Carrier 48Tfd008 014 Users Manual
48TFF008-012 to the manual a800217e-ac22-4a34-8b65-f3daa3ba0313
2015-01-24
: Carrier Carrier-48Tfd008-014-Users-Manual-310670 carrier-48tfd008-014-users-manual-310670 carrier pdf
Open the PDF directly: View PDF .
Page Count: 48
Download | |
Open PDF In Browser | View PDF |
48TFD008-014 48TFE008-014 48TFF008,012 Single-Package Rooftop Heating/Cooling Units 50 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33 Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1 • ROOF CURB • SLAB MOUNT Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2 Step 3 — Install External Trap for Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2 • POSITIONING Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . 8 Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . 8 Step 7 — Make Electrical Connection . . . . . . . . . . . . 8 • FIELD POWER SUPPLY • FIELD CONTROL WIRING • HEAT ANTICIPATOR SETTINGS Step 8 — Adjust Factory-Installed Options . . . . . . 11 • APOLLO CONTROL • MANUAL OUTDOOR-AIR DAMPER • OPTIONAL DURABLADE ECONOMIZER • OPTIONAL ECONOMI$ER Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 20 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-41 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 42-46 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1 Disconnect gas piping from unit when leak testing at pressure greater than 3.4 kPa (1/2 psig). Pressures greater than 3.4 kPa (1/2 psig) will cause gas valve damage resulting in hazardous condition. If gas valve is ever subjected to pressure greater than 3.4 kPa (1/2 psig), it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 3.4 kPa (1/2 psig) or less, a unit connected to such piping must be isolated by manually closing the gas valve(s). Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. INSTALLATION Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See Fig. 1. Step 1 — Provide Unit Support SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If gas, electric power or control power is to be routed through the curb, attach the accessory thru-the-curb service connection plates to the roof curb in accordance with the accessory installation instructions. Connection plates must be installed before unit is set in roof curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can also result in air leaks and poor unit performance. Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg 1 1-01 Replaces: New Book 1 4 Tab 1a 6a SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 152 mm (6 in.) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. NOTE: Horizontal units may be installed on a roof curb if required. To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 4. The piping for the condensate drain and external trap can be completed after the unit is in place. All units must have an external trap for condensate drainage. Install a trap at least 102-mm (4-in.) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 25 mm (1 in.) per 3 m (10 ft) of run. Do not use a pipe size smaller than the 19-mm (3/4-in.) unit connection. Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical units. Do not connect ductwork to unit. For horizontal applications, fieldsupplied flanges should be attached to horizontal discharge openings and all ductwork secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed –87 Pa (–.35 in. wg) with Durablade economizer, –26 Pa (–.30 in. wg) with EconoMi$er or –112 Pa (–.45 in. wg) without economizer. These units are designed for a minimum heating operation continuous return-air temperature of 10 C (50 F) (dry bulb), or an intermittent operation down to 7 C (45 F) (dry bulb), such as when used with a night set-back thermostat. Step 4 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 5 for additional information. Operating weight is shown in Tables 1A and 1B and Fig. 5. Lifting holes are provided in base rails as shown in Fig. 5 and 6. Refer to rigging instructions on unit. All panels must be in place when rigging. POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 6. Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. Be sure that unit is installed so that snow will not block the combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used. (Copy continued on page 4.) Step 3 — Install External Trap for Condensate Drain — The unit’s 19-mm (3/4-in.) condensate drain connections are located at the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications. When using the standard side drain connection, make sure the plug (Red) in the alternate bottom connection is tight before installing the unit. Fig. 1 — Horizontal Conversion Panels 2 CONNECTOR PKG. ACCY. CRBTMPWR001A00 CRBTMPWR002A00 CRBTMPWR003A00 CRBTMPWR004A00 B 2′-87/16″ [827] C 1′-1015/16″ [583] D ALT DRAIN HOLE GAS 13/4″ [44.5] 3/4″ [19] NPT 1/ ″ 2 [12.7] NPT 3/4″ [19] NPT POWER 4″ [19] NPT 11/4″ [31.7] 3/ 3/4″ [19] NPT 11/4″ [31.7] CONTROL 1/2″ [12.7] 1/ ″ 2 [12.7] ROOF CURB ACCESSORY CRRFCURB003A00 CRRFCURB004A00 “A” UNIT SIZE 48TF 1′-2″ [356] 2′-0″ [610] 008-014 NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels: 1-in. [25] thick polyurethane foam, 13/4 lb density. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: 16-gage steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance 4 ft [1219] on each side. 7. Direction of airflow. 8. Connector packages CRBTMPWR001A00 and 2A00 are for thru-the-curb gas type. Packages CRBTMPWR003A00 and 4A00 are for thruthe-bottom type gas connections. Fig. 2 — Roof Curb Details 3 Although unit is weatherproof, guard against water from higher level runoff and overhangs. Position unit on roof curb so that the following clearances are maintained: 7 mm (1/4-in.) clearance between roof curb and base rails on each side and duct end of unit; 84 mm (35/16-in.) clearance between roof curb and condenser coil end of unit. (See Fig. 2, section C-C.) Locate mechanical draft system flue assembly at least 1219 mm (48 in.) from any opening through which combustion products could enter the building, and at least 1219 mm (48 in.) from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 2.13 m (7 ft) above grade. Flue vent discharge must have a minimum horizontal clearance of 1219 mm (48 in.) from electric and gas meters, gas regulators, and gas relief equipment. Flue gas can deteriorate building materials. Orient unit so that flue gas will not affect building materials. Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute), latest revision, U.S.A. Standards. (Copy continued on page 8.) MAXIMUM ALLOWABLE DIFFERENCE mm (in.) A-B 13 (0.5) B-C 25 (1.0) A-C 25 (1.0) Fig. 3 — Unit Leveling Tolerances DRAIN PLUG NOTE: Drain plug is shown in factory-installed position. Fig. 4 — Condensate Drain Pan NOTES: 1. Dimension in ( ) is in millimeters. 2. Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. 3. Weights include base unit without economizer. See Tables 1A and 1B for economizer weights. UNIT 48TF D/E/F008 D/E/F012 D/E014 All panels must be in place when rigging. Fig. 5 — Rigging Details 4 MAX WEIGHT lb 870 1035 1050 kg 395 469 476 DIMENSIONS ‘‘A’’ ‘‘B’’ ‘‘C’’ in. mm in. mm in. mm 87.38 2219 40.25 1022 41.31 1050 87.38 2219 40.25 1022 49.31 1253 87.38 2219 40.25 1022 49.31 1253 Table 1A — Physical Data (SI) UNIT SIZE 48TF Low Heat (D), Medium Heat (E), High Heat (F) NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Unit Durablade Economizer EconoMi$er Roof Curb* COMPRESSOR TYPE Quantity Oil (ml) REFRIGERANT TYPE Operating Charge (kg) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/m Total Face Area (sq m) CONDENSER FAN Nominal L/s Quantity...Diameter (mm) Motor BkW...r/s EVAPORATOR COIL Rows...Fins/m Total Face Area (sq m) EVAPORATOR FAN Quantity...Size (mm x mm) Type Drive Nominal L/s Motor kW Maximum Continuous BkW Motor Frame Size Fan r/s Range Motor Bearing Type Maximum Allowable r/s Motor Pulley Pitch Diameter Min/Max (mm) Nominal Motor Shaft Diameter (mm) Fan Pulley Pitch Diameter (mm) Nominal Fan Shaft Diameter (mm) Belt, Quantity...Type...Length (mm) Pulley Center Line Distance (mm) Speed Change per Full Turn of Movable Pulley Flange (r/s) Movable Pulley Maximum Full Turns From Closed Position Factory Setting Factory Speed Setting (r/s) Fan Shaft Diameter at Pulley (mm) FURNACE SECTION Rollout Switch Cutout Temp (C) Burner Orifice Diameter (mm) Natural Gas — Std Liquid Propane — Alt Thermostat Heat Anticipator Setting (amps) 400 v Stage 1 Stage 2 Gas Input (kW) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range (C) Manifold Pressure (kPa) Natural Gas — Std Liquid Propane — Alt Field Gas Connection Size (mm) HIGH-PRESSURE SWITCH (kPa) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (kPa) Cutout Reset (Auto.) FREEZE PROTECTION THERMOSTAT Opens (C) Closes (C) OUTDOOR-AIR INLET SCREENS D 008 E 21.5 F 395 20 28 65 Hermetic 2 1479 ea Bhp — BkW — 014 F D E 35.9 469 20 28 65 Hermetic 2 1479 ea R-22 476 20 28 65 Scroll 2 1597 ea 2.10 2.22 3.08 3.49 3.22 3.49 Enhanced Copper Tubes, Aluminum Lanced Fins 1...669 2...669 2...669 1.90 1.92 2.30 Propeller Type 2880 3050 3050 2...559 2...559 2...559 .19...15.5 .19...15.5 .19...15.5 Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device 3...590 3...590 4...590 0.74 0.93 1.03 Centrifugal Type 1...381 x 381 1...381 x 381 1...381 x 381 Belt Belt Belt 1230 1700 1980 1.12 1.50 2.24 1.79 1.79 2.76 56 56 56 8.2-11.7 9.5-13.0 12.0-15.0 Ball Ball Ball 26.7 26.7 26.7 61/86 71/97 102/127 16 16 22 178 178 203 25 25 25 1...A...1245 1...A...1245 1...A...1346 425-489 403-445 403-445 .70 .70 .60 5 5 8.2 25 5 5 9.5 25 90.6 .14 .14 21.1 31.4 5 5 12.0 25 90.6 3.05 2.44 .14 .20 39.8 59.8 90.6 3.05 2.44 3.05 2.44 31.9 50.4 4-21 7-24 19 19 –6-10 .14 .20 31.9 50.4 80 2-18 7-24 2-18 .14 .20 39.8 59.8 80 7-24 13 8.3 8.3 19 19 19 8.3 8.3 19 3103 ± 345 3.28 2.59 3.05 2.44 3.28 2.59 .14 .20 43.9 65.6 39.8 59.8 43.9 65.6 80 4-21 8.3 8.3 19 3448 ± 345 2951 2206 48 ± 21 152 ± 48 Quantity...Size (mm) RETURN-AIR FILTERS Quantity...Size (mm) 012 E 29.2 D 4...406 x 508 x 51 LEGEND Brake Horsepower Fan Input Watts x Motor Efficiency –1 ± 3 7±3 Cleanable 1...508 x 635 x 25 1...406 x 635 x 25 Throwaway 4...508 x 508 x 51 4...508 x 508 x 51 *Weight of 356 mm (14-in.) roof curb. NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in the liquid line. 5 Table 1B — Physical Data (English) UNIT SIZE 48TF Low Heat (D), Medium Heat (E), High Heat (F) NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Durablade Economizer EconoMi$er Roof Curb* COMPRESSOR TYPE Quantity Oil (oz) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor BkW...Rpm EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Maximum Continuous Bhp Motor Frame Size Fan Rpm Range Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Min/Max (in.) Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type...Length (in.) Pulley Center Line Distance (in.) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns From Closed Position Factory Setting Factory Speed Setting (rpm) Fan Shaft Diameter at Pulley (in.) FURNACE SECTION Rollout Switch Cutout Temp (F) Burner Orifice Diameter (in. ...drill size) Natural Gas — Std Liquid Propane — Alt Thermostat Heat Anticipator Setting (amps) 400 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 ‘ Efficiency (Steady State) (%) Temperature Rise Range (F) Manifold Pressure (in. wg) Natural Gas — Std Liquid Propane — Alt Field Gas Connection Size (in.) HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (psig) Cutout Reset (Auto.) FREEZE PROTECTION THERMOSTAT Opens (F) Closes (F) OUTDOOR-AIR INLET SCREENS D 008 E 6.1 F 870 44 62 143 Hermetic 2 50 ea Bhp — BkW — 014 F D E 10.2 1035 44 62 143 Hermetic 2 50 ea R-22 1050 44 62 143 Scroll 2 54 ea 4-10 4-11 6-13 7-11 7- 2 7- 8 Enhanced Copper Tubes, Aluminum Lanced Fins 1...17 2...17 2...17 20.50 20.50 25.00 Propeller Type 6100 6500 6500 2...22 2...22 2...22 1/4...930 1/4...930 1/4...930 Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device 3...15 3...15 4...15 8.0 10.0 11.1 Centrifugal Type 1...15 x 15 1...15 x 15 1...15 x 15 Belt Belt Belt 2600 3500 4200 1 2 3 1 /2 2.40 2.40 3.70 56 56 56 492-700 571-779 717-900 Ball Ball Ball 1600 1600 1600 2.4/3.4 2.8/3.8 4.0/5.0 5/8 5/8 7/8 7.0 7.0 8.0 — — — 1...A...49 1...A...49 1...A...53 16.75-19.25 15.85-17.50 15.85-17.50 41 41 36 5 5 492 1 5 5 571 1 195 .14 .14 72,000 107,000 20-50 .14 .20 109,000 172,000 80 35-65 1/2 3.5 3.5 3/4 5 5 717 1 195 .120...31 .096...41 .14 .20 136,000 204,000 45-75 .120...31 .096...41 .120...31 .096...41 109,000 172,000 .14 .20 136,000 204,000 80 45-75 35-65 3.5 3.5 3/4 3/4 450 ± 50 195 .129...30 .102...38 .120...31 .096...41 .129...30 .102...38 .14 .20 150,000 224,000 136,000 204,000 150,000 224,000 80 40-70 45-75 40-70 3.5 3.5 3/4 500 ± 50 428 320 7±3 22 ± 7 Quantity...Size (in.) RETURN-AIR FILTERS Quantity...Size (in.) 012 E 8.3 D 4...16 x 20 x 2 LEGEND Brake Horsepower Fan Input Watts x Motor Efficiency 30 ± 5 45 ± 5 Cleanable 1...20 x 25 x 1 1...16 x 25 x 1 Throwaway 4...20 x 20 x 2 4...20 x 20 x 2 *Weight of 356 mm (14-in.) roof curb. NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in the liquid line. 6 STANDARD UNIT WEIGHT UNIT 48TF D/E/F008 D/E/F012 D/E014 Lb 870 1035 1050 Kg 395 469 476 DURABLADE ECONOMIZER WEIGHT Lb Kg 44 20 44 20 44 20 ECONOMI$ER CORNER CORNER CORNER CORNER WEIGHT WEIGHT (A) WEIGHT (B) WEIGHT (C) WEIGHT (D) Lb 62 62 62 Kg 28 28 28 NOTES: 1. Dimensions in [ ] are in millimeters. 2. 3. Center of gravity. Direction of airflow. 4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all ductwork should be attached to the flanges. 5. Minimum clearance (local codes or jurisdiction may prevail): a. Between unit, flue side and combustible surfaces, 36 in. [914]. b. Bottom of unit to combustible surfaces (when not using curb), 1 in. [25]. Bottom of base rail to combustible surfaces (when not using curb) 0 inches. c. Condenser coil, for proper airflow, 36 in. [914] one side, 12 in. [304] the other. The side getting the greater clearance is optional. d. Overhead, 60 in. [1624] to assure proper condenser fan operation. e. Between units, control box side, 42 in. [1067] per NEC (National Electrical Code). f. Between unit and ungrounded surfaces, control box side, 36 in. [914] per NEC. g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. [1067] per NEC. h. Horizontal supply and return end, 0 inches. 6. With the exception of the clearance for the condenser coil and combustion side as stated in notes 5a, b and c, a removable fence or barricade requires no clearance. 7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material if set on base rail. 8. The vertical center of gravity is 1′-7″ [483] for 008, 1′-11″ [584] for 012 and 014 up from the bottom of the base rail. Lb 189 225 228 Kg 86 102 103 Lb 161 192 195 Kg 73 87 88 Lb 239 285 289 Kg 109 129 131 Lb 280 333 338 Kg 127 151 153 “H” F G 13/8″ Dia [35] Field Power Supply Hole 21/2″ Dia [64] Power Supply Knockout 13/4″ Dia [44] Charging Port Hole 7/ ″ Dia [22] Field Control Wiring Hole 8 3/ ″ [19] - 14 NPT Condensate Drain 4 1/ ″ [13] - 14 NPT Gas Connection 48TFD008 2 3/ ″ [19] - 14 NPT Gas Connection 48TFE,F008 4 48TFD,E012 & 014, 48TJF012 2″″ Dia [51] Power Supply Knockout Fig. 6 — Base Unit Dimensions 7 “K” ft-in. [mm] ft-in. [mm] ft-in. 1-27/8 [ 378] 3-55/16 [1050] 2-911/16 2-57/8 [ 759] 4-15/16 [1253] 3-03/8 1-27/8 [ 378] 4-15/16 [1253] 3-03/8 CONNECTION SIZES A B C D E “J” “L” [mm] ft-in. [856] 2- 27/16 [924] 2-107/16 [924] 2-107/16 [mm] [672] [875] [875] BOTTOM POWER CHART, THESE HOLES REQUIRED FOR USE WITH ACCESSORY PACKAGES — CRBTMPWR002A00 (POWER AND CONTROL) AND CRBTMPWR004A00 (POWER, CONTROL, AND GAS) THREADED CONDUIT SIZE 1/ ″ [12.7] 2 1 1 /4″ [31.7] 3/ ″ [19] FPT 4 WIRE USE 24 V Power Gas REQURED HOLE SIZES (MAX.) 7/ ″ [22.2] 8 3 1 /4″ [44.4] 15/8″ [41.3] Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood and screen in location shown in Fig. 7. Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes. For natural gas applications, gas pressure at unit gas connection must not be less than 13.5 kPa (4.0 in. wg) (17.0 kPa [5.0 in. wg] in high heat units) or greater than 44.0 kPa (13.0 in. wg) while unit is operating. For liquid propane applications, the gas pressure must not be less than 17.0 kPa (5.0 in. wg) or greater than 44.0 kPa (13.0 in. wg) at the unit connection. Size gas supply piping for 1.7 kPa (0.5 in. wg) maximum pressure drop. Do not use supply pipe smaller than unit gas connection. NOTE: When installing gas piping to gas valve inlet, use properly sized back-up wrench on inlet flange flats. Support gas piping as shown in the table in Fig. 8. For example, a 19 mm (3/4-in.) gas pipe must have one fieldfabricated support beam every 2.4 m (8 ft). See Fig. 8 for typical pipe guide and locations of external manual gas shutoff valve. Fig. 7 — Flue Hood Details BASE UNIT Step 7 — Make Electrical Connections X 228 mm (9") MINIMUM CLEARANCE FOR PANELREMOVAL GAS REGULATOR* MANUAL GAS SHUTOFF VALVE* 1219 mm (48") MINIMUM DRIP LEG PER NFGC* BASE RAIL Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition (U.S.A. Standards), and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others. ROOF CURB FIELD-FABRICATED SUPPORT* FROM GAS METER LEGEND NFGC — National Fuel Gas Code (U.S.A. Standard) *Field supplied. NOTE: Follow all local codes. SPACING OF SUPPORTS STEEL PIPE NOMINAL DIAMETER mm (in.) 13 (1/2) 19 or 25 (3/4 or 1) 32 or larger (11/4 or larger) FIELD POWER SUPPLY — All units are factory wired for the voltage shown on the nameplate. Refer to unit label diagram for additional information. Pigtails are provided for field service. When installing units, provide a disconnect per local codes. Use copper conductors only when splice connectors are used. All field wiring must comply with local requirements. Install conduit through side panel openings indicated in Fig. 6. Route power lines through connector to terminal connections as shown in Fig. 9. Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 2, Note 2 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. NOTE: If field-installed thru-the-bottom connections are used, refer to the accessory installation instructions for power wiring. Refer to Fig. 6 for drilling holes in basepan. X DIMENSION m (ft) 1.8 (6) 2.4 (8) 3.0 (10) Fig. 8 — Gas Piping Guide (With Accessory Thru-the-Curb Service Connections) FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions. NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 15 to 23 m (51 to 75 ft), use no. 16 AWG insulated wire (35 C minimum). For over 23 m (75 ft), use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. Refer to Table 3 for wire conversions. 8 Table 2 — Electrical Data UNIT 48TF 008 012 014 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — NOMINAL VOLTAGE (50 Hz) 400 (3 phase) 400 (3 phase) 400 (3 phase) VOLTAGE RANGE Min Max COMPR (ea) RLA LRA OFM (ea) FLA IFM MINIMUM UNIT DISCONNECT FLA LRA POWER SUPPLY FLA MCA MOCP* 360 440 6.4 42.0 0.3 2.6 17.6 20 18 108 360 440 8.9 52.0 0.3 2.6 23.2 30 24 128 360 440 10.4 73.0 0.7 5.4 29.4 35 31 192 LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code (U.S.A.) Outdoor (Condenser) Fan Motor Rated Load Amps Example: Supply voltage is 400-3-50. AB = 393 v BC = 403 v AC = 396 v Average Voltage = = *Fuse or HACR circuit breaker. 393 + 403 + 396 3 1192 3 = 397 Determine maximum deviation from average voltage. (AB) 397 – 393 = 4 v (BC) 403 – 397 = 6 v (AC) 397 – 396 = 1 v Maximum deviation is 6 v. Determine percent of voltage imbalance. 6 % Voltage Imbalance = 100 x 397 NOTES: 1. In compliance with NEC requirements (U.S.A. Standard) for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage = 1.5% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. Table 3 — American/European Wire Conversions Route thermostat cable or equivalent single leads of colored wire from thermostat subbase terminals to low-voltage connections on unit (shown in Fig. 10) as described in Steps 1-4 below. 1. If unit is mounted on roof curb and accessory thru-thecurb service plate connection is used, route wire through connection plate. 2. Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 6). 3. Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 11. The raceway provides the UL-required (Underwriters’ Laboratories) clearance between highand low-voltage wiring. 4. Connect thermostat wires to screw terminals on lowvoltage connection board. HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .20 amp for secondstage heating, except for 008 low heat. Set both first and second stage heat anticipator settings for 008 at .14 amp. AMERICAN Industry Standard Size 18 AWG 16 AWG 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 400 kcmil 500 kcmil 600 kcmil American Conversion Size (mm2) 0.82 1.30 2.08 3.30 5.25 6.36 13.29 21.14 26.65 33.61 42.39 53.49 67.42 85.00 107.19 126.64 151.97 177.90 202.63 253.29 303.95 LEGEND AWG — American Wire Gage kcmil — Thousand Circular Mils 9 EUROPEAN Industry Standard Size (mm2) 1.0 1.5 2.5 4.0 6.0 10.0 16.0 25.0 — 35.0 50.0 — 70.0 95.0 120.0 150.0 — 185.0 240.0 300.0 — C IFC NEC LEGEND — Contactor — Indoor (Evaporator) Fan Contactor — National Electrical Code (U.S.A. Standard) Splice Connection (Factory Supplied) Equipment Ground Field Wiring Factory Wiring Fig. 9 — Power Wiring Connections UNIT LOW VOLTAGE CONNECTION BOARD INTEGRATED GAS UNIT CONTROLLER (IGC) LEGEND AHA — Adjustable Heat Anticipator CC — Cooling Compensator Field Wiring Factory Wiring Fig. 10 — Low-Voltage Connections RACEWAY COMPRESSOR NO. 2 COMPRESSOR NO.1 Fig. 11 — Field Control Wiring Raceway and Compressor Location 10 Step 8 — Adjust Factory-Installed Options 9. Remove and save screws currently on sides of hood. Insert screens. Secure screens to hood using the screws. See Fig. 15. APOLLO CONTROL — The optional Apollo control is used to actively monitor all modes of operation as well as indoor (evaporator) fan status, filter status, and indoor-air quality. The Apollo control is designed to work with Carrier TEMP and VVT® systems. The thermostat must be wired to the Apollo control before starting the unit. Refer to the Apollo control installation instructions for information on installing the thermostat. See Fig. 12 for Apollo location. MANUAL OUTDOOR-AIR DAMPER — The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping. Assembly: 1. Determine quantity of ventilation required for building. Record amount for use in Step 8. 2. Remove and save evaporator coil access panel and screws. See Fig. 13. 3. Separate hood and screen from basepan by removing the screws and brackets securing them. Save all screws and discard brackets. 4. Replace evaporator coil access panel using screws from Step 2. 5. Place hood on front of evaporator coil access panel. See Fig. 14 for hood details. Secure top of hood with the screws removed in Step 3. See Fig. 15. 6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper. Remove and save 2 manual outdoor-air adjustment screws (one on each side of damper blade). 7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 14 and 15. Secure hood with 6 side screws from Step 6. 8. Adjust minimum position setting of the damper blade by adjusting the 2 manual outdoor-air adjustment screws on the front of the damper blade. See Fig. 13. Slide blade vertically until it is in the appropriate position determined by Fig. 16. Tighten screws. WIRING TO THERMOSTAT APOLLO CONTROL Fig. 13 — Damper Panel with Manual Outdoor-Air Damper Installed CONTROL WIRING Fig. 14 — Outdoor-Air Hood Details Fig. 12 — Apollo Control Factory-Installed in Typical Unit Fig. 15 — Damper with Hood Attached 11 50 0 0.6 m ) ) 1 (5 2" 0.4 m m PE N m m )O 100 0.8 3" 6 (7 m m) 1" (2 5 150 NEGATIVE PRESSURE (in. wg) NEGATIVE PRESSURE (Pa) 200 c. Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 22. 7. Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 20. 8. If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum position setting for required airflow. See Fig. 23. Adjust minimum position setting by loosening the screws on the position setting bracket. See Fig. 24. Slide bracket until the top screw is in the position determined by Fig. 23. Tighten screws. 9. Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips provided. See Fig. 25. Make sure OAT terminals are positioned up. 10. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged. 11. Fasten hood top and side plate assembly to outdoor-air opening panel with screws provided. 12. Place knob supplied with economizer on OAT. See Fig. 25. Set OAT for 1.7° C (3° F) below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 25. 13. Connect OAT per Fig. 26. 14. Slide outdoor-air inlet screens into screen track on hood side plate. While holding screens in place, fasten screen retainer to hood using screws provided. NOTE: Refer to Fig. 27 for Durablade economizer barometric relief damper characteristics. 1.0 250 2m 11 "( 4.4 0.2 0 2 0 100 6 8 4 OUTDOOR AIRFLOW (cfm x 100) 300 200 400 OUTDOOR AIRFLOW (L/s) 10 12 500 Fig. 16 — Position Setting OPTIONAL DURABLADE ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate. Assembly 1. Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 8. 2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer and outdoor-air damper hood package from filter section. 3. Assemble outdoor-air hood top and side plates as shown in Fig. 18. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time. 4. On 012 and 014 units, install vertical discharge block-off plate on right side over return air duct opening. See Fig. 19. 5. a. Slide economizer into unit and secure with screws. See Fig. 20. NOTE: Be sure to engage rear economizer flange under tabs at rear of vertical return-air opening. b. Remove screw and discard from barometric relief damper. See Fig. 20. 6. To convert to horizontal discharge application: a. Rotate the economizer 90 degrees until the economizer motor faces the condenser section (see Fig. 21). b. Rotate the barometric relief damper hinge 90 degrees. Barometric relief damper should open vertically to operate properly. OUTDOOR-AIR OPENING PANEL FILTER ACCESS PANEL Fig. 17 — Access Panel Locations 12 ECONOMIZER CONTROL BOARD ECONOMIZER PLUG ECONOMIZER MOTOR TOP SCREW SHIPPING SCREW Fig. 20 — Durablade Economizer Installed in Unit ECONOMIZER CONTROL BOARD ECONOMIZER MOTOR Fig. 18 — Outdoor-Air Hood Details POSITION SETTING BRACKET Fig. 21 — Horizontal Durablade Economizer Installation (90 Degree Rotation) Fig. 19 — Vertical Discharge Block-Off Plate (48TF012, 014 Units Only) BLOCK-OFF PLATE Fig. 22 — Horizontal Discharge Block-Off Plate 13 Example: Given — Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . . 25 Pa (0.1 in. wg) Outdoor Airflow . . .. . . . . . . . . . . . . . . . . . . . . . . . 520 L/s (1100 cfm) Determine — Setting = 150 mm (6 in.) OAT (TERMINALS ARE UP) TOP Fig. 23 — Durablade Economizer Damper Minimum Position Setting UNIT 0 OUTSIDE AIR SCREEN 2 1 ENTHALPY CONTROL REV. B B TR C 24VAC 2 TR1 1 3 mA MIN. AT 11 VDC B A ENTHALPY CONTROL 3 D CW–SETPOINTS–CCW 3 4 5 198818A RUSH AT 24VAC CONTACTS SHOWN IN HIGH ENTHALPY OR UNPOWERED STATE °F CONTACT RATINGS: 1.5A RUN, 3.5A IN OUTDOOR TEMP. % 90 H DAMPER U 70 CLOSED M I 60 DAMPER D OPEN I 30 T Y 10 50 55 60 65 70 75 80 85 6 SO D TR S 4 2 5 3 P1 T1 1 P T 7 C MINIMUM POSITION OPEN HOOD 97-3672 9 8 REV. Fig. 25 — Outdoor-Air Thermostat/ Enthalpy Control Installation Fig. 24 — Durablade Economizer Minimum Position Damper Setting 14 CONTROLLER ECONOMI$ER PLUG ACTUATOR 0.70 150 0.60 125 100 75 PRESSURE DROP (in. wg) PRESSURE DROP (Pa) Fig. 26 — Wiring Connections for Outdoor-Air Thermostat 175 GEAR-DRIVEN DAMPER OUTDOOR AIR TEMPERATURE SENSOR 0.50 BAROMETRIC RELIEF DAMPERS 0.40 Fig. 28 — EconoMi$er Component Locations 0.30 50 0.20 25 0.10 0 0.00 200 0 100 400 200 600 CFM 300 L/s 800 1000 400 1200 500 570 Fig. 27 — Durablade Economizer Barometric Relief Damper Characteristics OPTIONAL ECONOMI$ER — See Fig. 28 for EconoMi$er component locations. 1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 29. NOTE: If installing an optional Power Exhaust Assembly, refer to the EconoMi$er Power Exhaust Installation Instructions, then proceed to Step 6. Controller should be mounted in vertical position as shown in Fig. 28. 2. To assemble the hood assembly remove the EconoMi$er hood from its packaging. Locate the outdoor air opening panel. See Fig. 30. 3. Install the 19 mm x 19 mm (3/4 x 3/4-in.) seal strip on the exhaust air hood top panel. Install the 3 mm x 22 mm (1/8 x 7/8-in.) seal strip on the exhaust air hood side panels and bottom brackets. Assemble the exhaust air hood to the outdoor air opening panel as shown in Fig. 30, using the screws provided. Do not attach hood assembly to unit at this time. 4. Install the 3 mm x 22 mm (1/8 x 7/8-in. seal strip on the outdoor air hood top and side panels. Assemble the outdoor air hood to the outdoor air opening panel as shown in Fig. 31, using the screws provided. Do not attach completed hood (Fig. 32) assembly to the unit at this time. OUTDOOR-AIR OPENING PANEL FILTER ACCESS PANEL Fig. 29 — Typical Access Panel Locations OUTDOOR AIR OPENING PANEL EXHAUST AIR HOOD TOP SCREEN RETAINER SEAL STRIP EXHAUST AIR HOOD SIDES EXHAUST AIR SCREEN EXHAUST AIR BOTTOM BRACKET Fig. 30 — Exhaust Air Hood Assembly 15 OUTDOOR AIR OPENING PANEL SEAL STRIP OUTDOOR AIR HOOD TOP BLOWER SCREEN RETAINER SEAL STRIP OUTDOOR AIR INLET SCREENS INSTALL RETURN AIR BLOCK-OFF PLATE ASSEMBLED EXHAUST HOOD FILTER OUTDOOR AIR HOOD SIDES Fig. 31 — Outdoor Air Hood Assembly REMOVE FACTORY INSTALLED BLOCK-OFF PLATE (008 AND 012 UNITS ONLY) Fig. 33 — Return Air Block-Off Plate Installation (48TF014 Units Only) UNIT FILTER RACK ECONOMIZER CLIP HVAC UNIT ECONOMIZER UNIT BASE Fig. 32 — Completed Hood Assembly ECONOMIZER REAR FLANGE Fig. 34 — Rear EconoMi$er Flange Installation 5. Slide the outdoor air inlet screens into the screen track on the hood side panels. While holding the screens in place, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen. Do not attach hood assembly to unit at this time. 6. For 48TF014 units, install the return air block-off plate over the return air duct opening. See Fig. 33. NOTE: For 48TF008 and 012 units, remove the factoryinstalled block-off plate. See Fig. 33. 7. Slide the EconoMi$er assembly into the rooftop unit. See Fig. 34 and 35. NOTE: Be sure to engage rear EconoMi$er flange under tabs in return air opening of the unit base. See Fig. 34. 8. Install the outdoor air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 35. 9. Remove and store the 12-pin jumper plug from the unit wiring harness located in the upper left corner and insert the EconoMi$er plug into the unit wiring harness. Refer to wiring diagram Fig. 36 and 37. Also refer to Fig. 38 if installing an accessory power exhaust. 10. Install the complete hood assembly on the unit and secure using the screws provided. 11. Remove the indoor fan motor access panel. 12. Mount the supply air temperature sensor to the lower left portion of the indoor blower housing with the two (2) screws provided (see Fig. 39). Connect the violet and pink wires to the corresponding connections on the supply air temperature sensor. Replace the indoor fan motor access panel. WIRING HARNESS OUTDOOR AIR BLOCK-OFF PLATE Fig. 35 — EconoMi$er Installed in 48TF008 and 012 Units 16 OAT LEGEND — Outdoor-Air Thermostat Fig. 36 — EconoMi$er Wiring BROWN ECONOMI$ER CONTROLLER VIOLET OAT WHITE RED COM OAH +15 V RAT COM RAH +15 V CO2 (+) CO2 COM DAT COM REM POT COM LED COM BROWN VIOLET WHITE RED TEMP TEMP COM OUT PWR OUTDOOR AIR SENSOR TEMP TEMP COM OUT PWR RETURN AIR SENSOR CO2 SENSOR 24 V+ COM VAC SUPPLY AIR TEMPERATURE SENSOR PINK TEMP VIOLET TEMP Fig. 37 — EconoMi$er Sensor Wiring 17 TO FUSED DISCONNECT HT01AH850 (460 VAC) RED YEL BLU GRAY H1 H3 H2 H4 X4 X2 X3 X1 SECONDARY 230VAC FIELD SUPPLIED WIRING BLACK BLACK LT. BLUE BROWN FAN 1 C1 GREEN/ YELLOW 4-PIN CONNECTOR PLUG 2 x 4 IN. HANDY BOX BLACK L1 1 BLUE L2 2 GREEN GND 3 4 3 6 9 2 5 8 1 4 7 B BLACK R1 24 VAC A BLUE L1 1 L2 2 GND 3 4 230 VAC 1 PHASE 3-PIN CONNECTOR PLUG ORANGE 1 YELLOW 2 BROWN BLACK BLACK BLUE LT. BLUE GREEN BROWN FAN 2 3 6 9 2 5 8 1 4 7 C1 GREEN/ YELLOW BLUE Fig. 38 — Wiring Diagram for Power Exhaust System SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION SUPPLY AIR TEMPERATURE SENSOR Fig. 39 — Supply Air Sensor Placement 18 B BLACK R2 24 VAC A 3 4. Calculate the minimum airflow across the EconoMi$er. a. Calculate % of outside air using the following formula. % Outdoor air through EconoMi$er Mixture Temp – Return Air Temp % Outdoor air = Outdoor Temp – Return Air Temp CO2 Control Set Up — If a CO2 sensor is not being used, proceed to the next section. If a CO2 sensor is being used, perform the following: 1. Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater amount of outdoor air to enter. The range is 800 to 1,400 ppm. 2. Locate the CO2 SP (PPM) potentiometer and adjust to the desired set point. See Fig. 40. Mechanical Cooling Lockout — Determine the outdoor-air temperature at which you want the mechanical cooling (compressors) to be disabled. Locate the mechanical cooling lockout (MECH CLG LOCKOUT) potentiometer. To disable this feature, turn the potentiometer counterclockwise (CCW) to the OFF position. Otherwise, set the value between –12 and 15 C (10 and 60 F). Mechanical cooling will not operate when the outdoor air temperature is below this value. See Fig. 40. Dry Bulb Changeover Set Up — Determine the dry bulb changeover set point from Table 4. The settings are A, B, C and D. Locate the ECON SP potentiometer and set the dry bulb changeover set point. See Fig. 40. When the OAT is above this set point, the damper is limited to minimum position setting. b. Multiply total CFM by percentage outdoor air, this gives outdoor air volume in CFM. 5. Turn on base unit power. NOTE: The EconoMi$er begins operation three minutes after power up. Personal Injury Hazard. Avoid possible injury by keeping fingers away from damper blades. 6. See Fig. 41 for barometric relief damper characteristics. Table 4 — Changeover Set Points SETTINGS Dry Bulb C (°F) Single Enthalpy* KJ/Kg (Btu/lb) Differential Temperature* C (°F, Not Adjustable) Differential Enthalpy* KJ/Kg (Btu/lb, Not Adjustable) A 23 (73) 63 (27) 1.1 (2) 2 (1) B 21 (69) 58 (25) 1.1 (2) 2 (1) C 19 (66) 56 (24) 1.1 (2) 2 (1) D 17 (63) 51 (22) 1.1 (2) 2 (1) Fig. 40 — EconoMi$er Control Adjustment Potentiometers (Factory Settings) If a potentiometer fails, its setting will default to the values in Table 5. PRESSURE DROP (Pa) 125 Table 5 — Default Potentiometer Settings POTENTIOMETER CO2 SP (PPM) MECH CLG LOCKOUT, C (F) ECON SP MIN POS (%) DEFAULT SETTING 1,000 8.3 (47) D 20 Ventilation Air (Minimum Position Set Up) — If ventilation air is not required, proceed to Step 5. If ventilation air is required, perform the following: 1. The indoor fan must be on to set the ventilation air. Either put the thermostat in the continuous fan mode or jumper the R and G terminals at the rooftop unit connection board. 2. Locate the minimum position (MIN POS) potentiometer. Turn the potentiometer full CCW to fully close the outdoor air dampers. Turn the potentiometer gradually clockwise (CW) to the desired position. See Fig. 40. 3. Replace the filter access panel. See Fig. 21. Ensure the filter access panel slides along the tracks and is securely engaged. 100 75 50 25 0 STATIC PRESSURE (IN.WG) *Field-installed accessory. 0.5 0.4 0.3 0.2 0.1 0 0 400 0 200 800 1200 1600 2000 FLOW (CUBIC FEET/MINUTE) 400 600 800 1000 2400 1200 FLOW (L/s) Fig. 41 — EconoMi$er Barometric Relief Capacity 19 Step 9 — Adjust Evaporator-Fan Speed — Adjust evaporator-fan speed to meet jobsite requirement. Table 6 shows motor performance. Tables 7 and 8 show fan rpm at motor pulley settings, Table 9 shows motor efficiencies and Tables 10 and 11 give accessory static pressure drops. Refer to Tables 12-23 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Table 1A or 1B. To change fan speed: 1. Shut off unit power supply and install lockout tag. 2. Loosen belt by loosening fan motor mounting plate nuts (see Fig. 42 and 43). 3. Loosen movable pulley flange setscrew (see Fig. 44). 4. Screw movable flange toward fixed flange to increase fan speed and away from fixed flange to decrease fan speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1A or 1B. 5. Set movable flange at nearest flat of pulley hub and tighten setscrew (see Table 1A or 1B for speed change for each full turn of pulley flange). To align fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mounting plate. To adjust belt tension (see Fig. 42 and 43): 1. Loosen fan motor mounting nuts. 2. Size 008 — Slide motor mounting plate away from fan scroll for proper belt tension (13 mm [1/2-in.] deflection with 3.6 to 4.5 kg [8 to 10 lbs] of force) and tighten mounting nuts. See Fig. 42. Sizes 012,014 — Slide motor mounting plate downward to tighten belt tension (13 mm [1/2-in.] deflection with 2.3 to 4.5 kg [5 to 10 lbs] of force) and tighten mounting nuts. See Fig. 43. 3. Adjust bolt and nut on mounting plate to secure motor in fixed position. See Fig. 44. Realign fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mounting plate. MOTOR MOUNTING PLATE NUTS Fig. 42 — Typical Belt-Drive Motor Mounting for Size 008 Fig. 43 — Typical Belt-Drive Motor Mounting for Sizes 012,014 Fig. 44 — Evaporator-Fan Pulley Adjustment Table 6 — Evaporator-Fan Motor Performance UNIT 48TF UNIT RATED VOLTAGE 008 012 014 400 400 400 MAXIMUM ACCEPTABLE CONTINUOUS BkW* 2.76 2.76 2.76 MAXIMUM ACCEPTABLE CONTINUOUS BHP* 2.90 3.70 3.70 LEGEND BHP — Brake Horsepower BkW — kW x Motor Efficiency MAXIMUM ACCEPTABLE OPERATING WATTS 2615 3313 3313 MAXIMUM AMP DRAW 3.6 5.0 5.0 *Extensive motor and electrical testing on these units ensures that the full range of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 20 Table 7 — Fan R/s at Motor Pulley Settings (SI) UNIT 48TF 0 1/ 008 012 014 11.70 13.00 15.00 11.35 12.65 14.70 2 1 11/2 11.00 12.30 14.40 10.65 11.95 14.10 MOTOR PULLEY TURNS OPEN 2 21/2 3 10.30 11.60 13.80 9.95 11.25 13.50 9.60 10.90 13.20 31/2 4 41/2 5 9.25 10.55 12.90 8.90 10.20 12.60 8.55 9.85 12.30 8.20 9.50 12.00 31/2 4 41/2 5 555 634 771 534 613 753 513 592 735 492 571 717 Table 8 — Fan Rpm at Motor Pulley Settings (English) UNIT 48TF 0 1/ 008 012 014 700 779 900 681 760 883 2 1 11/2 660 739 865 639 718 843 MOTOR PULLEY TURNS OPEN 2 21/2 3 618 697 825 597 676 807 576 655 789 Table 9 — Evaporator-Fan Motor Efficiency MOTOR 48TF D/E/F008 D/E/F012 D/E014 EFFICIENCY (%) 80 80 85 NOTE: Convert watts to bhp using the following formula: bhp = watts input x motor efficiency 746 Table 10 — Accessory/FIOP Static Pressure Drop (Pa) — 48TF008-014 UNIT 48TF RATED VOLTAGE L/s All 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 008-014 DURABLADE ECONOMIZER PRESSURE DROP 5 6 7 8 9 10 11 12 13 14 15 16 17 ECONOMI$ER — — — 31 35 41 50 59 67 75 84 90 97 FIOP — Factory-Installed Option Table 11 — Accessory/FIOP Static Pressure Drop (in. wg) — 48TF008-014 UNIT 48TF RATED VOLTAGE CFM All 2200 2500 3000 3500 4000 4500 5000 5500 6000 008-014 DURABLADE ECONOMIZER PRESSURE DROP .02 .02 .03 .04 .05 .06 .07 .08 .09 FIOP — Factory-Installed Option 21 ECONOMI$ER .07 .09 .13 .18 .23 .30 .36 — — Table 12 — Fan Performance, 48TF008 — Vertical Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1150 1200 1275 1300 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 100 50 150 200 R/s BkW R/s BkW R/s BkW R/s BkW 8.8 9.0 9.3 9.6 9.9 10.1 10.4 10.7 11.0 11.3 11.5 11.8 12.2 12.4 12.8 0.45 0.47 0.53 0.58 0.63 0.68 0.78 0.81 0.90 0.99 1.06 1.16 1.24 1.35 1.47 10.1 10.3 10.5 10.8 11.1 11.3 11.5 11.8 12.0 12.4 12.6 12.9 13.2 13.4 13.7 0.62 0.65 0.70 0.78 0.85 0.86 0.96 1.06 1.10 1.22 1.30 1.38 1.49 1.60 1.70 11.2 11.4 11.6 11.9 12.1 12.3 12.6 12.8 13.0 13.3 13.6 13.8 14.1 14.4 14.6 0.79 0.82 0.89 0.96 1.02 1.09 1.18 1.25 1.35 1.43 1.54 1.65 1.75 1.84 1.97 12.2 12.4 12.6 12.8 13.1 13.2 13.5 13.7 14.0 14.2 14.4 14.7 14.9 15.1 15.4 0.96 1.02 1.08 1.17 1.26 1.29 1.38 1.48 1.56 1.67 1.78 1.88 2.00 2.10 2.24 EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1150 1200 1275 1300 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 300 250 350 400 R/s BkW R/s BkW R/s BkW R/s BkW 13.2 13.3 13.5 13.8 14.0 14.1 14.4 14.5 14.8 15.0 15.2 15.5 15.7 15.9 16.2 1.15 1.21 1.28 1.37 1.45 1.53 1.61 1.72 1.80 1.92 2.01 2.14 2.24 2.37 2.51 14.1 14.1 14.3 14.6 14.7 14.9 15.2 15.4 15.6 15.8 16.0 16.2 16.4 16.7 16.9 1.39 1.41 1.46 1.55 1.65 1.73 1.84 1.95 2.07 2.15 2.27 2.41 2.52 2.66 2.78 15.1 15.2 15.3 15.2 15.5 15.6 15.8 16.1 16.3 16.6 16.7 16.9 17.2 17.4 — 1.73 1.76 1.76 1.72 1.84 1.88 2.04 2.15 2.29 2.42 2.56 2.65 2.82 2.92 — 15.8 15.9 16.1 16.3 16.5 16.7 16.4 16.5 17.0 17.2 17.5 17.6 — — — 1.96 2.00 2.17 2.17 2.10 2.10 2.18 2.34 2.49 2.66 2.80 2.92 — — — LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 22 Table 13 — Fan Performance, 48TF012 — Vertical Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2250 2300 2400 2450 100 50 150 250 200 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 9.8 10.0 10.3 10.6 10.9 11.1 11.4 11.7 12.0 12.2 12.5 12.8 13.1 13.3 13.6 13.9 14.2 14.5 14.8 0.55 0.60 0.66 0.72 0.78 0.86 0.93 1.00 1.08 1.16 1.25 1.34 1.44 1.53 1.64 1.75 1.86 1.98 2.10 10.9 11.2 11.4 11.7 12.0 12.2 12.5 12.7 12.9 13.2 13.4 13.7 13.9 14.2 14.5 14.7 15.0 15.3 15.6 0.67 0.74 0.80 0.86 0.93 1.00 1.08 1.15 1.23 1.31 1.40 1.50 1.60 1.71 1.82 1.94 2.06 2.19 2.32 12.0 12.2 12.4 12.6 12.8 13.1 13.3 13.6 13.8 14.1 14.3 14.6 14.9 15.1 15.3 15.6 15.8 16.1 — 0.79 0.86 0.92 0.98 1.06 1.14 1.22 1.31 1.40 1.49 1.59 1.69 1.80 1.91 2.02 2.13 2.25 2.38 — 12.9 13.1 13.3 13.6 13.7 14.0 14.2 14.4 14.6 14.8 15.1 15.3 15.6 15.8 16.1 16.3 16.6 — — 0.92 0.98 1.05 1.12 1.20 1.28 1.36 1.44 1.53 1.63 1.74 1.85 1.97 2.09 2.21 2.34 2.47 — — 13.8 13.9 14.2 14.4 14.6 14.8 15.0 15.2 15.4 15.6 15.9 16.1 16.3 16.5 16.8 — — — — 1.04 1.11 1.18 1.25 1.34 1.42 1.52 1.60 1.70 1.79 1.90 2.00 2.12 2.24 2.37 — — — — EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2250 2300 2400 2450 350 300 400 500 450 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 14.6 14.8 15.0 15.1 15.3 15.5 15.8 16.0 16.2 16.4 16.6 16.8 17.0 17.2 — — — — — 1.15 1.23 1.30 1.39 1.47 1.56 1.66 1.75 1.86 1.96 2.07 2.18 2.30 2.41 — — — — — 15.3 15.5 15.7 15.9 16.1 16.3 16.4 16.6 16.9 17.1 17.3 17.5 — — — — — — — 1.26 1.35 1.44 1.52 1.61 1.70 1.80 1.90 2.01 2.12 2.24 2.36 — — — — — — — 16.1 16.2 16.4 16.6 16.8 17.0 17.2 17.3 17.5 17.7 17.9 — — — — — — — — 1.38 1.47 1.55 1.65 1.74 1.85 1.95 2.05 2.16 2.26 2.39 — — — — — — — — 16.9 17.1 17.1 17.3 17.4 17.6 17.8 18.0 18.2 18.4 — — — — — — — — — 1.45 1.60 1.68 1.77 1.88 1.98 2.09 2.20 2.31 2.43 — — — — — — — — — 17.7 17.8 17.9 18.0 18.1 18.2 18.4 18.6 — — — — — — — — — — — 1.68 1.81 1.86 1.91 2.00 2.11 2.22 2.34 — — — — — — — — — — — LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 23 Table 14 — Fan Performance, 48TF014 — Vertical Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1900 1950 2000 2050 2100 2150 2250 2300 2350 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850 2900 2950 3000 3050 3100 100 50 150 250 200 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 12.5 12.7 13.0 13.3 13.6 13.9 14.2 14.5 14.8 15.0 15.4 15.7 15.9 16.2 16.5 16.8 17.1 17.4 17.7 18.0 18.3 18.6 18.9 19.2 1.10 1.18 1.27 1.36 1.46 1.56 1.67 1.78 1.89 2.01 2.16 2.28 2.43 2.58 2.72 2.89 3.05 3.21 3.40 3.57 3.76 3.96 4.15 4.38 13.5 13.7 14.0 14.3 14.5 14.8 15.1 15.4 15.7 15.9 16.2 16.5 16.8 17.1 17.3 17.6 17.9 18.2 18.5 18.8 19.1 19.4 19.6 — 1.27 1.36 1.46 1.56 1.66 1.78 1.89 2.00 2.13 2.25 2.38 2.52 2.65 2.81 2.95 3.12 3.28 3.45 3.64 3.81 4.02 4.21 4.40 — 14.4 14.6 14.9 15.1 15.4 15.7 15.9 16.2 16.4 16.7 17.0 17.3 17.5 17.8 18.1 18.4 18.7 18.9 19.2 19.5 19.8 20.1 — — 1.42 1.52 1.62 1.72 1.84 1.95 2.07 2.19 2.32 2.46 2.60 2.75 2.90 3.05 3.22 3.39 3.56 3.74 3.93 4.11 4.29 4.51 — — 15.3 15.5 15.7 16.0 16.2 16.5 16.7 17.0 17.2 17.5 17.7 18.0 18.2 18.5 18.8 19.0 19.3 19.6 19.9 20.2 — — — — 1.63 1.73 1.81 1.91 2.01 2.13 2.24 2.37 2.51 2.64 2.79 2.95 3.10 3.26 3.43 3.60 3.80 3.98 4.18 4.37 — — — — 16.1 16.4 16.6 16.8 17.0 17.3 17.5 17.7 18.0 18.2 18.5 18.7 18.0 19.2 19.4 19.7 20.0 20.2 20.5 — — — — — 1.81 1.92 2.02 2.14 2.25 2.37 2.48 2.60 2.72 2.85 2.99 3.13 3.29 3.47 3.64 3.83 4.01 4.19 4.41 — — — — — EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1900 1950 2000 2050 2100 2150 2250 2300 2350 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850 2900 2950 3000 3050 3100 350 300 400 500 450 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 17.0 17.2 17.4 17.6 17.8 18.0 18.2 18.5 18.7 18.9 19.2 19.4 19.6 19.9 20.1 20.4 20.6 20.9 — — — — — — 2.00 2.11 2.22 2.33 2.45 2.59 2.71 2.85 2.99 3.12 3.27 3.38 3.54 3.69 3.86 4.03 4.21 4.40 — — — — — — 17.9 18.0 18.2 18.4 18.6 18.8 19.0 19.2 19.4 19.6 19.8 20.1 20.3 20.5 20.8 21.0 — — — — — — — — 2.21 2.31 2.43 2.54 2.66 2.79 2.93 3.05 3.21 3.36 3.53 3.67 3.83 4.01 4.16 4.32 — — — — — — — — 18.7 18.8 19.0 19.2 19.3 19.5 19.7 19.9 20.1 20.3 20.5 20.7 21.0 21.2 21.4 — — — — — — — — — 2.39 2.51 2.63 2.76 2.89 3.01 3.15 3.29 3.43 3.59 3.74 3.93 4.09 4.27 4.44 — — — — — — — — — 19.4 19.6 19.8 19.9 20.1 20.3 20.4 20.6 20.8 21.0 21.2 21.4 21.6 — — — — — — — — — — — 2.58 2.71 2.84 2.97 3.10 3.24 3.37 3.52 3.67 3.82 3.99 4.15 4.33 — — — — — — — — — — — 20.1 20.3 20.5 20.7 20.8 21.0 21.2 21.3 21.5 21.7 — — — — — — — — — — — — — — 2.74 2.88 3.02 3.17 3.32 3.46 3.60 3.76 3.92 4.08 — — — — — — — — — — — — — — LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 5. Standard drive range is 12.0 to 15.0 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 2.76. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 24 Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1075 1125 1150 1200 1250 1300 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 100 50 150 225 200 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 8.1 8.4 8.6 8.9 9.1 9.4 9.7 10.0 10.2 10.5 10.8 11.1 11.4 11.7 12.0 12.2 12.5 0.34 0.39 0.42 0.46 0.51 0.56 0.62 0.67 0.74 0.80 0.88 0.97 1.04 1.12 1.23 1.33 1.42 9.5 9.7 9.9 10.2 10.4 10.7 10.9 11.2 11.4 11.7 11.9 12.2 12.4 12.7 13.0 13.2 13.5 0.49 0.53 0.58 0.64 0.70 0.75 0.82 0.88 0.94 1.02 1.09 1.17 1.25 1.35 1.45 1.54 1.65 10.7 10.9 11.1 11.3 11.5 11.7 12.0 12.2 12.4 12.7 12.9 13.2 13.4 13.7 13.9 14.2 14.4 0.66 0.71 0.76 0.81 0.87 0.93 0.99 1.07 1.15 1.23 1.32 1.41 1.51 1.61 1.70 1.81 1.92 11.8 12.0 12.2 12.4 12.6 12.7 12.9 13.2 13.4 13.6 13.8 14.0 14.3 14.5 14.8 15.0 15.2 0.81 0.89 0.96 1.02 1.08 1.14 1.22 1.27 1.36 1.44 1.53 1.63 1.73 1.85 1.95 2.08 2.20 12.4 12.5 12.7 12.8 13.0 13.2 13.4 13.6 13.8 14.0 14.2 14.4 14.7 14.9 15.1 15.4 15.6 0.92 0.98 1.05 1.11 1.19 1.25 1.33 1.40 1.48 1.56 1.65 1.75 1.85 1.97 2.07 2.20 2.34 EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1075 1125 1150 1200 1250 1300 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 300 250 350 400 R/s BkW R/s BkW R/s BkW R/s BkW 12.9 13.0 13.1 13.3 13.5 13.7 13.9 14.1 14.3 14.2 14.8 14.9 15.1 15.3 15.5 15.8 16.0 1.03 1.08 1.13 1.21 1.29 1.37 1.44 1.52 1.60 1.68 1.77 1.86 1.97 2.08 2.20 2.32 2.46 13.9 14.0 14.1 14.3 14.4 14.5 14.7 14.9 15.1 15.3 15.5 15.7 15.9 16.1 16.3 16.5 16.7 1.29 1.34 1.38 1.42 1.48 1.56 1.66 1.77 1.86 1.94 2.04 2.13 2.24 2.35 2.45 2.58 2.70 15.0 15.1 15.2 15.2 15.3 15.4 15.5 15.7 15.9 16.1 16.3 16.5 16.6 16.3 17.0 17.2 17.5 1.60 1.68 1.69 1.74 1.78 1.81 1.84 1.97 2.08 2.21 2.31 2.42 2.52 2.64 2.76 2.87 2.99 15.7 15.9 16.0 16.0 16.2 16.3 16.4 16.5 16.6 16.8 17.0 17.2 17.4 17.6 17.7 17.9 18.1 1.89 1.92 1.96 2.01 2.06 2.09 2.19 2.18 2.29 2.43 2.55 2.70 2.82 2.94 3.05 3.19 3.31 LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 25 Table 16 — Fan Performance, 48TF012 — Horizontal Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2300 2350 2400 2500 100 50 150 250 200 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 9.1 9.4 9.6 9.8 10.1 10.3 10.6 10.8 11.1 11.3 11.6 11.9 12.1 12.4 12.7 12.9 13.2 13.5 — 0.49 0.54 0.59 0.65 0.71 0.77 0.84 0.92 1.00 1.09 1.18 1.28 1.38 1.49 1.61 1.74 1.86 2.00 — 10.5 10.7 10.9 11.1 11.3 11.5 11.7 11.9 12.1 12.3 12.6 12.8 13.0 13.2 13.4 13.7 13.9 14.2 14.4 0.63 0.68 0.73 0.80 0.86 0.92 0.98 1.04 1.14 1.22 1.31 1.40 1.50 1.60 1.70 1.81 1.93 2.05 2.14 11.6 11.8 12.0 12.2 12.4 12.6 12.8 13.0 13.2 13.4 13.6 13.8 14.0 14.2 14.4 14.6 14.8 15.0 15.2 0.77 0.82 0.88 0.95 1.01 1.07 1.14 1.21 1.29 1.38 1.47 1.56 1.64 1.73 1.83 1.93 2.03 2.14 2.25 12.6 12.8 13.0 13.2 13.4 13.5 13.7 13.9 14.1 14.3 14.5 14.7 14.9 15.1 15.3 15.5 15.7 — — 0.89 0.96 1.02 1.09 1.16 1.23 1.30 1.39 1.47 1.55 1.65 1.73 1.82 1.93 2.04 2.15 2.27 — — 13.5 13.7 13.9 14.1 14.2 14.4 14.6 14.8 15.0 15.2 15.3 15.5 15.8 15.9 16.1 — — — — 0.99 1.06 1.14 1.22 3.10 1.38 1.47 1.55 1.64 1.72 1.82 1.92 2.02 2.13 2.24 — — — — EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2300 2350 2400 2500 350 300 400 500 450 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 14.5 14.6 14.8 14.9 15.0 15.2 15.4 15.6 15.8 16.0 16.2 16.3 16.5 16.7 16.9 — — — — 1.13 1.20 1.26 1.33 1.42 1.51 1.61 1.71 1.80 1.91 2.01 2.10 2.21 2.32 2.43 — — — — 15.2 15.4 15.6 15.7 15.9 16.0 16.2 16.3 16.5 16.7 16.9 17.1 — — — — — — — 1.22 1.30 1.40 1.48 1.56 1.64 1.73 1.84 1.94 2.06 2.17 2.29 — — — — — — — 16.1 16.2 16.3 16.5 16.7 16.8 17.0 17.1 17.2 17.4 17.6 — — — — — — — — 1.40 1.43 1.50 1.60 1.70 1.79 1.89 1.98 2.07 2.19 2.31 — — — — — — — — 16.8 16.9 17.1 17.2 17.3 17.5 17.7 17.8 18.0 — — — — — — — — — — 1.54 1.60 1.68 1.72 1.81 1.91 2.03 2.15 2.24 — — — — — — — — — — 17.7 17.8 17.9 18.0 18.0 18.2 18.3 18.5 18.7 — — — — — — — — — — 1.82 1.86 1.91 1.97 1.97 2.04 2.15 2.27 2.40 — — — — — — — — — — LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 1.79. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 26 Table 17 — Fan Performance, 48TF014 — Horizontal Discharge Units (SI) EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1900 1950 2000 2050 2100 2150 2200 2250 2325 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850 2900 2950 3000 3050 3100 100 50 150 225 200 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 11.5 11.8 12.1 12.3 12.6 12.8 13.1 13.3 13.6 13.9 14.1 14.4 14.7 14.9 15.2 15.4 15.7 15.9 16.2 16.5 16.7 17.0 17.3 17.5 0.96 1.04 1.12 1.18 1.27 1.36 1.44 1.53 1.63 1.74 1.84 1.95 2.07 2.18 2.32 2.44 2.57 2.71 2.86 2.98 3.11 3.25 3.38 3.52 12.7 12.9 13.2 13.4 13.6 13.9 14.1 14.4 14.6 14.9 15.1 15.4 15.6 15.8 16.1 16.4 16.6 16.9 17.1 17.3 17.6 17.8 18.1 18.3 1.14 1.22 1.29 1.38 1.46 1.56 1.66 1.75 1.87 1.98 2.10 2.22 2.34 2.47 2.60 2.74 2.89 3.03 3.18 3.32 3.46 3.60 3.74 3.89 13.7 13.9 14.2 14.4 14.6 14.9 15.1 15.3 15.5 15.8 16.0 16.2 16.5 16.7 16.9 17.2 17.4 17.7 17.9 18.2 18.4 18.7 — — 1.32 1.40 1.49 1.59 1.68 1.78 1.88 1.99 2.10 2.20 2.31 2.44 2.56 2.69 2.83 2.96 3.11 3.27 3.46 3.57 3.72 3.87 — — 14.7 14.9 15.1 15.3 15.5 15.7 16.0 16.2 16.4 16.6 16.8 17.1 17.3 17.5 17.8 18.0 18.2 18.4 18.7 18.9 — — — — 1.49 1.57 1.65 1.75 1.86 1.96 2.07 2.20 2.30 2.44 2.56 2.69 2.83 2.96 3.11 3.26 8.38 3.55 3.70 3.85 — — — — 15.6 15.8 16.0 16.2 16.4 16.6 16.8 17.0 17.2 17.4 17.6 17.8 18.1 18.3 18.5 18.7 19.0 19.2 — — — — — — 1.71 1.80 1.89 1.96 2.05 2.15 2.26 2.36 2.50 2.64 2.77 2.90 3.05 3.20 3.34 3.51 3.67 3.84 — — — — — — EXTERNAL STATIC PRESSURE (Pa) AIRFLOW (L/s) 1900 1950 2000 2050 2100 2150 2200 2250 2235 2400 2450 2500 2550 2600 2650 2700 2750 2800 2850 2900 2950 3000 3050 3100 350 300 400 500 450 R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW 16.6 16.7 16.9 17.1 17.2 17.4 17.6 17.8 18.0 18.2 18.4 18.6 18.8 19.0 19.2 19.4 19.7 — — — — — — — 1.91 2.00 2.11 2.20 2.30 2.42 2.52 2.61 2.71 2.83 2.97 3.09 3.25 3.42 3.58 3.73 3.91 — — — — — — — 17.5 17.6 17.8 17.9 18.1 18.2 18.4 18.6 18.8 18.9 19.1 19.3 19.5 19.7 19.9 20.1 — — — — — — — — 2.11 2.21 2.31 2.42 2.53 2.64 2.76 2.88 3.00 3.13 3.24 3.35 3.49 3.63 3.81 3.92 — — — — — — — — 18.2 18.4 18.6 18.7 18.9 19.0 19.2 19.4 19.5 19.7 19.9 20.0 20.2 20.4 — — — — — — — — — — 2.29 2.41 2.52 2.64 2.76 2.88 2.99 3.11 3.26 3.39 3.52 3.66 3.81 3.95 — — — — — — — — — — 18.9 19.1 19.3 19.5 19.6 19.8 20.0 20.1 20.3 20.5 20.6 20.8 — — — — — — — — — — — — 2.44 2.58 2.71 2.84 2.97 3.10 3.23 3.37 3.49 3.64 3.77 3.93 — — — — — — — — — — — — 19.3 19.6 19.9 20.1 20.3 20.5 20.7 20.9 21.0 21.2 — — — — — — — — — — — — — — 2.55 2.71 2.87 3.02 3.17 3.31 3.45 3.60 3.75 3.89 — — — — — — — — — — — — — — LEGEND BkW — Fan Input kW x Motor Efficiency R/s — Revolutions Per Second of Blower Wheel 5. Standard drive range is 12.0 to 15.0 r/s. All other speeds require a field-supplied drive. 6. Maximum continuous BkW is 2.76. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 27 Table 18 — Fan Performance, 48TF008 — Vertical Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 0.4 0.2 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 506 514 521 536 551 559 567 582 598 614 630 646 662 679 695 712 729 745 754 0.52 0.55 0.56 0.63 0.69 0.72 0.75 0.83 0.90 0.98 1.07 1.16 1.26 1.36 1.47 1.59 1.71 1.84 1.91 586 593 600 613 626 634 641 655 670 684 699 714 729 744 759 774 790 805 813 0.72 0.76 0.79 0.85 0.93 0.97 1.00 1.08 1.17 1.25 1.35 1.45 1.55 1.66 1.78 1.90 2.03 2.17 2.24 656 662 668 680 693 700 706 719 732 745 759 773 787 801 816 830 845 860 868 0.95 0.99 1.02 1.09 1.17 1.21 1.25 1.34 1.43 1.53 1.63 1.74 1.86 1.98 2.10 2.23 2.37 2.52 2.59 718 724 730 741 753 759 764 776 789 802 815 828 841 854 867 881 895 909 917 1.18 1.22 1.26 1.34 1.43 1.48 1.52 1.61 1.71 1.81 1.92 2.04 2.16 2.29 2.42 2.56 2.71 2.87 2.95 EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 1.2 1.0 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 776 781 786 796 808 814 819 831 842 854 866 878 891 904 917 930 943 956 963 1.43 1.78 1.50 1.59 1.69 1.74 1.79 1.89 2.00 2.11 2.23 2.35 2.48 2.61 2.75 2.90 3.05 3.22 3.30 838 841 843 849 859 864 869 880 892 903 915 926 938 950 963 976 988 — — 1.78 1.81 1.83 1.88 1.96 2.01 2.06 2.17 2.29 2.42 2.54 2.67 2.81 2.95 3.10 3.25 3.41 — — 898 902 905 910 912 915 918 927 938 949 961 972 983 995 1007 — — — — 2.21 2.25 2.28 2.31 2.31 2.34 2.37 2.47 2.58 2.71 2.85 3.00 3.14 3.30 3.45 — — — — 935 939 943 952 963 968 973 976 983 993 1003 1015 1026 — — — — — — 2.58 2.60 2.62 2.74 2.81 2.81 2.81 2.84 2.92 3.03 3.17 3.32 3.47 — — — — — — LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 492 to 700 rpm. All other rpms require a field-supplied drive. 6. Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 28 Table 19 — Fan Performance, 48TF012 — Vertical Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 0.4 0.2 0.6 1.0 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 592 607 622 638 653 669 684 700 715 731 747 763 778 794 810 826 842 858 874 890 906 0.76 0.83 0.90 0.98 1.06 1.15 1.24 1.33 1.43 1.54 1.65 1.76 1.88 2.00 2.13 2.27 2.41 2.55 2.70 2.86 3.03 661 676 690 705 719 733 747 760 774 787 801 816 831 846 861 876 892 907 922 938 953 0.93 1.01 1.09 1.17 1.26 1.35 1.44 1.54 1.64 1.74 1.85 1.97 2.10 2.23 2.37 2.52 2.67 2.83 2.99 3.16 3.33 722 734 746 759 772 786 800 814 828 843 857 872 886 900 913 927 940 954 968 — — 1.09 1.17 1.25 1.33 1.43 1.53 1.64 1.75 1.86 1.98 2.10 2.23 2.36 2.50 2.64 2.78 2.92 3.08 3.24 — — 779 791 803 815 826 838 850 863 875 888 902 916 929 943 958 973 987 1002 — — — 1.26 1.34 1.43 1.52 1.62 1.72 1.82 1.92 2.04 2.16 2.30 2.44 2.58 2.73 2.89 3.04 3.21 3.38 — — — 829 840 852 864 876 888 900 912 924 936 948 960 972 985 999 1012 — — — — — 1.42 1.51 1.60 1.70 1.81 1.91 2.03 2.14 2.26 2.30 2.51 2.64 2.78 2.93 3.09 3.26 — — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 1.4 1.2 1.6 2.0 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 880 890 900 910 921 933 945 957 969 981 993 1005 1016 1028 1040 — — — — — — 1.58 1.68 1.77 1.88 1.98 2.10 2.22 2.34 2.47 2.60 2.74 2.88 3.03 3.17 3.32 — — — — — — 924 935 946 957 967 976 986 998 1010 1022 1034 1046 1058 — — — — — — — — 1.73 1.84 1.95 2.06 2.17 2.29 2.41 2.54 2.67 2.81 2.96 3.11 3.26 — — — — — — — — 970 977 987 998 1009 1020 1030 1039 1049 1060 1072 1084 — — — — — — — — — 1.89 2.00 2.11 2.23 2.35 2.48 2.61 2.74 2.87 3.02 3.17 3.32 — — — — — — — — — 1019 1026 1029 1037 1047 1058 1069 1081 1091 1100 1110 — — — — — — — — — — 2.00 2.17 2.28 2.40 2.53 2.66 2.80 2.94 3.08 3.23 3.38 — — — — — — — — — — 1066 1070 1075 1082 1087 1095 1106 1117 1128 — — — — — — — — — — — — 2.30 2.44 2.51 2.58 2.70 2.84 2.98 3.13 3.29 — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 571 to 779 rpm. All other speeds require a field-supplied drive. 6. Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 29 Table 20 — Fan Performance, 48TF014 — Vertical Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 0.4 0.2 0.6 1.0 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 729 745 761 777 793 810 826 842 859 876 892 909 926 942 959 976 993 1010 1027 1043 1060 1077 1094 1111 1128 1145 1.36 1.46 1.56 1.67 1.79 1.91 2.04 2.17 2.31 2.46 2.60 2.77 2.93 3.11 3.29 3.47 3.67 3.87 4.07 4.29 4.51 4.74 4.98 5.22 5.48 5.74 790 805 820 836 851 867 883 898 914 930 945 961 977 993 1009 1025 1041 1057 1073 1090 1106 1122 1139 1155 — — 1.58 1.69 1.80 1.92 2.05 2.18 2.32 2.46 2.60 2.76 2.91 3.07 3.24 3.41 3.60 3.78 3.98 4.18 4.39 4.61 4.83 5.07 5.41 5.55 — — 847 861 875 889 904 918 933 948 962 977 992 1008 1024 1039 1055 1071 1086 1102 1118 1133 1149 1165 1181 — — — 1.79 1.89 2.02 2.14 2.27 2.41 2.55 2.70 2.85 3.01 3.18 3.36 3.54 3.73 3.92 4.12 4.33 4.54 4.76 4.99 5.22 5.46 5.70 — — — 902 915 928 941 955 968 982 996 1010 1024 2039 1053 1068 1080 1097 1112 1127 1142 1157 1173 1189 — — — — — 2.06 2.17 2.29 2.40 2.42 2.54 2.79 2.93 3.09 3.26 3.43 3.61 3.80 3.90 4.19 4.40 4.61 4.84 5.07 5.31 5.55 — — — — — 955 967 979 991 1004 1017 1030 1043 1056 1070 1083 1097 1111 1126 1139 1153 1168 1182 1197 1211 — — — — — — 2.29 2.41 2.55 2.68 2.82 2.96 3.11 3.25 3.40 3.55 3.71 3.88 4.06 4.25 4.46 4.67 4.90 5.13 5.36 5.61 — — — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 1.4 1.2 1.6 2.0 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1008 1019 1029 1040 1052 1064 1076 1088 1101 1114 1126 1140 1153 1166 1180 1194 1208 1221 1235 — — — — — — — 2.55 2.67 2.80 2.94 3.08 3.23 3.40 3.56 3.73 3.90 4.07 4.25 4.41 4.59 4.78 4.98 5.19 5.41 5.64 — — — — — — — 1060 1070 1079 1089 1100 1110 1121 1133 1144 1157 1169 1181 1194 1207 1220 1233 1246 — — — — — — — — — 2.80 2.94 3.07 3.22 3.36 3.51 3.67 3.84 4.00 4.19 4.38 4.58 4.77 4.97 5.18 5.38 5.58 — — — — — — — — — 1108 1118 1128 1137 1147 1157 1167 1178 1188 1199 1210 1222 1234 1247 1259 1272 — — — — — — — — — — 3.05 3.19 3.34 3.49 3.65 3.81 3.97 4.14 4.31 4.49 4.68 4.87 5.09 5.30 5.52 5.74 — — — — — — — — — — 1152 1163 1173 1183 1193 1202 1212 1222 1232 1242 1252 1263 1274 1286 — — — — — — — — — — — — 3.27 3.44 3.60 3.76 3.93 4.09 4.27 4.44 4.62 4.81 5.00 5.20 5.40 5.62 — — — — — — — — — — — — 1190 1203 1214 1225 1236 1245 1255 1265 1274 1284 1294 — — — — — — — — — — — — — — — 3.46 3.65 3.83 4.00 4.19 4.38 4.56 4.74 4.93 5.13 5.33 — — — — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 717 to 900 rpm. All other rpms require a field-supplied drive. 6. Maximum continuous bhp is 3.7. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 30 Table 21 — Fan Performance, 48TF008 — Horizontal Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 0.4 0.2 0.6 0.9 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 499 507 513 528 542 550 557 573 588 604 620 636 652 668 684 701 717 733 742 0.50 0.53 0.55 0.60 0.66 0.69 0.72 0.79 0.86 0.94 1.02 1.11 1.21 1.31 1.41 1.53 1.65 1.77 1.84 580 586 592 606 619 627 634 648 662 676 690 704 718 732 747 762 777 792 800 0.70 0.73 0.76 0.83 0.90 0.94 0.97 1.05 1.13 1.21 1.30 1.39 1.49 1.59 1.70 1.82 1.94 2.07 2.14 652 658 663 674 686 692 698 711 723 737 750 764 778 793 807 821 835 849 856 0.94 0.97 1.00 1.06 1.13 1.17 1.21 1.29 1.38 1.48 1.58 1.69 1.80 1.92 2.04 2.16 2.29 2.42 2.49 717 722 727 738 748 754 759 770 782 794 806 818 831 844 857 871 885 899 907 1.17 1.22 1.26 1.34 1.41 1.45 1.49 1.58 1.66 1.76 1.86 1.97 2.09 2.21 2.35 2.48 2.63 2.78 2.86 748 752 756 766 777 783 787 798 809 821 832 844 856 869 882 895 908 922 929 1.30 1.34 1.38 1.46 1.55 1.60 1.64 1.73 1.82 1.92 2.02 2.13 2.25 2.37 2.51 2.64 2.79 2.95 3.03 EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 2200 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750 1.2 1.0 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 779 783 786 795 806 812 816 827 837 848 849 870 882 894 907 919 932 945 952 1.43 1.46 1.49 1.58 1.68 1.74 1.79 1.88 1.98 2.08 2.18 2.29 2.40 2.53 2.66 2.80 2.95 3.11 3.20 839 843 846 853 859 864 868 878 889 900 910 920 931 942 954 966 978 990 997 1.78 1.81 1.84 1.88 1.94 1.99 2.04 2.16 2.29 2.41 2.52 2.64 2.76 2.89 3.02 3.15 3.30 3.45 3.54 905 908 910 912 919 920 921 928 937 947 958 968 979 989 1000 1011 1022 1034 1040 2.21 2.25 2.25 2.31 2.37 2.39 2.41 2.45 2.57 2.70 2.85 2.99 3.13 3.26 3.40 3.55 3.69 3.84 3.93 951 955 959 967 971 974 976 983 986 993 1002 1012 1023 1034 1044 1054 1065 1076 1082 2.57 2.59 2.61 2.68 2.73 2.76 2.78 2.88 2.91 3.01 3.15 3.30 3.47 3.63 3.79 3.94 4.10 4.28 5.27 LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 492 to 700 rpm. All other rpms require a field-supplied drive. 6. Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 31 Table 22 — Fan Performance, 48TF012 — Horizontal Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 0.4 0.2 0.6 1.0 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 552 565 578 591 605 619 633 648 662 677 692 707 722 737 752 768 783 799 814 — — 0.68 0.74 0.81 0.88 0.96 1.04 1.13 1.23 1.33 1.44 1.55 1.67 1.80 1.94 2.08 2.24 2.40 2.56 2.74 — — 632 644 656 668 680 691 703 714 726 738 750 762 775 787 800 814 827 841 855 868 883 0.87 0.93 1.00 1.08 1.16 1.23 1.31 1.39 1.51 1.61 1.73 1.84 1.97 2.09 2.21 2.35 2.50 2.64 2.80 2.90 3.10 701 711 723 734 745 755 766 777 789 801 813 825 837 848 860 871 883 894 906 918 931 1.05 1.12 1.20 1.28 1.36 1.44 1.52 1.61 1.72 1.82 1.94 2.05 2.16 2.27 2.39 2.51 2.64 2.77 2.91 3.05 3.21 761 772 782 793 803 813 824 835 846 857 868 878 889 900 912 924 937 949 961 972 — 1.22 1.31 1.39 1.47 1.56 1.65 1.74 1.85 1.95 2.06 2.17 2.28 2.40 252 2.66 2.80 2.95 3.10 3.26 3.40 — 816 825 835 845 856 867 877 887 897 908 918 929 941 952 962 973 983 994 — — — 1.36 1.45 1.55 1.65 1.75 1.86 1.97 2.07 2.18 2.29 2.40 2.53 2.66 2.80 2.93 3.07 3.21 3.36 — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 1.4 1.2 1.6 2.0 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 871 879 887 895 904 914 924 935 946 956 967 977 987 999 1008 1019 — — — — — 1.54 1.63 1.71 1.80 1.91 2.03 2.15 2.28 2.40 2.53 2.66 2.78 2.91 3.04 3.19 3.34 — — — — — 918 928 937 946 953 961 970 980 989 1000 1010 1021 1032 1042 — — — — — — — 1.67 1.78 1.90 2.00 2.10 2.20 2.32 2.45 2.58 2.73 2.87 3.02 3.17 3.32 — — — — — — — 967 973 981 991 1000 1009 1017 1024 1033 1042 1052 1062 1072 — — — — — — — — 1.89 1.94 2.04 2.16 2.29 2.41 2.53 2.64 2.76 2.91 3.06 3.22 3.38 — — — — — — — — 1010 1018 1026 1032 1041 1051 1061 1069 1077 1085 1093 1102 — — — — — — — — — 2.09 2.17 2.26 2.32 2.44 2.57 2.72 2.87 2.99 3.12 3.24 3.41 — — — — — — — — — 1063 1070 1075 1080 1083 1090 1099 1109 1118 1127 — — — — — — — — — — — 2.46 2.51 2.57 2.64 2.65 2.74 2.88 3.03 3.20 3.36 — — — — — — — — — — — LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 571 to 779 rpm. All other rpms require a field-supplied drive. 6. Maximum continuous bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 32 Table 23 — Fan Performance, 48TF014 — Horizontal Discharge Units (English) EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 0.4 0.2 0.6 1.0 0.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 677 691 705 720 734 749 764 779 793 808 822 837 852 867 882 896 911 926 940 955 970 985 1000 1015 1030 1046 1.20 1.28 1.37 1.47 1.56 1.66 1.77 1.88 1.99 2.11 2.24 2.37 2.51 2.65 2.79 2.95 3.11 3.27 3.44 3.62 3.80 3.99 4.18 4.39 4.59 4.81 748 761 773 786 800 813 826 840 854 868 882 896 910 924 938 952 967 981 995 1010 1024 1039 1053 1068 1083 1097 1.43 1.52 1.62 1.71 1.82 1.92 2.04 2.16 2.28 2.42 2.56 2.71 2.86 3.01 3.17 3.33 3.50 3.68 3.86 4.04 4.23 4.42 4.62 4.83 5.04 5.26 810 822 834 847 860 873 886 899 912 925 937 950 963 977 990 1003 1017 1030 1044 1058 1072 1086 1100 1114 1128 1142 1.65 1.75 1.86 1.97 2.09 2.21 2.33 2.46 2.59 2.73 2.86 3.00 3.15 3.30 3.46 3.63 3.80 3.98 4.17 4.38 4.59 4.80 5.02 5.25 5.48 5.71 869 880 891 902 914 926 938 951 963 975 988 1001 1014 1027 1040 1053 1066 1079 1092 1105 1118 1131 1144 1158 — — 1.89 1.98 2.08 2.19 2.31 2.44 2.57 2.71 2.86 3.00 3.16 3.32 3.48 3.65 3.82 4.00 4.18 4.35 4.54 4.73 4.93 5.14 5.36 5.58 — — 928 937 947 956 967 978 989 1000 1012 1024 1036 1048 1060 1073 1085 1098 1111 1124 1137 1150 1163 1176 — — — — 2.17 2.28 2.39 2.50 2.60 2.71 2.83 2.96 3.09 3.25 3.42 3.59 3.76 3.94 4.12 4.30 4.50 4.70 4.91 5.12 5.34 5.56 — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000 5100 5200 5300 5400 5500 5600 5700 5800 5900 6000 6100 6200 1.4 1.2 1.6 2.0 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 984 993 1002 1011 1021 1030 1040 1050 1061 1071 1082 1093 1105 1117 1129 1141 1153 1166 1178 1190 1203 — — — — — 2.43 2.55 2.66 2.79 2.91 3.04 3.18 3.31 3.43 3.56 3.70 3.86 4.02 4.20 4.40 4.60 4.80 5.01 5.22 5.44 5.67 — — — — — 1036 1046 1055 1064 1072 1081 1090 1100 1109 1119 1129 1139 1150 1161 1172 1183 1194 1206 1218 1230 — — — — — — 2.68 2.81 2.94 3.07 3.20 3.34 3.48 3.63 3.78 3.93 4.09 4.24 4.38 4.54 4.71 4.91 5.08 5.29 5.52 5.75 — — — — — — 1080 1092 1102 1112 1121 1130 1139 1148 1156 1166 1175 1185 1194 1204 1214 1225 1236 1247 — — — — — — — — 2.90 3.05 3.20 3.34 3.49 3.64 3.79 3.94 4.09 4.26 4.43 4.60 4.77 4.95 5.13 5.29 5.47 5.65 — — — — — — — — 1114 1129 1143 1155 1165 1175 1185 1194 1203 1212 1221 1230 1239 1248 1257 1267 — — — — — — — — — — 3.07 3.25 3.42 3.59 3.76 3.92 4.08 4.25 4.42 4.58 4.76 4.93 5.12 5.31 5.61 5.70 — — — — — — — — — — 1135 1156 1174 1190 1203 1215 1226 1236 1246 1255 1264 1273 1282 1291 — — — — — — — — — — — — 3.17 3.39 3.59 3.80 3.99 4.18 4.36 4.54 4.72 4.91 5.09 5.28 5.47 5.66 — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower at Motor Shaft Rpm — Revolutions Per Minute of Blower Wheel 5. Standard drive range is 717 to 900 rpm. All other rpms require a field-supplied drive. 6. Maximum continuous bhp is 3.7. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 7. Interpolation is permissible. Do not extrapolate. NOTES: 1. Boldface indicates field-supplied drive required. (See Note 5.) 2. indicates field-supplied motor and drive are required. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify. 33 START-UP TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Unit Preparation — Make sure that unit has been installed in accordance with these installation instructions and applicable codes. Make sure that Start-Up Checklist, located on back page of this booklet, has been completed and filled out. Main Burners — Main burners are factory set and should require no adjustment. TO CHECK ignition of main burners and heating controls, move thermostat set point above room temperature and verify that the burners light and evaporator fan is energized. After ensuring that the unit continues to heat the building, lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off (fan will turn off only if fan selector switch is in the AUTO. position). Refer to Table 24 for the correct orifice to use at high altitudes. NOTE: Upon a call for heat, the main burners will remain on for a minimum of 60 seconds. ADJUST GAS INPUT — The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Manifold pressure should be 872 Pa (3.5 in. wg). NOTE: Unit uses a 2 stage gas valve. There is no need to adjust the “Low Fire” manifold pressure. Measure Gas Flow (Natural Gas Units) — Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be 872 Pa (3.5 in wg). Normal manifold pressure is 872 Pa (3.5 in. wg) in high fire, W1 and W2 inputs to gas valve. Proceed as follows: 1. Turn off gas supply to unit. 2. Remove pipe plug on manifold then connect manometer at this point. Turn on gas to unit. Ensure gas valve is in high fire operation. Observe manifold pressure and proceed as follows to adjust gas input: 1. Remove cover screw over regulator adjustment screw on gas valve. Ensure gas valve is operating in high fire mode. 2. Turn regulator adjustment screw clockwise to increase gas input, or turn regulator adjustment screw counterclockwise to decrease input. High fire manifold pressure must be 872 Pa (3.5 in. wg). Return-Air Filters — Make sure correct filters are installed in filter tracks (see Tables 1A and 1B). Do not operate unit without return-air filters. Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit. Compressor Mounting — Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts. On 48TF014 units, remove the tiedown bands that hold the compressors together. Internal Wiring — Check all electrical connections in unit control boxes. Tighten as required. Ensure wiring does not come into direct contact with refrigerant tubing. Refrigerant Service Ports — Each refrigerant system has 4 Schrader-type service gage ports: one on the suction line, one on the liquid line, and two on the compressor discharge line. Be sure that caps on the ports are tight. One Schrader-type valve is located under both the high-pressure switch and the low-pressure switch when ordered as an option. High Flow Valves — Located on the compressor hot gas and suction tubes are High Flow Valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrigerant leakage could occur. Compressor Rotation — On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gages to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 1. Note that the evaporator fan is probably also rotating in the wrong direction. 2. Turn off power to the unit and install lockout tag. 3. Reverse any two of the unit power leads. 4. Reapply power to unit. Reenergize compressor. The suction and discharge pressure levels should now move to their normal start-up levels. NOTE: When the compressor is rotating in the wrong direction, the unit will make an elevated level of noise and will not provide cooling. Unsafe operation of the unit may result if manifold pressure is outside 847 to 897 Pa (3.4 to 3.6 in. wg) range. Personal injury or unit damage may result. 3. Replace cover screw cap on gas valve. 4. Turn off gas supply to unit. Remove manometer from pressure tap and replace pipe plug on gas valve. Turn on gas to unit and check for leaks. Heating 1. Purge gas supply line of air by opening union ahead of gas valve. When gas odor is detected, tighten union and wait 5 minutes before proceeding. 2. Turn on electrical supply and open manual gas valve. 3. Set system switch selector at HEAT position and fan switch at AUTO. or ON position. Set heating temperature lever above room temperature. 4. The induced-draft motor will start, purging heat exchangers. Cooling — To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor, indoor and outdoor fans start on closure of contactors. Check unit charge. Refer to Refrigerant Charge section, page 37. Unit must operate a minimum of 15 minutes before adjusting charge. Reset thermostat at a position above room temperature. Compressor and outdoor fans will shut off. Evaporator fan will shut off after 30-second delay. 34 Safety Relief — A soft-solder joint at the suction line 5. After a call for heating, the main burners should light within 5 seconds. If the burners do not light, then there is a 22-second delay before another 5-second ignition try. If the burners still do not light, the time delay is repeated. If the burners do not light within 15 minutes, there is a lockout. To reset the control, break the 24 v power to W1. 6. The evaporator-fan motor will turn on 45 seconds after the burners are ignited. 7. The evaporator-fan motor will turn off 45 seconds after the thermostat temperature is satisfied. 8. Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate and in Table 1A or 1B. Schrader port provides pressure relief under abnormal temperature and pressure conditions. Ventilation (Continuous Fan) — Set fan and system selector switches at ON and OFF positions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off. Operating Sequence COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motors, compressor no. 1, and both condenser fans start. The condenserfan motor runs continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts. When the thermostat is satisfied, C1 and C2 are deenergized and the compressors and outdoor (condenser) fan motors (OFM) shut off. After a 30-second delay, the indoor (evaporator) fan motor (IFM) shuts off. If the thermostat fan selector switch is in the ON position, the evaporator motor will run continuously. HEATING, UNITS WITHOUT ECONOMIZER — When the thermostat calls for heating, terminal W1 is energized. In order to prevent thermostat short-cycling, the unit is locked into the Heating mode for at least 1 minute when W1 is energized. The induced-draft motor (IDM) is then energized and the burner ignition sequence begins. The indoor (evaporator) fan motor (IFM) is energized 45 seconds after a flame is ignited. On units equipped for two stages of heat, when additional heat is needed, W2 is energized and the high-fire solenoid on the main gas valve (MGV) is energized. When the thermostat is satisfied and W1 and W2 are deenergized, the IFM stops after a 45-second time-off delay. COOLING, UNITS WITH DURABLADE ECONOMIZER — When the outdoor-air temperature is above the OAT (outdoor-air thermostat) setting and the room thermostat calls for cooling, compressor contactor no. 1 is energized to start compressor no. 1 and the outdoor (condenser) fan motor (OFM). The indoor (evaporator) fan motor (IFM) is energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor contactor no. 2 will be energized, starting compressor no. 2. After the thermostat is satisfied, the damper moves to the fully closed position when using an auto fan or to the minimum position when using a continuous fan. When the outdoor-air temperature is below the OAT setting and the thermostat calls for cooling, the economizer dampers move to the minimum position. If the supply-air temperature is above 14 C (57 F), the damper continues to open until it reaches the fully open position or until the supply-air temperature drops below 11 C (52 F). When the supply-air temperature falls to between 14 C (57 F) and 11 C (52 F), the damper will remain at an intermediate open position. If the supply-air temperature falls below 11 C (52 F), the damper will modulate closed until it reaches the minimum position or until the supply-air temperature is above 11 C (52 F). When the thermostat is satisfied, the damper will move to the fully closed position when using an auto fan or to the minimum position when using a continuous fan. Table 24 — Altitude Compensation* ELEVATION m or km (ft) 0-610 m (0-2,000) 610 m (2,000) 914 m (3,000) 1.22 km (4,000) 1.52 km (5,000) 1.83 km (6,000) 2.13 km (7,000) 2.44 km (8,000) 2.74 km (9,000) 3.05 km (10,000) 3.35 km (11,000) 3.66 km (12,000) 3.96 km (13,000) 4.27 km (14,000) 31.4, 50.4, AND 59.8 kW (107,000, 172,000 AND 204,000 BTUH NOMINAL INPUT Natural Liquid Gas Propane Orifice Orifice Size† Size† 3.0 (31) 2.4 (41) 2.9 (32) 2.3 (42) 2.9 (32) 2.3 (42) 2.9 (32) 2.3 (42) 2.8 (33) 2.2 (43) 2.8 (34) 2.2 (43) 2.8 (35) 2.1 (44) 2.7 (36) 2.1 (44) 2.6 (37) 2.0 (45) 2.5 (38) 2.0 (46) 2.5 (39) 1.9 (47) 2.4 (40) 1.9 (47) 2.4 (41) 1.9 (48) 2.3 (42) 1.9 (48) 65.6 kW (224,000 BTUH) NOMINAL INPUT Natural Liquid Gas Propane Orifice Orifice Size† Size† 3.2 (30) 2.5 (38) 3.2 (30) 2.5 (39) 3.0 (31) 2.4 (40) 2.9 (32) 2.4 (41) 2.8 (33) 2.3 (42) 2.8 (34) 2.2 (43) 2.8 (35) 2.2 (43) 2.7 (36) 2.1 (44) 2.6 (37) 2.1 (44) 2.5 (38) 2.0 (45) 2.5 (39) 2.0 (45) 2.4 (40) 2.0 (46) 2.4 (41) 1.9 (47) 2.3 (42) 1.9 (47) *As the height above sea level increases, there is less oxygen. Therefore, heat input rate should be reduced at higher altitudes. †Orifice available through your local distributor. Integrated Gas Controller (IGC) Operation NOTE: The default value for the evaporator-fan motor ON and OFF delay is 45 seconds. The Integrated Gas Controller (IGC) modifies this value when abnormal limit switch cycles occur. Based upon unit operating conditions, the ON delay can be reduced to 0 seconds and the OFF delay can be extended to 180 seconds. When one flash of the LED (light-emitting diode) is observed, the evaporator-fan ON/OFF delay has been modified. If the limit switch trips at the start of the heating cycle during the evaporator ON delay, the time period of the ON delay for the next cycle will be 5 seconds less than the time at which the switch tripped. (Example: If the limit switch trips at 30 seconds, the evaporator-fan ON delay for the next cycle will occur at 25 seconds.) To prevent short-cycling, a 5-second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating. The evaporator-fan OFF delay can also be modified. Once the call for heating has ended, there is a 10-minute period during which the modification can occur. If the limit switch trips during this period, the evaporator-fan OFF delay will increase by 15 seconds on the next cycle. A maximum of 9 trips can occur, extending the evaporator-fan OFF delay to 180 seconds. To restore the original default value, reset the power to the unit. TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting heating selector lever below room temperature will shut unit off temporarily until space temperature falls below thermostat setting. 35 SERVICE If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second-stage cooling. Compressor no. 1 and the condenser fan will be energized and the position of the economizer damper will be determined by the supply-air temperature. Compressor no. 2 is locked out. When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be determined by the supply-air temperature. After a 30-second delay, the IFM shuts off. If the thermostat fan selector switch is in the ON position, the IFM will run continuously. COOLING UNITS WITH ECONOMI$ER — When the OAT is above the ECON SP set point and the room thermostat calls for Stage 1 cooling (R to G + Y1), the indoor fan motor (IFM) is energized and the EconoMi$er damper modulates to minimum position. The compressor contactor is energized to start the compressor and outdoor-fan motor (OFM). After the thermostat is satisfied, the damper modulates to the fully closed position when the IFM is deenergized. When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling (R to G + Y1), the EconoMi$er modulates to the minimum position when the IFM is energized. The EconoMi$er provides Stage 1 of cooling by modulating the return and outdoor air dampers to maintain a 13 C (55 F) supply air set point. If the supply-air temperature (SAT) is greater than 14 C (57 F), the EconoMi$er modulates open, allowing a greater amount of outdoor air to enter the unit. If the SAT drops below 12 C (53 F), the outdoor air damper modulates closed to reduce the amount of outdoor air. When the SAT is between 12 C (53 F) and 14 C (57 F), the EconoMi$er maintains its position. If outdoor air alone cannot satisfy the cooling requirements of the conditioned space, and the OAT is above the MECH CLG LOCKOUT set point, the EconoMi$er integrates free cooling with mechanical cooling. This is accomplished by the strategies below. NOTE: Compressors have a two-minute Minimum On, Minimum Off, and interstage delay timer. 1. If Y1 is energized, and the room thermostat calls for Y2 (2-stage thermostat), the compressor and OFM are energized. The position of the EconoMi$er damper is maintained at its current value. 2. If Y1 is energized for more than 20 minutes, and Y2 is not energized (whether or not a 2-stage thermostat is used), the compressor and OFM are energized. The position of the EconoMi$er damper is maintained at its current value. 3. If Y1 is energized, and compressor no. 1 is already energized (see Step 2) and the room thermostat calls for Y2, compressor no. 1 continues to operate. If Y2 remains energized for more than 20 minutes, compressor no. 2 is energized. NOTE: Compressor no. 2 cannot be energized unless there is a signal for Y2 from the space thermostat. 4. If compressor no. 2 is energized, and the Y2 signal from the thermostat is satisfied, compressors 1 and 2 are deenergized. Re-asserting Y2 will start compressor no. 1 and (after a 20-minute interstage delay) compressor no. 2. 5. If compressor no. 1 is energized and the thermostat is satisfied, compressor no. 1, the OFM, and IFM are deenergized and the EconoMi$er modulates closed. When the OAT is below the MECH CLG LOCKOUT set point, the compressors remain off. When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts. Cleaning — Inspect unit interior at the beginning of each heating and cooling season or more frequently as operating conditions require. EVAPORATOR COIL — Clean coil as required. Inspect coil at beginning of heating and cooling seasons. 1. Turn unit power off. Remove evaporator coil access panel. 2. If economizer is installed, remove economizer by disconnecting Molex plug and removing economizer mounting screws. Refer to Accessory Economizer Installation Instructions or Optional Economizer sections on pages 12 and 15 for more details. 3. Remove filters from unit. 4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, backflush toward return-air section to remove foreign material. Caution should be taken as to not overflow the evaporator drain condensate pan. 5. Flush condensate pan after completion. 6. Reinstall economizer and filters. 7. Reconnect wiring. 8. Replace access panels. CONDENSER COIL — Inspect coil monthly. Clean condenser coil annually, and as required by location and outdoorair conditions. One-Row Coils — Wash coil with commercial cleaner. Clean outer surfaces with a stiff brush in the normal manner. It is not necessary to remove top panel. 2-Row Coils — Clean coil as follows: 1. Turn off unit power. 2. Remove top panel screws on condenser end of unit. 3. Remove condenser coil corner post. See Fig. 45. To hold top panel open, place coil corner post between top panel and center post. See Fig. 46. 4. Remove screws securing coil to center post. 5. Remove fastener holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 47. 6. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 7. Secure inner and outer coil rows together with a fieldsupplied fastener. 8. Reposition the outer coil section and remove the coil corner post from between the top panel and center post. 9. Reinstall the coil corner post and replace all screws. CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against freeze-up. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters. BELTS — Adjust belt tension and pulley alignment at least twice a year or more frequently as operating conditions require. Refer to Step 9 — Adjust Evaporator for Fan Speed for procedures. 36 Lubrication COMPRESSORS — Each compressor is charged with the correct amount of oil at the factory. FAN-MOTOR BEARINGS — Fan-motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser- or evaporator-fan motors is required. Condenser-Fan Adjustment (Fig. 48) 1. Shut off unit power supply and tag disconnect. 2. Remove condenser-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. 3. Adjust fan height as shown in Fig. 48. 4. Tighten setscrews and replace condenser-fan assembly. Fig. 45 — Cleaning Condenser Coil 48TF UNIT VOLTAGE 400 V FAN HEIGHT “A” (in.) 89 (3.50) Fig. 48 — Condenser-Fan Adjustment Manual Outdoor-Air Damper — If outdoor-air damper blade is required, see Manual Outdoor-Air Damper section on page 12. Economizer Adjustment — Refer to Optional Durablade Economizer section on page 14. Condenser Coil Grille — Condenser coil grille is shipped factory-installed. No adjustments are required. Fig. 46 — Propping Up Top Panel Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate (also refer to Tables 1A and 1B). Refer to Carrier GTAC 2-5 Charging, Recovery, recycling, and reclamation training manual and the following procedures. Unit panels must be in place when unit is operating during charging procedure. NO CHARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Tables 1A and 1B). LOW CHARGE COOLING — Using the Cooling Charging Charts, Fig. 49-51 vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from the type normally used. The charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit. TO USE COOLING CHARGING CHARTS — Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully reclaim some of the charge. Recheck the suction pressure as charge is adjusted. Example (Fig. 51, Circuit 1): Outdoor Temperature. . . . . . . . . . . . . . . . . . . . . . . . .13 C (55 F) Suction Pressure. . . . . . . . . . . . . . . . . . . . . . . .483 kPa (70 psig) Suction Temperature should be. . . . . . . . . . . . . . . . .23 C (74 F) (Suction temperature may vary ± 3 C [5 F].) Fig. 47 — Separating Coil Sections 37 Fig. 49 — Cooling Charging Charts, 48TF008 Units Fig. 50 — Cooling Charging Charts, 48TF012 Units 38 CIRCUIT NO. 2 CIRCUIT NO. 1 Fig. 51 — Cooling Charging Chart; 48TF014 Units Flue Gas Passageways — To inspect the flue collector box and upper areas of the heat exchanger: 1. Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section below. 2. Remove the flue cover to inspect the heat exchanger. 3. Clean all surfaces as required using a wire brush. problems when the power supply is interrupted. When a break in power occurs, the module will be reset (resulting in a loss of fault history) and the indoor (evaporator) fan ON/OFF times will be reset. For additional information, refer to the Start-Up, Heating section on page 34. The LED error code can be observed through the viewport. During servicing refer to the label on the control box cover or Table 25 for an explanation of LED error code descriptions. If lockout occurs, unit may be adjusted by interrupting power supply to unit for at least 5 seconds. Combustion-Air Blower — Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bimonthly to determine proper cleaning frequency. To inspect blower wheel, shine a flashlight into draft hood opening. If cleaning is required, remove motor and wheel as follows: 1. Slide burner access panel out. 2. Remove the 6 screws that attach induced-draft motor housing to vestibule plate (Fig. 52). 3. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with Steps 4 and 5. 4. To remove blower from the motor shaft, remove 2 setscrews. 5. To remove motor, remove the 4 screws that hold blower housing to mounting plate. Remove the motor cooling fan by removing one setscrew. Then remove nuts that hold motor to mounting plate. 6. To reinstall, reverse the procedure outlined above. Table 25 — LED Error Code Description* LED INDICATION ON OFF 1 Flash† 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes** ERROR CODE DESCRIPTION Normal Operation Hardware Failure Evaporator Fan On/Off Delay Modified Limit Switch Fault Flame Sense Fault 4 Consecutive Limit Switch Faults Ignition Lockout Fault Induced-Draft Motor Fault Rollout Switch Fault Internal Control Fault Temporary 1 hour automatic reset fault LEGEND LED — Light-Emitting Diode *A 3-second pause exists between LED error code flashes. If more than one error code exists, all applicable codes will be displayed in numerical sequence. †Indicates a code that is not an error. The unit will continue to operate when this code is displayed. **Indicates internal processor fault and will reset itself in 1 hour. Limit Switch — Remove blower access panel (Fig. 6). Limit switch is located on the fan deck. Burner Ignition — Unit is equipped with a direct spark ignition 100% lockout system. Integrated Gas Unit Controller (IGC) is located in the control box (Fig. 11). Module contains a self-diagnostic LED (light-emitting diode). A single LED on the IGC provides a visual display of operational or sequential IMPORTANT: Refer to Troubleshooting Tables 26-30 for additional information. 39 Main Burners — At the beginning of each heating season, inspect for deterioration, blockage due to corrosion or other causes. Observe the main burner flames and replace burners if necessary. INDUCEDDRAFT MOTOR MOUNTING PLATE ROLLOUT SWITCH When working on gas train, do not hit or plug orifice spuds. BURNER SECTION REMOVAL AND REPLACEMENT OF GAS TRAIN (Fig. 52 and 53) 1. Shut off manual gas valve. 2. Shut off power to unit and tag disconnect. 3. Slide out burner section side panel (not shown). 4. Disconnect gas piping at unit gas valve. 5. Remove wires connected to gas valve. Mark each wire. 6. Remove wires from ignitor and sensor wires at the Integrated Gas Unit Controller (IGC). 7. Remove the 2 screws that attach the burner rack to the vestibule plate. 8. Slide the burner tray out of the unit (Fig. 53). 9. To reinstall, reverse the procedure outlined above. CLEANING AND ADJUSTMENT 1. Remove burner rack from unit as described in Removal and Replacement of Gas Train section on this page. 2. Inspect burners; if dirty, remove burners from rack. 3. Using a soft brush, clean burners and cross-over port as required. 4. Adjust spark gap. See Fig. 54. 5. Reinstall burners on rack. 6. Reinstall burner rack as described in Removal and Replacement of Gas Train section. FLUE EXHAUST VESTIBULE PLATE INDUCEDDRAFT MOTOR BLOWER HOUSING MANIFOLD PRESSURE TAP GAS VALVE Fig. 52 — Burner Section Details Fig. 53 — Burner Tray Details Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request. 40 48TFD008 31.4/21.1 kW INPUT (107,000/72,000 BTUH) 48TFE008, 48TFD012 50.4/31.9 kW INPUT/ (172,000/109,000 BTUH) 48TFD014, 48TFE012, 48TFF008 59.8/39.8 kW INPUT (204,000/136,000 BTUH) 48TFE014, 48TFF012 65.6/43.9 kW INPUT (224,000/150,000 BTUH) NOTE: Dimensions in ( ) are millimeters. Fig. 54 — Spark Gap Adjustment 41 TROUBLESHOOTING Table 26 — LED Error Code Service Analysis PROBLEM Hardware failure. (LED OFF) CAUSE Loss of power to control module (IGC). REMEDY Check 5- amp fuse on IGC, power to unit, 24-v circuit breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v transformer. If the overload trips, allow 10 minutes for automatic reset. High temperature limit switch is open. Check the operation of the indoor (evaporator) fan motor. Limit switch fault. Ensure that the supply-air temperature rise is in accordance with (LED 2 flashes) the range on the unit nameplate. The IGC sensed flame that should not be Reset unit. If problem persists, replace control board. Flame sense fault. present. (LED 3 flashes) Check operation of indoor (evaporator) fan motor and that supply-air 4 consecutive limit switch trips. Inadequate airflow to unit. temperature rise agrees with range on unit nameplate information. (LED 4 flashes) Unit unsuccessfully attempted ignition for Check ignitor and flame sensor electrode spacing, gaps, etc. Ignition lockout. 15 minutes. Ensure that flame sense and ignition wires are properly termi(LED 5 flashes) nated. Verify that unit is obtaining proper amount of gas. IGC does not sense that induced-draft Check for proper voltage. If motor is operating, check the Induced-draft motor fault. motor is operating. speed sensor plug/IGC Terminal J2 connection. Proper (LED 6 flashes) connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black. Rollout switch has opened. Rollout switch will automatically reset, but IGC will continue to Rollout switch fault. lock out unit. Check gas valve operation. Ensure that induced(LED 7 flashes) draft blower wheel is properly secured to motor shaft. Reset unit at unit disconnect. Microprocessor has sensed an error in If error code is not cleared by resetting unit power, replace the Internal control fault. the software or hardware. IGC. (LED 8 flashes) Processor will be reset after 1 hour. Temporary 1 hour automatic reset Stray radio frequency signals in ?? fault. (LED 9 flashes) LEGEND IGC — Integrated Gas Unit Controller LED — Light-Emitting Diode IMPORTANT: Refer to Table 28 — Heating Service Troubleshooting for additional troubleshooting information. If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board. The IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken. 42 Table 27 — Cooling Service Troubleshooting PROBLEM Compressor and condenser fan will not start. Compressor will not start but condenser fan runs. Compressor cycles (other than normally satisfying thermostat). Compressor operates continuously. Excessive head pressure. Head pressure too low. Excessive suction pressure. Suction pressure too low. Compressor no. 2 will not run. Compressor makes excessive noise (48TF014 scroll only). CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Faulty wiring or loose connections in compressor circuit. Compressor motor burned out, seized, or internal overload open. Defective run/start capacitor, overload, or start relay. One leg of 3-phase power dead. Refrigerant overcharge or undercharge. Defective compressor. Insufficient line voltage. Blocked condenser. Defective run/start capacitor, overload, or start relay. Defective thermostat. Faulty condenser-fan motor or capacitor. Restriction in refrigerant system. Dirty air filter. Unit undersized for load. Thermostat set too low. Low refrigerant charge. Leaking valves in compressor. Air in system. Condenser coil dirty or restricted. Dirty air filter. Dirty condenser coil. Refrigerant overcharged. Air in system. Condenser air restricted or air short-cycling. Low refrigerant charge. Compressor valves leaking. Restriction in liquid tube. High heat load. Compressor valves leaking. Refrigerant overcharged. Dirty air filter. Low refrigerant charge. Metering device or low side restricted. Insufficient evaporator airflow. Temperature too low in conditioned area. Field-installed filter drier restricted. Unit in economizer mode. Compressor rotating in wrong direction. 