Carrier 50Xp Users Manual 05PD

50XP to the manual 6e085886-5a07-4bb8-b8d5-8466a80c0ddb

2015-01-24

: Carrier Carrier-50Xp-Users-Manual-310489 carrier-50xp-users-manual-310489 carrier pdf

Open the PDF directly: View PDF PDF.
Page Count: 24

DownloadCarrier Carrier-50Xp-Users-Manual- 50XP-05PD  Carrier-50xp-users-manual
Open PDF In BrowserView PDF
50XP
Performancet 13 SEER
Single ---Packaged Air Conditioner System with PuronR
(R ---410A) Refrigerant Single and Three Phase
2 to 5 Nominal Tons (Sizes 024---060)

Product Data

C99064

Fig. 1 -- Unit 50XP
Single--Packaged Products with Energy--Saving Features and
PuronR refrigerant.
S Up to 13.5 SEER
S Factory--Installed TXV
S Variable Speed Blower--Standard
S Low Sound Levels

FEATURES/BENEFITS
One--piece cooling unit
with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation
High--efficiency design with a SEER (Seasonal Energy Efficiency
Ratio) of up to 13.5.
Puron Environmentally Sound Refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
IdealHumidity Technology featuring Thermidistat control and
Variable Speed Blower motor that provides greater comfort,
humidity control, and energy efficiency. You can expect up to 30
times better dehumidification; economical constant fan for less
than $50 a year, which provides improved indoor air quality and
more even temperatures from room to room; and reduced indoor
noise due to lower air velocity. In addition, you’ll realize improved
installation flexibility with 3 different airflow choices for best
overall comfort.

Easy Installation
Factory--assembled package is a fully self--contained, electric
cooling unit that is prewired, pre--piped, and pre--charged for
minimum installation expense. These units are available in a
variety of standard cooling sizes with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
Durable, dependable components
Scroll Compressors are designed for high efficiency. Each
compressor is hermetically sealed against contamination to help
promote longer life and dependable operation. Each compressor
also has vibration isolation to provide quieter operation. All
compressors have internal high pressure and overcurrent
protection.
Convertible duct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow. Downflow operation is easily provided in the field to
allow vertical ductwork connections. The basepan utilizes
knockout style seals on the bottom openings to ensure a positive
seal in the horizontal airflow mode.
Direct--drive variable speed blower motor is standard on all
models.
Direct--drive PSC condenser--fan motors are designed to help
reduce energy consumption and provide for cooing operation
down to 55_F (13_C) outdoor temperature. Motormasterr II low
ambient kit is available as a field--installed accessory.
Thermostat controls
Time Guardr
II anti--short cycle protection circuitry. If a
non--corporate thermostat without anti--short cycle protection is
used the Time Guard II field--installed anti--short cycle kit is
recommended.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
Thermostatic Expansion Valve -- A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Evaporator and condenser coils are computer--designed for
optimum heat transfer and cooling efficiency. The evaporator coil
is fabricated from copper tube and aluminum fins and is located
inside the unit for protection again damage. The condenser coil is
internally mounted on the top tier of the unit. Copper fin coils and
pre--coated fin coils are available from the factory by special order.
these coils are recommended in applications where aluminum fins
are likely to be damaged due to corrosion. They are ideal for
seacoast applications.
High and Low Pressure Switches provide added reliability for the
compressor.

1

50XP

Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 72dBA. (See Page 4.)
Easy to service cabinets provide easy single--panel accessibility to
serviceable components during maintenance and installation. The
basepan with integrated drain pan provides easy ground level
installation with or without a mounting pad. Convenient handholds
are provided to manipulate the unit on the jobsite. A nesting feature
ensures a positive basepan to roof curb seal when the unit is roof
mounted. A convenient 3/4--in. (19.05 mm) wide perimeter flange
makes frame mounting on a rooftop easy.
Louvered Grille provides hail and vandalism protection for the
coil.
Cabinets are constructed of heavyduty, phosphated, zinc--coated
prepainted steel capable of withstanding 500 hours of salt spray.
Interior surfaces of the evaporator and electric heater compartments
are insulated with cleanable semi--rigid insulation board, which
keeps the conditioned air from being affected by the outdoor
ambient temperature and provides improved indoor air quality.
(Conforms to American Society of Heating, Refrigeration and Air
Conditioning Engineers No. 62P.) The sloped drain pan minimizes
standing water in the drain. An external drain is provided.

TABLE OF CONTENTS
FEATURES/BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . 3
ARI CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
OPTIONS AND ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . 6
BASE UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . 8--9
ACCESSORY ROOF CURB . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 12--16
TYPICAL PIPING AND WIRING . . . . . . . . . . . . . . . . . . . . . 17
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19--20
TYPICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . 21--23
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . 25--26

2

MODEL NUMBER NOMENCLATURE

50XP

---

024

--- --- ---

3

0

1

--- ---

Options
BT --- AL evap, vinyl condenser
CC --- AL evap, CU condenser
CU --- CU evap & condenser
TP --- Base unit with tin plated indoor coil hairpins
TV --- TP with vinyl coating on outdoor coil
TC --- TP with AL indoor coil & CU/CU outdoor
coil

Type of Unit
50XP --- Single Packaged
Air Conditioner
System
N/A
Nominal Cooling Capacity
024 --- 2.0 Tons
030 --- 2.5 Tons
036 --- 3.0 Tons
042 --- 3.5 Tons
048 --- 4.0 Tons
060 --- 5.0 Tons

Packaging
Series

Electrical Supply
3 --- 208/230 ---1 ---60
5 --- 208/230 ---3 ---60

N/A

LEGEND
AL --- Aluminum
CU --- Copper

ISO 9001:2000

REGISTERED

3

50XP

See Price Page for full list of factory options.
Only used if ordering an option

ARI* CAPACITIES

50XP

Cooling Capacities and Efficiencies
UNIT 50XP

NOMINAL TONS

STANDARD CFM

024
030
036
042
048
060

2
2--1/2
3
3--1/2
4
5

770
960
1100
1450
1450
1710

LEGEND
dB--- Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning & Refrigeration Institute.
**At “A” conditions---80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F (35_C) outdoor db.
{ Rated in accordance with U.S. Government DOE Department of Energy)
test procedures and/or ARI Standards 210/240.

NET COOLING
CAPACITIES (Btuh)
24,000
29,000
36,000
41,000
45,000
57,000

EER**

SEER†

11.0
11.0
11.2
11.2
11.0
11.0

13.2
13.0
13.5
13.0
13.0
13.0

Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7_C) db, 67°F wb (19.4_C) indoor entering---air
temperature and 95°F db (35_C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

A--Weighted Sound Power (dBA)
50XP
024
030
036
042
048
060
*

STANDARD
RATING
(dBA)
72
72
72
72
78
78

TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
125

250

500

1000

2000

4000

8000

58.8
58.8
60.7
56.7
62.4
63.5

63.5
63.5
63.3
62.8
69.9
67.6

67.2
67.2
66.8
67.8
71.3
71.8

66.9
66.9
66.5
67.4
73.4
75.5

63.7
63.7
64.2
63.7
70.0
71.0

58.3
58.3
60.3
57.7
66.3
68.1

50.0
50.0
53.0
50.8
60.1
59.9

Tested in accordance with ARI Standard 270 (not listed in ARI).

4

PHYSICAL DATA
Physical Data--Unit 50XP

COMPRESSORS
Quantity
REFRIGERANT (R --- 410A)
Quantity (lb.)
Quantity (kg)
REFRIGERANT METERING DEVICE
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Diameter (mm)
Motor Hp (Rpm)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size (in.)
Size (mm.)
Motor HP (RPM)
HIGH --- PRESSURE SWITCH
(psig) Cut--- out Reset (Auto)
LOSS--- OF--- CHARGE / LOW --- PRESSURE
SWITCH (Liquid Line) (psig) cut--- out Reset (auto)
RETURN--- AIR FILTERS†}
Throwaway Size (in.)
Throwaway Size (mm)

024
2
356
161

030
2 ---1/2
360
163

036
3
378
171

042
3 ---1/2
436
198

048
4
470
213

060
5
515
234

10.7
4.9

11.25
5.1

13.2
6.0

Scroll
1
7.3
3.3

8.0
3.6

9.5
4.3
TXV

2...21
11.95

2...21
12.0

2...21
13.6

2...21
15.4

2...21
17.4

2...21
19.3

2350
22
558.8
1/8 (825)

2700
22
558.8
1/8 (825)

2350
22
558.8
1/8 (825)

2800
22
558.8
1/8 (825)

3300
22
558.8
1/4 (1100)

3300
22
558.8
1/4 (1100)

3...15
3.7

3...15
3.7

4...15
3.7

3...15
4.7

4...15
4.7

4...17
5.7

800
10x10
254x254
1/2 (1050)

1000
10x10
254x254
1/2 (1050)

1400
11x10
279.4x254
3/4 (1075)

1750
11x10
279.4x254
1.0 (1040)

1100
1400
11x10
11x10
279.4x254
279.4x254
3/4 (1000)
3/4 (1075)
650 +/ --- 15
420 +/ --- 25
20 +/ --- 5
45 +/ --- 10

20x20x1
508x508x25

20x24x1
508x610x25

24x30x1
610x762x25

Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity
of 300 ft/minute for throwaway type or 450 ft/minute for high ---capacity type. Air filter pressure drop for non ---standard filters must not exceed 0.08 IN. W.C..
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.

{

5

50XP

UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT (lb)
SHIPPING WEIGHT (kg)

OPTIONS AND ACCESSORIES

compartment. Heater sizes range from 5.0 to 20.0 kW. The electric
heater design allows the use of a single--point power supply for the
entire unit, resulting in lower installed costs.
Filter Rack features easy installation, serviceability, and
high--filtering performance for vertical or horizontal applications.
Flat roof curbs in both 8 in. (203.2 mm) and 14 in. (355.6 mm)
sizes are available for roof mounted applications.

Factory--installed options

50XP

Coil options include Tin--Plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction. See
model number nomenclature for coil options.
*Tin--Plated indoor coils are built with special hairpins that are
designed to resist both general pitting corrosion and excessive
indoor corrosion(Formicary Corrosion).
Field--installed accessories

Square--to--round duct transition kit enables 024--048 size units

to be fitted to 14 in. (355.6 mm) round ductwork.
Thermidistat Control coupled with the system’s variable speed
indoor blower delivers Carrier’s patented IdealHumidity
Technology that allows for even greater humidity control. Along
with more precisely controlling temperature and humidity, the
Thermidistat offers full seven--day programmability allowing you
to further customize your comfort and energy savings.
Thermostats provide control for the system heating and cooling
functions. Thermostat models are available in both programmable
and non--programmable versions.
Crankcase Heater provides anti--floodback protection for
low--load cooling applications.
Compressor start kit assists compressor start--up by providing
additional starting torque on single phase units and prolongs
compressor motor life.
Rigging kit includes lifting brackets which are inserted into the
unit base rigging holds to lift unit for rooftop applications.
Low--ambient kit (Motormaster II control) allows the use of
mechanical cooling down to outdoor temperatures as low as 0_F
(--17_C) when properly installed.
Solid--state Time Guard II device provides short--cycling
protection for the compressor. Not required with corporate
electronic thermostats.
Lifting kit, including 4 metal brackets that are available to assist in
lifting this product onto a roof application.

Economizer with Solid-- State Controls and Barometric
Relief Dampers
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Flat Roof Curbs (8-- in. and 14-- in.) (203.2 and 355.6 mm)
Square-- to-- Round Duct Transition Kit
Thermidistatt
Thermostats
Crankcase Heater
Compressor Start Kit (for use on single--phase units only)
Rigging Kit
Low Ambient Kit (Motormaster® II Control)
Solid-- State Time Guard® II Device
Lifting Kit

Economizer with solid--state controls and barometric relief
dampers includes filter racks and provide outdoor air during
cooling and reduce compressor operation.
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required.
Each package has a heater module that slides into the controls

Electric Heaters
CATALOG
ORDERING NO.

NOMINAL
CAPACITY (kW)

USED WITH SIZES

FUSES

024

030

036

042

048

060

ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)
CPHEATER052A00

5.0

0

X

X

X

X

X

X

CPHEATER069A00

7.5

0

X

X

X

X

X

X

CPHEATER065A00

10.0

0

X

X

X

X

X

X

CPHEATER051A00

15.0

4

X

X

X

X

X

CPHEATER053A00

20.0

6

X

X

20.0

6

CPHEATER054A00

X

ELECTRIC HEATERS (208/230 — THREE PHASE — 60 Hz)
CPHEATER055A00

5.0

0

X

X

X

X

CPHEATER056A00

10.0

0

X

X

X

X

X

CPHEATER057A00

15.0

0

X

X

X

X

CPHEATER059A00

20.0

6

X

X

X

X

NOTE: Electric heaters are rated at 240v. Refer to Multiplication Factors table for other voltages.
X = Approved combinations.

Minimum Airflow for Reliable Electric Heater Operation (CFM)
UNIT SIZE
AIRFLOW

024
750

030
1000

036
1250

042
1400

6

048
1500

060
1800

ECONOMIZER

COIL
FILTER ACCESS DOOR
(HORIZONTAL
APPLICATION ONLY.)
DO NOT REMOVE
FROM DOWNFLOW
DISCHARGE.

FILTER

REPLACEMENT
PANEL

ECONOMIZER

HOLE FOR
ECONOMIZER
WIRING HARDNESS
17 13/32
11 13/32”

CAULK BOTTOM CORNER
OF ECONOMIZER
ON EACH SIDE

SIDE VIEW

16 1/4”

HINGED FILTER
ACCESS DOOR

FI LTER
COIL

50XP

RAINHOOD
DOOR
LATCH ANGLE

INSTALL
FILTER ACCESS
DOOR STICKER

ALUMINUM
FILTER

ECONOMIZER

BASE

FLANGE
ON BASE

DETAIL

MANUAL OUTSIDE AIR DAMPER

FILTER RACK
BEND FLANGE AT 90˚ -SCREW TO
DIVIDER WITH 1-IN. SCREW

REPLACEMENT
PANEL

MANUAL OUTSIDE
AIR HOOD

TOP FILTER RACK
EV APORATOR
COIL

DAMPER
BLADE

BOTTOM FILTER
RACK

A05239

7

50XP

UNIT DIMENSIONS - 50XP024--036

A08452

8

50XP

UNIT DIMENSIONS - 50XP042--060

A08453

9

ACCESSORY ROOF CURB -- 50XP024--060
HVAC unit
base

HVAC unit
base

Screw
(NO TE A)

Screw
(NOTE A)

Gasketing
inner flange*

*Gasketing
outer flange

Gask eting
inner flange*

*Gasketing
outer flange
Wood nailer*

Wood nailer*
Flashing field
supplied

Flashing field
supplied

Roofcurb*
Insulation (field
supplied)

Roofing material
field supplied

50XP

Insulation (field
supplied)

Roofing material
field supplied

Duct work
field supplied

Cant strip
field supplied

Roofcurb*

Cant strip
field supplied

Duct work
field supplied

Roof

Roof

*Provided with roofcurb

*Provided with roofcurb

Roof Curb for Small Cabinet

Roof Curb for Large Cabinet

Note A: When unit mounting scre w is used
,
retainer bracket must also be used.

Note A: When unit mounting scre w is used
,
retainer bracket must also be used.

Supply opening
(B x C)

B Typ.
44 5/ 16"

D
CTyp.

(1126 mm)

R/A
A

Gasket around
duct

Insulated
deck pan

Short
Support
Insulated
deck pan

S/A

Gasket around
outer edge

Long
Support

Return opening
(B X C)

C00076

UNIT SIZE
50XP024-- 036
50XP042-- 060

ORDERING NUMBER
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00

A
IN. (MM)
8 (203)
14 (356)
8 (203)
14 (356)

B
IN. (MM)
11 (279)
11 (279)
16--3/16 (411)
16--3/16 (411)

C
IN. (MM)
16--1/2 (419)
16--1/2 (419)
17--3/8 (441)
17--3/8 (441)

D
IN. (MM)
28--3/4 (730)
28--3/4 (730)
40--1/4 (1022)
40--1/4 (1022)

NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.

10

50XP UNIT SUGGESTED RIGGING

1

2
(914 mm)

DETAIL A

4
A07216

Unit*
Rigging
Weight

SMALL CABINET
030
030

024

024

lb

kg

lb

345

156

349

036

036

kg

lb

kg

158

367

166

A08005

Unit*
Rigging
Weight

LARGE CABINET
048
048

042

042

lb

kg

lb

kg

060
lb

060
kg

425

193

459

208

504

229

NOTE: See dimensional drawing for corner weight distribution. Corner weights shown on drawing are based on unit---only weights and do not include packaging.

SELECTION PROCEDURE (WITH EXAMPLE)
1. Determine cooling and heating requirements at
design conditions:

4. Determine fan speed and power requirements at
design conditions.

Given:
Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . . . 15,000 Btuh
Condenser Entering Air Temperature . . . . . . . . 95°F(35°C)
Indoor--Air Temperature . . . . . . . . . . . . . 80°F (26°C) edb
67°F (19°C) ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 CFM
External Static Pressure . . . . . . . . . . . . . . . . . 0.20 IN. W.C.
Electrical Characteristics . . . . . . . . . . . . . . . . . . . 230--1--60

Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Filter Pressure
Drop Table, and the Accessory Electric Heat Pressure Drop table,
find:
External Static Pressure
0.200 IN. W.C.
Filter
0.130 IN. W.C.
Wet Coil Pressure Drop
0.032 IN. W.C.
Total Static Pressure
0.362 IN. W.C.
Enter the table for Dry Coil Air Delivery—At 0.362 IN. W.C. ESP
(external static pressure) and NOM speed pin selection, the motor
will deliver 1235 cfm.

2. Select unit based on required cooling capacity.
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F (35°C). The 036 unit at 1225 CFM and 67°F
(19°C) ewb (entering wet bulb) will provide a total capacity of
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.

5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208--1--60.

3. Select electric heat.
The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.
15,000 Btuh
= 4.4kW of heat required
3,414 Btuh/kW
Enter the Electric Heater Packages table for 208/240, single--phase,
036 unit. The 5 kW heater at 240v most closely satisfies the
heating required. To calculate kW at the 208v, multiply the heater
kW by multiplication factor 0.75 found in the Wattage
Multiplication Factors table.
5 kW x 0.75 = 3.75 kW
3.75 kW x 3414 = 12,802.50 Btuh

11

50XP

3

12

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62
(16.7)
24.0
21.9
1.7
22.9
21.4
1.9
21.8
20.8
2.2
20.5
20.2
2.4
19.2
19.4
2.7
17.8
18.5
2.9

62
(16.7)
TC
27.9
75
SHC
24.1
(23.9)
kW
2.1
TC
26.9
85
SHC
23.8
(29.4)
kW
2.3
TC
25.6
95
SHC
23.1
(35)
kW
2.6
TC
24.3
105
SHC
22.4
(40.6)
kW
2.9
TC
22.8
115
SHC
21.7
(46.1)
kW
3.2
TC
21.4
125
SHC
20.7
(51.7)
kW
3.5
See Legend and Notes on Page 15.

Temp _F (_C) Outdoor
Air Entering
Condenser

50XP030

125
(51.7)

115
(46.1)

105
(104.6)

95
(35)

85
(29.4)

75
(23.9)

Temp _F (_C)
Outdoor Air Entering
Condenser

50XP024

PERFORMANCE DATA

67
(19.4)
26.5
18.7
1.8
25.3
18.1
2.0
24.0
17.6
2.2
22.6
16.9
2.4
21.1
16.3
2.7
19.4
15.5
3.0

67
(19.4)
30.7
20.6
2.1
29.5
20.3
2.4
28.2
19.9
2.6
26.6
19.3
2.9
24.9
18.8
3.2
24.9
18.8
3.2

875/0.06
63*
(17.2)
28.6
20
2.1
27.5
19.5
2.3
26.2
19.1
2.6
24.7
18.6
2.9
23.2
18
3.2
21.4
17.3
3.5

63*
(17.2)
24.5
21.3
1.7
23.3
20.7
1.9
22.2
20.2
2.2
20.9
19.5
2.4
19.5
18.8
2.7
18.0
18.1
2.9

800/0.026

72
(22.2)
33.6
16.8
2.1
32.3
16.4
2.4
30.8
16
2.6
29.2
15.4
2.9
27.3
14.8
3.2
27.3
14.8
3.2

72
(22.2)
29.1
15.4
1.8
27.9
14.9
2.0
26.5
14.3
2.2
25.0
13.7
2.4
23.3
13.0
2.7
21.4
12.3
3.0

Evaporator Air --- CFM/BF
1000/0.07
Evaporator Air --- Ewb _F (_C)
62
63*
67
72
(16.7)
(17.2)
(19.4)
(22.2)
28.8
29.4
31.6
34.5
26
21.2
22.1
17.8
2.1
2.1
2.1
2.2
27.6
28.1
30.2
33.1
25.6
20.8
21.7
17.4
2.3
2.4
2.4
2.4
26.3
26.8
28.8
31.5
24.7
20.5
21.3
16.9
2.6
2.6
2.6
2.6
25.1
25.3
27.2
29.7
23.8
19.9
20.8
16.3
2.9
2.9
2.9
2.9
23.8
23.6
25.3
27.7
22.3
19.3
20.2
15.7
3.2
3.2
3.2
3.2
23.8
23.6
25.3
27.7
22.3
19.3
20.2
15.7
3.2
3.2
3.2
3.2

62
(16.7)
24.6
23.5
1.8
23.5
22.9
2.0
22.3
22.3
2.2
21.0
21.6
2.4
19.8
20.6
2.7
18.5
19.2
3.0

Evaporator Air --- CFM/BF
900/0.032
Evaporator Air --- Ewb _F (_C)
63*
67
72
(17.2)
(19.4)
(22.2)
25.1
27.1
29.8
22.8
19.8
16.1
1.8
1.8
1.8
23.9
25.8
28.5
22.2
19.2
15.6
2.0
2.0
2.0
22.6
24.5
27.0
21.6
18.7
15.0
2.2
2.2
2.2
21.3
23.0
25.4
20.9
18.0
14.3
2.4
2.5
2.5
19.9
21.5
23.7
20.2
17.3
13.7
2.7
2.7
2.7
18.5
19.5
21.7
19.2
16.5
12.9
3.0
3.0
3.0

62
(19.7)
29.3
27
2.1
28.3
26.5
2.4
27
26.2
2.6
25.9
24.4
2.9
24.5
23.7
3.2
24.5
23.7
3.2

62
(19.7)
25.1
25.0
1.8
23.9
24.3
2.0
22.7
23.6
2.2
21.6
22.5
2.5
20.7
21.5
2.7
19.0
19.8
3.0

50XP

67
(19.4)
27.4
20.8
1.8
26.2
20.3
2.1
24.8
19.7
2.3
23.3
19.0
2.5
21.7
18.3
2.8
19.9
17.6
3.1

63*
(17.2)
30
22.6
2.1
28.7
22.1
2.4
27.3
21.7
2.6
25.7
21.1
2.9
24
20.5
3.2
24
20.5
3.2

67
(19.4)
32.2
23.5
2.1
30.8
23.1
2.4
29.3
22.6
2.6
27.5
22.1
2.9
25.7
21.5
3.2
25.7
21.5
3.2

1125/0.08

63*
(17.2)
25.5
24.2
1.8
24.3
23.6
2.0
23.0
22.9
2.2
21.7
22.2
2.5
20.4
21.2
2.7
19.0
19.7
3.0

1000/0.04

72
(22.2)
35.2
18.7
2.2
33.7
18.3
2.4
32
17.8
2.6
30.1
17.2
2.9
28.1
16.6
3.2
28.1
16.6
3.2

72
(22.2)
30.4
16.7
1.9
28.9
16.2
2.1
27.4
15.6
2.3
25.7
14.9
2.5
23.6
14.1
2.8
21.9
13.5
3.1

13

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62
(16.7)
36.2
33.2
2.7
34.6
32.4
2.9
33.0
31.6
3.2
31.3
30.6
3.6
29.6
29.3
4.0
27.8
27.5
4.4

62
(16.7)
TC
39.6
75
SHC
33.5
(23.9)
kW
3.0
TC
37.9
85
SHC
32.8
(29.4)
kW
3.3
TC
36.2
95
SHC
32.0
(35)
kW
3.7
TC
34.2
105
SHC
31.0
(104.6)
kW
4.1
TC
32.1
115
SHC
30.0
(46.1)
kW
4.5
TC
29.8
125
SHC
28.6
(51.7)
kW
4.9
See Legend and Notes on Page 15.

Temp _F (_C) Outdoor
Air Entering
Condenser

50XP042

125
(51.7)

115
(46.1)

105
(104.6)

95
(35)

85
(29.4)

75
(23.9)

Temp _F (_C) Outdoor
Air Entering
Condenser

50XP036
67
(19.4)
39.7
27.8
2.7
37.9
27.1
3.0
36.0
26.4
3.3
34.0
25.6
3.6
31.8
24.8
4.0
29.4
23.9
4.4

63*
(17.2)
40.4
27.6
3.0
38.7
26.9
3.3
36.8
26.1
3.7
34.8
25.2
4.1
32.6
24.3
4.5
30.1
23.2
4.9

67
(19.4)
43.4
28.6
3.0
41.5
27.8
3.4
39.6
27.0
3.7
37.4
26.2
4.1
35.0
25.2
4.5
32.3
24.2
4.9

1225/0.06

63*
(17.2)
36.8
26.7
2.7
35.1
26.0
2.9
33.4
25.3
3.2
31.5
24.5
3.6
29.4
23.7
4.0
27.2
22.8
4.3

1100/0.06

PERFORMANCE DATA (CONT)

72
(22.2)
47.6
23.4
3.1
45.5
22.7
3.4
43.4
21.9
3.8
41.0
21.1
4.1
38.4
20.2
4.5
35.3
19.1
5.0

72
(22.2)
43.8
22.3
2.7
41.8
21.6
3.0
39.7
20.9
3.3
37.5
20.1
3.6
35.0
19.3
4.0
32.4
18.4
4.4

Evaporator Air --- CFM/BF
1400/0.07
Evaporator Air --- Ewb _F (_C)
62
63*
67
72
(16.7)
(17.2)
(19.4)
(22.2)
40.5
41.2
44.2
48.4
35.4
29.0
30.0
24.3
3.0
3.0
3.0
3.1
38.7
39.4
42.3
46.3
34.6
28.2
29.2
23.6
3.3
3.3
3.4
3.4
36.9
37.5
40.3
44.1
33.8
27.4
28.4
22.8
3.7
3.7
3.7
3.8
34.9
35.4
38.0
41.6
32.7
26.5
27.6
22.0
4.1
4.1
4.1
4.1
32.8
33.1
35.5
38.9
31.4
25.6
26.6
21.0
4.5
4.5
4.5
4.6
30.6
30.5
32.7
35.7
29.6
24.5
25.5
20.0
4.9
4.9
4.9
5.0

Evaporator Air --- CFM/BF
1225/0.07
Evaporator Air --- Ewb _F (_C)
62
63*
67
72
(16.7)
(17.2)
(19.4)
(22.2)
36.9
37.4
40.3
44.4
34.7
27.9
29.0
23.1
2.7
2.7
2.7
2.8
35.3
35.6
38.4
42.4
34.0
27.1
28.3
22.4
3.0
3.0
3.0
3.0
33.7
33.8
36.5
40.2
32.9
26.4
27.6
21.7
3.3
3.3
3.3
3.4
32.1
31.9
34.3
37.9
31.5
25.7
26.8
20.9
3.6
3.6
3.7
3.7
30.4
29.8
32.1
35.4
30.0
24.8
26.0
20.0
4.0
4.0
4.0
4.0
28.4
27.5
29.7
32.7
28.2
23.8
25.0
19.1
4.4
4.4
4.4
4.4

50XP

62
(19.7)
41.5
37.9
3.0
39.7
37.0
3.3
37.8
35.9
3.7
36.0
34.3
4.1
34.0
32.8
4.5
31.7
30.6
4.9

62
(19.7)
37.9
36.9
2.8
36.4
35.6
3.1
34.8
34.4
3.4
33.1
32.8
3.8
31.3
31.0
4.1
29.3
29.0
4.5

67
(19.4)
41.0
30.9
2.8
39.1
30.2
3.1
37.0
29.4
3.4
34.9
28.6
3.8
32.6
27.7
4.1
30.1
26.7
4.5

63*
(17.2)
42.1
30.8
3.0
40.2
30.0
3.3
38.2
29.1
3.7
36.0
28.3
4.1
33.7
27.3
4.5
31.0
26.1
4.9

67
(19.4)
45.1
31.9
3.0
43.2
31.1
3.4
41.0
30.3
3.7
38.7
29.4
4.1
36.1
28.5
4.5
33.2
27.3
4.9

1575/0.08

63*
(17.2)
38.1
29.6
2.8
36.3
28.9
3.1
34.4
28.1
3.4
32.4
27.3
3.7
30.3
26.4
4.1
28.0
25.4
4.5

1400/0.08

72
(22.2)
49.4
25.6
3.1
47.2
24.8
3.4
44.9
24.0
3.8
42.3
23.2
4.1
39.5
22.2
4.6
36.2
21.1
5.0

72
(22.2)
45.1
24.2
2.9
43.1
23.6
3.2
40.8
22.8
3.5
38.4
22.0
3.8
35.8
21.1
4.2
33.0
20.2
4.5

14

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

62
(16.7)
45.0
39.3
3.4
42.8
38.2
3.7
40.6
36.9
4.1
38.2
35.7
4.6
35.7
34.4
5.0
33.4
32.1
5.6

62
(16.7)
TC
57.2
75
SHC
49.4
(23.9)
kW
4.1
TC
54.7
85
SHC
48.2
(29.4)
kW
4.5
TC
52.2
95
SHC
47.0
(35)
kW
5.0
TC
49.4
105
SHC
45.7
(104.6)
kW
5.5
TC
46.5
115
SHC
44.3
(46.1)
kW
6.1
TC
43.3
125
SHC
42.8
(51.7)
kW
6.7
See Legend and Notes on Page 15.

Temp _F (_C) Outdoor
Air Entering
Condenser

50XP060

125
(51.7)

115
(46.1)

105
(104.6)

95
(35)

85
(29.4)

75
(23.9)

Temp _F (_C) Outdoor
Air Entering
Condenser

50XP048
67
(19.4)
49.6
33.4
3.4
47.2
32.3
3.8
44.7
31.2
4.2
42.1
30.1
4.6
39.3
28.9
5.1
36.2
27.6
5.6

63*
(17.2)
58.2
47.9
4.1
55.6
46.7
4.5
53.0
45.4
5.0
50.2
44.1
5.6
47.2
42.7
6.2
43.9
41.2
6.8

67
(19.4)
62.4
41.6
4.2
59.7
40.4
4.6
56.9
39.2
5.1
53.8
37.9
5.6
50.5
36.4
6.2
46.7
34.9
6.8

1500/0.04

63*
(17.2)
45.8
32.0
3.4
43.6
30.9
3.7
41.3
29.8
4.1
38.9
28.7
4.6
36.3
27.5
5.0
33.4
26.2
5.6

1260/0.06

PERFORMANCE DATA (CONT)

72
(22.2)
68.1
33.8
4.2
65.2
32.6
4.7
62.0
31.4
5.2
58.7
30.1
5.7
55.0
28.7
6.3
52.2
27.8
6.8

72
(22.2)
54.7
27.2
3.4
52.1
26.2
3.8
49.4
25.2
4.2
46.4
24.0
4.6
43.3
22.9
5.1
39.4
21.5
5.7

Evaporator Air --- CFM/BF
1750/0.07
Evaporator Air --- Ewb _F (_C)
62
63*
67
72
(16.7)
(17.2)
(19.4)
(22.2)
58.8
59.7
64.0
69.8
53.6
51.8
44.5
35.4
4.2
4.3
4.3
4.4
56.2
57.0
61.1
66.6
52.4
50.5
43.2
34.2
4.7
4.7
4.8
4.9
53.5
54.3
58.0
63.2
51.1
49.2
41.9
32.9
5.1
5.2
5.3
5.3
50.7
51.4
54.8
59.6
49.8
47.9
40.6
31.6
5.7
5.7
5.8
5.9
48.1
48.3
51.3
56.8
48.1
46.6
39.2
30.6
6.2
6.3
6.4
6.4
45.2
45.1
47.4
52.5
45.2
45.1
37.6
28.9
6.8
6.9
7.0
7.0

Evaporator Air --- CFM/BF
1400/0.06
Evaporator Air --- Ewb _F (_C)
62
63*
67
72
(16.7)
(17.2)
(19.4)
(22.2)
46.7
47.3
51.2
56.3
42.6
34.3
35.8
28.9
3.4
3.4
3.4
3.5
44.3
44.9
48.6
53.5
41.3
33.2
34.7
27.7
3.7
3.7
3.8
3.8
41.8
42.4
46.0
50.7
39.9
32.0
33.6
26.7
4.1
4.1
4.2
4.2
39.6
39.8
43.1
47.6
38.3
30.7
32.3
25.5
4.6
4.6
4.6
4.7
38.2
37.1
40.1
44.2
35.7
29.5
31.0
24.3
5.1
5.0
5.1
5.1
34.6
34.1
36.9
40.5
33.8
28.2
29.7
22.9
5.6
5.6
5.6
5.6

62
(19.7)
60.0
57.6
4.4
57.4
56.3
4.8
55.0
55.0
5.2
52.5
52.5
5.8
49.7
49.7
6.4
46.4
46.4
7.0

62
(19.7)
48.1
45.8
3.4
45.6
44.3
3.8
44.2
43.0
4.2
41.5
40.0
4.6
38.7
38.2
5.1
36.1
35.6
5.6

50XP

67
(19.4)
52.5
38.4
3.4
49.9
37.3
3.8
47.0
36.1
4.2
44.0
34.8
4.6
40.8
33.5
5.1
37.5
31.9
5.6

63*
(17.2)
60.8
55.4
4.4
58.1
54.2
4.9
55.3
52.9
5.3
52.4
51.6
5.8
49.7
49.7
6.4
46.4
46.4
7.0

67
(19.4)
64.9
47.1
4.5
61.9
45.8
5.0
58.7
44.5
5.5
55.4
43.2
6.0
51.8
41.8
6.6
47.9
40.2
7.2

2000/0.01

63*
(17.2)
48.7
36.8
3.4
46.1
35.5
3.8
43.7
34.6
4.1
40.8
33.2
4.6
37.9
31.8
5.1
34.8
30.2
5.6

1600/0.08

72
(22.2)
70.8
36.8
4.6
67.4
35.6
5.0
64.1
34.4
5.5
60.2
33.0
6.1
57.0
31.7
6.6
52.2
29.7
7.2

72
(22.2)
57.8
30.6
3.5
54.8
29.4
3.8
51.8
28.3
4.2
48.5
27.0
4.7
45.0
25.8
5.1
41.2
24.4
5.6

15

=

1.10 x cfm

Sensible capacity (Btuh)

air leaving evaporator coil (hlwb)

Wet---bulb temperature corresponding to enthalpy

= tedb ---

hlwb

= hewb --4.5 x cfm

total capacity (Btuh)

50XP

Where: hewb = Enthalpy of air entering evaporator coil
4. The SHC is based on 805 F (26.6_C) edb temperature of air entering evaporator coil. Below 80_F (26.6_C) edb, subtract (corr factor x cfm) from SHC.
Above 80_F (26.6_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it.

tlwb

tldb

COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator ---fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

* At 75°F (24°C) entering dry bulb---Tennessee Valley Authority (TVA) rating conditions; all others at 80°F (27°C) dry bulb.
LEGEND
BF— Bypass Factor
edb— Entering Dry ---Bulb
Ewb— Entering Wet---Bulb
kW — Total Unit Power Input
SHC— Sensible Heat Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (net)
rh—Relative Humidity

PERFORMANCE DATA (CONT)

PERFORMANCE DATA (CONT)
Economizer 1--in. Filter Pressure Drop (IN. W.C.)
UNIT50XP
024-- 036
042-- 060

PRESSURE DROP
0.20
0.25

Multiplication Factors
HEATER kW RATING

VOLTAGE DISTRIBUTION V/3/60
200
208
230
240

240

MULTIPLICATION FACTOR
0.69
0.75
0.92
1.00

50XP

Filter Pressure Drop Table (IN. W.C.)
FILTER SIZE
in. (mm)
20X20X1
(508X508X25)
20X24X1
(508X610x25)
24X30X1
(610X762x25)

500

600

700

800

900

1000

1100

1200

1300

CFM
1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

0.05

0.07

0.08

0.10

0.12

0.13

0.14

0.15

—

—

—

—

—

—

—

—

—

—

—

—

—

—

0.09

0.10

0.11

0.13

0.14

0.15

0.16

—

—

—

—

—

—

—

—

—

—

—

—

—

—

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.18

—

Electric Heat Pressure Drop Tables (IN. W.C.)
Small Cabinet: 024--036
CFM

STATIC

500
0.00
0.00
0.00
0.00

5 kW
7.5 kW
10 kW
15 kW

600
0.00
0.00
0.00
0.00

700
0.00
0.00
0.00
0.00

800
0.00
0.00
0.00
0.02

900
0.00
0.00
0.00
0.04

1000
0.00
0.00
0.02
0.06

1100
0.00
0.02
0.04
0.08

1200
0.00
0.03
0.06
0.10

1300
0.02
0.05
0.07
0.12

1400
0.04
0.07
0.09
0.14

1500
0.06
0.08
0.10
0.16

1600
0.07
0.09
0.11
0.18

Large Cabinet: 042--060
STATIC

1100
0.00
0.00
0.00
0.00
0.02

5 kW
7.5 kW
10 kW
15 kW
20 kW

1200
0.00
0.00
0.00
0.02
0.03

1300
0.00
0.01
0.01
0.03
0.04

1400
0.01
0.02
0.02
0.04
0.05

1500
0.02
0.03
0.03
0.05
0.06

1600
0.03
0.04
0.04
0.06
0.07

CFM
1800
0.05
0.06
0.06
0.08
0.09

1700
0.04
0.05
0.05
0.07
0.08

1900
0.06
0.07
0.07
0.09
0.10

2000
0.07
0.08
0.08
0.10
0.11

2100
0.08
0.09
0.09
0.11
0.12

2200
0.09
0.10
0.10
0.12
0.13

2300
0.10
0.11
0.11
0.13
0.14

2400
0.11
0.12
0.12
0.14
0.15

2500
0.12
0.13
0.13
0.15
0.16

ECM Dry Coil Airflow--Small Cabinet
CFM ADJUST PIN SELECT
EXTERNAL STATIC
PRESSURE RANGE
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY

UNIT
SIZE
024
030
036

LO PIN

NOM PIN

HI PIN

0.0-- 0.39

0.4-- 0.69

0.7-- 1.0

0.0-- 0.39

0.4-- 0.69

0.7-- 1.0

0.0-- 0.39

0.4-- 0.69

0.7-- 1.0

800
715
1010
890
1110
990

725
670
920
845
1025
960

--825
795
970
910

885
715
1105
890
1235
990

805
695
1030
865
1175
975

730
645
930
825
1115
940

990
795
1255
1010
1400
1125

930
775
1160
980
1355
1110

855
745
1050
925
1280
1085

ECM Dry Coil Airflow--Large Cabinet
CFM ADJUST PIN SELECT
EXTERNAL STATIC PRESSURE RANGE
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY

UNIT SIZE
042
048
060

LO PIN
0.1-- 1.0
1100
980
1260
1120
1575
1400

NOM PIN
0.1-- 1.0
1225
980
1400
1120
1750
1400

NOM PIN
0.1-- 1.0
1410
1125
1610
1290
2010
1610

Wet Coil Pressure Drop (IN. W.C.)
Unit
Size
024
030
036
042
048
060

600
0.005

700
0.007
0.007

800
0.010
0.010

900
0.012
0.012
0.019

1000
0.015
0.015
0.023
0.014

Standard CFM (S.C.F.M)
1300
1400
1500

1100

1200

0.018
0.027
0.017

0.021
0.032
0.020
0.027

0.024
0.037
0.024
0.032

16

0.042
0.027
0.036

0.047
0.031
0.041
0.029

1600

1700

1800

1900

2000

2100

0.035
0.046
0.032

0.039
0.052
0.036

0.043
0.057
0.040

0.063
0.045

0.068
0.049

0.053

TYPICAL PIPING AND WIRING

ROOF-MOUNTING
CURB

ROOF

RETURN-AIR
FLEXIBLE DUCT

50XP

SUPPLY-AIR
FLEXIBLE DUCT

CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)

CEILING

C00023

INDOOR
THERMOSTAT

RETURN
AIR

FROM
POWER
SOURCE

TOP COVER

DISCONNECT
PER NEC*

*NEC - NATIONAL ELECTRICAL CODE
C00063

17

APPLICATION DATA
Condensate trap — A 2--in. (51 mm) condensate trap must be
field supplied.
1” (25 mm) MIN.
TRAP
OUTLET
2” (51 mm) MIN.

50XP

A08001

Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Removal
of the inserts is similar to removing an electrical knock--out. Leave
on duct covers to seal the horizontal discharge openings in the unit.
Units installed in horizontal discharge orientation do not require
duct covers.

Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton for standard cooling modes. Airflow can be lower in
certain modes when humidity removal is an issue.
Minimum cooling operating outdoor air temperature — All
standard units have a minimum outdoor operating temperature of
55_F (13_C). With accessory low ambient temperature kit, units
can operate at temperatures down to 0_F (--17_C).
Maximum cooling operating outdoor air temperature —
Maximum outdoor operating air temperature is 125_F (52_C).

18

ELECTRICAL DATA
NOMINAL
V--- PH --- HZ

VOLTAGE
RANGE

COMPRESSOR

OFM

IFM

MIN

MAX

RLA

LRA

FLA

FLA

50XP-024

208/230-1-60

187

253

13.5

61.0

0.8

4.3

50XP-030

208/230-1-60

187

253

15.9

73.0

0.8

4.3

208/230-1-60

187

253

16.9

83.0

0.8

6.8

208/230-3-60

187

253

12.2

77.0

0.8

6.8

208/230-1-60

187

253

22.4

105.0

0.8

6.8

208/230-3-60

187

253

15.4

88.0

0.8

6.8

208/230-1-60

187

253

21.3

109.0

1.6

6.8

208/230-3-60

187

253

14.7

91.0

1.6

6.8

208/230-1-60

187

253

27.0

145.0

1.6

9.1

208/230-3-60

187

253

19.2

137.0

1.6

9.1

50XP-036

50XP-042

50XP-048

50XP-060

ELECTRIC HEAT
NOMINAL
KW

FLA

-/3.8/5
5.4/7.2
7.5/10
-/3.8/5
5.4/7.2
7.5/10
11.3/15
-/3.8/5
5.4/7.2
7.5/10
11.3/15
-/5
10
15
-/3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/3.8/5
7.5/10
11.3/15
15/20
-/3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/3.8/5
7.5/10
11.3/15
15/20
-/3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/3.8/5
7.5/10
11.3/15
15/20

-/18.1/20.8
26/30
36.1/41.7
-/18.1/20.8
26/30
36.1/41.7
54.2/62.5
-/18.1/20.8
26/30
36.1/41.7
54.2/62.5
-/10.4/12
20.8/24.1
31.3/36.1
-/18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12
20.8/24.1
31.3/36.1
41.6/48
-/18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12
20.8/24.1
31.3/36.1
41.6/48
-/18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/10.4/12
20.8/24.1
31.3/36.1
41.6/48

POWER SUPPLY
MAX
FUSE or
MCA
CKT BKR
22.0/22.0
30/30
27.9/31.4
30/35
37.9/42.9
40/45
50.5/57.5
60/60
23.6/23.6
30/30
27.9/31.4
30/35
37.9/42.9
40/45
50.5/57.5
60/60
73.1/83.5
26.9/26.9
35/35
31.1/34.5
35/35
41.0/46.0
45/50
53.6/60.6
--76.2/86.6
--23.0/23.0
30/30
23.0/23.5
30/30
34.6/38.6
35/35
47.6/53.6
50/60
30.9/30.9
45/45
31.1/34.5
45/45
41.0/46.0
45/50
53.6/60.6
--76.2/86.6
--98.8/112.7
--27.0/27.0
35/35
27.0/27.0
35/35
34.6/38.6
35/35
47.6/53.6
50/60
60.5/68.5
--33.9/33.9
45/45
33.9/34.5
45/45
41.0/46.0
45/50
53.6/60.6
--76.2/86.6
--98.8/112.7
--26.7/26.7
35/35
26.7/26.7
35/35
34.6/38.6
35/35
47.6/53.6
50/60
60.5/68.5
--44.3/44.3
60/60
44.3/44.3
60/60
44.3/48.9
60/60
56.5/63.5
--79.1/89.5
--101.6/115.5
--33.0/33.0
40/40
33.0/33.0
40/40
37.4/41.4
40/45
50.5/56.5
60/60
63.3/71.3
---

460-3-60.
452 v
464 v
455 v
452
1371
*Heater capacity (kW) based on heater voltage of 208v, 240v, &
480v. If power distribution voltage to unit varies from rated
heater voltage, heater kW will vary accordingly.

457
457 452
464 457
457 455

5
7
2
7
7
457
1.53

19

464

455

MOCP
----------------80/90
------60/70
80/90
--------------60/70
80/90
100/125
--------70/70
------60/70
80/90
100/125
--------70/70
------60/70
80/90
100/125
--------70/80

50XP

UNIT

50XP

TYPICAL WIRING SCHEMATIC 208/230--1--60

A08460

20

50XP

TYPICAL WIRING SCHEMATIC 208/230--3--60

A08461

21

CONTROLS
Operating sequence
Heating — If accessory electric heaters are installed, on a call for
heat, circuit R--W is made through the thermostat contacts. Circuit
R--G is made which energizes the IFM. If the heaters are staged,
then the thermostat closes a second set of contacts (W2) when
second stage is required. When thermostat is satisfied, contacts
open, deenergizing the heater relay. After a preselected delay, the
IFM shuts off. If the thermostat fan selector switch is in the “ON”
position, the IFM will run continuously at speed selected on Easy
Select Board.
NOTE: On units with a Time Guard® II device: Once the
compressor has started and then stopped, it cannot be restarted
again until 5 minutes have elapsed.
The indoor blower operation with a call for fan operation (G) in
cooling mode will perform by the on/off delay profile selected at
start up on the Easy Select Board.

50XP

Cooling — When the system thermostat calls for cooling, 24 V is
supplied to the “Y” and “G” terminals of the thermostat. This
completes the circuit to the contactor coil (C) and indoor fan
board. The normally open contacts of C close and complete the
circuit to compressor motor (COMP) and to outdoor (condenser)
fan motor (OFM). Both motors start instantly. The IFM starts
according to the selection pin set--up on the Easy Select Board.
On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y” and “G” terminals (provided the fan switch is in
the “AUTO” position) de--energizing the compressor contactor and
opening the contacts supplying power to compressor/OFM. After a
preselected delay, the IFM shuts off. If the thermostat fan selector
switch is in the “ON” position, the IFM will run continuously at
speed selected on Easy Select Board

22

Packaged Electric Cooling Unit
Constant Volume Application
HVAC Guide Specifications
Size Range:
2 to 5 Tons, Nominal Cooling
Model Number: 50XP
Part 1 — General
SYSTEM DESCRIPTION
Outdoor rooftop mounted or ground mounted, electric cooling
unit utilizing a hermetic compressor for cooling duty and
optional electric heating. Unit shall discharge supply air
vertically or horizontally as shown on contract drawings.
Condenser fan/coil section shall have a draw--thru design with
vertical discharge for minimum sound levels.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
210/240 and 270.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard.
D. Unit shall be UL listed and c--UL certified as a total
package for safety requirements.
E. Roof curb shall be designed to conform to NRCA
Standards.
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled per manufacturer’s
recommendations.
Part 2 — Products
EQUIPMENT
A. General:
Factory--assembled, single--piece, cooling unit. Contained
within the enclosure shall be all factory wiring, piping,
controls, refrigerant charge with R--410A refrigerant, and
special features required prior to field start--up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated,
zinc--coated, pre--painted steel capable of with--standing 500
hours in salt spray.
2. Normal service shall be through a single removable cabinet
panel.
3. The unit shall be constructed on a rust proof unit base that
has an externally trapped, integrated sloped drain pan.
4. Evaporator fan compartment top surface shall be insulated
with a minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive
and mechanical means. The evaporator wall sections will be
insulated with a minimum semi--rigid foil--faced board capable of being wiped clean. Aluminum foil--faced fiberglass
insulation shall be used in the entire indoor air cavity
section.
5. Unit shall have a field--supplied condensate trap.

C. Fans:
1. The evaporator fan shall be direct--drive variable speed
motor and control, as shown on equipment drawings.
2. Fan wheel shall be made from steel, be double--inlet type
with forward curved blades with corrosion resistant finish.
Fan wheel shall be dynamically balanced.
3. Condenser fan shall be direct drive propeller type with aluminum blades riveted to corrosion resistant steel spiders, be
dynamically balanced, and discharge air vertically.
D. Compressor:
1. Fully hermetic compressors with factory--installed vibration
isolation.
2. Scroll compressors shall be standard on all units.
E. Coils:
Evaporator and condenser coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed. (Copper/copper and vinyl--coated construction
available as option). Tube sheet openings shall be belled to
prevent tube wear.
F. Refrigerant Components:
Refrigerant expansion device shall be of the TXV
(thermostatic expansion valve) type.
G. Filters:
Filter section shall consist of field--installed, throwaway, 1--in.
(25 mm) thick fiberglass filters of commercially available
sizes.
H. Controls and Safeties:
1. Unit controls shall be complete with a self--contained low
voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
3. Unit shall provide High and Low/Loss--of--Charge Pressure
Safety Protection.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F
(51_C) ambient outdoor temperature,exceeding maximum
load criteria of ARI Standard 210.
2. Compressor with standard controls shall be capable of operation down to 55_F (13_C) ambient outdoor temperature.
3. Indoor Fan on/off delay profile is selected (for cooling) on
the Easy Select board.
J. Electrical Requirements:
All unit power wiring shall enter the unit cabinet at a single
location.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
2. All fan motors shall have permanently lubricated bearings,
and inherent, automatic reset, thermal overload protection.
3. Condenser fan motor shall be totally enclosed.
L. Grille:
1. Louvered Grille:
Louvered grille shall be standard on all units.

23

50XP

GUIDE SPECIFICATIONS

50XP

GUIDE SPECIFICATIONS (CONT)

6. Low Ambient Package:
Shall consist of a solid--state control and condenser coil
temperature sensor for controlling condenser--fan motor operation, which shall allow unit to operate down to 0_F
(--18_C) outdoor ambient temperature when properly
installed.
7. Filter Rack Kit:
Shall provide filter mounting for downflow or horizontal
applications.
8. Square--To--Round Duct Transitions (024--048):
Shall have the ability to convert the supply and return openings from rectangular to round. (024--048 only)
9. Compressor Protection:
Solid--state control shall protect compressor by preventing
“short cycling.“
10. Crankcase Heater:
Shall provide anti--floodback protection for low--load cooling applications.
11. Electric Heaters:
a. Electric heater shall be availabel as a field--installed
option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single point
power connection capability.
12. Compressor Start Kit (single phase units only):
Shall provide additional starting torque for single--phase
compressors.

M. Special Features:
1. Coil Options:
Shall include factory--installed optional tin--plated indoor,
copper/copper and vinyl--coated refrigerant coils.
2. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
3. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
4. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
5. Thermostat:
To provide for one--stage heating and cooling in addition
manual or automatic changeover and indoor fan control.

Copyright 2008 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 09/08

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

24

Catalog No: 50XP---05PD
Replaces: 50XP--- 4PD



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2008:11:17 11:36:55-05:00
Create Date                     : 2008:11:17 11:31:53-05:00
Metadata Date                   : 2008:11:17 11:36:55-05:00
Format                          : application/pdf
Title                           : 50XP-05PD
Creator                         : bact2wt
Document ID                     : uuid:34f4a40f-cff6-4de1-a5fc-b80e39b4992d
Instance ID                     : uuid:db6ae8f6-091f-4da2-9c7e-74930df54500
Page Count                      : 24
Author                          : bact2wt
EXIF Metadata provided by EXIF.tools

Navigation menu