CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0601181
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 72
Download | |
Open PDF In Browser | View PDF |
40UV, UH050-200 Unit Ventilators with Product Integrated Control (PIC) Installation, Start-Up and Service Instructions CONTENTS SAFETY CONSIDERATIONS Page ] ],2 1 ] t I 2 2 2-24 2 2 8 8 8 23 24 24-46 24 SAFETY CONSIDERATIONS ............................ INTRODUCTION ...................................... PREINSTALLATION ..................................... Unpack and Inspect Units .............................. Protect Units From Damage ............................ Prepare Jobsite for Unit Installation .................... Identify and Prepare Units ............................. PHYSICAL DATA........................................ INSTALLATION ...................................... Placing Vertical Units in Position ....................... Placing Horizontal Units in Position .................... Make Piping Connections ............................... Make Electrical Connections ............................ Actuators (Field-Supplied) .............................. Make Duct Connections .............................. Make Final Preparations .............................. PRODUCT INTEGRATED CONTROL ................ Physical Characteristics .............................. Unit Ventilator Comfort Control Module Installation and Field Wiring ........................ 27 Sensors .............................................. 29 Carrier Comfort Network_ Interface .................. 38 Relays ................................................ 39 Actuators ............................................. 39 Direct Expansion (DX) Cooling ........................ 41 DX System Design .................................... 41 Electric Heat .......................................... 42 Remote Start ......................................... 42 Fire/Smoke Status Input .............................. 42 Valves ................................................ 43 SET-UP, CONFIGURATION, AND OPERATION ...................................... 46-49 START-UP ............ ................................. 50 SERVICE ............................................ 50-66 Preventing Excessive Condensation on Unit.......... 50 Check Drain .......................................... 50 Fan Motor Bearings ................................... 50 Fan Shaft Ball Bearing ................................ 50 Clean Fan Wheel ...................................... 50 Clean or Replace Air Filters ........................... 50 ECM Motor Removal and Reinstallation ............... 50 Blower Assembly Section Removal and Reinstallation .................................. 52 Coil Assembly Removal and Reinatallation ........... 53 Ball Bearing Replacement ............................ 57 Blower Wheel Removal and Reinstallation ............ 62 Sleeve Bearing Replacement ......................... 63 Damper Section Removal and Reinatallation .......... 65 TESTING ............................................ 67-71 Water Valve Tests ..................................... 67 Face and Bypass Damper Tests ...................... 67 Dampers .............................................. Fan Tests ............................................. 68 Filter Maintenance .................................... 68 Remote Start Input .................................... 68 Sensors .............................................. 68 Fire Shutdown Option ................................ 68 Electric Heat and Direct Expansion Cooling .......... 68 Mixed-Air Damper Sensors Final Calibration .......... 69 Testing Completion ................................... 69 Unit Diagnostics and Troubleshooting ................ 69 Book 3 Installation and servicing of this unit can be hazardous due to system pressure, electrical components and equipment location (such as a ceiling or elevated structare). Untrained personnel can perform the basic maintenance functions of replacing fdters. Only trained and qualified service personnel should perform all other operations. When installing this unit, observe precautions in the literature, tags and labels attached to the equipment, and any other safety precautions that may apply. • Follow all safety codes. • Wear safety glasses and work gloves. • Use care in handling and installing this accessory. • Use quenching cloth for all brazing operations. • Have fire extinguisher available for all brazing operations. Before perfomamg service or maintenance operations, tam off main power switch to the mill Electrical shock could cause personal injury. INTRODUCTION This document contains general installation instructions for the 40U_,UH unit ventilators and information and _coubleshooting of the Product Integrated Control (PIC) option. See submittal drawings for unit configurations, dimensions, clearances, and pipe connections. Refer to unit wiring label for all electrical connections; follow NEC (National Electrical Code) and local codes. PREINSTALLATION Unpack and Inspect UnitsRemove shipping wraps from all units. Check the shipment against shipping order. If shipment is damaged or incomplete, file claim with transportation company and advise Carrier immediately. Protect Units From Damage -- To maintain warranty, protect units against adverse weather, theft, vandalism, and debris on jobsite. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor and fan wheels. If the equipment is stored for any length of time before installation, it should remain in its shipping container in a clean, dry, and climate controlled area. Prepare Jobsite for Unit Installation -To save time and to reduce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all critical dimensions such as pipe, wire, and duct connection requirements. Refer to job drawings and product dimension drawings as required. Insmlct all Wades in their part of the installation. Manufacturer reserves the Hght to discontinue, or change at any 11me,specifications or designs wi_out notice and without incurring obligatlot_.s. Catalog No 534-094 Printed in U.S.A. Form 40UV, UH-6SI Pg 1 7-05 Replaces: 40UV, UH-3SI Identify and Prepare Units 1. Be sure power requirements match available power source. Refer to the unit nameplate and wiring diagram. 2. Remove front (40UV) or bottom (40UH) access panels from the unit. Retain the 5/32-in. socket bead fastcners and panels for minstallation later. 3. Rotate the fan shaft by hand to ensure that fans are unresWicted and can rotate freely. Check for shipping damage and fan obstructions. PHYSICAL Component Table I. DATA weight data of 40UV, LrH units is provided in INSTALLATION Units must be installed level and plumb. Failure to do so may result in excessive vibration and/or premature failure. Placing Vertical l. Units in Position Select the unit location; ensure that service clearance is provided. Allow enough grille clearance to maintain unrestricted airflow. See submittal drawings and Fig. 1 and 2 for dimensions. 2. Make sore wall behind unit is smooth and plumb; ff necessary, install furring strips on walls with irregular surfaces or mullions. Furring strips must be positioned behind mounting holes in unit. Fasteners, furring strips, and other seals (if required) must be field supplied. 3. Remove all wall and floor moldings from behind the unit4. Move unit into position. Unit must be snug against wall and furring strips. 5. Adjust unit leveling legs so unit is level. Unit must be level for proper operation and condensate drainage. 6. Using field-supplied fasteners, reach into unit and attach unit to the wall using the 3/4 in. mounting holes in the back panel. 7. Protect the unit from jobsite debris. Do not allow foreign material to fall into drain pan. Prevent dust and debris from being deposited on motor or fan. Placing Horizontal Units in Position l. Select the unit location; ensure that service clearance is provided. Allow enough grille clearance to maintain ura'estricted airflow. Make sure that ceiling is able to support the weight of the unit. See Fig. 3-5 for nominal unit weight. See submittal drawings and Fig. 3_5 for dimensions. NOTE: See page 23 for additional requirements for units ducted to multiple openings. 2. Ensure that bottom panels have been removed from unit_ When unit is lifted, access to the 3/4in. mounting holes is through the bottom of the unit- Hanger rods and fasteners and other required hardware must be field supplied. 3. Using a forklift or other mechanical lifting device, raise the unit to the mounting position. If forklift or other lifting device is likely to contact a painted wall surface, protect the surface as necessary. 4. Use rods and fasteners to suspend the unit at the mounting holes on the top of the unit. The unit must be suspended at the 3/4in. mounting holes; do not use any other locations. 5. If desired, install field-supplied vibration isolators. Adjust isolators so unit is uniformly suspended and pitched. 6. To ensure proper drainage and operation, ensure unit is level and tighten all fasteners. DO NOT mount the unit on a slope. Pitch of horizontal suspended units can change after coil is filled; recheck after filling coil. 7. Protect the unit from jobsite debris. Do not allow foreign material to fail into drain pan. Prevent dust and debris from being deposited on motor or fan. Table I -- Physical Data UNIT 40UV, UR 050* NOMINAL AIRFLOW (CIm) FANS Quantity 500 075 100 750 1000 125 150 200" 1250 1500 2000 1 2 3 4 5 5 0.32 8 8.32 8 8.32 8 8.32 8 8.32 8 9.5 6 9 x 241/4 9x36 l& 9x 481/4 9 x 601/4 9 x 721/+ 9 x 731/4 1 1 1 1 1 1 40UV ERIPPING WEIGHT _ (Appfox Ib 16Sla in. Deep Unit 21_1e In. Deep Unit 40UH SHIPPING WEIGHT'* (Appro_ 1t3) 330 340 400 410 480 499 590 605 660 6/5 30Vz In. Deep Unit -- 420 500 620 690 36 In. Deep Unit 40 In. Deep Unit 44 in. Deep Unit 40UV INSTALLED WEIGHT** (Approx Ib 16s/+ in. Deep Unit 217/s In. Deep Unit 40UH INSTALLED WEIGHT** --..... 500 530 600 640 740 790 830 880 315 325 380 390 460 470 570 595 640 655 ---..... 405 485 515 480 580 620 600 720 770 670 810 860 1.5 2.0 2.4 Diameter (in. I Width On-) RLTERS Rom,=,s .llo ,nasok l,I Romthal Size •t_in_ 2 in_ thlOkn Quantity ,.x301 . ) --- -1020 1050 --- (Approx th) 30V= In. Deep Unit 36 in. Deep Unit 40 in. Deep Unit 44 in. Deep Unit COil_ WATER WEIGHT (Approx Ib per row of coil) COB. CONr4_i iur_S (in. OD) Water Coils with 1 to 5 Rows Steam Coils (All Units) DX Coils LEGEND DX -- Direct Expansion 1 .O -1_)00 1030 2.7 Return _/8 7/a Suction 7/e 27 Supply 7,s 11/a LJquid 3/a "4OUV only, 1"40UH 40 and 44 in. deep units onnly.. _Weight based controls. on damper_ordro|led unit with 5-row coil and factory-fastalled REMOVABLE BOTFOM PANEL .78 _ 10.61 _(EACHEND) (_'P)_I I _ 12.37 F.... if r r.... _ t 522 +opwEw 2°OCK DISCHARGE GRILLE Wl (SEE NOTE 2) 12.10 (TYp) 1.00 (UNIT SHOWN WITH 1,00" END / ----9 II O PANELS) --J ,"4 _BOX I I ,/J 200 r-_ L TUNNEL-_ ELECTRICAL I ]_--J CCN CONTROLLER (OPTIONAL) L L _# _4 LJ ................................... FRONT SERVICE PANELS (SEE NOTE 3) FRONT _ NON-FUSED DISCONNECT SWITCH .,. 2.08 VIEW 13.oo F --RECESSED RETURN AIR/KICK PANEL RIGHT SIDE VIEW 8.08 REMOVABLE (TYP-SEE ( EACH END) NOTE 2) PIPE TUNNEL_ 7.04GYP) PANEL 1.54 (TYP) 3 ACCESS OPEN[NG (EACH END) 7.00(TYp) 22.00 18.25 # L (_ 25 (MOUNTING HOLES-TYP4 PLACES) UNIT 40UV AIRFLOW (cfm) OPENING AIR _--OUTSIDE L 4.50 .90 REAR VIEW DIMENSIONS(in. Wl W2 W3 050 075 500 750 50 62 24 36 16.60 31,67 100 125 150 1000 1250 1500 74 86 98 48 60 72 46.74 61,81 78.47 APPROXIMATE SHIPPING WEIGHT (Ib) 330 400 480 590 660 2.00 (TYP) 6.75 (TYP) LEGEND CCN -- APPROXIMATE INSTALLED WEIGHT (Ib) 315 380 480 570 640 Carrier Comfort Network_ NOTES: 1. All dimensions are in inches. 2. Dimension does not include end panets. 3. Three front panels provided for service access. 4. Motor and electrical power input box on right side of unit. Box includes fan speed switch. OrdOff switchand non-fused disconnect switch. 5. Connection hand is determined by facing discharge of unit. Fig. 1 -- 40UV Dimensions -- 16s/e-in. Deep Units (Standard) 5.98 ITS)-- 12.37 5Z_ 2.08 j s 5.22 TOP VIEW _ BARSTOCK DISCHARGEGRILLE W1 (SEE NOTE2) 1.00 (UNIT SHOWN WITH 1.00" END PANELS) 12.00 _FY'P) 1.7 2.404_. --MOTOR / _--2oo I 7_ Fsox 14: ELECTRICAL CCN CONTROLLER (OPTIONAL) _ / 7-J = DISCONNECT SSWlTCH NON-FUSED / / / L ................................. FRONT SERVICE PANELS (SEE NOTE 3) _//J TUNNE PIPINGL_ iii ; ; II __ -RECESSED RETURN AIR/KICK PANEL FRONT VIEW END VIEW REMOVABLE PANEL (EACH END) B.08 7.04 (TYP) NOTE 2) CCESS OPENING (EACH END) W2 18.25 OUTSIDE AIR OPENING ,75 (MOUNTING HOLE_-TYP* 4 PLACES) 4.50 LEGEND REAR VIEW 050 075 500 750 50 62 24 36 16.60 31,67 APPROXIMATE SHIPPING WEIGHT (Ib) 340 410 100 1000 74 48 48.74 490 125 150 1250 1500 86 98 60 72 61.81 78.47 605 675 UNIT 40UV AIRFLOW (cfm) DIMENSiONS(in.) Wl W2 W3 CCN -- Carrier Comfort Network_ APPROXIMATE INSTALLED WEIGHT (Ib) 325 390 470 595 NOTES: 1. All dimensions are in inches. 2. Dimension does not include end panels. 3. Three _ont panels provided for service access. 4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, On/Off switch and non-fused disconnect switch. 5. Connection hand is determined by facing discharge of unit. 655 Fig. 2 -- 40UV Dimensions -- 2171a-in.Deep Units (With Piping Chase) 4 30.50 FRONTVIEW DISCHARGE GRILLE (OPTIONAL) LEFT SIDE VIEW Wl (SEE NOTE 2) loo_L F MOTOR ; (UNIT SHOWN WITH 1,00" END /t r-Z,_ PANELS) JL_ 2.00 ELECTRICAL BOX I _NON-FUSED DISCONNECT SWITCH (mmmmmlm L CCN CONTROLLER (OPTIONAL) BOTFOM SERVICE PANELS (SEE NOTE 3) BOTTOM VIEW --_ RL-I-URN AIR LOUVERED PANEL (OPTIONAL) 8.0S (TYP-SEE REMOVABLE PANEL NOTE 2) (EACH END) 1.54 (TYp) 17.50 18.25 (_.75 (MOUNTING HOLES-TYP- OUTSIDE AIR OPENING -- 2.50 (TYP) 4.50 6.75 (TYp) TOP 4 PLACES) 2.27 VIEW W2 3 00 5me0I\ l+ \ --REAROUTS,DE m __:E?OP N' N(OPT'ONAL' L__ 5.76 AIR OPENING (OPTIONAL) LEGEND CCN -- Carrier Comfort Network_ DIMENSIONS(in.) REAR VIEW UNIT AIRFLOW 40UH 075 100 (cfm) 750 1000 Wl 62 74 W2 36 48 W3 31.67 46.74 APPROXIMATE SHIPPING WEIGHT (Ib) 420 500 125 150 1250 1500 86 98 60 72 61.81 78.47 620 690 APPROXIMATE INSTALLED WEIGHT (Ib! 405 480 6OO 670 NOTES: 1. All dimensions are in inches. 2, Dimension does not include end panels. 3. Two bottom panels provided for service access. 4. Motor and electrical power input box on right side of unit. Box includesfan speed switch. On/Off switch and non-fused disconnect switch. 5. Connection hand is determined by facing discharge of unit. Fig. 3 -- 40UH Dimensions -- 301/2-in. Deep Units II II IIl_lllllll_lllllllll_Jlrll| IIIIl_llllllllllllllllllFJl| ;............ _ 36.00 W5 (OPENING) FRONT VIEW SIDE (SIZE DOUBLE DEFLECTION (SEEWl NOTE 2) I--4- 750 I (TO OPENING) DISCHARGE GRILLE (OPTIONAL) 1.00 (UNIT SHOWN WITH 1.00" END PANELS) 4.OO 3 ,,,,, W3 (OPENING) LEFT SIDE VIEW (SIZES 075 TO 150) LEFT 15.5 II ......... - ELECTRICAL BOX CCN CONTROLLER (OPTIONAL) VIEW 200) RETURNAIR _/ LOUVEREDPANEL (OPTIONAL) BO'I-rOM VIEW BOTTOM SERVICE PANELS (SEE NOTE 3) 8.00 NON-FUSED DISCONNECT SWITCH g_.75 (MOUNTING HOLESTYP-4 PLACES) -- NOTE 2) REMOVABLE PANEL (EACH END) 17.50 W4 2.50 (TYp) 3.67 (ryP) LEGEND CCN- Carrier Comfort Network_ UNIT AIRFLOW 40UH (ofm) DEPTH (in.) DIMENSIONS (in.) APPROXIMATE SHIPPING WEIGHT_b) Wl W2 W3 W4 W5 075 100 750 1000 36 36 62 36 36 18.67 7.00 500 74 48 48 18.67 7.00 600 125 150 1250 1500 36 35 86 60 60 18.67 7.00 740 98 72 72 18.67 7.00 830 200 2OOO 40 98 72 72 26.92 10.00 1020 APPROXIMATE INSTALLED WEIGHT (Ib) 485 58O 720 810 1 O00 NOTES: I. All dimensions are in inches. 2. Dimension does not include end panels. 3. Two bottom panels provided for service access. 4. Motor and electrical power input box on right side of unit. Box includes fan speed switch, On/Off switch and non-fused disconnect switch. 5. Connection hand is determined by facing discharge of unit. Fig. 4 -- 40UH Dimensions -- Front Discharge Units t 16.63 1 °00---1 FRONT VIEW LEFT SIDE VIEW (SIZES 075 TO 150) 1.00 (UNIT 4.00 _ I _ __ 7.50 WITH 1.00" END PANELS) L__ _PIPE "1_TUNNEL W3 (OPENING) (SEE NOTE 2) SHOWN -- ! I W5 (OPENING ilIiii : O i f LEFT SIDE VIEW (SIZE 200) - ELECTRICAL BOX J -----7 ' _-]IUlIIIIII CCN CONTROLLER I Ly- (OPTIONAL) RETURN AJR LOUVERED PANEL (OPTIONAL) BOTTOM SERVICE PANELS (SEE NOTE 3) Bo'n'OM DISCONNECT SWITCH VIEW 8.00 1.00 (TYp) (TYP) NOTE 2) 475 _l-- REMOVABLE PANEL (EACH END) OPENING (OPTIONAL 17.50 W4 _ 2.50 3,67 (TYP) 1.25 (TYP) 4.50 TOP VIEW (_ .75 (MOUNTING HOLES--TYP-4 PLACES) 2.27 5.00 _ _1 REAR OUTSI DWE2AIR / I OPENING(C)PTIONAL)7 l _ 300 " iL II 3_! 575 _ LEGEND CCN -- Carrier Comfort Network_ o ,, IT II _,_G(%_,_N%)_ REAR VIEW DIMENSIONS (In.) APPROXIMATE SHIPPING WEIGHT (Ib) 530 APPROXIMATE INSTALLED WEIGHT (Ib) 515 UNIT AIRFLOW DEPTH 40UH 075 (cfm) 750 (in.) 40 Wl 62 W2 36 W3 36 W4 18.67 W5 7.00 100 1000 40 74 48 48 18.67 7.00 640 620 125 1250 40 86 60 60 18.67 7.00 790 150 1500 40 98 72 72 10.67 7.00 880 770 86O 200 2000 44 98 72 72 26.92 10.00 1050 1030 NOTES: 1. All dimensions are in inches. 2. Dimension does not include end panels. 3. Two bottom panels provided for service access. 4. Motor and electricel power input box on right side of unit. Box includes fan speed switch, OnJOff switch and nonfused disconnect switch. 5. Connection hand is determined by facing discharge of unit. Fig, 5 -- 40UH Dimensions -- Down Discharge Plenum Make Piping Connections -- Access to piping is available through the access panels at the front, top, or end of the vertical unit (horizontal access from bottom or side). Route piping through the pipe tunnel or the unit's back panel or floor panel. Metal blank-off panels must be trimmed to complete piping installation. All piping connections must be performed by qualified personnel in accordance with local and national codes. DRAIN CONNECTIONS -- Condensate drain connections are located on each end of the drain pan near the bottom of the unit. Condensate drain line must be 3/4 in. copper tubing, .galvanized pipe, PVC or similar plastic pipe. Install drain line m accordance with all applicable codes. Insulate the drain line to prevent sweating. See Fig. 6 for typical drain trap construction. Units with cooling coils require traps to prevent air from entering the condensate fitting and preventing proper drainage. Drain must flow downhill from the unit a minimum of 1/_in. per ft. Drain must be flee and clear at all times. 3/4" GALVANIZED PiPE 3/4" PVC OR COPPER 3" MIN 3" MIN 2" MIN 2" MIN Fig. 6 -- Typical Condensate Drain Trap Construction EQUALIZER _/ I SENSING BULB (CLAMPED TO SUCTION LINE AND INSULATED) __ Insulate drain lines to prevent condensate. Care must be taken to avoid interference with control panel on left side drain. WATER SUPPLY/RETURN CONNECTIONS -- Install pipmg in accordance with all apphcable codes. All piping must be supported separately from coils. Water supply must be connected so that entering water is on leaving-air side of coil. See the connection labels on the unit to locate the inlet. Coils must be adequately vented to prevent air binding. Be sure valves are in proper operating position and are easily accessible for adjustment. If coil and valve package connections will be made with a solder joint, care should be taken to ensure that components in the valve package are not subjected to high temperatures which may damage seals or other materials. Many 2-position electric control valves are provided with a manual operating lever. This lever should be in the OPEN position during all soldering operations. If coil connection is made with a union, the coil side of the union must be prevented from turning (it must be backed up) during tightening. Do not overdghten? Overtightening will distort (egg shape) the union seal surface and destroy the union NOTE: A freezestat is factory-installed when a hot water/steam coil is installed. STEAM CONNECTIONS -- On units with steam heating coils, the maximum steam pressure applied to the unit should never exceed 10 psig (operating pressure 6 psig). DIRECT EXPANSION REFRIGERANT PIPING -- Use the condensing unit manufacturer's recommended line sizes and requirements. Perform leak test using nitrogen. Evacuate and charge per recommended heating, ventilation, and air conditioning (HVAC) procedures and all applicable codes. Insulate suction line after leak test up to the coil section end plate for correct operation and to ehminate sweating. Use refrigerantgrade copper lines only. The unit is NOT to be apphed as a heat pump. See Fig. 7 for refrigerant piping connections with recommended locations for the thermostatic expansion valve (TXV) and sensing bulb. HYDRONIC COIL PIPING -- When all joints am complete, perform hydrostatic test for leaks. Vent all coils at this time. Cheek interior unit piping for signs of leakage from shipping damage or mishandling. If leaks are found, notify a Carrier representative before initiating any repairs. Release trapped air from system (refer to Make Final Preparations section). _ SUCTION LINE LIQUID LINE NOTE: FollowTXV manufacturer's instructions. Fig. 7 -- Typical TXV (Thermostatic Valve) Installation Expansion All water coils must be protected from freezing after initial filling with water. Even if system is drained, unit coils may still have enough remaining water to cause damage when exposed to temperatures below freezing. Following the hydrostatic test, insulate all piping up to the coil section end plate to prevent sweating. To ensure compliance with building codes, restore the structtue's original fire resistance rating by sealing all holes with material carrying the same fire rating as the structure. Make Electrical Connections -- Refer to unit serial plate for required supply voltage, fan and heater amperage, and required circuit ampacities. Refer to unit wiring diagram for unit and field wiring. See Tables 24 for electrical data. All input power wiring connections are accessed through the electrical panel on front right-hand side of the unit. Use the openings that am for the piping connections. See the dimensional drawings Fig. 1-5 for electrical box connections. The fan motor should never be controlled by any wiring or device other than the factory-supplied switch or thermostat/ switch combination unless prior factory authorization is obtained. Fan motor may be temporarily wired for use during construction only with prior factory approval and only in strict accordance with the instructions issued at that time. All electrical connections should be made by qualified personnel and be in accordance with governing codes and ordinances. Any modification of unit wiring without factory authorization will invalidate all factory warranties and nullify any agency listings. See Fig. 8A and 8B for typical wiring connections for basic unit with CCN (Carrier Comfo_ Network®) controls. Actuators (Field-Supplied) -- Field-supplied actuators must be mounted on l/z in. diameter damper shafts. Table 2 -- Electric Heater Data for Units with PSC Motor HP UNIT NOMINAL V/PWHz 208/1/60 240/1/60 277/1/50 40UV060 (at 500 Cfm) 1/s 208/3/60 NUMBER OF ELEMENTS FLA 3 4 17.2 22.2 5 27.3 6 3 4 32.3 19.5 460/3/60 ---- MCA -MOCP -PSC -- 90 97 104 119 97 106 TOTAL CAPACITY MCA MocP 21.5 27,8 25 30 3.2 4,2 34.1 35 5.3 40.4 24.4 45 25 6.3 4.2 31,7 39.0 35 40 5.6 7.0 46.3 21 ,O 50 25 8,4 4.2 (kW) 25.3 31.2 6 3 37.0 16.8 115 124 97 4 5 21.8 26.9 106 115 27.3 33.6 30 35 5,6 7,0 6 3 31.9 124 39.9 13.5 40 15 8.4 3.2 19.6 20 4.2 24.4 24.4 15.1 25 25 20 5.3 6.3 4.2 106 116 124 22.4 25 5.6 27.8 27.8 30 30 7.0 8.4 07 7.5 11.1 15 15 4.2 5.6 13.8 13.8 15 15 7.0 8.4 4 5 4 5 6 3 10.8 15.8 19.5 19.5 12.1 17,9 22.2 22.2 4 6.0 8.9 5 6 11.0 11,0 LEGEND OX FLA I.AT (F) 5 6 3 240/3/60 LAT Direct Expansion Full LoadAmps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse S_ze or Circuit Breaker Amps) Permanent Split Capacitor 90 97 104 110 97 106 115 124 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat posiiton only and connections are on the right side. 4. Face and bypass units are available with 3 heating elements only. Table 2 -- Electric Heater Data for Units with PSC Motor (cont) UNIT HP NOMINAL V/Ph/Hz 208/1/60 NUMBER OF ELEMENTS 3 23.7 4 30.9 38.1 5 6 240/1/60 40UV, UH075 (at 750 Cfm) MCA -MOCP -PSC -- 3O 40 50 6.0 7.5 108 47.6 56.7 96 104 33.8 44.2 6O 35 9.0 6.0 113 121 54.6 45 60 65,0 29.1 70 30 38.1 47.1 40 50 60 (kW) 4.5 3 4 30.5 96 104 5 37.7 44,9 113 121 14.5 21.7 99 56.2 18.2 96 102 27,2 33.8 33.8 20.6 40 40 8.0 10.0 12.0 4 5 27.0 27.0 20 3O 35 8.0 10.0 12.0 4.5 6.0 7.5 9.0 4 16.5 24.8 5 30.9 113 6 30.9 8.2 121 96 38.6 38.6 10.2 15 6.0 5 12.3 15.4 104 113 15,4 19.2 20 20 8.0 10.0 6 15.4 121 19,2 20 12.0 4 31.0 35 8.0 10.0 12.0 6.0 103 96 104 LEGEND --- 29.6 38.6 43.7 52.0 23.3 3 DX FLA I-AT 69 96 102 35.3 3 460/3/60 MOCP 5 6 240/_60 MCA 4 3 208/3/60 TOTAL CAPACITY (F) 45.3 27.0 6 1/5 LAT 3 6 27711/60 FLA 25 35 6.0 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position onlyand connections are on the rightside. 4. Face and bypass units are available with 3 heating elements only, Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature U nit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor z0 Table 2 -- Electric Heater uNrr HP NOMINAL v/Ph/Hz 208/1/60 240/1/60 277/1_0 40UV, UH1OO (at 1000 Cfm) 208/3/60 240/3/60 460/3/60 Data for Units with PSC Motor (cont) NUMBER OF ELEMENTS FLA TOTAL CAPACITY (F) MCA MOCP 38.6 40 60 6.0 8.0 (kW) 3 4 5 30.9 40.5 89 95 50.2 102 50.7 62.7 70 10.0 6 59.8 35.3 46.5 I O8 96 74.7 44,2 80 45 11,9 8.0 104 58.1 57.6 112 121 96 72,0 85.8 38.1 60 80 90 10,7 13.3 16.0 I04 112 50.1 5 6 40.1 49.7 59,4 3 18,7 4 5 28.3 35.4 89 95 102 6 3 35.4 21.3 108 44.3 44.3 96 26.6 4 32.4 5 6 3 40.5 40.5 104 112 40.5 50.7 121 96 50.7 3 4 5 6 3 4 4 5 6 68.7 30.5 10.6 16.1 121 62.2 74.2 23.4 35.4 40 8.0 60 70 10.7 13.3 80 25 16.0 6.0 40 45 8.0 10.0 45 11,9 30 45 8.0 10.7 60 60 13.3 16.0 13.2 20.1 25.2 15 25 8.0 10.7 20.2 104 112 30 13.3 20.2 121 25.2 30 16.0 LEGEND DX FLA LAT LAT NOTES: t. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the rightside. 4. Face and bypass units are available with 3 heating elements only. ---- Direct Expansion Full LoadAmps Leaving-Air Temperature at 70 F Entering-Air Temperature MCA -- Unit Minimum Circuit Ampacity MOCP -- Maximum Ovemurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) PSC -- Permanent Split Capacitor 1] Table 2 -- Electric UNIT HP NOMINAL V/Ph/Hz 208/1/60 240/1/60 277/1/60 40UV, UH125 (at 1250 Cfm) 1/s 208/3/60 240/3/60 460/3/60 Heater Data for Units with PSC Motor (cont) NUMBER OF ELEMENTS FLA ---- MCA -MOCP -PSC -- (F) MCA 47.6 62.7 77.7 3 4 38.1 89 50.1 5 6 62.2 96 102 3 4 43.7 108 96 57.6 5 71.4 6* 3 85.3 4 49.7 5 6 61.8 3 4 5 22.9 6 3 43.7 4 40.0 5 6 3 50.2 13.0 96 62.7 16.2 4 19.9 5 6 25.0 104 113 25.0 121 74.2 37.7 73.8 34.9 43.7 26.1 50.2 LEGEND DX FLA I.AT LAT MOCP TOTAL CAPACITY (kW) 50 70 7.5 10.0 92.8 80 100 12.5 15.0 104 54.6 71.9 60 80 10.0 13.3 113 121 89.3 106.7 96 104 113 121 89 96 102 108 96 104 113 121 90 16,7 47.1 110 50 20.0 10,0 62.2 77.2 70 80 13.3 16,7 92.2 28.6 43.6 100 30 2O,O 7.5 45 60 10.0 12.5 54.7 32.6 50.0 60 35 15.0 10.0 50 13.3 62.7 70 70 20 16.7 20.0 10,0 24.9 31.3 25 13.3 35 16,7 31.3 35 20.0 54.7 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm, 2. Water and DX coil used on electric heat units have left-hand coil connections. 3, Electricheatisavailableinthereheatpositiononlyandconnections are on the right side. 4. Face and bypass units are available with 3 heating elements only, Direct Expansion Full LoadAmps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Ovemurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor *Left hand coil connections only. 12 Table 2 -- Electric UNIT HP NOMINAL V/Ph/Hz 208/1/60 240/1/60 277/1/60 40UV,UH150 (at 1500 Cfm) 208/3/60 240/3/60 460/3/60 Heater Data for Units with PSC Motor (cont) NUMBER OF ELEMENTS FLA --- MCA -MOCP -PSC -- (F) MCA MOCP 56.7 60 80 100 TOTAL CAPACITY (kW) 9.0 12.0 3 4 5 45.3 59,8 89 96 74.2 102 74.7 92.8 6* 88.7 52.0 68.7 109 96 110.8 65.0 125 70 18.0 12.0 104 113 85.8 106.7 90 110 16,0 20.0 6O 80 12.0 3 4 15.0 5* 6 85.3 3 4 44.9 96 56.2 59,4 73.8 104 113 74.2 92.3 100 27.0 80 41.5 52.1 96 102 33.8 61.9 35 6O 70 6 3 4 52.1 30.9 108 65.1 65,1 12.0 15.0 7O 4O 18.0 12.0 5 6 3 59,8 59,8 15.4 4 5 23.7 29.8 6 29,8 5 6 3 4 5 47,5 LEGEND DX FLA LAT LAT 96 104 113 121 96 104 113 121 38.6 16.0 20.0 9,0 59.5 74.8 74.8 6O 16.0 80 90 20.0 24.0 19,2 29.6 37.3 2O 30 40 12.0 16.0 37.3 4O 20.0 24.0 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat le available in the reheat position only and connections are on the right side. 4. Face and bypass units are available with 3 heating elements only. Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Ovemurrent Protection (Maximum Fuse SLze or Circuit Breaker Amps) Permanent Split Capacitor *Left hand coil connections only. 13 Table 3 -- Electric Heater Data for Units with ECM UNIT HP NOMINAL V/Ph/Hz 208/1/66 240/1/60 277/1/60 40UV05O (at 500 Cfm) NUMBER OF ELEMENTS 3 4 5 6 208/3/60 240/3/60 460/3/60 LAT (F) MCA MOCP 16.5 90 97 104 20.6 25 3,2 26.9 33.2 30 35 4,2 5,3 21.5 26,6 31,6 18,8 24,6 110 97 39.5 23.5 40 25 6,3 4,2 106 5 30,5 30.8 38.1 35 40 5.6 7.0 6 3 4 36.3 16,3 115 t 24 45.4 20.3 50 25 8.4 4.2 21,3 97 166 26.6 30 5.6 5 26,4 31,4 115 124 33.0 39.3 35 40 7.0 8,4 10,1 15.1 90 12.6 18.9 15 20 3.2 4.2 23.5 23.5 25 25 5.3 6.3 14.3 21,6 15 25 4.2 5.6 26.9 26.9 30 30 7.6 8.4 3 4 5 --- MCA -MOCP -PSC -- 97 104 6 18.8 18.8 3 4 11.4 17.2 5 6 3 21.5 21.5 5.4 124 97 6.8 15 4.2 4 8.3 10.5 106 115 16.4 13.1 15 15 5.8 7.0 124 13.1 15 8.4 5 6 10.5 LEGEND DX FLA LAT (kW) 3 4 6 1/3 TOTAL CAPACITY FLA 110 97 106 115 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the rigl_ side. 4. Face and bypass units are available with 3 heating elements only. Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor ]4 Table3-UNIT HP NOM[NAL V/Ph/Hz 208/1/60 240/1/50 277/1/60 40UV, UH075 (at 750 Cfm) 1/z 208/3/60 240/0/60 460/0/60 Electric Heater NUMBER OF ELEMENTS Data for Units with ECM (cont) FLA 3 24.0 4 31.2 5 6 38.4 3 4 27.3 35.6 96 104 5 44.0 113 6 3 4 52.3 121 96 5 6 38.1 3 4 14.8 5 6 45.6 23.7 30.9 45.3 --- MCA -MOCP -PSC -- 89 96 102 108 104 113 121 89 MCA 30.0 MOCP TOTAL CAPACITY (kW) 30 40 50 4.5 6.0 7.5 60 9.0 35 45 6.0 8.0 55.0 65.4 29.6 60 70 10.0 12.0 30 6.0 38.6 40 50 60 8.0 10.0 12.0 39.0 48.0 57.0 34.1 44.5 47.6 56.7 18.5 27.6 34.2 20 30 4.5 6,0 27.3 96 102 35 7,5 27.3 108 34.2 3 4 16.8 96 104 20.9 31.4 35 25 35 9.0 6.0 8,0 5 31.2 39.0 39.0 10.0 31.2 113 121 40 6 3 10.2 12,0 6.0 4 5 12.3 96 104 40 15 20 20 8.0 10,0 6 15.4 20 12,0 22.0 25.1 8.2 15.4 LEGEND DX FLA LAT LAT (F) 113 121 15.4 19.2 19.2 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2, Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the right side. 4, Face and bypass units are available with 3 heating elements only, Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse S_e or Circuit Breaker Amps) Permanent Split Capacitor 15 Table 3 -- Electric UNIT HP NOMINAL V/Ph/Hz 208/1/60 240/1/60 277/1/60 Heater Data for Units with ECM (cont) NUMBER OF ELEMENTS FLA 3 208/3/60 240/3/60 460/3/60 MCA MOCP 31.5 89 39.4 4 5 41.1 50.8 95 51.4 40 60 6.0 8.0 6 3 4 60.4 35.9 102 108 96 63.4 75.5 70 80 10.0 11.9 104 112 44.9 58.8 45 60 8.0 10.7 5 47.1 58.2 13,3 69.3 31.2 121 72.7 88.6 80 6 3 40.8 39.0 51.0 16,0 8.0 4 5 96 104 90 40 112 121 63.1 75.1 60 70 10.7 13.3 24.1 80 25 16.0 6.0 28.9 89 95 102 108 36.2 45.0 45.0 40 50 8.0 10.0 6 36.0 36.0 3 4 5 21.9 33.0 41.1 96 104 27.3 41.2 50 30 11,9 8.0 45 10.7 51.4 6 3 41.1 112 121 96 104 13.3 16.0 8.0 4 10.6 16.2 60 60 15 10.7 20.3 20.3 112 20.2 25.3 25 5 6 121 25.3 30 30 13.3 16.0 4 5 50.4 60.1 19.3 LEGEND DX FLA I.AT --- MCA -MOCP -PSC -- TOTAL CAPACITY (F) 6 3 40UV,UH100 (at 1000 Cfm) LAT 51.4 13.3 (kW) NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal ctm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the right side. 4. Face and bypass units are available with 3 heating elements onty. Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor ]6 Table 3 -- Electric UNIT HP NOMINAL V/Ph/Hz 208/1/60 Heater Data for Units with ECM (cont) NUMBER OF ELEMENTS 277/1/60 40UV, UH125 (at 1250 Cfm) 1/2 208/3/60 460/3/60 49.3 50 7,5 95 102 108 64.3 79.4 7O 80 10.0 12,5 94.4 56.2 100 15.0 96 73.6 90.9 10.0 13.3 72.7 1O4 113 60 80 86.6 39.0 121 96 108.3 48.7 100 110 16.7 20.0 104 63.8 50 70 10.0 13.3 5 51.0 63,1 6 3 75.1 24.2 113 121 89 78.8 93.9 80 100 16.7 20.0 7.5 36,2 45,0 96 102 30.2 45.3 35 4 5 6 45.0 27.4 108 56.3 56.3 50 60 60 10.0 12.5 15.0 96 104 34.2 51.6 35 10.0 60 13.3 113 121 64.3 70 70 20 16.7 20.0 10,0 30 13.3 35 35 16,7 20.0 4 5 6" 3 4 4 5 6 3 39.4 51.5 63.5 75.5 45.0 58.9 41.3 51.5 51.5 13.2 4 20.2 5 6 25.3 25.3 LEGEND DX FLA LAT ---- MCA -MOCP -PSC -- TOTAL CAPACITY 89 3 240/3/60 MOCP MCA 6 3 240/1/60 LAT (F) 3 4 5 FLA 96 104 64.3 16.5 113 25.2 31.6 121 31.6 (kW) NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the right side. 4. Face and bypass units are available with 3 heating elements only Direct Expansion Full LoadAmps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Ovemurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor *Left hand coil connections only. ]? Table3-UNIT HP NOMINAL VfPh/Hz 208/1/60 Electric Heater Data for Units with ECM (cont) NUMBER OF ELEMENTS MOCP 46.7 39 61.1 75.6 96 102 58.3 76.4 60 8O 90.0 108 94.4 112.5 100 125 53.3 70.0 96 104 66.6 87.5 70 18.0 12.0 66.6 113 108.3 90 110 20.0 46.2 96 104 57.8 6O 12.0 60.7 75.1 113 93.9 8O 100 20.0 28.3 42.8 89 96 6 53.4 53.4 102 108 3 4 32.2 48.9 5 6 61.1 61.1 3 4 15.6 24.0 5 6 30.1 30.1 5 6* 4 5* 6 3 277/1/60 40UV,UH150 (at 1500 Cfm) 4 5 6 3 1/2 208/3/60 240/3/60 460/3/60 4 5 LEGEND DX FLA LAT ---- MCA -MOCP -PSC -- TOTAL CAPACITY MCA 3 240/1/60 LAT (F) 3 4 FLA 96 104 113 75.8 (kW) 9.0 12.0 15.0 16.0 16,0 35.4 40 53.5 66.7 60 70 66.7 40.9 7O 15.0 18.0 45 70 12.0 16.0 8O 8O 20.0 24.0 20 3O 12.0 61.1 121 96 76.4 76.4 19.5 104 113 30.0 37.6 121 37.6 40 40 9.0 12.0 16.0 20.0 24.0 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position only and connections are on the right side. 4. Face and bypass units are available with 3 heating elements only. Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entering-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse Size or Circuit Breaker Amps) Permanent Split Capacitor *Left hand coil connections only. ]g Table3 -UNIT HP NOMINAL V/PWHz 208/1/60 Electric Heater Data for Units with ECM (cont) NUMBER OF ELEMENTS 3 4 5 6* 3 240/1/60 40UH200 (at 2000 Cfm) 208/3/60 240/3/60 460/3/60 50.1 64.6 79.0 93.5 ---- MCA -MOCP -PSC -- TOTAL CAPACITY (F) MCA MOCP 84 62.7 89 84 99 80.7 98.8 116.8 70 90 100 9.0 12,0 15.0 125 80 18.0 12.0 (kW) 89 96 71.0 91.8 100 16.0 102 112.7 125 20.0 48.8 63.3 89 96 61.0 70 80 12.0 16.0 5 6 77.7 102 100 20.0 3 4 31.8 84 5 6 46.3 56.9 56.9 89 94 3 4 35.7 52.4 5 6 64.6 64.6 3 4 16,9 25.2 5 6 31,3 4 5* 4 31.3 LEGEND DX FLA I.AT LAT 56.8 73.5 90.1 6 3 27_1_0 FLA 99 89 96 102 I08 89 96 102 I08 79.1 97,1 39.8 57.9 71.1 71.1 44.6 65.5 80.8 80.8 21.1 31.5 39.1 39.1 40 9.0 69 80 12.0 15.0 80 45 70 18.0 12.0 16.0 90 90 20.0 24,0 25 12.0 35 40 16,0 20,0 40 24.0 NOTES: 1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm. 2. Water and DX coil used on electric heat units have left-hand coil connections. 3. Electric heat is available in the reheat position onlyand connections are on the right side. 4. Face and bypass units are available with 3 heating elements only. Direct Expansion Full Load Amps Leaving-Air Temperature at 70 F Entedng-Air Temperature Unit Minimum Circuit Ampacity Maximum Overcurrent Protection (Maximum Fuse S_-e or Circuit Breaker Amps) Permanent Split Capacitor *Left hand coil connections only 19 Table 4 -- Motor Data PSC MOTORS UNIT 40UV,UH SIZE MOTORHp VOLTAGE FLA MCA MOP (Amps) 115 3.7 4.6 8,3 050* I/s 208/230 266 2.0 1.6 2.5 2,0 4,5 3,6 115 208/230 3,7 2.0 4.6 2.5 8.3 4.5 265 115 1.6 3.7 2.0 4.6 3.6 8.3 208/230 265 2,0 1,6 2.5 2,0 4.5 3,6 115 3,7 4.6 8.3 208/230 265 2,0 t .6 2,5 2,0 4,5 3,6 t 15 208/230 265 3.7 2.0 1.6 4,6 2.5 2,0 8,3 4.5 3,6 VOLTAGE FLA MCA 115 1.4 1.8 3.1 1.3 1,1 1.6 1.4 2.9 2.6 3,7 2,3 4.6 2.9 8.3 5.1 2.0 4,0 2.5 5,0 4.5 9.1 2,6 2.3 3,2 2,9 5.8 5.1 208/230 4.7 3.3 5.9 4.1 10.6 7.4 265 2.9 3.6 6.6 115 4.7 3.3 5.9 4.1 10.6 7.4 2.9 9,6 3.6 12.0 6.6 21.6 6.8 5.5 8.5 6.9 15.3 12.4 O75 100 '/s 125 I/s 150 MAX FUSE SIZE (Amps) 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 ECM UNIT 40UV, UH SIZE MOTOR Hp 05O* % 208/230 265 115 1/3 075 208/230 265 115 1/3 100 208/230 265 115 1/2 125 150 208/230 265 115 200t" ¾ 208/236 265 LEGEND ECM FLA MCA MOP PSC ------ Electronically Commutated Motor Full Load Amps Minimum Circuit Amps Maximum Overload Protection Permanent Split Capacitor *Available in vertical configuration only, "j-Available in horizontal configuration only, 2O MOP(Am_) MAX FUSE SIZE {Amps) 15 15 15 15 15 15 15 15 t5 16 15 15 15 15 15 20 15 15 BLK/100 Lt --- __.,,_ 115v DISC1 • BLK/101 BLK/I_ SWl CBC1 USE COPPER SUPPLY WIRES N .... I WHT/110 BLK/10g ,.0v.c il ,.vAc WHT/110 WHT/I_ WHT/111 _II_RN_504 • GND .... % _ I SW2 C) AUTO BRN/51 7m RED/511 _ !_ YEU51 WHT/515 OF F (_ CONT VIO/51' V!O/516 BLU/EC9 ORN/EC2• DISC -ECM -ESP -FU -GND -LLT -SW -TRAN ---_ _--- LEGEND Disconnect Switch Electronically Comrnutated Motor External Static Pressure Fuse Ground Water Coil Low LimitThermostat Switch Transformer Harness Conn•ction • Connection Point Splice • Splice Terminal Connection O Component Tie Point .... Optional Wiring -- Factory Wiring Chassis Ground Earth Ground BLU/51 WHT/51 Ii I ORN/51; SEE NOTE 3 SPEEDBOARD HIGH LOW YEUE05 = RED,EO<. _ 5 EC NOTES: 1. Make electrical installation in accordance with job diagram, and in compliance with naUon•l and local electrical codes, 2. Low limit thermostat (LLT) is installed on all units with water ceils. 3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, MAX • re for field use with increased ESR Fig. 8A -- Unit Ventilator Wiring with CCN Controls -- Control Box (115 vac) i ,W,RE \J ,P,. POWER _ CABLE RECEPTACLE _ _ ON MOTOR RESISTOR HARNESS 1000 ohm I V1C GRI CBC3 Jl Power BRN RED _ Detail A - STEAM -- _ I000 ohm_ VALVE RAT _CX SAT RED OAT NOTE i NOTE 1 SPT BLK 1"2 T1 i T3 i RED WHT SAT RED NOTE 3 BLU --I J4 Sewice WIRING LL OR T4 i MAT T5 i Te = CCN _J3 NOTE 2 w/Setp°lnt Adjust OAT TE TTi_. Tg VlO/2 See Detail A for Slum Vah_ Wiring, LEGEND AQ CCN CGO_ CGOVR COM CW ECM t-J ----- GND HW -LL -MAT -NC -NO OA OAT -OCC/ -UNOCC RAT RH SAT EPT SPT ADJ Air Quality Carder Comfort Network® Changeover Changeover Common Chilled Water E_ectronically Commu Commutatad Motor Ground Hot Water Low Limit Device Mixed Air Temperature Normally Closed Normally Open Outdcor Ad Outdoor Air Temperature Occupied/Unoccupied Return Air Temperature Relative Humdity Supply Air Temperature Space Temperature Space Temperature Adjustment Harness Connection SPT ADJ csc2 Ni3 <-3 T10 i YEI aT26 YEI RED OR BLU rio SpikesTerminal Connection Component Tie Point -_,T6_ NOTE3 BLU BLUII RED REE '2 '3 4-8 '4 (-4 YEL I YEL BLU l BLU F_ED RED _6 ORN ORN _7 YEL YEL _8 BLK _9 GRa GRA TL/ 1"2 Ccollng _. '5 v2c T31 VIO _ V_ _ T33 WHT I WHT _ T34 OA damper no_tnRtniledon ReclrculationOniy Uni_ eLK BLK _ =_ ENTHALPY SWtTCH SFS T17 m BC,,_._3 c aE°i! L'-r T22 _ Heetlng T37 Enable K3 SW2_;OM I_- YEL Factory Wiring SW2-AUTO 5_ WHT t_?_T VIO Chassis Ground SW2-CONT -ECM i _ r_ VIO BLU BLU I ") ORN ECM ORN )RN CH_VR ORN OCC_UNOCC _LK/21 FIRFJSMOKE DETECTOR T23 m Sp_r_ DI _4m K2 IRN K1 ORN/38 RED/FSD NOTE 5 BRN BRN :_ TB2 FED 3"21m T36 Comm
Source Exif Data:File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 72 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 13:48:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools