0-300.0 0.0-5.0 0.0-100.0 0.0-100.0 0.0-100.0 kW % % AMPS kW % kWH kW AMPS AMPS AMPS AMPS AMPS AMPS VOLTS VOLTS VOLTS AMPS HZ % % % % % % AMPS AMPS VOLTS VOLTS VOLTS VOLTS AMPS AMPS DEG F DEG F DEG F DEG F VOLTS % % % NOTES: 1. All variables with CAPITAL LETTER point names are available for CCN read operation. 2. Those shown with (**) shall support write operations for ICVC only. 26 POINT LNAMPS P LNAMPS A LNVOLT -P LNVOLT A LINE_PFLINE KW LIN EK,W P LDAMPS_P LDAMPS A MOTOR PF MOTOR KW MOTORKWP MOTORKWH DEM KW LN A-MPSl LN_AMPS2 LN AMPS3 LD AMPSl LD AMPS2 LD_AMPS3 LN_VOLT1 LN_VOLT2 LN VOLT3 GF-AMPS LINEFREQ RECT OV INV O-V MOTOR OV LN IMB I MT- IMB- I LN IMB V AM-PS_,g,CT AMPS RE VOLT ACT VOLT RE BUS -REF BUS VOLT FLUXAMPS TORQAMPS INV TEMP REC TEMP VFD ENCL CP TEMP H U_]ID SR HUMIDITY VFD FOUT VFD ACT Table 4 -- ICVC Display Data (cont) EXAMPLE 7 -- VFD STAT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MEN0]. 2. Press [S_T0S]. 3. Scroll down to highlight ]VFD STAT]. 4. Press [S_EC_. DESCRIPTION VFD Fault Code Single Cycle Dropout Line Current Imbalance Line Voltage Imbalance Line Phase Reversal High Line Voltage Low Line Voltage High DC Bus Voltage Low DC Bus Voltage Motor Current Imbalance Motor Overload Rectifier Overcurrent Rectifier Overtemp Rectifier Power Fault Inverter Overcurrent Inverter Overtemp Inverter Power Fault Ground Fault Frequency Fault VFD Power On Reset Start Complete Stop Complete Condenser High Pressure Motor Amps Not Sensed Start Acceleration Fault Stop Fault VFD Start Inhibit VFD Checksum Error VFD Comm Fault VFD Fault VFD Gateway Version # VFD Inverter Version # VFD Rectifier Version # STATUS 0-223 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0-255 0-1000 0-1000 UNITS NORMAL/ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL/ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM FALSE/TRUE FALSE/TRUE NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM NORMAL!ALARM POINT VFD FLT CYCLE_I LINEIM I LINEIM V PH REV HI _VOLT LdW VOLT HI DCBUS L(9 DCBUS MO-TIM I MOTOR- OV RECT_C_ RECT OT RECT PU INV O] INV OT INV PU GRIND FLT FREQ#LT VFD POR STAtgT OK STOP OK PRS TRIP NO _,MPS ACCELFLT AMPSTOP STRT INH CHECKSUM VFD COMM VFDFAULT VFG VER INV _/ER RECVER NOTES: 1. All variables with point names written in capital letters are available for CCN Read operation only. (*) Variables support write operations for all CCN Devices. (**) Variables shall support write operations for the ICVC only. 2. This table supports the service tool password disable access. It will only allow forcing with the service tool for a one-time bypass of both the Service menu and the VFD config data table. Exit from the Service menu reverts to normal password operation. EXAMPLE 8 -- ICVC PWD DISPLAY SCREEN To access this display from the IOVC default screen: 1. Press [MEN0]. 2. Press [_AT0S]. 3. Scroll down to highlight [ ICVC 4. Press [_T_T]. PWD]. DESCRIPTION Disable Service Password **Remote Reset Option Reset Alarm? CCN Mode? STATUS UNITS DSABLE/ENABLE DSABLE/ENABLE NO/YES NO/YES 0-1 0-1 0-1 0-1 POINT PSWD DiS RESE]_OPT REMRESET REM CCN NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations for the ICVC only. To Disable Service Password, force that item to a value of "1" using Service Tool. Once this has been done, the Service menu and the VFD Config Data screens can be accessed without a password. This access is cancelled the time the user exits the Service menu/screen. **If the Remote Reset Option is set to a value of "1" at the ICVC, alarms may be reset and CCN mode may be reinstated remotely using Service Tool, Building Supervisor, or ComfortWORKS® controls. EXAMPLE g -- SETPOINT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MEN0]. 2. Press [SETPOINT]. 3. Press [S_E_]. DESCRIPTION Base Demand Limit Control Point LCW Setpoint ECW Setpoint Ice Build Setpoint Tower Fan High Setpoint STATUS 40-100 UNITS % POINT DLM 10-120 15-120 15-60 55-105 DEG DEG DEG DEG Icwsp ecwsp ice sp TFH SP F F F F NOTE: All variables are available for CCN read operation; forcing shall not be supported on setpoint screens. 27 DEFAULT 100 50.0 60.0 40.0 75 Table 4 -- ICVC Display Data (cont) EXAMPLE 10- CAPACITY DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MENO]. 2. Press _. 3. Scroll down to highlight [CONTROL ALGORITHM STATUS[. 4. Press _SELECf]. 5. Scroll down to highlight [CAPACITY]. 6. Press _SELECT]. DESCRIPTION STATUS Entering Chilled Water Leaving Chilled Water Capacity Control Control Point Control Point Error ECW Delta T ECW Reset LCW Reset Total Error + Resets Guide Vane Delta Target Guide Vane Pos Actual Guide Vane Poe Target VFD Speed Actual VFD Speed Demand Limit Inhibit Amps/kW Ramp -40-245 -40-245 UNITS DEC F DEC F POINT ECW LCW 10-120 -99-99 -99-99 -99-99 -99-99 -99-99 -2-2 0-100 0-100 0-100 0-110 0-100 40-100 DEC F ^F ^F ^F ^F ^F % % % % % % % ctrlpt cperr ecwdt ecwres Icwres error gvd GV TRG GV POS VF[3_OUT VFD_ACT DEM INH DMDLIM NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; screen. EXAMPLE 11 -- OVERRIDE forcing shall not be supported on maintenance DISPLAY SCREEN To access this display from the IOVC default screen: 1. Press [MENU]. 2. Press _. 3. Scroll down to highlight ICONTROL ALGORITHM STATUS I. 4. Press ISELECT]. 5. Scroll down to highlight [OVERRIDE[. 6. Press _SELECT]. DESCRIPTION Comp Motor Winding Temp Comp Motor Temp Override Condenser Pressure Cond Press Override Evaporator Refrig Temp Evap Ref Override Temp Comp Discharge Temp Comp Discharge Alert Comp Thrust Brg Temp Comp Thrust Brg Alert Rectifier Temperature Rectifier Temp Override Inverter Temperature Inverter Temp Override Actual Superheat Superheat Required Condenser Refrig Temp STATUS UNITS DEC F DEC F PSI PSI DEC F DEC F DEC F DEC F DEC F DEC F DEC F DEC F DEC F DEC F ^F ^F DEC F -40-245 150-200 0-420 90-180 -40-245 2-45 -40-245 125-200 -40-245 185-185 0-300 125.0-200.0 0-300 125-200 -20-99 6-99 -40-245 NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; screens. 28 POINT MTRW mt over CR-P cp_over ERT ert over CMPD cd alert MTRB tb alert RECT TEMP REC OVER INV TEMP INV OVER SUFTRHEAT SUPR_REQ CRT forcing shall not be supported on maintenance Table 4 -- ICVC Display Data (cont) EXAMPLE 12To access this display from the ICVC default screen: 1. Press _MENO]. 2. Press _. 3. Scroll down to highlight [CONTROL ALGORITHM 4. Press [SELECT]. 5. Scroll down to highlight ILL_MAINT.I 6. Press [S_EC_. DESCRIPTION LL_MAINT DISPLAY SCREEN STATUS]. STATUS UNITS POINT LeadLag Control LEADLAG: Configuration NOTE 1 leadlag Current Mode NOTE 2 Ilmode DSABLE/ENABLE Ioadbal Load Balance Option 0/1 LAG START Time 2-60 MIN lagstart LAG STOP Time 2-60 MIN lagstop Prestart Fault Time 2-30 MIN preflt Pulldown: Delta T/Min x.xx ^F pull dt Satisfied? 0/1 NO/YES pull_sat LEAD CHILLER in Control 0/1 NO/YES leadctrl LAG CHILLER: Mode NOTE 3 lagmode Run Status NOTE 4 lagstat Start/Stop NOTE 5 lag_s_s NO/YES Recovery Start Request 0/1 lag_rec STANDBY CHILLER: Mode NOTE 3 stdmode Run Status NOTE 4 stdstat Std s_s Start/Stop NOTE 5 NO/YES std rec Recovery Start Request 0/1 DEG F SP,_RE_T1 Spare Temperature 1 -40-245 DEG F SPARE_T2 Spare Temperature 2 -40-245 NOTES: 1. DISABLE, LEAD, LAG, STANDBY, INVALID 2. DISABLE, LEAD, LAG, STANDBY, RECOVERY, CONFIG 3. Reset, Off, Local, CCN 4. Timeout, Ready, Recycle, Prestart, Startup, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout, Ctl Test 5. Stop, Start, Retain 6. All variables with CAPITAL LETTER point names are available for CCN read operation; forcing shall not be supported on maintenance screens. EXAMPLE To access this display from the ICVC default screen: 1. Press [MEN0]. 2. Press _. 3. Scroll down to highlight [CONTROL ALGORITHM 4. Press [SELECT]. 5. Scroll down to highlight _VFD HIST]. 6. Press [_TEC_. DESCRIPTION VFD FAULT HISTORY Values at Last Fault: Line Current Phl(R) Line Current Ph2(S) Line Current Ph3(T) Load Current Phl(U) Load Current Ph2(V) Load Current Ph3(W) Line Voltage Phl(RS) Line Voltage Ph2(ST) Line Voltage Ph3(TR) Ground Fault Current Line Frequency Line Power Factor Line Current Imbalance Line Voltage Imbalance Motor Power Factor Motor Current Imbalance Motor Overload Line Active Current Line Reactive Current Line Active Voltage Line Reactive Voltage DC Bus Voltage DC Bus Voltage Reference Flux Current Torque Current Inverter Temperature Rectifier Temperature VFD Enclosure Temp VFD Cold Plate Temp Actual VFD Speed Chiller Fault State VFD Fault Code 13 -- VFD_HIST DISPLAY SCREEN STATUS]. STATUS 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-999.0 0.0-99.0 0.00-2.00 0.0-100.0 0.0-100.0 0.00-2.00 0.0-100.0 0.0-100.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-99999.0 0.0-300.0 0.0-300.0 0.0-300.0 0.0-300.0 0.0-100.0 200-225 200-225 UNITS POINT AMPS AMPS AMPS AMPS AMPS AMPS VOLTS VOLTS VOLTS AMPS Hz LNAMPS1H LNAMPS2H LNAMPS3H LDAMPS1H LDAMPS2H LDAMPS3H LNVOLT1H LNVOLT2H LNVOLT3H GF AMPSH LIN-EFRQH LINE PFH LN_IIV1BIH LN IMBVH MO-TORPFH MT IMBIH MOTOROVH AMPSACTH AMPS REH VOLTA-CTH VOLT REH BUSV-OLTH BUS REFH FLU)(AMPH TORQAMPH INVTEMPH RECTEMPH VFDENCLH CP TEMPH VFD ACTH VFDSTATH VFD_FLTH % % % % AMPS AMPS VOLTS VOLTS VOLTS VOLTS AMPS AMPS DEG F DEG F DEG F DEG F % NOTE: All variables with point names written in capital letters are available for CCN read operation. Forcing shall not be supported on maintenance screens. 29 Table 4 -- ICVC Display Data (cont) EXAMPLE 14 --WSMDEFME DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MENU]. 2. Press _. 3. Scroll down to highlight ICONTROL ALGORITHM STATUS I. 4. Press [SELECT]. 5. Scroll down to highlight [WSMDEFME]. 6. Press [SELECT]. DESCRIPTION WSM Active'?. STATUS 0/1 UNITS NO/YES POINT WSMSTAT Chilled Water Temp Equipment Status Commanded State CHW setpt Reset Value Current CHW Set Point 0.0-99.9 0/1 XXXXXXXX 0.0-25.0 0.0-99.9 DEG F OFF/ON TEXT ^F DEG F CHWTEMP CHWRST CHWRENA CHWRVAL CHWSTPT NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation; screens. EXAMPLE 15-- forcing shall not be supported on maintenance NET OPT DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MENU]. 2. Press _. 3. Scroll down to highlight [EQUIPMENT CONFIGURATION I. 4. Press [_T]. 5. Scroll down to highlight [NET OPT]. 6. Press [SE_CT]. DESCRIPTION Loadshed Function Group Number Demand Limit Decrease Maximum Loadshed Time CCN Occupancy Config: Schedule Number Broadcast Option Alarm Configuration Re-Alarm Time Alarm Routing STATUS UNITS POINT DEFAULT 0-16 0-60 0-480 % MIN Idsgrp Idsdlta maxshed o 2o 6o 3-99 0-1 DSABLE/ENABLE occ num occbrcst 3 DSABLE retime routing 30 10000000 0-1440 xxxxxxxx MIN NOTE: No variables are available for CCN read or write operation. 3O Table 4 -- ICVC Display Data (cont) EXAMPLE 16- VFD CONF DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press rMEN0]. 2. Press _. 3. Scroll down to highlight [VFD CONFIG DATA[. 4. Press FSELECT1. 5. Enter password (4444 Factory Default). 6. Scroll down to highlight [VFD CONF[. 7. Press [SELECT1. DESCRIPTION STATUS UNITS VOLTS Hz NO/YES VOLTS AMPS kW kW AMPS AMPS 346-480 45.0-62.0 0/1 346-480 10-1500 0-7200 0-7200 10-1500 10-1500 1500-3600 0-5600 O/1 0.0-102.0 0.0-102.0 0.0-102.0 0.0-102.0 1-10 1-10 5-40 1-10 5-40 1-10 5-60 5-60 0/1 Motor Nameplate Voltage Compressor 100% Speed Line Freq=60 Hz? (No=50) * Rated Line Voltage * Rated Line Amps * Rated Line Kilowatts * Motor Rated Load KW * Motor Rated Load Amps Motor Nameplate Amps Motor Nameplate RPM Motor Nameplate KW Inverter PWM Frequency (0=4 k Hz, 1=2 k Hz) Skip Frequency 1 Skip Frequency 2 Skip Frequency 3 Skip Frequency Band Line Voltage % Imbalance Line Volt Imbalance Time Line Current % Imbalance Line Current Imbal Time Motor Current % Imbalance Motor Current Imbal Time Increase Ramp Time Decrease Ramp Time Single Cycle Dropout NOTE: Those parameters marked with a * shall not be downloaded EXAMPLE kW Nz Hz Hz Hz % SEC % SEC % SEC SEC SEC DSABLE/ENABLE POINT 460 60.0 YES 46O 2OO 100 100 2OO 100 3456 100 0 102.0 102.0 102.0 0.0 10 10 4O 10 4O 10 3O 3O DSABLE comp 100 line frq vfd volt vfd amps vfd rlkw mot rlkw mot rla motorni motorpm motorkw pwm freq skipfrql skipfrq2 skipfrq3 skipband v unbal v time lineim i lineim t motim i motim t ramp Tnc rampdec cycdrop to the VFD, but shall be used in other calculations 17 -- OPTIONS DEFAULT motornv and algorithms in the ICVC. DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [M_U]. 2. Press _. 3. Scroll down to highlight IEQUIPMENT SERVICE I. 4. Press [SEL_T]. 5. Scroll down to highlight _. 6. Press [_LECT]. DESCRIPTION Auto Restart Option Remote Contacts Option Soft Stop Amps Threshold Surge/Hot Gas Bypass Surge Limit/HGBP Option Select: Surge=0, HGBP=I Min. Load Point (T1,P1) Surge/HGBP Delta T1 Surge/HGBP Delta P1 Full Load Point (T2,P2) Surge/HGBP Delta T2 Surge/HGBP Delta P2 Surge/HGBP Deadband Surge Protection Surge Delta% Amps Surge Time Period Ice Build Control Ice Build Option Ice Build Termination 0=Temp, 1=Contacts, 2=Both Ice Build Recycle Head Pressure Reference Delta P at 0% (4mA) Delta P at 100% (20mA) Minimum Output STATUS 0/1 0/1 40-100 UNITS DSABLE/ENABLE DSABLE/ENABLE % 0/1 POINT astart modes strtstop DEFAULT DSABLE DSABLE 100 srg hgbp 0.5-20 30-170 ^F PSI hgbdtl hgbdpl 1.5 5O 0.5-20 50-170 0.5-3 ^F PSI ^F hgbdt2 hgb dp2 hgb db lO 85 1 5-20 7-10 % MIN surge_a surge t lO 8 0/1 0-2 DSABLE/ENABLE ibopt ibterm DSABLE 0 0/1 DSABLE/ENABLE ibrecyc DSABLE 20-85 20-85 0-100 PSI PSI % HPDPO HPDP100 HPDPMIN% 25 5O 0 NOTE: No variables are available for CCN read or write operation. 3! Table 4 -- ICVC Display Data (cont) EXAMPLE 18 -- SETUP1 DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press _MENU_. 2. Press _. 3. Scroll down to highlight [EQUIPMENT SERVICE I . 4. Press _SELECTI. 5. Scroll down to highlight ISEf0P1]. 6. Press [SE_]. DESCRIPTION STATUS UNITS Comp Motor Temp Override Cond Press Override Rectifier Temp Override Inverter Temp Override Comp Discharge Alert Comp Thrust Brg Alert 150-200 90-165 155-170 155-170 125-200 165-185 DEG PSI DEG DEG DEG DEG Chilled Medium Chilled Water Deadband Evap Refrig Trippoint Refrig Override Delta T Evap Approach Alert Cond Approach Alert Condenser Freeze Point 0/1 0.5-2.0 0.0-40.0 2.0-5.0 0.5-15 0.5-15 -20 - 35 Flow Delta P Display Evap Flow Delta P Cutout Cond Flow Delta P Cutout Water Flow Verify Time Oil Press Verify Time Recycle Control Restart Delta T Shutdown Delta T F POINT DEFAULT MT_OVER CP OVER REC OVER INV -OVER CD _,LERT TB ALERT 20O 125 160 160 200 175 WATER/BRINE ^F DEG F ^F ^F ^F DEG F MEDIUM CWDB ERT TRIP REF OVER EVAP AL CONE) AL CDFRt_EZE WATER 1.0 33 3 5 6 34 0-1 0.5 - 50.0 0.5 - 50.0 0.5-5 15-300 DSABLE/ENABLE PSI PSI MIN SEC FLOWDISP EVAP CUT CONE) CUT WFLO_/ T OILPR T DSABLE 5.0 5.0 5 4O 2.0-10.0 0.5-4.0 DEG F DEG F rcycr dt rcycs dt F F F F Spare Alert/Alarm Enable Disable=0, Lo=1/3,Hi=2/4 Spare Spare Spare Spare Temp Temp Temp Temp #1 #1 #2 #2 0-4 -40-245 0-4 -40-245 Enable Limit Enable Limit DEG F DEG F splen spllim sp2_en sp21im 0 245 0 245 NOTE: No variables are available for CCN read operation. Forcing shall not be supported on service screens. EXAMPLE 19 -- SETUP2 DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MENU]. 2. Press _. 3. Scroll down to highlight [EQUIPMENT SERVICE]. 4. Press _SE[EC_. 5. Scroll down to highlight ISETUP2]. 6. Press FSELEC_. DESCRIPTION STATUS POINT DEFAULT gv_inc gv_dec gw_ecw 6.5 6.0 2 % gv_ctrl 8O 0/1 0-78 0-100 0-78 0-10o 0-78 0-10o 15-22 DSABLE/ENABLE % % % % % % mA diff_opt gv25 df 25 gv 50 df 50 gv_75 df 75 diff ma DSABLE 25 0 5O 0 75 0 18 0.1-1.5 1-5 65-100 90-100 % % % vfd gain vfd step vfd min vfd_max 0.75 2 7O 100 Capacity Control Proportional Inc Band Proportional DEC Band Proportional ECW Band 2-I0 2-I0 I-3 Guide Vane Travel Limit 30- I O0 Diffuser Control Diffuser Option Guide Vane 25% Load Pt Diffuser 25% Load Point Guide Vane 50% Load Pt Diffuser 50% Load Point Guide Vane 75% Load Pt Diffuser 75% Load Point Diffuser Full Span mA VFD Speed Control VFD Gain VFD Increase Step VFD Minimum Speed VFD Maximum Speed UNITS NOTE: No variables are available for CCN read or write operation; forcing shall not be supported on service screens. 32 Table 4 -- ICVC Display Data (cont) EXAMPLE 20 -- LEADLAG DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press [MENU]. 2. Press _. 3. Scroll down to highlight IEQUIPMENT SERVICE I . 4. Press [SELECT]. 5. Scroll down to highlight ILEADLAG I. 6. Press [SEL_T]. DESCRIPTION STATUS Lead Lag Control LEAD/LAG: Configuration DSABLE=0, Lead=l LAG=2, STANDBY=3 Load Balance Option Common Sensor Option LAG % Capacity LAG Address LAG START Timer LAG STOP Timer PRESTART FAULT Timer STANDBY Chiller Option STANDBY % Capacity STANDBY Address UNITS 0-3 DSABLE/ENABLE DSABLE/ENABLE % 0/1 0/1 25-75 1-236 2-60 2-60 2-30 0/1 25-75 1-236 MIN MIN MIN DSABLE/ENABLE % POINT DEFAULT leadlag o Ioadbal commsens lag_per lagadd lagstart lagstop preflt stndopt stnd_per stnd_add DSABLE DSABLE 5O 92 10 10 5 DSABLE 5O 93 POINT DEFAULT 1 NOTE: No variables are available for CCN read or write operation. EXAMPLE 21 -- RAMP DEM DISPLAY SCREEN To access this display from the IOVC default screen: 1. Press [MENO]. 2. Press _. 3. Scroll down to highlight IEQUIPMENT SERVICE I . 4. Press [SELECT]. 5. Scroll down to highlight IRAMP DEM I . 6. Press [S_E_]. DESCRIPTION STATUS 0/1 Pulldown Ramp Type: Select: Temp=0, Load=l Demand Limit and kW Ramp Demand Limit Source Select: Amps=0, kW=l Amps or Kw Ramp%/Min Demand Limit Prop Band Demand Limit At 20 mA 20 mA Demand Limit Opt Demand Watts Interval UNITS rampslct 0/1 5-20 3-15 40-100 0/1 5-60 dem_src kw ramp dem_app dem_20ma dem sel dw_i_t lO lO 4o DSABLE 15 UNITS POINT DEFAULT 0/1 2-10 DSABLE/ENABLE ^F ecw_opt trap ramp DSABLE 3 -30- 30 ^F deg_20ma 10 -40-245 -40-245 -30-30 DEG F DEG F ^F res_rtl res rt2 deg- rt 85 65 10 0-15 0-15 -30-30 AF restd_l restd 2 deg_chw 10 0 5 res_sel 0 % % DSABLE/ENABLE MIN NOTE: No variables are available for CCN read or write operation. EXAMPLE 221TEMP_CTL DISPLAY SCREEN To access this display from the ICVC default screen: 1. Press[MEN 0]. 2. Press_. 3. Scroll down to highlightlEQUIPMENT SERVICE I . 4. Press[SELECT]. 5. Scroll down to highlightlTEMP CTq. 6. Press[SEL_T]. DESCRIPTION Control Point ECW Control Option Temp Pulldown Deg/Min Temperature Reset RESET TYPE f Degrees Reset At 20 mA RESET TYPE 2 Remote Temp 1> No Reset Remote Temp 1> Full Reset Degrees Reset RESET TYPE 3 CHW Delta T 1> No Reset CHW Delta T 1> Full Reset Degrees Reset Enable Reset Type STATUS AF AF 0-3 33 PIC III System Table 5 -- Functions IMPORTANT: Words not Du't of ptu'agraph headings and printed in all capit_d letters can be viewed on the [CVC (e.g., LOCAL, CCN, RUNNING ALARM, etc.). Words printed both in _dl capit_d letters and it_dics can also be viewed on the ICVC and tu'e parameters (CONTROL MODE, TARGET GUIDE VANE POS, etc.) with associated v_dues (e.g., modes, temperatures, pressures, percentages, on, off. enable, disable, etc.). Words printed in _dlcapital letters and in a box represent sollkeys on the ICVC (e.g., and _ ). See Table 4 for exmnples of the type of information that can appegu on the ICVC screens. Figures 14-20 give an overview of ICVC operations and menus. Guide Vane Delta Modes NORMAL CONTROL MODE GUIDE VANE DELTA IGV VFD From +0,2 to +2.0 Increase 1st Increase when IGV = max From -0.2 to -2.0 Decrease when VFD speed = rnin Decrease 1st Normal Control mode occurs SURGE/HGBP DELTA T_ SURGE PREVENTION MODE IGV VFD Increase only if VFD speed = max and if Increase hot gas 1st bypass is present and open Decrease when ACTIVE -- DELTA T > CAPACITY CONTROL -- Generally the chiller adjusts capacity in response to deviation of leaving or entering chilled water temperature from control point. CONTROL POINT is based on the configured SETPOINT (in the SETPOINT screen: LCW SET POINT or ECW SET POINT or ICE BUILD SET POINT), and CONTROL POINT is equal to this SETPOINT plus any active chilled water reset value. A reset v_due may originate from any of the three chilled water/brine reset options configured in the ICVC Service/Equipment Service/ TEMP CTL screen (see page 42) or from a CCN device. The default reset v_due is 0 ° E CONTROL POINT may be viewed or manually overridden from the MAINSTAT screen. Surge Prevention Mode occurs < SURGE/HGBP DELTA T_ Minor adjustments to the rate of capacity adjustment can be made by changing PROPORTIONAL INC (Increase) BAND, PROPORTIONAL DEC (Decrease) BAND, and PROPORTIONAL ECW (Entering Chilled Water) GAIN in the Service/ Equipment Service/SETUP2 screen. Increasing the PROPORTIONAL [NC BAND or PROPORTIONAL DEC BAND, or decreasing PROPORTIONAL ECW GAIN will reduce the amplitude of the capacity control response (within limits). See also Proportional Bands and Gain on page 35. The TARGET VFD SPEED, ACTUAL VFD SPEED and the VFD GAIN can be viewed and modified in the CAPACITY display screen. The TARGET VFD SPEED can be manually overridden by the operator fi'om the COMPRESS screen. The VFD MINIMUM SPEED, VFD MAXIMUM SPEED, VFD GAIN and VFD INCREASE STEP can be selected and modified in the SETUP2 display screen. TARGET and ACTUAL VFD SPEED can be viewed in the COMPRESS screen. when ACTIVE DELTA T The VFD GAIN ptuameter allows for additional adjustment of the VFD response. Increasing VFD GAIN will increase the rate of speed change. Generally for the case of line voltage equaling motor voltage (460 volts), VFD output 0notor) current is a few percent higher than line current at full speed (60 Hz). As drive speeds decrease fiom maximum, drive output voltage decreases linedy with output frequency, and motor current continues to increase relative to line current. ECW CONTROL OPTION -- If this option is enabled, the PIC III uses the ENTERING CHILLED WATER temperature to modulate the vanes instead of the LEAVING CHILLED WATER temperature. The ECW CONTROL OPTION may be viewed on the TEMP_CTL screen, which is accessed fiom the EQUIPMENT SERVICE screen. CONTROL POINT DEAD)BAND-This is the tolerance range on the chilled water/brine temperature control point. If the water temperature goes outside the CHILLED WATER DEADBAND, the PIC III opens or closes the guide vanes until the temperature is within tolerance. The PIC III may be configured with a 0.5 to 2 F (0.3 to 1.1 C) deadband. CHILLED WATER DEADBAND may be viewed or modified on the SETUPI screen, which is accessed from the EQUIPMENT SERVICE table. Factors and variables used in the capacity control determination are displayed in the Service/Control Algorithln Status/ Capacity screen and in the Status/COMPR screen. Viewing this data will aid in troubleshooting and understanding current operation. Variable Speed (VFD) Application -- The PIC III controls the machine capacity by modulating both motor speed and inlet guide vanes in response to chilled water temperature deviation from the CONTROL POINT (see above). During operation when the CONTROL POINT is not met within 1/3 the width of the CHILLED WATER DEAD)BAND, the controller will calculate a GUIDE VANE DELTA which will effect a percentage change to either the guide vane position or TARGET VFD SPEED. Factol.s considered in the capacity control algorithln include: (1) the sign and magnitude of GUIDE VANE DELTA (based on deviation from CONTROL POINT adjusted for the error trends and CHILLED WATER DEAl)BAND), (2) ACTUAL GUIDE VANE POSITION, (3) ACTUAL VFD SPEED, and (4) surge prevention mode. Generally the controller will maintain the highest inlet guide vane setting at the lowest speed to maximize efficiency while avoiding surge. For example, a 1° F (0.6 ° C) deadband setting controls the water temperature within _+0.5° F (0.3 ° C) of the control point. This may cause fiequent guide vane movement if the chilled water load fluctuates frequently. A value of 1° F (0.6 ° C) is the default setting. DIFFUSER CONTROL--On all units with Frmne 5 compmssol.s and those Frmne 4 compressors with the variable (split ring) dilluser option, the PIC III adjusts the difluser actuator position (DIFFUSER ACTUATOR on the COMPRESS screen) based on the ACTUAL GUIDE VANE POSITION. This is done in accordance with a compressor build-specific "schedule" entered in the SETUP2 screen. The schedule consists of guide wme and diffuser positions for three points (designated as the 25%, 50%, and 75% Load Points). In order for the schedule to be valid, the guide vane values must be ascending and the diffuser values must be descending for the three points. Diflhser actuator output is controlled by a 4 to 20 mA output from CCM terminals J8-3(+) and J8-4(-). Figure shows the relationship between diffuser-related pguameters for a typic_d build. See Fig. 21. First the c',_culation of GUIDE VANE DELTA is performed. If GUIDE VANE DELTA is positive, the response will be an IGV or VFD position increase (within limits). If GUIDE VANE DELTA is negative, the response will be gm IGV or VFD position decrease (within limits). Next, the surge prevention mode is detemfined based on location of the present operating point on the CHILLED WATER DELTA T/ACTIVE DELTA P map relative the configured stage prevention line. This mode will either be Norm_d or Surge Prevention. The table below indicates which output is modulated that. When the Ih.st output roaches its limit (ACTUAL GUIDE VANE position roaches maximum), the second output is modulated. See Table 5. 34 Full Open 2 mA (O%) 4 mA (0.2% KILOWATTS (demand) by limiting capacity via guide vane control. The limit applied is called ACTIVE DEMAND LIMIT. which is equ_d to a BASE DEMAND LIMIT value (set in the SETPOINTS Screen, page 22, default value 100%), or that determined by AUTO DEMAND LIMIT INPUT (tin optional 4 to 20 mA input, described below). ACTIVE DEMAND LIMIT may _flso be forced to be different from BASE DEMAND LIMIT by manually overriding the value (forcing) from the MAINSTAT screen or writing a value via a CCN network device, or controlled by another chiller in Lead Lag operation (see page 44). surge more likely *6 c£ 75 % Load Point o o surge 50 % Load 09 less likely Point rotating stall less likely rJ. The demand limit may be based on either line cunent or kW. as indicated by DEMAND LIMIT SOURCE in the EQUIPMENT SERVICE/RAMP_DEM table. The default is 0, for demand limiting based on AVERAGE LINE CURRENT (percent of RATED LINE AMPS, as displayed on the default screen). Setting DEMAND LIMIT SOURCE to 1 makes demand limiting based on PERCENT LINE KILOWATTS (displayed in the MAINSTAT scleen). LINE KILOWATTS is measured by the VFD, and the MOTOR RATED LOAD kW value (100% rated kW) is set in the VFD_CONF table. Full -Closed 25 % Load approx, 4 rnA* Point I (_00%) 0 % * Diffuser full Span mA. Fig. 21 -- 50 % 78 % GUIDE VANE OPENING (%) Diffuser Control If the DEMAND LIMIT SOURCE (percent line current) exceeds the ACTIVE DEMAND LIMIT by 5% or less, increases in guide vane opening will be prevented. If the DEMAND LIMIT SOURCE (percent line current) exceeds the ACTIVE DEMAND LIMIT by more than 5%, the guide vanes will be forced to close. Also, as the DEMAND LIMIT SOURCE approaches the ACTIVE DEMAND LIMIT from a lower value, allowable capacity increases become increasingly more limited, beginning when the DEMAND LIMIT SOURCE is within the DEMAND LIMIT PROP BAND (configumble in the RAMP_DEM table). Diffuser control output is enabled whenever the DIFFUSER OPTION is enabled, whether the machine is rtmning or not. As shown in Fig. 21,0% output corresponds to a full open diffusel: The minimum closed position (25% Load Point value) will be at less than 100% for most diffusers (depending upon the model). This coordinated guide vane-diffiJser operation may be tested in the Control Test selection "IGV & SRD Actuator". Note that the diffuser actuator should NOT be forced to a greater percent than the configured 25% Load Point (maximum) value. The diffuser opening can be incremented from fully open to completely closed. A 0% setting is tully open; a 100% setting is completely closed. To obtain file proper settings for Diffuser Control, contact a Carrier Engineering representative. Demand Limit Control Option -- The demand limit control option (20 mA DEMAND LIMIT OPT) is extern_flly controlled by a 4 to 20 mA signal from an energy management system (EMS). The option is set up on the RAMP_DEM screen. When enabled, 4 mA will set ACTIVE DEMAND LIMIT to 100% of the DEMAND LIMIT SOURCE Qegardless of the value of BASE DEMAND LIMIT), and 20 mA will set ACTIVE DEMAND LIMIT to the value configured as "20MA DEMAND LIMIT OPT" in the RAMP_DEM table. PROPORTIONAL BANDS AND GAIN -- Proportiomfl band is the rote at which capacity control (including guide vane position and, if applicable, VFD speed) is adjusted in proportion to how far the chilled water/brine temperature is from the CONTROL POINT. Proportional gain determines how quickly capacity control reacts to how quickly the temperature is moving from the CONTROL POINT. The proportional bands and gain may be viewed or modified from the SETUP2 scleen, which is accessed from the EQUIPMENT SERVICE table. Wire the auto demand limit input to terminals J5-1 (-) and J5-2 (+) on the CCM. In order to use a 1 to 5 vdc input instead of 4 to 20 mA, install a 25 ohm resistor in series with the + lead at terminal J5-2. The Proportional Band -- Thele gu'e two response modes, one for temperature response above the control point, the other for the response below the control point. A DEMAND KILOWATI'S monitoring feature is also available. This feature provides a display of average demand (power) in kilowatts (in the POWER screen). This v_due is continuously updated and averaged over the preceding time interval specified as DEMAND WATFS INTERVAL in the SERVICE / EQUIPMENT SERVICE/RAMP DEM screen. CHILLER TIMERS AND STARTS COUNTER -- The PIC III m_dntains two run time clocks: COMPRESSOR ONTIME and SERVICE ONTIME. COMPRESSOR ONTIME indicates file total lifetime compressor run hours. SERVICE ONTIME is a _esettable timer that can be used to indicate the hours since file last service visit or any other event. A separate counter tallies compressor stmls as TOTAL COMPRESSOR STARTS. All of these can be viewed on the MA[NSTAT screen on the ICVC. Both ontime counters roll over to 0 at 500,000 hom.s. Manual changes to SERVICE ONTIME from the ICVC me permitted at any time. If the controller is replaced, one opportunity, before the first st_utup with the new controllel; is provided to set COMPRESSOR ONTIME and TOTAL COMPRESSOR STARTS to the last readings retained with the prior controllel: The SERVICE ONTIME timer can register up to 32,767 hours before it rolls over to zero. The temperature response above the control point is called the PROPORTIONAL INC BAND, and it can slow or quicken capacity control response to chilled water/brine temperatures above the CHILLED WATER DEADBAND. The PROPORTIONAL INCBAND can be adjusted from a setting of 2 to 10; the default setting is 6.5. The response below the control point is called the PROPORTIONAL DEC BAND, and it can slow or quicken the capacity control response to chilled water temperature below the deadband plus file control point. The PROPORTIONAL DEC BAND can be adjusted on the ICVC from a setting of 2 to 10. The default setting is 6.0. NOTE: Increasing either of these settings causes the capacity control to respond more slowly than at a lower setting. The PROPORTIONAL ECW GAIN can be adjusted on the ICVC display for v_dues of 1, 2, or 3; the default setting is 2. Increase this setting to increase guide vane response to a change in entering chilled water temperatme. DEMAND LIMITING--The PIC III controls provide a feature for limiting AVERAGE LINE CURRENT or LINE 35 Thechilleralsomaintains a start-to-stmt timer and a stop-to-start time_: These timers limit how soon the chiller can be started. START INHIBIT TIMER is displayed on the MAINSTAT screen. See the Start-Up/Shutdown/Recycle Sequence section, page 50, for more information on this topic. • VFD power faults • VFD over temperature • dew formation on the VFD cold plate *Superlleat is the difference between saturation temperature and sensible temperature. The high discharge temperature safety measures only sensible temperature. VFD faults or optional protective devices within the VFD can shut down the chillel: OCCUPANCY SCHEDULE--The chiller schedule, described in the Time Schedule Operation section (page 21 ), determines when the chiller can ran. Each schedule consists of from 1 to 8 occupied or unoccupied time periods, set by the operatol: The chiller can be stm-ted and run during an occupied time period (when OCCUPIED? is set to YES on the MAINSTAT display screen). It cannot be started or run during an unoccupied time period (when OCCUPIED? is set to NO on file MAINSTAT display screen). These time periods can be set for each &ty of file week and for holi&tys. The day begins wifll 0000 hours and ends with 2400 hours. The default setting for OCCUPIED? is YES, unless an unoccupied time period is in effect. If compressor motor overload occurs, check the motor for grounded or open phases before attempting a restart. If the PIC [IXcontrol initiates a safety shutdown, it displays the reason for the shutdown (the fault) on the ICVC display screen along with a primmy and seconda q message, and blinks the alarm light on the control panel. The ahum is stored in memory and can be viewed on the ALARM HISTORY and VFD_HIST screens on the ICVC, along with a message for troubleshooting. If the safety shutdown was also initiated by a fault detected in the motor stm-tek the conditions at the time of the fault will be stored in VFD_HIST. These schedules can be set up to follow a building's occupancy schedule, or the chiller can be set so to run 100% of the time, if the operator wishes. The schedules also can be bypassed by forcing the CHILLER START/STOP parameter on the MAINSTAT screen to START. For more information on forced starts, see Loc_fl Start-Up, page 50. The schedules also can be overridden to keep file chiller in an occupied state for up to 4 hours, on a one time basis. See the Time Schedule Operation section, page 21. To give morn precise information or warnings on the chiller's operating condition, the operator can define alert limits on various monitored inputs in the SETUPI screen. A partkd list of protective safety and alert limits is provided in Table 6. A complete list of alarm and alert messages is provided in the Troubleshooting Guide section, page 79. Figure 19 shows a schedule for a typical office building with a 3-horn: off-peak, cool-down period from midnight to 3 a.m., following a weekend shutdown. Holickly periods are in an unoccupied state 24 hours per day. The building operates Monday through Friday. 7:00 a.m. to 6:00 p.m., and Saturdays from 6:00 a.m. to 1:00 p.m. This schedule also includes the Monday midnight to 3:00 a.m. weekend cool-down schedule. Shunt Trip (Option) -- The function of the shunt trip option on the PIC Ill is to act as a safety trip. The shunt trip is wired from the stan&trd I/O board to a shunt trip equipped VFD circuit breakel: If the HC IIl tries to shut down the compressor using a normal shutdown procedure but is unsuccessful for 20 seconds, the shunt trip output is energized and causes the circuit breaker to trip off. If ground fault protection has been applied to the startel; file ground fault trip also energizes the shunt trip to trip the circuit breakel: Protective devices in the starter can also energize the shunt trip. The shunt trip feature can be tested using the Control Test feature in the DISCRETE OUTPUTS CONTROL TEST screen. NOTE: This schedule is for illustration only and is not intended to be a recommended schedule for chiller operation. Whenever the chiller is in the LOCAL mode, it uses Occupancy Schedule 01 (OCCPC01S). When the chiller is in the ICE BUILD mode, it uses Occupancy Schedule 02 (OCCPC02S). When the chiller is in CCN mode, it uses Occupancy Schedule 03 (OCCPC03S). The CCN SCHEDULE NUMBER is configured on the NET OPT display scleen, accessed from the EQUIPMENT CONFIGURATION table. See NiNe 4, Exalnple 15. SCHEDULE NUMBER can be changed to tiny v_flue from 03 to 99. If this number is changed on the NET OPT screen, the operator must go to the ATTACH TO NETWORK DEVICE screen to upload the new number into the SCHEDULE screen. See Fig. 17. Default Screen Freeze -- When the chiller is in an al;um state, the default ICVC display "freezes," that is, it stops updating. The til_t line of the ICVC default screen displays a primary akum message; the second line displays a secon&lry ;darm message. The ICVC default screen freezes to enable the operator to see the conditions of the chiller at the time of the alarm. If the value in almm is one nommlly displayed on the default screen, it flashes between normal and reverse contrast. The ICVC default screen remains frozen until the condition that caused the akum is remedied by the operator Use [CVC display and alarm shutdown record sheet (CL-12) to record all v;dues from default screen freeze. Safety Controls -- _n_e PIC III monitors all safety control inputs and, if required, shuts down the chiller or limits the guide wines to protect the chiller from possible damage from any of the following conditions: • high bearing temperature • high motor winding temperature • high discharge temperature • low discharge superlleat* • low oil pressure • low cooler refrigerant temperature/pressure • condenser high pressure or low pressure • inadequate water/brine cooler and condenser flow • high, low, or loss of voltage • ground fault • voltage imbalance • current imbalance • excessive motor acceleration time • excessive starter transition time • lack of motor current signal • excessive motor amps • excessive compressor surge • temperature and transducer faults Knowledge of the operating state of the chiller at file time an alarm occurs is useful when troubleshooting. Additional chiller information can be viewed on the status screens and the VFD_HIST screen. Troubleshooting information is recorded in the ALARM HISTORY table, which can be accessed from the SERVICE menu. To determine what caused the _flmm, the operator should mad both file primary and secondm-y default screen messages, as well as the aimin history. The primmy message indicates file most recent almm condition. The secon&lry message gives more derail on the algum condition. Since there may be more than one alarm condition, another _darm message may appetu after the fil.st condition is clemed. Check the ALARM HISTORY screen for additional help in determining the reasons for file _flarms. Once _dl existing _dmms me clemed (by pressing the softkey), the default ICVC display returns to norm_fl operation. 36 Table 6 -- Protective Safety Limits and Control Settings MONITORED Temperature Pressure PARAMETER Sensors Out of Range Transducers High Compressor Out of Range Discharge Temperature ALARM/ ALERT .O6>Voltage Ratio>.98 or - 40 F> Temperature>245 F for 3 seconds Preset Alarm, Voltage Ratio=Input Voltage Reference(5 Volts) Voltage/ 260-271 .06>Voltage Preset Alarm, Voltage Ratio=Input Voltage Reference(5 Volts) Voltage/ 231 103 233 102 Compressor Thrust Bearing Temperature 101 234 243 Low Evaporator Temperature Freeze Protection) 232 1 o4 Transducer 239 Voltage Fault High Condenser Pressure --Control 235 Ratio>.98 COMP DISCHARGE (104.4 C) COMP DISCHARGE ALERT for 3 seconds TEMP > 220 F Preset Alarm, Configure COMP ALERT in SETUP1 screen TEMP > COMP DISCHARGE Configure COMP DISCHARGE screen COMP DISCHARGE TEMP > COMP DISCHARGE ALERT - 10 F (5.6 C) COMP MOTOR WINDING TEMP > 220 F (104 C) COMP MOTOR WINDING TEMP > COMP MOTOR TEMP OVERRIDE - 10 F (5.6 C) COMP THRUST BRG TEMP > COMP THRUST BRG ALERT - 10 F (5.6 C) COMP THRUST BRG TEMP > 185 F (85 C) Chiller in RECYCLE SHUTDOWN and EVAP TEMPEVAP APPROACH ALERT Preset Alarm, Configure EVAP APPROACH ALERT in SETUP1 screen 0 ° F (-17.8 C) EVAP APPROACH ALERT Configure EVAP REFRIG TRIP POINT and CHILLED MEDIUM in SETUP1 screen EVAPORATOR REFRIG TEMP < 33 F + REFRIG OVERRIDE DELTA T (water) EVAPORATOR REFRIG TEMP < EVAP REFRIG TRIPPOINT (brine) Prestart Alert, Configure REFRIG OVERRIDE DELTA T in SETUP1 screen 5.5 VDC< Voltage Reference<4.5 VDC CONDENSER PRESSURE > 165 PSI Preset Alarm Preset Alarm, Switch closes at 110 _+- PSIG Preset Alarm, Configure COMP MOTOR TEMP OVERRIDE in SETUP1 screen Prestart Alert, Configure COMP MOTOR TEMP OVERRIDE in SETUP1 screen Preset Alert, Configure COMP THRUST ALERT in SETUP1 screen Preset Alarm, configure EVAP REFRIG TRIPPOINT in SETUP1 screen Prestart Alert, Configure EVAP REFRIG TRIPPOINT and CHILLED MEDIUM in SETUP1 screen Preset Alarm, Configure COND PRESS OVERRIDE in SETUP1 screen Prestart 106 CONDENSER PRESSURE OVERRIDE - 20 PSI > COND PRESS Prestart Alert, Configure COND PRESS OVERRIDE in SETUP1 screen CONDENSER > 145 PSI Prestart Alert PRESSURE _+5 PSIG) & 244 Chiller in PUMPDOWN mode and CONDENSER REFRIG TEMP < CONDENSER FREEZE POINT Preset Alarm, Configure CONDENSER POINT in SETUP1 screen. 154 Energizes condenser pump relay if CONDENSER REFRIGTEMP CONDENSER FREEZE POINT + 5 ° F (2.8 ° C) and ENTERING COND LIQUID > CONDENSER FREEZE POINT Configure CONDENSER SETUP1 screen 228 OIL PRESSURE DELTA P < 13 PSlD and VFD START = TRUE Preset Alarm OIL PRESSURE DELTA P < 18 PSlD and startup complete after OIL PRESS VERIFY TIME elapsed Preset Alarm, Configure OIL PRESS VERIFY TIME in SETUP1 screen Preset Alert Low Pressure 142 OIL PRESSURE complete Pressure 227 OIL PRESSURE DELTA P > 4 PSI immediately before oil pump turned on OILSUMPTEMP < 150 Fand OILSUMPTEMP EVAP REFRIG TEMP + 50 F (27.8 C) Sensor Fault Low Temperature Line Voltage--High 105 211/145 DELTA P < 18 PSlD and startup Line voltage > approximately calculated by VFD High 108 Low 212/146 Low 107 PERCENT threshold Imbalance 216 LINE VOLTAGE IMBALANCE % IMBALANCE Single Cycle Dropout Imbalance Line Frequency Out of Range ICVC Power on Reset BRG Preset Alarm High Pressure Switch Open(165 VFD START = YES Low Pressure Power -- ALERT in SETUP1 207 Low Pressure Line Current -- DISCHARGE Switch Low Condenser Pressure Freeze Protection) Oil-- COMMENTS 260-271, 140,141 167 High Motor Temperature LIMIT 210/144 209/143 222 214/148 PERCENT threshold 528 V, limits are LINE VOLTAGE > Overveltage DC BUS VOLTAGE < approximately limits are calculated by a VFD 408 V, LINE VOLTAGE < Undervoltage > LINE VOLTAGE < Prestart Alert Preset Alarm/Alert Preset Prestart Alert Preset Alarm/Alert Preset Prestart Alert Configure LINE VOLTAGE % IMBALANCE and LINE VOLT IMBALANCE TIME in VFD CONF screen Preset Alarm 47 Hz < LINE FREQUENCY Preset Alarm < 63 Hz 37 POINT in Preset Alarm Line Voltage on 2 Phases < 50% for 1 Cycle LINE CURRENT IMBALANCE>LINE CURRENT % IMBALANCE Loss of control power to ICVC for excessive time _eriod FREEZE FREEZE Configure LINE CURRENT % IMBALANCE LINE CURRENT IMBALANCE TIME in VFD CONF screen Preset Alarm and Table 6 -- Protective Limits and Control Settings MONITORED Motor- PARAMETER ALARM/ALERT (cont) LIMIT COMMENTS Surge 236 > 5 surge events within SURGE TIME PERIOD and VFD SPEED > 90% Preset Alarm, Configure SURGE DELTA% AMPS and SURGE TIME PERIOD in OPTIONS screen Surge 236 > 5 surge events within SURGE TIME PERIOD and VFD SPEED < 90% Preset Alarm, Configure SURGE DELTA% AMPS and SURGE TIME PERIOD in OPTIONS screen Current Imbalance 225 MOTOR CURRENT IMBALANCE>MOTOR CURRENT % IMBALANCE Configure MOTOR CURRENT % IMBALANCE and MOTOR CURRENT IMBAL TIME in VFD CONF screen Overload 217 Any LOAD CURRENT PHASE > 108% for Excessive Time Period Preset Alarm, Configure MOTOR LOAD ACTIVE DEMAND LIMIT in MAINSTAT screen Excessive Amps Acceleration Fault 206 PERCENT Preset Alarm 2O3 PERCENT LOAD CURRENT > 95% and VFDSTART = TRUE for 5 to 40 sec Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS Amps Not Sensed 202 PERCENT LOAD CURRENT < 5% for 3 seconds and VFD START=TRUE for 20 sec Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS Starts Limit Exceeded Trip LOAD CURRENT > 110% for 30 sec. 100 More than 8 starts in 12 hours Preset Prestart Alert Low Chilled Water Flow 229 Optional Alarm, Configure WATER FLOW VERIFY TIME in SETUP1 screen Low Cond Water Flow 230 High Approach--Evaporator 162 CHILLED LIQUID FLOW = FALSE after CHILLED WATER PUMP = ON & WATER FLOW VERIFY TIME elapsed COND WATER FLOW = FALSE after COND WATER PUMP = ON & WATER FLOW VERIFY TIME elapsed EVAPORATOR APPROACH > EVAP APPROACH ALERT and startup complete CONDENSER APPROACH > COND APPROACH ALERT and startup complete ACTUAL VFD SPEED > VFD SPEED OUTPUT + 10% 204 PERCENT LOAD CURRENT VFDSTART = NO for 20 sec >15% and Preset Alarm, PERCENT LOAD CURRENT = AVERAGE LOAD CURRENT/MOTOR RATED LOAD AMPS 218 RECTIFIER limit exceeded Preset Alarm, Configure RECTIFIER OVERRIDE in SETUP1 screen TEMP 110 RECTIFIER TEMPERATURE > RECTIFIER OVERRIDE -20 F (11.1 C) Rectifier current limit exceeded Prestart Alert, Configure RECTIFIER OVERRIDE in SETUP1 screen TEMP Condenser VFD--High Inverter-- 245 VFD Speed Failureto Rectifier-- 163 Stop High Temperature TEMP Configure EVAP APPROACH screen Configure COND APPROACH screen ALERT in SETUP1 ALERT in SETUP1 Preset Alarm, Must be outside +10% threshold 75 sec. Overcurrent 241 Power Fault 2OO IGBT current limit exceeded or a fault was detected in the rectifier Preset Alarm High Temperature 219 INVERTER Preset Alarm, Configure INVERTER TEMP OVERRIDE in SETUP1 screen 111 286 INVERTER TEMPERATURE > INVERTER OVERRIDE-20 F (11.1 C) Inverter current limit exceeded 201 IGBT current limit exceeded Preset Alarm 256 Inductor temperature Preset Alarm, Temperature opened Preset Alarm/Alert Power Fault Inductor TEMPERATURE Optional Alarm, Configure WATER FLOW VERIFY TIME in SETUP1 screen -- Overtemperature DC Bus Voltage -- Switch High Low Ground Fault Optional Limits -- 205/166 215 22O Spare Temperature Guide Vane Position Low Discharge Superheat 158,159, 248,249 253 240 TEMPERATURE Preset Alarm limit exceeded TEMP limit exceeded DC BUS VOLTAGE Limit Exceeded Prestart Alert, Configure INVERTER OVERRIDE in SETUP1 screen TEMP Preset Alarm DC BUS VOLTAGE <407VDC at 400/480 V Line Side Voltage GROUND FAULT CURRENT > 7% of Drive Rated Amps Sensed SPARE TEMPERATURE > SPARE TEMP LIMIT Preset Alarm ACTUAL GUIDE VANE POS > 4% after 4 minutes of closing ACTUAL GUIDE VANE POSITION < .045 volts after startup complete ACTUAL GUIDE VANE POSITION > 3.15 volts after startup complete ACTUAL GUIDE VANE POSITION < -1% after startup complete ACTUAL GUIDE VANE POSITION > 103% after startup complete DISCHARGE SUPERHEAT < SUPERHEAT REQUIRED -3 ° F (1.7 ° C) for 60 seconds Preset Alarm 38 for switch in reactor has Preset Alarm Optional Alarm/Alert, Configure SPARE TEMP ENABLE and SPARE TEMP LIMIT in SETUP1 screen Preset Alarm Preset Alarm Preset Alarm Preset Alarm Preset Alarm, DISCHARGE SUPERHEAT = COMP DISCHARGE TEMP - CONDENSER REFRIG TEMP Ramp Loading -- Tile rmnp loading control slows down tile rate at which the compressor loads up. This control can prevent the compressor fiom loading up during the short period of time when tile chiller is started and tile chilled water loop has to be brought down to CONTROL POINT. This helps reduce electlical demand charges by slowly bringing the chilled water to CONTROL POINT. The total power draw during this period remains ahnost unchanged. Whenever the motor current demand limit set point (ACTIVE DEMAND LIMIT) is reached, it activates a capacity ovenide, again, with a 2-step process. Exceeding 110% of the rated load amps for more than 30 seconds will initiate a safety shutdown. The high compressor lift (surge prevention) set point will cause a capacity ovenide as well. When the surge prevention set point is reached, the controller normally will only prevent the guide vanes from opening. If so equipped, the hot gas bypass valve will open instead of holding the vanes. The hot gas bypass will only open if the compressor is at 100% speed. See the Surge Prevention Algorithm section, page 42. There are several methods of romp loading with the PIC III. Ramp loading can be based on LEAVING CHILLED WATER, ENTERING CHILLED WATER, PERCENT LINE CURENT or PERCENT MOTOR KILOWATFS. PULLDOWN RAMP TYPE is selected fiom tile RAMP DEM screen. High Discharge Temperature 1. Temperature ramp loading (TEMP PULLDOWN DE(;/ MIN) limits the degrees per minute rote at which either LEA VING CHILLED WATER or ENTERING CHILLED WATER temperature decreases. This rate is configured by the operator on the TEMP_CTL screen. NOTE: If chiller control power has been off for 3 hours or more, file next startup (only) will follow temperature ramp loading using the minimum rate regardless of the rmnp loading method and rate which m:e configured in the screens. This is used to maximize oil reclaim during stmtup. 2. Oil Sump Temperature and Pump Control -- The oil sump telnperature is regulated by the PIC III, with the oil heater relay when the chiller is shut down. As part of the pre-start checks executed by the controls, the oil sump temperature (OIL SUMP TEMP) is compared to the cooler refrigerant temperature (EVAPORATOR REFRIG TEMP) if the OIL SUMP TEMP is less than 150 F (65.6). If the diffelence between these 2 temperatures is 50 F (27.8 C) or less, the start-up will be delayed until either of these conditions is no longer true. Once this temperature criteria is satisfied, the start-up continues. The oil heater relay is energized whenever the chiller compressor is off and the oil sump temperature is less than 140 F (60.0 C) or the OIL SUMP TEMP is less than the EVAP REFRIG TEMP plus 53 ° F (29.4 ° C). The oil heater is turned off when the OIL SUMP TEMP is either: • morethan 152 F (66.7 C), or • more than 142 F (61.1 C) and more than the EVAP REFRIG TEMP plus 55 ° F (30.6 ° C). The oil heater is always off during start-up or when the compressor is running. The oil pump is also energized dnring the time the oil is being heated (for 30 seconds at the end of every 30 minutes). The oil pump will not operate if the EVAPORATOR PRESSURE is less than -5 psig (-34.5 kPa). Motor load ramp loading (AMPS OR KW RAMP %/ MINI limits the rate at which tile compressor motor current or complessor motor load increases. The AMPS OR KW RAMP %/MIN rate is configured by the operator on the RAMP_DEM screen in line current or motor kilowatts. If kilowatts is selected for the DEMAND LIMIT SOURCE, the MOTOR RATED LOAD KILOWATTS must be entered in the VFD_CONF screen. The TEMP PULLDOWN DEG/MIN may be viewed or modified on the TEMP_CTL screen which is accessed from the EQUIPMENT SERVICE screen. PULLDOWN RAMP TYPE, DEMAND LIMIT SO URCE, and AMPS OR KW RAMP _/MIN may be viewed or modified on the RAMP_DEM screen. Capacity Override Control -- If the COMP DISCltARGE TEMP increases above 160 F (71.1 C), the guide vanes _ue proportionally opened to increase gas flow through the compressol: If the LEAVING CHILLED WATER temperature decreases 5 ° F (2.8 ° C) below the control set point temperature, as a result of opening the guide vanes, the PIC III will bring the chiller into the recycle mode. (Table 7) -- Capacity overrides can prevent some safety shutdowns caused by exceeding the motor amperage limit, low evaporator temperature safety limit, high motor temperature safety limit, and high condenser pressure limit. In all cases there are two stages of compressor capacity control applied by guide vane operation. 1. When the value of interest crosses the First Stage Set point into the Override Region, the guide vanes are prevented from opening furthel: and the status line on the ICVC indicates the reason for the override. Normal capacity control operation is restoled when the value crosses back over the First Stage Set point, leaving the Override Region. (Refer to Table 7.) Oil Cooler -- The oil must be cooled when the compressor is running. This is accomplished through a small, plate-type heat exchanger (also called the oil cooler) located behind the oil pump. The heat exchanger uses liquid condenser refrigerant as the cooling liquid. Refrigerant thermostatic expansion valves (TXVs) regulate refrigerant flow to control the oil temperature entering the bearings. The bulbs for the expansion valves are strapped to the oil supply line leaving the heat exchangel: and the valves are set to maintain 110 F (43 C). 2. When the value of interest is in the Override Region and further crosses the Second Stage Set point, the guide vanes me closed until the value meets the Ovenide Termination Condition. The PIC III controls resume norm_d capacity control operation after the override termination condition has been satisfied. (In the case of high dischmge supeflleat, there is an intermediate stage). NOTE: The TXVs me not adjustable. The oil sump tempemtme may be at a lower temperature during compressor operation. 39 Table 7 -- Capacity Overrides FIRST STAGE SET POINT OVERRIDE CONDITION View/Modify on ICVC Screen High Condenser Pressure (COND PRESS OVERRIDE) SETUP1 High Motor Temperature (COMP MOTOR TEMP OVERRIDE) Override Default Value CONDENSER PRESSURE >125 psig (862 kPa) SECOND Configurable Range 90 to 165 psig (621 to 1138 kPa) COMP MOTOR WINDING TEMP > 2OO F (93 C) SETUP1 150 to 200 F (66 to 93 C) REFRIG TEMP < EVAP REFRIG TRIPPOINT + 3 F (1.7 C) SETUP1 Min TI: 1.5 F (0.8 C) High Compressor Lift (SURGE/HGBP DELTA T,P) OVERRIDE TERMINATION Value Value CONDENSER PRESSURE > COND PRESS OVERRIDE + 2.4 psig (16.5 kPA) CONDENSER PRESSURE < CONDENSER PRESS OVERRIDE - 1 PSI (6.9 kPa) COMP MOTOR WINDING TEMP > COMP MOTOR TEMP OVERRIDE + 10 F (5.6 C) COMPR MOTOR WINDING TEMP < COMP MOTOR TEMP OVERRIDE2 F (1.1 C) 2 to 5 F (1.1 to 2.8 C) - 1 F (.6 C) NOTE: EVAP REF OVERRIDE TEMP = EVAP REFRIG TRIPPOINT + REFRIG OVERRIDE DELTA T EVAP REFRIG TEMP > EVAP REF OVERRIDE TEMP +2F(1.1C) 0.5 - 2.0 F (0.3- 1.1 C) 30 - 170 psid (207 - 1172 kPad) 0.5 - 20 F (0.3- 11,1 C) 50 - 170 psid (345 - 1172 kPad) None ACTIVE DELTA T > SURGE/ HGBP DELTA T + SURGE/HGBP DEADBAND Automatic 0 to 100% None Press RELEASE softkey after selecting TARGET GUIDE VANE POS COMPRESS Automatic VFD MINIMUM SPEED to 100% MAINSTAT Automatic 40 to 100% OPTIONS Min PI: 50 psid (345 kPa) Max T2:10 F (5.6 C) Max P2:85 psid (586 kPad) Manual Guide Vane Target (TARGET GUIDE VANE POS) STAGE SET POINT EVAPORATOR REFRIG TEMP < EVAP REF OVERRIDE TEMP EVAPORATOR Low Evaporator Temperature (REFRIG OVERRIDE DELTA T) Table COMPRESS Forced TARGET VFD SPEED Manual Speed Control (TARGET VFD SPEED) Motor Load (ACTIVE DEMAND LIMIT) ACTUAL SUPERLow Discharge Superheat OVERRIDE HEAT< SUPERHEAT REQUIRED for conditions High Rectifier Temperature (RECTIFIER TEMP OVERRIDE) SETUP1 RECTIFIER TEMPERATURE> 160 F (71 C) High Inverter Temperature (INVERTER TEMP OVERRIDE) SETUP1 INVERTER TEMPERATURE 160 F(71 C) Remote Start/Stop Controls > None ACTIVE DEMAND < Set Point - 2% LIMIT LIMIT ACTUAL SUPERHEAT < SUPERHEAT REQUIRED ACTUAL SUPERHEAT > SUPERHEAT REQUIRED + 1 F (0.56 C) RECTIFIER TEMP > RECTIFIER TEMP OVERRIDE + 10 F (5,6 C) RECTIFIER TEMP < RECTIFIER TEMP OVERRIDE - 5 F (2.8 C) 155 to 170 F INVERTER TEMP > INVERTER TEMP OVERRIDE + 10 F(5,6C) INVERTER TEMP < INVERTER TEMP OVERRIDE -5 F(2.8C) (66 to 77 C) the certified drawings for further details on contact ratings. The contacts must have 24 vac dry contact rating. may be used to stmt Spare Safety and Spare Temperature Inputs -- Norln_dly closed (NC) discrete inputs for addition_d fieldsupplied safeties may be wired to the spare protective limits input channel in place of the factory-installed jumper on terminals 19 and 20 of the low voltage terminal strip. The opening of tiny contact will result in a safety shutdown and a display on the ICVC. Refer to the certified drawings for safety contact ratings. IN 12 HOURS parmneter on the MAINSTAT screen) occur. (not counting either lecycle restmts or auto restarts after power failure) an excessive starts alarm displays, preventing the from starting. Tile operator ACTIVE DEMAND > Set Point + 5% - 1.25 F (0,7 C) and stop the chillel: Howevel; the device should not be progmmmed to st_ut and stop file chiller in excess of 2 or 3 times every 12 hours. If more than 8 st_uts in 12 hom_ (the STARTS chiller Press RELEASE softkey after selecting TARGET VFD SPEED 155 to 170 F (66 to 77 C) -- A remote device, such as a timeclock that uses a set of contacts, cannot override either a capacity inhibit or a capacity decrease command generated by the PIC III must press the softkey on the ICVC to override the starts counter and start the chillel: If the chiller records 12 starts (excluding recycle starts) in a sliding 12-hour period, it can be lestarted only by pressing Extra amdog telnperature sensors may also be added to the CCM module (SPARE TEMPERATURE #l and SPARE TEMPERATURE #2) at terminals J4 25-26 and J4 27-28, respectively. The analog temperature sensors may be configured in the EQUIPMENT SERVICE/SETUPI table to cause an alert (Enable value l or 2) or almm (Enable value 3 or 4), or neither (Enable value 0). An alarm will shut down a running chiller, but an alert will not. The fault condition will be triggered when crossing a high limit (Enable value 2 or 4) or low limit (Enable value l or 3), configurable between -40 F to 245 F (-40 C to 118 C). The spare temperature sensors are readable on the CCN netwoN. They also have specific uses as common temperature sensors in a Lead/Lag system (see page 44). the _ softkey followed by the _ or _ softkey. This ensures that, if the automatic system is m_dfunctioning, the chiller will not repeatedly cycle on and off. If the AUTORESTART OPTION in the OPTIONS scieen and the REMOTE CONTACTS OPTION are enabled, the REMOTE CONTRACTS must be closed in order for the chiller to lest_ut following a power failure. If the automatic restmt after a power failure option (AUTO RESTART OPTION on file OPTIONS screen) is not activated when a power failure occurs, and if the remote contact is closed, the chiller will indicate an _darm Alarm (Trip) Output Contacts -- One set of alarm contacts is provided in file stmlel: The contact ratings are provided in the certified drawings. The contacts are located on terminals 9 and l0 of the TB2 field wiring terminal strip in the VFD enclosure. because of the loss of voltage. The contacts for remote start are wired into terminals 23 trod 24 of the low voltage terminal strip in the VFD enclosure. See 4O When the chiller is off and CONDENSER REFRIG TEMP is less than the CONDENSER FREEZE POINT, the CONDENSER WATER PUMP will be energized (Alert State 154) Howevel, if the chiller is in pump down, and when it entered pump down mode the CONDENSING REFRIG TEMP was more than 5 ° F (2.7 ° C) above the CONDENSER FREEZE POINT. the same low temperature condition will generate Alarm State 244 trod the CONDENSER WATER PUMP will be energized. In either case, the fault state will clem and the pump will turn off when the CONDENSER REFRIG TEMP is more than 5 ° F (2.7 ° C) above the CONDENSER FREEZE POINT and the entering condenser water temperature is greater than the CONDENSER FREEZE POINT. If the chiller is in Recycle Shutdown Mode when the condition occurs, the controls will transition to a non-recycle shutdown. Kilowatt Output -- An output is available on tile CCM module [Terminal J8-1 (+) and J8-2 (-)1 to represent the power consumption of the chiller Tile 4 to 20 mA signal generated by the CCM module can be wired to the building automation or energy management system to monitor the chiller's energy consumption. Output is 2 mA with the chiller off. and it varies linedy from 4 mA (representing 0% rated kilowatt consumption) to 20 mA (representing 100% RATED LINE KILOWATFS). The rated peak kilowatt consumption is configured by the user in the VFD_CONF display screen by the setting the RATED LINE KILOWATFS fiom the machine electrical &tta nameplate. Remote Reset of Alarms -- A stan&u'd feature of the PIC |II controls is the ability to reset a chiller in a shutdown alarm state from a remote location. [f the condition which caused the alarm has cleared the chiller can be placed back into a normal CCN operating mode when the REMOTE RESET OPTION (ICVC_PSWD menu) is set to ENABLE. A variety of Career Comfort Network software systems including ComfortVIEW TM or Network Sel-v'ice Tool TM can access the PIC III controls and reset the displayed alarm. Third party software from building automation systems (BAS) or energy management systems (EMS) can also access the PIC III controls through a Carrier DataLINK rM module and reset the fault displayed. Both methods would access the ICVC_PSWD screen and fome the RESETALARM? point to YES to reset the fault condition. [f the P[C III controls have determined that is safe to start the chiller the CCN MODE? point (ICVC_PSWD screen) can be forced to YES to place the chiller back into norln;fl CCN operating mode. The only exceptions am the following ahums that cannot be reset from a remote location: Aimm/Alert STATE 100, 200, 201, 204, 206, 217-220, 233, 234, 247, and 259. To view alarm codes, refer to Troubleshooting Guide, Checking Display Messages, page 79. After the alarm has been reset the PIC HI control will increment the STARTS IN 12 HOURS counter by one upon restart. If the limit of 8 starts in a 12-hour period is reached (Pmstart/Alert state 100), this must be reset at the local chiller control panel Evaporator Freeze Protection -- When the EVAPORATOR REFRIG TEMP is less than the EVAP REFRIG TRIPPOINT plus the REFRIG OVERRIDE DELTA T (configurable fi_m 2 ° to 5 ° F or 1.1 ° to 2.8 ° C), Alert State 122 will be displayed, and a capacity override will occm: (See Table 7.) When the unit is running or in recycle, if the EVAPORATOR REFRIG TEMP is equal to or less than the EVAP REFRIG TRIPPOINT (33 ° F or 0.6 ° C for watek configurable for brine), Protective Limit Alarm State 232 will be displayed, the unit will shut down, and the CHILLED WATER PUMP will remgfin on. The alarm will be clem'able when the leaving chilled water temperature rises 5°F (2.8°C) above the CONTROL POINT. When the unit is off, if the EVAPORATOR REFRIG TEMP is less than the EVAP REFRIG TRIPPOINTplus 1° F (0.6 ° C), Alarm State 243 will be generated and the CHILLED WATER PUMP will be turned on. The _flmm can be reset when the EVAPORATOR REFRIG TEMP rises 5 ° F (2.8 ° C) above the EVAP REFRIG TRIPPOINT` Tower Fan Relay Low and High -- Low condenser water temperature can cause the chiller to shut down when refrigerant temperature is low. The tower fan relays, located in the stmter, am controlled by the PIC III to energize and deenergize as the pressure differential between cooler and condenser vessels changes. This prevents low condenser water temperaturn and maximizes chiller efficiency. The tower fan relay can only accomplish flris if the relay has been added to the cooling tower temperature controllel: TOWER FAN RELAY LOW is turned on whenever the condenser water pump is running, flow is verified, ;rod the difference between cooler and condenser pressure is more than 30 psid (207 kPad) for entering condenser water temperature greater than 65 F (18.3 C). TOWER FAN RELAY LOW is turned off when the condenser pump is off. flow is stopped, or the EVAP REFRIGERANT TEMP is less than the EVAP REF OVERRIDE TEMP for ENTERING CONDENSER WATER temperature less than 62 F (16.7 C), or the difference between the CONDENSER PRESSURE and EVAPORATOR PRESSURE is less than 25 psi d (172.4 kPad) for ENTERING CONDENSER water less than 80 F (27 C). TOWER FAN RELAY HIGH is turned on whenever the condenser water pump is running, flow is verified and the difference between EVAPORATOR PRESSURE and CONDENSER PRESSURE is more than 35 psid (241.3 kPa) for ENTERING COND WATER temperature greater than the TOWER FAN HIGH SETPOINT (SETPOINT menu, default 75 F [23.9 C]). (IeVC). Condenser Pump Control -- The chiller will monitor the CONDENSER PRESSURE and may turn on the condenser pump if the condenser pressure becomes too high while the compressor is shut down. The COND PRESS OVERRIDE paralneter is used to determine this pressure point. COND PRESS OVERRIDE is found in the SETUPI display screen, which is accessed from the EQUIPMENT SERVICE table. The default value is 125 psig (862 kPa). If the CONDENSER PRESSURE is greater than or equal to the COND PRESS OVERRIDE, and the ENTERING CONDENSER WATER temperature is less than 115 F (46 C), the condenser pump will energize to try to decrease the pressure and Alert 151 will be generated. The pump will turn off when the condenser pressure is 3.5 psi (24.1 kPa) less than the pressure override and the CONDENSER REFRIG TEMP is within 3 ° F (1.7 ° C)of the ENTERING CONDENSER WATER temperature. Condenser Freeze Prevention -- This control _dgorithm helps prevent condenser tube freeze-up by energizing the condenser pump relay. The PIC III controls the pump and, by starting it, helps to prevent the water in the condenser fiom freezing. The PIC III can perform this lhnction whenever the chiller is not running excq)t when it is either actively in pumpdown or in pumpdown/lockout with the fieeze prevention disabled. 41 TileTOWER FAN RELAY HIGH is turned off when the condenser pump is off, flow is stopped, or the EVAPORATOR REFRIG TEMP is less than the EVAP REF OVERRIDE TEMP and ENTERING CONDENSER WATER is less than 70 F (21.1 C), or the difference between EVAPORATOR PRESSURE and CONDENSER PRESSURE is less than 28 Psid (193 kPa), and ENTERING CONDENSER WATER temperature is less than TOWER FAN HIGH SETPOINT minus 3 F (-16.1 C). Tile TOWER FAN RELAY LOW and TOWER FAN RELAY HIGH parameters are accessed fiom the STARTUP screen. input the reset type number (1, 2, or 3) in the SELECT/ ENABLE RESET TYPE input line. RESET TYPE 1:4 to 20 mA (1 to 5 vdc) TEMPERATURE RESET - Reset Type 1 is "automatic" reset utilizing a 4 to 20 mA or 1 to 5 vdc analog input signal provided from any external sensol; controllel: or other device which is appropriately configured. Reset Type 1 permits up to _+30° F (_+16.7 ° C) of reset to the chilled water set point. Inputs are wired to terlninals J5-3 (-) and J5-4 (+) on the CCM (for 4-20 mA input). In order to utilize a 1 to 5 vdc input, a 250 ohln resistor must be wired in series with the + input lead (J5-4). For either input type, SW2 DIP switches should be set in the ON (up) position. Inputs equivalent to less than 4 mA result in no reset, and inputs exceeding 20 mA are treated as 20 mA. RESET TYPE 2: REMOTE TEMPERATURE RESET -Reset Type 2 is an automatic chilled water temperature reset based on a remote temperature sensor input signal. Reset type 2 permits _+30 ° F (_+ 16 ° C) of automatic reset to the set point based on a temperature sensor wired to the CCM module (see wiring diagrams or certified diawings). The temperature sensor must be wired to terminal J4-13 and J4-14. To configure Reset Type 2, enter the temperature of the remote sensor at the point where no temperature reset will occur (REMOTE TEMP -> NO RESET). Next, enter the temperatme at which the full amount of reset will occur (REMOTE TEMP -> FULL RESET). Then, enter the maximum mnount of reset requiled to operate the chiller (DEGREES RESET). Reset Type 2 can now be activated. IMPORTANT: A field-supplied water temperature control system for condenser water should be installed. Tile system should maintain the leaving condenser water temperature at a temperatme that is at least 20 ° F (11 ° C) above file leaving chilled water temperature. The tower fan relay control is not a substitute for a condenser water temperature control. When used with a water temperature control system, the tower fan relay control can be used to help prevent low condenser water temperatures. Auto. Restart After Power Failure -- Tiais option may be enabled or disabled and may be viewed or modified on the OPTIONS screen, which is accessed from the EQUIPMENT CONFIGURATION table. If the AUTO RESTART OPTION is enabled, the chiller will st:ut up automatically after a power failure has occurred, generating one of the following faults: single cycle dropout (if enabled), line cunent imbalance, high line voltage, low line voltage, low DC bus voltage, high DC bus voltage, VFD power on reset, and ICVC power on reset (alerts 143-148, 165 and 166). With this feature enabled, these faults _u'e treated as alerts instead of alarms, so st_utup proceeds as soon as the condition is rectified. The 15 and 1-minute start inhibit timers are ignoled during this type of startup, and the STARTS IN 12 HOURS counter is not incremented. RESET TYPE 3 -- Reset Type 3 is an automatic chilled water temperature reset based on cooler temperature difference. Reset Type 3 adds _+30 ° F (_+ 16° C) based on the temperature diffelence between the ENTERING CHILLED WATER and LEA VIAl(; CHILLED WATER temperature. To configure Reset Type 3, enter the chilled water temperature difference (the difference between entering and leaving chilled water) at which no temperature reset occurs (CHW DELTA T-> NO RESET). Tills chilled water temperature difference is usually the full design load temperature difference. Next, enter the difference in chilled water temperature at which the full amount of reset occurs (CttWDELTA T-> FULL RESET). Finally. enter the amount of reset (DEGREES RESET). Reset Type 3 can now be activated. When power is restored after file power failure and if the compressor had been running, the oil pump will energize for one minute before energizing the cooler pump. AUTO RESTART will then continue like a normal start-up. Surge Prevention Algorithm -- This is an operator configumble feature that can determine if lift conditions are too high for the compressor and then take corrective action. Lift is defined as the difference between the plessure at the impeller eye and at the impeller discharge. Tile maximum lift a particular impeller wheel can perform varies with the gas flow through the impeller and the dialneter of the impellec If power to the ICVC module has been off for mole than 3 hours or the timeclock has been set for the fi_t time, start the compressor with the slowest TEMP PULLDOWN DEG/MIN rate possible in order to minimize oil foaming. Tile oil pump is energized occasionally during the time the oil is being brought up to proper tempemtme in order to eliminate refiigemnt that has migrated to the oil sump during the power failure. The pump turns on for 30 seconds at the end of every 30-minute period until the chiller is started. Tile lift capability (surge line) of a v_uiable speed compressor shifts upward as speed increases. Consequently. the line which serves as the surge prevention threshold is made to shift upward in a similar fashion as speed is increased. If the operating point goes above the surge prevention line as adjusted for the current operating speed, then surge prevention actions are taken. Note that the line constructed fiom SURGE/HGBP DELTA TI, SURGE/HBBP DELTA PI, SURGE/HBBP DELTA T2, and SURGE/HBBP DELTA P2 values is applied to the full speed condition only. These surge characteristics are factory set based on the original selection, with the values printed on a label affixed to the bottom interior face of the control panel. Since operating conditions may affect the surge plevention algorithm, some field adjustments may be necessary. Water/Brine Reset -- Chilled water capacity control is based on achieving and maintaining a CONTROL POINT temperatme, which is the sum of the LCWSETPOINTorECW SETPOINT (from the SETPOINT screen) and a Water/Brine Reset value, if any. CONTROL POINTis limited to a minimum of 35 F (+1.7 C) for water, or 10 F (-12.2 C) for brine. Tilree types of chilled water or brine reset are available and can be viewed or modified on the TEMP_CTL screen, which is accessed from the EQUIPMENT SERVICE table. Tile ICVC default screen indicates when the chilled water reset is active. TEMPERATURE RESET on the MAINSTAT screen indicates the amount of reset. Tile CONTROL POINT will be determined by adding the TEMPERATURE RESET to the SETPOINT. A chiller equipped with a VFD can adjust inlet guide position or compressor speed to avoid surge (if not already at COMPRESSOR 100% SPEED). Thus, the primary response to entering the surge prevention region or incurring an actual surge event (see file Surge Protection section) is to increase complessor speed. This moves the compressor's surge line and To activate a reset type, access the TEMP_CTL scleen and input all configuration information for that reset type. Tilen, 42 thecontrol's modelof thesurgeprevention lineup.Guide vanes arenotpermitted toopenfurther whensurge prevention ison.Oncespeed hasbeenincreased tomaximum, if stilloperatinginthesurge prevention region andif theHotGasBypass optionisinstalled, thehotgasbypass valve will open. When in Surge Prevention mode, withacommand todecrease capacity theguide vanes willclose butspeed willnotdecrease. NOTE:If uponromp-up a chillerwithVFDtends togotofull speed before guidevanes openfully,that is an indication that the lift at low load is excessive, and the operating point moved directly into the surge prevention region. In this case, investigate the ability of the condenser cooling means (e.g., cooling tower) to provide cooling water in accor&mce with the design load/entering condenser water temperature schedule. The portion of the surge count threshold attributable to cur- rent can be adjusted from the OPTIONS screen (see Table 4). Scroll down to the SURGE DELTA % AMPS parameter, and use the [INCREASE] or [DECREASE] softkey to adjust the percent current fluctuation. The default setting is 10% amps. The SURGE TIME PERIOD can also be adjusted from the OPTIONS soeen. Scroll to the SURGE TIME PERIOD parameter, and use the [INCREASE] or [DECREASE]softkey to adjust the amount of time. The default setting is 8 minutes. Access the display soeen (COMPRESS) to monitor surge count (SURGE PROTECTION COUNTS). A surge condition occm:s when the lift becomes so high the gas flow across the impeller reverses. This condition can eventu_dly cause chiller damage. When enabled, the Surge Prevention Algorithm will adjust either the ACTUAL GUIDE VANE POSITION or ACTUAL VFD SPEED to maintain the complessor at a safe distance from surge while maintaining machine efficiency. If the surge condition degrades then the algorithm will move aggressively away from surge. This condition can be identified when the SURGE/H(;BP ACTIVE? on the HEAT EX display screen displays a YES. the 19XRV DEFAULTS:ATt = 1.5= F AP1 = 50 psid AT2 = llY" F AP2 = 85 psid HGBP/SURGE PREVENTION ON 85- _p (psi) The surge prevention algorithm first determines if corrective action is necessary. The algorithm checks two sets of operator-configured data points, the lower stage point (MIN. LOAD POINT [T1,P1]) and the upper surge point (FULL LOAD POINT [T2,P2]). The surge characteristics vary between different chiller configurations and operating conditions. DEADBAND REGION (lo, 85) , 50- 1 The surge prevention algorithm function and settings are graphically displayed on Fig. 22 and 23. The two sets of load points on the graph (default settings m'e shown) describe a line the algorithm uses to determine the maximum lift of the compressor for the design maximum operating speed. When the actual differential pressme between the cooler and condenser (delta P) and the temperature difference between the entering and leaving chilled water (delta T) are above the line on the graph (as defined by the MIN LOAD POINTS and FULL LOAD POINTS), the algorithm operates in Surge Prevention mode. This is determined when the ACTIVE DELTA T is less than SURGE/HGBP DELTA T minus the SURGE/HGBP DEADBAND. 2 3 4 5 6 7 8 9 10 11 AT (F) LEGEND ECW HGBP LOW ---- Entering Chilled Water Hot Gas Bypass Leaving Chilled Water AP = (Condenser Psi) -(Cooler AT = (ECW) - (LCW) Psi) Fig. 22-19XRV Not Gas Bypass/Surge Prevention with Default English Settings zxp (kPa) 19XRV DEFAULTS: When in Surge Prevention mode, with a command to increase capacity, the VFD speed will increase until VFD MAXIMUM SPEED is reached. At VFD MAXIMUM SPEED, when Capacity still needs to increase, the IGV's open. When in Surge Plevention mode, with a command to decrease capacity, the IGVs will close. The optional hot gas bypass will open in surge prevention mode only if the TARGET VFD SPEED is at the VFD MAXIMUM SPEED. AT1 =.8° C APt = 345 kPad AT2 = 5.6° C AP2 = 586 kPad HGBP/SURGE PREVENTION ON DEADBAND (&6, 586) REGION 500- Surge Protection -- The PIC III monitors surge, which is detected as a fluctuation in compressor motor amperage. Each time the fluctuation exceeds an operator-specified limit, the PIC III registers a stage protection count. The current fluctuation threshold that triggers a surge protection count is equal to the sum of SURGE DELTA % AMPS plus the CHILLED WATER DELTA T. If more than 5 surges occur within an operator-specified time (SURGE TIME PERIOD), the PIC III initiates a surge protection shutdown of the chillec The SURGE PROTECTION COUNTS remain displayed in the COMPRESS screen until the almm is reset, at which time they are re-zeroed. 400- 300- .2 A .6 .81,0 2.0 3.0 4.0 5.0 &T (C) LEGEND ECW RGBP LOW If a surge count is registered and if ACTUAL VFD SPEED is less than VFD MAXIMUM SPEED then motor speed will be increased by the configured VFD INCREASE STER While the SURGE PROTECTION COUNTS are >0, a speed decrease will not be honored. ---- Entering Chilled Water Hot Gas Bypass Leaving Chilled Water AP = (Condenser kPa) - (Cooler kPa) AT = (ECW) - (LCW) Fig. 23 i 19XRV Hot Gas Bypass/Surge Prevention with Default Metric Settings 43 6.0 Head Pressure Reference Output (See Fig. 24) -- • • • • • The PIC [II control outputs a 4 to 20 mA signal for the configurable Delta P (CONDENSER PRESSURE minus EVAPORATOR PRESSURE) leference cmwe shown in Fig. 24. The DELTA P AT 100% (chiller at maximum load condition default at 50 psi), DELTA P AT 0% (chiller at minimum load condition default at 25 psi) trod MINIMUM OUTPUT points are configurable in the EQUIPMENT SERVICE-OPTIONS table. When configuring this output ensure that minimum requirements for oil pressure and proper condenser FLASC onlice performance are mtdntained. The 4 to 20 mA output from VFD TBI terminals 17 and 18 may be useful as a reference signal to control a towel bypass valve, tower speed control, condenser pump speed control, etc. Note that it is up to the site design engineering agent to integrate this analog output with any external system device(s) to produce the desired effect. Carrier does not make any claim that this output is directly usable to control any specific piece of equipment (that is, without further control elements or signal conditioning), although it may be. COMMON POINT TIONLead/lag chilled water point (Spare Temp #1 and desired. SENSOR USAGE AND INSTALLAoperation does not require a common sensor However. common point sensors #2) may be added to the CCM module, if NOTE: If the common point sensor option is chosen on a chilled water system, each chiller should have its own common point sensor installed. Each chiller uses its own common point sensor for control when that chiller is designated as the lead chillel: The PIC III cannot read the value of common point sensors installed on the other chillers in the chilled water system. If leaving chilled water control (ECW CONTROL OPTION is set to 0 [DSABLEI TEMP CTL screen) and a common point sensor is desired (COMMON SENSOR OPTION in LEADLAG screen selected as 1) then the sensor is wired in Spare Temp #1 position on the CCM (terminals J4-25 and J4-J26). The head pressure reference output will be on whenever the condenser pump is operating. It may also be manually operated in CONTROLS TEST. When the head pressure differential is less than the value entered forDELTA PATO%, the output will be maintained at 4 mA. If the entering chilled water control option (ECW CONTROL OPTION) is enabled (configured in TEMP_CTL screen) and a common point sensor is desired (COMMON SENSOR OPTION in LEADLAG screen selected as 1) then the sensor is wired in Spare Temp #2 position on the CCM (terminals J4-27 and J4-28). Lead/Lag Control -- The lead/lag control system automatically starts and stops a lag or second chiller in a 2-chiller water system. A third chiller can be added to the lead/lag system as a standby chiller to start up in case the lead or lag chiller in the system has shut down during an ahum condition and additional cooling is required. Refer to Fig. 17 and 18 for menu, table, and screen selection information. When installing chillers in series, either a common point sensor should be used (preferred), or the LEAVING CHILLED WATER sensor of the upstremn chiller must be moved into the leaving chilled water pipe of the downstream chillel: In this application the COMMON SENSOR OPTION should only be enabled for the upstremn chiller if that chiller is configured as the Lead. NOTE: The lead/lag function can be configured on the LEADLAG screen, which is accessed from the SERVICE menu and EQUIPMENT SERVICE table. See Table 4, Example 20. Lead/lag status during chiller operation can be viewed on the LL_MAINT display screen, which is accessed from the SERVICE menu and CONTROL ALGORITHM STATUS table. See Table 4, Example 12. If ENTERING CHILLED WATER control is required on chillers piped in series, either the common point return chilled water sensor should be used (preferred), or the LEAVING CHILLED WATER sensor of the downstream chiller must be relocated to the LEAVING CHILLED WATER pipe of the upstream chiller. In this application the COMMON SENSOR OPTION should only be enabled for the downstream chiller if that chiller is configured as the Lead. Note that ENTERING CHILLED WATER control is not recommended for chillers installed in series due to potential control stability problems. To properly control the LEAVING CHILLED WATER TEMPERATURE when chillers me piped in parallel, the water flow through the shutdown chiller(s) should be isolated so that no water bypass around the operating chiller occurs. However. if water bypass around the operating chiller is unavoi&_ble, a common point sensor in the mixed LEAVING CHILLED WATER piping should be provided and enabled for the Lead chillel: Lead/Lag System Requirements: • all chillers in the system must have software capable of performing the lead/lag function • water pumps MUST be energized from the PIC III controls • water flows should be constant • the CCN time schedules for all chillers must be identical Operation Features: • 2chiller lead/lag DELTAP AT100% "3 l NON-ZERO ',EXAMPLE OF ' M N MUM ',REFERENCE ',OUTPUT DE LTA P addition of a third chiller for backup manual rotation of lead chiller load balancing if configured staggered restart of the chillers after a power failure chillers may be piped in parallel or in series chilled water flow CHILLER COMMUNICATION chiller's Installation Instructions, Interface section for infommtion wiring. s" a" i DELTA P__ AT0% ===7 LEAD/LAG OPERATIONThe PIC III not only has the ability to operate 2 chillers in lead/lag, but it can also start a designated standby chiller when either the lead or lag chiller is faulted and capacity requirements are not met. The lead/lag option only operates when the chillel_ are in CCN mode. If any other chiller configured for lead/lag is set to the LOCAL or OFF modes, it will be unavailable for lead/lag operation. t = .......... ]11 0mA 2 mA4mA (O%) 20 mA (100%) 4T0 20 mA OUTPUT Fig. 24- Head Pressure Reference WIRING -- Refer to the Cmrier Comfort Network on chiller communication Output 44 Lead/Lag Chiller Configuration and Operation • A chiller is designated the lead chiller when its LEADLAG: CONFIGURATION value on the LEADLAG screen is set to "1 ." • A chiller is designated the lag chiller when its LEADLAG: CONFIGURATION value is set to "2." • A chiller is designated as a standby chiller when its LEADLAG: CONFIGURATION value is set to "3." • A value of "0" disables the lead/lag designation of a chiller. This setting should also be used when "normal" operation without regard to lead/lag rules is desired (in LOCAL or CCN mode). only if one of the other two chillel_ is in an alarm (*) condition (as shown on file ICVC panel). If both lead and lag chillers me in an alarm (*) condition, the standby chiller defaults to operate in CCN mode, will operate based on its configured CCN occupancy schedule and remote contacts input. Lag Chiller Start-Up Requirements -- Before the lag chiller can be started, the following conditions must be met: 1. Lead chiller ramp loading must be complete. 2. When configuring the LAG ADDRESS value on the LEADLAG screen of chiller "A" enter the address of the chiller on the system which will serve as lag when/if chiller "A" is configured as lead. For example, if you ale configuring chiller A, enter the address for chiller B as file lag address. [f you ale configuring chiller B, enter the addiess for chiller A as the lag address. This makes it easier to rotate the lead and lag chillers. Note that only the lag and standby chiller addresses specified in the configmed lead chiller's table me relevant at a given time. Lead chilled water temperature must be greater than the CONTROL POINT temperature (see the MAINSTAT screen) plus 1/2 the CHILLED WATER DEADBAND temperature (see the SETUPI screen). NOTE: The chilled water telnperature sensor may be the leaving chilled water sensor, the return water sensol: the common supply water sensor, or the common return water sensor, depending on which options are configured and enabled. 3. 4. If file address assignlnents in the LAG ADDRESS and STANDBY ADDRESS parameters conflict, the lead/lag function is disabled and an alert (!) message displays. For example, if the LAG ADDRESS matches the lead chiller's addiess, the lead/lag will be disabled and an alert (!) message displayed. The lead/lag maintenance screen (LL_MAINT) displays the message 'INVALID CONFIG' in the LEADLAG: CONFIGURATION and CURRENT MODE fields. The lead chiller responds to normal start/stop controls such as the occupancy schedule, a forced start or stop, and lemote start contact inputs. After completing stmt-up and ramp loading, the PIC III evaluates the need for additional capacity. If additional capacity is needed, the PIC III initiates the stmt-up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in _darm) or is in the OFF or LOCAL modes, the chiller at file STANDBY ADDRESS (if configured) is requested to start. After the second chiller is stmted and is running, the lead chiller monitors conditions and evaluates whether the capacity has been reduced enough for the lead chiller to sustain the system alone. If the capacity is reduced enough for file lead chiller to sustain the CONTROL POINT temperatures alone, then the operating lag chiller is stopped. Lead chiller ACTIVE DEMAND LIMIT (see the MAINSTAT screen) value must be greater than 95% of lhll load mnps. Lead chiller telnperature pulldown rate (TEMP PULLDOWN DEG_IN on the TEMP_CTL screen) of the chilled water temperature is less than 0.5 ° F (0.27 ° C) per minute for a susttdned period of 100 seconds. 5. The lag chiller status indicates it is in CCN mode and is not in an alarm condition. If the current lag chiller is in tin alarm condition, the standby chiller becomes the active lag chiller, if it is configured and available. 6. The configured LAG START TIMER entry has elapsed. The LAG START TIMER stmts when the lead chiller rmnp loading is completed. The LAG START TIMER entry is on the LEADLAG screen, which is accessed from the EQUIPMENT SERVICE table of the SERVICE menu. When all the above requirements have been met, file lag chiller is commanded to a STARTUP mode (indicated by "CONTRL" flashing next to the CHILLER START/STOP parameter in the MAINSTAT screen). The PIC III control then monitors the lag chiller for a successful stark If the lag chiller fails to start, the standby chiller, if configured, is started. Lag Chiller Shutdown Requirements -- The following conditions must be met in order for the lag chiller to be stopped. 1. Lead chiller AVERAGE LINE CURRENT or MOTOR PERCENT KILOWATTS (on the MAINSTAT screen) is less than the lead chiller percent capacity. NOTE: Lead Chiller Pement Capacity = 115 - LAG % CAPACITY The LAG % CAPACITY parameter is on the LEADLAG screen, which is accessed from the EQUIPMENT SERVICE table on the SERVICE menu. If the lead chiller is stopped in CCN mode for tiny reason other than an almm (*) condition, the lag and standby chillers are also stopped. If the configured lead chiller stops for an alarln condition, the configured lag chiller takes the lead chiller's place as the lead chillel: and the standby chiller serves as the lag chillel: The PRESTART FAULT TIMER provides a timeout if there is a prestart alert condition that prevents a chiller from starting in a timely mannel: If the configured lead chiller does not complete its start-up before the PRESTART FAULT TIMER (a user-configured v_due) elapses, then the lag chiller starts, and the lead chiller shuts down. The lead chiller then monitors the lag, acting as the lead, for a stm't request. The PRESTART FAULT TIMER parameter is on the LEADLAG screen, which is accessed fi_m the EQUIPMENT SERVICE table of the SERVICE menu. If the lag chiller does not achieve start-up before the PRESTART FAULT TIMER elapses, the lag chiller stops, and the standby chiller is requested to start, if configured and ready. 2. The lead chiller chilled water temperature is less than the CONTROL POINT temperature (see the MAINSTAT screen) plus I/2 the CHILLED WATER DEADBAND temperature (see the SETUPI screen). 3. The configured LAG STOP TIMER entry has elapsed. The LAG STOP TIMER starts when the lead chiller chilled water temperature is less than file chilled water CONTROL POINT plus 1/2 of the CHILLED WATER DEADBAND trod the lead chiller compressor motor load (MOTOR PERCENT KILOWATT or AVERAGE LINE CURRENT on the MAINSTAT screen) is less than the Lead Chiller Percent Capacity. NOTE: Lead Chiller Percent Capacity = 115 - LAG % CAPACITY The LAG % CAPACITY parameter is on the LEADLAG screen, which is accessed fi_>mthe EQUIPMENT SERVICE table on the SERVICE menu. Standby Chiller Configuration and Operation -- A chiller is designated as a standby chiller when its LEADLAG: CONFIGURATION wdue on the LEADLAG screen is set to "3." The standby chiller can operate as a replacement for the lag chiller 45 FAULTED CHILLER OPERATION --If file lead chiller shuts down because of an alarm (*) condition, it stops communicating to the lag and standby chillers. After 30 seconds, the lag chiller becomes the acting lead chiller and starts and stops the standby chiller, if necessary. If the lag chiller goes into alarm when file lead chiller is also in aimm, the standby chiller reverts to a stand-alone CCN mode of operation. If the lead chiller is in an alarm (*) condition (as shown on tile ICVC panel), press tile _ softkey to clear tile alarm. The chiller is placed in CCN mode. The lead chiller communicates and monitors the RUN STATUS of the lag and standby chillers. If both the lag and standby chillers are running, the lead chiller does not attempt to start and does not assume the role of lead chiller until either the lag or standby chiller shuts down. If only one chiller is running, the lead chiller waits for a stmt request from the operating chiller When the configured lead chiller stm-ts,it assumes its role as lead chillel: lee Btlih:l Control -- The selectable ice build mode permits use of the chiller to refmeze or control the temperature of an ice mselwoir which may, for example, be used for thermtd storage. This mode differs from water or brine chilling in flint terlnination (indication that the need for cooling has been satisfied) is based on input(s) other than the temperature which is being controlled during operation. NOTE: For ice build control to operate properly, the PIC HI must be in CCN mode. The PIC III can be configured for ice build operation. • From the SERVICE menu, access the EQUIPMENT SERVICE table. From there, select the OPT'IONS screen to enable or disable the ICE BUILD OPTION. See Table 4, Example 17. • The ICE BUILD SETPOINT can be configured from the SETPOINT display, which is accessed fiom the PIC III main menu. See Table 4, Example 9. • The ice build schedule can be viewed or modified from the SCHEDULE table. From this table, select the ice build schedule (OCCPC02S) screen. See Fig. 19 and the section on Time Schedule Operation, page 21, for morn information on modifying chiller schedules. The ice build time schedule defines the period(s) during which ice build is active if the ice build option is enabled. If the ice build time schedule overlaps other schedules, the ice build time schedule takes priority. During the ice build period, the CONTROL POINT is set to the ICE BUILD SETPOINT for temperature control. The ICE BUILD RECYCLE and ICE BUILD TERMINATION parameters, accessed from the OPTIONS screen, allow the chiller operator to recycle or terminate the ice build cycle. The ice build cycle can be configured to terminate when: • the ENTERING CHILLED WATER temperature is less than the ICE BUILD SETPOINZ In this case, the operator sets the ICE BUILD TERMINATION parameter to 0 (the default setting) on the OPTIONS screen. • the ICE BUILD CONTACTS input from an ice level indicator are opened. In this case, the operator sets the ICE BUILD TERMINATION parameter to 1 on the OPTIONS screen. • the chilled water temperature is less than the ICE BUILD SETPOINT and the ICE BUILD CONTACTS input from an ice level indicator are open. In this case, the operator sets the ICE BUILD TERMINATION parameter to 2 on the OPTIONS screen. • the end of the ice build time schedule (OCCPC02S) has been reached. ICE BUILD INITIATION--The ice build time schedule (OCCPC02S) is the means for activating the ice build option. Ice Build is enabled if: If the lag chiller is the only chiller running when the lead chiller assumes its role as a lead chiller then the lag chiller will perfoml a RECOVERY START REQUEST (LL_MAINT screen). The lead chiller will stmt up when the following conditions am met. 1. Lag chiller romp loading must be complete. 2. Lag CHILLED WATER TEMP (MAINSTAT screen) is greater than CONTROL POINT plus q2 the CHILLED WATER DEADBAND temperature. 3. 4. Lag chiller ACTI1/E DEMAND LIMIT value must be gleater than 95% of full load amps. Lag chiller temperature pulldown rate (TEMP PULLDOWN DEG/MIN) of the chilled water temperature is less than 0.5 F (0.27 C) per minute. 5. The standby chiller is not running as a lag chiller. 6. The configured LAG START TIMER configured in the lag (acting lead) chiller has elapsed. The LAG START TIMER is sttu-ted when the lag (acting lead) chiller's romp loading is completed. LOAD BALANCING--When the LOAD BALANCE OPTION (see LEADLAG screen) is enabled, the lead chiller sets the ACTI1/E DEMAND LIMIT in the lag chiller to the lead chiller's compressor motor load value MOTOR PERCENT KILOWATTS or AVERAGE LINE CURRENT on the MAINSTAT screen). This value has limits of 40% to 100%. In addition, the CONTROL POINT for the lag chiller must be modified to a value of 3 ° F (1.67 ° C) less than the lead chiller's CONTROL POINT value. If the LOAD BALANCE OPTION is disabled, the ACTIVE DEMAND LIMIT and the CONTROL POINTme both forced to the sallle value as the lead chillel: • AUTO. RESTART AFTER POWER FAILURE -- When an auto. restart condition occurs, each chiller may have a delay added to the stm-t-up sequence, depending on its lead/lag configuration. The lead chiller does not have a delay. The lag chiller has a 45-second delay. The standby chiller has a 90-second delay. The delay time is added after the chiller water flow is verified. The PIC III ensures the guide vanes me closed. After the guide vane position is confirmed, the delay for lag and standby chillers occurs prior to energizing the oil pump. The normtd start-up sequence then continues. The auto. rests.u1 delay sequence occurs whether the chiller is in CCN or LOCAL mode and is intended to stagger the compressor motor sttu-ts. Preventing the motors from st_uling simultaneously helps reduce the inrush demands on the building power system. • a day of the week and a time period on the ice build time schedule are enabled. The SCHEDULE screen shows an X in the day field and ON/OFF times are designated for the day(s), a,_d the ICE BUILD OPTION is enabled. The following events take place (unless overridden by a higher authority CCN device). • CHILLER START/STOP is forced to START. • The CONTROL POINT is forced to the ICE BUILD SETPOINT. • Any force (Auto) is removed from the ACTIVE DEMAND LIMIT. NOTE: A pmameter's value can be forced, that is, file vtdue can be manually changed tit the ICVC by tin operatok changed fiom another CCN device, or changed by other algorithms in the PIC III control system. 