CARRIER Package Units(both Units Combined) Manual L0912106
User Manual: CARRIER CARRIER Package Units(both units combined) Manual CARRIER Package Units(both units combined) Owner's Manual, CARRIER Package Units(both units combined) installation guides
Open the PDF directly: View PDF .
Page Count: 44
Download | |
Open PDF In Browser | View PDF |
® Irn to the Expertg_ Installation Instructions NOTE: Read the entire the installation TABLE instruction before SAFETY starting OF CONTENTS SAFETY CONSIDERATIONS INSTALLATION manual .................... 1 ............................... Step 1 - Plan for Unit Location Step 2 - Plan for Sequence 5 .................. of Unit Installation Step 3 - Inspect Unit ........................... Step 4 - Provide Unit Support Step 5 - Field Fabricate 5 6 6 ................... Ductwork Step 6 - Rig and Place Unit ...... 6 ................ 8 ..................... 8 Step 7 - Convert to Horizontal and Connect Ductwork ............................ 9 Step 8 - Install Outside 9 Air Hood Step 9 - Install Flue Hood Step 10 - Install Gas Piping ................ ..................... .................... Step 11 - Install External Condensate and Line ........................... Step 12 - Make Electrical 10 11 Trap 13 Connections Step 13 - Humidi-MiZer TM-Space RH Controller ........... .................. Step 14 - Adjust Factory-Installed Step 15 - Install Accessories Options ................... 13 37 ........ 43 43 CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in USA, ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements. It is important to recognize safety information. This is the safety-alert symbol A'x. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. FIRE,EXPLOSION HAZARD Failuretofollowthiswarningcouldresultinpersonal injuryordeath. Disconnect gaspipingfromunitwhenleaktestingat pressure greaterthan0.5 psig(3450Pa).Pressures greater than0.5psig(3450Pa)will causegasvalve damage resulting in hazardous condition. If gasvalve is subjected to pressure greaterthan0.5 psig(3450 Pa),it mustbereplaced beforeuse.Whenpressure testingfield-supplied gaspipingat pressures of 0.5 psig(3450Pa)orless,aunitconnected to suchpiping mustbeisolated byclosing themanual gasvalve. PERSONAL HAZARD INJURY Failure to follow injury or death. AND this warning ENVIRONMENTAL could Relieve pressure and recover all system repair or final unit disposal. Ware safety glasses and gloves refrigerants. Keep torches and other away from refrigerants and oils. cause refrigerant personal before when handling ignition sources CUT HAZARD ELECTRICALSHOCKHAZARD Failure to follow this warning could cause personal injury or death. Before performing service or maintenance operations on unit, always turn oft" main power switch to unit and install lockout tag. Unit may have more than one power switch. UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury, death and/or equipment damage. Puron ® (R-410A) refrigerant systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on Puron refrigerant equipment. Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing equipment. 53 3/8 E848] NOTES: 1 DIMENSIONS ARE IN INCHES, DIMENSIONS IN [ ] ARE IN MILLIMETERS 2 _ CENTER OF GRAVITY 3 _ DIRECTION 32 f ECONOMIZER HOOD (OPTIONAL} 1/4 [818] 16 [406] Lc OF AIR FLOW 2B 5/8 10 718 [277] [652] ik RE'TURN _ RETURN AIR AIR 44 [111_] CONDENSATE GRAIN OPENING IN 18 8ASERAN 26 f [41 [411] 16 [563] !/8 14 ,Z [512] 1/4 12 //4 6 //2 SUPPLY [747] 1/4 E ALT l_iil I [B71B]IAR l 12 B 3/B 1/8 [85] [307] _FLUE HOOD [lO0] N _L 4 / _ 18 TOP !/2 E_Yo] B/8 [1/8] fELECTRICAL DISCONNECT CONTROL ACCESS BOX INDOOR PANEL ACCESS 8LOWER INSTALLED DISCONNEcTOPTIONAL--'__FACTORY _oo _ Bs/B-- I_ HANDLE_ B 3/4 [95] [67] TYP CURB [1!87] __ " o6 _: L Bs,8 [213] _ 30 1/8 LEFT [1888] FRONT FILTER ACCESS PANEL (TOOL LESS} COMP ACCESS PANEL CONDENSER COIL INDOOR COIL ACCESS PANEL BACK RELIEF BAROMETRIC FLOW RIGHT AIR AIR Vertical Connections !1 / Economizer B/8 [289] E1 B //8 _oo [155] t Horizontal Connections THRU THESE CONNECTION HOLES 3/8 II [55] DIA FIELD POWER SUPPLY CONDUIT 2" C D [BO] BIA 3/4" 7/811 POWER [B1] [22] DIA DIA SUPPLY GAUGE FIEL8 NROCNOUT 314" 14 NPT cONDENSATE F liB" 14 NPT GAS 8 B llZ II [64] 81A ' DO / Economizer THE FOR ACCESS CONTROL PLUG WIRING BASE USE CHART CRBTMPWROOIAOl, HOLE Y¢ 3/411 Z@* {003) DRAIN sUPPLY USE REQ'D OOBAOl HOLE A_C (OO/,OO3) ]12 7/8" 24V II ÷ FOR ÷÷ (OOl} //811 POWER FPT "THRU FITTINGS NNOCK WINE II CONNECTION POWER SIZE 1/211 FOR E _ SIZES (MAX) UNIT !8 %/8 HOLE lIB 8 E1 :_ SIZES THREADED A REQUIRED " GAS THE BASEPAN" FOR ONLY SELECT POWER, ×,Y, / !/8" 1 3116 [22Z] OPTION, & Z PROVIDE8 EITHER B/4" OR I/2" DEPENDING OR WIRE AB4 [B47] [472] [284] II FACTORY ARE 48TC [222] [300] _urc A0_ _L?,';,%18 SIZE OUT PROVIGES FLANGE 3/4" FPT & FITTIRG THRU CURB C09303 Fig. 1 1 Unit Dimensional Drawing UNIT STD UNIT WEIGHT LBS. KG, CORNER WEIGHT (A) LBS. KO. CORNER WEIGHT (B) LBS. KG. CORNER WEIGHT (C) LBS, KG. CORNER WEIGHT (D) LBS, KG. C.G. HEIGHT X Y Z 48TC-A04 483 219 111 50 125 57 131 59 116 53 59 [991] 25 [584] 48TC-AO5 557 244 124 56 I39 63 145 66 129 59 59 [991] 23 [584] 48TC-A06 569 258 131 59 147 67 154 70 137 62 59 [991] 25 [584] 17 1/4 [458] 48TC-A07 652 296 150 68 169 76 176 80 157 71 39 [991] 23 [584] 20 [511] CORNER A 16 3/8 [416] 17 [432] 1/8 CORNERB L @, 0 @ " CORNERO CORNER C × -- TOP 1 i E_ ,:]oo FRONT C09304 Fig. 1 - Unit Dimensional Drawing (cont.) INSTALLATION Jobsite NOTE: Consider also the effect of adjacent units. Be sure that unit is installed such that snow will not block the combustion intake or flue outlet. Survey Complete the following checks before 1. Consult local building codes Electrical Code) ANSI/NFPA tion requirements. 2. Determine unit location unit location. installation. and the NEC (National 70 for special installa- (from project plans) 3. Check for possible overhead obstructions interfere with unit lifting or rigging. Step 1 -- Plan for Unit or select which may Location Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 2. Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used. Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA--54--84--1. In Canada, installation must be in accordance with the CANl--B149 installation codes for gas burning Although unit is weatherproof, water from higher level runoff the unit. appliances. avoid locations and overhangs that permit to fall onto Locate mechanical draft system flue assembly (1.2 m) from any opening through which products could enter the building, and at least from any adjacent building (or per local code). flue assembly at least 10 ft (3.05 m) from unit's fresh air intake hood if within 3 ft (0.91 elevation (or per local code). When unit adjacent to public walkways, flue assembly least 7 ft (2.1 m) above grade. < _42" Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 -Install External Condensate Trap and Line - for required trap dimensions. (1067) J _. J jJ . // 1 Required Otherwise, Roof bottom condensate drain connection. 36" (914mm) for condensate connection. C07459 Fig. 2 - Service Clearance at least 4 ft combustion 4 ft (1.2 m) Locate the an adjacent m) of same is located must be at Dimensional Drawing mount -- Check building codes requirements. Unit operating for weight weight is shown distribution in Table 1. Table 1 - Operating Weights 48TC UNITS LB (KG) Component A04 A05 A08 A07 Base Unit 483 (219) 537 (244) 569 (258) 852 (298) Vertical 50 (23) 50 (23) 50 (23) 50 (23) Horizontal 80 (38) 80 (38) 80 (38) 80 (38) 27 (10) 34 (13) 34 (13) 41 (15) Cu Fins 25 (11) 43 (20) 56 (25) 73 (33) Powered Outlet Curb 32 (15) 32 (15) 32 (15) 32 (15) Economizer Humidi-MiZer T_System 14-in/356 mm 110 (50) 110 (50) 110 (50) 110 (50) 24-in/610 mm 145 (66) 145 (66) 145 (66) 145 (66) Step 2 1 Plan for Sequence of Unit Step 4 1 Installation The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps. Curb-mounted installation Install curb Install field-fabricated i ductwork inside curb Install accessory thru-base service connection package (affects curb and unit) (refer to accessory installation instructions for details) Prepare bottom condensate drain connection to suit planned condensate line routing (refer to Step 11 for details) Rig and place unit Install outdoor air hood Install flue hood Install gas piping Install condensate line trap and piping Make electrical connections installation i Prepare pad and unit supports Check and tighten connection plug the bottom Unit Support Roof Curb Mount i Accessory roof curb details and dimensions are shown in Fig. 3. Assemble and install accessory roof curb in accordance with instructions shipped with the curb. NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 3. Improperly applied gasket can also result in air leaks and poor unit performance. Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 4. Refer to Accessory Roof Curb Installation Instructions for additional information as required. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork ntust be attached to curb and not to the unit. The accessory thru-the-base power and gas connection package must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired, use factory-supplied 1/2-in. pipe coupling and gas plate assembly to mount the thru-the-roof curb connection to the roof curb. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb. Install other accessories Pad-mounted Provide condensate drain If electric and control wiring is to be routed through the basepan, attach the accessory thru-the-base service connections to the basepan in accordance with the accessory installation instructions. Slab Mount (Horizontal Rig and place unit Convert unit to side duct connection arrangement Install field-fabricated ductwork at unit duct openings Install outdoor air hood Install flue hood Units Only) i Provide a level concrete slab that extends a minimum of 6 in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. Install gas piping NOTE: Horizontal units may be installed on a roof curb if required. Install condensate line trap and piping Make electrical connections Alternate Unit Support Mount) i Install other accessories A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side. Frame-mounted installation i Frame-mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan. Step 3 1 Inspect unit Inspect unit for transportation with transportation agency. damage. File any claim Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided. (In Lieu of Curb or Slab CONNECTOR PKG. ACCY. B D ALT DRAIN HOLE C GAS POWER ACCESSORY POWER CONTROL ROOFCURB ACCESSORY I A I UNIT SIZE 3/4" [_9} CRBTMPWROO1A01 NPT 1'-9W16" 1'-4" lS//' [551] [406] [44.5] 3//, [19] NPT 1/2" [12.7] NPT CRBTMPWROO3A01 1/2" [12.7] NPT CRRFCURB001A01 1_,, [12.7] NPT CRRFCURB002A01 "1 I I I I C # \ ! j \ I I _)4- %% \ I - I -- I ii I _ I # \\ _ \1 I # t. # A04-A07 8. Connector package CRBTMPWROO1A01 is for thru-the-curb type gas. CRBTMPWROO3A01 is for thru-the-base type gas connections. I "11 _ NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance: 4 ft on each side. 