CARRIER Air Conditioner/heat Pump(outside Unit) Manual L1001423
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
AQUAZONE TM 50VS Vertical Stack Water Source Heat Pump with PURON® (R-410A) Refrigerant Installation, Start-Up, and Service Instructions CONTENTS SAFETY CONSIDERATIONS ......................... GENERAL ........................................... Page 1 1 INSTALLATION ................................... 2-17 Step 1 -- Check Jobsite ............................. 2 Step 2 -- Check Unit ................................. 8 • STORAGE • PROTECTION • INSPECT UNIT Step 3 -- Locate Unit ................................ 8 Step 4 -- Install Drywall ............................. 8 Step 5 -- Install Cabinet and Riser ................... 8 • SYSTEM PIPING ARRANGEMENTS • RISER MATERIAL, SIZING AND INSTALLATION • RISER EXPANSION • RISER CONNECTIONS • COMMERCIAL WATER LOOP APPLICATION • GROUND-LOOP HEAT PUMP APPLICATION • OPEN-LOOP GROUND WATER SYSTEMS Step 6 -- Wire Field Power Supply Connections .... 13 • ELECTRICAL-LINE VOLTAGE • POWER CONNECTION • 208/230-VOLT OPERATION Step 7 -- Wire Field Control Connections .......... 15 Step 8 -- Clean and Flush System .................. 15 Step 9 -- Install Hose Kit ........................... 15 Step 10Install Chassis into the Cabinet ......... 16 Step 11 -- Install Return Panel ..................... 16 Step 12Install Supply Grille ..................... 17 PRE-START-UP .................................. 17,18 System Checkout ................................... 18 FIELD SELECTABLE INPUTS .................... 18,19 DIP Switch Settings and Operation ................. 18 Standard 24-vac Sequence of Operation ............ 19 START-UP ....................................... 19,20 Operating Limits .................................... 20 Lockout Mode ...................................... 20 SERVICE ........................................... Water Coil Maintenance ............................ Filters .............................................. Condensate Drain .................................. Compressor ........................................ Fan Motors ......................................... Evaporator Coil ..................................... Cabinet ............................................. Refrigerant System ................................. TROUBLESHOOTING ............................ Lockout Modes ..................................... START-UP CHECKLIST ....................... IMPORTANT: starting installation. Read the entire instruction SAFETY be 21 21 21 21 21 21 21 21 21 21,22 21 CL1,CL2 manual before CONSIDERATIONS Installation and servicing of air-conditioning hazardous due to system pressure equipment can and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform basic maintenance functions such as cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. hnproper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or a local distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements. Understand the signal words -- DANGER, WARNING, and CAUTION. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage. Recognize safety information. This is the safety-alert symbol (AX). When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury. Electrical shock can cause personal injury or death. Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Turn off accessory heater power if applicable. GENERAL This installation and start-up instructions Aquazone TM water source heat pump systems. literature is for The 50VS water source heat pump (WSHP) is a vertically stacked unit with electronic controls designed for year-round cooling and heating. IMPORTANT: The installation of water source heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations. Manufacturer reserves the right to discontinue, or change at any time, specifications Catalog No. 04-53500046-01 Printed in U.S.A. Form 50VS-1SI or designs without notice and without incurring obligations. Pg 1 10-08 Replaces: New INSTALLATION The 50VS units are designed for indoor installations. Units are typically installed in a floor-level closet or a small mechanical room. Be sure to allow adequate space around the unit for servicing. See Fig. 1-5 for unit dimensions. Step 1 E Check Jobsite E Installation, operation and maintenance instructions are provided with each unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check out the system before operation. Complete the inspections and instructions listed below to prepare a unit for installation. See Table 1 for unit physical data. To avoid equipment damage, do not use units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units quickly becomes clogged with construction dirt and debris which may cause system damage. IMPORTANT: This equipment is designed for indoor installation ONLY. Extreme variations in temperature, humidity and corrosive water or air will adversely affect the unit performance, reliability and service life. Table 1 -- Physical Data -- 50VS Unit COOLING CAPACITY UNIT 50VSA,B 50VSC,D 50VSE,F 50VSG,H 50VSI,J 50VSK,L 50VSM,N (Btuh) 9,200 11,700 16,500 18,000 22,500 28,500 32,700 12,500 16,000 22,500 24,500 31,000 38,000 170 45,000 HEATING CABINET CAPACITY (Btuh) WEIGHT (Ib) CHASSIS WEIGHT (Ib) 120 99 I 105 I 119 COMPRESSOR (1 each) High Side Pressure (psig) I R-410A Airflow (cfm) (oz) 27.5 I I 27.5 36.7 I 41.6 I 49.4 I 63.5 I 61.8 7.08 ] 6.69 450 9.21 540 640 x 9.99 820 1120 1300 6.5 8.5 9.5 4.8 7.2 10.2 1.48 1.81 1.48 0 SIDE DATA Flow Rate (gpm) 2.6 Size (FPT) (in.) Water Side Pressure Condensate Scroll (in. wg) Water Connection 205 198 PSC/2 speed 370 WATER/CONDENSATE ] 170 CHARGE Fan Motor Type/Speeds Blower Wheel Size (Depth x Width) (in.) Std/High Static Static Pressure 187 550 Low Side Pressure (psig) FACTORY REFRIGERANT FAN DATA 122 Rotary Drop (psi) Connection 5.8 ] 1/2 3.2 ] 5.8 4.5 5.2 3/4 11.5 11.8 3/4 Size (in.) AIR COIL DATA Total Face Area (sq ft) 1.48 1.48 Tube Size (in.) Fin Spacing (FPI) Number of Rows CABINET 12 2 1.81 I 1.48 3/8 14 10 3 DATA Depth (in.) 18 24 Height (in.) 88 88 Width (in.) Standard Filter -- 1 in. Washable 18 LEGEND FPI PSC --- Fins Per Inch Permanent Split Capacitor 14-1/4 x 18-1/2 I 24 14-1/4 x 22-1/2 19 x 28-3/4 2 1/2" _ 2 1/2" DIMENSION A (in.) WATER CONNECTION SIZE (FPT) (in.) 50VSA,B 18 1/2 1/2 50VSC,D 18 1/2 1/2 50VSE, F 18 3/4 3/4 50VSG,H 18 3/4 3/4 50VSI,J 241/4 3/4 3/4 50VS K, L 241/4 3/4 3/4 50VSM,N 241/4 3/4 3/4 UNIT 0 o 0 0 COIL CONNECTION SIZE (in.) SWAG E SUPPLY 6 1/8" 13 13/16" GRILLE OPTIONAL 24V THERMOSTAT LOCATION 2 3/8" 21/4" CONTROL ACCESS ' FILTER BOX 104" to 115" REGULATOR FLOW LOCATION FACTORY-INSTALLED SUPPLY AND RETURN FEEDERS WITH BALL VALVES f 55 1/2" 65 1/4" HOSE KITS I RETURN PUMPCHASSIS AIR COIL DRAIN -3-- PAN ACOUSTICAL FACTORY 5 5/8" RISER TAILPIECE Fig. 1 -- 50VS Unit Dimensional Data P-TRAP 5/8-in. C I I I 2_in. L DIMENSIONAL DATA Grille Size (in.) Cabinet Height W (in.) H (in.) A (in.) B (in.) C (in.) 16 x 14 STD 157/16 137/16 18 16 8 14 x 12 STD 133/8 113/8 16 14 7 12 x 10 STD 117/16 117/16 14 12 6 10x8 STD 97/16 97/16 12 10 5 NOTES: 1. Single deflection grilles include adjustable vertical blades for controlling horizontal path of discharge. 2. Double deflection grilles include adjustable vertical and horizontal blades for controlling horizontal and vertical path of discharge air (recommended). 3. Dimensions are in inches. 4. All dimensions are 4- 1/4 inch. 5. Discharge grilles are shipped loose for field installation. 6. Construction is roll formed aluminum frame and blades. 7. Standard finish is powder coated and will be the same color as the return grille. 8. Installation of grille on adjacent unit sides may require a duct extension to prevent air bypass around discharge grilles. 9. Mounting hardware included. Fig. 2 -- Single and Double Deflection Aluminum Discharge Grille A W 5/8" --O o C 1 \ I ' I 1, r l DIMENSIONAL 3 1/8" DATA Grille Size (in.) Cabinet Height W (in.) H (in.) A (in.) B (in.) 16 x 14 STD 153/16 133/16 173/4 14 x 12 STD 133/16 113/16 153/4 12 x 10 STD 113/16 93/16 10x8 STD 93/16 73/16 C (in.) D (in.) 153/4 N/A 47/8 133/4 67/8 N/A 133/4 113/4 57/8 N/A 113/4 93/4 47/8 N/A NOTES: 1. The opposed blade damper allows control of air volume (cfm) and path of discharge air. Recommended for applications requiring unequal airflow or side discharge grille(s) with additional top discharge air opening. 2. Dimensions are in inches. 3. All dimensions are 4- 1/4 inch. 4. Discharge grilles are shipped loose for field installation. 5. Construction is roll formed aluminum frame and blades. 6. Standard finish is powder coated and will be the same color as the return grille. 7. Installation of grille on adjacent unit sides may require a duct extension to prevent air bypass around discharge grilles. 8. Mounting hardware included. Fig. 3 -- Double Deflection with Opposed Damper Aluminum Discharge Grille STANDARD PERIMETER BYPASS ALLEN LOCK, REMOVABLE -- OPTIONAL PERIMETER BYPASS ALLEN LOCK OR KEY LOCK, HINGED OPTIONAL LOUVERED ALLEN LOCK, REMOVABLE 2.95 21.13 26.28 24.19 L i mB 55L.35 63.15 58.00 61 1 'r r 17.68 2.38 , 30.38* ' ] ....................................... _ *ROUGH-IN STANDARD PERIMETER BYPASS ALLEN LOCK, REMOVABLE NOTE: All dimensions OPENING PLUS 1/4-in. OPTIONAL PERIMETER BYPASS ALLEN LOCK OR KEY LOCK, HINGED OPTIONAL LOUVERED ALLEN LOCK, REMOVABLE are in inches. Fig. 4 -- Return Panel and Frame Dimensions -- 50VSA-VSH Units STANDARD PERIMETER BYPASS ALLEN LOCK, REMOVABLE OPTIONAL PERIMETER BYPASS ALLEN LOCK OR KEY LOCK, HINGED OPTIONAL LOUVERED ALLEN LOCK, REMOVABLE 32.28 2.95 27.13 30.19 58.75 63.90 61.86 | 24.91 r m | -- 19.68 2.38 , 2438. STANDARD PERIMETER BYPASS ALLEN LOCK, REMOVABLE * ROUGH-IN OPENING PLUS 1/4-in. OPTIONAL PERIMETER BYPASS ALLEN LOCK OR KEY LOCK, HINGED OPTIONAL LOUVERED ALLEN LOCK, REMOVABLE NOTE: All dimensions are in inches, Fig. 5 -- Return Panel and Frame Dimensions -- 50VSI-VSN Units Step 2 -- Check Unit -- Upon receipt of shipment at the jobsite, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. Ensure the shipping company makes proper notation of any shortages or damage on all copies of the freight bill. Concealed damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of shipment. NOTE: It is the responsibility of the purchaser necessary claims with the shipping company. to file all 1. Be sure that the location chosen for unit installation provides ambient temperatures maintained above freezing. Well water applications are especially susceptible to freezing. 2. Be sure the installation areas, private offices spaces. DO NOT store or install units in corrosive enviromnents or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage. INSPECT UNIT -- To prepare the unit for installation, plete the procedures listed below: com- 1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped. location is isolated from sleeping and other acoustically sensitive 2. NOTE: A sound control accessory package may be used to help eliminate sound in sensitive spaces. Do not remove installation. 3. 3. Check local codes to be sure a secondary required under the unit. Verify that the unit's refrigerant robing is free of kinks or dents, and that it does not touch other unit components. 4. 4. Be sure unit is mounted at a height sufficient to provide an adequate slope of the condensate lines. If an appropriate slope cannot be achieved, a field-supplied condensate pump may be required. Inspect all electrical connections. Be sure connections clean and tight at their terminations. 5. Remove blower. drain pan is not the packaging any blower support until the unit is ready for cardboard are from inlet of the 5. Provide sufficient space for duct connection. Do not allow the weight of the ductwork to rest on the unit. 6. Locate and verify any accessory kit located in compressor and/or blower section. 6. Provide adequate clearance for filter replacement and drain pan cleaning. Do not allow piping, conduit, etc. to block filter access. 7. Remove any access panel screws that may be difficult to remove once unit is installed. 7. Provide sufficient access to allow maintenance and servicing of the fan and fan motor, compressor and coils. Removal of the entire unit from the closet should not be necessary. 8. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of unit if necessary. 9. Provide ready access to water valves and fittings, and screwdriver access to unit side panels, discharge collar, and all electrical connections. 10. Where access to side panels is limited, pre-removal of the control box side mounting screws may be necessary for future servicing. STORAGE -- If the equipment is not needed ilmnediately at the jobsite, it should be left in its shipping carton and stored in a clean, dry area of the building or in a warehouse. Units must be stored in an upright position at all times. If carton stacking is necessary, stack units a maximum of 3 cartons high. Do not remove any equipment from its shipping package until it is needed for installation. PROTECTION -- Once the units are properly positioned on the jobsite, cover them with either a shipping carton, vinyl fihn, or an equivalent protective covering. Cap open ends of pipes stored on the jobsite. This precaution is especially flnportant in areas where painting, plastering, or spraying of fireproof lnaterial, etc. is not yet complete. Foreign material that accumulates within the units can prevent proper start-up and necessitate costly clean-up operations. Before installing any of the system components, examine each pipe, fitting, and valve, and remove foreign material found in or on these components. be sure to any dirt or Step 3 _ Locate Unit _ should be considered The when choosing following guidelines a location for a WSHP: • Units are for indoor use only. • Locate in areas where ambient temperatures are between 39 F and 102 F and relative humidity is no greater than 75%. Provide sufficient connections. space for water, electrical and duct Locate unit in an area that allows easy access and removal of filter and access panels. Allow enough maintenance. space for service personnel to perform Return air must be able to freely enter the space if unit needs to be installed in a confined area such as a closet. Step 4 _ Install Drywall _ All rough-in instructions and drawings ar e designed for a single layer of 5/s in- thick drywall. Refer to Fig. 6. Rough-in dimensions will be affected if drywall thickness is different than 5/8 in., the return panel will not fit snugly to the wall and form a tight seal. Install drywall using conventional construction methods. Drywall cannot be fastened to the studs with adhesive alone; a mechanical fastener such as drywall screws must be used. Vacuum all drywall dust and construction debris from coils, drain pans and blower discharge plenum after cutting out supply and return holes for grilles. When installation is complete, cover cabinet supply and return air openings. Do not allow paint or wall texture over-spray to contact coil, fan or other unit components. Warranties are void if paint or other foreign debris is allowed to contaminate internal unit components. Step 5 -- Install Cabinet and Riser SYSTEM PIPING ARRANGEMENTS -- Figure 7 shows some of the colmnon piping layouts for water source heat pumps. 2-pipe systems are depicted but the same methods can be applied to 4-pipe systems. The direct return system shows the most common piping arrangement. This is the most cost effective method of piping to install since the water is supplied and returned to a riser column at the same place, at the bottom or top of the building. However, this type of system requires more effort to individually balance water flow to the units. The risers are normally capped at the ends opposite the main supply and return piping and may require a field-installed flush and vent loop. The first reverse return system shows a system, which is commonly used to minimize individual unit water flow balancing and is often referred to as "self balancing." This riser arrangement has a natural affinity to balance the flow to each unit in the riser column. However, individual unit balancing may still be required. This piping system is used on 2-pipe systems only and has an individual return for each riser column. The second reverse return system shows a system with a common reverse return riser installed separately from the individual unit riser columns. This riser arrangement allows for more flexibility in individual unit riser sizing but has the same general characteristics as the "reverse return" system described above. It may also be a better fit for the particular structural and architectural requirements of the building. This piping system may also be used on 4-pipe systems. Regardless of the system selected, optimum performance can only be achieved through adjustlnent to the recommended water flow at each individual unit (see Table 1 for individual unit water flow requirements). RISER MATERIAL, SIZING, AND INSULATION -Some of the factors affecting riser application and sizing are noise, tube erosion and economics. Water source heat pumps maybe supplied with factory-installed risers; the riser material, diameter, length and insulation thickness must be determined for each unit based on its positioning within the building. Figure 8 displays riser robe diameter sizes as a function of flow (gpm), friction loss and water velocity. For maxilnum riser velocity on pressure drop per 100 ft, refer to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) Fundamentals Handbook for Riser Sizing. Generally, riser copper type, size, length and insulation thickness are determined by the location of the water source heat pump unit in the building. Chilled water and hot water risers are available in Type-M, Type-L copper, varying diameters from 3/4 to 21/2 in., and with either no insulation, 1/2 or 3/4 in. thick closed cell foam insulation. Condensate risers are available in Type-M copper, varying diameters from 3/4 to 11/4 in., and with no insulation, 1/2 or 3/4 in. thick closed cell foam insulation. All factory-supplied risers and riser extensions are insulated for the full length of the riser, eliminating the need for field insulation. Insulation is not required on loop water piping except where the piping runs through unheated areas, outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient conditions. Insulation is required if loop water temperature drops below the dew point (insulation is required for the ground loop applications in most clilnates). Riser sizing is generally based on the water flow requirements of each unit and the units on higher and lower floors that tie into the same riser column depending on the piping system chosen. Water piping is often designed at approximately 5 ft/s. Keeping this in mind, risers can be reduced in size as the water flow decreases froln floor to floor. For low-rise buildings, riser sizes can be of a single diameter. The reduced material handling on site will often offset the extra costs associated with the larger risers. RISER EXPANSIONGenerally, in medium to high-rise buildings, allowances must be made for pipe expansion. In applications supplemented with factory (or field) supplied between the floor riser extensions, assemble and install extensions before installing cabinet. NOTE: Riser assemblies are designed to accommodate a maximum of 11/8 in. expansion and contraction up to a total movement of 21/4 inches. If the total calculated rise expansion exceeds 21/4 in., expansion devices must be used (field provided). 50VS UNIT DIMENSIONS SIZE A (in.) B C 245/8 3011/16 245/8 6311/16 50VSI-VSN 307/8 3611/16 305/8 647/18 EXISTING WALL fA_ RISERS -- RETURNDRAINSUPPLY- __ \RETURN PANEL \ \_ DRYWALL TOP VIEW DRYWALL EXISTING WALL _ / STUD _4__.f] _ "_[_ UNIT CABINET _ j_\ _ DETAIL A Fig. 6 -- Framing Rough-In Detail D 50VSA-VSH 1 11/16in. MIN FRAME FASTENERS BY OTHERS _ RETGAsKETURNPANEL DIRECT Flush/Vent ! Loop RETURN Capped Roof REVERSE RETURN REVERSE RETURN WiTH A COMMON REVERSE RETURN RISER Risers Roof ¢ •4 I 1I 3rd Floor =1 =i - 3rd Floor i i 2nd Floor 2rid Floor k m I st Floor R R-- s ===e, 1 =! -1 . | i • • > -- 1st Floor tgR Mains Mains Basement Basement Fig. 7 -- System Piping Arrangements All riser modifications necessitated by variations in flooPtofloor dimensions including cutting off or extending risers is the sole responsibility of the installing contractor. Additional expansion compensation must be made in the riser system in the field where movement is expected to exceed the factory allowances. Figure 9 displays the expansion characteristics of risers compared to water temperature differential. Assuming a lninimum water temperature of 20 F and a maxilnum water temperature of 120 K the temperature difference of 100 F indicates 90 feet of riser will expand or contract 1 inch. To eliminate stress, a riser system must be anchored at least once to the building structure. Technical information on pipe expansion, contraction and anchoring can be found in the ASHRAE HVAC Systems and Equipment Handbook and various other technical publications. Riser expansion and the anchoring of each unit is the responsibility of the design engineer and installing contractor. RISER CONNECTIONSInstall cabinet with risers as follows: _E "5 ft. g 3.0 4.0 1 I 1o 9.0 8.0 7.0 6.o 5.06.07.08.0 I /I 20 10 I',...,_ _ 30 40 1o "- 8o T- 5.0 ...... 3.0 ["- ez ! ! 1 6"s ! -.._/ I 17"42, 80 ,4 / / 5 ft /'f'-4d "_- I lit N4'_s 2.0 = O.. 1.o , 3.0 , , / 40 5todbrbso 10 1.0 20 Water Flow 30 40 50 507080100 Rate - GPM Fig. 8 -- Friction Loss of Risers 550 Keep risers off the floor while moving the cabinet. Failure to heed this warning could result in equipment damage. 500 i Be sure that all the copper fittings are clean and flee of dirt. Raise the cabinet upright and lower it into the riser from the floor below. !- 0 5. X_. 400 W Center risers in the pipe chase and shim the cabinet level. Plumb risers in two planes to assure proper unit operation and condensate drainage. ._ 350 ' T- 300 280 ,..= 200 Attach the cabinet assembly to the floor and the building structure on at least two sides using sheet metal angles (field provided). A field-provided base vibration dampening pad can be used to help eliminate transfer of any vibration to the structure. If vibration dampening pads are used some rough-in dimensional changes will need to be considered before installation due to style and thickness of the pads. Additional anchorage can be provided by installing brackets at the top of the cabinet (field provided). DO NOT attach drywall studs to the equipment 450 !- NOTE: The top of each riser is equipped with a 3 in. deep swaged connection. There is sufficient extension at the bottom to allow insertion of approxhnately 2 in. of the riser into the swaged top of the riser below. 4. 3.0 t_ m 3. ,o I £ 1. Move cabinet into position. 2. 6.8 d__/ / I/'--J [/ 100 _, ii 4.0 50 607080 2 t-- = •_ 150 "a 100 tr 50 --- -- 20 40 60 80 100 120 140 160 Water TemperatureDifference - F cabinet. Fig. 9 -- Allowable Riser Lengths Between System Expansion Loops 10 6. When all units on a riser are anchored into place, complete riser joints as follows: a. Verify that all riser joints are vertically aligned and that risers penetrate at least 1 in. into the swaged joint of the riser below. DO NOT let riser joint bottom out. b. 7. Piping Installation -- All earth loop piping materials should be limited to polyethylene fusion only for in ground sections of the loop. Galvanized or steel fittings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fittings should be avoided due to their potential to leak in earth coupled applications. A flanged fitting should be substimted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat exchanger. Braze riser joints with a high-temperature alloy using proper Phos-copper of Silfos. Soft solder 5050, 60-40, 85-15, or 95-5 or low temperature alloys are not suitable riser weld materials. Earth loop temperatures can range between 25 and 110 F. Flow rates between 2.25 and 3.0 gpm per ton of cooling capacity is recommended in these applications. c. Anchor built-in risers to the building structure with at least one contact point. To accommodate vertical expansion and contraction DO NOT fasten risers rigidly within the unit. d. Verify that unit shut-off valves are closed. DO NOT OPEN VALVES until the system has been cleaned and flushed. Pressures of at least 100 psi should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled. e. Flush system; refer to System Cleaning ing section for more information. f. Install vents in piping loop as required to bleed the system of air accumulated during installation. Flushing the Earth Loop -- Upon completion of system installation and testing, flush the system to remove all foreign objects and purge to remove all air. Install supply duct extension(s) provided by folding the tabs down to secure cabinet. Test individual horizontal loop circuits before backfilling. Test vertical U-bends and pond loop assemblies prior to installation. and Flush- Antifreeze -- In areas when minilnum entering loop temperarares drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local Carrier distributor should be consulted for the antifreeze best suited to your area. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if 30 F is the lninilnum expected entering loop temperature, the leaving loop temperature would be 25 to 22 F and freeze protection should be at 15 F. Calculation as follows: 30F15F= 15F. with the cabinet extension(s) to COMMERCIAL WATER LOOP APPLICATION -- Coinmercial systems typically include a number of units connected to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system; therefore, air elimination equipment is a major portion of the mechanical room plumbing. In piping systems expected to utilize water temperatures below 50 F, 1/2 in. closed-cell insulation is required on all piping surfaces to eliminate condensation. Metal to plastic threaded joints should never be used due to their tendency to leak over time. All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. Calculate the total volume of fluid in the piping system. Then use the percentage by volume shown in Table 2 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity. Teflon tape thread sealant is recommended for use in system piping to minimize internal fouling of the heat exchanger. Do not over tighten connections and route piping so as not to interfere with service or maintenance access. Hose kits include shut off valves, pressure/temperature (P/T) plugs for performance measurement, high pressure stainless steel braided hose, and hose adaptors. Balancing also be used. valves and variable speed pumping Table 2 -- Antifreeze Percentages TYPE systems my Methanol 100% USP Food Grade Propylene Glycol Ethanol* The piping system should be flushed to remove dirt, pipe shavings, chips, and other foreign material prior to operation. See System Cleaning and Flushing section. The flow rate is usually set between 2.25 and 3.5 gpm per ton for most applications of water loop heat pumps. To ensure proper maintenance and servicing, P/T ports are imperative for temperature and flow verification, as well as performance checks. by Volume MINIMUM TEMPERATURE FOR LOW TEMPERATURE PROTECTION 10 F 15 F 20 F 25 F 25% 21% 16% 10% 38% 25% 22% 15% 29% 25% 20% 14% *Must not be denatured with any petroleum based product. OPEN - LOOP GROUND WATER SYSTEMS -- Shut off valves should be included for ease of servicing. Boiler drains or other valves should be "tee'd" into the lines to allow acid flushing of the heat exchanger. P/T plugs should be used so that pressure drop and temperature can be measured. Piping materials should be limited to copper or PVC SCH80. Water loop heat pump (cooling tower/boiler) systems typically utilize a common loop, maintained between 60 to 90 E The use of a closed circuit evaporate cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary. GROUND-LOOP HEAT PUMP APPLICATION NOTE: Due to the pressure SCH40 is not recommended. and temperature extremes, PVC Water quantity should be plentiful and of good quality. Consult Table 3 for water quality guidelines and recommendations. Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualified technician, as acid cleaning agents and special pumping equipment are required. NOTE: In most commercial building applications using a frame style or plate style heat-exchanger should be used to isolate the water source heat pump units from the ground water loop increasing system performance, equipment longevity. Pre-Installation -- Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential furore damage to the installation. 11 Inareas withextremely hardwater, theownershould beinformed thattheheatexchanger mayrequire additional system maintenance andoccasional acidflushing. In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treatment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits. Water Supply and Quality -- Check water supply. Water supply should be plentiful and of good quality. See Table 3 for water quality guidelines. IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closedsystem application design requirements may cause damage to the tube-in-tube heat exchanger. This damage is not the responsibility of the manufacturer. Table 3 -- Water Quality Guidelines CONDITION I MATERIAL* HX I REClRCULATINGt CLOSED I OPEN LOOP AND REClRCULATING Scaling Potential -- Primary Measurement Above the given limits, scaling is likely to occur, Scaling indexes should be calculated pH/CalciUmHardness Method I All Index Limits for Probable Scaling Situations I N/A (Operation outside I <100 ppm is not recommended.) Scaling indexes should be calculated at 150 F for direct use and HWG applications, implemented. Ryznar Stability Index using the limits below, pH < 7.5 and Ca Hardness, these limits WELL** and at 90 F for indirect HX use. A monitoring plan should be All N/A 6.0 - 7.5 If >7.5 minimize steel pipe use. All N/A -0.5 to +0.5 If <-0.5 minimize steel pipe use. Based upon 150 F HWG and direct well, 85 F indirect well HX. Iron Fe 2+ (Ferrous) (Bacterial Iron Potential) All N/A <0.2 ppm (Ferrous) If Fe2+ (ferrous) >0.2 ppm with pH 6 - 8, 02<5 ppm check for iron bacteria. Iron Fouling All N/A <0.5 ppm of Oxygen Above this level deposition will occur. All 6 - 8.5 Monitor/treat as needed. 6 - 8.5 Minimize steel pipe below 7 and no open tanks with pH <8. All N/A At H2S>0.2 ppm, avoid use of copper and cupronickel piping or HXs. Rotten egg smell appears at 0.5 ppm level. Copper alloy (bronze or brass) cast components are okay to <0.5 ppm. All N/A Langelier Saturation Index Iron Fouling Corrosion Preventiontt pH Hydrogen Sulfide (H2S) Ammonia Ion as Hydroxide, Chloride, Nitrate and Sulfate Compounds Maximum Chloride Levels <0.5 ppm <0.5 ppm Maximum allowable at maximum water temperature. 50 F (10 C) <20 ppm <150 ppm <400 ppm <1000 ppm >1000 ppm 75 F (24 C) NR NR <250 ppm <550 ppm >550 ppm 100 F (38 C) NR NR <150 ppm <375 ppm >375 ppm Copper CuproNickel 304 SS 316 SS Titanium N/A N/A N/A N/A N/A All <10 ppm of particles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. <10 ppm (<1 ppm "sandfree" for reinjection) of particles and a maximum velocity of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not removed can potentially clog components. All N/A Use cupronickel heat exchanger when concentrations of calcium or sodium chloride are greater than 125 ppm are present. (Seawater is approximately 25,000 ppm.) Erosion and Clogging Particulate Size and Erosion Brackish HWG-HX -N/A -NR SS --- LEGEND Hot Water Generator Heat Exchanger Design Limits Not Applicable Considering Potable Water Application Not Recommended Stainless Steel ttlf Recirculating *Heat exchanger materials considered are copper, cupronickel, 304 SS (stainless steel), 316 SS, titanium. fCIosed recirculating system is identified by a closed pressurized piping system. **Recirculating open wells should observe the open recirculating design considerations. 12 the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists. Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause system problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0. To convert ppm to grains per gallon, divide by 17. Hardness in mg/I is equivalent to ppm. Step 6 -Connections Wire Field Power Supply serial plate. Line and low voltage wiring must be done in accordance with local codes or the NEC, whichever is applicable. POWER CONNECTION Units Equipped with Disconnect -- Connect incoming line voltage to the disconnect switch and ground wire to the ground lug provided inside the electrical compartment. Electrical shock can cause personal iniury or death. When installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Units without Disconnect -- Line voltage connection is made by connecting the incoming line voltage wires to the line side(s) of the contactor. 208/230-VAC OPERATION--All colmnercial 208/230-v units are factory wired for 208-v single-phase operation. For 230-v single-phase operation the primary voltage to the transformer must be changed. Remove the red lead from the compressor contactor capping it with a wire nut and connecting the orange 230-vac lead wire from the transformer to the compressor contactor. ELECTRICAL-LINE VOLTAGE -- All field-installed wiring, including electrical ground, must comply with the National Electrical Code (NEC) as well as all applicable local codes. Refer to Tables 4 and 5 for fuse sizes. Refer to Table 6 for blower speed wiring. See Fig. 10 for field connections or the electrical diagram located on the back of the electrical compartment front panel. All electrical connections must be made by the installing (or electrical) contractor. All final electrical connections must be made with a length of flexible conduit to minhnize vibration and sound transmission to the building. NOTE: Failure to change the primary voltage lead when using 240-vac line voltage may result in electrical component damage and intermittent system failure. General Line Voltage Wiring -Be sure the available power is the same voltage and phase shown on the unit Table 4 -- Cabinet Electrical Data -- 50VS Unit S U P PLY VOLTAGE V-Hz-Ph MOTO R VOLTAGE V-Hz-Ph FAN MOTOR FLA (A) MOTOR POWER (W) 50VSA,B 208/230-1-60 208/230-1-60 0.30 130 6.5 15 50VSC,D 208/230-1-60 208/230-1-60 0.40 142 8.6 15 50VSE,F 208/230-1-60 208/230-1-60 0.88 180 11.9 20 50VSG,H 208/230-1-60 208/230-1-60 1.18 240 12.5 20 50VSI,J 208/230-1-60 208/230-1-60 1.60 304 16.2 30 50VSK,L 208/230-1-60 208/230-1-60 1.80 368 19.5 30 50VSM,N 208/230-1-60 208/230-1-60 2.06 442 21.0 35 UNIT MIN CIRCUIT AMP MAX FUSE SIZE (A) LEGEND FLA -- Full Load Amps Table 5 -- Chassis Electrical Data -- 50VS Unit UNIT SUPPLY VOLTAGE V-Hz-Ph 50VSA,B 208/230-1-60 6.5 15 20 3.27 4.0 3.75 4.60 50VSC,D 208/230-1-60 8.6 15 27 4.40 4.0 5.25 6.25 50VSE,F 208/230-1-60 11.9 20 42 6.30 5.4 7.07 8.80 50VSG,H 208/230-1-60 12.5 20 42 6.70 7.6 7.50 9.00 50VSI,J 208/230-1-60 16.2 25 46 8.20 8.0 9.20 11.70 50VSK,L 208/230-1-60 19.5 30 70 11.00 10.4 12.20 14.10 50VSM,N 208/230-1-60 21.0 30 79 12.70 16.0 13.65 16.50 MIN CIRCUIT AMP MAX FUSE SIZE (A) COMPRESSOR (LRA) COOLING CURRENT (A) MAX COOLING CURRENT (A) LEGEND LRA -- Locked Rotor Amps Table 6 -- 50VS Unit Blower Performance and Speed Wiring UNIT FAN SPEED AND WIRING RATED CFM MIN CFM 0 0.01 0.05 0.1 50VSA,B LOW (Black) HI (Blue) 360 260 361 316 358 310 341 294 321 278 294 262 50VSC,D LOW (Blue) HI (Red) 420 300 424 361 421 358 398 341 376 321 350 305 50VSE,F LOW (Black) HI (Blue) 540 390 551 470 549 465 535 455 521 439 509 428 50VSG,H LOW (Blue) HI (Red) 630 455 626 551 622 549 604 535 592 521 577 509 50VSI,J LOW (Orange) HI (Brown) 820 600 821 768 817 765 814 762 812 759 802 751 50VSK,L LOW (Black) HI (Blue) 1080 780 1081 956 1075 951 1070 942 1049 928 1024 911 50VSM,N LOW(Blue) HI (Red) 1220 850 1222 1102 1219 1096 1194 1091 1160 1070 1129 1044 NOTE: Operation not recommended in shaded area. 13 EXTERNAL 0.15 STATIC PRESSURE (in. wg) HEATING CURRENT (A) MAX HEATING CURRENT (A) BLOWER SPEED WIRING Unit 208-230160/1 PowerSupply NI ! BI k Unit Orange Brown Black Blue Red 50VSA,B Low High -- -- -- 50VSC,D 50VSE,F --- Low -- High Low -High --- 50VSG,H -- -- -- Low High 50VSI,J 50VSK,L Low -- High -- -Low -High --- 50VSM,N -- -- -- Low High IL 0plonaI Note 4 Oap -White ©range- Note 6 I BRt o Transformer -- oo io-: ......... I oo See Chart Above Pl Orange YlC_ (_ ........ ......I-Yell°w I /_W[liLe! - SWl ollot ..... xq@o_ Note,I_51....... I-=.o-*--ASUPPLY RETURN O t SUPPLY AIR TO ROOM T RETURN AIR FROM ROOM LEFT RIGHT CABINET Field-supplied and installed piping Cross hoses in slave cabinet (36 in. hoses required in slave unit) FRONT Supply Grille Sizes and Arrangements UNIT DISCHARGE Single Double 10x8 (in.) Triple 50VSA,B (Small Cabinet) 14xl 2 50VSC,D (Small Cabinet) 14xl 2 10x8 10x8 50VSE,F (Small Cabinet) 14x12 10x8 10x8 50VSG,H (Small Cabinet) 14x12 10x8 10x8 50VSI,J (Large Cabinet) 16x14 12x10 12x10 50VSK, L (Large Cabinet) 16x14 12x10 12x10 50VSM,N (Large Cabinet) 16x14 12x10 12x10 SLAVE "_1 I"_'- MASTER 10x8 Dimension to suit local codes and installer LEGEND C -RS -- Condensate Return Supply Drain NOTES: 1, Refer to the table and the airflow arrangements above to determine grille size and location based on the type and size of the unit cabinet/chassis combination, 2, The riser compartment is defined as being the rear of each unit, Supply air grilles and return air/access panel can be any side except rear, 3, Return air location also denotes the control location and servicing access, 4, Single discharge openings are not recommended for 50VSI-VSN units, Triple discharge openings are not recommended for 50VSA-VSD units, Fig. 12 -- 50VS Unit Airflow Arrangements 17 Table 9 -- Limits of Operation Air Limits Cooling (F) Heating (F) Ambient Air Maximum 50 50 Ambient Air Minimum 1O0 85 80,6 80,6/66,2 68 68 100/83 80 30 20 50-110 30-70 120 90 Rated Ambient Air Rated Entering Air (db/wb) Entering Air Maximum (db/wb) Entering Water Minimum* Entering Water (Normal) Entering Water Maximum IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off. Table 10- 4. 5. 6. 7. insulation when operating below the dew point, Unit fan: Manually rotate fan to verify flee rotation and ensure that blower wheel is secured to the motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are pre-oiled at the factory. Check unit fan speed selection and compare to design requirements. Condensate line: Verify that condensate properly pitched toward dram. 3. (PC) 1 -- Test/Normal ON ON ON 2 -- FP1 15 F/32 F ON ON ON ON ON ON or OFF OFF OFF OFF 4 -- RV Cooling Off/On ON ON ON ON 5 -- Com2/Coml ON OFF OFF OFF 6 -- Corn2 Modbus Address OFF OFF OFF OFF 7 -- Corn2 Modbus Address OFF OFF OFF OFF 8 -- Corn2 Modbus Address OFF OFF OFF OFF LEGEND ---- Dual In-Line Package Personal Computer Printed Circuit Board Table 11 -- BacNet TM Control Board (PCB) DIP SWITCH NUMBER Checkout for set System pH: Check and adjust water pH if necessary to maintain a level between 6 and 8.5. Proper pH promotes longevity of hoses and fittings. Cooling tower/boiler: points and operation. Check equipment for proper 5. Standby pumps: Verify that the standby pump is properly installed and in operating condition. 6. System controls: Verify that system controls function and operate in the proper sequence. 7. Low water temperature cutout: Verify that low water temperature cutout controls are provided for the outdoor portion of the loop. Otherwise, operating problems may DIP -PCB -- ON 2 OFF 3 OFF 4 OFF 5 6 OFF OFF 7 OFF 8 OFF Dual In-Line Package Printed Circuit Board DIP Switch Settings DIP SWITCH 1 (Test Mode = Off/Normal and Operation Mode = On) Test Mode -- Test mode is used to speed up the operation sequence of the unit, therefore creating a more timely troubleshooting technique. All time delays are shorted by 10 times with the exception of the high-pressure lockout which is instantaneous regardless of which mode the switch is positioned. DIP switch 1 must be placed into the Normal mode to resume proper operation of the unit. set DIP SWITCH 2 (FP 1 at 15 F = Off/FP 1 at 32 F = On) Water Side Freeze Protection Setting -- DIP switch 2 is used to determine the loop freeze protection setting. Depending on the brine concentration of the liquid source, the temperature can be set at 15 F or 32 F. The switch MUST be set to the "On" position if pure water is used as the source brine. This is normally the case in open loop systems. Set the DIP switch to the "OIF' position for closed loop systems that contain a brine concentration that allows liquid temperatures to fall to, or below, 15E occur. System control center: Verify that the control center and alarm panel have appropriate set points and are operating as designed. FIELD SELECTABLE POSITION OFF/ON 1 LEGEND System flushing: Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger, water valves and other components. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Verify that all air is purged from the system. Air in the system can cause poor operation or system corrosion. 4. 8. LonWorks DIP PC PCB Unit controls: Verify that the microprocessor DIP (dual m-line package) switches are set for proper operation and system configuration. 1. System water temperature: Check water temperature proper range and also verify heating and cooling points for proper operation. 2. BacNet line is open and Water flow balancing: Record inlet and outlet water temperatures for each heat pump upon start-up. This check can eliminate nuisance trip outs and high velocity water flow that could erode heat exchangers. System Modbus No Network 3 -- Tstat Comm/ 24-vae Dry Bulb Wet Bulb *Requires additional PROTOCOL DIP SWITCH NUMBER LEGEND db -wb-- Heat Pump Control Board (PCB) DIP SWITCH 3 (Tstat at Cmmn= off/tstat at 24-vac = On) Thermostat Selection -- DIP switch 3 is used to select the type of thermostat that will be used to control the unit. A digital colr_numcatmg thermostat can be purchased with the unit that will allow all fault signals to be displayed on the thermostat. This allows for efficient troubleshooting and does not require that the technician access the electrical control box INPUTS Jumpers and DIP switches on the control board are used to customize unit operation and can be configured in the field. See Tables 10 and 11 for heat pump and BacNet control board DIP switch settings. 18 todetermine theuniterror.If adigitalcolmnunicating thermostatisused DIPswitch 3mustbesetinthe"Off"position. If a 24-vac thermostat is usedsetDIPswitch3 intothe"On" position. DIPSWITCH 4 (RVatCooling = Off/RVatCooling= On) HEATING FIRST STAGE (Y1) -- When the microprocessor receives (Y1) at the 24-vac thermostat input connection the unit will proceed with the cooling first stage sequence. The microprocessor must receive these signals for 2 continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/deenergize after 5 seconds. The microprocessor will then verify that the anti short cycling delay has been satisfied. Once the anti short cycling delay has been satisfied the compressor and will cycle "On." The blower will cycle "On" in low speed 15 seconds after the compressor is cycled "On." HEATING SECOND STAGE (Y1, Y2) -- When the microprocessor receives (Y1, Y2) at the 24-vac thermostat input connection the unit will proceed with the heating second stage sequence. The microprocessor must receive these signals for 2 continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/deenergize after 5 seconds. The microprocessor will then verify that the anti short cycling delay has been satisfied. Once the anti short cycling delay has been satisfied the compressor and will cycle "On." The blower will cycle "On" in high speed 15 seconds after the compressor is cycled "On." FAN ONLY MODE (G) -- The fan only mode can be used only with a 24-vac thermostat and will energize the low speed blower when a (G) input has been received at the 24-vac thermostat input connection. When the input is removed the blower will deenergize immediately. Reversing Valve Operation -- DIP switch 4 is used to determine the reversing valve (RV) position in the Cooling mode (deenergized/energized). This function is used only when a 24vac thermostat is used and is determined by the reversing valve output of the thermostat in the Cooling mode. If the thermostat deenergizes the reversing valve in the Cooling mode then set the DIP switch in the "Off" position. If the thermostat energizes the reversing valve in the Cooling mode set the DIP switch in the "On" position. DIP Switch 5 (Corn2 = Off/BacNet (Coml TM DIP Switch 6 (Corn2 modbus address) DIP Switch 7 (Corn2 modbus address) DIP Switch 8 (Corn2 modbus address) Standard or LonWorks(R)) = On!Colmnunicating 24-vac Sequence Thermostat) of Operation RANDOM START DELAY -- When the unit is first powered "On" the control microprocessor will generate a random number to determine the start delay of the compressor operation (3 to 5 minutes). This delay is used to prevent multiple units from cycling "On" at the same time. The purpose is to prevent a large power load on the building electrical system after a power outage. After the number, or delay time, is generated the microprocessor will use this thne to determine the minimum amount of time that must be delayed before the compressor is cycled "On" after a demand is received from the thermostat. START-UP 1. Turn on the line power to all heat pumps. 2. Turn the thermostat fan position to "ON." Blower should start. ANTI SHORT CYCLING DELAY -- After the random start delay is generated the microprocessor will use this time to determine the minimum amount of time that must be delayed before the compressor is cycled "On" after a demand is received from the thermostat. This allows the refrigerant system to equalize in pressure and prevents short-cycling of the compressor. MINIMUM COMPRESSOR RUNTIME -- The minimum compressor mntime of each cycle, heating or cooling, is 60 seconds. Once the compressor is energized it will not deenergize, even if the thermostat input is removed, until the minimum mntime is satisfied. COOLING FIRST STAGE (Y1, O) -- When the microprocessor receives (Y1, O) at the 24-vac thermostat input connection the unit will proceed with the cooling first stage sequence. The microprocessor must receive these signals for 2 continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energjze/deenergize after 5 seconds. 3. Balance airflow at registers. 4. Adjust all valves to their full open positions. Room temperature should be within the minimum-maximum ranges of Table 9. During start-up checks, loop water temperature entering the heat pump should be between 60 and 95 E 5. Two factors determine the operating limits of the 50VS heat pumps: supply-water temperature and the return-air temperature. When any one of these factors is at a minimum or maxhnum level, the other factor must be at a normal level to ensure proper unit operation. a. Adjust the unit thermostat to the warmest setting. Place the thermostat mode switch in the "COOL" position. Slowly reduce thermostat setting until the compressor activates. b. Check for cool air delivery at the unit grille within a few minutes after the unit has begun to operate. NOTE: Units have a 3 to 5 minute time delay in the control circuit that can be eliminated on the microprocessor control board. See test mode described in the DIP Switch Settings and Operation section. The microprocessor will then verify that the anti-short cycling delay has been satisfied. Once the anti short cycling delay has been satisfied the compressor and will cycle "On." The blower will cycle "On" in low speed 15 seconds after the compressor is cycled "On." C. COOLING SECOND STAGE (Y1, Y2, O)When the microprocessor receives (Y1, Y2, O) at the 24-vac thermostat input connection the unit will proceed with the cooling second stage sequence. The microprocessor must receive these signals for 2 continuous seconds before it recognizes the inputs as valid. Once the input signals are determined to be valid the reversing valve will energize/deenergize after 5 seconds. The microprocessor will then verify that the anti short cycling delay has been satisfied. Once the anti short cycling delay has been satisfied the compressor and will cycle "On." The blower will cycle "On" in high speed 15 seconds after the compressor is cycled "On." 19 Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap is filled to provide a water seal. d. Refer to Table 12. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, see Troubleshooting section. e. Check air temperature drop across the air coil when compressor is operating. Air temperature drop should be between 15 and 25 E f. Turnthermostat to"OFF"position. A hissing noise indicates properfunctioning ofthereversing valve. g. Allow 5 minutesbetween testsfor pressure to equalize before beginning heating test. h. Adjustthethermostat tothelowestsetting. Place the thermostat position. mode switch in the Slowly raise the thermostat to a higher temperature until the compressor activates. j. Check for warm air delivery within after the unit has begun to operate. k. Refer to Table 9. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is outside of the operating range, check refrigerant pressures. Check air temperature rise across the air coil when compressor is operating. Air temperature rise should be between 20 and 30 F. in. Check for vibration, Lockout Mode E If the microprocessor board is flashing a system warning and the unit is locked out and not running, the lockout can be cleared from the microprocessor by a momentary shutdown of incoming line voltage (208-vac or 230-vac). A lockout that still occurs after line voltage shutdown means that the fault still exists and needs to be repaired. "HEAT" i. 1. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit performance, reliability, and service life. HIGH-PRESSURE LOCKOUT (HP) -- The high-pressure lockout will occur if the discharge pressure of the compressor exceeds 600 psi. The lockout is ilrnnediate and has no delay from the time the high-pressure switch opens to the lockout. Upon lockout the compressor will be deenergized ilmnediately. The blower will be deenergized 15 seconds after the compressor is deenergized. a few minutes LOW-PRESSURE LOCKOUT (LP) -The low-pressure lockout will occur if the suction pressure falls below 40 psi for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. noise, and water leaks. 6. If unit fails to operate, perform troubleshooting analysis (see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to ensure proper diagnosis and repair of the equipment. 7. When testing is complete, comfort level. set system to maintain FREEZE PROTECTION 1 LOCKOUTThe freeze protection 1 lockout will occur if the liquid line temperature falls below the set point (15 F or 30 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. desired NOTE: If performance during any mode appears abnormal refer to the troubleshooting section of this manual. To obtain maximum performance, the air coil should be cleaned before start-up. Use a coil cleaner for use on indoor evaporator refrigeration equipment. FREEZE PROTECTION 2 LOCKOUT -- The freeze protection 1 lockout will occur if the air coil temperature falls below the set point 32 F for 30 continuous seconds. See DIP switch 2. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. Table 12 -- Temperature Change Through Heat Exchanger CONDENSATE OVERFLOW 1 LOCKOUT (CO1) -The unit contains one condensate overflow sensor located in the chassis drain pan below the air coil. A condensate lockout will occur if the sensor senses condensate for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. OVER/UNDER VOLTAGE PROTECTION -- If the unit control voltage is less than 18-vac or greater than 30-vac the unit will shut down all inputs ilrnnediately. Once the voltage has reached acceptable levels the unit microprocessor will power "On" automatically and resume previous operation. LEAVING WATER TEMPERATURE SENSOR FAILURE (LWT)If the leaving water temperature thermistor fails it will not affect the operation of the unit. This sensor is for monitoring purposes only. DISCHARGE AIR TEMPERATURE SENSOR FAILURE (DAT)If the discharge temperature thermistor fails it will not affect the operation of the unit. This sensor is for monitoring purposes only. FREEZE PROTECTION 1 TEMPERATURE SENSOR FAILURE (FP1) --If the freeze protection 1 thermistor fails for 30 continuous seconds an FP1 lockout will occur. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. The sensor must be replaced if this lockout occurs. FREEZE PROTECTION 2 TEMPERATURE SENSOR FAILURE (FP2) -- If the freeze protection 2 thermistor fails for 30 continuous seconds an FP2 lockout will occur. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. The sensor must be replaced if this lockout occurs. WATER FLOW GPM For Closed Loop: Ground Source or Closed Loop Systems at 3 gpm per ton For Open Loop: Ground Water Systems at 1.5 gpm per ton Operating RISE IN COOLING (°F) DROP IN HEATING (°F) 9-12 4-8 20-26 10-17 Limits ENVIRONMENTUnits are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). POWER SUPPLY -- A voltage variation plate utilization voltage is acceptable. of_+ 10% of name- STARTING CONDITIONSStarting conditions vary depending upon model number and are based upon the following: • • • • Conditions in Table 9 are not normal or continuous operating conditions. Minimuln/lnaximuln limits are start-up conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis. Voltage utilization range complies with ARI Standard 110. Determination of operating limits is dependent primarily upon three factors: a. Ambient b. Return c. When levels, ensure temperature air temperature Water temperature any one of these factors is at lninimum or maximum the other two factors should be at normal levels to proper unit operation. 20 SERVICE check to ensure amp draw is no more than 10% greater than indicated on serial data plate. Evaporator Coil -- The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning. Electrical shock can cause personal iniury or death. When installing or servicing system, always turn off main power to system. There may be more than one disconnect switch. Use caution when cleaning the coil fins as the fin edges are extremely sharp. Failure to heed this warning could result in personal iniury. The installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Cabinet _ The cabinet can be cleaned using a mild detergent. Do not allow water to stay m contact with the cabinet for long periods of thne to prevent corrosion of the cabinet sheet metal. Water Coil Maintenance Refrigerant System -- To maintain CLOSED LOOP SYSTEM (All Other Water Loop Applications) -- Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treatment and mineral build-up through water use can also contribute to higher maintenance. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. However, flow rates over 3 gpm per ton can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks. sealed circuit integrity, do not install service gages unless unit operation appears abnormal. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit. TROUBLESHOOTING Lockout Modes _ If the microprocessor board is flashing a system warning and the unit is locked out and not running, the lockout can be cleared from the microprocessor by a momentary shutdown of incoming line voltage (208-vac or 230-vac). A lockout that still occurs after line voltage shudown means that the fault still exists and needs to be repaired. HIGH-PRESSURE LOCKOUT (HP) -- The high-pressure lockout will occur if the discharge pressure of the compressor exceeds 600 psi. The lockout is ilr_nediate and has no delay from the time the high-pressure switch opens to the lockout. Upon lockout the compressor will be deenergized ilmnediately. The blower will be deenergized 15 seconds after the compressor is deenergized. OPEN LOOP SYSTEM (Direct Ground Water) -If the system is installed m an area with a known high mineral content (125 ppm or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. Therefore, 1.5 gpm per ton is recolr_nended as a minhnum flow. Minimum flow rate for entering water temperatures below 50 F is 2.0 gpm per ton. LOW-PRESSURE LOCKOUT (LP) -The low-pressure lockout will occur if the suction pressure falls below 40 psi for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. FREEZE PROTECTION 1 LOCKOUT -- The freeze protection 1 lockout will occur if the liquid line temperature falls below the set point (15 F or 30 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. Filters -- A clean filter must be used to obtain maximum performance. Filters should be inspected every month under normal operating conditions. It is especially flnportant to provide consistent washing of these filters (in the opposite direction of the normal airflow) once per month. Never operate a unit without a filter, severe system damage can occur. FREEZE PROTECTION 2 LOCKOUT -- The freeze protection 2 lockout will occur if the air coil temperature falls below the set point (32 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. Condensate Drain- In areas where airborne bacteria may produce an algae build-up in the dram pan, it may be necessary to remove and treat the drain pan chemically with an algaecide approximately every three months to minimize the problem. The condensate pan may also need to be cleaned periodically to ensure indoor air quality. The condensate dram can pick up lint and dirt, especially with dirty filters. Inspect the dram twice a year to avoid the possibility of plugging. CONDENSATE OVERFLOW 1 LOCKOUT (CO1) -The unit contains one condensate overflow sensor located in the chassis drain pan below the air coil. A condensate lockout will occur if the sensor senses condensate for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. OVER/UNDER VOLTAGE PROTECTION -- If the unit control voltage is less than 18-vac or greater than 30-vac the unit will shut down all inputs ilr_nediately. Once the voltage Compressor _ Conduct annual amperage checks to insure that amp draw is no more than 10% greater than indicated on the serial data plate. Fan Motors odic maintenance dirt accumulating failure. Conduct _ All units have lubricated fan motors. Perioiling is not recolmnended, as it will result in in the excess oil and cause eventual motor annual dry operation check and amperage 21 hasreached acceptable levels,theunitmicroprocessor will power onautomatically andresume previous operation. LEAVINGWATERTEMPERATURE SENSOR FAILURE(LWT)-- If theleavingwatertemperature thermistor fails,it willnotaffecttheoperation oftheunit.Thissensor is formonitoring purposes only. DISCHARGE AIRTEMPERATURE SENSOR FAILURE (DAT)-- If thedischarge temperature thermistor fails,it will notaffecttheoperation oftheunit.Thissensor isformonitoringpurposes only. FREEZEPROTECTION 1 TEMPERATURE SENSOR FAILURE(FP1)--If thefreeze protection 1thermistor fails for 30continuous seconds anFP1lockoutwill occur.The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. The sensor must be replaced if this lockout occurs. FREEZE PROTECTION 2 TEMPERATURE SENSOR FAILURE (FP2) -- If the freeze protection 2 thermistor fails for 30 continuous seconds an FP2 lockout will occur. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. The sensor must be replaced if this lockout occurs. If unit performance during any mode appears abnormal, refer to Table 13. Table 13 -- Troubleshooting SYSTEM WARNING (FLASH) LED1 LED2 LED3 LED4 SYSTEM LOCKOUT (STEADY ON) LED1 LED2 LED3 LED4 POSSIBLE Er 1 OFF OFF OFF FLASH OFF OFF OFF ON Low Airflow (Heating), Low Water Flow (Cooling) Er 2 OFF OFF FLASH OFF OFF OFF ON OFF Low Refrigerant Charge Er 4 OFF OFF FLASH FLASH OFF OFF ON ON Water Temperature < 35 F or < 15 F (Heating) FAULTDESCRIPTION ERROR CODE (COMMTSTAT) High Pressure Lockout < 600 psi Low Pressure Lockout < 40 psi Freeze Protection, Side Air Freeze Protection, Side < 35 F Air FAULT CAUSE Er 5 OFF FLASH OFF OFF OFF ON OFF OFF Blower Failure (Cooling) Condensate Overflow Er 9, Er 10 OFF FLASH OFF FLASH OFF ON OFF ON Clogged Drain Line Over/Under Low Voltage Protection, 18-vac > voltage, 30-vac Er 11 OFF FLASH FLASH OFF OFF ON ON OFF Loss of Power, Brown Out Er 13 FLASH OFF OFF OFF N/A N/A N/A N/A Sensor Resistance Above or Below Specification Er 14 FLASH OFF OFF FLASH N/A N/A N/A N/A Sensor Resistance Above or Below Specification Er 15 FLASH OFF FLASH OFF ON OFF ON OFF Sensor Resistance Above or Below Specification Er 16 FLASH OFF FLASH FLASH ON OFF ON ON Sensor Resistance Above or Below Specification LWT Sensor Failure (Low Water Temperature) DAT Sensor Failure (Discharge Air Temperature) FP1 Sensor Failure (Freeze Protection) FP2 Sensor Failure (Freeze Protection) LEGEND LED -- Light-Emitting Diode NOTE: Warning LEDs and error codes are found on the system control board. Copyright 2008 Carrier Corporation Manufacturer reserves the right to discontinue, Catalog No. 04-53500046-01 Printed in U.S.A. or change at any time, specifications or designs without notice and without incurring obligations. Form 50VS-1Sl Pg 22 11-08 Replaces: New START-UP CHECKLIST CUSTOMER: JOB NAME: MODEL NO.: SERIAL NO.: DATE: PRE-START-UP DOES THE UNiT VOLTAGE CORRESPOND HAVE THE POWER AND CONTROL TIGHT? (Y/N)_ HAVE WATER CONNECTIONS (Y/N) __ HAS PUMP BEEN TURNED HAS CONDENSATE WITH THE SUPPLY VOLTAGE AVAILABLE? WIRING CONNECTIONS (Y/N) BEEN MADE AND TERMINALS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? ON AND ARE ISOLATION CONNECTION IS AN AIR FILTER INSTALLED? VALVES OPEN? (Y/N) __ BEEN MADE AND IS A TRAP INSTALLED? (Y/N) __ (Y/N) __ II. START-UP IS FAN OPERATING IF 3-PHASE (Y/N) __ WHEN COMPRESSOR SCROLL COMPRESSOR OPERATES? (Y/N) __ IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS. UNIT VOLTAGE -- COOLING OPERATION PHASE AB VOLTS PHASE BC VOLTS (if 3 phase) PHASE CA VOLTS (if 3 phase) PHASE AB AMPS PHASE BC AMPS (if 3 phase) PHASE CA MPS (if 3 phase) CONTROL VOLTAGE IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? IF NOT, CHECK FOR PROPER TRANSFORMER (Y!N) __ CONNECTION. TEMPERATURES FILL IN THE ANALYSIS COAXIAL HEAT EXCHANGER AIR COIL CHART ATTACHED. COOLING CYCLE: FLUID IN F FLUID OUT F PSI FLOW HEATING CYCLE: FLUID IN F FLUID OUT F PSI FLOW COOLING AIR IN CYCLE: F AIR OUT F HEATING AIR IN CYCLE: F AIR OUT F CL-1 HEATING CYCLE ANALYSIS PSI _\\\ __ SAT \\ oF \\\\\\ ,:", AIR ,_ \\COIL\\ oF SUCTION \\\\\\ \\\\\\ \ oF \ \ \ 7 _ , COMPRESSOR \\\\\\ EXPANSION VALVE , \ \ \ \ DISCHARGE \ \\\\\\ \\\\\\ \\LJ t oF LIQUID LINE °F PSI WATER IN COOLING CYCLE o F __PSI WATER OUT iii Z -7 ¢h iii i-i-o ¢h (D Z ANALYSIS o, < i-__ \\\\\, \\ PSI __ SAT o oF \\\\ x\\\\\ AIR _COILO SUCTION oF oF COMPRESSOR _\\\\\ _\\\\, EXPANSION VALVE ,\\\\\ DISCHARGE ,\\\\, x\\\\\ _\\\\\ _\\\\\ iii Z -7 t _'F LIQUID LINE ¢h iii i.°F PSI WATER IN HEAT OF EXTRACTION (ABSORPTION) FLOW RATE (OPM) x 6 __?F ¢h (D __PSI WATER OUT OR HEAT OF REJECTION TEMP. DIFF. (DEO. F) x Z o, < i-- = FLUID FACTOR* = (Btu/hr) SUPERHEAT SUBCOOLING = SUCTION TEMPERATURE = __ (DEG F) - SUCTION = DISCHARGE SATURATION = __ (DEG F) SATURATION TEMPERATURE TEMPERATURE - LIQUID LIN_ TEMPERATURE *Use 500 for water, 485 for antifreeze. Copyright 2008 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500046-01 Printed in U.S.A. Form 50VS-1 SI Pg CL-2 11-08 Replaces: New
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 24 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Fri Feb 12 04:30:53 2010 Author : Title : Subject :EXIF Metadata provided by EXIF.tools