Carrier 592 085 Users Manual
592-085 to the manual 39556ba7-5f45-4d63-b263-7ecb587257c2
2015-01-24
: Carrier Carrier-592-085-Users-Manual-310448 carrier-592-085-users-manual-310448 carrier pdf
Open the PDF directly: View PDF .
Page Count: 56
Download | |
Open PDF In Browser | View PDF |
ARCHITECTS AND ENGINEERS’ MANUAL PREMIER SERIES 52P COMFORT SERIES 52C PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS CONTENTS Page Page APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4 Seamless Basepan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Condensate Drain Valve. . . . . . . . . . . . . . . . . . . . . . . . 11 Condensate Removal System. . . . . . . . . . . . . . . . . . . . 11 Heat Pumps Pay Their Own Way. . . . . . . . . . . . . . . . . 12 Heat Pump Energy Savings . . . . . . . . . . . . . . . . . . . . . 13 ORDERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Product Catalog Number . . . . . . . . . . . . . . . . . . . . . . . 14 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . 15 FIELD-INSTALLED ACCESSORIES . . . . . . 16-26 New Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Retrofit/Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Carrier Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Application Considerations . . . . . . . . . . . . . . . . . . . . . . 4 PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . 5 PRODUCT FEATURES AND BENEFITS . . . . 6-13 Quiet Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Most Efficient Performance . . . . . . . . . . . . . . . . . . . . . . 6 Efficient Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 No-Rust Weather Last™ Wall Sleeve and Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Removable Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . 7 Anti-Theft Knobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Two-Piece Lifetime Indoor Filter . . . . . . . . . . . . . . . . . . 8 Washable Vent Air Filter . . . . . . . . . . . . . . . . . . . . . . . . 8 Bi-Directional Discharge Grille . . . . . . . . . . . . . . . . . . . 8 Power Cord for 265-V Units . . . . . . . . . . . . . . . . . . . . . 9 Power Cord Protection for 230/208-V Units . . . . . . . . . 9 Bi-Molded Condenser Shroud . . . . . . . . . . . . . . . . . . . . 9 Snow Baffle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Easy Access to Chassis. . . . . . . . . . . . . . . . . . . . . . . . . 10 Hidden Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Enhanced Copper Tubing . . . . . . . . . . . . . . . . . . . . . . . 11 DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION. . . . . . . . . . . . . . . . . . . . . . . . . 27-33 PRODUCT DATA . . . . . . . . . . . . . . . . . . . . . . . . . 34-41 EXPANDED RATINGS DATA. . . . . . . . . . . . . . .42,43 SOUND DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . 45-50 52PQ and 52CQ . . . . . . . . . . . . . . . . . . . . . . . . . . . .45,46 52PE and 52CE . . . . . . . . . . . . . . . . . . . . . . . . . . . .47,48 Energy Management/Front Desk Control . . . . . . . . . . 49 Single Thermostat/Multiple PTAC Units . . . . . . . . . . . 50 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . 51-53 TYPICAL WARRANTY . . . . . . . . . . . . . . . . . . . .54,55 ACCESSORY LIST . . . . . . . . . . . . . . . . . . . . . . . . . . 56 For more information available on the internet, see the www.carrier.com or www.lodgingAC.com web sites. December 2004 Copyright Carrier Corporation Cat. No. 592-085 Valued Carrier Customer, Carrier’s Architects and Engineer’s manual has been specifically developed to make your product and accessory selection easier and faster. This manual will help you customize your application to ensure the greatest comfort for your guests and the highest reliability and lowest costs for you. Enjoy the ultimate in comfort, humidity control, and energy savings with Carrier’s complete line of Packaged Terminal Air Conditioning (PTAC) products. Choose from either the Premier series (52P) which is Carrier's most energy efficient PTAC unit ever, or the Comfort series (52C) for mid-range energy efficiency and outstanding value. The Premier and Comfort series PTAC lines have many common features and benefits. The 52P and 52C units are both built on the same platform with common components and airflow systems to ensure the highest quality product for your money. The most significant difference between the 52P and 52C products is the refrigerant system. The Premier refrigerant system utilizes Carrier's highest efficiency compressors and coil design to achieve maximum energy efficiency. The Comfort refrigerant system uses our standard efficiency compressors and coils to attain competitive efficiency levels which exceed the industry standard ARI minimum-efficiency levels. It’s your choice. Choose the Premier series and start recovering your investment immediately through energy savings, or choose our Comfort series and enjoy years of economical, trouble-free operation and comfort. Thank you for choosing Carrier and investing in the highest quality air conditioning and heating system ever. Best regards, Lodging Products Group 2 APPLICATIONS Whether you are designing a new structure or replacing packaged terminal air conditioning units in an existing building, Carrier will meet your needs. • Hotels and motels • Nursing homes and assisted living care centers • Offices • Apartments • Single-family dwellings • Home conversions and residential add-ons Lower Operating Costs And Reliable Comfort For The Occupant • Heat pump models offer substantial savings over models with conventional electric resistance heaters • Individual units allow tenants to choose the degree of comfort and operating economy. • Rapid servicing reduces downtime: complete chassis can be replaced in minutes without disrupting other occupants. • Each unit operates independently of other units in the building. No dependency by building on central HVAC system. NEW CONSTRUCTION The Carrier 52P and 52C Packaged Terminal Air Conditioning (PTAC) unit is designed to meet the needs of the architect, engineer, and contractor. For unit installation, Carrier’s expert support network will assist in all applicable aspects of the construction project, from preparing a budget to start-up. ADVANTAGES FOR NEW CONSTRUCTION Design Flexibility For The Architect/Engineer • Super-quiet performance, indoors and out • No bulky duct system • No separate equipment room • No water towers or additional cooling equipment • No complex match-up of different HVAC components • Less sensitivity to building orientation (sun, wind, shade) • Optional architectural grille to permit custom exterior appearance Initial Cost Savings For The Building Owner • No expensive component HVAC system purchase • No equipment room or maintenance engineering staff • Two-part delivery to minimize on-site damage • Weather-protected wall sleeve that goes in place during construction; chassis that slides in place after construction • No seasonal changeover required for cooling or heating — units are self-contained comfort systems RETROFIT/REPLACEMENT If you are replacing a unit in an existing wall sleeve, your options include: • Replace the existing wall sleeve with a Carrier Weather Last™ sleeve. See accessory sleeve section for selecting the correct sleeve for your application. Note, in most cases, when replacing the wall sleeve, the exterior grille must also be replaced. • Use an existing sleeve and exterior grille. The Carrier 52P and 52C series PTAC will fit into most major competitors wall sleeves/grilles, including GE, Amana, Trane, Bryant, Carrier 52S and Carrier 52B, and NO accessory retrofit kit is required. Carrier units will also retrofit into Friedrich T series and ZoneAire wall sleeves, with a required wall sleeve extension (see accessory Friedrich Retrofit Wall Sleeve Adapter). IMPORTANT: All other sleeve or exterior grille retrofit applications need prior approval from Carrier. Please contact your Carrier representative for assistance. CARRIER WARRANTY Carrier’s five-year warranty is the most comprehensive in the industry. Carrier provides: • Full coverage for parts and labor for first year. • Four additional years of full coverage on sealed refrigeration systems. • Limited second through fifth year coverage on nonrefrigeration system parts. 3 APPLICATIONS (cont) APPLICATION CONSIDERATIONS Oversizing If a PTAC unit is oversized (cooling capacity is greater than required capacity for the specific application), the unit will cool the space down to the desired temperature too quickly. The unit will cycle on and off, however, dehumidification only takes place when the unit is operating. The result of this type of application in a hot and/or humid climate would be a cool, yet excessively humid, space. Installation instructions are shipped with all PTAC units. It is important that air conditioning systems be properly sized and installed for each application in order to achieve the desired temperature and humidity levels within the space to be conditioned. It is strongly recommended that a professional engineer match the PTAC units with the building structure and climate. The following application considerations are all important in choosing the proper PTAC system for the building structure. Air Infiltration Excessive air infiltration can intensify problems associated with undersizing or oversizing a PTAC unit. This can be the cause of insufficient cooling, dehumidification, or heating. Sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floors, ceilings or wall joints. Undersizing If a PTAC unit is undersized (cooling capacity is less than required capacity for an application), the unit will not be able to cool the space down to the desired temperature during very hot days. The result could be warm and humid or warm and dry conditioned space. 4 PRODUCT OVERVIEW (52P AND 52C) This section summarizes product features covered in detail in later sections of this manual: 2 AIR FILTERS 2-WAY DISCHARGE GRILLE WIRE SCREEN FRESH AIR CONTROL ARM THERMOSTAT WITH TEMPERATURE LIMITER BI-MOLDED CONDENSER SHROUD MODE SELECTION SWITCH COPPER TUBE ALUMINUM FIN COILS ROTARY COMPRESSORS TEST ING DO 1.PRE 2.PLU SS RESE G RECE INTO T BUTT 3.PRE PTAC POWE ON. R LE. SHOUSS TEST 4. PRES LD BUTT LIGHT ON FOR S RESE . UNIT T BUTT NOT USE. USE ON AGAIN IS TEST ABOV E FAILS LOUVERED FRONT PANEL CONTROL DOOR ACCESS TO ELECTRICAL INDOOR COMPONENTS THROUGH BASEPAN FOR CONTROL BOX DOOR COIL CONDENSATE REMOVAL PLUG TEST/ RESET BUTTONS WALL SLEEVE Polymer, Metal or Extended Wall Sleeve — Designed for rugged duty, acoustic absorption, and attractive appearance for years to come. Rotary Compressors — Provide quiet, reliable operation. Copper Tube Aluminum Fin Coils — Enhanced coils provide durability, high performance, and ease of operation. Fresh Air Control Arm — Allows outdoor air into room through vent filter for improved air quality. Fan Cycle Switch — Dual options: (1) Continuous fan operation. (2) Cycle fan ON and OFF with compressor operation. Thermostat with Temperature Limiter — Provides improved temperature control with a temperature limiter that allows temperature range restraints for the unit by making a simple adjustment. Anti-Theft Knobs — Provides protection against theft of the thermostat knob and the mode selection knob. Control Door — Provides protection for controls and enhances appearance. Easy Access to Electrical Components — Simply remove two screws and drop down the control box door. Improved Condensate Removal — Minimizes condensate water on outside of building. New Two-Piece Filter Design — Provides improved air filtration and can be removed easily for cleaning. Durable Discharge Grille — Made of polycarbonate; holds up under the toughest conditions. Louvered Front Panel — Made of high impact polystyrene. Provides improved performance and quiet operation. Mode Selection Switch — Rotary switch allows for easy selection of operating mode. Bi-Molded Condenser Shroud — The two-piece condenser shroud allows easy access for service and maintenance to the outdoor coil and other components. Power Cord Protection — Power cord for the 230/208-v unit provides power cord protection. 5 PRODUCT FEATURES AND BENEFITS (52P AND 52C) The 52P and 52C models are a single-package, through-the-wall unit for heating and cooling hotel rooms, offices, apartments, condominiums, and residential additions. Features include: • Improved sound quality for quiet operation • Exceeds ARI (Air Conditioning and Refrigeration Institute) efficiency requirements with exceptional energy efficiency ratios (EERs) • Easy access, lifetime filters • User friendly controls • Easy to read dials • Enhanced temperature and humidity control • Improved condensate removal system • Multi-room structure design • Fixed wall sleeve, slide-out chassis • Attractive, durable cabinet featuring new design • Chassis that easily retrofits to most major competitors’ sleeves without use of retrofit kit • Low operating costs • No bulky duct system • No seasonal changeover The new aerodynamic split condenser shroud design improves airflow and reduces outdoor noise, providing a more relaxing outdoor environment. The new split design allows for easy access to the outdoor coil to facilitate routine cleaning of the coil. The propeller-type fan design allows for efficient low-speed operation. MOST EFFICIENT PERFORMANCE High EERs provide excellent operating economy. The system operates without bulky ductwork, separate equipment room, and complex match-up of different components. Heating and Cooling modes are available without seasonal changeover. EFFICIENT FAN MOTOR An efficient, totally enclosed PSC (permanent split capacitor) fan motor provides a choice of high or low speeds for heating and cooling. A fan-only setting provides air circulation. The fan motor requires no maintenance and no lubrication. QUIET OPERATION Occupants and neighbors are protected against noise intrusion. Indoor sound reduction is achieved because of the unit’s design and its louvered front cover, indoor scroll and blower, and heavy gage unit partition. Rotary compressors provide quiet, reliable operation. The indoor scroll provides a more uniform air discharge. 6 NO-RUST WEATHER LAST™ WALL SLEEVE AND FRONT PANEL The indoor front panel and polymer wall sleeve use nonmetallic compounds that never rust or corrode, do not support combustion, and do not give off toxic fumes. The weather-resistant feature exceeds requirements of Underwriters’ Laboratories and resists damage caused by impact and scratching. The Weather Last feature also insulates and has up to 10 times the acoustic absorption of metal cabinets. Insulated polymer wall sleeves combine all of the above features with factory-installed insulation. The insulation helps to reduce heat loss, save energy, provide better sound absorption, and reduce the risk of sleeve sweating. Carrier’s metal wall sleeves are available in a variety of sizes for most standard and deep wall applications. All metal wall sleeves come with factory-installed insulation, designed to minimize heat loss and reduce outdoor noise transmissions into the room. Standard Wall Sleeve (Polymer) 42 in. 16 in. 14/18/24/26/28 in. Standard and Deep Wall Sleeve (Metal) REMOVABLE FRONT PANEL The louvered front panel fits firmly onto the chassis and features easy removal for service. It provides front air intake to enhance performance and quiet operation. It also allows the option of flush mounting PTAC unit to the floor. If desired, the front panel can be secured to the unit with field-supplied screws. The 2 locking screws (if installed) are located behind the removable filter handles. REMOVABLE FILTER LOCATION OF REMOVED FILTER LOCKING SCREW (NOTE: 2nd LOCKING SCREW IS LOCATED BEHIND 2nd FILTER) Removable Front Panel MODE TEMPERATURE ANTI-THEFT KNOBS OFF The anti-theft knobs are captured underneath the front panel of the unit to prevent the knobs from being removed or stolen. LO LO HI HI WARMER COOLER HEAT FAN COOL Anti-Theft Knobs 7 PRODUCT FEATURES AND BENEFITS (cont) TWO-PIECE LIFETIME INDOOR FILTER New two-piece removable filters easily slide in and out from the front of the PTAC unit and are interchangeable. The front panel does not need to be removed to access or change the filters. The filters are washable and permanent. Two-Piece Indoor Filter WASHABLE VENT AIR FILTER The unique vent system is activated by a two-position control. Fresh outside air is redirected by the vent door to an inside low-pressure area. A molded plastic filter prevents dirt and debris from entering the room side of the unit. The vent mechanism is made from noncorrosive material ensuring reliable operation. A magnet on the door and high-pressure airflow create a tight, draftfree seal when the vent door is closed. The vent will provide 50 cfm of fresh air. NOTE: If more fresh air cfm is required, a Power-Vent Kit is available (see accessories). Outdoor Vent Filter Location BI-DIRECTIONAL DISCHARGE GRILLE 40 DEGREE AIR FLOW 80 DEGREE AIR FLOW The discharge grille is constructed of durable polycarbonate and is reversible. Air flows upward at a 40 degree angle to the floor but can easily be adjusted to an 80 degree angle to the floor. Reversible Polycarbonate Discharge Grille 8 POWER CORD FOR 265-V UNITS A power cord is included for 265-v units. The power cord is 18 in. long (cord extends 15 in. from bottom of front panel) and per UL and National Electrical codes must plug into an electrical subbase. 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 265-V Unit with Power Cord POWER CORD PROTECTION FOR 230/208-V UNITS The power cord for the 230/208-v unit provides power cord protection by automatically disconnecting power during an unsafe condition. Power can be restored by pressing the RESET button. 30 Amp In-line Power Cord 15/20 Amp Power Cord Plug Head BI-MOLDED CONDENSER SHROUD BI-MOLDED CONDENSER SHROUD The bi-molded condenser shroud provides easy access for service and maintenance of the condenser coil and related components. Bi-Molded Condenser Shroud SNOW BAFFLE The snow baffle is provided to keep snow from blowing into the intake and landing on the internal components of the PTAC unit. Melted snow can form ice on moving parts and cause damage to the unit. SNOW BAFFLE Snow Baffle 9 PRODUCT FEATURES AND BENEFITS (cont) EASY ACCESS TO CHASSIS Access to the chassis simply requires removing four screws and then sliding the chassis out of the sleeve for service. TEST 1.PRES DO ING 2.PLUG S RESET RECEP INTO BUTTO 3.PRES TACLEPOWE N. R SHOULS TEST . 4. PRESS D BUTTO LIGHT. N UNIT FOR RESET NOT USE. BUTTO USE N AGAIN IS TEST ABOVE FAILS CHASSIS ATTACHMENT SCREWS (SAME LOCATION ON OPPOSITE SIDE) PLUG TEST/ RESET BUTTONS Easy Service Access HIDDEN CONTROLS Fan Cycle Switch The factory-wired control box houses all control components and is quickly accessible without removing the chassis from the wall sleeve. By simply removing two screws on control box, the hinged door lowers, providing quick access to all the electrical components. The wiring diagram is located on the front of the control box door. The fan cycle switch allows the fan to operate in 2 modes: • Continuous — This setting allows the fan to run continuously, circulating air even when the temperature setting has been satisfied. This setting, which helps to keep the room temperature closer to the thermostat setting, is used for maximum comfort. • Cycle — This setting allows the fan to cycle on and off with the compressor during heating or cooling. The fan stops when the temperature setting is reached. The longer unit off-time makes this option more energy-efficient with only slightly wider variations in room temperature. NOTE: On wall thermostat models, the fan cycle/ continuous feature is typically located at the wall thermostat. Temperature Limiter and Control Knob The limiter reduces operating costs by allowing the owner to control the range of cooling and heating temperatures available to the occupant. It is located under the front panel on control box, out of the occupant’s sight. Each setting on the limiter is equivalent to 5° F and the range of temperature settings available to the owner is from 60 to 90 F. The limiter is not pre-set at the factory (providing full range for the occupant). Outdoor Air Vent Control Control of the outdoor-air vent is handled by a vent handle located under the front panel on the left side of the unit. This handle rotates to manually open and close the outdoor vent. The vent will provide 50 cfm of fresh air. NOTE: If more fresh air cfm is required, a Power-Vent Kit is available (see accessories). 10 ENHANCED COPPER TUBING Enhanced copper tubing is more efficient and durable and can be repaired in the field, if required. Because copper is a very stable metal, it is durable and resists corrosion. Enhanced copper tubing increases: • heat transfer capability • the efficiency of the cooling and heating processes • thermal conductivity (by creating additional tube surface and turbulent refrigerant gas flow) Every Carrier PTAC coil undergoes thorough leak testing and pressure testing up to 350 lb per square inch. SEAMLESS BASEPAN Seamless drawn basepan walls add protection against water accumulation resulting from storm-driven rain with heavy wind. Carrier’s deep basepan holds up to 11/2 gallons of water without spilling. Closed cell foam insulators are located between the basepan and coils, keeping coils from direct contact with the basepan and providing additional protection against corrosion. Enhanced Copper Tubing CONDENSATE DRAIN VALVE The temperature-activated drain valve opens when the outdoor temperature drops below 45 F to prevent water from freezing in the basepan. Condensate Drain Valve Prevents Water from Freezing in Basepan CONDENSATE REMOVAL SYSTEM Carrier’s 52P and 52C Series units have an improved condensate (water) disposal system. In addition to slinger ring technology, Carrier has developed and patented a Condensate Suction Port. The suction port, along with the slinger ring, draws in water which is sprayed up onto the outdoor coil. The water then evaporates, thus providing better disposal of excess condensate, improving unit efficiency. NOTE: If it is necessary to remove 100% of the condensate, the Carrier Drain Kit (Part No.: DRAIN-KIT4PK) is recommended. SLINGER RING CONDENSATE SUCTION PORT CONDENSER SECTION Condensate Disposal System 11 PRODUCT FEATURES AND BENEFITS (cont) HEAT PUMPS PAY THEIR OWN WAY How The Heat Pump Works Heat pump models are available at a nominal additional cost. In many locales, the payback is realized in just a few months. Cost and payback details are provided on the next page. Special Features Two-Stage Indoor Thermostat: In Hot Weather: The indoor thermostat senses the indoor temperature and automatically turns on the electric heat to warm the room quickly. After the desired temperature conditions have been satisfied, the thermostat automatically switches to heat pump mode. If compressor failure occurs, the thermostat will provide backup electric heat automatically. Carrier’s PTAC units provide indoor comfort in the same manner as conventional air conditioners, removing heat and humidity from indoor air. The heat and humidity is released to the outdoors. Carrier’s highefficiency design saves energy and reduces cooling costs. Outdoor Thermostat: During the heating cycle, the outdoor thermostat senses outdoor coil temperature. It switches the unit to electric heat mode when the outdoor coil temperature is 20 F or below (approximately 35 F outdoor-air temperature). The thermostat switches the unit back to heat pump mode when the outdoor coil temperature rises above 40 F, which is enough to provide heat to meet demand. The entire operation is completely automatic. Reversing Valve: In Cool Weather: The reversing valve provides quiet refrigerant flow after the unit shuts off. The valve controls the direction of refrigerant flow for both heating and cooling functions and remains energized as long as the controls are in the heat position. When the cooling controls are activated, the valve automatically reverses to the cooling position. When the outdoor coil temperature is above 20 F (approximately 35 F outdoor-air temperature), the heat pump draws heat from outdoor air and uses it to heat indoor air. Since heat is transferred and not produced, Carrier’s heat pump uses less electricity and reduces energy costs significantly. Manual Compressor Override Switch: This switch completely locks out the compressor. Note that the compressor and heater do not operate at the same time, thus conserving energy. In Sub-Freezing Weather: When the outdoor coil temperature falls below 20 F (approximately 35 F outdoor-air temperature), the unit automatically switches on a built-in electric heater. The compressor stops and a blower circulates warm air produced by the heater. When the outdoor coil temperature rises above 40 F, heat pump operation resumes automatically. 12 HEAT PUMP ENERGY SAVINGS Heat pumps save more on operating costs during the heating cycle than heat/cool models. The table below shows that the higher initial cost of purchasing a heat pump is quickly made up in lower operating costs. Use the map to identify the climate zone’s designated number. Reading down the left-hand column of the table, select the cost/kWh rate in this zone that most closely approximates your local rate. The approximated savings and payback period is found at the intersection of your zone/rate line and the desired Btuh Cooling Capacity column. Exact savings are determined by lifestyle, local electrical rates, and climatic conditions. ZONE VI V ZONE V ZONE IV ZONE III II ZONE II ZONE I CARRIER HEAT PUMP INITIAL COST VERSUS SAVINGS OVER HEAT/COOL MODELS 7000 BTUH1 COOLING ELECTRIC ZONE COST/kWH CAPACITY Annual Savings* $.06 $ 34.26 I $.08 $ 45.68 $.10 $ 57.10 $.06 $ 57.12 II $.08 $ 76.16 $.10 $ 95.20 $.06 $ 58.02 III $.08 $ 77.36 $.10 $ 96.70 $.06 $ 82.02 $.08 $109.36 $.10 $136.70 IV $.12 $164.04 $.14 $191.38 $.16 $218.72 $.06 $ 57.36 $.08 $ 76.48 V $.10 $ 95.60 $.12 $114.72 $.14 $133.84 $.06 $ 93.72 $.08 $124.96 VI $.10 $156.20 $.12 $187.44 $60 PREMIUM Payback in Months 21 16 13 13 9 8 12 9 7 9 7 5 4 4 3 13 9 8 6 5 8 6 5 4 9000 BTUH2 COOLING CAPACITY Annual Savings* $ 43.08 $ 57.44 $ 71.80 $ 71.76 $ 95.68 $119.60 $ 72.84 $ 97.12 $121.40 $103.02 $137.36 $171.70 $206.04 $240.38 $274.72 $ 71.94 $ 95.92 $119.90 $143.88 $167.86 $117.66 $156.88 $196.10 $235.32 $75 PREMIUM Payback in Months 21 16 13 13 9 8 12 9 7 9 7 5 4 4 3 13 9 8 6 5 8 6 5 4 12000 BTUH2 COOLING CAPACITY Annual Savings* $ 58.20 $ 77.60 $ 97.00 $ 96.96 $129.28 $161.60 $ 98.40 $131.20 $164.00 $139.14 $185.52 $231.90 $278.28 $324.66 $371.04 $ 97.26 $129.68 $162.10 $194.52 $272.33 $159.00 $212.00 $265.00 $318.00 $90 PREMIUM Payback in Months 19 14 11 11 8 7 11 8 7 8 6 5 4 3 3 11 8 7 6 4 7 5 4 3 15000 BTUH3 COOLING CAPACITY Annual Savings* $ 68.34 $ 91.12 $113.90 $113.64 $151.52 $189.40 $115.38 $153.84 $192.30 $163.14 $217.52 $271.90 $326.28 $380.66 $435.04 $113.94 $151.92 $189.90 $227.88 $265.86 $186.48 $248.64 $310.80 $372.96 $110 PREMIUM Payback in Months 19 14 12 12 9 7 11 9 7 8 6 5 4 3 3 12 9 7 6 5 7 5 4 4 LEGEND kWH — Kilowatt Hour *Computer projections based on full cooling load at 95° F. Savings projected for 230 v ratings. 1Heating load is 5,000 Btuh at winter design point temperature. 2Heating load is 10,000 Btuh at winter design point temperature. 3Heating load is 15,000 Btuh at winter design point temperature. For precise energy savings in your geographical location, go to www.lodgingAC.com to use Carrier’s energy calculator. 13 ORDERING DATA (52P AND 52C) For immediate assistance, call 1-800-827-7435 or contact your local Carrier dealer. Standard Unit • Chassis with front panel • Electro-mechanical controls • Cord-connected chassis for 230/208-v and 265-v units Lead-time: Many models are in stock for immediate delivery; call for lead-times. EXTERIOR GRILLE (ACCESSORY) Y) TEST DO FRONT PANEL (STANDARD) 1.PRE 2.PLU SS RESE G RECE INTO T BUTT 3.PRE PTAC POWE ON. R LE. SHOUSS TEST 4. PRES LD BUTT LIGHT ON FOR S RESE . UNIT T BUTT NOT USE. USE ON AGAIN IS TEST ABOV E FAILS ING PLUG TEST/ RESET BUTTONS CHASSIS (STANDARD) Standard 52P or 52C Unit PRODUCT CATALOG NUMBER 14 WALL SLEEVE (ACCESSOR FACTORY-INSTALLED OPTIONS (52P AND 52C) WALL THERMOSTAT CONTROL (RC,RP) Carrier’s wall thermostat control option includes: • a standard chassis with front panel • factory-installed low voltage controls for remote thermostat operation • indoor coil freeze protection • user accessible selector switch for high or low fan speed Wall thermostat and wall thermostat wire must be ordered separately. See page 50 for a diagram of multiple PTAC units controlled by a single thermostat. NOTE: Be sure to connect reversing valve wiring to the O connection of the thermostat for heat pump applications. NOTE: Do not use a power stealing digital thermostat (common must be connected for digital thermostats). FAN SPEED Comfort WALL THERMOSTAT COMFORT CORROSION PROTECTION (CP,RP) To protect against the corrosive effects of a seacoast environment, this option includes: • a standard chassis with front panel • special protections consisting of: — painted control box and unit partitions — pre-coated aluminum coils with copper tubing — stainless steel tube sheets (outdoor coil) — totally enclosed fan motor with moistureresistant windings NOTE: All installations within one mile of the sea coast or other corrosive environment must use Corrosion Protection (CP). 15 LO HI FIELD-INSTALLED ACCESSORIES (52P AND 52C) WALL SLEEVES The sleeve's alpine mist color (a shade of beige) closely matches the front panel and blends in well with any inside or outside decor. The polymer wall sleeve comes in both insulated (factory installed) or non-insulated, to meet the requirements of every application. Weather Last™ Wall Sleeve For the best performance and longest life, Carrier recommends genuine Carrier wall sleeves for all installations. All Carrier wall sleeves are built with a pitch of 1/4 in. per foot; for self-pitching of the unit, the wall sleeve must be installed level (any error should be pitched to the outside). Overflow slots on the outside of the sleeve are in place to divert excess water during severe weather. Insulated Polymer Wall Sleeve Part No.: SLEEVE-INSUL-1PK Carrier’s accessory insulated polymer wall sleeve, with factory-installed insulation, provides superior sound absorption, reduces heat loss and prevents sleeve sweating, a condition that can occur when the outside temperature is cold and the indoor conditions are warm and humid. Important Sleeve Installation Considerations: • All Carrier's sleeves are self pitching and must be mounted level in all directions. (Do not use rails to level sleeve.) • The sleeve should be caulked on all sides, including both inside and outside the building. • If more than 4 in. of wall sleeve projects into the room, an accessory subbase must be used for support. • For all applications with an accessory subbase, wall sleeve must extend 31/4 in. minimum into room and must be 31/4 in. minimum to 51/2 in. maximum above floor (including carpeting) to allow for proper fit of subbase. • For applications where the wall sleeve is mounted flush to the exterior of the building (or recessed in), Carrier recommends a fieldsupplied drip edge be installed to prevent water infiltration into the building. • Insulated wall sleeves should be considered for superior sound absorption, to reduce heat loss and to prevent sleeve sweating, a condition that can occur when the outside temperature is cold and the indoor conditions are warm and humid. IMPORTANT: Insulated Polymer Wall sleeve provides superior sound absorption, reduces heat loss and prevents sleeve sweating. Corrosion-Protected Polymer Sleeve Non-Insulated Polymer Wall Sleeve Polymer Wall Sleeves Part No.: WALL-SLEEVE-1PK Part No.: WALL-SLEEVE-9PK Carrier’s accessory non-insulated polymer wall sleeve, provides a superior appearance and protection for many applications. Choose a polymer wall sleeve for maximum protection and appearance. All Carrier’s polymer wall sleeves are made from a molded polymer that is designed for strength and durability. This material has excellent corrosion resistance and a flammability rating of UL94-5V. The sleeve surface is textured to prevent shine and hide scratches. The rib configuration on the sleeve bottom, allows easy chassis removal and aids in drainage. The locating holes in the side and top panels, allow easy fastening of the sleeve to wall openings. Refer to dimension drawings (pages 28 and 29) for typical wall installation and dimensions. For applications where weather conditions could influence sleeve sweating, a condition that can occur when the outside temperature is cold and the indoor conditions are warm and humid, the Insulated Polymer Wall sleeve should be considered. 16 Insulated Metal Wall Sleeves 42 IN. Part No.: SLEEVE-STEEL-1PK Part No.: SLEEVE-EXT18-1PK Part No.: SLEEVE-EXT24-1PK Part No.: SLEEVE-EXT26-1PK Part No.: SLEEVE-EXT28-1PK Carrier's metal wall sleeves are available in a variety of sizes for most applications and difficult installations. Choose from 14 in., 18 in., 24 in., 26 in., or 28 in. standard depth sizes. All metal wall sleeves come with factory-installed insulation, designed to minimize heat loss, reduce outdoor noise transmissions into the room and prevent sleeve sweating. In addition, the metal wall sleeve provides a flammability rating higher than UL94-5V. 16 IN. 14/18/24/26/28 IN. Standard and Extended Metal Wall Sleeve 1 IN. Wall Sleeve Molding Kit Part No.: SLEEVE-MOLDING For a superior look and to hide any construction imperfections, use Carrier's wall sleeve molding kit to trim the wall sleeve to the wall. The molding kit is a perfect solution and can be used with any Carrier wall sleeve (matches Carrier wall sleeve color). 1/2 IN. Wall Sleeve Molding Kit Friedrich (and ZoneAire) Retrofit Wall Sleeve Adapter Part No.: FR-SLEEVE-EXT The Friedrich (and ZoneAire) wall sleeve adapter is constructed of sheet metal and is designed to increase the depth of an existing Friedrich T-series or ZoneAire wall sleeve to accommodate Carrier’s industry standard PTAC units. 16 IN. 42 IN. 3 IN. Friedrich Wall Sleeve Adapter Kit Climate Master Wall Sleeve Adapter Part No.: CM-SLEEVE-EXT The Climate Master wall sleeve adapter is constructed of sheet metal and is designed to increase the depth of an existing Climate Master 121/2 in. wall sleeve to accommodate Carrier’s industry standard PTAC units. 16 IN. 42 IN. 1 1/2 IN. Climate Master Wall Sleeve Adapter Kit 17 FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) OUTDOOR GRILLES Polymeric Architectural Outdoor Grilles (Louvered) Carrier recommends only the use of Carrier-supplied grilles for use on the 52P and 52C series units. However, the architectural designs of a building may dictate the use of special or oversized grilles and/or louvers. Special louvers or any special architectural treatment of the building façade that may restrict free circulation of condenser airflow should be referred to Carrier Corporation for evaluation and approval. Part No.: GRILLE-PLA-BROWN Part No.: GRILLE-PLA-BEIGE Part No.: GRILLE-PLA-ALPIN (color matches Carrier wall sleeve) This value line of polymeric architectural outdoor grilles will blend attractively with most building exteriors. Mounted easily from inside the room, the onepiece, molded grille is designed for protection, enhanced appearance, and superior weather-resistance. The grille is made of durable polymer and has a colorfast, lightly textured finish that blends well with most exterior finishes. Aluminum Architectural Outdoor Grilles (Louvered) Part No.: GRILLE-ALU-CLEAR (anodized aluminum) Part No.: GRILLE-ALU-WHITE Part No.: GRILLE-ALU-BEIGE Part No.: GRILLE-ALU-ALPIN (color matches Carrier wall sleeve) Part No.: GRILLE-ALU-BRONZ Part No.: GRILLE-ALU-MBRNZ Part No.: GRILLE-ALU-BROWN Part No.: GRILLE-ALU-LGREY Part No.: GRILLE-ALU-SGREY Part No.: GRILLE-ALU-PEACH Part No.: GRILLE-ALU-MELON Part No.: GRILLE-ALU-RDBRK Part No.: GRILLE-ALU-BLUE Part No.: GRILLE-ALU-GREEN This premium line of decorative outdoor grilles will enhance the appearance of any building. The grilles are made of strong, durable, extruded, anodized aluminum and are designed to be mounted easily from inside the room. These elegant grilles, available in many standard colors, have baked enamel finishes containing 50% kynar resin, for a superior finish that will withstand the most extreme conditions. See inside of back cover for standard colors and color samples. For more information on custom colors and sizes, contact Reliable Products at 1-800-239-4621. Architectural Grille in Aluminum or Polymeric Standard Outdoor Aluminum Grille Part No.: GRILLE-ALU-STAMP This cost-effective, one-piece standard grille is made from durable anodized aluminum. The grille is lightweight, has a clear finish, and is easy to install from inside the room. Standard Grille 18 Outdoor Grille Selection IMPORTANT: If you wish to use a grille not made by Carrier for your Carrier unit(s), contact the Carrier Application Engineering Group at 1-800-894-6449. X Y The following guidelines must be followed in the initial selection of any alternate exterior grille or louver: 1. The louver must have a minimum of 65% free area. Free area is the minimum area of the opening in an air inlet or outlet in which air can pass. Free Area (%) = X/Y. 2. The louver should be attached to the wall sleeve in a manner that will prevent recirculation of condenser discharge air into the inlet. In most applications, baffles, splitters, and/or gasket will be required between the chassis tube end sheets and the louver to prevent air recirculation. The above criteria must be followed, since a louver that is restrictive or allows recirculation will result in a reduction of the unit’s capacity and efficiency and will ultimately shorten the compressor life. Y X Y X X Y Louver Dimensional Reference Sample Calculations Free Area (%) = x x 100 y x = 1″ y = 1.5″ F.A. (%) = 1 x 100 = 66.7% 1.5 Hardwire Kit Part No.: HARDWIRE-KIT-1PK This accessory hardwire kit provides a permanent connection to the unit. Electrical hard wiring is required when NEC (National Electrical Code) or local codes restrict the use of power cord and plug connections. The hardwire kit mounts on the front right side of the unit and comes with 36 inches of flexible steel conduit and a Molex connector for easy connect/disconnect. Hardwire Kit Conduit Interface Kit Part No.: CONDUIT-INTF-4PK The conduit interface accessory kit provides the wire connection to the unit to interface to field-supplied conduit. Conduit Interface Kit 19 FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) SUBBASE Part No.: SUBBASE-NON-ELEC Part No.: SUBBASE-230V-15A Part No.: SUBBASE-230V-20A Part No.: SUBBASE-230V-30A Part No.: SUBBASE-265V-15A Part No.: SUBBASE-265V-20A Part No.: SUBBASE-265V-30A Part No.: SUBBASE-HARDWIRE Part No.: LEVELING-LEGS This decorative subbase supports the unit and is available in three basic models: non-electrical, electrical, and hardwired. A subbase (or leveling legs) is required for installations where the wall sleeve extends 4 or more inches into the room or the wall is less than 2 in. thick. The minimum clearance between the bottom of the sleeve and the floor is 31/4 in., and the maximum clearance is 51/2 inches. IMPORTANT: All standard cord-connected 265-v PTAC units will require a field-installed electrical subbase accessory per UL and NEC electrical codes. All subbase models are pre-assembled, mount to the wall sleeve, and come with adjustable legs and side skirting to provide a finished appearance. Non-electrical subbase The easy to install, non-electrical subbase provides mechanical support and requires no wiring. Non-Electrical Subbase Assembly Electrical subbase The electrical subbase has a factory-installed electrical junction box containing a receptacle for corded packaged terminal air conditioner (PTAC) units. The electrical subbase series offers models from 230-v, 15 amp up to 265-v, 30 amp. Knockouts are provided for power source connections. Electrical Subbase Assembly Hardwired subbase The hardwired electrical subbase has a factoryinstalled junction box containing 19 in. of flexible conduit (for a perfect fit to the PTAC unit) and all mating connections for easy assembly to PTAC units. Knockouts are provided for power source connections. Hardwired Subbase Assembly 20 Leveling legs Part No.: LEVELING-LEGS Leveling legs attach easily to Carrier’s wall sleeve and offer accurate leveling and support for units without a subbase. Leveling legs are adjustable from 31/4 in. to 51/2 in. Leveling-Legs Subbase Fuse Kit Part No.: SUBBASE-FUSE-15A Part No.: SUBBASE-FUSE-20A Part No.: SUBBASE-FUSE-30A The fuse kit provides in-line overcurrent protection at the unit when required by NEC (National Electric Code) or local codes. IMPORTANT: The Fuse Kit can only be used with the electrical or hardwired subbase. Subbase Fuse Kit Subbase Power Disconnect Switch ON Part No.: SUBBASE-SWITCH The subbase power disconnect 2-pole switch provides a recessed power disconnect for the PTAC unit when required by NEC or local codes. IMPORTANT: This accessory can only be used with the electrical or hardwired subbase. Power Disconnect Switch Assembly 21 FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) THERMOSTATS Carrier’s full line of wall thermostats are designed to enhance every PTAC application. Wall thermostats are simple and easy to use. Wall thermostats provide better temperature and humidity control as they can be placed in an optimal position in the room. NOTE: See page 50 for a wiring diagram of multiple PTAC units controlled by one thermostat. Digital Programmable Thermostat Part No.: TSTATCCPAC01-B (for heat/cool models) Part No.: TSTATCCPHP01-B (for heat pump models) This microcomputer-controlled, 7-day programmable wall thermostat has enhanced features that provide automatic control for both heat pumps and heating/ cooling units. It is used only on wall thermostat control (RC,RP) models. Programmable Thermostat Non-Programmable Thermostat Part No.: TSTATCCBPC01-B (for heat/cool models) Part No.: TSTATCCBPH01-B (for heat pump models) This low-voltage, easy-to-use non-programmable thermostat provides maximum guest comfort. This thermostat can only be used on wall thermostat (RC,RP) models. Non-Programmable Thermostat Manual Changeover Wall Thermostat Part No.: HH01AD045 (for heat/cool and heat pump models) This manual changeover wall thermostat provides a reliable and consistent level of occupant temperature control for both heat pumps and heating/cooling units. The thermostat consists of a conventional vented cover and a coiled bimetal element. It is used only on wall thermostat control (RC,RP) models. Auto FAN On Heat •60• 70•8 0•90 Off • Cool Manual Thermostat 22 Wall Thermostat Interface Retrofit Kit Part No.: RC-FIELDKIT230HC Part No.: RC-FIELDKIT230HP Part No.: RC-FIELDKIT265HC Part No.: RC-FIELDKIT265HP The Wall Thermostat Interface Retrofit Kit allows PTAC units with standard unit-mounted controls to be field converted for use with wall thermostat controls. NOTE: To obtain retrofit kits for previous 52S Carrier models, contact your Carrier sales representative. WA L L T MO HER S TA OM T C FOR T Wall Thermostat Interface Retrofit Kit 2-Speed Fan Control from Wall Thermostat 2 4 Part No.: 2SPEED-TSTAT-KIT This kit includes an automatic heat/cool changeover thermostat and relay logic for allowing multiple fan speed control from the wall thermostat. The thermostat is simple to operate and install, and provides features designed for the lodging industry, such as, Hi and Low fan speed control, freeze guard, set point limits and large, easy to read display. 5 6 FAN AUTO F TO SET PRESS FAN F/C OR COOLER WARMER 1 3 Auto Changeover Thermostat and Speed Control Relay Part No.: 2SPEED-RCFAN-KIT This kit only contains the relay logic for allowing multiple fan speed control from a wall thermostat. NOTE: When selecting a thermostat, ensure that the thermostat is capable of 2-fan speed control. Thermostat Locking Cover Part No.: TSTAT-COVER-6X7 Part No.: TSTAT-COVER-7X10 The thermostat locking cover prevents unauthorized access to the thermostat. Thermostat Locking Cover 23 FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) Condensate Drain Kit Part No.: DRAIN-KIT-4PK This universal drain kit may be used internally or externally to route condensate to a drainage system. It can be field-installed on any Carrier wall sleeve. Although Carrier’s units are designed to dissipate all the condensate generated during normal cooling, there may be times when abnormal conditions cause more condensate than the unit can dissipate. If condensate that drips from the wall sleeve is objectionable, this internal/external drain kit should be installed. The drain kit may be attached to the exterior right or left side of the wall sleeve for external draining or may be mounted to the room side of the wall sleeve for internal draining. Drain Kit IMPORTANT: For internal drains installed in the plastic wall sleeve, the drain must be installed on the flat area of the sleeve. It cannot be installed in the wafer area. Lateral Duct Kit Part No.: LATERAL-DUCT (Adapter Plenum and Extension) The accessory lateral duct kit allows one unit to heat or cool two rooms. The kit provides substantial savings for apartments, hotel suites, and office suites by eliminating the need for separate units for every room. The amount of air that can be diverted to an adjoining room is adjustable from 20 to 30 percent. The lateral duct kit consists of two main components, the plenum and the extension duct. The kit mounts to the wall sleeve and allows either right or left side ducting. Consider the following when designing a ducted application. • The maximum extension of the duct length is 4 feet. • The duct run must be straight and horizontal; no bends or turns. • The minimum recommended clearance between the unit and the adjoining room wall is 6 inches. • You must provide for return air from the adjoining room. • Carrier 52P and 52C units are not qualified for use with any other ducting scheme. See page 31 for more information. NOTES: 1. Lateral Duct Kit includes wall register for duct extension and a molding kit to trim the wall opening. 2. The sleeve should extend a minimum of 3-in. into the room to install mounting brackets. 3. The Lateral Duct Kit is not compatible with previous PTAC models. Lateral Duct Kit 24 Power Vent with Power Door Kit Part No.: PWR-VENT-DOOR230 Part No.: PWR-VENT-DOOR265 Carrier's power vent kit, utilizing a specially designed fan, when installed in the unit's fresh air vent, will supply up to 95 cfm of outside air into the room. The power vent will only operate when the unit fan runs, and the unit will automatically open or close the vent door, depending on the operation of the fan. The kit comes pre-assembled from the factory and is very easy to install. Power Vent with Door Kit Lateral Air Deflector Part No.: DEFLECTOR-1PK Carrier’s exclusive lateral air deflector allows discharge air to be directed right or left in a room. This field-installed accessory is equipped with independently adjustable louvers to enhance air circulation. Lateral air deflectors are recommended for units mounted in a corner or off-center in a room. NOTE: The lateral air deflector is not compatible with previous PTAC models. Accessory Air Deflector Curtain Deflector Part No.: CURTDFL-52CP-1PK The curtain deflector is used to prevent curtains from being blown into the discharge air. Curtain Deflector Kit Security Door Kit Part No.: SECURITY-DOOR This key-locking security door kit prevents unauthorized access to the unit’s heating and cooling controls and prevents tampering with units in public locations and institutions. This field-installed accessory includes two matching keys and fits all Carrier 52P and 52C models. Keys are common to all Security Door kits. Security Door Kit 25 FIELD-INSTALLED ACCESSORIES (52P AND 52C) (cont) Replacement Filters Part No.: AIR-FILTER-10PK The Carrier 52P and 52C model replacement air filters come in packages of 10. The filters save energy by preventing the evaporator coils from being plugged with dirt and lint. These economical and sturdy filters are interchangeable and may be washed, vacuumed, and reused. Easily Replaceable Filters Energy Management Kit Part No.: EM-KIT This field-installed accessory kit allows individual units to be turned on and off from a remote location. The kit incorporates Carrier’s Freeze Guard protection that prevents rooms from freezing during extreme or extended cold periods. Under these conditions, the Freeze Guard automatically disables front desk control and allows the unit to maintain a temperature of at least 50 F in the room. When the room reaches 65 F, the Freeze Guard feature returns the unit control to the front desk. This kit interfaces to most energy management systems. When installed in locations other than the front desk, the kit can control unit operation by receiving signals from field-supplied devices such as motion sensors or heat sensing detectors. Control devices connected to the Energy Management Kit must have normally open sets of contacts (when the switch is open, the unit operates). A 24-volt transformer must be field supplied and connected to the Energy Management Kit. (See typical wiring diagram on page 49.) Energy Management Kit 26 DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION TYPICAL WALL INSTALLATION If practices are unknown, consult your local architect or building contractor. Installed wall sleeve must be level from side to side and front to back. Proper building practices must be used when constructing a wall opening to support a PTAC wall sleeve and chassis. DISCHARGE GRILLE 3 -6 (1067) ACCESSORY WALL SLEEVE REMOVABLE FRONT PANEL 3.94" (100) HINGED CONTROL ACCESS DOOR 15/20 AMP PLUG HEAD (SEE NOTE #8) 2.03" (51.6) 7.24" (184) 1 -10 (558.8) 6 (152.4) 2.00" (50.7) 4 -4 (1320.8) 30 AMP IN-LINE CORD 208/230-V SERVICE CORD 30 AMP 12" (304.8) 208/230-V UNITS 3’-6” (1067) DISCHARGE GRILLE ACCESSORY WALL SLEEVE HINGED CONTROL ACCESS DOOR REMOVABLE FRONT PANEL (SEE NOTE #8) 15” (381) 265-V SERVICE CORD (SEE NOTE #9) 6” (152.4) 15” (381) 265-V UNITS 52P and 52C Dimension Drawing 27 NOTES: 1. Dimensions in parenthesis are in millimeters. 2. Minimum opening sizes apply to all wall openings. 3. Proper building practices must be used when constructing a wall opening to support a PTAC wall sleeve and chassis. If practices are unknown consult your local architect or building contractor. 4. Installed wall sleeve must be level from side to side and front to back (do not use rails to level sleeve). 5. If wall sleeve extends into the room more than 4-in., an accessory subbase or field fabricated front support should be used to prevent wall sleeve from tipping forward. 6. For all applications with an accessory subbase, wall sleeve must extend into room 31/4-in. (83 mm) minimum and 31/4-in. (83 mm) minimum from floor. 7. For all applications with an accessory lateral duct, sleeve must extend into the room 3-in. (76.2 mm) minimum. In applications where the sleeve will not extend a minimum 3-in., the lateral duct mounting brackets must be mounted on the wall sleeve prior to wall sleeve installation. 8. Remote control models, “RC” and “RP” units, use low voltage connections (24 volt AC). 9. 265 volt cord connected units must plug into a 265 volt electrical subbase per UL requirement (or hardwire can be used). 10. The 265 volt electrical cord is approximately 15-in. long from where it exits the front panel. DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) WALL SLEEVE MOUNTING DIMENSIONS FOR STANDARD AND ACCESSORY GRILLES JACK STUDS MAIN STUD HEADER- 4’ x 4’ OR (2) 2’ x 4’ ON EDGE 16 1/4” 42 1/8” Standard Polymer Non-Insulated Wall Sleeve Standard Polymer Insulated Wall Sleeve JACK STUD 42 in. CRIPPLE 16 in. FLOOR SUB-FLOOR Framing and Minimum Wall Sleeve Opening 14/18/24/26/28 in. Standard and Extended Metal Insulated Wall Sleeve NOTES (ALL SLEEVES): 1. Never install fasteners through bottom of sleeve. 2. Never use rails to level sleeve. Wall Sleeve Mounting (All Models) 28 TYPICAL WALL INSTALLATION NOTES: 1. Sleeve may be flush mounted to floor, but front panel may have to be notched to accommodate service cord. 2. If more than 4 in. of sleeve projects into room, an accessory subbase must be used for support. 3. For walls 2 in. thick or less, an accessory subbase must be used for support. 4. Caulk around sleeve on both indoor and outdoor sides. Typical Wall Sleeve Installation Typical Curtain Wall Installation (All Models) 29 DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) MINIMUM CLEARANCE FOR INDOOR AND OUTDOOR DISCHARGE AIR Blocking indoor or outdoor discharge air could cause premature failure of unit. 15” MINIMUM DISTANCE FROM FRONT PANEL TO OBJECTS IN ROOM 36" MINIMUM DISTANCE FROM SLEEVE TO BUILDING WALLS, SHRUBS, etc. 52P and 52C Indoor and Outdoor Discharge Air Circulation OUTDOOR VIEW GRILLE MOUNTING HOLES WALL S LE EVE 2 3/8” (60.3) WALL SLEEVE-(2) DRAIN LOCATIONS GRILLE MOUNTING HOLES CONDENSATE OVERFLOW HOLES 2 3/8” (60.3) (OUTSIDE) Back of Polymer Wall Sleeve 30 TYPICAL LATERAL DUCT INSTALLATION WALL REGISTER ALTERNATE EXTENSION POSITION* LATERAL DUCT EXTENSION PLENUM END CAP 3’-8” (117.6) WALL MOLDING 3’-11 1/2” (1206.5) MAX. REVERSIBLE AIR GRILLE 3’-11 1/2” (1206.5) MAX. *Only one Lateral Duct Extension may be installed per unit. Lateral duct extensions may be installed on either side of the unit. NOTE: For all applications with an accessory lateral duct, sleeve must extend into the room a minimum of 3 inches. In applications where the sleeve will not extend a minimum of 3 in., the lateral duct mounting brackets will need to be mounted on the sleeve prior to installation to the wall. 52P and 52C Lateral Duct 31 DIMENSION DRAWINGS AND INSTALLATION DATA — NEW CONSTRUCTION (cont) 52P AND 52C WITH SUBBASE 0’-3 1/4” MIN. (83) 0’-5 1/2” MAX. (140) 0’-0 7/8” (22) SUBBASE ACCESS COVERS OUTSIDE WALL SEE NOTES 1 9/16” (39.7) SIDE 19 1/2” (495.3) (3) 7/8” (22.2) DIA. KNOCKOUTS (3) 1 1/8” (28.6) DIA. KNOCKOUTS REAR VIEW ACCESSORY SUBBASE ELECTRICAL CONNECTIONS SUBBASE LEVELING BOLTS ACCESSORY DRAIN (EXTERNAL OR INTERNAL) NOTES: 1. Accessory subbase is required for applications where: • Wall sleeve extends 4 or more inches into the room. • Wall thickness is less than 2 inches. • All 265-v cord-connected applications. 2. For all applications with an accessory subbase: • Wall sleeve must extend 4 in. minimum into the room and 31/4 in. minimum above the floor. • Subbase height is adjustable from 31/4 in. minimum to 51/2 in. maximum above floor (including carpeting). Refer to wall sleeve installation instructions. 32 17” (431.8) WALL THERMOSTAT CONNECTIONS FAN SPEED CONTROL KNOB R Y W G O C POWER CORD ACCESS COVER THERMOSTAT WIRE (FIELDSUPPLIED) R Y W G O C POWER CORD THERMOSTAT Control Box Wire Terminal for Wall Thermostat Models Terminal Connector Removal and Replacement NOTE: Thermostat wire is field supplied. Recommended wire gage is 18 to 20 gage solid thermostat wire. Thermostat wire should always be routed around or under, NEVER through, the wall sleeve. The wire should then be routed behind the front panel to the easily accessible terminal connector. THERMOSTAT WIRE ROUTING (UNDER SLEEVE, BEHIND FRONT PANEL) Terminal Wire Routing 33 PRODUCT DATA (52P) PERFORMANCE AND ELECTRICAL DATA MODEL 52PQ (230/208-1-60) MODEL NUMBER 52PQ 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) AMPS WATTS VOLTAGE HEATER Heating EER COP† RANGE kW Cooling Heating (Volts) Cooling Heating** Cooling Rev. Cyc. Electric 7,200/ 7,100 6,300/ 6,300 7,800/ 6,400 2.3 12.7/12.7 3.4/3.4 2.7/2.9 10.4/ 9.5 567/ 559 2393/1985 7,200/ 7,100 6,300/ 6,300 11,600/ 9,700 3.4 12.7/12.7 3.4/3.4 2.7/2.9 15.2/14.1 567/ 559 3493/2935 9,100/ 9,000 7,900/ 7,900 7,800/ 6,400 2.3 11.5/11.5 3.2/3.2 3.7/3.8 10.4/ 9.5 791/ 783 2393/1985 9,100/ 9,000 7,900/ 7,900 11,600/ 9,700 3.4 11.5/11.5 3.2/3.2 3.7/3.8 15.2/14.1 791/ 783 3493/2935 12,100/12,000 11,000/11,000 7,800/ 6,400 2.3 11.1/10.7 3.2/3.2 4.8/5.3 10.8/ 9.9 1090/1122 2470/2047 187-253 12,100/12,000 11,000/11,000 11,600/ 9,700 3.4 11.1/10.7 3.2/3.2 4.8/5.3 15.6/14.5 1090/1122 3570/2997 12,100/12,000 11,000/11,000 17,000/13,600 5.0 11.1/10.7 3.2/3.2 4.8/5.3 22.5/20.0 1090/1122 5170/4147 14,800/14,300 14,100/13,500 7,800/ 6,400 2.3 9.7/ 9.5 3.0/3.0 6.5/7.1 10.8/ 9.9 1526/1505 2470/2047 14,800/14,300 14,100/13,500 11,600/ 9,700 3.4 9.7/ 9.5 3.0/3.0 6.5/7.1 15.6/14.5 1526/1505 3570/2997 14,800/14,300 14,100/13,500 17,000/13,600 5.0 9.7/ 9.5 3.0/3.0 6.5/7.1 22.5/20.0 1526/1505 5170/4147 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52PQ (%) Amps 207---3 100 0.075 0.44 307---3 209---3 99 0.075 0.44 309---3 212---3 312---3 99 0.125 0.75 512---3 215---3 315---3 99 0.125 0.75 515---3 Indoor CFM LO/HI†† MAX FUSE MIN. RECEPR-22 DEHUMIDIFI- SENSIBLE APPROX. CHASSIS SIZE CIRCUIT TACLE CHARGE CATION HEAT SHIP WT. (Amps) AMPS TYPE (oz) (Pints/Hr) FACTOR (lb) 220/260 220/260 270/350 250/320 15 20 15 20 15 20 30 15 20 30 13.0 19.0 13.0 19.0 13.3 19.3 27.9 13.3 19.3 27.9 A B A B A B C A B C 24 1.5 0.78 125 24 2.4 0.73 125 34 3.4 0.71 140 32 4.6 0.67 150 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 380-93. †Coefficient of Performance (COP) at 47 F outdoor ambient temperature. **Electric resistance heater power and fan motor power. ††Fan motor indoor CFM (LO/HI) shown for 230-1-60 units. New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 230/208 250/20 250/15 250/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association *May be used for 15-amp applications if fused for 15 amps. 34 B C 6-15R 6-20R 6-30R 15 20* 30 2.3 3.4 5.0 PERFORMANCE AND ELECTRICAL DATA MODEL 52PQ (265-1-60) MODEL NUMBER 52PQ 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Heating Cooling Rev. Cycle Electric 7,200 6,300 7,800 7,200 6,300 11,600 9,100 7,700 7,800 9,100 7,700 11,600 12,100 10,800 7,800 12,100 10,800 11,600 12,100 10,800 17,000 14,700 14,100 7,800 14,700 14,100 11,600 14,700 14,100 17,000 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52PQ % Amps 207---4 97 0.075 0.46 307---4 209---4 97 0.075 0.46 309---4 212---4 312---4 99 0.125 0.71 512---4 215---4 315---4 96 0.125 0.71 515---4 Indoor CFM LO/HI 220/260 220/260 270/340 250/320 HEATER kW EER COP† 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 12.3 12.3 11.5 11.5 11.1 11.1 11.1 9.7 9.7 9.7 3.4 3.4 3.2 3.2 3.2 3.2 3.2 3.0 3.0 3.0 MAX. FUSE SIZE (Amps) AMPS VOLTAGE RANGE Cooling Heating** Cooling Heating 2.4 2.4 3.1 3.1 4.2 4.2 4.2 5.7 5.7 5.7 9.2 13.3 9.2 13.3 9.4 13.5 19.6 9.4 13.5 19.6 585 585 791 791 1090 1090 1090 1515 1515 1515 2396 3496 2396 3496 2470 3570 5170 2470 3570 5170 239-292 MIN. RECEPR-22 CIRCUIT TACLE CHARGE AMPS TYPE†† (oz) 15 20 15 20 15 20 25 15 20 25 11.3 16.5 11.3 16.5 11.6 16.7 24.3 11.6 16.7 24.3 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 380-93. †Coefficient of Performance (COP) at 47 F outdoor ambient temperature. **Electric resistance heater power and fan motor power. ††All 265-v units require an electrical subbase (receptacle or hardwire model). A B A B A B C A B C WATTS DEHUMIDIFICATION (Pints/Hr) SENSIBLE APPROX. CHASSIS HEAT SHIP WT FACTOR (lb) 26 1.5 0.78 125 24 2.4 0.73 125 34 3.4 0.71 140 33 4.6 0.67 150 New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 265 277/20 277/15 277/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association 35 7-15R B 7-20R C 7-30R 15 20 30 2.3 3.4 5.0 PRODUCT DATA (52P) (cont) PERFORMANCE AND ELECTRICAL DATA MODEL 52PC AND PE (230/208-1-60) 52PC performance and electrical data is the same as 52PE without electric heat. MODEL NUMBER 52PE 007---3 207---3 307---3 009---3 209---3 309---3 012---3 212---3 312---3 512---3 015---3 215---3 315---3 515---3 MODEL NUMBER 52PE 007---3 207---3 307---3 009---3 209---3 309---3 012---3 212---3 312---3 512---3 015---3 215---3 315---3 515---3 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,200/ 7,100 7,200/ 7,100 7,200/ 7,100 9,100/ 9,000 9,100/ 9,000 9,100/ 9,000 12,100/12,000 12,100/12,000 12,100/12,000 12,100/12,000 15,000/14,700 15,000/14,700 15,000/14,700 15,000/14,700 — 7,800/ 6,400 11,600/ 9,700 — 7,800/ 6,400 11,600/ 9,700 — 7,800/ 6,400 11,600/ 9,700 17,000/13,600 — 7,800/ 6,400 11,600/ 9,700 17,000/13,600 — 2.3 3.4 — 2.3 3.4 — 2.3 3.4 5.0 — 2.3 3.4 5.0 12.7/12.7 12.7/12.7 12.7/12.7 11.7/11.9 11.7/11.9 11.7/11.9 11.1/10.7 11.1/10.7 11.1/10.7 11.1/10.7 9.8/ 9.8 9.8/ 9.8 9.8/ 9.8 9.8/ 9.8 POWER FACTOR (%) FAN MOTOR Full Indoor Horsepower Load CFM Amps LO/HI** 100 0.075 0.44 220/260 99 0.075 0.44 220/260 99 0.125 0.75 270/350 95 0.125 0.75 250/320 VOLTAGE RANGE (Volts) AMPS WATTS Cooling Heating† Cooling Heating 187-253 2.7/2.9 2.7/2.9 2.7/2.9 3.0/3.1 3.0/3.1 3.0/3.1 4.8/5.3 4.8/5.3 4.8/5.3 4.8/5.3 6.4/7.1 6.4/7.1 6.4/7.1 6.4/7.1 — 10.4/ 9.5 15.2/14.1 — 10.4/ 9.5 15.2/14.1 — 10.8/ 9.9 15.6/14.5 22.5/20.0 — 10.8/ 9.8 15.6/14.5 22.5/20.0 567/ 559 567/ 559 567/ 559 778/ 756 778/ 756 778/ 756 1090/1122 1090/1122 1090/1122 1090/1122 1531/1500 1531/1500 1531/1500 1531/1500 — 2393/1985 3493/2935 — 2393/1985 3493/2935 — 2470/2047 3570/2997 5170/4147 — 2470/2047 3570/2997 5170/4147 R-22 CHARGE (oz) DEHUMIDIFICATION (Pints/Hr) SENSIBLE HEAT FACTOR APPROX. SHIP WT. (lb) 24 1.5 0.78 125 23 2.4 0.73 125 34 3.4 0.71 140 32 4.8 0.66 150 MAX. FUSE SIZE (Amps) MIN. CIRCUIT AMPS RECEPTACLE TYPE 15 15 20 15 15 20 15 15 20 30 15 15 20 30 4.8 13.0 19.0 5.4 13.0 19.0 8.4 13.3 19.3 27.9 11.1 13.3 19.3 27.9 A A B A A B A A B C A A B C LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 310-93. †Electric resistance heater power and fan motor power. **Fan motor indoor CFM (LO/HI) shown for 230-1-60 units. New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 230/208 250/20 250/15 250/30 OUTLET BLADE CONFIGURATION A TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) HACR NEMA LEGEND — Heating, Air Conditioning, and Refrigeration — National Electrical Manufacturers Association *May be used for 15-amp applications if fused for 15 amps. 36 B C 15 20* 30 2.3 3.4 5.0 PERFORMANCE AND ELECTRICAL DATA MODEL 52PC AND PE (265-1-60) 52PC performance and electrical data is the same as 52PE without electric heat. MODEL NUMBER 52PE 007---4 207---4 307---4 009---4 209---4 309---4 012---4 212---4 312---4 512---4 015---4 215---4 315---4 515---4 MODEL NUMBER 52PE 007---4 207---4 307---4 009---4 209---4 309---4 012---4 212---4 312---4 512---4 015---4 215---4 315---4 515---4 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,200 7,200 7,200 9,100 9,100 9,100 12,100 12,100 12,100 12,100 15,100 15,100 15,100 15,100 — 7,800 11,600 — 7,800 11,600 — 7,800 11,600 17,000 — 7,800 11,600 17,000 — 2.3 3.4 — 2.3 3.4 — 2.3 3.4 5.0 — 2.3 3.4 5.0 12.7 12.7 12.7 11.7 11.7 11.7 11.1 11.1 11.1 11.1 10.0 10.0 10.0 10.0 POWER FACTOR % FAN MOTOR Full Indoor Horsepower Load CFM Amps LO/HI 97 0.075 0.46 220/260 97 0.075 0.46 220/260 99 0.125 0.71 270/340 100 0.125 0.71 250/320 VOLTAGE RANGE (Volts) AMPS WATTS Cooling Heating† Cooling Heating 2.4 2.4 2.4 3.0 3.0 3.0 4.2 4.2 4.2 4.2 5.7 5.7 5.7 5.7 — 9.2 13.3 — 9.2 13.3 — 9.4 13.5 19.6 — 9.4 13.5 19.6 567 567 567 778 778 778 1090 1090 1090 1090 1510 1510 1510 1510 — 2396 3496 — 2396 3496 — 2470 3570 5170 — 2470 3570 5170 239-292 MAX. FUSE MIN. RECEPR-22 SIZE CIRCUIT TACLE CHARGE (Amps) AMPS TYPE** (oz) 15 15 20 15 15 20 15 15 20 25 15 15 20 25 3.7 11.3 16.5 4.7 11.3 16.5 6.7 11.6 16.7 24.3 8.7 11.6 16.7 24.3 A A B A A B A A B C A A B C DEHUMIDI- SENSIBLE APPROX. CHASSIS FICATION HEAT SHIP WT. (Pints/Hr) FACTOR (lb) 26 1.5 0.78 125 24 2.4 0.73 125 34 3.4 0.71 140 32 5.0 0.66 150 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 310-93. †Electric resistance heater power and fan motor power. **All 265-v units require an electrical subbase (receptacle or hardwire model). New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 265 277/20 277/15 277/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association 37 B C 7-15R 7-20R 7-30R 15 20 30 2.3 3.4 5.0 PRODUCT DATA (52C) PERFORMANCE AND ELECTRICAL DATA MODEL 52CQ (230/208-1-60) MODEL NUMBER 52CQ 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) AMPS WATTS VOLTAGE HEATER Heating EER COP† RANGE kW Cooling Heating (Volts) Cooling Heating** Cooling Rev. Cyc. Electric 7,000/ 6,900 6,100/ 6,000 7,800/ 6,400 2.3 11.1/11.1 3.1/3.1 3.0/3.2 10.4/ 9.5 631/ 622 2393/1985 7,000/ 6,900 6,100/ 6,000 11,600/ 9,700 3.4 11.1/11.1 3.1/3.1 3.0/3.2 15.2/14.1 631/ 622 3493/2935 9,000/ 8,900 7,900/ 7,800 7,800/ 6,400 2.3 10.7/10.7 3.1/3.1 4.3/4.7 10.4/ 9.5 841/ 832 2393/1985 9,000/ 8,900 7,900/ 7,800 11,600/ 9,700 3.4 10.7/10.7 3.1/3.1 4.3/4.7 15.2/14.1 841/ 832 3493/2935 12,000/11,900 10,800/10,700 7,800/ 6,400 2.3 10.1/10.1 3.0/3.0 5.1/5.5 10.8/ 9.9 1188/1178 2470/2047 187-253 12,000/11,900 10,800/10,700 11,600/ 9,700 3.4 10.1/10.1 3.0/3.0 5.1/5.5 15.6/14.5 1188/1178 3570/2997 12,000/11,900 10,800/10,700 17,000/13,600 5.0 10.1/10.1 3.0/3.0 5.1/5.5 22.5/20.0 1188/1178 5170/4147 14,600/14,300 14,100/13,500 7,800/ 6,400 2.3 9.5/ 9.5 3.0/3.0 6.5/7.1 10.8/ 9.9 1537/1505 2470/2047 14,600/14,300 14,100/13,500 11,600/ 9,700 3.4 9.5/ 9.5 3.0/3.0 6.5/7.1 15.6/14.5 1537/1505 3570/2997 14,600/14,300 14,100/13,500 17,000/13,600 5.0 9.5/ 9.5 3.0/3.0 6.5/7.1 22.5/20.0 1537/1505 5170/4147 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52CQ (%) Amps 207---3 100 0.075 0.44 307---3 209---3 99 0.075 0.44 309---3 212---3 312---3 99 0.125 0.75 512---3 215---3 315---3 99 0.125 0.75 515---3 Indoor CFM LO/HI†† MAX FUSE MIN. RECEPR-22 DEHUMIDIFI- SENSIBLE APPROX. CHASSIS SIZE CIRCUIT TACLE CHARGE CATION HEAT SHIP WT. (Amps) AMPS TYPE (oz) (Pints/Hr) FACTOR (lb) 220/260 220/260 270/350 250/320 15 20 15 20 15 20 30 15 20 30 13.0 19.0 13.0 19.0 13.3 19.3 27.9 13.3 19.3 27.9 A B A B A B C A B C 26 1.5 0.78 125 28 2.4 0.73 125 28 3.4 0.71 140 32 4.6 0.67 150 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 380-93. †Coefficient of Performance (COP) at 47 F outdoor ambient temperature. **Electric resistance heater power and fan motor power. ††Fan motor indoor CFM (LO/HI) shown for 230-1-60 units. New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 230/208 250/20 250/15 250/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association *May be used for 15-amp applications if fused for 15 amps. 38 B C 6-15R 6-20R 6-30R 15 20* 30 2.3 3.4 5.0 PERFORMANCE AND ELECTRICAL DATA MODEL 52CQ (265-1-60) MODEL NUMBER 52CQ 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 CAPACITY* (Btuh) Heating Cooling Rev. Cycle Electric 7,000 6,100 7,800 7,000 6,100 11,600 8,900 7,700 7,800 8,900 7,700 11,600 12,000 10,800 7,800 12,000 10,800 11,600 12,000 10,800 17,000 14,600 14,100 7,800 14,600 14,100 11,600 14,600 14,100 17,000 FAN MOTOR MODEL POWER Full NUMBER FACTOR Horsepower Load 52CQ % Amps 207---4 97 0.075 0.46 307---4 209---4 97 0.075 0.46 309---4 212---4 312---4 99 0.125 0.71 512---4 215---4 315---4 96 0.125 0.71 515---4 Indoor CFM LO/HI 220/260 220/260 270/340 250/320 HEATER kW EER COP† 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 11.1 11.1 10.7 10.7 10.1 10.1 10.1 9.5 9.5 9.5 3.1 3.1 3.1 3.1 3.0 3.0 3.0 3.0 3.0 3.0 MAX. FUSE SIZE (Amps) AMPS VOLTAGE RANGE Cooling Heating** Cooling Heating 2.6 2.6 3.6 3.6 4.7 4.7 4.7 5.7 5.7 5.7 9.2 13.3 9.2 13.3 9.4 13.5 19.6 9.4 13.5 19.6 631 631 832 832 1188 1188 1188 1537 1537 1537 2396 3496 2396 3496 2470 3570 5170 2470 3570 5170 239-292 MIN. RECEPR-22 CIRCUIT TACLE CHARGE AMPS TYPE†† (oz) 15 20 15 20 15 20 25 15 20 25 11.3 16.5 11.3 16.5 11.6 16.7 24.3 11.6 16.7 24.3 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 380-93. †Coefficient of Performance (COP) at 47 F outdoor ambient temperature. **Electric resistance heater power and fan motor power. ††All 265-v units require an electrical subbase (receptacle or hardwire model). A B A B A B C A B C WATTS DEHUMIDIFICATION (Pints/Hr) SENSIBLE APPROX. CHASSIS HEAT SHIP WT. FACTOR (lb) 26 1.5 0.78 125 28 2.4 0.73 125 29 3.4 0.71 140 33 4.6 0.67 150 New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 265 277/20 277/15 277/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association 39 B C 7-15R 7-20R 7-30R 15 20 30 2.3 3.4 5.0 PRODUCT DATA (52C) (cont) PERFORMANCE AND ELECTRICAL DATA MODEL 52CE (230/208-1-60) MODEL NUMBER 52CE 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 MODEL NUMBER 52CE 207---3 307---3 209---3 309---3 212---3 312---3 512---3 215---3 315---3 515---3 CAPACITY* (Btuh) Cooling Heating HEATER kW EER 7,000/ 6,900 7,000/ 6,900 9,000/ 8,900 9,000/ 8,900 12,000/11,900 12,000/11,900 12,000/11,900 14,600/14,300 14,600/14,300 14,600/14,300 7,800/ 6,400 11,600/ 9,700 7,800/ 6,400 11,600/ 9,700 7,800/ 6,400 11,600/ 9,700 17,000/13,600 7,800/ 6,400 11,600/ 9,700 17,000/13,600 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 11.1/11.1 11.1/11.1 10.7/10.7 10.7/10.7 10.1/10.1 10.1/10.1 10.1/10.1 9.5/ 9.5 9.5/ 9.5 9.5/ 9.5 POWER FACTOR (%) FAN MOTOR Full Indoor Horsepower Load CFM Amps LO/HI** 100 0.075 0.44 220/260 99 0.075 0.44 220/260 99 0.125 0.75 270/350 95 0.125 0.75 250/320 VOLTAGE RANGE (Volts) AMPS WATTS Cooling Heating† Cooling Heating 187-253 3.0/3.2 3.0/3.2 4.0/4.3 4.0/4.3 5.4/5.8 5.4/5.8 5.4/5.8 6.4/7.1 6.4/7.1 6.4/7.1 10.4/ 9.5 15.2/14.1 10.4/ 9.5 15.2/14.1 10.8/ 9.9 15.6/14.5 22.5/20.0 10.8/ 9.9 15.6/14.5 22.5/20.0 631/ 622 631/ 622 841/ 832 841/ 832 1188/1178 1188/1178 1188/1178 1537/1505 1537/1505 1537/1505 2393/1985 3493/2935 2393/1985 3493/2935 2470/2047 3570/2997 5170/4147 2470/2047 3570/2997 5170/4147 R-22 CHARGE (oz) DEHUMIDIFICATION (Pints/Hr) SENSIBLE HEAT FACTOR APPROX. SHIP WT. (lb) 21 1.5 0.78 125 28 2.4 0.73 125 29 3.4 0.71 140 32 4.8 0.66 150 MAX. FUSE SIZE (Amps) MIN. CIRCUIT AMPS RECEPTACLE TYPE 15 20 15 20 15 20 30 15 20 30 13.0 19.0 13.0 19.0 13.3 19.3 27.9 13.3 19.3 27.9 A B A B A B C A B C LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 310-93. †Electric resistance heater power and fan motor power. **Fan motor indoor CFM (LO/HI) shown for 230-1-60 units. New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 230/208 250/20 250/15 250/30 OUTLET BLADE CONFIGURATION A TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) HACR NEMA LEGEND — Heating, Air Conditioning, and Refrigeration — National Electrical Manufacturers Association *May be used for 15-amp applications if fused for 15 amps. 40 B C 15 20* 30 2.3 3.4 5.0 PERFORMANCE AND ELECTRICAL DATA MODEL 52CE (265-1-60) CAPACITY* (Btuh) MODEL NUMBER 52CE 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 MODEL NUMBER 52CE 207---4 307---4 209---4 309---4 212---4 312---4 512---4 215---4 315---4 515---4 Cooling Heating HEATER kW EER 7,000 7,000 8,900 8,900 12,000 12,000 12,000 14,600 14,600 14,600 7,800 11,600 7,800 11,600 7,800 11,600 17,000 7,800 11,600 17,000 2.3 3.4 2.3 3.4 2.3 3.4 5.0 2.3 3.4 5.0 11.1 11.1 10.7 10.7 10.1 10.1 10.1 9.5 9.5 9.5 POWER FACTOR % FAN MOTOR Full Indoor Horsepower Load CFM Amps LO/HI 97 0.075 0.46 220/260 97 0.075 0.46 220/260 99 0.125 0.71 270/340 100 0.125 0.71 250/320 AMPS VOLTAGE RANGE (Volts) 239-292 Heating† Cooling Heating 2.7 2.7 3.4 3.4 4.7 4.7 4.7 5.7 5.7 5.7 9.2 13.3 9.2 13.3 9.4 13.5 19.6 9.4 13.5 19.6 631 631 832 832 1188 1188 1188 1537 1537 1537 2396 3496 2396 3496 2470 3570 5170 2470 3570 5170 MAX. FUSE MIN. RECEPR-22 SIZE CIRCUIT TACLE CHARGE (Amps) AMPS TYPE** (oz) 15 20 15 20 15 20 25 15 20 25 11.3 16.5 11.3 16.5 11.6 16.7 24.3 11.6 16.7 24.3 A B A B A B C A B C WATTS Cooling DEHUMIDI- SENSIBLE APPROX. CHASSIS FICATION HEAT SHIP WT (Pints/Hr) FACTOR (lb) 22 1.5 0.78 125 29 2.4 0.73 125 28 3.4 0.71 140 32 5.0 0.66 150 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI Standard 310-93. †Electric resistance heater power and fan motor power. **All 265-v units require an electrical subbase (receptacle or hardwire model). New York City Department of Buildings, Material and Equipment Acceptance — MEA #242-04-E RECEPTACLES AND FUSE TYPES UNIT NAMEPLATE VOLTAGE OUTLET RATED VOLTS/AMPS 265 277/20 277/15 277/30 OUTLET BLADE CONFIGURATION A NEMA CONFIGURATION TIME DELAY FUSE OR HACR CIRCUIT BREAKER (AMPS) HEATER (KILOWATTS) LEGEND HACR — Heating, Air Conditioning, and Refrigeration NEMA — National Electrical Manufacturers Association 41 B C 7-15R 7-20R 7-30R 15 20 30 2.3 3.4 5.0 EXPANDED RATINGS DATA (52P AND 52C) COOLING PERFORMANCE ALL 7000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 260 CFM TEMP (F) AIR ENT. COND (40% RH) 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 7.05 0.54 2.35 6.93 0.56 2.45 6.85 0.59 2.56 6.76 0.61 2.67 6.70 0.64 2.79 6.57 0.67 2.91 6.42 0.70 3.03 6.28 0.73 3.17 EVAP AIR — EWB (F) 62.00 67.00 7.23 8.04 0.54 0.55 2.36 2.37 7.08 7.90 0.57 0.57 2.46 2.48 6.95 7.72 0.59 0.59 2.56 2.58 6.81 7.54 0.61 0.62 2.67 2.68 6.70 7.36 0.64 0.64 2.79 2.79 6.59 7.17 0.67 0.67 2.91 2.91 6.41 6.97 0.70 0.70 3.04 3.03 6.27 6.76 0.73 0.72 3.17 3.17 ALL 9000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 260 CFM TEMP (F) AIR ENT. COND (40% RH) 72.00 8.85 0.55 2.39 8.71 0.57 2.49 8.54 0.60 2.59 8.35 0.62 2.89 8.17 0.64 2.80 7.98 0.67 2.92 7.79 0.70 3.03 7.59 0.73 3.16 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 8.58 0.71 3.14 8.44 0.75 3.28 8.29 0.78 3.44 8.12 0.82 3.59 7.94 0.85 3.74 7.75 0.89 3.89 7.57 0.92 4.06 7.38 0.96 4.24 EVAP AIR — EWB (F) 62.00 67.00 8.91 9.71 0.72 0.71 3.14 3.13 8.72 9.56 0.75 0.74 3.28 3.27 8.52 9.47 0.78 0.78 3.44 3.42 8.30 9.29 0.82 0.81 3.60 3.58 8.07 9.06 0.85 0.85 3.74 3.74 7.84 8.83 0.89 0.89 3.90 3.92 7.60 8.59 0.93 0.93 4.07 4.10 7.38 8.32 0.97 0.97 4.24 4.27 72.00 10.46 0.71 3.12 10.48 0.74 3.27 10.39 0.78 3.41 10.26 0.81 3.56 10.07 0.85 3.72 9.80 0.88 3.89 9.67 0.92 4.06 9.41 0.97 4.24 LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. 52CQ 12,000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 350 CFM 52PC,PE,CE 12,000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 350 CFM TEMP (F) AIR ENT. COND (40% RH) 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 12.44 1.06 4.65 12.29 1.10 4.85 12.10 1.15 5.05 11.89 1.20 5.26 11.66 1.25 5.48 11.43 1.30 5.70 11.19 1.35 5.94 10.94 1.41 6.18 EVAP AIR — EWB (F) 62.00 67.00 12.74 13.61 1.06 1.05 4.65 4.59 12.51 13.52 1.10 1.09 4.84 4.80 12.29 13.20 1.15 1.13 5.05 4.98 12.01 12.97 1.20 1.18 5.26 5.18 11.73 12.72 1.25 1.23 5.48 5.40 11.48 12.40 1.30 1.28 5.70 5.62 11.23 12.20 1.35 1.33 5.94 5.86 10.98 11.91 1.41 1.39 6.18 6.10 TEMP (F) AIR ENT. COND (40% RH) 72.00 13.84 1.02 4.48 13.90 1.07 4.69 13.84 1.11 4.91 13.70 1.17 5.12 13.34 1.21 5.31 13.12 1.26 5.52 12.98 1.31 5.76 12.73 1.37 6.00 80 85 90 95 100 105 110 115 LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 12.17 1.07 4.73 11.95 1.11 4.93 11.74 1.16 5.14 11.54 1.21 5.36 11.37 1.26 5.58 11.19 1.31 5.81 11.04 1.37 6.06 10.86 1.42 6.31 EVAP AIR — EWB (F) 62.00 67.00 12.50 12.83 1.07 1.05 4.74 4.65 12.35 12.72 1.11 1.10 4.95 4.86 12.10 12.62 1.16 1.15 5.16 5.08 11.90 12.50 1.21 1.20 5.38 5.31 11.68 12.35 1.26 1.25 5.60 5.54 11.47 12.17 1.31 1.30 5.83 5.78 11.28 11.93 1.37 1.35 6.07 6.01 11.02 11.59 1.42 1.41 6.31 6.25 LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. 42 72.00 13.23 1.03 4.57 13.19 1.08 4.79 13.06 1.13 5.00 12.95 1.17 5.21 12.80 1.23 5.45 12.63 1.28 5.68 12.44 1.33 5.92 12.19 1.39 6.17 COOLING PERFORMANCE (cont) 52PQ 12,000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 350 CFM TEMP (F) AIR ENT. COND (40% RH) 80 85 90 95 100 105 110 115 MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 11.79 0.97 4.29 11.60 1.02 4.49 11.39 1.07 4.69 11.17 1.12 4.90 11.66 1.17 5.12 12.16 1.22 5.34 12.69 1.27 5.57 13.23 1.32 5.81 EVAP AIR — EWB (F) 62.00 67.00 11.95 12.65 0.97 0.95 4.27 4.17 11.74 12.48 1.02 1.00 4.48 4.38 11.49 12.28 1.07 1.04 4.68 4.59 11.24 12.05 1.12 1.09 4.90 4.80 10.97 11.78 1.17 1.14 5.12 5.02 10.70 11.50 1.22 1.20 5.34 5.25 10.45 11.17 1.27 1.25 5.57 5.48 10.19 10.83 1.32 1.30 5.81 5.72 ALL 15,000 NOMINAL BTUH MODELS Evaporator entering air temp. — 80 F Evap. air — 320 CFM TEMP (F) AIR ENT. COND (40% RH) 72.00 13.17 0.93 4.08 12.97 0.97 4.27 12.79 1.02 4.48 12.58 1.07 4.69 12.33 1.12 4.91 12.04 1.17 5.13 11.75 1.22 5.36 11.39 1.27 5.59 80 85 90 95 100 105 110 115 LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I MBtuh kW I 57.00 — — — — — — — — — 12.98 1.67 7.32 12.78 1.74 7.63 12.51 1.81 7.95 12.24 1.88 8.27 11.95 1.96 8.62 EVAP AIR — EWB (F) 62.00 67.00 14.77 15.82 1.39 1.36 6.09 6.00 14.55 15.63 1.45 1.43 6.38 6.27 14.20 15.39 1.53 1.49 6.72 6.56 13.85 15.08 1.61 1.56 7.05 6.85 13.51 14.79 1.68 1.63 7.37 7.16 13.03 14.39 1.75 1.70 7.68 7.48 12.54 13.91 1.82 1.78 8.00 7.80 12.05 13.54 1.89 1.85 8.32 8.14 72.00 16.74 1.33 5.85 16.59 1.40 6.14 16.39 1.46 6.43 16.15 1.53 6.73 15.85 1.60 7.03 15.48 1.67 7.35 15.04 1.75 7.67 14.53 1.82 8.00 LEGEND EWB — Entering Wet Bulb I — Compressor Current Amps kW — Total Power MBtuh — Total Cooling Capacity (Btuh in thousands) RH — Relative Humidity NOTES: 1. Total current (I) based on 230-volt system. 2. Evaporator entering dry bulb air temperature is 80 F. COOLING SENSIBLE HEAT FACTORS (SHF) AT 80 F INDOOR DB MODEL 52PC,PE,PQ,CE,CQ All 7,000 Nominal Btuh Models All 9,000 Nominal Btuh Models 52CQ 12,000 Nominal Btuh Models 52CE,PC,PE 12,000 Nominal Btuh Models 52PQ 12,000 Nominal Btuh Models All 15,000 Nominal Btuh Models INDOOR WB (F) 57 62 67 72 57 62 67 72 57 52 67 72 57 62 67 72 57 62 67 72 57 62 67 72 80 0.91 0.89 0.71 0.53 0.93 0.86 0.67 0.51 0.94 0.88 0.69 0.50 0.92 0.89 0.68 0.51 0.93 0.89 0.69 0.51 — 0.86 0.67 0.50 85 0.91 0.90 0.72 0.53 0.93 0.87 0.67 0.51 0.94 0.89 0.69 0.51 0.91 0.89 0.69 0.51 0.93 0.90 0.70 0.51 — 0.86 0.67 0.50 LEGEND DB — Dry Bulb WB — Wet Bulb 43 OUTDOOR AMBIENT DB TEMPERATURE (F) 90 95 100 105 0.91 0.91 0.91 0.90 0.91 0.91 0.92 0.92 0.72 0.74 0.74 0.75 0.54 0.54 0.54 0.55 0.93 0.93 0.92 0.92 0.88 0.89 0.90 0.91 0.68 0.70 0.70 0.70 0.51 0.51 0.52 0.52 0.94 0.94 0.94 0.94 0.91 0.92 0.93 0.93 0.70 0.70 0.71 0.72 0.52 0.52 0.53 0.53 0.90 0.90 0.90 0.90 0.90 0.90 0.91 0.92 0.70 0.72 0.72 0.73 0.51 0.51 0.52 0.53 0.93 0.93 0.93 0.93 0.91 0.92 0.93 0.93 0.71 0.71 0.72 0.73 0.52 0.52 0.53 0.53 — 0.91 0.91 0.91 0.86 0.87 0.88 0.89 0.68 0.68 0.69 0.70 0.51 0.51 0.51 0.52 110 0.90 0.91 0.76 0.55 0.92 0.92 0.71 0.52 0.94 0.93 0.73 0.54 0.90 0.92 0.74 0.53 0.93 0.93 0.74 0.53 0.91 0.90 0.71 0.52 115 0.90 0.91 0.77 0.56 0.92 0.92 0.72 0.53 0.94 0.93 0.74 0.54 0.90 0.92 0.75 0.54 0.93 0.93 0.75 0.54 0.90 0.91 0.71 0.53 SOUND DATA (52P AND 52C) INDOOR SOUND DATA (52P AND 52C) The tables below indicate the approximate indoor and outdoor sound levels. Tests were conducted in the Carrier Sound Testing Laboratory according to ARI (Air Conditioning and Refrigeration Institute) Noise Rating Standard 300 for non-ducted indoor airconditioning equipment. INDOOR SOUND ESTIMATING TABLE OPERATING VOLTS MODE LOW COOL HIGH COOL FAN LOW HEAT HIGH HEAT 208 230 265 208 230 265 208 230 265 208 230 265 208 230 265 INDOOR SOUND ESTIMATING TABLE (dBA) Nominal Sizes (Btuh) 52PQ and 52CQ 52PC, PE and 52CE 7000 9000 12000 15000 7000 9000 12000 15000 52.6 51.2 55.2 59.3 51.4 54.4 55.4 59.3 54.5 54.2 57.6 59.3 54.4 56.5 57.4 59.3 54.5 53.9 57.6 59.3 54.4 55.4 57.4 59.3 57.1 57.1 61.4 63.7 56.9 58.9 61.8 63.7 57.9 57.8 63.0 63.7 57.9 58.8 63.0 63.7 57.9 58.9 63.0 63.7 57.9 58.3 63.0 63.7 56.3 57.1 61.1 63.7 56.3 57.1 61.1 63.7 57.2 57.7 62.4 63.7 57.2 57.7 62.4 63.7 57.2 57.1 62.4 63.7 57.2 57.1 62.4 63.7 50.7 53.7 55.4 59.5 50.8 50.8 54.5 58.8 53.9 53.8 59.5 59.5 54.1 54.1 57.7 58.8 53.9 53.8 59.5 59.5 54.1 53.6 57.7 58.8 56.5 56.2 61.9 65.0 56.3 57.1 61.1 63.7 57.2 57.8 63.0 65.0 57.2 57.7 62.4 63.7 57.2 57.8 63.0 65.0 57.2 57.1 62.4 63.7 INDOOR SOUND ESTIMATING TABLE (BELS) Nominal Sizes (Btuh) 52PQ and 52CQ 52PC, PE and 52CE 7000 9000 12000 15000 7000 9000 12000 15000 5.3 5.1 5.5 5.9 5.1 5.4 5.5 5.9 5.5 5.4 5.8 5.9 5.4 5.7 5.7 5.9 5.5 5.4 5.8 5.9 5.4 5.5 5.7 5.9 5.7 5.7 6.1 6.4 5.7 5.9 6.2 6.4 5.8 5.8 6.3 6.4 5.8 5.9 6.3 6.4 5.8 5.9 6.3 6.4 5.8 5.8 6.3 6.4 5.6 5.7 6.1 6.4 5.6 5.7 6.1 6.4 5.7 5.8 6.2 6.4 5.7 5.8 6.2 6.4 5.7 5.7 6.2 6.4 5.7 5.7 6.2 6.4 5.1 5.4 5.5 6.0 5.1 5.1 5.5 5.9 5.4 5.4 6.0 6.0 5.4 5.4 5.8 5.9 5.4 5.4 6.0 6.0 5.4 5.4 5.8 5.9 5.7 5.6 6.2 6.5 5.6 5.7 6.1 6.4 5.7 5.8 6.3 6.5 5.7 5.8 6.2 6.4 5.7 5.8 6.3 6.5 5.7 5.7 6.2 6.4 OUTDOOR SOUND ESTIMATING TABLE OPERATING VOLTS MODE LOW COOL HIGH COOL FAN LOW HEAT HIGH HEAT 208 230 265 208 230 265 208 230 265 208 230 265 208 230 265 OUTDOOR SOUND ESTIMATING TABLE (dBA) Nominal Sizes (Btuh) 52PQ and 52CQ 52PC, PE and 52CE 7000 9000 12000 15000 7000 9000 12000 15000 53.9 52.6 54.9 61.1 51.0 53.1 55.5 61.1 55.3 55.0 57.7 61.1 54.2 56.3 57.7 61.1 55.3 55.0 57.7 61.1 54.2 55.2 57.7 61.1 56.7 57.7 60.1 64.4 56.2 57.6 60.2 64.4 58.9 58.9 62.2 64.4 57.2 58.7 62.6 64.4 58.9 58.1 62.2 64.4 57.2 58.8 62.6 64.4 55.5 57.7 61.3 64.0 55.5 57.7 61.3 64.0 56.4 58.7 63.0 64.0 56.4 58.7 63.0 64.0 56.4 58.7 63.0 64.0 56.4 58.8 63.0 64.0 54.7 54.3 57.8 63.9 51.2 51.2 55.0 58.7 57.6 57.3 59.7 63.9 54.8 54.8 57.9 58.7 57.6 56.6 59.7 63.9 54.8 54.9 57.9 58.7 58.2 59.6 62.2 66.5 55.5 57.9 61.3 64.0 59.9 60.4 63.8 66.5 56.4 58.7 63.0 64.0 59.9 57.8 63.8 66.5 56.4 58.8 63.0 64.0 OUTDOOR SOUND ESTIMATING TABLE (BELS) Nominal Sizes (Btuh) 52PQ and 52CQ 52PC, PE and 52CE 7000 9000 12000 15000 7000 9000 12000 15000 5.4 5.3 5.5 6.1 5.1 5.3 5.6 6.1 5.5 5.5 5.8 6.1 5.4 5.6 5.8 6.1 5.5 5.5 5.8 6.1 5.4 5.5 5.8 6.1 5.7 5.8 6.0 6.4 5.6 5.8 6.0 6.4 5.9 5.9 6.2 6.4 5.7 5.9 6.3 6.4 5.9 5.8 6.2 6.4 5.7 5.9 6.3 6.4 5.6 5.8 6.1 6.4 5.6 5.8 6.1 6.4 5.6 5.9 6.3 6.4 5.6 5.9 6.3 6.4 5.6 5.9 6.3 6.4 5.6 5.9 6.3 6.4 5.5 5.4 5.8 6.4 5.1 5.1 5.5 5.9 5.8 5.7 6.0 6.4 5.5 5.5 5.8 5.9 5.8 5.7 6.0 6.4 5.5 5.5 5.8 5.9 5.8 6.0 6.2 6.7 5.6 5.8 6.1 6.4 6.0 6.0 6.4 6.7 5.6 5.9 6.3 6.4 6.0 5.8 6.4 6.7 5.6 5.9 6.3 6.4 SOUND TRANSMISSION CLASS (STC) = 25 44 WIRING DIAGRAMS (52P AND 52C) COMPONENT LEGEND Component Connection (Marked) CAP COMP FM FCS HTR IT OFT OL PLS RVS SLS ST SW — — — — — — — — — — — — — Component Connection (Unmarked) Accessory or Optional Wiring To Indicate Common Potential Only Not To Represent Wire Capacitor Compressor Fan Motor Fan Cycle Switch Heater Indoor Thermostat Outdoor Frost Thermostat Overload Primary Limit Switch Reversing Valve Solenoid Secondary Limit Switch Start Thermistor Switch NOTES: 1. Recommended for use on grounded power supply only. 2. Compressor and fan motor thermally protected. 3. Use copper conductors only. 4. All wiring must conform with N.E.C. and local codes. 5. Dashed lines indicate components when used. 6. OFT determines whether to bring on compressor heat or electric heat. 52PQ and 52CQ — Typical Wiring Schematic for Standard Heat Pump Units 45 WIRING DIAGRAMS (52P AND 52C) (cont) TYPICAL THERMOSTAT INTERFACE T’STAT OUTPUT: RC CONTROLER OUTPUT: UNIT OPERATION: ‘G’ — 24 VAC ‘FR’ — LINE VAC FAN ‘G’ — 0 VAC ‘FR’ — 0 VAC ‘Y’ — 24 VAC ‘HR1 & HR2’ — LINE VAC HEATING ‘O’ — 0 VAC ‘RVR’ — LINE VAC ‘W’ — 24 VAC ‘HR1 & HR2’ — LINE VAC HEATING ‘Y’ — 24 VAC ‘CR’ — LINE VAC COOLING ‘O’ — 24 VAC ‘RVR’ — 0 VAC ‘R’ — 24 VAC ‘R’ — 24 VAC OUTPUT POWER TO WALL ‘C’ — COMMON ‘C’ — COMMON THERMOSTAT 1. If ‘W’ is ON, then ‘FR’ is forced ON (regardless of ‘G’) & ‘CR’ is forced OFF. 2. If ‘Y’ is ON, then ‘FR’ is forced ON (regardless of ‘G’). 3. If IFT (indoor coil) is < 20° F, then ‘CR’ is forced OFF until IFT is > 50° F. COMPONENT LEGEND Component Connection (Marked) FM — Fan Motor ST — Start Thermistor Component Connection (Unmarked) HTR — Heater TRANS — Transformer Terminal Board Connection IFT — Indoor Frost Thermostat PCBD — Printed Circuit Board Field Splice OFT — Outdoor Frost Thermostat — HR1 — Heater Relay Field Control Wiring OL — Overload — HR2 — Heater Relay Accessory or Optional Wiring PLS — Primary Limit Switch — CR — Compressor Relay To Indicate Common Potential Only Not To Represent Wire RVS — Reversing Valve Solenoid — FR — Fan Relay — RVR — Reversing Valve Relay CAP — Capacitor SLS — Secondary Limit Switch COMP — Compressor SSS — Speed Selector Switch NOTES: 1. Recommended for use on grounded power supply only. 2. Compressor and fan motor thermally protected. 3. Use copper conductors only. 4. All wiring must conform with N.E.C. and local codes. 5. Dashed lines indicate components when used. 6. Field control wire suitable for N.E.C. class 2 control circuit, at 24 volts. 7. OFT determines whether to bring on compressor heat or electric heat. 52PQ and 52CQ — Typical Wiring Schematic for Wall Thermostat Control Heat Pump Units 46 52PE and 52CE — Typical Wiring Schematic for Standard Heat/Cool Units 47 WIRING DIAGRAMS (52P AND 52C) (cont) 52PE and 52CE — Typical Wiring Schematic for Wall Thermostat Control Heat/Cool Units 48 FRONT DESK SWITCH PANEL ROOM 100 ROOM 101 ROOM N FIELD-SUPPLIED 24-V TRANSFORMER (SEE NOTE 1) B W PTAC #1 AWG B PTAC W — — — — B B W W PTAC #N PTAC #2 LEGEND American Wire Gage Black Packaged Terminal Air Conditioner White NOTES: 1. To size transformer, use the following equation: Quantity of PTAC units x 12 va = Transformer Size (va) Example: 110 PTAC Units x 12 va = 1320 va Transformer 2. Following are recommended wire sizes: AWG WIRE SIZE NO. MAXIMUM LENGTH (ft) 24 22 20 18 16 400 600 900 1500 2000 Typical Wiring Schematic for Energy Management Kit 49 WIRING DIAGRAMS (52P AND 52C) (cont) MASTER PTAC R R Y Y W W G G O O C C T’STAT R UNIT 1 Y W G O C R UNIT 2 Y W G O C All units must be connected to same ground source. To accomplish this, be sure to connect all units to the same breaker box. Failure to do so may cause damage to the unit. R UNIT 3 Y W NOTES: 1. Do not daisy chain R (24 VAC). 2. Maximum of 4 PTAC units can be connected to one single wall thermostat. 3. Wall thermostat wire is field-supplied and should be 18 to 20 gage solid thermostat wire. G O C Typical Wiring for Multiple PTAC Units Connected to a Single Wall Thermostat 50 GUIDE SPECIFICATIONS PACKAGED TERMINAL COOLING UNIT WITH HEAT PUMP OR ELECTRIC HEATING HVAC Guide Specifications Size Range: 1.03 DELIVERY, STORAGE, AND HANDLING A. The packaging of the chassis shall be sufficient to protect the chassis from damage during shipment via an enclosed truck. Chassis must also be able to withstand an impact force of 10 g’s and a random continuous force of 1g, during shipping. B. Chassis, wall sleeves, and grilles shall be shipped in separate cartons. Universal handling instructions shall be defined and visible on the carton, from front, back and sides. C. Chassis shall be capable of withstanding temperatures from –40 F to 155 F, at 5 to 95 percent RH, non-condensing, during shipment and storage, without component failure. D. Unit shall be stored and handled per manufacturer’s recommendations. Cooling: Heating: 6,900 to 15,100 Btuh 6,000 to 14,100 Btuh Heat Pump 6,400 to 17,000 Btuh Electric Carrier Model Numbers: 52PC Premier Series, Cooling Only 52PE Premier Series, Cooling with Electric Heat 52PQ Premier Series, Heat Pump with Electric Heat 52CE Comfort Series, Cooling with Electric Heat 52CQ Comfort Series, Heat Pump with Electric Heat Part 2 — Products 2.01 EQUIPMENT A. General: Factory-assembled, single-piece heating and/or cooling unit. Contained within the unit enclosure shall be compressor, coils, fans and fan motor, heating means, controls, all wiring and piping, and a full refrigerant charge (R-22). Packaged Terminal Air Conditioners shall be of the sizes and capacities as shown on the contract drawing schedule and in the specifications. B. Chassis: The chassis shall be a factory-assembled, singlepiece heating and/or cooling unit, that is simple to install and operate. Just slide the chassis into a wall sleeve, plug it into an outlet, and operate after installation. The chassis dimensions shall not exceed 42 in. wide and 16 in. high with room cabinet in place. The chassis shall consist of the following functional sections and components: 1. Operating Characteristics: Chassis shall be capable of starting and running at 115 F ambient outdoor temperature per maximum load criteria of ARI Standard 310/ 380. 2. Electrical: Chassis shall be equipped with a 58 in. power cord for 208/230 v models or a 15 in. power cord for 265 v models. The chassis current draw shall be specified on the chassis nameplate and match electrical requirements specified on the Contract drawing schedule and specifications. The power cord plug configuration shall conform to NEMA standards and the rating shall support the current draw of the electric resistance heater. For 265 v installations, UL codes require the use of an electrical equipped subbase for power cord usage or hardwire conduit for noncorded installations. C. Airflow System: The airflow system shall consist of one permanent split-capacitor, direct-drive permanently lubricated, two-speed fan motor for the indoor and outdoor fans. The outdoor fan shall be a dynamically balanced, corrosion-resistant polymer multi-blade Part 1 — General 1.01 SYSTEM DESCRIPTION Single piece, thru-the-wall electrically controlled unit using hermetic rotary compressor for cooling and heat pump or electric resistance heat, as shown on the contract drawings. A. Insulated Polymer Wall Sleeve: Wall sleeve shall provide excellent thermal insulation, be textured to hide scratches and prevent shine, will have superior outdoor noise absorption and shall be corrosion free for the life of the product. The Wall Sleeve must have dimensions of 42 in. width x 16 in. height x 147/8 in. depth and be shipped with a rear weather barrier installed. B. Wall Sleeve Molding: Molding shall trim the wall sleeve to the existing wall, to hide wall imperfections and irregularities in the wall opening. C. Outdoor Polymer Louvered Grille: Outdoor grille shall resist corrosion, breakage and match the color specified on drawing schedule and specifications. D. Subbase: Subbase will support the wall sleeve when it extends into the room more than 4 inches. Subbase must come from the factory pre-assembled, with a built in receptacle (size as specified on drawing schedule and specifications) or with factoryinstalled hardwire, pre-sized for an exact fit to the unit. 1.02 QUALITY ASSURANCE System shall be approved and certified by UL and UL, Canada. Chassis capacity and efficiency performance shall be certified in accordance with ARI standard 310/380. Chassis shall meet ASHRAE Standard 90.1 for minimum energy efficiency. Chassis shall meet the New York City Department of Building, Material and Equipment acceptance requirement (MEA). 51 GUIDE SPECIFICATIONS (cont) D. E. F. G. axial flow design, with integrated slinger ring. The indoor fan shall be a dynamically balanced, polymer, reverse curve blower wheel, to assure uniform air distribution. The Fan Motor shall be of an enclosed design to reduce the effects of moisture and corrosion. Compressor and Refrigerant: The rotary-type Compressor shall be fully hermetic with internal and external vibration isolation. The refrigeration system will be sealed and contain a full refrigerant charge (R-22). Coils: Condenser and evaporator coils to be constructed of high-efficiency, 11 element lance sine wave enhanced aluminum fins and 3/8-in. seamless axial grooved copper tubing, necessary to achieve EER and COP rating, as specified on the chassis nameplate. Factory-Installed Electric Heater: The factory-installed, open coil type, electric heater is standard in heat/cool and heat pump chassis. The electric heater shall contain both an automatic reset and a one-shot overtemperature protection device. The heating capacity of the electric heater shall be as identified on the Contract drawing schedule and in the specifications. Controls: All standard models shall be equipped with electromechanical controls to simplify the serviceability of the unit. 1. The chassis shall have standard controls, accessible and covered by a hinged door. The mode selection control shall consist of a mechanical rotary selector switch, which provides OFF, FAN ONLY, HEAT or COOL operations. The temperature selection control shall be an adjustable thermostat with upper and lower limits. 2. All standard models shall have a continuous/ fan cycle selector switch located behind the front panel. It shall allow the selection of continuous fan operation for maximum comfort or cycle operation (fan only runs with cooling or heating operation) for maximum energy savings. 3. All standard models shall have a Temperature Limiter control located behind the front panel. The temperature limiter allows a room temperature range to be set, to avoid extreme temperature settings, to maximize energy savings. 4. Emergency Heat Switch (Heat Pump Models Only) shall disable the compressor in heating mode and only allow the use of electric heat during heating cycles. The Emergency Heat switch is active at all outdoor ambient temperatures. 5. Wall thermostat chassis (RC and RP models) shall come from the factory ready for wall thermostat installation, including a blank out plate in place of the control knobs. No fieldinstalled kits or wire harnesses shall be required. 6. Wall thermostat chassis (RC and RP models) shall have a user selectable fan speed control H. I. J. K. L. M. N. O. 52 switch, on the control panel, to optimize fan speed for maximum comfort. Safeties: Compressor shall have automatic reset, overtemperature and overcurrent protection. The fan motor shall have an inherent, automatic reset overtemperature protection. The electric heater shall have two overtemperature protectors. Front Panel (supplied with chassis): Front panel shall be constructed of a polymer material to resist breakage and corrosion. It shall have a front louvered surface with integrated control door and air filters. The air filters shall be easily accessible without removing the front panel from the chassis. Anti-Theft Control Knobs: All chassis knobs shall resist breakage and corrosion. They shall be mounted on to the control box section and captured behind the front panel, to prevent unauthorized removal. Bi-Directional Discharge Grille: Bi-directional polymer discharge grille shall resist corrosion and breakage. It shall be easily set to direct air at 40 degrees from horizontal or 80 degrees from horizontal. This non-metallic discharge grille shall be cool to the touch during the heating cycle. Ventilation: The chassis shall have a manual adjustable fresh air vent with a concealed manual control. The vent control shall allow a maximum of 50 cfm of fresh air to be drawn into the room when the indoor fan is operating and the door is open. The ventilation air can be increased to approximately 95 cfm by adding the Booster Ventilation accessory kit (see section Q.13) High-Efficiency Condensate Removal System: The chassis shall have a condensate removal system consisting of a condensate suction port, to draw and atomize condensate, and a slinger ring integrated in the outdoor fan, to disperse condensate onto the condenser coil to be evaporated. Snow Baffle: The chassis shall contain a snow baffle to prevent melting snow from freezing and potentially damaging the outdoor fan. Corrosion Protection (CP and RP Models Only): Chassis with Corrosion Protection (CP,RP) shall be used for coastal or corrosive environments, to prolong the life of the product. Minimum requirements are: 1. All outdoor-exposed sheet metal parts shall be coated with a polyester powder coat paint. 2. Compressor and outdoor-fan motor finish shall be capable of withstanding 500 hours of salt spray testing per ASTM B-117. 3. Compressor mounting screws shall be SermaGuard™ coated. 4. Outdoor coil fin stock shall be coated and able to withstand 1000 hours of salt spray testing per ASTM B-117. 5. Outdoor coil tube sheets shall be made of 316L stainless steel. P. Lateral Duct System (optional): The lateral duct system shall allow one system to heat or cool two adjacent rooms, with up to a maximum of 30% of the discharge air being diverted to the adjoining room (a return air path must be provided from the adjoining room). The lateral duct kit consists of two main components, the plenum and the extension duct. In addition, the kit includes an adjustable chassis discharge air grille, adjustable wall register and decorative wall molding for duct extension. The Lateral Duct system shall be adaptable for either right or left side ducting, with a maximum duct extension of 4 feet. The duct run must be straight and horizontal; no bends or turns. Q. Accessories: 1. Insulated Polymer Wall Sleeve (P/N: SLEEVE-INSUL-1PK) shall be made from a molded polymer, with factory-installed Styrofoam insulation and a minimum flammability rating of UL94-5V. The sleeve surface shall be textured to prevent shine and hide scratches. 2. Deep Wall Metal Wall Sleeve (up to 28-in.) (P/N: SLEEVE-EXTxx-1PK) shall be a onepiece, extended wall sleeve, with factory installed insulation and deep wall baffles integrated. 3. Sleeve Molding (P/N: SLEEVE-MOLDING) shall trim the wall sleeve to the existing wall to hide wall joints and irregularities due to the sleeve opening. 4. Architectural Grille (P/N: GRILLE-PLAxxxxx or GRILLE-ALU-xxxxx) shall be polymeric for long durable life or painted aluminum for a superior color match to the building. 5. Subbase (P/N: SUBBASE-xxxV-xxA) shall be pre-assembled from the factory and UL listed. Subbase options include: Non-electrical subbase: The non-electrical subbase shall be pre-assembled and provides mechanical support and requires no wiring. Electrical subbase: The electrical subbase shall be pre-assembled with factory-installed electrical junction box containing a receptacle for corded units. Hardwired subbase: The hardwired electrical subbase shall be pre-assembled with factory installed electrical junction box containing 19 in. of flexible conduit (for a perfect fit to the unit) and all mating connections. 6. Leveling Legs (P/N: LEVELING-LEGS) shall attach easily to Carrier’s wall sleeve to provide accurate, adjustable leveling and support to units without a subbase. 7. Hardwire Kit (P/N: HARDWIRE-KIT) shall provide a permanent connection to the unit. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 53 The hardwire kit mounts on the front right side of the unit and shall have 36 in. of flexible steel conduit and a Molex connector for easy connect/disconnect. Conduit Interface Kit (P/N: CONDUIT-INTF4PK) shall provide wire connection to the unit to interface with field-supplied conduit. Condensate Drain (P/N: DRAIN-KIT-4PK) kit shall be used internally or externally to route excess condensate to a drainage system. It can be field-installed on any Carrier wall sleeve. The drain kit shall be attached to the exterior right or left side of the wall sleeve for external draining or may be mounted to the bottom of the wall sleeve for internal draining. Lateral Duct (P/N: LATERAL-DUCT) kit shall include an adapter plenum, extension duct, wall register and wall molding. The lateral duct system allows one system to heat or cool two adjacent rooms, by directing up to 30% of the airflow to the adjacent room. See section 4.0 for detailed specification. Energy Management (P/N: EM-KIT) shall allow individual units to be turned on and off from a remote location or by a motion sensing device. This kit interfaces to most energy management systems. Lateral Air Deflector (P/N: DEFLECTOR1PK) shall allow right or left air distribution from the chassis. Lateral air deflectors are recommended for units mounted in a corner or off-center in a room. Curtain Deflector (P/N: CURTDEL-52CP1PK) shall prevent curtains from being blown into the discharge air. Security door (P/N: SECURITY-DOOR) kit shall prevent unauthorized access to the unit’s heating and cooling controls and prevents tampering with units in public locations and institutions. The security door shall include two matching keys and keys shall be common to all Carrier Security Door kits. Wall Thermostats (P/N: TSTATCCBxx01-B) shall operate with 24 VAC, be digital and non-programmable, easy-to-use and provide maximum guest comfort. Sleeve Molding (P/N: SLEEVE-MOLDING) shall trim the wall sleeve to the existing wall to hide wall joints and irregularities due to the sleeve opening. Power Fresh Air Vent (P/N: PWR-VENTDOORxxx) kit shall provide approximately 95 cfm of outdoor air for ventilation into the room. The kit shall have an automatically door that opens when the fan is on and closes when the fan is off. 54 NOTE: Service and Maintenance items excluded in this warranty may be covered by a separate service agreement through the seller at time of purchase. CARRIER WILL NOT BE RESPONSIBLE FOR: 1. CLEANING REQUIRED PRIOR TO WARRANTY REPAIR. 2. Standard maintenance, cleaning or damage resulting from failure to perform normal maintenance as outlined in the owner’s manual. 3. Instruction on methods of control and use of air conditioning unit after initial installation. 4. Damage or repairs needed as a consequence of faulty installation or application. This is the responsibility of the installer. 5. Failure to start due to voltage conditions, blown fuses, open circuit breakers or any other damages due to the inadequacy or interruption of electrical services. 6. Damage or repairs needed as a consequence of any misapplication, abuse, unauthorized alteration, improper servicing or operation. 7. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environment, or other conditions beyond the control of CARRIER. EXCEPTION TO CORROSIVE ENVIRONMENT IN ABOVE PARAGRAPH — Packaged terminal units (52 Series) built with corrosion protection are exempt from the exclusion — “Corrosive Environment.” The unit model number is identified on the nameplate with a CP suffix. 8. Reimbursement for replacement parts or repair services which are not supplied or designated by CARRIER and which are specifically covered under this warranty. 9. CARRIER products installed outside the continental U.S.A., Alaska, Hawaii and Canada. 10. Shipping damage or damage as a result of transporting the unit. This is the responsibility of the selling dealer or the authorized Room Air Conditioner service station. 11. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE WHATSOEVER. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. 12. Warranty coverage of accessory items (wall thermostats, wall sleeves, etc.). Catalog No. 530-122 (Rev. 3/02) This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. *Authorized independent dealers or service stations are registered with Carrier Air Conditioning through its distributor organization. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY. LIMITATION OF WARRANTIES — ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN AND APPLIES. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER. LIMITED EXTENDED FOUR-YEAR WARRANTY ON NON-SEALED REFRIGERATION SYSTEM ONLY — During the second through fifth years after date of original purchase, Carrier will, through its authorized servicing dealers and service stations and free of charge to the end user or subsequent users, repair or replace any non-sealed system part (motor, solenoid, thermistor, thermostat, relays, switch, capacitor, overload, drain valve, bulb heater, fan, stator) if defective in material or workmanship. The replacement part can be new or a remanufactured part at CARRIER’S sole option. THIS LIMITED WARRANTY DOES NOT INCLUDE LABOR, user is responsible for labor, including cost of diagnosis of problem, removal and transportation of the air conditioner to and from the service center, and reinstallation charges necessary to accomplish repair. FULL EXTENDED FOUR-YEAR WARRANTY ON SEALED REFRIGERATION SYSTEM ONLY — During the second through fifth years after date of original purchase, CARRIER will, through its authorized servicing dealers and service stations* and free of charge to the end user or subsequent users, repair or replace the compressor, condenser, evaporator or connecting tubing if defective in material or workmanship. This includes system refrigeration charge. The replacement part can be new or a remanufactured part as provided at CARRIER’S sole option. FULL ONE-YEAR WARRANTY — During the first year after purchase, CARRIER will, through its authorized independent servicing dealers or service stations*, and free of charge to the user or subsequent users, repair or replace any parts which are defective in material or workmanship. The replacement part can be a new or remanufactured part as provided at CARRIER’S sole option. Carrier Packaged Terminal Air Conditioner Warranty TYPICAL WARRANTY 55 2. CONTACT YOUR DEALER OR THE RECOMMENDED CARRIER AUTHORIZED SERVICE CENTER. They have been set up to handle the great majority of all possible service problems. The quickest, surest and best way to get your air conditioner back in service is to use this step before proceeding further. 1. CHECK THE THINGS YOU CAN DO YOURSELF. These include being sure the air conditioner is plugged in firmly in an appropriate receptacle, checking the fuse or circuit breaker and ensuring its replacement or resetting, if necessary, and rereading the instruction book to ensure that all controls are set properly. By doing this you can save money. Many unnecessary service calls result in the serviceman doing what the owner can do for him or herself. 4. CONTACT CARRIER IF A SATISFACTORY SOLUTION IS NOT REACHED IN STEPS 2 AND 3. Carrier Air Conditioning Consumer Relations Department Carrier Parkway, P.O. Box 4808 Syracuse, New York 13221 Telephone: 1-800-894-6449 3. CONTACT THE CARRIER DISTRIBUTOR SERVING YOUR AREA. Your dealer can provide the distributor’s name or you can consult your yellow pages. IF YOUR AIR CONDITIONER DOES NOT WORK, FOLLOW THESE STEPS IN ORDER: Carrier Corporation ACCESSORY LIST ACCESSORY Wall Sleeves Exterior Grilles* FORM NUMBER PART NUMBER 52S-48SI WALL-SLEEVE-1PK WALL-SLEEVE-9PK SLEEVE-INSUL-1PK 52S-50SI SLEEVE-STEEL-1PK 52S-49SI SLEEVE-EXT18-1PK SLEEVE-EXT24-1PK SLEEVE-EXT26-1PK SLEEVE-EXT28-1PK N/A SLEEVE-MOLDING 52C,P-26SI FR-SLEEVE-EXT 52C,P-28SI 52S-59SI 52C,P-29SI 52C,P-11SI CM-SLEEVE-EXT GRILLE-ALU-STAMP GRILLE-PLA-BROWN GRILLE-PLA-BEIGE GRILLE-PLA-ALPIN GRILLE-ALU-CLEAR GRILLE-ALU-WHITE GRILLE-ALU-BRONZ GRILLE-ALU-MBRNZ GRILLE-ALU-BROWN GRILLE-ALU-BEIGE GRILLE-ALU-ALPIN GRILLE-ALU-PEACH GRILLE-ALU-MELON GRILLE-ALU-LGREY GRILLE-ALU-SGREY GRILLE-ALU-RDBRK GRILLE-ALU-BLUE GRILLE-ALU-GREEN BAFFLE-KIT-1PK SUBBASE-NON-ELEC SUBBASE-230V-15A SUBBASE-230V-20A SUBBASE-230V-30A SUBBASE-265V-15A SUBBASE-265V-20A SUBBASE-265V-30A SUBBASE-HARDWIRE SUBBASE-SWITCH SUBBASE-FUSE-15A SUBBASE-FUSE-20A SUBBASE-FUSE-30A LEVELING-LEGS HARDWIRE-KIT-1PK 52C,P-19SI CONDUIT-INTF-4PK 52S-53SI DRAIN-KIT-4PK N/A HH01AD045 TSTATCCBPC01-B TSTATCCBPH01-B TSTATCCPAC01-B TSTATCCPHP01-B RC-FIELDKIT230HC 52S-65SI 52S-60SI Subbase 52C,P-31SI 52C,P-1SI 52C,P-2SI 52C,P-17SI Subbase Field-Installed Kits Sleeve Support Electrical Connections Condensate Drain Kit Wall Thermostats 52C,P-3SI 52C,P-4SI 52C,P-5SI DESCRIPTION Non-Insulated Polymer Wall Sleeve, 1 per pack Non-Insulated Polymer Wall Sleeve, 9 per pack Insulated Polymer Wall Sleeve, 1 per pack Insulated Metal Wall Sleeve, 1 per pack Extended Metal Wall Sleeve for Deep Wall Applications (18 in. deep), 1 per pack Extended Metal Wall Sleeve for Deep Wall Applications (24 in. deep), 1 per pack Extended Metal Wall Sleeve for Deep Wall Applications (26 in. deep), 1 per pack Extended Metal Wall Sleeve for Deep Wall Applications (28 in. deep), 1 per pack Molding kit to trim the wall sleeve to the wall Friedrich wall sleeve extension to retrofit Carrier PTAC unit into Friedrich 111/2″ deep (T Series) wall sleeve. 1 per pack Climate Master Wall Sleeve extension to retrofit Carrier PTAC unit into Climate Master 121/2″ deep wall sleeve. 1 per pack Stamped Aluminum Exterior Grille, Clear Finish Polymer Architectural Rear Grille, Brown Polymer Architectural Rear Grille, Beige Polymer Architectural Rear Grille, Alpine (matches Carrier Wall Sleeve) Aluminum Architectural Exterior Grille, Clear Finish Aluminum Architectural Exterior Grille, White Aluminum Architectural Exterior Grille, Light Bronze Aluminum Architectural Exterior Grille, Medium Bronze Aluminum Architectural Exterior Grille, Brown (Dark Bronze) Aluminum Architectural Exterior Grille, Beige Aluminum Architectural Exterior Grille, Alpine (matches Carrier Wall Sleeve) Aluminum Architectural Exterior Grille, Peach Aluminum Architectural Exterior Grille, Melon Aluminum Architectural Exterior Grille, Light Grey Aluminum Architectural Exterior Grille, Slate Gray Aluminum Architectural Exterior Grille, Red Brick Aluminum Architectural Exterior Grille, Blue Aluminum Architectural Exterior Grille, Green Ensures good air seal and prevents air recirculation when Carrier sleeve is used with a non-Carrier grille. Non-electrical Subbase Electrical subbase with factory-installed 208/230V, 15 amp receptacle Electrical subbase with factory-installed 208/230V, 20 amp receptacle Electrical subbase with factory-installed 208/230V, 30 amp receptacle Electrical subbase with factory-installed 265V, 15 amp receptacle Electrical subbase with factory-installed 265V, 20 amp receptacle Electrical subbase with factory-installed 265V, 30 amp receptacle Electrical subbase with factory-installed hardwire kit (230/208V and 265V) Field-Installable Switch kit for an electrical subbase Field-Installed Fuse Kit (15 amp) for electrical subbase Field-Installed Fuse Kit (20 amp) for electrical subbase Field-Installed Fuse Kit (30 amp) for electrical subbase Attaches to wall sleeve for accurate and adjustable leveling and support for units without a subbase Permanent power connection to the unit (includes 36″ of flexible conduit and unit-mounted connector, 230/208V and 265V) 1 per pack Interface kit for field-supplied conduit to provide permanent power connection (230/208V and 265V) to the unit. Kit includes Molex connector for easy connect/disconnect. 4 per pack Attaches to wall sleeve for controlled internal or external disposal of condensate-4 per pack N/A 2SPEED-TSTAT-KIT 2SPEED-RCFAN-KIT TSTAT-COVER-6X7 N/A TSTAT-COVER-7X10 Replacement Filters Energy Management Locking Security Control Door Lateral Duct Kit Power Vent Retrofit Kit Air/Curtain Deflector N/A AIR-FILTER-10PK Electro-mechanical Wall Thermostat (Heat/Cool and Heat Pump) Value Series Electronic Thermostat w/Digital display (Heat/Cool Models) Value Series Electronic Thermostat w/Digital display (Heat Pump Models) 7-Day Programmable Electronic Thermostat (Heat/Cool Models) 7-Day Programmable Electronic Thermostat (Heat Pump Models) Field-installed wall thermostat retrofit kit to convert a standard 230V Heat/Cool unit to an RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC). Field-installed wall thermostat retrofit kit to convert a standard 230V Heat Pump unit to an RC unit. Wall thermostat sold separately. Field-installed wall thermostat retrofit kit to convert a standard 265V Heat/Cool unit to an RC unit. Wall thermostat sold separately (can be used to convert a cool only unit to RC). Field-installed wall thermostat retrofit kit to convert a standard 265V Heat Pump unit to a RC unit. Wall thermostat sold separately. Field-installed automatic heat/cool changeover thermostat with 2-speed fan control at thermostat. Multiple fan speed control relay only. Thermostat is not included. Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with non-programmable and electro-mechanical thermostats. Outside dimensions: 61/2″ x 71/2″ x 215/16″. 1 per pack Clear plastic locking thermostat cover prevents unauthorized access to thermostat. Cover for use with programmable thermostats. Outside dimensions: 71/4″ x 93/4″ x 33/8″. 1 per pack Replacement air filters in package of 10 52C,P-24SI EM-KIT Allows unit to be turned on and off from a remote location (includes freeze guard protection) 52C,P-23SI SECURITY-DOOR Key-locking security door to prevent access to heating and cooling controls 52C,P-25SI 52C,P-32SI 52C,P-9SI 52C,P-21SI LATERAL-DUCT PWR-VENT-DOOR230 PWR-VENT-DOOR265 DEFLECTOR-1PK CURTDFL-52CP-1PK Touch-Up Paint N/A CARRIER-TOUCH-UP Ductwork to allow one unit to heat and cool two rooms (plenum plus extension duct and registers) Power vent with automatic door that opens and closes when the fan turns on and off (230V). Power vent with automatic door that opens and closes when the fan turns on and off (265V). Lateral air deflector, with individually adjustable louvers, to enhance air circulation, 1 per pack Curtain deflector for 52C and 52P models — prevents curtains from blowing into discharge air stream. 1 per pack. NOTE: Curtain deflector for previous models are also available. Contact Carrier Representative. Touch up paint for repainting scratches or chips. Wall Thermostat Interface Retrofit Kit 52C,P-30SI RC-FIELDKIT230HP RC-FIELDKIT265HC RC-FIELDKIT265HP 52C,P-34SI *Custom colors are also available. 56
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Page Mode : UseOutlines XMP Toolkit : 3.1-701 Create Date : 2003:05:29 16:20:08Z Creator Tool : ADOBEPS4.DRV Version 4.20 Modify Date : 2005:11:09 18:52:23-05:00 Metadata Date : 2005:11:09 18:52:23-05:00 Format : application/pdf Creator : Carrier Corporation Title : Description : Subject : Producer : Acrobat Distiller 4.0 for Windows Keywords : Document ID : uuid:3659d114-2f7a-47a1-89ae-0a92e7002ab4 Instance ID : uuid:3eab78a6-ad9c-4321-88e9-e17456fca344 Page Count : 56 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools