Carrier Weathermaster 48 50Z030 105 Users Manual 48_50z 5t
WEATHERMASTER 48ZT 48_50z-5t
4850Z030-105 to the manual 4782251c-06fc-4ab9-9284-ac84b4e092ae
2015-01-24
: Carrier Carrier-Weathermaster-48-50Z030-105-Users-Manual-310461 carrier-weathermaster-48-50z030-105-users-manual-310461 carrier pdf
Open the PDF directly: View PDF .
Page Count: 180
Download | |
Open PDF In Browser | View PDF |
WEATHERMASTER® 48/50Z030-105 Single Package Large Rooftop Units with COMFORTLINK™ Version 4.X Controls Controls, Start-Up, Operation, Service and Troubleshooting Page CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 2 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3,4 Conventions Used in this Manual . . . . . . . . . . . . . . . . 3 BASIC CONTROL USAGE . . . . . . . . . . . . . . . . . . . . . . 4-7 ComfortLink Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Scrolling Marquee. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Accessory Navigator™ Display . . . . . . . . . . . . . . . . . . 4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 System Pilot™ Interface. . . . . . . . . . . . . . . . . . . . . . . . . . 5 CCN Tables and Display. . . . . . . . . . . . . . . . . . . . . . . . . . 5 • GENERIC STATUS DISPLAY TABLE START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-32 Unit Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Unit Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Accessory Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Crankcase Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Evaporator Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 CONTROLS QUICK START . . . . . . . . . . . . . . . . . . . 33-36 Two-Stage Constant Volume Units with Mechanical Thermostat . . . . . . . . . . . . . . . . . . . . . . . 33 Two-Stage Constant Volume Units with Space Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Variable Air Volume Units Using Return Air Sensor or Space Temperature Sensor. . . . . . . . . 33 Multi-Stage Constant Volume Units with Mechanical Thermostat . . . . . . . . . . . . . . . . . . . . . . . 33 Multi-Stage Constant Volume Units with Space Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Indoor Air Quality Options . . . . . . . . . . . . . . . . . . . . . . 34 Exhaust Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Set Clock on VFD (if installed). . . . . . . . . . . . . . . . . . . 35 Programming Operating Schedules . . . . . . . . . . . . . 36 SERVICE TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-38 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Service Test Mode Logic . . . . . . . . . . . . . . . . . . . . . . . . 38 Independent Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 THIRD PARTY CONTROL . . . . . . . . . . . . . . . . . . . . . 39, 40 Thermostat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Alarm Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Remote Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 VFD Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Supply Air Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Demand Limit Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Economizer/Outdoor Air Damper Control . . . . . . . 39 CONTROLS OPERATION . . . . . . . . . . . . . . . . . . . . . 40-83 Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 • SYSTEM MODES • HVAC MODES Unit Configuration Submenu . . . . . . . . . . . . . . . . . . . . 42 Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 • SETTING UP THE SYSTEM • MACHINE DEPENDENT CONFIGURATIONS • SET POINTS • SUPPLY AIR RESET CONFIGURATION • COOLING CONFIGURATION • COOL MODE SELECTION PROCESS • COOL MODE DIAGNOSTIC HELP • SUMZ COOLING ALGORITM • DEMAND LIMIT CONTROL • HEAD PRESSURE CONTROL • ECONOMIZER INTEGRATION WITH MECHANICAL COOLING Heating Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 • SETTING UP THE SYSTEM • HEAT MODE SELECTION PROCESS • TEMPERATURE DRIVEN HEAT MODE EVALUATION • HEAT MODE DIAGNOSTIC HELP • TWO-STAGE GAS AND ELECTRIC HEAT CONTROL • HYDRONIC HEATING CONTROL • STAGED GAS HEATING CONTROL • INTEGRATED GAS CONTROL BOARD LOGIC • RELOCATE SAT FOR HEATING-LINKAGE SYSTEM • TEMPERING MODE Static Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . 61 • OPERATION • SETTING UP THE SYSTEM • STATIC PRESSURE RESET • RELATED POINTS Fan Status Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . 64 • GENERAL • SETTING UP THE SYSTEM • SUPPLY FAN STATUS MONITORING LOGIC Dirty Filter Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 • SETTING UP THE SYSTEM • ECONOMIZER OPERATION • ECONOMIZER CHANGEOVER SELECT • UNOCCUPIED ECONOMIZER FREE COOLING • OUTDOOR AIR CFM CONTROL • ECONOMIZER OPERATION CONFIGURATION • ECONOMIZER DIAGNOSTIC HELP Building Pressure Control. . . . . . . . . . . . . . . . . . . . . . . 69 • BUILDING PRESSURE CONFIGURATION • BUILDING PRESSURE CONTROL OPERATION • CONFIGURING THE BUILDING PRESSURE ACTUATORS TO COMMUNICATE VIA ACTUATOR SERIAL NUMBER • CONTROL ANGLE ALARM CONFIGURATION Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480039-01 Printed in U.S.A. Form 48/50Z-5T Pg 1 7-08 Replaces: 48/50Z-4T Page CONTENTS (cont) Control Circuit, 115 V. . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Control Circuit, 24 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Gas Heat (48Z Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Compressor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . 132 Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . 132 APPENDIX A — LOCAL DISPLAY TABLES. . 133-141 APPENDIX B — CCN TABLES . . . . . . . . . . . . . . 142-156 APPENDIX C — UNIT STAGING TABLES. . . . 156-159 APPENDIX D — VFD INFORMATION . . . . . . . . 160-168 APPENDIX E — MODE SELECTION PROCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169, 170 INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171 CONTROLS SET POINT AND CONFIGURATION LOG . . . . . . . . . . . . . . . .CL-1 - CL-6 UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . .CL-7 Page Smoke Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 • FIRE SMOKE INPUTS • AIRFLOW CONTROL DURING THE FIRE/SMOKE MODES • RELEVANT ITEMS Indoor Air Quality Control . . . . . . . . . . . . . . . . . . . . . . . 73 • OPERATION • SETTING UP THE SYSTEM • PRE-OCCUPANCY PURGE • OPTIONAL AIRFLOW STATION Humidification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 • SETTING UP THE SYSTEM • OPERATION • CONFIGURING THE HUMIDIFIER ACTUATOR Dehumidification and Reheat . . . . . . . . . . . . . . . . . . . . 77 • SETTING UP THE SYSTEM • OPERATION Temperature Compensated Start . . . . . . . . . . . . . . . . 78 • SETTING UP THE SYSTEM • TEMPERATURE COMPENSATED START LOGIC Carrier Comfort Network® (CCN). . . . . . . . . . . . . . . . . 79 Alert Limit Configuration . . . . . . . . . . . . . . . . . . . . . . . . 80 Sensor Trim Configuration . . . . . . . . . . . . . . . . . . . . . . 81 Discrete Switch Logic Configuration . . . . . . . . . . . . 81 Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Remote Control Switch Input . . . . . . . . . . . . . . . . . . . . 83 Hot Gas Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Space Temperature Offset . . . . . . . . . . . . . . . . . . . . . . . 83 TIME CLOCK CONFIGURATION . . . . . . . . . . . . . . 84, 85 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . 85-102 Complete Unit Stoppage . . . . . . . . . . . . . . . . . . . . . . . . 85 Single Circuit Stoppage . . . . . . . . . . . . . . . . . . . . . . . . . 85 Service Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Thermistor Troubleshooting . . . . . . . . . . . . . . . . . . . . . 85 Transducer Troubleshooting. . . . . . . . . . . . . . . . . . . . . 86 Forcing Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . 90 Run Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 • AUTO VIEW OF RUN STATUS • ECONOMIZER RUN STATUS • COOLING INFORMATION • MODE TRIP HELPER • CCN/LINKAGE DISPLAY TABLE • COMPRESSOR RUN HOURS DISPLAY TABLE • COMPRESSOR STARTS DISPLAY TABLE • SOFTWARE VERSION NUMBERS DISPLAY TABLE Alarms and Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 MAJOR SYSTEM COMPONENTS . . . . . . . . . . . 102-124 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Factory-Installed Components . . . . . . . . . . . . . . . . . 102 Accessory Control Components. . . . . . . . . . . . . . . . 122 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125-132 Service Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Refrigerant Feed Components. . . . . . . . . . . . . . . . . . 130 Thermostatic Expansion Valve (TXV) . . . . . . . . . . . 130 Refrigeration Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Oil Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Gas System Adjustment (48Z Only). . . . . . . . . . . . . 131 Moisture/Liquid Indicator. . . . . . . . . . . . . . . . . . . . . . . 131 Filter Drier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Liquid Line Service Valve. . . . . . . . . . . . . . . . . . . . . . . 131 Compressor Discharge Service Valve . . . . . . . . . . 131 Compressor Suction Service Valve . . . . . . . . . . . . . 131 Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of replacing filters. Trained service personnel should perform all other operations. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. WARNING Before performing service or maintenance operation on unit turn off and lock off main power switch to unit. Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. The unit may have an internal non-fused disconnect or a field-installed disconnect. CAUTION This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components. WARNING 1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details. 2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. What to do if you smell gas: 1. DO NOT try to light any appliance. 2. DO NOT touch any electrical switch, or use any phone in your building. 3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. 4. If you cannot reach your gas supplier call the fire department. 2 The 48/50Z units contain the factory-installed ComfortLink control system which provides full system management. The main base board (MBB) stores hundreds of unit configuration settings and 8 time of day schedules. The MBB also performs self diagnostic tests at unit start-up, monitors the operation of the unit, and provides alarms and alert information. The system also contains other optional boards that are connected to the MBB through the Local Equipment Network (LEN). Information on system operation and status are sent to the MBB processor by various sensors and optional board that are located at the unit and in the conditioned space. Access to the unit controls for configuration, set point selection, schedule creation, and service can be done through a unit-mounted scrolling marquee. Access can also be done through the Carrier Comfort Network® using ComfortVIEW™ software, Network Service Tool, or the accessory Navigator™ device. The ComfortLink system controls all aspects of the rooftop. It controls the supply-fan motor, compressors, and economizers to maintain the proper temperature conditions. The controls also cycle condenser fans to maintain suitable head pressure. All VAV units can be equipped with optional IGV (inlet guide vanes) or VFD (variable frequency drive) for supply duct pressure control. The ComfortLink™ controls can directly control the speed of the VFD based on a static pressure sensor input. In addition the ComfortLink controls can adjust (but not control on CV and non-modulating power exhaust units) the building pressure using multiple power exhaust fans controlled from damper position or from a building pressure sensor. The control safeties are continuously monitored to prevent the unit from operating under abnormal conditions. Sensors include suction pressure transducers and saturated discharge pressure transducers which allow for display of the unit’s operational pressures. A scheduling function, programmed by the user, controls the unit occupied/unoccupied schedule. Up to 8 different schedules can be programmed. The controls also allow the service person to operate a quick test so that all the controlled components can be checked for proper operation. GENERAL This book contains Start-Up, Controls, Operation, Troubleshooting and Service information for the 48/50Z Series rooftop units. See Table 1. These units are equipped with ComfortLink™ controls version 4.X or higher. Use this guide in conjunction with the separate installation instructions packaged with the unit. Refer to the Wiring Diagrams literature for more detailed wiring information. The 48/50Z Series units provide ventilation, cooling, and heating (when equipped) in variable air volume (VAV) and constant volume (CV) applications. Table 1 — Z Series Product Line UNIT SIZE 48ZG All 48ZN All 50ZG All 50ZN All 50Z2 All 50Z3 All 48ZT 075-105 48ZW 075-105 50ZT 075-105 50ZW 075-105 50ZX 075-105 50ZZ 075-105 48Z6 075-105 48Z8 075-105 50Z6 075-105 50Z7 075-105 50Z8 075-105 50Z9 075-105 APPLICATION Gas Heat, Vertical Supply CV 2-Stage Gas Heat, Vertical Supply VAV and CV Multi Vertical Supply, Optional Electric Heat CV 2-Stage Vertical Supply, Optional Electric Heat VAV and CV Multi Horizontal Supply CV 2-Stage Horizontal Supply VAV and CV Multi Gas Heat, Vertical Supply High-Capacity Power Exhaust CV 2-Stage Gas Heat, Vertical Supply High-Capacity Power Exhaust VAV and CV Multi Vertical Supply, Optional Electric Heat High-Capacity Power Exhaust CV 2-Stage Vertical Supply, Optional Electric Heat High-Capacity Power Exhaust VAV and CV Multi Horizontal Supply, Optional Electric Heat High-Capacity Power Exhaust CV 2-Stage Horizontal Supply, Optional Electric Heat High-Capacity Power Exhaust VAV and CV Multi Gas Heat, Vertical Supply Return/Exhaust Fan CV 2-Stage Gas Heat, Vertical Supply Return/Exhaust Fan VAV and CV Multi Vertical Supply, Optional Electric Heat Return/Exhaust Fan CV 2-Stage Horizontal Supply, Vertical Return Optional Electric Heat Return/Exhaust Fan CV 2-Stage Vertical Supply, Optional Electric Heat Return/Exhaust Fan VAV and CV Multi Horizontal Supply, Vertical Return Optional Electric Heat Return/Exhaust Fan VAV and CV Multi Conventions Used in This Manual — The following conventions for discussing configuration points for the local display (scrolling marquee or Navigator™ accessory) will be used in this manual. Point names will be written with the Mode name first, then any submodes, then the point name, each separated by an arrow symbol (→). Names will also be shown in bold and italics. As an example, the IAQ Economizer Override Position which is located in the Configuration mode, Indoor Air Quality Configuration sub-mode, and the Air Quality Set Points sub-sub-mode, would be written as Configuration→ IAQ→IAQ.SP→IQ.O.P. This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and submodes using the UP ARROW and DOWN ARROW keys. The arrow symbol in the path name represents pressing ENTER to move into the next level of the menu structure. When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, Configuration→IAQ→AQ.CF→IQ.AC = 1 (IAQ Analog Input). Pressing the ESCAPE and ENTER keys simultaneously will scroll an expanded text description of the point name across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text. The CCN point names are also referenced in the local display tables for users configuring the unit with CCN software LEGEND CV 2-Stage CV Multi VAV — Constant Volume, 2-Stage — Constant Volume, Multiple Adaptive Demand — Variable Air Volume 3 instead of the local display. The CCN tables are located in Appendix B of this manual. MODE Run Status BASIC CONTROL USAGE Service Test Temperature Pressures ComfortLink™ Controls — The ComfortLink controls are a comprehensive unit-management system. The control system is easy to access, configure, diagnose and troubleshoot. The controls are flexible, providing two types of constant volume cooling control sequences, two variable air volume cooling control sequences, and heating control sequences for two-stage electric and gas systems, for multiple-stage gas heating, and hydronic heat in both Occupied and Unoccupied schedule modes. This control also manages: • VAV duct pressure (through optional VFD or inlet guide vanes), with reset • Building pressure through four different power exhaust systems • Return fan applications using fan tracking • Condenser fan cycling for low ambient head pressure control • Dehumidification (with reheat) and humidifier sequences • Space ventilation control, in Occupied and Unoccupied periods, using CO2 sensors or external signals, with ventilation defined by damper position or ventilation airflow measurement • Smoke control functions • Occupancy schedules • Occupancy or start/stop sequences based on third party signals • Alarm status and history and run time data • Management of a complete unit service test sequence System diagnostics are enhanced by the use of multiple external sensors for air temperatures, air pressures and refrigerant pressures. Unit-mounted actuators provide digital feedback data to the unit control. The ComfortLink™ controller is fully communicating and cable-ready for connection to the Carrier Comfort Network® (CCN) building management system. The control provides high-speed communications for remote monitoring via the Internet. Multiple 48/50Z Series units can be linked together (and to other ComfortLink controller equipped units) using a 3-wire communication bus. The ComfortLink control system is easy to access through the use of a unit-mounted display module. There is no need to bring a separate computer to this unit for start-up. Access to control menus is simplified by the ability to quickly select from 11 menus. A scrolling readout provides detailed explanations of control information. Only four, large, easy-to-use buttons are required to maneuver through the entire controls menu. The display readout is designed to be visible even in bright sunlight. For added service flexibility, an accessory hand-held Navigator™ module is also available. This portable device has an extended communication cable that can be plugged into the unit’s communication network either at the main control box or at the opposite end of the unit, at a remote modular plug. The Navigator display provides the same menu structure, control access and display data as is available at the unit-mounted scrolling marquee display. Setpoints Inputs Alarm Status Outputs Configuration Time Clock ESCAPE ENTER Operating Modes Alarms Fig. 1 — Scrolling Marquee 4 buttons and a group of 11 LEDs that indicate the following menu structures: • Run Status • Service Test • Temperatures • Pressures • Set points • Inputs • Outputs • Configuration • Timeclock • Operating Modes • Alarms Through the scrolling marquee, the user can access all of the inputs and outputs to check on their values and status, configure operating parameters plus evaluate the current decision status for operating modes. Because the 48/50Z Series units are equipped with suction pressure and discharge pressure transducers, the scrolling marquee can also display refrigerant circuit pressures typically obtained from service gages. The control also includes an alarm history which can be accessed from the display. In addition, through the scrolling marquee, the user can access a built-in test routine that can be used at start-up commissioning and to diagnose operational problems with the unit. Accessory Navigator™ Display — The accessory hand-held Navigator display can be used with the 48/50Z Series units. See Fig. 2. The Navigator display operates the same way as the scrolling marquee device. The Navigator display is plugged into the RJ-11 jack in the main control box on the COMM board. The Navigator display can also be plugged into the RJ-11 jack located on the unit corner post located at the economizer end of the unit. Co m NA T IM E EWT LW T SETP MO fort VIG Li n k ATO R 12. 54. 58 44. 6 F 4 4 . 01 F F DE Run Statu s Servi ce Te st Temp eratur es Pres sures Setpo ints Inputs Al ar m St atu s Outpu ts Confi gurat ion Time Cloc k Opera ting Mode s ESC Alarm s Scrolling Marquee — This device is the keypad inter- ENT face used to access the control information, read sensor values, and test the unit. The scrolling marquee is located in the main control box and is standard on all units. The scrolling marquee display is a 4-key, 4-character, 16-segment LED (light-emitting diode) display module. The display also contains an Alarm Status LED. See Fig. 1. The display is easy to operate using ER Fig. 2 — Accessory Navigator Display 4 with the ENTER key and then pressing the arrow keys simultaneously. Operation — All units are shipped from the factory with the scrolling marquee display, which is located in the main control box. See Fig. 1. In addition, the ComfortLink™ controls also supports the use of the handheld Navigator™ display. Both displays provide the user with an interface to the ComfortLink control system. The displays have and arrow keys, an ESCAPE key and an ENTER key. These keys are used to navigate through the different levels of the display structure. The Navigator and the scrolling marquee operate in the same manner, except that the Navigator display has multiple lines of display and the scrolling marquee has a single line. All further discussions and examples in this document will be based on the scrolling marquee display. See Table 2 for the menu structure. and Depending on the unit model, factory-installed options and field-installed accessories, some of the items in the various mode categories may not apply. System Pilot™ Interface — The System Pilot interface (33PILOT-01) is a component of the 3V™ system and serves as a user-interface and configuration tool for all Carrier communicating devices. The System Pilot interface can be used to install and commission a 3V zoning system, linkage compatible air source, universal controller, and all other devices operating on the Carrier communicating network. Additionally, the System Pilot interface can serve as a wallmounted temperature sensor for space temperature measurement. The occupant can use the System Pilot interface to change set points. A security feature is provided to limit access of features for unauthorized users. See Fig. 3 for System Pilot interface details. The four keys are used to navigate through the display structure, which is organized in a tiered mode structure. If the buttons have not been used for a period, the display will default to the AUTO VIEW display category as shown under the RUN STATUS category. To show the top-level display, press the ESCAPE key until a blank display is shown. Then use the and arrow keys to scroll through the top-level categories. These are listed in Appendix A and will be indicated on the scrolling marquee by the LED next to each mode listed on the face of the display. CCN Tables and Display — In addition to the unit- mounted scrolling marquee display, the user can also access the same information through the CCN tables by using the Service Tool or other CCN programs. Details on the CCN tables are summarized in Appendix B. The variable names used for the CCN tables and the scrolling marquee tables may be different and more items are displayed in the CCN tables. As a reference, the CCN variable names are included in the scrolling marquee tables and the scrolling marquee names are included in the CCN tables in Appendix B. GENERIC STATUS DISPLAY TABLE — The GENERICS points table allows the service/installer the ability to create a custom table in which up to 20 points from the 5 CCN categories (Points, Config, Service-Config, Set Point, and Maintenance) may be collected and displayed. In the Service-Config table section, there is a table named “generics”. This table contains placeholders for up to 20 CCN point names and allows the user to decide which points are displayed in the GENERIC points table. Each one of these placeholders allows the input of an 8-character ASCII string. Go into the Edit mode for the Service-Config table “generics” and enter the CCN name for each point to be displayed in the custom points table in the order they will be displayed. When done entering point names, download the table to the rooftop unit control. When a specific mode or sub-mode is located, push the ENTER key to enter the mode. Depending on the mode, there may be additional tiers. Continue to use the and keys and the ENTER keys until the desired display item is found. At any time, the user can move back a mode level by pressing the ESCAPE key. Once an item has been selected the display will flash showing the item, followed by the item value and then followed by the item units (if any). Items in the Configuration and Service Test modes are password protected. The display will flash PASS and WORD when required. Use the ENTER and arrow keys to enter the four digits of the password. The default password is 1111. Pressing the ESCAPE and ENTER keys simultaneously will scroll an expanded text description across the display indicating the full meaning of each display point. Pressing the ESCAPE and ENTER keys when the display is blank (MODE LED level) will return the display to its default menu of rotating AUTO VIEW display items. In addition, the password will need to be entered again before changes can be made. Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. If the display is in rotating auto-view, press the ENTER key to stop the display at the desired item. Press the ENTER key again so that the item value flashes. Use the arrow keys to change the value of state of an item and press the ENTER key to accept it. Press the ESCAPE key and the item, value or units display will resume. Repeat the process as required for other items. MODIFY/ SELECT NAVIGATE/ EXIT If the user needs to force a variable, follow the same process as when editing a configuration parameter. A forced variable will be displayed with a blinking “f” following its value. For example, if supply fan requested (FAN.F) is forced, the display shows “YESf”, where the “f” is blinking to signify a force on the point. Remove the force by selecting the point that is forced SCROLL + PAGE - Fig. 3 — System Pilot User Interface 5 Table 2 — Scrolling Marquee Menu Display Structure RUN STATUS Auto View of Run Status (VIEW) SERVICE TEST Service Test Mode (TEST) Econ Run Status (ECON) Software Command Disable (STOP) ↓ ↓ Cooling Information (COOL) ↓ ↓ ↓ Soft Stop Request (S.STP) ↓ TEMPERATURES PRESSURES SETPOINTS INPUTS OUTPUTS CONFIGURATION Air Temperatures (AIR.T) Air Pressures (AIR.P) Occupied Heat Setpoint (OHSP) General Inputs (GEN.I) Fans (FANS) Unit Configuration (UNIT) Compressor Feedback (FD.BK) Cooling (COOL) ↓ Refrigerant Temperatures (REF.T) ↓ Refrigerant Pressures (REF.P) Occupied Cool Setpoint (OCSP) Unoccupied Heat Setpoint (UHSP) Unoccupied Cool Setpoint (UCSP) CCN Linkage (LINK) Test Independent Outputs (INDP) Heat - Cool Setpoint (GAP) ↓ Compressor Run Hours (HRS) ↓ Compressor Starts (STRT) ↓ Software Version Numbers (VERS) ↓ Test Fans (FANS) ↓ Calibrate Test Actuators (ACT.C) ↓ Test Cooling (COOL) ↓ Test Heating (HEAT) Thermostat Inputs (STAT) ↓ ↓ Supply Fan Request (FAN.F) ↓ ↓ ↓ Mode Trip Helper (TRIP) ↓ ↓ ↓ Fire-Smoke Modes (FIRE) ↓ ↓ Relative Humidity (REL.H) ↓ ↓ VAV Occ Cool On (V.C.ON) Air Quality Sensors (AIR.Q) ↓ ↓ VAV Occ Cool Off (V.C.OF) ↓ Supply Air Setpoint (SASP) ↓ CFM Sensors (CFM) ↓ Reset Inputs (RSET) ↓ 4-20 Milliamp Inputs (4-20) ↓ ↓ Heating (HEAT) Actuators (ACTU) ↓ General Outputs (GEN.O) ↓ Cooling Configuration (COOL) ↓ Evap/Discharge Temp. Reset (EDT.R) ↓ ↓ Economizer Configuration (ECON) ↓ Building Press. Configs (BP) ↓ Cool/Heat Setpt. Offsets (D.L.V.T) ↓ Indoor Air Quality Cfg. (IAQ) Heating Supply Air Setpoint (SA.HT) Humidity Configuration (HUMD) Tempering Purge SASP (T.PRG) Dehumidification Config. (DEHU) Tempering in Cool SASP (T.CL) CCN Configuration (CCN) Tempering in Vent Occ SASP (T.V.OC) Alert Limit Config. (ALLM) Tempering in Vent Unocc. SASP (T.V.UN) Sensor Trim Config. (TRIM) ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓ ↓ Switch Logic (SW.LG) ↓ Display Configuration (DISP) 6 Control Type (CTRL) ↓ Daylight Savings Time (DAY.S) Supply Air Setpoint Lo (SA.LO) ↓ Local Time Schedule (SCH.L) ↓ Supply Static Press. Config. (SP) ↓ ↓ HVAC Mode (HVAC) Heating Configuration (HEAT) Demand Limit Config. (DMD.L) ↓ ↓ OPERATING MODES System Mode (SYS.M) Month, Date, Day and Year (DATE) Local Holiday Schedules (HOL.L) Supply Air Setpoint Hi (SA.HI) ↓ TIME CLOCK Time of Day (TIME) ↓ ↓ ↓ Mode Controlling Unit (MODE) ALARMS Currently Active Alarms (CURR) ↓ Reset All Current Alarms (R.CUR) ↓ Alarm History (HIST) direction. See Tables 26-28 for motor limitations. See Table 29 for air quantity limits. Static pressure drop is shown in Tables 30A-30C. FIELD-SUPPLIED FAN DRIVES — Supply fan and power exhaust fan drives are fixed-pitch, non-adjustable selections, for maximum reliability and long belt life. If the factory drive sets must be changed to obtain other fan speeds, consult the nearest Browning Manufacturing Co. sales office with the required new wheel speed and the data from Physical Data and Supply Fan Drive Data tables (center distances, motor and fan shaft diameters, motor horsepower) in Installation Instructions for a modified drive set selection. For minor speed changes, the fan sheave size should be changed. (Do not reduce the size of the motor sheave; this will result in reduced belt horsepower ratings and reduced belt life.) See page 128 for belt installation procedure. IMPORTANT: The computer system software (ComfortVIEW™, Service Tool, etc.) that is used to interact with CCN controls always saves a template of items it considers as static (e.g., limits, units, forcibility, 24-character text strings, and point names) after the software uploads the tables from a control. Thereafter, the software is only concerned with run time data like value and hardware/force status. With this in mind, it is important that anytime a change is made to the Service-Config table “generics” (which in turn changes the points contained in the GENERIC point table), that a complete new upload be performed. This requires that any previous table database be completely removed first. Failure to do this will not allow the user to display the new points that have been created and the software will have a different table database than the unit control. Controls — Use the following steps for the controls: 1. Set any control configurations that are required (fieldinstalled accessories, etc.). The unit is factory configured for all appropriate factory-installed options. 2. Enter unit set points. The unit is shipped with the set point default values. If a different set point is required, use the scrolling marquee, Navigator display, ComfortVIEW™ software or Service Tool to change the configuration values. 3. If the internal time schedules are going to be used, configure the Occupancy schedule. 4. Verify that the control time periods programmed meet current requirements. 5. Start unit using Service Test mode to verify operation of all major components. 6. If the unit is a VAV unit make sure to configure the static pressure set point. To check out the VFD, use the VFD instructions shipped with the unit. START-UP IMPORTANT: Do not attempt to start unit, even momentarily, until all items on the Start-Up Checklist (in installation instructions) and the following steps have been completed. Unit Preparation — Check that unit has been installed in accordance with the installation instructions and applicable codes. Unit Setup — Make sure that the economizer hood has been installed and that the outdoor filters are properly installed. Internal Wiring — Ensure that all electrical connections in the control box are tightened as required. If the unit has staged gas heat make sure that the LAT sensors have been routed to the supply ducts as required. Gas Heat — Verify gas pressure before turning on gas heat as follows: 1. Turn off field-supplied manual gas stop, located external to the unit. 2. Connect pressure gages to supply gas tap, located at fieldsupplied manual shutoff valves. 3. Connect pressure gages to manifold pressure tap on unit gas valve. 4. Supply gas pressure must not exceed 13.5 in. wg. Check pressure at field-supplied shut-off valve. 5. Turn on manual gas stop and initiate a heating demand. Jumper R to W1 in the control box to initiate heat. 6. Use the Service Test procedure to verify heat operation. 7. After the unit has run for several minutes, verify that incoming pressure is 5.0 in. wg or greater and that the manifold pressure is 3.5 in wg. If manifold pressure must be adjusted refer to Gas Valve Adjustment section. Accessory Installation — Check to make sure that all accessories including space thermostats and sensors have been installed and wired as required by the instructions and unit wiring diagrams. Crankcase Heaters — Crankcase heaters are energized as long as there is power to the unit, except when the compressors are running. IMPORTANT: Unit power must be on for 24 hours prior to start-up of compressors. Otherwise damage to compressors may result. Evaporator Fan — Fan belt and fixed pulleys are factoryinstalled. See Tables 3-25 for fan performance. Remove tape from fan pulley, and be sure that fans rotate in the proper 7 Table 3 — Fan Performance — 48ZG,ZN030 and 50ZG,ZN030 Units Without Discharge Plenum* AIRFLOW (Cfm) 6,000 7,500 9,000 10,500 12,000 13,500 15,000 0.2 Rpm Bhp 222 0.59 248 0.94 278 1.46 311 2.16 344 3.08 379 4.25 415 5.69 0.4 Rpm Bhp 284 0.91 300 1.28 323 1.80 349 2.52 378 3.44 410 4.62 442 6.06 AIRFLOW (Cfm) 1.8 2.0 6,000 7,500 9,000 10,500 12,000 13,500 15,000 AIRFLOW (Cfm) 6,000 7,500 9,000 10,500 12,000 13,500 15,000 Rpm 567 575 581 588 598 610 626 Bhp 3.84 4.57 5.38 6.31 7.41 8.71 10.25 Rpm 595 604 611 617 625 637 651 Bhp 4.30 5.10 5.97 6.95 8.08 9.41 10.98 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 339 1.27 388 1.66 430 2.07 469 2.50 350 1.68 395 2.11 437 2.57 475 3.05 366 2.22 407 2.69 446 3.19 483 3.71 387 2.95 424 3.43 459 3.96 493 4.51 412 3.89 445 4.39 477 4.93 508 5.51 440 5.07 469 5.58 498 6.13 527 6.73 470 6.52 496 7.04 523 7.61 549 8.22 1.4 Rpm Bhp 504 2.93 511 3.54 517 4.25 526 5.10 539 6.12 555 7.36 575 8.87 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 622 4.78 647 5.26 671 5.75 695 6.25 632 5.63 658 6.18 683 6.73 707 7.29 639 6.56 665 7.16 691 7.78 715 8.40 645 7.59 672 8.25 697 8.92 722 9.59 652 8.77 679 9.47 704 10.19 728 10.91 662 10.14 687 10.88 712 11.63 736 12.40 675 11.74 699 12.51 723 13.30 746 14.10 Rpm 717 730 739 746 752 759 768 1.6 Rpm Bhp 536 3.38 544 4.05 550 4.81 558 5.70 569 6.75 583 8.02 601 9.55 3.0 Bhp 6.76 7.86 9.03 10.28 11.65 13.18 14.92 3.2 Rpm 738 752 761 769 775 782 790 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 759 7.79 779 8.32 799 8.85 817 9.39 773 9.01 794 9.60 814 10.20 833 10.80 783 10.30 805 10.95 825 11.60 845 12.26 791 11.67 812 12.38 833 13.09 854 13.81 797 13.15 819 13.91 840 14.68 860 15.45 804 14.77 825 15.59 846 16.41 867 17.23 812 16.59 833 17.45 853 18.31 874 19.19 LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30A on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 8 Bhp 7.27 8.43 9.66 10.97 12.39 13.98 15.75 Table 4 — Fan Performance — 48ZG,ZN035 and 50ZG,ZN035 Units Without Discharge Plenum* AIRFLOW (Cfm) 7,000 8,000 10,000 12,000 14,000 15,000 0.2 Rpm Bhp 246 0.84 266 1.14 310 1.98 357 3.20 406 4.87 430 5.89 0.4 Rpm Bhp 301 1.19 315 1.50 350 2.36 390 3.60 435 5.28 458 6.31 AIRFLOW (Cfm) 1.8 2.0 7,000 8,000 10,000 12,000 14,000 15,000 AIRFLOW (Cfm) 7,000 8,000 10,000 12,000 14,000 15,000 Rpm 577 583 594 609 629 641 Bhp 4.40 4.94 6.16 7.67 9.57 10.69 Rpm 606 612 623 636 655 666 Bhp 4.91 5.49 6.79 8.36 10.30 11.44 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 352 1.58 398 2.01 440 2.46 479 2.93 362 1.92 406 2.37 447 2.85 484 3.35 389 2.80 427 3.30 464 3.83 499 4.38 424 4.06 457 4.58 489 5.15 520 5.74 463 5.76 492 6.30 520 6.89 548 7.52 485 6.80 511 7.35 538 7.95 564 8.59 1.4 Rpm Bhp 514 3.40 519 3.87 532 4.96 551 6.36 576 8.18 590 9.26 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 633 5.43 659 5.95 684 6.49 707 7.03 640 6.05 666 6.62 691 7.19 715 7.78 651 7.42 677 8.07 703 8.73 727 9.39 663 9.05 689 9.77 714 10.49 738 11.22 680 11.04 704 11.81 728 12.59 751 13.38 690 12.20 714 12.99 737 13.79 760 14.61 Rpm 730 738 751 762 774 782 1.6 Rpm Bhp 547 3.90 552 4.39 564 5.55 580 7.01 603 8.86 616 9.96 3.0 Bhp 7.58 8.37 10.06 11.97 14.18 15.44 3.2 Rpm 752 760 774 785 796 804 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 773 8.70 793 9.27 813 9.85 832 10.43 782 9.57 802 10.18 823 10.80 842 11.43 796 11.42 817 12.11 838 12.81 858 13.52 807 13.48 828 14.25 849 15.02 869 15.80 818 15.82 840 16.66 860 17.50 880 18.35 825 17.13 846 18.00 866 18.87 886 19.76 LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30A on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 9 Bhp 8.14 8.97 10.74 12.72 14.99 16.28 Table 5 — Fan Performance — 48ZG,ZN040 and 50ZG,ZN040 Units Without Discharge Plenum* AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 0.2 Rpm 252 290 330 372 415 459 503 Bhp 0.98 1.67 2.65 3.96 5.67 7.84 10.51 0.4 Rpm 303 333 369 407 447 488 530 1.8 Rpm 571 579 590 607 629 656 687 Bhp 4.60 5.75 7.21 9.07 11.41 14.28 17.71 Bhp 1.33 2.11 3.18 4.61 6.44 8.72 11.51 2.0 Rpm 600 608 618 633 653 678 707 Bhp 5.14 6.36 7.87 9.78 12.16 15.09 18.60 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 350 1.72 394 2.14 434 2.58 472 3.06 373 2.55 412 3.01 448 3.51 483 4.03 404 3.70 438 4.23 470 4.78 501 5.35 439 5.22 469 5.83 498 6.44 526 7.07 476 7.15 504 7.85 530 8.54 556 9.24 515 9.55 541 10.34 565 11.12 589 11.91 555 12.46 579 13.36 602 14.24 624 15.11 Rpm 507 517 532 554 581 612 645 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 628 5.70 654 6.27 679 6.85 703 7.44 636 6.98 662 7.62 688 8.28 712 8.94 645 8.55 671 9.25 696 9.96 720 10.69 658 10.51 683 11.25 707 12.02 730 12.80 676 12.94 699 13.73 722 14.54 744 15.37 700 15.91 721 16.76 742 17.62 762 18.49 727 19.48 747 20.38 766 21.30 785 22.22 Rpm 726 736 744 753 766 783 804 1.4 Bhp 3.55 4.58 5.94 7.72 9.95 12.69 15.98 1.6 Rpm 540 549 562 581 605 634 666 3.0 Bhp 8.04 9.62 11.43 13.60 16.22 19.39 23.17 3.2 Rpm 748 758 766 775 787 803 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 770 9.27 791 9.90 811 10.54 830 11.18 780 11.00 802 11.71 822 12.43 842 13.15 789 12.96 810 13.73 831 14.52 851 15.32 797 15.24 818 16.07 839 16.93 859 17.79 808 17.95 828 18.85 849 19.75 868 20.67 823 21.21 842 22.15 862 23.11 — — — — — — — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30A on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 10 Bhp 4.07 5.16 6.56 8.38 10.67 13.47 16.84 Bhp 8.65 10.30 12.19 14.41 17.08 20.29 — Table 6 — Fan Performance — 48ZG,ZN050 and 50ZG,ZN050 Units Without Discharge Plenum* AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 0.2 Rpm 276 296 339 382 427 473 519 Bhp 1.34 1.74 2.76 4.15 5.96 8.26 11.10 0.4 Rpm 323 339 376 416 458 501 545 1.8 Rpm 579 584 597 615 639 667 699 Bhp 5.23 5.85 7.36 9.29 11.71 14.69 18.25 Bhp 1.73 2.17 3.29 4.79 6.71 9.12 12.06 2.0 Rpm 608 613 625 641 663 689 719 Bhp 5.81 6.47 8.03 10.01 12.48 15.51 19.14 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 366 2.15 407 2.60 445 3.08 482 3.58 379 2.62 418 3.09 454 3.59 489 4.12 411 3.81 445 4.35 477 4.91 509 5.49 448 5.40 478 6.01 506 6.63 535 7.26 487 7.42 514 8.11 540 8.81 565 9.52 527 9.93 552 10.72 576 11.50 600 12.29 570 12.99 593 13.88 615 14.76 637 15.63 Rpm 516 522 539 562 590 623 658 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 636 6.41 662 7.02 687 7.64 712 8.27 641 7.10 667 7.74 692 8.40 717 9.07 651 8.72 677 9.42 702 10.14 726 10.88 666 10.74 690 11.50 714 12.27 738 13.06 686 13.27 709 14.07 731 14.89 753 15.73 711 16.35 732 17.20 753 18.07 773 18.96 739 20.04 759 20.95 778 21.88 797 22.82 Rpm 735 740 750 760 775 793 816 1.4 Bhp 4.11 4.68 6.09 7.92 10.23 13.08 16.50 1.6 Rpm 549 554 568 589 615 645 679 3.0 Bhp 8.91 9.75 11.63 13.87 16.58 19.86 23.77 3.2 Rpm 757 763 772 783 796 813 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 779 10.23 800 10.90 821 11.58 840 12.27 785 11.14 806 11.85 826 12.57 846 13.30 794 13.16 816 13.94 836 14.73 857 15.54 804 15.52 825 16.37 846 17.22 866 18.10 817 18.34 837 19.24 857 20.15 877 21.08 833 21.71 853 22.66 872 23.62 — — — — — — — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30A on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 11 Bhp 4.66 5.26 6.71 8.60 10.97 13.88 17.38 Bhp 9.57 10.44 12.39 14.69 17.45 20.78 — Table 7 — Fan Performance — 48ZG,ZN055 and 50ZG,ZN055 Units Without Discharge Plenum* AIRFLOW (Cfm) 10,000 12,500 15,000 17,500 20,000 22,500 25,000 0.2 Rpm Bhp 207 1.04 235 1.69 265 2.59 295 3.78 327 5.31 359 7.23 392 9.59 AIRFLOW (Cfm) 1.8 10,000 12,500 15,000 17,500 20,000 22,500 25,000 AIRFLOW (Cfm) 10,000 12,500 15,000 17,500 20,000 22,500 25,000 Rpm 497 497 501 512 528 548 571 Bhp 7.27 7.73 8.63 10.09 12.09 14.60 17.63 0.4 Rpm 253 276 302 331 360 390 421 Bhp 1.50 2.23 3.23 4.52 6.15 8.16 10.60 2.0 Rpm 523 523 526 535 549 567 589 Bhp 8.39 8.83 9.67 11.07 13.06 15.59 18.66 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 295 2.03 334 2.66 371 3.41 405 4.26 312 2.78 346 3.40 379 4.10 410 4.88 335 3.85 365 4.51 394 5.20 422 5.96 361 5.24 389 5.97 415 6.71 440 7.48 388 6.98 414 7.79 439 8.60 462 9.43 417 9.09 442 10.00 465 10.90 487 11.81 447 11.62 470 12.64 492 13.64 513 14.63 Rpm 438 440 449 465 485 508 533 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 549 9.55 573 10.75 596 11.98 618 13.23 549 10.00 573 11.22 597 12.49 619 13.81 550 10.77 574 11.94 597 13.17 619 14.46 557 12.11 579 13.21 601 14.38 622 15.60 570 14.07 590 15.12 610 16.24 630 17.40 587 16.61 605 17.66 624 18.75 642 19.88 607 19.71 624 20.78 642 21.89 659 23.02 Rpm 639 641 641 643 649 660 676 1.4 Bhp 5.20 5.75 6.78 8.30 10.28 12.72 15.62 1.6 Rpm 468 469 476 489 507 528 552 3.0 Bhp 14.51 15.16 15.80 16.88 18.62 21.06 24.19 3.2 Rpm 659 662 662 663 668 678 692 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 679 17.13 697 18.46 715 19.81 733 21.17 682 17.98 702 19.43 721 20.90 739 22.40 682 18.63 702 20.10 721 21.62 740 23.17 683 19.60 702 21.04 721 22.53 740 24.06 687 21.20 706 22.57 724 24.00 742 25.46 696 23.55 713 24.86 731 26.22 748 27.62 709 26.62 725 27.91 741 29.22 — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30B on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 12 Bhp 6.20 6.70 7.67 9.17 11.17 13.65 16.62 Bhp 15.81 16.55 17.19 18.21 19.89 22.28 25.39 Table 8 — Fan Performance — 48ZG,ZN060 and 50ZG,ZN060 Units Without Discharge Plenum* AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 0.2 Rpm 234 271 308 348 390 433 476 Bhp 1.54 2.65 4.22 6.36 9.19 12.80 17.29 0.4 Rpm 276 309 344 380 417 456 497 1.8 Rpm 504 509 521 543 570 601 634 Bhp 7.56 8.87 10.79 13.56 17.22 21.81 27.34 Bhp 2.03 3.27 5.00 7.29 10.24 13.93 18.50 2.0 Rpm 530 535 544 563 588 618 650 Bhp 8.57 9.95 11.85 14.60 18.28 22.93 28.56 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 312 2.57 348 3.20 382 3.93 415 4.74 341 3.88 370 4.53 399 5.24 428 6.04 374 5.73 400 6.46 426 7.22 450 8.02 408 8.18 434 9.04 457 9.88 479 10.74 444 11.29 469 12.29 491 13.27 512 14.23 481 15.14 504 16.30 526 17.44 546 18.53 519 19.82 541 21.15 562 22.45 581 23.70 Rpm 446 455 474 501 532 565 599 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 555 9.61 578 10.66 600 11.73 621 12.81 559 11.07 583 12.25 606 13.45 628 14.68 567 12.97 590 14.14 612 15.38 633 16.66 583 15.69 603 16.84 623 18.05 643 19.31 607 19.39 625 20.53 642 21.72 660 22.95 635 24.07 651 25.25 667 26.46 684 27.70 666 29.78 681 31.02 696 32.28 711 33.56 Rpm 641 650 654 662 678 700 726 1.4 Bhp 5.63 6.91 8.88 11.64 15.21 19.62 24.93 1.6 Rpm 476 482 498 522 551 583 617 3.0 Bhp 13.91 15.95 17.99 20.63 24.24 28.98 34.88 3.2 Rpm 660 670 675 682 695 715 —- AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 679 16.11 697 17.23 714 18.35 730 19.49 690 18.52 709 19.84 727 21.15 745 22.49 695 20.76 714 22.20 733 23.66 — — 701 23.41 719 24.87 738 26.38 — — 713 26.97 730 28.40 747 29.89 — — 731 31.67 747 33.08 —— — — — — — — — — — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30B on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 13 Bhp 6.58 7.85 9.81 12.58 16.20 20.71 26.14 Bhp 15.01 17.23 19.36 21.99 25.58 30.31 — Table 9 — Fan Performance — 48ZG,ZN070 and 50ZG,ZN070 Units Without Discharge Plenum* AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 0.2 Rpm 258 302 348 397 447 476 Bhp 2.23 3.92 6.36 9.74 14.18 17.29 0.4 Rpm 297 338 380 424 470 497 1.8 Rpm 507 519 543 575 612 634 Bhp 8.39 10.42 13.56 17.93 23.55 27.34 Bhp 2.80 4.67 7.29 10.80 15.35 18.50 2.0 Rpm 533 542 563 593 628 650 Bhp 9.46 11.48 14.60 18.99 24.69 28.56 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 330 3.38 362 4.02 392 4.73 422 5.53 368 5.39 395 6.10 421 6.84 446 7.64 408 8.18 434 9.04 457 9.88 479 10.74 450 11.88 475 12.91 497 13.91 517 14.89 494 16.60 516 17.82 538 19.01 558 20.16 519 19.82 541 21.15 562 22.45 581 23.70 Rpm 451 471 501 537 576 599 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 558 10.57 582 11.71 605 12.89 627 14.08 565 12.60 588 13.78 610 15.02 632 16.30 583 15.69 603 16.84 623 18.05 643 19.31 611 20.10 629 21.24 646 22.43 664 23.67 645 25.86 661 27.05 677 28.27 692 29.53 666 29.78 681 31.02 696 32.28 711 33.56 Rpm 648 653 662 681 708 726 1.4 Bhp 6.42 8.50 11.64 15.88 21.29 24.93 1.6 Rpm 480 495 522 556 594 617 3.0 Bhp 15.29 17.62 20.63 24.96 30.82 34.88 3.2 Rpm 668 674 682 698 723 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 687 17.76 706 19.01 724 20.27 741 21.54 694 20.38 713 21.79 732 23.24 — — 701 23.41 719 24.87 738 26.38 — — 715 27.67 732 29.10 749 30.58 — — 739 33.51 — — — — — — — — — — — — — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 48/50ZN units only. Bhp — Brake Horsepower Kilowatts = *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30B on page 32. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 14 Bhp 7.37 9.42 12.57 16.89 22.41 26.14 Bhp 16.52 18.99 21.99 26.29 32.15 — Table 10 — Fan Performance — 50ZG,ZN030 Units With Discharge Plenum and 50Z2,Z3030 Units AIRFLOW (Cfm) 6,000 7,500 9,000 10,500 12,000 13,500 15,000 0.2 Rpm Bhp 255 0.95 291 1.51 330 2.28 371 3.28 413 4.56 456 6.12 500 7.99 AIRFLOW (Cfm) 1.8 6,000 7,500 9,000 10,500 12,000 13,500 15,000 AIRFLOW (Cfm) 6,000 7,500 9,000 10,500 12,000 13,500 15,000 Rpm 594 605 617 633 652 676 703 Bhp 5.43 6.16 7.02 8.12 9.52 11.25 13.30 0.4 Rpm Bhp 313 1.35 340 1.93 372 2.73 408 3.76 447 5.07 487 6.66 528 8.58 2.0 Rpm 623 635 646 660 679 701 726 Bhp 6.09 6.88 7.76 8.86 10.27 12.00 14.07 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 364 1.82 411 2.35 454 2.92 494 3.52 386 2.41 428 2.94 468 3.51 505 4.13 413 3.22 451 3.76 487 4.34 522 4.96 444 4.28 479 4.84 512 5.43 544 6.06 479 5.61 510 6.19 540 6.80 570 7.44 516 7.23 544 7.83 572 8.46 599 9.12 555 9.18 581 9.80 606 10.45 631 11.13 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 651 6.75 676 7.41 701 8.08 725 8.75 664 7.62 691 8.36 716 9.11 741 9.88 674 8.52 702 9.31 728 10.11 753 10.93 687 9.64 713 10.43 739 11.25 764 12.09 704 11.04 729 11.84 753 12.66 777 13.50 725 12.78 748 13.58 771 14.40 794 15.24 749 14.86 771 15.66 793 16.49 814 17.34 1.4 Rpm 530 541 555 574 598 626 656 Rpm 747 765 777 788 800 816 835 Bhp 4.14 4.78 5.61 6.71 8.11 9.81 11.83 3.0 Bhp 9.42 10.64 11.76 12.95 14.37 16.11 18.20 1.6 Rpm 563 574 587 604 626 651 680 3.2 Rpm 769 787 800 811 823 838 856 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 789 10.77 809 11.45 829 12.13 848 12.81 809 12.18 830 12.96 851 13.73 870 14.51 823 13.44 844 14.29 866 15.15 886 16.01 833 14.71 856 15.61 877 16.52 898 17.44 845 16.16 867 17.08 888 18.01 — — 859 17.90 880 18.82 — — — — 876 20.00 896 20.92 — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 15 Bhp 4.78 5.46 6.30 7.40 8.80 10.51 12.56 Bhp 10.10 11.41 12.60 13.82 15.26 16.99 19.09 Table 11 — Fan Performance — 50ZG,ZN035 Units With Discharge Plenum and 50Z2,Z3035 Units AIRFLOW (Cfm) 7,000 8,000 10,000 12,000 14,000 15,000 0.2 Rpm Bhp 285 1.35 311 1.81 367 3.04 426 4.74 486 6.98 517 8.33 AIRFLOW (Cfm) 1.8 7,000 8,000 10,000 12,000 14,000 15,000 AIRFLOW (Cfm) 7,000 8,000 10,000 12,000 14,000 15,000 Rpm 607 615 636 663 698 718 Bhp 6.03 6.58 7.94 9.83 12.31 13.78 0.4 Rpm Bhp 337 1.78 358 2.25 406 3.52 459 5.26 515 7.55 544 8.92 2.0 Rpm 637 645 664 689 722 741 Bhp 6.74 7.32 8.70 10.59 13.08 14.56 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 384 2.26 428 2.80 469 3.38 507 4.00 402 2.75 442 3.29 481 3.87 517 4.50 443 4.05 479 4.61 512 5.21 545 5.84 491 5.82 522 6.42 552 7.05 581 7.70 543 8.15 570 8.78 597 9.44 623 10.12 570 9.54 596 10.18 621 10.85 646 11.55 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 665 7.46 691 8.18 717 8.91 741 9.65 673 8.07 700 8.84 726 9.62 751 10.41 691 9.48 717 10.29 743 11.11 768 11.96 715 11.38 739 12.19 764 13.03 787 13.88 745 13.88 768 14.69 791 15.53 813 16.39 763 15.36 785 16.19 807 17.03 828 17.90 1.4 Rpm 542 551 576 609 649 671 1.6 Bhp 4.66 5.16 6.51 8.38 10.83 12.27 Rpm 576 584 606 637 674 694 3.0 Rpm 764 775 792 810 834 849 Bhp 10.39 11.20 12.82 14.76 17.27 18.78 3.2 Rpm 786 797 815 833 856 869 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 807 11.88 828 12.62 848 13.37 867 14.12 819 12.80 841 13.61 861 14.42 881 15.23 837 14.57 859 15.47 881 16.37 —— 855 16.57 876 17.51 897 18.45 — — 876 19.10 897 20.04 — — — — 890 20.61 — — — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 16 Bhp 5.34 5.86 7.21 9.09 11.55 13.01 Bhp 11.13 12.00 13.69 15.66 18.17 19.69 Table 12 — Fan Performance — 50ZG,ZN040 Units With Discharge Plenum and 50Z2,Z3040 Units AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 8,000 10,000 12,000 14,000 16,000 18,000 20,000 0.2 Rpm 293 343 395 449 504 559 615 Bhp 1.62 2.66 4.09 5.97 8.32 11.20 14.66 0.4 Rpm 344 385 431 481 533 586 640 1.8 Rpm 603 623 648 677 712 749 790 Bhp 6.23 7.70 9.50 11.73 14.45 17.73 21.61 Bhp 2.10 3.19 4.68 6.62 9.06 12.04 15.59 2.0 Rpm 632 651 674 702 735 771 811 Bhp 6.87 8.41 10.26 12.54 15.30 18.61 22.52 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 390 2.62 432 3.18 470 3.76 507 4.36 425 3.76 463 4.36 498 4.99 532 5.64 466 5.29 500 5.93 532 6.60 562 7.30 512 7.28 541 7.96 570 8.67 598 9.40 560 9.77 587 10.50 613 11.25 638 12.02 611 12.82 635 13.59 659 14.38 682 15.19 663 16.44 685 17.28 707 18.11 728 18.96 Rpm 541 563 592 626 663 705 749 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 659 7.50 685 8.14 710 8.78 734 9.43 678 9.13 703 9.86 728 10.60 752 11.33 699 11.04 724 11.83 748 12.63 772 13.44 726 13.35 750 14.19 772 15.04 795 15.89 757 16.16 779 17.03 801 17.92 822 18.82 792 19.50 813 20.42 833 21.34 853 22.27 830 23.45 — — — — — — Rpm 757 776 794 817 843 873 — 1.4 Bhp 4.97 6.31 8.01 10.16 12.81 16.01 19.83 1.6 Rpm 573 594 620 652 688 727 770 3.0 Bhp 10.07 12.08 14.25 16.76 19.73 23.23 — 3.2 Rpm 779 798 817 838 863 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 800 11.35 821 12.00 841 12.64 860 13.28 820 13.57 841 14.31 862 15.06 882 15.81 838 15.90 859 16.73 880 17.57 900 18.40 859 18.53 879 19.42 899 20.32 — — 883 21.58 — — — — — — — — — — — — — — — — — — — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 17 Bhp 5.60 7.00 8.75 10.93 13.62 16.86 20.71 Bhp 10.71 12.82 15.07 17.64 20.65 — — Table 13 — Fan Performance — 50ZG,ZN050 Units With Discharge Plenum and 50Z2,Z3050 Units AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 AIRFLOW (Cfm) 9,000 10,000 12,000 14,000 16,000 18,000 20,000 0.2 Rpm 324 349 403 459 515 573 630 Bhp 2.15 2.74 4.23 6.17 8.63 11.65 15.28 0.4 Rpm 369 392 439 490 544 599 654 1.8 Rpm 617 628 654 686 721 761 803 Bhp 7.08 7.87 9.74 12.06 14.88 18.27 22.27 Bhp 2.67 3.28 4.82 6.83 9.34 12.44 16.14 2.0 Rpm 645 656 680 710 744 782 823 Bhp 7.77 8.59 10.51 12.88 15.74 19.17 23.21 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 412 3.23 452 3.83 488 4.44 523 5.08 431 3.87 469 4.48 504 5.12 537 5.78 474 5.45 507 6.11 539 6.80 570 7.51 521 7.50 550 8.20 579 8.93 607 9.69 571 10.07 597 10.82 623 11.59 649 12.38 623 13.21 647 14.00 671 14.82 694 15.65 677 16.97 699 17.81 720 18.66 741 19.53 Rpm 556 569 599 634 674 716 762 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 672 8.47 698 9.18 723 9.90 747 10.62 682 9.33 708 10.07 733 10.82 757 11.58 706 11.30 730 12.10 754 12.90 778 13.73 734 13.71 757 14.55 780 15.41 802 16.27 767 16.62 789 17.51 810 18.41 831 19.32 803 20.09 824 21.02 844 21.96 864 22.92 — — — — — — — — Rpm 770 780 800 824 852 884 — 1.4 Bhp 5.73 6.46 8.23 10.46 13.20 16.50 20.43 1.6 Rpm 587 599 627 660 698 739 783 3.0 Bhp 11.34 12.35 14.56 17.15 20.24 23.88 — 3.2 Rpm 793 802 822 845 872 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 814 12.79 835 13.52 855 14.25 875 14.99 824 13.89 845 14.67 866 15.45 886 16.23 844 16.24 865 17.09 885 17.95 — — 866 18.94 886 19.85 — — — — 892 22.12 — — — — — — — — — — — — — — — — — — — — — — LEGEND 2. See Table 30A before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 18 Bhp 6.40 7.16 8.98 11.25 14.03 17.37 21.34 Bhp 12.07 13.12 15.39 18.04 21.17 — — Table 14 — Fan Performance — 50ZG,ZN055 Units With Discharge Plenum and 50Z2,Z3055 Units AIRFLOW (Cfm) 10,000 12,500 15,000 17,500 20,000 22,500 25,000 AIRFLOW (Cfm) 10,000 12,500 15,000 17,500 20,000 22,500 25,000 AIRFLOW (Cfm) 10,000 12,500 15,000 17,500 20,000 22,500 25,000 0.2 Rpm 217 248 281 315 351 389 427 Bhp 1.21 2.01 3.13 4.64 6.64 9.20 12.39 0.4 Rpm 258 286 317 348 381 414 449 1.8 Rpm 500 498 501 514 535 561 590 Bhp 7.48 8.63 10.03 12.05 14.76 18.17 22.27 Bhp 1.71 2.63 3.90 5.55 7.64 10.25 13.48 2.0 Rpm 527 525 526 536 554 579 606 Bhp 8.46 9.76 11.17 13.17 15.88 19.34 23.51 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 296 2.29 334 2.97 371 3.76 407 4.63 319 3.26 349 3.95 380 4.71 410 5.58 347 4.64 374 5.38 400 6.18 425 7.03 378 6.43 403 7.29 426 8.16 449 9.05 409 8.68 433 9.68 456 10.66 477 11.64 440 11.43 464 12.59 486 13.71 506 14.81 473 14.75 496 16.06 517 17.34 537 18.59 Rpm 440 440 450 471 497 525 555 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 552 9.45 576 10.44 598 11.42 619 12.41 552 10.93 577 12.12 601 13.32 624 14.54 550 12.38 575 13.65 598 14.97 621 16.32 557 14.35 579 15.60 600 16.91 621 18.28 573 17.06 592 18.29 611 19.58 630 20.91 596 20.54 613 21.78 629 23.06 646 24.40 622 24.78 637 26.07 653 27.39 668 28.75 Rpm 639 646 644 643 649 663 683 1.4 Bhp 5.56 6.52 7.95 10.00 12.65 15.91 19.82 1.6 Rpm 471 469 476 493 516 543 573 3.0 Bhp 13.41 15.76 17.71 19.70 22.31 25.78 30.13 3.2 Rpm 659 667 666 663 668 680 699 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 677 15.40 695 16.40 712 17.40 728 18.41 687 18.22 706 19.45 725 20.69 742 21.92 687 20.54 707 21.98 727 23.43 746 24.89 684 22.69 704 24.24 724 25.83 743 27.43 686 25.27 705 26.84 723 28.44 742 30.09 697 28.68 713 30.21 730 31.79 747 33.42 714 33.04 729 34.55 — — — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 19 Bhp 6.51 7.54 8.95 10.99 13.68 17.03 21.04 Bhp 14.41 16.99 19.11 21.18 23.77 27.20 31.56 Table 15 — Fan Performance — 50ZG,ZN060 Units With Discharge Plenum and 50Z2,Z3060 Units AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 AIRFLOW (Cfm) 12,000 15,000 18,000 21,000 24,000 27,000 30,000 0.2 Rpm 241 281 323 366 410 455 500 Bhp 1.82 3.14 5.03 7.61 10.97 15.23 20.52 0.4 Rpm 280 316 355 395 437 479 522 1.8 Rpm 486 498 518 546 577 611 648 Bhp 7.94 9.90 12.57 16.07 20.49 25.91 32.43 Bhp 2.41 3.87 5.92 8.66 12.20 16.65 22.11 2.0 Rpm 511 520 539 564 594 628 663 Bhp 8.91 10.93 13.66 17.23 21.74 27.26 33.90 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 314 3.04 346 3.72 376 4.47 405 5.26 346 4.61 374 5.38 400 6.19 426 7.05 382 6.80 408 7.68 431 8.58 454 9.53 421 9.69 444 10.71 466 11.73 487 12.78 460 13.39 482 14.55 503 15.71 523 16.88 501 18.00 522 19.33 542 20.64 560 21.95 543 23.64 563 25.14 581 26.61 599 28.06 Rpm 433 450 476 507 541 578 616 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 535 9.91 559 10.94 581 11.99 603 13.07 543 12.01 564 13.11 586 14.26 606 15.43 559 14.78 579 15.95 598 17.15 617 18.39 583 18.42 600 19.64 618 20.90 635 22.19 611 23.00 628 24.31 644 25.63 660 26.99 643 28.63 659 30.03 674 31.44 689 32.87 678 35.38 — — — — — — Rpm 624 627 636 653 676 703 — 1.4 Bhp 6.11 7.95 10.50 13.85 18.07 23.26 29.52 1.6 Rpm 460 474 498 527 560 595 632 3.0 Bhp 14.16 16.63 19.65 23.51 28.38 34.33 — 3.2 Rpm 645 646 654 669 691 718 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 664 16.40 683 17.55 702 18.70 720 19.87 666 19.12 685 20.39 703 21.69 721 23.01 672 22.28 690 23.64 708 25.02 725 26.44 686 26.25 703 27.67 719 29.11 735 30.59 707 31.23 722 32.71 737 34.20 — — — — — — — — — — — — — — — — — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 20 Bhp 7.01 8.90 11.52 14.94 19.27 24.58 30.97 Bhp 15.28 17.86 20.95 24.86 29.77 35.82 — Table 16 — Fan Performance — 50ZG,ZN070 Units With Discharge Plenum and 50Z2,Z3070 Units AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 AIRFLOW (Cfm) 14,000 17,500 21,000 24,500 28,000 30,000 0.2 Rpm 268 316 366 417 470 500 Bhp 2.64 4.67 7.61 11.61 16.88 20.52 0.4 Rpm 304 348 395 444 493 522 1.8 Rpm 493 515 546 583 623 648 Bhp 9.17 12.07 16.07 21.32 27.96 32.43 Bhp 3.32 5.54 8.66 12.87 18.35 22.11 2.0 Rpm 516 535 564 600 639 663 Bhp 10.19 13.14 17.23 22.59 29.35 33.90 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 335 4.02 364 4.76 391 5.55 418 6.39 376 6.39 402 7.25 426 8.14 449 9.06 421 9.69 444 10.71 466 11.73 487 12.78 467 14.09 489 15.28 509 16.47 529 17.66 515 19.77 536 21.15 555 22.51 573 23.87 543 23.64 563 25.14 581 26.61 599 28.06 Rpm 444 472 507 547 590 616 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 539 11.24 562 12.33 583 13.45 605 14.60 556 14.26 576 15.42 595 16.61 615 17.84 583 18.42 600 19.64 618 20.90 635 22.19 616 23.87 633 25.18 649 26.53 664 27.89 655 30.75 670 32.18 685 33.63 699 35.09 678 35.38 — — — — — — Rpm 625 634 653 680 — — 1.4 Bhp 7.27 10.03 13.85 18.86 25.22 29.52 1.6 Rpm 468 493 527 565 607 632 3.0 Bhp 15.77 19.09 23.51 29.29 — — 3.2 Rpm 645 652 669 695 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 665 18.18 684 19.42 703 20.68 721 21.95 671 21.70 689 23.05 706 24.42 724 25.82 686 26.24 703 27.67 719 29.11 735 30.59 711 32.17 726 33.65 741 35.16 — — — — — — — — — — — — — — — — — — LEGEND 2. See Table 30B before using Fan Performance tables. 3. Conversion — Bhp to kW: 50ZN,Z3 units only. Bhp — Brake Horsepower Kilowatts = NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 21 Bhp 8.20 11.03 14.94 20.08 26.59 30.97 Bhp 16.96 20.39 24.86 30.71 — — Table 17 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9075 Units With Forward-Curved Fan* AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 0.2 Rpm Bhp 211 2.35 232 3.27 253 4.42 275 5.83 298 7.53 320 9.55 343 11.91 367 14.65 390 17.78 0.4 Rpm Bhp 243 3.06 261 4.06 281 5.31 301 6.82 321 8.62 342 10.75 364 13.22 386 16.06 408 19.31 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 272 3.80 299 4.59 325 5.43 349 6.30 288 4.88 313 5.74 337 6.65 360 7.59 305 6.21 329 7.14 351 8.11 372 912 324 7.81 346 8.82 366 9.86 386 10.94 343 9.70 364 10.80 383 11.92 402 13.07 363 11.93 383 13.11 401 14.31 419 15.54 384 14.50 402 15.78 420 17.07 437 18.37 405 17.45 422 18.83 439 20.20 455 21.59 426 20.80 443 22.28 459 23.75 474 25.24 1.4 Rpm Bhp 372 7.21 381 8.57 393 10.17 406 12.05 420 14.25 436 16.79 453 19.70 471 23.00 489 26.73 Rpm 395 402 413 425 438 453 469 486 504 1.8 Rpm Bhp 416 9.12 423 10.62 432 12.36 443 14.38 455 16.70 470 19.38 485 22.43 501 25.89 518 29.76 2.0 Rpm Bhp 437 10.10 442 11.68 450 13.50 460 15.58 472 17.98 486 20.72 500 23.83 516 27.36 533 31.32 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Hp Rpm Hp Rpm Hp Rpm Hp 457 11.10 476 12.13 495 13.17 513 14.22 462 12.77 480 13.88 498 15.00 516 16.15 469 14.66 486 15.84 504 17.05 521 18.27 478 16.82 495 18.07 511 19.35 527 20.65 489 19.28 505 20.60 521 21.96 536 23.33 501 22.08 517 23.48 532 24.89 547 26.34 515 25.27 530 26.73 544 28.22 559 29.72 530 28.86 544 30.38 558 31.94 572 33.51 546 32.89 560 34.48 573 36.10 586 37.74 3.0 Rpm Hp 531 15.29 533 17.31 537 19.53 543 21.98 551 24.72 561 27.80 573 31.26 585 35.11 599 39.41 3.2 Rpm Hp 548 16.38 550 18.48 553 20.78 559 23.32 566 26.14 576 29.29 586 32.81 599 36.74 612 41.11 1.6 Bhp 8.15 9.58 11.25 13.20 15.46 18.07 21.05 24.43 28.24 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Hp Rpm Hp Rpm Hp Rpm Hp 564 17.47 581 18.58 596 19.71 612 20.84 566 19.68 582 20.88 597 22.10 613 23.33 569 22.06 585 23.36 600 24.66 615 25.99 574 24.68 589 26.06 604 27.45 618 28.85 581 27.57 596 29.04 610 30.51 624 31.99 590 30.80 604 32.33 617 33.88 631 35.44 600 34.39 613 35.99 627 37.61 640 39.24 612 38.38 624 40.05 637 41.74 650 43.44 624 42.81 637 44.54 649 46.29 661 48.06 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 22 Table 18 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9075 Units With Airfoil Fan* AIRFLOW (Cfm) 15,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 AIRFLOW (Cfm) 15,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 AIRFLOW (Cfm) 15,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 0.30 Rpm Bhp 622 3.32 657 3.86 727 5.11 798 6.60 870 8.37 942 10.42 1015 12.73 1088 15.52 1162 18.68 0.60 Rpm Bhp 673 4.27 705 4.85 771 6.20 838 7.80 907 9.66 977 11.73 1047 14.26 1118 17.15 1190 20.43 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.90 1.20 1.50 1.80 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 721 5.24 768 6.27 815 7.33 859 8.44 751 5.87 795 6.93 839 8.02 882 9.15 812 7.30 853 8.42 892 9.58 931 10.66 876 8.98 913 10.18 950 11.31 985 12.59 942 10.83 977 12.14 1010 13.47 1043 14.83 1010 13.13 1042 14.54 1073 15.96 1103 17.40 1078 15.77 1108 17.28 1137 18.79 1166 20.32 1147 18.77 1176 20.38 1203 21.99 1230 23.61 1218 22.15 1244 23.87 1270 25.58 1296 27.29 2.10 Rpm Bhp 903 9.57 924 10.32 970 11.92 1021 13.91 1076 16.22 1134 18.87 1194 21.87 1257 25.25 1321 29.01 2.40 Rpm Bhp 945 10.63 965 11.43 1008 13.22 1056 15.28 1108 17.65 1163 20.37 1222 23.44 1283 26.90 1345 30.75 2.70 Rpm Bhp 985 11.83 1004 12.68 1045 14.54 1090 16.67 1140 19.11 1193 21.90 1250 25.04 1309 28.57 1370 32.50 3.00 Rpm Bhp 1024 13.05 1042 13.95 1081 15.90 1124 18.10 1171 20.61 1222 23.45 1277 26.67 1335 30.27 1394 34.28 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.30 3.60 3.90 4.20 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1062 14.29 1098 15.54 1132 16.80 1166 18.07 1079 15.24 1114 16.55 1149 17.86 1182 19.19 1116 17.28 1150 18.69 1184 20.11 1216 21.54 1157 19.56 1190 21.05 1222 22.56 1253 24.09 1202 22.14 1233 23.69 1263 25.28 1293 26.88 1252 25.04 1280 26.67 1309 28.31 1337 29.99 1304 28.33 1331 30.01 1358 31.72 1385 33.46 1360 32.00 1386 33.75 1411 35.52 1436 37.32 1418 36.08 1442 37.89 1466 39.74 1490 41.60 4.50 Rpm Bhp 1199 19.34 1215 20.52 1248 22.99 1284 25.63 1323 28.51 1365 31.69 1411 35.22 1461 39.15 1513 43.49 4.80 Rpm Bhp 1230 20.63 1246 21.87 1279 24.45 1314 27.19 1352 30.16 1393 33.42 1437 37.01 1486 40.99 1537 45.40 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 5.10 5.40 5.70 6.00 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1261 21.92 1291 23.22 1320 24.52 1348 25.84 1276 23.22 1306 24.58 1335 25.95 1363 27.32 1309 25.92 1338 27.40 1367 28.88 1395 30.37 1343 28.77 1372 30.35 1400 31.94 1428 33.55 1380 31.82 1408 33.50 1435 35.20 1462 36.90 1420 35.16 1447 36.92 1473 38.70 1499 40.49 1463 38.82 1489 40.66 1514 42.51 1539 44.38 1510 42.87 1535 44.77 1559 46.69 1583 48.63 1560 47.34 1583 49.30 1606 51.28 1629 53.28 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 23 Table 19 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9090 Units With Forward-Curved Fan* AIRFLOW (Cfm) 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 AIRFLOW (Cfm) 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 AIRFLOW (Cfm) 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 0.2 Rpm Bhp 232 3.27 253 4.42 275 5.83 298 7.53 320 9.55 343 11.91 367 14.65 390 17.78 414 21.36 437 25.39 0.4 Rpm Bhp 261 4.06 281 5.31 301 6.82 321 8.62 342 10.75 364 13.22 386 16.06 408 19.31 431 22.99 454 27.13 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 288 4.88 313 5.74 337 6.65 360 7.59 305 6.21 329 7.14 351 8.11 372 9.12 324 7.81 346 8.82 366 9.86 386 10.94 343 9.70 364 10.80 383 11.92 402 13.07 363 11.93 383 13.11 401 14.31 419 15.54 384 14.50 402 15.78 420 17.07 437 18.37 405 17.45 422 18.83 439 20.20 455 21.59 426 20.80 443 22.28 459 23.75 474 25.24 448 24.59 464 26.17 479 27.75 494 29.32 470 28.84 485 30.53 500 32.20 514 33.87 1.4 Rpm Bhp 381 8.57 393 10.17 406 12.05 420 14.25 436 16.79 453 19.70 471 23.00 489 26.73 508 30.90 528 35.55 Rpm 402 413 425 438 453 469 486 504 523 542 1.8 Rpm Bhp 423 10.62 432 12.36 443 14.38 455 16.70 470 19.38 485 22.43 501 25.89 518 29.76 536 34.11 555 38.92 2.0 Rpm Bhp 442 11.68 450 13.50 460 15.58 472 17.98 486 20.72 500 23.83 516 27.36 533 31.32 550 35.73 568 40.63 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 462 12.77 480 13.88 498 15.00 516 16.15 469 14.66 486 15.84 504 17.05 521 18.27 478 16.82 495 18.07 511 19.35 527 20.65 489 19.28 505 20.60 521 21.96 536 23.33 501 22.08 517 23.48 532 24.89 547 26.34 515 25.27 530 26.73 544 28.22 559 29.72 530 28.86 544 30.38 558 31.94 572 33.51 546 32.89 560 34.48 573 36.10 586 37.74 563 37.38 576 39.04 589 40.73 601 42.45 581 42.36 593 44.10 605 45.87 618 47.64 3.0 Rpm Bhp 533 17.31 537 19.53 543 21.98 551 24.72 561 27.80 573 31.26 585 35.11 599 39.41 614 44.18 630 49.45 Rpm 550 553 559 566 576 586 599 612 626 641 1.6 Bhp 9.58 11.25 13.20 15.46 18.07 21.05 24.43 28.24 32.49 37.23 3.2 Bhp 18.48 20.78 23.32 26.14 29.29 32.81 36.74 41.11 45.94 51.27 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 566 19.68 582 20.88 597 22.10 613 23.33 569 22.06 585 23.36 600 24.66 615 25.99 574 24.68 589 26.06 604 27.45 618 28.85 581 27.57 596 29.04 610 30.51 624 31.99 590 30.80 604 32.33 617 33.88 631 35.44 600 34.39 613 35.99 627 37.61 640 39.24 612 38.38 624 40.05 637 41.74 650 43.44 624 42.81 637 44.54 649 46.29 661 48.06 638 47.72 650 49.51 662 51.33 674 53.17 653 53.12 665 54.98 676 56.87 — — 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 24 Table 20 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9090 Units With Airfoil Fan* AIRFLOW (Cfm) 17,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 AIRFLOW (Cfm) 17,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 AIRFLOW (Cfm) 17,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 0.30 Rpm Bhp 692 4.45 727 5.11 798 6.60 870 8.37 942 10.42 1015 12.73 1088 15.52 1162 18.68 1235 22.25 1309 26.26 0.60 Rpm Bhp 737 5.50 771 6.20 838 7.80 907 9.66 977 11.73 1047 14.26 1118 17.15 1190 20.43 1262 24.12 1335 28.23 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.90 1.20 1.50 1.80 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 781 6.56 824 7.64 865 8.77 906 9.93 812 7.30 853 8.42 892 9.58 931 10.66 876 8.98 913 10.18 950 11.31 985 12.59 942 10.83 977 12.14 1010 13.47 1043 14.83 1010 13.13 1042 14.54 1073 15.96 1103 17.40 1078 15.77 1108 17.28 1137 18.79 1166 20.32 1147 18.77 1176 20.38 1203 21.99 1230 23.61 1218 22.15 1244 23.87 1270 25.58 1296 27.29 1288 25.94 1313 27.76 1338 29.57 1362 31.38 1359 30.17 1383 32.09 1407 34.00 1430 35.91 2.10 Rpm Bhp 946 11.03 970 11.92 1021 13.91 1076 16.22 1134 18.87 1194 21.87 1257 25.25 1321 29.01 1386 33.20 1452 37.82 2.40 Rpm Bhp 985 12.29 1008 13.22 1056 15.28 1108 17.65 1163 20.37 1222 23.44 1283 26.90 1345 30.75 1409 35.02 1475 39.73 2.70 Rpm Bhp 1024 13.58 1045 14.54 1090 16.67 1140 19.11 1193 21.90 1250 25.04 1309 28.57 1370 32.50 1433 36.87 1497 41.66 3.00 Rpm Bhp 1061 14.90 1081 15.90 1124 18.10 1171 20.61 1222 23.45 1277 26.67 1335 30.27 1394 34.28 1456 38.72 1519 43.60 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.30 3.60 3.90 4.20 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1097 16.24 1132 17.59 1166 18.96 1199 20.35 1116 17.28 1150 18.69 1184 20.11 1216 21.54 1157 19.56 1190 21.05 1222 22.56 1253 24.09 1202 22.14 1233 23.69 1263 25.28 1293 26.88 1252 25.04 1280 26.67 1309 28.31 1337 29.99 1304 28.33 1331 30.01 1358 31.72 1385 33.46 1360 32.00 1386 33.75 1411 35.52 1436 37.32 1418 36.08 1442 37.89 1466 39.74 1490 41.60 1479 40.58 1501 42.48 1524 44.38 1546 46.32 1540 45.55 1562 47.52 1583 49.50 1605 51.50 4.50 Rpm Bhp 1231 21.74 1248 22.99 1284 25.63 1323 28.51 1365 31.69 1411 35.22 1461 39.15 1513 43.49 1568 48.27 1626 53.52 4.80 Rpm Bhp 1262 23.14 1279 24.45 1314 27.19 1352 30.16 1393 33.42 1437 37.01 1486 40.99 1537 45.40 1591 50.25 1647 55.56 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 5.10 5.40 5.70 6.00 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1292 24.55 1322 25.97 1351 27.40 1379 28.83 1309 25.92 1338 27.40 1367 28.88 1395 30.37 1343 28.77 1372 30.35 1400 31.94 1428 33.55 1380 31.82 1408 33.50 1435 35.20 1462 36.90 1420 35.16 1447 36.92 1473 38.70 1499 40.49 1463 38.82 1489 40.66 1514 42.51 1539 44.38 1510 42.87 1535 44.77 1559 46.69 1583 48.63 1560 47.34 1583 49.30 1606 51.28 1629 53.28 1613 52.25 1635 54.27 1657 56.31 1678 58.37 1668 57.63 1689 59.70 1710 61.80 1730 63.93 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 25 Table 21 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9105 Units With Forward-Curved Fan* AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 0.2 Rpm Bhp 275 5.83 298 7.53 320 9.55 343 11.91 367 14.65 390 17.78 414 21.36 437 25.39 461 29.92 485 34.96 509 40.54 0.4 Rpm Bhp 301 6.82 321 8.62 342 10.75 364 13.22 386 16.06 408 19.31 431 22.99 454 27.13 477 31.77 500 36.91 523 42.61 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 324 7.81 346 8.82 366 9.86 386 10.94 343 9.70 364 10.80 383 11.92 402 13.07 363 11.93 383 13.11 401 14.31 419 15.54 384 14.50 402 15.78 420 17.07 437 18.37 405 17.45 422 18.83 439 20.20 455 21.59 426 20.80 443 22.28 459 23.75 474 25.24 448 24.59 464 26.17 479 27.75 494 29.32 470 28.84 485 30.53 500 32.20 514 33.87 492 33.58 506 35.38 521 37.16 534 38.93 514 38.85 528 40.74 542 42.63 555 44.50 537 44.65 550 46.66 563 48.64 576 50.62 1.4 Rpm Bhp 406 12.05 420 14.25 436 16.79 453 19.70 471 23.00 489 26.73 508 30.90 528 35.55 548 40.69 568 46.36 589 52.59 Rpm 425 438 453 469 486 504 523 542 561 581 601 1.8 Rpm Bhp 443 14.38 455 16.70 470 19.38 485 22.43 501 25.89 518 29.76 536 34.11 555 38.92 574 44.25 593 50.10 613 56.52 2.0 Rpm Bhp 460 15.58 472 17.98 486 20.72 500 23.83 516 27.36 533 31.32 550 35.73 568 40.63 586 46.03 605 51.98 625 58.49 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.2 2.4 2.6 2.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 478 16.82 495 18.07 511 19.35 527 20.65 489 19.28 505 20.60 521 21.96 536 23.33 501 22.08 517 23.48 532 24.89 547 26.34 515 25.27 530 26.73 544 28.22 559 29.72 530 28.86 544 30.38 558 31.94 572 33.51 546 32.89 560 34.48 573 36.10 586 37.74 563 37.38 576 39.04 589 40.73 601 42.45 581 42.36 593 44.10 605 45.87 618 47.64 599 47.85 611 49.67 623 51.51 634 53.37 617 53.87 629 55.77 640 57.71 652 59.63 636 60.48 648 62.46 659 64.47 — — 3.0 Rpm Bhp 543 21.98 551 24.72 561 27.80 573 31.26 585 35.11 599 39.41 614 44.18 630 49.45 646 55.25 663 61.59 — — Rpm 559 566 576 586 599 612 626 641 657 674 — 1.6 Bhp 13.20 15.46 18.07 21.05 24.43 28.24 32.49 37.23 42.47 48.23 54.56 3.2 Bhp 23.32 26.14 29.29 32.81 36.74 41.11 45.94 51.27 57.14 63.54 — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 4.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 574 24.68 589 26.06 604 27.45 618 28.86 581 27.57 596 29.04 610 30.51 624 31.99 590 30.80 604 32.33 617 33.88 631 35.44 600 34.39 613 35.99 627 37.61 640 39.24 612 38.38 624 40.05 637 41.74 650 43.44 624 42.81 637 44.54 649 46.29 661 48.06 638 47.72 650 49.51 662 51.33 674 53.17 653 53.12 665 54.98 676 56.87 — — 669 59.06 680 60.98 — — — — — — — — — — — — — — — — — — — — 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 26 Table 22 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9105 Units With Airfoil Fan* AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 0.30 Rpm Bhp 798 6.60 870 8.37 942 10.42 1015 12.73 1088 15.52 1162 18.68 1235 22.25 1309 26.26 1383 30.73 1457 35.67 1532 41.12 0.60 Rpm Bhp 838 7.80 907 9.66 977 11.73 1047 14.26 1118 17.15 1190 20.43 1262 24.12 1335 28.23 1407 32.80 1480 37.85 1554 43.40 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.90 1.20 1.50 1.80 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 876 8.98 913 10.18 950 11.31 985 12.59 942 10.83 977 12.14 1010 13.47 1043 14.83 1010 13.13 1042 14.54 1073 15.96 1103 17.40 1078 15.77 1108 17.28 1137 18.79 1166 20.32 1147 18.77 1176 20.38 1203 21.99 1230 23.61 1217 22.15 1244 23.87 1270 25.58 1296 27.29 1288 25.94 1313 27.76 1338 29.57 1362 31.38 1359 30.17 1383 32.09 1407 34.00 1430 35.91 1431 34.85 1454 36.87 1476 38.89 1498 40.89 1503 40.00 1525 42.13 1546 44.24 1567 46.36 1575 45.65 1596 47.88 1616 50.10 1637 52.31 2.10 Rpm Bhp 1021 13.91 1076 16.22 1134 18.87 1194 21.87 1257 25.25 1321 29.01 1386 33.20 1452 37.82 1520 42.90 1588 48.46 1657 54.51 2.40 Rpm Bhp 1056 15.28 1108 17.65 1163 20.37 1222 23.44 1283 26.90 1345 30.75 1409 35.02 1475 39.73 1541 44.90 1608 50.56 1676 56.71 2.70 Rpm Bhp 1090 16.67 1140 19.11 1193 21.90 1250 25.04 1309 28.57 1370 32.50 1433 36.87 1497 41.66 1562 46.92 1628 52.66 1696 58.91 3.00 Rpm Bhp 1124 18.10 1171 20.61 1222 23.45 1277 26.67 1335 30.27 1394 34.28 1456 38.72 1519 43.60 1583 48.94 1648 54.78 1715 61.10 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.30 3.60 3.90 4.20 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1157 19.56 1190 21.05 1222 22.56 1253 24.09 1202 22.14 1233 23.69 1263 25.28 1293 26.88 1252 25.04 1280 26.67 1309 28.31 1337 29.99 1304 28.33 1331 30.01 1358 31.72 1385 33.46 1360 32.00 1386 33.75 1411 35.52 1436 37.32 1418 36.08 1442 37.89 1466 39.74 1490 41.60 1479 40.58 1501 42.48 1524 44.38 1546 46.32 1540 45.55 1562 47.52 1583 49.50 1605 51.50 1604 50.97 1624 53.02 1645 55.08 1665 57.15 1668 56.89 1688 59.02 1707 61.16 1727 63.31 1734 63.31 1752 65.52 1771 67.74 1790 69.97 4.50 Rpm Bhp 1284 25.63 1323 28.51 1365 31.69 1411 35.22 1461 39.15 1513 43.49 1568 48.27 1626 53.52 1685 59.25 1746 65.47 — — 4.80 Rpm Bhp 1314 27.19 1352 30.16 1393 33.42 1437 37.01 1486 40.99 1537 45.40 1591 50.25 1647 55.56 1705 61.35 1765 67.65 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 5.10 5.40 5.70 6.00 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1343 28.77 1372 30.35 1400 31.94 1428 33.55 1380 31.82 1408 33.50 1435 35.20 1462 36.90 1420 35.16 1447 36.92 1473 38.70 1499 40.49 1463 38.82 1489 40.66 1514 42.51 1539 44.38 1510 42.87 1535 44.77 1559 46.69 1583 48.63 1560 47.34 1583 49.30 1606 51.28 1629 53.28 1613 52.25 1635 54.27 1657 56.31 1678 58.37 1668 57.63 1689 59.70 1710 61.80 1730 63.93 1725 63.48 1745 65.63 1765 67.79 1785 69.97 1784 69.85 — — — — — — — — — — — — — — 2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add component pressure drop for economizer. Do not add component pressure drop for power exhaust. 3. See Table 30C before using Fan Performance tables. 4. Conversion — Bhp to kW: LEGEND 48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only. Bhp — Brake Horsepower *If calculating static pressure for a 48 Series unit, be sure to add gas heat pressure drop from Table 30C. NOTES: 1. Fan performance is based on wet coils and clean 2-in. filters. Kilowatts = Bhp x .746 Motor efficiency See Tables 26-28 for motor efficiency. 27 Table 23 — Fan Performance — Standard Capacity Power Exhaust Size 030-050 Units AIRFLOW (Cfm) 6,000 8,000 10,000 12,000 14,000 16,000 18,000 20,000 0.20 Rpm Bhp 380 0.95 440 1.69 504 2.73 575 4.17 650 6.09 729 8.57 809 11.57 891 15.47 0.40 Rpm Bhp 468 1.47 523 2.40 582 3.68 643 5.33 708 7.42 778 10.02 851 13.19 927 17.22 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.60 0.80 1.00 1.20 1.40 1.60 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 543 2.01 612 2.60 676 3.24 738 3.92 796 4.64 852 5.39 591 3.08 651 3.77 706 4.49 759 5.23 810 6.01 859 6.82 647 4.55 703 5.38 754 6.22 802 7.06 847 7.92 891 8.80 705 6.42 760 7.45 809 8.44 854 9.41 896 10.38 937 11.27 766 8.73 819 9.97 867 11.05 910 12.22 951 13.38 990 14.53 829 11.43 879 12.93 926 14.37 969 15.76 — — — — 896 14.90 942 16.61 987 18.29 — — — — — — 967 19.08 — — — — — — — — — — 1.80 Rpm Bhp 905 6.17 907 7.66 933 9.70 976 12.29 — — — — — — — — 2.00 Rpm Bhp 956 6.98 953 8.53 975 10.52 — — — — — — — — — — 1.8 Rpm Bhp 808 5.86 822 7.30 845 9.03 878 11.16 918 13.81 — — — — — — 2.0 Rpm Bhp 850 6.47 861 8.00 881 9.80 910 11.98 — — — — — — — — Size 055-155 Units AIRFLOW (Cfm) 10,000 12,000 14,000 16,000 18,000 20,000 22,000 24,000 0.2 Rpm Bhp 416 1.65 480 2.67 546 4.09 613 5.95 682 8.32 752 11.27 821 14.86 892 19.16 0.4 Rpm Bhp 469 2.03 524 3.09 584 4.55 647 6.46 712 8.88 779 11.89 846 15.53 915 19.89 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 522 2.47 574 2.97 624 3.51 673 4.08 720 4.66 765 5.26 568 3.56 612 4.09 656 4.67 699 5.29 741 5.94 782 6.61 621 5.05 659 5.61 697 6.21 735 6.87 772 7.56 809 8.28 680 7.00 713 7.59 746 8.22 779 8.90 812 9.62 845 10.37 741 9.47 771 10.10 800 10.76 830 11.47 859 12.21 889 13.00 805 12.53 832 13.19 858 13.90 885 14.63 911 15.41 — — 871 16.23 895 16.94 919 17.69 — — — — — — — — — — — — — — — — — — Bhp — Brake Horsepower Table 24 — Fan Performance — Return/Exhaust Fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9075-105 Units) AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 0.2 Rpm Bhp 594 3.61 619 4.09 687 5.57 756 7.37 825 9.50 895 11.94 965 14.94 1035 18.43 1105 22.42 1176 26.96 1246 32.09 1317 37.83 1388 44.22 — — 0.4 Rpm Bhp 594 3.61 652 4.76 718 6.35 786 8.25 853 10.50 922 13.08 990 16.21 1059 19.81 1128 23.93 1198 28.59 1267 33.83 1337 39.69 1407 46.21 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 617 4.02 646 4.58 674 5.16 700 5.75 725 6.36 749 6.99 681 5.40 708 6.02 733 6.65 757 7.29 781 7.94 803 8.61 746 7.07 771 7.76 795 8.45 817 9.14 839 9.85 860 10.56 812 9.06 836 9.84 858 10.59 879 11.25 900 12.03 920 12.82 878 11.31 901 12.20 923 13.06 943 13.90 962 14.75 981 15.60 945 14.12 967 15.10 988 16.05 1007 16.99 1026 17.91 1044 18.83 1013 17.36 1034 18.46 1054 19.51 1073 20.53 1091 21.54 1108 22.54 1081 21.09 1101 22.29 1120 23.45 1138 24.57 1156 25.67 1172 26.76 1149 25.33 1169 26.65 1187 27.92 1205 29.14 1222 30.34 1238 31.51 1218 30.11 1237 31.55 1255 32.93 1272 34.26 1288 35.56 1304 36.83 1287 35.47 1305 37.03 1322 38.53 1339 39.97 1355 41.38 1370 42.75 1356 41.46 1374 43.14 1391 44.75 1407 46.31 — — — — — — — — — — — — — — — — — — — — — — — — — — — — 1.8 Rpm Bhp 772 7.62 825 9.30 881 11.20 939 13.62 1000 16.46 1061 19.76 1125 23.54 1189 27.83 1253 32.67 1319 38.08 1385 44.10 — — — — — — 2.0 Rpm Bhp 795 8.25 847 9.99 901 11.96 958 14.43 1018 17.33 1079 20.69 1141 24.54 1204 28.91 1269 33.83 1333 39.32 1399 45.43 — — — — — — 2.2 Rpm Bhp 816 8.89 867 10.59 921 12.74 977 15.25 1035 18.21 1095 21.62 1157 25.54 1220 29.98 1283 34.98 1348 40.55 1413 46.75 — — — — — — 2.4 Rpm Bhp 836 9.52 887 11.31 940 13.52 995 16.10 1052 19.10 1112 22.58 1173 26.55 1235 31.06 1298 36.13 1362 41.78 — — — — — — — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.6 2.8 3.0 3.2 3.4 3.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 856 10.15 874 10.67 892 11.31 910 11.94 926 12.57 942 13.19 907 12.05 926 12.78 944 13.52 961 14.25 978 14.98 995 15.71 959 14.33 977 15.13 995 15.95 1012 16.77 1029 17.59 1046 18.42 1013 16.96 1031 17.82 1048 18.70 1065 19.59 1081 20.49 1097 21.39 1069 20.01 1086 20.93 1103 21.86 1119 22.81 1135 23.76 1150 24.73 1128 23.54 1144 24.51 1159 25.49 1175 26.49 1190 27.50 1205 28.52 1188 27.57 1203 28.59 1218 29.64 1233 30.68 1247 31.74 1262 32.81 1249 32.14 1264 33.23 1278 34.32 1292 35.42 1306 36.53 1320 37.65 1312 37.28 1326 38.42 1340 39.58 1353 40.74 1367 41.92 1380 43.09 1375 43.00 1389 44.22 1402 45.45 1415 46.67 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 3.8 Rpm Bhp 958 13.80 1011 16.44 1062 19.24 1113 22.30 1166 25.71 1220 29.55 1276 33.89 1334 38.78 1393 44.27 — — — — — — — — — — 4.0 Rpm Bhp 973 14.42 1026 17.16 1078 20.07 1129 23.21 1181 26.69 1234 30.58 1290 34.98 1347 39.93 1406 45.46 — — — — — — — — — — NOTE: The 48Z6,Z8 and 50Z6,Z7,Z8,Z9 units come standard with economizer and exhaust/return power exhaust. 28 Table 25 — Fan Performance — High-Capacity Power Exhaust (48ZT,ZW075-105 and 50ZT,ZW,ZX,ZZ) AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 AIRFLOW (Cfm) 14,000 16,000 18,000 20,000 22,000 24,000 26,000 28,000 30,000 32,000 34,000 36,000 38,000 40,000 Rpm 480 526 574 622 671 722 772 824 875 928 980 1033 1086 1139 AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 Bhp Rpm Bhp Rpm 4.28 520 4.86 557 5.86 563 6.47 597 7.84 608 8.45 639 10.26 654 10.87 684 13.16 701 13.76 730 16.59 750 17.16 777 20.58 799 21.13 824 25.18 849 25.70 873 30.43 899 30.91 922 36.35 950 36.80 972 42.98 1001 43.40 1022 50.37 1053 50.75 1072 58.53 1105 58.89 1124 67.52 1157 67.84 — Bhp 5.48 7.12 9.14 11.57 14.46 17.86 21.82 26.37 31.55 37.41 43.98 51.30 59.40 — Rpm 592 629 670 712 757 802 849 896 944 993 1042 1092 1142 — Rpm 659 690 726 765 807 850 894 940 986 1033 1081 1129 — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 Bhp Rpm Bhp Rpm 7.42 691 8.09 722 9.22 720 9.94 749 11.36 754 12.14 780 13.91 791 14.73 816 16.89 831 17.75 854 20.35 873 21.25 895 24.33 916 25.26 937 28.89 961 29.83 981 34.06 1006 35.01 1026 39.88 1053 40.84 1071 46.39 1100 47.35 1118 53.65 1147 54.59 1165 — — — — — — — — Bhp 8.77 10.68 12.93 15.57 18.63 22.16 26.21 30.81 36.00 41.84 48.36 55.60 — — Rpm 752 777 806 840 877 917 958 1001 1045 1090 1136 — — — Rpm 811 832 858 888 922 959 998 1040 1082 1126 1170 — — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 2.4 2.6 2.8 Bhp Rpm Bhp Rpm 10.83 839 11.53 866 12.93 858 13.69 884 15.35 882 16.17 907 18.14 911 19.01 934 21.34 944 22.26 966 25.00 980 25.98 1000 29.16 1018 30.17 1037 33.86 1058 34.91 1077 39.14 1100 40.23 1118 45.05 1143 46.16 1160 51.61 — — — — — — — — — — — — — — — Bhp 12.23 14.46 16.99 19.89 23.20 26.95 31.20 35.98 41.33 47.29 — — — — Rpm 892 910 931 957 987 1020 1057 1095 1135 — — — — — Rpm 943 959 978 1001 1029 1060 1094 1131 1169 — — — — — AVAILABLE EXTERNAL STATIC PRESSURE (in. wg) 3.4 3.6 3.8 Bhp Rpm Bhp Rpm 14.34 967 15.05 990 16.77 983 17.55 1006 19.50 1001 20.34 1024 22.57 1023 23.47 1045 26.03 1050 26.99 1070 29.94 1080 30.94 1099 34.32 1113 35.37 1131 39.23 1148 40.33 1166 44.69 — — — — — — — — — — — — — — — — — — — — — — — Bhp 15.75 18.33 21.19 24.38 27.96 31.96 36.44 41.44 — — — — — — Rpm 1013 1029 1046 1066 1090 1118 1149 — — — — — — — 0.2 Rpm 436 486 536 588 639 692 745 798 851 905 959 1013 1067 1121 Bhp 3.79 5.37 7.37 9.81 12.75 16.21 20.24 24.87 30.15 36.10 42.76 50.17 58.36 67.37 1.2 Rpm 626 660 698 739 782 827 872 918 965 1013 1062 1111 1160 — Bhp 6.76 8.50 10.60 13.10 16.05 19.48 23.44 27.99 33.15 38.98 45.50 52.77 60.81 — 2.2 Rpm 782 805 832 864 900 938 979 1020 1064 1108 1153 — — — Bhp 10.14 12.18 14.53 17.27 20.43 24.04 28.17 32.83 38.07 43.95 50.49 — — — 3.2 Rpm 918 934 955 979 1008 1040 1075 1113 1152 — — — — — Bhp 13.64 16.00 18.66 21.67 25.08 28.93 33.27 38.14 43.56 — — — — — LEGEND Bhp — Brake Horsepower 29 1.0 Bhp 6.11 7.80 9.86 12.32 15.23 18.65 22.60 27.14 32.31 38.14 44.69 51.98 60.05 — 2.0 Bhp 9.45 11.42 13.73 16.41 19.52 23.10 27.17 31.81 37.02 42.88 49.41 — — — 3.0 Bhp 12.93 15.23 17.82 20.78 24.14 27.94 32.23 37.05 42.44 — — — — — 4.0 Bhp 16.46 19.11 22.04 25.29 28.92 32.98 37.51 — — — — — — — Table 26 — Supply Fan Motor Limitations (Sizes 030-070) HIGH-EFFICIENCY MOTORS Nominal Maximum Maximum Amps Rated Bhp BkW Bhp BkW 230 v 380 v 460 v 575 v Efficiency 8.7 6.49 22.0 — — — 84.1 7.5 5.60 9.5 7.09 — 15.0 12.0 10.0 88.5 10.2 7.61 28.0 — — — 89.5 10 7.46 11.8 8.80 — 20.7 14.6 12.0 89.5 15.3 11.41 43.8 — — 91.0 15 11.19 18.0 13.43 — 27.0 21.9 19.0 91.0 22.4 16.71 62.0 — — — 91.0 20 14.92 23.4 17.46 — 37.4 28.7 23.0 91.0 28.9 21.56 72.0 — — — 91.7 25 18.65 29.4 21.93 — 43.8 37.4 31.0 91.7 35.6 26.56 95.0 — — — 92.4 30 22.38 34.7 25.89 — N/A 48.0 47.0 92.4 40 29.80 42.0 31.30 N/A N/A 55.0 N/A 93.0 Nominal Bhp BkW 7.5 5.60 10 7.46 15 11.19 20 14.92 25 18.65 30 22.38 40 29.84 PREMIUM-EFFICIENCY MOTORS Maximum Maximum Amps Bhp BkW 230 v 460 v 8.7 6.49 22.0 — 9.5 7.09 — 12.0 10.2 7.61 28.0 — 11.8 8.80 — 15.0 15.3 11.41 43.8 — 18.0 13.43 21.9 22.4 16.71 58.2 — 23.4 17.46 — 28.7 28.9 21.56 73.0 — 29.4 21.93 — 36.3 35.6 26.56 82.6 — 34.7 25.89 — 41.7 42.0 31.33 — 55.0 Rated Efficiency 91.7 91.7 91.7 91.7 93.0 93.0 93.6 93.6 93.6 93.6 93.6 93.6 94.5 LEGEND Bhp — Brake Horsepower BkW — Brake Kilowatts NOTES: 1. Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 2. All motors comply with Energy Policy Act (EPACT) Standards effective October 24, 1997. Table 27 — Supply Fan Motor Limitations (Sizes 075-105) HIGH-EFFICIENCY MOTORS Max Amps Nominal Rated BkW Max Bhp Max BkW HP 460 V 575 V Efficiency 30 22.4 34.7 25.9 48.0 47.0 92.4 40 29.8 42.0 31.3 55.0 48.8 93.0 50 37.3 57.5 42.9 71.0 52.8 93.0 60 44.8 69.0 51.5 82.6 60.5 93.6 75 59.5 86.25 64.3 99.5 N/A 94.1 PREMIUM-EFFICIENCY MOTORS Max Amps Nominal Rated BkW Max Bhp Max BkW HP 460 V 575 V Efficiency 30 22.4 34.7 25.9 48.0 N/A 93.6 40 29.8 42.0 31.3 55.0 N/A 94.5 50 37.3 57.5 42.9 71.0 N/A 94.5 60 44.8 69.0 51.5 75.0 N/A 95.4 75 59.5 86.25 64.3 95.5 N/A 95.4 LEGEND Bhp — Brake Horsepower BkW — Brake Kilowatts NOTES: 1. Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 2. All motors comply with Energy Policy Act (EPACT) Standards effective October 24, 1997. 30 Table 28 — High-Capacity Power Exhaust Systems Motor Limitations (48ZT,ZW and 50ZT,ZW,ZX,ZZ Units) Nominal HP BkW 20 30 40 50 60 14.9 22.4 29.8 37.3 44.8 Nominal HP BkW 20 30 40 50 60 14.9 22.4 29.8 37.3 44.8 HIGH-EFFICIENCY MOTORS Max Amps (ea) Max Max Bhp BkW 460 V 575 V 23.6 17.6 14.6 12.0 36.0 26.9 21.9 19.0 46.8 34.9 28.7 23.0 58.8 43.9 37.4 31.0 69.0 51.5 48.0 47.0 PREMIUM-EFFICIENCY MOTORS Max Amps (ea) Max Max Bhp BkW 460 V 575 V 23.6 17.6 15.0 N/A 36.0 26.9 21.9 N/A 46.8 34.9 28.7 N/A 58.8 43.9 36.3 N/A 69.0 51.5 41.7 N/A Rated Efficiency 89.5 91.0 91.0 91.7 92.4 Rated Efficiency 91.7 93.0 93.6 93.6 93.6 LEGEND Bhp — Brake Horsepower BkW — Brake Kilowatts NOTES: 1. Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown in the Motor Limitations table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 2. All motors comply with Energy Policy Act (EPACT) Standards effective October 24, 1997. Table 29 — Unit Design Airflow Limit UNIT SIZE 030 035 040 050 055 060 070 075 090 105 UNIT TYPE 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN Low Heat 48ZG,ZN High Heat 50ZG,ZN,Z2,Z3 48ZG,ZN,ZT,ZW,Z6,Z8 Low Heat 48ZG,ZN,ZT,ZW,Z6,Z8 High Heat 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9 48ZG,ZN,ZT,ZW,Z6,Z8 Low Heat 48ZG,ZN,ZT,ZW,Z6,Z8 High Heat 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9 48ZG,ZN,ZT,ZW,Z6,Z8 Low Heat 48ZG,ZN,ZT,ZW,Z6,Z8 High Heat 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9 MINIMUM COOLING CFM 6,000 6,000 6,000 7,000 7,000 7,000 8,000 8,000 8,000 9,000 9,000 9,000 10,000 10,000 10,000 12,000 12,000 12,000 14,000 14,000 14,000 15,000 15,000 (VAV) 22,000 (CV) 15,000 (VAV) 22,000 (CV) 17,000 (VAV) 22,000 (CV) 17,000 (VAV) 26,000 (CV) 17,000 (VAV) 26,000 (CV) 20,000 (VAV) 30,000 (CV) 20,000 (VAV) 30,000 (CV) 20,000 (VAV) 30,000 (CV) LEGEND CV — Constant Volume VAV — Variable Air Volume 31 MAXIMUM CFM 15,000 15,000 15,000 15,000 15,000 15,000 20,000 20,000 20,000 20,000 19,500 20,000 25,000 25,000 25,000 30,000 30,000 30,000 30,000 30,000 30,000 30,000 30,000 30,000 34,000 34,000 34,000 44,000 36,500 44,000 Table 30A — Component Pressure Drops (in. wg) (Size 030-050 Units) COMPONENT ECONOMIZER INLET GUIDE VANES FILTERS Pleated (2-in.) Bags With Prefilters* POWER EXHAUST LOW GAS HEAT HIGH GAS HEAT ELECTRIC HEAT† 36 kW 72 kW 108 kW HIGH CAP COIL (040) HIGH CAP COIL (050) 6,000 0.06 0.01 8,000 0.09 0.02 10,000 0.12 0.03 12,000 0.16 0.04 0.01 0.36 0.07 0.04 0.13 0.01 0.38 0.08 0.09 0.21 0.01 0.41 0.09 0.27 0.31 0.02 0.51 0.13 0.45 0.50 0.03 0.03 0.09 0.05 0.03 0.04 0.06 0.12 0.08 0.05 0.07 0.12 0.18 0.12 0.08 0.11 0.18 0.26 0.16 0.11 CFM 14,000 0.21 0.05 16,000 0.25 0.06 18,000 0.29 0.08 20,000 0.35 0.10 0.04 0.64 0.18 0.68 0.73 0.04 0.77 0.24 0.91 1.02 0.03 0.91 0.32 1.17 1.32 0.02 1.01 0.41 1.45 1.64 0.17 0.25 0.34 0.21 0.14 0.25 0.35 0.45 0.27 0.19 0.35 0.46 0.59 0.33 0.23 0.47 0.64 0.78 0.40 0.29 *Bag filter cfm limit is 25,000. †Available on vertical return and discharge units only. Table 30B — Component Pressure Drops (in. wg) (Size 055-070 Units) COMPONENT ECONOMIZER INLET GUIDE VANES FILTERS Pleated (2-in.) Bags With Prefilters* VERTICAL POWER EXHAUST 10,000 0.05 0.01 12,000 0.07 0.02 14,000 0.08 0.03 16,000 0.10 0.04 18,000 0.12 0.05 CFM 20,000 0.14 0.06 22,000 0.16 0.08 24,000 0.19 0.10 26,000 0.21 0.11 28,000 0.24 0.13 30,000 0.26 0.15 0.00 0.45 0.00 0.57 0.00 0.68 0.01 0.80 0.02 0.94 0.03 1.07 0.03 1.23 0.04 1.38 0.04 — 0.05 — 0.05 — 0.38 0.02 0.04 0.06 0.10 0.13 0.17 0.21 0.25 0.29 0.33 HORIZONTAL POWER EXHAUST* 0.12 0.16 0.21 0.27 0.34 0.41 0.49 0.58 0.68 0.78 0.89 LOW GAS HEAT HIGH GAS HEAT ELECTRIC HEAT† 36 kW 72 kW 108 kW HIGH CAP COIL (055) HIGH CAP COIL (060,070) 0.22 0.25 0.24 0.28 0.27 0.30 0.33 0.35 0.33 0.41 0.35 0.47 0.37 0.54 0.41 0.58 0.44 0.68 0.51 0.81 0.61 0.94 0.04 0.05 0.07 0.05 0.03 0.05 0.07 0.09 0.07 0.05 0.07 0.10 0.13 0.09 0.06 0.09 0.13 0.17 0.12 0.08 0.12 0.17 0.22 0.14 0.10 0.15 0.20 0.27 0.17 0.13 0.18 0.24 0.32 0.21 0.15 0.21 0.29 0.38 0.24 0.18 0.24 0.34 0.44 0.28 0.21 0.28 0.39 0.51 0.32 0.25 0.33 0.46 0.59 0.37 0.28 *Bag filter cfm limit is 25,000. †Available on vertical return and discharge units only. Table 30C — Component Pressure Drops (in. wg) (Size 075-105 Units) COMPONENT ECONOMIZER* INLET GUIDE VANES VERTICAL POWER EXHAUST* HORIZONTAL POWER EXHAUST* LOW GAS HEAT HIGH GAS HEAT 108 kW ELECTRIC HEAT† 216 kW ELECTRIC HEAT† 30% PLEATED FILTER 65% PLEATED FILTER HIGH CAP COIL (075) HIGH CAP COIL (090,105) 15,000 0.10 0.04 0.08 0.24 0.09 0.27 0.05 0.08 0.01 0.14 0.08 0.01 18,000 0.12 0.05 0.13 0.34 0.14 0.37 0.07 0.12 0.01 0.14 0.11 0.02 20,000 0.14 0.06 0.17 0.41 0.19 0.46 0.09 0.14 0.01 0.15 0.13 0.03 22,000 0.16 0.08 0.21 0.49 0.23 0.55 0.11 0.17 0.02 0.15 0.15 0.04 *The 48ZT,ZW and 50ZT,ZW,ZX,ZZ units come standard with economizer and high-capacity power exhaust. †Available on vertical return and discharge units only. 24,000 0.19 0.10 0.25 0.58 0.29 0.65 0.13 0.20 0.02 0.16 0.18 0.05 CFM 26,000 28,000 0.21 0.23 0.11 0.13 0.29 0.33 0.68 0.78 0.35 0.42 0.77 0.89 0.15 0.17 0.24 0.28 0.03 0.03 0.16 0.17 0.21 0.23 0.07 0.08 30,000 0.26 0.15 0.38 0.89 0.49 1.03 0.20 0.32 0.04 0.17 0.26 0.10 34,000 0.31 0.20 0.46 1.13 0.67 1.33 0.26 0.41 0.05 0.18 0.33 0.14 36,000 0.34 0.22 0.51 1.26 0.76 1.50 0.29 0.46 0.06 0.19 0.36 0.16 38,000 0.37 0.24 0.55 1.40 0.86 1.68 0.32 0.51 0.06 0.20 0.40 0.19 40,000 0.40 0.27 0.60 1.55 0.97 1.87 0.36 0.57 0.07 0.20 0.43 0.21 NOTE: Power exhaust pressure drop does not need to be added to supply fan static pressure on return fan units (48Z6,Z8 and 50Z6,Z7,Z8,Z9075-105) and on high-capacity power exhaust units (48ZT,ZW and 50ZT,ZW,ZX,ZZ075-105). 32 10. See Economizer Options section on page 34 for additional economizer option configurations. 11. See Exhaust Options section on page 34 for additional exhaust option configurations. CONTROLS QUICK START The following section will provide a quick user guide to setting up and configuring the Z Series units with ComfortLink™ controls. See Basic Control Usage section on page 4 for information on operating the control. Variable Air Volume Units Using Return Air Sensor or Space Temperature Sensor — To Two-Stage Constant Volume Units with Mechanical Thermostat — To configure the unit, per- configure the unit, perform the following: 1. The type of control is configured under Configuration →UNIT→C.TYP. Set C.TYP to 1 (VAV-RAT) for return air sensor. Set C.TYP to 2 (VAV-SPT) for space temperature sensor. NOTE: For VAV with a space sensor (VAV-SPT), under Configuration→UNIT→SENS→SPT.S, enable the space sensor by setting SPT.S to ENBL. 2. The space temperature set points and the supply air set points are configured under the Setpoints menu. The heating and cooling set points must be configured. See the Heating Control and Cooling Control sections for further description on these configurations. Configure the following set points: form the following: 1. The type of control is configured under Configuration →UNIT→C.TYP. Set C.TYP to 4 (TSTAT 2 STG). 2. Remove jumpers from R-W2 and W2-W1 on TB202 in the control box. 3. See Economizer Options section on page 34 for additional economizer option configurations. 4. See Exhaust Options section on page 34 for additional exhaust option configurations. Two-Stage Constant Volume Units with Space Sensor — To configure the unit, perform the following: 1. The type of control is configured under Configuration →UNIT→C.TYP. Set C.TYP to 6 (SPT 2 STG). 2. Under Configuration→SENS→SPT.S, enable the space sensor by setting SPT.S to ENBL (enable). 3. The space temperature set points are configured under the Setpoints menu. The heating and cooling set points must be configured. See the Heating Control and Cooling Control sections on pages 54 and 45 for further description on these configurations. Configure the following set points: OHSP OCSP UHSP UCSP GAP 3. To program time schedules, make sure SCH.N=1 under Configuration→CCN→SC.OV→SCH.N to configure the control to use local schedules. 4. Under the Timeclock→SCH.L submenu, enter the desired schedule. See Time Clock section for further descriptions of these configurations. 5. Under Configuration→SP→SP.SP, the Supply Duct Static Pressure set point should be configured. OHSP Occupied Heat Setpoint OCSP Occupied Cool Setpoint UHSP Unoccupied Heat Setpoint UCSP Unoccupied Cool Setpoint GAP Heat-Cool Setpoint Gap 4. The degrees of demand from the space temperature set points are configured under the Configuration→D.LV.T submenu. See the Heating Control and Cooling Control sections for further description on these configurations. Configure the following set points: 5. 6. 7. 8. 9. SP.SP Static Pressure Set point 6. If supply air temperature reset is desired, under the Configuration→EDT.R submenu, the following set points should be configured: RS.CF RTIO LIMT RES.S L.H.ON Demand Level Lo Heat On H.H.ON Demand Level Hi Heat On L.H.OF Demand Level Lo Heat Off L.C.ON Demand Level Lo Cool On H.C.ON Demand Level Hi Cool On L.C.OF Demand Level Lo Cool Off Install jumpers between R-W2 and W2-W1. Under Configuration→UNIT→CV.FN, set CV.FN to 1 for continuous fan or 0 for automatic fan. To program time schedules, set SCH.N=1 under Configuration→CCN→SC.OV→SCH.N to configure the control to use local schedules. Under the Timeclock→SCH.L submenu, enter the desired schedule. See Time Clock section for further descriptions of these configurations. Under the Configuration→CCN→SC.OV submenu, the following schedules and overrides should be configured: O.T.L. SPT.O T58.O Occupied Heat Set point Occupied Cool Set point Unoccupied Heat Set point Unoccupied Cool Set point Heat-Cool Set point Gap EDT Reset Configuration Reset Ratio Reset Limit EDT 4-20 mA Reset Input NOTE: Configure either RTIO and LIMT or RES.S. All three are not used. 7. See the Economizer Options section on page 34 for additional economizer option configurations. 8. See the Exhaust Options section on page 34 for addition exhaust option configurations. Multi-Stage Constant Volume Units with Mechanical Thermostat — To configure the unit, per- form the following: 1. Under Configuration→UNIT→C.TYP, set C.TYP to 3 (TSTAT MULTI). 2. Remove jumpers from R-W2 and W2-W1 on TB202 in the control box. 3. Under the Setpoints menu, set the following configurations: Override time limit SPT override enabled? T58 override enabled? SA.HI SA.LO 33 Supply Air Set Point Hi Supply Air Set Point Lo 4. See the Economizer Options section on this page for additional economizer option configurations. 5. See the Exhaust Options section on this page for additional exhaust option configurations. O.C.MX Economizer Minimum Flow O.C.DB Economizer Minimum Flow Deadband If equipped with an outdoor flow station, make sure Configuration→ECON→OCF.S is enabled. If an outdoor air cfm station is used, then the economizer will control to cfm, not a position, as long as the sensor is valid. Therefore, Configuration→ECON→O.C.MX supersedes Configuration→ECON→EC.MN. Multi-Stage Constant Volume Units with Space Sensor — To configure the unit, perform the following: 1. Under Configuration→UNIT→C.TYP, set C.TYP to 5 (SPT MULTI). 2. Install jumpers between R-W2 and W2-W1. 3. Under the Setpoints menu, the following configurations should be set: SA.HI SA.LO Indoor Air Quality Options DEMAND CONTROL VENTILATION — Under Configuration→IAQ→DCV.C, the following configuration parameters should be set to establish the minimum and maximum points for outdoor air damper position during demand control ventilation (DCV): EC.MN Economizer Min.Position IAQ.M IAQ Demand Vent Min.Pos. O.C.MX Economizer Min.Flow O.C.MN IAQ Demand Vent Min.Flow Configuration→IAQ→DCV.C→IAQ.M is used to set the absolute minimum vent position (or maximum reset) under DCV. Configuration→IAQ→DCV.C→EC.MN is used to set the minimum damper position (or with no DCV reset). This is also referenced in the economizer section. Configuration→IAQ→DCV.C→O.C.MX is used only with the outdoor air flow station and will supersede Configuration→IAQ→DCV.C→EC.MN as long as the outdoor air cfm sensor is valid. Configuration→IAQ→DCV.C→O.C.MN is used only with the outdoor air flow station and will supersede Configuration→IAQ→DCV.C→IAQ.M as long as the outdoor air cfm sensor is valid. Supply Air Set Point Hi Supply Air Set Point Lo 4. Under the Setpoints submenu, the heating and cooling set points must be configured: OHSP OCSP UHSP UCSP GAP D.LV.T Occupied Heat Setpoint Occupied Cool Setpoint Unoccupied Heat Setpoint Unoccupied Cool Setpoint Heat-Cool Setpoint Gap Cool/Heat Set Point Offsets 5. Under Configuration→UNIT→SENS→SPT.S, enable the space sensor by setting SPT.S to ENBL. 6. Under Configuration→UNIT→CV.FN, set CV.FN to 1 for continuous fan or 0 for automatic fan. 7. To program time schedules, set SCH.N=1 under Configuration→CCN→SC.OV→SCH.N to configure the control to use local schedules. 8. Under the Timeclock→SCH.L submenu, enter the desired schedule. See Time Clock section for further descriptions of these configurations. 9. See the Economizer Options section below for addition economizer option configurations. 10. See the Exhaust Options section below for addition exhaust option configurations. Exhaust Options — The following exhaust options should be configured. UNIT Economizer Options — Under the Configuration→ 48ZG 50ZG,Z2 48ZN 50ZN,Z3 48ZT,ZW 50ZT,ZW,ZX,ZZ 48Z6,Z8 50Z6,Z7,Z8,Z9 ECON submenu, the following set points should be configured: EC.EN EC2.E EC.MN EC.MX E.TRM E.SEL OA.E.C OA.EN OAT.L O.DEW ORH.S Economizer Enabled? Econ Act.2 Installed? Economizer Min.Position Economizer Maximum Position Economizer Trim for SumZ? Econ Changeover Select OA Enthalpy Change Over Select Outdoor Enthalpy Compare Value High OAT Lockout Temp OA Dew Point Temp Limit Outside Air RH Sensor X S.O. NA STD X X S.O. NA NA NA X S.O. NA NA NA NA NA STD NA NA NA NA NA STD LEGEND Available as Factory Option Available as Special Order Not Available on this Unit Standard Feature on this Unit *Single VFD controlling both fan motors. †Single VFD controlling one fan motor and staging the second fan motor. Configuration→BP→BF.CF=1 (Two-Stage Exhaust Option) — For two-stage exhaust, under the Configuration→BP submenu, configure the following: Configuration→ECON→EC.MN should always be set for the minimum damper position. If the unit is equipped with an outdoor air flow station, the following points in Configuration→ECON→CFM.C need to be set. OCF.S — — — — EXHAUST TYPE HighConstant Modulating S.O. Capacity Return Volume Power VFD* Power Exhaust† 2-Stage Exhaust Exhaust† BP.P1 BP.P2 Outdoor Air CFM Sensor 34 Power Exhaust On Setp.1 Power Exhaust On Setp.2 Configuration→BP→BF.CF=2 (Modulating Power Exhaust with Two LEN Actuators Option) — For modulating exhaust, the Configuration→BP submenu, configure the following: BP.SP BP.SO FT.OF Fan Track Internl EEPROM (see note below, not used when Fan Track Learning is disabled) FT.RM Fan Track Internal Ram (see note below, not used when Fan Track Learning is disabled) FT.RS Fan Track Reset Internal (see note below, not used when Fan Track Learning is disabled) SCF.C Supply Air CFM Config (see note below, not used when Fan Track Learning is disabled) NOTE: These configurations are used only if Fan Tracking learning is enabled. When fan tracking learning is enabled, the control will add an offset to the Fan Track Initial DCFM (Configuration→BP→FAN.T→FT.ST) if the building pressure deviates from the Building Pressure Set Point (BP.SP). Periodically, at the rate set by the Fan Track Learn Rate (FT.TM) the delta cfm is adjusted upward or downward with a maximum adjustment at a given instance to be no greater than Fan Track Max correction (FT.AD). The delta cfm can not ever be adjusted greater than or less than the Fan Track Max Clamp (FT.MX). Building Pressure Set point BP Set point Offset Under Configuration→BP→B.V.A the following configurations may be adjusted: BP.FS VFD/Act. Fire Speed/Pos. BP.MN VFD/Act. Min. Speed/Pos. BP.1M BP 1 Actuator Max Pos. BP.2M BP 2 Actuator Max Pos. Configuration→BP→BP.CF=3 (VFD Power Exhaust Option) — Under Configuration→BP the following configurations may be adjusted: BP.SP BP.SO Building Pressure Set point BP Set point Offset Set Clock on VFD (If Installed) — The clock set mode is used for setting the date and time for the internal clock of the VFD. In order to use the timer functions of the VFD control, the internal clock must be set. The date is used to determine weekdays and is visible in the fault logs. Refer to the VFD section in Appendix D on page 160 for information on operating the VFD and using the keypad. To set the clock, perform the following procedure from the VFD keypad: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight CLOCK SET on the display screen and press ENTER (SOFT KEY 2). The clock set parameter list will be displayed. 3. Use the UP or DOWN keys to highlight CLOCK VISIBILITY and press SEL (SOFT KEY 2). This parameter is used to display or hide the clock on the screen. Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 4. Use the UP or DOWN keys to highlight SET TIME and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the hours and minutes. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 6. Use the UP or DOWN keys to highlight SET DATE and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the day, month, and year. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 7. Use the UP or DOWN keys to highlight DATE FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 8. Press EXIT (SOFT KEY 1) twice to return to the main menu. Under Configuration→BP→B.V.A the following configurations may be adjusted: BP.FS VFD/Act. Fire Speed/Pos. BP.MN VFD/Act. Min. Speed/Pos. BP.MX VFD Maximum Speed Configuration→BP→BP.CF=4 (High-Capacity VFD Power Exhaust) — Under Configuration→BP the following configurations may be adjusted: BP.SP BP.SO Building Pressure Set point BP Set point Offset Under Configuration→BP→B.V.A the following configurations may be adjusted: BP.FS VFD/Act. Fire Speed/Pos. BP.MN VFD/Act. Min. Speed/Pos. BP.MX VFD Maximum Speed BP.CL BP Hi Cap VFD Clamp Val. BP.WT BP Hi Cap VFD Clamp Time Configuration→BP→BP.CF=5 (Return/Exhaust — Fan Tracking Control) — Under Configuration → BP the following configurations may be adjusted: BP.SP Building Pressure Setpt. (see note below) Under Configuration→BP→B.V.A the following configurations may be adjusted: BP.FS VFD/Act. Fire Speed/Pos. BP.MN VFD/Act. Min. Speed/Pos. BP.MX VFD Maximum Speed Under Configuration→BP→FAN.T the following configurations may be adjusted: FT.CF Fan Track Learn Enable (see note below) FT.TM Fan Track Learn Rate (see note below, not used when Fan Track Learning is disabled) FT.ST Fan Track Initial DCFM FT.MX Fan Track Max Clamp (see note below, not used when Fan Track Learning is disabled) FT.AD Fan Track Max Correction (see note below, not used when Fan Track Learning is disabled) 35 same procedure to display and save the desired minutes value. 5. Configure the unoccupied time for period 1 (UNC). Press ENTER to go into Edit mode, and the first two digits of the 00.00 will start flashing. Use the UP or DOWN key to display the correct value for hours, in 24-hour (military) time. Press ENTER and hour value is saved and the minutes digits will start flashing. Use the same procedure to display and save the desired minutes value. 6. The first schedule is now complete. If a second schedule is needed, such as for weekends or holidays, scroll down and repeat the entire procedure for period 2 (PER.2). If additional schedules are needed, repeat the process for as many as are needed. Eight schedules are provided. Programming Operating Schedules — The ComfortLink™ controls will accommodate up to eight different schedules (Periods 1 through 8), and each schedule is assigned to the desired days of the week. Each schedule includes an occupied on and off time. As an example, to set an occupied schedule for 8 AM to 5 PM for Monday through Friday, the user would set days Monday through Friday to ON for Period 1. Then the user would configure the Period 1 Occupied From point to 08:00 and the Period 1 Occupied To point to 17:00. To create a different weekend schedule, the user would use Period 2 and set days Saturday and Sunday to ON with the desired Occupied On and Off times. NOTE: By default, the time schedule periods are programmed for 24 hours of occupied operation. To create a schedule, perform the following procedure: 1. Scroll to the Configuration mode, and select CCN CONFIGURATION (CCN). Scroll down to the Schedule Number (Configuration→CCN→SC.OV=SCH.N). If password protection has been enabled, the user will be prompted to enter the password before any new data is accepted. SCH.N has a range of 0 to 99. The default value is 1. A value of 0 is always occupied, and the unit will control to its occupied set points. A value of 1 means the unit will follow a local schedule, and a value of 65 to 99 means it will follow a CCN schedule. Schedules 2-64 are not used as the control only supports one internal/local schedule. If one of the 2-64 schedules is configured, then the control will force the number back to 1. Make sure the value is set to 1 to use a local schedule. 2. Enter the Time Clock mode. Scroll down to the LOCAL TIME SCHEDULE (SCH.L) sub-mode, and press ENTER. Period 1 (PER.1) will be displayed. 3. Scroll down to the MON point. This point indicates if schedule 1 applies to Monday. Use the ENTER command to go into Edit mode, and use the UP or DOWN key to change the display to YES or NO. Scroll down through the rest of the days and apply schedule 1 where desired. The schedule can also be applied to a holiday. 4. Configure the beginning of the occupied time period for Period 1 (OCC). Press ENTER to go into Edit mode, and the first two digits of the 00.00 will start flashing. Use the UP or DOWN key to display the correct value for hours, in 24-hour (military) time. Press ENTER and hour value is saved and the minutes digits will start flashing. Use the SERVICE TEST General — The units are equipped with a Service Test fea- ture, which is intended to allow a service person to force the unit into different modes of operation. To use this feature, enter the Service Test category on the local display and place the unit into the test mode by changing Service Test→TEST from OFF to ON. The display will prompt for the password before allowing any change. The deffault password is 1111. Once the unit enters the Service Test mode, the unit will shut down all current modes. TEST — The TEST command turns the unit off (hard stop) and allows the unit to be put in a manual control mode. STOP — The STOP command completely disables the unit (all outputs turn off immediately). Once in this mode, nothing can override the unit to turn it on. The controller will ignore all inputs and commands. S.STP — Setting Soft Stop to YES turns the unit off in an orderly way, honoring any timeguards currently in effect. FAN.F — By turning the FAN FORCE on, the supply fan is turned on and will operate as it normally would, controlling duct static pressure on VAV applications or just energizing the fan on CV applications. To remove the force, press ENTER and then press the UP and DOWN arrows simultaneously. The remaining categories: INDP, FANS, ACT.C, COOL, and HEAT are sub-menus with separate items and functions. See Table 31. 36 Table 31 — Service Test ITEM TEST STOP S.STP FAN.F INDP →HUM.R →ALRM FANS →F.MOD →E.POS →S.FAN →I.POS →S.VFD →P.E.1 →P.E.2 →BP1.P →BP2.P →E.VFD →CD.F.A →CD.F.B →CD.MM ACT.C →ECN.C →E.CAL →ECN.A →EC2.C →E2.CL →EC2.A →IGV.C →I.CAL →IGV.A →IGV.M →BP1.C →B1.CL →BP1.A →BP1.M →BP2.C →B2.CL →BP2.A →BP2.M →HTC.C →HT.CL →HTC.A →HMD.C →HM.CL →HMD.A COOL →E.POS →SP.SP →CL.ST →LD.LG →A1 →U1.A1 →U2.A1 →A2 →B1 →U1.B1 →U2.B1 →B2 HEAT →HT.ST →HT.1 →HT.2 →HT.3 →HT.4 →HT.5 →HT.6 →H.I.R →HTC.C EXPANSION Service Test Mode Local Machine Disable Soft Stop Request Supply Fan Request TEST INDEPENDENT OUTPUTS Humidifier Relay Remote Alarm/Aux Relay TEST FANS Fan Test Automatic? Econo Damper Command Pos Supply Fan Relay IGV Actuator Command Pos Supply Fan VFD Speed Power Exhaust Relay 1 Power Exhaust Relay 2 BP 1 Command Position BP 2 Command Position Exhaust Fan VFD Speed Condenser Fan Circuit A Condenser Fan Circuit B Motormaster Condenser Fan CALIBRATE TEST-ACTUATORS Economizer Act.Cmd.Pos. Economizer Calibrate Cmd Econ Act. Control Angle Economzr 2 Act.Cmd.Pos. Economzr 2 Calibrate Cmd Econ2 Act.Control Angle IGV Actuator Command Pos IGV Act. Calibrate Cnd IGV Act. Control Angle VFD-IGV Maximum Speed BP 1 Command Position BP 1 Actuator Cal Cmd BP Act.1 Control Angle BP 1 Actuator Max Pos. BP 2 Command Position BP 2 Actuator Cal Cmd BP Act.2 Control Angle BP 2 Actuator Max Pos. Ht.Coil Command Position Heating Coil Act. Cal.Cmd Heat Coil Act.Ctl.Angle Humidifier Command Pos. Humidifier Act. Cal.Cmd Humidifier Act.Ctrl.Ang. TEST COOLING Econo Damper Command Pos Static Pressure Setpoint Requested Cool Stage Lead/Lag Select Test Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay TEST HEATING Requested Heat Stage Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay Ht.Coil Command Position RANGE ON/OFF YES/NO YES/NO YES/NO UNITS ON/OFF ON/OFF HUMR_TST ALRM_TST YES/NO % ON/OFF 0-100 0-100 ON/OFF ON/OFF 0-100 0-100 0-100 ON/OFF ON/OFF ON/OFF 0-100 YES/NO read only 0-100 YES/NO read only 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 YES/NO read only 0-100 0-5 0-n LEAD/LAG ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-n ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-100 37 POINT MAN_CTRL UNITSTOP SOFTSTOP SFANFORC % % % % % % % % % % % % % % % % "H2O % FANAUTO ECONFANS SFAN_TST IGVFNTST SGVFDTST PE1_TST PE2_TST BLDPTST1 BLDPTST2 EFVFDTST CNDA_TST CNDB_TST PCFABTST ECONOTST ECONOCAL ECONCANG ECON2TST ECON2CAL ECN2CANG SPIGVTST IGV_CAL IGC_CANG STATPMAX BLDG1TST BLDG1CAL BP1_CANG BP1SETMX BLDG2TST BLDG2CAL BP2_CANG BP2SETMX HTCLACTC HCOILCAL HTCLCANG HUMD_TST HUMIDCAL HUMDCANG ECONCOOL SPSP_TST CLST_TST LL_TST CMPA1TST UNL1_TST UNL2_TST CMPA2TST CMPB1TST UNL3_TST UNL4_TST CMPB2TST HTST_TST HS1_TST HS2_TST HS3_TST HS4_TST HS5_TST HS6_TST HIR_TST HTCLHEAT WRITE STATUS config forcible forcible • Service Test→COOL→SP.SP (Static Pressure Setpoint). Upon entering the cooling sub-menu, the static pressure control item will default to the unit's static pressure set point. Thereafter, as mechanical cooling commences and the fan starts, the static pressure can be manually adjusted during the cool mode without affecting the configured set point for normal runtime operation. By adjusting the static pressure set point, the user can increase or decrease the supply airflow. Do not use a static pressure that will exceed the system limits. • Service Test→COOL→CL.ST (Requested Cool Stage). If this item is set to a non-zero value, the current assigned compression stage for this unit will be selected and enacted. Thereafter, the individual compressor and unloaders items will be “read-only” and reflect the current staging state. In addition, this item will automatically clamp the cooling stages to its pre-configured maximum. • Service Test→COOL→LD.LG (Lead/Lag Select Test). This item may only be adjusted when the cooling stage pattern request item is set to zero. If the request pattern is zero, then the user may select whether the cooling stage request is based on lead or lag staging. • Manual relay control of individual compressors and unloaders. If the cooling stage pattern request is set to zero, the user will have the ability to manually control compressors and unloaders. If the user energizes mechanical cooling, the supply fan and the outdoor fans will be started automatically. During mechanical cooling, the unit will protect itself. Compressor diagnostics are active, monitoring for high discharge pressure, low suction pressure, etc. Service Test Mode Logic — Operation in the Service Test mode is sub-menu specific except for the INDP submenu. Leaving the sub-menu while a test is being performed and attempting to start a different test in the new sub-menu will cause the previous test to terminate. When this happens, the new request will be delayed for 5 seconds. For example, if compressors were turned on under the COOL sub-menu, any attempt to turn on heating stages within the HEAT sub-menu would immediately turn off the compressors and 5 seconds later the controller would honor the requested heat stages. However, it is important to note that the user can leave a Service Test mode to view any of the local display menus (Run Status, Temperatures, Pressures, Setpoints, Inputs, Outputs, Configuration, Time Clock, Operating Modes, and Alarms) and the control will remain in the Service Test mode. Independent Outputs — The INDP sub-menu items can be turned on and off regardless of the other category states. For example, the humidifier relay or remote alarm/auxiliary relay can be forced on in the INDP sub-menu and will remain on if compressor stages were requested in the COOL sub-menu. Fans — Upon entering the FANS sub-menu, the user will be able to enact either a manual or automatic style of test operation. The first item in the sub-menu, Fan Test Mode Automatic (Service Test→FANS→F.MOD), allows the fan and the configured static pressure or building pressure control to begin as in the application run mode. During this automatic mode, it is possible to manually control condenser fans A and B. If Fan Test Mode Automatic (Service Test→FANS→ F.MOD), is set to NO, then the user will have individual control over duct static pressure (VFD speed or IGV position), building pressure and condenser fan control. Additionally, the controller will protect the system from developing too much static pressure. If the static pressure during manual control rises above 3 in. wg or if the Static Pressure Set Point (Setpoints→SPSP) is greater than 2.5 in. wg and static pressure is 0.5 in. wg higher than SPSP, then all options in the FANS menu will be cleared back to their default OFF states. The power exhaust dampers can be individually energized or together and their damper positions can be forced to any position. Heating — If unit has a thermostat connected (C.TYP = 3 or 4), install the RED jumper wires between TB202, terminals R (1), W2 (3) and W1 (4). Terminal block TB202 is located in the unit control box. Remember to disconnect these jumpers when Test Mode is completed. The Heat Test Mode sub-menu will offer automatic fan start-up if not a gas fired heat unit. On gas heat units, the IGC feedback from the gas control units will bring the fan on as required. Within this sub-menu, control of the following is possible: • Service Test→HEAT→HT.ST (Requested Heat Stage). When this item is non-zero, the currently configured heat type will energize the corresponding heat relay pattern that reflects the requested stage. In addition the upper limit will be clamped to reflect the maximum configured number of stages. When non-zero, the heat relays will be “read-only” and reflect the currently selected pattern. • Service Test→HEAT→HT.1-6, Service Test→HEAT→ H.I.R (Manual Heat Relay Control). If the “Heat Stage Request” item is set to zero, it will be possible to individually control the heat relays, including the heat interlock relay. • Service Test→HEAT→HTC.C (Ht Coil Command Position). If configured for this heat type, the user will be able to manually control the positioning of the actuator which controls hot water (0 to 100%). NOTE: When service test has been completed, if unit has a thermostat connected (C.TYP = 3 or 4), remove the RED jumper wires at TB202, terminals R (1), W2 (3) and W1 (4). Terminal block TB202 is located in the unit control box. Store these jumpers in the unit control box for future use. Actuators — In the ACT.C sub-menu, it will be possible to control and calibrate actuators. Calibration is a mode in which the actuator moves from 0% to the point at which the actuator stalls, and it will then use this angular travel range as its “control angle”. It will also be possible to view the “control angle” adopted by the actuator after a calibration. Within this sub-menu, the user may calibrate and control economizer actuators 1 and 2, the inlet guide vane actuator, the building pressure actuators 1 and 2, the hydronic heating coil actuator, and the humidifier steam valve control actuator. NOTE: Once a calibration has been started, the user cannot exit test mode or select any other test mode operation until complete. Cooling — The cooling sub-menu offers many different service tests. • Service Test→Cool→E.POS (Econo Damper Command Pos). It is possible to manually move the actuator during the cooling test mode at all times, regardless if economizer cooling is suitable or not. 38 In either case, it will be necessary to install a controls expansion module (CEM). DEMAND LIMIT DISCRETE INPUTS — First, set DM.L.S in Configuration→DMD.L to 1 (2 switches). When Inputs→GEN.I→DL.S1 (Demand Switch no. 1) is OFF, the control will not set any limit to the capacity, and when ON, the control sets a capacity limit to the Configuration→DMD.L→D.L.S1 set point. Likewise, when Inputs→GEN.I→DL.S2 (Demand Switch no. 2) is OFF, the control will not set any limit to the capacity, and when ON, the control sets a capacity limit to the Configuration→DMD.L→D.L.S2 set point. If both switches are ON, Inputs→GEN.I→DL.S2 is used as the limiter of capacity. Under Configuration→SW.LG, set the logic state appropriately for the action desired. Set the DL1.L and DL2.L configurations. They can be set normally open or normally closed. For example, if DL1.L is set to OPEN, the user will need to close the switch to cause the control to limit capacity to the demand limit 1 set point. Likewise, if DL1.L is set to CLSE (closed), the user will need to open the switch to cause the control to limit capacity to the demand limit 1 set point. DEMAND LIMIT 4 TO 20 mA INPUT — Under Configuration→DMD.L, set configuration DM.L.S to 2 (2 = 4 to 20 mA control). Under the same menu, set D.L.20 to a value from 0 to 100 to set the demand limit range. For example, with D.L.20 set to 50, a 4 mA signal will result in no limit to the capacity and 20 mA signal will result in a 50% reduction in capacity. THIRD PARTY CONTROL Thermostat — The method of control would be through the thermostat inputs: Y1 = first stage cooling Y1 and Y2 = first and second stage cooling W1 = first stage heating W1 and W2 = first and second stage heating G = supply fan Alarm Output — The alarm output (not available when the unit is configured for hot gas reheat), TB201-12 and TB201-11, will provide relay closure whenever the unit is under an alert or alarm condition. Remote Switch — The remote switch may be configured for three different functions. Under Configuration→UNIT, set RM.CF to one of the following: 0 = no remote switch 1 = occupied/unoccupied switch 2 = start/stop switch 3 = occupancy override switch Under Configuration→SW.LG, RMI.L, the remote occupancy switch can be set to either a normally open or normally closed switch input. Normal is defined as either unoccupied, start or “not currently overridden,” respective to the RM.CF configuration. With RM.CF set to 1, no time schedules are followed and the unit follows the remote switch only in determining the state of occupancy. With RM.CF set to 2, the remote switch can be used to shut down and disable the unit, while still honoring timeguards on compressors. Time schedules, internal or external, may be run simultaneously with this configuration. With RM.CF set to 3, the remote input may override an unoccupied state and force the control to go occupied mode. As with the start/stop configuration, an internal or external time schedule may continue to control occupancy when the switch is not in effect. Economizer/Outdoor Air Damper Control — There are multiple methods for externally controlling the economizer damper. IAQ DISCRETE INPUT CONFIGURATION — The IAQ (indoor air quality) discrete input configuration requires a CEM module (optional) to be installed and an interface to a switch input at TB204-11 and TB204-12. The state of the input on the display can be found at Inputs→AIR.Q→IAQ.I. Before configuring the switch functionality, first determine how the switch will be read. A closed switch can indicate either a low IAQ condition or a high IAQ condition. This is set at Configuration→SW.LG and IAQ.L. The user can set what a low reading would mean based on the type of switch being used. Setting IAQ.L to OPEN means that when the switch is open the input will read LOW. When the switch is closed, the input will read HIGH. Setting IAQ.L to CLSE (closed) means that when the switch is closed the input will read LOW, and therefore, when the switch is open the switch will read HIGH. There are two possible configurations for the IAQ discrete input. Select item Configuration→IAQ→AQ.CF→IQ.I.C and configure for either 1 (IAQ Discrete) or 2 (IAQ Discrete Override). IQ.I.C = 1 (IAQ Discrete) — If the user sets IQ.I.C to 1 (IAQ Discrete), and the switch logic (Configuration→SW.LG→ IAQ.L) is set to OPEN, then an open switch reads low and a closed switch reads high. If the switch is open, the economizer will be commanded to the IAQ Demand Vent Minimum Position. If the outdoor flow station is installed and outdoor air cfm can be read, the economizer will move to the IAQ Demand Vent Minimum Flow CFM control setting. These settings may be adjusted and are located here: Configuration→IAQ→DCV.C→IAQ.M Configuration→IAQ→DCV.C→O.C.MN VFD Control — On VFD equipped supply fans, supply duct static pressure control may be left under unit control or be externally controlled. To control a VFD externally with a 4 to 20 mA signal, set SP.CF to 0, under the Configuration→SP menu. This will disable the ComfortLink™ controls from varying the VFD speed in response to duct pressure with its 4 to 20 mA output. See Appendix D and the VFD literature supplied with the unit for VFD configurations and field wiring connections to the VFD. Supply Air Reset — With the installation of the Control Expansion Module (CEM), the ComfortLink controls are capable of accepting a 4 to 20 mA signal, to reset the supply-air temperature up to a maximum of 20 F. Under Configuration→EDT.R set RS.CF to 3 (external 4 to 20 mA supply air reset control). The 4 to 20 mA input to the control system (TB203-4 and TB203-5), will be linearized and range from 0º to 20 F. For example, 4 mA = 0º F reset, 12 mA = 10º F reset and 20 mA = 20º F reset. Demand Limit Control — The term Demand Limit Control refers to the restriction of the machine’s mechanical cooling capacity to control the amount of power that a machine may use. Demand Limiting is possible via two means: Two discrete inputs tied to demand limit set point percentages. OR A 4 to 20 mA input that can reduce or limit capacity linearly to a set point percentage. 39 If the switch is closed, the IAQ reading will be high and the economizer will be commanded to the Economizer Minimum Position. If the outdoor airflow station is installed and outdoor air cfm can be read, the economizer will move to the Economizer Minimum Flow CFM control setting. These settings may be adjusted and are located here: Configuration→IAQ→DCV.C→EC.MN Configuration→IAQ→DCV.C→O.C.MX IQ.I.C = 2 (IAQ Discrete Override) — If the user sets IQ.I.C to 2 (IAQ Discrete Override), and Configuration→SW.LG→ IAQ.L is set to OPEN, then an open switch reads low and a closed switch reads high. If the switch reads low, no action will be taken. If the switch reads high, the economizer will immediately be commanded to the IAQ Economizer Override Position. This can be set from 0 to 100% and can be found at Configuration→IAQ→AQ.SP→ IQ.O.P. FAN CONTROL FOR THE IAQ DISCRETE INPUT — Under Configuration→IAQ→AQ.CF, the IQ.I.F (IAQ Discrete Input Fan Configuration) must also be set. There are three configurations for IQ.I.F. Select the configuration which will be used for fan operation. This configuration allows the user to decide (if the supply fan is not already running), whether the IAQ discrete switch will start the fan, and in which state of occupancy the fan will start. IQ.I.F = 0 IQ.I.F = 1 IQ.I.F = 2 on the differential air quality (DAQ). If DAQ rises above D.F.ON, the control will request the fan on until DAQ falls below D.F.OF. NOTE: If D.F.ON is configured below DAQ.H, the unit is in occupied mode, and the fan was off, then DAQ rose above D.F.ON and the fan came on, the economizer will go to the economizer minimum position (EC.MN). The 4 to 20 mA signal from the sensor wired to TB12 and TB11 is scaled to an equivalent indoor CO2 (IAQ) by the parameters IQ.R.L and IQ.R.H located under the Configuration→IAQ→AQ.SR menu. The parameters are defined such that 4 mA = IQ.R.L and 20 mA = IQ.R.H. When the differential air quality DAQ (IAQ – OAQ.U) exceeds the DAQ.H set point (Configuration→IAQ→AQ.SP menu) and the supply fan is on, the economizer minimum vent position (Configuration→IAQ→DCV.C→EC.MN) is overridden and the damper is moved to the IQ.P.O configuration. When the DAQ falls below the DAQ.L set point (Configuration→IAQ→AQ.SP menu), the economizer damper is moved back to the minimum vent position (EC.MN). NOTE: Configuration OAQ.U is used in the calculation of the trip point for override and can be found under Configuration→ IAQ→AQ.SP. IQ.A.C = 3 (4 to 20 mA Damper Control) — This configuration will provide full 4 to 20 mA remotely controlled analog input for economizer minimum damper position. The 4 to 20 mA signal is connected to terminals TB12 and TB11. The input is processed as 4 mA = 0% and 20 mA = 100%, thereby giving complete range control of the effective minimum position. The economizer sequences can be disabled by removing the enthalpy switch input at TB201-4 and not enabling any other economizer changeover sequence at Configuration→ ECON→E.SEL. Complete control of the economizer damper position is then possible by using a 4 to 20 mA economizer minimum position control or a 0 to 10 kilo-ohm 0 to 100% economizer minimum position control via configuration decisions at Configuration→IAQ→IQ.A.C. To disable the standard enthalpy control input function, remove the enthalpy switch input connection at TB201-4 and provide a jumper from TB201-3 to TB201-4 (see wiring diagrams in Major System Components section on page 102). IQ.A.C = 4 (10 Kohm Potentiometer Damper Control) — This configuration will provide input for a 10 kilo-ohm linear potentiometer that acts as a remotely controlled analog input for economizer minimum damper position. The input is processed as 0 ohms = 0% and 10,000 ohms = 100%, thereby giving complete range control of the effective minimum position. NOTE: For complete economizer control, the user can make the economizer inactive by removing the enthalpy switch connection from terminal TB201-4. Minimum Position Override Switch input will not start fan Minimum Position Override Switch input will start fan in occupied mode only Minimum Position Override Switch input will start fan in both occupied and unoccupied modes IAQ ANALOG INPUT CONFIGURATION — This input is an analog input located on the main base board (MBB). There are 4 different functions for this input. The location of this configuration is at Configuration→IAQ→AQ.CF→IQ.A.C. The functions possible for IQ.A.C are: • 0 = no IAQ analog input • 1 = IAQ analog input • 2 = IAQ analog input used to override to a set position • 3 = 4 to 20 mA 0 to 100% economizer minimum position control • 4 = 0 to 10 kilo-ohms 0 to 100% economizer minimum position control Options 2, 3, and 4 are dedicated for third party control. IQ.A.C = 2 (IAQ Analog Input Used to Override) — Under Configuration→IAQ→AQ.SP, set IQ.O.P (IAQ Economizer Override Position). The IQ.O.P configuration is adjustable from 0 to 100%. These configurations are also used in conjunction with Configuration→IAQ→AQ.CF→IQ.A.F (IAQ 4 to 20 mA Fan Configuration). There are three configurations for IQ.A.F and they follow the same logic as for the discrete input. This configuration allows the user to decide (if the supply fan is not already running), if the IAQ Analog Minimum Position Override input will start the fan, and in which state of occupancy the fan will start. IQ.A.F = 0 IQ.A.F = 1 IQ.A.F = 2 CONTROLS OPERATION Modes — The ComfortLink™ controls operate under a hierarchy of command structure as defined by three essential elements: the System mode, the HVAC mode and the Control mode. The System mode is the top level mode that defines three essential states for the control system: OFF, RUN and TEST. The HVAC mode is the functional level underneath the System mode which further defines the operation of the control. The Control mode is essentially the control type of the unit (Configuration→UNIT→C.TYP). This defines from where the control looks to establish a cooling or heating mode and whether 2 stages or multiple stages of cooling capacity operation are controlled. Furthermore, there are a number of modes which operate concurrently when the unit is running. The operating modes of IAQ analog sensor input cannot start the supply fan IAQ analog sensor input can start the supply fan in occupied mode only IAQ analog sensor input can start the supply fan in both occupied and unoccupied modes If IQ.A.F is configured to request the supply fan, then configurations D.F.ON and D.F.OF need to be set. These configuration settings are located under Configuration→ IAQ→AQ.SP and configure the fan override operation based 40 the control are located at the local displays under Operating Modes. See Table 32. 5. Fire Shut Down (traumatic fire shutdown condition based on the Fire Shutdown Input (Inputs→FIRE→FSD). (“Fire-Shutdown Mode”) 6. Emergency Stop, which is forced over the CCN through the Emergency Stop Variable (EMSTOP). (“CCN Emergency Stop”) 7. Start-up Delay. (“Startup Delay = 0-900 secs”) 8. Service test ending transition timer. (“Service Test Ending”) 9. Unexplained internal software failure. (“Internal Failure”) System Mode Test — When the system mode is Test, the control is limited to the Test mode and is controllable via the local displays (scrolling marquee and Navigator™ display) or through the factory service test control. The System Test modes are Factory Test Enabled and Service Test Enabled. See the Service Test section on page 36 for details on test control in this mode. 1. Factory Test mode (“Factory test enabled”) 2. Service Test mode (“Service test enabled”) System Mode Run — When the system mode is Run, the software application in the control is free to run the HVAC control routines by which cooling, heating, IAQ, etc., is possible. There are two possible text displays for this mode, one is normal run mode and the other occurs if one of the following fire-smoke modes is present: smoke purge, pressurization or evacuation. 1. Normal run time state (“Unit Operation Enabled”) 2. Fire-Smoke control mode (“Fire-Smoke Control”) HVAC MODES (Operating Mode→HVAC) — The HVAC mode is dependant on the system mode to allow it to further determine the operational state of the rooftop unit. The actual determination of an HVAC mode is based on a hierarchal decision making process whereby certain overrides may interfere with normal temperature/humidity control. The decision making process that determines the HVAC mode is shown in Fig. 4 and Appendix E. Each HVAC mode is described below. The HVAC mode number is shown in the parenthesis after the mode. HVAC Mode — OFF (01) — The unit is off and no operating modes are active. HVAC Mode — STARTING UP (02) — The unit is transitioning from the OFF mode to a different mode. HVAC Mode — SHUTTING DOWN (03) — The unit is transitioning from a mode to the OFF mode. HVAC Mode — DISABLED (04) — The unit is shut down due to a software command disable through the scrolling marquee, a CCN emergency stop command, a service test end, or a control-type change delay. HVAC Mode — SOFTSTOP REQUEST (05) — The unit is off due to a soft stop request from the control. HVAC Mode — REM SW.DISABLE (06) — The unit is off due to the remote switch. HVAC Mode — COMP.STUCK ON (07) — The unit is shut down because there is an indication that a compressor is running even though it has been commanded off. HVAC Mode — TEST (08) — The unit is in the self test mode which is entered through the Service Test menu. Table 32 — Operating Modes Display Table ITEM SYS.M HVAC CTRL MODE OCC T.OVR DCV SA.R DMD.L T.C.ST IAQ.P LINK LOCK H.NUM EXPANSION ascii string ascii string ascii string MODES CONTROLLING UNIT Currently Occupied Timed Override in Effect DCV Resetting Min Pos Supply Air Reset Demand Limit in Effect Temp.Compensated Start IAQ Pre-Occ Purge Active Linkage Active — CCN Mech.Cooling Locked Out HVAC Mode Numerical Form RANGE CCN POINT n/a n/a n/a ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF number MODEOCCP MODETOVR MODEADCV MODESARS MODEDMLT MODETCST MODEIQPG MODELINK MODELOCK MODEHVAC Currently Occupied (OCC) — This variable displays the current occupied state of the unit. Timed Override in Effect (T.OVR) — This variable displays if the state of occupancy is currently occupied due to an override. DCV Resetting Minimum Position (DCV) — This variable displays if the economizer position has been lowered from its maximum vent position. Supply Air Reset (SA.R) — This variable displays if the supply air set point that the rooftop is attempting to maintain is currently being reset upwards. This applies to cooling only. Demand Limit in Effect (DMD.L) — This variable displays if the mechanical cooling capacity is currently being limited or reduced by an outside third party. Temperature Compensated Start (T.C.ST) — This variable displays if Heating or Cooling has been initiated before the occupied period to pre-condition the space. IAQ Pre-Occupancy Purge Active (IAQ.P) — This variable displays if the economizer is open and the fan is on to preventilate the building before occupancy. Linkage Active CCN (LINK) — This variable displays if a linkage master in a zoning system has established “linkage” with this air source (rooftop). Mechanical Cooling Locked Out (LOCK) — This variable displays if mechanical cooling is currently being locked due to low outside air temperature. HVAC Mode Numerical Form (H.NUM) — This is a numerical representation of the HVAC modes which may be read via a point read. SYSTEM MODES (Operating Modes→SYS.M) System Mode Off — When the system mode is OFF, all outputs are to be shut down and no machine control is possible. The following list displays the text assigned to the System Mode when in the OFF mode and the conditions that may cause this mode are checked in the following hierarchal order: 1. Wake up timer on a power reset. (“Initializing System ...”) 2. System in the process of shutting down compressors and waiting for timeguards to expire. (“Shutting Down ...”) 3. Factory shut down (internal factory control level — SHUTDOWN). (“Factory Shut Down”) 4. Unit Stop (software application level variable that acts as a hard shut down — Service Test→STOP). (“Local Machine Stop”) 41 HVAC Mode — VENT (09) — This is a normal operation mode where no heating or cooling is required and outside air is being delivered to the space to control IAQ levels. HVAC Mode — HIGH COOL (10) — This is a normal cooling mode where a high cooling demand is required. HVAC Mode — LOW COOL (11) — This is a normal cooling mode where a low cooling demand is required. HVAC Mode — UNOCC. FREE COOL (12) — In this mode the unit will operate in cooling but will be using the economizer for free cooling. Entering this mode will depend on the status of the outside air. The unit can be configured for outside air changeover, differential dry bulb changeover, outside air enthalpy changeover, differential enthalpy changeover, or a custom arrangement of enthalpy/dewpoint and dry bulb. See the Economizer section for further details. HVAC Mode — TEMPERING HICOOL (13) — The economizer is at minimum vent position but the combination of the outside-air temperature and the economizer position has dropped the supply-air temperature below the tempering cool set point. Staged gas heat or hydronic heat is used to temper the ventilation air. HVAC Mode — TEMPERING LOCOOL (14) — The economizer is at minimum vent position but the combination of the outside-air temperature and the economizer position has dropped the supply-air temperature below the tempering cool set point. Staged gas heat or hydronic heat is used to temper the ventilation air. HVAC Mode — TEMPERING VENT (15) — The economizer is at minimum vent position but the supply-air temperature has dropped below the tempering vent set point. Staged gas heat or hydronic heat is used to temper the ventilation air. HVAC Mode — LOW HEAT (16) — The unit will be in low heating demand mode using either gas or electric heat. HVAC Mode — HIGH HEAT (17) — The unit will be in high heating demand mode using either gas or electric heat. HVAC Mode — FREEZESTAT TRIP (18) — If the Freezestat trips, the unit enters the Freezestat Trip HVAC mode. The supply fan will run, the hydronic heat valve will be wide open, and the economizer damper will be at minimum. HVAC Mode — STATIC PRESSURE FAIL (19) — The unit is off due to failure of the static pressure sensor. HVAC Mode — PLENUM PRESSURE FAIL (20) — The unit is off due to a plenum pressure switch trip. HVAC Mode — FIRE SHUT DOWN (21) — The unit has been stopped due to a fire shutdown input (FSD) or two or more of the fire control modes, purge, evacuation, or pressurization have been requested simultaneously. HVAC Mode — PRESSURIZATION (22) — The unit is in the special fire pressurization mode where the supply fan is on, the economizer damper is open and the power exhaust fans are off. This mode is invoked by the Fire Pressurization (PRES) input which can be found in the INPUT→FIRE submenu. HVAC Mode — EVACUATION (23) — The unit is in the special Fire Evacuation mode where the supply fan is off, the economizer damper is closed and the power exhaust fans are on. This mode is invoked by the Fire Evacuation (EVAC) input which can be found in the INPUT→FIRE submenu. HVAC Mode — SMOKE PURGE (24) — The unit is in the special Fire Purge mode where the supply fan is on, the economizer damper is open and the power exhaust fans are on. This mode is invoked by the Fire Evacuation (PURG) input which can be found in the INPUT→FIRE submenu. HVAC Mode — DEHUMIDIFICATION (25) — The unit is operating in the Dehumidification mode. HVAC Mode — RE-HEAT (26) — The unit is operating in Reheat mode. Unit Configuration Submenu — The UNIT submenu under the Configuration mode of the local display contains general unit configuration items. This section will define all of these configurations here for easy reference. The sub-menu which contains these configurations is located at the local display under Configuration→UNIT. See Table 33. Machine Control Type (C.TYP) — This configuration defines the technique and control source responsible for selecting a cooling, heating, or vent mode and in determining the method by which compressors are staged. The control types are: • C.TYP = 1 (VAV-RAT) and C.TYP = 2 (VAV-SPT) Both of these configurations refer to standard VAV operation. If the control is occupied, the supply fan is run continuously and return-air temperature will be used in the determination of the selection of a cooling mode. VAV-SPT differs from VAV-RAT only in that during the unoccupied period, space temperature will be used instead of return-air temperature to start the fan for 10 minutes to establish an accurate return-air temperature before the return-air temperature is allowed to call out any mode. • C.TYP = 3 (TSTAT – MULTI) This configuration will force the control to monitor the thermostat inputs to make a determination of mode. Unlike traditional 2-stage thermostat control, the unit is allowed to use multiple stages of cooling control and perform VAVtype operation. The control will be able to call out a LOW COOL or a HIGH COOL mode and maintain a low or high cool supply air set point. • C.TYP = 4 (TSTAT- 2 STG) This configuration will force the control to monitor the thermostat inputs to make a determination of mode and allow only 2 stages of control for both heating and cooling. • C.TYP = 5 (SPT – MULTI) This configuration will force the control to monitor a space temperature sensor to make a determination of mode. Unlike traditional 2-stage space temperature control, the unit is allowed to use multiple stages of cooling control and perform VAV-type operation. The control will be able to call out a LOW COOL or a HIGH COOL mode and maintain a low or high cool supply air set point. • C.TYP = 6 (SPT- 2 STG) This configuration will force the control to monitor the space temperature sensor to make a determination of mode and allow 2 stages of control for both heating and cooling. 42 System Mode = OFF? No FireSmoke Control System Mode Yes Inputs -> FIRE -> FSD in alarm? No HVAC Mode = OFF (Disabled) Unit not in factory test AND fire-smoke control mode is alarming? No Yes Inputs -> FIRE -> PRES in alarm? Yes No Inputs -> FIRE -> EVAC in alarm? Yes HVAC Mode = OFF (Fire Shutdown) No Yes HVAC Mode = OFF (Pressurization) HVAC Mode = OFF (Evacuation) HVAC Mode = OFF (Purge) Exceptions Config->UNIT-> C.TYP changed while unit running? No System Mode = TEST? No Yes Service Test -> S.STP = YES? Yes 15-second delay Config->UNIT-> RM.CF =2 AND Inputs->GEN.I-> REMT = ON No Yes (Config->HEAT-> HT.TY=4 OR Config-> DEHU->D.SEL=1)AND (Inputs ->GEN.I-> FRZ.S=ALRM?) Yes HVAC Mode = SoftStop Request HVAC Mode = TEST No No Yes HVAC Mode = OFF (Rem. Sw. Disable) HVAC Mode = Freeze Stat Trip HVAC Mode = OFF (Disabled) Config->SP-> SP.CF = 1 OR 2 and static pressure sensor has failed Yes HVAC Mode = OFF (Static Pres. Fail) Unit control free to select normal heating/cooling HVAC mode No Config->UNIT-> SFS.M=1 OR 2 AND Config->UNIT-> SFS.S=YES? and supply fan has failed No Config->BP-> BP.CF=5 AND There is a plenum pressure switch error Yes No Unit just waking up from power reset? Yes HVAC Mode = OFF (Fan Status Fail) HVAC Mode = OFF (Plenum Pressure Trip) Yes HVAC Mode = OFF (Starting Up) HVAC Mode = OFF HVAC Mode = Vent HVAC Mode = Tempering Vent HVAC Mode = Low Cool Unit control free to choose HVAC Mode HVAC Mode = Tempering LoCool HVAC Mode = High Cool HVAC Mode = Tempering HiCool HVAC Mode = Low Heat HVAC Mode = Re-Heat HVAC Mode = High Heat HVAC Mode = Dehumidification HVAC Mode = Unocc. Free Cool Fig. 4 — Mode Selection 43 No Unit shutting down? Yes HVAC Mode = Shutting Down No Compressor contactor welded on? Yes HVAC Mode = Comp. Stuck On No Table 33 — Unit Configuration ITEM UNIT C.TYP CV.FN RM.CF CEM TCS.C TCS.H SFS.S SFS.M VAV.S SIZE 50.HZ MAT.S MAT.R MAT.D ALTI DLAY AUX.R SENS SPT.S SP.O.S SP.O.R SRH.S RRH.S FLT.S EXPANSION UNIT CONFIGURATION Machine Control Type Fan Mode (0=Auto, 1=Cont) Remote Switch Config CEM Module Installed Temp.Cmp.Strt.Cool Factr Temp.Cmp.Strt.Heat Factr Fan Fail Shuts Down Unit Fan Stat Monitoring Type VAV Unocc.Fan Retry Time Unit Size (30-105) 50 Hertz Unit ? MAT Calc Config Reset MAT Table Entries? MAT Outside Air Default Altitude……..in feet: Startup Delay Time Auxiliary Relay Config INPUT SENSOR CONFIG Space Temp Sensor Space Temp Offset Sensor Space Temp Offset Range Space Air RH Sensor Return Air RH Sensor Filter Stat.Sw.Enabled ? RANGE 1-6 0-1 0-3 Yes/No 0 - 60 0 - 60 Yes/No 0-2 0 - 720 30 - 105 Yes/No 0-2 Yes/No 0 - 100 0 - 60000 0 -900 0-3 Enable/Disable Enable/Disable 1 - 10 Enable/Disable Enable/Disable Enable/Disable UNITS min min min % sec CCN POINT DEFAULTS CTRLTYPE FAN_MODE RMTINCFG CEM_BRD TCSTCOOL TCSTHEAT SFS_SHUT SFS_MON SAMPMINS UNITSIZE UNIT_HZ MAT_SEL MATRESET MATOADOS ALTITUDE DELAY AUXRELAY 4 1 0 No 0 0 No 0 50 30 No 1 No 20 0 0 0 SPTSENS SPTOSENS SPTO_RNG SPRHSENS RARHSENS FLTS_ENA Disable Disable 5 Disable Disable Disable Configuration→IAQ→AQ.CF→OQ.A.C = 1 (OAQ SENSDAQ) (Outdoor Air Quality Sensor) Configuration→IAQ→AQ.CF→OQ.A.C = 2 (4-20 NO DAQ) (4 to 20 mA sensor, no DAQ) Temperature Compensated Start Cooling Factor (TCS.C) — This factor is used in the equation of the Temperature Compensated Start Time Bias for cooling. Refer to the Temperature Compensated Start section for more information. A setting of 0 minutes indicates Temperature Compensated Start in Cooling is not permitted. Temperature Compensated Start Cooling Factor (TCS.H) — This factor is used in the equation of the Temperature Compensated Start Time Bias for heating. Refer to the Temperature Compensated Start section for more information. A setting of 0 minutes indicates Temperature Compensated Start in Heating is not permitted. Fan Fail Shuts Downs Unit (SFS.S) — This configuration will determine whether the unit should shut down on a supply fan status fail or simply alert the condition and continue to run. If set to YES, then the control will shut down the unit and send out an alarm if supply fan status monitoring fails. If set to NO, the control will not shut down the unit if supply fan status monitoring fails but the control will send out an alert. Fan Status Monitoring (SFS.M) — This configuration selects the type of fan status monitoring to be performed. 0 - NONE — No switch or monitoring 1 - SWITCH — Use of the fan status switch 2 - SP RISE — Monitoring of the supply duct pressure. VAV Unoccupied Fan Retry Time (VAV.S) — Machine control types 1 and 2 (VAV-RAT,VAV-SPT) include a process for sampling the return-air temperature during unoccupied periods to prove a valid demand for heating or cooling before initiating an unoccupied heating or cooling mode. If the sampling routine runs but concludes a valid demand condition does not exist, the sampling process will not be permitted for the period of time defined by this configuration. Reducing this value allows a more frequent re-sampling process. Setting this value to zero will prevent any sampling sequence. Unit Size (SIZE) — There are several unit sizes (tons) for the Z Series control. Make sure this configuration matches the size called out by the model number of the unit. This is important as the cooling stage tables are directly determined based on both the SIZE and 50.HZ configurations. Fan Mode (CV.FN) — The Fan Mode configuration can be used for machine control types (Configuration→ UNIT→C.TYP) 3, 4, 5, and 6. The Fan Mode variable establishes the operating sequence for the supply fan during occupied periods. When set to 1 (Continuous), the fan will operate continuously during occupied periods. When set to 0 (Automatic), the fan will run only during a heating or cooling mode. Remote Switch Config (RM.CF) — The remote switch input is connected to TB201 terminals 1 and 2. This switch can be used for several remote control functions. Please refer to the Remote Control Switch Input section for details on its use and operation. CEM Module Installed (CEM) — This configuration instructs the control to communicate with the controls expansion module (CEM) over the local equipment network (LEN) when set to Yes. When the unit is configured for certain sensors and configurations, this option will be set to Yes automatically. The sensors and configurations that automatically turn on this board are: Configuration→UNIT→SENS→SRH.S = Enable (Space Relative Humidity Sensor Enable) Configuration→UNIT→SENS→RRH.S = Enable (Return Air Relative Humidity Sensor Enable) Configuration→EDT.R→RES.S = Enable (4 to 20 mA Supply Air Reset Sensor Enable) Configuration→ECON→ORH.S = Enable (Outside Air Relative Humidity Sensor Enable) Configuration→ECON→CFM.C→OCF.S = Enable (Outdoor Air CFM Sensor Enable) Configuration→DEHU→D.SEN = 3 (DISCR.INPUT) (Dehumidification Sensor – Discrete Input Select) Configuration→DMD.L→DM.L.S = 1 (2 SWITCHES) (Demand Limiting using 2 discrete switches) Configuration→DMD.L→DM.L.S = 2 (4-20 MA CTRL) (Demand Limiting using a 4 to 20 mA sensor) Configuration→IAQ→AQ.CF→IQ.I.C = 1 (IAQ DISCRETE) (IAQ discrete switch control) Configuration→IAQ→AQ.CF→IQ.I.C = 2 (IAQ DISC.OVR) (IAQ discrete switch “override” control) 44 equipped with a VFD, the VFD output is not 0%). The default is 0. Space Temp Sensor (SPT.S) — If a space temperature sensor is installed (T55/T56), enable this configuration. Space Temp Offset Sensor (SP.O.S) — If a T56 sensor is installed with the space temperature offset slider, enable this configuration. Space Temp Offset Range (SP.O.R) — If a space temperature offset sensor is installed, it is possible to configure the range of the slider by adjusting this range configuration. Space Air RH Sensor (SRH.S) — If a space relative humidity sensor is installed, enable this configuration. Return RH Sensor (RRH.S) — If a return air relative humidity sensor is installed, enable this configuration. Filter Status Switch Enabled? (FLT.S) — If a filter status switch is installed, enable this configuration to begin the monitoring of the filter status input (Inputs→GEN.I→ FLT.S). See the Dirty Filter Switch section for more details on installation and operation. 50 Hertz Unit? (50.HZ) — Some units are designed to run at 50 Hertz instead of 60 Hertz. Make sure this configuration matches the frequency called out by the model number of the unit. This is important as the cooling stage tables are directly determined based on both the SIZE and 50.HZ configurations. MAT Calc Config (MAT.S) — This configuration gives the user three options in the processing of the mixed-air temperature (MAT) calculation: • MAT.S = 0 The control will not attempt to learn MAT over time. The control will simply calculate MAT based on the position of the economizer, outside and return air temperature, linearly. • MAT.S = 1 The control will attempt to learn MAT over time. Any time the system is in a vent mode and the economizer stays at a particular position for long enough, MAT = EDT (evaporator discharge temperature). Using this, the control has an internal table whereby it can more closely determine the true MAT value. • MAT.S = 2 The control will stop learning and use whatever the control has already learned. Using this setting infers that the control has spent some time set to MAT.S = 1. First set MAT.S = 1, then go into the Service Test mode. Turn on the fan and open the economizer to a static position for 5 minutes. Move to several positions (20%,40%,60%,80%). It is important that the difference between return and outside temperature be greater than 5 degrees. (The greater the delta, the better.) When done, set MAT.S = 2 and the system has been commissioned. Reset MAT Table Entries? (MAT.R) — This configuration allows the user to reset the internally stored MAT learned configuration data back to the default values. The defaults are set to a linear relationship between the economizer damper position and OAT and RAT in the calculation of MAT. MAT Outside Air Position Default (MAT.D) — This configuration is used to calculate MAT when the economizer option is disabled. The configuration is adjustable from 0 to 100% outside air. This defines the fixed ventilation position that will be used to correctly calculate MAT. Altitude……..In Feet: (ALTI) — As the control does not include a barometric pressure sensor to define the calculation of enthalpy and cfm, the control does include an altitude parameter which will serve to set up a default barometric pressure for use with calculations. The effect of barometric pressure in these calculations is not great, but could have an effect depending on the installed elevation of the unit. If the rooftop is installed at a particularly high altitude and enthalpy or cfm are being calculated, set this configuration to the current elevation of the installed rooftop. Start Up Delay Time (DLAY) — This option inhibits the unit from operating after a power reset. The configuration may be adjusted from 0 to 900 seconds of delay. Auxiliary Relay Configuration (AUX.R) — This configuration allows the user to configure the function of the auxiliary relay. The configuration can be set from 0 to 3. If AUX.R is set to 0, the auxiliary relay will be energized during an alarm. The relay can be used to turn on an indicator light or sound an alarm in a mechanical room. If AUX.R is set to 1, the auxiliary relay will energize when the controls determine dehumidification/reheat is needed. The relay would be wired to a third party dehumidification/reheat device and would energize the device when needed. If AUX.R is set to 2, the auxiliary relay will energize when the unit is in the occupied state. The relay could then be used to control lighting or other functions that need to be on during the occupied state. If AUX.R is set to 3, the auxiliary relay will energize when the supply fan is energized (and, if Cooling Control — The Z Series ComfortLink™ con- trols offer two basic control approaches to mechanical cooling: 2-stage cooling (CV) and multiple stages of cooling (VAV). In addition, the ComfortLink control offers the ability to run multiple stages of cooling for either a space temperature sensor or thermostat by controlling the unit to either a low or high cool supply air set point. The control type (Configuration→ UNIT→C.TYP) determines the selection of the type of cooling control as well as the technique for selecting a cooling mode. Unit staging tables are shown in Appendix C. NOTE: Whether a unit has a VFD, inlet guide vanes, or a supply fan installed for static pressure control has no effect on configuration of the machine control type (C.TYP). No matter what the control type, it is possible to run the unit in either CV or VAV mode provided there are enough stages to accommodate lower air volumes for VAV operation. Refer to the section on static pressure control on page 61 for information on how to set up the unit for the type of supply fan control desired. SETTING UP THE SYSTEM Machine Control Type (Configuration→UNIT→C.TYP) — The most fundamental cooling control configuration is located under Configuration→UNIT. ITEM EXPANSION RANGE UNIT UNIT CONFIGURATION C.TYP Machine Control Type 1 - 6 CCN POINT DEFAULTS CTRLTYPE * *This default is model number dependent. This configuration defines the technique and control source responsible for selecting a cooling mode and in determining the method by which compressors are staged. The control types are: • C.TYP = 1 (VAV-RAT) and C.TYP = 2 (VAV-SPT) Both of these configurations refer to standard VAV operation. If the control is occupied, the supply fan is run continuously and return-air temperature will be used for both in the determination of the selection of a cooling mode. VAV-SPT differs from VAV-RAT only in that during the unoccupied period, space temperature will be used instead of return-air temperature to start the fan for ten minutes before the return-air temperature is allowed to call out any mode. • C.TYP = 3 (TSTAT – MULTI) This configuration will force the control to monitor the thermostat inputs to make a determination of mode. Unlike traditional 2-stage thermostat control, the unit is allowed to use multiple stages of cooling control and perform VAV style operation. The control will be able to call out a LOW 45 • 3 = 3RD PARTY RESET The reset value is determined by a 4 to 20 mA third party input. An input of 4 mA would correspond to 0º F reset. An input of 20 mA would correspond to 20º F reset. Configuring the control for this option will cause RES.S to become enabled automatically with the CEM board. To avoid alarms make sure the CEM board and third party input are connected first before enabling this option. Reset Ratio (RTIO) — This configuration is used when RS.CF is set to 1 or 2. For every degree that the controlling temperature (space/return) falls below the occupied cooling set point (OCSP), the calculated value of the supply air reset will rise by the number of degrees as specified by this parameter. Reset Limit (LIMT) — This configuration is used when RS.CF is set to 1 or 2. This configuration places a clamp on the amount of supply air reset that can be applied. EDT 4-20 mA Reset Input (RES.S) — This configuration is automatically enabled when Configuration→EDT.R→ RS.CF is set to 3 (third party reset). COOLING CONFIGURATION — Relevant configurations for mechanical cooling are located at the local display under Configuration→COOL. See Table 37. Capacity Threshold Adjust (Z.GN) — This configuration is used for units using the “SumZ” algorithm for cooling capacity control (Configuration→UNIT→C.TYP = 1, 2, 3 or 5). The configuration affects the cycling rate of the cooling stages by raising or lowering the threshold that demand must build to in order to add or subtract a stage of cooling. Normally this configuration should not require any tuning or adjustment. If there is an application where the unit may be significantly oversized and there are indications of high compressor cycles then the Capacity Threshold Adjust (Z.GN) can be used to adjust the overall logic gain. Normally this is set to 1.0, but it can be adjusted from 0.5 to 4.0. As the value of Z.GN is increased, the cycling of cooling stages will be slowed. Compressor Lockout Temperature (MC.LO) — This configuration is the outdoor air temperature setting below which mechanical cooling is locked out. Lead/Lag Operation? (L.L.EN) — This configuration allows for lead/lag compressor operation for the unit. If this configuration is set to Yes, every time cooling capacity drops to 0%, on the next call for cooling, the control will start up the first compressor on the circuit which did not start the previous cooling cycle. If set to No, circuit A will always start first. Motormaster Control? (M.M.) — The condenser head pressure control for the unit is managed directly by the ComfortLink™ controls. There is no physical motormaster device in the unit. This configuration allows the head pressure control sequence to permit additional cycling control of the condenser fans. Setting this configuration to YES permits mechanical cooling operation down to 0° F (–18 C) outdoor temperature. If this configuration is set to NO, the mechanical cooling system is not suited for operation below 35 F (1.8 C) outdoor temperature. Head Pressure Set Point (HPSP) — This is the head pressure set point used by the ComfortLink controls during condenser fan, head pressure control. Enable Compressor A1 (A1.EN) — This configuration is used to disable the A1 compressor in case of failure. Enable Compressor A2 (A2.EN) — This configuration is used to disable the A2 compressor in case of failure. Enable Compressor B1 (B1.EN) — This configuration is used to disable the B1 compressor in case of failure. Enable Compressor B2 (B2.EN) — This configuration is used to disable the B2 compressor in case of failure. CSB A1 Feedback Alarm (CS.A1) — This configuration is used to enable or disable the compressor A1 feedback alarm (105 ton size units only). This configuration must be enabled at all times for 105 ton units. COOL or a HIGH COOL mode and maintain a low or high cool supply air set point. • C.TYP = 4 (TSTAT – 2 STG) This configuration will force the control to monitor the thermostat inputs to make a determination of mode. • C.TYP = 5 (SPT – MULTI) This configuration will force the control to monitor a space temperature sensor to make a determination of mode. Unlike traditional 2-stage space temperature control, the unit is allowed to use multiple stages of cooling control and perform VAV style operation. The control will be able to call out a LOW COOL or a HIGH COOL mode and maintain a low or high cool supply air set point. • C.TYP = 6 (SPT – 2 STG) This configuration will force the control to monitor the space temperature sensor to make a determination of mode and allow two stages of cooling. MACHINE DEPENDENT CONFIGURATIONS — Some configurations are linked to the physical unit and must not be changed. The configurations are provided in case a field replacement of a board occurs and the settings are not preserved by the download process of the new software. The following configurations apply to all machine control types (C.TYP) except 4 and 6. These configurations are located at the local display under Configuration→UNIT. See Table 34. Table 34 — Machine Dependent Configurations ITEM UNIT SIZE 50.HZ EXPANSION RANGE CCN POINT UNIT CONFIGURATION Unit Size (30-105) 30 - 105 UNITSIZE 50 Hertz Unit ? Yes/No UNIT_HZ DEFAULTS * * *Dependent on unit. Unit Size (SIZE) — There are several unit sizes (tons) for the Z Series control. Make sure this configuration matches the size called out by the model number of the unit. This is important as the cooling stage tables are directly determined based on both the SIZE and 50.HZ configurations. 50 Hertz Unit? (50.HZ) — Some units are designed to run at 50 Hertz instead of 60 Hertz. Make sure this configuration matches the frequency called out by the model number of the unit. This is important as the cooling stage tables are directly determined based on both the SIZE and 50.HZ configurations. SET POINTS — The set points for both cooling and heating are located at the local display under Setpoints. See Table 35. SUPPLY AIR RESET CONFIGURATION — Supply air reset can be used to modify the current cooling supply air set point. Supply air reset is applicable to control types, C.TYP = 1,2,3, and 5. The configurations for reset can be found at the local display under Configuration→EDT.R. See Table 36. EDT Reset Configuration (RS.CF) — This configuration applies to several machine control types (Configuration →UNIT →C.TYP = 1,2,3, and 5). • 0 = NO RESET No supply air reset is in effect • 1 = SPT RESET Space temperature will be used as the reset control variable along with both RTIO and LIMT in the calculation of the final amount of reset to be applied (Inputs→RSET →SA.S.R). • 2 = RAT RESET Return-air temperature will be used as the reset control variable along with both RTIO and LIMT in the calculation of the final amount of reset to be applied (Inputs→RSET→ SA.S.R). 46 Table 35 — Setpoints ITEM OHSP OCSP UHSP UCSP GAP V.C.ON V.C.OF SASP SA.HI SA.LO SA.HT T.PRG T.CL T.V.OC T.V.UN EXPANSION Occupied Heat Setpoint Occupied Cool Setpoint Unoccupied Heat Setpoint Unoccupied Cool Setpoint Heat-Cool Setpoint Gap VAV Occ. Cool On Delta VAV Occ. Cool Off Delta Supply Air Setpoint Supply Air Setpoint Hi Supply Air Setpoint Lo Heating Supply Air Setpt Tempering Purge SASP Tempering in Cool SASP Tempering Vent Occ SASP Tempering Vent Unocc. SASP RANGE 40-99 40-99 40-99 40-110 2-10 0-25 1-25 45-75 45-75 45-75 90-145 –20-80 5-75 –20-80 –20-80 UNITS dF dF dF dF deltaF deltaF deltaF dF dF dF dF dF dF dF dF CCN POINT OHSP OCSP UHSP UCSP HCSP_GAP VAVOCON VAVOCOFF SASP SASP_HI SASP_LO SASPHEAT TEMPPURG TEMPCOOL TEMPVOCC TEMPVUNC DEFAULT 68 75 55 90 5 3.5 2 55 55 60 85 50 5 65 50 Table 36 — Supply Air Reset Configuration ITEM EDT.R RS.CF RTIO LIMT RES.S EXPANSION EVAP.DISCHRGE TEMP RESET EDT Reset Configuration Reset Ratio Reset Limit EDT 4-20 ma Reset Input RANGE UNITS 0-3 0 - 10 0 - 20 Enable/Disable deltaF CCN POINT EDRSTCFG RTIO LIMT EDTRSENS DEFAULT 2 2 10 Disable Table 37 — Cooling Configuration ITEM COOL Z.GN MC.LO L.L.EN M.M. HPSP A1.EN A2.EN B1.EN B2.EN CS.A1 CS.A2 CS.B1 CS.B2 HPS.A HPS.B H.SST EXPANSION COOLING CONFIGURATION Capacity Threshold Adjst Compressor Lockout Temp Lead/Lag Operation ? Motor Master Control ? Head Pressure Setpoint Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 CSB A1 Feedback Alarm CSB A2 Feedback Alarm CSB B1 Feedback Alarm CSB B2 Feedback Alarm CMPA1 Hi.Pr.Sw. Trip CMPB1 Hi.Pr.Sw. Trip Hi SST Alert Delay Time RANGE –10 - 10 –25 - 55 Yes/No Yes/No 80 - 150 Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable 365 - 415 365 - 415 5 - 30 UNITS dF dF PSIG PSIG min CCN POINT Z_GAIN OATLCOMP LLENABLE MOTRMAST HPSP CMPA1ENA CMPA2ENA CMPB1ENA CMPB2ENA CSB_A1EN CSB_A2EN CSB_B1EN CSB_B2EN HPSATRIP HPSBTRIP HSSTTIME DEFAULT 1 40 No No 113 Enable Enable Enable Enable Enable Enable Enable Enable 415 415 10 sample the discharge pressure on circuit B and store this value minus 3 psig and attempt to catch this failure the next time before the switch trips. The value is modifiable by the user but will still get overriden if the control does not catch a high pressure condition before the switch trips. High SST Alert Delay Time (H.SST) — This option allows the low saturated suction temperature alert timing delay to be adjusted. COOL MODE SELECTION PROCESS — The Z Series ComfortLink™ controls offer three distinct methods by which they may select a cooling mode. 1. Thermostat (C.TYP=3 and 4): The thermostat does not depend upon the state of occupancy or temperature and the modes are called out directly by the discrete inputs (Inputs→STAT→Y1 and Y2). 2. VAV cooling types (C.TYP=1 and 2) are called out in the occupied period (Operating Modes→MODE→ OCC=ON). 3. VAV cooling types (C.TYP=1 and 2) are called out in the unoccupied period (Operating Modes→MODE→ OCC=OFF). They are also used for space sensor control types (C.TYP=5 and 6) in both the occupied and unoccupied periods. This section is devoted to the process of cooling mode determination for the three types outlined above. CSB A2 Feedback Alarm (CS.A2) — This configuration is used to enable or disable the compressor A2 feedback alarm (105 ton size units only). This configuration must be enabled at all times for 105 ton units. CSB B1 Feedback Alarm (CS.B1) — This configuration is used to enable or disable the compressor B1 feedback alarm (105 ton size units only). This configuration must be enabled at all times for 105 ton units. CSB B2 Feedback Alarm (CS.B2) — This configuration is used to enable or disable the compressor B2 feedback alarm (105 ton size units only). This configuration must be enabled at all times for 105 ton units. Compressor A1 High Pressure Switch Trip (HPS.A) — This configuration is used when high-pressure switches are used. This is true for all units except the 105 ton size units which incorporate current sensor boards (CSB). In the case of a highpressure switch trip on compressor A1, the control will sample the discharge pressure on circuit A and store this value minus 3 psig and attempt to catch this failure the next time before the switch trips. The value is modifiable by the user but will still get overriden if the control does not catch a high pressure condition before the switch trips. Compressor B1 High Pressure Switch Trip (HPS.B) — This configuration is used when high-pressure switches are used. This is true for all units except the 105 ton size units which incorporate current sensor boards (CSB). In the case of a high-pressure switch trip on compressor B1, the control will 47 VAV Cool Mode Selection during the Occupied Period (C.TYP = 1,2 and Operating Modes→MODE→OCC =ON) — There is no difference in the selection of a cooling mode for either VAV-RAT or VAV-SPT in the occupied period. The actual selection of a cool mode, for both control types, is based upon the controlling return-air temperature (Temperatures→ AIR.T→CTRL→R.TMP). Typically this is the same as the return air temperature thermistor (Temperatures→AIR.T→ RAT) except when under CCN Linkage. VAV Occupied Cool Mode Evaluation Configuration — There are VAV occupied cooling offsets under Setpoints. ITEM V.C.ON V.C.OF L.H.ON DMDLHON L.H.OF DMDLHOFF V.C. OF VAVOCOFF a48-8414 Fig. 5 — VAV Occupied Period Trip Logic NOTE: With vent mode, it is possible to exit out of a cooling mode during the occupied period if the return-air temperature drops low enough. When supply-air temperature reset is not configured, this capability will work to prevent over-cooling the space during the occupied period. Supply Air Set Point Control and the Staging of Compressors — Once the control has determined that a cooling mode is in effect, the cooling control point (Run Status→VIEW →CL.C.P) is calculated and is based upon the supply air set point (Setpoints→SASP) plus any supply air reset being applied (Inputs→RSET→SA.S.R). Refer to the SumZ Cooling Algorithm section on page 50 for a discussion of how the Z Series ComfortLink™ controls manage the staging of compressors to maintain supply-air temperature. VAV Cool Mode Selection during the Unoccupied Period (C.TYP = 1,2; Operating Modes→MODE→OCC=OFF) and Space Sensor Cool Mode Selection (C.TYP=5 & 6) — The machine control types that utilize this technique of mode selection are: • C.TYP = 1 (VAV-RAT) in the unoccupied period • C.TYP = 2 (VAV-SPT) in the unoccupied period • C.TYP = 5 (SPT-MULTI) in both the occupied and unoccupied period • C.TYP = 6 (SPT- 2 STG) in both the occupied and unoccupied period These particular control types operate differently than the VAV types in the occupied mode in that there is both a LOW COOL and a HIGH COOL mode. For both of these modes, the control offers two independent set points, Setpoints→SA.LO (for LOW COOL mode) and Setpoints→SA.HI (for HIGH COOL mode). The occupied and unoccupied cooling set points can be found under Setpoints. CCN DEFAULT POINT deltaF VAVOCON 3.5 EXPANSION RANGE UNITS VAV Occ. 0-25 Cool On Delta VAV Occ. 1-25 Cool Off Delta V.C. ON VAVOCON OHSP deltaF VAVOCOFF 2 Cool Mode Determination — If the machine control type (Configuration→ UNIT→C.TYP) = 1 (VAV-RAT) or 2 (VAVSPT) and the control is occupied (Operating Modes→ MODE→OCC=ON), then the unit will not follow the occupied cooling set point (OCSP). Instead, the control will follow two offsets in the determination of an occupied VAV cooling mode (Setpoints→V.C.ON and Setpoints→V.C.OF), applying them to the low-heat off trip point and comparing the resulting temperature to the return-air temperature. The Setpoints→V.C.ON (VAV cool mode on offset) and Setpoints→V.C.OF (VAV cool mode off offset) offsets are used in conjunction with the low heat mode off trip point to determine when to bring cooling on and off and in enforcing a true “vent” mode between heating and cooling. See Fig. 5. The occupied cooling set point is not used in the determination of the cool mode. The occupied cooling set point is used for supply air reset only. The advantage of this offset technique is that the control can safely enforce a vent mode without worrying about crossing set points. Even more importantly, under CCN linkage, the occupied heating set point may drift up and down and as such this technique of using offsets ensures a guaranteed separation in degrees F between the calling out of a heating or cooling mode at all times. NOTE: There is a sub-menu at the local display (Run Status →TRIP) that allows the user to see the exact trip points for both the heating and cooling modes without having to calculate them. Refer to the Cool Mode Diagnostic Help section on page 50 for more information. To enter into a VAV Occupied Cool mode, the controlling temperature must rise above [OHSP minus L.H.ON plus L.H.OF plus V.C.ON]. To exit out of a VAV Occupied Cool Mode, the controlling temperature must fall below [OHSP minus L.H.ON plus L.H.OF plus V.C.ON minus V.C.OF]. ITEM dF CCN DEFAULT POINT OCSP 75 dF UCSP EXPANSION RANGE UNITS OCSP Occupied 55-80 Cool Setpoint Unoccupied 75-95 Cool Setpoint UCSP 90 The heat/cool set point offsets are found under Configuration→D.LV.T. See Table 38. Table 38 — Cool/Heat Set Point Offsets Configuration ITEM D.LV.T L.H.ON H.H.ON L.H.OF L.C.ON H.C.ON L.C.OF C.T.LV H.T.LV C.T.TM H.T.TM EXPANSION COOL/HEAT SETPT. OFFSETS Dmd Level Lo Heat On Dmd Level(+) Hi Heat On Dmd Level(-) Lo Heat Off Dmd Level Lo Cool On Dmd Level(+) Hi Cool On Dmd Level(-) Lo Cool Off Cool Trend Demand Level Heat Trend Demand Level Cool Trend Time Heat Trend Time RANGE -1 - 2 0.5 - 20.0 0.5 - 2.0 -1 - 2 0.5 - 20.0 0.5 - 2 0.1 - 5 0.1 - 5 30 - 600 30 - 600 48 UNITS ^F ^F ^F ^F ^F ^F ^F ^F sec sec CCN POINT DMDLHON DMDHHON DMDLHOFF DMDLCON DMDHCON DMDLCOFF CTRENDLV HTRENDLV CTRENDTM HTRENDTM DEFAULT 1.5 0.5 1 1.5 0.5 1 0.1 0.1 120 120 Operating modes are under Operating Modes→MODE. ITEM MODE OCC T.C.ST modes there is a timeguard which enforces a time delay between the transitioning from a low cool to a high cool mode. This time delay is 8 minutes. There is a timeguard which enforces a time delay between the transitioning from a heat mode to a cool mode. This time delay is 5 minutes. Supply Air Set Point Control — Once the control has determined that a cooling mode is in effect, the cooling control point (Run Status→VIEW→CL.C.P) is calculated and is based upon either Setpoints→SA.HI or Setpoints→SA.LO, depending on whether a high or a low cooling mode is in effect, respectively. In addition, if supply air reset is configured, it will also be added to the cooling control point. Refer to the SumZ Cooling Algorithm section for a discussion of how the Z Series ComfortLink™ controls manage supply-air temperature and the staging of compressors for these control types. C.TYP = 3 and 4 (Thermostat Cool Mode Selection) — When a thermostat type is selected, the decision making process involved in determining the mode is straightforward. Upon energizing the Y1 input only, the unit HVAC mode will be LOW COOL. Upon the energizing of both Y1 and Y2 inputs, the unit HVAC mode will be HIGH COOL. If just input G is energized the unit HVAC mode will be VENT and the supply fan will run. Selecting the C.TYP = 3 (TSTAT – MULTI) control type will cause the control to do the following: • The control will read both the Configuration→UNIT→ SIZE and Configuration→UNIT→50.HZ configuration parameters to determine the number of cooling stages and the pattern for each stage. • An HVAC mode equal to LOW COOL will cause the unit to select the Setpoints→SA.LO set point to control to. An HVAC mode equal to HIGH COOL will cause the unit to select the Setpoints→SA.HI set point to control to. Supply air reset (if configured) will be added to either the low or high cool set point. • The control will utilize the SumZ cooling algorithm and control cooling to a supply air set point. See the section for the SumZ Cooling Algorithm section for information on controlling to a supply air set point and compressor staging. Selecting the C.TYP = 4 (TSTAT – 2 STG) control type means that only two stages of cooling will be used. An HVAC mode of LOW COOL will energize one circuit and an HVAC mode of HIGH COOL will energize both circuits provided the economizer is not able to provide adequate free cooling. Refer to the section on Economizer Integration with Mechanical Cooling for more information. EXPANSION RANGE CCN POINT MODES CONTROLLING UNIT Currently Occupied ON/OFF MODEOCCP Temp.Compensated Start ON/OFF MODETCST Cool Mode Evaluation Logic — The first thing the control determines is whether the unit is in the occupied mode (OCC) or is in the temperature compensated start mode (T.C.ST). If the unit is occupied or in temperature compensated start mode, the occupied cooling set point (OCSP) is used. For all other modes, the unoccupied cooling set point (UCSP) is used. For further discussion and simplification this will be referred to as the “cooling set point.” See Fig. 6. Demand Level Low Cool On Offset (L.C.ON) — This is the cooling set point offset added to the cooling set point at which point a Low Cool mode starts. Demand Level High Cool On Offset (H.C.ON) — This is the cooling set point offset added to the “cooling set point plus L.C.ON” at which point a High Cool mode begins. Demand Level Low Cool Off Offset (L.C.OF) — This is the cooling set point offset subtracted from “cooling set point plus L.C.ON” at which point a Low Cool mode ends. NOTE: The “high cool end” trip point uses the “low cool off” (L.C.OF) offset divided by 2. To enter into a LOW COOL mode, the controlling temperature must rise above [the cooling set point plus L.C.ON.] To enter into a HIGH COOL mode, the controlling temperature must rise above [the cooling set point plus L.C.ON plus H.C.ON.] To exit out of a LOW COOL mode, the controlling temperature must fall below [the cooling set point plus L.C.ON minus L.C.OF.] To exit out of a HIGH COOL mode, the controlling temperature must fall below [the cooling set point plus L.C.ON minus L.C.OF/2.] Comfort Trending — In addition to the set points and offsets which determine the trip points for bringing on and bringing off cool modes, there are 2 configurations which work to hold off the transitioning from a low cool to a high cool mode if the space is cooling down quickly enough. This technique is referred to as comfort trending and the configurations of interest are C.T.LV and C.T.TM. Cool Trend Demand Level (C.T.LV) — This is the change in demand that must occur within the time period specified by C.T.TM in order to hold off a HIGH COOL mode regardless of demand. This is not applicable to VAV control types (C.TYP=1 and 2) in the occupied period. As long as a LOW COOL mode is making progress in cooling the space, the control will hold off on the HIGH COOL mode. This is especially true for the space sensor machine control types (C.TYP) = 5 and 6, because they may transition into the occupied mode and see an immediate large cooling demand when the set points change. Cool Trend Time (C.T.TM) — This is the time period upon which the cool trend demand level (C.T.LV) operates and may hold off staging or a HIGH COOL mode. This is not applicable to VAV control types (C.TYP=1 and 2) in the occupied period. See the Cool Trend Demand Level section for more details. Timeguards — In addition to the set points and offsets which determine the trip points for bringing on and bringing off cool Hi Cool Start H.C.ON Lo Cool Start L.C. OF L.C.ON L.C. OF/2 Hi Cool End Lo Cool End Cooling Setpoint (OCSP,UCSP) Fig. 6 — Cool Mode Evaluation 49 ADD.R = R.PCT * (C.CAP — capacity after adding a cooling stage) For example: If R.PCT = 0.2 and the control would be adding 20% cooling capacity by taking the next step up, 0.2 times 20 = 4 F (ADD.R) Next Stage EDT Increase (SUB.R) — This variable represents (if subtracting a stage of cooling) how much the temperature should rise in degrees depending on the R.PCT calculation and exactly how much capacity is to be subtracted. SUB.R = R.PCT * (C.CAP — capacity after subtracting a cooling stage) For Example: If R.PCT = 0.2 and the control would be subtracting 30% capacity by taking the next step down, 0.2 times –30 = –6 F (SUB.R) Rise Per Percent Capacity (R.PCT) — This is a real time calculation that represents the amount of degrees of drop/rise across the evaporator coil versus percent of current running capacity. R.PCT = (MAT – EDT)/ C.CAP Cap Deadband Subtracting (Y.MIN) — This is a control variable used for Low Temp Override (L.TMP) and Slow Change Override (SLOW). Y.MIN = -SUB.R*0.4375 Cap Deadband Adding (Y.PLU) — This is a control variable used for High Temp Override (H.TMP) and Slow Change Override (SLOW). Y.PLU = -ADD.R*0.4375 Cap Threshold Subtracting (Z.MIN) — This parameter is used in the calculation of SMZ and is calculated as follows: Z.MIN = Configuration→COOL→Z.GN * (–10 + (4* (–SUB.R))) * 0.6 Cap Threshold Adding (Z.PLU) — This parameter is used in the calculation of SMZ and is calculated as follows: Z.PLU = Configuration→COOL→Z.GN * (10 + (4* (–ADD.R))) * 0.6 High Temp Cap Override (H.TMP) — If stages of mechanical cooling are on and the error is greater than twice Y.PLU, and the rate of change of error is greater than 0.5° F per minute, then a stage of mechanical cooling will be added every 30 seconds. This override is intended to react to situations where the load rapidly increases. Low Temp Cap Override (L.TMP) — If the error is less than twice Y.MIN, and the rate of change of error is less than –0.5° F per minute, then a mechanical stage will be removed every 30 seconds. This override is intended to quickly react to situations where the load is rapidly reduced. Pull Down Cap Override (PULL) — If the error from set point is above 4° F, and the rate of change is less than –1° F per minute, then pulldown is in effect, and “SUM” is set to 0. This keeps mechanical cooling stages from being added when the error is very large, but there is no load in the space. Pulldown for units is expected to rarely occur, but is included for the rare situation when it is needed. Most likely pulldown will occur when mechanical cooling first becomes available shortly after the control goes into an occupied mode (after a warm unoccupied mode). Slow Change Cap Override (SLOW) — With a rooftop unit, the design rise at 100% total unit capacity is generally around 30° F. For a unit with 4 stages, each stage represents about 7.5° F of change to EDT. If stages could reliably be cycled at very fast rates, the set point could be maintained very precisely. Since it is not desirable to cycle compressors more than 6 cycles per hour, slow change override takes care of keeping the PID under control when “relatively” close to set point. COOL MODE DIAGNOSTIC HELP — To quickly determine the current trip points for the cooling modes, the Run Status sub-menu at the local display allows the user to view the calculated start and stop points for both the cooling and heating trip points. The following sub-menu can be found at the local display under Run Status→TRIP. See Table 39. Table 39 — Run Status Mode Trip Helper ITEM TRIP UN.C.S UN.C.E OC.C.S OC.C.E TEMP OC.H.E OC.H.S UN.H.E UN.H.S HVAC EXPANSION MODE TRIP HELPER Unoccup. Cool Mode Start Unoccup. Cool Mode End Occupied Cool Mode Start Occupied Cool Mode End Ctl.Temp RAT,SPT or Zone Occupied Heat Mode End Occupied Heat Mode Start Unoccup. Heat Mode End Unoccup. Heat Mode Start the current HVAC MODE UNITS dF dF dF dF dF dF dF dF dF CCN POINT UCCLSTRT UCCL_END OCCLSTRT OCCL_END CTRLTEMP OCHT_END OCHTSTRT UCHT_END UCHTSTRT String The controlling temperature is “TEMP” and is in the middle of the table for easy reference. The HVAC mode can also be viewed at the bottom of the table. SUMZ COOLING ALGORITHM — The SumZ cooling algorithm is an adaptive PID (proportional, integral, derivative) which is used by the control whenever more than 2 stages of cooling are present (C.TYP = 1,2,3, and 5). This section will describe its operation and define the pertinent parameters. It is generally not necessary to modify parameters in this section. The information is presented primarily for reference and may be helpful for troubleshooting complex operational problems. The only configuration parameter for the SumZ algorithm is located at the local display under Configuration→ COOL→Z.GN. See Table 37. Capacity Threshold Adjust (Z.GN) — This configuration is used on units using the “SumZ” algorithm for cooling capacity control (Configuration→UNIT→C.TYP = 1, 2, 3 and 5). It affects the cycling rate of the cooling stages by raising or lowering the threshold that capacity must build to in order to add or subtract a stage of cooling. The cooling algorithm’s run-time variables are located at the local display under Run Status→COOL. See Table 40. Current Running Capacity (C.CAP) — This variable represents the amount of capacity currently running in percent. Current Cool Stage (CUR.S) — This variable represents the cool stage currently running. Requested Cool Stage (REQ.S) — This variable represents the requested cool stage. Cooling relay timeguards in place may prevent the requested cool stage from matching the current cool stage. Maximum Cool Stages (MAX.S) — This variable is the maximum number of cooling stages the control is configured for and capable of controlling. Active Demand Limit (DEM.L) — If demand limit is active, this variable will represent the amount of capacity that the control is currently limited to. Capacity Load Factor (SMZ) — This factor builds up or down over time (–100 to +100) and is used as the means of adding or subtracting a cooling stage during run time. It is a normalized representation of the relationship between “Sum” and “Z”. Next Stage EDT Decrease (ADD.R) — This variable represents (if adding a stage of cooling) how much the temperature should drop in degrees depending on the R.PCT calculation and exactly how much additional capacity is to be added. 50 Table 40 — Run Status Cool Display ITEM COOL C.CAP CUR.S REQ.S MAX.S DEM.L SUMZ SMZ ADD.R SUB.R R.PCT Y.MIN Y.PLU Z.MIN Z.PLU H.TMP L.TMP PULL SLOW EXPANSION COOLING INFORMATION Current Running Capacity Current Cool Stage Requested Cool Stage Maximum Cool Stages Active Demand Limit COOL CAP. STAGE CONTROL Capacity Load Factor Next Stage EDT Decrease Next Stage EDT Increase Rise Per Percent Capacity Cap Deadband Subtracting Cap Deadband Adding Cap Threshold Subtracting Cap Threshold Adding High Temp Cap Override Low Temp Cap Override Pull Down Cap Override Slow Change Cap Override RANGE UNITS % % -100 – +100 ^F ^F CCN POINT CAPTOTAL COOL_STG CL_STAGE CLMAXSTG DEM_LIM WRITE STATUS forcible SMZ ADDRISE SUBRISE RISE_PCT Y_MINUS Y_PLUS Z_MINUS Z_PLUS HI_TEMP LOW_TEMP PULLDOWN SLO_CHNG 3) the amount of expected rise for the next cooling stage subtraction The calculation of “Z” requires two variables, Z.PLU used when adding a stage and Z.MIN used when subtracting a stage. They are calculated with the following formulas: Z.PLU = Z.GN * (10 + (4*(–ADD.R))) * 0.6 Z.MIN = Z.GN * (–10 + (4*(–SUB.R))) * 0.6 Where: Z.GN = configuration used to modify the threshold levels used for staging (Configuration→COOL→Z.GN) ADD.R = R.PCT * (C.CAP – capacity after adding a cooling stage) SUB.R = R.PCT * (C.CAP – capacity after subtracting a cooling stage) Both of these terms, Z.PLU and Z.MIN, represent a threshold both positive and negative upon which the “SUM” calculation must build up to in order to cause the compressor to stage up or down. Comparing SUM and Z — The “SUM” calculation is compared against Z.PLU and Z.MIN. • If “SUM” rises above Z.PLU, a cooling stage is added. • If “SUM” falls below Z.MIN, a cooling stage is subtracted. There is a variable called SMZ which is described in the reference section and which can simplify the task of watching the demand build up or down over time. It is calculated as follows: If SUM is positive: SMZ = 100*(SUM/Z.PLU) If SUM is negative: SMZ = –100*(SUM/Z.MIN) Mixed Air Temperature Calculation (MAT) — The mixedair temperature is calculated and is a function of the economizer position. Additionally there are some calculations in the control which can zero in over time on the relationship of return and outside air as a function of economizer position. There are two configurations which relate to the calculation of “MAT”. These configurations can be located at the local display under Configuration→UNIT. SumZ Operation — The SumZ algorithm is an adaptive PID style of control. The PID is programmed within the control and the relative speed of staging can only be influenced by the user through the adjustment of the Z.GN configuration, described in the reference section. The capacity control algorithm uses a modified PID algorithm, with a self adjusting gain which compensates for varying conditions, including changing flow rates across the evaporator coil. Previous implementations of SumZ made static assumptions about the actual size of the next capacity jump up or down. This control uses a “rise per percent capacity” technique in the calculation of SumZ, instead of the previous “rise per stage” method. For each jump, up or down in capacity, the control will know beforehand the exact capacity change brought on. Better overall staging control can be realized with this technique. SUM Calculation — The PID calculation of the “SUM” is evaluated once every 80 seconds. SUM = Error + “SUM last time through” + (3 * Error Rate) Where: SUM = the PID calculation Error = EDT – Cooling Control Point Error Rate = Error – “Error last time through” NOTE: “Error” is clamped between –10 and +50 and “Error rate” is clamped between –5 and +5. This “SUM” will be compared against the “Z” calculations in determining whether cooling stages should be added or subtracted. Z Calculation — For the “Z” calculation, the control attempts to determine the entering and the leaving-air temperature of the evaporator coil and based upon the difference between the two during mechanical cooling, determines whether to add or subtract a stage of cooling. This is the adaptive element. The entering-air temperature is referred to as MAT (mixed-air temperature) and the leaving-air temperature of the evaporator coil is referred to as EDT (evaporator discharge temperature). They are found at the local display under the Temperatures→CTRL sub-menu. The main elements to be calculated and used in the calculation of SumZ are: 1) the rise per percent capacity (R.PCT) 2) the amount of expected rise for the next cooling stage addition ITEM UNIT MAT.S MAT.R 51 EXPANSION RANGE CCN POINT DEFAULTS UNIT CONFIGURATION MAT Calc Config 0 - 2 MAT_SEL 1 Reset MAT Table Yes/No MATRESET No Entries? • CCN loadshed functionality. NOTE: It is also possible to force the demand limit variable (Run Status→COOL→DEM.L). To use Demand Limiting, select the type of demand limiting to use. This is done with the Demand Limit Select configuration (Configuration→DMD.L→DM.L.S). To view the current demand limiting currently in effect, look at Run Status→COOL→DEM.L. The configurations associated with demand limiting can be viewed at the local display at Configuration→DMD.L. See Table 41. Demand Limit Select (DM.L.S) — This configuration determines the type of demand limiting. • 0 = NONE — Demand Limiting not configured. • 1 = 2 SWITCHES — This will enable switch input demand limiting using the switch inputs connected to the CEM board. Connections should be made to TB204 terminals 1, 2, 3, and 4. • 2 = 4 to 20 mA — This will enable the use of a remote 4 to 20 mA demand limit signal. The CEM module must be used. The 4 to 20 mA signal must come from an externally sourced controller and should be connected to TB203 terminals 2 and 3. • 3 = CCN LOADSHED — This will allow for loadshed and red lining through CCN communications. Two-Switch Demand Limiting (DM.L.S = 1) — This type of demand limiting utilizes two discrete inputs: Demand Limit Switch 1 Setpoint (D.L.S1) — Dmd Limit Switch Setpoint 1 (0-100% total capacity) Demand Limit 2 Setpoint (D.L.S2) — Dmd Limit Switch Setpoint 2 (0-100% total capacity) The state of the discrete switch inputs can be found at the local display: Inputs→GEN.I→DL.S1 Inputs→GEN.I→DL.S2 The following table illustrates the demand limiting (Run Status→COOL→DEM.L) that will be in effect based on the logic of the applied switches: MAT Calc Config (MAT.S) — This configuration gives the user three options in the processing of the mixed-air temperature (MAT) calculation: • MAT.S = 0 The control will not attempt to learn MAT over time. The control will simply calculate MAT based on the position of the economizer, outside and return air temperature, linearly. • MAT.S = 1 The control will attempt to learn MAT over time. Any time the system is in a vent mode and the economizer stays at a particular position for long enough, MAT = EDT. Using this, the control has an internal table whereby it can more closely determine the true MAT value. • MAT.S = 2 The control will stop learning and use whatever the control has already learned. Using this setting infers that the control has spent some time set to MAT.S = 1. First set MAT.S = 1. Then go into the Service Test mode, turn on the fan and open the economizer to a static position for 5 minutes. Move to several positions (20%,40%,60%,80%). It is important that the difference between return and outside temperature be greater than 5 degrees. (The greater the delta, the better). When done, set MAT.S = 2 and the system has been commissioned. Reset MAT Table Entries? (MAT.R) — This configuration allows the user to reset the internally stored MAT learned configuration data back to the default values. The defaults are set to a linear relationship between the economizer damper position and OAT and RAT in the calculation of MAT. SumZ Overrides — There are a number of overrides to the SumZ algorithm which may add or subtract stages of cooling. • High Temp Cap Override (H.TMP) • Low Temp Cap Override (L.TMP) • Pull Down Cap Override (PULL) • Slow Change Cap Override (SLOW) Economizer Trim Override — The unit may drop stages of cooling when the economizer is performing free cooling and the configuration Configuration→ECON→E.TRM is set to Yes. The economizer controls to the same supply air set point as mechanical cooling does for SumZ when E.TRM = Yes. This allows for much tighter temperature control as well as cutting down on the cycling of compressors. For a long cooling session where the outside-air temperature may drop over time, there may be a point at which the economizer has closed down far enough were the unit could remove a cooling stage and open up the economizer further to make up the difference. Mechanical Cooling Lockout (Configuration→COOL→ MC.LO) — This configuration allows a configurable outsideair temperature set point below which mechanical cooling will be completely locked out. DEMAND LIMIT CONTROL — Demand Limit Control may override the cooling algorithm and clamp or shed cooling capacity during run time. The term Demand Limit Control refers to the restriction of the machine capacity to control the amount of power that a machine will use. Demand limit control is intended to interface with an external Loadshed Device either through CCN communications, external switches, or 4 to 20 mA input. The control has the capability of loadshedding and limiting in 3 ways: • Two discrete inputs tied to configurable demand limit set point percentages. • An external 4 to 20 mA input that can reset capacity back linearly to a set point percentage. Switch Status Inputs→GEN.I→DL.S1 = OFF Inputs→GEN.I→DL.S2 = OFF Inputs→GEN.I→DL.S1= ON Inputs→GEN.I→DL.S2 = OFF Inputs→GEN.I→DL.S1= ON Inputs→GEN.I→DL.S2 = ON Inputs→GEN.I→DL.S1= OFF Inputs→GEN.I→DL.S2 = ON Run Status→COOL→DEM.L = 1 100% Configuration→DMD.L→D.L.S1 Configuration→DMD.L→D.L.S2 Configuration→DMD.L→D.L.S2 4-20 mA Demand Limiting (DM.L.S = 2) — If the unit has been configured for 4 to 20 mA demand limiting, then the Inputs→4-20→DML.M value is used to determine the amount of demand limiting in effect (Run Status→COOL→ DEM.L). The Demand Limit at 20 mA (D.L.20) configuration must be set. This is the configured demand limit corresponding to a 20 mA input (0 to 100%). The value of percentage reset is determined by a linear interpolation from 0% to “D.L.20”% based on the Inputs→ 4-20→DML.M input value. The following examples illustrate the demand limiting (Run Status→COOL→DEM.L) that will be in effect based on amount of current seen at the 4 to 20 mA input, DML.M. D.L.20 = 80% DML.M = 4mA DEM.L = 100% 52 D.L.20 = 80% DML.M = 12 mA DEM.L = 90% D.L.20 = 80% DML.M = 20mA DEM.L = 80% Table 41 — Demand Limit Configuration ITEM DMD.L DM.L.S D.L.20 SH.NM SH.DL SH.TM D.L.S1 D.L.S2 EXPANSION DEMAND LIMIT CONFIG. Demand Limit Select Demand Limit at 20 ma Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time Demand Limit Sw.1 Setpt. Demand Limit Sw.2 Setpt. RANGE 0-3 0 - 100 0 - 99 0 - 60 0 - 120 0 - 100 0 - 100 UNITS % % min % % CCN POINT DMD_CTRL DMT20MA SHED_NUM SHED_DEL SHED_TIM DLSWSP1 DLSWSP2 DEFAULT 0 100 0 0 60 80 50 Fan Stage 1 Operation — If Stage 1 Cycling (Motormaster) is not selected, the stage 1 fan output will be ON whenever mechanical cooling is ON (either circuit) and OFF when mechanical cooling is OFF (both circuits). If Stage 1 Cycling (Motormaster) is selected, the first stage operates as follows: The fan stage turns ON whenever either saturated condensing temperature (SCT) is greater than 138 F. The fan stage 1 turns OFF whenever both SCTs are less than the HPSP – 37 F for 90 seconds and fan stage is 1. Fan Stage 2 Operation (Sizes 030-050) — The control energizes fan CD.F.A when either of the SCTs exceeds HPSP and the Stage 1 Fan (CD.MM) has been energized for 60 seconds. Fan CD.F.A is turned OFF when both SCTs have been less than the set point – 35 F for a period of 2 minutes. Fan stage 2 will turn OFF if both circuits are turned off. Fan Stage 2 Operation (Sizes 055-105) — There are two conditions that may request the second stage fan for independent control: • the control energizes fan stage 2 when the SCT for that circuit exceeds HPSP and the Stage 1 fan has been energized for 60 seconds. • the control energizes fan stage 2 if the SCT for the particular circuit exceeds 143 F during the first 60 seconds after fan stage 1 has been turned on. Fan stage 2 turns OFF when the SCT for the particular circuit has been less than HPSP – 35 F for a period of 2 minutes. Head Pressure Control Exceptions — For size 105 units, current sensor boards are able to diagnose a compressor stuck on condition. If any of the current sensor boards for the fourcompressor unit detects a compressor stuck on, then the first stage fan is turned on immediately (CD.MM). If compressors A1 or A2 are diagnosed as stuck on, the second stage fan for that circuit will be turned on (CD.F.A). If compressors B1 or B2 are diagnosed as stuck on, the second stage fan for that circuit will be turned on (CD.F.B). If no compressors are stuck on, the next check will determine whether compressors are on or not. If any compressor has not been commanded on, the first stage fan is not allowed on. This is also true for the second stage fan and units configured for unit sizes 030-050. For unit sizes 055-105, if no compressors in a circuit are commanded on, the corresponding second stage fan is not allowed on (CD.F.A, CD.F.B). ECONOMIZER INTEGRATION WITH MECHANICAL COOLING — When the economizer is able to provide free cooling (Run Status→ECON→ACTV = YES), mechanical cooling may be delayed or even held off indefinitely. NOTE: Once mechanical cooling has started, this delay logic is no longer relevant. Multi-Stage Cooling Economizer Mechanical Cooling Delay — This type of mechanical cooling delay is relevant to the following machine control types: C.TYP = 1 VAV-RAT C.TYP = 2 VAV-SPT C.TYP = 3 TSTAT-MULTI C.TYP = 5 SPT-MULTI CCN Loadshed Demand Limiting (DM.L.S = 3) — If the unit has been configured for CCN Loadshed Demand Limiting, then the demand limiting variable (Run Status→COOL→ DEM.L) is controlled via CCN commands. The relevant configurations for this type of demand limiting are: Loadshed Group Number (SH.NM) — CCN Loadshed Group number Loadshed Demand Delta (SH.DL) — CCN Loadshed Demand Delta Maximum Loadshed Time (SH.TM) — CCN Maximum Loadshed time The Loadshed Group Number (SH.NM) corresponds to the loadshed supervisory device that resides elsewhere on the CCN network and broadcasts loadshed and redline commands to its associated equipment parts. The SH.NM variable will default to zero which is an invalid group number. This allows the loadshed function to be disabled until configured. Upon reception of a redline command, the machine will be prevented from starting if it is not running. If it is running, then DEM.L is set equal to the current running cooling capacity (Run Status→COOL→C.CAP). Upon reception of a loadshed command, the DEM.L variable is set to the current running cooling capacity (Run Status →COOL→C.CAP) minus the configured Loadshed Demand Delta (SH.DL). A redline command or loadshed command will stay in effect until a Cancel redline or Cancel loadshed command is received, or until the configurable Maximum Loadshed time (SH.TM) has elapsed. HEAD PRESSURE CONTROL — Condenser head pressure for the 48/50Z series is managed directly by the ComfortLink™ controls. The controls are able to cycle two stages of outdoor fans to maintain acceptable head pressure. Fan stages will react to discharge pressure sensors with the pressure converted to the corresponding saturated condensing temperature. Unit size is used to determine if the second stage fans are configured to respond to a particular circuit (independent control) or both circuits (common control). An option to allow fan cycling on the first stage is configured by setting Configuration→COOL→M.M = Yes. NOTE: The term Motormaster is used in the software to refer to a fan cycling on the first stage. An actual Motormaster® device is not used or required. Cycling is done by the ComfortLink controls. There are two configurations provided for head pressure control that can be found at the local display: Configuration→COOL→M.M. — Motormaster enable Configuration→COOL→HPSP — Head Pressure Set point There are three outputs provided to control head pressure: Outputs→FANS→CD.F.A — Condenser Fan A Outputs→FANS→CD.F.B — Condenser Fan B Outputs→FANS→CD.MM — “Motor master” or the fan cycling output 53 If the economizer is able to provide free cooling at the start of a cooling session, the mechanical cooling algorithm (SumZ), checks the economizer’s current position (Run Status →ECON→ECN.P) and compares it to the economizer’s maximum position (Configuration→ECON→EC.MX) – 5%. Once the economizer has opened beyond this point a 150 second timer starts. If the economizer stays beyond this point for 2.5 minutes continuously, the mechanical cooling algorithm is allowed to start computing demand and stage compressors and unloaders. 2-Stage Cooling Economizer Mechanical Cooling Delay — This type of mechanical cooling delay is relevant to the following machine control types: C.TYP = 4 TSTAT-2 STG C.TYP = 6 SPT-2 STG If the economizer is able to provide free cooling at the start of a cooling session (for either a low cool or a high cool mode), the 2-stage cooling algorithm will start a 10-minute hold off timer on staging. Once this timer has expired, the 2-stage cooling algorithm will qualify both the temperature of the evaporator discharge temperature (EDT) and the outside-air temperature (OAT). If either of these temperatures are less than the current cooling control point (Run Status→VIEW→CL.C.P) plus 1.5° F, mechanical cooling will be held off. But if both of these temperatures are above CL.C.P + 1.5° F, the first compressor will be requested and a 5-minute hold off timer will be started that will give the first compressor time to run before the second compressor may be started. At this point, if the 5-minute timer expires and the cooling mode request is high or the cooling mode request is low and dehumidification is active (Operating Modes→MODE→ DEHU=ON), the 2-stage cooling algorithm checks whether EDT is 1.5° F greater than the current cooling control point (CL.C.P) and if it is, the second compressor will be requested. Heating Control — The Z Series ComfortLink™ con- trols offers control for four different types of heating systems to satisfy general space heating requirements: 2-stage gas heat, 2-stage electric heat, multiple-stage gas heat and hydronic heat. Heating control also provides tempering and reheat functions. These functions are discussed in separate sections. Reheat is discussed under Dehumidification function on page 77. Variable air volume (VAV) type applications (C.TYP = 1, 2, 3, or 5) require that the space terminal positions be commanded to open to minimum heating positions when gas or electric heat systems are active, to provide for the unit heating system’s Minimum Heating Airflow rate. Also, for VAV applications, the heat interlock relay (HIR) function provides the switching of a control signal intended for use by the VAV terminals. This signal must be used to command the terminals to open to their Heating Open positions. The HIR is energized whenever the Heating mode is active, an IAQ pre-occupied force is active, or if fire smoke modes, pressurization, or smoke purge modes are active. Hydronic heating applications that use the unit’s control require the installation of a Local Equipment Network (LEN) communicating actuator on the hydronic heating coil’s control valve. This actuator (with or without matching control valve) may be separately shipped for field installation. All heating systems are available as factory-installed options. The hydronic heating coil may also be field-supplied and field-installed; the LEN actuator is still required if unit control will be used to manage this heating sequence. SETTING UP THE SYSTEM — The essential heating configurations located at the local display under Configuration→ HEAT. See Table 42. Table 42 — Heating Configuration ITEM HEAT HT.CF HT.SP OC.EN LAT.M SG.CF HT.ST CAP.M M.R.DB S.G.DB RISE LAT.L LIM.M SW.H.T SW.L.T HT.P HT.D HT.TM HH.CF HW.P HW.I HW.D HW.TM ACT.C SN.1 SN.2 SN.3 SN.4 SN.5 C.A.LM EXPANSION HEATING CONFIGURATION Heating Control Type Heating Supply Air Setpt Occupied Heating Enabled MBB Sensor Heat Relocate STAGED GAS CONFIGS Staged Gas Heat Type Max Cap Change per Cycle S.Gas DB min.dF/PID Rate St.Gas Temp. Dead Band Heat Rise dF/sec Clamp LAT Limit Config Limit Switch Monitoring? Limit Switch High Temp Limit Switch Low Temp Heat Control Prop. Gain Heat Control Derv. Gain Heat PID Rate Config HYDRONIC HEAT CONFIGS Hydronic Ctl.Prop. Gain Hydronic Ctl.Integ. Gain Hydronic Ctl.Derv. Gain Hydronic PID Rate Config HYDR.HEAT ACTUATOR CFGS. Hydronic Ht.Serial Num.1 Hydronic Ht.Serial Num.2 Hydronic Ht.Serial Num.3 Hydronic Ht.Serial Num.4 Hydronic Ht.Serial Num.5 Hydr.Ht.Ctl.Ang.Lo Limit RANGE 0-4 80 - 120 Yes/No Yes/No 0-4 5 - 45 0-5 0-5 0.05 - 0.2 0 - 20 Yes/No 110 - 180 100 - 170 0 - 1.5 0 - 1.5 60 - 300 0 - 1.5 0 - 1.5 0 - 1.5 15 - 300 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 *Some defaults are model number dependent. 54 UNITS CCN POINT DEFAULT HEATTYPE SASPHEAT HTOCCENA HTLATMON 0* 85 No No sec HTSTGTYP HTCAPMAX HT_MR_DB HT_SG_DB HTSGRISE HTLATLIM HTLIMMON HT_LIMHI HT_LIMLO HT_PGAIN HT_DGAIN HTSGPIDR 0* 45* 0.5 2 0.06 10 Yes 170* 160* 1 1 90 sec HW_PGAIN HW_IGAIN HW_DGAIN HOTWPIDR 1 1 1 90 HTCL_SN1 HTCL_SN2 HTCL_SN3 HTCL_SN4 HTCL_SN5 HTCLCALM 0 0 0 0 0 85 dF ^F ^F dF dF With sufficient heating demand, there are still conditions that will prevent the unit from selecting a heat mode. First, the unit must be configured for a heat type (Configuration→ HEAT→HT.CF not equal to “NONE”). Second, the unit has a configuration which can enable or disable heating in the occupied period except for a standard morning warmup cycle (Configuration→HEAT→OC.EN). See descriptions above in the Setting Up the System section for more information. If the unit is allowed to select a heat mode, then the next step is an evaluation of demand versus set point. At this point, the logic is the same as for control types SPT Multi-Stage and SPT-2 Stage, (C.TYP = 5,6) except for the actual temperature compared against set point. See Temperature Driven Heat Mode Evaluation section. Tstat-Multi-Stage (C.TYP = 3) and Tstat-2 Stage (C.TYP = 4) — There is no difference to consider for selecting a heat mode whether the control type is for TSTAT 2-stage or TSTAT multi-stage as this only refers to how cooling will be handled. With thermostat control the W1 and W2 inputs determine whether the HVAC Mode is LOW or HIGH HEAT. W1 = ON, W2 = OFF: HVAC MODE = LOW HEAT* W2 = ON, W2 = ON: HVAC MODE = HIGH HEAT *If the heating type is either 2-stage electric or 2-stage gas, the unit may promote a low heat mode to a high heat mode. NOTE: If W2 = ON and W1 is OFF, a “HIGH HEAT” HVAC Mode will be called out but an alert (T422) will be generated. See Alarms and Alerts section on page 94. SPT Multi-Stage (C.TYP = 5) and SPT 2 Stage (C.TYP = 6) — There is no difference to consider for selecting a heat mode whether the control type is for SPT 2-stage or SPT multi-stage as this only refers to how cooling will be handled. So, for a valid heating type selected (HT.CF not equal to zero) the unit is free to select a heating mode based on space temperature (SPT). If the unit is allowed to select a heat mode, then the next step is an evaluation of demand versus set point. At this point, the logic is the same as for control types VAV-RAT and VAV-SPT, (C.TYP = 1,2) except for the actual temperature compared against set point. See Temperature Driven Heat Mode Evaluation section below. TEMPERATURE DRIVEN HEAT MODE EVALUATION — This section discusses the technique for selecting a heating mode based on temperature. Regardless of whether the unit is configured for return air or space temperature the logic is exactly the same. For the rest of this discussion, the temperature in question will be referred to as the “controlling temperature.” First, the occupied and unoccupied heating set points under Setpoints must be configured. Heating Control Type (HT.CF) — The heating control types available are selected/configured with this variable. 0 = No Heat 1 = Electric Heat 2 = 2 Stage Gas Heat 3 = Staged Gas Heat 4 = Hydronic Heat Heating Supply Air Set Point (HT.SP) — In a low heat mode for either staged gas or hydronic heat, this is the supply air set point for heating. Occupied Heating Enable (OC.EN) — This configuration only applies when the unit’s control type (Configuration →UNIT→C.TYP) is configured for 1 (VAV-RAT) or 2 (VAVSPT). If the user wants to have the capability of performing heating throughout the entire occupied period, then this configuration needs to be set to “YES”. Most installations do not require this capability, and if heating is installed, it is used to heat the building up in the morning. In this case set OC.EN to “NO”. NOTE: This unit des not support simultaneous heating and cooling. If significant simultaneous heating and cooling demand is expected, it may be necessary to provide additional heating or cooling equipment and a control system to provide occupants with proper comfort. MBB Sensor Heat Relocate (LAT.M) — This option allows the user additional performance benefit when under CCN Linkage for the 2-stage electric and gas heating types. As twostage heating types do not “modulate” to a supply air set point, no leaving air thermistor is required and none is provided. The evaporator discharge thermistor, which is initially installed upstream of the heater, can be repositioned downstream and the control can expect to sense this heat. While the control does not need this to energize stages of heat, the control can wait for a sufficient temperature rise before announcing a heating mode to a CCN Linkage system (ComfortID™). If the sensor is relocated, the user will now have the capability to view the leaving-air temperature at all times at Temperatures→AIR.T→CTRL→LAT. NOTE: If the user does not relocate this sensor for the 2-stage electric or gas heating types and is under CCN Linkage, then the control will send a heating mode (if present) unconditionally to the linkage coordinator in the CCN zoning system regardless of the leaving-air temperature. HEAT MODE SELECTION PROCESS — There are two possible heat modes that the control will call out for heating control: HVAC Mode = LOW HEAT and HVAC Mode = HIGH HEAT. These modes will be called out based on control type (C.TYP). VAV-RAT (C.TYP = 1) and VAV-SPT (C.TYP = 2) — There is no difference in the selection of a heating mode for either VAV-RAT or VAV-SPT, except that for VAV-SPT, space temperature is used in the unoccupied period to turn on the supply fan for 10 minutes before checking return-air temperature. The actual selection of a heat mode, LOW or HIGH for both control types, will be based upon the controlling return-air temperature. ITEM OHSP UHSP EXPANSION RANGE UNITS Occupied Heat 55-80 Setpoint Unoccupied 40-80 Heat Setpoint CCN DEFAULT POINT dF OHSP 68 dF UHSP 55 Then, the heat/cool set point offsets under Configuration→ D.LV.T should be set. See Table 43. Table 43 — Heat/Cool Set Point Offsets ITEM D.LV.T L.H.ON H.H.ON L.H.OF L.C.ON H.C.ON L.C.OF C.T.LV H.T.LV C.T.TM H.T.TM EXPANSION COOL/HEAT SETPT. OFFSETS Dmd Level Lo Heat On Dmd Level(+) Hi Heat On Dmd Level(-) Lo Heat Off Dmd Level Lo Cool On Dmd Level(+) Hi Cool On Dmd Level(-) Lo Cool Off Cool Trend Demand Level Heat Trend Demand Level Cool Trend Time Heat Trend Time RANGE -1 - 2 0.5 - 2.0 0.5 - 2 -1 - 2 0.5 - 2 0.5 - 2 0.1 - 5 0.1 - 5 30 - 600 30 - 600 55 UNITS ^F ^F ^F ^F ^F ^F ^F ^F sec sec CCN POINT DMDLHON DMDHHON DMDLHOFF DMDLCON DMDHCON DMDLCOFF CTRENDLV HTRENDLV CTRENDTM HTRENDTM DEFAULT 1.5 0.5 1 1.5 0.5 1 0.1 0.1 120 120 Related operating modes are under Operating Modes→ MODE. ITEM MODE OCC T.C.ST EXPANSION RANGE MODES CONTROLLING UNIT Currently Occupied ON/OFF Temp.Compensated Start ON/OFF view the state of the system. This menu also contains the cool trip points as well. See Table 44 at the local display under Run Status→TRIP. CCN POINT Table 44 — Mode Trip Helper Table MODEOCCP MODETCST ITEM TRIP UN.C.S UN.C.E OC.C.S OC.C.E TEMP OC.H.E OC.H.S UN.H.E UN.H.S HVAC The first thing the control determines is whether the unit is in the occupied mode (OCC) or in the temperature compensated start mode (T.C.ST). If the unit is occupied or in temperature compensated start mode, the occupied heating set point (OHSP) is used. In all other cases, the unoccupied heating setpoint (UHSP) is used. The control will call out a low or high heat mode by comparing the controlling temperature to the heating set point and the heating set point offset. The set point offsets are used as additional help in customizing and tweaking comfort into the building space. Demand Level Low Heat on Offset (L.H.ON) — This is the heating set point offset below the heating set point at which point Low Heat starts. Demand Level High Heat on Offset (H.H.ON) — This is the heating set point offset below [the heating set point minus L.H.ON] at which point high heat starts. Demand Level Low Heat Off Offset (L.H.OF) — This is the heating set point offset above [the heating set point minus L.H.ON] at which point the Low Heat mode ends. See Fig. 7 for an example of offsets. To enter into a LOW HEAT mode, if the controlling temperature falls below [the heating set point minus L.H.ON], then HVAC mode = LOW HEAT. To enter into a HIGH HEAT mode, if the controlling temperature falls below [the heating set point minus L.H.ON minus H.H.ON], then HVAC mode = HIGH HEAT. To get out of a LOW HEAT mode, the controlling temperature must rise above [the heating set point minus L.H.ON plus L.H.OF]. To get out of a HIGH HEAT mode, the controlling temperature must rise above [the heating set point minus L.H.ON plus L.H.OF/2]. The Run Status table in the local display allows the user to see the exact trip points for both the heating and cooling modes without doing the calculations. Heat Trend Demand Level (H.T.LV) — This is the change in demand that must be seen within the time period specified by H.T.TM in order to hold off a HIGH HEAT mode regardless of demand. This is not applicable to VAV control types (C.TYP=1 and 2) in the occupied period. This technique has been referred to as “Comfort Trending.” As long as a LOW HEAT mode is making progress in warming the space, the control will hold off on a HIGH HEAT mode. This is relevant for the space sensor machine control types (C.TYP = 5 and 6) because they may transition into the occupied mode and see an immediate and large heating demand when the set points change. Heat Trend Time (H.T.TM) — This is the time period upon which the heat trend demand level (H.T.LV) operates and may work to hold off staging or a HIGH HEAT mode. This is not applicable to VAV control types (C.TYP=1 and 2) in the occupied period. See “Heat Trend Demand Level” section for more details. HEAT MODE DIAGNOSTIC HELP — To quickly determine the current trip points for the low and high heat modes, there is a menu in the local display which lets the user quickly EXPANSION MODE TRIP HELPER Unoccup. Cool Mode Start Unoccup. Cool Mode End Occupied Cool Mode Start Occupied Cool Mode End Ctl.Temp RAT,SPT or Zone Occupied Heat Mode End Occupied Heat Mode Start Unoccup. Heat Mode End Unoccup. Heat Mode Start the current HVAC MODE UNITS CCN POINT dF dF dF dF dF dF dF dF dF UCCLSTRT UCCL_END OCCLSTRT OCCL_END CTRLTEMP OCHT_END OCHTSTRT UCHT_END UCHTSTRT String The controlling temperature is “TEMP” and is in the middle of the table for easy reference. Also, the “HVAC” mode can be viewed at the bottom of the table. TWO-STAGE GAS AND ELECTRIC HEAT CONTROL (HT.CF = 1,2) — If the HVAC mode is LOW HEAT: • If electric heat is configured, then the control will request the supply fan ON • If gas heat is configured, then the IGC IFO input controls the supply fan request • The control will turn on Heat Relay 1 (HS1) • If evaporator discharge temperature is less than 50 F, then the control will turn on Heat Relay 2 (HS2)* If the HVAC mode is HIGH HEAT: • If electric heat is configured, then the control will request the supply fan ON • If gas heat is configured, then the IGC IFO input controls the supply fan request • The control will turn on Heat Relay 1 (HS1) • The control will turn on Heat Relay 2 (HS2) *The logic for this “low heat” override is that one stage of heating will not be able to raise the temperature of the supply airstream sufficient to heat the space. HYDRONIC HEATING CONTROL (HT.CF = 4) — Hydronic heating in Z Series units refers to a hot water coil controlled by an actuator. This actuator is a Local Equipment Network (LEN) communicating actuator and may be field supplied. When Configuration→HEAT→HT.CF=4, there is a thermistor array called Temperatures→AIR.T→CCT, that is connected to the RCB, that serves as the evaporator discharge temperature (EDT). The leaving-air temperature (LAT) is assigned the thermistor that is normally assigned to EDT and is located at the supply fan housing (Temperatures→AIR.T→ SAT). The configurations for hydronic heating are located at the local displays under Configuration→HEAT→HH.CF. See Table 45. HEATING SET POINT L.H.ON L.H.OF L.H.OF/2 H.H.ON 66.0 F Fig. 7 — Heating Offsets 56 68.0 F 67.5 F 66.5 F a48-8407 Table 45 — Hydronic Heat Configuration ITEM HH.CF HW.P HW.I HW.D HW.TM ACT.C SN.1 SN.2 SN.3 SN.4 SN.5 C.A.LM EXPANSION HYDRONIC HEAT CONFIGS Hydronic Ctl.Prop. Gain Hydronic Ctl.Integ. Gain Hydronic Ctl.Derv. Gain Hydronic PID Rate Config HYDR.HEAT ACTUATOR CFGS. Hydronic Ht.Serial Num.1 Hydronic Ht.Serial Num.2 Hydronic Ht.Serial Num.3 Hydronic Ht.Serial Num.4 Hydronic Ht.Serial Num.5 Hydr.Ht.Ctl.Ang.Lo Limit RANGE 0 - 1.5 0 - 1.5 0 - 1.5 15 - 300 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 UNITS sec CCN POINT DEFAULT HW_PGAIN HW_IGAIN HW_DGAIN HOTWPIDR 1 1 1 90 HTCL_SN1 HTCL_SN2 HTCL_SN3 HTCL_SN4 HTCL_SN5 HTCLCALM 0 0 0 0 0 85 actuator. Five individual numbers make up this serial number and these can be programmed to match the serial number of the actuator in its Hydronic Heating Actuator Configs group, ACT.C (SN.1, SN.2, SN.3, SN.4, SN.5). NOTE: The serial numbers for all LEN actuators can be found inside the control doors of the unit as well as on the actuator itself. If an actuator is replaced in the field, it is a good idea to remove the additional peel off serial number sticker on the actuator and cover up the old one inside the control doors. STAGED GAS HEATING CONTROL (HT.CF = 3) — As an option, the units with gas heat can be equipped with staged gas heat controls that will provide from 5 to 11 stages of heat capacity. This is intended for tempering mode and tempering economizer air when in a cooling mode and the dampers are fully closed. Tempering can also be used during a preoccupancy purge to prevent low temperature air from being delivered to the space. Tempering for both staged gas and hydronic heat will be discussed in its own section. This section will focus on heat mode control, which ultimately is relevant to tempering, minus the consideration of the supply air heating control point. The staged gas configurations are located at the local display under Configuration→HEAT→SG.CF. See Table 46. Staged Gas Heat Type (HT.ST) — This configuration instructs the control how many stages and in what order are they staged. Max Cap Change per Cycle (CAP.M) — This configuration limits the maximum change in capacity per PID run time cycle. S.Gas DB Min.dF/PID Rate (M.R.DB) — This configuration is a deadband minimum temperature per second rate. See capacity calculation logic on next page for more details. St.Gas Temp.Dead Band (S.G.DB) — This configuration is a deadband delta temperature. See capacity calculation logic on next page for more details. Heat Rise in dF/Sec Clamp (RISE) — This configuration clamps heat staging up when the leaving-air temperature is rising too fast. LAT Limit Config (LAT.L) — This configuration senses when leaving air temperature is outside a delta temperature band around set point and allows staging to react quicker. Limit Switch Monitoring? (LIM.M) — This configuration allows the operation of the limit switch monitoring routine. This is always enabled for Z Series as a limit switch temperature sensor is always present for staged gas operation. Limit Switch High Temp (SW.H.T) — This configuration is the temperature limit above which stages of heat will be shed. Limit Switch Low Temp (SW.L.T) — This configuration is the temperature limit above which no additional stages of heat will be allowed. Heat Control Prop. Gain (HT.P) — This configuration is the proportional term for the PID which runs in the HVAC mode LOW HEAT. Hydronic Heating Control Proportional Gain (HW.P) — This configuration is the proportional term for the PID which runs in the HVAC mode LOW HEAT. Hydronic Heating Control Integral Gain (HW.I) — This configuration is the integral term for the PID which runs in the HVAC mode LOW HEAT. Hydronic Heating Control Derivative Gain (HW.D) — This configuration is the derivative term for the PID which runs in the HVAC mode LOW HEAT. Hydronic Heating Control Run Time Rate (HW.TM) — This configuration is the PID run time rate which runs in the HVAC mode LOW HEAT. Hydronic Heating Logic If the HVAC mode is LOW HEAT: • The control will command the supply fan on • The control will modulate the hot water coil actuator to the heating control point (Run Status→VIEW→ HT.C.P). The heating control point for hydronic heat is the heating supply air set point (Setpoints→SA.HT). If the HVAC mode is HIGH HEAT: • The control will command the supply fan on • The control will command the hot water coil actuator to 100% Hydronic Heating PID Process — If the HVAC mode is LOW HEAT, then the hydronic heating actuator will modulate to the heating control point (Run Status→VIEW→HT.C.P). Control is performed with a generic PID loop where: Error = Heating Control Point (HT.C.P) – Leaving Air Temperature (LAT) The PID terms are calculated as follows: P = K * HW.P * error I = K * HW.I * error + “I” last time through D = K * HW.D * (error – error last time through) Where K = HW.TM/60 to normalize the effect of changing the run time rate. NOTE: The PID values should be not be modified without approval from Carrier. Freeze Status Switch Logic (Inputs→GEN.I→FRZ.S) — If the freezestat input (FRZ) alarms, indicating that the coil is freezing, normal heat control is overridden and the following actions will be taken: 1. Command the hot water coil actuator to 100%. 2. Command the economizer damper to 0%. 3. Command the supply fan on. Configuring Hydronic Heat to Communicate Via Actuator Serial Number — Every actuator used in the Z Series control system has its own unique serial number. The rooftop control uses this serial number to communicate with the actuator over the local equipment network (LEN). These serial numbers are programmed at the factory and should not need changing. Should field replacement of an actuator become necessary, it will be required to configure the serial numbers of the new 57 Table 46 — Staged Gas Configuration ITEM SG.CF HT.ST CAP.M M.R.DB S.G.DB RISE LAT.L LIM.M SW.H.T SW.L.T HT.P HT.D HT.TM EXPANSION STAGED GAS CONFIGS Staged Gas Heat Type Max Cap Change per Cycle S.Gas DB min.dF/PID Rate St.Gas Temp. Dead Band Heat Rise dF/sec Clamp LAT Limit Config Limit Switch Monitoring? Limit Switch High Temp Limit Switch Low Temp Heat Control Prop. Gain Heat Control Derv. Gain Heat PID Rate Config RANGE 0-4 5 - 45 0-5 0-5 0.05 - 0.2 0 - 20 Yes/No 110 - 180 100 - 170 0 - 1.5 0 - 1.5 60 - 300 UNITS ^F ^F dF dF sec CCN POINT HTSTGTYP HTCAPMAX HT_MR_DB HT_SG_DB HTSGRISE HTLATLIM HTLIMMON HT_LIMHI HT_LIMLO HT_PGAIN HT_DGAIN HTSGPIDR DEFAULT 0* 45* 0.5 2 0.06 10 Yes 170* 160* 1 1 90 *Some configurations are model number dependent. CAP.M. This sum can be no larger or no smaller than +CAP.M or –CAP.M. Finally, the desired capacity is calculated: Staged Gas Capacity Calculation = “P + D” + old Staged Gas Capacity Calculation NOTE: The PID values should not be modified without approval from Carrier. Heat Control Derv. Gain (HT.D) — This configuration is the derivative term for the PID which runs in the HVAC mode LOW HEAT. Heat PID Rate Config (HT.TM) — This configuration is the PID run time rate. Staged Gas Heating Logic If the HVAC mode is HIGH HEAT: • The supply fan for staged gas heating is controlled by the 48Z Integrated Gas Control (IGC) boards and unless the supply fan is on for a different reason, will be controlled by the IGC IFO input. • Command all stages of heat ON If the HVAC mode is LOW HEAT: • The supply fan for staged gas heating is controlled by the integrated gas control (IGC) boards and unless the supply fan is on for a different reason, will be controlled by the IGC IFO input. • The unit will control stages of heat to the heating control point (Run Status→VIEW→HT.C.P). The heating control point in a LOW HEAT HVAC mode for staged gas is the heating supply air set point (Setpoints→SA.HT). Staged Gas Heating PID Logic — The heat control loop is a PID design with exceptions, overrides and clamps. Capacity rises and falls based on set point and supply-air temperature. When the staged gas control is in Low Heat or Tempering Mode (HVAC mode), the algorithm calculates the desired heat capacity. The basic factors that govern the controlling technique are: • how fast the algorithm is run. • the amount of proportional and derivative gain applied. • the maximum allowed capacity change each time this algorithm is run. • deadband hold-off range when rate is low. This routine is run once every “HT.TM” seconds. Every time the routine is run, the calculated sum is added to the control output value. In this manner, integral effect is achieved. Every time this algorithm is run, the following calculation is performed: Error = HT.C.P – LAT Error_last = error calculated previous time P = HT.P*(Error) D = HT.D*(Error – Error_last) The P and D terms are overridden to zero if: Error < S.G.DB AND Error > – S.G.DB AND D < M.R.DB AND D > – M.R.DB “P + D” are then clamped based on IMPORTANT: When gas or electric heat is used in a VAV application with third party terminals, the HIR relay output must be connected to the VAV terminals in the system in order to enforce a minimum heating cfm. The installer is responsible to ensure the total minimum heating cfm is not below limits set for the equipment. Failure to do so will result in limit switch tripping and may void warranty. Staged Gas Heat Staging — Different unit sizes will control heat stages differently based on the amount of heating capacity included. These staging patterns are selected based on the model number. The selection of a set of staging patterns is controlled via the heat stage type configuration parameter (HT.ST). As the heating capacity rises and falls based on demand, the staged gas control logic will stage the heat relay patterns up and down, respectively. The Heat Stage Type configuration selects one of 5 staging patterns that the stage gas control will use. In addition to the staging patterns, the capacity for each stage is also determined by the staged gas heating PID control. Therefore, choosing the heat relay outputs is a function of the capacity desired, the heat staging patterns based on the heat stage type (HT.ST) and the capacity presented by each staging pattern. As the staged gas control desired capacity rises, it is continually checked against the capacity of the next staging pattern. When the desired capacity is greater than or equal to the capacity of the next staging pattern, the next heat stage is selected (Run Status→VIEW→HT.ST = Run Status→VIEW→ HT.ST + 1). Similarly, as the capacity of the control drops, the desired capacity is continually checked against the next lower stage. When the desired capacity is less than or equal to the next lower staging pattern, the next lower heat stage pattern is selected (Run Status→VIEW→HT.ST = Run Status →VIEW→ HT.ST – 1). The first two staged gas heat outputs are located on the MBB board and outputs 3, 4, 5, and 6 are located on the SCB board. These outputs are used to yield from 2 to 9 stages as shown in Table 47. The heat stage selected (Run Status→VIEW→HT.ST) is clamped between 0 and the maximum number of stages possible (Run Status→VIEW →H.MAX) for the chosen set of staging patterns. See Tables 48-50. 58 cutoff mode condition, a stage will drop each time through. Falling back below the cutoff point will turn off the LAT cutoff mode. INTEGRATED GAS CONTROL BOARD LOGIC — All gas heat units are equipped with one or more integrated gas control (IGC) boards. This board provides control for the ignition system for the gas heat sections. On size 030-050 low heat units there will be one IGC board. On size 030-050 high heat units and 055-105 low heat units there are two IGC boards. On size 055-105 high heat units there are three IGC boards. When a call for gas heat is initiated, power is sent to W on the IGC boards. For standard 2-stage heat, all boards are wired in parallel. For staged gas heat, each board is controlled separately. When energized, an LED on the IGC board will be turned on. See Table 51 for LED explanations. Each board will ensure that the rollout switch and limit switch are closed. The induceddraft motor is then energized. When the speed of the motor is proven with the Hall Effect sensor on the motor, the ignition activation period begins. The burners ignite within 5 seconds. If the burners do not light, there is a 22-second delay before another 5-second attempt is made. If the burners still do not light, this sequence is repeated for 15 minutes. After 15 minutes have elapsed and the burners have not ignited then heating is locked out. The control will reset when the request for W (heat) is temporarily removed. When ignition occurs, the IGC board will continue to monitor the condition of the rollout switch, limit switches, Hall Effect sensor, and the flame sensor. Forty-five seconds after ignition has occurred, the IGC will request that the indoor fan be turned on. The IGC fan output (IFO) is connected to the indoor fan input on the MBB which will indicate to the controls that the indoor fan should be turned on (if not already on). If for some reason the overtemperature limit switch trips prior to the start of the indoor fan blower, on the next attempt the 45-second delay will be shortened by 5 seconds. Gas will not be interrupted to the burners and heating will continue. Once modified, the fan delay will not change back to 45 seconds unless power is reset to the control. The IGC boards only control the first stage of gas heat on each gas valve. The second stages are controlled directly from the MBB board. The IGC board has a minimum on-time of 1 minute. In modes such as Service Test where long minimum on times are not enforced, the 1-minute timer on the IGC will still be followed and the gas will remain on for a minimum of 1 minute. Limit Switch Temperature Monitoring (LIM.M) — Variable air volume applications in the low heat or tempering mode can experience low airflow and as a result it is possible for nuisance trips of the gas heat limit switch, thereby shutting off all gas stages. In order to achieve consistent heating in a tempering mode, a thermistor (Temperatures→AIR.T→S.G.LS) is placed next to the limit switch and monitored for overheating. In order to control a tempering application where the limit switch temperature has risen above either the upper or lower configuration parameters (SW.L.T, SW.H.T), the staged gas control will respond to clamp or drop all gas stages. If the Limit Switch Monitoring configuration parameter (LIM.M) is set to YES, all the modes will be monitored. If set to NO, then only LAT Cutoff mode and Capacity Clamp mode for RISE will be monitored. If S.G.LS rises above SW.L.T or if (LAT – LAT last time through the capacity calculation) is greater than (RISE) degrees F per second, the control will not allow the capacity routine to add stages and will turn on the Capacity Clamp mode. If S.G.LS rises above SW.H.T the control will run the capacity routine immediately and drop all heat stages and will turn on the Limiting mode. If S.G.LS falls below SW.L.T the control will turn off both Capacity Clamp mode and Limiting mode with one exception. If (LAT – LAT last time through the capacity calculation) is greater than “RISE” degrees F per second, the control will stay in the Capacity Clamp mode. If control is in the Limiting mode and then S.G.LS falls below SW.L.T, and LAT is not rising quickly, the control will run the capacity calculation routine immediately and allow a full stage to come back on if desired this first time through upon recovery. This will effectively override the “max capacity stage” clamp. In addition to the above checks, it is also possible at low cfm for the supply-air temperature to rise and fall radically between capacity calculations, thereby impacting the limit switch temperature. In the case where supply-air temperature (LAT) rises above the control point (HT.C.P) + the cutoff point (LAT.L) the control will run the capacity calculation routine immediately and drop a stage of heat. Thereafter, every time the capacity calculation routine runs, provided the control is still in the LAT Table 47 — Staged Gas Heat NUMBER OF STAGES 2 HT.ST CONFIGURATION 0 5 1 9 3 UNIT SIZE 48Z 030-050 030-050 055-105 055-105 HEAT SIZE Low High Low High Table 48 — Staged Gas Heat Control Steps (HT.ST = 0) STAGE 0 1 2 Heat 1 MBB-RLY8 IGC1 OFF ON ON Heat 2 MBB-RLY7 MGV1 OFF OFF ON RELAY OUTPUT Heat 3 Heat 4 SCB-RLY1 SCB-RLY2 IGC2 MGV2 OFF OFF OFF OFF OFF OFF 59 Heat 5 SCB-RLY3 IGC3 OFF OFF OFF Heat 6 SCB-RLY4 MGV3 OFF OFF OFF CAPACITY % 0 75 100 Table 49 — Staged Gas Heat Control Steps (HT.ST = 1) STAGE 0 1 2 3 4 5 Heat 1 MBB-RLY8 IGC1 OFF ON ON ON ON ON Heat 2 MBB-RLY7 MGV1 OFF OFF ON OFF ON ON RELAY OUTPUT Heat 3 Heat 4 SCB-RLY1 SCB-RLY2 IGC2 MGV2 OFF OFF OFF OFF OFF OFF ON OFF ON OFF ON ON Heat 5 SCB-RLY3 IGC3 OFF OFF OFF OFF OFF OFF Heat 6 SCB-RLY4 MGV3 OFF OFF OFF OFF OFF OFF CAPACITY % Heat 6 SCB-RLY4 MGV3 OFF OFF OFF OFF OFF OFF OFF OFF OFF ON CAPACITY % 0 37 50 75 87 100 Table 50 — Staged Gas Heat Control Steps (HT.ST = 3) STAGE 0 1 2 3 4 5 6 7 8 9 Heat 1 MBB-RLY8 IGC1 OFF ON ON ON ON ON ON ON ON ON Heat 2 MBB-RLY7 MGV1 OFF OFF ON OFF ON ON OFF OFF ON ON RELAY OUTPUT Heat 3 Heat 4 SCB-RLY1 SCB-RLY2 IGC2 MGV2 OFF OFF OFF OFF OFF OFF ON OFF ON OFF ON ON ON OFF ON ON ON ON ON ON 0 25 33 50 58 67 75 83 92 100 5 equivalent duct diameters downstream of the unit. Also, care should be taken to avoid placing the thermistor within a direct line-of-sight of the heating element to avoid radiant effects. Run a new two-wire conductor cable from the control box through the low voltage conduit into the space inside the building and route the cable to the new sensor location. Installing a New Sensor — Procure a duct-mount temperature sensor (Carrier P/N 33ZCSENPAT or equivalent 10-kilo-ohm at 25C NTC [negative temperature coefficient] sensor). Install the sensor through the side wall of the duct and secure. Re-Using the Factory SAT Sensor — The factory sensor is attached to the left-hand side of the supply fan housing. Disconnect the sensor from the factory harness. Fabricate a mounting method to insert the sensor through the duct wall and secure in place. Attach the new conductor cable to the sensor leads and terminate in an appropriate junction box. Connect the opposite end inside the unit control box at the factory leads from MBB J8 terminals 11 and 12 (PNK) leads. Secure the unattached PNK leads from the factory harness to ensure no accidental contact with other terminals inside the control box. TEMPERING MODE — In a vent or cooling mode, the economizer at minimum position may send extremely cold outside air down the ductwork of the building. Therefore it may be necessary to bring heat on to counter-effect this low supply-air temperature. This is referred to as the tempering mode. Table 51 — IGC LED Indicators ERROR CODE Normal Operation Hardware Failure Fan On/Off Delay Modified Limit Switch Fault Fame Sense Fault Five Consecutive Limit Switch Faults Ignition Lockout Fault Ignition Switch Fault Rollout Switch Fault Internal Control Fault Software Lockout Heat 5 SCB-RLY3 IGC3 OFF OFF OFF OFF OFF OFF ON ON ON ON LED INDICATION On Off 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes NOTES: 1. There is a 3-second pause between error code displays. 2. If more than one error code exists, all applicable error codes will be displayed in numerical sequence. 3. Error codes on the IGC will be lost if power to the unit is interrupted. RELOCATE SAT FOR HEATING-LINKAGE APPLICATIONS — If Configuration→HEAT→LAT.M is set to YES, the supply air temperature thermistor (Temperatures→AIR.T → SAT) must be relocated downstream of the installed heating device. This only applies to two-stage gas or electric heating types (Configuration→HEAT→ HT.CF=1 or 2). Determine a location in the supply duct that will provide a fairly uniform airflow. Typically this would be a minimum of 60 in HVACMODE, the tempering routine will re-assess the tempering set point which may cause the control to continue or exit tempering mode. Setting up the System — The relevant set points for tempering are located at the local display under Setpoints: ITEM T.PRG T.CL T.V.OC T.V.UN EXPANSION Tempering Purge SASP Tempering in Cool SASP Tempering Vent Occ SASP Tempering Vent Unocc. SASP –20-80 dF CCN DEFAULT POINT TEMPPURG 50 5-75 dF TEMPCOOL 5 –20-80 dF TEMPVOCC 65 –20-80 dF TEMPVUNC 50 RANGE UNITS Static Pressure Control — Variable air volume (VAV) air-conditioning systems must provide varying amounts of air to the conditioned space. As air terminals downstream of the unit modulate their flows, the unit must simply maintain control over duct static pressure in order to accommodate the needs of the terminals, and therefore to meet the varying combined airflow requirement. The unit design includes two alternative optional means of accommodating this requirement. This section describes the technique by which this control takes place. A unit intended for use in a VAV system can be equipped with either an optional variable frequency drive (VFD) or inlet guide vanes (IGV) for the supply fan. The speed of the fan or the position of the IGV can be controlled directly by the ComfortLink™ controls. A transducer is used to measure duct static pressure. The signal from the transducer is received by the RCB board and is then used in a PID control routine that outputs a 4 to 20 mA signal to the VFD, or a digital LEN signal to the IGV. Generally only VAV systems utilize static pressure control. It is required because as the system VAV terminals modulate closed when less air is required, there must be a means of controlling airflow from the unit, thereby effectively preventing overpressurization and its accompanying problems. The three most fundamental configurations for most applications are Configuration→SP→SP.CF, which is the static pressure control type, Configuration→SP→SP.S, used to enable the static pressure sensor, and Configuration→SP →SP.SP, the static pressure set point to be maintained. OPERATION — On units equipped with either VFD or IGV and a proper static pressure sensor, when SP.CF, SP.S and SP.SP are configured, a PID routine periodically measures the duct static pressure and calculates the error from set point. This error at any point in time is simply the duct static pressure set point minus the measured duct static. The error becomes the basis for the Proportional term of the PID. The routine also calculates the integral of the error over time, and the derivative (rate of change) of the error. A value is calculated as a result of this PID routine, and this value is then used to create an output signal used to adjust the IGV or VFD to maintain the static pressure set point. Static pressure reset is the ability to force a lowering of the static pressure set point through an external control signal. Explained in detail further below, the control supports this in two separate ways; through a 4 to 20 mA signal input wired to TB203 terminals 6 and 7 (thereby facilitating third party control), or via CCN. In the latter case, this feature leverages the communications capabilities of VAV systems employing ComfortID™ terminals under linkage. The system dynamically determines and maintains an optimal duct static pressure set point based on the actual load conditions in the space. This can result in a significant reduction in required fan energy by lowering the set point to only the level required to maintain adequate airflow throughout the system. SETTING UP THE SYSTEM — The options for static pressure control are found under the Local Display Mode Configuration→SP. See Table 52. Operation — First, the unit must be in a vent mode, a low cool, or a high cool HVAC mode to be considered for a tempering mode. Secondly, the tempering mode is only allowed when the rooftop is configured for staged gas or hydronic heating (Configuration→HEAT→HT.CF=3 or 4). If the control is configured for staged gas or hydronic heating and the control is in a vent, low cool, or high cool HVAC mode, and the rooftop control is in a situation where the economizer must maintain a minimum position/minimum cfm, then the evaporator discharge temperature (EDT) will be monitored. If the EDT falls below a particular trip point then the tempering mode may be called out: HVAC mode = “Tempering Vent” HVAC mode = “Tempering LoCool” HVAC mode = “Tempering HiCool” The decision making/selection process for the tempering trip set point is as follows: • If an HVAC cool mode is in effect, then the vent trip point is T.CL. • If in a pre-occupied purge mode (Operating Modes→ MODE→IAQ.P=ON), then the trip point is T.PRG. • If in an occupied mode (Operating Modes→MODE→ IAQ.P=ON), then the trip point is TEMPVOCC. • For all other cases, the trip point is TEMPVUNC. NOTE: The unoccupied economizer free cooling does not qualify as a HVAC cool mode as it is an energy saving feature and has its own OAT lockout already. The unoccupied free cooling mode (HVAC mode = Unocc. Free Cool) will override any unoccupied vent mode from triggering a tempering mode. If OAT is above the chosen tempering set point, tempering will not be allowed. Additionally, tempering mode is locked out if any stages of mechanical cooling are present. A minimum amount of time must pass before calling out any tempering mode. In effect, the EDT must fall below the trip point value –1° F continuously for a minimum of 2 minutes. Also, at the end of a mechanical cooling cycle, there must be a minimum 10 minutes of delay allowed before considering a tempering during vent mode in order to allow any residual cooling to dissipate from the evaporator coil. If the above conditions are met, the algorithm is free to select the tempering mode (MODETEMP). If a tempering mode becomes active, the modulating heat source (staged gas or hot water) will attempt to maintain leaving-air temperature (LAT) at the tempering set point used to trigger the tempering mode. The technique for modulation of set point for staged gas and hydronic heat is the same as in a heat mode. More information regarding the operation of heating can be referenced in the Heating Control section. Recovery from a tempering mode (MODETEMP) will occur when the EDT rises above the trip point. On any change 61 Table 52 — Static Pressure Control Configuration ITEM SP →SP.CF →SP.S →SP.LO →SP.HI →SP.SP →SP.MN →SP.MX →SP.FS →SP.RS →SP.RT →SP.LM →SP.EC →S.PID →S.PID→SP.TM →S.PID→SP.P →S.PID→SP.I →S.PID→SP.D →ACT.C →ACTC→SN.1 →ACTC→SN.2 →ACTC→SN.3 →ACTC→SN.4 →ACTC→SN.5 →ACTC→C.A.LM EXPANSION SUPPLY STATIC PRESS.CFG. Static Pressure Config Static Pressure Sensor Static Press. Low Range Static Press. High Range Static Pressure Setpoint VFD-IGV Minimum Speed VFD-IGV Maximum Speed VFD-IGV Fire Speed Over. Stat. Pres. Reset Config SP Reset Ratio (″/dF) SP Reset Limit in iwc (″) SP Reset Econo.Position STAT.PRESS.PID CONFIGS Static Press. PID Run Rate Static Press. Prop. Gain Static Pressure Intg. Gain Static Pressure Derv. Gain IGV ACTUATOR CONFIGS IGV Serial Number 1 IGV Serial Number 2 IGV Serial Number 3 IGV Serial Number 4 IGV Serial Number 5 IGV Cntrl Angle Lo Limit RANGE 0, 1, 2 Enable/Disable –10 - 0 0 - 10 0-5 0 - 100 0 - 100 0 - 100 0-4 0 - 2.00 0 - 2.00 0 - 100 5 - 120 0-5 0-2 0-5 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 UNITS in. W.C. in. W.C. in. W.C. % % % % sec deg CCN POINT DEFAULT STATICFG SPSENS SP_LOW SP_HIGH SPSP STATPMIN STATPMAX STATPFSO SPRSTCFG SPRRATIO SPRLIMIT ECONOSPR 0 Disable 0 5 1.5 20 100 100 0 0.2 0.75 5 SPIDRATE STATP_PG STATP_IG STATP_DG 15 0.5 0.5 0.3 IGV_SN1 IGV_SN2 IGV_SN3 IGV_SN4 IGV_SN5 IGV_CALM 0 0 0 0 0 25 VFD-IGV Minimum Speed (SP.MN) — This is the minimum speed for the supply fan VFD or the minimum opening for the supply fan IGV. Typically the value is chosen to maintain a minimum level of ventilation. NOTE: Most VFDs have a built-in minimum speed adjustment which must be configured for 0% when using ComfortLink controls for static pressure control. VFD-IGV Maximum Speed (SP.MX) — This is the maximum speed for the supply fan VFD or the maximum opening for the supply fan IGV. This is usually set to 100%. VFD-IGV Fire Speed Override (SP.FS) — This is the speed that the supply fan VFD or the supply fan IGV will use during the fire modes; pressurization, evacuation and purge. This is usually set to 100%. Static Pressure Reset Configuration (SP.RS) — This option is used to configure the static pressure reset function. When SP.RS = 0, there is no static pressure reset via an analog input. When SP.RS = 1, there is static pressure reset based on the CEM 4-20MA input and ranged from 0 to 3 in. wg. When SP.RS = 2, there is static pressure reset based on RAT and defined by SP.RT and SP.LM. When SP.RS = 3, there is static pressure reset based on SPT and defined by SP.RT and SP.LM. When SP.RS = 4, there is VFD speed control where 0 mA = 0% speed and 20 mA = 100% (SP.MN and SP.MX will override). Static Pressure Reset Ratio (SP.RT) — This option defines the reset ratio in terms of static pressure versus temperature. The reset ratio determines how much is the static pressure reduced for every degree below set point for RAT or SPT. Static Pressure Reset Limit (SP.LM) — This option defines the maximum amount of static pressure reset that is allowed. This is sometimes called a “clamp.” NOTE: Resetting static pressure via RAT and SPT is primarily a constant volume application which utilizes a VFD. The reasoning is that there is significant energy savings in slowing down a supply fan as opposed to running full speed with supply air reset. Maintaining the supply air set point and Static Pressure Configuration (SP.CF) — This variable is used to configure the use of ComfortLink™ controls for static pressure control. It has the following options: 0 (None) — No static pressure control by ComfortLink controls. This would be used for a constant volume (CV) application when static pressure control is not required or for a VAV application if there will be third-party control of the VFD or IGV. In this latter case, a suitable means of control must be field installed. 1 (VFD Control) — This will enable the use of ComfortLink controls for static pressure control via a supply fan VFD. 2 (IGV Control) — This will enable the use of ComfortLink controls for static pressure control via supply fan inlet guide vanes (IGV). Static Pressure Sensor (SP.S) — This variable enables the use of a supply duct static pressure sensor. This must be enabled to use ComfortLink controls for static pressure control. If using a third-party control for the VFD or IGV, this should be disabled. Static Pressure Low Range (SP.LO) — This is the minimum static pressure that the sensor will measure. For most sensors this will be 0 in. wg. The ComfortLink controls will map this value to a 4 mA sensor input. Static Pressure High Range (SP.HI) — This is the maximum static pressure that the sensor will measure. Commonly this will be 5 in. wg. The ComfortLink controls will map this value to a 20 mA sensor input. Static Pressure Set Point (SP.SP) — This is the static pressure control point. It is the point against which the ComfortLink controls compares the actual measured supply duct pressure for determination of the error that is used for PID control. Generally one would set SP.SP to the minimum value necessary for proper operation of air terminals in the conditioned space at all load conditions. Too high of a value will cause unnecessary fan motor power consumption at part-load conditions and/or noise problems. Too low a value will result in insufficient airflow. Additional information will be found on page 63, under Static Pressure Reset. 62 IGV Serial Number 4 (ACT.C→SN.4) — This variable records the fourth segment of the IGV actuator serial number. IGV Serial Number 5 (ACT.C→SN.5) — This variable records the fifth segment of the IGV actuator serial number. IGV Control Angle Low Limit (ACT.C→C.A.LM) — The IGV actuator learns what its end stops are though a calibration at the factory. Field-installed actuators may be calibrated in the Service Test mode. When an actuator learns its end stops through this internal calibration, it remembers what its “control angle range” is. From then on, the actuator will resolve this control angle and express its operation in a percentage (%) of this learned range. If the IGV has not learned a sufficient control angle range during calibration, it will be unable to control itself properly. For this reason the IGV actuator used in the Z Series control system has a configurable control angle alarm low limit in its “Economizer Actuator Configs” group, ACT.C. (C.A.LM). If the control angle learned through calibration is less than Configuration→SP→ACT.C→C.A.LM, an alert will occur and the actuator will not function. NOTE: This configuration does not typically need adjustment. It is configurable for the small number of jobs which may require a custom solution or workaround. STATIC PRESSURE RESET — The configuration for Static Pressure Reset is found under Configuration→UNIT. slowing down the fan has the additional benefit of working around dehumidification concerns. Static Pressure Reset Economizer Position (SP.EC) — This option effectively resets ECONOMIN to fully occupied ventilation position, to account for the drop in static pressure during static pressure reset control. The static pressure reset for the calculation cannot be larger than the supply air static set point (SPSP). The calculation is as follows: (Static Pressure Reset/SPSP) x (ECONOSPR – ECONOMIN) As an example, the static pressure set point (SPSP) = 1.5 in. wg. The current static pressure reset is set to 0.5 in. wg. The settings for ECONOSPR = 50% and ECONOMIN = 20%. Therefore, the amount to add to the economizer’s ECONOMIN configuration is: (0.5/1.5) x (50-20) = 10%. In effect, for the positioning of the economizer, ECONOMIN would now be replaced by ECONOMIN + 10%. Static Pressure PID Config (S.PID) — Static pressure PID configuration can be accessed under this heading in the Configuration→SP submenu. Under most operating conditions the control PID factors will not require any adjustment and the factory defaults should be used. If persistent static pressure fluctuations are detected, small changes to these factors may improve performance. Decreasing the factors generally reduce the responsiveness of the control loop, while increasing the factors increase its responsiveness. Note the existing settings before making changes, and seek technical assistance from Carrier before making significant changes to these factors. Static Pressure PID Run Rate (S.PID→SP.TM) — This is the number of seconds between duct static pressure readings taken by the ComfortLink PID routine. Static Pressure Proportional Gain (S.PID→SP.P) — This is the proportional gain for the static pressure control PID control loop. Static Pressure Integral Gain (S.PID→SP.I) — This is the integral gain for the static pressure control PID control loop. Static Pressure Derivative Gain (S.PID→SP.D) — This is the derivative gain for the static pressure control PID control loop. IGV Actuator Configs (ACT.C) — Every actuator used in the Z Series control system has its own unique serial number. The rooftop control uses this serial number to communicate with the actuator over the local equipment network (LEN). These serial numbers are programmed at the factory and should not need changing. Should field replacement of an actuator become necessary, it will be necessary to configure the serial numbers of the new actuator. Five individual numbers make up this serial number and these can be programmed to match the serial number of the actuator in its “IGV Actuator Configs” group, ACT.C (SN.1, SN.2, SN.3, SN.4, SN.5). NOTE: The serial numbers for all LEN actuators can be found inside the control doors of the unit as well as on the actuator itself. If an actuator is replaced in the field, it is a good idea to remove the additional peel-off serial number sticker on the actuator and use it to replace the old one inside the control panel doors. The format for the overall serial number is 111-222-333-444-555, where each of these segments can be 1, 2 or 3 digits in length. Valid numbers are in the range 1-255. IGV Serial Number 1 (ACT.C→SN.1) — This variable records the first of the five segments of the IGV digital LEN actuator serial number. The complete serial number is used by the ComfortLink controls to communicate with the actuator. IGV Serial Number 2 (ACT.C→SN.2) — This variable records the second segment of the IGV actuator serial number. IGV Serial Number 3 (ACT.C→SN.3) — This variable records the third segment of the IGV actuator serial number. ITEM EXPANSION RANGE CCN POINT DEFAULT →SENS→SP.RS Static Press. Reset Sensor. Enable/ Disable SPRSTSEN Disable Static Pressure Reset Sensor (SP.RS) — If the outdoor air quality sensor is not configured (Configuration→IAQ →AQ.CF→OQ.A.C=0), then it is possible to use the outdoor air quality sensor location on the CEM board to perform static pressure reset via an external 4-20 mA input. Enabling this sensor will give the user the ability to reset from 0 to 3-in. wg of static pressure. The reset will apply to the supply static pressure set point (Configuration→SP→SP.SP), where 4 mA = 0-in. wg and 20 mA = 3-in. wg. As an example, the static pressure reset input is measuring 6 mA, and the input is resetting 2 mA of its 16 mA control range. The 4 to 20 mA range corresponds directly to the 0 to 3 in. wg of reset. Therefore 2 mA reset is 2/16 * 3-in. wg = 0.375-in. wg of reset. If the static pressure set point (SP.SP) = 1.5-in. wg, then the static pressure control point for the system will be reset 1.5 – 0.375 = 1.125-in. wg. For third party 4 to 20 mA SP reset, wire the input to TB203 terminals 6 and 7. For reset via a connected ComfortID™ system, the Linkage Coordinator terminal monitors the primary-air damper position of all the terminals in the system. It then calculates the amount of supply static pressure reduction necessary to cause the most open damper in the system to open more than the minimum value (60%) but not more than the maximum value (90% or negligible static pressure drop). This is a dynamic calculation, which occurs every two minutes whenever the system is operating. It ensures that the supply static is sufficient to supply the required airflow at the worst case terminal but not more than necessary, so that the air terminals do not have to operate with a pressure drop greater than required to maintain the airflow set point of each individual terminal in the system. As the system operates, if the most open damper opens more than 90%, the system recalculates the pressure reduction variable and Configuration→UNIT →SENS→SP.RS, the amount of reset, is reduced. If the most open damper closes to less than 60%, the system recalculates the pressure reduction variable and SP.RS is increased. With this system, one needs to enter as the static pressure set point SP.SP either a maximum duct design pressure or maximum equipment pressure, whichever is less. The system will 63 determine the actual set point required and deliver the required airflow to every terminal under the current load conditions. As the conditions and airflow requirements at each terminal change throughout the operating period, so will SP.RS and the unit’s effective static pressure set point. In the unlikely chance that both static pressure reset control signals are simultaneously present, the CCN signal will take precedence. RELATED POINTS — These points represent static pressure control and static pressure reset inputs and outputs. See Table 53. Static Pressure mA (SP.M) — This variable reflects the value of the static pressure sensor signal received by the ComfortLink™ controls. It may in some cases be helpful in troubleshooting. Static Pressure mA Trim (SP.M.T) — This input allows a modest amount of trim to the 4 to 20 mA static pressure transducer signal, and can be used to calibrate a transducer. Static Pressure Reset mA (SP.R.M) — This input reflects the value of a 4 to 20 mA static pressure reset signal applied to TB203 terminals 6 and 7, from a third party control system. Static Pressure Reset (SP.RS) — This variable reflects the value of a static pressure reset signal applied from a CCN system. The means of applying this reset is by forcing the value of the variable SPRESET through CCN. Supply Fan VFD Speed (S.VFD) — This output can be used to check on the actual speed of the VFD. This may be helpful in some cases for troubleshooting. IGV Actuator Current Pos (IGV.P) — This output reflects the current position of the supply fan inlet guide vanes. This may be helpful in some cases for troubleshooting. IGV Act. Commanded Pos (IGV.C) — This output reflects the commanded position of the supply fan inlet guide vanes. By comparing this to the actual position of the guide vanes, this may be helpful in some cases for troubleshooting. Table 54 — Fan Status Monitoring Configuration ITEM SFS.S SFS.M EXPANSION RANGE CCN POINT Fan Fail Shuts Down Unit Yes/No SFS_SHUT Fan Stat Monitoring Type 0 - 2 SFS_MON Fan Stat Monitoring Type (SFS.M) — This configuration selects the type of fan status monitoring to be performed. 0 - NONE — No switch or monitoring 1 - SWITCH — Use of the fan status switch 2 - SP RISE — Monitoring of the supply duct pressure. Fan Fail Shuts Down Unit (SFS.S) — This configuration will configure the unit to shut down on a supply fan status fail or simply alert the condition and continue to run. When configured to YES, the control will shut down the unit if supply fan status monitoring fails and send out an alarm. If set to no, the control will not shut down the unit if supply fan status monitoring fails but send out an alert. SUPPLY FAN STATUS MONITORING LOGIC — Regardless of whether the user is monitoring a discrete switch or is monitoring static pressure, the timings for both techniques are the same and rely upon the configuration of static pressure control. The configuration that determines static pressure control is Configuration→SP→SP.CF. If this configuration is set to 0 (none), a fan failure condition must wait 60 continuous seconds before taking action. If this configuration is 1 or 2 (VFD or IGV), a fan failure condition must wait 3 continuous minutes before taking action. If the unit is configured to monitor a fan status switch (SFS.M = 1), and if the supply fan commanded state does not match the supply fan status switch for 3 continuous minutes, then a fan status failure has occurred. If the unit is configured for supply duct pressure monitoring (SFS.M = 2), then • If the supply fan is requested ON and the static pressure reading is not greater than 0.2 in. wg for 3 continuous minutes, a fan failure has occurred. • If the supply fan is requested OFF and the static pressure reading is not less than 0.2-in. wg for 3 continuous minutes, a fan failure has occurred. Fan Status Monitoring GENERAL — The Z Series ComfortLink controls offer the capability to detect a failed supply fan through either a duct static pressure transducer or an accessory discrete switch. The fan status switch is an accessory that allows for the monitoring of a discrete switch, which trips above a differential pressure drop across the supply fan. For any unit with a factory-installed duct static pressure sensor, it is possible to measure duct pressure rise directly, which removes the need for a differential switch. Any unit with an installed supply fan VFD or inlet guide vanes will have the duct static pressure sensor as standard. SETTING UP THE SYSTEM — The fan status monitoring configurations are located in Configuration→UNIT. See Table 54. Dirty Filter Switch — The unit can be equipped with a field-installed accessory dirty filter switch. The switch is located in the filter section. If a dirty filter switch is not installed, the switch input is configured to read “clean” all the time. To enable the sensor for dirty filter monitoring set Configuration→UNIT→SENS→FLT.S to ENABLE. The state of the filter status switch can be read at Inputs→GEN.I→ FLT.S. See Table 55. Table 53 — Static Pressure Reset Related Points ITEM Inputs → 4-20 → SP.M → 4-20 → SP.M.T → 4-20 →SP.R.M → RSET →SP.RS Outputs → Fans → S.VFD → ACTU → IGV.P → ACTU → IGV.C EXPANSION RANGE UNITS CCN POINT Static Pressure mA Static Pressure mA Trim Static Pressure Reset mA Static Pressure Reset 4-20 -2.0 → +2.0 4-20 0.0-3.0 mA mA mA in. wg SP_MA SPMATRIM SPRST_MA SPRESET Supply Fan VFD Speed IGV Actuator Current Pos IGV Act. Commanded Pos 0-100 0-100 0-100 % % % SFAN_VFD IGV_RPOS IGV_CPOS 64 DEFAULT 0.0 0.0 the section on indoor air quality for further information on how to reset the economizer further to gain energy savings and to more carefully monitor IAQ problems. Economizer Maximum Position (EC.MX) — The upper limit of the economizer may be limited by setting EC.MX. It defaults to 98% to avoid problems associated with slight changes in the economizer damper’s end stop over time. Typically this will not need to be adjusted. Economizer Trim for Sum Z? (E.TRM) — Sum Z is the adaptive cooling control algorithm used for multiple stages of mechanical cooling capacity. The configuration option, E.TRM is typically set to Yes, and allows the economizer to modulate to the same control point (Sum Z) that is used to control capacity staging. The advantage is lower compressor cycling coupled with tighter temperature control. Setting this option to No will cause the economizer, if it is able to provide free cooling, to open to the Economizer Max. Position (EC.MX) during mechanical cooling. ECONOMIZER OPERATION — There are four potential elements which are considered concurrently which determine whether the economizer is able to provide free cooling: 1. Dry bulb changeover (outside-air temperature qualification) 2. Enthalpy switch (discrete control input monitoring) 3. Economizer changeover select (E.SEL economizer changeover select configuration option) 4. Outdoor dewpoint limit check (requires an installed outdoor relative humidity sensor installed) Dry Bulb Changeover — Outside-air temperature may be viewed under Temperatures→AIR.T→OAT. The control constantly compares its outside-air temperature reading against the high temperature OAT lockout (OAT.L). If the temperature reads above OAT.L, the economizer will not be allowed to perform free cooling. NOTE: If the user wishes to disable the enthalpy switch from running concurrently, a field-supplied jumper must be installed between TB201 terminals 3 and 4. Enthalpy Switch — The state of the enthalpy switch can be viewed under Inputs→GEN.I→ENTH. Enthalpy switches are installed as standard on all Z Series rooftops. When the switch reads high, free cooling will be disallowed. The enthalpy switch opens (reads high) when the outdoor enthalpy is above 24 Btu/lb or dry bulb temperature is above 70 F and will close when the outdoor enthalpy is below 23 Btu/lb or the dry bulb temperature is below 69.5 F. NOTE: The enthalpy switch has both a low and a high output. To use this switch as designed the control must be connected to the low output. Additionally there is a switch logic setting for the enthalpy switch under Configuration→SW.LG→ENT.L. This setting must be configured to closed (CLSE) to work properly when connected to the low output of the enthalpy switch. There are two jumpers under the cover of the enthalpy switch. One jumper determines the mode of the enthalpy switch/receiver. The other is not used. For the enthalpy switch, the factory setting is M1 and should not need to be changed. See Fig. 8 for a diagram showing the settings on the enthalpy switch. Table 55 — Dirty Filter Switch Points ITEM Configuration→UNIT →SENS→FLT.S Inputs→GEN.I →FLT.S EXPANSION RANGE CCN POINT FLTS_ENA Filter Enable/ Stat.Sw.Enabled ? Disable Filter Status Input DRTY/CLN FLTS Monitoring of the filter status switch is disabled in the Service Test mode and when the supply fan is not commanded on. If the fan is on and the unit is not in a test mode and the filter status switch reads “dirty” for 2 continuous minutes, an alert is generated. Recovery from this alert is done through a clearing of all alarms or after cleaning the filter and the switch reads “clean” for 30 seconds. NOTE: The filter switch should be adjusted to allow for the operating cfm and the type of filter. Refer to the accessory installation instructions for information on adjusting the switch. Economizer — The economizer control is used to manage 0% 50% 100% OFF M1 M2 M3 the outside and return air dampers of the unit to provide ventilation air as well as free cooling based on several configuration options. This section contains a description of the economizer and its ability to provide free cooling. See the section on indoor air quality for more information on setting up and using the economizer to perform demand controlled ventilation (DCV). See the Third Party Control section for a description on how to take over the operation of the economizer through external control. The economizer system also permits this unit to perform smoke control functions based on external control switch inputs. Refer to the Smoke Control Modes section for detailed discussions. Economizer control can be based on automatic control algorithms using unit-based set points and sensor inputs. This economizer control system can also be managed through external logic systems. The economizer system is a factory-installed option. This option includes a factory-installed enthalpy control device to determine the changeover condition that permits free cooling operation. This unit can also have the following devices installed to enhance economizer control: • Outside air humidity sensor • Return air humidity sensor • Outside airflow control NOTE: All these options require the controls expansion module (CEM). The Z Series economizer damper is managed by a communicating actuator motor(s) over the unit’s Local Equipment Network (LEN). This provides the ability of the control system to monitor, diagnose and report the health and operation of the actuator and damper system to the local display and CCN network, thus providing extensive diagnostic tools to servicers. SETTING UP THE SYSTEM — The economizer configuration options are under the Local Display Mode Configuration →ECON. See Table 56. Economizer Installed? (EC.EN) — If an economizer is not installed or is to be completely disabled the configuration option EC.EN may be set to No. Otherwise in the case of an installed economizer, this option must be set to Yes. Economizer Actuator 2 Installed? (EC2.E) — For 48/50Z055105 units, a second economizer actuator is required. For sizes 055-105, set this configuration to Yes. Economizer Minimum Position (EC.MN) — The configuration option EC.MN is the economizer minimum position. See Fig. 8 — Enthalpy Switch Jumper Positions 65 Table 56 — Economizer Configuration Table ITEM EC.EN EC2.E EC.MN EC.MX E.TRM E.SEL OA.E.C OA.EN OAT.L O.DEW ORH.S CFM.C OCF.S O.C.MX O.C.MN O.C.DB E.CFG E.P.GN E.RNG E.SPD E.DBD UEFC FC.CF FC.TM FC.L.O ACT.C SN.1.1 SN.1.2 SN.1.3 SN.1.4 SN.1.5 C.A.L1 SN.2.1 SN.2.2 SN.2.3 SN.2.4 SN.2.5 C.A.L2 EXPANSION Economizer Installed? Econ.Act.2 Installed? Economizer Min.Position Economizer Max.Position Economzr Trim For SumZ ? Econ ChangeOver Select OA Enthalpy ChgOvr Selct Outdr.Enth Compare Value High OAT Lockout Temp OA Dewpoint Temp Limit Outside Air RH Sensor OUTDOOR AIR CFM CONTROL Outdoor Air CFM Sensor Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband ECON.OPERATION CONFIGS Economizer Prop.Gain Economizer Range Adjust Economizer Speed Adjust Economizer Deadband UNOCC.ECON.FREE COOLING Unoc Econ Free Cool Cfg Unoc Econ Free Cool Time Un.Ec.Free Cool OAT Lock ECON.ACTUATOR CONFIGS Econ Serial Number 1 Econ Serial Number 2 Econ Serial Number 3 Econ Serial Number 4 Econ Serial Number 5 Econ Ctrl Angle Lo Limit Econ 2 Serial Number 1 Econ 2 Serial Number 2 Econ 2 Serial Number 3 Econ 2 Serial Number 4 Econ 2 Serial Number 5 Econ 2 Ctrl Angle Lo Limit RANGE Yes/No Yes/No 0 - 100 0 - 100 Yes/No 0-3 1-5 18 - 28 -40 - 120 50 - 62 Enable/Disable Enable/Disable 0 - 20000 0 - 20000 200 - 1000 0.7 - 3.0 0.5 - 5 0.1 - 10 0.1 - 2 0-2 0 - 720 40 - 70 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 UNITS CCN POINT ECON_ENA ECON_TWO ECONOMIN ECONOMAX ECONTRIM ECON_SEL OAEC_SEL OAEN_CFG OAT_LOCK OADEWCFG OARHSENS DEFAULT Yes No 5 98 Yes 0 4 24 60 55 Disable OCFMSENS OACFMMAX OACFMMIN OACFM_DB Disable 2000 0 400 ^F EC_PGAIN EC_RANGE EC_SPEED EC_DBAND 1 2.5 0.75 0.5 min dF UEFC_CFG UEFCTIME UEFCNTLO 0 120 50 ECON_SN1 ECON_SN2 ECON_SN3 ECON_SN4 ECON_SN5 ECONCALM ECN2_SN1 ECN2_SN2 ECN2_SN3 ECN2_SN4 ECN2_SN5 ECN2CALM 0 0 0 0 0 85 0 0 0 0 0 85 % % dF dF CFM CFM CFM ^F is required. Once the sensor and board are installed, enable Configuration→ECON→ORH.S, the outdoor relative humidity sensor configuration option. This will automatically enable the CEM board, if it is not enabled already. If the user selects one of the Honeywell curves, A,B,C or D, then OA.E.C options 1-4 should be selected. See Fig. 9 for a diagram of these curves on a psychrometric chart. OA.E.C = 1 Honeywell A Curve OA.E.C = 2 Honeywell B Curve OA.E.C = 3 Honeywell C Curve OA.E.C = 4 Honeywell D Curve OA.E.C = 5 custom enthalpy curve If the user selects OA.E.C = 5, a direct compare of outdoor enthalpy versus an enthalpy set point is done. This outdoor enthalpy set point limit is configurable, and is called Configuration→ECON→OA.EN. Depending on what Configuration→ECON→OA.E.C is configured for, if the outdoor enthalpy exceeds the Honeywell curves or the outdoor enthalpy compare value (Configuration →ECON→OA.EN), then free cooling will not be allowed. NOTE: If the user wishes to disable the standard enthalpy control from running concurrently, a field-supplied jumper must be installed between TB201 terminals 3 and 4. Differential Enthalpy Changeover — This option compares the outdoor-air enthalpy to the return air enthalpy and chooses the option with the lowest enthalpy. This option should be used in climates with high humidity conditions. This option uses both humidity sensors and dry bulb sensors to calculate the enthalpy of the outdoor and return air. An accessory outdoor air humidity sensor (ORH.S) and return air humidity sensor (RRH.S) are used. The outdoor air relative humidity sensor config (ORH.S) and return air humidity sensor config (Configuration→SENS→RRH.S) must be enabled. NOTE: If the user wishes to disable the standard enthalpy control from running concurrently, a field-supplied jumper must be installed between TB201 terminals 3 and 4. Outdoor Dewpoint Limit Check — If an outdoor relative humidity sensor is installed, the control is able to calculate the The enthalpy switch may also be field converted to a differential enthalpy switch by field installing an enthalpy sensor (33CSENTSEN or HH57ZC001). The enthalpy switch/receiver remains installed in its factory location to sense outdoor air enthalpy. The additional enthalpy sensor (33CSENTSEN) is mounted in the return airstream to measure return air enthalpy. The enthalpy control jumper must be changed from M1 to M2 for differential enthalpy control. For the 2-wire return air enthalpy sensor, connect power to the Vin input and signal to the 4-20 loop input. See Fig. 8 for diagram showing the settings and inputs on the enthalpy switch. There is another way to accomplish differential enthalpy control when both an outdoor and return air relative humidity sensor are present. See Economizer Changeover Select section below for further information. ECONOMIZER CHANGEOVER SELECT (E.SEL) — The control is capable of performing any one of the following changeover types in addition to both the dry bulb lockout and the standard external input: E.SEL = 0 none E.SEL = 1 Differential Dry Bulb Changeover E.SEL = 2 Outdoor Enthalpy Changeover E.SEL = 3 Differential Enthalpy Changeover Differential Dry Bulb Changeover — As both return air and outside air temperature sensors are installed as standard on these units, the user may select this option, E.SEL = 1, to perform a qualification of return and outside air in the enabling/ disabling of free cooling. If this option is selected and outsideair temperature is greater than return-air temperature, free cooling will not be allowed. Outdoor Enthalpy Changeover — This option should be used in climates with higher humidity conditions. The Z Series control can use an enthalpy switch or enthalpy sensor, or the standard installed outdoor dry bulb sensor and an accessory relative humidity sensor to calculate the enthalpy of the air. Setting Configuration→ECON→E.SEL = 2 requires that the user configure Configuration→ECON→OA.E.C, the Outdoor Enthalpy Changeover Select, and install an outdoor relative humidity sensor. A control expansion module (CEM) 66 outdoor air dewpoint temperature and will compare this temperature against the outside air dewpoint temperature limit configuration (Configuration→ECON→O.DEW). If the outdoor air dewpoint temperature is greater than O.DEW, free cooling will not be allowed. Fig. 10 shows a horizontal limit line in the custom curve of the psychrometric chart. This is the outdoor air dewpoint limit boundary. Custom Psychrometric Curves — Refer to the psychrometric chart and the standard Honeywell A-D curves in Fig. 9. The curves start from the bottom and rise vertically, angle to the left and then fold over. This corresponds to the limits imposed by dry bulb changeover, outdoor enthalpy changeover and outdoor dewpoint limiting respectively. Therefore, it is now possible to create any curve desired with the addition of one outdoor relative humidity sensor and the options for changeover now available. See Fig. 10 for an example of a custom curve constructed on a psychrometric chart. Configuring the Economizer to Communicate Via Actuator Serial Number — Every actuator used in the Z Series control system has its own unique serial number. The rooftop control uses this serial number to communicate with the actuator over the local equipment network (LEN). These serial numbers are programmed at the factory and should not need changing. Should field replacement of an actuator become necessary, it will be required to configure the serial numbers of the new actuator. Five individual numbers make up this serial number and these can be programmed to match the serial number of the actuator in its Economizer Actuator Configs group, ACT.C (SN1.1, SN1.2, SN1.3, SN1.4, SN1.5, SN2.1, SN2.2, SN2.3, SN2.4, SN2.5). NOTE: The serial numbers for all LEN actuators can be found inside the control doors of the unit as well as on the actuator itself. If an actuator is replaced in the field, it is a good idea to remove the additional peel-off serial number sticker on the actuator and cover up the old one inside the control doors. CONTROL CURVE A B C D CONTROL POINT (approx Deg) AT 50% RH 73 68 63 58 Fig. 9 — Psychrometric Chart for Enthalpy Control Fig. 10 — Custom Changeover Curve Example 67 • No fan failure when configured to for unit to shut down on a fan failure If all of the above conditions are satisfied: Unoccupied Economizer Free Cooling will start when both of the following conditions are true: {SPT > (OCSP + 2)} AND {SPT > (OAT + 8)} The Unoccupied Economizer Free Cooling Mode will stop when either of the following conditions are true: {SPT < OCSP} OR {SPT < (OAT + 3)} where SPT = Space Temperature and OCSP = Occupied Cooling Set Point. When the Unoccupied Economizer Free Cooling mode is active, the supply fan is turned on and the economizer damper modulated to control to the supply air set point (Setpoints→ SASP) plus any supply air reset that may be applied (Inputs→ RSET→SA.S.R). OUTDOOR AIR CFM CONTROL — If an outdoor air cfm flow station has been installed, the economizer is able to provide minimum ventilation based on cfm, instead of damper position. The outdoor air cfm reading can be found in Inputs→CFM→O.CFM. During cfm control, the economizer must guarantee a certain amount of cfm at any time for ventilation purposes. If the outdoor air cfm measured is less than the current calculated cfm minimum position, then the economizer will attempt to open until the outdoor air cfm is greater than or equal to this cfm minimum position. The following options are used to program outside air cfm control. Outdoor Air Cfm Sensor Enable (OCF.S) — If this option is enabled, the outdoor air cfm sensor will be read and outside air cfm control will be enabled. Economizer Minimum Flow Rate (O.C.MX) — This option replaces the Economizer Minimum Position (Configuration →ECON→EC.MN) when the outdoor air cfm sensor is enabled. IAQ Demand Vent Minimum Flow Rate (O.C.MN) — This option replaces the IAQ Demand Ventilation Minimum Position (Configuration→IAQ→DCV.C→IAQ.M) when the outdoor air cfm sensor is enabled. Economizer Minimum Flow Deadband (O.C.DB) — This option defines the deadband of the cfm control logic. The configurable deadband is added to the economizer’s minimum cfm position and creates a range (ECMINCFM to ECMINCFM ± OACFM_DB) where the economizer will not attempt to adjust to maintain the minimum cfm position. Increasing this deadband value may help to slow down excessive economizer movement when attempting to control to a minimum position at the expense of bringing in more ventilation air than desired. ECONOMIZER OPERATION CONFIGURATION — The configuration items in the E.CFG menu group affect how the economizer modulates when attempting to follow an economizer cooling set point. Typically, they will not need adjustment. In fact, it is strongly advised not to adjust these configuration items from their default settings without first consulting a service engineering representative. In addition, the economizer cooling algorithm is designed to automatically slow down the economizer actuator’s rate of travel as outside air temperature decreases. ECONOMIZER DIAGNOSTIC HELP — Because there are so many conditions which might disable the economizer from being able to provide free cooling, the control has a display table to identify these potentially disabling sources. The user can check ACTV, the “Economizer Active” flag. If this flag is set to Yes there is no reason to check DISA (Economizer Disabling Conditions). If the flag is set to No, this means that at least one or more of the flags under the group DISA are set to Yes and the user can discover what is preventing the economizer from performing free cooling by checking the table. Control Angle Alarm Configuration — The economizer actuator determines its end stops through a calibration at the factory. Field-installed actuators may be calibrated in the Service Test mode. When an actuator learns its end stops through calibration, it also determines its control angle. The actuator will resolve this control angle and express its operation in a percent (%) of this learned range. If the economizer has not learned a sufficient control angle during calibration, the economizer damper will be unable to control ventilation and free cooling. For this reason the economizer actuator used in the Z Series control system has a configurable control angle alarm low limit (Configuration →ECON→ACT.C→C.A.L1 or C.A.L2). If the control angle learned through calibration is less than C.A.L1 or C.A.L2, an alert will occur and the actuator will not function. NOTE: This configuration does not typically need adjustment. It is configurable for the small number of jobs which may require a custom solution or workaround. UNOCCUPIED ECONOMIZER FREE COOLING — This Free Cooling function is used to start the supply fan and use the economizer to bring in outside air when the outside temperature is cool enough to pre-cool the space. This is done to delay the need for mechanical cooling when the system enters the occupied period. This function requires the use of a space temperature sensor. When configured, the economizer will modulate during an unoccupied period and attempt to maintain space temperature to the occupied cooling set point. Once the need for cooling has been satisfied during this cycle, the fan will be stopped. Configuring the economizer for Unoccupied Economizer Free Cooling is done in the UEFC group. There are three configuration options, FC.CF, FC.TM and FC.LO. Unoccupied Economizer Free Cooling Configuration (FC.CF) — This option is used to configure the type of unoccupied economizer free cooling control that is desired. 0 = disable unoccupied economizer free cooling 1 = perform unocc. economizer free cooling as available during the entire unoccupied period. 2 = perform unocc. economizer free cooling as available, FC.TM minutes before the next occupied period. Unoccupied Economizer Free Cooling Time Configuration (FC.TM) — This option is a configurable time period, prior to the next occupied period, that the control will allow unoccupied economizer free cooling to operate. This option is only applicable when FC.CF = 2. Unoccupied Economizer Free Cooling Outside Lockout Temperature (FC.LO) — This configuration option allows the user to select an outside-air temperature below which unoccupied free cooling is not allowed. This is further explained in the logic section. Unoccupied Economizer Free Cooling Logic — The following qualifications that must be true for unoccupied free cooling to operate: • Unit configured for an economizer • Space temperature sensor enabled and sensor reading within limits • Unit in the unoccupied mode • FC.CF set to 1 or FC.CF set to 2 and control is within FC.TM minutes of the next occupied period • Not in the Temperature Compensated Start mode • Not in a cooling mode • Not in a heating mode • Not in a tempering mode • Outside-air temperature sensor reading within limits • Economizer would be allowed to cool if the fan were requested and in a cool mode • OAT > FC.LO (1.0° F hysteresis applied) • Unit not in a fire smoke mode 68 The economizer’s reported and commanded positions are also viewable, as well as outside air temperature, relative humidity, enthalpy and dew point temperature. The following information can be found under the Local Display Mode Run Status→ECON. See Table 57. Economizer Control Point Determination Logic — Once the economizer is allowed to provide free cooling, the economizer must determine exactly what set point it should try to maintain. The set point the economizer attempts to maintain when “free cooling” is located at Run Status→VIEW→EC.C.P. This is the economizer control point. The control selects set points differently, based on the control type of the unit. This control type can be found at Configuration→UNIT→C.TYP. There are 6 types of control. C.TYP = 1 VAV-RAT C.TYP = 2 VAV-SPT C.TYP = 3 TSTAT Multi-Staging C.TYP = 4 TSTAT 2 Stage C.TYP = 5 SPT Multi-Staging C.TYP = 6 SPT 2 Stage If the economizer is not allowed to do free cooling, then EC.C.P = 0. If the economizer is allowed to do free cooling and the Unoccupied Free Cooling Mode is ON, then EC.C.P = Setpoints→SASP + Inputs→RSET→SA.S.R. If the economizer is allowed to do free cooling and the Dehumidification mode is ON, then EC.C.P = the Cooling Control Point (Run Status→VIEW→CL.C.P). If the C.TYP is either 4 or 6, and the unit is in a cool mode, then: If Stage = 0 EC.C.P = the Cooling Control Point (Run Status→VIEW→CL.C.P) If Stage = 1 53.0 + economizer suction pressure reset If Stage = 2 48.0 + economizer suction pressure reset NOTE: To check the current cooling stage go to Run Status →Cool→CUR.S. If the C.TYP is either 1,2,3 or 5, and the unit is in a cool mode, then EC.C.P = the Cooling Control Point (Run Status→ VIEW→CL.C.P). Economizer Suction Pressure Reset for Two-Stage Cooling — If the unit’s control type is set to either 2-stage thermostat or 2-stage space temperature control, then there is no cooling control point. Stages 1 and 2 are brought on based on demand, irrespective of the evaporator discharge temperature. In this case, the economizer monitors suction pressure and resets the economizer control point accordingly in order to protect the unit from freezing. For those conditions when the economizer opens up fully but is not able to make set point, and then a compressor comes on, it is conceivable that the coil might freeze. This can be indirectly monitored by checking suction pressure. Rather than fail a circuit, the control will attempt to protect the unit by resetting the economizer control point until the suction pressure rises out of freezing conditions. If either circuit’s suction pressure drops to within 5 psig of the low suction pressure trip point, the control will start adding reset to the economizer control point if it is active. It will be possible to reset the control point upwards, 10 degrees (2 degrees per psig), between the low suction pressure trip point of 48 psig and 5 psig above it. If this does not work, and if the suction pressure drops below the trip point, then the control will further reset the control point 1 degree every 15 seconds up to a maximum of 10 degrees. The resulting effect will be to warm up the mixed air entering the evaporator, thereby raising the suction pressure. Building Pressure Control — This control sequence provides control of the building pressure through the modulating flow rate functions of one of the modulating power exhaust options or through management of the return fan option. This function also provides control of the constant volume 2-stage power exhaust option. See below for available power exhaust options for each unit model. HIGH CONSTANT MODULATING S.O. CAPACITY RETURN/ VOLUME POWER POWER EXHAUST† 2-STAGE EXHAUST VFD* EXHAUST† 48ZG, 50ZG,Z2 X X S.O. NA NA 48ZN, 50ZN,Z3 NA X S.O. NA NA 48ZT,ZW NA NA NA STD NA 50ZT,ZW,ZX,ZZ 48Z6,Z8 NA NA NA NA STD 50Z6,Z7,Z8,Z9 UNIT X S.O. NA STD — — — — LEGEND Available as Factory Option Available as Special Order Not Available on this Unit Standard Feature on this Unit *Single VFD controlling both fan motors. †Single VFD controlling one fan motor and staging of the second fan motor. Table 57 — Economizer Run Status Table ITEM ECN.P EC2.P ECN.C ACTV DISA UNV.1 UNV.2 ENTH DBC DEW DDBC OAEC DEC EDT OAT FORC SFON CLOF OAQL HELD DH.DS O.AIR OAT OA.RH OA.E OA.D.T EXPANSION Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. Economizer Active ? ECON DISABLING CONDITIONS Econ Act. Unavailable? Econ2 Act. Unavailable? Enth. Switch Read High ? DBC - OAT Lockout? DEW - OA Dewpt.Lockout? DDBD- OAT > RAT Lockout? OAEC- OA Enth Lockout? DEC - Diff.Enth.Lockout? EDT Sensor Bad? OAT Sensor Bad ? Economizer Forced ? Supply Fan Not On 30s ? Cool Mode Not In Effect? OAQ Lockout in Effect ? Econ Recovery Hold Off? Dehumid. Disabled Econ.? OUTSIDE AIR INFORMATION Outside Air Temperature Outside Air Rel. Humidity Outside Air Enthalpy Outside Air Dewpoint Temp RANGE 0-100 0-100 0-100 YES/NO UNITS % % % YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO WRITE STATUS forcible ECONUNAV ECN2UNAV ENTH DBC_STAT DEW_STAT DDBCSTAT OAECSTAT DEC_STAT EDT_STAT OAT_STAT ECONFORC SFONSTAT COOL_OFF OAQLOCKD ECONHELD DHDISABL dF % dF 69 CCN POINT ECONOPOS ECON2POS ECONOCMD ECACTIVE OAT OARH OAE OADEWTMP forcible forcible BUILDING PRESSURE CONFIGURATION — The building pressure configurations are found at the local display under Configuration→BP. See Table 58. Building Pressure Config (BP.CF) — This configuration selects the type of building pressure control. • BP.CF = 0, No building pressure control • BP.CF = 1, constant volume two-stage exhaust based on economizer position • BP.CF = 2, Modulating building pressure control based on building pressure sensor • BP.CF = 3, VFD controlling two exhaust fan motors • BP.CF = 4, VFD control of one of the two exhaust fan motors (sizes 075-105 with high-capacity exhaust option) • BP.CF = 5, used on sizes 075-105 with return/exhaust fan option Building Pressure Sensor (BP.S) — This configuration allows the reading of a building pressure sensor when enabled. This is automatically enabled when BP.CF = 2, 3, 4 or 5. Building Pressure (+/–) Range (BP.R) — This configuration establishes the range in in. wg that a 4 to 20 mA sensor will be scaled to. The control only allows sensors that measure both positive and negative pressure. Building Pressure SETP (BP.SP) — This set point is the building pressure control set point. If the unit is configured for a type of modulating building pressure control, then this is the set point that the control will control to. BP Setpoint Offset (BP.SO) — For building pressure configurations BP.CF=2, 3, and 4, this is the offset below the building pressure set point that the building pressure must fall below to turn off power exhaust control. Power Exhaust on Setp.1 (BP.P1) — When configured for building pressure control type BP.CF = 1 (constant volume two-stage control), the control will turn on the first power exhaust fan when the economizer’s position exceeds this set point. Power Exhaust on Setp.2 (BP.P2) — When configured for building pressure control type BP.CF = 1 (constant volume two-stage control), the control will turn on the second power exhaust fan when the economizer’s position exceeds this set point. VFD/Act. Fire Speed/Pos (BP.FS) — For BP.CF = 2, 3, 4, and 5, this configuration is the VFD speed position override when the control is in the purge and evacuation smoke control modes. VFD/Act. Min Speed/Pos (BP.MN) — For BP.CF = 2, 3, 4, and 5, this configuration is the minimum VFD speed/actuator position during building pressure control. VFD Maximum Speed/Pos (BP.MX) — For BP.CF = 3 and 5, this configuration is the maximum VFD speed during building pressure control. BP 1 Actuator Max Pos. (BP.1M) — For BP.CF = 2, this configuration is the maximum actuator no. 1 position during building pressure control. BP 2 Actuator Max Pos. (BP.2M) — For BP.CF = 2, this configuration is the maximum actuator no. 2 position during building pressure control. BP Hi Cap VFD Clamp Val. (BP.CL) — For BP.CF = 4, this configuration is a limit which creates a deadband which controls the action of the second power exhaust relay. Fan Track Learn Enable (FT.CF) — For BP.CF = 5, this return/exhaust control configuration selects whether the fan tracking algorithm will make corrections over time and add a learned offset to FT.ST. If this configuration is set to No, the unit will try to control the delta cfm value between the supply and return VFDs only based on FT.ST. Fan Track Learn Rate (FT.TM) — For BP.CF = 5, this return/ exhaust control configuration is a timer that affects corrections to the delta cfm operation. The smaller this value, the more often corrections may be made based on building pressure error. This configuration is only valid when FT.CF = Yes. Fan Track Initial DCFM (FT.ST) — For BP.CF = 5, this return/exhaust control configuration is the start point upon which corrections (offset) are made over time when FT.CF = Yes. It is the constant control point for delta cfm control when FT.CF = No. Fan Track Max Clamp (FT.MX) — For BP.CF = 5, this return/exhaust control configuration is the maximum positive delta cfm control value allowed unless outdoor air cfm control is available and then the delta cfm control value would be clamped to the outdoor air cfm value directly (see the Economizer section for a description of outdoor air cfm configuration). Fan Track Max Correction (FT.AD) — For BP.CF = 5, this return/exhaust control configuration is the maximum correction allowed every time a correction is made based on FT.TM. This configuration is only valid when FT.CF = Yes. Fan Track Internal EEPROM (FT.OF) — For BP.CF = 5, this return/exhaust control internal EEPROM value is a learned correction that is stored in non-volatile RAM and adds to the offset when FT.CF = Yes. This value is stored once per day after the first correction. This configuration is only valid when FT.CF = Yes. Fan Track Internal Ram (FT.RM) — For BP.CF = 5, this return/exhaust control internal value is not a configuration but a run time correction that adds to the offset throughout the day when FT.CF = Yes. This value is only valid when FT.CF = Yes. Fan Track Reset Internal (FT.RS) — This option is a one time reset of the internal RAM and internal EEPROM stored offsets. If the system is not set up correctly and the offsets are incorrect, this learned value can be reset. Supply Air Cfm Config (SCF.C) — For BP.CF = 5, this configuration is set at the factory depending on whether an air foil or forward curve supply air fan is being used. This information is then used by the control to determine the correct cfm tables to be used when measuring supply air cfm. Building Pressure Run Rate (BP.TM) — For BP.CF = 2,3,4, and 5, this configuration is the PID run time rate. Building Pressure Proportional Gain (BP.P) — For BP.CF = 2,3,4, and 5, this configuration is the PID Proportional Gain. Building Pressure Integral Gain (BP.I) — For BP.CF = 2,3,4, and 5, this configuration is the PID Integral Gain. Building Pressure Derivative Gain (BP.D) — For BP.CF = 2,3,4, and 5, this configuration is the PID Derivative Gain. BUILDING PRESSURE CONTROL OPERATION Configuration→BP→BP.CF = 1 (Constant Volume 2-Stage Control) — Two exhaust fan relays will be turned on and off based on economizer position to maintain building pressure control. The two trip set points are Configuration→ BP→BP.P1 and Configuration→BP→BP.P2. If the economizer position is greater than or equal to BP.P1, then power exhaust relay 1 is energized, turning on the first stage. A 60-second timer is initialized. If the economizer falls 5% below the BP.P1, then the power exhaust fan relay is turned off. If the economizer position is less than BP.P1 and the 60-second timer has expired, the power exhaust fan relay is turned off. The same logic applies to the second power exhaust fan relay, except the BP.P2 trip point is monitored. If the economizer position is greater than or equal to BP.P2, then power exhaust relay 2 is energized, turning on the second stage. A 60-second timer is initialized. If the economizer is 5% below the BP.P2 the second power exhaust fan relay is turned off. If the economizer is less than BP.P2 and the 60-second timer has expired, the power exhaust fan relay is turned off. 70 Table 58 — Building Pressure Configuration ITEM BP BP.CF BP.S BP.R BP.SP BP.SO BP.P1 BP.P2 B.V.A BP.FS BP.MN BP.MX BP.1M BP.2M BP.CL FAN.T FT.CF FT.TM FT.ST FT.MX FT.AD FT.OF FT.RM FT.RS SCF.C B.PID BP.TM BP.P BP.I BP.D ACT.C BP.1 SN.1 SN.2 SN.3 SN.4 SN.5 C.A.LM BP.2 SN.1 SN.2 SN.3 SN.4 SN.5 C.A.LM EXPANSION BUILDING PRESS. CONFIGS Building Press. Config Building Pressure Sensor Bldg. Press. (+/-) Range Building Pressure Setp. BP Setpoint Offset Power Exhaust On Setp.1 Power Exhaust On Setp.2 VFD/ACTUATOR CONFIG VFD/Act. Fire Speed/Pos. VFD/Act. Min.Speed/Pos. VFD Maximum Speed BP 1 Actuator Max Pos. BP 2 Actuator Max Pos. BP Hi Cap VFD Clamp Val. FAN TRACKING CONFIG Fan Track Learn Enable Fan Track Learn Rate Fan Track Initial DCFM Fan Track Max Clamp Fan Track Max Correction Fan Track Internl EEPROM Fan Track Internal RAM Fan Track Reset Internal Supply Air CFM Config BLDG.PRESS.PID CONFIGS Bldg.Pres.PID Run Rate Bldg.Press. Prop. Gain Bldg.Press. Integ. Gain Bldg.Press. Deriv. Gain BLDG.PRES. ACTUATOR CFGS BLDG.PRES. ACT.1 CONFIGS BP 1 Serial Number 1 BP 1 Serial Number 2 BP 1 Serial Number 3 BP 1 Serial Number 4 BP 1 Serial Number 5 BP1 Cntrl Angle Lo Limit BLDG.PRES. ACT.2 CONFIGS BP 2 Serial Number 1 BP 2 Serial Number 2 BP 2 Serial Number 3 BP 2 Serial Number 4 BP 2 Serial Number 5 BP2 Cntrl Angle Lo Limit RANGE 0-5 Enable/Disable 0.10 - 0.25 -0.25 - 0.25 0 - 0.5 0 - 100 0 - 100 0 - 100 0 - 50 50 - 100 85 - 100 85 - 100 5 - 25 UNITS CCN POINT DEFAULT "H2O "H2O "H2O % % BLDG_CFG BPSENS BP_RANGE BPSP BPSO PES1 PES2 0* Disable* 0.25 0.05 0.05 25 75 % % % % % % BLDGPFSO BLDGPMIN BLDGPMAX BP1SETMX BP2SETMX BLDGCLMP 100 10 100 100 100 10 DCFM_CFG DCFMRATE DCFMSTRT DCFM_MAX DCFM_ADJ DCFM_OFF DCFM_RAM DCFMRSET SCFM_CFG No 15 2000 4000 1000 0 0 No 1 BPIDRATE BLDGP_PG BLDGP_IG BLDGP_DG 10 0.5 0.5 0.3 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 BP_1_SN1 BP_1_SN2 BP_1_SN3 BP_1_SN4 BP_1_SN5 BP1_CALM 0 0 0 0 0 35 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 BP_2_SN1 BP_2_SN2 BP_2_SN3 BP_2_SN4 BP_2_SN5 BP2_CALM 0 0 0 0 0 35 Yes/No 5-60 -20000 - 20000 0 - 20000 0 -20000 -20000 - 20000 -20000 - 20000 Yes/No 1-2 5 - 120 0-5 0-2 0-5 min CFM CFM CFM CFM CFM sec *Some configurations are model number dependent. Configuration→BP→BP.CF = 2 (Modulating Power Exhaust) — Control is accomplished with two LEN communicating actuators in tandem and one exhaust fan relay. If building pressure (Pressures→AIR.P→BP) rises above the building pressure set point (BP.SP) and the supply fan is on, building pressure control is initialized. Thereafter, if the supply fan relay goes off or if the building pressure drops below the BP.SP minus the building pressure set point offset (BP.SO) for 5 continuous minutes, building pressure control will be stopped. Any time building pressure control becomes active, the exhaust fan relay turns on, starting the dual exhaust fan motors. After the exhaust fan relay turns on, control is performed with a PID loop where: Error = BP – BP.SP K = 1000 * BP.TM / 60 (normalize the PID control for run rate) P = K * BP.P * (error) I = K * BP.I * (error) + “I” calculated last time through the PID D = K * BP.D * (error – error computed last time through the PID) Power exhaust control signal (limited between BP.MN and (BP.1M/BP.2M) %) = P + I + D Configuration→BP→BP.CF = 3 (VFD Controlling Exhaust Fan Motors) — The VFD controlling high-capacity power exhaust consists of an exhaust fan VFD (Outputs→FANS→ E.VFD) enabled by one power exhaust relay (Outputs→FANS →P.E.1). If building pressure (Pressures→AIR.P→BP) rises above the building pressure set point (BP.SP) and the supply fan is on, then building pressure control is initialized. Thereafter, if the supply fan relay goes off or if the building pressure drops below the BP.SP minus the building pressure set point offset (BP.SO) for 5 continuous minutes, building pressure control will be stopped. The 5-minute timer will continue to re-initialize while the VFD is commanded to a position > 0%. If the building pressure falls below the set point, the VFD will slow down automatically. Any time building pressure control becomes active, the exhaust fan relay turns on which energizes the exhaust fan VFD. Control is performed with a PID loop where: Error = BP – BP.SP K = 1000 * BP.TM/60 (normalize the PID control for run rate) P = K * BP.P * (error) I = K * BP.I * (error) + “I” calculated last time through the PID D = K * BP.D * (error – error computed last time through the PID) VFD control signal (clamped between BP.MN and BP.MX%) =P+I+D NOTE: Do not change values of PID set point without approval from Carrier. BP.CF = 4 (High-Capacity Exhaust Control) — Control is accomplished with a VFD and two exhaust fan relays. Highcapacity power exhaust consists of an exhaust fan VFD (Outputs→FANS→E.VFD) enabled by one power exhaust relay (Outputs→FANS→P.E.1) and a second power exhaust relay (Outputs→FANS→P.E.2) which controls a single speed fan which is equal in capacity to the VFD running at full speed. 71 supply and return fan if the building pressure deviates from the Building Pressure Set Point (BP.SP). Periodically, at the rate set by the fan track learn rate (FT.TM), the delta cfm is adjusted upward or downward with a maximum adjustment at a given instance to be no greater than fan track max correction (FT.AD). The delta cfm can not ever be adjusted greater than or less than the fan track initial delta cfm (FT.ST) than by the Fan Track Max Clamp (FT.MX). CONFIGURING THE BUILDING PRESSURE ACTUATORS (BP.CF = 2) TO COMMUNICATE VIA ACTUATOR SERIAL NUMBER — Every actuator used in the Z Series control system has its own unique serial number. The rooftop control uses this serial number to communicate with the actuator over the local equipment network (LEN). These serial numbers are programmed at the factory and should not need changing. Should field replacement of an actuator become necessary, it will be necessary to configure the serial numbers of the new actuator. Five individual numbers make up each serial number and these can be programmed to match the serial number of the actuators in the building pressure actuator configurations group, ACT.C.→BP.1 and BP.2 (SN.1, SN.2, SN.3, SN.4, SN.5). NOTE: The serial numbers for all LEN actuators can be found inside the control doors of the unit as well as on the actuator itself. If an actuator is replaced in the field, it is a good idea to remove the additional peel-off serial number sticker on the actuator and cover up the old one inside the control doors. CONTROL ANGLE ALARM CONFIGURATION C.ALM (BP.CF = 2) — The building pressure actuators learn what its end stops are though a calibration at the factory. Field-installed actuators may be calibrated in the Service Test mode. When an actuator learns its end stops through calibration, it stores the control angle. The actuator will resolve this control angle and express its operation in a percent (%) of this learned range. If a building pressure actuator has not learned a sufficient control angle during calibration, the actuator will be unable to control building pressure. For this reason the building pressure actuators used in the Z Series control system have configurable control angle alarm low limits in the Building Pressure Actuator Configurations group, ACT.C→BP.1 and BP.2. (C.A.LM). If the control angle learned through calibration is less than C.A.LM, an alert will occur and the actuator will not function. NOTE: This configuration does not typically need adjustment. It is configurable for the small number of jobs which may require a custom solution or workaround. Controlling high-capacity power exhaust differs from normal power exhaust in the following ways: • The integral term is not used. The percentile commanded position of the VFD is used instead. • A “clamp percent” configuration is added (BP.CL) to create a deadband that will assist the algorithm in controlling the second power exhaust relay. If building pressure (BP) rises above the building pressure set point (BP.SP) and the supply fan is on, building pressure control is initiated. Thereafter if the supply fan relay goes off or if the building pressure drops below the BP.SP minus the building pressure set point offset (BP.SO) for 5 continuous minutes, building pressure control will be stopped. The 5-minute timer will continue to reset while the VFD is commanded to a position > 0%. If the building pressure falls below the set point, the VFD will shut down automatically. Any time building pressure control becomes active, the exhaust fan relay turns on which energizes the exhaust fan VFD. After the exhaust fan relay turns on, PID control ensues without an “I” term: Error = BP – BP.SP K = 1000 * BP.TM / 60 (normalize the PID control for run rate) P = K * BP.P * (error) D = K * BP.D * (error - error computed last time through the PID) VFD control signal (clamped between 0 and 100%) = VFD Output last time through + (P + D) NOTE: The sum of P + D will be clamped on any timed calculation to an internally calculated value which guarantees the VFD is not commanded more or less an amount, than it cannot achieve before the next time VFD capacity is again calculated. Bringing the single speed fan (P.E.2) ON and OFF is coordinated with the VFD speed. When building pressure first becomes active, P.E.2 is OFF, P.E.1 is ON and the VFD is allowed to climb to 100%. BP.CL will be used to act as hysteresis so that when the P + D term is evaluated and it exceeds BP.CL, the control will go through a one-minute period hold off time where the VFD is commanded to BP.CL, and P.E.2 is brought on. After the transition to P.E.2 ON is complete, the control will continue to control the VFD from BP.CL%. If BP rises, the control will speed up the VFD. Should the VFD drop to 0%, and the next time through the PID the P + D term calculation is less than – BP.CL, the control will go through another one-minute PID hold off period where P.E.2 is commanded OFF and the VFD is commanded to 100 – BP.CL. Configuration→BP→BP.CF =5 (Return/Exhaust Control) — Fan tracking is the method of control used on plenum return fan option. The fan tracking algorithm controls the exhaust/ return fan VFD and the exhaust fan relay. The ComfortLink™ controls use a flow station to measure the flow of both the supply and the return fans. The speed of the return fan is controlled by maintaining a delta cfm (usually with supply airflow being greater of the two) between the two fans. The building pressure is controlled by maintaining this delta cfm between the two fans. In general, the greater the delta between supply airflow and return airflow, the higher the building pressure will be. Conversely, as the return airflow quantity increases above the supply airflow, the lower the building pressure will be. Whenever there is a request for the supply fan (or there is the presence of the IGC feedback on gas heat units), the return fan is started. The delta cfm is defined as S.CFM – R.CFM. The return fan VFD is controlled by a PID on the error of delta cfm actual from delta cfm set point. If the error is positive the drive will increase speed. If the error is negative the drive will decrease speed. NOTE: These configurations are used only if Fan Tracking Learning is enabled. When Fan Tracking Learning is enabled, the control will adjust the delta cfm (FT.ST) between the Smoke Control Modes — There are four smoke control modes that can be used to control smoke within areas serviced by the unit: Pressurization mode, Evacuation mode, Smoke Purge mode, and Fire Shutdown. Evacuation, Pressurization and Smoke Purge modes require the controls expansion board (CEM). The Fire Shutdown input is located on the main board (MBB) on terminals TB201-5 and 6. The unit may also be equipped with a factory-installed return air smoke detector that is wired to TB201-5,6 and will shut the unit down if a smoke condition is determined. Field-monitoring wiring can be connected to terminal TB201-13 and 14 to monitor the smoke detector. Inputs on the CEM board can be used to put the unit in the Pressurization, Evacuation, and Smoke Purge modes. These switches or inputs are connected to TB204 as shown below. Refer to Major System Components section on page 102 for wiring diagrams. Pressurization — TB204-5 and 6 Evacuation — TB204-7 and 8 Smoke Purge — TB204-9 and 10 Each mode must be energized individually on discrete inputs and the corresponding alarm is initiated when a mode is activated. The fire system provides a normally closed dry 72 contact closure. Multiple smoke control inputs, sensed by the control will force the unit into a Fire Shutdown mode. FIRE SMOKE INPUTS — These discrete inputs can be found on the local display under Inputs→FIRE. ITEM FIRE FSD PRES EVAC PURG When a space or return air CO2 sensor is connected to the unit control, the unit’s IAQ routine allows a demand-based control for ventilation air quantity, by providing a modulating outside air damper position that is proportional to CO2 level. The ventilation damper position is varied between a minimum ventilation level (based on internal sources of contaminants and CO2 levels other than from the effect of people) and the maximum design ventilation level (determined at maximum populated status in the building). Demand Control Ventilation (DCV) is also available when the ComfortLink™ unit is connected to a CCN system using ComfortID™ terminal controls. This function also provides alternative control methods for controlling the amount of ventilation air being admitted, including fixed outdoor air ventilation rates (measured as cfm), external discrete sensor switch input and externally generated proportional signal controls. The IAQ function requires the installation of the factoryoption economizer system. The DCV sequences also require the connection of accessory (or field-supplied) space or return air CO2 sensors. Fixed cfm rate control requires the factoryinstalled outdoor air cfm option. External control of the ventilation position requires supplemental devices, including a 4 to 20 mA signal, a 10-kilo-ohm potentiometer, or a discrete switch input, depending on the method selected. Outside air CO2 levels may also be monitored directly and high CO2 economizer restriction applied when an outdoor air CO2 sensor is connected. (The outdoor CO2 sensor connection requires installation of the controls expansion module [CEM].) The ComfortLink controls have the capability of DCV using an IAQ sensor. The indoor air quality (IAQ) is measured using a CO2 sensor whose measurements are displayed in parts per million (ppm). The IAQ sensor can be field-installed in the return duct. There is also an accessory space IAQ sensor that can be installed directly in the occupied space. The sensor must provide a 4 to 20 mA output signal and must include its own 24-v supply. The sensor connects to TB202 terminals 11 and 12. Be sure to leave the 182-ohm resistor in place on terminals 11 and 12. OPERATION — The unit’s indoor air quality algorithm modulates the position of the economizer damper between two user configurations depending upon the relationship between the IAQ and the outdoor air quality (OAQ). Both of these values can be read at the Inputs→AIR.Q submenu. The lower of these two configurable positions is referred to as the IAQ Demand Vent Min Position (IAQ.M), while the higher is referred to as Economizer Minimum Position (EC.MN). The IAQ.M should be set to an economizer position that brings in enough fresh air to remove contaminants and CO2 generated by sources other than people. The EC.MN value should be set to an economizer position that brings in enough fresh air to remove contaminants and CO2 generated by all sources including people. The EC.MN value is the design value for maximum occupancy. The logic that is used to control the dampers in response to IAQ conditions is shown in Fig. 11. The ComfortLink controls will begin to open the damper from the IAQ.M position when the IAQ level begins to exceed the OAQ level by a configurable amount, which is referred to as Differential Air Quality Low Limit (DAQ.L). If OAQ is not being measured, OAQ can be manually configured. It should be set at around 400 to 450 ppm or measured with a handheld sensor during the commissioning of the unit. The OAQ reference level can be set using the OAQ Reference Set Point (OAQ.U). When the differential between IAQ and OAQ reaches the configurable Diff. Air Quality Hi Limit (DAQ.H), then the economizer position will be EC.MN. When the IAQ–OAQ differential is between DAQ.L and DAQ.H, the control will modulate the damper between IAQ.M and EC.MN as shown in Fig. 11. The relationship is a linear relationship but other non-linear options can be used. The CCN WRITE POINT STATUS EXPANSION RANGE FIRE-SMOKE INPUTS Fire Shutdown Input Pressurization Input Evacuation Input Smoke Purge Input ALRM/NORM ALRM/NORM ALRM/NORM ALRM/NORM FSD PRES EVAC PURG forcible forcible forcible forcible Fire Shutdown Mode — This mode will cause an immediate and complete shutdown of the unit. Pressurization Mode — This mode attempts to raise the pressure of a space to prevent smoke infiltration from an adjacent space. Opening the economizer (thereby closing the return air damper), shutting down power exhaust and turning the indoor fan on will increase pressure in the space. Evacuation Mode — This mode attempts to lower the pressure of the space to prevent infiltrating an adjacent space with its smoke. Closing the economizer (thereby opening the returnair damper), turning on the power exhaust and shutting down the indoor fan decrease pressure in the space. Smoke Purge Mode — This mode attempts to draw out smoke from the space after the emergency condition. Opening the economizer (thereby closing the return-air damper), turning on both the power exhaust and indoor fan will evacuate smoke and bring in fresh air. AIRFLOW CONTROL DURING THE FIRE/SMOKE MODES — All non-smoke related control outputs will get shut down in the fire/smoke modes. Those related to airflow will be controlled as explained below. The following matrix specifies all actions the control shall undertake when each mode occurs (outputs are forced internally with CCN priority number 1 - “Fire”): DEVICE Economizer Indoor Fan — VFD/IGV Power Exhaust VFD-Actuator Heat Interlock Relay 100% 100% 0% FIRE SHUTDOWN 0% ON/FSO* ON/FSO* OFF OFF OFF ON/FSO* ON/FSO* OFF ON ON OFF OFF PRESSURIZATION PURGE EVACUATION *“FSO” refers to the supply and exhaust VFD/IGV fire speed override configurable speed. RELEVANT ITEMS: The economizer’s commanded output can be found in Outputs→ECON→ECN.C. The configurable fire speed override for supply fan VFD/IGV is in Configuration→SP→SP.FS. The supply fan relay’s commanded output can be found in Outputs→FANS→S.FAN. The supply fan VFD’s commanded speed can be found in Outputs→FANS→S.VFD. The inlet guide vane’s commanded position can be found in Outputs→ACTU→IGV.C. The configurable fire speed override for exhaust VFD/actuator is in Configuration→BP→B.V.A→BP.FS. The exhaust fan VFD’s commanded speed can be found in Outputs→FANS→E.VFD. The power exhaust actuators command positions can be found in Outputs→ACTU→BPx.C. Indoor Air Quality Control — The indoor air quality (IAQ) function will admit fresh air into the space whenever space air quality sensors detect high levels of CO2. 73 damper position will never exceed the bounds specified by IAQ.M and EC.MN during IAQ control. If the building is occupied and the indoor fan is running and the differential between IAQ and OAQ is less than DAQ.L, the economizer will remain at IAQ.M. The economizer will not close completely. The damper position will be 0 when the fan is not running or the building is unoccupied. The damper position may exceed EC.MN in order to provide free cooling. The ComfortLink™ controls are configured for air quality sensors which provide 4 mA at 0 ppm and 20 mA at 2000 ppm. If a sensor has a different range, these bounds must be reconfigured. These pertinent configurations for ranging the air quality sensors are IQ.R.L, IQ.R.H, OQ.R.L and OQ.R.H. The bounds represent the PPM corresponding to 4 mA (low) and 20 mA (high) for IAQ and OAQ, respectively. If OAQ exceeds the OAQ Lockout Value (OAQ.L), then the economizer will remain at IAQ.M. This is used to limit the use of outside air which outdoor air CO2 levels are above the OAQ.L limit. Normally a linear control of the damper vs. the IAQ control signal can be used, but the control also supports non-linear control. Different curves can be used based on the Diff.IAQ Responsiveness Variable (IAQ.R). See Fig. 12. SETTING UP THE SYSTEM — The IAQ configuration options are under the Local Display Mode Configuration→IAQ. See Table 59. IAQ Analog Sensor Config (Configuration→IAQ→ AQ.CF→IQ.A.C) — This is used to configure the type of IAQ position control. It has the following options: • IQ.A.C = 0 (No analog input). If there is no other minimum position control, the economizer minimum position will be Configuration→IAQ→EC.MN and there will be no IAQ control. • IQ.A.C = 1 (IAQ analog input). An indoor air (space or return air) CO2 sensor is installed. If an outdoor air CO2 sensor is also installed, or OAQ is broadcast on the CCN, or if a default OAQ value is used, then the unit can perform IAQ control. • IQ.A.C = 2 (IAQ analog input with minimum position override) — If the differential between IAQ and OAQ is above Configuration→IAQ→AQ.SP→DAQ.H, the economizer minimum position will be the IAQ override position (Configuration→IAQ→AQ.SP→IQ.O.P). • IQ.A.C = 3 (4 to 20 mA minimum position) — With a 4 to 20 mA signal connected to TB202 terminal 11 and 12, the economizer minimum position will be scaled linearly from 0% (4 mA) to EC.MN (20 mA). • IQ.A.C = 4 (10K potentiometer minimum position) — With a 10K linear potentiometer connected to TB202 terminal 11 and 12, the economizer minimum position will be scaled linearly from 0% (0 kilo-ohms) to EC.MN (10 kilo-ohms). IAQ Analog Fan Config (Configuration→IAQ→AQ.CF→ IQ.A.F) — This configuration is used to configure the control of the indoor fan. If this option is used then the IAQ sensor must be in the space and not in the return duct. It has the following configurations: • IQ.A.F = 0 (No Fan Start) — IAQ demand will never override normal indoor fan operation during occupied or unoccupied period and turn it on. • IQ.A.F = 1 (Fan On If Occupied) — IAQ demand will override normal indoor fan operation and turn it on (if off) only during the occupied period (CV operation with automatic fan). • IQ.A.F = 2 (Fan On Occupied/Unoccupied) — IAQ demand will always override normal indoor fan operation and turn it on (if off) during both the occupied and unoccupied period. For IQ.A.F = 1 or 2, the fan will be turned on as described above when DAQ is above the DAQ Fan On Set Point (Configuration→IAQ→AQ.SP→D.F.ON). The fan will be turned off when DAQ is below the DAQ Fan Off Set Point (Configuration→IAQ→AQ.SP→D.F.OF). The control can also be set up to respond to a discrete IAQ input. The discrete input is connected to TB204 terminal 11 and 12. Table 59 — Indoor Air Quality Configuration ITEM DCV.C EC.MN IAQ.M O.C.MX O.C.MN O.C.DB AQ.CF IQ.A.C IQ.A.F IQ.I.C IQ.I.F OQ.A.C AQ.SP IQ.O.P IQ.O.C DAQ.L DAQ.H D.F.OF D.F.ON IAQ.R OAQ.L OAQ.U AQ.S.R IQ.R.L IQ.R.H OQ.R.L OQ.R.H IAQ.P IQ.PG IQ.P.T IQ.P.L IQ.P.H IQ.L.O EXPANSION DCV ECONOMIZER SETPOINTS Economizer Min.Position IAQ Demand Vent Min.Pos. Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband AIR QUALITY CONFIGS IAQ Analog Sensor Config IAQ 4-20 ma Fan Config IAQ Discrete Input Config IAQ Disc.In. Fan Config OAQ 4-20ma Sensor Config AIR QUALITY SETPOINTS IAQ Econo Override Pos. IAQ Override Flow Diff.Air Quality LoLimit Diff. Air Quality HiLimit DAQ PPM Fan Off Setpoint DAQ PPM Fan On Setpoint Diff. AQ Responsiveness OAQ Lockout Value User Determined OAQ AIR QUALITY SENSOR RANGE IAQ Low Reference IAQ High Reference OAQ Low Reference OAQ High Reference IAQ PRE-OCCUPIED PURGE IAQ Purge IAQ Purge Duration IAQ Purge LoTemp Min Pos IAQ Purge HiTemp Min Pos IAQ Purge OAT Lockout RANGE 0 - 100 0 - 100 0 - 20000 0 - 20000 200 - 1000 UNITS % % CFM CFM CFM 0-4 0-2 0-2 0-2 0-2 0 - 100 0 - 31000 0 - 1000 100 - 2000 0 - 2000 0 - 2000 -5 - 5 0 - 2000 0 - 5000 % CFM 0 - 5000 0 - 5000 0 - 5000 0 - 5000 Yes/No 5 - 60 0 - 100 0 - 100 35 - 70 74 min % % dF CCN POINT DEFAULT ECONOMIN IAQMINP OACFMMAX OACFMMIN OACFM_DB 5 0 2000 0 400 IAQANCFG IAQANFAN IAQINCFG IAQINFAN OAQANCFG 0 0 0 0 0 IAQOVPOS IAQOVCFM DAQ_LOW DAQ_HIGH DAQFNOFF DAQFNON IAQREACT OAQLOCK OAQ_USER 100 10000 100 700 200 400 0 0 400 IAQREFL IAQREFH OAQREFL OAQREFH 0 2000 0 2000 IAQPURGE IAQPTIME IAQPLTMP IAQPHTMP IAQPNTLO No 15 10 35 50 economizer minimum position will be Configuration→ IAQ→DCV.C→IAQ.M. • IQ.I.C = 2 (IAQ Discrete Input with Minimum Position Override. This will indicate that the IAQ level (high or low) will be indicated by the discrete input and the economizer minimum position will be the IAQ override position, IQ.P.O (when high). It is also necessary to configure how the fan operates when using the IAQ discrete input. IAQ Discrete Fan Config (Configuration→IAQ→AQ.CF →IQ.I.F) — This is used to configure the operation of the fan during an IAQ demand condition. It has the following configurations: • IQ.I.F = 0 (No Fan Start) — IAQ demand will never override normal indoor fan operation during occupied or unoccupied period and turn it on. • IQ.I.F = 1 (Fan On If Occupied) — IAQ demand will override normal indoor fan operation and turn it on (if off) only during the occupied period (CV operation with automatic fan). • IQ.I.F = 2 (Fan On Occupied/Unoccupied) — IAQ demand will always override normal indoor fan operation and turn it on (if off) during both the occupied and unoccupied period. Economizer Min Position (Configuration→IAQ→DCV.C →EC.MN) — This is the fully occupied minimum economizer position. IAQ Demand Vent Min Pos. (Configuration→IAQ→ DCV.C→IAQ.M) — This configuration will be used to set the minimum damper position in the occupied period when there is no IAQ demand. IAQ Econo Override Pos (Configuration→IAQ→AQ.SP→ IQ.O.P) — This configuration is the position that the economizer goes to when override is in effect. OAQ 4-20 mA Sensor Config (Configuration→IAQ→ AQ.CF→OQ.A.C) — This is used to configure the type of outdoor sensor that will be used for OAQ levels. It has the following configuration options: • OQ.A.C = 0 (No Sensor) — No sensor will be used and the internal software reference setting will be used. • OQ.A.C = 1 (OAQ Sensor with DAQ) — An outdoor CO2 sensor will be used. • OQ.A.C = 2 (4 to 20 mA Sensor without DAQ). OAQ Lockout Value (Configuration→IAQ→AQ.SP→ OAQ.L) — This is the maximum OAQ level above which demand ventilation will be disabled. Diff. Air Quality Lo Limit (Configuration→IAQ→ AQ.SP →DAQ.L) — This is the differential CO2 level at which IAQ control of the dampers will be initiated. Diff. Air Quality Hi Limit (Configuration→IAQ→ AQ.SP →DAQ.H) — This is the differential CO2 level at which IAQ control of the dampers will be at maximum and the dampers will be at the Configuration→ IAQ→DCV.C→EC.MN. DAQ ppm Fan On Set Point (Configuration →IAQ→AQ.SP→D.F.ON) — This is the CO2 level at which the indoor fan will be turned on. DAQ ppm Fan Off Set Point (Configuration→IAQ →AQ.SP→D.F.OF) — This is the CO2 level at which the indoor fan will be turned off. IAQ Low Reference (Configuration→IAQ→AQ.S.R→ IQ.R.L) — This is the reference that will be used with a to non-Carrier IAQ sensor that may have a different characteristic curve. It represents the CO2 level at 4 mA. IAQ High Reference (Configuration→IAQ→AQ.SR →IQ.R.H) — This is the reference that will be used with a non-Carrier IAQ sensor that may have a different characteristic curve. It represents the CO2 level at 4 mA. MINIMUM IAQ DAMPER POSITION INCREASING VENTILATION ECONOMIZER MINIMUM DAMPER POSITION VENTILATION FOR PEOPLE VENTILATION FOR SOURCES 100 500 AQ DIFFERENTIAL LOW (DAQ.L) 700 1000 INSIDE/OUTSIDE CO2 DIFFERENTIAL INSIDE CO2 CONCENTRATION AQ DIFFERENTIAL HIGH (DAQ.H) Fig. 11 — IAQ Control NOTE: Calculating the IAQ.M and EC.MN damper position based on differential IAQ measurement. Based on the configuration parameter IAQREACT, the reaction to damper positioning based on differential air quality ppm can be adjusted. IAQREACT = 1 to 5 (more responsive) IAQREACT = 0 (linear) IAQREACT = –1 to –5 (less responsive) Fig. 12 — IAQ Response Curve IAQ Discrete Input Config (Configuration→IAQ→AQ.CF →IQ.I.C) — This configuration is used to set the type of IAQ sensor. The following are the options: • IQ.I.C = 0 (No Discrete Input) — This is used to indicate that no discrete input will be used and the standard IAQ sensor input will be used. • IQ.I.C = 1 (IAQ Discrete Input) — This will indicate that the IAQ level (high or low) will be indicated by the discrete input. When the IAQ level is low, the 75 OAQ Low Reference (Configuration→IAQ→AQ.S.R →OQ.R.L) — This is the reference that will be used with a O.C.MX — Econ OACFM DCV Max Flow O.C.DB — Econ OACFM MinPos Deadbd When the outdoor air cfm sensor is enabled, the Economizer Min.Position (Configuration→IAQ→DCV.C→EC.MN) and the IAQ Demand Vent Min.Pos (Configuration→IAQ→ DCV.C→IAQ.M) will no longer be used. During vent periods, the control will modulate the damper to maintain the outdoor air intake quantity between O.C.MX and O.C.MN. The indoor air quality algorithm will vary the cfm between these two values depending on Configuration→IAQ→AQ.SP→DAQ.L and the Configuration→IAQ→AQ.SP→DAQ.H set points and upon the relationship between the IAQ and the outdoor air quality (OAQ). The economizer’s OA CFM Minimum Position Deadband (O.C.DB) is the deadband range around the outdoor cfm control point at where the damper control will stop, indicating the control point has been reached. See the Economizer section for more information. non-Carrier OAQ sensor that may have a different characteristic curve. It represents the CO2 level at 4 mA. OAQ High Reference (Configuration→IAQ→AQ.S.R→ OQ.R.H) — This is the reference that will be used with a nonCarrier OAQ sensor that may have a different characteristic curve. It represents the CO2 level at 4 mA. Diff. IAQ Responsiveness (Configuration→IAQ→AQ.SP →IAQ.R) — This is the configuration that is used to select the IAQ response curves as shown in Fig. 12. PRE-OCCUPANCY PURGE — The control has the option for a pre-occupancy purge to refresh the air in the space prior to occupancy. This feature is enabled by setting Configuration→IAQ→ IAQ.P→IQ.PG to Yes. The IAQ Purge will operate under the following conditions: • IQ.PG is enabled • the unit is in the unoccupied state • Current Time is valid • Next Occupied Time is valid • time is within two hours of the next occupied period • time is within the purge duration (Configuration→ IAQ→IAQ.P→IQ.P.T) If all of the above conditions are met, the following logic is used: If OAT >= IQ.L.O and OAT <= OCSP and economizer is available then purge will be enabled and the economizer will be commanded to 100%. Else, if OAT < IQ.L.O then the economizer will be positioned to the IAQ Purge LO Temp Min Pos (Configuration→ IAQ→IAQ.P→IQ.P.L) If neither of the above are true then the dampers will be positioned to the IAQ Purge HI Temp Min Pos (Configuration →IAQ→IAQ.P→IQ.P.H) If this mode is enabled the indoor fan and heat interlock relay (VAV) will be energized. IAQ Purge (Configuration→IAQ→IAQ.P→IQ.PG) — This is used to enable IAQ pre-occupancy purge. IAQ Purge Duration (Configuration→IAQ→IAQ.P→ IQ.P.T) — This is the maximum amount of time that a purge can occur. IAQ Purge Lo Temp Min Pos (Configuration→IAQ→ IAQ.P→IQ.P.L) — This is used to configure a low limit for damper position to be used during the purge mode. IAQ Purge Hi Temp Min Pos (Configuration→IAQ→ IAQ.P→IQ.P.H) — This is used to configure a maximum position for the dampers to be used during the purge cycle. IAQ Purge OAT Lockout Temp (Configuration→IAQ→ IAQ.P→IQ.L.O) — Nighttime lockout temperature below which the purge cycle will be disabled. OPTIONAL AIRFLOW STATION — The ComfortLink™ controls are capable of working with a factory-installed optional airflow station that measures the amount of outdoor air entering the economizer. This flow station is intended to measure ventilation airflows and has a limitation as to the maximum flow rate it can measure. The limits are 18,000 cfm for sizes 030-050 and 31,000 cfm for sizes 055-105. All configurations for the outdoor airflow station can be found in the Configuration→ECON→CFM.C, sub-menu. For this algorithm to function, the Outdoor Air Cfm Sensor Configuration (OCF.S.) must be enabled. There are three set point configurations: O.C.MN — Econ OACFM DCV Min Flow Humidification — The Z Series ComfortLink controls can control a field-supplied and installed humidifier device. The ComfortLink controls provide two types of humidification control: A discrete stage control (via a relay contact) and a proportional control type (communicating to a LEN actuator). The discrete stage control is used to control a single-stage humidifier, (typically a spray pump). The proportional control type is typically used to control a proportional steam valve serving a steam grid humidifier. The ComfortLink controls must be equipped with a controls expansion module and an accessory space or return air relative humidity sensor. If a humidifier using a proportional steam valve is selected, the Carrier LEN actuator (Carrier Part No. HF23BJ049) must be adapted to the humidifier manufacturer’s steam valve. Contact Belimo Aircontrols for information on actuator linkage adapter packages required to mount the LEN actuator on the specific brand and type of steam valve mounted by the humidifier manufacturer. The LEN actuator address must be programmed into the ComfortLink unit’s humidifier actuator serial number variables. NOTE: If the unit has the IGV option installed, it will be necessary to fabricate a LEN harness extension to connect the humidifier LEN actuator to the unit’s LEN harness. SETTING UP THE SYSTEM — These humidity configuration are located in the local displays under Configuration→ HUMD. See Table 60. Related points are shown in Table 61. Humidifier Control Configuration (HM.CF) — The humidifier control can be set to the following configurations: • HM.CF = 0 — No humidity control. • HM.CF = 1 — Discrete control based on space relative humidity. • HM.CF = 2 — Discrete control based on return air relative humidity. • HM.CF = 3 — Analog control based on space relative humidity. • HM.CF = 4 — Analog control based on return air relative humidity. Humidity Control Set Point (HM.SP) — The humidity control set point has a range of 0 to 100%. Humidifier PID Run Rate (HM.TM) — This is the PID run time rate. Humidifier Proportional Gain (HM.P) — This configuration is the PID Proportional Gain. Humidifier Integral Gain (HM.I) — This configuration is the PID Integral Gain. Humidifier Derivative Gain (HM.D) — This configuration is the PID Derivative Gain. 76 Table 60 — Humidity Configuration ITEM HUMD HM.CF HM.SP H.PID HM.TM HM.P HM.I HM.D ACT.C SN.1 SN.2 SN.3 SN.4 SN.5 C.A.LM EXPANSION HUMIDITY CONFIGURATION Humidifier Control Cfg. Humidifier Setpoint HUMIDIFIER PID CONFIGS Humidifier PID Run Rate Humidifier Prop. Gain Humidifier Integral Gain Humidifier Deriv. Gain HUMIDIFIER ACTUATOR CFGS Humd Serial Number 1 Humd Serial Number 2 Humd Serial Number 3 Humd Serial Number 4 Humd Serial Number 5 Humd Ctrl Angle Lo Limit CCN POINT RANGE HUMD_CFG HUSP 0-4 0 - 100 HUMDRATE HUMID_PG HUMID_IG HUMID_DG 10 - 120 0-5 0-5 0-5 HUMD_SN1 HUMD_SN2 HUMD_SN3 HUMD_SN4 HUMD_SN5 HUMDCALM 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 UNITS DEFAULT 0 40 % sec 30 1 0.3 0.3 0 0 0 0 0 85 Table 61 — Related Humidity Points ITEM Config→UNIT→SENS→SRH.S Config→UNIT→SENS→RRH.S Inputs→REL.H→RA.RH Inputs→REL.H→SP.RH Outputs→ACTU→HMD.P Outputs→ACTU→HMD.C Outputs→GEN.O→HUM.R EXPANSION Space Air RH Sensor Return Air RH Sensor Return Air Rel. Humidity Space Relative Humidity Humidifier Act.Curr.Pos. Humidifier Command Pos. Humidifier Relay UNITS % % % % CCN POINT SPRHSENS RARHSENS RARH SPRH HUMDRPOS HUMDCPOS HUMIDRLY WRITE STATUS forcible forcible may be calibrated in the Service Test mode. When an actuator learns its end stops through calibration, it determines its control angle. The actuator will resolve this control angle and express its operation in a percent (%) of this learned range. If the humidifier actuator has not learned a sufficient control angle during calibration, the actuator will be unable to control humidity. For this reason, the humidifier actuator has a configurable control angle alarm low limit (C.A.LM). If the control angle learned through calibration is less than C.A.LM, an alert will occur and the actuator will not function. NOTE: This configuration does not typically need adjustment. It is configurable for the small number of jobs which may require a custom solution or workaround. OPERATION — For operation, PID control will be utilized. The process will run at the rate defined by the Configuration →HUMD→H.PID→HM.TM. The first part of humidity control tests the humidity control configuration and will turn on corresponding configurations to read space or return air relative humidity. If the supply fan has been ON for 30 seconds and the space is occupied, then the humidification is started. Actuator Control — Control is performed with a generic PID loop where: Error = HM.SP – humidity sensor value (SP.RH or RA.RH, depending on configuration). The PID terms are calculated as follows: P = K * HM.P * error I = K * HM.I * error + “I” last time through D = K * HM.D * (error – error last time through) Where K = HM.TM/60 to normalize the effect of changing the run time rate Relay Output Control — If the humidity sensor reading is greater than the humidity set point then the humidity relay (Outputs→GEN.O→HUM.R) is closed. The relay will open when the humidity is 2% less than the humidity set point. CONFIGURING THE HUMIDIFIER ACTUATOR — Every actuator used in the Z Series control system has its own unique serial number. The rooftop control uses this serial number to communicate with the actuator over the local equipment network (LEN). The actuator serial number is located on a two-part sticker affixed to the side of the actuator housing. Remove one of the actuator’s serial number labels and paste it onto the actuator serial number records label located inside the left-hand access panel at the unit’s control panel. Five individual numbers make up this serial number. Program the serial number of the actuator in its Humidifier Actuator Configurations group, ACT.C (SN.1, SN.2, SN.3, SN.4, SN.5) NOTE: The serial numbers for all LEN actuators can be found inside the control doors of the unit as well as on the actuator itself. If an actuator is replaced in the field, it is a good idea to remove the additional peel-off serial number sticker on the actuator and cover up the old one inside the control doors. Control Angle Alarm (Configuration→HUMD→ACTC→ C.A.LM) — The humidifier actuator learns what its end stops are though a calibration at the factory. Field-installed actuators Dehumidification and Reheat — The Dehumidification function will override comfort condition set points based on dry bulb temperature and deliver cooler air to the space in order to satisfy a humidity set point at the space or return air humidity sensor. The Reheat function will energize a suitable heating system concurrent with dehumidification sequence should the dehumidification operation result in excessive cooling of the space condition. The dehumidification sequence requires the installation of a space or return air humidity sensor or a discrete switch input. A CEM (option or accessory) is required to accommodate an RH (relative humidity) sensor connection. Reheat is possible when multiple-step staged gas control option or hydronic heat (option or field-installed coil) is installed. Reheat is also possible using a heat reclaim coil (field-supplied and installed) or a hot gas reheat coil (special order, factory-installed). Dehumidification and reheat control are allowed during Cooling and Vent modes in the Occupied period. On constant volume units using thermostat inputs (C.TYP = 3 or 4), the discrete switch input must be used as the dehumidification control input. The commercial Thermidistat™ device is the recommended accessory device. SETTING UP THE SYSTEM — The settings for dehumidification can be found at the local display at Configuration→ DEHU. See Table 62. Dehumidification Configuration (D.SEL) — The dehumidification configuration can be set for the following settings: • D.SEL = 0 — No dehumidification and reheat. 77 Table 62 — Dehumidification Configuration ITEM DEHU D.SEL D.SEN D.EC.D D.V.CF D.V.RA D.V.HT D.C.SP D.RH.S EXPANSION DEHUMIDIFICATION CONFIG. Dehumidification Config Dehumidification Sensor Econ disable in DH mode? Vent Reheat Setpt Select Vent Reheat RAT offset Vent Reheat Setpoint Dehumidify Cool Setpoint Dehumidify RH Setpoint RANGE 0-3 1-3 Yes/No 0-1 0-8 55-95 40-55 10-90 UNITS deltaF dF dF % CCN POINT DHSELECT DHSENSOR DHECDISA DHVHTCFG DHVRAOFF DHVHT_SP DHCOOLSP DHRELHSP DEFAULT 0 1 Yes 0 0 70 45 55 NOTE: If Configuration→DEHU→D.SEL = 1 or 2, then either staged gas or hot water valve control will be automatically enabled (Configuration→HEAT→HT.CF will be set to either 3 or 4). If a tempering, unoccupied or “mechanical cooling locked out” HVAC mode is present, dehumidification will be disabled. An HVAC: Off, Vent or Cool mode must be in effect to launch either a Reheat or Dehumidification mode. If an associated sensor responsible for dehumidification fails, dehumidification will not be attempted (SPRH, RARH). Initiating a Reheat or Dehumidification Mode — To call out a Reheat mode in the Vent or the Off HVAC mode, or to call out a Dehumidification mode in a Cool HVAC mode, one of the following conditions must be true: • The space is occupied and the humidity is greater than the relative humidity trip point (D.RH.S). • The space is occupied and the discrete humidity input is closed. Dehumidification and Reheat Control — If a dehumidification mode is initiated, the rooftop will attempt to lower humidity as follows: • Economizer Cooling — The economizer, if allowed to perform free cooling, will have its control point (Run Status→VIEW→EC.C.P) set to Configuration→DEHU →D.C.SP. If Configuration→DEHU→D.EC.D is disabled, the economizer will always be disabled during dehumidification. • Cooling — For all cooling control types: A High Cool HVAC mode will be requested internally to the control to maintain diagnostics, although the end user will see a Dehumidification mode at the display. In addition, for multi-stage cooling units the cooling control point will be set to Configuration→DEHU→D.C.SP (no SASP reset is applied). • Reheat When Cooling Demand is Present — For reheat control during dehumidification: If reheat follows an offset subtracted from return-air temperature (Configuration→DEHU→D.SEL = 2), then no heating will be initiated and the alarm relay will be energized. If Configuration→DEHU→D.SEL = 1 and Configuration→HEAT→HT.CF = staged gas or hot water valve, then the selected heating control type will operate in the low heat/modulating mode. • The heating control point will be whatever the actual cooling set point would have been (without any supply air reset applied). • Reheat During Vent Mode — If configured (Configuration→DEHU→D.V.CF = 0), the heating control point will be equal to RAT - D.V.RA. If configured (Configuration→DEHU→D.V.CF=1), the heating control point will be equal to the D.V.HT set point. Ending Dehumidification and Reheat Control — When either the humidity sensor fall 5% below the set point (Configuration→DEHU→D.RH.S) or the discrete input reads “LOW”, the Dehumidification mode will end. • D.SEL = 1 — The control will perform both dehumidification and reheat with modulating valve (hydronic). • D.SEL = 2 — The control will perform dehumidification and reheat with staged gas only. • D.SEL = 3 — The control will perform both dehumidification and reheat with third party heat via an alarm relay. In the case of D.SEL=3, during dehumidification, the alarm relay will close to convey the need for reheat. A typical application might be to energize a 3-way valve to perform hot gas reheat. Dehumidification Sensor (D.SEN) — The sensor can be configured for the following settings: • D.SEN = 1 — Initiated by return air relative humidity sensor. • D.SEN = 2 — Initiated by space relative humidity sensor. • D.SEN = 3 — Initiated by discrete input. Economizer Disable in Dehum Mode (D.EC.D) — This configuration determines economizer operation during Dehumidification mode. • D.EC.D = YES — Economizer disabled during dehumidification (default). • D.EC.D = NO — Economizer not disabled during dehumidification. Vent Reheat Set Point Select (D.V.CF) — This configuration determines how the vent reheat set point is selected. • D.V.CF = 0 — Reheat follows an offset subtracted from return air temperature (D.V.RA). • D.V.CF = 1 — Reheat follows a dehumidification heat set point (D.V.HT). Vent Reheat RAT Offset (D.V.RA) — Set point offset used only during the vent mode. The air will be reheated to returnair temperature less this offset. Vent Reheat Set Point (D.V.HT) — Set point used only during the vent mode. The air will be reheated to this set point. Dehumidify Cool Set Point (D.C.SP) — This is the dehumidification cooling set point. Dehumidity RH Set Point (D.RH.S) — This is the dehumidification relative humidity trip point. OPERATION — Dehumidification and reheat can only occur if the unit is equipped with either staged gas or hydronic heat. Dehumidification without reheat can be done on any unit but Configuration→DEHU→D.SEL must be set to 2. If the machine’s control type is a TSTAT type (Configuration→UNIT→C.TYP=3 or 4) and the discrete input selection for the sensor is not configured (D.SEN not equal to 3), dehumidification will be disabled. If the machine’s control type is a TSTAT type (Configuration→UNIT→C.TYP=3 or 4) and the economizer is able to provide cooling, a dehumidification mode may be called out, but the control will not request mechanical cooling. If a 2-stage control type is selected (Configuration→UNIT →C.TYP = 4 or 6), then the economizer, if active, locks out mechanical cooling during the Dehumidification mode. NOTE: Configuring Configuration→DEHU→D.SEN to 1,2 or 3 will enable the CEM board along with the sensor selected for control. Temperature Compensated Start — This logic is used when the unit is in the unoccupied state. The control will calculate early Start Bias time based on Space Temperature 78 one time broadcaster is present, problems with the time will occur. NOTE: Only the time and date broadcaster can perform daylight savings time adjustments. Even if the rooftop is stand alone, the user may want to set this to ON to accomplish the daylight/savings function. CCN OAT Broadcast (OAT.B) — If this configuration is set to ON, the control will periodically broadcast its outside-air temperature at a rate of once every 30 minutes. CCN OARH Broadcast (ORH.B) — If this configuration is set to ON, the control will periodically broadcast its outside air relative humidity at a rate of once every 30 minutes. CCN OAQ Broadcast (OAQ.B) — If this configuration is set to ON, the control will periodically broadcast its outside air quality reading at a rate of once every 30 minutes. Global Schedule Broadcast (G.S.B) — If this configuration is set to ON and the schedule number (SCH.N) is between 65 and 99, then the control will broadcast the internal time schedule once every 2 minutes. CCN Broadcast Acknowledger (B.ACK) — If this configuration is set to ON, then when any broadcasting is done on the bus, this device will respond to and acknowledge. Only one device per bus can be configured for this option. Schedule Number (SCH.N) — This configuration determines what schedule the control may follow. SCH.N = 0 The control is always occupied. SCH.N = 1 The control follows its internal time schedules. The user may enter any number between 1 and 64 but it will be overwritten to “1” by the control as it only has one internal schedule. SCH.N = 65-99 The control is either set up to receive to a broadcasted time schedule set to this number or the control is set up to broadcast its internal time schedule (G.S.B) to the network and this is the global schedule number it is broadcasting. If this is the case, then the control still follows its internal time schedules. Accept Global Holidays? (HOL.T) — If a device is broadcasting the time on the bus, it is possible to accept the time yet not accept the global holiday from the broadcast message. Override Time Limit (O.T.L) — This configuration allows the user to decide how long an override occurs when it is initiated. The override may be configured from 1 to 4 hours. If the time is set to 0, the override function will become disabled. Timed Override Hours (OV.EX) — This displays the current number of hours left in an override. It is possible to cancel an override in progress by writing “0” to this variable, thereby removing the override time left. SPT Override Enabled? (SPT.O) — If a space sensor is present, then it is possible to override an unoccupied period by pushing the override button on the T55 or T56 sensor. This option allows the user to disable this function by setting this configuration to NO. T58 Override Enabled? (T58.O) — The T58 sensor is a CCN device that allows cooling/heating set points to be adjusted, space temperature to be written to the rooftop unit, and the ability to initiate a timed override. This option allows the user to disable the override initiated from the T58 sensor by setting this option to NO. Global Schedule Override? (GL.OV) — If the control is set to receive global schedules then it is also possible for the global schedule broadcaster to call out an override condition as well. This configuration allows the user to disable the global schedule broadcaster from overriding the control. deviation from the occupied cooling and heating set points. This will allow the control to start the unit so that the space is at conditioned levels when the occupied period starts. This is required for ASHRAE 90.1 compliance. A space sensor is required for non-linkage applications. SETTING UP THE SYSTEM — The settings for temperature compensated start can be found in the local display under Configuration→UNIT. ITEM TCS.C TCS.H EXPANSION RANGE UNITS CCN POINT Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT TCST-Cool Factor (TCS.C) — This is the factor for the start time bias equation for cooling. TCST-Heat Factor (TCS.H) — This is the factor for the start time bias equation for heating. NOTE: Temperature compensated start is disabled when these factors are set to 0. TEMPERATURE COMPENSATED START LOGIC — The following conditions must be met for the algorithm to run: • Unit is in unoccupied state. • Next occupied time is valid. • Current time of day is valid. • Valid space temperature reading is available (sensor or DAV-Linkage). The algorithm will calculate a Start Bias time in minutes using the following equations: If (space temperature > occupied cooling set point) Start Bias Time = (space temperature – occupied cooling set point)* TCS.C If (space temperature < occupied heating set point) Start Bias Time = (occupied heating set point – space temperature)*TCS.H When the Start Bias Time is greater than zero the algorithm will subtract it from the next occupied time to calculate the new start time. When the new start time is reached, the Temperature Compensated Start mode is set (Operating Modes→MODE→ T.C.ST), the fan is started and the unit controlled as in an occupied state. Once set, Temperature Compensated mode will stay on until the unit goes into the Occupied mode. The Start Bias Time will be written into the CCN Linkage Equipment Table if the unit is controlled in DAV mode. If the Unoccupied Economizer Free Cool mode is active (Operating Modes→HVAC = “UNOCC FREE COOL”) when temperature compensated start begins, the Unoccupied Free Cool mode will be stopped. Carrier Comfort Network® (CCN) — It is possible to configure the ComfortLink™ controls to participate as an element of the Carrier Comfort Network (CCN) system directly from the local display. This section will deal with explaining the various programmable options which are found under the CCN sub-menu in the Configuration mode. The major configurations for CCN programming are located in the local displays at Configuration→CCN. See Table 63. CCN Address (CCNA) — This configuration is the CCN address the rooftop is assigned. CCN Bus Number (CCNB) — This configuration is the CCN bus the rooftop is assigned. CCN Baud Rate (BAUD) — This configuration is the CCN baud rate. CCN Time/Date Broadcast (TM.DT) — If this configuration is set to ON, the control will periodically send the time and date out onto the CCN bus once a minute. If this device is on a CCN network then it will be important to make sure that only one device on the bus has this configuration set to ON. If more than 79 Table 63 — CCN Configuration ITEM CCN CCNA CCNB BAUD BROD TM.DT OAT.B ORH.B OAQ.B G.S.B B.ACK SC.OV SCH.N HOL.T O.T.L. OV.EX SPT.O T58.O GL.OV EXPANSION CCN CONFIGURATION CCN Address CCN Bus Number CCN Baud Rate CCN BROADCST DEFINITIONS CCN Time/Date Broadcast CCN OAT Broadcast CCN OARH Broadcast CCN OAQ Broadcast Global Schedule Broadcst CCN Broadcast Ack'er CCN SCHEDULES-OVERRIDES Schedule Number Accept Global Holidays? Override Time Limit Timed Override Hours SPT Override Enabled ? T58 Override Enabled ? Global Sched. Override ? RANGE UNITS POINT DEFAULT 1 - 239 0 - 239 1-5 CCNADD CCNBUS CCNBAUDD 1 0 3 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF CCNBC OATBC OARHBC OAQBC GSBC CCNBCACK On Off Off Off Off Off 0 - 99 YES/NO 0-4 0-4 YES/NO YES/NO YES/NO SCHEDNUM HOLIDAYT OTL OVR_EXT SPT_OVER T58_OVER GLBLOVER 1 No 1 0 Yes Yes No HRS HRS Alert Limit (RA.H.O), then Alert 305 will be generated and operation will continue. The alert will automatically reset. RAT Low Alert Limit/Unocc (RA.L.U) — If the return-air temperature is below the configurable unoccupied RAT Low Alert Limit (RA.L.U), then Alert 304 will be generated. Unit operation will continue but VAV heating operation will be disabled. The alert will automatically reset. RAT High Alert Limit/Unocc (RA.H.U) — If the return-air temperature is above the configurable unoccupied RAT High Alert Limit (RA.H.U), then Alert 305 will be generated. Operation will continue. The alert will automatically reset. OAT Low Alert Limit (OAT.L) — If the outside-air temperature measured by the OAT thermistor is below the configurable OAT Low Alert Limit (OAT.L) then alert T316 will be generated. OAT High Alert Limit (OAT.H) — If the outside-air temperature measured by the OAT thermistor is above the configurable OAT High Alert Limit (OAT.H) then alert T317 will be generated RARH Low Alert Limit (R.RH.L) — If the unit is configured to use a return air relative humidity sensor (Configuration→UNIT→SENS→RRH.S), and the measured level is below the configurable RH Low Alert Limit (R.RH.L), then Alert 308 will occur. The unit will continue to run and the alert will automatically reset. RARH High Alert Limit (R.RH.H) — If the unit is configured to use a return air relative humidity sensor (Configuration→UNIT→SENS→RRHS), and the measured level is above the configurable RARH High Alert Limit (R.RH.H), then Alert 309 will occur. The unit will continue to run and the alert will automatically reset. OARH Low Alert Limit (O.RH.L) — If the unit is configured to use an outdoor air relative humidity sensor (Configuration→ECON→ORH.S) and the measured level is below the configurable OARH Low Alert Limit (O.RH.L), then economizer operation will be disabled. The unit will continue to run and the alert will automatically reset. OARH High Alert Limit (O.RH.H) — If the unit is configured to use a return air relative humidity sensor (Configuration→ECON→ORH.S) and the measured level is above the configurable OARH High Alert Limit (O.RH.H), then economizer operation will be disabled. The unit will continue to run and the alert will automatically reset. Supply Duct Pressure Low Alert Limit (SP.L) — If the unit is a VAV unit with a supply duct pressure sensor and the measured supply duct static pressure is below the configurable SP Low Alert Limit (DP.L), then Alert 310 will occur. The unit will continue to run and the alert will automatically reset. Alert Limit Configuration — The ALLM submenu is used to configure the alert limit set points. A list is shown in Table 64. SPT Low Alert Limit/Occ (SP.L.O) — If the space temperature is below the configurable occupied SPT Low Alert Limit (SP.L.O), then Alert 300 will be generated and the unit will be stopped. The alert will automatically reset. SPT High Alert Limit/Occ (SP.H.O) — If the space temperature is above the configurable occupied SPT High Alert Limit (SP.H.O), then Alert 301 will be generated and the unit will be stopped. The alert will automatically reset. SPT Low Alert Limit/Unocc (SP.L.U) — If the space temperature is below the configurable unoccupied SPT Low Alert Limit (SP.L.U), then Alert 300 will be generated and the unit will be stopped. The alert will automatically reset. SPT High Alert Limit/Unocc (SP.H.U) — If the space temperature is above the configurable unoccupied SPT High Alert Limit (SP.H.U), then Alert 301 will be generated and the unit will be stopped. The alert will automatically reset. EDT Low Alert Limit/Occ (SA.L.O) — If the space temperature is below the configurable occupied evaporator discharge temperature (EDT) Low Alert Limit (SA.L.O), then Alert 302 will be generated and cooling operation will be stopped but heating operation will continue. The alert will automatically reset. EDT High Alert Limit/Occ (SA.H.O) — If the space temperature is above the configurable occupied EDT High Alert Limit (SA.H.O), then Alert 303 will be generated and heating operation will be stopped but cooling operation will continue. The alert will automatically reset. EDT Low Alert Limit/Unocc (SA.L.U) — If the space temperature is below the configurable unoccupied EDT Low Alert Limit (SA.L.U), then Alert 302 will be generated and cooling operation will be stopped but heating operation will continue. The alert will automatically reset. EDT High Alert Limit/Unocc (SA.H.U) — If the space temperature is above the configurable unoccupied EDT High Alert Limit (SA.H.U), then Alert 303 will be generated and heating operation will be stopped but cooling operation will continue. The alert will automatically reset. RAT Low Alert Limit/Occ (RA.L.O) — If the return-air temperature is below the configurable occupied RAT Low Alert Limit (RA.L.O), then Alert 304 will be generated and internal routines will be modified. Unit operation will continue but VAV heating operation will be disabled. The alert will automatically reset. RAT High Alert Limit/Occ (RA.H.O) — If the return-air temperature is above the configurable occupied RAT High 80 Table 64 — Alert Limit Configuration ITEM SP.L.O SP.H.O SP.L.U SP.H.U SA.L.O SA.H.O SA.L.U SA.H.U RA.L.O RA.H.O RA.L.U RA.H.U OAT.L OAT.H R.RH.L R.RH.H O.RH.L O.RH.H SP.L SP.H BP.L BP.H IAQ.H EXPANSION SPT lo alert limit/occ SPT hi alert limit/occ SPT lo alert limit/unocc SPT hi alert limit/unocc EDT lo alert limit/occ EDT hi alert limit/occ EDT lo alert limit/unocc EDT hi alert limit/unocc RAT lo alert limit/occ RAT hi alert limit/occ RAT lo alert limit/unocc RAT hi alert limit/unocc OAT lo alert limit OAT hi alert limit RARH low alert limit RARH high alert limit OARH low alert limit OARH high alert limit SP low alert limit SP high alert limit BP lo alert limit BP high alert limit IAQ high alert limit RANGE -10-245 -10-245 -10-245 -10-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 0-100 0-100 0-100 0-100 0-5 0-5 -0.25-0.25 -0.25-0.25 0-5000 UNITS dF dF dF dF dF dF dF dF dF dF dF dF dF dF % % % % "H2O "H2O "H2O "H2O POINT SPLO SPHO SPLU SPHU SALO SAHO SALU SAHU RALO RAHO RALU RAHU OATL OATH RRHL RRHH ORHL ORHH SPL SPH BPL BPH IAQH DEFAULT 60 85 45 100 40 100 40 100 60 90 40 100 -40 150 0 100 0 100 0 2 -0.25 0.25 1200 Space Temperature Sensor Trim (SPT.T) — This variable is used to adjust the space temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Limit Switch Trim (L.SW.T) — This variable is used to adjust the limit switch temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Air Temperature Leaving Evaporator Trim (CCT.T) — This variable is used to adjust the leaving evaporator temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Suction Pressure Circuit A Trim (SP.A.T) — This variable is used to adjust the suction pressure sensor reading for circuit A. The sensor reading can be adjusted ± 50 psig to match the actual measured pressure. Suction Pressure Circuit B Trim (SP.B.T) — This variable is used to adjust the suction pressure sensor reading for circuit B. The sensor reading can be adjusted ± 50 psig to match the actual measured pressure. Discharge Pressure Circuit A Trim (DP.A.T) — This variable is used to adjust the discharge pressure sensor reading for circuit A. The sensor reading can be adjusted ± 50 psig to match the actual measured pressure. Discharge Pressure Circuit B Trim (DP.B.T) — This variable is used to adjust the discharge pressure sensor reading for circuit B. The sensor reading can be adjusted ±50 psig to match the actual measured pressure. 4 to 20 mA Inputs — There are a number of 4 to 20 mA inputs which may be calibrated. These inputs are located in Inputs→4-20. They are: • SP.M.T — static pressure milliamp trim • BP.M.T — building pressure milliamp trim • OA.M.T — outside air cfm milliamp trim • RA.M.T — return air cfm milliamp trim • SA.M.T — supply air cfm milliamp trim Supply Duct Pressure High Alert Limit (SP.H) — If the unit is a VAV unit with a supply duct pressure sensor and the measured supply duct static pressure is above the configurable SP High Alert Limit (SP.H), then Alert 311 will occur. The unit will continue to run and the alert will automatically reset. Building Pressure Low Alert Limit (BP.L) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP Low Alert Limit (BP.L). If the measured pressure is below the limit then Alert 312 will occur. Building Pressure High Alert Limit (BP.H) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP Hi Alert Limit (BP.H). If the measured pressure is above the limit, then Alert 313 will occur. Indoor Air Quality High Alert Limit (IAQ.H) — If the unit is configured to use a CO2 sensor and the level is above the configurable IAQ High Alert Limit (IAQ.H) then the alert will occur. The unit will continue to run and the alert will automatically reset. Sensor Trim Configuration — The TRIM submenu is used to calibrate the sensor trim settings. The trim settings are used when the actual measured reading does not match the sensor output. The sensor can be adjusted to match the actual measured reading with the trim function. A list is shown in Table 65. IMPORTANT: Sensor trim must not be used to extend unit operation past the allowable operating range. Doing so may void the warranty. Air Temperature Leaving Supply Fan Sensor (SAT.T) — This variable is used to adjust the supply fan temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Return Air Temperature Sensor Trim (RAT.T) — This variable is used to adjust the return air temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Outdoor Air Temperature Sensor Trim (OAT.T) — This variable is used to adjust the outdoor air temperature sensor reading. The sensor reading can be adjusted ± 10° F to match the actual measured temperature. Discrete Switch Logic Configuration — The SW.LG submenu is used to configure the normally open/normally closed settings of switches and inputs. This is used when field-supplied switches or input devices are used instead of Carrier devices. The normally open or normally closed setting may be different on a field-supplied device. These points are used to match the control logic to the field-supplied device. 81 Table 65 — Sensor Trim Configuration ITEM TRIM SAT.T RAT.T OAT.T SPT.T L.SW.T CCT.T SP.A.T SP.B.T DP.A.T DP.B.T EXPANSION SENSOR TRIM CONFIG. Air Temp Lvg SF Trim RAT Trim OAT Trim SPT Trim Limit Switch Trim Air Temp Lvg Evap Trim Suct.Press.Circ.A Trim Suct.Press.Circ.B Trim Dis.Press.Circ.A Trim Dis.Press.Circ.B Trim RANGE -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -50 - 50 -50 - 50 -50 - 50 -50 - 50 UNITS POINT ^F ^F ^F ^F ^F ^F PSIG PSIG PSIG PSIG SAT_TRIM RAT_TRIM OAT_TRIM SPT_TRIM LSW_TRIM CCT_TRIM SPA_TRIM SPB_TRIM DPA_TRIM DPB_TRIM DEFAULT 0 0 0 0 0 0 0 0 0 0 IAQ Discrete Input — Low (IAQ.L) — The IAQ discrete input is set for normally open when low. If a field-supplied IAQ discrete input is used that is normally closed, change this variable to closed. Fire Shutdown — Off (FSD.L) — The fire shutdown input is set for normally open when off. If a field-supplied fire shutdown input is used that is normally closed, change this variable to closed. Pressurization Switch — Off (PRS.L) — The pressurization input is set for normally open when off. If a field-supplied pressurization input is used that is normally closed, change this variable to closed. Evacuation Switch — Off (EVC.L) — The evacuation input is set for normally open when off. If a field-supplied evacuation input is used that is normally closed, change this variable to closed. Smoke Purge — Off (PRG.L) — The smoke purge input is set for normally open when off. If a field-supplied smoke purge input is used that is normally closed, change this variable to closed. Dehumidify Switch — Off (DH.LG) — The dehumidify input is set for normally open when off. If a field-supplied dehumidify input is used that is normally closed, change this variable to closed. The defaults for this switch logic section will not normally need changing. However, if a field-installed switch is used that is different from the Carrier switch, these settings may need adjustment. IMPORTANT: Many of the switch inputs to the control can be configured to operate as normally open or normally closed. Settings for switch logic are found at the local displays under the Configuration→SW.LG submenu. See Table 66. Filter Status Input — Clean (FTS.L) — The filter status input for clean filters is set for normally open. If a field-supplied filter status switch is used that is normally closed for a clean filter, change this variable to closed. IGC Feedback — Off (IGC.L) — The input for IGC feedback is set for normally open for off. If a field-supplied IGC feedback switch is used that is normally closed for feedback off, change this variable to closed. Remote Switch — Off (RMI.L) — The remote switch is set for normally open when off. If a field-supplied control switch is used that is normally closed for an off signal, change this variable to closed. Enthaply Input — Low (ENT.L) — The enthalpy input is set for normally closed when low. If a field-supplied enthalpy switch is used that is normally open when low, change this variable to open. Fan Status Switch — Off (SFS.L) — The fan status switch input is set for normally open for off. If a field-supplied fan status switch is used that is normally closed, change this variable to closed. Demand Limit Switch 1 — Off (DL1.L) — The demand limit switch no. 1 input is set for normally open for off. If a field-supplied demand limit switch is used that is normally closed, change this variable to closed. Demand Limit Switch 2 — Off (DL2.L) — The demand limit switch no. 2 input is set for normally open for off. If a field-supplied demand limit switch is used that is normally closed, change this variable to closed. Display Configuration — The DISP submenu is used to configure the local display settings. A list is shown in Table 67. Test Display LEDs (TEST) — This is used to test the operation of the ComfortLink™ display. Metric Display (METR) — This variable is used to change the display from English units to Metric units. Language Selection (LANG) — This variable is used to change the language of the ComfortLink display. At this time, only English is available. Password Enable (PAS.E) — This variable enables or disables the use of a password. The password is used to restrict use of the control to change configurations. Service Password (PASS) — This variable is the 4-digit numeric password that is required if enabled. Table 66 — Switch Logic Configuration ITEM SW.LG FTS.L IGC.L RMI.L ENT.L SFS.L DL1.L DL2.L IAQ.L FSD.L PRS.L EVC.L PRG.L DH.LG EXPANSION SWITCH LOGIC: NO / NC Filter Status Inpt-Clean IGC Feedback - Off RemSw Off-Unoc-Strt-NoOv Enthalpy Input - Low Fan Status Sw. - Off Dmd.Lmt.Sw.1 - Off Dmd.Lmt.Sw.2 - Off IAQ Disc.Input - Low Fire Shutdown - Off Pressurization Sw. - Off Evacuation Sw. - Off Smoke Purge Sw. - Off Dehumidify Sw. - Off RANGE Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close 82 CCN POINT FLTSLOGC GASFANLG RMTINLOG ENTHLOGC SFSLOGIC DMD_SW1L DMD_SW2L IAQINLOG FSDLOGIC PRESLOGC EVACLOGC PURGLOGC DHDISCLG DEFAULT Open Open Open Close Open Open Open Open Open Open Open Open Open Table 67 — Display Configuration ITEM EXPANSION Test Display LEDs Metric Display Language Selection Password Enable Service Password TEST METR LANG PAS.E PASS RANGE ON/OFF ON/OFF 0-1(multi-text strings) ENABLE/DISABLE 0000-9999 Table 68 — Remote Switch Configuration REMT RM.CF RMI.L EXPANSION RANGE Remote ON/OFF Input State Remote Switch 0-3 Config RemSw Open/Close Off-Unoc-Strt-NoOv UNITS POINT TEST DISPUNIT LANGUAGE PASS_EBL PASSWORD DEFAULT Off Off 0 Enable 1111 during periods of low evaporator loading. This system is not controlled by the ComfortLink™ control system and it is available to operate whenever circuit A is running. The hot gas bypass option consists of a pressure regulating valve, a manual service valve and tubing connecting the circuit A hot gas refrigerant line to the circuit A evaporator distributors (one distributor on sizes 030-035, two distributors on sizes 040-105). The pressure regulating valve opens the bypass circuit as the evaporator suction pressure decreases into a range that might generate frost formation on the evaporator surface if sustained compressor operation occurs. The hot gas refrigerant enters the evaporator coil and adds refrigeration load to the compressor circuit to offset a low load situation in the mixed air temperature condition. Total bypass capacity is approximately 5 tons. The hot gas bypass system is a factory-installed option, installed on circuit A only. When this option is provided, the control function for Lead-Lag sequencing must be disabled (Configuration→ Cool→ L.L.EN is set to No). Remote Control Switch Input — The remote switch input is located on the RCB board and connected to TB201 terminals 1 and 2. The switch can be used for several remote control functions. See Table 68. ITEM UNITS CCN POINT RMTIN RMTINCFG RMTINLOG Remote Input State (Inputs→GEN.I→REMT) — This is the actual real time state of the remote input. Remote Switch Config (Configuration→UNIT→ RM.CF) — This is the configuration that allows the user to assign different types of functionality to the remote discrete input. • 0 — NO REMOTE SW — The remote switch will not be used. • 1 — OCC-UNOCC SW — The remote switch input will control the occupancy state. When the remote switch input is ON, the unit will forced into the occupied mode. When the remote switch is OFF, the unit will be forced into the unoccupied mode. • 2 — STRT/STOP — The remote switch input will start and stop the unit. When the unit is commanded to stop, any timeguards in place on compressors will be honored first. When the remote switch is ON, the unit will be commanded to stop. When the remote switch is OFF the unit will be enabled to operate. • 3 — OVERRIDE SW — The remote switch can be used to override any internal or external time schedule being used by the control and force the unit into an occupied mode when the remote input state is ON. When the remote switch is ON, the unit will be forced into an occupied state. When the remote switch is OFF, the unit will use its internal or external time schedules. Remote Switch Logic Configuration (Configuration→ SW.LG→RMI.L) — The control allows for the configuration of a normally open/closed status of the remote input switch via RMI.L. If this variable is configured OPEN, then when the switch is open, the remote input switch perceives the logic state as OFF. Correspondingly, if RMI.L is set to CLOSED, the remote input switch will perceive a closed switch as meaning OFF. See Table 69. Space Temperature Offset — Space Temperature Off- set corresponds to a slider on a T56 sensor that allows the occupant to adjust the space temperature by a configured range during an occupied period. This sensor is only applicable to units that are configured as either 2-Stage SPT or Multi-Stage SPT control (Configuration→UNIT→C.TYP = 5 and 6). ITEM SP.O.S SP.O.R SPTO EXPANSION Space Temp Offset Sensor Space Temp Offset Range Space Temperature Offset RANGE UNITS CCN POINT SPTOSENS Enable/ Disable 1 - 10 SPTO_RNG +- SP.O.R ^F SPTO Space Temperature Offset Sensor (Configuration→UNIT →SENS→SP.O.S) — This configuration disables the reading of the offset slider. Space Temperature Offset Range (Configuration →UNIT→SENS→SP.O.R) — This configuration establishes the range, in degrees F, that the T56 slider can affect SPTO when adjusting the slider from the far left (-SP.O.R) to the far right (+SP.O.R). The default is 5° F. Space Temperature Offset Value (Temperatures→AIR.T →SPTO) — The Space Temperature Offset Value is the reading of the slider potentiometer in the T56 that is resolved to delta degrees based on SP.O.R. Hot Gas Bypass — Hot gas bypass is an automatically operating system used to limit evaporator suction pressure Table 69 — Remote Switch Logic Configuration REMOTE SWITCH LOGIC CONFIGURATION (RMI.L) OPEN CLOSED SWITCH STATUS REMOTE INPUT STATE (REMT) OPEN CLOSED OPEN CLOSED OFF (0) ON (1) ON (0) OFF (1) 0 REMOTE SWITCH CONFIGURATION (RM.CF) 1 2 3 No Remote Switch Occ-Unocc Switch Start/Stop Override xxxxx xxxxx xxxxx xxxxx Unoccupied Occupied Occupied Unoccupied Start Stop Stop Start No Override Override Override No Override 83 SATURDAY IN PERIOD (PER.X→DAYS→SAT) — This variable is used to include or remove Saturday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Saturday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Saturday. This variable can be set for Periods 1 through 8. SUNDAY IN PERIOD (PER.X→DAYS→SUN) — This variable is used to include or remove Sunday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Sunday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Sunday. This variable can be set for Periods 1 through 8. HOLIDAY IN PERIOD (PER.X→DAYS→HOL) — This variable is used to include or remove a Holiday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then holidays will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on holidays. This variable can be set for Periods 1 through 8. OCCUPIED FROM (PER.X→OCC) — This variable is used to configure the start time of the Occupied period. All days in the same period set to YES will enter into Occupied mode at this time. OCCUPIED TO (PER.X→UNC) — This variable is used to configure the end time of the Occupied period. All days in the same period set to YES will exit Occupied mode at this time. TIME CLOCK CONFIGURATION This section describes each Time Clock menu item. Not every point will need to be configured for every unit. Refer to the Controls Quick Start section for more information on what set points need to be configured for different applications. The Time Clock menu items are discussed in the same order that they are displayed in the Time Clock table. The Time Clock table is shown in Table 70. Hour and Minute (HH.MM) — The hour and minute of the time clock are displayed in 24-hour, military time. Time can be adjusted manually by the user. When connected to the CCN, the unit can be configured to transmit time over the network or receive time from a network device. All devices on the CCN should use the same time. Only one device on the CCN should broadcast time or problems will occur. Month of Year (MNTH) — This variable is the current month of the calendar year. Day of Month (DOM) — This variable is the current day (1 to 31) of the month. Day of Week (DAY) — This variable is the current day of the week (Monday through Sunday). Year (YEAR) — This variable is the current year (for example, 2005). Local Time Schedule (SCH.L) — This submenu is Local Holiday Schedules (HOL.L) — This submenu used to program the time schedules. There are 8 periods (PER.1 through PER.8). Each time period can be used to set up a local schedule for the unit. Refer to the Programming Operating Schedules section on page 36 for more information. MONDAY IN PERIOD (PER.X→DAYS→MON) — This variable is used to include or remove Monday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Monday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Monday. This variable can be set for Periods 1 through 8. TUESDAY IN PERIOD (PER.X→DAYS→TUE) — This variable is used to include or remove Tuesday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Tuesday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Tuesday. This variable can be set for Periods 1 through 8. WEDNESDAY IN PERIOD (PER.X→DAYS→WED) — This variable is used to include or remove Wednesday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Wednesday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Wednesday. This variable can be set for Periods 1 through 8. THURSDAY IN PERIOD (PER.X→DAYS→THU) — This variable is used to include or remove Thursday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Thursday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Thursday. This variable can be set for Periods 1 through 8. FRIDAY IN PERIOD (PER.X→DAYS→FRI) — This variable is used to include or remove Friday from the schedule. Each period is assigned an occupied on and off time. If this variable is set to YES, then Friday will be included in that period’s occupied time schedule. If this variable is set to NO, then the period’s occupied time schedule will not be used on Friday. This variable can be set for Periods 1 through 8. is used to program the local holiday schedules. Up to 30 holidays can be configured. When a holiday occurs, the unit will follow the occupied schedules that have the HOLIDAY IN PERIOD point set to YES. Holiday Start Month (HD.01 to HD.30→ MON) — This is the start month for the holiday. The numbers 1 to 12 correspond to the months of the year (e.g., January = 1). Holiday Start Day (HD.01 to HD.30→DAY) — This is the start day of the month for the holiday. The day can be set from 1 to 31. Holdiay Duration (HD.01 to HD.30→LEN) — This is the length in days of the holiday. The holiday can last up to 99 days. Daylight Savings Time (DAY.S) — The daylight savings time function is used in applications where daylight savings time occurs. The function will automatically correct the clock on the days configured for daylight savings time. DAYLIGHT SAVINGS START (DS.ST) — This submenu configures the start date and time for daylight savings. Daylight Savings Start Month (DS.ST→ST.MN) — This is the start month for daylight savings time. The numbers 1 to 12 correspond to the months of the year (e.g., January = 1). Daylight Savings Start Week (DS.ST→ST.WK) — This is the start week of the month for daylight savings. The week can be set from 1 to 5. Daylight Savings Start Day (DS.ST→ST.DY) — This is the start day of the week for daylight savings. The day can be set from 1 to 7 (Sunday=1, Monday=2, etc.). Daylight Savings Minutes To Add (DS.ST→MIN.A) — This is the amount of time that will be added to the time clock for daylight savings. DAYLIGHT SAVINGS STOP (DS.SP) — This submenu configures the end date and time for daylight savings. Daylight Savings Stop Month (DS.SP→SP.MN) — This is the stop month for daylight savings time. The numbers 1 to 12 correspond to the months of the year (e.g., January = 1). 84 Table 70 — Time Clock Menu ITEM TIME HH.MM DATE MNTH DOM DAY YEAR SCH.L PER.1 PER.1→DAYS PER.1→DAYS→MON PER.1→DAYS→TUE PER.1→DAYS→WED PER.1→DAYS→THU PER.1→DAYS→FRI PER.1→DAYS→SAT PER.1→DAYS→SUN PER.1→DAYS→HOL PER.1→OCC PER.1→UNC Repeat for periods 2-8 HOL.L HD.01 HD.01→MON HD.01→DAY HD.01→LEN Repeat for holidays 2-30 DAY.S DS.ST DS.ST→ST.MN DS.ST→ST.WK DS.ST→ST.DY DS.ST→MIN.A DS.SP DS.SP→SP.MN DS.SP→SP.WK DS.SP→SP.DY DS.SP→MIN.S EXPANSION TIME OF DAY Hour and Minute MONTH,DATE,DAY AND YEAR Month of Year Day of Month Day of Week Year LOCAL TIME SCHEDULE PERIOD 1 DAY FLAGS FOR PERIOD 1 Monday in Period Tuesday in Period Wednesday in Period Thursday in Period Friday in Period Saturday in Period Sunday in Period Holiday in Period Occupied from Occupied to LOCAL HOLIDAY SCHEDULES HOLIDAY SCHEDULE 01 Holiday Start Month Start Day Duration (Days) RANGE DAYLIGHT SAVINGS TIME DAYLIGHT SAVINGS START Month Week Day Minutes to Add DAYLIGHTS SAVINGS STOP Month Week Day Minutes to Subtract POINT DEFAULT 00:00 TIME multi-text strings 0-31 multi-text strings e.g. 2003 MOY DOM DOWDISP YOCDISP YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO 00:00 00:00 PER1MON PER1TUE PER1WED PER1THU PER1FRI PER1SAT PER1SUN PER1HOL PER1_OCC PER1_UNC 0-12 0-31 0-99 HOL_MON1 HOL_DAY1 HOL_LEN1 1 - 12 1-5 1-7 0 - 90 STARTM STARTW STARTD MINADD 4 1 7 60 1 - 12 1-5 1-7 0 - 90 STOPM STOPW STOPD MINSUB 10 5 7 60 Period 1 only Yes Yes Yes Yes Yes Yes Yes Yes 00:00 24:00 Daylight Savings Stop Week (DS.SP→SP.WK) — This is the stop week of the month for daylight savings. The week can be set from 1 to 5. Daylight Savings Stop Day (DS.SP→SP.DY) — This is the stop day of the week for daylight savings. The day can be set from 1 to 7 (Sunday=1, Monday=2, etc.). Daylight Savings Minutes To Subtract (DS.SP→MIN.S) — This is the amount of time that will be removed from the time clock after daylight savings ends. Service Analysis — Detailed service analysis can be TROUBLESHOOTING Thermistor Troubleshooting — The EDT, OAT, found in Tables 71-73 and Fig. 13. Restart Procedure — Before attempting to restart the machine, check the alarm list to determine the cause of the shutdown. If a shutdown alarm for a particular circuit has occurred, determine and correct the cause before allowing the unit to run under its own control again. When there is problem, the unit should be diagnosed in Service Test mode. The alarms must be reset before the circuit can operate in either Normal mode or Service Test mode. RAT, LAT, T55, T56, and T58 space temperature sensors use 10K thermistors. Resistances at various temperatures are listed in Tables 74 and 75. THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital volt-ohmmeter is required to perform this check. 1. Connect the digital voltmeter across the appropriate thermistor terminals at the J8 terminal strip on the main base board. 2. Using the voltage reading obtained, read the sensor temperature from Tables 74 and 75. 3. To check thermistor accuracy, measure temperature at probe location with an accurate thermocouple-type temperature-measuring instrument. Insulate thermocouple to avoid ambient temperatures from influencing reading. Temperature measured by thermocouple and temperature determined from thermistor voltage reading should be within 5° F (3° C) if care was taken in applying thermocouple and taking readings. If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) using either voltage drop measured across thermistor at the J8 terminal, or by The scrolling marquee display shows the actual operating conditions of the unit while it is running. If there are alarms or there have been alarms, they will be displayed in either the current alarm list or the history alarm list. The Service Test mode allows operation of the compressors, fans, and other components to be checked while the unit is not operating. Complete Unit Stoppage — There are several conditions that can cause the unit to not provide heating or cooling. If an alarm is active which causes the unit to shut down, diagnose the problem using the information provided in the Alarms and Alerts section on page 94, but also check for the following: • Cooling and heating loads are satisfied. • Programmed schedule. • General power failure. • Tripped control circuit transformers circuit breakers. • Tripped compressor circuit breakers. • Unit is turned off through the CCN network. Single Circuit Stoppage — If a single circuit stops incorrectly, there are several possible causes. The problem should be investigated using information from the alarm and alert list. 85 determining the resistance with unit shut down and thermistor disconnected from J8. Compare the values determined with the value read by the control in the Temperatures mode using the scrolling marquee display. pressure of circuits A and B. The pressure/voltage characteristics of these transducers are in shown in Tables 76 and 77. The accuracy of these transducers can be verified by connecting an accurate pressure gage to the second refrigerant port in the suction line. Transducer Troubleshooting — The electronic control uses 2 suction pressure transducers to measure the suction Table 71 — Cooling Service Analysis PROBLEM Compressor and Fan Will Not Start. CAUSE Power failure. Fuse blown or circuit breaker tripped. Check CB1, CB2, and CB3. Disconnect off. Compressor time guard to prevent short cycling. Thermostat or occupancy schedule set point not calling for Cooling. Outdoor temperature too low. REMEDY Call power company. Replace fuse or reset circuit breaker. Power disconnect. Check using ComfortLink™ scrolling marquee. Check using ComfortLink scrolling marquee. Check Compressor Lockout Temperature (MC.LO) using ComfortLink scrolling marquee. Active alarm. Check active alarms using ComfortLink scrolling marquee. Compressor Cycles (Other Than Insufficient line voltage. Determine cause and correct. Normally Satisfying Thermostat). Active alarm. Check active alarms using ComfortLink scrolling marquee. Compressors Operates Unit undersized for load. Decrease load or increase of size of unit. Continuously. Thermostat or occupancy schedule set point too low. Reset thermostat or schedule set point. Dirty air filters. Replace filters. Low refrigerant charge. Check pressure, locate leak, repair evacuate, and recharge. Condenser coil dirty or restricted. Clean coil or remove restriction. Excessive Head Pressures. Loose condenser thermistors. Tighten thermistors. Dirty condenser coil. Clean coil. Refrigerant overcharge. Recover excess refrigerant. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to suction line and insulate. 2. Replace TXV (and filter drier) if stuck open or closed. Condenser air restricted or air short cycling. Determine cause and correct. Restriction in liquid tube. Remove restriction. Condenser Fans Not Operating. No Power to contactors. Fuse blown or plug at motor loose. Excessive Suction Pressure. High heat load. Check for sources and eliminate Faulty TXV. 1. Check TXV bulb mounting and secure tightly to suction line and insulate. 2. Replace TXV (and filter drier) if stuck open or closed. Refrigerant overcharged. Recover excess refrigerant. Suction Pressure Too Low. Dirty air filters. Replace air filters. Low refrigerant charge. Check for leaks, repair, and recharge. Faulty TXV. 1. Check TXV bulb mounting and secure tightly to suction line and insulate. 2. Replace TXV (and filter drier) if stuck open or closed. Insufficient evaporator airflow. Check belt tension. Check for other restrictions. Temperature too low in conditioned area (low return- Reset thermostat or occupancy schedule. air temperature). LEGEND CB — Circuit Breaker TXV — Thermostatic Expansion Valve 86 Table 72 — Gas Heating Service Analysis PROBLEM Burners Will Not Ignite. CAUSE Active alarm. No power to unit. No power to IGC (Integrated Gas Control). Heaters off due to time guard to prevent short cycling. Thermostat or occupancy schedule set point not calling for Cooling. No gas at main burners. Inadequate Heating. Water in gas line. Dirty air filters. Gas input too low. Thermostat or occupancy schedule set point only calling for W1. Unit undersized for load. Restricted airflow. Too much outdoor air. Limit switch cycles main burners. Poor Flame Characteristics. Incomplete combustion (lack of combustion air) results in: Aldehyde odors, CO, sooting flame, or floating flame. Burners Will Not Turn Off. Unit is in Minimum on-time. Unit running in Service Test Mode. REMEDY Check active alarms using ComfortLink™ scrolling marquee. Check power supply, fuses, wiring, and circuit breakers. Check fuses and plugs. Check using ComfortLink scrolling marquee. Check using ComfortLink scrolling marquee. Check gas line for air and purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes before attempting to re-light unit. Drain water and install drip. Replace air filters. Check gas pressure at manifold. Refer to gas valve adjustment in Installation, Start-up, and Service Manual. Allow time for W2 to energize. Decrease load or increase of size of unit. Remove restriction. Check economizer position and configuration. Adjust minimum position using ComfortLink scrolling marquee. Check rotation of blower, thermostat heat anticipator settings, and temperature rise of unit. Adjust as needed. Check all screws around flue outlets and burner compartment. Tighten as necessary. Cracked heat exchanger, replace. Unit is over-fired, reduce input. Adjust gas line or manifold pressure. Check vent for restriction. Clean as necessary. Check orifice to burner alignment. Check using ComfortLink scrolling marquee. Check using ComfortLink scrolling marquee. Table 73 — Electric Heat Service Analysis PROBLEM No Heat. CAUSE Power failure. Fuse blown or circuit breaker tripped. Check CB1, CB2, and CB3. Thermostat occupancy schedule set point not calling for Heating. No 24 vac at primary contactor. No power (high voltage) to L2 of primary contactor. Bad electrical elements. 87 REMEDY Call power company. Replace fuse or reset circuit breaker. Check using ComfortLink scrolling marquee. Check transformer and circuit breaker. Check safety switches “one-shot” backup and auto limit. Power off unit and remove high voltage wires. Check resistance of heater, replace if open. Table 74 — 10K Thermistor vs Resistance (T55, T56, OAT, RAT, EDT, LAT Sensors) (F) TEMP (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 VOLTAGE DROP (V) 4.758 4.750 4.741 4.733 4.724 4.715 4.705 4.696 4.686 4.676 4.665 4.655 4.644 4.633 4.621 4.609 4.597 4.585 4.572 4.560 4.546 4.533 4.519 4.505 4.490 4.476 4.461 4.445 4.429 4.413 4.397 4.380 4.363 4.346 4.328 4.310 4.292 4.273 4.254 4.235 4.215 4.195 4.174 4.153 4.132 4.111 4.089 4.067 4.044 4.021 3.998 3.975 3.951 3.927 3.903 3.878 3.853 3.828 3.802 3.776 3.750 3.723 3.697 3.670 3.654 3.615 3.587 3.559 3.531 3.503 3.474 3.445 3.416 3.387 3.357 3.328 3.298 3.268 3.238 3.208 3.178 3.147 3.117 3.086 3.056 3.025 RESISTANCE (Ohms) 196,453 189,692 183,300 177,000 171,079 165,238 159,717 154,344 149,194 144,250 139,443 134,891 130,402 126,183 122,018 118,076 114,236 110,549 107,006 103,558 100,287 97,060 94,020 91,019 88,171 85,396 82,729 80,162 77,662 75,286 72,940 70,727 68,542 66,465 64,439 62,491 60,612 58,781 57,039 55,319 53,693 52,086 50,557 49,065 47,627 46,240 44,888 43,598 42,324 41,118 39,926 38,790 37,681 36,610 35,577 34,569 33,606 32,654 31,752 30,860 30,009 29,177 28,373 27,597 26,838 26,113 25,396 24,715 24,042 23,399 22,770 22,161 21,573 20,998 20,447 19,903 19,386 18,874 18,384 17,904 17,441 16,991 16,552 16,131 15,714 15,317 TEMP (F) 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 VOLTAGE DROP (V) 2.994 2.963 2.932 2.901 2.870 2.839 2.808 2.777 2.746 2.715 2.684 2.653 2.622 2.592 2.561 2.530 2.500 2.470 2.439 2.409 2.379 2.349 2.319 2.290 2.260 2.231 2.202 2.173 2.144 2.115 2.087 2.059 2.030 2.003 1.975 1.948 1.921 1.894 1.867 1.841 1.815 1.789 1.763 1.738 1.713 1.688 1.663 1.639 1.615 1.591 1.567 1.544 1.521 1.498 1.475 1.453 1.431 1.409 1.387 1.366 1.345 1.324 1.304 1.284 1.264 1.244 1.225 1.206 1.187 1.168 1.150 1.132 1.114 1.096 1.079 1.062 1.045 1.028 1.012 0.996 0.980 0.965 0.949 0.934 0.919 0.905 88 RESISTANCE (Ohms) 14,925 14,549 14,180 13,824 13,478 13,139 12,814 12,493 12,187 11,884 11,593 11,308 11,031 10,764 10,501 10,249 10,000 9,762 9,526 9,300 9,078 8,862 8,653 8,448 8,251 8,056 7,869 7,685 7,507 7,333 7,165 6,999 6,838 6,683 6,530 6,383 6,238 6,098 5,961 5,827 5,698 5,571 5,449 5,327 5,210 5,095 4,984 4,876 4,769 4,666 4,564 4,467 4,370 4,277 4.185 4,096 4,008 3,923 3,840 3,759 3,681 3,603 3,529 3,455 3,383 3,313 3,244 3,178 3,112 3,049 2,986 2,926 2,866 2,809 2,752 2,697 2,643 2,590 2,539 2,488 2,439 2,391 2,343 2,297 2,253 2,209 TEMP (F) 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 VOLTAGE DROP (V) 0.890 0.876 0.862 0.848 0.835 0.821 0.808 0.795 0.782 0.770 0.758 0.745 0.733 0.722 0.710 0.699 0.687 0.676 0.666 0.655 0.645 0.634 0.624 0.614 0.604 0.595 0.585 0.576 0.567 0.558 0.549 0.540 0.532 0.523 0.515 0.507 0.499 0.491 0.483 0.476 0.468 0.461 0.454 0.447 0.440 0.433 0.426 0.419 0.413 0.407 0.400 0.394 0.388 0.382 0.376 0.370 0.365 0.359 0.354 0.349 0.343 0.338 0.333 0.328 0.323 0.318 0.314 0.309 0.305 0.300 0.296 0.292 0.288 0.284 0.279 0.275 0.272 0.268 0.264 RESISTANCE (Ohms) 2,166 2,124 2,083 2,043 2,003 1,966 1,928 1,891 1,855 1,820 1,786 1,752 1,719 1,687 1,656 1,625 1,594 1,565 1,536 1,508 1,480 1,453 1,426 1,400 1,375 1,350 1,326 1,302 1,278 1,255 1,233 1,211 1,190 1,169 1,148 1,128 1,108 1,089 1,070 1,052 1,033 1,016 998 981 964 947 931 915 900 885 870 855 841 827 814 800 787 774 762 749 737 725 714 702 691 680 670 659 649 639 629 620 610 601 592 583 574 566 557 Table 75 — 10K Thermistor vs Resistance (T55, T56, OAT, RAT, EDT, LAT Sensor) (C) TEMP (C) –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 VOLTAGE DROP (V) 4.762 4.748 4.733 4.716 4.700 4.682 4.663 4.644 4.624 4.602 4.580 4.557 4.533 4.508 4.482 4.455 4.426 4.397 4.367 4.335 4.303 4.269 4.235 4.199 4.162 4.124 4.085 4.044 4.003 3.961 3.917 3.873 3.828 3.781 3.734 3.686 3.637 3.587 3,537 3.485 3.433 3.381 3.328 3.274 3.220 3.165 3.111 RESISTANCE (Ohms) 200,510 188,340 177,000 166,342 156,404 147,134 138,482 130,402 122,807 115,710 109,075 102,868 97,060 91,588 86,463 81,662 77,162 72,940 68,957 65,219 61,711 58,415 55,319 52,392 49,640 47,052 44,617 42,324 40,153 38,109 36,182 34,367 32,654 31,030 29,498 28,052 26,686 25,396 24,171 23,013 21,918 20,883 19,903 18,972 18,090 17,255 16,474 TEMP (C) 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 VOLTAGE DROP (V) 3.056 3.000 2.944 2.889 2.833 2.777 2.721 2.666 2.610 2.555 2.500 2.445 2.391 2.337 2.284 2.231 2.178 2.127 2.075 2.025 1.975 1.926 1.878 1.830 1.784 1.738 1.692 1.648 1.605 1.562 1.521 1.480 1.439 1.400 1.362 1.324 1.288 1.252 1.217 1.183 1.150 1.117 1.086 1.055 1.025 0.996 0.968 RESISTANCE (Ohms) 15,714 15,000 14,323 13,681 13,071 12,493 11,942 11,418 10,921 10,449 10,000 9,571 9,164 8,776 8,407 8,056 7,720 7,401 7,096 6,806 6,530 6,266 6,014 5,774 5,546 5,327 5,117 4,918 4,727 4,544 4,370 4,203 4,042 3,889 3,743 3,603 3,469 3,340 3,217 3,099 2,986 2,878 2,774 2,675 2,579 2,488 2,400 TEMP (C) 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 VOLTAGE DROP (V) 0.940 0.913 0.887 0.862 0.837 0.813 0.790 0.767 0.745 0.724 0.703 0.683 0.663 0.645 0.626 0.608 0.591 0.574 0.558 0.542 0.527 0.512 0.497 0.483 0.470 0.457 0.444 0.431 0.419 0.408 0.396 0.386 0.375 0.365 0.355 0.345 0.336 0.327 0.318 0.310 0.302 0.294 0.287 0.279 0.272 0.265 RESISTANCE (Ohms) 2,315 2,235 2,157 2,083 2,011 1,943 1,876 1,813 1,752 1,693 1,637 1,582 1,530 1,480 1,431 1,385 1,340 1,297 1,255 1,215 1,177 1,140 1,104 1,070 1,037 1,005 974 944 915 889 861 836 811 787 764 742 721 700 680 661 643 626 609 592 576 561 Table 76 — Suction Pressure Transducer Pressure (psig) vs Voltage (SSP-A, SSP-B) PRESSURE (PSIG) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 VOLTAGE DROP (V) 0.290 0.324 0.357 0.391 0.425 0.458 0.492 0.526 0.560 0.593 0.627 0.661 0.694 0.728 0.762 0.795 0.829 0.863 0.897 0.930 0.964 0.998 1.031 1.065 1.099 1.132 1.166 1.200 1.234 1.267 1.301 1.335 1.368 1.402 PRESSURE (PSIG) 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 VOLTAGE DROP (V) 1.436 1.470 1.503 1.537 1.571 1.604 1.638 1.672 1.705 1.739 1.773 1.807 1.840 1.874 1.908 1.941 1.975 2.009 2.042 2.076 2.110 2.144 2.177 2.211 2.245 2.278 2.312 2.346 2.380 2.413 2.447 2.481 2.514 2.548 PRESSURE (PSIG) 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 89 VOLTAGE DROP (V) 2.582 2.615 2.649 2.683 2.717 2.750 2.784 2.818 2.851 2.885 2.919 2.952 2.986 3.020 3.054 3.087 3.121 3.155 3.188 3.222 3.256 3.290 3.323 3.357 3.391 3.424 3.458 3.492 3.525 3.559 3.593 3.627 3.660 3.694 PRESSURE (PSIG) 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 VOLTAGE DROP (V) 3.728 3.761 3.795 3.829 3.862 3.896 3.930 3.964 3.997 4.031 4.065 4.098 4.132 4.166 4.200 4.233 4.267 4.301 4.334 4.368 4.402 4.435 4.469 4.503 4.537 4.570 4.604 4.638 4.671 4.705 4.739 4.772 4.806 4.840 Run Status Menu — The Run Status menu provides the user important information about the unit. The Run Status table can be used to troubleshoot problems and to help determine how and why the unit is operating. AUTO VIEW OF RUN STATUS — The Auto View of Run Status display table provides the most important unit information. The HVAC Mode (Run Status→VIEW→ HVAC) informs the user what HVAC mode the unit is currently in. Refer to the Modes section on page 40 for information on HVAC modes. The occupied status, unit temperatures, unit set points, and stage information can also be shown. See Table 78. Run Status→VIEW→HVAC — Displays the current HVAC Mode(s) by name. HVAC Modes include: Table 77 — Discharge Pressure Transducer Pressure (psig) vs Voltage PRESSURE VOLTAGE DROP (psig) (v) 0 0.466 10 0.564 20 0.663 30 0.761 40 0.860 50 0.958 60 1.056 70 1.155 80 1.253 90 1.352 100 1.450 110 1.549 120 1.647 130 1.745 140 1.844 150 1.942 160 2.041 170 2.139 180 2.238 190 2.336 200 2.434 210 2.533 220 2.631 230 2.730 240 2.828 250 2.927 260 3.025 270 3.124 280 3.222 290 3.320 300 3.419 310 3.517 320 3.616 330 3.714 340 3.813 350 3.911 360 4.009 370 4.108 380 4.206 390 4.305 400 4.403 410 4.502 420 4.600 OFF VENT HIGH HEAT STARTING UP HIGH COOL FIRE SHUT DOWN SHUTTING DOWN LOW COOL PRESSURIZATION DISABLED UNOCC FREE COOL EVACUATION SOFTSTOP REQUEST TEMPERING HICOOL SMOKE PURGE REM SW DISABLE TEMPERING LOCOOLDEHUMIDIFICATION COMP STUCK ON TEMPERING VENT RE-HEAT TEST LOW HEAT Run Status→VIEW→OCC — Displays the current occupancy status of the control. Run Status→VIEW→MAT — Displays the current value for mixed-air temperature. This value is calculated based on return-air and outside-air temperatures and economizer damper position. Run Status→VIEW→EDT — Displays the current evaporator discharge air temperature during Cooling modes. This value is read at the supply air thermistor location (or at cooling coil thermistor array if unit is equipped with hydronic heating coil). Run Status→VIEW→LAT — Displays the current leavingair temperature during Vent and Hydronic Heating modes. This value is read at the supply air thermistor location. Run Status→VIEW→EC.C.P — Displays the current economizer control point value (a target value for air temperature leaving the evaporator coil location). Run Status→VIEW→ECN.P — Displays the current actual economizer position (in percentage open). Run Status→VIEW→EC2.P — Displays the current position of actuator no. 2 (in percentage open). Run Status→VIEW→CL.C.P — Displays the current cooling control point (a target value for air temperature leaving the evaporator coil location). Run Status→VIEW→C.CAP — Displays the current amount of unit cooling capacity (in percent of maximum). Compare to staging tables in Appendix C. Run Status→VIEW→CL.ST — Displays the current number of requested cooling stages. Compare to staging tables in Appendix C and to C.CAP above. Run Status→VIEW→HT.C.P — Displays the current heating control point, for use with staged gas control option only (a target value for air temperature leaving the supply duct). Run Status→VIEW→HT.ST — Displays the current number of heating stages active (for staged gas control option only). Compare to following point. Run Status→VIEW→H.MAX — Displays the maximum number of heat stages available for this model. Forcing Inputs and Outputs — Many of variables may be forced both from the CCN and directly at the local display. This can be useful during diagnostic testing and also during operation, typically as part of an advanced third party control scheme. Please see Appendix A and B. NOTE: In the case of a power reset, any force levels in effect at the time of the power reset will be cleared. CONTROL LEVEL FORCING — If any of the following points are forced with a priority level of 7 (consult CCN literature for a description of priority levels), the software clears the force from the point if it has not been written to or forced again within the timeout periods defined below: Temperatures→AIR.T→OAT Temperatures→AIR.T→RAT Temperatures→AIR.T→SPT Inputs→RSET→SP.RS Inputs→REL.H→OA.RH Inputs→AIR.Q→OAQ Outside Air Temperature Return Air Temperature Space Temperature Static Pressure Reset Outside Air Relative Humidity Outside Air Quality 30 minutes 3 minutes 3 minutes 30 minutes 30 minutes 30 minutes 90 IDM — IGC — LEGEND Induced-Draft Motor Integrated Gas Unit Controller NOTE: Thermostat Fan Switch in the “AUTO” position. Fig. 13 — IGC Service Analysis Logic 91 Table 78 — Auto View of Run Status Display Table ITEM VIEW →HVAC →OCC →MAT →EDT →LAT →EC.C.P →ECN.P →EC2.P →CL.C.P →C.CAP →CL.ST →HT.C.P →HT.ST →H.MAX EXPANSION AUTO VIEW OF RUN STATUS ascii string spelling out the hvac modes Occupied ? Mixed Air Temperature Evaporator Discharge Tmp Leaving Air Temperature Economizer Control Point Economizer Act.Curr.Pos. Economzr2 Act.Curr.Pos. Cooling Control Point Current Running Capacity Requested Cool Stage Heating Control Point Requested Heat Stage Maximum Heat Stages RANGE UNITS YES/NO 0-100 0-100 dF dF dF dF % % dF dF POINT string OCCUPIED MAT EDT LAT ECONCPNT ECONOPOS ECON2POS COOLCPNT CAPTOTAL CL_STAGE HEATCPNT HT_STAGE HTMAXSTG WRITE STATUS forcible R.PCT = (MAT – EDT)/C.CAP Cap Deadband Subtracting (Y.MIN) — This is a control variable used for Low Temp Override (L.TMP) and Slow Change Override (SLOW). Y.MIN = –SUB.R*0.4375 Cap Deadband Adding (Y.PLU) — This is a control variable used for High Temp Override (H.TMP) and Slow Change Override (SLOW). Y.PLU = –ADD.R*0.4375 Cap Threshold Subtracting (Z.MIN) — This parameter is used in the calculation of SMZ and is calculated as follows: Z.MIN = Configuration→COOL→Z.GN * (–10 + (4* (–SUB.R))) * 0.6 Cap Threshold Adding (Z.PLU) — This parameter is used in the calculation of SMZ and is calculated as follows: Z.PLU = Configuration→COOL→Z.GN * (10 + (4* (–ADD.R))) * 0.6 High Temp Cap Override (H.TMP) — If stages of mechanical cooling are on and the error is greater than twice Y.PLU, and the rate of change of error is greater than 0.5° F, then a stage of mechanical cooling will be added every 30 seconds. This override is intended to react to situations where the load rapidly increases. Low Temp Cap Override (L.TMP) — If the error is less than twice Y.MIN, and the rate of change of error is less than –0.5° F, then a mechanical stage will be removed every 30 seconds. This override is intended to quickly react to situations where the load is rapidly reduced. Pull Down Cap Override (PULL) — If the error from set point is above 4° F, and the rate of change is less than –1° F per minute, then pulldown is in effect, and “SUM” is set to 0. This keeps mechanical cooling stages from being added when the error is very large, but there is no load in the space. Pulldown for units is expected to rarely occur, but is included for the rare situation when it is needed. Most likely pulldown will occur when mechanical cooling first becomes available shortly after the control goes into an occupied mode (after a warm unoccupied mode). Slow Change Cap Override (SLOW) — With a rooftop unit, the design rise at 100% total unit capacity is generally around 30° F. For a unit with 4 stages, each stage represents about 7.5° F of change to EDT. If stages could reliably be cycled at very fast rates, the set point could be maintained very precisely. Since it is not desirable to cycle compressors more than 6 cycles per hour, slow change override takes care of keeping the PID under control when “relatively” close to set point. MODE TRIP HELPER — The Mode Trip Helper table provides information on the unit modes and when the modes start and stop. See Table 81. This information can be used to help determine why the unit is in the current mode. ECONOMIZER RUN STATUS — The Economizer Run Status display table provides information about the economizer and can be used to troubleshoot economizer problems. See Table 79. The current position, commanded position, and whether the economizer is active can be displayed. All the disabling conditions for the economizer and outside air information is also displayed. COOLING INFORMATION — The Cooling Information run status display table provides information on the cooling operation of the unit. See Table 80. Current Running Capacity (C.CAP) — This variable represents the amount of capacity currently running as a percent. Current Cool Stage (CUR.S) — This variable represents the cool stage currently running. Requested Cool Stage (REQ.S) — This variable represents the requested cool stage. Cooling relay timeguards in place may prevent the requested cool stage from matching the current cool stage. Maximum Cool Stages (MAX.S) — This variable is the maximum number of cooling stages the control is configured for and capable of controlling. Active Demand Limit (DEM.L) — If demand limit is active, this variable will represent the amount of capacity that the control is currently limited to. Capacity Load Factor (SMZ) — This factor builds up or down over time (–100 to +100) and is used as the means of adding or subtracting a cooling stage during run time. It is a normalized representation of the relationship between “Sum” and “Z”. See the SUMZ Cooling Algorithm section on page 50. Next Stage EDT Decrease (ADD.R) — This variable represents (if adding a stage of cooling) how much the temperature should drop in degrees depending on the R.PCT calculation and how much additional capacity is to be added. ADD.R = R.PCT * (C.CAP – capacity after adding a cooling stage) For example: If R.PCT = 0.2 and the control would be adding 20% cooling capacity by taking the next step up, 0.2 times 20 = 4 F ADD.R Next Stage EDT Increase (SUB.R) — This variable represents (if subtracting a stage of cooling) how much the temperature should rise in degrees depending on the R.PCT calculation and how much capacity is to be subtracted. SUB.R = R.PCT * (C.CAP – capacity after subtracting a cooling stage) For Example: If R.PCT = 0.2 and the control would be subtracting 30% capacity by taking the next step down, 0.2 times –30 = –6 F SUB.R. Rise Per Percent Capacity (R.PCT) — This is a real time calculation that represents the amount of degrees of drop/rise across the evaporator coil versus percent of current running capacity. 92 Table 79 — Economizer Run Status Display Table ITEM ECON →ECN.P →EC2.P →ECN.C →ACTV →DISA →DISA→UNV.1 →DISA→UNV.2 →DISA→ENTH →DISA→DBC →DISA→DEW →DISA→DDBC →DISA→OAEC →DISA→DEC →DISA→EDT →DISA→OAT →DISA→FORC →DISA→SFON →DISA→CLOF →DISA→OAQL →DISA→HELD →DISA→DH.DS →O.AIR →O.AIR→OAT →O.AIR→OA.RH →O.AIR→OA.E →O.AIR→OA.D.T EXPANSION ECONOMIZER RUN STATUS Economizer Act.Curr.Pos. Economzr2 Act.Curr.Pos. Economizer Act.Cmd.Pos. Economizer Active ? ECON DISABLING CONDITIONS Econ Act. Unavailable? Econ2 Act. Unavailable? Enth. Switch Read High ? DBC - OAT Lockout? DEW - OA Dewpt.Lockout? DDBD- OAT > RAT Lockout? OAEC- OA Enth Lockout? DEC - Diff.Enth.Lockout? EDT Sensor Bad? OAT Sensor Bad ? Economizer Forced ? Supply Fan Not On 30s ? Cool Mode Not In Effect? OAQ Lockout in Effect ? Econ Recovery Hold Off? Dehumid. Disabled Econ.? OUTSIDE AIR INFORMATION Outside Air Temperature Outside Air Rel. Humidity Outside Air Enthalpy OutsideAir Dewpoint Temp RANGE 0-100 0-100 0-100 YES/NO UNITS % % % POINT ECONOPOS ECON2POS ECONOCMD ECACTIVE YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO WRITE STATUS forcible ECONUNAV ECN2UNAV ENTH DBC_STAT DEW_STAT DDBCSTAT OAECSTAT DEC_STAT EDT_STAT OAT_STAT ECONFORC SFONSTAT COOL_OFF OAQLOCKD ECONHELD DHDISABL dF % OAT OARH OAE OADEWTMP dF forcible forcible Table 80 — Cooling Information Display Table ITEM COOL →C.CAP →CUR.S →REQ.S →MAX.S →DEM.L →SUMZ →SUMZ→SMZ →SUMZ→ADD.R →SUMZ→SUB.R →SUMZ→R.PCT →SUMZ→Y.MIN →SUMZ→Y.PLU →SUMZ→Z.MIN →SUMZ→Z.PLU →SUMZ→H.TMP →SUMZ→L.TMP →SUMZ→PULL →SUMZ→SLOW EXPANSION COOLING INFORMATION Current Running Capacity Current Cool Stage Requested Cool Stage Maximum Cool Stages Active Demand Limit COOL CAP. STAGE CONTROL Capacity Load Factor Next Stage EDT Decrease Next Stage EDT Increase Rise Per Percent Capacity Cap Deadband Subtracting Cap Deadband Adding Cap Threshold Subtracting Cap Threshold Adding High Temp Cap Override Low Temp Cap Override Pull Down Cap Override Slow Change Cap Override RANGE UNITS % CAPTOTAL COOL_STG CL_STAGE CLMAXSTG DEM_LIM % -100 → +100 POINT WRITE STATUS forcible SMZ ADDRISE SUBRISE RISE_PCT Y_MINUS Y_PLUS Z_MINUS Z_PLUS HI_TEMP LOW_TEMP PULLDOWN SLO_CHNG ^F ^F Table 81 — Mode Trip Helper Display Table ITEM TRIP →UN.C.S →UN.C.E →OC.C.S →OC.C.E →TEMP →OC.H.E →OC.H.S →UN.H.E →UN.H.S →HVAC EXPANSION MODE TRIP HELPER Unoccup. Cool Mode Start Unoccup. Cool Mode End Occupied Cool Mode Start Occupied Cool Mode End Ctl.Temp RAT,SPT or Zone Occupied Heat Mode End Occupied Heat Mode Start Unoccup. Heat Mode End Unoccup. Heat Mode Start ascii string spelling out the hvac modes RANGE UNITS POINT WRITE STATUS UCCLSTRT UCCL_END OCCLSTRT OCCL_END CTRLTEMP OCHT_END OCHTSTRT UCHT_END UCHTSTRT string COMPRESSOR STARTS DISPLAY TABLE — The Compressor Starts Display Table displays the number of starts for each compressor. See Table 84. SOFTWARE VERSION NUMBERS DISPLAY TABLE — The Software Version Numbers Display Table displays the software version numbers of the unit boards and devices. See Table 85. CCN/LINKAGE DISPLAY TABLE — The CCN/Linkage display table provides information on unit linkage. See Table 82. COMPRESSOR RUN HOURS DISPLAY TABLE — The Compressor Run Hours Display Table displays the number of run time hours for each compressor. See Table 83. 93 Table 82 — CCN/Linkage Display Table ITEM LINK →MODE →L.Z.T →L.C.SP →L.H.SP EXPANSION CCN - LINKAGE Linkage Active - CCN Linkage Zone Control Tmp Linkage Curr. Cool Setpt Linkage Curr. Heat Setpt RANGE UNITS POINT ON/OFF WRITE STATUS MODELINK LZT LCSP LHSP dF dF dF Table 83 — Compressor Run Hours Display Table ITEM HRS →HR.A1 →HR.A2 →HR.B1 →HR.B2 EXPANSION COMPRESSOR RUN HOURS Compressor A1 Run Hours Compressor A2 Run Hours Compressor B1 Run Hours Compressor B2 Run Hours RANGE 0-999999 0-999999 0-999999 0-999999 UNITS POINT HRS HRS HRS HRS HOURS_A1 HOURS_A2 HOURS_B1 HOURS_B2 WRITE STATUS config config config config Table 84 — Compressor Starts Display Table ITEM STRT →ST.A1 →ST.A2 →ST.B1 →ST.B2 EXPANSION COMPRESSOR STARTS Compressor A1 Starts Compressor A2 Starts Compressor B1 Starts Compressor B2 Starts RANGE 0-999999 0-999999 0-999999 0-999999 UNITS POINT CY_A1 CY_A2 CY_B1 CY_B2 WRITE STATUS config config config config Table 85 — Software Version Numbers Display Table ITEM VERS →MBB →RCB →ECB →SCB →CEM →ECON →IGV →HUMD →HEAT →BP1 →BP2 →MARQ →NAVI EXPANSION SOFTWARE VERSION NUMBERS CESR131292-xx-xx CESR131249-xx-xx CESR131249-xx-xx CESR131226-xx-xx CESR131174-xx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx CESR131171-xx-xx CESR130227-xx-xx RANGE UNITS POINT WRITE STATUS string string string string string string string string string string string string string In addition, the compressors have several diagnostics monitoring the safety of the system which may cause a number of attempts to be re-tried before locking out the system from operation. This feature reduces the likelihood of false alarms causing a properly working system to be shutdown incorrectly. For the compressor and circuit diagnostics, some of these alerts/alarms will not broadcast an initial failure to the CCN network until all attempts to recover have occurred and failed. These alerts will be accessible in the alarm history of the control (Alarms→HIST). All the alarms and alerts are summarized in Table 86. Alarms and Alerts — There are a variety of different alerts and alarms in the system. T — Alert: Part of the unit is down, but the unit is still partially able to provide cooling or heating. A — Alarm: The unit is down and is unable to provide cooling or heating. All alarms are displayed with a code of AXXX or TXXX where XXX is the alarm/alert number. All alerts start with “T” and all alarms start with “A”. The response of the control system to various alerts and alarms depends on the seriousness of the particular alert or alarm. In the mildest case, an alert does not affect the operation of the unit in any manner. 94 95 ALARM OR ALERT NUMBER T051 A051 T052 A052 T055 A055 T056 A056 T057 T058 T072 T073 T074 T075 T076 T077 T078 T082 T090 T091 T092 T093 T094 T095 T130 T131 T132 T133 T134 T135 T136 T137 T138 T139 T140 T141 A150 A152 T153 A154 T155 A156 A157 A171 T172 A173 A174 T177 T178 A200 T210 T211 T220 T221 T229 T245 T246 T247 T300 T301 T302 T303 T304 T305 T308 T309 DESCRIPTION Circuit A, Compressor 1 Failure Circuit A, Compressor 1 Stuck On Failure Circuit A, Compressor 2 Failure Circuit A, Compressor 2 Stuck On Failure Circuit B, Compressor 1 Failure Circuit B, Compressor 1 Stuck On Failure Circuit B, Compressor 2 Failure Circuit B, Compressor 2 Stuck On Failure Circuit A, High Pressure Switch Failure Circuit B, High Pressure Switch Failure Evap. Discharge Reset Sensor Failure Outside Air Temperature Thermistor Failure Space Temperature Thermistor Failure Return Air Thermistor Failure Outside Air Relative Humidity Sensor Fail Space Relative Humidity Sensor Failure Return Air Relative Humidity Sensor Fail Space Temperature Offset Sensor Failure Circ A Discharge Press Transducer Failure Circ B Discharge Press Transducer Failure Circ A Suction Press Transducer Failure Circ B Suction Press Transducer Failure Circ A Discharge Press exceeded 440 psig Circ B Discharge Press exceeded 440 psig Low Suction Pressure Circuit A Low Suction Pressure Circuit B High Suction Pressure Circuit A High Suction Pressure Circuit B High Discharge Pressure Circuit A High Discharge Pressure Circuit B Compressor A1 low differential pressure Compressor A2 low differential pressure Compressor B1 low differential pressure Compressor B2 low differential pressure Circ A Max Diff Operating Press Exceeded Circ B Max Diff Operating Press Exceeded Unit is in Emergency Stop Unit Down due to Failure Real Time Clock Hardware Failure Serial EEPROM Hardware Failure Serial EEPROM Storage Failure Error Critical Serial EEPROM Storage Fail Error A/D Hardware Failure Staged Gas Control Board Comm Failure Control Expansion Module Comm Failure RCB board Communication Failure ECB board Communication Failure 4-20 mA Demand Limit Failure 4-20 mA Static Pressure Reset Fail Linkage Timeout Error - Comm Failure Building Pressure Transducer Failure Static Pressure Transducer Failure Indoor Air Quality Sensor Failure Outdoor Air Quality Sensor Failure Economizer Min Pos Override Input Failure Outside Air Cfm Sensor Failure Supply Air Cfm Sensor Failure Return Air Cfm Sensor Failure Space Temperature Below Limit Space Temperature Above Limit Supply Temperature Below Limit Supply Temperature Above Limit Return Temperature Below Limit Return Temperature Above Limit Return Air Relative Humidity Below Limit Return Air Relative Humidity Above Limit Compressor locked off (after 3 strikes) Compressor locked off Compressor locked off (after 3 strikes) Compressor locked off Compressor locked off (after 3 strikes) Compressor locked off Compressor locked off (after 3 strikes) Compressor locked off Compressor locked off Compressor locked off No supply air reset applied No OAT functions allowed No SPT functions allowed No RAT functions allowed No outside air RH functions allowed No space RH functions allowed No return air RH functions allowed No space temperature offset applied Circuit shut down Circuit shut down Circuit shut down Circuit shut down Circuit shut down Circuit shut down Circuit staged down Circuit staged down Circuit shut down Circuit shut down Circuit staged down Circuit staged down Circuit shut down Circuit shut down Circuit shut down Circuit shut down Circuit shut down Circuit shut down Unit shut down No mechanical cooling available Unit shut down Unit shut down Alert only Unit shut down Unit shut down Staged gas control disabled All CEM board functions disabled Unit shut down Unit shut down No demand limiting No static pressure reset Resorts to local unit setpoints No building pressure control function No static pressure control No IAQ control OAQ defaults to 400 ppm Operate without override No OA CFM control Unit shut down Unit shut down Alert only Alert only Alert only Alert only Alert only Alert only Alert only Alert only ACTION TAKEN BY CONTROL Table 86 — Alert and Alarm Codes RESET METHOD Automatic then manual after 3 strikes Manual Automatic then manual after 3 strikes Manual Automatic then manual after 3 strikes Manual Automatic then manual after 3 strikes Manual Automatic then manual Automatic then manual Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Manual Manual Automatic then manual after 3 strikes Automatic then manual after 3 strikes Automatic then manual after 3 strikes Automatic then manual after 3 strikes Automatic then manual after 3 strikes Automatic then manual after 3 strikes Manual Manual Manual Manual Manual Manual Manual Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic 96 ALARM OR ALERT NUMBER T310 T311 T312 T313 T314 T316 T317 A400 A404 A405 A406 A407 T408 T409 A409 T421 T422 T423 T424 T430 A430 T500 T501 T502 T503 T610 T611 T612 T613 T614 A620 A621 T622 A623 A624 T630 T631 T632 T633 T634 A640 A641 T642 A643 A644 A650 A651 T652 A653 A654 A660 A661 T662 A663 A664 T670 T671 T672 T673 T674 A700 T701 T702 T703 A704 T705 A706 DESCRIPTION Supply Duct Static Pressure Below Limit Supply Duct Static Pressure Above Limit Building Static Pressure Below Limit Building Static Pressure Above Limit IAQ Above Limit OAT Below Limit OAT Above Limit Hydronic Freeze Stat Trip Fire Shut Down Emergency Mode (fire-smoke) Evacuation Emergency Mode Pressurization Emergency Mode Smoke Purge Emergency Mode Dirty Air Filter Supply Fan Status Failure Supply Fan Status Failure Thermostat Y2 Input On without Y1 On Thermostat W2 Input On without W1 On Thermostat Y and W Inputs On Thermostat G Input Off On a Cooling Call Plenum Pressure Safety Switch Trip Plenum Pressure Safety Switch Trip Current Sensor Board Failure - A1 Current Sensor Board Failure - A2 Current Sensor Board Failure - B1 Current Sensor Board Failure - B2 Economizer Actuator Out of Calibration Economizer Actuator Comm Failure Economizer Actuator Control Range Increased Econ Actuator Overload, Setpt Not Reached Econ Actuator Comm Fail, Daughter Brd-MFT IGV Actuator Out of Calibration IGV Actuator Communication Failure IGV Actuator Control Range Increased IGV Actuator Overload, Setpnt Not Reached IGV Actuator Comm Fail, Daughter Board-MFT Humidifier Actuator Out of Calibration Humidifier Actuator Communication Failure Humidifier Actuator Control Range Increased Humidifier Act Overload, Setpt Not Reached Humidifier Act Comm Fail, Daughter Brd-MFT Heating Coil Actuator Out of Calibration Heating Coil Actuator Comm Fail Heat Coil Actuator Control Range Increased Ht Coil Act Ovrload, Setpt Pos Not Reached Heat Coil Act Com Fail, Daughter Board-MFT Bldg.Press. Actuator 1 Out of Calibration Bldg.Press. Actuator 1 Comm Failure Bldg.Press. Act. 1 Control Range Increased BP Act. 1 Overload, Setpnt Pos Not Reached BP Actuator 1 Com Fail, Daughter Board-MFT Bldg.Press. Actuator 2 Out of Calibration Bldg.Press. Actuator 2 Comm Failure Bldg.Press. Act. 2 Control Range Increased BP Act. 2 Overload, Setpnt Pos Not Reached BP Actuator 2 Com Fail, Daughter Board-MFT Economizer 2 Actuator Out of Calibration Economizer 2 Actuator Comm Failure Economizer 2 Actuator Control Range Increased Econ2 Overload, Setpt Not Reached Econ2 Actuator Comm Fail, Daughter Brd-MFT Air Temp Lvg Supply Fan Thermistor Failure Staged Gas 1 Thermistor Failure Staged Gas 2 Thermistor Failure Staged Gas 3 Thermistor Failure Staged Gas Lvg Air Temp Sum Total Failure Limit Switch Thermistor Failure Hydronic Evap Discharge Thermistor Failure Alert only Alert only Alert only Alert only Alert only Alert only Alert only Unit in emergency mode Unit shut down Run evacuation mode Run pressurization mode Run smoke purge mode Alert only Alert only Unit shut down Run on Y2 Run on W2 No cooling or heating Turn fan on and cool Alert only Unit shut down Alert only Alert only Alert only Alert only Alert only No economizer functions Alert only Alert only No economizer functions Alarm only No IGV functions Alert only Alarm only No IGV functions Alert only No humidifer functions Alert only Alert only No humidifer functions Alarm only No heating coil functions Alert only Alarm only No heating coil functions Alarm only No building pressure control Alert only Alarm only No building pressure control Alarm only No building pressure control Alert only Alarm only No building pressure control Alert only No economizer functions Alert only Alert only No economizer functions Unit shut down Average remaning sensors Average remaning sensors Average remaning sensors No staged gas function No software limit switch function Unit shut down ACTION TAKEN BY CONTROL Table 86 — Alert and Alarm Codes (cont) Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Manual Manual Automatic Automatic Automatic Automatic Automatic Manual Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic RESET METHOD seconds, an alarm is generated. These alarms are only monitored for a period of 10 seconds after the compressor relay has been commanded OFF. This is done to facilitate a service technician forcing a relay to test a compressor. In addition, if a compressor stuck failure occurs and the current sensor board reports the compressor and the request off, certain diagnostics will take place. 1. As A1 and B1 both have 1 unloader, the control will energize the particular unloader for these compressors if the failure occurs. 2. If any of the 4 compressors are diagnosed as stuck on and the current sensor board is on and the request is off, the control will request the supply fan which will automatically start building air flow control. 3. Heating will be disabled while any one of the compressors has this problem. The reset method will be manual for these alarms. The possible causes are: • Welded contact on compressor relay or contactor. • Frozen compressor relay on MBB. To check out alerts A051, A052, A055, A056: 1. Place the unit in Service Test mode. All compressors should be Off. 2. Verify that there is not 24v at the contactor coil. If there is 24v at the contactor, check relay on MBB and wiring. 3. Check for welded contactor. 4. Verify CSB wiring. 5. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working and condenser fans are energized after compressor starts. T057 (Circuit A, High Pressure Switch Failure) T058 (Circuit B, High Pressure Switch Failure) — These alerts occur on all units except the 48/50Z105 units (current sensor board units). If the high-pressure switch trips on a circuit with compressors commanded on, the discharge pressure is sampled. If the discharge pressure is between 368 and 418 psig, then the discharge pressure trip point (Configuration→Cool→HPS.A, HPS.B) is adjusted to the previously sampled trip point minus 3 psig. This is done to make a rough calibration of the high pressure trip point which is used by the high discharge pressure diagnostics. When the trip happens, all mechanical cooling on the circuit is shut down for 15 minutes. After 15 minutes, the circuit will be allowed to come back on. An internal flag is set which needs to sense the lead compressor on a circuit go from on to off, indicating the circuit came back on after the 15-minute delay and successfully completed a cooling cycle. If the high-pressure switch trips again, the high pressure alarm occurs which will then require a manual reset of the unit. T072 (Evaporator Discharge Reset Sensor Failure) — This sensor is responsible for third party reset of the cooling supply air set point. If the unit is configured for “third party reset” (Configuration→EDT.R→RS.CF=3) and this alert occurs, no reset will be applied to the cooling supply air set point. Recovery from this alert is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM board. DIAGNOSTIC ALARM CODES AND POSSIBLE CAUSES T051 (Circuit A, Compressor 1 Failure) T052 (Circuit A, Compressor 2 Failure) T055 (Circuit B, Compressor 1 Failure) T056 (Circuit B, Compressor 2 Failure) NOTE: These alerts only occur on units with a current sensor board (CSB) (48/50Z105 only). If the current sensor board reads OFF while the compressor relay has been commanded ON for a period of 4 continuous seconds, an alert is generated. Any time this alert occurs, a strike will be called out on the affected compressor. If three successive strikes occur the compressor will be locked out requiring a manual reset or power reset of the circuit board. The clearing of strikes during compressor operation is a combination of 3 complete cycles or 15 continuous minutes of run time operation. So, if there are one or two strikes on the compressor and three short cycles (ONOFF,ON-OFF, ON-OFF) occur in less than 15 minutes, the strikes will be reset to zero for the affected compressor. Also, if the compressor turns on and runs for 15 minutes straight with no compressor failure, the compressor's strikes are cleared as well. NOTE: Until the compressor is locked out, for the first two strikes, the alert will not be broadcast to the network, nor will the alarm relay be closed. The possible causes are: • High-pressure switch (HPS) open. The high-pressure switch is wired in series with the compressor relays off of the MBB. If the high-pressure switch opens while the MBB is commanding the compressor on, the compressor stops and the CSB no longer detects current, causing the control to activate the alert. • Circuit breaker trip. • Wiring error. To check out alerts T051, T052, T055, T056: 1. Turn on the compressor in question using Service Test mode. If the compressor does not start, then most likely the problem is one of the following: HPS open, circuit breaker trip, incorrect safety wiring, or incorrect compressor wiring. 2. If the compressor starts, verify that the indoor and outdoor fans are operating properly. 3. If the CSB is always detecting current, then verify that the compressor is on. If the compressor is on, check the contactor and the relay on the MBB. If the compressor is off and there is no current, verify CSB wiring and replace if necessary. 4. Return to Normal mode and observe compressor operation to verify that compressor current sensor is working and condenser fans are energized after compressor starts. A051 (Circuit A, Compressor 1 Stuck On Failure) A052 (Circuit A, Compressor 2 Stuck On Failure) A055 (Circuit B, Compressor 1 Stuck On Failure) A056 (Circuit B, Compressor 2 Stuck On Failure) NOTE: These alarms only occur on units with a current sensor board (CSB) (48/50Z105 only). If the current sensor board reads ON while the compressor relay has been commanded OFF for a period of 4 continuous 97 T094 (Circ A Discharge Press exceeded 440 psig) T095 (Circ B Discharge Press exceeded 440 psig) — Should the discharge pressure read by a discharge pressure transducer exceed 440 psig for any reason, the circuit will be stopped which requires a manual reset for recovery. The unit highpressure switch should trip before the discharge pressure reaches this value. Check for failed a high-pressure switch or a discharge pressure transducer out of calibration. T130 (Low Suction Pressure Circuit A) T131 (Low Suction Pressure Circuit B) — If a circuit is equipped with unloaders and the suction pressure drops below 48 psig for 15 seconds, then that circuit is staged down until either the pressure remains above 48 psig or the compressor is staged off naturally, due to lessening demand. Each subsequent circuit stage will then be turned off every 15 seconds. There will be a start-up delay if the outside-air temperature is too low. When the outdoor ambient is below 60 F, during initial start-up, suction pressure is ignored for a period of 5 minutes. The alarm and recovery of the low pressure condition will follow the basic three strike methodology. If a low suction pressure condition is detected while the circuit is ON and action has been taken to lower capacity, a “strike” is called out (only if the circuit is staged off in this condition). If less than three strikes have occurred, the alarm will show up in alarm history and locally at the display, but will not be broadcast (just as in the high discharge pressure condition). To recover (if the alarm is not manual), both a 10-minute timer must expire and the suction pressure must recover above 54 psig. If recovery occurs, staging will be allowed on the circuit once again. A strike is tied to the circuit going off entirely, not reducing capacity and recovering. Therefore it is possible that multiple alerts may be stored but not broadcast in this condition. If all compressors in the circuit go down twice due to low suction pressure, the next low suction pressure condition is a manual alarm and the circuit is locked out and the alarm broadcast to the network. If the circuit operates with capacity for 15 continuous minutes and the low discharge pressure alarm condition is not manual, all strikes will be cleared. T132 (High Suction Pressure Circuit A) T133 (High Suction Pressure Circuit B) — During operation, the suction pressure cannot exceed 100 psig (60 F saturated). If after 5 minutes of operation, suction pressure exceeds this value, then all compressors in that circuit are stopped and the alarm is tripped. Reset method is automatic after time guards have expired. The three strike rule applies which means the third time is a manual reset and CCN broadcast for the alert/alarm. T134 (High Discharge Pressure Circuit A) T135 (High Discharge Pressure Circuit B) — There is a configuration for each circuit which monitors high discharge pressure (Configuration→Cool→HPS.A, HPS.B). This configuration is adjusted to compensate for calibration whenever a high pressure switch fault occurs. If discharge pressure rises above this trip point, the individual circuit starts staging down 1 stage every 5 seconds. To recover, both a 10-minute timer must expire and the discharge pressure must fall 25 psig below the trip point. If the circuit recovers, the circuit will stage back up (if the alarm is not manual), allowing one stage every 5 seconds. The timer starts 10 minutes since the last circuit stage was decreased. The alarming and recovery of the high discharge pressure condition will follow the basic three strike methodology. A strike is tied to the circuit going off entirely, not reducing capacity and recovering. Therefore it is possible, multiple alerts may be stored but not broadcast in this condition. If the circuit operates with capacity for 15 continuous minutes and the high discharge pressure alarm condition is not manual, all strikes will be cleared. T073 (Outside Air Temperature Thermistor Failure) — Failure of this thermistor (Temperatures→AIR.T→OAT) will disable any elements of the control which requires its use. Economizer control beyond the vent position and the calculation of mixed air temperature for the SumZ algorithm will not be possible. Recovery from this alert is automatic. Reason for error is either a faulty thermistor, wiring error, or damaged input on the MBB control board. T074 (Space Temperature Thermistor Failure) — Failure of this thermistor (Temperatures→AIR.T→SPT) will disable any elements of the control which requires its use. If the unit is configured for SPT 2 stage or SPT multi-stage operation and the sensor fails, no cooling or heating mode may be chosen. Recovery from this alert is automatic. Reason for error is either a faulty thermistor in the T55, T56 or T58 device, wiring error, or damaged input on the MBB control board. T075 (Return Air Thermistor Failure) — Failure of this thermistor (Temperatures→AIR.T→RAT) will disable any elements of the control which requires its use. Elements of failure include: • the calculation of mixed air temperature for sumZ control • the selection of a mode for VAV units • economizer differential enthalpy or dry bulb control • RAT offset control for dehumidification • return air temperature supply air reset • fan tracking for building pressure control. Recovery from this alert is automatic. Reason for error is either a faulty thermistor, wiring error, or damaged input on the MBB control board. T076 (Outside Air Relative Humidity Sensor Failure) — Failure of this sensor (Inputs→REL.H→OA.RH) will disable any elements of the control which requires its use. Elements of failure include: economizer outdoor and differential enthalpy control. Recovery from this alert shall be automatic. Reason for error is either a faulty sensor, wiring error or damaged input on the CEM control board. T077 (Space Relative Humidity Sensor Failure) — Failure of this sensor (Inputs→REL.H→SP.RH) will disable any elements of the control which requires its use. Elements of failure include humidification and dehumidification. Recovery from this alert is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. T078 (Return Air Relative Humidity Sensor Fail) — Failure of this sensor (Inputs→REL.H→RA.RH) will disable any elements of the control which requires its use. Elements of failure include economizer differential enthalpy control, humidification, and dehumidification. Recovery from this alert is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. T082 (Space Temperature Offset Sensor Failure) — When this failure occurs, there is no offset available that may be applied to space temperature. Recovery from this alert is automatic. Reason for error is either a faulty slider potentiometer, wiring error, or damaged input on the MBB control board. T090 (Circ A Discharge Press Transducer Failure) T091 (Circ B Discharge Press Transducer Failure) — The associated circuit becomes disabled whenever this transducer (Pressures→REF.P→DP.A, DP.B) fails. Recovery from this alert is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the MBB control board. T092 (Circ A Suction Press Transducer Failure) T093 (Circ B Suction Press Transducer Failure) — The associated circuit becomes disabled whenever this transducer (Pressures→REF.P→SP.A, SP.B) fails. Recovery from this alert is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the MBB control board. 98 to the staged gas control board, or damage to the RS-485 drivers on the LEN bus. T172 (Control Expansion Module Comm Failure) — Any function associated with a sensor configured for use that resides on the controls expansion module will be disabled until communication is re-established. Recovery is automatic. Reason for failure may be due to incorrect wiring, power loss to the control expansion module, or damage to the RS-485 drivers on the LEN bus. A173 (RCB Board Communication Failure) — As the RCB board is integral to all Z series units, the error will cause a system shutdown until communication is re-established. Recovery is automatic. Reason for failure may be due to incorrect wiring, power loss to the RCB board, or damage to the RS-485 drivers on the LEN bus. A174 (ECB Board Communication Failure) — The ECB board is responsible for building pressure control. Building Pressure control configurations that require this board will cause a complete system shut down when communication failure occurs. Recovery is automatic. Reason for failure may be due to incorrect wiring, power loss to the ECB board, or damage to the RS-485 drivers on the LEN bus. T177 (4-20 mA Demand Limit Failure) — If this transducer fails, and the unit is configured to perform demand limiting with this transducer, no capacity limiting will be performed and an alert will be generated. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. T178 (4-20 mA Static Pressure Reset Fail) — If this transducer fails, and the unit is configured to perform static pressure reset with this transducer, no static pressure reset will be performed and an alert will be generated. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. A200 (Linkage Timeout Error — Comm Failure) — If linkage is established via the CCN with ComfortID™ terminals, a 5-minute timeout on loss of communication will be monitored. If 5 minutes expires since the last communication from a VAV Linkage Master, the unit will remove the link and flag the alert. When the rooftop loses its link, the temperature and set points are derived locally. Recovery is automatic on re-establishment of communications. Reason for failure may be wiring error, too much bus activity, or damaged RS-485 drivers. T210 (Building Pressure Transducer Failure) — If the building pressure transducer (Pressures→AIR.P→BP) fails, building pressure control fails also. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the RCB control board. T211 (Static Pressure Transducer Failure) — If the static pressure transducer (Pressures→AIR.P→SP) fails, static pressure control fails also. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the RCB control board. T220 (Indoor Air Quality Sensor Failure) — If the indoor air quality sensor (Inputs→AIR.Q→IAQ) fails, demand control ventilation is not possible. The control defaults to the max vent position. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the MBB control board. T221 (Outdoor Air Quality Sensor Failure) — If the outdoor air quality sensor (Inputs→AIR.Q→OAQ) fails, OAQ defaults to 400 ppm and demand control ventilation will continue. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. T229 (Economizer Min Pos Override Input Failure) — If the economizer minimum position override input fails, the economizer will operate as if it were not configured for T136 (Compressor A1 Low Differential Pressure) T137 (Compressor A2 Low Differential Pressure) T138 (Compressor B1 Low Differential Pressure) T139 (Compressor B2 Low Differential Pressure) — If the pressure differential between the discharge and suction pressure transducers is less than 50 psig for more than 15 minutes when the circuit is running, an alert will be issued and the circuit shut down. Any compressor that is currently on at the time of the alert will have its own individual alarm sent. Reset is manual. T140 (Circ A Max Diff Operating Press Exceeded) T141 (Circ B Max Diff Operating Press Exceeded) — Depending on the compressor loading, after 5 minutes of operation if the discharge versus suction pressure ratios exceed the curves in Fig. 14, then all compressors in that circuit are stopped and the alert tripped. Reset is manual. A150 (Unit is in Emergency Stop) — If the CCN point name “EMSTOP” in the System table is set to emergency stop, the unit will shut down immediately and broadcast an alarm back to the CCN indicating that the unit is down. This alarm will clear when the variable is set back to “enable”. A152 (Unit Down Due to Failure) — This alarm occurs whenever both cooling circuits are unavailable to cool. Mechanical cooling is impossible due to a failure in the system explained through other current alarms. Possible problems are: • plenum pressure switch trips on a return fan tracking unit • the supply fan status alarms have been instructed to shut down the unit • both circuits incapable of cooling due to multiple alerts of compressors and/or pressure alerts • a hardware failure of the main board's analog to digital converter or EEPROM chip • a critical storage failure in EEPROM has rendered the unit inoperable • the unit is configured for inlet guide vanes and the actuator controlling the vanes is in fault. Reset is automatic. T153 (Real Time Clock Hardware Failure) — The RTC clock chip on the MBB is not responding. Recovery is automatic but typically board replacement may be necessary. A154 (Serial EEPROM Hardware Failure) — The unit will be completely shut down. The serial EEPROM chip on the MBB which stores the unit's configurations is not responding. Recovery is automatic but typically board replacement is necessary. T155 (Serial EEPROM Storage Failure Error) — Configuration data in the serial EEPROM chip can not be verified which may mean MBB replacement. It is possible a re-initialization of the database or particular storage area(s) may clean up this problem. Reset is automatic. A156 (Critical Serial EEPROM Storage Fail Error) — The unit is completely shut down. Critical configuration data in the serial EEPROM chip can not be verified which may mean MBB replacement. Recovery is automatic but typically board replacement is necessary. NOTE: The machine will shut down. This may happen after downloading via the CCN if the device code was corrupted. Try downloading again or use the LEN connection to download. A157 (A/D Hardware Failure) — The unit will be completely shut down. The analog to digital conversion chip on the MBB has failed. Recovery is automatic but typically board replacement is necessary. A171 (Staged Gas Control Board Comm Failure) — Staged Gas Heating is disabled until communication with the staged gas control board is re-established. Recovery is automatic. Reason for failure may be due to incorrect wiring, power loss 99 (Configuration→ALLM→RA.L.U) for 10 minutes, then an alert will be broadcast. T305 (Return Air Temperature Above Limit) — If the return air temperature is below the RAT HI Alert Limit/Occ (Configuration→ALLM→RA.H.O) for 5 minutes or RAT HI Alert Limit/Occ (Configuration→ALLM→RA.H.U) for 10 minutes, then an alert will be broadcast. The alert will automatically reset. T308 (Return Air Relative Humidity Below Limit) — If the unit is configured to use a return air relative humidity sensor through the Return Air RH Sensor (Configuration→UNIT→ SENS→RRH.S) setting, and the measured level is below the configurable RH Low Alert Limit (Configuration→ALLM→ R.RH.L) for 5 minutes, then the alert will occur. The unit will continue to run and the alert will automatically reset. T309 (Return Air Relative Humidity Above Limit) — If the unit is configured to use a return air relative humidity sensor through the Return Air RH Sensor (Configuration→UNIT→ SENS→RRH.S) setting, and the measured level is above the configurable RH High Alert Limit (Configuration→ALLM→ R.RH.H) for 5 minutes, then the alert will occur. Unit will continue to run and the alert will automatically reset. T310 (Supply Duct Pressure Below Limit) — If the unit is a VAV unit with a supply duct pressure sensor and the measured supply duct static pressure (Pressures→AIR.P→SP) is below the configurable SP Low Alert Limit (Configuration→ALLM →SP.L) for 5 minutes, then the alert will occur. The unit will continue to run and the alert will automatically reset. T311 (Supply Duct Pressure Above Limit) — If the unit is a VAV unit with a supply duct pressure sensor and the measured supply duct static pressure (Pressures→AIR.P→SP) is above the configurable SP Low Alert Limit (Configuration→ALLM →SP.H) for 5 minutes, then the alert will occur. The unit will continue to run and the alert will automatically reset. T312 (Building Static Pressure Below Limit) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP Low Alert Limit (Configuration→ALLM→BP.L). If the measured pressure (Pressures→AIR.P→BP) is below the limit for 5 minutes then the alert will occur. T313 (Building Static Pressure Above Limit) — If the unit is configured to use modulating power exhaust then a building static pressure limit can be configured using the BP HI Alert Limit (Configuration→ALLM→BP.H). If the measured pressure (Pressures→AIR.P→BP) is above the limit for 5 minutes, then the alert will occur. T314 (IAQ Above Limit) — If the unit is configured to use a CO2 sensor and the level (Inputs→AIR.Q→IAQ) is above the configurable IAQ High Alert Limit (Configuration→ALLM → IAQ.H) for 5 minutes then the alert will occur. The unit will continue to run and the alert will automatically reset. override. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the MBB control board. This error only occurs when the unit is configured for minimum position override and a 4-20 mA signal is not present. T245 (Outside Air Cfm Sensor Failure) — If the outside air cfm sensor (Inputs→CFM→O.CFM) fails, the economizer will default to discrete positioning of the economizer (Configuration →IAQ→DCV.C→IAQ.M, Configuration→Econ→ EC.MN). Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the CEM control board. T246 (Supply Air Cfm Sensor Failure) — If the supply air cfm sensor (Inputs→CFM→S.CFM) fails, fan tracking is not possible and the system will shut down. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the ECB control board. T247 (Return Air Cfm Sensor Failure) — If the return air cfm sensor (Inputs→CFM→R.CFM) fails, fan tracking is not possible and the system will shut down. Recovery is automatic. Reason for error is either a faulty sensor, wiring error, or damaged input on the ECB control board. T300 (Space Temperature Below Limit) — If the space temperature is below the configurable SPT Low Alert Limits (occupied [Configuration→ALLM→SP.L.O] for 5 minutes or unoccupied [Configuration→ALLM→SP.L.U] for 10 minutes), then an alert will be broadcast. The alert will automatically reset. T301 (Space Temperature Above Limit) — If the space temperature is above the configurable SPT High Alert Limits (occupied [Configuration→ALLM→SP.H.O] for 5 minutes or unoccupied [Configuration→ALLM→SP.H.U] for 10 minutes), then an alert will be broadcast. The alert will automatically reset. T302 (Supply Temperature Below Limit) — If the supply-air temperature measured by the supply temperature sensor is below the configurable SAT LO Alert Limit/Occ (Configuration→ ALLM→SA.L.O) for 5 minutes or the Low Supply air temperature alert limit unoccupied mode (Configuration→ALLM→ SA.L.U) for 10 minutes, then an alert will be broadcast. T303 (Supply Temperature Above Limit) — If the supply temperature is above the configurable SAT HI Alert Limit Occ (Configuration→ALLM→SAH.O) for 5 minutes or the SAT HI Alert Limit/Unocc (Configuration→ALLM→SA.H.U) for 10 minutes, then an alert will be broadcast. The alert will automatically reset. T304 (Return Air Temperature Below Limit) — If the return air temperature measured by the RAT sensor is below the configurable RAT LO Alert Limit/Occ (Configuration→ ALLM→RA.L.O) for 5 minutes or RAT HI Alert Limit/Occ DISCHARGE PRESSURE (PSIG) 450 400 350 UNTIL CHARGE FULL 300 2/3 250 1/2 1/3 200 150 20 40 60 80 SUCTION PRESSURE (PSIG) Fig. 14 — Differential Pressure Chart 100 100 T316 (OAT Below Limit) — If the outside-air temperature measured by the OAT thermistor (Temperatures→AIR.T→ OAT) is below the configurable OAT Low Alert Limit (Configuration→ALLM→OAT.L) for 5 minutes then the alert will be broadcast. T317 (OAT Above Limit — If the outside-air temperature measured by the OAT thermistor (Temperatures→AIR.T→ OAT) is above the configurable OAT High Alert Limit (Configuration→ALLM→OAT.H) for 5 minutes then the alert will be broadcast. A400 (Hydronic Freezestat Trip) — If the freezestat for the hydronic coil trips, the unit goes into emergency mode and does not allow cooling or heating. The economizer goes to 0% open. Supply fan operation is enabled. Recovery is automatic when the switch goes off. A404 (Fire Shut Down Emergency Mode [fire-smoke]) — If the fire shutdown input is energized (fire shutdown is in effect), or if two fire smoke modes are incorrectly energized at the same time, a Fire Shutdown mode will occur. This is an emergency mode requiring the complete shutdown of the unit. Recovery is automatic when the inputs are no longer on. A405 (Evacuation Emergency Mode) — If the evacuation input on the CEM is energized, an evacuation mode occurs which flags an alarm. This mode attempts to lower the pressure of the space to prevent smoke from moving into another space. This is the reverse of the Pressurization Mode. Closing the economizer, opening the return-air damper, turning on the power exhaust, and shutting down the indoor fan will decrease pressure in the space. Recovery is automatic when the input is no longer on. A406 (Pressurization Emergency Mode) — If the pressurization input on the CEM is energized, a pressurization mode occurs which flags an alarm. This mode attempts to raise the pressure of a space to prevent smoke infiltration from another space. The space with smoke should be in an Evacuation Mode attempting to lower its pressure. Opening the economizer, closing the return air damper, shutting down power exhaust, and turning the indoor fan on will increase pressure in the space. Recovery is automatic when the input is no longer on. A407 (Smoke Purge Emergency Mode) — If the smoke purge input on the CEM is energized, a smoke purge mode occurs which flags an alarm. This mode attempts to draw out smoke from the space after the emergency condition. Opening the economizer, closing the return-air damper, and turning on both the power exhaust and indoor fan will evacuate smoke and bring in fresh air. Recovery is automatic when the input is no longer on. T408 (Dirty Air Filter) — If no dirty filter switch is installed, the switch will read “clean filter” all the time. Therefore the dirty filter routine runs continuously and diagnoses the input. Because of the different possible times it takes to generate static pressure, this routine waits 2 minutes after the fan starts before the dirty filter switch is monitored. If the dirty filter switch reads “dirty filter” for 2 continuous minutes, an alert is generated. No system action is taken. This is a reminder that it is time to change the filters in the unit. Recovery from this alert is through a clearing of all alarms (manual) or after the dirty filter switch reads clean for 30 continuous seconds (automatic). T409 (Supply Fan Commanded On, Sensed Off Failure) T409 (Supply Fan Commanded Off, Sensed On Failure) A409 (Supply Fan Commanded On, Sensed Off Failure) A409 (Supply Fan Commanded Off, Sensed On Failure) — Both the alert and the alarm refer to the same failure. The only difference between the alarm and alert is that in the case where the supply fan status configuration to shut down the unit is set to YES (Configuration→UNIT→SFS.S), the alarm will be generated AND the unit will be shut down. It is possible to configure Configuration→UNIT→SFS.M to either a switch or to monitor a 0.2-in. wg rise in duct pressure if the unit is VAV with duct pressure control (IGV or VFD). The timings for failure for both are the same and are illustrated in the following table: UNIT TYPE/MODE CV (no gas heat) CV (gas heat) VAV (IGV/no gas heat) VAV (VFD/no gas heat) VAV (IGV/gas heat) VAV (VFD/gas heat) MINIMUM ON TIME WAIT 30 seconds 2 minutes 2 minutes 1 minute 4 minutes 3 minutes MINIMUM OFF TIME WAIT 1 minute 4 minutes 4 minutes 1 minute 4 minutes 4 minutes Recovery is manual. Reason for failure may be a broken fan belt, failed fan relay or failed supply fan status switch. T421 (Thermostat Y2 Input On without Y1 On) — If Y2 is on and Y1 is off then this alert condition is initiated. The control continues as if both Y1 and Y2 were requested. Alert recovery will not occur until Y1 is seen. This handles some conditions of an incorrectly wired thermostat and may prevent multiple alerts and recoveries from clogging the alarm histories. T422 (Thermostat W2 Input On without W1 On) — If W2 is on and W1 is off then this alert condition is initiated. The control continues as if both W1 and W2 were requested. Alert recovery will not occur until W1 is seen. This handles some conditions of an incorrectly wired thermostat and may prevent multiple alerts and recoveries from clogging the alarm histories. T423 (Thermostat Y and W Inputs On) — Simultaneous calls for heating and cooling are illegal and will be alarmed. Cooling and heating will be locked out. Recovery is automatic when the condition no longer exists. T424 (Thermostat G Input Off On a Cooling Call) — If G is off and there is a cooling request (Y1 or Y2), then it is possible the G connection has not been made to the unit terminal block. An alert is initiated for this condition as continuous fan operation and manual fan control may not be possible. Cooling is started, if allowed, and the fan is turned on. The controls do not diagnose the fan if a heat request (W1 or W2) is in progress. T430 (Plenum Pressure Safety Switch Trip) A430 (Plenum Pressure Safety Switch Trip) — If the unit is configured for fan tracking and the plenum pressure switch trips, the unit will be instructed to shut down immediately. The first 2 times the switch trips, the unit will automatically start up and clear the alert 3 minutes after the switch recovers. The third time the switch trips, the unit shuts down and calls out the alarm. Manual reset of the switch (located in the auxiliary control panel) is required. Software reset is automatic when switch has been reset. Possible causes are blocked exhaust or return dampers causing high pressure at the plenum fan. T500 (Current Sensor Board Failure - A1) T501 (Current Sensor Board Failure - A2) T502 (Current Sensor Board Failure - B1) T503 (Current Sensor Board Failure - B2) NOTE: These alerts are only applicable to size 105 units. If the current sensor board malfunctions or is not properly connected to its assigned digital input, an alert will be generated. It takes 2 to 4 seconds to log the alert. If the alert is logged, it stays active for a minimum of 15 seconds to provide the application a reasonable time to catch the failure. Compressors will be not be inhibited by this failure. Recovery is automatic. Reason for failure may be a faulty current sensor board, incorrect wiring, or a damaged input on the MBB control board. 101 this error will probably require actuator replacement as this problem is internal to the Belimo actuator itself. A700 (Air Temp Lvg Supply Fan Thermistor Failure) — The failure of this sensor will shut the system down and generate an alarm as this thermistor is a critical component to fundamental operation and diagnosis of the rooftop unit. Recovery is automatic. Reason for failure may be incorrect wiring, a faulty thermistor, or a damaged input on the MBB control board. T701 (Staged Gas 1 Thermistor Failure) T702 (Staged Gas 2 Thermistor Failure) T703 (Staged Gas 3 Thermistor Failure) — If any of the staged gas thermistors (Temperatures→AIR.T→S.G.L1-3) fails, an alert will be generated and the remaining thermistors will be averaged together (Temperatures→AIR.T→S.G.LS) without the failed thermistor. Recovery is automatic. Reason for failure may be incorrect wiring, faulty thermistor, or a damaged input on the staged gas control board (SCB). A704 (Staged Gas Lvg Air Temp Sum Total Failure) — If all three staged gas thermistors (Temperatures→AIR.T→ S.G.L1,2,3) fail, staged gas will be shut down and this alarm will be generated. Recovery is automatic. Reason for failure may be faulty wiring, faulty thermistors, or damaged inputs on the staged gas control board (SCB). T705 (Limit Switch Thermistor Failure) — A failure of this thermistor (Temperatures→AIR.T→S.G.LM) will cause an alert to occur and a disabling of the limit switch monitoring function for the staged gas control board (SCB). Recovery is automatic. Reason for failure may be due to faulty wiring, a faulty thermistor, or a damaged input on the staged gas control board (SCB). A706 (Hydronic Evap Discharge Thermistor Failure) — If the unit is configured for hot water heating (hydronic), then the unit has a thermistor (Temperatures→AIR.T→CCT) installed between the evaporator coil and the hot water coils that functions as the evaporator discharge temperature thermistor for cooling. If this thermistor fails, an alarm will be generated and the system will be shut down. Recovery is automatic. Reason for failure may be due to faulty wiring, a faulty thermistor, or a damaged input on the ECB control board. T610 (Economizer Actuator Out of Calibration) A620 (IGV Actuator Out of Calibration) T630 (Humidifier Actuator Out of Calibration) A640 (Heating Coil Actuator Out of Calibration) A650 (Bldg.Press. Actuator 1 Out of Calibration) A660 (Bldg.Press. Actuator 2 Out of Calibration) T670 (Economizer 2 Actuator Out of Calibration — Each of the Belimo LEN communicating actuators must have a minimum control range to operate. If the actuator, after a calibration, has not learned a control range appropriate for the application, this alarm/alert will be sent. No action will be taken on this error. Recovery is automatic. Reason for failure may be an obstruction or stuck linkage that prevents full range calibration. T611 (Economizer Actuator Comm Failure) A621 (IGV Actuator Communication Failure) T631 (Humidifier Actuator Communication Failure) A641 (Heating Coil Actuator Comm Fail) A651 (Bldg.Press. Actuator 1 Comm Failure) A661 (Bldg.Press. Actuator 2 Comm Failure) T671 (Economizer 2 Actuator Comm Failure) — Each of the actuators communicates over the local equipment network (LEN). If this error occurs, then it is impossible to control the actuator. Depending on the function of the actuator, the control will shut down any process associated with this actuator. Recovery is automatic. Reason for failure may be incorrect wiring, incorrect serial number configuration, or damaged RS-485 drivers on the LEN bus. T612 (Economizer Actuator Control Range Increased) T622 (IGV Actuator Control Range Increased) T632 (Humidifier Actuator Control Range Increased) T642 (Heat Coil Actuator Control Range Increased) T652 (Bldg.Press. Act. 1 Control Range Increased) T662 (Bldg.Press. Act. 2 Control Range Increased) T672 (Economizer 2 Actuator Control Range Increased) — The actuators, once properly calibrated, learn their end stops for movement. During normal operation, if the actuator perceives that the actuator is able to go farther than its learned range of operation, this error will be broadcast. Reason for failure may be a slipping of the linkage and therefore this error may mean that the actuator cannot perform its assigned function. Recovery requires a fix of any slipped linkage and/or a re-calibration. T613 (Econ Actuator Overload, Setpt Not Reached) A623 (IGV Actuator Overload, Setpnt Not Reached) T633 (Humidifier Act Overload, Setpt Not Reached) A643 (Ht Coil Act Ovrload, Setpt Pos Not Reached) A653 (BP Act. 1 Overload, Setpnt Pos Not Reached) A663 (BP Act. 2 Overload, Setpnt Pos Not Reached) T673 (Econ2 Actuator Overload, Setpt Not Reached) — If an actuator is unable to achieve a commanded position within a reasonable period of time, this alarm or alert will be broadcast. This may be an indication of a stuck actuator. No action is taken. Recovery is automatic. T614 (Econ Actuator Comm Fail, Daughter Brd-MFT) A624 (IGV Actuator Comm Fail, Daughter Board-MFT) T634 (Humidifier Act Comm Fail, Daughter Brd-MFT) A644 (Heat Coil Act Com Fail, Daughter Board-MFT) A654 (BP Actuator 1 Com Fail, Daughter Board-MFT) A664 (BP Actuator 2 Com Fail, Daughter Board-MFT) T674 (Econ2 Actuator Comm Fail, Daughter Brd-MFT) — Each of the actuators has an internal daughter card, which translates communications from the LEN bus to Belimo’s MFT (Multi-Function Technology®) communication bus and back. If communication breaks down between the actuator and its internal daughter card, this alarm/alert will result. This makes the actuator unusable and any functions associated with the particular actuator are shut down. Recovery is automatic, but MAJOR SYSTEM COMPONENTS General — The 48/50Z Series package rooftop units with electric cooling and with gas heating (48Z units) or electric cooling and electric or hydronic heating (50Z Units) contain the ComfortLink™ electronic control system that monitors all operations of the rooftop. The control system is composed of several components as listed below. See Fig. 15-22 for typical control and power component schematics. Figures 23-25 show the layout of the control box. Factory-Installed Components MAIN BASE BOARD (MBB) — See Fig 26. The MBB is the center of the ComfortLink control system. The MBB contains the major portion of the operating software and controls the operation of the unit. The MBB has 22 inputs and 11 outputs. See Table 87 for the inputs and output assignments. The MBB also continuously monitors additional data from the ECB, RCB, SCB, and CEM boards through the LEN communications port. The MBB also communicates with and controls the actuator motors, economizer, power exhaust dampers, VFDs, IGVs, hydronic valves, and humidifier valves. The MBB also interfaces with the Carrier Comfort Network® system through the CCN communications port located on the COMM3 board. The COMM3 board has permanent terminals as well as a J11 jack for temporary connections. The board is located in the main control box. 102 a48-8408 103 Fig. 15 — Typical Power Schematic (Sizes 030-050 Shown) a48-8409 Fig. 16 — Main Base Board Input/Output Connections 104 a48-8410 Fig. 17 — RCB, ECB, CEM, SCB Input/Output Connections 105 a48-8411 Fig. 18 — Typical Gas Heat Unit Control Wiring (48Z055-105 Units Shown) 106 a50-8248 Fig. 19 — Typical Electric Heat Unit Control Wiring (50Z055-105 Units Shown) 107 a48-8412 Fig. 20 — Typical Power Wiring (115-V) (48Z Units) 108 a50-8249 Fig. 21 — Typical Power Wiring (115-V) (50Z Units) 109 a48-8413 110 Fig. 22 — Typical Gas Heat Section (Size 055-105 Units Shown) 111 Fig. 23 — Component Arrangement (Size 030-050 Units) 112 Fig. 24 — Component Arrangement (Size 055-070 Units) 113 Fig. 25 — Component Arrangement (Size 075-105 Units) LEGEND FOR FIG. 15-25 ACCSY ACC’Y AF AN APS BM BR C CB CBT CCB CCN CCT CEM CH CM COMP CR CSB CV DI DPT ECB ECON EQUIP FU GND GVR HC HIR HPS HS HV I — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Accessory Accessory Airfoil Analog Air Pressure Switch Blower Motor Blower Relay Compressor Contactor Compressor Circuit Breaker Circuit Breaker, Transformer Control Circuit Breaker Carrier Comfort Network® Cooling Coil Thermistor Controls Expansion Module Crankcase Heater Combustion Motor Compressor Control Relay Current Sensor Board Constant Volume Digital Input Discharge Pressure Transducer Economizer Control Board Economizer Equipment Fuse Ground Gas Valve Relay Heater Contactor Heat Interlock Relay High-Pressure Switch Hall Effect Sensor High Voltage Ignitor IAQ IDM IFC IFCB IFM IGC IGV IP LEI LEN LS MBB MGV MMC MMR MOD PE NEC OA OAQ OAT OD OFC OFM OPT PE PEC PECB PEM PL PTC — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — RA RAT RCB — — — Indoor Air Quality Induced Draft Motor Indoor Fan Contactor Indoor Fan Circuit Breaker Indoor Fan Motor Integrated Gas Controller Inlet Guide Vane Internal Protector Local Equipment Interface Local Equipment Network Limit Switch Main Base Board Main Gas Valve Motormaster® Contactor Motormaster Relay Modulating Power Exhaust National Electrical Code Outdoor Air Outdoor Air Quality Outdoor-Air Thermostat Outdoor Outdoor Fan Contactor Outdoor Fan Motor Option Power Exhaust Power Exhaust Contactor Power Exhaust Circuit Breaker Power Exhaust Motor Plug Assembly Positive Temperature Coefficient Power Reference Return Air Return Air Thermistor Rooftop Control Board RED LED - STATUS GREEN LED - LEN (LOCAL EQUIPMENT NETWORK) RF RS SAT SCB SEN SPT STDU TB TRAN U VAV VFD — — — — — — — — — — — — Return Fan Rollout Switch Supply Air Thermistor Staged Gas Control Board Sensor Suction Pressure Transducer Standard Tier Display Unit Terminal Block Transformer Unloader Variable Air Volume Variable Frequency Drive Terminal Block Terminal (Unmarked) Terminal (Marked) Splice Factory Wiring Field Wiring To indicate common potential only, not to represent wiring. To indicate factory-installed option or accessory YELLOW LED CCN (CARRIER COMFORT NETWORK) INSTANCE JUMPER (SET TO 1) CEPL130346-01 HK 50AA029 CE BO 430346 J1 J4 STATUS J2 J10 LEN J3 J5 J6 J7 J9 J8 Fig. 26 — Main Base Board (MBB) cfm. This board is located in the main control box. Input and output assignments are summarized in Table 89. STAGED GAS HEAT BOARD (SCB) — When optional staged gas heat is used, the SCB board is installed and controls additional stages of gas heat. See Fig. 28. The SCB also provides additional sensors for monitoring of the supply-air and limit switch temperatures. This board is located in the main unit control box. The inputs and outputs are summarized in Table 90. ROOFTOP CONTROL BOARD (RCB) — The RCB has additional inputs and outputs required for the control of the unit. All units have an RCB board. See Fig. 27. The board has 9 inputs and 8 outputs. Details can be found in Table 88. The RCB board is located in the main control box. ECONOMIZER CONTROL BOARD (ECB) — The ECB is used on size 075-105 units with high-capacity power exhaust or return/exhaust fan. See Fig. 27. The ECB board sends a 4 to 20 mA signal to the VFD to control the exhaust fan speed. The board also has inputs to sense the return fan cfm and supply fan 114 Table 87 — Main Control Board (MBB) Inputs and Outputs POINT NAME POINT DESCRIPTION I/O PLUG AND PIN POINT REFERENCE NAME SIGNAL PIN(S) PORT STATE INPUTS IGCIFO FSD G W2 W1 Y2 Y1 IGC IFO input Fire Shutdown Switch Thermostat G input Thermostat W2 input Thermostat W1 input Thermostat Y2 input Thermostat Y1 input DI1 DI2 DI3 DI4 DI5 DI6 DI7 J6, 3-4 J6, 5-6 J7, 1-2 J7, 3-4 J7, 5-6 J7, 7-8 J7, 9-10 4 6 2 4 6 8 10 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac CSB_A1 CSB_B1 CSB_A2 CSB_B2 Compressor A1 Feedback Compressor B1 Feedback Compressor A2 Feedback Compressor B2 Feedback DIG1 DIG2 DIG3 DIG4 J9, 10-12 J9, 7-9 J9, 4-6 J9, 1-3 10=5v, 11=Vin, 12=GND 7=5v, 8=Vin, 9=GND 4=5v, 5=Vin, 6 =GND 1=5v, 2=Vin, 3=GND 0 = 5vdc, 1 = 0vdc 0 = 5vdc, 1 = 0vdc 0 = 5vdc, 1 = 0vdc 0 = 5vdc, 1 = 0vdc DP_A DP_B SP_A SP_B RAT SAT OAT SPT SPTO IAQ IAQINMOV FLTS Cir A Discharge Pressure Cir B Discharge Pressure Cir A Suction Pressure Cir B Suction Pressure Return Air Temperature Air Temp Lvg Supply Fan Outside Air Temperature Space Temperature Space Temperature Offset IAQ - PPM Return CO2 (IAQANCFG = 1,2) 4-20ma/10k pot MinPosOver(IAQANCFG = 3,4) Filter Status Switch AN1 AN2 AN3 AN4 AN5 AN6 AN7 AN8 AN9 AN10 AN10 AN11 J8, 21-23 J8, 24-26 J8, 15-17 J8, 18-20 J8, 9-10 J8, 11-12 J8, 13-14 J8, 1-2 J8, 3-4 J8, 5-6 J8, 5-6 J8, 7-8 21=5v, 22=Vin, 23=GND (thermistor 21-22) 24=5v, 25=Vin, 26=GND (thermistor 24-25) 15=5v, 16=Vin, 17=GND (thermistor 15-16) 18=5v, 19=Vin, 20=GND (thermistor 18-20) 9 11 13 1 3 5 5 7 (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) OUTPUTS CMPB2 CMPB1 CMPA2 CMPA1 CONDFANB CONDFANA HS2 HS1 PE1 SFAN ALRM Compressor B2 Compressor B1 Compressor A2 Compressor A1 Condenser Fan Circuit B Condenser Fan Circuit A Heat Relay 2 Heat Relay 1 Power Exhaust Relay 1 Supply Fan Relay Remote Alarm Relay RLY 1 RLY 2 RLY 3 RLY 4 RLY 5 RLY 6 RLY7 RLY 8 RLY 9 RLY 10 RLY 11 J10, 20-21 J10, 22-23 J10, 24-25 J10, 26-27 J10, 10-11 J10, 12-13 J10, 14-16 J10, 17-19 J10, 4-6 J10, 7-9 J10, 1-3 20 = RLY1A (=RLY2A), 21 = RLY1B 22 = RLY2A (=RLY1A), 23 = RLY2B 24 = RLY3A (=RLY4A), 25 = RLY3B 26 = RLY4A (=RLY3A), 27 = RLY4B 10 = RLY5A (=RLY6A), 11 = RLY5B 12 = RLY6A (=RLY5A), 13 = RLY6B 14 = 15 = RLY7A, 16 = RLY7B 17 = 18 = RLY8A, 19 = RLY8B 4 = 5 = RLY9A, 6 = RLY9B 7 = 8 = RLY10A, 9 = RLY10B 1 = 2 = RLY11A, 3 = RLY11B 1 = Closes RLY1A / RLY1B 1 = Closes RLY2A / RLY2B 1 = Closes RLY3A / RLY3B 1 = Closes RLY4A / RLY4B 1 = Closes RLY5A / RLY5B 1 = Closes RLY6A / RLY6B 1 = Closes RLY7A / RLY7B 1 = Closes RLY8A / RLY8B 1 = Closes RLY9A / RLY9B 1 = Closes RLY10A / RLY10B 1 = Closes RLY11A / RLY11B Fig. 27 — Economizer Control Board (ECB) and Rooftop Control Board (RCB) 115 Table 88 — Rooftop Control Board (RCB) Inputs and Outputs POINT NAME I/O POINT NAME POINT DESCRIPTION PLUG AND PIN REFERENCE SIGNAL PIN(S) PORT STATE INPUTS RMTIN ENTH SFS CIRCAHPS CIRCBHPS FRZ Remote Input State Enth. Switch Read High ? Supply Fan Status Switch Circ A High Press.Switch Circ B High Press.Switch Freeze Status Switch DI1 DI2 DI3 DI4 DI5 DI6 J4, 1-2 J4, 3-4 J4, 5-6 J4, 7-8 J4, 9-10 J4, 11-12 2 4 6 8 10 12 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, BP SP CCT Building Pressure Static Pressure Air Temp Lvg Evap Coil AN1 AN2 AN3 AN4 AN5 AN6 J5, 1-3 J5, 4-6 J6, 1-2 J6, 3-4 J6, 5-6 J6, 7-8 1=24VDC, 2=0-20mA in, 3=GND 4=24VDC, 5=0-20mA in, 6=GND 1 3 5 7 0-20mA 0-20mA (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) OUTPUTS SFAN_VFD Supply Fan VFD Speed AO1 J9, 1-2 1=0-20mA, 2=GND 0-20mA OUT PULSCFAB Pulsed Condenser Fan A-B PP/MP J7, 1-3 1=PP/MP Data, 2=24VAC, 3=GND Belimo PP/MP Protocol UNL_1_A1 UNL_2_A1 PE2 HIR UNL_1_B1 HUMIDRLY UNL_2_B1 Unloader 1 - Comp A1 Unloader 2 - Comp A1 Power Exhaust Relay 2 (BLDG_CFG = 1) Heat Interlock Relay (BLDG_CFG not 1) Unloader 1 - Comp B1 Humidifier Relay Unloader 2 - Comp B1 RLY1 RLY 2 RLY 3 RLY 3 RLY 4 RLY 5 RLY 6 J8, 1-3 J8, 4-6 J8, 7-9 J8, 7-9 J8, 10-12 J8, 13-15 J8, 16-18 1 = 2 = RLY1A, 3 = RLY1B 4 =5 = RLY2A, 6 = RLY2B 7 = 8 = RLY3A, 9 = RLY3B 7 = 8 = RLY3A, 9 = RLY3B 10 = 11 = RLY4A, 12 = RLY4B 13 = 14 = RLY5A, 15 = RLY5B 16 = 17 = RLY6A, 18 = RLY6B 1 = Closes RLY1A / RLY1B 1 = Closes RLY2A / RLY2B 1 = Closes RLY3A / RLY3B 1 = Closes RLY3A / RLY3B 1 = Closes RLY4A / RLY4B 1 = Closes RLY5A / RLY5B 1 = Closes RLY6A / RLY6B 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 Table 89 — Economizer Control Board (ECB) Inputs and Outputs POINT NAME INPUTS PPS I/O POINT NAME POINT DESCRIPTION SIGNAL PIN(S) PORT STATE NA NA NA NA DI1 DI2 DI3 DI4 DI5 DI6 J4, 1-2 J4, 3-4 J4, 5-6 J4, 7-8 J4, 9-10 J4, 11-12 2 4 6 8 10 12 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, 24VAC = 1, Supply Air CFM Return Air CFM NA NA NA NA AN1 AN2 AN3 AN4 AN5 AN6 J5, 1-3 J5, 4-6 J6, 1-2 J6, 3-4 J6, 5-6 J6, 7-8 1=24VDC, 2=0-20mA in, 3=GND 4=24VDC, 5=0-20mA in, 6=GND 1 3 5 7 0-20mA 0-20mA (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) OUTPUTS EFAN_VFD Exhaust Fan VFD Speed AO1 J9, 1-2 1=0-20mA, 2=GND 0-20mA OUT PP/MP J7, 1-3 1=PP/MP Data, 2=24VAC, 3=GND Belimo PP/MP Protocol PE2 Power Exh. VFD Stage 2 (BLDG_CFG = 4) RLY1 RLY 2 RLY 3 RLY 4 RLY 5 RLY 6 J8, 1-3 J8, 4-6 J8, 7-9 J8, 10-12 J8, 13-15 J8, 16-18 1 = 2 = RLY1A, 3 = RLY1B 4 =5 = RLY2A, 6 = RLY2B 7 = 8 = RLY3A, 9 = RLY3B 10 = 11 = RLY4A, 12 = RLY4B 13 = 14 = RLY5A, 15 = RLY5B 16 = 17 = RLY6A, 18 = RLY6B 1 = Closes RLY1A / RLY1B 1 = Closes RLY2A / RLY2B 1 = Closes RLY3A / RLY3B 1 = Closes RLY4A / RLY4B 1 = Closes RLY5A / RLY5B 1 = Closes RLY6A / RLY6B SACFM RACFM Plenum Press.Safety Sw. PLUG AND PIN REFERENCE NA NA 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 0VAC = 0 Table 90 — Staged Gas Control Board (SCB) Inputs and Outputs POINT NAME POINT DESCRIPTION I/O POINT NAME PLUG AND PIN REFERENCE SIGNAL PIN(S) PORT STATE INPUTS LIMSWTMP LAT1SGAS LAT2SGAS LAT3SGAS Limit Switch Temperature Staged Gas LAT 1 Staged Gas LAT 2 Staged Gas LAT 3 AN1 AN2 AN3 AN4 AN5 AN6 AN7 AN8 AN9 AN10 J5, 1-3 J5, 4-6 J5, 7-9 J5, 10-12 J5, 13-15 J6, 1-3 J6, 4-6 J6, 7-9 J7, 1-2 J7, 3-4 1=5v, 2=Vin, 3=GND (thermistor 1-2) 4=5v, 5=Vin, 6=GND (thermistor 4-5) 7=5v, 8=Vin, 9=GND (thermistor 7-8) 10=5v, 11=Vin, 12=GND (thermistor 10-11) 13=5v, 14=Vin, 15=GND (thermistor 13-14) 1=5v, 2=Vin, 3=GND (thermistor 1-2) 4=5v, 5=Vin, 6=GND (thermistor 4-5) 7=5v, 8=Vin, 9=GND (thermistor 7-8) 1 3 (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (0-5VDC, thermistor, ohms) (thermistor, ohms) (thermistor, ohms) OUTPUTS HTSGCALC Staged Gas Capacity Calc AO1 AO2 J8, 1-2 J8, 3-4 1=0-20mA, 2=GND 3=0-20mA, 4=GND 0-20mA OUT 0-20mA OUT HS3 HS4 HS5 HS6 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 RLY1 RLY2 RLY3 RLY4 RLY5 J9, 1-3 J9, 4-6 J9, 7-9 J9, 10-12 J9, 13-15 1 = 2 = RLY1A, 3 = RLY1B 4 =5 = RLY2A, 6 = RLY2B 7 = 8 = RLY3A, 9 = RLY3B 10 = 11 = RLY4A, 12 = RLY4B 13 = 14 = RLY5A, 15 = RLY5B 1 = Closes RLY1A / RLY1B 1 = Closes RLY2A / RLY2B 1 = Closes RLY3A / RLY3B 1 = Closes RLY4A / RLY4B 1 = Closes RLY5A / RLY5B 116 ADDRESS DIP SWITCHES ALL ON RED LEDSTATUS CEBD430427 GREEN LEDLEN (LOCAL EQUIPMENT NETWORK) HK50AA032 CEPL130427 J2 J1 PWR PWR J4 1 1 LEN LEN 4 J3 13 1 J9 4 13 10 10 7 XDCR/THERM 7 RELAYS 4-POSITION DIP SWITCH J5 J6 J7 4 7 XDCR/THERM 1 3 1 J8 3 THERM 1 0-20mA OUT Fig. 28 — Staged Gas Heat Control Board (SCB) LOW VOLTAGE TERMINAL STRIP — This circuit board provides a connection point between the major control boards and a majority of the field-installed accessories. See Table 92. The circuit breakers for the low voltage control transformers, interface connection for the Carrier Comfort Network® (CCN) communication, and interface connection for the Local Equipment Network (LEN) communication are also located on the low voltage terminal strip. INTEGRATED GAS CONTROL (IGC) — One IGC is provided with each bank of gas heat exchangers. One is used on low heat size 030-050 units. Two are used on high heat size 030-050 units and low heat 055-105 units. Three are used on high heat 055-105 units. The IGC controls the direct spark ignition system and monitors the rollout switch, limit switches, and induced-draft motor Hall Effect switch. The IGC is equipped with an LED (light-emitting diode) for diagnostics. See Table 93. COMPRESSOR PROTECTION BOARD (CSB) (Size 105 Units Only) — This board monitors the status of the compressor by sensing the current flow to the compressors and then provides digital status signal to the MBB. CONTROL EXPANSION MODULE (CEM) — The optional CEM is used to provide inputs for demand limiting, remote set point and other optional inputs typically needed for energy management systems. See Fig. 29. On CCN systems these inputs can be interfaced to through the CCN communications. It is located in the main control box. The CEM also has inputs for accessory relative humidity sensors. This board is also used on units equipped with optional outdoor air CFM monitoring. The inputs and outputs are summarized in Table 91. The optional (or accessory) CEM is used to accept inputs for additional sensors or control sequence switches, including: • Smoke control mode field switches • VAV supply air set point reset using an external 4 to 20 mA signal • Outdoor air CO2 sensor • Space, return and/or outdoor air relative humidity sensors • IAQ function discrete switch • Demand limit sequence proportional signals or discrete switches The CEM is factory-installed when the outdoor air cfm control option is installed. 117 J2 LEN J3 TEST 1 PWR J4 J1 STATUS CEPL130351-01 CEBD430351 J5 J7 J6 TEST 2 GREEN LED LEN (LOCAL EQUIPMENT NETWORK) RED LED - STATUS ADDRESS DIP SWITCH (ALL ON) Fig. 29 — Controls Expansion Board (CEM) Table 91 — Control Expansion Module (CEM) Inputs and Outputs POINT NAME POINT DESCRIPTION I/O POINT NAME PLUG AND PIN REFERENCE SIGNAL PIN(S) PORT STATE INPUTS DHDISCIN DMD_SW1 DMD_SW2 PRES EVAC PURG IAQIN Dehumidify Switch Input Demand Limit Switch 1 Demand Limit Switch 2 Pressurization Evacuation Smoke Purge IAQ - Discrete Input DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 J7, 1-2 J7, 3-4 J7, 5-6 J7, 7-8 J7, 9-10 J7, 11-12 J7, 13-14 2 4 6 8 10 12 14 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac 0 = 24vac, 1= 0vac OACFM OARH SPRH RARH Outside Air CFM Outside Air Rel.Humidity Space Relative Humidity Return Air Rel.Humidity AN7 AN8 AN9 AN10 J6, 1-3 J6, 4-6 J6, 7-9 J6, 10-12 2 (1 = loop power) 5 (4 = loop power) 8 (7 = loop power) 11 (10 = loop power) (0-20mA input) (0-20mA input) (0-20mA input) (0-20mA input) DMDLMTMA EDTRESMA OAQ SPRESET 4-20ma Demand Signal EDT Reset milliampere OAQ - PPM Return CO2 SP Reset milliamps AN1 AN2 AN3 AN3 AN4 AN5 AN6 J5, 1-2 J5, 3-4 J5, 5-6 J5, 5-6 J5, 7-8 J5, 9-10 J5, 11-12 1 3 5 5 7 9 11 (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) (thermistor, ohms) 118 Table 92 — Field Terminal Connections BOARD TERMINAL DESCRIPTION NO. NUMBER TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box) 11 L1 power supply TB1 12 L2 power supply 13 L3 power supply NEUTRAL (in Main Control Box) Neutral 1 Neutral Power CCN COMMUNICATIONS (in Main Control Box) 1 LEN + 2 LEN C 3 LEN – 4 24 vac Comm Port 5 CCN + 7 CCN c 7 CCN – 8 Grd TB201 - FIELD CONNECTIONS (in Main Control Box) 1 Remote Occupied/Economizer Enable 24 vac out 2 Remote Occupied/Economizer Enable 24 vac in 3 Not Used 4 OD Enthalpy Switch in 5 Fire Shut Down 6 Fire Shut Down 7 VAV Heater Interlock Relay 8 VAV Heater Interlock Relay TB201 9 Humidifier Output, Ground 10 Humidifier Output, 24 VAC 11 Unit Alarm Output 12 Unit Alarm Output 13 Smoke Detector Alarm Input 14 Smoke Detector Alarm Input 15 Not Used 16 Not Used TB202 - THERMOSTAT CONNECTIONS (in Main Control Box) 1 Thermostat R 2 Thermostat G 3 Thermostat W2 4 Thermostat W1 5 Thermostat Y2 6 Thermostat Y1 7 Not Used 8 Space Sensor TH 9 Space Sensor COM TB202 10 Space Sensor Offset SW Indoor Air IAQ Remote Sensor/Remote 11 Pot/Remote 4-20 mA Indoor Air IAQ Remote Sensor/Remote 12 Pot/Remote 4-20 mA 13 Not Used 14 Not Used 15 Not Used 16 Not Used TB203 - FIELD CONNECTIONS (in Main Control Box) 1 Ground 2 Demand Limit 4-20 mA (+) 3 Demand Limit 4-20 mA (-) 4 Supply Air Reset 4-20 mA (+) 5 Supply Air Reset 4-20 mA (-) 6 Outdoor Air IAQ 4-20 mA (+) 7 Outdoor Air IAQ 4-20 mA (-) 8 Space Humidity 4-20 mA (+) TB203 9 Space Humidity 4-20 mA (-) 10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15 Not Used 16 Not Used LEGEND IAQ — Indoor Air Quality VAV — Variable Air Volume 119 TYPE 208-230/460/575/380/-3-60, 400-3-50 208-230/460/575/380/-3-60, 400-3-50 208-230/460/575/380/-3-60, 400-3-50 5 vdc, logic 5 vdc, logic 5 vdc, logic 24 vac 5 vdc, logic 5 vdc, logic 5 vdc, logic ground external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) — 24 vac external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) — — 24 vac output 24 vac input 24 vac input 24 vac input 24 vac input 24 vac input — Thermistor input Thermistor input Thermistor input Thermistor input or externally powered 4 to 20 mA when used with 180 ohm resistor Thermistor input or externally powered 4 to 20 mA when used with 180 ohm resistor ground 4 to 20 mA loop power 4 to 20 mA loop power 4 to 20 mA loop power 4 to 20 mA signal 4 to 20 mA loop power 4 to 20 mA signal 4 to 20 mA loop power 4 to 20 mA signal — — — — — — — Table 92 — Field Terminal Connections (cont) BOARD TERMINAL DESCRIPTION NO. NUMBER TB204 - FIELD CONNECTIONS (in Main Control Box) 1 Demand Limit Redline 24 vac out 2 Demand Limit Redline 24 vac in 3 Demand Limit Loadshed 24 vac out 4 Demand Limit Loadshed 24 vac in 5 Fire Pressuration 24 vac out 6 Fire Pressuration 24 vac in 7 Fire Evacuation 24 vac out 8 Fire Evacuation 24 vac in TB204 9 Fire Smoke Purge 24 vac out 10 Fire Smoke Purge 24 vac in 11 IAQ Switch 24 vac out 12 IAQ Switch 24 vac in 13 Not Used 14 Not Used 15 Not Used 16 Not Used TYPE external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) external contact (maximum 24 vac, 3 A) — — — — LEGEND IAQ — Indoor Air Quality VAV — Variable Air Volume control includes a full alarm history, which can be accessed from the display. In addition, through the scrolling marquee the user can access a built-in test routine that can be used at startup commission and to diagnose operational problems with the unit. The scrolling marquee is located in the main control box and is standard on all units. SUPPLY FAN — The 48/50Z030-050 units are equipped with a single 25 x 25-in. forward-curved fan. The 48/50Z055-070 units are equipped with a single 30 x 27-in. forward-curved fan. The 48/50Z075-105 units are equipped with either a single 36 x 30-in. forward-curved fan or a 36-in. airfoil fan. The fan sleds are spring isolated and driven by a single, 3-phase motor. The fan is controlled directly by the ComfortLink™ controls. VARIABLE FREQUENCY DRIVE (VFD) — On variable air volume units with optional VFD, the supply fan speed is controlled by a 3-phase VFD. The VFD is located in the supply fan section (030-050 units) or mixing box section (055-105 units) behind an access door. The VFD speed is controlled directly by the ComfortLink™ controls through a 4 to 20 mA signal based on a supply duct pressure sensor. The VFD has a display, which can be used for service diagnostics, but setup of the building pressure and control loop factors should be done through the scrolling marquee display. The VFD is powered during normal operation to prevent condensation from forming on the boards during the off mode and is stopped by driving the speed to 0 (by sending a 4 mA signal to the VFD). The Z Series units use ABB VFDs. The interface wiring for the VFDs is shown in Fig. 31. Terminal designations are shown in Table 94. Table 93 — IGC Board Inputs and Outputs POINT NAME INPUTS RT W G LS RS SS CS FS OUTPUTS CM IFO R SPARK LED POINT DESCRIPTION CONNECTOR PIN NO. 24 Volt Power Supply Heat Demand Fan Limit Switch Rollout Switch Hall Effect Sensor Centrifugal Switch (Not Used) Flame Sense RT,C 2 3 7,8 5,6 1,2,3 9,10 FS Induced Draft Motor Indoor Fan 24 Volt Power Output (Not Used) Sparker Display LED CM IFO R — SCROLLING MARQUEE — This device is the keypad interface used to access the control information, read sensor values, and test the unit. The scrolling marquee display is a 4-key, 4-character, 16-segment LED display as well as an Alarm Status LED. See Fig. 30. The display is easy to operate using 4 buttons and a group of 11 LEDs that indicate the following menu structures: • Run Status • Service Test • Temperatures • Pressures • Set points • Inputs • Outputs • Configuration • Timeclock • Operating Modes • Alarms Through the scrolling marquee, the user can access all the inputs and outputs to check on their values and status. Because the unit is equipped with suction pressure transducers and discharge saturation temperature sensors, the scrolling marquee can also display pressures typically obtained from gages. The MODE Run Status Service Test Temperature Pressures Setpoints Inputs Alarm Status Outputs Configuration Time Clock ESCAPE ENTER Operating Modes Alarms Fig. 30 — Scrolling Marquee 120 + – Fig. 31 — VFD Wiring Table 94 — VFD Terminal Designations TERMINAL U1 V1 W1 U2 V2 W2 X1-11 (GND) X1-12 (COMMON) X1-10 (24 VDC) X1-13 (DI-1) X1-10 (24 VDC) X1-16 (DI-4) X1-2 (AI-1) X1-3 (AGND) out the back of the unit or discharged through the return air section of the economizer. ECONOMIZER MOTOR(S) — The economizer outside air and return air dampers are gear-driven dampers without linkages. An LEN communicating economizer motor(s) controls their position. The motor position is controlled by the MBB through the LEN communication bus. This allows for accurate control of the motors as well as feedback information and diagnostics information. The control has a self-calibration routine that allows the motor position to be configured at initial unit start-up. The motor(s) is located on the economizer and can be reached through the filter access door. THERMISTORS AND PRESSURE TRANSDUCERS — The unit is equipped with several thermistors for measurement of temperatures. The thermistors are summarized in Table 95. The units have two pressure transducers that are connected to the low side of the system. These two pressure transducers measure the low side pressure and are used for low pressure protection and coil freeze protection. The units also have two pressure transducers that are connected to the high side of the system. These two pressure transducers measure the discharge pressure and are used to cycle the condenser fans to maintain head pressure. By using the high and low side pressure transducers, the ComfortLink controls display the high and low side pressures and saturation temperatures and a normal gage set is not required. SMOKE DETECTOR — The units can be equipped with an accessory smoke detector located in the return air. The detector is wired to the ComfortLink controls and, if activated, will stop the unit by means of a special fire mode. The smoke detector can also be wired to an external alarm system through TB201 terminals 5 and 6. The sensor is located in the return air section. FILTER STATUS SWITCH — The units can be equipped with an optional filter status switch. The switch measures the pressure drop across the filters and closes when an adjustable pressure set point is exceeded. The sensor is located in the return air section behind the filter access door. FUNCTION Three-Phase Main Circuit Input Power Supply Three-Phase AC Output to Motor, 0 V to Maximum Input Voltage Level Factory-supplied jumper Run (factory-supplied jumper) Start Enable 1 (factory-supplied jumper). When opened the drive goes to emergency stop. Factory wired for 4 to 20 mA remote input POWER EXHAUST — The units can be equipped with an optional power exhaust system. The power exhaust fans are two belt-drive forward-curved fans. On non-modulating systems, the fans are staged by the ComfortLink™ controls based on the economizer damper position. For modulating (CV or VAV) applications, the fans are turned on by the ComfortLink control based on building pressure sensed by the building pressure transducer. The fan output is modulated via discharge dampers with LEN communicating actuators to maintain the building pressure set point. HIGH CAPACITY POWER EXHAUST (Sizes 075-105 Only) — The power exhaust fans are two belt-driven forwardcurved fans. Operation of the power exhaust is a combination modulating/staged control. The lead fan is controlled by a VFD and provides 0 to 50% of total exhaust capability. The second fan is staged On/Off (for a step of 50% of total exhaust capability) according to the VFD output level on fan no. 1. RETURN/EXHAUST FAN (Sizes 075-105 Only) — The return/exhaust fan power exhaust assembly consists of one belt-drive plenum fan. The plenum fan pressurizes the plenum fan section so that the air can either be discharged horizontally 121 Table 95 — Thermistors and Unit Operation Control Pressure Transducers SENSOR Thermistors DESCRIPTION AND LOCATION Cooling Coil Thermistor input. Provided with factory-option hydronic heat. Located on face of the hydronic heating coil. Consists of 4 thermistors wired into a 2x2 array. Limit Switch Thermistor. Provided with Staged Gas Control option. Located in the heating LST compartment. OAT Outside Air Thermistor. Located in top of the return plenum, attached to roof pole. Return Air Thermistor. RAT Without Economizer: Located on left side base rail in the return plenum. With Economizer: Located on left side face of return damper section in the return plenum. Supply Air Thermistor. Located in the Supply Fan section, on left side of the fan housing. SAT (May be relocated or replaced when unit is used with CCN Linkage systems; see page 60.) Leaving Air Thermistors, provided with Staged Gas Control option. Shipped in the heating LAT 1,2,3 compartment. Installer must pull out and mount in the supply duct. Control Pressure Transducers Building Pressure. Provided with Modulating Power Exhaust, High-Capacity Power Exhaust BP and Return Fan options. Located in the auxiliary control box (left-hand side of unit near return plenum). DPA Discharge Pressure (refrigerant), Circuit A. Located on compressor A1 high-side connections. DPB Discharge Pressure (refrigerant), Circuit B. Located on compressor B1 high-side connections. SPA Suction Pressure (refrigerant), Circuit A. Located on compressor A1 low-side connections. SPB Suction Pressure (refrigerant), Circuit B. Located on compressor B1 low-side connections. Duct Static Pressure. Provided with VAV models equipped with VFD or Inlet Guide Vane options. DSP Located in the auxiliary control box (right-hand side of unit near return plenum). Supply Air Cfm (velocity pressure). Provided with factory-option return fan system FT_SF (sizes 075-105 only). Located in the supply fan compartment, on right side, on vertical post. Return Air Cfm (velocity pressure). Provided with factory-option return fan system FT_RF (sizes 075-105 only). Located in auxiliary control box (right-hand side, filter access panel). Outside Air CFM Outside Air Cfm Monitor (velocity pressure). Provided with the Outside Air Cfm Control option. Control Located in auxiliary control box (right-hand side, filter access panel). CCT PART NO. HH79NZ039 (4) HH79NZ034 HH79NZ039 HH79NZ039 HH79NZ039 HH79NZ034 (3) HK05ZG018 HK05YZ007 HK05YZ007 HK05YZ001 HK05YZ001 HK05ZG010 HK05ZG015 HK05ZG07 50ZZ400290 (030-070) 50ZZ400289 (075-105) LEGEND VAV — Variable Air Volume The ComfortLink controls also support the use of space temperature sensors and can be used with the T55 and T56 sensors. The controls can also be used with CCN communicating T58 room sensor. The T55 and T56 sensors are connected to TB202 terminals 8, 9, and 10. The T58 sensor is connected to the CCN connections on COMM board. Whenever a unit equipped with heat is operated without a thermostat, the user must install the red jumpers from R to W1, and W2 on TB202 for the heat function to work correctly. SPACE CO2 SENSORS — The ComfortLink controls also support a CO2 IAQ sensor that can be located in the space for use in demand ventilation. The sensor must be a 4 to 20 mA sensor and should be connected to TB202 terminals 11 and 12. ECONOMIZER HUMIDITY CHANGEOVER SENSORS — The ComfortLink controls support 5 different changeover systems for the economizer. These are: • Outdoor enthalpy switch • Outdoor air dry bulb • Differential dry bulb • Outdoor air enthalpy curves • Differential enthalpy • Custom curves (a combination of an enthalpy/dewpoint curve and a dry bulb curve). The units are equipped as standard with an outdoor air enthalpy control. Outside air and return air dry bulb sensors which support the dry bulb changeover method are also supplied as standard. If the other methods are to be used, then a field-installed humidity sensor must be installed for outdoor air enthalpy and customer curve control and two humidity sensors must be installed for differential enthalpy. Installation holes are pre-drilled and wire harnesses are installed in every unit for connection of the humidity sensors. The ComfortLink controls have the capability to convert the measured humidity and dry bulb temperature into enthalpy. FAN STATUS SWITCH — The units can be equipped with an optional fan status switch that will monitor the pressure rise across the indoor fans. RETURN AIR CO2 SENSOR — The unit can be equipped with a return air IAQ CO2 sensor that is used for the demand control ventilation. The sensor is located in the return air section and can be accessed from the filter access door. BOARD ADDRESSES — Each board in the system has an address. The MBB has a default address of 1 but it does have an instance jumper that should be set to 1 as shown in Fig. 26. For the other boards in the system there is a 4-dip switch header on each board that should be set as shown below. BOARD RCB ECB SCB CEM SW1 0 1 0 0 SW2 0 0 0 0 SW3 0 0 0 0 SW4 0 0 0 0 0 = On; 1 = Off Accessory Control Components — In addition to the factory-installed options, the units can also be equipped with several field-installed accessories that expand the control features of the unit. The following hardware components can be used as accessories. ROOM THERMOSTATS — The ComfortLink™ controls support a conventional electro-mechanical or electronic thermostat that uses the Y1, Y2, W1, W2, and G signals. The control also supports an additional input for an occupied/ unoccupied command that is available on some new thermostats. The ComfortLink controls can be configured to run with up to 6 stages of capacity. Although the unit can be configured for normal 2-stage control, it is recommended that the multistage control be used. The room thermostat is connected to TB202. 122 to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative and white for the signal ground. Use a similar scheme for cables containing different colored wires. At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network: 1. Turn off power to the control box. 2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.) 3. Connect the red wire to (+) terminal on the COMM board, the white wire to COM terminal on the COMM board, and the black wire to the (–) terminal on the COMM board. 4. The RJ14 CCN connector on the COMM board can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool). 5. Restore power to unit. ACCESSORY NAVIGATOR™ DISPLAY — The accessory handheld Navigator display can be used with the 48/50Z series units. See Fig. 32. The Navigator display operates the same way as the scrolling marquee device. The RCB and ECB boards contain a second LEN port than can be used with the handheld Navigator display. CONTROL MODULE COMMUNICATIONS Red LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs as shown on Fig. 26-29. When operating correctly, the red status LEDs should blink in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Also, be sure that the main base board is supplied with the current software and that all boards are configured on. If necessary, reload current software. If the problem still persists, a board may need to be replaced. A board LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced. Green LED — The boards also have a green LED, which is the indicator of the operation of the LEN communications, which is used for communications between the boards. On the MBB board the Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED that will blink whenever power is on and there is communication occurring. If LEN LED is not blinking, check LEN connections for potential communication errors (J3 and J4 connectors). A 3-wire sensor bus accomplishes communication between modules. These 3 wires run in parallel from module to module. Yellow LED — The MBB has one yellow LED. The Carrier Comfort Network® (CCN) LED will blink during times of network communication. The other boards do not have a CCN communications port. CARRIER COMFORT NETWORK INTERFACE — The 48/50Z Series units can be connected to the CCN if desired. See Fig. 33. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is field supplied and installed. See the Installation Instructions for wiring information. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at the COMM board. See Fig. 16. Consult the CCN Contractor’s Manual for further information. NOTE: Conductors and drain wire must be 20-AWG (American Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/ nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. It is important when connecting to a CCN communication bus that a color-coding scheme be used for the entire network IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus. Co m NA T IM E EWT LW T SETP MO fort VIG Li n k ATO R 12. 54. 58 44. 6 F 4 4 . 01 F F DE Run Statu s Servi ce Te st Temp eratur es Pres sures Setpo ints Inputs Al ar m St atu s Outpu ts Confi gurat ion Time Cloc k Opera ting Mode Alarm s s ENT ESC ER Fig. 32 — Accessory Navigator Display 123 CCN BUS ROOFTOP UNIT ROOFTOP UNIT CL CL BUILDING SUPERVISOR NETWORK OPTIONS ROOFTOP UNIT ROOFTOP UNIT CL CL HEATING/COOLING UNITS REMOTE CCN SITE AUTODIAL GATEWAY TO ADDITIONAL TERMINALS TERMINAL SYSTEM MANAGER CL TCU ROOFTOP UNIT DAV AIR TERMINAL TCU TCU DAV AIR TERMINAL NON CARRIER HVAC EQUIPMENT COMFORT CONTROLLER CCN CL DAV HVAC TCU — — — — — AIR DISTRIBUTION-DIGITAL AIR VOLUME CONTROL (DAV) LEGEND Carrier Comfort Network® ComfortLink™ Controls Digital Air Volume Heating, Ventilation, and Air Conditioning Terminal Control Unit Fig. 33 — CCN System Architecture 124 DAV FAN POWERED MIXING BOX right side of the unit (when facing return air end). See Fig. 37 and 38. All gas system components are in the gas section. MAIN BURNERS (48Z Only) — At the beginning of each heating season, inspect for deterioration due to corrosion or other causes. Observe the main burner flames and adjust if necessary. See Gas System Adjustment section on page 131. FLUE GAS PASSAGEWAYS (48Z Only) — The flue collector box and heat exchanger cells may be inspected by removing heat exchanger access panel, flue box cover, and main burner assembly (Fig. 39). Refer to Main Burners Removal and Replacement section on page 131 for burner removal sequence. If cleaning is required, remove heat exchanger baffles and clean tubes with a wire brush. Use caution with ceramic heat exchanger baffles. When installing retaining clip, be sure the center leg of the clip extends inward toward baffle. See Fig. 40. COMBUSTION-AIR BLOWERS (48Z Only) — Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency. To inspect blower wheel, remove heat exchanger access panel. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel assembly by removing screws holding motor mounting plate to top of combustion fan housing (Fig. 41). The motor and wheel assembly will slide up and out of the fan housing. Remove the blower wheel from the motor shaft and clean with a detergent or solvent. Replace motor and wheel assembly. ECONOMIZER DAMPER MOTOR(S) — On units so equipped, the economizer motor(s) is located in the mixing box section. Access to it is through the door labeled FILTER SECTION. CONDENSER FANS AND FAN MOTORS — Remove the wire fan guard on top of the unit to gain access to the condenser fans and motors. INLET GUIDE VANE MOTOR — The inlet guide vane motor is located on the evaporator-fan sled on the side opposite the fan motor. See Fig. 42A and 42B. Access is through the door labeled FAN SECTION. 25% OUTDOOR-AIR DAMPER — Access to adjust the damper is through the hoods. Remove filters to gain access into unit to adjust linkage arms. MODULATING POWER EXHAUST DAMPER MOTOR — The modulating power exhaust damper motor is located in the return-air end of the unit. SERVICE Service Access — All unit components can be reached through clearly labeled hinged access doors. These doors are not equipped with tiebacks, so if heavy duty servicing is needed, either remove them or prop them open to prevent accidental closure. Each door is held closed with 3 latches. The latches are secured to the unit with a single 1/4-in. –20 x 1/2-in. long bolt. See Fig. 34. To open, loosen the latch bolt using a 7/16-in. wrench. Pivot the latch so it is not in contact with the door. Open the door. To shut, reverse the above procedure. NOTE: Disassembly of the top cover may be required under special service circumstances. It is very important that the orientation and position of the top cover be marked on the unit prior to disassembly. This will allow proper replacement of the top cover onto the unit and prevent rainwater from leaking into the unit. IMPORTANT: After servicing is completed, make sure door is closed and relatched properly, and that the latches are tight. Failure to do this can result in water leakage into the indoor-air section of the unit. COMPRESSORS Sizes 030-050 — Access to the compressors is through the doors on the condenser end of the unit. This door also provides access to the discharge and suction service valves, the crankcase heaters, and the high-pressure and low-pressure switches. Compressor no. 1 is always the compressor on the left when facing main control box. Sizes 055-105 — The oil pump end (compressor access) of each compressor is readily accessible from sides of unit. Access the motor end of the compressor through the condenser end of the unit or by removing compressor. LIQUID SERVICE VALVES, FILTER DRIERS, AND SIGHT GLASSES Sizes 030-050 — Access to these components is through the access panel on the right side of the unit. See Fig. 35. There is also a Schrader port in each suction line that is accessible through this same panel. When charging unit, route service line through the round holes and replace panel to minimize air bypass. Sizes 055-105 — Access to these components is from the side of the unit. SUPPLY-FAN MOTORS, PULLEYS, AND BELTS — Access to these components is through the 2 doors labeled FAN SECTION on each side of the unit. POWER EXHAUST MOTORS, PULLEYS, AND BELTS — Access to these components is through the door below the side economizer hoods on both sides of the unit. See Fig. 36. RETURN AIR FILTERS — Access to these filters is through the door marked FILTER SECTION. UNIT CONTROL BOX — Access to this component is through the doors marked ELECTRICAL SECTION on the condenser end of the unit. GAS HEAT SECTION (48Z Only) — Access to the gas heat section is through the door labeled HEAT SECTION on the IMPORTANT: When replacing panel, be sure to properly secure it in order to prevent water from being drawn into the unit. The motor is accessed through the small door below the side economizer hoods on the left side of the unit. See Fig. 36. RETURN-AIR FILTERS — Access to these filters is through the door marked FILTER SECTION. Filters in upper and lower bag filter tracks can only be removed from the right side of the unit. 125 Fig. 34 — Door Latch NOTE: High heat consists of sections 1 and 2. Low heat consists of section 1 only. Fig. 37 — Gas Section Detail, Sizes 030-050 Fig. 35 — Typical Filter Drier and Liquid Service Valve Access NOTE: High heat consists of sections 1-3. Low heat consists of sections 1 and 2 only. Fig. 36 — Modulating Power Exhaust Motor Access (Both Sides) Fig. 38 — Gas Section Detail, Sizes 055-105 126 INLET GUIDE VANE MOTOR Fig. 42A — Inlet Guide Vane Motor (Sizes 055-070) Fig. 39 — Burner Section Detail CERAMIC BAFFLE CLIP HEAT EXCHANGER TUBES NOTE: One baffle and clip will be in each upper tube of the heat exchanger. Fig. 40 — Removing Heat Exchanger Ceramic Baffles and Clips Fig. 42B — Inlet Guide Vane Motor (Sizes 075-105) Fig. 41 — Combustion Blower Removal 127 1. Turn off unit power. 2. Adjust motor plate so belts can be installed without stretching over the grooves of the pulley. (Forcing the belts can result in uneven belt stretching and a mismatched set of belts.) 3. Before tensioning the belts, equalize belt slack so that it is on the same side of the belt for all belts. Failure to do so may result in uneven belt stretching. 4. Tighten belts using the motor plate adjusting bolts. 5. Adjust until proper belt tension (1/2-in. [13 mm] deflection with one finger centered between pulleys) is obtained. Be sure to adjust both adjusting bolts the same number of turns. NOTE: Check the tension at least twice during the first day of operation, as there is normally a rapid decrease in tension until the belts have run in. Check tension periodically thereafter and keep it at the recommended tension. With the correct belt tension, belts may slip and squeal momentarily on start-up. This slippage is normal and disappears after wheel reaches operating speed. Excessive belt tension shortens belt life and may cause bearing and shaft damage. PULLEY ALIGNMENT — For proper belt life, the motor and fan pulleys must be properly aligned. To check, first turn off unit power. Place a straightedge against the motor and fan pulleys. See Fig. 45. If the pulleys are properly aligned, the straightedge should be parallel to the belts. If they are not parallel, check that the motor shaft and fan shaft are parallel. If they are not, adjust the motor plate adjusting bolts until they are. After verifying that the shafts are parallel, loosen the setscrews on the motor pulley. Move pulley on the shaft until the pulleys are parallel. To move the sheave on the shaft, loosen the belts. If necessary, blower sheave can also be moved on the shaft. INSTALLING REPLACEMENT MOTOR PULLEY (Supply Fan Only) — To install a field-supplied replacement pulley: 1. Turn off unit power. 2. Loosen belts using motor adjusting bolts until belts can be removed without stretching them over the grooves of the pulley. 3. Remove belts. 4. Loosen setscrews on motor pulley. 5. Slide pulley off motor shaft. Make sure setscrews on new pulley are loose. 6. Slide new pulley onto fan shaft and align it with the fan pulley as described in Pulley Alignment section above. 7. Tighten setscrews. 8. Install belts and tension properly as described in Pulley Alignment section above. CONDENSER FAN ADJUSTMENT (All Units Except 050, 070, 075 Units with High-Capacity Evaporator Coil) 1. Turn off unit power. 2. Remove fan guard and loosen fan hub setscrew. 3. See Fig. 46 and adjust fan height using a straight edge laid across the fan deck. 4. Tighten setscrew and replace rubber hubcap to prevent hub from rusting to the motor shaft. Fill hub recess with Permagum if hub has no rubber hubcap. 5. Replace fan guard. Adjustments RETURN/EXHAUST FAN MOTOR PLATE Adjust using a 3/4-in. wrench on the adjusting bolts: 1. Loosen holddown bolts. (See Fig. 43). 2. Turn the adjusting bolts to move the motor mounting plate toward or away from the fan to loosen or tighten the belts. Make the same number of turns to each bolt. 3. Retighten holddown bolts. SUPPLY FAN AND POWER EXHAUST MOTOR PLATE — Adjust using a 15/16-in. wrench on the adjusting bolts: 1. Loosen holddown bolts. (See Fig. 44.) 2. Turn the adjusting bolts to move the motor mounting plate toward or away from the fan to loosen or tighten the belts. Make the same number of turns to each bolt. 3. Retighten holddown bolts. HOLDDOWN BOLTS HOLDDOWN BOLTS Fig. 43 — Return/Exhaust Fan Motor Plate Adjustment Fig. 44 — Motor Plate Adjustment BELT INSTALLATION AND TENSIONING IMPORTANT: When installing or replacing belts, always use a complete set of new, matched belts to prevent potential vibration problems. Mixing belts often results in premature breakage of the new belts. 128 Check for proper rotation of the fan(s) once reinstalled (counterclockwise viewed from above). If necessary to reverse, switch leads at contactor(s) in control box. AIR PRESSURE TRANSDUCER FIELD ADJUSTMENT — All transducers have been factory calibrated and should not require field adjustment. If field adjustment is necessary, follow the instructions below. To re-calibrate a transducer: 1. Shut the unit power off. 2. Take the wiring and pressure tubing off the transducer. Take the transducer out of the unit. 3. Connect a 24-vdc power supply to transducer terminals EXC(+) and COM(–). See Fig. 48. 4. Using a digital multimeter measure the current between terminals EXC(+) and OUT. 5. With both pressure ports open to atmosphere adjust the Zero (Z) screw potentiometer on the transducer and read the multimeter until the desired current output at 0 in. wg pressure is obtained (see Fig. 48). 6. Reinstall the transducer in the unit. 7. Restore power to the unit. Cleaning — Inspect unit at the beginning of each heating and cooling season and during each season as operating conditions may require. Clean condenser coil with a vacuum cleaner, fresh water, compressed air, or a bristle brush (not wire). Coil cleaning should be a part of the planned maintenance program. Clean evaporator coil with a stiff bristle brush (not wire), vacuum cleaner, or compressed air. Check and clean condensate drain annually at the start of the cooling season. Replace return-air filters at the start of each heating and cooling season or as often as necessary during each season, depending on operating conditions. 1. Remove economizer outdoor-air filters from the hoods by removing the filter retainers. 2. Clean filters with steam or hot water and mild detergent. 3. Reinstall filters in hoods after cleaning. Never replace cleanable filters with throwaway filters. Fig. 45 — Pulley Alignment PLASTIC FAN PROPELLER CLEARANCE OF 0.25 INCHES (6.4 MM) FOR STANDARD CONDENSER FANS FAN DECK SURFACE Fig. 46 — Condenser-Fan Adjustment (Standard Units) FAN ORIFICE Fig. 47 — Condenser Fan Position (Units with High Capacity Evaporator Coil Option) CONDENSER FAN ADJUSTMENT (Sizes 050,070,075 With High-Capacity Evaporator Coil Option) — Each fan is supported by a formed wire mount bolted to a fan deck and covered with a wire guard. The exposed end of the fan motor shaft is protected from weather by grease. If the fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan cover, retaining clips, and fan guard. For proper performance, the fans should be positioned as shown in Fig. 47. Tighten setscrews to 14 ± 1 ft-lb (18 ± 1.3 N-m). 129 TRANSDUCER PART NUMBER INPUT RANGE (in. wg) OUTPUT OUTPUT RANGE AT 0 IN. WG HK05ZG019 0-5 4-20 mA 4 mA HK05ZG020 0-1 4-20 mA 4 mA HK05ZG021 0-15 4-20 mA 4 mA –0.25-0.25 4-20 mA 12 mA HK05ZG022 The TXV is set to maintain 10 to 13 F superheat leaving the evaporator coil. It controls the flow of refrigerant to the evaporator coils. USAGE Refrigeration Circuits Supply Duct/ Air Foil Fan Cfm Forward Curved Fan Cfm Return/ Exhaust Fan Cfm Building Pressure PRESSURE PORTS LEAK TESTING — Units are shipped with a full operating charge of R-22 (see unit nameplate). If there is no pressure in the system, introduce enough nitrogen to search for the leak. Repair the leak using good refrigeration practices. After leaks are repaired, system must be evacuated and dehydrated using methods described in GTAC II, Module 4, System Dehydration. REFRIGERANT CHARGE (Refer to Unit Nameplate) — At the liquid line connection point on each circuit is a factoryinstalled liquid line service valve. On each valve is a 1/4-in. Schrader connection for charging liquid refrigerant. All units are shipped with a complete operating charge of R-22. See unit nameplate and for amount of charge. When adding a complete charge, evacuate system using standard evacuating procedures and weigh in the specified amount of charge. All units use the same charging chart. See Fig. 49. Charging with Unit Off and Evacuated — Close liquid line service valve before charging. Weigh in charge shown in unit nameplate. Open liquid line service valve; start unit and allow it to run several minutes fully loaded. Check for a clear sight glass. Be sure clear condition is liquid and not vapor. Complete charging the unit. Charging with Unit Running — If charge is to be added while unit is operating, it is necessary to have all condenser fans and compressors operating. It may be necessary to block condenser coils at low-ambient temperatures to raise condensing pressure to approximately 280 psig to turn all condenser fans on. Do not totally block a coil to do this. Partially block all coils in uniform pattern. Charge vapor into compressor low-side service port located above oil pump crankshaft housing. Charge each circuit until sight glass shows clear liquid. HIGH LOW COM OUT S EXC Z Fig. 48 — Transducer Details Lubrication COMPRESSORS — Each compressor is correctly charged at the factory. Refer to 06D and 06E Compressor Service Manuals if additional information regarding compressor lubrication system is required. FAN SHAFT BEARINGS — Lubricate fan shaft bearings at least once a year with suitable bearing grease. Extended grease lines are provided on pulley side of blower. Typical lubricants are given below: MANUFACTURER Texaco Mobil Sunoco Texaco Oil Charge — All units are factory charged with oil. Acceptable oil level for each compressor is shown in Table 96. When additional oil or a complete charge is required, use only Carrier-approved compressor oil. Approved oils are: Petroleum Specialties, Inc. — Cryol 150A (factory oil charge) Texaco, Inc. — Capella WF-32-150 Witco Chemical Co. — Suniso 3GS Do not reuse drained oil, and do not use any oil that has been exposed to atmosphere as oil is highly hygroscopic and rapidly absorbs moisture. ADD OIL — Close suction shutoff valve and pump down crankcase to 2 psig. (Low-pressure cutout must be jumpered.) Wait a few minutes and repeat until pressure remains steady at 2 psig. Remove oil fill plug above the oil level sight glass, add oil through plug hole, and replace plug. Run compressor for 20 minutes and check oil level. REMOVE OIL — Pump down compressor to 2 psig. Loosen the 1/4-in. pipe plug at the compressor base and allow the oil to seep out past the threads of the plug. NOTE: The crankcase will be slightly pressurized. Do not remove the plug, or the entire oil charge will be lost. Small amounts of oil can be removed through the oil pump discharge connection while the compressor is running. LUBRICANT Regal AFB-2* Mobilplex EP No. 1 Prestige 42 Multifak 2 *Preferred lubricant because it contains rust and oxidation inhibitors. INLET GUIDE VANE BEARINGS (Units With Optional Inlet Guide Vanes) — These bearings are oil impregnated. Lubricate annually with a few drops of nondetergent SAE (Society of Automotive Engineers) 20 oil. FAN MOTOR BEARINGS — The condenser-fan and evaporator-fan motors have sealed bearings so no field lubrication is required. DOOR HINGES — All door hinges should be lubricated at least once a year. Refrigerant Feed Components — Each refrigerant circuit (2 per unit) has all the necessary refrigerant controls. Table 96 — Oil Charge Thermostatic Expansion Valve (TXV) — On sizes 030 and 035, each circuit has one TXV. On size 040 and 050, each circuit has 2. The superheat is nonadjustable. On sizes 055-105, each circuit has 2 TXVs on which superheat may be adjusted if necessary. Adjustment is not normally required or recommended. COMPRESSOR 06D 06E 299 All other 06E 130 OIL CHARGE (Pints) 10.0 19.0 20.0 CHARGING CHART BOTH CIRCUITS ALL OUTDOOR FANS MUST BE OPERATING INLET PRESSURE TAP (ON SIDE) 1/8-IN. 27 NPT Liquid Temperature at Liquid Valve (deg F) 140 120 OUTLET PRESSURE TAP (ON SIDE) 1/8-IN. 27 NPT Add Charge if Above Curve 100 Reduce Charge if Below Curve 80 LOW-FIRE REGULATOR HIGH-FIRE REGULATOR ADJUSTMENT SCREW ADJUSTMENT SCREW 60 Fig. 50 — Gas Valve Moisture/Liquid Indicator — A clear flow of liquid refrigerant indicates sufficient charge in the system. Bubbles indicate undercharged system or the presence of noncondensables. Moisture in the system measured in parts per million (ppm) changes the color of the indicator: Green — moisture below 45 ppm (dry) Chartreuse — 45 to 130 ppm (caution!) Yellow — moisture above 130 ppm (wet) Change filter driers at the first sign of moisture in the system. See Carrier Charging Handbook for more information. 40 50 100 150 200 250 300 350 400 Liquid Pressure at Liquid Valve (PSIG) Fig. 49 — Charging Chart — 48/50Z030-105 Units Gas System Adjustment (48Z Only) GAS VALVE ADJUSTMENT — The gas valve opens and closes in response to the unit control. When power is supplied to valve terminals D1 and C2, the main valve opens to its preset position. The regular factory setting is stamped on the valve body (3.3 in. wg). To adjust regulator: 1. Set thermostat at setting for no call for heat. 2. Switch main gas valve to OFF position. 3. Remove 1/8-in. pipe plug from manifold or gas valve pressure tap connection. Install a suitable pressuremeasuring device. 4. Switch main gas valve to ON position. 5. Set thermostat at setting to call for heat. 6. Remove screw cap covering regulator adjustment screw (see Fig. 50). 7. Turn adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. 8. Once desired pressure is established, set thermostat setting for no call for heat, turn off main gas valve, remove pressure-measuring device, and replace 1/8-in. pipe plug and screw cap. MAIN BURNERS — For all applications, main burners are factory set and should require no adjustment. MAIN BURNER REMOVAL AND REPLACEMENT 1. Shut off (field-supplied) manual main gas valve. 2. Shut off power to unit. 3. Remove gas section access door, door frame, and corner post. 4. Disconnect gas piping from gas valve inlet. 5. Remove wires from gas valve. 6. Remove wires from rollout switch. 7. Remove sensor wire and ignitor cable form IGC board. 8. Remove 2 screws securing manifold bracket to basepan. 9. Remove 2 screws that hold the burner support plate flange to the vestibule plate. 10. Lift burner assembly out of unit. 11. Replace burner assembly. Reinstall by reversing Steps 1 to 10. IMPORTANT: Unit must be in operation at least 12 hours before moisture indicator can give an accurate reading. With unit running, indicating element must be in contact with liquid refrigerant to give a true reading. Filter Drier — Replace whenever the moisture/liquid indicator shows moisture in the system. Liquid Line Service Valve — Located immediately ahead of the filter drier, this valve has a 1/4-in. flare connection for field charging. With the liquid circuit shut, the compressor can be used to pump the refrigerant down into the high side. The refrigerant can then be stored there by closing the compressor discharge valve. Compressor Discharge Service Valve — Each compressor has one. Compressor Suction Service Valve — Each compressor has one. Protective Devices COMPRESSOR PROTECTION Overcurrent — Each compressor has one manual reset, calibrated trip, magnetic circuit breaker. Do not bypass connections or increase the size of the circuit breaker to correct trouble. Determine the cause and correct it before resetting the breaker. Overtemperature — Each 06D compressor has an internal protector to protect it against excessively high discharge gas temperatures. Each 06E compressor has an external discharge gas thermostat. See Fig. 51. They will reset, but the circuit will automatically be locked out by the control board. Unit must be manually reset by interrupting control power. Crankcase Heater — Each compressor has a crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. Since 115-v power for the crankcase heaters is drawn from the unit control circuit, main unit power must be on for the heaters to be energized. 131 LIMIT SWITCH THERMISTOR (Staged Gas Unit Only) — The limit switch thermistor is a factory-installed component. It is located next to the lower limit switch. The limit switch thermistor senses temperature at limit switch location and prevents the limit from tripping while the unit is operating at low airflow. ROLLOUT SWITCH — This switch senses any flame or excessive heat in the main burner compartment and deenergizes the gas valve. If this occurs, the gas heating system is locked out (7 flashes on IGC board) until the rollout switch is reset manually. Reset rollout switch manually by powering down and powering up of the unit. When the rollout switch trips, it usually indicates a flue blockage. Inspect the unit for any obstruction in the flue system, for holes in the flue box, a defective hall effect sensor, a defective inducer motor, or a loose combustion blower. IMPORTANT: After a prolonged shutdown or service job, energize the crankcase heaters for 24 hours before starting the compressor. EVAPORATOR-FAN MOTOR PROTECTION — A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature. They are also protected against a severe overcurrent condition by manual reset, calibrated trip, magnetic circuit breakers on a common circuit. As with the circuit breakers, do not bypass connections or increase breaker size to correct trouble. Determine the cause and correct it before resetting the breaker. HIGH-PRESSURE SWITCHES — See Fig. 51 for compressor mounting locations. Settings for these switches are shown in Tables 97A and 97B. If either switch trips, that refrigerant circuit will be automatically locked out by the controls. To reset, recycle control power to unit. Compressor Removal — Access to the pump end of the compressor is from the compressor side of the unit. Access to the motor end of the compressor is from the inside of the unit. All compressors can be removed from the compressor side of the unit. IMPORTANT: All compressor mounting hardware and support brackets removed during servicing must be reinstalled prior to start-up. Table 97A — Pressure Switch Settings (psig) SWITCH High CUTOUT 426 ± 7 CUT-IN 320 ± 20 1. Disconnect power to unit; lockout power to compressor. 2. Close suction and discharge service valves. 3. Relieve refrigerant pressure into a refrigerant recovery system. 4. Remove: a. Fan-cycling pressure switch (FCPS) b. High-pressure switch 5. Disconnect power wires at terminal box and disconnect conduit. 6. Disconnect wires from crankcase heater. 7. Disconnect service valves from compressor. 8. Remove 4 locknuts securing compressor to the spring assemblies. 9. Lift compressor off mounting bolts and remove. Table 97B — Pressure Switch Settings (Pa) SWITCH High CUTOUT 2937 ± 48 CUT-IN 2206 ± 138 Relief Devices — All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side. Control Circuit, 115 V — This control circuit is protect- ed against overcurrent by a 5-amp (sizes 030-090) or 9-amp (size 105) circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. Control Circuit, 24 V — This control circuit is protected against overcurrent by a 3.2-amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. Compressor Replacement — Perform the following: Gas Heat (48Z Only) 1. Reverse procedure in Compressor Removal section to end of Step 4. 2. Reinstall service valves and safety switches, and tighten to torques as listed: LIMIT SWITCHES — The maximum supply-air temperature is controlled by a limit switch located in the gas section. The limit is designed to trip at 100 F above the maximum temperature rise. When the limit trips, 2 flashes occur on the IGC board. The gas valve is deenergized. After cooling, the system will reset and fires gas again. If four trips occur, the system shuts down into Lockout and 4 flashes occur on the IGC board. The system must then be manually reset by power down and power up of the unit. TORQUE COMPRESSOR(S) Tighten discharge valves to — 20-25 ft-lb (27- 34 N-m) 06E-250, 06D-537 80-90 ft-lb (109-122 N-m) 06E-265,275,299 Tighten suction valves to — 80- 90 ft-lb (109-122 N-m) 06E-250, 06D-537 90-120 ft-lb (122-163 N-m) 06E-265,275,299 Tighten the following fittings as specified — 120 in.-lb (13.5 N-m) High-Pressure Switch 3. Leak-check and evacuate system, recover refrigerant. 4. Recharge system per pre-start-up and start-up sequences. Recheck oil levels. 5. Energize crankcase heater for 24 hours prior to restart of system. Fig. 51 — Typical Compressor Overtemperature and High-Pressure Switch Locations 132 APPENDIX A — LOCAL DISPLAY TABLES MODE — RUN STATUS ITEM VIEW →HVAC →OCC →MAT →EDT →LAT →EC.C.P →ECN.P →EC2.P →CL.C.P →C.CAP →CL.ST →HT.C.P →HT.ST →H.MAX ECON →ECN.P →EC2.P →ECN.C →ACTV →DISA →DISA→UNV.1 →DISA→UNV.2 →DISA→ENTH →DISA→DBC →DISA→DEW →DISA→DDBC →DISA→OAEC →DISA→DEC →DISA→EDT →DISA→OAT →DISA→FORC →DISA→SFON →DISA→CLOF →DISA→OAQL →DISA→HELD →DISA→DH.DS →O.AIR →O.AIR→OAT →O.AIR→OA.RH →O.AIR→OA.E →O.AIR→OA.D.T COOL →C.CAP →CUR.S →REQ.S →MAX.S →DEM.L →SUMZ →SUMZ→SMZ →SUMZ→ADD.R →SUMZ→SUB.R →SUMZ→R.PCT →SUMZ→Y.MIN →SUMZ→Y.PLU →SUMZ→Z.MIN →SUMZ→Z.PLU →SUMZ→H.TMP →SUMZ→L.TMP →SUMZ→PULL →SUMZ→SLOW TRIP →UN.C.S →UN.C.E →OC.C.S →OC.C.E →TEMP →OC.H.E →OC.H.S →UN.H.E →UN.H.S →HVAC LINK →MODE →L.Z.T →L.C.SP →L.H.SP HRS →HR.A1 →HR.A2 →HR.B1 →HR.B2 STRT →ST.A1 →ST.A2 →ST.B1 →ST.B2 VERS →MBB →RCB →ECB →SCB →CEM →ECON →IGV →HUMD →HEAT →BP1 →BP2 →MARQ →NAVI EXPANSION AUTO VIEW OF RUN STATUS ascii string spelling out the hvac modes Occupied ? Mixed Air Temperature Evaporator Discharge Tmp Leaving Air Temperature Economizer Control Point Economizer Act.Curr.Pos. Economzr Act.Curr.Pos. Cooling Control Point Current Running Capacity Requested Cool Stage Heating Control Point Requested Heat Stage Maximum Heat Stages ECONOMIZER RUN STATUS Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. Economizer Active ? ECON DISABLING CONDITIONS Econ Act. Unavailable? Econ2 Act. Unavailable? Enth. Switch Read High ? DBC - OAT Lockout? DEW - OA Dewpt.Lockout? DDBD- OAT > RAT Lockout? OAEC- OA Enth Lockout? DEC - Diff.Enth.Lockout? EDT Sensor Bad? OAT Sensor Bad ? Economizer Forced ? Supply Fan Not On 30s ? Cool Mode Not In Effect? OAQ Lockout in Effect ? Econ Recovery Hold Off? Dehumid. Disabled Econ.? OUTSIDE AIR INFORMATION Outside Air Temperature Outside Air Rel. Humidity Outside Air Enthalpy OutsideAir Dewpoint Temp COOLING INFORMATION Current Running Capacity Current Cool Stage Requested Cool Stage Maximum Cool Stages Active Demand Limit COOL CAP. STAGE CONTROL Capacity Load Factor Next Stage EDT Decrease Next Stage EDT Increase Rise Per Percent Capacity Cap Deadband Subtracting Cap Deadband Adding Cap Threshold Subtracting Cap Threshold Adding High Temp Cap Override Low Temp Cap Override Pull Down Cap Override Slow Change Cap Override MODE TRIP HELPER Unoccup. Cool Mode Start Unoccup. Cool Mode End Occupied Cool Mode Start Occupied Cool Mode End Ctl.Temp RAT,SPT or Zone Occupied Heat Mode End Occupied Heat Mode Start Unoccup. Heat Mode End Unoccup. Heat Mode Start ascii string spelling out the hvac modes CCN - LINKAGE Linkage Active - CCN Linkage Zone Control Tmp Linkage Curr. Cool Setpt Linkage Curr. Heat Setpt COMPRESSOR RUN HOURS Compressor A1 Run Hours Compressor A2 Run Hours Compressor B1 Run Hours Compressor B2 Run Hours COMPRESSOR STARTS Compressor A1 Starts Compressor A2 Starts Compressor B1 Starts Compressor B2 Starts SOFTWARE VERSION NUMBERS CESR131292-xx-xx CESR131249-xx-xx CESR131249-xx-xx CESR131226-xx-xx CESR131174-xx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx xx-xx-xxx-xxx-xx CESR131171-xx-xx CESR130227-xx-xx RANGE UNITS YES/NO 0-100 0-100 dF dF dF dF % % dF dF 0-100 0-100 0-100 YES/NO % % % YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO dF % % 0-999999 0-999999 0-999999 0-999999 ECONOPOS ECON2POS ECONOCMD ECACTIVE OAT OARH OAE OADEWTMP CAPTOTAL COOL_STG CL_STAGE CLMAXSTG DEM_LIM forcible forcible forcible forcible 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 90,92 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 69,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 92,93 UCCLSTRT UCCL_END OCCLSTRT OCCL_END CTRLTEMP OCHT_END OCHTSTRT UCHT_END UCHTSTRT string 93 93 93 93 93 93 93 93 93 93 dF dF dF MODELINK LZT LCSP LHSP 94 94 94 94 HRS HRS HRS HRS HOURS_A1 HOURS_A2 HOURS_B1 HOURS_B2 config config config config 94 94 94 94 CY_A1 CY_A2 CY_B1 CY_B2 config config config config 94 94 94 94 ^F ^F string string string string string string string string string string string string string 133 forcible PAGE NO. SMZ ADDRISE SUBRISE RISE_PCT Y_MINUS Y_PLUS Z_MINUS Z_PLUS HI_TEMP LOW_TEMP PULLDOWN SLO_CHNG ON/OFF 0-999999 0-999999 0-999999 0-999999 string OCCUPIED MAT EDT LAT ECONCPNT ECONOPOS ECON2POS COOLCPNT CAPTOTAL CL_STAGE HEATCPNT HT_STAGE HTMAXSTG WRITE STATUS ECONUNAV ECN2UNAV ENTH DBC_STAT DEW_STAT DDBCSTAT OAECSTAT DEC_STAT EDT_STAT OAT_STAT ECONFORC SFONSTAT COOL_OFF OAQLOCKD ECONHELD DHDISABL dF % -100 → +100 CCN POINT 94 94 94 94 94 94 94 94 94 94 94 94 94 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — SERVICE TEST ITEM TEST STOP S.STP FAN.F INDP →HUM.R →ALRM FANS →F.MOD →E.POS →S.FAN →I.POS →S.VFD →P.E.1 →P.E.2 →BP1.P →BP2.P →E.VFD →CD.F.A →CD.F.B →CD.MM ACT.C →ECN.C →E.CAL →ECN.A →EC2.C →E2.CL →EC2.A →IGV.C →I.CAL →IGV.A →IGV.M →BP1.C →B1.CL →BP1.A →BP1.M →BP2.C →B2.CL →BP2.A →BP2.M →HTC.C →HT.CL →HTC.A →HMD.C →HM.CL →HMD.A COOL →E.POS →SP.SP →CL.ST →LD.LG →A1 →U1.A1 →U2.A1 →A2 →B1 →U1.B1 →U2.B1 →B2 HEAT →HT.ST →HT.1 →HT.2 →HT.3 →HT.4 →HT.5 →HT.6 →H.I.R →HTC.C EXPANSION Service Test Mode Local Machine Disable Soft Stop Request Supply Fan Request TEST INDEPENDENT OUTPUTS Humidifier Relay Remote Alarm / Aux Relay TEST FANS Fan Test Automatic? Econo Damper Command Pos Supply Fan Relay IGV Actuator Command Pos Supply Fan VFD Speed Power Exhaust Relay 1 Power Exhaust Relay 2 BP 1 Command Position BP 2 Command Position Exhaust Fan VFD Speed Condenser Fan Circuit A Condenser Fan Circuit B Motormaster Condensr Fan CALIBRATE TEST-ACTUATORS Economizer Act.Cmd.Pos. Economizer Calibrate Cmd Econ Act. Control Angle Economzr 2 Act.Cmd.Pos. Economzr 2 Calibrate Cmd Econ2 Act. Control Angle IGV Actuator Command Pos IGV Act. Calibrate Cnd IGV Act. Control Angle VFD-IGV Maximum Speed BP 1 Command Position BP 1 Actuator Cal Cmd BP Act.1 Control Angle BP 1 Actuator Max Pos. BP 2 Command Position BP 2 Actuator Cal Cmd BP Act.2 Control Angle BP 2 Actuator Max Pos. Ht.Coil Command Position Heating Coil Act. Cal.Cmd Heat Coil Act.Ctl.Angle Humidifier Command Pos. Humidifier Act. Cal.Cmd Humidifier Act.Ctrl.Ang. TEST COOLING Econo Damper Command Pos Static Pressure Setpoint Requested Cool Stage Lead/Lag Select Test Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay TEST HEATING Requested Heat Stage Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay Ht.Coil Command Position RANGE ON/OFF YES/NO YES/NO YES/NO UNITS ON/OFF ON/OFF YES/NO % ON/OFF 0-100 0-100 ON/OFF ON/OFF 0-100 0-100 0-100 ON/OFF ON/OFF ON/OFF % % % % % 0-100 YES/NO read only 0-100 YES/NO read only 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 YES/NO read only % % % % % % % % % % 0-100 0-5 0-n LEAD/LAG ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-n ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-100 % "H2O % 134 CCN POINT MAN_CTRL UNITSTOP SOFTSTOP SFANFORC WRITE STATUS config forcible forcible PAGE NO. 36,37 36,37 36,37 36,37 HUMR_TST ALRM_TST 37 37 FANAUTO ECONFANS SFAN_TST IGVFNTST SGVFDTST PE1_TST PE2_TST BLDPTST1 BLDPTST2 EFVFDTST CNDA_TST CNDB_TST PCFABTST 37,38 37 37 37 37 37 37 37 37 37 37 37 37 ECONOTST ECONOCAL ECONCANG ECON2TST ECON2CAL ECN2CANG SPIGVTST IGV_CAL IGC_CANG STATPMAX BLDG1TST BLDG1CAL BP1_CANG BP1SETMX BLDG2TST BLDG2CAL BP2_CANG BP2SETMX HTCLACTC HCOILCAL HTCLCANG HUMD_TST HUMIDCAL HUMDCANG 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 ECONCOOL SPSP_TST CLST_TST LL_TST CMPA1TST UNL1_TST UNL2_TST CMPA2TST CMPB1TST UNL3_TST UNL4_TST CMPB2TST 37,38 37,38 37,38 37,38 37,38 37 37 37 37 37 37 37 HTST_TST HS1_TST HS2_TST HS3_TST HS4_TST HS5_TST HS6_TST HIR_TST HTCLHEAT 37,38 37,38 37,38 37,38 37,38 37,38 37,38 37,38 37,38 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — TEMPERATURES ITEM AIR.T →CTRL →CTRL→EDT →CTRL→LAT →CTRL→MAT →CTRL→R.TMP →CTRL→S.TMP →SAT →OAT →RAT →SPT →SPTO →CCT →S.G.LS →S.G.L1 →S.G.L2 →S.G.L3 →S.G.LM REF.T →SCT.A →SST.A →SCT.B →SST.B EXPANSION AIR TEMPERATURES CONTROL TEMPS Evaporator Discharge Tmp Leaving Air Temperature Mixed Air Temperature Controlling Return Temp Controlling Space Temp Air Tmp Lvg Supply Fan Outside Air Temperature Return Air Temperature Space Temperature Space Temperature Offset Air Temp Lvg Evap Coil Staged Gas LAT Sum Staged Gas LAT 1 Staged Gas LAT 2 Staged Gas LAT 3 Staged Gas Limit Sw.Temp REFRIGERANT TEMPERATURES Cir A Sat.Condensing Tmp Cir A Sat.Suction Temp. Cir B Sat.Condensing Tmp Cir B Sat.Suction Temp. RANGE -40 - 240 -40 - 240 UNITS CCN POINT dF dF dF dF dF dF dF dF dF ^F dF dF dF dF dF dF EDT LAT MAT RETURN_T SPACE_T SAT OAT RAT SPT SPTO CCT LAT_SGAS LAT1SGAS LAT2SGAS LAT3SGAS LIMSWTMP dF dF dF dF SCTA SSTA SCTB SSTB WRITE STATUS forcible forcible forcible forcible forcible forcible MODE — PRESSURES ITEM AIR.P →SP →BP REF.P →DP.A →SP.A →DP.B →SP.B EXPANSION AIR PRESSURES Static Pressure Building Pressure REFRIGERANT PRESSURES Cir A Discharge Pressure Cir A Suction Pressure Cir B Discharge Pressure Cit B Suction Pressure RANGE UNITS CCN POINT "H2O "H2O SP BP PSIG PSIG PSIG PSIG DP_A SP_A DP_B SP_B WRITE STATUS MODE — SETPOINTS ITEM OHSP OCSP UHSP UCSP GAP V.C.ON V.C.OF SASP SA.HI SA.LO SA.HT T.PRG T.CL T.V.OC T.V.UN EXPANSION Occupied Heat Setpoint Occupied Cool Setpoint Unoccupied Heat Setpoint Unoccupied Cool Setpoint Heat-Cool Setpoint Gap VAV Occ. Cool On Delta VAV Occ. Cool Off Delta Supply Air Setpoint Supply Air Setpoint Hi Supply Air Setpoint Lo Heating Supply Air Setpt Tempering Purge SASP Tempering in Cool SASP Tempering Vent Occ SASP Tempering Vent Unocc. SASP RANGE 40-99 40-99 40-99 40-110 2-10 0-25 1-25 45-75 45-75 45-75 80-120 -20-80 5-75 -20-80 -20-80 135 UNITS dF dF dF dF deltaF deltaF deltaF dF dF dF dF dF dF dF dF CCN POINT OHSP OCSP UHSP UCSP HCSP_GAP VAVOCON VAVOCOFF SASP SASP_HI SASP_LO SASPHEAT TEMPPURG TEMPCOOL TEMPVOCC TEMPVUNC DEFAULT 68 75 55 90 5 3.5 2 55 55 60 85 50 5 65 50 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — INPUTS ITEM GEN.I →FLT.S →G.FAN →REMT →ENTH →S.FN.S →FRZ.S →PP.SW →DL.S1 →DL.S2 →DH.IN FD.BK →HPS.A →HPS.B →CS.A1 →CS.A2 →CS.B1 →CS.B2 STAT →G →W1 →W2 →Y1 →Y2 FIRE →FSD →PRES →EVAC →PURG REL.H →OA.RH →OA.EN →OA.DP →RA.RH →RA.EN →SP.RH →SP.EN AIR.Q →IAQ.I →IAQ →OAQ →DAQ →IQ.P.O CFM →O.CFM →R.CFM →S.CFM →D.CFM RSET →SA.S.R →SP.RS 4-20 →IAQ.M →OAQ.M →SP.R.M →DML.M →EDR.M →ORH.M →SRH.M →RRH.M →SAC.M →SA.M.T →RAC.M →RA.M.T →OAC.M →OA.M.T →BP.M →BP.M.T →SP.M →SP.M.T EXPANSION GENERAL INPUTS Filter Status Input Fan Request From IGC Remote Input State Enth. Switch Read High ? Supply Fan Status Switch Freeze Status Switch Plenum Press.Safety Sw. Demand Limit Switch 1 Demand Limit Switch 2 Dehumidify Switch Input COMPRESSOR FEEDBACK Circ A High Press. Switch Circ B High Press. Switch Compressor A1 Feedback Compressor A2 Feedback Compressor B1 Feedback Compressor B2 Feedback THERMOSTAT INPUTS Thermostat G Input Thermostat W1 Input Thermostat W2 Input Thermostat Y1 Input Thermostat Y2 Input FIRE-SMOKE INPUTS Fire Shutdown Input Pressurization Input Evacuation Input Smoke Purge Input RELATIVE HUMIDITY Outside Air Rel. Humidity Outdoor Air Enthalpy OutsideAir Dewpoint Temp Return Air Rel. Humidity Return Air Enthalpy Space Relative Humidity Space Enthalpy AIR QUALITY SENSORS IAQ - Discrete Input IAQ - PPM Return CO2 OAQ - PPM Return CO2 Diff.Air Quality in PPM IAQ Min.Pos. Override CFM SENSORS Outside Air CFM Return Air CFM Supply Air CFM Fan Track Control D.CFM RESET INPUTS Supply Air Setpnt. Reset Static Pressure Reset 4-20 MILLIAMP INPUTS IAQ Milliamps OAQ Milliamps SP Reset milliamps 4-20 ma Demand Signal EDT Reset Milliamps OARH Milliamps SPRH Milliamps RARH Milliamps SACFM Milliamps Supply Air CFM Trim (ma) RACFM Milliamps Return Air CFM Trim (ma) OACFM Milliamps Outside Air CFM Trim(ma) BP Milliamps Bldg. Pressure Trim (ma) SP Milliamps Static Press. Trim (ma) RANGE UNITS CCN POINT WRITE STATUS DRTY/CLN ON/OFF * YES/NO ON/OFF ALRM/NORM HIGH/LOW ON/OFF ON/OFF ON/OFF FLTS IGCFAN RMTIN ENTH SFS FRZ PPS DMD_SW1 DMD_SW2 DHDISCIN HIGH/LOW HIGH/LOW ON/OFF ON/OFF ON/OFF ON/OFF CIRCAHPS CIRCBHPS CSB_A1 CSB_A2 CSB_B1 CSB_B2 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF G W1 W2 Y1 Y2 forcible forcible forcible forcible forcible ALRM/NORM ALRM/NORM ALRM/NORM ALRM/NORM FSD PRES EVAC PURG forcible forcible forcible forcible OARH OAE OADEWTMP RARH RAE SPRH SPE forcible % dF % % HIGH/LOW -2.0 → 2.0 -2.0 → 2.0 -2.0 → 2.0 -2.0 → 2.0 -2.0 → 2.0 % IAQIN IAQ OAQ DAQ IAQMINOV CFM CFM CFM CFM OACFM RACFM SACFM DELTACFM ^F SASPRSET SPRESET ma ma ma ma ma ma ma ma ma IAQ_MA OAQ_MA SPRST_MA DMDLMTMA EDTRESMA OARH_MA SPRH_MA RARH_MA SACFM_MA SAMATRIM RACFM_MA RAMATRIM OACFM_MA OAMATRIM BP_MA BPMATRIM SP_MA SPMATRIM ma ma ma ma forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible config config config config *The display text changes depending on the remote switch configuration (Configuration→UNIT→RM.CF). If RM.CF is set to 0 (No Remote Switch), then the display text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.” 136 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — OUTPUTS ITEM FANS →S.FAN →S.VFD →E.VFD →P.E.1 →P.E.2 →CD.F.A →CD.F.B →CD.MM COOL →A1 →U1.A1 →U2.A1 →A2 →B1 →U1.B1 →U2.B1 →B2 HEAT →HT.1 →HT.2 →HT.3 →HT.4 →HT.5 →HT.6 →H.I.R →HTC.P ACTU →ECN.P →EC2.P →ECN.C →IGV.P →IGV.C →BP1.P →BP1.C →BP2.P →BP2.C →HTC.P →HTC.C →HMD.P →HMD.C GEN.O →HUM.R →ALRM EXPANSION FANS Supply Fan Relay Supply Fan VFD Speed Exhaust Fan VFD Speed Power Exhaust Relay 1 Power Exhaust Relay 2 Condenser Fan Circuit A Condenser Fan Circuit B Motormaster Condensr Fan COOLING Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay HEATING Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay Ht.Coil Act.Current Pos. ACTUATORS Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. IGV Actuator Current Pos IGV Actuator Command Pos BP 1 Actuator Curr.Pos. BP 1 Command Position BP 2 Actuator Curr.Pos. BP 2 Command Position Ht.Coil Act.Current Pos. Ht.Coil Command Position Humidifier Act.Curr.Pos. Humidifier Command Pos. GENERAL OUTPUTS Humidifier Relay Remote Alarm / Aux Relay RANGE ON/OFF 0-100 0-100 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF UNITS CCN POINT WRITE STATUS SFAN SFAN_VFD EFAN_VFD PE1 PE2 CONDFANA CONDFANB PULSCFAB % % ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF CMPA1 UNL_1_A1 UNL_2_A1 CMPA2 CMPB1 UNL_1_B1 UNL_2_B1 CMPB2 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-100 % HS1 HS2 HS3 HS4 HS5 HS6 HIR HTCLRPOS 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 % % % % % % % % % % % % % ECONRPOS ECON2POS ECONOCMD IGV_RPOS IGV_CPOS BP1_RPOS BP1_CPOS BP2_RPOS BP2_CPOS HTCLRPOS HTCLCPOS HUMDRPOS HUMDCPOS ON/OFF ON/OFF forcible forcible HUMIDRLY ALRM forcible MODE — CONFIGURATION ITEM UNIT →C.TYP →CV.FN →RM.CF →CEM →TCS.C →TCS.H →SFS.S →SFS.M →VAV.S →SIZE →50.HZ →MAT.S →MAT.R →MAT.D →ALTI →DLAY →AUX.R →SENS →SENS→SPT.S →SENS→SP.O.S →SENS→SP.O.R →SENS→SRH.S →SENS→RRH.S →SENS→FLT.S COOL →Z.GN →MC.LO →L.L.EN →M.M. →HPSP →A1.EN →A2.EN →B1.EN →B2.EN →CS.A1 →CS.A2 →CS.B1 →CS.B2 →HPS.A →HPS.B →H.SST EXPANSION UNIT CONFIGURATION Machine Control Type Fan Mode (0=Auto, 1=Cont) Remote Switch Config CEM Module Installed Temp.Cmp.Strt.Cool Factr Temp.Cmp.Strt.Heat Factr Fan Fail Shuts Down Unit Fan Stat Monitoring Type VAV Unocc.Fan Retry Time Unit Size (30-105) 50 Hertz Unit ? MAT Calc Config Reset MAT Table Entries? MAT Outside Air Default Altitude……..in feet: Startup Delay Time Auxiliary Relay Config INPUT SENSOR CONFIG Space Temp Sensor Space Temp Offset Sensor Space Temp Offset Range Space Air RH Sensor Return Air RH Sensor Filter Stat.Sw.Enabled ? COOLING CONFIGURATION Capacity Threshold Adjst Compressor Lockout Temp Lead/Lag Operation ? Motor Master Control ? Head Pressure Setpoint Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 CSB A1 Feedback Alarm CSB A2 Feedback Alarm CSB B1 Feedback Alarm CSB B2 Feedback Alarm CMPA1 Hi.Pr.Sw. Trip CMPB1 Hi.Pr.Sw. Trip Hi SST Alert Delay Time RANGE 1 - 6 (multi-text strings) 0 - 1 (multi-text strings) 0 - 3 (multi-text strings) Yes/No 0 - 60 0 - 60 Yes/No 0 - 2 (multi-text strings) 0 - 720 30 - 105 Yes/No 0 - 2 (multi-text strings) Yes/No 0 -100 0 - 60000 0 -900 0 - 3 (multi-text strings) UNITS min min min % secs Enable/Disable Enable/Disable 1 - 10 Enable/Disable Enable/Disable Enable/Disable -10 - 10 -25 - 55 Yes/No Yes/No 80 - 150 Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable 365 - 415 365 - 415 5 - 30 137 dF dF PSIG PSIG min CCN POINT DEFAULT PAGE NO. CTRLTYPE FAN_MODE RMTINCFG CEM_BRD TCSTCOOL TCSTHEAT SFS_SHUT SFS_MON SAMPMINS UNITSIZE UNIT_HZ MAT_SEL MATRESET MATOAPOS ALTITUDE DELAY AUXRELAY 4 1 0 No 0 0 No 0 50 30 No 1 No 20 0 0 0 42,44 44 44 44 44 44 44 44 44 44 44,45 44,45 44,45 44,45 44,45 SPTSENS SPTOSENS SPTO_RNG SPRHSENS RARHSENS FLTS_ENA Disable Disable 5 Disable Disable Disable 44,45 44,45 44,45 44,45 44,45 44,45 Z_GAIN OATLCOMP LLENABLE MOTRMAST HPSP CMPA1ENA CMPA2ENA CMPB1ENA CMPB2ENA CSB_A1EN CSB_A2EN CSB_B1EN CSB_B2EN HPSATRIP HPSBTRIP HSSTTIME 1 40 No No 113 Enable Enable Enable Enable Enable Enable Enable Enable 415 415 10 46,47 46,47 46,47 46,47 46,47 46,47 46,47 46,47 46,47 46,47 47 47 47 47 47 47 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — CONFIGURATION (cont) ITEM EDT.R →RS.CF →RTIO →LIMT →RES.S HEAT →HT.CF →HT.SP →OC.EN →LAT.M →SG.CF →SG.CF→HT.ST →SG.CF→CAP.M →SG.CF→M.R.DB →SG.CF→S.G.DB →SG.CF→RISE →SG.CF→LAT.L →SG.CF→LIM.M →SG.CF→SW.H.T →SG.CF→SW.L.T →SG.CF→HT.P →SG.CF→HT.D →SG.CF→HT.TM →HH.CF →HH.CF→HW.P →HH.CF→HW.I →HH.CF→HW.D →HH.CF→HW.TM →HH.CF→ACT.C →HH.CF→ACTC→SN.1 →HH.CF→ACTC→SN.2 →HH.CF→ACTC→SN.3 →HH.CF→ACTC→SN.4 →HH.CF→ACTC→SN.5 →HH.CF→ACTC→C.A.LM SP →SP.CF →SP.S →SP.LO →SP.HI →SP.SP →SP.MN →SP.MX →SP.FS →SP.RS →SP.RT →SP.LM →SP.EC →S.PID →S.PID→SP.TM →S.PID→SP.P →S.PID→SP.I →S.PID→SP.D →ACT.C →ACTC→SN.1 →ACTC→SN.2 →ACTC→SN.3 →ACTC→SN.4 →ACTC→SN.5 →ACTC→C.A.LM ECON →EC.EN →EC2.E →EC.MN →EC.MX →E.TRM →E.SEL →OA.E.C →OA.EN →OAT.L →O.DEW →ORH.S →CFM.C →CFM.C→OCF.S →CFM.C→O.C.MX →CFM.C→O.C.MN →CFM.C→O.C.DB →E.CFG →E.CFG→E.P.GN →E.CFG→E.RNG →E.CFG→E.SPD →E.CFG→E.DBD →UEFC →UEFC→FC.CF →UEFC→FC.TM →UEFC→FC.L.O →ACT.C →ACTC→SN.1.1 →ACTC→SN.1.2 →ACTC→SN.1.3 →ACTC→SN.1.4 →ACTC→SN.1.5 →ACTC→C.A.L1 →ACTC→SN.2.1 →ACTC→SN.2.2 →ACTC→SN.2.3 →ACTC→SN.2.4 →ACTC→SN.2.5 →ACTC→C.A.L2 EXPANSION EVAP.DISCHRGE TEMP RESET EDT Reset Configuration Reset Ratio Reset Limit EDT 4-20 ma Reset Input HEATING CONFIGURATION Heating Control Type Heating Supply Air Setpt Occupied Heating Enabled MBB Sensor Heat Relocate STAGED GAS CONFIGS Staged Gas Heat Type Max Cap Change per Cycle S.Gas DB min.dF/PID Rate St.Gas Temp. Dead Band Heat Rise dF/sec Clamp LAT Limit Config Limit Switch Monitoring? Limit Switch High Temp Limit Switch Low Temp Heat Control Prop. Gain Heat Control Derv. Gain Heat PID Rate Config HYDRONIC HEAT CONFIGS Hydronic Ctl.Prop. Gain Hydronic Ctl.Integ. Gain Hydronic Ctl.Derv. Gain Hydronic PID Rate Config HYDR.HEAT ACTUATOR CFGS. Hydronic Ht.Serial Num.1 Hydronic Ht.Serial Num.2 Hydronic Ht.Serial Num.3 Hydronic Ht.Serial Num.4 Hydronic Ht.Serial Num.5 Hydr.Ht.Ctl.Ang.Lo Limit SUPPLY STATIC PRESS.CFG. Static Pressure Config Static Pressure Sensor Static Press. Low Range Static Press. High Range Static Pressure Setpoint VFD-IGV Minimum Speed VFD-IGV Maximum Speed VFD-IGV Fire Speed Over. Stat. Pres. Reset Config SP Reset Ratio SP Reset Limit SP Reset Econo. Position STAT.PRESS.PID CONFIGS Stat.Pres.PID Run Rate Static Press. Prop. Gain Static Pressure Intg. Gain Static Pressure Derv. Gain IGV ACTUATOR CONFIGS IGV Serial Number 1 IGV Serial Number 2 IGV Serial Number 3 IGV Serial Number 4 IGV Serial Number 5 IGV Cntrl Angle Lo Limit ECONOMIZER CONFIGURATION Economizer Installed? Econ.Act.2 Installed? Economizer Min.Position Economizer Max.Position Economzr Trim For SumZ ? Econ ChangeOver Select OA Enthalpy ChgOvr Selct Outdr.Enth Compare Value High OAT Lockout Temp OA Dewpoint Temp Limit Outside Air RH Sensor OUTDOOR AIR CFM CONTROL Outdoor Air CFM Sensor Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband ECON.OPERATION CONFIGS Economizer Prop.Gain Economizer Range Adjust Economizer Speed Adjust Economizer Deadband UNOCC.ECON.FREE COOLING Unoc Econ Free Cool Cfg Unoc Econ Free Cool Time Un.Ec.Free Cool OAT Lock ECON.ACTUATOR CONFIGS Econ Serial Number 1 Econ Serial Number 2 Econ Serial Number 3 Econ Serial Number 4 Econ Serial Number 5 Econ Ctrl Angle Lo Limit Econ 2 Serial Number 1 Econ 2 Serial Number 2 Econ 2 Serial Number 3 Econ 2 Serial Number 4 Econ 2 Serial Number 5 Ecn2 Ctrl Angle Lo Limit RANGE 0 - 3 (multi-text strings) 0 - 10 0 - 20 Enable/Disable UNITS CCN POINT DEFAULT PAGE NO. EDRSTCFG RTIO LIMT EDTRSENS 2 3 10 Disable 46,47 46,47 46,47 46,47 HEATTYPE SASPHEAT HTOCCENA HTLATMON 0 85 No No 54,55 54,55 54,55 54,55 sec HTSTGTYP HTCAPMAX HT_MR_DB HT_SG_DB HTSGRISE HTLATLIM HTLIMMON HT_LIMHI HT_LIMLO HT_PGAIN HT_DGAIN HTSGPIDR 0 45 0.5 2 0.06 10 Yes 170 160 1 1 90 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,57,58 54,58 54,58 sec HW_PGAIN HW_IGAIN HW_DGAIN HOTWPIDR 1 1 1 90 54,57 54,57 54,57 54,57 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 HTCL_SN1 HTCL_SN2 HTCL_SN3 HTCL_SN4 HTCL_SN5 HTCLCALM 0 0 0 0 0 85 54,57 54,57 54,57 54,57 54,57 54,57 0-2 (multi-text strings) Enable/Disable -10 - 0 0 - 10 0-5 0 - 100 0 - 100 0 - 100 0 - 4 (multi-text strings) 0.00 - 2.00 0.00 - 2.00 0 - 100 STATICFG SPSENS SP_LOW SP_HIGH SPSP STATPMIN STATPMAX STATPFSO SPRSTCFG SPRRATIO SPRLIMIT ECONOSPR 0 Disable 0 5 1.5 20 100 100 0 0.20 0.75 5 62 62 62 62 62 62 62 62 62 62 62 62,63 5 - 120 0-5 0-2 0-5 SPIDRATE STATP_PG STATP_IG STATP_DG 15 0.5 0.5 0.3 62,63 62,63 62,63 62,63 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 IGV_SN1 IGV_SN2 IGV_SN3 IGV_SN4 IGV_SN5 IGV_CALM 0 0 0 0 0 25 62,63 62,63 62,63 62,63 62,63 62,63 ECON_ENA ECON_TWO ECONOMIN ECONOMAX ECONTRIM ECON_SEL OAEC_SEL OAEN_CFG OAT_LOCK OADEWCFG OARHSENS Yes No 5 98 Yes 0 4 24 60 55 Disable 65,66 65,66 65,66 65,66 65,66 66 66 66 66 66,67 66 OCFMSENS OACFMMAX OACFMMIN OACFM_DB Disable 2000 0 400 66,68 66,68 66,68 66,68 ^F EC_PGAIN EC_RANGE EC_SPEED EC_DBAND 1 2.5 0.75 0.5 66 66 66 66 min dF UEFC_CFG UEFCTIME UEFCNTLO 0 120 50 66,68 66,68 66,68 ECON_SN1 ECON_SN2 ECON_SN3 ECON_SN4 ECON_SN5 ECONCALM ECN2_SN1 ECN2_SN2 ECN2_SN3 ECN2_SN4 ECN2_SN5 ECN2CALM 0 0 0 0 0 85 0 0 0 0 0 85 66,67 66,67 66,67 66,67 66,67 66 66,67 66,67 66,67 66,67 66,67 66 0-4 80 - 120 Yes/No Yes/No 0-4 5 - 45 0-5 0-5 0.05 - 0.2 0 - 20 Yes/No 110 - 180 100 - 170 0 - 1.5 0 - 1.5 60 - 300 0 - 1.5 0 - 1.5 0 - 1.5 15 - 300 Yes/No Yes/No 0 - 100 0 - 100 Yes/No 0 - 3 (multi-text strings) 1 - 5 (multi-text strings) 18 - 28 -40 - 120 50 - 62 Enable/Disable Enable/Disable 0 - 20000 0 - 20000 200 - 1000 0.7 - 3.0 0.5 - 5 0.1 - 10 0.1 - 2 0-2 (multi-text strings) 0 - 720 40 - 70 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 138 deltaF dF ^F ^F dF dF % % % dF dF CFM CFM CFM ^F APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — CONFIGURATION (cont) ITEM BP →BP.CF →BP.S →BP.R →BP.SP →BP.SO →BP.P1 →BP.P2 →B.V.A →B.V.A→BP.FS →B.V.A→BP.MN →B.V.A→BP.MX →B.V.A→BP.1M →B.V.A→BP.2M →B.V.A→BP.CL →FAN.T →FAN.T→FT.CF →FAN.T→FT.TM →FAN.T→FT.ST →FAN.T→FT.MX →FAN.T→FT.AD →FAN.T→FT.OF →FAN.T→FT.RM →FAN.T→FT.RS →FAN.T→SCF.C →B.PID →B.PID→BP.TM →B.PID→BP.P →B.PID→BP.I →B.PID→BP.D →ACT.C →ACT.C→BP.1 →ACT.C→BP.1→SN.1 →ACT.C→BP.1→SN.2 →ACT.C→BP.1→SN.3 →ACT.C→BP.1→SN.4 →ACT.C→BP.1→SN.5 →ACT.C→BP.1→C.A.LM →ACT.C→BP.2 →ACT.C→BP.2→SN.1 →ACT.C→BP.2→SN.2 →ACT.C→BP.2→SN.3 →ACT.C→BP.2→SN.4 →ACT.C→BP.2→SN.5 →ACT.C→BP.2→C.A.LM D.LV.T →L.H.ON →H.H.ON →L.H.OF →L.C.ON →H.C.ON →L.C.OF →C.T.LV →H.T.LV →C.T.TM →H.T.TM DMD.L →DM.L.S →D.L.20 →SH.NM →SH.DL →SH.TM →D.L.S1 →D.L.S2 IAQ →DCV.C →DCV.C→EC.MN →DCV.C→IAQ.M →DCV.C→O.C.MX →DCV.C→O.C.MN →DCV.C→O.C.DB →AQ.CF →AQ.CF→IQ.A.C →AQ.CF→IQ.A.F →AQ.CF→IQ.I.C →AQ.CF→IQ.I.F →AQ.CF→OQ.A.C →AQ.SP →AQ.SP→IQ.O.P →AQ.SP→IQ.O.C →AQ.SP→DAQ.L →AQ.SP→DAQ.H →AQ.SP→D.F.OF →AQ.SP→D.F.ON →AQ.SP→IAQ.R →AQ.SP→OAQ.L →AQ.SP→OAQ.U →AQ.S.R →AQ.S.R→IQ.R.L →AQ.S.R→IQ.R.H →AQ.S.R→OQ.R.L →AQ.S.R→OQ.R.H →IAQ.P →IAQ.P→IQ.PG →IAQ.P→IQ.P.T →IAQ.P→IQ.P.L →IAQ.P→IQ.P.H →IAQ.P→IQ.L.O EXPANSION BUILDING PRESS. CONFIGS Building Press. Config Building Pressure Sensor Bldg. Press. (+/-) Range Building Pressure Setp. BP Setpoint Offset Power Exhaust On Setp.1 Power Exhaust On Setp.2 VFD/ACTUATOR CONFIG VFD/Act. Fire Speed/Pos. VFD/Act. Min.Speed/Pos. VFD Maximum Speed BP 1 Actuator Max Pos. BP 2 Actuator Max Pos. BP Hi Cap VFD Clamp Val. FAN TRACKING CONFIG Fan Track Learn Enable Fan Track Learn Rate Fan Track Initial DCFM Fan Track Max Clamp Fan Track Max Correction Fan Track Internl EEPROM Fan Track Internal RAM Fan Track Reset Internal Supply Air CFM Config BLDG.PRESS.PID CONFIGS Bldg.Pres.PID Run Rate Bldg.Press. Prop. Gain Bldg.Press. Integ. Gain Bldg.Press. Deriv. Gain BLDG.PRES. ACTUATOR CFGS BLDG.PRES. ACT.1 CONFIGS BP 1 Serial Number 1 BP 1 Serial Number 2 BP 1 Serial Number 3 BP 1 Serial Number 4 BP 1 Serial Number 5 BP1 Cntrl Angle Lo Limit BLDG.PRES. ACT.2 CONFIGS BP 2 Serial Number 1 BP 2 Serial Number 2 BP 2 Serial Number 3 BP 2 Serial Number 4 BP 2 Serial Number 5 BP2 Cntrl Angle Lo Limit COOL/HEAT SETPT. OFFSETS Dmd Level Lo Heat On Dmd Level(+) Hi Heat On Dmd Level(-) Lo Heat Off Dmd Level Lo Cool On Dmd Level(+) Hi Cool On Dmd Level(-) Lo Cool Off Cool Trend Demand Level Heat Trend Demand Level Cool Trend Time Heat Trend Time DEMAND LIMIT CONFIG. Demand Limit Select Demand Limit at 20 ma Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time Demand Limit Sw.1 Setpt. Demand Limit Sw.2 Setpt. INDOOR AIR QUALITY CFG. DCV ECONOMIZER SETPOINTS Economizer Min.Position IAQ Demand Vent Min.Pos. Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband AIR QUALITY CONFIGS IAQ Analog Sensor Config IAQ 4-20 ma Fan Config IAQ Discrete Input Config IAQ Disc.In. Fan Config OAQ 4-20ma Sensor Config AIR QUALITY SETPOINTS IAQ Econo Override Pos. IAQ Override Flow Diff.Air Quality LoLimit Diff. Air Quality HiLimit DAQ PPM Fan Off Setpoint DAQ PPM Fan On Setpoint Diff. AQ Responsiveness OAQ Lockout Value User Determined OAQ AIR QUALITY SENSOR RANGE IAQ Low Reference IAQ High Reference OAQ Low Reference OAQ High Reference IAQ PRE-OCCUPIED PURGE IAQ Purge IAQ Purge Duration IAQ Purge LoTemp Min Pos IAQ Purge HiTemp Min Pos IAQ Purge OAT Lockout RANGE UNITS CCN POINT DEFAULT PAGE NO. 0 - 5 (multi-text strings) Enable/Disable 0.10 - 0.25 -0.25 - 0.25 0 - 0.5 0 - 100 0 - 100 "H2O "H2O "H2O % % BLDG_CFG BPSENS BP_RANGE BPSP BPSO PES1 PES2 0 Disable 0.25 0.05 0.05 25 75 70,71 70,71 70,71 70,71 70,71 70,71 70,71 0 - 100 0 - 50 50 - 100 85 - 100 85 - 100 5 - 25 % % % % % % BLDGPFSO BLDGPMIN BLDGPMAX BP1SETMX BP2SETMX BLDGCLMP 100 0 100 100 100 10 70,71 70,71 70,71 70,71 70,71 70,71 Yes/No 5-60 -20000 - 20000 0 - 20000 0 -20000 -20000 - 20000 -20000 - 20000 Yes/No 1 - 2 (multi-text strings) min CFM CFM CFM CFM CFM DCFM_CFG DCFMRATE DCFMSTRT DCFM_MAX DCFM_ADJ DCFM_OFF DCFM_RAM DCFMRSET SCFM_CFG No 15 2000 4000 1000 0 0 No 1 70,71 70,71 70,71 70,71 70,71 70,71 70,71 70,71 70,71 BPIDRATE BLDGP_PG BLDGP_IG BLDGP_DG 10 0.5 0.5 0.3 70,71 70,71 70,71 70,71 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 BP_1_SN1 BP_1_SN2 BP_1_SN3 BP_1_SN4 BP_1_SN5 BP1_CALM 0 0 0 0 0 35 70-72 70-72 70-72 70-72 70-72 70-72 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 BP_2_SN1 BP_2_SN2 BP_2_SN3 BP_2_SN4 BP_2_SN5 BP2_CALM 0 0 0 0 0 35 70-72 70-72 70-72 70-72 70-72 70-72 DMDLHON DMDHHON DMDLHOFF DMDLCON DMDHCON DMDLCOFF CTRENDLV HTRENDLV CTRENDTM HTRENDTM 1.5 0.5 1 1.5 0.5 1 0.1 0.1 120 120 48,55,56 48,55,56 48,55,56 48,49,55 48,49,55 48,49,55 48,49,55 48,55,56 48,49,55 48,55,56 0 100 0 0 60 80 50 52,53 53 53 53 53 53 53 5 - 120 0-5 0-2 0-5 -1 - 2 0.5 - 20.0 0.5 - 2.0 -1 - 2 0.5 - 20.0 0.5 - 2.0 0.1 - 5.0 0.1 - 5.0 30 - 600 30 - 600 sec ^F ^F ^F ^F ^F ^F ^F ^F sec sec 0 - 3 (multi-text strings) 0 - 100 0 - 99 0 - 60 0 - 120 0 - 100 0 - 100 % min % % DMD_CTRL DMT20MA SHED_NUM SHED_DEL SHED_TIM DLSWSP1 DLSWSP2 0 - 100 0 - 100 0 - 20000 0 - 20000 200 - 1000 % % CFM CFM CFM ECONOMIN IAQMINP OACFMMAX OACFMMIN OACFM_DB 5 0 2000 0 400 74-76 74,75 74 74 74 IAQANCFG IAQANFAN IAQINCFG IAQINFAN OAQANCFG 0 0 0 0 0 74 74 74,75 74,75 74,75 IAQOVPOS IAQOVCFM DAQ_LOW DAQ_HIGH DAQFNOFF DAQFNON IAQREACT OAQLOCK OAQ_USER 100 10000 100 700 200 400 0 0 400 74,75 74 74-76 74-76 74,75 74,75 74,76 74,75 74 IAQREFL IAQREFH OAQREFL OAQREFH 0 2000 0 2000 74,75 74,75 74,76 74,76 IAQPURGE IAQPTIME IAQPLTMP IAQPHTMP IAQPNTLO No 15 10 35 50 74,76 74,76 74,76 74,76 74,76 % 0 - 4 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 0 - 100 0 - 31000 0 - 1000 100 - 2000 0 - 2000 0 - 2000 -5 - 5 0 - 2000 0 - 5000 % CFM 0 - 5000 0 - 5000 0 - 5000 0 - 5000 Yes/No 5 - 60 0 - 100 0 - 100 35 - 70 139 min % % dF APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — CONFIGURATION (cont) ITEM HUMD →HM.CF →HM.SP →H.PID →H.PID→HM.TM →H.PID→HM.P →H.PID→HM.I →H.PID→HM.D →ACT.C →ACTC→SN.1 →ACTC→SN.2 →ACTC→SN.3 →ACTC→SN.4 →ACTC→SN.5 →ACTC→C.A.LM DEHU →D.SEL →D.SEN →D.EC.D →D.V.CF →D.V.RA →D.V.HT →D.C.SP →D.RH.S CCN →CCNA →CCNB →BAUD →BROD →BROD→TM.DT →BROD→OAT.B →BROD→ORH.B →BROD→OAQ.B →BROD→G.S.B →BROD→B.ACK →SC.OV →SC.OV→SCH.N →SC.OV→HOL.T →SC.OV→O.T.L. →SC.OV→OV.EX →SC.OV→SPT.O →SC.OV→T58.O →SC.OV→GL.OV ALLM →SP.L.O →SP.H.O →SP.L.U →SP.H.U →SA.L.O →SA.H.O →SA.L.U →SA.H.U →RA.L.O →RA.H.O →RA.L.U →RA.H.U →OAT.L →OAT.H →R.RH.L →R.RH.H →O.RH.L →O.RH.H →SP.L →SP.H →BP.L →BP.H →IAQ.H TRIM →SAT.T →RAT.T →OAT.T →SPT.T →L.SW.T →CCT.T →SP.A.T →SP.B.T →DP.A.T →DP.B.T SW.LG →FTS.L →IGC.L →RMI.L →ENT.L →SFS.L →DL1.L →DL2.L →IAQ.L →FSD.L →PRS.L →EVC.L →PRG.L →DH.LG DISP →TEST →METR →LANG →PAS.E →PASS EXPANSION HUMIDITY CONFIGURATION Humidifier Control Cfg. Humidifier Setpoint HUMIDIFIER PID CONFIGS Humidifier PID Run Rate Humidifier Prop. Gain Humidifier Integral Gain Humidifier Deriv. Gain HUMIDIFIER ACTUATOR CFGS Humd Serial Number 1 Humd Serial Number 2 Humd Serial Number 3 Humd Serial Number 4 Humd Serial Number 5 Humd Ctrl Angle Lo Limit DEHUMIDIFICATION CONFIG. Dehumidification Config Dehumidification Sensor Econ disable in DH mode? Vent Reheat Setpt Select Vent Reheat RAT offset Vent Reheat Setpoint Dehumidify Cool Setpoint Dehumidify RH Setpoint CCN CONFIGURATION CCN Address CCN Bus Number CCN Baud Rate CCN BROADCST DEFINITIONS CCN Time/Date Broadcast CCN OAT Broadcast CCN OARH Broadcast CCN OAQ Broadcast Global Schedule Broadcst CCN Broadcast Ack'er CCN SCHEDULES-OVERRIDES Schedule Number Accept Global Holidays? Override Time Limit Timed Override Hours SPT Override Enabled ? T58 Override Enabled ? Global Sched. Override ? ALERT LIMIT CONFIG. SPT lo alert limit/occ SPT hi alert limit/occ SPT lo alert limit/unocc SPT hi alert limit/unocc EDT lo alert limit/occ EDT hi alert limit/occ EDT lo alert limit/unocc EDT hi alert limit/unocc RAT lo alert limit/occ RAT hi alert limit/occ RAT lo alert limit/unocc RAT hi alert limit/unocc OAT lo alert limit OAT hi alert limit RARH low alert limit RARH high alert limit OARH low alert limit OARH high alert limit SP low alert limit SP high alert limit BP lo alert limit BP high alert limit IAQ high alert limit SENSOR TRIM CONFIG. Air Temp Lvg SF Trim RAT Trim OAT Trim SPT Trim Limit Switch Trim Air Temp Lvg Evap Trim Suct.Press.Circ.A Trim Suct.Press.Circ.B Trim Dis.Press.Circ.A Trim Dis.Press.Circ.B Trim SWITCH LOGIC: NO / NC Filter Status Inpt-Clean IGC Feedback - Off RemSw Off-Unoc-Strt-NoOv Enthalpy Input - Low Fan Status Sw. - Off Dmd.Lmt.Sw.1 - Off Dmd.Lmt.Sw.2 - Off IAQ Disc.Input - Low Fire Shutdown - Off Pressurization Sw. - Off Evacuation Sw. - Off Smoke Purge Sw. - Off Dehumidify Sw. - Off DISPLAY CONFIGURATION Test Display LEDs Metric Display Language Selection Password Enable Service Password RANGE 0-4 0 - 100 UNITS CCN POINT DEFAULT PAGE NO. HUMD_CFG HUSP 0 40 76,77 76,77 HUMDRATE HUMID_PG HUMID_IG HUMID_DG 30 1 0.3 0.3 76,77 76,77 76,77 76,77 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 HUMD_SN1 HUMD_SN2 HUMD_SN3 HUMD_SN4 HUMD_SN5 HUMDCALM 0 0 0 0 0 85 77 77 77 77 77 77 0-3(multi-text strings) 1-3(multi-text strings) Yes/No 0-1(multi-text strings) 0-8 55-95 40-55 10-90 DHSELECT DHSENSOR DHECDISA DHVHTCFG DHVRAOFF DHVHT_SP DHCOOLSP DHRELHSP 0 1 Yes 0 0 70 45 55 77,78 78 78 78 78 78 78 78 1 - 239 0 - 239 1 - 5 (multi-text strings) CCNADD CCNBUS CCNBAUDD 1 0 3 79,80 79,80 79,80 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF CCNBC OATBC OARHBC OAQBC GSBC CCNBCACK On Off Off Off Off Off 79,80 79,80 79,80 79,80 79,80 79,80 SCHEDNUM HOLIDAYT OTL OVR_EXT SPT_OVER T58_OVER GLBLOVER 1 No 1 0 Yes Yes No 79,80 79,80 79,80 79,80 79,80 79,80 79,80 % 10 - 120 0-5 0-5 0-5 sec 0 - 99 YES/NO 0-4 0-4 YES/NO YES/NO YES/NO ^F dF dF % HRS HRS -10-245 -10-245 -10-245 -10-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 0-100 0-100 0-100 0-100 0-5 0-5 -0.25-0.25 -0.25-0.25 0-5000 dF dF dF dF dF dF dF dF dF dF dF dF dF dF % % % % "H2O "H2O "H2O "H2O SPLO SPHO SPLU SPHU SALO SAHO SALU SAHU RALO RAHO RALU RAHU OATL OATH RRHL RRHH ORHL ORHH SPL SPH BPL BPH IAQH 60 85 45 100 40 100 40 100 60 90 40 100 -40 150 0 100 0 100 0 2 -0.25 0.25 1200 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 80,81 81 81 81 81 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -50 - 50 -50 - 50 -50 - 50 -50 - 50 ^F ^F ^F ^F ^F ^F PSIG PSIG PSIG PSIG SAT_TRIM RAT_TRIM OAT_TRIM SPT_TRIM LSW_TRIM CCT_TRIM SPA_TRIM SPB_TRIM DPA_TRIM DPB_TRIM 0 0 0 0 0 0 0 0 0 0 81,82 81,82 81,82 81,82 81,82 81,82 81,82 81,82 81,82 81,82 Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close FLTSLOGC GASFANLG RMTINLOG ENTHLOGC SFSLOGIC DMD_SW1L DMD_SW2L IAQINLOG FSDLOGIC PRESLOGC EVACLOGC PURGLOGC DHDISCLG Open Open Open Close Open Open Open Open Open Open Open Open Open 82 82 82 82 82 82 82 82 82 82 82 82 82 ON/OFF ON/OFF 0 - 1 (multi-text strings) ENABLE/DISABLE 0000 - 9999 TEST DISPUNIT LANGUAGE PASS_EBL PASSWORD Off Off 0 Enable 1111 82,83 82,83 82,83 82,83 82,83 140 APPENDIX A — LOCAL DISPLAY TABLES (cont) MODE — TIMECLOCK ACRONYM TIME →HH.MM DATE →MNTH →DOM →DAY →YEAR SCH.L →PER.1 →PER.1→DAYS →PER.1→DAYS→MON →PER.1→DAYS→TUE →PER.1→DAYS→WED →PER.1→DAYS→THU →PER.1→DAYS→FRI →PER.1→DAYS→SAT →PER.1→DAYS→SUN →PER.1→DAYS→HOL →PER.1→OCC →PER.1→UNC Repeated for periods 2 to 8 HOL.L →HD.01 →HD.01→MON →HD.01→DAY →HD.01→LEN Repeated for holidays 2 to 30 DAY.S DS.ST DS.ST→ST.MN DS.ST→ST.WK DS.ST→ST.DY DS.ST→MIN.A DS.SP DS.SP→SP.MN DS.SP→SP.WK DS.SP→SP.DY DS.SP→MIN.S NAME TIME OF DAY Hour and Minute MONTH,DATE,DAY AND YEAR Month of Year Day of Month Day of Week Year LOCAL TIME SCHEDULE PERIOD 1 DAY FLAGS FOR PERIOD 1 Monday in Period Tuesday in Period Wednesday in Period Thursday in Period Friday in Period Saturday in Period Sunday in Period Holiday in Period Occupied from Occupied to LOCAL HOLIDAY SCHEDULES HOLIDAY SCHEDULE 01 Holiday Start Month Start Day Duration (Days) DAYLIGHT SAVINGS TIME DAYLIGHT SAVINGS START Month Week Day Minutes to Add DAYLIGHTS SAVINGS STOP Month Week Day Minutes to Subtract RANGE UNITS CNN POINT DEFAULTS PAGE NO. 00:00 TIME 84,85 multi-text strings 0-31 multi-text strings e.g. 2003 MOY DOM DOWDISP YOCDISP 84,85 84,85 84,85 84,85 YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO YES/NO 00:00 00:00 PER1MON PER1TUE PER1WED PER1THU PER1FRI PER1SAT PER1SUN PER1HOL PER1_OCC PER1_UNC 0-12 0-31 0-99 HOL_MON1 HOL_DAY1 HOL_LEN1 1 - 12 1-5 1-7 0 - 90 STARTM STARTW STARTD MINADD 4 1 7 60 84,85 84,85 84,85 84,85 84,85 1 - 12 1-5 1-7 0 - 90 STOPM STOPW STOPD MINSUB 10 5 7 60 84,85 85 85 85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 84,85 Period 1 only Yes Yes Yes Yes Yes Yes Yes Yes 00:00 24:00 84,85 84,85 84,85 84,85 84,85 MODE — OPERATING MODES ITEM SYS.M HVAC CTRL MODE →OCC →T.OVR →DCV →SA.R →DMD.L →T.C.ST →IAQ.P →LINK →LOCK →H.NUM EXPANSION ascii string spelling out the system mode ascii string spelling out the hvac modes ascii string spelling out the "control type" MODES CONTROLLING UNIT Currently Occupied Timed Override in Effect DCV Resetting Min Pos Supply Air Reset Demand Limit in Effect Temp.Compensated Start IAQ Pre-Occ Purge Active Linkage Active - CCN Mech.Cooling Locked Out HVAC Mode Numerical Form RANGE UNITS CCN POINT string string string ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF number MODEOCCP MODETOVR MODEADCV MODESARS MODEDMLT MODETCST MODEIQPG MODELINK MODELOCK MODEHVAC MODE — ALARMS ITEM CURR R.CUR HIST EXPANSION CURRENTLY ACTIVE ALARMS this is a dynamic list of active alarms Reset All Current Alarms ALARM HISTORY this is a record of the last 20 alarms RANGE YES/NO UNITS CCN POINT strings ALRESET strings 141 WRITE STATUS ram config APPENDIX B — CCN TABLES In the following tables the structure of the tables which are used with the Service Tool as well as the names and data that are included in each table are shown. There are several CCN variables that are not displayed through the scrolling marquee and are used for more extensive diagnostics and system evaluations. All Z series units with ComtfortLink™ controls have a port for interface with the Carrier Comfort Network® (CCN) system. On TB3 there is a J11 jack which can be used for temporary connection to the CCN network or to computers equipped with CCN software like the Service Tool. Also on TB3 there are screw connections that can be used for more permanent CCN connections. STATUS DISPLAY TABLES TABLE COOLING DISPLAY NAME HVAC Mode…………..: Control Mode………..: RANGE UNITS POINT NAME ascii text strings ascii text strings Current Running Capacity Curr.Calc. Cool Capacity Current Cool Stage Requested Cool Stage Maximum Cool Stages % % CAPTOTAL COOLCALC COOL_STG CL_STAGE CLMAXSTG Cooling Control Point Evaporator Discharge Tmp Mixed Air Temperature Next capacity step down Next capacity step up dF dF dF % % COOLCPNT EDT MAT CAPNXTDN CAPNXTUP COOL_A Current Cool Stage Current Cool Stage A Cir A Discharge Pressure Cir A Suction Pressure Cir A Sat.Condensing Tmp Cir A Sat.Suction Temp. Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor A1 Feedback Compressor A2 Feedback Circ A High Press.Switch Circuit A Stage Inhibit PSIG PSIG dF dF COOL_STG CLSTAGEA DP_A SP_A SCTA SSTA CMPA1 UNL_1_A1 UNL_2_A1 CMPA2 CSB_A1 CSB_A2 CIRCAHPS CIRAFAIL COOL_B Current Cool Stage Current Cool Stage B Cir B Discharge Pressure Cir B Suction Pressure Cir B Sat.Condensing Tmp Cir B Sat.Suction Temp. Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay Compressor B1 Feedback Compressor B2 Feedback Circ B High Press.Switch Circuit B Stage Inhibit PSIG PSIG dF dF COOL_STG CLSTAGEB DP_B SP_B SCTB SSTB CMPB1 UNL_1_B1 UNL_2_B1 CMPB2 CSB_B1 CSB_B2 CIRCBHPS CIRBFAIL ECONDIAG Economizer Active ? Conditions which prevent economizer being active: Econ Act. Unavailable? Econ2 Act. Unavailable Enth.Switch Read High ? DBC - OAT lockout? DEW - OA Dewpt. lockout? DDBC- OAT > RAT lockout? OAEC- OA Enth Lockout? DEC - Diff.Enth.Lockout? EDT Sensor Bad ? OAT Sensor Bad ? Economizer forced ? Supply Fan not on 30s ? Cool Mode not in effect? OAQ lockout in effect ? Econ recovery hold off? Dehumid. Disabled Econ.? Yes/No ECACTIVE Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No ECONUNAV ECN2UNAV ENTH DBC_STAT DEW_STAT DDBCSTAT OAECSTAT DEC_STAT EDT_STAT OAT_STAT ECONFORC SFONSTAT COOL_OFF OAQLOCKD ECONHELD DHDISABL 142 WRITE STATUS APPENDIX B — CCN TABLES (cont) STATUS DISPLAY TABLES (cont) TABLE ECONOMZR DISPLAY NAME RANGE Economizer Act.Curr.Pos. Economizer 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. Economizer Active ? Economizer Control Point Outside Air Temperature Evaporator Discharge Tmp Controlling Return Temp Econo Current Min. Pos. Econo Current Min. CFM Outside Air CFM UNITS % % % dF dF dF dF % CFM CFM POINT NAME ECONOPOS ECON2POS ECONOCMD ECACTIVE ECONCPNT OAT EDT RETURN_T ECMINPOS ECMINCFM OACFM WRITE STATUS forcible forcible forcible GENERAL Occupied ? Static Pressure Building Pressure Outside Air CFM Return Air CFM Supply Air CFM Outside Air Rel.Humidity Return Air Rel.Humidity Space Relative Humidity Space Temperature Offset Supply Air Setpnt. Reset Static Pressure Reset IAQ - PPM Return CO2 OAQ - PPM Return CO2 IAQ Min.Pos.Override YES/NO "H2O "H2O CFM CFM CFM % % % ^F ^F % OCCUPIED SP BP OACFM RACFM SACFM OARH RARH SPRH SPTO SASPRSET SPRESET IAQ OAQ IAQMINOV forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible HT_STAGE HTCLRPOS HEATCPNT HS1 HS2 HS3 HS4 HS5 HS6 HIR forcible GENERIC 20 points dependent upon the configuration of the "generics" table in the Service-Config section on page 150 HEATING HVAC Mode…………..: Control Mode………..: Heat Control Type……: Re-Heat Control Type...: Heating Mode………..: Requested Heat Stage Ht.Coil Act.Current Pos. Heating Control Point Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay ascii text strings ascii text strings ascii text strings ascii text strings ascii text strings System Mode…………: HVAC Mode…………..: Control Mode………..: Currently Occupied Timed Override in effect DCV resetting min pos Supply Air Reset Demand Limit in Effect Temp.Compensated Start IAQ pre-occ purge active Linkage Active - DAV Mech.Cooling Locked Out HVAC Mode Numerical Form ascii text strings ascii text strings ascii text strings On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off number MODEOCCP MODETOVR MODEADCV MODESARS MODEDMLT MODETCST MODEIQPG MODELINK MODELOCK MODEHVAC ascii text strings UCCLSTRT UCCL_END OCCLSTRT OCCL_END CTRLTEMP OCHT_END OCHTSTRT UCHT_END UCHTSTRT string % dF MODEDISP MODETRIP Unoccup. Cool Mode Start Unoccup. Cool Mode End Occupied Cool Mode Start Occupied Cool Mode End Ctl.Temp RAT,SPT or Zone Occupied Heat Mode End Occupied Heat Mode Start Unoccup. Heat Mode End Unoccup. Heat Mode Start HVAC Mode…………..: TEMPCTRL Evaporator Discharge Tmp Leaving Air Temperature Mixed Air Temperature Controlling Return Temp Controlling Space Temp dF dF dF dF dF 143 EDT LAT MAT RETURN_T SPACE_T forcible forcible APPENDIX B — CCN TABLES (cont) STATUS DISPLAY TABLES (cont) TABLE TEMPS DISPLAY NAME RANGE Air Temp Lvg Supply Fan Return Air Temperature Outside Air Temperature Space Temperature Space Temperature Offset Staged Gas LAT Sum Staged Gas LAT 1 Staged Gas LAT 2 Staged Gas LAT 3 Staged Gas Limit Sw.Temp Air Temp Lvg Evap Coil Cir A Sat.Condensing Tmp Cir B Sat.Condensing Tmp Cir A Sat.Suction Temp. Cir B Sat.Suction Temp. UNITS dF dF dF dF ^F dF dF dF dF dF dF dF dF dF dF POINT NAME SAT RAT OAT SPT SPTO LAT_SGAS LAT1SGAS LAT2SGAS LAT23SGAS LIMSWTMP CCT SCTA SCTB SSTA SSTB WRITE STATUS forcible forcible forcible forcible TSTAT Control Mode………..: Thermostat Y1 Input Thermostat Y2 Input Thermostat W1 Input Thermostat W2 Input Thermostat G Input ascii text strings On/Off On/Off On/Off On/Off On/Off Y1 Y2 W1 W2 G forcible forcible forcible forcible forcible Filter Status Input Fan request from IGC Fire Shutdown Input Thermostat G Input Thermostat W2 Input Thermostat W1 Input Thermostat Y2 Input Thermostat Y1 Input Remote Input State Enth. Switch Read High ? Supply Fan Status Switch Circ A High Press.Switch Circ B High Press.Switch Freeze Status Switch Plenum Press.Safety Sw. Demand Limit Switch 1 Demand Limit Switch 2 Pressurization Input Evacuation Input Smoke Purge Input IAQ - Discrete Input Dehumidify Switch Input Dirty/Clean On/Off Alarm/Normal On/Off On/Off On/Off On/Off On/Off On/Off Yes/No On/Off On/Off On/Off Alarm/Normal High/Low On/Off On/Off Alarm/Normal Alarm/Normal Alarm/Normal High/Low On/Off FLTS IGCFAN FSD G W2 W1 Y2 Y1 RMTIN ENTH SFS CIRCAHPS CIRCBHPS FRZ PPS DMD_SW1 DMD_SW2 PRES EVAC PURG IAQIN DHDISCIN forcible UINPUTS forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible UOUTPUTS FANS Supply Fan Relay Supply Fan VFD Speed Supply Fan Request Exhaust Fan VFD Speed Power Exhaust Relay 1 Power Exhaust Relay 2 Condenser Fan Circuit A Condenser Fan Circuit B MotorMaster Condensr Fan COOLING Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay HEATING Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay ACTUATORS Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. IGV Actuator Current Pos IGV Actuator Command Pos Humidifer Act.Curr.Pos. Humidifier Command Pos. Ht.Coil Act.Current Pos. Ht.Coil Command Position BP 1 Actuator Curr.Pos. BP 1 Command Position BP 2 Actuator Curr.Pos. BP 2 Command Position GENERAL OUTPUTS Humidifier Relay Remote Alarm / Aux Relay On/Off 0-100 Yes/No 0-100 On/Off On/Off On/Off On/Off On/Off % % SFAN SFAN_VFD SFANFORC EFAN_VFD PE1 PE2 CONDFANA CONDFANB PULSCFAB On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off CMPA1 UNL_1_A1 UNL_2_A1 CMPA2 CMPB1 UNL_1_B1 UNL_2_B1 CMPB2 On/Off On/Off On/Off On/Off On/Off On/Off On/Off HS1 HS2 HS3 HS4 HS5 HS6 HIR 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 % % % % % % % % % % % % % On/Off On/Off ECONOPOS ECON2POS ECONOCMD IGV_RPOS IGV_CPOS HUMDRPOS HUMDCPOS HTCLRPOS HTCLCPOS BP1_RPOS BP1_CPOS BP2_RPOS BP2_CPOS HUMIDRLY ALRM 144 forcible forcible forcible forcible APPENDIX B — CCN TABLES (cont) SET POINT TABLE TABLE SET_PNT DISPLAY NAME RANGE Occupied Heat Setpoint Occupied Cool Setpoint Unoccupied Heat Setpoint Unoccupied Cool Setpoint Heat-Cool Setpoint Gap VAV Occ. Cool On Delta VAV Occ. Cool Off Delta Supply Air Setpoint Supply Air Setpoint Hi Supply Air Setpoint Lo Heating Supply Air Setpt Tempering Purge SASP Tempering in Cool SASP Tempering in Vent Occ SASP Tempering Vent Unocc. SASP 40-99 40-99 40-99 40-110 2-10 0-25 1-25 45-75 45-75 45-75 90-145 -20-80 5-75 -20-80 -20-80 UNITS dF dF dF dF deltaF deltaF deltaF dF dF dF dF dF dF dF dF POINT NAME OHSP OCSP UHSP UCSP HCSP_GAP VAVOCON VAVOCOFF SASP SASP_HI SASP_LO SASPHEAT TEMPPURG TEMPCOOL TEMPVOCC TEMPVUNC DEFAULT 68 75 55 90 5 3.5 2 55 55 60 85 50 5 65 50 CONFIG TABLES TABLE ALARMDEF DISPLAY NAME RANGE Alarm Routing Control Equipment Priority Comm Failure Retry Time Re-Alarm Time Alarm System Name 00000000-11111111 0-7 1 - 240 1 - 255 up to 8 alphanum CCN Time/Date Broadcast CCN OAT Broadcast CCN OARH Broadcast CCN OAQ Broadcast Global Schedule Broadcst Daylight Savings Start: Month Week Day Minutes to Add Daylight Savings Stop: Month Week Day Minutes to Subtract Device Name: Description: Location: Software Part Number: Model Number: Serial Number: Reference Number: Broadcast Supervisory Holiday Start Month Start Day Duration (days) Occupancy Supervisory Timed Override Hours Period 1 DOW (MTWTFSSH) Occupied From Occupied To Period 2 DOW (MTWTFSSH) Occupied From Occupied To Period 3 DOW (MTWTFSSH) Occupied From Occupied To Period 4 DOW (MTWTFSSH) Occupied From Occupied To Period 5 DOW (MTWTFSSH) Occupied From Occupied To Period 6 DOW (MTWTFSSH) Occupied From Occupied To Period 7 DOW (MTWTFSSH) Occupied From Occupied To Period 8 DOW (MTWTFSSH) Occupied From Occupied To Z-Series Z Series Rooftop UNITS POINT NAME DEFAULT ALRM_CNT EQP_TYPE RETRY_TM RE-ALARM ALRM_NAM 1100000 5 10 30 Z-SERIES Off/On Off/On Off/On Off/On Off/On CCNBC OATBC OARHBC OAQBC GSBC Off Off Off Off Off 1 - 12 1-5 1-7 0 - 90 STARTM STARTW STARTD MINADD 4 1 7 60 1 - 12 1-5 1-7 0 - 90 STOPM STOPW STOPD MINSUB 10 5 7 60 1-12 1-31 1-99 HOL-MON HOL-DAY HOL-LEN 0 0 0 0 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 00000000 0:00 0:00 OVR-EXT DOW1 OCCTOD1 UNOCTOD1 DOW2 OCCTOD2 UNOCTOD2 DOW3 OCCTOD3 UNOCTOD3 DOW4 OCCTOD4 UNOCTOD4 DOW5 OCCTOD5 UNOCTOD5 DOW6 OCCTOD6 UNOCTOD6 DOW7 OCCTOD7 UNOCTOD7 DOW8 OCCTOD8 UNOCTOD8 min min BRODEFS Ctlr-ID HOLIDAY HOLDY01S to HOLDY30S OCCDEFCS CESR131292-XX-XX 145 APPENDIX B — CCN TABLES (cont) CONFIG TABLES (cont) TABLE SCHEDOVR DISPLAY NAME RANGE Schedule Number Accept Global Holidays? Override Time Limit Timed Override Hours Accepting an Override: SPT Override Enabled ? T58 Override Enabled ? Allowed to Broadcast a Global Sched. Override ? 0-99 Yes/No 0-4 0-4 Occupied Heat Setpoint Occupied Cool Setpoint Unoccupied Heat Setpoint Unoccupied Cool Setpoint Heat-Cool Setpoint Gap VAV Occ. Cool On Delta VAV Occ. Cool Off Delta Supply Air Setpoint Supply Air Setpoint Hi Supply Air Setpoint Lo Heating Supply Air Setpt Tempering Purge SASP Tempering in Cool SASP Tempering in Vent Occ SASP Tempering Vent Unocc. SASP 55-80 55-80 40-80 75-95 2-10 0-25 1-25 45-75 45-75 45-75 90-145 -20-80 5-75 -20-80 -20-80 UNITS POINT NAME DEFAULT SCHEDNUM HOLIDAYT OTL OVR_EXT 0 No 1 0 Yes/No Yes/No SPT_OVER T58_OVER Yes Yes Yes/No GLBLOVER No OHSP OCSP UHSP UCSP HCSP_GAP VAVOCON VAVOCOFF SASP SASP_HI SASP_LO SASPHEAT TEMPPURG TEMPCOOL TEMPVOCC TEMPVUNC 68 75 55 90 5 3.5 2 55 55 60 85 50 5 65 50 hours hours SET_PNT dF dF dF dF deltaF deltaF deltaF dF dF dF dF dF dF dF dF SERVICE-CONFIG TABLES TABLE ALLM DISPLAY NAME RANGE SPT lo alert limit/occ SPT hi alert limit/occ SPT lo alert limit/unocc SPT hi alert limit/unocc EDT lo alert limit/occ EDT hi alert limit/occ EDT lo alert limit/unocc EDT hi alert limit/unocc RAT lo alert limit/occ RAT hi alert limit/occ RAT lo alert limit/unocc RAT hi alert limit/unocc OAT lo alert limit OAT hi alert limit RARH low alert limit RARH high alert limit OARH low alert limit OARH high alert limit SP low alert limit SP high alert limit BP lo alert limit BP high alert limit IAQ high alert limit -10-245 -10-245 -10-245 -10-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 -40-245 0-100 0-100 0-100 0-100 0-5 0-5 -0.25-0.25 -0.25-0.25 0-5000 Building Press. Config Building Pressure Sensor Bldg. Press. (+/-) Range Building Pressure Setp. BP Setpoint Offset Power Exhaust On Setp.1 Power Exhaust On Setp.2 Bldg.Pressure Fire Speed Bldg.Pressure Min. Speed Bldg.Pressure Max. Speed BP 1 Actuator Max Pos. BP 2 Actuator Max Pos. BP Hi Cap VFD Clamp Val. BP Hi Cap VFD Clamp Time Fan Track Learn Enable Fan Track Learn Rate Fan Track Initial DCFM Fan Track Max Clamp Fan Track Max Correction Fan Track Internl EEPROM Fan Track Internal RAM Fan Track Reset Internal Supply Air CFM Config 0-5 Enable/Disable 0.10 - 0.25 -0.25 - 0.25 0 - 0.5 0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 85 - 100 85 - 100 5 - 25 30 - 255 Yes/No 5-60 -20000 - 20000 0 - 20000 0 -20000 -20000 - 20000 -20000 - 20000 Yes/No 1 - 2 (multi-text strings) UNITS dF dF dF dF dF dF dF dF dF dF dF dF dF dF % % % % "H2O "H2O "H2O "H2O POINT NAME DEFAULT SPLO SPHO SPLU SPHU SALO SAHO SALU SAHU RALO RAHO RALU RAHU OATL OATH RRHL RRHH ORHL ORHH SPL SPH BPL BPH IAQH 60 85 45 100 40 100 40 100 60 90 40 100 -40 150 0 100 0 100 0 2 -0.25 0.25 1200 BLDG_CFG BPSENS BP_RANGE BPSP BPSO PES1 PES2 BLDGPFSO BLDGPMIN BLDGPMAX BP1SETMX BP2SETMX BLDGCLMP BLDGWAIT DCFM_CFG DCFMRATE DCFMSTRT DCFM_MAX DCFM_ADJ DCFM_OFF DCFM_RAM DCFMRSET SCFM_CFG 0 Disable 0.25 0.05 0.05 25 75 100 10 100 100 100 10 60 NO 15 2000 4000 1000 0 0 No 1 BP__ 146 "H2O "H2O ^"H2O % % % % % % % % sec min CFM CFM CFM CFM CFM APPENDIX B — CCN TABLES (cont) SERVICE-CONFIG TABLES (cont) TABLE BP__ (cont) DISPLAY NAME RANGE Bldg.Pres.PID Run Rate Bldg.Press. Prop. Gain Bldg.Press. Integ. Gain Bldg.Press. Deriv. Gain BP 1 Serial Number 1 BP 1 Serial Number 2 BP 1 Serial Number 3 BP 1 Serial Number 4 BP 1 Serial Number 5 BP1 Cntrl Angle Lo Limit BP 2 Serial Number 1 BP 2 Serial Number 2 BP 2 Serial Number 3 BP 2 Serial Number 4 BP 2 Serial Number 5 BP2 Cntrl Angle Lo Limit 5 - 120 0-5 0-2 0-5 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 Capacity Threshold Adjst Compressor Lockout Temp Lead/Lag Operation ? Motor Master Control ? Head Pressure Setpoint Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 CSB A1 Feedback Alarm CSB A2 Feedback Alarm CSB B1 Feedback Alarm CSB B2 Feedback Alarm CMPA1 Hi.Pr.Sw. Trip CMPB1 Hi.Pr.Sw. Trip Hi SST Alert Delay Time -10 - 10 -25 - 55 Yes/No Yes/No 80 - 150 Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable 365-415 365-415 5 - 30 Dehumidification Config Dehumidification Sensor Econ disable in DH mode? Vent Reheat Setpt Select Vent Reheat RAT offset Vent Reheat Setpoint Dehumidify Cool Setpoint Dehumidify RH Setpoint 0-3 1-3 Yes/No 0-1 0-8 55-95 40-55 10-90 Metric Display Language Selection Password Enable Service Password Contrast Adjustment Brightness Adjustment Off/On 0-1 Enable/Disable 0000-9999 0-255 0-255 Dmd Level Lo Heat On Dmd Level(+) Hi Heat On Dmd Level(-) Lo Heat Off Dmd Level Lo Cool On Dmd Level(+) Hi Cool On Dmd Level(-) Lo Cool Off Cool Trend Demand Level Heat Trend Demand Level Cool Trend Time Heat Trend Time -1 - 2 0.5 - 20.0 0.5 - 2.0 -1 - 2 0.5 - 20.0 0.5 - 2.0 0.1 - 5.0 0.1 - 5.0 30 - 600 30 - 600 Demand Limit Select Demand Limit at 20 ma Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time Demand Limit Sw.1 Setpt. Demand Limit Sw.2 Setpt. 0-3 0 - 100 0 - 99 0 - 60 0 - 120 0 - 100 0 - 100 UNITS sec POINT NAME DEFAULT BPIDRATE BLDGP_PG BLDGP_IG BLDGP_DG BP_1_SN1 BP_1_SN2 BP_1_SN3 BP_1_SN4 BP_1_SN5 BP1_CALM BP_2_SN1 BP_2_SN2 BP_2_SN3 BP_2_SN4 BP_2_SN5 BP2_CALM 10 1 1 0.5 0 0 0 0 0 35 0 0 0 0 0 35 PSIG PSIG min Z_GAIN OATLCOMP LLENABLE MOTRMAST HPSP CMPA1ENA CMPA2ENA CMPB1ENA CMPB2ENA CSB_A1EN CSB_A2EN CSB_B1EN CSB_B2EN HPSATRIP HPSBTRIP HSSTTIME 1 40 No No 113 Enable Enable Enable Enable Enable Enable Enable Enable 415 415 10 ^F dF dF % DHSELECT DHSENSOR DHECONEN DHVHTCFG DHVRAOFF DHVHT_SP DHCOOLSP DHRELHSP 0 1 No 0 0 70 45 55 DISPUNIT LANGUAGE PASS_EBL PASSWORD CNTR_ADJ BRTS_ADJ Off 0 Enable 1111 0 0 DMDLHON DMDHHON DMDLHOFF DMDLCON DMDHCON DMDLCOFF CTRENDLV HTRENDLV CTRENDTM HTRENDTM 1.5 0.5 1 1.5 0.5 1 0.1 0.1 120 120 DMD_CTRL DMT20MA SHED_NUM SHED_DEL SHED_TIM DLSWSP1 DLSWSP2 0 100 0 0 60 80 50 COOL dF dF DEHU DISP DLVT ^F ^F ^F ^F ^F ^F ^F ^F sec sec DMDL 147 % % min % % APPENDIX B — CCN TABLES (cont) SERVICE-CONFIG TABLES (cont) TABLE ECON DISPLAY NAME RANGE Economizer Installed ? Econ. Act.2 Installed ? Economizer Min.Position Economizer Max.Position Economzr trim for sumZ ? Econ ChangeOver Select OA Enthalpy ChgOvr Selct Outdr.Enth Compare Value High OAT Lockout Temp OA Dewpoint Temp Limit Outside Air RH Sensor Outdoor Air CFM Sensor Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband Economizer Prop.Gain Economizer Range Adjust Economizer Speed Adjust Economizer Deadband Unoc Econ Free Cool Cfg Unoc Econ Free Cool Time Un.Ec.Free Cool OAT Lock Econ Serial Number 1 Econ Serial Number 2 Econ Serial Number 3 Econ Serial Number 4 Econ Serial Number 5 Econ Ctrl Angle Lo Limit Yes/No Yes/No 0 - 100 0 - 100 Yes/No 0-3 1-5 18 - 28 55 - 120 50 - 62 Enable/Disable Enable/Dsable 0 - 20000 0 - 20000 200 - 1000 0.7 - 3.0 0.5 - 5 0.1 - 10 0.1 - 2 0-2 0-720 40-70 0-255 0-255 0-255 0-255 0-255 0-90 EDT Reset Configuration Reset Ratio Reset Limit EDT 4-20 ma Reset Input 0-3 0 - 10 0 - 20 Enable/Disable Heating Control Type Heating Supply Air Setpt Occupied Heating Enabled MBB Sensor Heat Relocate Staged Gas Heat Type Max Cap Change per Cycle S.Gas DB min.dF/PID Rate St.Gas Temp. Dead Band Heat Rise dF/sec Clamp LAT Limit Config Limit Switch Switch Monitoring? Limit Switch High Temp Limit Switch Low Temp Heat Control Prop. Gain Heat Control Derv. Gain Heat PID Rate Config Hydronic Ctl.Prop. Gain Hydronic Ctl.Integ. Gain Hydronic Ctl.Derv. Gain Hydronic PID Rate Config Hydronic Ht.Serial Num.1 Hydronic Ht.Serial Num.2 Hydronic Ht.Serial Num.3 Hydronic Ht.Serial Num.4 Hydronic Ht.Serial Num.5 Hydr.Ht.Ctl.Ang.Lo Limit 0-4 80-120 Yes/No Yes/No 0-4 5 - 45 0-5 0-5 0.05 - 0.2 0 - 20 Yes/No 110 - 180 100 - 170 0 - 1.5 0 - 1.5 60 - 300 0 - 1.5 0 - 1.5 0 - 1.5 15 - 300 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 Humidifier Control Cfg. Humidifier Setpoint Humidifier PID Run Rate Humidifier Prop. Gain Humidifier Integral Gain Humidifier Deriv. Gain Humd Serial Number 1 Humd Serial Number 2 Humd Serial Number 3 Humd Serial Number 4 Humd Serial Number 5 Humd Ctrl Angle Lo Limit 0-4 0 - 100 10 - 120 0-5 0-5 0-5 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 UNITS % % BTU/LBM dF dF CFM CFM CFM ^F ^F min dF POINT NAME DEFAULT ECON_ENA ECON_TWO ECONOMIN ECONOMAX ECONTRIM ECON_SEL OAEC_SEL OAEN_CFG OAT_LOCK OADEWCFG OARHSENS OCFMSENS OACFMMAX OACFMMIN OACFM_DB EC_PGAIN EC_RANGE EC_SPEED EC_DBAND UEFC_CFG UEFCTIME UEFCNTLO ECON_SN1 ECON_SN2 ECON_SN3 ECON_SN4 ECON_SN5 ECONCALM Yes No 5 98 Yes 0 4 24 60 55 Disable Dsable 2000 0 400 1 2.5 0.75 0.5 0 120 50 EDRSTCFG RTIO LIMT EDTRSENS 2 3 10 Disable HEATTYPE SASPHEAT HTOCCENA HTLATMON HTSTGTYP HTCAPMAX HT_MR_DB HT_SG_DB HTSGRISE HTLATLIM HTLIMMON HT_LIMHI HT_LIMLO HT_PGAIN HT_DGAIN HTSGPIDR HW_PGAIN HW_IGAIN HW_DGAIN HOTWPIDR HTCL_SN1 HTCL_SN2 HTCL_SN3 HTCL_SN4 HTCL_SN5 HTCLCALM 0 85 No No 0 45 0.5 2 0.06 10 Yes 170 160 1 1 90 1 1 1 90 0 0 0 0 0 85 HUMD_CFG HUSP HUMDRATE HUMID_PG HUMID_IG HUMID_DG HUMD_SN1 HUMD_SN2 HUMD_SN3 HUMD_SN4 HUMD_SN5 HUMDCALM 0 40 30 1 0.3 0.3 0 0 0 0 0 85 85 EDTR ^F HEAT dF ^F ^F dF dF sec sec HUMD 148 % sec APPENDIX B — CCN TABLES (cont) SERVICE-CONFIG TABLES (cont) TABLE IAQ_ DISPLAY NAME RANGE Economizer Min.Position IAQ Demand Vent Min.Pos. Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband IAQ Analog Sensor Config IAQ 4-20 ma Fan Config IAQ Discrete Input Config IAQ Disc.In. Fan Config OAQ 4-20ma Sensor Config IAQ Econo Override Pos. IAQ Override flow Diff.Air Quality LoLimit Diff. Air Quality HiLimit DAQ PPM Fan Off Setpoint DAQ PPM Fan On Setpoint Diff. AQ Responsiveness OAQ Lockout Value User determined OAQ IAQ Low Reference IAQ High Reference OAQ Low Reference OAQ High Reference IAQ Purge IAQ Purge Duration IAQ Purge LoTemp Min Pos IAQ Purge HiTemp Min Pos IAQ Purge OAT Lockout 0 - 100 0 - 100 0 - 20000 0 - 20000 200 - 1000 0-4 0-2 0-2 0-2 0-2 0 - 100 0 - 31000 0 - 1000 100 - 2000 0 - 2000 0 - 2000 -5 - 5 0 - 2000 0 - 5000 0 - 5000 0 - 5000 0 - 5000 0 - 5000 Yes/No 5-60 0-100 0-100 35-70 Static Pressure Config Static Pressure Sensor Static Press. Low Range Static Press. High Range Static Pressure Setpoint VFD-IGV Minimum Speed VFD-IGV Maximum Speed VFD-IGV Fire Speed Over. Stat. Pres. Reset Config SP Reset Ratio SP Reset Limit SP Reset Econo. Position Stat.Pres.PID Run Rate Static Press. Prop. Gain Static Press. Intg. Gain Static Press. Derv. Gain IGV Serial Number 1 IGV Serial Number 2 IGV Serial Number 3 IGV Serial Number 4 IGV Serial Number 5 IGV Cntrl Angle Lo Limit 0-2 Enable/Disable -10 - 0 0 - 10 0-5 0 - 100 0 - 100 0 - 100 0 - 4 (multi-text strings) 0.00 - 2.00 0.00 - 2.00 0 - 100 5 - 120 0-5 0-2 0-5 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 Filter Status Inpt-Clean IGC Feedback - Off RemSw Off-Unoc-Strt-NoOv Enthalpy Input - Low Fan Status Sw. - Off Dmd.Lmt.Sw.1 - Off Dmd.Lmt.Sw.2 - Off IAQ Disc.Input - Low Fire Shutdown - Off Pressurization Sw. - Off Evacuation Sw. - Off Smoke Purge Sw. - Off Dehumidify Sw. - Off Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Air Temp Lvg SF Trim RAT Trim OAT Trim SPT Trim Limit Switch Trim Air Temp Lvg Evap Trim Suct.Press.Circ.A Trim Suct.Press.Circ.B Trim Dis.Press.Circ.A Trim Dis.Press.Circ.B Trim Static Press. Trim (ma) Bldg. Pressure Trim (ma) Outside Air CFM Trim (ma) Supply Air CFM Trim (ma) Return Air CFM (ma) -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -10 - 10 -50 - 50 -50 - 50 -50 - 50 -50 - 50 -2 - 2 -2 - 2 -2 - 2 -2 - 2 -2 - 2 UNITS % % CFM CFM CFM % CFM min % % dF POINT NAME DEFAULT ECONOMIN IAQMINP OACFMMAX OACFMMIN OACFM_DB IAQANCFG IAQANFAN IAQINCFG IAQINFAN OAQANCFG IAQOVPOS IAQOVCFM DAQ_LOW DAQ_HIGH DAQFNOFF DAQFNON IAQREACT OAQLOCK OAQ_USER IAQREFL IAQREFH OAQREFL OAQREFH IAQPURGE IAQPTIME IAQPLTMP IAQPHTMP IAQPNTLO 5 0 2000 0 400 0 0 0 0 0 100 10000 100 700 200 400 0 0 400 0 2000 0 2000 No 15 10 35 50 STATICFG SPSENS SP_LOW SP_HIGH SPSP STATPMIN STATPMAX STATPFSO SPRSTCFG SPRRATIO SPRLIMIT ECONOSPR SPIDRATE STATP_PG STATP_IG STATP_DG IGV_SN1 IGV_SN2 IGV_SN3 IGV_SN4 IGV_SN5 IGV_CALM 0 Disable 0 5 1.5 10 100 100 0 0.20 0.75 5 15 0.5 0.5 0.3 0 0 0 0 0 25 FLTSLOGC GASFANLG RMTINLOG ENTHLOGC SFSLOGIC DMD_SW1L DMD_SW2L IAQINLOG FSDLOGIC PRESLOGC EVACLOGC PURGLOGC DHDISCLG Open Open Open Close Open Open Open Open Open Open Open Open Open SAT_TRIM RAT_TRIM OAT_TRIM SPT_TRIM LSW_TRIM CCT_TRIM SPA_TRIM SPB_TRIM DPA_TRIM DPB_TRIM SPMATRIM BPMATRIM OAMATRIM SAMATRIM RAMATRIM 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 SP__ "H2O % % % % sec SWLG TRIM 149 ^F ^F ^F ^F ^F ^F APPENDIX B — CCN TABLES (cont) SERVICE-CONFIG TABLES (cont) TABLE UNIT DISPLAY NAME RANGE Machine Control Type Fan Mode (0=auto, 1=cont) Remote Switch Config CEM Module Installed Temp.Cmp.Strt.Cool Factr Temp.Cmp.Strt.Heat Factr Fan fail shuts down unit Fan Stat Monitoring Type VAV Unocc.Fan Retry time Unit Size (30-105) 50 Hertz Unit ? MAT Calc Config Type Reset MAT Table Entries? MAT Outside Air Default Altitude……..in feet: Startup Delay Time Auxiliary Relay Config Space Temp Sensor Space Temp Offset Sensor Space Temp Offset Range Space Air RH Sensor Return Air RH Sensor Filter Stat.Sw.Enabled ? Stat. Pres. Reset Sensor 1-6 0-1 0-3 Yes/No 0-60 0-60 Yes/No 0-2 0-720 30-105 Yes/No 0-2 Yes/No 0 - 100 0-60000 0 - 900 0 - 3 (multi-text strings) Enable/Disable Enable/Disable 1 - 10 Enable/Disable Enable/Disable Enable/Disable Enable/Disable POINT_01 Definition POINT_02 Definition POINT_03 Definition POINT_04 Definition POINT_05 Definition POINT_06 Definition POINT_07 Definition POINT_08 Definition POINT_09 Definition POINT_10 Definition POINT_11 Definition POINT_12 Definition POINT_13 Definition POINT_14 Definition POINT_15 Definition POINT_16 Definition POINT_17 Definition POINT_18 Definition POINT_19 Definition POINT_20 Definition 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII 8 CHAR ASCII UNITS POINT NAME CTRLTYPE FAN_MODE RMTINCFG CEM_BRD TCSTCOOL TCSTHEAT SFS_SHUT SFS_MON SAMPMINS UNITSIZE UNIT_HZ MAT_SEL MATRESET MATOAPOS ALTITUDE DELAY AUXRELAY SPTSENS SPTOSENS SPTO_RNG SPRHSENS RARHSENS FLTS_ENA SPRSTSEN min min min % secs DEFAULT 4 1 0 No 0 0 No 0 50 30 No 1 No 20 0 0 0 Disable Disable 5 Disable Disable Disable Disable generics POINT_01 POINT_02 POINT_03 POINT_04 POINT_05 POINT_06 POINT_07 POINT_08 POINT_09 POINT_10 POINT_11 POINT_12 POINT_13 POINT_14 POINT_15 POINT_16 POINT_17 POINT_18 POINT_19 POINT_20 MAINTENANCE DISPLAY TABLES TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS ALARMS01 Active Alarm -----------------------Active Alarm -----------------------Active Alarm -----------------------Active Alarm ------------------------ ascii ascii ascii ascii ascii ascii ascii ascii Compressor A1 Relay Circ A High Press.Switch Compressor A1 Feedback Curr.Sens.Brd. A1 Status CSB A1 Feedback Alarm Comp A1 Locked Out ? Compressor A1 Strikes Enable Compressor A1 Compressor A2 Relay Compressor A2 Feedback Curr.Sens.Brd. A2 Status CSB A2 Feedback Alarm Comp A2 Locked Out ? Compressor A2 Strikes Enable Compressor A2 Compressor B1 Relay Circ B High Press.Switch Compressor B1 Feedback Curr.Sens.Brd. B1 Status CSB B1 Feedback Alarm Comp B1 Locked Out ? Compressor B1 Strikes On/Off On/Off On/Off ascii Enable/Disable Yes/No ALARM_01 ALARM_02 ALARM_03 ALARM_04 follow same format for… ALARMS02 to ALARMS05 COMPRESR Enable/Disable On/Off On/Off ascii Enable/Disable Yes/No Enable/Disable On/Off On/Off On/Off ascii Enable/Disable Yes/No 150 CMPA1 CIRCAHPS CSB_A1 CSBA1ASC CSB_A1EN CMPA1LOK CMPA1STR CMPA1ENA CMPA2 CSB_A2 CSBA2ASC CSB_A2EN CMPA2LOK CMPA2STR CMPA2ENA CMPB1 CIRCBHPS CSB_B1 CSBB1ASC CSB_B1EN CMPB1LOK CMPB1STR config config config config config APPENDIX B — CCN TABLES (cont) MAINTENANCE DISPLAY TABLES (cont) TABLE COMPRESR (cont) DISPLAY NAME RANGE Enable Compressor B1 Compressor B2 Relay Compressor B2 Feedback Curr.Sens.Brd. B2 Status CSB B2 Feedback Alarm Comp B2 Locked Out ? Compressor B2 Strikes Enable Compressor B2 Enable/Disable On/Off On/Off ascii Enable/Disable Yes/No Comp. Security Password Low SP Circ.A Trip 48.0 Low SP Circ.B Trip 48.0 MOP 1/3 Lo SP Trip 28.0 MOP 1/3 Lo DP Trip 242.7 MOP 1/3 Hi SP Trip 75.0 MOP 1/3 Hi DP Trip 430.0 MOP 1/3 Mm DP Trip 3.985 MOP 1/3 Mb DP Tr 131.117 MOP 1/2 Lo SP Trip 28.0 MOP 1/2 Lo DP Trip 242.7 MOP 1/2 Hi SP Trip 61.5 MOP 1/2 Hi DP Trip 430.0 MOP 1/2 Mm DP Trip 5.591 MOP 1/2 Mb DP Trp 156.55 MOP 2/3 Lo SP Trip 28.0 MOP 2/3 Lo DP Trip 316.2 MOP 2/3 Hi SP Trip 57.4 MOP 2/3 Hi DP Trip 430.0 MOP 2/3 Mm DP Trip 3.871 MOP 2/3 Mb DP Trp 207.82 MOP Ful Lo SP Trip 28.0 MOP Ful Lo DP Trip 340.0 MOP Ful Hi SP Trip 52.4 MOP Ful Hi DP Trip 430.0 MOP Ful Mm DP Trip 3.689 MOP Ful Mb DP Trp 103.28 0-10000 Active Demand Limit Percent Total Capacity Demand Limit Select Demand Limit Switch 1 Demand Limit Switch 2 Demand Limit Sw.1 Setpt. Demand Limit Sw.2 Setpt. 4-20 ma Demand Signal Demand Limit at 20 ma CCN Loadshed Signal Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time 0-100 0-100 0-3 On/Off On/Off 0-100 0-100 4-20 0-100 0-99 0-99 0-60 0-120 UNITS Enable/Disable POINT NAME WRITE STATUS CMPB1ENA CMPB2 CSB_B2 CSBB2ASC CSB_B2EN CMPB2LOK CMPB2STR CMPB2ENA config config COMPPASS LSPATRIP LSPBTRIP SP13L_T DP13L_T SP13H_T DP13H_T DP13Mm_T DP13Mb_T SP12L_T DP12L_T SP12H_T DP12H_T DP12Mm_T DP12Mb_T SP23L_T DP23L_T SP23H_T DP23H_T DP23Mm_T DP23Mb_T SPFLL_T DPFLL_T SPFLH_T DPFLH_T DPFLMm_T DPFLMb_T config config config config config config config config config config config config config config config config config config config config config config config config config config config DEM_LIM CAPTOTAL DMD_CTRL DMD_SW1 DMD_SW2 DLSWSP1 DLSWSP2 DMDLMTMA DMT20MA DL_STAT SHED_NUM SHED_DEL SHED_TIM forcible config COMPTRIP PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG PSIG DMANDLIM % % % % ma % % min config forcible forcible config config forcible config config config config ECON_MIN Economizer Act.Cmd.Pos. Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Econo Current Min. Pos. Econo Current Min. CFM Outside Air CFM Diff.Air Quality in PPM IAQ Min.Pos.Override Econ Remote 10K Pot Val. IAQ - PPM Return CO2 OAQ - PPM Return CO2 IAQ - Discrete Input IAQ Demand Vent Min.Pos. Economizer Min.Position IAQ Demand Vent Min.Flow Economizer Min.Flow Econ OACFM MinPos Deadbd IAQ Analog Sensor Config IAQ 4-20 ma Fan Config IAQ Discrete Input Confg IAQ Disc.In. Fan Config IAQ Econo Override Pos. Diff.Air Quality LoLimit Diff.Air Quality HiLimit DAQ PPM Fan Off Setpoint DAQ PPM Fan On Setpoint Diff. AQ Responsiveness IAQ Low Reference IAQ High Reference OAQ Lockout Value OAQ 4-20ma Sensor Config IAQ milliamps OAQ milliamps % % % % CFM CFM % % % CFM CFM CFM % ma ma 151 ECONOCMD ECONOPOS ECON2POS ECMINPOS ECMINCFM OACFM DAQ IAQMINOV ECON_POT IAQ OAQ IAQIN IAQMINP ECONOMIN OACFMMIN OACFMMAX OACFM_DB IAQANCFG IAQANFAN IAQINCFG IAQINFAN IAQOVPOS DAQ_LOW DAQ_HIGH DAQFNOFF DAQFNON IAQREACT IAQREFL IAQREFH OAQLOCK OAQANCFG IAQ_MA OAQ_MA forcible forcible forcible forcible forcible forcible config config config config config config config config config config config config config config config config config config config APPENDIX B — CCN TABLES (cont) MAINTENANCE DISPLAY TABLES (cont) TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS EC_DIAG Economizer Active ? Conditions which prevent economizer being active: Econ Act. Unavailable? Econ 2 Act. Unavailable? Enth.Switch Read High ? DBC - OAT lockout? DEW - OA Dewpt. lockout? DDBC- OAT > RAT lockout? OAEC- OA Enth Lockout? DEC - Diff.Enth.Lockout? EDT Sensor Bad ? OAT Sensor Bad ? Economizer forced ? Supply Fan not on 30s ? Cool Mode not in effect? OAQ lockout in effect ? Econ recovery hold off? Dehumid. Disabled Econ.? Outside Air Temperature OutsideAir DewPoint Temp Outside Air Rel.Humidity Outdoor Air Enthalpy Return Air Temperature Return Air Rel.Humidity Return Air Enthalpy High OAT Lockout Temp Econ ChangeOver Select OA Enthalpy ChgOvr Selct Outdr.Enth Compare Value OA Dewpoint Temp Limit Supply Fan Relay Economizer Act.Cmd.Pos. Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Evaporator Discharge Tmp Economizer Control Point EDT Trend in degF/minute Economizer Prop.Gain Economizer Range Adjust Economizer Speed Adjust Economizer Deadband Economizer Timer Yes/No ECACTIVE Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No ECONUNAV ECN2UNAV ENTH DBC_STAT DEW_STAT DDBCSTAT OAECSTAT DEC_STAT EDT_STAT OAT_STAT ECONFORC SFONSTAT COOL_OFF OAQLOCKD ECONHELD DHDISABL OAT OADEWTMP OARH OAE RAT RARH RAE OAT_LOCK ECON_SEL OAEC_SEL OAEN_CFG OADEWCFG SFAN ECONOCMD ECONOPOS ECON2POS EDT ECONCPNT EDTTREND EC_PGAIN EC_RANGE EC_SPEED EC_DBAND ERATETMR dF dF % dF % dF dF % % % dF dF ^F ^F ^F sec forcible forcible forcible forcible config config config config config forcible config config config config config ENTHALPY Outdoor Air Enthalpy Outside Air Temperature Outside Air Rel.Humidity Outside Air RH Sensor OA Dewpoint Temp Limit OutsideAir DewPoint Temp OutsideAir Humidty Ratio OA H2O Vapor Sat.Pressur OA H2O Partial.Press.Vap Space Enthalpy Space Temperature Controlling Space Temp Space Relative Humidity Space Temp Sensor Space Air RH Sensor Return Air Enthalpy Return Air Temperature Controlling Return Temp Return Air Rel.Humidity Return Air RH Sensor Altitude……..in feet: Atmospheric Pressure dF % dF dF "Hg "Hg dF dF % dF dF % "Hg OAE OAT OARH OARHSENS OADEWCFG OADEWTMP OA_HUMR OA_PWS OA_PWS SPE SPT SPACE_T SPRH SPTSENS SPRHSENS RAE RAT RETURN_T RARH RARHSENS ALTITUDE ATMOPRES forcible forcible config forcible forcible forcible forcible config config forcible forcible forcible config config config HUMIDITY Space Relative Humidity Return Air Rel.Humidity Humidifier Relay Humidifier Act.Curr.Pos. Humidifier Command Pos. Humidifier Setpoint Humidifier Control Config Humidifier Prop. Gain Humidifier Integral Gain Humidifier Deriv. Gain Humidifier PID Run Rate Space Air RH Sensor Return RH Sensor % % % % % sec Enable/Disable Enable/Disable 152 SPRH RARH HUMIDRLY HUMDRPOS HUMDCPOS HUSP HUMD_CFG HUMID_PG HUMID_IG HUMID_DG HUMDRATE SPRHSENS RARHSENS forcible forcible config config config config config config config config APPENDIX B — CCN TABLES (cont) MAINTENANCE DISPLAY TABLES (cont) TABLE LEN_ACTU DISPLAY NAME Economizer Act.Curr.Pos. Economzr 2 Act.Curr.Pos. Economizer Act.Cmd.Pos. IGV Actuator Current Pos. IGV Actuator Command Pos Humidifier Act.Curr.Pos. Humidifier Command Pos. Ht.Coil Act.Curr.Pos. Ht.Coil Command Position BP 1 Actuator Curr.Pos. BP 1 Command Position BP 2 Actuator Curr.Pos. BP 2 Command Position Find LEN bus actuator ? BELx Serial Number- RANGE 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 0-100 Yes/No UNITS % % % % % % % % % % % % % POINT NAME ECONOPOS ECON2POS ECONOCMD IGV_RPOS IGV_CPOS HUMDRPOS HUMDCPOS HTCLRPOS HTCLCPOS BP1_RPOS BP1_CPOS BP2_RPOS BP2_CPOS BELSERCH BELXSNUM WRITE STATUS forcible config LINKDATA Supervisory Element # Supervisory Bus Supervisory Block Number Average Occup. Heat Stp. Average Occup. Cool Stp. Average Unocc. Heat Stp. Average Unocc. Cool Stp. Average Zone Temperature Average Occup. Zone Temp Linkage System Occupied? Next Occupied Day Next Occupied Time Next Unoccupied Day Next Unoccupied Time Last Unoccupied Day Last Unoccupied Time dF dF dF dF dF dF SUPE-ADR SUPE-BUS BLOCKNUM AOHS AOCS AUHS AUCS AZT AOZT LOCC LNEXTOCD LNEXTOCC LNEXTUOD LNEXTUNC LLASTUOD LLASTUNC MILLIAMP IAQ milliamps OAQ milliamps SP Reset milliamps 4-20 ma Demand Signal EDT Reset milliamps OARH milliamps SPRH milliamps RARH milliamps SACFM milliamps RACFM milliamps OACFM milliamps BP milliamps SP milliamps ma ma ma ma ma ma ma ma ma ma ma ma ma IAQ_MA OAQ_MA SPRST_MA DMDLMTMA EDTRESMA OARH_MA SPRH_MA RARH_MA SACFM_MA RACFM_MA OACFM_MA BP_MA SP_MA MODES System Mode…………: HVAC Mode…………..: Control Mode………..: Currently Occupied Timed Override in effect DCV resetting min pos Supply Air Reset Demand Limit in Effect Temp.Compensated Start IAQ pre-occ purge active Linkage Active - DAV Mech.Cooling Locked Out HVAC Mode Numerical Form ascii text strings ascii text strings ascii text strings On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off On/Off number Current Day, Time & Date: Occupancy Controlled By: ascii date & time ascii text ascii text ascii text Yes/No MODEOCCP MODETOVR MODEADCV MODESARS MODEDMLT MODETCST MODEIQPG MODELINK MODELOCK MODEHVAC OCCDEFME Currently Occupied Current Occupied Time Current Unoccupied Time Next Occupied Day & Time Next Unocc. Day & Time Last Unocc. Day & Time Current Occup. Period # Timed-Override in Effect Timed-Override Duration Yes/No hours 153 TIMEDATE OCDFTXT1 OCDFTXT2 OCDFTXT3 MODE_OCC STRTTIME ENDTIME NXTOC_DT NXTUN_DT PRVUN_DT PER_NO OVERLAST OVR_HRS forcible APPENDIX B — CCN TABLES (cont) MAINTENANCE DISPLAY TABLES (cont) TABLE PRESBLDG DISPLAY NAME Building Pressure Return Air CFM Supply Air CFM Power Exhaust Relay 1 Power Exhaust Relay 2 BP 1 Actuator Curr.Pos. BP 1 Command Position BP 2 Actuator Curr.Pos. BP 2 Command Position Exhaust Fan VFD Speed Building Pressure Setp. BP Setpoint Offset Fan Track Learn Enable Fan Track Learn Rate Fan Track Initial DCFM Fan Track Max Clamp Fan Track Max Correction Fan Track Internl EEPROM Fan Track Reset Internal Fan Track Internal RAM Fan Track Control D.CFM RANGE UNITS "H2O CFM CFM On/Off On/Off % % % % % "H2O ^"H2O Yes/No min CFM CFM CFM CFM CFM CFM POINT NAME BP RACFM SACFM PE1 PE2 BP1_RPOS BP1_CPOS BP2_RPOS BP2_CPOS EFAN_VFD BPSP BPSO DCFM_CFG DCFMRATE DCFMSTRT DCFM_MAX DCFM_ADJ DCFM_OFF DCFMRSET DCFM_RAM DELTACFM WRITE STATUS config config config config config config config config config PRESDUCT Static Pressure Supply Fan VFD Speed IGV Actuator Current Pos IGV Actuator Command Pos Static Pressure Setpoint Static Pressure Reset "H2O % % % "H2O SP SFAN_VFD IGV_RPOS IGV_CPOS SPSP SPRESET config forcible STAGEGAS Heating Mode………..: Requested Heat Stage Heating Control Point Staged Gas LAT Sum Staged Gas LAT 1 Staged Gas LAT 2 Staged Gas LAT 3 Staged Gas Limit Sw.Temp Heat PID Timer Staged Gas Capacity Calc Current Running Capacity Proportional Cap. Change Derivative Cap. Change Maximum Heat Stages Hi Limit Switch Tmp Mode LAT Cutoff Mode Capacity Clamp Mode ascii text strings dF dF dF dF dF sec % % HT_STAGE HEATCPNT LAT_SGAS LAT1SGAS LAT2SGAS LAT3SGAS LIMSWTMP HTSGTIMR HTSGCALC HTSG_CAP HTSG_P HTSG_D HTMAXSTG LIMTMODE LATCMODE CAPMODE STRTHOUR Compressor A1 Run Hours Compressor A2 Run Hours Compressor B1 Run Hours Compressor B2 Run Hours Compressor A1 Starts Compressor A2 Starts Compressor B1 Starts Compressor B2 Starts hours hours hours hours HR_A1 HR_A2 HR_B1 HR_B2 CY_A1 CY_A2 CY_B1 CY_B2 Cooling Control Point Mixed Air Temperature Evaporator Discharge Tmp Return Air Temperature Outside Air Temperature Econo Damper Current Pos Economzr 2 Act.Curr.Pos. Capacity Threshold Adjst Capacity Load Factor Next Stage EDT Decrease Next Stage EDT Increase Rise Per Percent Capacity Cap Deadband Subtracting Cap Deadband Adding Cap Threshold Subtracting Cap Threshold Adding High Temp Cap Override Low Temp Cap Override Pull Down Cap Override Slow Change Cap Override dF dF dF dF dF % % COOLCPNT MAT EDT RAT OAT ECONOPOS ECON2POS Z_GAIN SMZ ADDRISE SUBRISE RISE_PCT Y_MINUS Y_PLUS Z_MINUS Z_PLUS HI_TEMP LOW_TEMP PULLDOWN SLO_CHNG config config config config config config config config SUMZ On/Off On/Off On/Off On/Off 154 forcible forcible config APPENDIX B — CCN TABLES (cont) MAINTENANCE DISPLAY TABLES (cont) TABLE DISPLY NAME RANGE UNITS POINT NAME WRITE STATUS SYSTEM Reset All Current Alarms Reset Alarm History Reset the Device Local Machine Disable Soft Stop Request Emergency Stop CEM AN4 10K temp J5, 7-8 CEM AN5 10K temp J5, 9-10 CEM AN6 10K temp J5, 11-12 CEM AN1 10K temp J5, 1-2 CEM AN4 4-20 ma J5, 7-8 CEM AN5 4-20 ma J5, 9-10 CEM AN6 4-20 ma J5, 11-12 CEM AN1 4-20 ma J5, 1-2 Yes/No Yes/No Yes/No Yes/No Yes/No Enable/Disable ALRESET ALHISCLR RESETDEV UNITSTOP SOFTSTOP EMSTOP CEM10K1 CEM10K2 CEM10K3 CEM10K4 CEM4201 CEM4202 CEM4203 CEM4204 Economizer Act.Cmd.Pos. Economizer Calibrate Cmd Econ Act. Control Angle Economzr 2 Act.Cmd.Pos. Economzr 2 Calibrate Cmd Econ2 Act. Control Angle IGV Actuator Command Pos IGV Act. Calibrate Cnd IGV Act. Control Angle VFD-IGV Maximum Speed BP 1 Command Position BP 1 Actuator Cal Cmd BP Act.1 Control Angle BP 1 Actuator Max Pos. BP 2 Command Position BP 2 Actuator Cal Cmd BP Act.2 Control Angle BP 2 Actuator Max Pos. Ht.Coil Command Position Heating Coil Act. Cal.Cmd Heat Coil Act.Ctl.Angle Humidifier Command Pos. Humidifier Act. Cal.Cmd Humidifier Act.Ctrl.Ang. 0-100 YES/NO read only 0-100 YES/NO read only 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 0-100 YES/NO read only 0-100 YES/NO read only Econo Damper Command Pos Static Pressure Setpoint Requested Cool Stage Lead/Lag Select Test Compressor A1 Relay Unloader 1 - Comp A1 Unloader 2 - Comp A1 Compressor A2 Relay Compressor B1 Relay Unloader 1 - Comp B1 Unloader 2 - Comp B1 Compressor B2 Relay 0-100 0-5 0-n LEAD/LAG ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF Fan Test Automatic? Econo Damper Command Pos Supply Fan Relay IGV Actuator Command Pos Supply Fan VFD Speed Power Exhaust Relay 1 Power Exhaust Relay 2 BP 1 Command Position BP 2 Command Position Exhaust Fan VFD Speed Condenser Fan Circuit A Condenser Fan Circuit B Motormaster Condensr Fan ON/OFF 0-100 0-100 ON/OFF ON/OFF 0-100 0-100 0-100 ON/OFF ON/OFF ON/OFF Requested Heat Stage Heat Relay 1 Heat Relay 2 Relay 3 W1 Gas Valve 2 Relay 4 W2 Gas Valve 2 Relay 5 W1 Gas Valve 3 Relay 6 W2 Gas Valve 3 Heat Interlock Relay Ht.Coil Command Position 0-n ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF 0-100 Humidifier Relay Remote Alarm / Aux Relay ON/OFF ON/OFF HUMR_TST ALRM_TST MBB CESR131292RCB CESR131249ECB CESR131249SCB CESR131226CEM CESR131174Economizr Serial NumberIGV Serial NumberHumidfier Serial NumberHeat Coil Serial NumberBP #1 Serial NumberBP #2 Serial NumberMARQUEE CESR131171NAVIGATOR CESR130227- ascii version# ascii version# ascii version# ascii version# ascii version# ascii serial num ascii serial num ascii serial num ascii serial num ascii serial num ascii serial num ascii version# ascii version# MBB_SW RCB_SW ECB_SW SCB_SW CEM_SW ECONSNUM IGV_SNUM HUMDSNUM HTCLSNUM BP1_SNUM BP2_SNUM MARQ_SW NAVI_SW TESTACTC % % % % % % % % % % ECONOTST ECONOCAL ECONCANG ECON2TST ECON2CAL ECN2CANG SPIGVTST IGV_CAL IGC_CANG STATPMAX BLDG1TST BLDG1CAL BP1_CANG BP1SETMX BLDG2TST BLDG2CAL BP2_CANG BP2SETMX HTCLACTC HCOILCAL HTCLCANG HUMD_TST HUMIDCAL HUMDCANG TESTCOOL % "H2O ECONCOOL SPSP_TST CLST_TST LL_TST CMPA1TST UNL1_TST UNL2_TST CMPA2TST CMPB1TST UNL3_TST UNL4_TST CMPB2TST TESTFANS YES/NO % % % % % % FANAUTO ECONFANS SFAN_TST IGVFNTST SGVFDTST PE1_TST PE2_TST BLDPTST1 BLDPTST2 EFVFDTST CNDA_TST CNDB_TST PCFABTST TESTHEAT % HTST_TST HS1_TST HS2_TST HS3_TST HS4_TST HS5_TST HS6_TST HIR_TST HTCLHEAT TESTINDP VERSIONS 155 config config config config forcible forcible forcible forcible forcible forcible forcible forcible forcible forcible APPENDIX B — CCN TABLES (cont) TIME SCHEDULE CONFIG TABLE Allowable Entries: Day not selected = 0 Day selected = 1 Period 1: Period 2: Period 3: Period 4: Period 5: Period 6: Period 7: Period 8: DAY FLAGS MTWTFSSH OCCUPIED TIME UNOCCUPIED TIME 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00000000 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 APPENDIX C — UNIT STAGING TABLES STAGING SEQUENCE — SIZE 030 UNITS — 60 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 0 0 1 1 1 u1 0 1 1 0 0 0 0 0 0 0 0 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 0 0 0 1 0 u4 0 0 0 0 1 0 0 0 1 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 16% 32% 50% 66% 82% 100% 0% 16% 32% 50% 66% 82% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 030 UNITS — 50 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 0 1 1 1 1 1 u1 0 1 1 1 0 0 0 0 0 0 1 1 0 0 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 0 u4 0 0 1 0 1 0 0 0 1 0 1 0 1 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 u4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 29% 43% 57% 71% 85% 100% 0% 14% 28% 43% 57% 71% 85% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 035 UNITS CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 1 0 0 1 1 1 1 1 u1 0 1 1 1 1 1 1 0 0 0 1 1 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 1 1 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 0 LEGEND a,b — Compressor Circuit Designation u — Unloader 156 PERCENT 0% 14% 28% 43% 57% 71% 85% 100% 0% 29% 43% 57% 71% 85% 100% APPENDIX C — UNIT STAGING TABLES (cont) STAGING SEQUENCE — SIZE 040 UNITS — 60 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 0 1 2 3 4 Lag 0 — Off 1 — On a1 0 1 1 1 1 0 0 0 1 1 u1 0 1 0 0 0 0 0 0 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 1 0 0 0 1 0 u4 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 25% 50% 75% 100% 0% 25% 50% 75% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 040 UNITS — 50 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 1 1 0 0 0 1 1 1 1 1 u1 0 1 1 1 1 1 1 0 0 0 0 0 1 1 1 0 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 1 0 0 1 0 u4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 u4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 19% 37% 41% 59% 62% 80% 89% 100% 0% 22% 43% 59% 62% 80% 89% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 050 UNITS CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 1 1 1 1 1 u1 0 1 1 0 1 1 0 0 0 1 1 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 1 1 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 0 PERCENT 0% 19% 37% 57% 62% 80% 100% 0% 22% 41% 59% 62% 80% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 055 UNITS — 60 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 0 1 2 3 4 5 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 0 0 0 1 1 1 u1 0 1 1 0 0 0 0 0 0 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 0 0 0 1 0 LEGEND a,b — Compressor Circuit Designation u — Unloader 157 u4 0 0 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 20% 40% 60% 80% 100% 0% 20% 40% 60% 80% 100% APPENDIX C — UNIT STAGING TABLES (cont) STAGING SEQUENCE — SIZE 055 UNITS — 50 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 11 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 1 1 1 1 0 0 0 1 1 1 1 1 1 1 1 1 u1 0 1 1 1 1 1 1 0 1 0 0 0 0 0 1 1 1 1 1 0 1 0 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 1 0 1 1 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 1 1 0 0 1 0 u4 0 0 0 0 1 0 0 1 0 0 0 0 1 0 1 0 1 0 0 1 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 19% 37% 48% 51% 62% 66% 71% 80% 86% 100% 0% 14% 29% 33% 48% 51% 62% 66% 71% 80% 86% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 060 UNITS — 60 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 0 0 1 1 1 u1 0 1 1 0 0 0 0 0 0 0 0 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 0 0 0 1 0 u4 0 0 0 0 1 0 0 0 1 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 17% 33% 50% 67% 83% 100% 0% 17% 33% 50% 67% 83% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 060 UNITS — 50 Hz CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 0 0 1 1 1 u1 0 1 1 0 0 0 0 0 0 0 0 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 0 0 0 1 0 LEGEND a,b — Compressor Circuit Designation u — Unloader 158 u4 0 0 0 0 1 0 0 0 1 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PERCENT 0% 17% 33% 50% 67% 83% 100% 0% 17% 33% 50% 67% 83% 100% APPENDIX C — UNIT STAGING TABLES (cont) STAGING SEQUENCE — SIZE 070 AND 075 UNITS CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 1 1 0 0 1 1 1 1 1 1 1 u1 0 1 1 0 1 1 1 1 0 0 0 1 1 1 1 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 0 0 0 0 0 0 0 1 1 1 0 1 1 0 0 1 1 1 0 1 1 0 0 1 1 1 0 1 0 0 0 1 0 0 0 1 0 u4 0 0 0 0 0 0 0 0 0 0 1 1 1 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 u4 0 0 0 0 1 0 0 0 1 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 u4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 b2 0 0 0 0 0 0 0 0 1 1 0 0 0 1 1 1 1 1 1 1 PERCENT 0% 14% 29% 43% 51% 66% 71% 86% 100% 0% 19% 33% 48% 51% 66% 71% 86% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 090 UNITS CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 0 1 2 3 4 5 6 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 0 0 0 0 1 1 1 u1 0 1 1 0 0 0 0 0 0 0 0 1 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 0 0 0 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 1 0 0 0 1 0 0 0 1 0 PERCENT 0% 17% 33% 50% 67% 83% 100% 0% 17% 33% 50% 67% 83% 100% LEGEND a,b — Compressor Circuit Designation u — Unloader STAGING SEQUENCE — SIZE 105 UNITS CIRCUIT A STAGE Lead 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 Lag 0 — Off 1 — On a1 0 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 1 1 1 1 u1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 0 1 1 0 1 0 COMPRESSOR OR UNLOADER u2 a2 b1 u3 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 1 1 1 0 1 1 1 0 1 1 0 0 1 1 1 0 1 1 0 0 0 0 0 0 0 1 1 0 0 1 0 0 0 1 1 0 0 1 0 0 0 1 1 0 0 1 0 0 0 1 0 0 1 1 0 0 1 1 0 LEGEND a,b — Compressor Circuit Designation u — Unloader 159 PERCENT 0% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0% 20% 30% 40% 50% 60% 70% 80% 90% 100% APPENDIX D — VFD INFORMATION condensation from forming on the boards during the off mode and is stopped by driving the speed to 0 (by sending a 4 mA signal to the VFD). The Z Series units use ABB VFDs. The interface wiring for the VFDs is shown in Fig. A. The VFD connects through an isolation board to the 4 to 20 mA RCB board. Terminal designations are shown in Table A. Configurations are shown in Table B. On variable air volume units with optional VFD, the supply fan speed is controlled by a 3-phase VFD. The VFD is located in the supply fan section (030-050 units) or mixing box section (055-105 units) behind an access door. The VFD speed is controlled directly by the ComfortLink™ controls through a 4 to 20 mA signal based on a supply duct pressure sensor. The VFD has a display, which can be used for service diagnostics, but setup of the building pressure and control loop factors should be done through the scrolling marquee display. The VFD is powered during normal operation to prevent Table A — VFD Terminal Designations TERMINAL U1 V1 W1 U2 V2 W2 X1-11 (GND) X1-12 (COMMON) X1-10 (24 VDC) X1-13 (DI-1) X1-10 (24 VDC) X1-16 (DI-4) X1-2 (AI-1) X1-3 (AGND) FUNCTION Three-Phase Main Circuit Input Power Supply Three-Phase AC Output to Motor, 0 V to Maximum Input Voltage Level Factory-supplied jumper Run (factory-supplied jumper) Start Enable 1 (Factory-supplied jumper). When opened the drive goes to emergency stop. Factory wired for 4 to 20 mA remote input Fig. A — VFD Wiring 160 APPENDIX D — VFD INFORMATION (cont) Table B — VFD Configurations PARAMETER GROUP Start-Up Data Start/Stop/Dir Analog Inputs Relay Outputs System Controls OVER RIDE Accel/Decel MOTOR PARAMETER TITLE LANGUAGE APPLIC MACRO MOTOR CTRL MODE MOTOR NOM VOLT MOTOR NOM CURR MOTOR NOM FREQ MOTOR NOM SPEED EXT1 COMMANDS DIRECTION MINIMUM AI1 MAXIMUM AI1 RELAY OUTPUT 1 RELAY OUTPUT 2 RELAY OUTPUT 3 RUN ENABLE START ENABLE 1 OVERRIDE SEL OVERRIDE FREQ OVERRIDE SPEED OVER PASS CODE OVERRIDE STOP FUNCTION ACCELER TIME 1 DECELER TIME 1 SWITCHING FREQ PARAMETER INDEX 9901 9902 9904 9905 9906 9907 9908 1001 1003 1301 1302 1401 1402 1403 1601 1608 1701 1702 1703 1704 1705 2102 2202 2203 2606 CARRIER DEFAULT ENGLISH USER 1 SCALAR: FREQ 460v *TBD* 60 Hz 1750 rpm DI-1 REVERSE 20.0 % 100.0 % STARTED RUN FAULT (-1) NOT SELECTED DI-4 DI-3 60 Hz 1750 rpm ENTERED ON RAMP 30.0s 30.0s 8 kHz VFD Operation — The VFD keypad is shown in Fig. B. The function of SOFT KEYS 1 and 2 change depending on what is displayed on the screen. The function of SOFT KEY 1 matches the word in the lower left-hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower right-hand box on the display screen. If the box is empty, then the SOFT KEY does not have a function on that specific screen. The UP and DOWN keys are used to navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the drive to automatic control. The HAND key is used to change control of the drive to local (hand held) control. The HELP button is used to access the help screens. Fig. B — VFD Keypad 161 APPENDIX D — VFD INFORMATION (cont) STANDARD DISPLAY MODE — Use the standard display mode to read information on the drive status and operate the drive. To reach the standard display mode, press EXIT until the LCD display shows status information as described below. See Fig. C. The top line of the LCD display shows the basic status information of the drive. The HAND icon indicates that the drive control is local from the control panel. The AUTO icon indicates that the drive is in remote control mode, such as the basic I/O (X1) or field bus. The arrow icon indicates the drive and motor rotation status. A rotating arrow (clockwise or counterclockwise) indicates that the drive is running and at set point and the shaft direction is forward or reverse. A rotating blinking arrow indicates that the drive is running but not at set point. A stationary arrow indicates that the drive is stopped. For Carrier rooftop units, the correct rotation is counterclockwise. The upper right corner shows the frequency set point that the drive will maintain. Using parameter group 34, the middle of the LCD display can be configured to display 3 parameter values. The default display shows parameters 0103 (OUTPUT FREQ) in percentages, 0104 (CURRENT) in amperes, and 0120 (AI1) in milliamperes. The bottom corners of the LCD display show the functions currently assigned to the two soft keys. The lower middle displays the current time (if configured to show the time). The first time the drive is powered up, it is in the OFF mode. To switch to local hand-held control and control the drive using the control panel, press and hold the HAND button. Pressing the HAND button switches the drive to hand control while keeping the drive running. Press the AUTO button to switch to remote input control. To start the drive press the HAND or AUTO buttons, to stop the drive press the OFF button. To adjust the speed in HAND mode, press the UP or DOWN buttons (the reference changes immediately). The reference can be modified in the local control (HAND) mode, and can be parameterized (using Group 11 reference select) to also allow modification in the remote control mode. PARAMETERS MODE — The Parameters mode is used to change the parameters on the drive. To change parameters, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2). 5. Use the UP or DOWN keys to change the value of the parameter. 6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed. 7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu. NOTE: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the Carrier application macro. START UP WITH ASSISTANT — Initial start-up has been performed at the factory. To start up the VFD with the Start-Up Assistant or reset the VFD with the Carrier defaults, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight ASSISTANTS on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight Carrier Assistant and press SEL (SOFT KEY 2). 4. The Carrier Assistant will ask questions to determine the correct parameters for the VFD. Select the desired values and press SAVE (SOFT KEY 2) after every change. The process will continue until all the parameters are set. a. The Carrier Assistant will ask “Is this an Air Handler or Rooftop?” Select “Rooftop.” b. The Carrier Assistant will ask “Is this a High E or Premium E motor?” Select the correct efficiency type. c. If the VFD can be used with two different size (HP) motors, then the Carrier Assistant will ask the user to choose the proper HP. Select the correct motor horsepower. START UP BY CHANGING PARAMETERS INDIVIDUALLY — Initial start-up is performed at the factory. To start up the VFD with by changing individual parameters, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight PARAMETERS on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight the desired parameter group and press SEL (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight the desired parameter and press EDIT (SOFT KEY 2). 5. Use the UP or DOWN keys to change the value of the parameter. 6. Press SAVE (SOFT KEY 2) to store the modified value. Press CANCEL (SOFTKEY 1) to keep the previous value. Any modifications that are not saved will not be changed. 7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Continue until all the parameters have been configured and then press EXIT (SOFT KEY 1) to return to the main menu. NOTE: The current parameter value appears above the highlight parameter. To view the default parameter value, press the UP and DOWN keys simultaneously. To restore the default factory settings, select the application macro “HVAC Default.” VFD Modes — The VFD has several different modes for configuring, operating, and diagnosing the VFD. The modes are: • Standard Display mode — shows drive status information and operates the drive • Parameters mode — edits parameter values individually • Start-up Assistant mode — guides the start up and configuration • Changed Parameters mode — shows all changed parameters • Drive Parameter Backup mode — stores or uploads the parameters • Clock Set mode — sets the time and date for the drive • I/O Settings mode — checks and edits the I/O settings 162 APPENDIX D — VFD INFORMATION (cont) Upload All Parameters — To upload and store parameters in the control panel from the VFD, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight UPLOAD TO PANEL and press SEL (SOFT KEY 2). 4. The text “Copying Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1). 5. When the upload is complete, the text “Parameter upload successful” will be displayed. 6. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu. 7. The control panel can now be disconnected from the drive. Download All Parameters — To download all parameters from the control panel to the VFD, perform the following procedure: 1. Install the control panel with the correct parameters onto the VFD. 2. Select MENU (SOFT KEY 2). The Main menu will be displayed. 3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight DOWNLOAD TO DRIVE ALL and press SEL (SOFT KEY 2). 5. The text “Restoring Parameters” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1). 6. When the download is complete, the text “Parameter download successful” will be displayed. 7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu. 8. The control panel can now be disconnected from the drive. Download Application Parameters — To download application parameters only to the control panel from the VFD, perform the following procedure: 1. Install the control panel with the correct parameters onto the VFD. 2. Select MENU (SOFT KEY 2). The Main menu will be displayed. 3. Use the UP or DOWN keys to highlight PAR BACKUP on the display screen and press ENTER (SOFT KEY 2). 4. Use the UP or DOWN keys to highlight DOWNLOAD APPLICATION and press SEL (SOFT KEY 2). 5. The text “Downloading Parameters (partial)” will be displayed with a progress indicator. To stop the process, select ABORT (SOFT KEY 1). 6. When the download is complete, the text “Parameter download successful” will be displayed. 7. The display will then return to the PAR BACKUP menu. Select EXIT (SOFT KEY 1) to return to the main menu. 8. The control panel can now be disconnected from the drive. Fig. C — Standard Display Example START-UP ASSISTANT MODE — To use the Start-Up Assistant, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight ASSISTANTS on the display screen and press ENTER (SOFT KEY 2). 3. Use the UP or DOWN keys to highlight Commission Drive and press SEL (SOFT KEY 2). 4. The Start-Up Assistant will display the parameters that need to be configured. Select the desired values and press SAVE (SOFT KEY 2) after every change. The process will continue until all the parameters are set. The assistant checks to make sure that entered values are in range. The assistant is divided into separate tasks. The user can activate the tasks one after the other or independently. The tasks are typically done in this order: Application, References 1 and 2, Start/Stop Control, Protections, Constant Speeds, PID Control, Low Noise Setup, Panel Display, Timed Functions, and Outputs. CHANGED PARAMETERS MODE — The Changed Parameters mode is used to view and edit recently changed parameters on the drive. To view the changed parameters, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight CHANGED PAR on the display screen and press ENTER (SOFT KEY 2). A list of the recently changed parameters will be displayed. 3. Use the UP or DOWN keys to highlight the desired parameter group and press EDIT (SOFT KEY 2) to change the parameter if desired. 4. Press EXIT (SOFT KEY 1) to exit the Changed Parameters mode. DRIVE PARAMETER BACKUP MODE — The drive parameter back up mode is used to export the parameters from one drive to another. The parameters can be uploaded from a VFD to the removable control panel. The control panel can then be transferred to another drive and the parameters downloaded into memory. Depending on the motor and application, there are two options available. The first option is to download all parameters. This copies both application and motor parameters to the drive from the control panel. This is recommended when using the same application for drives of the same size. This can also be used to create a backup of the parameters group for the drive. The second option downloads only the application parameters to the drive. This is recommended when using the same application for drives of different sizes. Parameters 9905, 9906, 9907, 9908, 9909, 1605, 1607, 5201, and group 51 parameters and internal motor parameters are not copied. 163 APPENDIX D — VFD INFORMATION (cont) CLOCK SET MODE — The clock set mode is used for setting the date and time for the internal clock of the VFD. In order to use the timer functions of the VFD control, the internal clock must be set. The date is used to determine weekdays and is visible in the fault logs. To set the clock, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight CLOCK SET on the display screen and press ENTER (SOFT KEY 2). The clock set parameter list will be displayed. 3. Use the UP or DOWN keys to highlight CLOCK VISIBILITY and press SEL (SOFT KEY 2). This parameter is used to display or hide the clock on the screen. Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 4. Use the UP or DOWN keys to highlight SET TIME and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the hours and minutes. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 6. Use the UP or DOWN keys to highlight SET DATE and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the day, month, and year. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 7. Use the UP or DOWN keys to highlight DATE FORMAT and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 8. Press EXIT (SOFT KEY 1) twice to return to the main menu. I/O SETTINGS MODE — The I/O Settings mode is used for viewing and editing the I/O settings. To configure the I/O settings, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 2. Use the UP or DOWN keys to highlight I/O SETTINGS on the display screen and press ENTER (SOFT KEY 2). The I/O Settings parameter list will be displayed. 3. Use the UP or DOWN keys to highlight the desired I/O setting and press SEL (SOFT KEY 2). 4. Use the UP or DOWN keys to select the parameter to view. Press OK (SOFT KEY 2). 5. Use the UP or DOWN keys to change the parameter setting. Press SAVE (SOFT KEY 2) to save the configuration. Press CANCEL (SOFT KEY 1) to keep the previous value. Any modifications that are not saved will not be changed. 6. Press EXIT (SOFT KEY 1) twice to return to the main menu. Third Party Controls — For conversion to third party control of the VFD, perform the following procedure: 1. Remove the factory-installed jumper between X1-10 and X1-13 (control of VFD start/stop). 2. Remove the factory-installed jumper between X1-10 and X1-16 and replace with a normally closed safety contact for control of VFD start enable. 3. Install speed signal wires to AI-1 and AGND. This input is set at the factory for a 4 to 20 mA signal. If a 0 to 10 vdc signal is required, change DIP switch J1 (located above the VFD control terminal strip) to OFF (right position to left position) and change parameter 1301 to 0% from 20%. VFD Diagnostics — The drive detects error situations and reports them using: • the green and red LEDs on the body of the drive (located under the keypad) • the status LED on the control panel • the control panel display • the Fault Word and Alarm Word parameter bits (parameters 0305 to 0309) The form of the display depends on the severity of the error. The user can specify the severity for many errors by directing the drive to ignore the error situation, report the situation as an alarm, or report the situation as a fault. FAULTS (RED LED LIT) — The VFD signals that it has detected a severe error, or fault, by: • enabling the red LED on the drive (LED is either steady or flashing) • setting an appropriate bit in a Fault Word parameter (0305 to 0307) • overriding the control panel display with the display of a fault code • stopping the motor (if it was on) • sets an appropriate bit in Fault Word parameter 03050307. The fault code on the control panel display is temporary. Pressing the MENU, ENTER, UP button or DOWN buttons removes the fault message. The message reappears after a few seconds if the control panel is not touched and the fault is still active. ALARMS (GREEN LED FLASHING) — For less severe errors, called alarms, the diagnostic display is advisory. For these situations, the drive is simply reporting that it had detected something unusual. In these situations, the drive: • flashes the green LED on the drive (does not apply to alarms that arise from control panel operation errors) • sets an appropriate bit in an Alarm Word parameter (0308 or 0309) • overrides the control panel display with the display of an alarm code and/or name Alarm messages disappear from the control panel display after a few seconds. The message returns periodically as long as the alarm condition exists. CORRECTING FAULTS — The recommended corrective action for faults is shown in the Fault Codes Table C. The VFD can also be reset to remove the fault. If an external source for a start command is selected and is active, the VFD may start immediately after fault reset. 164 APPENDIX D — VFD INFORMATION (cont) Table C — Fault Codes FAULT CODE 1 FAULT NAME IN PANEL OVERCURRENT 2 DC OVERVOLT 3 DEV OVERTEMP 4 5 6 SHORT CIRC OVERLOAD DC UNDERVOLT 7 AI1 LOSS 8 AI2 LOSS 9 MOT OVERTEMP 10 PANEL LOSS 11 ID RUN FAIL 12 MOTOR STALL 13 14 15 RESERVED EXT FAULT 1 EXT FAULT 2 16 EARTH FAULT 17 UNDERLOAD 18 19 20 21 22 23 THERM FAIL OPEX LINK OPEX PWR CURR MEAS SUPPLY PHASE RESERVED 24 OVERSPEED 25 26 27 RESERVED DRIVE ID CONFIG FILE 28 SERIAL 1 ERR 29 30 31 32 33 34 35 101-105 201-206 EFB CON FILE FORCE TRIP EFB 1 EFB 2 EFB 3 MOTOR PHASE OUTP WIRING SYSTEM ERROR SYSTEM ERROR 1000 PAR HZRPM 1001 PAR PFA REFNG 1002 PAR PFA IOCNF 1003 PAR AI SCALE 1004 PAR AO SCALE 1005 PAR PCU 2 1006 PAR EXT RO 1007 PAR FBUS 1008 PAR PFA MODE 1009 PAR PCU 1 1010 OVERRIDE/PFA CONFLICT DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters 2202 ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections. Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply, insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds), or undersized brake chopper (if present). Drive heat sink is overheated. Temperature is at or above 115 C (239 F). Check for fan failure, obstructions in the air flow, dirt or dust coating on the heat sink, excessive ambient temperature, or excessive motor load. Fault current. Check for short-circuit in the motor cable(s) or motor or supply disturbances. Inverter overload condition. The drive output current exceeds the ratings. Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply, blown fuse, or under voltage on main circuit. Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and connection for analog input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI2002 MAXIMUM SPEED 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ 2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: -128/+128 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: -128/+128 Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active. Parameter values are inconsistent. The number of programmed PFA relays does not match with Interlock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT parameters 1401 through 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118 AUTOCHANGE INTERV, and 8120 INTERLOCKS. Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that parameter 1304 AI 2 MIN > 1305 AI 2 MAX. Parameter values are inconsistent. Check that parameter 1504 AO 1 MIN > 1505 AO 1 MAX and that parameter 1510 AO 2 MIN > 1511 AO 2 MAX. Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check the following parameters: 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6 Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746 * 9909 MOTOR NOM POWER (if units are HP, e.g., in US) Parameter values are inconsistent. Check the extension relay module for connection and 1410 through 1412 RELAY OUTPUTS 4 through 6 have non-zero values. Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g., 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL = 0. Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must be = 3 (SCALAR SPEED), when 8123 PFA ENABLE is activated. Parameter values for power control are inconsistent or improper motor nominal frequency or speed. Check for both of the following: 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992 Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA interlocks cannot be observed in the override mode. 165 APPENDIX D — VFD INFORMATION (cont) speed at the time of the fault. To clear the fault history (all of Group 04, Fault History parameters), follow these steps: 1. In the control panel, Parameters mode, select parameter 0401. 2. Press EDIT. 3. Press the UP and DOWN buttons simultaneously. 4. Press SAVE. CORRECTING ALARMS — To correct alarms, first determine if the Alarm requires any corrective action (action is not always required). Use Table D below to find and address the root cause of the problem. To reset a fault indicated by a flashing red LED, turn off the power for 5 minutes. To reset a fault indicated by a red LED (not flashing), press RESET from the control panel or turn off the power for 5 minutes. Depending on the value of parameter 1604 (FAULT RESET SELECT), digital input or serial communication could also be used to reset the drive.When the fault has been corrected, the motor can be started. HISTORY — For reference, the last three fault codes are stored into parameters 0401, 0412, 0413. For the most recent fault (identified by parameter 0401), the drive stores additional data (in parameters 0402 through 0411) to aid in troubleshooting a problem. For example, a parameter 0404 stores the motor Table D — Alarm Codes ALARM CODE ALARM NAME IN PANEL 2001 — Reserved 2002 — Reserved 2003 — Reserved 2004 DIR LOCK 2005 I/O COMM 2006 AI1 LOSS 2007 AI2 LOSS 2008 PANEL LOSS 2009 — 2010 MOT OVERTEMP 2011 UNDERLOAD 2012 MOTOR STALL 2013* AUTORESET 2014* AUTOCHANGE 2015 PFA INTERLOCK 2016 2017* — OFF BUTTON 2018* PID SLEEP 2019 2020 ID RUN OVERRIDE START ENABLE 1 MISSING START ENABLE 2 MISSING EMERGENCY STOP 2021 2022 2023 DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe). Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line. Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001). Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001). Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM). Reserved Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters. Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to 3015. Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near. This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To control automatic reset, use parameter group 31 (AUTOMATIC RESET). This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the Pump Alternation macro. This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when Autochange is used), or a speed regulated motor (when Autochange is not used). Reserved This alarm indicates that the OFF button has been pressed. This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126. The VFD is performing an ID run. Override mode is activated. This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To correct, check the digital input configuration and the communication settings. This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter 1609. To correct, check the digital input configuration and the communication settings. Emergency stop is activated. *This alarm is not indicated by a relay output, even when the relay output is configured to indicate alarm conditions (parameter 1401 RELAY OUTPUT = 5 (ALARM) or 16 (FLT/ALARM). 166 APPENDIX D — VFD INFORMATION (cont) To replace the main fan for frame sizes R5 and R6, perform the following (see Fig. E): 1. Remove power from drive. 2. Remove the screws attaching the fan. 3. Disconnect the fan cable. 4. Install the fan in reverse order. 5. Restore power. INTERNAL ENCLOSURE FAN REPLACEMENT — The VFD IP 54 / UL Type 12 enclosures have an additional internal fan to circulate air inside the enclosure. To replace the internal enclosure fan for frame sizes R1 to R4, perform the following (see Fig. F): 1. Remove power from drive. 2. Remove the front cover. If diagnostics troubleshooting has determined that the drive is defective during the warranty period, contact ABB Automation Inc., at 1-800-435-7365, option 4, option 3. A qualified technician will review the problem with the caller and make a determination regarding how to proceed. This may involve dispatching a designated service station (DSS) representative from an authorized station, dispatching a replacement unit, or advising return for repair. VFD Maintenance — If installed in an appropriate envi- ronment, the VFD requires very little maintenance. Table E lists the routine maintenance intervals recommended by Carrier. Table E — Maintenance Intervals MAINTENANCE INTERVAL Heat Sink Temperature Check and Cleaning Main Cooling Fan Replacement Internal Enclosure Cooling Fan Replacement Capacitor Change (Frame Size R5 and R6) HVAC Control Panel Battery Change Every 6 to 12 months (depending on the dustiness of the environment) Every five years 3 Every three years Every ten years 3 4 Every ten years HEAT SINK — The heat sink fins accumulate dust from the cooling air. Since a dusty sink is less efficient at cooling the drive, overtemperature faults become more likely. In a normal environment check the heat sink annually, in a dusty environment check more often. Check the heat sink as follows (when necessary): 1. Remove power from drive. 2. Remove the cooling fan. 3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a vacuum cleaner at the air outlet to trap the dust. If there a risk of the dust entering adjoining equipment, perform the cleaning in another room. 4. Replace the cooling fan. 5. Restore power. MAIN FAN REPLACEMENT — The main cooling fan of the VFD has a life span of about 60,000 operating hours at maximum rated operating temperature and drive load. The expected life span doubles for each 18 F drop in the fan temperature (fan temperature is a function of ambient temperatures and drive loads). Fan failure can be predicted by the increasing noise from fan bearings and the gradual rise in the heat sink temperature in spite of heat sink cleaning. If the drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are available from Carrier. To replace the main fan for frame sizes R1 through R4, perform the following (see Fig. D): 1. Remove power from drive. 2. Remove drive cover. 3. For frame sizes R1 and R2, press together the retaining clips on the fan cover and lift. For frame sizes R3 and R4, press in on the lever located on the left side of the fan mount, and rotate the fan up and out. 4. Disconnect the fan cable. 5. Install the new fan by reversing Steps 2 to 4. 6. Restore power. 2 Fig. D — Main Fan Replacement (Frame Sizes R1-R4) Bottom View (R5) 3 2 Bottom View (R6) 2 Fig. E — Main Fan Replacement (Frame Sizes R5 and R6) 167 3 APPENDIX D — VFD INFORMATION (cont) 2. Remove the front cover. 3. Lift the fan out and disconnect the cable. 4. Install the fan in reverse order. 5. Restore power. CONTROL PANEL CLEANING — Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the display window. BATTERY REPLACEMENT — A battery is only used in assistant control panels that have the clock function available and enabled. The battery keeps the clock operating in memory during power interruptions. The expected life for the battery is greater than ten years. To remove the battery, use a coin to rotate the battery holder on the back of the control panel. Replace the battery with type CR2032. 3. The housing that holds the fan in place has barbed retaining clips at each corner. Press all four clips toward the center to release the barbs. 4. When the clips/barbs are free, pull the housing up to remove from the drive. 5. Disconnect the fan cable. 6. Install the fan in reverse order, noting the following: the fan airflow is up (refer to arrow on fan); the fan wire harness is toward the front; the notched housing barb is located in the right-rear corner; and the fan cable connects just forward of the fan at the top of the drive. To replace the internal enclosure fan for frame sizes R5 or R6, perform the following: 1. Remove power from drive. A48-7716 Fig. F — Internal Enclosure Fan Replacement 168 APPENDIX E — MODE SELECTION PROCESS Else If: Configured for static pressure control (Configuration→SP→SP.CF = 1,2) and the static pressure sensor (Pressures→AIR.P→SP) fails: The following section is to be used in conjunction with Fig. 4 on page 43. To help determine why the unit controls are in a certain mode, the programming logic is provided below. The software will proceed, step by step, until a mode is reached. If an “If” statement is true, then that mode will be entered. The “Else” statement refers to other possible choices. If the System Mode is OFF: { If the fire shut down input (Inputs→FIRE→FSD) is in “alarm”: HVAC mode: ("Fire Shut Down ") OFF Else HVAC mode: ("Disabled ") OFF } Else If: The rooftop is not in “factory test” and a fire smoke-control mode is “alarming”: { If the pressurization input (Inputs→FIRE→PRES) is in “alarm”: HVAC mode: ("Pressurization ") Else If the evacuation input (Inputs→FIRE→EVAC) is in “alarm”: HVAC mode: ("Evacuation ") Else If the smoke purge input (Inputs→FIRE→PURG) is in “alarm”: HVAC mode: ("Smoke Purge ") } Else If: Someone changed the machine’s control type (Configuration→UNIT→C.TYP) during run time, a 15 second delay is called out: { HVAC mode: ("Disabled ") OFF } Else If: The System Mode is TEST: { HVAC mode: ("Test ") } Else If: The “soft stop” command (Service Test→S.STP) is forced to YES: { HVAC mode: ("SoftStop Request") } Else If: The remote switch config (Configuration→ UNIT→RM.CF)=2; “start/stop”, and the remote input state (Inputs→GEN.I→REMT)=ON: { HVAC mode: ("Rem. Sw. Disable") OFF } Else If: Configured for hydronic heat (Configuration→ HEAT→HT.CF=4) or configured for dehumidification with modulating valve reheat (Configuration→ DEHU→D.SEL=1) and the freeze stat switch trips (Inputs→GEN.I→FRZ.S = ALRM) { HVAC mode: ("Freeze Stat Trip") } { HVAC mode: ("Static Pres.Fail") OFF } Else If: Configured for supply fan status monitoring (Configuration→UNIT→SFS.M = 1,2) and configured to shut the unit down on fan status fail (Configuration→UNIT→SFS.S = YES) { HVAC mode: ("Fan Status Fail ") OFF Else If: Configured for return fan tracking (Configuration→BP→BP.CF = 5) and there is a plenum pressure switch error HVAC mode: ("Plen.Press.Fail ") OFF } Else If: The unit is just waking up from a power reset { HVAC mode: ("Starting Up ") OFF } Else If: A compressor is diagnosed as being “Stuck On” { HVAC mode: ("Comp. Stuck On ") Else The control is free to select the normal heating/ cooling HVAC modes: { — — — — — — 169 HVAC mode: ("Off ") The unit is off and no operating modes are active. HVAC mode: ("Tempering Vent ") The economizer is at minimum vent position but the supply air temperature has dropped below the tempering vent set point. Gas or hydronic heat is used to temper the ventilation air. HVAC mode: ("Tempering LoCool") The economizer is at minimum vent position but the combination of the outside-air temperature and the economizer position has dropped the supply-air temperature below the tempering cool set point. Gas or hydronic heat is used to temper the ventilation air. HVAC mode: ("Tempering HiCool") The economizer is at minimum vent position but the combination of the outside air temperature and the economizer position has dropped the supply air temperature below the tempering cool set point. Gas or hydronic heat is used to temper the ventilation air. HVAC mode: ("Re-Heat ") The unit is operating in dehumidification with a reheat device. HVAC mode: ("Dehumidification") The unit is operating in the Dehumidification mode. APPENDIX E — MODE SELECTION PROCESS (cont) — — — — — HVAC mode: ("Vent ") This is a normal operation mode where no heating or cooling is required and outside air is being delivered to the space to control IAQ levels. HVAC mode: ("Low Cool ") This is a normal cooling mode when a low cooling demand exists. HVAC mode: ("High Cool ") This is a normal cooling mode when a high cooling demand exists. HVAC mode: ("Low Heat ") This is a normal heating mode when a low heating demand exists. HVAC mode: ("High Heat ") This is a normal heating mode when a low heating demand exists. — HVAC mode: ("Unocc. Free Cool") In this mode the unit will operate in cooling but will be using the economizer for free cooling. Entering this mode will depend on the status of the outside air. The unit can be configured for outside air changeover, differential dry bulb changeover, outside air enthalpy changeover, differential enthalpy changeover, or a custom arrangement of enthalpy/dewpoint and dry bulb. See the Economizer section for further details. } NOTE: There is also a transitional mode whereby the machine may be waiting for relay timeguards to expire before shutting the machine completely down: HVAC mode: ("Shutting Down ") 170 INDEX Accessory control components 122 Accessory installation 7 Accessory Navigator™ display 4, 123 Actuators 38 Adjustments 128 Airflow control during Fire/smoke modes 73 Alarm output 39 Alarms and alerts 94 Alert limit configuration 80 Auto view of run status 90 Basic control usage 4-7 Building pressure configuration 70 Building pressure control 69 Carrier Comfort Network® (CCN) 79 CCN tables and display 5, 142-156 CCN/Linkage display table 93, 94 Cleaning 129 ComfortLink™ controls 4 Complete unit stoppage 85 Compressor discharge service valve 131 Compressor removal 132 Compressor replacement 132 Compressor run hours display table 93, 94 Compressor starts display table 93, 94 Compressor suction service valve 131 Configuring building pressure actuators 72 Configuring the humidifier actuator 77 Control circuit, 115 v 132 Control circuit, 24 v 132 Controls 7 Controls operation 5, 40-83 Controls quick start 33-36 Controls set point and configuration log CL-1 to CL-6 Conventions used in this manual 3 Cool mode selection process 47 Cooling 38 Cooling control 45 Cooling mode diagnostic help 50 Crankcase heaters 7 Dehumidification and reheat 77 Demand limit control 39, 52 Dirty filter switch 64 Discrete switch logic configuration 81 Display configuration 82 Economizer 65 Economizer diagnostic help 68 Economizer integration with mechanical cooling 53 Economizer operation 65 Economizer options 34 Economizer run status 92 Economizer/outdoor air damper control 39 Evacuation mode 73 Evaporator fan 7 Exhaust options 34 Factory-installed components 102 Fan status monitoring 64 Fans 38 Filter drier 131 Fire shutdown mode 73 Fire-smoke inputs 73 Forcing inputs and outputs 90 Gas heat (48Z only) 7, 132 Gas system adjustment (48Z only) 131 Generics table 5 Head pressure control 53 Heat mode diagnostic help 56 Heat mode selection process 55 Heating 38 Heating control 54 Hot gas bypass 83 Humidification 76 HVAC modes 41 Hydronic heating control 56 Independent outputs 38 Indoor air quality control 73 Indoor air quality options 34 Internal wiring 7 Liquid line service valve 131 Local display tables 133-141 Lubrication 130 Major system components 102-124 Mode selection process 169, 170 Mode trip helper 92 Modes 40 Moisture/liquid indicator 131 Multi-stage constant volume units with mechanical thermostat 33 Multi-stage constant volume units with space sensor 34 Oil charge 130 Optional airflow station 76 Outdoor air cfm control 68 Pre-occupancy purge 76 Pressurization mode 73 Programming operating schedules 36 Protective devices 131 Refrigerant feed components 130 Refrigeration circuits 130 Relief devices 132 Remote control switch input 83 Remote switch 39 Restart procedure 85 Run status menu 90 Safety considerations 2 Scrolling marquee 4, 120 Sensor trim configuration 81 Service 125-132 Service access 125 Service analysis 85 Service test 36-38 Service test mode logic 38 Set clock on VFD (if installed) 35 Single circuit stoppage 85 Smoke control modes 72 Smoke purge mode 73 Software version numbers display table 93, 94 Space temperature offset 83 Staged gas heating control 57 Start up 7-32 Static pressure control 61 Static pressure reset 63 SUMZ cooling algoritm 50 Supply air reset 39 Supply fan status monitoring logic 64 System modes 41 System Pilot™ 5 Temperature compensated start 78 Temperature compensated start logic 79 Thermistor troubleshooting 85 Thermostat 39 Thermostatic expansion valve (TXV) 130 Third party control 39, 40 Time clock configuration 84, 85 Transducer troubleshooting 86 Troubleshooting 85-102 Two-stage constant volume units with mechanical thermostat 33 Two-stage constant volume units with space sensor 33 Two-stage gas and electric heat control 56 Unit Configuration (unit) submenu 42 Unit preparation 7 Unit setup 7 Unit staging tables 156-159 Unit start-up checklist CL-7 Unoccupied economizer free cooling 68 Variable air volume units using return air sensor or space temperature sensor 33 VFD control 39 VFD information 160-168 171 Copyright 2008 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480039-01 Printed in U.S.A. Form 48/50Z-5T Pg 172 7-08 Replaces: 48/50Z-4T CONTROLS SET POINT AND CONFIGURATION LOG MODEL NUMBER: Software Version SERIAL NUMBER: MBB CESR131292-- DATE: RCB CESR131249-- TECHNICIAN: ECB CESR131249-- NAVI CESR131227-- SCB CESR131226-- CEM CESR131174-- MARQ CESR131171-- ITEM UNIT →C.TYP →CV.FN →RM.CF →CEM →TCS.C →TCS.H →SFS.S →SFS.M →VAV.S →SIZE →50.HZ →MAT.S →MAT.R →MAT.D →ALTI →DLAY →AUX.R →SENS →SENS→SPT.S →SENS→SP.O.S →SENS→SP.O.R →SENS→SRH.S →SENS→RRH.S →SENS→FLT.S COOL →Z.GN →MC.LO →L.L.EN →M.M. →HPSP →A1.EN →A2.EN →B1.EN →B2.EN →CS.A1 →CS.A2 →CS.B1 →CS.B2 →HPS.A →HPS.B →H.SST EDT.R →RS.CF →RTIO →LIMT →RES.S EXPANSION UNIT CONFIGURATION Machine Control Type Fan Mode (0=Auto, 1=Cont) Remote Switch Config CEM Module Installed Temp.Cmp.Strt.Cool Factr Temp.Cmp.Strt.Heat Factr Fan Fail Shuts Down Unit Fan Stat Monitoring Type VAV Unocc.Fan Retry Time Unit Size (30-105) 50 Hertz Unit ? MAT Calc Config Reset MAT Table Entries? MAT Outside Air Default Altitude……..in feet: Startup Delay Time Auxiliary Relay Config INPUT SENSOR CONFIG Space Temp Sensor Space Temp Offset Sensor Space Temp Offset Range Space Air RH Sensor Return Air RH Sensor Filter Stat.Sw.Enabled ? COOLING CONFIGURATION Capacity Threshold Adjst Compressor Lockout Temp Lead/Lag Operation ? Motor Master Control ? Head Pressure Setpoint Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 CSB A1 Feedback Alarm CSB A2 Feedback Alarm CSB B1 Feedback Alarm CSB B2 Feedback Alarm CMPA1 Hi.Pr.Sw. Trip CMPB1 Hi.Pr.Sw. Trip Hi SST Alert Delay Time EVAP.DISCHRGE TEMP RESET EDT Reset Configuration Reset Ratio Reset Limit EDT 4-20 ma Reset Input RANGE 1 - 6 (multi-text strings) 0 - 1 (multi-text strings) 0 - 3 (multi-text strings) Yes/No 0 - 60 min 0 - 60 min Yes/No 0 - 2 (multi-text strings) 0 - 720 min 30 - 105 Yes/No 0 - 2 (multi-text strings) Yes/No 0 - 100‘% 0 - 60000 0 - 900 secs 0 - 3 (multi-text strings) DEFAULT SETTING 4 1 0 No 0 0 No 0 50 30 No 1 No 20 0 0 0 Enable/Disable Enable/Disable 1 - 10 Enable/Disable Enable/Disable Enable/Disable Disable Disable 5 Disable Disable Disable -10 - 10 -25 - 55 dF Yes/No Yes/No 80 - 150 dF Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable Enable/Disable 365 - 415 PSIG 365 - 415 PSIG 5 - 30 min 1 40 No No 113 Enable Enable Enable Enable Enable Enable Enable Enable 415 415 10 0 - 3 (multi-text strings) 0 - 10 0 - 20 ^F Enable/Disable 2 3 10 Disable Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480039-01 Printed in U.S.A. Form 48/50Z-5T CL-1 7-08 Replaces: 48/50Z-4T ITEM HEAT →HT.CF →HT.SP →OC.EN →LAT.M →SG.CF →SG.CF→HT.ST →SG.CF→CAP.M →SG.CF→M.R.DB →SG.CF→S.G.DB →SG.CF→RISE →SG.CF→LAT.L →SG.CF→LIM.M →SG.CF→SW.H.T →SG.CF→SW.L.T →SG.CF→HT.P →SG.CF→HT.D →SG.CF→HT.TM →HH.CF →HH.CF→HW.P →HH.CF→HW.I →HH.CF→HW.D →HH.CF→HW.TM →HH.CF→ACT.C →HH.CF→ACTC→SN.1 →HH.CF→ACTC→SN.2 →HH.CF→ACTC→SN.3 →HH.CF→ACTC→SN.4 →HH.CF→ACTC→SN.5 →HH.CF→ACTC→C.A.LM SP →SP.CF →SP.S →SP.LO →SP.HI →SP.SP →SP.MN →SP.MX →SP.FS →SP.RS →SP.RT →SP.LM →SP.EC →S.PID →S.PID→SP.TM →S.PID→SP.P →S.PID→SP.I →S.PID→SP.D →ACT.C →ACTC→SN.1 →ACTC→SN.2 →ACTC→SN.3 →ACTC→SN.4 →ACTC→SN.5 →ACTC→C.A.LM EXPANSION HEATING CONFIGURATION Heating Control Type Heating Supply Air Setpt Occupied Heating Enabled MBB Sensor Heat Relocate STAGED GAS CONFIGS Staged Gas Heat Type Max Cap Change per Cycle S.Gas DB min.dF/PID Rate St.Gas Temp. Dead Band Heat Rise dF/sec Clamp LAT Limit Config Limit Switch Monitoring? Limit Switch High Temp Limit Switch Low Temp Heat Control Prop. Gain Heat Control Derv. Gain Heat PID Rate Config HYDRONIC HEAT CONFIGS Hydronic Ctl.Prop. Gain Hydronic Ctl.Integ. Gain Hydronic Ctl.Derv. Gain Hydronic PID Rate Config HYDR.HEAT ACTUATOR CFGS. Hydronic Ht.Serial Num.1 Hydronic Ht.Serial Num.2 Hydronic Ht.Serial Num.3 Hydronic Ht.Serial Num.4 Hydronic Ht.Serial Num.5 Hydr.Ht.Ctl.Ang.Lo Limit SUPPLY STATIC PRESS.CFG. Static Pressure Config Static Pressure Sensor Static Press. Low Range Static Press. High Range Static Pressure Setpoint VFD-IGV Minimum Speed VFD-IGV Maximum Speed VFD-IGV Fire Speed Over. Stat. Pres. Reset Config SP Reset Ratio SP Reset Limit SP Reset Econo Position STAT.PRESS.PID CONFIGS Stat.Pres.PID Run Rate Static Press. Prop. Gain Static Pressure Intg. Gain Static Pressure Derv. Gain IGV ACTUATOR CONFIGS IGV Serial Number 1 IGV Serial Number 2 IGV Serial Number 3 IGV Serial Number 4 IGV Serial Number 5 IGV Cntrl Angle Lo Limit CL-2 RANGE 0-4 80 - 120 dF Yes/No Yes/No DEFAULT 0 85 No No 0-4 5 - 45 0-5 0 - 5 ^F 0.05 - 0.2 0 - 20 ^F Yes/No 110 - 180 dF 100 - 170 dF 0 - 1.5 0 - 1.5 60 - 300 sec 0 45 0.5 2 0.06 10 Yes 170 160 1 1 90 0 - 1.5 0 - 1.5 0 - 1.5 15 - 300 sec 1 1 1 90 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 0 0 0 0 85 0-2 (multi-text strings) Enable/Disable -10 - 0 0 - 10 0-5 0 - 100 0 - 100 0 - 100 0 - 4 (multi-text strings) 0.00 - 2.00 0.00 - 2.00 0 - 100% 0 Disable 0 5 1.5 20 100 100 0 0.20 0.75 5 5 - 120 0-5 0-2 0-5 15 0.5 0.5 0.3 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 0 0 0 0 25 SETTING - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE CONTROLS SET POINT AND CONFIGURATION LOG (cont) CONTROLS SET POINT AND CONFIGURATION LOG (cont) ITEM ECON →EC.EN →EC2.E →EC.MN →EC.MX →E.TRM →E.SEL →OA.E.C →OA.EN →OAT.L →O.DEW →ORH.S →CFM.C →CFM.C→OCF.S →CFM.C→O.C.MX →CFM.C→O.C.MN →CFM.C→O.C.DB →E.CFG →E.CFG→E.P.GN →E.CFG→E.RNG →E.CFG→E.SPD →E.CFG→E.DBD →UEFC →UEFC→FC.CF →UEFC→FC.TM →UEFC→FC.L.O →ACT.C →ACTC→SN.1.1 →ACTC→SN.1.2 →ACTC→SN.1.3 →ACTC→SN.1.4 →ACTC→SN.1.5 →ACTC→C.A.L1 →ACTC→SN.2.1 →ACTC→SN.2.2 →ACTC→SN.2.3 →ACTC→SN.2.4 →ACTC→SN.2.5 →ACTC→C.A.L2 BP →BP.CF →BP.S →BP.R →BP.SP →BP.SO →BP.P1 →BP.P2 →B.V.A →B.V.A→BP.FS →B.V.A→BP.MN →B.V.A→BP.MX →B.V.A→BP.1M →B.V.A→BP.2M →B.V.A→BP.CL EXPANSION ECONOMIZER CONFIGURATION Economizer Installed? Econ.Act.2 Installed? Economizer Min.Position Economizer Max.Position Economzr Trim For SumZ ? Econ ChangeOver Select OA Enthalpy ChgOvr Selct Outdr.Enth Compare Value High OAT Lockout Temp OA Dewpoint Temp Limit Outside Air RH Sensor OUTDOOR AIR CFM CONTROL Outdoor Air CFM Sensor Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband ECON.OPERATION CONFIGS Economizer Prop.Gain Economizer Range Adjust Economizer Speed Adjust Economizer Deadband UNOCC.ECON.FREE COOLING Unoc Econ Free Cool Cfg Unoc Econ Free Cool Time Un.Ec.Free Cool OAT Lock ECON.ACTUATOR CONFIGS Econ Serial Number 1 Econ Serial Number 2 Econ Serial Number 3 Econ Serial Number 4 Econ Serial Number 5 Econ Ctrl Angle Lo Limit Econ 2 Serial Number 1 Econ 2 Serial Number 2 Econ 2 Serial Number 3 Econ 2 Serial Number 4 Econ 2 Serial Number 5 Econ 2 Ctrl Angle Lo Limit BUILDING PRESS. CONFIGS Building Press. Config Building Pressure Sensor Bldg. Press. (+/-) Range Building Pressure Setp. BP Setpoint Offset Power Exhaust On Setp.1 Power Exhaust On Setp.2 VFD/ACTUATOR CONFIG VFD/Act. Fire Speed/Pos. VFD/Act. Min.Speed/Pos. VFD Maximum Speed BP 1 Actuator Max Pos. BP 2 Actuator Max Pos. BP Hi Cap VFD Clamp Val. RANGE Yes/No Yes/No 0 - 100% 0 - 100% Yes/No 0 - 3 (multi-text strings) 1 - 5 (multi-text strings) 18 - 28 -40 - 120 dF 50 - 62 dF Enable/Disable Yes No 5 98 Yes 0 4 24 60 55 Disable Enable/Disable 0 - 20000 CFM 0 - 20000 CFM 200 - 1000 CFM Disable 2000 0 400 0.7 - 3.0 0.5 - 5 ^F 0.1 - 10 0.1 - 2 ^F 1 2.5 0.75 0.5 0-2 (multi-text strings) 0 - 720 min 40 - 70 dF 0 120 50 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0 - 90 0 - 5 (multi-text strings) Enable/Disable 0.10 - 0.25 "H2O -0.25 - 0.25 "H2O 0 - 0.5 "H2O 0 - 100% 0 - 100% 0 - 100% 0 - 50% 50 - 100% 85 - 100% 85 - 100% 5 - 25% CL-3 DEFAULT 0 0 0 0 0 85 0 0 0 0 0 85 0 Disable 0.25 0.05 0.05 25 75 100 0 100 100 100 10 SETTING ITEM BP (cont) →FAN.T →FAN.T→FT.CF →FAN.T→FT.TM →FAN.T→FT.ST →FAN.T→FT.MX →FAN.T→FT.AD →FAN.T→FT.OF →FAN.T→FT.RM →FAN.T→FT.RS →FAN.T→SCF.C →B.PID →B.PID→BP.TM →B.PID→BP.P →B.PID→BP.I →B.PID→BP.D →ACT.C →ACT.C→BP.1 →ACT.C→BP.1→SN.1 →ACT.C→BP.1→SN.2 →ACT.C→BP.1→SN.3 →ACT.C→BP.1→SN.4 →ACT.C→BP.1→SN.5 →ACT.C→BP.1→C.A.LM →ACT.C→BP.2 →ACT.C→BP.2→SN.1 →ACT.C→BP.2→SN.2 →ACT.C→BP.2→SN.3 →ACT.C→BP.2→SN.4 →ACT.C→BP.2→SN.5 →ACT.C→BP.2→C.A.LM D.LV.T →L.H.ON →H.H.ON →L.H.OF →L.C.ON →H.C.ON →L.C.OF →C.T.LV →H.T.LV →C.T.TM →H.T.TM DMD.L →DM.L.S →D.L.20 →SH.NM →SH.DL →SH.TM →D.L.S1 →D.L.S2 IAQ →DCV.C →DCV.C→EC.MN →DCV.C→IAQ.M →DCV.C→O.C.MX →DCV.C→O.C.MN →DCV.C→O.C.DB →AQ.CF →AQ.CF→IQ.A.C →AQ.CF→IQ.A.F →AQ.CF→IQ.I.C →AQ.CF→IQ.I.F →AQ.CF→OQ.A.C EXPANSION RANGE FAN TRACKING CONFIG Fan Track Learn Enable Fan Track Learn Rate Fan Track Initial DCFM Fan Track Max Clamp Fan Track Max Correction Fan Track Internl EEPROM Fan Track Internal RAM Fan Track Reset Internal Supply Air CFM Config BLDG.PRESS.PID CONFIGS Bldg.Pres.PID Run Rate Bldg.Press. Prop. Gain Bldg.Press. Integ. Gain Bldg.Press. Deriv. Gain BLDG.PRES. ACTUATOR CFGS BLDG.PRES. ACT.1 CONFIGS BP 1 Serial Number 1 BP 1 Serial Number 2 BP 1 Serial Number 3 BP 1 Serial Number 4 BP 1 Serial Number 5 BP1 Cntrl Angle Lo Limit BLDG.PRES. ACT.2 CONFIGS BP 2 Serial Number 1 BP 2 Serial Number 2 BP 2 Serial Number 3 BP 2 Serial Number 4 BP 2 Serial Number 5 BP2 Cntrl Angle Lo Limit COOL/HEAT SETPT. OFFSETS Dmd Level Lo Heat On Dmd Level(+) Hi Heat On Dmd Level(-) Lo Heat Off Dmd Level Lo Cool On Dmd Level(+) Hi Cool On Dmd Level(-) Lo Cool Off Cool Trend Demand Level Heat Trend Demand Level Cool Trend Time Heat Trend Time DEMAND LIMIT CONFIG. Demand Limit Select Demand Limit at 20 ma Loadshed Group Number Loadshed Demand Delta Maximum Loadshed Time Demand Limit Sw.1 Setpt. Demand Limit Sw.2 Setpt. INDOOR AIR QUALITY CFG. DCV ECONOMIZER SETPOINTS Economizer Min.Position IAQ Demand Vent Min.Pos. Economizer Min.Flow IAQ Demand Vent Min.Flow Econ.Min.Flow Deadband AIR QUALITY CONFIGS IAQ Analog Sensor Config IAQ 4-20 ma Fan Config IAQ Discrete Input Config IAQ Disc.In. Fan Config OAQ 4-20ma Sensor Config CL-4 Yes/No 5-60 min -20000 - 20000 CFM 0 - 20000 CFM 0 -20000 CFM -20000 - 20000 CFM -20000 - 20000 CFM Yes/No 1 - 2 (multi-text strings) DEFAULT SETTING No 15 2000 4000 1000 0 0 No 1 5 - 120 sec 0-5 0-2 0-5 10 0.5 0.5 0.3 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 0 0 0 0 35 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 0 0 0 0 35 -1 - 2 ^F 0.5 - 20.0 ^F 0.5 - 2.0 ^F -1 - 2 ^F 0.5 - 20.0 ^F 0.5 - 2.0 ^F 0.1 - 5.0 ^F 0.1 - 5.0 ^F 30 - 600 sec 30 - 600 sec 1.5 0.5 1.0 1.5 0.5 1.0 0.1 0.1 120 120 0 - 3 (multi-text strings) 0 - 100% 0 - 99 0 - 60% 0 - 120 min 0 - 100% 0 - 100% 0 100 0 0 60 80 50 0 - 100% 0 - 100% 0 - 20000 CFM 0 - 20000 CFM 200 - 1000 CFM 0 - 4 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 0 - 2 (multi-text strings) 5 0 2000 0 400 0 0 0 0 0 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE CONTROLS SET POINT AND CONFIGURATION LOG (cont) CONTROLS SET POINT AND CONFIGURATION LOG (cont) ITEM IAQ (cont) →AQ.SP →AQ.SP→IQ.O.P →AQ.SP→IQ.O.C →AQ.SP→DAQ.L →AQ.SP→DAQ.H →AQ.SP→D.F.OF →AQ.SP→D.F.ON →AQ.SP→IAQ.R →AQ.SP→OAQ.L →AQ.SP→OAQ.U →AQ.S.R →AQ.S.R→IQ.R.L →AQ.S.R→IQ.R.H →AQ.S.R→OQ.R.L →AQ.S.R→OQ.R.H →IAQ.P →IAQ.P→IQ.PG →IAQ.P→IQ.P.T →IAQ.P→IQ.P.L →IAQ.P→IQ.P.H →IAQ.P→IQ.L.O HUMD →HM.CF →HM.SP →H.PID →H.PID→HM.TM →H.PID→HM.P →H.PID→HM.I →H.PID→HM.D →ACT.C →ACTC→SN.1 →ACTC→SN.2 →ACTC→SN.3 →ACTC→SN.4 →ACTC→SN.5 →ACTC→C.A.LM DEHU →D.SEL →D.SEN →D.EC.D →D.V.CF →D.V.RA →D.V.HT →D.C.SP →D.RH.S CCN →CCNA →CCNB →BAUD →BROD →BROD→TM.DT →BROD→OAT.B →BROD→ORH.B →BROD→OAQ.B →BROD→G.S.B →BROD→B.ACK →SC.OV →SC.OV→SCH.N →SC.OV→HOL.T →SC.OV→O.T.L. →SC.OV→OV.EX EXPANSION RANGE AIR QUALITY SETPOINTS IAQ Econo Override Pos. IAQ Override Flow Diff.Air Quality LoLimit Diff. Air Quality HiLimit DAQ PPM Fan Off Setpoint DAQ PPM Fan On Setpoint Diff. AQ Responsiveness OAQ Lockout Value User Determined OAQ AIR QUALITY SENSOR RANGE IAQ Low Reference IAQ High Reference OAQ Low Reference OAQ High Reference IAQ PRE-OCCUPIED PURGE IAQ Purge IAQ Purge Duration IAQ Purge LoTemp Min Pos IAQ Purge HiTemp Min Pos IAQ Purge OAT Lockout HUMIDITY CONFIGURATION Humidifier Control Cfg. Humidifier Setpoint HUMIDIFIER PID CONFIGS Humidifier PID Run Rate Humidifier Prop. Gain Humidifier Integral Gain Humidifier Deriv. Gain HUMIDIFIER ACTUATOR CFGS Humd Serial Number 1 Humd Serial Number 2 Humd Serial Number 3 Humd Serial Number 4 Humd Serial Number 5 Humd Ctrl Angle Lo Limit DEHUMIDIFICATION CONFIG. Dehumidification Config Dehumidification Sensor Econ disable in DH mode? Vent Reheat Setpt Select Vent Reheat RAT offset Vent Reheat Setpoint Dehumidify Cool Setpoint Dehumidify RH Setpoint CCN CONFIGURATION CCN Address CCN Bus Number CCN Baud Rate CCN BROADCST DEFINITIONS CCN Time/Date Broadcast CCN OAT Broadcast CCN OARH Broadcast CCN OAQ Broadcast Global Schedule Broadcst CCN Broadcast Ack'er CCN SCHEDULES-OVERRIDES Schedule Number Accept Global Holidays? Override Time Limit Timed Override Hours 0 - 100% 0 - 31000 CFM 0 - 1000 100 - 2000 0 - 2000 0 - 2000 -5 - 5 0 - 2000 0 - 5000 0 - 5000 0 - 5000 0 - 5000 0 - 5000 SETTING 100 10000 100 700 200 400 0 0 400 0 2000 0 2000 Yes/No 5 - 60 min 0 - 100% 0 - 100% 35 - 70 dF No 15 10 35 50 0-4 0 - 100% 0 40 10 - 120 sec 0-5 0-5 0-5 30 1 0.3 0.3 0 - 255 0 - 255 0 - 255 0 - 255 0 - 255 0-90 0 0 0 0 0 85 0-3(multi-text strings) 1-3(multi-text strings) Yes/No 0-1(multi-text strings) 0-8 delta F 55-95 dF 40-55 dF 10-90% 1 - 239 0 - 239 1 - 5 (multi-text strings) CL-5 DEFAULT 0 1 Yes 0 0 70 45 55 1 0 3 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF On Off Off Off Off Off 0 - 99 YES/NO 0 - 4 HRS 0 - 4 HRS 1 No 1 0 ITEM CCN (cont) →SC.OV→SPT.O →SC.OV→T58.O →SC.OV→GL.OV ALLM →SP.L.O →SP.H.O →SP.L.U →SP.H.U →SA.L.O →SA.H.O →SA.L.U →SA.H.U →RA.L.O →RA.H.O →RA.L.U →RA.H.U →OAT.L →OAT.H →R.RH.L →R.RH.H →O.RH.L →O.RH.H →SP.L →SP.H →BP.L →BP.H →IAQ.H TRIM →SAT.T →RAT.T →OAT.T →SPT.T →L.SW.T →CCT.T →SP.A.T →SP.B.T →DP.A.T →DP.B.T SW.LG →FTS.L →IGC.L →RMI.L →ENT.L →SFS.L →DL1.L →DL2.L →IAQ.L →FSD.L →PRS.L →EVC.L →PRG.L →DH.LG DISP →TEST →METR →LANG →PAS.E →PASS EXPANSION SPT Override Enabled ? T58 Override Enabled ? Global Sched. Override ? ALERT LIMIT CONFIG. SPT lo alert limit/occ SPT hi alert limit/occ SPT lo alert limit/unocc SPT hi alert limit/unocc EDT lo alert limit/occ EDT hi alert limit/occ EDT lo alert limit/unocc EDT hi alert limit/unocc RAT lo alert limit/occ RAT hi alert limit/occ RAT lo alert limit/unocc RAT hi alert limit/unocc OAT lo alert limit OAT hi alert limit RARH low alert limit RARH high alert limit OARH low alert limit OARH high alert limit SP low alert limit SP high alert limit BP lo alert limit BP high alert limit IAQ high alert limit SENSOR TRIM CONFIG. Air Temp Lvg SF Trim RAT Trim OAT Trim SPT Trim Limit Switch Trim Air Temp Lvg Evap Trim Suct.Press.Circ.A Trim Suct.Press.Circ.B Trim Dis.Press.Circ.A Trim Dis.Press.Circ.B Trim SWITCH LOGIC: NO / NC Filter Status Inpt-Clean IGC Feedback - Off RemSw Off-Unoc-Strt-NoOv Enthalpy Input - Low Fan Status Sw. - Off Dmd.Lmt.Sw.1 - Off Dmd.Lmt.Sw.2 - Off IAQ Disc.Input - Low Fire Shutdown - Off Pressurization Sw. - Off Evacuation Sw. - Off Smoke Purge Sw. - Off Dehumidify Sw. - Off DISPLAY CONFIGURATION Test Display LEDs Metric Display Language Selection Password Enable Service Password RANGE YES/NO YES/NO YES/NO -10-245 dF -10-245 dF -10-245 dF -10-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF -40-245 dF 0-100% 0-100% 0-100% 0-100% 0-5 "H2O 0-5 "H2O -0.25-0.25 "H2O -0.25-0.25 "H2O 0-5000 -10 - 10 ^F -10 - 10 ^F -10 - 10 ^F -10 - 10 ^F -10 - 10 ^F -10 - 10 ^F -50 - 50 PSIG -50 - 50 PSIG -50 - 50 PSIG -50 - 50 PSIG Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close Open/Close ON/OFF ON/OFF 0 - 1 (multi-text strings) ENABLE/DISABLE 0000 - 9999 CL-6 DEFAULT SETTING Yes Yes No 60 85 45 100 40 100 40 100 60 90 40 100 -40 150 0 100 0 100 0 2 -0.25 0.25 1200 0 0 0 0 0 0 0 0 0 0 Open Open Open Close Open Open Open Open Open Open Open Open Open Off Off 0 Enable 1111 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE CONTROLS SET POINT AND CONFIGURATION LOG (cont) UNIT START-UP CHECKLIST MODEL NO.: _________________________________ SERIAL NO.: ______________________________________ SOFTWARE VERSION _________________________ TECHNICIAN: ____________________________________ DATE: _______________________________________ PRE-START-UP: VERIFY THAT DIP SWITCH SETTINGS ARE CORRECT VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT REMOVE ALL COMPRESSOR SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS VERIFY INSTALLATION OF ECONOMIZER HOOD VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT CHECK GAS PIPING FOR LEAKS (48Z ONLY) CHECK THAT RETURN-AIR FILTER AND OUTDOOR-AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT IS LEVEL WITHIN TOLERANCES FOR PROPER CONDENSATE DRAINAGE CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE, AND SETSCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SUCTION, DISCHARGE, AND LIQUID SERVICE VALVES ON EACH CIRCUIT ARE OPEN VERIFY THAT CRANKCASE HEATERS HAVE BEEN ON 24 HOURS BEFORE START-UP. START-UP: ELECTRICAL SUPPLY VOLTAGE L1-L2 __________ __________ L3-L1 __________ COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 __________ L2 __________ L2 _________ COMPRESSOR AMPS — COMPRESSOR NO. 2 L1 __________ L2 __________ L2 _________ SUPPLY FANS AMPS EXHAUST FAN AMPS __________ (CV) ________ (VAV) ________ * L2-L3 *VAV fan supply amps reading must be taken with a true RMS meter for accurate readings. TEMPERATURES OUTDOOR-AIR TEMPERATURE __________ F DB (Dry Bulb) RETURN-AIR TEMPERATURE __________ F DB__________ F WB (Wet Bulb) COOLING SUPPLY AIR __________ F GAS HEAT SUPPLY AIR __________ F (48Z ONLY) ELECTRIC HEAT SUPPLY AIR __________ F (50Z ONLY, IF EQUIPPED) PRESSURES GAS INLET PRESSURE __________ GAS MANIFOLD PRESSURE STAGE NO. 1 __________ IN. WG STAGE NO. 2 __________IN. WG (48Z ONLY) REFRIGERANT SUCTION CIRCUIT NO. 1 __________ PSIG CIRCUIT NO. 2__________ PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 2 __________ PSIG CIRCUIT NO. 2__________ PSIG IN. WG (48Z ONLY) ______________________ VERIFY REFRIGERANT CHARGE. CL-7 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53480039-01 Printed in U.S.A. Form 48/50Z-5T CL-8 7-08 Replaces: 48/50Z-4T - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE Copyright 2008 Carrier Corporation
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0 (Windows) Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:08:21 15:43:16-04:00 Create Date : 2008:08:21 15:43:16-04:00 Format : application/pdf Title : 48_50z-5t.fm Creator : MSDT05K Document ID : uuid:2c6cd420-f86e-4177-a8c7-1f701e10e51a Instance ID : uuid:bfc40301-56a8-46c1-8479-7121fb586ad0 Page Count : 180 Author : MSDT05KEXIF Metadata provided by EXIF.tools