ARCHITECTS AND ENGINEERS’ MANUAL
PREMIER SERIES 52P
COMFORT SERIES 52C
PACKAGED TERMINAL
AIR CONDITIONERS
AND HEAT PUMPS

CONTENTS
Page

Page

APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4

Seamless Basepan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Drain Valve. . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Removal System. . . . . . . . . . . . . . . . . . . . 11
Heat Pumps Pay Their Own Way. . . . . . . . . . . . . . . . . 12
Heat Pump Energy Savings . . . . . . . . . . . . . . . . . . . . . 13
ORDERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Product Catalog Number . . . . . . . . . . . . . . . . . . . . . . . 14
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . 15
FIELD-INSTALLED ACCESSORIES . . . . . . 16-26

New Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Retrofit/Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Carrier Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Application Considerations . . . . . . . . . . . . . . . . . . . . . . 4
PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . 5
PRODUCT FEATURES AND BENEFITS . . . . 6-13
Quiet Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Most Efficient Performance . . . . . . . . . . . . . . . . . . . . . . 6
Efficient Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
No-Rust Weather Last™ Wall Sleeve and
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Removable Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . 7
Anti-Theft Knobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Two-Piece Lifetime Indoor Filter . . . . . . . . . . . . . . . . . . 8
Washable Vent Air Filter . . . . . . . . . . . . . . . . . . . . . . . . 8
Bi-Directional Discharge Grille . . . . . . . . . . . . . . . . . . . 8
Power Cord for 265-V Units . . . . . . . . . . . . . . . . . . . . . 9
Power Cord Protection for 230/208-V Units . . . . . . . . . 9
Bi-Molded Condenser Shroud . . . . . . . . . . . . . . . . . . . . 9
Snow Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Easy Access to Chassis. . . . . . . . . . . . . . . . . . . . . . . . . 10
Hidden Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Enhanced Copper Tubing . . . . . . . . . . . . . . . . . . . . . . . 11

DIMENSION DRAWINGS AND
INSTALLATION DATA — NEW
CONSTRUCTION. . . . . . . . . . . . . . . . . . . . . . . . . 27-33
PRODUCT DATA . . . . . . . . . . . . . . . . . . . . . . . . . 34-41
EXPANDED RATINGS DATA. . . . . . . . . . . . . . .42,43
SOUND DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . 45-50
52PQ and 52CQ . . . . . . . . . . . . . . . . . . . . . . . . . . . .45,46
52PE and 52CE . . . . . . . . . . . . . . . . . . . . . . . . . . . .47,48
Energy Management/Front Desk Control . . . . . . . . . . 49
Single Thermostat/Multiple PTAC Units . . . . . . . . . . . 50
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . 51-53
TYPICAL WARRANTY . . . . . . . . . . . . . . . . . . . .54,55
ACCESSORY LIST . . . . . . . . . . . . . . . . . . . . . . . . . . 56

For more information available on the internet, see the www.carrier.com or www.lodgingAC.com web sites.

December 2004

Copyright  Carrier Corporation

Cat. No. 592-085

Valued Carrier Customer,
Carrier’s Architects and Engineer’s manual has been specifically developed to make your
product and accessory selection easier and faster. This manual will help you customize
your application to ensure the greatest comfort for your guests and the highest reliability
and lowest costs for you.
Enjoy the ultimate in comfort, humidity control, and energy savings with Carrier’s complete line of Packaged Terminal Air Conditioning (PTAC) products. Choose from either
the Premier series (52P) which is Carrier's most energy efficient PTAC unit ever, or the
Comfort series (52C) for mid-range energy efficiency and outstanding value.
The Premier and Comfort series PTAC lines have many common features and benefits.
The 52P and 52C units are both built on the same platform with common components and
airflow systems to ensure the highest quality product for your money. The most significant
difference between the 52P and 52C products is the refrigerant system. The Premier refrigerant system utilizes Carrier's highest efficiency compressors and coil design to achieve
maximum energy efficiency. The Comfort refrigerant system uses our standard efficiency
compressors and coils to attain competitive efficiency levels which exceed the industry
standard ARI minimum-efficiency levels.
It’s your choice. Choose the Premier series and start recovering your investment immediately through energy savings, or choose our Comfort series and enjoy years of economical,
trouble-free operation and comfort.
Thank you for choosing Carrier and investing in the highest quality air conditioning and
heating system ever.
Best regards,
Lodging Products Group

2

APPLICATIONS
Whether you are designing a new structure or replacing packaged terminal air conditioning units in an
existing building, Carrier will meet your needs.
• Hotels and motels
• Nursing homes and assisted living care centers
• Offices
• Apartments
• Single-family dwellings
• Home conversions and residential add-ons

Lower Operating Costs And Reliable Comfort
For The Occupant
• Heat pump models offer substantial savings over
models with conventional electric resistance heaters
• Individual units allow tenants to choose the degree
of comfort and operating economy.
• Rapid servicing reduces downtime: complete chassis can be replaced in minutes without disrupting
other occupants.
• Each unit operates independently of other units in
the building. No dependency by building on central
HVAC system.

NEW CONSTRUCTION
The Carrier 52P and 52C Packaged Terminal Air Conditioning (PTAC) unit is designed to meet the needs of
the architect, engineer, and contractor. For unit installation, Carrier’s expert support network will assist in
all applicable aspects of the construction project, from
preparing a budget to start-up.
ADVANTAGES FOR NEW CONSTRUCTION
Design Flexibility For The Architect/Engineer
• Super-quiet performance, indoors and out
• No bulky duct system
• No separate equipment room
• No water towers or additional cooling equipment
• No complex match-up of different HVAC
components
• Less sensitivity to building orientation (sun, wind,
shade)
• Optional architectural grille to permit custom exterior appearance
Initial Cost Savings For The Building Owner
• No expensive component HVAC system purchase
• No equipment room or maintenance engineering
staff
• Two-part delivery to minimize on-site damage
• Weather-protected wall sleeve that goes in place
during construction; chassis that slides in place after
construction
• No seasonal changeover required for cooling or
heating — units are self-contained comfort systems

RETROFIT/REPLACEMENT
If you are replacing a unit in an existing wall sleeve,
your options include:
• Replace the existing wall sleeve with a Carrier
Weather Last™ sleeve. See accessory sleeve section for selecting the correct sleeve for your application. Note, in most cases, when replacing the wall
sleeve, the exterior grille must also be replaced.
• Use an existing sleeve and exterior grille. The
Carrier 52P and 52C series PTAC will fit into most
major competitors wall sleeves/grilles, including
GE, Amana, Trane, Bryant, Carrier 52S and Carrier
52B, and NO accessory retrofit kit is required.
Carrier units will also retrofit into Friedrich T series
and ZoneAire wall sleeves, with a required wall
sleeve extension (see accessory Friedrich Retrofit
Wall Sleeve Adapter).
IMPORTANT: All other sleeve or exterior grille
retrofit applications need prior approval from
Carrier. Please contact your Carrier representative
for assistance.

CARRIER WARRANTY
Carrier’s five-year warranty is the most comprehensive in the industry. Carrier provides:
• Full coverage for parts and labor for first year.
• Four additional years of full coverage on sealed
refrigeration systems.
• Limited second through fifth year coverage on nonrefrigeration system parts.

3

APPLICATIONS (cont)
APPLICATION
CONSIDERATIONS

Oversizing
If a PTAC unit is oversized (cooling capacity is greater
than required capacity for the specific application), the
unit will cool the space down to the desired temperature too quickly.
The unit will cycle on and off, however, dehumidification only takes place when the unit is operating. The
result of this type of application in a hot and/or humid
climate would be a cool, yet excessively humid, space.

Installation instructions are shipped with all PTAC
units. It is important that air conditioning systems be
properly sized and installed for each application in
order to achieve the desired temperature and humidity
levels within the space to be conditioned. It is strongly
recommended that a professional engineer match the
PTAC units with the building structure and climate.
The following application considerations are all
important in choosing the proper PTAC system for the
building structure.

Air Infiltration
Excessive air infiltration can intensify problems associated with undersizing or oversizing a PTAC unit.
This can be the cause of insufficient cooling, dehumidification, or heating. Sources of air infiltration include
vents, gaps around windows and doors, and improperly sealed floors, ceilings or wall joints.

Undersizing
If a PTAC unit is undersized (cooling capacity is less
than required capacity for an application), the unit will
not be able to cool the space down to the desired temperature during very hot days. The result could be
warm and humid or warm and dry conditioned space.

4

PRODUCT OVERVIEW (52P AND 52C)
This section summarizes product features covered in
detail in later sections of this manual:
2 AIR
FILTERS

2-WAY
DISCHARGE
GRILLE

WIRE SCREEN

FRESH AIR
CONTROL
ARM

THERMOSTAT WITH
TEMPERATURE
LIMITER

BI-MOLDED
CONDENSER
SHROUD

MODE
SELECTION
SWITCH

COPPER TUBE
ALUMINUM
FIN COILS

ROTARY
COMPRESSORS

TEST
ING

DO

1.PRE
2.PLU SS RESE
G
RECE INTO T BUTT
3.PRE PTAC POWE
ON.
R
LE.
SHOUSS TEST
4. PRES LD
BUTT
LIGHT
ON
FOR S RESE .
UNIT
T BUTT
NOT USE.
USE
ON
AGAIN
IS TEST

ABOV
E FAILS

LOUVERED
FRONT
PANEL

CONTROL
DOOR

ACCESS TO ELECTRICAL
INDOOR COMPONENTS THROUGH
BASEPAN FOR
CONTROL BOX DOOR
COIL
CONDENSATE
REMOVAL
PLUG TEST/
RESET BUTTONS

WALL
SLEEVE

Polymer, Metal or Extended Wall Sleeve — Designed for rugged duty, acoustic absorption, and attractive appearance for years to
come.
Rotary Compressors — Provide quiet, reliable operation.
Copper Tube Aluminum Fin Coils — Enhanced coils provide durability, high performance, and ease of operation.
Fresh Air Control Arm — Allows outdoor air into room through vent filter for improved air quality.
Fan Cycle Switch — Dual options:
(1) Continuous fan operation.
(2) Cycle fan ON and OFF with compressor operation.
Thermostat with Temperature Limiter — Provides improved temperature control with a temperature limiter that allows temperature range restraints for the unit by making a simple adjustment.
Anti-Theft Knobs — Provides protection against theft of the thermostat knob and the mode selection knob.
Control Door — Provides protection for controls and enhances appearance.
Easy Access to Electrical Components — Simply remove two screws and drop down the control box door.
Improved Condensate Removal — Minimizes condensate water on outside of building.
New Two-Piece Filter Design — Provides improved air filtration and can be removed easily for cleaning.
Durable Discharge Grille — Made of polycarbonate; holds up under the toughest conditions.
Louvered Front Panel — Made of high impact polystyrene. Provides improved performance and quiet operation.
Mode Selection Switch — Rotary switch allows for easy selection of operating mode.
Bi-Molded Condenser Shroud — The two-piece condenser shroud allows easy access for service and maintenance to the outdoor coil and other components.
Power Cord Protection — Power cord for the 230/208-v unit provides power cord protection.

5

PRODUCT FEATURES AND BENEFITS
(52P AND 52C)
The 52P and 52C models are a single-package,
through-the-wall unit for heating and cooling hotel
rooms, offices, apartments, condominiums, and residential additions. Features include:
• Improved sound quality for quiet operation
• Exceeds ARI (Air Conditioning and Refrigeration
Institute) efficiency requirements with exceptional
energy efficiency ratios (EERs)
• Easy access, lifetime filters
• User friendly controls
• Easy to read dials
• Enhanced temperature and humidity control
• Improved condensate removal system
• Multi-room structure design
• Fixed wall sleeve, slide-out chassis
• Attractive, durable cabinet featuring new design
• Chassis that easily retrofits to most major competitors’ sleeves without use of retrofit kit
• Low operating costs
• No bulky duct system
• No seasonal changeover

The new aerodynamic split condenser shroud design
improves airflow and reduces outdoor noise, providing
a more relaxing outdoor environment. The new split
design allows for easy access to the outdoor coil to
facilitate routine cleaning of the coil. The propeller-type
fan design allows for efficient low-speed operation.

MOST EFFICIENT
PERFORMANCE
High EERs provide excellent operating economy. The
system operates without bulky ductwork, separate
equipment room, and complex match-up of different
components. Heating and Cooling modes are available
without seasonal changeover.

EFFICIENT FAN MOTOR
An efficient, totally enclosed PSC (permanent split
capacitor) fan motor provides a choice of high or low
speeds for heating and cooling. A fan-only setting
provides air circulation. The fan motor requires no
maintenance and no lubrication.

QUIET OPERATION
Occupants and neighbors are protected against noise
intrusion. Indoor sound reduction is achieved because
of the unit’s design and its louvered front cover, indoor
scroll and blower, and heavy gage unit partition.
Rotary compressors provide quiet, reliable operation.
The indoor scroll provides a more uniform air
discharge.

6

NO-RUST WEATHER LAST™
WALL SLEEVE AND FRONT
PANEL
The indoor front panel and polymer wall sleeve use
nonmetallic compounds that never rust or corrode, do
not support combustion, and do not give off toxic
fumes. The weather-resistant feature exceeds requirements of Underwriters’ Laboratories and resists damage caused by impact and scratching. The Weather
Last feature also insulates and has up to 10 times the
acoustic absorption of metal cabinets.
Insulated polymer wall sleeves combine all of the
above features with factory-installed insulation. The
insulation helps to reduce heat loss, save energy, provide better sound absorption, and reduce the risk of
sleeve sweating.
Carrier’s metal wall sleeves are available in a variety
of sizes for most standard and deep wall applications.
All metal wall sleeves come with factory-installed
insulation, designed to minimize heat loss and reduce
outdoor noise transmissions into the room.

Standard Wall Sleeve (Polymer)

42 in.

16 in.

14/18/24/26/28 in.

Standard and Deep Wall Sleeve (Metal)

REMOVABLE FRONT PANEL
The louvered front panel fits firmly onto the chassis
and features easy removal for service. It provides front
air intake to enhance performance and quiet operation.
It also allows the option of flush mounting PTAC unit
to the floor. If desired, the front panel can be
secured to the unit with field-supplied screws. The
2 locking screws (if installed) are located behind the
removable filter handles.
REMOVABLE
FILTER

LOCATION OF
REMOVED FILTER

LOCKING SCREW
(NOTE: 2nd LOCKING SCREW
IS LOCATED BEHIND
2nd FILTER)

Removable Front Panel

MODE

TEMPERATURE

ANTI-THEFT KNOBS

OFF

The anti-theft knobs are captured underneath the front
panel of the unit to prevent the knobs from being
removed or stolen.

LO

LO

HI

HI
WARMER

COOLER

HEAT

FAN

COOL

Anti-Theft Knobs
7

PRODUCT FEATURES AND BENEFITS (cont)
TWO-PIECE LIFETIME
INDOOR FILTER
New two-piece removable filters easily slide in and
out from the front of the PTAC unit and are interchangeable. The front panel does not need to be
removed to access or change the filters. The filters are
washable and permanent.
Two-Piece Indoor Filter

WASHABLE VENT AIR FILTER
The unique vent system is activated by a two-position
control. Fresh outside air is redirected by the vent door
to an inside low-pressure area. A molded plastic filter
prevents dirt and debris from entering the room side of
the unit. The vent mechanism is made from noncorrosive material ensuring reliable operation. A magnet on
the door and high-pressure airflow create a tight, draftfree seal when the vent door is closed.

The vent will provide 50 cfm of fresh air.
NOTE: If more fresh air cfm is required, a Power-Vent
Kit is available (see accessories).
Outdoor Vent Filter Location

BI-DIRECTIONAL
DISCHARGE GRILLE

40 DEGREE
AIR FLOW

80 DEGREE
AIR FLOW

The discharge grille is constructed of durable polycarbonate and is reversible. Air flows upward at a
40 degree angle to the floor but can easily be adjusted
to an 80 degree angle to the floor.

Reversible Polycarbonate Discharge Grille
8

POWER CORD FOR 265-V
UNITS
A power cord is included for 265-v units. The power
cord is 18 in. long (cord extends 15 in. from bottom of
front panel) and per UL and National Electrical codes
must plug into an electrical subbase.

20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1

265-V Unit with Power Cord

POWER CORD PROTECTION
FOR 230/208-V UNITS
The power cord for the 230/208-v unit provides power
cord protection by automatically disconnecting power
during an unsafe condition. Power can be restored by
pressing the RESET button.

30 Amp In-line
Power Cord

15/20 Amp Power
Cord Plug Head
BI-MOLDED
CONDENSER
SHROUD

BI-MOLDED CONDENSER
SHROUD
The bi-molded condenser shroud provides easy access
for service and maintenance of the condenser coil and
related components.

Bi-Molded Condenser Shroud

SNOW BAFFLE
The snow baffle is provided to keep snow from blowing into the intake and landing on the internal components of the PTAC unit. Melted snow can form ice on
moving parts and cause damage to the unit.
SNOW
BAFFLE

Snow Baffle
9

PRODUCT FEATURES AND BENEFITS (cont)
EASY ACCESS TO CHASSIS
Access to the chassis simply requires removing four
screws and then sliding the chassis out of the sleeve
for service.

TEST

1.PRES

DO

ING

2.PLUG S RESET
RECEP INTO
BUTTO
3.PRES TACLEPOWE
N.
R
SHOULS TEST .
4. PRESS D
BUTTO
LIGHT.
N UNIT
FOR
RESET
NOT USE.
BUTTO
USE
N AGAIN
IS TEST
ABOVE
FAILS

CHASSIS ATTACHMENT SCREWS
(SAME LOCATION ON OPPOSITE SIDE)
PLUG TEST/
RESET BUTTONS

Easy Service Access

HIDDEN CONTROLS

Fan Cycle Switch

The factory-wired control box houses all control components and is quickly accessible without removing
the chassis from the wall sleeve. By simply removing
two screws on control box, the hinged door lowers,
providing quick access to all the electrical components. The wiring diagram is located on the front of the
control box door.

The fan cycle switch allows the fan to operate in
2 modes:
• Continuous — This setting allows the fan to run
continuously, circulating air even when the temperature setting has been satisfied. This setting, which
helps to keep the room temperature closer to the
thermostat setting, is used for maximum comfort.
• Cycle — This setting allows the fan to cycle on and
off with the compressor during heating or cooling.
The fan stops when the temperature setting is
reached. The longer unit off-time makes this option
more energy-efficient with only slightly wider variations in room temperature.
NOTE: On wall thermostat models, the fan cycle/
continuous feature is typically located at the wall
thermostat.

Temperature Limiter and Control
Knob
The limiter reduces operating costs by allowing the
owner to control the range of cooling and heating temperatures available to the occupant. It is located under
the front panel on control box, out of the occupant’s
sight. Each setting on the limiter is equivalent to 5° F
and the range of temperature settings available to the
owner is from 60 to 90 F. The limiter is not pre-set at
the factory (providing full range for the occupant).

Outdoor Air Vent Control
Control of the outdoor-air vent is handled by a vent
handle located under the front panel on the left side of
the unit. This handle rotates to manually open and
close the outdoor vent.

The vent will provide 50 cfm of fresh air.
NOTE: If more fresh air cfm is required, a Power-Vent
Kit is available (see accessories).

10

ENHANCED COPPER TUBING
Enhanced copper tubing is more efficient and durable
and can be repaired in the field, if required.
Because copper is a very stable metal, it is durable and
resists corrosion. Enhanced copper tubing increases:
• heat transfer capability
• the efficiency of the cooling and heating processes
• thermal conductivity (by creating additional tube
surface and turbulent refrigerant gas flow)
Every Carrier PTAC coil undergoes thorough leak testing and pressure testing up to 350 lb per square inch.

SEAMLESS BASEPAN
Seamless drawn basepan walls add protection against
water accumulation resulting from storm-driven rain
with heavy wind.
Carrier’s deep basepan holds up to 11/2 gallons of
water without spilling. Closed cell foam insulators are
located between the basepan and coils, keeping coils
from direct contact with the basepan and providing
additional protection against corrosion.

Enhanced Copper Tubing

CONDENSATE DRAIN VALVE
The temperature-activated drain valve opens when the
outdoor temperature drops below 45 F to prevent
water from freezing in the basepan.

Condensate Drain Valve Prevents
Water from Freezing in Basepan

CONDENSATE REMOVAL
SYSTEM
Carrier’s 52P and 52C Series units have an improved
condensate (water) disposal system. In addition to
slinger ring technology, Carrier has developed and patented a Condensate Suction Port. The suction port,
along with the slinger ring, draws in water which is
sprayed up onto the outdoor coil. The water then evaporates, thus providing better disposal of excess condensate, improving unit efficiency.
NOTE: If it is necessary to remove 100% of the condensate, the Carrier Drain Kit (Part No.: DRAIN-KIT4PK) is recommended.

SLINGER
RING

CONDENSATE
SUCTION PORT
CONDENSER SECTION

Condensate Disposal System
11

PRODUCT FEATURES AND BENEFITS (cont)
HEAT PUMPS PAY THEIR
OWN WAY

How The Heat Pump Works

Heat pump models are available at a nominal additional cost. In many locales, the payback is realized in
just a few months. Cost and payback details are provided on the next page.

Special Features
Two-Stage Indoor Thermostat:
In Hot Weather:

The indoor thermostat senses the indoor temperature
and automatically turns on the electric heat to warm
the room quickly. After the desired temperature conditions have been satisfied, the thermostat automatically
switches to heat pump mode. If compressor failure
occurs, the thermostat will provide backup electric
heat automatically.

Carrier’s PTAC units provide indoor comfort in the
same manner as conventional air conditioners, removing heat and humidity from indoor air. The heat and
humidity is released to the outdoors. Carrier’s highefficiency design saves energy and reduces cooling
costs.

Outdoor Thermostat:
During the heating cycle, the outdoor thermostat
senses outdoor coil temperature. It switches the unit to
electric heat mode when the outdoor coil temperature
is 20 F or below (approximately 35 F outdoor-air temperature). The thermostat switches the unit back to
heat pump mode when the outdoor coil temperature
rises above 40 F, which is enough to provide heat
to meet demand. The entire operation is completely
automatic.

Reversing Valve:

In Cool Weather:

The reversing valve provides quiet refrigerant flow
after the unit shuts off. The valve controls the direction
of refrigerant flow for both heating and cooling functions and remains energized as long as the controls are
in the heat position. When the cooling controls are
activated, the valve automatically reverses to the cooling position.

When the outdoor coil temperature is above 20 F
(approximately 35 F outdoor-air temperature), the
heat pump draws heat from outdoor air and uses it to
heat indoor air. Since heat is transferred and not produced, Carrier’s heat pump uses less electricity and
reduces energy costs significantly.

Manual Compressor Override Switch:
This switch completely locks out the compressor. Note
that the compressor and heater do not operate at the
same time, thus conserving energy.

In Sub-Freezing Weather:
When the outdoor coil temperature falls below 20 F
(approximately 35 F outdoor-air temperature), the
unit automatically switches on a built-in electric
heater. The compressor stops and a blower circulates
warm air produced by the heater. When the outdoor
coil temperature rises above 40 F, heat pump operation
resumes automatically.
12

HEAT PUMP ENERGY
SAVINGS
Heat pumps save more on operating costs during the heating cycle
than heat/cool models. The table
below shows that the higher initial
cost of purchasing a heat pump is
quickly made up in lower operating
costs.
Use the map to identify the climate
zone’s designated number. Reading
down the left-hand column of the
table, select the cost/kWh rate in
this zone that most closely approximates your local rate. The approximated savings and payback period
is found at the intersection of your
zone/rate line and the desired Btuh
Cooling Capacity column. Exact
savings are determined by lifestyle,
local electrical rates, and climatic
conditions.

ZONE
VI

V
ZONE V
ZONE IV

ZONE III
II
ZONE II
ZONE I

CARRIER HEAT PUMP INITIAL COST VERSUS SAVINGS OVER HEAT/COOL MODELS
7000 BTUH1
COOLING
ELECTRIC
ZONE COST/kWH CAPACITY
Annual
Savings*
$.06
$ 34.26
I
$.08
$ 45.68
$.10
$ 57.10
$.06
$ 57.12
II
$.08
$ 76.16
$.10
$ 95.20
$.06
$ 58.02
III
$.08
$ 77.36
$.10
$ 96.70
$.06
$ 82.02
$.08
$109.36
$.10
$136.70
IV
$.12
$164.04
$.14
$191.38
$.16
$218.72
$.06
$ 57.36
$.08
$ 76.48
V
$.10
$ 95.60
$.12
$114.72
$.14
$133.84
$.06
$ 93.72
$.08
$124.96
VI
$.10
$156.20
$.12
$187.44

$60
PREMIUM
Payback
in Months
21
16
13
13
9
8
12
9
7
9
7
5
4
4
3
13
9
8
6
5
8
6
5
4

9000 BTUH2
COOLING
CAPACITY
Annual
Savings*
$ 43.08
$ 57.44
$ 71.80
$ 71.76
$ 95.68
$119.60
$ 72.84
$ 97.12
$121.40
$103.02
$137.36
$171.70
$206.04
$240.38
$274.72
$ 71.94
$ 95.92
$119.90
$143.88
$167.86
$117.66
$156.88
$196.10
$235.32

$75
PREMIUM
Payback
in Months
21
16
13
13
9
8
12
9
7
9
7
5
4
4
3
13
9
8
6
5
8
6
5
4

12000 BTUH2
COOLING
CAPACITY
Annual
Savings*
$ 58.20
$ 77.60
$ 97.00
$ 96.96
$129.28
$161.60
$ 98.40
$131.20
$164.00
$139.14
$185.52
$231.90
$278.28
$324.66
$371.04
$ 97.26
$129.68
$162.10
$194.52
$272.33
$159.00
$212.00
$265.00
$318.00

$90
PREMIUM
Payback
in Months
19
14
11
11
8
7
11
8
7
8
6
5
4
3
3
11
8
7
6
4
7
5
4
3

15000 BTUH3
COOLING
CAPACITY
Annual
Savings*
$ 68.34
$ 91.12
$113.90
$113.64
$151.52
$189.40
$115.38
$153.84
$192.30
$163.14
$217.52
$271.90
$326.28
$380.66
$435.04
$113.94
$151.92
$189.90
$227.88
$265.86
$186.48
$248.64
$310.80
$372.96

$110
PREMIUM
Payback
in Months
19
14
12
12
9
7
11
9
7
8
6
5
4
3
3
12
9
7
6
5
7
5
4
4

LEGEND
kWH — Kilowatt Hour
*Computer projections based on full cooling load at 95° F. Savings projected for 230 v ratings.
1Heating load is 5,000 Btuh at winter design point temperature.
2Heating load is 10,000 Btuh at winter design point temperature.
3Heating load is 15,000 Btuh at winter design point temperature.

For precise energy savings in your geographical location, go to www.lodgingAC.com to
use Carrier’s energy calculator.
13

ORDERING DATA (52P AND 52C)
For immediate assistance, call 1-800-827-7435 or contact
your local Carrier dealer.

Standard Unit
• Chassis with front panel
• Electro-mechanical controls
• Cord-connected chassis for 230/208-v and 265-v
units
Lead-time: Many models are in stock for immediate
delivery; call for lead-times.
EXTERIOR
GRILLE
(ACCESSORY)

Y)

TEST

DO

FRONT
PANEL
(STANDARD)

1.PRE
2.PLU SS RESE
G
RECE INTO T BUTT
3.PRE PTAC POWE
ON.
R
LE.
SHOUSS TEST
4. PRES LD
BUTT
LIGHT
ON
FOR S RESE .
UNIT
T BUTT
NOT USE.
USE
ON
AGAIN
IS TEST
ABOV
E FAILS

ING

PLUG TEST/
RESET BUTTONS

CHASSIS
(STANDARD)

Standard 52P or 52C Unit

PRODUCT CATALOG
NUMBER

14

WALL SLEEVE
(ACCESSOR

FACTORY-INSTALLED OPTIONS (52P AND 52C)
WALL THERMOSTAT
CONTROL (RC,RP)
Carrier’s wall thermostat control option includes:
• a standard chassis with front panel
• factory-installed low voltage controls for remote
thermostat operation
• indoor coil freeze protection
• user accessible selector switch for high or low fan
speed
Wall thermostat and wall thermostat wire must be
ordered separately.
See page 50 for a diagram of multiple PTAC units controlled by a single thermostat.
NOTE: Be sure to connect reversing valve wiring to
the O connection of the thermostat for heat pump
applications.
NOTE: Do not use a power stealing digital thermostat
(common must be connected for digital thermostats).

FAN SPEED

Comfort

WALL THERMOSTAT COMFORT

CORROSION PROTECTION
(CP,RP)
To protect against the corrosive effects of a seacoast
environment, this option includes:
• a standard chassis with front panel
• special protections consisting of:
— painted control box and unit partitions
— pre-coated aluminum coils with copper tubing
— stainless steel tube sheets (outdoor coil)
— totally enclosed fan motor with moistureresistant windings
NOTE: All installations within one mile of the sea
coast or other corrosive environment must use Corrosion Protection (CP).

15

LO

HI

FIELD-INSTALLED ACCESSORIES (52P AND 52C)
WALL SLEEVES

The sleeve's alpine mist color (a shade of beige)
closely matches the front panel and blends in well with
any inside or outside decor.
The polymer wall sleeve comes in both insulated (factory installed) or non-insulated, to meet the requirements of every application.

Weather Last™ Wall Sleeve
For the best performance and longest life, Carrier
recommends genuine Carrier wall sleeves for all
installations.
All Carrier wall sleeves are built with a pitch of 1/4 in.
per foot; for self-pitching of the unit, the wall sleeve
must be installed level (any error should be pitched to
the outside). Overflow slots on the outside of the
sleeve are in place to divert excess water during severe
weather.

Insulated Polymer Wall Sleeve
Part No.: SLEEVE-INSUL-1PK
Carrier’s accessory insulated polymer wall sleeve, with
factory-installed insulation, provides superior sound
absorption, reduces heat loss and prevents sleeve
sweating, a condition that can occur when the outside
temperature is cold and the indoor conditions are warm
and humid.

Important Sleeve Installation Considerations:
• All Carrier's sleeves are self pitching and must be
mounted level in all directions. (Do not use rails
to level sleeve.)
• The sleeve should be caulked on all sides, including both inside and outside the building.
• If more than 4 in. of wall sleeve projects into the
room, an accessory subbase must be used for
support.
• For all applications with an accessory subbase,
wall sleeve must extend 31/4 in. minimum into
room and must be 31/4 in. minimum to 51/2 in.
maximum above floor (including carpeting) to
allow for proper fit of subbase.
• For applications where the wall sleeve is
mounted flush to the exterior of the building
(or recessed in), Carrier recommends a fieldsupplied drip edge be installed to prevent water
infiltration into the building.
• Insulated wall sleeves should be considered for
superior sound absorption, to reduce heat loss
and to prevent sleeve sweating, a condition that
can occur when the outside temperature is cold
and the indoor conditions are warm and humid.

IMPORTANT: Insulated Polymer Wall sleeve provides superior sound absorption, reduces heat loss
and prevents sleeve sweating.

Corrosion-Protected Polymer Sleeve

Non-Insulated Polymer Wall
Sleeve

Polymer Wall Sleeves

Part No.: WALL-SLEEVE-1PK
Part No.: WALL-SLEEVE-9PK
Carrier’s accessory non-insulated polymer wall sleeve,
provides a superior appearance and protection for
many applications.

Choose a polymer wall sleeve for maximum protection and appearance.
All Carrier’s polymer wall sleeves are made from a
molded polymer that is designed for strength and durability. This material has excellent corrosion resistance
and a flammability rating of UL94-5V.
The sleeve surface is textured to prevent shine and
hide scratches. The rib configuration on the sleeve bottom, allows easy chassis removal and aids in drainage.
The locating holes in the side and top panels, allow
easy fastening of the sleeve to wall openings. Refer to
dimension drawings (pages 28 and 29) for typical wall
installation and dimensions.

For applications where weather conditions could
influence sleeve sweating, a condition that can occur
when the outside temperature is cold and the indoor
conditions are warm and humid, the Insulated Polymer Wall sleeve should be considered.

16

Insulated Metal Wall Sleeves

42 IN.

Part No.: SLEEVE-STEEL-1PK
Part No.: SLEEVE-EXT18-1PK
Part No.: SLEEVE-EXT24-1PK
Part No.: SLEEVE-EXT26-1PK
Part No.: SLEEVE-EXT28-1PK
Carrier's metal wall sleeves are available in a variety
of sizes for most applications and difficult installations. Choose from 14 in., 18 in., 24 in., 26 in., or
28 in. standard depth sizes. All metal wall sleeves
come with factory-installed insulation, designed to
minimize heat loss, reduce outdoor noise transmissions into the room and prevent sleeve sweating. In
addition, the metal wall sleeve provides a flammability
rating higher than UL94-5V.

16 IN.

14/18/24/26/28 IN.

Standard and Extended Metal Wall Sleeve
1 IN.

Wall Sleeve Molding Kit
Part No.: SLEEVE-MOLDING
For a superior look and to hide any construction
imperfections, use Carrier's wall sleeve molding kit to
trim the wall sleeve to the wall. The molding kit is a
perfect solution and can be used with any Carrier wall
sleeve (matches Carrier wall sleeve color).

1/2 IN.

Wall Sleeve Molding Kit

Friedrich (and ZoneAire) Retrofit Wall Sleeve Adapter
Part No.: FR-SLEEVE-EXT
The Friedrich (and ZoneAire) wall sleeve adapter is
constructed of sheet metal and is designed to increase
the depth of an existing Friedrich T-series or ZoneAire
wall sleeve to accommodate Carrier’s industry standard PTAC units.

16 IN.

42 IN.

3 IN.

Friedrich Wall Sleeve Adapter Kit

Climate Master Wall Sleeve
Adapter
Part No.: CM-SLEEVE-EXT
The Climate Master wall sleeve adapter is constructed
of sheet metal and is designed to increase the depth of
an existing Climate Master 121/2 in. wall sleeve to
accommodate Carrier’s industry standard PTAC units.

16 IN.

42 IN.

1 1/2 IN.

Climate Master Wall Sleeve Adapter Kit
17

FIELD-INSTALLED ACCESSORIES
(52P AND 52C) (cont)
OUTDOOR GRILLES

Polymeric Architectural Outdoor
Grilles (Louvered)

Carrier recommends only the use of Carrier-supplied
grilles for use on the 52P and 52C series units. However, the architectural designs of a building may dictate the use of special or oversized grilles and/or
louvers. Special louvers or any special architectural
treatment of the building façade that may restrict free
circulation of condenser airflow should be referred to
Carrier Corporation for evaluation and approval.

Part No.: GRILLE-PLA-BROWN
Part No.: GRILLE-PLA-BEIGE
Part No.: GRILLE-PLA-ALPIN (color matches
Carrier wall sleeve)
This value line of polymeric architectural outdoor
grilles will blend attractively with most building exteriors. Mounted easily from inside the room, the onepiece, molded grille is designed for protection,
enhanced appearance, and superior weather-resistance.
The grille is made of durable polymer and has a colorfast, lightly textured finish that blends well with most
exterior finishes.

Aluminum Architectural
Outdoor Grilles (Louvered)
Part No.: GRILLE-ALU-CLEAR (anodized aluminum)
Part No.: GRILLE-ALU-WHITE
Part No.: GRILLE-ALU-BEIGE
Part No.: GRILLE-ALU-ALPIN (color matches
Carrier wall sleeve)
Part No.: GRILLE-ALU-BRONZ
Part No.: GRILLE-ALU-MBRNZ
Part No.: GRILLE-ALU-BROWN
Part No.: GRILLE-ALU-LGREY
Part No.: GRILLE-ALU-SGREY
Part No.: GRILLE-ALU-PEACH
Part No.: GRILLE-ALU-MELON
Part No.: GRILLE-ALU-RDBRK
Part No.: GRILLE-ALU-BLUE
Part No.: GRILLE-ALU-GREEN
This premium line of decorative outdoor grilles will
enhance the appearance of any building. The grilles
are made of strong, durable, extruded, anodized aluminum and are designed to be mounted easily from
inside the room. These elegant grilles, available in
many standard colors, have baked enamel finishes
containing 50% kynar resin, for a superior finish that
will withstand the most extreme conditions. See inside
of back cover for standard colors and color samples.
For more information on custom colors and sizes, contact Reliable Products at 1-800-239-4621.

Architectural Grille in
Aluminum or Polymeric

Standard Outdoor Aluminum
Grille
Part No.: GRILLE-ALU-STAMP
This cost-effective, one-piece standard grille is made
from durable anodized aluminum. The grille is lightweight, has a clear finish, and is easy to install from
inside the room.

Standard Grille
18

Outdoor Grille Selection
IMPORTANT: If you wish to use a grille not
made by Carrier for your Carrier unit(s), contact the Carrier Application Engineering Group
at 1-800-894-6449.

X

Y

The following guidelines must be followed in the initial selection of any alternate exterior grille or louver:
1. The louver must have a minimum of 65% free area.
Free area is the minimum area of the opening in an
air inlet or outlet in which air can pass. Free Area
(%) = X/Y.
2. The louver should be attached to the wall sleeve in a
manner that will prevent recirculation of condenser
discharge air into the inlet. In most applications, baffles, splitters, and/or gasket will be required between
the chassis tube end sheets and the louver to prevent
air recirculation.
The above criteria must be followed, since a louver
that is restrictive or allows recirculation will result in a
reduction of the unit’s capacity and efficiency and will
ultimately shorten the compressor life.

Y

X
Y

X

X
Y

Louver Dimensional Reference

Sample Calculations
Free Area (%) =

x
x 100
y

x = 1″
y = 1.5″
F.A. (%) =

1
x 100 = 66.7%
1.5

Hardwire Kit
Part No.: HARDWIRE-KIT-1PK
This accessory hardwire kit provides a permanent connection to the unit. Electrical hard wiring is required
when NEC (National Electrical Code) or local codes
restrict the use of power cord and plug connections.
The hardwire kit mounts on the front right side of the
unit and comes with 36 inches of flexible steel conduit
and a Molex connector for easy connect/disconnect.
Hardwire Kit

Conduit Interface Kit
Part No.: CONDUIT-INTF-4PK
The conduit interface accessory kit provides the wire
connection to the unit to interface to field-supplied
conduit.

Conduit Interface Kit

19

FIELD-INSTALLED ACCESSORIES
(52P AND 52C) (cont)
SUBBASE
Part No.: SUBBASE-NON-ELEC
Part No.: SUBBASE-230V-15A
Part No.: SUBBASE-230V-20A

Part No.: SUBBASE-230V-30A
Part No.: SUBBASE-265V-15A
Part No.: SUBBASE-265V-20A

Part No.: SUBBASE-265V-30A
Part No.: SUBBASE-HARDWIRE
Part No.: LEVELING-LEGS

This decorative subbase supports the unit and is available in three basic models: non-electrical, electrical,
and hardwired.
A subbase (or leveling legs) is required for installations where the wall sleeve extends 4 or more inches
into the room or the wall is less than 2 in. thick.
The minimum clearance between the bottom of the
sleeve and the floor is 31/4 in., and the maximum clearance is 51/2 inches.
IMPORTANT: All standard cord-connected 265-v
PTAC units will require a field-installed electrical
subbase accessory per UL and NEC electrical codes.
All subbase models are pre-assembled, mount to the
wall sleeve, and come with adjustable legs and side
skirting to provide a finished appearance.

Non-electrical subbase
The easy to install, non-electrical subbase provides
mechanical support and requires no wiring.

Non-Electrical Subbase Assembly

Electrical subbase
The electrical subbase has a factory-installed electrical
junction box containing a receptacle for corded packaged terminal air conditioner (PTAC) units. The electrical subbase series offers models from 230-v, 15 amp
up to 265-v, 30 amp. Knockouts are provided for
power source connections.
Electrical Subbase Assembly

Hardwired subbase
The hardwired electrical subbase has a factoryinstalled junction box containing 19 in. of flexible
conduit (for a perfect fit to the PTAC unit) and all mating connections for easy assembly to PTAC units.
Knockouts are provided for power source connections.
Hardwired Subbase Assembly

20

Leveling legs
Part No.: LEVELING-LEGS
Leveling legs attach easily to Carrier’s wall sleeve and
offer accurate leveling and support for units without a
subbase. Leveling legs are adjustable from 31/4 in. to
51/2 in.
Leveling-Legs

Subbase Fuse Kit
Part No.: SUBBASE-FUSE-15A
Part No.: SUBBASE-FUSE-20A
Part No.: SUBBASE-FUSE-30A
The fuse kit provides in-line overcurrent protection at
the unit when required by NEC (National Electric
Code) or local codes.
IMPORTANT: The Fuse Kit can only be used with
the electrical or hardwired subbase.
Subbase Fuse Kit

Subbase Power Disconnect
Switch
ON

Part No.: SUBBASE-SWITCH
The subbase power disconnect 2-pole switch provides
a recessed power disconnect for the PTAC unit when
required by NEC or local codes.
IMPORTANT: This accessory can only be used
with the electrical or hardwired subbase.

Power Disconnect Switch Assembly

21

FIELD-INSTALLED ACCESSORIES
(52P AND 52C) (cont)
THERMOSTATS
Carrier’s full line of wall thermostats are designed to
enhance every PTAC application. Wall thermostats are
simple and easy to use. Wall thermostats provide better temperature and humidity control as they can be
placed in an optimal position in the room.
NOTE: See page 50 for a wiring diagram of multiple
PTAC units controlled by one thermostat.

Digital Programmable
Thermostat
Part No.: TSTATCCPAC01-B (for heat/cool models)
Part No.: TSTATCCPHP01-B (for heat pump models)
This microcomputer-controlled, 7-day programmable
wall thermostat has enhanced features that provide
automatic control for both heat pumps and heating/
cooling units. It is used only on wall thermostat control (RC,RP) models.

Programmable Thermostat

Non-Programmable Thermostat
Part No.: TSTATCCBPC01-B (for heat/cool models)
Part No.: TSTATCCBPH01-B (for heat pump models)
This low-voltage, easy-to-use non-programmable thermostat provides maximum guest comfort. This thermostat can only be used on wall thermostat (RC,RP)
models.
Non-Programmable Thermostat

Manual Changeover Wall
Thermostat
Part No.: HH01AD045 (for heat/cool and heat pump
models)
This manual changeover wall thermostat provides a
reliable and consistent level of occupant temperature
control for both heat pumps and heating/cooling units.
The thermostat consists of a conventional vented
cover and a coiled bimetal element. It is used only on
wall thermostat control (RC,RP) models.

Auto
FAN
On

Heat

•60•

70•8

0•90

Off

•
Cool

Manual Thermostat
22

Wall Thermostat Interface
Retrofit Kit
Part No.: RC-FIELDKIT230HC
Part No.: RC-FIELDKIT230HP
Part No.: RC-FIELDKIT265HC
Part No.: RC-FIELDKIT265HP
The Wall Thermostat Interface Retrofit Kit allows
PTAC units with standard unit-mounted controls to be
field converted for use with wall thermostat controls.
NOTE: To obtain retrofit kits for previous 52S Carrier
models, contact your Carrier sales representative.

WA L

L T

MO
HER

S TA

OM
T C

FOR

T

Wall Thermostat Interface Retrofit Kit

2-Speed Fan Control from Wall
Thermostat

2

4

Part No.: 2SPEED-TSTAT-KIT
This kit includes an automatic heat/cool changeover
thermostat and relay logic for allowing multiple fan
speed control from the wall thermostat. The thermostat
is simple to operate and install, and provides features
designed for the lodging industry, such as, Hi and Low
fan speed control, freeze guard, set point limits and
large, easy to read display.

5
6
FAN AUTO

F
TO SET PRESS
FAN

F/C

OR

COOLER

WARMER

1

3

Auto Changeover Thermostat and
Speed Control Relay

Part No.: 2SPEED-RCFAN-KIT
This kit only contains the relay logic for allowing multiple fan speed control from a wall thermostat.
NOTE: When selecting a thermostat, ensure that the
thermostat is capable of 2-fan speed control.

Thermostat Locking Cover
Part No.: TSTAT-COVER-6X7
Part No.: TSTAT-COVER-7X10
The thermostat locking cover prevents unauthorized
access to the thermostat.

Thermostat Locking Cover

23

FIELD-INSTALLED ACCESSORIES
(52P AND 52C) (cont)
Condensate Drain Kit
Part No.: DRAIN-KIT-4PK
This universal drain kit may be used internally or
externally to route condensate to a drainage system. It
can be field-installed on any Carrier wall sleeve.
Although Carrier’s units are designed to dissipate all
the condensate generated during normal cooling, there
may be times when abnormal conditions cause more
condensate than the unit can dissipate. If condensate
that drips from the wall sleeve is objectionable, this
internal/external drain kit should be installed.
The drain kit may be attached to the exterior right or
left side of the wall sleeve for external draining or may
be mounted to the room side of the wall sleeve for
internal draining.

Drain Kit

IMPORTANT: For internal drains installed in the
plastic wall sleeve, the drain must be installed on
the flat area of the sleeve. It cannot be installed in
the wafer area.

Lateral Duct Kit
Part No.: LATERAL-DUCT (Adapter Plenum and
Extension)
The accessory lateral duct kit allows one unit to heat
or cool two rooms. The kit provides substantial savings for apartments, hotel suites, and office suites by
eliminating the need for separate units for every room.
The amount of air that can be diverted to an adjoining
room is adjustable from 20 to 30 percent.
The lateral duct kit consists of two main components,
the plenum and the extension duct. The kit mounts to
the wall sleeve and allows either right or left side ducting. Consider the following when designing a ducted
application.
• The maximum extension of the duct length is 4 feet.
• The duct run must be straight and horizontal; no
bends or turns.
• The minimum recommended clearance between the
unit and the adjoining room wall is 6 inches.
• You must provide for return air from the adjoining
room.
• Carrier 52P and 52C units are not qualified for use
with any other ducting scheme.
See page 31 for more information.
NOTES:
1. Lateral Duct Kit includes wall register for duct
extension and a molding kit to trim the wall opening.
2. The sleeve should extend a minimum of 3-in. into
the room to install mounting brackets.
3. The Lateral Duct Kit is not compatible with previous PTAC models.

Lateral Duct Kit

24

Power Vent with Power Door Kit
Part No.: PWR-VENT-DOOR230
Part No.: PWR-VENT-DOOR265
Carrier's power vent kit, utilizing a specially designed
fan, when installed in the unit's fresh air vent, will supply up to 95 cfm of outside air into the room. The
power vent will only operate when the unit fan runs,
and the unit will automatically open or close the vent
door, depending on the operation of the fan. The kit
comes pre-assembled from the factory and is very easy
to install.
Power Vent with Door Kit

Lateral Air Deflector
Part No.: DEFLECTOR-1PK
Carrier’s exclusive lateral air deflector allows discharge air to be directed right or left in a room. This
field-installed accessory is equipped with independently adjustable louvers to enhance air circulation.
Lateral air deflectors are recommended for units
mounted in a corner or off-center in a room.
NOTE: The lateral air deflector is not compatible with
previous PTAC models.

Accessory Air Deflector

Curtain Deflector
Part No.: CURTDFL-52CP-1PK
The curtain deflector is used to prevent curtains from
being blown into the discharge air.

Curtain Deflector Kit

Security Door Kit
Part No.: SECURITY-DOOR

This key-locking security door kit prevents unauthorized access to the unit’s heating and cooling controls
and prevents tampering with units in public locations
and institutions. This field-installed accessory includes
two matching keys and fits all Carrier 52P and 52C
models. Keys are common to all Security Door kits.
Security Door Kit

25

FIELD-INSTALLED ACCESSORIES
(52P AND 52C) (cont)
Replacement Filters
Part No.: AIR-FILTER-10PK
The Carrier 52P and 52C model replacement air filters
come in packages of 10. The filters save energy by preventing the evaporator coils from being plugged with dirt
and lint. These economical and sturdy filters are interchangeable and may be washed, vacuumed, and reused.

Easily Replaceable Filters

Energy Management Kit
Part No.: EM-KIT
This field-installed accessory kit allows individual
units to be turned on and off from a remote location.
The kit incorporates Carrier’s Freeze Guard protection
that prevents rooms from freezing during extreme or
extended cold periods. Under these conditions, the
Freeze Guard automatically disables front desk control
and allows the unit to maintain a temperature of at
least 50 F in the room. When the room reaches 65 F,
the Freeze Guard feature returns the unit control to the
front desk.
This kit interfaces to most energy management systems. When installed in locations other than the front
desk, the kit can control unit operation by receiving
signals from field-supplied devices such as motion
sensors or heat sensing detectors.
Control devices connected to the Energy Management
Kit must have normally open sets of contacts (when
the switch is open, the unit operates). A 24-volt transformer must be field supplied and connected to the
Energy Management Kit. (See typical wiring diagram
on page 49.)

Energy Management Kit

26

DIMENSION DRAWINGS AND INSTALLATION
DATA — NEW CONSTRUCTION
TYPICAL WALL
INSTALLATION

If practices are unknown, consult your local architect
or building contractor.
Installed wall sleeve must be level from side to side
and front to back.

Proper building practices must be used when constructing a wall opening to support a PTAC wall sleeve
and chassis.

DISCHARGE
GRILLE

3 -6
(1067)

ACCESSORY
WALL SLEEVE

REMOVABLE
FRONT PANEL
3.94"
(100)

HINGED CONTROL
ACCESS DOOR

15/20 AMP
PLUG HEAD
(SEE NOTE #8)

2.03"
(51.6)
7.24"
(184)

1 -10
(558.8)
6
(152.4)

2.00"
(50.7)

4 -4
(1320.8)

30 AMP IN-LINE
CORD
208/230-V
SERVICE CORD
30 AMP
12"
(304.8)

208/230-V UNITS
3’-6”
(1067)

DISCHARGE
GRILLE

ACCESSORY
WALL SLEEVE
HINGED CONTROL
ACCESS DOOR

REMOVABLE
FRONT PANEL

(SEE NOTE #8)

15”
(381)

265-V
SERVICE CORD
(SEE NOTE #9)

6”
(152.4)
15”
(381)

265-V UNITS

52P and 52C Dimension Drawing
27

NOTES:
1. Dimensions in parenthesis are in
millimeters.
2. Minimum opening sizes apply to
all wall openings.
3. Proper building practices must
be used when constructing a
wall opening to support a PTAC
wall sleeve and chassis. If practices are unknown consult your
local architect or building
contractor.
4. Installed wall sleeve must be
level from side to side and front
to back (do not use rails to level
sleeve).
5. If wall sleeve extends into the
room more than 4-in., an accessory subbase or field fabricated
front support should be used to
prevent wall sleeve from tipping
forward.
6. For all applications with an
accessory subbase, wall sleeve
must extend into room 31/4-in.
(83 mm) minimum and 31/4-in.
(83 mm) minimum from floor.
7. For all applications with an
accessory lateral duct, sleeve
must extend into the room 3-in.
(76.2 mm) minimum. In applications where the sleeve will not
extend a minimum 3-in., the lateral duct mounting brackets
must be mounted on the
wall sleeve prior to wall sleeve
installation.
8. Remote control models, “RC”
and “RP” units, use low voltage
connections (24 volt AC).
9. 265 volt cord connected units
must plug into a 265 volt electrical subbase per UL requirement
(or hardwire can be used).
10. The 265 volt electrical cord is
approximately 15-in. long from
where it exits the front panel.

DIMENSION DRAWINGS AND INSTALLATION
DATA — NEW CONSTRUCTION (cont)
WALL SLEEVE MOUNTING DIMENSIONS FOR STANDARD
AND ACCESSORY GRILLES
JACK STUDS
MAIN STUD
HEADER- 4’ x 4’ OR
(2) 2’ x 4’ ON EDGE

16 1/4”

42 1/8”

Standard Polymer Non-Insulated Wall Sleeve
Standard Polymer Insulated Wall Sleeve

JACK STUD

42 in.
CRIPPLE
16 in.
FLOOR

SUB-FLOOR

Framing and Minimum Wall Sleeve Opening

14/18/24/26/28 in.

Standard and Extended Metal Insulated Wall Sleeve

NOTES (ALL SLEEVES):
1. Never install fasteners through bottom of sleeve.
2. Never use rails to level sleeve.

Wall Sleeve Mounting (All Models)

28

TYPICAL WALL INSTALLATION
NOTES:
1. Sleeve may be flush mounted to floor, but front panel may have
to be notched to accommodate service cord.
2. If more than 4 in. of sleeve projects into room, an accessory
subbase must be used for support.
3. For walls 2 in. thick or less, an accessory subbase must be
used for support.
4. Caulk around sleeve on both indoor and outdoor sides.

Typical Wall Sleeve Installation

Typical Curtain Wall Installation (All Models)

29

DIMENSION DRAWINGS AND INSTALLATION
DATA — NEW CONSTRUCTION (cont)
MINIMUM CLEARANCE FOR INDOOR AND
OUTDOOR DISCHARGE AIR
Blocking indoor or outdoor discharge air could
cause premature failure of unit.

15” MINIMUM DISTANCE FROM
FRONT PANEL TO OBJECTS IN ROOM

36" MINIMUM DISTANCE FROM
SLEEVE TO BUILDING WALLS,
SHRUBS, etc.

52P and 52C Indoor and Outdoor Discharge Air Circulation

OUTDOOR VIEW

GRILLE
MOUNTING
HOLES

WALL S
LE

EVE

2 3/8”
(60.3)
WALL SLEEVE-(2)
DRAIN LOCATIONS

GRILLE
MOUNTING
HOLES
CONDENSATE
OVERFLOW
HOLES
2 3/8”
(60.3)

(OUTSIDE)

Back of Polymer Wall Sleeve

30

TYPICAL LATERAL DUCT INSTALLATION
WALL
REGISTER

ALTERNATE
EXTENSION
POSITION*

LATERAL DUCT
EXTENSION
PLENUM
END
CAP

3’-8”
(117.6)

WALL
MOLDING

3’-11 1/2”
(1206.5)
MAX.

REVERSIBLE
AIR GRILLE

3’-11 1/2”
(1206.5)
MAX.

*Only one Lateral Duct Extension may be installed per
unit. Lateral duct extensions may be installed on either
side of the unit.

NOTE: For all applications with an accessory lateral duct, sleeve
must extend into the room a minimum of 3 inches. In applications
where the sleeve will not extend a minimum of 3 in., the lateral duct
mounting brackets will need to be mounted on the sleeve prior to
installation to the wall.

52P and 52C Lateral Duct

31

DIMENSION DRAWINGS AND INSTALLATION
DATA — NEW CONSTRUCTION (cont)
52P AND 52C WITH SUBBASE

0’-3 1/4” MIN. (83)
0’-5 1/2” MAX. (140)

0’-0 7/8”
(22)
SUBBASE ACCESS COVERS
OUTSIDE
WALL
SEE
NOTES

1 9/16”
(39.7)
SIDE

19 1/2”
(495.3)
(3) 7/8” (22.2)
DIA. KNOCKOUTS
(3) 1 1/8” (28.6) DIA.
KNOCKOUTS

REAR VIEW
ACCESSORY SUBBASE
ELECTRICAL CONNECTIONS

SUBBASE LEVELING BOLTS
ACCESSORY DRAIN
(EXTERNAL OR INTERNAL)

NOTES:
1. Accessory subbase is required for applications where:
• Wall sleeve extends 4 or more inches into the room.
• Wall thickness is less than 2 inches.
• All 265-v cord-connected applications.
2. For all applications with an accessory subbase:
• Wall sleeve must extend 4 in. minimum into the room and 31/4 in. minimum above the floor.
• Subbase height is adjustable from 31/4 in. minimum to 51/2 in. maximum above floor (including carpeting).
Refer to wall sleeve installation instructions.

32

17”
(431.8)

WALL THERMOSTAT CONNECTIONS
FAN SPEED
CONTROL
KNOB

R
Y
W
G
O
C

POWER
CORD
ACCESS
COVER

THERMOSTAT
WIRE (FIELDSUPPLIED)
R
Y
W
G
O
C

POWER
CORD

THERMOSTAT

Control Box Wire Terminal for
Wall Thermostat Models

Terminal Connector
Removal and Replacement

NOTE: Thermostat wire is field supplied. Recommended wire gage is
18 to 20 gage solid thermostat wire. Thermostat wire should always be
routed around or under, NEVER through, the wall sleeve. The wire
should then be routed behind the front panel to the easily accessible
terminal connector.

THERMOSTAT WIRE ROUTING (UNDER
SLEEVE, BEHIND FRONT PANEL)

Terminal Wire Routing

33

PRODUCT DATA (52P)
PERFORMANCE AND ELECTRICAL DATA
MODEL 52PQ (230/208-1-60)
MODEL
NUMBER
52PQ
207---3
307---3
209---3
309---3
212---3
312---3
512---3
215---3
315---3
515---3

CAPACITY* (Btuh)
AMPS
WATTS
VOLTAGE
HEATER
Heating
EER
COP† RANGE
kW
Cooling
Heating
(Volts) Cooling Heating** Cooling
Rev. Cyc.
Electric
7,200/ 7,100 6,300/ 6,300 7,800/ 6,400
2.3
12.7/12.7 3.4/3.4
2.7/2.9 10.4/ 9.5 567/ 559 2393/1985
7,200/ 7,100 6,300/ 6,300 11,600/ 9,700
3.4
12.7/12.7 3.4/3.4
2.7/2.9 15.2/14.1 567/ 559 3493/2935
9,100/ 9,000 7,900/ 7,900 7,800/ 6,400
2.3
11.5/11.5 3.2/3.2
3.7/3.8 10.4/ 9.5 791/ 783 2393/1985
9,100/ 9,000 7,900/ 7,900 11,600/ 9,700
3.4
11.5/11.5 3.2/3.2
3.7/3.8 15.2/14.1 791/ 783 3493/2935
12,100/12,000 11,000/11,000 7,800/ 6,400
2.3
11.1/10.7 3.2/3.2
4.8/5.3 10.8/ 9.9 1090/1122 2470/2047
187-253
12,100/12,000 11,000/11,000 11,600/ 9,700
3.4
11.1/10.7 3.2/3.2
4.8/5.3 15.6/14.5 1090/1122 3570/2997
12,100/12,000 11,000/11,000 17,000/13,600
5.0
11.1/10.7 3.2/3.2
4.8/5.3 22.5/20.0 1090/1122 5170/4147
14,800/14,300 14,100/13,500 7,800/ 6,400
2.3
9.7/ 9.5 3.0/3.0
6.5/7.1 10.8/ 9.9 1526/1505 2470/2047
14,800/14,300 14,100/13,500 11,600/ 9,700
3.4
9.7/ 9.5 3.0/3.0
6.5/7.1 15.6/14.5 1526/1505 3570/2997
14,800/14,300 14,100/13,500 17,000/13,600
5.0
9.7/ 9.5 3.0/3.0
6.5/7.1 22.5/20.0 1526/1505 5170/4147

FAN MOTOR
MODEL POWER
Full
NUMBER FACTOR
Horsepower Load
52PQ
(%)
Amps
207---3
100
0.075
0.44
307---3
209---3
99
0.075
0.44
309---3
212---3
312---3
99
0.125
0.75
512---3
215---3
315---3
99
0.125
0.75
515---3

Indoor
CFM
LO/HI††

MAX FUSE
MIN.
RECEPR-22
DEHUMIDIFI- SENSIBLE APPROX.
CHASSIS
SIZE
CIRCUIT TACLE CHARGE
CATION
HEAT
SHIP WT.
(Amps)
AMPS
TYPE
(oz)
(Pints/Hr)
FACTOR
(lb)

220/260
220/260

270/350

250/320

15
20
15
20
15
20
30
15
20
30

13.0
19.0
13.0
19.0
13.3
19.3
27.9
13.3
19.3
27.9

A
B
A
B
A
B
C
A
B
C

24

1.5

0.78

125

24

2.4

0.73

125

34

3.4

0.71

140

32

4.6

0.67

150

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††Fan motor indoor CFM (LO/HI) shown for 230-1-60 units.
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

230/208
250/20

250/15

250/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association
*May be used for 15-amp applications if fused for 15 amps.

34

B

C

6-15R

6-20R

6-30R

15

20*

30

2.3

3.4

5.0

PERFORMANCE AND ELECTRICAL DATA
MODEL 52PQ (265-1-60)
MODEL
NUMBER
52PQ
207---4
307---4
209---4
309---4
212---4
312---4
512---4
215---4
315---4
515---4

CAPACITY* (Btuh)
Heating
Cooling
Rev. Cycle Electric
7,200
6,300
7,800
7,200
6,300
11,600
9,100
7,700
7,800
9,100
7,700
11,600
12,100
10,800
7,800
12,100
10,800
11,600
12,100
10,800
17,000
14,700
14,100
7,800
14,700
14,100
11,600
14,700
14,100
17,000

FAN MOTOR
MODEL
POWER
Full
NUMBER FACTOR
Horsepower Load
52PQ
%
Amps
207---4
97
0.075
0.46
307---4
209---4
97
0.075
0.46
309---4
212---4
312---4
99
0.125
0.71
512---4
215---4
315---4
96
0.125
0.71
515---4

Indoor
CFM
LO/HI
220/260
220/260

270/340

250/320

HEATER
kW

EER

COP†

2.3
3.4
2.3
3.4
2.3
3.4
5.0
2.3
3.4
5.0

12.3
12.3
11.5
11.5
11.1
11.1
11.1
9.7
9.7
9.7

3.4
3.4
3.2
3.2
3.2
3.2
3.2
3.0
3.0
3.0

MAX. FUSE
SIZE
(Amps)

AMPS

VOLTAGE
RANGE

Cooling

Heating**

Cooling

Heating

2.4
2.4
3.1
3.1
4.2
4.2
4.2
5.7
5.7
5.7

9.2
13.3
9.2
13.3
9.4
13.5
19.6
9.4
13.5
19.6

585
585
791
791
1090
1090
1090
1515
1515
1515

2396
3496
2396
3496
2470
3570
5170
2470
3570
5170

239-292

MIN.
RECEPR-22
CIRCUIT TACLE CHARGE
AMPS
TYPE††
(oz)

15
20
15
20
15
20
25
15
20
25

11.3
16.5
11.3
16.5
11.6
16.7
24.3
11.6
16.7
24.3

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††All 265-v units require an electrical subbase (receptacle or hardwire model).

A
B
A
B
A
B
C
A
B
C

WATTS

DEHUMIDIFICATION
(Pints/Hr)

SENSIBLE APPROX.
CHASSIS
HEAT
SHIP WT
FACTOR
(lb)

26

1.5

0.78

125

24

2.4

0.73

125

34

3.4

0.71

140

33

4.6

0.67

150

New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

265
277/20

277/15

277/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association

35

7-15R

B
7-20R

C
7-30R

15

20

30

2.3

3.4

5.0

PRODUCT DATA (52P) (cont)
PERFORMANCE AND ELECTRICAL DATA
MODEL 52PC AND PE (230/208-1-60)
52PC performance and electrical data is the same as 52PE without electric heat.
MODEL
NUMBER
52PE
007---3
207---3
307---3
009---3
209---3
309---3
012---3
212---3
312---3
512---3
015---3
215---3
315---3
515---3
MODEL
NUMBER
52PE
007---3
207---3
307---3
009---3
209---3
309---3
012---3
212---3
312---3
512---3
015---3
215---3
315---3
515---3

CAPACITY* (Btuh)
Cooling

Heating

HEATER
kW

EER

7,200/ 7,100
7,200/ 7,100
7,200/ 7,100
9,100/ 9,000
9,100/ 9,000
9,100/ 9,000
12,100/12,000
12,100/12,000
12,100/12,000
12,100/12,000
15,000/14,700
15,000/14,700
15,000/14,700
15,000/14,700

—
7,800/ 6,400
11,600/ 9,700
—
7,800/ 6,400
11,600/ 9,700
—
7,800/ 6,400
11,600/ 9,700
17,000/13,600
—
7,800/ 6,400
11,600/ 9,700
17,000/13,600

—
2.3
3.4
—
2.3
3.4
—
2.3
3.4
5.0
—
2.3
3.4
5.0

12.7/12.7
12.7/12.7
12.7/12.7
11.7/11.9
11.7/11.9
11.7/11.9
11.1/10.7
11.1/10.7
11.1/10.7
11.1/10.7
9.8/ 9.8
9.8/ 9.8
9.8/ 9.8
9.8/ 9.8

POWER
FACTOR
(%)

FAN MOTOR
Full
Indoor
Horsepower Load
CFM
Amps LO/HI**

100

0.075

0.44

220/260

99

0.075

0.44

220/260

99

0.125

0.75

270/350

95

0.125

0.75

250/320

VOLTAGE
RANGE
(Volts)

AMPS

WATTS

Cooling

Heating†

Cooling

Heating

187-253

2.7/2.9
2.7/2.9
2.7/2.9
3.0/3.1
3.0/3.1
3.0/3.1
4.8/5.3
4.8/5.3
4.8/5.3
4.8/5.3
6.4/7.1
6.4/7.1
6.4/7.1
6.4/7.1

—
10.4/ 9.5
15.2/14.1
—
10.4/ 9.5
15.2/14.1
—
10.8/ 9.9
15.6/14.5
22.5/20.0
—
10.8/ 9.8
15.6/14.5
22.5/20.0

567/ 559
567/ 559
567/ 559
778/ 756
778/ 756
778/ 756
1090/1122
1090/1122
1090/1122
1090/1122
1531/1500
1531/1500
1531/1500
1531/1500

—
2393/1985
3493/2935
—
2393/1985
3493/2935
—
2470/2047
3570/2997
5170/4147
—
2470/2047
3570/2997
5170/4147

R-22
CHARGE
(oz)

DEHUMIDIFICATION
(Pints/Hr)

SENSIBLE
HEAT
FACTOR

APPROX.
SHIP WT.
(lb)

24

1.5

0.78

125

23

2.4

0.73

125

34

3.4

0.71

140

32

4.8

0.66

150

MAX.
FUSE
SIZE
(Amps)

MIN.
CIRCUIT
AMPS

RECEPTACLE
TYPE

15
15
20
15
15
20
15
15
20
30
15
15
20
30

4.8
13.0
19.0
5.4
13.0
19.0
8.4
13.3
19.3
27.9
11.1
13.3
19.3
27.9

A
A
B
A
A
B
A
A
B
C
A
A
B
C

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310-93.
†Electric resistance heater power and fan motor power.
**Fan motor indoor CFM (LO/HI) shown for 230-1-60 units.
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

230/208
250/20

250/15

250/30

OUTLET BLADE CONFIGURATION
A
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
HACR
NEMA

LEGEND
— Heating, Air Conditioning, and Refrigeration
— National Electrical Manufacturers Association

*May be used for 15-amp applications if fused for 15 amps.

36

B

C

15

20*

30

2.3

3.4

5.0

PERFORMANCE AND ELECTRICAL DATA
MODEL 52PC AND PE (265-1-60)
52PC performance and electrical data is the same as 52PE without electric heat.
MODEL
NUMBER
52PE
007---4
207---4
307---4
009---4
209---4
309---4
012---4
212---4
312---4
512---4
015---4
215---4
315---4
515---4

MODEL
NUMBER
52PE
007---4
207---4
307---4
009---4
209---4
309---4
012---4
212---4
312---4
512---4
015---4
215---4
315---4
515---4

CAPACITY* (Btuh)
Cooling

Heating

HEATER
kW

EER

7,200
7,200
7,200
9,100
9,100
9,100
12,100
12,100
12,100
12,100
15,100
15,100
15,100
15,100

—
7,800
11,600
—
7,800
11,600
—
7,800
11,600
17,000
—
7,800
11,600
17,000

—
2.3
3.4
—
2.3
3.4
—
2.3
3.4
5.0
—
2.3
3.4
5.0

12.7
12.7
12.7
11.7
11.7
11.7
11.1
11.1
11.1
11.1
10.0
10.0
10.0
10.0

POWER
FACTOR
%

FAN MOTOR
Full
Indoor
Horsepower Load
CFM
Amps LO/HI

97

0.075

0.46

220/260

97

0.075

0.46

220/260

99

0.125

0.71

270/340

100

0.125

0.71

250/320

VOLTAGE
RANGE
(Volts)

AMPS

WATTS

Cooling

Heating†

Cooling

Heating

2.4
2.4
2.4
3.0
3.0
3.0
4.2
4.2
4.2
4.2
5.7
5.7
5.7
5.7

—
9.2
13.3
—
9.2
13.3
—
9.4
13.5
19.6
—
9.4
13.5
19.6

567
567
567
778
778
778
1090
1090
1090
1090
1510
1510
1510
1510

—
2396
3496
—
2396
3496
—
2470
3570
5170
—
2470
3570
5170

239-292

MAX. FUSE
MIN.
RECEPR-22
SIZE
CIRCUIT TACLE CHARGE
(Amps)
AMPS
TYPE**
(oz)
15
15
20
15
15
20
15
15
20
25
15
15
20
25

3.7
11.3
16.5
4.7
11.3
16.5
6.7
11.6
16.7
24.3
8.7
11.6
16.7
24.3

A
A
B
A
A
B
A
A
B
C
A
A
B
C

DEHUMIDI- SENSIBLE APPROX.
CHASSIS
FICATION
HEAT
SHIP WT.
(Pints/Hr)
FACTOR
(lb)

26

1.5

0.78

125

24

2.4

0.73

125

34

3.4

0.71

140

32

5.0

0.66

150

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310-93.
†Electric resistance heater power and fan motor power.
**All 265-v units require an electrical subbase (receptacle or hardwire model).
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

265
277/20

277/15

277/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association

37

B

C

7-15R

7-20R

7-30R

15

20

30

2.3

3.4

5.0

PRODUCT DATA (52C)
PERFORMANCE AND ELECTRICAL DATA
MODEL 52CQ (230/208-1-60)
MODEL
NUMBER
52CQ
207---3
307---3
209---3
309---3
212---3
312---3
512---3
215---3
315---3
515---3

CAPACITY* (Btuh)
AMPS
WATTS
VOLTAGE
HEATER
Heating
EER
COP† RANGE
kW
Cooling
Heating
(Volts) Cooling Heating** Cooling
Rev. Cyc.
Electric
7,000/ 6,900 6,100/ 6,000 7,800/ 6,400
2.3
11.1/11.1 3.1/3.1
3.0/3.2 10.4/ 9.5 631/ 622 2393/1985
7,000/ 6,900 6,100/ 6,000 11,600/ 9,700
3.4
11.1/11.1 3.1/3.1
3.0/3.2 15.2/14.1 631/ 622 3493/2935
9,000/ 8,900 7,900/ 7,800 7,800/ 6,400
2.3
10.7/10.7 3.1/3.1
4.3/4.7 10.4/ 9.5 841/ 832 2393/1985
9,000/ 8,900 7,900/ 7,800 11,600/ 9,700
3.4
10.7/10.7 3.1/3.1
4.3/4.7 15.2/14.1 841/ 832 3493/2935
12,000/11,900 10,800/10,700 7,800/ 6,400
2.3
10.1/10.1 3.0/3.0
5.1/5.5 10.8/ 9.9 1188/1178 2470/2047
187-253
12,000/11,900 10,800/10,700 11,600/ 9,700
3.4
10.1/10.1 3.0/3.0
5.1/5.5 15.6/14.5 1188/1178 3570/2997
12,000/11,900 10,800/10,700 17,000/13,600
5.0
10.1/10.1 3.0/3.0
5.1/5.5 22.5/20.0 1188/1178 5170/4147
14,600/14,300 14,100/13,500 7,800/ 6,400
2.3
9.5/ 9.5 3.0/3.0
6.5/7.1 10.8/ 9.9 1537/1505 2470/2047
14,600/14,300 14,100/13,500 11,600/ 9,700
3.4
9.5/ 9.5 3.0/3.0
6.5/7.1 15.6/14.5 1537/1505 3570/2997
14,600/14,300 14,100/13,500 17,000/13,600
5.0
9.5/ 9.5 3.0/3.0
6.5/7.1 22.5/20.0 1537/1505 5170/4147

FAN MOTOR
MODEL POWER
Full
NUMBER FACTOR
Horsepower Load
52CQ
(%)
Amps
207---3
100
0.075
0.44
307---3
209---3
99
0.075
0.44
309---3
212---3
312---3
99
0.125
0.75
512---3
215---3
315---3
99
0.125
0.75
515---3

Indoor
CFM
LO/HI††

MAX FUSE
MIN.
RECEPR-22
DEHUMIDIFI- SENSIBLE APPROX.
CHASSIS
SIZE
CIRCUIT TACLE CHARGE
CATION
HEAT
SHIP WT.
(Amps)
AMPS
TYPE
(oz)
(Pints/Hr)
FACTOR
(lb)

220/260
220/260

270/350

250/320

15
20
15
20
15
20
30
15
20
30

13.0
19.0
13.0
19.0
13.3
19.3
27.9
13.3
19.3
27.9

A
B
A
B
A
B
C
A
B
C

26

1.5

0.78

125

28

2.4

0.73

125

28

3.4

0.71

140

32

4.6

0.67

150

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††Fan motor indoor CFM (LO/HI) shown for 230-1-60 units.
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

230/208
250/20

250/15

250/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association
*May be used for 15-amp applications if fused for 15 amps.

38

B

C

6-15R

6-20R

6-30R

15

20*

30

2.3

3.4

5.0

PERFORMANCE AND ELECTRICAL DATA
MODEL 52CQ (265-1-60)
MODEL
NUMBER
52CQ
207---4
307---4
209---4
309---4
212---4
312---4
512---4
215---4
315---4
515---4

CAPACITY* (Btuh)
Heating
Cooling
Rev. Cycle Electric
7,000
6,100
7,800
7,000
6,100
11,600
8,900
7,700
7,800
8,900
7,700
11,600
12,000
10,800
7,800
12,000
10,800
11,600
12,000
10,800
17,000
14,600
14,100
7,800
14,600
14,100
11,600
14,600
14,100
17,000

FAN MOTOR
MODEL
POWER
Full
NUMBER FACTOR
Horsepower Load
52CQ
%
Amps
207---4
97
0.075
0.46
307---4
209---4
97
0.075
0.46
309---4
212---4
312---4
99
0.125
0.71
512---4
215---4
315---4
96
0.125
0.71
515---4

Indoor
CFM
LO/HI
220/260
220/260

270/340

250/320

HEATER
kW

EER

COP†

2.3
3.4
2.3
3.4
2.3
3.4
5.0
2.3
3.4
5.0

11.1
11.1
10.7
10.7
10.1
10.1
10.1
9.5
9.5
9.5

3.1
3.1
3.1
3.1
3.0
3.0
3.0
3.0
3.0
3.0

MAX. FUSE
SIZE
(Amps)

AMPS

VOLTAGE
RANGE

Cooling

Heating**

Cooling

Heating

2.6
2.6
3.6
3.6
4.7
4.7
4.7
5.7
5.7
5.7

9.2
13.3
9.2
13.3
9.4
13.5
19.6
9.4
13.5
19.6

631
631
832
832
1188
1188
1188
1537
1537
1537

2396
3496
2396
3496
2470
3570
5170
2470
3570
5170

239-292

MIN.
RECEPR-22
CIRCUIT TACLE CHARGE
AMPS
TYPE††
(oz)

15
20
15
20
15
20
25
15
20
25

11.3
16.5
11.3
16.5
11.6
16.7
24.3
11.6
16.7
24.3

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 380-93.
†Coefficient of Performance (COP) at 47 F outdoor ambient
temperature.
**Electric resistance heater power and fan motor power.
††All 265-v units require an electrical subbase (receptacle or hardwire model).

A
B
A
B
A
B
C
A
B
C

WATTS

DEHUMIDIFICATION
(Pints/Hr)

SENSIBLE APPROX.
CHASSIS
HEAT
SHIP WT.
FACTOR
(lb)

26

1.5

0.78

125

28

2.4

0.73

125

29

3.4

0.71

140

33

4.6

0.67

150

New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

265
277/20

277/15

277/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association

39

B

C

7-15R

7-20R

7-30R

15

20

30

2.3

3.4

5.0

PRODUCT DATA (52C) (cont)
PERFORMANCE AND ELECTRICAL DATA
MODEL 52CE (230/208-1-60)
MODEL
NUMBER
52CE
207---3
307---3
209---3
309---3
212---3
312---3
512---3
215---3
315---3
515---3

MODEL
NUMBER
52CE
207---3
307---3
209---3
309---3
212---3
312---3
512---3
215---3
315---3
515---3

CAPACITY* (Btuh)
Cooling

Heating

HEATER
kW

EER

7,000/ 6,900
7,000/ 6,900
9,000/ 8,900
9,000/ 8,900
12,000/11,900
12,000/11,900
12,000/11,900
14,600/14,300
14,600/14,300
14,600/14,300

7,800/ 6,400
11,600/ 9,700
7,800/ 6,400
11,600/ 9,700
7,800/ 6,400
11,600/ 9,700
17,000/13,600
7,800/ 6,400
11,600/ 9,700
17,000/13,600

2.3
3.4
2.3
3.4
2.3
3.4
5.0
2.3
3.4
5.0

11.1/11.1
11.1/11.1
10.7/10.7
10.7/10.7
10.1/10.1
10.1/10.1
10.1/10.1
9.5/ 9.5
9.5/ 9.5
9.5/ 9.5

POWER
FACTOR
(%)

FAN MOTOR
Full
Indoor
Horsepower Load
CFM
Amps LO/HI**

100

0.075

0.44

220/260

99

0.075

0.44

220/260

99

0.125

0.75

270/350

95

0.125

0.75

250/320

VOLTAGE
RANGE
(Volts)

AMPS

WATTS

Cooling

Heating†

Cooling

Heating

187-253

3.0/3.2
3.0/3.2
4.0/4.3
4.0/4.3
5.4/5.8
5.4/5.8
5.4/5.8
6.4/7.1
6.4/7.1
6.4/7.1

10.4/ 9.5
15.2/14.1
10.4/ 9.5
15.2/14.1
10.8/ 9.9
15.6/14.5
22.5/20.0
10.8/ 9.9
15.6/14.5
22.5/20.0

631/ 622
631/ 622
841/ 832
841/ 832
1188/1178
1188/1178
1188/1178
1537/1505
1537/1505
1537/1505

2393/1985
3493/2935
2393/1985
3493/2935
2470/2047
3570/2997
5170/4147
2470/2047
3570/2997
5170/4147

R-22
CHARGE
(oz)

DEHUMIDIFICATION
(Pints/Hr)

SENSIBLE
HEAT
FACTOR

APPROX.
SHIP WT.
(lb)

21

1.5

0.78

125

28

2.4

0.73

125

29

3.4

0.71

140

32

4.8

0.66

150

MAX.
FUSE
SIZE
(Amps)

MIN.
CIRCUIT
AMPS

RECEPTACLE
TYPE

15
20
15
20
15
20
30
15
20
30

13.0
19.0
13.0
19.0
13.3
19.3
27.9
13.3
19.3
27.9

A
B
A
B
A
B
C
A
B
C

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310-93.
†Electric resistance heater power and fan motor power.
**Fan motor indoor CFM (LO/HI) shown for 230-1-60 units.

New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

230/208
250/20

250/15

250/30

OUTLET BLADE CONFIGURATION
A
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
HACR
NEMA

LEGEND
— Heating, Air Conditioning, and Refrigeration
— National Electrical Manufacturers Association

*May be used for 15-amp applications if fused for 15 amps.

40

B

C

15

20*

30

2.3

3.4

5.0

PERFORMANCE AND ELECTRICAL DATA
MODEL 52CE (265-1-60)
CAPACITY* (Btuh)

MODEL
NUMBER
52CE
207---4
307---4
209---4
309---4
212---4
312---4
512---4
215---4
315---4
515---4

MODEL
NUMBER
52CE
207---4
307---4
209---4
309---4
212---4
312---4
512---4
215---4
315---4
515---4

Cooling

Heating

HEATER
kW

EER

7,000
7,000
8,900
8,900
12,000
12,000
12,000
14,600
14,600
14,600

7,800
11,600
7,800
11,600
7,800
11,600
17,000
7,800
11,600
17,000

2.3
3.4
2.3
3.4
2.3
3.4
5.0
2.3
3.4
5.0

11.1
11.1
10.7
10.7
10.1
10.1
10.1
9.5
9.5
9.5

POWER
FACTOR
%

FAN MOTOR
Full
Indoor
Horsepower Load
CFM
Amps LO/HI

97

0.075

0.46

220/260

97

0.075

0.46

220/260

99

0.125

0.71

270/340

100

0.125

0.71

250/320

AMPS

VOLTAGE
RANGE
(Volts)

239-292

Heating†

Cooling

Heating

2.7
2.7
3.4
3.4
4.7
4.7
4.7
5.7
5.7
5.7

9.2
13.3
9.2
13.3
9.4
13.5
19.6
9.4
13.5
19.6

631
631
832
832
1188
1188
1188
1537
1537
1537

2396
3496
2396
3496
2470
3570
5170
2470
3570
5170

MAX. FUSE
MIN.
RECEPR-22
SIZE
CIRCUIT TACLE CHARGE
(Amps)
AMPS
TYPE**
(oz)
15
20
15
20
15
20
25
15
20
25

11.3
16.5
11.3
16.5
11.6
16.7
24.3
11.6
16.7
24.3

A
B
A
B
A
B
C
A
B
C

WATTS

Cooling

DEHUMIDI- SENSIBLE APPROX.
CHASSIS
FICATION
HEAT
SHIP WT
(Pints/Hr)
FACTOR
(lb)

22

1.5

0.78

125

29

2.4

0.73

125

28

3.4

0.71

140

32

5.0

0.66

150

LEGEND
EER — Energy Efficiency Ratio
*Rated in accordance with ARI Standard 310-93.
†Electric resistance heater power and fan motor power.
**All 265-v units require an electrical subbase (receptacle or hardwire model).
New York City Department of Buildings, Material and Equipment
Acceptance — MEA #242-04-E

RECEPTACLES AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE
OUTLET RATED VOLTS/AMPS

265
277/20

277/15

277/30

OUTLET BLADE CONFIGURATION
A
NEMA CONFIGURATION
TIME DELAY FUSE OR HACR
CIRCUIT BREAKER (AMPS)
HEATER (KILOWATTS)
LEGEND
HACR — Heating, Air Conditioning, and Refrigeration
NEMA — National Electrical Manufacturers Association

41

B

C

7-15R

7-20R

7-30R

15

20

30

2.3

3.4

5.0

EXPANDED RATINGS DATA (52P AND 52C)
COOLING PERFORMANCE
ALL 7000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 260 CFM
TEMP (F) AIR ENT.
COND (40% RH)
80

85

90

95

100

105

110

115

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
7.05
0.54
2.35
6.93
0.56
2.45
6.85
0.59
2.56
6.76
0.61
2.67
6.70
0.64
2.79
6.57
0.67
2.91
6.42
0.70
3.03
6.28
0.73
3.17

EVAP AIR — EWB (F)
62.00
67.00
7.23
8.04
0.54
0.55
2.36
2.37
7.08
7.90
0.57
0.57
2.46
2.48
6.95
7.72
0.59
0.59
2.56
2.58
6.81
7.54
0.61
0.62
2.67
2.68
6.70
7.36
0.64
0.64
2.79
2.79
6.59
7.17
0.67
0.67
2.91
2.91
6.41
6.97
0.70
0.70
3.04
3.03
6.27
6.76
0.73
0.72
3.17
3.17

ALL 9000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 260 CFM
TEMP (F) AIR ENT.
COND (40% RH)

72.00
8.85
0.55
2.39
8.71
0.57
2.49
8.54
0.60
2.59
8.35
0.62
2.89
8.17
0.64
2.80
7.98
0.67
2.92
7.79
0.70
3.03
7.59
0.73
3.16

80

85

90

95

100

105

110

115

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
8.58
0.71
3.14
8.44
0.75
3.28
8.29
0.78
3.44
8.12
0.82
3.59
7.94
0.85
3.74
7.75
0.89
3.89
7.57
0.92
4.06
7.38
0.96
4.24

EVAP AIR — EWB (F)
62.00
67.00
8.91
9.71
0.72
0.71
3.14
3.13
8.72
9.56
0.75
0.74
3.28
3.27
8.52
9.47
0.78
0.78
3.44
3.42
8.30
9.29
0.82
0.81
3.60
3.58
8.07
9.06
0.85
0.85
3.74
3.74
7.84
8.83
0.89
0.89
3.90
3.92
7.60
8.59
0.93
0.93
4.07
4.10
7.38
8.32
0.97
0.97
4.24
4.27

72.00
10.46
0.71
3.12
10.48
0.74
3.27
10.39
0.78
3.41
10.26
0.81
3.56
10.07
0.85
3.72
9.80
0.88
3.89
9.67
0.92
4.06
9.41
0.97
4.24

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

52CQ 12,000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 350 CFM

52PC,PE,CE 12,000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 350 CFM

TEMP (F) AIR ENT.
COND (40% RH)
80

85

90

95

100

105

110

115

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
12.44
1.06
4.65
12.29
1.10
4.85
12.10
1.15
5.05
11.89
1.20
5.26
11.66
1.25
5.48
11.43
1.30
5.70
11.19
1.35
5.94
10.94
1.41
6.18

EVAP AIR — EWB (F)
62.00
67.00
12.74
13.61
1.06
1.05
4.65
4.59
12.51
13.52
1.10
1.09
4.84
4.80
12.29
13.20
1.15
1.13
5.05
4.98
12.01
12.97
1.20
1.18
5.26
5.18
11.73
12.72
1.25
1.23
5.48
5.40
11.48
12.40
1.30
1.28
5.70
5.62
11.23
12.20
1.35
1.33
5.94
5.86
10.98
11.91
1.41
1.39
6.18
6.10

TEMP (F) AIR ENT.
COND (40% RH)

72.00
13.84
1.02
4.48
13.90
1.07
4.69
13.84
1.11
4.91
13.70
1.17
5.12
13.34
1.21
5.31
13.12
1.26
5.52
12.98
1.31
5.76
12.73
1.37
6.00

80

85

90

95

100

105

110

115

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
12.17
1.07
4.73
11.95
1.11
4.93
11.74
1.16
5.14
11.54
1.21
5.36
11.37
1.26
5.58
11.19
1.31
5.81
11.04
1.37
6.06
10.86
1.42
6.31

EVAP AIR — EWB (F)
62.00
67.00
12.50
12.83
1.07
1.05
4.74
4.65
12.35
12.72
1.11
1.10
4.95
4.86
12.10
12.62
1.16
1.15
5.16
5.08
11.90
12.50
1.21
1.20
5.38
5.31
11.68
12.35
1.26
1.25
5.60
5.54
11.47
12.17
1.31
1.30
5.83
5.78
11.28
11.93
1.37
1.35
6.07
6.01
11.02
11.59
1.42
1.41
6.31
6.25

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

42

72.00
13.23
1.03
4.57
13.19
1.08
4.79
13.06
1.13
5.00
12.95
1.17
5.21
12.80
1.23
5.45
12.63
1.28
5.68
12.44
1.33
5.92
12.19
1.39
6.17

COOLING PERFORMANCE (cont)
52PQ 12,000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 350 CFM
TEMP (F) AIR ENT.
COND (40% RH)
80

85
90

95
100

105
110

115

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
11.79
0.97
4.29
11.60
1.02
4.49
11.39
1.07
4.69
11.17
1.12
4.90
11.66
1.17
5.12
12.16
1.22
5.34
12.69
1.27
5.57
13.23
1.32
5.81

EVAP AIR — EWB (F)
62.00
67.00
11.95
12.65
0.97
0.95
4.27
4.17
11.74
12.48
1.02
1.00
4.48
4.38
11.49
12.28
1.07
1.04
4.68
4.59
11.24
12.05
1.12
1.09
4.90
4.80
10.97
11.78
1.17
1.14
5.12
5.02
10.70
11.50
1.22
1.20
5.34
5.25
10.45
11.17
1.27
1.25
5.57
5.48
10.19
10.83
1.32
1.30
5.81
5.72

ALL 15,000 NOMINAL BTUH MODELS
Evaporator entering air temp. — 80 F Evap. air — 320 CFM
TEMP (F) AIR ENT.
COND (40% RH)

72.00
13.17
0.93
4.08
12.97
0.97
4.27
12.79
1.02
4.48
12.58
1.07
4.69
12.33
1.12
4.91
12.04
1.17
5.13
11.75
1.22
5.36
11.39
1.27
5.59

80

85
90

95
100

105
110

115

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I
MBtuh
kW
I

57.00
—
—
—
—
—
—
—
—
—
12.98
1.67
7.32
12.78
1.74
7.63
12.51
1.81
7.95
12.24
1.88
8.27
11.95
1.96
8.62

EVAP AIR — EWB (F)
62.00
67.00
14.77
15.82
1.39
1.36
6.09
6.00
14.55
15.63
1.45
1.43
6.38
6.27
14.20
15.39
1.53
1.49
6.72
6.56
13.85
15.08
1.61
1.56
7.05
6.85
13.51
14.79
1.68
1.63
7.37
7.16
13.03
14.39
1.75
1.70
7.68
7.48
12.54
13.91
1.82
1.78
8.00
7.80
12.05
13.54
1.89
1.85
8.32
8.14

72.00
16.74
1.33
5.85
16.59
1.40
6.14
16.39
1.46
6.43
16.15
1.53
6.73
15.85
1.60
7.03
15.48
1.67
7.35
15.04
1.75
7.67
14.53
1.82
8.00

LEGEND
EWB
— Entering Wet Bulb
I
— Compressor Current Amps
kW
— Total Power
MBtuh — Total Cooling Capacity (Btuh in thousands)
RH
— Relative Humidity
NOTES:
1. Total current (I) based on 230-volt system.
2. Evaporator entering dry bulb air temperature is 80 F.

COOLING SENSIBLE HEAT FACTORS (SHF) AT 80 F INDOOR DB
MODEL
52PC,PE,PQ,CE,CQ
All 7,000
Nominal Btuh
Models
All 9,000
Nominal Btuh
Models
52CQ 12,000
Nominal Btuh
Models
52CE,PC,PE 12,000
Nominal Btuh
Models
52PQ 12,000
Nominal Btuh
Models
All 15,000
Nominal Btuh
Models

INDOOR WB
(F)
57
62
67
72
57
62
67
72
57
52
67
72
57
62
67
72
57
62
67
72
57
62
67
72

80
0.91
0.89
0.71
0.53
0.93
0.86
0.67
0.51
0.94
0.88
0.69
0.50
0.92
0.89
0.68
0.51
0.93
0.89
0.69
0.51
—
0.86
0.67
0.50

85
0.91
0.90
0.72
0.53
0.93
0.87
0.67
0.51
0.94
0.89
0.69
0.51
0.91
0.89
0.69
0.51
0.93
0.90
0.70
0.51
—
0.86
0.67
0.50

LEGEND
DB — Dry Bulb
WB — Wet Bulb

43

OUTDOOR AMBIENT DB TEMPERATURE (F)
90
95
100
105
0.91
0.91
0.91
0.90
0.91
0.91
0.92
0.92
0.72
0.74
0.74
0.75
0.54
0.54
0.54
0.55
0.93
0.93
0.92
0.92
0.88
0.89
0.90
0.91
0.68
0.70
0.70
0.70
0.51
0.51
0.52
0.52
0.94
0.94
0.94
0.94
0.91
0.92
0.93
0.93
0.70
0.70
0.71
0.72
0.52
0.52
0.53
0.53
0.90
0.90
0.90
0.90
0.90
0.90
0.91
0.92
0.70
0.72
0.72
0.73
0.51
0.51
0.52
0.53
0.93
0.93
0.93
0.93
0.91
0.92
0.93
0.93
0.71
0.71
0.72
0.73
0.52
0.52
0.53
0.53
—
0.91
0.91
0.91
0.86
0.87
0.88
0.89
0.68
0.68
0.69
0.70
0.51
0.51
0.51
0.52

110
0.90
0.91
0.76
0.55
0.92
0.92
0.71
0.52
0.94
0.93
0.73
0.54
0.90
0.92
0.74
0.53
0.93
0.93
0.74
0.53
0.91
0.90
0.71
0.52

115
0.90
0.91
0.77
0.56
0.92
0.92
0.72
0.53
0.94
0.93
0.74
0.54
0.90
0.92
0.75
0.54
0.93
0.93
0.75
0.54
0.90
0.91
0.71
0.53

SOUND DATA (52P AND 52C)
INDOOR SOUND DATA
(52P AND 52C)
The tables below indicate the approximate indoor and
outdoor sound levels. Tests were conducted in the
Carrier Sound Testing Laboratory according to
ARI (Air Conditioning and Refrigeration Institute)
Noise Rating Standard 300 for non-ducted indoor airconditioning equipment.
INDOOR SOUND ESTIMATING TABLE
OPERATING
VOLTS
MODE

LOW
COOL
HIGH
COOL

FAN

LOW
HEAT
HIGH
HEAT

208
230
265
208
230
265
208
230
265
208
230
265
208
230
265

INDOOR SOUND ESTIMATING TABLE (dBA)
Nominal Sizes (Btuh)
52PQ and 52CQ
52PC, PE and 52CE
7000 9000 12000 15000 7000 9000 12000 15000
52.6 51.2 55.2
59.3 51.4 54.4 55.4
59.3
54.5 54.2 57.6
59.3 54.4 56.5 57.4
59.3
54.5 53.9 57.6
59.3 54.4 55.4 57.4
59.3
57.1 57.1 61.4
63.7 56.9 58.9 61.8
63.7
57.9 57.8 63.0
63.7 57.9 58.8 63.0
63.7
57.9 58.9 63.0
63.7 57.9 58.3 63.0
63.7
56.3 57.1 61.1
63.7 56.3 57.1 61.1
63.7
57.2 57.7 62.4
63.7 57.2 57.7 62.4
63.7
57.2 57.1 62.4
63.7 57.2 57.1 62.4
63.7
50.7 53.7 55.4
59.5 50.8 50.8 54.5
58.8
53.9 53.8 59.5
59.5 54.1 54.1 57.7
58.8
53.9 53.8 59.5
59.5 54.1 53.6 57.7
58.8
56.5 56.2 61.9
65.0 56.3 57.1 61.1
63.7
57.2 57.8 63.0
65.0 57.2 57.7 62.4
63.7
57.2 57.8 63.0
65.0 57.2 57.1 62.4
63.7

INDOOR SOUND ESTIMATING TABLE (BELS)
Nominal Sizes (Btuh)
52PQ and 52CQ
52PC, PE and 52CE
7000 9000 12000 15000 7000 9000 12000 15000
5.3
5.1
5.5
5.9
5.1
5.4
5.5
5.9
5.5
5.4
5.8
5.9
5.4
5.7
5.7
5.9
5.5
5.4
5.8
5.9
5.4
5.5
5.7
5.9
5.7
5.7
6.1
6.4
5.7
5.9
6.2
6.4
5.8
5.8
6.3
6.4
5.8
5.9
6.3
6.4
5.8
5.9
6.3
6.4
5.8
5.8
6.3
6.4
5.6
5.7
6.1
6.4
5.6
5.7
6.1
6.4
5.7
5.8
6.2
6.4
5.7
5.8
6.2
6.4
5.7
5.7
6.2
6.4
5.7
5.7
6.2
6.4
5.1
5.4
5.5
6.0
5.1
5.1
5.5
5.9
5.4
5.4
6.0
6.0
5.4
5.4
5.8
5.9
5.4
5.4
6.0
6.0
5.4
5.4
5.8
5.9
5.7
5.6
6.2
6.5
5.6
5.7
6.1
6.4
5.7
5.8
6.3
6.5
5.7
5.8
6.2
6.4
5.7
5.8
6.3
6.5
5.7
5.7
6.2
6.4

OUTDOOR SOUND ESTIMATING TABLE
OPERATING VOLTS
MODE

LOW
COOL
HIGH
COOL

FAN

LOW
HEAT
HIGH
HEAT

208
230
265
208
230
265
208
230
265
208
230
265
208
230
265

OUTDOOR SOUND ESTIMATING TABLE (dBA)
Nominal Sizes (Btuh)
52PQ and 52CQ
52PC, PE and 52CE
7000 9000 12000 15000 7000 9000 12000 15000
53.9 52.6 54.9
61.1 51.0 53.1 55.5
61.1
55.3 55.0 57.7
61.1 54.2 56.3 57.7
61.1
55.3 55.0 57.7
61.1 54.2 55.2 57.7
61.1
56.7 57.7 60.1
64.4 56.2 57.6 60.2
64.4
58.9 58.9 62.2
64.4 57.2 58.7 62.6
64.4
58.9 58.1 62.2
64.4 57.2 58.8 62.6
64.4
55.5 57.7 61.3
64.0 55.5 57.7 61.3
64.0
56.4 58.7 63.0
64.0 56.4 58.7 63.0
64.0
56.4 58.7 63.0
64.0 56.4 58.8 63.0
64.0
54.7 54.3 57.8
63.9 51.2 51.2 55.0
58.7
57.6 57.3 59.7
63.9 54.8 54.8 57.9
58.7
57.6 56.6 59.7
63.9 54.8 54.9 57.9
58.7
58.2 59.6 62.2
66.5 55.5 57.9 61.3
64.0
59.9 60.4 63.8
66.5 56.4 58.7 63.0
64.0
59.9 57.8 63.8
66.5 56.4 58.8 63.0
64.0

OUTDOOR SOUND ESTIMATING TABLE (BELS)
Nominal Sizes (Btuh)
52PQ and 52CQ
52PC, PE and 52CE
7000 9000 12000 15000 7000 9000 12000 15000
5.4
5.3
5.5
6.1
5.1
5.3
5.6
6.1
5.5
5.5
5.8
6.1
5.4
5.6
5.8
6.1
5.5
5.5
5.8
6.1
5.4
5.5
5.8
6.1
5.7
5.8
6.0
6.4
5.6
5.8
6.0
6.4
5.9
5.9
6.2
6.4
5.7
5.9
6.3
6.4
5.9
5.8
6.2
6.4
5.7
5.9
6.3
6.4
5.6
5.8
6.1
6.4
5.6
5.8
6.1
6.4
5.6
5.9
6.3
6.4
5.6
5.9
6.3
6.4
5.6
5.9
6.3
6.4
5.6
5.9
6.3
6.4
5.5
5.4
5.8
6.4
5.1
5.1
5.5
5.9
5.8
5.7
6.0
6.4
5.5
5.5
5.8
5.9
5.8
5.7
6.0
6.4
5.5
5.5
5.8
5.9
5.8
6.0
6.2
6.7
5.6
5.8
6.1
6.4
6.0
6.0
6.4
6.7
5.6
5.9
6.3
6.4
6.0
5.8
6.4
6.7
5.6
5.9
6.3
6.4

SOUND TRANSMISSION CLASS (STC) = 25
44

WIRING DIAGRAMS (52P AND 52C)

COMPONENT LEGEND
Component Connection (Marked)

CAP
COMP
FM
FCS
HTR
IT
OFT
OL
PLS
RVS
SLS
ST
SW

—
—
—
—
—
—
—
—
—
—
—
—
—

Component Connection (Unmarked)
Accessory or Optional Wiring
To Indicate Common Potential Only
Not To Represent Wire
Capacitor
Compressor
Fan Motor
Fan Cycle Switch
Heater
Indoor Thermostat
Outdoor Frost Thermostat
Overload
Primary Limit Switch
Reversing Valve Solenoid
Secondary Limit Switch
Start Thermistor
Switch

NOTES:
1. Recommended for use on grounded power supply only.
2. Compressor and fan motor thermally protected.
3. Use copper conductors only.
4. All wiring must conform with N.E.C. and local
codes.
5. Dashed lines indicate components when used.
6. OFT determines whether to bring on compressor heat or electric heat.

52PQ and 52CQ — Typical Wiring Schematic for Standard Heat Pump Units

45

WIRING DIAGRAMS (52P AND 52C) (cont)

TYPICAL THERMOSTAT INTERFACE
T’STAT OUTPUT:
RC CONTROLER OUTPUT:
UNIT OPERATION:
‘G’ — 24 VAC
‘FR’ — LINE VAC
FAN
‘G’ — 0 VAC
‘FR’ — 0 VAC
‘Y’ — 24 VAC
‘HR1 & HR2’ — LINE VAC
HEATING
‘O’ — 0 VAC
‘RVR’ — LINE VAC
‘W’ — 24 VAC
‘HR1 & HR2’ — LINE VAC
HEATING
‘Y’ — 24 VAC
‘CR’ — LINE VAC
COOLING
‘O’ — 24 VAC
‘RVR’ — 0 VAC
‘R’ — 24 VAC
‘R’ — 24 VAC OUTPUT
POWER TO WALL
‘C’ — COMMON
‘C’ — COMMON
THERMOSTAT
1. If ‘W’ is ON, then ‘FR’ is forced ON (regardless of ‘G’) & ‘CR’ is forced OFF.
2. If ‘Y’ is ON, then ‘FR’ is forced ON (regardless of ‘G’).
3. If IFT (indoor coil) is < 20° F, then ‘CR’ is forced OFF until IFT is > 50° F.
COMPONENT LEGEND
Component Connection (Marked)

FM

—

Fan Motor

ST

—

Start Thermistor

Component Connection (Unmarked)

HTR

—

Heater

TRANS

—

Transformer

Terminal Board Connection

IFT

—

Indoor Frost Thermostat

PCBD

—

Printed Circuit Board

Field Splice

OFT

—

Outdoor Frost Thermostat

— HR1

—

Heater Relay

Field Control Wiring

OL

—

Overload

— HR2

—

Heater Relay

Accessory or Optional Wiring

PLS

—

Primary Limit Switch

— CR

—

Compressor Relay

To Indicate Common Potential Only Not To Represent Wire RVS

—

Reversing Valve Solenoid

— FR

—

Fan Relay

— RVR

—

Reversing Valve Relay

CAP

— Capacitor

SLS

—

Secondary Limit Switch

COMP

— Compressor

SSS

—

Speed Selector Switch

NOTES:
1. Recommended for use on
grounded power supply only.
2. Compressor and fan motor
thermally protected.
3. Use copper conductors only.
4. All wiring must conform with
N.E.C. and local codes.
5. Dashed lines indicate components when used.
6. Field control wire suitable for
N.E.C. class 2 control circuit,
at 24 volts.
7. OFT determines whether to
bring on compressor heat or
electric heat.

52PQ and 52CQ — Typical Wiring Schematic for Wall Thermostat Control Heat Pump Units

46

52PE and 52CE — Typical Wiring Schematic for Standard Heat/Cool Units

47

WIRING DIAGRAMS (52P AND 52C) (cont)

52PE and 52CE — Typical Wiring Schematic for Wall Thermostat Control Heat/Cool Units

48

FRONT DESK SWITCH PANEL
ROOM 100

ROOM 101

ROOM N

FIELD-SUPPLIED
24-V
TRANSFORMER
(SEE NOTE 1)

B

W

PTAC #1

AWG
B
PTAC
W

—
—
—
—

B

B

W

W

PTAC #N

PTAC #2

LEGEND
American Wire Gage
Black
Packaged Terminal Air Conditioner
White

NOTES:
1. To size transformer, use the following equation:
Quantity of PTAC units x 12 va = Transformer Size (va)
Example: 110 PTAC Units x 12 va = 1320 va Transformer
2. Following are recommended wire sizes:
AWG WIRE SIZE NO.
MAXIMUM LENGTH (ft)

24
22
20
18
16

400
600
900
1500
2000
Typical Wiring Schematic for Energy Management Kit

49

WIRING DIAGRAMS (52P AND 52C) (cont)
MASTER
PTAC

R

R

Y

Y

W

W

G

G

O

O

C

C

T’STAT

R
UNIT 1

Y
W
G
O
C

R
UNIT 2

Y
W
G
O
C

All units must be connected to same ground source.
To accomplish this, be sure to connect all units to
the same breaker box. Failure to do so may cause
damage to the unit.

R
UNIT 3

Y
W

NOTES:
1. Do not daisy chain R (24 VAC).
2. Maximum of 4 PTAC units can be connected to one single wall
thermostat.
3. Wall thermostat wire is field-supplied and should be 18 to
20 gage solid thermostat wire.

G
O
C

Typical Wiring for Multiple PTAC Units Connected to a Single Wall Thermostat

50

GUIDE SPECIFICATIONS
PACKAGED TERMINAL
COOLING UNIT WITH
HEAT PUMP OR ELECTRIC
HEATING
HVAC Guide Specifications
Size Range:

1.03 DELIVERY, STORAGE, AND HANDLING
A. The packaging of the chassis shall be sufficient to
protect the chassis from damage during shipment
via an enclosed truck. Chassis must also be able to
withstand an impact force of 10 g’s and a random
continuous force of 1g, during shipping.
B. Chassis, wall sleeves, and grilles shall be shipped in
separate cartons. Universal handling instructions
shall be defined and visible on the carton, from
front, back and sides.
C. Chassis shall be capable of withstanding temperatures from –40 F to 155 F, at 5 to 95 percent RH,
non-condensing, during shipment and storage,
without component failure.
D. Unit shall be stored and handled per manufacturer’s
recommendations.

Cooling:
Heating:

6,900 to 15,100 Btuh
6,000 to 14,100 Btuh Heat Pump
6,400 to 17,000 Btuh Electric
Carrier Model Numbers:
52PC Premier Series, Cooling Only
52PE Premier Series, Cooling with Electric
Heat
52PQ Premier Series, Heat Pump with
Electric Heat
52CE Comfort Series, Cooling with Electric
Heat
52CQ Comfort Series, Heat Pump with
Electric Heat

Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece heating and/or
cooling unit. Contained within the unit enclosure
shall be compressor, coils, fans and fan motor, heating means, controls, all wiring and piping, and a
full refrigerant charge (R-22).
Packaged Terminal Air Conditioners shall be of the
sizes and capacities as shown on the contract drawing schedule and in the specifications.
B. Chassis:
The chassis shall be a factory-assembled, singlepiece heating and/or cooling unit, that is simple to
install and operate. Just slide the chassis into a wall
sleeve, plug it into an outlet, and operate after
installation. The chassis dimensions shall not
exceed 42 in. wide and 16 in. high with room cabinet in place. The chassis shall consist of the following functional sections and components:
1. Operating Characteristics:
Chassis shall be capable of starting and running at 115 F ambient outdoor temperature per
maximum load criteria of ARI Standard 310/
380.
2. Electrical:
Chassis shall be equipped with a 58 in. power
cord for 208/230 v models or a 15 in. power
cord for 265 v models. The chassis current
draw shall be specified on the chassis nameplate and match electrical requirements specified on the Contract drawing schedule and
specifications. The power cord plug configuration shall conform to NEMA standards and the
rating shall support the current draw of the
electric resistance heater.
For 265 v installations, UL codes require the
use of an electrical equipped subbase for
power cord usage or hardwire conduit for noncorded installations.
C. Airflow System:
The airflow system shall consist of one permanent
split-capacitor, direct-drive permanently lubricated, two-speed fan motor for the indoor and outdoor fans. The outdoor fan shall be a dynamically
balanced, corrosion-resistant polymer multi-blade

Part 1 — General
1.01 SYSTEM DESCRIPTION
Single piece, thru-the-wall electrically controlled unit
using hermetic rotary compressor for cooling and heat
pump or electric resistance heat, as shown on the contract drawings.
A. Insulated Polymer Wall Sleeve:
Wall sleeve shall provide excellent thermal insulation, be textured to hide scratches and prevent
shine, will have superior outdoor noise absorption
and shall be corrosion free for the life of the product. The Wall Sleeve must have dimensions of
42 in. width x 16 in. height x 147/8 in. depth and be
shipped with a rear weather barrier installed.
B. Wall Sleeve Molding:
Molding shall trim the wall sleeve to the existing
wall, to hide wall imperfections and irregularities in
the wall opening.
C. Outdoor Polymer Louvered Grille:
Outdoor grille shall resist corrosion, breakage and
match the color specified on drawing schedule and
specifications.
D. Subbase:
Subbase will support the wall sleeve when it
extends into the room more than 4 inches. Subbase
must come from the factory pre-assembled, with a
built in receptacle (size as specified on drawing
schedule and specifications) or with factoryinstalled hardwire, pre-sized for an exact fit to the
unit.
1.02 QUALITY ASSURANCE
System shall be approved and certified by UL and
UL, Canada. Chassis capacity and efficiency performance shall be certified in accordance with ARI
standard 310/380. Chassis shall meet ASHRAE
Standard 90.1 for minimum energy efficiency.
Chassis shall meet the New York City Department of
Building, Material and Equipment acceptance requirement (MEA).
51

GUIDE SPECIFICATIONS (cont)

D.

E.

F.

G.

axial flow design, with integrated slinger ring. The
indoor fan shall be a dynamically balanced, polymer, reverse curve blower wheel, to assure uniform
air distribution. The Fan Motor shall be of an
enclosed design to reduce the effects of moisture
and corrosion.
Compressor and Refrigerant:
The rotary-type Compressor shall be fully hermetic
with internal and external vibration isolation. The
refrigeration system will be sealed and contain a
full refrigerant charge (R-22).
Coils:
Condenser and evaporator coils to be constructed of
high-efficiency, 11 element lance sine wave
enhanced aluminum fins and 3/8-in. seamless axial
grooved copper tubing, necessary to achieve
EER and COP rating, as specified on the chassis
nameplate.
Factory-Installed Electric Heater:
The factory-installed, open coil type, electric heater
is standard in heat/cool and heat pump chassis. The
electric heater shall contain both an automatic reset
and a one-shot overtemperature protection device.
The heating capacity of the electric heater shall be
as identified on the Contract drawing schedule and
in the specifications.
Controls:
All standard models shall be equipped with electromechanical controls to simplify the serviceability of
the unit.
1. The chassis shall have standard controls,
accessible and covered by a hinged door. The
mode selection control shall consist of a
mechanical rotary selector switch, which provides OFF, FAN ONLY, HEAT or COOL operations. The temperature selection control shall
be an adjustable thermostat with upper and
lower limits.
2. All standard models shall have a continuous/
fan cycle selector switch located behind the
front panel. It shall allow the selection of continuous fan operation for maximum comfort or
cycle operation (fan only runs with cooling
or heating operation) for maximum energy
savings.
3. All standard models shall have a Temperature
Limiter control located behind the front panel.
The temperature limiter allows a room temperature range to be set, to avoid extreme temperature settings, to maximize energy savings.
4. Emergency Heat Switch (Heat Pump Models
Only) shall disable the compressor in heating
mode and only allow the use of electric
heat during heating cycles. The Emergency
Heat switch is active at all outdoor ambient
temperatures.
5. Wall thermostat chassis (RC and RP models)
shall come from the factory ready for wall
thermostat installation, including a blank out
plate in place of the control knobs. No fieldinstalled kits or wire harnesses shall be
required.
6. Wall thermostat chassis (RC and RP models)
shall have a user selectable fan speed control

H.

I.

J.

K.

L.

M.

N.

O.

52

switch, on the control panel, to optimize fan
speed for maximum comfort.
Safeties:
Compressor shall have automatic reset, overtemperature and overcurrent protection. The fan motor
shall have an inherent, automatic reset overtemperature protection. The electric heater shall have two
overtemperature protectors.
Front Panel (supplied with chassis):
Front panel shall be constructed of a polymer material to resist breakage and corrosion. It shall have a
front louvered surface with integrated control
door and air filters. The air filters shall be easily
accessible without removing the front panel from
the chassis.
Anti-Theft Control Knobs:
All chassis knobs shall resist breakage and corrosion. They shall be mounted on to the control box
section and captured behind the front panel, to prevent unauthorized removal.
Bi-Directional Discharge Grille:
Bi-directional polymer discharge grille shall resist
corrosion and breakage. It shall be easily set to
direct air at 40 degrees from horizontal or
80 degrees from horizontal. This non-metallic discharge grille shall be cool to the touch during the
heating cycle.
Ventilation:
The chassis shall have a manual adjustable fresh air
vent with a concealed manual control. The vent
control shall allow a maximum of 50 cfm of fresh
air to be drawn into the room when the indoor fan is
operating and the door is open. The ventilation air
can be increased to approximately 95 cfm by adding the Booster Ventilation accessory kit (see
section Q.13)
High-Efficiency Condensate Removal System:
The chassis shall have a condensate removal system consisting of a condensate suction port, to draw
and atomize condensate, and a slinger ring integrated in the outdoor fan, to disperse condensate
onto the condenser coil to be evaporated.
Snow Baffle:
The chassis shall contain a snow baffle to prevent
melting snow from freezing and potentially damaging the outdoor fan.
Corrosion Protection (CP and RP Models Only):
Chassis with Corrosion Protection (CP,RP) shall be
used for coastal or corrosive environments, to prolong the life of the product. Minimum requirements
are:
1. All outdoor-exposed sheet metal parts shall be
coated with a polyester powder coat paint.
2. Compressor and outdoor-fan motor finish shall
be capable of withstanding 500 hours of salt
spray testing per ASTM B-117.
3. Compressor mounting screws shall be
SermaGuard™ coated.
4. Outdoor coil fin stock shall be coated and able
to withstand 1000 hours of salt spray testing
per ASTM B-117.
5. Outdoor coil tube sheets shall be made of 316L
stainless steel.

P.

Lateral Duct System (optional):
The lateral duct system shall allow one system to
heat or cool two adjacent rooms, with up to a
maximum of 30% of the discharge air being
diverted to the adjoining room (a return air path
must be provided from the adjoining room). The
lateral duct kit consists of two main components,
the plenum and the extension duct. In addition, the
kit includes an adjustable chassis discharge air
grille, adjustable wall register and decorative wall
molding for duct extension.
The Lateral Duct system shall be adaptable for
either right or left side ducting, with a maximum
duct extension of 4 feet. The duct run must be
straight and horizontal; no bends or turns.
Q. Accessories:
1. Insulated Polymer Wall Sleeve (P/N:
SLEEVE-INSUL-1PK) shall be made from a
molded polymer, with factory-installed Styrofoam insulation and a minimum flammability
rating of UL94-5V. The sleeve surface shall be
textured to prevent shine and hide scratches.
2. Deep Wall Metal Wall Sleeve (up to 28-in.)
(P/N: SLEEVE-EXTxx-1PK) shall be a onepiece, extended wall sleeve, with factory
installed insulation and deep wall baffles
integrated.
3. Sleeve Molding (P/N: SLEEVE-MOLDING)
shall trim the wall sleeve to the existing wall to
hide wall joints and irregularities due to the
sleeve opening.
4. Architectural Grille (P/N: GRILLE-PLAxxxxx or GRILLE-ALU-xxxxx) shall be polymeric for long durable life or painted aluminum for a superior color match to the building.
5. Subbase (P/N: SUBBASE-xxxV-xxA) shall be
pre-assembled from the factory and UL listed.
Subbase options include:
Non-electrical subbase: The non-electrical
subbase shall be pre-assembled and provides
mechanical support and requires no wiring.
Electrical subbase: The electrical subbase
shall be pre-assembled with factory-installed
electrical junction box containing a receptacle
for corded units.
Hardwired subbase: The hardwired electrical
subbase shall be pre-assembled with factory
installed electrical junction box containing
19 in. of flexible conduit (for a perfect fit to the
unit) and all mating connections.
6. Leveling Legs (P/N: LEVELING-LEGS) shall
attach easily to Carrier’s wall sleeve to provide
accurate, adjustable leveling and support to
units without a subbase.
7. Hardwire Kit (P/N: HARDWIRE-KIT) shall
provide a permanent connection to the unit.

8.
9.

10.

11.

12.

13.
14.

15.

16.

17.

53

The hardwire kit mounts on the front right side
of the unit and shall have 36 in. of flexible steel
conduit and a Molex connector for easy
connect/disconnect.
Conduit Interface Kit (P/N: CONDUIT-INTF4PK) shall provide wire connection to the unit
to interface with field-supplied conduit.
Condensate Drain (P/N: DRAIN-KIT-4PK) kit
shall be used internally or externally to route
excess condensate to a drainage system. It can
be field-installed on any Carrier wall sleeve.
The drain kit shall be attached to the exterior
right or left side of the wall sleeve for external
draining or may be mounted to the bottom of
the wall sleeve for internal draining.
Lateral Duct (P/N: LATERAL-DUCT) kit
shall include an adapter plenum, extension
duct, wall register and wall molding. The lateral duct system allows one system to heat or
cool two adjacent rooms, by directing up to
30% of the airflow to the adjacent room. See
section 4.0 for detailed specification.
Energy Management (P/N: EM-KIT) shall
allow individual units to be turned on and off
from a remote location or by a motion sensing
device. This kit interfaces to most energy management systems.
Lateral Air Deflector (P/N: DEFLECTOR1PK) shall allow right or left air distribution
from the chassis. Lateral air deflectors are recommended for units mounted in a corner or
off-center in a room.
Curtain Deflector (P/N: CURTDEL-52CP1PK) shall prevent curtains from being blown
into the discharge air.
Security door (P/N: SECURITY-DOOR) kit
shall prevent unauthorized access to the unit’s
heating and cooling controls and prevents
tampering with units in public locations and
institutions. The security door shall include
two matching keys and keys shall be common
to all Carrier Security Door kits.
Wall Thermostats (P/N: TSTATCCBxx01-B)
shall operate with 24 VAC, be digital and
non-programmable, easy-to-use and provide
maximum guest comfort.
Sleeve Molding (P/N: SLEEVE-MOLDING)
shall trim the wall sleeve to the existing wall to
hide wall joints and irregularities due to the
sleeve opening.
Power Fresh Air Vent (P/N: PWR-VENTDOORxxx) kit shall provide approximately
95 cfm of outdoor air for ventilation into the
room. The kit shall have an automatically door
that opens when the fan is on and closes when
the fan is off.

54

NOTE: Service and Maintenance items excluded in this warranty may be covered by
a separate service agreement through the seller at time of purchase.

CARRIER WILL NOT BE RESPONSIBLE FOR:
1. CLEANING REQUIRED PRIOR TO WARRANTY REPAIR.
2. Standard maintenance, cleaning or damage resulting from failure to perform
normal maintenance as outlined in the owner’s manual.
3. Instruction on methods of control and use of air conditioning unit after initial
installation.
4. Damage or repairs needed as a consequence of faulty installation or application. This is the responsibility of the installer.
5. Failure to start due to voltage conditions, blown fuses, open circuit breakers
or any other damages due to the inadequacy or interruption of electrical
services.
6. Damage or repairs needed as a consequence of any misapplication, abuse,
unauthorized alteration, improper servicing or operation.
7. Damage as a result of floods, winds, fires, lightning, accidents, corrosive
environment, or other conditions beyond the control of CARRIER.
EXCEPTION TO CORROSIVE ENVIRONMENT IN ABOVE PARAGRAPH —
Packaged terminal units (52 Series) built with corrosion protection are exempt
from the exclusion — “Corrosive Environment.” The unit model number is
identified on the nameplate with a CP suffix.
8. Reimbursement for replacement parts or repair services which are not supplied or designated by CARRIER and which are specifically covered under
this warranty.
9. CARRIER products installed outside the continental U.S.A., Alaska, Hawaii
and Canada.
10. Shipping damage or damage as a result of transporting the unit. This is the
responsibility of the selling dealer or the authorized Room Air Conditioner
service station.
11. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE WHATSOEVER. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so
the above limitation or exclusion may not apply to you.
12. Warranty coverage of accessory items (wall thermostats, wall sleeves, etc.).

Catalog No. 530-122 (Rev. 3/02)

This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

*Authorized independent dealers or service stations are registered with Carrier Air Conditioning through its distributor organization.

ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED
DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER
NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY
THE REMAINING TIME PERIOD OF THIS WARRANTY.

LIMITATION OF WARRANTIES — ALL IMPLIED WARRANTIES (INCLUDING
IMPLIED WARRANTIES OF MERCHANTABILITY) ARE HEREBY LIMITED IN
DURATION TO THE PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN
AND APPLIES. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG
AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY
TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE
EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY
DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER.

LIMITED EXTENDED FOUR-YEAR WARRANTY ON NON-SEALED REFRIGERATION SYSTEM ONLY — During the second through fifth years after date of original purchase, Carrier will, through its authorized servicing dealers and service
stations and free of charge to the end user or subsequent users, repair or replace
any non-sealed system part (motor, solenoid, thermistor, thermostat, relays, switch,
capacitor, overload, drain valve, bulb heater, fan, stator) if defective in material or
workmanship. The replacement part can be new or a remanufactured part at
CARRIER’S sole option. THIS LIMITED WARRANTY DOES NOT INCLUDE
LABOR, user is responsible for labor, including cost of diagnosis of problem,
removal and transportation of the air conditioner to and from the service center, and
reinstallation charges necessary to accomplish repair.

FULL EXTENDED FOUR-YEAR WARRANTY ON SEALED REFRIGERATION
SYSTEM ONLY — During the second through fifth years after date of original purchase, CARRIER will, through its authorized servicing dealers and service stations*
and free of charge to the end user or subsequent users, repair or replace the
compressor, condenser, evaporator or connecting tubing if defective in material or
workmanship. This includes system refrigeration charge. The replacement part can
be new or a remanufactured part as provided at CARRIER’S sole option.

FULL ONE-YEAR WARRANTY — During the first year after purchase, CARRIER
will, through its authorized independent servicing dealers or service stations*, and
free of charge to the user or subsequent users, repair or replace any parts which
are defective in material or workmanship. The replacement part can be a new or
remanufactured part as provided at CARRIER’S sole option.

Carrier
Packaged Terminal
Air Conditioner Warranty

TYPICAL WARRANTY

55

2. CONTACT YOUR DEALER OR THE RECOMMENDED
CARRIER AUTHORIZED SERVICE CENTER. They have been set up
to handle the great majority of all possible service problems. The
quickest, surest and best way to get your air conditioner back in
service is to use this step before proceeding further.

1. CHECK THE THINGS YOU CAN DO YOURSELF. These include
being sure the air conditioner is plugged in firmly in an appropriate
receptacle, checking the fuse or circuit breaker and ensuring its replacement or resetting, if necessary, and rereading the instruction
book to ensure that all controls are set properly. By doing this you
can save money. Many unnecessary service calls result in the
serviceman doing what the owner can do for him or herself.

4. CONTACT CARRIER IF A SATISFACTORY SOLUTION IS NOT
REACHED IN STEPS 2 AND 3.
Carrier Air Conditioning
Consumer Relations Department
Carrier Parkway, P.O. Box 4808
Syracuse, New York 13221
Telephone: 1-800-894-6449

3. CONTACT THE CARRIER DISTRIBUTOR SERVING YOUR AREA.
Your dealer can provide the distributor’s name or you can consult your
yellow pages.

IF YOUR AIR CONDITIONER DOES NOT WORK, FOLLOW THESE STEPS IN ORDER:

Carrier Corporation

ACCESSORY LIST
ACCESSORY
Wall Sleeves

Exterior Grilles*

FORM NUMBER
PART NUMBER
52S-48SI
WALL-SLEEVE-1PK
WALL-SLEEVE-9PK
SLEEVE-INSUL-1PK
52S-50SI
SLEEVE-STEEL-1PK
52S-49SI
SLEEVE-EXT18-1PK
SLEEVE-EXT24-1PK
SLEEVE-EXT26-1PK
SLEEVE-EXT28-1PK
N/A
SLEEVE-MOLDING
52C,P-26SI
FR-SLEEVE-EXT
52C,P-28SI
52S-59SI

52C,P-29SI
52C,P-11SI

CM-SLEEVE-EXT
GRILLE-ALU-STAMP
GRILLE-PLA-BROWN
GRILLE-PLA-BEIGE
GRILLE-PLA-ALPIN
GRILLE-ALU-CLEAR
GRILLE-ALU-WHITE
GRILLE-ALU-BRONZ
GRILLE-ALU-MBRNZ
GRILLE-ALU-BROWN
GRILLE-ALU-BEIGE
GRILLE-ALU-ALPIN
GRILLE-ALU-PEACH
GRILLE-ALU-MELON
GRILLE-ALU-LGREY
GRILLE-ALU-SGREY
GRILLE-ALU-RDBRK
GRILLE-ALU-BLUE
GRILLE-ALU-GREEN
BAFFLE-KIT-1PK
SUBBASE-NON-ELEC
SUBBASE-230V-15A
SUBBASE-230V-20A
SUBBASE-230V-30A
SUBBASE-265V-15A
SUBBASE-265V-20A
SUBBASE-265V-30A
SUBBASE-HARDWIRE
SUBBASE-SWITCH
SUBBASE-FUSE-15A
SUBBASE-FUSE-20A
SUBBASE-FUSE-30A
LEVELING-LEGS
HARDWIRE-KIT-1PK

52C,P-19SI

CONDUIT-INTF-4PK

52S-53SI

DRAIN-KIT-4PK

N/A

HH01AD045
TSTATCCBPC01-B
TSTATCCBPH01-B
TSTATCCPAC01-B
TSTATCCPHP01-B
RC-FIELDKIT230HC

52S-65SI
52S-60SI

Subbase

52C,P-31SI
52C,P-1SI
52C,P-2SI

52C,P-17SI

Subbase
Field-Installed
Kits
Sleeve Support
Electrical
Connections

Condensate
Drain Kit
Wall
Thermostats

52C,P-3SI
52C,P-4SI
52C,P-5SI

DESCRIPTION
Non-Insulated Polymer Wall Sleeve, 1 per pack
Non-Insulated Polymer Wall Sleeve, 9 per pack
Insulated Polymer Wall Sleeve, 1 per pack
Insulated Metal Wall Sleeve, 1 per pack
Extended Metal Wall Sleeve for Deep Wall Applications (18 in. deep), 1 per pack
Extended Metal Wall Sleeve for Deep Wall Applications (24 in. deep), 1 per pack
Extended Metal Wall Sleeve for Deep Wall Applications (26 in. deep), 1 per pack
Extended Metal Wall Sleeve for Deep Wall Applications (28 in. deep), 1 per pack
Molding kit to trim the wall sleeve to the wall
Friedrich wall sleeve extension to retrofit Carrier PTAC unit into Friedrich 111/2″ deep
(T Series) wall sleeve. 1 per pack
Climate Master Wall Sleeve extension to retrofit Carrier PTAC unit into Climate Master 121/2″ deep wall sleeve. 1 per pack
Stamped Aluminum Exterior Grille, Clear Finish
Polymer Architectural Rear Grille, Brown
Polymer Architectural Rear Grille, Beige
Polymer Architectural Rear Grille, Alpine (matches Carrier Wall Sleeve)
Aluminum Architectural Exterior Grille, Clear Finish
Aluminum Architectural Exterior Grille, White
Aluminum Architectural Exterior Grille, Light Bronze
Aluminum Architectural Exterior Grille, Medium Bronze
Aluminum Architectural Exterior Grille, Brown (Dark Bronze)
Aluminum Architectural Exterior Grille, Beige
Aluminum Architectural Exterior Grille, Alpine (matches Carrier Wall Sleeve)
Aluminum Architectural Exterior Grille, Peach
Aluminum Architectural Exterior Grille, Melon
Aluminum Architectural Exterior Grille, Light Grey
Aluminum Architectural Exterior Grille, Slate Gray
Aluminum Architectural Exterior Grille, Red Brick
Aluminum Architectural Exterior Grille, Blue
Aluminum Architectural Exterior Grille, Green
Ensures good air seal and prevents air recirculation when Carrier sleeve is used with a non-Carrier grille.
Non-electrical Subbase
Electrical subbase with factory-installed 208/230V, 15 amp receptacle
Electrical subbase with factory-installed 208/230V, 20 amp receptacle
Electrical subbase with factory-installed 208/230V, 30 amp receptacle
Electrical subbase with factory-installed 265V, 15 amp receptacle
Electrical subbase with factory-installed 265V, 20 amp receptacle
Electrical subbase with factory-installed 265V, 30 amp receptacle
Electrical subbase with factory-installed hardwire kit (230/208V and 265V)
Field-Installable Switch kit for an electrical subbase
Field-Installed Fuse Kit (15 amp) for electrical subbase
Field-Installed Fuse Kit (20 amp) for electrical subbase
Field-Installed Fuse Kit (30 amp) for electrical subbase
Attaches to wall sleeve for accurate and adjustable leveling and support for units without a subbase
Permanent power connection to the unit (includes 36″ of flexible conduit and unit-mounted
connector, 230/208V and 265V) 1 per pack
Interface kit for field-supplied conduit to provide permanent power connection
(230/208V and 265V) to the unit. Kit includes Molex connector for easy connect/disconnect.
4 per pack
Attaches to wall sleeve for controlled internal or external disposal of condensate-4 per pack

N/A

2SPEED-TSTAT-KIT
2SPEED-RCFAN-KIT
TSTAT-COVER-6X7

N/A

TSTAT-COVER-7X10

Replacement
Filters
Energy
Management
Locking Security
Control Door
Lateral Duct Kit
Power Vent
Retrofit Kit
Air/Curtain
Deflector

N/A

AIR-FILTER-10PK

Electro-mechanical Wall Thermostat (Heat/Cool and Heat Pump)
Value Series Electronic Thermostat w/Digital display (Heat/Cool Models)
Value Series Electronic Thermostat w/Digital display (Heat Pump Models)
7-Day Programmable Electronic Thermostat (Heat/Cool Models)
7-Day Programmable Electronic Thermostat (Heat Pump Models)
Field-installed wall thermostat retrofit kit to convert a standard 230V Heat/Cool unit to an
RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
Field-installed wall thermostat retrofit kit to convert a standard 230V Heat Pump unit to an
RC unit. Wall thermostat sold separately.
Field-installed wall thermostat retrofit kit to convert a standard 265V Heat/Cool unit to an
RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC).
Field-installed wall thermostat retrofit kit to convert a standard 265V Heat Pump unit to a
RC unit. Wall thermostat sold separately.
Field-installed automatic heat/cool changeover thermostat with 2-speed fan control at thermostat.
Multiple fan speed control relay only. Thermostat is not included.
Clear plastic locking thermostat cover prevents unauthorized access to thermostat.
Cover for use with non-programmable and electro-mechanical thermostats.
Outside dimensions: 61/2″ x 71/2″ x 215/16″. 1 per pack
Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for
use with programmable thermostats. Outside dimensions: 71/4″ x 93/4″ x 33/8″. 1 per pack
Replacement air filters in package of 10

52C,P-24SI

EM-KIT

Allows unit to be turned on and off from a remote location (includes freeze guard protection)

52C,P-23SI

SECURITY-DOOR

Key-locking security door to prevent access to heating and cooling controls

52C,P-25SI
52C,P-32SI
52C,P-9SI
52C,P-21SI

LATERAL-DUCT
PWR-VENT-DOOR230
PWR-VENT-DOOR265
DEFLECTOR-1PK
CURTDFL-52CP-1PK

Touch-Up Paint

N/A

CARRIER-TOUCH-UP

Ductwork to allow one unit to heat and cool two rooms (plenum plus extension duct and registers)
Power vent with automatic door that opens and closes when the fan turns on and off (230V).
Power vent with automatic door that opens and closes when the fan turns on and off (265V).
Lateral air deflector, with individually adjustable louvers, to enhance air circulation, 1 per pack
Curtain deflector for 52C and 52P models — prevents curtains from blowing into
discharge air stream. 1 per pack.
NOTE: Curtain deflector for previous models are also available. Contact Carrier Representative.
Touch up paint for repainting scratches or chips.

Wall Thermostat
Interface
Retrofit Kit

52C,P-30SI

RC-FIELDKIT230HP
RC-FIELDKIT265HC
RC-FIELDKIT265HP
52C,P-34SI

*Custom colors are also available.

56



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : 3.1-701
Create Date                     : 2003:05:29 16:20:08Z
Creator Tool                    : ADOBEPS4.DRV Version 4.20
Modify Date                     : 2005:11:09 18:52:23-05:00
Metadata Date                   : 2005:11:09 18:52:23-05:00
Format                          : application/pdf
Creator                         : Carrier Corporation
Title                           : 
Description                     : 
Subject                         : 
Producer                        : Acrobat Distiller 4.0 for Windows
Keywords                        : 
Document ID                     : uuid:3659d114-2f7a-47a1-89ae-0a92e7002ab4
Instance ID                     : uuid:3eab78a6-ad9c-4321-88e9-e17456fca344
Page Count                      : 56
Author                          : Carrier Corporation
EXIF Metadata provided by EXIF.tools

Navigation menu