Product
Data

50AH
Horizontal Indoor
Single-Package
Cooling Units
2 to 5 Nominal Tons

Single Package Cooling Units
Featuring:
• compact design
• flexibility
• easy maintenance
• high quality and reliability
• quiet and efficient scroll compressor
technology

Features/Benefits
All in one package — high
cooling efficiency,
installation convenience,
ease of accessibility for timesaving maintenance.
Space and cost saving design
Model 50AH is specifically designed to
provide the building owner with truly outof-sight cooling, because it installs inside
the ceiling. That’s why we call it the Carrier ROOMTOP® unit. The compact design and low silhouette enable it to fit
easily and securely above the conditioned
space. Single-package construction
makes it easy to install with minimal time
and cost.

Application flexibility
If desired for particular applications, the
unit can also be installed as a split system
with the condenser section mounted horizontally. Centrifugal fans permit ducting
of both evaporator and condenser air.

Quiet operation
Commercial end users appreciate the extra comfort of quiet operation. Carrier
engineers met the challenge by specifying heavy insulation, vibration-resistant
construction and operating components
that function at low noise levels, all of
which keep system sound at a minimum
level.

Easy maintenance
When it comes to maintenance, the
50AH rates high in accessibility. Indoor
Copyright 2002 Carrier Corporation

Form 50AH-6PD

location is ideal for the maintenance
technician, and five access panels, easily
removed, provide quick and convenient
access to all components when needed.
As an added plus, all required service/
maintenance access can be from one
side allowing the unit to be located
against a wall or ceiling plenum obstruction, an obvious space-saving idea.

Carrier quality and reliability

Scroll compressor technology

The Carrier 50AH ROOMTOP® units
have much to offer the cost- and
efficiency-conscious commercial owner.
Every unit is thoroughly run tested at the
factory and equipped with safety controls
designed to monitor and protect over the
life of the unit.

Scroll compressors are designed for high
efficiency and are internally spring
mounted to minimize vibration noise.
Each compressor is hermetically sealed
against contamination to promote longer
life and dependable operation. Scroll
compressors are standard on all units.

Table of contents
Page

Quality Assurance

Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ARI Capacity Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11,12
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15

ISO

23
25

®

90
01:2000 #A

Model number nomenclature
50AH

–

048 –

M

–

5

4

1

XX

Model Designation –
50AH Horizontal,
Indoor Single-Package
Cooling Unit

FIOP*
Packaging
1 – Domestic
2 – Export

Nominal Tons
048 – 4
024 – 2
060 – 5
036 – 3

Design Revision

Indoor Fan Motor
– – Standard Motor
M – 1.5 hp Optional Motor

Voltage
3 – 230-1-60
5 – 208/230-3-60

6 – 460-3-60

*FIOP — Factory-Installed option, contact your Carrier representative for details.

ARI* capacity ratings
UNIT
50AH
024
036

048

060

V-PH-Hz
230-1-60
230-1-60
208/230-3-60
460-3-60
230-1-60
208/230-3-60
460-3-60
230-1-60
208/230-3-60
460-3-60

TOTAL
kW
2.56

NET TOTAL
COOLING CAP. (Btuh)
24,800

NOMINAL
CFM
800

4.3

36,000

1200

5.63

49,500

1600

6.9

58,500

2000

LEGEND
dB
— Decibels
EER — Energy Efficiency Ratio
SEER — Seasonal Energy Efficiency Ratio
TDR — Time-Delay Relay
*Air-conditioning and Refrigeration Institute.
†TDR is standard.

2

EER

SEER

—
—
8.40
8.40
—
8.80
8.80
—
8.50
8.50

—
10.00
—
—
—
—
—
9.70
—
—

NOTES:
1. Ratings are at zero condenser air static and rated in
accordance with ARI Standard 210.
NET CAPACITY (Btuh)
2. EER =
TOTAL WATTS

SEER
(with TDR)
10.50†
10.00
—
—
10.00†
—
—
10.00
—
—

SOUND RATING
(dB)
78
82

82

82

Physical data
UNIT 50AH
SHIPPING WEIGHT (lb)*
OPERATING WEIGHT (lb)
Base Unit, Evaporator/Condenser Section
REFRIGERANT TYPE
Operating Charge (lb)†
COMPRESSOR — TYPE
Quantity...Model
Oil (oz)
HPS Setting (psig)
Cutout
Reset
LPS Setting (psig)
Cutout
Reset
CONDENSATE DRAIN CONNECTION
Size (in.)...Type
CONDENSER COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
CONDENSER FAN
Nominal Cfm
Maximum Rpm
Blower Size (in.)
Pulley Pitch Diameter (in.)
Blower
Motor (Variable)
Motor Hp
Motor Rpm
EVAPORATOR COIL
Size (L x H) (in.)
Number of Rows...Fins/in.
EVAPORATOR AIR FAN (Standard)
Nominal Cfm
Max Rpm
Blower Size (in.)
Motor Hp (Rpm)
EVAPORATOR AIR FAN (Optional)
Nominal Cfm
Max Rpm
Blower Size (in.)
Motor Hp
Motor Rpm
Pulley Pitch Diameter (in.)
Blower
Motor (Variable)
INDOOR-AIR FILTERS
Number...Size (in.)
INTERCONNECTING TUBING SIZE (in.)††
Hot Gas
Liquid

HPS
LPS

024
560

036
590

450, 193/256

480, 206/274

048
690

060
700

580, 250/330

590, 254/336

7.4

7.6

(1)...SR48
70

(1)...ZR57
54

R-22
5.4

5.5
Scroll

(1)...ZR23
24

(1)...ZR34
42
426 ± 7
320 ± 20
27 ± 4
67 ± 7

3/4...FPT
Copper Tubes — Aluminum Fins
40 x 16
40 x 22
4...17
4...13.6
Centrifugal — Belt Drive
1350
2250
1500
12 x 9

40 x 15
4...13.6
Centrifugal — Direct Drive
1350
1100
12 x 6
None
None
1/2
825

5.0
6.0
2.4-3.4
1.9-2.9
3/4
1
1725
1725
Copper Tubes — Aluminum Fins
34 x 16
4...15
Centrifugal — Direct Drive
1200
1600
1150
10 x 6
1/2 (1075)

34 x 15
4...14.4
800
1100
10 x 5
1/6 (850)

LEGEND
— High-Pressure Switch
— Low-Pressure Switch

*Shipping weights include base unit plus packaging.
†If components are to be split, additional refrigerant will be needed.
**Two-speed motor.
††Use Type L copper only.

2450

6.0
2.4-3.4
11/2
1725
34 x 22
4...14.4
2000
900/1050**
10 x 6
3/4 (1050)
Centrifugal Belt Drive

1600

2000
1300
10 x 8
11/2
1725

Not
Available

4.2
2.4-3.4
Factory-Supplied Cleanable Type
1...14 x 34 x 1

1...21 x 34 x 1

1/2
3/8

1/2
3/8

1/2
3/8

1/2
3/8

NOTE: If components are to be split, the maximum length of refrigerant tubing to be
used is 50 equivalent ft, assuming components will be installed in same horizontal plane.
If components are not to be installed in same horizontal plane, contact your Carrier representative for more information. For additional piping information, refer to Carrier
System Design Manual, Part 3.

NOTE: Fasten threaded rods through holes in end frames. Use 2 rods
on each side of unit for a total of 4.

All panels must be in place when rigging.

OPERATING WEIGHT DISTRIBUTION AND
CENTER OF GRAVITY
UNIT
50AH
024
036
048
060

1
93/42
95/43
112/51
114/52

WEIGHT (lb/kg)
OF CORNER
2
3
108/49 139/63
113/51 148/67
143/65 183/83
143/65 186/84

4
120/54
124/56
142/64
147/67

DIMENSIONS
(ft-in./mm)
A
B
2-5 /737 2-15/8/651
2-43/4/730 2-2 /660
2-5 /737 2-3 /686
2-43/4/730 2-23/4/679

3

Field-installed accessories
Thermostat and subbase — Attractive wall-mounted
24-v accessory provides precise temperature control.
Automatic and Manual changeover models available. A
thermostat subbase is available that works with CycleLOC™ circuitry. If a safety device trips, compressor locks
out and subbase warning light (LK OUT) alerts occupant.
Three models available: One stage cool/two stage heat;
two stage cool/two stage heat; one stage cool/one stage
heat.
Time Guard® II circuit (standard on single-phase
units) — Time Guard II device prevents short cycling of
compressor if thermostat is rapidly changed; automatically
prevents compressor from restarting for 5 minutes after
shutdown.
Electric heaters — A wide range of models is available
from 5 to 30 kW, 208-, 240- and 480-v, single- and 3-ph
units. The heaters mount easily on 50AH discharge opening. The heater control box is accessible from the bottom
of heater.

88EN ELECTRIC HEAT MODULE
ACCESSORY

DIMENSIONS (in.)
UNIT
50AH

A

024,036 131/2
048,060

4

24

B

C

D

DUCT
OPENING

16

21/2

81/2

71/8 x 14

213/4

3

19

71/8 x 207/8

Condensate pump — The condensate pump is used
when the distance and slope to the nearest drain is far
enough to prevent the natural drainage of unit. The pump
is mounted remotely from the unit and includes a signal
light (field-installed) which illuminates when the reservoir
rises beyond a certain level. The unit automatically shuts
down when this reservoir level is achieved.
Head pressure control damper — This accessory is
duct mounted and allows unit to mechanically cool down to
0° F.
Damper dimensions fit 024, 036 sizes.
NOTE: For use with 048 and 060 size units, ductwork
from unit to damper must be reduced in size to fit damper
dimensions.
Vibration isolators — Package of four isolators used for
dampening any unit vibration so that vibrating sounds are
not transmitted to building structure. Isolators are spring,
ceiling type.

HEAD PRESSURE CONTROL DAMPER (in.)

Base unit dimensions

DIMENSIONS (ft-in.)
UNIT
50AH
024
036
048
060

A

B

2-5
2-43/4
2-5
2-43/4

2-15/8
2-2
2-3
2-23/4

C
1- 53/4
1- 53/4
1-115/8
1-115/8

D

E

1-2
1-2
1-87/8
1-87/8

1-1
1-1
1-77/8
1-77/8

UNIT COMPONENT LOCATIONS

5

Selection procedure (with example)
I Determine cooling requirements at design
conditions.
Given:
Gross Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . .39,000 Btuh
Sensible Heat Capacity (SHC) . . . . . .30,500 Btuh
Temperature of Air Entering Condenser . . . . .95 F
Temperature of Air Entering
Evaporator . . . . . . . . . . . . . . . 80 F edb/67 F ewb
Evaporator Air Quantity. . . . . . . . . . . . 1,200 cfm
External Static Pressure:
Condenser . . . . . . . . . . . . . . . . . . .0.50 in. wg
Evaporator (includes static pressure
drop of factory-supplied filter
of 0.06 in. wg) . . . . . . . . . . . . . . .0.20 in. wg
II Select unit based upon required cooling
capacity.
Enter cooling capacity table at temperature of air
entering condenser of 95 F. The 50AH036 unit at

1200 cfm and 67 F ewb will provide a Total
Capacity (TC) of 44,200 Btuh and a Sensible Heat
Capacity (SHC) of 31,300 Btuh. Since the entering
air is 80 F edb, an SHC correction is not required.
III Determine evaporator fan performance.
Enter Evaporator Fan Performance table at
1200 cfm and 50AH036 data. The external static
pressure shown (0.23 in. wg) will exceed the
0.20 in. wg required. The fan motor will require
0.52 kW.
IV Determine condenser fan performance and
motor pulley setting requirements.
Enter Condenser Fan Performance table at
the selected cfm and required static pressure of
0.50 in. wg. The fan motor will require 0.73 kW
and the motor pulley should be set at 2 turns open
at 1350 cfm of condenser air required.
NOTE: Unit 50AH024 contains a direct-drive condenser fan assembly.

Performance data
GROSS COOLING CAPACITIES
50AH024
Temp
Air Ent
Condenser
(F)
TC
85 SHC
kW
TC
95 SHC
kW
TC
105 SHC
kW
TC
115 SHC
kW

50AH036
Evaporator Air Quantity — Cfm/BF
600/0.02
800/0.03
1000/0.04
Evaporator Air Ewb Temp (F)
72
67
62
72
67
62
72
67
62
27.1 25.3 23.0 27.7 26.4 24.6 27.8 26.9 25.8
13.5 17.0 20.2 14.7 19.4 23.7 15.6 21.5 25.8
1.64 1.62 1.61 1.65 1.63 1.62 1.65 1.64 1.63
26.6 24.5 20.8 27.4 25.8 22.9 28.0 26.5 25.2
13.4 16.7 19.1 14.7 19.4 22.8 16.0 21.7 25.2
1.85 1.84 1.80 1.86 1.85 1.82 1.87 1.85 1.84
25.8 22.3 18.4 27.1 24.5 21.2 27.7 25.6 23.6
13.1 15.8 17.9 14.7 18.9 21.2 16.2 21.5 23.6
2.09 2.05 1.99 2.11 2.08 2.04 2.12 2.10 2.07
24.6 19.9 16.5 26.1 22.0 19.8 26.8 23.6 22.3
12.7 14.8 16.5 14.4 17.9 19.8 16.0 20.7 22.3
2.36 2.29 2.22 2.39 2.33 2.29 2.39 2.35 2.33

See Legend on page 7.

6

Temp
Air Ent
Condenser
(F)
TC
85 SHC
kW
TC
95 SHC
kW
TC
105 SHC
kW
TC
115 SHC
kW

Evaporator Air Quantity — Cfm/BF
900/0.01
1050/0.01
1200/0.02
Evaporator Air Ewb Temp (F)
72
67
62
72
67
62
72
67
62
45.0 41.1 37.3 45.8 42.3 38.6 46.5 43.4 39.8
22.5 27.7 32.6 23.6 29.9 35.6 24.6 32.0 38.3
3.19 3.07 2.96 3.22 3.11 3.00 3.25 3.14 3.04
43.0 38.8 34.3 44.1 40.1 35.8 45.0 44.2 37.4
21.8 26.8 31.1 23.1 29.1 34.1 24.4 31.3 36.8
3.42 3.28 3.15 3.46 3.33 3.20 3.49 3.37 3.25
40.4 35.8 29.6 41.6 37.1 31.3 42.6 38.2 33.2
20.9 25.6 28.5 22.3 27.9 30.8 23.7 30.2 33.2
3.63 3.48 3.38 3.68 3.53 3.44 3.73 3.58 3.49
37.7 30.6 25.8 38.7 31.6 37.8 39.7 32.8 29.7
19.9 23.3 25.8 21.3 25.5 27.8 22.7 27.8 29.7
3.85 3.71 3.59 3.90 3.76 3.67 3.94 3.80 3.73

Performance data (cont)
GROSS COOLING CAPACITIES (cont)
50AH048

50AH060

Temp
Air Ent
Condenser
(F)
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

85

95

105

115

BF
Ewb
kW
SHC
TC

—
—
—
—
—

1200/0.06
72
56.0
27.8
3.77
54.0
27.1
4.21
51.8
26.3
4.69
49.5
25.5
5.21

67
52.1
34.8
3.68
50.1
34.0
4.11
47.9
33.1
4.58
45.5
32.2
5.09

62
47.9
41.6
3.59
45.7
40.4
4.01
42.3
38.8
4.45
38.6
37.0
4.92

Evaporator Air Quantity Cfm/BF
1600/0.08
Evaporator Air Ewb Temp (F)
57 72 67 62 57 72
44.4 57.7 54.5 50.6 49.6 59.4
44.4 30.2 39.6 48.0 49.6 32.8
3.53 3.81 3.74 3.66 3.64 3.85
42.4 55.7 52.3 48.6 47.3 57.4
42.4 29.6 38.8 47.0 47.3 32.4
3.95 4.25 4.18 4.09 4.07 4.31
40.2 53.6 50.0 45.1 45.0 54.6
40.2 29.0 38.0 44.8 45.0 31.3
4.40 4.75 4.65 4.54 4.53 4.77
37.7 51.2 47.6 41.9 42.1 52.2
37.7 28.3 27.3 41.8 42.1 30.7
4.89 5.27 5.17 5.03 5.03 5.30

Temp
Air Ent
Condenser
(F)

2000/0.10
67
56.0
43.9
3.77
53.8
43.2
4.21
51.4
42.4
4.69
49.1
42.0
5.23

62
52.7
52.5
3.70
51.0
50.9
4.15
48.9
48.9
4.63
45.8
45.8
5.14

57
52.3
52.3
3.69
50.9
50.9
4.15
48.6
48.6
4.63
45.8
45.8
5.14

85

95

105

115

The following formulas may be used:

LEGEND
Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input (kilowatts)
Gross Sensible Heat Capacity (1000 Btuh)
Gross Total Cooling Capacity (1000 Btuh)

tldb = tedb –
tlwb =

NOTES:
1. Performance based on nominal condenser airflow listed in physical data table
on page 3.
2. SHC is based on 80 F db temperature of air entering the coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.

BYPASS
FACTOR
(BF)
.025
.05
.10
.20
.30
.35

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Quantity — Cfm/BF
1500/0.06
2000/0.09
2250/0.10
Evaporator Air Ewb Temp (F)
72
67
62
72
67
62
72
67
62
64.8 58.5 52.9 68.0 61.5 56.3 68.9 62.5 58.0
33.2 41.1 48.5 37.2 47.3 55.7 38.9 50.0 57.7
4.49 4.29 4.13 4.59 4.83 4.22 4.62 4.41 4.27
61.9 55.7 50.2 65.1 58.7 54.0 66.1 59.7 55.8
32.3 40.1 47.3 36.4 46.5 54.0 38.2 49.3 55.8
4.94 4.72 4.57 5.04 4.81 4.67 5.07 4.84 4.72
58.5 52.4 47.2 61.5 55.2 51.4 62.6 56.3 53.3
31.1 38.8 45.8 35.2 45.2 51.4 37.1 48.1 58.2
5.41 5.20 5.04 5.51 5.28 5.16 5.55 5.32 5.22
54.9 49.0 44.1 57.8 51.7 48.7 58.7 52.6 50.4
29.8 37.5 44.0 34.0 43.9 48.7 35.9 46.7 50.4
5.93 5.72 5.56 6.04 5.80 5.70 6.07 5.83 5.75

sensible capacity (Btuh)
1.10 x cfm

Wet-bulb temperature corresponding to enthalpy of air leaving
evaporator col (hlwb).

hlwb = hewb –

total capacity (Btuh)
4.5 x cfm

Where:
hewb = Enthalpy of air entering evaporator coil

ENTERING AIR DRY-BULB TEMPERATURE (F)
78
77
76
75
Under 75
82
83
84
85
Over 85
Correction Factor
1.07
2.12
3.19
4.25
5.32
1.04
2.07
3.11
4.14
5.18
.98
1.96
2.94
3.92
4.90
Use formula
.87
1.74
2.62
3.49
4.36
shown below
.76
1.53
2.29
3.05
3.82
.71
1.42
2.13
2.83
3.54
79
81

Correction Factor = 1.10 x (1 – BF) x db – 80)

EVAPORATOR FAN PERFORMANCE
UNIT SIZE — 50AH
CFM
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

024
ESP
.60
.54
.43
.29
.11
—
—
—
—
—
—
—
—
—
—

036
Fan kW
.20
.22
.24
.26
.29
—
—
—
—
—
—
—
—
—
—

ESP
—
—
—
.69
.57
.42
.23
—
—
—
—
—
—
—
—

048*
Fan kW
—
—
—
.44
.46
.49
.52
—
—
—
—
—
—
—
—

LEGEND
ESP — External Static Pressure (in. wg)
kW — Total Fan Motor Power Input (kilowatts)
*Standard direct drive indoor (evaporator) fan motor (IFM). For optional
belt drive IFM performance, see table on page 8.
NOTES:
1. Above fan performance is based on wet coil and deducted casing
losses, and clean factory-installed permanent cleanable filter.

ESP
—
—
—
—
—
1.10
1.01
.90
.79
.67
.54
.39
.22
.03
—

060*
Fan kW
—
—
—
—
—
.45
.49
.51
.55
.58
.61
.64
.67
.70
—

ESP
—
—
—
—
—
1.11
1.045
.97
.88
.78
.67
.53
.52
.40
.28

Fan kW
—
—
—
—
—
.52
.55
.57
.59
.62
.64
.67
.70
.74
.78

2. Evaporator fans are direct drive (except 048, 060 special order
evaporator-fan motor option). Refer to Belt Drive Evaporator Fan
Performance table on page 8.
3. Interpolation is permissible, do not extrapolate.
4. For units installed with accessory electric heaters, see Electric
Heater Static Pressure Drop table for additional performance losses.

7

Performance data (cont)
BELT DRIVE EVAPORATOR FAN PERFORMANCE
(Special Order Only, Pricing and
ordering on related price pages.)
UNIT SIZE — 50AH
CFM

048
ESP
—
—
—
.81
.72
.63
.55
.47
.42
.34

1800
1850
1900
1950
2000
2050
2100
2150
2200
2250

060
Fan kW
—
—
—
1.03
1.05
1.07
1.08
1.11
1.14
1.17

ESP
—
—
—
—
—
—
1.02
.93
.84
.75

Fan kW
—
—
—
—
—
—
1.17
1.21
1.24
1.27

LEGEND
ESP — External Static Pressure (in. wg)
kW — Total Fan Power Motor Input (kilowatts)
NOTE: Pulley setting must be adjusted to limit cfm to 450 cfm/ton
maximum. Unit operation beyond that limit may result in blow-off and
condensate problems.

CONDENSER FAN PERFORMANCE
UNIT
50AH

024

036

048

060

COND
CFM
1525
1475
1400
1350
1300
1650
1600
1550
1500
1450
1400
1350
1300
2700
2600
2550
2450
2350
2300
2200
3100
3000
2900
2850
2750
2700
2650
2600
2550
2500
2450
2400

0.0
Turns
Note 4
—
—
—
—
2
—
—
3
4
—
5
—
2
—
3
—
—
4
—
3
—
—
4
—
—
—
5
—
—
—
—

0.1
kW
.66
—
—
—
—
.84
—
—
.72
.63
—
.51
—
.90
—
.81
—
—
.68
—
1.34
—
—
1.11
—
—
—
.95
—
—
—
—

Turns
—
Note 4
—
—
—
—
2
—
—
3
4
—
5
—
2
—
3
—
—
4
—
3
—
—
4
—
—
—
—
5
—
—

kW
—
.64
—
—
—
—
.82
—
—
.70
.61
—
.50
—
.87
—
.77
—
—
.66
—
1.32
—
—
1.07
—
—
—
—
.92
—
—

EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.3
0.4
Turns
kW
Turns
kW
Turns
kW
—
—
—
—
—
—
—
—
—
—
—
—
Note 4
.63
—
—
—
—
—
—
Note 4
.62
—
—
—
—
—
—
Note 4
.62
—
—
—
—
—
—
—
—
—
—
—
—
2
.80
—
—
—
—
—
—
2
.78
1
.84
—
—
—
—
2
.76
3
.68
—
—
—
—
—
—
3
.67
—
—
4
.57
—
—
3
.65
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2
.83
1
.89
—
—
—
—
2
.80
1
.86
3
.74
—
—
—
—
—
—
—
—
2
.77
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2
1.39
—
—
3
1.24
—
—
—
—
—
—
—
—
2
1.32
—
—
3
1.17
—
—
—
—
—
—
—
—
4
1.01
—
—
—
—
—
—
—
—
3
1.12
—
—
—
—
—
—
—
—
4
.97
—
—
5
.90
—
—
—
—

LEGEND
kW — Total Fan Motor Power Input (kilowatts)
NOTES:
1. Above fan performance is based upon coil and deducted casing
losses only.
2. External static pressure (ESP) is measured in inches water gage
(in. wg).
3. Interpolation is permissible. Do not extrapolate.
4. Condenser fan on unit size 024 only, is direct drive.

8

0.5
Turns
—
—
—
—
—
—
—
—
—
1
—
2
—
—
—
—
—
—
0
1
—
—
—
—
—
—
—
2
—
—
—
3

kW
—
—
—
—
—
—
—
—
—
.83
—
.73
—
—
—
—
—
—
.90
.82
—
—
—
—
—
—
—
1.26
—
—
—
1.08

0.6
Turns
—
—
—
—
—
—
—
—
—
—
1
—
2
—
—
—
—
—
—
0
—
—
—
—
—
—
1
—
—
—
2
—

kW
—
—
—
—
—
—
—
—
—
—
.81
—
.71
—
—
—
—
—
—
.86
—
—
—
—
—
—
1.37
—
—
—
1.21
—

5. Minimum one turn open of motor pulley is required on unit sizes 036
and 060.
6. Number of turns open applies to field setting of motor pulley.
7. Factory setting as follows: 036, 4 turns open; 048, 2 turns open; 060,
5 turns open.
8. Care should be taken when hoods and/or louvers are installed to
avoid condenser air recirculation.

ELECTRIC HEATER STATIC PRESSURE DROP (in. wg)
ELECTRIC HEATER
UNIT 88EN
0500CA01
0075CA01
0115CA01
0075EA01
1150EA01
0100EA01
0150EA01
0200EA01
0300EA01
0300CA01
0100FA01
0150FA01
0200FA01
0300FA01

UNIT
50AH
024, 036
1-stage
heat

048, 060
2-stage
heat

MIN
CFM
400
510
620
320
720
970
1240
1350
1220
1220
1130
1360
1350
1270

600
.02
.03

800
.04
.06

1000
.06
.10

1200
.10
.16

UNIT CFM
1400
—
—

1600
—
—

1800
—
—

2000
—
—

2200
—
—

.04

.08

.13

.19

—

—

—

—

—

—

—

—

.04

.06

.08

.12

.15

.17

—

—

—

.08

.11

.14

.18

.22

.26

—

—

—

.04

.06

.08

.12

.15

.17

—

—

—

.08

.11

.14

.18

.22

.26

NOTE: Above electric heaters are not UL (Underwriters’ Laboratories) or CSA (Canadian Standards Association)
listed for use with optional high-static evaporator-fan motor (048, 060 units only).

Controls
Operating sequence
Cooling — Thermostat calls for cooling. Indoor (evaporator) fan relay is energized and starts evaporator fan. Compressor contactor is energized to start compressor and
condenser fan (up to a 5-minute delay on single-phase
units). When room thermostat is satisfied, the evaporator
fan, compressor, and condenser fan shut off.
Continuous fan operation — The thermostat can be
set for continuous operation by setting the fan switch to
ON.

Electrical data
UNIT
50AH

V-PH
(60 Hz)

024

230-1
230-1
208/230-3
460-3
230-1
208/230-3
460-3
208/230-3
460-3
230-1
208/230-3
460-3
208/230-3
460-3

036
048
048*
060
060*

HACR
Hp
FLA
LRA
MOCP
RLA

—
—
—
—
—
—

VOLTAGE RANGE
Min
207
207
187
414
207
187
414
187
414
207
187
414
187
414

Max
254
254
254
508
254
254
508
254
508
254
254
508
254
508

COMPRESSOR
RLA
11.4
17.2
10.3
5.1
24.4
15.5
7.4
15.5
7.4
28.8
17.3
9.0
17.3
9.0

LRA
56
96
77
40
150
105
55
105
55
169
123
62
123
62

FAN MOTORS
Evaporator
Condenser
Hp
FLA
Hp
FLA
.17
1.10
.50
3.40
.50
3.20
.75
6.06
.50
3.20
.75
3.93
.50
1.50
.75
1.97
.75
4.00
1.0
8.35
.75
4.00
1.0
3.93
.75
2.15
1.0
1.97
1.5
5.60
1.0
3.93
1.5
2.80
1.0
1.97
.75
4.00
1.5
9.50
.75
4.00
1.5
4.82
.75
2.15
1.5
2.41
1.5
5.60
1.5
4.82
1.5
2.80
1.5
2.41

POWER SUPPLY
Min Ckt
Amps

MOCP
Amps

19.0
29.5
19.9
8.9
42.9
27.3
13.4
28.9
16.3
49.5
30.4
15.8
32.0
16.0

25
40
25
15
60
35
20
35
20
60
40
20
40
20

LEGEND
Heating, Air Conditioning, and Refrigeration
Horsepower
Full Load Amps
Locked Rotor Amps
Maximum Overcurrent Protection (HACR breaker)
Rated Load Amps

*Optional evaporator-fan motor nameplate data.

9

Electrical data (cont)
ELECTRIC HEATER DATA
ELECTRIC HEATER
UNIT 88EN
0050CA01
0075CA01
0115CA01
0075EA01

USED WITH
UNIT 50AH

024, 036
1-Stage Heat

1150EA01
0100EA01
0150EA01
0200EA01

048, 060
2-Stage Heat

0300EA01
0300CA01
0100FA01
0150FA01
0200FA01
0300FA01

V-PH
(60 Hz)
240-1
240-1
240-1
208-3
240-3
208-3
240-3
208-3
240-1*
240-3
208-3
240-1*
240-3
208-3
240-1*
240-3
208-3
240-3
240-1
480-3
480-3
480-3
480-3

CAP. (kW)
5.0
7.5
11.5
5.6
7.6
11.3
15.0
7.5
10.0
10.0
11.3
15.0
15.0
15.0
20.0
20.0
22.5
30.0
30.0
10.0
15.0
20.0
30.0

Heater Amps
20.8
31.3
47.9
15.6
18.0
31.2
36.1
20.8
41.7
24.1
31.2
62.5
36.1
41.7
83.3
46.9
62.5
72.2
124.0
12.0
18.1
24.1
36.1

LEGEND
MCA — Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Circuit Protection
(Fuses or Circuit Breaker)
*May be field converted to single-phase units, see electric heat installation instructions.
NOTE: Separate power source is required for all heaters. Control from base unit 50AH (24 v).

10

BRANCH CIRCUIT
MCA
26.0
39.1
59.9
19.5
22.6
39.0
45.1
26.0
52.1
30.1
39.0
78.1
45.1
52.1
104.2
58.6
78.2
90.2
155.0
15.0
22.6
30.1
45.1

MOCP (Amps)
30
40
60
20
25
40
50
30
60
35
40
80
50
60
110
60
80
100
175
15
25
35
50

Typical wiring schematic
50AH048,060 — 230-1-60 UNITS

LEGEND
AHA
C
CB
CC
EQUIP GND
HPS
HR
IFC
IFR
JB
L
LPS
NEC
PL
TB
TC
TH
TRAN

—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

Adjustable Heat Anticipator
Contactor Compressor
Circuit Breaker
Cooling Compensator
Equipment Ground
High-Pressure Switch
Heater Relay
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan Relay
Junction Box
Light
Low-Pressure Switch
National Electrical Code
Plug Assembly
Terminal Block
Thermostat-Cooling
Thermostat-Heating
Transformer

Marked Wire
Denotes connection point between subbase and thermostat
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Field Splice
Splice (Marked)
Factory Splice
Factory Wiring
Accessory or Optional Wiring
Field Control Wiring
Field Power Wiring
To indicate common potential only not to represent wiring

11

Typical wiring schematic (cont)
50AH036,048,060 — 208/230-3-60 UNITS

LEGEND
AHA
C
CB
CC
CLO
CT
EQUIP GND
HPS
HR
IFC
IFR
JB
L
LOR
LPS
NEC
PL
TB
TC
TH
TRAN

12

—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

Adjustable Heat Anticipator
Contactor Compressor
Circuit Breaker
Cooling Compensator
Compressor Lockout
Current Transformer
Equipment Ground
High-Pressure Switch
Heater Relay
Indoor (Evaporator) Fan Contactor
Indoor (Evaporator) Fan Relay
Junction Box
Light
Lockout Relay
Low-Pressure Switch
National Electrical Code
Plug Assembly
Terminal Block
Thermostat-Cooling
Thermostat-Heating
Transformer

Marked Wire
Denotes connection point between subbase and thermostat
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Field Splice
Splice (Marked)
Factory Splice
Factory Wiring
Accessory or Optional Wiring
Field Control Wiring
Field Power Wiring
To indicate common potential only not to represent wiring

Typical piping and wiring

LEGEND
NEC — National Electrical Code
NOTES:
1. Wiring and piping shown are not intended for or to include all
details for specific installation.
2. All wiring must comply with applicable local and national codes.

3. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual, Part 3, for details.
4. For other installation details refer to Installation Instructions.
5. If unit sections are field split, 8 threaded support rods are required.
6. Ensure condenser air recirculation is minimized.

Application data
OUTDOOR-AIR TEMPERATURE OPERATING LIMITS (F)
UNIT 50AH
Without Head Pressure Control
With Head Pressure Control

Minimum
Maximum
Minimum
Maximum

024
35
126
0
126

036
35
126
0
126

Field splitting instructions — If components are split,
maximum length of refrigerant tubing to be used is 50 ft,
assuming components are installed in same horizontal
plane. Condenser may be mounted up to 12 ft above evaporator. Liquid line tubing is 3/8-in. OD copper tubing, and
discharge line is 1/2-in. OD copper tubing. For additional
piping information, refer to Carrier System Design Manual, Part 3. Units should always be within line of sight from
each other, or separate NEC (National Electrical Code)

048
40
126
0
126

060
40
126
0
126

disconnects will be required. Junction boxes should be
installed in both the evaporator and condenser sections
adjacent to D-shaped grommets, to provide a location to
splice the outdoor-fan motor factory wiring (no. 16 AWG
[American Wire Gage], 4/64-in. thick insulation). Field wiring should be a minimum of no. 16 AWG, 4/64-in. thick
insulation. Check all applicable electrical codes to ensure
proper compliance.

