Cabling the Dell™
PowerEdge™ R710
 

A Dell Technical White Paper 

By Chris M. Kitten and Jose L. Flores
Dell │ Datacenter Infrastructure Engineering
March 2009
 
 

 

Cabling the Dell™ PowerEdge™ R710 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND 
TECHNICAL INACCURACIES. THE CONTENT IS PROVIDED AS IS, WITHOUT EXPRESS OR IMPLIED WARRANTIES OF 
ANY KIND. 
© 2009 Dell Inc. All rights reserved. Reproduction of this material in any manner whatsoever without the express 
written permission of Dell Inc. is strictly forbidden. For more information, contact Dell. 
Dell, the DELL logo, and the DELL badge, PowerEdge, is a trademark of Dell Inc. 
 

 
 

Page ii 

Cabling the Dell™ PowerEdge™ R710 
 

Table of Contents 
Introduction ............................................................................................................................................................... 2 
Cabling a PowerEdge R710 with CMA ....................................................................................................................... 2 
2.1  Installing the Cables to the System ................................................................................................................. 2 
Figure 1: System with Cables Installed .......................................................................................................... 2 
2.2  Route the Power Cables Through the Strain Reliefs ....................................................................................... 3 
Figure 2:  Routing Power Cables Through the Strain Reliefs ......................................................................... 3 
2.3  Routing the Cables Through the CMA ............................................................................................................. 3 
Figure 3:  Routing the Cables Through the CMA ........................................................................................... 4 
Figure 4: Completed Left Side Mounted CMA Installation ............................................................................ 5 
Figure 5: Completed Right Side Mounted CMA Installation .......................................................................... 5 
Cabling a PowerEdge R710 Without a CMA .............................................................................................................. 5 
3.1  Routing the Cables .......................................................................................................................................... 5 
Figure 6: Cable Routing Without a CMA ........................................................................................................ 6 
Replacing a Power Supply on a PowerEdge R710 with CMA ..................................................................................... 6 
Figure 7: Replacing Outer Power Supply ....................................................................................................... 7 
Cabling a PowerEdge R710 Installed in Static Rails ................................................................................................... 7 
Figure 8: Cabling a System Installed in Static Rails ........................................................................................ 7 
 
 

 
 

 

Page 1 

Cabling the Dell™ PowerEdge™ R710 
 

Introduction 
This white paper describes recommended cable routing procedures, both with and without the optional Cable 
Management Arm (CMA) for the Dell™ PowerEdge™ R710 in the following racks: 
•
•
•
•

PowerEdge 4210 
PowerEdge 2410 
PowerEdge 4220 
PowerEdge 2420 

If using the optional CMA, following these procedures will allow you to extend the system from the rack for service 
without powering down or disconnecting the cables. If not using the CMA, following these procedures will ensure 
secure attachment and strain relief of the cables behind the system. For guidelines on how to route cables within 
the rack, refer to the Dell White Paper “Best Practices Guide for Rack Enclosures.” 

Cabling a PowerEdge R710 with CMA 
This section details how to cable a PowerEdge R710 using a CMA. If you are cabling the system without the 
optional CMA, please refer to “Cabling a PowerEdge R710 Without a CMA” later in this white paper. 
Follow the instructions contained in the Rack Installation Guide found in the rail kit to install the server into the 
rack and to install the cables. All illustrations in the following sections were created using a PowerEdge R710. 
NOTE:  The PowerEdge R710 is not compatible with previous‐generation rails and CMAs. 

2.1  Installing the Cables to the System 
Attach the CMA tray to the back of the rails as described in the CMA Installation Instructions provided in the CMA 
kit. Plug in all applicable cables to the rear of the system. Verify that all connections are secure. See Figure 1. 
Figure 1: System with Cables Installed 
 
 
 
 
 
 
 

 

 
 

 

Page 2 

Cabling the Dell™ PowerEdge™ R710 
 

2.2  Route the Power Cables Through the Strain Reliefs 
After the tray and cables are installed, route the power cables through the strain reliefs located on the power 
supply handles as shown in Figure 2. 
Figure 2:  Routing Power Cables Through the Strain Reliefs 

 
 
 
 
 
 

 
2.3  Routing the Cables Through the CMA 
NOTE:  The CMA can be installed on either the right or left rear side of the rails.  Mounting the CMA on the side 
opposite the power supplies (left side mount) is recommended; otherwise, the CMA must be disconnected in order 
to remove the outer power supply. Refer to “Replacing a Power Supply on a PowerEdge R710 with CMA” later in 
this white paper for details on power supply replacement. 
NOTE:  For guidelines on how to route cables within the rack, refer to the Dell White Paper “Best Practices Guide 
for Rack Enclosure”. 
Left Side Mounting Instructions 
1. Install the CMA on the left rear side of the rails by attaching both CMA housings to the attachment brackets on 
the rails. See Figure 3. 
2. Route the cables through the CMA while keeping any twisting of the cables to a minimum. If the cable bundle 
includes a KVM dongle, place the dongle inside the CMA basket. Use the hook and loop straps on the CMA to 
secure the cables.  
 

 
 

 

Page 3 

Cabling the Dell™ PowerEdge™ R710 
 
Figure 3:  Routing the Cables Through the CMA 

 
 
 
 
 
 

Cables entering CMA should
have a small amount of slack
to avoid cable strain when
CMA is extended.

 
 
 
 
 

NOTE: Do not store excess
cable slack inside the CMA.
The cable may protrude
through the CMA causing
binding and potentially
damaging the cable.

 
3.

4.
5.
6.
7.

 
 

Once all the cables are routed through the CMA, dress the cables between the back of the system and the 
entrance of the CMA with the tie wraps provided in the CMA kit. The tie wraps are shown in yellow in all 
illustrations. 
Clip off the excess length of material from the tie wraps and make sure that the tie wraps are positioned to 
avoid interference with adjacent systems.  
Return the CMA to the closed (retracted) position. 
Extend the system from the rack to verify there is sufficient slack in the cables at both the entrance and exit of 
the CMA. 
See Figure 4 for an example of a completed left side mounted CMA installation. 

Page 4 

Cabling the Dell™ PowerEdge™ R710 
 
Figure 4: Completed Left Side Mounted CMA Installation 
 
 
 
 
 
 
 
 
 

 
Right Side Mounting Instructions 
Install the CMA on the right rear side of the rails by attaching both CMA housings to the attachment brackets on 
the rails. Follow steps 2‐6 from the left side mounting instructions in the previous section.  See Figure 5 for an 
example of a completed right side mounted CMA installation. 
Figure 5: Completed Right Side Mounted CMA Installation 

 
 
 
 
 
 
 
 
 

Cabling a PowerEdge R710 without a CMA 
NOTE:  The CMA on the Dell PowerEdge R710 is optional. Without the CMA installed, the system must be powered 
down and all cables disconnected before it can be removed from the rack. 

3.1  Routing the Cables 
1.

 
 

Plug in all applicable cables to the rear of the system, verifying that all connections are secure. 

Page 5 

Cabling the Dell™ PowerEdge™ R710 
 
2.

3.

Using the hook and loop straps supplied with the rail kit, bundle the cables and secure them to either the left 
rail or right rail CMA attachment brackets as described in the Rack Installation Guide. See Figure 6 for an 
example of power cables secured to the right CMA bracket and data cables secured to the left CMA bracket.
It is recommended that the cables be secured to the outer brackets, but cables may be secured to the inner 
brackets if desired. 

Figure 6: Cable Routing Without a CMA 

 
 
 
 
 
 
 

Replacing a Power Supply on a PowerEdge R710 with CMA 
1.
2.
3.
4.

5.
6.
7.
8.
 

 
 

Remove the tray from under the CMA as described in the CMA Installation Instructions provided with the CMA 
kit. 
Swing the CMA into the service position.
Disconnect the power cord from the power supply and disengage the strain relief. 
Remove and replace the power supply 
a. If the CMA is attached to the right side and the outer power supply needs to be replaced, the inner 
CMA attachment housing will need to be disconnected. While supporting the CMA with one hand, 
remove and replace the power supply with the other hand as shown in Figure 7.   
b. If the  CMA is attached to the right side and the inner power supply needs to be replaced, the CMA 
does not need to be disconnected. 
c. If the CMA is attached to the left side, both power supplies can be removed without disconnecting 
the CMA. 
Plug  in the power cord. 
Re‐engage the strain relief.  
Replace the CMA support tray.  
Return the CMA to the closed (retracted) position. 
 

Page 6 

Cabling the Dell™ PowerEdge™ R710 
 
Figure 7: Replacing Outer Power Supply 

 
 
 

Inner CMA attachment
  housing has been
disconnected
 
 
 
 
 
 
 
 

Cabling a PowerEdge R710 Installed in Static Rails 
NOTE:  The CMA is only compatible with sliding rails, and not with static rails. 
1.
2.
3.
4.

Follow the instructions in the Rack Installation Guide included in the static rail kit to install the server into a 2‐
post or 4‐post rack.  
Verify that the hook and loops straps provided with the static rail kit are installed to the rear of the rails.  
Plug in all applicable cables to the rear of the system and verify that all connections are secure. 
Using the hook and loop straps supplied with the rail kit, bundle the cables and secure them to either the left 
rail or right rail as described in the Rack Installation Guide. See Figure 8.

Figure 8: Cabling a System Installed in Static Rails 

 
 
 
 
 
 
 

 
 
 

Page 7 



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Format                          : application/pdf
Creator                         : Dell Inc.
Title                           : Cabling PowerEdge R710
Subject                         : White Papers12
Description                     : White Papers12
Producer                        : Acrobat Distiller 7.0.5 (Windows); modified using iTextSharp 5.1.3 (c) 1T3XT BVBA
Keywords                        : esuprt_ser_stor_net#esuprt_poweredge#PowerEdge Rack Enclosure 4220#poweredge-4220#PowerEdge Rack Enclosure 4820#poweredge-4820#PowerEdge Rack Enclosure 4020S#poweredge-4020s#PowerEdge Rack Enclosure 2420#poweredge-2420#White Papers12
Create Date                     : 2009:03:18 13:28:54-05:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2012:09:14 12:02:40-05:00
Page Count                      : 9
Author                          : Dell Inc.
Productcode                     : poweredge-4220#poweredge-4820#poweredge-4020s#poweredge-2420
Typecode                        : wp12
Typedescription                 : White Papers12
Languagecodes                   : en-us
Sectioncode                     : wp
Sectiondescription              : White Papers
Publishdate                     : 2012-05-23 00:00:00
Expirydate                      : 9999-09-09 00:00:00
Manualurl                       : http://ftp.dell.com/manuals/commonfolder/poweredge-4220_White Papers12_en-us.pdf
Readytocopy                     : false
Futureproductindication         : No
Categorypathforfutureprodcuts   : 
Businesskeywords                : 
Filesize                        : 1065
Creationdate                    : D:20090318132854-05'00'
Moddate                         : D:20120914104452-05'00'
EXIF Metadata provided by EXIF.tools

Navigation menu