CARRIER Air Conditioner/heat Pump(outside Unit) Manual L1002284
User Manual: CARRIER CARRIER Air conditioner/heat pump(outside unit) Manual CARRIER Air conditioner/heat pump(outside unit) Owner's Manual, CARRIER Air conditioner/heat pump(outside unit) installation guides
Open the PDF directly: View PDF .
Page Count: 26
Download | ![]() |
Open PDF In Browser | View PDF |
® to the Expertg rll Installation Instructions SAFETY Improper installation, CONSIDERATIONS adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual packaged with the kits or accessories when installing. 40QAC, QAQ instructions Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. []nit Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1. Recognize When safety you see information. This is the safety-alert this symbol on the unit symbol and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal practices injury which or death. CAUTION is used to identify unsafe would result in minor personal injury or product and property damage. NOTE is used which will result in enhanced installation, 38HDR, NOTE: Read installation. the entire QRR instruction ELECTRICALSHOCK []nit manual before starting the Failure to follow injury or death. to highlight suggestions reliability, or operation. HAZARD this warning could result Before installing, modifying, or servicing electrical disconnect switch must be in personal system, in the position. There may be more than 1 disconnect Lock out and tag switch with a suitable warning []NIT OPERATION AND SAFETY main OFF switch. label. HAZARD Failure to follow this warning could result in personal injury or equipment damage. Puron refrigerant systems operate at higher pressures than standard R-22 systems. To avoid damage to the unit or possible personal injury, do not use R-22 service equipment or components on Puron refrigerant equipment. PERSONAL HAZARD INJURY AND Failure to follow this caution and / or equipment damage. DO NOT removed. operate the unit EQUIPMENT may result without DAMAGE in personal a filter or with injury grille DIMENSIONS - INDOOR NOTES: 1. Dimensions in [ ] are in millimeters. 2. _ Direction of airflow. 3. Standard unit clearances are as follows: • 0 in. on tou and rear • 3 in. on left side • 12 in. on riqht side • 36 in.on bottom (When facing unit discharge.) [254] "-4" [102] O" 2 11116" [881 ....... [214_ REAR VIEW I --- 0"-10" I _ -%2_Y'31 [19O] ..... 0"-77/[B'_ | HIGH 0'-1 [ I [t_'T_,_ _ VOLTAGE KNOCKOUT 5/8" _0'-1 [42] I--°- BOX ; -----I CONTROL .......................................................................................... II i I I $ G- [102] _ _ / ) { /" \ F___]__I 0"_-5 11 [ I 0"-4" '4* 11116" [42] 1 I \ P" I/8" [130] )I _/ k CONDENSATEPUNPA3[SE UIR\\ ........ AoLR EY.F:A2E. \ / o.8.O, ON, (20" MAX. LIFT) 0"-3 5/8" LOW VOLTAGE TO OUTDOOR UNIT _ 0'-4 _-_ _;:I 7/8" I _\\-_-_--L::F::;RANT ]I L_ ____ _ AND THERMOSTAT _, pIp IN° CONN . (VAPOR SIDE) _8;_?LE PLARE (018, 024) 3/4"MALE FLARE(036,048,OEO) _O3/_NNpAIPING CONN, (3/4. HALE / _ POWER B NFT) VENTILATION ACCESSORY DUCT RING [131] -- REVERSE BRACKETS FOR L OPT IONAL CONCEALED MOUNTING (4)MOUNTING BOLT HOLES POWER VENTILATION ACCESSORY MINIMUM 0'-3 _ [763 CLEARANCE REOUIRED IN BACK OF UNIT V--_- {- O' -1/2 _ X 1 LONG 0'-1 1/4" TOP POWER-'/ ENTRANCE KNOCKOU] _0'-2 [69] I [I72] _-,-II_I[ L tl/]6" TOP ACCESS FOR WIRING, REFRIGERANT g ACCESSORY CONDENSATE DRAINAGE [OPTIONAL) I I ACCESS TO CONDENSATE PUHP THRU SIDE PANEL [2783 8 E A 0"-8/16" -_7 [253] 0"-6 VIEW '-4" !! o'-11L J FRONT [291 B VIEW [8] O' - 10 _ [254] 4_/4 ° 1t093 ALTERNATE TOP 1/8" ............................................... rlO.q DIA 0"-1 9/16" [I87] AUTOMATIC AIR SWEEP LOUVERS _ A08580 UNIT SIZE 024 036 048 060 WEIGHT Cooling Only 108 117 149 179 (Ib) Heat Pump 110 119 151 181 B A if-in, mm 4-215/16 4-1013/16 5-119/16 7-8 1294 1493 1817 2336 if-in, 3-10 4--57/8 5--65/8 7--3 Fig. 1 - 40QA E F mm if-in, mm 1169 1368 1692 2211 4-15/8 4--91/2 5--101/4 7--65/6 1260 1459 1783 2302 Dimensions if-in, --1 --97/8 1 -- 115/6 mm --555 601 if-in. 1-95/8 2--11/2 3--31/16 4-- 119/16 mm 549 648 992 1512 UNIT SERIES 38HDRO18 38HDRO24 38NDR030 38NDR036 38HDRO48 38NDRO60 I 1.2 t I 1,2 1,2 ELECTRICAL CHARACTERISTICS x 0 0 0 X x 0 0 0 0 0 0 x x o o x I x I I x x XlOlXlX 6 ('0 04 '-9, "T', 0 ,_ 6 (_0 04 eb 0 A B Z5 31 37 37 I18" 1/8" 3116" 3/16" 4_ 3/16" 36 36 44 44 44 43 3116" C 15116" 15/16" 9116" 91t6" 9/161 44 9116" D E 14 14 17 17 9116" 9/16" I116" 1/16" 16" 16" 18 7116" 18 7/16" 17 1/161 18 17 I116" Z3 23 30 30 T116" 7116" T/16" IIZ" 1/2" 30 18 7/16" F I/Z 17 17 19 19 19 I 30 IIZ" 3116" 3/16" 518" 5/8" _181 19 518" G 17 23 29 29 3S H J 118" 1/8" 3/16" 3/16" 22" 28" 34 I116" 34 1/16" _/161 40 35 3/16" 1/161 40 I116" K 13" 14" 13 11116" 13 11/16" 14 I/Z I 14 IIZ" L M 6 6 8 B 518" 3/4" 118" 1/8" 11 11 t5 t5 I14" 5/8" 7/8" 7/8" 8 I/Z 18 7/S I 8 I12" 518" 5/8" 314" 314" I 18 7/8" N 2 2 3 3 15116" 15116" 7/16" 7/16" 718" 3 718" 3 7/16" 7/16" OPERATING SHIPPING SHIPPING WEIGHTIIbsl WEIGHTllbs) DIMENSIONS (L x W x H) P 6" 6" 6 I12" 6 1/2" 155 180 ZOO 218 6 Z8J IIZ" 6 I12" 171 198 223 240 309 319 294 429110-x 18-x 281/1042 9110" 50 1/2" X 50 1/2" X SO 112" X 50 1/2" X X 20 20 20 20 REOUIRED CLEARANCES: WITH COIL rACING WALL; ALLOW G" MIN CLEARANCEON COIL SIDE AND COIL END AND 3G" MIN CLEARANCE ON COMPRESSOREND AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN CLEARANCEON FAN SIDE AND COIL END AND 36" MIN CLEARANCE ON COMPRESSOREND AND COIL SIDE. WITN MULTI UNIT APPLICATION; ARRANGEUNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER. x : YES 0 : NO , o 2. lAIR p MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F. MAX. 125°F. 3, SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER, E 4, CENTER OF GRAVITY_ I 1/2" f 2 1/2" _--'_L LIL, 5 ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. 4 3/16- t ' UNITSI_ K lAIR 18,24 30,36,48.60 J_ JUNCTION 80X FOR POWERSUPLLY AND 1 7111 V L 18" X 34 1/10" 1/2" X 40 2/10" 1/2" X 40 2/10" 1/2" X 4G 2/10" 1/2" X 46 2/10" CONTROL CONNECTIONS ! H'"'"''"'"'"" ......... re,,, _ J r FIELD CONTROL SUPPLY""-----.... WIRE ENTRY 7/8" HOLE W/GROMMET _t A /-_M VAPOR LINE CONN. FEMALE SWEAT CONN. 1 1/2" 0 L B. t HI _-_3/8" LIOUID 1 LINE 1" FEMALE SWEAT CONN, Fig. 2 - 38HDR Outdoor Unit Dimensions L 4 I12" - English MOUNT_ PAD D_ 23" X 42" 24" X 50" POWERSUPPLY CONN. HOLE SIZES PROVIDED: 718"-1/?"TRADE 1 3/1G"-314"TRADE 1 318"-1"TRADE EL_ CHARACll_ UNIT 38HDR018 38HDR024 38HDR030 38HDR036 38HDR048 38HDR060 I 1,2 I I 1.2 1,2 x x x O O O O O OIO x x o o XlX XlX XlOlXIX O O A B C D E F G H J K L M N p 638.2 790.6 944,6 944.6 t097.0 1097,0 938.2 938,2 1t3t.9 1131.9 1t31.9 1131_9 369.9 369,9 433,4 433.4 433.4 433,4 406,4 406.4 4G8.3 468.3 468,3 468,3 595.3 595.3 774,7 774.7 774.7 774.7 436,6 436.6 498,5 498.5 498.5 498,5 435.0 587.4 741,4 741.4 893,8 893,8 558,8 711.2 865.2 865.2 1017,G 1017,G 330.2 355.6 347.7 347.7 368,3 368,3 t68,3 171,5 20G.4 206.4 215,9 215,9 285,8 295.3 403.2 403.2 479,4 479.4 15,9 15,9 19.0 19.0 22,2 22,2 74,6 74_G 87.3 t52.4 152.4 tG5.t 87.3 87,3 87.3 0PB_ATING _ WBQHT'_G)int0t.mKO)Dt,ABVSK3NS L x Wx 70,4 81.8 90.9 77,7 90,0 101.4 1090,2 X 457,7 X 714,3 1090.2 X 457,7 X 8GG,7 1282.7 X 520.7 X 1020,7 165.1 99.0 109.0 12B2.7 x 520.7x 1020.7 t65.t t29,0 140,4 1282,7 165.1 t33,6 145.0 1282,7x 520.7x 1173.1 X 520,7 REOUIREDCLEARAHCES: WITH COIL FACIHG WALL; ALLOW152,4 XIH CLEARANCEON COIL SIDE AND COIL END AND 914,4 MIN CLEARANCE OH GOMPRESSOREHD AND FAH SIDE, WITH FAN FACING WALL; ALLOW203.2 MIN CLEARANCEON FAN SIDE AND COIL END AND 914,4 MIN CLEARANCE ON COMPRESSOREHD AND COIL SIDE. WITH MULTI UNIT APPLICATION; ARRANGEUNITS SO DISCHARGEOF ONE DOES NOT ENTER INLET OF ANOTHER, X = YES O: NO lAIR 2, MINIMUM OUTDOOROPERATING AMBIENT [H COOLING MODE IS 12._C. MAX. 51.?C. LL I 3. SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODELNUMBER, 4, CENTEROF GRAVITY_ 190,5_ I!!/1 I 5, ALL DIMEHSIONS ARE IN "MM" UNLESS NOTED. uNrr sizz F t- t 18.24 K 30,36.48,60 1 175 36.5-" CONTROLCONNECTIONS • '"'"'".................... ' ,I f FIELD CONTROLSUPPLY_ WIRE ENTRY 22.22 HOLE W/GROMMET 38,1 D A H _M FEMALE SWEATCONN. VAPORLINE CONN. GI/ ] l "L r FEMALESWEATCONN. Fig. 3 - 38HDR Outdoor Unit Dimensions - SI MOUNTING PAD 584.2 X t066.8 609,6 X 1270,0 FIELD POWERSUPPLYCONN. HOLE SIZES PROVIDED: 22.22 - 12.70 TRADE 30,16 - 19,05 TRADE JUNCTION BOX FOR POWERSUPLLY AND B I I X 1173,1 1 34.92 - 25.40 TRADE E_C_CAL UNIT 5B_IESCHARACT_S_CS 38QRR018 38QRRO24 38QRR030 38QRRO36 38QRR048 380RR060 0 0 0 0 0 0 x 0 0 XlOlOlO X X X 0 0 0 010 xlx XlX Xl°lXIN 0 A 25 31 37 37 43 43 1/8" I18" 3116" 3116" 3116" 3116" B 36 36 44 44 44 44 t5/t6" 15116" 9116" 9116" 9116" 9116" C 14 14 17 17 17 17 9/16" 9116" 1116" 1116" 1116" 1116" D E t6" 16" 18 7116" 18 7116" 18 7116" 18 7116" 23 23 30 30 30 30 7/16" 7116" 112" 112" 112" 112" F G 17 3/16" 17 3116" 19 518" 19 518" 19 518" 19 518" t7 23 29 29 35 35 1/8" I18" 3116" 3116" 3116" 3116" H J 22" 28" 34 1116" 34 1116" 40 1116" 40 1116" 13" 14" 13 11116" 13 11116" 14 112" 14 112" K 6 6 8 8 8 8 L 5/8" 314" 118" 118" 112" 112" 1t 11 15 15 18 18 1/4" 518" 718" 718" 718" 718" M N 5/8" 518" 314" 314" 718" 718" 2 2 3 3 3 3 P 15!16" 15116" 7116" 7116" 7116" 7116" 6 6 6 6 6" 6" 112" 112" 112" 112" OPB_ATING SHIPPING SHIPPING WBGHTabs) WBGHTllbs) DIMB_ISIONS (L x W x HI 167 183 429110.x_o,,x 28ino" 176 187 232 278 306 194 210 255 303 331 42 9/10" 50 1/2" X 50 1/2" X 50 t/2" X 50 112" X X 20 20 20 20 18" X 34 1/10" 1/2" X 40 2/10" 1/2" X 40 2/10" t/2" X 46 2!10" 112" X 46 2110" REOUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6" MIN CLEARANCE ON COIL SIDE AND COIL END AND 36" MIN CLEARANCE ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN CLEARANCE ON FAN SIDE AND COIL END AND 36" MIN CLEARANCE ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION; ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER. X : YES 0 : NO 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55°F, MAX. 125°F. IAIR 3, SERIES DESIGNATION IS THE 13TH POSITION OF THE UNIT MODEL NUMBER, 4, CENTER OF GRAVITY_ 5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED. T I _IhlIVlUM UMT SITW MOUNTINGPAD DIMB_ISIONS F f 18,24 30,36,48,60 K I 23" X 42" 24" X 50" l IAIR JUNCTION BOX FOR POWER SUPLLY AND CONTROL CONNECTIONS o F-i FIELD CONTROL SUPPLY_---_ WIRE ENTRY 718" HOLE WIGROMMET _t I VAPOR LINE CONN, FEMALE SWEAT CONN, 1/2" [] G ,1 L 8" LIOUID LINE MALE FLARE CONN. Fig. 4 - 38QRR Outdoor Unit Dimensions - English POWER SUPPLY CONN, HOLE SIZES PROVIDED: 718"-II2"TRADE 1 3116"-314"TRADE 1 318"-I"TRADE B.ECTRICAL UMT SB:IIES CHARAC'I'B_ISTICS 380RR018 380RR024 380RR030 380RR036 380RH048 380RR060 0 0 0 0 0 0 x 0 0 0 x x x x 0 0 0 0 0 0 x x 0 0 x x I I I 638.2 790.6 944.6 944.6 1097,0 1097.0 XlOlXlX o B C 938.2 938.2 1131,9 1131.9 1131.9 1131.9 369.9 369.9 433,4 433.4 433,4 433.4 D 406.4 406.4 468.3 468.3 468.3 468.3 E F 595.3 595.3 774,7 7?4.7 774.7 774.7 436.6 436.6 498,5 498.5 498,5 498.5 G 435.0 587.4 741.4 741.4 893.8 893.8 H J 558.8 711.2 865.2 865.2 1017.6 1017,6 330.2 355.6 347,7 347.7 368.3 368,3 K 168.3 171.5 206,4 206.4 215,9 215.9 L M 285.8 295.3 403.2 403.2 479.4 479.4 15.9 15.9 19.0 19.0 22.2 22.2 8 I. X : YES 0 : NO N P 74.6 74.6 87.3 87.3 87.3 87.3 152.4 t52.4 165.1 165.1 t65.1 165.1 OPERATINGSI-IPRNG SHIPPING WBOHT(KO) WBGHT(KO) DIMB_51ONG (L x W x H) 75.9 80.0 85.0 105,4 126.4 139.0 83.2 88.2 95,4 115.9 137.7 150,4 1090.2 1090.2 1282.7 1282.7 1282,7 1282.7 X X X X X X 457.7 457.7 520.7 520.7 520.7 520.7 X X X X X X REOUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152,4 MIN CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE ON COMPRESSOR END AND FAN SIDE, WITH FAN FACING WALL; ALLOW 203,2 MIN CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION; ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER. MINIMUM OUTDOOROPERATING AMBIENT IN COOLING MODE IS 12.8°C, MAX. 51.7°C. I 2. SERIES DESIGNATION UNIT MODEL NUMBER. E IS THE 13TH POSITION OF THE 4. CENTER OF GRAVITY_ 190,5 F !!r'll 63.5 5, F ALL DIMENSIONS UNIT SI2_ 106.4 t I 18,24 K IAIR 30.36,48,60 ARE IN "MM" UNLESS NOTED. MINIMUM MOUNTING PAD DIIVlB_51ONS 584,2 X 1066.8 609,6 X 1270.0 J uu' FFIELD /HOLE /22,22 /30.16 JUNCTION BOX FOR POWER SUPLLY AND - CONTROL CONNECTIONS B o 38.1 o VAPOR LINE CONN. FEMALE SWEAT CONN, @ T [] L G t r ° _.L._u q LIOUIDLINE MALE FLARE CONN. Fig. 5 - 38QRR Unit Dimensions 1 203.2 114.3 25,4 Outdoor 36.5 _ _/34.92-25.40TRADE .I/ FIELD CONTROL SUPPLY_------_ WIRE ENTRY 22.22 HOLE WlGROMMET - SI 714.3 866.7 1020,7 1020.7 1173,1 1173.1 POWER SUPPLY CORN, SIZES PROVIDED: - 12.70 TRADE - 19.05 TRADE These installation systems listed Parts List Indoor The instructions in table cover the installation of the matched 2. Table System Type Unit following items are included Table with the indoor I - Installation unit: == ""5 o O Materials Part No. 1 2 Name of Part Side Panels Hex Head Bolts Qty. 2 4 3 4 Mounting Bracket Pistons 2 1 5 6 Installation Template Adapter Tubes 1 2 2 - Matched Nominal Capacity Systems Outdoor Unit Indoor Unit 018 38HDRO18---3 40QACO24. - -3 024 38HDR024---3 40QAC024---3 030 38HDR030---3 40QAC036---3 036 38HDR036---3/5/6 40QAC036---3 048 38HDRO48- - -3/5/6 40QACO48- 060 38HDRO60- - -3/5/6 4OQACO6O- - -3 - -3 018 38QRRO18---3 40QAQO24---3 _. 024 38QRRO24- 40QAQO24- _= 030 38QRRO30---3 - -3 - -3 40QAQO36---3 iD. :'r MOUNTING SLOT 036 048 38QRRO3638QRRO48- - -3/5/6 - -3/5/6 40QAQO3640QAQO48- 060 38QRRO60- - -3/5/6 4OQAQO6O- - -3 Units must be configured on page 9. for 1-1/2 SYSTEM ton operation. - -3 - -3 Refer to instructions REQUIREMENTS Clearances Allow sufficient space around the indoor proper airflow circulation and servicing. Fig. 5 for minimum required clearances, HEX-HEAD BOLT Piping: Piping PiDin_ Lengths The minimum A09532 Fig. 6 - Hanging Fan Coil Unit (3 m). and insulation length between Outdoor Unit The following items are included with the outdoor u-FILTER unit: / unit for to Fig. 1 through is field supplied, the indoor Refer to table 3 for the maximum Table 3 - Maximum and outdoor Refer and outdoor lengths Refrigerant units is 10 fl allowed. Line Lengths Unit Size Max Line Length if(m) Max Elevation (ID over OD) if(m) Max Elevation (OD over OD) if(m) 18K 24K 200 (61) 200 (61) 65 (19.8) 65 (19.8) 200 (61) 200 (61) 3OK 36K 200 (61) 200 (61) 65 (19.8) 65 (19.8) 200 (61) 200 (61) 48K 6OK 200 (61) 200 (61) 65 (19.8) 65 (19.8) 200 (61) 200 (61) Note:For lengths greater than 25 ft (7.6 m), refer to the Duct Free Long Line Guide. Pipe Sizes Refer to table A09536 4 for pipe sizes. Table Fig. 7 - 38HDR018-036 _F PISTON HEATING PISTON CAP __ET_ERE_I_/--FLARE FILTER /--/DRIER _._LINE !(BY SET OTHERS) HEATING A09537 Fig. 8 - 38QRR018-036 Model Filter Drier 38HDR 38QRR _" w- Piston Cap w- 4 - Pipe Sizes PIPE SIZES (in) Pistons w- Flare Connector w- Unit Size Liquid Phase 18 24 30 36 48 60 3/8 3/8 3/8 3/8 3/8 3/8 Vapor 38HDR 5/8 5/8 3/4 3/4 7/8 7/8 38QRR 5/8 5/8 3/4 3/4 3/4 3/4 Note:On heat pumps, both lines need to be insulated using at least 1/2 inch closed foam insulation. Refriuerant Charge Power and Connecting Power: The 38HDR and 38QRR units can be matched with multiple outdoor units and thus additional charge might be required when matched with the 40QAC or 40QAQ units. Table 5 - Additional Additional • The main power is supplied to both the indoor and outdoor units. Charge Unit Size Charge 38HDR 018 024 030 036 048 060 0.7 (0.32) 1.3 (0.59) 1.4 (0.64) 0.2 (0.1) 0.2 (0.1) 0.5 (0.23) • Consult local building codes, NEC (National Electric Code) or lb. (kg.) CEC (Canadian Electric Code) for any special requirements. • Use Table 7 for the electrical requirements for the outdoor units 38QRR 0.7 (0.32) 0.8 (0.36) 0 0.5 (0.23) 0 0 and Table 8 for the indoor units to correctly size the cables and disconnect switches. Control Wiring Thermostat Note:The above additional charge is required amount for line lengths up to 25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will be required. Refer to the Duct Free Splits Long Line Guide. indoor the Metering Device The 40QAC and 40QAQ units use an accurator or a TXV as shown in Table 6. Cooling Only 40QAC TVX TVX TVX TVX TVX TVX 018 024 030 036 048 060 NOTE: Pistons are supplied with either the indoor or outdoor Table units 18 AWG User Interface the Heat Pumps only be units. used for A two and control wiring conductor a seven conductor is recommended between the is required for is required on cable for cable any length of the type following of system 9 to select - Finished three on hand the proper thermostats and the can desired be used depending features. Refer thermostat. units. / QRR Electrical Requirements 38QRR UNIT SIZE V-PH-Hz 018 208/230-1-60 12.1 20 12.1 20 024 208/230-1-60 17.7 25 18.8 30 030 208/230-1-60 19.1 30 17.5 30 208/230-1-60 19.1 30 20.9 30 208/230 -3 -60 13.0 20 14.1 20 460-3 -60 7.9 15 7.9 15 208/230-1-60 26.4 40 34.6 50 208/230-3 17.9 25 22.4 30 8.4 15 10.0 15 208/230-1-60 34.5 60 34.5 60 208/230 -3 -60 21.5 30 23.6 40 10.6 15 10.6 15 048 MIN CKT AMPS -60 460-3 -60 060 460-3-60 Table UNIT 8 - 40QAC VOLTAGE V-Ph-60 Hz / QAQ FUSE/HACR AMPS Electrical BKR MIN CKT AMPS FUSE/HACR BKR AMPS Requirements 40QAC 40QAQ MCA MOCP MCA MOCP 024 208/230-1 0.63 15.0 9.29 15.0 036 208/230-1 1.60 15.0 17.70 20.0 048 208/230-1 2.00 15.0 23.80 25.0 060 208/230-1 3.30 15.0 28.70 30.0 Table 9 - Thermostat Selection System Type Model Number Cooling Only & HP 53DFS250-SL Cooling Only 53DFS250-FS Cooling Only 53DFST2-NP 7 Day Programmable = #_ 5+1 +1 Day Programmable Remote Room Sensor _/ Dry Contact Equipped _/ - on to Table 38QRR 40 43 55 63 73 80 7 - 38HDR ft Goods Accessory 38HDR 036 up to 200 (61.0 m). Sizes 40QAQ 49 55 65 70 80 TXV should outdoor pumps, Any Unit Size wires and cooling heat Table 6 - Accurator Cables - Field Supplied Operating INSTALL Range Ensure that the system operates shown in the following tables. Cooling operating the application guidelines Plan the installation Indoor Unit (35) operating (21.7) (19.4) cessory Indoor Unit 2. Remove the indoor down and perform (13.9) a. Remove Minimum DB WB °F (°C) °F (°C) -20 a power (19.4) 80 (26.7) 71 (21.7) 55 (12.8) accessories is available the unit adja- ventilation unit from the carton the following kit ac- side panels and place it upside steps: by sliding forward, then away from See Fig. 9. [4721 ; 3/16" LOOSEN BOLTS AND SLIDE- "_3Js"_J HOUNTIBG BRACKET THIS OIRECIION_TO RENOVE 2 I/8 ,4 (23.9) place is available. sides of the unit. Maximum DB WB °F (°C) °F (°C) 75 67 you begin. If possible, wall and fresh air is required, range: Outdoor Unit before unit location. cent to an outside wall if fresh air is required, and ensure that the location allows for complete air distribution. NOTE: If unit is not installed adjacent to an outside Minimum DB WB °F (°C) °F (°C) 55 (12.8) 67 57 Maximum DB WB °F (°C) °F (°C) 128 (51.7) 95 71 UNIT carefully 1. Select indoor range: Outdoor Unit Heating within INDOOR (-28.9) )[3_8 4_2_i. 314" _4 Accessories An extensive list of field installed for both indoor and outdoor units. Identify what accessories, if any, are required for the application at hand and consult the separate installation instructions for the accessories. Some of the 'L'OE 'BE,,EL T.',J //i/ BIRECTION_TO (LIQUID accessories, especially on the indoor easier if planned ahead. units, can be installed much SIDE) _WPOB SIBE_/ R,EMOVABLE / REHOVE AIR FILTER / _ F, ,,,B. --L,. i _ : \.,.,...ooE_ NEC LU= .I." I "d6* _, 8LK 230_' 048,0 _L_, L_L_J THER" O,____T AT ( N_)ENSATE I>JNP A{;tE SORY _S i_ TRAI _ NOTE ? 0_2 IFM? C O['LY _EPO'/E '_HEN _CCE;SO Y IS U',E --4HT_WHT TBf TB PL[ .... !YE S WH c_ PL2 -----t -- _ T_4 ' ALTERN#TE T'STAT ,4/AIR ,WEE> F J[' ±CITOR CONTROL RELAY DEFI@ T IELAY EQUII .GN). E_UII :"El T POUiD F>T FREEZE PROTECTI(N THE_MO F! FAN _ELAY FU FUE :_> 2. bI!E [[, ACCORDANCE _ITH ATION#L ELECTRICALCOlE .E.C. AN[} LOCAL{:ODES. 3. TRAnSFORmER IS THERMALLYP_OTECTEt A_D WILL RESET AUTOMATICALLY IFM{S} ARE I_HERE_TLY THERmaLLYPROTECTEd. S. USE COPPERCONDUCTOr, S ONLY. _. WHENUSI_S THE_I_OSTATWITH AIR SWEEPFdNCTION: ¸YELLOW WIRE FRO_ _3 TO BE CONNECTED TO _SRI. BL_¢I. _ WIRE TO BE _I_;(:r)N_4ECTE_) FROM_SR_. LEA/E ISLe'OKWIRE TIE W_>I_E[} TO YELLOWWIRE. sLeeK FACTOR_ AS_ NOTE5 CLARKE DELAY TAT COMPONENT ARRANGEMENT OR#l} _EL_ MOTOR i iiiiii )ELAy RELAy F'Rt ER E(; JIP (_N) F]EL PO_E_ OI_CON_ECT PER NE¢ A09597 Fig. 20 - 38HDR and 40QAC Cooling 15 System Wiring Diagram SCHEMATIC - HEATPUMP LEGEND NOTES TER (> () :.J Fq f: A09598 Fig. 21 - 38QRR and 40QAQ Heat Pump 16 System Wiring Diagram Complete Connect Indoor Piping The piping to the indoor unit can be routed from the back, side and top. If the unit is being piped from the top or the side see note below. guidelines 3. Cut the liquid tube cutter. the correct piping should ward a small amount the conditioned regular line to the correct of refrigerant length using a space. flow of condensate be pitched toward water, pipe in. per ft. is routed through the side of the unit, at- tach a field fabricated piece of sheet drain pipe as shown in Fig. 23. piping connections. lines and make flare the drain an open drain or sump at a down- slope of at least 1/4 3. If the drain piping 4. Remove the flare nuts from the indoor Install them onto the liquid and suction connections. 5. Apply inside 2. To insure in mind. and suction Line 1. Use hard polyvinyl chloride (PVC) pipe material with nominal ID of 3/4 in. to connect at drain line. Use pipe insulation 1/4 in. thick, such as Armaflex insulation, on exposed 2. Run the line set and the control wiring from the outdoor to the indoor unit through the hole in the wall. Keep the piping general Drain Observe all local sanitary codes when installing condensate drains. Refer to Fig. 23 for drain pipe connection from indoor unit. 1. On heat 400A0024 - 048, the cooling piston {indoor} is shipped in the factory installed metering device with the indoor unit. Use Table 6 to verify that you have piston size for the system being installed. Condensate 4. Attach drain pipe with nylon as shown in Fig. 23. metal wire tie passing oil to the flare connec- to support through the hole KNOCKOUT {REAR PIPING) tion and tubing. 6. Align the tubing door unit. 7. Tighten wrenches NOTE: pipe When adaptors with the refrigerant the flare nut and finish as shown piping are the installation on the inusing two in Fig. 22. is being supplied adaptors to the indoor ends to the line set. connections unit routed with from the connections the top or side, two unit. and Flare sweat the WIRE TIE HOLE pipe DRAIN PIPING REAR EXIT the other PIPING HOLE FOR RIGHT ,_._ DRAIN PIPING DRAIN PIPING PLATE (F_eldFabrtcaed) RIGHT- HAND EXIT A09534 Fig. 23 - Routing A07354 Fig. 22 - Tighten Flare Drain Piping Nut NOTE: 8. Insulate both connections on the 38QRR connection on the 38HDR units. and the liquid line Do not fasten insulation, nylon 5. Install an external NOTE: Should may be ordered pump 17 wire ties tight enough to deform the as this affects performance. before trap at the end of the condensate the installation as a fields-installed hanging the unit. require one, accessory. a condensate line. pump It is easier to install Complete Control 2. Route Wiring 1. Run the control indoor unit. wiring close to the ternfinal block on the 2. Connect the wires as shown in Fig 18 and Fig. 20 for 38HDR units, and Fig. 19 and Fig. 21 for 38QRR units. Complete Power Connection To Indoor Be sure field wiring complies with local building codes and unit voltage is within linfits shown in Table 12. Contact voltage. local power company for correction 3. Connect wire ground screw. NOTE: wire Unit When away sharp and NEC, line leads from to high routing from voltage and The 208/230-v units operation, interchange the blue (208-v) unused wires with wire nuts. Failure to follow or death. this warning 1. Mount thermostat hardware provided injury stat, preferably jected to drafts Before installing, modifying, or servicing system, main electrical disconnect switch nmst be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitaMe warning label. 2, board (TBI) and condensate piping and any are factory wired For to 24-v 208-v for 230-v to operation, wires. Cap any wires Refer to Table 9 for a on an interior wall, in an area that is not subor direct sunlight through windows. wires to the control the thermostat 3/8 in. space between Route thermostat. to a wall in the occupied space using with the thermostat. Locate the thermo- Run the thermostat unit. If running 3, to the fan box. Thermostat systems use a three speed list of recommended thermostats. could result in personal ternfinal and red (230-v) These HAZARD disconnect on the control the wire in the unit, use care to keep the refrigerant transformer Install ELECTRICALSHOCK inside the whole edges. NOTE: 24-v of improper line power coil. Place wire through through box of the indoor the back of the unit, the unit and the wall is required. over refrigerant and drain piping as shown in Fig. 24. []NIT DAMAGE HAZARD Failure to follow this caution or improper operation. may result in equipment damage Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation could void any applicable _ Carrier warranty. NOTE: unit. Use copper NOTE: wire only between Install branch circuit disconnect of adequate size to handle accessible from, unit, per section 440-14 of NEC. allow indoor unit to share disconnect with outdoor within local code before sight *Field-supplied. of, installing A09533 Fig. 24 - Routing NOTE: impede ground and power ELECTRICALSHOCK Failure to follow or death. check disconnect and and readily Some codes can be locked; Locate switch(es) current unit if disconnect in this manner. per NEC. disconnect unit starting 1. Route wires. HAZARD this warning could result in personal with existing electrical Do not route wires Wires Over under Piping the piping, injury codes. 18 or wires could air filter removal. 4. Connect the thermostat wires to the indoor for a 40QAC unit and Fig. 26 for a 40QAQ According to NEC and most local codes, the unit must have an uninterrupted, unbroken ground to nfininfize personal iniury if an electric fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance REFRIGERANTPIPING unit per Fig 25 unit. THERHOSTAT THERMOSTAT m TB2 FT- D T82 E J r E HP ONLY D FT B- f r COOLING ONLY--_ J _ r_q [] E0 m H_[] E FT D FT D IT rfq EI I A09545 Fig. 25 - Thermostat Reassemble Wire Connection for 40QAC Fig. 26 - Thermostat Indoor Unit Evacuate 1. Reinstall filters and inlet grilles 2. Reinstall the side panels START-UP Preliminary 1. Check Checks condensate the drain drainage connection, system; insert a water on the opposite bottle up into side of Wire Connection and Dehydrate UNIT DAMAGE HAZARD Failure to follow this caution for 40QAQ the System may result in equipment or improper operation. Never use the system compressor as a vacuum damage pump. the fan coil unit and fill the drain pan (see Fig. 27). Water must flow steadily; if not, check the pipe slope or inspect for any pipe restrictions. Using Vacuum Pump 1. Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve. (See Fig. 28.) 2. Connect LOUVERS charge hose to vacuum pump. 3. Fully open the low side of manifold 4. Start vacuum 5. Evacuate method. 6. After using either evacuation manifold gage. (See Fig. 29.) pump deep vacuum or fully close is complete, gage and stop operation triple evacuation the low of vacuum side of pump. 7. The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.3 oz. per foot of extra the maximum allowable length. A09538 Fig. 27 - Inserting 2. Make tight. sure all wiring 3. Field electrical plate rating. 4. Check connections Pan are correct power source must that all barriers, covers, and panels sure that the filters have been installed tioned Water Into Drain agree and they are with unit valves hose from charge 9. Fully open service valves 10. Securely name tighten are in place. En- of the low valves. Refrigerant _B and return-air grilles on the indoor unit and that the discharge louvers are posi- connection Indoor Unit Low Side High Side Service Valve must be closed. A07360 6. On units with crankcase heaters, are tight around the compressor. ensure belly-band heaters Fig. 28 - Service 19 up to B and A. caps of service Outdoor Unit correctly. 5. All service 8. Disconnect charge side service valve. piping Valve Triple Manifold Gage Evacuation Method The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. 500 microns " Low side valve Refer to Fig. 31 and proceed _Z.) High side valve Charge hose-_ 2. Close service / Charge hose Vacuum as follows: 1. Pump system down to 28 in. of mercury and allow pump continue operating for an additional 15 minutes. 3. Connect pump valves a nitrogen open until system 4. Close service and shut off vacuum cylinder pressure to pump. and regulator to system and is 2 psig. valve and allow system to stand for 1 hr. Dur- ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture. 5. Repeat this procedure as indicated in Fig. 31. System then be free of any contaminants and water vapor. Low side valve A07361 will IEVACUATE I Fig. 29 - Manifold I BREAK VACUUM WITH DRY NITROGEN I Deep Vacuum Method The deep vacuum method requires a vacuum pump capable pulling a vacuum of 500 microns and a vacuum gage capable accurately measuring is the most _ositive [28!3 of of IEVACUATE I this vacuum depth. The deep vacuum method way of assuring a system is free of air and IBREAK VACUUM WITH DRY NITROGEN I liquid water. See Fig. 30) IEvACuATE I ICHECK FOR T,GHT OR¥ SYSTEM I LEAK IN SYSTEM (IF IT HOLDS DEEP VACUUM) I RELEASE C,ARGE,NTO SYSTE I o A95425 VACUUM TIGHT TOO WET Fig. 31 - Triple TIGHT DRY SYSTEM 1 2 3 4 MINUTES 5 6 Evacuation Method To Start the Unit: 1. If the outdoor unit is equipped with a crankcase heater, turn on the indoor and outdoor disconnect switches to supply 7 power the system 12 hours before starting the system. A95424 Fig. 30 - Deep Vacuum 2. Release charge into the system by opening liquid and suction line service valves. Graph 3. Set the wireless low ambient 4. Refer remote temperature. to Table control or wired Operate 5 to determine (back-seating) remote control be- the unit for 15 minutes. if additional charge is re- quired. Also, if you have a long line application, refer to the Duct Free Long Line Application Guide to determine the additional 5. Calculate charge that is required the total additional beyond charge 25 ft (7.6 m). required and weigh 6. Charge should be added as liquid (not gas) slowly fully to low side to avoid liquid slugging. 20 in. and care- OPERATING Ceiling-suspended SAFETIES SEQUENCE fan coil units have a relay board which controls system operation in response to a room thermostat. The user may manually select any one of 3 fan speeds for unit operation. The discharge louvers on continuously. A switch the swing flmction the unit can be stationary or swing located at the bottom of the unit will turn on and off. Ceiling-suspended systems power ventilation kit and/or FAN OPERATION operation. See may be equipped -- thermostat condensate pump. Fan are coils instructions with an accessory senses MODE a demand OPERATION for cooling, -- fan of speed condensate pump (if so equipped) switch will continue to operate runs whenever If the unit has the accessory ventilation operate fan is set for medium HEAT PUMP senses a demand the indoor OPERATION for heating speed (if not already energized. The internal kit, the ventilation -- When the indoor operating), the UNIT thermostat pump (if supplied) thermostat are not operated during heating relay (CR2) closes, and the compressor this warning DAMAGE Failure damage could result in personal system, in the To avoid main OFF switch. label. HAZARD to follow this caution or improper operation. shrinkage, do may not wash result filter in equipment in water over 120°F (48.9°C). To avoid damage, do not expose filter to fire or direct sunlight . Clean the filter more frequently when air is extremely dirty. fan will thermostat valve will not be For proper maintenance Lubrication condensate HAZARD position. There may be more than 1 disconnect Lock out and tag switch with a suitable warning the fan will start in the selected and the reversing MAINTENANCE Before installing, modifying, or servicing electrical disconnect switch must be or high speed. room freeze of 28 °F (-2.22 ° C) or fan will be shut down off. AND Failure to follow injury or death. fan will stop with the compressor. whenever will turn the system ELECTRICALSHOCK is satisfied. When the cooling demand is satisfied, the compressor and outdoor fan will stop. If the system is in the AUTO. position, the indoor safety coil selection. is energized. until the room the following Indoor 3-speed reversing valve is energized (heat pump only) and/or the unit is in cooling. As long as the condensate float switch and freeze protection thermostat are closed, the cooling relays in the fan coil unit will close. This energizes the compressor and outdoor fan in the outdoor unit. The compressor with components: accessory condensate pump, cooling cycle only) -- If the level of condensate in the drain pan rises too high, the condensate float When the room thermostat the fan coil relay board is equipped system until the coil temperature exceeds 28°F (-2.22°C). The indoor fan will continue to run. Condensate float switch (units equipped with The indoor fan(s) will start in the selected speed (if it is not already operating). The reversing valve (heat pump only) will energize for cooling operation. The internal The system protect protection thermostat -- If a coil temperature lower is sensed, the compressor and outdoor When the fan(s) is operating in medium or high speed and the unit is equipped with the power ventilation kit, the ventilation fan will operate to provide fresh air. COOLING -to CLEANING capable for devices and freeze protection operation. The control and outdoor fan are system operation, operations in Table -- outdoor-fan The motors indoor-fan, are factory perform the cleaning automatic air sweep, and 13. lubricated and require and the no oiling. AIR FILTERS energized through the defrost board (DFB), which is located in the outdoor unit. The microprocessor logic in the DFB is energized when the compressor starts, and the defrost timer runs. Once every 90 minutes DFB logic (factory default setting) of compressor checks the defrost thermostat (DFT). UNIT run time, the If the DFT is Failure damage open, the unit continues in heating operation. If the DFT is closed, the DFB switches the unit to defrost mode. The timing on the DFB may be set at either 30, 50, or 90 minutes. DEFROST (Heat Pump Only) -- The DFB energizes the RVS The DFB logic checks the DFT opens back to normal DFB switches the 10-minute defrost timer turns off and the DFT. If in less than 10 nfinutes, the DFB switches the unit heating operation. If the DFT remains closed, the the unit back to heating operation after 10 minutes. When the DFB changes back to heating mode, the RVR (reversing valve relay) is de-energized and the reversing valve switches back to heating operation. Both the outdoor and indoor fans come back on, and if necessary, the electric heater also turns on. SYSTEM HAZARD to follow this caution or improper operation. may result in equipment Operating the system with dirty air filters may damage the indoor unit and can cause reduced cooling performance, intermittent system operation, frost build-up on the indoor coil, and blown fuses. Inspect and clean or replace the air filters monthly. (reversing valve solenoid), and the reversing valve switches to the cooling position. The K1 relay on the DFB opens and the outdoor fan stops. The W2 contact on the DFB is also energized, which in turn energizes the defrost relay on the fan coil relay board, the electric heater and stops the indoor fan. DAMAGE REMOVE AIR straight out. CLEAN or washed OR FILTERS REPLACE in warm -- Remove FILTERS -- filters Filters water. Shake filter to remove by pulling them can be vacuumed any excess water, and replace by sliding filter behind grille until filter snaps in place. Refer to Fig. 32. If the filter has begun to break down or is torn, replace it. Replacement filters are available through your dealer. 21 Table 13 - Cleaning INDOOR and Maintenance Schedule MONTHLY TASK QUARTERLY YEARLY UNIT Clean Air Filters X X Clean Drain Pipe Clean Condensate Drain Pan X Clean Indoor Coil X Clean Indoor Unit Front Panel OUTDOOR X UNIT Clean the Fins From Outside X Open the Unit and Clean Fins Inside Remove Dust From Electrical Parts X Check Electrical Connections Clean Outdoor Fan X X are Tight X Clean Outdoor Coil X Check that Outdoor Fan Assembly Clean Drain Pan NOTE: Maintenance CLEAN procedures INDOOR UNIT panel of the unit becomes X is Tight X for the outdoor BOTTOM units are in the individual unit installation PANEL dirty or smudged, panel with a soft dry cloth. Use off carefully with a dry cloth. a mild -- If the bottom wipe the outside liquid detergent SERVICE of the and wipe CLEAN INDOOR COIL -- To clean the coil, remove indoor unit bottom panel and vacuum the coil fins, using care not to bend or damage CLEAN CUT ELECTRICALSHOCK Failure to follow or death. fins. OUTDOOR COIL (Outdoor instructions. []nit) HAZARD this warning could result in personal injury Before servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. HAZARD Failure to follow this caution may result in personal iniury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when cleaning. Clean coil carefully. ENVIRONMENTAL Failure to follow damage. To clean the outdoor 1. Remove from discharge this caution may result in environmental Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal. coil: any dirt or obstruction HAZARD opening. 2. Use a garden hose to spray water on the coil. Debris that collects between coil fins inhibits heat transfer -- direct the water spray between CLEAN CONDENSATE pans at the start of each cooling water into the drain. To clean or replace A. REMOVE FILTERS coil fins to flush out debris. DRAINS drain -- season. Clean all drains Check and drain the flow by pouring pan: 1. Place a plastic sheet on the floor to catch any water INTAKE GRILLE that may B. WASH OR FILTERS, (((" "_ spill from drain pan. 2. Remove tached). the intake grille 3. Remove the condensate water drain into a 3-gallon []NIT DAMAGE and water distribution in the drain assembly (at- pan by letting bucket. HAZARD C. VACUUM FILTERS Failure to follow this caution may result in equipment damage, A09539 Fig. 32 - Cleaning Do not use a screwdriver to pry drain pan out of assembly - it could damage the pan. 4. Remove 5. Carefully the 4 screws holding the drain pan. hold the drain pan to remove it from the assembly. 22 Filters Before Calling for IF SYSTEM FAILS TO OPERATE -- Be sure: Service Save the cost of a service 1. Be sure main power call by doing to system the following: is turned on. 2. Press Mode button until OFF is displayed. 3. Press Mode button until either Wait 5 minutes. COOL or HEAT is displayed (as desired). 4. Adjust thermostat set point to desired room temperature. If system starts within a few minutes, service may not be necessary. If system does not operate properly, check Table 14 for typical solutions. • unit ON/OFF switch is in ON position • fuse or circuit breaker is not tripped FRESH AIR INSTALLATION The have units an installation installation of fresh Before beginning, building practices, OPTION option, which allows for field air ventilation. Plan the installation carefully. measure carefully and follow acceptable NEC, and local codes. Ventilation-Air Accessory installation instructions. -- Refer to ventilation air accessory TROUBLESHOOTING If the under-ceiling Refer to Table If the problem fan coil unit fails to start or operate properly, sometimes the problem is minor and can be handled 14 for some common problems, causes, and typical solutions. See Fig. 36 and 37 for additional cannot be corrected, contact a local dealer for further assistance. Table PROBLEM System Does Not Start. System Does Not Cool Properly. unit disconnect power switch is off. is set to night mode. Replace fuse or reset circuit breaker.* Turn on disconnect switch(as). Cancel mode using Day/Night button on thermostat. Power failure. Restore power. Unit is in off mode. Press Mode button on thermostat plays the desired unit mode. Three-minute Wait for 3 minutes. Temperature ure. time delay is running. is above or below the selected temperat- Select new temperature Clean or replace air filter(s). Temperature Reset temperature thermostat. is set too high or too low. unit outdoor coil restricted. until thermostat dis- using the thermostat. Air filter(s) in indoor unit is dirty or needs to be replaced. Outdoor to desired comfort setting using the Remove obstruction. Fan speed is set too low. Adjust fan speed to high or auto. using the Fan button on the thermostat. Air filter(s) in indoor unit is dirty or needs to be replaced. Clean or replace air filter(s). Temperature Reset temperature thermostat. Outdoor is set too high or too low. unit outdoor coil restricted. to desired comfort setting using the Remove obstruction. System Does not Heat Properly. Ice or frost has Formed on Indoor Coil JInsufficient Airflow. Fan speed is set too low. Adjust fan speed to high or auto. using the Fan button on the thermostat. Outdoor Check manual defrost timer setting and adjust as necessary. unit outdoor Low outdoor-air call. details. TYPICAL SOLUTION Blown fuse or circuit breaker tripped at building entry. Thermostat a service 14 - Troubleshooting CAUSE Indoor and/or outdoor without system troubleshooting coil is frosted up. temperature. Run system in fan-only mode until frost is gone. Air filter(s) in indoor unit is dirty or needs to be replaced. Clean or replace air filter(s). Air filter(s) in indoor unit is dirty or needs to be replaced. Clean or replace air filter(s). Fan coil unit coil is blocked. Clean air discharge louvers. If fuse blows or circuit breaker trips again after first start attempt, DO NOT attempt to start system again. Contact your local dealer for assistance. When outdoor temperature is approximately 55°F (12.8°C) or below, indoor coil frosting may occur when system is operated in cooling or maximum dehumidification mode. Units are not intended to operate below 55°F (12.8°C) without appropriate accessories. 23 I NO HEATING OR INSUFFICIENT HEATING RUNS BUT CYCLES ON INTERNAL COMPRESSOR OVERLOAD COMPRESSOR WILL NOT RUN I I I RUNS INSUFFICIENT COMPRESSOR HEATING I CLOSED -"-t I _1 COIL OPEN OR CONTACTOR SHORTED I _1 OPEN INDOOR THERMOSTAT I _-t PRESSURE SWITCH LIQUID-LINE OPEN I _t POWER SUPPLY COMPRESSOR OPEN ---[ STOPPED I ._ OR LOOSE LEAD'S AT COMPRESSOR I _-[ GEAR 11PHI _1 COMPRESSOR STUCK _ I "_1 LOSS OF CHARGE ___ OVERLOAD COMPRESSOR OPEN LEADS FAN DISCHARGE RESTRICTION LINE IN OR NONCONDENSABLES OVERCHARGE IN SYSTEM i FAN MOTOR AT BURNED FAN MOTOR OUT I _1 OPEN CIRCUIT CONTROL OR GROUNDED COMPRESSOR MOTOR ___OPEN'SHORTED' WINDINGS _l DEFECTIVE CAPACITORRUN TOO _--I LINE HIGH f FAN AT --[ VALVE REVERSING STUCK I ODT SET-rING TOO LOW --[ RESTRICTED LIQUID LINE I CAP TUBE PINCHED OR BULB NOT SENSING TRUE OUTDOOR TEMP __{ PISTON I RESTRICTED ACCURATER® OR CLOGGED I CHARGED UNDER- I FAN MOTOR OVERLOAD INTERNAL OPEN I _1 BURNED FAN MOTOR OUT I NC CONTACTS OPEN ON CIRCUIT DEFROST RELAY BOARD _1 _1 ----I "'t OUTDOOR DIRTY COIL I CAPACITOR DEFECTIVE (1 -PH) RUN I _1 RESTRICTED STRAINER I BEARINGS COMPRESSOR FAULTY I _1 HEAVILY OUTDOOR FROSTEDCOIL BROKEN FUSE LINK ] __l I _1 HIGH-LOAD CONDITION I I "_1 1 OR VOLTAGE LOW t _1 RELAY OR CONTACTOR STRIP HEATER DEFECTIVE POWER CIRCUIT TO HEATER OPENING ELEMENTS IN I I THERMOSTAT OUTDOOR DEFECTIVE I _1 .__ _{ RUNNING ______J LOOSE MOTOR LEADS REFRIGERANT CHARGE LOW ] I OUTI RFAN STOPPED OUTDOOR ] NOT OPERATING 1 _.____.._1 LOOSE -1 STR'PHEATE_ I LOW HEAD CAPACITOR DEFECTIVE DAMAGED VALVE I I LOWSOCT'ON I MOTOR CYCLING ON INDOOR FAN OVERLOAD I [ ] REVERSING _-t INTERNAL _-_ ORDIRTY INDOOR FILTERSCOIL I J NTAOTOR 1 --[CONTAOTO ENJ VOLTAGE DEFECTIVE TRANSFORMER LOW- I I I t I VALVE JAMMED IN REVERSING MIDPOSmON I I CONTACTS WELDED CLOSED IN DEFROST FAN MOTOR RELAY DEFROST THERMOSTAT DEFECTIVE THERMOSTAT IN POOR PHYSICAL CONTACT WITH DEFROST TUBE VALVE DID NOT REVERSING SHIFT I -'_ BROKEN ELEMENT HEATER TEMPERATURE OPENOVERTHERMOSTAT ] l THERMOSTAT DEFECTIVE ROOM 1 (2ND STAGE') ] PROPERLY _t SUPERHEAT HIGH I I CHARGED UNITNOT t'- CIRCUIT DEFECTIVE BOARD I BAD ELECTRICAL CONNECTION ANYWHEREIN DEFROST CIRCUIT LEGEND NC -- Normally Closed ODT -- Outdoor Thermostat NOTE: For systems with indoor units equipped with microprocessor control, see separate controls, service, and troubleshooting manual. A07435 Fig. 33 - Troubleshooting the Heating 24 Cycle INSUFFICIENT NO COOUNG COOLING OR [ I LOW-VOLTAGE TRANSFORMER DEFECTIVE l COMPRESSOR RUNS BUT INSUFFICIENT COOLING COMPRESSOR RUNS BUT CYCLES ON INTERNAL OVERLOAD i I [ _{ t WILL NOT RUN COMPRESSOR ] I ] 1 £ g POWER SUPPLY COMPRESSOR OPEN _ LOOSE COMPRESSOR LEADS AT ] ] _[ STOPPED OR CYCUNGON OUTDOOR OVERLOADFAN _L RESTRICTED OR RECIRCULATING OUTDOOR AIR 1 --_ LOOSE FAN MOTOR LEAD AT I LOW PRESSURE SUCTION 1 l LOW HEAD HIGH PRESSURE SUCTION I HIGHSOCT'ON 1 LOW SUPERHEAT __[ NC CONTACTS OPEN DEFROST RELAYS _ i _-[ DIRTY AIR FILTERS __{ __] VALVE HUNG UP OR INTERNAL REVERSING LEAK OVERCHARGED [_ --_ STUCK REVERSING DAMAGED VALVE OR THERMOSTAT OPEN _{i OPENCIRCUIT CONTROL ] _-[ LOSS OF CHARGE ] FAULTY GEAR _{ START (!-PH) OR GROUNDED COMPRESSOR _[ q ELECTRICAL CONNECTION LOOSE _[_ ___ OPEN, MOTOR SHORTED, WINDINGS INTERNAL PROTECTION COMPRESSOR OPEN --_ DEFECTIVE CARAC_OR RUN DISCHARGE RESTRICTEDTUBE DEFECTIVE MOTOR -_ _{INOORRECT CAPACITOR OFM OR NONCONDENSABLES OVERCHARGE IN SYSTEM __{ ] --_ DEFPOST THERMOSTAT DEFECTIVE COMPRESSOR DEFECTIVE VALVES RESTRICTED DUCT DAMPERS PARTLY CLOSED } INDOOR FROSTED COIL ] SLIGHTLY LIQUID LINE RESTRICTED 1 PRESSURE RELIEF iNTERNAL OPEN 1 UNIT ACCURATER iNCORRECT PISTON 1 1 REFRIGERANT CHARGE LOW COMPRESSOR STUCK __ _[ 1 _{_ TOO HIGH OR LINE LOW VOLTAGE DEFECTIVE CAPAC_OR RUN ] t RESTRICTED ACCURATER® BEARINGS ,_ COMPRESSOR =¢ULTY ] _[ __ ACCURATER INCORRECT PISTON STRAINER INDOOR RESTRICTED COIL MOTOR DEFECTIVE I _ OR CYCLING BLOWER ON INDOOR OVERLOAD l LEGEND NC ODT --- Normally Closed Outdoor Thermostat NOTE: For systems with indoor units equipped with microprocessor control, see separate controls, service, and troubleshooting manual. A07436 Fig. 34 - Troubleshooting the Cooling 25 Cycle Copyright 2009 Carrier Corp. • 7310 W. Morris Manufacturer reserves the right to change, St. • Indianapolis, IN 46231 at any time, specification8 and design8 Printed without in U.S.A. Edition notice and without 2d Date: 10/09 obligations, Catalog No: 40QAC-Q-2SI Replaces: 40QAC- Q- lSl
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Page Count : 26 Page Layout : SinglePage Page Mode : UseNone Producer : Goby Monitor Application version 4, 0, 0, 13 Create Date : Fri Feb 19 04:12:04 2010 Author : Title : Subject :EXIF Metadata provided by EXIF.tools