13

Guide specifications
Indoor Packaged Unit
HVAC Guide Specifications — Section 15787
Size Range: 2 to 5 Tons, Nominal
Carrier Model Number: 50AH
Part 1 — General
1.01 SYSTEM DESCRIPTION
Indoor mounted, electrically controlled packaged
horizontal cooling unit utilizing a hermetic type
scroll compressor.
1.02 QUALITY ASSURANCE
A. Unit shall be certified in accordance with ARI
Standard 210.
B. Unit shall be UL listed and carry a UL label.
C. Unit shall be CSA approved (except 3 ton, 3-phase
units).
D. Unit shall be factory run-tested to ensure proper
performance prior to delivery.
1.03 DELIVERY, STORAGE, AND HANDLING
A. Unit shall be shipped completely assembled and
ready to operate.
B. Unit shall be shipped factory charged with refrigerant R-22.
C. Unit shall be stored and handled in accordance with
the unit manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory assembled horizontal, single piece, air
cooled, indoor, ceiling plenum mounted electric
cooling unit. Contained within the unit enclosure
shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required
prior to start-up.
B. Unit Cabinet:
1. Constructed of galvanized steel.
2. Interior shall be insulated with 1/2-in. thick neoprene coated fiberglass. Insulation shall be
bonded to interior surfaces by sprayed water
reduceable adhesive.
3. Equipped with 3 same side access panels and
2 bottom hanging removable doors to facilitate
ease of maintenance. Side panels allow access
to the control box, refrigeration components,
and condenser coil. Control box shall be hinged
allowing access to the compressor and pressure
switches. Bottom doors shall allow access to
and easy removal of the condenser and evaporator motors and blower assemblies.
4. Equipped with two 3/4-in. threaded condensate
drain connections below the evaporator coil
and one 3/4-in. threaded connection for condenser coil wash down. Connections shall be
factory plugged for field removal.

14

C.

D.

E.

F.

G.

H.

5. Field splittable through the removal of 4 bolts
and extending refrigerant piping and wiring to
allow remote horizontal or vertical condenser
mounting.
6. Unit shall have an integral hanging bracket
requiring only 4 threaded rods (8 if unit is split)
run to the top flange of the unit for hanging,
eliminating need for external hanger brackets.
7. Contains junction box for power connection
and opening for routing of control wiring.
Fans:
1. Evaporator:
a. Blower shall be of the forward-curved, centrifugal, direct-drive type or belt drive (4 and
5 tons only).
b. Motor shall have permanently lubricated
bearings.
c. Unit sizes 048, 060 shall be available with
an optional 1.5 hp fan motor.
2. Condenser:
a. Blower shall be of the forward-curved, centrifugal, direct-driven type (024 only), or belt
drive (036,048,060).
b. Motor shall have permanently lubricated
bearings.
Compressor:
1. Fully hermetic scroll type.
2. Mounted on suitable spring vibration isolators.
3. Equipped with internal line break protection.
Coils:
Evaporator and condenser coils shall be of nonferrous construction with aluminum fins mechanically bonded to seamless copper tubes with all joints
brazed.
Refrigerant Components:
Refrigerant components shall include:
1. Capillary tube feed system.
2. Refrigerant filter-drier.
Filter Section:
Filter section shall consist of factory-installed, permanent, cleanable air filter, removable from the
same side as the access panels without the use of
tools.
Controls and Safeties:
Control system shall include a high-pressure switch,
a low-pressure switch, and a compressor lockout
feature which upon tripping of any safety device
shall prevent compressor from restarting until reset
at the thermostat (on all 3-phase units and 036
single-phase units only).
Time Guard® II device (single-phase only) shall prevent the compressor from restarting for a minimum
of 5 minutes after shutdown.

I. Operating characteristics:
1. Unit shall operate using refrigerant R-22.
2. Unit shall be designed for indoor suspended
horizontal mounting and operation.
J. Electrical Requirements
Unit shall have single point power connection to
leads in terminal box.
K. Special Features:
Certain standard features are not applicable when
the features designated by * are specified. For assistance in amending the specifications, your local
Carrier Sales Office should be contacted.
* 1. Electric Heat Module:
a. Provides encased heater elements that shall
attach directly to the base unit discharge.
b. Shall have bottom access.
c. UL listed.
2. Thermostat Assembly:
Provides cooling and fan control. Standard subbase shall include ‘‘Compressor malfunction
light’’ designed to illuminate if compressor lockout is activated.

3. Time Guard® II Device Compressor Cycle
Delay:
Prevents compressor from restarting for a minimum of 5 minutes after shutdown.
* 4. Condensate Pump:
Unit shall be equipped with remotely located
condensate pump. A field-installed light shall
illuminate when reservoir rises above a preset
level. Unit shall shut down upon reservoir light
illumination.
* 5. Head Pressure Control Package:
Allows unit to mechanically cool down to 0° F
ambient temperature. Package shall include
damper operating device and all necessary
hardware.
6. Vibration Isolation Package:
Shall provide 4 spring hangers for ceiling
mounted unit to damper vibration that may be
transmitted to building structure.

15

Carrier Corporation • Syracuse, New York 13221

204

9-02

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
New Book 1
Pg 16
Catalog No. 525-00039
Printed in U.S.A.
PC 111
Form 50AH-6PD
Replaces: 50AH-5PD
Tab IP1a
Tab 2b 7a



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2002:09:10 12:36:50
Producer                        : Acrobat Distiller 4.0 for Windows
Author                          : Carrier Corporation
Creator                         : ADOBEPS4.DRV Version 4.20
Title                           : 50ah-6pd.fm
Modify Date                     : 2004:02:23 12:40:57-05:00
Page Count                      : 16
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu