CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0601181

User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides

Open the PDF directly: View PDF PDF.
Page Count: 72

DownloadCARRIER  Air Conditioner/heat Pump(outside Unit) Manual L0601181
Open PDF In BrowserView PDF
40UV, UH050-200
Unit Ventilators
with Product Integrated Control (PIC)

Installation, Start-Up and Service Instructions
CONTENTS

SAFETY CONSIDERATIONS
Page
]
],2
1
]
t
I
2
2
2-24
2
2
8
8
8
23
24
24-46
24

SAFETY CONSIDERATIONS ............................
INTRODUCTION ......................................
PREINSTALLATION .....................................
Unpack and Inspect Units ..............................
Protect Units From Damage ............................
Prepare Jobsite for Unit Installation ....................
Identify and Prepare Units .............................
PHYSICAL DATA........................................
INSTALLATION ......................................
Placing Vertical Units in Position .......................
Placing Horizontal Units in Position ....................
Make Piping Connections ...............................
Make Electrical Connections ............................
Actuators (Field-Supplied) ..............................
Make Duct Connections ..............................
Make Final Preparations ..............................
PRODUCT INTEGRATED CONTROL ................
Physical Characteristics ..............................
Unit Ventilator Comfort Control Module
Installation and Field Wiring ........................
27
Sensors ..............................................
29
Carrier Comfort Network_ Interface ..................
38
Relays ................................................
39
Actuators .............................................
39
Direct Expansion (DX) Cooling ........................
41
DX System Design ....................................
41
Electric Heat ..........................................
42
Remote Start .........................................
42
Fire/Smoke Status Input ..............................
42
Valves ................................................
43
SET-UP, CONFIGURATION, AND
OPERATION ......................................
46-49
START-UP ............
.................................
50
SERVICE ............................................
50-66
Preventing Excessive Condensation on Unit..........
50
Check Drain ..........................................
50
Fan Motor Bearings ...................................
50
Fan Shaft Ball Bearing ................................
50
Clean Fan Wheel ......................................
50
Clean or Replace Air Filters ...........................
50
ECM Motor Removal and Reinstallation ...............
50
Blower Assembly Section Removal
and Reinstallation ..................................
52
Coil Assembly Removal and Reinatallation ...........
53
Ball Bearing Replacement ............................
57
Blower Wheel Removal and Reinstallation ............
62
Sleeve Bearing Replacement .........................
63
Damper Section Removal and Reinatallation ..........
65
TESTING ............................................
67-71
Water Valve Tests .....................................
67
Face and Bypass Damper Tests ......................
67
Dampers ..............................................
Fan Tests .............................................
68
Filter Maintenance ....................................
68
Remote Start Input ....................................
68
Sensors ..............................................
68
Fire Shutdown Option ................................
68
Electric Heat and Direct Expansion Cooling ..........
68
Mixed-Air Damper Sensors Final Calibration ..........
69
Testing Completion ...................................
69
Unit Diagnostics and Troubleshooting ................
69

Book 3

Installation and servicing of this unit can be hazardous due
to system pressure, electrical components and equipment
location (such as a ceiling or elevated structare). Untrained
personnel can perform the basic maintenance functions of
replacing fdters. Only trained and qualified service personnel
should perform all other operations.
When installing this unit, observe precautions in the literature, tags and labels attached to the equipment, and any other
safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling and installing this accessory.
• Use quenching cloth for all brazing operations.
• Have
fire extinguisher
available
for all brazing
operations.

Before perfomamg service or maintenance operations, tam
off main power switch to the mill Electrical shock could
cause personal injury.

INTRODUCTION
This document contains general installation instructions for
the 40U_,UH unit ventilators and information and _coubleshooting of the Product Integrated Control (PIC) option.
See submittal drawings for unit configurations, dimensions,
clearances, and pipe connections. Refer to unit wiring label for
all electrical connections; follow NEC (National Electrical
Code) and local codes.

PREINSTALLATION
Unpack and Inspect UnitsRemove shipping wraps
from all units. Check the shipment against shipping order. If
shipment is damaged or incomplete, file claim with transportation company and advise Carrier immediately.
Protect
Units From Damage -- To maintain warranty, protect units against adverse weather, theft, vandalism,
and debris on jobsite. Do not allow foreign material to fall into
drain pan. Prevent dust and debris from being deposited on
motor and fan wheels.
If the equipment is stored for any length of time before installation, it should remain in its shipping container in a clean,
dry, and climate controlled area.

Prepare Jobsite

for Unit Installation -To save
time and to reduce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all
critical dimensions such as pipe, wire, and duct connection
requirements. Refer to job drawings and product dimension
drawings as required. Insmlct all Wades in their part of the
installation.

Manufacturer reserves the Hght to discontinue, or change at any 11me,specifications or designs wi_out notice and without incurring obligatlot_.s.
Catalog No 534-094
Printed in U.S.A.
Form 40UV, UH-6SI
Pg 1
7-05
Replaces: 40UV, UH-3SI

Identify and Prepare

Units

1. Be sure power requirements
match available power
source. Refer to the unit nameplate and wiring diagram.
2. Remove front (40UV) or bottom (40UH) access panels
from the unit. Retain the 5/32-in. socket bead fastcners and
panels for minstallation later.
3. Rotate the fan shaft by hand to ensure that fans are
unresWicted and can rotate freely. Check for shipping
damage and fan obstructions.

PHYSICAL
Component
Table I.

DATA

weight data of 40UV, LrH units is provided in

INSTALLATION

Units must be installed level and plumb. Failure to do so
may result in excessive vibration and/or premature failure.

Placing Vertical
l.

Units in Position
Select the unit location; ensure that service clearance is
provided. Allow enough grille clearance to maintain
unrestricted airflow. See submittal drawings and Fig. 1
and 2 for dimensions.

2. Make sore wall behind unit is smooth and plumb; ff
necessary, install furring strips on walls with irregular
surfaces or mullions. Furring strips must be positioned
behind mounting holes in unit. Fasteners, furring strips,
and other seals (if required) must be field supplied.
3. Remove all wall and floor moldings from behind the unit4. Move unit into position. Unit must be snug against wall
and furring strips.

5. Adjust unit leveling legs so unit is level. Unit must be
level for proper operation and condensate drainage.
6. Using field-supplied fasteners, reach into unit and attach
unit to the wall using the 3/4 in. mounting holes in the
back panel.
7. Protect the unit from jobsite debris. Do not allow foreign
material to fall into drain pan. Prevent dust and debris
from being deposited on motor or fan.