46 NOTE: TheIceBuildsteps donotoccurif thechillerisconfiguredandoperating asa lagor standby chillerfor lead/lag operation andisactively beingcontrolled byaleadchillerThe leadchillercommunicates theICE BUILD SET POINZ the CONTACTS me open and the ICE BUILD RECYCLE is set to DSABLE (0). In this case, the ICE BUILD CONTACTS provide ice level termination control. The contacts m'e used to stop the ice build function when a time period on the ice build schedule (OCCPC02S) is set for ice build operation. The remote contacts can still be opened and closed to start and stop the chiller when a specific time period on the ice build schedule is not set for ice build. desired CHILLER START/STOP state, and the ACTIVE DEMAND LIMIT to the lag or standby chiller as required for ice build, if configured to do so. START-UP/RECYCLE OPERATION -- If the chiller is not running when ice build activates, the HC III checks the following conditions, based on the ICE BUILD TERMINATION value, to avoid starting the compressor unnecessarily: • if ICE BUILD TERMINATION is set to the TEMP option and the ENTERING CHILLED WATER temperature is less than or equal to the ICE BUILD SETPOINT; • if ICE BUILD TERMINATION is set to the CONTACTS option and the ICE BUILD CONTACT is open; • if the ICE BUILD TERMINATION is set to the BOTH (temperature and contacts) option and the ENTERING CHILLED WATER temperature is less than or equal to the ICE BUILD SETPOINT and the ICE BUILD CONTACT is open. The ICE BUILD RECYCLE on the OPTIONS screen determines whether or not the chiller will go into an ice build RECYCLE mode. 4. NOTE: It is not possible to override file CHILLER START/ STOP, CONTROL POINE and ACTIVE DEMAND LIMIT variables from CCN devices (with a priority 4 or greater) during the ice build period. Howevel: a CCN device can override these settings during 2-chiller lead/lag operation. RETURN TO NON-ICE BUILD OPERATIONS -- Tile ice build lunction forces the chiller to start, even if _dl other schedules indicate that file chiller should stop. When file ice build lunction terminates, the chiller returns to normal temperatme control and st_u't!stop schedule operation. The CHILLER START/ STOP and CONTROL POINT return to normal operation. If the CHILLER START/STOP or CONTROL POINT has been forced (wifll a device of less than 4 priority) before file ice build function stmted, when the ice build lunction ends, the plevious forces (of less than 4 priority) me not automatic_dly restored. • If the ICE BUILD RECYCLE is set to DSABLE (disable), the HC III reverts to normal (non-ice build) temperature control when the ice build function is terminated by satisfying one of the above conditions. Once ice build is terminated in this manner, it will not be reinitiated until the next ice build schedule period begins. • If the ICE BUILD RECYCLE is set to ENABLE, the PIC III goes into an ICE BUILD RECYCLE mode, and the chilled water pump relay remains energized to keep the chilled water flowing when the compressor shuts down. If the temperature of the LEA1/ING CHILLED WATER later increases above the ICE BUILD SETPOINT plus half the RECYCLE RESTART DELTA T value, the compressor restarts, controlling the chilled water/brine temperature to the ICE BUILD SETPOINT. TEMPERATURE CONTROL DURING ICE BUILD -During ice build, the capacity control algorithm shall use the CONTROL POINT minus 5 F (-2.8 C) for control of the LEAVING CHILLED WATER temperature. The ECW CONTROL OPTION and any temperature reset option shall be ignored, if enabled, during ice build. Also, the following control options will be ignored during ice build operation: Attach to Network Device Control -- _qle Service menu includes the ATTACH TO NETWORK DEVICE screen. From this screen, the operator can: • enter the time schedule number (if changed) for OCCPC03S, as defined in the NET_OPT screen • attach the ICVC to any CCN device, if the chiller has been connected to a CCN network. This may include other PIC-controlled chillers. • upgrade software Figure 25 shows the ATTACH TO NETWORK DEVICE screen. The LOCAL parameter is _dways the ICVC module address of the chiller on which it is mounted. Whenever the controller identification of the ICVC changes, the change is reflected automatically in the BUS and ADDRESS columns for the local device. See Fig. 18. Default addiess for local device is BUS 0 ADDRESS 1. • ECW CONTROL OPTION and any temperature reset options (confiigured on TEMP_CTL screen). • 20 mA DEMAND LIMIT OPT (configured on RAMP_DEM screen). TERMINATION OF ICE BUILD -- The ice build lhnction terminates under the following conditions: 1. Time Schedule --When the current time on the ice build time schedule (OCCPC02S) is i,ot set as an ice build time period. 2. 3. Entering Chilled Water Temperature and ICE BUILD Contacts --Ice Build operation terminates when the ICE BUILD TERMINATION parameter is set to 2 (BOTH) and the conditions described above in items 2 and 3 for ENTERING CHILLED WATER temperature and ICE BUILD CONTACTS have occurred. When the ATFACH TO NETWORK DEVICE screen is accessed, infomlation can not be lead from the ICVC on any device until one of the devices listed on that screen is attached. The ICVC erases information about the module to which it was attached to make room for information on another device. Therefore, a CCN module must be attached when this screen is entered. To attach any CCN device, highlight softkey and press the ]ATTACH] "UPLOADING TABLES, PLEASE ICVC then uploads the highlighted Entering Chilled Water Temperature -- Ice build operation terminates, based on temperature, if the ICE BUILD TERMINATION paralneter is set to 0 (TEMP), the ENTERING CHILLED WATER temperature is less than the ICE BUILD SETPOINT. and the ICE BUILD RECYCLE is set to DSABLE. ff the ICE BUILD RECYCLE OPTION is set to ENABLE, a recycle shutdown occms and recycle start-up depends on the LEA1/ING CHILLED WATER temperature being greater than the water/brine CONTROL POINT plus the RESTART DELTA Ttemperature. it using the sollkey. WAIT' device The message displays. The or module. If the module addi'ess cannot be found, the message "COMMUNICATION FAILURE" appems. The ICVC then reverts back to the ATTACH TO DEVICE screen. Try another device or check the addiess of the device that would not attach. The upload process time for each CCN module is different. In gener_d, the uploading process takes 1 to 2 minutes. Befole leaving the ATTACH TO NETWORK DEVICE screen, select the LOCAL device. Otherwise, the ICVC will be unable to Remote Contacts/Ice Level Input -- Ice build operation terminates when the ICE BUILD TERMINATION parameter is set to 1 (CONTACTS) and the ICE BUILD display information 47 on the local chillel: ATTACHING TOOTHERCCNMODULES -- If thechillerICVChasbeenconnected toaCCNNetwork orotherPIC controlled chillel.s through CCNwiring,theICVCcanbeused tovieworchange ptuameters ontheothercontrollers. Other PICIII chillers canbeviewed andsetpointschanged (if the otherunitis in CCNcontrol), if desired, fromthisparticular ICVCmodule. If themodule number is notvalid,the"COMMUNICATIONFAILURE"message will showanda newad&ess number mustbeentered orthewiringchecked. If filemodule is communicating properly, the"UPLOADIN PROGRESS" message will flashandfilenewmodule cannowbeviewed. Whenever thereisa question regarding whichmodule on theICVCis cunently beingshown, checkthedevicename descriptor ontheupperlefthandcorner of theICVCscreen. SeeFig.25. WhentheCCNdevice hasbeenviewed, theATI'ACH TO NETWORK DEVICE tableshould beused toattach tothePIC thatis onthechillel:MovetotheATFACH TONETWORK DEVICE table(LOCALshould behighlighted) andpress the softkey toupload theLOCALdevice. TheICVC forthe19XRV willbeuploaded anddefault screen willdisplay. NOTE:TheICVCwill notautomatically reattach tothelocal module onthechillel:Press the_ soflkey toattach to theLOCALdevice andviewthechilleroperation. NAME ALWAYS ICVC THE MODULE(" ON THE DESCRIPTOR TABLE ![ 19XRV-_ OTH E R CCN _ MODULES / | ,vrrAc'H-_o_v_c_ NAME r_l_cR1r,_ON _US A_r_R_SS 0 _/ NVICE 8 o o I_VlCE _ 0 0 k._ o_,_a ....... 0 | _ _---.----,_ _ o _,_H_mc-aJ ............ LOCATION _/ OFCCN _/MODULE Fig. 25 -- Example of Attach to Network Device Screen Service SELECT EXIT F--I F--I NOTE: The SERVICE screen password can be changed by entering the ICVC CONFIGURATION screen under SERVICE menu. The password is located at the bottom of the menu. The [CVC screen displays the following SERVICE screens: • • • • • • • • • • • list of available Alarm History Alert History Control Test Control Algorithm Status Equipment Configuration VFD Config Data Equipment Service Time and Date Attach to Network Device Log Out of Device ICVC Configuration See Fig. 18 for additional screens and tables available from softkey to screen and log out of a network device, from the default ICVC Operation -- An overview of the tables and for the SERVICE function is shown in screen, press the _ and [SERVICE] softkeys. Enter the password and, flom the SERVICE menu, highlight LOG OUT screens available Fig. 18. TO ACCESS THE SERVICE SCREENS -- When the SERVICE screens are accessed, a password must be entered. OF NETWORK DEVICE and press the _ The ICVC default screen will now be displayed. 1. From the main MENU screen, press the [SERVICE] soflkey. The soflkeys now correspond to the numerals 1, 2,3,4. 2. PREVIOUS NOTE: To prevent unauthorized pe_.sons D_m accessing the ICVC service screens, the ICVC automatically signs off and password-protects itself if a key has not been pressed for 15 minutes. The sequence is as follows. Filleen minutes after the last key is pressed, the default screen displays, the ICVC screen light goes out (analogous to a screen saver), and the ICVC logs out of the password-protected SERVICE menu. Other screen and menus, such as the STATUS screen can be accessed without the password by pressing the appropriate softkey. TO LOG OUT OF NETWORK DEVICE -- To access this "XI DEvicesi I _ tll_llllllllllll_ NEXT the SERVICE screens listed above. Use the _ return to the main MENU screen. / l_x_ j_ If fl_is occurs, return to Step 1 and try to access the SERVICE screens again. If the password is correct, the softkey labels change to: TIME BROADCAST ENABLE -- The first displayed line, "Time Broadcast Enable", in the SERVICE/EQUIPMENT CONFIGURATION/BRODEF screen, is used to designate the loc_d chiller as the sole time broadcaster on a CCN network (there may only be one). If there is no CCN network present and/or there is no designated time broadcaster on the netwoN, current time and date, Daylight Saving Time (DST), and holidays as configured in the local chiller's control will be applied. If a network is present and one time broadcaster on the network has been enabled, current time and date, DST. and holi&ty schedules as configured in the controls of the designated time broadcaster will be applied to all CCN devices (including chillers) on the network. Press the four digits of the password, one at a time. An asterisk (*) appetus as each digit is entered ENTER A 4 DIGIT PASSWORD:* NOTE: The initial factory-set password is 1-1-1-1. If the password is incorrect, an error message is displayed INVALID softkey. PASSWORD 48 HOLIDAYSCHEDULING (Fig.26)-- Up to 18different holidays canbedefined for special schedule consideration. Thereale two differentscreensto be configured. Filet,in theSERVICE/EQUIPMENT CONFIGURATION/ HOLIDAYS screen, selectthe fil_t unused holidayently (HOLDY01 S,forexmnple). Asshown inFig.26,enteranumberforSt_u-t Month(1=January, 2=February ..... 12=December),anumber forStartDay(1- 31),andDuration indays(099).Bydefault there alenoholidays setup.Second, intheoccupancy Schedule tables, specify andenable (bysetting "X"under the"H"column) runtimeperiod(s) whichwillapplytoallholidays. (Refer toFig.19onpage 21.)A runtimeperiod whichis enabled forholidays maybeapplied tooneormorenon-holiday daysoftheweekaswell.Thismaybedoneforthelocal(table OCCPC01S), Ice Build (OCCPC02S), trod/orCCN (OCCPC03S) schedule(s). If the chiller is on a CCN netwoN, the active holiday definition will be that configured in the device designated at the sole time broadcaster (if one is so enabled). See the TIME BROADCAST ENABLE section. screen, see the SERVICE Press IINCREASEI selected value. 11. Press _ 12. screen, press [SERVICE] Press _ to return to the previous menu. To disable the Daylight Savings Time function 0 minutes for "Start Advance" and "Stop Back". simply enter ITEM DEFINITION Month 1 = January. 2 = February ..... 12 = December. Day of Week 1 = Monday...., 7 = Sunday 1 = first occurrence of selected Day of Week in the selected month, 2 = second occurrence of the selected Day, etc. This is not necessarily what one would conclude from looking at a standard calendar. For example, April 14, 2003, is Day 1 Week 2, but April 15, 2003, is Day 2 Week 3. Week the 2. If not logged on, follow the instructions for Attach to Network Device or To Log Out. Once logged on, press until Equipment Configuration is highlighted. 3. Once Equipment Configuration is highlighted, _to access. Time Time of day in 24-hour format when the time advance or set back will occur. Advance/Back "Advance" occurs first in the year, setting the time ahead by the specified number of minutes on the selected date. "Back" sets the time back by the specified amount (later in the year). press 4. Press _ until HOLIDAYS is highlighted. This is the Holiday Definition table. 5. Press _ to enter the Data Table Select screen. This screen lists 18 holiday tables. 6. Press _ to highlight the holiday table that is to be viewed or changed. Each table is one holiday period, stm-tingon a specific date, and lasting up to 99 days. 7. Press _ to access the holiday table. The Configuration Select table now shows the holiday start month and day. and how many days the holiday period will last. Fig. 26 -- Example of Holiday Period Screen 8. Pless _ or [PREVIOUS] to highlight tfie month, day, or duration. 9. Press _ the DAYLIGHT SAVING TIME CONFIGURATION -- The BRODEF table also defines Daylight Saving Time (DST) changes. This feature is by default enabled, and the settings should be reviewed and adjusted if desired. The following line-item entries ;ue configurable for both DST "Stall" and "Stop", and they are defined in Table 8. menu to access to change to save the changes. To view or change the holiday periods for up to 18 different holidays, perform the following operation: 1. At the Menu Service menu. or IDECREASEI Table 8 -- Daylight Saving Time Values The broadcast function must be activated for the holidays configured on the HOLIDEF screen to work properly. Access the BRODEF screen fi_)m the EQUIPMENT CONFIGURATION table and select ENABLE to activate function. Note that when the chiller is connected to a CCN Network, only one chiller or CCN device c_m be configured as the broadcast device. The controller that is configured as the broadcaster is the device responsible for transmitting holiday, time, and daylight-savings dates throughout the network. To access the BRODEF structure, Fig. 18. 10. to modify the month, day, or duration. 49 START-UP/SHUTDOWN/ RECYCLE SEQUENCE (Fig. 27) Local Start-Up -- screen, press the _ L_cal start-up (ora manual start-up) is initiated by pressing the _ menu softkey on the default CONTACT ICVC scleen. Ix_c_d start-up can proceed when the chiller schedule indicates that the CURRENT TIME and CURRENT DATE have been established CONTACTS as a mn time and date, and after screens. Both timel_ must expire before the chiller will stall. If the timers have not expired, the RUN STATUS pm'ameter on the MAINSTAT screen will read TIMEOUT. If the OCCUPIED ? pm'ameter on the MAINSTAT screen is set to NO, the chiller can be forced to stm't as follows. From softkey to override the schedule MAINSTAT screen and press the [RELEASE] softkey. This action returns the chiller to the stmt and stop times established by the schedule. default screen, press the _ and [SCHEDULE] softkeys. Scroll down and select the current schedule. Select OVERRIDE, and set the desiled override time. QUANTITY REMOTE ] softkey. 9 -- Prestart Checks REQUIREMENT ALERT STATE IF FALSE STARTS IN 12 HOURS < 8 (not counting recycle restarts or auto restarts after power failure) ALERT is cleared once RESET is pressed. 100 COMP THRUST BRG TEMP < [COMP THRUST BRG ALERT] -10 ° F (5.6 ° C) 101 COMP MOTOR WINDING TEMP < [COMP MOTOR TEMP OVERRIDE] -10 ° F (5.6 ° C) < [COMP DISCHARGE ALERT] -10 ° F (5.6 ° C) 102 COMP DISCHARGE CHECKED select Ftfilure to verily any of the requirements up to this point will result in the PIC III aborting the stall and displaying the applicable pre-start mode of failure on the ICVC default screen. A pre-start failure does not advance the STARTS IN 12 HOURS countel: Any failure after the VFD has energized results in a safety shutdown, advances the starts in 12 hours counter by one, and displays the applicable shutdown status on the [CVC display. The minimum time to complete the entire prestart sequence is approximately 185 seconds. Another condition for st;ut-up must be met for chillers that have the REMOTE CONTACTS OPTION on the EQUIPMENT SERVICE screen set to ENABLE. For these chillers, the REMOTE START CONTACT parameter on the MAINSTAT screen must be CLOSED. From the ICVC default Table INPUT and press the [RELEASE Compressor ontime and service ontime timers start, and the complessor STARTS IN 12 HOURS counter and the number of stalls over a 12-hour period counter advance by one. The chiller may also be stmted by overriding the time schedthe override, If the water/brine temperature is high enough, the st;u't-up sequence continues and checks the guide vane position. If the guide vanes are more than 4% open, the stall-up is delayed until the PIC IIl closes the vanes. If the vanes are closed and the oil pump pressure is less than 4 psi (28 kPa), the oil pump relay energizes. The PIC [II then waits until the oil pressure (OIL PRESS VERIFY TIME, operator-configured, default of 40 seconds) leaches a maximum of 18 psi (124 kPa). After oil pressure is verified, the PIC III waits 40 seconds, and the VFD energizes to start the compressol: Press the and start the chiflel: released, regardless of the progrmnmed schedule. To release the forced start, highlight CHILLER START/STOP fiom the From softkey. Then, press the the NOTE: 19XRV units are not available with factou-installed chilled water or condenser water flow devices (available as an accesso U for use with the CCM Control board). and NOTE: The chiller will continue to run until this forced start is ule. To end Scroll to softkey. Scroll REMOTE START Five seconds latel', the CONDENSER WATER PUMP relay energizes. Thirty seconds later the PIC III monitors the chilled water trod condenser water flow devices and waits until the WATER FLOW VERIFY TIME (operator-configured, default 5 minutes) expires to confirm flow. After flow is verified, the chilled water temperature is compmed to CONTROL POINT plus/_ CHILLED WATER DEADBAND. If the temperature is less than or equal to this value, the PIC III turns off the CONDENSER WATER PUMP relay and goes into a RECYCLE mode. NOTE: The time schedule is said to be "occupied" if the OCCUPIED ? pmameter on the MAINSTAT scleen is set to YES. For more information on occupancy schedules, see the sections on Time Schedule Operation (page 21), Occupancy Schedule (page 36), and To Prevent Accidental Stall-Up (page 67), and Fig. 19. softkeys. Scroll to highlight MAINSTAT. Pless the softkey. Scroll to highlight CHILLER START/STOP. softkeys. Once local start-up begins, the PIC III performs a series of pre-start tests to verify that all pre-start alefls and safeties are within the limits shown in Table 7. The RUN STATUS parameter on the MAINSTAT screen line now reads PRESTART. If a test is not successful, the start-up is delayed or aborted. If the tests are successful, the CHILLED WATER PUMP relay energizes, and the RUN STATUS line now reads STARTUR See Table 9. of the motol: The value of these timers is displayed as START INHIBIT TIMER and can be viewed on the MAINSTAT and the default [CVC screen, press the _ and press the _ softkey. the internal timers have expired. The timers include a 15-minute start-to-start timer and a l-minute stop-to-start timel. which together serve to prevent excessive cycling and abuse DEFAULT and _ highlight MAINSTAT and press the _ down the MAINSTAT screen to highlight EVAPORATOR TEMP REFRIG TEMP < [EVAP REFRIG TRIPPOINT] + [REFRIG OVERRIDE 103 DELTA T] 104 OIL SUMP TEMP < 150 ° F (65.5 ° C) or <[EVAP REFRIG TEMP] + 50 ° F (10 ° C) 105 CONDENSER < CONDENSER PRESSURE < 145 psi (1000 kPa) 106 PRESSURE OVERRIDE -20 PSI (138 kPa) and PERCENT LINE VOLTAGE < [UNDERVOLTAGE PERCENT LINE VOLTAGE > [OVERVOLTAGE THRESHOLD] Must have been calibrated ACTUAL GUIDE VANE POS THRESHOLD] 5O 107 108 109 • MACHINE SAFETIES, EVAPORATOR PUMP CONDENSER WATER PUMP WATER FLOW, CHILLED WATER TEMP, GUIDE VANES OIL PUMP,TOWER FAN CONTROL • OIL PRESSURE COMPRESSOR, COMPRESSOR ONTIME, SERVICE ONTIME 3OM_RESSC tUNNIN 15-MINUTE START*TO-START Automatic I 1-MINUTE STOP-TO-START ODE Pre-start F ! checks are made; G evaporator -- START INITIATED: started, B -- Condenser pump C -- Water flows verified (30 seconds to 5 minutes maximum after B). Chilled water temperatures checked against control point, Guide vanes checked for closure, Oil pump started; tower fan control enabled. D -- Oil pressure after C). E -- Compressor motor starts; compressor ontime and service ontime start, 15-minute inhibit timer starts (10 seconds after D), total compressor starts advances by one, and the number of starts over a 12-hour period advances by one. • water pump started (5 seconds after A), minimum, • • • 300 seconds maximum F -- SHUTDOWN INITIATED -- Compressor motor stops; compressor ontime and service ontime stop, and 1-minute inhibit timer starts. G -- Oil pump and evaporator pumps deenergized (60 seconds after F). Condenser pump and tower fan control may continue to operate if condenser pressure is high. Evaporator pump may continue if in RECYCLE mode. O/A-- To activate the soft stop amps threshold feature, scroll to the bottom of OPTIONS screen on the [CVC. Use the [INCREASE] or [DECREASE[ softkey to set the SOFT STOP AMPS THRESHOLD parmneter to the percent of amps at which the motor will shut down. The default setting is 100% alnps (no soft stop). The range is 40 to 100%. When the soft stop amps threshold feature is being applied, a status message, "SHUTDOWN IN PROGRESS, COMPRESSOR UNLOADING" displays on the ICVC. Sequence The soft stop amps threshold function can be terminated and the compressor motor deenergized immediately by depressing the STOP button twice. Shutdown Sequence--Chiller shutdown begins if any of the following occurs: • the STOP button is pressed for at least one second (the alarm light blinks once to confirm the stop command) • a recycle condition is present (see Chilled W_tter Recycle Mode section) • the time schedule has gone into unoccupied mode • the chiller protective limit has been reached and chiller is in alarm • the start/stop status is overridden to stop from the CCN network or the [CVC Chilled • that occur during shutdown Water Recycle Mode-- The chiller may cycle off and wait until the load increases to restart when the compressor is running in a lightly loaded condition. This cycling is norlnal and is known as "recycle." A recycle shutdown is initiated when any of the following conditions are true: • When a stop signfd occurs, the shutdown sequence first stops the compressor by deactivating the VFD output to the motor A status message of "SHUTDOWN IN PROGRESS, COMPRESSOR DEENERGIZED" is displayed, and the comptessor ontime and service ontime stop. The guide vanes are then brought to the closed position. The oil pump relay and the chilled water/brine pump telay shut down 60 seconds after the compressor stops. The condenser water pump shuts down at the same time if the ENTERING CONDENSER WATER temperature is greater than or equal to 115 F (46.1 C) find the CONDENSER REFRIG TEMP is greater titan the CONDENSER FREEZE POINT plus 5 F (-15.0 C). The stop-to-statl timer now begins to count down. If the statl-to-stmt timer value is still greater than the value of the start-to-stop timet: then this time displays on the ICVC. Certain conditions this sequence. AVERAGE LINE CURRENT (%) drops below the SOFT STOP AMPS THRESHOLD ACTUAL GUIDE VANE POSITION drops below 4% 4 minutes have elapsed the STOP button is pressed twice If file chiller enters an alarm state or if the compressor enters a RECYCLE mode, the compressor deenergizes immediately. Restart permitted (both inhibit timers expired: minimum of 15 minutes after E; minimum of 1 minute after F). Fig. 27 -- Control -- The soft Any time the compressor is directed to STOP (except in the cases of a fault or recycle shutdown), the guide vanes ate directed to close, and the compressor shuts off when any of the following is true: O/A A verified (15 seconds Soft Stop Amps Threshold stop fillips threshold feature closes the guide vanes of the compressor automaticfflly if a non-recycle, non-alarm stop signal occurs before the compressor motor is deenergized. II *'TIME The condenser pump shuts down when the CONDENSER PRESSURE is less than the COND PRESS OVERRIDE threshold minus 3.5 psi (24.1 kPa) and the CONDENSER REFRIG TEMP is less than or equal to the ENTERING CONDENSER WATER temperature plus 3° F (-1.6° C). If the chiller shuts down due to low refl'igerant temperature, the chilled water pump continues to run until the LEAVING (/HILLED WATER temperature is greater than the CONTROL POINTtemperature, plus 5° F (2.8 ° C). • • LEA1/ING CHILLED WATER temperature (or ENTERING CHILLED WATER temperature, if the ECW CONTROL OPTION is enabled) is more than 5 ° F (2.8 ° C) below the CONTROL POINT. LEAI/ING CHILLED WATER temperature (or ENTERING CHILLED WATER temperature, if the ECW CONTROL OPTION is enabled) is below the CONTROL POINT. and the chilled water temperature difference is less than the (RECYCLE CONTROL) SHUTDOWN DELTA T (configured in the EQUIPMENT SERVICE/ SETUPI table). the LEA1/ING (/HILLED WATER temperature is within 3 ° F (1.7 ° C) of the EI/AP REFRIG TRIPPOINT. NOTE: Recycle shutdown will not occur if the CONTROL POINT has been modified (e.g., by a chilled water reset input) within the previous 5 minutes of operation. Also, chilled water recycle logic does not apply to Ice Build operation (refer to page 46). When the chiller is in RECYCLE mode, the chilled water pump relay remains energized so the chilled water temperatute can be monitored for increasing load. The recycle control uses RESTART DELTA T to check when the compressor should be restarted. This is an opettltor-configured function which defaults to 5 ° F (2.8 ° C). This value can be viewed or modified can change [f the AVERAGE LINE CURRENT is greater than 5% alter shutdown, the oil pump and chilled water pump remain energized and the alarm is displayed. 51 ontheSETUPItable.Thecompressor will restart whenthe chilleris: • in LCW CONTROLandthe LEAVING (7HILLED • WATER temperature is greater than the POINT plus the (RECYCLE CONTROL) DELTA T. in ECW CONTROL and the ENTERING WATER temperature is greater than the POINT plus the (RECYCLE CONTROL) DELTA T. Once these conditions am met, the compressor st_ut-up with a normal start-up sequence. _'SAE PLUG_ _"SAE FLARENUT CHILLED CONTROL RESTART THERMC 8" initiates (203 mm) a An alert condition may be generated if 5 or more recycle stmt-ups occur in less than 4 hom.s. Excessive recycling can reduce chiller life; therefore, compressor recycling due to extremely low loads should be reduced. SIGHT DISTI WATER OR METHYL ALCOHOL To reduce compressor recycling, use the time schedule to shut file chiller down dunng known low load operation period, or incmase the chiller load by running the fan systems. If the hot gas bypass is installed, adjust the values to ensum that hot gas is energized during light load conditions. Increase the (RECYCLE CONTROL) RESTART DELTA T on the SETUPI table to lengthen the time between restmts. Fig. 28 -- Typical Wet-Bulb Type Vacuum Indicator The chiller should not be operated below design minimum load without a hot gas bypass installed. Open Oil Circuit Valves -- Check to ensure the oil filter isolation valves (Fig. 4) am open by removing the valve cap and checking the valve stem. Safety Shutdown- A safety shutdown is identic_d to a manual shutdown with the exception that, during a safety shutdown, the ICVC displays the mason for the shutdown, the alarm light blinks continuously, and the spare alarm contacts am energized. Oil Charge -- The oil chmge for the 19XRV compmssor depends on the compressor Frame size: • • • • After a safety shutdown, the _ soflkey must be pressed to clem the ahum. If the ahum condition is still present, the _dmln light continues to blink. Once file ;tlarm is clemed, file operator must press the _ or_ softkeys to restart the chillel: BEFORE INITIAL • • • • • START-UP list of applicable design temperatums and pressures (product data submittal) chiller certified prints starting equipment details and wiring diagrams diagrams and instructions for special controls or options pumpout unit instructions Equipment • • • • • Required mechanic's tools (refrigeration) including T30 torx True RMS digital multimeter with clamp-on current probe or True RMS digital clamp-on meter rated for at least 480 vac or 650 vdc electronic leak detector absolute pressure manometer or wet-bulb vacuum indicator (Fig. 28) 500-v insulation tester (megohmmeter) for compressor motors with nameplate voltage of 600 v or less, or a 5000-v insulation tester for compressor motor rated above 600 v Using the Optional Storage Frame Frame Frame Frame 12 gal Frame 2 compressor-3 compressor-4 compressor-4 compressor (,45 L) 5 compressor-- 8 8 10 with gal (30 L) gal (30 L) gal (37.8 L) split ring diffuser option -- 18 gal (67.8 L) The chiller is shipped with oil in the compressor When the sump is full, the oil level should be no higher than the middle of the upper sight glass, and minimum level is the bottom of the lower sight glass (Fig. 2). [f oil is added, it must meet C_urier's specification for centrilhgal compressor use as described in the Oil Specification section. Charge the oil through the oil charging valve located near the bottom of the transmission housing (Fig. 2). The oil must be pumped from the oil container through file charging valve due to higher refrigerant pressure. The pumping device must be able to lift from 0 to 200 psig (0 to 1380 kPa) or above unit pressure. Oil should only be charged or removed when the chiller is shut down. Job Data Required • I_- CONTROL RESTART Tighten All Gasketed Joints and Guide Vane Shaft Packing -- Gaskets ;rod packing normally relax by the time the chiller rerives at the jobsite. Tighten all gasketed joints and the guide vane shaft packing to ensum a leak-tight chillel: Gasketed joints (excluding O-rings) may include joints at some or all of the following: • Waterbox covers • Compressor suction elbow flanges (at compressor and at the cooler) • Compressor discharge flange • Compressor discharge line spacer (both sides) if no isolation valve • Cooler inlet line spacer (both sides) if no isolation valve • Hot gas bypass valve (both sides of valve) • Hot gas bypass flange at compressor Tank and Pump- out System -- Refer to Chillers with Storage Tanks section, page 71 for pumpout system prepmation, refngerant transfeL and chiller evacuation. Remove Shipping Packaging -- Remove any packaging material from the control centeL power panel, guide vane actuatoL motor cooling and oil reclaim solenoids, motor and bearing temperatum sensor covers, and the VFD. Refer to Table 10 for bolt torque requimments. 52 Table 10SAE BOLT SIZE (in.) LOW Bolt Torque Requirements, 2, A307 GR A HEX HEAD NO MARKS CARBON STEEL Foot Pounds SAE 5, SA449 SOCKET HEAD OR HEX WITH 3 RADIAL LINES MEDIUM CARBON STEEL Minimum SAE 8, SAE354 GR BD HEX HEAD WITH 6 RADIAL LINES MEDIUM CARBON STEEL Minimum Maximum 1_ 4 6 6 Maximum 9 Minimum 9 Maximum 13 _16 8 11 13 18 20 28 46 318 13 19 22 31 32 _16 21 30 35 50 53 75 l& 32 45 53 75 80 115 _16 46 65 75 110 115 168 5/8 68 95 105 150 160 225 314 105 150 175 250 260 370 718 140 200 265 380 415 590 1 210 300 410 580 625 893 1 l& 330 475 545 780 985 1,410 11/4 460 660 770 1,100 1,380 1,960 13/8 620 885 1,020 1,460 1,840 2,630 1 l& 740 1060 1,220 1,750 2,200 3,150 1 s/8 101 O 1450 1,670 2,390 3,020 4,31 O 1_4 1320 1890 2,180 3,110 3,930 5,610 17/8 1630 2340 2,930 4,190 5,280 7,550 2 1900 2720 3,150 4,500 5,670 8,100 2114 2180 3120 4,550 6,500 8,200 11,710 216 3070 4380 5,000 7,140 11,350 16,210 2_4 5120 7320 8,460 12,090 15,710 22,440 3 6620 9460 11,040 15,770 19,900 28,440 Check Chiller Tightness-proper sequence and procedures Figure 29 for leak testing. outlines tile transferred. Adjust the springs when the refrigerant ing condition and the water circuits are full. The 19XRV chillers me shipped with the refrigerant contained in the condenser shell and the oil charge in the compressor. The cooler is shipped with a 15 psig (103 kPa) refrigerant charge. Units may be ordered with the refiigemnt shipped separately, along with a 15 psig (103 kPa) nitrogenholding chmge in each vessel. is in operat- Refrigerant Tracer -- C_urier recommends the use of an environment_dly acceptable refrigerant tracer for leak testing with an electronic detector or halide torch. Ultrasonic leak detectors under pressure. To determine if there are any leaks, the chiller should be chmged with refrigerant. Use an electronic leak detector to check all flanges and solder joints after the chiller is pressurized. If any leaks me detected, follow the leak test procedure. can also be used if the chiller is Do not use air or oxygen as a means of pressurizing the chillel: Mixtures of HFC-134a and air can undergo combustion. If the chiller is spring isolated, keep all springs blocked in both directions to prevent possible piping stress and dmnage during the transfer of refrigerant from vessel to vessel during the leak test process, or any time refrigerant is being 53 LEAK TEST OF 19XRV 1, ATTACH COMPOUND GAGE TO EACH VESSEL 2. NOTE AMBLENT TEN_IPERATURE GAGE READINGS I MACHINES WITH REFRIGERANT 4, I MAGHNESW,THN,TROGEN ROLD,NGDHARGE I CHARGE 1 4, PRESSURE ON CONDENSER VESSEL IS LESS THAN SA/URA_ED REFRIGERAN F PRESSURE (SEE REFRIGERANT PRESSURETEMPERATURE TABLES 11A AND 1113) PRESSURE ON CONDENSERVESBELtS AT REFRIGERANT SATURATED COND!TIONS SEE REFRIGERANT PRESSURE*TEMPERATURETABLES 1AAND 1E _AK COOLER PRESSURE READING IS BELOW 15 PRIG (103 kP_,t) COOLER PRESSURE READING S 15 PSIG (103 kPej OR HIGHER 4, PRESSURE READING IS LESS THAN 15 PSIG (103 kPei BUr GREATER THAN 0 PSIG (0 kPa) SUSPEC PRBSSURE IS AT 15 PRIG (103 kP_,) (FACTORY CHARGE) ED LEAK SUSPECTED 1, I EVACUATE HOLDING CHARGE RELEASE FROMNITROGEN VESSELS AND REDORDRRESSURES I POWER UP CONTROLS TO ENSURE OIL HEATER IS ON AND OIL IS HOT, EQUAUZE PRESSURE BE,,_,:_4EEN COOLER AND CONDENSER I (IF USING ELECTRONIC DETECTOR, L ADD TRACER GAS NOW) r'_ 1 BERPORM_.EA_TEST I POWER UP CONTROLS TO ENSURE OIL HEATER IS ON AND OIL I9 HOT, EQUALIZE PRESSURE BETWEEN COOLER AND CONDENSER ½ I 4_ [ FIoAK[_ :;I- l I USING SOAP BUBBLE SOLU]ION_ ULTRASONICS ELECTRONIC PERFORMORLEAK TEST DETECTOR { PBRFORMLEAK,SS," 1 FOUND 1 EVACUATB ] AND MARK ALL LEAK SOURCES AND MARK ilcco , STANDING ALL LEAK [ SOURCES LODATEJ ,1i: IN THE VESSEL REPAIR ALL LEAKS RETEST ONLY THO_E JOtNTS RELEASE THE REPAIRED PRESSURE THAT WERE REPAIR DEHYDRATE VESSEL IF VESSEL WAS I CONTINUE I WITH MACHINE STARTUP / .I COMPLETE CHARGING Fig. 29 -- 19XRV Leak Test Procedures MACHINE IIC I 1 BERFORMLEA_TEST I I UNTIL PRESSURE iS ABOVE ADD REFRIGERANT 35 PSIG (241kP_) I UNTIL PRESSURE S ABOVE 30 PSIG (241kPa) ADD REFRIGERANT / _,>,,'ss I [ I Leak Test Chiller -- Due to regulations regarding refiigerant emissions and the difficulties associated with separating contaminants from the refrigerant, Carrier recommends the following leak test procedure. See Fig. 29 for an outline of the leak test procedure. Refer to Fig. 30 and 31 during pumpout procedures and Tables 11A and 11B for refi'igerant pressure/ temperature values. 1. [f the pressure condition: readings the holding are normal charge for the 5. chiller a. Evacuate present. fiom the vessels, b. Raise the chiller pressure, if necessary, by adding refrigerant until pressure is at the equivalent saturated pressure for the surrounding temperature. Follow the pumpout procedures in the Transfer Refrigerant from Pumpout Storage Tank to Chiller section, Steps I a - e, page 72. 6. a. Prepare to leak test chillers ant (Step 2h). b. c. Check for large leaks by connecting a nitrogen bottle and raising the pressure to 30 psig (207 kPa). Soap test all joints. If the test pressure holds for 30 minutes, prepare the test for small leaks (Steps 2g-h). Plainly mark any leaks that are found. d. Release e. Repair all leaks. f. Retest the joints g. After successfully completing the test for large leaks, remove as much nitrogen, air. and moisture as possible, given the fact that small leaks may be present in the system. This can be accomplished by following the dehydration procedure, outlined in the Chiller Dehydration section, page 58. h. 3. 4. the pressure a. Transfer the refrigerant to the pumpout tank and perform a standing vacuum outlined in the Standing Vacuum Test below. b. If the chiller fails the standing for large leaks (Step 2b). c. If the chiller passes the standing vacuum test, dehydrate the chiller. Follow the procedure in the Chiller Dehydration section. Charge the chiller with refrigerant (see Transfer Refrigerant fiom Pumpout Storage Tank to Chiller section, page 72). with refriger- vacuum storage test as section, test, check 7. If a leak is found after a retest, pump the refrigerant back into the pumpout storage tank or, if isolation valves are present, pump the refrigerant into the non-leaking vessel (see Pumpout and Refrigerant Transfer procedures section). 8. Transfer the refrigerant until the chiller pressure is at 18 in. Hg (40 kPa absolute). Repair the leak and repeat the procedure, beginning from Step 2h, to ensure a leak-tight repail: (If the chiller is opened to the atmosphere for an extended period, evacuate it before repeating the leak test.) 9. c. Leak test chiller as outlined in Steps 3-9. If the pressure readings are abnormal for the chiller condition: shipped If no leak is found after a retest: if Never charge liquid refrigerant into the chiller if the pressure in the chiller is less than 35 psig (241 kPa) for HFC-134a. Charge as a gas only, with the cooler and condenser pumps running, until this pressure is reached, using PUMPDOWN LOCKOUT and TERMINATE LOCKOUT mode on the PIC III. Flashing of liquid lefrigerant at low pressures can cause tube freeze-up and considerable damage. 2. be repaired. Note the toted chiller leak rate on the start-up _eport. If no leak is found during the initi_d start-up procedures, complete the transfer of refrigerant gas from the pumpout storage tank to the chiller (see Transfer Refiigerant from Pumpout Storage Tank to Chiller section, page 72). Retest for leaks. Standing Vacuum Test -- When perforlning the standing vacuum test or chiller dehydi'ation, use a manometer or a wet bulb indicatol: Dial gages cannot indicate the small amount of acceptable leakage during a short period of time. 1. Attach an absolute pressure indicator to the chillel: 3. Valve off the pump to hold the vacuum manometer or indicator reading. 4. a. If the leakage rate is less than 0.05 in. Hg (0.17 kPa) in 24 hours, the chiller is sufficiently tight. b. 55 bulb Evacuate the vessel (see Pumpout and Refrigerant Transfer Procedures section, page 71 ) to at least 18 in. Hg vac, ref 30-in. bar (41 kPa), using a vacuum pump or the pump out unit. that were repaired. Check the chiller carefully with an electronic leak detectol: halide torch, or soap bubble solution. Leak Determination --If an electronic leak detector indicates a leak, use a soap bubble solution, if possible, to confirm. Total all leak rates for the entire chillel: Leakage at rates greater than 0.1% of the total charge per year must or wet 2. in the system. Slowly raise the system pressure to a maximum of 160 psig (1103 kPa) but no less than 35 psig (241 kPa) for HFC-134a by adding refrigerant. Proceed with the test for small leaks (Steps 3-9). manometer and record the ffthe leakage rate exceeds 0.05 in. Hg (0.17 kPa) in 24 hours, repressurize the vessel and test for leaks. If refrigerant is available in the other vessel, pressurize by following Steps 2-10 of Return Chiller To Normal Operating Conditions section, page 73. If not, use nitrogen and a refi'igerant tracer Raise the vessel plessure in increments until the leak is detected. If refrigerant is used, the maximum gas pressure is approximately 70 psig (483 kPa) for HFC-134a at normal ambient temperature. If nitrogen is used, limit the leak test pressure to 160 psig (1103 kPa) maximum. _) Fig. 30 -- Typical Optional Pumpout System Piping Schematic STORAGE TANK VAPOR VALVE with Storage Tank REFRIGERANT CHARGING VALVE REFRIGERANT ISOLATION VALVE REFRIGERANT CHARGING PRESSURE RELIEF SAFETY LIQUID LIVE SERVICE VALVE ........ :: VALVE VALVE_ OIL ....._ PUMPOUT = SERVICE PUMPOUTVALVE UNIT ON 1_= SERVICE VALVE ON CHILLER _SEPARATOR _ _.//**./_*f COMPRESSOR _] ___ i ....... CONDENSER ".... -_ q I PUMPOUT PUMPOUT WATER SUPPLY CONDENSER AND RETURN Fig. 31 -- Typical Optional Pumpout System Piping Schematic without Storage Tank 56 Table 11AHFC-134a PressureTemperature (F) TEMPERATURE, F 0 2 4 6 8 Table 11B -- HFC-134a PressureTemperature (C) PRESSURE (psig) 6.60 7.52 8.60 9.66 10.79 TEMPERATURE, C -18.0 -16.7 -15.6 -14.4 -13.3 PRESSURE (kPa) 44.8 51.9 59.3 66.6 74.4 10 12 14 16 18 11.96 13.17 14.42 15.72 17.06 -12.2 -11.1 -10.0 -8.9 -7.8 82.5 90.8 99.4 106.0 118.0 20 22 24 26 28 18.45 19.88 21.37 22.90 24.46 -6.7 -5.6 -4.4 -3.3 -2.2 127.0 137.0 147.0 158.0 169.0 30 32 34 36 38 26.11 27.80 29.53 31.32 33.17 -1.1 0.0 1.1 2.2 3.3 180.0 192.0 204.0 216.0 229.0 40 42 44 46 48 50 52 54 56 58 35.08 37.04 39.06 41.14 43.26 45.46 47.74 50.07 52.47 54.93 4.4 5.0 5.6 6.1 6.7 7.2 7.8 8.3 8.9 9.4 242.0 248.0 255.0 261.0 269.0 276.0 284.0 290.0 298.0 305.0 60 62 64 66 68 57.46 60.06 62.73 65.47 68.29 10.0 11.1 12.2 13.3 14.4 314.0 329.0 345.0 362.0 379.0 70 72 74 76 78 80 82 84 86 88 71.18 74.14 77.18 80.30 83.49 66.17 90.13 93.57 97.09 100.70 15.6 16.7 17.8 18.9 20.0 21.1 22.2 23.3 24.4 25.6 396.0 414.0 433.0 451.0 471.0 491.0 511.0 532.0 554.0 576.0 90 92 94 96 98 104.40 108.18 112.06 116.02 120.08 26.7 27.8 28.9 30.0 31.1 598.0 621.0 645.0 669.0 694.0 100 102 104 106 108 124.23 128.47 132.81 137.25 141.79 32.2 33.3 34.4 35.6 36.7 720.0 746.0 773.0 800.0 826.0 110 112 114 116 118 146.43 151.17 156.01 160.96 166.01 37.8 38.9 40.0 41.1 42.2 657.0 886.0 916.0 946.0 978.0 120 122 124 126 128 171.17 176.45 181.83 187.32 192.93 43.3 44.4 45.6 46.7 47.8 1010.0 1042.0 1076.0 1110.0 1145.0 130 132 134 136 138 140 198.66 204.50 210.47 216.55 222.76 229.09 48.9 50.0 51.1 52.2 53.3 1180.0 1217.0 1254.0 1292.0 1330.0 54.4 55.6 56.7 57.8 58.9 60.0 1370.0 1410.0 1451.0 1493.0 1536.0 1580.0 5? Chiller Dehydration the chiller the chiller complete has been is known -- Dehy&'ation is recommended open for a considerable period to contain moisture, or if there loss of chiller holding chmge if of time, if has been a or refrigerant pressure. _...,. FROM TO VACUUM IIL:--;:L4 PUMP S¥STEM-' I _A_l_'n Im_ _I_I_E_ENS_ES_ ON COLD SURFACES Do not start o1 megohm-test the compressor motor or oil pump motor, even for a rotation check, if tile chiller is under dehydration vacuum. Insulation breakdown and severe &tmage may result. -.4IP- _]1 _ _ MIXTURE OF DRYICEAND METHYL ALCOHOL Fig. 32 -- Dehydration Cold Trap Dehydiation can be done at room temperatures. Using a cold trap (Fig. 32) may substanti_dly reduce the time required to complete the dehydration. The higher the room temperature, the faster dehydration takes place. At low room temperatures, a very deep vacuum is required to boil off any moisture. If low ambient temperatures am involved, contact representative for the dehydration techniques Perform 1. dehydiation a qualified required. vacuum as possible pressure manometer or a wet bulb to measure the vacuum. Open the vacuum indicator only when taking a valve open for 3 minutes to allow the to equalize witi1 the chiller With the chiller ambient temperature at 60 F (15.6 C) or highel: operate tile vacuum pump until the manometer roads 29.8 in. Hg vac, mf 30 in. bin: (0.1 psia) (-100.61 kPa) or a vacuum indicator roads 35 F (1.7 C). the pump is to be dehydiated, an additional open condenser water has been piped in. Check for field-supplied shutoff valves and controls as specified in the job data. Check for refrigerant leaks on field-inst_dled piping. See Fig. 30 and 31. all isolation Check Relief Valves -- Be sure the relief valves have been piped to the outdoors in compliance with tile latest edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections must allow for access to the v_tive mechanism for periodic inspection and leak testing. 2 hours. Do not apply a greater vacuum than 29.82 in. Hg vac (757.4 mm Hg) or go below 33 F (.56 C) on the wet bulb vacuum indicatol: At this temperature and pressure, The 19XRV relief valves are set to relieve at the 185 psig (1275 kPa) chiller design pressure. isolated pockets of moisture can turn into ice. The slow rate of evaporation (sublimation) of ice at these low temperatures and plessums greatly increases dehydi'ation time. off tile vacuum the instrument 6. After 7. pump, stop the pump, and record instrument reading. wait, take another has not changed, indicates vacuum dehydi'ation loss, repeat Inspect the VFD -- Tile LiquiFlo TM 2.0 AC di'ive is a PWM (Pulse Width Modulated), liquid-cooled drive that provides vector and general purpose regulation for a wide range of applications. Identify the drive from the Drive Pall Number on the drive's nameplate (Fig. 33) and the model number matrix in (Fig. 34). If The control center is designed environmental conditions: is complete. If Steps 4 and 5. If tile reading continues to change after several perform a leak test up to the maximum (1103 kPa) pressure. Ix)cate and lepair the repeat Identify reading. a 2-hour the reading the reading CONDITION attempts, 160 psig leak, and dehydration. Water Piping specifications have been to operate in the following SPECIFICATION Ambient Temperature (outside NEMA 1 enclosure) 32 to 122 F (0 ° to 50 C) Storage Temperature (ambient) -40 to 149 F (-40 to 65 C) -- Refer to piping diagrams provided in the certified di'awings. [nspect the piping to the cooler and condense1: Be sum that the flow directions am conect and that all piping the Check Optional Pumpout Compressor Water PipingIf the optkmal pumpout storage tank and/or pmnpout system _u'e installed, check to ensure the pmnpout vacuum. 4. Valve Measure Water must be within design limits, clean, and treated to ensure proper chiller perfommnce and to reduce the potential of tube &tmage due to corrosion, scaling, or erosion. Carrier assumes no responsibility for chiller damage resulting from unUeated or improperly treated watel: to If the entire chiller v_tives (if present). 5. vented with no stress on flows through the cooler service 3. Operate must be properly and covel.s. Water as follows: Use an absolute vacuum indicator shutoff valve to the reading. Leave the indicator systems nozzles and condenser must meet job requirements. pressure drop across tile cooler and the condenser Connect a high capacity vacuum pump (5 cfin [.002 m:Vsl or Ireget is lecommended) to the refiigemnt chmging v_dve (Fig. 2). Tubing from the pump to the chiller should be as short in length and as large in diameter provide least resistance to gas flow. 2. Piping waterbox Humidity 5% to 95% (non-condensing) This section describes how to identify tile drive using the model number matrix and shows the major drive components. met. 58 Input Power Wiring -- All wiring should be installed in conformance with applicable local, national, and international codes. Use grommets, when hubs are not provided, to guard against wire chafing. Use the following steps to connect main input circuit breaker: 12=ncm@[j n_ ID NO.: AC input power to the 18O7(X)-X)(X-XXX 1. Turn off. lockout, and tag the input power to the diive. Input Rating: XXXVAC X)O(A 50/60Hz 3PH Oulput Rating: 0-48OVAC X)O(A 0-400Hz 3PH Short Circuit Rating: XXXXXX 2. Remove the input wiring panel and drill the required number of openings in the top of the drive enclosure. Take care that metal chips do not enter the enclosure. 3. Wire the AC input power leads by routing them through the openings to the main input circuit breakel: Interrupt Capacity Ragng: )OOOO¢,X Max. Ambient Temperature: 50°C Enclosure Type: TYPE 1 Coolant Type: _ Design Pressure: X)O( X)O(X Carder Part Number: 19XRA2X)O(XX VFD Sedal Number. XXXXXX_OO( Carrier Dwg. Number: 19XV04004501 Mfd. In XX)O(on XJoc)O( Do not route control wiring carrying 30 v or less within a conduit carrying 50 v or highel: Failure to observe this precaution could result in electromagnetic interference in the control wiring. Made In USA for Carder Colporagon, Syracuse. NY 13221-4808. Fig. 33 -- VFD Nameplate LF20 0608CC 4. Connect the three-phase AC input power leads (per job specification) to the appropriate input terminals of the circuit breaker 5. Tighten the AC input power terminals to the proper torque as specified on the input circuit breakel: R LF20 = LiquiFIo 2.0 Checking the Installation -- Use Continuous Ampere Rating and Frame Size structions to verify the condition in- 1. Turn off. lockout, and tag the input power to the diive. Coolant Method R = refrigerant the following of the instalhttion: R134a 2. Wait a minimum of 5 minutes for the DC bus to dischtuge. Fig. 34 -- Identifying the Drive Model Number 3. All wiring should be installed in conformance with the applicable local, national, and international codes (e.g., NEC/CEC). IDENTIFYING THE DRIVE BY PART NUMBER -- Each AC drive can be identified by its assembly number. See Fig. 33. This number appears on the shipping label and on the drive's nameplate. LiquiFlo TM 2.0 AC power module can be identified by its model number See Fig. 34. This number appears on the shipping htbel and on the power module's nameplate. Power ratings are provided in Table 12. 4. Remove any debris, enclosure. 5. Check that machine. 6. Verify that the wiring to the terminal strip and the power terminals is coned. 7. Verify that all of the VFD power module circuit bo_ud connectors are fully engaged and taped in phtce. 8. Check that the wire size is within terminal and that the wiles me tightened properly. 9. Check that specified and conectly rated. BE AWARE that certtfin automatic start arrangements can engage the startel: Open the disconnect ahead of the starter in addition to shutting off the chiller or pump. Failure to do so could result in serious personal inju U or death from electric shock. 10. PARTNUMBER 12 -- Drive Assembly FRAME SIZE 19XVA2AA 2AA 19XVA2CC 2CC *110% outputcurrentcapabilityforl is adequate cle_u'ance around the specifications branch circuit protection Check that the incoming nameplate voltage. from the is installed power is within _+10% of chiller 11. Verify that a properly sized ground wile is installed and a suitable emlh ground is used. Check for and eliminate any grounds between the power leads. Verify that all ground leads are unbroken. The mtfin disconnect on the starter fiont panel may not deenergize all internal circuits. Open all internal and lemote disconnects before servicing the st_uter Failure to do so could lesult in serious peLson_d injmy or death from electric shock. Table there such as metal shavings, and Power Module ENCLOSURE RATING NEMA1 minute. 150% outputcurrentcapability _r5sec. 59 Ratings NOMINAL INPUT VOLTAGE (V) 380 TO 460 INPUT CURRENT (AMPS) 440 608 OUTPUT CURRENT AT 4 kHz* (AMPS) 460 608 Inspect Wiring Ground Fault Troubleshooting -- Follow this procedure only if ground faults are declared by tile chiller controls. Test the chiller compressor motor and its power lead insulation resistance with a 500-v insukition tester such as a megohlnmetec Do not check the voltage supply without proper equipment and precautions. Sedous personal injury may result. Follow power company recommen&ttions. a. 1. Examine the wiring for conformance to the job wiring diagrmns and all applicable electrical codes. Compare the ampere rating on the VFD enclosure nmneplate to the rating on the compressor nameplate. OVERLOAD TRIP AMPS must be 108% of the MOTOR RATED LOAD AMPS. 4. The control center must be wired to components and terminals required for PIC III refrigeration control. Check line side power and for control components shown on the Cellified Prints. The control center must share control of cooler and condenser liquid pumps and cooling tower fans. 5. 6. b. Connect a voltmeter across the power wires to the VFD and measure the phase to phase and phase to ground voltage. Compare this reading to the voltage rating on the compressor and st_uter nameplates. 3. Ensure all electrical equipment and controls are properly grounded in accordance with the job di'awings, certified drawings, and all applicable electrical codes. 8. Ensure the customer's contractor has ation of the pumps, cooling tower auxiliary equipment. This includes properly lubricated and have proper proper rotation. 9. Tighten _dl wiring connections on the high and low voltage termimd blocks in the control center enclosure below the control panel. 10. Inspect the control panel in file control center enclosure to ensure that the contractor has used the knockouts to feed the wires into the back of the control panel. Wiring into the top of the panel can cause debris to fall into the control centel: Clean and inspect the interior of the control center if this has occurred. With the tester connected to the motor leads, take 10-second and 60-second megohm readings as follows: Tie terminals 1, 2, and 3 together the group and ground. c. and test between Divide the 60-second resistance reading by the 10-second reading. The ratio, or polarization index, must be one or higher. Both the 10 and 60-second readings must be at least 50 megohms. If the readings are unsatisfactory, repeat the test at the motor with the power leads disconnected. Satisfactory readings in this second test indicate the fault is in the power leads. Carrier Comfort Network Interface -- Tile C_urier Colnfol-t Network (CCN) connnunication bus wiring is supplied and inst_dled by the electrical contractol: It consists of shielded, 3-conductor cable with di'ain wire. Check the phase to phase and phase to ground line voltage to the control center and the optional pumpout compressoc Compare voltages against nameplate values. Ensure that fused disconnects or circuit breakers have been supplied to the control center and optional pumpout unit. 7. switch and follow The motor leads must be disconnected from the VFD before an insulation test is performed. The voltage generated from the tester can damage the starter solid-state components in the VFD. Do not apply any kind of test voltage, even for a rotation check, if the chiller is under a dehydration vacuum. Insulation breakdown and serious &image may result. 2. Open the starter main disconnect lockout/tagout rules. The system elements are connected to the communication bus in a daisy chgdn m'rangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it. Tile negative pins must be wired to the negative pins. The signal ground pins must be wired to file signal ground pins. See installation manual. NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned coppel: Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -4 F to 140 F (-9-0 C to 60 C) is required. See table below for cables flint meet the requirements. verified proper operfans, and associated ensuring motors are electric_d supply and MANUFACTURER CABLE NO. Alpha American Belden Columbia 2413 or 5463 A22503 8772 02525 When connecting tile CCN communication bus to a system element, a color code system for the entire network is recommended to simplify installation and checkout. The following color code is recommended: Do not apply power unless a qualified Carrier technician is present. Serious personal injuU may result. 11. Apply power to the control center. Go to the ICVC and access the MENU>SERVICE>VFD CONFIG DATA>VFD_CONF screen. Confirm that the parameters entered in VFD_CONF match the information on the Machine Nameplate and Sales Requisition. Confirm that the serial numbers on the chiller, Machine Nameplate, and Sales Requisition are consistent. SIGNAL TYPE + Ground 6O CCN BUS CONDUCTOR INSULATION COLOR CCN TERMINAL CONNECTION ICVC PLUG J1 PIN NO. Red White Black RED (+) WHITE (G) BLACK (-) 1 2 3 Power Up the Controls and Check the Oil Heater -- Ensure that an oil level is visible in the compres- date, and day of the week. The HOLIDAY parameter should only be configured to YES if the present &ty is a holiday. NOTE: Because a schedule is integral to the chiller control sequence, the chiller will not start until the time and &tte have been set. sor before energizing the controls. A circuit bleaker in the starter energizes the oil heater and the control circuit. When first powered, the ICVC should display the default screen within a short period of time. NOTE: The date format is MM-DD-YY DD-MM-YY format for SI metric units. Tile oil heater is energized by powering the control circuit. This should be done several hours before sta-t-up to minimize oil-refiigerant migration. The oil heater is controlled by the PIC Ill and is poweled through a contactor in the power panel. A separate circuit breaker powers the heater and the control circuit. This ammgement allows the heater to energize when the main motor circuit breaker is off for service work or extended shutdowns. Tile oil heater relax/status (OIL HEATER RELAY) can be viewed on the COMPRI_SS table on the ICVC. Oil sump temperature can be viewed on the ICVC default screen. CHANGE ICVC CONFIGURATION IF NECESSARY -From the SERVICE table, access the ICVC CONFIGURATION screen. From there, view or modify the ICVC CCN address, change to English or SI units, and change the password. If fllere is more than one chiller at the jobsite, change the ICVC addiess on each chiller so that each chiller has its own address. Note and record the new addiess. Change the screen to SI units as required, and change the password if desiled. TO CHANGE THE PASSWORD -- The password changed from the ICVC CONFIGURATION screen. SOFTWARE VERSIONThe software part number is labeled on the backside of the [CVC module, The software velMon also appears on the ICVC configuration screen as the last two digits of the software part numbel: Software 1. Press the _ current password Do not operate the chiller befole the control configuraions have been checked and a Control Test has been satisfactorily completed. Protection by safety controls cannot be assumed until all control configurations have been confirmed. and [SERVICE] softkeys. Enter the and highlight ICVC CONFIGURA- 2. Use file _ softkey to scroll to PASSWORD. The first digit of file password is highlighted on the screen. 3. To change [DECREASE] As the 19XRV unit is configured, all configuration settings should be written down. A log, such as the one shown on pages CL-I to CL-I 2, provides a list for configuration values. press the _ Input the Design Set Points -- Access the ICVC set point screen and view/modify the BASE DEMAND LIMIT set point, and either the LCW SETPOINT or the ECW SETPOINT. The PIC III can control a set point to either the leaving or entering chilled water This control method is set in the EQUIPMENT SERVICE (TEMP_CTL) table. For more information about how to set up a time schedule, see the Controls section, page 11. is the IINCREASE] or softkey. 4. The next digit is highlighted. Change it, and the third and fourth digits in the same way the lil.st was changed. 5. After the last digit is changed, the ICVC goes to file BUS to leave 1. Press the _ and [SERVICE] softkeys. Enter the password and highlight ICVC CONFIGURATION. Press Input Service Configurations -- Ti_e following configurations require the ICVC scleen to be in the SERVICE tion of the menu. press When the desired digit is seen, TO CHANGE THE ICVC DISPLAY FROM ENGLISH TO METRIC UNITS --By default, the ICVC displays information in English units. To change to metric units, access the ICVC CONFIGURATION scleen: The CCN Occupied Schedule (OCCPC03S) should be configured if a CCN system is being installed or if a secon&try time schedule is needed. OCCPC03S digit, soflkey. Be sure to remember the password. Retain a copy for future reference. Without the password, access to the SERVICE menu will not be possible unless the ICVC PSWD menu on the STATUS screen is accessed by a Carrier representative. Access the schedule OCCPC01S screen on the ICVC and set up the occupied time schedule according to the customer's requirements. If no schedule is available, the default is factory set for 24 hours occupied, 7 days per week including holi&tys. Schedule the NUMBER pmametel: Press the _ softkey that screen and leturn to the SERVICE menu. Input the Local Occupied Schedule (OCCPC01S) -- • • • • • • may be TION. Press the _ softkey. Only the last 5 entries on the ICVC CONFIG screen c_m be changed: BUS NUMBER, ADDRESS, BAUD RATE, US IMP/ METRIC, and PASSWORD. Configuration NOTE: The default CCN Occupied configmed to be unoccupied. for English units and the _ por- password input time and date ICVC configuration service parameters equipment configuration automated control test softkey. 2. Use file _ softkey to scroll to US IMP/METRIC. 3. Press the softkey flint conesponds to file units desired for display on the ICVC (e.g., US or METRIC). CHANGE LANGUAGE--By default, the ICVC displays information in English. To change to another Language, access the ICVC CONFIGURATION screen: 1. Press the _ and [SERVICE[ softkeys. Enter the password and highlight ICVC CONFIGURATION. Press PASSWORD -- When accessing the SERVICE tables, a password must be entered. All ICVC are initially set for a password of 1- 1- 1- 1 in the ICVC CONFIGURATION SCREEN. the _ INPUT TIME AND DATE -- Access the TIME AND DATE table on the SERVICE menu. Input the present time of chy, 2. 61 Use the _ softkey. softkey to scroll to LID LANGUAGE. 3. Press theINCREASE or DECREASE softkey untilthe desired language isdisplayed. Press _ toconfirm desired language. MODIFYCONTROLLER IDENTIFICATION IF NECESSARY-- TheICVCmodule ADDRESS can be changed from Carrier Mmq uB MACHINE $_FI.Y DATA MACH_ ELEC_ICAL DATA u_ the ICVC CONFIGURATION screen. Change this adc_hess for each chiller if there is more than one chiller at the jobsite. Write the new adc_hess on the [CVC module for future reference. INPUT EQUIPMENT SERVICE ESSARYiThe EQUIPMENT service tables. NAMEPLATE M_ r_Cl_CUsT _R_A_ER _ZE I MACHINEELECINCAL DATA _*o_ N_M PLAXE VO AG_ 10AD SIDE PARAMETERS IF NECSERVICE table has six VERIFY VFD CONFIGURATION AND PARAMETERS IF NECESSARY (Fig. 35) SIDE CHANGE IMPORTANT: The VFD controller has been factory configured for use and communications to the International Chiller Visual Controller (ICVC). Some parmneters ;ue specific to the chiller configuration and will need to be verified prior to operation. All command functions must be initiated from the [CVC. VFD CHILLER FIELD SET UP AND VERIFICATION sA,,,, Label Ix_cations -- Verify the following labels have been installed properly and match the chiller requisition: • Surge Parameters -- Located inside the control panel (see Fig. 9). • Refrigeration Machine Nameplate -- Located on the right side of the control panel (see Fig. 9). • External Machine Electrical Data Nameplate -- Ix_cated on the right side of the VFD as viewed from its front. (See Fig. 35). • Internal Machine Electrical Data Nameplate -- Ix_cated on the inside of the left VFD enclosure door. (See Fig. 35). • Record all nameplate information on the Initial Start-up Checklist at the end of this manual. • • Check VFD CONFIG TABLE -- Enter screen on the [CVC by entering the sequence when the chiller is not running: • MENU • SERVICE • Password (default 1111) • VFD CONFIG DATA • Password (default 4444) • VFD_CONF NOTE: Some of the parameters drive is stopped. • • • • • • • • Electrical Data Namoplato Motor Nameplate kW i Motor nameplate rated power: Inverter PWM Frequency -- Sets the carrier frequency for the pulse width modulation output. NOTE: Other pm'ameters on these screens me normally left at the default settings; however, they may be changed by the operator as _equired. The voltage and current imbalance level and imbalance persistence time on the VFD_CONF table can be adjusted to increase or decrease the sensitivity of these fault conditions. Increasing time or pe_.sistence decreases sensitivity. Decreasing time or persistence increases sensitivity to the fault condition. the VFD_CONF following screen Confirm that the following parameters VFD_CONF screen match the values on the Machine Electrical Data Nameplate: EXTERNAL INTERNAL Fig. 35 -- Machino COOEce_I,I_,,o, can be changed only when the It is the operator's responsibility to distribute access to the ICVC passwords. Carrier is not responsible for unauthorized access violations within the operator's organization. Failure to observe this warning could result in bodily injury. in the Internal Compressor 100% Speed -- Compressor speed required to run at chiller design point. Rated Line Voltage -- Nominal line voltage selected for the job site. Rated Line Amps -- Line current required for the chiller to run at the design point. Rated Line Kilowatts -- Line power required for the chiller to run at the design point. Motor Rated Load kW -- Power consumed by the motor when running at the chiller design point. Motor Rated Load Amps -- Motor current required for the chiller to run at the design point. Motor Nameplate Amps -- Motor nameplate full load amps. Motor Nameplate RPM -- Rated speed of the motor when running at motor nameplate rated frequency, rated current, and rated voltage. See the Initial Start-Up Checklist section for VFD Job Specific Configuration table. For job specific pm'ameters see the Machine Electrical Data Nameplate (Fig. 35) inside of the VFD enclosure door Modify Minimum and Maximum Load Points (ATI/PI: AT2/ P2) If-NecessaLy -- These pairs of chiller load points, located on the OPTIONS screen, determine when to limit guide vane travel or open the hot gas bypass valve when surge prevention is needed. These points should be set based on individual chiller operating conditions. SET SURGE LIMIT/HGBP OPTION to 0 if the chiller is not equipped with an optional hot gas bypass. Set SURGE LIMIT/HGBP OPTION to 1 if a hot gas bypass has been installed. 62 A labelthatliststheconfiguration v_dues ofthecontrols is located ontheinside oftheunit'scontrolpanel. These v_dues arebased upontheoriginalselection ofthechillel:Jobsite conditions mayrequire aslightmodification tothese parameters. If afterconfiguring avalueforthese points, surge preventionis operating toosoonor toolatefor conditions, these parameters should bechanged byfileoperatol: Anexmnple ofsuchaconfiguration isshown below. Refrigerant: HCFC134a Estimated Minimum Load Conditions: 44 F (6.7 C) LCW 45.5 F (7.5 C) ECW 43 F (6.1 C) Suction Temperature 70 F (21.1 C) Condensing Temperature Estimated Maaimum Load Conditions: Compressors wifll vmiable diflhser control have actuators tested and stamped with the milliamp (mA) value that results in 100% actuator rotation. This v¢flue is configured on the SETUP2 screen. It is labeled DIFFUSER FULL SPAN mA. MODIFY EQUIPMENT CONFIGURATION IF NECESSARY -- The EQUIPMENT SERVICE table has screens to select, view, or modify parameters. Career's certified drawings have the configuration values required for the jobsite. Modify fllese values only if requested. EQUIPMENT SERVICE Screen Modifications -- Change the values on these screens according to specific job data. See file certified drawings for the correct values. Modifications can include: • Chilled water reset (CHW SETPT RESET VALUE) • Entering chilled water control (ECW CONTROL OPTION) • 4 to 20 mA demand limit (DEMAND LIMIT AT 20 mA) • AUTO RESTART OPTION (Enable/Disable) • REMOTE CONTACT OPTION (Enable/Disable) 120 - 37 = 83 psid (827 - 255 = 572 kPad) add about 10 psid AT2 = 10 ° F (5.5 ° C) AP2 = 93 psid (642 kPad) Calculate Minimum Load -- To calculate the minimum load conditions, estimate the temperature difference the cooler will have at 10% load, then estimate what the suction and condensing temperatures will be at this point. Use the proper saturated pressure and temperature for the particular refrigerant used. Owner-Modified CCN Tables -- The following EQUIPMENT CONFIGURATION screens me described for reference only. OCCDEFCSThe OCCDEFCS screen contains the Ix_cal trod CCN time schedules, which can be modified here or on the SCHEDULE screen as described previously. Suction Temperature: 43 F (6.1 C) = 38 psig (262 kPa) saturated refrigerant pressure (HFC- 134a) HOLIDAYS -- From file HOLIDAYS screen, file days of the year that holidays are in effect can be configured. See the holiday paragraphs in the Controls section for more details. BRODEF The BRODEF screen defines the start trod end of &tylight savings time. By default this feature is enabled. Enter file (kites for the start and end of daylight savings if required for your location. Note that for Day of Week, 1 represents Monday. Start Week and Stop Week refer to the instance of the selected Day of Week during the selected month and yem: To disable the feature, change "Stml Advance" and "Stop Back" times to 0 (minutes). In the BRODEF table the user may also identify a chiller as the time broadcaster for a CCN netwoN. There should be only one device on a CCN network which is designated as the Time Broadcastel: ALARM ROUTING--This is in the table SERVICE-> EQUIPMENT CONFIGURATION->NET OPT under the heading Alarm Configuration. Alarm Routing consists of tin 8-bit binary number Only bits 1, 2, and 4 (counting from the left, first) are used. (The others do not mattel:) The bits can be set by tiny device which can access and change configuration Condensing Temperature: 70 F (21.1 C) = 71 psig (490 kPa) saturated refrigerant pressure (HFC-134a) Minimum Load ATI (at 20% Load): 2 F (1.1 C) Minimum Load API : 71 - 38 = 33 psid (490 - 262 = 228 kPad) Again, to avoid unnecesstuy surge prevention, (140 kPad) at API from these conditions: ATI = 2F(I.I C) API = 53 psid (368 kPad) If surge prevention LOAD At low loads (<50%) At high loads (>50%) add 20 psid occurs too soon or too late: SURGE PREVENTION OCCURS TOO SOON SURGE PREVENTION OCCURS TOO LATE Increase Pl by 2 psid (14 kPad) Increase P2 by 2 psid (14 kPad) Decrease P1 by 2 psid (14 kPad) Decrease P2 by 2 psid (14 kPad) Further adjustments can be made if response to surge prevention or protection is not functioning as desired. VFD GAIN and I/FD INCREASE STEP can be adjusted to allow for more agglessive changes in speed when surge prevention or protection is active. CONFIGURE DIFFUSER CONTROL IF NECESSARYIf the compressor is equipped with a variable diflhser, (size 4 or 5 complessor) access the SETUP2 screen. Scroll to DIFFUSER CONTROL and press the IENABLE] softkey. Compare the diflhser and guide vane values (GUIDE VANE 25% LOAD PT, GUIDE VANE 50% LOAD PT, GUIDE VANE 75% LOAD PT, DIFFUSER 25% LOAD POINT, DIFFUSER 50% LOAD POINT, DIFFUSER 7.5% LOAD POINT) to the values located on the label inside the control panel above the ICVC. See Fig. 9. 44 F (6.7 C) LCW 54 F (12.2 C) ECW 42 F (5.6 C) Suction Temperature 98 F (36.7 C) Condensing Temperature Calculate Maximum Load -- To calculate the maximum load points, use file design load condition <a. If the chiller full load cooler temperature difference is more than 15 F (8.3 C), estimate the refrigerant suction and condensing temperatures at this difference. Use file proper saturated pressure and temperature for the pmticular refrigerant used. Suction Temperature: 42 F (5.6 C) = 37 psig (255 kPa) saturated refrigerant pressure (HFC- 134a) Condensing Temperature: 98 F (36.7 C) = 120 psig (1827 kPa) saturated refrigerant pressure (HFC- 134a) Maximum Load AT2: 54 - 44 = 10 ° F (12.2 - 6.7 = 5.5 ° C) Maximum Load AP2: To avoid unnecessmy surge prevention, (70 kPad) to AP2 from these conditions: The differential pressure (AP) and temperature (AT) can be monitored during chiller operation by viewing ACTI1/E DELTA P and ACTIVE DELTA T (HEAT EX screen). Compming SURGE/HGBP DELTA T to ACTIVE DELTA T will determine when the SURGE PREVENTION function will occur The smaller the difference between the SURGE/HGBP DELTA T and the A CTI1/E DELTA T v_flues, the closer to surge prevention. 63 tables. If anyofthese 3 bitsis setto1,thecontroller (ICVC, forexample) willbroadcast any;darms whichoccm: • first bit = 1 indicates thatthealarmshouldberead and processed by a "front end" device,suchas • • Table 13 -- Control Test Menu Functions TESTS TO BE PERFORMED ComfortWORKS®. second bit = 1 indicates that the alarm should be read and processed by a TeLINK TM or Autodial Gateway module. fourth bit = 1 indicates that the alarm should be read and processed by an alarm printer interface (an optional module), ServiceLink TM, or a DataLINK TM modules. 1. CCM Thermistors Entering Chilled Water Leaving Chilled Water Entering Condenser Water Leaving Condenser Water Evap Saturation Temp Comp Discharge Temp Comp Thrust Brg Temp Oil Sump Temp Comp Motor Winding Temp Spare Temperature 1 Spare Temperature 2 Remote Reset Sensor 2. CCM Pressure Transducers Evaporator Pressure Condenser Pressure Oil Pump Delta P Chilled Water Delta Condenser Water Delta P Transducer Voltage Ref Humidity Sensor Input Relative Humidity 3. Pumps Oil Pump -- Confirm Pressure Chilled Water -- Confirm Flow and Delta P Condenser Water -- Confirm Delta P 4. Discrete Outputs Oil Heater Relay Hot Gas Bypass Relay Tower Fan Relay Low Tower Fan Relay High VFD Coolant Solenoid Alarm Relay Shunt Trip Relay 5. IGV & SRD Actuator Open/Close If present, split ring diffuser will operate in coordination with the guide vanes per configured schedule. 6. Head Pressure Output 7. Diffuser Actuator* Increase/Decrease 8. Pumpdown Lockout When using pumpdown/Iockout, observe freeze up precautions when removing charge: Instructs operator which valves to close and when. Starts chilled water and condenser water pumps and requests flow confirmation. Monitors Evaporator pressure Condenser pressure Evaporator temperature during pumpout procedures Turns pumps off after pumpdown. Locks out compressor. 9. Terminate Lockout Starts pumps and monitors flows. Instructs operator which valves to open and when. Monitors Evaporator pressure Condenser pressure Evaporator temperature during charging process Terminates compressor lockout. 10. Guide Vane Calibration Automatic, displays guide vane position signal voltage. This test is required before first startup with new Actuator or Controller. The Re-Alarm time is a time period after which, if a preexisting and previously broadcast ;darm has not been cleared, it will be rebroadcast on the CCN network. Other _ibles -- The TIME screens contain See the applicable CCN screens. These tables Building Supervisol: CONSUME, NET_OPT. and RUNparameters used with a CCN system. manual for more information on these can only be defined from a CCN ALARM CONTROL ALARM ROUTING This decision determines which CCN system elements will receive and process alarms sent by the CSM. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a digit to 1 specifies that alarms will be sent to the system element that corresponds to that digit. Setting all digits to 0 disables alarm processing. Digits in this decision correspond to CCN system elements in the following manner: Alarm Printer Autodail Interface Module 1 / Gateway Local Building Supervisors(s) or ComfortWORKS _ I I 1 1 0 1 I 0 I 0 I I 0 I 0 l unused NOTE: If your CCN does not contain ComfortWORKS® controls or a Building Supervisor, Autodial Gateway, or APIM to serve as an alarm acknowledger, set all digits in this decision to 0 in order to prevent unnecessary activity on the CCN Communication Bus. Allowable Entries 00000000 to 11111111 0 = Disabled, 1 = Enabled Default Value 11010000 Fig. 36 -- Alarm Control and Alarm Routing Perform a Control Test -- Check the safety controls status by performing an CONTROL TEST table function (Table 13). automated and select control a test test. Access the to be performed The Automated Control Test checks all outputs and inputs for lunction. In order to successfully proceed with the controls test, the compressor should be off. no aimms showing, and voltage should be within _+10% of Nmneplate value. The complessot can be put in OFF mode by pressing the STOP push button on the [CVC. Each test asks the operator to confirm the operation is occurring and whether or not to continue. If an error occurs, the operator can try to addless the problem as the test is being done or note the problem and proceed to the next test. NOTE: Enter guide vane c;dibration actuator feedback potentiometer input terminals 9 and 10). DEVICES TESTED Open/Close 4-20 mA output (independent of guide vanes) *Diffuser tests function only on size 4 and 5 compressor control enabled. to calibrate guide vane on CCM (Plug J4 upper with diffuser NOTE: During any of the tests, an out-of-range reading will have an asterisk (*) next to the reading and a message will be displayed if diffuser control is enabled. NOTE: [f during the control test the guide vanes do not open, the low pressure ;dmm is not active. (An active low plessure ;dmm causes the guide vanes to close.) verify NOTE: The oil pump test will not cooler pressure is below -5 psig (-35 energize kPa). the oil pump When the control test is finished or the _ sollkey is pressed, the test stops, and the CONTROL TEST menu displays. If a specific automated test procedure is not completed, access the particular control test to test the limction when ready. The CONTROL TEST menu is described in Table 13. if 64 PRESSURE TRANSDUCER CALIBRATION -- Transducers measuring singlepressure values (suchascondenser andevaporator pressure) arecalibrated individually, whilea pairof transducers measuring a pressure differential (OIL/ PUMPDELTAR CONDENSER WATERDELTAR CHILLED WATER DELTAP)tuecalibrated together asadifferential. Inunitswith[CVCcontrollers, transducel.'s forsensingwatersideflowarenotprovided asstan&ud. These reading canbe viewedandcalibrated fromtheCOMPRESS and HEAT_EX screens ontheICVCcontrollel: Eachtransducer ortransducer paircanbec_flibrated attwo points: zero(0psigor0kPa)and"highend"(between 25and 250psig,or between 173and1724kPa).It is notusually necess_uy to calibrate at initialstart-up. Howevel, at high altitude locations, recalibration maybenecessary toensure the proper refrigerant temperature-pressure relationship. ZERO POINT CALIBRATION -- Shut down the compressor. and cooler and condenser pumps. There must be no water flow through the heat exchangers, but these systems must be tilled. For differential pairs, leave the transducers installed. For single vMue transducers, disconnect the transducer's electrical cable, remove the sensor from its Schmder fitting, then reconnect the cable. NOTE: If the cooler or condenser vessels tue at 0 psig (0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for the zero point without removal. Access the HEAT_EX or COMPRESS screen under the STATUS menu, and view the particular transducer reading. (OIL PUMP DELTA P is in the COMPRESS screen; all others are in HEAT_EX.)If the displayed reading is not 0 psi (0 kPa), press the SELECT key to highlight the associated line in the display, then the ENTER key. (For zero point c_dibration, the INCREASE and DECREASE keys have no effect.) The v_flue should change to 0.0. value can be changed value. to tiny value within _+15% of a nominal NOTE: Prior calibrations may have shilled the present pre-c_flibration value from the center of this range. In this case, the limit of acceptable new values will be less than 15% in one direction. If the [CVC fails to accept the high end calibration, the value will not change and the display will show "Higher Force In Effect". This indicates that the sensor voltage is out of the acceptable range for the entered value. If this occm.s with a differential pail: one possible remedy is to swap the high end (inlet) and low end (outlet) transducers. In most cases this puts the sensor voltage within the acceptable range. Each transducer is supplied with 5 vdc power from the CCM. Pressure transducer readings are derived from voltage ratio, not absolute voltage, which compensates for any reference voltage variation. If this power supply fails, a transducer voltage reference _darm is generated. If transducer readings are suspected of being faulty, check the supply voltage, measured between the high and low (that and third) terminals of tiny transducer 3 terminal connection at the CCM. This is _dso displayed in CONTROL TEST under CCM PRESSURE TRANSDUCERS. Check Optional Pumpout System Controls and Compressor -- Controls include an on/off switch, a 0.5-amp fuse, the compressor overloads, an internal thermostat, a compressor contactor, refrigerant low pressure cut-out and a refrigerant high pressure cutout. The high pressure cutout is factory set to open at 185 psig (1276 kPa) and reset at 140 psig (965 kPa). The low pressure cutout is factory set to open at 7 psia (-15.7 in. HG) and close at 9 psia (-11.6 in. HG). Ensure the water-cooled condenser has been connected. Ensure oil is visible in the compressor sight glass. Add oil if necesstuy. See the Pumpout and Refrigerant Transfer Procedures and Optional Pumpout System Maintenance sections, pages 71 and 78, for details on the transfer of refrigerant, oil specifications, etc. If the [CVC fails to accept the zero point calibration, the value will not change to 0.0 and the display will show "Higher Force In Effect". This indicates that the sensor voltage is out of the acceptable range. For each single value transducer there are 3 terminals at the CCM: 0 vdc (low), "sensor" voltage, and 5.00 vdc (high). With a base supply voltage of 5.00 volts, the acceptable range of voltage taken between the low and sensor terminals for zero point c_flibration is 0.40 to 0.55 v. For each transducer differential pair there are two 3-terminal sets at the CCM. With a base supply voltage of 5.00 volts, the acceptable range of voltage t_&en between the sensor terminal for the high end transducer (water inlet or oil pump discharge) and the sensor terminal for the low end transducer (water outlet or oil sump) for zero point calibration is -0.065 to +0.085 v. If this occurs with a differential pail: one possible remedy is to swap the high end (e.g., inlet) and low end (e.g., outlet) transducers. In most cases this puts the sensor voltage within the acceptable range. HIGH END CALIBRATION -- High end calibration can be performed between 25 and 250 psig (173 and 1724 kPa), comptu'ing the pressure readings in the ICVC display to an accurate refrigeration gage. While it normally will have a negligible effect, it may improve transducer accuracy over the full pressure range. High end c¢flibration is not recommended for transducer differential pairs. Pressure can be provided by attaching a regulated 250 psig (1724 kPa) pressure source, such as from a nitrogen cylindel: to the transducel: High Altitude Locations -- Because the chiller is initi;dly calibrated at sea level, it is necess;uy to rec;dibrate the pressure transducers if the chiller has been moved to a high ;altitude location. See the c;dibration procedure in the Troubleshooting Guide section. Charge Refrigerant into Chiller The transfel: addition, or removal of refrigerant in isolated chillers may place severe stress on external if springs have not been blocked in both up and directions. Failure to block springs in both up and directions could result in severe personal injury and ment damage. spring piping down down equip- Always operate the condenser and chilled water pumps during charging operations to prevent freeze-ups. Damage could result to equipment if condenser and chilled water pumps ;ue not operated during pumpdown or charging. Access the HEAT EX screen under the STATUS menu, and the CONDENSER PRESSURE or EVAPORATOR PRESSURE to the reference pressure gage. To change the displayed reading, press the SELECT key to highlight the associated line in the display, then the INCREASE or DECREASE key to set the new value, then the ENTER key. Generally, the The standard 19XRV chiller is shipped with the refrigerant _flready charged in the vessels. Howevel: the 19XRV chiller may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Ewlcuate the nitrogen from the entire chillel: and charge the chiller from refl'igerant cylinders. 65 CHILLEREQUALIZATION WITHOUTA PUMPOUT UNIT The full refrigerant chmge on the 19XRV will vary with chiller components and design conditions, as indicated on the job data specifications. An approximate chtuge may be determined by adding the condenser charge to the cooler chmge as listed in Table 14. Whenequ_flizing refrigerant pressure onthe19XRV chiller afterservice workorduringtheinitialchillerstall-up, do not use the dischalig, e isolation valve to equali',.e. Eiflier the motor cooling isolation valve or a charging hose (connected between the refrigerant charging valves on top of the cooler and condenser) should be used as the equalization valve. Dmnage to the float valve could result. Always operate the condenser and chilled water pumps whenever charging, transferring, or removing refrigerant from the chillel: Ftdlure to do so could result in serious personal injury or equipment &image. To equalize the pressure differential on a refrigerant isolated 19XRV chillek use the terminate lockout function of the CONTROL TEST on the SERVICE menu. This helps to turn on pumps and advises the operator on proper procedures. Use the CONTROL TEST terminate lockout monitor conditions and start the pumps. 3. 4. IMPORTANT: Turn on the chilled water denser water pumps to prevent freezing. and con-[ I Slowly open the motor cooling isolation valve. The chiller cooler and condenser pressures will gradually equalize. This process takes approximately 15 minutes. TRIMMING REFRIGERANT CHARGE -- The 19XRV unit is shipped with the correct charge for the design duty of the chillel: On most 19XRV chillers the design LTD (Leaving Temperature Difference) between the leaving chilled water temperature and the cooler refrigerant temperature is so low that the traditional method of trimming the charge to achieve a minimum LTD is not practical. In the case where leaks have been found and corrected and the LTD is greater than about 4 ° F (2.2 ° C) above design, add refligemnt until the full load design LTD is approached, and then charge for proper oil return at low load. (A high cooler LTD can also be caused by dirty tubes, water box division plate bypass, a Du-tiafly closed liquid isolation valve, or a sticking float valve.) Once the pressures have equalized, the cooler isolation v_dve, the condenser isolation valve, and the hot gas isolation valve may now be opened. Refer to Fig. 30 and 31, for the location of the valves. Whenever turning reattach the valve from opening or chiller operation, injury. the discharge isolation valve, be sine to locking device. This prevents the valve closing during service work or during which could result in serious pel.sonal If low load oil loss is experienced, operate the chiller at low load with the guide vanes nedy closed and observe the flow through the sight glass in the oil skimmer line. Under low load operation one should be able to see a flow of bubbly oil and refrigerant in the sight glass. If there is no visible flow, add refrigerant. If the sight glass shows a flow of nearly clear fluid, remove refrigerant. CHILLER EQUALIZATION WITH PUMPOUT UNIT -The following steps describe how to equalize refrigerant pressure on an isolated 19XRV chiller using the pumpout unit. 1. Access the terminate lockout function on the CONTROL TEST screen. 2. IMPORTANT: Turn on the chilled water denser water pumps to prevent freezing. and con-] to If the chiller has been shipped with a holding chmge, the refrigerant is added through the pumpout charging connection (Fig. 30 and 31, valve lb). First evacuate the nitrogen holding chmge from file chiller vessels. Charge the refrigerant as a gas until the system pressure exceeds 35 psig (141 kPa) for HFC-134a. Aller the chiller is beyond this pressure the refrigerant should be charged as a liquid until all the recommended refrigerant charge has been added. The charging valve (Fig. 30 and 31, v_flve I a or I b) can be used to charge liquid to the cooler or condenser Do not charge liquid through the liquid line service valve. The following steps describe how to equalize refrigerant pressure in tin isolated 19XRV chiller without a pumpout unit. 1. Access terminate lockout function on the CONTROL TEST screen. 2. function The preferred location at which refrigerant should be added directly into the chiller is through file service valve at the top of the condensel: If that valve is not accessible due to presence of an attached pumpdown unit which does not have a storage tank, add charge through the valve connected to the side of the condenser drain float sump. Adding charge through the di'ain valve at the base of the chiller (off file liquid line) is NOT recommended. I 3. Open valve 4 on the pumpout unit and open valves la and l b on the chiller cooler and condensek Fig. 30 and 31. Slowly open valve 2 on the pumpout unit to equalize the pressure. This process takes approximately 15 minutes. 4. Once the pressures have equalized, the dischmge isolation valve, cooler isolation valve, optional hot gas bypass isolation valve, and the refrigerant isolation valve can be opened. Close valves la and lb, and all pumpout unit valves. Table 14 lists file 19XRV chiller refrigerant charges for each cooler and condenser code. Total refrigerant charge is the sum of the cooler and condenser charge. 66 Table 14COOLER CODE 10 11 12 15 16 17 20 21 22 30 31 32 35 36 37 40 41 42 45 46 47 50 51 52 55 56 57 6O 61 62 65 66 67 7O 71 72 Check Motor Refrigerant (HFC-134a) Charge REFRIGERANT CHARGE Ib 290 310 330 320 340 370 345 385 435 350 420 490 400 480 550 560 630 690 640 720 790 750 840 900 870 940 980 940 980 1020 1020 1060 1090 1220 1340 1440 CONDENSER CODE kg 132 141 150 145 154 168 157 175 197 159 190 222 161 218 250 254 266 313 290 327 358 340 361 408 395 426 445 426 445 463 463 461 494 553 608 653 INITIAL 1. Engage tile control power circuit breaker (CB2) located inside the left hand side of the VFD enclosure. REFRIGERANT CHARGE Ib 200 200 200 250 250 250 225 225 225 260 260 260 310 310 310 260 280 280 330 330 330 400 400 400 490 490 490 420 420 420 510 510 510 780 780 780 10 11 12 15 16 17 20 21 22 30 31 32 35 36 37 40 41 42 45 46 47 50 51 52 55 56 57 60 61 62 65 66 67 70 71 72 kg 91 91 91 113 113 113 102 102 102 118 118 118 141 141 141 127 127 127 150 150 150 161 161 181 222 222 222 190 190 190 231 231 231 354 354 354 -- 3. The VFD checks for proper phase rotation as soon as power is applied to the starter and the PIC III controls power up. The controls do not permit a start if the phase rotation is not correct. 4. An ahum message will appear on the ICVC if the phase rotation is incorrect. If this occurs reverse any 2 of the 3 incoming power leads to the VFD and reapply powel: The motor is now ready for a rotation check. 5. After the default screen status message states 'Ready to Stmt' press the _ softkey. The PIC III control performs start-up checks. 6. When the starter is energized and the motor begins turn, check for clockwise motor rotation (Fig. 37). 2. Cooling tower water is at proper design entering temperature. 3. Chiller is charged with refrigerant and all refi'igerant oil valves are in their proper operating positions. 4. Oil is at the proper level in the reservoir 5. Oil reservoir temperature is above 140 F (60 C) or above refrigerant temperature plus 50 ° F (28 ° C). 6. Vtdves in the evaporator open. are not automatic, on the to and Compressor Stop 2. Press the Stop button and listen for any unusual from the compressor as it coasts to a stop. Accidental Start-Up -- sounds A chiller STOP ovenide setting may be entered to prevent accident_d start-up during service or whenever necessmy. Access the MAINSTAT screen and using the _ or highlight the CHILLER START/STOP level and at-or-below and condenser (CBl) When the motor is at full speed, note the OIL PRESSURE reading on the ICVC default screen. Normal 19XRV oil pressure readings are between 18 and 30 psid (124 to 207 kPad). The oil pressure should be between 18 and 40 psid (124 to 276 kPad) on Frame 3 compressors equipped with rolling element bearings. To Prevent Power is on to the main startel: oil pump relay, tower fan stmter, oil heater relay, and file chiller control panel. disconnect I. START-UP I. [PREVIOUS] softkeys, pammetel: Override the current START value by pressing the _ and softkey. Press file _ softkey followed by the _ softkey. The word SUPVSR! displays on the [CVC indicating the override is in place. sight glasses. To restml water circuits are removed. the chiller the STOP Access the MAINSTAT override setting ensure water is _ -- forces tile chiller ON • _ -- forces tile chiller OFF • ]RELEASE control. ] -- puts the chiller under remote or schedule To the return chiller The default [CVC command is in effect. 67 START/STOP. • to normal control, ]RELEASE] softkey followed by the _ mole information, see Local Start-Up, page 50. Access the CONTROL TEST screen. Scroll down on the TERMINATE LOCKOUT option. Press the SELECT (to enable the chiller to start) and answer YES to reset unit to operating mode. The chiller is locked out at the factory in order to prevent accidental start-up. must be screen and using or ]PREVIOUS] softkeys highlight CHILLER The 3 softkeys that appear represent 3 choices: Do not permit water or brine that is wmmer than 110 F (43 C) to flow through the cooler or condensel: Refrigerant overpressure may discharge through the relief valves and result in the loss of refrigerant charge, damaging the chillel: 7. Finally close the main motor front of the VFD enclosure. Check Oil Pressure Before stmting file chillel; verify: NOTE: If the pumps circulating properly. 2. Do not check motor rotation during coastdown. Rotation may have reversed during equalization of vessel pressures. the VFD is not stmted by a technician who has completed Reliance LiquiFlo TM Tier 1 Training and whose name is IMPORTANT: Reliance VFD wmTanty will be void if legi stered with The Reliance. Preparation Rotation screen message press the softkey. For line indicates which OPERATING Operator INSTRUCTIONS Duties I. Becolne falniliar with the chiller and related equiplnent before operating the cNllel: 2. Prepare the system for start-up, start and stop the chiller. and place the system in a shutdown condition. Maintain a log of operating conditions and document any abnormal readings. CORRECT MOTOR ROTATION IS CLOCKWISE WHEN VIEWED THROUGH MOTOR SIGHT GLASS 3. 4. Inspect the equipment, make routine adjustments, fred perform a Control Test. Maintain the proper oil and refrigerant levels. TO CHECK ROTATION, ENERGIZE COMPRESSOR MOTOR MOMENTARILY. DO NOT LET MACHINE DEVELOP CONDENSER PRESSURE. CHECK ROTATION IMMEDIATELY. 5. Protect the system from &image during shutdown periods. 6. Maintain the set point, time schedules, functions. ALLOWING CONDENSER PRESSURE TO BUILD OR CHECKING ROTATION WHILE MACHINE COASTS DOWN MAY GIVE A FALSE INDICATION DUE TO GAS PRESSURE EQUALIZING THROUGH COMPRESSOR. Fig. 37 -- Correct Motor Prepare Rotation described and other PIC HI the Chiller for Start-Up -- Follow in the Initial Start-Up section, page 67. the steps To Start the Chiller Check Chiller Operating Condition -- Clleck to be sure that chiller temperatures, pressures, water flows, find oil find lefiigemnt levels indicate the system is functioning properly. Instruct the Customer I. Start the water pumps, if they are not automatic. 2. On the ICVC -- Ensure the operator(s) understand all operating and maintenance procedures. Point out the various chiller parts and explain their function as pa-t of file complete system. COOLER-CONDENSER--Float chamber, relief valves, refrigerant charging valve, temperatme sensor locations, pressure transducer locations, Schmder fittings, waterboxes and tubes, and vents find drains. OPTIONAL PUMPOUT STORAGE TANK AND PUMPOUT SYSTEM -- Transfer vfdves find pumpout system, refrigerant charging and pumpdown procedme, find relief devices. press the _ or stfu-t sequence will start. Follow the procedure described in the Start-Up/Shutdown/Recycle Sequence section, page 50. Check the Running System -- After the compressor starts, the operator should monitor the ICVC display find observe the parameters for normal operating conditions: 1. The oil reselaToir temperature (49 C) during shutdown. MOTOR COMPRESSOR ASSEMBLY -- Guide vane actuator: transmission, motor cooling system, oil cooling system, temperature and pressure sensors, oil sight glasses, integral oil pump, isolatable oil Iiltel; extra oil and motor temperature sensol_, synthetic oil, find compressor serviceability. MOTOR COMPRESSOR LUBRICATION SYSTEM -Oil pump, cooler filter, oil heatel: oil charge and specification, operating and shutdown oil level, temperature and pressure, and oil charging connections. CONTROL SYSTEM--CCN and LOCAL start, reset, menu, softkey functions, ICVC operation, occupancy schedule, set points, safety controls, find auxiliay and optiomd controls. sepmate screen, [_ soflkey to start the system. If the chiller is in the OCCUPIED mode find the start timel_ have expired, the Operator AUXILIARY EQUIPMENT-Disconnects, trical sources, pumps, and cooling towel: default CHECK OPERATOR KNOWLEDGE-Stm-t, stop, and shutdown procedures, safety and operating controls, refrigerant and oil charging, and job safety. REVIEW THE START-UP OPERATION, AND MAINTENANCE MANUAL. NOTE: Manufds find notebooks should not be stored under the VFD power module as they will block airflow into the power module cooling fan. Remove the manuals if they were placed under the power module during shipping. 68 be above 120 F 2. The bearing oil temperature accessed on the COMPRESS table should be 120 to 165 F (49 to 74 C) for compressors using journal bemings, and up to 175 F (79 C) for Frame 3 compressors equipped with rolling element bemings. If the bearing temperatme reads more than 180 F (83 C) wifll the oil pump running, stop the chiller and determine the cause of the high temperature. Do not restart the chiller until corrected. 3. The oil level should be visible anywhere in one of the two sight glasses. Foaming oil is acceptable as long as the oil pressure and temperature are within limits. 4. The OIL PRESSURE should be between 18 and 30 psid (124 to 207 kPad) differential, as seen on the ICVC default screen. Typically the reading will be 18 to 25 psid (124 to 172 kPad) at initial start-up. Typical values may be up to 10 psid (69 kPad) higher for Frame 3 compressors equipped with rolling element bearings. 5. The moisture motor cooling dry condition. 6. The condenser pressure and temperature varies with the chiller design conditions. Typically the pressure will range between 60 and 135 psig (390 to 950 kPa) with a corresponding temperature range of 60 to 105 F (15 to 41 C). The condenser entering water temperature should be controlled below the specified design entering water temperature to save on compressor kilowatt requirements. 7. Cooler pressure and temperature also will vary with the design conditions. Typical pressure range will be between 60 and 80 psig (410 and 550 kPa), with temperature ranging between 34 find 45 F (1 and 8 C). elec- DESCRIBE CHILLER CYCLES -- Refi'igerant, motor cooling, lubrication, and oil reclaim. REVIEW MAINTENANCEScheduled, routine, and extended shutdowns, importance of a log sheet, importance of water treatment and tube cleaning, and importance of maintaining a leak-free chiller SAFETY DEVICES AND PROCEDURES -- Electrical disconnects, relief device inspection, and handling refrigerant. should indicator sign glass on the refrigerant line should indicate refrigerant flow and a 8. Thecompressor mayoperate atfull capacity fora short timeafterthepulldown ramping hasended, eventhough thebuilding loadis sm_dl. Theactiveelectric_d demand setting canbeoveMdden tolimitthecompressor [kW.or thepulldown rotecanbedecreased to avoida high demand chaisefor theshortperiodof highdemand operation. Pulldown ratecanbebased onloadrateor temperature rateandis accessed ontheEQUIPMENT SERVICEscreen,RAMPDEM table (N_ble4, Example 21). To Stop the Chiller The occupancy schedule starts and stops the chiller automatically once the time schedule is configured. 2. By pressing the STOP button for one second, the alarm light blinks once to confirm the button has been pressed. The compressor will then follow the normal shutdown in the Shutdown Sequence, Sequence section, page 50. Manual is diagnosed After Limited Shutdown-No speci_d preparations should be necessary. Follow the regular preliminary checks and starting procedures. for Extended Shutdown -- The refrigerant should be transferred into the pumpout storage tank (if supplied; see Pumpout and Refiigermlt Transfer Procedures) to reduce chiller pressure and the possibility of leaks. Maintain a holding ch;uge of 5 to 10 lb (2.27 to 4.5 kg) of refrigerant or nitrogen to prevent air from leaking into the chillel: -- It is possible to NOTE: Manual control mode overrides the configured pulldown ramp rate during st;ut-up and permits the guide vanes to open at a faster rate. The PIC lII controls will close the guide vanes if the motor current exceeds the ACTIVE DEMAND LIMIT or capacity override limits. The guide vanes will _flso close if the chilled water temperature falls below the CONTROL POINT. For descriptions of capacity overrides and set points, see the Controls section. If freezing temperatures ;u'e likely to occur in the chiller area, drain the chilled watel: condenser watel; and the pumpout condenser water circuits to avoid freeze-up. Keep the waterbox drains open. Leave the oil ch;uge in the chiller with the oil heater and controls energized to maintain the minimum oil reservoir temperature. Refrigeration Log- A refrigeration log (as shown in Fig. 38), is a convenient checklist for routine inspection and maintenance and provides a continuous record of chiller performance. It is also an aid when scheduling routine maintenance and diagnosing chiller problems. -- Ensure the water sys- tem drains ;u'e closed. It may be advisable to flush the water circuits to remove any soft rust which may have formed. This is a good time to brash the tubes and inspect the Schrader fittings on the waterside flow devices for fouling, if necessary. Check the cooler pressure on the ICVC default screen compare it to the original holding charge that was left in chillel: [f (after adjusting for ambient temperature changes) loss in pressure is indicated, check for refrigerant leaks. Check Chiller Tightness section, page 53. Guide Vane Operation Similarly. the TARGET VFD SPEED can be manu;dly set in the COMPRESS screen. The target value is still limited to be between configured VFD MINIMUM SPEED and VFD MAXIMUM SPEED. Once speed is manually set in this mannel, capacity control changes are directed to modulate the guide vanes. Preparation Shutdown When the entering con- manually operate the guide vanes in order to check control operation or to control the guide vanes in an emergency. Manu;d operation is possible by overriding the tinget guide vane position. Access the COMPRESS screen on the ICVC and scroll down to highlight TARGET GUIDE VANE POS. To control the position, use the [INCREASE] or [DECREASE] softkey to adjust to the percentage of guide vane opening that is desired. Zero percent is fully closed; 100% is fully open. To release the guide vanes to automatic control, press the [RELEASEJ softkey. l an IMPORTANT: isolating knifeDoswitch. not attempt High to intensity stop thearcing chiller may by opening occm: Do not restart the chiller until the problem and corrected. Operation- denser water temperature drops very low. the operator should automatically cycle the cooling tower fans off to keep the temperature up. Piping may ;dso be arranged to bypass the cooling towel: The PIC llI controls have a low limit tower fan output that can be used to assist in this control (terminals 5 and 6 on the TB2 haz;udous voltage field wiring terminal strip). The chiller will not restmt until the _ or softkey is pressed. The chiller is now in the OFF control mode. After Extended C;uefully make all legular preliminary and running system checks. Perform a Control Test before start-up. If the compressor oil level appears abnormally high, the oil may have absorbed refrigerant. Ensme that the oil temperatme is above 140 F (60 C) or above the cooler refrigerant temperature plus 50 ° F (27 ° C). Cold Weather I. sequence as described Start-Up/Shutdown/Recycle Recharge the chiller by transferring refrigerant from the pumpout storage tank (if supplied). Follow the Pumpout and Refrigerant Transfer Procedures section, page 71. Observe freeze-up precautions. Keep a record of the chiller pressmes, temperatures, and liquid levels on a sheet similar to the one in Fig. 38. Automatic recording of PIC [II data is possible by using CCN devices such as the Data Collection module and a Building Supervisol: Contact a C_urier representative for more information. and the any See 69 REFRIGERATION Plant LOG CARRIER 19XRV HERMETIC CENTRIFUGAL MODEL NO. DATE SERIAL NO. COOLER CONDENSER Water Refrigerant TIME Refrigerant Temp In Out InTemPout Press. Temp In PressUreout GPM VFD Oil Thrust GPM MACHINE MOTOR RLA COMPRESSOR Water Pressure Press. REFRIGERATION InTemPout BearingTemp Pressure SumPTemp Level _j Fig. 38 -- Refrigeration Log Average Line Average Line Line Average Load Current Voltage Kilowatts Current Inverter Temp Rectifier Temp VFD Coolant Flow OPERATOR INITIALS REMARKS PUMPOUT AND REFRIGERANT TRANSFER PROCEDURES Preparation -- The 19XRV chiller TO READ 1. COllie equipped wifll an optional pumpout storage tank, pumpout system, or pumpout compressol: The refrigerant can be pumped for service work to either the chiller compressor vessel or chiller condenser vessel by using the optional pumpout system. If a pumpout storage tank is supplied, the refrigerant can be isolaed in the storage tank. The following procedures describe how to transfer refrigerant from vessel to vessel and perfonn chiller evacuaions. lllay Pumpout Unit pumpout 2. To determine pumpout storage vacuum -0-400 psi (-101-0-2769 file storage tank. 3. Refer to Fig. numbers. 30, 31, and vessel (Fig. 40 for valve locations _ _-::-_ L2 CONTROL POWER TRANSFORMER PUMPOUT COMPRESSOR _ _ -- -- --HZ_'I _ _ CRANKCASE H4 LEGEND C FU GND HTR MTR NC OL SS 6oVA XFMR-1 HIGH PRESSURE SAFETY 2_ -- "_m _ LOW AUTO -N-C-OP SS-1 OFF ON _'_185-P L_J'-I_| E_ _ PRESSURE _9"- NC_O-_SE-.> OPEN 2 < _7 psia HEATER 240-600v 27-40 WATT D H1 x2 CONTROL E15.7 "6i_L )<2 I H.?Lin" HG}jI Fig. 39 -- Pumpout and PRESSURE CHILLERS WITH STORAGE In the Valve/Condition tables ilia accompany these file letter "C" indicates a closed v_dve. Figures 9 and locations of the valves. 20L C_-----_-_-2 L .... L1 by Always run chiller cooler and condenser waer pumps and always charge or transfer refrigerant as a gas when chiller vessel pressure is less than 35 prig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up. --Oil C 9) tank pressure, a 30 in. Hg kPa) gage is attached to should be visible in the pumpout unit compressor sight glass under all operating conditions and during shutdown. If oil is low. add oil as described under Optional Pumpout System Maintenance section, page 78. The pumpout unit control wiring schematic is detailed in Fig. 39. D or The ICVC dispkly on file chiller control panel is suitable for determining refrigerant-side pressures and low (soft) vacuum. To assure the desired range and accuracy when measuring evacuation and dehydration, use a quality vacuum indicator or manometel: This can be placed on POSITIVE TANKS -instructions, 10 show the Do not mix lefrigerants from chillers that use different compressor oils. Compressor &image can result. Optional during Transfer. addition, or removal of refrigerant in springisolated chillers may place severe stress on external piping if springs have not been blocked in both up and down directions. During transfer of refrigerant into and out of the optional storage tank, carefully monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to _fllow for refrigerant expansion. Overfilling may result in dmnage to the tank or personal injury. the PRESSURES file Schrader connections on each removing the pressure transducel: Always run the chiller cooler and condenser water pumps and always charge or transfer refrigerant as a gas when the chiller pressure is less than 35 psig (241 kPa). Below these pressures, liquid refrigerant flashes into gas, resulting in extremely low temperatures in the cooler/condenser tubes and possibly causing tube freeze-up. Operating REFRIGERANT leak testing: Unit Wiring 71 Schematic --------- Contactor Fuse Ground Heater Motor Normally Closed Overload Selector Switch FRAME ASSEMBLY CONTROL PANEL c. Turn off tile pumpout d. e. Turn off the chiller water pumps. Close valves 3 and 4. f. Open valves 2 and 5. VALVE CONDITION VALVE 2_ VALVE 4_ _COMPRESSOR VALVE / 5 ENTERING WATER / LEAVING WATER Refrigerant fiOl]l Pumpout Equ_dize refligerant Storage Close pumpout and storage tank valves 2, 4, 5, and 10, and close refrigerant charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present. 2. water pumps and monitor Open pumpout and storage tank open chiller valves la and lb. lb 2 C 3 4 C 5 C valves chiller 2. Transfer watec I a, I b, 2, 5, and 6. lb C 2 C 3 C 4 C 5 C 6 C 7 C 10 C lb remaining 2 Turn off pumpout condenser watel: the Refrigerant from Chiller to Pumpout 11 Storage pressure. Valve positions: la lb 2 C 3 4 C 5 C 6 7 C 10 C 3 4 5 6 water. Place valves in 11 3 and 6; 7 C 10 C 11 7 10 VALVE Run the pumpout compressor in automatic mode until vacuum switch is satisfied and compressor stops. Close valves 7 and 10. VALVE CONDITION c. 3. la lb 2 3 C Turn off the pumpout Remove any remaining 4 C 5 6 7 C 10 C 11 compressor. refrigerant. a. b. Turn on chiller water pumps. Turn on pumpout condenser watec c. Place valves in the following positions: 11 Run the pumpout compressor until the chiller pressure reaches 35 psig (241 kPa); then, shut off the pumpout compressor. Warm chiller condenser water will boil off any entrapped liquid refrigerant and chiller pressure will rise. refrigerant. 11 CONDITION a. Close valve 5 and open valve 4. Turn off the pumpout condenser water, and turn on the pumpout compressor in manual mode to push liquid refrigerant out of the storage tank. Monitor the storage tank level until the tank is empty. b. Close refrigerant charging 11 Transfer the remaining liquid. a. Turn off pumpout condenser the following positions: b. 6 11 Slowly open wflve 5 and refrigerant charging valves 7 and 10 to allow liquid refrigerant to drain by gravity into the storage tank. VALVE CONDITION Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charging valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller. ]la 11 Close valves b. Gradually crack open valve 5 to increase chiller pressure to 35 psig (241 kPa). Slowly feed refrigerant to prevent freeze-up. VALVE CONDITION 10 C VALVE CONDITION b. e. 7 C j. VALVE CONDITION pressure. Turn on chiller pressures. d. 6 i. la C condenser 5 Run the pumpout compressor in manual mode until the storage tank pressure reaches 5 psig (34 kPa), 18 in. Hg vacuum (41 kPa absolute). Turn off the pumpout compressor. 1. Equalize refrigerant Tank to Chiller a. la 4 C Turn on pumpout k. Transfer Tank During transfer of refrigerant into and out of the 19XR storage tank, carelhlly monitor the storage tank level gage. Do not fill the tank more than 90% of capacity to allow for refrigerant expansion. Overfilling may result in &image to the tank and personal injury. VALVE CONDITION 3 C h. a. c. 2 CONDENSER Fig. 40 -- Pumpout Unit Transfer lb g. VALVE CONDITION OIL SEPARATOR la compressor. When chiller pressure rises to 40 psig (276 kPa), turn on the pumpout compressor until the pressure again reaches 35 psig (241 kPa), then, turn off the pumpout compressor. Repeat this process until the chiller pressure no longer rises; then, turn on the pumpout compressor and pump out until the chiller pressure reaches 18 in. Hg vacuum (41 kPa absolute). This can be done in On or Automatic mode. valves 7 and 10. 72 f. Close valves VALVE CONDITION 4. la C I a, I b, 3, 4, and 6. lb C 2 C 3 C 4 C 5 C 6 C 7 C 10 C 11 g. Turn off the pumpout condenser water. Establish vacuum for service. To conserve refrigerant, operate the pumpout compressor as described in Step 3e until the chiller pressure is reduced to 18 in. Hg vacuum (41 kPa absolute). All Refrigerant 1. Push lefrigemnt to Chiller Condenser into chiller condenser a. Turn on the chiller chiller pressure. b. Valve positions: water Vessel b. Valve positions: and monitor 2. _ the 11 in the chiller c. Equalize the refrigerant condenseE d. Turn off chiller water denser water supply. e. Turn on pumpout compressor the chiller cooler vessel. f. When all liquid has been pushed into the chiller condenser vessel, close the cooler refrigerant isolation valve (11 ). g. Turn on the chiller water pumps. h. Turn off the pumpout pumps cooler and pumpout and e. Turn on pumpout compressor out of the chiller condenser. f. When all liquid is out of the chiller condenser. close valve 11 and any other liquid isolation valves on the chiller. g. Turn off the pumpout c. Run pumpout compressor until the chiller cooler vessel pressure reaches 18 in. Hg vacuum (41 kPa absolute). Monitor pressures on the chiller control panel and on refrigerant gages. This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automatically at approximately 15 in. Hg vacuum (51 kPa absolute). water. Turn off pumpout Turn off chiller compressoc Transfer All Refrigerant 1. Push lefiigemnt condenser water pumps to Chiller vessel. _ 3 and 4 11 C c. Tnrn on pumpout d. e. Run the pumpout compressor until the chiller condenser reaches 18 in. Hg vacuum (41 kPa absolute) in Manual or Automatic mode. Monitor pressure at the chiller control panel and refrigerant gages. Close valve lb. f. Turn off pumpout g. Close valves condenser water. compressor. la, 2, and 5. _ 11 C Turn off pumpout condenser water. Turn off chiller water pumps and lock out chiller compressoE Refrigerant to Normal Operating Conditions Turn on chiller water pumps. 3. Open valves la, lb, and 3. _ 11 C 4. Crack open valve 5, gradually increasing pressure in the evacuated chiller vessel to 35 psig (241 kPa). Feed refiigerant slowly to prevent tube freeze-up. 5. Leak test to ensure chiller vessel integrity. 6. Open v_dve 5 fully. CONDITION VALVE 11 C h. compressol: 2. e. Turn off pumpout compressor. f. Close valves lb, 3, and 4. g. con- to push refrigerant Make sure that liquid line service valves are closed and valves 2 and 5 are open. CONDITION VALVE d. Close valve la. _ and 1. Be sure that the chiller vessel that was opened has been evacuated. 11 c Turn on pumpout and pumpout b. Return b. VALVE CONDITION pumps cooler Turn on chiller water pumps. 5; open VALVE condenser water in the chiller a. i. CONDITION 11 Turn off chiller denser water. h. 2 and _ the d. CONDITION VALVE compressor. and monitor Equalize the refrigerant condensel: con- to push liquid out of Evacuate gas from chiller cooler vessel. a. Close liquid line service valves valves 3 and 4. pumps c. CONDITION VALVE CONDITION VALVE water Evacuate gas from chiller condenser vessel. pumps Turn on the chiller chiller pressure. VALVE CONDITION This operation can be done in Automatic or On mode. In Automatic mode, the compressor will stop automatically at approximately 15 in. Hg vacuum (51 kPa absolute). CH[LLERS WITH ISOLATION VALVES -- Tile valves referred to in the following instructions are shown in Fig. 31 and 40. Valve 7 remains closed. Transfer a. _ 11 C 7. Close valves la, lb, 3, and 5. 8. Open chiller isolation valves, if present. valve 11 and any other isolation watel: and lock out chiller CONDITION VALVE Turn off chiller Cooler Vessel into the chiller cooler vessel. 73 _ 11 water pumps. DISTILLING THE REFRIGERANT Adding 2. Equalize the refl'igerant pressure. a. Turn on chiller water pumps and monitor chiller pressures. b. Close pumpout and storage tank valves 2, 4, 5, and 10, and close chiller charging valve 7; open chiller isolation valve 11 and any other chiller isolation valves, if present. c. Open pumpout and storage tank valves 3 and 6; open chiller valves la and lb. VALVE CONDITION 3. lb 2 C 3 4 C 5 C 6 7 C 10 C Gradually crack open valve 5 to increase chiller pressure to 35 psig (241 kPa). Slowly feed refrigerant to prevent freeze-up. e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. the procedures Charge section, page 75. de- Always use the compressor pumpdown function in the Control Test table to turn on the cooler pump and lock out the compressor when transfen'ing refrigerant. Liquid refligemnt may flash into a gas and cause water in the heater exchanger tubes to freeze when the chiller pressure is below 35 psig (241 kPa) for HFC-134a, resulting in equipment damage. Removing Refrigerant -- If the optional pumpout system is used, the 19XRV refrigerant charge may be transferred to a pumpout storage tank or to the chiller condenser or cooler vessels. Follow the procedures in the Pumpout and Refrigerant Transfer Procedmes section when transferringrefrigerant from one vessel to another: 11 d. Adjusting the Refrigerant Charge -- If the addition or removal of refrigerant is required to improve chiller performance, follow the procedures Refrigerant Chmge section, page 75. given under the Trim Transfer remaining refrigerant. a. Close valve 3. Refrigerant Leak Testing -- Because HFC-134a refrigerantis above atmospheric pressure at room temperature, b. Open valve 2. leak testing can be performed with refrigerant in the chillel: Use an electronic halide leak detector, soap bubble solution, or ultrasonic leak detectol: Ensure that the room is well ventilated and free from concentration of refrigerant to keep false readings to a minimum. Before making aW necessguy repairs to a leak, transfer all refrigerant from the leaking vessel. c. d. Turn on Run the pressure (41 kPa e. Turn off the pumpout f. Close valves g. Turn off pumpout VALVE CONDITION 4. la Refrigerant--Follow scribed in Trim Refrigerant 1. Transfer the refligerant flom the chiller to the pumpout storage tank as described in the Transfer the Refligerant from Chiller to Pumpout Storage Tank section. pumpout condenser water. pumpout compressor until the storage tank reaches 5 psig (34 kPa), 18 in. Hg vacuum absolute) in Manual or Automatic mode. la C Leak Rate -- It is recommended by ASHRAE that chillers be taken off line immediately and repaired if the refrigerant leak rate for the entire chiller is more than 10% of the operating refrigerant charge per yegu: compressor. la, lb, 2, 5, and 6. lb C condenser 2 C 3 C 4 C In addition, Carrier recommends that leaks totalling less than the above rate but more than a rate of 0.1% of the total chguge per yegu should be lepaired during annu_d maintenance or whenever the refrigerant is transferred for other service work. water. 5 C 6 C 7 C 10 C 11 Test After Service, Drain the contaminants from the bottom of the storage tank into a containel: Dispose of contaminants safely. GENERAL Repair, or Major Leak- If all the refrigerant has been lost or if the chiller has been opened for service, the chiller or the affected vessels must be pressure tested and leak tested. Refer to the Leak Test Chiller section to perform a leak test. MAINTENANCE Refrigerant Properties -- The standard refrigerant for the 19XRV chiller is HFC-134a. At normal atmospheric pressure, HFC-134a refrigerant will boil at -14 F (-25 C) and must, therefore, be kept in pressurized containel.s or storage tanks. The refrigerant is practically odorless when mixed with air and is noncombustible at atmospheric pressure. Read the Material Safety Data Sheet and the latest ASHRAE Safety Guide for Mechanical Refrigeration to learn more about safe handling of this refrigerant. HFC-134a refrigerant should not be mixed with air or oxygen and pressurized for leak testing. In general, this refrigerant should not be present with high concentrations of air or oxygen above atmospheric pressures, because the mixture can undergo combustion, which could result in serious personal injury or death. TESTING WITH REFRIGERANT TRACER -- Use an environmentally acceptable refrigerant as a tracer for leak test procedures. Use dry nitrogen to raise the machine pressure to leak testing levels. TESTING WITHOUT REFRIGERANT TRACER -- Another method of leak testing is to pressurize with nitrogen only and to use a soap bubble solution or an ultrasonic leak detector to determine if leaks are present. Refrigerant HFC-134a will dissolve oil and some nonmetallic materials, dq the skin, and, in heavy concentrations, may displace enough oxygen to cause asphyxiation. When handling this refrigerant, protect the hands and eyes and avoid breathing fumes. 74 TO PRESSURIZE WITH DRY NITROGEN Trim Refrigerant Charge -- To reraove any excess refrigerant, follow the procednm in Transfer Refrigerant from Chiller to Pumpout Storage Tank section, Steps la and b, page 72. Refer to the Trimming Refligerant Charge section on page 66. NOTE: Pressurizing with dU nitrogen for leak testing should not be done if the full refiigerant charge is in the vessel because purging file nitrogen is veU dill]cult. 1. Connect a copper tube fiom the pressure regulator on the cylinder to the refligemnt charging valve. Never apply full cylinder pressure to the pressurizing line. Follow the listed sequence. 2. Open file charging valve fully. 3. Slowly open the cylinder regulating valve. 4. Observe the pressure gage on the chiller and close the regulating valve when the pressure reaches test level. Do not (,.w_,ed 140 psig (965 kPa). 5. Close the charging valve on the chiller. Remove the copper tube if it is no longer mquimdi WEEKLY Check the Lubrication System -- Mark the oil level on the reservoir sight glass, and observe the level each week while the chiller is shut down. If the level goes below the lower sight glass, check the oil reclaim system for proper operation. If additional oil is required, add it through the oil di'ain ch_u'gingwdve (Fig. 2). A pump is required when adding oil against refrigerant pressure. The oil charge for the 19XRV compressor depends on the compressor Frmne size: • Frame 2 compressor-8 gal (30 L) • Frame 3 compressor-8 gal (30 L) • Frame 4 compressor-10 gal (37.8 L) • Frame 4 compressor with split ring diffuser -- 12 gal (45 L) • Frame 5 compressor -- 18 gal (67.8 L) The added oil must meet Career specifications for the 19XRV. Refer to Changing Oil Filter and Oil Changes section on page 76. Any additional oil that is added should be logged by noting the amount and date. Any oil that is added due to oil loss that is not related to service will eventually return to the sump. It must be removed when the level is high. An oil heater is controlled by the PIC III to maintain oil temperature (see the Controls section) when the compressor is off. The ICVC COMPRESS screen displays whether the heater is energized or not. The heater is energized if the OIL HEATER RELAY p_umneter reads ON. [f the PIC III shows that the heater is energized and if the sump is still not heating up, the power to the oil heater may be off or the oil level may be too low. Check the oil level, the oil heater contactor voltage, and oil heater resistance. Repair the Leak, Retest, and Apply Standing After pressurizing tile chiller, test for leaks with an electronic halide leak detectok soap bubble solution, or an ultrasonic leak detector. Bring the chiller back to atmospheric pressure, repair a W leaks found, and retest. After retesting and finding no leaks, apply a standing vacuum test. Then dehydrate the chiller. Refer to the Standing Vacuum Test and Chiller Dehydiation section (pages 55 and 58) in the Before [nitial Start-Up section. Vacuum Test- Checking Guide Vane Linkage -- When the chiller is off. the guide vanes are closed and the actuator mechanism is in the position shown in Fig. 41. [f slack develops in the diive chain, do the following to eliminate backlash: 1. With the chiller shut down and the actuator fl.dly closed, remove the chain guard and loosen the actuator bracket holddown bolts. 2. Loosen guide vane sprocket adjusting bolts. 3. PU bracket upwards to remove slack, then mtighten the bracket holddown bolts. 4. Retighten the guide vane sprocket adjusting bolts. Ensure that the guide vane shaft is rotated fully in the clockwise direction in order close it fully. The PIC 1II does not permit compressor start-up if the oil temperature is too low. The PIC III continues with start-up only after the temperature is within allowable limits. 3 ACT SPROCKET VANE ACTUATOR SCHEDULED CHAIN GUARD Service Ontime -- The [CVC will display a SERVICE ONTIME value on the MAINSTAT screen. This value should be reset to zero by the service person or the operator each time major service won is completed so that the time between service can be viewed and tracked. CLOSE VANE SPROCKET GUIDE VANE SPROCKET ADJUSTING BOLTS Fig. 41 --Guide MAINTENANCE Establish a regular maintenance schedule based on actual chiller requirements such as chiller load, run hours, and water quality. The time inteia'als listed in this section an" o_'red as guides to sem'i_z" onh" BRACKET HOLDDOWN BOLTS VANE SHAFT MAINTENANCE Vane Actuator Linkage 75 Inspect the Control Panel -- Maintenance consists of general cleaning and tightening of connections. Vacuum the cabinet to eliminate dust build-up. If the chiller control malfunctions, refer to the Troubleshooting Guide section for control checks and adjustments. Oil Specification -- If oil is added, it must meet the following Carrier specifications: Oil Type for units using R-134a .................. Inhibited polyolester-based synthetic compressor oil formatted for use with HFC, gear-driven, hermetic compressors. ISO Viscosity Grade ................................. Ensure power to the control center is off when cleaning and tightening connections inside the control p_mel. Failure to disconnect power could result in electrocution. The polyolester-based oil (P/N: PP23BZI03) ordered from a local Carrier representative. 68 may be Oil Changes--Cmrier Check Safety and Operating recommends changing the oil after the first year of operation and every three to five years thereafter as a minimum in addition to a yedy oil amdysis. Howevel: if a continuous oil monitoring system is functioning and a yearly oil analysis is performed, file time between oil changes can be extended. TO CHANGE THE OIL Controls Monthly Table tion, least Table -- Check values of monitored parameters (see 6 for safety control settings). To ensure chiller protecthe Automated Control Test should be performed at once per month (with machine in OFF mode). See 12 for Control Test functions. 1. Transfer the refrigerant into the chiller condenser vessel (for isolatable vessels) or to a pumpout storage tank. Changing Oil Filter--Change the oil filter on a yearly basis or when the chiller is opened for repairs. The 19XRV chiller has an isolatable oil filter so that the filter may be changed with the refrigerant remaining in the chiller. Early 19XRV compressors were designed with the oil filter housing attached to the oil pump. The following procedure applies to later 19XRV compressors which have the oil filter separate flom the oil pump. 1. Ensure the compressor compressor is open. is off and the disconnect Disconnect 3. Close the oil filter isolation valves located behind power panel on top of oil pump assembly. Close the isolation valves located on both ends of the oil filtel: Have rags and a catch basin available to collect oil spillage. 4. the power to the oil pump. 5. Equfdize the filter's higher internal pressure to ambient by connecting an oil charging hose to the Schmder valve on the oil filter housing. Collect the oil-refrigerant mixture which is dischm'gedi 6. Remove the oil filter assembly by loosening the hex nuts on both ends of the filter assembly. 7. Insert the replacement tilter assembly with the rerow on the housing pointing away from the oil pump. 8. Rotate the assembly so that the schraeder drain vfflve is oriented fit the bottom, and tighten the connection nut on each end to a torque of approximately 30 ft-lb (41 N-m) Evacuate the filter housing by placing a vacuum pump on the charging valve. Follow the normal evacuation procedures. Shut the charging valve when done and reconnect the valve so that new oil can be pumped into the filter housing. Fill with the stone amount that was removed; then close file charging valve. 10. Remove the hose from the chmging valve, open the isolation valves to the filter housing, and turn on the power to the pump and the motol: Open file control and oil heater circuit breakel: 5. Change the oil filter fit this time. See Changing section. Oil Filter 6. Change the refrigerant filter fit this time, see the next section, Refrigerant Filtec 7. Charge the chiller with oil. Chmge until the oil level is equal to the oil level marked in Step 2. Turn on the power to the oil heater and let file PIC [II warm it up to fit least 140 F (60 C). Operate the oil pump manually, using the Control Test function, for 2 minutes. For shutdown conditions, the oil level should be full in the lower sight glass. If the oil level is above 1/2 full in the upper sight glass, remove the excess oil. The oil level should now be equal to the amount shown in Step 2. Refrigerant Filter -- A refrigerant filter/driel, located on the refrigerant cooling line to the motol; should be changed once a ye;u or more often if filter condition indicates a need for more frequent replacement. Change the filter by closing the filter isolation valves (Fig. 4) and slowly opening the flare fittings with a wrench and back-up wrench to relieve the pressure. A moisture indicator sight glass is located beyond this filter to indicate the volume and moisture in the refrigerant. If the moisture indicator indicates moisture, locate the source of water immediately by performing a thorough leak check. The oil filter housing is at a high pressure. Relieve this pressure slowly. Failure to do so could result in serious personal injury. 9. Mark the existing oil level. 3. 4. When the chiller pressure is 5 psig (34 kPa) or less, drain the oil reservoir by opening the oil charging vfdve (Fig. 2). Slowly open the valve against refrigerant pressure. for the 2. 2. Oil Reclaim Filter--The oil reclaim system has a strainer on file eductor suction line, a strainer on the discharge pressure line, and a filter on the cooler scavenging line. Replace file filter once per year or more often if tilter condition indicates a need for more frequent replacement. Change the filter by closing the filter isolation valves and slowly opening the flare fitting with a wrench and back-up wrench to relieve the pressure. Change the stminel_ once every 5 yeal_ or whenever refrigerant is evacuated from the coolel: 76 VFD Refrigerant Strainer -- A t_efiigerant strainer is located in the 5/8 in. line that supplies refiigerant to the VFD. The strainer should be replaced once a year or more often if the str;dner condition indicates a need for mote ft_equent replacement. Change the filter by closing the refrigerant cooling line isolation valves. Refiigerant pressure can be relieved through access valves on the strainer housing. Tighten 5/8 flare nuts to 55 to 66 ft-lb (75 to 89 Nm). Inspect inspection service. Refrigerant Float System -every 5 years or when the condenser 1. Transfer the refrigerant into the cooler pumpout storage tank. 2. Remove the float access covet: signs of corrosion or scale. Replace a sensor or Schmder fitting if corroded or remove any scale if found. CONDENSER AND OPTIONAL FLOW DEVICES -Since this water circuit is usually an open-type system, the tubes may be subject to contamination and scale. Clean the condenser tubes with a rotmy tube cleaning system at least once per yetu and more often if the water is contaminated. Inspect the entering and leaving condenser water sensors and flow devices for signs of corrosion or scale. Replace the sensor or Schrader fitting if corroded or remove any scale if foundi Perforln this is opened for Higher than normal condenser pressures, together with the inability to reach full refiigeration load, usually indicate ditty tubes or air in the chillet: If the refiigeration log indicates a rise above normal condenser pressures, check the condenser refiigerant temperature against the leaving condenser water temperature. If this reading is more than what the design difference is supposed to be, the condenser tubes may be ditty or water flow may be incorrect. Because HFC-134a is a high-pressure refiigetant, air usually does not enter the chiller vessel or into a 3. Clean the chamber and valve assembly thoroughly. sure the valve moves fieely. Ensure that all openings fiee of obstructions. 4. Examine the cover gasket and replace if necessmy. Be are During the tube cleaning process, use brushes specially designed to avoid scraping and scratching the tube wall. Contact a Carrier representative to obtain these brushes. Do not use wire brushes. See Fig. 42 for a view of the float v_dve design. For linear float valve designs, inspect the orientation of the float slide pin. It must be pointed toward the bubbler tube for proper operation. Inspect Relief Valves and Piping -- The relief v_dves on this chiller protect the system against the potentially dangerous effects of overpressure. To ensure against dalnage to the equipment and possible injury to personnel, these devices must be kept in peak operating condition. As a minimum, the following maintenance is required. Hard scale may require chemic_d treatment for its prevention or removal. Consult a water treatment specialist for proper treatment. 1. At least once a yeat: disconnect the vent piping at the valve outlet and catefttlly inspect the valve body and mechanism for any evidence of interned corrosion or rest, dirt, sc_de, leakage, etc. 2. If corrosion or foreign material is found, do not attempt to repair or recondition. Replace the valve. 3. If the chiller is installed in a corrosive atmosphere or the relief v_dves ate vented into a corrosive atmosphere, inspect the relief valves at more fiequent intervals. Compressor Bearing and Gear Maintenance Water Leaks -- The refiigerant moisture indicator on the refiigetant motor cooling line (Fig. 2) indicates whether there is water leakage during chiller operation. Water leaks should be repaired immediately. The chiller must be dehydi'ated after repair of water leaks. See Chiller Dehydi'ation section, page 58. -- 1 2 The key to good bearing and gear maintenance is proper lubrication. Use the proper grade of oil, maintained at recommended level, temperature, and pressure. Inspect the lubrication system regularly and thoroughly. Excessive beating were can sometimes be detected through increased vibration or increased beating temperature. Gears and babbitted joumal and thrust bearings should be exalnined approximately every five years for signs of wear based on the results of the annual oil analysis. To inspect the bearings, a complete compressor teatdown is required. Only a trained setvice technician should remove and examine the bearings. The fiequency of exalnination is determined by the hours of chiller operation, load conditions during opetafion, and the condition of the oil and the lubrication system. Rolling element bearings (Frmne 3 compressor high speed shaft only) cannot be field inspected; excessive vibration is the primary sign of wear or damage. If either symptom appems, contact an experienced and responsible service organization for assistance. Inspect the Heat Devices Exchanger Tubes and Flow 8 LEGEND COOLER AND OPTIONAL FLOW DEVICES -- Inspect and clean the cooler tubes at the end of the first operating season. Because these tubes have internal ridges, a rotary-type tube cleaning system is needed to fully clean the tubes. Inspect the tubes' condition to determine the scheduled frequency for future cle_ming and to determine whether water treatment in the chilled water/brine circuit is adequate. Inspect the entering and leaving chilled water temperature sensors and flow devices for 1 2 3 4 5 6 7 8 --------- 7 Refrigerant Inlet from FLASC Chamber Linear Float Assembly Float Screen Bubble Line Float Cover Bubble Line Connection Refrigerant Outlet to Cooler Gasket Fig. 42 -- 19XRV Float Valve Design 77 Water Treatment--Untreated or improperly treated water may result in corrosion, scaling, erosion, or algae. The services of a qu_dified water treatment specialist should be obtained to develop and monitor a treatment program. fittings. Comptue the two readings. If there is a difference in readings, the transducer can be calibrated as described in the Troubleshooting Guide section. Oil differential pressure (OIL PUMP DELTA P on the COMPRESS screen) should be zero whenever the compressor is off. Optional Pumpout System Maintenance -- For pumpout unit colnpressor maintenance details, refer to the 19XR Positive Pressure Stolage System Installation, Start-Up, and Service Instructions. Water must be within design flow limits, clean, and treated to ensure proper chiller performance and reduce the potential of tube &image due to corrosion, scaling, erosion, and algae. CtuTier assumes no responsibility for chiller &image resulting from untreated or improperly treated watec Inspect OPTIONAL PUMPOUT COMPRESSOR OIL CHARGE -Use oil conforming to Carrier specifications for reciprocating compressor usage. Oil requirements are as follows: ISO Viscosity ................................ Cturier Pfut Number. ........... the VFD 68 or 220 PP23BZ 103 or PP23BZ104 The total oil chtuge is 13 oz. (0.5 L) Oil should be visible in the pumpout compressor sight glass both during operation and at shutdown. Always check the oil level before operating the pumpout compressol: Before adding changing oil, relieve the refrigerant pressure through the access valves. The motor leads must be disconnected from the starter before an insulation test is performed. The voltage generated from the tester can &_mage the starter o1 drive components. Relieve refrigerant follows: pressure and add oil to the pumpout unit 1. Close service v_dves 2and4. Before working on tiny st_uter or drive, shut off the chillel: open and tag all disconnects supplying power to the stfulec After disconnecting input power to a VFD and before touching tiny internal components, wait five minutes for the DC bus capacitors to discharge, then check the voltage with a voltmetel: Failure to observe this precaution could result in sever bodily injury or death. 2. Run the pumpout compressor in Automatic mode for one minute or until the vacuum switch is satisfied and compressor shuts off. 3. Move the pumpout selector switch to OFE Pumpout compressor shell should now be under vacuum. 4. Oil can be added to the shell with a hand oil pump through the access valve in the compressor base. NOTE: The compressor access valve has a self-sealing fitting which will require a hose connection with a depressor to open. OPTIONAL PUMPOUT SAFETY CONTROL SETTINGS (Fig. 43)--The optional pumpout system high-pressure switch opens fit 185 psig (1276 kPa) and closes fit 140 psig (965 kPa). Check the switch setting by operating the pumpout compressor and slowly throttling the pumpout condenser water The disconnect on the st_uter fiont panel does not deenergize all internal circuits. Open all internal and remote disconnects before servicing the sttutel: Never open isolating knife switches while equipment is operating. Electrical arcing can cause serious injury. Ordering Replacement Chiller Parts -- When ordering Carrier specified parts, the following information must accompany tin order: • chiller model number and serial number • name, quantity, and part number of the part required • delivery address and method of shipment. Periodically vacuum or blow off accumulated debris on internal VFD enclosure components with a high-velocity, lowpressure blowec Power connections on newly installed VFDs may relax and loosen after a month of operation. Turn power off and retighten. Recheck annually thereafter. CONTACTOR TERMINAL STRIP SWITCH FUSES \ Loose power connections can cause voltage spikes, heating, m¢fllimctioning, or failures. over- @ Recalibrate Pressure Transducers -- Once a yea1, the pressure transducers should be checked against a pressure gage reading. Check all eight transducers: the 2 oil differenti_fl pressure transduco_, the condenser pressure transducer, the cooler pressure transduce1: the diffuser pressure transducer (only for compressors equipped with split ring diffusers), and the optional wato_ide pressure transducer pairs (consisting of 4 flow devices: 2 cooler. 2 condenser). Note the evaporator and condenser pressure readings on the HEAT EX screen on the ICVC (EVAPORATOR PRESSURE and CONDENSER PRESSURE). Attach an accurate set of refrigeration gages to the cooler and condenser Schmder TRANSFORMER Fig. 43 -- 78 Pumpout Control Box (Interior) TROUBLESHOOTING GUIDE (Tables 15-18B) RESISTANCE CHECK -- Turn off the control power and, fi_)m the module, disconnect the terminal plug of the sensor in question. With a digital ohmmetel: measure sensor resistance between receptacles as designated by the wiring diagram. The resistance and corresponding temperature are listed in Table 18A or 18B. Check the resistance of both wires to ground. This resistance should be infinite. Overview- The PIC III has many features to help tile operator and technician troubleshoot a 19XRV chiller • • The ICVC shows the chiller's actual operating conditions and can be viewed while the unit is running. The ICVC default screen freezes when an alarm occurs. VOLTAGE DROP -- The voltage drop across any energized sensor can be measured with a digital voltmeter while the control is energized. Table 18A or 18B lists the relationship between temperature and sensor voltage drop (volts dc measmed across the energized sensor). Exercise ctue when measuring voltage to prevent damage to the sensor leads, connector plugs, and modules. Sensors should also be checked at the sensor plugs. Check the sensor wire at the sensor for 5 vdc if the control is powered on. The freeze enables the operator to view the chiller conditions at the time of alarm. The STATUS screens continue to show current information. Once all alarms have been cleared • • • • • (by correcting the problems and pressing the softkey), the ICVC default screen returns to normal operation. The CONTROL ALGORITHM STATUS screens (which include the CAPACITY. OVERRIDE, LL_MAINT. VFD_HIST. LOADSHED, CUR_ALARM, WSMDEFME, and OCCDEFCM screens) display information that helps to diagnose problems with chilled water temperature control, chilled water temperature control overrides, hot gas bypass, surge algorithm status, and time schedule operation. See Table 15. The control test feature facilitates the proper operation and test of temperature sensors, pressure transducers, the guide vane actuator, oil pump, water pumps, tower control, and other on/off outputs while the compressor is stopped. It also has the ability to lock off the compressor and turn on water pumps for pumpout operation. The ICVC shows the temperatures and pressures required during these operations. From other SERVICE tables, the operator/technician can access configured items, such as chilled water resets, override set points, etc. If an operating fault is detected, an alarm message is generated and displayed on the ICVC default screen. A more detailed message -- along with a diagnostic message -is also stored into the ALARM HISTORY and ALERT H[STORY tables. Review the ALERT HISTORY table to view other less critical events and abnormal conditions which may have occurred. Compare timing of relevant alerts and alarms. Checking Display Messages--The Relieve all refrigerant pressure or &'ain the water before replacing temperature sensors or thermowells threaded into the refrigerant pressure boundary. Failure to do so could result in persomd injmy and equipment damage. CHECK SENSOR ACCURACY-Place the sensor in a medium of known temperature and compare that temperatme to the measured reading. The thermometer used to determine the temperature of the medium should be of laboratory qu_flity with 0.5 ° F (.25 ° C) graduations. The sensor in question should be accurate to within 2 ° F (1.2 ° C). See Fig. 7 for sensor locations. The sensors are immersed directly in the refrigerant or water circuits. The wiring at each sensor is easily disconnected by unlatching the connectol: These connectors allow only one-way connection to the sensol: When installing a new sensor, apply a pipe sealant or thread sealant to the sensor threads. DUAL TEMPERATURE SENSORS -- For servicing convenience, there are 2 sensol_ each on the beming and motor temperature sensors. If one of the sensors is &_maged, the other can be used by simply moving a wire. The number 2 terminal in the sensor terminal box is the common line. To use the second sensol: move the wire from the number I position to the number 3 position. first area to check when troubleshooting the 19XRV is the ICVC display. If the alarm light is flashing, check the primary and secon&wy message lines on the ICVC default screen (Fig. 14). These messages will indicate where the fault is occurring. These messages contain the alarm message with a specified code. This code or state appears with each alarln and alert message. The ALARM and ALERT HISTORY tables on the [CVC SERVICE menu also contains a message to further expand on the fault description. NOTE: The &_te format in these tables is MM/DD/YY. Checking Pressure Transducers-There are 6 factoly-installed pressure transducers, with inputs available for optional cooler and condenser watel.side differential pressure transducers. The ICVC softwm'e will display a default reading of 26 psi during start-up and operation. An additional transducer. factory inst;_lled in the bottom of the cooler barrel, will read as EVAPORATOR SATURATION TEMP on the HEAT_EX DISPLAY screen. This provides additional protection against a loss of water flow condition. These pressure transducers can be calibrated if necessary. It is not usually necessary to calibrate at initial start-up. However. at high altitude locations, it is necessmy to calibrate the transducel.'s to ensure the proper refrigerant temperature/ pressure relationship. Each transducer is supplied with 5 vdc power from the CCM. If the power supply fifils, a transducer voltage reference alarm occurs. If the transducer reading is suspected of being faulty, check the TRANSDUCER VOLTAGE REF supply voltage. It should be 5 vdc _+.5v displayed in CONTROL TEST under CCM PRESSURE TRANSDUCERS. If the TRANSDUCER VOLTAGE REF is correct, the transducer should be recalibrated or replaced. For a complete list of possible _darm and alert messages, see Table 15. If the alarm light starts to flash while accessing a menu screen, press the _ softkey to return to the defimlt screen to read the almm message. The STATUS screen can also be accessed to determine where an alarm exists. A "C" to the right ofa pammeter's value means that there is a communications fault on that channel. Checking Temperature Sensors --All temperature sensors are thermistor-type sensors. This means that the resistance of the sensor varies with temperature. All sensors have the same resistance characteristics. If the controls m'e on, determine sensor temperature by measuring voltage diop; if the controls are powered off, detemfine sensor temperature by measuring resistance. Compare the readings to the values listed in Table 18A or 18B. Also check that inputs on CCM J5-1 through J5-6 have not been grounded and are not receiving anything other than a 4 to 20 mA signal. 79 COOLER CONDENSER PRESSURE TRANSDUCER AND OPTIONAL WATERSIDE FLOW DEVICE CALIBRATION -- Calibration can be checked by compming the plessme leadings from file transducer to an accurate refrigeration gage leading. These readings can be viewed or calibrated from the HEAT_EX screen on the ICVC. The transducer can be checked grad calibrated fit 2 pressure points. These calibration points me 0 psig (0 kPa) and between 25 and 250 psig (173 and 1724 kPa). To calibrate these transducers: 1. Shut down the compressor, NOTE: There exchangers. should coolek and condenser be no flow through high altitude pumps. Disconnect the transducer in question from its Schmder fitting for cooler or condenser transducer calibration. For oil pressure or flow device calibration keep transducer in place. NOTE: If the cooler or condenser vessels are at 0 psig (0 kPa) or are open to atmospheric pressure, the transducers can be calibrated for zero without removing the transducer from the vessel. 3. Access the HEAT_EX scleen and view the particular transducer reading (the EVAPORATOR PRESSURE or CONDENSER PRESSURE parameter on the HEAT EX Control Table 15- TABLE If the transducer value is not within the calibration range, the transducer returns to the original reading. If the pressure is within the allowed range (noted above), check the voltage ratio of the transducer. To obtain the voltage ratio, divide the voltage (dc) input from the transducer by the TRANSDUCER VOLTAGE REF supply voltage signal (displayed in CONTROL TEST menu in the PRESSURE TRANSDUCERS screen) or measure across the positive (+ red) and negative (- black) leads of the transducer. For example, the condenser transducer voltage reference is measured fit CCM terminals J2-4 and J2-6, the condenser transducer voltage input. The input to reference voltage ratio must be between 0.80 and 0.11 for the software to allow calibration. Pressurize the transducer until the ratio is within range. Then attempt calibration again. between Checkout Procedure -- One These maintenance screens are very useful in helping to determine how the control temperature is calculated and guide vane positioned and also for observing the leactions from load changes, control point overrides, hot gas bypass, surge prevention, etc. The tables are: softkey. The value will now go to zero. No high end calibration is necessary for OIL PRESSURE DELTA P or flow devices. point can fdso be calibrated Algorithms of the tables on the [CVC SERVICE menu is CONTROL ALGORITHM STATUS. The maintenance screens may be viewed from the CONTROL ALGORITHM STATUS table to see how a particulm control algorithm is operating. HEAT_EX screen, and OIL PUMP DELTA P on the COMPRESS screen). It should read 0 psi (0 kPa). If the reading is not 0 psi (0 kPa), but within _+5 psi (35 kPa), the value may be set to zero by pressing the softkey while the appropriate transducer ptuameter is highlighted on the ICVC screen. Then press the A high pressure fok so the is correct. Be sure to use a back-up wrench on the Schrader fitting whenever removing a transducek since the Schmder fitting may back out with the transducek causing an uncontrolled loss of refrigerant and possible injury to personnel. screen). To calibrate oil pressure or liquidside flow device, view the particular reading (CHILLED WATER DELTA P and CONDENSER WATER DELTA P on the 4. relationship The PIC III does not allow calibration if the transducer is too far out of calibration. In this case, a new transducer must be installed and re-calibrated. If calibration problems are encountered on the OIL PRESSURE DELTA P channel, sometimes swapping the compressor oil discharge pressure transducer and the oil sump pressure transducer will offset an adverse transducer tolerance stack up and allow the calibration to proceed. TRANSDUCER REPLACEMENT -- Since the transducers are mounted on Schrader-type fittings, there is no need to remove refrigerant from the vessel when replacing the transducers. Disconnect the transducer winng. Do not pull on the transducer wires. Unscrew the transducer from the Schmder fitting. When instfdling a new transducer, do not use pipe sealer (which can plug the sensor). Put the plug connector back on the sensor and snap into place. Check for refi'igerant leaks. the heat 2. locations must be compensated chiller temperature/pressure Capacity Control OVERRIDE Override Status LEAD/LAG Status Time Schedules Status OCCDEFCM 25 WSMDEFME Water System Manager Status VFD HIST VFD Alarm History Loadshed Status LOADSHED CURALARM calibrated by accessing the appropriate transducer pmameter on the HEAT_EX screen, highlighting the pm'ametek pressing the _ softkey, and then using the EXPANDED NAME CAPACITY LL MAINT and 250 psig (172.4 and 1723.7 kPa) by attaching a regulated 250 psig (1724 kPa) pressure (usually from a nitrogen cylinder). The high pressure point can be Control Current Alarm Status Algorithm Status Tables DESCRIPTION This tableshows all values used to calculate the chilled water/brine control point. Details of all chilled water control override values. Indicates LEAD/LAG operation status. The Local and CCN occupied schedules are displayed here to help the operator quickly determine whether the schedule is in the "occupied" mode or not. The water system manager is a CCN module that can turn on the chiller and change the chilled water control point, This screen indicates the status of this system. Displays VFD values at last fault. DisplaysLeadshed (Demand Limit) status. Displays current chiller alarms. Surge and hot gas bypass parameters may be observed in the HEAT_EX screen. The surge and hot gas bypass control algorithm status is viewed from tiffs screen. All values defiling wifll this control are displayed. [INCREASE 1 or [DECREASE] softkeys to adjust the vfdue to the exact pressure on the refrigerant gage. Press the _ softkey to finish the calibration. Pressures fit 8O Control Test -- The Control Test feature can check all the thermistor temperature sensors, pressure transducel_, pumps and their associated flow devices, the guide vane actuatol: and other control outputs such as tower fans, VFD cooling solenoid, shunt trip relay, oil heaters, alarm relay and hot gas bypass. The tests can help to determine whether a switch is defective or a pump relay is not operating, as well as other useful n_ubleshooting issues. During pumpdown operations, the pumps _ue energized to prevent fieeze-up and the vessel pressures and temperatures ale displayed. The Pumpdown/ Lockout feature prevents compressor start-up when there is no refiigerant in the chiller or if the vessels are isolated. The Terminate Lockout feature ends the Pumpdown/Lockout after the pumpdown procedure is reversed and refrigerant is added. LEGEND CCN CCM DPI ICVC PIC III TXV VFD VFG --------- TO TABLES 16A-16J Carrier Comfort Network Chiller Control Module Drive Peripheral Interface International Chiller Visual Control Product Integrated Controls III Thermostatic Expansion Valve Variable Frequency Drive Variable Frequency (Drive) Gateway Table 16 -- Alarm and Alert Messages A. MANUAL STOP PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY MANUALLY STOPPED -- PRESS TERMINATE PUMPDOWN MODE CCN OR LOCAL TO START TO SELECT CCN OR LOCAL PIC III in OFF mode, press CCN or LOCAL softkey to start unit. Enter the CONTROL TEST table and select TERMINATE LOCKOUT to unlock compressor. SHUTDOWN IN PROGRESS COMPRESSOR UNLOADING Chiller unloading before shutdown due to soft!stop feature. SHUTDOWN IN PROGRESS COMPRESSOR DEENERGIZED Chiller compressor is being commanded deenergized within one minute. ICE BUILD SHUTDOWN B. READY OPERATION IN PROGRESS COMPLETE to stop. Water pumps are Chiller shutdown from Ice Build operation. RECYCLE RESTART PENDING Chilled water temperature below recycle set point. Cooling load is less than chiller minimum capacity. TO START PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE UNOCCUPIED READY TO START IN XX MIN REMOTE CONTACT OPEN Remote contacts are open. Close contacts to start. READY TO START IN XX MIN STOP COMMAND Chiller START/STOP on MAINSTAT manually forced to stop. Release SUPERVISOR force to start. READY TO START IN XX MIN OCCUPIED READY TO START IN XX MIN REMOTE CONTACT CLOSED Chiller timer countdown complete. Unit will proceed to start. Remote contact Enabled and Closed. READY TO START IN XX MIN START COMMAND Chiller START/STOP on MAINSTAT manually forced to start. Release SUPERVISOR force to start under normal control. READY TO START IN XX MIN RECYCLE RESTART PENDING Chiller is recycle mode. READY TO START UNOCCUPIED Time schedule for PIC III is unoccupied in OCCPC01S screen. Chiller will start when state changes to occupied. Make sure the time and date are correct in the TIME AND DATE screen. READY TO START REMOTE CONTACT OPEN Remote contacts have stopped the chiller. Close contacts to start. READY TO START STOP COMMAND Chiller START/STOP on MAINSTAT manually forced to stop. Release SUPERVISOR force to start. READY TO START OCCUPIED READY TO START REMOTE CONTACT CLOSED Chiller timer counting down. Unit ready to start. READY TO START START COMMAND Chiller START/STOP on MAINSTAT has been manually forced to start. Chiller will start regardless of time schedule or remote contact status. STARTUP INHIBITED LOADSHED C. IN RECYCLE MODE CAUSE/REMEDY READY TO START IN XX MIN Time schedule for PIC III is unoccupied. Chillers will start only when occupied. Check OCCPCnnS and Holidays screens. IN EFFECT MODE Chiller timer counting down. Unit ready to start. IN EFFECT MODE IN EFFECT MODE Chiller timers countdown IN EFFECT IN EFFECT is complete. Unit will proceed to start. CCN Ioadshed module commanding chiller to stop. SHUTDOWN PRIMARY MESSAGE SECONDARY RECYCLE RESTART PENDING OCCUPIED RECYCLE RESTART PENDING RECYCLE RESTART RECYCLE RESTART MESSAGE PROBABLE MODE CAUSE/REMEDY Unit in recycle mode, chilled water temperature above Setpoint to start. is not sufficiently REMOTE CONTACT CLOSED Unit in recycle mode, chilled water temperature above Setpoint to start. is not sufficiently PENDING START COMMAND Chiller START/STOP on MAINSTAT manually forced to start, chilled water temperature is not sufficiently above Setpoint to start. PENDING ICE BUILD MODE IN EFFECT Chiller in ICE BUILD mode. Chilled water temperature ICE BUILD conditions. 81 is satisfied for Table 16 -- Alarm and Alert Messages (cont) D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is necessary. ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE compressor ADDITIONAL starts CAUSE/REMEDY 100 PRESTART ALERT STARTS LIMIT EXCEEDED 100_Excessive (8 in 12 hours), 101 PRESTART ALERT HIGH BEARING TEMPERATURE 101_Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*. Check oil heater for proper operation. Check for low oil level, partially closed oil supply valves, clogged oil filters. Check the sensor wiring and accuracy. Check Comp Thrust Brg Alert setting in SETUP1 screen. 102 PRESTART ALERT HIGH MOTOR TEMPERATURE 102-_Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*. Check motor sensors for wiring and accuracy. Check motor cooling line for proper operation, or restrictions. Check for excessive starts within a short time span. Check Comp Motor Temperature Override setting in SETUP1 screen. 103 PRESTART ALERT HIGH DISCHARGE TEMP 103_Comp Discharge Temp [VALUE] exceeded limit of [LIMIT]*. Allow discharge sensor to cool. Check sensor wiring and accuracy. Check for excessive starts. Check Comp Discharge Alert setting in SETUP1 screen. 104 PRESTART ALERT LOW REFRIGERANT TEMP 104-_Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. Check transducer wiring and accuracy. Check for low chilled fluid supply temperatures. Check refrigerant charge. Check Refrig Override Delta T in SETUP1 screen. 105 PRESTART ALERT LOW OIL TEMPERATURE 105_Oil Sump Temp [VALUE] exceeded limit of [LIMIT]*. Check oil heater contactor/relay and power. Check oil level and oil pump operation. 106 PRESTART ALERT HIGH CONDENSER PRESSURE 106_Condenser Pressure [VALUE] exceeded limit of [LIMIT]*. Check transducer wiring and accuracy. Check for high condenser water temperatures. Check high condenser pressure switch wiring. 107 PRESTART ALERT LOW LINE VOLTAGE 107-_Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*. Check voltage supply. Check voltage transformers and switch gear. Consult power utility if voltage is low. 108 PRESTART ALERT HIGH LINE VOLTAGE 108_Percent Line Voltage [VALUE] exceeded limit of [LIMIT]*. Check voltage supply. Check power transformers. Consult power utility if voltage is high. 109 PRESTART ALERT GUIDE VANE CALIBRATION 109_Actual Guide Vane Pos Calibration Required Before Startup. Press STOP button on ICVC and perform Guide Vane Calibration in Controls Test screen. Check guide vane actuator feedback potentiometer. 110 PRESTART ALERT HIGH RECTIFIER TEMP 110_Rectifier Temperature exceeded limit of [LIMIT]*. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage. 111 PRESTART ALERT HIGH INVERTER TEMP 111-_lnverter Temperature [VALUE] exceeded limit of [LIMIT]*. [VALUE] Depress the RESET softkey if additional start is required. Reassess start-up requirements. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage. *[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. E. START-UP IN PROGRESS PRIMARY MESSAGE SECONDARY MESSAGE MODE CAUSE/REMEDY STARTUP IN PROGRESS OCCUPIED Chiller is starting. Time schedule is Occupied. STARTUP IN PROGRESS REMOTE CONTACT CLOSED Chiller is starting. Remote contacts are Enabled and Closed. STARTUP IN PROGRESS START COMMAND Chiller is starting. Chiller START/STOP start. AUTORESTART PROGRESS IN OCCUPIED AUTORESTART PROGRESS IN REMOTE CONTACT CLOSED Chiller is starting after power failure. Remote contacts are Enabled and Closed. AUTORESTART PROGRESS IN START COMMAND Chiller is starting after power failure. Chiller START/STOP screen manually forced to start. IN EFFECT MODE in MAINSTAT manually forced to Chiller is starting after power failure. Time schedule is Occupied. IN EFFECT 82 on MAINSTAT Table 16 -- Alarm and Alert Messages (cont) R NORMALRUN PRIMARY MESSAGE SECONDARY MESSAGE CAUSE]REMEDY RUNNING -- RESET ACTIVE BY 4-20 mA SIGNAL Auto chilled water reset active based on external input. RUNNING -- RESET ACTIVE RUNNING -- RESET ACTIVE REMOTE TEMP SENSOR CHW TEMP DIFFERENCE Auto chilled water reset active based on external input. Auto chilled water reset active based on CHW Delta T in TEMP CTL screen. RUNNING -- TEMP CONTROL LEAVING CHILLED WATER Default method of temperature RUNNING -- TEMP CONTROL ENTERING CHILLED WATER Entering Chilled Water control enabled in TEMP RUNNING -- TEMP CONTROL TEMPERATURE Ramp Loading in effect. Use RAMP DEM screen to modify. RUNNING -- DEMAND LIMITED BY DEMAND RAMP LOADING Ramp Loading in effect. Use RAMP DEM screen to modify. RUNNING -- DEMAND LIMITED BY LOCAL DEMAND SETPOINT Demand limit set point is less than actual demand. RUNNING -- DEMAND LIMITED BY 4-20 mA SIGNAL Demand limit is active based on external auto demand limit option. RUNNING -- DEMAND LIMITED BY CCN SIGNAL Demand limit is active based on control limit signal from CCN. RUNNING -- DEMAND LIMITED BY LOADSHED/REDLINE Demand limit is active based on LOADSHED screen set-up. RUNNING -- TEMP CONTROL HOT GAS BYPASS Hot gas bypass valve is energized description. RUNNING -- DEMAND LIMITED BY LOCAL SIGNAL Active demand limit manually overridden on MAINSTAT table. RUNNING -- TEMP CONTROL ICE BUILD MODE Chiller is running under Ice Build temperature RUNNING -- DEMAND LIMITED MOTOR LOAD CURRENT Chiller has reached 100% of Load Current Rating during normal operation. RUNNING -- DEMAND LIMITED VFD LINE CURRENT Chiller has reached 100% of Line Current Rating during normal operation. G. NORMAL ICVC FAULT STATE RUN WITH RAMP LOADING control. CTL screen. (open). See Surge prevention control. OVERRIDES PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE ADDITIONAL CAUSE]REMEDY 120 RUN CAPACITY LIMITED HIGH CONDENSER PRESSURE 120-_Condenser Pressure [VALUE] exceeded limit of [LIMIT]*. 121 RUN CAPACITY LIMITED HIGH MOTOR TEMPERATURE 121_Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*. 122 RUN CAPACITY LIMITED LOW EVAP REFRIG TEMP 122_-_Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. Check refrigerant charge. Check that optional cooler liquid line isolation valve is fully open. Check for excessive condenser flow or low chilled water flow. Check for low entering cooler temperature. Check that condenser inlet and outlet water nozzles are piped correctly. Check for waterbox division plate gasket bypass. 123 RUN CAPACITY LIMITED HIGH COMPRESSOR LIFT 123-_Surge Prevention Override: Lift Too High For Compressor Check for high condenser water temperature low suction temperature. Check for high Evaporator or Condenser approaches. Check surge prevention parameters in OPTIONS screen. 124 RUN CAPACITY LIMITED MANUAL GUIDE VANE TARGET 124_Run Capacity Limited: Manual Guide Vane Target. Target Guide Vane Position has been forced in the COMPRESS screen. Select and RELEASE force to return to normal (automatic) operation. 125 RUN CAPACITY LIMITED LOW DISCHARGE SUPERHEAT No Alert message. Check for oil loss or excess refrigerant charge. Verify that the valves in the oil reclaim lines are open. 126 RUN CAPACITY LIMITED HIGH RECTIFIER 126_Rectifier Temperature [VALUE] exceeded limit of [LIMIT]*. Check Rectifier Temp Override in SETUP1 screen. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid. Check for proper VFD cooling fan operation and blockage. 127 RUN CAPACITY LIMITED MANUAL SPEED CONTROL No Alert message. Chiller is not in automatic temperature 128 RUN CAPACITY LIMITED HIGH INVERTER TEMP 128-qnverter Temperature [VALUE] exceeded limit of [LIMIT]*. Check Inverter Temp Override in SETUP1 screen. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid. Check for proper VFD cooling fan operation and blockage. TEMP Check condenser water pump operation. Check for high condenser water temperatures or low flow rate. Verify that isolation valves are open. Check Cond Press Override setting in SETUP1. Check for closed valves or restriction in motor cooling lines. Check for closed refrigerant isolation valves. Check Comp Motor Temp Override setting in SETUP1. or control. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 8.3 Table 16 -- Alarm and Alert Messages (cont) H. OUT-OF-RANGE SENSOR ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE 260 SENSOR FAULT LEAVING CHILLED WATER 260-+Sensor Fault: Check Leaving Chilled Water Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 261 SENSOR FAULT ENTERING WATER 261 -+Sensor Fault: Check Entering Chilled Water Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 262 SENSOR FAULT CONDENSER 262-+Sensor Fault: Check Condenser Pressure Sensor. Check sensor wiring. Check for disconnected Check for condensation connector. or shorted wiring. in transducer 263-+Sensor Fault: Check Evaporator Pressure Sensor. Check sensor wiring. Check for disconnected Check for condensation connector. or shorted wiring. in transducer 263 SENSOR FAULT PRIMARY CAUSE CHILLED PRESSURE EVAPORATOR PRESSURE ADDITIONAL CAUSE/REMEDY 264 SENSOR FAULT COMPRESSOR TEMP BEARING 264-+Sensor Fault: Check Comp Thrust Brg Temp Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 265 SENSOR FAULT COMPRESSOR TEMP MOTOR 265-+Sensor Fault: Check Comp Motor Winding Temp Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 266 SENSOR FAULT COMP DISCHARGE 266-+Sensor Fault: Check Comp Discharge Temp Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 267 SENSOR FAULT OIL SUMP TEMP 267-+Sensor Fault: Check Oil Sump Temp Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 268 SENSOR FAULT COMP OIL PRESS DIFF 268-+Sensor Fault: Check Oil Pump Delta P Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. 269 SENSOR FAULT CHILLED WATER FLOW 269-+Sensor Fault: Check Chilled Water Delta P Sensor. Check sensor wiring and accuracy. Check for disconnected or shorted wiring. If 3ressure transducers are not installed, check for presence of resistors and jumpers on lower CCM terminal block J3. 270 SENSOR FAULT COND WATER FLOW 270-+Sensor Fault: Check Cond Water Delta P Sensor. Check sensor wiring and accuracy. Check for disconnected or shorted wiring. If 3ressure transducers are not installed, check for presence of resistors and jumpers on lower CCM terminal block J3. 271 SENSOR FAULT EVAP SATURATION TEMP 271-+Sensor Fault: Check Evap Saturation Temp Sensor. Check sensor resistance or voltage drop. Check for proper wiring. Check for disconnected or shorted wiring. TEMP 84 Table 16 -- Alarm and Alert Messages (cent) I. CHILLER PROTECTIVE LIMIT FAULTS ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE POWER PRIMARY CAUSE CAUSE/REMEDY 200 PROTECTIVE LIMIT RECTIFIER FAULT 201 PROTECTIVE LIMIT INVERTER POWER FAULT 201_lnverter Power Fault: Check VFD Status. Malfunction within VFD Power Module. Call Carrier Service. 202 PROTECTIVE LIMIT MOTOR AMPS NOT SENSED 202-_Motor Amps Not Sensed -- Average Load Current [VALUE]. Check main circuit breaker for trip. Increase Current % Imbalance in VFD CONF screen. 203 FAILURE TO START MOTOR ACCELERATION FAULT 203_Motor Acceleration Fault -- Average Load Current [VALUE]. 204 FAILURE TO STOP VFD SHUTDOWN 204_VFD Shutdown Fault: Check Inverter Power Unit. Check that inlet guide vanes are fully closed at start-up. Check Motor Rated Load Amps in VFD CONF screen. Reduce unit pressure if possible. VFD Circuit Board malfunction. Call Carrier Service. 205 PROTECTIVE LIMIT HIGH DC BUS VOLTAGE 205_High DC Bus Voltage: [VALUE] exceeded limit of [LIMIT]*. Verify phase to phase and phase to ground line voltage. Monitor AC line for high transient voltage conditions. VFD Circuit Board malfunction. Call Carrier Service. 206 PROTECTIVE LIMIT VFD FAULT 206-_VFD Fault Code: [VALUE]; Check VFD Fault Code List. See VFD Fault Code description action. 207 PROTECTIVE LIMIT HIGH CONDENSER PRESSURE 207-_High Cond Pressure trip. [VALU E] exceeded Switch Trippoint. Check Compressor Discharge High Pressure switch wiring and accuracy. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables in refrigerant. 208 PROTECTIVE LIMIT EXCESSIVE AMPS 208_Percent Load Current [VALUE] exceeded limit of [LIMIT]*. Check Motor Rated Load Amps in VFD CONF screen. Percent Load Current > 110%. Check Motor Rated Load Amps setting. 209 PROTECTIVE LIMIT LINE CURRENT IMBALANCE 209_Line Current Imbalance: Check VFD Fault History for Values. Check phase to phase and phase to ground )ower distribution bus voltage. Check Line Current % Imbalance in VFD_CONF screen. Consult power company. 210 PROTECTIVE LIMIT LINE VOLTAGE DROPOUT 210-_Single Cycle Line Voltage Dropout. Temporary loss of voltage. Disable Single Cycle Dropout in VFD CONF screen. 211 PROTECTIVE LIMIT HIGH LINE VOLTAGE 211_High Percent Line Voltage [VALUE]. Check phase to phase and phase to ground distribution bus voltage. Consult power company. 212 PROTECTIVE LIMIT LOW LINE VOLTAGE 212_Low Percent Line Voltage [VALUE]. Check phase to phase and phase to ground distribution bus voltage. Consult power company. 213 PROTECTIVE LIMIT VFD MODULE RESET 213_VFD Module Power-On Reset When Running. Temporary loss of VFD control voltage. Check VFD control power breaker, transformer and fuses. 214 PROTECTIVE LIMIT POWER LOSS 214_Control Power Loss When Running. Check phase to phase and phase to ground distribution bus voltage. Check VFD fuses. Check 24 vac power supply to ICVC. Consult power company. 215 PROTECTIVE LIMIT LOW DC BUS VOLTAGE 215-cLew DC Bus Voltage: [VALUE] exceeded limit of [LIMIT]*. Verify phase-to-phase and phase-to-ground voltage. VFD Circuit Board malfunction. Call Carrier Service. 216 PROTECTIVE LIMIT LINE VOLTAGE IMBALANCE 216-_Line Voltage Imbalance. Check VFD Fault History for Values. Check phase-to-phase and phase-to-ground distribution bus voltage. Increase Line Voltage % Imbalance in VFD CONF screen. 217 PROTECTIVE LIMIT MOTOR OVERLOAD TRIP 217-+Motor Overload Trip; Check VFD configurations, Any phase current > 106% RLA. Can result from significant load side current imbalance when running at full load. Check entering condenser water temperature and water flow rate. Check Motor Rated Load Amps in VFD CONF screen. 218 PROTECTIVE LIMIT VFD RECTIFIER OVERTEMP 218_VFD Rectifier Temp Exceeded: Check Cooling and VFD Cenfig. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage. 219 PROTECTIVE LIMIT VFD INVERTER OVERTEMP 219-_VFD Inverter Temp Exceeded: Check Cooling and VFD Cenfig. Check that VFD refrigerant isolation valves are open. Check VFD refrigerant cooling solenoid and refrigerant strainer. Check for proper VFD cooling fan operation and blockage. FAULT MOTOR 200_Rectifier Power Fault: Check VFD Status. ADDITIONAL Malfunction within VFD Power Module. Call Carrier Service. and corrective line *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 85 Table 16 -- Alarm and Alert Messaged (cont) I. CHILLER PROTECTIVE LIMIT FAULTS(cont) ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE 220 PROTECTIVE LIMIT 221 PROTECTIVE LIMIT UNUSED 222 PROTECTIVE LIMIT LINE FREQUENCY 223 LOSS OF COMMUNICATION 224 PROTECTIVE 225 PRIMARY CAUSE GROUND FAULT 220-_Ground Fault Trip; Check Motor and Current Sensors. ADDITIONAL CAUSE/REMEDY Check for condensation on motor terminals. Check motor power leads for phase to phase or phase to ground shorts. Disconnect motor from VFD and megger motor. Call Carrier Service. 221_UNUSED TRIP 222-_Line Frequency -[VALUE] exceeded limit of [LIMIT]; Check Power Supply. If operating from a generator, check generator size and speed. WITH VFD GATEWAY MODULE 223_Loss of SIO Comm with VFD Gateway: Check VFG Module and Power. Check VFD communication wiring and connectors on VFD Gateway and DPI board. Check for compatibility between ICVC and Gateway software. LIMIT VFD COMMUNICATIONS FAULT 224_Loss of DPI Comm with VFD Gateway: Check VFG to VFD Comm. Check VFD communication wiring and connectors. Check status lights on DPI Communications Interface Board. Call Carrier Service. PROTECTIVE LIMIT MOTOR CURRENT IMBALANCE Check Motor Current % Imbalance in VFD CONF screen. 226 PROTECTIVE LIMIT LINE PHASE REVERSAL 225_Motor Current Imbalance: Check VFD Fault History for Values. 226-_Line Phase Reversal: Check Line Phases. 227 PROTECTIVE LIMIT OIL PRESS SENSOR FAULT 227_Oil Pressure Delta P [VALUE] (Pump Off): Check Pump/Transducers. Check Check Check Check transducer wiring and accuracy. power supply to pump. pump operation. transducer calibration. 228 PROTECTIVE LIMIT LOW OIL PRESSURE 228-_Low Operating Oil Pressure [VALUE]: Check Oil Pump and Filter. Check Check Check Check Check Check Check Check transducer wiring and accuracy. power supply to pump. pump operation. oil level. for partially closed service valves. oil filters. for foaming oil at start-up. transducer calibration. 229 PROTECTIVE LIMIT LOW CHILLED WATER FLOW 229_Low Chilled Water Flow; Check Switch/Delta P Config & Calibration. 230 PROTECTIVE LIMIT LOW CONDENSER WATER FLOW 230-_Low Condenser Water Flow; Check Switch/Delta P Config & Calibration. 231 PROTECTIVE LIMIT HIGH DISCHARGE Perform pump control test. Check optional transducer calibration and wiring. Check Evaporator Refrigerant Temperature sensor. Check chilled water valves. Check for evaporator saturation temperature < 34 deg. F if not in Pumpdown Lockout mode. Place unit in Pumpdown mode before removing charge. Perform pump control test. Check optional transducer calibration and wiring. Check condenser water valves. Check for condenser pressure > 130 PSlG. Check for closed compressor discharge isolation valve. Check if chiller was operating in surge. Check sensor resistance or voltage drop. Check for proper wiring. Check for proper condenser flow and temperature. Check compressor discharge isolation valve. Check for proper inlet guide vane and optional diffuser actuator operation. 232 PROTECTIVE LIMIT LOW REFRIGERANT TEMP TEMP 231_Comp Discharge Temp [VALUE] Exceeded Limit of [LIMIT]*. 232_Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. Reverse connections to circuit breaker. of any two line conductors Check for proper refrigerant charge. Check float valve operation. Check for closed condenser liquid line isolation valve. If problem occurs at high load, check for low condenser pressure which causes inadequate flasc orifice differential pressure. Check for proper water flow and temperature. Confirm that condenser water enters bottom row of condenser tubes first. Check Evaporator Refrigerant Temperature sensor. Check for division plate gasket bypass. Check for fouled tubes. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 86 Table 16 -- Alarm and Alert Messages (cent) I. CHILLER PROTECTIVE LIMIT FAULTS(cent) ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY 233 PROTECTIVE LIMIT HIGH MOTOR TEMPERATURE 233->Comp Motor Winding Temp [VALUE] exceeded limit of [LIMIT]*. 234 PROTECTIVE LIMIT HIGH BEARING TEMPERATURE 234_Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*. 235 PROTECTIVE LIMIT HIGH CONDENSER PRESSURE 235_Condenser Pressure [VALUE] exceeded limit of [LIMIT]*. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check transducer wiring and accuracy. 236 PROTECTIVE LIMIT COMPRESS SPEED 236_Compressor Surge: Check condenser water temp and flow. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check surge prevention parameters in OPTIONS screen. Increase VFD Increase Step in SETUP2. Check VFD Minimum Speed in SETUP2 screen. 237 PROTECTIVE LIMIT SPARE SAFETY DEVICE 237_Spare Spare safety input has tripped or factory installed jumper is not present on Terminal Block 1 (TB1). 238 PROTECTIVE LIMIT EXCESSIVE SURGE 238->Compressor Surge: Check condenser water temp and flow. Check for high condenser water temperatures, low water flow, fouled tubes. Check for division plate/gasket bypass. Check for noncondensables. Check surge prevention parameters in OPTIONS screen. Check cooling tower control settings and performance to design/selection temperatures across the entire operating range of the chiller. Check cooler approach and water flow. 239 PROTECTIVE LIMIT TRANSDUCER VOLTAGE FAULT 239-->Transducer Voltage Ref [VALUE] exceeded limit of [LIMIT]*. Check that CCM transducer voltage reference is between 4.5 v and 5.5 v. Check that pressure transducers are not shorted to ground. This fault is normally declared the first time an ICVC is powered up if it was downloaded with software when it was not connected to a CCM. Call Carrier Service. 24O PROTECTIVE LIMIT LOW DISCHARGE SUPERHEAT 240_Check Overcharge Check for oil loss or excessive refrigerant. If oil level is low, refrigerant charge may be too low resulting in ineffective oil reclaim. Excessive refrigerant charge may cause liquid carryover into compressor. Check calibration of evaporator pressure and condenser pressure sensors. Check calibration of compressor discharge tem)erature sensor. 241 PROTECTIVE LIMIT RECTIFIER OVERCURRENT 241 ->Rectifier Overcurrent Fault: Check VFD Status. Check for high water temperatures in water flow rates. 242 LOSS OF COMMUNICATION WITH CCM MODULE 242-_Loss of Communication With CCM, Check Comm. Connectors. Check wiring and control power to CCM. 243 POTENTIAL FREEZE-UP EVAP PRESS/1-EMP TOO LOW 243->Evaporator Refrig Temp [VALUE] exceeded limit of [LIMIT]*. Check for proper refrigerant charge. Check float valve operation. Check for proper fluid flow and temperature. Confirm that condenser water enters bottom row of condenser tubes first. Check Evaporator Refrigerant Temperature sensor. Check for division plate gasket bypass. Check for fouled tubes. 244 POTENTIAL FREEZE-UP COND PRESS/TEMP LOW 244->Condenser Refrig Temp [VALUE] exceeded limit of [LIMIT]*. Condenser water too cold or chiller shut down with brine below 32 F in cooler so equalization temperature in chiller approached 32 E Check condenser pressure transducer. Check refrigerant charge. SURGE/LOW COMPR TOO Safety Device. for Oil in Or of Refrigerant. Check motor sensors wiring and accuracy. Check motor cooling line and spray nozzle for proper operation, or restrictions. Check for excessive starts within a short time span. Check oil heater for proper operation. Check for low oil level, partially closed oil supply valves, or clogged oil filter. Check oil cooler refrigerant thermal expansion valves. Check for sensor wiring and accuracy. This fault can result from extended operation at low load with low water flow to the evaporator or condenser. or changes *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 87 Table 16 -- Alarm and Alert Messages (cont) I. CHILLER PROTECTIVE LIMIT FAULTS(cont) ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE 245 PROTECTIVE LIMIT HIGH VFD SPEED 246 PROTECTIVE LIMIT INVALID DIFFUSE CONFIG. 247 PROTECTIVE LIMIT DIFFUSER FAULT 248 PROTECTIVE LIMIT 249 PROTECTIVE 250 UNUSED 251 PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY 245--_Actual VFD Speed exceeded limit of Target VFD Speed + 10%. 246_Diffuser Control Invalid Configuration: Check SETUP2 Entries. Actual VFD Speed on COMPRESS screen must not exceed Target VFD Speed by more than 10%. 247-+Diffuser Position Fault: Check Guide Vane/Diffuser Actuator. Confirm that Diffuser Option in SETUP 2 screen has not been Enabled if compressor does not have a split ring diffuser. May indicate rotating stall condition. Check rotating stall transducer wiring accuracy and sealing. Check diffuser schedule and guide vane schedule in SETUP2 screen. Check for proper operation of diffuser and inlet guide vane actuators including inlet guide vane calibration. Check diffuser actuator coupling for rotational slip. Check resistor between CCM terminals J3-7 and J3-8. Check for electrical noise in CCM Diffuser Pressure wiring. Do not continue to operate com3ressor except for diagnostic purposes. SPARE TEMPERATURE #1 248-_Spare Temperature #1 [VALUE] exceeded limit of [LIMIT]*. Check Spare Temperature Enable and Spare Temperature Limit in SETUP1 Screen. LIMIT SPARE TEMPERATURE #2 249_Spare Temperature #2 [VALUE] exceeded limit of [LIMIT]*. 250-_Unused State. Check Spare Temperature Enable and Spare Temperature Limit in SETUP1 Screen. PROTECTIVE LIMIT VFD CONFIG CONFLICT 251_VFD Config Conflict (VFD Uploaded): Verify to Reset Alarm. The VFD CONF table in the Gateway does not match that which is in the ICVC. This is a normal fault if an ICVC has been uploaded with software when it was not attached to the CCM Enter VFD CONF screen and then exit VFD CONF screen by pressing EXIT then CANCEL. Re-enter the VFD CONF screen, 3ress EXIT then SAVE. Parameters stored in the Gateway will be uploaded into the ICVC. Confirm valid settings in VFD CONF screen. 252 PROTECTIVE LIMIT VFD CONFIG CONFLICT The VFD CONF table in the Gateway does not match that which is in the ICVC. 253 PROTECTIVE LIMIT GUIDE VANE CALIBRATION 252-+VFD Config Conflict VFD Downloaded): Verify to Reset Alarm. 253_Guide Vane Fault [VALUE]. Check Calibration. 254 PROTECTIVE LIMIT VFD CHECKSUM 255 PROTECTIVE LIMIT VFD DEW PREVENTION 256 PROTECTIVE LIMIT INDUCTOR OVERTEMP 257 PROTECTIVE LIMIT VFD START INHIBIT 258 UNUSED STATE POSITION UNUSED UNUSED ERROR 254_Checksum Error: Press Reset to Restore Configuration. 255-_Dew Prevention - Coolant Too Cold. Check Solenoid & Cond T. 256-+Inductor Overtemp Trip Check Temp Switch and Cooling Fans. 257_VFD Start Inhibit: Check VFD Diagnostic Parameters 212/214. Check 25%, 50%, and 75% Guide Vane and Diffuser Load Point entries in SETUP2 screen. Enter CONTROL TEST and execute Guide Vane Calibration. Check CCM guide vane feedback terminals J4-9 and J4-10. Check guide vane feedback potentiometer. Alarm before start indicates guide vane opening is not less than 4%. Alarm running indicates guide vane position is < -1% or > 103%, or feedback voltage is < .045 or > 3.15 VDC. Actual VFD checksum does not match calculated value. VFD COLDPLATE TEMP is too close to dew _oint based on VFD ENCLOSURE TEMP and RELATIVE HUMIDITY in POWER screen. Check for moisture in VFD enclosure. Check Humidity Sensor in CONTROLS TEST. Check for contamination on CCM J3-7 and J3-9 Humidity Sensor. Check that VFD refrigerant cooling modulating valve is closing. Check for cooling fan air flow obstructions. The VFD Start Inhibit is derived from the Alarm bit being set in the VFD. The conditions causing the alarm must be corrected in the VFD to enable subsequent starts and operation. See VFD parameters 212/214. 258_Unused. *[LIMIT] is shown on the ICVC as the temperature, pressure, volta e, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 88 Table 16 -- Alarm and Alert Messages (cont) I. CHILLER PROTECTIVE ICVC FAULT STATE LIMIT FAULTS (cont) PRIMARY MESSAGE SECONDARY MESSAGE 259 PROTECTIVE LIMIT CCN OVERRIDE 282 PROTECTIVE LIMIT 283 PROTECTIVE LIMIT 284 PRIMARY CAUSE STOP ADDITIONAL CAUSE/REMEDY 259_CCN Emergency/ Override Stop. CCN has signaled the chiller to stop.This fault must be manually reset from the default screen of the ICVC. INVALID VFD CONFIG 282-+Line Frequency [VALUE] Exceeded Configuration Range. INVALID VFD CONFIG 283_Compressor 100% Speed Config Ranges: 50=Hz 45-52; 60 Hz=55-62. LINE FREQUENCY in POWER screen must be maintained between 45-52 Hz if LINE FREQ=60Hz? is set to NO(50 Hz). LINE FREQUENCY must be maintained between 55-62 Hz if LINE FREQ=60Hz? is set to YES (60 Hz). COMPRESSOR 100% SPEED in VFD CONF screen must be set between 45-52 Hz [{ LINE FREQ=60Hz? is set to NO(50 Hz). COMPRESSOR 100% SPEED must be set between 55-62 Hz if LINE FREQ=60Hz? is set to YES (60 Hz). VFD GATEWAY COMPATIBILITY CONFLICT 284_VFD Gateway Compatibility Conflict: Check VFG/ VFD Versions. VFD Gateway and VFD software versions are not compatible. Call Carrier Service. 285 VFD GATEWAY COMPATIBILITY CONFLICT 285-_VFD Gateway Compatibility Conflict: Check VFG/ ICVC Versions. VFD Gateway and ICVC software versions are not compatible. Call Carrier Service. 286 PROTECTIVE INVERTER OVERCURRENT 286_lnverter Overcurrent Fault: Check VFD Status. Check for high entering water temperature or low condenser water flow. Check current settings in VFD CONF screen. LIMIT *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. J. CHILLER ALERTS ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE 140 SENSOR ALERT LEAVING COND WATER TEMP 141 SENSOR ALERT ENTERING COND WATER TEMP 142 LOW OIL PRESSURE CHECKOILFI_ER ALERT 143 AUTORESTART PENDING LINECURRENT IMBALANCE 144 AUTORESTART PENDING LINEVOLTAGE DROPOUT 145 AUTORESTART PENDING HIGH LINE VOLTAGE 146 AUTORESTART PENDING LOW LINE VOLTAGE 147 AUTORESTART PENDING VFD MODULE RESET 148 AUTORESTART PENDING POWER LOSS 149 SENSOR ALERT HIGH DISCHARGE 150 SENSOR ALERT HIGH BEARING TEMPERATURE TEMP ADDITIONAL CAUSE/REMEDY 140-_Sensor Fault: Check Leaving Cond Water Sensor. 141_Sensor Fault: Check Entering Cond Water Sensor. 142_Low Oil Pressure Alert. Check Oil Filter. Check sensor resistance Check for proper wiring. 143-_Line Current Imbalance: Check VFD Fault History for Values. 144-+Single Cycle Line Voltage Dropout. Power loss has been detected in any phase. Chiller automatically restarting. 145_High Percent Line Voltage [VALUE]. 146_Low Percent Line Voltage [VALUE]. 147->VFD Module Power-On Reset When Running. Check phase )ower. 148_Control Power-Loss When Running. 149_Comp Discharge Temp [VALUE] Exceeded Limit of [LIMIT]*. Check 24 vac control power supply to ICVC. 150_Comp Thrust Brg Temp [VALUE] exceeded limit of [LIMIT]*. Check Check Check Check Check Check Check Check Check Check Check Check Check or voltage drop. sensor resistance or voltage drop. for proper wiring. for partially or closed shut-off valves. oil filter. oil pump and power supply. oil level. for foaming oil at start-up. transducer wiring and accuracy. A drop in line voltage has been detected within 2 voltage cycles. Chiller automatically restarting if Auto Restart is enabled in OPTIONS screen. to phase and phase to ground line Check phase to phase and phase to ground line )ower. VFD Module has detected a hardware fault due to electrical noise, power loss or software and has reset. Chiller automatically restarting. Check for power loss and sources of electromagnetic interference. Check sensor resistance or voltage drop. Check for proper wiring. Check for proper inlet guide vane and optional diffuser actuator operation. Check for proper condenser flow and temperature. Check for high lift or low load. Check for fouled tubes or noncondensables in the chiller. sensor resistance or voltage drop. for proper wiring. for partially closed service valves. oil cooler TXV. oil level and oil level. *[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 89 Table 16 -- Alarm and Alert Messages (cont) J. CHILLER ALERTS (cont) ICVC FAULT STATE PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE 151 CONDENSER PRESSURE ALERT PUMP RELAY ENERGIZED 151_High Condenser Pressure [VALUE]: Pump Energized to Reduce Pressure. Check sensor wiring and accuracy. Check condenser flow and water temperature. Check for fouled tubes. This alarm is not caused by the High Pressure Switch. 152 RECYCLE ALERT EXCESSIVE STARTS 152_Excessive starts, Chiller load is too low to keep compressor on line and there has been more than 5 starts in 4 hours. Increase chiller load, adjust hot gas bypass, increase RECYCLE RESTART DELTA T from SETUP1 Screen. 153 no message: ALERT only no message; ALERT only 153_Lead/Lag DisabledConfig: Duplicate Chiller Address. Illegal chiller address configuration in Lead/Lag screen. Both chillers require a different address. 154 POTENTIAL FREEZE=UP COND PRESS/TEMP TOO LOW 154_Condenser )revention. The condenser pressure transducer is reading a 3ressure that could freeze the condenser tubes. Check for condenser refrigerant leaks. Check fluid temperature. Check sensor wiring and accuracy. Place the chiller in PUMPDOWN mode if the vessel is evacuated. 155 OPTION SENSOR FAULT REMOTE RESET SENSOR 155-_Sensor Fault/Option Disabled: Remote Reset Sensor. Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4. 156 OPTION SENSOR FAULT AUTO CHILLED WATER RESET 156_-_Sensor Fault/Option Disabled: Auto Chilled Water Reset. Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J5. 157 OPTION SENSOR FAULT AUTO DEMAND LIMIT INPUT 157-_Sensor Fault/Option Disabled: Auto Demand Limit Input. Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J5. 158 SENSOR ALERT SPARE TEMPERATURE #1 158_-_Spare Temperature 1 [VALUE] exceeded limit of [LIMIT]*. Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4. Check Spare Temp #1 Limit in SETUP1 screen. 159 SENSOR ALERT SPARE TEMPERATURE #2 Check sensor resistance or voltage drop. Check for proper wiring to CCM connector J4. Check Spare Temp #2 Limit in SETUP1 screen. 161 LOSS OF COMMUNICATION WITH WSM 159_Spare Temperature 2 [VALUE] exceeded limit of [LIMIT]*. 161_-_WSM Cool Source -Loss of Communication. 162 SENSOR ALERT EVAPORATOR APPROACH 162-_ Evaporator Approach [VALUE] Exceeded Limit of [LIMIT]*. Check that refrigerant charge level is adequate, waterbox division plate gaskets are sealing, evaporator tubes are not fouled and that oil reclaim system is working. Check sensor resistance or voltage drop. Check for proper wiring. Check Evap Approach Alert setting in SETUP1 screen. 163 SENSOR ALERT CONDENSER 163-_Condenser Approach [VALUE] Exceeded Limit of [LIMIT]*. Check sensors resistance or voltage drop. Check for proper wiring. Check Cond Approach Alert setting in SETUP1 screen. Check for noncondensable gas in the condenser. Check that the condenser tubes are not fouled. 164 VFD SPEED ALERT LOW VFD SPEED 164_Actual VFD Speed exceeded limit of Target VFD Speed -10%. Actual VFD Speed on COMPRESS screen must be at least 90% of Target VFD Speed. 165 AUTORESTART PENDING LOW DC BUS VOLTAGE 165_Low DC Bus Voltage: [VALUE] Exceeded Limit of [LIMIT]*. Verify phase to phase and phase to ground line voltage. 166 AUTORESTART PENDING HIGH DC BUS VOLTAGE 166_High DC Bus Voltage: [VALUE] Exceeded Limit of [LIMIT]*. Verify phase to phase and phase to ground line voltage. Monitor AC line for high transient voltage conditions. 167 SYSTEM ALERT HIGH DISCHARGE 167_Comp Discharge Temp [VALUE] exceeded limit of [LIMIT]*. Check sensor resistance or voltage drop. Check for proper wiring. Check for excessive starts. Check Comp Discharge Alert setting in SETUP1 screen. 168 SENSOR ALERT HUMIDITY INPUT RECYCLE APPROACH SENSOR TEMP recycle freeze up ADDITIONAL Check Check (Water Check CAUSE/REMEDY settings in WSMDEFME screen. CCN communications link with WSM System Manager) Module. Supervisory Part of WSM. 168-_Sensor Fault: Check Check humidity sensor wiring on CCM connecHumidity Sensor Input Sensor. tots J3 and J5. Check Humidity Sensor Input in Controls Test. *[LIMIT] is shown on the ICVC as the temperature, pressure, volta e, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. 90 Table 17 -- Fault Code Descriptions and Corrective Actions Fault Type indicates if the fault is: 1 -- Auto-resettable 2 -- Nomresettable 3User-configurable 4 -- Normal Fault VFD FAULT CODE FAULT TYPE DESCRIPTION ACTION ICVC FAULT STATE 2 Auxiliary Input 1 Input is open. Check remote wiring. 3 Power Loss 1, 3 DC bus voltage remained below 85% of nominal for longer than Power Loss Time (185). Enable/disable with Fault Config 1 (238). Monitor the incoming AC line for low voltage or line power interruption. 215 4 UnderVoltage DC bus voltage fell below the minimum value of 407V DC at 400/480V input Enable/disable with Fault Config 1(233). Monitor the incoming AC line for low voltage or )ower interruption. 215 5 OverVoltage DC bus voltage exceeded maximum value. Monitor the AC line transient conditions. be caused by motor decel time or install 205 6 Current reg saturated for > timeout 7 Motor Overload 8 Invtr Base Temp 1 Base temperature 9 Invtr IGBT Temp 1 12 HW OverCurrent 13 1,3 1 1, 3 for high line voltage or Bus overvoltage can also regeneration. Extend the dynamic brake option. 206 Internal electronic overload trip. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by Motor NP FLA (42). 217 Check for proper temperature coolant. and flow rate of 219 Output transistors have exceeded their maximum operating temperature, Check for proper temperature coolant. and flow rate of 219 The drive output current has exceeded the hardware current limit, Check programming. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess cu rrent. 286 Ground Fault 1 A current path to earth ground in excess of 7% of drive rated amps has been detected at one or more of the drive output termF nals. Check the motor and external wiring to the drive output terminals for a grounded condition. 220 24 Decel Inhibit 3 The drive is not following a commanded deceleration because it is attempting to limit bus voltage. 1. Verify input voltage is within drive specified limits. 2. Verify system ground impedance follows proper grounding techniques. 3. Disable bus regulation and/or add dynamic brake resistor and/or extend deceleration time. 204 25 OverSpeed Limit 1 Functions such as slip compensation or bus regulation have attempted to add an output frequency adjustment greater than that programmed in Overspeed Limit (83). Remove excessive load or overhauling condF tions or increase Overspeed Limit (83). 206 29 Analog In Loss 1,3 An analog input is configured to fault on 1. Check parameters. signal loss. A signal loss has occurred. 2. Check for broken/loose connections Configure with Anlg In 1,2 Loss (324, 327). inputs. Enable/disable 1 with Fault Config 1 (238). exceeded limit. 206 at 33 Auto Rstrt Tries 3 Drive unsuccessfully attempted to reset a Correct the cause of the fault and manually fault and resume running for the proclear. grammed number of Auto Rstrt Tries (174). Enable/disable with Fault Config 1 (238). 206 35 Current FBK Lost 4 The magnitude of motor current feedback Verify connection of current feedback device was less than 5% of the configured Motor and motor terminals. If fault repeats replace Nameplate Amps for the time configured in current feedback devices and/or power supply. the Motor Imbalance Time. Detection of this fault is disabled when the Motor Imbalance Time is set to the maximum value of 10.0 seconds. 206 36 SW OverCurrent The drive output current has exceeded the software current, Check for excess load, improper DC boost setting. DC brake volts set too high. 286 37 Motor I Imbalance Phase current displayed in Imbalance Display (221) > percentage set in Imbalance Limit (49) for time set in Imbalance Time (50). Clear fault. 225 1 LEGEND DPI/I/O EPROM FLA IGBT NP ------ Drive Peripheral Interface Inputs/Outputs Erasable, Programmable, Read-Only Full Load Amps Insulated Gate Bipolar Transistor Nameplate 91 Table 17 -- Fault Code Descriptions and Corrective Actions (cont) Fault Type indicates if the fault is: 1 -- Auto-resettable 2 -- Nomresettable 3 -- User-configurable 4 -- Normal Fault VFD FAULT CODE FAULT TYPE 38 Phase U to Grnd 39 Phase V to Grnd 40 Phase W to Grnd 41 Phase UV Short 42 Phase VW Short 43 Phase UW Short 48 DESCRIPTION ACTION ICVC FAULT STATE 22O A phase-to-ground fault has been detected between the drive and motor in this phase. • Check the wiring between the drive and motor. 2. Check motor for grounded phase. 3. Replace drive• Excessive current has been detected between these two output terminals• • Check the motor and drive output terminal wiring for a shorted condition• 2. Replace drive• 246 Params Defaulted The drive was commanded values to EPROM. • Clear the fault or cycle power to the drive• 2. Program the drive parameters as needed. 206 63 Shear Pin 3 Programmed Current Lint Val (148) has been exceeded. Enabled/disable with Fault Config 1 (238)• Check load requirements (148) setting. 206 64 Drive OverLoad Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded• Reduce load or extend Accel Time (140)• 6g DB Resistor Out of Range Port 1-5 Net Loss 71- 75 to write default and Current Lmt Val 286 206 The network card connected to DPI port stopped communicating. The fault code indicates the offending port number (71 = port 1, 72 = port 2, etc.). • Check communication board for proper connection to external network. 2. Check external wiring to module on port. 206 76 Peripheral Fault at DPI Port 6 77 IR Volts Range The drive autotuning default is Calculate, and the value calculated for IR Drop Volts is not in the range of acceptable values. Re-enter motor nameplate data. 206 78 FluxAmpsRef The value for flux amps determined by the autotune procedure exceeds the programmed Motor NP FLA (42). • Reprogram Motor NP FLA (42) with the correct motor nameplate value. 2. Repeat Autotune (61). 206 7g Excessive Load Motor did not come up to speed in the allot• Uncouple load from motor. ted time. 2. Repeat Autotune (61). 206 80 AutoTune Aborted The autotune procedure was canceled by the user. Restart procedure. 206 81- 85 Port 1-6 DPI Loss DPI port stopped communicating• • If module was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, modules, Main Control board or complete drive as required• 2. Check OIM connection• 206 Rang 206 An attached peripheral with control capabilities via Logic Source Sel (89) (or OIM control) was removed. The fault code indicates the offending port number (81 = port 1, etc.). 86 DPI Port 6 Communication Loss 87 Autotune: Ixo too Ixo voltage calculated from motor namelarge 4 )late data is too high. Parameter Chksum 2 The checksum read from the board does not match the checksum calculated• Re-enter motor nameplate data. 206 • Restore defaults. 2. Reload user set if used. 206 101 UserSetl 206 UserSet2 Chksum 2 The checksum read from the user set does not match the checksum calculated• Re-save user set. 102 103 104 UserSet3 Chksum 2 Pwr Brd Chksuml The checksum read from the EPROM does not match the checksum calculated from the EPROM data. Clear the fault or cycle power to the drive• 206 105 Pwr Brd Chksum2 The checksum read from the board does not match the checksum calculated• • Cycle power to the drive• 2. If problem persists, replace drive• 206 100 Chksum 2 206 LEGEND DPI/I/O EPROM FLA IGBT NP ------ Drive Peripheral Interface Inputs/Outputs Erasable, Programmable, Read-Only Full Load Amps Insulated Gate Bipolar Transistor Nameplate 92 Table 17 -- Fault Code Descriptions and Corrective Actions (cont) Fault Type indicates if the fault is: 1 -- Auto-resettable 2 -- Non-resettable 3User-configurable 4 -- Normal Fault VFD FAULT CODE FAULT TYPE DESCRIPTION 106 Incompat MCB-PB 2 Drive rating information stored on the 3ower board is incompatible with the Main Control board. 107 Replaced MCB-PB k Main Control board was replaced and 3arameters were not programmed, I/O Board Check Sum Non-Resettable 109 ACTION 110 I/O Board Failure Non-Resettable 121 Loss of communication 122 I/O Board Comm Loss k I/O Board Fail 2O0 Inverter Dsat u,v,w High current was detected in an IGBT. 201 205 206 207 208 to I/O board, 206 206 1, Verify proper motor data is entered. 2. Reduce current limit. 286 Inverter Unused Bit 4 Inverter section of power structure hardware reported unexpected fault. Invtr Gate Kill Inverter gate kill contact is open. Rectifier Dsat High current was detected in an IGBT. Check wiring harness. 206 Rectifier IOC Rectifier overcurrent. 1, Verify proper motor data is entered. 2, Reduce current limit. 241 206 High current was detected in an IGBT. u,v,w 212 213 206 1. Cycle power, 2. If fault repeats, replace I/O board, 1. Check for loose connection in IGBT wire harness, 2 Check IGBTs. 3. Check precharge resistors and fuses. 4. Check precharge contactor. Board failure. 210 211 1. Restore defaults, 2. Reprogram parameters. 206 u,v,w 209 206 Cycle power. Inverter OverCurrent u,v,w 204 Load compatible version files into drive. 206 202 203 ICVC FAULT STATE Close gate kill contact. 1. Check for loose connection harness, 2, Check IGBTs. 201 207, 235 in IGBT wire 200 214 Reactor Temp Temperature switch in reactor opened, Check for proper temperature operation. 215 Rectifier Unused Bit 4 Rectifier section of power structure hareware reported unexpected fault. Check wiring harness. 206 216 Rectifier Ground Fault Excessive ground current measured. Check for grounded input wiring. 220 217 Rectifier Base Temp Excessive rectifier temperatured measured, Check for proper temperature coolant. and flow rate of 218 218 Rectifier IGBT Temp Excessive calculated IGBT temperature. Check for proper temperature coolant. and flow rate of 218 219 Rectifier IT Overload Short-term current rating of rectifier exceeded, Low input voltage can result in increased current load. Provide proper input voltage to the drive. 212 220 Rectifier 12T Overload Long-term current rating of rectifier exceeded, Low input voltage can result in increased current load. Provide proper input voltage to the drive. 212 221 Ride Thru Abort Input power loss timed out. 1. Verify input power and connections. 2, Check Line Sync board. 3. Check AC Line I/O board. 210 222 High AC Line Input line voltage is too high. Reduce input voltage to meet specification 480 _+10%. 223 Low DC Bus The bus voltage is too low. Verify proper input voltage. 215 224 Rctfr Over Volt The bus voltage is too high. Monitor the AC line transient conditions, be caused by motor decel time or install 205 LEGEND DP1/1/O EPROM FLA IGBT NP ------ Drive Peripheral Interface Inputs/Outputs Erasable, Programmable, Read-Only Full Load Amps Insulated Gate Bipolar Transistor Nameplate 93 and fan of for high line voltage or Bus overvoltage can also regeneration. Extend the dynamic brake option. 211 Table 17 -- Fault Code Descriptions and Corrective Actions (cont) Fault Type indicates if the fault is: 1 -- Auto-resettable 2 -- Non-resettable 3 -- User-configurable 4 -- Normal Fault VFD FAULT CODE FAULT TYPE DESCRIPTION ACTION ICVC FAULT STATE 225 Input Amp Imbalance Input phase current imbalance exceeded limits, Check for loose connection wiring. 226 Input Volt Imbalance Input voltage imbalance exceeded limits. Check for problem in input power distribution. 216 227 AC Line Lost Input power Lost. . 2. 3. 4. 210 228 Line Frequency Line frequency not in the range of 47-63 Hz. Verify connection between AC Line Sync and AC Line I/O boards. 222 229 Rectifier Checksum The checksum read from the board does not match the checksum calculated. . Restore defaults. 2. Reload user set if used. 206 230 Inverter HW Detected a Fault Bit Non Was Found 4 Inverter section of power structure hareware reported unexpected fault. Check wiring harness. 206 231 Recyifier HW Detected a Fault Bit Non Was Found 4 Rectifier portion of pwoer structure hareware reported unexpected fault. Check wiring harness. 206 232 Rctfr Not OK A fault was detected in the rectifier other than one specifically decoded, Look at rectifier parameter 243 to see fault code. 200 233 Precharge closed Precharge was closed when it should be open. . Check AUX contacts on precharge. 2. Check input bit 0 in rectifier parameter to view status of input. 3. Check wiring. 4. Check precharge resistors and fuses. 206 Precharge was open when it should be closed. . Check AUX contacts on precharge. 2. Check input bit 0 in rectifier parameter to view status of input. 3. Check wiring. 4. Check precharge resistors and fuses. 234 Precharge open Verify Check Check Verify in input power 209 proper input voltage. line sync board and fuse. AC line I/O board. connection between boards. 216 206 216 235 Rctfr Pwr Board Drive rating information stored on the )ower board is incompatible with the Main Control board. The checksum read from the board does not match the checksum calculated. Load compatible version files into drive. . Cycle power to the drive. 2. If problem persists, replace drive. 206 236 Rctfr I/O Board Loss of communication Board failure. Cycle power. . Cycle power. 2. If fault repeats, replace I/O board. 206 237 Rectifier Start Timed Out 4 The rectifier did not regulate to the desired bus voltage within the defined time. Replace rectifier power board and/or rectifier control board. 206 238 Rectified Not Logged In 4 Rectifier took too long to connect to inverter, . Check the cabling between the communications interface and the two control boards. 2. Connect one DPI device at a time to see if one of the DPI devices is causing the problem. 3. Replace the communications interface. 4. Replace the rectifier control board. 206 239 Rectifier Power Phased ACB 4 Input power is phased ACB rather than ABC. Switch two of the input power phases. 206 to I/O board. LEGEND DPI/I/O EPROM FLA IGBT NP ------ Drive Peripheral Interface Inputs/Outputs Erasable, Programmable, Read-Only Full Load Amps Insulated Gate Bipolar Transistor Nameplate 94 Table 18A -- Thermistor Temperature (F) vs. Resistance/Voltage TEMPERATURE -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 58 57 58 59 PIC III VOLTAGE DROP (V) RESISTANCE (Ohms) 4.700 4.690 4.680 4.670 4.659 4.648 4.637 4.625 4.613 4.601 4.588 4.576 4.562 4.549 4.535 4.521 4.507 4.492 4.477 4.461 4.446 4.429 4.413 4.396 4.379 4.361 4.344 4.325 4.307 4.288 4.269 4.249 4.229 4.209 4.188 4.167 4.145 4.123 4.101 4.079 3.056 4.033 4.009 3.985 3.960 3.936 3.911 3.886 3.861 3.835 3,808 3.782 3.755 3.727 3.700 3.672 3.644 3.617 3.588 3.559 3.530 3.501 3.471 3.442 3.412 3.382 3.353 3.322 3.291 3.260 3.229 3.198 3.167 3.135 3.104 3.074 3.042 3.010 2.978 3.946 2.914 2.882 2.850 2.819 2.788 98,010 94,707 91,522 88,449 85,486 82,627 79,871 77,212 74,648 72,175 69,790 67,490 65,272 63,133 61,070 59,081 57,162 55,311 53,526 51,804 50,143 48,541 46,996 45,505 44,066 42,679 41,339 40,047 38,800 37,596 36,435 35,313 34,231 33,185 32,176 31,202 30,260 29,351 28,473 27,624 26,804 26,011 25,245 24,505 23,789 23,096 22,427 21,779 21,153 20,547 19,960 19,393 18,843 18,311 17,796 17,297 16,814 16,346 15,892 15,453 15,027 14,614 14,214 13,826 13,449 13,084 12,730 12,387 12,053 11,730 11,416 11,112 10,816 10,529 10,250 9,979 9,717 9,461 9,213 8,973 8,739 8,511 8,291 8,076 7,868 TEMPERATURE (F) 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 PIC III VOLTAGE DROP (V) RESISTANCE (Ohms) 2.756 2.724 2.692 2.660 2.628 2.596 2.565 2.533 2.503 2.472 2.440 2.409 2.378 2.347 2.317 2.287 2.256 2.227 2.197 2.167 2.137 2.108 2.079 2.050 2.021 1.993 1.965 1.937 1.989 1.881 1.854 1.827 1.800 1.773 1.747 1.721 1.695 1.670 1.644 1.619 1.595 1.570 1.546 1.523 1.499 1.476 1.453 1.430 1.408 1.386 1.364 1.343 1.321 1.300 1.279 1.259 1.239 1.219 1.200 1.180 1.161 1.143 1.124 1.106 1.088 1.070 1.053 1.036 1.019 1.002 0.986 0.969 0.953 0.938 0.922 0.907 0.893 0.878 0.864 0.849 0.835 0.821 0.808 0,795 0.782 7,665 7,468 7,277 7,091 6,911 6,735 6,564 6,399 6,238 6,081 5,929 5,781 5,637 5,497 5,361 5,229 5,101 4,976 4,855 4,737 4,622 4,511 4,403 4,298 4,196 4,096 4,000 3,906 3,814 3,726 3,640 3,556 3,474 3,395 3,318 3,243 3,170 3,099 3,031 2,964 2,898 2,835 2,773 2,713 2,655 2,597 2,542 2,488 2,436 2,385 2,335 2,286 2,239 2,192 2,147 2,103 2,060 2,018 1,977 1,937 1,898 1,860 1,822 1,786 1,750 1,715 1,680 1,647 1,614 1,582 1,550 1,519 1,489 1,459 1,430 1,401 1,373 1,345 1,318 1,291 1,265 1,240 1,214 1,190 1,165 9.5 TEMPERATURE (F) 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 Drop PIC III VOLTAGE DROP (V) 0.769 0.756 0.744 0.731 0.719 0.707 0.696 0.684 0.673 0.662 0.651 0.640 0.630 0.619 0.609 0.599 0,589 0.579 0.570 0.561 0.551 0.542 0.533 0.524 0.516 0.508 0.499 0.491 0,484 0.476 0.468 0.460 0.453 0.445 0,438 0,431 0,424 0.418 0.411 0,404 0.398 0.392 0.385 0.379 0.373 0.367 0.361 0.356 0.350 0.344 0.339 0.333 0.328 0.323 0.318 0.313 0.308 0.304 0.299 0.294 0.290 0.285 0.281 0.277 0.272 0.268 0.264 0.260 0.256 0.252 0.248 0.245 0.241 0.237 0.234 0.230 0.227 0.224 0.220 0.217 0.214 RESISTANCE (Ohms) 1,141 1,118 1,095 1,072 1,050 1,029 1,007 986 965 945 925 906 887 868 850 832 815 798 782 765 75O 734 719 7O5 690 677 663 650 638 626 614 602 591 581 570 561 551 542 533 524 516 5O8 501 494 487 48O 473 467 461 456 45O 445 439 434 429 424 419 415 410 4O5 401 396 391 386 382 377 372 367 361 356 35O 344 338 332 325 318 311 3O4 297 289 282 Table 18B -- Thermistor Temperature TEMPERATURE (c) -33 -32 -31 -30 -29 -28 -27 -26 -25 -24 -23 -22 -21 -20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 --8 -7 -6 -6 -4 --3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2O 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 PIC III VOLTAGE DROP (V) 4.722 4.706 4.688 4.670 4.650 4.630 4.608 4.586 4.562 4.538 4.512 4.486 4.458 4.429 4.399 4.368 4.336 4.303 4.269 4.233 4.196 4.158 4.119 4.079 4.037 3.994 3.951 3.906 3.861 3.814 3.765 3.716 3.667 3.617 3.565 3.512 3.459 3.406 3.353 3.298 3.242 3.185 3.129 3.074 3.016 2.959 2.901 2.844 2.788 2.730 2.672 2.615 2.559 2.503 2.447 2.391 2.335 2.280 2.227 2.173 2.120 2.067 2.015 1.965 1.914 1.865 1.816 1.768 1.721 1.675 1.629 RESISTANCE (Ohms) 106 880 100 260 94 165 88 480 83170 78125 73 580 69 250 65 205 61 420 57 875 54 555 51 450 48 536 45 807 43 247 40 845 38 592 38 476 34 489 32 621 30 866 29 216 27 633 26 202 24 827 23 532 22 313 21 163 20 079 19 058 18 094 17 184 16 325 15 515 14 749 14 026 13 342 12 696 12 085 11 506 10 959 10 441 9 949 9 485 9 044 8 627 8 231 7 855 7 499 7 161 6 840 6 536 6 246 5 971 5 710 5 461 5 225 5 000 4 786 4 583 4 389 4 204 4 028 3 861 3 701 3 549 3 404 3 266 3 134 3 008 (C) vs. Resistance/Voltage TEMPERATURE (c) 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 96 Drop PIC III VOLTAGE DROP (V) 1.585 1.542 1.499 1.457 1.417 1.377 1.338 1.300 1.263 1.227 1.192 1.158 1.124 1.091 1.060 1.029 0.999 0.969 0.941 0.913 0.887 0.861 0.835 0.811 0.787 0.764 0.741 0.719 0.698 0.677 0.657 0.638 0.619 0.601 0.583 0.566 0.549 0.533 0.518 0.503 0.488 0.474 0.460 0.447 0.434 0.422 0.410 0.398 0.387 0.376 0.365 0.355 0.344 0.335 0.325 0.316 0.308 0.299 0.291 0.283 0.275 0.267 0.260 0.253 0.246 0.239 0.233 0.227 0.221 0.215 RESISTANCE (Ohms) 2 888 2 773 2 663 2 559 2 459 2 363 2 272 2 184 2 101 2 021 1 944 1 871 1 801 1 734 1 670 1 609 1 550 1 493 1 439 1 387 1 337 1 290 1 244 1 200 1 158 1 116 1 079 1 041 1 006 971 938 906 876 836 8O5 775 747 719 693 669 645 623 6O2 583 564 547 531 516 5O2 489 477 466 456 446 436 427 419 410 4O2 393 385 376 367 357 346 335 324 312 299 285 Control Modules the ICVC. Communications between the [CVC and the CCM is accomplished through the SIO (Sensor Input/ Output) bus, which is a phone cable. The communication between the CCM and VFD is accomplished through the sensor bus, which is a 3-wire cable. Turn controller power off before servicing controls. This ensures safety and prevents &image to the controllec 2. The ICVC and CCM modules perform continuous diagnostic evaluations of the hmdware to determine its condition. Proper operation of all modules is indicated by LEDs (light-emitting diodes) located on the circuit board of the ICVC and CCM. All system operating intelligence resides in the ICVC. Some safety shutdown logic resides in the Gateway in case communications are lost between the VFD and ICVC. Outputs are controlled by the CCM and VFD as well. There is one green LED located on the CCM board, and one red LED located on the ICVC and CCM boards respectively. RED LED (Labeled as STAT) --If the red LED: • • • • 3. Blinks continuously at a 2-second interval, the module is operating properly Is lit continuously, there is a problem that requires replacing the module Is off continuously, the power should be checked Blinks 3 times per second, a software error has been discoveled and the module must be replaced on Module Power is supplied to the modules within the control panel via the 24-vac TI and T2 transformers. The transformers _u'e located within the power panel. In the power panel, TI supplies power to the compressor oil heatel: and optional hot gas bypass, and T2 supplies power to both the ICVC and CCM. T3 provides 24V power to the optiomd DataLINK TM modules. If there is no input powel, check the luses and circuit breaker If the fuse is good, check for a shorted secondary of the transformer or. if power is present to the module, replace the module. GREED LED (Labeled as COM)-These LEDs indicate the communication status between different paris of the controller and the network modules and should blink continuously. Notes If a green LED is on continuously, check the communication wiring. If a green LED is off. check the red LED operation. If the red LED is normal, check the module address switches (SWI) (Fig. 44 and 45). Confirm _dl switches _ue in OFF position. Power is connected Chiller Control DataPort TM to Plug Jl on each module. Module (CCM) (Fig 45) INPUTS -- Each input channel has 2 or 3 terminals. Refer to individual chiller wiring diagrams for the con'ect terminal numbers for a specific application. OUTPUTSOutput is 24 vac. There are 2 termimds per output. Refer to the chiller wiring diagram for a specific application for the correct terminal numbel_. Operation 1. The chiller operator monitors and modifies configurations in the microprocessor by using the 4 softkeys and MODULE PART NUMBER SOFTWARE PART NUMBER CCN INTERFACE CONNECTION DATALINK DATAPORT / We • / OR MODULE (OPTION) • m o o @ ICVC o []CB1 \ [ @ CONTRAST ADJUSTMENT / BACK OFICVC J7 SIO / J1 POWER/ CCN or \ J8 SERVICE SWl Fig 44 -- Rear of ICVC (International Chiller Visual Controller) 97 J1 24 VAC o ° © ANA' OUT SIO J6 "------.- SW2 © V/I INPUTS J5 Fig. 45 -- Chiller Control Module (CCM) Replacing Defective Processor Modules i The module replacement pan number is printed on a sm_dl label on the rear of the ICVC module. The chiller model and serial numbers tue printed on the chiller nameplate located on an exterior corner post. The proper software is factory-installed by Carrier in the replacement module. When ordering a replacement chiller visual control (ICVC) module, specify the complete replacement part number, lilll chiller model numbek and chiller serial numbel: The installer must configure the new module to the original chiller data. Follow the procedures described in the Software Configuration section on page 61. Electrical shock can cause pel,sonal injm 7. Disconnect electrical power before servicing. 3. all INSTALLATION 1. Verify the existing ICVC module is defective by using the procedure described in the Troubleshooting Guide section, page 79, and the Control Modules section, page 97. Do not select the ATTACH TO NETWORK DEVICE table if the [CVC indicates a communication failure. 2. 4. Power off the controls. 5. Remove the old ICVC. 6. Install the new ICVC module. back on. 7. The [CVC now network device. 8. Data regarding the ICVC configuration should have been recorded and saved. This data must be reconfigured into the new ICVC. If this data is not available, follow the procedures described in the Software Configuration section. If the module to be replaced is functional, configurations may also be copied manually. The &{ta sheets on pages CL-3 and CL-II _u'e provided for this purpose. Default values are shown so that only deviations from these need to be recorded. 98 If a CCN Building Supervisor or Service Tool is available, the module configuration should have already been uploaded into memory. When the new module is installed, the configuration can be downloaded from the computec Any communication wires from other chillers or CCN modules should be disconnected to prevent the new ICVC module from uploading incorrect run hours into memw 7. Record wdues for the TOTAL COMPRESSOR STARTS, SERVICE ONTIME and the COMPRESSOR ONTIME from the MAINSTAT screen on the ICVC. automatically Turn the control attaches to the power local Set the current time and &tie in the SERVICE/TIME AND DATE screen. Set the CCN Bus and Address in the SERVICE / ICVC CONFIGURATION screen. Press the alarm RESET softkey (from the default screen). Upload via Service Tool or manually reenter all non-default configuration values. (Refer to pages CL-3 through CL-II.) If the correct VFD Configuration values are displayed in the VFD_CONF table when that table is viewed, simply press EXIT then SAVE to reload all of them. Use Service Tool or manually reenter TOTAL COMPRESSOR STARTS, SERVICE ONTIME and COMPRESSOR ONTIME. [f forced using Service Tool, release the force on SERVICE ONTIME after the desired v_due has been set. 9. Perform theguidevane calibration procedure (inControl Test). Check andrecalibrate pressure transducer leadings (refertopage64).Check thattheCURRENT TIME and DATE in the TIMEAND DPI RIBBON CABLE CONNECTOR DATE screen are correct. DPI Communications Interface Board Status LEDs -- VFD status can be determined from the status LEDs on the DPI Communications Interface Board shown in Fig. 46. The DPI Board is mounted on file fiont of the VFD power module in a vertical orientation. Gateway provides SIO bus The SIO connector Status LEDsThe RS485 VFD Gateway a communication link between the CCM and ICVC to the VFD Drive Peripheral Interface (DPI) board. bus communicates with the Gateway through VFD A32. See Fig. 47. The Gateway has four status indicators on the top side of the module. DRIVE STATUS INDICATOR -- The DRIVE status indicator is on the right side of the Gateway. See Table 19. A32 TERMINAL BLOCK NUMBER STATUS INDICATOR 1 DRIVE 2 MS 3 NET A 4 NET B DESCRIPTION DPI Connection Status Module Status Serial Communication Serial Communication NOTE: If all status indicators power. Status Traffic Status are off, the Gateway is not receiving Fig. 47 -- Gateway Status LEDs IJ ,7.110 T=0 ° =°-° Ill = N RECTIFIER LED COLOR G teen Yellow Red Red Inverter Green Rectifier INTVERTER LED STATE Flashing DESCRIPTION Drive ready, but not running and no faults are present Steady Drive running, no faults are present. Flashing Steady The drive is not ready. A VFD start inhibit is in effect. An alarm condition exits. Check VFD Fault Code in ICVC VFD Flashing A fault has occurred. Check VFD Fault Code in ICVC VFD STAT screen. Steady A non-resettable Steady VFD Gate Kill circuit has opened due to a normal shutdown command or because the compressor high pressure switch has opened. This status LED combination is normal when the chiller is not running. Fig. 46- STAT screen. fault has occurred. Check VFD Fault Code in ICVC VFD STAT screen. DPI Communications 99 Interface Board Status LEDs uO Table 19 -- DRIVE Status Indicator STATE Off CAUSE Flashing Red Solid Red Orange Flashing Green Solid Green LED Table 20 STATE Off ACTION The Gateway is not powered or is not connected properly to the drive. • Securely connect the Gateway to the drive using the DPI ribbon cable. • Apply power to the drive. The Gateway is not receiving a ping message from the drive. The drive has refused an I/O connection from the Gateway. • Verify that cables are securely connected. • Cycle power to the drive. IMPORTANT: Cycle power after making the following correction: • Verify that all DPI cables on the drive are securely connected and not damaged. Replace cables if necessary. The Gateway is connected to a product that does not support Rockwell Automation DPI communications. • Check wires leading to the A32 terminal block. • Check that A32 terminal block is fully engaged. The Gateway is establishing an I/O connection to the drive or the I/O has been disabled. Normal behavior. The Gateway is properly connected and is communicating with the drive. No action required. MS STATUS second CORRECTIVE Table 21 -- NET A Status Indicator: State Definitions INDICATOR from -- -- The MS status Indicator: CAUSE CAUSE Off The module is not powered or is not properly connected to the network. • Securely connect the Gateway ribbon cable to the drive DPI board. • Attach the RS485 cable in First incoming network command not yet recognized. Gateway to the connector. • Apply power to the drive. Flashing Green Online to network, but not producing or consuming I/O information, No action required. The LED will turn solid green when communication resumes. Solid Green The module is properly connected and communicating on the network. No action required. Off indicator Solid Green is the CAUSE CORRECTIVE ACTION Gateway not receiving data over the network. • Check wires leading to A32 terminal block. • Check that A32 terminal block is fully engaged. Gateway is transmitting data. No action required. 20. Physical Data -- Tables 23A-29 and Fig. 48-57 provide additional information on component weights, compressor fits and clearances, physical and electrical &Lta, and wiring schematics for the operator's convenience during troubleshooting. Definitions CORRECTIVE ACTION Table 22 -- NET B Status Indicator: State Definitions See Table State CORRECTIVE NET B STATUS INDICATOR -- Tile NETB status indicator is the left LED on file Gateway. See Table 22. STATE the fight of the Gateway. MS Status STATE ACTION The Gateway is not )owered. • Securely connect the Gateway to the drive using the ribbon cable. • Apply power to the drive. Flashing Green The Gateway is operational. No I/O data is being transferred. Normal behavior during SIC configuration initialization 3rocess. Solid Red The Gateway is operational and transferring I/O data. No action required. Do not attempt to disconnect flanges while the machine is under pressure. Failure to relieve pressure can result in persomd injury or damage to the unit. NET A STATUS INDICATOR -- The NET A status indicator is tile third LED from the right of the Gateway. See Table 21. Before rigging the compressor, ing the power panel. 100 disconnect all wires enter- Table 23A -- Heat Exchanger Data (English) ENGLISH NUMBER OF TUBES Dry (Rigging) Weight (Ib) SIZE Cooler Condenser Cooler Only Condenser Chiller Only Refrigerant Weight (Ib) Cooler Condenser Charge Water Volume (gal) Cooler Condenser 10 11 12 142 161 180 180 200 225 2,707 2,777 2,848 2,704 2,772 2,857 290 310 330 200 200 200 34 37 40 42 45 49 15 16 17 142 161 180 180 200 225 2,968 3,054 3,141 2,984 3,068 3,173 320 340 370 250 250 250 39 43 47 48 52 57 20 21 22 200 240 282 218 266 315 3,407 3,555 3,711 3,373 3,540 3,704 345 385 435 225 225 225 48 55 62 48 55 63 30 31 32 200 240 280 218 267 315 4,071 4,253 4,445 3,694 3,899 4,100 350 420 490 260 260 260 56 64 72 56 65 74 35 36 37 200 240 280 218 267 315 4,343 4,551 4,769 4,606 4,840 5,069 400 480 550 310 310 310 61 70 80 62 72 83 40 41 42 324 364 400 370 417 463 4,908 5,078 5,226 8,039 5,232 5,424 560 630 690 280 280 280 104 112 119 110 119 129 45 46 47 324 364 400 370 417 463 5,363 5,559 5,730 5,602 5,824 6,044 640 720 790 330 330 330 112 122 130 120 130 141 50 51 52 431 485 519 509 556 602 8,713 5,940 6,083 6,090 6,283 6,464 750 840 900 400 400 400 132 143 150 147 156 165 5A 5B 50 225 241 258 ---- 5,124 5,177 5,243 500 520 550 ---- 123 126 129 ---- 55 56 57 431 485 519 509 556 602 6,257 6,517 6,682 870 940 980 490 490 490 144 156 164 161 171 182 5F 5G 5H 225 241 258 ---- 5,577 5,640 5,716 550 570 600 ---- 133 137 141 ---- 60 61 62 557 599 633 648 695 741 6,719 6,895 7,038 6,764 6,949 7,130 940 980 1020 420 420 420 168 176 183 182 191 200 65 66 67 557 599 633 648 695 741 7,392 7,594 7,759 7,682 7,894 8,102 1020 1060 1090 510 510 510 183 193 201 200 210 220 70 71 72 644 726 790 781 870 956 9,942 10,330 10,632 10,782 11,211 11,612 1220 1340 1440 780 780 780 241 259 274 267 286 305 NOTES: 1. Cooler data: based on a 150 psig, nozzle-in-head includes suction elbow, Weight does not include ---6,785 7,007 7,215 ---- 2. Condenser data: based on a condenser with standard wall tubing, 2-pass, 150 psig, nozzle-in-head waterbox with victaulic grooves. Weight includes the float valve, discharge elbow, and distribution piping. Weight does not include unit-mounted starter, isolation valves, and pumpout unit. coolerwith standard wall tubing, 2-pass, waterbox with victaulic grooves. Weight control panel, and distribution piping, compressor, 101 Table 23B -- Heat Exchanger Data (Sl) NUMBER OF TUBES Sl Dry (Rigging) Weight (kg) SIZE Condenser Only Chiller Refrigerant Cooler Weight(kg) Condenser Charge Water Cooler Volume (L) Condenser Cooler Condenser Cooler Only 10 11 12 142 161 180 180 200 225 1228 1260 1292 1227 1257 1296 132 141 150 91 91 91 129 140 151 159 170 185 15 16 17 20 21 22 142 161 180 200 240 282 180 200 225 218 266 315 1346 1385 1425 1545 1613 1683 1354 1392 1439 1530 1606 1680 145 154 168 113 113 113 148 163 178 182 197 216 156 175 197 102 102 102 182 208 235 182 208 238 30 31 32 200 240 282 218 266 315 1847 1929 2016 1676 1769 1860 159 191 222 118 118 118 212 242 273 212 246 280 35 36 37 200 240 282 218 266 315 1970 2064 2163 2089 2195 2299 181 218 249 141 141 141 231 265 303 235 273 314 40 41 42 45 46 47 324 364 400 324 364 400 366 415 464 366 415 464 2226 2303 2370 2433 2522 2599 2286 2373 2460 2541 2642 2742 254 286 313 127 127 127 394 424 450 416 450 488 290 327 358 150 150 150 424 462 492 454 492 534 50 51 52 431 485 519 507 556 602 2591 2694 2759 2762 2850 2932 340 381 408 181 181 181 500 541 568 556 591 625 5A 5B 50 225 241 258 ---- 2324 2348 2378 ---- 227 236 249 55 56 57 5F 5G 5H 431 485 519 225 241 258 507 556 602 ---- 2838 2956 3031 2530 2558 2593 3078 3178 3273 ---- 395 426 445 60 61 62 557 599 633 648 695 741 3048 3128 3192 3068 3152 3234 426 445 463 191 191 191 636 666 693 689 723 757 65 66 67 557 599 633 648 895 741 3353 3445 3519 3485 3581 3675 463 481 494 231 231 231 693 731 761 757 795 833 70 71 72 644 726 790 781 870 956 4510 4686 4823 4891 5085 5267 553 608 653 354 354 354 912 980 1037 1011 1083 1155 NOTES: 1. Cooler data: based on a cooler with standard wall tubing, 2-pass, 1034 kPa, nozzleqn-head waterbox with victaulic grooves. Weight includes suction elbow, control panel, and distribution piping. Weight does not include compressor. 466 477 488 222 222 222 249 259 272 545 591 621 609 647 689 503 519 534 2. Condenser data: based on a condenser with standard wall tubing, 2-pass, 1034 kPa, nozzle-in-head waterbox with victaulic grooves. Weight includes the float valve, discharge elbow, and distribution piping. Weight does not include unit-mounted starter, isolation valves, and pumpout unit. 102 Table 24A -- 19XRV Additional Data for Cooler Marine Water Boxes* ENGLISH COOLER FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME, 2, 1 AND 3 2, 2 PASS 3_ 1 AND 3 3, 2 PASS 4, 1 AND 3 4, 2 PASS 5, 1 AND 3 5, 2 PASS 6, 1 AND 3 6, 2 PASS 7, 1 AND 3 7, 2 PASS 8, 1 AND 3 8, 2 PASS 2, 1 AND 3 2, 2 PASS 3, 1 AND 3 3, 2 PASS 4, 1 AND 3 4, 2 PASS 5, 1 AND 3 5, 2 PASS 6, 1 AND 3 6, 2 PASS 7, 1 AND 3 7, 2 PASS 8, 1 AND 3 8, 2 PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS peig 150 150 150 150 150 150 150 150 150 150 150 150 150 150 300 300 300 300 300 300 300 300 300 300 300 300 300 300 Rigging Weight (Ib) 730 365 730 365 1888 944 2448 1223 2860 1430 3970 1720 5048 2182 860 430 860 430 2162 1552 2655 1965 3330 2425 5294 4140 6222 4952 SI Water Volume (gal) 84 42 84 42 109 54 122 61 139 69 309 155 364 182 84 42 84 42 109 47 122 53 139 58 309 146 364 161 *Add to heat exchanger data for total weights or volumes. NOTES: 1. Weight adder shown is the same for cooler and condenser of equal frame size. kPa 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 Rigging Weight (kg) 331 166 331 166 856 428 1109 555 1297 649 1801 780 2290 990 390 195 390 195 981 704 1204 891 1510 1100 2401 1878 2822 2246 Water Volume (L) 318 159 318 159 412 2O5 462 231 524 262 1170 585 1376 688 318 159 318 159 412 178 462 199 524 218 1170 553 1376 609 2, For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volumes), Table 24B -- 19XRV Additional Data for Condenser Marine Water Boxes* ENGLISH CONDENSER FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME FRAME 2, 2, 3, 3, 4, 4, 5, 5, 6, 6, 7, 7, 8, 8, 2, 2, 3, 3, 4, 4, 5, 5, 6, 6, 7, 7, 8, 8, FRAME, PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS 1 AND 3 2 PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS psig 150 150 150 150 150 150 150 150 150 150 150 150 150 150 300 300 300 300 300 300 300 300 300 300 300 300 300 300 Rigging Weight !lb) N/A 365 N/A 365 N/A 989 N/A 1195 N/A 1443 N/A 1561 N/A 1751 N/A 430 N/A 430 N/A 1641 N/A 1909 N/A 2451 N/A 4652 N/A 4559 SI Water Volume N/A 42 N/A 42 N/A 54 N/A 60 N/A 69 N/A 123 N/A 141 N/A 42 N/A 42 N/A 47 N/A 50 N/A 58 N/A 94 N/A 94 *Add to heat exchanger data for total weights or volumes. NOTES: 1. Weight adder shown is the same for cooler and condenser of equal frame size. kPa 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 1034 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 2068 Rigging Weight N/A 166 N/A 166 N/A 449 N/A 542 N/A 655 N/A 708 N/A 794 N/A 195 N/A 195 N/A 744 N/A 866 N/A 1112 N/A 2110 N/A 2068 Water Volume tL) N/A 159 N/A 159 N/A 2O5 N/A 226 N/A 262 N/A 465 N/A 532 N/A 159 N/A 159 N/A 178 N/A 190 N/A 218 N/A 386 N/A 385 2, For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volumes), 103 Table 25A -- 19XRV Motor Weights -- Standard MOTOR CODE Motors ENGLISH StatorWeight*(Ib) 60 Hz 50 Hz SI Rotor Weightt (Ib) 60 Hz 50 Hz End Bell Cover(Ib) Stator Weight* (kg) 60 Hz 50 Hz Rotor Weightt (kg) 60 Hz 50 Hz End Bell Cover(kg) BD 900 915 190 205 185 408 415 86 93 84 BE 915 965 200 220 185 415 438 91 100 84 BF 975 1000 215 230 185 442 454 98 104 84 BG BH 1000 1030 1060 230 250 185 454 481 104 113 84 1175 240 265 185 467 501 109 120 84 BJ 1105 185 501 120 -- CB 1154 1188 236 255 274 523 539 107 116 125 CC 1182 1196 243 260 274 536 542 110 118 125 CD CE 1220 1253 1258 252 270 274 553 571 114 122 125 1272 261 281 274 568 577 118 127 125 CL 1261 1328 265 284 274 572 602 120 129 125 CM 1294 1353 273 293 274 587 614 124 133 125 CN 1321 1386 280 303 274 599 629 127 137 125 CP 1343 1413 282 308 274 609 641 128 140 125 CO 1419 1522 300 336 274 644 690 136 152 125 CR 1567 274 711 152 -- 125 DB 1570 1725 324 347 236 712 782 147 157 107 DC 1580 1737 326 354 236 717 788 148 161 107 DD DE 1919 1939 2069 423 458 318 870 938 192 208 144 2089 428 463 318 880 948 194 210 144 DF 1989 2139 448 478 318 902 970 203 217 144 DG 2054 1998 473 422 318 932 906 215 191 144 DH 2099 2056 488 443 318 952 933 221 201 144 DJ 2159 2101 508 464 318 979 953 230 210 144 DK 2380 318 1080 237 -- 145 ER 2700 2770 651 701 414 1388 1415 295 341 188 EJ 2760 2890 670 701 414 1408 1474 325 341 188 EK 2760 2890 670 718 414 1442 1474 325 348 188 EL 2800 2960 685 751 414 1442 1529 334 363 188 EM 2800 2960 685 751 414 1483 1529 334 363 188 EN 2960 3110 751 801 414 1483 1597 363 386 188 EP 2960 3110 780 801 414 1515 1597 376 386 188 EO 3110 414 1411 363 -- 188 265 335 522 801 *Stator weight includes stator and shell. tRotor weight includes rotor and shaft. NOTE: When different voltage largest weightis given. 104 motors 84 have different weights the Table 25B -- 19XRV Motor Weights -- High-Efficiency MOTOR CODE Motors SI ENGLISH Stator Weight*(Ib) 60 Hz 50 Hz Rotor Weightt (Ib) 60 Hz 50 Hz End Bell Cover (Ib) StatorWeight*(kg) 60 Hz 50 Hz Rotor Weightt (kg) 60 Hz 50 Hz End Bell Cover (kg) BD 1030 1030 240 240 185 467 467 109 109 84 BE 1070 1070 250 250 185 485 485 113 113 84 BF 1120 1120 265 265 185 508 508 120 120 84 BG BH 1175 1175 1175 290 290 185 533 533 132 132 84 1175 290 290 185 533 533 132 132 84 BJ 1175 185 533 CB 1235 1290 242 255 274 560 585 110 116 125 CC 1260 1295 249 259 274 572 587 113 117 125 CD CE 1286 1305 1358 258 273 274 583 616 117 124 125 1377 265 279 274 592 625 120 127 125 CL 1324 1435 280 296 274 601 651 127 134 125 CM 1347 1455 303 298 274 611 660 137 135 125 CN 1358 1467 316 316 274 616 665 143 143 125 CP 1401 1479 329 316 274 635 671 149 143 125 CQ 1455 1479 329 329 274 660 671 149 149 125 CR 1567 274 711 DB 1950 1950 406 406 318 885 885 184 184 144 DC 1950 2025 406 429 318 885 919 184 195 144 DD DE 2150 2150 2250 536 546 318 975 1021 243 248 144 2250 550 550 318 975 1021 249 249 144 DF 2250 2380 575 567 318 1021 1080 261 257 144 DG 2250 2380 599 599 318 1021 1080 272 272 144 DH 2380 2380 604 604 318 1080 1080 274 274 144 DJ 2380 2380 614 614 318 1080 1080 279 279 144 DK 2380 318 1080 LB 1873 1939 364 389 318 850 880 165 176 144 LC 1939 2023 389 406 318 850 918 176 184 144 LD 2023 2043 406 417 318 880 927 184 189 144 LE 2043 2096 417 434 318 918 951 189 197 144 LF 2096 2133 434 444 318 927 968 197 201 144 LG 2133 2199 444 458 318 951 997 201 2O8 144 LH 2199 318 968 ER 3060 3120 701 751 414 1388 1415 318 341 188 EJ EK 3105 3180 3250 716 751 414 1408 1474 325 341 188 3250 716 768 414 1442 1474 325 348 188 EL 3180 3370 737 801 414 1442 1529 334 363 188 EM 3270 3370 737 801 414 1483 1529 334 363 188 EN 3270 3520 801 851 414 1483 1597 363 386 188 EP 3340 3520 830 851 414 1515 1597 376 386 188 EQ 3520 414 1597 290 335 614 458 851 *Stator weightincludes stator and shell. tRotor weightincludesrotor and shaft. 132 152 125 279 144 2O8 386 NOTE: When different voltage largest weight is given. 105 84 motors 144 188 have different weights the Table 26A -- 19XRV Waterbox HEAT EXCHANGER COOLER/ CONDENSER WATERBOX DESCRIPTION Cover Weights -- English (Ib) FRAME 1 Standard Nozzles Flanged COOLER/ CONDENSER HEAT EXCHANGER COOLER/ CONDENSER HEAT EXCHANGER COOLER/ CONDENSER 177 204 320 350 32O 35O NIH, 2 Pass Cover, 150 psig 185 218 320 350 32O 35O NIH, 3 Pass Cover, 150 psig 180 196 310 340 310 34O NIH Plain End Cover, 150 psig 136 136 300 300 3OO 3OO 300 300 3OO 3OO 486 MWB End Cover, 150 psig NIH, 1 Pass Cover, 300 psig 248 301 411 486 411 NIH, 2 Pass Cover, 300 psig 255 324 411 518 411 518 NIH, 3 Pass Cover, 300 psig 253 288 433 468 433 468 NIH Plain End Cover, 300 psig 175 175 400 400 4OO 4OO 400 400 4OO 4OO FRAME 4 WATERBOX DESCRIPTION Standard Nozzles FRAME 5 FRAME Flanged NIH, 1 Pass Cover, 150 psig 148 185 168 229 187 223 NIH, 2 Pass Cover, 150 psig 202 256 224 298 257 330 NIH, 3 Pass Cover, 150 psig 473 489 629 655 817 843 NIH Plain End Cover, 150 psig MWB End Cover, 150 psig 138 138 154 154 172 172 317 317 393 393 503 503 NIH, 1 Pass Cover, 300 psig 593 668 764 839 959 1035 NIH, 2 Pass Cover, 300 psig 594 700 761 878 923 1074 NIH, 3 Pass Cover, 300 psig 621 656 795 838 980 1031 NIH/MWB End Cover, 300 psig 569 569 713 713 913 913 FRAME 7 COOLER WATERBOX DESCRIPTION Standard Nozzles Flanged Flanged Standard Nozzles Flanged 329 441 329 NIH, 2 Pass Cover, 150 psig 426 541 426 541 NIH, 3 Pass Cover, 150 psig 1202 1239 1113 1171 315 315 315 315 789 789 7O3 7O3 NIH, 1 Pass Cover, 300 psig 1636 1801 1472 1633 NIH, 2 Pass Cover, 300 psig 1585 1825 1410 1644 NIH, 3 Pass Cover, 300 psig 1660 1741 1496 1613 NIH/MWB End Cover, 300 psig 1451 1451 1440 1440 FRAME 8 COOLER WATERBOX DESCRIPTION Standard Nozzles Flanged Flanged FRAME 7 CONDENSER NIH, 1 Pass Cover, 150 psig NIH Plain End Cover, 150 psig MWB End Cover, 150 psig Standard Nozzles 6 Standard Nozzles 441 FRAME 8 CONDENSER Standard Nozzles Flanged NIH, 1 Pass Cover, 150 psig 417 494 417 NIH, 2 Pass Cover, 150 psig 531 685 531 685 NIH, 3 Pass Cover, 150 psig 1568 1626 1438 1497 NIH Plain End Cover, 150 psig MWB End Cover, 150 psig 404 404 404 404 1339 1339 898 898 NIH, 1 Pass Cover, 300 psig 2265 2429 1860 2015 NIH, 2 Pass Cover, 300 psig 2170 2499 1735 2044 NIH, 3 Pass Cover, 300 psig 2273 2436 1883 1995 NIH/MWB End Cover, 300 psig 1923 1923 1635 1635 LEGEND NIH -MWB -- FRAME 3 Standard Flanged Nozzles NIH, 1 Pass Cover, 150 psig MWB End Cover, 300 psig HEAT EXCHANGER FRAME 2 Standard Nozzles Flanged 494 NOTE:Weightfor NIH 2-Pass Cover, 150 psigisincludedinthe exchanger weights showninTable 23A. Nozzle-lmHead Marine Waterbox 106 heat Table 26B -- 19XRV Waterbox HEAT EXCHANGER COOLER/ CONDENSER WATERBOX DESCRIPTION Cover Weights -- Sl (kg) FRAME1 Standard Nozzles Flanged HEAT EXCHANGER COOLER/ CONDENSER HEAT EXCHANGER COOLER/ CONDENSER 93 145 159 145 159 NIH, 2 Pass Cover, 1034 kPa 84 99 145 159 145 159 NIH, 3 Pass Cover, 1034 kPa 82 89 141 154 141 154 NIH Plain End Cover, 1034 kPa 62 62 136 136 136 136 136 136 136 136 MWB End Cover, 1034 kPa NIH, 1 Pass Cover, 2068 kPa 112 137 186 220 186 22O NIH, 2 Pass Cover, 2068 kPa 116 147 186 235 186 235 NIH, 3 Pass Cover, 2068 kPa 115 131 196 212 196 212 79 79 181 181 181 181 181 181 181 181 FRAME 5 FRAME4 WATERBOX DESCRIPTION Standard Nozzles Flanged Standard Nozzles FRAME 6 Flanged Standard Nozzles Flanged NIH, 1 Pass Cover, 1034 kPa 67 84 76 104 85 101 NIH, 2 Pass Cover, 1034 kPa 92 116 102 135 117 150 NIH, 3 Pass Cover, 1034 kPa 215 222 285 297 371 382 63 63 70 70 78 78 MWB End Cover, 1034 kPa NIH, 1 Pass Cover, 2068 kPa 144 144 178 178 228 228 269 303 347 381 435 469 NIH, 2 Pass Cover, 2068 kPa 269 318 345 398 419 487 NIH, 3 Pass Cover, 2068 kPa 282 298 361 380 445 468 NIH/MWB End Cover, 2068 kPa 258 258 323 323 414 414 NIH Plain End Cover, 1034 kPa FRAME 7 COOLER WATERBOX DESCRIPTION Standard Nozzles Flanged FRAME 7 CONDENSER Standard Nozzles Flanged NIH, 1 Pass Cover, 1034 kPa 149 200 149 2OO NIH, 2 Pass Cover, 1034 kPa 193 245 193 245 NIH, 3 Pass Cover, 1034 kPa 545 562 5O5 531 NIH Plain End Cover, 1034 kPa 143 143 143 143 MWB End Cover, 1034 kPa NIH, 1 Pass Cover, 2068 kPa 358 358 319 319 742 817 668 741 NIH, 2 Pass Cover, 2068 kPa 719 828 640 746 NIH, 3 Pass Cover, 2068 kPa 753 790 679 732 NIH/MWB End Cover, 2068 kPa 658 658 653 653 FRAME 8 COOLER WATERBOX DESCRIPTION Standard Nozzles Flanged FRAME 8 CONDENSER Standard Nozzles Flanged NIH, 1 Pass Cover, 1034 kPa 189 224 189 224 NIH, 2 Pass Cover, 1034 kPa 241 311 241 311 NIH, 3 Pass Cover, 1034 kPa 711 738 652 679 NIH Plain End Cover, 1034 kPa 183 183 183 183 MWB End Cover, 1034 kPa NIH, 1 Pass Cover, 2068 kPa 607 607 407 407 1027 1102 844 914 NIH, 2 Pass Cover, 2068 kPa 984 1134 787 927 NIH, 3 Pass Cover, 2068 kPa 1031 1105 854 905 872 872 742 742 NIH/MWB End Cover, 2068 kPa LEGEND NIH -MWB -- Flanged 80 MWB End Cover, 2068 kPa COOLER/ CONDENSER FRAME 3 Standard Nozzles NIH, 1 Pass Cover, 1034 kPa NIH Plain End Cover, 2068 kPa HEAT EXCHANGER FRAME 2 Standard Nozzles Flanged NOTE:Weightfor NIH 2-Pass Cover, 1034 kPa is included in the heatexchanger weights showninTable 23B. Nozzle-In-Head Marine Waterbox 107 Table 27 -- Optional Pumpout Electrical Data PUMPOUT UNIT 19XR04026501 VOLTS-PH-Hz 19XR04026501 MAX RLA LRA 208/230-3-60 15.8 105 208/230-3-50 15.8 105 19XR04026502 460-3-60 7.8 52 19XR04026503 400-3-50 7.8 52 LEGEND LRA RLA --- Locked Rotor Amps Rated Load Amps Table 28 -- Additional Miscellaneous FRAME 2 COMPRESSOR ITEM CONTROL CABINET OPTIONAL DISCHARGE OPTIONAL COOLER UNIT-MOUNTED ISOLATION VALVE FRAME 3 COMPRESSOR Ib 34 kg 15 26 12 INLET ISOLATION VALVE VFD 1600 Weights 726 FRAME 4 COMPRESSOR 34 15 Ib 34 kg 15 Ib 34 kg 15 46 21 74 34 108 49 13 6 13 6 24 11 726 1600 726 1600 726 Ib kg 1600 LEGEND VFD -- Variable Frequency Drive Table 29 -- Motor Voltage Code MOTOR CODE VOLTS FREQUENCY 62 63 64 52 380 416 460 400 60 60 60 50 108 FRAME 5 COMPRESSOR 19XRV COMPRESSOR COMPRESSOR FITS AND CLEARANCES FRAME 2 FRAME 3 (in.) FRAME 4 FRAME 4 FRAME 5 Code 201-299 321-390, 3ZZ 421-490 4B1-4W8 501-600 DESCRIPTION Fixed Diffuser With Rolling Element Bearings Fixed Diffuser Split Ring Diffuser Split Ring Diffuser ITEM A Low Speed Journal-Gear End .0050/.0040 .0050/.0040 .0055/.0043 .0055/.0043 .0069/.0059 B Low Speed Journal-Motor End .0050/.0040 .0050/.0040 .0053/.0043 .0053/.0043 .0065/.0055 .0115/.0055 N/A .010/-.005 .010/-.005 N/A Cl Low Speed Labyrinth to Thrust Disk C2 Labyrinth to Low Speed Shaft N/A .010/.005 .0095/.0055 .0095/.0055 .013/.009 D Low Speed Shaft Thrust Float .020/.008 .020/.008 .023/.008 .023/.008 .020/.008 E Impeller Eye to Shroud Ff Impeller Bore to Shaft-Rear F2 Impeller Bore to Shaft-Front G Impeller Discharge to Shroud H Impeller Spacer to Shaft I Slinger to Shaft J -.0020/-.0005 -.0021/-.0006 -.0021/-.0006 -.0019/-.0005 N/A -.0014/.0000 -.0014/.0000 -.0014/.0000 .0025/.0010 .0025/.0010 .0025/.0010 .0025/.0010 .0024/.0010 .0013/.0005 .0012/.0004 .0012/.0004 .0012/.0004 .0012/.0004 Labyrinth to Slinger .013/.009 .010/.006 .010/.006 .010/.006 .010/.006 K Labyrinth to Impeller .012/.008 .012/.008 .012/.008 .012/.008 .012/.008 L High Speed Journal-Impeller .0047/.0037 N/A .0040/.0028 .0040/.0028 .0048/.0038 M Thrust Assembly Seal Ring Axial Clearance N Thrust Assembly Seal Ring to Shaft O High Speed Shaft Thrust Float P High Speed Journal-Gear N/A End End -.0025/-.0010 .006/.002 N/A .006/.002 .006/.002 .006/.002 .0045/.0015 N/A .0045/.0015 .0045/.0015 .0045/.0015 .014/.008 0 Float .014/.008 .014/.008 .014/.008 .0050/.0040 N/A .0048/.0038 .0048/.0038 .0062/.0052 *Depends on impeller size, contact your Carrier Service Re 3resentative for more information. must be removed from the high speed shaft and bearing assembly before the high speed shaft and bearing assembly can be separated from the transmission. 4. If any components within the Frame 3 rolling element high speed shaft and bearing assembly are damaged it is recommended that the entire high speed shaft and bearing assembly be replaced. 5. Impeller spacing should be performed in accordance with the most recent Carrier Impeller Spacing Service Bulletin. NOTES: 1. All clearances for cylindrical surfaces are diametrical. 2. Dimensions shown are with rotors in the thrust position. 3. Frame 3 rolling element style high speed shaft and bearing assembly cannot be pulled from impeller end. The transmission assembly must be removed from the compressor casting (after the impeller is removed) and the bearing temperature sensor Fig. 48 -- Compressor 109 Fits and Clearances SEE VIEW A10RA2 A 2 COMPRESSOR, TRANSMISSION AREA (FRAME 1) OIL HEATER RETAINING NUT (NOT SHOWN) 2) BULLGEAR RETAINING BOLT 3) DEMISTER BOLTS (NOT SHOWN) 4) IMPELLER BOLT COMPRESSOR, TRANSMISSION 3 5 COMPRESSOR SEE VIEW B SHOWN) AREA THRUST Cl VIEW A1 LOW SPEED SHAFT THRUST DISK VIEW A2 LOW SPEED SHAFT THRUST DISK Fig. 48 -- Compressor Fits and Clearances (cont) 110 NOTE5 F2 IMPELLER SHIMMING TO BE DETERMINED AT ASSEMB_ SEE VIEW C VIEW B -- HIGH SPEED SHAFT (FRAME 2, 4, OR 5) +0.0007 0.025 +0.0007 -0.0007- 0.0011 0.0013 INTERFERENCE 0.0011 0.0013 INTERFERENCE 0.0012 0.0004 VIEW B -- HIGH SPEED Fig. 48 -- Compressor SHAFT (FRAME 3) Fits and III Clearances (cont) \ VIEW C -- HIGH SPEED SHAFT RING SEAL A CAUTION CAUTION USE COPPER CONDtJC'I'0RS 0NY UTII,]SEZ DES ALWAYS • TERM USE 2 NUT • ADAPTOR Insulate T0 TO BOLTS EN WRENCHES INSULATOR • BRASS • LUG CONDUCTEURS TO 32 - of ft. ft ALWAYS USE 2 WRENCHES TO T]GHTEN, o TERM INSULATOR TO MOTOR 15 35 ft Ib o CABLE LUG NUTS ..... ft.lb. lb ft. lb. max [b, [b. with cable it+ ....3 3035 45 +,ntir'r + cnnnection including 1 inch term insulator. 15+35 INSULATOR STUD (1/2") USE COPPER CONDUCTORS ONLY UTII,ISEZ DES CONDUCTEUBS EN CUIVRE SEUI,MENT SEU,MENT TIGHTEN, M0'10R TERM TERM T0 CUIVRE eler_Ir]eai insulation and Insulate iz_slllation 1 inch of entire connection including 1 inch term insulator. @Je of with electrical (¸:able insula±,io_ insulation and I i_ch of the TAPETO EXTENDTO AND OVER TERMINAL STUD- _ r....... 1© _-INSULATION -'\4---I 2@ 3© LEAD }_TRE |NS[H,A lCN @6 @4 8@ A DAD'p]_N? _ ........ ,1 _A_NSS NU]" ] L'-TERMINAL INSIJLATOR <-_-'A?+[ER ATTACHrNE @,5 LEAD, 'tHiS AREA TO BE WRAPPED?_THONELAYFROF TIIERNAL INSULATION PUTTY AND AT I[,EAS'] FOUR ELECTRICAL LAYERS OF INSULATING APPROPRIATE TAPE 13 MOTOR LEAD INSTALLATION LABELS 19XRV COMPRESSOR COMPRESSOR ITEM ASSEMBLY TORQUES FRAME 4 FRAME 4 FRAME 5 Code FRAME 2 201-299 321=390, 3ZZ FRAME 3 421-490 4B1-4W8 501-600 DESCRIPTION Fixed Diffuser With Rolling Element Bearings Fixed Diffuser Split Ring Split Ring Diffuser Diffuser 1 Oil Heater Retaining Nut- ft-lb (N'm) N/A 18-22 (25-30) 18-22 (25-30) 18-22 (25-30) 18-22 (25-30) 2 Bull Gear Retaining Bolt-- ft-lb (N'm) 80-90 (108-122) 80-90 (108-122) 80-90 (108-122) 80-90 (108-122) 80-90 (108-122) 3 Demister 15-19 (20-26) 15-19 (20-26) 15-19 (20-26) 15-19 (20-26) 15-19 (20-26) 4 Impeller bolt Torque -- ft-lb (N'm) 32-48 (43-65) 55-60 (75-81) 55-60 (75-81) 55-60 (75-81) 160-225 (217-305) Bolts -- ft Ib (N'm) Fig. 48 -- Compressor Fits and Clearances (cont) ll2 LEGEND AUX CB CCM CCN COM COMM DUDP GRD GVA HGBP HPS ICVC IGV J RHS T TB VFD -------------- Auxiliary Circuit Breaker Chiller Control Module Carrier Comfort Network Common Communications Data Link/Data Port Chassis Ground Guide Vane Actuator Hot Gas Bypass High Pressure Switch International Chiller Visual Controller Inlet Guide Vane Junction -- Relative Humidity Sensor Transformer Terminal Block -- Variable Frequency Drive 1C 2C 3C FOR FIG. 49-54 Compressor Oil Heater Contactor Oil Pump Contactor Hot Gas Bypass Relay Field Control Wiring Field Power Wiring Factory Wiring Shielded Cable _ >--I I • <_ @ Male/Female Potentiometer Pressure Switch A o-Aro Compr Oil Pump Terminal Cartridge Resistor Fuse Chassis Ground Connector Terminal Block Connection Temperature Switch Wire Splice or Junction I Common Potential Component Terminal © VFD Terminal Thermistor Transducer 113 Transformer IGBT _ DE_OTE_ COND_=CTO_ _ALE/F_E_4_L_ ¢ON_ECTOR Fig. 49 -- Electronic PIC III Control Panel Wiring Schematic (Frame 2, 3, 4 Compressor, Standard Diffuser) lEGEND DENOTES OIL ABBREV PUMP TERMINA C RCUIT BREAKER DDM (:HILLER CONTROL At ON LISTING MODULE HGBP HOT GAS BYPASS TB TERMINAL BOARD _v_ INE GD,OE V ACP_',TGU__t__ . -GUIDE DENOTES POWER PANEL TERMINAL 0 CB VANE ACTUAI©R D_NOTES COMPONLNT TERMINAL W_RE SP_CE i i i i i i i - _ COMPONENTi O_T_ON W_R_NG _ LAYOUT DENOTES MALE/F_MALE DENOTES MACH, •_ COMPR OiL _,C, CONTROL PANEL CONN, /C (BLK) (B K) _N (WHT) YEL VBLi_ABE _ PER JOB REGMT 22 -- O_ X 2B _ ' 12 0 i BL_ (BLK) -(BLK) COMPR OiL PUMP MOTOR (1 i/2 HP) 10 GVA L2 tO GVA L _ I (BLU) [............................. (RED) .................. (WHT) (W_T) (BLK) 230 i r (W_T) 2_ (RED) L_ (WHI} i p I II I i I COMPR DISCH HIGH PRES5 TO VFD/AB2/2_ VFD/A32/4m_ (BLK) I I TO CB/_ TO CB2_ i I II HGBP TO VFD/A32/3_ I I (CLR) TO STARTER (OPTIONAL) (BLU) (RED) TO CCH J7_2_ (BLK) _ _ /, (LU) t • I { D) (YL) _ HD_P SOLENOID I 3C 2 2sc) VWIBNG (_R_,) _ (BLU) 1 {CLR) POWER PANEL W1RING 5CHENATIC (RE_)I _ (YE) HGBP l _ SOL I NOID tt o I CCM ,'_, Fig. 50 -- Power Panel Wiring Schematic I I I I I (BI I K) ! _ I/// I 1 I _2 I I os o I I I I I I I co,,i I I I I I I I I iI ° BGBP II I I iiiii - _R) I I, '_,_I I_L) I • I TO I I ._LL)_ _ I I II r O TO CCM Ji2 4m I ) I (LK) i_) (Y) " -_eK)--III , (GRN) ( U) _:0 i i (Oi J12-5_ VFD COOLANT SOLENOID OPTIONAL _A/\ ODIFC_FION i i ORD TO CCM J?_3_ TO CCH J?_i_ I _ K) WIRING i--i'i IIIIII I TO CCM J12 _ I c ii /_ /C iO + DENOTES VFD PANE_ CONN, l i HEALER CB_K) I I ' LIA#_A_DRI I ' IlBV CONIRO _V_'ABB ONY I PDWER VFD ENCLOSURE OIL PUMP PANEL COHPRESSI]R OIL PUNP 3BDI4161480V-3-60 (1 t12 H, P.) 400-3-._0 CDNTACTOR (_-12_[J_- --( Y EL.) I I _ BLK) 1C I- ___J (l15v ONLY} COMPRESSOR [:_30wArTs-D2XR£ OILHEA_ tmO varr_-mxR_.0Z_R4 FiGDP FR_IE 115V ONLY -(WHT) (RZD) 7 HX < 115V HO_P J<) ONLY FR,_HE 1 [HRU HGBP < WHT) TI (BLK) (B_K>------l T _(B (BLK) =tXTE _ (RED) (RED) T "_ (SEE _4 VKD (RED (WHT) >lc IIHT)- [_HINAL I'_'---HSBP FR,_IE 1 THRU 7 HX tl_V TI II.K)---- 1 ,c<> F _LI<) I L(WHT>-_ _-----------( RE O_>--_ I (WHT) SEE _4V FOR C_rTROL$ _C -(BLK) -<_ _ FRAME I THRU (RED) (I).-K) ----e-----(BLK )-- g71a _'_ 6 HX (YZL)----e-----< YEL)-- 115V ONLY (I]PTIONAL) (BLU) l*IGgP SE]L£NO]D Ig W HI">.- (BLK) ] (/_L_)I Fig. 51 -- 19XRV Chiller Control Schematic $ ACTUATOR 7 HX ONLY 6 HX -(RED) T[ HGBP _FRAME SOLENOI D CHILLER CBe CONTROL PANEL _+_c.i 'IC _JI2 --(DL 24 V_£ VA C_I 2A IEVC-Jt i( _yi--J I_RN) +d_ZS) ' (_I_Y) J1 -- _/_L_RM ICVC CB1 q ((_RY) I CB] I F -_T_ -k -- s'_op | CcM J6 _UIO _E_ND L[MIIZZZSZZZZ Z .... .... r-'V--i $ l t I (_HIELIO/._--J EvaPm_r_ rm, V---_'_ RED)-- E_CA_RATCIR LV& _)---( uaTm T_:Np, _)----< RED)+---+ _I.I<)-_ CORI_ZN_ Bl, SEE CHART _EU]W _>----< _LFO_ VATER TEMP, _>---( IseI-I_I÷Ir_ I I F '_" _-r _ ' _ (C_)-- +a,e. REm+E+E++ 1 (_K_ I C_4 I _---_oml ---I I I iLI ]_li._= ii, +°i+ _ J6 _DLIDP SL.KZ_-_ I Ji G,V+ _S[TION FEE]JI_C_K (R_> _VER EVAP,,SATUma_TION_>_( _mN>_ (S_4"I) + ¢_: I_ _REII_ wATERIZNP. II"I '_ISLO) R{I))_ _----1_------( REl)) _ _ (OPTION) P_ (REIi)--VF_ IA3 _/3 _ ELK>--F_.--->_ v#_>-- @ COMPRESSB_ _>---< DI$CHN_GE I[MI:+_>----( RZ_>----BLK)---- tHRUST ]_F_AR [NO CIIMP_SOR _ r_P_r_g SPARE) _'(SHIELII b @ -@ BLK)--..@ C LR_.....-- FEED P_i ++ "fZN_RAI'UR[ L_>--.-( MI]'fl]R TEMP+ '_-'_:_( SPARE "TEMP.#] BACK TZNTI_TERC(< ONH +LK)----_LK _--'--" SPARD F --i>>--'(VHT)-_>--< BLK)--- ++ Jll FEE-->>--< v_-INFERNAL VARIABLE GUIDE V#C_E CONTROL SEE I15/230V FOR R3WER / CONTINLEI) ON SHEEI 6 CONTINUE_ ZI_ SHEET 6 Fig. 51 -- lgXRV Chiller Control Schematic (cont) CONTINUED / "x ON SI_EE'T6 _INUED FROM _EET CONTINUED 5 \/ CONTINUED FROM SHET \/ FROM SHEET 5 J12 c_ (BLK) (3RN) C_E B531 (gLK) C_ OIL SUMP PRESSURE _-.-._>---< [_>---< _>---< _LK_ CLR)---RED>---- OIL PUMP _>--"( I_LK)----DISCH. PRESSURE [_'_>-'-- ---- D_19D_ OIL PUMP MOll]R -i1 YF11OODLANT SOLENOID (BB',_ (BLK)------_, "-PT-[4-_o_., AI VFD ENCLOSURE VFO PDWER >IC MODULE LOAD RESIS]OR SIAND_RD]/0 LOAD ] RESISTOR B31_ JUMPER _c aux LOAD HPS ET_D RESISTOR CLOSE:110_7 PSIG. r--_ _ 8_I-- SWI JUMPER -----<_----- T1 >ic EVAP_ATOR REFI_IOER_NT PESSURE _ _>---( BLK)----CLF_ R_ CONDENSER REFR ]6ERANT PRESSURE t-_>__< _>---( CLR).. _ REI)>---- Fig. 51 -- 19XRV Chiller Control Schematic (cont) 5 CARRIER 19XRV LF2 VFD WIRING DIAGRAM _z_e _e_ _osz__, c. oll _M_ CR_D_ _SLK_ _Z_C --:,4] iAe_ec-- Fig. 52 -- 19XRV Chiller VFD Schematic I1_:;;:,:::::::)'_...... J _N_OL NOTE_ pANEL 1. THIS FEATURE IS STANDARD IN THE PIC II OONTROLS, BUT REQUIRE5 A CONIROLIJZR Y_TH A NON--GROUNDED OR 1-5Vdc OUTI_UT SIONAL NOT BY CARRIE_ .... ,7, ¢CM MCOLAJ_ ----r"r-p-----"IAUIO -_-_-_--- 4-2OmA DEMAND RESE1 \\ _CONIROLLER 2. _IS FEA_RE IS SIANDARD IN THE PIC II_ONTROLS, BUT REOUIRES A SENSOR PACKAGE OPTION, BY CARRIER. (ITEM #3, SEE OPTION LISTINO) INPUT (SEE NOTE #I) __----IT--IAUm C_fLLEO _ATER RESE_ ---,_--JCON_OLLER INPUT (SEE NOTE _) 3. PINS SHOWN FOR REFERENCE ONLY. ACTUAL PIN LAYOUT NOT SHOWN, ] I ____ t___ 4--20r.A (O-IOOXkw) DATAUNK OR TRANSFORMER (OPIION) _--(_) .... 4s_ SPARE _EMP #1 SmSOR (COMMON SUPPLY] CSEE NOTE C l(/h(//l #2) RELAY (oRno.} SPARETEMP12 SENSOR (COMMONREIURN)(SEENOTE#2) REMOIE 1EMP RESEI SENSOR (_ N01Z /2) OATAUNK 13_ DATAPOR'[ MOOULE ITI_ 1 OR2) _E oPnON k ]S_NO BELOW) % PROIECTIVEDATA TRANSMW G_ID 1 D-SHELLI _ I RECEIVE DATA I RS-2Z2 PORT fO BAS CONIRQ__'_CE (SEENOTE _) POWER PANEL (_OWN _ ÷ CONTROL PANEL OPTIONAL W1RING SP 0 1 COMPONENT LAYOUT COVERREMOVED) 2 03NTRCL pANEL j TD_MINAL BLOCK OPTION ITE_ USTING DESCRIPTION I DAIAPORT MOOULE 2 DAIAUNK MOOULE 3 SENSOR PA_KA(_£ CHECK TO ORDER °°°i Icvc e o o o @ INSIDE PANEL COVER Fig. 53 -- 19XRV Chiller Control CONTROL PANEL COMPONENT Panel Component Layout LAYOUT NOTES: I GENERAL 1,0 CONTROL VFD SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH &O CARRIER ENGINEERING REQUIREMENT Z-420o 1,1 1.2 MUST HAVE 24VAC RATING. MAX WITH ALL APPUCABLE SWI'[CHES WITH C43LI)PLATED BIFURCATED C:ONIAC'ISARE RECX3MMENDED. CODES AND JOB SPECIFICATION& EQUIPMENT INSIALLATION AND CONrACIS ARE SHOWN 3.2 REMOVE COMPONENT, AND 3,_ TME VF'D CONTACT ANNUNCIATOR 277VAC. ASSUME FAN AND THE CHILLER SHUII]OYvN. NARNING - DO NOT USE ALUMINUM _RING TO VFD DR ANT 3.4 AND AND 2,3 POWER CONDUCTOR CHILLER FULL LOAD AMPS UNE LUG ADAPTORS (# CONDUCTORS) VFD MAX INPUT AMPS. RATING MUST MEET VFD NAMEPLATE TOWER FAN MEANS STANDARD 65KAIC # CONDUCTORS RANGE) SPARE $-20mA NON--GROUNDEO OF 500 VOLTAGE CABLES PER PHASE 3.6 OP_ONAL CONDUCTOR RANGE 405A 3 3/0 608A 3 3/0- - BY CARRIER. WIRINI_CARRYING OUTPUT 4-20mA SIGNAL FOR COOLER AND COIL AND ALARM UP TO 3 AMPS TO START PUMPS MACHINE PROTECTION, AT AND TOWER IF PRIMARY MEANS. ALSO PROVIDE DD NOT USE STARTER FOR CONTACTOR A CONTROL COIL, ACTUATOR MOTOR 3DV OR LESS WIIHIN A CONDUIT "NHICH AND FOR CONTROLLERS A MAXIMUM WITH A INPUT IMPEDANCE OHMS. REMOVE JUMPER WIRE TB1/19 TO TB1/20 IOOKAIC LUG CAPACITY (PER PHASE) # CONDUCTORS IS DESIGNED INPUT SIGNAL AS FI_I_I.OWS: LUG CAPACITY (PER PHASE) AUXILLIARY LOADS. (MINIMUM CIRCUIT AMPACITY), SIZE (CONDUCTOR AT 115VAC TO ASSURE AS THE POWER SOURCE OTHER (VA) MOTOR CONTROL IS BY OTHER FOR DDNTROL ARE REQUIRED AT INSTALLATION. MINIMUM QUANTITY AND LOADS MOTOR CONTACTOR WIRING REOUIRED FOR CARRIER DO NOT ROUTE CONTROL 3.5 UNE S@E IS 10mA. HAS WIRES 'CARRYING 50V OR HIGHER OR ALONG SIDE WIRES CARR'fING 50V OR HIGHER, Z,1 METAL CONDUII MUST BE USED FGR IHE POI_ER WIRES, FROVI VFD TO BRANCH FEEDER. 2,2 CAN CONTROL TOWER FAN DEVICES IS RATED 5 AMPS TRANSFORMER PROVIDE A LOCAL MEANS OF DISODNNEGTINO POWER TO VFD, PROVIDE SHORT CIRCUIT PROTECTION FOR THE CHILLER AND INIERCONNECTING WIRE AT THE BRANCH FEEDER. IHE SHOR'[ CIRCUIT PROfE'_:TION SHALL BE FUSED TYPE OR EQUiVALEN'f CIRCUIT BREAKDR PER SHEEI 3 OF 4 OF THIS DOCUMEN'f. OUTPUTS PUMP, CONTROL PARALLEL IS BOrnA. NOMINAL CURRENT TBI-Ig AND "fBI-20 BEFORE CDNNECI]N_ MOTORS MUST BE PROVIDED PUMP CONDUCTORS, CURRENT BY CARRIER], THESE TERMINALS. FOR CONDENSER UTERATURE. IN THE POSITION IHEY WOULD ,.LIMPERWIRE BETWEEN SAFETIES BETV_ CONTROL DEVICES. MUST _lll DEIAILS IN EQUIPMENT SUBMITTAL DRA_NOS AND S_TCHES AND THE LOCA]ION INTERFERE WITH EQUIPMENT ACCESS ALL STARIINO AND WITH THE CIRCUIT DE-ENERGIZED 2,0 DEVICE CONTACTS WIRING, TI'3:_MINAIlON GF CONDUCTORS AND DEVICES, MUS'f 8E IN COMPUANCE THE ROUTING OF FIELD-INS'[ALLEDCONDUIT AND CONDUCTORS POWER OR LAROEP,. START/STOP SAFELY DEVICE CONTAC:TS_ (DEVICES NOI SUPPUED COMPLY 1,5 TO BE AT LEAST 18 A_ DEVICE CONTACTS, REMOTE AND SPARE OR THE READING. AOdUSIlNG OR SERVICING OF ANY 1,4 CONDUCTORS 3.1 ICE BUILD START/ERMINATE ALL FIELD-SUPPUED CONDUCTORS, DEVICES AND 'THE FIELD-INSTALLATION OF FIELD-INSTALLED DEVICES, MUST NOT 1,3 _RI N(3 FIELD SUPPLIED CONTROL CONDUCTOR RANGE 500MCM 2 40D - 500MCM 500MCM 3 3/0 - 2.4- COMPRESSOR MOTOR AND CONTROLS MUST BE GROUND[I) BY USING EGUIPM[NT GROUNDING LUGS PROVIDED INSIDE UNIT MOUNTED VFD ENCLOSURE, Fig. 54 -- 19XRV Field Wiring 400MCM IF INSTALLING SPARE SAFETY" CONTACT. INCOMING POWER WATER-PUMPS AND FANS AMp, CLASS J, TIME DELAY, 6DD VOLT AMP. _LA$S L 600 'lIME DELAY. VOL1 VARIABLE FREQUENCY DRIVE [ II J V-1PH-50/60HZ ] L_J Z CUSTOMER SUPPLIED RE_IOTE ALARM SEE NO_ ;5,3 I -...... ....... (OPTIONAL) REQUIRED POWER WIRING REQUIRED CONTROL WIRING OPTIONAL WIRINC FIELD WIRING Fig. 54 -- 19XRV Field Wiring (cont) 122 :1= P3 F,- T" -VOLTS -VOLTS EVAPORATOR U CdJID PUMP MOTOR CONDENSE]R LIQUID PUMP MOTOR {NOT (NOT BY CARRIER) BY CARRIER) PRIMARY COOLING TOWER FAN Full Reset STATUS SERVICE CHW Delta T->No Reset SERVICE CHW Setpt Reset Value Commanded State SERVICE SERVICE Common Option SERVICE Comp Discharge Sensor Alert SERVICE Comp Discharge Alert SERVICE Comp Discharge Temp STATUS Comp Discharge Temp SERVICE Comp Discharge Temp SERVICE Comp Motor Temp Override SERVICE Comp Motor Temp Override SERVICE Comp Motor Winding Temp STATUS Comp Motor Winding Temp SERVICE Comp Motor Winding Temp SERVICE TM 2 ICVC PARAMETER INDEX (cont) TABLE SCREEN NAME MAINSTAT CONTROL ALGORITHM CONTROL ALGORITHM STATUS STATUS EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM CONTROL ALGORITHM EQUIPMENT SERVICE CONTROL ALGORITHM EQUIPMENT STATUS STATUS STATUS SERVICE CONTROL ALGORITHM STATUS CONTROL TEST MAINSTAT TEMP CTL X X TEMP X CTL WSMDEFME WSMDEFME LEADLAG X OVERRIDE SETUP1 X CONTROL ALGORITHM EQUIPMENT OVERRIDE THERMITORS STATUS SERVICE OVERRIDE SETUP1 X COMPRESS CONTROL ALGORITHM STATUS CONTROL TEST CONTROL ALGORITHM Brg Alert SERVICE Brg Alert SERVICE Comp Thrust Brg Temp STATUS Comp Thrust Brg Temp SERVICE Comp Thrust Brg Temp SERVICE CONTROL TEST Compressor 100% Speed SERVICE VFD CONFIG DATA Compressor Ontime Compressor Ontime EQUIPMENT OVERRIDE THERMITORS Comp Thrust STATUS SERVICE OVERRIDE SETUP1 X COMPRESS CONTROL ALGORITHM STATUS OVERRIDE THERMITORS STATUS VFD CONF X MAINSTAT DEFAULT SCREEN Cond Approach Alert Cond Flow Delta P Cutout Cond Press Override SERVICE SERVICE SERVICE Cond Press Override SERVICE Condenser Condenser Approach Freeze Point STATUS SERVICE Condenser Condenser High Pressure Pressure Condenser Pressure SERVICE Condenser Pressure SERVICE Condenser Refrig Temp STATUS Condenser Refrig Temp SERVICE Condenser Condenser Condenser Refrigerant Temperature Water Delta P Water Delta P STATUS SERVICE Condenser Condenser Water Delta P Water Flow SERVICE STATUS CONTROL TEST Condenser Water Flow SERVICE CONTROL TEST Condenser Water Pump STATUS Condenser Water Pump CONSUME Control Mode SERVICE SERVICE STATUS Control Point SERVICE Control Point STATUS Control Point SERVICE Control Control Point Point Error SETPOINT SERVICE TEST WSMDEFME VFD HIST COMPRESS Comp Thrust CONTROL CONFIGURABLE EQUIPMENT SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT EQUIPMENT SETUP1 SETUP1 OVERRIDE X X SERVICE SETUP1 X SERVICE HEAT EX SETUP1 X STATUS STATUS VFD STAT HEAT EX CONTROL ALGORITHM STATUS CONTROL TEST OVERRIDE PRESSURE TRANSDUCERS HEAT EX CONTROL ALGORITHM STATUS OVERRIDE DEFAULT SCREEN HEAT EX PRESSURE TRANSDUCERS CONTROL TEST PUMPS STARTUP PUMPS STARTUP CONTROL TEST EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS PUMPS CONSUME MAINSTAT CAPACITY MAINSTAT EQUIPMENT SERVICE CONTROL ALGORITHM STATUS X TEMP X CTL SETPOINT CAPACITY X SERVICE Current Current CHW Setpoint Date SERVICE SERVICE CONTROL ALGORITHM STATUS WSMDEFME TIME AND DATE X Current Current Mode Time SERVICE SERVICE CONTROL ALGORITHM STATUS LL MAINT TIME AND DATE X 128 APPENDIX -- 19XRV LIQUlFLO MENU SOFTKEY PARAMETER Date TM 2 ICVC PARAMETER TABLE SCREEN NAME SERVICE Day of Week SERVICE Daylight SERVICE Savings DC Bus Voltage CONFIGURATION STATUS DC Bus Voltage SERVICE DC Bus Voltage Reference STATUS DC Bus Voltage Reference SERVICE Decrease EQUIPMENT Ramp Time CONFIGURABLE TIME AND DATE X TIME AND DATE X BRODEF X POWER CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST POWER VFD CONF X Degrees Reset SERVICE EQUIPMENT SERVICE TEMP CTL X Degrees Reset SERVICE EQUIPMENT SERVICE TEMP CTL X Degrees Reset At 20 mA SERVICE EQUIPMENT SERVICE TEMP CTL X Delta P at 0% (4 mA) SERVICE EQUIPMENT SERVICE OPTIONS X Delta P at 100% (20 mA) Demand Kilowatts SERVICE STATUS EQUIPMENT SERVICE OPTIONS POWER X Demand Limit and kW Ramp Demand Limit At 20 mA SERVICE SERVICE EQUIPMENT EQUIPMENT SERVICE SERVICE RAMP DEM RAMP DEM Demand Limit Demand Limit Decrease Inhibit SERVICE SERVICE Demand Limit Demand Limit Prop Band Source SERVICE SERVICE EQUIPMENT EQUIPMENT SERVICE SERVICE Demand Watts Interval SERVICE EQUIPMENT SERVICE Description Device Name SERVICE SERVICE Diffuser 25% Load Point SERVICE EQUIPMENT SERVICE SETUP2 X Diffuser 50% Load Point SERVICE EQUIPMENT SERVICE SETUP2 X Diffuser Diffuser 75% Load Point Actuator SERVICE STATUS EQUIPMENT SERVICE SETUP2 COMPRESS X Diffuser Actuator SERVICE Diffuser Actuator SERVICE Diffuser Actuator SERVICE Diffuser Control SERVICE EQUIPMENT SERVICE SETUP2 Diffuser Full Span mA SERVICE EQUIPMENT SERVICE SETUP2 X SERVICE STATUS EQUIPMENT SERVICE SETUP2 ICVC PWD X X Diffuser Option Disable Service Discharge Discrete SERVICE INDEX (cont) Password Pressure Outputs SERVICE Control Test SERVICE SERVICE SERVICE ECW Setpoint Stop Enable Reset Type X X RAMP DEM X ICVC CONFIGURATION ICVC CONFIGURATION CONTROL TEST CONTROL TEST IGV & SRD ACTUATOR CONTROL TEST DIFFUSER CONTROL TEST ACTUATOR X PRESSURE TRANSDUCERS CONTROL TEST SETPOINT X STATUS MAINSTAT X TEMP X Water STATUS Entering Chilled Water STATUS Entering Chilled Water Entering Chilled Water Entering Cond Water Entering Condenser Water Entering Condenser Water EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL ALGORITHM STATUS EQUIPMENT SERVICE CTL HEAT EX CONTROL ALGORITHM STATUS CAPACITY DEFAULT SCREEN SERVICE CONTROL TEST THERMITORS SERVICE CONTROL TEST THERMITORS STATUS HEAT EX DEFAULT SCREEN SERVICE Alert RAMP DEM RAMP DEM SETPOINT SERVICE Status X X Chilled Evap Approach X NET OPT CAPACITY TEMP CTL CAPACITY CAPACITY Entering Equipment EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS SERVICE ECW Control Option ECW Delta T ECW Reset Emergency VFD CONFIG DATA CONTROL ALGORITHM STATUS WSMDEFME SERVICE EQUIPMENT SERVICE SETUP1 X Evap Flow Delta P Cutout SERVICE EQUIPMENT SERVICE SETUP1 X Evap Ref Override SERVICE Temp Evap Refrig Trippoint SERVICE Evap Saturation Temp STATUS Evap Saturation Temp SERVICE Evaporator Approach STATUS Evaporator Pressure STATUS Evaporator Pressure SERVICE CONTROL ALGORITHM EQUIPMENT STATUS SERVICE OVERRIDE SETUP1 HEAT EX CONTROL TEST THERMITORS HEAT EX HEAT EX CONTROL TEST 129 PRESSURE TRANSDUCERS X APPENDIX -- 19XRV LIQUlFLO MENU SOFTKEY PARAMETER Evaporator Refrig Temp STATUS Evaporator Refrig Temp SERVICE Evaporator Refrigerant 2 ICVC PARAMETER INDEX (cont) TABLE SCREEN NAME STATUS Flux Current SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS STATUS SERVICE STATUS STATUS Ground Fault Current SERVICE Group Number Guide Vane 25% Load Pt SERVICE SERVICE Guide Vane 50% Load Pt SERVICE EQUIPMENT Guide Vane 75% Load Pt Guide Vane Calibration SERVICE SERVICE EQUIPMENT Guide Vane Control Guide Vane Delta SERVICE SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION EQUIPMENT SERVICE SERVICE Head Pressure Head Pressure Output Control Reference Head Pressure Head Pressure Reference Reference Test VFD HIST STAT OPTIONS VFD STAT POWER VFD HIST X X SERVICE SETUP2 X SERVICE SETUP2 CONTROL TEST X IGV & SRD ACTUATOR CAPACITY X CONTROL TEST CONTROL ALGORITHM STATUS COMPRESS EQUIPMENT SERVICE SERVICE STATUS SERVICE SERVICE EQUIPMENT SERVICE CONTROL TEST SETUP2 X CONTROL TEST HEAT EX X OPTIONS HEAD PRESSURE OUTPUT High DC Bus Voltage STATUS VFD STAT High Line Voltage STATUS VFD STAT Holiday HOLIDAYS SERVICE SERVICE Hot Gas Bypass Relay Hot Gas Bypass Relay Test Humidity EQUIPMENT CONFIGURATION STATUS SERVICE X NET OPT SETUP2 STATUS Guide Vane Travel Limit SETUP1 POWER VFD Full Load Point (T2, P2) Ground Fault Ground Fault Current Guide Vane Delta OVERRIDE DEFAULT SCREEN SERVICE STATUS Fault CONFIGURABLE HEAT EX CONTROL ALGORITHM Temperature Flow Delta P Display Flux Current Frequency TM TIME AND DATE HOLIDAYS X X HEAT EX CONTROL TEST DISCRETE OUTPUTS X Sensor Input STATUS Humidity Sensor Input Ice Build Contact SERVICE STATUS Ice Build Control SERVICE EQUIPMENT SERVICE OPTIONS Ice Build Option SERVICE EQUIPMENT SERVICE OPTIONS X Ice Build Recycle SERVICE EQUIPMENT SERVICE OPTIONS X SERVICE SETPOINT OPTIONS OCCP02S X X X CONFIGURATION OCCDEFCS X Ice Build Setpoint Ice Build Termination Ice Build Time Schedule Ice Build Time Schedule ICVC CONFIGURATION IGV & SRD Actuator Incompatibility SETPOINT SERVICE SCHEDULE (OCCPC02S) SERVICE SERVICE STATUS Increase Ramp Time Inverter Overcurrent Inverter Overload SERVICE STATUS STATUS Overtemp Power Fault CONTROL TEST EQUIPMENT EQUIPMENT PRESSURE TRANSDUCERS MAINSTAT SERVICE Fault Inverter Inverter POWER CONTROL TEST VFD VFD CONFIG DATA STATUS STATUS VFD VFD STAT STAT VFD CONF Inverter PWM Frequency SERVICE Inverter Temp Override SERVICE Inverter Temp Override SERVICE Inverter Temperature STATUS Inverter Temperature SERVICE CONTROL ALGORITHM STATUS OVERRIDE Inverter Temperature SERVICE CONTROL ALGORITHM STATUS VFD HIST LAG % Capacity LAG Address LAG CHILLER: SERVICE SERVICE Mode VFD CONFIG DATA STAT VFD CONF VFD STAT POWER CONTROL ALGORITHM EQUIPMENT STATUS SERVICE X X OVERRIDE SETUP1 X POWER EQUIPMENT EQUIPMENT SERVICE SERVICE LEADLAG LEADLAG SERVICE CONTROL ALGORITHM STATUS LL MAINT LAG Start Time SERVICE CONTROL ALGORITHM STATUS LL MAINT LAG START Timer SERVICE LAG Stop Time LAG STOP Timer SERVICE SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT SERVICE 130 X X LEADLAG X LL MAINT LEADLAG X APPENDIX -- 19XRV LIQUlFLO PARAMETER LCW Reset MENU SOFTKEY TM 2 ICVC PARAMETER TABLE INDEX (cont) SCREEN NAME SERVICE CONTROL ALGORITHM STATUS CAPACITY SETPOINT SERVICE CONTROL ALGORITHM STATUS SETPOINT LLMAINT Lead Lag Control SERVICE CONTROL ALGORITHM STATUS LLMAINT Lead Lag Control SERVICE LEAD/LAG: Configuration SERVICE LEAD/LAG: SERVICE LCW Setpoint LEAD CHILLER in Control Configuration EQUIPMENT SERVICE CONTROL ALGORITHM EQUIPMENT STATUS SERVICE LEADLAG LEADLAG Chilled Water STATUS Leaving Chilled Water SERVICE Leaving Chilled Water Leaving Chilled Water SERVICE CONTROL TEST THERMITORS Leaving Cond Water SERVICE CONTROL TEST THERMITORS Leaving Condenser Water Leaving Condenser Water X HEAT EX CONTROL ALGORITHM STATUS CAPACITY DEFAULT SCREEN STATUS HEAT EX DEFAULT SCREEN LID Language Line Active Current SERVICE STATUS Line Active Current SERVICE Line Active Voltage STATUS ICVC CONFIGURATION POWER CONTROL ALGORITHM STATUS VFD HIST SERVICE SERVICE CONTROL ALGORITHM STATUS VFD CONFIG DATA VFD HIST VFD CONF Line Current Line Current Imbal Time Imbalance SERVICE STATUS VFD CONFIG DATA VFD CONF POWER Line Current Imbalance STATUS Line Current Imbalance SERVICE Line Current Phl (R) STATUS Line Current Phl (R) SERVICE Line Current Ph2 (S) STATUS Line Current Ph2 (S) SERVICE Line Current Ph3 (T) STATUS Line Current Ph3 (T) SERVICE SERVICE Line Frequency STATUS Line Frequency Line Kilowatts SERVICE STATUS X POWER Line Active Voltage Line Current % Imbalance Line Phase Reversal Line Power Factor X LLMAINT Leaving Line Freq=60 Hz? (No=50) CONFIGURABLE X X VFD STAT CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST POWER POWER POWER VFD CONFIG DATA VFD CONF X POWER CONTROL ALGORITHM STATUS STATUS STATUS VFD HIST POWER VFD STAT POWER Line Power Factor SERVICE CONTROL ALGORITHM STATUS VFD HIST Line Reactive Line Reactive Current Current STATUS SERVICE CONTROL ALGORITHM STATUS POWER VFD HIST Line Reactive Voltage STATUS POWER Line Reactive Voltage Line Volt Imbalance Time SERVICE SERVICE CONTROL ALGORITHM STATUS VFD CONFIG DATA VFD HIST VFD CONF X Line Voltage % Imbalance SERVICE VFD CONFIG DATA VFD CONF X Line Voltage Imbalance STATUS Line Voltage Imbalance STATUS Line Voltage Imbalance SERVICE Line Voltage Phl (RS) STATUS Line Voltage Phl (RS) SERVICE Line Voltage Ph2 (ST) STATUS Line Voltage Ph2 (ST) SERVICE Line Voltage Ph3 (TR) STATUS Line Voltage Ph3 (TR) POWER VFD STAT CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST SERVICE CONTROL ALGORITHM STATUS VFD HIST Load Balance Option SERVICE CONTROL ALGORITHM STATUS LL MAINT Load Balance Option SERVICE Load Current Phl (U) STATUS Load Current Phl (U) SERVICE Load Current Ph2 (V) STATUS Load Current Ph2 (V) SERVICE Load Current Ph3 (W) STATUS Load Current Ph3 (W) SERVICE POWER POWER POWER EQUIPMENT SERVICE LEADLAG POWER CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST CONTROL ALGORITHM STATUS VFD HIST POWER POWER 131 X APPENDIX -- 19XRV LIQUlFLO PARAMETER Loadshed MENU SOFTKEY TM 2 ICVC PARAMETER INDEX (cont) TABLE SCREEN NAME SERVICE CONTROL ALGORITHM STATUS LOADSHED Loadshed Loadshed Function Function SERVICE SERVICE EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS NET OPT LOADSHED Loadshed Timer SERVICE CONTROL ALGORITHM STATUS LOCAL CONFIGURABLE LOADSHED DEFAULT SCREEN Local Network Device SERVICE Local Time Schedule ATTACH TO NETWORK SCHEDULE Local Time Schedule (OCCPC01 S) LOG OUT OF DEVICE SERVICE SERVICE Low DC Bus Voltage STATUS Low Line Voltage Maximum Loadshed STATUS SERVICE Time EQUIPMENT CONFIGURATION CONFIGURATION X X OCCP01S X OCCDEFCS X VFD EQUIPMENT DEVICE STAT VFD STAT NET OPT X Min. Load Point (T1, P1) SERVICE EQUIPMENT SERVICE OPTIONS Minimum Output Model Number SERVICE SERVICE EQUIPMENT SERVICE OPTIONS ICVC CONFIGURATION Motor Motor Amps Not Sensed Current % Imbalance STATUS SERVICE Motor Motor Current Current Imbal Time Imbalance SERVICE STATUS Motor Current Imbalance STATUS Motor Motor Current Imbalance Kilowatt Hours SERVICE STATUS Motor Kilowatts Motor Nameplate Amps SERVICE VFD CONFIG DATA VFD CONF X Motor Nameplate kW SERVICE VFD CONFIG DATA VFD CONF X Motor Nameplate RPM SERVICE VFD CONFIG DATA VFD CONF X Motor Motor Nameplate Overload Voltage SERVICE STATUS VFD CONFIG DATA VFD CONF POWER X Motor Motor Overload Overload Motor Power Factor STATUS Motor Power Factor SERVICE Motor Motor Rated Load Amps Rated Load kW SERVICE SERVICE VFD CONFIG DATA VFD CONFIG DATA VFD CONF POWER VFD CONTROL ALGORITHM STATUS STATUS STATUS SERVICE VFD STAT VFD CONF X X X STAT VFD HIST POWER POWER CONTROL ALGORITHM STATUS VFD STAT VFD HIST CONTROL ALGORITHM STATUS VFD HIST POWER VFD CONFIG DATA VFD CONFIG DATA VFD VFD CONF CONF X X OCCPC01S (Local Time Schedule) SCHEDULE OCCP01S X OCCPC02S (Ice Build Time Schedule) SCHEDULE OCCP02S X OCCPC03S (CCN Time Schedule) SCHEDULE OCCP03S X OCCPC01S (Local Time Schedule) SERVICE EQUIPMENT CONFIGURATION OCCDEFCS X OCCPC02S (Ice Build Time Schedule) SERVICE EQUIPMENT CONFIGURATION OCCDEFCS X OCCPC03S (CCN Time Schedule) SERVICE EQUIPMENT CONFIGURATION OCCDEFCS X Occupied? STATUS Oil Heater Relay STATUS Oil Heater Relay Test SERVICE Oil Press Verify Time Oil Pressure SERVICE Oil Pressure SERVICE Acceptable? MAINSTAT COMPRESS CONTROL TEST EQUIPMENT SERVICE CONTROL TEST DISCRETE OUTPUTS X SETUP1 DEFAULT SCREEN X PUMPS Oil Pump Delta P STATUS STARTUP X Oil Pump Delta P STATUS COMPRESS X Oil Pump Delta P SERVICE CONTROL TEST Oil Pump Delta P SERVICE CONTROL TEST Oil Pump Relay STATUS Oil Pump Relay SERVICE Oil Sump Temp STATUS Oil Sump Temp STATUS PRESSURE TRANSDUCERS PUMPS STARTUP CONTROL TEST PUMPS STARTUP COMPRESS Oil Sump Temp DEFAULT SCREEN Oil Sump Temp SERVICE Password (VFD CONFIG DATA) SERVICE CONTROL TEST VFD CONFIG DATA X Password (SERVICE) SERVICE ICVC CONFIGURATION X 132 THERMITORS APPENDIX -- 19XRV LIQUlFLO MENU SOFTKEY PARAMETER TM 2 ICVC PARAMETER TABLE INDEX (cont) SCREEN NAME Percent Line Current STATUS MAINSTAT Percent Line Current Percent Line Current STATUS POWER DEFAULT SCREEN Percent Line Kilowatts STATUS MAINSTAT Percent Line Kilowatts STATUS POWER Percent Line Voltage Percent Load Current Percent Motor Kilowatts STATUS STATUS STATUS POWER POWER POWER Pressure Transducers Control Test PRESTART FAULT Time PRESTART FAULT Timer SERVICE SERVICE SERVICE CONFIGURABLE CONTROL TEST CONTROL ALGORITHM STATUS EQUIPMENT SERVICE PRIMARY MESSAGE LL MAINT LEADLAG X DEFAULT SCREEN Proportional Dec Band SERVICE EQUIPMENT SERVICE SETUP2 X Proportional ECW Gain SERVICE EQUIPMENT SERVICE SETUP2 X Proportional Inc Band SERVICE EQUIPMENT SERVICE SETUP2 X Pulldown Ramp Type: Pulldown: Delta T/Min SERVICE SERVICE RAMP DEM LL MAINT X CONTROL TEST X Pumpdown/Lockout Control Test SERVICE Pumpdown/Lockout Control Test SERVICE Pumps Control Test SERVICE Rated Line Amps Rated Line Kilowatts SERVICE SERVICE Rated Line Voltage Re-alarm Time SERVICE SERVICE Recovery Start Request Rectifier Overcurrent SERVICE STATUS EQUIPMENT SERVICE CONTROL ALGORITHM STATUS CONTROL TEST CONTROL TEST CONTROL TEST VFD CONFIG DATA VFD CONFIG DATA VFD CONFIG DATA EQUIPMENT CONFIGURATION CONTROL ALGORITHM STATUS VFD CONF VFD CONF X X VFD CONF NET OPT X X LLMAINT VFD STAT Rectifier Overload STATUS POWER Rectifier Rectifier Overtemp Power Fault STATUS STATUS VFD STAT VFD STAT Rectifier Temp Override SERVICE Rectifier Temp Override SERVICE Rectifier Temperature STATUS Rectifier Temperature SERVICE CONTROL ALGORITHM STATUS OVERRIDE Rectifier Temperature SERVICE CONTROL ALGORITHM STATUS VFD HIST Recycle Redline Control SERVICE SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS SETUP1 LOADSHED Reference Number Refrig Override Humidity Relative Humidity Remote Contacts SERVICE SERVICE SERVICE STATUS STATUS SERVICE Remote Start Contact STATUS Remote Temp->No RESET Reset Alarm? STATUS SERVICE Reset Reset OVERRIDE SETUP1 EQUIPMENT SERVICE CONTROL TEST SETUP1 POWER EQUIPMENT SERVICE CONTROL TEST SERVICE EQUIPMENT SERVICE SERVICE EQUIPMENT SERVICE STATUS OPTIONS X ICVC PWD MAINSTAT THERMITORS X MAINSTAT X TEMP X CTL TEMP CTL DEFAULT SCREEN ICVC PWD EQUIPMENT SERVICE TEMP CTL RESET TYPE 2 SERVICE EQUIPMENT SERVICE TEMP CTL RESET TYPE 3 SERVICE EQUIPMENT SERVICE TEMP CTL Restart SERVICE EQUIPMENT SERVICE SERVICE STATUS X PRESSURE TRANSDUCERS SERVICE Run Status Run Status X ICVC CONFIGURATION RESET TYPE 1 Delta T X POWER STATUS Option Remote Reset Option Remote Reset Sensor Remote Reset Sensor Remote Temp->Full EQUIPMENT SERVICE Delta T Relative CONTROL ALGORITHM CONTROL ALGORITHM 133 STATUS SETUP1 LL MAINT MAIN STAT X X X X APPENDIX -- 19XRV LIQUlFLO PARAMETER MENU SOFTKEY TM 2 ICVC PARAMETER INDEX (cont) TABLE SCREEN NAME CONFIGURABLE RUNTIME SERVICE EQUIPMENT CONFIGURATION RUNTIME X Schedule Number SECONDARY MESSAGE SERVICE EQUIPMENT CONFIGURATION NET OPT DEFAULT SCREEN X Serial SERVICE Service Number Ontime ICVC CONFIGURATION STATUS Shunt Trip Relay MAINSTAT STATUS Shunt Trip Relay Test Shutdown Delta T SERVICE SERVICE STARTUP CONTROL TEST EQUIPMENT SERVICE DISCRETE OUTPUTS SETUP1 VFD X X Single Cycle Dropout STATUS Single Cycle Dropout SERVICE VFD CONFIG DATA VFD_CONF STAT X X Skip Frequency 1 SERVICE VFD CONFIG DATA VFD Skip Frequency 2 SERVICE VFD CONFIG DATA VFD_CONF X Skip Frequency 3 SERVICE VFD CONFIG DATA VFD CONF X Skip Frequency Band SERVICE VFD CONFIG DATA VFD CONF X Soft Stop Amps Threshold Software Part Number SERVICE SERVICE EQUIPMENT SERVICE Spare Alert/Alarm SERVICE EQUIPMENT SERVICE Enable Spare Safety Input STATUS CONF OPTIONS ICVC CONFIGURATION X SETUP1 STARTUP Spare Temp #1 Enable SERVICE EQUIPMENT SERVICE SETUP1 X Spare Temp #1 Limit SERVICE EQUIPMENT SERVICE SETUP1 X Spare Temp #2 Enable SERVICE EQUIPMENT SERVICE SETUP1 X Spare Temp #2 Limit SERVICE EQUIPMENT SERVICE SETUP1 X Spare Temperature 1 STATUS Spare Temperature 1 SERVICE Spare Temperature 1 SERVICE Spare Temperature 2 STATUS Spare Temperature 2 SERVICE Spare Temperature 2 SERVICE STANDBY % Capacity STANDBY Address SERVICE SERVICE STANDBY Chiller Option STANDBY CHILLER: Mode SERVICE SERVICE Start Acceleration Start Advance STATUS SERVICE Fault Start Complete COMPRESS CONTROL ALGORITHM STATUS CONTROL TEST COMPRESS CONTROL ALGORITHM STATUS CONTROL TEST EQUIPMENT EQUIPMENT SERVICE SERVICE EQUIPMENT SERVICE CONTROL ALGORITHM STATUS EQUIPMENT CONFIGURATION STATUS EQUIPMENT CONFIGURATION EQUIPMENT Start Time Start Week SERVICE SERVICE EQUIPMENT EQUIPMENT Start/Stop Starts In 12 Hours SERVICE STATUS Stop Back SERVICE X VFD_STAT BRODEF X X CONFIGURATION CONFIGURATION CONFIGURATION BRODEF BRODEF X X CONTROL ALGORITHM EQUIPMENT STATUS CONFIGURATION X LL MAINT MAINSTAT BRODEF X STARTU P STATUS SERVICE LEADLAG LL_MAINT BRODEF MAINSTAT BRODEF STATUS Stop Day of Week X X VFD_STAT SERVICE STATUS SERVICE Stop Complete LEADLAG LEADLAG STARTU P Start Day of Week Start Inhibit Timer Start Month Stop Complete LL MAINT THERMITORS STATUS Start Complete LL MAINT THERMITORS VFD_STAT EQUIPMENT CONFIGURATION BRODEF X Stop Fault STATUS Stop Month SERVICE EQUIPMENT CONFIGURATION BRODEF X Stop Time SERVICE EQUIPMENT CONFIGURATION BRODEF X Stop Week SERVICE EQUIPMENT CONFIGURATION BRODEF X Superheat Surge/HGBP Required SERVICE VFD_STAT CONTROL ALGORITHM STATUS OVERRIDE Active? STATUS Gas Bypass SERVICE EQUIPMENT SERVICE OPTIONS Surge Delta % Amps SERVICE EQUIPMENT SERVICE OPTIONS X Surge Limit/HGBP SERVICE EQUIPMENT SERVICE OPTIONS X SERVICE EQUIPMENT SERVICE OPTIONS EQUIPMENT SERVICE Surge/Hot Option Surge Protection Surge Protection Surge Time Period Counts HEAT_EX STATUS SERVICE COMPRESS 134 OPTIONS X APPENDIX -- 19XRV LIQUlFLO TM 2 ICVC PARAMETER PARAMETER MENU SOFTKEY Surge/HGBP Deadband SERVICE EQUIPMENT SERVICE OPTIONS X Surge/RGBP Delta P1 SERVICE EQUIPMENT SERVICE OPTIONS X Surge/RGBP Delta P2 SERVICE EQUIPMENT SERVICE OPTIONS X Surge/RGBP Delta T STATUS Surge/RGBP Delta T1 SERVICE EQUIPMENT SERVICE OPTIONS X Surge/RGBP Delta T2 SERVICE EQUIPMENT SERVICE OPTIONS X System Alert/Alarm TABLE INDEX (cont) SCREEN NAME HEAT EX STATUS Target Guide Vane Pos STATUS Target Guide Vane Pos SERVICE MAINSTAT COMPRESS CONTROL ALGORITHM STATUS STATUS COMPRESS Target VFD Speed STATUS STARTUP Target VFD Speed SERVICE Temp Pulldown SERVICE Temperature Reset STATUS Temperature Reset Terminate Lockout SERVICE SERVICE Thermistors Control TIME AND DATE Time Broadcast Test Enable CONTROL ALGORITHM EQUIPMENT STATUS SERVICE CAPACITY TEMP CTL EQUIPMENT EQUIPMENT SERVICE SERVICE TEMP CTL CONTROL TEST EQUIPMENT CONFIGURATION Torque Current SERVICE CONTROL ALGORITHM STATUS VFD HIST Total Compressor Starts Total Error + Resets STATUS SERVICE CONTROL ALGORITHM STATUS MAINSTAT CAPACITY Tower Fan High Setpoint SETPOINT SETPOINT STATUS STARTUP Tower Fan Relay Low SERVICE POWER CONTROL TEST DISCRETE OUTPUTS STATUS SERVICE CONTROL TEST DISCRETE OUTPUTS Transducer SERVICE CONTROL TEST PRESSURE TRANSDUCERS Ref US Imp / Metric Values at Last Fault: VFD Checksum SERVICE SERVICE Error STATUS VFD Cold Plate Temp STATUS VFD Cold Plate Temp VFD Comm Fault VFD CONFIG PASSWORD VFD Coolant Flow VFD Coolant VFD Coolant Flow Solenoid SERVICE STATUS SERVICE CONTROL ALGORITHM STATUS STATUS SERVICE VFD Enclosure Temp STATUS VFD Enclosure VFD Fault temp SERVICE STATUS ICVC CONFIGURATION VFD HIST STATUS VFD HIST VFD STAT VFD CONFIG DATA POWER DISCRETE OUTPUTS CONTROL TEST CONTROL ALGORITHM STATUS X VFD HIST VFD STAT STATUS CONTROL ALGORITHM STATUS VFD HIST VFD FAULT HISTORY SERVICE CONTROL ALGORITHM STATUS VFD HIST VFD Gain SERVICE VFD Increase Step VFD Inverter Version X POWER SERVICE # X HEAT EX VFD Fault Code Version X POWER CONTROL ALGORITHM VFD Fault Code VFD Gateway X VFD STAT STATUS Test X STARTUP Tower Fan Relay Low Test Voltage X BRODEF STATUS Tower Fan Relay High Test X CONTROL TEST TIME AND DATE Torque Current Tower Fan Relay High X MAINSTAT SERVICE SERVICE SERVICE X CAPACITY Target VFD Speed Deg/Min. CONFIGURABLE VFD STAT EQUIPMENT SERVICE STATUS SETUP2 X VFD STAT SERVICE STATUS EQUIPMENT SERVICE SETUP2 VFD STAT X VFD Maximum Speed SERVICE EQUIPMENT SERVICE SETUP2 X VFD Minimum Speed VFD Power On Reset SERVICE STATUS EQUIPMENT SERVICE SETUP2 VFD STAT X EQUIPMENT SERVICE VFD Rectifier Version # # VFD Speed Control VFD Start VFD Start Inhibit Water Flow Verify Time WSM Active? STATUS SERVICE STATUS VFD STAT STATUS SERVICE SERVICE SETUP2 STARTUP VFD STAT EQUIPMENT SERVICE CONTROL ALGORITHM STATUS 135 SETUP1 WSMDEFME X INDEX Abbreviations and explanations 4, 5 Adding refrigerant 74 Adjusting the refrigerant charge 74 After extended shutdown 69 Alter limited shutdown 69 Alarm (trip) output contacts 40 Attach to network device control 47 Automatic soft stop amps threshold 51 Auto. restart alter power failure 42 Bearings 8 Before initial start-up .52-67 Capacity override .;9 Carrier Comfort Network interface 60 Changing oil filter 76 Charge refrigerant into chiller 65 Chilled water recycle mode 51 Chiller control module (CCM) 97 Chiller dehydration 58 Chiller familiarization 5, 6 Chiller information nameplate 5 Chiller operating condition (check) 68 Chiller tightness (check) 53 Chillers with isolation valves 73 Chillers with storage tanks 71 Cold weather operation 69 Compressor bearing and gear maintenance 77 Condenser 5 Condenser freeze prevention 41 Condenser pump control 41 Control algorithms checkout procedure 80 Controlpanel 5 Control modules 97 Control test 64, 81 Controls 11-49 Cooler 5 Defimlt screen freeze .;6 Definitions (controls) 11 Design set points, (input) 61 Details (lubrication cycle) 8 Display messages (check) 79 Equipment required .52 Evaporator freeze protection 41 Extended shutdown (preparation for) 69 General (controls) 11 General maintenance 74, 75 Ground fault troubleshooting 60 Guide vane linkage (check) 7.5 Head pressure reference output 44 Heat exchanger tubes and flow devices (inspect) 77 High altitude locations 65 High discharge temperature control .;9 Ice build control 46 ICVC operation and menus 16 Initial start-up 6Z 6_5' Initial start-up checklist for 19XRV hermetic centrifugal liquid chiller CL-lro CL-12 Input power wiring 59 Inspect the control panel 76 Instruct the customer operator 68 Introduction 4 Job data required .52 Kilowatt output 41 Lead/lag control 44 Leak rate 74 Leak test chiller .5.5 Local occupied schedule (input) 61 Local start-up 50 Lubrication cycle 8, 9 Lubrication system (check) 7.5 Manual guide vane operation 69 Motor and lubricating oil cooling cycle 7 Motor-compressor 5 Motor rotation (check) 67 Notes on module operation 97 Oil changes 76 Oil charge .52 Oil cooler 39 Oil pressure _mdcompressor stop (check) 67 Oil reclaim filter 76 Oil reclaim system 8 Oil specification 76 Oil sump temperature and pump control 39 Open oil circuit valves .52 Operating instructions 68-70 Operating the optional pumpout unit 71 Operator duties 68 Optional pumpout compressor water piping (check) 5_5' Optional pumpout system controls and compressor(check) 65 Optional pumpout system maintenance 78 Ordering replacement chiller parts 78 Overview (troubleshooting guide) 79 Perform a control test 64 Physical data 99 PIC III system components 11 PIC III system functions .;4 Power up the controls and check the oil heater 61 Preparation (initialstart-up) 67 Preparation (pumpout and refrigerant transfer procedures) 71 Prepare the chiller for start-up 68 Pressure transducers (check) 79 Prevent accidental start-up 67 Pumpont and refrigerant transfer procedures 71-74 Ramp loading 39 Recalibmte pressure transducers 7,5' Refrigerant filter 76 Refrigerant float system (inspect) 77 Refrigerant leak testing 74 Refrigerant properties 74 Refrigerant (removing) 74 Refrigerant tracer 53 Refrigeration cycle 7 Refrigeration log 69 Relief valves (check) 58 Relief valves and piping (inspect) 77 Remote reset of alarms 41 Remote start/stop controls 40 Repair the leak, retest, and apply standing vacuum test 7.5 Replacing defective processor modules 98' Running system (check) 68 Safety and operating controls (check monthly) 76 Safety considerations 1 Safety controls .;6 Safety shutdown 52 Scheduled maintenance 75-78 Service configurations (input) 61 Ser_.ice ontime 7.5 Seta.'ice operation 48' Shipping packaging (remove) .52 Shunt trip (option) 36 Shutdown sequence 51 Software configuration 61 Spare safety and space temperature inputs 40 Standing vacuum test 55 Starting equipment 9-11 Start-up/shutdown/recycle sequence 50-.52 Start the chiller 68 Stop the chiller 69 Storage vessel 5 Sunnnary (lubrication cycle) 8 Surge prevention algorithm 42 Surge protection 43 System components 5 Temperature sensors (check) 79 Test after service, repair, or m:tior leak Tighten all gasketed joints and guide vane packing .52 Tower fan relay low and high 41 Trim refrigerant charge 7.5 Troubleshooting guide 79-126 Unit-mounted VFD 9 Using the optional storage tank and pumpout system 52 Variable frequency drive 5 VFD cooling cycle 8 VFD (identify) 58 VFD (inspect) 78 Water/brine reset 42 Water leaks 77 Water piping (inspect) 58 Water treatment 78 Weekly nmintenance 7.5 Wiring (inspect) 60 74 Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, PC 211 Catalog No. 531-986 or change at any time, specifications Printed in U.S.A. or designs without notice and without incurring obligations. Form 19XRV-1SS Pg 136 4-05 Replaces: New INITIAL START-UP CHECKLIST FOR 19XRV HERMETIC CENTRIFUGAL LIQUID (Remove and use for job file.) CHILLER MACHINE INFORMATION: NAME JOB NO. ADDRESS MODEL CITY STATE ZIP S/N DESIGN CONDITIONS: TONS (kW) BRINE FLOW RATE TEMPERATURE IN TEMPERATURE OUT PRESSURE DROP PASS SUCTION TEMPERATURE CONDENSER TEMPERATURE COOLER CONDENSER COMPRESSOR: Volts RLA OLTA STARTER: OIL PUMP: Mfg Volts Type RLA S/N OLTA REFRIGERANT: Type: __ CARRIER OBLIGATIONS: Charge __ Assemble ................... Leak Test ................... Yes [] Yes [] No [] No [] Dehydrate .................. Charging ................... Operating Instructions Yes [] Yes [] No [] No [] Hrs. START-UP TO BE PERFORMED IN ACCORDANCE WITH APPROPRIATE MACHINE START-UP INSTRUCTIONS JOB DATA REQUIRED: 1. Machine Installation Instructions .................. Yes [] No [] 2. 3. 4. 5. Machine Assembly, Wiring and Piping Diagrams ...... Starting Equipment Details and Wiring Diagrams ...... Applicable Design Data (see above) ................ Diagrams and Instructions for Special Controls ....... Yes Yes Yes Yes [] [] [] [] No No No No [] [] [] [] INITIAL MACHINE PRESSURE: YES NO Was Machine Tight? If Not, Were Leaks Corrected? Was Machine Dehydrated After Repairs? CHECK OIL LEVEL AND RECORD: 3/4 1/2 Top sight glass 1/4 ADD OIL: Yes [] No [] Amount: 3/4 1/2 Bottom sight glass 1/4 RECORD PRESSURE DROPS: CHARGE REFRIGERANT: Book Tab Cooler Initial Charge Condenser Final Charge After Trim Manufacturer reserves the right to discontinue, or change at any time_ specifications or designs without notice and without incurring obligations. h2 PC 211 Catalog No, 531-986 Printed in U.S,A. Form 19XRV-1SS CL-1 4-05 Replaces: F New INSPECT WIRING AND RECORD ELECTRICAL RATINGS: Motor Voltage Line Voltages: DATA: Motor(s) Amps Motor FIELD-INSTALLED Oil Pump Voltage Oil Pump Starter LRA Rating Controls/Oil Heater STARTERS ONLY: Check continuity T1 to T1, etc. (Motor to starter, disconnect motor leads T1, T2, T3.) Do not megger VFD; disconnect leads to motor and megger the leads. "PHASE TO PHASE .... MEGGER MOTOR 10-Second Readings: 60-Second Readings: Polarization T1 -T2 T1 -T3 PHASE TO GROUND" T2-T3 T1-G T2-G T3-G Ratio: VFD Manufacturer VFD Serial Number U3 z VFD Date Code u c_ U3 CONTROLS: SAFETY, OPERATING, ETC. c_ Perform Controls Test (Yes/No) z PIC III CAUTION COMPRESSOR MOTOR AND CONTROL PANEL MUST BE PROPERLY AND INDIVIDUALLY CONNECTED BACK TO THE EARTH GROUND IN THE STARTER (IN ACCORDANCE WITH CERTIFIED DRAWINGS). RUN MACHINE: q I- Yes o Do these safeties shut down machine? Condenser Water Flow Chilled Water Flow Yes [] Yes [] No [] No [] Pump Interlocks Yes [] No [] INITIAL START: Line Up All Valves in Accordance With Instruction Manual: Start Water Pumps and Establish Water Flow LU 2: Oil Level OK and Oil Temperature OK Check Oil Pump Rotation-Pressure u tm LU Check Compressor Motor Rotation (Motor End Sight Glass) and Record: I- Clockwise Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? *If yes, determine cause. Yes* [] No [] c_ Z o, I- START MACHINE AND OPERATE. COMPLETE THE FOLLOWING: A: B: C: D: E: F: Trim charge and record under Charge Refrigerant Into Chiller section on page 65. Complete any remaining control calibration and record under Controls section (pages 11-49). Take at least two sets of operational log readings and record. After machine has been successfully run and set up, shut down and mark shutdown oil and refrigerant levels. Give operating instructions to owner's operating personnel. Hours Given: Hours Call your Carrier factory representative to report chiller start-up. SIGNATURES: CARRIER TECHNICIAN CUSTOMER REPRESENTATIVE DATE DATE CL-2 o CO/WO 19XRV PIC III SETPOINT DESCRIlrrlON Base Demand 3ABLE CONFIGURATION RANGE Limit 40 to 100 StIEET UNITS DEFAULT % 100 LCW Setpoint 10to 120 (- 12.2 to 48.9) DEG F (C) 50.0 (10) ECW Setpoint 15to 120 (-9.4 to 48.9) DEG F (C) 60.0 (15.6) Ice Build Setpoint 15 to 60 (-9.4 to 15.6) DEG F (C) 40.0 (4.4) Tower Fan Itigh Setpoint 55 to 105 (13 to 41 ) DEG F (C) 75 (24) Upload all control configuration ICVC Softwme ICVC Controller tables via service tool'? Yes [] No [] Version Number: Identification: BUS: ADDRESS: CL-3 VALUE O I 19XRV PIC III TIME SCHEDULE M Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: T W CONFIGURATION Day Flag T F S S SHEET Occupied Time II I OCCPC01S Unoccupied Time LU zm c_ NOTE: Default setting is OCCUPIED 24 hours/day. LU i- tm I ICE BUILD 19XRV PIC III TIME SCHEDULE CONFIGURATION SHEET I OCCPC02S z o, Io M Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: T W Day Flag T F S S Occupied Time It Unoccupied Time LU zm tm LU I- NOTE: Default setting is UNOCCUPIED 24 hours/day. Z o, I 19XRV PIC III TIME SCHEDULE M T W CONFIGURATION Day Flag T F S Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: NOTE: Default setting is OCCUPIED 24 hours/day. CL-4 S It SHEET I OCCPC03S Occupied Time Unoccupied Time Io 19XRV PIC III VFD_CONF DESCRIIrFION Motor Nameplate CONFIGURATION RANGE SIIEET UNITS DEFAULT 380-460 VOLTS 460 45.0-62.0 Hz 60.0 0/l NO/YES YES 346-480 VOLTS 460 * Rated Line Amps * Rated Line Kilowatts * Motor Rated Load KW l 0-1500 0-7200 0-7200 AMPS kW kW 200 100 100 * Motor 10-1500 AMPS 200 l 0-1500 AMPS 100 Compressor 100% Speed Line Freq=60 * Rated Voltage TABLE Hz? (No=50) Line Voltage Rated Load Amps Motor Nameplate Amps Motor Nameplate RPM 1500-3600 Motor Nameplate KW 0-5600 3456 kW 100 Inverter PWM Frequency (0=4 k Hz, 1=2 k Hz) 0/l Skip Frequency I 0.0-102.0 Hz 102.0 Skip Frequency 2 0.0-102.0 Hz 102.0 Skip Frequency 3 0.0-102.0 Hz 102.0 Skip Frequency Band 0.0-102.0 Hz 0.0 Line Voltage % Imbalance Line Volt Imbalance Time l - l0 l - l0 % SEC l0 l0 Line Current 5-40 % 40 l-l0 SEC l0 5-40 % 40 Line Current % Imbalance Imbal Time Motor Current % Imbalance Motor Current Imbal 0 l - l0 SEC l0 Increase Ramp Time 5-60 SEC 30 Decrease Ramp 5-60 SEC 30 DSABLE/ENABLE DSABLE Time Single Cycle Dropout Time 0/l NOTE: Those parameters marked with a * shall not be downloaded VALUE to the VFD, but shall be used in other calculations CL-5 and algorithms in the ICVC. O 19XRV PIC HI OIq'IONS DESCRIF1TON Auto Restart Option Remote Contacts Option Soft Stop Amps Threshold Surge/llot Gas Bypass Surge Limit/HGBP Option Select: Surge=0, HGBP=I Min. Load Point (T1, P1) Surge/ItGBP Delta T1 Surge/ItGBP Delta P1 Full Load Point TABLE RANGE 0/1 0/1 40 to 100 CONFIGURATION SIIEET UNITS DSABLE/ENABLE DSABLE/ENABLE % DEFAULT DSABLE DSABLE 100 ^F fie) 1.5(0.8) PSI (kPa) 50 (344.8) 0/1 0.5 to 20 (.3to 11.1) 30 to 170 (206.9 to 1172.2) LI3 zm (T2, P2) Surge/ltGBP Delta T2 Surge/IR_BP Delta P2 Surge/liGBP Deadband Surge Protection Surge Delta% Amps Surge Time Period VALUE 0.5 to 20 (.3to 11.1) 50 to 170 (344.8 to 1172.2) 0.5 to 3 (.3 to 1.7) C3 ^F fie) 10 (5.6) PSI (kPa) 85 (586.1) ^F (^C) 1 (0.6) z S .< D o 7to 10 % MIN 10 8 Ice Build Option Ice Build Termination 0=Temp, l=Contacts, 2=Both 0/1 DSABLE/ENABLE DSABLE Ice Build Recycle 0/1 5 to 20 LI3 Ice Build Control Oto 2 0 DSABLE/ENABLE DSABLE HA zm Iiead Pressure Reference C3 HA Delta P at 0% (4 mA) Delta P at 100% (20 mA) Minimum Output 20 to 85 (138 to 586) 20 to 85 (138 to 586) 0 to 100 psi (kPa) 25 (172) C3 (9 psi (kPa) 50 (344.8) % 0 Z o, < D o CL-6 CO/WO 19XRV PIC IIl SETUP1 DESCRHrl'ION TABLE CONFIGURATION RANGE Comp Motor Temp Override 150 to 200 (66 to 93) Cond Press Override Comp Discharge Alert 90 to 165 (621 to 1138) 155 to 170 (68 to 77) 155 to 170 (68 to 77) 125 to 200 (52 to 93) Comp Thrust Brg Alert 165 to 185 (74 to 85) Chilled Medium 0/1 Rectifier Temp Override Inverter Temp Override Chilled Water Deadband Evap Refrig Trippoint Refrig Override Delta T Evap Approach Alert Cond Approach Alert .5 to 2.0 (0.3 to 1.1) 0.0 to 40.0 (-17.8 to 4.4) 2.0 to 5.0 (1.1 to 2.8) 0.5 to 15 (0.3 to 8.3) 0.5 to 15 (0.3 to 8.3) UNITS SttEET DEFAULT °F (°C) 200 (93) PSI (kPa) 125 (862) °F (°C) 160 (71) °F (°C) 160 (71) °F (°C) 200 (93) °F (°C) 175 (79) WATER/ BRINE WATER T (_C) 1.0 (0.6) °F (°C) 33 (0.6) T (_C) 3 (1.7) T CC) 5 (2.8) T (_C) 6 (3.3) °F (°C) 34(1.1) DSABLE/ ENABLE DSABLE Condenser Freeze Point -20 to 35 (-28.9 to 1.7) Flow Delta P Display 0 to 1 Evap Flow Delta P Cutout 0.5 to 50.0 (3.4 to 344.8) PSI (kPa) 5.0 (34.5) Cond Flow Delta P Cutout 0.5 to 50.0 (3.4 to 344.8) PSI (kPa) 5.0 (34.5) Water Flow Verify Time Oil Press Verify Time Recycle Control 0.5 to 5 15 to 300 MIN SEC 5 40 Restart Delta T 2.0 to 10.0 (1.1 to 5.6) °F (°C) 5 (2.8) Shutdown Delta T 0.5 to 4.0 (0.3 to 2.2) °F (°C) 1 (.0.6) Spare Alert/Alarm Enable Disable=0, Lo=l/3, Iii=214 Spare Temp #1 Enable 0 to 4 Spare Temp #1 Limit _40 to 245 (_40 to 118) Spare Temp #2 Enable 0 to 4 Spare Temp #2 Limit _40 to 245 (_40 to 118) NOTE:Novariablesareavailablefor CCNreadoperation. Forcing 0 °F (°C) 245 (118) 0 °F (°C) shallnotbe supported CL-7 on 245 (118) servicescreens. VALUE O 19XRV PIC IH SETUP2 DESCRIPFION Capacity TABLE STATUS CONFIGURATION UNITS SIIEET DEFAULT VALUE Control Proportional Inc Band 2 to 10 6.5 Proportional DEC Band 2 to 10 6.0 Proportional ECW I to 3 2.0 Guide Vane Travel Gain Limit 30 to 100 % 80 Diffuser Option Guide Vane 25% Load Pt Diffuser 25% Load Point 0/1 0 to 78 0 to 100 DSABLE/ENABLE % % DSABLE 25 0 Guide Vane 50% Load Pt 0 to 78 % 50 Diffuser 50% Load Point 0 to 100 % 0 Guide Vane 75% Load Pt 0 to 78 % 75 Diffuser 75% Load Point 0 to 100 % 0 Diffuser Full Span mA 15 to 22 mA 18 Diffuser Control U3 zm u3 q D VFD Speed Control VFD Gain VFD Increase z L) 0.1 to 1.5 Step 0.75 1 to 5 % 2 VFD Minimum Speed 65 to 100 % 70 VFD Maximum Speed 90 to 100 % 100 U3 zm u3 Z q L) CL-8 CO/WO 19XRV PIC HI LEADLAG DESCRIF1TON TABLE CONFIGURATION RANGE UNITS StlEET DEFAULT Lead Lag Control LEAD/LAG: Configuration DSABLE=0, LEAD=l, LAG=2, STANDBY=3 0 to 3 Load Balance 0/1 DSABLE/ENABLE DSABLE 0/1 DSABLE/ENABLE DSABLE LAG% Capacity LAG Address 25 to 75 1 to 236 % 50 92 LAG START Timer 2 to 60 MIN 10 LAG STOP Timer 2 to 60 MIN 10 2 to 30 MIN 5 0/1 DSABLE/ENABLE DSABLE 25 to 75 I to 236 % 50 93 Common PRESTART STANDBY Option Sensor Option FAULT Chiller Timer Option STANDBY% Capacity STANDBY Address 0 CL-9 VALUE O 19XRV PIC III RAMP_DEM DESCRIFI'ION RANGE Pulldown Ramp Type: Select: Temp=0, Load=l Demand Limit CONFIGURATION UNITS SIIEET DEFAULT 0/1 1 0/1 0 VALUE and kW Ramp Demand Limit Source Select: Amps=0, kW= 1 Amps or kW Load Ramp% Demand Demand TABLE Limit Prop Band Limit At 20 mA 20 mA Demand Limit Opt Demand Watts Interval Min 5 to 20 10 3 to 15 40 to 100 % % 10 40 0/1 5 to 60 DSABLE/ENABLE MIN DSABLE 15 lad 19XRV PIC Ill TEMP_CTL TABLE CONFIGURATION zm SIIEET lad DESCRIlrl'ION RANGE UNITS DEFAULT Control Point VALUE _3 ECW Control Option DSABLE/ENABLE DSABLE ^F (^C) 3 (1.7) -30 to 30 (-17 to 17) ^F (_C) 10 (6) Temp -> No Reset -40 to 245 (-40 to 118) DEG F (C) 85 (29) Temp -> Full Reset -40 to 245 (-40 to 118) DEG F (C) 65 (18) -30 to 30 (-17 to 17) ^F (^C) 10 (6) Temp Pulldown Deg/Min 0/1 2to 10 (1.1 to 5.6) Z o, < Temperature Reset RESET TYPE 1 Degrees Reset At 20 mA RESET TYPE 2 Remote Remote Degrees Reset RESET TYPE lad _3 3 lad CIIW Delta T -> No Reset 0 to 15 (0 to 8) ^F (_C) 10 (6) CIIW Delta T -> Full Reset 0 to 15 (0 to 8) -30 to 30 (-17 to 17) _F (_C) 0 (0) ^F (_C) 5 (3) Degrees Reset Enable Reset Type zm Z o, 0 to 3 0 CL-10 < CO/WO BROADCAST DESCRIF1TON Time Broadcast Enable (BRODEF) CONFIGURATION RANGE StlEET UNITS DEFAULT DSABLE/ENABLE DSABLE I to 12 4 Start Day of Week Start \¥eek 1 to 7 1 to 5 7 1 Start Time Start Advance 00:00 to 24:00 0 to 360 Stop Month 1 to 12 10 Stop Day of Week 1 to 7 7 Stop Week 1 to 5 5 Stop Time 00:00 to 24:00 Stop Back 0 to 360 Daylight Savings Start Month HH:MM MIN 02:00 0 02:00 MIN CL-II 0 VALUE CO/_O_ ICVC DISPLAY AND ALARM SItUTDOWN fPRIMARY STATE RECORD SIIEET MESSAGE: SECONDARY DATE: MESSAGE: TIME: COMPRESSOR ONTIME: CHW IN CHW OUT EVAP REF CDW IN CDW OUT COND REF LU z u C3 LU tm Z o, < io OILTEMP OILPRESS COMMUNICATION AMPS %IN MESSAGE LU CCN LOCAL RESET 2: MENU u rm J LU IS c_ Z o, < io Copyright 2005 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Book 2J2 Tab F PC 211 Catalog No. 531-988 Printed in U.SA. or designs without notice and without incurring obligations. Form 19XRV-1SS CL-12 4-05 Replaces: New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 148 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Wed Apr 04 20:26:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools