Carrier 50He003 006 Users Manual 50h 1si 1 5

50HJ004 to the manual 1b90cbc6-b060-4c64-a7db-f45573cf641f

2015-01-24

: Carrier Carrier-50He003-006-Users-Manual-310406 carrier-50he003-006-users-manual-310406 carrier pdf

Open the PDF directly: View PDF PDF.
Page Count: 72

DownloadCarrier Carrier-50He003-006-Users-Manual- 50h-1si 1-5  Carrier-50he003-006-users-manual
Open PDF In BrowserView PDF
50HJ004---007
50HE003---006
Single---Package Rooftop Electric Cooling
Units with Optional Electric Heat

Installation Instructions
TABLE OF CONTENTS

SAFETY CONSIDERATIONS
Page

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1--Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . 2
ROOF CURB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SLAB MOUNT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ALTERNATE UNIT SUPPORT . . . . . . . . . . . . . . . . . 2
Step 2--Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . 2
Step 3--Install External Trap for Condensate Drain . . . . . . . 2
Step 4--Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . 4
POSITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 5 — Make Electrical Connections . . . . . . . . . . . . . . . . 8

. When you see this symbol on the furnace and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability,or operation.

FIELD POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . 8
FIELD CONTROL WIRING . . . . . . . . . . . . . . . . . . . . 8
HEAT ANTICIPATOR SETTINGS . . . . . . . . . . . . . . . 8
Step 6 — Adjust Factory-Installed Options . . . . . . . . . . . 29
COBRA™ ENERGY RECOVERY UNITS . . . . . . . 29
HUMIDI-MIZER™ ADAPTIVE
DEHUMIDIFICATION SYSTEM . . . . . . . . . . . . . . 29
DISCONNECT SWITCH . . . . . . . . . . . . . . . . . . . . . 29
MANUAL OUTDOOR-AIR DAMPER . . . . . . . . . . 29

!

CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . . 29
NOVAR CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . 29

WARNING

ELECTRICAL SHOCK HAZARD

PREMIERLINK™ CONTROL . . . . . . . . . . . . . . . . . 31

Failure to follow this warning could cause personal
injury or death.

OPTIONAL ECONOMI$ER IV AND
ECONOMI$ER2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.

ECONOMI$ER IV STANDARD SENSORS . . . . . . 35
ECONOMI$ER IV CONTROL MODES . . . . . . . . . 36
Step 7 — Adjust Evaporator-Fan Speed . . . . . . . . . . . . . . 41
PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

INSTALLATION

SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

1

Step 1 —Provide Unit Support
Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. (See Fig. 2.) Install insulation,
cant strips, roofing felt, and counter flashing as shown. Ductwork
must be attached to curb, not to the unit. If electric control power
or gas service is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan in
accordance with the accessory installation instructions.
Connections must be installed before unit is set on roof curb.

50HE,HJ

NOTE: Horizontal units may be installed on a roof curb if
required.
Alternate Unit Support
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If sleeper
rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Step 2 —Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, field-supplied isolation flanges should be attached to
horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire
codes.
A minimum clearance is not required around ductwork. Cabinet
return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
Step 3 —Install External Trap for
Condensate Drain
Condensate drain connections are located on the bottom and side
of the unit. Unit discharge connections do not determine the use
of drain connections; either drain connection can be used with
vertical or horizontal applications.
When using the standard side drain connection, ensure the plug
(Red) in the alternate bottom connection is tight before installing
the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (Red) from the bottom
connection to the side connection. The center drain plug looks
like a star connection, however it can be removed with a 1/2-in.
socket drive extension. (See Fig. 4.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage.
Install a trap 4-in. deep and protect against freeze-up. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (3/4 in.). (See Fig. 5.)

Fig. 1 --- Horizontal Conversion Panels

C06108

IMPORTANT: The gasketing of the unit to the roof curb is critical
for a watertight seal. Install gasket supplied with the roof curb as
shown in Fig. 2. Improperly applied gasket can result in air leaks and
poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to
Accessory Roof Curb Installation Instructions for additional
information as required.

Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.

2

CRBTMPWR001A01
CRBTMPWR002A01
CRBTMPWR003A01
CRBTMPWR004A01

B

1

-911 /16
[551]

C

1 -4
[406]

D ALT
DRAIN
HOLE

13/4

[44.5]

GAS
3/4
[19] NPT
1/2
[12.7] NPT
3/4
[19] NPT

POWER
[19] NPT
11/4 [31.7]

CONTROL

ROOF CURB
ACCESSORY

ACCESSORY
POWER

CRRFCURB001A01

3/4

3/4

[19] NPT

1/

2

[12.7]

CRRFCURB002A01

1/
2

[12.7]

A
1 -2
[356]
2 -0
[610]

UNIT
SIZE

50HJ004-007
50HE003-006

NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest
on curb).
6. Service clearance: 4 ft on each side.

11/4 [31.7]

7.

Direction of airflow.

8. Connector packages CRBTMPWR001A01
and 002A01 are for thru-the-curb type gas.
Packages CRBTMPWR003A01 and 004A01
are for thru-the-bottom type gas connections.

50HE,HJ

CONNECTOR
PKG. ACCY.

Fig. 2 --- Roof Curb Details

3

C06155

Step 4 —Rig and Place Unit
Inspect unit for transportation damage, and file any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit, and
rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 1, 2 and Fig. 6 for additional
information. Operating weight is shown in Table 1, 2 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 7. Refer
to rigging instructions on unit.

50HE,HJ

!

WARNING

CONDENSATE PAN (SIDE VIEW)
HORIZONTAL
DRAIN PLUG
DRAIN OUTLET

PERSONAL INJURY AND PROPERTY DAMAGE
HAZARD

NOTE: Drain plug is shown in factory-installed position.

Failure to follow this warning could result in personal
injury, death and property damage.

Fig. 4 --- Condensate Drain Connection

C06003

All panels must be in place when rigging and lifting.

Positioning
Maintain clearance around and above unit to provide minimum
distance from combustible materials, proper airflow, and service
access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are
maintained: 1/4 in. clearance between the roof curb and the base
rail inside the front and rear, 0.0 in. clearance between the roof
curb and the base rail inside on the duct end of the unit. This will
result in the distance between the roof curb and the base rail
inside on the condenser end of the unit being approximately
equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air
inlets near exhaust vents or other sources of contaminated air.

NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.

Fig. 5 --- Condensate Drain Piping Details

C06004

Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
After unit is in position, remove polyethylene shipping wrapper
and top crating.

MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
0.5

B-C
1.0

Fig. 3 --- Unit Leveling Tolerances

A-C
1.0

C06110

4

C06111

Fig. 6 --- Rigging Details
UNIT
50HE
003
004
005
006
UNIT
50HJ
004
005
006
007

OPERATING
WEIGHT

“A”

lb
kg
435
197
445
202
465
211
520
236
OPERATING
WEIGHT

in.
73.69
73.69
73.69
73.69

lb
530
540
560
635

in.
73.69
73.69
73.69
73.69

kg
240
245
254
288

mm
1872
1872
1872
1872
“A”
mm
1872
1872
1872
1872

DIMENSIONS
“B”
in.
mm
35.50
902
35.50
902
35.50
902
35.50
902
DIMENSIONS
“B”
in.
mm
35.50
902
35.50
902
35.50
902
35.50
902

!

“C”
in.
33.31
33.31
33.31
33.31

mm
847
847
847
847
“C”

in.
33.31
33.31
33.31
33.31

mm
847
847
847
847

WARNING

PERSONAL INJURY AND PROPERTY DAMAGE
HAZARD

Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.

Fig. 7 --- Roof Curb Alignment

C06208

5

50HE,HJ

NOTES:
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
3. Hook rigging shackles through holes in base rail as shown in detail "A." Holes in base rails are centered around the unit center of gravity. Use wooden
top skid when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
5. Weights include base unit without the Humidi-MiZerTM adaptive dehumidification system. See Table 1 for unit operating weights with the
Humidi-MiZer system.

6
Fig. 8 --- 50HJ004--007 Base Unit Dimensions

50HE,HJ

C06156

7
Fig. 9 --- 50HE003--006 Base Unit Dimensions

50HE,HJ

C06157

Step 5 —Make Electrical Connections

!

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_C minimum). For 50 to 75 ft, use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
1. Connect thermostat wires to screw terminals of lowvoltage
terminal board.
2. Pass the control wires through the hole provided in the
control box.
3. Some models may be equipped with a raceway built into
the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between
high--voltage and low voltage wiring. For models without
a raceway, ensure to provide the NEC required clearance
between high--voltage and low--voltage wiring.
Heat Anticipator Settings
Set heat anticipator settings at 0.8 amp for first stage and 0.3 for
second stage heating.

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death,

50HE,HJ

Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug in
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC (National
Electrical Code), ANSI/NFPA (National Fire Protection
Association), latest edition, and local electrical codes. Do
not use gas piping as an electrical ground.

Field Power Supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the transformer must be rewired by
disconnecting the black wire from the 230-v 1/4--in. terminal on
the transformer and connecting it to the 200-v 1/4--in. terminal
from the transformer.
Refer to unit label diagram for additional information. Pigtails
are provided for field service. Use factory-supplied splices or UL
(Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local
requirements.
Install field wiring as follows:
1. Install conduit through side panel openings. For units
without electric heat, install conduit between disconnect
and control box.
2. Install power lines to terminal connections as shown in
Fig. 12.
3. For units with electric heat, refer to Accessory Electric
Heat Installation Instructions.
During operation, voltage to compressor terminals must bewithin
range indicated on unit nameplate (also see Table 3 and 4). On
3--phase units, voltages between phases must be balanced within
2% and the current within 10%. Use the formula shown in Table
3 and 4, Note 2, to determine the percentage of voltage
imbalance. Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical
components. Such operation invalidates any applicable Carrier
warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on wiring the unit.
Field Control Wiring
Install a Carrier-approved accessory thermostat assembly
according to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the conditioned
space to sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored wire
from subbase terminals through connector on unit to low-voltage
connections (shown in Fig. 10 and 11).

COOL STAGE 1

Y1/W2

R

FAN

G

G

HEAT STAGE 1

W/W1

Y1

COOL STAGE 2

Y/Y2

Y2

HEAT STAGE 2

O/W2

W1

24 VAC HOT

R

W2

24 VAC COM

C

C
IPD/X

N/A
OUTDOOR AIR

S1

SENSOR

S2

WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION

THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
D
B
A
C

LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when
configured for A/C operation.

Fig. 10 --- Low--Voltage connections With or
Without Economizer or Two--Position Damper
CONTROL
CONNECTION
BOARD

THERMOSTAT CONTROL
CONNECTION
BOARD

R

24 VAC

R

R

G

RMTOCC

Y1

Y1

Y2

CMPSAFE

Y2

Y2

FSD

W1

W1

SFS

W2

W2

NOT USED

G

G

C

C

C

C

X

X

X

W1

Fig. 11 --- Low--Voltage Connections
(Units with PremierLinkt Controls)

8

C06008

C06009

BASE UNIT 50HJ
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
Humidi-MiZer™ Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Humidi-Mizer Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Total Face Area (sq ft)
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous Bhp
Std
Hi-Static
Motor Frame Size
Std
Hi-Static
Fan Rpm Range
Std
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Std
Motor Pulley Pitch Diameter A/B (in.)
Hi-Static
Nominal Motor Shaft Diameter (in.)
Std
Hi-Static
Fan Pulley Pitch Diameter (in.)
Std
Hi-Static
Belt — Type...Length (in.)
Std
Hi-Static
Pulley Center Line Distance (in.)
Std
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Hi-Static
Std
Movable Pulley Maximum Full
Turns from Closed Position
Hi-Static
Factory Setting — Full Turns Open
Std
Hi-Static
Factory Speed Setting (rpm)
Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid LIne) (psig)
Cutout
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
OUTDOOR-AIR INLET SCREENS
RETURN-AIR FILTERS
Quantity...Size (in.)

004
3

005
4

006
5

007
6

435
15
50
115

445
23
50
115

465
25
50
115

540
29
50
115

1
42

1
53

1
50

1
60

10-0
20-5

12- 8
23-14

Scroll

R-22
Acutrol™ Metering Device

5-8
12-5

10-2
18-8

Propeller
1...22
1...22
3500
4100
1/8...825
1/ ...1100
4
180
320
Enhanced Copper Tubes, Aluminum Lanced Fins
2...17
2...17
16.5
16.5
Enhanced Copper Tubes, Aluminum Double-Wavy Fins

1...22
3500
1/8...825
180
1...17
14.6
2...15
5.5

2...15
5.5

1...17
3.9

4...15
5.5

2...17
2...17
3.9
3.9
Centrifugal Type, Belt Drive
1...10 x 10
1...10 x 10
1600
2000
1.20
1.30/2.40*
2.40
2.90
48
56
56
56
770-1185
1035-1460/1035 ---1460*
1075-1455
1300-1685
Ball
Ball
2100
2100
1.9/2.9
2.4/3.4
2.8/3.8
3.4/4.4
1/
5/
2
8
5/
7/8
8
4.0
4.0
4.5
4.5
1...A...36
1....4...40
1...A...39
1...A...40
10.0-12.4
14.7-15.5
70
75
65
60
5
6
6
5
3
3
31/2
31/2
936
1248
1233
1396
5/
5/
8
8

1...10 x 10
1200
1.20
2.40
48
56
680-1044
1075-1455
Ball
2100
1.9/2.9
2.8/3.8
1/
2
5/
8

4.5
4.5
1...A...36
1...A...39
10.0-12.4
65
65
5
6
3
31/2
826
1233
5/
8

1...22
4100
1/ ...1100
4
320
2...17
21.3
4...15
7.3
2...17
5.2
1...10 x 10
2400
2.40
2.90
56
56
1120-1585
1300-1685
Ball
2100
2.4/3.4
3.4/3.4
5/
8
7/
8
3.7
4.5
1...A...38
1...A...40
14.7-15.5
95
60
5
5
3
31/2
1304
1396
5/
8

450 ± 50
428
320
7±3
22 ± 5
30
45
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 16 x 2
2...16 x 25 x 2

LEGEND

Bhp — Brake Horsepower
*Single phase/three phase.

9

50HE,HJ

Table 1—Physical Data 50HJ

50HE,HJ

Table 2—Physical Data 50HE
BASE UNIT 50HE
NOMINAL CAPACITY
OPERATING WEIGHT (lb)
Unit
Humidi-MiZer™ Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Humidi-Mizer Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Total Face Area (sq ft)
Unit with Humidi-Mizer Adaptive Dehumidification System
Rows...Fins/in.
Total Face Area (sq ft)
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous Bhp
Std
Hi-Static
Motor Frame Size
Std
Hi-Static
Motor Rpm
Fan Rpm Range
Std
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Std
Motor Pulley Pitch Diameter A/B (in.)
Hi-Static
Nominal Motor Shaft Diameter (in.)
Std
Hi-Static
Fan Pulley Pitch Diameter (in.)
Std
Hi-Static
Belt — Type...Length (in.)
Std
Hi-Static
Pulley Center Line Distance (in.)
Std
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Hi-Static
Std
Movable Pulley Maximum Full
Turns from Closed Position
Hi-Static
Factory Setting — Full Turns Open
Std
Hi-Static
Factory Speed Setting (rpm)
Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid LIne) (psig)
Cutout
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
OUTDOOR-AIR INLET SCREENS
RETURN-AIR FILTERS
Quantity...Size (in.)
LEGEND

Bhp — Brake Horsepower

003
2

004
3

435
13
50
115

445
15
50
115

1
25

1
42

5 ---3
10 ---2

7 ---11
14 ---0

1...17
14.6
2...15
4.2

2...15
5.5

1...17
3.5

1...17
3.9

1...10 x 10
800
0.58

1...10 x 10
1200
1.20
2.40
48
56
1620
680-1044
1075-1455
Ball
2100
1.9/2.9
2.8/3.8

48
1620
400-1000
Ball
1620
2.4/3.2
7/

1/
2
5/
8

8
8

4.5
4.5
1...A...36
1...A...39
10.0-12.4
65
65
5
6
3
31/2
826
1233
5/
8

4.0
4.5
1...A...36
10.0 ---12.4
60
5
3
756
5/

465
23
50
115
Scroll
1
56
R-22
Acutrol™ Metering Device

006
5
635
25
50
115
1
53

8 ---8
12 ---11
14 ---13
21 ---0
Propeller
1...22
1...22
1...22
3500
3500
4100
1/8...825
1/8...825
1/ ...1100
4
180
180
320
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17
2...17
2...17
14.6
16.5
16.5
Enhanced Copper Tubes, Aluminum Double-Wavy Fins

1...22
3000
1/8...825
180

5/

005
4

8

2...15
5.5
2...17
3.9
Centrifugal Type, Belt Drive
1...10 x 10
1600
1.20
2.40
48
56
1620
770-1185
1075-1455
Ball
2100
1.9/2.0
2.8/3.8
1/
2
5/
8
4.0
4.0
1...A...36
1...A...39
10.0-12.4
70
65
5
6
3
31/2
936
1233
5/
8

4...15
5.5
2...17
3.9
1...10 x 10
2000
1.30/2.40*
2.90
48/56*
56
1725
1035-1460
1300-1685
Ball
2100
2.4/3.4
3.4/4.4
5/
8
5/
8
4.0
4.5
1....4...40
1...A...40
14.7-15.5
75
60
6
5
3
31/2
1248
1396
5/
8

450 ± 50
428
320
7±3
22 ± 5
30
45
Cleanable. Screen quantity and size varies with option selected.
Throwaway
2...16 x 25 x 2
***These units do NOT meet the California low NOx requirements.
†††California SCAQMD compliant low NOx models have combustion products that are
controlled to 40 nanograms per joule or less.

*Single phase/three phase.

10

208/230-3-60
460-3-60
(SIZES 006 AND 007)

50HE,HJ

208/230-1-60

575-3-60
(SIZES 004 AND 005)

575-3-60
(SIZES 006 AND 007)

460-3-60
(SIZES 004 AND 005)

208/230-3-60
(SIZES 004 AND 005)

C
COMP
IFC
NEC
TB

—
—
—
—
—

LEGEND
Contactor
Compressor
Indoor (Evaporator) Fan Contactor
National Electrical Code
Terminal Block

Fig. 12 --- Power Wiring Connections
LOW VOLTAGE
CONNECTIONS

INTEGRATED GAS UNIT
CONTROLLER (IGC)

Fig. 13 --- Field Control Wiring Raceway

C06125

11

C06158

12

004
(3 tons)

003
(2 tons)

UNIT SIZE

460--- 3--- 60

208/230--- 3--- 60

STD

208/230--- 1--- 60

STD

HS

STD

STD

IFM
TYPE

208/230--- 1--- 60

Nominal
V--- Ph--- Hz

414

414

NO

YES

187

187

YES

NO

187

187

NO

YES

187

187

NO

YES

187

187

NO

YES

Min

CONV
OUTLET

508

508

254

254

254

254

254

254

254

254

Max

VOLTAGE RANGE

1

1

1

1

1

1

1

1

1

1

QTY

5.1

5.1

10.3

10.3

10.3

10.3

16.0

16.0

10.9

10.9

RLA

39.0

39.0

77.0

77.0

77.0

77.0

88.0

88.0

63.0

63.0

LRA

1

1

1

1

1

1

1

1

1

1

QTY

0.4

0.4

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

FLA

OUTDOOR FAN

Table 3—Electrical Data--50HE
COMPRESSOR (each)

2.2

2.2

5.8

5.8

4.9

4.9

4.9

4.9

2.0

2.0

IFM
FLA

ELECTRIC HEAT
CRHEATER
Actual
--- --- --- A00
or B00
kW†
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
002,002
9.8/11.6
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
002,002
9.8/11.6
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
005A00
12/14.7
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
005A00
12/14.7
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
005A00
12/14.7
NONE
—/ —
001A00
3.3/ 4.0
002A00
4.9/ 5.8
003B00
6.5/ 8.0
004B00
7.9/ 9.6
005A00
12/14.7
NONE
—
006A00
5.5
007A00
8.1
008A00
10.6
009A00
12.9
NONE
—
006A00
5.5
007A00
8.1
008A00
10.6
009A00
12.9
MCA
16.3/16.3
22.4/25.4
31.8/36.4
41.8/47.8
49.9/57.2
22.3/22.3
27.4/30.4
36.8/41.4
46.8/52.8
54.9/62.2
25.6/25.6
26.0/29.0
35.5/40.0
45.4/51.4
53.5/60.8
64.8/73.8
31.6/31.6
31.6/34.0
40.5/45.0
50.4/56.4
58.5/65.8
69.8/78.8
18.5/18.5
18.5/19.4
23.1/25.7
28.8/32.3
33.5/37.7
47.8/54.2
24.5/24.5
24.5/24.5
28.1/30.7
33.8/37.3
38.5/42.7
52.8/59.2
19.4/19.4
19.4/20.5
24.2/26.8
29.9/33.4
34.6/38.8
48.9/55.4
25.4/25.4
25.4/25.5
29.2/31.8
34.9/38.4
39.6/43.8
53.9/60.4
9.0
11.8
16.0
20.0
23.8
11.7
15.1
19.4
23.4
27.2

—/—
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
—/—
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
—/—
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
—/—
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
—/—
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
—/—
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
—/—
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
—/—
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
—
7.2
10.6
13.8
16.8
—
7.2
10.6
13.8
16.8

**

20/20
25/30
35/40
45/50
50/60
25/25
30/35
40/45
50/60
60/70
30/30
30/30
40/40
50/60
60/70
70/80
35/35
35/35
45/45
60/60
60/70
70/80
25/25
25/25
25/30
30/35
35/40
50/60
30/30
30/30
30/35
35/40
40/45
60/60
25/25
25/25
30/30
35/35
35/40
50/60
30/30
30/30
35/35
40/40
40/45
60/70
15.0
15.0
20.0
25.0
25.0
15.0
20.0
20.0
25.0
30.0

MOCP

POWER SUPPLY *
FLA

50HE,HJ

16/16
21/23
29/33
38/44
46/53
21/21
26/29
35/39
44/50
51/58
25/25
25/27
33/37
42/47
49/56
60/68
30/30
30/32
38/42
47/53
55/61
65/73
18/18
18/18
21/24
26/30
31/35
44/50
24/24
24/24
27/29
32/35
36/40
50/55
19/19
19/19
22/25
28/31
32/36
45/51
25/25
25/25
28/30
33/36
37/41
51/56
9.0
11.0
15.0
18.0
22.0
11.0
13.0
17.0
21.0
24.0

FLA

69/69
69/69
69/69
69/69
69/69
73/73
73/73
73/73
73/73
73/73
101/101
101/101
101/101
101/101
101/101
101/101
106/106
106/106
106/106
106/106
106/106
106/106
90/90
90/90
90/90
90/90
90/90
90/90
95/95
95/95
95/95
95/95
95/95
95/95
120/120
120/120
120/120
120/120
120/120
120/120
124/124
124/124
124/124
124/124
124/124
124/124
46.0
46.0
46.0
46.0
46.0
48.0
48.0
48.0
48.0
48.0

LRA

DISCONNECT SIZE

13

004
(3 tons)

UNIT SIZE

575--- 3--- 60

460--- 3--- 60

Nominal
V--- Ph--- Hz

HumidiMi$er

HS

STD

HS

IFM
TYPE

NO
YES
NO
YES
NO
YES
518

518

518

414

414

NO

YES

Min

CONV
OUTLET

632

632

632

508

508

Max

VOLTAGE RANGE

1

1

1

1

1

QTY

4.2

4.2

4.2

5.1

5.1

RLA

31.0

31.0

31.0

39.0

39.0

LRA

1

1

1

1

1

QTY

0.4

0.4

0.4

0.4

0.4

FLA

OUTDOOR FAN

2.6

2.0

1.9

2.6

2.6

IFM
FLA

Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each)

50HE,HJ

ELECTRIC HEAT
CRHEATER
Actual
--- --- --- A00
or B00
kW†
NONE
—
006A00
5.5
007A00
8.1
008A00
10.6
009A00
12.9
NONE
—
006A00
5.5
007A00
8.1
008A00
10.6
009A00
12.9
NONE
—
NONE
—
NONE
—
NONE
—
NONE
—
NONE
—
MCA
9.4
12.3
16.5
20.5
24.3
12.1
15.6
19.9
23.9
27.7
7.6
9.7
7.7
9.8
7.7
9.8

FLA
—
7.2
10.6
13.8
16.8
—
7.2
10.6
13.8
16.8
—
—
—
—
—
—

**

15.0
15.0
20.0
25.0
25.0
15.0
20.0
20.0
25.0
30.0
10
15
10
15
10
15

MOCP

POWER SUPPLY *

9.0
11.0
15.0
19.0
22.0
12.0
14.0
18.0
21.0
25.0
7
9
8
10
8
10

FLA

60.0
60.0
60.0
60.0
60.0
62.0
63.0
63.0
63.0
63.0
35
36
40
42
48
49

LRA

DISCONNECT SIZE

14

005
(4 tons)

UNIT
SIZE

575--- 3--- 60

460--- 3--- 60

208/230--- 3--- 60

STD

208/230--- 1--- 60

HumidiMi$er

HS

STD

HS

STD

HS

STD

IFM
TYPE

NOMINAL
V--- PH--- Hz

NO
YES
NO
YES
NO
YES

YES

NO

518

518

518

414

414

414

414

NO

YES

187

187

YES

NO

187

187

NO

YES

197

197

Min

YES

NO

CONV
OUTLET

632

632

632

508

508

508

508

254

254

254

254

254

254

Max

VOLTAGE
RANGE

1

1

1

1

1

1

1

1

1

1

1

1

1

QTY

6.1

6.1

6.1

7.1

7.1

7.1

7.1

14.1

14.1

14.1

14.1

21.0

21.0

RLA

38.0

38.0

38.0

45.0

45.0

45.0

45.0

95.0

95.0

95.0

95.0

115.0

115.0

LRA

1

1

1

1

1

1

1

1

1

1

1

1

1

QTY

0.8

0.6

0.6

0.8

0.8

0.8

0.8

1.5

1.5

1.5

1.5

1.5

1.5

FLA

OUTDOOR FAN

2.6

2.0

1.9

2.6

2.6

2.2

2.2

5.8

5.8

4.9

4.9

4.9

4.9

IFM
FLA
CRHEATER
--- --- A00 or
B00
NONE
001A00
003B00
002,002
003,003
004,004
NONE
001A00
003B00
002,002
003,003
004,004
NONE
002A00
003B00
005A00
004,004
NONE
002A00
003B00
005A00
004,004
NONE
002A00
003B00
005A00
004,004
NONE
002A00
003B00
005A00
004,004
NONE
006A00
008A00
009A00
008,008
NONE
006A00
008A00
009A00
008,008
NONE
006A00
008A00
009A00
008,008
NONE
006A00
008A00
009A00
008,008
NONE
NONE
NONE
NONE
NONE
NONE

Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each)
FLA
—/—
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
—/—
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
—/—
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
—/—
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
—/—
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
—/—
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
—
—
—
—
—

Actual kW{
—/—
3.3/ 4.0
6.5/ 8.0
9.8/ 11.6
13.1/ 16
16.0/ 19.3
—/—
3.3/ 4.0
6.5/ 8.0
9.8/ 11.6
13.1/ 16
16.0/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
12/ 14.7
16/ 19.3
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
—
—
—
—
—

ELECTRIC HEAT

50HE,HJ

32.7/32.7
32.7/32.7
45.4/51.4
64.8/73.8
84.7/96.8
100.9/115.5
38.7/38.7
38.7/38.7
50.4/56.4
69.8/78.8
89.7/101.8
105.9/120.5
24.0/24.0
24.0/25.7
28.8/32.3
47.8/54.2
60.8/69.3
30.0/30.0
30.0/30.7
33.8/37.3
52.8/59.2
65.8/74.3
24.9/24.9
24.9/26.8
29.9/33.4
48.9/55.4
62.0/70.4
30.9/30.9
30.9/31.8
34.9/38.4
53.9/60.4
67.0/75.4
11.9
11.9
20.0
23.8
37.3
14.6
15.1
23.4
27.2
40.7
12.3
12.3
20.5
24.3
37.8
15.0
15.6
23.9
27.7
41.2
10.1
12.3
10.2
12.4
10.3
12.5

MCA
40/40
40/40
50/60
70/80
90/100
110/125
45/45
45/45
60/60
70/80
90/110
110/125
30/30
30/30
30/35
50/60
70/70
35/35
35/35
35/40
60/60
70/80
30/30
30/30
35/35
50/60
70/80
35/35
35/35
40/40
60/70
70/80
15.0
15.0
25.0
25.0
40.0
20.0
20.0
25.0
30.0
45.0
15.0
15.0
25.0
25.0
40.0
20.0
20.0
25.0
30.0
45.0
15
15
15
15
15
15

MOCP**

POWER SUPPLY

32/32
32/32
42/47
60/68
78/89
93/106
37/37
37/37
47/53
65/73
83/95
98/112
24/24
24/24
26/30
44/50
56/64
29/29
29/29
32/35
50/55
62/69
25/25
25/25
28/31
45/51
57/65
30/30
30/30
33/36
51/56
63/70
12.0
12.0
18.0
22.0
34.0
14.0
14.0
21.0
24.0
37.0
12.0
12.0
19.0
22.0
35.0
15.0
15.0
21.0
25.0
37.0
10
12
10
12
10
12

FLA

130/130
130/130
130/130
130/130
130/130
130/130
135/135
135/135
135/135
135/135
135/135
135/135
110/110
110/110
110/110
110/110
110/110
115/115
115/115
115/115
115/115
115/115
140/140
140/140
140/140
140/140
140/140
145/145
145/145
145/145
145/145
145/145
53.0
53.0
53.0
53.0
53.0
55.0
55.0
55.0
55.0
55.0
67.0
67.0
67.0
67.0
67.0
69.0
70.0
70.0
70.0
70.0
44
45
50
52
55
57

LRA

DISCONNECT SIZE

15

006
(tons)

UNIT
SIZE

208/230--- 3--- 60

STD

208/230--- 1--- 60

HS

STD

IFM
TYPE

NOMINAL
V--- PH--- Hz

YES

NO

187

187

187

187

NO

YES

187

187

Min

YES

NO

CONV
OUTLET

254

254

254

254

254

254

Max

VOLTAGE
RANGE

1

1

1

1

1

1

QTY

17.3

17.3

17.3

17.3

25.0

25.0

RLA

123.0

123.0

123.0

123.0

150.0

150.0

LRA

1

1

1

1

1

1

QTY

1.5

1.5

1.5

1.5

1.5

1.5

FLA

OUTDOOR FAN

7.5

7.5

5.8

5.8

6.6

6.6

IFM
FLA
CRHEATER
--- --- A00 or
B00
NONE
002A00
003B00
02,002
003,003
004,004
NONE
002A00
003B00
02,002
003,003
004,004
002A00
004B00
005A00
004,004
004,005
NONE
002A00
004B00
005A00
004,004
004,005
NONE
002A00
004B00
005A00
004,004
004,005
NONE
002A00
004B00
005A00
004,004
004,005

Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each)

—/—
4.9/ 5.8
6.5/ 8.0
8.7/ 11.6
13.0/ 16.0
15.8/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
8.7/ 11.6
13.0/ 16.0
15.8/ 19.3
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3

MCA
50/50
50/50
50/60
70/80
90/100
60/50
60/50
60/60
80/90
100/110
110/125
90/100
35/35
35/40
50/60
70/80
80/90
40/40
40/40
40/45
60/70
70/80
90/100
35/35
35/35
40/45
60/60
70/80
80/90
40/40
40/40
45/50
60/70
70/80
90/100

MOCP**

POWER SUPPLY

39.4/39.4
39.4/42.1
47.5/53.6
66.9/76.0
86.8/98.9
103.0/117.6
45.4/45.4
45.4/47.1
52.5/58.6
71.9/81.0
91.8/103.9
108.0/122.6
28.9/28.9
34.6/38.8
48.9/55.4
62.0/70.4
76.3/86.9
34.9/34.9
34.9/34.9
39.6/43.8
53.9/60.4
67.0/75.4
81.3/91.9
30.6/30.6
30.6/30.6
36.7/40.9
51.1/57.5
64.1/72.5
78.4/89.1
36.6/36.6
36.6/36.6
41.7/45.9
56.1/62.5
69.1/77.5
83.4/94.1

50HE,HJ

FLA
—/—
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
—/—
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
—/—
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
—/—
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
—/—
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8

Actual kW{

ELECTRIC HEAT

38/38
38/39
44/49
62/70
80/91
95/108
44/44
44/44
49/55
67/75
85/96
100/114
28/28
32/36
45/51
57/65
70/80
34/34
34/34
37/41
51/56
63/70
76/86
30/30
30/30
34/38
47/53
59/67
72/82
36/36
36/36
39/43
53/58
65/72
78/87

FLA

187/187
187/187
187/187
187/187
187/187
187/187
191/191
191/191
191/191
191/191
191/191
191/191
168/168
168/168
168/168
168/168
168/168
173/173
173/173
173/173
173/173
173/173
173/173
187/187
187/187
187/187
187/187
187/187
187/187
192/192
192/192
192/192
192/192
192/192
192/192

LRA

DISCONNECT SIZE

16

460--- 3--- 60

575--- 3--- 60

006
(tons)

006
(tons)

HumidiMi$er

HS

STD

HS

STD

IFM
TYPE

NO
YES
NO
YES
NO
YES

YES

NO

YES

NO

CONV
OUTLET

518

518

518

414

414

414

414

Min

632

632

632

508

508

508

508

Max

1

1

1

1

1

1

1

QTY

7.1

7.1

7.1

8.4

8.4

8.4

8.4

RLA

53.0

53.0

53.0

70.0

70.0

70.0

70.0

LRA

1

1

1

1

1

1

1

QTY

0.8

0.6

0.6

0.8

0.8

0.8

0.8

FLA

OUTDOOR FAN

3.4

2.8

2.0

3.4

3.4

2.6

2.6

IFM
FLA
CRHEATER
--- --- A00 or
B00
NONE
006A00
008A00
009A00
008,008
008,009
NONE
006A00
008A00
009A00
008,008
008,009
NONE
006A00
008A00
009A00
008,008
008,009
NONE
006A00
008A00
009A00
008,008
008,009
NONE
NONE
NONE
NONE
NONE
NONE

Table 3 — Electrical Data--50HE (cont)
COMPRESSOR (each)
FLA
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
—
—
—
—
—

Actual kW{
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
—
—
—
—
—

ELECTRIC HEAT

NOTES:
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
{ Heater capacity (kW) is based on heater voltage of 240v, 480v or 575v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly

FLA ---Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps

NOMINAL
V--- PH--- Hz

UNIT
SIZE

VOLTAGE
RANGE

50HE,HJ

13.9
13.9
20.5
24.3
37.8
40.8
16.6
16.6
23.9
27.7
41.2
44.2
14.7
14.7
21.5
25.3
38.8
41.8
17.4
17.4
24.9
28.7
42.2
45.2
11.5
13.6
12.3
14.4
12.2
14.4

MCA
20.0
20.0
25.0
25.0
40.0
45
20.0
20.0
25.0
30.0
45.0
45
20.0
20.0
25.0
30.0
40.0
45
20.0
20.0
25.0
30.0
45.0
50
15
15
15
20
15
20

MOCP**

POWER SUPPLY

14.0
14.0
19.0
22.0
35.0
38
16.0
16.0
21.0
25.0
37.0
40
14.0
14.0
20.0
23.0
36.0
38
17.0
17.0
22.0
26.0
38.0
41
11
13
12
14
12
14

FLA

92.0
92.0
92.0
92.0
92.0
92
94.0
95.0
95.0
95.0
95.0
95
101.0
102.0
102.0
102.0
102.0
102
104.0
104.0
104.0
104.0
104.0
104
65
67
74
76
78
80

LRA

DISCONNECT SIZE

17

004
(3 tons)

UNIT
SIZE

208/230--- 3--- 60

STD

208/230--- 1--- 60

HS

STD

IFM TYPE

NOMINAL
V--- PH--- Hz

YES

NO

187

187

187

187

NO

YES

187

187

Min

YES

NO

CONV
OUTLET

254

254

254

254

254

254

Max

VOLTAGE
RANGE

1

1

1

1

1

1

QTY

10.3

10.3

10.3

10.3

16

16

RLA

77

77

77

77

88

88

LRA

COMPRESSOR (each)

1

1

1

1

1

1

QTY

0.7

0.7

0.7

0.7

0.7

0.7

FLA

OUTDOOR FAN

5.8

5.8

4.9

4.9

4.9

4.9

IFM
FLA
CRHEATER
--- --- A00 or
B00
—
001
002
003
004
002+002
—
001
002
003
004
002+002
—
001
002
003
004
002+002
—
001
002
003
004
002+002
—
001
002
003
004
002+002
—
001
002
003
004
002+002

Table 4—Electrical Data--50HJ

—/ —
15.9/ 18.3
23.5/ 27.1
31.4/ 36.3
37.9/ 43.1
46.9/ 54.2
—/ —
15.9/ 18.3
23.5/ 27.1
31.4/ 36.3
37.9/ 43.1
46.9/ 54.2
—/ —
9.2/ 10.6
13.6/ 15.6
18.1/ 20.9
21.9/ 25.3
33.4/ 38.5
—/ —
9.2/ 10.6
13.6/ 15.6
18.1/ 20.9
21.9/ 25.3
33.4/ 38.5
—/ —
9.2/ 10.6
13.6/ 15.6
18.1/ 20.9
21.9/ 25.3
33.4/ 38.5
—/ —
9.2/ 10.6
13.6/ 15.6
18.1/ 20.9
21.9/ 25.3
33.4/ 38.5

—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 11.6
—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 11.6
—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 14.7
—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 14.7
—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 14.7
—/ —
3.3/ 4.0
4.9/ 5.8
6.5/ 8.0
7.9/ 9.6
9.8/ 14.7

MCA

**

30/ 30
30/ 30
40/ 40
50/ 50
60/ 60
70/ 80
35/ 35
35/ 35
45/ 45
60/ 60
60/ 70
70/ 80
25/ 25
25/ 25
25/ 30
30/ 35
35/ 40
50/ 60
30/ 30
30/ 30
30/ 35
35/ 40
35/ 45
50/ 60
25/ 25
25/ 25
30/ 30
35/ 35
35/ 40
50/ 60
30/ 30
30/ 30
35/ 35
40/ 40
40/ 45
60/ 70

MOCP

POWER SUPPLY *

25.6/ 25.6
26.0/ 29.0
35.5/ 40.0
45.4/ 51.4
53.5/ 60.0
64.8/ 73.8
31.6/ 31.6
31.6/ 34.0
40.5/ 45.0
50.4/ 56.4
58.5/ 65.0
69.8/ 78.8
18.5/ 18.5
18.5/ 19.4
23.1/ 25.7
28.8/ 32.3
33.5/ 37.7
47.8/ 54.2
24.5/ 24.5
24.5/ 24.5
28.1/ 30.7
33.8/ 37.3
38.5/ 42.7
52.8/ 59.2
19.4/ 19.4
19.4/ 20.5
24.2/ 26.8
29.9/ 33.4
34.6/ 38.8
48.9/ 55.4
25.4/ 25.4
25.4/ 25.5
29.2/ 31.8
34.9/ 38.4
39.6/ 43.8
53.9/ 60.4

50HE,HJ

FLA

Actual
kW†

ELECTRIC HEAT

25/ 25
25/ 27
33/ 37
42/ 47
49/ 55
60/ 68
30/ 30
30/ 32
38/ 42
47/ 53
55/ 61
65/ 73
18/ 18
18/ 18
21/ 24
26/ 30
31/ 35
44/ 50
24/ 24
24/ 24
27/ 29
32/ 35
36/ 40
50/ 55
19/ 19
19/ 19
22/ 25
28/ 31
32/ 36
45/ 51
25/ 25
25/ 25
28/ 30
33/ 36
37/ 41
51/ 56

FLA

101/ 101
101/ 101
101/ 101
101/ 101
101/ 101
101/ 101
106/ 106
106/ 106
106/ 106
106/ 106
106/ 106
106/ 106
90/ 90
90/ 90
90/ 90
90/ 90
90/ 90
90/ 90
95/ 95
95/ 95
95/ 95
95/ 95
95/ 95
95/ 95
120/ 120
120/ 120
120/ 120
120/ 120
120/ 120
120/ 120
124/ 124
124/ 124
124/ 124
124/ 124
124/ 124
124/ 124

LRA

DISCONNECT SIZE

18

004
(3 tons)

UNIT
SIZE

575--- 3--- 60

460--- 3--- 60

NOMINAL
V--- PH--- Hz

HumidiMi$er

HS

STD

HS

STD

IFM TYPE

414

518
518
518
518
518
518

NO
YES
NO
YES
NO
YES

414

414

414

Min

YES

NO

YES

NO

CONV
OUTLET

632
632
632
632
632
632

508

508

508

508

Max

VOLTAGE
RANGE

1
1
1
1
1
1

1

1

1

1

QTY

4.2
4.2
4.2
4.2
4.2
4.2

5.1

5.1

5.1

5.1

RLA

31
31
31
31
31
31

39

39

39

39

LRA

1
1
1
1
1
1

1

1

1

1

QTY

0.4
0.4
0.4
0.4
0.4
0.4

0.4

0.4

0.4

0.4

FLA

OUTDOOR FAN

1.9
1.9
2.0
2.0
2.6
2.6

2.6

2.6

2.2

2.2

IFM
FLA
CRHEATER
--- --- A00 or
B00
—
006
007
008
009
—
006
007
008
009
—
006
007
008
009
—
006
007
008
009
—
—
—
—
—
—

Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (each)
FLA
—
7.2
10.6
13.8
16.8
—
7.2
10.6
13.8
16.8
—
7.2
10.6
13.8
16.8
—
7.2
10.6
13.8
16.8
—
—
—
—
—
—

Actual
kW†
—
5.5
8.1
10.6
12.9
—
5.5
8.1
10.6
12.9
—
5.5
8.1
10.6
12.9
—
5.5
8.1
10.6
12.9
—
—
—
—
—
—

ELECTRIC HEAT

50HE,HJ

9.0
11.8
16.0
20.0
23.8
11.7
15.1
18.7
22.7
26.5
9.4
12.3
16.5
20.5
24.3
12.1
15.6
19.2
23.2
27.0
7.3
9.5
7.7
9.8
7.7
9.8

MCA
20
20
20
25
25
20
20
20
25
30
20
20
20
25
25
20
20
20
25
30
20
20
10
15
10
15

MOCP

POWER SUPPLY *

**
9
11
15
18
22
11
13
17
21
24
9
11
15
19
22
12
14
18
21
25
7
9
8
10
8
10

FLA

46
46
46
46
46
48
48
48
48
48
60
60
60
60
60
62
63
63
63
63
36
30
40
42
48
50

LRA

DISCONNECT SIZE

19

005
(4 ton)

UNIT
SIZE

575--- 3--- 60

460--- 3--- 60

208/230--- 3--- 60

STD

208/230--- 1--- 60

HUMIDIZER

HS

STD

HS

STD

HS

STD

IFM TYPE

NOMINAL
V--- PH--- Hz

414

518
518
518
518
518
518

NO
YES
NO
YES
NO
YES

414

YES

NO

414

414

NO

YES

187

187

YES

NO

187

187

NO

YES

197

197

NO

YES

Min

CONV
OUTLET

632
632
632
632
632
632

508

508

508

508

254

254

254

254

254

254

Max

VOLTAGE RANGE

1
1
1
1
1
1

1

1

1

1

1

1

1

1

1

1

QTY

6.4
6.4
6.4
6.4
6.4
6.4

6.4

6.4

6.4

6.4

13.5

13.5

13.5

13.5

23.7

23.7

RLA

40
40
40
40
4
4

46.5

46.5

46.5

46.5

93

93

93

93

126

126

LRA

1
1
1
1
1
1

1

1

1

1

1

1

1

1

1

1

QTY

0.4
0.4
0.4
0.4
0.4
0.4

0.4

0.4

0.4

0.4

0.7

0.7

0.7

0.7

0.7

0.7

FLA

OUTDOOR FAN

1.9
1.9
2.0
2.0
2.6
2.6

2.6

2.6

2.2

2.2

5.8

5.8

4.9

4.9

4.9

4.9

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
001
003
002+002
003+003
004+004
—
001
003
002+002
003+003
004+004
—
002
003
005
004+004
—
002
003
005
004+004
—
002
003
005
004+004
—
002
003
005
004+004
—
006
008
009
008+008
—
006
008
009
008+008
—
006
008
009
008+008
—
006
008
009
008+008
—
—
—
—
—
—

Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (EACH)

—/—
15.9/ 18.3
31.4/ 36.3
46.9/ 54.2
62.8/ 72.5
75.8/ 87.5
—/—
15.9/ 18.3
31.4/ 36.3
46.9/ 54.2
62.8/ 72.5
75.8/ 87.5
—/—
13.6/ 15.6
18.1/ 20.9
33.4/ 38.5
43.8/ 50.5
—/—
13.6/ 15.6
18.1/ 20.9
33.4/ 38.5
43.8/ 50.5
—/—
13.6/ 15.6
18.1/ 20.9
33.4/ 38.5
43.8/ 50.5
—/—
13.6/ 15.6
18.1/ 20.9
33.4/ 38.5
43.8/ 50.5
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
7.2
13.8
16.8
27.7
—
—
—
—
—
—

—/—
3.3/ 4.0
6.5/ 8.0
9.8/ 11.6
13.1/ 16
16.0/ 19.3
—/—
3.3/ 4.0
6.5/ 8.0
9.8/ 11.6
13.1/ 16
16.0/ 19.3
—/—
4.9/ 5.8
6.5/ 8
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8
12/ 14.7
16/ 19.3
—/—
4.9/ 5.8
6.5/ 8
12/ 14.7
16/ 19.3
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
5.5
10.6
12.9
21.1
—
—
—
—
—
—

50HE,HJ

FLA

Actual kW{

ELECTRIC HEAT

35.2/ 35.2
35.2/ 35.2
45.4/ 51.4
64.8/ 73.8
84.7/ 96.8
100.9/ 115.5
41.2/ 41.2
41.2/ 41.2
50.4/ 56.4
69.8/ 78.8
89.7/ 101.8
105.9/ 120.5
22.5/ 22.5
23.1/ 25.7
28.8/ 32.3
47.8/ 54.2
60.8/ 59.3
28.5/ 28.5
28.5/ 30.7
33.8/ 37.3
52.8/ 59.2
65.8/ 74.3
23.4/ 23.4
24.2/ 26.8
29.9/ 33.4
48.9/ 55.4
62.0/ 70.4
29.4/ 29.4
29.4/ 31.8
34.9/ 38.4
53.9/ 60.4
67.0/ 75.4
10.6
11.8
20.0
23.8
37.3
13.3
15.1
22.7
26.5
40.0
11.0
12.3
20.5
24.3
37.8
13.7
15.6
23.2
27.0
40.5
10.3
12.5
10.4
12.6
10.4
12.6

45/ 45
45/ 45
50/ 60
70/ 80
90/ 100
110/ 125
50/ 50
50/ 50
60/ 60
70/ 80
90/ 100
110/ 125
30/ 30
30/ 30
30/ 35
50/ 60
70/ 70
35/ 35
35/ 35
35/ 40
60/ 60
70/ 80
30/ 30
30/ 30
35/ 35
50/ 60
70/ 80
35/ 35
35/ 35
40/ 40
60/ 70
70/ 80
20
20
25
25
40
20
20
25
30
45
20
20
25
25
40
20
20
25
30
45
15
15
15
15
15
15

MOCP**

POWER SUPPLY
MCA
34/ 34
34/ 34
42/ 47
60/ 68
78/ 89
93/ 106
39/ 39
39/ 39
47/ 53
65/ 73
83/ 95
98/ 112
22/ 22
22/ 24
26/ 30
44/ 50
56/ 64
27/ 27
27/ 29
32/ 35
50/ 55
62/ 69
23/ 23
23/ 25
28/ 31
45/ 51
57/ 65
29/ 29
29/ 30
33/ 36
51/ 56
63/ 70
10
11
18
22
34
13
13
21
24
37
11
11
19
22
35
13
14
21
25
37
10
12
10
12
10
12

FLA

139/ 139
139/ 139
139/ 139
139/ 139
139/ 139
139/ 139
144/ 144
144/ 144
144/ 144
144/ 144
144/ 144
144/ 144
106/ 106
106/ 106
106/ 106
106/ 106
106/ 106
111/ 111
111/ 111
111/ 111
111/ 111
111/ 111
136/ 136
136/ 136
136/ 136
136/ 136
136/ 136
140/ 140
140/ 140
140/ 140
140/ 140
140/ 140
53
54
54
54
54
55
56
56
56
56
67
68
68
68
68
70
70
70
70
70
45
47
52
53
57
59

LRA

DISCONNECT SIZE

20

006
(5 ton)

UNIT
SIZE

575--- 3--- 60

460--- 3--- 60

208/230--- 3--- 60

STD

208/230--- 1--- 60

HUMIDIZER

HS

STD

HS

STD

HS

STD

IFM TYPE

NOMINAL
V--- PH--- Hz

414

518
518
518
518
518
518

NO
YES
NO
YES
NO
YES

414

414

414

187

187

YES

NO

YES

NO

YES

NO

187

187

NO

YES

187

187

NO

YES

Min

CONV
OUTLET

632
632
632
632
632
632

508

508

508

508

254

254

254

254

254

254

Max

VOLTAGE RANGE

1
1
1
1
1
1

1

1

1

1

1

1

1

1

1

1

QTY

7.1
7.1
7.1
7.1
7.1
7.1

9

9

9

9

17.3

17.3

17.3

17.3

28.8

28.8

RLA

50
50
50
50
50
50

62

62

62

62

123

123

123

123

169

169

LRA

1
1
1
1
1
1

1

1

1

1

1

1

1

1

1

1

QTY

0.6
0.6
0.6
0.6
0.6
0.6

0.8

0.8

0.8

0.8

1.5

1.5

1.5

1.5

1.5

1.5

FLA

OUTDOOR FAN

2.0
2.0
2.8
2.8
3.4
3.4

3.4

3.4

2.6

2.6

7.5

7.5

5.8

5.8

8.8

8.8

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
002
003
002+002
003+003
004+004
—
002
003
002+002
003+003
004+004
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
—
—
—
—
—

Table 4 — Electrical Data--50HJ (cont)
COMPRESSOR (EACH)
FLA
—/—
23.5/ 27.1
31.4/ 36.3
46.9/ 54.2
62.8/ 72.5
75.8/ 87.5
—/—
23.5/ 27.1
31.4/ 36.3
46.9/ 54.2
62.8/ 72.5
75.8/ 87.5
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
7.2
13.8
16.8
27.7
30.1
—
—
—
—
—
—

Actual kW{
—/—
4.9/ 5.8
6.5/ 8.0
8.7/ 11.6
13.0/ 16.0
15.8/ 19.3
—/—
4.9/ 5.8
6.5/ 8.0
8.7/ 11.6
13.0/ 16.0
15.8/ 19.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
—
—
—
—
—

ELECTRIC HEAT

50HE,HJ

46.3/ 46.3
46.3/ 46.3
50.3/ 56.3
69.7/ 78.7
49.5/ 101.6
105.8/ 120.4
52.3/ 52.3
52.3/ 52.3
55.3/ 61.3
74.7/ 83.7
94.5/ 106.6
110.8/ 125.4
28.9/ 28.9
28.9/ 28.9
34.6/ 38.8
48.9/ 55.4
62/ 70.4
76.3/ 86.9
34.9/ 34.9
34.9/ 34.9
39.6/ 43.8
53.9/ 60.4
67/ 75.4
81.3/ 91.9
30.6/ 30.6
30.6/ 30.6
36.7/ 40.9
51.1/ 57.5
64.1/ 72.5
78.4/ 89.1
36.6/ 36.6
36.6/ 36.6
41.7/ 45.9
56.6/ 62.5
69.1/ 77.5
83.4/ 94.1
14.7
14.7
20.5
24.3
37.8
40.8
17.4
17.4
23.2
27.0
40.5
43.5
15.5
15.5
21.5
25.3
38.8
41.8
18.2
18.2
24.2
28.0
41.5
44.5
11.5
13.6
12.3
14.4
12.2
14.4

60/ 60
60/ 60
60/ 60
70/ 80
90/ 110
110/ 125
60/ 60
60/ 60
60/ 70
80/ 90
100/ 110
125/ 150
35/ 35
35/ 35
35/ 35
50/ 50
70/ 70
80/ 80
40/ 40
40/ 40
40/ 40
60/ 70
70/ 80
90/ 100
35/ 35
35/ 35
40/ 45
60/ 60
70/ 80
80/ 90
40/ 40
40/ 40
45/ 50
60/ 70
70/ 80
90/ 100
20
20
25
25
40
45
20
20
25
30
45
45
20
20
25
30
40
45
20
20
25
30
45
45
15
15
15
15
15
20

MOCP**

POWER SUPPLY
MCA
45/ 45
45/ 45
46/ 52
64/ 72
82/ 93
97/ 111
50/ 50
50/ 50
52/ 57
70/ 78
88/ 99
103/ 116
28/ 28
28/ 28
32/ 36
45/ 51
57/ 65
70/ 80
34/ 34
34/ 34
37/ 41
51/ 56
63/ 70
76/ 86
30/ 30
30/ 30
34/ 38
47/ 53
59/ 67
72/ 82
36/ 36
36/ 36
39/ 43
53/ 58
65/ 72
78/ 87
14
10
19
22
35
38
17
17
21
25
37
40
15
15
20
23
36
38
18
18
22
26
38
41
11
13
12
14
12
14

FLA

216/ 216
216/ 216
216/ 216
216/ 216
216/ 216
216/ 216
221/ 221
221/ 221
221/ 221
221/ 221
221/ 221
221/ 221
168/ 168
168/ 168
168/ 168
168/ 168
168/ 168
168/ 168
173/ 173
173/ 173
173/ 173
173/ 173
173/ 173
173/ 173
187/ 187
187/ 187
187/ 187
187/ 187
187/ 187
187/ 187
192/ 192
192/ 192
192/ 192
192/ 192
192/ 192
192/ 192
84
84
84
84
84
84
86
87
87
87
87
87
93
94
94
94
94
94
96
96
96
96
96
96
63
64
72
73
76
77

LRA

DISCONNECT SIZE

21

007
(6 ton)

UNIT
SIZE

575--- 3--- 60

460--- 3--- 60

208/230--- 3--- 60

NOMINAL
V--- PH--- Hz

HUMIDIMIZER

HS

STD

HS

STD

HS

STD

IFM
TYPE

632

518
518

NO

YES

632

632
632
632
632

518
518
518
518

NO
YES
NO
YES

508

508

508

508

254

254

414

414

414

414

187

187

254

254

Max

YES

NO

YES

NO

YES

NO

187

187

NO

YES

Min

CONV
OUTLET

VOLTAGE
RANGE

1

1

1
1
1
1

1

1

1

1

1

1

1

1

QTY

7.7

7.7

7.7
7.7
7.7
7.7

9.6

9.6

9.6

9.6

20.5

20.5

20.5

20.5

RLA

56

56

56
56
56
56

75

75

75

75

156

156

156

156

LRA

COMPRESSOR (each)

1

1

1
1
1
1

1

1

1

1

1

1

1

1

QTY

0.6

0.6

0.6
0.6
0.6
0.6

0.6

0.6

0.6

0.6

1.4

1.4

1.4

1.4

FLA

OUTDOOR FAN

3.4

3.4

2.0
2.0
2.8
2.8

3.4

3.4

2.6

2.6

7.5

7.5

5.8

5.8

IFM
FLA

—

—

CRHEATER
--- --- --- A00 or
B00
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
002
004
005
004+004
004+005
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
006
008
009
008+008
008+009
—
—
—
—
—

—

—

—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—/—
13.6/ 15.6
21.9/ 25.3
33.4/ 38.5
43.8/ 50.5
55.2/ 63.8
—
7.2
13.8
16.8
27.7
30.7
—
7.2
13.8
16.8
27.7
30.7
—
7.2
13.8
16.8
27.7
30.7
—
7.2
13.8
16.8
27.7
30.7
—
—
—
—

—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—/—
4.9/ 5.8
7.9/ 9.6
12.0/ 14.7
15.8/ 19.3
19.9/ 24.3
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
5.5
10.6
12.9
21.1
23.4
—
—
—
—
—

FLA

Actual
kW†

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

50HE,HJ

14.4

12.2

32.8/ 32.8
32.8/ 32.8
34.6/ 38.8
48.9/ 55.4
62.0/ 70.4
76.3/ 86.9
38.8/ 38.8
38.8/ 38.8
39.6/ 43.8
53.9/ 60.4
67.0/ 75.4
76.3/ 86.9
34.5/ 34.5
34.5/ 34.5
36.7/ 40.9
51.1/ 57.5
64.1/ 72.5
78.4/ 89.1
40.5/ 40.5
40.5/ 40.5
41.7/ 45.9
56.1/ 62.5
69.1/ 77.5
83.4/ 94.1
15.2
15.2
20.5
24.3
37.8
41.6
17.9
17.9
23.2
27.0
40.5
44.3
16.0
16.0
21.5
25.3
38.8
42.6
18.7
18.7
24.2
28.0
41.5
45.3
11.5
13.6
12.3
14.4

MCA

**

20

15

40/ 40
40/ 40
40/ 40
50/ 50
70/ 80
80/ 90
45/ 45
45/ 45
45/ 45
60/ 70
70/ 80
90/ 100
40/ 40
40/ 40
40/ 45
60/ 60
70/ 80
80/ 90
45/ 45
45/ 45
45/ 50
60/ 70
70/ 80
90/ 100
20
20
25
25
40
45
20
20
25
30
45
45
20
20
25
30
40
45
25
25
25
30
45
50
15
15
15
20

MOCP

POWER SUPPLY *

14

12

32/ 32
32/ 32
32/ 36
45/ 51
57/ 65
70/ 80
37/ 37
37/ 37
37/ 41
51/ 56
63/ 70
76/ 86
34/ 34
34/ 34
34/ 38
47/ 53
59/ 67
72/ 82
39/ 39
39/ 39
39/ 43
53/ 58
65/ 72
78/ 87
15
15
19
22
35
38
17
17
21
25
37
41
16
16
20
23
36
39
18
18
22
26
38
42
11
13
12
14

FLA

77

76

200/ 200
200/ 200
200/ 200
200/ 200
200/ 200
200/ 200
205/ 205
205/ 205
205/ 205
205/ 205
205/ 205
205/ 205
219/ 219
219/ 219
219/ 219
219/ 219
219/ 219
219/ 219
224/ 224
224/ 224
224/ 224
224/ 224
224/ 224
224/ 224
97
97
97
97
97
97
99
99
99
99
99
99
106
107
107
107
107
107
108
109
109
109
109
109
63
64
72
73

LRA

DISCONNECT SIZE

22

008
(7.5
ton)

UNIT
SIZE

460--- 3--- 60

208/230--- 3--- 60

NOMINAL
V--- PH--- Hz

HS

STD

HS

STD

IFM
TYPE

414

414

YES

414

414

187

187

NO

YES

NO

YES

NO

187

187

NO

YES

Min

CONV
OUTLET

508

508

508

508

254

254

254

254

Max

VOLTAGE RANGE

2

2

2

2

2

2

2

2

QTY

6.4

6.4

6.4

6.4

12.4

12.4

12.4

12.4

RLA

44

44

44

44

88

88

88

88

LRA

COMPRESSOR (each)

2

2

2

2

2

2

2

2

QTY

0.7

0.7

0.7

0.7

1.4

1.4

1.4

1.4

FLA

OUTDOOR FAN

4.8

4.8

3.4

3.4

10.6

10.6

7.5

7.5

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
016
013
014
015
014+016
—
016
013
014
015
014+016
—
016
013
014
015
014+016
—
016
013
014
015
014+016
FLA
—/—
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/—
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/—
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/—
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2

Actual kW{
—/—
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/—
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/—
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/—
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

38.2/ 38.2
38.2/ 40.6
51.1/ 57.5
74.0/ 84.0
92.8/ 105.6
119.9/ 136.9
44.2/ 44.2
44./ 45.6
56.1/ 62.5
79.0/ 89.0
97.8/ 110.6
124.9/ 141.9
41.3/ 41.3
41.3/ 44.5
54.9/ 61.4
77.9/ 87.8
96.6/ 109.5
123.7/ 140.8
47.3/ 47.3
47.3/ 49.5
59.9/ 66.4
82.9/ 92.8
101.6/ 114.5
128.7/ 145.8
19.2
25.1
29.1
46.0
53.9
66.9
21.9
28.5
31.8
48.7
56.6
69.6
20.6
26.9
30.8
47.8
55.6
68.7
23.3
30.3
33.5
50.5
58.3
71.4

MCA
45/ 45
45/ 45
60/ 60
80/ 90
100/ 110
125/ 150
50/ 50
50/ 50
60/ 70
80/ 90
100/ 125
125/ 150
45/ 45
50/ 50
60/ 70
80/ 90
100/ 110
125/ 150
50/ 50
60/ 60
70/ 70
90/ 100
110/ 125
150/ 150
20
20
20
50
60
70
20
20
35
50
60
70
20
20
35
50
60
70
20
35
35
60
60
80

MOCP**

POWER SUPPLY*

50HE,HJ

40/ 40
40/ 40
47/ 53
68/ 77
85/ 97
110/ 126
46/ 46
46/ 46
53/ 58
74/ 83
91/ 103
116/ 131
44/ 44
44/ 44
51/ 56
72/ 81
89/ 101
114/ 129
49/ 49
49/ 49
56/ 62
77/ 86
94/ 106
119/ 135
20
23
27
42
50
62
23
26
29
45
52
64
22
25
28
44
51
63
24
27
31
46
54
66

FLA
242/ 242
242/ 242
242/ 242
242/ 242
242/ 242
242/ 242
247/ 247
247/ 247
247/ 247
247/ 247
247/ 247
247/ 247
267/ 267
267/ 267
267/ 267
267/ 267
267/ 267
267/ 267
271/ 271
271/ 271
271/ 271
271/ 271
271/ 271
271/ 271
121
121
121
121
121
121
123
123
123
123
123
123
133
134
134
134
134
134
135
136
136
136
136
136

LRA

DISCONNECT SIZE

23

NOMINAL
V--- PH--- Hz

575--- 3--- 60

UNIT
SIZE

008
(7.5
ton)

HUMIDIMIZER

HS

STD

IFM
TYPE

518

518

518

NO

YES

518

NO

YES

518

518

NO

YES

Min

CONV
OUTLET

632

632

632

632

632

632

Max

VOLTAGE RANGE

2

2

2

2

2

2

QTY

4.8

4.8

4.8

4.8

4.8

4.8

RLA

34

34

34

34

34

34

LRA

COMPRESSOR (each)

2

2

2

2

2

2

QTY

0.7

0.7

0.6

0.6

0.6

0.6

FLA

OUTDOOR FAN

4.8

4.8

3.3

3.3

2.8

2.8

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
018
019
—
018
019
—
018
019
—
018
019
—
018
019
—
018
019
FLA
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7

Actual kW{
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

50HE,HJ

14.8
23.9
44.4
17.0
26.6
44.4
15.3
24.6
45.0
17.5
27.2
45.0
15.8
25.5
45.7
17.9
27.9
45.7

20
25
45
20
30
45
20
25
50
20
30
50
20
30
50
20
30
50

MOCP**

POWER SUPPLY*
MCA
16
22
41
18
24
43
16
23
42
18
25
44
17
23
42
19
25
44

FLA
91
91
91
93
93
93
101
101
101
103
103
103
104
104
104
106
106
106

LRA

DISCONNECT SIZE

24

009
(8.5
ton)

UNIT
SIZE

460--- 3--- 60

208/230--- 3--- 60

NOMINAL
V--- PH--- Hz

HS

STD

HS

STD

IFM
TYPE

YES

NO

YES

NO

YES

NO

414

414

414

414

187

187

187

187

NO

YES

Min

CONV
OUTLET

508

508

508

508

254

254

254

254

Max

VOLTAGE RANGE

2

2

2

2

2

2

2

2

QTY

7.4

7.4

7.4

7.4

13.4

13.4

13.4

13.4

RLA

55

55

55

55

105

105

105

105

LRA

COMPRESSOR (each)

2

2

2

2

2

2

2

2

QTY

0.7

0.7

0.7

0.7

1.4

1.4

1.4

1.4

FLA

OUTDOOR FAN

4.8

4.8

3.4

3.4

10.6

10.6

7.5

7.5

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
017
010
011
012
012+017
—
016
013
014
015
014+016
—
016
013
014
015
014+016
—
016
013
014
015
014+016
—
016
013
014
015
014+016
FLA
—/ —
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/ —
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/ —
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—/ —
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/ 102.0
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2
—
16.7
19.8
33.4
39.7
50.2

Actual kW{
—/ —
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/ —
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/ —
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—/ —
7.8/ 9.6
12.0/ 14.7
18.6/ 22.8
24.0/ 29.4
31.8/ 38.9
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3
—
12.8
15.2
25.5
30.3
38.3

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

40.2/ 40.2
40.2/ 40.6
51.1/ 57.5
74.0/ 84.0
92.8/ 105.6
119.9/ 136.9
46.2/ 46.2
46.2/ 46.2
56.1/ 62.5
79.0/ 89.0
97.8/ 110.6
124.9/ 141.9
43.3/ 43.3
43.3/ 44.5
54.9/ 61.4
77.9/ 87.8
96.6/ 109.5
123.7/ 140.8
49.3/ 49.3
49.3/ 49.5
59.9/ 66.4
82.9/ 92.8
101.6/ 114.5
128.7/ 145.8
21.5
25.1
29.1
46.0
53.9
66.9
24.2
28.5
31.8
48.7
56.6
69.6
22.9
26.9
30.8
47.8
55.6
68.7
25.6
30.3
33.5
50.5
58.3
71.4

MCA
45/ 45
45/ 45
60/ 60
80/ 90
100/ 110
110/ 150
50/ 50
50/ 50
60/ 70
80/ 90
100/ 125
125/ 150
50/ 50
50/ 50
60/ 70
80/ 90
100/ 110
125/ 150
60/ 60
60/ 60
70/ 70
90/ 100
110/ 125
150/ 150
30
30
30
50
60
70
30
30
35
50
60
70
30
30
35
50
60
70
30
35
35
60
60
80

MOCP**

POWER SUPPLY

50HE,HJ

42/ 42
42/ 42
47/ 53
68/ 77
85/ 97
110/ 126
48/ 48
48/ 48
53/ 58
74/ 83
91/ 103
116/ 131
46/ 46
46/ 46
51/ 56
72/ 81
89/ 101
114/ 129
51/ 51
51/ 51
56/ 62
77/ 86
94/ 106
119/ 135
23
23
27
42
50
62
25
26
29
45
52
64
24
25
28
44
51
63
27
27
31
46
54
66

FLA
276/ 276
276/ 276
276/ 276
276/ 276
276/ 276
276/ 276
281/ 281
281/ 281
281/ 281
281/ 281
281/ 281
281/ 281
301/ 301
301/ 301
301/ 301
301/ 301
301/ 301
301/ 301
305/ 305
305/ 305
305/ 305
305/ 305
305/ 305
305/ 305
143
143
143
143
143
143
145
145
145
145
145
145
155
156
156
156
156
156
157
158
158
158
158
158

LRA

DISCONNECT SIZE

25

NOMINAL
V--- PH--- Hz

575--- 3--- 60

UNIT
SIZE

009
(8.5
ton)

HUMIDIMIZER

HS

STD

IFM
TYPE

518

518

518

NO

YES

518

NO

YES

518

518

NO

YES

Min

CONV
OUTLET

632

632

632

632

632

632

Max

VOLTAGE RANGE

2

2

2

2

2

2

QTY

6.4

6.4

6.4

6.4

6.4

6.4

RLA

44

44

44

44

44

44

LRA

COMPRESSOR (each)

2

2

2

2

2

2

QTY

0.7

0.7

0.6

0.6

0.6

0.6

FLA

OUTDOOR FAN

3.3

3.3

3.3

3.3

2.8

2.8

IFM
FLA

CRHEATER
--- --- A00 or
B00
—
018
019
—
018
019
—
018
019
—
018
019
—
018
019
—
018
019
FLA
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7
—
16.4
32.7

Actual kW{
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0
—
17.0
34.0

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

50HE,HJ

18.4
23.9
44.4
20.6
26.6
44.4
18.9
24.6
45.0
21.1
27.9
45.0
19.4
25.2
45.7
21.5
27.9
48.3

25
25
45
25
30
45
25
25
50
25
30
50
25
30
50
25
30
50

MOCP**

POWER SUPPLY
MCA
19
22
41
21
24
43
20
23
41
22
25
43
20
23
42
22
25
44

FLA
111
111
111
113
113
113
121
121
121
123
123
123
124
124
124
126
126
126

LRA

DISCONNECT SIZE

26

012
(10 ton)

UNIT
SIZE

460--- 3--- 60

208/230--- 3--- 60

NOMINAL
V--- PH--- Hz

HS

STD

HS

STD

IFM
TYPE

YES

NO

YES

NO

YES

NO

414

414

414

414

187

187

187

187

NO

YES

Min

CONV
OUTLET

508

508

508

508

254

254

254

254

Max

VOLTAGE
RANGE

2

2

2

2

2

2

2

2

QTY

8.3

8.3

8.3

8.3

17.6

17.6

17.6

17.6

RLA

62.5

62.5

62.5

62.5

125

125

125

125

LRA

COMPRESSOR (each)

2

2

2

2

2

2

2

2

QTY

0.7

0.7

0.7

0.7

1.4

1.4

1.4

1.4

FLA

7.4

7.4

4.8

4.8

15

15

10.6

10.6

IFM
FLA
CRHEATER
--- --- A00 or
B00
—
017
010
012
012+017
012+010
—
017
010
012
012+017
012+010
—
017
010
012
012+017
012+010
—
017
010
012
012+017
012+010
—
016
013
015
014+016
015+013
—
016
013
015
014+016
015+013
—
016
13
15
014+016
015+013
—
016
013
015
014+016
015+013
FLA
—/ —
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 104.2
—/ —
21./ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 120.3
—/ —
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 120.3
—/ —
21./ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 120.3
—
16.7
19.8
39.7
50.2
60.1
—
16.7
19.8
39.7
50.2
60.1
—
16.7
19.8
39.7
50.2
60.1
—
16.7
19.8
39.7
50.2
60.1

Actual kW{
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—
12.8
15.2
30.3
38.3
45.9
—
12.8
15.2
30.3
38.3
45.9
—
12.8
15.2
30.3
38.3
45.9
—
12.8
15.2
30.3
38.3
45.9

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)
OUTDOOR FAN

53.0/ 53.0
53.0/ 53.0
54.9/ 61.4
96.6/ 109.5
123.7/ 140.8
143.5/ 133.5
59.0/ 59.0
59.0/ 59.0
59.9/ 66.4
101.6/ 114.5
128.7/ 145.8
148.5/ 137.5
57.4/ 57.4
57.4/ 57.4
60.4/ 66.9
102.1/ 115.0
129.2/ 146.3
149.0/ 139.0
63.4/ 63.4
63.4/ 63.4
65.4/ 71.9
107.1/ 120.0
134.2/ 151.3
154.0/ 143.0
24.9
26.9
30.8
55.6
68.7
66.1
27.6
30.3
33.5
58.3
71.4
70.1
27.5
30.1
34.1
58.9
71.9
69.4
30.2
33.5
36.8
61.6
74.6
73.4

MCA
60/ 60
60/ 60
60/ 70
100/ 110
125/ 150
150/ 150
70/ 70
70/ 70
70/ 70
110/ 125
150/ 150
150/ 150
70/ 70
70/ 70
70/ 80
110/ 125
150/ 150
150/ 175
70/ 70
70/ 70
80/ 80
110/ 125
150/ 175
175/ 175
30
30
35
60
70
80
30
35
35
60
80
80
30
35
40
60
80
80
35
40
40
70
80
80

MOCP**

POWER SUPPLY

50HE,HJ

56/ 56
56/ 56
56/ 56
89/ 101
114/ 129
132/ 151
61/ 61
61/ 61
61/ 62
94/ 106
119/ 135
138/ 156
61/ 61
62/ 62
61/ 62
94/ 106
119/ 135
137/ 156
66/ 66
66/ 66
66/ 67
99/ 111
124/ 140
143/ 161
26
26
28
51
63
75
29
29
31
54
66
77
29
29
31
54
66
78
32
32
34
57
69
80

FLA
341/ 341
341/ 341
341/ 341
341/ 341
341/ 341
341/ 341
345/ 345
345/ 345
345/ 345
345/ 345
345/ 345
345/ 345
364/ 364
364/ 364
364/ 364
364/ 364
364/ 364
364/ 364
369/ 369
369/ 369
369/ 369
369/ 369
369/ 369
369/ 369
170
171
171
171
171
171
172
173
173
173
173
173
182
182
182
182
182
182
184
184
184
184
184
184

LRA

DISCONNECT SIZE

27

NOMINAL
V--- PH--- Hz

575--- 3--- 60

UNIT
SIZE

012
(10 ton)

HUMIDIMIZER

HS

STD

IFM
TYPE

YES

NO

518

518

518

518

NO

YES

518

518

NO

YES

Min

CONV
OUTLET

632

632

632

632

632

632

Max

VOLTAGE
RANGE

2

2

2

2

2

2

QTY

6.3

6.3

6.3

6.3

6.3

6.3

RLA

50

50

50

50

50

50

LRA

COMPRESSOR (each)

2

2

2

2

2

2

QTY

0.7

0.7

0.6

0.6

0.6

0.6

FLA

7.4

7.4

5.6

5.6

3.3

3.3

IFM
FLA
CRHEATER
--- --- A00 or
B00
—
18
019
018+019
—
018
019
018+019
—
018
019
018+019
—
018
019
018+019
—
018
019
018+019
—
018
019
018+019
FLA
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1

Actual kW{
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)
OUTDOOR FAN

25
25
50
60
25
30
50
60
25
30
50
70
25
35
60
70
25
30
50
70
25
50
60
70

MOCP**

50HE,HJ

18.7
24.6
45.0
53.2
20.8
27.2
45.0
55.8
21.0
27.4
47.9
56.1
23.1
30.1
47.9
58.7
21.2
27.8
48.3
56.5
23.4
30.5
50.9
59.1

MCA

POWER SUPPLY

20
23
41
60
22
25
43
62
22
25
44
63
24
27
46
65
23
26
44
63
25
28
46
65

FLA
133
133
133
133
135
135
135
135
139
139
139
139
141
141
141
141
146
146
146
146
148
148
148
148

LRA

DISCONNECT SIZE

28

014
(12.5
tons)

STD

460--- 3--- 60

HUMIDIMIZER

YES

NO

518

518

518

518

NO

YES

414

414

NO

YES

187

187

Min

YES

NO

CONV
OUTLET

FLA ---Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps

575--- 3--- 60

STD

208/230--- 3--- 60

STD

IFM
TYPE

NOMINAL
V--- PH--- Hz

632

632

632

632

508

508

254

254

Max

2

2

2

2

2

2

2

2

QTY

7.4

7.4

7.4

7.4

9

9

19

19

RLA

54

54

54

54

70

70

156

156

LRA

COMPRESSOR (each)

2

2

2

2

2

2

2

2

QTY

0.7

0.7

0.6

0.6

0.7

0.7

1.4

1.4

FLA

OUTDOOR FAN

7.4

7.4

5.6

5.6

7.4

7.4

15

15

IFM
FLA
CRHEATER
--- --- A00 OR
B00
—
017
010
012
012+017
012+010
—
016
013
015
014+016
015+013
—
016
013
015
014+016
015+013
—
016
013
015
014+016
015+013
—
018
019
018+019
—
018
019
018+019
—
18
019
018+019
—
18
019
018+019
FLA
—/ —
21.7// 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 120.3
—/ —
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/ 102.0
104.2/ 120.3
—
16.7
19.8
39.7
50.2
60.1
—
16.7
19.8
39.7
50.2
60.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1
—
16.4
32.7
49.1

Actual kW{
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—/ —
7.8/ 9.6
12.0/ 14.7
24.0/ 29.4
31.8/ 38.9
37.5/ 45.9
—
12.8
15.2
30.3
38.3
45.9
—
12.8
15.2
30.3
38.3
45.9
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0
—
17.0
34.0
51.0

ELECTRIC HEAT

Table 4 — Electrical Data--50HJ (cont)

NOTES:
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
{ Heater capacity (kW) is based on heater voltage of 240v, 480v or 575v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly

UNIT SIZE

VOLTAGE
RANGE

60.6/ 60.6
60.6/ 60.6
60.4/ 66.9
102.1/ 115.0
129.2/ 146.3
149.0/ 139.0
66.6/ 66.6
66.6/ 66.6
65.4/ 71.9
107.1/ 120.0
134.2/ 151.3
154.0/ 143.0
29.1
30.1
34.1
58.9
71.9
69.4
31.8
33.5
36.8
61.6
74.6
73.4
23.5
27.4
47.9
56.1
25.6
30.1
47.9
58.7
23.7
27.8
48.3
56.5
25.9
30.5
50.9
59.1

MCA
70/ 70
70/ 70
70/ 70
110/ 125
150/ 150
150/ 175
70/ 70
70/ 70
80/ 80
110/ 125
150/ 175
175/ 175
35
35
40
60
80
80
35
40
40
70
80
80
30
30
50
70
30
35
50
70
30
35
50
70
35
40
60
80

MOCP**

POWER SUPPLY

50HE,HJ

64/ 64
64/ 64
64/ 64
94/ 106
119/ 135
137/ 156
70/ 70
70/ 70
70/ 70
99/ 111
124/ 140
143/ 161
31
31
31
54
66
78
33
33
34
57
69
80
25
25
44
63
27
27
46
65
25
26
44
63
27
28
46
65

FLA
426/426
426/426
426/426
426/426
426/426
426/426
431/431
431/431
431/431
431/431
431/431
431/431
197
197
197
197
197
197
199
199
199
199
199
199
147
147
147
147
149
149
149
149
154
154
154
154
155
155
155
155

LRA

DISCONNECT SIZE

% RELATIVE HUMIDITY

Fig. 14 --- Accessory Field--Installed Humidistat

Fig. 15 --- Light Commercial thermidistat Device

C06126

C06127

To install the humidistat:
1. Route humidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between
high--voltage and low voltage wiring. For models without
a raceway, ensure to provide the NEC required clearance
between high--voltage and low--voltage wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 16.

To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post on the left side of control box (See Fig.
13.) This raceway provides the required clearance between
high--voltage and low voltage wiring. For models without
a raceway, ensure to provide the NEC required clearance
between high--voltage and low--voltage wiring.
3. A field-supplied relay must be installed between the
thermidistat and the Humidi-Mizer circuit (recommended
relay: HN612KK324). (See Fig. 17.) The relay coil is
connected between the DEHUM output and C (common)
of the unit. The relay controls the Humidi-MiZer solenoid
valve and must be wired between the Humidi-MiZer fuse
and the low-pressure switch. Refer to the installation
instructions included with the Carrier Light Commercial
Thermidistat device for more information.
Disconnect Switch
The optional disconnect switch is non--fused. The switch has the
capability of being locked in place for safety purposes.
Manual Outdoor Damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
(See Fig. 18.)
3. Remove evaporator coil access panel. Separate hood and
screen from basepan by removing the 4 screws securing
them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 19 for hood details. Secure top of hood with the
4 screws removed in Step 3. (See Fig. 20.)
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. (See Fig. 19 and 20.) Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on the
front of the damper blade. (See Fig. 18.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 21. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. (See
Fig. 20.)
Convenience Outlet
An optional convenience outlet provides power for rooftop use.
For maintenance personnel safety, the convenience outlet power
is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.
Novar Controls
Optional Novar controls (ETM 3051) are available for
replacement or new construction jobs.

29

50HE,HJ

Step 6 —Adjust Factory-Installed Options
Cobra™ Energy Recovery Units
Please refer to the supplement provided for information on
installing and operating the factory optional COBRA Energy
Recovery Units. These units are equipped with a factory--installed
energy recovery unit and have different installation and operation
procedures than the standard unit.
Humidi--Mizer™ Adaptive Dehumidification
System
Humidi--MiZer system operation can be controlled by field
installation of a Carrier--approved humidistat. (See Fig. 14.)
NOTE: A light commercial Thermidistat™ device (Fig. 15) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided (units with PremierLink™ control).

50HE,HJ

LEGEND
CB
CR
DHR
DSV
HR
LPS
LSV
LTLO

—
—
—
—
—
—
—
—

Circuit Breaker
Cooling Relay
Dehumidify Relay
Discharge Solenoid Valve
Heater Relay
Low Pressure Switch
Liquid Solenoid Valve
Low Temperature Lockout

Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring

Field Splice

C06128

Fig. 16 --- Typical Humidi--MiZert Adaptive Dehumidification System
Humidistat Wiring (208/230--V Unit Shown)
LCT

ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2

R
C
Y1
Y2
G
W1
W2
DEHUM
OC

CB
LCT
LLSV
LTLO

—
—
—
—

R1
PINK

TSTATWIRES

LEGEND
Circuit Breaker
Light Commercial Thermidistat™ Device
Liquid Line Solenoid Valve
Low Temperature Lockout

R1

PINK

CB
3.2 AMPS

LTLO

RED
PINK

24 V
FROM
HUMIDI-MIZER SYSTEM
LLSV

HUMIDI-MIZER SYSTEM

Fig. 17 --- Typical Rooftop Unit with Humidi--Mizer
Adaptive Dehumidification System with Thermidistat Device

C06129

OUTDOOR
AIR OPENING
PANEL

3 SCREWS
(SIDE)

C06130

Fig. 18 --- Damper Panel with Manual Outdoor--Air
Damper Installed

Fig. 19 --- Outdoor--Air Hood Details

30

C06013

Fig. 21 --- Outdoor--Air Damper Position Setting

C06131

C06132

Premierlink™ Control
The PremierLink controller is compatible with Carrier Comfort
NetworkR (CCN) devices. This control is designed to allow
users the access and ability to change factory--defined settings,
thus expanding the function of the standard unit control board.
Carrier’s diagnostic standard tier display tools such as
Navigatort or Scrolling Marquee can be used with the
PremierLink controller.
The PremierLink controller (see Fig. 22 and 23) requires the use
of a Carrier electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is necessary for
broadcast of time of day functions (occupied/unoccupied). No
sensors are supplied with the field--mounted PremierLink control.
The factory--installed PremierLink control includes only the
supply--air temperature (SAT) sensor and the outdoor air
temperature (OAT) sensor as standard. An indoor air quality
(CO2) sensor can be added as an option. Refer to Table 5 for
sensor usage. Refer to Fig. 24 for PremierLink controller wiring.
The PremierLink control may be mounted in the control panel or
an area below the control panel.
NOTE: PremierLink controller versions 1.3 and later are shipped
in Sensor mode. If used with a thermostat, the PremierLink
controller must be configured to Thermostat mode.

31

50HE,HJ

Fig. 20 --- Outdoor--Air Damper With
Hood Attached

Install the Supply Air Temperature (SAT) Sensor
When the unit is supplied with a factory--mounted PremierLink
control,
the
supply--air
temperature
(SAT)
sensor
(33ZCSENSAT) is factory--supplied and wired. The wiring is
routed from the PremierLink control over the control box,
through a grommet, into the fan section, down along the back
side of the fan, and along the fan deck over to the supply--air
opening.
The SAT probe is wire--tied to the supply--air opening (on the
horizontal opening end) in its shipping position. Remove the
sensor for installation. Re--position the sensor in the flange of the
supply--air opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct. Use
two field--supplied, self--drilling screws to secure the sensor probe
in a horizontal orientation.
NOTE: The sensor must be mounted in the discharge airstream
downstream of the cooling coil and any heating devices. Be sure
the probe tip does not come in contact with any of the unit or heat
surfaces.
Outdoor Air Temperature Sensor (OAT)
When the unit is supplied with a factory-mounted PremierLink
control, the outdoor-air temperature sensor (OAT) is
factory-supplied and wired.
Install the Indoor Air Quality (CO2) Sensor
Mount the optional indoor air quality (CO2) sensor according to
manufacturer specifications.
A separate field-supplied transformer must be used to power the
CO2 sensor.
Wire the CO2 sensor to the COM and IAQI terminals of J5 on the
PremierLink controller. Refer to the PremierLink Installation,
Start-up, and Configuration Instructions for detailed wiring and
configuration information.
Enthalpy Sensors and Control
The enthalpy control (HH57AC077) is supplied as a
field-installed accessory to be used with the EconoMi$er2
damper control option. The outdoor air enthalpy sensor is part of
the enthalpy control. The separate field-installed accessory return
air enthalpy sensor (HH57AC078) is required for differential
enthalpy control.
NOTE: The enthalpy control must be set to the “D” setting for
differential enthalpy control to work properly.
The enthalpy control receives the indoor and return
enthalpy from the outdoor and return air enthalpy sensors and
provides a dry contact switch input to the PremierLink controller.
Locate the controller in place of an existing economizer controller
or near the actuator. The mounting plate may not be needed if
existing bracket is used.
A closed contact indicates that outside air is preferred to the
return air. An open contact indicates that the economizer should
remain at minimum position.
Outdoor Air Enthalphy Sensor/Enthalpy Controller
(HH57AC077)
To wire the outdoor air enthalpy sensor, perform the following (See
Fig. 25 and 26):
NOTE: The outdoor air sensor can be removed from the back of
the enthalpy controller and mounted remotely.

50HE,HJ

Table 5—PremierLink™ Sensor Usage
APPLICATION

OUTDOOR AIR
TEMPERATURE SENSOR

RETURN AIR
TEMPERATURE SENSOR

OUTDOOR AIR
ENTHALPY SENSOR

RETURN AIR
ENTHALPY SENSOR

Dry Bulb
Temperature with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)

Included --CRTEMPSN001A00

—

—

—

Differential Dry Bulb
Temperature with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)

Included --CRTEMPSN001A00

Required --33ZCT55SPT
or Equivalent

—

—

Single Enthalpy with
PremierLink*
(PremierLink
requires 4-20 mA
Actuator)

Included --Not Used

—

Required --HH57AC077
or Equivalent

—

Differential Enthalpy
with PremierLink*
(PremierLink
requires 4-20 mA
Actuator)

Included --Not Used

—

Required --HH57AC077
or Equivalent

Required --HH57AC078
or Equivalent

*PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature sensor CRTEMPSN001A00
— Included with factory-installed PremierLink control; field-supplied and field-installed with field-installed PremierLink control.
NOTES:
1. CO2 Sensors (Optional):
33ZCSENCO2 — Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 — Aspirator box used for duct-mounted CO2 room sensor.
33ZCT55CO2 — Space temperature and CO2 room sensor with override.
33ZCT56CO2 — Space temperature and CO2 room sensor with override and set point.
2. All units include the following Standard Sensors:
Outdoor-Air Sensor — 50HJ540569 — Opens at 67_F, closes at 52_F, not adjustable.
Mixed-Air Sensor — HH97AZ001 — (PremierLink control requires Supply Air Temperature sensor 33ZCSENSAT
and Outdoor Air Temperature Sensor CRTEMPSN001A00)
Compressor Lockout Sensor — 50HJ540570 — Opens at 35_F, closes at 50_F.

Fig. 22 --- PremierLink Controller

32

C06016

PREMIERLINK
CONTROL

50HE,HJ

HINGED
DOOR
PANEL

C06017

Fig. 23 --- PremierLinktController (Installed)

BLK

VIO

RED

VIO

OAT

7

7

6

6

YEL

BLK
RED
BLU
YEL
WHT

11

10

10

8

8

2

2

3

3

4

Space Temp./ Set
Point Adjustment

Indoor Air
Quality Sensor

Outdoor Air
Quality Sensor

4

1

1

5

5

9

9

12

12

TR
SR

Power Exhaust/Energy Recycler

GRA

RMTOCC

PNK

BRN

3

BLK

4

BRN

5

RED

BRN
ORN

RED

PNK
BRN

BRN

BLU

PremierLink

GRN

6

BRN

7

BLU

8

ORN

YEL
BLU
WHT
PNK

1

PNK
GRN

GRA

J9
0-20 mA

J2
J1
PWR COMMS

GRA
GRA

BLK

RED

Economi$er2
4 - 20mA

BLU

2

Y1

SFS

4

WHT

3

Y2

ORN

5

PNK

4

W1

ORN

6

RED

5

W2

PNK

7

WHT

6

G

8

BLK

7

C

8

X

+

RETURN AIR
ENTHALPY
SENSOR

GRA

COMMS —
OAT
—
PWR
—
RTU
—
SAT
—
TB
—

BRN

LEGEND
Communications
Outdoor Air Temperature Sensor
Power
Rooftop Unit
Supply Air Temperature Sensor
Terminal Block

Fig. 24 --- Typical PremierLink Control Wiring
33

ORN ORN

PNK
ORN
RED

3

CCN
Comm.

S

RED

FSD

GRAY
GRAY

RED

TB - 1
R
1

YEL

+

J8
Relays

WHT GRA

BRN

TR1

BLK

J7
PP/MP

2

CMPSAFE

OUTDOOR AIR
ENTHALPY SENSOR

RED
BRN

BLU

2

TB - 3

ORN

3

2

1

BLK

J4
DISCRETE

BLU

VIO

HK50AA039

BLU

BRN

J5
0 - 20 mA IN

11

PNK

J6
ANAL OG

PNK

TB - 2

SAT

WHT

RTU Terminal
Board

C06018

50HE,HJ

1. Use a 4-conductor, 18 or 20 AWG cable to connect the
enthalpy control to the PremierLink™ controller and
power transformer.
2. Connect the following 4 wires from the wire harness
located in rooftop unit to the enthalpy controller:
a. Connect the BRN wire to the 24 vac terminal (TR1) on
enthalpy control and to pin 1 on 12-pin harness.
b. Connect the RED wire to the 24 vac GND terminal (TR)
on enthalpy sensor and to pin 4 on 12-pin harness.
c. Connect the GRAY/ORN wire to J4-2 on PremierLink
controller and to terminal (3) on enthalpy sensor.
d. Connect the GRAY/RED wire to J4-1 on PremierLink
controller and to terminal (2) on enthalpy sensor.
NOTE: If installing in a Carrier rooftop, use the two gray wires
provided from the control section to the economizer to connect
PremierLink controller to terminals 2 and 3 on enthalpy sensor.
Return Air Enthalphy Sensor
Mount the return-air enthalpy sensor (HH57AC078) in the
return-air duct. The return air sensor is wired to the enthalpy
controller (HH57AC077). The outdoor enthalpy changeover set
point is set at the controller.
ENTHALPY CONTROLLER
A

B

TR

C
D SO

SR
2
LED

TR1
+

RED
BRN

BLK
RED

HH57AC078 ENTHALPY
SENSOR (USED WITH
ENTHALPY CONTROL
FOR DIFFERENTIAL
ENTHALPY OPERATION)

3

S (OUTDOOR
AIR
+ ENTHALPY
SENSOR)

+

C06020

ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS

WIRE HARNESS
IN UNIT

ACTUATOR

NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside airstream.

Fig. 25 --- Outdoor and Return Air Sensor Wiring
Connections for Differential Enthalpy Control

A1004

Fig. 26 --- Differential Enthalpy Control,
Sensor and Mounting Plate (33AMKITENT006)

GRAY/ORN
GRAY/RED

C7400

MOUNTING PLATE

S (RETURN AIR
+ ENTHALPY
SENSOR)

+

1

BRACKET

HH57AC077
ENTHALPY
CONTROL AND
OUTDOOR AIR
ENTHALPY SENSOR

OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR

C06019

Fig. 27 --- EconoMi$er IV Component Locations

To wire the return air enthalpy sensor, perform the following (See
Fig. 25):
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to
connect the return air enthalpy sensor to the enthalpy
controller.
2. At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
3. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the (SR+)
terminal on the enthalpy controller. Connect the BLK wire
to (S) spade connector on the return air enthalpy sensor
and the (SR) terminal on the enthalpy controller.

C06021

OUTDOOR
AIR HOOD

ECONOMI$ER2
PLUG

BAROMETRIC
RELIEF
DAMPER

HOOD
SHIPPING
BRACKET

GEAR DRIVEN
DAMPER

Fig. 28 --- EconoMi$er2 Component Locations

C06022

Optional Economi$er IV and Economi$er2
See Fig. 27 for EconoMi$er IV component locations. See Fig. 28 for
EconoMi$er2 component locations.
34

NOTE: These instructions are for installing the optional
EconoMi$er IV and EconoMi$er2 only. Refer to the accessory
EconoMi$er IV or EconoMi$er2 installation instructions when
field installing an EconoMi$er IV or EconoMi$er2 accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. (See
Fig. 29.)
2. The box with the economizer hood components is shipped
in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the
EconoMi$er IV in the position shown in Fig. 24. The
optional EconoMi$er2 with 4 to 20 mA actuator signal
control does not include the EconoMi$er IV controller. To
remove the component box from its shipping position,
remove the screw holding the hood box bracket to the top
of the economizer. Slide the hood box out of the unit. (See
Fig. 30.)
IMPORTANT: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. (See Fig. 31.)
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 32.)
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See
Fig. 32 and 33.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. (See Fig. 33.)
8. Caulk the ends of the joint between the unit top panel and
the hood top. (See Fig. 31.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 34. EconoMi$er2 wiring is shown
in Fig. 35.
Barometric flow capacity is shown in Fig. 36. Outdoor air
leakage is shown in Fig. 37. Return air pressure drop is shown in
Fig. 38.

B
Hood

ox

HOOD BOX
BRACKET

C06024

50HE,HJ

Fig. 30 --- Hood Box Removal

SIDE
PANEL

INDOOR
COIL
ACCESS
PANEL

TOP
SIDE
PANEL

CAULK
HERE

INDOOR
COIL
ACCESS
PANEL

Fig. 31 --- Indoor Coil Access Panel Relocation

C06025

TOP
PANEL
INDOOR COIL
ACCESS PANEL

LEFT
HOOD
SIDE

SCREW

B
19 1/16”

FILTER ACCESS PANEL
33 3/8”

HOOD DIVIDER

Fig. 32 --- Outdoor--Air Hood Construction

COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL

Fig. 29 --- Typical Access Panel Locations

C06023

C06026

Economi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to 20 mA
device used to measure the outdoor-air temperature. The outdoor-air
temperature is used to determine when the EconoMi$er IV can be
used for free cooling. The sensor is factory-installed on the
EconoMi$er IV in the outdoor airstream. (See Fig. 27.) The
operating range of temperature measurement is 40_ to 100_F.
35

Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor located at
the inlet of the indoor fan. (See Fig. 39.) This sensor is factory
installed. The operating range of temperature measurement is 0°
to 158_F. See Table 6 for sensor temperature/resistance values.

50HE,HJ

Table 6—Supply Air Sensor Temperature/
Resistance Values
TEMPERATURE (F)
–58
–40
–22
–4
14
32
50
68
77
86
104
122
140
158
176
185
194
212
230
248
257
266
284
302

RESISTANCE (ohms)
200,250
100,680
53,010
29,091
16,590
9,795
5,970
3,747
3,000
2,416
1,597
1,080
746
525
376
321
274
203
153
116
102
89
70
55

Table 7—Economi$er IV Sensor Usage

APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single Enthalpy
Differential
Enthalpy
CO2 for DCV
Control using a
Wall-Mounted
CO2 Sensor
CO2 for DCV
Control using a
Duct-Mounted
CO2 Sensor

ECONOMI$ER IV WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
33ZCSENCO2†
and
33ZCASPCO2**

O
R

CRCBDIOX005A00††

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be
needed for installation.
† 33ZCSENCO2 is an accessory CO2 sensor.
** 33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
†† CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2
and 33ZCASPCO2 accessories.

17 1/4”

DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM
FILTER

Economi$er IV Control Modes
IMPORTANT: The optional EconoMi$er2 does not include a
controller. The EconoMi$er2 is operated by a 4 to 20 mA signal
from an existing field-supplied controller (such as PremierLink™
control). See Fig. 35 for wiring information.
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different
sensors. Refer to Table 7. The EconoMi$er IV is supplied from
the factory with a supply--air temperature sensor and an outdoor-air temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different types of
changeover control and operation of the EconoMi$er IV and unit.

FILTER

BAROMETRIC
RELIEF
FILTER
CLIP

Fig. 33 --- Filter Installation

C06027

The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is
sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient temperature
lockout switch located in the outdoor air stream which is used to
lockout the compressors below a 42_F ambient temperature. (See
Fig. 27.)

Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for
outdoor dry bulb changeover control. The outdoor--air and
supply--air temperature sensors are included as standard. For this
control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV will adjust
the outdoor-air dampers to minimum position. If the outdoor air
temperature is below the set point, the position of the outdoor air
dampers will be controlled to provide free cooling using outdoor
air. When in this mode, the LED next to the free cooling set point
potentiometer will be on. The changeover temperature set point is
controlled by the free cooling set point potentiometer located on
the control. (See Fig. 40.) The scale on the potentiometer is A, B,
C, and D. See Fig. 41 for the corresponding temperature
changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb
sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory
sensor must be mounted in the return airstream. (See Fig. 42.)
Wiring is provided in the EconoMi$er IV wiring harness. (See
Fig. 33.)
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower temperature
airstream is used for cooling. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting. (See Fig. 40.)
36

50HE,HJ

FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK

LEGEND
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT — Potentiometer
RAT — Return-Air Temperature

Potentiometer Defaults Settings:
Power Exhaust Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting

NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
C06028

Fig. 34 --- EconoMi$er IV Wiring
BLACK

4
3
5

BLUE
500 OHM
RESISTOR

8
VIOLET

NOTE 1

6

PINK

7

RUN
RED

+

50HJ540573
ACTUATOR
ASSEMBLY

1
10

YELLOW

NOTE 3

2

OPTIONAL CO 2
SENSOR 4 - 20 mA
OUTPUT

11
9
WHITE

DIRECT DRIVE
ACTUATOR

12

ECONOMISER2 PLUG
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sensor or HH57A077
enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

Fig. 35 --- EconoMi$er2 with 4 to 20 mA Control Wiring
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry bulb
temperature sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 27.) When the outdoor air enthalpy
rises above the outdoor enthalpy changeover set point, the
outdoor-air damper moves to its minimum position. The outdoor

C06029

enthalpy changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$er IV controller. The set
points are A, B, C, and D. (See Fig. 43.) The factory-installed
620-ohm jumper must be in place across terminals SR and SR+
on the EconoMi$er IV controller. (See Fig. 27 and 44.)

37

FLOW IN CUBIC FEET PER MINUTE (cfm)

FLOW IN CUBIC FEET PER MINUTE (cfm)

SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION

SUPPLY AIR
TEMPERATURE
SENSOR

2500
2000
1500

Fig. 39 --- Supply Air Sensor Location

1000

C06033

500
0

0.15

0.05

0.25

STATIC PRESSURE (in. wg)

Fig. 36 --- Barometric Flow Capacity

C06030

30
25
20
15
10

C06034

Fig. 40 --- EconoMi$er IV Controller Potentiometer
and LED Locations

5
0

0.13

0.20 0.22

0.25

0.30 0.35 0.40

0.45

0.50

STATIC PRESSURE (in. wg)

Fig. 37 --- Outdoor--Air Damper Leakage
FLOW IN CUBIC FEET PER MINUTE (cfm)

50HE,HJ

Differential Enthalphy Control
For differential enthalpy control, the EconoMi$er IV controller
uses
two
enthalpy
sensors
(HH57AC078
and
CRENTDIF004A00), one in the outside air and one in the return
air duct. The EconoMi$er IV controller compares the outdoor
air enthalpy to the return air enthalpy to determine EconoMi$er
IV use. The controller selects the lower enthalpy air (return or
outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.

C06031

6000
5000
4000
3000
2000
1000
0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

STATIC PRESSURE (in. wg)

Fig. 38 --- Return--Air Pressure Drop

C06032

Replace the standard outside air dry bulb temperature sensor with
the accessory enthalpy sensor in the same mounting location.
(See Fig. 27.) Mount the return air enthalpy sensor in the return
air duct. (See Fig. 42.) Wiring is provided in the EconoMi$er IV
wiring harness. (See Fig. 34.) The outdoor enthalpy changeover
set point is set with the outdoor enthalpy set point potentiometer
on the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation control
based on the level of CO2 measured in the space or return air
duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV potentiometers
to correspond to the DCV voltage output of the indoor air quality
sensor at the user-determined set point. (See Fig. 45.)
If a separate field-supplied transformer is used to power the IAQ
sensor, the sensor must not be grounded or the EconoMi$er IV
control board will be damaged.
Exhaust Set Point Adjustment
The exhaust set point will determine when the exhaust fan runs
based on damper position (if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan Set
Point (EXH SET) potentiometer. (See Fig. 40.) The set point
represents the damper position above which the exhaust fans will
be turned on. When there is a call for exhaust, the EconoMi$er IV
controller provides a 45 ± 15 second delay before exhaust fan
38

(TO x

OA + (TR
)
100

x

Thermostats
The EconoMi$er IV control works with conventional thermostats
that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage
1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control
does not support space temperature sensors. Connections are
made at the thermostat terminal connection board located in the
main control box.
19

D

14

LED ON

C

LED OFF

13
12

LED ON

B

LED OFF

LED ON

A

11
10

LED OFF

9
40

45

50

55

60
65 70 75 80
DEGREES FAHRENHEIT

85

90

95

100

C06035

Fig. 41 --- Outside Air Temperature
Changeover Set Points
ECONOMI$ER IV
CONTROLLER

ECONOMI$ER IV

GROMMET

RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)

Fig. 42 --- Return Air Temperature or Enthalpy
Sensor Mounting Location

C06036

Occupancy Control
The factory default configuration for the EconoMi$er IV control
is occupied mode. Occupied mode is provided by the black
jumper from terminal TR to terminal N. When unoccupied mode
is desired, install a field-supplied timeclock function in place of
the jumper between TR and N. (See Fig. 34.) When the timeclock
contacts are closed, the EconoMi$er IV control will be in
occupied mode. When the timeclock contacts are open (removing
the 24-v signal from terminal N), the EconoMi$er IV will be in
unoccupied mode.

39

50HE,HJ

LED OFF

16
15

RA
) =TM
100

TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
As an example, if local codes require 10% outdoor air during
occupied conditions, outdoor-air temperature is 60_F, and
return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across
terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to
Fig. 34 and that the minimum position potentiometer is
turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured supply air temperature matches the
calculated value.
6. Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when
requiring
additional
temporary
ventilation.
If
a
field-supplied remote potentiometer (Honeywell part number
S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a remote
location.
To control the minimum damper position remotely, remove the
factory-installed jumper on the P and P1 terminals on the
EconoMi$er IV controller. Wire the field-supplied potentiometer
to the P and P1 terminals on the EconoMi$er IV controller. (See
Fig. 44.)
Damper Movement
Damper movement from full open to full closed (or vice versa)
takes 21/2 minutes.

LED ON

18
17

mA

activation to allow the dampers to open. This delay allows the
damper to reach the appropriate position to avoid unnecessary fan
overload.
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 40.) The minimum damper
position maintains the minimum airflow into the building during
the occupied period.
When using demand ventilation, the minimum damper position
represents the minimum ventilation position for VOC (volatile
organic compound) ventilation requirements. The maximum
demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum
position potentiometer should be used to set the occupied
ventilation position. The maximum demand ventilation position
should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments with at
least 10_F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature using the
following formula:

110
(43)

46

85
90
95 100 105
(29) (32) (35) (38) (41)

44

CONTROL CONTROL POINT
CURVE
APPROX. deg. F (deg. C)

(%
)
EH
UM
IDI
TY

38

LA

32

TIV

34

75
(24)

RE
80

22

60

70

24

65
(18)

10
0
90

28

30

70
(21)

26

EN
T

HA
LP
Y

BT
U

PE
R

PO

UN

36 D D

RY

AI
R

40

73 (23)
70 (21)
67 (19)
63 (17)

20

50

60
(16)

40

A

16
14

50
(10)

12

45
(7)

30

55
(13) B

18

50HE,HJ

80
(27)

42

AT 50% RH

A
B
C
D

C

20

D

40
(4)

10

35
(2)

B A
D C
35
(2)

40
(4)

45
(7)

50
(10)

55
60
(13) (16)

65
70
(18) (21)

75
(24)

80
85
(27) (29)

HIGH LIMIT
CURVE
90
95
(32) (35)

100
(38)

105 110
(41) (43)

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
C06037

Fig. 43 --- Enthalpy Changeover Set Points
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and cool
capacity of the equipment, the maximum ventilation rate must be
evaluated for design conditions. The maximum damper position
must be calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal
outside air design criteria.
A proportional anticipatory strategy should be taken with the
following conditions: a zone with a large area, varied occupancy,
and equipment that cannot exceed the required ventilation rate at
design conditions. Exceeding the required ventilation rate means
the equipment can condition air at a maximum ventilation rate
that is greater than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause the
fresh air supplied to increase as the room CO2 level increases
even though the CO2 set point has not been reached. By the time
the CO2 level reaches the set point, the damper will be at
maximum ventilation and should maintain the set point.
In order to have the CO2 sensor control the economizer damper in
this manner, first determine the damper voltage output for
minimum or base ventilation. Base ventilation is the ventilation
required to remove contaminants during unoccupied periods. The
following equation may be used to determine the percent of
outside-air entering the building for a given damper position. For
best results there should be at least a 10 degree difference in
outside and return-air temperatures.

(TO x

OA + (TR
)
100

x

RA
) =TM
100

TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
Once base ventilation has been determined, set the minimum
damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an output
of 3.6 volts to the actuator provides a base ventilation rate of 5%
and an output of 6.7 volts provides the maximum ventilation rate
of 20% (or base plus 15 cfm per person). Use Fig. 42 to
determine the maximum setting of the CO2 sensor. For example,
a 1100 ppm set point relates to a 15 cfm per person design. Use
the 1100 ppm curve on Fig. 45 to find the point when the CO2
sensor output will be 6.7 volts. Line up the point on the graph
with the left side of the chart to determine that the range
configuration for the CO2 sensor should be 1800 ppm. The
EconoMi$er IV controller will output the 6.7 volts from the CO2
sensor to the actuator when the CO2 concentration in the space is
at 1100 ppm. The DCV set point may be left at 2 volts since the
CO2 sensor voltage will be ignored by the EconoMi$er IV
controller until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been determined, set
the maximum damper demand control ventilation potentiometer
to this position. Do not set to the maximum position as this can
result in over-ventilation to the space and potential high-humidity
levels.
40

TR1

N

24
Vac
HOT

24 Vac
COM

Set
10V

2V
EXH

P1
P

Min
Pos

T1
T

DCV
2V
AQ1

SR

Max
10V

1

2
5

DCV

SO+

SR+

_

DCV

AQ

SO

+

Open

2V

3

4

EF

EF1

Set
10V

Free
Cool
B

C

A

D

C06038

Fig. 44 --- EconoMi$er IV Control
CO2 SENSOR MAX RANGE SETTING

RANGE CONFIGURATION (ppm)

6000
5000
4000

800 ppm
900 ppm
1000 ppm
1100 ppm

3000
2000
1000
0
2

3

4

5

6

7

8

DAMPER VOLTAGE FOR MAX VENTILATION RATE

Fig. 45 --- CO2 Sensor Maximum Range Setting

C06039

CO2 Sensor Configuration
The CO2 sensor has preset standard voltage settings that can be
selected anytime after the sensor is powered up. (See Table 8.)
Use setting 1 or 2 for Carrier equipment. (See Table 8.)
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. (See
Table 8.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed anytime
after the sensor is energized. Follow the steps below to change the
non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
4. Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until the desired
setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to
continue to the next variable.

Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humidity
load on any zone is the fresh air introduced. For some
applications, a device such as a 62AQ energy recovery unit is
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more than
adequate to remove the humidity loads for most commercial
applications.
If normal rooftop heating and cooling operation is not adequate
for the outdoor humidity level, an energy recovery unit and/or a
dehumidification option should be considered.
Step 7 —Adjust Evaporator--Fan Speed
Adjust evaporator-fan speed to meet jobsite conditions.
Tables 9 and 10 show fan rpm at motor pulley settings for the
50HE003--006 and 50HJ004--007 units. Tables 11 and 14 show
maximum amp draw of belt-drive motor. Table 13 shows sound
data. Refer to Tables 15-34 for performance data. See Table 35
for accessory static pressure drop. See Fig. 47 for the
Humidi-MiZer™ system static pressure drops.
For units with electric heating, required minimum cfm is 900 for
50HJ004; 1200 for 50HJ005; 1500 for 50HJ006 and 1800 for
50HJ007.
Belt Drive Motors
Fan motor pulleys are factory set for speed shown in Table 1.
Check pulley alignment and belt tension prior to start-up.
To change fan speed:
1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts.
(See Fig. 47.)
3. Loosen movable pulley flange setscrew (See Fig. 48).
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Table 1 for speed change for each
full turn of pulley flange.)
6. Adjust belt tension and align fan and motor pulleys per
guidance below.
NOTE: Once the required flange position is determined for the
correct blower rpm, it is recommended (but not required) that the
variable pitch pulley be replaced with a corresponding size fixed
sheave pulley.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from mounting.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (1/2-in. deflection with 7 to 10 lb of
force).
3. Tighten motor mounting nuts.
4. Adjust bolt and tighten nut to secure motor in fixed
position.

41

50HE,HJ

TR

EXH

N1

Table 8—CO2 Sensor Standard Settings

OUTPUT

VENTILATION
RATE
(cfm/Person)

ANALOG
OUTPUT

CO2
CONTROL RANGE
(ppm)

OPTIONAL
RELAY SETPOINT
(ppm)

RELAY
HYSTERESIS
(ppm)

Proportional

Any

0-10V
4-20 mA

0-2000

1000

50

Proportional

Any

2-10V
7-20 mA

0-2000

1000

50

3

Exponential

Any

0-10V
4-20 mA

0-2000

1100

50

4

Proportional

15

0-10V
4-20 mA

0-1100

1100

50

Proportional

20

0-10V
4-20 mA

0- 900

900

50

Exponential

15

0-10V
4-20 mA

0-1100

1100

50

Exponential

20

0-10V
4-20 mA

0- 900

900

50

Proportional

—

0-10V
4-20 mA

0-9999

5000

500

—

0-10V
4-20 mA

0-2000

700

50

SETTING

EQUIPMENT

1
Interface w/Standard
Building Control System

2

5
Economizer

6

8

Health & Safety

9

Parking/Air Intakes/
Loading Docks

Proportional

LEGEND
ppm — Parts Per Million

0.35

0.3

0.25
DELTA P IN. WG

50HE,HJ

7

0.2

0.15

0.1

4 & 5 ton
6 ton

0.05

3 ton

0
0

1000

2000

4000

3000

5000

6000

Fig. 46 --- Humidi--MiZert Adaptive Dehumidification System Static Pressure Drop (in. wg)

Fig. 47 --- Belt Drive Motor Mounting

C06134

Fig. 48 --- Evaporator--Fan Pulley Adjustment

42

C06133

C06041

Table 9—50HJ and 50he Fan Rpm at Motor Pulley Setting With Standard Motor*
UNIT
50HJ
50HE
003
004
005
006
007

MOTOR PULLEY TURNS OPEN
0

1/
2

1

11/2

2

21/2

3

31/2

4

41/2

5

51/2

6

936
1044
1185
1460
1585

906
1008
1144
1425
1538

876
971
1102
1389
1492

846
935
1061
1354
1445

816
898
1019
1318
1399

786
862
978
1283
1352

756
826
936
1248
1305

726
789
895
1212
1259

696
753
853
1177
1212

666
716
812
1141
1166

639
680
770
1106
1119

—
—
—
1070
—

—
—
—
1035
—

*Approximate fan rpm shown (standard motor/drive).

UNIT
004
005
006
007

1/
2

0
1455
1455
1685
1685

1423
1423
1589
1589

1
1392
1392
1557
1557

11/2
1360
1360
1525
1525

2
1328
1328
1493
1493

MOTOR PULLEY TURNS OPEN
21/2
3
31/2
1297
1265
1233
1297
1265
1233
1460
1428
1396
1460
1428
1396

41/2
1170
1170
1332
1332

4
1202
1202
1364
1364

5
1138
1138
1300
1300

51/2
1107
1107
—
—

6
1075
1075
—
—

*Approximate fan rpm shown (high-static motor/drive).

Table 11—Evaporator-Fan Motor Data — Standard Motor
UNIT
50HJ
50HE
003
004
005
006
007

UNIT
PHASE

MAXIMUM
CONTINUOUS BHP*

MAXIMUM
OPERATING WATTS*

ALL
Single

0.58
1.20

580
1000

Three

1.20

1000

Single

1.20

1000

Three

1.20

1000

Single

1.30

1650

Three

2.40

2120

Three

2.40

2120

UNIT VOLTAGE

MAXIMUM
AMP DRAW

2.0
208/230
208/230
460
575
208/230
208/230
460
575
208/230
208/230
460
575
208/230
460
575

75.0
4.9
4.9
2.2
2.2
4.9
4.9
2.2
2.2
9.2
6.7
3.0
3.0
6.7
3.0
3.0

LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

Table 12—Evaporator-Fan Motor Data — High-Static Motors
UNIT
50HJ
50HE

UNIT
PHASE

MAXIMUM
CONTINUOUS BHP*

MAXIMUM
OPERATING WATTS*

004

Three

2.40

2120

005

Three

2.40

2120

006

Three

2.90

2615

007

Three

2.90

2615

UNIT VOLTAGE

MAXIMUM
AMP DRAW

208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575

6.7
3.0
3.0
6.7
3.0
3.0
8.6
3.9
3.9
8.6
3.9
3.9

LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

43

50HE,HJ

Table 10—50HJ, 50HE Fan Rpm at Motor Pulley Setting With High-Static Motor*

Table 13—Accessory/FIOP Electric Heaters Static Pressure Drop (in. wg) — 50HJ004-007 and 50HE003--006
COMPONENT
1 Heater Module
2 Heater Modules

600
0.03
0.14

900
0.05
0.15

1200
0.07
0.16

1400
0.09
0.16

1600
0.09
0.16

CFM
1800
0.10
0.17

2000
0.11
0.17

2200
0.11
0.17

2400
0.12
0.18

2600
0.13
0.18

Table 14—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 50HJ004-007 and 50HE003--006
COMPONENT

50HE,HJ

Vertical EconoMi$er IV and EconoMi$er2
Horizontal EconoMi$er IV and EconoMi$er2

600
0.01
---

800
0.02
---

1000
0.035
---

1250

1500

CFM
1750

2000

2250

2500

2750

3000

0.045
—

0.065
—

0.08
0.1

0.12
0.125

0.145
0.15

0.175
0.18

0.22
0.225

0.255
0.275

LEGEND
FIOP --- Factory ---Installed Option
*The static pressure must be added to external static pressure. The sum and the indoor entering-air cfm should be used in conjunction with the Fan Performance
tables to determine indoor blower rpm and watts.

Table 14 — Evaporator-Fan Motor Efficiency
MOTOR 50HJ
003,004,005
006
007

EFFICIENCY
75
74/84*
84

*Single-phase/3-phase.
NOTE: Convert watts to bhp using the following formula:

bhp =

watts input x motor efficiency
746

GENERAL FAN PERFORMANCE NOTES

1. Values include losses for filters, unit casing, and wet coils. See Table 13 and 14 and Fig. 46 for accessory/FIOP static pressure
information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the
fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
See Table 11 and 12 on this page for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
4. Interpolation is permissible. Do not extrapolate.
5. Performance includes clean filter and wet coil.
Table 15—Fan Performance 50HE003 — Vertical Discharge Units; Standard Motor (Belt Drive)**

AIRFLOW
(Cfm)
600
700
800
900
1000

0.1
Rpm
Bhp
500
0.08
529
0.09
547
0.1
570
0.13
599
0.15

EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
531
0.08
607
0.14
713
0.21
788
0.29
567
0.09
633
0.16
739
0.24
816
0.32
592
0.12
660
0.19
761
0.27
845
0.37
620
0.14
691
0.22
793
0.32
870
0.42
650
0.16
717
0.26
818
0.36
894
0.47

44

1.0
Rpm
878
902
937
957
981

Bhp
0.37
0.41
0.47
0.53
0.58

AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

Rpm
566
598
632
666
701
737
774

0.2
Bhp
0.14
0.17
0.21
0.25
0.30
0.36
0.42

Rpm
1029
1052
1076
1100
1126
1152
1179

1.2
Bhp
0.63
0.70
0.77
0.85
0.94
1.03
1.13

Watts
142
173
210
252
300
355
417

Watts
630
695
767
845
930
1023
1123

Rpm
690
718
748
778
809
842
875

0.4
Bhp
0.23
0.27
0.31
0.36
0.42
0.48
0.55

EXTERNAL STATIC PRESSURE (in. wg
0.6
Watts Rpm
Bhp
Watts
Rpm
228
791
0.32
320
879
267
817
0.37
366
903
311
844
0.42
418
929
361
873
0.48
476
956
418
902
0.54
540
983
481
932
0.61
610
1012
551
962
0.69
689
1041

0.8
Bhp
0.42
0.47
0.53
0.60
0.67
0.75
0.83

Watts
418
471
530
594
665
744
830

Rpm
957
981
1006
1031
1057
1085
1112

1.0
Bhp
0.52
0.58
0.65
0.72
0.80
0.89
0.98

Watts
522
581
646
718
796
881
974

Rpm
1095
1118
1141
1165
1189
1215
—

1.4
Bhp
0.75
0.82
0.90
0.98
1.07
1.17
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
742
1157
0.86
859
1216
814
1179
0.94
937
1237
892
1202
1.03
1021
1260
977
1225
1.12
1112
—
1069
—
—
—
—
1168
—
—
—
—
—
—
—
—
—

1.8
Bhp
0.99
1.07
1.16
—
—
—
—

Watts
980
1064
1154
—
—
—
—

Rpm
1272
1293
—
—
—
—
—

2.0
Bhp
1.11
1.20
—
—
—
—
—

Watts
1105
1195
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.

Table 17—Fan Performance 50HJ004, 50he004 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

Rpm
566
598
632
666
701
737
774

0.2
Bhp
0.14
0.17
0.21
0.25
0.30
0.36
0.42

Rpm
1029
1052
1076
1100
1126
1152
1179

1.2
Bhp
0.63
0.70
0.77
0.85
0.94
1.03
1.13

Watts
142
173
210
252
300
355
417

Watts
630
695
767
845
930
1023
1123

Rpm
690
718
748
778
809
842
875

0.4
Bhp
0.23
0.27
0.31
0.36
0.42
0.48
0.55

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm
228
791
0.32
320
879
267
817
0.37
366
903
311
844
0.42
418
929
361
873
0.48
476
956
418
902
0.54
540
983
481
932
0.61
610
1012
551
962
0.69
689
1041

0.8
Bhp
0.42
0.47
0.53
0.60
0.67
0.75
0.83

Watts
418
471
530
594
665
744
830

Rpm
957
981
1006
1031
1057
1085
1112

1.0
Bhp
0.52
0.58
0.65
0.72
0.80
0.89
0.98

Watts
522
581
646
718
796
881
974

Rpm
1095
1118
1141
1165
1189
1215
1241

1.4
Bhp
0.75
0.82
0.90
0.98
1.07
1.17
1.28

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
742
1157
0.86
859
1216
814
1179
0.94
937
1237
892
1202
1.03
1021
1260
977
1225
1.12
1112
1282
1069
1249
1.22
1211
1306
1168
1274
1.32
1317
1330
1275
1300
1.44
1431
1355

1.8
Bhp
0.99
1.07
1.16
1.26
1.36
1.48
1.60

Watts
980
1064
1154
1252
1356
1469
1590

Rpm
1272
1293
1314
1337
1360
1384
1408

2.0
Bhp
1.11
1.20
1.30
1.40
1.51
1.63
1.76

Watts
1105
1195
1291
1395
1506
1625
1752

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.

45

50HE,HJ

Table 16—Fan Performance 50HJ004, 50HE004 — Vertical Discharge Units; Standard Motor
(Belt Drive)*

Table 18—Fan Performance 50HJ005, 50HE005 — Vertical Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM

50HE,HJ

1200
1300
1400
1500
1600
1700
1800
1900
2000

AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000

Rpm
666
701
737
774
811
849
887
926
965

0.2
Bhp
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86

Rpm
1100
1126
1152
1179
—
—
—
—
—

1.2
Bhp
0.85
0.94
1.03
1.13
—
—
—
—
—

Watts
252
300
355
417
487
565
651
746
852

Watts
845
930
1023
1123
—
—
—
—
—

Rpm
778
809
842
875
909
943
978
1014
1050

0.4
Bhp
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
361
873
0.48
476
956
418
902
0.54
540
983
481
932
0.61
610
1012
551
962
0.69
689
1041
629
994
0.78
774
1071
715
1026
0.87
869
1101
810
1059
0.98
972
1133
914
1092
1.09
1084
—
1028
—
—
—
—

0.8
Bhp
0.60
0.67
0.75
0.83
0.93
1.03
1.14
—
—

Watts
594
665
744
830
923
1025
1136
—
—

Rpm
1031
1057
1085
1112
1141
1170
—
—
—

1.0
Bhp
0.72
0.80
0.89
0.98
1.08
1.19
—
—
—

Watts
718
796
881
974
1076
1185
—
—
—

Rpm
1165
1189
1215
—
—
—
—
—
—

1.4
Bhp
0.98
1.07
1.17
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
977
1225
1.12
1112
—
1069
—
—
—
—
1168
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—

Rpm
—
—
—
—
—
—
—
—
—

2.0
Bhp
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field-supplied
drive.

Table 19—Fan Performance 50HJ005, 50HE005 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000

Rpm
666
701
737
774
811
849
887
926
965

0.2
Bhp
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86

Rpm
1100
1126
1152
1179
1206
1235
1264
1293
1324

1.2
Bhp
0.85
0.94
1.03
1.13
1.24
1.36
1.48
1.62
1.77

Watts
252
300
355
417
487
565
651
746
852

Watts
845
930
1023
1123
1231
1349
1475
1611
1756

Rpm
778
809
842
875
909
943
978
1014
1050

0.4
Bhp
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
361
873
0.48
476
956
418
902
0.54
540
983
481
932
0.61
610
1012
551
962
0.69
689
1041
629
994
0.78
774
1071
715
1026
0.87
869
1101
810
1059
0.98
972
1133
914
1092
1.09
1084
1164
1028
1127
1.21
1206
1197

0.8
Bhp
0.60
0.67
0.75
0.83
0.93
1.03
1.14
1.26
1.39

Watts
594
665
744
830
923
1025
1136
1257
1387

Rpm
1031
1057
1085
1112
1141
1170
1200
1231
1262

1.0
Bhp
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58

Watts
718
796
881
974
1076
1185
1304
1432
1570

Rpm
1165
1189
1215
1241
1268
1295
1323
1352
1381

1.4
Bhp
0.98
1.07
1.17
1.28
1.40
1.52
1.66
1.80
1.96

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
977
1225
1.12
1112
1282
1069
1249
1.22
1211
1306
1168
1274
1.32
1317
1330
1275
1300
1.44
1431
1355
1391
1326
1.56
1553
1381
1515
1352
1.69
1685
1407
1649
1380
1.84
1826
1434
1792
1408
1.99
1976
1461
1945
1436
2.15
2137
1489

1.8
Bhp
1.26
1.36
1.48
1.60
1.73
1.87
2.02
2.17
2.34

Watts
1252
1356
1469
1590
1719
1858
2006
2163
2332

Rpm
1337
1360
1384
1408
1433
1459
1485
1512
—

2.0
Bhp
1.40
1.51
1.63
1.76
1.90
2.04
2.20
2.37
—

Watts
1395
1506
1625
1752
1888
2034
2189
2353
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.

46

AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
790
828
866
905
944
983
1023
1063
1104
—
—

0.2
Bhp
0.40
0.46
0.54
0.62
0.71
0.81
0.92
1.05
1.18
—
—

Rpm
1224
1250
—
—
—
—
—
—
—
—
—

1.2
Bhp
1.18
1.27
—
—
—
—
—
—
—
—
—

Watts
353
412
478
551
633
723
821
929
1046
—
—

Watts
1045
1128
—
—
—
—
—
—
—
—
—

Rpm
897
931
966
1001
1037
1073
1110
1147
—
—
—

0.4
Bhp
0.53
0.60
0.68
0.77
0.87
0.98
1.10
1.23
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
471
991
0.68
600
1075
536
1022
0.75
670
1104
608
1054
0.84
747
1134
687
1087
0.94
832
1165
774
1120
1.04
925
1197
870
1154
1.16
1026
—
975
1189
1.28
1137
—
1089
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

0.8
Bhp
0.83
0.92
1.01
1.11
1.22
—
—
—
—
—
—

Watts
739
813
895
985
1084
—
—
—
—
—
—

Rpm
1152
1180
1208
1238
—
—
—
—
—
—
—

1.0
Bhp
1.00
1.09
1.19
1.29
—
—
—
—
—
—
—

Watts
888
966
1053
1148
—
—
—
—
—
—
—

Rpm
—
—
—
—
—
—
—
—
—
—
—

1.4
Bhp
—
—
—
—
—
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
—
—
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—
—
—

Rpm
—
—
—
—
—
—
—
—
—
—
—

2.0
Bhp
—
—
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.

47

50HE,HJ

Table 20—Fan Performance 50HJ006, 50HE006 Single-Phase — Vertical Discharge Units; Standard Motor (Belt Drive)*

Table 21—Fan Performance 50HJ006, 50he006 Three-Phase — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM

50HE,HJ

1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
790
828
866
905
944
983
1023
1063
1104
1145
1185

0.2
Bhp
0.40
0.46
0.54
0.62
0.71
0.81
0.92
1.05
1.18
1.32
1.48

Rpm
1224
1250
1278
1306
1335
1364
1395
1426
1457
1489
—

1.2
Bhp
1.18
1.27
1.37
1.48
1.61
1.74
1.88
2.03
2.19
2.37
—

Watts
353
412
478
551
633
723
821
929
1046
1174
1311

Watts
1045
1128
1219
1318
1426
1542
1668
1804
1949
2106
—

Rpm
897
931
966
1001
1037
1073
1110
1147
1185
1223
1262

0.4
Bhp
0.53
0.60
0.68
0.77
0.87
0.98
1.10
1.23
1.37
1.52
1.68

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
471
991
0.68
600
1075
536
1022
0.75
670
1104
608
1054
0.84
747
1134
687
1087
0.94
832
1165
774
1120
1.04
925
1197
870
1154
1.16
1026
1229
975
1189
1.28
1137
1262
1089
1224
1.41
1256
1295
1212
1260
1.56
1386
1329
1346
1296
1.72
1526
1364
1490
1333
1.89
1676
1399

0.8
Bhp
0.83
0.92
1.01
1.11
1.22
1.34
1.47
1.61
1.76
1.93
2.10

Watts
739
813
895
985
1084
1190
1306
1431
1567
1712
1868

Rpm
1152
1180
1208
1238
1268
1299
1330
1362
1395
1428
1462

1.0
Bhp
1.00
1.09
1.19
1.29
1.41
1.53
1.67
1.82
1.98
2.15
2.33

Watts
888
966
1053
1148
1251
1362
1483
1614
1754
1905
2067

Rpm
1291
1316
1343
1370
1398
1427
1456
1486
—
—
—

1.4
Bhp
1.36
1.46
1.57
1.69
1.81
1.95
2.09
2.25
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1212
1354
1.56
1387
1414
1299
1379
1.66
1478
1438
1394
1405
1.77
1576
1463
1497
1431
1.90
1683
1489
1609
1458
2.03
1799
1515
1730
1486
2.17
1925
1542
1860
1514
2.32
2060
—
2001
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
1.77
1.87
1.99
2.11
2.25
2.39
—
—
—
—
—

Watts
1570
1664
1766
1877
1997
2126
—
—
—
—
—

Rpm
1472
1495
1520
1545
—
—
—
—
—
—
—

2.0
Bhp
1.98
2.09
2.21
2.34
—
—
—
—
—
—
—

Watts
1761
1858
1964
2078
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.

48

AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
790
828
866
905
944
983
1023
1063
1104
1145
1185

0.2
Bhp
0.40
0.46
0.54
0.62
0.71
0.81
0.92
1.05
1.18
1.32
1.48

Rpm
1224
1250
1278
1306
1335
1364
1395
1426
1457
1489
1522

1.2
Bhp
1.18
1.27
1.37
1.48
1.61
1.74
1.88
2.03
2.19
2.37
2.56

Watts
353
412
478
551
633
723
821
929
1046
1174
1311

Watts
1045
1128
1219
1318
1426
1542
1668
1804
1949
2106
2272

Rpm
897
931
966
1001
1037
1073
1110
1147
1185
1223
1262

0.4
Bhp
0.53
0.60
0.68
0.77
0.87
0.98
1.10
1.23
1.37
1.52
1.68

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
471
991
0.68
600
1075
536
1022
0.75
670
1104
608
1054
0.84
747
1134
687
1087
0.94
832
1165
774
1120
1.04
925
1197
870
1154
1.16
1026
1229
975
1189
1.28
1137
1262
1089
1224
1.41
1256
1295
1212
1260
1.56
1386
1329
1346
1296
1.72
1526
1364
1490
1333
1.89
1676
1399

0.8
Bhp
0.83
0.92
1.01
1.11
1.22
1.34
1.47
1.61
1.76
1.93
2.10

Watts
739
813
895
985
1084
1190
1306
1431
1567
1712
1868

Rpm
1152
1180
1208
1238
1268
1299
1330
1362
1395
1428
1462

1.0
Bhp
1.00
1.09
1.19
1.29
1.41
1.53
1.67
1.82
1.98
2.15
2.33

Watts
888
966
1053
1148
1251
1362
1483
1614
1754
1905
2067

Rpm
1291
1316
1343
1370
1398
1427
1456
1486
1516
1547
1579

1.4
Bhp
1.36
1.46
1.57
1.69
1.81
1.95
2.09
2.25
2.42
2.60
2.80

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1212
1354
1.56
1387
1414
1299
1379
1.66
1478
1438
1394
1405
1.77
1576
1463
1497
1431
1.90
1683
1489
1609
1458
2.03
1799
1515
1730
1486
2.17
1925
1542
1860
1514
2.32
2060
1570
2001
1543
2.48
2204
1598
2151
1573
2.66
2360
1627
2312
1603
2.84
2526
—
2484
—
—
—
—

1.8
Bhp
1.77
1.87
1.99
2.11
2.25
2.39
2.55
2.72
2.90
—
—

Watts
1570
1664
1766
1877
1997
2126
2265
2415
2574
—
—

Rpm
1472
1495
1520
1545
1570
1596
1623
—
—
—
—

2.0
Bhp
1.98
2.09
2.21
2.34
2.48
2.63
2.79
—
—
—
—

Watts
1761
1858
1964
2078
2202
2335
2478
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.

49

50HE,HJ

Table 22—Fan Performance 50HJ006, 50HE006 — Vertical Discharge Units; High-Static Motor
(Belt Drive)*

Table 23—Fan Performance 50HJ007 — Vertical Discharge Units; Standard Motor (Belt Drive)*

50HE,HJ

AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm
907
945
984
1024
1063
1103
1143
1183
1224
1264
1305
1346
—

0.2
Bhp
0.63
0.72
0.82
0.93
1.05
1.18
1.32
1.47
1.63
1.81
1.99
2.20
—

Rpm
1304
1335
1366
1398
1430
1462
—
—
—
—
—
—
—

1.2
Bhp
1.51
1.64
1.78
1.93
2.09
2.27
—
—
—
—
—
—
—

Watts
558
638
727
823
929
1044
1168
1303
1448
1604
1772
1951
—

Watts
1337
1454
1580
1715
1858
2012
—
—
—
—
—
—
—

Rpm
1006
1042
1078
1115
1152
1189
1227
1265
1303
1342
1381
—
—

0.4
Bhp
0.80
0.90
1.00
1.12
1.25
1.39
1.54
1.70
1.87
2.06
2.26
—
—

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
708
1092
0.97
860
1169
796
1126
1.08
956
1201
892
1160
1.19
1060
1235
997
1195
1.32
1173
1268
1111
1230
1.46
1294
1302
1234
1266
1.60
1425
1337
1367
1302
1.76
1566
1371
1510
1339
1.93
1717
1406
1663
1375
2.12
1878
1442
1828
1412
2.31
2051
—
2003
—
—
—
—
—
—
—
—
—
—
—
—
—
—

0.8
Bhp
1.14
1.26
1.39
1.52
1.67
1.82
1.99
2.17
2.36
—
—
—
—

Watts
1015
1119
1230
1350
1480
1618
1767
1926
2095
—
—
—
—

Rpm
1239
1271
1303
1335
1368
1402
1435
—
—
—
—
—
—

1.0
Bhp
1.32
1.45
1.58
1.72
1.88
2.04
2.22
—
—
—
—
—
—

Watts
1174
1285
1403
1531
1668
1814
1970
—
—
—
—
—
—

Rpm
1365
1395
1426
1457
1488
—
—
—
—
—
—
—
—

1.4
Bhp
1.69
1.83
1.98
2.14
2.31
—
—
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1503
1422
1.88
1674
1477
1627
1452
2.03
1804
1506
1760
1482
2.19
1943
1535
1901
1512
2.35
2091
—
2052
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
2.08
2.23
2.40
—
—
—
—
—
—
—
—
—
—

Watts
1848
1984
2130
—
—
—
—
—
—
—
—
—
—

Rpm
1528
—
—
—
—
—
—
—
—
—
—
—
—

2.0
Bhp
2.28
—
—
—
—
—
—
—
—
—
—
—
—

Watts
2025
—
—
—
—
—
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied
drive.

50

AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm
907
945
984
1024
1063
1103
1143
1183
1224
1264
1305
1346
1387

0.2
Bhp
0.63
0.72
0.82
0.93
1.05
1.18
1.32
1.47
1.63
1.81
1.99
2.20
2.41

Rpm
1304
1335
1366
1398
1430
1462
1495
1529
1562
—
—
—
—

1.2
Bhp
1.51
1.64
1.78
1.93
2.09
2.27
2.45
2.64
2.85
—
—
—
—

Watts
558
638
727
823
929
1044
1168
1303
1448
1604
1772
1951
2142

Rpm
1006
1042
1078
1115
1152
1189
1227
1265
1303
1342
1381
1420
1459

0.4
Bhp
0.80
0.90
1.00
1.12
1.25
1.39
1.54
1.70
1.87
2.06
2.26
2.47
2.69

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
708
1092
0.97
860
1169
796
1126
1.08
956
1201
892
1160
1.19
1060
1235
997
1195
1.32
1173
1268
1111
1230
1.46
1294
1302
1234
1266
1.60
1425
1337
1367
1302
1.76
1566
1371
1510
1339
1.93
1717
1406
1663
1375
2.12
1878
1442
1828
1412
2.31
2051
1478
2003
1450
2.52
2235
1514
2191
1488
2.74
2431
—
2391
—
—
—
—

0.8
Bhp
1.14
1.26
1.39
1.52
1.67
1.82
1.99
2.17
2.36
2.56
2.78
—
—

Watts
1015
1119
1230
1350
1480
1618
1767
1926
2095
2275
2467
—
—

Rpm
1239
1271
1303
1335
1368
1402
1435
1470
1504
1539
—
—
—

1.0
Bhp
1.32
1.45
1.58
1.72
1.88
2.04
2.22
2.41
2.60
2.82
—
—
—

Watts
1174
1285
1403
1531
1668
1814
1970
2136
2313
2501
—
—
—

Rpm
1365
1395
1426
1457
1488
1520
1552
1585
—
—
—
—
—

1.4
Bhp
1.69
1.83
1.98
2.14
2.31
2.49
2.68
2.89
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1503
1422
1.88
1674
1477
1627
1452
2.03
1804
1506
1760
1482
2.19
1943
1535
1901
1512
2.35
2091
1565
2052
1543
2.53
2249
1596
2212
1574
2.72
2416
—
2383
—
—
—
—
2564
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
2.08
2.23
2.40
2.57
2.76
—
—
—
—
—
—
—
—

Watts
1848
1984
2130
2284
2449
—
—
—
—
—
—
—
—

Rpm
1528
1557
1586
1616
—
—
—
—
—
—
—
—
—

2.0
Bhp
2.28
2.44
2.61
2.79
—
—
—
—
—
—
—
—
—

Watts
2025
2168
2319
2481
—
—
—
—
—
—
—
—
—

Watts
1337
1454
1580
1715
1858
2012
2175
2349
2533
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.

Table 25—Fan Performance 50HE003 — Horizontal Discharge Units; Standard Motor (Belt Drive)**

AIRFLOW
(Cfm)
600
700
800
900
1000

0.1
Rpm
Bhp
490
0.08
519
0.09
537
0.1
560
0.13
589
0.15

EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
521
0.08
597
0.14
703
0.21
788
0.29
557
0.09
623
0.16
729
0.24
816
0.32
582
0.12
650
0.19
751
0.27
845
0.37
610
0.14
681
0.22
783
0.32
870
0.42
640
0.16
707
0.26
808
0.36
894
0.47

51

1.0
Rpm
868
892
927
947
971

Bhp
0.37
0.41
0.47
0.53
0.58

50HE,HJ

Table 24—Fan Performance 50HJ007 — Vertical Discharge Units; High-Static Motor (Belt Drive)*

Table 26—Fan Performance 50HJ004, 50HE004 — Horizontal Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

50HE,HJ

AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

Rpm
554
583
612
643
674
706
738

0.2
Bhp
0.14
0.16
0.20
0.23
0.28
0.33
0.38

Rpm
1017
1041
1065
1089
1114
1139
1164

1.2
Bhp
0.64
0.70
0.77
0.84
0.92
1.01
1.10

Watts
134
163
195
233
276
324
379

Watts
635
696
763
835
915
1000
1093

Rpm
681
707
735
762
791
820
849

0.4
Bhp
0.22
0.26
0.30
0.35
0.40
0.45
0.52

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
222
783
0.32
316
870
257
808
0.36
358
894
298
834
0.41
406
919
344
860
0.46
459
944
395
887
0.52
517
970
451
914
0.59
582
997
515
942
0.66
653
1024

0.8
Bhp
0.42
0.47
0.52
0.58
0.65
0.72
0.80

Watts
416
465
519
579
645
717
796

Rpm
947
971
995
1020
1045
1071
1097

1.0
Bhp
0.53
0.58
0.64
0.71
0.78
0.86
0.95

Watts
523
578
638
705
777
857
942

Rpm
1082
1105
1129
1153
1177
1202
—

1.4
Bhp
0.76
0.82
0.90
0.98
1.06
1.15
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
753
1143
0.88
876
1200
820
1166
0.95
948
1223
892
1189
1.03
1026
1245
971
1212
1.12
1111
—
1056
—
—
—
—
1149
—
—
—
—
—
—
—
—
—

1.8
Bhp
1.01
1.09
1.17
—
—
—
—

Watts
1004
1081
1165
—
—
—
—

Rpm
1254
—
—
—
—
—
—

2.0
Bhp
1.14
—
—
—
—
—
—

Watts
1136
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 680 to 1044 rpm. All other rpms require field-supplied
drive.

Table 27—Fan Performance 50HJ004, 50HE004 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500
AIRFLOW
CFM
900
1000
1100
1200
1300
1400
1500

Rpm
554
583
612
643
674
706
738

0.2
Bhp
0.14
0.16
0.20
0.23
0.28
0.33
0.38

Rpm
1017
1041
1065
1089
1114
1139
1164

1.2
Bhp
0.64
0.70
0.77
0.84
0.92
1.01
1.10

Watts
134
163
195
233
276
324
379

Watts
635
696
763
835
915
1000
1093

Rpm
681
707
735
762
791
820
849

0.4
Bhp
0.22
0.26
0.30
0.35
0.40
0.45
0.52

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
222
783
0.32
316
870
257
808
0.36
358
894
298
834
0.41
406
919
344
860
0.46
459
944
395
887
0.52
517
970
451
914
0.59
582
997
515
942
0.66
653
1024

0.8
Bhp
0.42
0.47
0.52
0.58
0.65
0.72
0.80

Watts
416
465
519
579
645
717
796

Rpm
947
971
995
1020
1045
1071
1097

1.0
Bhp
0.53
0.58
0.64
0.71
0.78
0.86
0.95

Watts
523
578
638
705
777
857
942

Rpm
1082
1105
1129
1153
1177
1202
1227

1.4
Bhp
0.76
0.82
0.90
0.98
1.06
1.15
1.25

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
753
1143
0.88
876
1200
820
1166
0.95
948
1223
892
1189
1.03
1026
1245
971
1212
1.12
1111
1269
1056
1236
1.21
1202
1292
1149
1261
1.31
1301
1316
1248
1285
1.41
1407
1341

1.8
Bhp
1.01
1.09
1.17
1.26
1.36
1.47
1.58

Watts
1004
1081
1165
1256
1353
1457
1570

Rpm
1254
1276
1299
1322
1346
1369
1394

2.0
Bhp
1.14
1.23
1.32
1.41
1.52
1.63
1.75

Watts
1136
1219
1308
1404
1508
1618
1736

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.

52

AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000

Rpm
643
674
706
738
771
804
837
871
906

0.2
Bhp
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76

Rpm
1089
1114
1139
1164
1190
—
—
—
—

1.2
Bhp
0.84
0.92
1.01
1.10
1.20
—
—
—
—

Watts
233
276
324
379
440
507
582
665
756

Watts
835
915
1000
1093
1193
—
—
—
—

Rpm
762
791
820
849
879
910
941
972
1004

0.4
Bhp
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
344
860
0.46
459
944
395
887
0.52
517
970
451
914
0.59
582
997
515
942
0.66
653
1024
584
971
0.74
731
1051
661
1000
0.82
816
1079
745
1029
0.91
909
1107
837
1059
1.02
1010
1136
938
1089
1.12
1119
—

0.8
Bhp
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
—

Watts
579
645
717
796
881
974
1075
1184
—

Rpm
1020
1045
1071
1097
1124
1151
—
—
—

1.0
Bhp
0.71
0.78
0.86
0.95
1.04
1.14
—
—
—

Watts
705
777
857
942
1035
1136
—
—
—

Rpm
1153
1177
1202
—
—
—
—
—
—

1.4
Bhp
0.98
1.06
1.15
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
971
1212
1.12
1111
—
1056
—
—
—
—
1149
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—

Rpm
—
—
—
—
—
—
—
—
—

2.0
Bhp
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field-supplied
drive.

Table 29—Fan Performance 50HJ005, 50HE005 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000
AIRFLOW
CFM
1200
1300
1400
1500
1600
1700
1800
1900
2000

Rpm
643
674
706
738
771
804
837
871
906

0.2
Bhp
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76

Rpm
1089
1114
1139
1164
1190
1217
1244
1271
1298

1.2
Bhp
0.84
0.92
1.01
1.10
1.20
1.31
1.42
1.55
1.68

Watts
233
276
324
379
440
507
582
665
756

Watts
835
915
1000
1093
1193
1301
1417
1541
1674

Rpm
762
791
820
849
879
910
941
972
1004

0.4
Bhp
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
344
860
0.46
459
944
395
887
0.52
517
970
451
914
0.59
582
997
515
942
0.66
653
1024
584
971
0.74
731
1051
661
1000
0.82
816
1079
745
1029
0.91
909
1107
837
1059
1.02
1010
1136
938
1089
1.12
1119
1165

0.8
Bhp
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
1.31

Watts
579
645
717
796
881
974
1075
1184
1301

Rpm
1020
1045
1071
1097
1124
1151
1178
1206
1234

1.0
Bhp
0.71
0.78
0.86
0.95
1.04
1.14
1.25
1.37
1.49

Watts
705
777
857
942
1035
1136
1244
1361
1486

Rpm
1153
1177
1202
1227
1252
1278
1305
1331
1358

1.4
Bhp
0.98
1.06
1.15
1.25
1.36
1.48
1.60
1.73
1.87

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
971
1212
1.12
1111
1269
1056
1236
1.21
1202
1292
1149
1261
1.31
1301
1316
1248
1285
1.41
1407
1341
1355
1311
1.53
1520
1366
1470
1336
1.65
1642
1391
1593
1362
1.78
1772
1416
1724
1388
1.92
1911
1442
1865
1415
2.07
2059
1468

1.8
Bhp
1.26
1.36
1.47
1.58
1.70
1.83
1.97
2.11
2.27

Watts
1256
1353
1457
1570
1690
1818
1955
2101
2256

Rpm
1322
1346
1369
1394
1418
1443
1468
1494
—

2.0
Bhp
1.41
1.52
1.63
1.75
1.87
2.01
2.15
2.31
—

Watts
1404
1508
1618
1736
1863
1998
2141
2294
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-supplied
drive.

53

50HE,HJ

Table 28—Fan Performance 50HJ005, 50he005 — Horizontal Discharge Units; Standard Motor
(Belt Drive)*

Table 30—Fan Performance 50HJ006, 50HE006 Single-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
AIRFLOW
CFM

50HE,HJ

1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
724
757
790
823
857
892
927
962
997
1033
1069

0.2
Bhp
0.33
0.39
0.45
0.52
0.59
0.67
0.77
0.87
0.97
1.09
1.22

Rpm
1188
1208
1229
—
—
—
—
—
—
—
—

1.2
Bhp
1.09
1.16
1.24
—
—
—
—
—
—
—
—

Watts
295
343
398
458
525
599
680
769
865
970
1084

Watts
970
1033
1103
—
—
—
—
—
—
—
—

Rpm
837
866
894
924
955
986
1017
1050
1082
1115
—

0.4
Bhp
0.45
0.51
0.58
0.65
0.73
0.82
0.92
1.02
1.14
1.26
—

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
402
937
0.59
524
1028
455
962
0.65
580
1050
514
988
0.72
643
1074
579
1015
0.80
712
1099
650
1043
0.89
787
1125
729
1072
0.98
870
1151
815
1101
1.08
960
1178
909
1131
1.19
1059
—
1010
—
—
—
—
1120
—
—
—
—
—
—
—
—
—

0.8
Bhp
0.74
0.81
0.88
0.96
1.05
1.15
1.26
—
—
—
—

Watts
660
719
784
857
936
1022
1116
—
—
—
—

Rpm
1111
1132
1154
1177
1201
—
—
—
—
—
—

1.0
Bhp
0.91
0.98
1.06
1.14
1.23
—
—
—
—
—
—

Watts
808
870
938
1013
1096
—
—
—
—
—
—

Rpm
1261
—
—
—
—
—
—
—
—
—
—

1.4
Bhp
1.29
—
—
—
—
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1143
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
—
—
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—
—
—

Rpm
—
—
—
—
—
—
—
—
—
—
—

2.0
Bhp
—
—
—
—
—
—
—
—
—
—
—

Watts
—
—
—
—
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.

54

AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
724
757
790
823
857
892
927
962
997
1033
1069

0.2
Bhp
0.33
0.39
0.45
0.52
0.59
0.67
0.77
0.87
0.97
1.09
1.22

Rpm
1188
1208
1229
1250
1273
1296
1320
1345
1371
1397
1424

1.2
Bhp
1.09
1.16
1.24
1.33
1.43
1.53
1.64
1.77
1.90
2.04
2.19

Watts
295
343
398
458
525
599
680
769
865
970
1084

Watts
970
1033
1103
1181
1266
1359
1459
1568
1686
1812
1948

Rpm
837
866
894
924
955
986
1017
1050
1082
1115
1149

0.4
Bhp
0.45
0.51
0.58
0.65
0.73
0.82
0.92
1.02
1.14
1.26
1.39

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
402
937
0.59
524
1028
455
962
0.65
580
1050
514
988
0.72
643
1074
579
1015
0.80
712
1099
650
1043
0.89
787
1125
729
1072
0.98
870
1151
815
1101
1.08
960
1178
909
1131
1.19
1059
1206
1010
1161
1.31
1165
1235
1120
1192
1.44
1279
1264
1239
1223
1.58
1403
1293

0.8
Bhp
0.74
0.81
0.88
0.96
1.05
1.15
1.26
1.37
1.50
1.63
1.77

Watts
660
719
784
857
936
1022
1116
1218
1329
1448
1576

Rpm
1111
1132
1154
1177
1201
1226
1251
1277
1304
1332
1360

1.0
Bhp
0.91
0.98
1.06
1.14
1.23
1.33
1.44
1.56
1.69
1.83
1.98

Watts
808
870
938
1013
1096
1185
1283
1389
1503
1625
1757

Rpm
1261
1279
1299
1319
1341
1363
1386
1409
1434
1459
—

1.4
Bhp
1.29
1.36
1.44
1.53
1.63
1.74
1.85
1.98
2.11
2.26
—

EXTERNAL STTIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1143
1330
1.49
1327
1395
1208
1347
1.57
1394
1412
1280
1366
1.65
1468
1429
1360
1385
1.74
1549
1448
1447
1405
1.84
1638
1467
1542
1427
1.95
1736
1488
1646
1448
2.07
1842
1508
1758
1471
2.20
1956
—
1878
1494
2.34
2080
—
2008
—
—
—
—
—
—
—
—
—

1.8
Bhp
1.71
1.79
1.88
1.97
2.07
2.18
2.30
—
—
—
—

Watts
1523
1590
1665
1748
1839
1939
2047
—
—
—
—

Rpm
1457
1474
1490
1508
1527
—
—
—
—
—
—

2.0
Bhp
1.95
2.02
2.11
2.20
2.31
—
—
—
—
—
—

Watts
1729
1797
1873
1957
2050
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-supplied
drive.

55

50HE,HJ

Table 31—Fan Performance 50HJ006, 50HE006 Three-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*

Table 32—Fan Performance 50HJ006, 50HE006 — Horizontal Discharge Units;
HIGH--STATIC Motor (Belt Drive)*
AIRFLOW
CFM

50HE,HJ

1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
CFM
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500

Rpm
724
757
790
823
857
892
927
962
997
1033
1069

0.2
Bhp
0.33
0.39
0.45
0.52
0.59
0.67
0.77
0.87
0.97
1.09
1.22

Rpm
1188
1208
1229
1250
1273
1296
1320
1345
1371
1397
1424

1.2
Bhp
1.09
1.16
1.24
1.33
1.43
1.53
1.64
1.77
1.90
2.04
2.19

Watts
295
343
398
458
525
599
680
769
865
970
1084

Watts
970
1033
1103
1181
1266
1359
1459
1568
1686
1812
1948

Rpm
837
866
894
924
955
986
1017
1050
1082
1115
1149

0.4
Bhp
0.45
0.51
0.58
0.65
0.73
0.82
0.92
1.02
1.14
1.26
1.39

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
402
937
0.59
524
1028
455
962
0.65
580
1050
514
988
0.72
643
1074
579
1015
0.80
712
1099
650
1043
0.89
787
1125
729
1072
0.98
870
1151
815
1101
1.08
960
1178
909
1131
1.19
1059
1206
1010
1161
1.31
1165
1235
1120
1192
1.44
1279
1264
1239
1223
1.58
1403
1293

0.8
Bhp
0.74
0.81
0.88
0.96
1.05
1.15
1.26
1.37
1.50
1.63
1.77

Watts
660
719
784
857
936
1022
1116
1218
1329
1448
1576

Rpm
1111
1132
1154
1177
1201
1226
1251
1277
1304
1332
1360

1.0
Bhp
0.91
0.98
1.06
1.14
1.23
1.33
1.44
1.56
1.69
1.83
1.98

Watts
808
870
938
1013
1096
1185
1283
1389
1503
1625
1757

Rpm
1261
1279
1299
1319
1341
1363
1386
1409
1434
1459
1484

1.4
Bhp
1.29
1.36
1.44
1.53
1.63
1.74
1.85
1.98
2.11
2.26
2.42

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1143
1330
1.49
1327
1395
1208
1347
1.57
1394
1412
1280
1366
1.65
1468
1429
1360
1385
1.74
1549
1448
1447
1405
1.84
1638
1467
1542
1427
1.95
1736
1488
1646
1448
2.07
1842
1508
1758
1471
2.20
1956
1530
1878
1494
2.34
2080
1553
2008
1518
2.49
2213
1576
2147
1543
2.65
2355
1599

1.8
Bhp
1.71
1.79
1.88
1.97
2.07
2.18
2.30
2.44
2.58
2.73
2.89

Watts
1523
1590
1665
1748
1839
1939
2047
2164
2290
2425
2571

Rpm
1457
1474
1490
1508
1527
1546
1566
1587
1609
—
—

2.0
Bhp
1.95
2.02
2.11
2.20
2.31
2.42
2.55
2.68
2.83
—
—

Watts
1729
1797
1873
1957
2050
2151
2262
2380
2509
—
—

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.

Table 33—Fan Performance 50HJ007 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
1800

1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm

0.2
Bhp

Rpm
1244
1268
1294
1320
1346
1372
1400
1427
—
—
—
—
—

1.2
Bhp
1.33
1.44
1.55
1.67
1.80
1.94
2.09
2.24
—
—
—
—
—

822
855
889
923
957
992
1026
1061
1097
1132
1168
1204
1240

0.51
0.59
0.66
0.75
0.85
0.95
1.06
1.19
1.32
1.46
1.61
1.77
1.94

Watts
455
520
591
668
753
845
945
1053
1169
1294
1428
1572
1725

Watts
1182
1275
1376
1483
1598
1721
1852
1992
—
—
—
—
—

Rpm

0.4
Bhp

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts
Rpm
Bhp
Watts
Rpm

0.8
Bhp

Watts

Rpm

1.0
Bhp

Watts

Rpm
1308
1332
1357
1382
1408
1434
1460
—
—
—
—
—
—

1.4
Bhp
1.51
1.63
1.74
1.87
2.01
2.15
2.31
—
—
—
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts
Rpm
Bhp
Watts
Rpm
1345
1369
1.70
1513
1427
1443
1393
1.82
1617
1450
1549
1417
1.95
1727
1474
1662
1441
2.08
1845
1498
1782
1466
2.22
1971
—
1911
1491
2.37
2105
—
2047
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
1.90
2.02
2.15
2.29
—
—
—
—
—
—
—
—
—

Watts
1687
1796
1911
2034
—
—
—
—
—
—
—
—
—

Rpm
1483
1505
1528
—
—
—
—
—
—
—
—
—
—

2.0
Bhp
2.10
2.23
2.36
—
—
—
—
—
—
—
—
—
—

Watts
1867
1979
2100
—
—
—
—
—
—
—
—
—
—

927
957
988
1019
1051
1083
1115
1148
1181
1214
1247
1281
1315

0.66
0.74
0.83
0.92
1.03
1.14
1.26
1.39
1.53
1.67
1.83
2.00
2.18

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.

589
659
737
821
912
1011
1118
1233
1356
1487
1629
1779
1939

1018
1046
1075
1104
1134
1164
1195
1226
1257
1289
1320
1353
—

0.82
0.91
1.00
1.10
1.21
1.33
1.46
1.59
1.74
1.90
2.06
2.24
—

728
805
888
979
1077
1182
1295
1416
1546
1684
1832
1989
—

1100
1127
1154
1182
1210
1239
1268
1297
1327
1358
1388
—
—

0.98
1.08
1.18
1.29
1.40
1.53
1.66
1.81
1.96
2.12
2.30
—
—

873
956
1045
1142
1245
1357
1476
1604
1740
1885
2039
—
—

1174
1200
1226
1253
1280
1308
1336
1364
1393
1422
—
—
—

1.15
1.25
1.36
1.48
1.60
1.73
1.87
2.02
2.18
2.35
—
—
—

1024
1113
1208
1310
1419
1537
1662
1796
1938
2089
—
—
—

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1120 to 1585 rpm. All other rpms require field-supplied
drive.

56

AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
AIRFLOW
CFM
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000

Rpm
822
855
889
923
957
992
1026
1061
1097
1132
1168
1204
1240

0.2
Bhp
0.51
0.59
0.66
0.75
0.85
0.95
1.06
1.19
1.32
1.46
1.61
1.77
1.94

Rpm
1244
1268
1294
1320
1346
1372
1400
1427
1455
1483
1512
1541
—

1.2
Bhp
1.33
1.44
1.55
1.67
1.80
1.94
2.09
2.24
2.41
2.59
2.77
2.97
—

Watts
455
520
591
668
753
845
945
1053
1169
1294
1428
1572
1725

Watts
1182
1275
1376
1483
1598
1721
1852
1992
2140
2297
2463
2640
—

Rpm
927
957
988
1019
1051
1083
1115
1148
1181
1214
1247
1281
1315

0.4
Bhp
0.66
0.74
0.83
0.92
1.03
1.14
1.26
1.39
1.53
1.67
1.83
2.00
2.18

EXTERNAL STATIC PRESSURE (in. wg)
0.6
Watts Rpm
Bhp
Watts
Rpm
589
1018
0.82
728
1100
659
1046
0.91
805
1127
737
1075
1.00
888
1154
821
1104
1.10
979
1182
912
1134
1.21
1077
1210
1011
1164
1.33
1182
1239
1118
1195
1.46
1295
1268
1233
1226
1.59
1416
1297
1356
1257
1.74
1546
1327
1487
1289
1.90
1684
1358
1629
1320
2.06
1832
1388
1779
1353
2.24
1989
1419
1939
1385
2.43
2156
1451

0.8
Bhp
0.98
1.08
1.18
1.29
1.40
1.53
1.66
1.81
1.96
2.12
2.30
2.48
2.68

Watts
873
956
1045
1142
1245
1357
1476
1604
1740
1885
2039
2202
2376

Rpm
1174
1200
1226
1253
1280
1308
1336
1364
1393
1422
1452
1482
—

1.0
Bhp
1.15
1.25
1.36
1.48
1.60
1.73
1.87
2.02
2.18
2.35
2.53
2.72
—

Watts
1024
1113
1208
1310
1419
1537
1662
1796
1938
2089
2249
2419
—

Rpm
1308
1332
1357
1382
1408
1434
1460
1487
1514
1541
—
—
—

1.4
Bhp
1.51
1.63
1.74
1.87
2.01
2.15
2.31
2.47
2.64
2.83
—
—
—

EXTERNAL STATIC PRESSURE (in. wg)
1.6
Watts Rpm
Bhp
Watts
Rpm
1345
1369
1.70
1513
1427
1443
1393
1.82
1617
1450
1549
1417
1.95
1727
1474
1662
1441
2.08
1845
1498
1782
1466
2.22
1971
1522
1911
1491
2.37
2105
1547
2047
1517
2.53
2247
1572
2192
1543
2.70
2398
—
2346
1570
2.88
2557
—
2509
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

1.8
Bhp
1.90
2.02
2.15
2.29
2.44
2.59
2.76
—
—
—
—
—
—

Watts
1687
1796
1911
2034
2165
2304
2451
—
—
—
—
—
—

Rpm
1483
1505
1528
1552
1575
1600
—
—
—
—
—
—
—

2.0
Bhp
2.10
2.23
2.36
2.51
2.66
2.82
—
—
—
—
—
—
—

Watts
1867
1979
2100
2227
2363
2507
—
—
—
—
—
—
—

NOTES:
1. Bold cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.

LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-supplied
drive.

57

50HE,HJ

Table 34—Fan Performance 50HJ007 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*

PRE-START-UP

!

WARNING

FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

50HE,HJ

Failure to follow this warning could result in personal
injury, death, and/or property damage.
1. Follow recognized safety practices and wear protective
goggles when checking or servicing a refrigerant system.
2. Do not operate the compressor or provide any electric
power to the unit unless the compressor terminal cover is
in place and secured.
3. Do not remove the compressor terminal cover until all
electrical sources are disconnected and tagged with lockout
tags.
4. Relieve all pressure from the system before touching or
disturbing anything inside the terminal box if a
refrigerant leak is suspected around the compressor
terminals. Use accepted methods to recover the
refrigerant.
5. Never attempt to repair a soldered connection while the
refrigerant system is under pressure.
6. Do not use a torch to remove any component. The
system contains oil and refrigerant under pressure. To
remove a component, wear protective goggles and proceed
as follows:
a. Shut off electrical power to the unit and tag
disconnect.
b. Recover refrigerant to relieve all pressure
from the system using both high-pressure
and low-pressure ports.
c. Cut component connection tubing with a
tubing cutter, and remove the component
from the unit.
d. Carefully unsweat the remaining tubing
stubs when necessary. Oil can ignite when
exposed to a torch flame.

Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, halide torch, or liquid-soap
solution.
c. Inspect all field-wiring and factory-wiring connections.
Be sure that connections are completed and tight. Be sure
that wires are not in contact with refrigerant tubing or
sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan Adjustment
section for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with water
to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts
have been removed.

START-UP
Step 1 —Unit Preparation
Make sure that the unit has been installed in accordance with
installation instructions and applicable codes.
Step 2 —Return--Air Filters
Make sure the correct filters are installed in the unit (See Table 1).
Do not operate the unit without return-air filters.
Step 3 —Outdoor--Air Inlet Screens
Outdoor-air inlet screen(s) must be in place before operating the
unit.
Step 4 —Compressor Mounting
Compressors are internally spring mounted. Do not loosen or
remove the compressor holddown bolts.
Step 5 —Internal Wiring
Check all electrical connections in unit control boxes; tighten
them as required.
Step 6 —Refrigerant Service Ports
Each unit system has 4 Schrader--type service ports: one on the
suction line, one on the liquid line, and 2 on the compressor
discharge line. Be sure that caps on the ports are tight.
Step 7 —High Flow Valves
Two high flow refrigerant valves are located on the hot gas tube
coming out of the compressor and the suction tubes. Large black
plastic caps distinguish these valves with O--rings located inside
the caps. No field access to these valves is available at this time.
Ensure the plastic caps are in place and tight or the possibility of
refrigerant leakage could occur.
Step 8 —Compressor Rotation
On 3-phase units be certain that the compressor is rotating in the
proper direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect the service gauges to suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
1. Note that the indoor fan (006 and 007 three-phase units
only) is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.
The suction and discharge pressure levels should now move to
their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes more noise and does not provide cooling.
Step 9 —Cooling
Set the space thermostat to the OFF position. Set the system
selector switch at COOL position and the fan switch at AUTO
position. Adjust the thermostat to a setting below room
temperature. The compressor starts when contactor closes.
Check cooling effects at a setting below room temperature.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The
compressor will shut off.
To Shut Off Unit -- Set the system selector switch at OFF
position. Resetting the thermostat at a position above room
temperature shuts off the unit temporarily until the space
temperature exceeds the thermostat setting. Units are equipped
58

because of the increase in fresh air, the outdoor--air damper will
be proportionally closed. Damper position will follow the higher
demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice versa)
will take between 1--1/2 and 2--1/2 minutes.
If free cooling can be used as determined from the appropriate
changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cooling
(Y1 closes at the thermostat) will cause the control to modulate
the dampers open to maintain the supply air temperature set point
at 50_ to 55_ F.
As the supply air temperature drops below the set point range of
50_ to 55_ F, the control will modulate the outdoor--air dampers
closed to maintain the proper supply--air temperature.
Heating -- Units With Economi$er IV
When the room temperature calls for heat, the heating controls are
energized as described in the Heating, Units Without Economizer
section. When the thermostat is satisfied, the economizer damper
moves to the minimum position.
Cooling -- Units With Economi$er2, Premierlinkt Control
and a Thermostat
When free cooling is not available, the compressors will be
controlled by the PremierLink control in response to the Y1 and
Y2 inputs from the thermostat.
The PremierLink control will use the following information to
determine if free cooling is available:

S
S

Indoor fan has been on for at least 30 seconds.

S
S
S

OAT must be less than 75_F.

The SPT, SAT, and OAT inputs must have valid
readings.
OAT must be less than SPT.
Enthalpy must be LOW (may be jumpered if an
enthalpy sensor not available).

Economizer position is NOT forced.
Pre-cooling occurs when there is no call from the thermostat
except G. Pre-cooling is defined as the economizer modulates to
provide 70_F supply air.
When free cooling is available the PremierLink control will
control the compressors and economizer to provide a supply-air
temperature determined to meet the Y1 and Y2 calls from the
thermostat using the following three routines. The three control
routines are based on OAT.
The 3 routines are based on OAT where:
SASP = Supply Air Set Point
DXCTLO = Direct Expansion Cooling Lockout Set Point
PID = Proportional Integral
Routine 1 (OAT < DXCTLO)

S

S

Y1 energized – economizer maintains a SASP =
(SATLO1 + 3).

Y2 energized – economizer maintains a SASP =
(SATLO2 + 3).
Routine 2 (DXCTLO < OAT < 68_F)

S

59

S

If only Y1 energized, the economizer maintains a
SASP = (SATLO1 + 3).

S

If SAT > SASP + 5 and economizer position > 80%,
economizer will go to minimum position for 3 minutes
or until SAT > 68_F.

S
S
S

First stage of mechanical cooling will be energized.
Integrator resets.
Economizer opens again and controls to current SASP
after stage one on for 90 seconds.

50HE,HJ

with a Cycle-LOC™ protection device. The unit shuts down on
any safety trip and remains off; an indicator light on the
thermostat comes on. Check the reason for the safety trip.
Compressor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF position and
then to ON position.
Step 10 —Heating
To start unit, turn on main power supply.
Set system selector switch at HEAT position and set thermostat at
a setting above room temperature. Set fan at AUTO position.
First stage of thermostat energizes the first--stage electric heater
elements; second stage energizes second--stage electric heater
elements, if installed. Check heating effects at air supply grille(s).
If electric heaters do not energize, reset limit switch (located on
evaporator--fan scroll) by pressing button located between
terminals on the switch.
TO SHUT OFF UNIT -- Set system selector switch at OFF
position. Resetting thermostat at a position below room
temperature temporarily shuts unit off until space temperature
falls below thermostat setting.
Step 11 —Safety Relief
A soft solder joint at the suction line fitting provides pressure
relief under abnormal temperature and pressure conditions.
Step 12 —Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions,
respectively. Evaporator fan operates continuously to provide
constant air circulation.
Step 13 —Operating Sequence
Cooling -- Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are
energized. The indoor-fan contactor (IFC), reversing valve
solenoid (RVS) and compressor contactor are energized and
indoor-fan motor, compressor, and outdoor fan starts. The
outdoor fan motor runs continuously while unit is cooling.
Heating -- Units Without Economizer
When the thermostat calls for heating, terminal W1 will be
energized with 24v. The IFC and heater contactor no. 1 (HC1)
are energized.
Cooling -- Units With Economi$er IV
When free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is available,
the outdoor-air damper is modulated by the EconoMi$er IV
control to provide a 50_ to 55_F supply-air temperature into the
zone. As the supply-air temperature fluctuates above 55_ or
below 50_F, the dampers will be modulated (open or close) to
bring the supply-air temperature back within the set point limits.
Integrated EconoMi$er IV operation on single-stage units
requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat call for
the fan (G). This will move the damper to its minimum position
during the occupied mode.
If the increase in cooling capacity causes the supply--air
temperature to drop below 45_F, then the outdoor--air damper
position will be fully closed. If the supply--air temperature
continues to fall, the outdoor--air damper will close. Control
returns to normal once the supply--air temperature rises above
48_F.
If optional power exhaust is installed, as the outdoor--air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
If field--installed accessory CO2 sensors are connected to the
EconoMi$er IV control, a demand controlled ventilation strategy
will begin to operate. As the CO2 level in the zone increases
above the CO2 set point, the minimum position of the damper
will be increased proportionally. As the CO2 level decreases

With Y1 and Y2 energized Economizer maintains an
SASP = SATLO2 + 3.

S

If SAT > SASP + 5 and economizer position >80%,
economizer will go to minimum position for 3 minutes
or until SAT > 68_F.

S
S

If compressor one is on then second stage of
mechanical cooling will be energized; otherwise the
first stage will be energized.
Integrator resets.

Economizer opens again and controls to SASP after
stage one on for 90 seconds.
Routine 3 (OAT > 68)

50HE,HJ

S
S

75
74
73
72
70
69
68

NOTE: PremierLink control performs smart staging of 2 stages of DX
cooling and up to 3 stages of heat.

Economizer is opened 100%.

Compressors 1 and 2 are cycled based on Y1 and Y2
using minimum on and off times and watching the
supply air temperature as compared to SATLO1 and
SATLO2 set points.
If optional power exhaust is installed, as the outdoor-air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
If field-installed accessory CO2 sensors are connected to the
PremierLink™ control, a PID-controlled demand ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally. As the CO2 level
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed.
Heating -- Units With Economi$er2 Premierlink Control and
a Thermostat
When the thermostat calls for heating, terminal W1 is energized.
The PremierLink control will move the economizer damper to the
minimum position if there is a call for G and closed if there is a
call for W1 without G. The IFC and heater contactor no. 1 (HC1)
are energized. When the thermostat is satisfied and W1 is
deenergized, the IFM stops after a 45--second time--off delay
unless G is still maintained.
Cooling -- Units With Economi$er2, Premierlink Control and
a Room Sensor
When free cooling is not available, the compressors will be
controlled by the PremierLink controller using a PID Error
reduction calculation as indicated by Fig 49.
The PremierLink controller will use the following information to
determine if free cooling is available:

S
S

Indoor fan has been on for at least 30 seconds.

S
S
S

OAT must be less than 75_F.

S

Economizer position is NOT forced.

The SPT, SAT, and OAT inputs must have valid
readings.
OAT must be less than SPT.
Enthalpy must be LOW (may be jumpered if and
enthalpy sensor is not available).

SET POINT
TEMPERATURE

71

TIME

Fig. 49 --- DX Cooling Temperature
Control Example

C06042

TEMPERATURE CONTROL

SPACE TEMPERATURE

S

TEMPERATURE CONTROL

SPACE TEMPERATURE

S

75
74
73
72

COOL SETPOINT
TEMPERATURE
HEAT SETPOINT

71
70
69
68
TIME

Fig. 50 --- Economizer Temperature
Control Example

C06043

When free cooling is available, the outdoor-air damper is
positioned through the use of a Proportional Integral (PID)
control process to provide a calculated supply-air temperature
into the zone. The supply air will maintain the space temperature
between the heating and cooling set points as indicated in Fig. 50.
The PremierLink control will integrate the compressors stages
with the economizer based on similar logic as the three routines
listed in the previous section. The SASP will float up and down
based on the error reduction calculations that compare space
temperature and space set point.
When outside-air temperature conditions require the economizer
to close for a compressor stage-up sequence, the economizer
control integrator is reset to zero after the stage-up sequence is
completed. This prevents the supply-air temperature from
dropping too quickly and creating a freeze condition that would
make the compressor turn off prematurely.
The high space set point is used for DX (direct expansion)
cooling control, while the economizer space set point is a
calculated value between the heating and cooling set points. The
economizer set point will always be at least one degree below the
cooling set point, allowing for a smooth transition from
mechanical cooling with economizer assist, back to economizer
cooling as the cooling set point is achieved. The compressors
may be used for initial cooling then the PremierLink controller
will modulate the economizer using an error reduction calculation
to hold the space temperature between the heating and cooling set
points. (See Fig. 50.)
The controller uses the following conditions to determine
economizer cooling:

S
S
S
60

Enthalpy is Low
SAT reading is available
OAT reading is available

SPT reading is available

S
S
S

Indoor fan has been on for at least 30 seconds.

S
S

SAT reading is available.

S
S

HEAT STAGES=1 (50% capacity) will energize HS1

S
S
S

HEAT STAGES=1 (33% capacity) will energize HS1

OAT ± SPT

Economizer Position is NOT forced
If any of the above conditions are not met, the economizer
submaster reference (ECSR) is set to maximum limit and the
damper moves to minimum position. The operating sequence is
complete. The ECSR is recalculated every 30 seconds.
If an optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
the
If field-installed accessory CO2 sensors are connected to
PremierLink™ control, a PID-controlled demand ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of the
damper will be increased proportionally. As the CO2 level
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed.
Heating -- Unit With Economi$er2, Premierlink Control and
a Room Sensor
Every 40 seconds the controller will calculate the required heat
stages (maximum of 3) to maintain Supply-Air Temperature
(SAT) if the following qualifying conditions are met:

subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then enters a thermostatic
expansion valve (TXV) where the liquid drops to a lower
pressure. The TXV does not have a pressure drop great enough to
change the liquid to a 2-phase fluid, so the liquid then enters the
Acutrol™ device at the evaporator coil.
The liquid enters the evaporator coil at a temperature lower than
in standard cooling operation. This lower temperature increases
the latent capacity of the rooftop unit. The refrigerant passes
through the evaporator and is turned into a vapor. The air passing
over the evaporator coil will become colder than during normal
operation. However, as this same air passes over the subcooling
coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air
temperature is warmer than 40_F. A factory-installed temperature
switch located in the condenser section will lock out subcooling
mode when the outside temperature is cooler than 40_F.
The scroll compressors are equipped with crankcase heaters to
provide protection for the compressors due to the additional
refrigerant charge required by the subcooling/reheat coil.
When in subcooling mode, there is a slight decrease in system
total gross capacity (5% less), a lower gross sensible capacity
(20% less), and a greatly increased latent capacity (up to 40%
more).

COOL mode is not active.
OCCUPIED, TEMP. COMPENSATED START or
HEAT mode is active.

Fire shutdown mode is not active.
If all of the above conditions are met, the number of heat stages is
calculated; otherwise the required number of heat stages will be
set to 0.
If the PremierLink controller determines that heat stages are
required, the economizer damper will be moved to minimum
position if occupied and closed if unoccupied.
Staging should be as follows:
If Heating PID STAGES=2
HEAT STAGES=2 (100% capacity) will energize HS2
If Heating PID STAGES=3 and AUXOUT = HS3

Fig. 51 --- Humidi--MiZer Normal
Design Cooling Operation

C06135

HEAT STAGES=2 (66% capacity) will energize HS2

HEAT STAGES=3 (100% capacity) will energize HS3
Units With Humidi-Mizer™ Adaptive
Dehumidification System
Normal Design Operation
When the rooftop operates under the normal sequence of
operation, the compressors will cycle to maintain indoor
conditions. (See Fig. 51.)
The Humidi-MiZer adaptive dehumidification system includes a
factory-installed Motormaster® low ambient control to keep the
head and suction pressure high, allowing normal design cooling
mode operation down to 0° F.
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the
liquid line solenoid valve (LLSV) forcing the hot liquid
refrigerant to enter into the subcooling coil. (See Fig. 52.)
As the hot liquid refrigerant passes through the subcooling/ reheat
dehumidification coil, it is exposed to the cold supply airflow
coming through the evaporator coil. The liquid is further

Fig. 52 --- Humidi--MiZer Subcooling
Mode Operation

61

C06136

50HE,HJ

S
S
S

50HE,HJ

Fig. 53 --- Humidi--Mizert Hot Gas
Reheat Mode Operation

C06137

Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a
hot gas solenoid valve (specific to hot gas reheat mode only) will
open to bypass a portion of hot gas refrigerant around the
condenser coil. (See Fig. 53.)
This hot gas will mix with liquid refrigerant leaving the
condenser coil and flow to the subcooling/reheat
dehumidification coil. Now the conditioned air coming off the
evaporator will be cooled and dehumidified, but will be warmed
to neutral conditions (72_F to 75_F) by the subcooling/reheat
dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to
provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are
moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat
ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode
operates only when the outside air temperature is warmer than
40_F. Below this temperature, a factory installed outside air
temperature switch will lockout this mode of operation.
See Table 36 for the Humidi-Mizer adaptive dehumidification
system sequence of operation.

4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results,
back-flush toward return-air section to remove foreign
material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Condenser Coil
Inspect coil monthly. Clean condenser coil annually, and as
required by location and outdoor air conditions.
One--Row Coil
Wash coil with commercial coil cleaner. It is not necessary to
remove top panel.
2-Row Coils
Clean coil as follows:
1. Turn off unit power and tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. (See Fig. 54.) To hold
top panel open, place coil corner post between top panel
and center post. (See Fig. 55.)

Fig. 54 --- Cleaning Condenser Coil

C06044

SERVICE

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
When sevicing unit, shut off all electrical power to unit
and install lockout tag.
Step 1 —Cleaning
Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
Evaporator Coil
1. Turn unit power off, tag disconnect. Remove evaporator
coil access panel.
2. If economizer or two-position damper is installed, remove
economizer by disconnecting Molex plug and
removing mounting screws.
3. Slide filters out of unit.

Fig. 55 --- Propping Up Top Panel

62

C06045

Table 35—Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and
System Response — Single Compressor Unit (50HE003--006, 50HJ004-007)
ECONOMIZER FUNCTION
48HE, HJ UNIT OPERATION
OAT. < Economizer Set Point
Economizer
Comp. 1
Subcooling Mode
Hot Gas Reheat Mode
Normal Operation
No
Off
On
Yes
No
No
Off
On
Yes
No
Yes
On
On
Yes
No
Yes
On
On
No
Yes
No
Off
On
No
Yes

NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT --- Outdoor Air Temperature

Fig. 56 --- Separating Coil Sections

Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further
lubrication is required. No lubrication of condenser-fan or
evaporator-fan motors is required.
Evaporator Fan Belt Adjustment
Inspect evaporator fan belt for wear, proper belt tension, and
pulley alignment as conditions require or at the beginning of each
heating and air conditioning season. Refer to Step 7 -- Adjust
Evaporator Fan Speed for adjustment and alignment procedures.
Step 3 —Condenser--Fan Adjustment
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub
setscrews. Adjust fan height as shown in Fig. 57. Tighten
setscrews and replace condenser-fan assembly.

C06046

4. Remove device holding coil sections together at return end
of condenser coil. Carefully separate the outer coil section
3 to 4 in. from the inner coil section. (See Fig. 57.)
5. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal manner.
6. Secure the sections together. Reposition the outer coil
section and remove the coil corner post from between the
top panel and center post. Install the coil corner and center
posts. Replace all screws.
Condensate Drain
Check and clean each year at the start of the cooling season. In
winter, keep the drain dry or protect it against freeze-up.
Filters
Clean or replace at the start of each heating and cooling season, or
more often if operating conditions require it. Replacement filters
must be the same dimensions as the original filters.
Outdoor--Air Inlet Screen
Clean the screen with steam or hot water and a mild detergent. Do
not use disposable filters in place of screens.
Step 2 —Lubrication
Compressor
The compressor is charged with the correct amount of oil at the
factory.

UNIT
003-006 AND 007 (208/230 v)
007 (460 v)

FAN HEIGHT (in.) — “A”
2.75
3.50

Fig. 57 --- Condenser--Fan Adjustment

C06138

Step 4 —EconoMi$er IV Adjustment
Refer to Optional EconoMi$er IV and EconoMi$er2 section.
Step 5 —Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to HVAC Servicing Procedures literature
available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 minutes
before checking or adjusting refrigerant charge.
No Charge
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer
to Table 1 and unit information plate.)

63

50HE,HJ

THERMOSTAT INPUT
H
Y1
Y2
Off
—
—
On
On
On
On
On
Off
On
On
On
On
On
Off
On
Off
Off

50HE,HJ

Low Charge Cooling
Using Cooling Charging Charts, Fig. 58--61, vary refrigerant
until the conditions of the charts are met. Note the charging charts
are different from type normally used. Charts are based on
charging the units to the correct superheat for the various
operating conditions. Accurate pressure gage and temperature
sensing device are required. Connect the pressure gauge to the
service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambient
temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit. An accurate
superheat, thermocouple--type or thermistor--type thermometer,
and a gauge manifold are required when using the superheat
charging method for evaluating the unit charge. Do not use
mercury or small dial--type thermometers because they are not
adequate for this type of measurement.

Fig. 59 --- Cooling Charging Chart,
Standard 50HJ005

Fig. 58 --- Cooling Charging Chart,
Standard 50HJ004

C06140

C06139

Humidi--Mizer™ System Charging
The system charge for units with the Humidi-MiZer adaptive
dehumidification system is greater than that of the standard unit
alone. The charge for units with this option is indicated on the
unit nameplate drawing. Also refer to Fig. 62-65. To charge
systems using the Humidi-MiZer adaptive dehumidification
system, fully evacuate, recover, and recharge the system to the
nameplate specified charge level. To check or adjust refrigerant
charge on systems using the Humidi-MiZer adaptive
dehumidification system, charge per Fig. 62-65.

Fig. 60 --- Cooling Charging Chart,
Standard 50HJ006

64

C06141

50HE,HJ
Fig. 61 --- Cooling Charging Chart,
Standard 50HJ007

C06142

C06144

Fig. 63 --- Cooling Charging Chart, 50HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System

NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fan at full speed.
The charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooling/reheat
dehumidification coil. A tap is provided on the unit to measure
liquid pressure entering the subcooling/reheat dehumidification
coil.
IMPORTANT: The subcooling mode charging charts (Fig.
62--65) are to be used ONLY with units having the
Humidi--MiZer adaptive dehumidification system. DO NOT use
standard charge (Fig. 58--61) for units with Humidi-- MiZer
system, and DO NOT use Fig. 62--65 for standard units.

C06143

Fig. 62 --- Cooling Charging Chart, 50HJ004 with
Optional Humidi--MiZer Adaptive Dehumidification System

65

If a charging device is used, temperature and pressure readings
must be accomplished using the charging charts.
F
125
115
105
95
85
75

50HE -- 2 TON CHARGING CHART
Suction Line Temperature (deg C)

5.5

10.5

15.5

20.5

25.5

C
52
46
41
35
29
24

105.0

Suction Line Pressure (psig)

95.0

648.0

90.0
598.0

85.0
80.0

548.0

75.0
498.0

Suction Line Pressure (kpa)

698.0

100.0

50HE,HJ

70.0
448.0

65.0
42

52

62

72

Suction Line Temp (deg F)

C06148

Fig. 66 --- Cooling Charging Chart,
Standard 50HE003

Fig. 64 --- Cooling Charging Chart, 50HJ005 with
Optional Humidi--MiZer Adaptive Dehumidification System

F
115
105
95
85
75

50HE - 3 TON CHARGING CHART
Suction Line Temperature (deg C)
6.1

11.1

16.1

21.1

95.0
Suction Line Pressure (psig)

C
46
41
35
29
24

648.2

598.2

85.0

548.2
75.0
498.2

65.0

Suction Line Pressure (kpa)

C06145

448.2
43

48

53
58
63
68
Suction Line Temp (deg F)

73

78

C06149

Fig. 67 --- Cooling Charging Chart,
Standard 50HE004
F
115
105
95
85
75

50HE - 4 TON CHARGING CHART

C06146

Suction Line Temperature (deg C)

Fig. 65 --- Cooling Charging Chart, 50HJ007 with
Optional Humidi--MiZer Adaptive Dehumidification System

5.6

10.6

15.6

20.6

C
46
41
35
29
24

25.6

692.0

642.0

87.0
592.0

77.0

542.0

Suction Line Pressure (kpa)

Suction Line Pressure (psig)

To Use Cooling Charging Chart, Standard Unit
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to charts to determine what suction
temperature should be. If suction temperature is high, add
refrigerant. If suction temperature is low, carefully recover some
of the charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 57):
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . 75°F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . 48°F
(Suction temperature may vary ± 5°F.)

97.0

492.0

67.0
42

47

52

57

62

67

72

77

Suction Line Temp (deg F)

Fig. 68 --- Cooling Charging Chart,
Standard 50HE005

66

C06150

Suction Line Temperature (deg C)

0.0

5.0

10.0

15.0

20.0

25.0

710.0

105.0
95.0

610.0

85.0
510.0

75.0
410.0

65.0
55.0

Suction Line Pressure (kpa)

810.0

115.0
Suction Line Pressure (psig)

C
46
41
35
29
24

310.0

42

47

52

57

62

67

72

77

Suction Line Temp (deg F)

Fig. 69 --- Cooling Charging Chart,
Standard 50HE006

C06151

To Use Cooling Charging Charts, Units With
Humidi--Mizer™ Adaptive Dehumidification System
Refer to charts (Fig. 62-65) to determine the proper leaving
condenser pressure and temperature.
Example (Fig. 62):
Leaving Condenser Pressure . . . . . . . . . . . . . . . . . 250 psig
Leaving Condenser Temperature . . . . . . . . . . . . . . . 105_F
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fan at full speed.
IMPORTANT: Refer to Troubleshooting Tables for additional
information.
Step 6 —Replacement Parts
A complete list of replacement parts may be obtained from any
Carrier distributor upon request.

TROUBLESHOOTING
Step 1 —Unit Troubleshooting
Refer to Tables 34-38 for unit troubleshooting details.
Step 2 —Economi$er IV Troubleshooting
See Table 39 for EconoMi$er IV logic.
A functional view of the EconoMi$er IV is shown in Fig. 67.
Typical settings, sensor ranges, and jumper positions are also
shown. An EconoMi$er IV simulator program is available from
Carrier to help with EconoMi$er IV training and
troubleshooting.
Economi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied with
the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.

4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals SO and +.
8. Put 620-ohm resistor across terminals SR and +.
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
4. Remove 620-ohm resistor across SO and +. The Free Cool
LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Single Enthalpy
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator should
be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between 90
and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
5. Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9 v. The actuator should
drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the
Exhaust LED turns on. The exhaust contacts will close 30
to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.

67

50HE,HJ

F
115
105
95
85
75

50HE -- 5 TON CHARGING CHART

50HE,HJ

DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20 and
80% open.
4. Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should
drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Supply--Air Input
To check supply-air input:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The
actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should
drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.

Economi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to operation.
No troubleshooting or testing is done by performing the
following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous
setting.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor from terminals SO
and +. If used, reconnect sensor from terminals SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect
wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and
P1.
11. Apply power (24 vac) to terminals TR and TR1.

68

Table 36—Cooling Service Analysis

Compressor Will Not Start
But Condenser Fan Runs.

Compressor Cycles (Other Than
Normally Satisfying Thermostat).

Compressor Operates Continuously.

Excessive Head Pressure.

Head Pressure Too Low.
Excessive Suction Pressure.
Suction Pressure Too Low.

Evaporator Fan Will Not Shut Off.

CAUSE

Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer, or
control relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in compressor circuit.
Compressor motor burned out, seized, or internal overload open.
Defective run/start capacitor, overload, start
relay.
One leg of 3-phase power dead.
Refrigerant overcharge or undercharge.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or start
relay.
Defective thermostat.
Faulty condenser-fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Condenser coil dirty or restricted.
Dirty air filter.
Dirty condenser coil.
Refrigerant overcharged.
Air in system.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High heat load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Low refrigerant charge.
Metering device or low side restricted.
Insufficient evaporator airflow.
Temperature too low in conditioned area.
Outdoor ambient below 25 F.
Time off delay not finished.

69

REMEDY

Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Replace fuse or reset circuit breaker. Determine
cause.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace filter.
Clean coil.
Recover excess refrigerant.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks, repair, and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Recover excess refrigerant.
Replace filter.
Check for leaks, repair, and recharge.
Remove source of restriction.
Increase air quantity. Check filter and replace if necessary.
Reset thermostat.
Install low-ambient kit.
Wait for 30-second off delay.

50HE,HJ

PROBLEM
Compressor and Condenser Fan
Will Not Start.

Table 37—Humidi-MiZer™ Adaptive Dehumidification System Subcooling Mode Service Analysis
PROBLEM

Subcooling Mode (Liquid Reheat)
Will Not Energize.

CAUSE

No power to control transformer from
evaporator-fan motor.
No power from control transformer to liquid line
solenoid valve.

Liquid line solenoid valve will not operate.
Liquid line solenoid valve will not open.
Low refrigerant charge or frosted evaporator coil.

Low System Capacity.

50HE,HJ

Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.

Thermostatic expansion valve (TXV).

REMEDY

Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck open; replace.
Valve is stuck closed; replace valve.
1. Check charge amount. Charge per Fig. 59-62.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
1. Check TXV bulb mounting, and secure tightly to suction line.
2. Replace TXV if stuck open or closed.

Table 38—Humidi-MiZer™ Adaptive Dehumidification System Hot Gas Reheat Mode Service Analysis
PROBLEM

CAUSE

Reheat Mode Will Not Energize.

No power to control transformer from
evaporator-fan motor.
No power from control transformer to hot gas
line solenoid valve

Hot gas line solenoid valve will not operate.
Low refrigerant charge or frosted evaporator coil.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Excessive Superheat.

Thermostatic expansion valve (TXV).
Liquid line solenoid valve will not operate.
Hot gas line solenoid valve will not close.

REMEDY

Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck closed; replace.
1. Check charge amount. Charge per Fig. 59-62.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
1. Check TXV bulb mounting, and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Valve is stuck, replace valve.
Valve is stuck; replace valve.

Table 39—EconoMi$er IV Input/Output Logic
Demand Control
Ventilation (DCV)
Below set
(DCV LED Off)

Above set
(DCV LED On)

INPUTS
Enthalpy*
Outdoor

Return

High
(Free Cooling LED Off)

Low

Low
(Free Cooling LED On)

High

High
(Free Cooling LED Off)

Low

Low
(Free Cooling LED On)

High

Y1
On
On
Off
On
On
Off
On
On
Off
On
On
Off

Y2
On
Off
Off
On
Off
Off
On
Off
Off
On
Off
Off

Compressor
Stage Stage
1
On
On
Off
On
Off
Off
On
On
Off
On
Off
Off

2
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off

OUTPUTS
N Terminal†
Occupied
Minimum position

Modulating** (between min.
position and full-open)
Minimum position
Modulating†† (between min.
position and DCV maximum)
Modulating***

Unoccupied

Damper
Closed
Modulating** (between
closed and full-open)
Closed
Modulating†† (between
closed and DCV
maximum)
Modulating†††

*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-air signal).

70

50HE,HJ
Fig. 70 --- EconoMi$er IV Functional View

71

C06053

START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:

SERIAL NO.:

DATE:

TECHNICIAN:

II. PRE-START-UP (insert checkmark in box as each item is completed)
j VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE
j VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT
j REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
j VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
50HE,HJ

j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
j CHECK GAS PIPING FOR LEAKS
j CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
j VERIFY THAT UNIT INSTALLATION IS LEVEL
j CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS

III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS
INDOOR-FAN AMPS

L1-L2
L1
L1

L3-L1
L3
L3

L2-L3
L2
L2

TEMPERATURES
OUTDOOR-AIR TEMPERATURE

DB

RETURN-AIR TEMPERATURE

DB

WB

COOLING SUPPLY AIR

DB

WB

PRESSURES (Cooling Mode)
REFRIGERANT SUCTION

PSIG

F

REFRIGERANT DISCHARGE

PSIG

F

j VERIFY THAT 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION. IF THEY
ARE NOT ROTATING IN CORRECT DIRECTION, LOCKING COLLAR MUST BE RE--TIGHTENED AFTER
CORRECTING DIRECTION OF ROTATION
j VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS
(IF EQUIPPED)

Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231

Printed in U.S.A.

Edition Date:09/06

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

72

Catalog No:50H-- 1SI
Replaces:50HJ--31SI



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 72
XMP Toolkit                     : XMP toolkit 2.9.1-14, framework 1.6
About                           : uuid:d864a5b8-1fc3-4fa5-aa65-2783b8e539c0
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2006:10:02 16:30:16-04:00
Create Date                     : 2006:10:02 16:13:26-04:00
Metadata Date                   : 2006:10:02 16:30:16-04:00
Document ID                     : uuid:af16f61e-19d1-4140-b131-7b2d71373ebc
Format                          : application/pdf
Title                           : 50h-1si 1-5
Creator                         : bact1hr
Author                          : bact1hr
EXIF Metadata provided by EXIF.tools

Navigation menu