Datamatic D4000 Water Meter Interface Unit User Manual FIREFLY Water User guide D4000

Datamatic, Ltd Water Meter Interface Unit FIREFLY Water User guide D4000

user manual

Download: Datamatic D4000 Water Meter Interface Unit User Manual FIREFLY Water User guide D4000
Mirror Download [FCC.gov]Datamatic D4000 Water Meter Interface Unit User Manual FIREFLY Water User guide D4000
Document ID962243
Application IDuUTRDVjvUOiBu2QbgSqXuA==
Document Descriptionuser manual
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize31.02kB (387720 bits)
Date Submitted2008-06-28 00:00:00
Date Available2008-06-29 00:00:00
Creation Date2008-05-08 13:13:31
Producing SoftwareGPL Ghostscript 8.54
Document Lastmod2008-05-08 13:13:31
Document TitleFIREFLY_Water_User_guide_D4000
Document CreatorPDFCreator Version 0.9.3
Document Author: andrewp

System Guide
D4000 MOSAIC – Water
Datamatic, Ltd. © 2008
©Datamatic, Ltd. 2008
-1-
Table Of Contents
Table Of Contents ..............................................................................................2
Regulatory Information .......................................................................................3
Introduction.........................................................................................................4
Equipment ..........................................................................................................5
D4000 MOSAIC Meter Interface Unit (MIU) ...................................................5
D4000 MOSAIC - Optic Sensor-end ..............................................................5
Lid Lock.........................................................................................................6
Installation Supplies............................................................................................7
Optic Sensor-end D4000 MOSAIC Installation Supplies ................................7
Installation Considerations..................................................................................8
Installation Procedures .......................................................................................9
Installation Overview for Water D4000 MOSAICs..........................................9
Final Optic Sensor-end D4000 MOSAIC Installation Steps..........................11
Contacting Datamatic .......................................................................................12
System Support during Business Hours ......................................................12
System Support after Business Hours .........................................................12
Paging a Support Representative after Business Hours ..............................12
-2-
©Datamatic, Ltd. 2007
Regulatory Information
United States of America, FCC:
Note: This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
--Reorient or relocate the receiving antenna.
--Increase the separation between the equipment and receiver.
--Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
--Consult the dealer or an experienced radio/TV technician for help.
FCC ID: ODYD4000
Caution: Changes or modifications not expressly approved by the manufacturer could void
the user’s authority to operate the equipment.
To comply with FCC RF exposure requirements, the device and the antenna for this device
must be installed to ensure a minimum separation distance of 20 cm or more from a person's
body. Other operating configurations should be avoided.
Canada, Industry Canada (IC)
The wireless radio of this device complies with RSS 210 Industry Canada. This Class B digital device
complies with Canadian ICES-003.
The installer of this radio equipment must ensure that the antenna is located or pointed such that
it does not emit RF field in excess of Health Canada limits for the general population; consult
Safety Code 6, obtainable from Health Canada’s website www.hc-sc.gc.ca/rpb
©Datamatic, Ltd. 2008
-3-
Introduction
The D4000 MOSAIC System is an automatic meter reading system designed for reading meter data
remotely and wirelessly. This is accomplished using the Datamatic D4000 MOSAIC Meter Interface
Unit (MIU) that forms a mesh network with neighboring D4000 MOSAIC MIUs, and reports data to the
Home Office (HO) through strategically placed gateway devices.
The main benefits of using a D4000 MOSAIC System are:
•
•
•
•
•
•
•
•
Real-time access to meter readings
Built-in logging of 72+ days of consumption data
Complete remote control of MIUs through MOSAIC Software Interface
Meter lids do not have to be removed for reads
Meter pits do not have to be dug out or pumped out for reads
Increased accuracy of meter readings
Safer meter reading procedure
Visiting the site is not necessary for data collection
Please consult the MOSAIC Software Interface Guide for user instructions regarding data access,
configuring, or upgrading the D4000 MOSAIC. After reviewing this guide you should be able to
successfully deploy the D4000 MOSAIC for your application.
-4-
©Datamatic, Ltd. 2007
Equipment
D4000 MOSAIC Meter Interface Unit (MIU)
The D4000 MOSAIC Meter Interface Unit (MIU) tracks and transmits meter reading data. Each D4000
MOSAIC can be configured to record 72+ days of hourly consumption readings, thereby enabling the
resolution of billing disputes. The D4000 MOSAIC signal includes the meter number, meter reading,
battery voltage, tamper flag, and a leak indicator.
Battery: 3.6-volt lithium chloride D-cell
Material: Polycarbonate
Construction: Ultrasonic welding
Operating Temperature Range: -40°F to 185°F
Radio Communication Frequency: 902 - 928 MHz
D4000 MOSAIC – Optic Sensor-end
This D4000 MOSAIC uses an optical sensor unit to track meter activity. The infrared sensor is oriented
so that the register needle approaches the sensor from the cable side and perpendicular to the cable. The
indicators on the top side of the sensor need to be aligned with the passing sweep hand. As the needle
sweeps past the sensor, it changes the light reflected back from the meter face, and an incremental count
is registered. The optical sensor is affixed to the meter face using a high-bond adhesive tape.
Unique Features:
•
•
•
•
•
•
Use existing meters.
The D4000 MOSAIC Optic Sensor Model is the only available technology for automating
meters without electronic registers
Ultrasonically-welded, seamless construction designed to withstand constant submersion
Leak Detection
Tamper Detection
Battery Status Indicator
Optical Sensor Tape Specification
Manufacturer: 3M
Part Number: 4951VHB
Minimum Application Temp: 33°° Fahrenheit
Curing Time: 24 hours
©Datamatic, Ltd. 2008
-5-
Lid Lock
If the lid has a hole for the unit, use the cap and wing nut assembly
(“lid lock” pictured at right). Ensure that enough space exists
between the box lid and the ground for the unit to sit. If not,
remove some of the dirt from the bottom of the box.
Do not over tighten lid locks.
D4000 MOSAIC Lid lock
-6-
©Datamatic, Ltd. 2007
Installation Supplies
Optic Sensor-end D4000 MOSAIC Installation Supplies
Basic Supplies:
•
•
Razor blade tool or chisel
Non Pumice Fast Orange
7.5 Fl. Oz Part No. 23108
15 Fl Oz. Part No 23116
• Cloth Rags
• 99% Isopropyl Rubbing Alcohol
• Lint Free Cotton Squares
• Plumber’s Goop Adhesive #15112 (Purple Tube)
• Zip Ties—14”
• ¾” PVC pipe; sch. 40
• Sensor flaps
• Wire Cutter (for cutting zip ties)
• 9 Volt Battery
• 3M Adhesive Replacements
Below is an illustration of materials used with Sensor-end installations:
©Datamatic, Ltd. 2008
-7-
Installation Considerations
1. Signal distance varies depending on the location of the D4000 MOSAIC. Those installed above
ground generally transmit the greatest distance.
2. The material of a pit or vault lid affects the transmission range. For example, a transmitter has a
greater range sending from a pit with a plastic lid than a cast iron lid.
3. Lids with holes of a diameter of roughly 1 3/4 inches make it possible to mount the D4000
MOSAIC through the lid. This can increase transmission range significantly.
4. Complete field installation of a D4000 MOSAIC takes 5-10 minutes, depending on the meter
location and mounting application.
5. If the lid has a hole for the unit, use the cap
and wing nut assembly (“lid lock” pictured
at right). Ensure that enough space exists
between the box lid and the ground for the
unit to sit. If not, remove some of the dirt
from the bottom of the box. Do not overtighten lid locks.
-8-
©Datamatic, Ltd. 2007
Installation Procedures
Installation Overview for Water D4000 MOSAICs
1. Perform a site survey to determine where best to install the Gateway devices and where to
designate MIU mesh network areas.
2. Configure MIUs before on site installation with the unique mesh word to form a group of
selected MIUs into a mesh network.
3. Prepare the meter.
4. Attach the D4000 MOSAIC.
5. Using a mobile gateway, take a reading to verify neighbor MIUs on the mesh.
6. Once the entire route is installed, verify connectivity from the installed gateway to the Home
Office.
#1 Preparation Of the Meter
1. Remove meter box lid.
2. Survey the meter, checking lid, hole depth, and overall cleanliness.
3. Check for meter disqualification.
4. Place sensor flap onto D4000 MOSAIC cable.
5. Flip lid back and pre-clean meter face/lens using Fast Orange non-pumice cleaner and a cloth or
cotton swab to remove residue.
6. Clean meter face/lens with 99% isopropyl alcohol and a NEW lint-free cotton swab.
7. Re-wipe the surface of the meter lens with a clean, new cotton swab each time until the swab
comes up clean, and the clean lens squeaks when wiped.
8. After cleaning, ensure that the lens is completely dry; allow time for the alcohol to evaporate.
NOTE: Only use isopropyl rubbing alcohol marked “99% by volume”. Lower concentrations, such as
the commonly available 91%, do not clean or evaporate well and adversely affect sensor-to-meter bond.
#2 Placement of the Sensor
1. Insert sensor cable through sensor flap.
2. Remove the adhesive backing from the high-bond tape on the optic sensor face.
3. Orient the sensor so the water meter needle approaches the sensor from the cable side and
perpendicular to the cable. There are indents on each side of the sensor base that are to be in line with
the needle when it passes. Do not place the sensor over any moving part or the sweep hand of the
register. Normally, place sensor along outer edge of register.
NOTE: Do not place the sensor over any moving part or the sweep hand of the register. Normally, place
sensor along outer edge of register.
Here is an example of correct Sensor Placement:
©Datamatic, Ltd. 2008
-9-
#3 Pressure – To the Sensor on the Meter
NOTE: Since the 3M tape provides a pressure sensitive seal, the installer must apply 15 lbs. of
pressure to the D4000 MOSAIC optical sensor immediately after attaching to the lens surface for a
minimum of 60 seconds.
1. Very Important: Press the adhesive down for 60+ seconds using 15 lbs of pressure. Allow 24-96
hours to cure.
2. Fasten the cable to the register with a zip tie.
3. Place Goop-Plumber’s Adhesive #15112 (purple tube) around the metal edge sensor and under the
tail of the sensor. Do not squirt the adhesive UNDER the 3M seal. The goal is to provide a
temporary water barrier between the meter face and the metal edge of the sensor, so that the 3M
adhesive can cure properly.
4. Position the flap at the base of the sensor so that it folds over and “hangs” above the register to try to
keep most of the stray light out while it processes through AutoCAL. The flap will be “pulled” over
the sensor snuggly lying flatter on the meter during the Read and Verify procedure that will be
discussed later.
- 10 -
©Datamatic, Ltd. 2007
Final Optic Sensor-end D4000 MOSAIC Installation Steps
1. A full cure on the seal is achieved in 24-96 hours. Do not touch, pull, move, or handle the sensor in
any way during this period.
2. Mount the D4000 MOSAIC box with the threaded neck pointing up.
3. Mounting can be accomplished by attaching to a wall, stake, or through a hole in the meter box or
vault.
4. Typical meter pits will use an 18” long ¾” PVC stake. Push the stake into the ground approx. 6”
deep, adjacent to the meter register.
5. Attach the D4000 MOSAIC to the stake with the zip ties (6” or 14”).
6. If utilizing a lid lock, make certain not to over-tighten the D4000 MOSAIC within the lock.
7. Check for lid clearance; be sure to never rest the weight of the meter lid on the D4000 MOSAIC.
D4000 MOSAIC Installation pictures:
Example of a GOOD Sensor-end Installation.
Example of a BAD Sensor-end Installation.
What is wrong here? ____________________
Example of a BAD Sensor-end Installation.
What is wrong here? ____________________
Example of a BAD Sensor-end Installation.
What is wrong here? _____________________
©Datamatic, Ltd. 2008
- 11 -
Contacting Datamatic
Datamatic, Ltd. offers the following benefits to customers under the RouteSTAR MVP Meter Reading
System maintenance agreement.
24-hour telephone support for MOSAIC Interface Software.
Two-hour response time on telephone calls.
Preventative maintenance on system hardware.
Best effort turn-around time for repairs.
Software updates.
System Support during Business Hours
Support is available to customers of Datamatic, Ltd. from 8:00 AM to 5:00 PM CST. The toll-free
customer support number is (888) 326-5032.
System Support after Business Hours
Customers requiring assistance after Datamatic business hours can leave a message for the
appropriate group. Emergency assistance is available 24 hours a day.
If this is an emergency, press 2 at the greeting to page a Customer Support Representative.
If this is not an emergency and can wait until the next business day, listen for the options to leave a
message.
Leave your name, number, and message at the prompt.
A customer support representative should return your call the next business day.
Paging a Support Representative after Business Hours
Call the Customer Support number above.
Press 2 to leave an emergency message.
Leave your name, number, and message at the prompt.
A support representative will be paged and return your call within two hours.
For the most timely response, call the Toll Free number (888) 326-5032 from 7:30am to 5:30pm CST or
submit an email. If you call after that time you can leave a message, and someone will call you back
within two hours.
There is also the Support Request Form, which you can fill out and submit. You will receive a response
back from support regarding the information you have entered on this page.
- 12 -
©Datamatic, Ltd. 2007

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Page Count                      : 12
Producer                        : GPL Ghostscript 8.54
Create Date                     : 2008:05:08 13:13:31-05:00
Modify Date                     : 2008:05:08 13:13:31
Title                           : FIREFLY_Water_User_guide_D4000
Creator                         : PDFCreator Version 0.9.3
Author                          : andrewp
Subject                         : 
EXIF Metadata provided by EXIF.tools
FCC ID Filing: ODYD4000

Navigation menu