Carrier Weathermaker 8000 58Wav Owners Manual
2014-08-26
: Carrier Carrier-Weathermaker-8000-58Wav-Owners-Manual carrier-weathermaker-8000-58wav-owners-manual carrier pdf
Open the PDF directly: View PDF .
Page Count: 24
Download | |
Open PDF In Browser | View PDF |
WeatherMaker 8000™ 58WAV Upflow Induced-Combustion Furnaces Visit www.carrier.com Installation, Start-Up, and Operating Instructions Sizes 045-155, Series 140 (LIMITED) NOTE: Read the entire instruction manual before starting the installation. Index Page SAFETY CONSIDERATIONS .....................................................1 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE........................................................................2-3 Dimensional Drawing ...............................................................2 Clearances From Combustible Materials .................................3 INTRODUCTION.....................................................................3 LOCATION ..............................................................................4 General.................................................................................4 Location Relative to Cooling Equipment ...........................4 Hazardous Locations ...........................................................4 AIR FOR COMBUSTION AND VENTILATION..............4-6 Unconfined Space................................................................4 Confined Space....................................................................5 AIR DUCTS..............................................................................6 General Requirements .........................................................6 Ductwork Acoustical Treatment .........................................6 Supply-Air Connections ......................................................6 Return-Air Connections.......................................................6 FILTER ARRANGEMENT .....................................................6 LEVELING LEGS (IF REQUIRED).......................................7 GAS PIPING .........................................................................7-8 ELECTRICAL CONNECTIONS.............................................8 115-v Wiring........................................................................8 24-v Wiring..........................................................................8 Accessories .......................................................................8-9 VENTING .................................................................................9 START-UP, ADJUSTMENT, AND SAFETY CHECK..12-20 General...............................................................................12 Sequence Of Operation ................................................12-15 Heating Mode ....................................................................13 Cooling Mode...............................................................13-15 Continuous Blower Mode .................................................15 Continuous Blower Speed Selection from Thermostat ....15 Heat Pump Mode...............................................................15 Start-Up Procedures .....................................................15-16 Adjustments ..................................................................16-20 Set Gas Input Rate .......................................................16-19 Set Temperature Rise...................................................19-20 Set Thermostat Heat Anticipator ......................................20 Check Safety Controls ............................................................20 Checklist..................................................................................21 ama CERTIFIED REGISTERED QUALITY SYSTEM SAFETY CONSIDERATIONS Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit and other safety precautions that may apply. Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-1999/ANSI Z223.1-1999 and the Installation Standards, Warm Air Heating and Air Conditioning Systems (NFPA 90B) ANSI/NFPA 90B. In Canada, refer to CAN/CGA-B149.1- and .2-M95 National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC). These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation. Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 535-757 Printed in U.S.A. Form 58WAV-9SI Pg 1 1-00 Replaces: New Tab 6a 8a AIRFLOW 28 1⁄2″ 2 1⁄16″ VENT CONN A D DIA HOLE POWER ENTRY 7⁄8-IN. DIA ACCESSORY DIA POWER ENTRY 2 11⁄16″ 5 13⁄16″ 13⁄16″ 2 3⁄8″ 1 3⁄4-IN. DIA HOLE GAS ENTRY 1 1⁄2-IN. DIA R.H. GAS ENTRY 7⁄8-IN. DIA ACCESSORY 1⁄2-IN. DIA THERMOSTAT WIRE ENTRY 2 3⁄8″ DIA HOLE THERMOSTAT WIRE ENTRY 13⁄16″ 7⁄8-IN. 5 3⁄8″ 12 5⁄16″ 1⁄2-IN. OUTLET 1″ 5 3⁄8″ 5 19″ 13⁄16″ 1″ 7⁄8-IN. 39 7⁄8″ 2 1⁄16″ SIDE INLET SIDE INLET 141⁄2″ TYP 1″ 1 3⁄4″ 5⁄16″ 24 AIR INLET 11⁄16″ 3″ 11⁄16″ 11⁄16″ E 1″ 231⁄4″ SIDE RETURN DUCT LOCATION 5⁄8″ TYP NOTES: 1. Two additional 7⁄8-in. dia holes are located in the top plate. 2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. 3. Minimum return-air opening at furnace: a. For 800 CFM–16-in. round or 141⁄2 x 12-in. rectangle. b. For 1200 CFM–20-in. round or 141⁄2 x 191⁄2-in. rectangle. c. For 1600 CFM–22-in. round or 141⁄2 x 231⁄4-in. rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM. A99060 Fig. 1—Dimensional Drawing Table 1—Dimensions (In.) UNIT SIZE 045-08 045-12 070-08 070-12 091-14 091-16 111-12 111-16 111-20 136-16 136-20 155-20 A 14-3/16 14-3/16 14-3/16 14-3/16 17-1/2 21 17-1/2 21 24-1/2 21 24-1/2 24-1/2 D 12-9/16 12-9/16 12-9/16 12-9/16 15-7/8 19-3/8 15-7/8 19-3/8 22-7/8 19-3/8 22-7/8 22-7/8 E 12-11/16 12-11/16 12-11/16 12-11/16 16 19-1/2 16 19-1/2 23 19-1/2 23 23 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE VENT CONN 4 4 4 4 4 4 4 4 4 5 5 5 SHIP. WT (LB) 119 121 126 129 147 159 155 164 182 173 186 196 3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.). 4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires. 5. Use this procedure for installed and uninstalled (ungrounded) furnaces. 6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects. 7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage. Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential. 1. Disconnect all power to the furnace. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND. 2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged. 2 MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION TOP / PLENUM This forced air furnace is equipped for use with This furnace is approved for UPFLOW installations only. natural gas at altitudes 0 - 10,000 ft (0-3,050m). An accessory kit, supplied by the manufacturer, 1" shall be used to convert to propane gas use or may be required for some natural gas applications. m This furnace is for indoor installation in building constructed on site. 1" 0" BA # This furnace may be installed on combustible E CK D SI E flooring in alcove or closet at minimum clearance AC RN from combustible material. FU T ON This furnace may be used with a Type B-1 Vent FR SE a nd may be vented in common with other gas-fired RV IC a ppliances. E E SI ## FR For furnaces wider than 14.25 inches (362mm) may be 0 inches. For single wall vent type 6 inches. For Type B-1 vent type 3 inches. 0" Clearance in inches. ON T 30" MIN ## BOTTOM DESSOUS # D 1" # 320325-101 REV. H Vent Clearance to combustibles: For Single Wall vents 6 inches (6 po). For Type B-1 vent type 1 inch (1 po). A98122 Fig. 2—Clearances to Combustibles INTRODUCTION The Model 58WAV, Series 140 Limited Furnace is available in sizes 44,000 through 154,000 Btuh input capacities. The design of the upflow gas-fired furnace is A.G.A./C.G.A. certified for natural and propane gas and for installation on combustible flooring, in alcoves, attics, basements, closets, or utility rooms. The furnace is factory-shipped for use with natural gas. A factory accessory gas conversion kit, as listed on the furnace rating plate is required to convert furnace for use with propane gas. The design of this furnace line is not A.G.A./C.G.A. certified for installation in mobile homes, recreation vehicles, or outdoors. FRONT °F °F RETURN AIR Before installing the furnace in the United States, refer to the current edition of the NFGC and the NFPA 90B. For copies of the NFGC and NFPA 90B, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol St., N.W., Washington DC 20001. MAX 85°F MIN 55°F A93042 Before installing the furnace in Canada, refer to the NSCNGPIC. For a copy of the NSCNGPIC, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada. This furnace is designed for a minimum continuous return-air temperature of 60°F db or an intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed a maximum of 85°F db. Installation must comply with regulations of serving gas supplier and local building, heating, plumbing or other codes in effect in the area in which installation is made. In absence of local building codes, installation must comply with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada. Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory-authorized and listed kits or accessories when modifying this product. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause premature component failure. For accessory installation details, refer to the applicable instruction literature. 3 NOTE: Remove all shipping brackets and materials before operating the furnace. Step 1—Location GENERAL Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances. 18-IN. MINIMUM TO BURNERS Do not use this furnace during construction when adhesives, sealers, and/or new carpets are being installed. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compounds of chlorine and fluorine when burned with combustion air form acids which cause corrosion of the heat exchangers and metal vent system. Some of these compounds are found in paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process. Excessive exposure to contaminated combustion air will result in safety and performance related problems. A93044 Step 2—Air For Combustion and Ventilation Provisions for adequate combustion and ventilation air must be provided in accordance with Section 5.3 of the NFGC, Air for Combustion and Ventilation, or applicable provisions of the local building codes. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. DO NOT install the furnace on its back or sides. Safety control operation will be adversely affected. A failure to follow this warning can cause fire, personal injury, or death. All fuel-burning equipment must be supplied with air for combustion of the fuel. Sufficient air MUST be provided to ensure there will not be a negative pressure in the equipment room or space. In addition, a positive seal MUST be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and blocked vent safeguard opening. This furnace must be installed so the electrical components are protected from water. This furnace shall not be installed directly on carpeting, tile, or any combustible material other than wood flooring. Locate furnace as close to the chimney/vent and as near the center of the air distribution system as possible. The furnace should be installed as level as possible. The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST BE PROVIDED for the ventilation devices, in addition to that required by the furnace. Provide ample space for servicing and cleaning. Always comply with the minimum fire protection clearances shown on the unit rating plate. LOCATION RELATIVE TO COOLING EQUIPMENT — The cooling coil must be installed parallel with or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with a furnace, dampers or other means used to control the flow of air must prevent chilled air from entering the unit. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position. The requirements for combustion and ventilation air depend upon whether the furnace is located in an unconfined or confined space. UNCONFINED SPACE An unconfined space has volume of at least 50 cu ft for each 1000 Btuh of total input for all appliances (such as furnaces, clothes dryers, water heaters, etc.) in the space. For Example: HAZARDOUS LOCATIONS 58WAV FURNACE INPUT BTUH 44,000 66,000 88,000 110,000 132,000 154,000 When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc. MINIMUM SQ FT WITH 7-1/2 FT CEILING 293 440 587 733 880 1026 If the unconfined space is of unusually tight construction, air for combustion and ventilation MUST come from either the outdoors or spaces freely communicating with the outdoors. Combustion and ventilation openings must be sized the same as for a confined 4 12″ MAX 1 SQ IN. PER 2000 BTUH* CONFINED SPACE 12″ MAX INTERIOR HEATED SPACE A D VENT THROUGH SUPPLY ROOF AIR 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL DUCTS TO OUTDOORS UNCONFINED SPACE 12″ MAX F 1 SQ IN. PER 4000 BTUH* OUTDOORS VENT THROUGH ROOF CONFINED SPACE SUPPLY AIR 1 SQ IN. PER 4000 BTUH* DUCTS TO OUTDOORS 1 SQ IN. PER 4000 BTUH* 6″ MIN (FRONT) † 1 SQ IN. PER 2000 BTUH* 12″ MAX 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL E B G 12″ MAX C 12″ MAX 12″ MAX RETURN AIR RETURN AIR DUCT TO OUTDOORS 1 SQ IN. PER 4000 BTUH* *Minimum dimensions of 3 in. * Minimum opening size is 100 sq in. with minimum dimensions of 3 in. † Minimum of 3 in. when type-B1 vent is used. NOTE: Use any of the following combinations of openings: A&B C&D D&E F&G A89012 A89013 Fig. 3—Confined Space: Air for Combustion and Ventilation from an Unconfined Indoor Space Fig. 4—Confined Space: Air for Combustion and Ventilation from Outdoors b. If building is constructed unusually tight, a permanent opening directly communicating with the outdoors shall be provided. See item 2 below. c. If furnace is installed on a raised platform to provide a return-air plenum, and return air is taken directly from hallway or space adjacent to furnace, all air for combustion must come from outdoors. 2. Air from outside the structure requires 1 of the following methods: a. If combustion air is taken from outdoors through 2 vertical ducts, the openings and ducts MUST have at least 1 sq in. of free area per 4000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.) b. If combustion air is taken from outdoors through 2 horizontal ducts, the openings and ducts MUST have at least 1 sq in. of free area per 2000 Btuh of total input for all equipment within the confined space. (See Fig. 4 and Table 2.) c. If combustion air is taken from outdoors through a single opening or duct (horizontal or vertical) commencing within 12 in. of the top of the confined space, opening and duct MUST have at least 1 sq in. of free area per 3000 Btuh of the total input for all equipment within the confined space and not less than the sum of the areas of all vent connectors in the confined space. (See Fig. 4 and Table 2.) Equipment clearances to the structure shall be at least 1 in. from the sides and back and 6 in. from the front of the appliances. space as defined below. Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room. CONFINED SPACE A confined space is defined as a space whose volume is less than 50 cu ft per 1000 Btuh of total input ratings of all appliances installed in that space. A confined space MUST have provisions for supplying air for combustion, ventilation, and dilution of flue gases using 1 of the following methods. (See Fig. 3, 4, and Table 2.) NOTE: In determining free area of an opening, the blocking effect of louvers, grilles, and screens must be considered. If free area of louver or grille design is unknown, assume that wood louvers have a 20 percent free area and metal louvers or grilles have a 60 percent free area. Screens, when used, must not be smaller than 1/4-in. mesh. Louvers and grilles must be constructed so they cannot be closed. The size of the openings depends upon whether air comes from outside of the structure or an unconfined space inside the structure. 1. All air from inside the structure requires 2 openings (for structures not usually tight): a. Each opening MUST have at least 1 sq in. of free area per 1000 Btuh of total input for all equipment within the confined space, but not less than 100 sq in. per opening. (See Fig. 3 and Table 2.) The minimum dimension of air openings shall not be less than 3 in. 5 Table 2—Minimum Free Area Of Combustion Air Opening* 58WAV FURNACE INPUT (BTUH) 44,000 66,000 88,000 110,000 132,000 154,000 AIR FROM INDOOR UNCONFINED SPACE Free Area of Opening (Sq In.) 100 100 100 110 132 154 OUTDOOR AIR THROUGH VERTICAL DUCTS Free Area of Round Opening and Duct Pipe (Sq In.) (In. Dia) 11.0 4 16.5 5 22.0 6 27.5 6 33.0 7 38.5 8 OUTDOOR AIR THROUGH HORIZONTAL DUCTS Free Area of Round Opening and Duct Pipe (Sq In.) (In. Dia) 22.0 6 33.0 7 44.0 8 55.0 9 66.0 10 77.0 10 OUTDOOR AIR THROUGH SINGLE DUCT Free Area of Round Opening and Duct Pipe (Sq In.) (In. Dia) 14.67 5 22.00 6 29.33 7 36.67 7 44.00 8 51.33 9 * Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances in the space require combustion air. Step 4—Return Air Connections When ducts are used, they must be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of ducts must not be less than 3 in. (See Fig. 4.) Never connect return-air ducts to the back of the furnace. A failure to follow this warning can cause a fire, personal injury, or death. AIR DUCTS Step 1—General Requirements The return-air duct must be connected to bottom , sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 1. Bypass humidifier may be attached into unused side return air portion of the furnace casing. DO NOT connect any portion of return-air duct to back of furnace casing. The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE). Or consult factory The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design airflow CFM at the design external static pressure. Step 5—Filter Arrangement The factory-supplied filter(s) is shipped in the blower compartment. Determine location for the filter and relocate filter retaining wire if necessary. See Fig. 5 for side return application and Fig. 6 for bottom return application. See Table 3 to determine correct filter size for desired filter location. Table 3 indicates filter size, location, and quantity shipped with the furnace. When a furnace is installed so that the supply ducts carry air to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. WASHABLE FILTER Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and return-duct connections to furnace with code approved tape or duct sealer. FILTER RETAINER Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended. Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See NFPA 90B or local code for further requirements. Step 2—Ductwork Acoustical Treatment A93045 Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts. Fig. 5—Side Filter Arrangement (Control Removed for Clarity) For bottom air-return applications, filter may need to be cut to fit some furnace casing widths. A bottom closure panel is factory installed in the bottom of the furnace. When bottom return inlet is desired, remove and discard the bottom closure panel. Two sets of hardware are needed for furnaces in 24-1/2-in. wide casings using 2 filters for bottom return. All hardware is provided for filter installation. Step 3—Supply Air Connections Connect supply-air duct to 3/4-in. flange on furnace supply-air outlet. The supply-air duct attachment must ONLY be connected to furnace supply-/outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected external to furnace main casing. NOTE: Furnaces with a 17-1/2-in. wide casing require an additional procedure when locating the filter for bottom return-air application. Field fabricate a sheet metal filler strip 1 X 3 X 24-1/2 in. and install it along side of the filter as shown in Fig. 6. Drive 2 screws through the casing side and into the filler strip to secure 6 171⁄2-IN. WIDE CASINGS ONLY: INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER. 5⁄16″ 241⁄2-IN. WIDE CASINGS ONLY: CUT AND FOLD FACTORY-PROVIDED FILTERS AS SHOWN TO DESIRED SIZE. 5⁄16″ 1 3⁄4″ 3″ 24 1/2″ 1 3⁄4″ 1″ 5⁄16″ 5⁄16″ 1 3⁄4″ 1 3⁄4″ A89014 Fig. 7—Leveling Leg Installation NOTE: The length of the bolt should not exceed 1-1/2 in. 1. Lay furnace on its back. Locate and drill 5/16-in. diameter hole in each bottom corner of furnace as shown in Fig. 7. 2. Install nut on bolt and install bolt and nut in hole. (Install flat washer if desired.) 3. Install another nut on other side of furnace base. (Install flat washer if desired.) 4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement. Step 7—Gas Piping Gas piping must be installed in accordance with national and local codes. Refer to the current edition of the NFGC. Canadian installations must be installed in accordance with NSCNGPIC and all authorities having jurisdiction. Refer to Table 4 for the recommended gas pipe size. Risers must be used to connect to the furnace and the meter. WASHABLE FILTER FILTER SUPPORT FILTER RETAINER A96030 Fig. 6—Bottom Filter Arrangement (Control Removed for Clarity) Table 3—Filter Information (In.) FURNACE CASING WIDTH 14-3/16 17-1/2 21 24-1/2 FILTER SIZE* Side Return Bottom Return (1) 16 X 25 X 1† (1) 14 X 25 X 1 (1) 16 X 25 X 1† (1) 16 X 25 X 1 (1) 16 X 25 X 1 (1) 20 X 25 X 1† (2) 16 X 25 X 1† (1) 24 X 25 X 1 If a flexible connector is required or allowed by the authority having jurisdiction, black iron pipe shall be installed at the gas valve and extend a minimum of 2 in. outside the furnace casing. FILTER TYPE Cleanable Cleanable Cleanable Cleanable * Filters can be field modified by cutting the frame as marked and folding to the desired size. Alternate sizes can be ordered from your distributor or dealer. † Factory provided with the furnace. Use the proper length of pipes to avoid stress on the gas control manifold. Failure to follow this warning can result in a gas leak, causing fire, explosion, personal injury, or death. it in place. Filter should rest on the top of the filler strip when installed. Connect the gas pipe to the furnace using a backup wrench to avoid damaging gas controls. Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death. Step 6—Leveling Legs (If Required) When the furnace is used with side inlet(s) and leveling legs are required, refer to Fig. 7, and install field-supplied, corrosionresistant 5/16-in. machine bolts and nuts. 7 GAS SUPPLY Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause a fire, explosion, personal injury, or death. MANUAL SHUTOFF VALVE (REQUIRED) Table 4—Maximum Capacity of Pipe* NOMINAL IRON PIPE SIZE (IN.) 1/2 3/4 1 1-1/4 1-1/2 INTERNAL DIAMETER (IN.) 0.622 0.824 1.049 1.380 1.610 LENGTH OF PIPE (FT) 10 20 30 40 50 175 360 680 1400 2100 120 250 465 950 1460 97 200 375 770 1180 82 170 320 660 990 73 151 285 580 900 SEDIMENT TRAP UNION * Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 10-2 NFPA 54-1999. Install a sediment trap in the riser leading to the furnace. The trap can be installed by connecting a tee to the riser leading from the furnace. Connect a capped nipple into the lower end of the tee. The capped nipple should extend below the level of the gas controls. (See Fig. 8.) Apply joint compound (pipe dope) sparingly and only to the male threads of each joint. The compound must be resistant to the action of propane gas. An accessible manual shutoff valve MUST be installed upstream of the furnace gas controls and within 72 in. of the furnace. A 1/8-in. NPT plugged tapping, accessible for test gage connection, MUST be installed immediately upstream of the gas supply connection to the furnace and downstream of the manual shutoff valve. Place ground joint union between the gas control manifold and the manual shutoff valve. Piping should be pressure tested in accordance with local and national plumbing and gas codes before the furnace has been attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas supply pipe must be disconnected from the furnace and capped before the pressure test. If the test pressure is equal to or less than 0.5 psig (14-in. wc), turn off electric shutoff switch located on the gas valve before the test. It is recommended that the ground joint union be loosened before pressure testing. After all connections have been made, purge the lines and check for leakage with regulated gas supply pressure. Step 8—Electrical Connections A89417 Fig. 8—Typical Gas Pipe Arrangement The cabinet MUST have an uninterrupted or unbroken ground according to NEC, ANSI/NFPA 70-1999 and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death. The junction box (J-box) can be moved to the left-hand side of the furnace when a left-side power supply is desired. Remove the 2 screws holding the auxiliary J-box. Mount the J-box on the left-hand side of the furnace (holes have been pre-drilled in casing). When moved, tuck the wiring harness behind the clip provided to keep extra wire lengths out of the way. NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light will flash rapidly and the furnace will not operate. 115-V WIRING — Refer to the unit rating plate or Table 5 for equipment electrical requirements. The control system requires an earth ground for proper operation. 24-V WIRING Make field 24-v connections at the 24-v terminal strip. (See Fig. 15.) Connect terminal Y/Y2 as shown in Fig. 9 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. The 24-v circuit contains an automotive-type, 3-amp fuse located on the main control board. Any 24-v shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size. Make all electrical connections in accordance with the National Electrical Code (NEC) ANSI/NFPA 70-1999 and local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with CSA C22.1 Canadian Electrical Code, or authorities having jurisdiction. ACCESSORIES 1. Electronic Air Cleaner (EAC) Two quick-connect terminals, marked EAC-1 and EAC-2, are provided for EAC connection. (See Fig. 15). These terminals are energized with 115-v, (1.0-amp maximum) during blower motor operation. 8 FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING NOTE 2 W FIVE WIRE THREE-WIRE HEATING-ONLY C R G Y THERMOSTAT TERMINALS FIELD-SUPPLIED DISCONNECT 208/230- OR 460-V THREE PHASE BLOWER DOOR SWITCH BLK BLK WHT WHT W GND 115-V FIELDSUPPLIED DISCONNECT GND AUXILIARY J-BOX C O N T R O L R 208/230-V SINGLE PHASE G COM GND NOTE 1 CONDENSING UNIT Y/Y2 24-V TERMINAL BLOCK FURNACE TWO WIRE NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation. 2. Some thermostats require a "C" terminal connection as shown. 3. If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. A99440 Fig. 9—Standard Heating and Cooling Application Wiring Diagram Table 5—Electrical Data UNIT SIZE VOLTS— HERTZ— PHASE 045-08 045-12 070-08 070-12 091-14 091-16 111-12 111-16 111-20 136-16 136-20 155-20 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 115—60—1 OPERATING VOLTAGE RANGE Maximum* Minimum* 127 104 127 104 127 104 127 104 127 104 127 104 127 104 127 104 127 104 127 104 127 104 127 104 MAXIMUM UNIT AMPS MINIMUM WIRE GAGE MAXIMUM WIRE LENGTH (FT)‡ MAXIMUM FUSE OR CKT BKR AMPS† 6.0 8.3 5.9 8.7 9.0 10.4 8.0 10.1 14.4 10.1 13.3 14.0 14 14 14 14 14 14 14 14 12 14 12 12 47 34 47 32 31 27 35 28 31 28 33 31 15 15 15 15 15 15 15 15 20 15 20 20 * Permissible limits of the voltage range at which the unit operates satisfactorily. † Time-delay type is recommended. ‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. Step 9—Venting Refer to the national or local installation code such as NFGC in the United States or the NSCNGPIC in Canada for proper vent sizing and installation requirements. Use the enclosed Installation Instruction (Single-Stage Vent Tables for Category I Fan-Assisted Furnaces) for a quick, easy reference. After fully assembling the vent connector to the furnace flue collar, securely fasten the vent connector to the collar with two fieldsupplied, corrosion-resistant, sheet metal screws located 180° apart and midway up the collar. The horizontal portion of the venting system shall maintain a minimum of 1/4-in. upward slope per linear ft and it shall be rigidly supported every 5 ft or less with hangers or straps to ensure that there will be no movement after installation. 2. Humidifier (HUM) Quick-connect terminal (HUM) and screw terminal (COM24V) are provided for 24-v humidifier connection. The terminals are energized with 24-v 0.5-amp maximum after inducer motor prepurge period. DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat™, Zone Controller or similar device. See Thermidistat, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection. A failure to follow this warning could result in fire. NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation. 9 THERMIDISTAT FURNACE CONTROL 1-SPEED AIR CONDITIONER N/A O/W2 N/A Y1/W2 Y1 HEAT STAGE 1 W/W1 W Y/Y2 Y/Y2 FAN G G 24 VAC HOT R R COOL STAGE 1 DEHUMIDIFY DHUM 24 VAC COMM Y DHUM C COM C HUM HUMIDIFY HUMIDIFIER (24 VAC) HUM N/A B OUTDOOR SENSOR CONNECTION S1 OUTDOOR SENSOR S2 See notes 5, 7, and 10 A99435 Fig. 10—Single-Stage Furnace with 1-Speed Air Conditioner THERMIDISTAT FURNACE CONTROL 2-SPEED AIR CONDITIONER N/A O/W2 COOL STAGE 1 Y1/W2 Y1 HEAT STAGE 1 W/W1 W Y/Y2 Y/Y2 FAN G G 24 VAC HOT R R COOL STAGE 1 DEHUMIDIFY DHUM 24 VAC COMM Y1 Y2 R DHUM COM C C HUM HUMIDIFY HUMIDIFIER (24 VAC) HUM N/A B OUTDOOR SENSOR CONNECTION S1 OUTDOOR SENSOR S2 See notes 5, 8, and 10 A99436 Fig. 11—Single-Stage Furnace with 2-Speed Air Conditioner 10 FURNACE CONTROL THERMIDISTAT 1-SPEED HEAT PUMP O RVS COOLING O/W2 N/A Y1/W2 Y1 HEAT STAGE 2 W/W1 W W2 Y/Y2 Y/Y2 Y FAN G G 24 VAC HOT R R (FURNACE) HEAT/COOL STAGE 1 (COMPRESSOR) DEHUMIDIFY DHUM 24 VAC COMM R DHUM COM C C HUM HUMIDIFY HUMIDIFIER (24 VAC) HUM N/A B OUTDOOR SENSOR CONNECTION S1 OUTDOOR SENSOR S2 See notes 1, 4, 6, 7, 9, and 10. A99437 Fig. 12—Single-Stage Furnace with 1-Speed Heat Pump (Dual Fuel) FURNACE CONTROL THERMIDISTAT 2-SPEED HEAT PUMP O RVS COOLING O/W2 Y1 Y1 W W2 Y/Y2 Y/Y2 Y2 FAN G G W3 24 VAC HOT R R R HEAT/COOL STAGE 1 Y1/W2 (COMPRESSOR LO) HEAT STAGE 3 W/W1 (FURNACE) HEAT/COOL STAGE 2 (COMPRESSOR HI) DEHUMIDIFY DHUM 24 VAC COMM DHUM COM C C HUM HUMIDIFY HUMIDIFIER (24 VAC) HUM N/A B OUTDOOR SENSOR CONNECTION S1 OUTDOOR SENSOR S2 See notes 1, 2, 3, 4, 6, 8, 9, and 10. A99438 Fig. 13—Single-Stage Furnace with 2-Speed Heat Pump (Dual Fuel) 11 FURNACE CONTROL TWO-STAGE THERMOSTAT 2-SPEED AIR CONDITIONER OR HEAT PUMP Heat Pump only O O Y1 Y1 W W W2 Y2 Y/Y2 Y2 G G W3 R R R Heat Pump only Y1 DHUM C COM C HUM HUMIDIFIER (24 VAC) See notes 1, 2, and 9. A99439 Fig. 14—Single-Stage Furnace with 2-Speed Outdoor Unit Notes: 1. Heat pump must have a high pressure switch for dual fuel applications. 2. Refer to outdoor equipment Installation Instructions for proper setup. 3. Select the "zone" position on the 2-speed heat pump control. 4. Outdoor air sensor must be attached in all dual fuel applications. 5. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default. 6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations. 7. Dip switch No. 2 on Thermidistat should be set in OFF position for single-speed compressor operation. This is factory default. 8. Dip switch No. 2 on Thermidistat should be set in ON position for 2-speed compressor operation. 9. Configuration Option No. 10 "Dual Fuel Selection" must be turned ON in all dual fuel applications. 10. No connection should be made to the furnace HUM terminal when using a Thermidistat. Step 10—Start-Up, Adjustment, and Safety Check SEQUENCE OF OPERATION GENERAL NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light will flash rapidly and furnace will not operate. Furnace control must be grounded for proper operation, or control will lockout. Control is grounded through green wire routed to gas valve and burner bracket screw. The furnace must have a 115-v power supply properly connected and grounded. Proper polarity must be maintained for correct operation. Thermostat wire connections at R, W, C, and Y must be made at the 24-v terminal block on the control board. The gas service pressure must not exceed 0.5 psig (14-in. wc), but must be no less than 0.16 psig (4.5-in. wc). Using the schematic diagram shown in Fig. 16, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully. NOTE: If there is a power interruption and any thermostat call, the control initiates a 90-sec blower only on period before starting another cycle. This furnace is equipped with a manual reset limit switch or fuse link in the gas control area. The switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switch. Correct inadequate combustion air supply problem and reset the switch or replace the fuse link. Before operating the furnace, check each manual reset switch for continuity. If necessary, press the button to reset the switch. The blower compartment door must be in place to complete the 115-v circuit to the furnace. 12 BLOWER OFF DELAY JUMPER SELECT Y1 DHUM G Com W Y/Y 2 R 24V J1 TEST/TWIN HUM HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX) HARNESS CONNECTOR 3-AMP FUSE SEC-1 24-V TRANSFORMER SEC-2 LED OPERATION & DIAGNOSTIC LIGHT EAC-2 115-VAC (L2) NEUTRAL CONNECTION 1 2 3 4 5 6 7 8 9 10 11 24-V THERMOSTAT TERMINALS 1 2 3 4 5 90 135 180 225 COOL HOT SURFACE IGNITOR CONNECTOR HEAT BLOWER SPEED SELECTION TERMINALS PRI SPARE-1 115-VAC (L1) POWER SUPPLY FAN SPARE-2 INDUCER MOTOR CONNECTOR EAC-1 ELECTRONIC AIR CLEANER TERMINALS (115-VAC 1.0 AMP MAX) A99417 Fig. 15—Furnace Control 1. Heating mode When the wall thermostat "calls for heat," the R-W circuit closes. The furnace control performs a self-check, verifies the pressure switch contacts are open, and starts inducer motor. stopping gas flow to the burners. The blower motor and EAC remain energized 90, 135, 180, or 225 sec (depending on the blower off-time selection). The furnace is factory set for a 135-sec blower off delay. a. Prepurge period—As the inducer motor comes up to speed, the pressure switch contacts close to begin a 15-sec prepurge period. h. Post-purge—The inducer motor remains energized 5 sec after the burners are extinguished. If jumper is across PL 7-6 and PL 7-9, the post-purge period is 15 sec. 2. Cooling mode b. Igniter warm-up—At the end of the prepurge period, the igniter is energized for a 17-sec igniter warm-up period. a. Single-Speed Outdoor Unit-See Figures 9,10 and 12. The thermostat closes the R to G and Y circuits. The R-Y/Y2 circuit starts the outdoor unit, and the R to G and Y/Y2 circuits start the furnace blower motor on COOL speed. Electronic air cleaner EAC-1 terminal is energized with 115v whenever blower is operating. When thermostat is satisfied, R to G and Y/Y2 circuits are opened. The outdoor unit stops and the furnace blower continues operating on COOL speed for an additional 90 sec. Jumper Y/Y2 to DHUM on the furnace control to reduce the cooling off-delay to 3 sec from 90. See figure 15. b. Two-Speed Outdoor Unit without Thermidistat-See Fig. 14. c. Ignition sequence—When the igniter warm-up period is completed, the gas valve opens, permitting gas flow to the burners where it is ignited. After 5 sec, the igniter is de-energized and a 2-sec flame-sensing period begins. d. HUM terminal is energized with the gas valve. See accessories in the Electrical Connections section. e. Flame-sensing—When burner flame is sensed, the control begins the blower on delay period and continues holding the gas valve open. If burner flame is not sensed, the control closes the gas valve and repeats ignition cycle. NOTE: Ignition sequence will repeat 3 additional time before a lockout occurs. Lockout automatically resets after 3 hr, or can be manually reset by turning 115v off (not at thermostat) for 3 sec minimum, then on again. The thermostat closes the R to G and Y1 circuits for low cooling and the R to G, Y1 and Y/Y2 circuits for high cooling. The R to Y1 circuit starts the outdoor unit on low cooling and the R to G and Y1 circuits start the furnace blower on FAN speed. The R to Y1 and Y2 circuits start the outdoor unit on high cooling and the R to G, Y1 and Y2 circuits start the furnace blower on COOL speed. If the R to Y2 circuit opens with the R to G and Y1 circuits still closed, the outdoor unit will drop to low cooling and the furnace control will drop the blower speed to FAN. f. Blower on delay—Forty-five sec after burner flame is proven, the blower motor is energized on heating speed. Simultaneously, the humidifier and electronic air cleaner terminals (HUM and COM-24V for humidifier, EAC-1 and EAC-2 for electronic air cleaner) are energized. If jumper is across PL 7-6 and PL 7-9. g. Blower off delay—When the thermostat is satisfied, the circuit between R-W is broken, de-energizing the gas valve 13 14 SEC-2 R Y/Y2 GND GV GVR HI/LO HSI HSIR HUM IDM IDR ILK JB LED LGPS LS OL PCB BLWR BLWM CAP CPU EAC-1 EAC-2 FAN FL FRS FSE FU1 FU2 EAC-1 START L1 6 5 4 9 8 7 BRN BRN WHT WHT 3 2 1 BLU ORN PL1 RED PL2 1 CAP -1 GRN PR1 2 GRN PL7 ORN BLK BLK WHT ILK WHT (COM) BLK RED FSE BLU 2 1 PL6 2 1 FRS2 FL NOTE #5 GV NOTE #11 (WHEN USED) LGPS WHT IDM WHT BLK YEL PRS FU1 HSIR IDR GVR-2 SEC-1 2 1 CPU HI/LO PL6 GVR-1 GVR SEC-2 PL3 2 1 COOL SPARE-1 HEAT FAN 2 3 1 2 8 6 HSI OL 9 NOT USED 3 11 7 NOT USED FRS2 GV NOTE #5 FSE FL (WHEN USED) NOTE #10 ALS NOTE #12 PRS (WHEN USED) NOTE #12 BVSS 6 5 8 2 DSS L2 EAC-2 (WHEN USED) NOTE #10 FRS1 IDM BLWM LGPS (WHEN USED) NOTE #11 LS 9 1 5 10 3 PL7 4 1 7 START CAP-1 SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE) NOT USED 4 PL1 2 1 COM LO MED LO MED HI HI EQUIPMENT GROUND PL5 HI/LO GND BLWR 24VAC 115VAC NOTE #6 TRAN PR1 PL2 FAN EAC-1 HSIR L2 A99407 1. If any of the original equipment wire is replaced use wire rated for 105°C. 2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL). 3. Blower motor speed selections are for average conditions, see installation instructions for details on optimum speed selection. 4. Use only copper wire between the disconnect switch and the furnace junction box (JB). 5. This wire must be connected to furnace sheet metal for control to detect flame. 6. Replace only with a 3 amp fuse. 7. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds. 8. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds. 9. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset after three hours. 10. When used, auxiliary limit switch (ALS) is on some downflow models only. When used, FL is on upflow models only. FRS1 and FRS2 only used downflow and horizontal models. 11. Factory connected when LGPS is not used. 12. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is installed. 325771-101 REV. B NOTES: COM G Y1 IDR TEST/TWIN DHUM Y/Y2 W R HUM ILK BLWR L1 L1 TO 115VAC FIELD DISCONNECT NOTE #4 Fig. 16—Furnace Wiring Diagram PLUG RECEPTACLE FIELD SPLICE EQUIPMENT GROUND FIELD EARTH GROUND FIELD WIRING TERMINAL CONDUCTOR ON PCB FIELD WIRING (24VAC) FIELD WIRING (115VAC) FACTORY WIRING (24VAC) FACTORY WIRING (115VAC) PCB TERMINAL UNMARKED TERMINAL 10-CIRCUIT PCB CONNECTOR 2-CIRCUIT PCB CONNECTOR 3-CIRCUIT ADAPTER CONNECTOR 2-CIRCUIT ADAPTER CONNECTOR 2-CIRCUIT HSI, PCB CONNECTOR 9-CIRCUIT ADAPTER CONNECTOR PRESSURE SWITCH, SPST-(N.O.) COMPONENT TEST & TWIN TERMINAL TRANSFORMER-115VAC/24VAC JUNCTION FUSED OR CIRCUIT BREAKER DISCONNECT SWITCH (WHEN REQ'D) NOTE #4 NEUTRAL WHT L1 BLK FU2 GRN WHT BLK WHT BLK WHT WHT GND GRN JB BLK PL5 RED BLU FRS1 (WHEN USED) NOTE #10 PL1 PL2 PL3 PL5 PL6 PL7 PRS TEST/TWIN TRAN 1 2 3 PL3 GRN LS NOTE #12 ORN (WHEN USED) NOTE #10 ALS ORN ORN (WHEN USED) NOTE #12 BVSS ORN RED DSS WHT BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR CAPACITOR MICROPROCESSOR AND CIRCUITRY ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FAN SELECT RELAY FUSE LINK FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME PROVING ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE (FIELD INSTALLED & SUPPLIED) EQUIPMENT GROUND GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITOR (115 VAC) HOT SURFACE IGNITOR RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.) INDUCED DRAFT MOTOR INDUCED DRAFT RELAY, SPST-(N.O.) BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS PRESSURE SWITCH, SPST-(N.O.) LIMIT SWITCH, AUTO RESET, SPST(N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW. PRINTED CIRCUIT BOARD LEGEND RED (LO) OL SPARE 2 PL1 J1 BLWM HUM FAN EAC-2 LED 1 SEC-1 FU1 BLK (HI) YEL (MED HI) BLU (MED LO) WHT (COM) SPARE 1 5 4 3 2 1 TEST/TWIN 225 180 G Com 24V W 90 135 1 2 3 4 5 6 7 8 9 10 11 Y1 RED WHT WHT GRN DHUM L2 HEAT COOL WHT YEL PCB TRAN BLOWER OFF DELAY JUMPER SELECT HSI setting of FAN to HEAT speed. Momentarily turning off the FAN switch again at the thermostat will shift the continuous blower speed selection from HEAT to COOL. Repeating the procedure will cause the control to shift from COOL to FAN speed. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption. When the R to G and Y1 circuit open, the furnace blower continues operating on FAN speed for an additional 90 sec. To set the cooling off-delay to 3 sec instead of 90, connect a jumper between the Y1 and DHUM thermostat connects on the furnace control. c. Two-Speed Outdoor Unit with Thermidistat-See Figure 11 and 13. 5. Heat pump mode The dehumidification output, DHUM, on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists and is turned OFF when demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the control operates in Thermidistat mode. When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off time during demand defrost cycles. When the W-Y1, W-Y/Y2, W-Y1-G, or W-Y/Y2-G thermostat inputs are received at the same time, the control changes the blower to HEAT speed or starts the blower if it was off, and begins a heating cycle. The blower remains on until the end of the prepurge period, then shuts off until the end of the ignition warm-up and trial for ignition periods (a total of 24 sec). The blower then comes back on at HEAT speed. The thermostat closes the R to G and Y1 circuits for low cooling and the R to G, Y1 and Y/Y2 circuits for high cooling. The R to Y1 circuit starts the outdoor unit on low cooling and the R to G and Y1 circuits start the furnace blower on FAN speed. The R to Y1 and Y2 circuits start the outdoor unit on high cooling and the R to G, Y1 and Y2 circuits start the furnace blower in COOL speed. If the R to Y2 circuit opens with the R to G and Y1 circuits still closed, the outdoor unit will drop to low cooling and the furnace control will drop the blower speed to FAN. When the thermostat is satisfied, the R to G and Y1 circuits are opened. The outdoor unit stops. When there is a dehumidify demand, the cooling blower off-delay is decreased from 90 to 3 sec. When the W input signal disappears, the control begins the normal inducer post-purge period and the blower changes to COOL speed after a 1-sec delay. If the W-Y/Y2-G or W-Y1-G signals disappear at the same time, the blower remains on for the selected heating blower off delay period and the inducer goes through its normal post-purge period. If the W-Y1 or W-Y/Y2 inputs should disappear, leaving the G signal input, the blower remains on at HEAT speed for the selected blower off-delay period and the inducer remains on for the normal post-purge period. After the blower off-delay is completed the control switches the blower to FAN speed. Anytime the control senses false flame, the control locks out of the heating mode. This occurs because the control cannot sense the W input due to the false flame signal, and as a result, sees only the Y/Y2 and/or Y1 input and goes into cooling mode, blower off delay. All other control functions remain in standard format. In Two-Speed Cooling with only the R to G and Y1 circuits closed and there is a demand for dehumidification, the furnace control blower will remain at FAN speed. In high cooling with a demand for dehumidification, the furnace control will drop the blower speed from COOL to HEAT for a maximum of 10 minutes before reverting back to COOL speed. If there is still a demand for dehumidification after 20 minutes, the control will drop the blower speed back to HEAT speed. This alternating 10-minute cycle will continue as long as there is a call for cooling. If the DHUM input is low for more than 48 hours, the control reverts back to non-Thermidistat operation. NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized START-UP PROCEDURES 1. Purge gas lines—After all connections have been made, purge the lines and check for leaks. 3. Continuous blower mode Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning can cause fire, explosion, personal injury, or death. NOTE: EAC-1 terminal is energized with 115v whenever blower operates. When the R-G circuit is made, the blower motor operates on FAN speed. During a call for heat, the blower stops, allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the 45-sec blower on delay period at HEAT speed. If jumper is across PL7-6 AND PL7-9, the blower on delay is 66 sec. 2. Component test—The furnace control board allows all components, except gas valve, to be run for a short period of time. This feature helps diagnose a system problem in case of a component failure. To initiate component test procedure, short (jumper) the TEST 3/16-in. quick connect terminal on control (behind the Y/Y2 terminal) and the COM-24V terminal on furnace thermostat connection block for approximately 2 sec. (See Fig. 15.) The blower reverts back to FAN speed after the heating blower OFF delay is completed. When the thermostat "calls for cooling," the blower operates on COOL speed. When the thermostat is satisfied, the blower operates an additional 90 sec before reverting back to continuous operation on FAN speed. NOTE: Component test feature will not operate if any thermostat signal is present at control board. 4. Continuous blower speed selection from thermostat Component test sequence is as follows. To select different continuous blower speeds from the room thermostat, momemtarily turn off the FAN switch or pushbutton on the room thermostat for 1-3 sec after the blower is operating. The control will shift the blower speed from factory a. Momentarily jumper TEST and COM-24V terminals until LED goes off. b. LED will display previous status code 4 times. 15 c. Inducer motor starts and continues to run for entire component test. DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overtire and heat exchanger failures. d. Hot surface igniter is energized for 15 sec, then deenergized. e. Blower motor operates on FAN speed for 10 sec, then stops. NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics. f. Blower motor operates on HEAT speed for 10 sec, then stops. g. Blower motor operates on COOL speed for 10 sec, then stops h. Inducer motor stops 3. To operate furnace, follow procedures on operating instructions label attached to furnace. 4. With furnace operating, set thermostat below room temperature and observe that furnace goes off. Set thermostat above room temperature and observe that furnace restarts. ADJUSTMENTS 1. Set gas input rate Furnace gas input rate on furnace rating plate is for installations at altitudes up to 2000 ft. Furnace input rate must be within ±2 percent of input on furnace rating plate. BURNER ORIFICE a. Determine natural gas orifice size and manifold pressure for correct input. (1.) Obtain average yearly gas heat value (at installed altitude) from local gas supplier. A93059 (2.) Obtain average yearly specific gas gravity from local gas supplier. DO NOT redrill orifices. Improper drilling (burrs, out-ofround holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of burners and heat exchangers, causing failures. (3.) Verify furnace model. Table 6 can only be used for model 58WAV Furnaces. (4.) Find installation altitude in Table 6. NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A. altitudes of 2001 to 3000 ft in Table 6. (3.) After correct manifold pressure is obtained, replace gas valve regulator adjustment screw cap and verify adjusted gas input rate using method outlined in item c. (5.) Find closest natural gas heat value and specific gravity in Table 6. (6.) Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation . (4.) Burner flame should be clear blue, almost transparent. (See Fig. 18.) c. Verify natural gas input rate by clocking gas meter. EXAMPLE: (0—2000 ft altitude) Heating value = 1025 Btu/cu ft Specific gravity = 0.62 Therefore: Orifice No. 43* Manifold pressure 3.3-in. wc * Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate. NOTE: High-Altitude Adjustment United States At installation altitudes above 2000 ft, this furnace has been approved for a 4 percent derate for each 1000 ft above sea level. See Table 7 for derate multiplier factor. EXAMPLE: 88,000 Btuh input furnace installed at 4300 ft. (7.) Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY. Furnace Input Rate at Sea Level X Derate Multiplier Factor = 88,000 X 0.82 = b. Adjust manifold pressure to obtain input rate. Furnace Input Rate at Installation Altitude 72,160 (1.) Remove regulator adjustment seal cap. (See Fig. 17.) (2.) Turn adjusting screw, counterclockwise (out) to decrease manifold pressure or clockwise (in) to increase manifold pressure. Canada At installation altitudes from 2000 to 4500 ft, this furnace must be derated 10 percent by an authorized Gas Conversion Station. To determine correct input rate for altitude, see example above and use 0.90 as derate multiplier factor. NOTE: This furnace has been approved for a manifold pressure of 3.2-in. wc to 3.8-in. wc when installed at altitudes up to 2000 ft. For altitudes above 2000 ft, the manifold pressure can be adjusted from 2.0-in. wc to 3.8-in. wc. a. Turn off all other gas appliances and pilots. 16 Table 6—Model 58WAV Orifice Size* and Manifold Pressure for Correct Input (Tabulated Data Based on 22,000 Btuh per Burner, Derated 4 Percent per 1000 Ft Above Sea Level) U.S.A. and Canada ALTITUDE RANGE (FT) 0 to 2000 U.S.A. and Canada ALTITUDE RANGE (FT) U.S.A. Altitudes 2001 to 3000 or Canada Altitudes 2000 to 4500 U.S.A. Only ALTITUDE RANGE (FT) 3001 to 4000 U.S.A. Only ALTITUDE RANGE (FT) 4001 to 5000 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 850 875 900 925 950 975 1000 1025 1050 1075 1100 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 775 800 825 850 875 900 925 950 975 1000 1025 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 750 775 800 825 850 875 900 925 950 975 1000 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 725 750 775 800 825 850 875 900 925 950 0.58 Orifice Manifold No. Pressure 42 3.6 42 3.4 42 3.2 43 3.7 43 3.6 43 3.4 43 3.2 44 3.5 44 3.3 45 3.8 45 3.7 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 42 3.8 41 3.5 41 3.6 42 3.6 42 3.7 42 3.8 42 3.4 42 3.5 42 3.6 42 3.2 42 3.3 42 3.4 43 3.7 43 3.8 42 3.2 43 3.5 43 3.6 43 3.7 43 3.3 43 3.4 43 3.5 43 3.2 43 3.3 43 3.4 44 3.4 44 3.6 43 3.2 44 3.3 44 3.4 44 3.5 45 3.8 44 3.2 44 3.4 Orifice No. 41 41 42 42 42 43 43 43 43 43 44 0.66 Manifold Pressure 3.7 3.5 3.7 3.5 3.3 3.8 3.6 3.5 3.3 3.2 3.5 0.58 Orifice Manifold No. Pressure 42 3.4 43 3.8 43 3.6 43 3.4 43 3.2 43 3.0 43 2.9 43 2.7 43 2.6 43 2.5 43 2.3 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 42 3.5 42 3.6 42 3.7 42 3.3 42 3.4 42 3.5 43 3.7 42 3.2 42 3.3 43 3.5 43 3.6 43 3.8 43 3.3 43 3.4 43 3.5 43 3.1 43 3.2 43 3.3 43 3.0 43 3.1 43 3.2 43 2.8 43 2.9 43 3.0 43 2.7 43 2.8 43 2.9 43 2.5 43 2.6 43 2.7 43 2.4 43 2.5 43 2.6 Orifice No. 42 42 42 42 43 43 43 43 43 43 43 0.66 Manifold Pressure 3.8 3.6 3.4 3.2 3.6 3.4 3.3 3.1 2.9 2.8 2.7 0.58 Orifice Manifold No. Pressure 43 3.8 43 3.6 43 3.4 43 3.2 43 3.0 43 2.8 43 2.7 43 2.5 43 2.4 43 2.3 43 2.2 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 42 3.3 42 3.4 42 3.5 43 3.7 43 3.8 42 3.3 43 3.5 43 3.6 43 3.7 43 3.3 43 3.4 43 3.5 43 3.1 43 3.2 43 3.3 43 2.9 43 3.0 43 3.1 43 2.8 43 2.9 43 2.9 43 2.6 43 2.7 43 2.8 43 2.5 43 2.6 43 2.6 43 2.4 43 2.4 43 2.5 43 2.2 43 2.3 43 2.4 Orifice No. 42 42 43 43 43 43 43 43 43 43 43 0.66 Manifold Pressure 3.6 3.4 3.8 3.6 3.4 3.2 3.0 2.9 2.7 2.6 2.5 0.58 Orifice Manifold No. Pressure 43 3.6 43 3.4 43 3.2 43 3.0 43 2.8 43 2.6 43 2.5 43 2.3 43 2.2 43 2.1 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 3.7 42 3.2 42 3.3 43 3.5 43 3.6 43 3.7 43 3.3 43 3.4 43 3.5 43 3.1 43 3.2 43 3.3 43 2.9 43 3.0 43 3.1 43 2.7 43 2.8 43 2.9 43 2.6 43 2.6 43 2.7 43 2.4 43 2.5 43 2.6 43 2.3 43 2.4 43 2.4 43 2.2 43 2.2 43 2.3 Orifice No. 42 43 43 43 43 43 43 43 43 43 0.66 Manifold Pressure 3.4 3.8 3.6 3.4 3.2 3.0 2.8 2.7 2.5 2.4 * Orifice sizes shown in BOLD are factory installed. 17 Table 6—Model 58WAV Orifice Size* and Manifold Pressure for Correct Input (Continued) (Tabulated Data Based on 22,000 Btuh per Burner, Derated 4 Percent per 1000 Ft Above Sea Level) U.S.A. Only ALTITUDE RANGE (FT) 5001 to 6000 U.S.A. Only ALTITUDE RANGE (FT) 6001 to 7000 U.S.A. Only ALTITUDE RANGE (FT) 7001 to 8000 U.S.A. Only ALTITUDE RANGE (FT) 8001 to 9000 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 700 725 750 775 800 825 850 875 900 925 950 975 1000 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 650 675 700 725 750 775 800 825 850 875 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 625 650 675 700 725 750 775 800 825 850 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 600 625 650 675 700 725 750 775 800 0.58 Orifice Manifold No. Pressure 43 3.4 43 3.1 43 2.9 43 2.7 43 2.6 43 2.4 43 2.3 43 2.2 43 2.0 48 3.6 48 3.4 49 3.8 49 3.6 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 3.5 43 3.6 43 3.7 43 3.2 43 3.4 43 3.5 43 3.0 43 3.1 43 3.2 43 2.8 43 2.9 43 3.0 43 2.7 43 2.8 43 2.8 43 2.5 43 2.6 43 2.7 43 2.4 43 2.4 43 2.5 43 2.2 43 2.3 43 2.4 43 2.1 43 2.2 43 2.2 48 3.8 43 2.1 43 2.1 48 3.6 48 3.7 43 2.0 48 3.4 48 3.5 48 3.6 49 3.8 48 3.3 48 3.4 Orifice No. 43 43 43 43 43 43 43 43 43 43 43 48 48 0.66 Manifold Pressure 3.8 3.6 3.3 3.1 2.9 2.8 2.6 2.5 2.3 2.2 2.1 3.7 3.5 0.58 Orifice Manifold No. Pressure 43 3.4 43 3.1 43 2.9 43 2.7 43 2.5 43 2.4 43 2.2 43 2.1 48 3.7 48 3.5 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 3.5 43 3.6 43 3.7 43 3.2 43 3.4 43 3.5 43 3.0 43 3.1 43 3.2 43 2.8 43 2.9 43 3.0 43 2.6 43 2.7 43 2.8 43 2.5 43 2.5 43 2.6 43 2.3 43 2.4 43 2.5 43 2.2 43 2.2 43 2.3 43 2.0 43 2.1 43 2.2 48 3.6 48 3.8 43 2.1 Orifice No. 43 43 43 43 43 43 43 43 43 43 0.66 Manifold Pressure 3.8 3.6 3.3 3.1 2.9 2.7 2.5 2.4 2.3 2.1 0.58 Orifice Manifold No. Pressure 43 3.1 43 2.9 43 2.7 43 2.5 43 2.3 43 2.2 43 2.0 48 3.6 48 3.4 49 3.8 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 3.3 43 3.4 43 3.5 43 3.0 43 3.1 43 3.2 43 2.8 43 2.9 43 3.0 43 2.6 43 2.7 43 2.8 43 2.4 43 2.5 43 2.6 43 2.3 43 2.3 43 2.4 43 2.1 43 2.2 43 2.3 48 3.7 43 2.1 43 2.1 48 3.5 48 3.6 48 3.8 48 3.3 48 3.4 48 3.5 Orifice No. 43 43 43 43 43 43 43 43 43 48 0.66 Manifold Pressure 3.6 3.3 3.1 2.9 2.7 2.5 2.3 2.2 2.1 3.6 0.58 Orifice Manifold No. Pressure 43 2.9 43 2.7 43 2.5 43 2.3 43 2.2 43 2.0 48 3.5 48 3.3 49 3.6 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 3.0 43 3.1 43 3.2 43 2.8 43 2.9 43 3.0 43 2.6 43 2.7 43 2.8 43 2.4 43 2.5 43 2.6 43 2.2 43 2.3 43 2.4 43 2.1 43 2.1 43 2.2 48 3.6 43 2.0 43 2.1 48 3.4 48 3.5 48 3.6 49 3.8 48 3.3 48 3.4 Orifice No. 43 43 43 43 43 43 43 48 48 0.66 Manifold Pressure 3.3 3.1 2.8 2.6 2.4 2.3 2.1 3.8 3.5 * Orifice sizes shown in BOLD are factory installed. 18 Table 6—Model 58WAV Orifice Size* and Manifold Pressure for Correct Input (Continued) (Tabulated Data Based on 22,000 Btuh per Burner, Derated 4 Percent per 1000 Ft Above Sea Level) U.S.A. Only ALTITUDE RANGE (FT) 9001 to 10,000 AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) 575 600 625 650 675 700 725 750 775 0.58 Orifice Manifold No. Pressure 43 2.7 43 2.5 43 2.3 43 2.1 48 3.7 48 3.4 49 3.8 49 3.5 49 3.3 SPECIFIC GRAVITY OF NATURAL GAS 0.60 0.62 0.64 Orifice Manifold Orifice Manifold Orifice Manifold No. Pressure No. Pressure No. Pressure 43 2.8 43 2.9 43 3.0 43 2.6 43 2.7 43 2.7 43 2.4 43 2.4 43 2.5 43 2.2 43 2.3 43 2.3 43 2.0 43 2.1 43 2.2 48 3.6 48 3.7 43 2.0 48 3.3 48 3.4 48 3.5 49 3.6 49 3.8 48 3.3 49 3.4 49 3.5 49 3.6 Orifice No. 43 43 43 43 43 43 48 48 49 0.66 Manifold Pressure 3.1 2.8 2.6 2.4 2.2 2.1 3.6 3.4 3.7 * Orifice sizes shown in BOLD are factory installed. Table 7—Altitude Derate Multiplier for U.S.A. ALTITUDE (FT) 0—2000 2001—3000 3001—4000 4001—5000 5001—6000 6001—7000 7001—8000 8001—9000 9001—10,000 % OF DERATE 0 8—12 12—16 16—20 20—24 24—28 28—32 32—36 36—40 Table 8—Gas Rate (Cu Ft/Hr) DERATE MULTIPLIER FACTOR FOR U.S.A.* 1.00 0.90 0.86 0.82 0.78 0.74 0.70 0.66 0.62 SECONDS FOR 1 REVOLUTION 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 * Derate multiplier factor is based on midpoint altitude for altitude range. b. Start furnace and let operate for 3 minutes. c. Measure time (in sec) for gas meter test dial to complete 1 revolution. d. Refer to Table 8 for cu ft of gas per hr. e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft) using natural gas heating value from local gas utility/supplier. EXAMPLE: (0—2000 ft altitude) Furnace input from rating plate is 110,000 Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 1050 Btu/cu ft Time for 1 revolution of 2-cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 8) Btu heating input = 103 X 1050 = 108,150 Btuh In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate. 2. Set temperature rise. Furnace must operate within range of temperature rise specified on the furnace rating plate. Determine the air temperature rise as follows. a. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not "see" heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts. b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine temperature rise. 19 SIZE OF SIZE OF SECONDS TEST DIAL TEST DIAL FOR 1 1 2 5 2 5 REVOLUTION 1 cu ft cu ft cu ft cu ft cu ft cu ft 360 720 1800 50 72 144 360 327 655 1636 51 71 141 355 300 600 1500 52 69 138 346 277 555 1385 53 68 136 340 257 514 1286 54 67 133 333 240 480 1200 55 65 131 327 225 450 1125 56 64 129 321 212 424 1059 57 63 126 316 200 400 100 58 62 124 310 189 379 947 59 61 122 305 180 360 900 60 60 120 300 171 343 857 62 58 116 290 164 327 818 64 56 112 281 157 313 783 66 54 109 273 150 300 750 68 53 106 265 144 288 720 70 51 103 257 138 277 692 72 50 100 250 133 267 667 74 48 97 243 129 257 643 76 47 95 237 124 248 621 78 46 92 231 120 240 600 80 45 90 225 116 232 581 82 44 88 220 113 225 563 84 43 86 214 109 218 545 86 42 84 209 106 212 529 88 41 82 205 103 206 514 90 40 80 200 100 200 500 92 39 78 196 97 195 486 94 38 76 192 95 189 474 96 38 75 188 92 185 462 98 37 74 184 90 180 450 100 36 72 180 88 176 439 102 35 71 178 86 172 429 104 35 69 173 84 167 419 106 34 68 170 82 164 409 108 33 67 167 80 160 400 110 33 65 164 78 157 391 112 32 64 161 76 153 383 116 31 62 155 75 150 375 120 30 60 150 73 147 367 ON AND OFF SWITCH Recheck temperature rise. It must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise or above. GAS PRESSURE REGULATOR ADJUSTMENT 3. Set thermostat heat anticipator. The thermostat heat anticipator must be set to match the amp draw of the electrical components in the R-W circuit. Accurate amp draw readings can be obtained at thermostat subbase terminals R and W. Fig. 19 illustrates an easy method of obtaining the actual amp draw. The amp reading should be taken after the blower motor has started. See the thermostat manufacturer’s instructions for adjusting the heat anticipator and for varying the heating cycle length. INLET PRESSURE TAP NOTE: When using an electronic thermostat, set the cycle rate for 3 cycles per hr. MANIFOLD PRESSURE TAP THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE OUT OF CIRCUIT.) A95618 Fig. 17—Redundant Automatic Gas Control Valve BURNER FLAME HOOK-AROUND AMMETER BURNER R Y W G 10 TURNS MANIFOLD FROM UNIT 24-V CONTROL TERMINALS A89020 Fig. 18—Burner Flame EXAMPLE: 5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS c. Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. A96316 Fig. 19—Amp Draw Check With Ammeter CHECK SAFETY CONTROLS — The flame sensor, gas valve, and pressure switch were all checked in the Start-Up Procedures section as part of normal operation. Disconnect the electrical power before changing the speed tap. A failure to follow this warning can cause personal injury. 1. Check primary limit control. This control shuts off the combustion control system and energizes the circulating-air blower motor if the furnace overheats. d. To change blower motor speed selections for heating mode, remove blower motor lead from control HEAT terminal. (See Fig. 15.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 9 for lead color identification. Reconnect original lead on SPARE terminal. The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes. As soon as the limit has shut off the burners, the return-air opening should be unblocked. By using this method to check the limit control, it can be established that the limit is functioning properly and operates if there is a motor failure. Table 9—Speed Selector COLOR SPEED Black Yellow (When present) Blue Red White High FACTORYATTACHED TO COOL Medium-High SPARE Medium-Low Low Common HEAT FAN L2 = 0.5 AMPS FOR THERMOSTAT ANTICIPATOR SETTING 2. Check blocked vent safeguard switch. The purpose of this control is to permit the safe shutdown of the furnace during certain blocked vent conditions. a. Disconnect power to furnace and remove vent connector from furnace outlet collar. Be sure to allow time for vent pipe to cool down before removing. 20 b. Restore power to furnace and set room thermostat above room temperature. status code 31. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately. Determine reason pressure switch did not function properly and correct condition. c. After normal start-up, allow furnace to operate for 2 minutes, then block flue outlet 100 percent. Furnace should cycle off within 2 minutes. e. Turn off 115-v power to furnace. d. Remove blockage and reconnect vent pipe to furnace outlet collar. f. Reconnect inducer motor wires, replace control door, and turn on 115-v power. e. Wait 5 minutes and then reset blocked vent safeguard switch. CHECKLIST 1. Put away tools, instruments, and clean up debris. 3. Check pressure switch. This control proves operation of draft inducer blower. 2. Verify manual reset switches have continuity. a. Turn off 115-v power to furnace. 3. Ensure blower and control access doors are properly installed. b. Remove control door and disconnect inducer motor lead wires from wire harness. 4. Cycle test furnace with room thermostat. 5. Check operation of accessories per manufacturer’s instructions. c. Turn on 115-v power to furnace. d. Set thermostat to "call for heat" and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a 6. Review User’s Manual with owner. 7. Leave literature packet near furnace. 21 CHECKLIST—INSTALLATION LOAD CALCULATION ____________ Heating Load (Btuh) ____________ Cooling Load (Btuh) ____________ Furnace Model Selection ____________ AIR FOR COMBUSTION AND VENTILATION Unconfined Space ____________ Confined Space VENTING ____________ NFGC (United States) ____________ NSCNGPIC (Canada) ____________ Local Codes ____________ 1/4-in. Upward Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST—START-UP ____________ Gas Input Rate (Set Within 2 percent of Rating Plate) ____________ Temperature Rise Adjusted ____________ Thermostat Anticipator Setting Adjusted or ____________ Thermostat Cycle Rate (3 cycles per Hr) CHECK SAFETY CONTROLS OPERATION ____________ Primary Limit ____________ Pressure Switches ____________ Draft Safeguard Switch 22 23 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training A94328 Copyright 2000 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58wav9si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 535-757 Printed in U.S.A. Form 58WAV-9SI Pg 24 1-00 Replaces: New Tab 6a 8a
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes XMP Toolkit : 3.1-701 Create Date : 2000:02:15 14:58:50Z Modify Date : 2005:11:14 11:09:21-05:00 Metadata Date : 2005:11:14 11:09:21-05:00 Producer : Acrobat Distiller 2.0 for Windows Keywords : Format : application/pdf Title : Description : Creator : Carrier Corporation Subject : Document ID : uuid:c6e36c3d-7195-4414-aef5-24880f318954 Instance ID : uuid:118a0e30-d93b-43e5-a064-98a34a690b2e Page Count : 24 Author : Carrier CorporationEXIF Metadata provided by EXIF.tools