43 REMEDY Call power company. Replace fuse or reset circuit breaker. Replace component. Determine cause and correct. Check wiring diagram and rewire correctly. Lower thermostat setting below room temperature. Check wiring and repair or replace. Determine cause. Replace compressor. Determine cause and replace. Replace fuse or reset circuit breaker. Determine cause. Recover refrigerant, evacuate system, and recharge to nameplate. Replace and determine cause. Determine cause and correct. Determine cause and correct. Determine cause and replace. Replace thermostat. Replace. Locate restriction and remove. Replace filter. Decrease load or increase unit size. Reset thermostat. Locate leak, repair, and recharge. Replace compressor. Recover refrigerant, evacuate system, and recharge. Clean coil or remove restriction. Replace filter. Clean coil. Remove excess refrigerant. Recover refrigerant, evacuate system, and recharge. Determine cause and correct. Check for leaks, repair, and recharge. Replace compressor. Remove restriction. Check for source and eliminate. Replace compressor. Recover excess refrigerant. Replace filter. Check for leaks, repair, and recharge. Remove source of restriction. Increase air quantity. Check filter and replace if necessary. Reset thermostat. Replace. Proper operation; no remedy necessary. Reverse the 3-phase power load as described in Start-Up, Compressor Rotation section on page 34. Table 28 — Heating Service Troubleshooting PROBLEM Burners will not ignite. Inadequate heating. Poor flame characteristics. Burners will not turn off. CAUSE Misaligned spark electrodes. REMEDY Check flame ignition and sensor electrode positioning. Adjust as needed. No gas at main burners. Check gas line for air purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes before attempting to relight unit. Check gas valve. Water in gas line. Drain water and install drip leg to trap water. No power to furnace. Check power supply, fuses, wiring, and circuit breaker. No 24 v power supply to control circuit. Check transformer. Transformers with internal overcurrent protection require a cool down period before resetting. Miswired or loose connections. Check all wiring and wirenut connections. Burned-out heat anticipator in thermostat. Replace thermostat. Broken thermostat wires. Run continuity check. Replace wires, if necessary. Dirty air filter. Clean or replace filter as necessary. Gas input to unit too low. Check gas pressure at manifold. Clock gas meter for input. If too low, increase manifold pressure, or replace with correct orifices. Unit undersized for application. Replace with proper unit or add additional unit. Restricted airflow. Clean filter, replace filter, or remove any restrictions. Blower speed too low. Use high speed tap, increase fan speed, or install optional blower, as suitable for individual units. Limit switch cycles main burners. Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. Too much outdoor air. Adjust minimum position. Check economizer operation. Incomplete combustion (lack of Check all screws around flue outlets and burner compartment. combustion air) results in: Tighten as necessary. Aldehyde odors, CO, sooting flame, or floating flame. Cracked heat exchanger. Overfired unit — reduce input, change orifices, or adjust gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Unit is locked into Heating mode for a Wait until mandatory one minute time period has one minute minimum. elapsed or power to unit. Table 29 — EconoMi$er Troubleshooting PROBLEM Damper Does Not Open POTENTIAL CAUSE Indoor (Evaporator) Fan is Off REMEDY Check to ensure that 24 vac is present at Terminal C1 (Common Power) on the IFC (Indoor [Evaporator] Fan Contactor) or that 24 vac is present at the IFO (Indoor [Evaporator] Fan On) terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). Check proper thermostat connection to G on the connection board. Check to ensure that 24 vac is present across Terminals 24 VAC and 24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram). If 24 vac is present, STATUS light should be on constantly. If IFM is on, check to ensure 24 vac is present on G Terminal of the EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram). If STATUS light is flashing one flash, the EconoMi$er controller is experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller. If STATUS light is flashing two flashes, the EconoMi$er controller senses the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1. Check the wiring between the EconoMi$er controller and the actuator. Hold CONFIG button between 3 and 10 seconds to verify the actuator’s operation. (This process takes 3 minutes to complete.) Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting. Set at correct value. See Table 4. No Power to EconoMi$er Controller No Power to G Terminal Controller Fault Thermostat Fault Actuator Fault EconoMi$er Operation Limited to Minimum Position Minimum Position Set Incorrectly EconoMi$er Changeover Set Point Set Too High or Too Low Supply Air Temperature Sensor Faulty If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is faulty. Check wiring or replace sensor. If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is faulty. Check wiring or replace sensor. The supply-air temperature is less than 7 C (45 F), causing the minimum position to be decreased. Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct, EconoMi$er is operating correctly. If a CO2 sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to the Start-Up instructions. EconoMi$er is operating correctly. Check to ensure the damper is not blocked. Outdoor Air Temperature Sensor Faulty Damper Position Less than Minimum Position Set Point Damper Does Not Return to Minimum Position Damper Does Not Close on Power Loss Supply Air Low Limit Strategy Controlling CO2 Ventilation Strategy Controlling Damper Travel is Restricted LEGEND IFM — Indoor Fan Motor PL — Plug 44 Table 30 — Durablade Economizer Troubleshooting PROBLEM Damper does not open. Economizer operation limited to minimum position. Damper does not close. Economizer damper does not close on power loss. C1 EC IFC IFO — — — — CAUSE Indoor (evaporator) fan is off. REMEDY 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Check proper thermostat connection to G on the connection board. No power to economizer motor. 1. Check that SW3 is properly making contact with the damper blade. Check that SW1 is in the NC (normally closed) position. 2. Check diode D1. If diode is not functioning properly, replace D1. 3. Confirm that the economizer control board is grounded properly at PL6-4 (brown wire) and at brown terminal of the economizer control board (brown wire). The economizer motor must also be grounded properly at the negative motor terminal (brown wire). 4. Verify SW1 and SW3 are working and wired properly (see unit label diagram). 5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If 24 vac not present, check unit wiring (see unit label diagram). If 24 vac is found in both places, check for 24 vac at the yellow terminal of the economizer control board (yellow wire). If 24 vac power is not present, replace the economizer control board. Economizer motor failure. If the indoor (evaporator) fan and economizer motor are energized, verify that there is a minimum of 18 vdc at the positive motor terminal. If the motor is not operating, replace the motor. OAT or EC set too high. 1. Set at correct temperature (1.7 C [3 F] below indoor space temperature). 2. Check OAT or EC by setting above outdoor temperature or humidity level. If the OAT or EC switches do not close, replace OAT or EC. Verify economizer control board is 1. Perform the following tests when OAT or EC is closed, Y1 is called correctly wired and works properly. for and damper is at minimum position. Confirm 24 vac on gray terminal of the economizer control board (gray wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Verify that SW1 and SW3 are wired correctly and working properly (see unit label diagram). 3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not present, check wiring (see unit wiring label diagram). 4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace economizer control board. Check SAT. 1. After verifying that the OAT and EC settings and the economizer control board wiring are correct, check to ensure that the 24 vac terminal of the SAT has 24 vac (white wire). If OAT, EC, and control board are functioning and wired properly and no 24 vac exists, check wiring (see unit label diagram). 2. If supply-air temperature is greater than 14 C (57 F), 24 vac should be found at terminal T2 on the SAT (pink wire). If 24 vac is not present, replace SAT. Incorrect wiring of economizer. 1. Verify that SW2 and SW4 are wired and working properly (see unit label diagram). 2. Check diode D2. If diode is not functioning properly, replace D2. Verify economizer control board is 1. After verifying that the wiring is correct, modulate the damper to the functioning properly. minimum position. Remove the call for G (evaporator fan). 2. If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac is not present, check wiring (see unit label diagram). 3. If damper still does not move, check for 24 vac at blue terminal of economizer control board (blue wire). If 24 vac is not present, replace the economizer circuit board. Check SAT. 1. After verifying that the wiring is correct and the economizer control board is functioning properly, place the OAT or EC switch in the closed position. Place a call for Y1 and open the damper to the fully open position. Confirm that the 24 vac terminal of the SAT has 24 vac (white wire). If 24 vac is not present, check wiring (see unit label diagram). 2. If supply-air temperature is less than 11 C (52 F), 24 vac should be found at terminal T1 on the SAT (violet wire). If 24 vac not found, replace SAT. Economizer motor failure. If economizer control board and SAT are functioning properly, verify that there is a minimum of 18 vdc at the positive motor terminal. If a minimum if 18 vdc is present and the motor is still not operating, replace the motor. Verify that close-on-power-loss and 1. Check voltage potential across batteries. If lower than 14 vdc, economizer control board are funcreplace close-on-power-loss power supply (9-v alkaline batteries). It tioning properly. is recommended that you check this emergency power supply on a regular basis or whenever the filters are changed. 2. If the close-on-power-loss and economizer control board are functioning properly, check for 14 vdc or higher at the blue terminal of the economizer control board (blue wire) when power is disconnected from unit. If 14 vdc is not present, replace the control board. LEGEND Common Power Enthalpy Control Indoor (Evaporator) Fan Contactor Indoor (Evaporator) Fan On OAT PL SAT SW — — — — Outdoor-Air Thermostat Plug Supply-Air Thermostat Economizer Position Switch 45 LEGEND — Adjustable Heat Anticipator — Blower Relay — Contactor, Compressor — Capacitor — Circuit Breaker — Cooling Compensator — Compressor Motor — Combustion Relay — Diode — Enthalpy Control — Economizer — Emergency Power Supply (9-Volt Battery) EQUIP — Equipment ER — Economizer Relay FPT — Freeze-Up Protection Thermostat FSS — Filter Status Sensor GND — Ground GVR — Gas Valve Relay HPS — High-Pressure Switch HS — Hall-Effect Sensor I — Ignitor IDM — Induced-Draft Motor IFC — Indoor-Fan Contactor IFM — Indoor Fan Motor IGC — Integrated Gas Unit Controller LPS — Low-Pressure Switch LS — Limit Switch MGV — Main Gas Valve MTR — Motor OAT — Outdoor-Air Thermostat OFM — Outdoor-Fan Motor P — Plug PL — Plug Assembly QT — Quadruple Terminal R — Relay RS — Rollout Switch SAT — Supply-Air Thermostat SEN — Sensor SW1 — Switch Fully Open SW2 — Switch Fully Closed SW3 — Switch Min. Vent Position SW4 — Switch Max. Vent Position TC — Thermostat-Cooling TH — Thermostat-Heating TRAN — Transformer AHA BR C CAP CB CC COMP CR D EC ECON EPS Field Splice Marked Wire Terminal (Marked) Terminal (Unmarked) Terminal Block Splice Splice (Marked) Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indicate common potential only. Not to represent wiring. NOTES: 1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its equivalent. 2. Three-phase motors are protected under primary single phasing conditions. Thermostat: HH07AT170, 172, 174 and P272-2783 Subbase: HH93AZ176, 178 and P272-1882, 1883 3. Set heat anticipator for first stage at 0.14 amp, second stage at 0.2 amp, except for 008 low heat, set both first and second stage at 0.14 amp. 4. Use copper conductors only. Fig. 55 — Typical Unit Wiring Schematic Copyright 2001 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg 46 1-01 Replaces: New Book 1 4 Tab 1a 6a I. PRELIMINARY INFORMATION MODEL NO.:________________________________ SERIAL NO.: ___________________________________ DATE:______________________________________ TECHNICIAN: __________________________________ JOB LOCATION: _______________________________ II. PRE-START-UP (insert checkmark in box as each item is completed) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK GAS PIPING FOR LEAKS CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS AND DRIVE BELTS TENSION. III. START-UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS COMPRESSOR AMPS INDOOR-FAN AMPS L1-L2 L1 L1 L1 L2-L3 L2 L2 L2 L3-L1 L3 L3 L3 TEMPERATURES OUTDOOR-AIR TEMPERATURE RETURN-AIR TEMPERATURE COOLING SUPPLY AIR GAS HEAT SUPPLY AIR DB DB DB DB WB PRESSURES GAS INLET PRESSURE kPa (IN. WG) GAS MANIFOLD PRESSURE kPa (IN. WG) (HI FIRE) REFRIGERANT SUCTION Pa (PSIG) — CIRCUIT NO. 1 Pa (PSIG) — CIRCUIT NO. 2 REFRIGERANT DISCHARGE Pa (PSIG) — CIRCUIT NO. 1 Pa (PSIG) — CIRCUIT NO. 2 VERIFY REFRIGERANT CHARGE USING CHARGING TABLES VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION (014 ONLY) Copyright 2001 Carrier Corporation Book Tab Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 1 4 Catalog No. 004-816 Printed in U.S.A. Form 48TF-C1SI Pg CL-1 1-01 Replaces: New 1a 6a - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE START-UP CHECKLIST (Remove and Store in Job File)
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Create Date : 2001:04:30 12:08:14Z Creator Tool : ADOBEPS4.DRV Version 4.20 Modify Date : 2005:11:11 18:52:03-05:00 Metadata Date : 2005:11:11 18:52:03-05:00 Format : application/pdf Creator : Carrier Corporation Title : Description : Subject : Producer : Acrobat Distiller 4.0 for Windows Keywords : Document ID : uuid:cb59f92e-160e-4122-91cf-acd5f95b6c33 Instance ID : uuid:1ed40813-7319-4c67-a5a9-5bb49bb91292 Page Count : 48 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools