P66 Series Electronic Fan Speed Controls Product Bulletin Johnson Inc. Air Conditioner F) 125465

User Manual: Johnson Controls Inc. Air Conditioner F)

Open the PDF directly: View PDF PDF.
Page Count: 7

DownloadP66 Series Electronic Fan Speed Controls Product Bulletin Johnson Inc. Air Conditioner F) 125465
Open PDF In BrowserView PDF
P66 Series Electronic Fan Speed Controls
Product Bulletin
Code No. LIT-125465
Issued September 30, 2009
Supersedes March 23, 2006

The P66 Series Electronic Fan Speed Controls are
refrigerant pressure actuated, electronic motor-speed
controllers. The P66 controls are designed for use with
single-phase permanent split-capacitor motors that are
approved by the motor manufacturer for speed control
applications.
The P66 controls provide condenser pressure control
by directly sensing condenser refrigerant pressure and
automatically adjusting the condenser fan motor speed
according to the sensed pressure.
The P66 provides an alternative to fan cycling control
in many small and medium size refrigeration and
Heating, Ventilating, and Air Conditioning (HVAC)
applications.

Figure 1: P66 Dual Sensor Fan Speed Control

Table 1: Features and Benefits
Features

Benefits

Exclusive Johnson Controls/PENN®
Pressure Transducer

Responds quickly to condenser pressure changes and condenser air delivery
requirements

Soft Start Capability

Provides a smooth fan startup, which reduces motor-starting noise and abrupt
changes in motor speed

208-240/277/480 VAC, 60 Hz Motor
Control

Suitable for a wide range of condenser fan motor applications

One or Two Pressure Transducers

Applicable to single- and multi-circuit condensers. The dual-sensor P66 control
models select the higher pressure input to control the fan speeds.

Two Effective Throttling Ranges
(ETRs)

Provide either a 30 or 60 psi (207 or 414 kPa) ETR

NEMA 1 or NEMA 3R (Rainproof)
Enclosure

Allows indoor and panel mounting or outdoor mounting applications

Built-in Voltage Surge Protection,
Radio Frequency Interference (RFI)
Suppression, and Ground Terminal
Screw

Achieves trouble-free operation

P66 Series Electronic Fan Speed Controls Product Bulletin

1

Application
IMPORTANT: Use this P66 Series Electronic Fan
Speed Control only as an operating control. Where
failure or malfunction of the P66 control could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the P66 control.
The P66 Series Electronic Fan Speed Controls are
pressure-actuated electronic motor-speed controllers
designed primarily to control condenser fan motors on
Heating, Ventilating, Air Conditioning, and Refrigeration
(HVAC/R) applications (Figure 2). These controls
regulate the supply voltage to the fan motor in
response to the sensed refrigerant pressure, providing
direct response to changes in condenser pressure,
regardless of the variations in air delivery curves.
P66 controls are available with one or two pressure
sensor inputs. In dual sensor models, the control
selects the input with the greatest demand.
P66 control models are also available with NEMA 3R
(Rainproof) enclosures for outdoor applications
(Figure 1). These models come with a plastic
enclosure, appropriate gaskets, and low voltage wire
leads for 24 VAC power. In addition, the critical high
voltage components are encapsulated in a potting
compound.
Note: NEMA 1 models cannot be retrofitted in the
field to obtain the NEMA 3R (Rainproof) rating.
A P66 and speed control motor can replace On/Off fan
cycling controls, multiple speed motors, condenser
flood-back systems, temperature fan-speed controls,
and modulating louver systems.

Typical applications include:
•

computer room air conditioning

•

commercial air conditioning

•

commercial refrigeration

!

CAUTION: Risk of Property Damage
Use only single-phase Permanent
Split-Capacitor (PSC) motors approved
by the manufacturer for speed control
applications with the P66 control. Failure
to use a single-phase PSC motor may
damage the motor and other property.

The P66 Series controls must be applied only to
single-phase motors intended for use with a solid-state
motor speed control. An applicable motor must be a
single-phase, permanent split-capacitor motor and
must be:
•

ball-bearing construction only (Sleeve-bearing
motors are not acceptable for use with P66
controls.)

•

designed to handle non-sinusoidal waveforms
generated by solid-state motor speed controls

•

designed to dissipate the motor heat generated at
reduced speed operation

Operation
Condensing unit installation, operation, and
maintenance determine the overall capability to
maintain a satisfactory pressure by means of fan speed
control. Within the operating range, the P66 control
provides air delivery in direct proportion to heat
rejection requirements. This allows the refrigeration
system to perform efficiently, even in very low ambient
temperatures.
The P66 pressure transducer provides direct response
to changes in condenser pressure, regardless of the
variations in fan delivery curves. The dual input models
select the pressure input from the transducer sensing
the highest pressure.
See Figure 2 for a typical operational sequence for a
P66 control.

Repair and Replacement
Do not make field repairs. For a replacement control,
contact the Original Equipment Manufacturer or your
local Johnson Controls/PENN distributor.

2

P66 Series Electronic Fan Speed Controls Product Bulletin

97%

Motor Voltage

90%

10% to 40%
of Line
(Model Specific)

No fan operation
in this
pressure range.

0
psig

Operating Range
(190/250 psig)

Operating Range
Plus 20 or 30 psi*

Pressure Input
350 psig

*20 psi for 30 psi Effective Throttling Range (ETR)
30 psi for 60 psi Effective Throttling Range (ETR)

Figure 2: Operation Chart for the P66 Fan Speed Control
Table 2: P66 Control Operation
Pressure Input

Motor Voltage

Pressure is between 0 psig and the low end of the
operating range.

0 to 5 volts

Pressure is at the low end of the operating range.

Start voltage: 10% to 40% of line - Model Specific (See
Table 3.)

Pressure is in the operating range.

Motor voltage varies directly with system pressure from start
voltage to 90% of line voltage.

Pressure is above the operating range.

A further pressure increase of 20 to 30 psi increases motor
voltage to 97% of the applied voltage.

P66 Series Electronic Fan Speed Controls Product Bulletin

3

0.218 Diameter Mounting Holes
5.54 for No. 10 Screw

Two 0.250 Spade Terminals
for 24 VAC Power Supply
Inside Plug (NEMA 1 Enclosure)

6.75
172
5.33
135

6.00
152
5.26
134

Valve
Depressor

7/16 in.
20 UNF-2B

3.38
86

4.56
116

4.20
107

0.27
7

4.72
120

1/4 in. Flare

1.28
33

Two 22 AWG Wire
Leads for 24 VAC
Power Supply
(NEMA 3R
Enclosure)

0.875
Diameter
22.23
Conduit Hole
(2 places)

NEMA 3R Enclosure

3.34
85
4.12
105

Figure 3: P66 Control and NEMA 3R Enclosure Dimensions, in./mm

4

P66 Series Electronic Fan Speed Controls Product Bulletin

FIG:P66_DMS_ENCLOSURE

0.093
2.36
Diameter
Capillary

Ordering Information
Table 3: P66 Series Control Model Information1
Product Code Number

Operating Pressure Range
(psig)

Start Voltage
(% of Supply Voltage)

Capillary Length (in.)

P66AAB-1C

190-250

10

60

P66AAB-4C

135-165

10

60

P66AAB-6C

170-230

16

60

P66AAB-9C

170-230

40

60

P66AAB-10C

190-250

16

120

P66AAB-11C

140-200

16

60

P66AAB-13C

60-90

16

60

P66AAB-14C

220-280

40

120

P66AAB-15C

190-250

40

60

P66AAB-19C

115-145

40

60

P66AAB-25C

180-240

10

120

P66AAB-26C

220-280

40

60

P66AAB-34C

320-410

40

60

P66AAD-1C*

160-220

25

60

P66BAB-1C

190-250

10

60

P66BAB-3C

170-230

16

60

P66BAB-4C

190-250

16

120

P66BAB-5C

190-250

40

60

P66BAB-9C

320-410

40

60

P66BAD-1C*

160-220

25

60

P66ABB-21C

220-280

16

120

P66ABB-24C

190-250

16

60

P66ABB-27C

170-230

40

60

Single Input Sensor Models

Dual Input Sensor Models

NEMA 3R Models

1.

All models are rated for 208-240/277/480 volt; 60 Hz except those with Product Code Numbers followed by an asterisk,
indicating 50 Hz Models.

Table 4: Fan Speed Control Replacement Guide (Part 1 of 2)1
Original Control Model Number

Replacement P66 Product Code Number

P15AJ-39

P66AAB-4C

P15AK-11

P66AAB-6C

P15AK-12

P66ABB-21C

P15AK-13

P66AAB-6C

P15AK-14

P66AAB-1C

P15DJ-5

P66AAB-6C

P15JJ-2 (Liebert® models)

P66AAB-1C

P15JJ-2 (Non Liebert models)

P66AAB-9C

P66 Series Electronic Fan Speed Controls Product Bulletin

5

Table 4: Fan Speed Control Replacement Guide (Part 2 of 2)1
Original Control Model Number

Replacement P66 Product Code Number

P15JJ-7

P66ABB-21C

P15JJ-8

P66AAB-1C

P65AAB-1

P66AAB-1C

P65AAB-2

P66AAB-1C

P65AAB-4

P66AAB-4C

P65AAB-6

P66AAB-6C

P65AAB-9

P66AAB-9C

P65AAB-10

P66AAB-10C

P65BAB-1

P66BAB-1C

P65BAB-2

P66BAB-1C

P65BAB-5

P66BAB-5C

P65AAB-2

P66AAB-1C

P66AAB-18

P66AAB-25C

P66AAB-21

P66ABB-21C

P66BAB-2

P66BAB-1C

P66BAB-4

P66BAB-1C

1.

When two P15s are used in parallel with one motor, replace both P15s with one P66BAB. Select the P66BAB with an
operating range similar to that of the P15s being replaced. When replacing a P15 or P65 with a P66, 24 VAC must be
provided. It is recommended that the P66 be used only with low heat rise ball bearing motors that are approved by the motor
manufacturer for fan speed control operation. Start voltage for P15 motors = 40%.

Technical Specifications
P66 Series Electronic Fan Speed Controls (Part 1 of 2)
Pressure Ratings: Low Pressure Models

Control Range: 80 to 200 psig (552 to 1,379 kPa)
Effective Throttling Range: 30 psig (207 kPa)
Maximum Working Pressure: 200 psig (1,379 kPa)
Maximum Overpressure: 250 psig (1,724 kPa)

Pressure Ratings: Medium Pressure Models

Control Range: 140 to 350 psig (965 to 2,413 kPa)
Effective Throttling Range: 60 psig (414 kPa)
Maximum Working Pressure: 350 psig (2,413 kPa)
Maximum Overpressure: 400 psig (2,758 kPa)

Pressure Ratings: High Pressure Models

Control Range: 300 to 500 psig (2,068 to 3,447 kPa)
Effective Throttling Range: 90 psig (621 kPa)
Maximum Working Pressure: 500 psig (3,447 kPa)
Maximum Overpressure: 610 psig (4,206 kPa)

Control Voltage

24 VAC, Class 2, 1 A

Line Voltage Range

208 to 480 VAC

Start Voltage

10% to 40% of line (Original Equipment Manufacturer [OEM] specified model specific)

Electrical Ratings: 208 VAC

Full Load Amperes: 8.0
Locked Rotor Amperes: 16.5
Ambient Temperature Maximum: 130°F/54°C

Electrical Ratings: 240 VAC

Full Load Amperes: 8.0
Locked Rotor Amperes: 16.5
Ambient Temperature Maximum: 130°F/54°C

6

P66 Series Electronic Fan Speed Controls Product Bulletin

P66 Series Electronic Fan Speed Controls (Part 2 of 2)
Electrical Ratings: 277 VAC

Full Load Amperes: 6.9
Locked Rotor Amperes: 14.3
Ambient Temperature Maximum: 130°F/54°C

Electrical Ratings: 480 VAC

Full Load Amperes: 4.0
Locked Rotor Amperes: 10.5
Ambient Temperature Maximum: 150°F/66°C

Ambient Temperature Minimum

-40°F/-40°C (at all voltages)

Ambient Storage Temperature

-40°F/-40°C to 185°F/85°C

Construction

Control Case: Galvanized steel case and cover
Base and Sensors: Galvanized steel
Plastic Enclosure: UV stabilized polycarbonate with closed cell foam
gasket (NEMA 3R models only)

Enclosure

NEMA 1 or NEMA 3R (Rainproof)

Wiring Connections

Low Voltage: 1/4 in. quick connects (NEMA 1); Two 6 in. 22 AWG Wire
Leads (NEMA 3R)
Line Voltage: 10-32 Screw Terminals

Pressure Connections

60 in./1.5 m or 120 in./3.0 m copper capillary with 1/4 in./6 mm flare nut
and Schrader® valve depressor

Mounting

Vertical only; two holes for No. 10 screws at the top and bottom

Compliance

UL Recognized (U.S.): File SA516, Guide SDFY2
UL Recognized (Canada): File SA516, Guide SDFY8

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Johnson Controls Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages
resulting from the misapplication or misuse of its products.

Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2009 Johnson Controls, Inc.

P66 Series Electronic Fan Speed Controls Product Bulletin
Published in U.S.A.

7

www.johnsoncontrols.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Page Mode                       : UseOutlines
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2009:09:30 16:57:28-05:00
Create Date                     : 2003:09:30 16:48:05Z
Metadata Date                   : 2009:09:30 16:57:28-05:00
Copyright                       : Johnson Controls, Inc.
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Format                          : application/pdf
Title                           : P66 Series Electronic Fan Speed Controls Product Bulletin
Creator                         : 
Document ID                     : uuid:8ee3ecdf-91df-4249-a1e2-7229dffb378b
Instance ID                     : uuid:5269a4bd-7903-4076-a085-0d29f4eb7af0
Page Count                      : 7
Page Layout                     : OneColumn
EXIF Metadata provided by EXIF.tools

Navigation menu