Carrier T 298 Users Manual
T--298 to the manual ade90665-5195-4046-a0b1-f9a4d5925d23
2015-01-24
: Carrier Carrier-T-298-Users-Manual-310558 carrier-t-298-users-manual-310558 carrier pdf
Open the PDF directly: View PDF .
Page Count: 49
Download | |
Open PDF In Browser | View PDF |
Transport Air Conditioning R 2P BLK 1 BRN WHT BLU 2 GRN/YEL F WHT C EVAP. RED RED H BLU WHT R YEL 1 C 2 BLU PTC S SERVICE MANUAL for MODEL AirV Rooftop Air Conditioning Systems T--298 Rev D SERVICE MANUAL For AirV AIR CONDITIONING AND HEATING EQUIPMENT MODELS 68RV11302A 68RV14102A 68RV14103A 68RV14112A 68RV15102A 68RV15103A SAFETY SUMMARY GENERAL SAFETY NOTICES The following general safety notices supplement the specific warnings and cautions appearing elsewhere in this manual. They are recommended precautions that must be understood and applied during operation and maintenance of the equipment covered herein. The general safety notices are presented in the following three sections labeled: First Aid, Operating Precautions and Maintenance Precautions. A listing of the specific warnings and cautions appearing elsewhere in the manual follows the general safety notices. FIRST AID An injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately. OPERATING PRECAUTIONS Always wear safety glasses. Keep hands clear of the evaporator blower and condenser fan. No work should be performed on the unit until all circuit breakers and start--stop switches are turned off, and power supply is disconnected. Always work in pairs. Never work alone. In case of severe vibration or unusual noise, stop the unit and investigate. MAINTENANCE PRECAUTIONS Beware of unannounced starting of the evaporator blower & condenser fan. Do not remove the ceiling grill assembly or the upper unit cover assembly before turning the power off, and disconnecting the power supply. Before disconnecting, discharge capacitors by shorting across the capacitors terminals. (See Paragraph 3.5.8) When disassembling wiring, use numbered stickers to identify wire leads and terminals. This aids in quick, accurate reassembly. Be sure power is turned off before working on motors, controllers, or electrical control switches. Tag any circuit breakers and power supply to prevent accidental energizing of circuits. Do not bypass any electrical safety devices, e.g. bridging an overload, or using any sort of jumper wires. Problems with the system should be diagnosed and any necessary repairs must be performed by qualified service personnel. In case of electrical fire, open circuit switch and extinguish with CO2 (never use water). Use dry nitrogen to pressurize the system for leak checking. Be careful not to exceed 150 psig test pressure in the hermetic compressor. Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury. Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use. Disconnect power to the AirV unit before checking the capacitor. Safety-- i T-298 SPECIFIC WARNING AND CAUTION STATEMENTS The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These recommended precautions must be understood and applied during operation and maintenance of the equipment covered herein. SPECIFIC WARNINGS AND CAUTIONS WARNING Be sure to observe warnings listed in the safety summary in the front of this manual before performing maintenance on the AirV system WARNING Before working on the unit be sure to first disconnect all electric power to the unit to avoid the possibility of electrical shock and personal injury. Before disconnecting, discharge capacitors by shorting across the capacitors terminals (Refer to paragraph 3.5.8) WARNING Shield coils with cardboard to protect hands against injury from sharp metal edges when removing compressor and other components. WARNING Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use. WARNING Disconnect power to the AirV unit before checking the capacitor. WARNING Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock. WARNING Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death. CAUTION Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sections. T--298 Safety-- ii CAUTION Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury. CAUTION The change from Fahrenheit to Celsius will be permanent. It cannot be changed back to Fahrenheit. CAUTION When re--assembling, ensure the battery springs are correctly placed in the battery spring holders. CAUTION Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes. Safety-- iii T-298 TABLE OF CONTENTS PARAGRAPH NUMBER Page DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 SERIAL NUMBER IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.3 DESIGN CHANGE DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.4 AirV SYSTEM COMPONENT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.4.1 Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.4.2 Compressor - 115 Volts, 60 Cycles, 1 Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.4.3 Compressor - 220 Volts, 50 Cycles, 1 Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.4.4 Thermostat Range (All Free Blow Units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.5 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.6 REFRIGERANT CYCLE-STANDARD SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 1.7 REFRIGERANT CYCLE - HEAT PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10 1.7.1 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10 1.7.2 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1 NO POWER TO UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.2 DUCTED UNIT WILL NOT OPERATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.3 DUCTED UNIT WILL NOT COOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.4 COMPRESSOR POWER SUPPLY OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY . . . . . . . . . . . . . . . . . . . . 2-1 2.6 CYCLES ON COMPRESSOR OVERLOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.8 CONDENSER AIR NOT ADEQUATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.9 INSUFFICIENT COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.10 COMPRESSOR FLOODING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY) . . . . . . . . . . . . . . . . . . . . . 2-2 2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.13 WATER LEAKAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2.14 INADEQUATE HEAT (FREE-BLOW HEAT ONLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 2.15 INADEQUATE HEAT (HEAT-PUMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Clearing Diagnostic Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 SERVICE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.1 PREVENTATIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.2 SERVICE - GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.3 CEILING UNIT - FREE BLOW SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.3.1 Filter Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.3.2 Ceiling Grill Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.3.3 Ceiling Panel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3.3.4 Master Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3.3.5 Air Sweep Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3.3.6 Indoor Thermostat Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3.3.7 Air Sweep Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3.3.8 Heat Strip Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 i T--298 TABLE OF CONTENTS - Continued 3.4 CEILING UNIT - DUCTED SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3.4.1 Filter Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3.4.2 Ceiling Grill Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3.4.3 Control Box Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3.4.4 Main PCB Board Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3.4.5 PCB Display Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3.4.6 Fuse Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 SERVICE - UPPER UNIT - STANDARD, HC & HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3.5.1 Exterior Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3.5.2 Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 3.5.3 Control Box Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 3.5.4 Upper Scroll Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3.5.5 Motor Assembly and Condenser Fan Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3.5.6 Evaporator Blower Wheel Adjustment or Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 3.5.7 Air Handling System Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 3.5.8 Capacitor Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 3.5.9 Capacitor Testing and Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting . . . . . 3-9 3.5.11 Line Voltage - 10% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 SERVICE - UPPER UNIT - LOW PROFILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 3.6.1 Exterior Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 3.6.2 Upper Scroll Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 3.6.3 Condenser Fan Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 3.6.4 Condenser Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 3.5 3.6 3.6.5 Evaporator Motor/Blower Assembly Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 3.6.6 Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3.6.7 Capacitor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3.6.8 Remote Control (Fahrenheit to Celsius) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 THERMOSTAT INSTALLATION AND START-UP INSTRUCTIONS (WALL MOUNTED) . . . . . . . . 3-15 3.7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.7.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.7.3 Thermostat Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.7.4 Install Thermostat - 12VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.7 3.8 LCD DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.8.1 Cool Only Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.8.2 Heat/Cool Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 SET THERMOSTAT CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.9.1 Enter Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 3.10 CHECK THERMOSTAT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3.10.1 Fan Operation (Cool Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3.10.2 Fan Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3.9 3.10.3 Cooling Operation (Cool Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3.10.4 Cooling Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3.10.5 Heating Operation (Heat/Cool) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 T--298 ii TABLE OF CONTENTS - Continued 3.11 CHECK THERMOSTAT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.11.1 Temperature Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.11.2 Timeguard Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.11.3 Cycle Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.11.4 Minimum On Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.11.5 Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16 3-16 3-17 3-17 3-17 3-17 4-1 4-1 LIST OF FIGURES FIGURE NUMBER Figure 1-1 Model/Serial Number Plate (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-2 Roof Unit Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-3 Ceiling Unit Component Identification (Free-Blow) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-4 Component Identification - Low Profile - Upper Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-5 Component Listing-Ceiling Unit For Ducted Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-6 Ducted System Air Flow Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-7 Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-8 Refrigerant Flow Schematic (Standard System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-9 Refrigerant Flow Schematic - Heat Pump - (Cool Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-10 Refrigerant Flow Schematic - Heat Pump - (Heat Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-1 Filter Removal - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-2 Ceiling Grill - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-3 Ceiling Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-4 Ceiling Panel With Heat Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-5 Control Box Assembly - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-6 Indoor Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-7 Air sweep motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-8 Heat Strip Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-9 Filter Removal - Ducted Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-10 Ceiling Grill - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-11 Control Box & PCB Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-12 Control Box Assembly - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-13 Main/Display PCB’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-14 Cover Assembly - Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-15 Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-16 Control Box Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-17 Water Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-18 Upper Scroll Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-19 Motor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-20 Spring Clamp Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-21 Motor Clip Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-22 Condenser Fan Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-23 Blower Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-24 Condenser With Motor Assembly & Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-25 Set-Up For Discharging a Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii Page 1-1 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 3-1 3-2 3-2 3-2 3-2 3-3 3-3 3-3 3-4 3-4 3-4 3-5 3-5 3-5 3-6 3-6 3-6 3-7 3-7 3-7 3-7 3-8 3-8 3-8 3-9 T--298 LIST OF FIGURES Figure 3-26 Cover Assembly - Low Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-27 Upper Scroll Assembly Locking Tabs (b.) & Screw Locations (c.) . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-28 Upper Scroll Assembly Keeper Tab Release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-29 Upper Scroll & Control Box Cover Removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-30 Condenser Fan Assembly & Retaining Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-31 Condenser Fan Motor & Fan Assembly Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-32 Condenser Fan Motor & Fan Assembly Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-33 Condenser Motor Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-34 Evaporator Motor Locking Tabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-35 Evaporator Motor/Blower Assembly In Cradle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-36 Evaporator Blower Wheel (Flush With End Of Motor Shaft) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-37 Control Box Assembly With Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-38 Remote Control Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-39 Remote Control PCB (FR9 Location) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-40 Wall Thermostat Wiring Diagram - Cool Only Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3-41 Wall Thermostat Wiring Diagram - Heat/Cool Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-1 Upper Unit Schematic - Standard & HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-2 Upper Unit Schematic - Low Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-3 Ceiling Unit Schematic - Cooling Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-4 Ceiling Unit Schematic - Heat/Cool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-5 Ceiling Unit, Standard - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-6 Heat Pump - Upper Unit - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-7 Heat Pump - Ceiling Unit - Free Blow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-8 Heat Pump - Upper Unit - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4-9 Heat Pump - Ceiling Unit - Ducted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 3-10 3-10 3-11 3-11 3-11 3-11 3-12 3-12 3-12 3-13 3-13 3-14 3-14 3-17 3-18 4-1 4-1 4-2 4-2 4-2 4-3 4-3 4-4 4-4 LIST OF TABLES TABLE NUMBER Page Table 1-1 Model Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Table 1-2 Additional Support Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Table 2-1 System Self-diagnostics Function (Ducted Remote) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 T--298 iv SECTION 1 DESCRIPTION 1.1 INTRODUCTION MODEL No. This manual contains service instructions and electrical data for the AirV, Carrier Transport Air Conditioning’s Recreational Vehicle air conditioning unit. Part No. 68RV14102A 99--00468--01 115 VOLTS The AirV units are two piece systems, consisting of the Upper Unit and the Ceiling unit. The Upper Unit contains the refrigeration system while the Ceiling Unit contains the controls and vents. The Ceiling Units are available in a free--blow or ducted configuration. Carrier Air Conditioning C Division of Carrier Corporation ph CAPACITY USE 20 AMP The free--blow units (see Figure 1-2) deliver air to the vehicle by means of front and rear end vents and one downward vent (air shower). The vents may all be opened or closed to direct air as desired. The front and rear vents are fitted with motorized dampers that oscillates to produce an “air--sweep” effect. These units may be fitted with optional electric heat. TIME DELAY FUSE OR CIRCUIT BREAKER AMPS DATE OF Mfg SERIAL No. 1 V hz 13,500 60 Btu/h 3,955 W 13.5 A 05/03 1303Y12345 DESIGN PSIG HIGH 350 LO 150 oz 15.9 kg 0.45 COMPRESSOR RLA 12.5 FAN MOTOR FLA 2.58 R--22 The ducted units (see Figure 1-5 and Figure 1-6) deliver air through ducting built in the vehicle ceiling. These units are fitted with a 12 VDC microprocessor control system, a display panel (PCB display) and a remote controller. These units may be wired to provide thermostatic control of the vehicle furnace. USE CEILING ASSY/ANY 99--00469--01 Figure 1-1 Model/Serial Number Plate (Typical) Carrier’s AirV air conditioning models include cooling only units, heating/cooling units, and heat pump units. The cooling only units are available with free blow or ducted air delivery. Cooling units with heat strips are available for free blow only. 1.3 DESIGN CHANGE DESCRIPTIONS The following list provides a description of changes in design and serial number breaks for those changes. 1400Y A diode was added to the Ducted Ceiling assembly control board to stop DC ripple from the converters, 2900Y Cover screw coating was changed in order to eliminate corrosion. 3400Y The plastic shroud was modified to improve drainage. 5100Y A new compressor and capacitor is introduced, improving stability and increasing capacity. 1201Y The temperature sensor was moved to the grill to improve temperature sensing during furnace mode, 2501Y The dual air sweep was added. 4501Y A switch was added to skip compressor malfunction test. 4601Y Change in material was made in order to strengthen the fan propeller. 4901Y The mounting bolt lengths were increased 3/4 inch. 4901Y The polar white ducted ceiling color was cut--in. 0703Y & 1903Y New style PCB -- Cool Mode -- Control & Power Assembly (Fans shut off in auto mode). 0803Y & 2603Y New style PCB -- Heat Pump -- Control & Power Assembly (Fans shut off in auto mode). 4204Y Minimum furnace setpoint lowered from 63°F to 45°F. Operation of the AirV units is controlled automatically by the temperature controller (thermostat), which maintains the vehicle’s interior temperature at the desired set point. Free Blow, cool--only units are available with a wall mounted thermostat. Table 1-1 lists model numbers and descriptions of the AirV units, and Table 1-2 lists additional support manuals that are available. 1.2 SERIAL NUMBER IDENTIFICATION Separate part numbers and serial numbers are provided for the upper and lower unit assemblies The numbers may be found on a plate readable from inside the vehicle, See Figure 1-7. The first two numbers of the serial number, see Figure 3-22, is the week the unit was manufactured. For example, 01 would designate the first week of the year and 52 would designate the last week of the year. The third and fourth numbers designate the year in which the unit was manufactured. For example, 99 would represent the year 1999, 00 the year 2000, and so on. The letter Y and all the numbers after it designates the unit serial number. Example: Y43210 A serial number of 1303Y12345 designates that the unit was manufactured the 13th week of 2003 and the serial number is Y12345. 1-1 T--298 Model Number 115V Standard System 68RV14102A 220V Standard System 68RV11302A High Capacity 68RV15102A Heat Pump Systems 68RV14112A LOW PROFILE 68RV15103A LOW PROFILE 68RV14103A Model Number Table 1-1. Model Chart UPPER UNIT (ROOF) Part Number Voltage 99--00468--00 115/1/60 99--00468--01 115/1/60 99--00468--02 220/1/50 99--00468--03 220/1/50 99--00468--08 115/1/60 99--00468--09 115/1/60 99--00468--04 115/1/60 (Free Blow) 99--00468--05 115/1/60 (Free Blow) 99--00468--06 115/1/60 (Ducted) 99--00468--07 115/1/60 (Ducted) 99--00468--10 (Free Blow -- High Capacity) 99--00468--12 (Free Blow -- Standard) CEILING UNIT Voltage 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 (12VDC) 220/1/50 220/1/50 220/1/50 220/1/50 115/1/60 115/1/60 115/1/60 (12VDC) 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 Amps 12.8 12.8 5.3 Cool 6.7 Heat 14.5 14.5 12.7 Cool 10.9 Heat 12.7 Cool 10.9 Heat 12.7 Cool 10.9 Heat 12.7 Cool 10.9 Heat 15.1 Cool 13.8 Heat 15.0 Cool 13.7 Heat Ivory White Ivory White White 68RV0011LA 68RV0010AB 68RV0010AB 68RV0010BB 68RV0010BB 68RV0040MA 99--00469--22 115/1/60 White Cool Only Interface Free Blow Free Blow Free Blow Free Blow Ducted Free Blow Free Blow Free Blow Ducted Free Blow Free Blow Ducted Free Blow Free Blow Free Blow Free Blow Ducted Wall Thermostat 68RV0010DB 99--00469--29 115/1/60 White Cool Only Free Blow Wall Thermostat 68RV0010BA 68RV0010KA 68RV0030AA 68RV0030BA 68RV0030KA 68RV0012CA T--298 1-2 Options Cool Only Cool Only Heat/Cool Heat/Cool Cool Only Cool Only Cool Only Heat/Cool Cool Only Heat Pump Heat Pump Heat Pump Cool Only Cool Only Heat/Cool Heat/Cool White Part Number 99--00469--00 99--00469--01 99--00469--02 99--00469--03 99--00469--06 99--00469--04 99--00469--05 99--00469--08 99--00469--10 99--00469--11 99--00469--12 99--00469--13 99--00469--23 99--00469--24 99--00469--25 99--00469--26 68RV0010AA Color White Ivory White Ivory White White Ivory White White White Ivory White White Ivory White Ivory Color White Ivory White Ivory White Ivory MANUAL--FORM NO. Table 1-2 Additional Support Manuals EQUIPMENT COVERED TYPE OF MANUAL (For) PART NO. 99--00469--00 99--00469--01 71LC6A54310 AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide 71LH6A54070 AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide 99--00469--02 99--00469--03 71LD6A54070 AirV 115 Volts--Ducted (Cool Only) Owner’s Guide 99--00469--06 71LH6A54070 AirV 220 Volts--Free Blow (Heat--Cool) Owner’s Guide 99--00469--08 99--00469--09 71RQ6A5401A AirV 115 Volts--Free Blow (Heat Pump) Owner’s Guide 99--00469--11 99--00469--12 71DQ6A5401A AirV 115 Volts--Ducted (Heat Pump) Owner’s Guide 99--00469--13 71DW6A54070 AirV 115 Volts--Ducted Wired Thermostat Owner’s Guide 99--00469--22 71LC6A54310 AirV 115 Volts--Free Blow (Cool Only) Owner’s Guide 99--00469--23 99--00469--24 71LH6A54070 AirV 115 Volts--Free Blow (Heat--Cool) Owner’s Guide 99--00469--25 99--00469--26 71RW6A54310 T--298PL 62--50455--00 AirV 115 Volts--Free Blow Wired Thermostat AirV Basic refrigeration Owner’s Guide Service Parts Service Training 99--00469--29 ALL ALL 1 2 3 4 5 1. 2. 3. Cover Condenser Evaporator 4. 5. Compressor Base Pan Figure 1-2 Roof Unit Component Identification 1-3 T--298 1 2 3 4 1. 2. Ceiling Panel Assembly Control Box Cover 3. 4. Control Assembly Ceiling Grill Assembly Figure 1-3 Ceiling Unit Component Identification (Free--Blow) T--298 1-4 1 2 3 4 5 9 6 7 8 10 11 1. 2. 3. 4. 5. 6. Cover Assembly Scroll Assembly -- Upper Condenser Fan Condenser Motor Evaporator Motor Evaporator Blower Wheel 7. 8. 9. 10. 11. Condenser Coil Scroll Assembly -- Lower Evaporator Coil Compressor Base Pan Assembly See Figure 1-3 for Ceiling Package (Free--Blow) Figure 1-4 Component Identification -- Low Profile -- Upper Unit 1-5 T--298 1 2 3 12 11 10 4 5 6 7 9 8 1. 2. 3. 4. 5. 6. Telescoping Divider (3 different sizes available) Divider Assembly Frame Panel, Insulation Assembly Control Box Assembly Control Box Cover Suction Packing Assembly 7. 8. 9. 10. 11. 12. Remote Control Assembly Remote Control Bracket Assembly Filter Assemblies (2) PCB Cover PCB Main Assembly PCB Display Figure 1-5 Component Listing--Ceiling Unit For Ducted Systems T--298 1-6 1 2 3 5 4 SCHEMATIC VIEW 1 SUPPLY AIR 5 2 1 3 SUPPLY AIR 4 RETURN AIR INSTALLED VIEW 1. 2. 3. Vehicle Duct System (Connection) 4. Control Box Assembly Telescoping Divider (3 different sizes available) 5. Supply Air Discharge Area Return Air Suction Area Figure 1-6 Ducted System Air Flow Arrangement 1-7 T--298 Serial number of Upper Unit Upper Unit Serial Number of Ceiling Unit Ceiling Unit (Cover Removed) Free Blow Type Serial Number of Ceiling Unit (Side of Control Box) Ceiling Assembly Frame Bottom of Upper Unit Ducted Type Serial Number of Upper Unit Bottom View After Installation (With Grille Removed) Figure 1-7 Serial Number Locations T--298 1-8 1.4 AirV SYSTEM COMPONENT SPECIFICATIONS d. Fully Loaded Amps -- High Capacity Cooling -- Approx. 14.5 AMPS Heating -- Approx. 11 AMPS 1.4.1 Refrigerant Charge Standard -- High Capacity -- Heat Pump R--22 -- 15.9 Ounces Low Profile (All) R--22 -- 16.9 Ounces 1.4.2 Compressor -- 115 Volts, 60 Cycles, 1 Phase a. Locked Rotor Amps -- Standard -- High Capacity -- Heat Pump 64.5 AMPS6 b. Locked Rotor Amps -- Low Profile High Capacity 59.0 AMPS c. Fully Loaded Amps -- Standard Cooling -- Approximate 12.8 AMPS Heating -- N/A e. Fully Loaded Amps -- Low Profile Cooling -- Approx. 14.1 AMPS Heating -- Approx. 13.8 AMPS f. Fully Loaded Amps -- Heat Pump Cooling -- Approx. 12.8 AMPS Heating -- Approx. 11 AMPS 1.4.3 Compressor -- 220 Volts, 50 Cycles, 1 Phase a. Locked Rotor Amps 23.6 AMPS 1.4.4 Thermostat Range (All Free Blow Units) 61° F (16° C) to 89° F (32° C) 1.5 START--UP Refer to operating instructions in Owners Guide (see Table 1-2) packaged with the vehicle system. CAPILLARY TUBE DISCHARGE LIQUID EVAPORATOR SUCTION ACCUMULATOR COMPRESSOR STRAINER CONDENSER Figure 1-8 Refrigerant Flow Schematic (Standard System) 1.6 REFRIGERANT CYCLE--STANDARD SYSTEM The evaporator blower (fan) pulls vehicle air through the filters, which remove particulate matter, and then pass the cleaned air through the evaporator coil. The cooling cycle is energized when the thermostat, located on the ceiling unit, calls for cooling. The main components of the system are the compressor, air-cooled condenser coil, strainer, capillary tube, evaporator coil and accumulator. The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line into the condenser coil. (See Figure 1-8.) The condenser fan circulates surrounding air (which is at a temperature lower than the refrigerant) over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside the tubes) to the air (flowing over the tubes). The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air. This removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through a strainer to the capillary tube. The strainer removes any impurities within the refrigerant system. The capillary tube meters the flow of liquid refrigerant to the evaporator coil. As the refrigerant flows through the capillary tube, there is a reduction in pressure and temperature. The low pressure, low temperature liquid that flows into the evaporator coil tubes is colder than the air that is circulated over the tubes. Heat transfer is established from the vehicle air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The evaporator coil tubes have aluminum fins to increase heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the vehicle. The transfer of heat from the air to the low temperature liquid refrigerant in the indoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats. When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off. 1-9 T--298 1.7 REFRIGERANT CYCLE -- HEAT PUMP DISCHARGE LIQUID INDOOR COIL CAPILLARY TUBE SUCTION STRAINER REVERSING VALVE ACCUMULATOR COMPRESSOR OUTDOOR COIL Figure 1-9 Refrigerant Flow Schematic -- Heat Pump -- (Cool Mode) capillary tube, there is a reduction in pressure and temperature. The indoor blower (fan) pulls inside air through the filters, which remove particulate matter, and then pass the cleaned air through the indoor coil. The low pressure, low temperature liquid that flows into the indoor coil tubes is colder than the air that is circulated over the tubes. Heat transfer is established from the indoor air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The indoor coil tubes have aluminum fins to increase heat transfer from the air to the refrigerant; therefore the cooler air is circulated to the interior of the vehicle. The transfer of heat from the air to the low temperature liquid refrigerant in the indoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats. When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off. 1.7.1 Cooling The cooling cycle is energized when the thermostat, located in the ceiling unit, calls for cooling The system controls are positioned for “normal” refrigerant flow, with the compressor discharge delivered to the outdoor coil and liquid delivered to the indoor coil. (See Figure 1-9.) The main components of the system are the compressor, reversing valve, air-cooled outdoor coil, strainer, capillary tube, indoor coil, and the accumulator. The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line and reversing valve into the outdoor coil. The outdoor fan circulates surrounding air (which is at a temperature lower than the refrigerant) over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside the tubes) to the outdoor air (flowing over the tubes). The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through the strainer to the capillary tube. The strainer removes any impurities within the refrigerant system. The capillary tube meters the flow of liquid refrigerant to the indoor coil. As the refrigerant flows through the T--298 1-10 DISCHARGE INDOOR COIL CAPILLARY TUBE LIQUID SUCTION STRAINER REVERSING VALVE ACCUMULATOR COMPRESSOR OUTDOOR COIL Figure 1-10 Refrigerant Flow Schematic -- Heat Pump -- (Heat Mode) outdoor coil. The strainer removes any impurities within the refrigerant system. The capillary tube meters the flow of liquid refrigerant to the outdoor coil. As the refrigerant flows through the capillary tube, there is a reduction in pressure and temperature. The low pressure, low temperature liquid that flows into the outdoor coil tubes is colder than the outdoor air that is circulated over the tubes. Heat transfer is established from the outdoor air (flowing over the tubes) to the refrigerant (flowing inside the tubes). The outdoor coil tubes have aluminum fins to increase heat transfer from the air to the refrigerant. The transfer of heat from the air to the low temperature liquid refrigerant in the outdoor coil causes the liquid to vaporize. This low temperature, low pressure vapor passes into the accumulator. The accumulator is designed with the inlet tube delivering refrigerant to the bottom of the tank and the outlet tube taking refrigerant form the top of the tank. This arrangement ensures that only vapor refrigerant is returned to the compressor, where the cycle repeats. When ventilation only is selected, the indoor fan functions to circulate air throughout the vehicle. The refrigerant cycle will remain off. 1.7.2 Heating The heating cycle is energized when the thermostat, located in the ceiling unit, calls for heat The system controls are positioned for “reverse” refrigerant flow, with the compressor discharge delivered to the indoor coil and liquid delivered to the outdoor coil. (See Figure 1-10.) The main components of the system are the compressor, reversing valve, indoor coil, capillary tube, strainer, air-cooled outdoor coil, and the accumulator. The compressor raises the pressure and the temperature of the refrigerant and forces it through the discharge line and reversing valve into the indoor coil. The indoor blower (fan) pulls inside air through the filters, which remove particulate matter, and then pass the cleaned air through the indoor coil. The vehicle air (which is at a temperature lower than the refrigerant) passes over the outside of the coil tubes. Heat transfer is established from the refrigerant (inside the tubes) to the vehicle air (flowing over the tubes). The tubes have fins designed to improve the transfer of heat from the refrigerant gas to the air; this removal of heat causes the refrigerant to liquefy, thus liquid refrigerant leaves the coil and flows through the strainer to the 1-11 T--298 SECTION 2 TROUBLESHOOTING For ducted units, the green operation indicator LED (SeeFigure 3-9) will flash if there is a problem. Refer to Table 2--1 for diagnostic information. PROBABLE REMEDY SYMPTOM AND PROBABLE CAUSE 2.1 NO POWER TO UNIT 1. Master switch off 2. Open circuit breaker 3. Defective wiring 4. Loose electrical connections 5. Faulty switches, thermostat, or fan 6. 12 VDC not connected (Ducted System) 7. 12 VDC in--line fuse open (Ducted) 2.2 DUCTED UNIT WILL NOT OPERATE 1. Display not illuminated 2. Display illuminated 2.3 DUCTED UNIT WILL NOT COOL 1. Green LED light flashes 5 times 2. Unit cools for a few moments then stops cooling 1. Reset master switch 2. Reset circuit breaker 3. Replace wiring 4. Tighten connections 5. Replace defective components 6. Connect to 12 VDC power source 7. Replace fuse 1. Check 12 Volt DC in--line fuse 2. Check 115 Volt AC Connections 1. Check 115 volt AC power source Momentarily disconnect 12 VDC power source Disable compressor malfunction test switch. Check AMP draw. Check ∆ T 2. Remove grill, verify evaporator coil probe is inserted into coil. Check AMP draw. Check ∆ T Replace unit 2.4 COMPRESSOR POWER SUPPLY OPEN 1. Loose leads at compressor terminals 1. Tighten leads 2. Defective motor overload switch 2. Replace switch 3. Defective capacitor 3. Replace capacitor -- Refer to Paragraph 3.5.8 4. Open compressor windings 4. Replace compressor 5. Seized compressor 5. Replace compressor 6. Capacitor incorrectly wired 6. Verify capacitor wiring (Refer to wiring diagram) 2.5 COMPRESSOR RUNS BUT CYCLES, FAN OPERATING ERRATICALLY 1. Loose lead at fan motor 1. Tighten lead. 2. Defective or burned out motor 2. Replace motor. 3. Outdoor air restricted or recirculating 3. Check for dirty condenser coil, proper clearance around unit, remove any obstructions. 4. Overcharge or noncondensables in system 4. Check AMP draw 5. Restricted discharge line 5. Check for obstruction in line. Check ∆ T. Replace unit. 6. Defective motor overload switch 6. Replace switch. 2-1 T--298 SYSTEM AND PROBABLE CAUSE 2.6 CYCLES ON COMPRESSOR OVERLOAD 1. Defective run capacitor 2. Defective compressor bearings or valves 3. Greatly restricted evaporator air, iced evaporator coil. 4. Low refrigerant charge 5. Evaporator capillary restricted 6. Liquid line restricted 7. Compressor hot PROBABLE REMEDY 1. Replace capacitor -- Refer to Paragraph 3.5.8 2. Replace unit. 3. Defrost evaporator coil. 4. Replace unit. 5. Replace unit. 6. Replace unit. 7. Verify refrigerant charge. Check AMP draw. Check ∆ T. 8. Weak or inconsistent line power 8. Check line voltage at time of compressor start--up. 2.7 INSUFFICIENT COOLING, COOLING AIR NOT ADEQUATE 1. Dirty evaporator coil 1. Clean as required. 2. Iced evaporator coil, slightly low refrigerant charge 2. Defrost or Recharge. 3. Improper fan operation 3. Verify fan rotation (Refer to wiring diagram) 4. Defective fan motor 4. Replace fan motor. 5. Return air filter is dirty 5. Remove and clean filters (Refer to paragraphs 3.3.1 & 3.4.1) 2.8 CONDENSER AIR NOT ADEQUATE 1. Outside Air Restricted 1. Check for obstruction at coil. Remedy as required. 2. Dirty coil 2. Clean coil. 3. Defective fan motor 3. Replace fan motor. 2.9 INSUFFICIENT COOLING 1. Unit undersized 1. Re--evaluate unit for proper capacity. 2. Capillary restricted 2. Check AMP draw. Check ∆ T. Replace unit. 2.10 COMPRESSOR FLOODING 1. Unit overcharged 1. Check AMP draw. Check ∆ T. Replace unit. 2. Low evaporator airflow 2. Clean filter and/or evaporator coil. 3. Defective electrical connections 3. Check connections per wiring diagram and tighten any loose connections. 2.11 HEATER CYCLES ON LIMIT SWITCH (HEAT/ COOL VERSION ONLY) 1. Dirty filter 1. Clean or replace filter. 2. Blocked evaporator air inlet (indoor) 2. Remove blockage. 3. Low airflow due to fan motor speed 3. Check fan motor. Repair or replace as necessary. 2.12 AIR SWEEP NOT WORKING (FREE BLOW VERSION ONLY) 1. Ceiling grill not properly aligned 1. Align ceiling grill. 2. Linkage in upper control box stuck 2. Align and lubricate linkage. 3. Air sweep motor failure 3. Replace motor. 2.13 WATER LEAKAGE 1. Water dripping from ceiling unit. 1. Verify vehicle is level Tighten unit mounting bolts evenly or replace unit gasket. T--298 2-2 PROBABLE REMEDY SYSTEM AND PROBABLE CAUSE 2.14 INADEQUATE HEAT (FREE--BLOW HEAT ONLY) 1. No heat from heat strip. 1. Verify AMP draw . ( 13.8 AMP) Verify resistance through heating element. (9 OHM) Check bi--metal switch. If open, replace switch. 2.15 INADEQUATE HEAT (HEAT--PUMP) NOTE: Allow unit to operate 15 minutes after switching from cooling mode. 1. Reversing valve not operating 1. Check for 115 volts at reversing valve coil 2. Outdoor coil icing. Check for reversing valve restriction Verify compressor operation 2. Check outdoor coil sensor Clearing Diagnostic Alarms When a repair has been accomplished due to a corresponding alarm, the alarm must be cleared. This is done by disconnecting the 12 VDC power to the ducted ceiling assembly for one or two seconds. Once the 12 VDC power is reconnected, the alarm should have been cleared. 2-3 T--298 Table 2--1 System Self--diagnostics Function (Ducted Remote) Flashes 2 Error Codes Error Contents (Priority) (Malfunction) 1 ROOM AIR THERMISTOR FAILURE Display Pattern 2 3sec . INDOOR COIL THERMISTOR FAILURE 3 FAN Mode FURNACE Mode 0.5 sec (3 Times) 3sec. 3sec . 4 OUTDOOR COIL THERMISTOR FAILURE 4 COMPRESSOR DRIVE MALFUNCTION 3sec . 5 FAN Mode FURNACE Mode 0.5 sec. (5 Times) 3sec . 6 FAN Mode FURNACE Mode 0.5 sec. (4 Times) 3sec. 5 FAN Mode 0.5 sec. (Twice) 3sec . 3 3sec . REVERSING VALVE DRIVE MAL-FUNCTION 6 3sec . DISCHARGE AIR THERMISTOR FAILURE 0.5 sec. (Once) 3sec . Continuous 7 FAN Mode FURNACE Mode 0.5 sec. (6Times) 3sec . 1 Allowed Modes THERMISTOR WIRING WRONG (only in cooling test mode) FAN Mode FURNACE Mode 3sec . 0.5 sec. (Continuous) FAN Mode 3sec . NOTE: If more than two errors occur, the highest ranked code is displayed. If the highest ranked error is cleared, the next highest ranked error code is displayed. T--298 2-4 SECTION 3 SERVICE AND MAINTENANCE 3.1 PREVENTATIVE MAINTENANCE WARNING Cleaning--Clean evaporator coil and condenser coil. Hold flashlight behind coil to see if all spaces are clear. Dust accumulation obstructs or reduces airflow and results in loss of cooling capacity. Both coils may be vacuumed when dry. Coils may also be brushed with a stiff brush and then blown out with compressed air. Before working on the unit be sure to first disconnect all electric power to the unit to avoid the possibility of electrical shock and personal injury. Before disconnecting, discharge capacitors by shorting across the capacitors terminals (Refer to paragraph 3.5.8) Thoroughly clean base pan, motors, fan wheels, and other components. Clean cover and ceiling grill. Mild detergents reduce electrostatic charges on plastic sections of the grill and are good cleaners. WARNING CAUTION Shield coils with cardboard to protect hands against injury from sharp metal edges when removing compressor and other components. Do not use carbon tetrachloride, solvents, or waxes containing solvents to clean plastic sections. 3.3 CEILING UNIT -- FREE BLOW SYSTEMS Painting--Paint any parts that show evidence of rust with a good rust--prevention paint. 3.3.1 Filter Removal The filters (Figure 3-1) are located in the ceiling grill. To remove the filters, do the following: a. Grasp the edge of the filter at recess in the end of the ceiling grill. b. Pull filter completely out of the filter slot. c. Vacuum filter or wash filter in luke--warm water. Shake off excess water and dry thoroughly. d. Replace filter by sliding the filter into the filter slot in the ceiling grill until the filter frame is flush with the interior grill. Wiring-- Check all wiring for deterioration and all electrical contacts for tightness or corrosion. Mounting--Make sure unit is secure on roof according to installation instructions provided in Owner’s Guide. Check fans to insure that they are correctly positioned in the center of the orifice, and tight on the shaft. Leaks--Check any connections that show evidence of oil or leaks. When unit is properly installed (refer to Owner’s Guide) check gaskets for possible air leakage. Controls--Check unit to ensure all controls are functioning correctly and unit operation is normal. Vibrations can cause unwanted noise. Filters NOTE Check to ensure that piping is not vibrating against side of the unit. NOTE For proper cleaning and flushing, use a UL approved refrigerant recovery/recycling system. NOTE Refrigerant removal must always include recovering the refrigerant, not allowing it to escape to the atmosphere. Figure 3-1 Filter Removal -- Free Blow 3.3.2 Ceiling Grill Removal To remove the ceiling grill (Figure 3-2) do the following: a. Before working on unit place the master switch in the OFF position and disconnect all electrical power. b. Remove 4 screws located on the ceiling grill, making sure to support the weight of the grill. c. Lower the ceiling grill from the ceiling panel. 3.2 SERVICE -- GENERAL General Notes—These Service Instructions are provided to assist the trained and qualified Carrier service technician in repairing or replacing components of the AirV units. 3-1 T--298 d. To replace the grill, place the grill up against the ceiling panel and align the screw holes in the grill with the ceiling panel. Heat Strip Connection e. Replace 4 screws. Heater Assembly Option Mounting Screws Figure 3-4 Ceiling Panel With Heat Option 3.3.4 Master Control Switch To remove the master control switch, do the following: a. Remove ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws that secure the control assembly (Item 2, Figure 1-3) to the control box cover. c. Remove the master control switch knob by grabbing the outside edge of the knob and pulling it off of the switch stem. d. Remove 2 screws securing the master control switch to the control assembly. e. Carefully disconnect wires from the master control switch. Label wires to aid in reassembly. f. Reverse above procedure for reassembly. Figure 3-2 Ceiling Grill -- Free Blow 3.3.3 Ceiling Panel Removal To remove the ceiling panel (Figure 3-3) do the following: a. Remove the ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the duct plate to the ceiling panel. c. Remove 4 mounting bolts making sure to support the weight of the ceiling panel. Junction Box With Cover Air Sweep Switch d. Disconnect the unit harnesses and main power wires from the ceiling panel. e. Lower the ceiling panel from the air conditioning unit. f. Reverse above procedure for reassembly. Air Sweep Cam Thermostat Serial/Model Number Tag Duct Plate & Mounting Holes Figure 3-5 Control Box Assembly -- Free Blow 3.3.5 Air Sweep Switch Removal To remove the air sweep switch, do the following: a. Remove ceiling grill. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the control assembly (Item 2, Figure 1-3) to the control box cover. Mounting Bolts Junction Box c. Disconnect wires from the air sweep switch. d. Pinch tabs on either end of the switch and slide out of lower control box cover. e. Reverse above procedure for reassembly. Figure 3-3 Ceiling Panel Assembly T--298 Master Control Switch 3-2 3.3.6 Indoor Thermostat Removal To remove the indoor thermostat (Figure 3-6) do the following: Air Sweep Motor a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Remove 5 screws securing the control assembly (item 3, Figure 1-3) to the control box cover. c. Remove the indoor thermostat knob by grabbing the outside edge of the knob and pulling it off of the thermostat stem. d.Remove 2 screws that secure the indoor thermostat to the lower control box cover. e. Carefully disconnect the 2 wires from the indoor thermostat. f. Remove the sensing bulb from the plastic clip. g. Carefully slide the sensing bulb through the rubber grommet. h. Remove the thermostat from the control assembly. i. Reverse above procedure for reassembly. Figure 3-7 Air sweep motor 3.3.8 Heat Strip Assembly Removal To remove the heat strip assembly (Figure 3-8) do the following: a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Unplug electrical connection at air sweep motor assembly. c. Remove two screws securing heat strip assembly to the ceiling panel assembly. d. Slide heat strip assembly away from air sweep motor assembly and pull down, easing the the electrical connection through the access hole. e. Reverse the procedures for reassembly. Thermostat Sensing Bulb Figure 3-6 Indoor Thermostat 3.3.7 Air Sweep Removal To remove the air sweep, do the following: a. Remove ceiling grille. (Refer to paragraph 3.3.2.) b. Remove cam (See Figure 3-3) from air sweep motor shaft. c. Remove 4 screws securing air sweep motor bracket to the ceiling panel assembly. Heat Strip d. Carefully disconnect air sweep motor wire terminations. e. Remove 2 screws securing air sweep motor (Figure 3-7) to control box and remove motor. f. Reverse above procedure for reassembly. Figure 3-8 Heat Strip Assembly 3-3 T--298 3.4 CEILING UNIT -- DUCTED SYSTEMS c. Remove two screws securing control box cover to control box assembly. See Figure 3-11. 3.4.1 Filter Removal d. Remove control box assembly cover. The filters (Figure 3-9) are located in the ceiling grill. To remove the filters, do the following: a. Grasp the edge of the filter at recess in the end of the ceiling grill. b. Pull filter completely out of the filter slot. c. Vacuum filter or wash filter in luke--warm water. Shake off excess water and dry thoroughly. d. Replace filter by sliding the filter into the filter slot in the ceiling grill until the filter frame is flush with the interior grill. Mounting Screws Filters Figure 3-10 Ceiling Grill -- Ducted e. Disconnect blue furnace wires. f. Unplug two connectors from upper unit. g. Unplug DC power plug #1 (red/yellow/black wires) See Figure 3-12 h. Unplug relay signal plug #2 (brown/red/orange/ yellow wires). See Figure 3-12 Operation Indicators i. While supporting control box assembly remove two screws securing control box assembly to ducted ceiling unit. Figure 3-9 Filter Removal -- Ducted Unit j. Pull control box assembly from the ducted ceiling unit. 3.4.2 Ceiling Grill Removal k. Reverse above procedure to reassemble. To remove the ceiling grill (Figure 3--10) do the following: a. Before working on unit place the master switch in the OFF position and disconnect all electrical power. Control Box b. Remove filters (Refer to paragraph 3.4.1). Control Box Cover Screws c. Remove 4 screws located on the ceiling grill, (two are under the filters) making sure to support the weight of the grill. Fuse d. Lower the ceiling grill from the ceiling panel. e. To replace the grill, place the grill up against the ceiling panel and align the screw holes in the grill with the ceiling panel. f. Replace 4 screws and 2 filters. 3.4.3 Control Box Assembly Removal PCB Cover To remove the control box assembly (Figure 3-11 & Figure 3-12) do the following: PCB Cover Screws a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Disconnect 115 volt (AC) and 12 volt (DC) power wires. T--298 Figure 3-11 Control Box & PCB Cover 3-4 3.4.5 PCB Display Removal 115V AC To remove the PCB display assembly (Figure 3-13) do the following. 12V DC a. Remove ceiling grill. Refer to paragraph 3.4.2. b. Push large clip away from PCB display assembly. c. Push center clip towards large clip. #1 Fuse d. Pull PCB display assembly from PCB cover. e. Unplug display wiring from PCB main assembly. Upper Unit Connectors f. Reverse above procedures of reassembly. Furnace Wires (blue) #2 3.4.6 Fuse Removal To remove the fuse (Figure 3-11) do the following: Figure 3-12 Control Box Assembly -- Ducted a. Remove ceiling grill. Refer to paragraph 3.4.2. 3.4.4 Main PCB Board Removal b. Turn fuse holder in direction of arrow (counter-- clock-wise). To remove the Main PCB board (Figure 3-13) do the following: c. Pull fuse from fuse holder. a. Remove ceiling grill. Refer to paragraph 3.4.2. d. Test and/or replace. b. Remove three screws securing the PCB cover to the ducted ceiling unit. e. Reverse above procedures for reassembly. c. Carefully turn over the PCB cover exposing the PCB main and the PCB display assemblies. 3.5 SERVICE -- UPPER UNIT -- STANDARD, HC & HP d. Gently push holding clip away from PCB main assembly. 3.5.1 Exterior Cover Removal e. Lift PCB main assembly from PCB cover assembly. CAUTION f. Unplug display wiring plug #4. Figure 3-13 g. Unplug thermistor/thermostat Figure 3-13 wiring plug #3. Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury. h. Unplug power wiring plug #1. Figure 3-12 i. Unplug signal wiring plug #2. Figure 3-12 To remove the exterior cover, do the following: j. Reverse above procedures for reassembly. a. Before working on unit place the master switch in the OFF position and disconnect all electrical power. b. Remove 15 screws securing the unit cover to the base pan assembly. See Figure 3-14. Holding Clips c. Carefully lift the exterior cover off of the unit base pan assembly. PCB Display d. Reverse above procedure for reassembly. PCB Main #4 #3 Cover Screws Figure 3-13 Main/Display PCB’s Figure 3-14 Cover Assembly -- Standard 3-5 T--298 3.5.2 Compressor Replacement Observe the same procedures for rotary compressors as for reciprocating compressors. a. Follow all safety codes. Reminder: use protective goggles, work gloves, and water soaked quenching cloth. b. Remove exterior cover. refer to paragraph 3.5.1. Disconnect all wiring from the compressor. c. Apply field--supplied, line--tap--valves to the suction and discharge lines as close to the compressor as possible. d. Recover the refrigerant charge from the unit. After recovering, cut the discharge and suction line process tubes below the tube crimps. If you choose a good tubing location for cutting the refrigeration lines initially, the location is easily accessible when making the final joints. Control Box Screws Figure 3-15 Control Box WARNING Oil vapor in piping stubs can ignite from torch flame and cause serious injury. Exercise extreme care when brazing, and keep brazing cloth and fire extinguisher handy for emergency use. Water Cover e. Connect a nitrogen supply to the unit at one of the line --tap--valve connectors (5--psig maximum flow), leaving the other connector open to the atmosphere. Braze angle valves with stubs to each process tube. f. Remove compressor from unit (3 bolts). g. Remove line--tap--valves from suction and discharge lines. Carefully braze the holes closed from where the line--tap--valves were removed. h. Clean system: add or replace liquid line filter drier. For proper cleaning and flushing use a UL approved refrigerant recycling system. i. Install new compressor and braze into place with field--supplied copper slip couplings. j.Connect wiring: replace wire terminals if necessary. k. Proceed with evacuation and charging (15.9 OZ. -.45 KG R22). Pinch off lines where angle valves were added. Cut off angle valves above pinch--off , and braze tubes. l. Start up unit. 3.5.3 Control Box Assembly Removal Figure 3-16 Control Box Removal c. Slide control box out of the lower scroll assembly. (See Figure 3-16.) d. To open control box remove 2 screws securing the water cover to the control box cover. e. Gently lift the water cover off of the control box. (See Figure 3-17.) f. Reverse above procedure for reassembly. To remove the control box assembly, do the following: a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove 2 screws securing control box assembly to the lower scroll assembly. (SeeFigure 3-15.) T--298 Control Box Cover Figure 3-17 Water Cover Removal 3-6 3.5.4 Upper Scroll Assembly Removal i. Remove condenser fan from motor shaft and lift fan out through the top of the condenser orifice. (See Figure 3-22) a. Remove exterior cover assembly. Refer to paragraph 3.5.1. j. Remove motor assembly. b. Remove 4 screws securing upper scroll assembly to the lower scroll assembly. (See Figure 3-18) k.Reverse above procedure for reassembly. c. Gently pry 4 snap clips open and lift the upper scroll assembly off of the lower scroll assembly. d. Reverse above procedure for reassembly. Screws 4 Places Ground screw Motor Ground Lead Figure 3-19 Motor Assembly Spring Clamp Snap Clip 4 Places Figure 3-18 Upper Scroll Assembly Figure 3-20 Spring Clamp Removal 3.5.5 Motor Assembly and Condenser Fan Removal a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove control box assembly. Refer to paragraph 3.5.3. Motor Clip c. Remove upper scroll assembly. Refer to paragraph 3.5.4. d. Remove 4 screws securing the condenser cover to the condenser orifice. (See Figure 3-24.) e. Carefully disconnect motor wire terminations from within the control box. f. Remove 1 screw securing the motor ground lead to the motor bracket assembly. (See Figure 3-19) g. Using flat--nosed pliers, depress the motor spring clamp and slide it off of the condenser fan (See Figure 3-20). h. Lift and slide motor towards evaporator coil to remove condenser fan from the motor shaft. Figure 3-21 Motor Clip Removal 3-7 T--298 3.5.7 Air Handling System Removal a. Remove exterior cover assembly. Refer to paragraph 3.5.1. b. Remove control box assembly. Refer to paragraph 3.5.3. c. Remove upper scroll assembly. Refer to paragraph 3.5.4. d. Remove motor assembly. Refer to paragraph 3.5.5. e. Remove 8 screws securing lower scroll assembly to the base pan assembly. f. Remove 1 screw from clamp securing suction tube to the base pan assembly. Condenser Fan g. Remove 3 nuts securing the compressor to the base pan assembly. h. Remove 2 screws securing the condenser orifice to the base pan assembly. i. Remove 2 screws securing the condenser coil assembly to the base pan assembly. Figure 3-22 Condenser Fan Removal 3.5.6 Evaporator Blower Wheel Adjustment or Removal a. Remove exterior cover assembly. Refer to Exterior Cover Assembly Removal instructions 3.5.1 b. Remove control box assembly. Refer to Control Box Assembly Removal instructions 3.5.3 c. Remove upper scroll assembly. Refer to Upper Scroll Assembly Removal instructions 3.5.4 d. Loosen motor assembly. Refer to Motor Assembly Removal instructions 3.5.5. e. Mark shaft at a point where wheel hub and motor shaft meet to aid in reassembly.(See Figure 3-23.) f. Remove 1 set screw holding the blower wheel to the motor shaft. (See Figure 3-23) g. Slide off blower wheel from motor shaft h. Reverse above procedure for reassembly. j. Carefully lift the entire assembly off of the base pan assembly. k. Reverse the above procedure for reassembly, ensuring that the air handling system is positioned correctly. Tighten all screws. Compressor Condenser Cover Set Screw Condenser Cover Screws Motor Assembly Base Pan Base Pan Figure 3-24 Condenser With Motor Assembly & Compressor Figure 3-23 Blower Wheel T--298 3-8 3.5.8 Capacitor Troubleshooting WARNING WARNING Do not touch the metal of the screwdriver when discharging the capacitor. You could receive a shock. Disconnect power to the AirV unit before checking the capacitor. b. After the capacitor has been discharged and all wires removed from the capacitor terminals, use an ohm-meter to test its resistance. c. Set the scale to R x 1K or 10K ohm and place the ohmmeter leads across the capacitor terminals. d. If the ohmmeter first reads 0, then rises toward infinity or some higher resistance, the capacitor is good. e. If the ohmmeter goes to 0 or a low resistance and stays there, the capacitor is shorted and needs to be replaced. f. If the ohmmeter reads infinity (OL) the capacitor is open and needs to be replaced. To test capacitor to determine if good, open or shorted, an ohm meter can be used. To determine a capacitor’s capacitance, a capacitor meter is required. Capacitors showing signs of leaks or bulging should be replaced immediately. 3.5.9 Capacitor Testing and Replacement Capacitors must be discharged properly before testing. a. Place a 20,000 ohm, 2 watt resistor across the terminals of the capacitor for approximately 30 seconds (See Figure 3-25 for a suggested tool). INSULATED SCREWDRIVER 20,000 -- OHM 2 -- WATT RESISTOR ATTACH TO CLEAN UNPAINTED METAL PART OF UNIT FRAME CLIP TO SCREWDRIVER TOUCH TO CAPACITOR TERMINALS TO DISCHARGE CAPACITOR Figure 3-25 Set--Up For Discharging a Capacitor 3.5.10 Positive Temperature Coefficient Thermister (PTC) (Start Thermistor) Troubleshooting a. Disconnect power from the AirV unit. b. Disconnect the wires to the PTC. c. Using an ohm meter, check for continuity across the PTC. If the PTC does not have continuity, it must be replaced. If continuity exists, reconnect the wires to the PTC. d. Reconnect power to the AirV unit. e. Turn on the AirV unit to start. f. Use a clamp--on amp probe to monitor the amp draw of the compressor during its start--up. When the compressor starts, an amp draw will be indicated for almost a second. If no amp draw is indicated or if the amp draw occurs for much longer than a second, the PTC is defective and must be replaced. 3.5.11 Line Voltage -- 10% Line voltage should be checked during peak electrical load periods. With the AirV unit on and the compressor operating, use a voltmeter to check the voltage being supplied to the AirV unit. The voltage must be within 10% of the units required voltage. A voltage drop greater than 10% will cause a premature compressor failure and needs to be corrected immediately. 3-9 T--298 3.6 SERVICE -- UPPER UNIT -- LOW PROFILE 3.6.1 Exterior Cover Removal b. b. CAUTION b. Coil fins are sharp. Use care when removing the cover form the base pan to avoid personal injury. b. To remove the exterior cover, do the following: a. Before working on unit place the master switch in the OFF position and disconnect all electrical power. b. Remove (8) screws securing the unit cover to the base pan assembly. See Figure 3-26. c. Carefully lift the exterior cover off of the unit base pan assembly. d. Reverse above procedure for reassembly. c. b. b. Figure 3-27 Upper Scroll Assembly Locking Tabs (b.) & Screw Locations (c.) Screws Screws Figure 3-26 Cover Assembly -- Low Profile 3.6.2 Upper Scroll Assembly Removal To remove the upper scroll assembly, do the following: a. Remove exterior cover assembly. Refer to paragraph 3.6.1. b. Release the (2) front, (2) rear, (1) left side and (1) right side locking tabs (See Figure 3-27) by pulling back on the tabs (See Figure 3-28). c. Remove the screw (1) from the control box cover (See Figure 3-27). d. With all (6) locking tabs released and control box screw removed, lift the upper scroll assembly off of the lower scroll assembly. e. Reverse above procedure for reassembly. Ensure all (6) locking tabs snap shut & lock. T--298 Figure 3-28 Upper Scroll Assembly Keeper Tab Release 3-10 Evaporator Coil Retaining Ring Figure 3-30 Condenser Fan Assembly & Retaining Ring Fan Stop Condenser Coil 13MM Bolt Condenser Motor 13MM Bolt Grommet Figure 3-29 Upper Scroll & Control Box Cover Removed Figure 3-31 Condenser Fan Motor & Fan Assembly Stop 3.6.3 Condenser Fan Assembly Removal To remove condenser fan assembly, do the following: a. Perform steps outlined in Section 3.6.2. b. Depress and Figure 3-30). remove Retaining Ring (See Tab c. Using both hands, carefully pull up on fan assembly until it is free of the motor shaft. d. When replacing the fan assembly make sure the fan assembly is against the stop on the shaft (See Figure 3-31) e. Push back on tab to allow fan assembly to rest against stop (See Figure 3-32). Fan assembly will now be flush with the end of the motor shaft. Figure 3-32 Condenser Fan Motor & Fan Assembly Tab f. Reverse above procedure for reassembly. 3-11 T--298 3.6.4 Condenser Motor Removal To remove condenser fan motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Remove (3) 13MM bolts (See Figure 3-31). c. Remove (3) Grommets. Inspect, replace or reuse. d. Cut Tie--Wraps & discard (2 locations). When reassembling, tie--wrap at same 2 locations. e. Remove ground wire from compressor bracket (See Figure 3-33). f. Un--plug (yellow/brown/white) from control box assembly. g. Reverse above procedure for reassembly. Blower Side Locking Tabs Cond. Motor Ground Screw Outside Locking Tabs Comp. Mounting Bolt Figure 3-33 Condenser Motor Ground 3.6.5 Evaporator Motor/Blower Assembly Removal To remove the evaporator motor, do the following: a. Perform steps outlined in Section 3.6.2. b. Pull back on and release the (4) locking tabs. There are 2 on each side of the control box assembly. (See Figure 3-34). Figure 3-34 Evaporator Motor Locking Tabs Lower Scroll Assembly Capacitor c. Lift control box assembly from lower scroll assembly, exposing evaporator motor. d. Un--plug (black/blue/white/brown) evaporator motor from control box assembly. e. Remove ground wire (green/yellow) from motor housing. f. Lift motor/blower assembly from lower scroll assembly cradle. g. Carefully remove the blower wheel from the evaporator motor shaft by pushing out from the motor side. T--298 Cradle Figure 3-35 Evaporator Motor/Blower Assembly In Cradle 3-12 NOTE When reassembling the blower wheel on to the motor shaft ensure that the blower wheel is flush with the end of the motor shaft (SeeFigure 3-36). NOTE When placing the evaporator motor/blower assembly back into the lower scroll assembly cradle, make sure that the assembly is seated securely in the cradle. (See Figure 3-35). h. Reverse above procedure for reassembly. 3.6.6 Compressor Replacement Perform the procedures outlined in Section 3.5.2 There are 4 bolts with the Low Profile Compressor. The system charge for the Low Profile unit is 16.9 OZ. 3.6.7 Capacitor Removal To remove the capacitor, do the following: a. Perform steps a., b. & c. as outlined in Section 3.6.5. Wheel Flush With Motor Shaft b. Perform steps outlined in Sections 3.5.8 & 3.5.9. c. The Low Profile Capacitor is removed from the control box assembly by pushing on the capacitor from under the control box assembly (See Figure 3-35). Figure 3-36 Evaporator Blower Wheel (Flush With End Of Motor Shaft) Control Box Assembly Upper Scroll Assembly Capacitor Terminal Block Figure 3-37 Control Box Assembly With Capacitor 3.6.8 Remote Control (Fahrenheit to Celsius) CAUTION All Remote Control Assemblies in the United States are pre--set to display in Fahrenheit degrees (see Figure 3-38). To change from a Fahrenheit display to a Celsius display do the following: The change from Fahrenheit to Celsius will be permanent. It cannot be changed back to Fahrenheit. 3-13 T--298 a. Remove the batteries from the remote control. b. Carefully remove the remote cover by inserting a narrow flat object between the cover and remote body and prying apart. c. Remove the brass screw holding the PCB in place. d. Carefully remove the PCB board from the remote body, making sure the battery springs release from their holders. e. Locate FR9 on the PCB board (see Figure 3-39). f. Carefully cut the FR9 jumper wire. g. Reverse above procedure for reassembly. CAUTION When re--assembling, ensure the battery springs are correctly placed in the battery spring holders. Battery Springs BATTERIES & COVER Spring Holders PCB COVER BODY Figure 3-38 Remote Control Components PCB FR9 Figure 3-39 Remote Control PCB (FR9 Location) T--298 3-14 2.Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into the wall. 3.As each wire is disconnected, record wire color and terminal marking. 4.Discard or recycle old thermostat. 3.7 THERMOSTAT INSTALLATION AND START-UP INSTRUCTIONS (WALL MOUNTED) 3.7.1 Introduction The thermostat is a wall mounted, low--voltage thermostat which maintains room temperature by controlling the operation of a heating and air conditioning system. Batteries are not required; temperature and mode settings are preserved with the power off. NOTE Mercury is a hazardous waste and must be desposed of properly. CAUTION c. Seperate the front and back pieces of plastic. d. Route thermostat wires through hole in back piece of plastic. Level plastic against wall (for aesthetic value only -- thermostat need not be leveled for proper operation) and mark wall through 2 mounting holes. e. Drill two 3/16 inch mounting holes in wall where marked. Improper wiring or installation may damage thermostat. Wiring must conform to local and national electrical codes. WARNING NOTE Mounting holes on thermostat are designed to fit on a horizontal J--Box. Before installing thermostat, turn off all power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death. f. Secure back plastic to wall with 2 anchors and screws provided, making sure all wires extend through hole in plastic. g. Connect wires to proper terminal of the connector block in the front piece of plastic. h. Pusr any excess wire back into wall. Excess wire inside the thermostat plastic case can interfere with proper air flow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can effect operation. i. Snap front and back pieces of plastic together. j. Turn on power to the unit. 3.7.2 Installation NOTE Read all instructions before starting the installation. NOTE The thermostat requires no batteries. The thermostat is not a power stealing device and MUST have both R and C connected. 3.8 LCD DISPLAY 3.8.1 Cool Only Thermostat (Part No. 1110--421) On power up, the LCD readout will display C (Cool Only). 3.7.3 Thermostat Location The thermostat should be mounted: Approximately 5 foot (1.5m) from the floor. Close to or in a frequently used room, preferably on an inside partitioning wall. 3.8.2 Heat/Cool Thermostat (Part No. 1110--420) On power up, the LCD readout will display HC (Heat/ Cool). On a section of wall without pipes or duct work. The thermostat should NOT be mounted: Close to a window, or an outside wall, or next to a door leading to the outside. 3.9 SET THERMOSTAT CONFIGURATION While in configuration mode, three option choices can be made. Exposed to direct light and heat from a lamp, sun, fireplace, or other temperature--radiating object which may cause a false reading. A - Anticipator Value Adjustment Close to or in direct airflow from supply registers and return--air grilles. d - Display Temperature Fahrenheit/Celcius Selection In areas with poor air circulation, such as behind a door or in an alcove. oF - Offset Adjustment For Room Temperature 3.7.4 Install Thermostat -- 12VDC 3.9.1 Enter Configuration Mode Enter and hold the FAN button for approximately 10 seconds until room temperature disappears and the display reads A. You are now in the configuration mode. a. Turn off all power to unit. b. If an existing thermostat is being replaced: 1.Remove existing thermostat from wall. 3-15 T--298 NOTE If the FAN button is pressed again or if no button is pressed for two minutes, the thermostat will exit the configuration mode and return to normal operation. To re--enter the configuration mode, the FAN button must be pressed and held for 10 seconds again. c. d. Use UP & DOWN buttons to select a value between --5 and 5. e. Press MODE buttonto return to oF. UP & DOWN buttons now move between option choices; or press FAN button to exit configuration mode. 3.10 CHECK THERMOSTAT OPERATION While in the configuration mode, the following options are available: A. ANTICIPATOR -- Value Adjustment This adjustment controls the sensitivity and cycle rate of the thermostst. Higher numbers decrease the sensitivity and slow the cycle rate. Lower numbers increase the sensitivity and increase the cycle rate. However, a limiting feature will not allow more than 4 equipment cycles per hour, regardless of setting. Values can range from 1 to 3. Factory default setting is 2. This default selection will provide optimum performance in nearly all installations. Try it first. Do not change settings unless there is evidence of need to do so. Unlike conventional anticipators, this setting is not determined by current draw. There is no need to measure, know, or compensate for current. To Adjust: a. Enter configuration mode (if not already there). 3.10.1 Fan Operation (Cool Only) 1. Press FAN button, starting fan operation. FAN annunciator turns on; Lo is displayed in the room temperature area for 5 seconds indicating Fan Low Speed. 2. Press FAN button, FAN annunciator remains on; Hi is displayed in room temperature area for 5 seconds indicating Fan High Speed. 3. Press FAN button, stopping fan operation. FAN annunciator turns off. 3.10.2 Fan Operation (Heat/Cool) 1. Press FAN button, starting low fan (Lo) operation. FAN annunciator turns on. 2. Press FAN button, starting high fan (Hi) operation. FAN annunciator remains on. b. Use UP & DOWN buttons to display A. c. Press MODE button once to display current value. d. Use UP & DOWN buttons to move between values. e. Press MODE buttonto return to A. UP & DOWN buttons now move between option choices A, d, oF or press FAN button to exit configuration mode. d. Fahrenheit/Celsius Selection This selection operates the thermostat in either Fahrenheit or Celsius. To Select: a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to display d. c. Press MODE button once to display current selection of F or C. d. Use UP & DOWN buttons to change between F & C. e. Press MODE buttonto return to d. UP & DOWN buttons now move between option choices; or press FAN button to exit configuration mode. 3. Press FAN button, stopping fan operation. FAN annunciator turns off. 3.10.3 Cooling Operation (Cool Only) 1. Press and release MODE button until COOL is displayed. 2. Press DOWN button until LCD readout reads 10 degrees below room temperature. Cooling and High Fan system should begin to operate within 5 minutes. 3.10.4 Cooling Operation (Heat/Cool) 1. Press and release MODE button until COOL is displayed. 2. Press DOWN button until LCD readout reads 10 degrees below room temperature. Cooling and High Fan system should begin to operate within 5 minutes. 3.10.5 Heating Operation (Heat/Cool) 1. Press and release MODE button until HEAT is displayed. oF. Room Temperature Offset Adjust Selection The selected number is the number of degrees, plus or minus, which will be added to the actual temperature. The numbers can range between --5 and +5. Factory default is 0. This adjusted value will be used as actual temperature for both display and control action. The effect is that a positive number selection will make the room temperature lower, and vice versa. The thermostat is calibrated within an accuracy of plus or minus 2 degrees when shipped from the factory; this adjustment will provide the best accuracy when set to o. To Select: a. Enter configuration mode (if not already there). b. Use UP & DOWN buttons to display oF . T--298 Press MODE button once to display offset value. 2. Press UP button until LCD readout reads 10 degrees above room temperature. Heating system should begin to operate within 1 minute. 3.11 CHECK THERMOSTAT OPERATION 3.11.1 Temperature Display The thermostat will display room temperature until the UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current set point is displayed. If no buttons are pressed for 5 seconds, the display will change back to show room temperature. 3-16 3.11.2 Timeguard Timer minutes regardless of demand). However, pressing UP and FAN buttons simultaneously or changing the set point will override the timer for 1 cycle. A 3--minute timeguard is built into the thermostat immediately upon power up, and any time the compressor (output “Y”) turns off. The compressor will not turn on until the timeguard has expired. Pressing UP and FAN buttons simultaneously will override the timeguard for 1 cycle. 3.11.4 Minimum On Timer Once the equipment has turned on, it will remain on for a minimum of 2 minutes regardless of demand. However, the equipment can turn off in less than 2 minutes if a change in set point, or a changein mode occurs. 3.11.3 Cycle Timer 3.11.5 Error Messages In normal cooling (and heating) operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15 minutes). Both the “Y” (cooling) and “W” (heating) outputs have a 15--minute timer that starts counting down when the output is turned on, (e.g., if “Y” output is turned on for 9 minutes and then satisfies, it cannout turn back on for another 6 Factory Wiring UPPER UNIT Motor E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace the thermostat. ---- (two dashes) will be displayed if the thermostat cannot properly read the room temperature. If ---appears, replace the thermostat. Field Wiring Comp. 1 2 3 4 2 1 2 3 4 J 1 115V AC High Voltage Power Supply L N2 N1 THERMOSTAT POWERBOX ASSEMBLY 1 W 2 Y 3 GH GH FAN (High) 4 GL GL FAN (Low) 5 C Y COOL (Compressor) 12VDC LowVoltage Power Supply R C CEILING UNIT Figure 3-40 Wall Thermostat Wiring Diagram -- Cool Only Model 3-17 T--298 Factory Wiring Field Wiring UPPER UNIT Motor Comp. 1 2 3 4 21 1 2 3 4 J 115V AC High Voltage Power Supply L N2 N1 THERMOSTAT POWERBOX ASSEMBLY 1 W 2 Y 3 GH GH FAN (High) 4 GL GL FAN (Low) 5 C R TB C 1 2 Y COOL (Compressor) Blue Blue + 12VDC 12 VDC (Gnd) FURNACE CEILING UNIT Figure 3-41 Wall Thermostat Wiring Diagram -- Heat/Cool Model T--298 3-18 12VDC LowVoltage Power Supply SECTION 4 WIRING SCHEMATICS 4.1 INTRODUCTION This Section contains wiring schematics for the AirV units. Figure 4--1 is the schematic for the standard upper unit assembly and it is applicable to all standard units. Figure 4--2 is the schematic for the Low Profile upper unit assembly. Figure 4--3 is the schematic for a free blow ceiling unit without heat while Figure 4--4 is a free blow unit with heat. Figure 4--5 is for a ducted unit with microprocessor control. Figure 4--6 is for an Upper Unit Heat Pump with free blow application and Figure 4--7 is the matching free blow ceiling unit. Figure 4--8 is for the Upper Unit Heat Pump ducted application and Figure 4--9 is the matching ducted ceiling unit. Note that the ducted units have 115 VAC power for the components and 12 VDC power for the microprocessor control system. Figure 4--10 is for the ducted or free blow application that uses a wall--mounted thermostat, with or without the furnace option. Where applicable, diagrams that designate 115 Volt, 60 H, 1 Phase, are also available using 220 Volts, 50 H, 1 Phase. Most noteably Figure 4--1 and Figure 4--5. FAN MOTOR 4P 2P BLK 1 BLU 2 PLUG CONNECTS TO CEILING UNIT SEE FIG> 4--3 OR 4--4 BLK 1 BRN WHT BLU 2 GRN/YEL 3 GRN/YEL 4 CONTROL BOX 2P F WHT GRN/YEL C EVAP. H RED RED CAPACITOR BLU WHT 1 R YEL 2 YEL 2 1 PTC C BLU S OVERLOAD PROTECTOR (If Used) COMPRESSOR Figure 4--1 Upper Unit Schematic -- Standard & HC PLUG CONNECTS TO CEILING UNIT. SEE DIAGRAM SUPPLIED WITH CEILING UNIT FOR ADDITIONAL WIRING. (UNIT - 99-- 00468-- 10) 4P INDOOR FAN MOTOR 4P BLK 1 1 BLU 2 WHT WHT 3 BRN GRN/YEL 4 BLK 1 2 2 3 3 4 4 BLU GRN/YEL WHT BRN FMC YEL 2P WHT 1 YEL 2 OUTDOOR FAN MOTOR 3P 1 1 2 2 3 3 YEL WHT BRN C BRN F H CAPACITOR WHT WHT LEGEND OLP: OVERLOAD PROTECTION PTC: START THERMISTER JTB: JOINT TERMINAL BLOCK FMC: INDOOR FAN MOTOR CAPACITOR YEL OLP (IF USED) YEL C 1 2 (3) R S RED BLU RED PTC (IF USED) BLU COMPRESSOR Figure 4--2 Upper Unit Schematic -- Low Profile 4-1 T--298 UPPER UNIT FOR ADDITIONAL WIRING. BLK BLU 1 2 ASW 1 2 ORN ORN 6 WHT 1 2 1 BLK YEL 8 ORN L C PLUG CONNECTS TO UPPER UNIT. 4P 3 2P 2 4 WHT GRN/YEL 115 VAC SUPPLY WIRE IT SW ASM 2P { WHT 1 YEL GRN/YEL 2 SEE DIAGRAM SUPPLIED WITH 4 SWITCH POSITION CONTACTS MADE HIGH FAN 1--4 . 1--6 LOW FAN 1--2 . 1--6 NONE OFF LOW COOL 1--2 . 1--6 . 1--8 HIGH COOL 1--4 . 1--6 . 1--8 O (OFF) ASW 2 I (ON) 2 -- 1 LEGEND ASM : AIR SWEEP MOTOR ASW : AIR SWEEP SWITCH SW : SWITCH IT : INDOOR THERMOSTAT Figure 4--3 Ceiling Unit Schematic -- Cooling Only L L1 ORN 2 1 BLK YEL 1 1 B 3 IT ASW 115 VAC SUPPLY WIRE HT ORN HEATER--ASSY BLK 1 3 LOW COOL L2--C . L1--L . L1--A . B--3 HIGH COOL L2--C . L1--H . L1--A . B--3 HEAT L2--HT . L1--L . L1--A . B--1 WHT GRN/YEL ASM C 2P WHT WHT CEC GRN/YEL 1 YEL NONE L1--L . L1--A 2 4 WHT CONTACTS MADE LOW FAN HIGH FAN BT 2P { 2 OFF HEATER BLK 2 WHT L2 1 3 BLU BLK 2P 2 RED WHT ORN A 1 UPPER UNIT FOR ADDITIONAL BLU SWITCH POSITION L1--H . L1--A O (OFF) ASW 1 (ON) 2 2 -- 1 LEGEND ASM AIR SWEEP MOTOR ASW AIR SWEEP SWITCH SW SWITCH IT INDOOR THERMOSTAT CEC CLOSED END CONNECTOR WIRING. H 4P PLUG CONNECTS TO UPPER UNIT. BLK SEE DIAGRAM SUPPLIED WITH SW BT BIMETAL 2 Figure 4--4 Ceiling Unit Schematic -- Heat/Cool LEGEND IDC Th : INDOoR COIL THERMISTER RA Th : ROOM AIR THERMISTER KY : RELAY DI : DIODE 1 2 3 4 3 2 RA Th IDC Th CN1 BLK BRN 1 2 3 4 PCB 1 BLK CN3 1 WHT Y CN4 CN4 CONTROL 2 GRN/YEL BLU BLK WHT 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 1 2 3 1 2 3 RY1 RY3 BLK L RY2 N2 WHT N1 115 VAC POWER GRN/YEL ASS’Y FUSE D1 250V 3.15A RY4 CN1 CN9 1 2 3 4 5 6 7 8 CN2 1 2 CN9 1 2 3 4 5 6 7 8 BLU DISPLAY PCB AS BLU Figure 4--5 Ceiling Unit, Standard -- Ducted T--298 2 1 4-2 RED BLK (+) (--) 12 VDC POWER PLUG CONNECTS TO CEILING UNIT. SEE DIAGRAM SUPPLIED WITH CEILING UNIT FOR ADDITIONAL WIRING. FAN MOTOR OLP: OVERLOAD PROTECTION PTC: START THERMISTER RVC: REVERSING VALVE COIL 4P 4P 1 2 BLK 1 1 BLU 2 2 WHT 3 GRN/YEL 4 3 3 4 4 BLK BLU GRN/YEL WHT BRN GRN/YEL BRN EVAP. CONTROL BOX WHT 2P 2P BLK 1 1 2 2 RVC BLK(BLU) BRN 2 1 F H C CAPACITOR WHT WHT 2P 1 BLK RED 2 OLP (IF USED) 1 2 (3) BLU RED R YEL RED PTC C S FREEZE SWITCH BLU COMPRESSOR Figure 4--6 Heat Pump -- Upper Unit -- Free Blow SW 4P ORN A 2 1 ORN WHT 1 2 1 2 2P ASW BLK HT BLK ORN C HEATER BT BLK 115 VAC SUPPLY WIRE B 3 BLK { YEL RED H 1 3 L IT 2P BLK 2 1 ASM 2 2P 1 1 BRN C 2 2 WHT WHT GRN/YEL 4 GRN/YEL WHT 1 3 WHT HEATER AS L2 2 OFF WIRING. UPPER UNIT FOR ADDITIONAL L L1 SWITCH POSITION SEE DIAGRAM SUPPLIED WITH BLU 1 PLUG CONNECTS TO UPPER UNIT. BLK H CONTACTS MADE NONE LOW FAN L1--L . L1--A HIGH FAN L1--H . L1--A LOW COOL L2--C . L1--L . L1--A . B--3 HIGH COOL L2--C . L1--H . L1--A . B--3 HEATING L2--HT . L1--L . L1--A . B--1 ASW O (OFF) 2 1 (ON) 2 -- 1 LEGEND ASM: AIR SWEEP MOTOR ASW: AIR SWEEP SWITCH CEC YEL 2P SW: SWITCH 1 IT: 2 CEC: CLOSED END CONNECTOR WHT BT: INDOOR THERMOSTAT BIMETAL Figure 4--7 Heat Pump -- Ceiling Unit -- Free Blow 4-3 T--298 1 BRN ODC Th BLK ODA Th LEGEND 2 CN :HOUSING CONNECTOR 3 FAN MOTOR CN BLU RVC :REVERSING VALVE COIL BLU 2 ODA Th :OUTDOOR AIR THERMISTOR RED RED GRN/YEL 3 3 ODC Th :OUTDOOR COIL THERMISTOR GRN/YEL WHT 5 4 PTC :START THERMISTOR OLP :OVERLOAD PROTECTOR BLK 1 2 BRN 6 BRN CONTROL EVAP. BOX WHT F C WHT 1 H CAPACITOR YEL 2 WIRING. CEILING UNIT FOR ADDITIONAL PLUG CONNECTS TO CEILING UNIT. SEE DIAGRAM SUPPLIED WITH BLK 1 COMPRESSOR RED OLP 1 BLK(BLU) RVC 2 1 BLU RED R (IF USED) 2 (3) YEL C PTC S BLU CN Figure 4--8 Heat Pump -- Upper Unit -- Ducted LEGEND PLUG CONNECTS TO UPPER UNIT. IDC Th: INDOOR COIL THERMISTER NOTE SEE DIAGRAM SUPPLIED WITH UPPER UNIT RA Th: ROOM AIR THERMISTER FOR ADDITIONAL WIRING. ODC Th: OUTDOOR COIL THERMISTER ODC ODA Th :OUTDOOR AIR THERMISTOR ODA 1 2 3 RVC: REVERSING VALVE COIL D1: DIODE BLK K: RELAY RVC MOTOR 1 2 1 2 3 4 WHT RED BLU BLK RED BLK BRN 1 2 CN5 * FACTORY WIRING * FIELD WIRING (115VAC HIGH VOLT.) * FIELD WIRING (12VDC LOW VOLT.) COMPRESSOR 2 1 GRN/YEL WHT BLK 1 2 3 4 CN3 Y CN5 1 2 3 RA Th BLK CN1 1 2 3 4 IDC Th CONTROL PCB ASS’Y BRN 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CN4 1 2 3 CN9 1 2 3 4 5 6 7 8 CN6 1 2 3 4 5 6 7 8 CN4 1 2 3 1 2 3 BLK K7 K2 1 2 3 4 5 6 7 8 K1 K4 115VAC POWER WHT N1 GRN/YEL POWER PCB ASS’Y FUSE D1 2 K6 250V 3.15A 1 CN1 CN6 BLU 1 2 BLU FURNACE SIGNAL DISPLAY PCB AS Figure 4--9 Heat Pump -- Ceiling Unit -- Ducted T--298 L N2 CN2 CN9 K3 4-4 RED BLK (+) 12VDC POWER (--) Figure 4--10 Ceiling Unit -- Wall Thermostat -- Ducted & Free Blow 4.2 WALL MOUNTED THERMOSTATS For proper wiring of Wall Mounted Thermostats as an accessory, refer to Figure 3-40 (Wall Thermostat Wiring Diagram -- Cool Only Model) or Figure 3-41 (Wall Thermostat Wiring Diagram -- Heat/Cool Model). 4-5 T--298 INDEX A I Air Handling System , 3-8 Indoor Thermostat , 3-3 Air Sweep Removal, 3-3 INTRODUCTION, 1-1, 4-1 Air Sweep Switch , 3-2 L LCD DISPLAY, 3-15, 3-16 C Leaks, 3-1 Capacitor Testing, 3-9 M Capacitor Testing and Replacement, 3-9 Ceiling Grill -- Ducted, 3-4 Main Pcb Board, 3-5 Ceiling Grill -- Free Blow, 3-1 Master Control Switch, 3-2 Ceiling Panel -- Free Blow, 3-2 Motor , 3-7 CEILING UNIT -- DUCTED SYSTEMS, 3-4 Mounting, 3-1 CEILING UNIT -- FREE BLOW , 3-1 Cleaning, 3-1 P Compressor , 3-6, 3-13 Painting, 3-1 Condenser Fan, 3-7 PCB Display , 3-5 Control Box -- Ducted, 3-4 PREVENTATIVE MAINTENANCE, 3-1 Control Box -- Upper Unit, 3-6 Controls, 3-1 R Cool Only Thermostat, 3-15 REFRIGERANT CYCLE, 1-9, 1-10 D S Design Change, 1-1 Serial Number, 1-1 SERVICE -- GENERAL, 3-1 SERVICE -- UPPER UNIT -- LOW PROFILE, 3-10 E SERVICE AND MAINTENANCE, 3-1 Evaporator Blower Wheel, 3-8 START--UP, 1-9 Exterior Cover, 3-5, 3-10, 3-15 T F THERMOSTAT INSTALLATION AND START--UP INSTRUCTIONS (WALL MOUNTED), 3-15 Filter Removal -- Free Blow, 3-1 TROUBLESHOOTING, 2-1, 2-3 Filter Removal -- Ducted, 3-4 U Fuse Removal -- Ducted, 3-5 Upper Scroll Assembly, 3-7, 3-10, 3-11, 3-12, 3-13 H W Heat Strip, 3-3 WIRING SCHEMATICS, 4-1 Heat/Cool Thermostat, 3-15 Index -1 T--298 Carrier Transport Air Conditioning 50 Grumbacher Road York PA 17402 USA Tel: 1--800--673--2431 Fax: 1--717--764--0401 Carrier Transicold Division, Carrier Corporation Transport Air Conditioning Group P.O. Box 4805 Syracuse, N.Y. 13221 U.S A www.carrier.transicold.com A member of the United Technologies Corporation family. Stock symbol UTX ©2006 Carrier Corporation D Printed in U. S. A. 0606
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Create Date : 2006:06:20 08:25:05-04:00 Modify Date : 2006:06:20 08:28:49-04:00 Metadata Date : 2006:06:20 08:28:49-04:00 Format : application/pdf Title : untitled Document ID : uuid:5185f295-92dd-4f4a-abcd-c17a3d7b4104 Instance ID : uuid:be963e3c-42ac-43db-ba2c-3f14b50f0677 Has XFA : No Page Count : 49EXIF Metadata provided by EXIF.tools