40RU
Packaged Air---Handling Units
60 Hz
With PuronR (R---410A) Refrigerant
Sizes 25, 28, 30

Installation, Start---Up and
Service Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
PRE-- INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 2
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . 2–22

Chilled Water Coil Freeze Protection . . . . . . . . . . . 26
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . 26
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
START-- UP CHECKLIST . . . . . . . . . . . . . . . . . . 39-- 40

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

SAFETY CONSIDERATIONS

Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service agency, or your distributor or branch for
information or assistance. The qualified installer or
agency must use factory-- authorized kits or accessories
when modifying this product. Refer to the individual
instructions package

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant and Chilled Water Piping Access . . . . . 13
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . 17
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . 18
Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . 19
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . 21
Return-- Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 21
START-- UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23–36
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fan Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Position Adjustment . . . . . . . . . . . . . . . . 24
Individual Fan Wheel Adjustment . . . . . . . . . . . . . . 25
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . . . . 25
Pulley and Drive Adjustment . . . . . . . . . . . . . . . . . . 25
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Return-- Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and appropriate
national electrical codes (in USA, ANSI/NFPA70,
National Electrical Code (NEC); in Canada, CSA C22.1)
for special requirements.
It is important to recognize safety information. This is the
. When you see this symbol on the
safety-- alert symbol
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-- alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.

!

PRE--INSTALLATION

WARNING

1. The power supply (v, ph, and Hz) must correspond to
that specified on unit rating plate.
2. The electrical supply provided by the utility must be
sufficient to handle load imposed by this unit.
3. Refer to Installation, General section (page 2) and
Fig. 1 and Fig. 2 for locations of electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.
4. This installation must conform with local building
codes and with the NEC (National Electrical Code) or
ANSI (American National Standards Institute)/NFPA
(National Fire Protection Association) latest revision.
Refer to provincial and local plumbing or wastewater
codes and other applicable local codes.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.

40RU

!

WARNING

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal
injury,death and/or equipment damage.
PuronR (R-- 410A) refrigerant systems operate at
higher pressures than standard R-- 22 systems. Do not
use R-- 22 service equipment or components on Puron
refrigerant equipment.

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear safety glasses and gloves when handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.

Moving and Storage - To transfer unit from truck to
storage site, use a fork truck. Do not stack units more than
2 high during storage. If unit is to be stored for more than
2 weeks before installation, choose a level, dry storage
site free from vibration. Do not remove plastic wrap or
skid from unit until final installation.
Rigging - All 40RU Series units can be rigged by using
the shipping skid. Units are shipped fully assembled. Do
not remove shipping skids or protective covering until
unit is ready for final placement; damage to bottom panels
can result. Use slings and spreader bars as applicable to
lift unit.

INSTALLATION
General - Allow the following clearances for service
access and airflow:
S Rear: 3 ft (914 mm) [21/2 ft (762 mm) with electric heat
accessory]
S Front: 21/2 ft (762 mm)

!

CAUTION

CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
40RU units.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Ensure voltage listed on unit data plate agrees with
electrical supply provided for the unit.

S Right Side: 31/2 ft (1067 mm)
S Left Side: 21/2 ft (762 mm)
For units equipped with an economizer, refer to the
accessory installation instructions for additional clearance
requirements. Be sure floor, wall, or ceiling can support
unit weight (Tables 1A – 1F). See Fig. 1 and Fig. 2 for
dimensions.
Uncrating - Move unit as near as possible to final
location before removing shipping skid.
Remove metal banding, top skid, and plastic wrap.
Examine unit for shipping damage. If shipping damage is
evident, file claim with transportation agency. Remove
base skid just prior to actual installation.
Check nameplate information against available power
supply and model number description in Fig. 3.
NOTE: Be sure to remove the styrofoam shipping pad
from the thermostatic expansion valve (TXV). Verify that
it has been removed. See Fig. 5.
Accessories - Refer to instructions shipped with each
accessory for specific information.
2

Table 1A — 40RUA Physical Data, English — Cooling Units
UNIT 40RUA*

25

28

30

NOMINAL CAPACITY (Tons)

20

25

30

Base Unit with TXV

730

1050

1062

Plenum

225

325

325

OPERATING WEIGHT (lb)

FANS
Qty...Diam. (in.)

2...15

2...18

2...18

Nominal Airflow (cfm)

8000

10000

12000

6000 – 10000

7500 – 12500

9000 – 15000

208/230---3---60 and 460---3---60

5.0

7.5

10.0

575---3---60

5.0

7.5

10.0

208/230---3---60 and 460---3---60

1745

1745

1745

575---3---60

1745

1755

1755

Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)

REFRIGERANT
Operating charge (lb)
(approx per circuit){
DIRECT ---EXPANSION COIL

R--- 410A
3.5

4.5

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (psig)
Face Area (sq ft)

5.0

650
19.88

24.86

No. of Splits

2

2

2

No. of Circuits per Split

18

20

24

Split Type...Percentage
Rows...Fins/in.

29.83

Face...50/50
4...15

4...15

4...15

2...11/8

2...13/8

2...13/8

PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)

2...5/8

DX Coil — Liquid Refrigerant (ODF)

1...21/2

Steam Coil, In (MPT)

1...1/2

Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2
1...11/4 ODM/1 IDF

Condensate (PVC)
FILTERS
Quantity...Size (in.)

Throwaway — Factory Supplied
4...16 x 20 x 2
4...16 x 24 x 2

Access Location

4...20 x 24 x 2
4...20 x 25 x 2
Either Side

STEAM COIL}
Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

1...10

1...10

1...10

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

2...8.5

2...12.5

2...12.5

HOT WATER COIL}
Max Working Pressure (psig)

150

Water Volume
(gal)

13.9

(ft3)

14.3
1.90

LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.

3

40RU

Motor Speed (rpm)

Table 1B — 40RUA Physical Data, SI — Cooling Units
UNIT 40RUA*

25

28

30

NOMINAL CAPACITY (kW)

70

87

105

Base Unit with TXV

331

477

482

Plenum

102

148

148

2...381

2...457

2...457

3775

4119

5663

2831 – 4719

3539 – 5899

4247 – 7079

208/230---3---60 and 460---3---60

3.73

5.60

7.46

575---3---60

3.73

5.60

7.46

208/230---3---60 and 460---3---60

29.1

29.1

29.1

575---3---60

29.1

29.3

29.3

OPERATING WEIGHT (kg)

FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)

40RU

Motor Speed (r/s)

REFRIGERANT

R--- 410A

Operating charge (kg)
(approx per circuit){
DIRECT ---EXPANSION COIL

1.59

2.04

2.27

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (kPag)

4481

Face Area (sq m)

1.85

2.30

No. of Splits

2

2

2

No. of Circuits per Split

18

20

24

Split Type...Percentage

2.77

Face...50/50

Rows...Fins/m

4...591

4...591

4...591

2...11/8

2...13/8

2...13/8

PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)

2...5/8

DX Coil — Liquid Refrigerant (ODF)

1...21/2

Steam Coil, In (MPT)

1...1/2

Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2
1...11/4 ODM/1 IDF

Condensate (PVC)
FILTERS
Quantity...Size (mm.)

Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51

Access Location

4...508 x 610 x 51
4...508 x 635 x 51
Either Side

STEAM COIL}
Max Working Pressure (kPag at 126° C)
Total Face Area (sq m)
Rows...Fins/m

138
1.24

1.39

1.39

1...394

1...394

1...394

HOT WATER COIL}
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m

1034
1.24

1.39

1.39

2...335

2...335

2...335

Water Volume
(L)

52.6

54.1

(m3)

0.052

0.054

LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.

4

Table 1C — 40RUQ Physical Data, English — Heat Pump Units
UNIT 40RUQ*

25

NOMINAL CAPACITY (Tons)

20

OPERATING WEIGHT (lb)
Base Unit with TXV

720

Plenum

140

FANS
Qty...Diam. (in.)

2...15

Nominal Airflow (cfm)

8000

Airflow Range (cfm)

6000--- 10000

Nominal Motor Hp (Standard Motor)
208/230---3---60 and 460---3---60

5.0

575---3---60

5.0

208/230---3---60 and 460---3---60

1745

575---3---60

1745

REFRIGERANT

R--- 410A

Operating charge (lb)
(approx per circuit){
DIRECT ---EXPANSION COIL

3.5/3.5
Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (psig)

650

Face Area (sq ft)

19.9

No. of Splits

2

No. of Circuits per Split

2

Split Type...Percentage

Face....50/50

Rows...Fins/in.

4...15

PIPING CONNECTIONS,
Quantity...Size (in.)
2...11/8

DX Coil — Suction (ODF)

2...5/8

DX Coil — Liquid Refrigerant (ODF)

1...21/2

Steam Coil, In (MPT)

1...11/2

Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2
1...11/4 ODM/1 IDF

Condensate (PVC)
FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2
4...16 x 24 x 2
Right or Left Side

Access Location
STEAM COIL}
Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

13.33

Rows...Fins/in.

1...10

HOT WATER

COIL}

Max Working Pressure (psig)

150

Total Face Area (sq ft)

13.33

Rows...Fins/in.

2...8.5

Water Volume
(gal)

13.9

(ft3)

1.85

LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.

5

40RU

Motor Speed (rpm)

Table 1D — 40RUA Physical Data, SI — Heat Pump Units
UNIT 40RUQ*

25

NOMINAL CAPACITY (kW)

70

OPERATING WEIGHT (kg)
Base Unit with TXV

326

Plenum

44

FANS
Qty...Diam. (mm)

2...381

Nominal Airflow (L/s)

3775

Airflow Range (L/s)

2831--- 4719

Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60

3.73

575---3---60

3.73

40RU

Motor Speed (r/s)
208/230---3---60 and 460---3---60

29.1

575---3---60

29.1

REFRIGERANT

R--- 410A

Operating charge (kg)
(approx per circuit){
DIRECT ---EXPANSION COIL

1.59/1.59
Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (kPag)

4482

Face Area (sq m)

1.85

No. of Splits

2

No. of Circuits per Split

2

Split Type...Percentage

Face...50/50

Fins/m

591

PIPING CONNECTIONS,
Quantity...Size (in.)
2...11/8

DX Coil — Suction (ODF)

2...5/8

DX Coil — Liquid Refrigerant (ODF)

1...21/2

Steam Coil, In (MPT)

1...11/2

Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)

1...2

Hot Water Coil, Out (MPT)

1...2
1...11/4 ODM/1 IDF

Condensate (PVC)
FILTERS

Throwaway — Factory Supplied

Quantity...Size (mm)

4...406 x 610 x 51
4...406 x 508 x 51

Access Location

Right or Left Side

STEAM COIL}
Max Working Pressure (kPag at 126° C)

138

Total Face Area (sq m)

1.24

Rows...Fins/m
HOT WATER

1...394

COIL}

Max Working Pressure (kPag)

1034

Total Face Area (sq m)

1.24

Rows...Fins/m

2...335

Water Volume
(L)

52.6

(m3)

0.052

LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
{
Units are shipped without refrigerant charge.
}
Field installed accessory only.

6

Table 1E — 40RUS Physical Data, English — Chilled Water Units
UNIT 40RUS*

25

28

30

NOMINAL CAPACITY (Tons)

20

25

30

Base Unit

683

1035

1042

Plenum

225

325

325

OPERATING WEIGHT (lb)

FANS
Qty...Diam. (in.)

2...15

2...18

2...18

Nominal Airflow (cfm)

8000

10000

12000

6000 – 10000

7500 – 12500

9000 – 15000

208/230---3---60 and 460---3---60

5.0

7.5

10.0

575---3---60

5.0

7.5

10.0

208/230---3---60 and 460---3---60

1745

1745

1745

575---3---60

1745

1755

1755

Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)

CHILLED WATER COIL

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (psig)

435

Face Area (sq ft) – Upper

11.0

12.4

15.5

Face Area (sq ft) – Lower

8.3

12.4

12.4

Rows...Fins/in.

3...15

PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In.
Chilled Water — Out

2...13/8 ODM
2...21/ ODM
8

Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)

2...21/ ODM
8
2...21/ ODM
8

2...21/ ODM
8
1...21/2
1...11/2

1...2

Hot Water Coil, Out (MPT)

1...2
1...11/4 ODM/1 IDF

Condensate (PVC)
FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2
4...16 x 24 x 2

Access Location
STEAM

2...21/8 ODM

4...20 x 24 x 2
4...20 x 25 x 2
Either Side

COIL}

Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

1...10

1...10

1...10

Total Face Area (sq ft)

13.33

15.0

15.0

Rows...Fins/in.

2...8.5

2...12.5

2...12.5

HOT WATER COIL}
Max Working Pressure (psig)

150

Water Volume
(gal)

13.9

14.3

(ft3)

1.1

1.90

LEGEND
}

Field installed accessory only.

7

40RU

Motor Speed (rpm)

Table 1F — 40RUS Physical Data, SI — Chilled Water Units
UNIT 40RUS*

25

28

30

NOMINAL CAPACITY (kW)

70

87

105

OPERATING WEIGHT (kg)
Base Unit
Plenum

310
102

469
148

473
148

2...381
3775
2831 – 4719

2...457
4719
3539 – 5899

2...457
5663
4247 – 7079

3.73
3.73

5.60
5.60

7.46
7.46

29.1
29.1

29.1
29.3

29.1
29.3

40RU

FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
208/230---3---60 and 460---3---60
575---3---60
Motor Speed (r/s)
208/230---3---60 and 460---3---60
575---3---60
CHILLED WATER COIL
Max Working Pressure (kPag)
Face Area (sq m) – Upper
Face Area (sq m) – Lower
Rows...Fins/m
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In
Chilled Water — Out
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (PVC)
FILTERS
Quantity...Size (mm.)
Access Location
STEAM COIL}
Max Working Pressure (kPag at 125° C)
Total Face Area (sq m)
Rows...Fins/m
HOT WATER COIL}
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
(m3)

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins
2999
1.02
1.15
1.44
0.77
1.15
1.15
3...591
3...591
3...591

2...13/8 ODM
2...13/8 ODM

2...21/8 ODM
2...21/8 ODM

Throwaway — Factory Supplied
4...406 x 508 x 51
4...508 x 610 x 51
4...406 x 610 x 51
4...508 x 635 x 51
Either Side

1.24
1...394

138
1.39
1...394

1.39
1...394

1.24
2...335

1034
1.39
2..493

1.39
2...493

52.6
0.052

LEGEND
}

2...21/8 ODM
2...21/8 ODM
1...21/2
1...11/2
1...2
1...2
1...11/4 ODM/1 IDF

Field installed accessory only.

8

54.1
0.054

40RU
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT WEIGHT
lb (kg)
40RUA*25
730 (331)
40RUQ*25
720 (326)
40RUS*25
683 (310)
UNIT

Fig. 1 - Dimensions – Size 25

9

C10722

40RU

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.

Direction of airflow.

3. Recommended clearance:
• Rear: 3 in. [914 mm] (2 ft, 6 in. [762 mm]
with electric heat accessory)
• Front: 2 ft, 6 in. [762 mm]
• Right Side: 2 ft, 6 in. [762 mm]
• Left Side: 2 ft, 6 in. [762 mm]
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
6. 40RUS may require alternate or additional
field favricated poping access holes

UNIT
40RUA*28
40RUA*30
40RUS*28
40RUS*30

Fig. 2 - Dimensions – Sizes 28 and 30

10

UNIT WEIGHT
lb (kg)
1050 (477)
1062 (482)
1035 (469)
1042 (473)
C10723

1

2

4

0 R U A A 2

3

4

5

6

7

_____________

8

9

10 11 12 13 14 15 16 17 18

5 A 1 A 6

– 0 A 0 A 0

____

Model Type

Brand / Packaging

40RU = Carrier Fan Coil
Puronr R–410ARefrigerant

0 = Standard
Not Used
A = Place Holder

Type of Coil
A = StandardDXCoil
Q = Heat Pump
S = Chilled Water Coil

Service Options
0 = Non-Painted Cabinet
1 = Painted Cabinet

Refrigerant Options
A = None

Not Used
A = Place Holder

Nominal Tonnage
25 = 20 Tons
28 = 25 Tons
30 = 30 Tons

40RU

Not Used
0 = Place Holder
Design Rev
– = Catalog Model Number
1 = Design Revision (original)

Not Used
A = Place Holder
Indoor Fan Options
1 = Fan Drive and Motor - Low / Motor Efficiency - Standard

Voltage
1 = 575/3/60
5 = 208/ 230/3/60
6 = 460/3/60

2 = Fan Drive and Motor - Med / Motor Efficiency - Standard
3 = Fan Drive and Motor - High / Motor Efficiency - Standard

Coil Options
A = Al/Cu
C!0724

Fig. 3 - Model Number Nomenclature
POSITION NUMBER
TYPICAL

1
2

2
6

3
1

POSITION
1−2
3−4
5
6−10

4
0

5
G

6
1

7
2

8
3

9
4

10
5

DESIGNATES
Week of manufacture (fiscal calend ar)
Year of manufacture (“10” = 2010)
Manufacturing location (G = ETP, Texas, USA)
Seq uential numb er
C!0725

Fig. 4 - Serial Number Nomenclature
TXV

horizontal arrangement with return air entering
horizontally and the supply air discharging horizontally.
When applying the unit in a horizontal arrangement,
ensure the condensate drain pan is located at the bottom
center of the unit for adequate condensate disposal. See
Fig. 6 for condensate connections for each unit position.

COIL

PLUG

PLUG

CONDENSATE
DRAIN

REMOVE FOAM BLOCK

LEGEND
TXV — Thermostatic Expansion Valve

Fig. 5 - Foam Block Location

LEGEND
Accessory Line
Alternate Air Intake and Discharge

C10683

Air Intake and Discharge

Unit Positioning - The unit can be mounted on the floor
for vertical application with return air entering the face of
the unit and supply air discharging vertically through the
top of the unit. The unit can also be applied in a

Note: Maintain recommended clearances
per Fig. 1 and Fig. 2

Fig. 6 - Typical Unit Positioning
11

C10684

Typical positioning and alternate return air locations are
shown in Fig. 6. Alternate return air locations can be used
by moving the unit panel from the alternate return air
location to the standard return air location. Refer to
overhead suspension accessory drawing (Fig. 7) for

preferred suspension technique. The unit needs support
underneath to prevent sagging.
IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain from
unit.

40RU

OVERHEAD SUSPENSION ACCESSORY — UNIT SIZE 25

OVERHEAD SUSPENSION ACCESSORY — UNIT SIZES 28, 30

NOTE: Dimensions in [ ] are millimeters

Fig. 7 - Preferred Suspension Technique
12

C10728

Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points
when leveling.
Refrigerant and Chilled Water Piping Access - The
40RU Series units come with standard knockouts for
refrigerant and chilled water piping. These knockouts are
located on both sides of the unit for installation flexibility.
The standard knockouts provide sufficient access to the
unit’s coils for all 40RUA*25, 28, and 30 units.
40RUQ*25 units, as well as 40RUS*25, 28, and 30 units
require additional holes which must be field-- fabricated to
accommodate the piping. See Fig. 8 for the positions and
dimensions of the additional access holes required for
40RUQ and 40RUS units. Recommended access hole use
is also listed for all units. Note that Fig. 8 shows the
access holes on the control-- box side of the unit; this is the
side of the unit with the coil headers, so it is used most
often for piping access.
IMPORTANT:
underground.

Do

not

bury

refrigerant

piping

Refrigerant Piping - See Tables 1A–1F for refrigerant
pipe connection sizes. For ease in brazing, it is
recommended that all internal solder joints be made
before unit is placed in final position.

The 40RU direct-- expansion units have internal
factory-- installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-- 410A. See Table
2 for part numbers. Knockouts are provided in the unit
corner posts for 40RU refrigerant piping. See Fig. 8,
which also lists recommended knockouts and access holes
to use for each 40RU unit size. Recommended fittings are
listed in Table 3.
The sensor bulb capillary tubes must be routed from the
TXVs inside the unit through one of the piping access
holes. Clamp the TXV sensor bulb on a vertical portion of
the suction line, outside the unit. See Fig. 9.
NOTE: Be sure to remove the styrofoam shipping pad
from the TXV. Verify that it has been removed. See Fig. 5.
IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 40RU Series evaporator coils have a face-- split
design. Ensure that lower circuit of coil is first on/last off
when connected to the condensing unit and/or system
controls. See Fig. 10.
External TXV equalizer connections are provided and
factory-- brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction
line at least 45 degrees above bottom, at approximately
the 4 o’clock or 8 o’clock position. See Fig.11.

8
7
6
5
A

4

B

C

D

3
2
1

C10727

FIELD--FABRICATED HOLE DIAMATERS
in. (mm)

FIELD--FABRICATED HOLE POSITION DIMENSIONS
in. (mm)

UNIT

USE HOLE
NUMBERS

No. 5

No. 6

No. 7

No. 8

A

B

C

D

40RUA*25, 28, 30

1,2, 3, 4

—

—

—

—

—

—

—

—

40RUS*25

4, 5, 6, 7

13/4 (44.5)

13/4 (44.5)

13/4 (44.5)

—

3.0 (76.2)

6.0 (152.5)

10.5 (266.7)

—

40RUQ*25

3{,

11/8

11/8

(28.6)

13/4 (44.5)

—

3.25 (82.6)

6.125 (155.6)

10.38 (263.7)

21/2 (63.5)

21/2 (63.5)

21/2 (63.5)

6.0 (152.5)

9.625 (244.5)

13.38 (339.9)

40RUS*28, 30

5, 6, 7

5, 6, 7, 8

(28.6)

21/2 (63.5)

{ Must be enlarged from 11/ in. (28.6mm) to 13/ in. (44.5mm)
8
4

NOTE: Access hole knockouts 1--- 4 are factory--- supplied.

Fig. 8 - Refrigerant and Chilled Water Piping Access Holes
13

17.0 (431.8)

40RU

Unit Isolation - Where extremely quiet operation is
essential, install isolators between floor and base of unit,
or between ceiling and top section of unit.

EQUALIZER LINE

TXV
SENSING
BULB

UPPER
SPLIT

SOLENOID
VALVE
AIRFLOW

15 DIAMS
MIN

15 DIAMS
MIN

TXV
10
DIAMS
8 DIAMS
MIN

40RU

SIGHT
GLASS

8 DIAMS
MIN
EQUALIZER
FILTER
LINE
DRIER

TXV
SENSING
BULB

LOWER
SPLIT

AIRFLOW

TXV

10
DIAMS

INDOOR
COIL

LEGEND:
TXV – Thermostatic Expansion Valve
NOTE: Component location arrangemetshown for field installation of
sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.
The TXVs and equilizer lines are factory installed.

Fig. 9 - Face-- Split Coil Suction and Liquid Line Piping (Typical)

C10726

LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.

FIRST ON/LAST OFF = B

VERTICAL INSTALLATION

Fig. 11 - TXV Sensing Bulb Location

FIRST ON/LAST OF F = A

HORIZONTAL INSTALLATIO N
C10688

Fig. 10 - Typical Evaporator Coil Connections (40RU)

14

C10689

Table 2 – Factory-- Installed Nozzle and Distributor Data
TXV
Qty...Part No.

DISTRIBUTOR
Qty...Part No.

FEEDER TUBES
PER DISTRIBUTOR{
Qty...Size (in.)

4 Row

2...BBIZE--- 8--- GA

2...D196--- 18--- 3/16

18...3/16

2...G6

4 Row

2...BBIZE--- 15--- GA

2...1126

20...3/16

2...C15

4 Row

2...BBIZE--- 15--- GA

2...1126

24...3/16

2...C17

2--- 12...3/16

2...G8

UNIT

COIL TYPE
STD

40RUA*25
40RUA*28
40RUA*30
40RUQ*25

4 Row

2...BBIZE--- 12.5--- GA

2...113--- 12--- 3/

16

NOZZLE
Qty...Part No.

{ Feeder tube size is 1/ in. (6.35 mm).
4
NOTE: Hot gas bypass applications require field---supplied auxiliary side connector.

Table 3 – Fitting Requirements
UNIT

ACCESS
HOLE NO.}

CONNECTION
TYPE

FITTINGS REQUIRED†
(in.)

CIRCUIT

1

Suction

Lower

11/8 Nipple, 75/8 L
11/8 Long Radius Elbow

2

Liquid

Lower

40RUA*25
3

Liquid

Upper

5/

8

Street Elbow

5/

8

Nipple, 61/2 L

5/

8

Long Radius Elbow

5/

8

Street Elbow

5/

8

Nipple, 91/2 L

5/

8

Long Radius Elbow

11/8 Nipple, 55/8 L
4

Suction

Upper

11/8 Long Radius Elbow
11/8 Nipple, 11 L
11/8 Long Radius Elbow

3

5

Suction

Lower

Suction

Lower

40RUQ*25
6

Liquid

Upper

11/8 Nipple, 3 L
11/8 Long Radius Elbow
5/

8

Nipple, 27/8 L

5/

8

45_ Elbow

5/

8

Nipple, 15/8 L

5/

8

Long Radius Elbow

5/

8

Nipple, 27/8 L

5/

8

45_ Elbow

5/

8

Nipple, 41/4 L

5/

8

Long Radius Elbow

11/8 Nipple, 5 L
7

Suction

Upper

11/8 45_ Elbow
11/8 Nipple, 83/4 L
11/8 Long Radius Elbow
13/8 Long Radius Elbow

4

Supply

Lower

13/8 Nipple, 33/4 L
13/8 Long Radius Elbow
13/8 Long Radius Elbow

5

Return

Lower

40RUS*25

13/8 Nipple, 33/8 L
13/8 Long Radius Elbow
13/8 Long Radius Elbow

6

Return

Upper

13/8 Nipple, 7 L
13/8 Long Radius Elbow
13/8 Long Radius Elbow

7

Supply

Upper

13/8 Nipple, 113/4 L
11/8 Long Radius Elbow

}
†

See Fig. 8 for access hole location by number.
Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

15

40RU

11/8 Street Elbow

Table 3 — Fitting Requirement (cont)
UNIT

ACCESS
HOLE NO.}

CONNECTION
TYPE

FITTINGS REQUIRED†
(in.)

CIRCUIT

13/8 Street Elbow
1

Suction

Lower

13/8 Nipple, 11 L
13/8 Long Radius Elbow

2

Liquid

Lower

40RUA*28
3

Liquid

Upper

5/

8

Street Elbow

5/

8

Nipple, 11/2 L

5/

8

Long Radius Elbow

5/

8

Street Elbow

5/

8

Nipple, 191/2 L

5/

8

Long Radius Elbow

13/8 Nipple, 43/16 L
4

Suction

Upper

13/8 Long Radius Elbow
13/8 Nipple, 231/4 L
13/8 Long Radius Elbow

40RU

21/8 Long Radius Elbow
5

Supply

Lower

21/8 Nipple, 31/2 L
21/8 Long Radius Elbow
21/8 Long Radius Elbow

6

Return

Lower

21/8 Nipple, 3 L
21/8 Long Radius Elbow

40RUS*28, 30

21/8 Long Radius Elbow
7

Return

Upper

21/8 Nipple, 67/8 L
21/8 Long Radius Elbow
21/8 Long Radius Elbow

8

Supply

Upper

21/8 Nipple, 117/8 L
21/8 Long Radius Elbow
13/8 Street Elbow

1

Suction

Lower

13/8 Nipple, 3 L
13/8 Long Radius Elbow

2

Liquid

Lower

40RUA*30
3

Liquid

Upper

5/

8

Street Elbow

5/

8

Nipple, 73/4 L

5/

8

Long Radius Elbow

5/

8

Street Elbow

5/

8

Nipple, 181/2 L

5/

8

Long Radius Elbow

13/8 Nipple, 43/16 L
4

Suction

Upper

13/8 Long Radius Elbow
13/8 Nipple, 191/4 L
13/8 Long Radius Elbow

}
†

See Fig. 8 for access hole location by number.
Fittings are listed in order from header or tee stub connection out to access hole in corner support post.

16

To size, design, and install chilled water piping, consult
the Carrier System Design manual. See Fig. 12 for an
example of a typical installation. Recommended fittings
are listed in Table 3.

Knockouts are provided in the unit corner posts for
40RUS refrigerant piping. Additional field-- fabricated
access holes are required for 40RUS chilled water piping.
See Fig. 8, which lists recommended knockouts and
access holes to use for each 40RUS unit size.

To access 40RUS coil vents and drains, remove the unit
side panel over the coil header. Vent and drain plugs are
on the top and bottom of header, respectively. See the
Service section for information on preventing coil
freeze-- up during winter.

40RU

Chilled Water Piping - See Tables 1E and 1F for chilled
water connection sizes. For ease in brazing, it it
recommended that all internal solder joints be made
before unit is placed in final position.

Fig. 12 - Typical 40RUS Chilled Water Piping

17

C10690

Condensate Drain - Install a trapped condensate drain
line to unit connection as shown in Fig. 13. The unit drain
connection is a PVC stub. See Fig. 14. Some areas may
require an adapter to connect to either galvanized steel or
copper pipe. For these applications, install a
field-- supplied threaded PVC adapter.

40RU

3” MIN.
[76]

Fig. 14 - Drain Pan Slope Adjustment

C10692

As shipped, the unit’s condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be
changed to pitch towards the side of the unit with the
drain connection. See Fig. 14. Loosen the 2 screws next to
the drain outlet at both ends of the unit, push drain pan
down in the slots near the drain connection, and up in the
slots on the opposite end. Re-- tighten screws. The pan
should have a pitch of at least 1/4 - in. over its length
toward the drain connection.
NOTE: Dimensions in [ ] are in millimeters

Fig. 13 - Condensate Drains

C10691

Fan Motors and Drives - Motor and drive packages are
factory installed in all units. The motor and drive
packages consist of the following items:

NOTE: A trap must be installed in the condensate drain
line to ensure that the static pressure of fans is balanced with
the water column in the drain line and that condensate can
drain completely from pan. Without a trap, air can be drawn
up drain line until water level in condensate pan becomes
equal to static pressure created by fans, preventing complete
drainage. Conditions will worsen as filters become dirty.

1 — fan motor

Install clean-- out plugs in trap. Pitch drain line downward
to an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels.
Observe all local sanitary codes.

For instructions on changing fan rotation, changing drive
speeds and adjusting drives, see Pulley and Drive
Adjustment in the Service section.

1 — adjustable motor pulley
1 — fan pulley
2 — matched fan belts
(40RUA*25-- 30, 40RUQ*25, 40RUS*25-- 30 units)

18

!

FAN
CONTACTOR
BOX

MOTOR
AND DRIVE

WIRE
ACCESS
FAN DRIVE
PULLEY

CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground. Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.

!

FAN SCROLL

WARNING

FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect
switch and fan coil unit. Use only copper wire.
(See Fig. 15)

COIL
FILTER
ELEMENTS

TXV BULB
ACCESS
REFRIGERANT
PIPING ACCESS

FILTER
RETAINER
CLIP

CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)

LEGEND
TXV — Thermostatic Expansion Valve

Fig. 16 - Wiring and Service Access
(Side Panel Removed)

C10693

Fan motors are factory-- installed on all units. Indoor-- fan
contactors are located in the fan contactor box behind the
side access panel (see Fig. 16 and 17). Wire the thermostat
to the 24-- v control circuit terminal block located in the
side of the fan contactor control box, according to Fig. 18
or the unit label diagram. If the air handler is part of a
split system, complete the wiring from the condensing
unit to the thermostat shown in Fig. 18.

105° C 600V
RJ A

ELECTRIC
DISCONNECT
SWITCH
COPPER

13

12

11

W

23

22

21

WIRE ONLY
ALUMINUM
WIRE

Fig. 15 - Disconnect Switch and Unit

FAN
CONTACTOR
A93033

Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 15-- 17 and the
unit label diagram. Connect power wiring with 1/4 - in.
ring terminal.

24V
TERMINAL
BLOCK
POWER
WIRING
KNOCKOUT
C10694

Fig. 17 - Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)

19

40RU

Power Supply and Wiring - Check the unit data plate to
ensure that available power supply matches electrical
characteristics of the unit. Provide a disconnect switch
with an integrated lock-- out feature of size required to
provide adequate fan motor starting current. See Tables
4-- 6 for unit electrical data.

Table 4 – Electrical Data, Standard Motors
UNIT
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28

40RUA30
40RUS30

FAN MOTOR

POWER SUPPLY

V ---PH ---Hz{

VOLTAGE
LIMITS

Hp (kW)

FLA

Minimum
Circuit Amps

MOCP

208/230--- 3--- 60

187--- 253

5.0 (3.73)

14.7/13.6

18.4/17.0

30/25

460--- 3--- 60

414--- 506

5.0 (3.73)

6.8

8.5

15

575--- 3--- 60

518--- 632

5.0 (3.73)

5.1

6.4

15

208/230--- 3--- 60

187--- 253

7.5 (5.59)

21.4/19.4

26.9/24.3

45/40

460--- 3--- 60

414--- 506

7.5 (5.59)

9.7

12.1

20

575--- 3--- 60

518--- 632

7.5 (5.59)

7.8

9.8

15

208/230--- 3--- 60

187--- 253

10.0 (7.46)

28.0/25.2

35.0/31.5

60/50

460--- 3--- 60

414--- 506

10.0 (7.46)

12.6

15.8

25

575--- 3--- 60

518--- 632

10.0 (7.46)

10.3

12.9

20

40RU

See Legend and Notes below.

Table 5 – Electrical Data, Alternate Motors
UNIT
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUA*30
40RUS*28
40RUS*30

FAN MOTOR

V ---PH ---Hz{

VOLTAGE
LIMITS

Hp (kW)

208/230--- 3--- 60

187--- 253

460--- 3--- 60

414--- 506

575--- 3--- 60

POWER SUPPLY
FLA

Minimum
Circuit Amps

MOCP

7.5 (5.59)

21.4/19.4

26.9/24.3

45/40

7.5 (5.59)

9.7

12.1

20

518--- 632

7.5 (5.59)

7.8

9.8

15

208/230--- 3--- 60

187--- 253

10.0 (7.46)

28.0/25.2

35.0/31.5

60/50

460--- 3--- 60

414--- 506

10.0 (7.46)

12.6

15.8

25

575--- 3--- 60

518--- 632

10.0 (7.46)

10.3

12.9

20

See Legend and Notes below.

Legend and Notes for Tables 4 and 5

LEGEND:
FLA
--- Full Load Amps
MOCP --- Maximum Overcurrent Protection
{ Motors are designed for satisfactory operation within 10% of
normal voltage shown. Voltages should not exceed the limits
shown in the Voltage Limits column.

Example: Supply voltage is 230-3-60
% Voltage Imbalance

1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance with The NEC. Article 440.
Average Voltage =

2. Motor FLA values are established in accordance with Underwriters’ Laboratories (UL). Standard 1995.

4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the
40RU indoor fan motor per NEC Article 430--- 28 (1) or (2)
(depends on length of conduit between heater enclosure and
40RU power entry location). Install wires in field --- installed
conduit.

max voltage deviation from average voltage
average voltage

AB = 393 v
BC = 403 v
AC = 396 v

NOTES:

3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the formula in the example
(see column to the right) to determine the percentage of voltage imbalance.

= 100 x

=

(393 + 403 + 396)

=

3

1192
3

397

Determine maximum deviation from average voltage.
(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance

= 100 x

6
397

= 1.5%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

20

40RU
Fig. 18 - Unit Wiring
Table 6 – Fan Contactor Coil Data
UNIT
40RU*

VOLTAGE
(vac)

MAXIMUM
HOLDING VA

25, 28, 30

24

10

Connecting Ductwork - Refer to the Carrier System
Design Manual for the recommended design and layout of
ductwork. Fig. 19 shows recommended duct connection to
units with 2 fans.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without ductwork or discharge
plenum unless fan speed has been adjusted for
external static pressure of zero in. wg. Failure to do so
may result in motor overload.
DISCHARGE CONNECTIONS — Duct flanges are
factory-- supplied; they are shipped inside the unit attached
to the hairpin end of the coil tube sheet for field

C10695

installation. Using the existing screws, install the duct
flanges on the unit’s fan deck. Each fan discharge requires
2 flanges; each flange must be bent in the middle to
conform to the discharge opening. See Fig. 20. After
flanges are installed, connect them to the supply duct
using a canvas connection to prevent vibration. It is
important that this connection be properly fabricated to
prevent high air friction losses and air noise.
RETURN CONNECTIONS — When using return-- air
ductwork, route return-- air duct to the unit’s return air inlet
near the filter rack, using a canvas connection to prevent
transmission of unit vibration. If the duct blocks off the
unit’s access panel, provide a slip joint in the ductwork to
permit removal for servicing.
OUTDOOR-- AIR INLET CONNECTIONS — Connect
outdoor-- air inlet to field-- installed accessory economizer.
Refer to Economizer Installation Instructions.
Return-- Air Filters - Type and size of filters are shown
in Tables 1A – 1F and are factory-- supplied and
factory-- installed. In all units with 2 fans, a filter
replacement tool (hook) is shipped inside the unit for field
use when replacing filters. See the Service section for
instructions on filter element replacement.

21

40RU

Fig. 19 - Typical Fan Discharge Connections for Multiple Fan Units

Fig. 20 - Duct Flange Installation

22

C10696

C10697

START--UP

2. To increase superheat, turn the stem clockwise. To decrease the superheat, turn the stem counterclockwise.
Do not turn the stem more than one full turn.
3. Wait until suction pressure and superheat stabilize.
This may take more than 30 minutes.
4. Continue adjustment until superheat reaches 10_F to
15_F (5.5_C to 8.3_C).
5. Replace the seal cap; tighten.

Before starting unit, check the following and correct as
necessary:
S Is unit solidly supported?
S Is fan adjusted for speed and pulley alignment?
S Are pulleys, motor, and bearings securely mounted?
S Are there any loose parts that will rattle or vibrate?

INSTALLER / INSTALLATEUR

S Is condensate drain pan pitched for correct drainage?

S Are all panels securely fastened?

La surchauffe TXV doit être vérifiée au
moment de la mise en route initiale et
ajustée si nécessaire. La surchauffe doit
être comprise entre 10 et 15 degrés F.

S Are all electrical connections correct and tight?
40RUA and 40RUQ ONLY —

40RU500073 2.0

S Is TXV bulb located on suction tube per Fig. 21?
Fig. 22 - Label, TXV Adjustment

S Is the capillary tube to the bulb free of kinks and not
subject to pinching?

SERVICE

S Is the bulb well secured to the suction tube with strap?
Also refer to condensing unit or outdoor heat pump section
instructions before starting a split system. A split system
start--up checklist is provided at the end of these instructions.
40RU500072 2.0

IMPORTANT! / IMPORTANT
UPPER SPLIT
BLOC SUPÉRIEUR

AIR FLOW
CIRCULATION
D'AIR

SIGHT GLASS
HUBLOT

LOWER
SPLIT
BLOC
INFÉRIEUR

AIR FLOW
CIRCULATION
D'AIR

S Cleaning or replacement of filters.

SOLENOID
VALVE
VANNE
SOLÉNOÏDE

8 DIAMS MIN
8 x DIA. MIN

S Testing for cooling/heating system leaks.

FILTER
DRIER
FILTRE
DESSICCATEUR

TXV SENSING
BULB
CAPTEUR TXV

S Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return-- air
grille (if present).

S Adjustment of fan motor, belt, bearings, and wheels.

TXV

15 DIAMS MIN 10 DIAMS
15 x DIA. MIN 10 x DIA. MIN

Inspection and maintenance should be performed at
regular intervals and should include the following:

S Inspection of panels and sealing of unit against air
leakage.

EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE

TXV
SENSING
BULB
CAPTEUR TXV

S Checking of all electrical connections.

!

TXV

EQUALIZER LINE

15 DIAMS MIN 10 DIAMS
15 x DIA. MIN 10 x DIA. MIN

CONDUITE D'ÉQUILIBRAGE

8 DIAMS MIN
8 x DIA. MIN

C10828

INDOOR COIL
ÉCHANGEUR INTÉRIEUR

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping
access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit.
See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.
Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur
de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale
de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise
en marche, et d'entretien. La surchauffe doit être ajustée sur place.

Fig. 21 - Label, TXV Bulb Location

C10827

Adjusting TXV for Superheat
(40RUA and 40 RUQ only) —
The unit-- mounted thermostatic expansion valve(s) is/are
factory set to provided superheat at the bulb location in
10_F to 15_F (5.5_C to 8.3_C) range. Actual system load
conditions may require adjustment of the factory setting.
To adjust the TXV superheat setting:
1. Remove the seal cap from the bottom of the TXV
body.

WARNING

Most unit service can be performed by removing one or
both of the unit’s side panels. Coil cleaning or removal or
insulation cleaning may require removal of a rear, top, or
bottom panel, depending on the unit’s orientation. When
service is completed, replace unit panels.
Panels - Panels are fastened to unit frame with sheet
metal screws. Fan and coil compartment must be sealed
tightly after service to prevent air from bypassing the
cooling coil.

23

40RU

TXV superheat must be checked at initial
unit start-up and adjusted if necessary.
Superheat must be 10 - 15 deg F.

S Are coil baffle plates tight against coil to prevent air
bypass?

Fan Motor Lubrication - Fan motor supplied with unit is
permanently lubricated and requires no further
lubrication.
Fan Shaft Bearings - Size 25-- 30 units have pillow-- block
bearings (Fig. 23) that must be lubricated with suitable
bearing grease approximately every 3 months. See Table 7
for suitable lubricants.
Table 7 – Lubricant Data
MANUFACTURER

LUBRICANT

Mobil

Mobilplex EP No. 2

Sunoco

Prestige 42

Texaco

Multifak 2

Texaco

Regal AFB--- 2*

Centering Fan Wheel - If fan and fan shaft assembly are
not properly centered, blades may scrape against the
blower side scroll plate or may create an objectionable
whistling noise. It may be necessary to adjust individual
fan wheels or move entire fan shaft. See the following two
sections.
Fan Shaft Position Adjustment - Loosen setscrew or
locking collar of each fan shaft bearing. Slide shaft into
correct position and replace locking collar (Fig. 24). To
replace locking collar, push collar up against inner face of
bearing. Turn collar in direction of fan rotation until tight,
and tighten setscrew. Tightening locking collar in
direction of fan rotation results in further tightening of
collar should setscrew work itself loose.

40RU

*Preferred lubricant, contains rust and oxidation inhibitors.

Fig. 24 - Fan Shaft Bearing

C10699

C10698

Fig. 23 - Fan Shaft, Bearings, and Fan Wheel (Typical)

Fig. 25 - Fan Motor Mounting
24

C10700

Individual Fan Wheel Adjustment - Loosen the 2
locking bolts holding fan wheel hub to shaft. See Fig. 23.
Position fan wheel in center of the fan housing and tighten
locking bolts. Clearance between wheel and housing
should be the same on both sides.

If complete belt replacement is required during servicing,
loosen the motor plate mounting bolts (Fig. 25), move
motor/plate assembly towards fan pulley, and pull belt(s)
off pulleys. Reverse the procedure with new bolts and
readjust deflection.
Fig. 27 - Fan Pulley Adjustments

Fan Rotation - Correct fan rotation with respect to fan
outlet is shown in Fig. 26.

C10702

4. If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until
the pulleys are aligned.
5. Tighten motor holddown bolts.
Pulley and Drive Adjustment - To obtain desired fan
speed, refer to the fan motor and drive data in Tables
8A-- 11D and adjust fan motor pulley as follows:

Fig. 26 - Fan Rotation
To reverse the direction of rotation of a
motor, reverse any 2 of the power leads.
connection diagram on the inside of motor
cover for proper reversing procedure of
motor.

1. Remove belt from fan motor pulley after loosening
motor from motor base.
2. Loosen setscrew in moveable flange of pulley. Screw
moveable flange toward fixed flange to increase the
fan speed and away from fixed flange to reduce
speed. Before tightening setscrew, make certain that
setscrew is over nearest flat surface of pulley hub
(Fig. 27).

C10701

3-- phase fan
Refer to the
terminal box
single-- phase

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Increasing fan speed produces a greater load on motor.
Do not exceed rated capacity of motor.

Fan Pulley Alignment - Align as follows:
1. Loosen setscrews on pulleys.
2. Align pulleys visually and tighten setscrews on fan
pulley to lock it in place.
3. Use the methods shown in Fig. 27 to check proper
pulley alignment.

Condensate Drains - Keep condensate drains free of dirt
and foreign matter.
Return-- Air Filters - Refer to Replacing Filters section
for filter accessibility and removal. Replace with clean
filters of the sizes listed in Tables 1A-- 1F.

25

40RU

Fan Belts - Motor mounting plate and motor support
angles are slotted to permit both vertical and horizontal
adjustment. Adjust belt(s) for correct deflection by
loosening motor plate mounting bolts, moving motor/plate
assembly forward or back, and re-- tightening bolts. Press
down on belt with one finger midway between fan and
motor pulleys to check deflection. The correct deflection
is 1/8 - in. (3.2 mm). See Fig. 25.

Chilled Water Coil Freeze Protection - Shut off water
supply to unit. Remove side panel of unit and remove vent
and drain plugs in top and bottom of coil header. Drain
coil and blow out remaining water. Reinstall plugs and
side panel.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment
damage.
Do not operate unit without air filters.

Alternative freeze protection methods follow:
S Circulate hot water within the water coil’s supply main
or supplementary space heating.
S Close off supply lines to unit and open a union or
field-- supplied drain valve in the return line.

40RU

IMPORTANT: Draining from return line will not
completely drain water from coils.
S After draining as much water as possible from coils, add
sufficient antifreeze to prevent residual water in the coil
from freezing.

SLID

E

FILTER
RETAINER
CLIP

S Add a sufficient quantity of non-- corrosive antifreeze to
the entire system to prevent all water within the system
from freezing.
Coil Removal - Remove unit panels and corner posts as
required. Disconnect coil connections and remove fastening
screws. Remove coil through end or side sections of unit.
Cleaning Cooling Coil - Remove return-- air filters.
Remove any heavy dirt that may have accumulated on
underside of coil. Coil can be cleaned more easily with a
stiff brush, vacuum cleaner, or compressed air when coil
is dry. If coil is wet or if water is to be used for cleaning,
guard against splashing water on electrical components or
damaging surrounding area. Clean coil baffles as
applicable and check for tight fit to be sure air does not
bypass coil.

Fig. 28 - Remove Filter Retainer Clip

C10703

Cleaning Insulation - The insulation contains an
immobilized antimicrobial agent that helps prevent the
growth of bacteria and fungi. Clean the inner surface of
the insulation according to the separate maintenance
instructions shipped with the unit.
Replacing Filters - Filters can be removed and installed
from either side of the unit. Install new filters in units that
have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 28).
3. Remove old filters by lifting and tilting them out of
the filter track. See Fig. 16 and 29. Use the factory-supplied filter hook to slide filters within reach for removal. The filter hook is shipped inside the unit in
the filter track
4. Reverse the procedure to install new filters.

Fig. 29 - Filter Removal/Replacement

26

C10704

Table 8A -- Fan Motor Data, Standard Motor — English
40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

1745

1745

1745

5.0

7.5

10.0

Frame (NEMA)

S184T

S213T

S215T

Shaft Dia (in.)

11/8

13/8

13/8

1745

1755

1755

5.0

7.5

10.0

Frame (NEMA)

184T

S213T

D215T

Shaft Dia (in.)

11/8

13/8

13/8

UNIT
208/230---3---60 and 460---3---60
Speed (rpm)
Hp

575---3---60
Speed (rpm)
Hp

40RU

LEGEND
NEMA — National Electrical Manufacturers Association

Table 8B -- Fan Motor Data, Alternate Motor — English
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

1745

1745

1745

208/230---3---60 and 460---3---60
Speed (rpm)
Hp

7.5

10.0

10.0

Frame (NEMA)

S213T

S215T

S215T

Shaft Dia (in.)

13/8

13/8

13/8

1755

1750

1750

575---3---60
Speed (rpm)
Hp

7.5

10.0

10.0

Frame (NEMA)

S213T

D215T

D215T

Shaft Dia (in.)

13/8

13/8

13/8

LEGEND
NEMA — National Electrical Manufacturers Association

27

Table 8C -- Fan Motor Data, Standard Motor — SI
40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

Speed (r/s)

29.08

29.08

29.08

Shaft kW

3.73

5.60

7.46

Frame (NEMA)

S184T

S213T

S215T

Shaft Dia (mm)

28.6

34.9

34.9

Speed (r/s)

29.08

29.25

29.25

Shaft kW

3.73

5.60

7.46

Frame (NEMA)

184T

S213T

S215T

Shaft Dia (mm)

28.6

34.9

34.9

UNIT
208/230---3---60 and 460---3---60

40RU

575---3---60

LEGEND
NEMA — National Electrical Manufacturers Association

Table 8D -- Fan Motor Data, Alternate Motor — SI
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

29.08

29.17

29.17

208/230---3---60 and 460---3---60
Speed (r/s)
Shaft kW

5.60

7.46

7.46

Frame (NEMA)

S213T

S215T

S215T

Shaft Dia (mm)

34.9

34.9

34.9

29.25

29.17

29.17

575---3---60
Speed (r/s)
Shaft kW

5.60

7.46

7.46

Frame (NEMA)

S213T

D215T

D215T

Shaft Dia (mm)

34.9

34.9

34.9

LEGEND
NEMA — National Electrical Manufacturers Association

28

Table 9A -- Standard Drive Data, 60 Hz — English
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

Motor Pulley Pitch Diameter (in.)

3.7--- 4.7

4.3--- 5.3

4.3--- 5.3

3.0

3.0

3.0

MOTOR DRIVE
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)

9.4

11.0

11.0

Pulley Bore (in.)

17/16

115/16

115/16

Belt No. — Section

2—B

2—B†

2—B†

Belt Pitch (in.)

41.8

(2) 42.8
(2) 43.8

(2) 42.8
(2) 43.8

771

752

752

679--- 863

682--- 841

674--- 831

1200

1100

1100

15.3

13.1

13.1

6

6

6

9.12--- 10.99

6.67--- 9.43

6.67--- 9.43

Factory Setting
Range
Max Allowable Speed (rpm)
1/
2

Change per
Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
†

Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9B -- Medium--Static Drive Data, 60 Hz — English
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

Motor Pulley Pitch Diameter (in.)

4.3--- 5.3

4.3--- 5.3

4.3--- 5.3

3.0

3.0

3.0

MOTOR DRIVE
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)

9.4

9.4

9.4

Pulley Bore (in.)

17/16

115/16

115/16

Belt No. — Section

1—B

2—B†

2—B†

Belt Pitch (in.)

41.8

(2) 38.8
(2) 39.8

(2) 38.8
(2) 39.8

881

881

881

798--- 984

798--- 984

798--- 984

Max Allowable Speed (rpm)

1200

1100

1100

Change per 1/2 Turn of
Moveable Motor Pulley
Flange

15.3

15.3

15.3

6

6

6

9.16--- 10.99

6.67--- 9.43

6.67--- 9.43

FAN SPEEDS (rpm)
Factory Setting
Range

MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
†

Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

29

40RU

FAN SPEEDS (rpm)

Table 9C -- High--Static Drive Data, 60 Hz — English
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

4.3--- 5.3

4.3--- 5.3

4.3--- 5.3

3.0

3.0

3.0

MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)

7.4

8.6

8.6

Pulley Bore (in.)

17/16

115/16

115/16

Belt No. — Section

2—B

2—B

2—B

Belt Pitch (in.)

36.8

378

37.8

FAN SPEEDS (rpm)

40RU

Factory Setting
Range
Max Allowable Speed (rpm)
1/
2

Change per
Turn of
Moveable Motor Pulley
Flange

1118

1024

1024

1014--- 1200†

873--- 1075

873--- 1075

1200

1100

1100

19.4

16.7

16.7

6

6

6

8.16--- 10.02

6.67--- 9.43

6.67--- 9.43

MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
† It

is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

Table 9D-- Standard Drive Data, 60 Hz — SI
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

Motor Pulley Pitch Diameter (mm)

94.0--- 119.4

109.2--- 134.6

109.2--- 134.6

3.0

3.0

3.0

Pulley Pitch Dia (mm)

239

279

279

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

2—B

2—B†

2—B†

Belt Pitch (mm)

1062

(2) 1987
(2) 1113

(2) 1987
(2) 1113

12.9

12.5

12.5

11.3--- 14.4

11.4--- 14.0

11.2--- 13.9

20.0

18.3

18.3

0.255

0.218

0.218

6

6

6

232--- 279

169--- 240

169--- 240

MOTOR DRIVE
Pulley Factory Setting
Full Turns Open
FAN DRIVE

FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1/ Turn
2

Change per
of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
†

Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

30

Table 9E -- Medium--Static Drive Data, 60 Hz — SI
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

109.2--- 134.6

109.2--- 134.6

109.2--- 134.6

3.0

3.0

3.0

MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)

239

239

239

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

1—B

2—B†

2—B†

Belt Pitch (mm)

1062

(2) 986
(2) 1011

(2) 986
(2) 1011

14.7

14.7

14.7

13.3--- 16.4

13.3--- 16.4

13.3--- 16.4

20.0

18.3

18.3

0.255

0.255

0.255

6

6

6

232--- 279

169--- 240

169--- 240

Factory Setting
Range
Max Allowable Speed (r/s)
1/ Turn
2

Change per
of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
†

Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9F -- High--Static Drive Data, 60 Hz — SI
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

Motor Pulley Pitch Diameter (mm)

109.2--- 134.6

109.2--- 134.6

109.2--- 134.6

3.0

3.0

3.0

Pulley Pitch Dia (mm)

188

203†

203

Pulley Bore (mm)

36.5

49.2

49.2

Belt No. — Section

2—B

2—B

2—B

Belt Pitch (mm)

935

935

960

18.6

17.1

17.1

16.9--- 20.0†

14.6--- 17.9

14.6--- 7.9

20.0

18.3

18.3

0.323

0.278

0.278

6

6

6

207--- 255

169--- 240

169--- 240

MOTOR DRIVE
Pulley Factory Setting
Full Turns Open
FAN DRIVE

FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1/
2

Change per
Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
† It

is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s

31

40RU

FAN SPEEDS (r/s)

Table 10A -- 40RU Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RU

40RUA*28
40RUS*28

40RUA*30
40RUS*30

AIRFLOW
(Cfm)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

6,000

532

1.25

569

1.39

639

1.69

711

2.06

781

2.48

846

2.93

905

3.60

7,000

608

1.93

641

2.09

702

2.42

763

2.08

824

3.23

885

3.71

943

4.23

8,000

686

2.83

716

3.01

770

3.38

823

3.77

876

4.21

930

4.70

983

5.24

9,000

764

3.97

791

4.18

841

4.59

888

5.02

935

5.47

982

5.96

1030

6.51

10,000

843

5.38

868

5.62

914

6.09

957

6.55

1000

7.02

1042

7.53

1084

8.08

7,500

456

1.29

490

1.47

556

1.85

621

2.25

678

2.64

729

3.06

778

3.60

8,750

521

1.98

551

2.18

608

2.61

664

3.07

720

3.53

770

3.99

816

4.45

10,000

587

2.88

614

3.11

664

3.59

714

4.09

763

4.62

812

5.15

857

5.68

11,250

653

4.03

678

4.29

724

4.82

768

5.37

812

5.95

856

6.54

899

7.14

12,500

720

5.46

743

5.75

785

6.33

825

6.93

865

7.55

904

8.20

944

8.86

15,000

829

8.84

850

9.19

888

9.88

924

10.57

958

11.27

991

11.99

1024

12.73

9,000

521

1.99

550

2.25

616

2.77

676

3.23

731

3.72

782

4.20

829

4.70

10,500

596

3.16

623

3.40

672

3.89

720

4.40

767

4.94

814

5.50

859

6.05

12,000

673

4.63

698

4.90

743

5.45

785

6.02

826

6.62

867

7.23

908

7.87

13,500

751

6.51

773

6.82

815

7.44

853

8.06

890

8.71

927

9.38

963

10.07

15,000

829

8.84

850

9.19

888

9.88

924

10.57

958

11.27

991

11.99

1024

12.73

See Legend and Notes on page 36.

Table 10A -- 40RU Standard Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
UNIT

AIRFLOW
(Cfm)

40RUA*28
40RUS*28

40RUA*30
40RUS*30

1.6

1.8

2.0

2.2

2.4

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

954

3.83

1005

4.27

1052

4.72

1098

5.22

1142

5.67

—

—

7,000

990

4.74

1040

5.24

1090

5.80

1135

6.30

1176

6.84

—

—

8,000

1028

5.79

1078

6.38

1130

7.00

1173

7.60

—

—

—

—

6,000
40RUA*25
40RUQ*25
40RUS*25

1.4
Rpm

9,000

1073

7.11

1120

7.72

1169

8.37

—

—

—

—

—

—

10,000

1126

8.75

1166

9.37

—

—

—

—

—

—

—

—

7,500

831

4.41

870

5.10

913

5.90

950

6.88

985

7.70

—

—

8,750

859

4.97

901

5.59

944

6.42

980

7.20

1020

8.10

—

—

10,000

900

6.20

939

6.74

976

7.33

1013

8.00

1050

8.82

—

—

11,250

941

7.73

980

8.32

1017

8.90

1052

9.51

1088

10.16

—

—
—

12,500

984

9.53

1022

10.19

1058

10.84

1093

11.49

—

—

—

15,000

1057

13.49

1090

14.28

—

—

—

—

—

—

—

—

9,000

866

5.20

899

5.85

950

6.65

989

7.38

1029

8.32

1077

9.74

10,500

902

6.60

942

7.14

980

7.70

1016

8.31

1051

8.99

1085

9.77

12,000

949

8.50

988

9.14

1026

9.76

1062

10.38

1095

11.01

—

—

13,500

1000

10.78

1036

11.49

1073

12.21

—

—

—

—

—

—

15,000

1057

13.49

1090

14.28

—

—

—

—

—

—

—

—

See Legend and Notes on page 36.

32

Table 10B -- 40RU Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

0

50

100

150

200

250

300

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

2830

8.86

0.94

9.48

1.04

10.65

1.26

11.84

1.53

13.01

1.85

14.10

2.19

15.08

2.53

3300

10.14

1.44

10.69

1.56

11.70

1.81

12.71

2.08

13.73

2.41

14.74

2.77

15.71

3.15

3780

11.43

2.11

11.93

2.25

12.84

2.52

13.71

2.81

14.60

3.14

15.49

3.51

16.39

3.91

4250

12.74

2.96

13.19

3.12

14.02

3.43

14.81

3.74

15.59

4.08

16.37

4.45

17.17

4.85

4720

14.05

4.01

14.47

4.19

15.23

4.54

15.96

4.88

16.66

5.24

17.36

5.62

18.07

6.03

3540

7.60

0.96

8.16

1.09

9.27

1.38

10.34

1.68

11.30

1.97

12.15

2.28

12.97

2.68

4130

8.68

1.47

9.18

1.62

10.13

1.94

11.07

2.29

11.99

2.63

12.84

2.97

13.60

3.32

4720

9.78

2.15

10.23

2.32

11.07

2.67

11.89

3.05

12.72

3.45

13.53

3.84

14.29

4.23

5310

10.89

3.01

11.30

3.20

12.06

3.59

12.80

4.00

13.53

4.43

14.27

4.88

14.99

5.33

5900

12.00

4.07

12.38

4.29

13.09

4.72

13.75

5.17

14.41

5.63

15.07

6.11

15.74

6.61

4250

8.68

1.48

9.17

1.68

10.27

2.07

11.27

2.41

12.19

2.77

13.03

3.13

13.81

3.50

4960

9.93

2.35

10.38

2.53

11.21

2.90

11.99

3.28

12.78

3.68

13.56

4.10

14.32

4.51

5660

11.21

3.45

11.63

3.66

12.38

4.07

13.08

4.49

13.76

4.93

14.45

5.39

15.14

5.87

6370

12.51

4.85

12.89

5.08

13.58

5.54

14.22

6.01

14.83

6.49

15.44

6.99

16.05

7.51

7080

13.82

6.59

14.17

6.85

14.81

7.36

15.40

7.88

15.97

8.40

16.52

8.94

17.06

9.49

See Legend and Notes on page 36.

Table 10B -- 40RU Standard Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

AIRFLOW
(L/s)

350

400

450

500

550

600

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

2830

15.90

2.86

16.75

3.18

17.53

3.52

18.30

3.89

19.03

4.23

—

—

3300

16.50

3.53

17.33

3.91

18.17

4.32

18.92

4.70

19.60

5.10

—

—

3780

17.13

4.32

17.97

4.76

18.83

5.22

19.55

5.67

—

—

—

—

4250

17.88

5.30

18.67

5.76

19.48

6.24

—

—

—

—

—

—

4720

18.77

6.52

19.43

6.99

—

—

—

—

—

—

—

—

3540

13.85

3.29

14.50

3.80

15.22

4.40

15.83

5.13

16.42

5.74

—

—

4130

14.31

3.71

15.01

4.17

15.74

4.79

16.33

5.37

17.00

6.04

—

—

4720

14.99

4.62

15.65

5.02

16.27

5.46

16.88

5.97

17.50

6.57

—

—

5310

15.68

5.77

16.34

6.20

16.95

6.64

17.53

7.09

18.09

7.58

—

—

5900

16.39

7.10

17.03

7.60

17.64

8.08

18.22

8.57

—

—

—

—

4250

14.43

3.88

14.98

4.36

15.84

4.96

16.48

5.50

17.16

6.21

17.96

7.26

4960

15.04

4.92

15.71

5.32

16.33

5.74

16.93

6.20

17.51

6.70

18.09

7.29

5660

15.81

6.34

16.47

6.81

17.10

7.28

17.69

7.74

18.26

8.21

—

—

6370

16.66

8.04

17.27

8.57

17.88

9.10

—

—

—

—

—

—

7080

17.61

10.06

18.16

10.64

—

—

—

—

—

—

—

—

See Legend and Notes on page 36.

33

40RU

UNIT

AIRFLOW
(L/s)

Table 10C -- 40RU High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English
EXTERNAL STATIC PRESSURE (in. wg)
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RU

40RUA*28
40RUS*28

40RUA*30
40RUS*30

AIRFLOW
(Cfm)

0.0

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

6,000

542

1.29

577

1042

646

1.72

716

2.09

785

2.51

849

2.95

907

3.40

7,000

620

1.99

652

2.15

711

2.48

771

2.85

831

3.28

890

3.76

947

4.27

8,000

700

2.92

728

3.10

781

3.46

833

3.85

885

4.29

938

4.78

990

5.32

9,000

781

4.10

806

4.30

854

4.71

900

5.13

946

5.58

993

6.08

1039

6.62

10,000

862

5.56

885

5.79

929

6.24

971

6.70

1012

7.18

1054

7.69

1096

8.24

7,500

476

1.39

510

1.58

579

1.99

644

2.40

701

2.81

752

3.29

804

3.96

8,750

545

2.14

574

2.35

633

2.81

691

3.29

747

3.77

797

4.25

842

4.76

10,000

615

3.12

641

3.36

692

3.87

743

4.41

794

4.96

843

5.51

888

6.05

11,250

685

4.37

709

4.64

754

5.20

800

5.79

845

6.40

891

7.02

935

7.64

12,500

756

5.92

778

6.22

819

6.83

860

7.47

901

8.14

942

8.83

983

9.52

9,000

539

2.18

569

2.39

626

2.85

683

3.34

739

3.83

791

4.32

837

4.82

10,500

620

3.37

646

3.62

695

4.13

744

4.68

793

5.25

842

5.83

888

6.41

12,000

701

4.94

724

5.22

769

5.80

811

6.40

854

7.04

897

7.69

940

8.36

13,500

783

6.95

804

7.27

844

7.91

883

8.57

920

9.26

958

9.97

996

10.71

15,000

865

9.45

884

9.81

921

10.52

956

11.24

991

11.98

1025

12.75

1059

13.54

See Legend and Notes on page 36.

Table 10C -- 40RU High--Capacity Fan Performance Data —
0.0--2.4 in. wg External Static Pressure — English (cont)
EXTERNAL STATIC PRESSURE (in. wg)
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

AIRFLOW
(Cfm)

1.4

1.6

1.8

2.0

2.2

2.4

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

6,000

961

3.86

1011

4.31

1058

4.77

1104

5.24

1147

5.71

—

—

7,000

1000

4.79

1050

5.32

1097

5.85

1142

6.38

1184

6.91

—

—

8,000

1041

5.88

1090

6.47

1137

7.07

1181

7.67

—

—

—

—

9,000

1086

7.21

1133

7.82

1178

8.47

—

—

—

—

—

—

10,000

1138

8.83

1180

9.46

—

—

—

—

—

—

—

—

7,500

874

5.33

897

5.91

940

6.80

990

7.50

—

—

—

—

8,750

886

5.36

930

6.13

982

7.32

1020

8.10

—

—

—

—

10,000

930

6.60

969

7.20

1007

7.89

1045

8.71

—

—

—

—

11,250

976

8.25

1014

8.86

1051

9.49

1086

10.17

—

—

—

—

12,500

1023

10.20

1061

10.88

1097

11.56

—

—

—

—

—

—

9,000

881

5.37

923

6.03

967

6.89

1020

8.25

—

—

—

—

10,500

930

6.97

970

7.55

1008

8.17

1045

8.86

—

—

—

—

12,000

981

9.02

1021

9.67

1058

10.32

1094

10.97

—

—

—

—

13,500

1035

11.45

1072

12.20

—

—

—

—

—

—

—

—

15,000

1093

14.35

—

—

—

—

—

—

—

—

—

—

See Legend and Notes on page 36.

34

Table 10D -- 40RU High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI
EXTERNAL STATIC PRESSURE (kPa)

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

0

50

100

150

200

250

300

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

2830

9.03

0.96

9.62

1.06

10.77

1.29

11.94

1.56

13.08

1087

14.15

2.20

15.12

2.54

3330

10.34

1.48

10.86

1.60

11.85

1.85

12.84

2.12

13.85

2.45

14.84

2.80

15.78

3.18

3780

11.67

2.17

12.14

2.31

13.02

2.58

13.88

2.87

14.75

3.20

15.63

3.56

16.50

3.96

4250

13.01

3.05

13.44

3.21

14.23

3.51

15.00

3.82

15.77

4.16

16.54

4.53

17.32

4.94

4720

14.36

4.15

14.75

4.32

15.48

4.66

16.18

4.99

16.87

5.35

17.56

5.73

18.26

6.14

3540

7.94

1.04

8.51

1.18

9.65

1.48

10.73

1.79

11.68

2.10

12.53

2.46

13.40

2.95

4130

9.08

1.59

9.57

1.75

10.55

2.10

11.52

2.46

12.45

2.81

13.28

3.17

14.04

3.55

4720

10.24

2.33

10.68

2.51

11.53

2.88

12.39

3.29

13.24

3.70

14.05

4.11

14.80

4.51

5310

11.42

3.26

11.81

3.46

12.57

3.88

13.33

4.32

14.09

4.77

14.85

5.24

15.58

570

5900

12.60

4.42

12.96

4.64

13.65

5.09

14.33

5.57

15.01

6.07

15.40

6.58

16.38

7.10

4250

8.99

1.62

9.49

1.78

10.44

2.12

11.39

2.49

12.32

2.86

13.18

3.22

13.95

3.59

4960

10.33

2.51

10.77

2.70

11.59

3.08

12.40

3.49

13.22

3.92

14.03

4.35

14.79

4.78

5660

11.68

3.68

12.07

3.90

12.81

4.33

13.52

4.77

14.23

5.25

14.95

5.74

15.66

6.23

6370

13.04

5.18

13.40

5.42

14.07

5.90

14.71

6.39

15.34

6.90

15.97

7.44

16.61

7.98

7080

14.42

7.05

14.74

7.31

15.36

7.84

15.94

8.38

16.51

8.93

17.08

9.51

17.65

10.10

See Legend and Notes on page 36.

Table 10D -- 40RU High--Capacity Fan Performance Data —
0--600 kPa External Static Pressure — SI (cont)
EXTERNAL STATIC PRESSURE (kPa)
UNIT

40RUA*25
40RUQ*25
40RUS*25

40RUA*28
40RUS*28

40RUA*30
40RUS*30

AIRFLOW
(L/s)

350

400

450

500

550

600

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

2830

16.01

2.88

16.85

3.22

17.64

3.56

18.39

3.91

19.12

4.26

—

—

3300

16.67

3.57

17.50

3.96

18.28

4.36

19.03

4.75

19.73

5.15

—

—

3780

17.35

4.39

18.17

4.82

18.95

5.27

19.68

5.72

—

—

—

—

4250

18.11

5.37

18.88

5.83

19.63

6.31

—

—

—

—

—

—

4720

18.96

6.58

19.67

7.05

—

—

—

—

—

—

—

—

3540

14.57

3.97

14.95

4.41

15.67

5.07

16.50

5.59

—

—

—

—

4130

14.76

3.99

15.51

4.57

16.36

5.46

17.00

6.04

—

—

—

—

4720

15.49

4.92

16.15

5.37

16.78

5.88

17.42

6.50

—

—

—

—

5310

16.26

6.15

16.91

6.61

17.51

7.08

18.10

7.58

—

—

—

—

5900

17.04

7.61

17.68

8.11

18.28

8.62

—

—

—

—

—

—

4250

14.68

4.00

15.38

4.49

16.12

5.14

17.00

6.15

—

—

—

—

4960

15.51

5.20

16.17

5.63

16.80

6.09

17.41

6.61

—

—

—

—

5660

16.35

6.72

17.01

7.21

17.64

7.69

18.23

8.18

—

—

—

—

6370

17.24

8.54

17.87

9.10

—

—

—

—

—

—

—

—

7080

18.22

10.70

—

—

—

—

—

—

—

—

—

—

See Legend and Notes on page 36.

35

40RU

UNIT

AIRFLOW
(L/s)

Legend and Notes for Tables 10A and 10C

40RU

LEGEND
Bhp --- Brake Horsepower Input to Fan
ESP --- External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 1200 rpm . Maximum
allowable fan speed for size 28 and 30 units is 1100 rpm.
2. Fan performance is based on deductions for wet coil, clean 2-in. filters,
and unit casing. See table at right for factory-supplied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
UNIT
40RUA*25
40RUQ*25
40RUS*25

AIRFLOW
(Cfm)

PRESSURE DROP
(in. wg)

6,000

0.12

8,000

0.19

10,000

0.26

7,500

0.15

40RUA*28
40RUS*28

10,000

0.22

12,500

0.30

9,000

0.19

40RUA*30
40RUS*30

12,000

0.29

15,000

0.40

Legend and Notes for Tables 10B and 10D
LEGEND
ESP --- External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 20 r/s. Maximum
allowable fan speed for size 28 and 30 units is 18.3 r/s.
2. Fan performance is based on deductions for wet coil, clean 51 ---mm
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.

FACTORY-SUPPLIED PRESSURE DROP — SI
UNIT
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28

40RUA*30
40RUS*30

36

AIRFLOW
(L/s)

PRESSURE DROP
(Pa)

2900

32

3800

47

4700

64

3500

36

4700

55

5900

76

4250

47

5650

71

7050

98

37

40RU

40RU
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 01/11

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

38

Catalog No: 40RU ---07SI
Replaces: 40RU--- 05SI

START--UP CHECKLIST
(SPLIT SYSTEMS WITH 40RU UNITS)

I. PRELIMINARY INFORMATION
OUTDOOR: MODEL NO.

INDOOR: MODEL NO.

SERIAL NO.

SERIAL NO.

ADDITIONAL ACCESSORIES

II. PRE--START--UP
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N)

WILL THIS DAMAGE PREVENT UNIT START-- UP? (Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)

CONTROLS
ARE THERMOSTAT(S) & INDOOR FAN CONTROL WIRING CONNECTIONS MADE & CHECKED? (Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N)
HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)

INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N)
ARE PROPER AIR FILTERS IN PLACE? (Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N)
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)

PIPING
40RUA, 40RUQ
HAS FOAM SHIPPING BLOCK BEEN REMOVED FROM THE TXV (Thermostatic Expansion Valve)? (Y/N)
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR UNIT (40RUA) OR OUTDOOR UINT
(40RUQ) COILS AS REQUIRED? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, INDOOR COILS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED) (Y/N)
ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING CORRECT LEVELS? (Y/N)
40RUS
HAS AIR BEEN BLED FROM SYSTEM? (Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CHILLERS, VALVES, & INDOOR COILS? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
39

40RU

IF SO, WHERE:

CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:

AB

V

AC

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

BC

V

V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START--UP
CHECK INDOOR FAN MOTOR SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:

40RU

COMP A1

COMP B1

OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING OUTDOOR UNIT AIR TEMP
LEAVING OUTDOOR UNIT AIR TEMP
INDOOR UNIT ENTERING AIR DB TEMP
INDOOR UNIT ENTERING AIR WB TEMP
INDOOR UNIT LEAVING AIR DB TEMP
INDOOR UNIT LEAVING AIR WB TEMP
OUTDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY)
OUTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY)
INDOOR UNIT ENTERING WATER TEMP
(40RUS ONLY)
INTDOOR UNIT LEAVING WATER TEMP
(40RUS ONLY)
COMPRESSOR AMPS (L1/L2/L3)

____/____/____

____/____/____

CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES, ARE THE SIGHT GLASSES SHOWING
OIL LEVEL AT 1/8 to 1/3 FULL? (Y/N)
NOTES:

Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date:01/11

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

40

Catalog No: 40RU ---07SI
Replaces: 40RU--- 05SI



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c321 44.398116, Tue Aug 04 2009 14:24:39
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2011:02:21 08:29:54-05:00
Create Date                     : 2011:02:21 08:29:54-05:00
Format                          : application/pdf
Title                           : 40RU-07SI
Creator                         : bact4qr
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Document ID                     : uuid:497193d6-7b0f-4408-8e62-e4fbc266072d
Instance ID                     : uuid:8e149b42-f5cc-484c-9e73-1472ba0305aa
Page Count                      : 40
Author                          : bact4qr
EXIF Metadata provided by EXIF.tools

Navigation menu