Crouzet Hsv User Manual

Hsv HSV HSV datasheet library assets cdn.crouzet-control.com

2017-07-05

User Manual: Crouzet Hsv HSV en datasheet library assets

Open the PDF directly: View PDF PDF.
Page Count: 5

DownloadCrouzet Hsv User Manual
Open PDF In BrowserView PDF
››HSV
››Monitoring Relays
››Speed Monitoring Relays
››DIN Rail Mount 35 mm
››Control of overspeed, underspeed, operating
rate, stopping
››Measurement via discrete sensors - 3-wire PNP
or NPN, Namur, voltage 0-30V or volt-free contact
type
››Works with either NO or NC sensors
››Time between pulses adjustable from 0.05 s to
10 min.
››Power-on inhibit time, adjustable from 0.6 to 60 s
››Inhibit time can be managed via an external
contact
Specifications
Nominal voltage (V)

Code

24 →240 V AC/DC

84874320

Power supply
Supply voltage Un

24 V →240 V AC/DC

Voltage supply tolerance

-15 % / +10 %

Operating range

20,4 V →264 V AC/DC

Polarity with DC voltage

No

AC supply voltage frequency

50 / 60 Hz ±10 %

Galvanic isolation of power supply/measurement

No

Power consumption at Un

5 VA in AC/3 W in DC

Immunity from micro power cuts

50 ms

Inputs and measuring circuit
Input circuit 3-wire sensors

PNP or NPN, 12V, 50 mA max.

Input circuit NAMUR sensor

12 V / 1.5 KOhm(s) *

Input circuit Contact

12 V / 9.5 KOhm(s)
0 V min. /30 V max. /9.5 KOhm(s)

Input circuit Voltage input

High state 4.5 V min.
Low state 1 V max.

Minimum pulse time

5 ms in high and low state

Frequency of measured signal

1.5 m Hz minimum, 22 Hz maximum

Measurement ranges

0,5 s - 1 s - 5 s - 10 s - 1 mn - 5 mn - 10 mn

Threshold adjustment

10 →100 % of the range

Fixed hysteresis

5 % of displayed threshold

Display precision

±10 % of full scale

Repetition accuracy with constant parameters

± 0,5 %

Measuring error with voltage drift

< 1 % across the whole range

Measuring error with temperature drift

± 0,1 % / °C max.

I Monitoring Relays

I 02

I www.crouzet-control.com

Time delays
Maximum threshold crossing response time

15 ms

Reset time S2

50 ms minimum (in memory mode)

Reset time

In memory mode (power break) : 1500 ms minimum

Inhibit time delay

On energisation : 0,6 →60 s (0, +10 % of full scale)

Repetition accuracy with constant parameters

± 0,5 %

Delay on pick-up

50 ms

Display precision

±10 % of full scale

Outputs
Type of output

1 single pole changeover relay

Type of contacts

No cadmium

Maximum breaking voltage

250 V AC/ DC

Max. breaking current

5A AC/DC

Min. breaking current

10 mA / 5 V DC

Electrical life (number of operations)

1 x 10⁵

Breaking capacity (resistive)

1250 VA AC

Maximum rate

360 operations/hour at full load

Operating categories acc. to IEC/EN 60947-5-1

AC 12, AC 13, AC 14, AC 15, DC 12, DC 13, DC 14

Mechanical life (operations)

30 x 10⁶

Insulation
Nominal insulation voltage IEC/EN 60664-1

250 V

Insulation coordination (IEC/EN 60664-1)

Overvoltage category III : degree of pollution 3

Rated impulse withstand voltage (IEC/EN 60664-1)

4 KV (1,2 / 50 μs)

Dielectric strength (IEC/EN 60664-1)

2 kV AC 50 Hz 1 min

Insulation resistance (IEC/EN 60664-1)

> 500 MOhm(s) / 500 V DC

General characteristics
Display power supply

Green LED

Display relay

Yellow LED

Inhibit display

Yellow LED

Casing

35 mm

Mounting

On 35 mm symmetrical DIN rail, IEC/EN 60715

Mounting position

All positions

Material : enclosure plastic type VO to UL94 standard

Incandescent wire test according to IEC 60695-2-11 &
NF EN 60695-2-11

Protection (IEC/EN 60529)

Terminal block : IP20

Weight

120 g

Connecting capacity IEC/EN 60947-1

Rigid : 1 x 4² - 2 x 2.5² mm²

Casing : IP30

1 x 11 AWG - 2 x 14 AWG
Flexible with ferrules : 1 x 2.5² - 2 x 1.5² mm²
1 x 14 AWG - 2 x 16 AWG
Max. tightening torques IEC/EN 60947-1

0,6 →1 Nm / 5,3 →8,8 Lbf.In

Operating temperature IEC/EN 60068-2

-20 →+50 °C

Storage temperature IEC/EN 60068-2

-40 →+70 °C

Humidity IEC/EN 60068-2-30

2 x 24 hr cycle 95 % RH max. without condensation 55 °C

Vibrations according to IEC/EN60068-2-6

10 →150 Hz, A = 0.035 mm

Shocks IEC/EN 60068-2-6

5g

Standards
Marking

CE (DBT) 2006/95/EC - EMC 2004/108/EC

Product standard

NF EN 60255-6 / IECI 60255-6 / UL 508 / CSA C22.2 N°14

I Monitoring Relays

I 03

I www.crouzet-control.com

Standards
Electromagnetic compatibility (EMC)

Immunity EN 61000-6-2/IEC 61000-6-2
Emission EN 61000-6-4/EN 61000-6-3
IEC 61000-6-4/IEC 61000-6-3
Emission EN 55022 class B

Certifications

UL, CSA

Conformity with environmental directives

RoHS

Comments
The IEC 60947-5-6/1999-12 NAMUR standard does not impose the
operating voltage (open circuit voltage) or the load resistance (source
resistance of the control amplifier), but it defines the test conditions for
which, using the sensor voltage/current characteristics with high and
low impedance, the normal operating zones are specified. The great
majority of NAMUR sensors use a 12 V supply voltage. Matching the
load resistance to the operating voltage allows the nominal switching
distance to be maintained.
Dimensions
HSV
60
44
23,2

35

90
2,6

45

67,5

3,5

5,5

Curves

Connections
HSV - Input circuits

2
1

E2

0V

11

Y1 12 V 12 V E1

+/–

24…240 V
50/60 Hz

–/+

A2

14

A1

S1

12

R

12

11

14

I Monitoring Relays

I 04

I www.crouzet-control.com

Connections
2

+

–

1
Y1 12 V 12 V E1

0V

11

E2

A2

14

A1

12

R

12

11

14

S1

+/–
24…240 V
50/60 Hz

–/+
2
B

BU

BK

1

E2

0V

11

Y1 12 V 12 V E1

+/–

A2

14

A1

12

R

12

11

14

S1

24…240 V
50/60 Hz

–/+
2

+

℮

–

E2

0V

1

11

Y1 12 V 12 V E1

+/–
24…240 V
50/60 Hz

–/+

A2

14

A1

S1

12

R

12

11

14

I Monitoring Relays

Connections

I 05

I www.crouzet-control.com



Navigation menu