Placing Horizontal

Units

in Position

l. Select the unit location; ensure that service clearance is
provided. Allow enough grille clearance to maintain ura'estricted airflow. Make sure that ceiling is able to support
the weight of the unit. See Fig. 3-5 for nominal unit weight.
See submittal drawings and Fig. 3_5 for dimensions.
NOTE: See page 23 for additional requirements for units
ducted to multiple openings.
2. Ensure that bottom panels have been removed from unit_
When unit is lifted, access to the 3/4in. mounting holes is
through the bottom of the unit- Hanger rods and fasteners
and other required hardware must be field supplied.
3. Using a forklift or other mechanical lifting device, raise
the unit to the mounting position. If forklift or other
lifting device is likely to contact a painted wall surface,
protect the surface as necessary.
4. Use rods and fasteners to suspend the unit at the mounting
holes on the top of the unit. The unit must be suspended at
the 3/4in. mounting holes; do not use any other locations.
5. If desired, install field-supplied vibration isolators. Adjust
isolators so unit is uniformly suspended and pitched.
6. To ensure proper drainage and operation, ensure unit is
level and tighten all fasteners. DO NOT mount the unit
on a slope. Pitch of horizontal suspended units can
change after coil is filled; recheck after filling coil.
7. Protect the unit from jobsite debris. Do not allow foreign
material to fail into drain pan. Prevent dust and debris
from being deposited on motor or fan.

Table I -- Physical Data
UNIT 40UV, UR

050*

NOMINAL AIRFLOW (CIm)
FANS
Quantity

500

075

100

750

1000

125

150

200"

1250

1500

2000

1

2

3

4

5

5

0.32
8

8.32
8

8.32
8

8.32
8

8.32
8

9.5
6

9 x 241/4

9x36 l&

9x 481/4

9 x 601/4

9 x 721/+

9 x 731/4

1

1

1

1

1

1

40UV ERIPPING WEIGHT _
(Appfox Ib
16Sla in. Deep Unit
21_1e In. Deep Unit
40UH SHIPPING WEIGHT'*
(Appro_ 1t3)

330
340

400
410

480
499

590
605

660
6/5

30Vz In. Deep Unit

--

420

500

620

690

36 In. Deep Unit
40 In. Deep Unit
44 in. Deep Unit
40UV INSTALLED
WEIGHT**
(Approx Ib
16s/+ in. Deep Unit
217/s In. Deep Unit
40UH INSTALLED
WEIGHT**

--.....

500
530

600
640

740
790

830
880

315
325

380
390

460
470

570
595

640
655

---.....

405
485
515

480
580
620

600
720
770

670
810
860

1.5

2.0

2.4

Diameter (in. I
Width On-)
RLTERS

Rom,=,s .llo
,nasok
l,I
Romthal

Size

•t_in_ 2 in_ thlOkn

Quantity

,.x301 .

)

---

-1020
1050

---

(Approx
th)
30V= In. Deep Unit
36 in. Deep Unit
40 in. Deep Unit
44 in. Deep Unit
COil_ WATER WEIGHT
(Approx Ib per row of coil)
COB. CONr4_i
iur_S (in. OD)
Water Coils with 1 to 5 Rows
Steam Coils (All Units)
DX Coils
LEGEND
DX -- Direct Expansion

1 .O

-1_)00
1030

2.7

Return
_/8
7/a
Suction
7/e

27

Supply
7,s
11/a
LJquid
3/a
"4OUV only,
1"40UH 40 and 44 in. deep units onnly..
_Weight
based
controls.

on damper_ordro|led

unit

with 5-row

coil and

factory-fastalled

REMOVABLE BOTFOM PANEL
.78

_

10.61 _(EACHEND)

(_'P)_I

I _

12.37 F.... if

r

r.... _

t

522 +opwEw

2°OCK
DISCHARGE GRILLE

Wl
(SEE NOTE 2)
12.10 (TYp)
1.00
(UNIT SHOWN
WITH 1,00" END

/
----9

II O

PANELS)

--J ,"4 _BOX

I
I

,/J

200

r-_

L

TUNNEL-_
ELECTRICAL

I

]_--J
CCN
CONTROLLER
(OPTIONAL)

L

L

_#

_4
LJ
...................................

FRONT SERVICE
PANELS
(SEE NOTE 3)

FRONT

_

NON-FUSED
DISCONNECT
SWITCH

.,.

2.08

VIEW

13.oo
F

--RECESSED
RETURN
AIR/KICK PANEL

RIGHT SIDE VIEW
8.08
REMOVABLE
(TYP-SEE
( EACH END)
NOTE 2) PIPE TUNNEL_

7.04GYP)

PANEL

1.54 (TYP)
3 ACCESS
OPEN[NG
(EACH END)

7.00(TYp)

22.00

18.25

#
L

(_ 25
(MOUNTING
HOLES-TYP4 PLACES)

UNIT
40UV

AIRFLOW
(cfm)

OPENING AIR
_--OUTSIDE

L
4.50

.90

REAR VIEW

DIMENSIONS(in.
Wl
W2
W3

050
075

500
750

50
62

24
36

16.60
31,67

100
125
150

1000
1250
1500

74
86
98

48
60
72

46.74
61,81
78.47

APPROXIMATE
SHIPPING
WEIGHT (Ib)
330
400
480
590
660

2.00

(TYP)
6.75 (TYP)

LEGEND
CCN --

APPROXIMATE
INSTALLED
WEIGHT (Ib)
315
380
480
570
640

Carrier Comfort Network_

NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panets.
3. Three front panels provided for service access.
4. Motor and electrical power input box on right side of
unit. Box includes fan speed switch. OrdOff switchand
non-fused disconnect switch.
5. Connection hand is determined by facing discharge of
unit.

Fig. 1 -- 40UV Dimensions -- 16s/e-in. Deep Units
(Standard)

5.98
ITS)--

12.37

5Z_
2.08

j

s
5.22

TOP VIEW _
BARSTOCK
DISCHARGEGRILLE
W1
(SEE NOTE2)

1.00
(UNIT SHOWN
WITH 1.00" END
PANELS)

12.00 _FY'P)

1.7
2.404_.

--MOTOR

/

_--2oo

I 7_

Fsox

14:

ELECTRICAL

CCN
CONTROLLER
(OPTIONAL)

_

/

7-J
=

DISCONNECT
SSWlTCH NON-FUSED

/ /
/

L

.................................

FRONT SERVICE
PANELS
(SEE NOTE 3)

_//J

TUNNE
PIPINGL_

iii

; ;
II

__

-RECESSED RETURN
AIR/KICK PANEL

FRONT VIEW

END VIEW
REMOVABLE PANEL
(EACH END)

B.08

7.04 (TYP)

NOTE 2)

CCESS
OPENING
(EACH END)

W2

18.25

OUTSIDE AIR
OPENING
,75
(MOUNTING
HOLE_-TYP*
4 PLACES)

4.50

LEGEND

REAR VIEW

050
075

500
750

50
62

24
36

16.60
31,67

APPROXIMATE
SHIPPING
WEIGHT (Ib)
340
410

100

1000

74

48

48.74

490

125
150

1250
1500

86
98

60
72

61.81
78.47

605
675

UNIT
40UV

AIRFLOW
(cfm)

DIMENSiONS(in.)
Wl
W2
W3

CCN -- Carrier Comfort Network_

APPROXIMATE
INSTALLED
WEIGHT (Ib)
325
390
470
595

NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Three _ont panels provided for service access.
4. Motor and electrical power input box on right side
of unit. Box includes fan speed switch, On/Off
switch and non-fused disconnect switch.
5. Connection hand is determined by facing discharge of unit.

655

Fig. 2 -- 40UV Dimensions -- 2171a-in.Deep Units
(With Piping Chase)

4

30.50

FRONTVIEW

DISCHARGE GRILLE
(OPTIONAL)

LEFT SIDE VIEW
Wl
(SEE NOTE 2)

loo_L

F

MOTOR

;

(UNIT SHOWN
WITH 1,00" END

/t

r-Z,_

PANELS)

JL_

2.00
ELECTRICAL
BOX

I

_NON-FUSED
DISCONNECT
SWITCH

(mmmmmlm
L

CCN
CONTROLLER
(OPTIONAL)
BOTFOM SERVICE
PANELS
(SEE NOTE 3)

BOTTOM VIEW

--_

RL-I-URN AIR
LOUVERED PANEL
(OPTIONAL)

8.0S
(TYP-SEE REMOVABLE PANEL
NOTE 2) (EACH END)

1.54

(TYp)

17.50

18.25

(_.75
(MOUNTING
HOLES-TYP-

OUTSIDE AIR
OPENING

--

2.50

(TYP)

4.50

6.75 (TYp)
TOP

4 PLACES)

2.27

VIEW

W2

3 00

5me0I\
l+
\ --REAROUTS,DE
m

__:E?OP N' N(OPT'ONAL'
L__
5.76
AIR OPENING (OPTIONAL)

LEGEND
CCN --

Carrier Comfort Network_

DIMENSIONS(in.)

REAR VIEW

UNIT

AIRFLOW

40UH
075
100

(cfm)
750
1000

Wl
62
74

W2
36
48

W3
31.67
46.74

APPROXIMATE
SHIPPING
WEIGHT (Ib)
420
500

125
150

1250
1500

86
98

60
72

61.81
78.47

620
690

APPROXIMATE
INSTALLED
WEIGHT (Ib!
405
480
6OO
670

NOTES:
1. All dimensions are in inches.
2, Dimension does not include end panels.
3. Two bottom panels provided for service access.
4. Motor and electrical power input box on right side of
unit. Box includesfan speed switch. On/Off switch and
non-fused disconnect switch.
5. Connection hand is determined by facing discharge of
unit.

Fig. 3 -- 40UH Dimensions -- 301/2-in. Deep Units

II
II IIl_lllllll_lllllllll_Jlrll|
IIIIl_llllllllllllllllllFJl|

;............

_

36.00

W5
(OPENING)

FRONT VIEW

SIDE

(SIZE

DOUBLE
DEFLECTION

(SEEWl
NOTE 2)

I--4- 750

I

(TO OPENING)
DISCHARGE GRILLE
(OPTIONAL)

1.00
(UNIT SHOWN
WITH 1.00"
END PANELS)

4.OO

3

,,,,,

W3 (OPENING)

LEFT SIDE VIEW
(SIZES 075 TO 150)

LEFT

15.5

II .........

- ELECTRICAL
BOX

CCN
CONTROLLER
(OPTIONAL)

VIEW

200)

RETURNAIR
_/
LOUVEREDPANEL
(OPTIONAL)
BO'I-rOM VIEW

BOTTOM SERVICE
PANELS
(SEE NOTE 3)

8.00

NON-FUSED
DISCONNECT
SWITCH

g_.75
(MOUNTING HOLESTYP-4 PLACES)

--

NOTE 2)
REMOVABLE PANEL
(EACH END)

17.50

W4

2.50
(TYp)

3.67

(ryP)

LEGEND
CCN-

Carrier Comfort Network_

UNIT AIRFLOW
40UH
(ofm)

DEPTH
(in.)

DIMENSIONS

(in.)

APPROXIMATE
SHIPPING
WEIGHT_b)

Wl

W2

W3

W4

W5

075
100

750
1000

36
36

62

36

36

18.67

7.00

500

74

48

48

18.67

7.00

600

125
150

1250
1500

36
35

86

60

60

18.67

7.00

740

98

72

72

18.67

7.00

830

200

2OOO

40

98

72

72

26.92

10.00

1020

APPROXIMATE
INSTALLED
WEIGHT (Ib)
485
58O
720
810
1 O00

NOTES:
I. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service
access.
4. Motor and electrical power input box on
right side of unit. Box includes fan speed
switch, On/Off switch and non-fused disconnect switch.
5. Connection hand is determined by facing
discharge of unit.

Fig. 4 -- 40UH Dimensions -- Front Discharge Units

t
16.63

1 °00---1

FRONT VIEW

LEFT SIDE VIEW
(SIZES 075 TO 150)
1.00
(UNIT
4.00

_

I

_

__

7.50

WITH 1.00"
END PANELS)

L__ _PIPE
"1_TUNNEL

W3
(OPENING)
(SEE
NOTE 2)

SHOWN
--

!

I

W5 (OPENING

ilIiii

:

O

i

f
LEFT SIDE VIEW
(SIZE 200)

- ELECTRICAL
BOX

J

-----7

'

_-]IUlIIIIII

CCN
CONTROLLER

I Ly-

(OPTIONAL)

RETURN AJR
LOUVERED
PANEL
(OPTIONAL)

BOTTOM SERVICE
PANELS
(SEE NOTE 3)

Bo'n'OM

DISCONNECT
SWITCH

VIEW

8.00
1.00 (TYp)

(TYP)
NOTE 2)

475
_l--

REMOVABLE PANEL
(EACH END)
OPENING

(OPTIONAL

17.50

W4

_

2.50

3,67
(TYP)

1.25

(TYP)

4.50
TOP VIEW

(_ .75
(MOUNTING HOLES--TYP-4 PLACES)
2.27
5.00 _

_1 REAR OUTSI DWE2AIR

/

I OPENING(C)PTIONAL)7

l

_

300
"

iL
II 3_!
575
_

LEGEND
CCN --

Carrier Comfort Network_

o

,,

IT II

_,_G(%_,_N%)_
REAR VIEW

DIMENSIONS

(In.)

APPROXIMATE
SHIPPING
WEIGHT (Ib)
530

APPROXIMATE
INSTALLED
WEIGHT (Ib)
515

UNIT

AIRFLOW

DEPTH

40UH
075

(cfm)
750

(in.)
40

Wl
62

W2
36

W3
36

W4
18.67

W5
7.00

100

1000

40

74

48

48

18.67

7.00

640

620

125

1250

40

86

60

60

18.67

7.00

790

150

1500

40

98

72

72

10.67

7.00

880

770
86O

200

2000

44

98

72

72

26.92

10.00

1050

1030

NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service
access.
4. Motor and electricel power input box on
right side of unit. Box includes fan
speed switch, OnJOff switch and nonfused disconnect switch.
5. Connection hand is determined by facing discharge of unit.

Fig, 5 -- 40UH Dimensions -- Down Discharge Plenum

Make Piping Connections -- Access to piping is
available through the access panels at the front, top, or end of
the vertical unit (horizontal access from bottom or side). Route
piping through the pipe tunnel or the unit's back panel or floor
panel. Metal blank-off panels must be trimmed to complete
piping installation. All piping connections must be performed
by qualified personnel in accordance with local and national
codes.
DRAIN CONNECTIONS
-- Condensate drain connections
are located on each end of the drain pan near the bottom of the
unit. Condensate drain line must be 3/4 in. copper tubing,
.galvanized pipe, PVC or similar plastic pipe. Install drain line
m accordance with all applicable codes. Insulate the drain
line to prevent sweating. See Fig. 6 for typical drain trap
construction.
Units with cooling coils require traps to prevent air from
entering the condensate fitting and preventing proper drainage.
Drain must flow downhill from the unit a minimum of 1/_in.
per ft. Drain must be flee and clear at all times.

3/4"
GALVANIZED PiPE

3/4"
PVC OR COPPER

3" MIN

3" MIN

2" MIN

2" MIN

Fig. 6 -- Typical Condensate Drain Trap
Construction
EQUALIZER
_/
I

SENSING BULB (CLAMPED TO
SUCTION LINE AND INSULATED)

__

Insulate drain lines to prevent condensate. Care must be
taken to avoid interference with control panel on left side
drain.
WATER SUPPLY/RETURN CONNECTIONS -- Install pipmg in accordance with all apphcable codes. All piping must be
supported separately from coils.
Water supply must be connected so that entering water is on
leaving-air side of coil. See the connection labels on the unit to
locate the inlet. Coils must be adequately vented to prevent air
binding. Be sure valves are in proper operating position and are
easily accessible for adjustment.
If coil and valve package connections will be made with a
solder joint, care should be taken to ensure that components in
the valve package are not subjected to high temperatures which
may damage seals or other materials. Many 2-position electric
control valves are provided with a manual operating lever. This
lever should be in the OPEN position during all soldering
operations.
If coil connection is made with a union, the coil side of the
union must be prevented from turning (it must be backed up)
during tightening. Do not overdghten? Overtightening will distort (egg shape) the union seal surface and destroy the union
NOTE: A freezestat is factory-installed when a hot water/steam
coil is installed.
STEAM CONNECTIONS
-- On units with steam heating
coils, the maximum steam pressure applied to the unit should
never exceed 10 psig (operating pressure 6 psig).
DIRECT EXPANSION REFRIGERANT PIPING -- Use the
condensing unit manufacturer's recommended line sizes and
requirements. Perform leak test using nitrogen. Evacuate and
charge per recommended heating, ventilation, and air conditioning (HVAC) procedures and all applicable codes. Insulate
suction line after leak test up to the coil section end plate for
correct operation and to ehminate sweating. Use refrigerantgrade copper lines only. The unit is NOT to be apphed as a
heat pump.
See Fig. 7 for refrigerant piping connections with recommended locations for the thermostatic expansion valve (TXV)
and sensing bulb.
HYDRONIC COIL PIPING -- When all joints am complete,
perform hydrostatic test for leaks. Vent all coils at this time.
Cheek interior unit piping for signs of leakage from shipping
damage or mishandling. If leaks are found, notify a Carrier
representative before initiating any repairs. Release trapped air
from system (refer to Make Final Preparations section).

_

SUCTION LINE

LIQUID LINE

NOTE: FollowTXV manufacturer's
instructions.
Fig. 7 -- Typical TXV (Thermostatic
Valve) Installation

Expansion

All water coils must be protected from freezing after initial
filling with water. Even if system is drained, unit coils may
still have enough remaining water to cause damage when
exposed to temperatures below freezing.
Following the hydrostatic test, insulate all piping up to the
coil section end plate to prevent sweating.
To ensure compliance with building codes, restore the structtue's original fire resistance rating by sealing all holes with
material carrying the same fire rating as the structure.
Make Electrical
Connections -- Refer to unit serial
plate for required supply voltage, fan and heater amperage, and
required circuit ampacities. Refer to unit wiring diagram for
unit and field wiring. See Tables 24 for electrical data.
All input power wiring connections are accessed through
the electrical panel on front right-hand side of the unit. Use the
openings that am for the piping connections. See the dimensional drawings Fig. 1-5 for electrical box connections.
The fan motor should never be controlled by any wiring or
device other than the factory-supplied switch or thermostat/
switch combination unless prior factory authorization is obtained. Fan motor may be temporarily wired for use during
construction only with prior factory approval and only in strict
accordance with the instructions issued at that time.
All electrical connections should be made by qualified personnel and be in accordance with governing codes and ordinances. Any modification of unit wiring without factory authorization
will invalidate all factory warranties and nullify any agency listings. See Fig. 8A and 8B for typical wiring connections for basic
unit with CCN (Carrier Comfo_ Network®) controls.

Actuators (Field-Supplied) -- Field-supplied actuators
must be mounted on l/z in. diameter damper shafts.

Table 2 -- Electric Heater Data for Units with PSC Motor
HP

UNIT

NOMINAL
V/PWHz

208/1/60

240/1/60

277/1/50
40UV060
(at 500 Cfm)

1/s
208/3/60

NUMBER
OF
ELEMENTS

FLA

3
4

17.2
22.2

5

27.3

6
3
4

32.3
19.5

460/3/60

----

MCA -MOCP -PSC

--

90
97
104
119
97
106

TOTAL
CAPACITY

MCA

MocP

21.5
27,8

25
30

3.2
4,2

34.1

35

5.3

40.4
24.4

45
25

6.3
4.2

31,7
39.0

35
40

5.6
7.0

46.3
21 ,O

50
25

8,4
4.2

(kW)

25.3
31.2

6
3

37.0
16.8

115
124
97

4
5

21.8
26.9

106
115

27.3
33.6

30
35

5,6
7,0

6
3

31.9

124

39.9
13.5

40
15

8.4
3.2

19.6

20

4.2

24.4
24.4
15.1

25
25
20

5.3
6.3
4.2

106
116
124

22.4

25

5.6

27.8
27.8

30
30

7.0
8.4

07

7.5
11.1

15
15

4.2
5.6

13.8
13.8

15
15

7.0
8.4

4
5

4
5
6
3

10.8
15.8
19.5
19.5
12.1
17,9
22.2
22.2

4

6.0
8.9

5
6

11.0
11,0

LEGEND
OX
FLA
I.AT

(F)

5

6
3
240/3/60

LAT

Direct Expansion
Full LoadAmps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse S_ze
or Circuit Breaker Amps)
Permanent Split Capacitor

90
97
104
110
97

106
115
124

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat posiiton only and connections are on the right side.
4. Face and bypass units are available with 3 heating elements
only.

Table 2 -- Electric Heater Data for Units with PSC Motor (cont)
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/60

NUMBER
OF
ELEMENTS
3

23.7

4

30.9
38.1

5
6

240/1/60

40UV, UH075
(at 750 Cfm)

MCA -MOCP -PSC

--

3O
40
50

6.0
7.5

108

47.6
56.7

96
104

33.8
44.2

6O
35

9.0
6.0

113
121

54.6

45
60

65,0
29.1

70
30

38.1
47.1

40
50
60

(kW)
4.5

3
4

30.5

96
104

5

37.7
44,9

113
121

14.5
21.7

99

56.2
18.2

96
102

27,2
33.8
33.8
20.6

40
40

8.0
10.0
12.0

4
5

27.0
27.0

20
3O
35

8.0
10.0
12.0
4.5
6.0
7.5
9.0

4

16.5
24.8

5

30.9

113

6

30.9
8.2

121
96

38.6
38.6
10.2

15

6.0

5

12.3
15.4

104
113

15,4
19.2

20
20

8.0
10.0

6

15.4

121

19,2

20

12.0

4

31.0

35

8.0
10.0
12.0
6.0

103
96
104

LEGEND
---

29.6
38.6

43.7
52.0
23.3

3

DX
FLA
I-AT

69
96
102

35.3

3

460/3/60

MOCP

5

6

240/_60

MCA

4

3
208/3/60

TOTAL
CAPACITY

(F)

45.3
27.0

6

1/5

LAT

3

6

27711/60

FLA

25
35

6.0

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position onlyand connections are on the rightside.
4. Face and bypass units are available with 3 heating elements
only,

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
U nit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

z0

Table 2 -- Electric Heater
uNrr

HP

NOMINAL
v/Ph/Hz

208/1/60

240/1/60

277/1_0
40UV, UH1OO
(at 1000 Cfm)
208/3/60

240/3/60

460/3/60

Data for Units with PSC Motor (cont)

NUMBER
OF
ELEMENTS

FLA

TOTAL
CAPACITY

(F)

MCA

MOCP

38.6

40
60

6.0
8.0

(kW)

3
4
5

30.9
40.5

89
95

50.2

102

50.7
62.7

70

10.0

6

59.8
35.3
46.5

I O8
96

74.7
44,2

80
45

11,9
8.0

104

58.1

57.6

112
121
96

72,0
85.8
38.1

60
80
90

10,7
13.3
16.0

I04
112

50.1

5
6

40.1
49.7
59,4

3

18,7

4
5

28.3
35.4

89
95
102

6
3

35.4
21.3

108

44.3
44.3

96

26.6

4

32.4

5
6
3

40.5
40.5

104
112

40.5
50.7

121
96

50.7

3
4
5
6
3
4

4
5
6

68.7
30.5

10.6
16.1

121

62.2
74.2
23.4
35.4

40

8.0

60
70

10.7
13.3

80
25

16.0
6.0

40
45

8.0
10.0

45

11,9

30
45

8.0
10.7

60
60

13.3
16.0

13.2
20.1
25.2

15
25

8.0
10.7

20.2

104
112

30

13.3

20.2

121

25.2

30

16.0

LEGEND
DX
FLA
LAT

LAT

NOTES:
t. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the rightside.
4. Face and bypass units are available with 3 heating elements
only.

----

Direct Expansion
Full LoadAmps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
-- Permanent Split Capacitor

1]

Table 2 -- Electric
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/60

240/1/60

277/1/60
40UV, UH125
(at 1250 Cfm)

1/s
208/3/60

240/3/60

460/3/60

Heater Data for Units with PSC Motor (cont)

NUMBER
OF
ELEMENTS

FLA

----

MCA -MOCP -PSC

--

(F)

MCA
47.6
62.7
77.7

3
4

38.1

89

50.1

5
6

62.2

96
102

3
4

43.7

108
96

57.6

5

71.4

6*
3

85.3

4

49.7

5
6

61.8

3
4
5

22.9

6
3

43.7

4

40.0

5
6
3

50.2

13.0

96

62.7
16.2

4

19.9

5
6

25.0

104
113

25.0

121

74.2

37.7

73.8

34.9
43.7

26.1

50.2

LEGEND
DX
FLA
I.AT

LAT

MOCP

TOTAL
CAPACITY

(kW)
50
70

7.5
10.0

92.8

80
100

12.5
15.0

104

54.6
71.9

60
80

10.0
13.3

113
121

89.3
106.7

96
104
113
121
89
96
102
108
96
104
113
121

90

16,7

47.1

110
50

20.0
10,0

62.2
77.2

70
80

13.3
16,7

92.2
28.6
43.6

100
30

2O,O
7.5

45
60

10.0
12.5

54.7
32.6
50.0

60
35

15.0
10.0

50

13.3

62.7

70
70
20

16.7
20.0
10,0

24.9
31.3

25

13.3

35

16,7

31.3

35

20.0

54.7

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm,
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3, Electricheatisavailableinthereheatpositiononlyandconnections are on the right side.
4. Face and bypass units are available with 3 heating elements
only,

Direct Expansion
Full LoadAmps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

*Left hand coil connections only.

12

Table 2 -- Electric
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/60

240/1/60

277/1/60

40UV,UH150
(at 1500 Cfm)
208/3/60

240/3/60

460/3/60

Heater

Data for Units with PSC Motor (cont)

NUMBER
OF
ELEMENTS

FLA

---

MCA -MOCP -PSC

--

(F)

MCA

MOCP

56.7

60
80
100

TOTAL
CAPACITY
(kW)
9.0
12.0

3
4
5

45.3
59,8

89
96

74.2

102

74.7
92.8

6*

88.7
52.0
68.7

109
96

110.8
65.0

125
70

18.0
12.0

104
113

85.8
106.7

90
110

16,0
20.0

6O
80

12.0

3
4

15.0

5*
6

85.3

3
4

44.9

96

56.2

59,4
73.8

104
113

74.2
92.3

100

27.0

80

41.5
52.1

96
102

33.8
61.9

35
6O
70

6
3
4

52.1
30.9

108

65.1
65,1

12.0
15.0

7O
4O

18.0
12.0

5
6
3

59,8
59,8
15.4

4
5

23.7
29.8

6

29,8

5
6
3
4
5

47,5

LEGEND
DX
FLA
LAT

LAT

96
104
113
121
96
104
113
121

38.6

16.0
20.0
9,0

59.5
74.8
74.8

6O

16.0

80
90

20.0
24.0

19,2
29.6
37.3

2O
30
40

12.0
16.0

37.3

4O

20.0
24.0

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat le available in the reheat position only and connections are on the right side.
4. Face and bypass units are available with 3 heating elements
only.

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Ovemurrent Protection (Maximum Fuse SLze
or Circuit Breaker Amps)
Permanent Split Capacitor

*Left hand coil connections only.

13

Table 3 -- Electric Heater Data for Units with ECM
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/66

240/1/60

277/1/60
40UV05O
(at 500 Cfm)

NUMBER
OF
ELEMENTS
3
4
5
6

208/3/60

240/3/60

460/3/60

LAT

(F)

MCA

MOCP

16.5

90
97
104

20.6

25

3,2

26.9
33.2

30
35

4,2
5,3

21.5
26,6
31,6
18,8
24,6

110
97

39.5
23.5

40
25

6,3
4,2

106

5

30,5

30.8
38.1

35
40

5.6
7.0

6
3
4

36.3
16,3

115
t 24

45.4
20.3

50
25

8.4
4.2

21,3

97
166

26.6

30

5.6

5

26,4
31,4

115
124

33.0
39.3

35
40

7.0
8,4

10,1
15.1

90

12.6
18.9

15
20

3.2
4.2

23.5
23.5

25
25

5.3
6.3

14.3
21,6

15
25

4.2
5.6

26.9
26.9

30
30

7.6
8.4

3
4
5

---

MCA -MOCP -PSC

--

97
104

6

18.8
18.8

3
4

11.4
17.2

5
6
3

21.5
21.5
5.4

124
97

6.8

15

4.2

4

8.3
10.5

106
115

16.4
13.1

15
15

5.8
7.0

124

13.1

15

8.4

5
6

10.5

LEGEND
DX
FLA
LAT

(kW)

3
4

6

1/3

TOTAL
CAPACITY

FLA

110
97
106
115

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the rigl_ side.
4. Face and bypass units are available with 3 heating elements
only.

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

]4

Table3-UNIT

HP

NOM[NAL
V/Ph/Hz

208/1/60

240/1/50

277/1/60

40UV, UH075
(at 750 Cfm)

1/z
208/3/60

240/0/60

460/0/60

Electric

Heater

NUMBER
OF
ELEMENTS

Data for Units with ECM (cont)
FLA

3

24.0

4

31.2

5
6

38.4

3
4

27.3
35.6

96
104

5

44.0

113

6
3
4

52.3

121
96

5
6

38.1

3
4

14.8

5
6

45.6

23.7
30.9
45.3

---

MCA -MOCP -PSC

--

89
96
102
108

104
113
121
89

MCA
30.0

MOCP

TOTAL
CAPACITY

(kW)
30
40
50

4.5
6.0
7.5

60

9.0

35
45

6.0
8.0

55.0
65.4
29.6

60
70

10.0
12.0

30

6.0

38.6

40
50
60

8.0
10.0
12.0

39.0
48.0
57.0
34.1
44.5

47.6
56.7
18.5
27.6
34.2

20
30

4.5
6,0

27.3

96
102

35

7,5

27.3

108

34.2

3
4

16.8

96
104

20.9
31.4

35
25
35

9.0
6.0
8,0

5

31.2

39.0
39.0

10.0

31.2

113
121

40

6
3

10.2

12,0
6.0

4
5

12.3

96
104

40
15
20
20

8.0
10,0

6

15.4

20

12,0

22.0

25.1

8.2

15.4

LEGEND
DX
FLA
LAT

LAT
(F)

113
121

15.4
19.2
19.2

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2, Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the right side.
4, Face and bypass units are available with 3 heating elements
only,

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse S_e
or Circuit Breaker Amps)
Permanent Split Capacitor

15

Table 3 -- Electric
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/60

240/1/60

277/1/60

Heater Data for Units with ECM (cont)

NUMBER
OF
ELEMENTS

FLA

3

208/3/60

240/3/60

460/3/60

MCA

MOCP

31.5

89

39.4

4
5

41.1
50.8

95

51.4

40
60

6.0
8.0

6
3
4

60.4
35.9

102
108
96

63.4
75.5

70
80

10.0
11.9

104
112

44.9
58.8

45
60

8.0
10.7

5

47.1
58.2

13,3

69.3
31.2

121

72.7
88.6

80

6
3

40.8

39.0
51.0

16,0
8.0

4
5

96
104

90
40

112
121

63.1
75.1

60
70

10.7
13.3

24.1

80
25

16.0
6.0

28.9

89
95
102
108

36.2
45.0
45.0

40
50

8.0
10.0

6

36.0
36.0

3
4
5

21.9
33.0
41.1

96
104

27.3
41.2

50
30

11,9
8.0

45

10.7

51.4

6
3

41.1

112
121
96
104

13.3
16.0
8.0

4

10.6
16.2

60
60
15

10.7

20.3
20.3

112

20.2
25.3

25

5
6

121

25.3

30
30

13.3
16.0

4
5

50.4
60.1
19.3

LEGEND
DX
FLA
I.AT

---

MCA -MOCP -PSC

--

TOTAL
CAPACITY

(F)

6
3

40UV,UH100
(at 1000 Cfm)

LAT

51.4
13.3

(kW)

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal ctm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the right side.
4. Face and bypass units are available with 3 heating elements
onty.

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

]6

Table 3 -- Electric
UNIT

HP

NOMINAL
V/Ph/Hz

208/1/60

Heater Data for Units with ECM (cont)

NUMBER
OF
ELEMENTS

277/1/60

40UV, UH125
(at 1250 Cfm)

1/2
208/3/60

460/3/60

49.3

50

7,5

95
102
108

64.3
79.4

7O
80

10.0
12,5

94.4
56.2

100

15.0

96

73.6
90.9

10.0
13.3

72.7

1O4
113

60
80

86.6
39.0

121
96

108.3
48.7

100
110

16.7
20.0

104

63.8

50
70

10.0
13.3

5

51.0
63,1

6
3

75.1
24.2

113
121
89

78.8
93.9

80
100

16.7
20.0
7.5

36,2
45,0

96
102

30.2
45.3

35

4
5
6

45.0
27.4

108

56.3
56.3

50
60
60

10.0
12.5
15.0

96
104

34.2
51.6

35

10.0

60

13.3

113
121

64.3

70
70
20

16.7
20.0
10,0

30

13.3

35
35

16,7
20.0

4
5
6"
3
4

4
5
6
3

39.4
51.5
63.5
75.5
45.0
58.9

41.3
51.5
51.5
13.2

4

20.2

5
6

25.3
25.3

LEGEND
DX
FLA
LAT

----

MCA -MOCP -PSC

--

TOTAL
CAPACITY

89

3
240/3/60

MOCP

MCA

6
3
240/1/60

LAT

(F)

3
4
5

FLA

96
104

64.3
16.5

113

25.2
31.6

121

31.6

(kW)

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the right side.
4. Face and bypass units are available with 3 heating elements
only

Direct Expansion
Full LoadAmps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

*Left hand coil connections only.

]?

Table3-UNIT

HP

NOMINAL
VfPh/Hz

208/1/60

Electric

Heater Data for Units with ECM (cont)

NUMBER
OF
ELEMENTS

MOCP

46.7

39

61.1
75.6

96
102

58.3
76.4

60
8O

90.0

108

94.4
112.5

100
125

53.3
70.0

96
104

66.6
87.5

70

18.0
12.0

66.6

113

108.3

90
110

20.0

46.2

96
104

57.8

6O

12.0

60.7
75.1

113

93.9

8O
100

20.0

28.3
42.8

89
96

6

53.4
53.4

102
108

3
4

32.2
48.9

5
6

61.1
61.1

3
4

15.6
24.0

5
6

30.1
30.1

5
6*
4
5*
6
3

277/1/60
40UV,UH150
(at 1500 Cfm)

4
5
6
3

1/2
208/3/60

240/3/60

460/3/60

4
5

LEGEND
DX
FLA
LAT

----

MCA -MOCP -PSC

--

TOTAL
CAPACITY

MCA

3
240/1/60

LAT

(F)

3
4

FLA

96
104
113

75.8

(kW)
9.0
12.0
15.0

16.0

16,0

35.4

40

53.5
66.7

60
70

66.7
40.9

7O

15.0
18.0

45
70

12.0
16.0

8O
8O

20.0
24.0

20
3O

12.0

61.1

121
96

76.4
76.4
19.5

104
113

30.0
37.6

121

37.6

40
40

9.0
12.0

16.0
20.0
24.0

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connections are on the right side.
4. Face and bypass units are available with 3 heating elements
only.

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
Permanent Split Capacitor

*Left hand coil connections only.

]g

Table3 -UNIT

HP

NOMINAL
V/PWHz

208/1/60

Electric

Heater Data for Units with ECM (cont)

NUMBER
OF
ELEMENTS
3
4
5
6*
3

240/1/60

40UH200
(at 2000 Cfm)
208/3/60

240/3/60

460/3/60

50.1
64.6
79.0
93.5

----

MCA -MOCP -PSC

--

TOTAL
CAPACITY

(F)

MCA

MOCP

84

62.7

89
84
99

80.7
98.8
116.8

70
90
100

9.0
12,0
15.0

125
80

18.0
12.0

(kW)

89
96

71.0
91.8

100

16.0

102

112.7

125

20.0

48.8
63.3

89
96

61.0

70
80

12.0
16.0

5
6

77.7

102

100

20.0

3
4

31.8

84

5
6

46.3
56.9
56.9

89
94

3
4

35.7
52.4

5
6

64.6
64.6

3
4

16,9
25.2

5
6

31,3

4
5*

4

31.3

LEGEND
DX
FLA
I.AT

LAT

56.8
73.5
90.1

6
3
27_1_0

FLA

99
89
96
102
I08
89
96
102
I08

79.1
97,1
39.8
57.9
71.1
71.1
44.6
65.5
80.8
80.8
21.1
31.5
39.1
39.1

40

9.0

69
80

12.0
15.0

80
45
70

18.0
12.0
16.0

90
90

20.0
24,0

25

12.0

35
40

16,0
20,0

40

24.0

NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position onlyand connections are on the right side.
4. Face and bypass units are available with 3 heating elements
only.

Direct Expansion
Full Load Amps
Leaving-Air Temperature at 70 F Entedng-Air
Temperature
Unit Minimum Circuit Ampacity
Maximum Overcurrent Protection (Maximum Fuse S_-e
or Circuit Breaker Amps)
Permanent Split Capacitor

*Left hand coil connections only

19

Table 4 -- Motor Data
PSC MOTORS
UNIT 40UV,UH SIZE

MOTORHp

VOLTAGE

FLA

MCA

MOP (Amps)

115

3.7

4.6

8,3

050*

I/s

208/230
266

2.0
1.6

2.5
2,0

4,5
3,6

115
208/230

3,7
2.0

4.6
2.5

8.3
4.5

265
115

1.6
3.7

2.0
4.6

3.6
8.3

208/230
265

2,0
1,6

2.5
2,0

4.5
3,6

115

3,7

4.6

8.3

208/230
265

2,0
t .6

2,5
2,0

4,5
3,6

t 15
208/230
265

3.7
2.0
1.6

4,6
2.5
2,0

8,3
4.5
3,6

VOLTAGE

FLA

MCA

115

1.4

1.8

3.1

1.3
1,1

1.6
1.4

2.9
2.6

3,7
2,3

4.6
2.9

8.3
5.1

2.0
4,0

2.5
5,0

4.5
9.1

2,6
2.3

3,2
2,9

5.8
5.1

208/230

4.7
3.3

5.9
4.1

10.6
7.4

265

2.9

3.6

6.6

115

4.7
3.3

5.9
4.1

10.6
7.4

2.9
9,6

3.6
12.0

6.6
21.6

6.8
5.5

8.5
6.9

15.3
12.4

O75

100

'/s

125

I/s

150

MAX FUSE SIZE
(Amps)
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

ECM
UNIT 40UV, UH SIZE

MOTOR Hp

05O*

%

208/230
265
115

1/3

075

208/230
265
115

1/3

100

208/230
265
115

1/2

125

150

208/230
265
115

200t"

¾

208/236
265

LEGEND
ECM
FLA
MCA
MOP
PSC

------

Electronically Commutated Motor
Full Load Amps
Minimum Circuit Amps
Maximum Overload Protection
Permanent Split Capacitor

*Available in vertical configuration only,
"j-Available in horizontal configuration only,

2O

MOP(Am_)

MAX FUSE SIZE
{Amps)
15
15
15
15
15
15
15
15
t5
16
15
15
15
15
15
20
15
15

BLK/100

Lt --- __.,,_
115v

DISC1 • BLK/101

BLK/I_

SWl

CBC1

USE COPPER SUPPLY WIRES
N ....

I

WHT/110

BLK/10g

,.0v.c
il ,.vAc

WHT/110

WHT/I_
WHT/111

_II_RN_504

•

GND .... %

_

I

SW2

C) AUTO

BRN/51

7m

RED/511 _

!_

YEU51

WHT/515

OF F
(_ CONT

VIO/51'

V!O/516

BLU/EC9
ORN/EC2•

DISC -ECM -ESP
-FU
-GND -LLT
-SW
-TRAN ---_ _---

LEGEND
Disconnect Switch
Electronically Comrnutated Motor
External Static Pressure
Fuse
Ground
Water Coil Low LimitThermostat
Switch
Transformer
Harness Conn•ction

•

Connection Point Splice

•

Splice Terminal Connection

O

Component Tie Point

....

Optional Wiring

--

Factory Wiring
Chassis Ground
Earth Ground

BLU/51
WHT/51 Ii

I

ORN/51;

SEE NOTE 3
SPEEDBOARD

HIGH
LOW

YEUE05

=

RED,EO<.

_

5

EC
NOTES:
1. Make electrical installation in accordance with job diagram, and in compliance with naUon•l and local electrical codes,
2. Low limit thermostat (LLT) is installed on all units with water ceils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, MAX
• re for field use with increased ESR

Fig. 8A -- Unit Ventilator Wiring with CCN Controls -- Control Box (115 vac)

i ,W,RE
\J

,P,.

POWER _
CABLE

RECEPTACLE
_

_

ON MOTOR

RESISTOR HARNESS
1000 ohm

I V1C
GRI

CBC3

Jl
Power

BRN
RED
_

Detail

A - STEAM

-- _ I000 ohm_
VALVE

RAT

_CX

SAT

RED

OAT

NOTE i

NOTE 1

SPT

BLK
1"2
T1 i
T3 i

RED

WHT

SAT

RED
NOTE 3

BLU

--I
J4
Sewice

WIRING

LL

OR

T4 i
MAT T5 i
Te =

CCN

_J3

NOTE 2

w/Setp°lnt Adjust

OAT TE
TTi_.
Tg

VlO/2
See Detail A for
Slum Vah_ Wiring,

LEGEND
AQ
CCN
CGO_
CGOVR
COM
CW
ECM

t-J

-----

GND
HW
-LL
-MAT
-NC
-NO
OA
OAT
-OCC/
-UNOCC
RAT
RH
SAT
EPT
SPT ADJ

Air Quality
Carder Comfort Network®
Changeover
Changeover
Common
Chilled Water
E_ectronically
Commu
Commutatad
Motor
Ground
Hot Water
Low Limit Device
Mixed Air Temperature
Normally Closed
Normally Open
Outdcor Ad
Outdoor Air Temperature
Occupied/Unoccupied
Return Air Temperature
Relative Humdity
Supply Air Temperature
Space Temperature
Space Temperature
Adjustment
Harness Connection

SPT ADJ

csc2

Ni3

<-3

T10 i

YEI
aT26

YEI

RED

OR

BLU
rio

SpikesTerminal Connection
Component Tie Point

-_,T6_
NOTE3
BLU
BLUII
RED

REE

'2
'3 4-8
'4 (-4

YEL

I

YEL

BLU

l

BLU

F_ED

RED

_6

ORN

ORN

_7

YEL

YEL

_8

BLK

_9

GRa

GRA

TL/

1"2 Ccollng

_.

'5

v2c

T31

VIO

_

V_

_

T33

WHT

I

WHT

_

T34

OA damper no_tnRtniledon
ReclrculationOniy Uni_

eLK

BLK

_

=_

ENTHALPY
SWtTCH
SFS T17 m

BC,,_._3
c

aE°i!

L'-r T22 _

Heetlng
T37 Enable

K3

SW2_;OM

I_-

YEL

Factory Wiring

SW2-AUTO

5_

WHT

t_?_T
VIO

Chassis Ground

SW2-CONT -ECM

i _
r_

VIO
BLU

BLU

I ")

ORN

ECM

ORN

)RN

CH_VR

ORN

OCC_UNOCC
_LK/21

FIRFJSMOKE
DETECTOR

T23 m

Sp_r_ DI _4m

K2

IRN

K1

ORN/38

RED/FSD
NOTE 5

BRN

BRN

:_

TB2

FED 3"21m

T36

Comm

Navigation menu