CARRIER Package Units(both Units Combined) Manual L0604537
48GS L0604537
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 32
Download | |
Open PDF In Browser | View PDF |
48GS, 48GX 3-Phase Single-Packaged Gas Heating/ Electric Cooling Units HEATING & COOLING Visit www.carrier.com Installation, Start-Up, and Operating Instructions 48GS Sizes 030-060, 48GX Sizes 030-060 NOTE: Read installation. the entire instruction TABLE SAFETY RECEIVING before starting ..................................................... .......................................................................... AND INSTALLATION .......................................... CHECK EQUIPMENT ............................................................. IDENTIFY UNIT ................................................................ INSPECT the OF CONTENTS CONSIDERATIONS INTRODUCTION manual SHIPMENT 1 2 2 2 2 ........................................................ 2 INSTALLATION ................................................................ PROVIDE uNrr SUPPORT .................................................... 2 2 ROOF CURB ....................................................................... SLAB MOUNT ................................................................... GROUND MOUNT ............................................................ FIELD FABRICATE PROVIDE RIG AND DUCTWORK ........................................ CLEARANCES ...................................................... PLACE UNIT ......................................................... CONNECT CONDENSATE DRAIN ...................................... INSTALL FLUE HOOD .......................................................... INSTALL INSTALL GAS PIPING ........................................................... DUCT CONNECTIONS ...................................... 2 2 6 6 7 7 7 8 8 10 A99338 Fig. 1--Unit 48GS and 48GX CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DISCHARGE .......................................................... 10 INSTALL ELECTRICAL CONNECTIONS ......................... 12 COMBUSTION-AIR BLOWER ....................................... 27 HIGH-VOLTAGE CONNECTIONS ................................ 12 SPECIAL PROCEDURES FOR 208-V OPERATION ...12 CONTROL VOLTAGE CONNECTIONS ....................... 12 LIMIT SWITCH ................................................................ BURNER IGNITION ........................................................ 27 27 MAIN 27 HEAT ANTICIPATOR SETTING ................................... TRANSFORMER PROTECTION .................................... CONDENSER CONDENSATE CONDENSER COIL, EVAPORATOR COIL, AND DRAIN PAN .......................................... FAN .......................................................... ELECTRICAL CONTROLS PRE-START-UP START-HE .......................................................................... 15 ................................................................................... 15 CHECK FOR REFRIGERANT LEAKS ............................... START-UP HEATING AND MAKE ADJUSTMENTS......16 CHECK CHECK HEATING CONTROL ....................................... GAS INPUT ........................................................ ADJUST GAS INPUT 12 15 ...................................................... BURNERS ............................................................. AND WIRING .................. 28 REFRIGERANT CIRCUIT ............................................... GAS INPUT ...................................................................... 15 27 28 28 28 EVAPORATOR AIRFLOW ............................................. 28 METERING DEVICE -- ACUTROL DEVICE ............. 28 16 16 LIQUID LINE STRAINER .............................................. 28 16 TROUBLESHOOTING ............................................................... 28 ............................................................ 28 CHECK BURNER FLAME .............................................. AIRFLOW AND TEMPERATURE RISE ....................... 19 19 HEATING SEQUENCE OF OPERATION ..................... LIMIT SWITCHES ........................................................... 19 19 NOTE TO INSTALLER-Before the installation, READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY. Also, AUXILIARY LIMIT SWITCH (ROLLOUT) .................. 19 START-UP COOLING AND MAKE ADJUSTMENTS......20 CHECKING COOLING CONTROL OPERATION .......20 make sure the User's Manual and Replacement Guide are left with the unit after installation. The furnace is NOT to be used for START-UP temporary CHECKLIST beating of buildings or structures under construction. CHECKING AND ADJUSTING REFRIGERANT CHARGE ........................................................................... 20 INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS .............................................................................. 21 COOLING SEQUENCE OF OPERATION ..................... MAINTENANCE ......................................................................... AIR FILTER ...................................................................... EVAPORATOR BLOWER AND MOTOR ..................... FLUE GAS PASSAGEWAYS ......................................... Manufacturer SAFETY CONSIDERATIONS 21 21 24 Installation and servicing of air-conditioning hazardous due to system pressure and electrical 24 26 trained and qualified personnel air-conditioning equipment. should install equipment can be components. Only repair, or service reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring otiligations. PC 101 Printed ir_ U.S.A. Catalog NO. 48GS,GX-TSI Pg 1 2-06 Replaces: New Untrained cleaning personnel by trained equipment, attached Follow can perform basic maintenance coils and filters. All other operations functions of should be performed service personnel. When working on air-conditioning observe precautions in the literature, tags, and labels to the unit, and other safety precautions that may apply. all safety codes. Wear safety gla.gses and work gloves. Use quenching cloth for unbrazing operations. available for all brazing operations. Improper nance, installation, or u_ adjustment, Have fire extinguisher alteration, can cause carbon monoxide service, poisoning, an explosion which can result in personal damage. Consult a qualified installer, service mainte- and job data. Verify unit voltage and amperage on unit rating plate agree with power supply INSPECT injury or unit agency, or gas SIUPMENT have it examined by transportation inspectors Forward claim papers directly to transportation facturer is not responsible for any damage Check all items against shipping nearest distributor if any item is missing. operations incurred in transit. list. Immediately leave notify all parts in original the packages 1. Remove unit from shipping carton. Leave top shipping skid on the unit as a spreader bar to prevent the rigging straps from damaging the unit. If the wood skid is not available, use a spreader service or maintenance before removal. company. Manu- INSTALLATION supplier for information or assistance. The qualified installer or agency must use only factory-authorized kits or accessories when modifying this product. Before performing listed to unit. Inspect for shipping damage while unit is still on shipping pallet. If unit appears to be damaged or is torn loose from its anchorage, To prevent loss or damage, until installation. fire, or requirements provided bar of sufficient length to protect unit from damage. 2. Position the lifting bracket assembly around unit. Be sure the strap does not twist. on unit, turn off gas supply to unit. Then turn off unit main power switch and install lockout tag. Electrical shock or explosion could cause serious injury or death. the base of the 3. Place each of the 4 metal lifting brackets in the composite pan. into the rigging holds 4. Thread lifting bracket unit as follows: around bottom (ratchet type). strapping perimeter of Recognize safety information. This is the safety-alert symbolzf x . When you see this symbol in instructions or manuals, be alert to a. Open lever the potential b. Feed strapping through tension buckle as shown in Fig. 7. c. Pull strapping through tension buckle Understand for personal injury. the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in serious injury or death. WARNING result in serious injury or death. signifies a hazard which could CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which operation. These will result in enhanced installation, reliability, or existing national these instructions cover minimum standards exceed requirements and conform to and safety codes. In some instances, certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation. and 48GX permit Models the tension must be secure 6. Attach buckle with an N in the fifth position of the model number are dedicated Low NO x units designed for California installation. These models meet the California maximum oxides of nitrogen (NO,) emissions requirements of 40 nanograms/joule or less as shipped from the factory and must be installed in California Air Quality Management Districts where a Low NO_ rule exists. RECEIVING AND INSTALLATION Step I_HECK EQUIPMENT UN1T The unit model number and serial number are stamped on unit identification plate. Check this information against shipping papers until clevis 4 rigging brackets. lifting brackets brackets or hook of sufficient strength to (See Fig. 7). 7. Attach the 2 safety straps directly 8. Position it is taut. Lifting in the rigging holds. field-supplied to the clevis or hook at the DO NOT attach the safety straps to the (See Fig. 7). lifting point directly 9. Lift unit. When unit is directly over the unit's center of gravity. over the roof curb, remove 2 safety straps. Lower the equipment ROOF CURB (See Fig. 4 for roof curb dimensions). IDENTIFY 5. Tighten Step 2--PROVIDE duct openings covered. Units may be installed either on a cement slab, or directly on the ground if local codes unit taut. squeeze safety latch, lift lever, and pull webbing INTRODUCTION unit sizes have return and discharge openings for both horizontal and downffuw configurations, and are factory shipped with all downflow a rooftop, strapping, outward. units (See Fig. 1) are fully self-contained, combination Category I gas heating/electric cooling units designec[ for outdoor installation (See Fig. 2 and 3 for unit dimensions). All buckle d. Snap lever down to lock strap in tension buckle. To relea._e hole in the lifting bracket instructions The 48GS of tension the onto the roof curb. UNIT SUPPORT Install accessory roof curb in accordance with instructions shipped with curb (See Fig. 4 for roof curb dimensions). Install insulation, cant strips, curb. roofing, IMPORTANT: and flashing. Ductwork must be attached to The ga,sketing of the unit to the roof curb is critical for a watertight seal. Install ga.sheting material supplied with the roof curb. Improperly applied gasketing can also result in air leaks and poor unit performance. Curb should be level to within I/4 in. This is necessary for unit drain to function properly. Refer to accessory roof curb installation instructions for additional information as required. SLAB MOUNT Place the unit on a solid, level concrete pad that is a minimum of 4 in. thick with 2 in. above grade. The slab should be flush on the compressor end of the unit (to allow condensate drain installation) and .should extend 2 in. on the three remaining sides of the unit (See Fig. 6). Do not secure the unit to the slab except when required by local codes. eLocKorrP_.[L r_ _e O'NL_ '"11111 _11111111 III suPeL_ ae 3 -- TOP VIEW REAR REQUIRED CLEARANCE TO COMBUSTIBLE MATL. REQUIRED CLEARANCE FOROPERATION AND SERVICING INCHES TOP OF UNIT ................................................................................... 14.00 DUCT SIDE OF UNIT ................................................................ 2.00 SIDE OPPOSPTE DUCTS ............................................................... 14.00 BOTTOM OF UN T 0 50 ELECTR C HEAT PANEL" i_ iiiii_i.iii.i , , i :'i"i "" " "36"00 [ram] [355¸6 [508] (355 6] 12 [914714] NEC. REQUIRED CLEARANCES. INCHES BETWEEN UNITS, pOWER ENTRY S DE .............................. 4200 UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES, POWER ENTRY S_DE ......................... 42,00 [mm [1066.8 [914 O] EVAP COIL ACCESS SIDE ....................................................... POWER ENTRY SIDE ....................................................... (EXCEPT FOR NEC REQUIREMENTS) UNIT TOP ............................................................................. SIDE OPPOSITE DUCTS .............................................................. DUCT PANEL ...................................................................... INCHES [mini 36.00 [9140 1 36¸00 [914.0 I 48 00 [1219.2] 36¸00 [914 O] 12 00 [304.8] * +MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE. [1066 8] LEGEND CG - Center of Gravity COND Condensor EVAP - Evaporator NEC - National Bectrical Code 9EQ'D +Required NOTE: Dimensions are In If] [mm] -- 7+e m -t+c+4) t ' +illllllllllll + _ _1_ 1 \\ +'+'+p+_,_++ ++++; , !lllllllllllllllll \ __ ' /_- " _Gr_'_ " "1 " _ 1 k ' \ ....... E_tRIC_L 14 B l _¢¢ESS p_N[L i;'+"++, -- -8_Le LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW C0(X)55 UNIT 48GS030040/060 ELECTRICAL CHARACTERISTICS 208/230-34_0 Ib kg X CENTER OF GRAVITY IN. (MM) Y 280.0 127.3 35.02 (5893) 21.5 (546.1) 13,75 (349,3) 15.0 (381.0) UNIT WEIGHT UNIT HEIGHT IN. (MM) "A" Z 48GS036OR0i090 208/230-3_0, 460-3-50 320.0 145.1 37.02 (940.3) 22.5 (571.5) 14.0 (355.6) 13.0 (330.2) 48GS042060/090 208/230_34_0, 460-3-60 355.0 161.4 35.0_ (889.5) 21.5 (546.1) 13.5 (342.9) 13.0 (330.2) 48GX030040/060 208/230-3-60 313.0 142.0 39,02 (991,1) 22,0 (558,8) 15.3 (987.4) 17.6 (447.0) 48GX036060/090 208/230-3-60, 460-3-60 321.0 145.6 35.02 (989.5) 22.0 (558.8) 15.3 (387.4) 16.5 (419.1) Fig. 2_8GS030-042 and 48GX030-036 Unit Dimensions SUPPL_ D[TU_M 0P_WING 0pEWIN_ ! i i {4 t_: _ 3 TOP VIEW REAR VIEW REQUIRED CLEARANCE TO COMmJSTIBLE MAll. TOP OF UNIT ................................................................................ DUCT SIDE OF UNIT ........................................................................ SIDE OPPOSITE DUCTS ................................................................ ELECTRIC HEAT PANEL ................................................................ BO'[TOM OFUNIT...: ........................................................................ REI_IIRB) INCHES 14.00 2.00 14.0'3 tmm] 355.6 _50.8 [355.6 36.C_ 0.50 [914.4] 12.7] CLEARANCE FOROPERATION AND SERVICING INCHES [mm] 36.00 [914.0] 36.00 [914.0} EVAR COIL ACCESS SIDE ............................................................ POWER ENTRY SIDE .................................................................. (EXCEPT FOR NEE REQUIREMENTS) UNIT ....................................................................................... SIDE TOp OPPOSITE DUCTS ............................................................ DUCT PANEL ............................................................................... 48.00 1219.2 I 36.001914.0]1 12.00 [304.8] * NEE. REQUIRED CLEARANCES. INCHES BETWEEN UNITS, pOWER ENTRY SIDE .................................... 4200 UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ,3600 UNIT AND BLOCK OR CONCRETE WALLS AND OTHER GROUNDED SURFACES POWER ENTRY SIDE ......................... 4200 [mm] [1066.8] [914.0] *MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE. [1066.8] LEGEND CG - Center of Gravity COND Condensor EVAP Evaporator NEE National Electrical Code REQ'D Required Hs _ NOTE: Dimensions =e in in [mini .......... _ _ io _e] DI_ WOE[ _- ..... \,,,,, \ llllIllllllllllll m [....... r .. [5._II FRONT VIEW RIGIIT _DE VIEW C00056 ELECTRICAL UNIT CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT IN. (MM) Ib kg 460-3-60 415 188.6 38.98 (990.2) 208./230-3-60, 460-3-60 450 204.5 38.98 (990.2) 22 (558.5) 16 (406.4) 17 (432._ 208/230-3-60, 460-3-60 382 173.3 38.98 (990.2) 23.0 (584.2) 16.3 (412,8) 16.6 (421.6) 30 208/230-3-60, 460-3-60 421 191.0 38.98 (999.2) 21.5 (545.1) 16.6 (422.1) 18.0 (457.2) 48GX060090/115/1 30 208/230-3-60, 460-3-60 468 212.3 42.98 (1091.1) 23.5 (596.9) 15.3 (412.8) 17.6 (447.0) 48GS04809Q/115il 30 48GS060090H 15/130 48GX042060/090 48GX048090/115il 208/230-3-60, Fig. 3_48GS048-060 X CENTER OF GRAVITY IN. (MM) Y 22 (558.5) and 48GX042-060 Unit Dimensions 4 15 (406.4) Z 17 (432.0) VACunit ! _ii!_i_ iiiii!i!i!_i __Screw _.g nailer* _n f_ii_i FIasSuk __ piefdS t_do I I_11 _H" Insusttion(field field supplied -Du_ _l_ _fieldsupplied R_f Roof Curb for Small Cabinet Roof Curb for Note A:When unit mounting screw is used retainer bracket must also be used. Large Cabinet Note A:When unit mounting screw is used retainer bracket must also be used. \/ \ R/A \ Insulated deckpan S/A Gasket around duct /\ Gasket around outer edge _ N C00076 UNIT SIZE 48GS030-042 48GS048-060 48GX030-036 48GX042-060 CPRFCURB006A0O A IN.(MM) 8 (203) CPRFCURB007AOO 14 (356) 11(279) 11(279) CPRFCURB008A00 8 (203) 14 (356) 163/16 (411) 163/16 (411) ODS CATALOG NUMBER B IN. (MM) C IN. (MM) 161/2 (419) 161/2 (419) 17 3/8 (441) D IN. (MM) 29-3/4 28-3/4 40-1/4 (730) (730) (1022) CPRFCURB009A00 17 3/9 (441) 40-1/4 (1022) NOTES: 1. Roof curb must be set up for unit being installed. 2. Seal etdp must be applied, as required, to unit being installed. 3. Dimensions in ( ) are in millimeters. 4. Roof curb is made of 16-gage steel. 5 Table I sts only he d mensions, per part number that have changed. 6. Attach ductwork to curb flanges of duct rest on curb. 7. nsuated panals: 1-in. hickfibergass b density. 8. Dimensions are in inches. 9. Wl_en unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic conditions. This bracket is available through Micrometl. Fig. 4---Roof Curb Dimensions 2 Y 4 x 3 COO070 48GS CORNER # 48GX 030 036 042 048 060 030 036 042 048 060 1 53.2 59.7 67.5 78.9 85.5 59.5 61.O 72.6 80.0 88.9 2 50.4 56.5 63,9 74.7 81,0 56,3 57.8 68.8 75,8 84.2 3 86.8 97.3 110.1 128.7 139.5 97.0 99,5 118.4 130.5 145.1 4 89.6 106.5 113.6 132.8 144.0 100.2 102,7 122.2 134.7 149.8 TOTAL WEIGHT 250 320 355 415 450 313 321 382 421 465 Fig. 5_48GS and 48GX Unit Corner Weights J J MINIMUMHEIGHT: _" DETAIL A SEE DETAIL AJ EVAR COIL COND. COIL C99014 Fig. 6_Slab Mounting Details A05179 SIZE I""X'MU 'WE'k I 'nHT l in mrn UNIT 48GS GROUND MOUNT The unit may be installed either on a slab or placed directly on the ground if local codes permit. Place the unit prepared with gravel for condensate di_harge. on level ground 030 302 137.3 21.5 546.1 13,75 349.3 036 342 155.1 22.5 571.5 14,0 355.6 042 377 171.4 21.5 546.1 13.5 342.9 048 437 198.6 22.0 556.5 17.0 432.0 060 472 214.5 22.0 558,5 17.0 432.0 Step 3---FIELD FABRICATE DUC'FWORK Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to uniL For horizontal applications, unit is provided with flanges on the horizontal openings. Installation of flexible duct connector is recommended to prevent transmission of vibration and/or noise to structure. All UNIT 48GX 030 335 152 22.0 558.5 15.30 388.6 036 343 156 22.0 558.5 16.30 388.6 042 404 183 23.0 584,2 16.3 414,0 048 443 201 21.5 546.1 16.3 414.0 060 490 222 23.5 596.9 16.3 414.3 Fig, 7--Suggested Rigging Table 1--Physical Data--Unit 48GS UNIT SIZE 48GS 030040 030060 036060 036690 042060 NOMINAL CAPACITY (ton) 2½ 2½ 3 3 3½ OPERATING WEIGHT (lb.) COMPRESSORS Quantity REFRIGERANT (R-22) Quantity (lb.) 280 280 320 320 355 042090 31/2 355 Reciprocating 1 3.65 3,65 I 4.4 4.4 Acutrol REFRIGERANT METERING DEVICE Orifice ID (in.) CONDENSER COIL Rows...Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Clm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows...Fins/in. Face Area ($q ft) EVAPORATOR BLOWER Nominal Airflow (C/m) Size (in.) Motor HP (Rpm) 5.7 I 5.7 Device .034 .O34 .032 ,032 .O34 .O34 1...17 9.1 1...17 9.1 1...17 10.9 1...17 10.9 1...17 9.1 1...17 9.1 2400 22 1/8 (625) 2400 22 1/8 (825) 3000 22 _A(1100) 3000 22 ,_i (1100) 3000 22 _A (1100) 3000 22 2...15 3.1 2._15 3.1 3._15 3.1 3...15 3.1 4...15 3.1 4...15 3.1 1000 10 x 10 1/4(1075) 1000 10 x 10 1/4 (1075) 1200 11 x 10 1/2 (1075) 1200 11 x 10 1/2 (1075) 1400 11 x 10 1400 11 x 10 3/4 (1076) 3/4 (1075) 2-.46 2...38 2...46 3_,38 3...46 20 X 20 20 X 24 20 X 24 FURNACE SECTION* Burner Orifice No. (Qty...Orill Size) Natural Gas Burner Orifice No. (Qty.-Drill Size) Propane Gas 2...45 2...50 RETURN-AIR FILTERS (in.)t Throwaway • Basedonaltitudeof 0 to 2000 It. TM 2...38 20 x 20 (11oo) 2...3_ 3...38 2...46 3...46 20 x 24 20 X 24 i" Required filter sizes shown are based on the larger of the AR] (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating ain'low velocity of 300 if]minute for throwaway type or 450 ft]rninute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg. ductwork should proof all external flashing be secured to the flanges. Insulate and weatherductwork, joints, and roof openings with counter and mastic in accordance Ducts passing and covered through with applicable an unconditioned codes. space must be insulated with a vapor barrier. If a plenum return ducted through is used on a vertical the roof deck to comply unit, the return should be with applicable A minimum clearance is not required around return-air static shall not exceed -.25 in. wg. Step 4--PROVIDE The required operating Step 5--RIG AND PLACE UNIT Cabinet support the additional and service clearances are shown in Fig. 2 and 3. Adequate combustion, ventilation and condenser air must be provided in accordance with section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code ANSI (American provisions carpeting, tile, or other combustible materialS. The unit may be installed on wood flooring or on Class A, B, or C roof covering materials. fire codes. ductwork. CLEARANCES minimum Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install die unit on National Standards Institute) Z223.1 or applicable of local building code. In Canada, follow sections 7.2, 7.3, or 7.4 or Can/CGA. (Canadian Gas Association) Installation Codes or applicable provisions of local building B149 code. Use spreader bars or crate top when rigging the unit. The units must be rigged for lifting (See Fig. 6). Refer to Table 1 and 2 for operating weight. Use extreme caution to prevent damage when moving the unit. Unit must remain in an upright position during all rigging and moving operatiottv.The unit must be level within 1/4"' for proper condensate drainage; therefore, the ground-level pad or accessory roof curb must be level before setting die unit in place. When a field-fabricated support is used, be sure that the support is level and properly supports die unit. Lifting point should be directly over the center of gravity Step 6--CONNECT compressor weight. for the unit. CONDENSATE DRAIN NOTE: When installing condensate drain connection be sure to comply with local codes and restrictions. life. The condenser fan pulls air through the condenser coil and discharges it through the top cover. Be sure that the fan discharge does not recirculate to the condenser coll. Do not locate the unit in Models 48GS either Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground- a corner or under a partial an overhead overhang obstruction. (such The minimum clearance under as a normal house overhang) extension is 48-in. above the unit top. The maximum horizontal of a partial overhang must not exceed 48-in.. and 48GX dispose of condensate 3/4 in. NPT fitting which exits through panel (See Fig. 2 and 3 for location). water through the compressor a access level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that Table 1--Physical Data--Unit 48GS (Continued) UNIT SIZE 48GS 048090 048115 048130 060090 NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb.) COMPRESSORS Quantity REFRIGERANT (R-22) Quantity (lb.) 4 415 4 415 4 415 5 450 Scroll 1 6.0 I 6.0 060115 5 060130 5 450 450 Reciprocating 1 ! 6.0 8.0 I g° I 60 Acutrol Device REFRIGERANT METERING DEVICE Orifice ID (in.) CONDENSER COIL Rows.- Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows._Fins/in. Face Area (sq It) EVAPORATOR BLOWER Nominal Airflow (Cfm) Size (in.) Motor Hp (Rpm) FURNACE SECTION* Burner Orifice No. (Qty._Drill Size) Natural Gas Burner Orifice No. (Qty...Drill Size) Propane Gas .O32 .032 .032 ,030 ,030 .030 1...17 12,3 1,,,17 12.3 1..,17 12.3 2...17 12.3 2-,17 12.3 2...17 12.3 3600 22 3600 22 !4 (1100) 3600 22 1,4(1100) 3600 22 1,4(1100) 3...15 4.7 3...15 4.7 3...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 1600 11 x lO 3/4 (1075) 1600 11X10 314 (1075) 1600 11X10 3/4 (1075) 2000 11X10 1.0 (1075) 2000 11 X 10 1.0 (1075) 2000 11 X 10 3...38 3.,.46 3.-33 3...42 3...31 3...41 3...38 3...46 24X30 24X30 1A(11o0) RETURN-AIR FILTERS (in.)t Throwaway * Basedon altitudeof0 to 2000 ft. 24X30 24X30 3600 22 1,4(1100) 36OO 22 t4 (110o) 1.0(1075) 3...31 3...41 3,,,33 3...42 24 X 30 24 X 30 t Required filter sizes shown are based on the larger of the ARI Air Conditioning and Refrigeration Institute) rated cooling airflow or the hea ing a rf ow ve oclty o 300 Wrn nste or throwaway type or 450 if/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg, the oudet of the trap is at least 1 in. lower than the drain pan NOTE: Dedicated low NO_ models MUST condensate connection to prevent the pan from overflowing (See Fig. 8). Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit. fornia Air quahty exists. If the installation (NO,) emissions requirements shipped from the factory. requires draining the condensate water away from the unit, install a 2-in. trap at the condensate connection to ensure proper drainage (See Fig. 8). Make sure that the outlet of the trap is at hi&st 1 in. lower than the drainpan condensate connection. This prevents the pan from overflowing. These models Management Districts meet the California be installed in Cali- where a Low NO_ rule maximum oxides of nitrogen of 40 nanograms/joule or less as NOTE: Low NO. requirements ap-ply only to natural gas installations. Prime the trap with water. Connect a drain tube -using a minimum of 3/4-in. PVC or 314-in. copper pipe (all field-supplied) - at the outlet end of the 2-in. trap. Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1-in. for every horizontal run. Be sure to check the drain tube for leaks. 10 R of TRAP OUTLET Install the flue hood as follows: 1. This ir_tallation must conform with local building codes and with the National Fuel Gas Code (NFGC), ANSI Z223.1 (in Canada, CAN/CGA B149.1, Fire Protection Association) 2" i rain. 2. Remove q t C00009 Fig. 8--Condensate Step 7--INSTALL Trap FLUE HOOD The flue hood assembly is shipped cial and local plumbing applicable local codes. screwed to the coil panel in the the service access panel to or wastewa_r flue hood from shipping compartment). location Place vent cap assembly codes and other (inside the blower over flue panel. Orient screw holes in vent cap with holes in the flue panel. 3. Secure flue hood to flue panel by inserting a single screw on the right side and the left side of the hood. Step 8---INSTALL indoor blower compartment. Remove locate the assembly (See Fig. 27). and B149.2) or NFPA (National latest revision. Refer to Provin- GAS PIPING The gas supply pipe enters the unit through the access hole provided. The gas connection to the unit is made to the 1/2-in. FPT gas inlet on the manual shutoff or gas valve. Table 2--Physical UNIT SIZE 48GX 030040 030060 NOMINAL CAPACITY (ton) 2½ 313 2½ 313 OPERATING WEIGHT (lb.) COMPRESSORS Quantity REFRIGERANT (R-22) Quantity (lb.) REFRIGERANT METERING DEVICE Orifice ID (in.) CONDENSER COIL Rows.-Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Ctm Diameter (in.) Motor Hp (Rpm) EVAPORATOR COIL Rows...Fins/in. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm) Size (in.) Motor Hp (Rpm) FURNACE SECTION* Burner Orifice No. (Qty.-Drill Size) Natural Gas Burner Orifice No. (Qty...Dri0 Size) Propane Gas Data--Unit 48GX 036060 042060 _6060 3 3 321 042090 3½ 3½ 382 382 _roll 1 4.4 4.4 5.2 5.2 6.4 6.4 .030 .030 .032 .032 .034 .034 1...17 12.7 1...17 12.7 2...17 9.1 2...17 9.1 2...17 12.3 2...17 12.3 2350 22 2350 22 2350 22 2350 22 3300 22 3300 22 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 1/8 (825) 3...15 3.1 3...15 3.1 3...15 3.7 3...15 3.7 3...15 4.7 3...15 4.7 106O 10x10 1/4 (1075) 1006 lOX10 1/4 (1075) 1200 11 X 10 1/2 (1075) 1200 11X10 1/2 (1075) 2...44 2,,.50 RETURN-AIR FILTERS (in.)t Throwaway • Based on altitude of 0 to2000 ft. 20 X 20 1400 11X 10 3/4 (1075) 2...38 2,,,38 3,,,38 2..,38 2...46 2...46 3,,,46 2..,46 20 X 20 20 X 24 20 X 24 1400 11X 10 3/4 (1075) 3...38 3...46 24 X 30 24 X 30 f Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 if]minute for high-capacity type. Air riser pressure drop for non-standard filters must not exceed 0.08 in. wg. Install a gas supply line that runs to the heating section. Refer to Table 3 and the NFGC for gas pipe sizing. Do not use cast-iron pipe. It is recommended that a black iron pipe is used. Check the local utility for recommendations concerning existing tines. Size gas supply piping for 0.5 in. wg maximum pressure drop. Never use pipe smaller than the 1/2-in. FPT gas ial_'t on the unit gas valve. For natural gas applications, the gas pressure at unit gas connection must not be less than 4.0 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 7.0 in. wg or greater than 13 in. wg at the unit connection. An l/8-in. NPT plugged tapping, accessible tion, must be installed immediately connection to the gas valve. for test gage connec- upstream pertinent CAN/CGA B149.1, (2)-M86). In codes, adhere to the following recommendations: 1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in. in every 15 ft to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter. 2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, bangers, etc. Use a minimum of one hanger every 6 ft. For pipe sizes larger than l/2 in., follow recommendations of national codes. 3. Apply joint compound (pipe dope) sparingly and only to male threads of jc;mt when making pipe connections. Use only pipe dope that is resistant to action of liquefied by local and/or national codes. Never use Teflon tape. 4. Install sediment trap in riser leading to heating _ction (See Fig. 9). This drip leg functions a.s a trap for dirt and condensate. 5. Install an accessible, external, gas supply pipe within 6. Install ground-joint unit manual shutoff 7. Pressure-test national unit. all plumbing manual main shutoff 6 ft of heating valve in section. union close to heating section between and external manual main shut-off valve. gas and piping gas in codes accordance before with connecting local and piping to of the gas supply When installing the gas supply fine, observe local codes pertaining to gas pipe installations. Refer to the NFGC ANSI Z223.1-1988 NFPA latest edition (in Canada, the absence of local building specified petroleum gases as NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systero_s when test pressure is in excess of 0.5 palg. Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig. The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union. Wl E_ Unstable manifold operation may occur when the gas valve and assembly are forced out of position while connect- ing improperly-routed rigid ga_s piping to the gas valve. Use a backup wrench when making connection to avoid strain on, or distortion of, the ga._ control piping. Table 2--Physical UNIT SIZE 48GX NOMINAL CAPACITY (ton) OPERATING WEIGHT (lb.) COMPRESSORS Quantity Data--Unit 48GX (Continued) 048090 4 048115 4 048130 4 060090 5 060115 5 060130 5 421 421 421 468 468 468 3.1 8.1 Scroll 1 REFRIGERANT (R-22) Quantity (lb.) 8.3 REFRIGERANT METERING DEVICE Orifice ID (in.) I 03 I 83 r 81 I Acutml Device CONDENSER COIL Rows...Fins/in. Face Area (sq ft) CONDENSER FAN Nominal Cfm Diameter (in,) Motor Hp (Rpm) EVAPORATOR COIL Rows,,.Finslin. Face Area (sq ft) EVAPORATOR BLOWER Nominal Airflow (Cfm) Size (in.) Motor Hp (Rpm) FURNACE SECTION* Burner Orifice No. (Qty...Drill Size) Natural Gas Burner Orifice No. (Qty...Drill Size) Propane Gas .O34 .034 .034 ,032 .032 .O32 2...17 12.3 2...17 12.3 2...17 12.3 2...17 16.4 2-.17 16,4 2...17 16.4 33O0 22 ¼ (1100) 3300 22 _A(1100) 3300 22 _A(1100) 3300 22 ¼ (1100) 3300 22 3300 22 (1100) 4...15 4.7 4...15 4.7 4...15 4.7 4...15 4.7 1600 11X 10 3/4 (1075) 1600 11X10 3/4 (1075) 1600 11X10 3/4 (1076) 1750 11X10 1,0 (1075) 3...33 3...42 3,,.31 3...41 3.-38 3...46 24X30 24X30 24X30 3,..38 3..,46 RETURN-AIR FILTERS (in.)t Throwaway 24 X 30 1A (1100) ' 4...15 4.7 4...15 4.7 1750 11X 10 1.0 (1075) 1750 11 X 10 1.0 (1075) 3...42 3...31 3,,.41 24 X 30 24 X 30 3.,.33 • Basedonaltitude of 0 to 2000 ft. _"Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 if/minute for high-capacity type. Air tilter pressure drop for non-standard filters must not exceed 0.08 in. wg. Table 3_Maximum NOMINAL IRON PIPE, SIZE (IN.) ½ Gas Flow Capacity* INTERNAL DIAMETER LENGTH OF PIPE, FTt (IN.) 10 .622 175 120 97 82 73 66 61 57 1 11A ,824 1.049 1.380 360 680 1400 250 465 950 200 375 770 170 320 600 151 285 580 138 260 530 125 240 490 118 220 460 11A 1,610 2100 1460 1180 990 900 810 750 690 650 ¾ 20 30 40 50 __apacity_fpipeincu__fgasperhrf_rgaspressure_f__5psig_r_ess_Pressuredr_p____5-in_wg Fire Protection Association NFPA 54. 60 70 80 90 100 126 150 53 50 44 40 110 205 430 103 195 400 620 basedona0.60speci 175 200 93 I 84 175 i 160 i 360 I 325 77 145 300 135 550 460 i 500 cg a',,itygas) Ree oTabeC_l 72 230 430 National f This length includes an ordinary number of fittings. Step 9--INSTALL DUCT CONNECTIONS The unit has duct flanges on the supply- and return-air openings on the side and bottom of the unit. For downshot applications, the ductwork connects to the roof connections sizes and locations). casing. CONFIGURING CHARGE serious injury curb (See UNITS FOR DOWNFLOW Fig. 2 and 3 for (VERTICAL) DIS- or death. cause serious 8. Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use soap-and-water solution codes and/or regulations). (or method specified injury or death. 1. Open all electrical work. by local 10 disconnects before starting any service IN I 3"MIN I C99020 Fig. 9_Sediment 2. Remove Trap DUCTCOVERSREMOVED return duct cover located on duct panel by breaking connecting & 10B). tabs with screwdriver and a hammer (See Fig. 10A C99012 Fig. 10B--Vertical Duct Cover Removed 3. To remove supply duct cover, break front and tight side connecting tabs with a screwdriver and a hammer. Push louver down to break rear and left side tabs (See Fig. 10A & 10B). 4. If unit ductwork is to be attached on the unit composite at this time. to veztical opening base (jackstand applications 7. After completing unit conversion, and power up unit. flanges only), do so air conditioning 90A or residence-type, ordinances. Adhere to the installing that the unit base insulation perimeter of the vertical return-air opening unit base with aluminum tape. Applicable require aluminum tape to prevent 6. Cover both horizontal the accessory watertight. duct duct openings cover exposed around following criteria for horizontal 2. Select and size ductwork, is air- and ventilating 90B; and/or when systems, local selecting, NFPA codes and sizing, and the duct system: 1. Units are shipped duct covers). fiberglass. opening NFPA the be secured to the local codes may duct installation supply-air registers, (by removing and return-air grilles according to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) recommendadons. with the duct covers from kit. Ensure all safety checks NOTre: The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of nonresidence-type 5. It is recommended perform and 3. Use flexible prevent transition transmission screwed or bolted ensure weathertight - t .I between rigid of vibration. ductwork The to duct flanges. Use and airtight seal. and unit to transition suitable may be gaskets to 4. All units must have field-supplied filters or accessory fdter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Tables 1 and 2. 5. Size all ductwork heating or cooling) size increases for maximum required airflow (either for unit being installed. Avoid abrupt duet or decreases or performance may be affected. 6. Adequately insulate and weatherproof all ductwork outdoors. Insulate ducts passing through unconditioned located space, and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors of America (ACCA) minimum installation standards for heating and air ,=T--- conditioning SUPPLY DUCT OPENING 7. RETURN DUCT OPENING Flasli, building building C99011 Fig. 10A Supply and Return Duct Opening 11 systems. weatherproof, structure practices. Secure all ducts to building and vibration-isolate in accordance structure. all openings with local codes in and good Step 10--INSTALL ELECTRICAL CONNECTIONS /_ HIGH VOLTAGE r._l LI"/_ -'1,'I I",[_ r - - - (SEE UNIT WIRING POWER LEADS l_ _oLABEL) The unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of serious injury if an electrical fault should occur. This ground may consist of an electrical rare connected to the unit ground FIELD-SUPPLIED FUSED DISCONNECT lug in the GND control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI/NFPA (latest edition) and local electrical codes. In Canada, follow Canadian Electrical Code CSA (Canadian Standards Association) C22.1 and CONTROL II _GRN_(G_) local POWER electrical codes. Failure to adhere to this warning in serious BOX could re.cull (SEE UNIT LOW-VOLTAGE WIRING LABEL) injury or death. _yEpIRc_A_O _TAT LEADS_ _i SPLICE BOX C99018 Failure to follow these precautions could result in damage the unit being installed: 1. Make all electrical connections Fig. 11--High- and Control-Voltage connections to SPECIAL in accordance ANSI/NFPA (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian codes. Electrical Code Refer to unit wiring Part 1 and applicable local unit and install lockout tag. Electrical Injury or death. diagram. CONTROL minimum) Standard electrical service switch mounted (See Tables 4 and 5 for electrical data). Run the low-voltage Locate five 18-gage 2. Connect ground ground 4. Connect field compressor 5. Connect to black wire on connection through the inlet splice box. wires leaving ANTICIPATOR The room thermostat control box. These low-voltage SETTING heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an ammeter between the W and R terminals to determine the exact to the lines side 11 of the contactor. field wire L2 to yellow wire on connection compressor 6. Connect L1 leads from the thermostat, box and make low-voltage connections (See Fig. 11). Secure all cut wires, so that they do not interfere with operation of unit. leads into the connection. 3. Locate the black and yellow wires connected of the contactor. a drip loop before to be routed into the low-voltage splice box (located below fight side of control box). Route leads through hole in bottom of control HEAT lead to chassis with unit) and install Provide connection leads can be identified by the colors red, green, yellow, brown, and white (See Fig. 11). Ensure the leads are long enough to the unit. (LI, L2, L3) and ground packet (included hole, and into unit low-voltage See unit wiring label and Fig. 11 for reference when making high voltage connections. Proceed as follows to complete the high- I. Run the high-voltage control box. wires. grommet in the knockout opening. running wire through panel. location). connections Unit control Connection grommet from the installer's The lleld-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used (See Fig. 2 and 3 for acceptable voltage thermostat. Remove knockout hole located in the flue panel adjacent to the control access panel (See Fig. 2 and 3). Remove the rubber with a fieldat, or within sight from, the unit. Refer to the unit rating plate for maximum fllse/circdit breaker size and minimum circuit amps (ampacity) for wire sizing CONNECTIONS more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35 C imbalance. a separate disconnect shock can cause serious Use no. 18 American Wire Gage (AWG) color-coded, insulated (35 C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located CONNECTIONS The unit must have supplied, waterproof, VOLTAGE Do not use any type of power-stealing problems may result. any panel to mount electrical hardware, conduit, etc. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper HIGH-VOLTAGE OPERATION Before making any wiring changes, make sure the gas supply is switched off first. Then switch off the power supply to the 3. Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. 4. Do not damage internal components when drilling through and/or phase FOR 208-V r!_kvl:1:]_llTI 2. Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE. voltage PROCEDURES with NEC required _tdng. NOTE: For thermostat approximate required anticipator adjustment fort to the occupants 13 of the contactor. selection purposes, use 0.18 amp for the setting. Failure to make a proper heat will result in improper operation, discomof the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation. field wire L3 to Blue wire from compressor. 12 Table 4--Electrical UNIT SIZE 46GS 030 O36 042 O48 O60 V-PH-HZ VOLTAGE RANGE COMPRESSOR Data--Unit 48GS OUTDOOR FAN MOTOR INDOOR FAN MOTOR POWER SUPPLY Min Max RLA LRA FLA FLA MCA 208/230-3-S0 187 253 12.6 13.2 187 253 9.0 0.8 1.6 2.0 208/230-3--60 68.0 78.0 Max Fuse or Ckt Bkr 20 460-3-60 414 506 4.5 40.0 0.9 3,6 1.9 16,5 8.4 25 15 208/230-3-60 187 253 10.7 85.0 1.6 3.8 18.8 25 460-3-60 414 506 5.3 42.0 0.9 187 253 13.5 1.6 0.9 2.0 3.8 9.5 22.3 15 35 2.0 11.3 15 6.2 3.2 31.1 14.7 45 20 208/2_0 460-3-60 414 506 6.7 108.0 47.5 208/230-3-60 187 253 18.6 125.0 1.6 460-3-60 414 506 8,5 66.5 0.9 EXAMPLE: Supply voltage is 460-3-60. A S C AB = 452 v AC = 455 v MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection RLA -- Rated Load Amps CKT BKR -- Circuit Breaker Average Voltage = 452 + 464 + 455 3 BC = 464 v = 1371 3 = 457 _" NOTES: 1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 436 and 440), the overcurrent protective device for the unit shall be Power Supply fuse. Canadian units may be fuse or circuit breaker. 2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. Determine maximum deviation from average voltage. (AB) 457 452=5v (BC) 464 457=7v (AC) 457 455=2v Maximum deviation is 7 v. Determine percent of voltage imbalance. % Voltage Imbalance = 100 x 7 457 -- 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. % Voltage imbalance = 100 x max voltage deviation from average voita_le average voltage I IMPORTANT: If the supply voltage phase imbalance is immediately,more than 2%, contact your local electric utility company 13 Table 5_Electrical UNIT SIZE 48GX V-PH-HZ 030 036 042 O48 O60 VOLTAGE RANGE Data_nit COMPRESSOR 48GX OUTDOOR FAN MOTOR INDOOR FAN MOTOR POWER SUPPLY RLA LRA FLA FLA MCA 253 9.0 63.0 0.8 2.1 14.2 Max Fuse or Ckt Bkr 20 253 11.2 75.0 0.8 3.6 18.4 25 414 506 5.4 37.5 208/230-3-60 187 253 12,4 88,0 0,9 1.6 1.9 4.1 9.6 21.2 15 30 460-3_0 208/230-3_0 414 187 506 253 6,1 13.0 44.0 93,0 0.9 2.0 10.5 15 1.5 4.1 21.9 30 Min Max 288/230_3_0 187 2O6/23_0 187 460-3-50 460-3-60 414 506 6.4 46.5 0.9 1.9 10.8 15 208/230-3-60 187 253 17.3 123.0 460-3_$0 414 506 9.0 62,0 1.6 0,9 6.2 3.2 29.4 15.4 45 20 EXAMPLE: Supply voltage is 460-3-60, A e c AB = 452 v FLA -- Full Load Amps LRA -- Locked Rotor Amps C LEGEND MCA -- Minimum Circuit Amps MOCP -- Maximum Ovemurrent Protection RLA -- Rated Load Amps CKT BKR -- Circuit Breaker AC = 455 v US Average Voltage = 452 + 464 + 455 3 BC = 464 v = 1371 3 = 457 NOTES: 1. In compliance with NEC (National Electrical Code) requirements for muitimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent prote_ive device for the unit shall be Power Supply fuse. Canadian units may be fuse or circuit breaker. 2. Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, determine size from NEC. 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imba/ance in supply volt= age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. Determine maximum deviation from average voltage. (AB) 457 452=5v (BC) 464 457=7v (AC) 457 455=2v Maximum deviation is 7 v. Determine percent of voltage imbalance. 7 % Voltage Imbalance = 100 x -457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. % Voltage imbalance = tOO x max voltage deviation from average voltage average voltage IMPORTANT:olf the supply itmnOmredlhataer_y2 %, contact your voltage phase imbalance is local electric utility company C99024 Table 5_Legend 14 TRANSFORMER PROTECTION the "OFF" position: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the The transformer is of the energy-limiting type. It is set to withstand a 30°sec. overload or shorted secondary condition. ground joint PPdE-START-UP union be loosened, and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines into a combustion chamber. Immediately upon detection of gas odor, retighten the union. Allow 5 Failure to observe the following serious injury: 1. Follow recognized safety warnings practices could result and wear in minutes compressor terminal cover c. Ensure and fan hub is 1/8 in. maximum from motor housing (See Fig. 12). 3. Do not remove compressor terminal cal sources are disconnected. 4. Relieve touching is in place then light unit. b. Make sure that condenser-fan blade is correctly positioned in fan orifice. Leading edge of condenser-fan blade should be 1/2 in. maximum from fan orifice ventari. protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless secured. to elapse, cover until all electri- and recover all refrigerant from system before or disturbing anything inside terminal box ff refrigerant leak is suspected around compressor terminals. 5. Never attempt to repair soldered connection while refrigerant system is under pressure. 6. Do not use torch to remove contains oil and refrigerant component, wear protective lows: a. Shut off gas supply any componenL System under pressure. To remove a goggles and proceed as fol- and then electrical b. Relieve and recover all refrigerant both high- and low-pressure ports. MOTORAND FANHUB C99009 Fig. 12--Fan Blade Clearance power to unit. from system MOTORSHAFT using c. Cut component connecting tubing with tubing cutter remove component from unit. and d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. Proceed as follows to inspect and prepare the unit for initial startup: 1. Remove access panel. 2. Read and follow instructions and INFORMATION 3. Make the following a. Inspect lines, on all WARNING, labels attached CAUTION, to, or shipped with, unit. inspections: for shipping and handling loose parle, disconnected damages such as broken wires, etc. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. c. Leak test all refrigerant tubing connections using electronic MANIFOLD leak detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, see the Check for Refrigerant Leaks section. d. Inspect all field- and factery-wirlng connections. that connections are completed and tight. e. Ensure wires do not contact refrigerant tubing C99019 Fig. 13_Burner Be sure d. Make sure that air falter(s) is in place. e. Make sure that condensate or sharp sheet metal edges. the following Assembly drain trap is filled with water to ensure proper drainage. f. Inspect coil f'ms. If damaged during shipping carefully straighten fins with a i'm comb. 4. Verify PIPE PLUG f. Make sure that all tools and miscellaneous been removed. and handling, conditions: loose parts have START-UP Step I_CHECK FOR REFRIGERANT LEAKS Proceed as follows charge the unit: to locate and repair a refrigerant leak and to 1. Locate leak and make sure that refrigerant system pressure has been relieved and reclaimed from beth high- and low-pressure por_. a. Make sure gas line is free of air. Before lighting the unit for the first time, perform the following with the gas valve in 2. Repair 15 leak following Refrigerant Service procedures. CHECK BURNER FLAME Check Table BURNER GAS INPUT gas input and manifold 6). If adjustment D after unit start-up proceed (See as follows: • The rated gas inputs shown in Table 6 are for altitudes from sea level to 2000 fit above sea level. These inputs are based on natural gas with a heating value of 1050 Btu/ft 3 at 0.65 specific gravity, or propane gas with a heating value of 2500 Btu/ft 3 at • For elevations 1000 ft above • When the ga.s supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size. 1.5 specific _IANIFOL pressure is required gravity. above 2000 ft, reduce input 4 percent sea level for each C99021 Fig. 14_Monoport NOTE: Install a f-alter drier whenever for repair. 3. Add a small charge leak-test unit. Burner the system has been opened of R-22 refrigerant vapor to system ADJUST and The gas input to the unit is determined 4. Recover refrigerant from refrigerant system and evacuate 500 microns if additional leaks are not found. to for required charge. Be sure compensate for internal volume to add extra of falter drier. HEATING AND refrigerant MAKE by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure must be measured to determine the input of 5. Charge unit with R-22 refrigerant, using a volumetriccharging cylinder or accurate scale. Refer to unit rating plate Step 2--START-UP MENTS GAS INPUT to propane ga_s units. Measure Gas Flow (Natural Gas Units) Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained ADJUST- between 3.4 and 3.6 in. wg. If larger adjustments are required, change main burner orifices following the recommendations of national and local codes. NOTE: Do not jumper Make sure any safety devices that burner when operating OFLfices are properly operation may occur when the burner orifices misaligned. the unit. aligned. turned Unstable in the manifold Proceed are Follow the fighting instructions on the heating section operation label (located inside the burner or blower access door) to start the heating HEATING access that use the same meter must be at the meter. as follows: to unit. 2. Remove on manifold pipe plug (See Fig. 13) and connect Turn on gas supply to unit. 3. Record number of seconds for gas meter test dial to make one revolution. and that all 4. Divide number of seconds seconds in one hour). CONTROL 5. Multiply Start and check the unit for proper heating control operation as follows (see furnace fighting instructions located inside burner or blower appliances 1. Turn off gas supply manometer. section. NOTE: Make sum that gas supply has been purged, gas piping has been checked for leaks. CHECK All other off when gas flow is measured 3. The induced-draft of the thermostat heating above EXAMPLE: the main burner should 5. The evaporator Assume 2. 3600+ 32= one value of the gas is 1050 one revolution. 112.5. 3. 112.5 x 1 =112.5 ft 3 of gas flow/hr. 4. 112.5 x 1050 = 118,125 break the 24-v power to W. fan will turn on 45 sec. after the flame of cu fit shown for one of gas flow per hour. that the size of test dial ks I cuft. 1. 32 sec. to complete light within 5 see. If the burners do not fight, there is a 22-see. delay before another 5-sec. try. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, of value of gas is not known). revolution takes 32 sec., and the heating Btu/ft 3. Proceed as follows: motor will start. 4. After a call for heating, of test dial to obtain cuft (number 6. Multiply result of Step 5 by Btu heating value of gas to obtain total measured input in Btuh. Compare this value with heating input shown in Table 6 (Consult the local gas supplier if the 1. Place room thermostat SYSTEM switch in the HEAT position and the fan switch is placed in ALrrO. position. control result of Step 4 by the number revolution panel): 2. Set the heating temperature room temperature. in Step 3 into 3600 Btuh input. If the desired gas input is 115,000 Btuh, only a minor change in the manifold pressure is required. has been established. The evaporator fan will turn off 45 sec. after the thermostat has been satisfied. Observe input: 16 manifold pressure and proceed as follows to adjust gas W4.3 BLK FIELD OFM SUPPLY POWER 10ONLY) EQUIP GMG COMP W56 BLU[SEE NOTE #4)_ W59YEL-- IFM W64YEL-W15YEL COOLINGFANLOGIC r T+30 G G ENERGIZED DEFNERGIZED IDM TRAN1 HEAtiNGFANLOGIC I I o 45 • T+3O W BR W BR ENERGIZED DE B_ERG[ZED W46 BRN-- % % OFF HEAT I B THI AHA _HEAT OAUTO _CCO TCl YI FAN G ON FIELD=THERMOSTAT COMMON -- W30 BRNLEGEND UNIT COMPONENT ARRANGEMENT SEGTION OLFDCORFAN [] EQUll G_D COMPRESSORINBOORFAN SECTION CQMp " _ECTION [_ CO_TROLBOX _ 24V L_PLICE_) [BN _AS SECTIOf_ DISCONNECT PER NEC AHA - BR C CAP COMPCR CS EQUIPFS FU GND GV GVR HS HV TRAN ] IDM IFC IFM IGC - L1 LS LS1 MGV - - Adjustable Heat Anticipator Blower Relay Contactor Capacitor Compressor Motor Combustion Relay Centrifugal Switch Equipment Flame Sensor Fuse Ground Gas Valve Gas Valve Relay Hall Effect Sensor High Voltage Transformer Ignitor inducab-Oraft Motor In.or-Fan Co_tactor Indoor-Fan Motor Integrated Gas Unff Controller Line Limit Switch Limi_ Switch Main Gas Velve NEC - ORe QT RS SEN SW TRAN - _ Reid Splice _ Terminal(Marked) _ ---.... _ National Electrical Code Outdoor-Fan Motor QuabrupleTerminel Rollout Switch Sensor Switch Transformer O Terminal (Unmarked) _ Splice -- - -- - Splice (Marked) FactoryWidng I_eld Contro_ Wiring Reid Power Wiring Accessory or Ol_ional Wiring To Indicate Common Potential Oely, Not toRedrcsentWiring NOTES: 1. If any of the odginel wires furniabed are reol_ced, thay must be replaced with type 90 degree C wire or its equivalent. 2. Seepricopagesforthermostatandsubbases. 3. Use 75 degree C copper conductors for field installation. 4. For high speed IFM, dis_3nnect RED wire from IGC terminal BM and connect BLK w_re from IFM, For medium speed, disconnect RED wire from IGC terminal BM and connect BLU wire from IFM. C00058 Fig. 15_208/230-3-60 Wiring Diagram, Units 48GS and 48GX ]7 F,ELO c I W45 BLK BLK CAP 2 E ,P_QMO --'/// l WO BLK L__ (060ONLY) % L3- \ N, / coMP IFM wB,YEL -W64 YEL --W15YEL --W14 FAN LOGIC BRN W56 BLU (SEE NOTE #4) - COGUNG YEL W5 YEL CAP 1 PRIMARY BLK Q BR 460V Vl0 r IDM G G ENERGIZED D_NW_IGIZED /_,_i _ I_BRN HEATING WOI L(3GIC ENERG_I_t _GRN YEk W46 BRN-- _-ENERGtZED CR --W13 1 RH BLK-- 24V SPUCE BR --W39 IGC RED _]_ Wl 9 WHT W20 GRN OFF -_ _HEAT II ° _LrrO _ i W21 RED _ II TCI ",'1 I I I --1 I MGV II I! II --W35 GRA_ FLt_E SEN --VEL--O I ON FIELO'THERMOSTAT I '- .......... _ --Wa2BRN-- m I I W33 YEL COMMON ill W30 BRN" LEGEND AHA COMPONENT SECTION FAN OUTDOOR ARRANGEMSNT [] EQUIF GND _,OMPRESN)R rNNXIRFAN SEC17ON SECTION _ _BOLBOX _ 24V °0 [] _ASSECTION DISCONNECT pERNEC - Adjustable Heat Anticipator BR - Blower Relay C - Contactor CAP - Capacitor COMPCompressor Motor CR - Combustion Relay CS - Cen_'ffugaJ Switch EQUIPEquipment FS l Rame Sensor FU - Fuse GND - Ground GV GVR HS HV TRAN I IDM IFC IFM IGC l - L1 LS LS1 MGV - l UNIT - Gas Valve Gas Valve Relay Hall Effect Sensor High VoRage Transformer Ignitor Inducod-Draft Motor ladoor-Fan Contactor Indoor-Fan Motor Integrated Gas Unit Controller Line Limit Switch Limit Switch MelnGasValve NEC - OFM QT RS SEN SW TRAN - _ Field Splice _ Terminal (Marked) _ ---.... -- National Bectdcal Code Outdoor-Fan Motor QuedrupleTerminal Rollout Switch Sensor Switch Transformer C) Terminal (Unmarked) • Splice -- - -- - Splice(Marked) FactoryWidng Reid Con_rolWiring Field PowerW_ring Accessory or Op5onal Widng TO Indicate Common Potential Only, Not teRepresentW_ring NOTES: 1. ff any of the original wires furnished ara replaced, they must be replaced with type 90 degree C wire or Its equivalent 2. See price pages fo_thermostat and subbase_ 3.. Use 75 degree copper conductors field installation. For high speed C IFM, disconnect RED for win_ from IGC terminal BM and connect BLK wlre from IFM. For medium speed, disconnect RED wire from IQC terminal BM and cennect BLU wire from IFM. C00059 Fig. 16_460-3-60 Wiring Diagram, Units 48GS and 48GX Table 6_Heating HEATING INPUT (BTUH)* NUMBER OF ORIFICES 40,000 Inputs GAS SUPPLY PRESSURE (IN. WG) Natural MANIFOLD PRESSURE (IN. WG) Propanel" Min Max Min Max 2 4.0 13,0 4.0 13.0 60,000 90,000 2 3 4.0 4.0 13.0 13.0 4.0 4.0 13.0 13,0 115,000 3 4.0 13.0 4.0 130,000 3 4.0 13.0 4.0 Natural 3.5 Propane," 3.5 3.5 3.5 13.0 3.5 3.5 3.4 3.7 13.0 3.5 3.5 • When a unit is converted to propane, different size orifices must be used. See separate, natural4o-propene conversion kit instructions. f Based on altitudes from sea level to 2000 It above sea level. For altitudes above 2000 It, reduce input rating 4 percent for each additional 1000 It above sea level. in Canada, from 2000 It above sea level to 4500 It above sea lev_, derato the unit 10 percent. 1. Remove valve. cover screw over regulator 2. Turn regulator adjustment screw input, or turn regulator adjustment adjustment AIRFLOW screw on gas clockv4se to increase screw counterclockwise AND TEMPERATURE RISE The heating section for each size unit is designed and approved for hearing operation within the temperature-rise range stamped on the gas to unit rating plate. decrease input. Manifold pressure must be between 3.4 and 3.6 in. wg. Unsafe operation of the unit may result if manifold Table 7 shows the approved temperature rise range for each heating input, and the air delivery cfm at various temperature rises. pressure is outside may result. The heating operation airflow must produce fails within the approved range. this range. Personal injury or unit damage a temperature Refer to Indoor Airflow and Airflow Adjustrnents heating airflow HEATING Manifold The main burner Pressure orifices (Propane the induced-draft as follows to adjust energized gas unit are sized for the pressure reading gas input on a propane matches the gas unit: and connect manometer (See cover screw over regulator regulator as adjustment specified clockwise to increase screw counterclockwise 6. Replace screw in Table adjustment ture rise above screw on gas to the correct 6. Turn manifold adjusting on (See Table manometer from pressure the maximum flow to the burners until LS resets. screw When the thermostat 8 for error codes). allowable temperature, the limit and pilot. The blower motor continues to run When die air temperature at the limit switch drops to the low-temperature setting of the limit switch, the switch closes and cover screw. completes the R control circuit. The electric-spark ignition cycles and the unit returns to normal beating operation. tap. Replace pipe plug on gas valve, then turn on gas to unit. Check for leaks. BURNER flame is established. switch opens and the R control circuit "breaks." Any interruption in the R control circuit instantly closes the gas valve and stops gas manifold pressure, or turn adjusting to decrease manifold pressure. 7. Turn off gas to unit. Remove CHECK the required Normally closed limit switch (LS) completes the control circuit through the thermostat R circuit. Should the leaving-air tempera- Valve. pressure, that it has reached begins. This function is performed by (IGC). The evaporator-fan motor is LIMIT SWITCHES 3. Turn on gas to unit. 5. Adjust 45 sec. afar LED is continuously pipe plug on manifold senses An LED (light-emitting diode) indicator is provided on the control board to monitor operation. The control board is located by removing the burner access panel. During normal operation, the Fig. 13). 4. Remove motor is satisfied and "W" is deenergized, the burners stop f-wing and the evaporator-fan motor shuts off after a 45-sec. time-off delay. 1. Turn off gas to unit. 2. Remove OF OPERATION speed, the burner sequence the integrated gas control Units) on a propane unit rated input when the manifold level specified in Table 6. Proceed SEQUENCE On a call for hearing, terminal "W" of the thermostat is energized, starting the induced-draft motor. When die hall-effect sensor on cover screw cap on gas valve. 4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks. Measure section to adjust when required. (See Fig. 15-16 and unit wiring label). may result. 3. Replace rise that AUXILIARY LIMIT SWITCH system (ROLLOUT) The function of the switch is to close the main gas valve in the event of flame rollout. The switch is loca_d above die main FLAME With burner access panel removed, observe the unit heating operation. Watch the burner flames to see if they are light blue and soR in appearance, and that the flames are approximately the same burners. When the temperature at the auxiliary switch reaches the maximum allowable temperature, the R control circuit trips, closing the gas valve and stopping gas flow to the burners. The indoor (evaporator) fan motor (IFM) and induced draft motor for each burner. Propane will have blue flame with yellow tips (See Fig. 14). Refer to the Maintenance section for information on burner removal. continue to man until FAULT CODE 7. 19 switch is reset. The IGC LED will display Table 7--Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input HEATING INPUT (BTUH) 20 25 30 35 40 45 50 55 60 65 70 40,000 1500 1200 1000 857 750 667 600 545 500 -- -- 60,000 2250 1800 1500 1286 1125 1000 900 818 750 692 -- 90,000 -- -- 2250 1929 1688 1500 1350 1227 1125 1038 964 115,000 -- -- -- 2464 2156 1917 1725 1568 1438 1327 1232 -- -- -- 2786 2438 2167 1950 1773 1625 1506 -- TEMPERATURE 130,000 RISE °F NOTE: Dashed areas do not fall within the approved temperature _se range of the unit. Table 8--LED Indications ERROR CODE LED INDICATION Normal Operation Hardware Failure On Off IMPORTANT: (48GS048 and Three-phase, 48GX030-060) These units must be checked Fan On/Off Delay Modified Limit Switch Fault 1 Flash 2 Flashes Flame Sense Fault Four Consecutive Limit Switch Faults 3 Flashes 4 Flashes Ignition Lockout Fault Induced-Draft Motor Fault Rollout Switch Fault 5 Flashes 6 Flashes 7 Flashes Internal Control Fault 8 Flashes Temporary lock-out (1 hr) 9 Flashes compressor suction and discharge matically lower than normal. CHECKING AND ADJUSTING NOTE: Adjustment of the with refrigerant CHARGE R-22 charge refrigerant, is not required of not having the proper R-22 charge. A superheat charging chart is attached to the outside of the service access panel. The chart includes the required suction line tempera- MAKE ADJUST- Ir!_ [,,,Y±'Ti]id [,,] _'I procedures the unit. may be dra- REFRIGERANT ture at given suction line pressures tures. Complete the required section before starting pressures The refrigerant system is fully charged tested, and factory-sealed. unless the unit is suspected AND compressor If not corrected within 5 shuts off the compressor. The 3-phase power leads to the unit must be reversed to correct rotation. When turning backwards, _roll compressors emit elevated noise levels, and the difference between 1. There is a 3-sec. pause between error code displays. 2. If more than one error code exists, all applicable error codes will be displayed in numerical sequence 3. This chart is on the wiring diagram located inside the burner access panel, COOLING compressor units direction-oriented. to ensure proper 3-phase power lead orientation. minutes, the internal protector NOTES: Step 3--START-UP MENTS scroll are and outdoor ambient tempera- An accurate superheat, thermocoupleor thermistor-type thermometer, a sling psychrometer, and a gauge manifold are required given in the Pre-Start-Up when using the superheat charging method for evaluating the unit charge. Do not use mercury or small dial-type thermometers Do not jumper any safety devices when operating the unit. Do not operate the compressor when the outdoor temperature beca_ve they are not adequate for this _pe of measurernent. is below 40OF (unless accessory low-ambient kit is installed). Do not rapid-cycle the compressor. Allow 5 minutes between "on" cycles CHECKING to prevent COOLING Start and check follows: compressor CONTROL the unit for proper damage. When evaluating cooling control operation as I. Place room thermostat SYSTEM switch in OFF position. Observe that blower motor starts when FAN switch is placed Proceed 2. Using 4. Measure room temperature) valve and record a. Outdoor 3. When using an auto-changeover room thermostat, place both SYSTEM and FAN switches in AUTO. positions. Observe that unit operates in Heating mode when temperature control (above with 3. Start unit in Cooling pressures stabilize. blower motors start. Observe that cooling cycle shuts down when control setting is satisfied. The evaporator fan will continue to run for 30 see. for heating" an indicated caps from low- and high-pressure hoses high-pressure gauge hoses fittings, respectively. 2. Place SYSTEM switch in COOL position and FAN switch in AUTO. position. Set cooling control below room temperature. Observe that compressor, condenser fan, and evaporator operates in Cooling mode when temperature control "call for cooling" (below room temperature). charge, adjust- as follows: 1. Remove in ON position and shuts down when FAN switch is placed in AUTO. position. is set to "call the refrigerant ment to the specified factory charge must always be very minimal. If a substantial adjustment is indicated, an abnormal condition exists somewhere in the cooling system, such as insufficient airflow across either coil or both coiLs. OPERATION c. Suction-tube d. Suction and is set to and let unit ran fittings. low- and service until system the following: iniet-air temperature (°F db). temperature (°F wb). temperature (low-side) attach to low- and high-pressure mode ambient-air b. Evaporator service core depressors, (°F) at low-side pressure service fitting. (psig). 5. Using "Conling Charging Charts," compare outdoor-air temperature (°F db) with the suction line pressure (psig) to 20 determine desired system operating suction linetemperature (See Fig.17-26). 6.Compare actualsuction-tube temperature with desired suction-tube temperature. Usinga tolerance of -+3°F,add refrigerant if actual temperature ismore than 3°F higher than proper suction-tube temperature, actual temperature is more suction-tabe temperature. than or remove refrigerant 3°F lower than required NOTE: If the problem causing the inaccurate refrigerant leak, refer to the Check for Refrigerant INDOOR AIRFLOW AND AIRFLOW Table 10-Color Coding for 460-V GE Motor Leads 3-SPEED 2-SPEED black = high speed black = high speed violet = jumper blue = jumper orange = medium speed if red = low speed readings is a Leaks section. red = low speed chassis parts. To select high speed on 460-v GE motors, separate ADJUSTMENTS the black (female quick connect - QC - from the jumper lead (male quick connect - QC) and connect the black lead to the BR. lr_*ulate the jumper COOLING to avoid contact SEQUENCE with any chassis parts. OF OPERATION With the room thermostat SYSTEM switch in the COOL position and the FAN switch in the AUTO position, of operation is as follows: Table 7 shows the temperature rise at various airflow rates. Tables 11 and 13 show both heating and cooling airflows at various external static pressures. Refer to these tables to determine the airflow for the system wet coil pressure NOTE: being installed (See Tables l. When Be sure that all supply- and return-air and adjusted 14 and 15 for grilles R to terminals thermostat: 2. The normally or explosion Airflow can be changed blower motor. Unit 48GS two- can cause by changing or three-speed factory wired for low speed wired for medium speed. All 48GX units are factory be wired for medium serious injury the lead connections motors operation. (except size Unit 48GS030 NOTE: of the Table on the 208/230V Coding 9-Color 030) in the field. motor leads, see Table 9. Motor black = high speed of the blower motor (BM), remove relay the fan evaporator has started relay BM close blower (indoor) it and then stopped, again until 5 minutes have elapsed. The terminal R to terminals Y and G. These open GE motor leads, see Table the speed of the blower motor (BM), remove be performed on this equipment. Tiffs combination local dealer about the availability of a The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and GE Motors on the 460-v thermostat NOTE: Consult your maintenance contract. (BR). This wire is attached to terminal BM of the integrated gas control (IGC) beard for 3-phase units. To change the speed, remove and replace with lead for desired blower motor speed. Insulate the removed lead to avoid contact with chassis parts. To change not be started of energized heating/cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling or heating of units, refer to Tables 16-18. red - low speed leg lead from the blower For color coding through To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenance must red = low speed For 460-V open contacts Leads black = high speed the speed (C) close MAINTENANCE for 208/230-V 2-SPEED speed of energized the circuit through compressor motor (COMP) (outdoor) fan motor (OFM). Both motors start circuits deenergize contactor coil C. The condenser and compressor motors stop. After a 30-sec. delay, the blower motor stops. The uhit is in a "standby" condition, waiting for the next "call for cooling" from the room thermostat. blue = medium speed motor contactor the cooling cycle remains "on" until the room temperature drops to a point that is sfightly below the cooling control setting of the room thermostat. At this point, the thermostat "breaks" the circuit are is factory 3-SPEED To change open contacts Once the compressor should For 208/230V For color coding circuits through and complete the circuit fan motor (IFM). for low speed and may need to or high speed Y and G. These completed 3. The set of normally or between wired that is slightly instantly. Before changing blower speed, shut off gas supply. Then disconnect electrical power to the unit and install lockout tag. shock rkses to a point are open, properly. and complete to condenser Electrical death. temperature sequence above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal drop). free from obstructions, the room the cooling 10. equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those fan motor procedures TO HEED speed lead from the blower relay (BR) and replace with the lead for the desired blower motor speed. The motor speed lead is OUS attached to terminal BM of the integrated gas control (IGC) board. For low and medium speeds, black must be connected to the jumper wire. Insulate removed lead end to avoid contact with recommended in the User's Manual. FAILURE THIS WARNING COULD RESULT IN SERI- INJURY EQUIPMENT. 21 AND POSSIBLE DAMAGE TO THIS Table 11--Dry Coil Air Delivery* - Horizontal Downflow Discharge Unit 48GS030-060 (Deduct 10 percent for 208 Volts) 230 AND 460 VOLT Unit M_or Speed 0,O 0.1 0,2 0.3 E_ernalSt_ic 0,4 P_ssure (in. wg) 0.5 0,6 WaHs 260 275 270 267 0.7 0.8 0.9 264 252 260 -- -- -- Cfm WaHs 950 380 880 375 825 365 750 360 670 355 580 350 400 344 .... 335 Cfm 1220 1150 312 -- -- 1090 1025 970 860 760 620 450 -- WaRs Cfm 485 1475 -- 475 1440 470 1350 460 1275 455 1200 445 1125 437 1025 430 925 415 750 385 400 --- Low WaUs Cfm 576 1430 566 1403 556 1365 538 1263 512 1157 497 1068 481 973 466 900 450 827 435 704 --- Med Watts Cfm 680 1720 671 1630 660 1538 624 1439 604 1346 620 1267 602 1167 558 1126 534 1018 512 958 496 781 Watts Cfm 810 1800 800 1745 790 1660 762 1600 766 1547 742 1465 723 1360 709 1276 688 1163 661 967 627 876 Low Wa6s Cfm --- 675 1454 660 1387 650 1326 640 1275 630 1204 620 1142 610 1061 595 995 580 918 --- Med WaRs -- 866 655 825 795 778 765 750 735 718 700 Cfm -- 1515 1458 1406 1350 1285 1224 1163 1091 1013 932 WaRs Cfm --- --- --- 1000 1551 950 1488 925 1424 910 1360 890 1296 875 1233 855 1146 833 1071 WaRs cfm -- 727 1678 712 1639 700 1600 688 1561 666 1500 644 1440 622 1379 595 1289 569 1198 -- wars - 853 836 621 807 762 756 730 699 667 640 Cfm -- 1914 1870 1825 1780 1711 1642 1573 1470 1367 1270 High WaRs Cfm --- 979 2150 959 2100 943 2050 927 2000 697 1922 868 1845 838 1767 802 1600 766 1535 736 1419 Low Watts Cfrn 1033 2105 949 2057 864 2009 836 1943 822 1909 608 1876 772 1823 737 1770 705 1698 674 1627 642 1531 Med WaRs 1084 1054 1024 994 971 055 928 997 867 635 803 CfTn Watts 2318 -- 2248 -- 2179 1184 2110 1152 2058 1120 2000 1102 1932 1084 1885 1056 1829 1029 1740 997 1638 965 Cfm -- -- 2349 2278 2207 2124 2041 2000 1960 1853 1745 Low 030 Med High 036 High 042 High Low 048 060 Med High * Air delivery values are without air filter and are for dry coil (See Table 14_8GS NOTE: Deduct field-supplied 1.0 Wet Coil Pressure Drop). air filter pressure drop and wet coil pressure drop to obtain exlemal static pressure available for ducting. Table 12--Filter Pressure Drop (In. wg) UNITSIZE RLTER SIZE 030 20 X 20 X 1 036 20 X 24 X 1 042, 648, 060 24 X 30 X 1 CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 22(;0 2300 0,05 0.07 0.08 0,10 0.12 0.13 0,14 0.15 ....... 0.09 0.10 0,11 0.13 0.14 0.15 0.16 0.07 0.08 0.09 0.10 Failure to follow these warnings could result in serious injury: I. FirsL turn off gas supply to the unit. Then turn off electrical power to the unit and install lockout tag before performing any maintenance or service on the unit. 2. Use extreme caution when removing panels 0.11 0.12 0,13 0.14 0.15 0.16 0,17 0,18 tion when servicing. and parts. As The minimum follows: with any mechanical equipment, personal injury can result from sharp edges, etc. 3. Never place anything combustible either on, or in contact with, the unit. 1. Inspect maintenance air filter(s) requirements each month. necessary. Certain geographical frequent inspections. 4. Should overheating occur or the gas supply fail to shut off, turn off external main manual gas valve to the unit. Then shut off electrical supply and install lockout tag. 2. Inspect indoor for this equipment are as Clean or replace when may require more locations coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean at least once per healing / cooling season or more often if needed. 22 Table 13--Dry Coil Air Delivery* - Horizontal and Downflow Discharge Unit 48GX030-060 (Deduct 10 percent for 208 Volts) 230 AND Unit Motor Speed WaRs 0,0 246 0.1 244 0.2 243 6.3 241 466 VOLT E_ernal Static Pressure 0.4 0.8 ....... (in. wg) 0.6 0,7 .... 0.8 0,9 1.0 Low 030 Med High Low 036 Med High Low 042 Med High Low 048 Med High LOW 060 Med High Cfm 982 860 808 736 WaRs 343 339 336 332 328 ....... 322 317 Cfm 1233 1179 1109 1038 953 855 754 .... WaRs .... 441 432 421 410 400 -- -- Cfm .... 1202 1111 1021 929 826 -- -- WaRs -- 470 458 445 430 415 399 384 -- -- -- Cfrn -- 1463 1406 1344 1273 1186 1091 983 -- -- -- WaRs -- -- 614 501 487 471 455 438 422 -- -- Cfm -- -- 1497 1428 1348 1255 1152 1042 929 -- -- WaRs Cfm --- --- --- 646 1491 636 1412 626 1325 614 1228 662 1120 589 1003 --- --- WaRs Cfm 643 1626 625 1614 614 1579 605 1532 593 1478 574 1421 549 1361 518 1295 486 1218 454 1120 --- WaRs .... 726 695 661 625 591 561 540 Cfm .... 1731 1672 1610 1541 1456 1345 1193 WaRs ....... 790 766 742 713 Cfm ....... 1699 1602 1494 1367 -- WaRs 614 588 577 572 566 556 539 517 491 -- Cfm 1591 1549 1518 1490 1460 1421 1372 1312 1242 -- -- WaRs 778 756 738 719 699 676 650 623 596 572 555 Cfm 1854 1837 1804 1759 1705 1643 1577 1508 1440 1375 1315 WaRs Cfm .... .... 896 1956 862 1879 829 1797 800 1709 775 1615 752 1514 728 1406 WaRs 834 813 782 746 712 680 652 626 -- -- -- Cfm 2016 1955 1898 1840 1781 1717 1646 1566 -- -- -- WaRs 941 889 851 822 797 772 745 714 679 639 -- Cfm 2379 2233 2124 2038 1964 1892 1814 1727 1626 1511 -- WaRs -- -- 960 949 920 863 845 812 783 753 -- Cfm -- -- 2497 2224 2076 1986 1915 1831 1721 1588 -- * Air delivery values are without air filter and are for dry coil (See Table 15-48GX Wet Coil Pressure Drop table), NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting. 751 I1C lOO 90- BO 1 70 i i 50 '50 - 40 40 50 SUCT]ON LINE I 4 1I0 50 70 TEMPERATURE ('F) 116 80 30 90 217 5UC7_0 _, LINE T£HpERATURE ('C) 40 5'0 50 SUCTION LINE TEHPERATURE(-F] I I 4 i_O 16 SUCTION LINE TEMPERATURE(.C] C00043 Fig. 17--Cooling Charging Chart, 48GS030 Units Fig. 18--Cooling Charging Chart, 48GS036 U_ 23 e44 ÷_ 75_ 110 68= 100- _v i i I i i i = i i ! i _' 105 41 95 :t5 65 18 . m _ LU __ _ o70 _ .TI _ J_'_ _"_' i, L,,,,_ !i' .- _7_ ,o11 30 40 50 I 60 70 80 90 I 27 I 32 SUCTION UNETEMPERATURE I°Fq I -1 Fig.19---Cooling ChargingChad,48GS042 U_ °4s I 4 SUCTION I I = 10 16 21 LINE TEMPERATURE (°C) Fig. 20--Cooling Charging Chart, 48GS048 Unl_ls°47 Ililll 689 o i 100- _ q_l _8o_£1 I I r- I _ ,==,,_._- .._, , I I !111 I_-'_ ! 45 73 i#) _LU Z 0 ; i 40- I ii'_ - i i '1 2o713o 3O 40 50 60 70 SUCTION UNE TEMPERATURE I_F) 1 1 I motor and wheel for cleanliness I 4 10 16 21 SUCTION LINE TEMPERATURE (°C) Fig. 21--Cooling 3. Inspect blower I 80 gO I I 27 32 Charging Chart, 48GS060 U_ m AIR FILTER at the begin- ning of each heating and cooling season. Clean when necessary. For first heating and cooling sem_on, inspect blower wheel hi-monthly to determine proper cleaning frequency. 4. Check electrical proper operation when necessary. connections each heating for dghtness and controls for and cooling season. Service tubes or sharp Inspect air filter(s) at least once each (throwaway-type) or clean (cleanable-type) month and replace at least twice during 6. Check and inspect heating section before each heating season. Clean and adjust when necessary. each heating and cooling season or whenever clogged with dust and/or lint. the f-alter(s) becomes 5. Ensure wires are not contacting sheet metal edges. 7. Check flue hood and remove refrigerant any obstructions, EVAPORATOR if necessary. NOTE: lubricate 24 BLOWER AND MOTOR All motors are permanently these motors. lubricated. Do not attempt to (0301 60HZ CHARGING CHART (036) 60HZ CHARGING CHART r_ _J_ 46 41 35 15 _5 95 29 24 18 13 B5 7 75 85 55 45 I 2761 40 L i _71 30 40 50 60 SUCTION LINETEMPERATURE _1 4 10 16 SUCTION LINETEMPERATURE Fig. 22--Cooling 27 32 4o so 6o _o 8o sucnoNLI_E TEMPERATUREII°_ 21 -1 °- 4 10 16 21 SUCTION LINE TEMPERA31JRE (°C) (_C) CHART 0_ _F 27 I 32 Fig. 23---Cooling Charging Chart, 48GX036 U_ ]_= ,C °51 (048) 60HZ CHARGING CHART 68_ 90- 100 i _62I 90- , 551 _ g 90 100 <_'62C _ 8_0 (_F} Charging Chart, 48GX030 Un_l_°46 (042) 60HZ CHARGING 68E 70 q 551 _6o ! o3 _o uJ ku _48E _7o 70 cu _ _41, o ="6o !i - _u z _ 41" o_z6o _ z L_ O _so! 27[ ku _ _ a4_ 40 271 4O 2O; 3O 30 I I -1 4 10 SUCTION Fig. 24---Cooling 16 LINE TEMPERATURE 21 27 I -1 312 I ("C) I C00052 Fig. 25--Cooling Charging Chart, 48GX042 Units For longer life, operating economy, and continuing clean accumulated dirt and grease from the blower motor annually. efficiency, wheel and 40 SIUCTION 50 60 LINE TEMPE 70 P,ATU RE I(°F) 4 t0 16 SUCTION UNETEMPERATURE 21 I°C) 80 90 I 27 ' 32 Charging Chart, 48GX048 Units °°53 c. On all units, remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment. Before cleaning the blower motor and wheel, disconnect d. Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly. gas supply. Then turn off and tag electrical power to the unit. Failure to adhere to this warning could cause serious injury or death. Cleaning the Blower 1. Remove housing, Remove Motor and Wheel and disassemble a. Remove e. Loosen Remove unit access blower assembly a. Ensure as follows: panel. setscrew(s) that secures wheel to motor shall screws that secure motor mount brackets to and slide motor and motor mount and clean blower proper reassembly out of housing. wheel as follows: by marking wheel orientation. b. Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes. b. Disconnect motor lead from blower relay (BM). Disconnect yellow lead from temainal L2 of the contactor. 25 Table 14_8GS INDUCED DRAFT MOTOR MOUNT Wet Coil Pressure Drop UNIT SIZE 48GS AIRFLOW (CFM) PRESSURE DROP (IN. WG) 030 900 1000 0.065 0.080 1100 0.097 1100 0.084 1200 1300 0.100 0.177 1300 0.103 1400 0.120 1500 1500 0.138 0.088 1600 0.100 1700 1900 0.113 0.108 2000 0.120 2100 0.132 036 042 048 060 ROLLOUT SWITCH COLLECTOR BOX BLOWER HOUSING BURNER RACK MOUNTING SCREW C99022 Fig. 27--Blower Housing and Flue Collector Box Table 1,5_48GX Wet Coil Pressure Drop UNIT SIZE 48GX AIRFLOW (CFM) 900 PRESSURE DROP (IN. WG) 0.0687 030 1000 0.083 1100 0.150 1100 1200 0.084 0.100 1300 0,177 1300 1400 0.099 0.177 1500 0.204 1500 1600 0.199 0.137 1700 0,156 1900 0.108 2000 0,120 2100 0.132 036 042 048 060 (060) 60HZ CHARGING CHART = _620 904 _ I ; _,_ _RT F I ==_o_ " L, L_ '2, I _ Fig. 28_Unit 85 _1 c. Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel 75 IV and housing with vacuum cleaner, using soft brash attachment. Remove grease and oil with mild solvent. 45 d. Reassemble 'k e. Reassemble z60d tightened shaft. f. Reinstall I' v 30 3. Restore 40 SU_TION 50 60 70 LIN E TEMPERATURE I°Ft I I I 4 10 16 21 SUCTION UNE TEMPERATURE (_C) wheel into housing. motor on motor 80 90 I 27 32 into housing. Be sure setscrews shaft fiats and not on round part are of unit access panel electrical power proper blower rotation cooling cycles. _ I Fig. 2_Cooling Access Panel , i -" "i. _41_ C99091 105 _,_ ,F FRONT ACCESS PANEL to unit. and motor Start unit and check for speeds during heating and FLUE GAS PASSAGEWAYS To inspect exchanger: the flue collector box and upper areas of the heat 1. Remove the combustion blower wheel and motor assembly according to directions in the Combustion-Air Blower section. Charging Chart, 48GX060 Units 26 1. Remove unit access 2. Remove the 7 screws that attach induced-draft panel (See Fig. 28). ing plate to blower housing HOUSING motor mount- (See Fig. 29). 3. Slide the motor and blower wheel a._sembly out of the blower housing (See Fig. 29). Clean the blower wheel. If additional cleaning is required, 4. To remove blower, continue remove with Steps 4 and 5. 2 setscrews. 5. To remove motor and cooling fan assembly, remove that hold blower housing to mounting plate. 6. To reinstall, LIMIT 2 SETSCREWS (HIDDEN) reverse the procedure outlined 4 screws above. SWITCH Remove unit access panel. partition. BURNER Limit switch is located on the blower IGNITION Unit is equipped system. Ignition with a direct spark ignition 100 percent lockout module is located in die control box. Module contains a self-diagnostic diagram for LED interpretation. LED. During servicing, refer to label If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit or by turning selector switch to OFF position at die thermostat. C99085 Fig. 29---Removal of Motor and Blower Wheel MAIN BURNERS At the beginning of each heating season, irtspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames Removal and adjust, if necessary. of Gas Train To remove die gas train for servicing: 1. Shut off main gas valve. 2. Shut off power to unit and install lockout 3. Remove unit access 4. Disconnect tag. panel (See Fig. 28). gas piping at unit gas valve. 5. Remove wires connected 6. Remove ignitor and sensor wires at the ignitor to gas valve. Mark each wire. 7. Remove the mounting screw that attaches the unit base (See Fig. 27). module. the burner rack to 8. Slide die burner rack out of the unit (See Fig. 27 and 30). 9. To reinstall, CONDENSER CONDENSATE C99086 Fig. 30_Burner Rack Removed 2. Remove collector the 3 screws holding die blower housing box cover (See Fig. 27-30). 3. Remove the 12 screws (See Fig. 29-30) beat exchangers. 4. Clean all surfaces, COMBUSTION-AIR holding the flue collector to die heat exchanger as required, assembly. Inspect reverse die procedure COIL, EVAPORATOR DRAIN PAN the condenser coil, evaporator outlined above. COIL, AND coil, and condensate drain pan at least once each year or more often if necessary. to die flue The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with die airflow through the condenser coil. box cover Inspect the Straighten using a wire brush. bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using die so_ brush attachment. Be careful not to bend die fins. If coated with oil or BLOWER Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodicaily during the heating bi- grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden bose. Re careful not to splash water on motors, insulation, wiring, or air l-alter(s). For best results, spray condenser coil fins from inside to outside die unit. To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows: On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush ail dirt and debris from the unit base. season. For the first heating sea.son, inspect blower monthly to determine proper cleaning frequency. wheel 27 Inspect thedrainpanandcondensate drain linewhen inspecting thecoils. Clean thedrain panand condensate drain byremoving all foreign matter fromthepan. Flush thepananddraintubewith clear water. Donotsplash water ontheinsulation, motor, wiring, or airfilter(s). If thedraintubeis restricted, clearit witha "plumbers snake" orsimilar probe device. Ensure thattheauxiliary drain portabove thedrain tubeisalso clear CONDENSER NOTE: Refer to the heating and/or cooling sequence in this publication 6 screws holding 3. Inspect the fan blades condenser 5. When replacing fan blade, away from the motor visible. See Fig. 12). 6. ErL_ure that setscrew when tightening. upside for cracks 4. If fan needs to be removed, fan off the motor shaft. grille and motor to top down on top cover to loosen the setscrew control _GERANT Annually CIRCUIT inspect all refrigerant base for oil accumulations. refrigerant leak. tubing Detecting connections and the unit oil generally indicates a panel position engages and slide the shaft will be EVAPORATOR the flat area on the motor shaft inspecting to locate all the electrical connections controls all or burned connections clean all the parts, restrip are the controls for tightness. properly system LIQUID replace checking exists, be -- ACUTROL DEVICE LINE STRAINER (to protect metering device) is made of wire mesh and located ha the liquid line on the inlet side of the metering device. the TROUBLESHOOTING Use the Troubleshooting occur with these units. operation. If discrepancies are observed in either or both operating cycles, or if a suspected malfunction has occurred, check each electrical component with the proper electrical instrumentation. label when making DEVICE The liquid line strainer and securely. and wiring, airflow does not require is suspected- lfa problem This metering device is a fixed orifice and is located in the header to the evaporator coil. Start the unit, and observe at least one complete and one complete cooling cycle to ensure proper Refer to the unit wiring AIRFLOW airflow. METERING and Tighten the connection the electrical is suspected, sure that all supply- and return-air grilles are open and free from obstructiomr, and that the air filter is clearL When necessary, refer to the Indoor Airflow andAirflow Adjustments section to check the AND WIRING If any smoky the connection, wire end and reassemble performance The gas input does not require checking unless improper heating performance is suspected. If a problem exists, refer to the Start-Up section. blade so the hub is 1/8 in. ha. of motor The heating and/or cooling unless improper performance all electrical screw connections. noticed, disassemble or if low cooling GAS INPUT end (l/8 CONTROLS access wiring. Check access panel. heating cycle of operation proper If no refrigerant leaks are found and low cooling performance is suspected, refer to the Checking and Adjusting Refrigerant Charge section. or bends. Irmpect and check the electrical controls and wiring annually. Be sure to turn off the gas supply, and then the electrical power to the uniL After determining leak-test all refrigerant tubing using an electronic leak-detector, halide torch, or liquid-soap solution. If a refrigerant leak is detected, refer to the Check for Refrigerant Leaks section. grille. ELECTRICAL Remove in FAN 2. Turn motor/grille a_s_mbly expose the fan blade. 7. Replace an aid operation If oil is detected l. Remove cover. as Use the Start-Up followed. these checkouts. 28 Guides (See Tables 16-18) if problems START-UP CHECKLIST Checklist to ensure proper start-up procedures are Table 16_Troubleshooting SYMPTOM Compressor and condenser will not start. fan Compressor will not start but condenser fan runs, Three-phase scroll compressor (48GS048 and 48GX030-060 only) makes excessive be a low pressure noise, and dilferentiat. Guide_Cooling CAUSE there may REMEDY Power Failure Call power company. Fuse blown or circuit breaker tdppad Replace fuse or reset cimuit breaker. Defective thermostat, contactor, transformer, or control relay Replace component. Insufficient line voltage Determine cause and correct. Incorrect or faulty widng Check widng diagram and rewire correctly. Thermostat setting too high Lower thermostat setting below room temperature. Faulty widng or loose connections in compressor circuit Check wiring and repair or replace. Compressor motor burned out, seized, or internal ovedoad open Determine cause Replace compressor. Defective run/start capacitor, overload, start relay Determine cause and replace. One leg of 3-phase power dead Replace fuse or reset circuit breaker. Determine cause. Scroll compressor is rotsting in the wrong direction Correct the direction of rotation by reversing the 3-phase power leads to the unit. Shut down unit to allow pressures to equat_ze. Refrigerant overcharge or undercharge Recover refrigerant, evacuate system, and recharge to capacities shown on nameplate. Defective compressor Compressor cycles (other than normally satisfying thermostat). Compressor Excessive operates oonUnuously, head pressure. Head pressure too low. Excessive suction pressure. Replace and determine cause. Determine cause and correct. insufficient line voltage Blocked condenser Determine cause and correct. Defective _n/start capacitor, ovedoad or start relay Defective thermostat Determine cause and replace. Faulty condenser-fan Restriction in refitgerant system Replace. Locate restriction and remove. Dirty air filter Unit undersized for load Replace filter. Decrease load or increase unit size. Thermostat set too low Reset thermostat. Low refrigerant charge Locate leak, repair, and recharge. Leaking valves in compressor Replace compressor. Air in system Condenser coil dirty or restricted Recover refrigerant, evacuate system, and recharge. Clean coil or remove restdction. Dirty air filter Replace filter. Dirty condenser COil Clean coil. Refrigerant overcharged Recover excess refrigerant. Air in system Condenser air restricted or air short_ysiing Recover refdgerant, evacuate system, and recharge. Determine cause and correct. Low refrigerant charge Check for leaks, repair, and recharge. Compressor valves leaking Replace compressor. Restriction in liquid tube Remove restriction. High heat load Check for source and eliminate. Compressor valves leaking Replace compressor. Refrigerant overcharged Recover excess refrigerant. Dirty air filter Replace Filter. Low refitgerant charge Check for leaks, repair, and recharge. Remove source of restdction. motor or capacitor Mefedng device or low side restdcted Suction pressure too low. Insufficient evaporator airflow Temperature too low in conditioned area Outdoor ambient below 40°F Fistd-instailed filter-alder restricted Replace thermostat. Increase air quantity. Check filter -- replace if necessary. Reset thermostat. install low-ambient kit. Replace. 29 Table 17--Troubleshooting SYMPTOM REMEDY Water in gas line Drain. Install drip htg. No power to f_mace Check power supply fuses, widng, or circuit breaker, Check transformer, NOTE: Some transformers have internal overcurrerd protection that requires a ccol_lown period to reset. No 24-v power supply to control circuit Burners will not ignite, inadequate Guide-Heating CAUSE heaUng. Poor flame characteristics. Miswirod or loose connections Check all widng and wirenut connections Burned-out heat anticipator in thermostat Replace thermostat. Broken thermostat wire Run continuity check, Replace wire if necessary. Mlaaligned spark electrodes Check flame ignition and sense electrode positioning. Adjust as necessary. No gas at main burners 1 .Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempting to light unit. 2. Check gas valve. Dirty air filter Clean or replace filter as necessary. Gas input to fumace too low Check gas pressure at manifold match with that on unit nameplate. Unit undersized for application Replace with proper unit or add additional unit. Restricted airflow Clean or replace rifler. Remove any restriction. Blower speed too low Use faster speed tap if available, or install aflemate motor. Limit switch cycles main burners Check rotation of blower, thermostat heat anticipator settings, temperature rise of unit. Adjust as necessary. Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame 1 .Tighten all screws around burner compartment. 2. Cracked heat exchanger. Replace. 3. Unit oven3red. Reduce input (change orifices or adjust gas line or manifold pressure). 4. Check burner alignment, Table 18---Troubleshooting Guide-LED Error Codes SYMPTOM CAUSE REMEDY Check 5-amp fuse on IGC*, power to unit, 24-v circuit breaker, and Hardware failure, (LED OFF) Loss of power to control module (IGC)'. transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the ovedoad tdps, ariow 10 minutes for automatic reset. High limit switch opens during heat Fan ON/OFF delay modified {LED/FLASH) exchanger warm-up period before fan-on delay expires. Limit switch opens within three minutes after blower_ff delay timing in Heating mode. Ensure unit is fired on rate; ensure temperature rise is correct. Ensure unWs exfamai static pressure is within application guidelines. Draft switch faults. (LED 2 flashes) High tempemtore limit switch is open. Flame sense fault. (LED 3 flashes) The IGC* sensed flame that should not be present. Reset unit. If problem persists, replace central board. 4 consecutive limit switch faults. (LED 4 flashes) Inadequate airflow to unit Check operation of indoor (evaporator) fan motor and that supply-air temperature rise agrees with range on unfl nameplate information. Ignition lockout. (LED 5 flashes) Unit unsuccessfully attempted ignition for 15 minutes, Check ignitor and flame sensor electrode spacing, gaps, etc. Ensure that flame sense and ignflion wires are properly terminated. Verify that unit is obtaining proper amount of gas. Induced-draft motor fault. (LED 6 flashes) IGC does not sense that ioduced-draft motor is operating.* Check for proper voltage. If motor is operating, check the speed sensor plug/IGC Terminal J2 connection. Proper connection: PIN 1 White PIN 2 -- Red PIN 3 -- Black. Roflout switch fault, (LED 7 flashes) Roltout switch has opened, Roliout switch will automatic.afly reset, but IGC* will continue to iockout unit. Check gas valve operation. Ensure that induced-draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect. Rofiout control fault. (LED 8 flashes) Microprocessor has sensed an error in the software or hardware. if error code is not cleared by resetting unit power, replace the IGC*. Electrical interference Reset 24-v. to control board or tom thermostat off, then on again. Fault will automatically reset itsefl in one (1) hour. Temporary software lock out. (LED 9 flashes) * WARNING i_. IGC is sens"I_ Check the operation of the indoor (evaporator) fan motor. Ensure that the supply-air temperature rise is in accordance with the range on the unit nameplate. impeding IGC software : If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The to static electflaity and may he damaged if the necessary precautions are not taken. IMPORTANT: Refer to Table 17--Troubleshoofing Guide-q-leating for additional troubleshooting analysis. LEGEND tP=re----_tegrated Gas Unit Controller LED -- Light*Emfltiog Diode 3O START-UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMATION MODEL NO: ............................................................................................................................................................. SERIAL NO: .............................................................................................................................................................. DATE: ........................................................................................................................................................................ TECHNICIAN: ........................................................................................................................................................... JOB LOCATION: ........................................................................................................................................................... H. PRE-START-UP (insert checkmark in box as each item is completed) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT __ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK GAS PIPING FOR LEAKS -- CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN VERIFY THAT UNIT INSTALLATION IS LEVEL __ CHECK FAN WHEEL PROPELLER FOR LOCATION IN HOUSING INSTRUCTIONS AND IN PLACE ORIFICE AND SETSCREW TIGHTNESS HI. START-UP ELECTRICAL SUPPLY VOLTAGE L!-L2 COMPRESSOR AMPS L1 L2-L3 ____ L2 COMPRESSOR L2 INDOOR AMPS L1 (EVAPORATOR) L3-L1 L3 L3 FAN AMPS TEMPERATURES OUTDOOR (CONDENSER) AIR TEMPERATURE: RETURN-AIR TEMPERATURE: DB COOLING SUPPLY AIR: GAS HEAT SUPPLY AIR: PRESSURES GAS INLET PRESSURE GAS MANIFOLD REFRIGERANT REFRIGERANT __ VERIFY __ VERIFY DIRECTION. * Me_asured at suction t Measured at liquid DB WB IN. WG PRESSURE SUCTION DISCHARGE DB WB IN. WG . PSIG PSIG SUCTION REFRIGERANT CHARGE USING CHARGING THAT 3-PHASE SCROLL COMPRESSOR inlet condenser 31 LINE TEMPt TABLES (48GS048 to compP..ssor line leaving LINE TEMP* DISCHARGE and 48GX030-060) IS ROTATING IN CORRECT Copyright 2006 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Manufacturer reserves the right to discontinue, or change at any time, specifications PC 101 Printed in U.S.A. Catalog No, 48GS,GX+TSI or designs without notice and without incurring obligations. Pg 32 2-06 Replaces: New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 32 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:14:38 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools