Carrier 58MVP060 User Manual FURNACE Manuals And Guides L0411125

CARRIER Furnace/Heater, Gas Manual L0411125 CARRIER Furnace/Heater, Gas Owner's Manual, CARRIER Furnace/Heater, Gas installation guides

User Manual: Carrier 58MVP060 58MVP060 CARRIER FURNACE - Manuals and Guides View the owners manual for your CARRIER FURNACE #58MVP060. Home:Heating & Cooling Parts:Carrier Parts:Carrier FURNACE Manual

Open the PDF directly: View PDF PDF.
Page Count: 52

DownloadCarrier 58MVP060 User Manual  FURNACE - Manuals And Guides L0411125
Open PDF In BrowserView PDF
58NVP
4-VVay MuMtipoise
[HEATING

VariabMe-Capacity

& COOUNG

Condensing

Dkect-Vent

Gas Furnace

\isit_ v_w carrier.corn

tnstammation, Start-Up,

and Operating

For Sizes 040 120,
Read

NOTE:
manual

the

entire

bei\_re starting

Series

t70

instruction

the installation

A93040

This symbol

--> indicates

a change

since the last issue,

Index

Page

DIMENSIONAL

DRAWING

........................................................

3

.....................................................
......................................................

2
4

........................................................

5

As an ENERGY STAR're
Pmmer, Carrier CoLvoradon has detem*ined
that
this product meets the EN'FR(SY

SAFETY
CONSIDERATIONS
Clearances
to Combustibles
 /

Installed

casing

connected

cut into

of return-air

(left

Furnaces

must

DO NOT

and side(s)

sides

DO NOT connect

duct to back of furnace

Downflow

Step

permitted

to follow

Furnaces

The return-air

The

of the t'urnace

side(s)

Cteanable

Filters may be field modified by cutting filter material and support rods (3) in
filters. Alternate sizes can be ordered from your distributor or dealer
1 Factory-provided with furnace.

lg

Table 3--Maximum

21-IN,WIDE
CASINGS
ONLY:
SUPPORT
RODS (3)
EXTEND 1/4" ON EACH
SIDE OF FILTER AND
REST ON CASING FLANGE

171/2dR, WIDE
CASINGS
ONLY:
INSTALL FIELD-SUPPLIED
FILTER FILLER STRIP
UNDER FILTER.

NOMINAL
IRON
P_PE
SiZE

INTERNAL
DIAMETER
(IN.)

Capacity

of Pipe*

LENGTH

OF PiPE (FT)

10

20

30

40

50

(BN.}
t/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1o1/4

1.380

1400

950

770

660

580

1-112

1.610

2100

1460

1180

990

900

* Cubic fi of gas per hr for gas _ressuresof 0.5 psig (14qn wc) orless, and
a pressure drop of 05qn wc based on a 0.60 specific gravity gas)Ref:
Table 9-2 NFPA 54-2002.
c

iii_,_,

Gas valve

"WASHABLE
FINER

shutoff

Hh,

s_itch

MUST

upward.

Failure

to

_bllow

property

damage

or death

be _cing

this

for_,_ard or tilted

x_aming

coutd

result

in

Never purge a gas line into a combustion
changber. Never test
_br gas leaks with an open flame
Use a commercially
available soap solution made specifically
fbr the detection of
leaks to check all connections.
A failure
to tb!!ow this
warning
death.

FILTER
RETAINER

could

result

in _re,

explosion,

personal

injury,

or

SUPPORT
A00290

Fig. 25--Bottom

FUter Arrangement

Use

proper

mani_bld.

length
Failure

leak resulting

PANEL

Closure

inim T

or death.

of tee is vertical

section

into lower

end of tee

of gas controls
manifold

Capped

Place

connector

Then connect

nipple

a grotmd

and manual

If a flexible

is required

jurisdiction,

black

furnace

gas control

valve

iron

should

joint

gas shutoff

having

An accessible
A93047

Bottom

personal

union

valve

shall

and extend

below

between

furnace

Panel

casing

manual

shutoffvalve

and within

by authority

be installed

a rnininaum

MUST

6 ft of furnace.

gas

(See Fig. 27)

or allowed
pipe

a capped

extend

be installed

at

of 2 in.

outside fm'nace casing. Failure to follow this caution
result in potential chaJ:_[ing of flexible gas connection.

FRONT FILLER

Fig. 26--Removing

in _]re, explosion,

on gas control

could result in a gas

stlaight-through

contIol

L

stress

in riser leading to furnace
Trap can be
a tee to riser leading
to furnace
so

level

-->

to a\oid
this warning

Install a sediment
trap
installed
by connecting
nipple

BOTTOM
CLOSURE
PANEL

of pipe
to follow

will

external

A 1/8-in. NPT

to

plugged

tapping, accessible
_br test gattge connection,
MUST be installed
immediately
upstream
of gas supply connection
to _hmace and
downsneam
of manual shutoff valve
NOTE:

The gas valve inlet pressure

use as test gauge
exceed
Fig

19

maximma_

62.)

connection
0.5 psig

tap connection

providing
(14=in

test pressure

wc) stated

is suitable

to

DOES

NOT

on gas valve

(See

GAS _

_--€

SUPPLY
MANUAL _/

II

SHUTOFF
(REQUIRED)/_

Furnace

control

conhol

will

must

be grounded

lock

out.

for proper

(ontrol

is

operation

grounded

or

through

green yellow wire connected
to gas valve and burner box
screw. Failure to follow this caution will result in intem_ittent

f

unit operation.
115-V

WIR1NG

Be%re

proceeding

voltage,

with

fiequency,

fftrnace

rating

electrical

and

plate.

connections,

phase

Also,

correspond

check

is sufficient

make
to that

certain

that

specified

on

to be sure d_at service

by power

supply

equipment

Refer to rating plate or Table

to handle

load

provided

imposed

4 for equipment

by

d_is

electrical

specifications
Make

all

electrical

Electrical

Gas Pipe Arrangement

Piping

should

and

NFGC

in the [ nited

national

plumbing

connected.
pipe

be pressure
and

If pressure

must

pressure

be

or NSCNGPIC

gas codes
exceeds

disconnected

in Canada,

before

0.5 psig
f?om

Electrical

in accordance

furnace

(33%7) rise

has been

we),

and

Field-supplied

and

local,

the famace
(I4-in.

is equal to or less than 0.5 psig (14-in.
switch

located

that ground

joint

testing.
Afier all connections
check for leakage at fftmace
gas

supply

on

pressure

gas

valve

bel\_re

and fuse

wc), mm off

befPre

union be loosened

test.

before

shall

be

within

the

polarity

pressure

plate

8--EleetricN

and

and 24-v wiring.

Check

showing

typical

field

and field electrical

Proper

115-v

control.

No component
switch

door
with

could

switch

operation

panel

result

opens

l15=v

connections

to fhmace

can occur. Do not bypass

removed.

in personal

power

Failure

to

follow

VOLTS-HERTZ-PHASE

040-14

115--60--1

060-14

115--60--1

080o14

(7221

be maintained

control

stares

this

NFPA

must

be located

for l15-v

wiring.

code indicator

or local codes

in accordance
could result

electrical

ground.

in electric

Elec=

personal

This may consist

fbr electrical

with existing

as an electrical

to minimize

occur.

approved

ground

and Canadian

Failure

shock,

ground
codes.

of

when
Do not

to follow

this

fire, or death.

Relocation
2 screws
J-box

holding

auxiliary

180 ° and attach

box

J-box.

(See Fig

to left side,

30.)

using

holes

provided

ir_jury or death.

OPERATING
VOLTAGE RANGE
Minimum*

127

104

8.9

127

104

8.9

115--60--1

127

104

080°20

115--60--1

127

100-20

115--60--1

120-20

115--60--1

Data
MINIMUM
WIRE
SIZE

LENGTH (FT).I:

MAXIMUM FUSE OR
CKT BKR AMPS**

14

31

15

14

31

15

8.9

14

31

15

104

13.8

12

32

20

127

104

13.8

12

32

20

127

104

13.8

12

32

20

Maximum*

If

light will

or unbroken

70-2002

fhult should

installed

2. Rotate

MAXIMUM
UN}T
ANPS

* Permissible limits
1 Unit ampacity =
load amps
$ Length shown is
** Time-delay type

means

to ftmaace

have an unintemlpted

wire or conduit

1. Remove

or

TaMe 4--Electrical
UNIT
SBZE

of 63°F

will NOT operate.

electrical

J°Box

warning

MUST

use gas piping

access

National

with the limitations

accessible

must

fhmace

to NEC ANSI

(7ode CSA

warning

close

polarity

and f:umace

according

for tightness.

Blower

with

and any local codes

having jurisdiction

A disconnecting

ir_iury if an electrical

diagram

all factow

shall conform

and readily

is incmTect,

The cabinet

with

Connections

See Fig. 28 for field wMng

(722.1 or authorities

specifications

flash rapidly

trical
Step

accordance
70°2002

and

maxinmm

minimum
inlet supply pressures
marked on the rating
the f:umace burners ON at HI=HEAT and OFF.

in

NFPA

branch electrical circuit containing a properly sized
breaker for this furnace. See Table 4 fbr wire size

sight from

HOT'Z:

It is

have been made, purge lines
prior to placing it into service.

ANSI

wiring

Use a separate
fuse or circuit

gas supply

capped

Code CSA

with

within

shutoff

recommended

The

tested

test

If test pressure
electric

States

leak

connections

(NEC)

or ordinances
that might apply For Canadian
installations,
all
electrical connections
must be made in accordance
with Canadian

A93324

Fig. 27--TyNcal

Code

MAXBNUM WIRE

of voltage range at which unit will operate satisfactorily.
125 percent of largest operating component's fu{I load amps plus 100 percent of all other potential
as measured 1 way along wire path between
is recommended

unit and service panel for maximum

2O

operating components'

2 percent voltage drop.

(EAC, humidifier,

etc.) full

....
....
--NOTE 5,
FtVE_
WIRE
THREE-WIRE _
H
ONLY

' THERMOSTAT
I (_ (_) (_
' _
I
J

_

I

I

I

I

I
E

I
_

"_
_

r___U27 __EEEExJ-®
115-V
SINGLE
PHASE

)

\

I-----I

In

--

-

@ @ I TERMINALS
J I
I

FIELD-SUPPLIED
DISCONNECT

I

i-_4...
J

208/230- OR
460-V

,

I-- I @ NOTE',

--!2.I / Gi:iW-i
_

115-V
FIELD-SUPPLIED
DISCONNECT

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-, 208/230-, 460-V WIRING

AUXILIARY
J-BOX

_

|

_
s- J
/.......
_
_J/m ____NOTE 1.....

J(i.

/

SWITCH

/_

....

208/230-V

/

L__

r--I---

' SINGLE

iI I
j
'I
F
j }

PHASE

.........

/
FURNACE ---"

CONDENStNGuNIT

24-V
TERMINAL

CONTROL
CENTER

TWO WIRE

BLOCK

NOTES:
1.
2.
3.
4.

Connect Y or Y/Y2 terminal as shown for proper cooling operation.
Proper polarity must be maintained for 115-v wiring.
Use W2 with 2-stage thermostat when zoning.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
5. Some thermostats require a "C" terminal connection as shown.
A98325

Fig. 28--Heating

and Cooling

Application

Wiring

maintenance
required,
£urnace

may

use only
contIol

Diagram

cause

fuse

to blow.

a t_t_se of identical

will flash status

If fi/se replacement

size

(3 amp)

and type

code 24 when fi/se needs

is
The

replace-

n'lent

ELECTRIC
DISCONNECT
SWITCH

NOTE:

Use AWG No

18 color-coded

lengths up to 100 ft For wire lengths
1d wire.

®

NOTE:
Fig

For additional

them_ostat

copper
over

them_ostat

wire for

100 _L use AWG

connection

diagrams,

No.

reference

54o6!

A93033

Fig. 2g--Disconnect

Do not

connect

and f_/mace. Use

aluminum

Switch

wire between

only copper

follow this caution will result
performance
satisfl_ction.

and Furnace

wire

disconnect

(See Fig

in intem_ittent

29)

switch
Failure

to

unit operation

or

FIELD
LOCATION
--€

If manual disconnect
switch is to be mounted
select a location where a drill or _hstener will
electrical or gas components
will result in intem_ittent
satisfitction.

f//'_

FACTORY
INSTALLED
LOCATION

on furnace,
not contact

Failure to J:bllow this caution
unit operation
or perfbm_aace

24oV WIRING
Make field 24-v thermostat connections at 24ov tem_inal block on
£umace control Y wire from d_em_ostat MUST be connected to

Y

YY2 terminal on contlot, as shown in Fig. 28, for proper cooling
operation. The 24ov tem_inal block is marked for easy connection
of field wiring. (See Fig. 32.) The 24ov circuit contains a 3-amp,
automotiveotype fuse located on fi/mace control. (See Fig. 32.)
Any electrical shorts of 24ov wiring during installation, service, or

A00212

Fig. 30--Relocating
2i

J=Box

AC( ESSORIES
1. Electronic

Air (leaner

The t:arnace

control

(1 0-amp

maximum)

Connect

an accesso_

are energized

blower

Electronic
connect

terminals

and EACo2.
n_axinmm

CARBON

terminals

during

1i4oin. female quick
quick-connect

(hA()
EAC

with

115v

Failure

operation.

connected

Air (?leaner

terminals

The terminals

are rated
during

using

could

to the two male 1i4oin.

on the control

and are energized

(if used)

board

marked

_br 115VA(,
blower

The

EAC-1

24 VA(,

screw terminal

The HUM
heating.

steps

shall

1. Seal any unused

an accessow

0.5 amp maximmn

terminal

on the control

is energized

HUM
board

when

thermostat

blower

and

contwl

HUM

terminal

there

and all doors

to HUM

ance(s)

(humidifier)
terminal on Thermidistat-r_L
Zone Controller or
similar device. See Thern'lidistaff M, Zone Controller,
thermoo
star, or controller
connection.

manui:acturer's

instructions

%r

The

0--Direct
58MVP

only)

ft_rnaces

combustion

require

is taken directly

gases are discharged
REMOVAL

VENT

(one

a direct-vent

fi'om outdoor

to outdoor

OF EXISTING

COMMON

a dedicated

In

proper

58MVP

system,

atmosphere,

(?ode and these

is no blockage

and all flue

the

being

inspected

appliance

an existing

original

venting

the remaining
I venting
_hmace

attached

system
and vent,

and spillage

(ategory
system

I fitrnace

appliances.

could

cause

leakage

of combustion

lighting

is removed
be sized

An improperly

the %rmation

of condensate
products

or replaced,
to properly

burner

and combustion

54 andor (SA
lation (?ode.

etc.

9. After

Place

opening

fireplace

above,

ance to their
Vent

system

other

appliances

system

B149A,

dampers

determined

22

system

return

so

resizing

appliances

that each
properly

doors

or candle.

in accordance
Z223.INFPA
Instal°

appliance

con°

vents when tested

windows,

exhaust
burning

_hns,
applio

of use.

may need to be resized.
vent systems

must be sized to approach
vent sizing

at

of main

Gas and Propane

conditions

or vent connectors

or connector

appliance

any of the above

and any other gas-fired

determined
using appropriate
or NSCNGPI(

the

5 minutes

during

Natural

previous

when

a summer

the them_ostat

of a match

is observed

to the xenting

as outlined

fans, such as

equipped

aker

Use the flame

it has been

nected

and

not connected

operate

Adjust

from draft hood

x enting

applio

continuously.

relief

operation.

an

so they are opera°

not

instructions.

the

are located

tests, the venting system must be corrected
with the National Fuel Gas (7ode. ANSI

in the

products,

space,

exhausts,

into operation.

hood

8. If improper

sized Categoo-

of condensate

into the living

the
vent

system

Do

cause

doors and windows
in which

and any appliance

is operating

Deterleakage,

could

Turn on any exhaust

speed.

7. Test for spillage

may no longer

space

and bathroom

6. Follow

FROM

SYSTEMS

the

dQ'ers
system.

ing at maximum
exhaust fan.

the drak
---5 When

close all building

dampers.

for

which

to the xenting

5. Turn on clothes

instructions.

or restriction,

deficiencies,

4. (?lose fireplace

atmosphere.

FURNA(ES

are

system.

of the building.

furnace

al! air

system

size and horizontal

connected

range hoods

system.

to the _ enting

in _enting

other spaces

Venting

directovent

appliance

into operation,

for proper

between

to the x enting
Step

for each

being placed

system

corrosion
and other
unsafe condition.

_i/rnace

into operation

or death

openings

3. As far as practical,
connect

be followed

connected

Installation

mine that

in

(See Fig. 32.)

DO NOT

poisoning

system

the x enting

Propane

strip.

is energized

for each appliance

placed

pitch, as required in the National Fuel Gas (;ode, ANSI
Z223A NFPA 54 or the (SA B149.1. Natural Gas and

humidifier
terminal

being

monoxide

to the venting

2. Inspect

(if used) to the 1/4-in. male quickoconnect
( o\_-24V

following

HAZARD
below

not in operation:

(HUM)

Connect

in carbon

system

xxhile all other appliances

operation.

(See Fig. 32.)
2. Humidifier

POISONING

the steps outlined

to the venting

result

connected

1.0 amps

motor

MONOXIDE

to fbllow

or vent

For any

connectors,

n_ininmm

size as

table fbund in the NFGC

CONNECTION DIAGRAM
sw178

D
040060
MODEL
38_080

_ )
......
DE_

D

5252

O_

700

D_

875

1050

O

D

1225

o
122 1

1225

5T0DE,
0 700
0, ,050
,225
,400
120

DE_

_lt cont fan ai ]ow w len CF Mtch_

hesa

Y1 DHUM

G

Corn_V]R
24V

CPU
DHUM
EAC1

Microwocessor / Circuitry
DHUM Connection (24VAC)
Electronic Air Clea net Connection
(115VAC 1 0 Amp Max)
ElectroNc AirCleaner Connection (Common)
Rarne Rollout Switch Man Reset SPST(NC )

GV
FSE
GVR
HPS
HPSR

1750

Fuse 3 Amp Aulomotive Blade Type
Factory Installed
Gas
V_lve
Flame
Proving Sensor Electrode
Gas Valve Relay OPSf (NO)
High Heat Ressure Sw_tN1 SPST(NO)
High Heat Ressure Swlt{ h Re]ay SPST(NC)

HSIR
Hot Surtdce Igniter Relay SPST(NO)
HUM
24VAC Humidifier Connection (05 Amp Max)
HUMR
Humidiaer
SPST(N
O )
HSI
Hot Surtdc Rela_
e Ign_er
(115VAC)
IDM
Inducer Draft Motor 2 Speed Shaded Pole
IDR
Inducer Motor Relay SPST(NO)
IHI/LOR Induc_ Motor Speed Change Re4ay SPDT

--

ar_ in )FF position

S]
c

IJS
_

I

3161 7
IIII
_ m _ N

I
r_

F_

--_P

54 3 2 1
IIII
I

-writ-

_

:L

RED _

LGPS
LED
LPS
IS
IND
PC£
PL1
PL2
PL3
PL4
PLY
PL9
PL10

Low
Pressure
Swath
SPST(NO/
Light Gas
Emitting
Diode
for Stdtus
Codes
Low Heat Pressure Switch SPST(NC))
Limit Switch Auto Reset,SPST(NC)
Inductor(Note#7)
Printed
CimuK Board
12 Circuit Connector
4 Circuit HSI & IDM Connector
4 CircuK ECM BLWM Connector
4 CircuR M odel Plug Connector
4 Circuit Communication
Connector
2 Circuit OAT Connector
2 Circuit HSI Connector

PL11
PL12
PL13
PL14
SW11
SW1 2
go/1 3
SW1 4

IDM Connector (12 Circu_c)
1 Cirr uK Inductor Splice Connector
16 Circuit ECM Bbwer Cod Connector
5 Circuit ECM Blower Power Connector
Manual Switch Status Code Recall SPSf (N O )
ManuaISwitdl
Low Heat Only SPST(NO)
Manual Switch Low Heat Rise Adj SPST(NO)
ManuaISwitch
Comtort/Efficiency Adjustment
SPST(NO)
ManuaISwitch
Cooling CfM_or
SPST(NO)

SW1 5

I
I

4

I

210

)in O_ posi_on

_

_rCond_ioning
Relay Detent
Air
Conditioning Relay
SPSI (N Jumper
O )
Blower Motor (ECM)
Con_nuous Fan (Adjustable Airflow C[M)
A_rCondiBoning(AdjustableAHow
CFM)
Communication
Relay SPDT

FUSE

1400

_

ACRDJ
ACR
BLWM
C[
C
COMMR

EAC 2
FRS

i

/Cswlt

1ZZ5

HtA/C

V'72

ir_ow vhen,

1050

1 Det

AC

I

875Z

2 Oet

_[_

I

700

gCll 6 Manual Switch Component Test SPST(NO)
SW1 78 Manual Switches Blower OfFDelay SPST(NO)
SW41
Manual Switch TWlnning Main (O_F)/Sec
(ON)

-

O
_

UNC ON
TERMINAL
CONfROL fERMINAL
FACTORYPOWER
WIRING (115VAC)
FACTORYCONTROL
NOTES:
WIRING (24VAC)
FIELDCONTROL

----WIRING (24VAC)
CONDUCfOR ON
CONTROL
FIELDWIRING
_l
SCREWTERMINAL
EQUIPMENT
GROUND

Fig. 31--Wiring

Use N_e
oNy copper
bel_teen totbe
disconr'ecl
_,vitch for
andcout_
tl_e o!
fiarnace
junclion
This
r_dst bew_re
cc4?nected
furnace
sr_et rr_lal
to prove
f!ar_ bex (J B}
f : If
any °f tl_e
wire isonly
replace_ use wire rated f°r f05°C
S}n_bols
are °rgin_
electric_equipl_enl
lepresental_on
Sdid iiees inskte PCB ale pnnted cimuit beard conYdcto_s alld are pot i_clt_ ied in legend
il
Replace only w_lJ_a 3 amp fuse
Inductc{ is used with 3/4 I_p aid 1 hp ECM Blower motors
] Faclory connected vZqen (LGPS) not used
Blower off delag gas beatir N selecl_ons are (90,12011501180)
seconds, o:)oling or [_at pump
90 seconds or 5 seconds _'_'en behurr

of vent condensate

(ombustion=air
termination

cement

combustion-air

sized for 2-in. pipe

NOTE: Slope combustion-air and vent pipes a n_ininmm of 1/4
in. per linear ft with no sags between hangers.

(ASTM)

In Canada, construct all combustion-air
of (SA
or ULC listed sche&de=40
and

zone,

preferred),
6 for required

using

When

vent pipe is exposed

such as when

and vent pipes
pressure

Center

must

either

terminate

through

together

in same

roof" or sidewall

accesso W termination

chimney

(roof

kit

clearances

24

it passes

is used
in Table

follow

this caution

an unheated
pipe

8 with Armaflex-type
will result

l{

to temperatures

through

as a raceway,

shown

e

in minor

must

below

fieezing,

space or when
be insulated

insulation

Failure

unit operation,

a
as
to

TABLE 8--APPROVED
ASTM SPECBFRCATION
(MARKED

ON NATERIAL)
D1527

COMBUSTION-AIR

AND VENT PIPE, FiTTiNG AND CEMENT MATERIALS

_,_ATERIAL

PIPE

FITTtNGS

SOLVENT

CEMENT

AND PRBNERS

ABS

Pipe

--

Schedule-40
Schedule-40

D1785

PVC

Pipe

--

D2238

For ABS

--

--

D2241

PVC

Pipe

--

SDR-21 & SDR-26

D2468

PVC

--

Fittings

Schedule-40

D2468

ABS

--

Fittings

Solvent
Cement

For ABS

Schedule-40
Solvent
Cement

D2564

For PVC

--

--

D2G61

ABS

Pipe

Fittings

D2G65

PVC

Pipe

Fittings

F438

CPVC

--

Fittings

Schedule-40

F441

CPVC

Pipe

--

Schedule-40

F442

CPVC

Pipe

--

F493

For CPVC

--

--

F628
F656

ABS
For PVC

Pipe
--

---

F891

PVC

Pipe

--

For PVC
DWV at Schedule-40

SDR
Solvent
Cement

For CPVC
Cellular Core DWV at Schedule-40

Primer

Combustion

air must

not

be

taken

fiom

inside

Cellular Core Schedule-40

elements

cleaning

are found

solvents,

other household
as possible

in aerosols,

detergents,

salts, air fresheners,
products.

Locate

fi'om swimming

structure

NOTE:

by halogens,
and iodides.

within

bleaches,

adhesives,

paint,

combustion=air

pool

Excessive

exposure

in safety

Solvent

cements

sparks,

and open

Avoid
eyes.
property

All

are

breathing
Failure

to contaminated

and perfbrmance

Use

in vapor
to follow

Keep

only

and

vent

away

fiom

will

heat,

in well ventilated

or allowing
injury,

air

problems.

contact

this warning

personal

combustion-air

watertight

combustible.

flame.

damage,

combustion

related

could

with
result

areas.
skin

or

in fire,

or death.

pipes

must

airtight

37, 38, 39, 40, or 41. Failure to fbllow this warning
result in property damage, personal ir_jury, or death.

could

The minimum

water

&oplets.

combustion-air

These

droplets

minimum

offset pipe section

to reduce

excessive

Combustion-Air
Detem_ine
1. Using

combustion-air
Table

may be undesirable,
fi'om exiting

confbustion-air

and vent pipe

diameters.

diameters

use

combustion=air
2, When
smallest

and

this

Pick the
diameter

housing
nected.

smallest
fbr

allowable

vent

systems

pipe diameter

pipe tength,

or

be cemented

except

connection

attachment
since

of

it may be

pipe as follows:

location

of combustion-air

intake pipe connec-

intake housing

combustion=air
unused

of

both

d. Install

where

pipe

into selected
of" short

must

combustion-air

b. Reposition

larger

in terminations

in Fig. 37, 38, 39, 40, and 41.

pipe fbr servicing.

c. Insert perforated
the

or

as shown

in Fig. 34

for application.

and vent pipes,

installing

to remove

appropriate

these

2 pipe

in Fig. 35,

vent pipe outlet.

determine

or pipe sections

areas

pipe to inlet housing

tion to combustion-air

Pipe Diameter

individtlally

flame disturbance,

arid Vent Pipe Attachment

a. Determine

and vent pipe diameter.

7,

elbows

All pipe joints

1. Attach

(each)

and a 12-in.

as shown

combustion,

may occur.

See shaded

combustion-air

(5-8 ft) may discharge

is recommended,

droplets

and Vent

NOTE:
necessary

and vent pipe length

is 5 ft. Short pipe lengths

Do not count
furnace

Combustion-Air

and
in Fig

for d_ese [i/maces

exactly

be

as shown

NOTE:

Pipes must also tem_inate

lockout

An 080o14 size filrnace located in Indianapolis, elevafion
650 ft above sea tevel, could be installed in an application
reqniring 3 elbows and 17 ft of vent pipe, along with 5
elbows and 16 t't of combustion=air pipe Table 6 indicates
this application would allow a l-li2=in, dianreter vent pipe,
but require a 2-in. diameter combustion air pipe (1°li2-in.
pipe is good for 20 ft with 3 elbows, but only 10 ft with 5
elbows). Therefore, 2=in. diameter pipe must be used fbr
both vent arid combustion-air pipes since larger required
diameter must always be used fbr both pipes. If same
installation were in Albuquerque, elevation 5250 ft above
sea level, installation would require 2-in. vent pipe and
combustion-air pipe. At 5001o to d000=ft elevation, 1ol/2in. pipe is not allowed with 5 elbows, but 2-in. pipe is good
for 68 ft with 5 elbows.

pump

house,

result

or incomplete

sense

& DWV

EXAMPLE:

and

inlet as _r

pool and swimming

IPS sizes

For PVC

flame
because
that air is frequently
contaminated
which include fluorides,
chlorides,
bromides,

IPS sizes

DWV

than reqnired

These

DESCRBPTION

support

use the

Do not use pipe size greater

e. Insert

25

intake

intake

housing

housing

disk assembly
combustion-air

intake

(fi_ctory=supplied

ftlrnace

casing

be positioned

2-in. diameter

fitting

(fi_ctoD- supplied)

support

should

plug

in

connection.

pipe

in loose

combustion-air
to bottom

pipe into intake

in intake

will

be

con-

parts

bag)

pipe hole. Pipe
of casing

housing.

hole.

_lr *a

_]

(_AIR

VENT TERMINAL

item

Clearance

A

Clearance
anticipated

B

Clearance

Description

above grade, veranda,

Canadian

porch, deck, balcony, or

E_

INLET

Installation

AREA WHERE

TERMINAL

IS NOT PERMITED

(I)

U.S Installation

(2)

12" (30cm) #

12" (30 cm)

6"(15crn)forappliances<10,OOOBTUH(3kW),12"(30

6" (15 crn) for appliances

cm) for appliances > 16,000 Btuh (3 kW) and <100,600 Btuh
(30 kW), 36" (91 cm) for appliances > 160,000 Btuh (30 kW)

for appliances > 10.0O0 Btuh (3 kW) and < 50,000 Btuh (15
kW), 12" (30 cm) for appliances > 56,006 Btuh (15 kW)

snow level
to a window or door that may be opened

C

Clearance

D

Vetfical clearance

to a permanently

to a ventilated

soffit located above the

distance of 2"(61 cm) from the

E

Clearance

to an unventilated

P

Clearance

to an outside corner

G

Clearance

to an inside corner

H

Clearance

soffit

to each side of the centedine
meter or gas service

I

Clearance

to service

J

Clearance

to non-mechanical

the combustion

< 10,600 BTUH (3kW), 9" (23 cm)

closed window

terminal within a horizontal
centerline of the terminal

electrical

SUPPLY

regulator

3" (91 cm) within 15 (4.5 m) above the meter/regulator

3" (91 cm) within 15"(45

regulator assembly

extended above

assembly

assembly

vent outlet

3" (91 cm)

air supply inlet to building or

air inlet to any other appliance

6" (15 ore) for appliances
for appliances
kW)and

< 10,OOOBTUH (3kW), 9" (23 ore)

> 10.0O0 Btuh (3 kW) and < t 06,000 Btuh (30

< 50,000 Btuh (15kW),

12"(30cm)

forappliances

6" (t 5 ore) for appliances
for appliances

m) above the meter/regulator

< 10,OOOBTUH (3kW), 9" (23 ore)

> 10.0O0 Btuh (3 kW) and < 50,000 Btuh (15

kW), 12" (30cm)for

appliances

> 50,060 Btuh (15 kW)

> 50,000 Btuh (I5 kW)
K

Clearance

to a mechanical

air supply inlet

L

Clearance

under a veranda, porch, deck. or balcony

12" (30 cm) +

M

Clearance

to each side of the centedine

12" (30 cm)

12" (30 cm)

3" (91 cm)

3" (91 cm)

3" (91 cm)

3" (91 cm)

below vent terminat of the furnace
vent, or other appliances
N

Clearance

O

Clearance

extended above or

to a dryer or water heater

of a dryer vent, water heater

direct vent intake or exhaust.

from a plumbing

vent stack

(1)

In accordance

with the current CSA B 149 1, Natural Gas and Propane

(2)

In accordance

with the current ANSl Z223.1/NFPA

#

18"

+

Permitted

3" (91 cm) above if within 10'(3m horizontally)

direct vent intake or exhaust

to the vent terminal

vent. or other appliances

6" (1.83 m)

Installafion

Code

54. Nafional Fuel Gas Code

(46cm)aboveroofsurface
only if veranda, porch, deck, or balcony is fully open on a minimum of t_vo sides beneath the floor

For clearances
manufactureCs

not specified in ANSi Z223.1/N PPA 54 or CSA B 149.1, clearances
installation instructions

shall be in accordance

with local installation

codes and the requirements

of the gas supplier

and the

Notes:
1.

2.

The vent for this appliance

shall not terminate

a Over public walkways; or
b. Near soffit vents or crawl space vents or other areas where condensate

or vapor could create a nusiance or hazard or property

c

to the operafion

Where condensate

vapor could cause damage or could be detrimental

of regulators,

damage; or

relief valves, or other equiprnent.

When Iocafing vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation
Recirculafion can cause poor combustion, inlet condensate problems, and accelerated corrosion of the heat exchangers.

of the combusfiob

products of adjacent

vents

A03227

-_ Table 6--Direct

Vent Termination
26

Clearance

COMBUSTION=AIR
The

combustion-air

unused

(

by using

fitting,

using

NOT IN
HORIZONTAL
SECTION

DO NOT

housing

or fitting

A plugged

NOTE:

Moisture

improper

termination

in

Fig. 33--Combustion-Air
and Vent Pipe Diameter
Transition Location and Elbow Configuration

moisture

Select 1 vent pipe connection and
1 combustion-air
pipe connection.

COMBUSTION-AIR 7

Install

a

screw.
Breakage

of intake

to occur
on this fitting

intake

intake pipe

may

be

intake

result

of

pipe tem_ina-

light

snow

or other

sources

of

in

a 3/16=in.

and AiC

a 1i8=im hole in

as a guide

combustion-air
where

is desired,

drill and conuect

This tube should

f_/mace

be

must

in Fig. 37, 38, 39, 40, or 41 so it will

to areas

could be pulled

tube

AIR

in

fitting

has been provided

combustion=air

to that shown

plug with

NOTE: Select 1 vent pipe connection and
1 combustion-air
pipe connection.

be installed

This

is found in combustion-air

If use of this drain connection
NOTE:

must

SCREW

air leakage

Ensure

not be susceptible

FITTKNG

or by &tiling
housing

OVERTIGHTEN
may cause

&ain connection

tion is similar
A93034

fitting

6 or No. 8 sheet metal

fk_r use when moisture
and combustion
box
TRANSITION IN
VERTICAL SECTION

PLUG

housing

iu intake

No

NOTE:

plug

intake

RTV sealant,

hole

field=supplied

HOUSING

intake

combustion=air

attached

FURNACE

INTAKE

be routed

(if used),

drill out fitting's

a field-supplied

to open

and should

tap

3/8-in.

condensate

&ain

be trapped

fk_r

(See Fig.

36.)

COMBUSTION-AIR

2. Attach

vent pipe as fbllows:

a. Determine
housing

location

b. Reposition

._T

(rubber)

to appropriate

tion. Tighten
_

pipe

connection

to inducer

in Fig. 34 for application.

elastomeric

and clamp
COMBUSTIONAIR

of vent

as shown

inducer

unused

housing

inducer

outlet

housing

cap

connec-

clan?p.

COMBUSTIONAIR

AiR
FLOW

UPFLOW

COMBUSTIONAIR

DOWNFLOW

COMBUSTIONAIR
VENT

Inducer

housing

against

inducer

housing.

Clamp

must

any condensate

leakage.

Failme

to follow

result

VENT

outlet

in electrical

cap must be installed

shock,

fire, personal

condensate
DISCHARGE

HORIZONTAL-RIGHT

to prevent

this warning

injury,

could

or death.

c Install pipe support (ii_ctory-supplied in loose parts bag)
into selected furnace casing vent pipe hole, Pipe support
should be positioned to bottom of casing hole,

Vent pipe must be installed
housing internal stop (lamp

HORIZONTAL-LEFT

and _idly seated

be tightened

result

DISCHARGE

NOTE:
casing.

A96187

leakage.

in electrical
A 2-in.
Make

Failure
shock,

diameter

and

coupling

NOTE: A 2=in, diameter pipe must be used within the furnace
casing Make all pipe diameter transitions outside _:urnace casing,

Insert

{rubber)

g, Drill a 1/8-in, hole iu 2-in, combustion-air
in intake housing as a guide

the clamp

both clamps

within

outside

fi'om

combustion-air
ti/rnace

to

casing.

housing

onto

connec-

vent pipe are

elastomeric

(rubber)
inducer

vent

housing

vent pipe _hrough the

and Nlly into inducer
on the internal

the pipe to inducer

to 15 inAb.

the furnace

I:umace

iaous-

stop. Tighten

iaousing.

Tighten

of torque.

hole filler cap (ti_ctory=supplied

in unused

3. Working

coupling

could

or death.

of inducer

the 2°in. diameter

to secure

e. Install casing

be used

clamps)

until it bottoms

screws

warning

and 2=in. diameter
the

2 loose

elastomeric

ing connection

h, Install a field-supplied No, 6 or No, 8 sheet metal screw
into combustion=air pipe,

sur_itces

dw-. Assemble

connection.

bag)

must

this
injury,

transitions

coupling,

(with

£ Install casing hole filler cap (factou-supplied in loose parts
bag) in mmsed combustion=air pipe casing hole
pipe using hole

pipe

that mating

tion, elastomeric
clean

to _bllow

fire, personal

all pipe diameter

d. Be certain

Fig. a4_Combustion-Air
and Vent Pipe
Connections

and fully seated against inducer
must be tightened to prevent any

pipe casing

outside,

cut

in loose parts
hole.

pipe

to

required

length(s).

NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake
housing or fitting may cause air leakage to occur.
NOTE: Do not attach combustion-air intake pipe pem_anently to
combustion-air intake housing since it may be necessary to remove
pipe for service of igniter or flame sensor,

4

Deburr

5

Chamfer outside
and cemeut.

6. Clean

27

inside

and outside

of pipe,

edge of pipe _br better

and dV all surfaces

to be joined.

distribution

of primer

121M,Nd,
H
9÷
-.,_

VENT

12" MIN _,_

VENT PIPE

PIPE -'-_11

_jJ-

HORIZONTAL

COMBUSTION-AIR PIPE

/'

COMBUSTI:N-AIR PIPE

HORIZONTAL TO SIDEWALL

TO ROOF

COMBUSTION-AIR
f

COMBUSTION-AIR

PIPE

VENT PIPE

PIPE J-_

Z_

12" MIN-_D,-VENT PIPE

VERTICALTO

ROOF

VERTICAL TO SIDEWALL

NOTE: A 12 In. minimum offset pipe section is recommended with
short (5 to 8 ft) vent systems. This recommendation is to reduce
excessive condensate droplets from exiting the vent pipe.
A96230

Fig. 38--Short

Vent (8 to 8 Ft) System
CONCENTRI( VENT AND COMBUSTION=AIR
TERMINATION KIT INSTALLATION

7. Check &y fit of pipe and mark insertion depth on pipe.
NOTE: It is recommended that all pipes be cut, prepared,
preassembled beK_re pem_anently cementing any.joint.

and

NOTg:: If these instructions dif_'cr flora those packaged with
tem_ination kit, follow kit instructions.

g. After pipes have been cut and preassembled, apply generous
layer of cement primer to pipe fitting socket and end of pipe
to insertion mark. Quickly apply approved cement to end of
pipe and fitdng socket (over primer) Apply cement in a light,
unii:orm coat on inside 05"socket to prevent buildup 05"excess
cement Apply second coat

Combustion-air and vent pipes must terminate outside structure. A
factoQ' accessory termination kit must be installed in 1 of the
installations shown in Fig. 37, 38, 39, 40, or 41. Four temaination
kits are available.
--9 See Table 6 for additional

termination information.

1. The 2-in. termination bracket kit is 5br l=in. 1ol/2 in., and
2°in. diameter 2°pipe termination systems.
2. The 3=in temaination bracket kit is 5br 2ol/2 in. and 3=in.

9. While cement is still wet, twist pipe into socket with 1/4 mm
Be sure pipe is fully inserted into fitting socket
10. Wipe excess cement fi'om joint. A continuous bead of cement
will be visible around perimeter of a prope*ly made joint.

diameter 2-pipe termination

systems.

3. The 2-in. concentric vent/air termination kit is for l-in, 1-1/2
in., 2=in. and 2-!/2 in. diameter pipe systems when single
penetlation of wall or roof is desired.
4. The 3-in. concentric vent/air termination kit is £_r 2-1/2 in. and

11. Handle pipe joints carefhlly until cement sets
12. Support combustion-air and vent piping a minimum of eve W
5 ft (3 k 5br SDR-21 or -26 PVC) using perSbrated metal
hanging strap

3=ira diameter pipe systems when single penetlation of wall or
roof is desired.

13. Slope combustion-air and vent pipes downward toward 5hrnace a minimum of 1/4 in per tinear ft with no sags between
hangers

NOTE: Shaded parts in Fig. 37, 3g, 39, 40, and 41 are considered
to be tet_ninations. These components should NOT be counted
when dote*mining pipe diametm Root" tem_ination is preferred
since it is less susceptible to damage, has reduced chances to take

14. [se appropriate methods to seal openings where vent and
combustion=air pipes pass through roof or sidewall

28

Tab{e 7--Maximum
ALTITUDE

0 to 2000

(IN.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-tn.
Concentric

1-1/2

50

45

40

35

30

25

2

70

70

70

70

70

70

060-14

2 Pipe or 2-tn.
Concentric

1-1/2

50

45

40

35

30

25

2

70

70

70

70

70

70

080-14
080-20

2 Pipe or 24n.
Concentric

1-1/2

30

25

20

15

10

5

2

70

70

70

70

70

70

100-20

2 Pipe or 2-tn.
Concentric

20

3001 to 4000

A_titude

A_titude

5001 to 60005

See

notes

on next

Termination

45

40

35

30

25

70

70

70

70

70

70

2-1/2

10

NA

NA

NA

NA

NA

3

35

30

15

NA

NA

NA

31:

70

70

70

70

70

70

Number of 90 ° Elbows

Pipe Diameter

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-tn.
Concentric

1-1/2

45

40

35

30

25

20

2

70

70

70

70

70

70

060-14

2 Pipe or 2-tn.
Concentric

1-1/2

45

40

35

30

25

20

2

70

70

70

70

70

70

080-14
080-20

2 Pipe or 2-in.
Concentric

1-1/2

26

21

16

11

6

NA

2

70

70

70

70

70

70

100-20

2 Pipe or 2-in.
Concentric

2

40

35

30

25

20

15

2-1/2

70

70

70

70

70

70

120-20

2 Pipe or 3-in.
Concentric

3

31

26

12

NA

NA

NA

31

63

62

62

61

61

61

Number of 90 ° Elbows

Termination
Type

Pipe Diameter

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-in.
Concentric

1-1/2

42

37

32

27

22

17

2

70

70

70

70

70

70

060-14

2 Pipe or 24n.
Concentric

1-1/2

42

37

32

27

22

17

2

70

70

70

70

70

70

080-14
080-20

2 Pipe or 2-tn.
Concentric

1-1/2

25

20

15

10

5

NA

2

70

70

70

70

70

70

100-20

2 Pipe or 2-tn.
Concentric

2

38

33

28

23

18

13

2-1/2

70

70

70

70

70

70

120-20

2 Pipe or 3-tn.
Concentric

3

29

24

10

NA

NA

NA

31

50

59

58

57

57

56

Unit
Size

Termination
Type

Pipe Diameter

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-tn.
Concentric

1-1/2

40

35

30

25

20

15

2

70

70

70

70

70

70

2 Pipe or 2-tn.
Concentric

1-1/2

40

35

30

25

20

15

2

70

70

70

70

70

70

080-14
080-20

2 Pipe or 2-tn.
Concentric

1-1/2

23

18

13

8

NA

NA

2

70

70

70

70

70

68

100-20

2 Pipe or 2-tn.
Concentric

2

36

31

26

21

16

11

2-1/2

70

70

70

70

70

70

120-20

2 Pipe or 3-tn.
Concentric

31

56

55

54

53

52

52

Unit
Size

Termination

Pipe Diameter

Type

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-tn.
Concentric

1-1/2

37

32

27

22

17

12

2

70

70

70

70

70

70

060-14

2 Pipe or 2-tn.
Concentric

1-1/2

37

32

27

22

17

12

2

70

70

70

70

70

70

080-14
080-20

2 Pipe or 2-tn.
Concentric

1-1/2

22

17

12

7

NA

NA

2

70

70

70

70

68

63

100-20

2 Pipe or 2-tn.
Concentric

2

33

28

23

18

13

8

2-1/2

70

70

70

70

70

70

120-20

2 Pipe or 3-tn.
Concentric

31

53

52

50

49

48

47

060-14
4001 to 5000$

2 Pipe or 3-tn.
Concentric

2
2-1/2

Type

Unit
Size

A_titude

OF 90 ° ELBOWS

PIPE DIAMETER

Unit
Size

2001 to 3000

NUMBER

TERMINATBON
TYPE

120-20

A_titude

AHowable Pipe Length (Ft)

UNIT
SRZE

page.

29

Number of 90 ° Elbows

Number of 90 ° Elbows

Table7--MaximumAJtowablePipeLength
ALTITUDE

6001 to 7000_

A_tJtude

7001 to 80OO_

A_titude

8001 to 9000_

A_titude

9001 to t0O0O_

UNIT
SRIE

TERMINATION
TYPE

(Ft)

Continued
NUMBER OF 90 ° ELBOWS

PiPE DIAMETER

(_N.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-In.
Concentric

1-1/2

35

30

25

20

15

10

2

70

70

68

67

66

64

060-14

2 Pipe or 2-In.
Concentric

1-1/2

35

30

25

20

15

10

2

70

70

68

67

66

64

080-14
080-20

2 Pipe or 2-In.
Concentric

1-1/2

20

15

10

5

NA

NA

2

70

70

68

67

62

57

100-20

2 Pipe or 2-In.
Concentric

2

31

26

21

16

11

6

2-1/2

70

70

68

67

66

64

120-20

2 Pipe or 3-In.
Concentric

31-

49

48

47

45

44

43

Unit
Size

Termination
Type

Pipe Diameter

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-In.
Concentric

1-1/2

32

27

22

17

12

7

2

66

65

63

62

60

59

060-14

2 Pipe or 2-In.
Concentric

1-1/2

32

27

22

17

12

7

2

66

65

63

62

60

59

080-14
080-20

2 Pipe or 2-In.
Concentric

1-1/2

18

13

8

NA

NA

NA

2

66

65

63

62

57

52

100-20

2 Pipe or 2-In.
Concentric

2

29

24

19

14

9

NA

2-1/2

66

65

63

62

60

59

120-20

2 Pipe or 3-In.
Concentric

31-

46

44

43

41

40

38

Unit
Size

Termination

6

Number of 90 ° Elbows

Number of 90 ° Elbows

Pipe Diameter

Type

(In.)*

1

2

3

4

5

040-14

2 Pipe or 2-In.
Concentric

1-1/2

30

25

20

15

10

5

2

62

60

58

56

55

53

060-14

2 Pipe or 2-In.
Concentric

1-1/2

30

25

20

15

10

5

2

62

60

58

56

55

53

080-14
080-20

2 Pipe or 2-In.
Concentric

1-1/2

17

12

7

NA

NA

NA

2

62

80

58

56

51

46

100-20

2 Pipe or 2-In.
Concentric

2

27

22

17

12

7

NA

2-1/2

62

60

58

56

55

53

120-20

2 Pipe or 3-In.
Concentric

31-

43

41

39

37

35

34

Unit
Size

Termination
Type

Pipe Diameter

(In.)*

1

2

3

4

5

6

040-14

2 Pipe or 2-In.
Concentric

1-1/2

27

22

17

12

7

NA

2

57

55

53

51

49

47

060-14

2 Pipe or 2-In.
Concentric

1-1/2

27

22

17

12

7

NA

2

57

55

53

51

48

47

080-14
080-20

2 Pipe or 2-In.
Concentric

1-1/2

15

10

5

NA

NA

NA

2

57

55

53

51

46

41

100-20

2 Pipe or 2-In.
Concentric

2

24

19

14

9

NA

NA

2-1/2

57

55

53

51

49

47

120-20

2 Pipe or 3-In.
Concentric

31-

39

37

35

33

31

29

Number of 90 ° Elbows

Disk usage--Unless
othepMse stated, use perforated disk assembly (factory-supplied
in loose parts bag)
1 Wide radius elbow
$ Vent sizing for Canadian installations over 4500 ft (1370m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA--Not AHowed; pressure switch will not make
NOTES:
1 Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur
2 Size both the combustion-air and vent pipe independently, determine the smallest diameter allowed by the table for each pipe, then use the larger diameter for both
pipes.
3 Assume two 45 ° elbows equal one 90 ° elbow Long radius elbows are desirable and may be required in some cases
4 Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5 The minimum pipe length is 5 ft for all applications

3O

For applications

COMBUSTION
- AIR
INTAKE
HOUSING

nsing

BURNER
BOX

Sidewall
41.

terminations

For applications
_COMBUSTION
AIR

PIPE

4

Disassemble

5

Check

Concentric
OPEN
DRAIN

using

contaminants,
Sidewall
surfaces

and has less visible

prodacts
Exposed

Sidewall

confbustion=air

extended

beyond

insulating

pipes

2. Using

Termination

location

combustion-air

winter

Pipe

design

temperature

length

insulation

(it)

in unconditioned

mining

spaces

Termination

accumulation

ibr

exposed

J:Pr maximan_

cannot

as stated in Table

where

vent vapors

or air conditioning

be positioned
leaves

equip-

so it will

(such as inside

kit shou!d

kit should

exceed

pipe

2. from position

loose pipe fittings
as used

1. Determine

Fig. 36--Intake

option

Fig. 40

procedures

TO

pipe

Insta!l bracket

lines in Fig 40, rotate
DRILL

combustion-air

by dashed lines in Fig. 37, install 90 ° street elbow into 90 °
elbow, making U-fitting. A 180 _ U-fitting may be used.

will

in Fig. 37.

31

between

"A" in Fig. 42, 43, 44, 45, and 46 represents
pipes

separation.

or

rain

shields,

as

touching

or

2-in.

AIR AND VENT
8 3/4" FOR 3" KIT
6 3/4" FOR 2" KIT
MAINTAIN 12 IN.
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL.
MAXIMUM OF 24 IN. ABOVE ROOF.

jJJ

/

MAINTAIN

12 IN.

,.\__

_-_
.. . :..."

(18 IN. FOR CANADA)
MINIMUM CLEARANCE
ABOVE HIGHEST
ANTICIPATED
SNOW
LEVEL. MAXIMUM OF
24 IN. ABOVE ROOF.

12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
A93055

A93054

Fig. 38--Concentric Vent and Combustion-Air
Termination {Preferred}

Fig. 39--Concentric

Roof

IN. SEPARATION
BOTTOM OF
•COMBUSTION AIR AND
OF VENT

COMBUSTION-AIR

Vent and Combustion-Air
Termination

,,7

12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.

:...'
/

Z-COMBUSTION-AIR
(ELBOW PARALLEL
TO WALL)
A87225

Fig. 40--Sidewall

Termination

Side

BOTTOM OF
COMBUSTION AIR AND
OF VENT
12 IN.
CLEARANCE
ABOVE HIGHEST
ANTICIPATED SNOW
LEVEL OR GRADE,
WHICHEVER IS
GREATER.
A87226

of 12 in. or More

Fig. 41--Sidewall
32

Termination

of Less than 12 in.

A96128

Fig. 42--Rooftop

Termination

(Dimension "A" is Touching

or 2-In. Maximum

Separation)

AIR
VENT

A93057

A93056

Fig. 43--Concentric
Vent and Combustion-Air
Termination (Dimension "A" is Touching
2qn. Maximum Separation)

Fig. 44_Concentric
Vent and Combustion-Air
Termination (Dimension "A" is Touching
2qn. Maximum Separation)

Roof
or

Side
or

/

ff

AIR
COMBUSTION

A96129

A96130

Fig. 45--Sidewall
Termination of 12 in. or Less
(Dimension "A '° is Touching or 2-In.
Maximum Separation)

Fig. 46--Sidewall
Termination of More Than 12 in.
(Dimension "A" is Touching or 2-In.
Maximum Separation)
33

Table8--MaximumAllowableExposedVent PipeLength(Ft)WithInsulationin WinterDesign
TemperatureAmbient*
W_NTER DESIGN
TEMPERATURE

UNIT
SiZE

(°F)
20

MAXIMUM PIPE
DIAMETER
(iN.)
2

0

(N.)t

0
21

1/2

3/4

1

37

42

50

57

2

10

22

25

30

35

-20

2

5

14

17

21

25

20

2

30

55

61

70

7O

0

2

16

33

38

46

53

-20

2

9

23

26

33

38

20

2

37

2

20

70
45

70
55

7O

0

65
39

-20

2

11

27

31

39

45

20

2-1/2

41

70

70

70

7O

0

2-1/2

21

42

48

59

68

-20

2-1/2

11

28

33

41

49

20

3

49

70

70

70

7O

0

3

26

51

58

70

7O

-20

3

15

35

40

50

060ot4

080ot4
080°20

100o20

120o20

Pipe length
(ft) specified
for maximum
as specified
in Table 7
t Insulation
thickness
based on R value

10--Condensate

TNIDKNESS

3/8

040ot4

Step

iNSULATiON

pipe

lengths

of 35

located

in unconditioned

spaces.

Pipes

located

in unconditioned

space

cannot

exceed

63

59

total

allowable

pipe

length

per in

Drain

GENERAL
trap is shipped

Condensate

installed

connected
for UPFLOW
RELOCATED
for use

in the blower

shetf and facto W

applications
Condensate
trap must be
in DOWTNFLOW
and HORIZONTAL

applications
(ondensate

trap MUST

An external

trap is not required

this condensate

be used for all applications.
when connecting

The field drain connection (condensate
is sized _br 1/2=in
(PVC,
1/2=in
connection_
Drain pipe and fittings
ASTM
D1785, D246d,
confbnn
F656.

to ASTM

fittings,

a condensate

pump

select

3 2 to 45.

schedule

select

/

to ASTM

40 (PVC

a pmnp

applications.

or

acidic,

nature

typically

if a pH neutralizer

Check

is

A93058

conden=

Fig. 47--Freeze

switch
of

Unit must

a condensate

The

temperature

is required

ATION

fimaace,

drained

A/C,

and humidifier

together.

supplied

trap

connections

The

prior

Air

to the

(furnace,

&ain

&ains
must

furnace

&ain

A/C, or humidifier)

art open

or vented

drain

as close

possible

to prevent

siphoning

may be combined
have

an external,

connection

and
&ain

must be terminated

into

to the respective

of d_e equipment's

equipment

draining

of the _i/rnace is permissible
should

drain pipe and prohibit

be taken when

freezing

Caution

if allowed

and then mined

during

or below

freeze

cold
unless

protection.

and left

weather
&ain

when

trap

and

See Service

and

Instructions
_br winterizing
procedure. (See Fig.
to follow this caution will result in intermittent

as

&ain

ambient

to 32°F

line have adequate

conditions

using
&ain

draining
in damage

( aution

operated,

structure

unit operation.

connection

codes

&ops

Maintenance
47.) Failure

tield=

All

See Fig 48 ibr example of possible field drain attachment
1/2-in. CPV(
or PVC tee ibr vent and Ai( or humidifier

Outdoor

not be installed,

off in an unoccupied

with local authorities

drain
APPLI(

Protection

-->

in the pH range

of d_is condensate,

filter may be desired.

which

To avoid

wit}* an overflow

is mildly

Due to corrosive

to detem_ine

certified

is required,
_lmace

a pump

condensate

pH neutralizing

Primer must conform

and
must

and cement.

ibr condensing

sate spillage,
Furnace

or F493

use CSA or ELC

PVC drain pipe,

approved

32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED

trap or drain robe coupling)
PV(,
or 5/8-in
ID tube

must con_brm
m ANSI standards
or D2846. CPVC or PV( cement

D2564

In Canada,

When

the field drain to

trap

by local

may freeze

draining.

34

should

be taken

to prevent

may cause personal
may cause saturated
to plants.

draining

injuries.

where

Excessive

soil conditions

slippew

condensate

which may result

START-UP,
Step
1

ADJUSTMENTS

AND

SAFETY

CHECK

l--General
Furnace

must have a 115=v power

supply

properly

connected

and grounded.
NOTE:

Proper

polarity

is incorrect,

and fhmace

polarity

must

be maintained

control

stares

for 115-v wiring.

indicator

light

3. Natural

gas service

pressure

R, W/W1, G, and
on furnace control.

must not exceed

0.5 psig (14=in.

wc), but must be no tess than 0.1d psig (4.5=in.
4. Blower access panel must
electrical circuit to ff_rnace.

--€

These

furnaces
box

gas valve

if an overheat

Fig. 48--ExamNe
(ONDENSATE
Freezing
cause

cracks,

shielded,

and possible

water

trap and drain

damage

use condensate

may

freeze

and waterproof

heat

tape.

line

occur.

(flame

off power
rollout)

to the

occurs

combustion=air

in intermittent

unit

operation

in

supply

or performance

DO
will

satisfac-

Before operating furnace, check flame rollout manual reset switch
for continuity
If necessm% press button to reset switch.

may

Step

accesso_

See Installation

2--Semect

Setup

AIR (ONDITIONING

self_regulating,

or heat tape manufacturer's

heat tape in half" and wrap

2. Locate

condition

venting condition
before resetting
switch.
this switch. Failure to fbltow this caution

Instructions

The

recommenda=

to cooling

heat tape between

on itself

3 times.

sides of condensate

trap back.

(See

1

Remove

2

Locate

3

Detem_ine

4

Use Fig.

Switch
(A/C)

air conditioning

airflow

setup

Positions

SETUP

SWIT(HES

switches

are used

to match

furnace

unit used.

To set the desired

1. Fold

reset limit switch

and shuts

inadequate

l15=v

If fieeze

protection

3 to 6 watt per ff at 120v and 40°F

with accessory

result
tion.

to complete

opens

Correct

wc).

PROTE(TION

left in condensate

is required,

or equivalent
supplied
tions.

DRAIN

condensate

protection

of Field Drain Attachment

be in place

with a manual

This switch

enclosure.

or improper
NOT jumper

A94054

are equipped

in burner
burner

If

rapidly

does not operate.

2. Thermostat
wire connections
at terminals
Y/Y2 must be made at 24-v terminal block

PIPE FOR
A/C OR
HUMIDIFIER
OPEN
STAND y
DRAIN

flashes

cooling

airflow:

main f_./mace door and blower
Ai(2 sett_p switches

access

panel.

on l_urnace control.

(See Fig

32)

Fig. 49.)
3. Use

wire ties to secure

positioned

in notches

heat

tape in place.

of condensate

Wire

trap sides.

air conditioning
50 or wiring

NOTE:

Excessive

may cause
using field-supplied

fScmrer's

instructions

heat tape,

for all other

fbllow

installation

heat

5

proper

setup

caused

blowoff

by improper

in cooling

Aid

switch

setup

mode

main furnace

EAC=I
terminal

door

terminal
is only

and blower

is energized
energized

access

whenever

when

panel

blower

blower

operates.

is energized

in

heating.

CONDENSATE

CONTINUOUS
The

airflow

for two-speed

fan airflow

SETUP

main Nrnace
CF setup

desired

control

the application
appropriate

This

setup

airflow

on I:umace

schematic

fan

when

tow-cooling

feature

allows

to be adjusted.

access

panel.

control.
airflow

To

airflow:

(See Fig. 32.)
or

to determine

tow-cooling

proper

setup

(See Fig. 31 and 51.)

main I:umace door

SWITCHES

airflow

or low-cooling

continuous

58 or wiring

desired

or to select

door and blower

switches

of CF switches.

The furnace

35

units.

continuous

5. Replace

A93036

cooling

set desired

position

Heat Tape

tim mode

or low-cooling

4. Use Fig.

Trap

SWITCHES
to select

fan airflow

3. Detem_ine
airflow.

MINIMUM)_

SETUP

are used

continuous

2. Locate

TAPE_

(CF)

switches

is in continuous

1. Remove

WIRE TIE(S)_

FAN

CF setup

thermostat

Fig. 49--Condensate

airflow

condensate

Replace

HUM

(3 WRAPS

to determine

(See Fig. 31 and 51)

tape manu=

guidelines.

NOTE:

HEAT

schematic

of AiC switches

heat tape, approximately

1 wrap per ft.
5. When

used.

ties can be

(See Fig. 49.)

position
4. Wrap field drain pipe with remaining

tonnage

and blower

access

panel.

(SWI)
has 8 setup

requirements,

requiremenL

switches

Position

that may be set to meet

these setup switches

fbr the

AIR CONDITIONING
TONS (12,000 BTU/HR)

AIRFLOW
(CFM)

040,060 & 080-14
MODEL

1-1/2

525

X

080-20 & 106
MODEL

120 MODEL

2

700

X

X

X

2-1/2

875

X

X

X

3

1050

X

X

X

3-1/2

1225

X

X

X

4

1400

X

X

5

1750

X

X

6

2100

X-INDICATES

AN ALLOWABLE

X

SELECTION.

A/C OR CF AIRFLOW SELECTION
BASED ON 350 CFM/TON
MODEL
SiZE

_
_

_
_

_
_

_
_

CHART

_
_

_
_

_
_

040,060,
080-14

DEF

5252

700

875

10501

1225

1225

1225

080-20,100

DEF

7002

875

1050

1225

1400

17501

1750

DEF

700

8752

1050

1225

1400

17501

2100

120

1 DEFAULT

A/C AIRFLOW

2.DEFAULT

CONT. FAN AIRFLOW

WHEN A/C SWITCHES

ARE IN OFF POSITION

WHEN CF SWITCHES

ARE IN OFF POSITION

A02349

Fig. 50--A/C or OF Airflow Selection
Based on 3500FN/Ton
Step

--€

Chart

3--Prime

Condensate

Trap

With

Water

Condensate
trap must be PRIMED or proper draining may not
occur The condensate
trap has 2 internal chambers which can
ONLY

be primed

of condensate
intermittent
1. Remove

by pouring

trap. Failure
malt operation

upper

inducer

water into the inducer
to £41ow this caution
or performance

housing

&aia

1i2oin.

ID

drain side

will result

in

satis_tction.
connection

cap.

(See

Fig. 52j
2. Connect
housing
3. Insert

A04001

-_ Fig. 51--Example
of Setup Switch
Position
1, Remove
2. Locate

main
setup

filrnace
switches

dooI

and blower

on fm'nace

access

control.

in OFF

(See Fig. 32.)

description.

(See Fig. 31 and 51.)

and blower

access

NOTE:
HEAT

Ifa bypass

humidifier

Rise Adjust)

%r the increased
NOTE:

fire, ace door

should

cally compensates

in return

dampers

%r modulating

blower

fiom bypass.
motor

to

upper

fimnel

inducer

into tube.

drain. (See Fig. 53j
and robe t'rom

4--Purge

Gas

inducer

housing

and replace

cap and clamp.
Lines

If not previously
done, purge the lines aJ:_er all connections
been made and check %r leaks.

(Low

This compensates

air resulting

are used,

Step

SWI_3

fmmet

&ain connection

panel.

setup switch

be in ON position.

temperature

If modulating

is used.

fieldosupplied

into open field
5. Remove

4. Replace

robe

connection.

4. Pont 1 quart of water into fannetimbe.
Water should run
throngh inducer housing,
overfill condensate
trap, and flow

panel

3. See Table 9 for setup switch
main

fieldosupplied
&ain

automatio

dampers.

36

have

Table
SETUP
SWITCH NO.
SWI-1

SW1-2

9--Furnace

Status Code Recovery

OFF

Turn ON to retrieve up to 7 stored status codes for troubleshooting
assistance when R thermostat lead is disconnected.

OFF

AHows 2-stage operation
Turn ON when using 2 stage
tion when R to W/W1 closes
W/W1

Heat Mode

Comfort/Efficiency

OFF

Adjustment

sates for increased return air temperature
midifier

OFF

Self-Test

Turn ON for 400 CFM per ton. Turn OFF for 350 CFM per ton
Turn ON to initiate Component Self-Test for troubleshooting
tance when R thermostat lead is disconnected
Turn OFF when Self-Test is completed.

OFF

SW1-7

Blower OFF delay

ON or OFF

Control blower Off Delay time

8W1-8

Blower OFF delay

ON or OFF

Control blower Off Delay time

Table 10--Blower
DESIRED HEATING
MODE SLOWER

SINGLE=STAGE

Off Delay Setup Switch
Position

SETUP SWITCH (SW1o7 AND SW1-8) POSITION
SW1-7

SW1-8

OFF

OFF

120

ON

OFF

t50

OFF

ON

180

ON

ON

5--Sequence

of Operation

diagram,

modes

%llow

sequence

(See Fig. 31.) Read

of operation

and follow

diagram

1 Inducer Prepurge Period-The fi/mace control CPI_ rams on
inducer motor IDM and slowly increases the inducer nrotor
speed. When the low-heat pressure switch LPS closes, in&cer
motor RPM is noted by the filmace control CPU, and a 25-sec.
prepurge period begins. The RPM is used to evaluate vent
system resistance. This evaluation is then used to dete*mine
the required RPM necessa W to operate the induce, motor
du*ing the tow-heat prepurge pe*iod and tow-heat mode.

carefully
NOTE:
(WiWI

If a power intelTuption
or WiWl=and-W2),
the

occurs
control

during a call for heat
will start a 90-second

blower-only
ON period two seconds after power is restored, if the
thermostat is still calling for gas heating. The amber LED light wilt
period,

after which

will be ON continuous,

flash code

12 during

the 90=second

as tong as no limits

are detected.

90=second

furnace

period,

the

door

must

will

respond

to the

the LED
After

d_e

thermostat

NOTE: The }teat cycle can start in either high-or tow=heat If a
high-heat cycle is initiated, the furnace control CPU will deenergize the high=heat pressure switch relay HPSR to close the NC
contact and continues to increase the inducer motor speed after the
tow=heat pressure switch LPS closes. When the high-heat pressure
switch closes, inducer motor RPM is noted by the Nrnace control

normally
The

blower

through

the blower

control

(PI_,

motor

BLWM,

be installed

door

transformer
hot-surface

interlock
TRAN,
igniter

for power
switch
inducer

to be conducted

ILK
motor

to the

furnace

IDM,

blower

HSI, and gas valve

MODE)

See Fig. 28 or 61 fbr thernlostat connections

The wall daermostat %alls for heat", closing the R to W circuit.
The furnace control (PU perfbm_s a self-check, verifies the
tow=heat and high=heat pressure switch contacts LPS and HPS are
open

through

wiring

AND TWO-STAGE

If power is intmrupted, the stored histo W is erased When this
happens, the control (7PErwill initially select low=heat for up to 16
minutes and then switch to high-heat, as tong as the the*mostat
continues to call t'o, heat Subsequent selection is based on stored
histo W of d_em_ostat cycle dines.

operation.
schematic

with SW1-7. See

The t:m'nace will start up in either tow= or high-heat If the _i.V.T,
ace
starts up in low=heat, the t'umace control (PI_ detem_ines the
tow=heat on time (flora 0 to 16 minutes) which is permitted befbre
switching to high=heat.

Furnace control must be grounded fbr proper operation, or
control will lock out. Control is grounded through
green@ellow wire routed to gas valve and burner box screw.
Failure to fbllow this caution will result in intermittent unit

different

Used in conjunction
Table 10

This furnace can opeiate as a two-stage fi/mace with a single-stage
thernrostat because fm'nace control CPEr includes a programmed
adaptive sequence of controlled opeiation, which selects low-heat
or high-heat operation. This selection is based upon the stored
histo W of the tength of previous gas heating periods of the
single-stage thermostat.

1

Using

with SW1-8. See

10

NOTE: Low-heat=only switch, SWI=2, selects either d-le lowheat=only operation mode when ON, (see item 2 below) or
adaptive heating mode when OFF, in response to a call for heat.
(See Fig. 32) When the W2 them_ostat terminal is eneigized, it
will always cause high=heat operation when the R to W circuit is
closed, regardless of the setting of the tow-heat only switch

Never purge a gas line into a combustion chamber Never test
for gas leaks with an open flame LTse a commercially
available soap solution made specifically for the detection of
teaks to check all connections Failure to follow this warning
could result in fire, explosion, personal inju% or death
Step

assis-

Used in conjunction

Table

THERMOSTAT

HEATING (ADAPTIVE

OFF DELAY (SEC)
90

This compen-

caused with bypass hu-

Turn ON to decrease Low Heat airflow by 7 percent and High Heat
airflow 8 percent for maximum comfort. On 040 unit will decrease
Low-Heat Airflow 11 percent and High-Heat Airflow 10 percent.

ON

CFM per ton adjust
Component

with a single stage thermostat.
thermostat to NIow Low Heat operaand High Heat operation when R to
and W2 close

Turn ON to increase Low Heat airflow by 18 percent

Low Heat
Rise Adjust

SWI-¢

Description
DESCRIPTION
OF USE

8W1-3

8W1-5

Switch

NORMAL
POSiTiON

Adaptive

aWl-4

Setup

SWITCH
NAME

GV,

37

2. Igniter

Warm-!

Surface
period.
--9

p-At

Igniter

3. Trial-For-Ignition

the main

close to energize
ignited

closes,

a 2-second

will remain
2-second

until

proving

high-heat

gas valve

CPU

4. Flame-Proving-When
proving

sensor

the blower-ON
valve

GV-M

open.

two seconds,
fbr up

to three

Ignition-Lockout.

the fmnace

flame

control

is proved

flame

CPU

the

at the flame-

control

CPU begins

to hold

the gas

is not prm'ed

within

will close the gas valve

GV-M,

the ignition

Trials-For-Ignition
will

sequence

before

be reset

interrupting

or by interrupting

the

operation,

and continues

three hours, by monmntarily
f;arnace,

is also energized.

CPU will repeat

Lockout

or until

high-heat

(PU

more

afler the

GV-HI

If the burner

and the fire, ace control

The
it is

selects

period

the control

opens.
where

The HSI igniter

is sensed

FSE, the filrnace

delay

peGVR

begins.

burner

electrode

begins.

the flame

solenoid

warm-up

HSI. Five seconds

period

period

If the f_urnace control

the Hot
warm-up

contacts

to the burners

Igniter
flame

energized

flame

relay

GV, the gas valve

gas flow

by the Hot Surface

GVR

the igniter

gas valve

the gas valve

GV permits

period,

for a 17-sec igniter

Sequence-When

riod is completed,
gas valve

end of the prepurge

HSI is energized

going

after

115 vac power

to the

24 vac power

at SEC1

(not at W/W1,

to

automatically

or SEC2

to

G, R, etc.).

A99118

Fig. 52--Inducer

Housing

If flame

Drain Tube

is proved

fi/mace

control

operate

the inducer

longer

proved.

5. Inducer

Speed

furnace
flame

motor

CPU

If cycle
in speed

for n_aximum

efficiency.

determine

the

motor

required

in high-heat

period

RPM

begins

necessary

is used

to operate

the

Low- To High-

speed

When

the high-heat

until

is noted

motor

pressure
GV-HI
system

From

(PLY will

not

thermostat
thermostat.

R-to-W

High-

delaygas

mode.

flow

five

When

the themmstat

de-energizing
to the

burners,

motor

the

BLWM
after

the

to high-heat.
fi/rnace

to tow-heat

is closed

is then

to operate

seconds

Heat-The

fi'om high-heat

motor
is used

evaluation

I)om tow-heat

To Low-

closes.

The RPM

The blower

airflow

HPS

the high-heat

and the inducer

necessary

relay

the inducer

switch

This

RPM

switch

increase

CPU.

circuit

is opened,

control

pressure

resistance.

switches

switch

contlot

pressure

is energized

the required

CPU

ener-

the fiu'nace

switch HPS closes,

to high-heat

contIol

and electronic

and remain

If the filmace

and slowly

the high-heat

in high-heat

transition

stopping

38

Heat-

by the f_arnace control

vent

HUM

to high-heat,

contact

W circuit

mode

terminal

HPSR to close the N(

9. Blower-Off

inducer

the

cycle.

from low-heat

motor

GV-M

are energized

the heating

used to detem_ine

is then used to

EAC-I

the the high-heat

to evaluate

The RPM

proven,

are as ]:bllows:

airflow.

(:PLY will de-energize

RPM

This evaluation

gas valve

the humidifier

tem_inal

From

8. Switching

resistance

after

ON at high-heat

throughout

fi/mace

prepurge

is

and high-heat

the

will

the 25-sec

flame

combustion

is opened,

seconds

is mined

inducer

vent system

is to optimize

burner

contlol

after flanm sense.

High-heat-35

gas valve solenoid

CPU before

the fmnace

after

the

(:PLY switches

to evaluate

the

d_e

slightly

is opened,

7. Switching

Trap

and

Low-heat-d0
seconds after the gas valve GV-M
BLWM is tarried ON at low-heat
airflow.

gized

Condensate

the

mode

in low-heat,

speed

15 seconds

in tow-heat

delay-If

air cleaner

Fig. 53--Filling

be present,

starts

in high-heat,
speed

delay for low-heat

Simultaneously,

A99119

not

the inducer

starts

The reduction

BLWM

-\

the cycle

reduces

the inducer

blower-ON

should

IDM on high speed until flanm is no

(PLY increases

6. Blower-On

flame

will lock out of Gas-Heating

Change-If

control
sense.

when

CPU

control

while

the

when using a single-stage

is satisfie&

the R to

the

gas

valve

and

de-energizing

GV-M,
the

humidifier
terminal
HUM Theinducer
motorIDMwill
remain
energized
fora 15=second
post-purge
period.
The
blower
motorBLWMandaircleaner
terminal
EA(-I will
remain
energized
atlow=heat
airflowortransition
tolow=heat
airflowfor 90, 120, 150, or 180 seconds (depending on
selection

at blower-OFF

delay switches).

CPU is *:actory=set [br a 120=second
TWO=STAGE

THERMOSTAT

See Fig. 60 fbr thermostat

AND

The fim'lace

blower-OFF

additional
cooling
2

sec.

Single-Stage

In this mode,

This

fi/mace

can

single=stage

HEATING

includes

ON to select
closing

the

the

tow-heat

thermostat

R-to-Wl-and=W2
gardless

only

mode

circuit.

(;losing

always

causes

high=heat

of the low-heat-only

must be

in response

R-to=W1

circuits

of the setting

operation

SWI=2

operation,

"calls for heat _', closing the R to W1 circuit

tow-heat

the R to Wl=and-W2

circuits

per_brms

and verifies

or closing

[:ornace

control

heat

and high-heat

a self-check

pressure

switch

NOTE:

selects

re=

contacts

for high-heat.

LPS

the low=

and HPS

are

The start=up and shutdown

functions

1. above

apply

switching

fiom low- to high-heat

1. S_itehing

Front

WI circuit
control
relay

to 2-stage

CPU

heating

mode

described

as

well,

Heat-If

the thermostat

and the R to W2 circuit

will

de=energize

to close

except

closes,

the high-heat

the NC

contact

for

gas valve

motor

RPM

used

solenoid

to evaluate

vent

then used to determine
the

GV-HI

is energized

is noted by the ft_rnace contlol

inducer

motor

system

resistance.

the required
in high-heat

mode.

BLWM will tlansition
to high=heat
the R to W2 circuit closes.
2. Switching

Front

W2 circuit
_hrnace

CPU

will

to open

the

inducer

motor

high=heat
inducer

motor

solenoid

GV-M

switch
LPS
will tlansition

the R to W2 circuit

switch

and

energized

R to

If starting up in tow-cooling,

slowly

The

"calls

1, Single-Speed

circuit

starts

Cooling
50.

airflow

115=v when
When

Nmace

blower

the tl",ermostat

opened.

The outdoor

BLWM

will

continue

relay

continues

is based

ACR to

the outdoor

on stored

unit

to

to call _br
history

of the

control
the Nrnace

as shown

switches

control

ti'om

CPU

will

circuits

tlansition

cooling

airflow.

High-cooling

transitioning
motor

motor

airflow

the outdoor

BLWM

is based

from low-cooling
will

shut down

BLWM

transitions

air cleaner

115 vac whenever
When

relay ACR

switch

to high-

on the

AiC

to high-cooling

the

in Fig. 50.

compressor

The electronic

to

the air

and the R to G=and=Yl-and=YiY2

the f:tmaace blower

shown

blower

speed,

in Fig. 50.

energize

the R to Yl-and=Y2

circuits

starts
airflow

tow-cooling

relay ACR. When the air conditioning

furnace
airflow.

tl_e

CF selection

CPU

circuits

at low-cooling

is energized

When

gas valve

BLWM

terminal

the blower

the thermostat

while

the

to rnn at high-cooling

EAC-!

motor

is satisfied,

The outdoor
and electronic

for 1 minute

is energized

BLWM

with

is operating.

the R to G=and-Y

circuit

are

unit stops, and the t\m_ace blower
air cleaner terminal EAC-1 will remain

energized

fbr an additional

to reduce

the cooling

90 seconds.

off-delay

Thermostat

Jumper

to 5 seconds.

and Two-Speed

Y1 to DHUM
(See Fig. 32.)

Cooling

connections.)
circuits.

The

BLWM

airflow.

shown

termina!

EAC-1

staging.

in Fig.

BLWM

is operating

is satisfied,

is energized

the R=to-G-and-Y

unit will stop, and filmace
operating

at cooling

airflow

(See Fig. 32.)
thermostat

cooling

with

circuits
blower

connections)

NOTE:
The air conditioning
relay disable jumper ACRDJ must
be disconnected
to allow thermostat
contlol of the outdoor unit

circuits

on cooling

on the AiC selection

(See Fig. 60 for thetanostat

R=to-Y

and R-to-G-and-YiY2

motor

motor

and switch

conditioning

opened.
BLWM

unit,

air cleaner

to high-cooling.

and the R to G=and-Y1

is the true on=board

The

The electronic

the t:iu'nace
(from 0 to 20

the air conditioning

motor

If the

unit

as tong as the low=heat

R-to=G=and-Y

is based

speed,
blower

3. Two-Stage

blower

switching

the

unit in either

on-time

as the thermostat

which

outdoor

for cooling"

the outdoor

befbre

terminal

as long

filmace

NOTE:

Cooling

start the furnace

is permitted

the Y/Y2

the

opens.

closes

the tow-cooling

and then energize

selection

remains
closed.
The blower
motor
to tow-heat airflow five seconds a_:_er

(See Fig. 28 fi_r them_ostat
tl",ermostat

which

When

opens,

sufficiently,

open.

CPU determines

to a

control

to energize

CPU can start up the cooling

unit to high-cooling

the

low=heat

HPS

A(R

low- or high-cooling.

high-cooling,

aJ_er

pressure

is de-energized.

will

is

MODE

The thellnostat

The

contact

pressure

HPS

will remain

high=heat

the outdoor

must

the furnace

The _u_aace control

the

motor

closed,

to the required

GV-HI

reduces

switch

pressure
BLWM

N(

pressm'e

IDM

pressure

the

solenoid

remains

the

speed

the high=heat

gas valve

high=heat

(70()LING

energize

HPSR

When

blower

five seconds

in place

A(RDJ
in response

unit to high=cooling.

on low-cooling

to operate

To Low- Heat= If the thermostat

relay

decrease
RPM.

evaluation

The

airflow

and the R to W1 circuit

control

switch

the

High-

opens,

This

jumper
mode

relay

and switch

of

The wall tlaermostat
"calls for cooling",
closing
the R to
G=and-Y circuits. The R to Y1 circuit starts the outdoor unit

The RPM is

RPM necessa_-

disable

temfinal

cooling. Subsequent
selection
thermostat
cycle times.

the

and the inducer
CPU.

of the length

thermostat.

cooling

(See Fig. 32.) When

high=cooling,

inducer motor speed until the high=heat pressure switch HPS
closes. When the high=heat pressure switch closes, the highheat

relay

op-

operation.

can mm on the air conditioning

energize

switch

increase

the stored history

a

CPU

of contIolled

or high-cooling

of the single-stage

the adaptive

with

contlol

Y/Y2

minutes

R to

pressure

sequence

unit

fiu'nace

If the power is interrupted,
the stored histoQ" is erased and the
_hmace control CPU will select tow=cooling
[br up to 20

the [:urnace

and slowly

the

(Adap-

CPU

minutes)

in item

and vice versa.

Low- To High-

is closed

HPSR

and delays

adaptive
upon

period

to enable

control

open.

the

The air conditioning

call for cooling.

for

Cooling

cooling

because
low-cooling

is based

cooling

be connected

switch.

The wal! themxostat
The

to

Two-Speed

a two=speed

themaostat

which

previous

the thermostat

to reduce

connections.)

operate

a programmed

eration,
only switch

to DHUM

(See Fig. 32)

and

(See Fig. 61 for them_ostat

control

connections

the tow-heat

Y/Y2

T]hermostat

This selection
NOTE:

Jumper

to 5 seconds

tive Mode)

delay

TWO=STAGE

90

off'delay

are

closes

or closes

high-cooling.

The

low-cooling

speed,

Nmace

blower

motor

the true on-board

for an

Yl-and-Y2

39

the R to G and=Y1

the

R to Y1 circuit

starts

(F selection
start

on tow-cooling
as shown

the outdoor

l:br low-

circuits

the outdoor

and the R to G=and=Y1

motor BLWM

circuits

circuits

R to G and=Yl-and=Y2
circuit

unit
starts

fi_r
on
the

airflow which

is

in Fig. 50. The R to
unit

on

high=cooling

spee& and the R to G=and-YY2 circuits start the furnace
blower motor BLWM at high=cooling ariflow. High-cooling
airflow is based on the A/C selection shown in Fig. 50.

CONTINL

The electronic air cleaner terminal EAC=I is energized with
115 vac whenever the blower motor BLWM is operating
When the thermostat is satisfied, the R to G-and=Y1 o1"R to
G=and=Yl-and=Y2 circuits are opened. The outdoor unit stops,
and the furnace blower BLWM and electlonic air cleaner

ous blower

the R to G circuit

motor

BLWM

shown

MODE
is closed

will operate

airflow

is initially

Factory

is energized

by the thermostat,

at continuous-blower

selection

in Fig. 50

EA(-1

default

as tong

based

the

(ontinu-

on the CF selection

is shown

as

the blower

airflow.
in Fig

blower

58. Terminal

motor

BLWM

is

energized.
During

a call for heat, the blower

motor

See Fig 54=57 %* Thexmidistat connections

tow-heat

the

BLWM

to continuous

midrange

BLWM
OFF

The dehumidification output, DHUM on the Thermidistat should
be connected to the furnace control thermostat tem_inal DHUM.

airflow,

will

ON until

OFF

will transition

airflow,

whichever

remain

and remain

BLWM

blower

is lowest.

the main

in high-heat)

exchangers

to heat more

quickly,

blower-ON

delay

at tow=heat

period

The

burners

for the blower-ON

and 35 seconds

the blower

low=heat

blower
then

(60

seconds

shut

the furnace

then restarts

or

motor

ignite

delay

allowing

airflow,

in
heat

at the end of the

or high-heat

airflow

respec-

tively.

When there is a dehumidK}" demand, the DHLM input is activated,
which means 24 vac signal is removed fiom the DHUM input
terminal. In other words, the DHUM input logic is reversed. The
DHUM input is mined ON when no dehumidify demand exists.
Once 24 vac is detected by the furnace contlol on the DHUM
input, the furnace control operates in Thennidistat mode. [f the
DHUM input is low for more than 48 hours, the furnace control
reverts back to non-Thermidistat mode.

The blower
after

motor BLWM

d_e heating

control

CPU

airflow

during

transitioning
When

will

will revert

to continuous-blower

is completed.

In high-heat,

&op

the

the

blower

selected

"calls

will operate

motor

to low=heat

delay

for high-cooling",

motor

furnace

period

be%re

airflow.

at high-cooling

the blower

airflow
the

BLWM

blower=OFF

to continuous-blower

is satisfied,

circuit is closed and
the Nrnace blower
airflow to 86% of
on=board CF selec=

cycle

the thermostat

BLWM

The cooling operation described in item 3. above applies to
operation with a Thermidistat. The exceptions are listed below:

the blower

airflow.

BLWM

When

will operate

motor

the thermostat
an additional

befbre

When

is opened,

the blower

motor

%r an additional

5 seconds,

if no other function

the R to G circuit

continue

operating

requires

blower

motor

Continuous

BLWM

Blower

To select

back

BLWM

to

will

operation.

Speed

different

transitioning

90

seconds
at high=cooling
airflow
continuous=blower
airflow.

b. High cooling-When the R to G-and Y/Y2 circuit is closed
and there is a demand for dehumidification, the furnace
blower motor BLWM will &op the blower airflow to 86%
of high-cooling airflow High=cooling airflow is based on
the AiC selection shown in Fig. 50

Selection

from

continuous=blower

Thermostat

speeds

fiom the room

thermostat,
momentarily
turn off the FAN" switch or pushbutton on the room them_ostat for 1=3 seconds after the blower
motor BLWM is operating. The furnace contlol CPU will shift
the continuous=blower
airflow fi'om the factory setting to the
next

c. Cooling off-delay=When the "call for cooling" is satisfied
and there is a demand for dehumidification, the cooling
blower=off delay is decreased fiom 90 seconds to 5
seconds.
SUPER=DEHUMIDIFY

BLOWER

When

terminal EAC=I wilt remain energized ibr an additional 90
seconds. Jumper YI to DHUM to reduce the cooling off-delay
to 5 seconds (See Fig. 32)
THERMIDISTAT MODE

a. Low cooling=When the R to G=and-Yl
there is a demand fbr dehumidification,
motor BLWM will &op the blower
low-cooling airflow which is the true
tion as shown in Fig. 50.

OUS

highest

CF

Momentarily
stat

MODE

the

continuous-blower

shift

shift the continuous-blower
as

shown

When

installed

the timing

demand

deiiost

the blower

used

airflow.
control

cycles.

following

50.

one more
you

will

to the lowest

selection

can

be

a power

inten'uption.

connections.

will remain
OFF

When
begins

control

BLWM

airflow,

to avoid

Whenever

the furnace

and remain

b. High coMing=When the R to Y/Y2 cicuit is closed, R to G
circuit is open, and there is a demand for dehumidifiation,
the furnace blower motor BLWM will drop the blower to
65% of high=cooling airflow fbr a maximmn of 10 minutes
each cooling cycle or until the R to G circuit closes or the
demand for dehumidification
is satisfied. High-cooling
airflow is based on the Ai( selection shown in Fig. 50.

sequence

motor

the midrange
BLWM

The

with a heat pump, the furnace

changes

Y1 or Y/Y2,

Low-cooling airflow is the true on=board CF selection as
shown in Fig. 50.

up

enough,
airflow

50.

Fig.

PUMP

See Fig. 56-59 for thermostat

a. Low coMing=When the R to Y1 circuit is closed, R to G
circuit is open, and there is a demand for dehumidification,
the furnace blower motor BLWM will &op the blower
airflow to 65% of tow-cooling airflow for a maximmn of
10 minutes each cooling cycle or until the R to G circuit
closes or the demand fbr dehumidification is satisfied.

procedure

in Fig.

in

again at the thermo-

as many times as desired and is stored in the memow

to be automatically
HEAT

this

shown
airflow

eventually
selection

repeat

as

switch

If you

changed

tion. The cooling operation desc*ibed in item 3 above also applies
to operation with a Thermidistat The exceptions are tisted betow:

airflow

off the FAN

increment.
(F

Super-Dehumidify7 mode can only be entered it"the furnace control
is in Thermidistat mode and d_ere is a demand ibr dehmnidifica=

will

selection

turning

control

long blower

WiWI

is energized

CPU will transition

at cooling

whichever

airflow,

on until the main burners

the W/W1
a normal

befbre

input

inducer

to or bring
airflow,

The blower

ignite,

coming

during

along with

tow=heat

is the lowest.

for 25 seconds

automatically

ofttimes

on
or

motor

then shut OFF

back on at heating

signal

disappears,

post=purge

period

the
while

furnace
changing

the blower airflow. If YY2 input is still energized,
the furnace
control CPU will transition
the blower motor BLWM airflow to

c. Cooling off-delay=When the "call for cooling" is satisfied
and there is a demand for dehumidification, the cooling
blower=off delay is decreased fiom 90 seconds to 5
seconds.

cooling

airflow.

is still

energized,

If Y/Y2

blower

motor

input

the furnace

BLWM

signal disappears
control

to low-cooling

CPU
airflow.

and the Y 1 input
wil!

transition

the

If both the Y1 and

YY2 signals disappear at the same time, the blower motor BLWM
will remain on at low-heat
airflow ibr d-_e selected blower-OFF
delay

4O

period.

At the end

of the blower=OFF

delay,

the blower

motor

BLWM

will shut OFF unless

case the blower
airflow.

motor

( OMPONENT

TEST

The t\_rnace
system

setup

test

switch

a component

procedure,

test system

ensure

EXAMPLE:

blower

SW1-6

to help diagnose

failure.

that

and all time

there

delays

are

have

no them_ostat

expired.

Turn

will not operate

signals

test sequence

at medium
b. After

control
speed

waiting

or until

furnace

BLWM

all time

delays

have

g

CPU tn*ns the inducer
and keeps

igniter
control

motor

it ON through
the furnace

CPU

ON at midrange

then

control

turns

airflow

IDM ON

2

step c.

ON fbr 15 seconds,

The

EAC

terminals

CPU

rams

test is completed,

the

blower

when

1 or more

25, 41, or 42) will flash. See Smwice Label
or Service/Stares

(ode

Instructions

NOTE:
To repeat component
OFF and then back ON.
Step

stares codes

on blower

test, turn

setup

b

c

Furnace

is

switch

e

codes.

orifice

SIZE;

pressure

burner

size in furnace.

ALWAYS

to obtain

enclosure

SWI=6

Remove

regulator

fbr low-

and high-heat

NEVER

CHECK

AND

input rate

fl'ont
always

be measured

Move

setup

seal caps that conceal

switch

Turn

low=heat

gas valve

SWI°2

with the

adjustment

regulators.

on cont*ol

screws

(See Fig. (52)

center

fire, ace locked

to

(in) to increase

at altitudes

thermostat

adjnsting

counterclockwise

RATE

the input rating for altitudes

by 2 percent

Adjust

manifold

Furnace

input

rate

furnace

rating

plate

1. Detem_ine

fbr each

above

1000 ft above

pressure

to obtain

screw

connections

(3/32)

(out) to decrease

to ON posiin low-heat

on control

hex Allen

to

wrench)

input rate or clockwise

input rate.

DO NOT set tow=heat manifbld

pressure

less than 1.3-in.

wc or more than 1.7-in. wc tbr natural

gas. If manitbld

outside this range, change
pressure in this range.

orifices

main burner

natural

gas orifice

_'

2000 ft must be

sea tevel
by

5 percent

to obtain

pressure

is

manifPld

_+2 percent

of input

size and manifbld

rate

pressure

b. Obtain

specific

ave*age

c Verii}' fire, ace model.
58MVP Furnaces
d. Find

installation

(at installed

gravity
Table

ahimde

from

for

in Table

f_ Follow

heat

intersection
manifbld

natural

value

and specific

pressure

orifice

settings

size

h Turn high-heat adjusting screw (5/64 hex Allen w*ench)
counterclockwise (out) to decrease input rate or clockwise
(in) to increase rate.

11.

gas heat value

to find

g. Jumper R and W/W1 and W2 thermostat connections on
fhmace control. (See Fig. 32.) This keeps I:urnace locked in
high=heat operation

tocal gas supplie*

to 4500

gravity
and

for proper

It, use USA

and specific

lines

IR

f\ Move setup switch SWI-2 to OFF position after completing
low-heat adjustment.

from tocal

11 can only be used fbr model

For Canadian altitudes of 2000
of 2001 to 3000 ft in Table 11.

e Find closest
Table 11.

altitude)

e

NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered &ill bit of
con'ect size. Never redrill art orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.

on

input
heat value

.

DO NOT bottom out gas valve regulator a_[iusting screw.
This can result in unregulated manifPld pressure and result in
excess overfire and heat exchanger f_ilures.

for

input rate.

n-rest be within

a Obtain ave*age
gas supplier.

NOTE:
altitudes

manifold

Remove

burner

ORIFI(E

d. Jumper R and W/W1
start furnace,

(11,

NOTE:

In Canada, the input rating must be derated
altitudes of 2000 ft to 4500 ft above sea level.

correct

and verif)

It.

In the [ .S.A,
reduced

input rate.

operation.

access panel

of stares

gas input rate on rating ptate is for installations

up to 2000

proper

tion. (See Fig. 32.) This keeps

g--Adiustments

SET GAS INP[T

wc fbr high heat
wc fbr tow heat

motor

then OFF.

the blower

fbr explanation

3%in.
16-in

NOTE:
Manifbld pressure
MUST
burner box cover REMOVED.

operating.
After the component

(heck

Adjust
a

then OFF.

fbr 15 seconds,

are energized

pressure:

to obtain

ASSUME
VERIFY.

d. After shutting the blower motor BLWM OFF, the I:urnace
colmol CPU shuts the inducer motor IDM OFF.
NOTE:

ft

if the control

is as fbllows:

15 seconds,

the hot surface
c. The

ff altitude)

* Furnace is shipped with No. 45 orifices In this example,
all main burner orifices are the correct size and do not need

on

to be changed

test feature

any thermostat

a. The furnace

2000

1050 Btuicu

Manifold

the

expired.
The component

(0

value

a

To initiate

(See Fig. 32.)

The component

is receiving

in which

at continuous

in the case of a component

to the control

NOTE:

operate

Specific gravity
0.62
Therefore:
Orifice No. 45

features

component

O is still energized,

will

Heating

problem

inputs

BLWM

gravity

in

to point

of

NOTE: DO NOT set high=heat mani%1d pressure less than 3.2-in.
we or more than 3 8-in. wc fbr natural gas If manifbld pressure is
outside this range, change main burner orifices to obtain manifPld
pressures in this range.
i When con'ect input is obtained, replace caps that conceal
gas valve regulator adjustment screws Main burner flame
should be clear blue, almost transparent. (See Fig 640

low= and high=heat
operation

j Remove jumpers R to WiWI and R to W2
3 Verify natural gas input rate by clocking gas meter.
NOTE: Be sm'e all pressure robing, combustion-air and vent
pipes, and burner enclosure f?ont are in place when checking input
by clocking gas meter.

41

THERMIDISTAT

TWO-STAGE
FURNACE

NOTE
HEAT

STAGE

SINGLE-SPEED
AIR CONDITIONER

THERMIDISTAT

TWO-STAGE
FURNACE

SINGLE-SPEED
HEAT PUMP

11

2
RVSCOOLING_

N/A

NOTE11

HEATSTAGE3
(FURNACEHi)_

HEAT

STAGE

1

COOL

STAGE

1

HEAT
STAGE
2 [_
(FURNACE LO)
HEAT/COOL
STAGE
(COMPRESSOR)

FAN [_
24 VAC HOT [_
DEHUMIDIFY

[_

24 VAC COMM

[_

[Z2_

1

FAN

[_

HOT

[_

/ .........
24 VAC

DEHUMIDIFY

24 VAC

COMM

[_

[_ HUM
[_ HUM
HUMIDIFIER
HUMIDIFY

[_

(24 VAC)

HUMIDIFY

N/A

..../ 4VAC/
I

_[

HUMIDIFIER

......

N/A [_

OUTDOOR

_/_c

coS_S°,%_
[2_

[

OUTDOOR
SENSOR

_,,

OONNEDT'ON
_[2_
See notes 2, 5, 7, 10, and 11

See notes 1, 2, 4, 6, 7, 9,10,11,

and 15
A00277

A00275

Fig. 54_Two-Stage

Furnace with
Conditioner

THERMIDISTAT

Single-Speed

TWO-STAGE
FURNACE

Fig. 56--Two-Stage

Air

TWO-SPEED
AIR CONDITIONER

Furnace with Single-Speed
Pump (Dual Fue{)

THERMIDISTAT

TWO-STAGE

Heat

TWO-SPEED

FURNACE

HEAT

PUMP

NOTE11
HEAT

STAGE

2

COOL

STAGE

1

HEAT

STAGE

t

COOL

STAGE

2

RVS COOLING

HEA(_CMOpQRLSsl
AGLEo1) _

NOTE12

HEA_FSTAGEE3 _
FAN

[_

24 VAC HOT

[_

DEHUMIDIFY

[_

24 VAC COMM

[_

......

NEAT/COOLSTAGE
2_
(COMPRESSORHI)

_

......

"fiTE_2 _

.....

FAN[_ ......................
[_

_

HUMIDIFY

....... [_

_

HUM

"'"-.

_VACHO_[_ ..........
[_
DEHOM'D'FY_
..........................
_4MAOOOMM[2
_ ............. [_:

.............

[_ HUM

......4VAC, i
/

HUMIDIFIER

.....

HUMIDIFY

...............

HUMIDIFIER(24
VAC)

N/A [_
N/A [_

OUTDOOR
SENSOR

Os_00_
_

OUTDOOR
_1:_

DONNEOT,ON
See notes 2, 5, 8,10,

coS_Sc°,_o,
l_
I1, and 12

See notes 1,2, 3, 4, 6, 8, 9, t0,12,13,

and 15

A00276

Fig. 55--Two-Stage

Furnace with Two-Speed Air Conditioner

A00278

Fig. 57--Two-Stage

42

Furnace with Two-Speed
Pump (Dual Fue{)

Heat

DUAL FUEL
THERMOSTAT

TWO-STAGE
FURNACE

NOTE 11

SINGLE-SPEED
HEAT PUMP

TWO-STAGE
THERMOSTAT

TWO-STAGE
FURNACE

NOTE

11

NOTE

12

TWO-SPEED
AIR CONDITIONER

[_

HEAT STAGE 2
(FURNACE LO)
HEAT/COOL STAGE 1
(COMPRESSOR)

E2_

FAN [_
24 VAC HOT [_

24 VAC COMM

[_

[_ HUM

N/A [_
RVS SENSING

_

HUM
See notes 2, tl,

[_

and 12

oo oOO s, so

o_o_R
_

A00281

Fig. 60--Two-Stage
Thermostat With Two-Stage
nace and Two=Speed Air Conditioner

OONNECT,ON
_

Fur-

See notes 1, 2, 4, 11, 14, 15, and 16
A00279

Fig. 58--Dual FuemThermostat
Furnace and Single-Speed

DUAL FUEL
THERMOSTAT

with Two-Stage
Heat Pump

TWO-STAGE
FURNACE

TWO-SPEED
HEAT PUMP

S;NGLE-STAGE
THERMOSTAT

TWO-STAGE
FURNACE

TWO-SPEED
AIR CONDITIONER

RVS COOLING

HEA_c_o_OO_ESs_o_4
_ .....................
C_ ...............................

HEA_FS_C_E_
_
...............
_
,,_
HEA_,cCOO_EST_o_,_
_ NOTE,_
_ ............................
FAN [_
24 VAC HOT [_

................

[_

_4MACCOMM_
...................
_ ...............................
N_A[2
_
RVS SENSING

]

HUM

See note 2

BNUM

[_

A02348

CONNECT,ON
/_ ....
See notes 1, 2, 3, 4, 12, 13,14,

Fig. 59--Dual Fuel Thermostat
Furnace and Two-Speed

Fig. 61--Single-Stage
Thermostat
With Two-Stage
Furnace and Two-Speed Air Conditioner

15, and _00280

With Two-Stage
Heat Pump

43

Notes for Fig. 54-61:
1. Heat pump
2. Refer

MUST

to outdoor

have a high pressure
equipment

3. Select the "ZONE"
4. Outdoor

position

Air Temperature

switch

Installation

on the two=speed
Sensor

fbr dual fi/el applications,

Instn/ctions

must

for additional

heat pump

be attached

No.1

on Thermidistat

No.

1 on Them_idistat

should

be set in ON position

7. Dip switch

No. 2 on Them_idistat

should

be set in OFF

should

be set in ON position

8. Dip switch

11. Optional

Option
should

connection.

to allow

10 "Dual

connection.

13. Furnace

must

be made to the furnace

Sensing

15. DO NOT

SELECT

board,

16. Dip switch

to control

If wire is connected,

control

14. The RVS

Fuel Selection"

If wire is connected,

Them_idistatiThem_ostat

control

No.

ThermidistatiThem_ostat

12. Optional

be set in OFF

position

for air conditioner
for heat pump

position

installations.

This is f_ctolw deJitult.

installations.

for single-speed

compressor

operation.

delimit.

No. 2 on Thermidistat

10. NO connection

procedure.

control.

6. Dip switch

9. Configuration

and setup

in all dual iq/el applications.

5. Dip switch

This is fhctow

should

infbrmation

to control

"L" should

the "F[ RNACE

This is controlled

SWI=2

compressor

operation.

ON in all dual 1:i/el applications.

when using
on filrnace

a Thermidistat.
control

should

be set in ON position

staging.
jumper

on Nrnace

control

should

be removed

via fm'nace

control

algorithm

to allow

unit staging.

heating

operation

not be connected
INTERFACE"

internally

D on Dual Fuel Thermostat

terminal

ACRDJ

outdoor

its own high°stage

terminal

HUM

dip switch
furnace

for two-speed

must be turned

This is internally

or "BALANCE

by the Them_idistatiDual

shoutd

be set in OFF

position

shoutd

be set in ON position

This is Pactory

used to sense defrost

POINT"

option

del:ault.

operation

on the two-speed

heat pump

Fuel The*mostat.
fbr single-speed

compressor

operation

This is f_cto W defitult
17. Dip switch

D on Dual Fuel Thermostat

44

for two-speed

compressor

operation,

TABLE 11 - ORBFmCE B{ZE* AND MANIFOLD
PRESSURES
FOR GAS iNPUT RATE
(TABULATED DATA BASED ON 20,000 BTUN HIGH-HEAT / 13,000 BTUH LOW-HEAT PER BURNER,
BERATED 2%/t000 FT ABOVE SEA LEVEL)
ALTITUDE

AVG, GAB

RANGE

HEAT VALUE

c

c

<:
¢q.

c

0.64

Orifice

Mrffid Press

Orifice

Mnfld Press

Orifice

(Btu/cu it)

No.

High/Low

No.

High/Low

No

High/Low

No.

900

43

3.5 / 1.5

43

3.6 / 1.5

43

3.8 / 1.6

42

32 / 1.3

925

44

3.8 / 1.6

43

3.5 / 1.5

43

3.6 / 1.5

43

37 / 1.6

950

44

3.6 / 1.5

44

3.8 / 1.6

43

3.4 / 1.4

43

35 / 1.5

975

44

3.4 / 1.5

44

3.6 / 1.5

44

3.7 / 1.6

44

38 / 1.6

1000

44

3.3 / 14

44

3.4 / 1.4

44

3.5 / 1.5

44

35 / 1.5

t025

45

3.8 / t.5

44

3.2 / 1.4

44

3.3 / 1.4

44

34 / 1.5

t050

45

3.5 / 1,5

45

3.7 t 1.5

45

3.8 / 1.5

44

33 / 1.4

t075

45

3.4 / t.4

45

3.5 / 1.5

45

3.7 / 1.5

45

3.8 / 1.6

1100

45

3.3 / t,4

45

3.4 / 1.4

45

3.5 t 1.5

45

3,6 / 1.5

U,S,A

800

43

3.8 / 16

42

3.2 / 1.4

42

3.3 / 1.4

42

35 / 1.5

Altitudes

825

43

3.6 / 15

43

3.7 / 1.6

43

3.8 / 1.6

42

32 / 1.4

2001

850

43

3.4 / 1.4

43

3.5 / 1.5

43

3.6 / 1.5

43

37 / 1.6

to 3000

875

44

3.7 / 1.5

44

3.8 / 1.6

43

3.4 / 1.4

43

35 / 1.5

or

900

44

3.5 / 1.5

44

3.6 / 1.5

44

3.7 / 1.6

44

38 / 1.6

Canada

925

44

3.3 / 14

44

3.4 / 1.4

44

3.5 / 1.5

44

35 / 1.5

Attitudes

950

45

3.7 t t,5

44

3.2 / 1.4

44

3.3 / 1.4

44

34 / 1.4

2001

075

45

3.5 / 1,5

45

3.7 t 1.5

45

3.8 / 1.6

44

32 / 1.4

to 4500

1000

45

3,4 t 1.4

45

3,5 / 1,5

45

3.6 / 1.5

45

3.7 / 1.6

775

43

3.7 / 1.6

42

3.2 / 1.3

42

3.3 / 1.4

42

34 / 1.4

800

43

3.5 / 1.5

43

3.6 / 1.5

43

3.8 / 1.6

42

32 / 1.3

825

44

3.8 / 1.6

43

3.4 / 1.4

43

3.5 / 1.5

43

37 / 1.5

850

44

3.6 / 1.5

44

3.7 / 1.6

44

3.8 / 1.6

43

34 / 1.5

875

44

3.4 / 1.4

44

3.5 / 1.5

44

3.6 / 1.5

44

37 / 1.6

900

44

3.2 / 1.3

44

3.3 / 1.4

44

3.4 / 1.4

44

35 / 1.5

925

45

3.7 / 1.5

45

3.8 t 1.5

44

3.2 / 1.4

44

33 / 1.4

950

45

3.5 / t,5

45

3.6 / 1.5

45

3.7 / 1.6

45

3,8 / 1.6

750

43

3.7 / 16

43

3.8 / 1.6

42

3.2 / 1.4

42

33 / 1.4

775

43

3.5 / 15

43

3.6 / 1.5

43

3.7 / 1.6

43

38 / 1.6

800

44

3.7 / 16

43

3.4 / 1.4

43

3.5 / 1.5

43

35 / 1.5

825

44

3.5 / 15

44

3.6 / 1.5

44

3.7 / 1.6

43

34 / 1.4

850

44

3.3 / 14

44

3.4 / 1.4

44

3.5 / 1.5

44

35 / 1.5

875

45

3.8 / 1.6

44

3.2 / 1.4

44

3.3 / 1.4

44

34 / 1.5

000

45

3.5 / t,5

45

3.7 t 1.5

45

3.8 / 1.5

44

32 / 1.4

025

45

3.4 / 1.4

45

3.5 / '1.5

45

3.6 / 1.5

45

3,7 / 1.6

725

43

3.6 / 15

43

3.8 / 1.6

42

3.2 / 1.4

42

33 / 1.4

750

43

3.4 / 14

43

3.5 / 1.5

43

3.6 / 1.5

43

38 / 1.6

775

44

3.7 / 15

44

3.8 / 1.5

43

3.4 / 1.4

43

35 / 1.5

800

44

3.4 / 1.5

44

3.6 / 1.5

44

3.7 / 1.6

44

38 / 1.6

825

44

3.2 / 14

44

3.3 / 1.4

44

3.4 / 1.5

44

35 / 1.5

850

45

3.7 t 1,6

45

3.8 / 1.5

44

3.2 / 1.4

44

34 / 1.4

875

45

3.5 / t,5

45

3.6 t 1.5

45

3.7 / 1.5

45

3.8 11.6

900

45

3.3 / 1,4

45

3.4 t 1.4

45

3.5 / 1.5

45

3.6 t 1.5

675

42

3.2 / 1.3

42

3.3 / 1.4

42

3.4 / 1.4

42

35 / 1.5

700

43

3.6 / 1.5

43

3.7 / 1.6

43

3.8 / 1.6

42

33 / 1.4

725

44

3.8 / 1.6

43

3.5 / 1.5

43

3.6 / 1.5

43

37 / 1.6

750

44

3.6 / 1.5

44

3.7 / 1.6

44

3.8 / 1.6

43

35 / 1.5

775

44

3.4 / 14

44

3.5 / 1.5

44

3.6 / 1.5

44

37 / 1.6

800

45

3.8 / 1.6

44

3.3 / 1.4

44

3.4 / 1.4

44

35 / 1.5

825

45

3.5 / t.5

45

3.7 / 1.6

45

3,8 t 1,6

44

33 / 1.4

85O

45

3,4 t t.4

45

3,5 / 1,5

45

3.6 t 1.5

45

3,7 ! 1.6

0
to

to

<:
¢q.

GAS

0.62

MnfldPress

3001

o

OF NATURAL

Orifice

2000

C

GRAVITY

0,60

AT ALTITUDE
(ft)

c

SPECIFIC

0,58

4000

4001

Mnfld

Press

High/Low

c

o

to

<:
¢o

5000

5001
to
6000

6001
to
7000

* Orifice

numbers

showr_ in BOLD

are factory-installed

45

TABLE

li

(TABULATED

- ORIFICE
DATA BASED

SBZE*

AND

ON 20,000
BERATED

ALTITUDE

(ft)

(Btu/cu

700i
c

to
8000

>,
"E
0
<

800i
to
9000

-_
c
o

900i

<.

to

i0000

* Orifice

numbers

2%!1000

shown

in BOLD

ft)

FT ABOVE
SPECIFIC

0.58

HEAT VALUE
AT ALTITUDE

PRESSURES

HIGH-HEAT/13,000

AVG. GAS

RANGE

o

MANIFOLD
BTUH

FOR
BTUH

GAS

mNPUT

LOW-HEAT

RATE

PER BURNER,

SEA LEVEL)
GRAVITY

OF NATURAL

0.60

GAS

0.62

0,64

Orifice

Mnfld Press

Orifice

Mnfld Press

Orifice

Mnfld Press

Orifice

Mnfid Press

No.

High/Low

No.

High/Low

No.

High/Low

No.

High/Low

650

43

3.8 / 1.6

42

3.2 / 1.4

42

34 / 1.4

42

35 / 1.5

675

43

3.5 / 1.5

43

3.7 / 1.6

43

38 / 1.6

42

32 / 1.4

700

44

3.8 / 1.6

43

3.4 / 1.4

43

35 / 1.5

43

36 / 1.5

725

44

3.5 / 1.5

44

3.6 / 1.5

44

38 / 1.6

43

34 / 1.4

750

44

3.3 / 1.4

44

3.4 / 1.4

44

35 / 1.5

44

36 / 1.5

775

45

3.7 / i.6

44

3.2 / 1.3

44

33 / 1.4

44

34 / 1.4

800

45

3.5 t 1.5

45

3.6 / i.5

45

3.7 t i.6

44

32 / 1.4

825

45

3.3 / 1.4

45

3.4 t 1.4

45

3,5 / 1.5

45

3,6 / 1.5

625

43

3.8 / 1.6

42

3.2 / 1.4

42

33 / 1.4

42

34 / 1.5

650

43

3.5 / 1.5

43

3.6 / 1.5

43

38 / 1.6

42

32 / 1.3

675

44

3.7 / 1.6

43

3.4 / 1.4

43

35 / 1.5

43

36 / 1.5

700

44

3.5 / 1.5

44

3.6 / 1.5

44

37 / 1.6

44

38 / 1.6

725

44

3.2 / 1.4

44

3.4 / 1.4

44

35 / 1.5

44

36 / 1.5

750

45

3.7 / i.5

45

3.8 t 1.8

44

32 / 1.4

44

33 / 1.4

775

45

3.4 / 1.5

45

3.6 / 1.5

45

3.7 / 1.6

45

3,8 / 1.6

600

43

3.8 / 1.6

42

3.2 / 1.4

42

33 / 1.4

42

34 / 1.4

625

43

3.5 / 1.5

43

3.6 / 1.5

43

37 / 1.6

43

38 / 1.6

650

44

3.7 / 1.6

44

3.8 / 1.6

43

34 / 1.5

43

36 / 1.5

675

44

3.4 / 1.4

44

3.5 / 1.5

44

37 / 1.5

44

38 / 16

700

44

3.2 / 1.3

44

3.3 / 1.4

44

34 / 1.4

44

35 / 15

725

45

3.6 / 1.5

45

3.7 / 1.6

45

3.8 t 1.6

44

33 / 1.4

are factory-installed

4d

ONtOFF

BURNER

FLAME

ALLEN SCREW
ADJUSTMENT
(UNDER CAP)

SWITCH

ADJUSTMENT
ALLEN SCREW
(UNDER CAP)

INLET
PRESSURE
TAP

MANIFOLD J
A89020

Fig. 64_Bumer
Table 12--Altitude

ENCLOSURE
REFERENCE
PRESSURE TAP

Fig. 62--Redundant

Automat{c

Gas Valve

Derate Multiplier

for U.S.A.

ALTITUDE
{FT}
0--2000

% OF
DERATE
0

DERATE MULTIPUER
FACTOR FOR U.S.A.*
1.00

2001--3000

4--6

0.95

3001--4000

6--8

0.93

4001--5000

8--10

0.91

5001--6000

10--12

0.89

6001--7000

12--14

0.87

7001--8000

14--16

0.85

8001--9000

16--18

0.83

9001--10,000

18--20

0.81

MANIFOLD
PRESSURE
TAP
A97386

Flame

* Derate multiplierfactorb

based on midpointaltitude _raltituderange.

CANADA
At installation

altitudes

must be derated
r---

BURNER A

Station

or Dealer

altitude,

see example

plier
_

ORIFICE

b

DO NO]: re&ill orifices
Improper
drilling (burrs, ont-oi:
ronnd
holes, etc,) can cause excessive
burner
noise and
misdirection
of burner
flanles
7his will result in flame
ures.

of burners

and heat

exchangers,

causing

d

correct

above

Table

adjustment (if required),

2000

ft, this _ilrnace has been approved

%r each 1000 J:'tabove
multiplier

input

rate

£_r

as derate multi-

box cover.

Check

that

input to be clocked

Obtain

gas

valve

average

heat

always

Be

heating

value

altitude

Consult

of gas heating

be per%treed

with

X

Derate
Multiplier
Factor

=

Furnace Input Rate
at Installation
ANtude

t00,000

X

0.91

=

91,000

caps

are

(at altitude)

in place

fiom

%r

local

gas

setup

h

Jumper

local

fbr calculations

is

gas utility

for altitude

value

i

Let f_/mace

j

Measure

k. Reikr
1. Multiply

gas appliances

switch

SWI-2

fire, ace locked

and pilots.

to ON position.
in tow-heat

(See Fig

32)

operation.

R to W/W1
run for 3 minutes

in tow-heat

time (in sec) for gas meter

tion. Note

47

of gas used

Check and veriJ:)- orifice size in furnace. NEVER ASSUME
THE ORIFICE
SIZE ALWAYS
CHECK
AND VERIFY.

This keeps

INPUT FURNACE

Furnace Input Rate
at Sea Leve_

value

sure

g. Move

sea level. See

_hctor and example

_=XAMPLE: I00,000 BTUN NIGH-NEAT
INBTALL'_D AT 4300 FT.

adjustment

for your

i\ Turn off all other

derate

12 %r derate

burner

proper

adjustment

UNITED STATES
for a 2 percent

correct

and use 095

fitctor.

Reinstall

NOTI:::

f3il°

e

At altitudes

determine

above

supplier.

(See Fig. 630

a Calculate high-altitude

To

ft, this furnace
Gas ( onversion

Orifice
c

impingement

to 4500

by an authorized

NOTI::: Clocking gas input rate MUST
the burner box cover INSTALLED

A93059

Fig. 83--Burner

J:i"om 2000

5 percent

operation,

to complete

1 revolu-

reading.

m Table

13 for cubic ft of gas per hr.

gas rate cu ftihr by heating

value

(Bmicu

ft).

m Movesetup
switch
SW1-2
toOFFposition
and
jmllper
R
andWiWlandW2tl-iermostat
connections.
(See
Fig32.)
Thiskeeps
furnace
locked
inhigh-heat
operation
Repeat
itemsithrough
1tbrhigh-heat
operation.
input from rating

Btu heating

input

Heating value of gas
Time for 1 revolution
Gas rate

plate

Btuicu

is 100,000

975 Bmicu ft
of 2=cu fi dial

input

ft altitude)

Table

Bmh

the orifice

size and manifold

is within

_+2 percent

of the I:umace

NOTE:

Measured

gas inputs

_+2 percent

installed

of that

(high

stated

Bmh

pressure

at sea level or derated

at higher

adjustment

must

operate

and tow heat)

furnace

rating

must

plate

particularly
2. When

R, WiWl,
arid
call for heat.

W2

thermostat

perature

rise.

For

high=heat

position

forget

to return

3. This

setup

Nmace

airflow

1

1
cu fl

2
cu

Rate Cu Ft/Hr
SECONDS

5

FOR

cu R

REVOLUTION

1

SIZE
1
cu fl

OF

TEST
2
cu fl

DiAL
5
cu fl

to OFF

a. Check

gas input

b. (heck

&rate

c. (heck

all return

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

d. Ensure

15

240

480

1200

55

65

131

327

control

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21
22

171
164

343
327

857
818

62
64

58

116

290

SET THERMOSTAT

23

157

313

783

66

56
54

112
109

281
273

When

24

150

300

750

68

53

106

265

anticipator

25

144

288

720

70

51

103

257

the R=WiWl

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

causing

using

for low-

position

and remove

Low

Heat Rise

Guide

HEAT

600

80

45

90

225

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

Fig. 65 illustrates

35

103

206

514

90

100

200

500

92

80
78

200
196

draw measurements.

36

40
39

37

97

195

486

94

38

76

192

38
39

95
92

189
185

474
462

96
98

38
37

75
74

188
184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

108

34

68

170

44

82

164

409

108

33

67

167

45

80

160

4OO

46

78

157

391

110

33

65

164

47

76

153

383

112

32

64

161

48

75

150

375

118

31

62

155

49

73

147

367

120

30

60

150

has started

1. To operate

Series

amp draw
subbase
should

heat anticipator
When

method

manufhcturer's
and for varying

using an electronic

heat

terminals

R and W.

should

mm

while

the tlaermostat

wires

of obtaining

in

can be

NOT be in d_e circuit

is operating

in low-heat,

during

current

thermostat

amp

be taken after blower
in low=heat.

setup

switch

ammeter

instructions
heating

SW1-2

to

leads across

for adjusting

the

cycle length.

them_ostat,

set cycle rate for 3

per hr.

3. Remm
setup switch SW1-2
thermostat
on subbase,

48

thermostat

measurements

ON position (See Fig. 32) and connect
thermostat
subbase R-W.
2. See thermostat

2=Stage

of components

has no subbase,

The amp reading
and Nmace

is used.

170 and later.

the

fi'om R and WiWI

finl_ace

on furnace

for Variable-Speed

the amp draw

If thermostat

an easy

SW1-3

thermostat,

Accurate

must be disconnected
nleasurement.

restrictions

ANTICIPATOR

and anticipator

232

operation.

switch

Furnaces

only at the thermostat

240

range

rise is outside

when a bypass humidifier

a non-electronic

116

proper
the

location.)

Condensing

120

cycles

within

and

than 0.5=in. wc.

Adjust

Troubleshooting

31

R=W2

providing

rise

in

DO NOT

ducts tbr excessive

greater

is in ON position

30

SW1-2

if applicable.

and supply

pressure

cmTent.

operain ON

(See Fig. 32 for switch

and high-heat

for altitude

circuit.

ten>

as follows:

must be set to match

The thermostat

NOTE:

switch
contlol.

of automatically

static

Electronic

motor

setup

furnace

d_e temperatme

(See Fig. 32 fbr switch
e. Check

is

air ten>

for tow=heat

on fine, ace rating plate. If temperature
proceed

measuring

return-air

to detem_ine

on fire, ace conUoi

on

of testing.

is capable

this range,

obtained

subtract

place

R-W2

switch

to maintain

specified

SWI=2

This practice

ducts.

stabilize,

operation,

arid jumper

as

ducts as near f:urnace

readings

temperature

switch

rise

do not see heat exchanger

rise can be determined

setup

rise specified

air temperature

and supply

readings

jumper upon completion
tem_inai location.)

FOR

or
for

with stlaight-run

supply=air

Temperature

by placing

OFF

REVOLUTION

of

to follow

areas not designed

of temperature

heat does not affect

them_ometer
from

position

SIZE OF TEST DiAL

oll unit

of mi@oint

the heat exchangers

Determine

in return

important

peramre

NOTE:

ranges

plate.

Be sure thern_on_eters

so that radiant

be

when

tion

SECONDS

specified

is OFF. Failure

in overheating

within

rating

1. Place thermometers

per that stated above when installed

TaNe 13--Gas

limits

a few degrees

may result

altitudes

n. Remove
jumper
across
connections
to terminate

within

flue gas in heat exchanger

on the furnace
follows:

In this

input rate.

heat

on

be

is within

condensing
condensate.

as possible.
within

must

this caution

Furnace

100,425

example,

rise

Operation

70 sec
13)

103 X 975

TelTlperature

rise range when setup switch SW1-4

fi X cu ft&r

103 cu ftihr (from

Btu heating

2000

RISE
1

rating plate.

EXAMPLE:
(High=heat
operation
at0
Furnace

SET TEMPERATURE

to OFF

position

and

replace

CHECK
TERMINALS WITH
THERMOSTAT REMOVED
(ANIT!CIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)

PRESSURE

This control
operation

AMMETER

proves

SWITCHES
operation

of the &aft

inducer

Check

switch

inducer

motor

as _bllows:

1

Turn off ll5-v

2

Remove

power

control

to fk/mace.

access

12=pin wire harness

door

and

at inducer

disconnect

motor

3

Tufa on 115=v power

4

Set d'*em_ostat to "call

to furnace
_br heat." When

fhnctioning

stares

properly,

code

pressure

42 will

switches

flash

on

are

t:m'nace

control approximately
20 sec after them_ostat switch is closed.
If either a status code 31 or 32 is flashed when inducer motor
is disconnected,

the t_urnace will shut itself down immediately.

Detem_ine

reason

properly
10 TURNS

the

5. Turn off 115=v power
6. Reconnect
access

FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE:

50 AMPS ON AMMETER
10 TURNS AROUND JAWS

8

= 0.5 AMPS FOR THERMOSTAT
ANTICIPATOR
SETTING

Step

7--Check

This section

covers

the installation
pressure
section

switches
as part

CHECK
This

the safety
were

shuts

air-circulating

in the

if t'tu'nace

method

block off remm

appear

on furnace
opening

Start-up

system

and

procedure

and energizes

the

this limit control

method

is to

check

be unblocked

this

that the limit is functioning
if there

a status

code 33

to permit

nomaal

contlol.

established

sa_?ly

to

Put away

2

Verify

the

is a restricted

4

(ycle

5

(hock
tions

7. Leave

has been operating

has shut off burners,

limit

control,

properly

can

be

and the furnace

return-air

failure. If the limit control does not _hnction
cause must be detemained
and corrected.

it

during

flmction

motor

wire

harness.

Reinstall

furnace

to furnace.

to desired

temperature

tools and instruments

flame

rollout

manual

blower

and

(lean

up debris.

reset switch
main

access

has continuity.
doors

are

properly

be_bre

valve,

overheats.

of checking

should

inducer

them_ostat

1

6. Review

air after Nmace

By using
operate

gas

of at least 5 minutes.

3. The return-air
air circulation.

will

sensor,

(ONTROL

motor

2. As soon as limit control
will

checked

off the gas control

1. The recommended
£_r a period

that must be checked

flame

operation.

LIMIT

blower

gradually

The

all

of nomaal

PRIMARY

control

controls

not

door.

3. Verii)
that
installed.

Controls

is complete

did

CHECKLIST

Draw Check with Ammeter

Safety

Reset

switches

to _hrnace.

7. Turn on 115-v power

A96316

Fig. 65--Amp

pressure

and cot_'ect the condition.

duct or motor
this test, the

49

test _i/rnace
operation

with room

thermostat.

of accessories

per

User's

Manual

with owner.

literature

packet

near furnace.

manul:acturer's

instruc-

CH ECKLmST--BNSTALLATION
LOAD CALCULATION
Condensate

Brain

Heating Load (Btuh)
Unit Level or Pitched Forward
Cooling Load (Btuh)
Internal Tubing Connections
and Traps

Furnace Model Selection
COMBUSTION

External Drain Connection
Sloped

AND VENT PIPING

Termination

Free of Kinks

Leak Tight and

Location
Condensate

Trap Primed before Start-Up

Roof or Sidewalt
Heat Tape Installed if Required
Termination

Kit -- 2 Pipe or Concentric

Combustion-Air

CBECKMBT--BTARToUp

Pipe Length
Gas Input Rate
(Set Within 2 percent of Rating Plate)

Combustion-Air

Pipe Elbow Quantity

Vent Pipe Length

Temperature

Rise Adjusted

Thermostat

Anticipator

Vent Pipe Elbow Quantity
Anticipator Setting Adjusted or
Pipe Diameter Determined

from Sizing Tabte
Cycle Rate (3 Cycles per Hr) Selected

Pipe Sloped To Furnace
Safety Controls

Cheek Operation

Pipe Insulation
Primary Limit

Over Ceitings

Pressure Switches
Low-Ambient

Exposed Pipes

5O

5i

Copyright

2004 CARRIER

Manufacture_
B°°kLL_.
Tab 16al 8a

reserves
PC 101

Corp.,

7310 W. Morris St • Indianapolis,

the right
Catalog

to discontinue,
No

535-80110

or change

IN 46231

58mvp13si

at any time, specifications

Pd_ted in U.S.A.

Form

or designs

58MVP-13SI

without

notice
Pg 52

and without
1-04

incurring

obligations,

Replaces:

58MVP-12SI



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Page Count                      : 52
Page Layout                     : SinglePage
Page Mode                       : UseNone
Producer                        : Goby Monitor Application version 3, 2, 1, 4
Create Date                     : Fri Apr 20 15:14:02 2007
Author                          : 
Title                           : 
Subject                         : 
EXIF Metadata provided by EXIF.tools

Navigation menu