CARRIER Air Conditioner/heat Pump(outside Unit) Manual L0601181
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 72
40UV, UH050-200
Unit Ventilators
with Product Integrated Control (PIC)
Installation, Start-Up and Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ............................ ]
INTRODUCTION ...................................... ],2
PREINSTALLATION ..................................... 1
Unpack and Inspect Units .............................. ]
Protect Units From Damage ............................ t
Prepare Jobsite for Unit Installation .................... I
Identify and Prepare Units ............................. 2
PHYSICAL DATA........................................ 2
INSTALLATION ...................................... 2-24
Placing Vertical Units in Position ....................... 2
Placing Horizontal Units in Position .................... 2
Make Piping Connections ............................... 8
Make Electrical Connections ............................ 8
Actuators (Field-Supplied) .............................. 8
Make Duct Connections .............................. 23
Make Final Preparations .............................. 24
PRODUCT INTEGRATED CONTROL ................ 24-46
Physical Characteristics .............................. 24
Unit Ventilator Comfort Control Module
Installation and Field Wiring ........................ 27
Sensors .............................................. 29
Carrier Comfort Network_ Interface .................. 38
Relays ................................................ 39
Actuators ............................................. 39
Direct Expansion (DX) Cooling ........................ 41
DX System Design .................................... 41
Electric Heat .......................................... 42
Remote Start ......................................... 42
Fire/Smoke Status Input .............................. 42
Valves ................................................ 43
SET-UP, CONFIGURATION, AND
OPERATION ...................................... 46-49
START-UP ............ ................................. 50
SERVICE ............................................ 50-66
Preventing Excessive Condensation on Unit.......... 50
Check Drain .......................................... 50
Fan Motor Bearings ................................... 50
Fan Shaft Ball Bearing ................................ 50
Clean Fan Wheel ...................................... 50
Clean or Replace Air Filters ........................... 50
ECM Motor Removal and Reinstallation ............... 50
Blower Assembly Section Removal
and Reinstallation .................................. 52
Coil Assembly Removal and Reinatallation ........... 53
Ball Bearing Replacement ............................ 57
Blower Wheel Removal and Reinstallation ............ 62
Sleeve Bearing Replacement ......................... 63
Damper Section Removal and Reinatallation .......... 65
TESTING ............................................ 67-71
Water Valve Tests ..................................... 67
Face and Bypass Damper Tests ...................... 67
Dampers ..............................................
Fan Tests ............................................. 68
Filter Maintenance .................................... 68
Remote Start Input .................................... 68
Sensors .............................................. 68
Fire Shutdown Option ................................ 68
Electric Heat and Direct Expansion Cooling .......... 68
Mixed-Air Damper Sensors Final Calibration .......... 69
Testing Completion ................................... 69
Unit Diagnostics and Troubleshooting ................ 69
SAFETY CONSIDERATIONS
Installation and servicing of this unit can be hazardous due
to system pressure, electrical components and equipment
location (such as a ceiling or elevated structare). Untrained
personnel can perform the basic maintenance functions of
replacing fdters. Only trained and qualified service personnel
should perform all other operations.
When installing this unit, observe precautions in the litera-
ture, tags and labels attached to the equipment, and any other
safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling and installing this accessory.
• Use quenching cloth for all brazing operations.
• Have fire extinguisher available for all brazing
operations.
Before perfomamg service or maintenance operations, tam
off main power switch to the mill Electrical shock could
cause personal injury.
INTRODUCTION
This document contains general installation instructions for
the 40U_,UH unit ventilators and information and _couble-
shooting of the Product Integrated Control (PIC) option.
See submittal drawings for unit configurations, dimensions,
clearances, and pipe connections. Refer to unit wiring label for
all electrical connections; follow NEC (National Electrical
Code) and local codes.
PREINSTALLATION
Unpack and Inspect Units- Remove shipping wraps
from all units. Check the shipment against shipping order. If
shipment is damaged or incomplete, file claim with transporta-
tion company and advise Carrier immediately.
Protect Units From Damage -- To maintain war-
ranty, protect units against adverse weather, theft, vandalism,
and debris on jobsite. Do not allow foreign material to fall into
drain pan. Prevent dust and debris from being deposited on
motor and fan wheels.
If the equipment is stored for any length of time before in-
stallation, it should remain in its shipping container in a clean,
dry, and climate controlled area.
Prepare Jobsite for Unit Installation -- To save
time and to reduce the possibility of costly errors, set up a com-
plete sample installation in a typical room at jobsite. Check all
critical dimensions such as pipe, wire, and duct connection
requirements. Refer to job drawings and product dimension
drawings as required. Insmlct all Wades in their part of the
installation.
Manufacturer reserves the Hght to discontinue, or change at any 11me,specifications or designs wi_out notice and without incurring obligatlot_.s.
Book 3 Catalog No 534-094 Printed in U.S.A. Form 40UV, UH-6SI Pg 1 7-05 Replaces: 40UV, UH-3SI
Identify and Prepare Units
1. Be sure power requirements match available power
source. Refer to the unit nameplate and wiring diagram.
2. Remove front (40UV) or bottom (40UH) access panels
from the unit. Retain the 5/32-in. socket bead fastcners and
panels for minstallation later.
3. Rotate the fan shaft by hand to ensure that fans are
unresWicted and can rotate freely. Check for shipping
damage and fan obstructions.
PHYSICAL DATA
Component weight data of 40UV, LrH units is provided in
Table I.
INSTALLATION
Units must be installed level and plumb. Failure to do so
may result in excessive vibration and/or premature failure.
Placing Vertical Units in Position
l. Select the unit location; ensure that service clearance is
provided. Allow enough grille clearance to maintain
unrestricted airflow. See submittal drawings and Fig. 1
and 2 for dimensions.
2. Make sore wall behind unit is smooth and plumb; ff
necessary, install furring strips on walls with irregular
surfaces or mullions. Furring strips must be positioned
behind mounting holes in unit. Fasteners, furring strips,
and other seals (if required) must be field supplied.
3. Remove all wall and floor moldings from behind the unit-
4. Move unit into position. Unit must be snug against wall
and furring strips.
5. Adjust unit leveling legs so unit is level. Unit must be
level for proper operation and condensate drainage.
6. Using field-supplied fasteners, reach into unit and attach
unit to the wall using the 3/4 in. mounting holes in the
back panel.
7. Protect the unit from jobsite debris. Do not allow foreign
material to fall into drain pan. Prevent dust and debris
from being deposited on motor or fan.
Placing Horizontal Units in Position
l. Select the unit location; ensure that service clearance is
provided. Allow enough grille clearance to maintain ura'e-
stricted airflow. Make sure that ceiling is able to support
the weight of the unit. See Fig. 3-5 for nominal unit weight.
See submittal drawings and Fig. 3_5 for dimensions.
NOTE: See page 23 for additional requirements for units
ducted to multiple openings.
2. Ensure that bottom panels have been removed from unit_
When unit is lifted, access to the 3/4in. mounting holes is
through the bottom of the unit- Hanger rods and fasteners
and other required hardware must be field supplied.
3. Using a forklift or other mechanical lifting device, raise
the unit to the mounting position. If forklift or other
lifting device is likely to contact a painted wall surface,
protect the surface as necessary.
4. Use rods and fasteners to suspend the unit at the mounting
holes on the top of the unit. The unit must be suspended at
the 3/4in. mounting holes; do not use any other locations.
5. If desired, install field-supplied vibration isolators. Adjust
isolators so unit is uniformly suspended and pitched.
6. To ensure proper drainage and operation, ensure unit is
level and tighten all fasteners. DO NOT mount the unit
on a slope. Pitch of horizontal suspended units can
change after coil is filled; recheck after filling coil.
7. Protect the unit from jobsite debris. Do not allow foreign
material to fail into drain pan. Prevent dust and debris
from being deposited on motor or fan.
Table I -- Physical Data
UNIT 40UV, UR 050* 075 100 125 150 200"
NOMINAL AIRFLOW (CIm) 500 750 1000 1250 1500 2000
FANS
Quantity 1 2 3 4 5 5
Diameter (in.I 0.32 8.32 8.32 8.32 8.32 9.5
Width On-) 8 8 88 8 6
RLTERS
Rom,=,s .llo l,,nasokI ,.x301 .
Romthal Size •t_in_ 2in_ thlOkn 9 x 241/4 9x36 l& 9x 481/4 9 x 601/4 9 x 721/+ 9 x731/4
Quantity 1 1 1111
40UV ERIPPING WEIGHT _
(Appfox Ib)
16Sla in. Deep Unit 330 400 480 590 660 --
21_1e In. Deep Unit 340 410 499 605 6/5 --
40UH SHIPPING WEIGHT'*
(Appro_ 1t3)
30Vz In. Deep Unit -- 420 500 620 690 --
36 In. Deep Unit -- 500 600 740 830
40 In. Deep Unit -- 530 640 790 880 1020
44 in. Deep Unit ..... 1050
40UV INSTALLED WEIGHT**
(Approx Ib
16s/+ in. Deep Unit 315 380 460 570 640 --
217/s In. Deep Unit 325 390 470 595 655 --
40UH INSTALLED WEIGHT**
(Approxth)
30V= In. Deep Unit -- 405 480 600 670 --
36 in. Deep Unit -- 485 580 720 810
40 in. Deep Unit -- 515 620 770 860 1_)00
44 in. Deep Unit ..... 1030
COil_ WATER WEIGHT
(Approx Ib per row of coil) 1 .O 1.5 2.0 2.4 2.7 27
COB. CONr4_i iur_S (in. OD) Return Supply
Water Coils with 1 to 5 Rows _/8 7,s
Steam Coils (All Units) 7/a 11/a
Suction LJquid
DX Coils 7/e 3/a
LEGEND "4OUV only,
DX -- Direct Expansion 1"40UH 40 and 44 in. deep units onnly..
_Weight based on damper_ordro|led unit with 5-row coil and factory-fastalled
controls.
REMOVABLE BOTFOM PANEL
.78 _ 10.61 _(EACHEND)
(_'P)_I I _
12.37F.... if r.... _ t
r 522 +opwEw 2°OCK
DISCHARGE GRILLE
1.00
(UNIT SHOWN
WITH 1,00" END
PANELS)
CCN
CONTROLLER
(OPTIONAL)
FRONT SERVICE
PANELS
(SEE NOTE 3)
----9
Wl
(SEE NOTE 2)
12.10 (TYp)
IO
I
I
I
]_--J
,/J ................................... .,.
FRONT VIEW
/L
_# TUNNEL-_
L200 L
r-_ ELECTRICAL
--J ,"4 _BOX
I
_4 NON-FUSED
LJ _ DISCONNECT
SWITCH
2.08 13.ooF
--RECESSED RETURN
AIR/KICK PANEL RIGHT SIDE VIEW
8.08 REMOVABLE PANEL
(TYP-SEE ( EACH END)
NOTE 2) PIPE TUNNEL_
7.04GYP)
1.54 (TYP) 3 ACCESS
OPEN[NG
(EACH END)
7.00(TYp)
18.25
(_ 25
(MOUNTING
HOLES-TYP-
4 PLACES)
#
L _--OUTSIDE AIR
OPENING
4.50 .90
REAR VIEW
22.00
L 2.00
(TYP)
6.75 (TYP) LEGEND
CCN -- Carrier Comfort Network_
UNIT AIRFLOW DIMENSIONS(in.
40UV (cfm) Wl W2 W3
050 500 50 24 16.60
075 750 62 36 31,67
100 1000 74 48 46.74
125 1250 86 60 61,81
150 1500 98 72 78.47
APPROXIMATE
SHIPPING
WEIGHT (Ib)
330
400
480
590
660
APPROXIMATE
INSTALLED
WEIGHT (Ib)
315
380
480
570
640
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panets.
3. Three front panels provided for service access.
4. Motor and electrical power input box on right side of
unit. Box includes fan speed switch. OrdOff switchand
non-fused disconnect switch.
5. Connection hand is determined by facing discharge of
unit.
Fig. 1 -- 40UV Dimensions -- 16s/e-in. Deep Units
(Standard)
5.98
ITS)--
12.37
5Z_
2.08
1.00
(UNIT SHOWN
WITH 1.00" END
PANELS)
CCN
CONTROLLER
(OPTIONAL)
FRONT SERVICE
PANELS
(SEE NOTE 3)
j s
5.22 TOP VIEW _BARSTOCK
DISCHARGEGRILLE
W1
(SEE NOTE2)
12.00 _FY'P) /
/
7-J=
//
/................................. iii
FRONT VIEW
--MOTOR 2.404_. _
1.7
_--2oo I 7_ ; ;
ELECTRICAL II
Fsox 14:
NON-FUSED _//J -
DISCONNECT
SSWlTCH
PIPINGL_
L TUNNE __
-RECESSED RETURN
AIR/KICKPANEL END VIEW
REMOVABLE PANEL
B.08 (EACH END) 7.04 (TYP)
NOTE 2) CCESS
OPENING
(EACH END)
18.25
,75
(MOUNTING
HOLE_-TYP*
4PLACES)
W2
OUTSIDE AIR
OPENING
4.50
REAR VIEW
LEGEND
CCN -- Carrier Comfort Network_
UNIT AIRFLOW DIMENSiONS(in.)
40UV (cfm) Wl W2 W3
050 500 50 24 16.60
075 750 62 36 31,67
100 1000 74 48 48.74
125 1250 86 60 61.81
150 1500 98 72 78.47
APPROXIMATE
SHIPPING
WEIGHT (Ib)
340
410
490
605
675
APPROXIMATE
INSTALLED
WEIGHT (Ib)
325
390
470
595
655
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Three _ont panels provided for service access.
4. Motor and electrical power input box on right side
of unit. Box includes fan speed switch, On/Off
switch and non-fused disconnectswitch.
5. Connection hand is determined by facing dis-
charge of unit.
Fig. 2 --40UV Dimensions -- 2171a-in.Deep Units
(With Piping Chase)
4
30.50
LEFT SIDE VIEW
loo_L
(UNIT SHOWN
WITH 1,00" END
PANELS)
CCN
CONTROLLER
(OPTIONAL)
BOTFOM SERVICE
PANELS
(SEE NOTE 3)
FRONTVIEW DISCHARGE GRILLE
(OPTIONAL)
Wl
(SEE NOTE 2)
/t
r-Z,_
I
(mmmmmlmL
BOTTOM VIEW
FMOTOR
;
JL_ 2.00
ELECTRICAL
BOX
_NON-FUSED
DISCONNECT
SWITCH
--_ RL-I-URN AIR
LOUVERED PANEL
(OPTIONAL)
8.0S
(TYP-SEE REMOVABLE PANEL
NOTE 2) (EACH END) 1.54
(TYp)
18.25 17.50
(_.75
(MOUNTING --
HOLES-TYP-
4 PLACES)
OUTSIDE AIR
OPENING
4.50
TOP VIEW
2.50
(TYP)
6.75 (TYp)
LEGEND
CCN -- Carrier Comfort Network_
2.27 W2 3 00
5me0I\ l+
\ --REAROUTS,DEm
__:E?OP N' N(OPT'ONAL'L__5.76
AIR OPENING (OPTIONAL)
REAR VIEW
UNIT AIRFLOW DIMENSIONS(in.) APPROXIMATE
SHIPPING
40UH (cfm) Wl W2 W3 WEIGHT (Ib)
075 750 62 36 31.67 420
100 1000 74 48 46.74 500
125 1250 86 60 61.81 620
150 1500 98 72 78.47 690
APPROXIMATE
INSTALLED
WEIGHT (Ib!
405
480
6OO
670
NOTES:
1. All dimensions are in inches.
2, Dimension does not include end panels.
3. Two bottom panels provided for service access.
4. Motor and electrical power input box on right side of
unit. Box includesfan speed switch. On/Off switch and
non-fused disconnectswitch.
5. Connection hand is determined by facing discharge of
unit.
Fig. 3 -- 40UH Dimensions -- 301/2-in. Deep Units
_36.00
LEFT SIDE VIEW
(SIZES 075 TO 150)
1.00
(UNIT SHOWN
WITH 1.00"
I--4- 750
4.OO END PANELS)
I
LEFT SIDE VIEW
(SIZE 200)
CCN
CONTROLLER
(OPTIONAL)
BOTTOM SERVICE
PANELS
(SEE NOTE 3)
II IIl_lllllll_lllllllll_Jlrll| 15.5 3
II IIIIl_llllllllllllllllllFJl|
;............ II ......... ,,,,,
W5 W3 (OPENING) (TO OPENING)
(OPENING) FRONT VIEW DOUBLEDEFLECTION
DISCHARGE GRILLE
(OPTIONAL)
Wl
(SEE NOTE 2)
- ELECTRICAL
BOX
RETURNAIR _/
LOUVEREDPANEL NON-FUSED
(OPTIONAL) DISCONNECT
BO'I-rOM VIEW SWITCH
8.00
NOTE 2)
REMOVABLE PANEL
(EACH END)
g_.75
-- (MOUNTING HOLES-
TYP-4 PLACES)
W4 17.50
LEGEND
CCN- Carrier Comfort Network_
3.67
(ryP)
2.50
(TYp)
UNIT AIRFLOW DEPTH
40UH (ofm) (in.)
075 750 36
100 1000 36
125 1250 36
150 1500 35
200 2OOO 40
DIMENSIONS (in.) APPROXIMATE
SHIPPING
Wl W2 W3 W4 W5 WEIGHT_b)
62 36 36 18.67 7.00 500
74 48 48 18.67 7.00 600
86 60 60 18.67 7.00 740
98 72 72 18.67 7.00 830
98 72 72 26.92 10.00 1020
APPROXIMATE
INSTALLED
WEIGHT (Ib)
485
58O
720
810
1 O00
NOTES:
I. All dimensions are ininches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service
access.
4. Motor and electrical power input box on
right side of unit. Box includes fan speed
switch, On/Off switch and non-fused dis-
connect switch.
5. Connection hand is determined by facing
discharge of unit.
Fig. 4 -- 40UH Dimensions -- Front Discharge Units
1 °00---1
LEFT SIDE VIEW
(SIZES 075 TO 150)
1.00
(UNIT SHOWN
4.00 _ _ 7.50 WITH 1.00" --
END PANELS)
I __ L__ _PIPE
"1_TUNNEL W5 (OPENING
LEFT SIDE VIEW
(SIZE 200) CCN
CONTROLLER
(OPTIONAL)
BOTTOM SERVICE
PANELS
(SEE NOTE 3)
t
16.63
FRONT VIEW
-----7 :O
(SEE NOTE 2) !
W3
(OPENING)
IilIiii J
i
f '
_-]IUlIIIIII IL-
y-
RETURN AJR
LOUVERED PANEL
(OPTIONAL)
Bo'n'OM VIEW
-ELECTRICAL
BOX
DISCONNECT
SWITCH
8.00
NOTE 2)
REMOVABLE PANEL
(EACH END)
475_l--
(TYP)
OPENING (OPTIONAL
1.00 (TYp)
W4 17.50
_
LEGEND
CCN -- Carrier Comfort Network_
3,67
(TYP)
(_ .75
(MOUNTING HOLES---
TYP-4 PLACES)
1.25 4.50
TOP VIEW
2.27 _1 REAR OUTSI DWE2AIR /
5.00 _I OPENING(C)PTIONAL)7 l _ "
300
iL
II 3_! o ,, ITII
575_ _,_G(%_,_N%)_
REAR VIEW
2.50
(TYP)
UNIT AIRFLOW DEPTH DIMENSIONS (In.) APPROXIMATE
SHIPPING
40UH (cfm) (in.) Wl W2 W3 W4 W5 WEIGHT (Ib)
075 750 40 62 36 36 18.67 7.00 530
100 1000 40 74 48 48 18.67 7.00 640
125 1250 40 86 60 60 18.67 7.00 790
150 1500 40 98 72 72 10.67 7.00 880
200 2000 44 98 72 72 26.92 10.00 1050
APPROXIMATE
INSTALLED
WEIGHT (Ib)
515
620
770
86O
1030
NOTES:
1. All dimensions are in inches.
2. Dimension does not include end panels.
3. Two bottom panels provided for service
access.
4. Motor and electricel power input box on
right side of unit. Box includes fan
speed switch, OnJOff switch and non-
fused disconnect switch.
5. Connection hand is determined by fac-
ing discharge of unit.
Fig, 5 -- 40UH Dimensions -- Down Discharge Plenum
Make Piping Connections -- Access to piping is
available through the access panels at the front, top, or end of
the vertical unit (horizontal access from bottom or side). Route
piping through the pipe tunnel or the unit's back panel or floor
panel. Metal blank-off panels must be trimmed to complete
piping installation. All piping connections must be performed
by qualified personnel in accordance with local and national
codes.
DRAIN CONNECTIONS -- Condensate drain connections
are located on each end of the drain pan near the bottom of the
unit. Condensate drain line must be 3/4 in. copper tubing,
.galvanized pipe, PVC or similar plastic pipe. Install drain line
m accordance with all applicable codes. Insulate the drain
line to prevent sweating. See Fig. 6 for typical drain trap
construction.
Units with cooling coils require traps to prevent air from
entering the condensate fitting and preventing proper drainage.
Drain must flow downhill from the unit a minimum of 1/_in.
per ft. Drain must be flee and clear at all times.
Insulate drain lines to prevent condensate. Care must be
taken to avoid interference with control panel on left side
drain.
WATER SUPPLY/RETURN CONNECTIONS -- Install pip-
mg in accordance with all apphcable codes. All piping must be
supported separately from coils.
Water supply must be connected so that entering water is on
leaving-air side of coil. See the connection labels on the unit to
locate the inlet. Coils must be adequately vented to prevent air
binding. Be sure valves are in proper operating position and are
easily accessible for adjustment.
If coil and valve package connections will be made with a
solder joint, care should be taken to ensure that components in
the valve package are not subjected to high temperatures which
may damage seals or other materials. Many 2-position electric
control valves are provided with a manual operating lever. This
lever should be in the OPEN position during all soldering
operations.
If coil connection is made with a union, the coil side of the
union must be prevented from turning (it must be backed up)
during tightening. Do not overdghten? Overtightening will dis-
tort (egg shape) the union seal surface and destroy the union
NOTE: A freezestat is factory-installed when a hot water/steam
coil is installed.
STEAM CONNECTIONS -- On units with steam heating
coils, the maximum steam pressure applied to the unit should
never exceed 10 psig (operating pressure 6 psig).
DIRECT EXPANSION REFRIGERANT PIPING -- Use the
condensing unit manufacturer's recommended line sizes and
requirements. Perform leak test using nitrogen. Evacuate and
charge per recommended heating, ventilation, and air condi-
tioning (HVAC) procedures and all applicable codes. Insulate
suction line after leak test up to the coil section end plate for
correct operation and to ehminate sweating. Use refrigerant-
grade copper lines only. The unit is NOT to be apphed as a
heat pump.
See Fig. 7 for refrigerant piping connections with recom-
mended locations for the thermostatic expansion valve (TXV)
and sensing bulb.
HYDRONIC COIL PIPING -- When all joints am complete,
perform hydrostatic test for leaks. Vent all coils at this time.
Cheek interior unit piping for signs of leakage from shipping
damage or mishandling. If leaks are found, notify a Carrier
representative before initiating any repairs. Release trapped air
from system (refer to Make Final Preparations section).
3/4"
PVC OR COPPER
3" MIN
2"MIN
3/4"
GALVANIZED PiPE
3" MIN
2" MIN
Fig. 6 -- Typical Condensate Drain Trap
Construction
EQUALIZER
_/ SENSING BULB (CLAMPED TO
ISUCTION LINE AND INSULATED)
__ SUCTION LINE
_LIQUID LINE
NOTE:FollowTXV manufacturer'sinstructions.
Fig. 7 -- Typical TXV (Thermostatic Expansion
Valve) Installation
All water coils must be protected from freezing after initial
filling with water. Even if system is drained, unit coils may
still have enough remaining water to cause damage when
exposed to temperatures below freezing.
Following the hydrostatic test, insulate all piping up to the
coil section end plate to prevent sweating.
To ensure compliance with building codes, restore the struc-
ttue's original fire resistance rating by sealing all holes with
material carrying the same fire rating as the structure.
Make Electrical Connections -- Refer to unit serial
plate for required supply voltage, fan and heater amperage, and
required circuit ampacities. Refer to unit wiring diagram for
unit and field wiring. See Tables 24 for electrical data.
All input power wiring connections are accessed through
the electrical panel on front right-hand side of the unit. Use the
openings that am for the piping connections. See the dimen-
sional drawings Fig. 1-5 for electrical box connections.
The fan motor should never be controlled by any wiring or
device other than the factory-supplied switch or thermostat/
switch combination unless prior factory authorization is ob-
tained. Fan motor may be temporarily wired for use during
construction only with prior factory approval and only in strict
accordance with the instructions issued at that time.
All electrical connections should be made by qualified per-
sonnel and be in accordance with governing codes and ordinanc-
es. Any modification of unit wiring without factory authorization
will invalidate all factory warranties and nullify any agency list-
ings. See Fig. 8A and 8B for typical wiring connections for basic
unit with CCN (Carrier Comfo_ Network®) controls.
Actuators (Field-Supplied) -- Field-supplied actuators
must be mounted on l/zin. diameter damper shafts.
Table 2 -- Electric Heater Data for Units with PSC Motor
UNIT FLA
40UV060
(at 500 Cfm)
HP NOMINAL NUMBER
OF
V/PWHz ELEMENTS
3
4
208/1/60 5
6
3
4
240/1/60 5
6
3
4
277/1/50 5
6
1/s 3
4
208/3/60 5
6
3
4
240/3/60 5
6
3
4
460/3/60 5
6
LEGEND
OX -- Direct Expansion
FLA -- Full LoadAmps
I.AT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse S_ze
orCircuit Breaker Amps)
PSC -- Permanent Split Capacitor
17.2
22.2
27.3
32.3
19.5
25.3
31.2
37.0
16.8
21.8
26.9
31.9
10.8
15.8
19.5
19.5
12.1
17,9
22.2
22.2
6.0
8.9
11.0
11,0
LAT
(F)
90
97
104
119
97
106
115
124
97
106
115
124
90
97
104
110
97
106
116
124
07
106
115
124
NOTES:
TOTAL
MCA MocP CAPACITY
(kW)
21.5 25 3.2
27,8 30 4,2
34.1 35 5.3
40.4 45 6.3
24.4 25 4.2
31,7 35 5.6
39.0 40 7.0
46.3 50 8,4
21 ,O 25 4.2
27.3 30 5,6
33.6 35 7,0
39.9 40 8.4
13.5 15 3.2
19.6 20 4.2
24.4 25 5.3
24.4 25 6.3
15.1 20 4.2
22.4 25 5.6
27.8 30 7.0
27.8 30 8.4
7.5 15 4.2
11.1 15 5.6
13.8 15 7.0
13.8 15 8.4
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available in the reheat posiiton only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
Table 2 -- Electric Heater Data for Units with PSC Motor (cont)
UNIT HP NOMINAL
V/Ph/Hz FLA MCA MOCP
40UV, UH075
(at 750 Cfm) 1/5
DX -- Direct Expansion
FLA
I-AT
208/1/60
240/1/60
27711/60
208/3/60
240/_60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
-- Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
-- Unit Minimum Circuit Ampacity
23.7
30.9
38.1
45.3
27.0
35.3
43.7
52.0
23.3
30.5
37.7
44,9
14.5
21.7
27.0
27.0
16.5
24.8
30.9
30.9
8.2
12.3
15.4
15.4
LAT
(F)
69
96
102
108
96
104
113
121
96
104
113
121
99
96
102
103
96
104
113
121
96
104
113
121
29.6
38.6
47.6
56.7
33.8
44.2
54.6
65,0
29.1
38.1
47.1
56.2
18.2
27,2
33.8
33.8
20.6
31.0
38.6
38.6
10.2
15,4
19.2
19,2
3O
40
50
6O
35
45
60
70
30
40
50
60
20
3O
35
35
25
35
40
40
15
20
20
20
TOTAL
CAPACITY
(kW)
4.5
6.0
7.5
9.0
6.0
8.0
10.0
12.0
6.0
8.0
10.0
12.0
4.5
6.0
7.5
9.0
6.0
8.0
10.0
12.0
6.0
8.0
10.0
12.0
MCA
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available inthe reheat position onlyand connec-
tions are on the rightside.
4. Face and bypass units are available with 3 heating elements
only,
z0
Table 2 -- Electric Heater Data for Units with PSC Motor (cont)
uNrr HP NOMINAL
v/Ph/Hz FLA MCA
40UV, UH1OO
(at 1000 Cfm)
208/1/60
240/1/60
277/1_0
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full LoadAmps
LAT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA -- Unit Minimum Circuit Ampacity
30.9
40.5
50.2
59.8
35.3
46.5
57.6
68.7
30.5
40.1
49.7
59,4
18,7
28.3
35.4
35.4
21.3
32.4
40.5
40.5
10.6
16.1
20.2
20.2
LAT
(F)
89
95
102
IO8
96
104
112
121
96
I04
112
121
89
95
102
108
96
104
112
121
96
104
112
121
38.6
50.7
62.7
74.7
44,2
58.1
72,0
85.8
38.1
50.1
62.2
74.2
23.4
35.4
44.3
44.3
26.6
40.5
50.7
50.7
13.2
20.1
25.2
25.2
TOTAL
MOCP CAPACITY
(kW)
40 6.0
60 8.0
70 10.0
80 11,9
45 8.0
60 10,7
80 13.3
90 16.0
40 8.0
60 10.7
70 13.3
80 16.0
25 6.0
40 8.0
45 10.0
45 11,9
30 8.0
45 10.7
60 13.3
60 16.0
15 8.0
25 10.7
30 13.3
30 16.0
MOCP -- Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
t. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat positiononly and connec-
tions are on the rightside.
4. Face and bypass units are available with 3 heating elements
only.
1]
Table 2 -- Electric Heater Data for Units with PSC Motor (cont)
UNIT HP NOMINAL
V/Ph/Hz FLA MCA
40UV, UH125
(at 1250 Cfm) 1/s
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6*
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full LoadAmps
I.AT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
38.1
50.1
62.2
74.2
43.7
57.6
71.4
85.3
37.7
49.7
61.8
73.8
22.9
34.9
43.7
43.7
26.1
40.0
50.2
50.2
13.0
19.9
25.0
25.0
LAT
(F)
89
96
102
108
96
104
113
121
96
104
113
121
89
96
102
108
96
104
113
121
96
104
113
121
47.6
62.7
77.7
92.8
54.6
71.9
89.3
106.7
47.1
62.2
77.2
92.2
28.6
43.6
54.7
54.7
32.6
50.0
62.7
62.7
16.2
24.9
31.3
31.3
TOTAL
MOCP CAPACITY
(kW)
50 7.5
70 10.0
80 12.5
100 15.0
60 10.0
80 13.3
90 16,7
110 20.0
50 10,0
70 13.3
80 16,7
100 2O,O
30 7.5
45 10.0
60 12.5
60 15.0
35 10.0
50 13.3
70 16.7
70 20.0
20 10,0
25 13.3
35 16,7
35 20.0
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm,
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3, Electricheatisavailableinthereheatpositiononlyandconnec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only,
*Left hand coil connections only.
12
Table 2 -- Electric Heater Data for Units with PSC Motor (cont)
UNIT HP NOMINAL
V/Ph/Hz FLA MCA MOCP
40UV,UH150
(at 1500 Cfm)
DX -- Direct Expansion
FLA
LAT
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6*
3
4
5*
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
-- Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
Temperature
45.3
59,8
74.2
88.7
52.0
68.7
85.3
44.9
59,4
73.8
27.0
41.5
52.1
52.1
30.9
47,5
59,8
59,8
15.4
23.7
29.8
29,8
LAT
(F)
89
96
102
109
96
104
113
96
104
113
80
96
102
108
96
104
113
121
96
104
113
121
56.7
74.7
92.8
110.8
65.0
85.8
106.7
56.2
74.2
92.3
33.8
61.9
65.1
65,1
38.6
59.5
74.8
74.8
19,2
29.6
37.3
37.3
60
80
100
125
70
90
110
6O
80
100
35
6O
70
7O
4O
6O
80
90
2O
30
40
4O
TOTAL
CAPACITY
(kW)
9.0
12.0
15.0
18.0
12.0
16,0
20.0
12.0
16.0
20.0
9,0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Ovemurrent Protection (Maximum Fuse SLze
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat le available in the reheat positiononly and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
*Left hand coil connectionsonly.
13
Table 3 -- Electric Heater Data for Units with ECM
UNIT
40UV05O
(at 500 Cfm)
HP NOMINAL
V/Ph/Hz
208/1/66
240/1/60
277/1/60
1/3
208/3/60
240/3/60
460/3/60
LEGEND
-- Direct Expansion
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
DX
FLA
LAT
Temperature
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
orCircuit Breaker Amps)
PSC -- Permanent Split Capacitor
-- Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
FLA
16.5
21.5
26,6
31,6
18,8
24,6
30,5
36.3
16,3
21,3
26,4
31,4
10,1
15.1
18.8
18.8
11.4
17.2
21.5
21.5
5.4
8.3
10.5
10.5
LAT
(F)
90
97
104
110
97
106
115
t 24
97
166
115
124
90
97
104
110
97
106
115
124
97
106
115
124
NOTES:
TOTAL
MCA MOCP CAPACITY
(kW)
20.6 25 3,2
26.9 30 4,2
33.2 35 5,3
39.5 40 6,3
23.5 25 4,2
30.8 35 5.6
38.1 40 7.0
45.4 50 8.4
20.3 25 4.2
26.6 30 5.6
33.0 35 7.0
39.3 40 8,4
12.6 15 3.2
18.9 20 4.2
23.5 25 5.3
23.5 25 6.3
14.3 15 4.2
21,6 25 5.6
26.9 30 7.6
26.9 30 8.4
6.8 15 4.2
16.4 15 5.8
13.1 15 7.0
13.1 15 8.4
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available inthe reheat position only and connec-
tions are on the rigl_ side.
4. Face and bypass units are available with 3 heating elements
only.
]4
Table3-- Electric Heater Data for Units with ECM (cont)
UNIT HP NOM[NAL NUMBER
OF FLA LAT
V/Ph/Hz ELEMENTS (F) MCA
40UV, UH075
(at 750 Cfm) 1/z
DX -- Direct Expansion
208/1/60
240/1/50
277/1/60
208/3/60
240/0/60
460/0/60
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
-- Full Load Amps
Leaving-Air Temperature at 70 F Entering-Air
FLA
LAT
Temperature
MCA -- Unit Minimum CircuitAmpacity
24.0
31.2
38.4
45.6
27.3
35.6
44.0
52.3
23.7
30.9
38.1
45.3
14.8
22.0
27.3
27.3
16.8
25.1
31.2
31.2
8.2
12.3
15.4
15.4
89
96
102
108
96
104
113
121
96
104
113
121
89
96
102
108
96
104
113
121
96
104
113
121
30.0
39.0
48.0
57.0
34.1
44.5
55.0
65.4
29.6
38.6
47.6
56.7
18.5
27.6
34.2
34.2
20.9
31.4
39.0
39.0
10.2
15.4
19.2
19.2
TOTAL
MOCP CAPACITY
(kW)
30 4.5
40 6.0
50 7.5
60 9.0
35 6.0
45 8.0
60 10.0
70 12.0
30 6.0
40 8.0
50 10.0
60 12.0
20 4.5
30 6,0
35 7,5
35 9.0
25 6.0
35 8,0
40 10.0
40 12,0
15 6.0
20 8.0
20 10,0
20 12,0
MOCP -- Maximum Overcurrent Protection (Maximum Fuse S_e
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2, Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat positiononly and connec-
tions are on the right side.
4, Face and bypass units are available with 3 heating elements
only,
15
Table 3 -- Electric Heater Data for Units with ECM (cont)
UNIT HP NOMINAL
V/Ph/Hz FLA MCA
40UV,UH100
(at 1000 Cfm)
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
31.5
41.1
50.8
60.4
35.9
47.1
58.2
69.3
31.2
40.8
50.4
60.1
19.3
28.9
36.0
36.0
21.9
33.0
41.1
41.1
10.6
16.2
20.3
20.3
LAT
(F)
89
95
102
108
96
104
112
121
96
104
112
121
89
95
102
108
96
104
112
121
96
104
112
121
39.4
51.4
63.4
75.5
44.9
58.8
72.7
88.6
39.0
51.0
63.1
75.1
24.1
36.2
45.0
45.0
27.3
41.2
51.4
51.4
13.3
20.2
25.3
25.3
TOTAL
MOCP CAPACITY
(kW)
40 6.0
60 8.0
70 10.0
80 11.9
45 8.0
60 10.7
80 13,3
90 16,0
40 8.0
60 10.7
70 13.3
80 16.0
25 6.0
40 8.0
50 10.0
50 11,9
30 8.0
45 10.7
60 13.3
60 16.0
15 8.0
25 10.7
30 13.3
30 16.0
DX -- Direct Expansion
FLA -- Full Load Amps
I.AT Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
orCircuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal ctm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3heating elements
onty.
]6
Table 3 -- Electric Heater Data for Units with ECM (cont)
UNIT HP NOMINAL
V/Ph/Hz FLA MCA
40UV, UH125
(at 1250 Cfm) 1/2
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6"
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full LoadAmps
LAT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA -- Unit Minimum Circuit Ampacity
39.4
51.5
63.5
75.5
45.0
58.9
72.7
86.6
39.0
51.0
63,1
75.1
24.2
36,2
45,0
45.0
27.4
41.3
51.5
51.5
13.2
20.2
25.3
25.3
LAT
(F)
89
95
102
108
96
1O4
113
121
96
104
113
121
89
96
102
108
96
104
113
121
96
104
113
121
49.3
64.3
79.4
94.4
56.2
73.6
90.9
108.3
48.7
63.8
78.8
93.9
30.2
45.3
56.3
56.3
34.2
51.6
64.3
64.3
16.5
25.2
31.6
31.6
TOTAL
MOCP CAPACITY
(kW)
50 7,5
7O 10.0
80 12,5
100 15.0
60 10.0
80 13.3
100 16.7
110 20.0
50 10.0
70 13.3
80 16.7
100 20.0
35 7.5
50 10.0
60 12.5
60 15.0
35 10.0
60 13.3
70 16.7
70 20.0
20 10,0
30 13.3
35 16,7
35 20.0
MOCP -- Maximum Ovemurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only
*Left hand coilconnections only.
]?
Table3-- Electric Heater Data for Units with ECM (cont)
UNIT HP NOMINAL
VfPh/Hz FLA MCA MOCP
40UV,UH150
(at 1500 Cfm) 1/2
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6*
3
4
5*
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full Load Amps
LAT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
46.7
61.1
75.6
90.0
53.3
70.0
66.6
46.2
60.7
75.1
28.3
42.8
53.4
53.4
32.2
48.9
61.1
61.1
15.6
24.0
30.1
30.1
LAT
(F)
39
96
102
108
96
104
113
96
104
113
89
96
102
108
96
104
113
121
96
104
113
121
58.3
76.4
94.4
112.5
66.6
87.5
108.3
57.8
75.8
93.9
35.4
53.5
66.7
66.7
40.9
61.1
76.4
76.4
19.5
30.0
37.6
37.6
60
8O
100
125
70
90
110
6O
8O
100
40
60
70
7O
45
70
8O
8O
20
3O
40
40
TOTAL
CAPACITY
(kW)
9.0
12.0
15.0
18.0
12.0
16.0
20.0
12.0
16,0
20.0
9.0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available inthe reheat positiononly and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
*Left hand coil connections only.
]g
Table3-- Electric Heater Data for Units with ECM (cont)
UNIT HP NOMINAL
V/PWHz FLA MCA
40UH200
(at 2000 Cfm)
208/1/60
240/1/60
27_1_0
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6*
3
4
5*
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full Load Amps
I.AT -- Leaving-Air Temperature at 70 F Entedng-Air
50.1
64.6
79.0
93.5
56.8
73.5
90.1
48.8
63.3
77.7
31.8
46.3
56.9
56.9
35.7
52.4
64.6
64.6
16,9
25.2
31,3
31.3
LAT
(F)
84
89
84
99
89
96
102
89
96
102
84
89
94
99
89
96
102
I08
89
96
102
I08
62.7
80.7
98.8
116.8
71.0
91.8
112.7
61.0
79.1
97,1
39.8
57.9
71.1
71.1
44.6
65.5
80.8
80.8
21.1
31.5
39.1
39.1
TOTAL
MOCP CAPACITY
(kW)
70 9.0
90 12,0
100 15.0
125 18.0
80 12.0
100 16.0
125 20.0
70 12.0
80 16.0
100 20.0
40 9.0
69 12.0
80 15.0
80 18.0
45 12.0
70 16.0
90 20.0
90 24,0
25 12.0
35 16,0
40 20,0
40 24.0
Temperature
MCA -- Unit Minimum CircuitAmpacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse S_-e
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coilconnections.
3. Electric heat is available inthe reheat position onlyand connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
*Left hand coil connections only
19
UNIT 40UV,UH SIZE
050*
O75
100
125
150
MOTORHp
I/s
'/s
I/s
Table 4 -- Motor Data
PSC MOTORS
VOLTAGE FLA MCA MOP (Amps)
115 3.7 4.6 8,3
208/230 2.0 2.5 4,5
266 1.6 2,0 3,6
115 3,7 4.6 8.3
208/230 2.0 2.5 4.5
265 1.6 2.0 3.6
115 3.7 4.6 8.3
208/230 2,0 2.5 4.5
265 1,6 2,0 3,6
115 3,7 4.6 8.3
208/230 2,0 2,5 4,5
265 t .6 2,0 3,6
t 15 3.7 4,6 8,3
208/230 2.0 2.5 4.5
265 1.6 2,0 3,6
MAX FUSE SIZE
(Amps)
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
UNIT 40UV, UH SIZE
05O*
075
100
125
150
200t"
MOTOR Hp
%
1/3
1/3
1/2
¾
LEGEND
ECM -- Electronically Commutated Motor
FLA -- Full Load Amps
MCA -- Minimum Circuit Amps
MOP -- Maximum Overload Protection
PSC -- Permanent Split Capacitor
*Available in vertical configuration only,
"j-Available in horizontal configuration only,
ECM
VOLTAGE
115
208/230
265
115
208/230
265
115
208/230
265
115
208/230
265
115
208/230
265
115
208/236
265
FLA MCA MOP(Am_)
1.4 1.8 3.1
1.3 1.6 2.9
1,1 1.4 2.6
3,7 4.6 8.3
2,3 2.9 5.1
2.0 2.5 4.5
4,0 5,0 9.1
2,6 3,2 5.8
2.3 2,9 5.1
4.7 5.9 10.6
3.3 4.1 7.4
2.9 3.6 6.6
4.7 5.9 10.6
3.3 4.1 7.4
2.9 3.6 6.6
9,6 12.0 21.6
6.8 8.5 15.3
5.5 6.9 12.4
MAX FUSE SIZE
{Amps)
15
15
15
15
15
15
15
15
t5
16
15
15
15
15
15
20
15
15
2O
BLK/100 DISC1 • BLK/101 BLK/I_ SWl BLK/10g
Lt --- __.,,_
115v USE COPPER SUPPLY WIRES
WHT/110 WHT/110 WHT/I_
N .... I
GND .... %
LEGEND
DISC -- Disconnect Switch
ECM -- Electronically Comrnutated Motor
ESP -- External Static Pressure
FU -- Fuse
GND -- Ground
LLT -- Water Coil Low LimitThermostat
SW -- Switch
TRAN -- Transformer
--_ _--- Harness Conn•ction
• Connection Point Splice
•Splice Terminal Connection
O Component Tie Point
.... Optional Wiring
-- Factory Wiring
Chassis Ground
Earth Ground
,.0v.c il ,.vAc
WHT/111 •_II_RN_504
NOTES:
1. Make electrical installation in accordance with job diagram, and in com-
pliance with naUon•l and local electrical codes,
2. Low limit thermostat (LLT) is installed on all units with water ceils.
3. Wire YEL/EC5 factory connected to LOW. Positions MED, HIGH, MAX
• re for field use with increased ESR
ISW2 C) AUTO WHT/515
OF F
(_ CONT V!O/516
CBC1
RED/511 _ !_
BRN/51 7m
_ YEU51
WHT/51 Ii I
VIO/51'
BLU/51
ORN/51;
BLU/EC9
ORN/EC2•
SEE NOTE 3
SPEEDBOARD
LOW YEUE05 _ 5
HIGH
= RED,EO<.
EC
i,W,RE\J ,P,.
POWER _ RECEPTACLE
CABLE _ _ ON MOTOR
Fig. 8A -- Unit Ventilator Wiring with CCN Controls -- Control Box (115 vac)
t-J
RESISTOR HARNESS
1000 ohm I V1C
NOTE 3 _-- _I000 ohm_ --I
Detail A - STEAM VALVE WIRING
LL OR
VlO/2 Ni3
See Detail A for
Slum Vah_ Wiring, VIC
LEGEND RED RED
AQ -- Air Quality BLU
CCN Carder Comfort Network® rio
CGO_ Changeover
COM -- Common
CW Chilled Water
ECM E_ectronically
Commu
GND Ground v2c
HW
CGOVR -- Changeover
-- Chilled Water NOTE3
Commutatad Motor
-- Hot Water
LL -- Low Limit Device
MAT -- Mixed Air Temperature
NC
NO
OA
OAT
OCC/
UNOCC
RAT
RH
SAT
EPT
SPT ADJ
-- Normally Closed
Normally Open
Outdcor Ad
-- Outdoor Air Temperature
-- Occupied/Unoccupied
Return Air Temperature
Relative Humdity
Supply Air Temperature
Space Temperature
Space Temperature
Adjustment
Harness Connection
Connection Point Splice
•SpikesTerminal Connection
O
RED F_ED
ORN
YEL
GRa
OA damper no_tnRtniledon
ReclrculationOniy Uni_ OAC
Component Tie Point
Opgonal Wiring
Factory Wiring
TL/ Chassis Ground
Earth Ground
BLUII
-_,T6_
BLU
RED
ORN
YEL
BLK
GRA
RED W_BLKRED
CB,m.CI
.RED==
24vt_t)-- '2<;eLK"
24 V (gnd} -- _. BRN
_D SW2_;OM I_- YEL
SW2-AUTO 5_ WHT
SW2-CONT -- i _ VIO
:_ ECM r_BLU
ECM I") ORN
NOTE 4
NOTES:
CBC3
BRN
RED
csc2
<-3
CBC2
'2 4-8
'3
'4 (-4
'5
_6
_7
_8 _- 5
_9
YEI
YEI
GRI
RED
RED
T1 i
Jl SPT
Power 1"2
T3 i
SAT
J4 T4 i
Sewice MAT T5 i
Te =
_J3 TTi_.
CCN OAT TE
Tg
SPT ADJ T10 i
aT26 24Vdc Tl1 mm
iRED ........... Spare AI TI 2 J
OR ORb
REE
YEL I YEL
BLU l BLU
BLU RAT NOTE 1
_CX SAT
RED OAT
(Field In_toiled}
NOTE i
BLK
WHT
NOTE 2 w/Setp°lnt Adjust
VIO _V_ _T33
WHT I WHT _T34
eLK BLK _T36
Heetlng
=_ T37 Enable
=_,mT38
1"2 Ccollng iT15_ WHT (Optional)
RH/Spam
_. T31 I___j _FieldSupped/
L_-.J
Heating
._T32 Outpat ENTHALPY
SWtTCH
CBC3
cBC,,_._3 ORN
aE°i!
BRN
4VO
t_?_T 5BLU
VIO WriT
BLU
ORN (8 CBC2
SFS T17 m
unused T18 m
OA Enth T19
R SIS 3"20m
FED 3"21m
L'-r T22 _
CH_VR T23 m
Sp_r_ DI _4m
Comm<ln T25 _
/IO
TB2
ORN/38
K3 K2 K1
)RN ORN
_LK/21
IRN
OCC_UNOCC f
FIRFJSMOKE
DETECTOR
RED/FSD
NOTE 5
1. When factory installed, options/wall-mount space sensor is wired to provide set point adjustment only, When remote sensor installation Is field required, disconnect
the factory-supplied return air sensor and wire as shown.
2. Use shielded wire when field installing these parts. Connect the drain wire to the unitchassis and insulate the sensor end, Factory wiring consists of unshlelded wire.
3. Hot water (HW) valve opens on loss of power. Chilled Water (CW) valve oloses on loss of power.
4. See power diagram for CBC1 wiring,
5. Wire RED/FSD factory wired to TB2. When field installing a fire/smoke detector, remove RED/FSD from TB2 and wire as shown.
Fig. 8B -- Unit Ventilator Wiring with CCN Controls -- Control Diagram (115 vac)
Make Duct Connections -- If applicable, install all
ductwolk to and from unit in accordance with all applicable
codes. Duct construction must allow unit to operate within duct
external static pressure limits as shown on job submittals and in
Tables 5 and 6. Duct opening should be the same size as the
unit. For units ducted to multiple openings, make sure there is
adequate straight duct, as shown below, immediately after the
traiL
40UH _ 200
Minimum Straight
Duct Required 75
(Length in ft)
Units designed to operate with ductwork may be damaged
if operated without intended ductwork attached.
Ensure that units ducted to multiple openings have sufficient
straight duct immediately after the uniL
Units provided with outside air must utilize the low-
temperature safety switch to prevent coil freeze-up.
Insulate all ductwork as required. Use flexible connections
to minimize duct-to-unit alignment problems and noise trans-
mission where specified.
Install ductwork, grilles, and plenums so that they do not
restrict access to filter.
Cut openings for supply and return air grilles, thermostats,
and switch plates where specified on job drawings. Be careful
not to cut wires, piping, or structural supports. Use a steel ther-
mostat shield ring to protect drywall from thermostat wiring
where applicable.
Prevent dust and debris from settling in unit. If wall finish or
color is to be applied by spraying, cover all openings to
prevent spray from entering unit_
Table 5 -- Unit Ventilator Airflow -- PSC Motor*
FACTORY SETTINGS -- CHILLED WATER COIL APPLICATIONS
Unit
40UV060
40UV,UH075
40UV,UH100
40UV,UH125
40UV,UH150
Speed 1-Row 2-Row
Max 522 510
High 503 490
Low 458 449
Max 806 778
High 682 664
Low 569 554
Max 1064 1033
High 662 659
Low 530 519
Max 1295 1285
High 899 930
Low 568 616
Max 1542 1480
High 1071 1068
Low 812 801
ApproxlmateAIrDellvery(Cfm)
3-Row 4-Row 5-Row
497 485 490
476 464 473
440 425 452
750 747 766
645 629 621
539 527 533
1001 1013 973
655 642 763
507 503 498
1215 1218 1239
876 865 852
597 570 563
1500 1484 1468
1065 1034 1033
790 881 848
6-Row
489
476
455
732
596
514
980
740
501
1250
846
558
1482
1031
842
7-Row
457
444
430
697
570
495
967
717
584
1175
846
573
1374
1013
799
FACTORY SETrlNGS -- ELECTRIC HEAT/DX COIL APPLICATIONS
Unit
40UVO60
40UV, UH075
40UV, UH100
40UV, UH126
40UV, UH150
Speed 1-Row 2-Row
Max 522 510
High 503 490
Low 458 449
Max 806 778
High 682 664
Low 5fi9 554
Max 1064 1033
High 794 788
Low 662 659
Max 1295 1285
High 1055 1040
Low 738 767
Max 1542 1480
High 1285 1257
Low 934 928
ApproxlmateAIrDellvery(Chn)
3-Row 4-Row 5-Row
497 485 490
476 464 452
440 425 410
750 747 766
645 629 621
539 527 533
1001 1013 973
782 773 857
655 642 628
1215 1218 1239
1024 995 1099
732 719 987
1500 1484 1468
1229 1248 1246
922 901 1033
6-Row
489
455
414
732
596
514
980
834
620
1250
1091
986
1482
1239
1031
7-Row
457
430
406
697
570
495
967
fil0
611
1175
1052
964
1374
1199
1013
LEGEND
CX -- Chilled Water Applications
DX -- Direct Expansion
HW -- Hot Water
*Standard on sizes 050-150.
NOTE: Use the table below to determine the heating and cooting coil
combinations available with PSC Motor operation.
HEATING COIL
COOLING COIL HW Steam Electric
5 Rows Clht 1 or 2 rows 1oN/Asr2ow 3 elements
4 Rows CW 3 rows 1 or 2 rows 4elements
3 Rows CW or nxt 4 rows 5 or 6 elements
tDX cooling applications are only available in 3-row cooling
configurations.
23
Table6-- Unit Ventilator Airflow -- ECM Airflow
UN_ S#E
4OUV050
40UV, UHO75
_U_UHI_
40UV, UH125
40U_UH150
4OUH200
MOTOR
HP COIL TYPE
CW
1/3 3-4EH/DX
5-6EH
CW
l/a 3_EH/DX
5-6EH
CW
1/3 3_.EH/DX
5-6EH 1016
CW 1266
1/z 3*4EH/DX 1266
5-6EH 1259
CW 1503
1/2 3-4EH/DX 150_
5-6EH 1517
s/4 ALL 2014
LEGEND
3-4EH/DX -- Direct Expansion Coil Applications with 3 to
4ELements of Electric Heat
5-6EH m5 to 6 Elements of Electdc Heat
CW -- Chilled Water lica5ons
ESP External Static_rel._u re
APPROXIMATE AIR DELIVERY (C/m)
ESP Speed Board Position
Low Position Med Position High Position Max Position
(0.0 In, wg) (0.10 in. wg) (0.25 in. wg) 10.45 in. wg)
Max Hi_lh Low Max High Low Max High Low Max Hi_lh Low
499 336 248 ............
499 419 336 --
491 380 324 --
747 484 346 753 548 432 752 530 437 751 541 386
747 644 498 753 609 472 752 612 470 751 618 498
755 645 583 746 598 539 755 585 554 765 610 542
997 703 505 987 693 543 1012 663 483 994 692 480
997 853 615 987 850 639 1012 823 526 994 819 618
819 71g 1002 851 709 1024 798 787 1024 820 734
880 657 1239 905 609 1235 898 676 1231 898 627
1023 769 1239 1055 758 1235 1037 765 1231 1010 778
1049 897 1239 995 888 1226 995 888 1253 994 919
1033 775 1479 1046 712 1494 1020 770 1485 1075 737
1246 956 1479 1216 965 1494 1269 927 1486 1222 917
1222 1068 1490 1206 1087 1498 1159 1120 1503 1188 1074
1384 1023 1981 1386 971 1965 1385 997 1814 1354 993
NOTES:
1. Factory default is Low Position.
2. Med, High, and Max positions are field settings.
Make Final Preparations
!. Turn power off (lock out and tag electrical disconnect).
2. Install thermostats and perform any other final wiring as
applicable.
3. Clean dirt, dust, and other construction debris from unit
interior. Be sure to check fan wheel and housing.
4. Rotate fan wheel by hand to be sure it is free and does not
rob on housing.
5. Be sum drain line is clear and is properly and securely
positioned. Pour water into drain to check operation.
6. Vent all air from unit coil and related piping. If air vent is
manual, release air from system by turning air vent screw
1V2 turns counterclockwise with screwdriver. When
steady stream of water begins to escape, close valve. If air
vent is automatic, trapped air will be vented automatical-
ly. Vent releases air slowly, usually dripping water into
drain pan in the process.
Make sure all service valves am open and that motorized
control valves, if supplied, are set for automatic operation.
7. Check all control valves in the system for proper opera-
tion in accordance with valve manufacturer's instructions.
8. For units with factory-installed balancing valves, adjust
as follows:
a. Butterfly valves -- Turn valve gate by inserting
screwdriver into slot in valve top and rotating up to
90 degrees. Valve is fully open when slot is parallel
with valve body. When slot is perpendicular to
body, flow through valve is at minimum. Valve
does not seal against flow.
b. Ball valves with lever handles -- Valve gate action
is similar to butterfly valves above except that
when handle is perpendicular to valve body, there
is no flow through valve. Ball valves may be used
as shutoff valves.
9. Install filter in frame at front of coil. If field-supplied
filters are used, be sure size is correct. See Table 1 for
filter data.
10. Ensure all panels and filters are installed before checking
fan operation. Turn on unit power. Check fan and motor
operation.
IMPORTANT: Do not start up or operate unit without
filter and panels installed. Be sure filter and unit interior
are clean.
PRODUCT INTEGRATED CONTROL
Physical Characteristics -- Figure 9 showsthe loca-
don of factory-supplied and factory-installed sensors, switches,
and devices (standard and optional). Tables 7-11 summarize
the Unit Ventilator Comfort Control module offerings and
accessory packages.
The control includes the electronic control board assembly,
fuses, relay, transformer, rermmal block, low-limit air tempera-
ture protection (water coil units only), and other devices. A
disconnect switch, located below the control box, is provided
to shut off the power to the control box (see Fig. 10). See
Tables 8 and 9 for factory-installed options and accessory
packages.
Control environmental limitations am as follows:
Shipping Temperature -40 to 185 F
Shipping Humidity 10 to 95%
Operating Temperature 32 to 140 F
Operating Humidity 10 to 90%
The Unit Ventilmor Comfort Control module is pewered from
the same source as the unit's single source power connection.
Field wiring fur accessories terminates in the control enclo-
sure. Control accessory wiring requirements am 18 or 20 gage,
2 or 3 conductor twisted as specified. Refer to wiring details for
more information. See Table 10 for control board terminal
designations.
Carder's 40UV, UH unit ventilators with factory-installed
controls are ETL listed and listed to UL standard 1995 for heat-
ing and cooling equipment. All listings are for the complete
unit and all factory-supplied accessories. Use of other accesso-
ry components am not covered under these listings.
24
Table 7 -- Standard Control Offerings
All control offerings provide the following features:
1. A 3-speed automatic fan control that minimizes fan noise by
matching the fan speed to the load. This process provides
better dehumidification during cooling and reduces energy
consumption.
2. American Society of Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) Cycle I, Cycle II, or Cycle I11damper con-
trol options (Cycle II default).
3. Conflgurable minimum ventilation set point (cfm) for ASHRAE
Cycle II or Cycle Ill damper control.
4. Demand controlled ventilation with optional sensor to meet ven-
tilationrequirements with improved efficiency.
5. Coil freeze protection on all units except non-water units.
6. Proportional Integrated Derivative (PID) logic heating, cooling
and damper controls to maintain temperature.
7. Adjustable filter maintenance timer on all units.
8. Direct shaft coupled, electric actuators on all dampers. Spring
returnon outdoor-air (OA) damper.
9. Spring return medulatingwater valves.
10. Optional relative humidity sensor for high humidity control or
dehumidification.
11. Optional remote-mounted space sensor with set point adjust-
ment, tenant override, and service port jack.
12. Optional linkage thermostat with time clock, set point adjust-
ment, .schedu e and. ho iday programming digital temperature
set pointand equlement status dzspley.
CONTROL SEQUENCE
2AJ3A
2Bi3B
2D/3D
2F/3F
2G/3G
2J/3J
20/30
21/31
22/32
23/33
24/34
25/35
2M/3M
2G/3G
2B/3B
2K/3K
OC
OE
OH
LEGEND
DX -- Direct Expansion
F&B -- Face and Bypass
APPLICATION
Heating/Cooling Valve Control
Chilled Water/Hot Water, 2-Pipe Changeover
Chilled Water/Hot Water or Steam, 4-Pipe
Chilled Water with Electric Heat
HUtWater or Steam Heatin_ Only
HUtWater or Steam with DX Cooling
Chilled Water Cooling Only
Heating/Cooling with Face and Bypass Damper Control
Chilled Water/Hot Water, 2-Pipe Changeover
Chilled Water/Hot Water or Steam, 4-Pipe
Chilled Water with Electric Heat
Hot Water or Steam with DX Cooling
Hot Water or Steam Heating Only
Chilled Water Cooling Only
Heating/Cooling with Humidity Control
F&B Chilled Water/Hot Water or Steam Heating 4-Pipe plus Valve Control Reheat for
Dehumidification
Cooling with Hot Water or Steam Reheat, Valve Control
Chilled Water/Hot Water Reheat, 4-Pipe Valve Control
F&B Chilled Water Coolingwith Hot Water or Steam Valve Control Reheat, 4-Pipe
Non-Water Systems
Electric Heat Only
Electric Heat with DX Cooling
DX CoolingOnly
Table 8 -- Field-Installed Accessories
PACKAGE NO.
33CSKITLST-01
CGCDXSENOOIA00
CGCDXSEN002A00
CGCDXGAS001 A00
HI-39ZZO03
PACKAGE DESCRIPTION
Programmable Linkage Thermostat with Timeclock
Wall-Mounted CO2 Sensor (No Display)
Wall-Mounted CO2 Sensor with Display
CO2 Sensor Calibration Service Kit
Wa_l-Mounted Relative Humidity Sensor
Table 9 -- Factory-Installed Options
CODE DESCRIPTION
DIGIT #15 (2,S,M,4,V) Space Temperature Sensor
DIGIT #15 (1,0,R,3) Changeover Switch
25
ELECTRIC HEAT
OVER TEMPERATURE
SAFETY (ELECTRIC HEATONLY)S_
FACE AND BYPASS
DAMPER ACTUATOR
OUTDOOR AIR (MAY BE LOCATED ON OPPOSITE
DAMPERACTUATOR _ END OF COMPARTMENT)
DAMPER ACTUATOR(S)
MODULE
RELATIVE
HUMIDITY
SENSOR
(FIELD-
INSTALLED
ACCESSORY)
SPACE
TEMPERATURE
SENSOR _7-
OPTION
t:o t!N
OISCO_NECT
SWITCH
(FACTORY-
INSTALLED
OPTION) CONTROL COMPARTMENT
WITH FACTORY-INSTALLED
OPTIONS SHOWN
LEGEND
ECM -- Electronically Commutated Motor
LLT -- Low-LimitThermostat
/
!
ROOM-AIR TEMPERATURE MIXED AIR TEMPERATURE SENSOR
SENSOR (UNIT FILTER REMOVED)
Fig. 9 -- Typical Unit Ventilator Comfort Control Module Sensor, Switch, and Device Locations
Table10-- ControlBoardTerminalDesignations
CONTROL BOARD
TERMINAL
T1
T2
T3
T4
T5
T6
1"/
T8
T9
T1O
Tll
T12
T13
T14
T15
T16
T17
T18
T19
1"20
FUNCTION CONTROL BOARD
TERMINAL
Space Temperature (+) T21
Space Temperature (Gnd) T22
Supply-AirTemperature (+) T23
Supply-AirTemperature (Gnd} T24
Mixed-Air Temperature (+) T25
Mixed-Air Temperature (Gnd) T26
Outdoor-Air Temperature (+) T27
Outdoor-Air Temperature (Gnd) T28
Space Temperature Adjust (+1 T29
Space Temperature Adjust (Gnd) T3O
Nut Used T31
Not Used 1"32
Air Quality (+) T33
Air Quality (Gnd) T34
Relative Humidity (+) T35
Relative Humid_ (Gnd) T36
Fan Status 1"37
Not Used T38
Outdoor Air Enthal WT39
Remote Start/Stop LEGEND
Gnd -- Ground
FUNCTION
Fire/Smoke Status
Freezestat
Changeover
Spare
Common/Ground
24 VDC (External PowerSupply)
Not Available
Cooling First Stage orValve Open
Cooling Common
Cooling Second Stage or Valve Close
Heating FirstStage or Valve Open
Heating Common
Heating Second Stage or Valve Close
OAD Open
CAD Common
CAD Close
Heating Enable
Common
Cooling Enable
OAD -- Outdoor-Air Damper
'!1/I
°°,,
° O
o
©
Fig. 10 _Control Switch Location
Unit Ventilator Comfort Control Module Instal-
lation and Field Wiring -- The modale is factory-
installed and factory-wired within the control compartment.
The Unit Ventilator Comfort Control module contains the soft-
ware and microprocessor that operates the unit. It continuously
monitors inputs and controls outputs such as the fan cooling
and heating coil valves and dampers.Refer to Fig. 11 for
wiring diagram connections between the unit's sensors and
actuators and the control module. Direct expansion cooling
and/or electric heat stage control are also provided.
27
POWER
[] J4RVICE CONNECTOR
CON
T26
_- 2lVdc
T1
T2I
I--_'_'--IT41T31
T61TEl
ANALOGI_5_'--ITsI_1
SENSOR
,NPUT Tic
I-
I-
T32 HEATING
_"_ OUTPUT
_"_'_ MIXEDAIR
T35 DAMPER
I_ OUTPUT
TI_I--
T19 _-_
DISCRETE T20_'_
SWITCH T21_'_
INPUTS T22_'_
_-"_ H_.TING T23_'--
T38 ENABLE T24_-
_-_ COOLING
I_.T=39T ENABLE COMMON
GND T251-_
K3 K2
HI/MED MED/LO K1
FANSPEED FANSPEED FANON/OFF
j-•I
I I
III
iI
iI
I I
I
tI
[ I I
i i
' r i ......._ OPTIONAL
_ -- -- -- L-_'-_-_--- _""---- -- --"[_ WALL SENSOR
TB
LEGEND
ADJ -- Adjust NC -- Normally Closed
AQ -- Air Quality NO -- Normally Open
CCN -- Carrier Comfort Network_ Controls RAT -- R_turn-Air Temperature Sensor
COM -- Common S/S -- Start/Stop
ENT -- Enthalpy Sensor SAT -- Supply-AirTemperature Sensor
GND -- Ground SPT -- Space Temperature Sensor
MAT -- Mixed-AirTemperature Sensor RH -- Relative Humidity
OA ENTH -- Outdoor-Air Enthalpy TB -- Terminal Block
Outdoor-Air Temperature
OAT -- Sensor
NOTE: Only one SPT sensor can be used. If wall-mounted sensor option isused,
unit-mounted sensor wire to terminal T1 must be removed.
Fig. 11 -- Unit Ventilator Comfort Control Module with Sensor Connections
28
Sensors
ROOM-AIR TEMPERATURE (RAT) SENSOR-- The RAT
sensor is factory-installed and factory-wired to the control. It
measures the temperature of the air returning to the unit from
the space.
The sensor consists of a thermistor, encased within an
epoxy bead. See Fig. 12. It is mounted behind the front center
panel, where it is hidden from view.
The sensor has a range of -40 to 245 F with a nominal
resistance of 10,000 ohms at 77 E The sensor is connected to
terminals T1 and T2 on the controller board. See Table 11.
Polarity is not a consideration. See Table 10 for resistance vs
temperature values.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR --The SAT
is factory-installed and factory-wired to the control module. It
measures the temperature of the air leaving the unit.
The sensor consists of a thermistor encased within an epoxy
bead. It is mounted in the fan discharge with the probe mount-
ed to sense the air temperature supplied to the room. See
Fig. 12.
The sensor's thermistor has a range of-40 to 245 F with a
nominal resistance of 10,000 ohms at 77 E
NOTE: A temperature of the supply air includes fan heal
In the control box, the sensor wiles are connected to termi-
nals T3 and T4 (SAT) on the controller board (see Table 11).
Polarity is not a consideration. See Table 12 for resistance vs
temperature values.
Fig. 12 -- Room-Air Temperature and Supply-Air
Temperature Sensor (Part No. HN79NZ005)
Table 11 -- Sensor Connections
CONTROL
SENSOR MODULE
PiN NO.
Unit Mounted Room-Air Temperature T1 and 7-2
Sensor (RAT)
Space Temperature Sensor (SPT) Wall T1, 7-9,T19, Shield
Mount (Option)
Supply-Air Temperature (SAT) 1-3and 7-4
Mixed-Air Temperature Sensor (MAT) 1-5and 7-6
Outdoor-Air Temperature Sensor (OAT) T7 and 7-8
Table 12 -- Thermistor Resistance vs Temperature Values for Room-Air Temperature Sensor,
Supply-Air Temperature Sensor, Mixed-Air Temperature Sensor,
and Optional Space Temperature Sensor
TEMP
(C)
--40
-35
-30
-25
-20
-15
-10
-5
O
5
10
15
20
25
3O
35
40
45
5O
56
6O
65
7O
TEMP
40
-31
43
_4
5
14
23
32
41
50
59
68
77
86
85
104
113
122
131
140
149
158
RESISTANCE
(Ohms)
335,651
242,195
176,683
130,243
96,974
72,895
55,298
42,315
32,651
25,395
19,903
15,714
12,494
10,0O0
8,056
6,530
5,325
4,367
3,601
2,985
2,487
2,082
1,752
29
OUTDOOR-AIR TEMPERATURE (OAT) SENSOR -- The
OAT sensor is factory-installed and factory-wired to the con-
trol. The OAT sensor monitors the temperature of the outside
air entering the unit. See Fig. 13.
The sensor is installed immediately upstream from the
outdoor-air damper where it will accurately sense the tempera-
tare of the outdoor air entering the mixing box. The sensor con-
nects to the conlrol module T7 and T8 (OAT) as shown in
Table 11.
The thermistor has a range of -40 to 245 F and a resistance
of 5,000 ohms at 77 F. See Table 13 for thermistor resistance
according to temperature value.
MIXED-AIR TEMPERATURE (MAT) SENSOR -- The
mixed-air temperature (MAT) sensor is factory-supplied,
factory-installed, and factory-wired with each unit. The MAT
measures the temperature of air in the mixing plenum area.
The MAT connects to terminals T5 and T6 on the con-
trol module using 1/4-in. female quick connect ternnnals. See
Table 11.
The sensor uses multiple thermistor elements. This sensor
provides both mechanical and electrical averaging to achieve
an accurate, average temperature measurement over the entire
element length. Polarity is not a consideration. See Table 12 for
resistance vs temperature values. The sensor is installed in the
mixing plenum before the filter so it can sense the average air
temperature. See Fig. 14.
The MAT has range of-40 to 245 F with a nominal resis-
tance of 10,000 ohms at 77 E
LOW-LIMIT THERMOSTAT-- The low-limit thermostat
(LLT) is factory-installed and factory-wired on all units with
water coils. The thermostat is used to protect the water coils
from freezing temperatures in the event of a malfunction by
detecting the status of a potentially damaging condition.
The LLT is a 12-ft capillary tube mounted in the air stream.
See Fig. 15.
The LLT provides a SPDT contact. The contact provides a
sensor status indication to the control module and an electrical
interlock to the fan and water valves. Upon detection of a fault
condition, the unit ventilator will stop the fan, close the
outdoor-air damper, and position water valves as specified in
the sequence of operation. The LLT is factory set to tripat 38 E
The temperature setting is non-adjustable. The switch will
automatically reset and restart the fan after its temperature has
risen by at least 5 °E
Table 13 -- Thermistor Resistance vs Temperature
Values for Outdoor-Air Temperature Sensor
RESISTANCE
(Ohms)
168,250.0
121,350.6
88,500.0
65,200.0
48,535.0
36,470.0
27,665.0
21,165.0
16,325.6
12,695.0
9,950.0
6,245.0
5,000.0
4,028.5
3,265.0
2,663.3
2,185.0
1,801.5
1,493.0
1,244.0
1,041.5
876.0
739.5
027.5
TEMPERATURE
(F)
-4O
-31
-22
-13
-4
5
14
23
32
41
50
68
77
86
95
104
113
122
131
140
149
158
167
176
The LLT is designed to trip if any 1-ft section of the capil-
lary tube senses cold air at or below the thermostat setting. The
temperature must exceed 43 F for the thermostat to automati-
cally reset to restore the circuit to normal operation.
REFRIGERANT LOW-LIMIT THERMOSTAT -- The re-
frigerant low limit thermostat (LLR) is factory-installed and
factory-wired on all units with direct expansion coils. The ther-
mostat is used to protect the water coils from freezing tempera-
tures in the event of a malfunction by detecting the status of a
potentially damaging condition.
The LLR is a 18 in. capillary tube mounted in the air stream.
See Fig. 15.
The LLR provides a SPDT contact. The normally closed
contact is connected in series with the direct expansion relay
coil, such that the DX (direct expansion) control relay is
dcenergized hi a fault condition. The LLR is factory set to trip
at 28 E The temperature seaing is non-adjustable. The switch
will automatically reset and allow direct expansion relay opera-
tion when the temperature has risen by at least 5° E
Fig. 13 -- Outdoor-Air Temperature Sensor
(Part No. HH79NZ055)
Fig. 14 -- Mixed-Air Temperature Sensor Installed
in Mixing Plenum (Part No. HH79NZ075)
Fig. 15 -- Low-Limit Thermostat
30
The LLR is designed to trip if any 1-ft section of the capital-
ly tube senses cold air below the LLR set point. The tempera-
ture must exceed 33 F for the LLR to automatically reset to
restore normal operations.
SPACE TEMPERATURE SENSOR (Factory-Installed
Option) -- The space temperature sensor is used to measure
the building interior temperature. See Fig. 16.
The sensor is shipped with the unit, factory-wired
and factory-mounted in the control swing panel inside the left
hand comparmaent.
If remote temperature sensing is required, then the sensor
may be removed and mounted on an internal wall where
temperature sensed is representative of the entire zone to be
serviced by the unit. The sensor wall plate accommodates the
National Electrical Manufacturers Association (NEMA)
standard 2 x 4 junction box. The sensor can be mounted direct-
ly on the wall surface if acceptable by local codes.
Do not mount the sensor in drafty locations (such as near
air-conditioning or heating ducts), over heat sources (such as
baseboard heaters or radiators), or directly above wall-mounted
lighting dimmers. Do not mount the sensor near a window
which may be opened, near a wall corner, or near a door.
Sensors mounted in these areas will have inaccurate and erratic
sensor readings.
The sensor should be mounted approximately 5 ft from the
floor, in an area representing the average temperature in the
space. Allow at least 4 ft between the sensor and any comer
and mount the sensor at least 2 ft from an open doorway.
Install the sensor as follows (see Fig. 17):
1. Locate the two Allen head screws at the bottom of the
sensor.
2. Turn the two screws clockwise to release the cover from
the sensor wall mounting plate.
3. Lift the cover from the bottom and then release it from
the top fasteners.
4. Feed the wires from the electrical box through the open-
ing in the center of the sensor mounting plate.
5. Using two no. 6-32 x 1 mounting screws (.provided with
the sensor), secure the sensor to the electrical box.
6. Use a three-conductor 20 gage shielded cable. The wire is
suitable for distances of up to 500 ft. The standard CCN
(Carder Comfort Network®) communication cable may
be used. If the set point adjustment (slide-bar) is not re-
quired, then an unshielded, 18 or 20 gage, two-conductor,
twisted pair cable may be used.
The CCN network service jack requires a separate,
shielded three-conductor CCN communication cable.
Always use separate cables for CCN communica-
tion and sensor wiring. (Refer to Fig. 18 for wire
designations.)
7. Replace the cover by inserting the cover at the top of the
mounting plate first, then swing the cover down over the
lower portion. Rotate the two Allen head screws counter-
clockwise until the cover is secured to the mounting plate
and locked in position.
For more sensor information see Table 12 for thermistor
resistance vs temperature values.
NOTE: Clean sensor with damp cloth only. Do not use
solvents.
Fig. 16 -- Space Temperature Sensor
(P/N HH51BX005)
3.28
CLEARANCE HOLES FOR
(2)#SMOUNTING
SCREWS ON CENTERLINE
.79 _F 115
NOTE: Dimensions are in inches.
Fig. 17 -- Space Temperature Sensor and
Wall-Mounted Humidity Sensor Mounting
31
WIRING THE SPACE TEMPERATURE SENSOR AND
SET POINTADJUSTMENT--To wire file sensor and
slidebar, perform file following (see Fig. 18):
1. Identify which cable is intended for sensor wiring.
2. Strip back the jacket from the cables at least 3 inches.
Strip q4-in, of insulation from each conductor. Cut the
shield and dram wire from the sensor end of the cable.
3. Connect the sensor cable as follows:
a. Install a jumper between the two center terminals
(SEN and SET).
b. Remove file existing factory-connected wire on
terminal T1 of the control module.
c. Connect one wire from the cable (RED) to the TI
terminal on the controller. Connect the other end
of the wire to the SEN terminal without the
jumper wire.
d. Connect another wire from the cable (BLACK) to
the T10 terminal on the controller. Connect the
other end of the wire to the remaining jumpered
SEN terminal.
e. Connect the remaining wire (WHrrE/CLR) to the
T9 terminal on the controller. Connect the other
end if the wire to the remaining open terminal on
the SET terminal block.
f. In the control box, install ano. 6 ring type crimp
lug on the shield drain wire. Install this lug under
the mounting screw in the upper right comer of
the controller (just above terminal T1).
WIRING THE CCN NETWORK COMMUNICATION
SERVICE JACK -- To wire the service jack, perform the
following:
1. Strip back the jacket from the CCN communication ca-
ble(s) for at least 3 inches. Strip l/4-in, of insulation from
each conductor. Remove the shield and separate the drain
wire from the cable. Twist together all the shield drain
wires and fasten them together using a closed end crimp
lug or a wire nut. Tape off any exposed bare wire to pre-
vent shorting.
2. Connect the CCN + signal wire(s) (RED) to Terminal 5.
3. Connect the CCN - signal wire(s) (BLACK) to Ter-
rffmal 2.
4. Connect the CCN GND signal wire(s) (WtffI'E/CLR) to
Terminal 4. Before wiring file Rill plug refer to Carrier
Comfort Network@ Interface, page 38 for communica-
tion bus wiring and cable selection. The cable selected
must be identical to the CCN communication bus wire
used for the entire network.
The other end of the communication bus cable must be
connectod to the remainder of the CCN communica-
tion bus. If the cable is installed as a T-tap into the bus,
the cable length cannot exceed 100 ft. Wire the CCN
service jack of the sensor in a daisy chain arrangement
with other equipment. Refer to Cartier Comfort
Network Interface section, page 38 for more details.
LINKAGE THERMOSTAT (Field-Installed Accessory) --
The linkage thermostat can be used to control multiple units
(up to 8 different sizes and types) from a single thermostat,
provide occupancy scheduling for any number of units (all
opamting on the same schedule), and broadcast the changeover
switch status (2-pipa systems) to all units in file system
(Fig. 19). The thermostat is equipped with two liquid crystal
displays (LCD). One LCD is used to display the set points,
space temperature, unit operating mode (Heating, Cooling, Off,
etc.), and discharge air temperature from the unit. The second
LCD displays the time and day of the week. The thermostat has
pushbutton keys to enter the temperature set points, program
file occupancy schedule, program holidays, set time, day, and
date, and configure file functionality of the device.
When the thermostat provides local occupancy and set point
scheduling for these units, it provides a Temperature Compen-
_ted Start feature which starts the unit(s) prior to file scheduled
occupied time in order for file space to achieve the occupied set
point temperature at file occupied time.
The thermostat uses CCN communications to provide the
required information exchange between the thermostat and file
unit's controls.
The thermostat can be used to provide global occupancy
scheduling for any number of units when aCCN user interface
is not provided. In this mode, a 3-wire communication bus
connected between each unit and the thermostat a!lows a user
to program and change equipment occupancy scheduling and
holidays from a single location without requiring the use of a
personal computer. This allows any number of unit ventilators
equipped with the Unit Ventilator Comfort Control module to
operate to a common occupancy schedule (all controllers must
be connected to a single CCN communication bus). Each Unit
Ventilator Comfort Control module will use its own set points
and space temperature settings.
The linkage thermostat can broadcast the value of an equip-
ment status point to all units connected to the communication
bus. The pomt name must be configured using a CCN Service
Tool at installation. A typical example is to broadcast file status
of file changeover switch (2-pipe systems) or a field-supplied
and field-installed outdoor-air enthalpy sensor from the one
unit where the sensor is installed to all other units. This action
reduces the installation cost and operating maintenance of the
entire system.
When used to provide Global Occupancy Scheduling or
Broadcast, file thermostat does NOT need to be mounted in any
specific space. The thermostat can be mounted anywhere in a
conditioned area as long it is connected to file CCN communi-
cation bus.
The linkage feature allows several units to operate from a
single common thermostat. This feature can be used if multiple
units serve a single common area. The thermostat must be
mounted in the common area space for this feature.
Thermostat Mounting Location -- DO NOT mount the sen-
sor in drafty locations (such as near air conditioning or heating
ducts), over heat sources (such as baseboard heaters or radia-
tors), or directly above wall mounted-hghting dimmers. DO
NOT mount file sensor near a window which may be opened,
near a wall comer, or near a door.
Sensors mounted in these areas will have inaccurate and
erratic sensor readings. The sensor should be mounted approxi-
mately 5 ft from the floor, in an area representing the average
temperature in the space. Allow at least 4 ft between the sensor
and any comer and mount the sensor at least 2 ft from an open
doorway. Follow the mounting and wiring inslructions includ-
ed with file thermostat for proper thennostat installation.
32
OVERRIDE
PUSHBUTrON
LEGEND
CCN -- Carrier Comfort Network_
COM -- Common
GNO -- Ground
SENSOR PC
BOARD
JUMPER TERMINALS
AS SHOWN
I
I
SET SEN
CCN
SERVICE
CONNECTOR
SET POINT
ADJUSTMENT
THERMISTORTEMPERATURE
SENSOR
Fig. 18 -- Space Temperature Sensor Wiring
33
9mtl
Fig, 19 -- Linkage Thermostat
Thermostat Power Supply -- The thermostat power supply,
included in the accessory package, provides the required
DC voltage to operate the thermostat, The power supply
includes 24 vac (Class II) transformer.
The transformer and power supply can be mounted within
the unit's control enclosure.
Wiling between the thermostat and the power supply is
limited to 100 ft maximum, fflonger distances am required, the
power supply and Wansformer must be remotely mounted
closer to the thermostat. Be sum to follow all code require-
merits when remotely mounting the transformer as the primary
wiring is Class 1 circuit type. The thermostat power wiring
requires the use of a 2-conductor, 18 AWG, twisted pair cable
to connect the power supply output ternunals to the thermostat.
Follow the installation instructions shipped with the thermostat
for proper installation.
Thermostat Communication Wiring -- The thermostat uses
CCN network communications to exchange data between the
thermostat and the equipment control or the CCN network for
system f_nctions. Use 3-conductor, 20 AWG (American Wire
Gage) minimum, shielded cable as specified in the Carrier
Comfort Network® Interface section. See Table 14.
Thermostat Remote Room Sensor Option -- The installer
has the option of mounting the thermostat in a mechanical
closet or other location in order to limit access to the device. A
remote sensor option can be installed in the space to properly
sense temperature at the occupied location. Refer to the instal-
lation instructions shipped with the thermostat for additional
information on this option.
Table 14- CCN Cable Requirements
MANUFACTURER CABLE NO,
Alpha 2413 or 5463
American A22503
Belden 8772
Columbia 02525
INDOOR AIR QUALITY (IAQ) SENSOR (Field-Installed
Accessory) -- The wall-mounted sensor monitors CO2 in the
conditioned air space, and uses infrared technology to detect
the levels of CO2 present in the air. See Fig. 20. This informa-
tion is used to modify the position of the outdoor-air dampers
to admit more outdoor air as required to provide the desired
ventilation rate. The sensor is available with or without an
LCD readout to display the CO2 level in ppm. Sensor acces-
sory descriptions and part numbers are shown in Table 15. To
mount the sensor, refer to the installation insa'uedons shipped
with the accessory kit.
Table 15 -- Indoor Air Quality Sensor Accessories
CO= SENSOR ACCESSORY DESCRIPTION
PART NUMBERS
CGCDXSENOOlAOO Wall Mount Sensor (No Display)
CGCDXSEN002AO6 Wall Mount Sensor with Display
CGCDXGAS001 A00 Sensor Calibration Service Kit
The CO2 sensors in Table 15 are all factory set for a range of
0 to 2000 ppm and a linear voltage output of 2 to Ill vde.
Fig. 21 shows ventilation rotes for various CO2 set points when
a typical CO2 level of 350 ppm is used. Refer to the instruc-
tions supplied with the CO2 sensor for electrical requirements
and terminal locations. Aseparate isolated field-supplied trans-
former is required to provide power to the sensor.
Any changes to the factory configuration of the sensor
require use of the User Interface Program (UIP), which is
included in the sensor calibration service kit.
The sensor must be properly located to accurately measure
die air quality of the occupied space. It should be mounted in a
location that will avoid direct breath contact.
Do not mount the sensor in drafty areas such as near the unit
discharge, open windows, fans, or over heat sources. Allow at
least 3 ft between the sensor and any comer. Avoid mounting
the sensor where it is influenced by the supply air; the sensor
gives inaccurate readings if supply air is blown directly onto
the sensor.
I U U U LSU_U _
ooooooc
ooooc
oooc
5.625
(14.3)
NOTE:Dimensionsarein inches.
Dimensionsin ( ) are incentimeters.
(12.7)
c
Fig. 20 -- Indoor Air Quality (COz) Sensor
(PN 33ZCSENCO2)
8O
700 9(X] 1100 1300 1500 1700 1900 2100 2300 2500
CO 2CONCENTRATION (PPM)
Fig. 21 -- Ventilation Rates Based on
CO2 Set Point
34
Air Quality Sensor Wiring -- To wire the sensor after it has
been mounted in the conditioned space, see Fig. 22 and the
installation instructions shipped with the sensor. For each
sensor, use 2-conductor 18 AWG twisted-pair cables
(unshielded) to connect the separate isolated 24 vac power
source to the sensor and to connect the sensor to the control
board terminals.
To connect the sensor to the control board, identify the
positive (+) and negative (-) output terminals to the sensor
te_M block and connect the positive terminal to terminal
T13. Connect the negative terminal to terminal TI4 on the
control board. Mount a field-supplied Class I], 24 vac trans-
former with a 40 va rating in a suitable location inside the unit's
control box. Whe the transformer primary to line voltage
power after any fuses and disconnect switches. Ensure the
transformer primary voltage rating matches the unit's voltage
rating. Refer to the wire label diagram shipped with the unit.
Connect one of the transformer secondary leads to the 24 vac
power terminal of the sensor. Connect the remaining secondary
lead to the ground terminal sensor.
[ [RV,DECONNECTOR
CCN
T26
I_ 24Vdc
T,
T61 -
A, LO T31Y__
SENSOR
,NP -rs O1 _1--
T11 }---
"{'32 HEATING
T_I_T OUTPUT
_'_" MIXED AIR
T3 DAMPER
I'_ OUTPUT
Tl_i--
T18 _----
T19_-_
DISCRETE T20_'_
SWITCH T211"_
INPUTS T221_
_"_. HEATING T23_
T38 ENABLE T241"_
I'_ COOLING
__T39 TENABLE COMMON
GND T25_'_
K3 1(2
HI/MED MED_.O K1
FAN SPEED FAN SPEED FAN ON/OFF
co. co. OM
........ FIELD SUPPLIED
ISOLATED 24VAC
POWER SOURCE
LEGEND
ADJ -- Adjust
AQ -- Air Quality
CGN -- Carrier Comfort Network_
COM -- Common
GND -- Ground
MAT -- Mixed-Air Temperature Sensor
OA ENTH -- Outdoor-Air Enthalpy
OAT -- Outdoor-Air Temperature Sensor
NC -- Normally Closed
NO -- Normally Open
RAT -- Return-AirTemperature Sensor
S/S -- Start]Stop
SAT -- Supply-AirTemperature Sensor
SPT -- Space Temperature Sensor
RH -- Relative Humidity
Fig. 22 -- Air Quality Sensor Wiring
35
RELATIVE HUMIDITY SENSOR (Field-Installed Acces-
sory) -- The relative humidity (RH) sensor is used to measure
die relative humidity of die air within the occupied space. The
sensor is ordered separately from the unit, is field-installed and
should be wired in the control compartment below the control
module. It may be mounted directly on an interior wall if
acceptable by local codes. See Fig. 23.
The sensor uses bulk polymer resistance technology, which
eliminates the effect of surface contamination and helps to
maintain sensor accuracy over a long period of time. It has a
long-term stability of less than 1% drift per year.
The relative humidity sensor has a range of 10 to 90% with
an accuracy 0f+_3% at 77 E It generates a 2 to 10 vde signal
which is sent to the controller.
If the sensor is installed directly on a wall surface, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field-supplied); do not overtighten screws. See Fig. 17. The
use of a standard 2 x 4-in. electrical box to accommodate the
wiring is recommended for installation.
DO NOT touch the sensing element or clean with chemical
solvents; they can permanently damage the sensor.
The sensor must be mounted vertically on the wall. The
Carrier logo should be oriented correctly when the sensor is
properly mounted.
DO NOT mount the sensor in drafty areas such as near the
unit's discharge grille, open windows or fans, or over heat
sources such as baseboard heaters, radiators, or wall-mounted
light dimmers. Sensors mounted in those areas will produce
inaccurate readings.
Avoid comer locations. Allow at least 4 ft between the
sensor and any corner. Airflow near comers tends to be
reduced, resulting in erratic sensor readings.
Sensor should be vertically mounted approximately 5 ft up
from the floor.
For distances up to 500 feet, use a 3-conductor shielded,
20 AWG cable. A CCN communication cable can be used. The
shield and drain wire must be removed from the sensor end of
the cable. See Fig. 24 for wiring details.
The power for the sensor is provided by the control board.
The board provides 24 vdc for the sensor. No additional power
source is required.
To wire the sensor, perform the following:
1. At the sensor, remove 4-in. of jacket from the cable. Strip
ll4-in, of insulation from each conductor. Route the cable
through the wire clearance opening in the center of the
sensor. See Fig. 24.
2. Connect the RED wire to the sensor screw terminal
marked (4-).
3.
4.
5.
6.
7.
8.
9.
10.
11.
Install one lead from the resistor (supplied with the sen-
sor) and the WHITE wire, into the sensor screw terminal
marked (-). After tightening the screw terminal, test the
connection by pulling gently on the resistor lead.
Connect the remaining lead from the resistor to the
BLACK wire and secure using a closed end type crimp
connector or wire nut.
Using eleetrical tape, insulate any exposed resistor lead to
prevent shorting.
At the control end, remove the jacket from the cable and
route the RED conductor over to the left side of the con-
_rol board. Route the remaining conductors to the right
side of the control board.
S_p V4-in. of insulation from each conductor and equip
each with a V4-in. female quick connect terminal.
Connect the RED wire to terminal T26 on the control
board.
Connect the BLACK wire to terminal T16 on the control
board.
Connect the WHITE/CI_AR wire to terminal T15 on the
control board.
Equip the shield wire with ano. 8 fork-type lug and
secure to the control module mounting screw between
terminals TI6 and T17.
Fig. 23 -- Wall-Mounted Relative Humidity Sensor
(Part No. HL39ZZ003)
36
[] RV,CEOON.ECTOR
T26
--_"_ 24Vdc
T2 __
T4 -
T5_-_
T6 I-
ANALOG _T8 _"
SENSOR
INPUT_T101_t'--
_T14T__ I-'-
T32 HEATING
_]_ OUTPUT
I--_ MIXED AiR
T35 DAMPER
I_ OLITPUT
FANSTA_.II
OA ENT_"
DISCRETE S_3
SWITCh{ FIRE SMOK
INPUTS LOWLIMI-- F2,?._
T37 HEATING
F24_'_
T38 ENABLE
_"_ COOLING COMMON
_.___.T ENABLE GND T25_-_
K3 K2
HI/MED MED/LO K1
FAN SPEED FAN SPEED FAN ON/OFF
LEED- .......
•_W..HiJ_E ......
......
/3 CONDUCTOR
_" ...... 20AWG SHIELDED
SHIF.LD GABLE
Tl_
TI9 _-_
F20_"
T21_'_
RESISTOR
W/SSUPPLIED
ENSOR)
tUMIDITY SENSOR
LEGEND
ADJ -- Adjust
AQ -- Air Quatity
CCN -- Carrier Comfort Network_
COM -- Common
GND -- Ground
MAT -- Mixed-Air Temperature Sensor
OA EN'fl-I -- Outdoor-Air Enthalpy
OAT -- Outdoor-Air Temperature Sensor
NC -- Normally Closed
NO -- Norma_y Open
RAT -- Return-Air Temperature Sensor
S/S -- Start/Stop
SAT -- Supply-AirTemperature Sensor
SPT -- Space Temperature Sensor
RH -- Relative Humidity
Fig. 24 -- Wiring of Relative Humidity Sensor to Control Board
37
CHANGEOVER SWITCH (Factory-Instalhid Option) --
The changeover switch is used with 2-pipe changeover units to
determine if the temperature of the water in the water loop can
provide cooling or heating (Fig. 25). The switch provides this
input to the control. The changeover switch is factory-wired to
the control and ready for field mounting to the water piping.
The switch mounts to the water pipe using a spring-loaded
clamp.
It is primarily used for a stand-alone application, although
the changeover switch may be required for CCN applications if
the water temperature status is not available through the
network. For stand-alone applications, one switch is required
for each 2-pipe unit. If the units are connected together on a
3-wire CCN communication bus and a linkage thermostat
(or Unit Ventilator Comfort Control module [P/N 110500]) is
used, then a single switch can be connected to any one unit and
the linkage thermostat can be configured to broadcast the
switch status to all other units.
IMPORTANT: The switch must be mounted on the
supply water pipe, where water flows continuously to
accurately sense the available water temperature. Never
mount the sensor on piping which is connected to a
2-way valve.
FILTER/SMOKE STATUS (CCN Systems Only) -- The
filter/smoke status is monitored by the control module and
contains an adjustable alarm limit. The control accumulates
fan-operating hours; when the total hours exceed the limit, an
alarm is generated.
The alarm limit is adjustable from 100 to 9900 hours. It is
factory preset to 1500 opumting hours. The limit is normally
field adjusted and is dependent on the fdter media used as well
as the quality and amount of outdoor air required. The normal
range is from 400 to 1500 hours.
Carrier Comfort Networke Interface --The Carrier
Comfort Network (CCN) communication bus wiring is
supplied and installed by the electrical contractor. It consists of
shielded, 3-conductor cable with drain wire.
The system elements am connected to the communication
bus in a daisy-chain arrangement. The positive pin of each
system element communication connector must be wired to the
positive pins of the system element on either side of it; the
negative pins must be wired to the negative pins; the signal
ground pins must be wired to signal ground pins. See Fig. 26
for location of the CCN communication connector (NET-
WORK) on the control module.
NOTE: Conductors and drain wire must be 20 AWG mini-
mum, stranded tinned copper. Individual conductors must be
insulated with PVC, PVCh_ylon, vinyl, Teflon, or polyethyl-
ene. An aluminorrdpolyester 100% foil shield and an outer
jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a
minimum operating temperature range of -20 C tu 60 C is
required. See Table 14 for cables that meet the requirements.
When connecting the CCN communication bus to a system
element; a color code system for the entire network is recom-
mended to simplify installation and checkout. The following
color code is recommended:
CCN BUS
SIGNAL CONDUCTOR CCN
TYPE INSULATION CONNECTOR
COLOR
+ RED 1
Ground WHITE 2
BLACK 3
Fig. 25 -- Changeover Switch
RJ-14
SERVICE -'-'-'-q
JACK
CCN
CONNECTOR
m
POWER
[] SERVICE
-i_l iNETWORK
Fig. 26 -- CCN Communication Connector
If acable with a different color scheme is selected, a similar
color code should be adopted for the entire network.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to ground at only one point. See Fig. 27. If
the communication bus cable exits from one building and en-
ters another, the shields must be connected to ground at the
lightning suppressor in each building where the cable enters or
exits the building (one point only).
To connect the control to the network, proceed as follows
(Fig. 27):
1. Tuna power to the control box OFF.
2. Remove the CCN connector from the control board.
3. Cut the CCN wire and strip the ends of the RED,
WHITE, and BLACK conductors.
4. Using a wire nut, connect the 2 drain wires together.
5. Insert and secure the 2 RED wires to terminal 1 of the
CCN connector.
6. Insert and secure the 2 WHITE wires to terminal 2 of the
CCN connector.
7. Insert and secure the 2 BLACK wires to terminal 3 of the
CCN connector.
8. Replace connector on control board.
9. Turn on power to control box.
38
---GROUND
DRAIN WIRE
BLACK
WHITE @
RED
*
CON TOR
DRAIN WIRE /_ DRAIN WIRE
BLACK BLACK
WHITE _WHITE
RED RED
co. OR
UNIT VENTILATOR UNIT VENTILATOR UNIT VENTILATOR
1000 FT MAXIMUM
LEGEND
CCN -- Carrier Comfort Network
Fig. 27 -- CCN Communication Wiring
UNIT VENTILATOR
Relays -- The fan relays am an integral component of the
control board. The fan motor speed control uses three SPDT
relays. The control relays am shown in Fig. 24. See the funow-
ing sections for a description of how the control relay is used
with each function.
FAN RELAY -- The fan relay (K1) is factory-wired and
factory-installed on all units. The relay interfaces with the
Electronically Commutated Motor (ECM) motor control
circuit and automatically starts and stops the fan.
FAN SPEED RELAYS -- The fan speed relays, I(2 and K3,
select the operating speed of the fan (High/Medium/Low). The
fan speed relays am factory-wired and factory-installed. These
relays control the speed of the motor.
Actuators
MODULATING OUTDOOR-AIR DAMPER ACTUATOR
(Fig. 28)--The outdoor-air damper actuator is factory-
supplied and factory-installed directly on the damper jackshaft.
All wiring between the actuator and the control is provided by
the factory. The actuator is mounted so that the spring return
will close the outdoor-air damper and open the return-air
damper on loss of power.
The actuator consists of an electronically controlled revers-
ible motor equipped with a microprocessor drive. The damper
actuator is supplied with approximately 8 ft of plenum rated
cable.
The actuator is capable of holding its position at any point in
the stroke and moving the damper in either direction.
The actuator is powered by the fused 24 vac transformer
located in the control box.
FACE AND BYPASS DAMPER ACTUATOR (Fig. 29) --
The actuator provides 35 in.-lb torque rating and is powered by
the 24-vac transformer located in the control box.
Face and bypass dampers am factory-supplied and factory-
installed on all face and bypass damper applications. These
actuators am proportional modulating, direct shaft mount type,
capable of being driven in either direction and holding position
at any point in the travel range.
The actuators are supplied with plenum rated cable.
Actuator connections depend on the application. Refer
to Application Data manual and wire label diagram for wiring
information.
The actuator is equipped with a SPDT damper end switch,
which senses when the damper is in the full bypass position.
The switch position is adjusted so that the switch closes
when the damper moves about 5degrees from the full bypass
position.
FIELD-SUPPLIED TWO-POSITION RELIEF DAMP-
ER- A field-supplied relay is required m wire a field-
supplied two-position damper or ventilation unit, such as a heat
recovery ventilator (HRV) or energy recovery ventilator (ERV)
to the control module. A SPST normally open relay, such as
HB61KK324, must be field-installed and wired for use with
the field-supplied damper actuator or ventilation unit.
Using 18 AWG twisted cable, connect the relay coil con-
tacts to the control terminals J1-2 and T34. See Fig. 24 and 30.
To connect a field-supplied two-position damper actuator,
(Fig. 30), connect one contact of the actuator to the normally
open contact of the relay. Connect the common contact of the
relay to one leg of the power source. Connect the other contact
of the actuator to the outer leg of the power source.
39
24VA_CS_,SOHz
SVA 2_J
Co.tml
Fig. 28 -- Modulating Outdoor-Air Damper
Actuator (Part No. HF23BJ040)
HF23BJ039
$2_ $2_1 3_ in4b {4 Nm)
g3 N3 _ .111_s _
3VA _ LA_21_
2U
Fig. 29 -- Face and Bypass Damper
Actuator (Part No. HF23BJ039)
FIELD-SUPPLIED r- -
DAMPER HRV OR
ERV
I
I
I
(HN61 KK324 RELAY SHOWN)
SEPARATE ISOLATED
POWER SOURCE
(24, 120, OR 240 VAC.)
[
(BLK) _--] J1
(RED)
_'_ CONTROLBOARD
ITERMINAL
LEGEND
ERV -- Ener Recovery Ventilator
HRV Heat_ecovery Ventilator
Field Wiring
Fig. 30 -- Two-Position Minimum Outdoor-Air Damper Relay
4O
Direct Expansion (DX) Cooling -- The Unit Venti-
lator Comfort Control module is designed to provide up to
2 stages of capacity control for direct expansion (DX) cooling
applications. The control can be interfaced with condensing
units, unloader solenoid valve, hot gas bypass valves, and liq-
uid line solenoid valves. In these applications, the stages of DX
capacity are controlled to maintain the space temperature at the
cooling set point. Typically, compressor stages and liquid line
solenoid valves operate normally open, while unloaders and
hot gas bypass valves operate normally dosed (see Fig. 31).
The Unit Ventilator Comfort Control module provides a
SPDT relay contact for the first stage of DX cooling. These
contacts are designed to switch up to 1 ampere of power (24 to
277 vac at 60 Hz).
Each DX output is configured to provide a minimum off
time of 5 minutes after being deenergized. This Time Guard
control feature allows the refrigerant pressures to equalize after
a compressor shutdown, thereby protecting compressors from
damage caused by starting with excessive loads. The "time
Guard control can be disabled if the stage is used to control a
solenoid valve or unloader.
OUTDOOR-AIR TEMPERATURE (OAT) LOCKOUT --
An outdoor-air temperature lockout is provided to disable all
DX cooling. The control compares the outdoor-air temperature
to the user-adjustable DX outdoor air lockout set point.
Whenever the OAT drops below die set point, all stages of DX
cooling are disabled.
The outdoor-air lockout feature is used to ensure the
condensing unit does not operate below its designed minimum
outdoor temperature.
DX System Design -- Recommendations for basic DX
system design and piping should always be followed and are
available in the Carrier System Design manual.
The Unit Ventilator Comfort Control module maintains the
space temperature at the cooling set point by operating the DX
stages as the space load requires. Configuration requirements
for systems using DX components vary according to the
system design.
IMPORTANT: Never oversize die condensing unit. ]
I
m
For units equipped with CCN controls, condensing units
should be sized for medium speed airflow unless a hot gas
bypass valve or two-stage condenser is supplied.
Several staging control examples for typical DX applica-
tions are shown in Examples 1-3. Use a service configuration
tool to configure the number of stages and the logic type and
'l]rne Guard control features. See Set-Up, Configuration and
Operation section on page 46 for further configuration details.
Example I -- Single-Stage Single Condensing Unit
STAGE STAGE LOGIC TIME GUARD
NUMBER TYPE TYPE FUNCTION
1 Compressor Normal Enabled
2 Hot Gas Inverted Disabled
Example 2 -- Two-Stage Single Condensing Unit
STAGE STAGE LOGIC TIME GUARD
NUMBER TYPE TYPE FUNCTION
1Compressor Normal Enabled
Electric Inverted Disabled
2 Unloaderno.1"
*Optional, basedonthesystem designorhotgas bypass.
Example 3 -- Condensing Unit with
Two-Speed Compressor
STAGE
NUMBER
1
2
STAGE LOGIC
TYPE TYPE
Compressor Normal
or Low Speed
Compressor Normal
or Hi_ihSpeed
TIME GUARD
FUNCTION
Enabled
Enabled
The preceding examples are typical; however, staging for
each system is unique. Staging is for capacity control only and
does not eliminate any components required for safety or by
recommended system design. Follow equipment application
and installation instructions for sizing, location of electrical
connections, and required components such as liquid-line
solenoid valves used for refrigerant isolation, and thermostatic
expansion valves.
NORMALLY OPEN CONTACT TERMINALS
5
CLOSED
CONTACT
TERMINALS
COIL TERMINALS
RELAY CONTACT RATINGS
48vaat 24vac 0.25 pewer factor I
125 va at 115 vac 0.25 power factor
230 va at 230 vac 0.25 power factor
Fig. 31 -- DX Control Relay (Part No. HN61KK324)
41
Electric Heat -- Two control relays am factory-supplied,
factory-instal]e.d and factory-wired to provide staging control
for electric heater applications. They am used to operate the
electric heater elements in two stages. The relays are installed
inside the electric heat control compartment. The heater circuit
connections depend upon the actual number of heater elements
provided. The Unit Ventilator Comfort Control module pro-
rides two stage electric heat control capability unless only one
element is provided.
The control operates the heater stages as required, but pre-
vents the discharge air temperature from exceeding 140 F at
any time.
The first stage is wired so that it operates between 33 to
50 percent of the total heater capacity. Refer to Table 16 for
heater element circuit connections.
Remote Start -- The remote start input is used to switch
the control operating mode from the unoccupied to the occu-
pied state by means of a contact closure from an external con-
trol system or an electro-mechanical time clock device. The
control device must provide an isolated single-pole contact.
Whenever the contact is closed and 24 vac is present on T20,
the control will operate in the Occupied mode.
Using 18 or 20 AWG wire, connect the remote start termi-
nal (T20) to one side of the remote contact. Connect the other
side of the contact to TB.
If a solid-state contact is provided by the control device,
then a field-supplied and field-installed load resistor may be
necessary to ensure reliable operation of the input. To ensure
proper operation, use a digital volt meter (DVM) and measure
the AC voltage between T20 and T25 with the external contact
in the OFF or open position.
The input will operate properly if the AC voltage is less than
1vac, otherwise a load resistor must be connected across termi-
nals T20 (remote start input) and T25 (ground). Typically, a
single 1000 ohm, 2 watX resistor will reduce the voltage suffi-
ciendy for most sohd-state contacts. If not, add additional resis-
tors, one at a time, until the voltage measured is below 1 vac.
Because the resistors heat when operating, die devices should
be permanently mounted to a field-supplied terminal strip and
20 AWG wire rated for at least 90 C should be used to connect
the resistor(s) to contrul terminals q'20 and T25.
Fire/Smoke Status Input -- The Fire/Smoke Status
Input is used to identify that a fan has stopped its normal opera-
tion due to an alarm condition at a local fire or smoke detector.
This input must be used in conjunction with a normally closed
contact which is wired into the fan motor control circuit.
A double-pole double-throw (DPDT) relay, part number
HN61 KK324, is recommended. One set of the relay contacts is
wired into the fan motor circuit and the other set is wired to the
control inpuL The control box provides 24 vac power for the
relay. The relay is controlled by a separate isolated contact set
from the smoke or fire detector.
All wiring from the detector should be appropriately rated
for the application and must comply with NEC, NFPA (Nation-
al Fire Protection Association) and any local codes.
SMOKEJFTRE DETECTOR WIRING (Normally Open
Contact Set) -- Perform the following procedure to wire the
smoke/fire detector:
1. Use 15 AWG wire rated for 600 vac for all wiring.
Eight 1&-in. insulated female quick-connect type lugs
are required.
2. Connect a wire from TB to one of the detector contact
terminals.
3. Connect the other detector contact terminal to the relay
coil terminal no. 1.
4. Connect die other coil terminal, no. 3, to ground in the
control box.
5. Connect the normally closed contact set (relay termi-
nals no. 5 and no. 6) to the fan motor wiring as shown
on the label diagram.
6. Connect one of the normally open relay contacts, ter-
minal no. 2, to TB (24 vac).
7. Connect the other side of the contact, terminal no. 4, to
T21 on the control module.
SMOKE/FIRE DETECTOR WIRING (Normally Closed
Contact Set) -- Perform the following procedure to wire the
smoke/fire detector:
1. Use 15 AWG wire rated for 600 vac for all wiring.
Eight lk-in, insulated female quick-connect type lugs
are required.
2. Connect a wire from TB to one of the detector contact
terminals.
3.
4.
Connect the other detector contact terminal to the relay
coil terminal no. 1.
Connect the other coil terminal, no. 3, to ground in the
control box.
5. Connect the normally open contact set (relay terminals
no. 2 and no. 4) to the fan motor wiring as shown on
the label diagram.
6. Connect one of the normally closed relay contacts, ter-
minal no. 5, to TB (24 vac).
7. Connect the other side of the contacL terminal no. 6, to
T21 on the control board.
TOTAL NO.
OF HEATER
CIRCUITS
3
4
5
6
Table 16- Heater Element Wiring
NO. OF CIRCUITS
CONTROLLED
BY STAGE 1
1
2
2
2
STAGE 1
CAPACITY _'/o)
33
50
40
33
NO. OF CIRCUITS
CONTROLLED
BY STAGE 2
2
2
3
4
STAGE 2
CAPACITY(%)
67
50
60
67
42
Valves
WATER VALVES--Water valve assembfies are shipped
with the unit for field installation. All factory-suppfied valves
are fully modulating and capable of being positioned at any
point within the travel range of the valve. Each valve is
shipped complete with an actuator and any required linkage.
The equal percentage characteristics of the modulating
valves provide close temperature control on heating, cooling or
reheat unit ventilator coils.
In case of power failure, a return spring sends the valve to
its normal position. The normal position is defined for each
control sequence.
Water Valve Actuators -- Water valve actuators are factory-
mounted on factory-supplied valve assemblies. The valve and
actuator assemblies are modulating spring retom for all water
and steam applications. Valves am factory supplied.
All valves use actuators with reversible electric motors. The
control provides proportional control to the electric motor
which receives a tri-state signal from the control
All valves have a spring retain feature that allows them to
retorn to a normal positions (normally closed) upon loss of
power.
All valve assemblies have electrically powered actuators.
Each actuator is factory-wired and operates its valve through a
linear stroke.
Each water valve actuator features a magnetic clutch to ex-
tend the life of the motor and gear train. A manual override le-
ver and position indicator facilitates field setup.
To prevent electric shock and equipment damage, discon-
nect the power to the control before performing any work
on valve assemblies.
On chilled water or hot water applications, the valve actua-
tors can be mounted in any position above the center line of the
valve body. For steam applications, mount the actuator above
the centerline of the valve body and at least 45 degrees from
veltiCal. This position prevents exposing the actuator to ex-
treme heat. Refer to Fig. 32.
The manual positioning lever on all water valves should
only be used when controller power is OFF. DO NOT
attempt to move this lever when controller power is
applied. If the position lever does not move freely for man-
ual positioning when the power is off, remove the valve
cover and push the solenoid plunger down using a small
screwdriver inserted in the slot below the solenoid.
DO NOT install valve assembly where excessive moisture,
corrosive fumes, and/or vibration am present.
INSTALL all 2-way valve assemblies so that they close
against system flow. Proper flow direction is from inlet
"BPort" to outlet "APort'.
ALWAYS install 3-way mixing valve with 2 inlet flows
and one outlet. Proper flow direction is: inlet "B Port' to
coil. Inlet 'A Port" to supply. "Common Port' to return. See
Fig. 33.
Water Valve Wiring- Valve wiring is determined by the
actual valve selected and the control sequence.
All valves are factory-wired to the control module and
tested.
Water valve specifications and dimensions are found in
Table 17 and Fig. 34.
DO NOT MOUNT
VALVE HERE 45 °MINIMUM/
VERTICAL 90 _MAXIMUM
FROM VERTICAL
Fig. 32 -- Valve Mounting Angle for
Steam Heating Applications
Table 17 -- Water Valve Specifications
FEATURE
Application
FluidTemperature I Minimum
IMaximum
Flow Type
Static PressureLimits
Current Requirement (24 V Supply)
J Body
Stem
Material Seat
Plug
Actuator
MaximumAmbientTemperatureand Humidity
Voltage
Actuator Power
Connections
Weight
SPECIFICATION
Hot or Chilled Water, up to 50% Glycol
_2F (0° C)
200 F (93 C)
Equal % Service Port Linear Bypass (3-way only)
300 psi (20.7 bar)
12 VA (in rush), 100 mA Continuous
Forged Brass
Chrome-Plated Brass
Stainless Steel
High Temperature Thermoplastic
Stainless Steel Base, Aluminum Cover
125 F (52 C) 95% Non-Condensing
24 vac -- 15%, +t 0%
50/60 Hz
12 VA inrush at 24 vac
2.5 VA holding
Screw Terminals
3.0 Ib(1360 Q)
43
WATER
COIL
<
c
3-WAY VALVE
WATER
COIL A • RETURN
J[ SUPPLY
2-WAY VALVE
Fig. 33 -- Typical Piping for Spring Return
2-Way and 3-Way Mixing Valves
(6O)
,.d;
If
+..-÷_
o_ oF
")18 _1-:
(2e) (ss)
4-3/6
(111)
3-3/4_
1-I . (99)
(221
"-7
(98)
NOTE: Dimensions are ininches (mm).
Fig. 34 -- Water Valve Dimensions
(Modulating Type)
1-3/4 (34)
_'WAY
The valve type is identified by the first digit of the two-digit
control code number. In Table 18, the water valve type is
shown for each unit depending on coil capacity.
For pressure drops other than those tested, see Table 19. See
Tables 20 and 21 for close-off pressure.
Table 18 -- Factory-Supplied Water Valves
CONTROL SEQUENCE
2A/3A
2B/3B
2D/3D
2Fi3F
2G/3G
2J/3J
2K/3K
2M/3M
20/30
21/31
22/32
23/33
24/34
25/35
LEGEND
APPLICATION
Chilled/Hot Water (Modulating Valve) Control
Chilled Water Cooling, Hot Water
or Steam Heating
Chilled Water Cooling, Electric Heat
Hot Water or Steam Heatin9 Only
Hot Water or Steam Heating, DX Cooling
Chilled Water Cooling Only
Face and Bypass Chilled Water Cooling
with Valve Control Heating
Face and B pass Chilled Water Cooling
withValve _oPntrol Reheat
Chilled Water/Hot Water Using Face
and Bypass Damper Control
Chilled Water Cooling. Hot Water or
Steam Heating
Chilled Water Cooling. Electric Heat
Hot Water or Steam Heating. DX Cooling
Hot Water or Steam Heating Only
Chilled Water Cooling Only
VALVE APPLICATION
Chilled Water/
Hot Water
Chilled Water
Hot Water/Steam
Chilled Water
Hot Water/steam
Hot Water/steam
Chilled Water
Chilled Water
Reheat
Chilled Water
Reheat
Preheat
Chilled Water/
Hot Water
Chilled Water
Hot Water/Steam
Chilled Water
Hot Water/Steam
Hot Water/Steam
Chilled Water
NORMAL POSITION
Open
Closed
Open
Open
Open
Open
Open
Closed
Open
Closed
Closed
Open
Open
Closed
Open
Open
Open
Open
Open
DX -- Direct Expansion
44
Table 19 -- Valve and Coil Pressure Drops vs Flow
UNIT
SIZE COIL VALVE
(NOMINAL ROWS SUPPLIED
CFM) (Cv)
1" 2,5
2* 2.5
500 3 2.5
42.5
5 2.5
1" 2.5
2* 2,5
750 3 2.5
4 2,5
52.5
1" 2.5
2* 2.5
1000 3 4.0
4 4.0
5 4.0
1" 2.5
2* 2,5
1250 3 4,0
4 4,0
5 4.0
1" 2.5
2* 2.5
1500 3 4.0
4 4.0
5 4,0
1" 2.5
2* 2,5
2000 3 4.8
4 4.0
5 4.0
LEGEND
Cv -- Coefficient of Volume
*Hot water only.
TYPICAL VALVE
AND COIL
PRESSURE DROP
psi gpm
3.1 4
3.3 4
3,3 4
3,3 4
3.3 4
3,1 4
3,5 4
3.3 4
3.3 4
3,3 4
3,6 4
3.5 4
4 6
4 6
4 6
3,6 4
3,5 4
6.7 8
6.7 8
6,7 8
3.6 4
3,8 4
10.8 10
10.8 10
10.8 10
3.6 4
3.8 4
10.8 10
10.8 10
10.8 10
desired gpm flow )2
NOTE: Desired Pressure Drop = (-
Table 20 -- 2-Way Water Valve Specifications
and Ratings
FLOW CLOSE-OFF
APPLICATION COEFFICIENT NORMAL
VOLUME PRESSURE
Cv PSi POSITION
1.3 35 OPEN
Steam 2.2 35 OPEN
4.4 35 OPEN
Rot/Chilled Water 2.5 50 OPEN
4.0 35 OPEN
Chilled Water 2.5 50 CLOSED
Only 4.0 35 CLOSED
LEGEND
Cv -- Coefficient of Volume
Table 21 -- 3-Way Water Valve
Specifications and Ratings
FLOW
APPPLICATION COEFFICIENT CLOSE-OFF NORMAL
VOLUME PRESSURE POSITION
Cv PSI (COIL)
Not/Chilled 2.5 50 OPEN
Water 4.0 35 OPEN
Chitled Water 2.5 50 CLOSED
Only 4.0 35 CLOSED
LEGEND
Cv -- Coefficient of Volume
2-WAY STEAM VALVES--All steam valves utilize an
electrically driven hydraulic actuator which provides a full
modulating capability and a return feature. Each steam valve is
factory_,,quipped with a spring linkage extension to prevent
any actuator damage due to high steam temperatures. Steam
valve specifications and dimensions are found in Table 22 and
Fig. 35.
Table 22 -- 2-Way Valve Specifications
Application
Fluid Temperature
Steam Pressure Limits
Flow Type
Material
Valve Connections
Maximum
Maximum inlet
Differential
Body
Stem
Seat
Plug
Pacldng
Disc
Maximum Ambient Temperature
Voltage
Actuator Power
Connections
Weight
Steam
281 F(138 C)
35 psi (241 kPa)
20 psi (138 kPa)
Equal%
Bronze
Stainless Steel
Bronze
Brass
Spring Loaded Teflon
Composition
Female, Union Sweat
s/s in. ID (1/2 in. Nominal Copper) Tube
140 F (60 C)
24 Vac -15%, +10% 50/60 Hz
22 VA at 24 vac
Wire Leads
6.0 Ib (3057 g)
NOTE: Avoid condensation which can facilitate corrosion. With 40 F (4 C) water, the maxi-
mum allowable ambient dew point temperature is 68 F (20 C). Piping insulation must not
stop drainage at actuator mounting nut. Do not use hydraulic actuators with fluid tempera-
tures below 40 F (4 C).
45
_3-1/4-_)
"9-25/32
FLOW
6-3/4
<11 IN 'A'
*Includes 21/32-in.(52 mm) for linkage extension.
NOTES:
1. Allow 3 in. clearance above actuator for removal. Mount actua-
tors above the valve body at 45-degrees from vertP.al. Refer to
Fi9. 32.
2. Dimensions are in inches.
Fig. 35 -- Valve Dimensions
SET-UP, CONFIGURATION, AND
OPERATION
The Unit Ventilator Comfort Control module (P/N 110500)
is designed to be installed using the CCN Network Service
Tool, or a CCN Building Management system such as Building
Supervisor, ComfortVIEW TM or ComfortWORKS® software.
The control provides several comprehensive screens for easy
set-up and configuration of the control. See Tables 23-29. Two
additional screens display the operation of the equipment.
Each unit is factory-configured for the control sequence or-
dered. Only set points, schedules, alarm limits, and user op-
tions need to be adjusted. Tables 23-29 depict the screens that
provide a fist of the information contained within each func-
tion, the expected range of values for each parameter, and the
allowable force limits or configuration range. For specific in-
formation about Network Service Tool, Building Supervisor,
ComfortVIEW, or ComfortWORKS software refer to the oper-
ating instructions for each specific piece of software.
The Service Configuration screens are used to specify the
equipment model and control sequence being used, such as the
type of heating or cooling used (chilled water, DX cooling,
steam, or hot water) and the damper control type (ASHRAE
Cycle I, II or III). These values am factouc-configured for the
control sequence as ordered. A separate configuration screen is
used to modify the factory pre-eonfigured alarm set points, if
required, in order to meet a specific customer requirement.
The service configuration screens are located under the
Diagnostic/Service Configuration function. See Table 24.
Alarm configurations am shown in Table 25.
The Modify controller screen allows the installer to select
from a list of standard control options which can be used for
specific applications. Standard control options include Space
Temperature Set Point adjusUnent with an adjustable maxi-
mum limit, the ability to provide dehumidification with or
without reheat, override duration, unoccupied free cooling, or
warm up temperature check, and other control features.
The control configuration screens are located under the
CCN Configuration function. See Table 27.
The Set Point screen is used to configure the desired control
set points for the specific application. These set points include
the occupied heating and coohng set points, the unoccupied
heating and cooling set points, the ventilation airflow set point,
the IAQ set point (optional) and the ASHRAE Cycle I]1 Damp-
er set point (for Cycle 111control). The Set Point screen is locat-
ed under the Modify/Set Points function. See Table 28.
The Points/Display screen is used to monitor equipment
operation and provides a simple overview including: the oper-
ating mode, heating and cooling capacity, ventilation airflow
value, equipment and sensor alarms, and a list of actual sensor
and output values. The Status Display screen is located under
the Points/_splay function. See Table 26.
The Maintenance screen provides an indication of the
control algorithm operation and a view of each individual con-
trol loop as it is currently functioning. The Maintenance
screens am located under the Diagnostic/Maintenance func-
tion. See Table 29. The Linkage Maintenance screens am locat-
ed under the Diagnostic/Maintenance function. See Table 29.
The Maintenance screen provides an indication of the informa-
tion the Unit Ventilator Comfort Control module has received
from the linkage thermostat (if supplied).
Act -- Actual
AQ -- AirQuality
ASCII -- AmericanStandardCode
for Information
Interchange
ASHRAE -- AmericanSocietyof
Heating,Refdgeration
andAirConditioning
Engineers
CCN -- CarrierComfortNetwork_
Gig 1 Configured
Cntrl -- Control
CV -- ConstantVolume
DI -- DiscreteInput
DX -- DirectExpansion
Ele -- Element
Hi Lira -- HighLimit
LEGEND (For Tables 23-29)
Hys -- Hystersis
Kd -- DerivativeConstant
Ki -- IntegralConstant
Kp -- ProportionalConstant
LoLim -- LowLimit
MAD -- Mixod-AirDamper
MAT -- MixedAirTemperature
Sensor
Med -- Medium
min -- minute
Norm -- Normal
Nr -- Number
OAT -- Outdoor-AirTemperature
Sensor
Oc/Occ -- Occupied
PID -- Proportional/Integral/
Derivative
Pos -- Position
RH -- Relative Humidity
Schd -- Schedule
SP/Setpt -- Setpoint
Stg -- Stage
Sup BIk #-- Supervisory Block
Number
Sup Bus -- Supervisory Bus
Number
Sup Ele -- Supervisory Element
Number
Temp/Tmp -- Temperature
Tim Gard 1Time Guard
Tmd Ovr -- Timed Override
Tmd Ovr Hrs -- Timed Override Hours
Unoc -- Unoccupied
46
Table 23 -- CCN Device Configuration
SOFTWARE
DEVICE NAME DESCRIPTION LOCATION PART NUMBER
Comfort
40UV/UH System Unit CESR-131191-02
Ventilator
NOTE: The device name, description, and location fields can be modified by the
BuildingSupervisor or ComfortWORKS_ software.
Table 24 -- Service Configuration
DESCRIPTION
2 Pipe Changeover
ASHRAE Cycle Fan Control
#Fan Speeds (1-3)
Unit SLze
% Air Flow Med
% Air Flow Low
Fan PID
Kp
Ki
Kd
Starting Value
CoolingType CV Cooling
Kp
Ki
Kd
Starting Value
Staged Cooling Nr of Stages
Stg 1 Tim Gard
Stg 2 Tim Gard
Stage 1 Logic Type
Sta e2L icType
_eating°_,pe
Heating
Kp
Ki
Kd
Starting Value
Fan Off Value
Staged Heating Nr of Stages
Stg 1 Tim Gard
Stg 2 Tim Gard
Stage 1 Lo ic Type
Damperg_ype
CV Mixed Air Damper
Kp
Ki
Kd
Starting Value
Air Quality
Kp
Ki
Max AQ Output
AQ Low Voltage
AQ High Voltage
AQ Low Reference (PPM)
AQ High Reference (PPM)
Filter Timer hrs * 100
Space Temp Trim
MAT Sensor Trim
OAT Sensor Trim
POINT NAME
UNITTYPE
CYCLE
FAN TYPE
UNI]'SIZE
AFMED
AFLOW
KP
KI
KD
STARTVAL
COOL_TYP
KP
KI
KD
STARTVAL
STAGES
TGf
TG2
CLT1
CLT2
HEAT TYp
KP
KI
KD
STARTVAL
HCFOV
STAGES
TG1
TG2
HLT1
MiXD
KP
KI
KD
STARTVAL
KP
KI
AQMDP
Volts
AQINHI
AQLO
AQHI
FIL TIMR
RATTRIM
MATTRIM
OATrRIM
STATUS IUNITS
Disable/Enable
X
X
xxxx CFM
%
%
XX.X
X.X
XX.X
xx.x %
x
XX.X
x,x
xx,x
XX.X °F
x
Disabie_nable
Disable/Enable
Norm]Inert
Norm/Invert
X
XX.X
X.X
XX.X
XX.X °F
:OLX °F
X
Disable/Enable
Disable/Enable
Norm/Invert
x
XX.X
X.X
XX.X
XX.X °F
XX.XX
XX.XX
xxx.x %
xx.x Volts
xx.x Volts
XXXX
XXXX
xx
_.X ^F
X3(.X ^F
xx.x ^F
RANGE
0-1"
1-3t
1 - 3t
100-5000
30-100
20-100
0.0 - 40.0
0.0 - 10.0
0.0 -20.0
0.0 -100.0
o- 3t
O.O- 40.0
0.0 -10.0
0.0 - 2O.O
40.0 - 903
1-2
0-1"
0-1"
0-1
0-1"
0 - 3/
0.0 -40.0
O,0 -10,0
0.0 -20.0
40.0 -90,0
35.0 -70,0
1-2
0-1"
0-1"
0-1"
0-2
0.0 - 40.0
0.0- 10,0
0.0 - 20.0
40.0 -90.0
0- 1.0
0- 1.0
0.0 - 100.0
0.0 -10.0
0.O -10.0
O.0-5000.0
0.0 - 5000.0
0 - 99
-5.0 -5.0
-5.0 - 5.0
-5.0 - 5.0
DEFAULT
Disable
2
3
1000
8O
7O
10.0
3.0
O.0
0.0
0
8.0
0.3
0.O
65.0
1
Enable
Enable
Normal
Normal
0
8.0
0.3
03
80.0
55.0
1
Enable
Enable
Normal
1
8.0
0.3
0.0
60.0
0.1
0.03
85.0
2.0
10,0
0.0
2000.0
12
0.0
0.0
0.0
*O = Disable or Normal
1= Enable or Inverted 1"0 = None
1= Modulating
2= Two Position
3 -- If applicable, Direct Expansion (DX) for Cooling Type. Electric
Heating for Heating Type.
47
Table 25 -- Alarm Service Configuration
DESCRIPTION
Alarm Routin Control
Realarm _-ime
Cntrl Temp Hys
Supply Air Temperature
Lo Lim
Hi Lira
Mixed Air Temperature
Lo Lira
Hi Lira
Relative Humidity
LOLim
Hi Lim
Outdoor Air CFM
Lo Lim
Hi Lira
Air Quality
Lo Lim
Hi Lim
Outdoor Air Temperature
Lo Lim
Hi Lim
*0 = Disable
1 = Enable.
1-255 disables realarming.
POINT NAME
ALRMCNT
REALARM
SPTHYS
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
LOWLIM
HIGHLIM
LOWLIM
HIGHUM
LOWLIM
HIGHLIM
STATUS /UNITS
xxxxxxxx
xxx
XX.X
XXX,X
XXX.X
XXX.X
XXX.X
XXX.X
XXX.X
XXXX.X
XXXX.X
XXXX.X
)O(XX.X
XXX.X
XXX.X
RANGE
0-1"
min 1-2551-
^F 1.0 -20.0
°F -40.0 - 245.0
°F -40.0 - 245.0
°F -40.0 -245.0
°F -40.0 - 245.0
%RH 0.0 -100.0
%RH 0.0 -100.0
CFM 0.0 -5000.0
CFM 5000 -5000
0.0 -5000.0
0.0 - 5000.0
°F -40.0 - 245.0
aF -40.0 - 245.0
DEFAULT
11010000
255
5.0
45.0
150.0
40.0
120.0
30.0
70.0
0.0
800.0
0.0
800.0
40.0
140.0
NOTE: Alarm retry time (in the event an alarm is not acknowledged)
is fixed at 5 minutes.
Table 26 -- Status Display
DESCRIPTION
Desired Mode
Equipment Status
Controllin Temperature
Space LIg-emperature
Supply Air Temperature
Mixed Air Temperature
Outdoor-Air Temperature
Fan Relay
Fan Status
Remote Start
Outdoor Air Enthalpy
Cooling Capacity
Heating Capacity
Outdoor Air cfm
MAD Capacity 0.0 - 100.0
Filter Status
Air Quality (PPM)
Relative Humidity
Fire Shutdown
FS
Coil Freeze Detection
Changeover Switch Input
Spare Discrete Input
Spare Analog Input
Mixed Air Damper 1
Mixed Air Damper 2
Cooling 1
Cooling 2
Heating 1
Heating 2
Heating Enable Output
Cooling Enable Output
POINT NAME
MODE
ALARM
SPT
RAT
SAT
MAT
OATEMP
SF
FANSTAT
REMOTE
ENT
CCAP
HCAP
OACFM
MIXDCAP
FLTSTAT
AQ
RH
CFD
STATUS/UNWS
x:OOO_X
Norm/Alarm
X_OK.X
XXX.X
XXX.X
X)O(.X
XXX.X
Oft/On
XX)O(XX
Off/On
High/Low
)OC(.X
XXX.X
)C<XX.X
XXX.Z
Clean/Ditty
XXXX.X
XXX.X
Norm/Alarm
Fire shutdown
Norm/Alarm
CHANGOVR
DI0
AI0
MIXD1
MIXD2
CCV1
CCV2
HCV1
HCV2
HEATING
COOLING
Heat/Cool
Oft/On
XX,X
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Oft/On
*The text used for Mode shall be one of the following:
Off, Occ Cool, Occ Heat, Fan Only, UnocCool, UnocHeat, Warm-Up, Free Cool.
TThe text used for Fan Status shall be one of the following:
Off, Low, Medium, High.
**0 = Off, High, or Clean 1 = On, Low, or Dirty.
NOTE: The presence of override limits indicates that the point is forcible, all others are read
only,
ASCII*
oF
°F
°F
oF
°F
ASCII1-
%
%
CFM
%
%RH
Vo}ts
OVERRIDE
LIMITS
-40.0 - 245.0
-40.0 - 245.0
-40.0 - 245.0
-40.0 -245,0
-40,0 - 245.0
0- 1"*
0-1-*
0-1"*
0.0 - 5000.0
0.0 - 100.0
0 - 1"*
0.0 - 5000.0
0.0 -100.0
0-1"*
0-1"*
0-1"*
0.0 - 10.0
0-1"*
0-1 _
0- 1"*
0-1 -
0-1 -
0-1 _
0-1"*
0-1"*
48
Table 27 -- CCN Configuration
DESCRIPTION
Warm-Up Temp Check
Unoccupied Fan Cycling
Unoccupied Free Cooling
Free CooliniqLock-out
DX Outdoor Air Lock-out
Max Offset Adjustment
Air Qua]ity Control
High Humidity Limit
Local RH Sensor
Reheat
Occ Schd
Tmd Ovr Hrs
Linkage Thermostat
Cool Strt Bias (mirddeg)
Heat Strt Bias (min/de_)
POINT
WARMENAB
FAN_CYCL
NTEN
NTLO
DXLO
LIMT
AQEN
HIHUM
RHSENS
REHEAT
OCCSCHED
TIMOVRID
KCOOL
KHEAT
STATUS IUNITS
Disable/Enable
Disable/Enable
Disable/Enable
xx.x °F
xxx.x °F
xx.x ^F
Disable/Enable
xxx.x %RH
No/Yes
Disable/Enable
Xx
x hours
Xx
xx
*0 = Disable or No 1 =Enable or Yes
"j-Valuebelow 65 (i.e., rain value/default) disables global occupancy from CCN.
xx
min
RANGE
0-1"
0-1"
0-1"
35 - 80
-40 - 65
0 - 20
0-1"
0 - 100
0-1"
0-1"
64 - 99t
0-4
O- 60
O- 60
DEFAULT
Enable
Disable
Enable
50.0
60.0
0.0
Disable
100.0
No
Disable
64
0
10
10
Table 28 -- Set Point Configuration
DESCRIPTION
Setpoint
Oc Heat SP
Oc Cool SP
Unoc Heat SP
Unoc Cool SP
Cycle lit Damper Setpt
Economizer Lock-Out Temp
Ventilation Setpoint
AQ Setpoiut (PPM)
POINT STATUS /UNITS
OHSP
OCSP
UHSP
UCSP
C3DSP
ELOSP
OASP
AQSP
XX.X
XX.X
XX.X
XX.X
)C(.X
XX.X
XXXX.X
XXXX.X
RANGE
°F 40 - 90
°F 45 - 99
°F 40 - 90
°F 45 - 99
°F 40 - 90
°F 40 - 90
CFM 100 - 5OO0
0 - 5000
DEFAULT
70.0
75.0
55.0
90.0
55.0
63.0
200.0
650.0
Table 29 -- Maintenance
DESCRIPTION
Occupied
Linkage in Effect
Tmd Ovr in Effect
Heat Master Reference
Heat Submaster Reference
Cool Master Reference
Cool Submaster Reference
MAD Master Reference
MAD Submaster Reference
Cfg MAD Min Position
Act MAD Min Position
Temperature Reset Value
Cooling in Effect
Heating in Effect
Reheat in Effect
AQ Control in Effect
AQ Calc Damper Pos
Fan Status DI
Fan Speed Relay 1
Fan Speed Relay 2
Linkage Thermostat Linkage Status
Sup Ele
Sup Bus
Sup BIk #
Avg Oc Heat SP
Avg Oc Cool SP
Avg Unoc Heat SP
Avg Unoc Cool SP
AvgZone Tmp
Avg Oc Zone Trap
Oc Stat
POINT
OCCSTAT
DAVCL
TIMOV*
HCMR
HCSR
CCMR
CCSR
MIXDMR
MIXDSR
MIXDMDP
DMPRMIN
RESET
COOLFLAG*
HEATFLAG*
REHTFLAG*
AQFLAG
MDPAQ*
FANDI
FANSPD1
FANSPD2
LINKSTAT*
SUPE-ADR*
SUPE-BUS*
BLOCKNUM*
OCLOSTPT*
OCHISTPT*
UNLOSTPT*
UNHISTPT*
AZT*
AOZT*
OCCSTAT*
STATUS /UNITS
No/Yes
NeiYes
No/Yes
xxx.x °F
XXX.X °F
XXX.X °F
xxx.x °F
xxx.x °F
XXX.X °F
Jc(x.x %
_<x.x %
xx.x ^F
No/Yes
NeiYes
NeiYes
No/Yes
)o(x.x %
Off/On
OfflOn
Off/On
x
xxx
xxx
x
_O(.X _F
XX.X °F
xx.x °F
xx.x °F
xx.x °F
xx.x °F
x
t0=off 1=On
NOTE: The presence of override limits indicates that the parameter is forcible;
all others are read only except those marked (*) which cannot be forced or read from CCN.
OVERRIDE LIMITS
35.0 to 140.0
40.0 to 150.0
48,0 to 120.0
0.0 to 100.0
0-1t
0-1t
49
START-UP
Start-up procedures vary depending on time of year (sum-
mer or winter) and building characteristics (new building/old
building, occupiedhmoccupied, etc.).
Start-up in the cooling mode requires proper care to avoid
condensation problems. Condensation forms on surfaces that
are colder than the dew point of the surrounding air. If a unit is
started and is piped with low-temperature chilled water in a
hot, humid atmosphere, condensation will form on many parts
of the unit. In order to avoid excessive condensation, higher
temperature water should initially be used (approximately 65 to
70 F). Also, the building should be as completely closed as
possible. Close the unit's outside-air dampers. Bathroom and
kitchen exhaust fans should be off.
As the building temperature drops, the chilled water temper-
ature can be gradually reduced until it reaches 50 E At this
point the outside-air damper can be opened to take in minimum
outside air. When the chilled water temperature is reduced to its
design point, the exhaust fans can be turned on.
SERVICE
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
Preventing Excessive Condensation on Unit --
Excessive condensationcan be causedby running chilled water
through a unit with the unit fan off. If fan cycling is used, a water
flow control valve should be installed to shut off the water when
the fan stops.
Other methods of control which avoid condensation prob-
lems are as follows:
1. If condensation is forming on the unit, verify the chilled
water valve is closing off tightly. Dirt or debris may pre-
vent the valve from closing completely.
2. Continuous fan operation with motorized chilled water
valve controlled by a thermostat.
3. Continuous fan operation with thermostat control to
switch fan from high to low speed (instead of off).
Check Drain -- Check drain pan, drain line, and trap at
start of each cooling season. Astandard type pipe cleaner for
3/4-in. ID pipe can be used to be sure pipe is clear of obstsuction
so that condensate is carried away. Check the drain line at filter
cleaning time during the cooling season. Be sure that debris has
not fallen into unit through supply air grille.
Fan Motor Bearings -- Standard motors are perma-
nent split capacitor, which are equipped with permanently
sealed and lubricated bearings. No lubrication is required
unless special motors have been supplied or unusual operating
conditions exist.
Fan Shaft Ball Bearing -- These mid and inboard
beatings are permanently sealed and lubricated. No additional
maintenance is required. The end bearings must be lubricated at
the start of each cooling and heating season. Add 5 to 10 drops
of SAE 20 or 30 non-detergent based oil to the bearing.
Clean Fan Wheel -- For access to fan assembly, remove
discharge grille (if supplied). If unit is connected to ductwork,
remove front (40UV) or bottom (40UH) panel, separate fan
shaft from motor at bushing, remove motor, and slide fan
assembly from track. Use a stiff brush or vacuum to remove
dirt and debris from scroll. Wipe all fan surfaces with a damp
cloth. Reassemble as necessary.
Clean or Replace Air Filters -- At the start of each
cooling season and after each month of operation (more or less
depending on operating conditions), replace throwaway filter
or clean permanent filter.
THROWAWAY FILTER -- Replace filter with a good quality
filter of the correct size. Do not attempt to clean and reuse
disposable filters. See Table 1 for filter sizes.
PERMANENT FILTER (Fiber Type)
1. Tap on solid surface to dislodge heavy particles.
2. Wash in hot water. If needed, use mild solution of com-
mercial solvent such as sal soda or trisodium phosphate.
3. Set filter on end so that water drains out through slots in
frame. Allow filter to dry thoroughly.
4. Recharge filter with recharging oil. Three ounces is suffi-
cient for a medium size filter. Oil may be applied by
insect spray gun. For easier spraying, the oil can be
warmed.
If the filter is dipped in the recharging oil, remove it
immediately and allow to drain through slots in frame.
5. Replace filter in unit.
If another type of filler is used, follow the filter maunfactur-
er's instructions.
ECM Motor Removal and Reinstallation
(Fig. 36) -- Cartier unit ventilators utilize an Electronically
Commutated Motor (ECM) to drive the indoor fan.
The ECM is a factory programmed motor that is standard
with factory-supplied controls (CCN) and units without
factory-supplied controls that are used in high-static applica-
tions or high-capacity coils.
The ECM is programmed with an algorithm that maintains
a constant torque as the static pressure on the system varies.
For example, as the filter pressure drop increases due to dirt,
the fan will increase speed (rpm) to maintain the cfm.
The ECM is identified by the two electsical receptacles
located on the housing. See Fig. 8A, 8B, and 36.
The first receptacle is a 5-rew in-line connector that feeds
the motor line voltage. This may be either 115 volts or
230 volts. Units that are wired for 230 volts have a jumper be-
tween terminals 1 and 2 on this plug (see wiring diagram).
The second receptacle on the motor is a 16-pin connector
and is used for speed switching. This is a low voltage (24-volt)
connection. There is a jumper wire between terminals 1 and 3.
This is a 24-volt ground. Voltage is present at all times when
the motor is energized.
NOTE: A time delay exists between the time the motor speed
is switched and the motor's reaction. This is designed into the
eleclronics and does nut indicate motor problems.
When replacing the motor, note the following:
Check the part number of the old motor against that of
the replacement. There is a tag indicating the eight-digit
part number and begins with LIVE. This is the program
number used for this motor.
• The motor must be installed per the instructions below.
It is important to maintain the dimension between the
fan compartment bulkhead and the coupling.
IMPORTANT: If a replacement cooling shroud has been
supplied, it should be installed and the old one
diseasded. The motor shroud directscooling air across
the motor m provide proper cooling. Never run the
motor without the cooling shroud in place. Ensure
the shroud inlet ring does not touch the motor; agap of
1116in. to Vsin. is acceptable.
50
I
.O
SHAFT
1.000 -+Q.063
[]
AND COOLING
SHROUD
ELECTRICAL
CONNECTIONS
FACINGUNIT
O FRONT.
SHROUD
OPENINGOVER
MOTORELECTRICAL
O CONNECTIONS.
MOTOR(ECM)
NOTES:
1. All dimensions shown in inches.
2. Not all components shownfor clarity.
3. Motor shroud not shown for clarity. Install prior
to operation,
4. Refer to Fig. 42 for cooling shroud installation.
Fig. 36 -- 40UV,UH Ventilator Blower Section Assembly -- ECM Motor Detail
5]
Ensure the unit is completely assembled when chocking the
fan speed. Replace all panels, including the filters, before
checking the fan for operation. When the internal pressure
drops at a normal condition, the loading on the motor will
be such that the fan can come up to selected speed.
Fa'dure to ensure unit is completely assembled may
result in reduced life of unit and/or personal injury.
To remove and re-instaU the motors, proceed as follows;
refer to Fig. 36:
1. Remove the wire plugs from the motor.
2. Remove the 2 screws holding the motor shroud to the
bulkhead.
3. Slide the shroud offthe motor to the right.
4. Loosen the 3 setscrews on the shaft coupling between the
motor shaft and the fan shaft.
5. Loosen the motor 'belly band' and slide motor out of the
'belly band' to the right. It is unnecessary to remove the
motor mounting bracket from the bulkhead. Loosen only
the "belly band' securing the motor in the mount.
6. Rdmstall the motor in the 'belly band."
7. Ensure the blower wheels are centered within the fan
housings (between the inlet rings) before ,securing the
motor shaft couphng.
The motor eloctronics will fail prematurely if no air is able
to circulate over the motor.
8. Ensure the motor housing is at least 1 in. from the
bulkhead so that air will be able to circulate over the
motor.
9. For vertical type units, position the motor so that the
motor wire plugs are front fa(mg on a horizontal plane.
For horizontal type units with ceding mounts, position the
motor so that the motor wire plugs are front facing on a
vertical plane.
10. Secure the 3 setscrews on the shaft coupling when the
motor is properly positioned and the blower wheels are
centered within their housing.
11. Re-socurethe motor 'belly band' around the motor.
12. Reinstall the motor shroud. It is important that the motor
shroud be installed prior to operation of the motor. Ensure
the venturi is installed on the motor shroud.
13. Re-secure the two screws holding the motor shroud to the
bulkhead.
14. Reinstan the motor wire plugs.
Blower Assembly Section Removal and Rein-
stallation (Fig. 37)
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
Be careful with all components during installation, espe-
cially the bearing and plastic blower wheels. Any extreme
force applied to these components can cause unintended
damage and could void the unit warranty.
To remove blower assembly:
1. Turn off power to the unit.
IMPORTANT: Tag each right front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrical information specific to each unit.
2. Remove all front (40UV) or bottom (40UH) panels. Re-
move end panels.
3. Remove top panel with 5/]6 in. nut driver and set optional
vanes and screens to the side (40UV). Remove ductwork
if rexluired and remove top (40UV) or front (40UtD dis-
charge plenum.
4. Remove 1/4in. head screws along length of unit that se-
cure coil baffle to blower section. See Item 5 in Fig. 37.
5. Remove four ]/4 in. head screws that connect the blower
section sides to the coil section sides. See Item 2 in
Fig. 37.
6. Remove the ]/4 in. head screw from the center of the
blower dock that attaches the blower deck to the pipe
chase. See Item 1 in Fig. 37.
7. Remove six 1/4 in. head screws attaching coil baffle to
coil section. See Item 4 in Fig. 37.
8. Remove the harness connector(s) from the motor.
9. Remove the V4 in. head screw from the green ground
wire that connects the motor to frame if unit has a PSC
motor. ECM motors are grounded through the harness.
10. Remove the two cardage bolts retaining the front brace to
the frame sides. See Item 6 in Fig. 37.
11. Remove the four nuts retaining the blower section to the
back (40UV) or top (40UH) frame. See Item 3 in Fig. 37.
12. Remove the two 5/16in. nuts retaining the inboard bearing
bracket to the pipe chase (40UV, UHI50 units only). See
Item 6 in Fig. 38.
13. Remove blower section from ftame.
52
Toreinstallblowerassemblytoframeofunit:
1. Reinstallblowersectionintoframeassembly.
2. Tightenthefour5/L6in.nutsretainingblowersectionto
frame.SeeItem3inFig.37.
3. Tightenthetwo5/16in.nutsretainingtheinboardbeating
brackettothepipechase(40UV,UH150unitsonly).See
Item6inFig.38.
4. Reinstalltwocarriageboltsthatattachthefrontbraceto
theframesides.SeeItem6inFig.37.
5. Rotatethefanshaftbyhand to ensure that fans are
unrestricted and can rotate freely. Check for any fan
obstructions.
6. Re-attach green ground wire that connects the motor to
the frame with 1Ain. head screw if unit has a PSC motor.
ECM motors are grounded through the harness.
7. Cormect harness conneetor(s) to motor.
8. Reinstall the coil baffle using six V4 in. head screws that
attach the coil baffle to the coil section. See Item 4 in
Fig. 37.
9. Reinstall the 1/4in. head screw at center of blower deck
attaching blower deck to pipe chase. See Item 1 in
Fig. 37.
10. Reinstall the four 1/4 in. head screws holding the blower
section sides to the coil section sides. See Item 2 in
Fig. 37.
11. Reinstall 1/4 in. head screws along length of the unit,
securing coil baffle to the blower section. See Item 5 in
Fig. 37.
12. Reinstall optional vanes and screens and install top panel
(40UV). Reinstall top (40UV) or front (40UH) discharge
plenum and ductwork, if required.
13. Reinstall front (40UV) or bottom (40UH) panels. Rein-
stall end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (4llUH) match-
us unit tag.
14. Restore power to unit.
IMPORTANT: Disassembly order is not as important as
reassembly. The assembly order of the bearing bracket
installation is critical to having a well balanced and
sound blower deck.
Coil Assembly Removal and Reinstallation
(Fig. 39)
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
Turn off all power supplies to equipment and controls. Fail-
ure to do so may cause personal injury or damage to the
uniL
To remove coil assembly:
1. Turn off power to the unit.
IMPORTANT: Tag each tight front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrical information specific to each unit.
2. Remove all front (40UV) or bottom (40UH) panels. Re-
move end panels.
3. Remove 1/4 in. head screws along length of unit that se-
cure coil baffle to blower section. See Item 2 in Fig. 39.
4. Remove four I/4 in. head screws that connect the blower
section sides to the coil section sides. See Item 1 in
Fig. 39.
5. Remove 114in. head screws attaching outside air (OA) ac-
tuator to damper shaft OR locking quadrant assembly to
damper shaft. Remove OA actuator or locking quadrant
assembly.
6. Tag low-limit thermostat wiring and terminals. Dis-
connect low-limit thermostat wiring (right end
compartment).
7. Drain water and/or recover refrigerant in accordance
with all applicable codes. Disconnect piping from coil
connections.
8. Tag optional electric heat element wire terminations for
later reconnection. Disconnect element wires from elec-
tric heat control box (remove coil baffle for access).
9. Remove the foor 5/16in. nuts retaining the coil section to
the flame.
10. Remove coil section from frame.
To reinstall coil assembly:
1. Replace coil section into frames assembly.
2. Tighten the four sh6 in. nuts retaining coil section to
frame.
3. Reconnect electric heat wiring in electric heat control
box.
4. Reconnect wiring to low limit thermostat.
5. Replace the four 1/4 in. head screws holding the blower
deck to coil section (two on each side).
6. Replace coil baffle using l& in. head screws. See Item 2
in Fig. 39.
7. Reinstall outside air actuator or locking quadrant handle
using V4 in. head screws.
8. Reconnect piping to coils. If water coil, purge air from
coils and perform hydrostatic test to check for leaks. If
DX coil, perform leak test using nilrogen, and evacuate
sod charge per recommended HVAC procedures and all
applicable codes.
9. Replace cod section side insulation.
10. Replace front (40UV) or bottom (40UH) panels. Replaee
end panels. Ensure that tag on each right front pond
(40UV) or middle botaom panel (40UH) matches unit
tag.
II. Restore power to unit.
53
RETURN AIR
TEMPERATURE
SENSOR(OPTIONA_
OPENING--
COIL BAFFLE_
CLIPS (SEE NOTE 3)
TEMPERATURE
SENSOR(OPTIONAL)
OPENING
DAMPER SECTION
SETCREWACCESS
ELECTRICAL
BOX
CHASE
NOTES:
1, Unit shown in vertical orientation. Drawing appfies
to horizontal and vertical units.
2. Not all components shownfor clarity.
3. 40UV, UH125-200 units only.
COIL SECTION
BLOWER SECTION
Fig. 37 -- 40UV,UH Ventilator Blower Section
54
<
SEE NOTE 4
SEE DETAIL A_I
• _ z:_ _ _
SEE DETAIL A BoTroM VIEW
NOTES:
1. Not all components shown for clarity.
2. This drawing applies to 1500 cfm units only.
3. Remove shaft, motor, and coupling prior to
bearing removal.
4. Refer to Fig. 36 and 43 for motor-coupling and
coupling-shaft tolerances.
DETAIL A
Fig. 38 -- 40UV,UH Ventilator Inboard Bearing (40UV,UH150 Only)
55
O
RETURN AIR
TEMPERATURE
SENSOR OPENING
FRONT
COIL
BAFFLE
SETSCREW ACCESS
ELECTRICAL
BOX
FILTER DOOR
RETAIN ER CLIPS
(SEE NOTE 3)
NOTES:
1. Unit shown in vertical orientation. Drawing
applies to horizontal and vertical units.
2. Not all components shown for clarity.
3. 40UV, UH125-150, 40UH200 units only.
COIL SECTION
Fig. 39 -- 40UV,UH Ventilator Coil Section
DAMPER SECTION
56
Ball Bearing Replacement (40UV, UH150;
40UH200 Units Only) -- Refer to Fig. 40 for 40UH200
units only, Fig. 41 for 40UV150 and 40UH150 units with PSC
motors, Fig. 42 for 40UV150 and 40UHI50 units with ECM
motors.
Lock out and tag all power supplies to equipment and con-
_a-olsprior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
The assembly order nfthe bearing installation is critical. Be
careful with all components during removal and installa-
tion. Any excessive force applied to these components can
cause unintended damage and void unit warranty.
To replace ball bearing:
1. Turn offall power to unit.
IMPORTANT: Tag each right front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrical information specific to each unit.
2. Remove front (40UV) or bottom (40UH) panels and right
(motor end) end panel.
3. Remove top panel and set optional vanes and screens to
the side (40UV). Remove ductwork if required and re-
move top (40UV) or front (40UH) discharge plenum. For
non-ducted 40UH horizontal units with front double de-
flection discharge grille, remove grille for access to wheel
setscrews. See Fig. 37.
4. Remove IA in. head screws along length of unit that se-
cure coil baffle to blower section and remove front coil
baffle. See Item 5 in Fig. 37.
5. Loosen setscrews on all blower wheels (two per wheel).
See Fig. 38 and Fig. 40.
6. Loosen bearing setscrews.
7. Remove wiring harness connector(s) from motor.
8. If unit has ECM motor, remove motor shroud (sheet met-
al cover -- Fig. 40, Item 6; Fig. 42, Item 4) by removing
two 5h6 in. hex nuts. Do not discard cooling shroud.
9. Loosen 5/16 in. motor mount (Fig. 40, Item 7; Fig. 41,
Item 2; Fig. 42, Item 2), nut (Fig. 40, Item 3; Fig. 41,
Item 5; Fig. 42, Item 6), and bolt (Fig. 40, Item 4; Fig. 41,
Item 4; Fig. 42, Item 5), until motor housing (Fig. 40,
Item 5; Fig. 41, Item 3; Fig. 42, Item 3) moves freely.
10. Slide shaft-coupling-motor assembly (Fig. 38, ltems 3, 2,
1; Fig. 40, Items 5, 2, Ill) out of wheels and unit until
shaft clears inboard/center bearing assembly (30 in. max
clearance required from edge of frame end).
11. Remove V2in. bolts (Fig. 38, Item 4; Fig. 40, Item 9) and
hex nuts (Fig. 38, Item 7; Fig. 40, Item 1) securing bear-
ing to beating bracket. Remove beating (Fig. 38, Item 5;
Fig. 40, Item 8).
12. Install new bearing (Fig. 38, Item 5; Fig. 40, Item 8).
Secure with I/2in. bolts (Fig. 38, Item 4; Fig. 40, Item 9)
and hex nuts (Fig. 38, Item 7; Fig. 40, Item 1).
13. Slide shaft-coupling-motor assembly (Fig. 38, Items 3, 2,
1; Fig. 40, Items 5, 2, 10) back into beating and wheels.
Do not use excessive force. Damage to wheels may
OCCUr.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
Insert shaft-coupling-motor assembly into wheels until
motor clearance is as specified for motor type (PSC or
ECM). See Fig. 43 or Fig. 36.
Ensure that motor shaft is perpendicular to motor blower
endplate. Tighten sh6 in. motor mount (Fig. 40, Item 7;
Fig. 41, Item 2; Fig. 42, Item 2), nut (Fig. 40, Item 3;
Fig. 41, Item 5; Fig. 42, Item 6), and bolt (Fig. 40, Item 4;
Fig. 41, Item 4; Fig. 42, Item 5), until motor (Fig. 40,
Item 5; Fig. 41, Item 3; Fig. 42, Item 3) is secure.
Install motor shroud (sheet metal cover -- Fig. 40,
Item 6; Fig. 42, Item 4) using two 5/16in. hex nuts if using
ECM motor. Align "window" with receptacles on motor.
Motor control module could overheat and fail if oper-
ated without cooling shroud.
Re-attach green ground wire that connects the motor to
the frame with 1/4in. head screw if unit has a PSC motor.
ECM motors are grounded through the harness.
Re-attach wiring harness connector(s) to motor.
Center each wheel in its respective housing and tighten
wheel setscrews (two for each wheel).
Rotate the fan shaft by hand to ensure that fans are
unrestricted and can rotate freely. Check for any fan
obstructions.
Remove lockout and operate unit for approximately
60 seconds to let inboard/center bearing motmt
self-adjust.
Lock out and tag all power supplies to equipment and
controls. Tighten the two bearing setscrews.
Reinstall the coil baffle using the six V4 in. head screws
that attach the coil baffle to the coil section. See Item 5 in
Fig. 37.
Reinstall 1/4in. head screws along length of unit securing
coil baffle to the blower section. See Item 5 in Fig. 37.
Reinstall optional vanes and screens and install top panel
(40UV). Reinstall top (40UV) or front (40UH) discharge
plenum and ductwork if required or discharge grille.
Reinstall front (40UV) or bottom (40UH) panels. Rein-
stall end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) match-
es trait tag.
27. Restore power to uniL
57
(SEEN_TE 5)"
(SEE NOTE 5) _/
(SEE NOTE 4)
NOTES:
1. Not all components shownfor clarity.
2. This drawing applies to 2000 cfm units only.
3. Remove shaft, motor and coupling prior to removing bearing.
Refer to Ball Bearing Replacement instructions.
4. Install sleeve bearing w_thoil cup facing up and towards the rear of
the assembly.
5. Refer to Fig. 36 for motor-coupling and shaft-couplingtolerances.
®
LEFT SIDE
VIEW
Fig. 40 -- 40UH200 Ventilator Blower Drive Train Assembly
UNIT
BOTTOM
58
(SEE NOTE 3)
(SEE NOTE 4)
NOTES:
1. Not all components shown for clarity.
2. Items no. 7, 16 and associated hardware not required for
40UV, UH150. Refer to Fig. 38 for 40UV.UHtS0 in-hoard bearing
replacement.
3. Install motor with capacitor facing up.
4. Install sleeve bearing with oil cup facing up and towards the rear of
the assembly. V
UNIT FRONT (40UV)
UNIT BOI_OM (40UH)
Fig. 41 --40UV,UH Ventilator Blower Drive Train Assembly --
40UV050-150 and 40UH075-150 Units (PSC Motor)
59
S_;E NOTE 2_ _
NOTES:
1. Not all components shown for ctarity.
2. Items no. 7, 10 and associated hardware not required for
40UV, UHt50. Refer to Fig. 38 for 40UV,UH150 in-board bearing
replacement.
3. Install motor with electrical connectionsfacing front of assembly.
4. Lnsta_loBcup facing up and towards the rear of the assembly. LEFT SIDE
Fig. 42 -- 40UV,UH Ventilator Blower Drive Train Assembly --
40UV050-150 and 40UH075-150 Units (ECM Motor)
UNIT FRONT (40UV)
UNIT BOI_OM (40UH)
6O
[_]0 o
I
- O[3
I I
BLOWER SECTION
FRONT VIEW
COUPLING
O o
°/
.125±(]_32
0,500+0.063
0
FACE OF MOTOR
FLUSH WITH FACE
OF INSULATION
NOTES:
1. All dimensions shown in inches.
2. Not all components shownfor clarity.
Fig. 43 -- 40UV,UH Ventilator Blower Section Assembly -- PSC Motor Detail
6]
Blower Wheel Removal and Reinstallation
(Fig. 44)- Refer to Fig. 40 for 40UH200 units only,
Fig. 41 for 40UV050-150 and 40UH075-125 units with PSC
motors, Fig. 42 for 40UV050-125 and 40UH075-150 units
with ECM motors.
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
The assembly order of the bearing installation is critical. Be
careful with all components during removal and installa-
tion. Any excessive force applied to these components can
cause unintended damage and void unit warranty.
To remove blower wheel:
1. Turn off all power to the unit.
2. Remove blower section per service instructions in Blower
Assembly Removal and Reinstallation.
IMPORTANT: Tag each fight front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrieal information specific to each unit.
3. Use s/32 in. hex tool to loosen setscrews on all blower
wheels (two per wheel).
4. Loosen inboard/center bearing setscrews (only on
40UV, UH 150 and 200 size units).
5. If unit has ECM motor, remove motor shroud (sheet
metal cover -- Fig. 40, Item 6; Fig. 42, Item 4) by remov-
ing two 5/16in. hex nuts. Do not discard cooling shroud.
6. Loosen 5/16 in. motor mount (Fig. 40, Item 7; Fig. 41,
Item 2; Fig. 42, Item 2), nut (Fig. 40, Item 3; Fig. 41,
Item 5; Fig. 42, Item 6), and bolt (Fig. 40, Item 4; Fig. 41,
Item 4; Fig. 42, Item 5), until motor housing (Fig. 40,
Item 5; Fig. 41, Item 3; Fig. 42, Item 3) moves freely.
7. Slide shaft-coopling-motur assembly (Fig. 38, Items 3, 2,
1; Fig. 40, Items 5, 2, 10) out of wheels and unit until
shaft clears inboard/center bearing assembly (30 in. max-
imum clearance required from edge of frame end).
8. Remove four 1/4in. head screw (Fig. 44, Item 6) securing
blower housing(s) (Fig. 44, Item 7) to blower deck
(Fig. 44, Item 3) and remove blower and wheel assembly.
9. Remove five V4in. head screws (Fig. 44, Item 5) securing
blower inlet ring (Fig. 44, Item 4) to blower housing and
remove inlet ring.
10. Remove blower wheel(s) (Fig. 44, ltem 8).
To reinstall blower wheel:
1. Install new blower wheel(s) (Fig. 44, Item 8). Ensure that
the fan blades are installed in the correct orientation (cup
of blade towards discharge).
2. Install inlet ring (Fig. 44, Item 4) and install five _Ain.
head screws (Fig. 44, Item 5) securing blower inlet ring to
blower housing (Fig. 44, Item 7).
3. Install four q4 in. head screws (Fig. 44, Item 6) securing
blower housing(s) (Fig. 44, Item 7) to blower deck
(Fig. 44, Item 3).
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
Slide shafx-coupling-motor assembly (Fig. 38, Items 3, 2,
1; Fig. 40, Items 5, 2, 10) back into bearing and wheels.
Do not use excessive force. Damage to wheels may
Occur.
Insert shaft-coopling-motor assembly into wheels until
motor clearance is as specified fur motor type (PSC or
ECM). See Fig. 43 or Fig. 36.
Ensure that motor shaft is perpendicular to motor blower
endplate. Tighten s/]6 in. motor mount (Fig. 40, Item 7;
Fig. 41, Item 2; Fig. 42, Item 2), nut (Fig. 40, Item 3;
Fig. 41, Item 5; Fig. 42, Item 6), and bolt (Fig. 40, Item 4;
Fig. 41, Item 4; Fig. 42, Item 5), until motor (Fig. 40,
Item 5; Fig. 41, Item 3; Fig. 42, Item 3) is secure.
Install motor shroud (sheet metal cover -- Fig. 40,
Item 6; Fig. 41; Fig. 42, Item 4) using two S/is in. hex nuts
if using ECM motor. Align "window" with receptacles on
motor. Motor control module could overheat and fail if
operated without cooling shroud.
Reinstall blower section into frame assembly. See Fig. 37.
Tighten the four 5/16in. nuts retaining blower section to
frame.
Tighten the two 5/16in. (Fig. 38, Item 6) nuts retaining the
inboard bearing bracket to the pipe chase (only on
40UV, UH150 and 200 size units).
Reinstall two carriage bolts (Fig. 37, Item 6) that attach
the front brace to the frame sides.
Re-attach green ground wire that connects the motor to
the frame with I/4 in. head screw if unit has a PSC motor.
ECM motors are grounded ll_-oogh die harness.
Re-attach wiring harness connector(s) to motor.
Center each wheel in its respective housing and tighten
wheel setscrews (two for each wheel).
Reinstall one 1/4in. head screw (Fig. 37, Item 1) at center
of blower deck attaching blower deck to pipe chase.
Reinstall the four 1/4 in. head screws (Fig. 37, Item 2)
holding the blower section sides to the coil section sides.
Rotate the fan sbaf_ by hand to ensure that fans are
unrestricted and can rotate freely. Check for any fan
obstructions.
Remove lockout and operate unit for approximately
60 seconds to let inboard/eentea- bearing mount serf-adjust
(only on 40UV, UH150 and 200 size units).
Lock out and tag all power supplies to equipment and
controls. Tighten the two bearing setscrews (only on
40UV, UH150 and 200 size units). See Fig. 38, 40 or 44.
Reinstall the coil baffle using the six 114in. head screws
that attach the coil baffle to the coil section. See Item 4 in
Fig. 37.
Reinstall l& in. head screws along length of tmit securing
coil baffle to the blower section. See Item 5 in Fig. 37.
Reinstall optional vanes and screens and install top panel
(40UV). Reinstall top (40UV) or front (40UH) discharge
plenum and ductwork if required or discharge grille.
Reinstall front (40UV) or bottom (40Lrl_ panels. Rein-
stall end panels. Ensure that tag on each right front
panel (40UV) or middle bottom panel (40UH) match-
es unit tag.
24. Restore power to unit.
62
Sleeve Bearing Replacement (40UV050-125,
40UH075-125 and 4OUH200 Units Only)
(Fig. 44)- Refer to Fig. 40 for 40UH200 units only,
Fig. 41 for 40UV050-150 and 40UH075-125 units with PSC
motors, Fig. 42 for 40UV050-125 and 40UH075-150 units
with ECM motors.
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
The assembly order of the bearing installation is critical. Be
careful with all components during removal and installa-
tion. Any excessive force applied to these components can
cause unintended damage and void unit warranty.
To replace ball bearing:
1. Turn off all power to unit.
IMPORTANT: Tag each right front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrical information specific to each unit.
2. Use 5/s2in. hex (Allen) tool or 318in. nut driver to remove
front (40UV) or bottom (40UH) panels and right (motor
end) end panel.
3. Remove 1/4 in. head screws (Item 5 in Fig. 37) along
length of unit that secure coil baffle to blower section and
remove front coil baffle.
4. Remove left blower section end (Item 2 in Fig. 44) insu-
lation (Item I in Fig. 44).
5. Use 7/16 in. socket to remove hex nuts (Fig. 40, Item 13;
Fig. 41, Item 8; Fig. 42, Item 9) securing end beating
bracket (Fig. 40, Item 12; Fig. 41, Item 7; Fig. 42, Item 8)
to blower section end.
6. Remove beating bracket assembly (Fig. 40, Items 12, 14,
13, 11; Fig.41, ltems 7, 10,9, 11; Fig. 42, Items 8, II, 10,
12) from blower section end. Use care to slide assembly
off of shaft end. Hold shaft from inside blower section
to prevent wheel damage.
7. Use 1/2 in. socket and 1/2 in. combination wrench to
remove hex nuts (Fig. 40, Item 13; Fig. 41, Item 9;
Fig. 42, Item 10) and bolts (Fig. 40, Item 11;Fig. 41, Item
11; Fig. 42, Item 12) holding bearing (Fig. 40, Item 14;
Fig. 41, Item 10; Fig. 42, Item 11) and bearing bracket
(Fig. 40, Item 12; Fig. 41, Item 7; Fig. 42, Item 8)
together.
Ensure sleeve bearing is installed with oil cup facing
upwards as shown in left side view.
8. Replace bearing (Fig. 40, Item 14; Fig. 41, Item 10;
Fig. 42, Item 11). Attach to beating bracket using hex
nuts and bolts. Align oil cup port with matching cutout in
bearing bracket.
9. Use 7/16in. socket to slide replacement beating (Fig. 40,
Item 14; Fig. 41, Item 10; Fig. 42, Item 11) on to the end
of shaft and install beating bracket assembly (Fig. 40,
Items 12, 14, 13, 11; Fig. 41, Items 7, 10,9, 11; Fig. 42,
Items 8, 11, 10, 12) in blower section end. Attach using
liex nuts.
10. Add 5 to 10 drops of SAE 20 or 30 non-detergent based
oil to bearing.
11. Rotate the fan shaft by hand to ensure that fans are
unrestricted and can rotate freely. Check for any fan
obstructions.
12. Reinstall left blower section end insulation (Item 1in
Fig. 44).
13. Reinstall V4 in. head screws (Item 5 in Fig. 37) along
length of unit securing coil baffle to the blower section.
14. Reinstall front (40UV) or bottom (40UH) panels. Rein-
stall end panels. Ensure that tag on each right front
panel (40UV) or middle botlom panel (40UH) match-
es unit tag.
15. Restore power to unit.
63
'0
AUTOMATIC RESET
HIGH TEMPERATURE
LIMIT SWITCH
(SEE NOTES 2,3)
(SEE CAUTION)
MANUALRESET
HIGHTEMPERATURE
LIMITSWITCH
(SEE NOTES2,3)
(SEE CAUTION)
TEMPERATURE
SENSOR (OPTIONAL)
OPENING
DO NOT CHANGE LIMIT SWITCH CAPILLARY TUBE LOCA-
TION! LIMIT SWITCHES MAY NOT FUNCTION PROPERLY.
NOTES:
1. Not all components shown for clarity.
2. Supplied on electric heat units only.
3. Secure capillary tubes to blower housing using high temperature
cable tie. Capillary tube lengths will vary depending on unit size.
RETURN AIR
TEMPERATURE
SENSOR (OPTIONAL)
OPENING
Fig. 44 -- 40UV, UH Ventilator Blower Section Assembly Sheet Metal (All Units)
MOTORAND
COUPLING
SETSCREW
ACCESS
64
Damper Section Removal and Reinstallation
(Fig. 45)
Lock out and tag all power supplies to equipment and con-
trois prior to servicing unit. Follow all safety codes. Failure
to do so could result in personal injury.
The assembly order of the beating installation is critical. Be
careful with ell components during removal and installa-
tion. Any excessive force applied to these components can
cause unintended damage and void unit warranty.
To remove damper section:
1. Turn off all power to unit.
IMPORTANT: Tag each right front panel (40UV) or
middle bottom panel (40UH) for each unit. Panels have
electrical information specific to each unit.
2. Use 5/32in. hex (Allen) tool or Sis in. nut driver to remove
front (40UV) or bottom (40UH) panels and right end
panels.
3. Rernove four carriage bolts and unts securing kickplate to
end frames.
IMPORTANT: Tag kickplate for each unit. Kickplate
has electrical information specific to each unit,
4. Remove the two 1/4in. head screws securing kickplate to
the damper sides (one on each side) and remove
kickplate.
5. Remove 1/4 in. head screws attaching outside air (OA)
actuator to damper shaft or attaching locking quadrant as-
sembly to damper shaft. Remove OA actuator or locking
quadrant as_mbly.
6. Remove six I/4 in. head screws (3 per side) securing
damper to 40UH unit rear panel.
7. Remove two 5116 in. nuts attaching damper assembly to
back frame.
8. Remove damper assembly from unit,
To replace damper section:
I. Replace damper assembly into umt.
2. Replace 5/16in. nuts attaching damper assembly to back
frame.
3. Replace six 1/4 in. head screws (3 per side) securing
damper to 40UH unit rear panel.
4. Replace 1/4 in. head screws attaching OA actuator to
damper shaft OR attaching locking quadrant assembly to
damper shaft. Replace OA actuator or locking quadrant
assembly.
5. Replace the two 1/4 in. head screws securing kickplate
to the damper sides (one on each side) and remove
kickplate.
6. Replace four carriage bolts and nuts securing kickplate to
end frames.
7. Reinstall front (40UV) or bottom (40UH) panels. Rein-
stall end panels. Ensure that tag on each fight front
panel (40UV) or middle bottom panel (40UH) match-
es unit tag.
8. Restore power to the unit,
65
_oRDISCHARGE AIR
TEMPERATURESENSOR
.• OPENING
OPENING
BAFFLE
DAMPER SECTION _
_MOTOR & COUPLING
SETSCREW ACCESS
_COIL SECTION
ELECTRICAL
BOX
SECTION
NOTES: A
1. Unit shown in vertical orientation. Drawing applies to horizontal and vertical units.
2. Not all components shown for clarity.
Fig. 45 -- 40UV,UH Ventilator Damper Section Removal/Installation
66
TESTING
The Unit Ventilator Comfort Control module is designed for
easy checkout and commissioning using the Carrier Comfort
Network® (CCN) Service Tool. An RI14 service connector
jack is provided on each control board, which eliminates the
need to modify any communication wiring when service is
required. See Fig. 26.
Before any testing is performed, be sure all configuration
has been completed and the device address and bus nureber
have been changed from the factory defaults.
NOTE: No two devices should use the same address even if
they am not connected to the CCN system. The Comfort Con-
troller uses this unique addressing to provide a restart delay
upon returning from a power failure and a start delay during
normal operation. This prevents excessive demand by stagger-
ing the start time for each piece of equipment using a Unit
Ventilator Comfort Controller.
To test the Comfort Controller, perform the following
procedure:
1. The controller database must be uploaded into the Net-
work Service Tool which will be used to perform the
testing. This will allow access to all the necessary con-
figuration and status information. Follow the operating
instructions provided with the service tool and perform
the controller upload.
2. With the control switch in the CONT position, apply
power to the control. Verify the red LED on the control
board flashes ON and OFF at a 1-second rate. It may
take up to 5 seconds for this to occur initially as the
control board is performing a self-health diagnostic
check. Verify the fan starts to operate.
3. Using the Network Service Tool, select the controller
to be tested from the menu provided, then select the
DISPLAY function.
4. Using a digital thermometer to initially check and ver-
ify the temperature sensor, check the temperature val-
ues for the space/return air sensor, the supply air
sensor, and the mixed air and outdoor-air sensors if
installed. If an error exists between the actual value
and the displayed reading, determine the difference
between the two values, and enter a set point Trim (see
Table 24) in the configuration table for the appropriate
sensor. No correction is required for the supply air sen-
sor. If this sensor has more than a _+5 degree F error,
replace the sensor.
5. Next, test the controller inputs and outputs as applica-
ble. Verify that all modulating outputs are driven fully
closed after power has been applied to the controller
for at least 3 minutes. Verify that each water valve and
the outdoor-air damper are fully closed. Use the proce-
dures below to test the inputs and outputs as applicable
to each control.
NOTE: The control drives all modulating outputs, which have
been configured, dosed when first returning from a power fail-
ure restart, regardless of whether an output is normally open,
normally closed, or non-spring return type.
Water Valve Tests
The manual positioning lever on all water valves should
only be used when controller power is OFF. DO NOT
attempt to move this lever when controller power is
applied. If the position lever does not move freely for man-
ual positioning when the power is off, remove the valve
cover and push the solenoid plunger down using a small
screwdriver inserted in the slot below the solenoid.
MODULATING COOLING CONTROL -- If a modulating
chilled type water valve is used, verify that valve position is
fully closed while the unit is unoccupied and the fan is OFF.
Using the Network Service Tool, page down to the bottom of
the Points Display screen and select the COOLING 2 output.
Force the output to OFF. Next, select the COOLING 1 output
and force this output ON. Verify the chilled water valve begins
to open. Allow the valve to fully open and check to ensure the
valve reaches its full stroke and does not stick or bind. After the
valve has stopped opening, select the COOLING 2 output and
force it to ON. The force placed earlier on the COOLING 1
output should be removed automatically and the chilled water
valve should begin to close. After the valve has fully closed,
remove any forces from the COOLING I and COOLING 2
outputs.
HEATING VALVES -- If a modulating hot water or steam
type heating valve is used, verify the position of the valve is
fully closed while the unit is unoccupied and the fan is OFF.
Using the Network Service Tool, page down to the bottom of
the Points Display screen and select the HEATING 2 output.
Force the output to OFF. Next, select the HEA'ITNG 1 output
and force this output ON. Verify the heating valve begins to
open. Allow the valve to fully open and check to ensure the
valve reaches its full stroke and does not stick or bind. After the
valve has stopped opening, select the HEATING 2 output and
force it to ON. The force placed earlier on the HEATING 1out-
put should be removed automatically and the heating valve
should begin to close. After the valve has fully closed, remove
any forces from the HEATING 1 and HEATING 2 outputs.
Face and Bypass Damper Tests
COOLING CONTROL -- For units equipped with cooling,
verify that the face and bypass damper is in the full coil bypass
position when the unit is unoccupied and the fan is off. Verify
that the switch position indicator on the face and bypass damp-
er actuator is pointing to the zem (0) position at this time.
Verify the cooling valve is closed.
Using the Network Service Tool, page down to the bottom
of the Status display screen and select the Heating Enable Out-
put point. Force this output to OFF. Next, select the Cooling
Enable Output and force this point to ON. Select the COOL-
ING 2 output and force this point to OFF. Select the COOL-
1NG 1 output and force this point to ON. Verify the face and
bypass damper begins to move toward the coil face position
and the cooling valve opens. Check to ensure the valve reaches
the full open position and the damper moves to the coil face po-
sition without sticking or binding. After the damper reaches the
full coil face position, select the COOLING 2 output and force
it to ON. The force placed earlier on the COOLING 1 output
should be removed automatically, and the damper should begin
moving toward the bypass position. After the face and bypass
damper is in the bypass position, force the Coohng Enable Out-
put to OFF. Verify the cooling valve is closed or closing. After
the valve has fully closed, remove any forces from the COOL-
ING 2, Heating Enable, or Cooling Enable Outputs.
HEATING CONTROL- For units equipped with heating,
verify that the face and bypass damper is in the full coil bypass
position when the unit is unoccupied and the fan is off. Verify
that the switch position indicator on the face and bypass damp-
er actuator is pointing to the zero (0) position at this time.
Verify the heating valve is closed.
Using the Network Service tool, page down to the bottom of
the Points display screen and select the Cooling Enable Output
point. Force this output to OFF. Next, select the Heating Enable
Output and force this point to ON. Select the HEATING 2 out-
put and force this point to OFF. Select the HEATING 1 output
and force this point to ON. Verify the face and bypass damper
begins to move toward the coil face position and the heating
valve opens. Check to ensure the valve reaches the ftdl open
position and the damper moves to the coil face position without
67
stickingorbinding.Afterthedamperreachesthefullcoilface
position,selecttheHEATING2outputandforceittoON.The
force placed earlier on the HEATING 1 output should be re-
moved automatically, and the damper should begin moving to-
ward the bypass position. After the face and bypass damper is
in the bypass position, verify the heating valve is closing. After
the valve has fully closed, remove any forces from the HEAT-
ING 2, Heating Enable, or Cooling Enable Outputs.
Dampers
MODULATING OUTDOOR (OA) AIR DAMPER -- Veri-
fy the position of the OA damper is fully closed off to outdoor
air when the unit is off or unoccupied. Using the Network Ser-
vice Tool, page down to the bottom of the Status Display
screen and select the MIXED AIR DAMPER 2 output. Force
the output to OFF. Next, select the MIXED AIR DAMPER l
output and force this output ON. Verify the dampers begin to
open to outdoor air while dosing off the retm'n air damper. Al-
low the dampers to fully open and chock to ensure the outdoor-
air damper reaches its full open position and does not stick or
bind. After the damper has stopped opening, disconnect power
to the controller by setting the control to OFF. Verify the spring
return feature fully opens the return air damper while the out-
door-air damper fully closes. Return the control switch to
CONT and wait for the damper to again fully open to the out-
door air.
After the outdoor-air damper is fully open, select the
MIXED AIR DAMPER 2 output and force it to ON. The force
placed earlier on the MIXED AIR DAMPER 1 output should
be removed automatically. The outdoor-air dampers should be-
gin to close while the return air damper begins to open. After
the outdoor-air dampers fully close, remove any forces from
the two outputs.
Fan Tests -- The Unit Ventilator Comfort Control module
Vrovides a fan relay output which starts and stops the fan when
the control switch is in the AUTO position. A three-speed out-
put control is used to switch the fan from LOW speed to
MEDIUM or HIGH speed as required by the load.
FAN RELAY OUTPUT--Set the control switch to the
AUTO position and using the Network Service Tool, select the
Status Display screen and verify the FAN STATUS and FAN
RELAY both read OFF. Set the control switch to the AUTO
position. Select the FAN RELAY and force the point to ON.
Verify the fan starts and the FAN STATUS changes within
10 seconds. Reseloct the FAN RELAY and force the point to
OFF. Verify the fan stops and the fan status changes to OFF.
Remove any force applied.
THREE-SPEED FAN -- To verify proper operation of the
fan speed control, the unit must be in the Unoccupied mode.
With the fan stopped, set the control switch to the CONT posi-
tion. Verify the fan operates at low speed. Using the Network
Service Too1, page down through the Maintenance screen and
locate the FAN SPEED RELAY 1 point. Force the FAN
SPEED RELAY 1 output to ON. Verify the fan speed increases
to MEDIUM. Select the FAN SPEED RELAY 2 output and
force this point to ON. Verify the fan speed increases to HIGH.
Remove any forces from FAN SPEED RELAY 1 and FAN
SPEED RELAY 2.
FAN STATUS -- Set the control switch in the OFF position.
Using the Network Service Too1, select the Points Display
screen and verify the Supply Fan Status reads OFF. Set the con-
trol switch to the CONT position and verify the fan is operat-
ing. Verify the Supply Fan Status reads ON.
Filter Maintenance -- For units connected to a CCN
system, a dirty filter alarm is generated and reported as soon as
the operating hours of the unit exceed the configured filter
maintenance interval. "lhis is a software function of the control-
ler and does not require any testing.
To reset the alarm after the filters have been serviced, use
the Network Service Tool and select the filter status from the
Status Display screen. Force the point to CLEAN. After wait-
ing 10 seconds, remove the force using the AUTO command.
This will reset the timer and reset the displayed value to
CLEAN.
Remote Start Input- Set the control switch to the
OFF position and using the Network Service Too1, select the
Status Display screen and verify the FAN STATUS and FAN
RELAY both read OFF. Set the control switch to the AUTO
position. Using a jumper wire, temporarily jumper terminals
TB to T20 of the control board. Verify the FAN RELAY reads
ON, the fan starts and the FAN STATUS changes from OFF.
From the Status Display screen, determine the operating
MODE. Remove the jumper. If the operating mode previously
was cooling, die MODE will change to FAN ONLY as soon
as the jumper is removed. The fan will continue to operate for
5 minutes. For all other modes, the fan should stop within
5 seconds after the jumper is removed.
Sensors
AIR QUALITY SENSOR OPTION -- Using die Network
Service Too1, select the Stares Display screen and verify the
Air Quality (CO2 sensor) reads at least 300 ppm. Verify
the sensor is configured for a 2 to 10 vdc output over a 0 to
2000 ppm sensing range. The hardware jumper inside the sen-
sor near the terminal connection block must also be installed in
the proper position for a voltage output. Any further sensor
chockout requires the use of the User Interface Program and a
calibration gas to provide an accurate verification. Refer to the
instructions provided in the calibration gas kit and the User In-
terfaea Program for operation of these items.
HUMIDITY SENSOR OPTION -- Using the Network Ser-
vice Too1, select the Status display screen and verify the Rela-
tive Humidity reads the proper value. Be sure the local RH sen-
sor decision in the CCN Configuration table has been set to
YES. The 499-ohm resistor, which has been factory-supplied
with the sensor, must also be correctly installed. Use a sling
psychrometer or local humidity sensor to verify the sensor is
reading properly.
Fire Shutdown Option -- Using the Network Service
Too], select the Status display screenand verify the Fire Shut-
down statusreads NORMAL when the local smoke orfire de-
rectoris in die normal state. Set the controlswitch to the AUTO
position, and force the FAN RELAY output ON. Verify the fan
start and the FAN STATUS reads ON. Trip the local smoke de-
tectur or fire detector and verify the Fire Shutdown input reads
ALARM, the supply fan immediately stops, and the FAN
STATUS reads OFF. Place the control switch in the CONT
position and verify the supply fan remains off. Reset the smoke
or fire detector and verify the supply fan restarts. Remove
all previous forces and set the control switch back to the OFF
position.
Electric Heat and Direct Expansion Cool-
ing- Electric heat and direct expansion cooling control
functions utilize both mechanical and software integrated safe-
ties which prevent the testing of these functions independently
of the equipment operation. These require that the equipment
be operating in order to prevent equipment damage. All previ-
ous testing must be completed prior to performing any DX and
electric heat tests.
ELECTR!C HEAT -- Set the control switch to the OFF posi-
tion. Using the Network Service Tool, select the Status Display
screen and verify the FAN STATUS and FAN RELAY both
read OFF. Verify a controlling temperature of 85 F or less. If
not, force the value to 70 ESet the control switch to the AUTO
position. Select the Remote Start point and force the point to
ON. Verify the fan starts and the FAN STATUS changes. Select
the Set Point screen and increase the Occupied Switch Set
68
Point to 90 F. Select the Points Display screen and verify the
Heating 1 output reads ON. If two stages am used, verify the
second stage is set to ON within two minutes. Verify both elec-
tric heat control relays are energized. Verify the electric heater
stage(s) are enabled and that the supply-air temperature in-
creases. Select the Set Point screen and return the set points to
their original values. Reselect the Remote Start input and set
the point to AUTO. Verify the supply fan stops and the Fan Sta-
tus changes to OFF. Reselect the Controlling Temperature
point and AUTO this point if it had previously been forced.
DIRECT EXPANSION COOLING -- Set the control switch
to the OFF position and the condensing unit disconnect to OFF.
Using the Network Service Tool, select the Points Display
screen and verify the FAN STATUS and FAN RELAY both
read OFF. Verify the Controlling Tempea'ature is greater than
55 F. If not, force the value to 70 E Set the control switch to the
AUTO position. Select the Remote Start point and force the
points to ON. Verify the fan starts and the FAN STATUS
changes. Select the Set Point screen and decrease the Occupied
Heating Set point to 40 F and decrease the Occupied Cooling
set point to 45 E Verify the outdoor-air temperature reads
above the configured DX Outdoor Air Lockout value. If not,
force the Outside-Air Temperature to 90 E Select the Points
Display screen and verify the Cooling 1 output reads ON. If
two stages are used, verify the second stage is set to ON within
2minutes. Verify both accessory relays are energized. Set the
condensing trait disconnect to ON. Verify the DX coohng
stage(s) are enabled and that the supply-air temperatme
decreases. Allow the unit to operate for 2 minutes minimum.
Select the Set Point screen and return the set points back to
their original values. Re.select the Remote Start input and
AUTO the point. Verify the mode changes to Fan Only. Resc-
lect the Controlling Temperature point and AUTO this point
if it had previously been forced. Reselect the Outside-Air
Temperature point and AUTO this point if it had previously
been forced. Allow the fan to operate to evapomtz the conden-
sate from the coil. The supply fan will stop automatically after
approximately 5 minutes.
Mixed-Air Damper Sensor Final Calibra-
tion -- The mixed-air damper control uses a temperature dif-
ference method to maintain the minimum outdoor-air ventila-
tion. For this reason, it is important that the sensors be calibrat-
ed to ensure that the de_Ctredquantity of outdoor air is provided
at any operating speed.
IMPORTANT: The Comfort Controller requires that
each unit be equipped with its own outdoor-air sensor
installed for mixing box applications. A broadcasted
OAT value from a single location will not ensure that the
outdoor-air temperature is being correctly measured for
an individual _t
To perform a final calibration for the sensors:
1. Set the control switch to the OFF position and using
the Network Service Tool, select the Display screen
and verify the FAN STATUS and FAN RELAY both
read OFF.
2.
3.
Set the control switch to the CONT position.
Using the Network Service Tool, page down to the
bottom of the Points Display screen and select the
MIXED-AIR DAMPER 2 OUTPUT. Force the output
to OFF.
4. Next, select the MIXED-AIR DAMPER 1output and
force this output ON. Wait for the dampers to fully
open to outdoor air while closing off the return-air
damper. Allow the unit to operate for 5 minutes after
the OA damper reaches its fully open position.
5. Verify the mixed-air temperature is within 0.3 ° F of
the outdoor-air temperature value. Using the OAT
(Fig. 24) function, adjust the Outdoor-Air Value so that
both sensors read the same relative temperature. (The
values should have been previously verified for accu-
racy earlier.)
6. Select the MIXED AIR DAMPER 2 output and force
it to ON. The force placed earlier on the MIXED-AIR
DAMPER 1 output should be removed automatically
and the OA dampers should begin to close while the
return-air damper begins to open.
7. After the OA dampers fully close, allow the unit to
operate for 5 minutes. Verify the return-air temperature
is within 0.3 °F of the mixed-air temperature reading.
If not, adjust the return-air temperature reading using
the OAT (Fig. 24) function so that both sensors read
the same temperature. (The value of the mixed-air
temperature and outdoor-air temperature were previ-
ously trimmed and should not be readjusted.)
8. Reselect the FAN RELAY and force the point to OFF.
Verify the fan stops and the FAN STATUS changes to
OFF. Remove the forces previously placed on the
MIXED-AIR DAMPER 1 and 2 outputs.
Testing Completion -- After all checkout and testing
has been completed, set the controller time by using the Build-
ing Time feature of the Network Service Tool (do NOT use the
Controller Time Function). After disconnecting from the unit,
CYCLE THE UNIT POWER to reset the valve and damper
positions and restore automatic control. Although the Unit
Ventilator Comfort Control module will not respond, the
controller will begin to maintain a software clock so that any
Network Alarm message will contain the correct time and date
stamp.
Additionally, the database for each control should be stored
on a 3.5 in. computer disk for future service use. The CCN Net-
work Service provides an Export function for this. Refer to the
Service Too1operating inslructions for fin'ther information. The
database disk will provide an easy method of reprogramming a
control board should it ever become necessary to replace it. All
the control configuration, set points, sensor trim information,
and controller addressing information is stored for easy down-
loading into a replacement control board assembly.
Unit Diagnostics and Troubleshooting -- See
Table 30 for 40UV,UFI diagnostics and troubleshooting
information.
69
Table 30 -- Unit Diagnostics And Troubleshooting
PROBLEM POSSIBLE CAUSE
Unit Does Not Operate Power to control is OFF
Remote Start/Stop (S/S) jumper not installed (for
stand-alone operation only)
Faulty connections
Control switch is in OFF positionor safety controls
are tripped
Smoke or tire detector is tripped, detector wiring
shorted
No Heating
No Cooling
Overheating
Overcooling
Mixed Air Damper Wgl
Not Operate
Damper Fails to Operate
Properly at Minimum
Position
Temperature Sensor Not
Reading Correctly
Heating is forced disabled
No hot wster/stearrde]ectricity
Electric heater safety tripped
Configuration error
No power to valve or relays
End switch improperly set (on Face and Bypass
units only)
Incorrect sensor reading
No fan status
Cooling is forced disabled
No chilled water/electricity
Condensing unit safetytripped
Configuration error
No power to valve or relays
Outdoor air temperature below DX outdoor air lock-
out
End switch improperly set (on Face and Bypass
units only)
incorrect sensor reading
No fan status
Heat outputs are forced
Configuration error
Cooling outputs are forced
Configuration error
Campers are forced
No power to actuator
Configuration error
Failed sensor (shortened or open)
No fan status
Incorrectly calibratedsensors
Loose connections
Sensor out of calibration
CORRECTIVE ACTION
Check localdisconnect or circuitbreaker,
Install jumper between T20 on control module and TB
(24 vac),
Check LED on control beard, If not flashing at a 1-second
rate, check for loose connections and 24 vac on POWER
connector.
Verify control switch is in the AUTO or CONT position,
Check for a tripped LL'I_
Check the status of the Fire Shutdown input, Determine
cause of detector trip and correct it necessary, Check for
shorted wiring and correct it necessary,
Verify no forces are present inthe Heating 1, Heating 2 or
Heating Enable outputs; remove if necessary,
Check source and correct any problems.
Determine cause for safety trip,typically insufficientair-
flow, Correct condition and reset safety switch in heater
contrst box.
Verify the control is configured properly for the type of
heat used.
Check for 24 vac at water valve. If no power, check for
open wiring.
Referto Face and Bypass Damper testing to verify proper
operation of end switch and water valves.
Verify the temperature sensors are reading the correct
temperatures.
Verify the Fan Status reads ON. Fan Status must read ON
for heat to operate.
Verify no forces are present in the Cooling 1, Cooling 2 or
Heatin_l Enable outputs; remove it necessary.
Check source and correct any problems.
Determine cause for safety trip, correct condition and
reset safety switch incondensing unit control box.
Verify the control is configuredproperly forthe type of
cooling used.
Check for 24 vac at water valve. If no power, check for
open wiring.
Verify DX Outdoor Air Lockout is correctly set to the mini-
mum recommended condensing unit operating tempera-
ture. Verify OAT sensor is reading correctly
Refer to Face and Bypass Damper Tests to verify proper
operation of end switch and water valves.
Verify the temperature sensors are reading the correct
temperatures.
Verify the Fan Status reads ON. Fan Status must read ON
for coolingto operate.
Verify no forces are preseut on the Heating 1 or Heating 2
outputs. Remove if necessary.
Verify the control is configured properly for the type of
heating used.
Verify no forces are present on the Cooling 1 or Cooling 2
outputs. Remove if necessary.
Verify the control is configured properly for the type of
cooling used.
Verify no forces are present on the MIX1 or MIX2 outputs.
Remove ifnecessary.
Check for 24 vac. If no power, check for open wiring.
Verity the control is properly configuredfor modulating
type OA damper.
Verity the temperature sensors are reading correctly.
Replace any bad sensor.
Verify the Fan Status reads ON. Fan Status must read ON
for dampers to operate.
Verity sensors are properly calibrated (reter to the test
section and repeat the calibration procedure). Verify no
forces are present on MAT, OAT,or SPT.
Verify all sensor lead connections are securely fastened.
Recheck each sensor reading usinga digital thermometer
as areference. Reset the TRiM value to zero before test-
ing each sensor (OAT,MAT, and RAT/SPT). Replace any
sensor requirin_ more than 5 degrees of correction.
?0
Table30 -- Unit Diagnostics and Troubleshooting (cont)
PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION
Indoor Air Quality (IAQ) IAQ not enabled Enable IAQ control operation.
Features Maffunctioning Set pointtoo high/too low Adjust the set pointto the correct value.
Space or return air temperature too high/low Controlwill resume when space/returns temperatures
recover.
Space Reletive Humiditytoo high Controlwill resume when relative humidity recovers.
Verify high humiditylimitis configured properly.Reset to
100% ifRH contro/is not used.
MAT sensor is shorted, open, or forced Normal operation will resume when MAT sensor is
operating properly. Remove Force; repair or replace MAT
sensor.
LLT Trips Frequently LLT switch malfunctioning Reptace LLT switch.
MAT sensor failed or out of calibration Verify MAT sensor is reading correctly.Trim or replace if
necessary.
IAQ Level Exceeds Maximum output value set too low Verify maximum output value has been correctly set.
Set Point Frequently Increase value in 10% increments.
(Generated Alarms) OAT sensor failed or open Normal operation will resume when OAT sensor is
repaired.
LEGEND
DX -- Direct Expansion
IAQ -- Indoor Air Quality
LED -- LightEmitting Diode
LLT -- Low-LimitThermostat
MAT -- Mixed-AirTemperature Sensor
MIX1 -- Mixed Air 1Terminal
MIX2 -- Mixed Air 2Terminal
OA -- Outdoor Air
OAT -- Outdoor-Air Temperature Sensor
RH -- Relative Humidity
RAT -- Return-Air Temperature
SPT -- Space Temperature Sensor
TB -- Terminal Box
7]
Copyright 2005 Carrier Corporation
Manufacturer m_erves the right to di_.ontinue, or _ange at any time, specilTw.atJonsor designs without noti_ and without incurring obligations.
Book 3 Catalog No. 534-094 Printed in U.S.A. Form 40LIV,UH-6SI Pg 72 1-06A 7-05 Replaces: 40UV, UH-3SI