7. Direction of airflow. C _II 48TC 2'-0" I # I o" B" [TB] I f i/ TYPICAL o' I I- ..... (4) S[OES 7/+B _ q I 0'3" [78] I I I 2" I SUPPLY AIR I 7/18" I [34/] O" 0 ' 7/16" 1" HEADS) # I _ [/1] (BOLT I I T 7 13/16" 1"1 F O' 1/8" EBo_o_; + O" A 0 (BOLT 0 # R[D]D (F]ELD ]NSbLATION SUPPLIED) 7/+B" E++] HEM)S) OPENING 7/16" O' 0 ++E+U HEAl)} LT 518" I OPENING 1" 7 [8 I l [11] SERVICE 7//6" FOR BABEPAN (SEE O" 2 112" (BOLT 1' 0 #8) / //4 O' ENTRY NOTE iA I/4"[?] _ @ 4 = 13/15" [427] 8 SUPPLY AIR RETURN VIEW HEAD OF INSIDE AIR _. "A-A" BOLT OF TO BE ON FLANGE ) S' [I 705] ?SIS" NOTE= / CAMBR]DGEPORT +SURE FASTENING DEV]CE ALTERNATE CONSTRUCTION. IB LOCK" CORNER ACCEPTABLE C07503 Fig. 3 - Roof Curb Details Ducts passing through unconditioned spaces insulated and covered with a vapor barrier. If a plenum return is used on a vertical should be ducted through the roof deck applicable fire codes. c A minimum UM ALLOWABLE DIFFERENCE IN. (MM) -"'_--_ 8 A-B I Step 1.0" (25) [ 1.0" (25) 5 -- Field Fabricate Place unit, the return to comply with around ductwork. Unit Lifting holes are provided in base rails as shown Refer to rigging instructions on unit. C06110 Fig. 4 - Unit Leveling Tolerances Step Rig and is not required be Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information. B-c [ A-C 0.5" (13) J_ 6 -- clearance must in Fig. 5. Ductwork NOTE: Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or 0.45 in. wg (112 Pa) without economizer. UNIT DAMAGE Failure to follow equipment damage. For vertical ducted applications, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. (914-1371) this caution may All panels must be in place when rigging. designed for handling by fork truck. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. 36"- 54" HAZARD result in Unit is not If using top crate as spreader bar, once unit is set, carefully lower wooden crate off building roof top to ground. Ensure that no people or obstructions are below prior to lowering the crate. POSITION ALL SEAL STRIPS IN PLACE BEFORE INSTALLING UNIT ON ROOF CURB AS CLOSE TO THIS END AS POSSIBLE. DETAIL "A" SEE DETAIL < "A" C06005 UNIT DIMENSIONS MAX WEIGHT A B C LB KG IN IVllVl IN MM IN MM 48TC-A04 520 236 74.38 1888 39 991 33.38 848 48TC-A05 575 261 74.38 1888 39 991 33.38 848 48TC-A06 605 274 74.38 1888 39 991 33.38 848 48TC-A07 690 313 74.38 1888 39 991 41.38 1051 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the unit center of gravity. Use wooden top to prevent rigging straps from damaging unit. 3. Unit weights do not include economizer. Fig. 5 - Rigging Details Before setting the unit onto the curb, recheck gasketing on curb. Positioning on Curb -- Position unit on roof curb so that the following clearances are maintained: 1/4 in. (6.4 ram) clearance between the roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being Fig. 3, section C-C. approximately Although unit is weatherproof, guard higher level runoff and overhangs. against equal water \\ \\ to \ from \ _M_ REMOVABLE SUPPLY DUCI ItORIZONTAL OPENING COVER C06108 UNIT DAMAGE Fig. 6 - Horizontal HAZARD Failure to follow equipment damage. this caution may All panels must be in place when rigging. designed for handling by fork truck. result in Unit is not Flue vent discharge must have a minimum horizontal clearance of 4 f! (1220 mm) from electric and gas meters, gas regulators; and gas relief equipment. Minimum distance between unit and other electrically live parts" is 48 inches (1220 mm). Step 8 -- Install Outside Conversion Panels Air Hood The outdoor hood components are shipped in a box located in the unit return air compartment behind the outdoor-ar opening access panel (or economizer). Access is through the filter access panel. See Fig. 7. FILTER ACCESS PANEL Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Locate mechanical draft system flue assembly at least 48 in. (1220 ram) from an adjacent building or combustible material. NOTE: kit will Installation reduce the material to 18 in. (460 ram). After unit is in shipping materials. COMPRESSOR ACCESS PANEL of accessory flue discharge deflector minimum clearance to combustible position, remove Step 7 -- Convert to Horizontal Ductwork (when required) rigging skids OUTDOOR-AIR OPENING AND INDOOR COILACCESS PANEL C06023 and Fig. 7 - Typical and Connect Unit is shipped in the vertical duct configuration. Unit without factory-installed economizer or return air smoke detector option may be field-converted to horizontal ducted configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 6. Access Panel Locations 1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. 2. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. See Fig. 8. Field-supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof or building openings with counter flashing and mastic in accordance with applicable codes. HOOD BOX BRACKET II / / /I / / iI i/ II iI Do not cover or obscure visibility to the unit's informative data plate when insulating horizontal ductwork. iI ii iI 0 iI I C06024 Fig. 8 - Hood Box Removal Motorized 2-Position Damper Hood i 2. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. See Fig. 11. 1. Assemble outdoor-air hood top and side plates as shown in Fig. 9. Install seal strips on hood top and sides. Put aside screen retainer and screws for later assembly. 2. Fasten hood top and side plate screws provided. See Fig. 9. 3. Slide outdoor-air inlet screen assembly into to unit with screen track on hood side plates. While holding screen) in place, fasten screen retainer to hood using screws provided. 4. Replace SEAL filter access panel. STRIP"-,--,q_ See Fig. 7. _ SCREEN RETAINER HOOD TOP _ SEAL STRIP_ _,,,,.,4.,,,,._ HOOD SIDE _ I _) Ull)j HOO D,,,.,..-,--,-""T_ SCREEN HOOD TRACKS _ S,OE 3 3/8" DIVIDER J //_ C06026 OUTDOOR OUTDOOR-AIR HOOD AIR INLET Fig. 11 - Economizer SCREEN Hood Construction UNASSEMBLED 3. Remove the shipping tape holding the economizer rometric relief damper in place. 4. Insert the hood divider between the hood sides. baSee Fig. 11 and 12. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter. 5. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 12. HOOD SIDE TRACKS HOOD FOR AIR ;REEN SIDES AND TOP ASSEMBLED C07504 Fig. 9 - Outdoor-Air Economizer Hood Hood Details i NOTE: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly. 1. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. See Fig. 10. ALUMINUM FILTER BAROMETRIC RELIEF FILTER CLIP SiDE PANEL C06027 Fig. 12 - Economizer 6. Caulk the ends of the joint and the hood top. 7. Replace Filter Installation between the unit top panel the filter access panel. TOP PANEL iNDOOR COIL ACCESS PANEL Step INDOOR COiL PANEL C06025 Fig. 10 - Indoor Coil Access 9 1 Install Flue Hood Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 13. Panel Relocation 10 gas regulator source and unit gas valve unit is operating at high-fire flow rate. connection when The gas supply line can approach the unit in three ways: horizontally from outside the unit (across the roof), thru-curb/under unit basepan (accessory kit required) or through unit basepan (factory-option or accessory kit required). Consult accessory kit installation instructions for details on these installation methods. FactoryFLUE OPENING BLOWER ACCESS PANEL C07081 Fig. 13 - Flue Hood Details Step 10 -- Install Option Thru-Base Connections -- This service connection kit consists of a 1/2-in NPT gas adapter fitting (brass), a 1/2-in electrical bulkhead connector and a 3/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. Gas Piping Installation of the gas piping must be accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances. LOW VOLTAGE CONNECTOR HIGH VOLTAGE CONDUIT CONNECTOR This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories. For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg (996 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. On 48TCFA04-A06 (high-heat) units, the gas pressure at unit gas connection must not be less than 5 in. wg (1245 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13.6 in. wg (3390 Pa) at the unit connection. The gas supply pipe enters the unit at the burner access panel on the front side of the unit, through the long slot at the bottom of the access panel. The gas connection to the unit is made to the 1/2-in. FPT gas inlet port on the unit gas valve EQUIPMENT DAMAGE Failure to follow to equipment. BRASS FITTING FOR 3 TO 6 TON UNITS. STAINLESS STEEL FITTING FOR 7 1/2 TO 12 1/2 TON. C08015 Fig. 14 - Fittings The thru-base gas connector has male and female threads. The male threads protrude above the basepan of the unit; the female threads protrude below the basepan. Check tightness gas piping. of connector lock nuts before connecting Install a 1/2-in NPT street elbow on the thru-base gas fitting. Attach a 1/2-in pipe nipple with minimum length of 16-in (406 mm) (field-supplied) to the street elbow and extend it through the access panel at the gas support bracket. See Fig. 15. HAZARD this caution may result in damage When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve. EMBOSSMENT BRASS FITTING FOR 3-6 TON UNITS C08016 Fig. 15 - Gas Line Piping Install a gas supply line that runs to the unit heating section. Refer to the NFPA 54/NFGC or equivalent code for gas pipe sizing data. Do not use a pipe size smaller than 1/2-in. Size the gas supply line to allow for a maximum pressure drop of 0.5-in wg (124 Pa) between SUPPORT BRACKET for 3 to 6 Ton Units Only Other hardware required to complete the installation of the gas supply line will include a manual shutoff valve, a sediment trap (drip leg) and a ground-joint union. A pressure regulator valve may also be required (to convert gas pressure from pounds to inches of pressure). The manual shutoff valve must be located within 6-ft (1.83 m) 11 of the unit. The union, located in the final leg entering the unit, must be located at least 9-in (230 mm) away from the access panel to permit the panel to be removed for service. If a regulator valve is installed, it must be located a minimum of 4-fl (1220 mm) away from the unit's flue outlet. Some municipal codes require that the manual shutoff valve be located upstream of the sediment trap. See Figures 16 and 17 for typical piping arrangements for gas piping that has been routed through the sidewall of the curb. See Fig. 18 for typical piping arrangement when thru-base is used. Ensure that all piping does not block access to the unit's main control box or limit the required working space in front of the control box. C08018 Fig. 18 - Gas Piping Thru-Base Connections _mm) rain Thru-Curb Adapter When installing the gas supply line, observe local codes pertaining to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA B149.1). In the absence of local building codes, adhere to the following pertinent recommendations: Jnion \ 1. Avoid low spots in long runs of pipe. Grade all pipe 1/4-in. in every 15 fl (7 mm in every 5 m) to prevent traps. Grade all horizontal runs downward to risers. Use risers to connect to heating section and to meter. 2. Protect all segments of piping system against physical and thermal damage. Support all piping with appropriate straps, hangers, etc. Use a minimum of one hanger every 6 fl (1.8 m). For pipe sizes larger than 1/2-in., follow recommendations of national codes. Unit Base Rail Shut Off Valve _/Drip Leg 3. Apply joint compound (pipe dope) sparingly and only to male threads of joint when making pipe connections. Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and/or national codes. If using PTFE (Teflon) tape, ensure the material is Double Density type and is labeled for use on gas lines. Apply tape per manufacturer's instructions. C07469 Fig. 16 - Gas Piping min Burner 4. Pressure-test all gas piping in accordance with local and national plumbing and gas codes before connecting piping to unit. Access Panel Union Thru-Curb Adapter Unit Bas_e Rail / Shut Off Valve Drip Leg C07470 NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union. Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations). Fig. 17 - Gas Piping 12 FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. • Connect gas pipe to unit using a backup wrench to avoid damaging gas controls. • Never purge a gas line into a combustion chamber. • Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. • Use proper length of pipe to avoid stress on gas control manifold. CONDENSATE PAN (SIDE VIEW) ALTERNATE STANDARD SIDE DRAIN DRAIN PLUG BOTTOM C08021 Fig. 20 - Condensate MINIMUM Drain orifice hole is essential Pan (Side View) PITCH NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned proper flame characteristics. DRAIN (FACTORY-INSTALLED) 2" (54) MIN SEE for NOTE TO ROOF DRAIN _'---..ROOF CURB DRAIN PLUG NOTE: Trap should be deep enough to offset maximum difference. A 4" (102) trap is recommended unit static C08022 Fig. 21 - Condensate Drain Piping Details All units" must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at i-in. per 10 f! (25 mm in 3 in) of run. Do not use a pipe size smaller than the unit connection (-%-in.). A93059 Fig. 19 - Orifice Step 11 -- Install External and Line Step 12 -- Make Hole Condensate Electrical Connections Trap ELECTRICAL The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 20. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal Failure to follow injury or death. HAZARD this warning could result in personal Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes. applications. When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a ]/2-in. square socket drive extension. To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a ]/2-in. square socket drive extension) and install it in the side drain connection. The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 21. SHOCK NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise. 13 Field Power control Supply -- If equipped with optional Powered Convenience Outlet: The power source leads to the convenience outlet's transformer primary are not factory connected. Installer must connect these leads according to required operation of the convenience outlet. If an always-energized convenience outlet operation is desired, connect the source leads to the line side of the unit-mounted box. The manual switch handle through an opening in the access factory test leads (see Fig. 22). is accessible panel. Discard the FIRE HAZARD Failure to follow this warning intermittent operation or performance disconnect. (Check with local codes to ensure this method is acceptable in your area.) If a de-energize via unit disconnect switch operation of the convenience outlet is desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit-mounted Do not connect aluminum could result satisfaction. wire between in disconnect switch and 48TC unit. Use only copper wire. (See Fig. 23.) disconnect, connect the source leads to compressor contactor C and indoor fan contactor IFC pressure lugs with unit field power leads. Refer to Fig. the discussion page 15. ELECTRIC DISCONNECT SWITCH 26 for power transformer connections and on connecting the convenience outlet on @ Field power wires are connected to the unit at line-side pressure lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component arrangement) or at factory-installed option non-fused disconnect switch. Max wire size is #2 AWG (copper only). Disconnect Option 9 I C?tFC_ I I I"-- plate .=L=.L= I I a I a a I per I I NEC I Disconnect a per NEC I _-i--7-a 208/230-1-60 (1-ph IFM) (+) =J=-L-J=_ Disconnect -7--T--I-L1 L2 I 575-3-60 Option L3 .... ,@ ,q>o,°2i!i'o, Z } Disconnect factory test leads; discard. C07494 Fig. 22 - Power Wiring Connections NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points on contactor C or optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only. Units with Factory-Installed The factory-installed in a weatherproof Disconnect -- option disconnect enclosure located the disconnect on the unit cabinet. Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size. All field wiring must comply with the NEC and local requirements. LI .... if mounting All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 22 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2 ga AWG per pole. L3 375-3-60 L2 Disconnect -- All units -- 208/230-3-60 460-3-60 Units With Disconnect Switch and Unit When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative C 79 J A93033 Fig. 23 - Disconnect Units Without Factory-Installed (See Fig. 22.) Units Without WIRE ONLY switch under is located the main All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is" to be connected to a 208-v power suppl); the control transformer must be rewired by moving the black wire with the 1/4-in. female spade connector from the 230-v connection and mowng it to the 200-v 1/4-in. male terminal on the primary side of the transformen Refer to unit label diagram for additional information. Field power wires will be connected line-side pressure lugs on the power terminal block or at factory-installed option non-fused disconnect. NOTE: Check all factory and field electrical connections for tightness. Field-supplied wiring shall conform with the limitations of 63°F (33°C) rise. 14 Convenience Outlets- ELECTRICAL Failure to follow injury or death. OPERATION HAZARD this warning could result Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots and align with the gasket; tighten the two screws until snug (do not over-tighten). in personal Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary. Mount the weatherproof cover to the backing plate as shown in Fig. 25. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching. COVER - WHILE-IN-USE WEATHERPROOF RECEPTACLE NOTINCLUDED Two types of convenience outlets are offered on 48TC models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 24. Pwd-CO Transformer Convenience Outlet GFCI S BASE PLATE FOR GFCIRECEPTACLE Pwd-CO Fuse C09022 Fig. 25 - Weatherproof '_ Control Cover Installation Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle. Box Access Panel C08128 Fig. 24 - Convenience Installing Weatherproof Outlet Location Cover - A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate. The weatherproof cover kit is shipped in the unit's control box. The kit includes the hinged cover, a backing plate and gasket. DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET. Remove the blank cover discard the blank cover. plate at the convenience outlet; Unit-powered type: A unit-mounted transformer is factory-installed to stepdown the main power supply voltage to the unit to l15-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit's control box access panel. See Fig. 24. The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit-mounted non-fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 26. 15 S?HE aTIfl ..,_1 E IEi/CE if the GFCI receptacle does not trip as required. RESET button to clear the tripped condition. C,'TLET 460,/ i_ D T_N4 ' U Gi!_ Factory- .... E".M3 the Connections -- BLL RE{}¸ _EL ........ LOCAL (109E 7GR_ I..... _ SECC, ND;R} Option Thru-Base Press _ED 'EL C0N_ECT _>E[_ G:¢!_ I BLJ 120V _, {}i), 'x£ ,} o, ;o ;q2#U 6FI S_/ITCH FSE Check tightness of connector lock nuts before connecting electrical conduits. CO ,IbG_ 'EL LK ,,HT C08283 UNIT CONNECT VOLTAGE AS PRIMARY CONNECTIONS TRANSFORMER TERMINALS 208, 230 240 LI: RED +YEL L2: BLU + GRA H1 + H3 H2 + H4 460 480 L1: RED Splice BLU + YEL L2: GRA H1 H2 + H3 H4 575 600 L1: RED L2: GRA Field-supplied and field-installed liquid tight conduit connectors and conduit may be attached to the connectors on the basepan. Pull correctly rated high voltage and low voltage through appropriate conduits. Connect the power conduit to the internal disconnect (if unit is so equipped) or to the external disconnect (through unit side panel). A hole must be field cut in the main control box bottom on the left side so the 24-v control connections can be made. Connect the control power conduit to the unit control box at this hole. H1 H2 Fig. 26 - Powered Convenience This service connection kit consists of a 1/2-in NPT gas adapter fitting (brass), a 1/2-in electrical bulkhead connector and a 3/4-in electrical bulkhead connector, all factory-installed in the embossed (raised) section of the unit basepan in the condenser section. The 3/4-in bulkhead connector enables the low-voltage control wires to pass through the basepan. The 1/2-in electrical bulkhead connector allows the high-voltage power wires to pass through the basepan. See Fig. 21. Units without Thru-Base 1. Install power wiring ings. Install conduit Outlet Wiring Connections -conduit through side panel openbetween disconnect and control box. Fuse on power type: The factory fuse is a Bussman "Fusetron" T-15, non-renewable screw-in (Edison base) type plug fuse. Convenience Outlet use : 15 Amps 2 to 3 Hours Maximum Continuous use : 8 Amps 24/7 I 50HJ542739 lines to terminal connections as shown Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 9. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 9, Note 2 to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. Utilization Maximum Intermittent 2. Install power in Fig. 22. 13.0 Field Control Wiring -- A9225 Fig. 27 - Convenience Outlet Utilization Notice Label Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps. Convenience outlet usage rating: Continuous usage: 8 amps maximum Intermittent usage: up to 15 amps maximum up to 2 hours maximum for Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing The 48TC unit requires an external temperature control device. This device can be a thermostat (field-supplied) or a PremierLink controller (available as factory-installed option or as field-installed accessory, for use on a Carrier Comfort Network or as a stand alone control) or the RTU-MP Controller for Building Management Systems using non-CCN protocols (RTU-MP is available as a factory-installed option only). Thermostat i Install a Carrier-approved accessory thermostat according to installation instructions included with the accessory. For complete economizer function, select a two-stage cooling thermostat. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions. 16 RACEWAY If the thermostat contains a logic circuit requiring 24-v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24-v source (no "C" connection required), use a thermostat cable or equivalent with minimum of six leads. Check the thermostat installation instructions for additional features which might require additional conductors in the cable. Using unit-mounted convenience outlets: unit-mounded convenience outlet circuits Units with will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets. For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35°C (95°F) minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated wire [35°C (95°F) minimum]. For over 75 ft. (23 m), use no. 14 AWG insulated wire [35°C (95°F) minimum]. All wire sizes larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Central Terminal Board Typical Thermostat Connections © @ @ G (Note 1) (Note 2) © ® FwSl % % Fq HOLE IN END PANEL (HIDDEN) C08027 Fig. 29 - Field Control Wiring Raceway Heat Anticipator Settings -Set heat anticipator settings at 0.14 amp for the first stage and 0.14 amp for second-stage heating, when available. Smoke Detectors -Smoke detectors are available as factory-installed options on 48TC models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only. All components necessary for operation are factory-provided and mounted. The unit is factory-configured for immediate smoke detector shutdown operation; additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements. T H E R M O S T A T Units equipped with factory-optional Return Air smoke detectors require a relocation of the sensor module at unit installation. See "Completing Installation of Return Air Smoke Sensor:" on page 19 for details. System Note 1: Typical multi4unction marking. Follow manufacturer's instructions to select Y2. Note 2: Y2 to Y2 connection required on single-stage integrated economizer function is desired. mmm configuration cooling units when Field Wiring C08069 Fig. 28 - Low-Voltage Connections Unit without thru-base connection kit -Pass the thermostat control wires through the hole provided in the corner post; then feed the wires through the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper-left corner of the Controls Connection Board. See Fig. 29. NOTE: If thru-the-bottom connections accessory is used, refer to the accessory installation instructions for information on routing power and control wiring. The smoke detector system consists of a four-wire controller and one or two sensors. Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building. It is not to be used as a life saving device. Controller The controller (see Fig. 30) includes a controller housing, a printed circuit board, and a clear plastic cover. The controller can be connected to one or two compatible duct smoke sensors. The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals. The controller has three LEDs (for Power, Trouble and Alarm) and a manual test/reset button (on the cover face). 17 For installations using two detector does not differentiate alarm or trouble condition. sensors, which the duct smoke sensor signals an Duct smoke sensor controller Conduit _ (supplied nuts by installer) Conduitsupport plate / Exhausttube ;_Terminalblockcover Controller housing Covergasket F(ordefing option) and electronics j Exhaustgasket F Conduit couplings (supplied by installer) _ J Controller cover See Detail Fastener Sensorhousing and electronics t A \\\\\\\ J (2x) Intake / gasket \\ \ \ \ \ \ Cover \\ \ // Trouble \\\ Plug / gasket (ordering option) \\\\\ \_\\ \\ ff Sensor cover C08208 Fig. 30 - Controller Assembly Magnetic I_l_ ..... Sensor The sensor (see Fig. 31) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The sampling tube (when used) and exhaust tube are attached during installation. The sampling tube varies in length depending on the size of the rooftop unit. The clear plastic cover permits visual inspections without having to disassemble the sensor. The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics. Each sensor includes a harness with an RJ45 terminal for connecting to the controller. Each sensor has four LEDs (for Power, Trouble, Alarm and Dirty) and a manual test/reset button (on the left-side of the housing). Air is introduced to the duct smoke detector sensor's sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation ....... JjL ...... T rou bl e D irty C08209 Fig. 31 - Smoke Smoke Detector Detector Sensor Locations Supply Air -- The Supply Air smoke detector sensor is located to the left of the unit's indoor (supply) fan. See Fig. 32. Access is through the fan access panel. There is no sampling tube used at this location. The sampling tube inlet extends through the side plate of the fan housing (into a high pressure area). The controller is located on a bracket to the right of the return filter, accessed through the lift-off filter panel. system through a (shorter) exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing chamber, the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers, change over air handling systems, notify the fire alarm control panel, etc. The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms. A rapid change in environmental conditions, such as smoke from a fire, causes the sensor to signal an alarm state but dust and debris accumulated over time does not. ,/ Smoke Detector Sensor C08245 Fig. 32 - Typical 18 Supply Air Smoke Location Detector Sensor Return Air without Economizer -- The sampling tube is located across the return air opening on the unit basepan. See Fig. 33. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See "Completing Installation of Return Air Smoke Sensor:" for details.) Return Air Detector _ Completing Sensor: Installation of Return Air Smoke 1. Unscrew the two screws holding the Return Air Sensor detector plate. See Fig. 35. Save the screws. 2. Remove the Return Air Sensor and its detector 3. Rotate the detector plate so the sensor wards and the sampling tube connection tom. See Fig. 36. plate. is facing outis on the bot- 4. Screw the sensor and detector plate into its operating position using screws from Step 1. Make sure the sampling tube connection is on the bottom and the exhaust tube is on the top. See Fig. 36. module (shipping position shown)* 5. Connect the flexible tube on the sampling sampling tube on the basepan. inlet to the Exhaust Return Air Detector *RA detector must be moved from shipping Sampling Tube position to operating Tubes Sample Tube position by installer C08126 C07307 Fig. 33 - Typical Return Air Detector Location Fig. 35 - Return Air Detector Fig. 36 - Return Air Sensor Shipping Position Return Air with Economizer -- The sampling tube is inserted through the side plates of the economizer housing, placing it across the return air opening on the unit basepan. See Fig. 34. The holes in the sampling tube face downward, into the return air stream. The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location. (This sensor is shipped in a flat-mounting location. Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected. See the following installation procedure.) C08127 Refer to Catalog No. on additional control features of these coordination. including C08129 Fig. 34 - Return Air Sampling Position Additional Application Data -HKRNKA-1XA for discussions Return Air Sampling Tube _/< Operating Tube Location 19 smoke detectors multiple unit PremierLink (Factory-Option) -- o HVAC SENSOR INPUTS c SPACE TEMP _._ TSTATC_ SET POINT ._ 8tU SUPPLY AIR TEMP -__ OUTDOOR ] Gm ,_ _¢ Am I ! C 2;_1oi TEMP _--_ INDOOR AIR QUALITY OUTDOOR s_r _N t& t_m Paff Nt_be_ 330SPREMLK _, .... -- PremcerL_nk -_ AIR QUALITY .m__ [ DUAL MODE SENSOR!STAT COMP SAFETY (Y1) 7 FIRE SHUTDOWN (Y2) /_ _ 8_mu {Z_°AJ SUPPLY FAN STATUS (Wl) NOT USED (W2) _'_ ENTHALPY STATUS (ENTH) lII=, .....- .............. °tt ............................. ..I \ / CCN/LEN PORT f k_Jl,_0'l| t / NAVIGATOR PORT 'I 4-20MA ECONOMIZER 'I &° '1 'i '1 ",.. INDOOR FAN MOTOR COMPR 1&2 HEAT LOW/HIGH EXHAUST RVS VALVE OUTPUTS C08199 Fig. 37 - PremierLink The PremierLink controller (see Fig. 37) is compatible with Carrier Comfort Network ® (CCN) devices. This control is designed to allow users the access and ability to change factory-defined settings, thus expanding the function of the standard unit control board. CCN service access tools include System Pilot (TM), Touch Pilot (TM) and Service Tool. (Standard tier display tools Navigator and Scrolling Marquee are not suitable for use with latest PremierLink controller (Version 2.x).) TM Controller The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 38. The PremierLink control is factory-mounted in the 48TC unit's main control box to the left of the Central Terminal Board (CTB). Factory wiring is completed through harnesses connected to the CTB thermostat. Field connections are made at a 16-pole terminal block (TB1) located on the bottom shelf of the unit control box in front of the PremierLink controller. The factory-installed PremierLink control includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er 2 package. \ m TM The PremierLink controller requires the use of a Carrier electronic thermostat or a CCN connection for time broadcast to initiate its internal timeclock. This is necessary for broadcast (occupied/unoccupied). of time of day RETURN AIR SENSOR _ SUPPLYAIR functions NOTE: PremierLink controller is shipped in Sensor mode. To be used with a thermostat, the PremierLink controller must be configured to Thermostat mode. Refer to PremierLink Configuration instructions for Operating Mode. Supply Air Temperature (SAT) Sensor -On FlOP-equipped 48TC unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor. C08200 Fig. 38 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units NOTE: Refer to Form 33CS-58SI for complete PremierLink configuration, operating sequences and troubleshooting information. Have a copy of this manual available at unit start-up. NOTE: airstream devices. with any 2O The sensor must be mounted in the discharge downstream of the cooling coil and any heating Be sure the probe tip does not come in contact of the unit's heater surfaces. C09300 Fig. 39 - PremierLink Wiring 21 Schematic Outdoor Air Temperature (OAT) Sensor I The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. EconoMi$er2 I The PremierLink control is used Connect T-55 - See connections. Connect terminals Fig. 40 for typical T-55 the T-55 SEN terminals internal to TB1 1 and 3 (see Fig. 41). TB1 with PL EconoMiSer2 (option or accessory) for outdoor air management. The damper position is controlled directly by the PremierLink control; EconoMi$er2 has no internal logic device. C08212 Fig. 41 - PremierLink Outdoor air management functions field-installation of these accessory can be enhanced control devices: T-55 Sensor with Space CO: sensor Connect T-56 - See Fig. 42 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to TB1 Outdoor terminals Enthalpy control (outdoor air or differential sensors) air CO: sensor Refer to Table 2 for accessory 1, 3 and 5 (see Fig. 43). part numbers. Field connections I Field connections for accessory sensor and input devices are made at the 16-pole terminal block (TB1) located on the control box bottom shelf in front of the PremierLink control (See Fig. 39). Some input devices also require a 24-vac signal source; connect at CTB terminal R at "THERMOSTAT" connection strip for this signal source. See connections figures on following pages for field connection locations (and for continued connections at the PremierLink board inputs). © CCN COM SENSOR Table 3 provides a summary of field connections for units equipped with Space Sensor. Table 4 provides a summary of field connections for units equipped with Space Thermostat. WIRING JUMPER TERM INALS AS SHOWN © Space Sensors The PremierLink controller is factory-shipped configured for Space Sensor Mode. A Carrier T-55 or T-56 space sensor must be used. T-55 space temperature sensor provides a signal of space temperature to the PremierLink control. T-56 provides same space temperature signal plus it allows for adjustment of space temperature setpoints from the face of the sensor by the occupants. C08202 Fig. 42 - T-56 Internal Connections TB1PL D TB1 PL % !_l'---Jumper s_ © D _, _ _W_HL(Q_N_)L', \ .\ 5,,_ 0Ep(+)j. BL@) t] _ C08213 CCN COM Fig. 43 - PremierLink Wl Connect \ / BRN (GND& [ ', SENSOR WIRING A 7-wire thermostat connection connection strip for these. Connect the thermostat's Y1, Y2, W1, W2 and G terminals to PremierLink TB1 as shown in Fig. 44. 4:b, © C08201 Space Temperature I Sensor requires a 24-v power source and a common connection. Use the R and C terminals on the CTB's THERMOSTAT @ Fig. 40 - T-55 Thermostat T-56 Sensor Wiring If the 48TC unit is equipped with factory-installed smoke detector(s), disconnect the factory BLU lead at TB1-6 (Y2) before connecting the thermostat. Identify the BLU lead originating at CTB-DDC-1; disconnect at TB1-6 and tape off. Confirm that the second BLU lead at TB1-6 remains connected to PremierLink J4-8. 22 SPACE THERMOSTAT CTB THERMOSTAT D TB1 42D (Z) PL E] % CTB THERMOSTAT C08119 Fig. 44 - Space Thermostat Table 2 - PremierLink Connections Sensor Usage APPLICATION OUTDOOR AIR TEMPERATURE SENSOR RETURN AIR TEMPERATURE SENSOR Differential Dry Bulb Temperature with PremierLink (PremierLink requires 4- 20 mA Actuator) Included CRTEMPSNOO1AO0 Required 33ZCT55SPT or equivalent Single Enthalpy with PremierLink (PremierLink requires 4- 20mA Actuator) Included Not Used Requires 33CSENTHSW Differential Enthalpy with PremierLink (PremierLink requires 4- 20mA Actuator) Included Not Used Requires 33CSENTHSW or equivalent OUTDOOR AIR ENTHALPY SENSOR NOTES: CO 2 Sensors (Optional): 33ZCSENC02 Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor. 33ZCASPC02 Aspirator box used for duct-mounted CO 2 room sensor. 33ZCT55C02 Space temperature and CO2 room sensor with override. 33ZCT56C02 Space temperature and CO2 room sensor with override and setpoint. 23 RETURN AIR ENTHALPY SENSOR Requires 33CSENTSEN or equivalent Table 3 - Space Mode FIELD CONNECTION INPUT SIGNAL 1 T55- SEN/T56- SEN Analog (1Okthermistor) 2 RMTOCC Discrete, 24VAC 3 T55- SEN/T56- SEN Analog (1Okthermistor) 4 CMPSAFE Discrete, 24VAC 5 T56- SET Analog (1Okthermistor) 6 FSD Discrete, 24VAC 7 LOOP- PWR Analog, 24VDC 8 SPS Discrete, 24VAC TB1 TERMINAL 9 IAQ-SEN 10 FILTER 11 IAQ- COM/OAQ- Analog, 4-20mA Discrete, 24VAC COM/RH- COM Analog, 4-20mA 12 CCN + (RED) Digital,, 5VDC 13 OAQ-SEN/RH-SEN Analog, 4-20mA 14 CCN Gnd (WriT) 15 AUX OUT(Power Exhaust) 16 CCN - (BLK) LEGEND: T55 T56 CCN CMPSAFE Sensor - FSD - Space Temperature Sensor Carrier Comfort Network (communication IAQ - Indoor Air Quality (C02) OAQ- Outdoor Air Quality (C02) bus) Safety RH Dirty Filter Switch - SFS - Table 4 - Thermostat TB1 TERMINAL 24VAC Digital, 5VDC Space Temperature Sensor Compressor FILTER Digital, 5VDC (Output)Discrete Fire Shutdown Relative Humidity Supply Fan Status Mode FIELD CONNECTION 1 RAT SEN 2 G 3 RAT SEN 4 Y1 INPUT Analog (10k thermistor) Discrete, Analog SIGNAL 24VAC (1Ok thermistor) Discrete, 24VAC 5 6 Y2 7 LOOP- 8 Wl 9 IAQ- COM/OAQ- 13 15 COM/RH-COM OAQ - SEN/RH Analog, AUX OUT (Power CCN - - SEN Analog, - G Carrier Comfort Network (communication Thermostat Fan 24VAC 4- 20mA 4- 20mA Digital, 5VDC Exhaust) (Output) (BLK) Discrete Digital, 5VDC LEGEND: CCN 24VAC 4-20mA Digital, 5VDC CCN Gnd (WriT) 16 24VDC Discrete, CCN + (RED) 14 24VAC Analog, Analog, W2 12 Discrete, Discrete, IAQ-SEN 10 11 PWR bus) RH - Relative Humidity Wl - Thermostat Heat Stage 1 Heat Stage 2 IAQ - Indoor Air Quality (C02) W2 - Thermostat OAQ - Outdoor Air Quality (C02) Y1 - Thermostat Cool Stage 1 RAT - Return Air Temperature Y2 - Thermostat Cool Stage 2 24 24VAC If the 48TC unit has an economizer system and free-cooling operation is required, a sensor representing Return Air Temperature must also be connected (field-supplied and installed). This sensor may be a T-55 Space Sensor (see Fig. 40) installed in the space or in the return duct, or it may be sensor PNO 33ZCSENSAT, installed in the return duct. Connect this sensor to TBI-1 and TB1-3 Return Air Enthalpy Sensor I Mount the return-air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy controller (33CSENTHSW). See Fig. 46. | per Fig. 41. 24V - 4-20 Main Configure the unit for Thermostat Mode I Connect to the CCN bus using a CCN service tool and navigate to PremierLink Configuration screen for Operating Mode. Default setting is Sensor Mode (value 1). Change the value to 0 to reconfigure the controller for Thermostat Mode. + VDC Out When the PremierLink is configured for Thermostat Mode, these functions are not available: Fire Shutdown (FSD), Remote Occupied (RMTOCC), Compressor Safety (CMPSAFE), Supply Fan Status (SFS), and Filter Pressure Switch (FILTER). ? RED --'_ECONO GND T| BLK .JMOTOR LOW 1- GRA _ + 24-36 VDC In - 4-20 Main Out C09027 Fig. 46 - Outside Economizer Outdoor controls i Air Enthalpy Control (PNO 33CSENTHSW) - The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 45.) To wire following: GRA_ m '_ECONO ,JMOTOR E__ ECON CTB Factory Wiring Harness return air enthalpy Air Enthalpy sensor, Sensor perform the 1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller. 2. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (+) terminal on the enthalpy controller. Connect the BLK wire to (-) spade connector on the return air enthalpy sensor and the (-) terminal on the enthalpy controller. Enthalpy Switch = RED BLK the and Return Wiring Indoor Air Quality (CO2 sensor) I The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air. C09026 Fig. 45 - Enthalpy Switch (33CSENTHSW) Connections Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled "ESL" to the terminal labeled "LOW". See Fig. 45. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND). The outdoor enthalpy enthalpy controller. changeover setpoint is set The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 47 for typical CO2 sensor wiring schematic. at the Differential Enthalpy Control I Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor. 25 Refer to Form 33CS-58SI, Start-up, and Configuration configuration information 0 PremierLink Instructions, Installation, for detailed Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) -- The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 49. The outdoor air CO2 sensor must be located in the economizer outside air hood. Q0q0VDC ® SIG COM ® 4-20mA NC '} ALARM COM_, RELAY NO J CONTACTS H _1-- 41/4" _4_---2 J31 O 33/4" ...................... t_ ...... --_b,,] 87654321 3.5" ........ --,-- J4 OC O © C08635 Fig. 47 - Indoor/Outdoor Air Quality (33ZCSENCO2) - Typical Wiring (CO2) @ @ 61t2" Sensor Diagram O 7 u @ To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact. OO @ COVER REMOVED SIDE VIEW C07135 Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream. Wiring the Indoor Air Quality Sensor -- For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 47. Connect the 4-20 mA terminal to terminal TB1-9 and connect the SIG COM terminal to terminal TBI-ll. Fig. 49 - Outdoor Air Quality Sensor Cover Wiring the Outdoor Air CO2 Sensor -- A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 47. Connect the 4 to 20 mA terminal to the TB1-13 terminal of the 48TC. Connect the SIG COM terminal to the TBI-ll terminal of the 48TC. See Fig. 50. OAQ Sensor/RH Sensor TB1 PL TB1 @ See Fig. 48. Fq 24 VAC C08275 IAQ Sensor TB1 PL TB1 [] 24 VAC C08636 Fig. 48 - Indoor CO2 Sensor Connections (33ZCSENCO2) Fig. 50 - Outdoor CO 2 Sensor Connections Smoke Detector/Fire Shutdown (FSD) -- This function is available only when PremierLink is configured for (Space) Sensor Mode. The unit is factory-wired for PremierLink FSD operation when PremierLink is factory-installed. 26 Fan (Pressure) Switch (NO, close on rise in pressure) On 48TC units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit's CTB input. The FSD function is initiated via the smoke detector's Alarm NO contact set. The PremierLink communicates the smoke detector's CCN building control. See Fig. wiring schematic. tripped 39, the CTB Thermostat o status to the PremierLink L@o- control can monitor []TB1 --0 C08118 Fig. 52 - PremierLink Wiring Fan Pressure Switch Connection Filter Status Switch I This function is available only when PremierLink is configured for (Space) Sensor Mode. PremierLink [] return filter status in two ways: By monitoring a field-supplied/installed pressure switch or via supply fan runtime hours. filter Using switch input: Install the dirty according to switch manufacturer's measure pressure drop across the Connect one side of the switch's NO THERMOSTAT-R terminal. Connect filter pressure switch instructions, to unit's return filters. contact set to CTB's the other side of the NO contact set to TBI-10. at the switch. See Fig. 51. for Dirty Filter Setpoint is set Remote Occupied Switch I The PremierLink control permits a remote timeclock to override the control's on-board occupancy schedule and place the unit into Occupied mode. This function may also provide a "Door Switch" time delay function that will terminate cooling and heating functions after a 2-20 minute delay. Connect one side of the NO contact set on the timeclock to CTB's THERMOSTAT-R terminal. Connect the other side of the timeclock contact to the unit's TB1-2 terminal. Remote Occupied Filter Switch (NO, close on rising pressure (high drop)) I CTB Thermostat CTB Thermostat c----o Time Clock T [] TB1 _ 0 PL @ C08214 --o TB1 PL D 427 Fig. 53 - PremierLink Refer C08216 Fig. 51 - PremierLink When the filter switch's Filter Switch NO contact pressure drop increases (indicating input signal to PremierLink causes read "DIRTY". Connection set closes as filter dirt-laden filters), the the filter status point to 33CS-58SI configuring the timer function. PremierLink Remote for additional control Occupied information for Door Install the differential pressure switch in the supply fan section according to switch manufacturer's instructions. Arrange the switch contact to be open on no flow and to close as pressure rises indicating fan operation. Connect one side of the switch's NO contact set to CTB's THERMOSTAT-R terminal. Connect the other side of the for Supply Switch Power Exhaust 33CS-58SI for Configuration Supply Fan Status Switch I The PremierLink control can monitor supply fan operation through a field-supplied/installed differential pressure switch. This sequence will prevent (or interrupt) operation of unit cooling, heating and economizer functions until the pressure switch contacts are closed indicating proper supply fan operation. on Power Exhaust (output) - Connect the accessory Power Exhaust contactor coils(s) per Fig. 54. TB1 Using Filter Timer Hours: Refer to Form instructions on using the PremierLink screens and on unit alarm sequence. NO contact set to TB1-8. Setpoint is set at the switch. See Fig. 52. to Form Wiring OTB D THERMOSTAT _TAN L PL GRA D C08120 Fig. 54 - PremierLink Power Connection CCN Communication Bus I Exhaust The PremierLink Output controller connects to the bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins, and likewise, positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the 3-pin plug. Fan Status 27 At any baud (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 It, with no more than 60 total devices on any 1000-ft section. Optically isolated RS-485 repeaters are required every 1000 ft. NOTE: Carrier device COMMUNICATION default BUS Connecting NOTE: When connecting the communication bus cable, a color code system for the entire network is recommended to simplify installation and checkout. See Table 6 for the recommended color code. is 9600 band. WIRE Table SPECIFICATIONS 6 - Color Code Recommendations -- The CCN Communication Bus wiring is field-supplied and field-installed. It consists of shielded 3-conductor cable with drain (ground) wire. The cable selected must be identical to the CCN Communication Bus wire used for the entire network. See Table 5 for recommended CCN bus: SIGNAL TYPE CCN BUS WIRE COLOR CCN PLUG PIN NUMBER + Red 1 Ground White 2 - Black 3 cable. Table 5 - Recommended MANUFACTURER Cables CABLE Alpha Connect TBI-12 (typically the CCN terminal. PART NO. 2413 or 5463 American A22503 Belden 8772 Columbia 02525 the CCN (+) lead (typically RED) to the unit's terminal. Connect the CCN (ground) lead WHT) to the unit's TBI-14 terminal. Connect (-) lead (typically BLK) to the unit's TBI-16 See Fig. 55. CCN Bus TB1 NOTE: Conductors and drain wire must be at least + (RED) 20 AWG, stranded, and tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of -20°C to 60°C is required. Do not run communication wire in the same conduit as or next to any AC voltage wiring. PL "D TB1 GND (WHT) '[l"_m TB1 C08276 Fig. 55 - PremierLink The communication bus shields must be tied together at each system element. If the communication bus is entirely within one building, the resulting continuous shield must be connected to ground at only one single point. If the communication bus cable exits from one building and enters another building, the shields must be connected to the grounds at a lightning suppressor in each building (one point only). 28 CCN Bus Connections RTU-MP control system -- The RTU-MP control is factory-mounted in the 48TC unit's main control box, to the left of the CTB. See The RTU-MP controller, see Fig. 56, provides expanded stand-alone operation of the HVAC system plus connection and control through communication with several Building Automation Systems (BAS) through popular third-party network systems. The available network systems are BACnet MP/TR Modbus and Johnson J2. Communication with LonWorks is also Fig. 57. Factory wiring is completed through harnesses connected to the CTB. Field connections for RTU-MP sensors will be made at the Phoenix connectors on the RTU-MP board. The factory-installed RTU-MP control includes the supply-air temperature (SAT) sensor. The outdoor air temperature (OAT) sensor is included in the FIOP/accessory EconoMi$er2 package. possible by adding an accessory interface card to the RTU-MP. Selection of the communication protocol and baud rate are made at on-board DIP switches. J4 Refer to Table 7, RTU-MP Controller Inputs and Outputs for locations of all connections to the RTU-MP board. J1 Board Power J2 o> "- (AO-I) 0-10VDC J3 Iv = B or_ = B J5 DO_ --_J (H) (Humidistat) DO-7 (Spare) DO=8 (PE) Power Exhaust) Jll J14 Protocol Selector *Remove Input j0 both for 0-SV InpuL11 (T_ (T-55 Accy) BACnet Accy) or Net Comm C0712g Fig. 56 - RTU-MP ] Multi-Protocol Control Board + RTU-MP FIOP + DDC + I_c_ss_S-_ : TERMINAL BOARD I . + UNIT 0_L¥ C09299 Fig. 57 - 48TC Control Box Component 29 Locations illl iii C09301 Fig. 58 - RTU-MP System Control Wiring Diagram 3O Table 7 - RTU-MP Controller Inputs and Outputs POINT NAME BACnet OBJECT NAME Sensor sptsens TYPE OF I/O CONNECTION NUMBERS PIN INPUTS Space Temperature Supply Air Temperature Local Outside Air Temperature Space Temperature Indoor Air Quality Outdoor Safety Offset Sensor Pot Air Quality Chain Feedback Compressor AI (10K Thermistor) J20-1,2 AI (10K Thermistor) J2-1,2 oatsens AI (10K Thermistor) J2-3, sptopot AI (lOOK Potentiometer) sat iaq AI (4-20 ma) J4-2, 3 oaq AI (4-20 ma) J4-5, 6 safety Safety 4 J20-3 DI (24 VAC) J1-9 compstat DI (24 VAC) J1-2 Fire Shutdown firedown DI (24 VAC) J1 - 10 Enthatpy enthatpy DI (24 VAC) J2-6, 7 DI (24 VAC) J5-7, 8 Switch Humidistat Input Status humstat CONFIGURABLE Space Relative Humidity Outside Air Relative Supply Fan Status Humidity Filter Status Remote Occupancy Input INPUTS* sprh AI (4-20 ma) oarh AI (4-20 ma) fanstat DI (24 VAC) filtstat DI (24 VAC) remocc J4-2,3 or J4-5,6 J5-1,2 or J5-3,4 J5 5,6 or J5-7,8 or DI (24 VAC) OUTPUTS Economizer Supply Commanded Position Fan Relay State econocmd 4-20ma sf J2-5 DO Relay (24VAC, 1A) J1-4 Compressor 1 Relay State comp_l DO Relay (24VAC, 1A) J1-8 Compressor 2 Relay State comp_2 DO Relay (24VAC, 1A) J1-7 Heat Stage 1 Relay State heat_l DO Relay (24VAC, 1A) J1-6 Heat Stage 2 Relay State heat_2 DO Relay (24VAC, 1A) J1-5 aux_2 DO Relay (24VAC, 1A) DO Relay 1A) Power Exhaust Dehumidification Relay State Relay State humizer (24VAC, J11-3 J11-7, 8 LEGEND AI Analog Input AO Analog Output DI Discrete Input DO Discrete Output * These inputs (if installed) take the place of the default input on the specific channel according Parallel pins J5-1 = J2-6, J5-3 = J1-10, J5-5 = J1-2 are used for field-installation. The RTU-MP controller space sensor. A standard the RTU-MP system. requires thermostat the use of a Carrier cannot be used with Supply Air Temperature (SAT) Sensor On FIOP-equipped 48TC unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor. The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct. Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 38. Outdoor Air Temperature (OAT) Sensor - The OAT is factory-mounted in the EconoMi$er2 (FIOP or to schematic. accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. EconoMi$er2 The RTU-MP control is used with EconoMiSer2 (option or accessory) for outdoor air management. The damper position is controlled directly by the RTU-MP control; EconoMi$er2 has no internal logic device. Outdoor air management functions field-installation of these accessory Enthalpy control (outdoor can be enhanced control devices: air or differential with sensors) Space CO2 sensor Outdoor air CO2 sensor Field Connections Field connections for accessory sensors and input devices are made the RTU-MR at plugs J1, J2, J4, J5, Jll and J20. All field control wiring that connects to the RTU-MP must be routed through the raceway built into the corner post as shown in Fig. 29. 31 8The raceway provides the UL required clearance between high- and low-voltage wiring. Pass the control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU-MR Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board. Space Temperature terminal (BRN) to J20-2. Connect the SET terminal (STO or BLK) to J20-3. BRN (COM) (SPT) Sensors A field-supplied Carrier space temperature sensor is required with the RTU-MP to monitor space temperature. There are 3 sensors available for this application: • 33ZCT55SPT, button space temperature • 33ZCT56SPT, space temperature button and setpoint • 33ZCT59SPT, (liquid setpoint crystal I I I I I I SET SEN OPB COM- iooo / screen, I I J button, I i sensor with LCD override PWR+ ooo sensor with override ........... space temperature SENSOR WIRING BLU (SPT) sensor with override POWER WIRING 24 VAC I and NOTE: Must use a separate isolated transformer. adjustment C07132 Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and setpoint adjustment connections. If the setpoint adjustment (slidebar) is not required, then an unshielded, 18 or 20 gauge, two-conductor, twisted pair cable may be used. Connect T-55 - See Fig. 40 for typical connections. Connect the T-55 SEN RTU-MP OR adjustment display) BLK (STO) I I J20-1 and J20-2. T-55 internal terminals to See Fig. 59. C08460 Fig. 59 - RTU-MP T-55 Sensor Connections Connect T-56 See Fig. 42 for T-56 internal connections. Install a jumper between SEN and SET terminals as illustrated. Connect T-56 terminals to RTU-MP J20-1, J20-2 and J20-3 per Fig. 60. Fig. 61 - Space Economizer Outdoor Temperature Sensor (33ZCT59SPT) Typical Wiring controls -- Air Enthalpy Control (PNO 33CSENTHSW) - The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 45.) Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled "ESL" to the terminal labeled "LOW". See Fig. 45. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND). The outdoor enthalpy enthalpy controller. changeover setpoint is set at the Differential Enthalpy Control -- Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor. "i,_---Jumper Return Air Enthalpy Sensor -- Mount the return-air enthalpy sensor (33CSENTSEN) in the return-air section of the economizer. The return air sensor is wired to the enthalpy C08461 Fig. 60 - RTU-MP Connect T-59 - The separate, isolated power for internal connections terminal (BLU) T-56 Sensor Connections To wire following: J20-1. Connect the the (33CSENTHSW). return air enthalpy See Fig. 46. sensor, perform the 1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller. T-59 space sensor requires a supply of 24 VAC. See Fig. 61 at the T-59. Connect the SEN to RTU-MP controller 2. Connect the field-supplied RED wire to (+) spade connector on the return air enthalpy sensor and the COM 32 (+) terminal on the enthalpy controller. Connect the BLK wire to (-) spade connector on the return air enthalpy sensor and the (-) terminal on the enthalpy controller. Indoor Air Quality (CO 2 sensor) -- The indoor air quality sensor accessory monitors space carbon dioxide (CO2) levels. This information is used to monitor IAQ levels. Several types of sensors are available, for wall mounting in the space or in return duct, with and without LCD display, and in combination with space temperature sensors. Sensors use infrared technology to measure the levels of CO2 present in the space air. The CO2 sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20. Refer to the instructions supplied with the CO2 sensor for electrical requirements and terminal locations. See Fig. 47 for typical CO2 sensor wiring schematic. with an outdoor cover. See Fig. 49. The outdoor air CO2 sensor must be located in the economizer outside air hood. Wiring the Outdoor Air CO2 Sensor -- A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 47. Connect the 4 to 20 mA terminal to RTU-MP J4-5. Connect the SIG COM terminal to RTU-MP J4-6. OAQ Sensor/Fill Sensor To accurately monitor the quality of the air in the conditioned air space, locate the sensor near a return-air grille (if present) so it senses the concentration of CO2 leaving the space. The sensor should be mounted in a location to avoid direct breath contact. Do not mount the IAQ sensor in drafty areas such as near supply ducts, open windows, fans, or over heat sources. Allow at least 3 ft (0.9 m) between the sensor and any corner. Avoid mounting the sensor where it is influenced by the supply air; the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream. Wiring the Indoor Air Quality Sensor -- 24 VAC C08463 Fig. 63 - RTU-MP / Outdoor CO 2 Sensor (33ZCSENCO2) Connections On 48TC units equipped with factory-installed Smoke Detector(s), the smoke detector controller implements the unit shutdown through its NC contact set connected to the unit's CTB input. The FSD function is initiated via the smoke detector's Alarm NO contact set. The RTU-MP controller communicates the smoke detector's status to the BAS building control. See Fig. RTU-MP System Control wiring schematic. tripped 58, the For each sensor, use two 2-conductor 18 AWG (American Wire Gage) twisted-pair cables (unshielded) to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals. The Fire Shutdown Switch configuration, MENU _Config-_Inputs-+input 5, identifies the normally open status of this input when there is no fire alarm. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 47. Connect the 4-20 mA terminal to RTU-MP J4-2 and connect the SIG COM terminal to RTU-MP J4-3. See Fig. 62. Connecting IAQ Sensor 24 VAC C08462 Fig. 62 - RTU-MP / Indoor CO 2 Sensor (33ZCSENCO2) Connections Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) -- The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged Filter Discrete Inputs Status The filter status accessory is a field-installed accessory. This accessory detects plugged filters. When installing this accessory, the unit must be configured for filter status by setting MENU--_onfig-_Inputs-,qnput 3, 5, 8, or 9 to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 56 and Fig. 58 for wire terminations at J5. Fan Status The fan status accessory is a field-installed accessory. This accessory detects when the indoor fan is blowing air. When installing this accessory, the unit must be configured for fan status by setting MENU-_onfig-_Inputs-+input 3, 5, 8, or 9 to Fan Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 56 and Fig. 58 for wire terminations at J5. 33 Remote Occupancy Communication The remote occupancy accessory is a field-installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. When installing this accessory, the unit must be configured for remote occupancy by setting MENU_Config-Hnputs--,input 3, 5, 8, or 9 to Remote Occupancy and normally open (N/O) or normally closed (N/C). Also set MENU--_Schedules--_occupancy source to DI on/off. Input 8 or 9 is recommended for easy of installation. Refer to Fig. 56 and Table 7 for wire terminations at J5. Power Exhaust (output) Connect the accessory Power Exhaust contactor coil(s) per Fig. 64. Power Exhaust CTB THERMOSTAT GRA - Protocols General Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications. In the BAS application, many different protocols are used, depending on manufacturer. Protocols do not change the function of a controller; just make the front end user different. The RTU-MP can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SWl and SW2) are used to set the board's network address. See Fig. 65 for the switch setting per protocol. The 3rd party connection to the RTU-MP is through plug J19. NOTE: Power switch settings. TAN Wiring must be cycled after changing the SW1-3 Refer to the RTU-MP 3rd Part)' Integration Guide for more detailed information on protocols, 3rd party wiring, and networking. C08464 Fig. 64 - RTU-MP Power Exhaust Connections SW3 Protocol Selection PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 BACnet MS/'FP (Master) Unused OFF OFF OFF ON OFF Select Baud Select Baud Modbus (Slave) Unused OFF OFF ON ON OFF Select Baud Select Baud N2 (Slave) Unused OFF OFF OFF ON ON OFF OFF LonWorks Unused ON ON OFF ON OFF OFF OFF NOT E: DS = Dip Switch C_a_ O_t_ BAOnet MS/TP SW6 example shown Baud j J _( 3&4_ S_ _ NSTP [ i Rate Selections BAUD RATE DS2 DS1 9600 OFF OFF 19,200 ON OFF 38,400 OFF ON 76,800 ON ON Fig. 65 - RTU-MP C07166 SW3 Dip Switch Settings 34 Local Access Virtual BACview Virtual BACview functions as the 6 Handheld The BACview 6 is a keypad/display interface used to connect to the RTU-MP to access the control information, read sensor values, and test the RTU, see Fig. 66. This is an accessory interface that does not come with the MP controller and can only be used at the unit. Connect the BACview 6 to the RTU-MP's J12 local access port. There are 2 password protected levels in the display (User and Admin). The user password is defaulted to 0000 but can be changed. The Admin password is 1111 and cannot be changed. There is a 10 minute auto logout if a screen is idle. See Form 48-50H-T-2T, Appendix A for navigation and screen content. BACview is a freeware computer program BACview 6 Handheld. The USB that Link interface (USB-L) is required to connect a computer to the RTU-MP board. The link cable connects a USB port to the J12 local access port. This program functions and operates identical to the handheld. RTU-MP Troubleshooting Communication LEDs The LEDs indicate if the controller is speaking to the devices on the network. The LEDs should reflect communication traffic based on the baud rate set. The higher the baud rate the more solid the LEDs will appear. Port P1 PI Protocol Selector RTU-MP J12 Cable P5 P5 BACview s Loca| Access CaNe C07170 Fig. 66 - BACview 6 Handheld 35 Connections Table 8 - LEDs The LEDs on the RTU-MP show the status of certain functions If this LED is on... Status is... Power The RTU MP has power Rx The RTU MP is receiving Tx The RTU MP is transmitting DO# The digital output The Run and Error If Run LED shows... data from the network segment data over the network segment is active LEDs indicate control module and network status And Error LED shows... Status per second Off Normal 2 flashes per second 2 flashes, alternating 2 flashes per second 3 flashes, then off Control 2 flashes per second 4 flashes, then pause Two or more devices on this network same ARC156 network address 2 flashes per second On Exec halted after frequent control programs halted 5 flashes per second On Exec start-up 5 flashes per second Off Firmware 7 flashes per second 7 flashes per second, Run LED 2 flashes 14 flashes On per second 14 flashes alternating with Run LED is... Five minute auto-restart alternating with per second, with Run LED module after system aborted, system errors period Boot is running after brownout Failure. Try the following solutions: • Turn the RTU-MP off, then on. • Format the RTU- MR • Download memory to the RTU-MR • Replace the RTU- MR NOTE: Refer to Form 48-50H-T-2T for complete configuration of RTU-ME operating sequences and troubleshooting information. Refer to RTU-MP 3rd Party Integration Guide for details on configuration and troubleshooting of connected networks. Have a copy of these manuals available at unit start-up. 36 or Boot is running in progress, recovery have the Brownout On error has just been formatted transfer Ten second delay Step 13 -- Humidi-MiZer Space RH Controller TM -- The Humidi-MiZer dehumidification system requires a field-supplied and -installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination thermostat-humidistat control device such as Carrier's EDGE (n_Pro Thermidistat with isolated contact set for dehumidification control. The humidistat temperature PermierLink To connect 1. Route plied) post. is normally control is control). 4O L:IT LL used in applications where a already provided (units with TM the Carrier humidistat (HL38MG029): the humidistat 2-conductor through the hole provided C09295 cable (field-supin the unit corner Fig. 67 - Accessory 2. Feed wires through the raceway build into the corner post (see Fig. 29) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring. 3. Use wire nuts to connect humidistat cable to two PINK leads Fig. 69. To connect 1. Route E-31_o in the low-voltage the Thermidistat the Thermidistat cable (field-supplied) the unit corner post. wiring as shown the hole provided Humidistat IC in actualtemp 59 device (33CS2PPRH-01): multi-conductor thermostat through Field-Installed outside temp in P _mU I 2. Feed wires through the raceway build into the corner post (see Fig. 29) to the 24-v barrier located on the left side of the control box. The raceway provides the UL-required clearance between high-voltage and low-voltage wiring. 3. The Thermidistat has dry contacts at terminals DI and D2 for dehumidification operation (see Fig. 70). The dry contacts must be wired between CTB terminal R and the PINK lead to the LTLO switch C09296 Fig. 68 - EDGE Pro Thermidistat with field-supplied wire nuts. Refer to the installation instructions included with the Carrier Edge Thermidistat device (Form 33CS-65SI or latest) for more information. 37 r,_m WIRING :i.... r FC (PH I OL} CLOlTERMBB _ __ CONTROL ,_HT i P,4K YEL _LU WH _H A % } % (} C09297 Fig. 69 - Typical Humidi-MiZer Adaptive Dehumidification System Humidistat EDGE Pro THERMIDISTAT .... O/W2/B Y1 Q i...... I I I l I I I Q G W2 Wl I l l I_ ll 1 I -- I i___4__ Y1 -- HumidilMiZer i -i- TM FlOP THERMOSTAT 'i i LTLO - PNK -- -- R 7 _ l I PNI_ ..... q Y2 _1 I............................ V+ Vg ---- I Q Q @ @ .... C I I I D1 D2 l I 1 _ OAT RRS SRTN HUM _ I I .... .... -- H ] l X* I I I q C Unit CTB THERMOSTAT l Rc .... Rh Q Wl .... G .... Y2 ......... Wiring <_1/'o _ _ REHEAT CONTROL I I...................... u__J ' *Connection not required. C09298 Fig. 70 - Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification with EDGE Pro Thermidistat Device 38 System Table ---- NOM. V-Ph-Hz 9 - Unit Wire/MOCP POWER IFM COMBUSTION MOTOREXHAUST TYPE FAN FLA FLA - 60 3- 60 o FLA LRA 29.5 45.0 29 99 27.6 40.0 27 97 29.5 45.0 29 99 19.9 30.0 20 91 21.8 30.0 22 96 19.9 30.0 20 91 21.8 30.0 22 96 20.2 30.0 20 109 22.1 30.0 22 111 10.4 15.0 10 47 11.4 15.0 11 48 10.4 15.0 10 47 11.4 15.0 11 48 HIGH 10.9 15.0 11 56 11.9 15.0 12 57 STD 7.5 15.0 8 45 9.4 15.0 10 47 7.5 15.0 8 45 9.4 15.0 10 47 HIGH 7.6 15.0 8 51 9.5 15.0 10 53 STD 34.1 50.0 33 135 36.0 50.0 35 137 34.1 50.0 33 135 36.0 50.0 35 137 24.0 30.0 24 101 25.9 30.0 26 103 24.0 30.0 24 101 25.9 30.0 26 103 HIGH 24.6 30.0 24 119 26.2 30.0 26 121 STD 10.9 15.0 11 50 11.9 15.0 12 51 10.9 15.0 11 50 11.9 15.0 12 51 HIGH 11.4 15.0 11 59 12.4 15.0 12 60 STD 7.5 15.0 8 45 9.4 15.0 10 47 7.5 15.0 8 45 9.4 15.0 10 47 7.6 15.0 8 51 9.5 15.0 10 53 1.9 0.48 MED O 0.48 STD MED 460-6-60 575-6-60 1.9 0.25 MED 208/260-1 - 60 1.0 0.24 1.9 0.48 MED 1.9 STD 208/260- 3- 60 MED 0.48 1.9 It) o -k O 460-6-60 MED 575-6-60 0.25 MED 1.0 0.24 1.9 HIGH 1Fuse or breaker LEGEND: Example: DISC - Disconnect FLA CO IFM -- Full load amps Convenient outlet Indoor fan motor LRA MCA MOCP PE - Locked rotor amps Minimum circuit amps Maximum over current protection Power exhaust UNPWR CO NOTES: - Unpowered v Q convenient Supply voltage is 260-3-60 BC = 231 v AB = 224 v AC = 226 v US 681 (224 + 231 + 226) = Average Voltage = 3 3 outlet 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Never operate a motor voltage is greater than termine the percentage LRA MOCP 97 MED FLA MCA 27 HIGH -k MOCP 40.0 STD 208/260- Data NO C.O. or UNPWRD C.O. NO RE. w/RE, (pwrd fr/unit) DISC. SIZE DISC. SIZE 27.6 STD 208/260-1 MCA Sizing Supply Voltage where a phase imbalance in supply 2%. Use the following formula to deof voltage imbalance. = Determine 227 maximum deviation from average voltage. (AB) 227 - 224 = 3 v (BC) 261 - 227 = 4 v (AC) 227- 226 = 1 v Maximum deviation is 4 v. Determine percent % Voltage imbalance of voltage imbalance. 4 = 100 x 227 max voltage % Voltage imbalance deviation from average = 1.76% voltage = 1O0 x average voltage This amount of phase imbalance maximum allowable 2%. is satisfactory as it is below the IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 39 Table 9 -- Unit Wire/MOCP NOM. V-Ph-Hz COMBUSTION IFM TYPE FAN MOTOR FLA Sizing Data (cont) NO C.O. or UNPWRD C.O. NO RE. w/RE, (pwrd fr/unit) DISC. SIZE DISC. SIZE POWER EXHAUST FLA MCA MOCP MOCP FLA LRA 60.0 68 152 41.5 60.0 40 154 41.7 60.0 40 177 46.6 60.0 46 179 26.4 40.0 26 128 28.6 40.0 28 130 26.7 40.0 26 146 28.6 40.0 28 148 ? HIGH 29.0 40.0 29 172 30.9 45.0 61 174 -k STD 12.8 20.0 12 61 16.8 20.0 14 62 13.6 20.0 16 70 14.6 20.0 14 71 HIGH 14.1 20.0 14 86 15.1 20.0 15 84 STD 10.0 15.0 10 47 11.9 15.0 12 49 10.9 15.0 11 64 12.8 15.0 13 66 HIGH 10.9 15.0 11 64 12.8 15.0 13 66 STD 30.9 45.0 30 159 32.8 50.0 32 161 208/260-1 - 60 1.9 0.48 MED STD 208/260- 6- 60 (D O 460-6-60 0.48 MED 575-6-60 208/260- MED 6- 60 460-6-60 1.9 0.25 MED 1.0 0.24 MED 1.9 0.48 33.2 50.0 33 185 35.1 50.0 35 187 HIGH 33.2 50.0 33 185 35.1 50.0 35 187 STD 15.8 25.0 15 80 16.8 25.0 17 81 16.6 25.0 16 96 17.6 25.0 17 94 17.6 25.0 17 102 18.6 25.0 19 103 12.1 15.0 12 64 14.0 20.0 14 66 12.9 20.0 16 75 14.8 20.0 15 77 12.9 20.0 16 75 14.8 20.0 15 77 MED 1.9 0.25 1.0 HIGH STD 575-6-60 LRA MCA 69.6 STD FLA MED 0.24 1.9 HIGH 1Fuse or breaker LEGEND: Example: DISC - Disconnect FLA CO IFM -- Full load amps Convenient outlet Indoor fan motor LRA MCA MOCP PE UNPWR CO NOTES: - Locked rotor amps Minimum circuit amps Maximum over current protection Power exhaust Unpowered convenient outlet v Q Supply voltage is 260-3-60 BC = 261 v AB AC == 224 226 vv US 681 (224 + 231 + 226) = Average Voltage = 3 = 227 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. Determine maximum deviation (AB) 227 - 224 = 3 v 2. Unbalanced 3-Phase Never operate a motor voltage is greater than termine the percentage Determine percent % Voltage imbalance Supply Voltage where a phase imbalance in supply 2%. Use the following formula to deof voltage imbalance. 3 from average voltage. (BC) 261 - 227 = 4 v (AC) 227- 226 = 1 v Maximum deviation is 4 v. of voltage imbalance. 4 = 100 x 227 max voltage % Voltage imbalance deviation from average voltage = 1.76% = 100 x average voltage This amount of phase imbalance maximum allowable 2%. is satisfactory as it is below the IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 40 Table 9 -- Unit Wire/MOCP Sizing Data (cont) w/PWRD C.O. I-- NOM. V-Ph-Hz COMBUSTION IFM TYPE FAN MOTOR FLA STD 208/230-1 - 60 POWER EXHAUST FLA 3- 60 575- 3- 60 3- 60 208/230-1 - 60 3- 60 It) ? 460- 575- 3- 60 3- 60 SIZE MOCP FLA LRA 34.3 50.0 35 104 32.4 45.0 33 102 34.3 50.0 35 104 24.7 30.0 25 96 26.6 30.0 28 98 24.7 30.0 25 96 26.6 30.0 28 98 25.0 30.0 26 114 26.9 30.0 28 116 12.6 15.0 13 49 13.6 20.0 14 50 12.6 15.0 13 49 13.6 20.0 14 50 HIGH 13.1 15.0 13 58 14.1 20.0 15 59 STD 9.2 15.0 9 47 11.1 15.0 12 49 9.2 15.0 9 47 11.1 15.0 12 49 HIGH 9.3 15.0 10 53 11.2 15.0 12 55 STD 38.9 60.0 39 140 40.8 60.0 41 142 38.9 60.0 39 140 40.8 60.0 41 142 28.8 40.0 29 106 30.7 40.0 31 108 28.8 40.0 29 106 30.7 40.0 31 108 HIGH 29.1 40.0 30 124 31.0 40.0 32 126 STD 13.1 15.0 13 52 14.1 20.0 14 53 13.1 15.0 13 52 14.1 20.0 14 53 HIGH 13.6 20.0 14 61 14.6 20.0 15 62 STD 9.2 15.0 9 47 11.1 15.0 12 49 9.2 15.0 9 47 11.1 15.0 12 49 9.3 15.0 10 53 11.2 15.0 12 55 0.48 MED 1.9 MED 0.48 1.9 MED 0.25 MED 1.0 0.24 1.9 0.48 MED 1.9 MED 0.48 MED 1.9 0.25 MED 1.0 0.24 1.9 HIGH 1Fuse or breaker LEGEND: CO DISC FLA IFM LRA MCA MOCP PE UNPWR CO NOTES: LRA 102 STD 208/230- FLA fr/unit) DISC. MCA MOCP (pwrd 33 STD 460- SIZE 45.0 HIGH ? MCA w/RE. DISC. 32.4 STD 208/230- NO RE. Example: Supply voltage Disconnect AB = 224 v Full load amps C°nvenient°utlet Indoor fan motor Locked rotor C QUS convenient (224 + 231 + 226) protection Average Voltage = 681 = 3 3 outlet 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Never operate a motor voltage is greater than termine the percentage BC = 231 v AC = 226 v _ amps Minimum circuit amps Maximum over current Power exhaust Unpowered is 230-3-60 Supply Voltage where a phase imbalance in supply 2%. Use the following formula to deof voltage imbalance. = 227 Determine maximum deviation (AB) 227 - 224 = 3 v from average voltage. (BC) 231 - 227 = 4 v (AC) 227- 226 = 1 v Maximum deviation is 4 v. Determine percent % Voltage imbalance of voltage imbalance. 4 = 100 x 227 max voltage % Voltage imbalance deviation from average voltage = 1.76% = 1O0 x average voltage This amount of phase imbalance maximum allowable 2%. is satisfactory as it is below the IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 41 Table 9 -- Unit Wire/MOCP Sizing Data (cont) w/PWRD C.O. NOM. V-Ph-Hz COMBUSTION IFM TYPE FAN MOTOR FLA POWER EXHAUST FLA STD NO RE. MCA w/RE. DISC. SIZE FLA LRA fr/unit) DISC. MCA MOCP (pwrd SIZE MOCP FLA LRA 44.4 60.0 44 157 46.3 60.0 46 159 46.5 60.0 46 182 48.4 60.0 48 184 31.2 45.0 31 133 33.1 45.0 34 165 31.5 45.0 32 151 33.4 45.0 34 156 ? HIGH 36.8 45.0 34 177 35.7 50.0 67 179 -k STD 15.0 20.0 15 63 16.0 20.0 16 64 15.5 20.0 16 72 16.5 20.0 17 76 HIGH 16.6 20.0 17 85 17.3 20.0 18 86 STD 11.7 15.0 12 49 13.6 20.0 14 51 12.6 15.0 13 66 14.5 20.0 15 68 HIGH 12.6 15.0 13 66 14.5 20.0 15 68 STD 35.7 50.0 36 164 37.6 50.0 68 166 208/260-1 - 60 1.9 0.48 MED STD 208/260- 3- 60 _D 0 460-6-60 575-6-60 208/260- 3- 60 460-6-60 MED 0.48 MED 1.9 0.25 MED 1.0 0.24 MED 1.9 0.48 38.0 50.0 38 190 39.9 50.0 40 192 HIGH 38.0 50.0 38 190 39.9 50.0 40 192 STD 18.0 25.0 18 82 19.0 25.0 19 86 18.8 25.0 19 95 19.8 25.0 20 96 19.8 25.0 20 104 20.8 60.0 21 105 13.8 20.0 14 66 15.7 20.0 16 68 14.6 20.0 15 77 16.5 20.0 17 79 14.6 20.0 15 77 16.5 20.0 17 79 MED 1.9 0.25 1.0 HIGH STD 575-6-60 MED 0.24 1.9 HIGH 1Fuse or breaker LEGEND: CO DISC FLA IFM LRA MCA MOCP PE UNPWR CO NOTES: Example: Supply voltage Disconnect AB = 224 v Full load amps C°nvenient°utlet Indoor fan motor Locked rotor C QUS BC = 231 v AC = 226 v _ amps Minimum circuit amps Maximum over current Power exhaust Unpowered is 260-3-60 convenient (224 + 231 + 226) protection 681 = Average Voltage = 3 3 outlet = 227 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. Determine maximum deviation (AB) 227 - 224 = 3 v 2. Unbalanced 3-Phase Never operate a motor voltage is greater than termine the percentage Determine percent % Voltage imbalance Supply Voltage where a phase imbalance in supply 2%. Use the following formula to deof voltage imbalance. from average voltage. (BC) 261 - 227 = 4 v (AC) 227- 226 = 1 v Maximum deviation is 4 v. of voltage imbalance. 4 = 100 x 227 max voltage % Voltage imbalance deviation from average voltage = 1.76% = 1O0 x average voltage This amount of phase imbalance maximum allowable 2%. is satisfactory as it is below the IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 42 POTENTIOMETER POWER EXH MINIMUM POS DCV MAX DCV SET ENTHALPY ECONOMIZER (FIOPIACCESSORY) DEFAULTS SETTINGS: MIDDLE FULLY CLOSED MIDDLE MIDDLE C SETTING PNI< VEO- B'L, I (ACCESSORY) REMOTE MIN POSITION POT SET EXH 1 2V IOV NIN POS 0 .pNK_ TI T_ T-_--JOPE_ rF_SA_C_Ri _ ; PL6-R [D AO SENSOR B MAX DCV BLU F L< "OAT TE--'%7 E,_,ALPY SERSOR SO BLK RED 2V I OV -- E_ COOL IRAT/ENTHALPY o SENSOF c BRN-- :< RED-ECONOMIZER NOTES: l 620 OHM, l WATT 5% RESISTER SHOULD BE REMOVED ONLY WHEN USING DIFFERENTIAL ENTHALPY OR DRY BULB 2 IF A SEPERATE FIELD SUPPLIED 24V TRANSFORMER IS USED FOR THE IAO SENSOR POWER SUPPLY, IT CANNOT HAVE THE SECONDARY OF THE TRANSFORMER GROUNDED 3 FOR FIELD INSTALLED REMOTE MINIMUM POSITION POT, REMOVE CONTROL BLACK WIRE JUMPER MINIMUM POSITION BETWEEN POT TO --I i TAN I "GRA-- A P AND Pl AND SET THE MINIMUM POSITION TO "ORN-12 I PWR EXHAUST ACCESSORY (NOT USED) -< _.J C09302 Fig. 71 - EconoMi$er Step 14 -- Adjust Factory-Installed IV Wiring Options EconoMi$er Smoke detector(s) will be connected Connections Board, at terminals Shutdown". Cut jumper JMP 3 when unit. EconoMi$er IV Occupancy at the Controls marked "Smoke ready to energize Differential Outdoor Smoke accessories Curb Thru-base connection is set on curb) LP conversion kit Manual outside Two-Position kit (must be installed outside before unit signal) detector (EconoMi$er IV) sensor sensor (Return Air and/or Supply Air) Louvered hail guard Hood-type hail guard UV-C lamp kit Phase monitor control Pre-Start and Start-Up instructions for information -- This completes the mechanical installation of the unit. Refer to the unit's Service Manual for detailed Pre-Start air damper motorized enthalpy sensor Refer to separate installation on installing these accessories. include: external DDC interface (PremierLink) 4-Inch filter tracks If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY. Cut jumper JMP 2 to complete the installation. Available dry-bulb Differential enthalpy CO2 sensor Switch -- Accessories control/for Power Exhaust Refer to Fig. 71 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Controls Connections Board. Step 15 -- Install IV (with control) EconoMi$er2 (without Barometric relief Smoke Detectors -- air damper and Start-Up 43 instructions. Copyright 2009 Carrier Corp. • Manufacturer reserves 7310 W. Morris St. • the right to change, Indianapolis, IN 46231 at any time, specification8 and design8 Printed in U.S.A. without Edition notice and without 44 Date: 06/09 obligations, Catalog No:48TC-05SI Replaces: 48T0- lSl
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 44 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Fri Dec 18 04:18:30 2009 Author : Title : Subject :EXIF Metadata provided by EXIF.tools