Product Data
25HCD3
Comfort™ 13 Heat Pump
with PuronrRefrigerant
1 --- 1 / 2 t o 5 N o m i n a l To n s
the environmentally sound refrigerant
Carrier heat pumps with Puronrrefrigerant provide a collection of
features unmatched by any other family of equipment. The 25HCD
has been designed utilizing Carrier’s Puron refrigerant. The
environmentally sound refrigerant allows consumers to make a
responsible decision in the protection of the earth’s ozone layer.
NOTE:Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S13.0 -- 14.5 SEER/ 11.0 -- 12.2 EER/ 7.7 -- 8.5 HSPF
SMicrotube Technologytrefrigeration system
SIndoor air quality accessories available
Sound
SSound level as low as 69 dBA
SSound levels as low as 69 dBA with accessory sound blanket
Comfort
SSystem supports EdgerThermidistattor standard thermostat
controls
Reliability
SPuronrrefrigerant -- environmentally sound, won’t deplete the
ozone layer and low lifetime service cost.
SScroll compressor
SInternal pressure relief valve
SInternal thermal overload
SHigh pressure switch
SLoss of charge switch
SFilter drier
SBalanced refrigeration system for maximum reliability
Durability
WeatherArmortprotection package:
SSolid, durable sheet metal construction
SDense wire coil guard
SBaked--on powder paint
Applications
SLong--line -- up to 250 feet (76.20 m) total equivalent length, up
to 200 feet (60.96 m) condenser above evaporator, or up to 80 ft.
(24.38 m) evaporator above condenser (See Longline Guide for
more information.)
SLow ambient (down to --20_F/--28.9_C) with accessory kit
2
MODEL NUMBER NOMENCLATURE
12345678910111213
N N A A A/N N N N A/N A/N A/N N N
25 H C D 3 36 A 0 0 3 0
Product
Series
Product
Family Tier Major
Series SEER Cooling
Capacity
Grille
Variations Open Open Voltage Minor
Series
25=HP H=RESHP C=Comfort D=Puron 3=13SEER A=Dense Grille
W=Wide Grille
0=Not
Defined
0=Not
Defined
3=208/230---1
5=208/230---3
6=460/3
0, 1, 2...
the environmentally sound refrigerant
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
STANDARD FEATURES
Feature 18 24 30 36 42 48 60
Puron Refrigerant XXXXXXX
Scroll Compressor XXXXXXX
FieldInstalledFilterDrier XXXXXXX
Front Seating Service Valves XXXXXXX
Internal Pressure Relief Valve XXXXXXX
Internal Thermal Overload XXXXXXX
Long Line capability XXXXXXX
Low Ambient capability with Kit XXXXXXX
Suction Line Accumulator XXXXXXX
High Pressure Switch XXXXXXX
Loss of Charge Switch XXXXXXX
X=Standard
25HCD3
3
PHYSICAL DATA
UNIT SIZE SERIES 18 --- 30 24 --- 30 30 --- 30, 50 36 --- 31, 50,
60 42 --- 31, 50 48 --- 31, 50,
60 60---30, 50, 60
Operating Weight lb (kg) 119
(54.1)
124
(56.4)
149
(67.7)
169
(76.7)
180
(81.6)
208
(94.3)
250
(113.4)
Shipping Weight lb (kg) 137
(62.3)
142
(64.5)
170
(77.3)
189
(85.9)
200
(90.9)
228
(103.6)
282
(127.9)
Compressor Type Scroll
REFRIGERANT Puron(R---410A)
Indoor Control Piston
49
Piston
57
Piston
67
Piston
70 (31)
73 (50,60)
Piston
76
Piston
80 (31)
82 (50, 60)
TXV
(Puron Hard
Shutoff)
Outdoor Heating Piston # 42 49 55 57 63 65 76
Charge lb (kg) 4.0
(1.81)
5.11
(2.32)
5.83
(2.64)
6.06
(2.75)
6.75
(3.06)
7.72
(3.50)
11.00
(4.99)
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty (CFM) 1800 2100 3000 3000 3400 3400 4000
Motor HP 1/12 1/10 1/5 1/5 1/4 1/4 1/4
Motor RPM 1100 1100 1100 1100 1100 1100 800
COND COIL
Face Area (Sq ft) 9.8 11.2 15.0 17.2 17.2 15.0 17.6
Fins per In. 20 20 20 20 20 20 20
Rows 1 1 1 1 1 2 2
Circuits 3 4 5 5 5 6 8
VALVE CONNECT. (In.) ID
Vapor 5/8 5/8 3/4 3/4 7/8 7/8 7/8
Liquid 3/8
REFRIGERANT TUBES (In.) OD
Rated Vapor* 5/8 5/8 3/4 3/4 7/8 7/8 1 --- 1 / 8
Liquid 3/8”
*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for HP systems with Puron refrigerant:
Vapor Line Sizing and Cooling Capacity Losses -- PuronrRefrigerant 1-- Stage Heat Pump Applications
Unit
Nominal
Size (Btuh)
Maximum
Liquid Line
Diameters
(In. OD)
Vapor Line
Diameters
(In.) OD
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
Standard
Application Long Line Application Requires Accessories
26 --- 50
(7.9---15.2)
51 --- 80
(15.5---24.4)
81 --- 100
(24.7---30.5)
101 --- 125
(30.8---38.1)
126 --- 150
(38.4---45.7)
151 --- 175
(46.0---50.3)
176 --- 200
(53.6---60.0)
201 --- 225
(61.3---68.6)
226 --- 250
(68.9---76.2)
18,000
1 --- S t a g e
HP with
Puron
3/8
1/2 1 2 3 4 6 7 8 9 10
5/8 0 0 1 1 1 2 2 3 3
24,000
1 --- S t a g e
HP with
Puron
3/8
5/8 0 1 1 2 3 3 4 4 5
3/4 0 0 0 0 1 1 1 1 1
30,000
1 --- S t a g e
HP with
Puron
3/8
5/8 1 2 3 3 4 5 6 7 8
3/4 0 0 1 1 1 2 2 2 3
7/8 0 0 0 0 1 1 1 1 1
36,000
1 --- S t a g e
HP with
Puron
3/8
5/8 1 2 4 5 6 7 9 10 11
3/4 0 0 1 1 2 2 3 3 4
7/8 0 0 0 0 1 1 1 1 2
42,000
1 --- S t a g e
HP with
Puron
3/8
3/4 0 1 2 2 3 4 4 5 6
7/8 0 0 1 1 1 2 2 2 3
48,000
1 --- S t a g e
HP with
Puron
3/8
3/4 0 1 2 3 4 5 5 6 7
7/8 0 0 1 1 2 2 2 3 3
60,000
1 --- S t a g e
HP with
Puron
3/8
3/4 1 2 4 5 6 7 9 10 11
7/8 0 1 2 2 3 4 4 5 5
1 --- 1 / 8 0 0 0 1 1 1 1 1 1
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-
tion Guidelines
25HCD3
4
REFRIGERANT PIPING LENGTH LIMITATIONS
Maximum Line Lengths:
The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for
allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.
Maximum Line Lengths for Heat Pump Applications
MAXIMUM ACTUAL LENGTH
ft (m)
MAXIMUM EQUIVALENT LENGTH{
ft (m)
MAXIMUM VERTICAL
SEPARATION ft (m)
Units on equal level 200 (61) 250 (76.2) N/A
Outdoor unit ABOVE
indoor unit 200 (61) 250 (76.2) 200 (61)
Outdoor unit BELOW
indoor unit See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
Maximum Total Equivalent Length{-- Outdoor Unit BELOW Indoor Unit
Size
Liquid Line
Diameter
w/ TXV
HP with PuronrRefrigerant --- Maximum Total Equivalent Length{
Vertical Separation ft (m) Outdoor unit BELOW indoor unit;
0 --- 2 0
(0 --- 6.1)
21 --- 30
(6.4 --- 9.1)
31 --- 40
(9.4 --- 12.2)
41 --- 50
(12.5 --- 15.2)
51 --- 60
(15.5 --- 18.3)
61 --- 70
(18.6 --- 21.3)
71 --- 80
(21.6 --- 24.4)
18000
HP with
Puron
3/8 250* 250* 250* 250* 250* 250* 250*
24000
HP with
Puron
3/8 250* 250* 250* 250* 250* 250* 250*
30000
HP with
Puron
3/8 250* 250* 250* 250* 250* 250* 250*
36000
HP with
Puron
3/8 250* 250* 250* 250* 250* 250* 250*
42000
HP with
Puron
3/8 250* 250* 250* 250* 250* 250* 150
48000
HP with
Puron
3/8 250* 250* 250* 250* 230 160 --- ---
60000
HP with
Puron
3/8 250* 225* 190 150 110 --- --- --- ---
* Maximum actual length not to exceed 200 ft (61 m)
{Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = o u t s i d e a c c e p t a b l e r a n g e
LONG LINE APPLICATIONS
An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing,
and vertical separation between the indoor and outdoor units.
For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories
are required:
HP WITH PURONrREFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
3/8 80 (24.4) 20 (6.1) vertical or 80 (24.4) total 80 (24.4)
Note: SeeLongLineGuidelinefordetails
25HCD3
5
ACCESSORIES
ORDER NUMBER DESCRIPTION 18--- 30 24---30 30---30 30---50 36--- 31 36---50 36--- 60 42--- 31 42--- 50 48--- 31 48--- 50 48--- 60 60--- 30,
50 60--- 60
HC32GE234 BALL BEARING MOTOR X
HC34GE239 BALL BEARING MOTOR X
HC36GE219 BALL BEARING MOTOR X X X X
HC34GE240 BALL BEARING MOTOR X X
HC38GE232 BALL BEARING MOTOR
HC38GE461 BALL BEARING MOTOR X
HC38GE228 BALL BEARING MOTOR
HC40GE226 BALL BEARING MOTOR X X
HC40GE466 BALL BEARING MOTOR X
HC40GE228 BALL BEARING MOTOR X
HC40GE467 BALL BEARING MOTOR X
KAACH1701AAA CRANKCASE HTR X X X X
KAACH1601AAA CRANKCASE HTR X
STANDARD CRANKCASE HTR S SS SSSSSS
KSACY0101AAA CYCLE PROTECTOR X X X X X X X X X X X X X X
KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X X X X X X X X
KSAHS1701AAA HARD START X X X X X X X X X X X X X X
KHAIR0101AAA ISOLATION RELAY X X X X X X X X X X X X X X
KSALA0301410 LOW AMBIENT PSW X X X X X X X X X X X X X X
KSALA0601AAA{MOTORMASTER 230V X X X X X X X X X X X X X X
KHAOT0201SEC OUTDOOR THERMOSTAT X X X X X X X X X X X X X X
KHAOT0301FST OUTDOOR THERMOSTAT X X X X X X X X X X X X X X
KHALS0401LLS SOLENOID VALVE X X X X X X X X X X X X X X
KHASS0606MPK* SNOW STAND RACK XXXXXXXXXXXXX
KSASH0601COP SOUND BLKT X X X X X X X X X X X X
KSASH2101COP SOUND BLKT X X
KAACS0201PTC STARTASSISTPTC X X X X X X X X X X X X X X
KSASF0101AAA SUPPORT FEET X X X X X X X X X X X X X X
KAATD0101TDR TIME DELAY RELAY X X X X X X X X X X X X X X
KSATX0201PUR TXV PURON HSO XXXX
KSATX0301PUR TXV PURON HSO XXXXX
KSATX0401PUR TXV PURON HSO XXX
KSATX0501PUR TXV PURON HSO X X
x = Accessory S = Standard
*AvailablethroughRCD
{Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, isolation relay, hard
shut---off TXV or liquid line solenoid valve.
ACCESSORY THERMOSTATS
PART NUMBER PROGRAM GAS ELECTRIC HEAT PUMP HEAT COOL
TC --- PHP01 5 --- 2 D a y √ √ 3 2
T C --- N H P 0 1 NP √ √ 3 2
TCSNHP01 NP √ √ 2 1
TB ---PHP01 5 --- 2 D a y √ √ √ 2 1
T B --- N H P 0 1 NP √ √ √ 2 1
THERMOSTAT ACCESSORIES
PART NUMBER BRIEF DESCRIPTION THERMOSTATS USED WITH
TSTATXXCNV10‡ Thermostat Conversion Kit (4 to 5 wire) --- 10 pack All Carrierbranded thermostats
T X --- L B P 0 1 LargeDecorativeBackplate T P --- P x x , T P --- N x x , T C --- P x x
T X --- M B P 0 1 Medium Decorative Backplate T C --- N x x , T B --- P x x
T X --- S B P 0 1 Small Decorative Backplate T B --- N x x
25HCD3
6
ACCESSORY USAGE GUIDELINE
Accessory
REQUIRED FOR LOW--- AMBIENT
COOLING APPLICATIONS
(Below 55F / 12.8C)
REQUIRED FOR
LONG LINE APPLICATIONS*
REQUIRED FOR
SEA COAST APPLICATIONS
(Within 2 miles / 3.22 km)
Accumulator Standard Standard Standard
Ball Bearing Fan Motor Ye s {No No
Compressor Start Assist Capacitor and
Relay Ye s Ye s No
Crankcase Heater Ye s Ye s No
Evaporator Freeze Thermostat Ye s No No
Hard Shutoff TXV Ye s Ye s Ye s
Isolation Relay Ye s No No
Liquid Line Solenoid Valve No See Long---Line Application Guideline No
Motor MasterControl or
Low Ambient Switch Ye s No No
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Application Guideline.
{Additional requirement for Low ---Ambient Controller (full modulation feature) MotorMasterrControl.
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when using MotorMasterr
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor
at each start up.
Usage Guideline:
Required for reciprocating compressors in the following
applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves
compressor lubrication on restart and minimizes the chance of
liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
6. Isolation Relay
An SPDT relay which switches the low--ambient controller out of
the outdoor fan motor circuit when the heat pump switches to
heating mode.
Usage Guideline:
Required in all heat pumps where low ambient kit has
been added.
7. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts
refrigerant liquid flow in response to compressor operation. It is to
be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.
Usage Guideline:
An LLS is required in all long line heat pump
applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.
8. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order
to maintain head pressure within normal operating limits. The
control will maintain working head pressure at low--ambient
temperatures down to 0_F(--18_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55_F
(12.8_C).
9. MotorMasterrLow--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C), it
maintains condensing temperature at 100_F10_F (37.8_C
6.5_C).
Usage Guideline:
A MotorMasterrLow Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
25HCD3
7
Accessory Description and Usage (Listed Alphabetically) -- CONTINUED
10. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also is required to enable special
thermostat features such as auxiliary heat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
11. Outdoor Thermostat
An SPDT temperature--actuated switch which turns on
supplemental electric heaters when outdoor air temperature drops
below a user--selected set point.
Usage Guideline:
Electric supplemental heat applications in non--variable
speed indoor units when electric heat staging is desired.
12. Secondary Outdoor Thermostat
An SPDT temperature--actuated switch which turns on third--stage
of supplemental electric heaters when outdoor air temperature
drops below the second--stage set point.
Usage Guideline:
Outdoor thermostat applications where electric heater is
capable of 3--stage operation.
13. Snow Stand Rack
Coated wire rack which supports unit 18 in. (457.2 mm) above
mounting pad to allow for drainage from unit base.
Usage Guideline:
Suggested in the following applications:
Heat pump installations in heavy snowfall areas.
Heat pump installations in snow drift locations.
Heat pump installations in areas of prolonged
subfreezing temperatures.
All commercial installations.
14. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces the
sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft.
(4.577 m) to quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft. (3.05 m) apart.
15. Thermostatic Expansion Valve (TXV) Bi--Flow
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Usage Guideline:
Accessory required to meet AHRI rating and system
reliability, where indoor not equipped.
Required in all heat pump applications designed with
Puron refrigerant.
16. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
Note: Most indoor unit controls include this feature. For those that
do not, use the guideline below.
Usage Guideline:
Accessory required to meet AHRI rating, where indoor
not equipped.
25HCD3
8
ELECTRICAL DATA
UNIT
SIZE V/PH OPER VOLTS* COMPR FAN MCA
MIN
WIRE
SIZE†
MIN
WIRE
SIZE†
MAX
LENGTH
ft (m)‡
MAX
LENGTH
ft (m)‡
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
18 --- 30
208/230/1 253 197
48.0 9.0 0.5 11.8 14 14 66 (20.1) 62 (18.9) 20
24 --- 30 58.3 12.8 0.77 16.8 14 14 46 (14.0) 44 (13.4) 25
30 --- 30 77.0 16.0 1.1 21.1 12 12 57 (17.4) 54 (16.5) 30
36 --- 31 70.0 15.6 1.1 20.6 12 12 60 (18.3) 57 (17.4) 35
42 --- 31 96.0 18.0 1.4 23.9 12 12 52 (15.8) 50 (15.2) 40
48 --- 31 99.0 21.8 1.4 28.7 10 10 69 (21.0) 66 (20.1) 45
60 --- 30 134.0 26.3 1.2 34.1 8 8 89 (27.1) 84 (25.6 50
30 --- 50
208/230/3 253 197
71.0 10.0 1.1 13.6 14 14 65 (19.8) 62 (18.9) 20
36 --- 50 73.0 10.4 1.1 14.1 14 14 61 (18.6) 58 (17.7) 20
42 --- 50 83.1 13.6 1.4 18.4 14 14 48 (14.6) 46 (14.0) 30
48 --- 50 83.1 13.8 1.4 18.7 14 14 48 (14.6) 46 (14.0) 30
60 --- 50 110.0 15.9 1.2 21.1 12 12 66 (20.1) 63 (19.2) 30
36 --- 60
460/3 253 197
38.0 5.8 0.6 7.9 14 14 227 (69.2) 216 (65.8) 10
48 --- 60 41.0 6.2 0.7 8.5 14 14 202 (61.6) 192 (58.5) 10
60 --- 60 52.0 7.8 0.6 10.4 14 14 165 (50.3) 157 (47.9) 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{If wire is applied at ambient greater than 30_C , c o n s u l t t a b l e 3 1 0 --- 1 6 o f t h e N E C ( N F PA 7 0 ) . T h e a m p a c i t y o f n o n --- m e t a l l i c --- s h e a t h e d c a b l e ( N M ) ,
trade name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
}Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
M C A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER
UNIT SIZE
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
18 --- 30 69 49.0 57.0 63.0 65.0 61.0 57.5 52.5
24 --- 30 73 51.0 59.5 66.0 68.5 63.5 59.0 53.0
30 --- 30, 50 74 52.5 64.0 68.0 69.0 67.0 64.5 58.5
36 --- 31 73 50.5 62.5 67.0 68.5 66.5 63.5 58.0
36 --- 50, 60 75 53.5 63.0 69.0 71.0 67.0 63.5 58.0
42 --- 31 77 55.0 65.0 71.0 72.0 70.0 67.0 59.5
42 --- 50 79 55.0 67.0 71.0 74.5 70.0 67.0 60.0
48 --- 31 80 59.0 67.0 72.5 75.0 73.5 69.5 61.5
48 --- 50, 60 80 59.5 69.5 74.0 76.0 72.5 69.5 64.5
60--- 30, 50, 60 77 55.0 63.0 67.5 71.5 68.0 64.0 60.5
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
A--WEIGHTED SOUND POWER WITH SOUND HOOD
UNIT SIZE
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
18 --- 30 69 50.0 57.0 63.0 64.5 61.0 57.0 51.0
24 --- 30 71 51.5 59.0 65.5 67.5 63.0 58.5 53.0
30 --- 30, 50 73 53.0 64.0 68.0 68.0 66.5 63.5 57.0
36 --- 31 73 52.0 63.0 66.5 68.0 65.5 62.5 56.5
36 --- 50, 60 74 54.0 63.5 68.5 70.0 66.0 63.0 57.0
42 --- 31 77 55.0 65.5 71.0 72.0 70.0 66.0 59.5
42 --- 50 78 56.0 67.0 71.0 73.5 69.5 66.5 60.0
48 --- 31 79 60.0 66.5 72.5 74.5 73.5 69.0 61.0
48 --- 50, 60 79 58.5 69.0 73.5 74.5 71.5 68.0 62.0
60--- 30, 50, 60 74 55.0 63.5 67.0 69.0 66.5 62.0 57.0
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- SERIES REQUIRED SUBCOOLING* ° F (° C)
18 --- 30 13 (7.2)
24 --- 30 13 (7.2)
30 --- 30, 50 9 (5.0)
36 --- 31 14 (7.8)
36 --- 50, 60 9 (5.0)
42 --- 31 15 (8.3)
42 --- 50 13 (7.2)
48 --- 31 17 (9.4)
48 --- 50, 60 13 (7.2)
60--- 30, 50, 60 15 (8.3)
NOTE: Subcooling is for field installed TXV (except for 060)
25HCD3
9
DIMENSIONS -- ENGLISH
25HCD3
10
DIMENSIONS -- SI
25HCD3
11
25HCD3 BALANCE POINT WORKSHEET
-23.3 -17.8 -12.2 -6.7 -1.1 4.4 10.0 15.6 21.1 26.7
0.0
2.9
5.9
8.8
11.7
14.7
17.6
20.5
23.4
0
10
20
30
40
50
60
70
80
-10.0 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0
kW
BUILDING HEAT LOSS, UNIT INTEGRATED HEATING CAPACIT Y, MBT UH
OUTDOOR TEMPERATURE
25HCD324
FB4CNF024
25HCD330
FB4CNF030
25HCD336
FB4CNF036
25HCD360
FY5BNB060
25HCD348
FB4CNF048
25HCD318
FB4CNF018
25HCD342
FB4CNF042
0F
0C
BASED ON INDOOR ENTERING
AIR AT 70◦F (21.1◦C) AND AT RATED
CFM
25HCD3
12
CLEARANCES
Clearances (various examples)
Wall
6”
(152.4)
24”
(609.6)
Service
Wall
Wall
Wall
12”
(304.8)
12”
(304.8)
18”
(457.2)
24”
(609.6)
Service
6”
(152.4)
12”
(304.8)
24”
(609.6)
Service
24”
(609.6)
Service
24”
(609.6)
Service
Note: Numbers in ( ) = mm
18”
(457.2)
18”
(457.2)
12”
(304.8)
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
25HCD3
13
TESTED AHRI* COMBINATION RATINGS
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at: www.MyCarrierRatings.com
For performance data at specific application &/or design conditions with various indoor unit combinations, the
equipment performance calculator can be accessed at : http://rpmob.wrightsoft.com/
Model Number Coil Model Number
Furnace
Model
Number
Cooling
Capacity EER SEER
High Temp
HSPF
Low Temp
Capacity
47˚F(8_C) COP Capacity
17˚F ( --- 8 _C) COP
25HCD318(A,W)**30 FB4CNF018 17,400 11.0 13.0 16,700 3.60 7.7 9,400 2.24
25HCD324(A,W)**30 FB4CNF024 23,400 11.0 13.0 22,000 3.48 7.7 13,000 2.28
25HCD330(A,W)**30 FB4CNF030 28,600 11.0 13.0 29,600 3.50 7.7 17,700 2.34
25HCD330(A,W)**50 FB4CNF030 28,600 11.0 13.0 29,600 3.50 7.7 17,700 2.34
25HCD336(A,W)**31 FB4CNF036 33,600 11.0 13.0 33,000 3.50 7.7 20,200 2.40
25HCD336(A,W)**50 FB4CNF036 33,600 11.0 13.0 33,000 3.54 7.7 20,200 2.40
25HCD336(A,W)**60 FB4CNF036 33,600 11.0 13.0 33,000 3.54 7.7 20,200 2.40
25HCD342(A,W)**31 FB4CNF042 42,000 11.0 13.0 39,500 3.60 8.0 24,400 2.40
25HCD342(A,W)**50 FB4CNF042 42,000 11.0 13.0 39,500 3.62 8.0 24,000 2.44
25HCD348(A,W)**31 FB4CNF048 47,000 11.0 13.0 45,000 3.48 8.0 28,600 2.44
25HCD348(A,W)**50 FB4CNF048 47,000 11.0 13.0 45,000 3.58 8.0 28,200 2.50
25HCD348(A,W)**60 FB4CNF048 47,000 11.0 13.0 45,000 3.58 8.0 28,200 2.50
25HCD360(A,W)**30 FY5BNB060 58,500 10.8 13.0 57,000 3.52 7.7 37,000 2.50
25HCD360(A,W)**50 FY5BNB060 58,500 10.8 13.0 57,000 3.52 7.7 37,000 2.50
25HCD360(A,W)**60 FY5BNB060 58,500 10.8 13.0 57,000 3.52 7.7 37,000 2.50
*AHRI = Air Conditioning, Heating & Refrigeration Institute
* Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on:
Cooling Standard: 80_F(27_C) db 67_F(19_C) wb indoor entering air temperature and 95_F(35_C) db air entering outdoor unit.
High---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 47_F(8_C) db 43° F (6_C) wb air entering outdoor unit.
Low---Temp Heating Standard: 70_F(21_C) db indoor entering air temperature and 17_F ( --- 8 _C ) d b 1 5 ° F ( --- 9 _C) wb air entering outdoor unit.
COP — Coefficient of Performance
EER — Energy Efficiency Ratio
HSPF — Heating Seasonal Performance Factor
SEER — Seasonal Energy Efficiency Ratio
25HCD3
14
DETAILED COOLING CAPACITIES#
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD318(A,W)**30 Outdoor Section With FB4CNF018 Indoor Section
525
57 (13.9) 16.65 16.65 1.22 15.93 15.93 1.37 14.83 14.83 1.52 13.70 13.70 1.70 12.53 12.53 1.90 11.26 11.26 2.13
62 (16.7) 17.30 15.33 1.22 16.38 14.89 1.37 15.05 14.24 1.52 13.73 13.73 1.70 12.55 12.55 1.90 11.28 11.28 2.13
63 (17.2)†† 17.67 12.51 1.22 16.71 12.09 1.38 15.42 11.53 1.53 13.80 10.84 1.70 12.20 10.17 1.89 10.50 9.46 2.11
67 (19.4) 19.21 13.04 1.23 18.18 12.64 1.39 17.04 12.18 1.56 15.53 11.58 1.73 13.75 10.89 1.92 11.97 10.20 2.14
72 (22.2) 21.16 10.63 1.25 20.17 10.28 1.41 19.02 9.88 1.59 17.68 9.38 1.79 16.09 8.82 1.99 14.07 8.12 2.19
600
57 (13.9) 17.43 17.43 1.24 16.66 16.66 1.39 15.79 15.79 1.56 14.44 14.44 1.72 13.17 13.17 1.92 11.83 11.83 2.15
62 (16.7) 17.78 16.48 1.24 16.83 15.99 1.39 15.81 15.81 1.56 14.46 14.46 1.72 13.20 13.20 1.92 11.85 11.85 2.15
63 (17.2)†† 18.10 13.33 1.24 17.09 12.90 1.39 15.97 12.42 1.56 14.16 11.66 1.71 12.51 10.97 1.91 10.78 10.19 2.13
67 (19.4) 19.65 13.89 1.25 18.59 13.51 1.41 17.40 13.04 1.58 16.09 12.53 1.77 14.10 11.76 1.94 12.26 11.03 2.16
72 (22.2) 21.57 11.12 1.26 20.56 10.79 1.43 19.41 10.41 1.61 18.06 9.95 1.80 16.50 9.40 2.02 14.39 8.68 2.21
675
57 (13.9) 18.11 18.11 1.25 17.28 17.28 1.41 16.38 16.38 1.58 15.09 15.09 1.75 13.73 13.73 1.94 12.32 12.32 2.17
62 (16.7) 18.22 17.49 1.25 17.31 17.31 1.41 16.41 16.41 1.58 15.12 15.12 1.75 13.75 13.75 1.95 12.34 12.34 2.17
63 (17.2)†† 18.46 14.11 1.25 17.39 13.67 1.41 16.24 13.18 1.58 14.48 12.44 1.73 12.78 11.70 1.93 11.09 11.09 2.15
67 (19.4) 19.98 14.69 1.26 18.91 14.33 1.42 17.69 13.87 1.60 16.35 13.35 1.79 14.38 12.58 1.96 12.51 11.79 2.18
72 (22.2) 21.88 11.57 1.28 20.86 11.27 1.44 19.69 10.90 1.62 18.34 10.46 1.82 16.73 9.90 2.04 14.63 9.20 2.23
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD324(A,W)**30 Outdoor Section With FB4CNF024 Indoor Section
700
57 (13.9) 22.27 22.27 1.62 21.36 21.36 1.82 20.01 20.01 2.01 18.55 18.55 2.25 17.03 17.03 2.51 15.40 15.40 2.81
62 (16.7) 23.17 20.79 1.63 22.02 20.23 1.83 20.58 19.52 2.03 18.58 18.58 2.25 17.06 17.06 2.51 15.42 15.42 2.81
63 (17.2)†† 23.65 16.96 1.63 22.45 16.42 1.83 21.09 15.82 2.05 18.86 14.86 2.25 16.76 13.96 2.50 14.55 13.00 2.79
67 (19.4) 25.62 17.65 1.66 24.33 17.13 1.86 22.96 16.57 2.09 21.15 15.84 2.32 18.89 14.94 2.55 16.55 14.01 2.83
72 (22.2) 28.04 14.27 1.70 26.88 13.86 1.91 25.54 13.37 2.14 23.99 12.83 2.40 22.07 12.12 2.68 19.47 11.20 2.92
800
57 (13.9) 23.24 23.24 1.65 22.28 22.28 1.86 21.18 21.18 2.08 19.52 19.52 2.29 17.86 17.86 2.55 16.14 16.14 2.85
62 (16.7) 23.74 22.26 1.66 22.55 21.65 1.86 21.23 21.23 2.08 19.55 19.55 2.29 17.89 17.89 2.55 16.17 16.17 2.85
63 (17.2)†† 24.17 18.01 1.67 22.92 17.47 1.87 21.53 16.86 2.08 19.35 15.93 2.29 17.13 14.97 2.54 14.90 13.98 2.82
67 (19.4) 26.14 18.72 1.69 24.87 18.26 1.90 23.40 17.68 2.13 21.78 17.03 2.37 19.36 16.08 2.59 16.93 15.10 2.87
72 (22.2) 28.50 14.87 1.73 27.33 14.48 1.94 25.98 14.01 2.17 24.43 13.49 2.43 22.48 12.81 2.71 19.90 11.92 2.97
900
57 (13.9) 24.05 24.05 1.69 23.03 23.03 1.89 21.91 21.91 2.12 20.37 20.37 2.34 18.61 18.61 2.60 16.76 16.76 2.89
62 (16.7) 24.25 23.56 1.69 23.07 23.07 1.89 21.94 21.94 2.12 20.40 20.40 2.34 18.64 18.64 2.60 16.81 16.81 2.89
63 (17.2)†† 24.60 19.04 1.69 23.29 18.48 1.90 21.88 17.87 2.12 19.70 16.93 2.32 17.49 15.95 2.57 15.23 14.83 2.85
67 (19.4) 26.54 19.73 1.72 25.26 19.31 1.93 23.76 18.77 2.16 22.10 18.10 2.41 19.74 17.16 2.63 17.27 16.11 2.90
72 (22.2) 28.85 15.42 1.76 27.68 15.06 1.97 26.31 14.61 2.20 24.75 14.11 2.46 22.87 13.52 2.74 20.25 12.62 3.01
See notes on page 17
25HCD3
15
DETAILED COOLING CAPACITIES#CONTINUED
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD330(A,W)**30 Outdoor Section With FB4CNF030 Indoor Section
875
57 (13.9) 27.18 27.18 2.02 26.03 26.03 2.24 24.78 24.78 2.50 23.39 23.39 2.79 21.45 21.45 3.07 19.49 19.49 3.42
62 (16.7) 28.44 24.01 2.03 26.96 23.33 2.25 25.36 22.59 2.51 23.65 21.76 2.79 21.48 21.48 3.07 19.54 19.54 3.42
63 (17.2)†† 29.05 19.61 2.04 27.50 18.95 2.26 25.87 18.25 2.52 24.07 17.50 2.80 21.55 16.47 3.07 18.91 15.40 3.40
67 (19.4) 31.49 20.43 2.07 29.83 19.77 2.30 28.06 19.07 2.55 26.17 18.34 2.85 24.14 17.56 3.17 21.41 16.53 3.49
72 (22.2) 34.60 16.62 2.11 33.02 16.06 2.34 31.22 15.43 2.60 29.22 14.74 2.91 26.97 13.94 3.25 24.63 13.15 3.63
1000
57 (13.9) 28.38 28.38 2.07 27.13 27.13 2.29 25.81 25.81 2.55 24.36 24.36 2.85 22.72 22.72 3.17 20.47 20.47 3.49
62 (16.7) 29.14 25.72 2.08 27.59 24.98 2.30 25.98 24.14 2.55 24.40 24.40 2.85 22.76 22.76 3.17 20.51 20.51 3.49
63 (17.2)†† 29.71 20.82 2.08 28.09 20.14 2.30 26.36 19.42 2.56 24.52 18.67 2.85 22.11 17.68 3.13 19.33 16.54 3.45
67 (19.4) 32.16 21.66 2.11 30.48 21.06 2.34 28.60 20.33 2.60 26.61 19.58 2.89 24.55 18.80 3.22 21.98 17.83 3.56
72 (22.2) 35.21 17.30 2.15 33.61 16.78 2.38 31.78 16.17 2.65 29.75 15.50 2.95 27.51 14.76 3.29 25.00 13.90 3.68
1125
57 (13.9) 29.38 29.38 2.12 28.07 28.07 2.34 26.66 26.66 2.60 25.15 25.15 2.90 23.48 23.48 3.23 21.30 21.30 3.56
62 (16.7) 29.75 27.27 2.12 28.15 28.15 2.34 26.70 26.70 2.60 25.18 25.18 2.90 23.51 23.51 3.23 21.34 21.34 3.56
63 (17.2)†† 30.21 21.97 2.12 28.53 21.28 2.35 26.75 20.55 2.60 24.84 19.77 2.89 22.76 18.90 3.20 19.71 17.60 3.50
67 (19.4) 32.67 22.83 2.15 30.96 22.26 2.38 29.01 21.55 2.64 26.97 20.78 2.94 24.86 19.98 3.27 22.48 19.05 3.63
72 (22.2) 35.66 17.95 2.19 34.05 17.45 2.42 32.19 16.87 2.69 30.14 16.21 2.99 27.89 15.49 3.33 25.30 14.64 3.72
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD336(A,W)**31 Outdoor Section With FB4CNF036 Indoor Section
1050
57 (13.9) 31.95 31.95 2.39 30.67 30.67 2.65 29.29 29.29 2.94 27.80 27.80 3.26 25.76 25.76 3.59 23.48 23.48 3.99
62 (16.7) 33.18 28.52 2.41 31.56 27.77 2.66 29.84 26.94 2.95 28.01 26.01 3.27 25.81 25.81 3.60 23.53 23.53 3.99
63 (17.2)†† 33.87 23.22 2.42 32.19 22.50 2.67 30.39 21.74 2.95 28.45 20.94 3.28 25.81 19.85 3.59 22.68 18.58 3.97
67 (19.4) 36.68 24.14 2.44 34.92 23.49 2.71 32.98 22.73 3.00 30.94 21.95 3.32 28.72 21.10 3.70 25.84 20.01 4.06
72 (22.2) 40.08 19.42 2.48 38.56 18.94 2.75 36.71 18.31 3.04 34.58 17.59 3.38 32.09 16.72 3.77 29.53 15.84 4.21
1200
57 (13.9) 33.27 33.27 2.45 31.91 31.91 2.71 30.46 30.46 3.00 28.89 28.89 3.33 27.12 27.12 3.70 24.64 24.64 4.06
62 (16.7) 33.98 30.51 2.46 32.31 29.67 2.72 30.54 30.54 3.00 28.93 28.93 3.33 27.16 27.16 3.70 24.68 24.68 4.07
63 (17.2)†† 34.60 24.67 2.47 32.85 23.94 2.72 30.97 23.16 3.01 28.97 22.34 3.33 26.70 21.41 3.69 23.25 19.97 4.02
67 (19.4) 37.41 25.60 2.49 35.66 25.04 2.76 33.60 24.27 3.05 31.47 23.46 3.38 29.19 22.59 3.75 26.62 21.61 4.16
72 (22.2) 40.70 20.22 2.53 39.19 19.78 2.79 37.34 19.19 3.09 35.20 18.50 3.43 32.76 17.71 3.82 29.95 16.76 4.27
1350
57 (13.9) 34.39 34.39 2.51 32.97 32.97 2.77 31.42 31.42 3.06 29.79 29.79 3.39 27.97 27.97 3.77 25.68 25.68 4.15
62 (16.7) 34.71 32.24 2.51 33.03 33.03 2.77 31.46 31.46 3.06 29.82 29.82 3.39 28.01 28.01 3.77 25.72 25.72 4.16
63 (17.2)†† 35.21 26.05 2.52 33.35 25.30 2.77 31.40 24.50 3.06 29.36 23.65 3.38 27.07 22.70 3.74 23.69 21.22 4.08
67 (19.4) 37.95 26.97 2.54 36.17 26.43 2.81 34.08 25.72 3.10 31.88 24.88 3.43 29.55 23.99 3.81 26.96 22.97 4.22
72 (22.2) 41.12 20.88 2.57 39.64 20.53 2.84 37.79 20.00 3.14 35.64 19.34 3.48 33.18 18.58 3.87 30.35 17.66 4.31
See notes on page 17
25HCD3
16
DETAILED COOLING CAPACITIES#CONTINUED
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD342(A,W)**31 Outdoor Section With FB4CNF042 Indoor Section
1225
57 (13.9) 39.37 39.37 3.01 37.75 37.75 3.34 36.03 36.03 3.69 34.20 34.20 4.07 31.58 31.58 4.44 28.93 28.93 4.89
62 (16.7) 41.08 37.19 3.01 38.99 36.16 3.34 36.82 35.06 3.70 34.58 33.87 4.08 31.64 31.64 4.44 28.98 28.98 4.89
63 (17.2)†† 41.94 30.35 3.01 39.77 29.36 3.34 37.53 28.35 3.70 35.15 27.30 4.09 31.79 25.83 4.45 28.16 24.25 4.86
67 (19.4) 45.43 31.55 2.98 43.16 30.64 3.34 40.70 29.62 3.72 38.18 28.58 4.12 35.48 27.48 4.56 31.93 26.05 4.98
72 (22.2) 49.74 25.53 2.94 47.65 24.77 3.32 45.25 23.90 3.72 42.59 22.96 4.15 39.57 21.82 4.63 36.47 20.70 5.14
1400
57 (13.9) 41.05 41.05 3.05 39.30 39.30 3.39 37.49 37.49 3.75 35.56 35.56 4.14 33.40 33.40 4.57 30.34 30.34 4.98
62 (16.7) 42.10 39.81 3.05 39.92 38.67 3.39 37.73 37.39 3.75 35.61 35.61 4.14 33.44 33.44 4.57 30.39 30.39 4.98
63 (17.2)†† 42.91 32.24 3.04 40.63 31.23 3.39 38.26 30.19 3.75 35.81 29.11 4.14 32.72 27.77 4.53 28.86 26.06 4.93
67 (19.4) 46.38 33.45 3.02 44.09 32.65 3.38 41.50 31.60 3.77 38.83 30.53 4.18 36.08 29.42 4.62 32.97 28.16 5.09
72 (22.2) 50.61 26.60 2.98 48.50 25.87 3.36 46.07 25.05 3.76 43.36 24.14 4.20 40.38 23.11 4.68 37.02 21.88 5.20
1575
57 (13.9) 42.49 42.49 3.09 40.64 40.64 3.44 38.70 38.70 3.80 36.67 36.67 4.20 34.47 34.47 4.64 31.57 31.57 5.07
62 (16.7) 43.00 42.10 3.09 40.76 40.76 3.44 38.75 38.75 3.80 36.71 36.71 4.20 34.51 34.51 4.64 31.63 31.63 5.07
63 (17.2)†† 43.68 34.03 3.08 41.28 33.00 3.44 38.83 31.93 3.80 36.30 30.82 4.20 33.52 29.59 4.62 29.39 27.70 5.00
67 (19.4) 47.08 35.20 3.05 44.76 34.43 3.42 42.12 33.50 3.82 39.37 32.39 4.23 36.51 31.23 4.68 33.42 29.94 5.16
72 (22.2) 51.25 27.56 3.02 49.14 26.89 3.39 46.67 26.10 3.81 43.93 25.24 4.25 40.90 24.23 4.73 37.53 23.06 5.25
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD348(A,W)**31 Outdoor Section With FB4CNF048 Indoor Section
1400
57 (13.9) 44.84 44.84 3.32 42.92 42.92 3.70 40.93 40.93 4.11 38.86 38.86 4.55 36.60 36.60 5.05 33.56 33.56 5.57
62 (16.7) 46.76 41.67 3.34 44.30 40.49 3.72 41.77 39.25 4.12 39.24 37.92 4.56 36.66 36.66 5.06 33.63 33.63 5.57
63 (17.2)†† 47.74 33.97 3.34 45.20 32.83 3.73 42.56 31.66 4.13 39.87 30.49 4.57 36.99 29.25 5.06 32.84 27.47 5.54
67 (19.4) 51.68 35.32 3.36 48.96 34.23 3.77 46.17 33.09 4.19 43.26 31.91 4.64 40.24 30.71 5.14 37.01 29.42 5.71
72 (22.2) 56.56 28.54 3.38 54.12 27.70 3.82 51.31 26.67 4.26 48.25 25.56 4.72 45.02 24.40 5.24 41.51 23.12 5.82
1600
57 (13.9) 46.75 46.75 3.40 44.70 44.70 3.78 42.55 42.55 4.20 40.36 40.36 4.65 38.00 38.00 5.16 35.38 35.38 5.73
62 (16.7) 47.86 44.58 3.40 45.34 43.30 3.79 42.77 42.42 4.20 40.41 40.41 4.65 38.05 38.05 5.16 35.43 35.43 5.73
63 (17.2)†† 48.79 36.07 3.41 46.10 34.88 3.80 43.34 33.68 4.21 40.55 32.48 4.65 37.59 31.21 5.14 33.69 29.53 5.64
67 (19.4) 52.69 37.40 3.43 50.00 36.46 3.84 47.00 35.27 4.27 43.99 34.06 4.73 40.86 32.83 5.22 37.56 31.51 5.79
72 (22.2) 57.44 29.66 3.45 55.02 28.92 3.89 52.17 27.93 4.33 49.07 26.85 4.80 45.76 25.71 5.31 42.25 24.50 5.89
1800
57 (13.9) 48.37 48.37 3.47 46.18 46.18 3.87 43.93 43.93 4.29 41.59 41.59 4.74 39.13 39.13 5.25 36.47 36.47 5.83
62 (16.7) 48.85 47.20 3.47 46.29 46.29 3.87 43.99 43.99 4.29 41.64 41.64 4.74 39.18 39.18 5.25 36.52 36.52 5.83
63 (17.2)†† 49.60 38.01 3.47 46.81 36.86 3.87 43.97 35.64 4.28 41.05 34.39 4.73 38.05 33.09 5.22 34.69 31.59 5.77
67 (19.4) 53.47 39.41 3.49 50.73 38.51 3.91 47.66 37.39 4.34 44.54 36.15 4.80 41.34 34.87 5.30 37.99 33.50 5.87
72 (22.2) 58.09 30.71 3.52 55.69 30.04 3.95 52.82 29.12 4.40 49.68 28.08 4.87 46.32 26.95 5.38 42.74 25.74 5.96
See notes on page 17
25HCD3
17
DETAILED COOLING CAPACITIES#CONTINUED
EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM EWB
°F(°C)
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot al
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Capacity MBtuh Tot a l
System
KW**
Tot a l Sens‡ Tot a l Sens‡ Tot a l Sens‡ Tot al Sens‡ Tot a l Sens‡ Tot al Sens‡
25HCD360(A,W)**30 Outdoor Section With FY5BNB060 Indoor Section
1750
57 (13.9) 57.16 57.16 4.38 54.99 54.99 4.83 52.69 52.69 5.33 50.18 50.18 5.91 47.44 47.44 6.57 44.45 44.45 7.32
62 (16.7) 59.15 52.45 4.41 56.47 51.18 4.85 53.63 49.82 5.35 50.65 48.37 5.92 47.54 47.30 6.57 44.51 44.51 7.32
63 (17.2)†† 60.11 42.61 4.42 57.31 41.34 4.86 54.35 40.02 5.36 51.18 38.61 5.92 47.79 37.14 6.57 44.16 35.59 7.32
67 (19.4) 64.72 44.22 4.47 61.70 42.95 4.92 58.50 41.62 5.42 55.07 40.20 5.98 51.41 38.74 6.63 47.49 37.18 7.36
72 (22.2) 71.01 35.89 4.55 67.67 34.62 5.00 64.16 33.30 5.50 60.39 31.90 6.07 56.34 30.42 6.71 52.00 28.86 7.44
2000
57 (13.9) 59.49 59.49 4.50 57.16 57.16 4.95 54.68 54.68 5.45 52.00 52.00 6.03 49.06 49.06 6.69 45.86 45.86 7.43
62 (16.7) 60.51 56.18 4.51 57.75 54.84 4.96 54.89 53.32 5.46 52.07 52.07 6.03 49.12 49.12 6.69 45.91 45.91 7.43
63 (17.2)†† 61.25 45.11 4.52 58.34 43.82 4.96 55.23 42.47 5.46 51.97 41.05 6.02 48.46 39.57 6.68 44.70 37.96 7.41
67 (19.4) 65.90 46.91 4.58 62.75 45.62 5.02 59.40 44.26 5.52 55.83 42.82 6.08 52.07 41.35 6.73 48.02 39.75 7.46
72 (22.2) 72.25 37.51 4.66 68.77 36.22 5.11 65.08 34.87 5.61 61.18 33.45 6.17 56.96 31.94 6.81 52.49 30.36 7.54
2250
57 (13.9) 61.41 61.41 4.61 58.94 58.94 5.06 56.30 56.30 5.57 53.46 53.46 6.14 50.35 50.35 6.80 46.98 46.98 7.54
62 (16.7) 61.74 59.59 4.62 58.94 58.94 5.06 56.37 56.37 5.57 53.52 53.52 6.14 50.39 50.39 6.80 47.03 47.03 7.54
63 (17.2)†† 62.12 47.48 4.62 59.10 46.18 5.06 55.93 44.82 5.56 52.55 43.38 6.12 48.95 41.84 6.77 45.12 40.18 7.51
67 (19.4) 66.78 49.46 4.68 63.51 48.15 5.12 60.08 46.79 5.62 56.44 45.35 6.19 52.54 43.80 6.83 48.41 42.16 7.56
72 (22.2) 73.16 39.03 4.76 69.54 37.71 5.21 65.76 36.35 5.71 61.72 34.91 6.27 57.39 33.38 6.91 52.81 31.78 7.63
* Tested combination.
{Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
}Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240---2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of indoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB — Entering Wet Bulb
25HCD3
18
HEAT PUMP HEATING PERFORMANCE
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 ( --- 1 9 . 4 ) 7 ( ---13.9) 17 (---8.3) 27 (---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C) CFM
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh To t al
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Tota l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg*
25HCD318(A,W)**30 Outdoor Section With FB4CNF018 Indoor Section
65
(18.3)
525 5.18 4.76 1.09 7.28 6.69 1.13 9.55 8.71 1.18 12.03 10.68 1.23 14.44 13.14 1.28 16.94 16.94 1.33 19.01 19.01 1.38 20.73 20.73 1.42
600 5.26 4.84 1.09 7.38 6.78 1.13 9.73 8.87 1.17 12.17 10.81 1.21 14.62 13.31 1.26 16.98 16.98 1.30 18.87 18.87 1.34 20.34 20.34 1.36
675 5.33 4.91 1.10 7.47 6.87 1.13 10.00 9.11 1.17 12.28 10.91 1.20 14.77 13.44 1.25 16.95 16.95 1.27 18.64 18.64 1.30 19.82 19.82 1.32
70
(21.1)
525 4.93 4.53 1.14 7.02 6.45 1.19 9.26 8.44 1.24 11.80 10.48 1.29 14.18 12.91 1.35 16.72 16.72 1.40 18.81 18.81 1.45 20.55 20.55 1.50
600 5.01 4.61 1.14 7.13 6.55 1.19 9.40 8.57 1.23 11.95 10.61 1.28 14.36 13.07 1.32 16.80 16.80 1.37 18.74 18.74 1.41 20.27 20.27 1.44
675 5.08 4.67 1.15 7.22 6.63 1.19 9.52 8.68 1.23 12.06 10.71 1.27 14.51 13.21 1.31 16.81 16.81 1.34 18.58 18.58 1.37 19.88 19.88 1.40
75
(23.9)
525 4.64 4.27 1.19 6.74 6.20 1.24 8.97 8.18 1.29 11.57 10.27 1.36 13.92 12.67 1.41 16.49 16.49 1.48 18.58 18.58 1.53 20.34 20.34 1.57
600 4.73 4.35 1.19 6.85 6.30 1.24 9.11 8.30 1.29 11.72 10.40 1.34 14.10 12.83 1.39 16.59 16.59 1.44 18.57 18.57 1.48 20.12 20.12 1.51
675 4.80 4.42 1.20 6.94 6.38 1.24 9.22 8.41 1.28 11.83 10.51 1.33 14.25 12.96 1.37 16.64 16.64 1.41 18.48 18.48 1.45 19.85 19.85 1.47
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
---3 (19.4) 7 ( ---13.9) 17 (---8.3) 27 (---2.i8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C) CFM
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh To t al
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Capacity MBtuh Tota l
Sys-
tem
KW
Tota l Integ Tota l Integ To t al Integ To t a l Integ Tota l Integ Tota l Integ To t al Integ To t a l Integ
25HCD324(A,W)**30 Outdoor Section With FB4CNF024 Indoor Section
65
(18.3)
700 7.98 7.35 1.45 10.55 9.70 1.54 13.20 12.03 1.60 16.25 14.43 1.67 19.15 17.43 1.73 22.05 22.05 1.80 25.36 25.36 1.89 28.21 28.21 1.97
800 8.15 7.50 1.46 10.74 9.87 1.54 13.42 12.23 1.60 16.65 14.78 1.65 19.39 17.64 1.70 22.34 22.34 1.76 25.60 25.60 1.83 28.25 28.25 1.91
900 8.29 7.63 1.47 10.91 10.02 1.55 13.60 12.40 1.60 16.82 14.94 1.65 19.58 17.82 1.69 22.59 22.59 1.74 25.74 25.74 1.80 28.20 28.20 1.86
70
(21.1)
700 7.54 6.94 1.51 10.14 9.31 1.61 12.78 11.66 1.67 15.64 13.89 1.74 18.85 17.15 1.82 21.72 21.72 1.89 24.99 24.99 1.98 27.87 27.87 2.07
800 7.71 7.09 1.52 10.32 9.49 1.61 13.00 11.85 1.67 15.96 14.18 1.73 19.08 17.36 1.79 22.00 22.00 1.85 25.27 25.27 1.93 27.95 27.95 2.00
900 7.85 7.22 1.53 10.49 9.64 1.62 13.19 12.03 1.67 16.26 14.44 1.72 19.29 17.55 1.78 22.24 22.24 1.83 25.44 25.44 1.89 27.94 27.94 1.96
75
(23.9)
700 7.08 6.51 1.58 9.68 8.89 1.68 12.36 11.27 1.75 15.19 13.49 1.82 18.59 16.91 1.91 21.39 21.39 1.98 24.61 24.61 2.08 27.51 27.51 2.17
800 7.24 6.66 1.59 9.86 9.06 1.68 12.57 11.46 1.75 15.45 13.73 1.81 18.81 17.11 1.88 21.66 21.66 1.95 24.91 24.91 2.02 27.62 27.62 2.10
900 7.38 6.79 1.60 10.03 9.22 1.69 12.76 11.63 1.75 15.68 13.92 1.80 18.99 17.28 1.87 21.90 21.90 1.92 25.11 25.11 1.99 27.65 27.65 2.06
See notes on page 21
25HCD3
19
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 ( --- 1 9 . 4 ) 7 (---13.9) 17 (---8.3) 27 (---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C) CFM Capacity MBtuh To t a l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Tota l Integ* Tota l Integ* To t a l Integ* To t a l Integ* Tota l Integ* To ta l Integ* To t a l Integ* Tota l Integ*
25HCD330(A,W)**30 Outdoor Section With FB4CNF030 Indoor Section
65
(18.3)
875 11.54 10.62 2.01 14.61 13.43 2.07 17.89 16.31 2.13 21.51 19.10 2.20 24.95 22.71 2.26 28.66 28.66 2.33 32.91 32.91 2.40 36.28 36.28 2.45
1000 11.73 10.79 2.02 14.83 13.63 2.07 18.18 16.58 2.12 21.76 19.32 2.18 25.26 22.99 2.23 29.04 29.04 2.29 33.14 33.14 2.34 36.10 36.10 2.37
1125 11.90 10.95 2.04 15.02 13.81 2.08 18.71 17.06 2.13 21.96 19.50 2.17 25.52 23.22 2.21 29.36 29.36 2.27 33.18 33.18 2.30 35.81 35.81 2.32
70
(21.1)
875 11.08 10.20 2.10 14.17 13.02 2.16 17.44 15.90 2.22 21.21 18.84 2.30 24.58 22.37 2.36 28.23 28.23 2.44 32.45 32.45 2.51 35.92 35.92 2.57
1000 11.30 10.40 2.11 14.41 13.24 2.17 17.70 16.14 2.22 21.45 19.05 2.28 24.88 22.64 2.33 28.60 28.60 2.39 32.74 32.74 2.45 35.79 35.79 2.49
1125 11.48 10.56 2.13 14.61 13.42 2.18 17.93 16.35 2.22 21.65 19.23 2.27 25.13 22.87 2.32 28.91 28.91 2.37 32.84 32.84 2.41 35.55 35.55 2.43
75
(23.9)
875 10.66 9.81 2.20 13.74 12.63 2.26 16.99 15.49 2.32 20.87 18.54 2.41 24.20 22.03 2.48 27.80 27.80 2.55 31.99 31.99 2.63 35.52 35.52 2.69
1000 10.85 9.98 2.21 13.97 12.83 2.26 17.25 15.73 2.32 21.12 18.76 2.39 24.49 22.29 2.44 28.16 28.16 2.50 32.32 32.32 2.56 35.45 35.45 2.60
1125 11.02 10.14 2.22 14.16 13.01 2.27 17.47 15.93 2.32 21.33 18.95 2.38 24.75 22.52 2.43 28.47 28.47 2.48 32.48 32.48 2.52 35.27 35.27 2.55
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 (19.4) 7 (--- 13.9) 17 (--- 8.3) 27 (--- 2.i8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F(°C) CFM
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Tot a l Integ Tot al Integ Tot al Integ Tot a l Integ Tot a l Integ To t a l Integ Tota l Integ To t a l Integ
25HCD336(A,W)**31 Outdoor Section With FB4CNF036 Indoor Section
65
(18.3)
1050 12.79 11.77 2.17 16.58 15.24 2.26 20.53 18.72 2.35 24.72 21.96 2.46 29.59 26.93 2.60 33.44 33.44 2.71 37.48 37.48 2.84 41.96 41.96 3.04
1200 13.08 12.04 2.19 16.92 15.55 2.28 20.91 19.07 2.36 25.18 22.36 2.46 29.99 27.29 2.58 33.84 33.84 2.68 38.05 38.05 2.80 42.68 42.68 2.97
1350 13.35 12.28 2.22 17.22 15.83 2.30 21.25 19.37 2.37 25.56 22.70 2.46 30.31 27.58 2.58 34.23 34.23 2.66 38.53 38.53 2.77 43.26 43.26 2.93
70
(21.1)
1050 11.97 11.01 2.27 15.80 14.52 2.36 19.79 18.04 2.46 24.01 21.32 2.57 29.06 26.45 2.72 32.95 32.95 2.83 36.89 36.89 2.97 41.27 41.27 3.17
1200 12.30 11.31 2.29 16.16 14.85 2.38 20.20 18.42 2.47 24.46 21.72 2.56 29.49 26.84 2.70 33.40 33.40 2.80 37.45 37.45 2.92 41.97 41.97 3.10
1350 12.56 11.55 2.32 16.46 15.13 2.40 20.53 18.72 2.48 24.83 22.06 2.57 29.84 27.16 2.69 33.76 33.76 2.78 37.92 37.92 2.89 42.56 42.56 3.06
75
(23.9)
1050 11.18 10.29 2.37 15.04 13.83 2.47 19.07 17.39 2.57 23.26 20.66 2.68 27.74 25.24 2.81 32.46 32.46 2.96 36.32 36.32 3.10 40.58 40.58 3.31
1200 11.45 10.53 2.40 15.37 14.13 2.48 19.45 17.73 2.57 23.71 21.06 2.67 28.43 25.87 2.79 32.89 32.89 2.92 36.86 36.86 3.05 41.27 41.27 3.24
1350 11.71 10.78 2.43 15.67 14.40 2.51 19.78 18.04 2.59 24.08 21.39 2.68 29.29 26.66 2.81 33.26 33.26 2.90 37.31 37.31 3.02 41.84 41.84 3.19
See notes on page 21
25HCD3
20
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 ( --- 1 9 . 4 ) 7 ( ---13.9) 17 (---8.3) 27 (---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C) CFM
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh To t al
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Capacity MBtuh Tota l
Syst.
KW†
Tota l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg* To t a l In-
teg*
25HCD342(A,W)**31 Outdoor Section With FB4CNF042 Indoor Section
65
(18.3)
1225 15.60 14.35 2.64 20.17 18.54 2.75 24.73 22.55 2.85 29.47 26.17 2.95 34.77 31.64 3.05 39.07 39.07 3.08 43.89 43.89 3.10 49.14 49.14 3.09
1400 15.96 14.69 2.66 20.52 18.86 2.76 25.15 22.93 2.85 29.96 26.61 2.94 35.16 32.00 3.03 39.57 39.57 3.05 44.52 44.52 3.05 49.61 49.61 3.01
1525 16.17 14.87 2.68 20.75 19.07 2.77 25.41 23.17 2.86 30.27 26.89 2.94 35.42 32.23 3.02 39.87 39.87 3.04 44.90 44.90 3.03 49.76 49.76 2.97
70
(21.1)
1225 14.87 13.68 2.80 19.40 17.83 2.88 23.98 21.87 2.97 28.70 25.49 3.06 34.24 31.16 3.17 38.52 38.52 3.21 43.24 43.24 3.23 48.43 48.43 3.23
1400 15.18 13.97 2.82 19.76 18.16 2.90 24.40 22.25 2.98 29.18 25.91 3.06 34.67 31.55 3.15 39.00 39.00 3.17 43.85 43.85 3.18 48.95 48.95 3.15
1525 15.33 14.10 2.84 20.00 18.37 2.91 24.66 22.49 2.99 29.49 26.19 3.06 34.94 31.79 3.14 39.30 39.30 3.16 44.23 44.23 3.16 49.17 49.17 3.11
75
(23.9)
1225 14.04 12.91 2.96 18.60 17.10 3.03 23.21 21.16 3.11 27.91 24.79 3.19 32.98 30.01 3.28 38.00 38.00 3.34 42.60 42.60 3.37 47.73 47.73 3.38
1400 14.34 13.20 2.99 18.96 17.42 3.04 23.61 21.53 3.11 28.39 25.21 3.18 34.12 31.05 3.28 38.46 38.46 3.30 43.19 43.19 3.31 48.30 48.30 3.29
1525 14.55 13.38 3.01 19.19 17.63 3.05 23.88 21.77 3.12 28.69 25.48 3.18 34.39 31.29 3.27 38.75 38.75 3.29 43.56 43.56 3.29 48.57 48.57 3.25
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 (19.4) 7 (--- 13.9) 17 (--- 8.3) 27 (---2.i8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F(°C) CFM
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Capacity MB-
tuh
Tot a l
Sys-
tem
KW
Tot a l Integ Tot al Integ Tot al Integ Tot a l Integ Tot a l Integ To t a l Integ Tota l Integ To t a l Integ
25HCD348(A,W)**31 Outdoor Section With FB4CNF048 Indoor Section
65
(18.3)
1400 18.42 16.95 3.14 23.65 21.74 3.21 28.90 26.35 3.28 35.25 31.31 3.40 40.02 36.42 3.48 45.07 45.07 3.56 50.81 50.81 3.66 57.16 57.16 3.81
1600 18.80 17.30 3.19 24.10 22.15 3.24 29.38 26.79 3.30 35.74 31.74 3.40 40.52 36.87 3.46 45.69 45.69 3.53 51.59 51.59 3.61 58.17 58.17 3.72
1800 19.15 17.61 3.24 24.47 22.49 3.28 29.81 27.18 3.33 36.14 32.10 3.41 40.97 37.28 3.46 46.22 46.22 3.52 52.24 52.24 3.59 58.97 58.97 3.66
70
(21.1)
1400 17.61 16.20 3.27 22.86 21.00 3.34 28.11 25.63 3.42 33.56 29.80 3.50 39.44 35.89 3.63 44.40 44.40 3.71 50.01 50.01 3.82 56.20 56.20 3.97
1600 17.99 16.55 3.31 23.30 21.41 3.37 28.60 26.08 3.43 34.24 30.41 3.51 39.94 36.35 3.61 45.00 45.00 3.68 50.76 50.76 3.77 57.15 57.15 3.90
1800 18.34 16.87 3.36 23.68 21.76 3.41 29.03 26.47 3.46 35.39 31.43 3.55 40.40 36.76 3.61 45.52 45.52 3.67 51.40 51.40 3.74 58.01 58.01 3.83
75
(23.9)
1400 16.74 15.40 3.41 22.00 20.22 3.48 27.27 24.87 3.56 32.66 29.01 3.65 38.91 35.41 3.79 43.75 43.75 3.87 49.22 49.22 3.98 55.27 55.27 4.15
1600 17.12 15.75 3.45 22.44 20.62 3.51 27.77 25.32 3.57 33.25 29.53 3.65 39.42 35.87 3.77 44.33 44.33 3.84 49.95 49.95 3.93 56.19 56.19 4.07
1800 17.47 16.07 3.50 22.83 20.98 3.55 28.20 25.71 3.60 33.75 29.98 3.66 39.83 36.24 3.77 44.84 44.84 3.83 50.57 50.57 3.90 57.03 57.03 4.01
See notes on page 21
25HCD3
21
HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F (° C)
--- 3 ( --- 1 9 . 4 ) 7 (---13.9) 17 (---8.3) 27 (---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C) CFM Capacity MBtuh To t a l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Capacity MBtuh To ta l
Syst.
KW†
Tota l Integ* Tota l Integ* To t a l Integ* To t a l Integ* Tota l Integ* To ta l Integ* To t a l Integ* Tota l Integ*
25HCD360(A,W)**30 Outdoor Section With FY5BNB060 Indoor Section
65
(18.3)
1750 24.86 22.87 3.95 31.48 28.93 4.06 38.08 34.72 4.17 45.28 40.21 4.30 52.48 47.76 4.47 58.88 58.88 4.62 66.42 66.42 4.80 73.43 73.43 4.96
2000 25.43 23.40 4.01 32.04 29.45 4.10 38.76 35.34 4.19 46.95 41.70 4.35 53.15 48.37 4.46 59.73 59.73 4.59 67.34 67.34 4.73 73.99 73.99 4.87
2250 25.95 23.87 4.08 32.60 29.95 4.16 39.33 35.86 4.23 47.49 42.18 4.37 53.73 48.90 4.46 60.46 60.46 4.59 67.94 67.94 4.70 74.27 74.27 4.82
70
(21.1)
1750 23.67 21.78 4.10 30.33 27.87 4.22 37.00 33.74 4.34 44.01 39.08 4.48 51.73 47.07 4.67 58.00 58.00 4.83 65.43 65.43 5.01 72.49 72.49 5.17
2000 24.22 22.28 4.16 30.94 28.43 4.27 37.68 34.36 4.36 44.80 39.79 4.49 52.40 47.68 4.65 58.81 58.81 4.79 66.40 66.40 4.93 73.04 73.04 5.08
2250 24.72 22.74 4.23 31.51 28.95 4.32 38.28 34.90 4.41 45.52 40.43 4.51 52.96 48.19 4.66 59.54 59.54 4.78 67.06 67.06 4.91 73.39 73.39 5.03
75
(23.9)
1750 22.37 20.58 4.27 29.13 26.77 4.39 35.90 32.74 4.52 42.85 38.05 4.66 51.00 46.41 4.89 57.17 57.17 5.05 64.41 64.41 5.23 71.54 71.54 5.39
2000 22.91 21.08 4.33 29.73 27.32 4.44 36.57 33.34 4.55 43.63 38.75 4.67 51.62 46.97 4.86 57.93 57.93 5.00 65.46 65.46 5.15 72.12 72.12 5.29
2250 23.41 21.54 4.40 30.29 27.84 4.50 37.15 33.87 4.59 44.29 39.34 4.70 52.19 47.49 4.86 58.63 58.63 4.99 66.17 66.17 5.11 72.48 72.48 5.24
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity.
{The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.
EDB —EnteringDryBulb
25HCD3
22
GUIDE SPECIFICATIONS
GENERAL
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
25HCD3
1--1/2 TO 5 NOMINAL TONS
System Description
Outdoor--mounted, air--cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition of
AHRI Standard 240.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have C--UL approval.
— Unit cabinet will be capable of withstanding Federal Test
Method Standard No. 141 (Method 6061) 500--hr salt
spray test.
— Air--cooled condenser coils are pressure tested and the
outdoor unit is leak tested.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is stored
and handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
— Factory assembled, single piece, air--cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puronr(R--410A), and special features required prior to
field start--up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
— Available with dense grille only.
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings.
— Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with steel wire
safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include liquid--line
shutoff valve with sweat connections, vapor--line shutoff
valve with sweat connections, system charge of Puronr
(R--410A) refrigerant, POE compressor oil, accumulator,
and reversing valve.
Operating Characteristics
— The capacity of the unit will meet or exceed _____ Btuh
at a suction temperature of _____ _F/_C. The power
consumption at full load will not exceed _____ kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____ Btuh
or greater at conditions of _____ CFM entering air
temperature at the evaporator at _____ _F wet bulb and
_____ _F/_C dry bulb, and air entering the unit at _____
_F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Nominal unit electrical characteristics will be _____ v,
three phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v to
_____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
25HCD3
23
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature for cooling mode is 125_F (51.7_C).
4. Minimum outdoor operating air temperature for heating mode is –30_F (–34.4_C).
5. Maximum outdoor operating air temperature for heating mode is 66_F (18.9_C).
6. For reliable operation, unit should be level in all horizontal planes.
7. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or elevation differences between indoor and outdoor units
greater than 20 ft (6.1 m), consult Residential Piping and Longline Guideline and Service Manual available from equipment distribut-
or.
8. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
10. Do not apply capillary tube indoor coils to these units.
11. Factory--supplied filter drier must be installed.
25HCD3
24
Copyright 2013 Carrier Corp. S7310 W. Morris St. SIndianapolis, IN 46231 Edition Date: 03/13
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 25HCD3---1PD
Replaces: New
25HCD3