CARRIER Package Units(both Units Combined) Manual L0606347
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 48
Download | |
Open PDF In Browser | View PDF |
50TM016-028 Single-Package Rooftop Units Electric Cooling with Electric Heat Option Installation, Start-Up and Service Instructions CONTENTS SAFETY CONSIDERATIONS ......................... INSTALLATION .................................. Step 1 -- Provide Unit Support ...................... • ROOF CURB • ALTERNATE UNIT SUPPORT Step 2 -- Rig and Place Unit ......................... • POSITIONING • ROOF MOUNT Step 3 -- Field Fabricate Ductwork .................. Step 4 -- Make Unit Duct Connections .............. Step 5 -- Trap Condensate Drain .................... Step 6 -- Make Electrical Connections ............. • FIELD POWER SUPPLY • FIELD CONTROL WIRING • OPTIONALNON-FUSED DISCONNECT • OPTIONAL CONVENIENCE OUTLET Step 7 -- Make Outdoor-Air Inlet Adjustments ........................................ • MANUAL OUTDOOR-AIR DAMPER Step 8 -- Install Outdoor-Air Hood .................. Step 9 -- Install All Accessories .................... • MOTORMASTER® I CONTROL INSTALLATION • MOTORMASTER V CONTROL INSTALLATION Step 10 -- Adjust Factory-Installed Options ........ • PREMIERLINK IMCONTROL • ENTHALPY SWITCH/RECEIVER • OUTDOOR ENTHALPY CONTROL • DIFFERENTIAL ENTHALPY CONTROL • ENTHALPY SENSORS AND CONTROL • OPTIONAL ECONOMI$ERIV AND ECONOMI$ER2 • ECONOMI$ERIV STANDARD SENSORS • ECONOMI$ERIV CONTROL MODES Step 11 --Install Humidistat for Optional MoistureMi$er TM Package .............. START-UP ....................................... SERVICE ........................................ TROUBLESHOOTING ............................ INDEX .............................................. START-UP CHECKLIST .......................... SAFETY Page 1 1-29 1 4 9 9 9 10 13 13 14 Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filtel.s. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for ;dl brazing operations. Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. limits are exceeded, the unit will automatically lock the compressor out of operation. Manual reset will be required I IMPORTANT: Units have high ambient operating limits. If to restart the compressor: INSTALLATION 16 28 30-36 37-42 43-45 46 CL-I Step 1 -- Provide Unit Support ROOF CURB -- Asselnble and install accessory roof curb or horizontal a&tpter roof curb in accordance with instructions shipped with the curb or horizontal adapter Accessory roof curb and horizontal adapter roof curb and information required to field fabricate a roof curb or horizontal adapter roof curb are shown in Fig. IA-2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be secured to roof curb before unit is set in place. IMPORTANT: The gasketing of the unit to the roof curb or adapter roof curb is critical for a leak-proof seal. Install gasket supplied with the roof curb or adapter roof curb as shown in Fig. IA and lB. hnpropefly applied gasket can result in air leaks and poor unit performance. CONSIDERATIONS Installation and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Manufacturer reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53500009-01 Printed in U.S.A, or designs without notice and without incurring obligations. Form 5OTM-4SI Pg 1 4-06 Replaces: 50TM-3SI I I _K o _EF sc_ _I 5 ON CR7 CU/BO!OAO0 /.i/2"" Z7!7 _1 !kbi 2- PLA\ _ V[EW 01: ROOf: CURB .... T *,, o cN STANDARD14. HIGHCURB {305} c,_rr ,so AO 2 o uNf o0, C bgB('zO_ 2 ". '_ECX'/N I'G {" ",/ [s o, J INBTDL L DTION _r _..... lIE IU _N vkl/b J C INS All (0' :_ v RE i ' BULB i *JE (REF RN = ROOF CUR[ ACC[ _,SOR' ]5 71[>P[D D[S_ [f_{_LED. INSULATED PDNELS_ I _ THICK NEOPRENE COATED i¸¸I/2 LB DENSITY I}IMFNS[ONS IN ( } ARE /N _1ill ]HETERS. c::_ {}IRE(}I {Of,, OF AiR iLOt_ ROOFCURB_ /6 GA. (VA03 $6) 91L. A 90 DEGREE ELBOW MUST BE INSTALLED ON THE SUPPLY DUCT WORK BELOW THE UNIT OIBCHARBE FOR UNITB EQUIPPED WITH , ELECTRIC HEATERS. \OE: T) PR:V{ ATIOq S i>P .... NOTE i. P. 3. 4 5. B. \T UP ;C ON, CURB , I{ IN I#ZAR} E "c_ DR/,IN ,,q T CAI ..................... 0/v "N O B[ i E" 2 3/ 6" (i885) i SUPPLY OPEhiNG) _ :r PAN N i/*r...... IE * NDOOR 1TCqE{) { #5 WtOWii. ONOTN{ ER J ANO i COM RFS{ (}R i 75) i i ]....... A A ' ................. ] I ................ 7 / i G' I/ 4_ _ _ i 3 I'IENI]ONS (310) Ub, l 3/4" / , NSULA[{ PAN[L :OR UPPIY AND RETLRN (CRRFCUR_O12AO0 / rchet} -o,i l {7\E{ odg iNG of mnf 0 L o _AI °'c *_),- o,'toL, !I[}E ONLY) I/4 ° I (SUPPL ($I} TABI O" or/d (_78) • NOH. /4<" X 4_ \ (32) X (102) IYP< /- P_C9 (degree {£O GASKET ]Tk CURB) E \_ FIELO i (44) OUOT SUI>I>I /E} ...... / (IANJ !(F ! E_9 ....O" 3" (76) R]GD (FEID Fig. 1A i Roof Curb Details i 50TM016-025 NSUL AT[ON SLRPL B) $i_1 ) SUPPL ] ED) :' ROOFCURB ACCESSORY I CURB I IHEIGHT] DESCRIPTION i ..........F'--I d CR,,CUROO1," ROD, H AO0 co,o IOH] __._ ,, m a_i, I DIMENSIONS 2 1/41_ (886} !IN RF SUPPLY OR NIRB _ 1 ii ii 13/ _,,i INSULA- _<3;D: 5 1/16 (226_) O" I ED _ANE / f i I i B DEC. IN. .28 .43 TOLERANCES: TO HORIZONTAL • i i {DEGREES AND INCHES1 A UNIT DEC. IN. ALL .28 .45 MAX CURB LEVELING FROM EDGE OF UNIT I i _Ui_pLV L3/161 OP N_'[x,G INSULATED i (31o): C Ui_B ii l 1 7 i3/6" (504) I PANEL CON_ RSATE DRAN I I I t RE IURN i i CURB OPENI G 8J I (GAS KEP NTRY ] S AREA CLEAR FOR GAS IRFD I))R F : I ii_D79} PLAN VIEW OF ROOR CUR8 NOTES: ,..,J 1, RGOFCURB 2. SIWENSIONS 3. [_DIRECTION 4, ROOF 5. TO PREVENT 6. OF THE INOOOR SECTION. UNIT CAN ONLY BE PITCHES AS SHOWN, INSULATED PANELS: T" THICN NEOPRENE COATED I-T/2 LB DENSITY. 7, ACCESSORY IN (I IS SA, IS ARE OF CURS: OISASSEMBLED. SHIPPES IN : (132/ _--OUTLiN[ OF UNIT NILLIWETENS. AIRFLOW, (VAO3-5S} THE HAZARD OF STEEL. STAGNANT A 9_ ELBOW MUST BE INSTALLED THE UNIT DISCHARGE FOR UNITS WATER ON THE [OUIPPES BUILD-UP SUPPLY WITH IN THE DRAIN PAN ATTACH DUCT WORK T i (SUPPLIED JRTTS WITH COUNTER (FIELD DUCT WORE BELOW ELECTRIC HEATERS, FLASH( NS SUPPLIEOI NOOF I NG FIELD ----_\ " SUPP Dt]C_T-LIEU _ IELD TOP ONLY _ D 12 F_'"T'S'u" 150'1) F RETURN SUPPLY _EIBHI i i 7 5 1/!0" FROM TABLE j £a_ S/4': X 4: _ (4419/18' _' _OPT ]ONAL RETURN ,,,: su,; SECTION L LNOM (';I'IS 5/18' TYP 4 PLACES Fig. 1B -- Roof Curb Details -- 50TM028 A'A FELT (FIELD SUPPLIED) CANT STRIP (PIELO SUPPLIED} _!/J _ ........ L RIGID (FIELD INSULATION SUPPLIES) SUPPLIESI 25% VENT AIR/ / ECONOMIZER --_/ HOOD _._ BLOCK-OFFAl__ PAN l I i HORIZONTAL SUPPI Y" CURB (CRRFCURB013A00) TRANSITION FULLY INSULATED SUPPLY PLENUM 14-3/4" 31_ _ I 143/4"1 ] _ / 2"uXI'_R T TYP. /_ I"ll/NSUDLEATIsITNy, STITCH WELDED/STICK PINNED & GLUED i 23 NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated transition duct, The pressure drop through the adapter curb is negligible, 12" WIDE STANDING SEAM PANELS For Horizontal return applications: The power exhaust and barometric relief dampers must be installed in the return air duct, ACCESSORY PACKAGE NO. CRRFCURB013A00 Fig. 2 -- Horizontal Supply/Return Curb or adapter roof curb should be level. This is necessary to permit unit &'ain to function properly. Unit leveling tolerance is + 1/16 in. per linear ft in any direction. Refer to Accessory Roof Curb or Horizont_d Adapter Roof Curb Installation Instructions for additional information as required. ALTERNATE UNIT SUPPORT -- When the curb or adapter cannot be used, support unit with sleepers using unit curb or adapter support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side. Rig and Place Unit--Inspect unit for transportation &mmge. File any chfim with transpom_tion agency. Keep unit upright, and do not drop. Use spleader bm_ over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frmne as a reference; leveling tolerance is + I/v, in. per line;u ft in any direction. See Fig. 3 for additional information. Unit weight is shown in Table 1. CURB HEIGHT 1'-11" (584) DESCRIPTION Pre-Assembled Horizontal Adapter Roof Curb Adapter Installation (016-025 Only) 10'-0" (3048) ,SPREADER BARS / .__ Four lifting holes am provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit. POSITIONING -- Provide clearance around and above unit for airflow, safety, and service access (Fig. 4-6). Do not insUdl unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated _fil: guard against water from ROOF MOUNT -- Check building codes for weight distribution requirements. "DETAIL A" RIGGING HOOK 3'-7 1/2" (t to51 Step 2 -- Although unit is weatherproof, higher level runoff and overhangs. DUCT UNIT BASE RAIL SEE DETAILA" UNIT 50TM DIMENSIONS MAXIMUM SHIPPING WEIGHT A B Ft-in. mm R-in. mm 810 6-111_ 6-111_ 2121 2121 4- 0 3-10 1219 1168 864 6-111_ 2121 3- 7 1092 1023 6-111_ 2121 3- 5 1041 016 Lb 1725 Kg 782 020 1785 025 1905 028 2255 NOTES: 1. Dimensions in ( ) are in millimeters, 2. Refer to Fig. 4-6 for unit operating weights. 3. Remove boards at ends of unit and runners prior to rigging. 4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars. 5. Weights do not include optional economizer. Add 90 Ib (41 kg) for economizer weight. See Table 1 for MoistureMi$er TM dehumidification package weight. 6. Weights given are for aluminum evaporator and condenser coil plate fins. All panels must be in place when rigging. Fig. 3 -- Rigging Details 9. {274} J / G' / / _ SUPPLY DUCTWORK BELOW ELECTRIC HEATERS 3 _ _ 7/8 ©]_\ D©NCENTR}C _.O. I} D K.0. / s1_ / ('...... NI:R MUST BE INSTALLED ON THE FOR UNITS EOUIPPEO WITH 4_ / 0UTDGOR COIL A 90 DEGREE ELBOW THE UNIT DISCHARGE C / -" ((} g 3/8" { A COND J NTR C K 0 / (3! ::ss _f {5/) '_3/4 _ £PT DRA]N {27) FAR SiDE CONNECTION @4i Y (3_0} Fig. 4 -- Base Unit Dimensions (1676) i 50TM016,020 S CT] ON A a _B Fig. 5 J Base Unit Dimensions J 50TM025 i/{l!/[): QLJIPP[I) ['E( OR 0 ,, CO_ER (iE{)>OWE_) :,8 o • i {,, / i ©" • '8" , HEN N }AN I COil bO_AI T / ,_ R .oo) v i .... O" (99) ONL 0 / sl "3" 2, _/cO0+iZER ,/ / { IOLE 0" .:.7 8/IS . IO CURS 0 X s_ , [ N 1/8" _/4: 7 (2) / _ : 0 _) S N o',/c, _Rv w C""_ (02, _7/8 _,o" m :! CT O_ RB AC RY H LL IETER8. (i97 _ ........................................................................................... .... _CON[.... _0 I • R : ArCE N i _ ) O" 4 _ /(1C2 [ 2 0 ( ) "_. 0'1 .2/4) | _- j S F. _-L i l ...... Z O' -q 2 //8' (2182) i i ...... - | 8,o ° (189) io ASS /E >RO>R CON) NSER FAh, O>ERAI ON LOCAl CO{)S 0 J; !)C /8N SAY PR[_A , M!ll lie EXC PT ON OF C ARANC [0 q CON[)[ £{R COl &N) H{ [}A,NRiR/R()W[IR EXiqAU AS $ AIEi) IN NOI _B, A REIO/ABLE FENCE OR BARR CDDE RE© AEE NO CLEARANCE 76 . \_ , 3,1o Y_ 0"7 _ _ L_ 59" .....,/<3 _ , . I ._ (" i e - J i ..................... 1 _ _ | : 1 D C _ORK ]0 8E / rTt_C ED ]0 DCCE5807_ _OOf bllN MUhl C ESbtNOE REAR 70" (21 ]4) FOR C)i R MO'_A F RIDUCi ) 0 4"0" (129) COND J ONE Pqb _ _ 5- LV 5 6 i AETUY_N 707) R f i DISEN510 p> " IICAL 1 2 ,,/, i _ n' I01{ .... ;//d ] _. .50 i) A YPCA[ OLi i i Table1 -UNIT 50TM NOMINAL CAPACITY (tone) OPERATING WEIGHT (Ib) Economizer MoistureMi$er TM Dehumidification Package Physical Data 016 020 025 028 15 1650 90 40 16 1710 90 40 20 1770 90 40 25 2120 90 40 11..,ZR72KC _.ZR94KC, 11,_ZR94KC ...ZRIOSKC, I 11._ZR108KC ._ZR125KC, 2 60, 60 40 85, 2 55, 45 106, 81 I 2 55, 45 106,106 COMPRESSOR/MANUFACTURER Quantity..,Model Scroll, Copeland (Ckt 1, Ckt 2) Number of Refrigerant Circuits Capacity Stages Oil (oz) (Ckt 1, Ckt(%) 2) REFRIGERANT TYPE Expansion Device Operating Charge (Ib-oz) 19-6 I 2 Rows,..Fins/in, Total Face Area (sq ft) 4...15 21,7 (in.) I 10,500 10,500 V2...1050 3,..22 1100 Cross-Hatched 17.5 4...15 6.13 184T Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Min/Max (in.) Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Nominal Fan Shaft Diameter Belt, Quantity..,Type...Length (in.) (in,) Pulley Center Line Distance (in,) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns From Closed Position Factory Speed Factory Speed Setting (rpm) LOW-PRESSURE Cutout Reset (Auto) Low-Medium High Static Static Low-Medium High Static Static Low-Medium High Static Static Low-Medium High Static Static Low-Medium High Static Static Low-Medium High Static Static at Pulley (in.) SWITCH I 2,,,12 x 12 Belt 6000 5 1745 Maximum Continuous Bhp Motor Frame Size Nominal Rpm High/Low Fan Rpm Range Fan Shaft Diameter 4_.15 21,7 V2_.1050 3,.,22 1100 COIL Rows,..Finslin, Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in,) Type Drive Nominal Cfm Motor Hp Motor Nominal Rpm HIGH-PRESSURE Cutout Reset (Auto) 18-11I 19-2 873-1021 1025-1200 Ball 1550 4.9/5,9 4.9/5,9 1 _& 9,4 8,0 17/16 1,,,BX...50 1,,,BX...48 13.3-14.8 37 44 6** 3,5 965 1134 17/16 I 4_.15 21.7 I 3_,1543.4 (2 coils) Propeller Type I 14,200 21,000 1 ,,,1075 2.,.30 3400 I V2...1050 6.,,22 2200 3/8-in. Copper Tubes, Aluminum Copper Plate Fins, Face Split 17,5 4...15 Lanced or 17.5 4_.15 I 910-1095 1069-1287 Ball 1550 4,9/5.9 4,9/5.9 11/8 9.4 8.0 17/16 1..,BX,..50 1._BX,.,48 13.3-14.8 37 34 17,5 4._15 I Centrifugal Type 2.,,12 x 12 2,.,12 x 12 Belt Belt 7200 8000 5 7.5 1745 1745 8.7 [208/230, 575 v] 5.90 9,5 [460 v] 184T 213T 2,.,12 x 12 Belt 10,000 10 1740 10.2 [208/230, 575 v] 11,8 [460 v] 215T 1002-1151 1066-1283 1332-1550 Ball 1550 4.9/5,9 4.9/5,9 13/8 8,0 6.4 1193-1369 Ball 1550 5.4/6.6 5.4/6.6 13/8 9.4 7.9 17/16 1._BX_.53 1_.BX._50 14.6-15.4 37 44 6tt 3.5 1002 1178 17/16 17/16 2,..BX-,50 2,.,BX-,47 14.6-15,4 36 45 6tt 3.5 1182 1470 6** 3.5 1095 1303 17/16 17/16 (psig) SWITCH (psig) 27 44 THERMOSTAT (F) 30 _+5 45 _+5 OUTDOOR-AIR INLET SCREENS Quantity,.,Size (in,) Cleanable 2...20 x 25 x 1 1,,.20 x 20 x 1 RETURN-AIR FILTERS Quantity,..Size (in.) Throwaway*** 4.,.20 x 20 x 2 4._16 x20 x2 POWER EXHAUST V2 Hp, 208/230-460 LEGEND --- 25-10 426 320 FREEZE PROTECTION Opens Closes Bhp TXV 26-13 13-14 Cross-Hatched 3/8-in. Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins CONDENSER FAN Nominal Cfm EVAPORATOR 19-6 I 13-8 COIL Motor Hp,.,Rpm Quantity..,Diameter Watts Input (Total) 2 50, 106 50 136, R-22 TXV c,rcuittt Circuit CONDENSER 1 _.ZRU140KC,* 1 _.ZR144KC Brake Horsepower Thermostatic Expansion Valve *The ZRU140KC compressor is a tandem compressor, consisting of a ZR72KC (25% total capacity) and a ZR68KC (24% total capacity), tCircuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and Circuit 2 uses the upper portion of both coils, **Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to 11/2turns open, v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v) tl-Pulley has 6 turns. Due to belt and pulley size, movable pulley cannot be set to 0 to V2 turns open, ***The 50TM028 unit requires 2-in, industrial-grade filters capable of handling face velocities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). NOTE: The 50TM016-028 on the suction side. units have a low-pressure switch (standard) located Step 3 -- Field Fabricate Ductwork -- Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned insulated and covered with a vapor barriel: space must be The 50TM units with electric heat require a l-in. clearance for the first 24 in. of ductwork. Outlet grilles must not lie directly below unit disch_u'ge. NOTE: A 90-degree elbow must be provided in the ductwork to comply with UL (Underwriters Laboratories) codes for use with electric heat. Step 4 -- Make Unit Duct Connections -- Unit is shipped for through-the-bottom duct connections. Ductwork openings tue shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. Attach all ductwork to roof curb and roof curb basepans. Refer to installation instructions shipped with accessory roof curb for mole information. Step 5 -- Trap Condensate Drain -- See Fig. 4-6 trod 10 for di'ain location. Plug is provided in drain hole and must be removed when unit is operating. One :V4-in. halfcoupling is provided inside unit evaporator section for condensate drain connection. An 81/2 in. x :V4-in. diameter nipple and a 2-in. x :V4-in. diameter pipe nipple are coupled to standard 3/4-in. diameter elbows to provide a straight path down through holes in unit base rails (see Fig. 11 ). A trap at least 4-in. deep must be used. For vertical supply and leturn units, tools or pmls could diop into ductwork and cause an injury. Inst_dl a 90-degree turn in the return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Due to electric heatel: supply duct will require 90-degree elbow. EVAPORATORFAN MOTOR ! BAFFLE Shaded area indicates block-off panels. NOTE NOTE: Dimensions A, A', and B, B' are obtained from field-supplied ceiling diffuser. Fig. 9 -- L V! Concentric Duct Details OUT NOTE: Do notdrill inthisarea;damage tobasepanmay result in water leak. Fig. 7 -- Air Distribution -- Thru-the-Bottom \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ NOTE 3/4" FPT DRAIN CONNECTION 1-3/8" DRAIN HOLES Fig. 10Condensate Drain Details (50TM016,020 Shown) AIR OUT AIR IN AIR OUT NOTE: Do not drill in this area; damage to basepan may result in water leak. Fig. 8 -- Concentric Duct Air Distribution 3/4" PPT DRAIN / 2-IN, (FIELD-SUPPLIED) NIPPLE / CONNECTION /HALF IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. ]_ ,e 3" BASE RAIL Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. _-__._ FIELD CONTROL WIRING -- Install a Carrier-approved accessory thermostat assembly according to the installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature. 81/2-1N. (FIELD_---'= SUPPLIED) NIPPLE Fig. 11 -- Condensate Step 6 -- Drain Piping Details Make Electrical FIELD POWER SUPPLY age shown on nameplate. When installing (National Electrical (Table 2). All field requirements. wMng Route thermostat cable or equiwdent single leads of no. 18 AWG (American Wire Gage) colored wire from subbase temrinals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 13. Connections -- Unit is factory wired for volt- NOTE: For wire runs up to 50 It, use no. 18 AWG insulated wire (35 C minimum). For 50 to 75 fi, use no. 16 AWG insulated wire (35 C minimum). For over 75 It, use no. 14 AWG insulated wire (35 C minimum). All wire lmger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. units, provide a disconnect, per NEC Code) requirements, of adequate size must comply with NEC and loc:d Set heat anticipator settings as indicated in Table 3. Settings may be changed slightly to provide a greater degree of comfort for a particular inst_dlation. Route power lines through control box access panel or unit basepan (Fig. 4-6) to connections as shown on unit wiring diagram and Fig. 12. Operating voltage to compressor must be within voltage range indicated on unit nmneplate. On 3-phase units, voltages between phases must be balanced within 2% and the current must be b_danced within 10%. ----] TBt I b w_ z W z z o_ ow o3o. The correct power phasing is critical in the operation of the scroll compressors. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to plemature complessor failure. Use the following formula to determine the percentage of voltage imbalance. Percentage of Voltage Imbalance EQUIP TB1 MAXIMUM WIRE SIZE = 100 x max voltage deviation fiom average voltage average voltage EXAMPLE: A B C GND UNIT 50TM All Supply voltage is 460-3-60. AB = 452 v 350 208/230 kcmil I VOLTAGE 460 2/0 575 2/0 LEGEND EQUIP GND kcmil NEC TB AC = 455 v BC = 464 Voltage v Average = 455 + 464 + 455 3 ------ Equipment Ground Thousand Circular Mils National Electrical Code Terminal Block Fig. 12- 1371 3 Field Power Wiring Connections = 457 Determine (AB) 457 (BC) 464 (AC) 457 Maximum maximum deviation - 452 = 5 v - 457 = 7 v - 455 = 2 v deviation is 7 v. from average Determine percent voltage imbalance: voltage: THERMOSTAT ASSEMBLY JUMPER I 7 Percentage of Voltage [mbalance = 100 x- 457 Cl cc = 1.53% m _ Z a_ O Z _ m m UNIT LOW-VOLTAGE CONNECTIONS Fig. 13 -- Field Control Thermostat Wiring This amount of phase imbalance is satisfacto U as it is below the maximum allowable 2%. 10 7- Table 2 -- Electrical Data UNIT 50TM NOMINAL VOLTAGE (3 Ph, 60 Hz) 208/230 VOLTAGE RANGE Min 187 Max 253 COMPRESSOR No. 1A No, 1 RLA 32.1 LRA 195 RLA LRA OFM No. 2 RLA 20.7 LRA 156 Qty 3 Hp 0.5 POWER EXHAUST IFM FLA (ea) 1.7 Hp 5.0 FLA 15.8/15.8 FLA LRA ELECTRIC HEAT* kW FLA --- 575 208/230 414 518 187 508 633 253 16.4 12 30.1 95 80 225 10 8.2 28.8 70 54 195 3 3 3 0.5 0.5 0.5 0.8 0.75 1.7 5.0 5.0 5.0 7.9 020 460 575 208/230 414 518 187 508 632.5 253 15.5 12.1 42 114 80 239 14.7 10.8 33.6 95 80 225 3 3 0.8 0.5 2 1 0.8 0.8 6.6 5.0 5.0 7.5 7.9 6.0 25.0/25.0 575 414 518 508 632.5 19.2 13.8 125 80 17.3 13.5 114 80 2 2 1 1.0 3.3 3.4 7.5 7.5 13.0 4.6 18.8 26/34 26/34 4.6 18.8 42/56 42/56 4.6 18.8 56/75"* 56/75"* -- 41 50 2.3 6.0 -- -- 43 50 2.3 6.0 32 32 39 39 59 62 60 70 2.3 6.0 55 55 66 66 76 79 90 90 2.3 6.0 80** 80** 96 96 106 109 125 125 2.1 4.8 -- --- 31 34 40 40 4.6 18.8 -- --- 4.6 18.8 26/34 26/34 4.6 18.8 42/56 42/56 4.6 18.8 2.3 71/ 82 71/ 82 109/122 114/128 110/128 125/180 117/135 117/135 166/155 172/161 175/175 178/175 156/180 156/180 176/200 182/206 200/225 200/225 82 82 87 92 110/110 110/110 109/122 114/128 110/125 125/150 117/135 117/135 166/155 172/161 175/175 175/175 56/75 56/75 156/180 156/180 176/200 182/206 200/225 200/225 6.0 -- --- 44 47 50 60 2.3 6.0 32 32 39 39 59 61 60 70 2.3 6.0 55 55 66 66 76 79 90 90 2.3 6.0 80 80 96 96 106 109 125 125 2.1 4.8 -- --- 34 36 40 40 4.6 18.8 -- --- 4.6 18.8 26/34 26/34 4.6 18.8 42/56 42/56 4.6 18.8 56/75 56/75 -- 61 80 2.3 6 -- -- 63 80 2.3 6 32 32 39 39 65 68 80 80 2.3 6 55 55 66 66 82 85 90 90 2.3 6 80 80 96 96 112 115 125 125 2.1 4.8 -- --- 48 50 60 60 10.0 71/ 71/ 87/ 92/ 124/124 129/129 150/150 150/150 124/134 129/140 150/150 180/150 117/135 117/135 178/166 183/172 200/175 200/175 156/180 156/180 187/211 193/217 200/228 200/225 71/ 82 71/ 82 Tab_confinued 1! 110/110 110/110 -- 025 460 MOCPt 18.8 6.0 15.8/15.8 MCA 82/ 82 86/ 86 4.6 016 460 POWER SUPPLY on next page. Table 2 -- Electrical Data (cont) UNIT 50TM NOMINAL VOLTAGE (3 Ph, 60 Hz) 208/230 VOLTAGE RANGE Min 187 Max 253 COMPRESSOR No, 1A No. I RLA 20.7 LRA 156 RLA 20.7 LRA 156 OFM No, 2 RLA 47.1 LRA 245 Qty 6 Hp 0.5 POWER EXHAUST IFM FLA (ea) 1.7 Hp FLA FLA 10.0 28.0/28.0 028 46O 578 414 518 508 622.5 10.0 16.4 75 108 10.0 8.2 75 54 19.6 15.8 125 100 6 6 0.5 0.5 10.0 0.8 0.8 10,0 LEGEND FLA HACR IFM LRA MCA MOCP NEC OFM RLA ---------- IMPORTANT: 178/178 175/178 138/188 143/143 178/178 178/178 4.6 18.8 26/34 26/34 4.6 18.8 42/56 42/56 117/135 117/135 181/170 187/176 200/175 200/200 4.6 18.8 56/75 56/75 156/180 186/180 191/215 197/221 200/225 200/225 2.3 6 -- -- 64 66 8O 80 2.3 6 32 32 39 39 67 70 80 80 2.3 6 55 55 66 66 84 87 90 100 2.3 6 80 80 96 96 114 117 125 125 2.1 4.8 -- -- 54 56 60 70 71/ 82 71/ 82 is satisfactory ty company as it is below the maxi- is more than 2%, con-] tamed ate y. J MCA calculation for 50TM016-028 units with electric heaters over 50 kW = (1.28 x IFM amps) + (1.00 x heater FLA). 4. Use the following table to determine heater capacity at actual voltage. HEATER RATING VOLTAGE 200 208 ACTUAL HEATER VOLTAGE 230 240 240 0.694 0.781 0.918 1.000 480 EXAMPLE: LIST_O 452 + 464 + 455 3 1371 3 = 487 12 380 440 460 480 0.626 0.840 0.918 1.000 34 kW (at 230 v) heater on 208 v = 34.0 (.751 mult factor) = 25.8 kW capacity at 208 v. AB = 452 v Average Voltage = BC = 464 v -- -- AC = 455 v (_ MOCPt 3. max voltage deviation from average voltage average voltage C MCA 138/138 143/143 18.8 Supply voltage is 480-3-60. B FLA If the supply voltage phase imbalance tact your oca e ectr cut NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance, % Voltage Imbalance A kW 4.6 = 1.53% This amount of phase imbalance mum allowable 2%. *Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. Heaters are rated at 240 v and 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. To determine heater capacity at actual unit voltage, multiply 240 v or 480 v capacity by multipliers found in table in Note 4. tFuse or HACR circuit breaker. **Electric heaters are field installed. EXAMPLE: 13,0 LRA POWER SUPPLY Determine maximum deviation from average voltage. (AB) 487 - 482 = 8 v (BC) 464 - 487 = 7 v (AC) 487 - 488 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance. 7 % Voltage Imbalance = 100 x 45_ Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps MinimumCircuitAmps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps = 100 x 14.6 ELECTRIC HEAT* Table 3 -- Heat Anticipator Settings UNIT 50TM UNIT VOLTAGES kW* 26/34 42/56 56/75 208/230-3-60 016-028 32 55 80 460-3-60 Step 7 -- Make Outdoor-Air STAGE 1 STAGE 2 .40 .66 .66 .66 .40 .66 .40 .40 .66 .40 .66 .66 Inlet Adjustments MANUAL OUTDOOR-AIR DAMPER -- All units (except fllose equipped with a factory-inst_dled economizer) have a manual outdoor-air &lmper to provide ventilation tdl: Dmnper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move &tmper to desired setting. Then retighten screws to secure &tmper (Fig. 15). 25% ADJUSTABLE AIR DAMPER *Heater kW is based on heater voltage of 208 v, 240 v or 480 v. OPTIONAL NON-FUSED DISCONNECT -- On units with the optional non-fused disconnect, incoming power will be wired into the disconnect switch. Refer to Fig. 14 for wiling for 100 and 200 amp disconnect switches. Units with an MOCP under 100 will use file 100 amp disconnect switch. Units with an MOCP over 100 will use the 200 amp disconnect switch. Refer to the applicable disconnect wiring diagrmn. BASE UNIT To prevent breakage during shipping, file disconnect handle and shaft are shipped and packaged inside the unit control box. Install file disconnect handle before unit operation. To install the handle and shaft, perform the following procedure: J SECURING 1. Open the control box door and remove the handle and shaft fi'om shipping location. 2. Loosen the Allen bolt located on the disconnect switch. The bolt is located on the square hole and is used to hold the shaft in place. The shaft cannot be inserted until the Allen bolt is moved. 3. Fig. 15 -- 25% Outdoor-Air Tighten the Allen bolt to lock the shaft into position. Close the control box dool: 6. Attach the handle to the external access door with file two screws provided. When the handle is in the ON position, the handle will be vertical. When the handle is in the OFF position, the handle will be horizontal. 7. Turn the handle to the OFF position and close the door. The handle should fit over the end of the shaft when the door is closed. 8. Install Outdoor-Air Hood -- The same type of factory-installed hood is used on units with 25% air ventilation and units with an economizel: IMPORTANT: If the unit is equipped with the optional EconoMiSerlV component, move the outdoor-air temperature sensor prior to installing the outdoor-air hood. See the Optional EconoMiSerIV and EconoMiSer2 section for more information. Personal Injury Hazard. Avoid possible injmN by keeping fingers away [roln dmnper blades. NOTE: The hood top panel, upper trod lower filter retainers, hood diain pan, baffle (028), and tilter support bracket are secured to the unit and shipping skid at the opposite end of the unit in front of the condenser coil. The screens, hood side panels, remaining section of filter support bracket, seal strip, and _dl other hardwme are in a package located inside file return-air tilter access panel (Fig. 16). 1. Attach seal strip to upper filter retainel: See Fig. 17. The handle must be in the OFF position to open the control box dool: OPTIONAL CONVENIENCE OUTLET-On units with optional convenience outlet, a l15-v GFI (ground fault interrupt) convenience outlet receptacle is provided for field wiring. Field wiring should be run through the 7/8-in. knockout provided in the basepan near the return air opening. 2. UNIT I00 AMP BLK. WIRING YEL. 6T3 4T2 2T1 LOAD 3. BLU. POWER SUPPLY UNIT 200 AMP BLK. 5L3 3L2 1L1 LINE Slide baffle (size 028 unit) behind lower filter retainer and tighten screws. 5. Ix_osen sheet metal screws for base unit top panel located above outdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoor-air inlet opening. 6. Match notches in hood top panel to unit top panel screws. Insert hood thmge between unit top panel flange and unit. Tighten screws. 7. Hold hood side panel flanges flat against unit, and install screws removed in Step 5. 8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket. 9. Attach remaining WIRING YEL, BLU. [ ONITPDWER , I NON FUSED DISCONNECT F]ELD POWER SUPPLY NOTE: The disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label. Fig. 14 -- Optional Non-Fused Disconnect Wiring 13 Assemble hood top panel and side panels, upper filter retainer, and hood drain pan (Fig. 18). Secure lower tilter retainer and long section of filter support bracket to unit. See Fig. 18. Leave screws loose on 028 units. 4. 100_ AMP FIELD Section Details Step 8 -- |nsert the disconnect shaft into the square hole on the disconnect switch. The end of the shaft is specially cut and the shaft can only be inserted in the correct orientation. 4. 5. SCREWS short section of filter support bracket. Step 9 -- OUTDOOR-AIR HOOD AND MOUNTING BRACKETS FILTER PACKAGEANE HOOD COMPONENTS ACCESS Fig. 16- PANEL Outdoor-Air Hood Component -- After ;dl the To avoid dmnage to the refiigelant coils and electric_d components, use recommended screw sizes only. Use care when drilling holes. Location PANEL UPPER Install All Accessories factory-installed options have been adjusted, install all fieldinst_dled accessories. Refer to the accessory inst_dlation instructions included with each accessory. MOTORMASTER® I CONTROL INSTALLATION (50TM016, 020, and 028 Only) Install Field-Fabricated Wind Baffles -- Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 19 for baffle details. Use 20-gage, galvanized sheet metal, or similar conosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles. Install Motormaster® I Controls -- Only one Motormaster I control is required for size 016 and 020 units. Two Motormaster I controls tue required for size 028 units -- one for circuit 1 and one for circuit 2. The Motommster [ control must be used in conjunction with the Accessory 0 ° F Ix_w Ambient Kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 (and 4 on size 028 units) while outdoor fans no. 2 and 3 (and 5 and 6 on size 028 units) are sequenced off by the Accessory 0 ° F Low Ambient Kit. HOOD DRAIN FILTER. RETAINER Accessom" 0 ° F I_m' Ambient Kit -- Install the Accessory Low AmiNent Kit per instruction supplied with accesso% Sensor Assemb@ -- Install the sensor assembly shown in Fig. 20. Fig. 17 -- Seal Strip Location (Air Hood Cross-Sectional View) BAFFLE 0° F in the location (028 ONLY) WIND j/t \ / /_4 BAFFLE __ RETAINER _ I LOWER FILTER FILTER SUPPORT i BRACKET \ / ___CROSS BREAK A \ \ HOOD SIDE PANELS (2) \ HOOD BAFFLETOP VIEW 1"(25)MIN---jl TOP _ PANEL 80"+2" _^ +50) -0" ,_z_z-0 BAFFLE I -- 10" (254) 40" (1016) • LOWER FILTER RETAINER •_10" - FILTER SUPPORT BRACKET "-'----_1 ÷ HOOD UPPER FILTER DRAIN PAN 3/4" (19)(TYP)--,,-t BAFFLE FRONTVIEW RETAINER NOTE: The outdoor-air hood comes with a baffle which is used on 028 units only; discard baffle for 016-025 units. Fig. 18 -- Outdoor-Air Hood *+-I-- - _,- NOTE: Dimensions in ( ) are in mm. Fig. 19 -- Details 14 Wind Baffle Details (254) (]yp) 1 15" (381) (rYp) 1" (25) MIN Motor Mount- To ensure proper fan height, replace the existing motor mount with the new motor mount provided with accessory. Trarl._fbrmer (460 and 575-v Ulli_ Only) -- On 460 and 575-volt units a transfonner is required. The transformer is provided with the accessot T and must be field-installed. Motormaster I Control -- Recommended mounting location is on the inside of the panel to the left of the control box. The control should be mounted on the inside of the panel, vertically, with leads protruding from bottom of extrusion. MOTORMASTER® V CONTROL INSTALLATION (50TM025 only) Install Field-Fabricated Wind Baffles -- Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 19 for baffle details. Use 20-gage, galwmized sheet metal, or similar corrosion-resistant met:d for baffles. Use field-supplied screws to attach baffles to unit. Screws should be I/4-in. diameter and 5&-in.long. Drill required sctew holes for mounting baffles. m SENSOR LOCATION To avoid dmnage to the refliget_tnt coils and electric_d components, use recommended screw sizes only. Use care when drilling holes. Install Motormaster V Controls -- The Motortnaster V control is a motor speed control device which adjusts condenser fan motor speed in response to declining liquid refrigetant pressure. A properly applied Motormaster V control extends the operating range of air-conditioning systems and permits operation at lower outdoor ambient temperatures. The minimum ambient temperatures at which the unit will operate are: TEMPERATURE Standard Unit ] 40 (4) [ OPERATING Unit with Low Ambient LIMITS -Kit HAIRPIN END HAIRPIN 50TM016 NOTE: All sensors bottom. END -20 ITEM DESCRIPTION CRLOWAMB015A00 480 CRLOWAMB016A00 575 CRLOWAMB017A00 FROMFUSEBLOCK m o TO PRESSURE TRANSDUCER TO MOTOR(S) Table 5 -- Applicable Voltages and Motors Fig. 21 -- Motormaster_) I COMPATIBLE END 50TM028 (CIRCUITS 1 AND 2) are located on the eighth hairpin up from the (-29) 208/230 460-3-60 208/230-3-60 575-3-60 HAIRPIN F° (C °) VOLTAGE ] _0 Fig. 20 -- Motormaster(_) I Sensor Locations Table 4 -- Motormaster V Control Package Usage VOLTAGE LOCATION Unit with MMV Control 25 (-4) 50TM025 SENSOR_ O 50TM020 To operate down to the ambient temperatures listed, Motormaster V controls (Fig. 21) must be added. Fieldfabricated and inst:dled wind baftles are also required for all units (see Fig. 19). The Motormaster V control permits operation of the unit to an ambient temperature of-20 F (-29 C). The control regulates the speed of 3-phase fan motot:s that me compatible with file control. These motors are factory installed. See Table 4 for the Motormaster V control accessory package usage. Table 5 shows applicable voltages and motors. Replacement of fan motor IS NOT REQUIRED ON CURRENT PRODUCTION UNITS since the control is compatible with the factory-installed fan motors. Only field wiring control is requited. Install the Motormaster V control per instructions supplied with accessory. UNIT m _o°O _o ° _oo°o _o ° _oo°o _o ° _oo°o _o ° _oo°o _o ° _oo°o _o ° €_o °° SENSOR-_o o LOCAT,ON _ o _oo°o _° ° _oo°o _° ° _oo°o _°o° MOTOR* HD52AK684 H D52AK654 HD52GE576 *Motormaster V compatible motors, P/N HD52AK654 for 208/230, 460 v and P/N HD52GE876 for 878 v, are installed in units with serial numbers 2801F and later. For units with serial numbers before 2801F, motor changeout is required prior to installing the Motorrnaster V control package. 15 V Control Step 10- Adjust PREMIERLINK Factory-Installed CONTROL TM -- Options Tile PmmierLink Install control- ler is available as a special order from the factory and is compatible with the Carrier Comfort Network® (CCN) system. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. Cmrier's diagnostic standard tier display tools such as Navigator TM device or Scrolling controllen Marquee can be used with the controller thermostat (see Fig. 22) requires or a CCN connection bl_)adcast its interred timeclock. to initiate This The the use of for time is necessm-y for bl_)adcast of time of day functions (occupied/unoccupied). No sensoLs me supplied with the field-mounted PmmierLink control The factory-installed PremierLink control includes only the supply-air temperature (SAT) sensor and the outdoor air temperature (OAT) sensor as stan&trd+ An indoor air quality (CO2) sensor can be added as an accessory. Refer to Table 6 for sensor usage. Refer to Fig. 23 for PmmierLink controller wiring+ The PremierLink control may be mounted in the control panel or an mea below the control INPUTS panel. OUTDOOR AIR QUALITY DUAL MODE SENSOR (STAT) is wire-tied inside the unit control I ....... R_ -- the Indoor Air Quality (CO22 Sensor Instructions for O I I I .....m<2+++__ Mount Pm_NlI,+bm: ItIC_P¢_ _,,=+,,+ ----" u==+,+ .... J ] ¢m_ i +s_ = I_ ] + i r4 i +IIO_IEN[III 1 ./ ,] -"++-+++ l 1111 _++_m mm_ COMP SAFETY (Y1) FIRE SHUTDOWN (Y2) SUPPLY FAN STATUS(W1) .Iio +Iqq'l'l+'l'I m_ ......... omm_ NOT USED (W2) ..................... .+J ENTHALPY STATUS(ENTH) / / CCN/LEN PORT the and IAQI termimds of J5 to the PremierLink Instal- Start-up, and Configuration and configuration information. +++_I_+i PremzerL_nk i m_" _l , w+_ =, q _7 III for Install O _ %%:_II box The outdoor-air and wired. No O i Sensor Outdoor Air Temperature (OAT) Sensor -temperature sensor ((-)AT) is factory-supplied adjustment is necessary. lation, wiring SET POINT INDOOR AIR QUALITY SAT sensor Wire the CO2 sensor to the COM on the PremierLink controller Refer SPACETEMP SUPPLY AIR TEMP OUTDOOR TEMP (SAT) accessory indoor air quality (COs) sensor according to manufacturer specifications. A sepm'ate field-supplied transformer must be used to power the CO2 sensol: NOTE: PmmierLink controller version 1.3 and later is shipped in Sensor mode (for use with space of mtum sensor). If used with a thermostat, the PremierLink controller must be configured to Thermostat mode. HVAC SENSOR Air Temperature shipping. Remove the sensor for installation. Locate a suitable location on the supply duct beneath the curb for SAT installation. Drill or punch a I/2-in. hole in the duct. Use two fieldsupplied, self-drilling screws to secure the sensor probe in a horizontal orientation. Route wiring from the sensor through the unit's control voltage hole in the unit base pan. Connect the sensor wires to J6 connector's Pin 5 (BRN lead) and Pin 6 (ORN lead) as indicated in Fig. 23. PremierLink The PremierLink a Canier electronic the Supply NOTE: The sensor must be mounted in the discharge tfirstmam downstream of the cooling coil and any heating devices. Be sure the probe tip does not come in contact with any unit or heat surfaces. t NAVIGATOR PORT / 4+20MA ECONOMIZER f "4 "-4 "-., COMPR HEAT EXHAUST INDOOR PANMOTOR 1 &2 OUTPUTS Fig. 22 -- PremierLink Controller 16 LOW/HIGH RVS VALVE detailed Table 6 -- PremierLink APPLICATION Differential OUTDOOR AIR TEMPERATURE SENSOR TM Sensor Usage RETURN AIR TEMPERATURE SENSOR OUTDOOR AIR ENTHALPY SENSOR RETURN AIR ENTHALPY SENSOR Required -33ZCT55S PT -- -- -- Required -33CSENTHSW or HH57AC077 -- -- Required -33CSENTHSW (HH57ZC003) or HH57AC077 Required33CSENTSEN or HH57AC078 Dry Bulb Temperature with PremierLink* (PremierLink requires 4-20 mA Actuator) Single Enthalpy with PremierLink* (PremierLink requires 4-20 mA Actuator) Differential Enthalpy with PremierLink* (PremierLink requires 4-20 mA Actuator) Included -HH79NZ039 or Equivalent Included -Not Used Included -Not Used *PremierLink control requires supply air temperature sensor 33ZCSENSAT and outdoor air temperature sensor HH79NZ039 -- Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control. NOTES: 1. CO2 Sensors (Optional): 33ZCSENCO2 -- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPCO2 -- Aspirator box used for duct-mounted CO2 room sensor. 33ZCT55CO2 -- Space temperature and CO2 room sensor with override. 33ZCT56CO2 -- Space temperature and CO2 room sensor with override and setpoint. 2. All units include the following Standard Sensors: Outdoor-air sensor -- 50HJ540569 -- Opens at 67 F, closes at 52 F, not adjustable. Mixed-air sensor -- HH97AZ001 -- (PremierLink control requires supply air temperature sensor 33ZCSENSAT and outdoor air temperature sensor HH79NZ039) Compressor lockout sensor -- 50HJ540570 -- Opens at 35 F, closes at 50 E ]7 ® DDCCONTnOL CMPSAFE Y1 _TH FSD Y2 SFS Wl NOTUSEn W2 ® ® nMTOCC C X EFIMELDTAT _c G (D © Q G TSTATCONTnOL C X Fig. 23 -- Typical PremierLink TM BOTJ401148 ECONOMIZE_ (CnECOMZn010B00) OAT PL PWR SAT TB TRAN Controls ENTHALPY SWITCH/RECEIVER -- The accessoly enthalpy switch/receiver (33CSENTHSW) senses temperature and humidity of the air sulTounding the device and c_dculates the enthalpy when used without an enthalpy sensoc The relay is energized when enthalpy is high and deenergized when enthalpy is low (based on ASHRAE [American Society of Heating, Refrigeration and Air Conditioning Engineers] 90.1 criteria). [f an accessol y enthalpy sensor (33CSENTSEN) is attached to the return air sensor input, then differential enthalpy is c_dculated. The relay is energized when the enlhalpy detected by the return air enthalpy sensor is less than the enth_dpy at the enthalpy switch/receivec The relay is deenergized when the enthalpy detected by the return air enth_dpy sensor is gleater than the enlh_dpy at the enthalpy switch/receiver (differential enthalpy control). See Fig. 24 and 25. is done using an average LEGEND Outdoor Air Temperature Sensor Plug Power Supply Air Temperature Sensor Terminal Block Transformer Control Mode) (National Electrical Manufacturers Association) enclosure and should be mounted in a location that is not exposed to outdoor elements such as rain or snow. Use two field-supplied no. 8 x 3/4-in. TEK sclews. Insert the screws through the holes in the sides of the enthalpy switch/receivec Wiring -- Carrier recommends the use of 18 to 22 AWG (American Wire Gage) twisted pair or shielded cable for all wiring. All connections must be made with l/4-in, female spade connectors. A 24-vac transformer is required to power the enthalpy switch/receiver; as shown in Fig. 26, lhe PlemierLink botud provides 24 vac. Connect the GND and 24 VAC terminals on the enlhalpy switchheceiver to lhe terminals on lhe tmnsformec On some applications, the power from the economizer harness can be used to power the enth'.Apy switch/receivec To power the enthalpy switch/receiver from the economizer harness, connect power of the enthalpy switchheceiver to the led and brown wires (1 and 4) on the economizer harness. OUTDOOR ENTHALPY CONTROL (Fig. 26) -- Outdoor enthalpy control lequires only an enth_dpy switch/receiver (33CSENTHSW). The enthalpy switch/receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy. The enthalpy switch/receiver enelgizes the relay output when the outdoor enthalpy is above 28 BTU/Ib OR dry bulb temperature is above 75 F and is deenergized when the outdoor enthalpy is below 27 BTU/Ib AND diy bulb temperature is below 74.5 E The relay output is wired to the unit economizer which will open or close depending on the output of the switch. NOTE: The enlhalpy calculation tude of 1000 ft above sea level. Wiring (Thermostat ------- For connection to rooftop units with PremierLink control, connect the LOW Enthalpy termimfl on lhe enthalpy switch/receiver to J4 -- pin 2 of the PlemierLink control on the HVAC unit. The switch can be powered through the PremierLink control board if desired. Wire the 24 VAC terminal on lhe enthalpy switchheceiver to J4 -- pin 1 on the PremierLink control. Wire the GND termin:d on the enthalpy switch/receiver to Jl -pin 2 on the PremierLink control The HI Enthalpy terminal is not used. See Fig. 26. _dti- Mounting -- Mount lhe enthalpy switch/receiver in a location where the outdoor air can be smnpled (such as the outdoor air intake). The enthalpy switch/receiver is not a NEMA 4 18 1. @ Thermistor F Fig. 24 -- Enthalpy Switch/Receiver (33CSENTHSW) Humidity Sensor Thermistor Dimensions S Humidity Fig. 25 -- Enthalpy Sensor Dimensions (33CSENTSEN) 0 0 T_T_T_ _U SPT I_K _r_ ...... Sensor _O_ 1 ¢ I { I Part Nurn_m 33CSPREMLK _ c_ei maP_ _i _2 _v pw .gB_....9.ON... ...... - - - -G_Y--'- _E_ ....... I I / I I I I I I I I __ (OR UNIT GROUND) \ *Used with Differential Fig. 26 -- Typical Wiring Schematic -- Carrier Rooftop 19 Unit with PremierLink TM Enthalpy Control only. Controls DIFFERENTIAL ENTHALPY CONTROL (Fig. 27) -Differential enthalpy control requires both an enthalpy switch/ receiver (33CSENTHSW) and an enthalpy sensor (33CSENTSEN). The enthalpy switch/receiver is mounted in the outdoor air inlet and calculates outdoor air enthalpy. The enthalpy sensor is mounted in the return airstream and calculates the enthalpy of the indoor ail: 4 screws holding the cover on the enthalpy sensor and then mmove the covet The factory settings for the jumpel,s am M3 and OFF. The mode jumper should be set to M3 for 4 to 20 mA output. The factory test jumper should remain on OFF or the enthalpy sensor will not calculate enflialpy. ENTHALPY SENSORS AND CONTROL -- The enthalpy control (HH57AC077) is supplied as a field-installed accessory to be used with the EconoMi$er2 damper control option. The outdoor air enth_dpy sensor is part of the enthalpy control. The separate field-installed accessory return air enflialpy sensor (HH57AC078) is required for differential enthalpy control. The enthalpy switch/receiver energizes the HI Enthalpy relay output when the outdoor enthalpy is greater than the indoor enthalpy. The LOW Enthalpy terminal is energized when the outdoor enthalpy is lower than the indoor enthalpy. The relay output is wired to the unit economizer which will open or close depending on the output of the switch. NOTE: The enthalpy calculation tude of 1000 ft above sea level. is done using an average NOTE: The enthalpy control must be set to the "D" setting for differential enthalpy control to work properly. The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the PremierLink controllel: Ix)cate the controller in place of gin existing economizer controller or near the actuatol: The mounting plate may not be needed if existing bracket is used. alti- Mounting -- Mount the enthalpy switch/receiver in a location where the outdoor air can be smnpled (such as the outdoor air intake). The enthalpy switch/receiver is not a NEMA 4 enclosure and should be mounted in a location that is not exposed to outdoor elements such as rain, snow, or direct sunlight. Use two field-supplied no. 8 x 3/4-in. TEK screws. Insert the screws through the holes in file sides of the enthtflpy switch/receivel: A closed contact indicates that outside air is preferred to the mtum ail: An open contact indicates that the economizer should remain tit minimum position. Mount the enthalpy sensor in a location where the indoor air can be sampled (such as the return air duct). The enflialpy sensor is not a NEMA 4 enclosure trod should be mounted in a location flint is not exposed to outdoor elements such as rain or snow. Use two field-supplied no. 8 x 3/4-in. TEK screws. Insert the screws through the holes in the sides of the enthalpy sensol: Outdoor Air Enthalpy Sensor/Enthalpy Controller (HH57AC077) -- To wire the outdoor air enthtflpy sensor, perform file following (see Fig. 28 and 29): NOTE: The outdoor air sensor can be removed from file back of the enthalpy controller and mounted remotely. 1. Use a 4-conductor, 18 or 20 AWG cable to connect the enthalpy control to the PremierLink controller and power transformeg Wiring -- Carrier recommends the use of 18 to 22 AWG twisted pair or shielded cable for all wiring. All connections must be made with l/4-in, female spade connectol.s. The PremierLink TM board provides 24 vac to power the enthalpy switch/receivel: Connect the GND and 24 VAC terminals on the enthalpy switch/receiver to the termimfls on the transformer On some applications, the power from the economizer harness can be used to power the enthalpy switch/ receivel: To power the enthalpy switch/receiver from the economizer harness, connect power of the enthalpy switch/receiver to the red and brown wires (1 and 4) on the economizer hmness. 2. Connect the LOW Enthalpy terminal on the enthalpy switch/receiver to J4 -- pin 2 of the PremierLink control on the HVAC unit. The switch can be powered through the PremierLink control bo_ud if desired. Wire the 24 VAC terminal on the enthalpy switch/receiver to J4 -- pin 1 on the PremierLink control. Wire file GND terminal on the enthalpy switch/ receiver to Jl -- pin 2 on the PremierLink control. The HI Enthalpy terminal is not used. See Fig. 27. Connect the following 4 wires from the wire harness located in rooftop unit to the enthtdpy controller: a. Connect the BRN wire to the 24 vac terminal (TRI) on enthalpy control and to pin 1 on 12-pin harness. b. Connect the RED wire to the 24 vac GND terminal (TR) on enthalpy sensor and to pin 4 on 12-pin harness. c. Connect the GRAY/ORN wire to J4-2 on PremierLink controller and to terminal (3) on enthalpy sensoE d. Connect the GRAY/RED wire to J4-1 on PremierLink controller and to terminal (2) on enthtdpy sensol: NOTE: Use the two gray wires provided from the control section to the economizer to connect PmmierLink controller to terminals 2 and 3 on enthalpy sensol: Return Air Enthalpy Sensor -- Mount the return-air enthalpy sensor (HH57AC078) in file return-air duct. The return air sensor is wired to the enflialpy controller (HH57AC077). The outdoor enthalpy changeover set point is set at the controllel: Connect the 4-20 mA IN terminal on the enthalpy switch/ receiver to the 4-20 mA OUT terminal on the return air enthalpy sensol: Connect the 24-36 VDC OUT terminal on the enthalpy switch/receiver to the 24-36 VDC IN terminal on the return air enthalpy sensor See Fig. 27. To wire the return air enthalpy ing (see Fig. 28): Enthalpy Switch/Receiver Jumper Settings -- There me two jumpers. One jumper determines the mode of the enthalpy switch/receivel: The other jumper is not used. To access the jumpers, remove the 4 screws holding the cover on the enthalpy switch/receiver and then lemove the covel: The factory settings for the jumpers are M 1 and OFF. The mode jumper should be set to M2 for differentkfl enthalpy control. The factory test jumper should remain on OFF or the enthtflpy switch/receiver will not calculate enthalpy. sensor, perform the follow- 1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controllel: Enthalpy Sensor Jumper Settings -- There me two jumpers. One jumper determines the mode of the enthalpy sensor. The other jumper is not used. To access the jumpers, remove the 2O 2. At the enthalpy control remove the resistor fi_m the (SR) and (+) terminals. factory-installed 3. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (SR+) terminal on the enthalpy controllel: Connect the BLK wire to (S) spade connector on the mtum air enthalpy sensor and the (SR) terminal on the enthalpy controller. 120 VAC LINE VOLTAGE k._,.J_Aj-- 24 VAC OUTPUT FROM N/C CONTACT WHEN THE ORN OUTDOOR ENTHALPY IS LESS THAN THE " INDOOR ENTHALPY F / 24 VAC OUTPUT FROM N/O CONTACT WHEN THE INDOOR ENTHALPY IS GREATER THAN THE OUTDOOR ENTHALPY HI LOW GND 24 ENTHALPY VAC "_, 33CSENTHSW 4-20 24-36 rnA VDC IN OUT 24-36 4-20 VDC rnA IN OUT / _, 33CSENTSEN / J JUMPER SE_INGS FOR 33CSENTHSW JUMPER SETTINGS FOR 33CSENTSEN O ol [ °1[a°°°l [ioOO I [ioO oO oO 1 O010 LEGEND N/C -N/O -- _ OOO Normally Closed Normally Open Fig. 27 -- Differential Enthalpy Control Wiring HH57AC077 ENTHALPY CONTROLAND OUTDOOR AIR ENTHALPY SENSOR ENTHALPYCONTROLLER TRI-_ITR1 i'-LI,_IL_I BRN RED A(_Csorh+E3-SR¢-I+[]- --1 + ENTHALPY (OUTDOORAIR I SENSOR) BLK _S RED I [] [] S (RETURN AIR I + ENTHALPY SENSOR GRAY/ORN LWIRE LED GRAY/RED JlN HARNESS HH57AC078 ENTHALPY SENSOR (USED WITH ENTHALPY CONTROL FOR DIFFERENTIAL ENTHALPY OPERATION) UNIT NOTES: 1. Remove factory-installed jumper across SR and + before connecting wires from return air sensor. 2, Switches shown in high outdoor air enthalpy state. Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy. 3. Remove sensor mounted on back of control and locate in outside airstream. Fig. 28 -- Outdoor and Return Air Sensor Wiring Connections for Differential Enthalpy Control ÷ MOUNTING PLATE 4! Fig. 29Differential Enthalpy Control, Sensor and Mounting Plate (33AMKITENT006) 21 OPTIONAL ECONOMISERIV AND ECONOMISER2 -See Fig. 30 and 31 for EconoMiSerIV component locations. See Fig. 32 for EconoMi$er2 component locations. FRAME TOP NOTE: These instructions are for installing the optiomd EconoMiSerIV and EconoMiSer2 only. Refer to the accessory EconoMiSerIV or EconoMiSer2 installation instructions when field installing an EconoMi$erIV or EconoMiSer2 accessory. ECONOMI$ER2 SCREWS SCREWS To complete installation of the optional EconoMiSerIV. perform the following procedure. 1. Remove the EconoMiSerlV hood. Refer to Step 8 -Install Outdoor-Air Hood on page 13 for information on removing and inst_flling the outdoor-air hood. 2. Relocate position Fig. 30. Fig. 32 -- EconoMi$er2 outdoor air temperature sensor from shipping to operation position on EconoMiSerIV. See Table 7 -- Outdoor Component Air Damper DAMPER I IMPORTANT: Failure to relocate the sensor will result in the EconoMiSerIV not operating properly. 3. Re-install economizer 4. Install all EconoMiSerIV accessories. wiring is shown in Fig. 33. EconoMiSer2 in Fig. 34. I I LEAKAGE 4500 0,040 /\ / SCREWS \ (INSTALLED SENSOR OPERATION POSiT,ON) 0.6 0.8 1.0 1.2 35 53 65 75 90 102 LOW TEMPERATURE COMPRESSOR Locations SUPPLY AIR TEMPERATURE LOCATION SENSOR TEMPERATURE -58 -40 -22 -4 14 32 50 68 77 86 104 122 140 158 176 185 194 212 230 246 257 266 284 302 FLANGE (HIDDEN) Locations 6000 0,070 7200 0,090 7500 0.100 9000 0,110 10,000 0,120 11,250 0,140 with end" Low Temperature Compressor Lockout Switch -The EconomiSerIV is equipped with an ambient temperature lockout switch located in the outdoor alLstream which is used to lockout the compressoLs below a 42 F ambient temperature. See Fig. 30. Table 9 -- Supply Air Sensor Temperature/ Resistance Values -- ECONOMI$ERIV Fig. 31 -- EconoMiSerlV Component Side View 5400 0,060 The temperature sensor looks like an eyelet terminal wires running to it. The sensor is located in the "crimp and is settled from moisture. LOCKOUT SWITCH EconoMi$erlV Component End View 5000 0.050 Supply Air Temperature (SAT) Sensor -- The supply air temperature sensor is a 3 K thermistor located at the inlet of the indoor fan. See Fig. 31. This sensor is factory installed. The operating range of temperature measmement is 0 ° to 158 IF. See Table 9 for sensor temperature/resistance v_dues. ,/ Fig. 30- (in. wg) 0.4 ECONOMI$ERIV STANDARD SENSORS Outdoor Air Temperature (OAT) Sensor -- The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA device used to measure the outdoor-air temperature. The outdoor-air temperature is used to determine when the EconoMiSerIV can be used for free cooling. The sensor must be field-lelocated. See Fig. 30. The operating range of temperature measurement is 40 to 100E AIR TEMPERATURE FRAME STATIC PRESSURE 0.2 CFM EconoMiSerIV wiring is shown OUTDOOR ECONOMI$ERIV Leakage Table 8 -- Return Air Pressure Drop (in. wg) hood. Outdoor air leakage is shown in Table 7. Return air pressure drop is shown in Table 8. SCREWS (cfm) Locations -- 22 (F) RESISTANCE (ohms) 200,250 100,680 53,010 29,091 16,590 9,795 5,970 3,747 3,000 2,416 1,597 1,080 746 525 376 321 274 203 153 116 102 89 70 55 YEL PNK -BLU RED --ORN {FIELD ACCESSORY) REI4OTEWIN POSITION _NI _ 4, ROT _ ,__, BLK _V EXHsEI ]OV ECONOMISER BOARD SENSOR (3k Ohm) B_.X--I-RE PO_ D- P_ ,AOSE._O L_k_ PLI*R (NOT USED) MAIN LP L_ OAT TEWP/ P(LI_8 TO Ii ) L- E_INALPY_LH_ _S+OSE_SOR I AO _4,.n_ _ _ _ ,0v 0 ,[ RCV _DCV ,[ 2V_ovSET Pckt - 5 CONTROL BOX PLI "9 I I DLU I I P"--_ ) FIELD PL1 SPLICE LALS =I L ( ( PR1 =R PLI _ID (ROT DRN FIE'LLD SPLICE RED ) USED) EDONOMI LEGEND DCV -- Demand Controlled Ventilation IAQ -- Indoor Air Quality LALS-Low Temperature Compressor Lockout Switch OAT -- Outdoor-Air Temperature POT -- Potentiometer Potentiometer Default Settings: Power Exhaust Middle Minimum Pos. Fully Closed DCV Max. Middle DCV Set Middle Enthalpy C Setting ZER NOTOR NOTES: 1, 620 ohm, 1 watt 5% resistor should be removed only when using differential enthalpy or dry bulb, 2, If a separate field-supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded. 3, For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set control minimum position POT to the minimum position, Fig. 33 -- EconoMi$erlV Wiring 4 3 7 RED 2 500 OHM 8 R ESISTO R---"L_ PINK 6 NOTE 1 BLUE RUN 5 OAT BLACK NOTE2 1 / 10 50HJ540573 ACTUATOR ASSEMBLY 11 9 WHITE DIRECT DRIVE ACTUATOR 12 ECONOMI$ER2 LEGEND OAT -- Outdoor Air Temperature Sensor NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor. Fig. 34 -- EconoMi$er2 Wiring 23 PLUG ECONOMISERIV CONTROL MODES Differential DLy Bulb Control -- For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory return air sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig. 37. IMPORTANT: The optional EconoMiSer2 does not include a controllel: The EconoMiSer2 is operated by a 4 to 20 mA signal from an existing field-supplied controller (such as PremierLink TM control). See Fig. 34 for wiring information. In this mode of operation, the outdoor-tfir temperature is compared to the return-air temperature and the lower temperature airstream is used for cooling. When using this mode of changeover control, turn the free cooling/enthalpy setpoint potentiometer fully clockwise to the D setting. See Fig. 35. Determine the EconoMiSerIV control mode before set up of the control. Some modes of operation may lequile diffelent sensors. Refer to Table 10. The EconoMiSerlV is supplied from the factory with a supply air temperature sensor, a low temperature compressor lockout switch, and an outdoor air temperature sensol: This _fllows for operation of the EconoMiSerlV with outdoor air &y bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMiSerlV and unit. Table 10 -- EconoMi$erlV APPLICATION Sensor Usage ECONOMI$ER IV WITH OUTDOOR DRY BULB SENSOR Accessories Outdoor Air Dry Bulb Differential Dry Bulb Single 002 for DCV Control using a Wall-Mounted CO2 Sensor CO2 for DCV Control using a Duct-Mounted CO2 Sensor AIR Required None. The outdoor air dry bulb sensor is factory installed. FAN SET POINT CRTEMPSN002A00* WHEN EXHAUST CONTACT tS MADE HH57AC078 Enthalpy Differential Enthalpy Outdoor Enthalpy Changeover -- For enthalpy control, accessory enthalpy sensor (p_ut number HH57AC078) is required. Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. See Fig. 30. When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the outdoorair damper moves to its minimum position. The outdoor enthalpy changeover set point is set with the outdoor enth_dpy set point potentiometer on the EconoMiSerIV controllel: The set points are A, B, C, and D. See Fig. 38. The factory-installed 620-ohln jumper must be in place across terminals SR and SR+ on the EconoMiSerIV controllel: See Fig. 33 and 39. HH57AC078 and CRENTDIF004A00* MINIMUM POSITION SETTING MAXIMUM DEMAND CONTROL VENTILATION SET POINT 33ZCSENCO2 and 33ZCASPCO2** 33ZCSENCO2t LED LIGHTS DEMAND CONTROL VENTILATION INPUT IS ABOVE SET POINT CRCBDIOX005A00tt VENTILATION *CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation. 1-33ZCSENCO2 is an accessory CO2 sensor. **33ZCASPCO2 is an accessory aspirator box required for ductmounted applications. 1-]-CRCBDiOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories. SET POINT LED LIGHTS WHEN OUTDOOR AiR iS SUITABLE FOR FREE COOLING FREE COOLING/ENTHALPY CHANGEOVER SET POINT Fig. 35 -- Outdoor Dry Bulb Changeover -- The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensol_ are included as stan&trd. For this control mode, the outdoor temperature is compmed to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMiSerIV will adjust the outside air dampers to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potentiometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. See Fig. 35. The sc_de on the potentiometer is A, B, C, and D. See Fig. 36 for the conesponding temperature changeover v_dues. EconoMi$erlV Controller and LED Locations [ 18-!_ Potentiometer L 17-i 16_ -- LED ON - LED OFF <15" I E14- ! LED OFF LED O; 13" _'-_L_ 12- 4O 45 50 55 60 65 70 75 LED ON- -- 80 85 90 DEGREES FAHRENHEIT Fig. 36 -- Outside Air Temperature Changeover Set Points 24 95 100 Differential Enthalpy Control -- For differential enthalpy control, the EconoMiSerIV controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return airstream on the EconoMiSer[V frame. Tile EconoMiSerIV controller compares the outdoor air enthalpy to file return air enthalpy to determine EconoMiSer[V use. Tile controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when file outdoor air has a lower enthalpy than the return air and is below the set point, the EconoMiSerIV opens to bring in outdoor _firfor fiee cooling. Replace the standard outside air d U bulb temperature sensor with the accessory enthalpy sensor in the stone mounting location. See Fig. 30. Mount the return air enth_dpy sensor in the return airstremn. See Fig. 37. Tile outdoor enth_dpy changeover set point is set with the outdoor enthalpy set point potentiometer on the EconoMiSerIV controller. When using this mode of changeover control, turn the enthalpy set point potentiometer fully clockwise to the D setting. NOTE: Remove 620-ohm resistor if differentkd enthalpy sensor is installed, Indoor Air Ouality (IAO) Sensor Input -- Tile IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct. RETURN AIR TEMPERATURE AND ENTHALPY SENSOR IAQ SENSOR Mount the accessory IAQ sensor according to manufacturer specifications. The IAQ sensor should be wired to the AQ and AQI terminals of the controllel: Adjust the DCV potentiometers to conespond to the DCV voltage output of the indoor air quality sensor at the use>determined set point. See Fig. 40. Fig. 37 -- Return Sensor Air Temperature or Enthalpy Mounting Location If a separate field-supplied transformer is used to power the IAQ sensol: the sensor must not be grounded or the EconoMiSer[V control board will be &imaged. CONTROL 85 90 95 100 105 110 (29) (32) (35) (38) (41) (43) CONTROLPOINT CURVE APPROXI°F (°C) AT 50% RH A 73(23) B 70(21) C D 67119 ) 63(17) i i i i i i i i i i i i i i i i i _ HIGH i 35 40 45 50 55 60 65 70 75 80 85 90 95 100 \ 105 (2) (4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) APPROXIMATE DRY BULB TEMPERATURE-- Fig. 38 -- Enthalpy °F (°C) Changeover 25 Set Points CURVE 110 (43) LIMIT at least 10 F temperature difference between the outdoor and return-air temperatures. To determine the minimum position setting, perform the following procedure: T ....... 1. Calculate the appropriate mixed air temperature following formula: OA RA (To x I---_T ) + (TR x _ ) = TM @ To = Outdoor-Air Temperature OA = Percent of Outdoor Air 2 TR = Return-Air Temperature RA = Percent of Return Air 5 ..... _ FFr_I using the 4 TM = Mixed-Air Temperature As an example, if local codes require 10% outdoor during occupied conditions, outdoor-air temperature 60 IF.and return-air temperature is 75 E EF1 air is (60 x. 10) + (75 x .90) = 73.5 F Fig. 39- EconoMi$erlV Controller 2. Disconnect TI. the supply-air 3. Ensure that terminals P used, make Fig. 33 and turned fully Connect 24 the factory-installed jumper is in place across and PI. If remote &tmper positioning is being sure that the termimds are wired according to that the minimum position potentiometer is clockwise. vac across termimds TR and TRI. CO 2 SENSOR MAX RANGE SETTING 6000 5000 4. z Q 4000 + 3000 2000 < __ + 1100 ppm _ 9o0 ppm Cmefully adjust the minimum position potentiometer until the measured mixed-air temperature matches the calculated v_due. 6. Reconnect 2 3 4 5 6 7 8 RATE sensor to terminals T and TI. To control the minimum dalnper position remotely, remove the factory-installed jumper on the P and PI terminals on the EconoMiSerIV controllel: Wire the field-supplied potentiometer to the P and PI terminals on the EconoMiSerIV controllel: See Fig. 39. Fig. 40 -- 002 Sensor Maximum Range Setting Exhaust Set Point Adjustment -- The exhaust set point will determine when the exhaust fan runs based on dmnper position (if accessol 7 power exhaust is installed). The set point is modified with the Exhaust Fan Set Point (EXH SET) potentiometel: See Fig. 35. The set point replesents file &tmper position above which the exhaust fan will be turned on. When there is a c_dl for exhaust, the EconoMi$erlV controller provides a 45 _+15 second delay before exhaust fan activation to allow the dampers to open. This delay _dlows the damper to reach the appropriate position to avoid unnecessary fan overload. Damper Movement -- Damper movement from full open to full closed (or vice versa) takes 21/2 minutes. Thermostats -- The EconoMi$erIV control works with conventional thermostats that have a YI (cool stage 1), Y2 (cool stage 2), WI (heat stage 1), W2 (heat stage 2), and G (fan). The EconoMi$erIV control does not support space temperature sensors. Connections are made at the thermostat terminal connection board located in the main control box. Minimum Position Control -- There is a minimum damper position potentiometer on the EconoMi$erlV controllel: See Fig. 35. The minimum &tmper position maintains the minimum airflow into the building during the occupied period. Occupancy Control -- The factory default configuration for the EconoMi$erIV control is occupied mode. This is implemented by the RED jumper at TB2-9 to TB2-10. When unoccupied mode is desired, remove the RED jumper and install a field-supplied timeclock function between TB2-9 and TB2-10. When the timeclock contacts are open, the unit control will be in unoccupied mode; when contacts are closed, file unit control will be in occupied mode. Demand Controlled Ventilation (DCV) -- When using the EconoMi$erIV for demand controlled ventilation, there are some equipment selection criteria which should be considered. When selecting the heat capacity and cool capacity of the equipment, the maximum ventilation rote must be evaluated for design conditions. The maximum damper position must be calculated to provide the desired fresh all: When using demand ventilation, the minimum dmnper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requilements. The maximum demand ventilation position is used for fully occupied ventilation. When demand minimum position cupied ventilation position should be the supply-air Remote control of the EconoMi$erIV dmnper is desirable when requiring additional temporm 7 ventilation. If a field-supplied remote potentiometer (Honeywell part number $963B1128) is wired to the EconoMiSerIV controller, the minimum position of the &tmper can be controlled from a remote location. 1000 DAMPER VOLTAGE FOR MAX VENTILATION T and 5. 1000 ppm Z z 800 ppm sensor from terminals ventilation control is not being used, the potentiometer should be used to set the ocposition. The maximum demand ventilation turned fully clockwise. Adjust the minimum position potentiometer to allow the minimum mnount of outdoor air. as required by local codes, to enter the building. Make minimum position adjustments with 26 Typically the maximum ventilation rate will be about 5 to 10% more than the typical cfm required per person, using nonnal outside air design criteria. since the CO2 sensor voltage will be ignored by the EconoMi$erIV controller until it rises above the 3.6 volt setting of the minimum position potentiometer. A proportional anticipato U strategy should be token with the following conditions: a zone with a large area, varied occupancy, and equipment that cannot exceed the requited ventilation rate at design conditions. Exceeding the required ventilation rate means the equipment can condition tfir at a maximum ventilation rate that is greater than the requited ventilation rate for maximum occupancy. A propot_tional-anticipatou strategy will cause the fresh air supplied to increase as the room CO2 level increases even though the CO2 set point has not been reached. By the time the CO: level teaches the set point, the damper will be at maximum ventilation and should maintain the set point. In order to have the COo_ sensor control the economizer damper in this manner, first determine the &mper voltage output for minimum or base ventilation. Base ventilation is the ventilation required to remove contmninants during unoccupied periods. The following equation may be used to determine the percent of outside-air entering the building for a given damper position. For best results there should be at least a 10 degree difference in outside and return-air temperatures. Once the fully occupied damper position has been determined, set the maximum damper demand control ventilation potentiometer to this position. Do not set to the maximum position as this can result in over-ventilation to the space and potential high-humidity levels. CO.2 Sensor Configuration -- The CO2 sensor has preset stan&trd voltage settings that can be selected anytime after the sensor is powered up. See Table 11. Use setting 1 or 2 for Carrier equipment. See Table 11. 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. To = Outdoor-Air Temperature OA = Percent of Outdoor Air TR = Return-Air Temperature RA = Percent of Return Air TM = Mixed-Air Temperature Once base ventilation has been determined, set the minimum damper position potentiometer to the correct position. The same equation can be used to determine the occupied or maximum ventilation rate to the building. For example, an output of 3.6 volts to the actuator provides a base ventilation rate of 5% and an output of 6.7 volts provides the maximum ventilation rate of 20% (or base plus 15 cfm pet person). Use Fig. 40 to determine the maximum setting of the CO: sensot: For example, a 1100 ppm set point relates to a 15 cftn per person design. Use the 1100 ppm curve on Fig. 40 to find the point when the CO2 sensor output will be 6.7 volts. Line up the point on the graph with the left side of the chart to determine that the range configuration for the CO2 sensor should be 1800 ppm. The EconoMiSerIV controller will output the 6.7 volts from the CO2 sensor to the actuator when the CO2 concentration in the space is at 1100 ppm. The DCV set point may be left at 2 volts SETTING EQUIPMENT 1 2 OUTPUT Proportional Interface w/Standard Building Control System Proportional -- 002 Press Mode twice. The STDSET Menu will appear. 3. Use the Up/Down Table 11. 4. Press Enter to lock in the selection. 5. Press Mode to exit and resume normal operation. button to select the preset number. See The custom settings of the CO2 sensor can be changed anytime after the sensor is energized. Follow the steps below to change the non-standard settings: 1. Press Clear and Mode buttons. Hold at least 5 seconds until the sensor enters the Edit mode. OA RA (To x l---ff_-) + (TR x _ ) = TM Table 11 2. 2. Press Mode twice. The STDSET 3. Use the Up/Down and press Enter 4. Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached. 5. Press Mode to move through the variables. 6. Press Enter to lock in the selection, continue to the next variable. Dehumidification mation fiom on any zone Menu will appeat: button to toggle to the NONSTD of Fresh Air with then press Mode to DCV Control -- Infor- ASHRAE indicates that the lmgest humidity load is the fresh air introduced. For some applications, a field-supplied energy recovery unit can be added to reduce file moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes am morn than adequate to remove file humidity loads for most commemi_fl applications. If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered. Sensor Standard Settings VENTILATION RATE (cfm/Pereon) ANALOG OUTPUT CO2 CONTROLRANGE (ppm) OPTIONAL RELAY SETPOINT (ppm) RELAY HYSTERESIS (pprn) Any 0-10V 4-20 mA 0-2000 1000 5O Any 2-10V 7-20 mA 0-2000 1000 5O 0-2000 1100 5O 3 Exponential Any 0-10V 4-20 mA 4 Proportional 15 0-10V 4-20 mA 0-1100 1100 5O Proportional 20 0-10V 4-20 mA 0- 900 900 5O 15 0-10V 4-20 mA 0-1100 1100 5O 20 0-10V 4-20 mA 0- 900 900 5O 5000 5OO 5 Economizer 6 Exponential 7 Exponential 8 Health & Safety Proportional 0-10V 4-20 mA 0-9999 9 Parking/Air Intakes/ Loading Docks Proportional 0-10V 4-20 mA 0-2000 LEGEND ppm -- menu Parts Per Million 27 7OO 5O Step 11 -- Install Humidistat for Optional MoistureMi$er TM Package-MoistureMiSer dehumidification package operation can be controlled by field inst;dlation ofa Canier-approved humidistat, To install the humidistat perform the following procedure: 1, Locate humidistat on a solid interior wall in the conditioned space. Location should be a well ventilated area to sense average humidity. 2, Route thermostat cable or equivalent single leads of cololed wire from Humidistat termimds through conduit in unit to the low voltage connection on the 2-pole terminal strip (TB3) as shown in Fig, 41 and 42, Remove the jumper from TB3, See Fig. 43 for operational diagram. Fig. 42 -- Typical MoistureMi$er Dehumidifcation Package Control Box MOISTUREMI$ER _'_YEL- YEL. / BLK i TO CRANKCASE / HEATER CIRCUITS BLK_ TRAN 24V BLK TRAN_ GRN YEL GRN YEL J CB LLSV LPS TB TRAN ------ LEGEND Circuit Breaker Liquid Line Solenoid Valve LowPressure Switch Terminal Block Transformer BLK BLK-- 3 2AMPS _ L S LPS1 8 LLSVLsw2 _ S_SLPS2 • L FACTORY INSTALLED JUMPER (OR HUMIDISTAT IF USED) Fig. 41 -- Typical MoistureMi$er Dehumidification Package Humidistat Wiring Schematic (460 V Unit Shown) 28 CONDENSER l COIL , DISCHARGE OUTDOORAIR COIL EQUALIZER LINE SUCTION J p-CCH CRANKCASE HEATER LIQUID EVAPORATOR COIL 3-WAY VALVE \°COMPRESSOR S-LPS _ SUB COOLER CONTROL LOW PRESSURE SWITCH TXV INDOOR AIR EQL TXV -- Thermostatic Expansion Valve Fig. 43 -- MoistureMi$er 29 TM Operation Diagram START-UP Use the following information and St_ut-Up Checklist page CL-I to check out unit PRIOR to start-up. on -- Check that unit has been installed in with these installation instructions and all applica- INTERNAL WIRING -- Check all electric;d unit control boxes; tighten as required. CRANKCASE HEATER--Heater there is power to unit and compressor connections in EVAPORATOR FANFan belt and variable pulleys are factory installed. Remove tape from the fan pulley. See Table 12 for air quantity limits. See Tables 13-16 for fan performance data. Be sure that rims rotate in the proper direction. See Table 17 for static pressure information for accessories and options. See Table 18 for fan rpm at various fan motor pulley settings. See Tables 19 and 20 for evaporator fan motor data. To alter fan performance, see Evaporator-Fan Performance Adjustment section, page 37. I COMPRESSOR MOUNTING -- Compressors are intern_dly spring mounted. Do not loosen or remove compressor holddown bolts. REFRIGERANT SERVICE PORTS -- Each refrigerant system has a total of 3 Schrader-type service gage ports. One port is located on the suction line, one on the complessor discharge line, and one on the liquid line. In addition Schmder-type v_dves are located underneath the low-plessure switches. Be sure that caps on the ports are tight. Table COMPRESSOR ROTATION -- It is important to be certain the compressors are rotating in the proper direction. To determine whether or not compressors tue rotating in the proper direction: pressure 2. Energize the compressol: 3. The suction pressure should drop and the discharge sure should rise, as is normal on any start-up. pres- If the suction pressme does not drop and the discharge sure does not rise to normal levels: pres- 1. Note that the evaporator the wrong direction. 2. fan is probably power leads. After a few minutes of reverse operation, the scroll compressor internal overload protection will open, which will activate the unit's lockout and requires a manual reset. Reset is accomplished by turning the thermostat on and off. is energized as long as is not operating. service gages to suction and discharge Turn on power to the compmssoc NOTE: When compressors are rotating in the wrong direction, the unit will have increased noise levels and will not provide heating and cooling. IMPORTANT: Unit power must be on for 24 hom_ prior to ] start-up. Otherwise, dmnage to compressor may result. 1. Connect fittings. Reverse any two of the incoming 4. The suction and discharge pressure levels should now move to their normal start-up levels. Unit Preparation accordance ble codes. 3. 12 -- Air Quantity UNIT 50TM MINIMUM CFM 016 020 025 028 4500 5400 6000 7000 Limits MAXIMUM CFM 7,500 9,000 10,000 11,250 CONDENSER FANS AND MOTORS -- Fans and motors are factory set. Refer to Condenser-Fan Adjustment section (page 38) as required. RETURN-AIR FILTERS -- Check that correct filtel_ are installed in filter tracks. See Table 1. Do not operate unit without return-air filters. OUTDOOR-AIR INLET SCREENS -- Outdoor-air screens must be in place before operating unit. _dso rotating in Turn off power to the unit. 3O inlet Table 13 -- Fan Performance -- 50TM016* AVAILABLE AIRFLOW (Cfm) 0.2 Rpm 753 747 741 735 759 790 821 852 883 914 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 EXTERNAL Watts 1307 1384 1465 1659 1854 2088 2340 2611 2903 3215 Bhp 1,53 1,62 1,72 1,95 2,18 2.45 2.74 3.06 3,40 3,77 Rpm 753 747 752 805 832 860 888 917 946 975 Watts 1307 1384 1500 1895 2118 2360 2621 2900 3200 3521 Bhp 1.53 1.62 1.76 2.22 2.48 2.77 3.07 3.40 3.75 4.13 Rpm 784 806 828 876 901 926 952 979 1006 1033 AVAILABLE AIRFLOW (Cfm) 1.2 Rpm 993 1009 1026 1064 1083 1104 1125 1147 1170 1193 4599 4809 5100 5700 6000 6300 6600 6900 7200 7500 Watts 2133 2319 2521 2975 3228 3501 3791 4101 4431 4781 Bhp 2.50 2.72 2.96 3,49 3,79 4,11 4,45 4,81 5,20 5,61 Rpm 1055 1070 1086 1120 1139 1158 1178 1199 1221 1243 Watts 2394 2585 2794 3260 3520 3799 4095 4412 4749 5107 Rpm 1114 1127 1142 1174 1192 1210 1229 1249 1270 -- 2,2 Rpm Watts 1276 3509 1287 3721 1299 3949 1325 4458 1340 4741 1356 5043 .................. .................. .................. .................. 4500 4800 5100 6700 6000 6300 6600 6900 7200 7500 Rpm 1397 1563 1745 2156 2388 2638 2906 3194 3501 3830 1,64 1,83 2,05 2,53 2,80 3.09 3,41 3,75 4,11 4,49 859 878 898 942 965 988 1013 1038 1063 1089 STATIC PRESSURE 1.6 Bhp 4,12 4,36 4.63 5.23 5.56 5.91 Rpm Watts 1326 3805 1336 4020 1347 4253 1373 4772 1387 5060 ............... Bhp 4,46 4,72 4.99 5.60 5.93 Rpm Watts 1375 4107 1384 4326 1395 4563 1418 5091 ............ Bhp 1.92 2.12 2.34 2.84 3.12 3.43 3.75 4.10 4.47 4.86 Rpm 928 946 964 1004 1026 1048 1070 1094 1118 1142 Watts 1880 2060 2255 2696 2943 3208 3491 3794 4117 4461 Bhp 2.20 2.42 2.65 3.16 3.45 3.76 4.10 4.45 4.83 5.23 (in. wg) 1.8 2,0 Bhp Rpm Watts Bhp Rpm Watts Bhp 2662 2859 3073 3551 3817 4102 4405 4728 5072 3,12 3,35 3,60 4,17 4,48 4,81 5,17 5.55 5.95 1170 1183 1196 1226 1243 1260 1278 1297 ...... 2938 3139 3359 3848 4119 4410 4720 5050 3.45 3.68 3.94 4.51 4.83 5.17 5.54 5.92 1224 1236 1248 1277 1292 1309 1326 -- 3220 3427 3650 4151 4427 4724 5039 -- 3.78 4.02 4.28 4.87 5.19 5.54 5.91 -- STATIC PRESSURE 2.8 Bhp 4,82 5,07 5.35 5.97 LEGEND Bhp -Watts-- 1.0 Watts 1635 1808 1996 2423 2663 2920 3196 3492 3807 4143 Watts EXTERNAL 2,6 2,4 0,8 Bhp EXTERNAL Bhp 2.81 3.03 3.28 3.82 4.13 4.46 4.80 5.18 5.57 5,99 (in, wg) Watts 1.4 AVAILABLE AIRFLOW (Cfm) STATIC PRESSURE 0.6 0.4 Rpm Watts 1421 4414 1430 4638 1440 4879 ......... (in. wg) 3,0 Bhp 5.18 5.44 5.72 Rpm 1467 1475 ...... Watts 4728 4955 3,2 Bhp 5.55 5,81 Rpm 1511 -- Watts 5047 -- Bhp 5.92 -- NOTES: Brake Horsepower Input Watts to Motor 1. *Standard low-medium static drive range is 873 to 1021 rpm. Alternate highstatic drive range is 1025 to 1200. Other rpms require a field-supplied drive. 2. Maximum continuous imum bhp See page continuous bhp for the standard motor is 6.13. The maximum watts is 5180. Do not adjust motor rpm such that motor maxand/or watts is exceeded at the maximum operating cfm. 33 for general fan performance notes. Table 14 -- Fan Performance -- 50TM020* AVAILABLE AIRFLOW (Cfm) 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 0.2 Rpm 682 730 778 828 878 928 979 1030 1082 1134 Bhp 1,99 2,38 2,82 3,31 3,84 4,42 5,05 5.73 6.46 7.25 Rpm 1.4 Bhp Watts 1675 2005 2373 2780 3227 3715 4245 4817 5433 6093 Watts 1086 1112 1142 1173 1207 1242 1279 1317 1356 1397 3,89 4.31 4.77 5.28 5.83 6.44 7.10 7.80 8,56 9.37 3275 3623 4010 4438 4906 5415 5966 6561 7198 7881 Rpm 760 802 846 892 938 985 1033 1082 1131 1180 Bhp 2.29 2.68 3.13 3.62 4.15 4.74 5.38 6.06 6.80 7.59 Watts 1922 2257 2630 3042 3494 3986 4521 5098 5718 6382 AVAILABLE AIRFLOW (Cfm) 5,500 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 0,4 Rpm 1.6 Bhp Watts 1142 1167 1194 1224 1255 1289 1324 1360 1398 1438 4,24 4.66 5.12 5,63 6,19 6.80 7.45 8.16 8,93 9.74 3567 3915 4304 4733 5203 5714 6268 6865 7505 8190 Rpm 832 871 911 953 996 1040 1085 1131 1178 1226 EXTERNAL EXTERNAL 0,6 Bhp 2.59 2.99 3.44 3.94 4.48 5.07 5.71 6.40 7.14 7.94 Watts 2177 2516 2893 3310 3766 4263 4801 5382 6007 6675 Rpm 901 935 972 1011 1051 1093 1136 1180 1225 1270 STATIC PRESSURE Rpm 1.8 Bhp Watts Rpm 1197 1219 1245 1273 1302 1334 1368 1403 1440 1477 4,59 5.01 5.47 5.98 6,55 7.16 7.82 8.53 9,29 10.11 3864 4213 4602 5033 5504 6018 6573 7173 7815 8503 1223 1245 1270 1296 1326 1357 1389 1424 1460 ...... LEGEND Bhp -Watts-- STATIC PRESSURE 0.8 Bhp 2,90 3,31 3,76 4,26 4,81 5,40 6,05 6.74 7.49 8.29 (in. wg) 1,0 Bhp 3.22 3.63 4.09 4.59 5.14 5.74 6.39 7.09 7.84 8.65 1.2 Watts 2441 2783 3164 3583 4043 4544 5086 5671 6299 6971 Rpm 965 997 1031 1067 1105 1144 1185 1227 1270 1313 Watts 2712 3057 3440 3863 4326 4830 5375 5964 6595 7271 1.9 Bhp Watts Rpm 2.0 Bhp Watts 4,77 5.19 5.65 6,17 6,73 7.34 8.00 8.71 9,48 4015 4364 4754 5184 5657 6171 6728 7328 7972 1249 1270 1294 1320 1348 1379 1411 1445 1480 4,96 5.37 5.83 6,35 6,91 7.52 8.18 8.90 9,67 4167 4516 4906 5337 5810 6325 6883 7484 8129 Rpm 1027 1056 1087 1121 1156 1194 1232 1272 1313 1356 Bhp 3.56 3.97 4.43 4.93 5.49 6.09 6.74 7.44 8.20 9.01 Watts 2990 3337 3722 4148 4613 5120 5669 6260 6895 7574 (in. wg) NOTES: Brake Horsepower Input Watts to Motor 1. *Standard low-medium static drive range is 910 to 1095 rpm. Alternate highstatic drive range is 1069 to 1287 rpm. Other rpms require a field-supplied drive. 2. 3! Maximum continuous bhp is 5.90. The maximum continuous watts is 5180. Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See page 33 for general fan performance notes. Table 15- Fan Performance- AVAILABLE AIRFLOW (Cfm) 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 0.2 Rpm 753 793 844 895 947 999 1052 1105 1158 Rpm 816 861 908 955 1004 1053 1103 1153 1204 1.2 Rpm 1089 1102 1136 1173 1211 1251 1292 1335 1378 Watts 2579 2959 3372 3817 4294 4803 5345 5919 6526 Bhp 3.06 3.51 4.00 4.53 5.09 5.70 6.34 7.02 7.74 Watts 3517 3891 4299 4739 5212 5718 6257 6830 7434 Bhp 4.17 4.62 5.10 5.62 8.18 8.78 7.42 8.10 8.82 2.2 Rpm 1332 1356 1381 1409 1440 1471 1505 1540 Wa_s 4750 5122 5519 5951 6417 6916 7449 8016 Rpm 884 925 968 1013 1058 1105 1152 1200 1249 EXTERNAL 1.4 Rpm 1125 1156 1188 1223 1259 1297 1337 1377 1419 Watts 3761 4132 4538 4977 5449 5954 6492 7063 7667 Bhp 4.48 4.90 5.38 5.90 8.48 7.08 7.70 8.38 9.10 AVAILABLE AIRFLOW (Cfm) 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Bhp 2.83 3.25 3.74 4.27 4.83 5.44 6.08 6.76 7.48 AVAILABLE AIRFLOW (Cfm) 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Watts 2385 2738 3151 3596 4073 4583 5125 5699 6306 EXTERNAL 0.4 Rpm 1180 1208 1239 1272 1308 1342 1380 1419 1460 EXTERNAL 2,4 Bhp 5.85 8.08 6.55 7.06 7.61 8.20 8.84 9.51 Rpm Wa_s 1380 5015 1402 5375 1427 5770 1453 6199 1482 6663 1513 7161 1545 7693 ............ Bhp 5.95 6.38 6.84 7,35 7.90 8.49 9.13 Rpm 1427 1447 1471 1496 1523 ......... ......... --- STATIC PRESSURE 0.6 Watts 2807 3186 3598 4042 4518 5027 5569 6142 6750 Bhp 3.33 3.78 4.27 4.80 5.36 5.96 6.61 7.29 8.01 Bhp 4.75 5.19 5.87 8.19 8.75 7.35 7.98 8.86 9.37 Bhp 8.25 8.88 7.14 7.65 8.20 Wa_s 3040 3418 3828 4271 4747 5255 5796 6369 6975 1.0 Bhp 3.61 4.05 4.54 5.07 5.63 6,23 6.88 7.56 8.27 Rpm 1010 1045 1082 1121 1162 1204 1247 1291 1336 Wat_ 3277 3653 4062 4504 4978 5485 6025 6598 7203 Bhp 5.05 5.48 5.98 6.48 7.03 7.63 8.27 8.94 9.65 Rpm 1283 1308 1335 1365 1398 1429 1464 1501 1538 Watts 4506 4871 5271 5705 8172 8873 7207 7776 8377 Bhp 8.56 8.98 7.45 7.95 Rpm 1517 1535 --- Watts 5793 6144 --- Bhp 3.89 4.33 4.82 5.34 5.91 6.51 7.15 7.83 8.55 (in. wg) 1,8 Rpm 1232 1259 1288 1319 1352 1386 1423 1460 1499 STATIC PRESSURE 2.6 Watts 5272 5630 6022 6449 6911 0.8 Rpm 949 987 1026 1068 1111 1155 1200 1246 1293 STATIC PRESSURE 1.6 Watts 4008 4377 4780 5217 5888 6192 6729 7299 7902 (in. wg) Watts 4255 4623 5025 5460 5929 6431 6967 7536 8138 2.0 Bhp 5.35 5.78 6.25 6.77 7.32 7.92 8.55 9.22 9.94 (in. wg) Rpm 1472 1492 1514 1538 ...... 2,8 Watts 5531 5888 6276 6701 3.0 Bhp 6.87 7.29 --- NOTES: 1. Maximum continuous bhp for the standard motor is 8.7 (for 208/230 and 575-v units) and 9.5 (for 460-v units). The maximum continuous watts is 7915 (for 208/230 and 575-v units) and 8640 (for 230 and 460-v units). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. 2. See page 33 for general fan performance notes. LEGEND Bhp Watts 50TM025" Brake Horsepower Input Wattsto Motor *Standard low-medium static drive range is 1002 to 1151 rpm. Alternate highstatic drive range is 1193 to 1369. Other rpms require a field-supplied drive. 32 Table 16 -- Fan Performance -- 50TM028" AVAILABLE AIRFLOW (Cfm) 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 0.2 EXTERNAL 0,6 STATIC PRESSURE 0,8 (in. wg) 1.0 1.2 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 845 896 948 1001 1053 1106 1159 1213 1266 1293 3.26 3.82 4.43 5.11 5.85 6.65 7.52 8.45 9.45 9.97 2693 3156 3667 4226 4836 5498 6214 6984 7810 8245 909 956 1005 1054 1104 1155 1206 1257 1309 1334 3.60 4.17 4.80 5.49 6.23 7.04 7.92 8.86 9.87 10.40 2979 3450 3969 4537 5155 5824 6547 7325 8159 8597 969 1014 1060 1106 1154 1202 1251 1300 1350 1375 3.96 4.54 5.17 5.87 6.63 7.44 8.33 9.28 10.29 10.83 3272 3752 4278 4853 5478 6155 6886 7671 8511 8953 1028 1069 1112 1156 1202 1248 1295 1342 1391 1415 4.32 4.91 5.56 6.26 7.02 7.85 8.74 9.70 10.73 11,26 3574 4060 4593 5175 5808 6492 7229 8020 8868 9313 1083 1123 1163 1205 1248 1293 1338 1384 1431 1454 4.70 5.29 5.94 6.66 7.43 8.26 9.16 10.13 11.16 11.70 3883 4375 4915 5504 6142 6833 7577 8375 9229 9677 1137 1174 1213 1253 1294 1336 1380 1424 1470 1493 5.08 5.68 6.34 7.06 7.84 8.68 9.59 10.56 11.60 12.15 4,200 4,698 5,243 5,838 6,483 7,179 7,929 8,733 9,594 10,045 AVAILABLE 1.4 AIRFLOW (Cfm) 7,000 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 0,4 EXTERNAL STATIC PRESSURE 1.6 (in. wg) 1.8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1189 1224 1261 1299 1338 1379 1421 1464 1508 1530 5.47 6,08 6,75 7.47 8.26 9.11 10.02 11.00 12.05 12.60 4,524 5,026 5,577 6,177 6,828 7,530 8,286 9,096 9,963 10,417 1239 1272 1307 1344 1382 1421 1461 1503 1546 ...... 5.87 6.48 7.16 7.89 8.68 9.54 10,46 11,45 12.50 4,854 5,362 5,917 6,523 7,179 7,887 8,648 9,464 10,336 1288 1320 1353 1388 1424 1462 1501 1541 -- 4.91 5,56 6,26 7,02 7.85 8,74 9,70 10,73 -- 5191 5703 6263 6873 7534 8247 9014 9835 -- LEGEND Refer to this page for general Fan Performance Bhp -- Brake Horsepower Watts -- Input Watts to Motor *Standard low-medium static drive range is 1066 to 1283 rpm. Alternate highstatic drive range is 1332 to 1550. Other rpms require a field-supplied drive. GENERAL FAN PERFORMANCE NOTES: 1. Values include losses for filters, unit casing, and wet coils. See Table 17 for accessory/factory-installed option static pressure information. 2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using fan motors up to the wattage ratings shown will not result Table 17 -- Accessory/FlOP Data note& NOTE: Maximum continuous bhp is 10.20 (208/230, 575 v) or 11.80 (460 v) and the maximum continuous watts are 9510 (208/230, 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm. See Evaporator Fan Motor Data tables for more information. NOTES in nuisance tripping or premature motor failure. Unit warranty will not be affected. See Evaporator-Fan Motor Performance data in Table 19 on page 34 for additional information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details. 4. Interpolation is permissible. Do not extrapolate. Static Pressure (in. wg) -- 50TM016-028 CFM COMPONENT 5400 I 6000 7200 9000 10,000 11,250 Glycol Coil 0.06 0.30 J 0.07 0.35 0.09 0.44 0.11 0.58 0.12 0.66 0.14 0.77 Electric Heat (kW) 26/34 32 42/56 55 56/75 80 0.08 0.08 0.11 0.11 0.14 0.14 0.09 0.09 0.12 0.12 0.15 0.15 0.11 0.11 0.15 0.15 0.20 0.20 0.15 0.15 0.19 0.19 0.24 0.24 0.17 0.17 0.21 0.21 0.26 0.26 0.20 0.20 0.24 0.24 0.29 0.29 MoietureMi$er 0.06 0.07 0.10 0.16 0.20 0.25 Economizer TM Dehumidification LEGEND FlOP -- Factory-Installed NOTES: 1. The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts. 2. Heaters are rated at 240 v and 480 v. There are no 575-v heaters. Option 33 Table 18 -- Fan Rpm at Motor Pulley Settings* MOTOR PULLEY TURNS OPEN UNIT 50TM 0 16 1 116 tt tt 2 216 3 1021 1002 984 316 965 947 4 416 928 910 5 516 891 873 6 1025 016t tt tt 016"* tt tt tt tt 1200 1178 1156 1134 1112 1091 1069 1047 020t tt tt 1095 1077 1058 1040 1021 1002 984 965 947 928 910 020** tt tt 1287 1265 1243 1222 1200 1178 1156 1134 1112 1091 1069 025t 025** tt tt tt tt tt tt ?t tt 1151 1369 1132 1347 1114 1098 1077 1058 1040 1021 1002 1325 1303 1281 1259 1237 1218 1193 028t tt tt 1283 1269 1247 1225 1203 1182 1160 1138 1116 1098 1066 028** tt tt -- -- 1551 1524 1497 1470 1443 1418 1388 1361 1332 *Approximate _n rpm shown. tlndicates standard drive package. **Indicates alternate drive package. ttDue to belt and pulley size, pulley cannot be set to this number of turns open. Table 19UNIT 50TM UNIT VOLTAGE 208/230 016 025 028 MAXIMUM ACCEPTABLE CONTINUOUS BHP* Motor Performance MAXIMUM ACCEPTABLE CONTINUOUS BkW* MAXIMUM ACCEPTABLE OPERATING WATTS 4.57 4.57 5,180 5,180 575 208/230 6.13 4.57 5,180 6.0 5.90 4.40 5,180 15.8 460 5.90 4.40 5,180 7.9 575 206/230 5.90 8.70 4.40 6.49 5,180 7,915 6.0 22.0 460 9.50 7.08 8,640 13.0 575 208/230 8.70 6.49 7,915 10.0 10.20 7.61 9,510 28.0 11.80 10.20 8.80 7.61 11,000 9,510 14.6 13.0 460 575 LEGEND BHP -BkW-- MAXIMUM AMP DRAW 6.13 6.13 460 020 Evaporator-Fan Brake Horsepower Brake Kilowatts *Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range of the motors can be utilized with confidence. Using your fan motors up to the horsepower (brake kilowatt) ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. Table 20 -- Evaporator-Fan MOTOR HORSEPOWER Motor Efficiency MOTOR EFFICIENCY !%) 5 Hp 87.5 7,5 Hp 88,5 10 Hp 89,5 NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT) effective October 24, 1997. 34 15.8 7.9 Operating • • • • • Sequence COOLING, UNITS WITHOUT ECONOMIZER -- When thennostat calls for cooling, termimds G and YI ale energized. The indoor (evaporator) fan contactor (IFC), outdoor fan contactot (OFC), and compressor contactor no. 1 (Ci) m'e energized and evaporator-fan motol: condenser fans and compressor no. 1 stall. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts. • Indoor fan has been on for at least 30 seconds. The SPT, SAT. and OAT inputs must have valid readings. OAT must be less than 75 E OAT must be less than SPT. Enthalpy must be LOW (may be jumpered if an enthalpy sensor not available). Economizer position is NOT forced. Pre-cooling occm.s when there is no call from the thermostat except G Pre-cooling is defined as the economizer modulates to provide 70 F supply _fil: HEATING. UNITS WITHOUT ECONOMIZER (If Optional or Accessory Heater is Installed) --Upon a call for heating through terminal WI, IFC and heater contactor no. 1 (HCi) are energized. On units equipped for 2 stages of heat, when additional heat is needed HC2 is energized through W2. COOLING. UNITS WITH ECONOMISERIV --When free cooling is not available, the compressors will be controlled by the zone thermostat. When free cooling is available, the outdoor-air &unper is modulated by the EconoMiSerlV control to provide a 50 to 55 F supply-air temperature into the zone. As the supply-air temperature fluctuates above 55 or below 50 IF. the dampel.s will be modulated (()pen or close) to bring the supply-air temperature back within set point limits. For EconoMiSerIV operation, there must be a thermostat call for the fan (G). This will move the damper to its minimum position during the occupied mode. When free cooling is available the PremierLink control will control the compressors, energize the reversing valve(s) and economizer to provide a supply-air temperature determined to meet the YI and Y2 calls from the therlnostat using the following three routines. The three control routines are based on OAT. The 3 routines are based on OAT where: Above 50 F supply-air temperature, the dmnpers will modulate from 100% open to the minimum open position. From 50 F to 45 F supply-air temperature, the &_mpers will maintain at the minimum open position. Below 45 F the dampers will be completely shut. As the supply-air temperature rises, the dampers will come back open to the minimum open position once the supply-air temperature rises to 48 E If optional power exhaust is inst_flled, as the outdoor-air damper opens and closes, the power exhaust fans will be energized and deenergized. • SASP = Supply Air Set Point DXCTLO Routine • • • • • • • • • • • Damper movement from full closed to lhll open (or vice vel_a) will take between 11/2and 21/2 minutes. • • 1 (OAT < DXCTLO) economizer maintains a SASP = economizer maintains a SASP = 2 (DXCTLO < OAT < 68 F) If only YI energized, the economizer maintains a SASP = (SATLOI + 3). If SAT > SASP + 5 and economizer position > 80%, economizer will go to minimum position for 3 minutes or until SAT > 68 E First stage of mechanical cooling will be energized. Integrator resets. Economizer opens again and controls to current SASP after stage one on for 90 seconds. With Yi and Y2 energized economizer maintains an SASP = SATLO2 + 3. If SAT > SASP + 5 and economizer position >80%, economizer will go to minimum position for 3 minutes or until SAT > 68 IF. If compressor one is on then second stage of mechanical cooling will be energized. Otherwise the first stage will be energized. Integrator resets. Economizer opens again and controls to SASP after stage one on for 90 seconds. Routine If free cooling can be used as determined from the appropriate changeover command (switch, diy bulb, enthalpy curve, differential dry bulb, or differential enthalpy), a call for cooling (YI closes at the thermostat) will cause the control to modulate the &tmpel_ open to maintain the supply air temperature set point at 50 to 55 IF. Cooling Lockout Set Point Integral YI energized (SATLOI + 3). Y2 energized (SATLO2 + 3). Routine If Iield-installed accessory CO2 sensors are connected to the EconoMiSerIV control, a demand controlled ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the &_mper will be increased proportionally. As the CO2 level decreases because of the increase in fresh ail: the outdoor-air damper will be proportionally closed. Dmnper position will follow the higher demand condition from DCV mode or free cooling mode. 3 (OAT > 68) Economizer is opened 100%. Compressors 1 and 2 are cycled based on YI and Y2 using minimum on and off times and watching the supply-air temperature as compared to SATLOI and SATLO2 set points. If optional power exhaust is installed, as the outdoor-air &tmper opens and closes, the power exhaust fans will be energized and deenergized. If field-installed accessory CO2 sensors me connected to the PremierLink control, a PlD-controlled demand ventilation strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the &_mper will be increased proportionally. As the CO2 level decreases because of the increase in fresh air, the outdoor-air &tmper will be proportionally closed. HEATING. UNITS WITH ECONOMISER2, PREMIERLINK CONTROL AND A THERMOSTAT -- When the thermostat calls for heating, terminal WI is energized. The PremierLink control will move the economizer damper to the minimum position if there is a call for G and closed if there is a call for WI without G. In order to prevent thermostat from short cycling, As the supply-air temperature diops below the set point range of 50 to 55 IF. the control will modulate the outdoor-air dampers closed to maintain the proper supply-air temperature. HEATING, UNITS WITH ECONOMISERIV -- When the room thermostat calls for heat, the heating controls are energized as described in the Heating, Units Without Economizer section. When the indoor fan is energized, the economizer damper moves to the minimum position. When the indoor fan is off. then the economizer dmnper is fully closed. COOLING. UNITS WITH ECONOMISER2, PREMIERLINK TM CONTROL AND A THERMOSTAT -- When free cooling is not available, the compressol_ will be controlled by the PremierLink control in response to the YI and Y2 inputs from the thermostat. The PremierLink control will use the following to determine if free cooling is available: = Direct Expansion PID = Proportional information 35 the unit is locked into the heating mode for at least 10 minutes when WI is energized. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the electric heat (if used) comes on. When the thermostat is satisfied and WI is deenergized, the [FM stops. COOLING. UNITS WITH ECONOMI$ER2, PREMIERLINK TM CONTROL AND A ROOM SENSOR --When free cooling is not available, the compressors will be controlled by the PremierLink controller using a PID Error reduction cfdculation as indicated by Fig 44. strategy will begin to operate. As the CO2 level in the zone increases above the CO2 set point, the minimum position of the damper will be increased proportionally. As the CO2 level decreases because of the increase in fresh all: the outdoor-air damper will be proportionally closed. HEATING. UNIT WITH ECONOMISER2, PREMIERLINK CONTROL AND A ROOM SENSOR -- Every 40 seconds the controller will cfflculate the required heat stages (maximum of 3) to mainttfin supply-air temperature (SAT) if the following qufdifying conditions are met: • Indoor fan has been on for fit least 30 seconds. • COOL mode is not active. • OCCUPIED, TEMRCOMPENSATED START or HEAT mode is active. • SAT reading is available. • Fire shutdown mode is not active. The PremierLink controller will use the following information to determine if fiee cooling is available: • Indoor fan has been on for at least 30 seconds. • The SPT. SAT. and OAT inputs must have valid readings. • OAT must be less than 75 E • OAT must be less than SPT. • Enthalpy must be LOW (may be jumpered if and enthalpy sensor is not available). • Economizer position is NOT forced. If all of the above conditions me met, the number of heat stages is cfflculated; otherwise the required number of heat stages will be set to 0. If the PremierLink controller detemfines that heat stages are required, the economizer damper will be moved to minimum position if occupied and closed if unoccupied. When free cooling is available, the outdoor-air damper is positioned through the use of a Proportional Integral (PID) control process to provide a calculated supply-air temperature into the zone. The supply air will maintain the space temperature between the heating and cooling set points as indicated in Fig. 45. Staging should be as follows: If Heating PID STAGES=2 • • The PlemierLink control will integrate the compressw_ stages with the economizer based on similar logic as the three routines listed in the previous section. The SASP will float up and down based on the error reduction calculations that comptue space temperature and space set point. The reversing vfdves will be energized. • • • • • • conditions (75% capacity) will energize HSI (100% capacity) will energize HS2 In order to prevent short cycling, the unit is locked into the Heating mode for fit least 10 minutes when HS 1 is deenergized. On units equipped for two stages of heat, when additional heat is needed, it may be provided by electric heat (if supplied). When the space condition is satisfied and HSI is deenergized the IFM stops. The fan will run continuously in the occupied mode as required by national energy and fresh air standards. When outdoor-air temperature conditions require the economizer to close for a compressor stage-up sequence, the economizer control integrator is reset to zero after the stage-up sequence is completed. This plevents the supply-air temperature from diopping too quickly and creating a freeze condition that would make the compressor turn off prematurely. The high space set point is used for DX (direct expansion) cooling control, while the economizer space set point is a cfdculated value between the heating and cooling set points. The economizer set point will always be at least one degree below the cooling set point, allowing for a smooth transition from mechanical cooling with economizer assist, back to economizer cooling as the cooling set point is achieved. The compressors may be used for initifd cooling then the PremierLink controller will modulate the economizer using an error reduction calculation to hold the space temperature between the heating and cooling set points. See Fig. 45. The controller uses the following economizer cooling: HEAT STAGES=I HEAT STAGES=2 TEMPERATURE w 75, '_ 734 CE CONTROL 724- ...... SET POINT 714 I- -- w 704 TEMPERATURE o 694 CO 68 J TIME NOTE: PremierLink control performs smart staging of 2 stages of DX cooling and up to 3 stages of heat. to determine Fig. 44 -- DX Cooling Temperature Control Example Enthalpy is Low SAT reading is available OAT reading is available SPT reading is available OAT < SPT Economizer Position is NOT forced TEMPERATURECONTROL D 74 If any of the above conditions ale not met, the economizer submaster reference (ECSR) is set to maximum limit and the dmnper moves to minimum position. The operating sequence is complete. The ECSR is lecalculated eve U 30 seconds. _ 73 If an optional power exhaust is instfdled, as the outdoor-air dmnper opens and closes, the power exhaust fans will be energized and deenergized. ow ii 72 _- 711 t ......... .................................... F-----coo, SETPO, T / \ I-- v TEMPERATURE L___HEATSETPOINT TIME If field-installed accessory CO2 sensors me connected to the PlemierLink control, a PID-controlled demand ventilation Fig. 45 -- Economizer Temperature Control Example 36 SERVICE Evaporator Fan Performance Adjustment (Fig. 46 and 47) -- Fan motor pulleys ;u'e factory set for speed shown in Table 1. To change fan speeds: Before performing service or maintenance operations on unit, turn off main power switch to unit. Tnm off accessory heater power switch if applicable. Electrical shock could cause pel.sonal injury. 1. Shut offunit Ix_osen nuts on the 2 cmriage bolts in the motor mounting base. Install jacking bolt and plate under motor base (bolt and plate are shipped in inst_fller's packet). See Fig. 47. Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts. 3. Ix_osen movable-pulley 4. Screw movable flange towmd fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motol: Do not exceed maximum speed specified in Table 1. Cleaning -- Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit intefiol: EVAPORATOR cial coil cleanel; COIL -- Clean as required with a commer- NOTE: The 50TM028 unit has a mist eliminator screen attached to the evaporator coil to prevent condensate runoff at high wet-bulb conditions. Check periodically and clean as necessmy. CONDENSER COIL--Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly -- clean as required. CONDENSATE DRAINstart of cooling season. Check and clean each year 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each lull turn of pulley flange.) 6. Replace and tighten belts. See Belt Tension Adjustment section on this page. at To align fan and motor pulleys: 1. Ix)osen fan pulley setscrews. NOTE: The 50TM028 unit requires industri_d grade throwaway filters capable of withstanding face velocities up to 625 fpm. Ensure that replacement filters for the 50TM028 units are rated for 625 fpm. OUTDOOR-AIR INLET SCREENS -- Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens. 2. Slide fan pulley along fan shaft. 3. Make anguku" alignment mounting pkite. Evaporator Fan Service by loosening motor from and Replacement -- The 50TM020-028 units use a fan motor mounting system that features a slide-out motor mounting pkite. To replace or service the motor, slide out the bracket. See Fig. 47. 1. Remove the evaporator-fan control access panel. Lubrication COMPRESSORSEach compressor is charged with the correct amount of oil at the factory. Conventional white oil (Sontext 200LT) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition of oil is required. See compressor nameplate for original oil charge. A complete rechmge should be four ounces less than the origimfl oil charge. When a compressor is exchanged in the field it is possible that a major portion of the oil from the replaced compressor may still be in the system. While this will not affect the reliability of the replacement compressol: the extra oil will add rotor di'ag and increase power usage. To remove this excess oil, an access valve may be added to the lower portion of the suction line at the inlet of the compressol: The compressor should then be mn for 10 minutes, shut down, and the access valve opened until no oil fows. This should be repeated twice to make sure the proper oil level has been achieved. FAN SHAFT BEARINGS -- The bearings are of the pillow block type and have grease fittings. The bearing opposite the motor end has an extended tube line so it can be lubricated from the motor side. Lubricate the bearings twice annually. access panel and the heating 2. Remove the center post (located between the evaporator fan and heating control access panels) and all screws securing it. 3. Ix_osen nuts on the two carriage bolts in the motor mounting base. 4. 5. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts. Remove the belt (hive. 6. Remove jacking bolt and tapped jacking bolt plate. 7. Remove the 2 screws that secure plate to the motor support channel. 8. Remove the 3 screws from the end of the motor support channel that interfere with the motor slide path. 9. Slide out the motor and motor mounting 10. Disconnect wiring connections ing bolts. 11. Remove the motol: Typical lubricants me given below: Texaco Mobil Sunoco Texaco flange setscrew (see Fig. 46). See Table 12 for air quantity limits. FILTERS -- Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size. MANUFACTURER power supply. 2. 12. pkite. and remove the 4 mount- To install the new motol: reverse Steps 1-11. Belt Tension LUBRICANT Regal AFB-2* Mobilplex EP No. 1 Prestige 42 Multifak 2 the motor mounting Adjustment -- Toadjust belt tension: 1. Ix_osen fan motor bolts. 2. *Preferred lubricant because it contains rust and oxidation inhibitors. CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS -- The condenser-fan and evaporator-fan motors have permanently sealed bemings, so no field lubrication is necesstuy. 37 Adjust belt tension: a. Size 016 Units: Move motor mounting plate up or down for proper belt tension (l/z in. deflection with one finger). b. Size 020-028 Units: Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension (:Vs in. deflection at midspan with one finger [9 lb force]). 3. Tighten nuts. 4. Adjust boltsandnutonmounting plate tosecure motorin fixedposition. Condenser-Fan chmge systems using the MoistureMiSer dehumidification package, fully evacuate, recovo: and re-chtuge the system to the nmneplate specified charge level. To check or adjust refrigerant chalge on systems using the MoistureMiSer dehumidification package, chtu'ge per the sttm&u'd subcooling ch_u'ts. The subcooler MUST be deenergized to use the chtuging charts. The ch_uts reference a liquid pressme (psig) and temperatme at a point between the condenser coil and the subcooler coil. A tap is provided on the unit to measure liquid pressure entering the subcooler (leaving the condenser). Adjustment 50TM0I 6,020,028 UNITS (Fig. 48) 1. Shut off unit power supply. 2. Remove access panel(s) closest to the fan to be adjusted. 3. Ix)osen fan hub setscrews. 4. Adjust fan height on shaft using a straightedge placed across the fan orifice. 5. Tighten setscrews and replace panel(s). 6. Turn on unit powel: SECOND BELT ON 10 liP MOTOR ONLY) 50TM025 UNITS (Fig. 49) 1. Shut off unit power supply. 2. Remove fan top-grille assembly and loosen fan hub screws. 3. Adjust Nn height on unit, using a straightedge placed across the fan orifice. 4. 5. (028 UNITS BE PARALLEL WITR BELT(S) / ENSURE PROPER CLEARANCE BETWEEN BELT(S) AND FAN SUPPORT NOTCH PULLEY Tighten setscrews and replace lubber hubcap to prevent hub fiom busting to motor shaft. Fill hub recess with permagum if robber hubcap is missing. MOVABLE FLANGES Power Failure -- Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper PULLEY 1710tOE Refrigerant Charge MOTORANDFAN SHAFTS MUST PARALLEL BE SETSCREWS_ -- Amount of refiigerant chalge is listed on unit nameplate and in Table 1. Refer to C;uTier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during ch;uging procedure. NOTE: Do not use recycled contaminants. refrigerant as it may FIXED SINGLE-GROOVE contain Fig. 46- NO CHARGE -- Use stan&ud evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant 0efer to Table 1). Evaporator-Fan Pulley Alignment and Adjustment FAN PULLEY LOW CHARGE COOLING -- Using cooling charging chmt (see Fig. 50), add or remove refrigerant until conditions of the chart are met. Note that charging chart is different from those normally used. An accurate pressure gage and temperaturesensing device is required. Charging is accomplished by ensuring the proper mnount of liquid subcooling. Measure liquid line pressure at the liquid line service valve using pressure gage. Connect temperature sensing device to the liquid line near the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading. TO USE THE COOLING CHARGING CHART -- Use the above temperature and pressure readings, and find the intersection point on the cooling charging chart. If intel_ection point on chart is above line, add refrigerant. If intersection point on chart is below line, ctuefully recover some of the charge. Recheck suction pressure as ch;uge is adjusted. NOTE: Indoor-air cfin must be within normal operating of unit. All outdoor fans must be operating. FLANGES ° CENTER POST BELT_ MOTOR PULLEY MOTOR PLATE MOUNTING PLATE R _ _o MOTOR SEE NOTE range M OTO R 2U ppo R_ The TXV (thermostatic expansion v;dve) is set to maintain between 15 and 20 degrees of superheat at the compressors. The v;dves abe factory set and should not require re-adjustment. _l_!r CHANNEL !"1_i'_ TMJ' JACKING BOLT NOTE: A 3V2-in. bolt and threaded plate are included in the installer's packet. They should be added to the motor support channel below the motor mounting plate to aid in raising the motor. The plate part number is 50DP503842. The adjustment bolt is 3/8-16 x 13/4 in.-LG. MOISTUREMISER TM SYSTEM CHARGING -- The system charge for units with the MoistureMiSer option is greater than that of the standard unit alone. The charge for units with this option is indicated on the unit nameplate drawing. To Fig. 47 -- Evaporator-Fan 38 Motor Section ._ r t , i Compressor Lockout i If any of the safeties (high-pressure. low-pressure, freeze protection thermostat, compressor internal flierlnostat) trip, or if there is loss of power to the compressors, die CLO (complessor lockout) will lock the compressors off. To reset, manually move the therlnostat setting. EVAPORATOR FAN MOTOR PROTECTION i A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before lesetting the breakel: CONDENSER-FAN MOTOR PROTECTION -- Each condenser-fan motor is internally protected against overtemperature. HIGH-PRESSURE AND LOW-PRESSURE SWITCHES -If either switch trips, or if the compressor overtemperatule switch activates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move the thermostat setting. FREEZE PROTECTION THERMOSTAT (FPT) i An FPT is located on the top and bottom of die evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to cleal: Once the frost has melted, the compressor can be leenergized. ........ ) ) oo +o:o= NOTE: Dimensions are in inches). Fig. 48 -- Condenser-Fan 50TM016,020,028 Adjustment, RAIN SHIELD NOTE: Dimensions are in inches. Fig. 49 -- Relief Condenser-Fan 50TM025 ALL OUTDOOR Devices -- All units have relief devices to protect against damage from excessive plessures (e.g., fire). These devices protect the high and low side. Adjustment, Control Circuit, 24-V -- This control circuit is protected against overcunent by a 3.2-amp circuit breaker Breaker can be reset. [f it trips, determine cause of trouble before resetting. See Fig. 51 and 52 for typical wiring. BOTH CIRCUITS FANS MUST BE OPERATING Replacement Parts parts may request. be obtained Diagnostic LEDs for diagnostic page 43. purpose. -- A complete list of replacement from any Carrier distributor upon -- qn_e unit control bomds have LEDs Refer to Troubleshooting section on Optional Hinged Access Doors -- When the optional service package is ordered or the if the hinged access doors option is ordered, the unit will be provided with external and internal hinged access doors to facilitate service. 50 100 150 200 250 300 350 Four external hinged access doors are provided on size 016025 units. Two external hinged doors ;ue provided on size 028 units. All external doors ale provided wifli 2 huge V4 turn hitches with folding bail-type handles. (Complessor access doors have one hitch.) A single door is provided for filter and drive access. One door is provided for control box access. The control box access door is interlocked with the non-fused disconnect which must be in the OFF position to open the dool: On size 016-025 units, two doors are provided for access to the compressor compartment. 400 LIQUID PRESSURE AT LIQUID VALVE (PSIG) Fig. 50 -- Cooling Charging Chart Filter Drier -- Replace whenever refiigerant system is exposed to atmosphere. Protective Overcurrent protection. Two internal access doors are provided inside the filter/ diive access door The filter access door (on the left) is secmed by 2 small 1/4turn latches with folding bail-type handles. This door must be opened prior to opening the diive access door The drive access door is shipped with 2 sheet metal screws holding the door closed. Upon initial opening of the dool: these screws may be removed and discarded. The door is fllen held shut by the filter access dook which closes over it. Devices COMPRESSOR PROTECTION -- Each compressor has internal line break motor Crankcase Heater -- All units are equipped with a 70-watt crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. The crankcase heater is energized whenever there is a main power to the unit and the compressor is not energized. energize the crankcase heaters for 24 hours before starting I IMPORTANT: shutdown or servicing, the compressors. After prolonged 39 ELECTRIC HEAT OPTION -BL ELECTRIC 208/240v _C_ HEAT 200/230V AMPS KW : A SEE ELECTRIC HEAT CHARY 71.3/823 25.71342 B 1171135 42.21561 C 156/180 56,2/74,8 -BL I " _c_ _BL , Y[ I Hc_ U " , {A _ C ONLY) /, I (B O_LY)_ I BL_ at_ SUPPLY" Y[L _L CC_ t3 II I I L 1 1 ,_ I _ _--_-- BL_ °"-_ _---_'<_-_ CAP2 o, m_ ore _, OFW_ :,: .... Bt_ _L_ _ic_ I y[L_) _ :LsELECIRTIC _BR_ B_ BR_ > TRA_ _2 RE_ ..... _'_;_gt ........... TO ECONOMIIZR OPIIONIACCgSSORY Bp_ _. TO ECONOMIZER OPTIONIACCESSORY 2081230V TM016.020 L REVIS]O. RZCOR_ P^_l _uwB[r 2081230V 017 TON 50HJ503171 SHY 2 OF __ _ _ 60 -<'I-- ,_._ vlo oPtmN _ .coy _eL-<<-- _ | vio _t j 3 Fig. 51 -- Typical Wiring Schematic 4O (50TM016,020 208/230 V Shown) COMPONENT ARRANGEMENT CONTROL BOX 0 _111 I-- OISCONNECT PERHElm _ m m BL_ PL1-R = F _{_cT_T_c i_ iEO_O 6_,_T_ " q i F _¢ii_c _- G_Ti_i" q iE]E]E]E] i° °__o_ !;2 LF:_.P,_....... J : o o o o o o o ) o_ -o i L FLI._.FLO .... j {A) zv 10v 0 to MAI_ CONYROL BOX PLI Fig. 52 -- Typical Component Arrangement (50TM016,020 41 Shown) LEGEND AND NOTES FOR FIG 51 AND 52 LEGEND AHA C CAP CB CC CH CLO COMP CR DM DU ------------ Adjustable, Heat Anticipator Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Motor Control Relay Damper Motor Dummy Terminal EQUIP FL FPT FU GND ------ Equipment Filament Freeze Protection Thermostat Fuse Ground HC HPS HTR IAQ IFC IFCB IFM IFR L LOR LPS LS ------------- Heater Contactor High-Pressure Switch Heater Indoor Air Quality Sensor Indoor Fan Contactor Indoor Fan Circuit Breaker Indoor Fan Motor Indoor Fan Relay Light Lockout Relay Low-Pressure Switch Limit Switch NEC OAT OCCUP OFC OFM OP ------- National Electrical Code Outdoor Air Temperature Sensor Occupancy Sensor Outdoor Fan Contactor Outdoor Fan Motor Overcurrent Protection PL PRI QT RAT SW TB TC TH TRAN Q O [_ • ---------- Plug Assembly Primary Quadruple Terminal Return Air Temperature Switch Terminal Block Thermostat Cooling Thermostat Heating Transformer Sensor Terminal (Marked) Terminal (Unmarked) Terminal Block Splice Factory Wiring E mE Field Wiring Option/Accessory _ To indicate common potential only; not to represent wiring. Economizer Motor Wiring _ Remote Pot Field Accessory OAT Sensor _ Disch Air Sensor RAT Accessory Sensor Low Ambient Lockout Switch NOTES: 1. Compressor and/or fan motor(s) thermally protected three phase motors protected against primary single phasing conditions. 2. If any of the original wire furnished must be replaced, it must be replaced with Type 90 ° C or its equivalent. 3. Jumpers are omitted when unit is equipped with economizer. 4. IFCB must trip amps is equal to or less than 140% FLA. 5. On TRAN1 use BLK lead for 460 v power supply and ORN lead for 575 v power supply. 6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. 7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single pole, double throw contact. An underlined number signifies a normally closed contact. Plain (no line) number signifies a normally open contact. 8. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb. 9. If a separate field supplied 24 v transformer is used for the IAQ sensor power supply, it cannot have the secondary of the transformer grounded. 10. OAT sensor is shipped inside unit and must be relocated in the field for proper operation. 11. For field installed remote minimum position POT. remove black wire jumper between P and P1 and set control minimum position POT to the minimum position. 42 TROUBLESHOOTING Unit Troubleshooting troubleshooting -- should turn on. The actuator should drive to between 90 and 95% open. 4. Turn the Exhaust potentiometer CW until the Exhaust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actuator should lemain in position. 5. Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9-v. The actuator should chive fully closed. 6. Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on. 7. Return EconoMiSerlV settings and wiring to normal after completing troubleshooting. DCV MINIMUM AND MAXIMUM POSITION -- To check the DCV minimum and maximum position: Refer to Tables 21 and 22 for details. EconoMi$erlV Troubleshooting-- for EconoMi$erIV logic. See Table 23 A fiJnctional view of the EconoMiSer is shown in Fig. 53. Typical settings, sensor ranges, and jumper positions me also shown. An EconoMi$erIV simulator program is available flom Cartier to help with EconoMiSerIV tr;fining and troubleshooting. ECONOMI$ERIV PREPARATION -- This procedure is used to prepare the EconoMiSerIV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9-v battery. 1.2 kilo-ohm resistol: and a 5.6 kilo-ohm resistor which are not supplied with the EconoMiSerlV. IMPORTANT: tiometers before Bestarting sure totroubleshooting. record the positions 1. Make sure EconoMiSerIV preparation procedure has been performed. 2. Connect a 9-v battely to AQ (positive node) and AQI (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. 3. Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 4. Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed. 5. Turn the Minimum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open. 6. Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open. 7. Remove the jumper from TR and N. The actuator should &ive fully closed. 8. Return EconoMi$erIV settings and wiring to normal after completing troubleshooting. of all poten- 1. Disconnect power at TR and TRI. All LEDs should be off. Exhaust fan contacts should be open. 2. Disconnect device at P and Pl. 3. Jumper P to Pl. 4. Disconnect wires at T and TI. Place 5.6 kilo-ohm resistor across T and TI. 5. Jumper TR to 1. 6. Jumper TR to N. 7. If connected, remove sensor from terminals So and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals So and +. 8. Put 620-ohm resistor across terminals SR and +. 9. Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise). 10. Set DCV maximum position potentiometer fiJlly CW Iclockwise). 11. Set enthalpy potentiometer to D. 12. Apply power (24 vac) to termimds TR and TRI. DIFFERENTIAL ENTHALPY-To check differential enthalpy: 1. Make sure EconoMiSerIV preparation procedure has been performed. 2. Place 620-ohm resistor across So and +. 3. Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit. 4. Remove 620-ohm resistor across So and +. The Free Cool LED should turn off. SUPPLY-AIR INPUT -- To check supply-air input: 1. Make sure EconoMiSerlV preparation procedure has been performed. 2. Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open. 3. Remove the 5.6 kilo-ohm resistor and jumper T to TI. The actuator should drive fully open. 4. Remove the jumper across T and TI. The actuator should &ive fully closed. 5. Return EconoMiSerIV settings and wiring to normal after completing troubleshooting. ECONOMISERIV TROUBLESHOOTING COMPLETION -- This procedure is used to return the EconoMiSerlV to operation. No troubleshooting or testing is done by performing the following procedure. 5. Return EconoMiSerIV settings and wiring to normal after completing troubleshooting. SINGLE ENTHALPY -- To check single enth_dpy: 1. Make sure EconoMiSerIV preparation procedure has been performed. 2. Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit. 1. Disconnect power at TR and TRI. 2. Set enthalpy potentiometer to previous setting. 3. Set DCV maximum position potentiometer to previous setting. 4. Set minimum position, DCV set point, and exhaust potentiometels to previous settings. 5. Remove 620-olun resistor from terminals SR and +. 6. Remove 1.2 kilo-olnn checkout resistor from termimds So and +. If used, reconnect sensor from temfin_ds So and +. 7. Remove jumper from TR to N. 8. Remove jumper from TR to 1. 9. Remove 5.6 kilo-ohln resistor from T and TI. Reconnect wires at T and TI. 10. Remove jumper from P to PI. Reconnect device at P and PI. 11. Apply power (24 vac) to terminals TR and TRI. 3. Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off. 4. Return EconoMiSerIV settings and wiring to normal after completing troubleshooting. DCV (Demand Controlled Ventilation) AND POWER EXHAUST -- To check DCV and Power Exhaust: 1. Make sure EconoMiSerlV preparation procedure has been performed. 2. Ensure terminals AQ and AQI are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed. 3. Connect a 9-v battery to AQ (positive node) and AQI (negative node). The LED for both DCV and Exhaust 43 Table 21 -- MoistureMi$er PROBLEM Subcooler Dehumidification TM Subcooler Service Analysis CAUSE Will Not Energize REMEDY No power to subcooler control transformer. No power from subceoler control transformer line three-way valve. Check power source. Ensure all wire connections are tight. to liquid Liquid line three-way valve will not operate. Subcooler Will Not Deenergize Low refrigerant fuse. Ensure continuity of wiring, low pressure switch open. allow low-pressure switch switch if it will not close, check transformer, 1. Solenoid coil defective; replace. 2. Solenoid valve stuckclosed; replace. Liquid Line three-way valve will not close. Low System Capacity 1. Fuse open; check 2. Subcooler control Cycle unit off and to reset. Replace 3. Transformer bad; Valve is stuck open; replace. charge or frosted coil. 1. Check charge amount. See system charging section. Evaporator coil frosted; check and replace subceeler control low-pressure switch if necessary. 2. Table 22 -- Cooling PROBLEM CAUSE Compressor and Condenser Fan Will Not Start, Insufficient Compressor Will Not Start but Condenser Fan Runs. contactor, transformer, Head Pressure. Determine Lower thermostat setting too high. Check wiring and repair or replace, Determine cause, Replace compressor, Defective overload. Determine cause and replace, Compressor Determine cause for safety trip and reset lockout, locked out Refrigerant power dead, overcharge Replace fuse or reset circuit breaker, Determine cause, or undercharge. Defective compressor, Recover refrigerant, evacuate system, and recharge to nameplate, Replace and determine cause. Insufficient line voltage. Blocked condenser. Determine Determine cause and correct, cause and correct, Defective overload. Determine cause and replace, Defective thermostat, Replace thermostat, motor, Replace, in refrigerant system. Locate restriction and remove, Dirty air filter, Unit undersized for load. Replace filter. Decrease load or increase unit size. Thermostat Reset thermostat, set too low. Low refrigerant charge, Locate leak, repair, and recharge, Air in system. Recover refrigerant, Condenser Clean coil or remove restriction, coil dirty or restricted, Dirty air filter, Clean coil, overcharged, Recover excess refrigerant. 1. Check TXV bulb mounting and secure tightly to suction line, 2. Replace TXV if stuck open or closed, Air in system. Condenser Suction Pressure. Too Low. Recover refrigerant, air restricted or air short-cycling. Determine Check for leaks, repair, and recharge. Restriction Remove restriction, in liquid tube. High heat load, Check for source and eliminate, Faulty TXV, 1. Check TXV bulb mounting and secure tightly to suction line, 2. Replace TXV if stuck open or closed. overcharged, Recover excess refrigerant. Dirty air filter, Replace filter. Low refrigerant charge, Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to suction line, 2. Replace TXV if stuck open or closed. Insufficient evaporator Temperature Field-installed airflow. too low in conditioned Increase air quantity. Check filter and replace if necessary, area. Reset thermostat. filter drier restricted. Replace. LEGEND TXV -- Thermostatic evacuate system, and recharge, cause and correct, Low refrigerant charge, Refrigerant Suction Pressure evacuate system, and recharge, Replace filter. coil. Faulty TXV. Excessive setting below room temperature, Faulty wiring or loose connections in compressor circuit, Compressor motor burned out, seized, or internal overload open. Refrigerant Too Low, cause and correct, Thermostat Dirty condenser Head Pressure Replace component, Check wiring diagram and rewire correctly. Restriction Excessive or control line voltage. Faulty condenser-fan Operates Call power company. Replace fuse or reset circuit breaker, Incorrect or faulty wiring. One leg of 3-phase Compressor Cycles (other than normally satisfying thermostat). REMEDY Power failure, Fuse blown or circuit breaker tripped, Defective thermostat, relay. Compressor continuously. Service Analysis Expansion Valve 44 Table 23 -- EconoMi$erlV Input/Output Logic INPUTS Demand Control Ventilation (DCV) Below set (DCV LED Off) Above set (DCV LED On) OUTPUTS Enthalpy* Outdoor N TerminaH- Compressor Return High (Free Cooling LED Off) Low Low (Free Cooling LED On) High High (Free Cooling LED Off) Low Low (Free Cooling LED On) High *For single enthalpy control, the module compares enthalpy to the ABCD set point. 1-Power at N terminal determines Occupied/Unoccupied 24 Vac (Occupied), no power (Unoccupied). **Modulation is based on the supply air sensor signal. ttModulation is based on the DCV signal. Y1 Y2 Stage 1 Stage 2 On On On Off On On On Off Off Off Off Off On On On Off On Off Off Off On On Occupied Unoccupied Damper Minimum position Closed Off Off Modulating** (between min. 3osition and full-open) Modulating** (between closed and full-open) Off Off Minimum position Closed On Off On On On Off Modulatingl-t (between min. 3osition and DCV maximum) Off Off Off Off Modulatingtl(between closed and DCV maximum) On On On Off On Off Off Off Modulating*** Modulatingl-l-t Off Off Off Off ***Modulation is based on the greater of DCV and supply air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply air signal). tttModulation is based on the greater of DCV and supply air sensor signals, between closed and either maximum position (DCV) or fully open (supply air signal). outdoor setting: Fig. 53 -- EconoMi$erlV 45 Functional View INDEX Air quantity limits 30 Carrier Comfort Network0) ChaNingchart, refrigerant Clearance 4-7 CO2 sensor Configuration 27 Settings 26, 27 Compressor Lubrication 37 Mounting 30 Rotation 30 Condensate drain Cleaning Location Condenser 16 39 .;7 9, 10 coil 8 Cleaning 37 Condenser fan 8 Adjustment 3& 39 Control circuit Wiring 10 Convenience outlet 13 Demand control ventilation Dehumidification 27 Dimensions 2, 3, 5-7 Ductwork 9 EconoMi$erIV 22-27 Control mode 24 26 Controller wiring 23 Damper nlovement 26 Demand ventilation control 26 Troubleshooting 43, 45 Usage 24 Wiring 23 EconoMi$er2 22, 23 Electrical connections 10 Electricaldata 11, 12 Enthalpy changeover set points 25 Evaporator coil 8 Cleaning 37 Evaporator fan motor Lubrication .;7 Motor data 34 Performance 31-33 Pulley adjustment 3Z .;8 Pulley setting 8, 34 Speed 34 Filter Cleaning .;7 Size 8 Freeze protection thermostat Heat anticipator settings 13 High-pressure switch 8, 39 Horizontal adapter roof curb Humidistat 28 Outdoor air inlet screens Cleaning 37 Dimensions 8 Physical data 8 Power supply 10 Wiring 10 PremierLink TM controls 16-19 Pressure, drop Economizer 33 Electric heat 33 MoistureMiSer 33 Pressure switches High pressure 8 Low pressure 8 Refrigerant Charge 38 Type 8 Refrigerant service ports 30 Replacement parts .;9 Return air filter 8, 30 Return air temperature sensor 25 Rigging unit 4 Roof curb Assembly 1 Dimensions 2, 3 Leveling tolerances 2-4 Safety considerations 1 Service 37-42 Start-up .;0-36 Start-up checklist CL-1 Supply-air temperature sensor 16,22 Thermostat 10 Troubleshooting 43-45 Weight Corner 5-7 Economizer 5-8 Maximum 4 Unit 5-8 Wind baffle 14, 15 Wiring Differentialenthalpy control 21 EconoMiSerlV 23 EconoMiSer2 23 Power connections 10 PremierLink 18 Thermostat 10 Unit 40, 41 8, 39 4 Indoor air quality sensor 16 Low-pressure switch & .;9 Manual outdoor air damper 13 MoistumMiSer TM dehumidification 28, 29, 38, 44 Motormasterq_) control 14, 15 Mounting Compressor 30 Unit 4 Non-fused disconnect 13 Operating limits 15 Operating sequence 35, 36 Cooling 35 EconoMi$erlV 35 EconoMi$er2 with PremierLink control 3.5,.;6 Heating 35 Outdoor air hood 13, 14 Outdoor air temperature sensor 16, 22 Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53500009-01 Printed in U.S.A. or designs without notice and without incurring obligations. Form 50TM-4SI Pg 46 4-06 Replaces: 50TM-3SI START-UP CHECKLIST MODEL NO.: SERIAL DATE: TECHNICIAN: NO.: PRE-START-UP: [] VERIFY THAT ALL PACKING MATERIALS [] VERIFY INSTALLATION OF INDOOR FAN MOTOR [] VERIFY INSTALLATION OF ECONOMIZER [] VERIFY THAT CONDENSATE [] VERIFY THAT ALL ELECTRICAL FROM UNIT ADJUSTMENT BOLT AND PLATE HOOD CONNECTION IS INSTALLED CONNECTIONS [] CHECK THAT FILTERS AND SCREENS [] VERIFY HAVE BEEN REMOVED PER INSTRUCTIONS AND TERMINALS ARE TIGHT ARE CLEAN AND IN PLACE THAT UNIT IS LEVEL [] CHECK FAN WHEEL IS TIGHT AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW LU [] VERIFY THAT FAN SHEAVES [] VERIFY THAT SCROLL [] VERIFY THAT CRANKCASE ARE ALIGNED AND BELTS ARE PROPERLY zm TENSIONED c_ COMPRESSOR HEATER IS ROTATING IN THE CORRECT HAS BEEN ENERGIZED LU DIRECTION I-- FOR 24 HOURS rm Z o, < I- START-UP: o ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS -- -- COMPRESSOR COMPRESSOR NO. 1 NO. 2 SUPPLY FAN AMPS L3-LI LI L2 L3 LI L2 L3 L2 L3 LI RES OUTDOOR-AIR RETURN-AIR L2-L3 EXHAUST FAN AMPS ELECTRIC HEAT AMPS (IF SO EQUIPPED) TEMPERATU LI-L2 TEMPERATURE LU F DB (Dry-Bulb) TEMPERATURE zm F DB F WB (Wet-Bulb) rm LU COOLING ELECTRIC SUPPLY AIR I- IF HEAT SUPPLY AIR (IF SO EQUIPPED)_ c_ F Z o, PRESSURES < I- REFRIGERANT SUCTION CIRCUIT NO. I PSIG CIRCUIT NO. 2 REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 [] VERIFY REFRIGERANT CHARGE USING CHARGING o PSIG PSIG CHART ON PAGE 39. GENERAL [] ECONOMIZER [] VERIFY MINIMUM INSTALLATION VENT AND CHANGEOVER OF ALL OPTIONS SETI'INGS TO JOB REQUIREMENTS AND ACCESSORIES Copyright 2006 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications Book 1 14 Tab 1b 16b Catalog No. 04-53500009-01 Printed in U.S,A. or designs without notice and without incurring obligations. Form 50TM-4SI Pg CL-1 4-06 Replaces: 50TM-3Sl
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 48 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 3, 2, 1, 4 Create Date : Fri Apr 20 14:41:28 2007 Author : Title : Subject :EXIF Metadata provided by EXIF.tools