AIR COOLED CONDENSING UNIT 38EH 38AH
User Manual: AIR COOLED CONDENSING UNIT 38EH
Open the PDF directly: View PDF
.
Page Count: 108
| Download | |
| Open PDF In Browser | View PDF |
38AH024-134 With 40RM016-034 Commercial Air-Cooled Split Systems 50 Hz Product Data 63 to 390 Nominal kW (18 to 111 Tons) This catalog describes the full range of versatile 38AH condensing units. For 38AH sizes 024-034, this catalog also describes matching Carrier 40RM air handlers, and gives combined ratings for these 38AH/ 40RM systems. All 38AH condensing units can also be matched to Carrier’s 39 Series air handlers. Use Carrier’s exclusive AHU (Air-Handling Unit) selection program to select these matching indoor units. Features/Benefits 38AH CONDENSING UNIT 40RM016-034 Copyright 1998 Carrier Corporation • Up to 4 compressors and 2 independent refrigerant circuits provide design flexibility; size 044-134 condensing units can supply one or 2 air handlers • Efficient 38AH Series units save energy • Variable air volume units operate at as low as 8% of nominal capacity without the use of energy-inefficient hot gas bypass. • Constant volume units operate at as low as 16% of nominal capacity (standard) or 8% of nominal capacity (with accessory unloader) • Weatherized steel cabinet ensures corrosion protection • Protection against high discharge and low suction refrigerant pressure, and low oil pressure ensure compressor reliability • Timed bypass of low pressure switch on start-up of 024-034 size units. • Crankcase heaters prevent oil dilution and ensure compressor lubrication Form 38AH-C4PD The 38AH condensing unit offers the utmost in system configuration and control adaptability. Its premiumquality standard components ensure durable, efficient and reliable operation. Versatility 38AH Series condensing units feature up to 4 compressors and 2 refrigerant circuits, and can be matched with a wide variety of air-handling units. All condensing unit circuits can supply a single air handler; size 044-134 units can supply 2 separate air handlers. Standard units have constant volume control. A variable air volume (VAV) option is available. The VAV units have electric unloaders on the compressors to closely match building loads. The VAV option requires only a simple connection to the Carrier ModuPanel™ discharge air controller, thereby saving installation time and cost. (NOTE: Unit sizes 024-034 require field supplied and installed accumulator.) Durable construction All 38AH units have weatherized cabinets constructed of heavy-duty galvanized steel prepainted with corrosionresistant baked enamel. Inside and outside surfaces are protected to ensure long life and good looks. The durable, galvanized steel, prepainted components exceed the requirements of the 500-hour salt spray test per ASTM B117. The unit’s coils have aluminum fins mechanically bonded to copper tubes for long-term reliability and improved heat transfer. An inert epoxy barrier is available on precoated fins to provide improved durability in mildly corrosive coastal environments. Copper fins on copper tubes are available for harsh industrial or coastal conditions. Reliability The 38AH condensing units feature time-proven, highly reliable 06D and 06E semi-hermetic compressors. Unloading capability is a standard feature on the lead compressor of each circuit. Each compressor has vibration isolators to provide quiet operation and reduced component stress. 2 Because 38AH units have 2 independent circuits, they provide inherent backup capability. Each circuit is also protected by the following safety features: • Time Guardt anti-short-cycling device • low oil pressure safety switch • low refrigerant pressure switch (suction) • high refrigerant pressure switch (discharge) • calibrated circuit breakers for compressors and outdoor fans Easier installation and service 38AH units are equipped with hinged control-box access doors, liquid line shutoff valves, and service valves on the compressors. Larger 38AH124 and 134 size units are shipped as 2 modules for easier handling and rigging. Table of contents Page Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Model Number Nomenclature — 38AH024-034 . . . . . . . . . . . . . . . . . . . 4 Model Number Nomenclature — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ratings Summary — 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 5 Options and Accessories — 38AH024-034/40RM . . . . . . . . . . . . . . . . . 6-8 Physical Data — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10 Physical Data — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11,12 Dimensions — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Dimensions — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15 Selection Procedure — 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . 16,17 Performance Data — 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . 18-31 Typical Piping and Wiring — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . 32,33 Electrical Data — 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36 Controls — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Typical Control Wiring Schematic — 38AH024-034 . . . . . . . . . . . . . . . . 38 Application Data — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39,40 Application Data — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-43 Model Number Nomenclature — 38AH044-134 . . . . . . . . . . . . . . . . . . . 44 Ratings Summary — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Options and Accessories — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 45,46 Physical Data — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-50 Dimensions — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-57 Selection Procedure, 2-Circuit Units — 38AH044-134 . . . . . . . . . . . . . . 58 Selection Procedure, Single-Circuit Units — 38AH044-084 Only . . . . . 58 Performance Data — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-84 Typical Piping and Wiring — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . 85,86 Electrical Data — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87,88 Controls — 38AH044-084 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Controls — 38AH094-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Typical Control Wiring Schematic — 38AH044-134 . . . . . . . . . . . . . . . . 91-93 Application Data — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94-100 Guide Specifications — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . 101-103 Guide Specifications — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104,105 Guide Specifications — 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . 106-108 Feature/Benefits (cont) Innovative Carrier 40RM airhandling units in sizes 016034: ideal matches for 38AH024-034 condensing units The 40RM Series has excellent fan performance, efficient direct-expansion (DX) coils, a unique combination of indoor air quality features, and easy installation. Its versatility and state-ofthe-art features help to ensure that your split system provides economical performance now and in the future. Indoor-air quality (IAQ) features The unique combination of IAQ features in the 40RM Series air handlers helps to make sure that only clean, fresh, conditioned air is delivered to the occupied space. Direct-expansion (DX) cooling coils prevent the build-up of humidity in the room, even during part-load conditions. The 016-034 sizes feature dualcircuit coils. Standard 51-mm (2-in.) disposable filters remove dust and airborne particles from the occupied space. Thermal insulation contains an immobilized anti-microbial agent to inhibit the growth of bacteria and fungi. The anti-microbial agent is registered with the U.S. Environmental Protection Agency (EPA). The pitched PVC drain pan can be adjusted for a right- or left-hand connection to provide positive drainage and to prevent standing condensate. The 40RM accessory economizer can provide ventilation air to improve indoor-air quality. When used with CO2 sensors, the economizer admits fresh outdoor air to replace stale, recirculated indoor air. Includes 24-v controls. Economy The 40RM Series packaged air handlers save money by providing reduced installation expense and energy-efficient performance. Quick installation is ensured by the multiposition design. Units can be installed in either the horizontal or vertical (upflow) configuration without modifications. All units have drainpan connections on both sides, and pans can be pitched for right- or lefthand operation with a simple adjustment. Fan motors and contactors are prewired and thermostatic expansion valves (TXVs) are factoryinstalled on all 40RM models. High efficiency, precision-balanced fans minimize air turbulence, surging, and unbalanced operation, cutting operating expenses. The economizer accessory precisely controls the blend of outdoor air and room air to achieve comfort levels. When the outside air enthalpy is suitable, outside air dampers can fully open to provide ‘‘free’’ cooling. Coil flexibility Model 40RM direct-expansion coils have galvanized steel tube sheets; inlet and outlet connections are on the same end. The coils are designed for use with Refrigerant 22 and have copper tubes mechanically bonded to aluminum sine-wave fins. The coils include matched, factory-installed TXVs with matching distributor nozzles. Accessory hot water and steam coils and electric heaters are also available. Easier installation and service The multiposition design and component layout help you to get the unit installed and running quickly. The DX coils have factory-installed TXVs with matching distributor nozzles. Units can be converted from horizontal to vertical operation by simply repositioning the unit. Drain pan connections are duplicated on both sides of the unit. The filters, motor drive, TXVs, and coil connections are all easily accessed by removing a single side panel. Rugged dependability 40RM units are made to last. The die-formed galvanized steel panels ensure structural integrity under all operating conditions. Galvanized steel fan housings are securely mounted to a die-formed galvanized steel deck. Mechanically bonded coil fins provide improved heat transfer. Rugged pillow-block bearings are securely fastened to the solid steel fan shaft with split collets and clamp locking devices. 3 Model number nomenclature — 38AH024-034 38AH 024 38AH — Commercial Air-Cooled Condensing Unit Nominal Capacity — kW (Tons) 024 — 63 (18) 028 — 73 (21) 034 — 87 (25) —— — 9 1 3 A A Compressors A — Standard Compressors — One Suction Pressure-Actuated Unloader on Lead Compressor C — Variable Air Volume (VAV) Option — Includes 2 Electric Unloaders on Lead Compressor and Control Box Modifications Not Used Condenser Coil Fin Material Aluminum (Standard) C — Copper (Optional) K — Precoated Aluminum (Optional) SO — Post-Coated Aluminum (Contact Factory) SO — Post-Coated Copper (Contact Factory) Voltage Designation 3 — 346-3-50 8 — 230-3-50 9 — 400-3-50 Fan Motors and Labels A — Standard Condenser Fan Motors and Labels B — Class F Fan Motors (Export Only) — Not UL Approved Packaging 1 — Standard Domestic Packaging — Bottom Skid 3 — Export Packaging — Top and Bottom Skid Revision Number 1 — Current Revision SO — Special Order UL — Underwriters’ Laboratories (U.S.A.) 4 Model number nomenclature — 40RM 40RM — 016 —— B 9 0 3 GC 40RM — Commercial Packaged Air Handler Factory-Installed Options GC — Unpainted, Standard Motor, and Standard Drive HC — Unpainted, Standard Motor, and Medium-Static Drive (Not available for sizes 016-028) TC — Unpainted, Alternate Motor, and Medium-Static Drive (sizes 016-028) YC — Unpainted, Alternate Motor, and High-Static Drive* ED — Painted, Standard Motor, and Standard Drive FD — Painted, Standard Motor, and Medium-Static Drive (Not available for sizes 016-028) RD — Painted, Alternate Motor, and Medium-Static Drive (sizes 016-028) WD — Painted, Alternate Motor, and High Static Drive* Cooling Coil — — Direct Expansion Nominal Capacity — kW (Tons) 016 — 52 (15) 024 — 70 (20) 028 — 87 (25) 034 — 105 (30) Not Used Expansion Device B — Thermostatic Expansion Valve Voltage Designation (V-Ph-Hz) 8 — 230-3-50 9 — 400-3-50 Revision Number 0 — Original Model Packaging 3 — Export Packaging *YC and WD option codes for all 034 size units designate standard motor and high-static drive. Ratings summary — 38AH024-034/40RM OUTDOOR UNIT 38AH 024 028 034 INDOOR UNIT 40RM 016 024 028 024 028 034 028 034 AIRFLOW L/s 2,800 3,800 4,700 3,800 4,700 5,650 4,700 5,650 Cfm 6,000 8,000 10,000 8,000 10,000 12,000 10,000 12,000 SYSTEM GROSS CAPACITY kW† Btuh** 57.3 195,000 62.5 214,000 66.3 227,000 68.9 236,000 73.5 251,000 77.6 265,000 82.6 283,000 87.7 300,000 CONDENSING UNIT ONLY GROSS CAPACITY* kW Btuh 63 216,000 73 250,000 87 297,000 *Condensing unit only ratings are at 7.2 C (45 F) saturated suction temperature and 36 C (95 F) entering-air temperature. †Total gross system capacity (kW) is based on 20 C wet bulb and 26.7 C dry bulb air entering indoor unit, and 36 C dry bulb air entering outdoor unit. **Total gross system capacity (Btuh) is based on 67 F wet bulb and 80 F dry bulb air entering indoor unit, and 95 F dry bulb air entering outdoor unit. 5 Options and accessories — 38AH024-034/40RM 38AH024-034 factory-installed options 40RM factory-installed options VAV option provides unit with 2 electric unloaders and control box modifications necessary to connect to a fieldinstalled ModuPanel™ control. Class F fan motors provide additional motor insulation for high ambient temperature environments. Condenser coil options are available to match coil construction to site conditions for the best corrosion durability. Pre-coated coils provide protection in mild coastal environments. All copper coils are best suited for moderate coastal applications, while post-coated coils provide superior protection in severe coastal and industrial applications. Prepainted steel units are available from the factory for applications that require painted units. Units are painted with American Sterling Gray color. (Check availability and lead times.) Alternate fan motors and drives are available to provide the widest possible range of performance. 38AH024-034 field-installed accessories Pressure-operated unloading allows compressors to be unloaded in response to compressor suction pressure. Electric unloader conversion package includes hardware and solenoid valve to convert a pressure-operated unloader to electric unloading. Electric unloading package provides an additional step of electric unloading. −29 C (−20 F) low-ambient temperature kit (Motormastert III) controls outdoor-fan motor operation to maintain the correct head pressure at low outdoor ambient temperatures. Only one low ambient temperature kit is required per unit. Gage panel package provides a suction and a discharge pressure gage for one refrigerant circuit. ModuPanel control box allows 38AH system to operate VAV system. Includes microprocessor satellite sequencer, 4 status lights, 5-hour bypass timer, and locked enclosure. Requires field-installed accumulator. Carrier’s line of thermostats provide both programmable and non-programmable capability with the new Debonair™ line of commercial programmable thermostats, the TEMP System controls offer communication capability with staged heating and cooling, the Commercial Electronic thermostats provide 7-day programmable capability for economical applications, while the nonprogrammable thermostats offer a multitude of staged heating and cooling subbase options. 40RM field-installed accessories Discharge plenum directs the air discharge directly into the occupied space; integral horizontal and vertical louvers enable redirection of airflow. Accessory is available unpainted or painted. Field assembly required. Two-row hot water coils have 5.9-mm (5⁄8-in.) diameter copper tubes mechanically bonded to aluminum plate fins. Coils have non-ferrous headers. One-row steam coil has 25.4-mm (1-in.) OD copper tube and aluminum fins. The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam coil has a broad operating pressure range; up to 1207 kPag at 204.4 C (175 psig at 400 F) and up to 2069 kPag at 148.9 C (300 psig at 300 F). IDT steam coils are especially suited to applications where sub-freezing air enters the unit. Electric resistance heaters have a one- or two-stage, open-wire design and are mounted in a rigid frame. Safety cutouts for high temperature conditions are standard. Heaters also feature single-point power connection. Economizer (enthalpy controlled) provides ventilation air and ‘‘free’’ cooling if outside ambient temperature and humidity are suitable. Can also be used with CO2 sensors to help meet indoor air quality requirements. Economizer comes complete with 24 v controls. Return-air grille provides a protective barrier over the return-air opening and gives a finished appearance to units installed in the occupied space. Accessory is available unpainted or painted. Subbase provides a stable, raised platform and room for condensate drain connection for floor-mounted units. Accessory is available unpainted or painted. Field assembly required. CONDENSER COIL PROTECTION APPLICATIONS ENVIRONMENT* DESCRIPTION (Enviro-Shield™ Option) Standard, Al/Cu Pre-Coated Al/Cu Cu/Cu Post-Coated Al/Cu Post-Coated Cu/Cu Standard, Non-Corrosive Mild Coastal Moderate Coastal Severe Coastal Combined Coastal and Industrial X X X X X LEGEND Al/Cu — Aluminum Fin with Copper Tube Coil Cu/Cu — Copper Fin with Copper Tube Coil Enviro-Shield — Family of Coil Protection Options Post-Coated — Organic Coating applied to Entire Coil Assembly Pre-Coated — Epoxy Coating Applied to Fin Stock Material *See ‘‘Selection Guide: Environmental Corrosion Protection’’ Catalog No. 811-839 for more information. 6 Industrial X Overhead suspension brackets support units in horizontal ceiling installations. Carrier’s line of thermostats provide both programmable and non-programmable capability with the new Debonair™ line of commercial programmable thermostats, the TEMP System controls offer communication capability with staged heating and cooling, the Commercial Electronic thermostats provide 7-day programmable capability for economical applications, while the nonprogrammable thermostats offer a multitude of staged heating and cooling subbase options. CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when the CO2 level in the space exceeds the set point. A Carrier Comfort System programmable thermostat can be used to override the sensor if the outside-air temperature is too high or too low. CO2 sensors can be connected to the Carrier Comfort System relay pack or to the economizer accessory. Connection to the economizer requires field-supplied and installed Honeywell dc adapter no. Q769C1004. Condensate drain trap includes an overflow shutoff switch than can be wired to turn off the unit if the trap becomes plugged. The kit also includes a wire harness that can be connected to an alarm if desired. The transparent trap is designed for easy service and maintenance. CARRIER THERMOSTATS COMMERCIAL ELECTRONIC THERMOSTAT DEBONAIR™ COMMERCIAL PROGRAMMABLE THERMOSTAT Carrier ® Pm COOL AUTO HEAT NON-PROGRAMMABLE THERMOSTAT H TEMP SYSTEM THERMOSTAT WITH TIMECLOCK C 7 Options and accessories — 38AH024-034/40RM (cont) 40RM WITH DISCHARGE PLENUM, RETURN GRILLE, AND SUBBASE 40RM WITH HOT WATER OR STEAM COIL HOT WATER OR STEAM COIL DISCHARGE PLENUM RETURN-AIR GRILLE SUBBASE FAN COIL UNIT 40RM WITH ECONOMIZER 40RM WITH CONDENSATE DRAIN TRAP ECONOMIZER FAN COIL UNIT 8 FAN COIL UNIT Physical data — 38AH024-034 38AH024-034 UNITS — SI UNIT 38AH NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) With Aluminum-Fin Coil With Copper-Fin Coil COMPRESSOR Type Quantity Cylinders (ea) Speed (r/s) Capacity Steps (FIOP or Acy) — % —% —% Unloader Setting (kPa) — Load — Unload OIL CHARGE PER CIRCUIT (L) REFRIGERANT Shipping Charge (kg)** Operating Charge, Typical (kg)** CONDENSER FANS Quantity...Dia (mm) Nominal Hp Nominal Airflow (L/s) Speed (r/s) Watts (total) CONDENSER COIL Rows...Fins/m Total Face Area (sq m) Storage Cap. (kg)†† CONTROLS Pressurestat (kPa) High Pressure Cutout Cut-in Low Pressure Cutout Cut-in Oil Pressure Cutout (Diff) Cut-in (Diff) FAN CYCLING CONTROLS No. 2 Fan: Temp Close (C) Temp Open (C) PRESSURE RELIEF Location Temp (C) CONNECTIONS (Sweat) (ea ckt) Suction — in. OD Liquid — in. OD LEGEND Diff — Differential FIOP — Factory-Installed Option VAV — Variable Air Volume 024 Circuit 1 028 Circuit 2 Circuit 1 034 Circuit 2 Circuit 1 Circuit 2 63 73 87 798.3 872.3 825.6 899.0 Reciprocating Semi-Hermetic 06DH328 06DA328 6 6 24.3 24.3 853.0 951.2 06DH824 6 24.3 06DA824 6 24.3 100 67* 33† 100 — — 524 400 1.36 9.1 2...762 1.0 7870 2...748 3.64 17.4 06DH328 6 24.3 100 100 100 67* — 67* 33† — 33† Factory Installed — 524 — 524 — 400 — 400 4.73 R-22 1.36 1.36 1.36 1.36 9.1 9.1 9.1 11.4 Propeller Type — Direct Driven 2...762 1.0 7870 16 3100 Enhanced Copper Tubes, Aluminum Lanced Fin 2...748 3.64 17.4 06DA537 6 24.3 100 — — — — 1.36 11.4 2...762 1.0 7400 3...670 3.64 26.0 2937 6 48 2206 6 138 186 6 21 303 6 34 Manual Reset 41.4 60.7 21.1 6 1.6 15.6 6 1.6 Fusible Plug Liquid Line, Suction Line, Compressor 99 13⁄8 5 ⁄8 *Standard unit — single pressure-actuated suction unloader on compressor no. 1. †VAV FIOP — double electrically actuated unloaders on compressor no. 1. **With 7.6 m of interconnecting piping. ††Condenser 80% full of liquid R-22 at 48.8 C. 9 Physical data — 38AH024-034 (cont) 38AH024-034 UNITS — ENGLISH UNIT 38AH NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) With Aluminum-Fin Coil With Copper-Fin Coil COMPRESSOR Type Quantity Cylinders (ea) Speed (rpm) Capacity Steps (FIOP or Acy) — % —% —% Unloader Setting (psig) — Load — Unload OIL CHARGE PER CIRCUIT (Pt) REFRIGERANT Shipping Charge (lb)** Operating Charge, Typical (lb)** CONDENSER FANS Quantity...Dia (in.) Nominal Hp Nominal Airflow (cfm) Speed (rpm) Watts (total) CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) Storage Cap. (lb)†† CONTROLS Pressurestat (psig) High Pressure Cutout Cut-in Low Pressure Cutout Cut-in Oil Pressure Cutout (Diff) Cut-in (Diff) FAN CYCLING CONTROLS No. 2 Fan: Temp Close (F) Temp Open (F) PRESSURE RELIEF Location Temp (F) CONNECTIONS (Sweat) (ea ckt) Suction — in. OD Liquid — in. OD LEGEND Diff — Differential FIOP — Factory-Installed Option VAV — Variable Air Volume 10 024 Circuit 1 028 Circuit 2 Circuit 1 034 Circuit 2 Circuit 1 Circuit 2 18 21 25 1760 1923 1820 1982 Reciprocating Semi-Hermetic 06DH328 06DA328 6 6 1450 1450 1880 2097 06DH824 6 1450 06DA824 6 1450 100 67* 33† 100 — — 76 58 3 20 2...30 1.0 16,700 2...19 39.20 37.7 06DH328 6 1450 100 100 100 67* — 67* 33† — 33† Factory Installed — 76 — 76 — 58 — 58 10 R-22 3 3 3 3 20 20 20 25 Propeller Type — Direct Driven 2...30 1.0 16,700 950 3100 Enhanced Copper Tubes, Aluminum Lanced Fin 2...19 39.20 37.7 06DA537 6 1450 100 — — — — 3 25 2...30 1.0 15,700 3...17 39.20 56.6 426 6 7 320 6 20 27 6 3 44 6 5 Manual Reset 6.0 8.8 70 6 3 60 6 3 Fusible Plug Liquid Line, Suction Line, Compressor 210 13⁄8 5⁄8 *Standard unit — single pressure-actuated suction unloader on compressor no. 1. †VAV FIOP — double electrically actuated unloaders on compressor no. 1. **With 25 ft of interconnecting piping. ††Condenser 80% full of liquid R-22 at 120 F. Physical data — 40RM 40RM — SI UNIT 40RM NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) Nominal Airflow (L/s) Airflow Range (L/s) Nominal Motor kW (Standard Motor) 230-3-50, 400-3-50 Motor Speed (r/s) 230-3-50, 400-3-50 REFRIGERANT Operating charge (kg) (approx per circuit)* DIRECT-EXPANSION COIL Max Working Pressure (kPag) Face Area (sq m) No. of Splits No. of Circuits per Split Split Type...Percentage Rows...Fins/m STEAM COIL Max Working Pressure (kPag at 204.4 C) Total Face Area (sq m) Rows...Fins/m HOT WATER COIL Max Working Pressure (kPag) Total Face Area (sq m) Rows...Fins/m Water Volume (L) (m3) PIPING CONNECTIONS, Quantity...Size (in.) DX Coil — Suction (ODF) DX Coil — Liquid Refrigerant (ODF) Steam Coil, In (MPT) Steam Coil, Out (MPT) Hot Water Coil, In (MPT) Hot Water Coil, Out (MPT) Condensate (PVC) FILTERS Quantity...Size Access Location 016 52 024 70 028 87 034 105 311 63 313 63 463 82 467 82 2...381 2831 2124-3539 2...381 3775 2831-4719 2...457 4719 3539-5899 2...457 5663 4247-7079 2.16 3.73 5.60 7.46 23.8 23.8 23.8 23.8 2.04/2.04 2.27/2.27 R-22 1.13/1.13 1.64 2 12 3...591 1.59/1.59 Enhanced Copper Tubes, Aluminum Sine-Wave Fins 2999 1.85 2.30 2 2 13 15 Face...50/50 3...670 3...591 2.77 2 18 3...591 1207 1.24 1...394 1.24 1...394 1.24 2...335 1.24 2...335 1.39 1...394 1.39 1...394 1.39 2...493 1.39 2...493 1034 52.6 0.052 2...11⁄8 54.1 0.054 2...11⁄8 2...13⁄8 2...13⁄8 2...5⁄8 1...21⁄2 1...21⁄2 1...2 1...2 1 1...1 ⁄4 ODM/1 IDF Throwaway — Factory Supplied 4...406 × 508 × 51 4...508 x 610 x 51 4...406 × 610 × 51 4...508 x 635 x 51 Right or Left Side LEGEND DX — Direct Expansion TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge. 11 Physical data — 40RM (cont) 40RM — ENGLISH UNIT 40RM NOMINAL CAPACITY (Tons) OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) Nominal Airflow (cfm) Airflow Range (cfm) Nominal Motor Hp (Standard Motor) 230-3-50, 400-3-50 Motor Speed (rpm) 230-3-50, 400-3-50 REFRIGERANT Operating charge (lb) (approx per circuit)* DIRECT-EXPANSION COIL Max Working Pressure (psig) Face Area (sq ft) No. of Splits Split Type...Percentage No. of Circuits per Split Rows...Fins/in. STEAM COIL Max Working Pressure (psig at 400 F) Total Face Area (sq ft) Rows...Fins/in. HOT WATER COIL Max Working Pressure (psig) Total Face Area (sq ft) Rows...Fins/in. Water Volume (gal) (ft3) PIPING CONNECTIONS, Quantity...Size (in.) DX Coil — Suction (ODF) DX Coil — Liquid Refrigerant (ODF) Steam Coil, In (MPT) Steam Coil, Out (MPT) Hot Water Coil, In (MPT) Hot Water Coil, Out (MPT) Condensate (PVC) FILTERS Quantity...Size (in.) Access Location LEGEND DX — Direct Expansion TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge. 12 016 15 024 20 028 25 034 30 685 140 690 140 1020 180 1030 180 2...15 6000 4500-7500 2...15 8000 6000-10,000 2...18 10,000 7500-12,500 2...18 12,000 9000-15,000 2.9 5.0 7.5 10.0 4.5/4.5 5.0/5.0 1425 R-22 2.5/2.5 17.67 2 12 3...15 3.5/3.5 Enhanced Copper Tubes, Aluminum Sine-Wave Fins 435 19.88 24.86 2 2 Face...50/50 13 15 3...17 3...15 29.83 2 18 3...15 175 13.33 1...10 13.33 1...10 13.33 2...8.5 13.33 2...8.5 15.0 1...10 15.0 1...10 15.0 2...12.5 15.0 2...12.5 150 13.9 1.85 2...11⁄8 14.3 1.90 2...11⁄8 2...13⁄8 2...13⁄8 2...5⁄8 1...21⁄2 1...21⁄2 1...2 1...2 1 1...1 ⁄4 ODM/1 IDF Throwaway — Factory Supplied 4...16 × 20 × 2 4...20 x 24 x 2 4...16 × 24 × 2 4...20 x 25 x 2 Right or Left Side Dimensions — 38AH024-034 NOTES: 1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit. 2. There must be minimum 8 ft [2440 mm] clear air space above unit. 3. ‘‘C’’ in the package number indicates copper coils. 4. Dimensions in [ ] are in millimeters. 5. The approximate operating weight of the unit is shown below. 6. Certified dimensional drawing is available on request. CORNER WEIGHT — lbs [kg] UNIT 38AH 024 024C 028 028C 034 034C ‘‘1’’ ‘‘2’’ ‘‘3’’ ‘‘4’’ 631.6 [286.5] 666.5 [302.3] 658.7 [298.8] 693.0 [314.3] 667.0 [302.5] 718.3 [325.8] 577.6 [262.0] 609.5 [276.5] 602.4 [273.3] 633.8 [287.5] 610.0 [276.7] 656.8 [297.9] 263.1 [119.3] 309.0 [140.2] 267.0 [121.1] 313.0 [142.0] 288.0 [130.7] 344.8 [156.4] 287.7 [130.5] 337.9 [153.3] 291.9 [132.4] 342.2 [155.2] 315.0 [142.9] 377.0 [171.0] CENTER OF GRAVITY A Dim. in. [mm] 40.00 [1016] 43.00 [1092] 39.25 [997] 42.25 [1073] 41.00 [1041] 44.00 [1117] B Dim. in. [mm] 32.75 [832] TOTAL UNIT WT lb [kg] 1760 [798.3] 1923 [872.3] 1820 [825.6] 1982 [899.0] 1880 [853.0] 2097 [951.2] 13 Dimensions — 40RM 40RM016,024 TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: • Rear: 76 mm (3 in.) • Front: 762 mm (2 ft, 6 in.) • Right side: 762 mm (2 ft, 6 in.) • Left side: 762 mm (2 ft, 6 in.) • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. UNIT 40RM 016 024 14 UNIT WEIGHT lb (kg) 685 (311) 690 (313) 40RM028,034 TXV — Thermostatic Expansion Valve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Recommended clearance: • Rear: 76 mm (3 in.) • Front: 762 mm (2 ft, 6 in.) • Right side: 762 mm (2 ft, 6 in.) • Left side: 762 mm (2 ft, 6 in.) • Local codes or jurisdiction may prevail. 4. Liquid piping not supplied by Carrier. 5. Duct flange is factory supplied and field installed. 15 Selection procedure — 38AH024-034/40RM — SI NOTE: Pages 22 and 23 contain combination ratings for 38AH024-034 units and matching 40RM air handlers. If the 38AH units are matched with 39L or 39NX air handlers, use the Carrier AHU (Air-Handling Unit) selection program software package for combination ratings. If Totalinet P702 water coolers are used, determine the performance by cross-plotting the condensing unit performance found in this book against the P702 performance in the P702 product data book. If the 38AH condensing units are matched with 2 independent 40RM units, cross-plot for performance ratings or contact Carrier Application Engineering for assistance. I Determine cooling load, evaporator-air temperature and quantity. Given: Total Cooling Capacity Required (TC) . . . . . . . . . . . . . . . . . . . . . . . . . 60 kW Sensible Heat Capacity Required (SHC) . . . . . . . . . . . . . . . . . . . . . . . 48 kW Temperature Air Entering Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . 36 C Temperature Air Entering Evaporator (db/wb) . . . . . . . . 26.7 C db, 20 C wb Evaporator Air Quantity . . . . . . . . . . . . . . . 3800 L/s External Static Pressure . . . . . . . . . . . . . . . . . . 150 Pa Length of Interconnecting Refrigerant Piping . . . . . . . . . . . . . . . 18 m (Linear) II Select condensing unit air-handler combination. For this example, select a 38AH024 matched with a 40RM024. (See Combination Ratings table, page 22) This 38AH024/40RM024 condensing unit-air handler combination provides 62.5 kW of total cooling capacity and 49.2 kW of sensible capacity at the given conditions. If other temperatures or airflow values are required, interpolate the values from the combination ratings. 16 III Determine sizes of liquid and suction lines. Enter the Refrigerant Pipe Sizes table (page 40). The sizes shown are based on an equivalent length of pipe. This equivalent length is equal to the linear length of pipe indicated at the top of each sizing column, plus a 50% allowance for fitting losses. (For a more accurate determination of actual equivalent length in place of using the estimated 50% value, refer to Carrier System Design Manual.) For this example, note in the linear length column that the proper pipe size is 5⁄8 in. for the liquid lines and 13⁄8 in. for the suction lines. IV Determine fan rpm and bhp (brake horsepower). At the Air Handler Fan Performance table (page 27), enter the 40RM024 section at 3800 L/s and move to the External Static Pressure (ESP) column. Note that the conditions require 14.30 r/s at 2.64 kW. V Determine motor and drive. Enter the Fan Motor Data tables on page 41, and find that the standard motor for a 40RM024 unit is rated at 3.73. Since the kW required is 2.64, a standard motor satisfies the requirement and should be used. Next, find the type of drive that satisfies the 14.30 r/s requirement in the Drive Data tables on page 42. For a 40RM024 unit, the Standard Drive table shows an r/s range of 11.9 to 14.6. Since the r/s required is 14.30, the standard drive satisfies the requirement and should be used. Select the standard motor and standard drive combination (option code GC or ED). Selection procedure — 38AH024-034/40RM — English NOTE: Pages 24 and 25 contain combination ratings for 38AH024-034 units and matching 40RM air handlers. If the 38AH units are matched with 39L or 39NX air handlers, use the Carrier AHU (Air-Handling Unit) selection program software package for combination ratings. If Totalinet P702 water coolers are used, determine the performance by cross-plotting the condensing unit performance found in this book against the P702 performance in the P702 product data book. If the 38AH condensing units are matched with 2 independent 40RM units, cross-plot for performance ratings or contact Carrier Application Engineering for assistance. I Determine cooling load, evaporator-air temperature and quantity. Given: Total Cooling Capacity Required (TC) . . . . . . . . . . . . . . . . . . 210,000 Btuh Sensible Heat Capacity Required (SHC) . . . . . . . . . . . . . . . . . 175,000 Btuh Temperature Air Entering Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . 95 F Temperature Air Entering Evaporator (db/wb) . . . . . . . . . . . 80 F db, 67 F wb Evaporator Air Quantity . . . . . . . . . . . . . . . 8000 cfm External Static Pressure . . . . . . . . . . . . . . . 1.0 in. wg Length of Interconnecting Refrigerant Piping . . . . . . . . . . . . . . . . 30 ft (Linear) II Select condensing unit air-handler combination. For this example, select a 38AH024 matched with a 40RM024. (See Combination Ratings table, page 24.) This 38AH024/40RM024 condensing unit-air handler combination provides 214,500 Btuh of total cooling capacity and 179,000 Btuh of sensible capacity at the given conditions. If other temperatures or airflow values are required, interpolate the values from the combination ratings. III Determine sizes of liquid and suction lines. Enter the Refrigerant Pipe Sizes table (page 40). The sizes shown are based on an equivalent length of pipe. This equivalent length is equal to the linear length of pipe indicated at the top of each sizing column, plus a 50% allowance for fitting losses. (For a more accurate determination of actual equivalent length in place of using the estimated 50% value, refer to Carrier System Design Manual.) For this example, note in the linear length column that the proper pipe size is 5⁄8 in. for the liquid lines and 13⁄8 in. for the suction lines. IV Determine fan rpm and bhp (brake horsepower). At the Air Handler Fan Performance table (page 29), enter the 40RM024 section at 8000 cfm and move to the External Static Pressure (ESP) column. Note that the conditions require 954 rpm at 4.23 bhp. V Determine motor and drive. Enter the Fan Motor Data tables on page 41, and find that the alternate motor for a 40RM024 unit is rated at 7.5 hp. Since the bhp required is 4.23, an alternate motor satisfies the requirement and should be used. Next, find the type of drive that satisfies the 954 rpm requirement in the Drive Data tables on pages 42 and 43. For a 40RM024 unit, the Medium-Static Drive table shows an rpm range of 814 to 1018 . Since the rpm required is 954, the medium-static drive satisfies the requirement and should be used. Select the alternate motor and medium-static drive combination (option code TC or RD). 17 Performance data — 38AH024-034/40RM CONDENSING UNIT RATINGS — SI 38AH024 SST (C) −6 −4 −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 38AH034 24 42.9 11.3 35.2 47.0 11.5 35.2 51.4 11.7 35.2 55.5 11.9 35.6 59.9 12.1 36.2 64.3 12.3 36.9 69.2 12.5 37.7 74.1 12.8 38.5 78.9 13.0 39.2 Air Temperature Entering Condenser (C) 28 32 36 40 44 48 40.6 38.0 35.6 33.0 30.6 28.2 11.6 12.1 12.6 13.0 13.4 13.7 39.2 43.2 47.1 51.1 55.2 59.2 44.6 41.8 39.2 36.6 34.0 31.4 11.9 12.5 13.0 13.5 13.9 14.3 39.2 43.2 47.2 51.2 55.2 59.2 48.6 45.8 43.0 40.2 37.4 34.8 12.1 12.8 13.4 14.0 14.5 15.0 39.2 43.2 47.2 51.2 55.2 59.2 52.8 49.8 47.0 44.0 41.2 38.4 12.4 13.1 13.8 14.5 15.0 15.6 39.6 43.5 47.4 51.3 55.3 59.2 57.0 54.0 51.0 48.2 45.2 42.2 12.7 13.5 14.2 14.9 15.5 16.1 40.1 43.9 47.8 51.6 55.5 59.3 61.4 58.2 55.2 52.2 49.0 46.0 13.0 13.8 14.6 15.4 16.0 16.7 40.7 44.4 48.1 51.9 55.6 59.4 66.0 62.8 59.6 56.4 53.2 50.0 13.3 14.1 15.0 15.8 16.5 17.3 41.4 45.1 48.8 52.4 56.2 59.9 70.8 67.4 64.0 60.8 57.4 54.0 13.6 14.5 15.4 16.3 17.1 17.8 42.1 45.8 49.4 53.1 56.8 60.4 75.6 72.0 68.6 65.2 61.6 58.2 13.8 14.8 15.8 16.7 17.6 18.4 42.9 46.5 50.1 53.8 57.4 61.0 52 25.7 14.2 63.2 28.8 14.9 63.2 31.8 15.6 63.2 35.5 16.3 63.2 39.3 16.9 63.2 42.9 17.5 63.1 46.8 18.1 63.6 50.7 18.8 64.1 54.7 19.4 64.7 38AH028 SST (C) −6 −4 −2 0 2 4 6 8 10 18 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 24 51.1 13.4 35.4 55.2 13.8 36.0 59.7 14.1 36.5 64.5 14.4 37.1 69.3 14.7 37.8 74.0 15.0 38.8 79.4 15.3 39.6 85.0 15.7 40.5 90.6 16.0 41.5 Air Temperature Entering Condenser (C) 28 32 36 40 44 48 48.6 46.0 43.4 40.8 38.4 36.0 14.0 14.7 15.3 15.9 16.5 17.1 39.3 43.3 47.3 51.2 55.2 59.1 52.8 50.0 47.4 44.8 42.2 39.6 14.3 15.1 15.8 16.5 17.1 17.7 39.8 43.7 47.6 51.4 55.3 59.2 57.0 54.2 51.4 48.6 46.0 43.2 14.7 15.5 16.3 17.0 17.7 18.3 40.3 44.1 47.8 51.6 55.5 59.3 61.6 58.6 55.6 52.8 49.8 47.0 15.1 15.9 16.8 17.5 18.3 19.0 40.9 44.6 48.4 52.1 55.9 59.6 66.2 63.2 60.0 57.0 54.0 51.0 15.5 16.4 17.3 18.1 18.9 19.7 41.7 45.3 49.0 52.7 56.5 60.2 71.0 67.6 64.4 61.2 58.0 54.8 15.9 16.8 17.8 18.7 19.5 20.4 42.4 46.1 49.7 53.4 57.1 60.7 76.2 72.6 69.2 65.8 62.4 59.2 16.3 17.3 18.3 19.2 20.2 21.0 43.3 46.9 50.5 54.1 57.8 61.4 81.6 77.8 74.2 70.6 67.0 63.4 16.6 17.7 18.8 19.8 20.8 21.8 44.1 47.7 51.3 54.9 58.5 62.2 86.8 83.0 79.0 75.2 71.6 67.8 17.0 18.2 19.3 20.4 21.4 22.4 45.0 48.6 52.1 55.7 59.3 62.9 52 33.3 17.7 63.1 37.0 18.4 63.0 40.5 19.1 63.1 43.9 19.8 63.4 47.9 20.6 64.0 51.6 21.3 64.4 55.6 22.2 65.1 59.8 22.9 65.7 64.0 23.6 66.4 SST (C) −6 −4 −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 24 59.8 16.6 35.9 65.5 17.0 36.1 70.8 17.3 36.2 76.4 17.6 36.8 82.2 18.0 37.5 88.0 18.4 38.2 94.4 18.9 39.0 100.8 19.4 39.9 107.3 19.6 40.9 Air Temperature Entering Condenser (C) 28 32 36 40 44 48 57.1 54.0 51.1 48.1 45.3 42.4 17.3 18.1 18.9 19.7 20.4 21.0 40.0 43.9 47.9 51.9 55.9 59.9 62.2 59.2 56.0 52.9 49.8 46.8 17.7 18.6 19.5 20.3 21.0 21.8 40.1 44.0 48.0 51.9 55.9 59.9 67.5 64.2 60.8 57.5 54.3 51.0 18.1 19.1 20.0 21.0 21.7 22.6 40.3 44.1 48.1 52.0 56.0 59.9 73.0 69.5 66.0 62.5 59.1 55.7 18.6 19.5 20.6 21.6 22.5 23.4 40.7 44.5 48.4 52.2 56.1 60.1 78.7 75.0 71.4 67.7 64.2 60.6 19.0 20.1 21.2 22.2 23.2 24.1 41.3 45.1 48.8 52.7 56.4 60.3 84.3 80.5 76.8 72.9 69.2 65.5 19.5 20.7 21.8 22.9 24.0 24.9 42.0 45.6 49.3 53.0 56.8 60.5 90.4 86.5 82.4 78.5 74.6 70.6 20.0 21.2 22.5 23.6 24.7 25.8 42.8 46.4 50.0 53.7 57.4 61.1 96.7 92.5 88.2 84.1 80.0 75.8 20.5 21.8 23.1 24.3 25.5 26.6 43.7 47.2 50.8 54.5 58.1 61.7 102.9 98.6 94.1 89.7 85.5 81.1 20.9 22.3 23.7 25.1 26.3 27.5 44.5 48.1 51.7 55.3 58.9 62.4 LEGEND CMP — Compressor Power, kW SDT — Saturated Discharge Temperature (leaving compressor) (C) SST — Saturated Suction Temperature (entering condensing unit) TCG — Total Cooling Capacity, Gross (kW) NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 52 39.5 21.8 63.8 43.5 22.7 63.8 47.7 23.5 63.9 52.2 24.5 63.8 57.0 25.3 64.0 61.7 26.2 64.2 66.7 27.1 64.8 71.7 28.0 65.4 76.8 29.0 66.0 CONDENSING UNIT CIRCUIT RATINGS — SI 38AH024 CIRCUIT NO. 1 OR 2 Air Temperature Entering Condenser (C) SST (C) 24 28 32 36 40 44 48 TCG 21.5 20.3 19.0 17.8 16.5 15.3 14.1 −6 CMP 5.6 5.8 6.1 6.3 6.5 6.7 6.9 SDT 35.2 39.2 43.2 47.1 51.1 55.2 59.2 TCG 23.5 22.3 20.9 19.6 18.3 17.0 15.7 −4 CMP 5.7 5.9 6.2 6.5 6.8 7.0 7.2 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 TCG 25.7 24.3 22.9 21.5 20.1 18.7 17.4 −2 CMP 5.8 6.1 6.4 6.7 7.0 7.3 7.5 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 TCG 27.8 26.4 24.9 23.5 22.0 20.6 19.2 0 CMP 5.9 6.2 6.6 6.9 7.2 7.5 7.8 SDT 35.6 39.6 43.5 47.4 51.3 55.3 59.2 TCG 29.9 28.5 27.0 25.5 24.1 22.6 21.1 2 CMP 6.1 6.4 6.7 7.1 7.5 7.8 8.1 SDT 36.2 40.1 43.9 47.8 51.6 55.5 59.3 TCG 32.2 30.7 29.1 27.6 26.1 24.5 23.0 4 CMP 6.2 6.5 6.9 7.3 7.7 8.0 8.4 SDT 36.9 40.7 44.4 48.1 51.9 55.6 59.4 TCG 34.6 33.0 31.4 29.8 28.2 26.6 25.0 6 CMP 6.3 6.6 7.1 7.5 7.9 8.3 8.6 SDT 37.7 41.4 45.1 48.8 52.4 56.2 59.9 TCG 37.0 35.4 33.7 32.0 30.4 28.7 27.0 8 CMP 6.4 6.8 7.2 7.7 8.1 8.5 8.9 SDT 38.5 42.1 45.8 49.4 53.1 56.8 60.4 TCG 39.5 37.8 36.0 34.3 32.6 30.8 29.1 10 CMP 6.5 6.9 7.4 7.9 8.4 8.8 9.2 SDT 39.2 42.9 46.5 50.1 53.8 57.4 61.0 38AH028 CIRCUIT NO. 1 OR 2 Air Temperature Entering Condenser (C) SST (C) 24 28 32 36 40 44 48 TCG 25.5 24.3 23.0 21.7 20.4 19.2 18.0 −6 CMP 6.7 7.0 7.3 7.7 8.0 8.3 8.5 SDT 35.4 39.3 43.3 47.3 51.2 55.2 59.1 TCG 27.6 26.4 25.0 23.7 22.4 21.1 19.8 −4 CMP 6.9 7.2 7.5 7.9 8.2 8.5 8.9 SDT 36.0 39.8 43.7 47.6 51.4 55.3 59.2 TCG 29.8 28.5 27.1 25.7 24.3 23.0 21.6 −2 CMP 7.0 7.4 7.8 8.1 8.5 8.8 9.2 SDT 36.5 40.3 44.1 47.8 51.6 55.5 59.3 TCG 32.2 30.8 29.3 27.8 26.4 24.9 23.5 0 CMP 7.2 7.6 8.0 8.4 8.8 9.1 9.5 SDT 37.1 40.9 44.6 48.4 52.1 55.9 59.6 TCG 34.7 33.1 31.6 30.0 28.5 27.0 25.5 2 CMP 7.4 7.8 8.2 8.6 9.1 9.5 9.8 SDT 37.8 41.7 45.3 49.0 52.7 56.5 60.2 TCG 37.0 35.5 33.8 32.2 30.6 29.0 27.4 4 CMP 7.5 7.9 8.4 8.9 9.3 9.8 10.2 SDT 38.8 42.4 46.1 49.7 53.4 57.1 60.7 TCG 39.7 38.1 36.3 34.6 32.9 31.2 29.6 6 CMP 7.7 8.1 8.6 9.2 9.6 10.1 10.5 SDT 39.6 43.3 46.9 50.5 54.1 57.8 61.4 TCG 42.5 40.8 38.9 37.1 35.3 33.5 31.7 8 CMP 7.8 8.3 8.9 9.4 9.9 10.4 10.9 SDT 40.5 44.1 47.7 51.3 54.9 58.5 62.2 TCG 45.3 43.4 41.5 39.5 37.6 35.8 33.9 10 CMP 8.0 8.5 9.1 9.7 10.2 10.7 11.2 SDT 41.5 45.0 48.6 52.1 55.7 59.3 62.9 CMP SDT SST TCG — — — — LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 52 12.8 7.1 63.2 14.4 7.5 63.2 15.9 7.8 63.2 17.7 8.2 63.2 19.7 8.5 63.2 21.4 8.8 63.1 23.4 9.1 63.6 25.4 9.4 64.1 27.3 9.7 64.7 38AH034 CIRCUIT NO. 1 Air Temperature Entering Condenser (C) SST (C) 24 28 32 36 40 44 48 TCG 25.0 23.7 22.3 21.0 19.6 18.3 17.0 −6 CMP 6.7 7.0 7.3 7.7 8.0 8.3 8.5 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3 TCG 27.5 26.0 24.6 23.1 21.7 20.3 18.9 −4 CMP 6.8 7.1 7.5 7.9 8.2 8.5 8.9 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3 TCG 29.9 28.4 26.8 25.2 23.7 22.2 20.7 −2 CMP 6.9 7.2 7.7 8.1 8.5 8.8 9.2 SDT 35.1 39.2 43.2 47.3 51.3 55.3 59.3 TCG 32.4 30.8 29.2 27.6 25.9 24.4 22.8 0 CMP 7.0 7.4 7.8 8.3 8.7 9.1 9.5 SDT 35.5 39.5 43.4 47.4 51.3 55.3 59.3 TCG 35.0 33.4 31.7 30.0 28.3 26.7 25.0 2 CMP 7.1 7.5 8.0 8.5 8.9 9.3 9.7 SDT 36.1 39.9 43.8 47.6 51.5 55.3 59.2 TCG 37.7 35.9 34.2 32.5 30.7 29.0 27.3 4 CMP 7.2 7.7 8.2 8.7 9.1 9.6 10.0 SDT 36.6 40.4 44.1 47.8 51.6 55.4 59.2 TCG 40.6 38.7 36.9 35.0 33.2 31.4 29.6 6 CMP 7.3 7.8 8.3 8.9 9.4 9.8 10.3 SDT 37.2 41.1 44.7 48.4 52.1 55.9 59.6 TCG 43.5 41.5 39.6 37.6 35.7 33.8 31.9 8 CMP 7.5 8.0 8.5 9.1 9.6 10.1 10.6 SDT 38.2 41.9 45.5 49.1 52.8 56.5 60.1 TCG 46.3 44.3 42.3 40.2 38.2 36.3 34.3 10 CMP 7.6 8.1 8.7 9.3 9.9 10.4 10.9 SDT 39.1 42.7 46.3 49.9 53.5 57.1 60.7 52 15.6 8.9 63.2 17.4 9.2 63.2 19.1 9.6 63.4 21.2 9.9 63.2 23.4 10.2 63.0 25.5 10.5 62.9 27.7 10.9 63.4 29.9 11.2 63.8 32.3 11.5 64.3 52 16.7 8.9 63.1 18.5 9.2 63.0 20.3 9.5 63.1 22.0 9.9 63.4 23.9 10.3 64.0 25.8 10.7 64.4 27.8 11.1 65.1 29.9 11.4 65.7 32.0 11.8 66.4 38AH034 CIRCUIT NO. 2 Air Temperature Entering Condenser (C) SST (C) 24 28 32 36 40 44 48 TCG 34.8 33.4 31.7 30.1 28.5 27.0 25.4 −6 CMP 9.9 10.3 10.8 11.2 11.7 12.1 12.5 SDT 36.7 40.7 44.6 48.6 52.6 56.5 60.5 TCG 38.0 36.2 34.6 32.9 31.2 29.5 27.9 −4 CMP 10.2 10.6 11.1 11.6 12.1 12.5 12.9 SDT 36.9 41.0 44.8 48.7 52.6 56.6 60.5 TCG 40.9 39.1 37.4 35.6 33.8 32.1 30.3 −2 CMP 10.4 10.9 11.4 11.9 12.5 12.9 13.4 SDT 37.3 41.3 45.0 48.8 52.7 56.6 60.5 TCG 44.0 42.2 40.3 38.4 36.6 34.7 32.9 0 CMP 10.6 11.2 11.7 12.3 12.9 13.4 13.9 SDT 38.1 41.8 45.6 49.3 53.1 56.9 60.8 TCG 47.2 45.3 43.3 41.4 39.4 37.5 35.6 2 CMP 10.9 11.5 12.1 12.7 13.3 13.9 14.4 SDT 38.8 42.7 46.3 50.0 53.8 57.5 61.3 TCG 50.4 48.4 46.3 44.3 42.2 40.2 38.2 4 CMP 11.2 11.8 12.5 13.1 13.8 14.4 14.9 SDT 39.8 43.5 47.1 50.8 54.4 58.1 61.8 TCG 53.9 51.7 49.6 47.4 45.3 43.2 41.0 6 CMP 11.6 12.2 12.9 13.6 14.2 14.9 15.5 SDT 40.7 44.4 48.0 51.6 55.2 58.9 62.5 TCG 57.4 55.2 52.9 50.6 48.4 46.2 43.9 8 CMP 11.9 12.5 13.3 14.0 14.7 15.4 16.0 SDT 41.7 45.4 48.9 52.5 56.1 59.7 63.3 TCG 61.0 58.6 56.3 53.9 51.5 49.2 46.8 10 CMP 12.1 12.8 13.6 14.4 15.2 15.9 16.6 SDT 42.8 46.3 49.9 53.4 57.0 60.6 64.1 52 23.9 13.0 64.4 26.1 13.4 64.5 28.6 13.9 64.3 31.0 14.5 64.4 33.6 15.1 65.0 36.1 15.7 65.4 38.9 16.2 66.2 41.7 16.8 66.9 44.5 17.4 67.7 NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 19 Performance data — 38AH024-034/40RM (cont) CONDENSING UNIT RATINGS — ENGLISH 38AH024 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 38AH034 75 141.8 11.4 95.0 161.6 11.7 95.0 181.6 11.9 95.0 202.4 12.2 97.0 223.0 12.5 98.0 247.6 12.8 101.0 268.0 13.1 103.0 Air Temperature 85 95 130.6 119.0 11.7 12.4 105.0 115.0 149.4 136.8 12.1 12.9 105.0 115.0 168.2 154.8 12.5 13.5 105.0 115.0 188.4 174.4 12.9 14.0 107.0 116.0 208.0 194.0 13.4 14.5 108.0 117.0 232.0 216.0 13.8 15.0 110.0 119.0 254.0 236.0 14.2 15.6 112.0 121.0 Entering 100 113.2 12.7 120.0 130.6 13.3 120.0 148.0 13.9 120.0 167.4 14.5 121.0 186.8 15.0 122.0 208.0 15.6 123.0 228.0 16.2 125.0 Condenser (F) 105 115 107.4 96.2 12.9 13.3 125.0 135.0 124.4 112.0 13.6 14.2 125.0 135.0 141.4 128.0 14.3 15.0 125.0 135.0 160.4 146.4 14.9 15.8 126.0 135.0 179.6 165.0 15.6 16.5 126.0 136.0 200.0 184.4 16.2 17.3 128.0 137.0 220.0 204.0 16.8 18.0 130.0 139.0 125 84.8 13.8 145.0 99.6 14.8 145.0 114.6 15.8 145.0 132.4 16.6 145.0 150.5 17.5 146.0 168.6 18.4 146.0 188.0 19.3 148.0 38AH028 SST (F) 20 25 30 35 40 45 50 20 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 75 168.4 13.5 95.0 189.0 13.9 97.0 210.2 14.3 98.0 231.6 14.8 99.0 256.8 15.1 102.0 284.0 15.7 104.0 306.0 16.0 106.0 Air Temperature 85 95 157.6 145.6 14.1 15.0 105.0 115.0 177.4 164.6 14.6 15.7 106.0 116.0 197.4 183.8 15.2 16.3 107.0 117.0 220.0 204.0 15.7 17.0 109.0 118.0 242.0 226.0 16.3 17.7 111.0 120.0 266.0 250.0 16.9 18.3 113.0 122.0 292.0 272.0 17.4 19.0 115.0 124.0 Entering 100 139.8 15.4 120.0 158.4 16.1 121.0 177.2 16.8 121.0 197.6 17.6 123.0 218.0 18.3 125.0 242.0 19.0 127.0 264.0 19.8 129.0 Condenser (F) 105 115 134.0 122.8 15.8 16.6 125.0 135.0 152.2 140.2 16.6 17.4 126.0 135.0 170.6 157.4 17.3 18.3 126.0 136.0 190.4 176.4 18.1 19.2 128.0 137.0 210.0 195.2 18.9 20.2 129.0 138.0 232.0 216.0 19.7 21.0 131.0 140.0 256.0 238.0 20.6 22.0 133.0 142.0 125 111.4 17.4 145.0 128.0 18.3 145.0 144.2 19.3 146.0 162.6 20.3 147.0 179.8 21.5 147.0 199.0 22.3 149.0 221.0 23.5 151.0 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 75 198.0 16.6 97.0 223.5 17.1 97.0 249.4 17.6 97.0 276.2 18.0 99.0 304.5 18.7 101.0 335.0 19.3 103.0 367.0 19.7 106.0 Air Temperature 85 95 185.5 171.2 17.4 18.5 107.0 117.0 209.4 194.4 18.1 19.3 107.0 117.0 234.3 217.7 18.7 20.1 107.0 117.0 260.0 243.0 19.4 20.8 109.0 118.0 287.0 269.0 20.0 21.7 110.0 119.0 316.0 297.0 20.7 22.6 112.0 121.0 346.0 325.0 21.4 23.4 115.0 124.0 Entering 100 164.4 19.0 122.0 187.0 19.8 122.0 210.0 20.7 122.0 235.5 21.5 123.0 260.0 22.4 124.0 287.0 23.3 126.0 314.0 24.3 128.0 Condenser (F) 105 115 157.6 144.4 19.5 20.4 127.0 137.0 179.6 165.3 20.5 21.5 127.0 137.0 202.3 186.0 21.3 22.5 127.0 137.0 226.5 209.8 22.2 23.6 128.0 137.0 251.0 233.5 23.2 24.7 129.0 138.0 278.0 259.0 24.2 25.8 130.0 140.0 305.0 283.0 25.2 27.0 133.0 141.0 LEGEND CMP — Compressor Power, kW SDT — Saturated Discharge Temperature (leaving compressor) (F) SST — Saturated Suction Temperature (entering condensing unit) TCG — Total Cooling Capacity, Gross (1000 Btuh) NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 125 131.0 21.4 147.0 150.8 22.6 147.0 170.2 23.8 147.0 193.2 25.0 147.0 215.8 26.2 147.0 240.0 27.4 149.0 262.0 28.8 150.0 CONDENSING UNIT CIRCUIT RATINGS — ENGLISH 38AH024 CIRCUIT NO. 1 OR 2 Air Temperature SST (F) 75 85 95 TCG 70.9 65.3 59.5 20 CMP 5.7 5.9 6.2 SDT 95.0 105.0 115.0 TCG 80.8 74.7 68.4 25 CMP 5.8 6.1 6.5 SDT 95.0 105.0 115.0 TCG 90.8 84.1 77.4 30 CMP 6.0 6.3 6.7 SDT 95.0 105.0 115.0 TCG 101.2 94.2 87.2 35 CMP 6.1 6.5 7.0 SDT 97.0 107.0 116.0 TCG 111.5 104.0 97.0 40 CMP 6.3 6.7 7.3 SDT 98.0 108.0 117.0 TCG 123.8 116.0 108.0 45 CMP 6.4 6.9 7.5 SDT 101.0 110.0 119.0 TCG 134.0 127.0 118.0 50 CMP 6.6 7.1 7.8 SDT 103.0 112.0 121.0 Entering 100 56.6 6.3 120.0 65.3 6.7 120.0 74.0 7.0 120.0 83.7 7.2 121.0 93.4 7.5 122.0 104.0 7.8 123.0 114.0 8.1 125.0 Condenser (F) 105 115 53.7 48.1 6.5 6.7 125.0 135.0 62.2 56.0 6.8 7.1 125.0 135.0 70.7 64.0 7.2 7.5 125.0 135.0 80.2 73.2 7.5 7.9 126.0 135.0 89.8 82.5 7.8 8.3 126.0 136.0 100.0 92.2 8.1 8.6 128.0 137.0 110.0 102.0 8.4 9.0 130.0 139.0 38AH028 CIRCUIT NO. 1 OR 2 Air Temperature SST (F) 75 85 95 TCG 84.2 78.8 72.8 20 CMP 6.7 7.0 7.5 SDT 95.0 105.0 115.0 TCG 94.5 88.7 82.3 25 CMP 6.9 7.3 7.8 SDT 97.0 106.0 116.0 TCG 105.1 98.7 91.9 30 CMP 7.2 7.6 8.2 SDT 98.0 107.0 117.0 TCG 115.8 110.0 102.0 35 CMP 7.4 7.9 8.5 SDT 99.0 109.0 118.0 TCG 128.4 121.0 113.0 40 CMP 7.6 8.2 8.8 SDT 102.0 111.0 120.0 TCG 142.0 133.0 125.0 45 CMP 7.8 8.4 9.2 SDT 104.0 113.0 122.0 TCG 153.0 146.0 136.0 50 CMP 8.0 8.7 9.5 SDT 106.0 115.0 124.0 Entering 100 69.9 7.7 120.0 79.2 8.1 121.0 88.6 8.4 121.0 98.8 8.8 123.0 109.0 9.2 125.0 121.0 9.5 127.0 132.0 9.9 129.0 Condenser (F) 105 115 67.0 61.4 7.9 8.3 125.0 135.0 76.1 70.1 8.3 8.7 126.0 135.0 85.3 78.7 8.7 9.2 126.0 136.0 95.2 88.2 9.1 9.6 128.0 137.0 105.0 97.6 9.5 10.1 129.0 138.0 116.0 108.0 9.9 10.5 131.0 140.0 128.0 119.0 10.3 11.0 133.0 142.0 CMP SDT SST TCG — — — — LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) 125 42.4 6.9 145.0 49.8 7.4 145.0 57.3 7.9 145.0 66.2 8.3 145.0 75.3 8.8 146.0 84.3 9.2 146.0 94.0 9.6 148.0 38AH034 CIRCUIT NO. 1 Air Temperature SST (F) 75 85 95 TCG 82.4 76.5 70.2 20 CMP 6.7 7.0 7.5 SDT 95.0 105.0 115.0 TCG 93.8 87.4 80.4 25 CMP 6.9 7.3 7.8 SDT 95.0 105.0 115.0 TCG 105.4 98.3 90.7 30 CMP 7.0 7.5 8.1 SDT 95.0 105.0 115.0 TCG 117.2 110.0 102.0 35 CMP 7.1 7.7 8.3 SDT 97.0 106.0 116.0 TCG 130.5 122.0 114.0 40 CMP 7.3 7.9 8.6 SDT 97.0 107.0 116.0 TCG 145.0 135.0 127.0 45 CMP 7.4 8.1 8.9 SDT 99.0 109.0 118.0 TCG 158.0 149.0 139.0 50 CMP 7.6 8.3 9.2 SDT 102.0 111.0 120.0 Entering 100 67.1 7.7 120.0 77.0 8.0 120.0 87.0 8.4 120.0 98.5 8.6 121.0 110.0 8.9 121.0 122.0 9.2 123.0 134.0 9.5 125.0 Condenser (F) 105 115 64.0 58.0 7.9 8.3 125.0 135.0 73.6 67.0 8.3 8.7 125.0 135.0 83.3 76.0 8.6 9.1 125.0 135.0 94.5 86.8 8.9 9.5 126.0 135.0 106.0 97.5 9.2 9.9 126.0 135.0 118.0 109.0 9.6 10.3 127.0 137.0 130.0 120.0 9.9 10.7 129.0 138.0 125 51.9 8.7 145.0 60.3 9.2 145.0 68.7 9.7 145.0 79.2 10.1 145.0 89.3 10.5 145.0 100.0 11.0 147.0 110.5 11.5 147.0 125 55.7 8.7 145.0 64.0 9.2 145.0 72.1 9.7 146.0 81.3 10.2 147.0 89.9 10.7 147.0 99.5 11.2 149.0 110.5 11.8 151.0 38AH034 CIRCUIT NO. 2 Air Temperature SST (F) 75 85 95 TCG 115.6 109.0 101.0 20 CMP 9.9 10.4 11.0 SDT 98.0 108.0 118.0 TCG 129.7 122.0 114.0 25 CMP 10.2 10.8 11.5 SDT 98.0 108.0 118.0 TCG 144.0 136.0 127.0 30 CMP 10.6 11.2 12.0 SDT 98.0 109.0 118.0 TCG 159.0 150.0 141.0 35 CMP 10.9 11.7 12.5 SDT 101.0 111.0 120.0 TCG 174.0 165.0 155.0 40 CMP 11.4 12.1 13.1 SDT 104.0 113.0 122.0 TCG 190.0 181.0 170.0 45 CMP 11.9 12.6 13.7 SDT 106.0 115.0 124.0 TCG 209.0 197.0 186.0 50 CMP 12.1 13.1 14.2 SDT 110.0 118.0 127.0 Entering 100 97.3 11.3 123.0 110.0 11.8 123.0 123.0 12.3 123.0 137.0 12.9 125.0 150.0 13.5 127.0 165.0 14.1 129.0 180.0 14.8 131.0 Condenser (F) 105 115 93.6 86.4 11.6 12.1 128.0 138.0 106.0 98.3 12.2 12.8 128.0 138.0 119.0 110.0 12.7 13.4 128.0 138.0 132.0 123.0 13.3 14.1 129.0 139.0 145.0 136.0 14.0 14.8 131.0 140.0 160.0 150.0 14.6 15.5 133.0 142.0 175.0 163.0 15.3 16.3 136.0 144.0 125 79.1 12.7 148.0 90.5 13.5 148.0 101.5 14.1 148.0 114.0 14.9 149.0 126.5 15.7 149.0 140.0 16.4 151.0 151.5 17.4 153.0 NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 21 Performance data — 38AH024-034/40RM (cont) COMBINATION RATINGS — SI 38AH024 AND 40RM016 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 2100/0.06 2800/0.10 3500/0.12 Evaporator Air — Ewb (C) 22 20 16 22 20 16 22 20 16 63.9 59.4 53.2 67.3 62.9 56.9 69.8 64.9 59.2 32.7 37.7 53.2 36.4 43.2 56.9 40.1 48.3 59.2 12.18 11.90 11.52 12.39 12.11 11.75 12.54 12.24 11.89 62.2 57.6 51.7 65.4 61.0 55.3 67.8 63.0 57.6 32.0 36.9 51.7 35.7 42.4 55.3 39.4 47.3 57.6 13.06 12.78 12.40 13.26 12.99 12.63 13.41 13.11 12.77 60.4 56.0 50.3 63.5 59.2 53.7 65.8 61.1 56.0 31.4 36.2 50.3 35.0 41.5 53.7 38.7 46.3 56.0 13.89 13.51 13.01 14.16 13.79 13.31 14.36 13.95 13.51 58.6 54.2 48.8 61.5 57.3 52.1 63.7 59.1 54.4 30.7 35.4 48.8 34.2 40.6 52.1 38.0 45.3 54.4 14.91 14.51 14.02 15.17 14.79 14.32 15.37 14.96 14.52 56.7 52.3 47.0 59.5 55.2 50.3 61.7 57.1 52.5 30.0 34.6 47.0 33.5 39.7 50.3 37.3 44.3 52.5 15.84 15.34 14.74 16.15 15.67 15.10 16.40 15.88 15.36 54.8 50.5 45.5 57.3 53.2 48.6 59.5 55.0 50.8 29.2 33.8 45.5 32.8 38.8 48.6 36.5 43.2 50.8 16.73 16.11 15.40 17.09 16.50 15.84 17.40 16.76 16.16 52.8 48.6 43.8 55.1 51.1 46.8 57.2 52.9 49.0 28.5 32.9 43.8 32.0 37.8 46.8 35.7 42.1 49.0 17.72 17.09 16.38 18.07 17.47 16.82 18.39 17.73 17.15 50.8 46.6 42.1 53.0 49.0 44.9 55.0 50.7 47.1 27.7 32.1 42.1 31.2 36.9 44.9 35.0 41.0 47.1 18.71 18.07 17.37 19.05 18.44 17.81 19.37 18.70 18.14 38AH024 AND 40RM024 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 2900/0.06 3800/0.10 4700/0.12 Evaporator Air — Ewb (C) 22 20 16 22 20 16 22 20 16 71.3 66.0 59.9 74.4 68.9 63.5 76.4 71.3 66.3 38.0 45.1 59.9 43.1 52.1 63.5 47.6 58.3 66.3 12.63 12.31 11.93 12.82 12.48 12.15 12.94 12.63 12.32 69.2 64.0 58.1 72.2 66.9 61.7 74.1 69.2 64.5 37.2 44.3 58.1 42.3 51.2 61.7 46.8 57.3 64.5 13.50 13.18 12.81 13.69 13.35 13.03 13.81 13.50 13.20 67.1 62.0 56.4 69.9 64.7 59.9 71.7 66.9 62.6 36.3 43.5 56.4 41.5 50.2 59.9 45.9 56.2 62.6 14.48 14.03 13.55 14.72 14.27 13.84 14.87 14.46 14.08 65.0 59.9 54.7 67.5 62.5 58.0 69.2 64.6 60.7 35.5 42.6 54.7 40.6 49.2 58.0 45.1 55.2 60.7 15.49 15.03 14.55 15.72 15.27 14.86 15.87 15.46 15.10 62.9 57.8 52.7 65.4 60.4 56.1 67.0 62.4 58.7 34.7 41.8 52.7 39.8 48.3 56.1 44.3 54.2 58.7 16.54 15.96 15.38 16.82 16.26 15.76 17.00 16.49 16.06 60.6 55.6 50.9 62.9 58.1 54.1 64.4 60.0 56.7 33.8 40.9 50.9 39.0 47.3 54.1 43.4 53.1 56.7 17.56 16.84 16.17 17.89 17.20 16.63 18.10 17.47 17.00 58.2 53.4 48.9 60.4 55.8 52.1 61.8 57.5 54.6 32.8 40.0 48.9 38.0 46.2 52.1 42.5 21.9 54.6 18.54 17.80 17.14 18.86 18.17 17.61 19.07 18.43 17.99 56.0 51.1 46.9 58.0 53.5 50.0 59.3 55.1 52.5 31.9 39.0 46.9 37.2 45.2 50.0 41.6 50.8 52.5 19.51 18.76 18.12 19.82 19.12 18.60 20.02 19.38 18.97 LEGEND BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry Bulb Lwb — Leaving Wet Bulb SHC — Sensible Heating Capacity (kW) TC — Total Capacity (kW) NOTES: 1. All combination ratings are based on refrigerant R-22. 2. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. At any other temperature, correct the SHC reading from the table of cooling capacities as follows: Correction factor = 1.23 x 10-3 x (1 − BF) x (db − 26.7) Above 26.7 C, add SHC correction to SHC. Below 26.7 C, subtract SHC correction from SHC. 22 38AH024 AND 40RM028 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 4700/0.10 5900/0.12 Evaporator Air — Ewb (C) 16 22 20 16 22 20 16 65.0 79.7 73.4 68.9 81.2 76.1 72.2 65.0 49.3 60.1 68.9 55.2 67.6 72.2 12.24 13.14 12.76 12.48 13.24 12.92 12.68 63.1 77.4 71.1 67.0 78.8 73.7 70.2 63.1 48.5 59.1 67.0 54.4 66.6 70.2 13.12 14.01 13.62 13.36 14.10 13.78 13.56 61.1 74.8 68.7 65.0 76.1 71.2 68.1 61.1 47.6 58.1 65.0 53.5 65.5 68.1 13.96 15.15 14.62 14.29 15.26 14.83 14.56 59.1 72.2 66.3 62.9 73.4 68.7 66.0 59.1 46.7 57.0 62.9 52.5 64.3 66.0 14.96 16.15 15.61 15.30 16.26 15.83 15.58 57.1 69.9 64.0 60.9 71.1 66.4 64.0 57.1 45.9 56.0 60.9 51.8 63.3 64.0 15.88 17.34 16.66 16.31 17.47 16.94 16.66 55.0 67.2 61.4 58.7 68.3 63.7 61.7 55.0 44.9 54.9 58.7 50.8 62.1 61.7 16.76 18.50 17.67 17.28 18.65 18.00 17.72 52.8 64.4 58.8 56.4 65.4 61.0 59.4 52.8 43.9 53.8 56.4 49.8 60.9 59.4 17.72 19.46 18.62 18.26 19.60 18.95 18.71 50.7 61.8 56.3 54.2 62.7 58.4 57.1 50.7 43.0 52.7 54.2 48.9 58.1 57.1 18.69 20.41 19.55 19.24 20.54 19.89 19.69 3500/0.06 22 77.3 43.2 13.00 75.1 42.4 13.87 72.8 41.5 14.97 70.4 40.6 15.98 68.3 39.9 17.15 65.8 38.9 18.30 63.2 38.0 19.28 60.8 37.1 20.25 20 70.6 51.6 12.58 68.1 50.9 13.43 65.5 50.2 14.34 62.9 49.5 15.30 60.4 48.8 16.25 57.7 48.0 17.14 55.0 47.2 18.04 52.3 46.5 18.94 38AH028 AND 40RM024 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 3800/0.10 4700/0.12 Evaporator Air — Ewb (C) 16 22 20 16 22 20 16 64.7 81.1 75.1 68.6 83.5 77.9 71.6 64.7 45.5 54.9 68.6 50.1 61.3 71.6 14.25 15.42 14.99 14.53 15.59 15.20 14.75 63.2 79.1 73.2 67.0 81.3 75.9 70.0 63.2 44.8 54.0 67.0 49.3 60.4 70.0 15.58 16.46 16.14 15.79 16.59 16.28 15.96 61.6 76.7 71.1 65.3 78.8 73.6 68.2 61.6 43.9 53.1 65.3 48.4 59.3 68.2 16.44 17.62 17.18 16.72 17.79 17.38 16.95 59.8 74.4 68.9 63.4 76.4 71.4 66.3 59.8 43.1 52.1 63.4 47.6 58.3 66.3 17.36 18.82 18.27 17.72 19.02 18.52 18.01 58.0 72.1 66.7 61.5 74.0 69.0 64.3 58.0 42.2 51.1 61.5 46.7 57.2 64.3 18.23 19.98 19.32 18.67 20.22 19.60 19.02 56.2 69.6 64.5 59.6 71.4 66.7 62.4 56.2 41.4 50.1 59.6 45.8 56.1 62.4 19.39 21.15 20.47 19.84 21.38 20.76 20.19 54.4 67.3 62.3 57.8 68.9 64.3 60.4 54.4 40.5 49.1 57.8 45.0 21.9 60.4 20.35 22.10 21.42 20.80 22.33 21.70 21.17 52.4 64.3 59.6 55.6 65.7 61.5 58.1 52.4 39.4 47.9 55.6 43.9 53.7 58.1 21.49 24.15 23.10 22.20 24.48 23.52 22.76 2900/0.06 22 77.4 40.4 15.16 75.6 39.7 16.26 73.4 38.8 17.36 71.3 38.0 18.51 69.1 37.1 19.61 66.9 36.2 20.78 64.7 35.4 21.75 62.0 34.3 23.63 20 71.9 47.5 14.77 70.1 46.8 15.96 68.1 45.9 16.95 66.0 45.1 17.98 63.9 44.2 18.96 61.7 43.4 20.11 59.6 42.5 21.06 57.2 41.5 22.55 4. Gross capacities shown do not include a deduction for evaporator-fan motor heat. 5. Formulas (cooling) sensible heat capacity (kW) 1.23 x 10−3 x (L/s) tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb) total capacity (kW) hlwb = hewb − 1.20 x 10−3 x (L/s) tldb = tedb − where hewb = enthalpy of air entering evaporator coil (kJ/kg). 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table on page 40 are based on 1.1° C line loss. COMBINATION RATINGS — SI (cont) 38AH028 AND 40RM028 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 3500/0.06 4700/0.10 5900/0.12 Evaporator Air — Ewb (C) 22 20 16 22 20 16 22 20 16 84.1 78.3 70.6 87.3 80.6 74.8 89.3 83.5 78.2 45.8 53.8 70.6 52.0 63.2 74.8 57.9 70.9 78.2 15.64 15.22 14.67 15.87 15.39 14.97 16.01 15.60 15.22 82.1 75.9 68.9 85.0 78.4 73.0 86.9 81.3 76.4 45.0 53.1 68.9 51.2 62.3 73.0 57.1 69.9 76.4 16.63 16.28 15.89 16.79 16.42 16.12 16.89 16.58 16.31 79.6 73.2 67.0 82.3 75.9 70.9 83.9 78.6 74.3 44.1 52.3 67.0 50.2 61.2 70.9 56.1 68.7 74.3 17.85 17.35 16.86 18.06 17.56 17.17 18.19 17.77 17.43 77.4 70.6 65.0 79.9 73.5 68.9 81.4 76.2 72.2 43.3 51.6 65.0 49.4 60.1 68.9 55.2 67.7 72.2 19.12 18.44 17.88 19.37 18.73 18.27 19.52 19.00 18.60 75.0 67.9 63.0 77.2 71.0 66.8 78.7 73.6 70.1 42.4 50.9 63.0 48.4 59.1 66.8 54.3 66.5 70.1 20.35 19.46 18.84 20.63 19.85 19.33 20.81 20.18 19.74 72.5 65.2 60.9 74.5 68.5 64.7 75.9 71.0 67.9 41.4 50.1 60.9 47.5 58.0 64.7 53.4 65.3 67.9 21.52 20.56 20.00 21.78 20.99 20.50 21.96 21.32 20.92 70.1 62.6 58.9 71.9 66.0 62.6 73.1 68.4 65.7 40.6 49.4 58.9 46.6 56.9 62.6 52.4 64.2 65.7 22.49 21.46 20.96 22.73 21.92 21.47 22.90 22.25 21.89 67.0 59.4 56.5 68.5 62.9 60.1 69.5 65.1 63.0 39.4 48.5 56.5 45.4 55.6 60.1 51.2 62.8 63.0 24.77 23.07 22.41 25.10 23.84 23.21 25.33 24.34 23.87 38AH028 AND 40RM034 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 4250/0.06 5650/0.10 7050/0.12 Evaporator Air — Ewb (C) 22 20 16 22 20 16 22 20 16 90.2 81.9 75.9 92.7 85.5 80.5 94.4 88.5 84.3 50.5 61.0 75.9 58.3 70.8 80.5 65.4 79.8 84.3 16.07 15.48 15.05 16.25 15.73 15.38 16.37 15.95 15.63 87.8 79.6 73.9 90.2 83.1 78.5 91.7 86.0 82.2 49.6 60.0 73.9 57.4 69.7 78.5 64.5 78.7 82.2 16.95 16.49 16.17 17.08 16.68 16.43 17.16 16.84 16.63 85.0 76.9 71.7 87.1 80.2 76.1 88.5 82.9 79.7 48.5 58.9 71.7 56.3 68.4 76.1 63.4 77.4 79.7 18.27 17.64 17.23 18.43 17.89 17.58 18.55 18.11 17.86 82.5 74.4 69.5 84.4 77.6 73.9 85.8 80.3 77.5 47.6 57.9 69.5 55.4 67.3 73.9 62.5 76.2 77.5 19.63 18.82 18.33 19.82 19.14 18.77 19.96 19.41 19.13 79.9 71.7 67.3 81.5 74.9 71.6 82.7 77.5 75.1 46.5 56.8 67.3 54.4 66.1 71.6 61.5 74.9 75.1 20.96 19.94 19.38 21.17 20.33 19.92 21.32 20.66 20.36 77.1 69.0 65.0 78.6 72.1 69.2 79.7 74.6 72.6 45.5 55.6 65.0 53.3 64.9 69.2 60.5 73.6 72.6 22.12 21.07 20.53 22.31 21.46 21.08 22.45 21.79 21.53 74.4 66.4 62.7 75.7 69.4 66.8 76.7 71.8 70.1 44.4 54.6 62.7 52.3 63.7 66.8 59.5 72.4 70.1 23.08 21.99 21.48 23.25 22.39 22.04 23.38 22.72 22.49 70.9 63.2 60.0 71.8 65.9 63.8 72.6 68.1 67.0 43.1 53.2 60.0 51.0 62.2 63.8 58.2 68.1 67.0 25.63 23.91 23.19 25.85 24.51 24.05 26.03 25.02 24.76 LEGEND BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry Bulb Lwb — Leaving Wet Bulb SHC — Sensible Heating Capacity (kW) TC — Total Capacity (kW) NOTES: 1. All combination ratings are based on refrigerant R-22. 2. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. At any other temperature, correct the SHC reading from the table of cooling capacities as follows: Correction factor = 1.23 x 10-3 x (1 − BF) x (db − 26.7) Above 26.7 C, add SHC correction to SHC. Below 26.7 C, subtract SHC correction from SHC. 38AH034 AND 40RM028 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 4700/0.10 5900/0.12 Evaporator Air — Ewb (C) 16 22 20 16 22 20 16 78.1 97.3 90.2 82.5 99.8 93.5 86.2 78.1 55.5 67.3 82.5 61.4 75.3 86.2 17.63 19.13 18.57 17.97 19.32 18.83 18.26 76.1 94.8 87.7 80.4 97.2 90.9 84.1 76.1 54.6 66.2 80.4 60.5 74.2 84.1 18.86 20.35 19.79 19.21 20.54 20.04 19.50 74.2 92.2 85.3 78.5 94.4 88.3 82.1 74.2 53.7 65.2 78.5 59.6 73.1 82.1 19.97 21.77 21.08 20.40 21.99 21.38 20.76 72.1 89.4 82.6 76.4 91.5 85.6 79.9 72.1 52.7 64.0 76.4 58.6 71.9 79.9 21.44 23.23 22.52 21.87 23.44 22.83 22.24 70.1 86.7 80.0 74.2 88.7 82.9 77.7 70.1 51.8 62.9 74.2 57.7 70.7 77.7 22.55 24.63 23.79 23.07 24.87 24.15 23.50 67.9 84.0 77.3 72.1 85.8 80.2 75.5 67.9 50.8 61.8 72.1 56.7 69.5 75.5 23.71 26.09 25.11 24.32 26.35 25.53 24.83 65.7 80.9 74.5 69.8 82.6 77.2 73.1 65.7 49.7 60.6 69.8 55.6 68.1 73.1 24.94 27.62 26.49 25.65 27.91 26.97 26.24 63.4 78.2 71.8 67.4 79.7 74.5 70.7 63.4 48.8 59.4 67.4 54.7 66.9 70.7 26.51 29.16 28.01 27.23 29.44 28.50 27.83 3500/0.06 22 93.1 49.1 18.80 90.8 48.2 20.03 88.5 47.4 21.40 86.0 46.5 22.88 83.6 45.6 24.24 81.1 44.6 25.66 78.4 43.6 27.17 75.8 42.7 28.74 20 88.9 56.8 18.47 86.1 56.0 19.66 83.4 55.2 20.89 80.5 54.4 22.30 77.6 53.6 23.49 74.7 52.8 24.72 71.7 51.9 25.99 68.7 51.1 27.45 38AH034 AND 40RM034 Temp (C) Air Entering Condenser 24 28 32 36 40 44 48 52 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — L/s/BF 5650/0.10 7050/0.12 Evaporator Air — Ewb (C) 16 22 20 16 22 20 16 84.4 103.9 96.2 89.4 106.2 99.5 93.4 84.4 62.2 75.4 89.4 69.3 84.8 93.4 18.12 19.65 19.04 18.51 19.82 19.30 18.82 82.1 101.2 93.4 87.1 103.3 96.7 91.1 82.1 61.2 74.2 87.1 68.3 83.5 91.1 19.34 20.86 20.24 19.74 21.02 20.50 20.06 80.0 98.2 90.7 84.8 100.1 93.8 88.8 80.0 60.2 73.0 84.8 67.3 82.2 88.8 20.55 22.37 21.62 21.03 22.56 21.93 21.43 77.6 95.1 87.7 82.4 96.9 90.8 86.2 77.6 59.1 71.7 82.4 66.2 80.9 86.2 22.01 23.82 23.05 22.50 24.00 23.37 22.90 75.3 92.1 84.8 80.0 93.8 87.8 83.8 75.3 58.1 70.5 80.0 65.2 79.5 83.8 23.20 25.30 24.39 23.78 25.51 24.77 24.26 72.9 89.1 81.9 77.5 90.6 84.8 81.2 72.9 57.0 69.2 77.5 64.1 78.2 81.2 24.45 26.84 25.78 25.13 27.07 26.21 25.68 70.4 85.6 78.7 74.9 87.0 81.5 78.5 70.4 55.8 67.8 74.9 62.9 76.7 78.5 25.77 28.45 27.24 26.55 28.70 27.72 27.19 67.9 82.6 75.8 72.3 83.9 78.5 75.9 67.9 54.7 66.5 72.3 61.9 75.4 75.9 27.31 29.97 28.74 28.11 30.20 29.22 28.75 4250/0.06 22 100.3 54.4 19.36 97.8 53.4 20.59 95.1 52.4 22.06 92.3 51.3 23.53 89.6 50.3 24.99 86.8 49.2 26.50 83.7 48.0 28.11 80.9 46.9 29.65 20 92.2 65.3 18.73 89.6 64.2 19.93 86.9 63.1 21.24 84.1 61.9 22.67 81.3 60.7 23.95 78.5 59.6 25.28 75.5 58.3 26.66 72.6 57.1 28.16 4. Gross capacities shown do not include a deduction for evaporator-fan motor heat. 5. Formulas (cooling) sensible heat capacity (kW) 1.23 x 10−3 x (L/s) tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb) total capacity (kW) hlwb = hewb − 1.20 x 10−3 x (L/s) tldb = tedb − where hewb = enthalpy of air entering evaporator coil (kJ/kg). 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled system (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table on page 40 are based on 1.1° C line loss. 23 Performance data — 38AH024-034/40RM (cont) COMBINATION RATINGS — ENGLISH 38AH024 AND 40RM016 Temp (F) Air Entering Condenser 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 38AH024 AND 40RM028 Evaporator Air — Cfm/BF 4500/0.03 6000/0.05 7500/0.08 Evaporator Air — Ewb (F) 72 67 62 72 67 62 72 67 62 211.3 191.6 173.6 221.7 203.6 186.3 229.2 211.4 195.4 106.1 131.1 166.6 118.5 151.3 186.3 130.3 169.2 195.4 13.46 13.13 12.83 13.63 13.33 13.04 13.75 13.46 13.19 202.6 184.4 167.6 211.9 195.4 179.6 218.9 202.5 188.3 103.0 127.9 161.4 114.9 147.4 179.6 126.6 164.7 188.3 14.70 14.28 13.90 14.91 14.53 14.17 15.06 14.69 14.37 198.0 180.5 164.3 206.8 191.0 175.8 213.5 197.8 184.4 101.4 126.1 158.5 112.9 145.2 175.8 124.7 162.4 184.4 15.32 14.82 14.36 15.57 15.12 14.69 15.75 15.31 14.93 193.2 176.4 160.8 201.5 186.4 172.0 208.0 192.9 180.3 99.7 124.3 155.4 111.0 143.0 172.0 122.7 160.0 180.3 16.00 15.51 15.05 16.25 15.80 15.38 16.43 15.99 15.62 183.5 167.7 153.1 191.0 177.0 163.7 197.0 183.0 171.8 96.3 120.4 148.6 107.0 138.5 163.7 118.8 155.0 171.8 17.26 16.61 16.01 17.57 17.00 16.45 17.82 17.24 16.78 173.2 158.7 145.1 179.8 167.2 155.1 185.4 172.5 162.9 92.7 116.3 141.6 102.8 133.7 155.1 114.6 149.8 162.9 18.63 17.91 17.23 18.96 18.33 17.73 19.23 18.60 18.11 38AH024 AND 40RM024 Temp (F) Air Entering Condenser 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW LEGEND BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry Bulb Lwb — Leaving Wet Bulb SHC — Sensible Heating Capacity (1000 Btuh) TC — Total Capacity (1000 Btuh) NOTES: 1. All combination ratings are based on refrigerant R-22. 2. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator coil. Below 80 F dry-bulb, subtract (correction factor × cfm) from SHC. Above 80 F dry bulb, add (correction factor × cfm) to SHC. 79 81 0.10 0.20 0.30 0.99 0.88 0.77 ENTERING-AIR DRY-BULB TEMP (F) 78 77 76 75 under 75 82 83 84 85 over 85 Correction Factor 1.98 2.97 3.96 4.95 Use formula 1.76 2.64 3.52 4.40 shown below. 1.54 2.31 3.08 3.85 Interpolation is permissible. Correction Factor = 1.1 x (1 − BF) x (db − 80). 24 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — Cfm/BF 10,000/0.06 12,500/0.08 Evaporator Air — Ewb (F) 62 72 67 62 72 67 62 214.3 261.8 239.0 229.0 266.4 248.1 241.2 212.5 160.6 212.9 229.0 180.5 240.6 241.2 13.50 14.30 13.92 13.75 14.37 14.07 13.95 205.3 248.7 227.1 219.4 252.6 235.7 230.9 204.2 155.9 208.0 219.4 175.9 235.2 230.9 14.76 15.74 15.25 15.08 15.83 15.45 15.34 200.5 242.1 221.0 214.3 245.7 229.4 225.6 199.9 153.6 205.5 214.3 173.6 229.4 225.6 15.39 16.56 15.97 15.78 16.67 16.21 16.10 195.6 235.3 214.8 209.1 238.6 223.0 220.1 195.3 151.2 202.9 209.1 171.2 223.0 220.1 16.07 17.24 16.63 16.47 17.34 16.88 16.79 185.6 222.6 202.6 198.8 225.4 210.6 209.5 186.2 146.8 197.9 198.8 166.8 210.6 209.5 17.35 18.87 18.05 17.89 18.99 18.38 18.33 175.0 208.8 189.8 187.7 211.2 197.4 197.9 176.5 141.9 189.8 187.7 162.1 197.4 197.9 18.72 20.40 19.45 19.35 20.52 19.83 19.86 7500/0.04 72 252.4 140.1 14.14 240.2 135.6 15.55 234.0 133.3 16.34 227.7 131.0 17.01 215.5 126.6 18.58 202.4 121.8 20.08 67 229.4 181.8 13.76 218.3 177.3 15.05 212.6 175.0 15.73 206.7 172.6 16.40 195.1 167.9 17.74 182.9 163.0 19.11 38AH028 AND 40RM024 Evaporator Air — Cfm/BF 6,000/0.03 8,000/0.06 10,000/0.07 Evaporator Air — Ewb (F) 72 67 62 72 67 62 72 67 62 234.5 214.7 196.5 244.6 224.8 209.7 249.6 232.7 220.2 123.6 158.1 191.1 140.2 183.3 209.7 154.6 206.1 220.2 13.84 13.51 13.21 14.01 13.68 13.43 14.09 13.81 13.60 223.9 205.4 188.9 233.0 214.5 201.4 237.2 221.8 211.5 119.5 154.3 184.5 136.0 179.0 201.4 150.2 201.1 211.5 15.18 14.76 14.38 15.39 14.96 14.67 15.48 15.13 14.90 218.4 200.4 184.7 227.0 209.1 196.9 230.9 216.2 206.8 117.4 152.2 180.9 133.9 176.7 196.9 148.0 198.6 206.8 15.89 15.39 14.94 16.14 15.63 15.29 16.25 15.83 15.57 212.7 195.4 180.4 220.9 203.5 192.4 224.4 210.4 202.0 115.3 150.2 177.1 131.7 174.4 192.4 145.7 195.9 202.0 16.57 16.06 15.62 16.82 16.30 15.98 16.92 16.51 16.26 201.6 185.1 171.4 209.2 192.5 183.0 212.1 199.1 192.3 111.0 145.9 169.3 127.4 169.7 183.0 141.4 190.8 192.3 18.01 17.33 16.76 18.32 17.63 17.24 18.44 17.91 17.63 189.8 174.3 162.0 196.6 180.8 173.1 198.9 187.1 182.0 106.5 141.5 161.1 122.8 164.8 173.1 136.7 185.3 182.0 19.45 18.68 18.07 19.79 19.01 18.62 19.90 19.32 19.07 BYPASS FACTOR Temp (F) Air Entering Condenser Temp (F) Air Entering Condenser 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — Cfm/BF 8,000/0.06 10,000/0.07 Evaporator Air — Ewb (F) 62 72 67 62 72 67 62 215.7 267.1 247.0 228.8 273.1 255.0 239.4 207.8 148.3 192.7 228.8 162.9 216.3 239.4 15.64 16.93 16.42 15.97 17.08 16.63 16.24 206.6 256.5 236.5 219.8 262.0 244.5 230.4 200.0 144.5 188.3 219.8 159.0 211.5 230.4 17.22 18.46 17.96 17.54 18.60 18.16 17.81 202.1 251.2 231.3 215.3 256.5 239.3 225.9 196.1 142.6 186.1 215.3 157.0 209.1 225.9 17.84 19.27 18.69 18.22 19.42 18.92 18.53 198.2 243.9 225.2 210.7 248.5 232.6 220.8 192.7 139.9 183.5 210.7 154.2 206.1 220.8 18.47 20.13 19.45 18.93 20.30 19.72 19.29 189.8 232.3 214.5 201.9 236.3 221.6 211.6 185.3 135.8 179.0 201.9 149.9 201.0 211.6 19.99 21.63 20.94 20.46 21.78 21.22 20.83 167.0 203.9 187.4 178.6 206.6 193.9 187.8 165.5 125.5 167.5 178.6 139.4 188.4 187.8 21.88 23.41 22.72 22.36 23.52 23.00 22.74 6,000/0.03 72 256.2 131.8 16.65 246.0 127.9 18.20 240.9 126.0 18.97 234.4 123.5 19.79 223.6 119.4 21.29 196.6 109.1 23.11 67 235.7 166.7 16.14 225.8 162.6 17.70 220.9 160.6 18.38 215.6 158.5 19.10 205.8 154.4 20.61 180.3 144.0 22.43 4. Gross capacities shown do not include a deduction for evaporator-fan motor heat. 5. Formulas tldb = tedb − sensible heat capacity (Btuh) 1.1 x cfm tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb) hlwb = hewb − total capacity (Btuh) 4.5 cfm where hewb = enthalpy of air entering evaporator coil 6. Combination ratings are based on a 2° F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table on page 40 are based on 2° F line loss. COMBINATION RATINGS — ENGLISH (cont) 38AH028 AND 40RM028 Temp (F) Air Entering Condenser 85 95 100 105 115 115 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 38AH034 AND 40RM028 Evaporator Air — Cfm/BF 7,500/0.04 10,000/0.06 12,500/0.08 Evaporator Air — Ewb (F) 72 67 62 72 67 62 72 67 62 275.2 252.7 234.7 285.3 262.8 249.2 290.6 271.7 261.4 148.5 191.1 231.2 168.8 222.6 249.2 188.5 250.9 261.4 17.13 16.57 16.12 17.38 16.82 16.48 17.52 17.04 16.78 264.5 241.8 225.1 274.3 251.6 239.7 279.2 260.6 251.9 144.5 186.7 222.4 164.9 218.0 239.7 184.7 246.1 251.9 18.66 18.09 17.68 18.91 18.34 18.04 19.03 18.56 18.35 259.1 236.3 220.3 268.7 246.0 235.0 273.5 255.0 247.2 142.6 184.5 218.0 163.0 215.7 235.0 182.8 243.6 247.2 19.50 18.83 18.37 19.78 19.12 18.79 19.92 19.38 19.15 251.2 229.6 215.2 260.0 238.6 229.2 264.3 247.1 240.8 139.7 181.8 213.4 159.9 212.7 229.2 179.8 240.2 240.8 20.40 19.61 19.09 20.72 19.94 19.60 20.87 20.25 20.02 239.3 218.3 205.6 247.4 226.7 219.2 251.1 234.9 230.4 135.3 177.2 204.6 155.5 207.8 219.2 175.4 234.8 230.4 21.89 21.09 20.60 22.21 21.41 21.12 22.35 21.73 21.55 210.1 189.8 180.9 217.0 197.1 194.0 219.6 205.1 204.6 124.6 165.7 181.9 144.8 195.7 194.0 164.9 221.8 204.6 23.67 22.82 22.45 23.96 23.13 23.00 24.07 23.46 23.44 38AH028 AND 40RM034 Temp (F) Air Entering Condenser 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW LEGEND BF — Bypass Factor Edb — Entering Dry Bulb Ewb — Entering Wet-Bulb kW — Compressor Motor Power Input Ldb — Leaving Dry Bulb Lwb — Leaving Wet Bulb SHC — Sensible Heating Capacity (1000 Btuh) TC — Total Capacity (1000 Btuh) NOTES: 1. All combination ratings are based on refrigerant R-22. 2. Direct interpolation is permissible. Do not extrapolate. 3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator coil. Below 80 F dry-bulb, subtract (correction factor × cfm) from SHC. Above 80 F dry bulb, add (correction factor × cfm) to SHC. 79 81 0.10 0.20 0.30 0.99 0.88 0.77 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — Cfm/BF 10,000/0.06 12,500/0.08 Evaporator Air — Ewb (F) 62 72 67 62 72 67 62 258.8 320.5 295.3 274.6 327.8 305.2 288.2 253.3 181.2 236.0 274.6 200.9 265.5 288.2 19.32 20.81 20.20 19.70 20.99 20.44 20.03 249.2 307.9 283.1 264.9 314.6 292.9 278.2 244.5 176.8 231.0 264.9 196.5 260.2 278.2 21.06 22.95 22.15 21.57 23.17 22.47 22.00 244.4 301.0 276.7 259.9 307.3 286.3 272.9 240.2 174.3 228.3 259.9 194.1 257.3 272.9 21.88 23.77 22.96 22.40 23.98 23.28 22.83 239.3 295.0 270.6 254.8 301.0 280.3 267.8 235.4 172.2 225.8 254.8 192.0 254.6 267.8 22.77 24.83 23.93 23.34 25.05 24.28 23.82 229.4 281.4 257.8 244.5 286.8 267.2 257.2 226.4 167.5 220.6 244.5 187.3 248.9 257.2 24.52 26.77 25.75 25.18 27.00 26.15 25.72 219.0 267.5 244.6 233.7 272.3 253.7 246.0 216.8 162.6 215.2 233.7 182.4 243.1 246.0 26.36 28.76 27.63 27.09 29.00 28.08 27.70 7,500/0.04 72 307.8 160.5 20.50 295.9 156.1 22.57 289.5 153.7 23.38 283.7 151.6 24.41 271.0 146.9 26.32 257.9 142.1 28.29 67 283.0 203.4 19.90 271.4 198.7 21.78 265.4 196.3 22.58 259.5 193.9 23.52 247.4 189.0 25.30 234.9 184.0 27.15 38AH034 AND 40RM034 Evaporator Air — Cfm/BF 9,000/0.04 12,000/0.06 15,000/0.08 Evaporator Air — Ewb (F) 72 67 62 72 67 62 72 67 62 291.7 266.7 251.6 300.7 276.9 267.5 305.2 286.3 280.5 162.4 214.9 249.7 189.9 251.2 267.5 211.7 283.4 280.5 17.54 16.92 16.54 17.77 17.17 16.94 17.88 17.41 17.26 280.4 255.1 241.3 289.1 265.1 257.4 293.2 274.5 270.3 158.1 210.3 240.4 186.0 246.5 257.4 207.7 274.5 270.3 19.06 18.43 18.08 19.28 18.68 18.48 19.38 18.91 18.81 274.7 249.3 236.2 283.2 259.2 252.3 287.2 268.7 265.2 156.0 208.0 235.8 184.0 244.1 252.3 205.7 268.7 265.2 19.95 19.21 18.83 20.20 19.50 19.30 20.32 19.78 19.68 265.5 241.5 229.9 273.2 250.6 245.1 276.7 259.5 257.4 152.5 204.9 230.1 180.6 240.6 245.1 202.2 259.5 257.4 20.92 20.04 19.62 21.20 20.38 20.18 21.32 20.70 20.62 252.4 229.1 219.2 259.4 237.6 234.0 262.4 246.2 245.8 147.5 200.0 220.4 175.9 235.4 234.0 197.5 246.2 245.8 22.40 21.50 21.12 22.67 21.83 21.69 22.78 22.16 22.14 221.1 198.5 192.2 226.8 206.2 206.4 228.9 214.4 217.6 135.6 187.9 195.9 164.9 206.2 206.4 186.3 214.4 217.6 24.13 23.19 22.92 24.37 23.51 23.52 24.45 23.85 23.98 BYPASS FACTOR Temp (F) Air Entering Condenser Temp (F) Air Entering Condenser 85 95 100 105 115 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW Evaporator Air — Cfm/BF 12,000/0.06 15,000/0.08 Evaporator Air — Ewb (F) 62 72 67 62 72 67 62 279.6 340.3 313.3 297.3 346.7 324.0 311.8 275.2 203.3 265.9 297.3 225.6 300.0 311.8 19.82 21.29 20.64 20.25 21.44 20.89 20.60 268.9 326.5 300.0 286.3 332.2 310.4 300.5 265.4 198.6 260.5 286.3 220.7 294.0 300.5 21.70 23.55 22.70 22.26 23.73 23.03 22.71 263.3 318.6 292.8 280.4 324.0 303.0 294.4 260.4 196.0 257.6 280.4 218.0 290.8 294.0 22.51 24.35 23.49 23.08 24.53 23.83 23.55 257.8 312.3 286.4 275.0 317.5 296.6 288.9 255.4 193.9 255.0 275.0 215.8 287.9 288.9 23.45 25.47 24.51 24.09 25.66 24.89 24.60 246.6 297.3 272.3 263.2 301.8 282.1 276.7 245.2 188.8 249.4 263.2 210.6 281.6 276.7 25.26 27.45 26.37 25.98 27.65 26.80 26.56 234.8 282.0 257.8 251.1 — 267.4 264.1 234.6 183.6 243.5 251.1 — 267.4 264.1 27.14 29.48 28.28 27.95 — 28.76 28.59 9,000/0.04 72 328.6 176.4 21.00 315.5 171.4 23.19 308.2 168.7 24.01 302.1 166.3 25.09 287.9 161.0 27.05 273.5 155.5 29.06 67 301.1 228.6 20.34 288.3 223.5 22.32 281.5 220.8 23.12 275.2 218.3 24.10 261.8 213.0 25.92 247.9 207.5 27.79 4. Gross capacities shown do not include a deduction for evaporator-fan motor heat. 5. Formulas tldb = tedb − sensible heat capacity (Btuh) 1.1 x cfm tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb) hlwb = hewb − total capacity (Btuh) 4.5 cfm where hewb = enthalpy of air entering evaporator coil 6. Combination ratings are based on a 2° F line loss. For a close-coupled system (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table on page 40 are based on 2° F line loss. ENTERING-AIR DRY-BULB TEMP (F) 78 77 76 75 under 75 82 83 84 85 over 85 Correction Factor 1.98 2.97 3.96 4.95 Use formula 1.76 2.64 3.52 4.40 shown below. 1.54 2.31 3.08 3.85 Interpolation is permissible. Correction Factor = 1.1 x (1 − BF) x (db − 80). 25 Performance data — 38AH024-034/40RM (cont) 40RM COIL ACCESSORY HEATING CAPACITIES — SI UNIT AIRFLOW 40RM (L/s) 2100 2800 3500 2900 3800 4700 3500 4700 5900 4250 5650 7050 016 024 028 034 1-ROW STEAM* 2-ROW HOT WATER COIL† Water PD Cap. (kW) Ldb Cap. (kW) Ldb Flow (kPa) (L/s) 117 61 120 62 2.6 13.3 129 53 137 55 3.0 16.2 140 48 154 51 3.3 19.5 135 53 150 58 3.3 15.6 140 46 170 52 3.7 18.6 146 41 191 49 4.1 22.3 149 50 189 60 4.1 16.9 166 44 218 53 4.7 20.8 183 41 247 50 5.4 25.4 164 47 215 57 4.7 18.5 180 41 247 51 5.4 22.8 196 38 278 48 6.0 27.7 LEGEND Cap. — Capacity (kW) Ldb — Leaving-Air Dry-Bulb Temp (C) PD — Pressure Drop (kPa) *Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam coils are non-freeze type. †Based on 93.3 C entering-water temperature, 11.1 C water temperature drop, 15.6 C entering-air temperature. NOTES: 1. Maximum operating limit for heating coils: 1207 kPag at 204.4 C. Capacity (kW) 2. Leaving db = ent db (C) + 1.23 x 10-3 x L/s 3. See Heating Correction Factors table. 5 11 16 HOT Ent Water Temp (C) 60 70 80 90 100 60 70 80 90 100 60 70 80 90 100 Steam Pressure (kPag) 0 14 35 AIRFLOW (Cfm) 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 9,000 12,000 15,000 016 024 028 034 Entering-Air Temp (C) 4 10 16 20 25 0.72 0.87 1.02 1.17 1.32 0.65 0.80 0.95 1.10 1.26 0.56 0.72 0.87 1.02 1.18 0.64 0.79 0.94 1.09 1.24 0.56 0.72 0.87 1.02 1.18 0.48 0.63 0.79 0.94 1.10 0.55 0.71 0.86 1.01 1.16 0.48 0.63 0.79 0.94 1.09 0.39 0.55 0.70 0.86 1.02 0.50 0.65 0.80 0.95 1.10 0.42 0.58 0.73 0.89 1.04 0.33 0.49 0.65 0.81 0.97 0.43 0.58 0.73 0.89 1.04 0.35 0.51 0.66 0.82 0.97 0.26 0.42 0.58 0.74 0.90 STEAM COIL Entering-Air Temp (C) 4 10 16 20 1.07 0.99 0.91 0.86 1.10 1.02 0.95 0.90 1.14 1.07 0.99 0.95 1-ROW STEAM* Cap. Ldb 402 141 458 129 479 118 458 129 487 115 499 105 511 122 575 112 626 106 560 117 621 107 670 101 2-ROW HOT WATER COIL† Cap. Ldb Gpm PD 412.0 145 41.2 4.5 471.0 133 47.1 5.5 529.0 125 52.9 6.6 506.0 138 50.6 5.1 584.0 128 58.4 6.3 652.0 120 65.2 7.5 649.0 140 64.9 5.7 752.0 130 75.2 7.1 842.0 122 84.2 8.5 735.0 136 73.5 6.2 850.0 126 85.0 7.8 950.0 119 95.0 9.3 LEGEND Cap. — Capacity (Btuh in thousands) Ldb — Leaving-Air Dry-Bulb Temp (F) PD — Pressure Drop (ft water) *Based on 5 psig steam, 60 F entering-air temperature. All steam coils are non-freeze type. †Based on 200 F entering water, 20 F water temperature drop, 60 F entering-air temperature. NOTES: 1. Maximum operating limit for heating coils: 175 psig at 400 F. Capacity (Btuh) 2. Leaving db = ent db (F) + 1.1 x cfm 3. See Heating Correction Factors table. WATER COIL 25 0.80 0.84 0.89 NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table. 26 UNIT 40RM 40RM HEATING CORRECTION FACTORS — ENGLISH 40RM HEATING CORRECTION FACTORS — SI Water Temp Drop (C) 40RM COIL ACCESSORY HEATING CAPACITIES — ENGLISH Water Temp Drop (F) 10 20 30 HOT Ent Water Temp (F) 140 160 180 200 220 140 160 180 200 220 140 160 180 200 220 Steam Pressure (psig) 0 2 5 WATER COIL Entering-Air Temp (F) 40 50 60 70 80 0.72 0.89 1.06 1.22 1.39 0.64 0.81 0.98 1.15 1.32 0.56 0.74 0.91 1.08 1.25 0.64 0.81 0.98 1.15 1.32 0.57 0.74 0.91 1.08 1.25 0.49 0.66 0.83 1.00 1.18 0.57 0.74 0.90 1.07 1.24 0.49 0.66 0.83 1.00 1.17 0.41 0.58 0.76 0.93 1.10 0.49 0.66 0.83 1.00 1.17 0.41 0.58 0.75 0.93 1.10 0.33 0.51 0.68 0.85 1.03 0.41 0.58 0.75 0.92 1.09 0.33 0.51 0.68 0.85 1.02 0.24 0.43 0.60 0.78 0.95 STEAM COIL Entering-Air Temp (F) 40 50 60 70 1.06 0.98 0.91 0.85 1.09 1.02 0.95 0.89 1.13 1.06 1.00 0.93 80 0.78 0.82 0.87 NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capacities table. 40RM FAN PERFORMANCE DATA — 0-300 Pa ESP — SI UNIT 40RM 016 024 028 034 AIRFLOW (L/s) 0 50 2100 r/s 6.43 kW 0.37 r/s 8.19 kW 0.55 2450 7.51 0.57 9.06 0.77 EXTERNAL STATIC PRESSURE (Pa) 100 150 200 r/s kW r/s kW r/s kW 9.65 0.73 10.90 0.92 12.10 1.11 10.40 0.97 250 r/s kW 13.10 1.30 300 r/s kW 14.10 1.50 11.60 1.18 12.70 1.39 13.70 1.60 14.60 1.81 2800 8.58 0.82 9.96 1.05 11.20 1.27 12.30 1.49 13.30 1.72 14.30 1.95 15.10 2.18 3150 9.65 1.14 10.90 1.38 12.00 1.63 13.10 1.87 14.00 2.12 14.90 2.36 15.80 2.61 3500 10.70 1.52 11.90 1.78 12.90 2.05 13.90 2.31 14.80 2.58 15.60 2.84 16.40 3.11 2900 8.58 0.86 9.96 1.09 11.20 1.32 12.30 1.55 13.30 1.78 14.20 2.01 15.10 2.25 3350 9.91 1.28 11.10 1.53 12.20 1.79 13.20 2.04 14.20 2.30 15.10 2.55 15.90 2.81 3800 11.30 1.81 12.30 2.09 13.30 2.37 14.30 2.64 15.10 2.93 16.00 3.21 16.80 3.49 4250 12.60 2.46 13.60 2.76 14.50 3.07 15.30 3.37 16.10 3.67 16.90 3.98 17.70 4.28 4700 13.90 3.24 14.80 3.57 15.60 3.90 16.40 4.22 17.20 4.55 17.90 4.88 18.60 5.21 3500 6.79 0.84 8.14 1.12 9.42 1.47 10.70 1.89 11.80 2.39 12.90 2.96 14.00 3.61 4100 7.95 1.29 9.12 1.60 10.20 1.96 11.30 2.38 12.40 2.86 13.40 3.40 14.30 4.00 4700 9.12 1.88 10.10 2.21 11.10 2.59 12.10 3.02 13.00 3.49 13.90 4.02 14.80 4.60 5300 10.30 2.62 11.20 3.00 12.10 3.37 12.90 3.81 13.80 4.29 14.60 4.82 15.40 5.38 5900 11.40 3.52 12.30 3.90 13.10 4.32 13.90 4.77 14.60 5.26 15.40 5.79 16.10 6.35 4250 7.86 1.33 8.99 1.63 10.10 1.97 11.10 2.37 12.20 2.83 13.20 3.34 14.10 3.92 4950 9.15 2.03 10.10 2.35 11.10 2.72 12.00 3.12 12.90 3.58 13.80 4.08 14.70 4.62 5650 10.40 2.92 11.30 3.27 12.20 3.66 13.00 4.08 13.80 4.54 14.60 5.04 15.40 5.57 6350 11.70 4.02 12.50 4.40 13.30 4.81 14.00 5.25 14.70 5.72 15.50 6.23 16.20 6.77 7050 13.00 5.37 13.70 5.77 14.40 6.21 15.10 6.66 15.70 7.15 16.40 7.67 17.10 8.21 40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — SI LEGEND ESP — External Static Pressure Bold indicates field-supplied drive required. Plain type indicates standard motor and standard drive. Underline indicates a different motor and drive combination is required. Refer to fan motor and drive tables, pages 41-43, to complete the selection. NOTES: 1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 034; 20 r/s for all other sizes. 2. Fan performance is based on deductions for wet coil, clean 51-mm filters, and unit casing. See right for factory-supplied filter pressure drop. 3. The standard motor and medium-static drive combination is not available for 40RM016-028 units. Use the alternate motor if the mediumstatic drive is required for these sizes. UNIT 40RM 016 024 028 034 AIRFLOW (L/s) 2100 2800 3500 2900 3800 4700 3500 4700 5900 4250 5650 7050 PRESSURE DROP (Pa) 20 30 42 32 47 64 36 55 76 47 71 98 27 Performance data — 38AH024-034/40RM (cont) 40RM FAN PERFORMANCE DATA — 350-600 Pa ESP — SI UNIT 40RM 016 024 028 034 AIRFLOW (L/s) 350 400 EXTERNAL STATIC PRESSURE (Pa) 450 500 550 r/s kW r/s kW r/s kW 16.70 2.11 17.40 2.32 18.20 2.53 2100 r/s 15.00 kW 1.70 r/s 15.80 kW 1.90 2450 15.50 2.03 16.30 2.25 17.10 2800 16.00 2.42 16.80 2.66 17.60 2.90 3150 16.60 2.87 17.40 3.12 18.10 3.38 3500 17.20 3.38 18.00 3.65 18.70 3.93 2900 16.00 2.49 16.80 2.73 17.50 3350 16.70 3.08 17.50 3.34 3800 17.50 3.77 18.20 4.06 18.60 2.93 19.30 3.16 18.30 3.14 19.00 3.38 19.70 3.63 18.80 3.64 19.50 3.90 — — 19.40 4.20 — — — — 2.97 18.30 3.22 19.00 3.47 19.70 18.20 3.61 18.90 3.87 19.60 4.14 — — 18.90 4.35 19.60 4.64 — — — — 3.72 4250 18.40 4.59 19.10 4.90 19.80 5.21 — — — — — — 4700 19.30 5.54 20.00 5.87 — — — — — — — — 3500 15.10 4.33 16.10 5.12 17.10 5.98 18.00 6.92 — — — — 4100 15.30 4.67 16.20 5.39 17.10 6.18 18.00 7.02 — — — — 4700 15.70 5.23 16.50 5.91 17.40 6.64 18.20 7.43 — — — — 5300 16.20 5.99 17.00 6.65 17.80 7.35 — — — — — — 5900 16.90 6.95 17.60 7.59 18.30 8.27 — — — — — — 4250 15.00 4.55 16.00 5.24 16.80 5.99 17.70 6.79 — — — — 4950 15.50 5.22 16.30 5.86 17.10 6.56 17.90 7.30 — — — — 5650 16.10 6.16 16.90 6.77 17.60 7.43 18.30 8.13 — — — — 6350 16.90 7.34 17.50 7.94 18.20 8.58 — — — — — — 7050 17.70 8.79 18.30 9.39 — — — — — — — — 40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — SI LEGEND ESP — External Static Pressure Bold indicates field-supplied drive required. Plain type indicates standard motor and standard drive. Underline indicates a different motor and drive combination is required. Refer to fan motor and drive tables, pages 41-43, to complete the selection. NOTES: 1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 034; 20 r/s for all other sizes. 2. Fan performance is based on deductions for wet coil, clean 51-mm filters, and unit casing. See right for factory-supplied filter pressure drop. 3. The standard motor and medium-static drive combination is not available for 40RM016-028 units. Use the alternate motor if the mediumstatic drive is required for these sizes. 28 kW 2.74 2.70 2.47 17.80 600 r/s 18.90 UNIT 40RM 016 024 028 034 AIRFLOW (L/s) 2100 2800 3500 2900 3800 4700 3500 4700 5900 4250 5650 7050 PRESSURE DROP (Pa) 20 30 42 32 47 64 36 55 76 47 71 98 40RM FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — ENGLISH UNIT 40RM 016 024 028 034 4,500 Rpm 391 Bhp 0.51 Rpm 495 Bhp 0.75 EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 Rpm Bhp Rpm Bhp Rpm Bhp 581 1.00 657 1.25 725 1.50 5,300 460 0.80 551 1.08 629 1.35 700 1.63 764 AIRFLOW (Cfm) 0.0 0.2 1.0 1.2 Rpm 787 Bhp 1.76 Rpm 845 Bhp 2.02 1.91 823 2.20 878 2.48 6,000 521 1.13 602 1.43 675 1.73 741 2.04 801 2.34 858 2.65 911 2.96 6,800 590 1.60 663 1.93 730 2.26 791 2.59 847 2.92 901 3.26 951 3.60 7,500 651 2.10 718 2.45 779 2.81 837 3.16 890 3.52 941 3.88 990 4.24 6,000 503 1.07 587 1.37 661 1.67 727 1.97 789 2.28 846 2.59 900 2.90 7,000 586 1.64 660 1.98 726 2.31 787 2.65 844 2.99 898 3.33 948 3.67 8,000 670 2.37 735 2.74 795 3.12 851 3.49 904 3.86 954 4.23 1001 4.61 9,000 754 3.28 812 3.69 867 4.09 918 4.50 967 4.90 1014 5.31 1059 5.72 10,000 838 4.39 891 4.83 941 5.27 988 5.70 1034 6.14 1077 6.85 1120 7.02 7,500 412 1.15 492 1.53 568 2.00 640 2.56 710 3.22 776 3.98 840 4.83 8,750 481 1.76 550 2.17 616 2.66 680 3.22 742 3.86 802 4.58 860 5.38 10,000 549 2.55 610 2.99 669 3.50 726 4.07 782 4.70 836 5.40 889 6.17 11,250 618 3.52 672 4.00 725 4.53 777 5.12 827 5.76 876 6.45 925 7.21 12,500 687 4.71 735 5.22 783 5.78 830 6.38 876 7.04 922 7.74 966 8.49 9,000 471 1.78 539 2.17 604 2.63 667 3.17 728 3.78 788 4.46 845 5.22 10,500 550 2.72 608 3.15 665 3.64 720 4.18 774 4.79 827 5.45 878 6.18 12,000 628 3.93 679 4.40 730 4.92 779 5.48 827 6.09 874 6.76 921 7.47 13,500 707 5.44 752 5.94 797 6.49 841 7.08 885 7.71 928 8.38 970 9.10 15,000 785 7.27 826 7.81 867 8.39 907 9.01 947 9.66 986 10.35 1024 11.07 40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — ENGLISH LEGEND ESP — External Static Pressure Bold indicates field-supplied drive required. Plain type indicates standard motor and standard drive. Underline indicates a different motor and drive combination is required. Refer to fan motor and drive tables, pages 41-43, to complete the selection. NOTES: 1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 034; 1200 rpm for all other sizes. 2. Fan performance is based on deductions for wet coil, clean 2-in. filters, and unit casing. See right for factory-supplied filter pressure drop. 3. The standard motor and medium-static drive combination is not available for 40RM016-028 units. Use the alternate motor if the mediumstatic drive is required for these sizes. UNIT 40RM 016 024 028 034 AIRFLOW (Cfm) 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 9,000 12,000 15,000 PRESSURE DROP (in. wg) 0.08 0.12 0.17 0.12 0.19 0.26 0.15 0.22 0.30 0.19 0.29 0.40 29 Performance data — 38AH024-034/40RM (cont) FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — ENGLISH UNIT 40RM 016 024 028 034 AIRFLOW (Cfm) 1.4 1.6 4,500 Rpm 899 Bhp 2.29 Rpm 951 5,300 930 2.78 980 6,000 961 3.28 6,800 999 3.94 7,500 1036 6,000 EXTERNAL STATIC PRESSURE (in. wg) 1.8 2.0 Bhp Rpm Bhp Rpm Bhp 2.56 999 2.84 1046 3.12 2.4 Bhp 3.41 Rpm 1133 Bhp 3.70 3.08 1027 3.38 1072 3.68 1116 3.99 1157 4.30 1009 3.60 1055 3.92 1098 4.24 1141 4.57 1181 4.91 1045 4.28 1089 4.63 1132 4.98 1173 5.33 — — 4.60 1080 4.97 1123 5.34 1164 5.71 — — — — 950 3.21 999 3.53 1045 3.85 1089 4.17 1131 4.50 1172 4.83 7,000 996 4.02 1042 4.37 1086 4.72 1129 5.07 1169 5.43 — — 8,000 1047 4.99 1091 5.37 1133 5.75 1173 6.13 — — — — 9,000 1102 6.13 1143 6.54 1183 6.96 — — — — — — 10,000 1160 7.46 1200 7.91 — — — — — — — — 7,500 903 5.79 963 6.83 1021 7.98 1078 9.21 — — — — 8,750 917 6.26 972 7.22 1025 8.26 1078 9.38 — — — — 10,000 941 7.01 991 7.91 1040 8.89 1089 9.93 — — — — 11,250 972 8.02 1019 8.89 1064 9.83 — — — — — — 12,500 1010 9.29 1053 10.15 1095 11.05 — — — — — — 9,000 901 6.07 955 6.98 1008 7.98 1060 9.05 — — — — 10,500 928 6.98 978 7.84 1026 8.76 1073 9.74 — — — — 12,000 966 8.24 1011 9.07 1055 9.95 1098 10.88 — — — — 13,500 1011 9.86 1052 10.67 1092 11.52 — — — — — — 15,000 1062 11.84 — — — — — — — — — — LEGEND ESP — External Static Pressure 40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — ENGLISH Bold indicates field-supplied drive required. Plain type indicates standard motor and standard drive. Underline indicates a different motor and drive combination is required. UNIT 40RM Refer to fan motor and drive tables, pages 41-43, to complete the selection. 016 NOTES: 1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 034; 1200 rpm for all other sizes. 2. Fan performance is based on deductions for wet coil, clean 2-in. filters, and unit casing. See right for factory-supplied filter pressure drop. 3. The standard motor and medium-static drive combination is not available for 40RM016-028 units. Use the alternate motor if the mediumstatic drive is required for these sizes. 30 2.2 Rpm 1091 024 028 034 AIRFLOW (Cfm) 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 9,000 12,000 15,000 PRESSURE DROP (in. wg) 0.08 0.12 0.17 0.12 0.19 0.26 0.15 0.22 0.30 0.19 0.29 0.40 40RM PLENUM ACCESSORY AIR THROW DATA — SI (m) UNIT 40RM AIRFLOW (L/s) 016 024 028 034 2800 3800 4700 5650 VANE DEFLECTION Straight 221⁄2° 45° 15.41 13.25 9.55 18.17 15.44 11.20 23.26 19.89 14.38 25.97 22.00 15.89 NOTE: Throw distances shown are for 0.381 m/sec terminal velocity. Use the following multipliers to determine throw values for other terminal velocities. TERMINAL VELOCITY (m/sec) 0.254 0.508 0.762 UNIT 40RM AIRFLOW (Cfm) 016 024 028 034 6,000 8,000 10,000 12,000 VANE DEFLECTION Straight 221⁄2° 45° 50 43 31 60 51 37 76 65 47 85 72 52 NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities. TERMINAL VELOCITY (Fpm) 50 100 150 THROW FACTOR X X X 40RM PLENUM ACCESSORY AIR THROW DATA — ENGLISH (Ft) 1.50 0.75 0.50 THROW FACTOR X X X 1.50 0.75 0.50 40RM ACCESSORY PRESSURE DROP — SI (Pa) UNIT 40RM 016 024 028 034 AIRFLOW (L/s) DISCHARGE PLENUM RETURN AIR GRILLE 2100 2800 3500 2900 3800 4700 3500 4700 5900 4250 5650 7050 24 39 56 41 64 91 37 59 86 50 80 114 2 5 7 5 10 15 5 7 12 7 12 17 Hot Water 36 57 82 60 93 132 67 109 157 92 147 210 HEATING COILS Steam 36 57 82 60 93 132 67 109 157 92 147 210 Electric 14 24 37 26 43 65 22 39 60 32 56 85 ECONOMIZER 15 22 37 23 43 69 15 22 35 20 35 52 40RM ACCESSORY PRESSURE DROP — ENGLISH (in. wg) UNIT 40RM 016 024 028 034 AIRFLOW (Cfm) DISCHARGE PLENUM RETURN AIR GRILLE 4,500 6,000 7,500 6,000 8,000 10,000 7,500 10,000 12,500 9,000 12,000 15,000 0.10 0.16 0.23 0.16 0.26 0.37 0.15 0.24 0.34 0.20 0.32 0.46 0.01 0.02 0.03 0.02 0.04 0.06 0.02 0.03 0.05 0.03 0.05 0.07 Hot Water 0.15 0.23 0.33 0.23 0.37 0.53 0.28 0.44 0.63 0.37 0.59 0.85 HEATING COILS Steam 0.15 0.23 0.33 0.23 0.37 0.53 0.28 0.44 0.63 0.37 0.59 0.85 Electric 0.06 0.10 0.15 0.10 0.17 0.26 0.09 0.16 0.24 0.13 0.22 0.34 ECONOMIZER 0.06 0.09 0.15 0.09 0.17 0.28 0.06 0.09 0.14 0.08 0.14 0.21 31 Typical piping and wiring — 38AH024-034 ROOFTOP INSTALLATION LEGEND TXV — Thermostatic Expansion Valve Piping Double Riser Piping (If Required) *Field supplied. †If double suction riser is required for piping system, size pipe diameter of 3 ft (maximum) riser according to application data on page 40. 32 NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor. 5. Internal factory-supplied TXVs not shown. GROUND LEVEL INSTALLATION LEGEND TXV — Thermostatic Expansion Valve Piping *Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor. 33 Electrical data — 38AH024-034/40RM 38AH024-034 UNIT 38AH VOLTAGE DESIGNATION NAMEPLATE VOLTAGE (3 Ph, 50 Hz) 803 903 303 803 903 303 803 903 303 230 400 346 230 400 346 230 400 346 024 028 034 SUPPLY VOLTAGE* POWER SUPPLY COMPRESSOR Min Max MCA MOCP ICF 198 342 311 198 342 311 198 342 311 254 400 380 254 400 380 254 400 380 101.2 46.5 62.8 110.9 55.7 68.2 135.9 65.1 78.1 125 60 80 150 70 90 175 90 110 268.8 204.0 194.8 298.8 234.0 216.8 355.8 240.0 257.8 RLA Ckt 1 Ckt 2 39.3 39.3 18.0 18.0 24.0 24.0 43.6 43.6 22.1 22.1 26.4 26.4 43.6 63.6 22.1 30.0 26.4 34.3 LRA Ckt 1 Ckt 2 128 128 99 99 93 93 143 143 114 114 104 104 143 200 114 120 104 145 FAN MOTORS† QTY 2 2 2 2 2 2 2 2 2 FLA (ea) 6.4 3.0 4.4 6.4 3.0 4.4 6.4 3.0 4.4 Nominal Hp Nominal kW 1 0.75 1 0.75 1 0.75 *Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed minimum and maximum. †All fans are protected by a single circuit breaker. LEGEND — Full Load Amps — Maximum Instantaneous Current Flow During Starting. (The point in the starting sequence where the sum of the LRA for the starting compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is maximum.) LRA — Locked Rotor Amps MCA — Minimum Circuit Amps (complies with National Electrical Code [NEC] Section 430-24) (U.S.A. Standard) MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps FLA ICF 40RM STANDARD MOTORS FAN MOTOR UNIT 40RM 016 024 028 034 V*-PH-HZ VOLTAGE LIMITS 230-3-50 400-3-50 230-3-50 400-3-60 230-3-50 400-3-50 230-3-50 400-3-50 207-253 360-440 207-253 360-440 207-253 360-440 207-253 360-440 LEGEND FLA — Full Load Amps MOCP — Maximum Overcurrent Protection *Motors are designed for satisfactory operation within 10% of nominal voltages shown. Voltages should not exceed the limits shown in the Voltage Limits column. NOTES: 1. Minimum circuit amp and MOCP values are calculated in accordance with NEC (National Electrical Code) (U.S.A. standard), Article 440. 2. Motor FLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 1995 (U.S.A. standard). 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage EXAMPLE: Supply voltage is 400-3-50. AB = 393 v BC = 403 v AC = 396 v 393 + 403 + 396 Average Voltage = 3 1192 = 3 = 397 34 kW (Hp) 2.16 2.16 3.73 3.73 5.59 5.59 7.46 7.46 POWER SUPPLY Minimum Circuit MOCP Amps 9.4 15 4.3 15 19.0 30 9.5 15 28.5 50 14.3 25 40.3 70 20.1 30 FLA (2.9) (2.9) (5.0) (5.0) (7.5) (7.5) (10.0) (10.0) 7.5 3.4 15.2 7.6 22.8 11.4 32.2 16.1 Determine maximum deviation from average voltage. (AB) 397 − 393 = 4 v (BC) 403 − 397 = 6 v (AC) 397 − 396 = 1 v Maximum deviation is 6 v. Determine percent voltage imbalance. 6 % Voltage Imbalance = 100 x 397 = 1.5% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 40RM ALTERNATE MOTORS FAN MOTOR UNIT 40RM 016 024 028 V*-PH-HZ VOLTAGE LIMITS 230-3-50 400-3-50 230-3-50 400-3-50 230-3-50 400-3-50 207-253 360-440 207-253 360-440 207-253 360-440 LEGEND FLA — Full Load Amps MOCP — Maximum Overcurrent Protection *Motors are designed for satisfactory operation within 10% of nominal voltages shown. Voltages should not exceed the limits shown in the Voltage Limits column. NOTES: 1. Minimum circuit amp and MOCP values are calculated in accordance with NEC (National Electrical Code) (U.S.A. standard), Article 440. 2. Motor FLA values are established in accordance with UL (Underwriters’ Laboratories) Standard 1995 (U.S.A. standard). 3. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance max voltage deviation from average voltage = 100 x average voltage EXAMPLE: Supply voltage is 400-3-50. AB = 393 v BC = 403 v AC = 396 v 393 + 403 + 396 Average Voltage = 3 1192 = 3 = 397 kW (Hp) 3.73 3.73 5.59 5.59 7.46 7.46 FLA (5.0) (5.0) (7.5) (7.5) (10.0) (10.0) 15.2 7.6 22.8 11.4 32.2 16.1 POWER SUPPLY Minimum Circuit MOCP Amps 19.0 30 9.5 15 28.5 50 14.3 25 40.3 60 20.1 30 Determine maximum deviation from average voltage. (AB) 397 − 393 = 4 v (BC) 403 − 397 = 6 v (AC) 397 − 396 = 1 v Maximum deviation is 6 v. Determine percent voltage imbalance. 6 % Voltage Imbalance = 100 x 397 = 1.5% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 40RM FAN CONTACTOR COIL UNIT 40RM 016-034 VOLTAGE (vac) 24 MAXIMUM HOLDING VA 10 35 Electrical data — 38AH024-034/40RM (cont) 40RM ELECTRIC HEATER ACCESSORY DATA UNIT 40RM HEATER PART NO. V-PH-Hz CAELHEAT016A00 240-3-50 CAELHEAT017A00 400-3-50 CAELHEAT019A00 240-3-50 CAELHEAT020A00 400-3-50 CAELHEAT022A00 240-3-50 CAELHEAT023A00 400-3-50 CAELHEAT025A00 240-3-50 CAELHEAT026A00 400-3-50 CAELHEAT028A00 240-3-50 CAELHEAT029A00 400-3-50 CAELHEAT031A00 240-3-50 CAELHEAT032A00 400-3-50 CAELHEAT034A00 240-3-50 CAELHEAT035A00 400-3-50 CAELHEAT037A00 240-3-50 CAELHEAT038A00 400-3-50 016,024 028,034 ELECTRIC HEATERS(S) FAN MOTOR Hp kW FLA 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 2.9 5.0 7.5 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 7.5 10.0 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 2.16 3.73 5.59 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 5.59 7.46 7.5 15.2 22.8 3.4 7.6 11.4 7.5 15.2 22.8 3.4 7.6 11.4 7.5 15.2 22.8 3.4 7.6 11.4 7.5 15.2 22.8 3.4 7.6 11.4 22.8 32.2 11.4 16.1 22.8 32.2 11.4 16.1 22.8 32.2 11.4 16.1 22.8 32.2 11.4 16.1 Nominal Capacity (kW) 10 10 10 10 10 10 20 20 20 20 20 20 30 30 30 30 30 30 50 50 50 50 50 50 20 20 20 20 40 40 40 40 50 50 50 50 70 70 70 70 LEGEND FLA — Full Load Amps Hp — Horsepower MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (Amps) *Values shown are for single-point connection of electric heat accessory and air handler. †Single-phase motors. All other motors are 3-phase. HEATER RATING VOLTAGE 240 480 575 36 Actual Capacity (kW) Stage 1 Stage 2 Total 10.0 10.0 10.0 6.9 6.9 6.9 20.0 20.0 20.0 13.9 13.9 13.9 20.0 20.0 20.0 13.9 13.9 13.9 30.0 30.0 30.0 20.8 20.8 20.8 20.0 20.0 13.9 13.9 20.0 20.0 13.9 13.9 30.0 30.0 20.8 20.8 40.0 40.0 27.8 27.8 — — — — — — — — — — — — 10.0 10.0 10.0 6.9 7.9 7.9 20.0 20.0 20.0 13.9 13.9 13.9 — — — — 20.0 20.0 13.9 13.9 20.0 20.0 13.9 13.9 30.0 30.0 20.8 20.8 10.0 10.0 10.0 6.9 6.9 6.9 20.0 20.0 20.0 13.9 13.9 13.9 30.0 30.0 30.0 20.8 20.8 20.8 50.0 50.0 50.0 34.7 34.7 34.7 20.0 20.0 13.9 13.9 40.0 40.0 27.8 27.8 50.0 50.0 34.7 34.7 70.0 70.0 48.6 48.6 208 230 0.694 — — 0.751 — — 0.918 — — 240 1 — — 24.1 24.1 24.1 10.0 10.0 10.0 48.1 48.1 48.1 20.0 20.0 20.0 72.2 72.2 72.2 30.1 30.1 30.1 120.3 120.3 120.3 50.1 50.1 50.1 48.1 48.1 20.0 20.0 96.2 96.2 40.1 40.1 120.3 120.3 50.1 50.1 168.4 168.4 70.2 70.2 MCA* MOCP* 39.4 49.1 58.6 16.8 22.0 26.8 69.5 79.1 86.4 29.3 45.1 49.2 99.6 109.2 118.7 41.8 47.1 51.8 159.7 169.4 178.9 66.9 72.1 76.9 88.6 100.4 39.3 45.2 148.8 160.5 64.4 70.2 178.9 190.6 76.9 82.8 196.9 208.6 84.4 90.3 40 50 70 20 25 35 70 80 90 30 50 50 100 110 125 50 50 60 175 175 200 70 80 80 90 110 40 50 150 175 70 80 200 200 80 90 200 225 90 100 NOTES: 1. Electrical resistance heaters are rated at 240 v, or 480 v. To determine heater capacity (kW) at unit nameplate multiply the 240-v, or 480-v, capacity (kW) by the factor shown in the table below for the unit voltage. 2. The following equation converts kW of heat energy to Btuh: kW x 3,412 = Btuh. 3. Heater contactor coils are 24 v and require 8 va holding current. 4. Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg. 5. MCA and MOCP values apply to both standard and alternate factorysupplied motors. ACTUAL HEATER VOLTAGE 200 FLA 400 440 460 480 — 0.694 — — 0.84 — — 0.918 — — 1 Controls — 38AH024-034 Operating sequence Within 6 seconds to 5 minutes (depending on timing logic) from a thermostat call for the first stage of cooling, compressor no. 1 and the condenser fans start. The no. 2 fan only starts if the outdoor ambient temperature is above 21.1 C (70 F). The oil pressure switch and the low pressure switch are bypassed for the first 2 minutes. If either the low pressure switch or oil pressure switch remain open after 2 minutes, the unit shuts down and goes into a lockout mode. The evaporator-fan motor starts immediately whenever there is a call for cooling. If a liquid line solenoid valve has been installed (for refrigerant control during the off cycle), then the solenoid valve for compressor no. 1 opens immediately upon a call for cooling. On standard units, compressor no. 1 operates either fully loaded or at one step of unloading, depending on the suction pressure, which is dependent on the evaporator load conditions. As the cooling demand increases, the thermostat calls for the second stage of cooling. Within 6 seconds to 5 minutes (depending on timing logic) from a call for the second stage of cooling, compressor no. 2 starts. The oil switch and low pressure switch for circuit no. 2 are bypassed for the first two minutes. As the cooling load is satisfied, the thermostat stops the call for the second stage of cooling, which in turn deenergizes compressor no. 2, closes the no. 2 liquid line solenoid (if installed) and energizes the compressor no. 2 crankcase heater. If the space temperature continues to decrease, then the thermostat stops the call for the first stage of cooling, which then deenergizes compressor no. 1 and the condenser fans, closes the no. 1 liquid line solenoid valve (if installed), and energizes the compressor no. 1 crankcase heater. The unit controls prevent both compressors from reenergizing within 5 minutes from a previous call for operation. If the unit safeties trip during operation, then the compressor remains locked out from further operation. To reset the lockout mode, the thermostat must be forced to stop calling for cooling by resetting the thermostat setting above the space temperature and then back to the desired set point. NOTE: If the thermostat fan switch is in the auto position, the evaporator fan cycles on and off as the thermostat calls for cooling (or heating). If the switch is in the continuous position, the fan runs when the condensing unit is powered. 37 38 230-3-50 346-3-50 400-3-50 230-1-50 **For a single air handler, LLS valve 1 is to be used on the lower (no. 1) evaporator circuit. The LLS valve 2 is to be used on the upper (no. 2) evaporator circuit. ††Only one indoor-fan contactor is required on single air-handler applications. Use Carrier accessory part no. 40RR900181 for indoor-fan contactor. UNIT (V-Ph-Hz) CONTROL CIRCUIT PROTECTED AT: (V-Ph-Hz) *Use thermostat wiring shown here for single air-handler applications. †CB3 protects control circuit at the following unit voltages: NOTES: 1. CB4 protects TB3 circuit; CB5 protects TB2 circuits. 2. LLS1 and LLS2 are field supplied. 3. TB2 and TB3 are in 24-v circuits. 4. On the 33CSUCE-06 Relay Pack, the outside-air sensor, supply-air sensor, and direct expansion coil sensor are available as options. 38AH024-034 UNITS WITH SINGLE AIR HANDLER CB COM IFC LLS NEC RV TB LEGEND — Circuit Breaker — Common — Indoor-Fan Contactor — Liquid Line Solenoid — National Electrical Code — Reversing Valve — Terminal Block Field Control Wiring Factory Wiring Field Power Wiring Indicates Common Potential; Does Not Indicate Wiring Typical control wiring schematic — 38AH024-034 Application data — 38AH024-034 Indoor equipment should be selected at no less than 40 L/s per kW (300 cfm/ton). Installation Select equipment to match or to be slightly less than peak load. This provides better humidity control, less unit cycling, and less part-load operation. When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions. The indoor fan must always be operating when outdoor unit is operating. IMPORTANT: Condensing units applied in VVT or VAV systems must have field-supplied and installed accumulators. Order 2 part number --KH--73LZ-001 from Service Parts (1 required for each refrigerant circuit). IMPORTANT: When application is in a VAV (variable air volume) system, total building load is not the sum of the individual peak loads. If individual peak loads are summed, the equipment tends to be oversized for the load. OPERATING LIMITS Maximum Outdoor Ambient Minimum Outdoor Ambient Minimum Return-Air Temperature Maximum Return-Air Temperature Normal Acceptable Saturation Suction Temperature Range Maximum Discharge Temperature Minimum Discharge Superheat To minimize return-air temperature extremes, use the equipment room as a return-air plenum when applying VVTt (variable volume temperature) systems with supply-to-return air recycle as used with Carrier VVT control systems. Ductwork should be sized according to unit size, not building load. To minimize the possibility of air recirculation, avoid the use of concentric supply/return grilles. 52C (125 F) See Minimum OutdoorAir Operating Temperature table below. 12.8 C (55 F) 35 C (95 F) −6.6 to 10.0 C (20 to 50 F) 135.0 C (275 F) 15.6 C (60 F) UNLOADING SEQUENCES CAPACITY/STAGE (%) CV Units (Standard)* VAV Units (Optional) 100, 83, 50, 33 100, 83, 67, 50, 33, 17 100, 83, 50, 33 100, 83, 67, 50, 33, 17 100, 85, 43, 28 100, 85, 77, 43, 28, 14 UNIT 38AH 024 028 034 LEGEND CV — Constant Volume VAV — Variable Air Volume *Additional unloading available with field-installed accessory unloader. NOTE: Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C (95 F) outdoor air temperature. MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND UNLOADING SEQUENCES UNIT 38AH 024 028 034 SYSTEM CAPACITY (%) 100 83 67† 50 33 17† 100 83 67† 50 33 17† 100 81 62† 43 29 14† MINIMUM OUTDOOR-AIR TEMP Standard Unit Low Ambient Control C F C F −29 −20 −29 −20 * * 11.7 53 −29 −20 −29 −20 * * −29 −20 −29 −20 * * 10.0 50 −29 −20 −29 −20 * * −29 −20 −29 −20 * * 9.4 49 −29 −20 −29 * −20 * *MotormasterT III cannot be used with 2 unloaders. †VAV or accessory unloader on Circuit 1. NOTE: Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing temperature and 100% capacity. 39 Application data — 38AH024-034 (cont) REFRIGERANT PIPE SIZES SINGLE SUCTION RISERS UNIT 38AH 0-25 (0-7.6) L S 1⁄2 11⁄8 1⁄2 11⁄8 1⁄2 11⁄8 1⁄2 11⁄8 1⁄2 11⁄8 5⁄8 13⁄8 024 Ckt 1 Ckt 2 028 Ckt 1 Ckt 2 034 Ckt 1 Ckt 2 LENGTH OF INTERCONNECTING PIPING, FOR EACH CIRCUIT — FT (M) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) L S L S L S 5⁄8 5⁄8 5 ⁄8 11⁄8 13⁄8 13⁄8 5⁄8 5⁄8 5 ⁄8 11⁄8 13⁄8 13⁄8 5⁄8 5⁄8 5 ⁄8 13⁄8 13⁄8 13⁄8 5⁄8 5⁄8 5 ⁄8 13⁄8 13⁄8 13⁄8 5⁄8 5⁄8 5 ⁄8 13⁄8 13⁄8 13⁄8 5⁄8 5⁄8 7 ⁄8 15⁄8 15⁄8 15⁄8 LEGEND L — Liquid Line S — Suction Line *Double suction riser required if evaporator is below condensing unit and 2 unloaders are used on that circuit. †Double suction riser required if evaporator is below condensing unit and compressor is equipped with 2 unloaders. Note the only time circuit no. 2 may be equipped with 2 unloaders is if it is serving its own air handler and the unit does not require low ambient operation (MotormasterT III control). 100-200 (30.5-61.0) L S 7 ⁄8 15⁄8*† 7 ⁄8 15⁄8*† 7 ⁄8 15⁄8*† 7 ⁄8 15⁄8*† 7 ⁄8 15⁄8*† 7 ⁄8 21⁄8*† NOTES: 1. All line sizes are inches OD. 2. Standard unit comes with one pressure-operated unloader on circuit no. 1. If unit serves one air handler, an additional unloader may be field installed on circuit no. 1 compressor only. If the unit serves 2 separate air handlers and low ambient operation is required (Motormaster III control), each circuit’s compressor may only be equipped with one unloader. 3. Equivalent line sizes in mm follow: in. 1⁄2 5⁄8 7⁄8 11⁄8 mm 12.7 15.9 22.2 28.6 in. 13⁄8 15⁄8 21⁄8 mm 34.9 41.3 54.0 DOUBLE SUCTION RISERS UNIT 38AH 024 Ckt Ckt 028 Ckt Ckt 034 Ckt Ckt 1 2 1 2 1 2 LENGTH OF INTERCONNECTING PIPING — Ft (M) 100-200 (30.5-61.0) A B C 11⁄8 13⁄8 15⁄8 13⁄8 13⁄8 15⁄8 1 3 1 ⁄8 1 ⁄8 15⁄8 11⁄8 13⁄8 15⁄8 11⁄8 13⁄8 15⁄8 13⁄8 15⁄8 21⁄8 MAXIMUM LIQUID LIFT UNIT 38AH 024 028 034 MAXIMUM LIQUID LIFT PER CIRCUIT — M (Ft) 23.2 (76) 22.3 (73) 30.5 (100) LEGEND — Suction Riser without Trap — Suction Riser with Trap — Suction Line to Condensing Unit — Pipe Diameter to be Same Size as Riser A 40 Application data — 40RM Operating limits Maximum fan speed — 40RM016,024 . . . . . . . . . . . . . . . . . . 20 r/s (1200 rpm) Maximum fan speed — 40RM028,034 . . . . . . . . . . . . . . . . 18.3 r/s (1100 rpm) General Select equipment to match or to be slightly less than peak load. This provides better humidity control, less unit cycling, and less part-load operation. Equipment should be selected to perform at no less than 40 L/s per kW (300 cfm/ton). The air handler fan must always be operating when the condensing unit is operating. Ductwork should be sized according to unit size, not building load. For larger units with two fans, a split duct transition is recommended at the fan outlets, but a plenum can be used with slight reduction in external static pressure capability. For variable air volume (VAV) systems with supply-toreturn air recycling, use the equipment room as a return air plenum. FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA UNIT 40RM 016 024 028 034 TXV Qty...Part No. 2...XVE-8 2...XVE-10 2...EBSVE-11 2...SVE-15 DISTRIBUTOR Qty...Part No. 2...1116 2...1116 2...1126 2...1126 FEEDER TUBES PER DISTRIBUTOR* 12 13 15 18 NOZZLE Qty...Part No. 2...E6 2...E8 2...C10 2...C12 *Feeder tube size is 6.35 mm (1⁄4 in.). NOTE: Hot gas bypass applications require field-supplied auxiliary side connector. 40RM FAN MOTOR DATA STANDARD MOTOR — ENGLISH STANDARD MOTOR — SI UNIT 016 40RM 230-3-50 and 400-3-50 Speed (r/s) 23.75 Shaft kW 2.16 Frame (NEMA) 56Y Shaft Dia (mm) 22.2 024 028 034 23.75 3.73 184T 28.6 23.75 5.59 S213T 34.9 23.75 7.46 S215T 34.9 NEMA — National Electrical Manufacturers Association (U.S.A.) ALTERNATE MOTOR — SI UNIT 40RM 230-3-50 and 400-3-50 Speed (r/s) Shaft kW Frame (NEMA) Shaft Dia (mm) UNIT 016 40RM 230-3-50 and 400-3-50 Speed (rpm) 1425 Hp 2.9 Frame (NEMA) 56Y 7⁄8 Shaft Dia (in.) 024 028 034 1425 5.0 184T 11⁄8 1425 7.5 S213T 13⁄8 1425 10.0 S215T 13⁄8 NEMA — National Electrical Manufacturers Association (U.S.A.) ALTERNATE MOTOR — ENGLISH 016 024 028 23.75 3.73 S184T 28.6 23.75 5.59 S213T 34.9 23.75 7.46 S215T 34.9 NEMA — National Electrical Manufacturers Association (U.S.A.) UNIT 40RM 230-3-50 and 400-3-50 Speed (rpm) Hp Frame (NEMA) Shaft Dia (in.) 016 024 028 1425 5.0 S184T 11⁄8 1425 7.5 S213T 13⁄8 1425 10.0 S215T 13⁄8 NEMA — National Electrical Manufacturers Association (U.S.A.) 41 Application data — 40RM (cont) 40RM DRIVE DATA STANDARD DRIVE — SI UNIT 40RM MOTOR DRIVE Motor Pulley Pitch Diameter (mm) Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (mm) Pulley Bore (mm) Belt No. — Section Belt Pitch (mm) FAN SPEEDS (r/s) Factory Setting Range Max Allowable Speed (r/s) Change per 1⁄2 Turn of Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (mm) HIGH-STATIC DRIVE — SI 016 024 028 034 86.4111.8 109.2134.6 109.2134.6 109.2134.6 2.5 3.0 3.0 3.0 229 36.5 1—A 1074 218 36.5 1—B 1062 279 49.2 2—B 1113 279 49.2 2—B 1113 10.3 9.011.6 20.0 13.3 11.914.6 20.0 10.4 9.311.5 18.3 10.4 9.311.5 18.3 0.265 0.230 0.180 0.180 5 6 6 6 265313 232279 169240 169240 MEDIUM-STATIC DRIVE — SI UNIT 40RM MOTOR DRIVE Motor Pulley Pitch Diameter (mm) Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (mm) Pulley Bore (mm) Belt No. — Section Belt Pitch (mm) FAN SPEEDS (r/s) Factory Setting Range Max Allowable Speed (r/s) Change per 1⁄2 Turn of Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (mm) 42 UNIT 40RM MOTOR DRIVE Motor Pulley Pitch Diameter (mm) Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (mm) Pulley Bore (mm) Belt No. — Section Belt Pitch (mm) FAN SPEEDS (r/s) Factory Setting Range Max Allowable Speed (r/s) Change per 1⁄2 Turn of Moveable Motor Pulley Flange MAX FULL TURNS FROM CLOSED POSITION SHAFTS CENTER DISTANCE (mm) 016 024 028 034 101.6127.0 101.6127.0 109.2134.6 109.2134.6 3.0 3.0 3.0 3.0 178 36.5 2—A 998 163 36.5 2—A 871 203 49.2 2—B 935 218 49.2 2—B 960 15.3 13.617.0 20.0 16.7 14.918.6 20.0 14.3 12.815.7 18.3 13.3 11.914.6 18.3 0.283 0.308 0.247 0.230 6 6 6 6 232279 207255 169240 169240 STANDARD DRIVE — ENGLISH 016 024 028 034 94.0119.4 101.6127.0 109.2134.6 109.2134.6 3.0 2.5 3.0 3.0 201 36.5 1—B 1011 178 36.5 2—A 922 239 49.2 2—B 1011 239 49.2 2—B 1011 12.6 11.114.1 20.0 15.3 13.617.0 20.0 12.1 10.913.4 18.3 12.1 10.913.4 18.3 0.252 0.340 0.210 0.210 6 5 6 6 232279 232279 169240 169240 UNIT 016 024 028 034 40RM MOTOR DRIVE Motor Pulley Pitch Diameter 3.4-4.4 4.3-5.3 4.3-5.3 4.3-5.3 (in.) Pulley Factory Setting 2.5 3.0 3.0 3.0 Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) 9.0 8.6 11.0 11.0 Pulley Bore (in.) 17⁄16 17⁄16 115⁄16 115⁄16 Belt No. — Section 1—A 1—B 2—B 2—B Belt Pitch (in.) 42.3 41.8 43.8 43.8 FAN SPEEDS (rpm) Factory Setting 618 795 622 622 538713557557Range 697 878 687 687 Max Allowable Speed (rpm) 1200 1200 1100 1100 Change per 1⁄2 Turn of Moveable Motor Pulley 15.9 13.8 10.8 10.8 Flange MAX FULL TURNS FROM 5 6 6 6 CLOSED POSITION SHAFTS CENTER DISTANCE 10.449.12- 6.676.67(in.) 12.32 10.99 9.43 9.43 40RM DRIVE DATA (cont) MEDIUM-STATIC DRIVE — ENGLISH HIGH-STATIC DRIVE —ENGLISH UNIT 016 024 028 034 40RM MOTOR DRIVE Motor Pulley Pitch Diameter 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3 (in.) Pulley Factory Setting 3.0 2.5 3.0 3.0 Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) 7.9 7.0 9.4 9.4 Pulley Bore (in.) 17⁄16 17⁄16 115⁄16 115⁄16 Belt No. — Section 1—B 2—A 2—B 2—B Belt Pitch (in.) 39.8 36.8 39.8 39.8 FAN SPEEDS (rpm) Factory Setting 756 916 728 728 667814652652Range 848 1018 803 803 Max Allowable Speed (rpm) 1200 1200 1100 1100 Change per 1⁄2 Turn of Moveable Motor Pulley 15.1 20.4 12.6 12.6 Flange MAX FULL TURNS FROM 6 5 6 6 CLOSED POSITION SHAFTS CENTER DISTANCE 9.169.16- 6.676.67(in.) 10.99 10.99 9.43 9.43 UNIT 016 024 028 034 40RM MOTOR DRIVE Motor Pulley Pitch Diameter 4.0-5.0 4.0-5.0 4.3-5.3 4.3-5.3 (in.) Pulley Factory Setting 3.0 3.0 3.0 3.0 Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) 7.0 6.4 8.0 8.6 Pulley Bore (in.) 17⁄16 17⁄16 115⁄16 115⁄16 Belt No. — Section 2—A 2—A 2—B 2—B Belt Pitch (in.) 39.3 34.3 36.8 37.8 FAN SPEEDS (rpm) Factory Setting 916 1002 855 795 814891766713Range 1018 1113 944 878 Max Allowable Speed (rpm) 1200 1200 1100 1100 Change per 1⁄2 Turn of Moveable Motor Pulley 17.0 18.5 14.8 13.8 Flange MAX FULL TURNS FROM 6 6 6 6 CLOSED POSITION SHAFTS CENTER DISTANCE 9.168.16- 6.676.67(in.) 10.99 10.02 9.43 9.43 43 Model number nomenclature — 38AH044-134 38AH — 094 —— — 9 0 3 AA 38AH — Split System Condensing Unit Factory-Installed Options 044-084: – – — Standard Unit AA — Class F Fan Motors BA — VAV Control Box Modification and Electric Unloaders CA — VAV Modifications and Class F Fan Motors DA — Single-Circuit Piping EA — Single-Circuit Piping with Class F Fan Motors FA — Single-Circuit Piping and VAV Modifications GA — Single-Circuit Piping, VAV Modifications, and Class F Fan Motors 094,104: – – — Standard Unit AA — Class F Fan Motors BA — VAV (Variable Air Volume) Modifications CA — Class F Fan Motors with VAV Modifications 124,134: DA — Standard Unit EA — Class F Fan Motors FA — VAV Modifications GA — Class F Fan Motors with VAV Modifications Start Options – — Across-the-Line Start P — Part-Wind Start Nominal Capacity 044 — 123 kW (35 Tons) 054 — 144 kW (41 Tons) 064 — 175 kW (50 Tons) 074 — 214 kW (61 Tons) 084 — 242 kW (69 Tons) 094 — 274 kW (78 Tons) 104 — 305 kW (87 Tons) 124 — 351 kW (100 Tons) 134 — 390 kW (111 Tons) Not Used Condenser Fin Material – — Aluminum (Standard) C — Copper (Optional) K — Pre-Coated Aluminum (Optional) SO — Post-Coated Aluminum (Contact Factory) SO — Post-Coated Copper (Contact Factory) Voltage Designation 3 — 346-3-50 (Part Wind) 8 — 230-3-50 (Part-Wind, 044 Size) 9 — 380/415-3-50 Packaging 2 — Coil Protection Only (For Closed Container Shipments) 3 — Standard Export (Top and Bottom Skid, Coil Protector and Full Plastic Bag Enclosure) 4 — Optional Export (Full Export Box) Revision Number SO — Special Order Ratings summary — 38AH044-134 UNIT SIZE 044 054 064 074 084 094 104 124 134 NOMINAL CAPACITY kW Tons 123 35 144 41 175 50 214 61 242 69 274 78 305 87 351 100 390 111 EER* 10.8 10.7 10.8 10.3 10.6 10.6 10.9 10.8 10.6 LEGEND EER — Energy Efficiency Ratio *Rated in accordance with ARI (Air Conditioning & Refrigeration Institute) standard 365-87 (U.S.A.). NOTE: Ratings are based on 7.2 C (45 F) suction temperature and 35 C (95 F) outside-air temperature, and include suction line losses. 44 Options and accessories — 38AH044-134 Factory-installed options VAV (Variable Air Volume) Control Box Modification makes the condensing unit compatible with the ModuPanel™ VAV controller. Includes factory-installed accumulator. Also includes electric unloaders on compressors as follows: 1 — 38AH044 2 — 38AH054-084,104 3 — 38AH094 4 — 38AH124,134 (2 per module) Single-Circuit Modification (Sizes 38AH044-084 Only) includes factory-installed accumulator and all piping and wiring modifications required to make the unit single circuit. Single-Circuit Modification with VAV (Sizes 38AH044084 Only) includes piping, wiring, and electric unloaders on compressors (one on 38AH044 and 2 on 38AH054084) to make the unit single circuit, VAV-ready. Also includes factory-installed accumulator. Class F Fan Motors provide additional motor insulation for high ambient temperature environments. Condenser coil options are available to match coil construction to site conditions for the best corrosion durability. Pre-coated coils provide protection in mild coastal environments. All copper coils are best suited for moderate coastal applications, while post-coated coils provide superior protection in severe coastal and industrial applications. Field-installed accessories Transformer relay package for remote-control (24-v) thermostat. One 2-stage thermostat is required for use with the relay package. Additional electric unloader package includes hardware to add an additional step of unloading (coil not included). Additional pressure unloader package includes all unloader valves and hardware. Gage panel package contains panel-mounted suction and discharge pressure gages. Hail guard package protects coils against damage from hail and airborne debris. ModuPanel control provides 10-step microprocessorbased control for VAV applications. Motormastert III control maintains correct condensing pressure at low ambient temperatures. Sound-reduction kit provides a specially designed system of fan propellers and stacks that lower noise without reducing unit performance; compatible with the Motormaster III accessory. Unloader conversion kit allows you to convert factoryinstalled pressure unloaders to electric unloading. Compressor grille package protects the compressor area after the unit is installed. Condenser coil grille package protects the condenser area after the unit is installed. Carrier’s line of thermostats provide both programmable and non-programmable capability with the new Debonair™ line of commercial programmable thermostats, the TEMP System controls offer communication capability with staged heating and cooling, the Commercial Electronic thermostats provide 7-day programmable capability for economical applications, while the nonprogrammable thermostats offer a multitude of staged heating and cooling subbase options. CONDENSER COIL PROTECTION APPLICATIONS ENVIRONMENT* DESCRIPTION (Enviro-Shield™ Option) Standard, Al/Cu Pre-Coated Al/Cu Cu/Cu Post-Coated Al/Cu Post-Coated Cu/Cu Standard, Non-Corrosive Mild Coastal Moderate Coastal Severe Coastal Industrial Combined Coastal and Industrial X X X X X X LEGEND Al/Cu — Aluminum Fin with Copper Tube Coil Cu/Cu — Copper Fin with Copper Tube Coil Enviro-Shield — Family of Coil Protection Options Post-Coated — Organic Coating applied to Entire Coil Assembly Pre-Coated — Epoxy Coating Applied to Fin Stock Material *See ‘‘Selection Guide: Environmental Corrosion Protection’’ Catalog No. 811-839 for more information. 45 Options and accessories — 38AH044-134 (cont) CARRIER THERMOSTATS COMMERCIAL ELECTRONIC THERMOSTAT DEBONAIR™ COMMERCIAL PROGRAMMABLE THERMOSTAT Carrier ® Pm COOL AUTO HEAT NON-PROGRAMMABLE THERMOSTAT H 46 C TEMP SYSTEM THERMOSTAT WITH TIMECLOCK Physical data — 38AH044-134 SI 38AH NOMINAL CAPACITY (kW) OPERATING WEIGHT WITH REFRIGERANT (kg) (Approx.) SHIPPING WEIGHT WITH COIL PROTECTION ONLY (kg) (Approx.) TYPICAL OPERATING REFRIGERANT CHARGE (kg, approx.) R-22 COMPRESSOR Type...r/s (Qty Cylinder)* Circuit† Model No. 06EOil Charge (L) Capacity Control Steps** CONDENSER FANS (6 Blade) Qty...Dia (mm) Airflow (L/s) Speed (r/s) Total Power (kW) CONDENSER COIL Row...Fins per m Face Area (m2) Storage Capacity (kg per circuit, approx.) FAN CYCLING CONTROLS †† Close (kPa) Open (kPa) CONNECTIONS Suction, ODF (in.)| Liquid, ODF (in.)| Hot Gas Bypass, ODF (in.) Cu-Al Coils Cu-Cu Coils Cu-Al Coils Cu-Cu Coils 044 123 1480 1609 1474 1605 28.1 (4) A 250 8.0 at 48.9 C 064 175 1617 1813 1601 1798 074 214 1729 1918 1715 1904 084 242 1840 2148 1814 2122 32.7 39.9 47.2 58.9 Reciprocating Semi-Hermetic...24.3 @ 50 Hz (4) A (6) B (6) A (6) B (6) A (6) B 250 265 265 275 275 299 8.0 9.9 9.9 9.9 9.9 9.0 4 (4) B 250 8.0 2...669 7.48 16 054 144 1501 1632 1492 1623 (6) A 299 9.0 (6) B 299 9.0 4...762 6...762 16 500 24 500 24 100 15.8 15.8 6.2 9.3 Enhanced Copper Tubes, Lanced Aluminum Fins 2...669 3...669 2...782 3...669 7.48 7.48 10.84 10.84 16 25 25 36 1758 ± 69 1103 ± 69 21⁄8 ⁄ Ckt A 58 ⁄ 58 ⁄ Ckt B 78 ⁄ 58 21⁄8 7⁄8 ⁄ 58 LEGEND Cu-Al — Copper Tube, Aluminum Fin Cu-Cu — Copper Tube, Copper Fin ODF — Outside Diameter, Female *06E250 compressors have 4 cylinders; all others have 6. †Circuit A compressor is lead on standard units; circuit B compressor is lead on optional single-circuit units. **Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional system capacity information. ††On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104, fans no. 5 and 6. \For single-circuit units, suction ODF is 25⁄8 in. and liquid ODF is 11⁄8 inches. Single circuit units have a factory-installed manifold; no field modification is required. NOTES: 1. Certified dimensional drawings available on request. 2. Equivalent connection values in mm are as follows: in. mm ⁄ ⁄ 1⁄ 1 2 ⁄8 25⁄8 58 78 18 15.9 22.2 28.6 54.0 66.7 47 Physical data — 38AH044-134 (cont) SI (cont) 38AH 094 104 124 124A 175.5 134 134B NOMINAL CAPACITY (kW) 274 305 214.5 OPERATING WEIGHT WITH REFRIGERANT (Approx.) (kg) Cu-Al 2308 2465 1647* 1647* 1647* 1759* Cu-Cu 2637 2794 1843* 1843* 1843* 1843* SHIPPING WEIGHT WITH COIL PROTECTION AND SKID (Approx.) (kg) Cu-Al 2554 2717 1860* 1860* 1860* 1851 Cu-Cu 2883 3046 1968* 1968* 1968* 2040 TYPICAL OPERATING R-22 REFRIGERANT Charge (Approx.) (kg) 67.1 61.2 39.9 39.9 39.9 47.2 Qty of Circuits 2 2 1 1 1 1 COMPRESSOR Type...R/s Reciprocating Semi-Hermetic...24.3 (Qty Cylinder)/Compressor† (6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 Model No. 06E −275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275 Oil Charge (L) 10 8 9 10 8 10 10 10 10 10 10 10 10 9 10 Circuit Capacity (%) (Approx.) 55 45 47 53 50 50 45 55 Capacity Control Steps** 6 8 4 4 4 4 CONDENSER FANS (6 Blade) Qty...Dia (mm) 6...762 6...762 4...762 4...762 4...762 6...762 Airflow (L/s) 24 544 24 544 16 520 16 520 16 520 24 544 Speed (R/s) 15.8 15.8 15.8 15.8 15.8 15.8 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2 CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fins Rows...Fins per m 3...669.3 3...669.3 3...669.3 3...669.3 3...669.3 2...781.6 Face Area (sq m) 11.9 11.9 7.5 7.5 7.5 10.8 Storage Capacity (kg per circuit, approx.) 81 81 50 50 50 50 at 49 C FAN CYCLING CONTROLS †† Close (kPa) 1758 ± 69 Open (kPa) 1103 ± 69 CONNECTIONS Suction, ODF (in.) 21⁄8 21⁄8 25⁄8 25⁄8 25⁄8 25⁄8 7⁄8 7⁄8 Liquid, ODF (in.) 11⁄8 11⁄8 11⁄8 11⁄8 5⁄8 5⁄8 5 ⁄8 5⁄8 5⁄8 5⁄8 Hot Gas Bypass, ODF (in.) LEGEND Cu-Al — Copper Tube, Aluminum Fin Cu-Cu — Copper Tube, Copper Fin ODF — Outside Diameter, Female VAV — Variable Air Volume *Includes piping and trim kit. †Compressor A1 is lead compressor on all circuits except circuit B on units 38AH094 and 104. Compressor B1 is lead on circuit B on units 38AH094 and 104. Compressors are shipped with minimum oil charge. **Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional system capacity information. ††On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104, fans no. 5 and 6. NOTES: 1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one 134A module and one 134B module. 2. Certified dimensional drawings available on request. 48 124B 175.5 134A 175.5 ENGLISH 38AH NOMINAL CAPACITY (Tons) OPERATING WEIGHT WITH REFRIGERANT (lb) (Approx.) SHIPPING WEIGHT WITH COIL PROTECTION ONLY (lb) (Approx.) TYPICAL OPERATING REFRIGERANT CHARGE (lb, approx.) R-22 COMPRESSOR Type...Rpm (Qty Cylinder)* Circuit† Model No. 06EOil Charge (pt) Capacity Control Steps** CONDENSER FANS (6 Blade) Qty...Dia (in.) Airflow (cfm) Speed (rpm) Total Power (kW) CONDENSER COIL — Rows Fins per...in. Face Area (ft2) Storage Capacity (lb per circuit, approx.) FAN CYCLING CONTROLS †† Close (psig) Open (psig) CONNECTIONS Suction, ODF (in.)†† Liquid, ODF (in.)†† Hot Gas Bypass, ODF (in.) Cu-Al Coils Cu-Cu Coils Cu-Al Coils Cu-Cu Coils 044 35 3259 3547 3250 3538 054 41 3309 3597 3290 3578 064 50 3565 3998 3530 3963 074 61 3812 4229 3780 4197 084 69 4057 4735 4000 4678 72 88 104 130 62 (4) A 250 17 at 120 F Reciprocating Semi-Hermetic...1458 @ 50 Hz (4) A (6) B (6) A (6) B (6) A (6) B 250 265 265 275 275 299 17 21 21 21 21 19 4 (4) B 250 17 4...30 35,000 950 6.2 2 17 80.5 35 2 17 80.5 35 (6) A 299 19 (6) B 299 19 6...30 52,000 51,000 950 9.3 3 17 80.5 55 2 19 116.7 55 3 17 116.7 80 255 ± 10 160 ± 10 21⁄8 ⁄ Ckt A 58 ⁄ 58 ⁄ Ckt B 78 ⁄ 58 21⁄8 7⁄8 ⁄ 58 LEGEND Cu-Al — Copper Tube, Aluminum Fn Cu-Cu — Copper Tube, Copper Fn ODF — Outside Diameter, Female *06E250 compressors have 4 cylinders; all others have 6. †Circuit A compressor is lead on standard units; circuit B compressor is lead on optional single-circuit units. **Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional system capacity information. ††On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104, fans no. 5 and 6. \For single-circuit units, suction ODF is 25⁄8 in. and liquid ODF is 11⁄8 inches. Single circuit units have a factory-installed manifold; no field modification is required. NOTE: Certified dimensional drawings available on request. 49 Physical data — 38AH044-134 (cont) ENGLISH (cont) 38AH 094 104 124 124A 50 134 134B NOMINAL CAPACITY (Tons) 78 87 61 OPERATING WEIGHT WITH REFRIGERANT (Approx.) (lb) Cu-Al 5088 5435 3630* 3630* 3630* 3877* Cu-Cu 5813 6160 4063* 4063* 4063* 4294* SHIPPING WEIGHT WITH COIL PROTECTION AND SKID (Approx.) (lb) Cu-Al 5630 5990 3907* 3907* 3907* 4080 Cu-Cu 6355 6715 4340* 4340* 4340* 4497 TYPICAL OPERATING R-22 REFRIGERANT Charge (Approx.) (lb) 148 135 88 88 88 104 Qty of Circuits 2 2 1 1 1 1 COMPRESSOR Type...Rpm Reciprocating Semi-Hermetic...1450 (Qty Cylinder)/Compressor† (6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 Model No. 06E −275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275 Oil Charge (pt) 21 17 19 21 17 21 21 21 21 21 21 21 21 19 21 Circuit Capacity (%) (Approx.) 55 45 47 53 50 50 45 55 Capacity Control Steps** 6 8 4 4 4 4 CONDENSER FANS (6 Blade) Qty...Dia (in.) 6...30 6...30 4...30 4...30 4...30 6...30 Airflow (cfm) 52,000 52,000 35,000 35,000 35,000 52,000 Speed (rpm) 950 950 950 950 950 950 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2 CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fin Rows...Fins per in. 3...17 3...17 3...17 3...17 3...17 2...19 Face Area (sq ft) 128.3 128.3 80.5 80.5 80.5 116.7 Storage Capacity (lb per ckt, approx.) 178 178 110 110 110 110 at 120 F FAN CYCLING CONTROLS †† Close (psig) 255 ± 10 Open (psig) 160 ± 10 CONNECTIONS Suction, ODF (in.) 21⁄8 21⁄8 25⁄8 25⁄8 25⁄8 25⁄8 7⁄8 7⁄8 Liquid, ODF (in.) 11⁄8 11⁄8 11⁄8 11⁄8 5⁄8 5⁄8 5 ⁄8 5⁄8 5⁄8 5⁄8 Hot Gas Bypass, ODF (in.) LEGEND Cu-Al — Copper Tube, Aluminum Fin Cu-Cu — Copper Tube, Copper Fin ODF — Outside Diameter, Female VAV — Variable Air Volume *Includes piping and trim kit. †Compressor A1 is lead compressor on all circuits except circuit B on units 38AH094 and 104. Compressor B1 is lead on circuit B on units 38AH094 and 104. Compressors are shipped with minimum oil charge. **Capacity control steps listed are for constant volume units with no accessories. Refer to Minimum Outdoor-Air Operating Temperature and Unloading Sequences tables, pages 94-96, for additional system capacity information. ††On all 044-134 units, fan no. 3 and 4; also on 38AH074,084 (dual-circuit units only) and 38AH094,104, fans no. 5 and 6. NOTES: 1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one 134A module and one 134B module. 2. Certified dimensional drawings available on request. 50 124B 50 134A 50 Dimensions — 38AH044-134 SIZES 044-064 (See Page 53 for Corner Weights) UNIT 38AH 044 044C 054 054C 064 064C DIMENSION Y 38-23⁄49 [984 mm] 38-31⁄89 [994 mm] 38-21⁄29 [978 mm] 38-39 [991 mm] 38-21⁄29 [978 mm] 38-33⁄169 [995 mm] DIMENSION X 48-1⁄29 [1232 mm] 48-9⁄169 [1234 mm] 48-3⁄169 [1224 mm] 48-3⁄89 [1229 mm] 48-1⁄29 [1232 mm] 48-5⁄89 [1235 mm] LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 044 044,054 064 044,054 064 VOLTAGE 230 346 346 380/415 380/415 Hz 50 50 50 50 50 DIAMETER 35⁄89 [92 mm] 21⁄29 [63 mm] 35⁄89 [92 mm] 21⁄29 [63 mm] 35⁄89 [92 mm] QTY. 1 1 1 1 1 NOTES: 1. The approximate operating weight of the unit is: 38AH044 3259 lb (1480 kg) 38AH044C 3547 lb (1609 kg) 38AH054 3309 lb (1501 kg) 38AH054C 3597 lb (1632 kg) 38AH064 3565 lb (1617 kg) 38AH064C 3998 lb (1813 kg) 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Two 51 mm (2 in.) dia holes are recommended for parallel conductors on 044 (230-V) units. 5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 6. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended. 51 Dimensions — 38AH044-134 (cont) SIZES 074, 084 (See Page 53 for Corner Weights) UNIT 38AH 074 074C 084 084C DIMENSION Y 38-31⁄89 [994 mm] 38-35⁄89 [1006 mm] 38-39 [991 mm] 38-311⁄169 [1008 mm] DIMENSION X 48-813⁄1688 [1443 mm] 48-81⁄89 [1425 mm] 48-99 [1448 mm] 48-89 [1422 mm] LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 074,084 074,084 VOLTAGE 346 380/415 Hz 50 50 DIAMETER 35⁄89 [92 mm] 35⁄89 [92 mm] QTY. 1 1 NOTES: 1. The approximate operating weight of the unit is: 38AH074 3812 lb (1729 kg) 38AH074C 4229 lb (1918 kg) 38AH084 4057 lb (1840 kg) 38AH084C 4735 lb (2148 kg) 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 5. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended. 52 OPERATIONAL CORNER WEIGHTS WITH REFRIGERANT CHARGE (Approximate) — Kg UNIT 38AH TOTAL WEIGHT 044 044C 054 054C 064 064C 074 074C 084 084C 1480 1609 1501 1632 1617 1813 1729 1918 1840 2148 C — Copper Fin Coils OPERATIONAL CORNER WEIGHT A B C D 426 405 316 332 460 438 347 364 437 411 316 337 469 444 350 369 462 459 347 350 510 508 397 399 520 447 352 410 577 481 391 470 553 476 375 436 646 538 438 526 OPERATIONAL CORNER WEIGHTS WITH REFRIGERANT CHARGE (Approximate) — Lb UNIT 38AH TOTAL WEIGHT 044 044C 054 054C 064 064C 074 074C 084 084C 3259 3547 3309 3597 3565 3998 3812 4229 4057 4735 OPERATIONAL CORNER WEIGHT A B C D 939 893 695 732 1013 967 765 802 964 905 697 742 1034 978 771 814 1018 1011 765 771 1125 1117 874 879 1146 986 777 903 1272 1059 862 1035 1220 1049 827 961 1425 1186 965 1159 C — Copper Fin Coils 53 Dimensions — 38AH044-134 (cont) UNIT 38AH094 DIMENSIONS OPERATIONAL CORNER ft-in. [mm] WEIGHTS — lb [kg] X Y A B C D 094 5-6 [1676] 2-7 [787] 1114 [505] 2192 [994] 1182 [536] 601 [273] 094C 5-6 [1676] 2-7 [787] 1273 [577] 2504 [1136] 1350 [612] 686 [311] UNIT 38AH LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers 54 CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 38AH NOTES: 1. The approximate operating weight of the unit is: 38AH094 — 5088 lb [2308 Kg] 38AH094C — 5813 lb [2637 Kg] 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] 094 VOLTAGE 346 380/415 DIAMETER in. [mm] 35⁄8 92] QUANTITY 1 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 5. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended. UNIT 38AH104 DIMENSIONS OPERATIONAL CORNER ft-in. [mm] WEIGHTS — lb [kg] X Y A B C D 104 5-3 [1600] 2-91⁄2 [851] 1240 [562] 2138 [970] 1302 [591] 755 [342] 104C 5-3 [1600] 2-91⁄2 [851] 1405 [637] 2423 [1099] 1476 [670] 856 [388] UNIT 38AH LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers NOTES: 1. The approximate operating weight of the unit is: 38AH104 — 5435 lb [2465 Kg] 38AH104C — 6160 lb [2794 Kg] 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 38AH 104 VOLTAGE 346 380/415 DIAMETER in. [mm] 35⁄8 [92] QUANTITY 1 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 5. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended. 55 Dimensions — 38AH044-134 (cont) UNIT 38AH124 UNIT 38AH MODULE 124A 124B 124A-C 124B-C DIMENSIONS ft-in. [mm] X Y K L — — 4-15⁄8 [1260] 3-21⁄8 [968] — — 4-15⁄8 [1260] 3-21⁄8 [968] — — 4-15⁄8 [1260] 3-27⁄8 [987] — — 4-15⁄8 [1260] 3-27⁄8 [987] LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers 56 OPERATIONAL CORNER WEIGHTS — lb [kg] A B C D 1037 1030 779 785 [470] [467] [353] [356] CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 38AH MODULE 124A 124B VOLTAGE DIAMETER in. [mm] QUANTITY 346, 380/415 35⁄8 [92] 1 1144 1137 889 894 [519] [516] [403] [406] NOTES: 1. The approximate operating weight of the unit is: 38AH124 — 7260 lb [3293 Kg] 38AH124C — 8126 lb [3686 Kg] 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 5. If spring isolators are used, a perimeter support channel between the assembled unit and the isolators is required. Do not support each module separately. 6. Each module must be rigged into position separately. The unit must not be rigged after modules have been connected. 7. Suction and liquid connections can exit on either side of the unit. 8. Field power supply connections are required for each module. UNIT 38AH134 UNIT 38AH MODULE 134A 134B 134A-C 134B-C DIMENSIONS ft-in. [mm] X Y K L 4-15⁄8 [1260] 3-21⁄8 [968] — — — — 4-87⁄8 [1445] 3-31⁄8 [994] 4-15⁄8 [1260] 3-27⁄8 [987] — — — — 4-81⁄8 [1426] 3-33⁄4 [1010] OPERATIONAL CORNER WEIGHTS — lb [kg] A B C D 1037 [470] 1030 [467] 779 [353] 785 [356] 1167 [529] 997 [452] 789 [358] 924 [419] 1144 [519] 1137 [516] 889 [403] 894 [406] 1293 [587] 1080 [490] 874 [396] 1047 [475] CHART 1, FIELD POWER SUPPLY CONNECTIONS UNIT 38AH MODULE 134A 134B VOLTAGE 346 380/415 DIAMETER in. [mm] 35⁄8 [92] QUANTITY 1 LEGEND C — Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers NOTES: 1. The approximate operating weight of the unit is: 38AH134 — 7507 lb [3405 Kg] 38AH134C — 8357 lb [3791 Kg] 2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [153 cm] Sides — 6 ft [183 cm] 3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. 4. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table, page 88 and Wiring Diagram book. 5. If spring isolators are used, a perimeter support channel between the assembled unit and the isolators is required. Do not support each module separately. 6. Each module must be rigged into position separately. The unit must not be rigged after modules have been connected. 7. Suction and liquid connections can exit on either side of the unit. 8. Field power supply connections are required for each module. 57 Selection procedure, 2-circuit units — 38AH044-134 SI I Determine required cooling capacity of each circuit, saturated suction temperature (SST) for each circuit, and the temperature of the air entering the condensing unit. Given: Circuit A Circuit B Cooling Load . . . . . . . . . . . . . . . . . 78 kW . . . 86 kW Saturated suction temperature . . . . . . . . . . . . . . . . . . . 6 C . . . . . . 6 C Entering-air temperature . . . . . . . . . 35 C . . . . . 35 C II Enter the Condensing Unit Circuit and Module Ratings tables for each circuit at the given suction temperatures and entering-air temperatures; select a unit that satisfies the requirements of each circuit. The 38AH064 unit has a cooling capacity of 79.5 kW at 6 C SST for circuit A, and a cooling capacity of 88.6 kW at 6 C SST for circuit B, both at an enteringair temperature of 35 C. The unit meets requirements according to the given conditions. ENGLISH I Determine required cooling capacity of each circuit, saturated suction temperature (SST) for each circuit, and the temperature of the air entering the condensing unit. Given: Circuit A Circuit B Cooling Load . . . . 252,000 Btuh . . . 281,000 Btuh Saturated suction temperature . . . . . . . . . . . . 40 F . . . . . . . . . . . 40 F Entering-air temperature . . . 95 F . . . . . . . . . . . 95 F II Enter the Condensing Unit Circuit and Module Ratings tables for each circuit at the given suction temperatures and entering-air temperatures; select a unit that satisfies the requirements of each circuit. The 38AH064 unit has a cooling capacity of 256,000 Btuh at 40 F SST for circuit A, and a cooling capacity of 286,000 Btuh at 40 F SST for circuit B, both at an entering-air temperature of 95 F. The unit meets requirements according to the given conditions. Selection procedure, single-circuit units — 38AH044-084 only SI I Determine required capacity, saturated suction temperature (SST) at the compressors, and the temperature of the air entering the condensing unit. Given: Cooling Load . . . . . . . . . . . . . . . . . . . . . . . . . . 156 kW Saturated suction temperature . . . . . . . . . . . . . . 4.0 C Entering-air temperature . . . . . . . . . . . . . . . . . . . 35 C II Enter the Condensing Unit Ratings table at the given suction temperature and entering-air temperature for the required cooling capacity. The 38AH064 unit has a cooling capacity of 156.1 kW at 4 C SST and 35 C entering-air temperature; the unit meets requirements according to the given conditions. ENGLISH I Determine required capacity, saturated suction temperature (SST) at the compressors, and the temperature of the air entering the condensing unit. Given: Cooling Load . . . . . . . . . . . . . . . . . . . . . 535,000 Btuh Saturated suction temperature . . . . . . . . . . . . . . . 40 F Entering-air temperature . . . . . . . . . . . . . . . . . . . 95 F 58 II Enter the Condensing Unit Ratings table at the given suction temperature and entering-air temperature for the required cooling capacity. The 38AH064 unit has a cooling capacity of 542,000 Btuh at 40 F SST and 95 F entering-air temperature; the unit meets requirements according to the given conditions. Performance data — 38AH044-134 CONDENSING UNIT RATINGS — SI 38AH044 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 105.5 24.2 33.3 114.2 24.7 33.7 123.6 25.1 34.2 133.1 25.6 34.7 143.1 26.1 35.3 153.5 26.6 35.9 164.1 27.0 36.6 27 96.9 26.3 39.2 105.4 27.0 39.5 114.3 27.7 39.9 123.6 28.4 40.5 133.1 29.0 41.0 143.1 29.7 41.6 153.3 30.4 42.3 30 92.6 27.3 42.1 100.8 28.2 42.4 109.6 28.9 42.8 118.7 29.7 43.3 128.0 30.5 43.9 137.9 31.2 44.5 147.9 31.9 45.1 32 89.6 27.9 44.0 97.8 28.8 44.3 106.5 29.7 44.8 115.4 30.5 45.2 124.7 31.4 45.7 134.3 32.2 46.4 144.2 32.9 47.0 Air Temperature 35 85.1 28.8 46.9 93.2 29.8 47.2 101.7 30.8 47.7 110.4 31.7 48.1 119.5 32.7 48.6 128.9 33.6 49.2 138.6 34.5 49.8 Entering Condenser (C) 38 41 43 80.6 76.1 73.1 29.4 30.1 30.4 49.9 52.8 54.8 88.6 83.9 80.7 30.6 31.4 31.8 50.2 53.0 55.0 96.9 92.1 88.8 31.8 32.6 33.1 50.5 53.4 55.3 105.5 100.4 97.1 32.8 33.8 34.4 51.0 53.8 55.7 114.4 109.1 105.6 33.9 35.0 35.7 51.4 54.3 56.2 123.6 118.2 114.5 34.9 36.1 36.9 52.0 54.8 56.7 133.0 127.3 123.6 36.0 37.2 38.1 52.6 55.4 57.3 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 123.0 29.5 35.7 133.3 30.2 36.0 144.2 30.9 36.5 155.4 31.6 36.5 167.0 32.5 37.6 178.9 33.2 38.4 191.2 33.9 39.2 27 113.2 32.0 41.6 123.0 32.9 41.8 133.4 33.8 42.2 144.2 34.7 42.7 155.3 35.7 43.3 166.8 36.6 44.0 179.0 37.6 44.7 30 108.1 33.0 44.5 117.8 34.2 44.8 128.0 35.1 45.2 138.5 36.2 45.5 149.4 37.2 46.1 160.7 38.3 46.7 172.2 39.3 47.4 32 104.9 33.7 46.5 114.3 34.9 46.7 124.4 36.0 47.1 134.7 37.1 47.5 145.5 38.3 48.0 156.6 39.4 48.6 168.0 40.5 49.3 Air Temperature 35 100.0 34.6 49.5 109.1 36.0 49.6 119.0 37.2 50.0 129.1 38.5 50.3 139.6 39.7 50.8 150.5 41.0 51.4 161.6 42.2 52.0 Entering Condenser (C) 38 41 43 95.1 90.2 87.0 35.5 36.2 36.7 52.4 55.4 57.4 104.0 98.9 95.6 37.0 37.8 38.3 52.6 55.5 57.5 113.6 108.3 104.8 38.3 39.3 39.9 52.9 55.8 57.8 123.5 117.9 114.1 39.6 40.8 41.5 53.3 56.1 58.1 133.8 127.9 124.0 41.0 42.3 43.0 53.7 56.5 58.5 144.4 138.3 134.2 42.4 43.7 44.6 54.2 57.0 59.0 155.2 148.8 144.6 43.7 45.2 46.1 54.8 57.6 59.5 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 148.5 35.7 34.7 160.3 36.6 35.1 172.9 37.5 35.7 185.8 38.4 36.4 199.4 39.3 37.2 213.0 40.2 38.0 227.0 41.1 38.9 27 137.2 38.6 40.5 148.6 39.8 40.9 160.7 41.0 41.5 173.1 42.2 42.1 185.9 43.4 42.8 198.9 44.5 43.6 213.0 45.7 44.4 30 131.7 40.0 43.5 142.8 41.3 43.8 154.6 42.6 44.3 166.6 43.9 44.9 179.2 45.3 45.6 192.4 46.5 46.4 205.8 47.9 47.2 32 127.9 40.8 45.5 138.9 42.3 45.7 150.5 43.6 46.3 162.4 45.0 46.8 174.7 46.4 47.5 187.5 47.8 48.2 200.3 49.3 49.1 Air Temperature 35 122.4 42.0 48.3 133.1 43.5 48.6 144.4 45.0 49.1 156.1 46.6 49.7 168.1 48.2 50.3 180.6 49.7 51.1 193.7 51.3 51.8 Entering Condenser (C) 38 41 43 116.9 111.4 107.8 43.1 44.0 44.6 51.3 54.2 56.2 127.3 121.6 117.8 44.8 45.8 46.4 51.6 54.5 56.4 138.4 132.4 128.4 46.4 47.6 48.3 52.0 54.9 56.9 149.8 143.4 139.2 48.1 49.4 50.2 52.6 55.4 57.3 161.4 154.8 150.5 49.7 51.2 52.2 53.2 56.0 57.9 173.7 166.7 162.2 51.4 53.1 54.1 53.9 56.7 58.5 186.0 178.9 174.0 53.2 54.9 56.0 54.6 57.4 59.3 SST (C) −2 0 2 4 6 8 10 46 68.4 30.9 57.7 75.9 32.4 57.9 83.9 33.8 58.3 92.0 35.3 58.6 100.4 36.7 59.0 109.1 38.0 59.6 117.9 39.3 60.1 49 63.8 31.2 60.7 71.1 32.9 60.9 78.9 34.4 61.1 86.8 36.0 61.5 95.1 37.5 61.9 103.5 39.0 62.4 112.2 40.5 62.9 52 59.2 31.3 63.6 66.4 33.1 63.7 73.9 34.9 64.0 81.7 36.6 64.4 89.7 38.3 64.8 98.0* 39.9* 65.3* 106.5* 41.5* 65.8* 49 77.4 37.6 63.3 85.4 39.6 63.5 94.1 41.5 63.6 103.0 43.4 63.9 112.3 45.1 64.2 122.0 47.0 64.7 132.0* 48.8* 65.2* 52 72.6* 38.0* 66.3* 80.4* 40.1* 66.4* 88.8* 42.2* 66.6* 97.4* 44.1* 66.9* 106.5* 46.1* 67.2* 116.0* 48.0* 67.5* 125.5* 50.0* 68.0* 49 97.0 46.0 62.1 106.4 48.2 62.3 116.4 50.4 62.7 126.7 52.6 63.1 137.3 54.7 63.6 148.4 57.0 64.2 159.6 59.1 64.8 52 91.6 46.5 65.1 100.7 48.9 65.2 110.5 51.2 65.6 120.5 53.5 66.0 130.8* 55.9* 66.4* 141.6* 58.2* 67.0* 152.5* 60.5* 67.6* 38AH054 SST (C) −2 0 2 4 6 8 10 46 82.2 37.3 60.3 90.4 39.1 60.5 99.4 40.7 60.7 108.5 42.4 61.0 118.1 44.2 61.3 128.2 45.9 61.8 138.3 47.5 62.3 38AH064 SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG — — — — LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 46 102.3 45.4 59.2 112.1 47.4 59.3 122.4 49.5 59.8 133.0 51.5 60.2 143.8 53.5 60.7 155.2 55.6 61.4 166.8 57.6 62.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 59 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — SI (cont) 38AH074 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 181.6 45.2 34.1 194.7 46.5 34.6 209.1 47.8 35.3 224.6 49.1 36.0 239.0 50.4 36.8 257.0 51.6 37.6 273.0 52.8 38.5 27 169.2 48.7 39.8 182.1 50.2 40.3 196.3 51.8 41.0 210.5 53.4 41.6 225.1 55.0 42.4 241.0 56.6 43.2 257.0 58.3 44.0 30 163.2 50.2 42.8 176.1 51.9 43.2 189.3 53.7 43.8 203.5 55.4 44.4 217.9 57.2 45.2 234.0 59.0 45.9 248.0 60.7 46.8 32 159.1 51.1 44.7 171.9 53.0 45.0 185.3 54.8 45.7 199.4 56.7 46.3 212.8 58.5 47.0 228.4 60.4 47.8 243.0 62.3 48.6 Air Temperature 35 153.1 52.4 47.6 165.6 54.5 47.9 178.4 56.5 48.5 192.4 58.4 49.1 205.6 60.5 49.8 221.0 62.6 50.6 236.0 64.6 51.4 Entering Condenser (C) 38 41 43 147.1 141.0 137.0 53.8 54.9 55.6 50.5 53.5 55.4 159.3 153.0 148.8 55.9 57.2 57.9 50.8 53.7 55.6 172.1 165.5 161.2 58.1 59.5 60.4 51.3 54.1 56.1 185.2 178.1 173.8 60.2 61.7 62.7 51.9 54.7 56.6 198.3 192.1 186.9 62.4 64.0 65.1 52.6 55.4 57.3 212.6 205.2 200.0 64.5 66.5 67.6 53.3 56.1 57.9 227.1 219.5 214.1 66.8 68.8 70.1 54.1 56.9 58.7 46 131.0 56.6 58.4 142.5 59.1 58.5 154.6 61.6 58.9 166.9 64.2 59.4 179.6 66.7 60.0 192.5 69.4 60.7 206.6 71.9 61.5 49 125.0 57.4 61.3 136.2 60.1 61.4 148.1 62.8 61.8 160.1 65.4 62.2 172.5 68.1 62.8 185.1 71.0 63.5 198.0 73.7 64.2 52 118.9 58.1 64.3 129.8 61.0 64.4 141.4 63.8 64.7 153.2 66.6 65.1 165.3 69.5 65.6 177.6* 72.4* 66.2* 190.4* 75.3* 66.9* TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 204.0 54.1 36.2 221.0 55.6 36.3 238.0 57.0 36.7 256.0 58.5 37.1 274.0 60.0 37.7 294.0 61.6 38.4 314.0 63.2 39.2 27 190.6 57.9 42.2 206.0 59.7 42.3 223.0 61.5 42.6 240.0 63.3 42.9 258.0 65.1 43.4 276.0 67.1 44.1 294.0 69.1 44.8 30 183.9 59.5 45.2 198.9 61.5 45.3 215.0 63.5 45.5 232.0 65.5 45.8 250.0 67.5 46.3 268.0 69.7 46.9 286.0 71.7 47.6 32 179.3 60.6 47.2 194.2 62.7 47.3 210.0 64.9 47.5 226.0 66.9 47.8 244.0 69.1 48.2 262.0 71.3 48.8 280.0 73.5 49.5 Air Temperature 35 172.7 62.1 50.2 187.1 64.4 50.3 203.0 66.7 50.4 219.0 68.9 50.7 236.0 71.3 51.1 252.0 73.7 51.7 270.0 76.1 52.3 Entering Condenser (C) 38 41 43 166.1 159.6 155.3 63.4 64.8 65.5 53.1 56.2 58.2 180.1 173.2 168.6 65.9 67.3 68.2 53.2 56.2 58.2 195.3 187.9 183.1 68.3 69.9 70.9 53.4 56.4 58.4 211.0 203.0 197.9 70.9 72.7 73.7 53.6 56.6 58.6 227.0 219.0 214.0 73.3 75.3 76.5 54.1 57.0 58.9 244.0 236.0 230.0 75.9 78.0 79.3 54.5 57.4 59.4 261.0 252.0 246.0 78.5 80.7 82.1 55.2 58.0 59.9 46 148.9 66.6 61.2 161.7 69.6 61.2 175.7 72.4 61.4 190.1 75.3 61.5 205.0 78.3 61.9 221.0 81.3 62.3 236.0 84.3 62.7 49 142.5 67.7 64.2 154.9 70.8 64.2 168.5 73.8 64.3 182.5 76.9 63.5 197.0 79.9 64.8 212.0 83.1 65.2 228.0 86.3 65.6 52 136.2* 68.6* 67.2* 148.2* 71.8* 67.2* 161.3* 75.0* 67.3* 174.9* 78.2* 67.4* 189.0* 81.5* 67.7* 204.0* 84.8* 68.1* 219.0* 88.1* 68.5* SST (C) −2 0 2 4 6 8 10 38AH084 SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG 60 — — — — LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT RATINGS — SI (cont) 38AH094 SST (C) −2 0 2 4 6 8 10 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 21 233.0 58.1 35.5 33.8 33.6 32.3 251.0 59.7 36.2 34.2 34.0 32.4 269.0 61.5 37.1 34.9 34.6 32.8 289.0 63.3 38.0 35.6 35.2 33.3 309.0 65.1 39.0 36.4 35.8 33.8 329.0 66.9 40.1 37.3 36.5 34.3 350.0 68.7 41.1 38.2 37.2 34.9 27 216.5 62.3 41.2 39.6 39.7 38.5 234.0 64.3 41.8 39.9 40.1 38.6 252.0 66.5 42.6 40.5 40.6 39.0 270.0 68.6 43.5 41.2 41.2 39.4 290.0 70.8 44.4 41.9 41.9 39.9 309.0 73.0 45.4 42.7 42.6 40.4 329.0 75.2 46.4 43.6 43.3 41.0 30 209.1 64.3 44.0 42.5 42.8 41.5 226.0 66.6 44.5 42.8 43.1 41.7 243.0 68.9 45.3 43.4 43.7 42.0 261.0 71.3 46.2 44.0 44.3 42.4 279.0 73.6 47.1 44.7 44.9 42.9 299.0 76.0 48.0 45.5 45.6 43.5 319.0 78.4 49.1 46.3 46.4 44.1 32 202.9 65.6 45.9 44.5 44.8 43.6 220.2 67.9 46.4 44.8 45.1 43.7 237.0 70.4 47.2 45.3 45.7 44.0 255.0 72.9 48.0 45.9 46.3 44.4 274.0 75.4 48.9 46.5 46.9 44.9 292.0 77.9 49.8 47.3 47.6 45.5 312.0 80.5 50.8 48.2 48.4 46.1 Air Temperature 35 195.6 67.4 48.8 47.4 47.8 46.7 211.7 69.9 49.2 47.7 48.1 46.8 228.0 72.5 49.9 48.2 48.6 47.1 246.0 75.2 50.7 48.7 49.2 47.4 264.0 77.9 51.6 49.3 49.9 47.9 282.0 80.6 52.5 50.1 50.6 48.4 301.0 83.3 53.5 50.9 51.3 49.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (kW) Entering Condenser (C) 38 41 43 187.3 178.7 173.1 68.9 70.3 71.1 51.6 54.5 56.5 50.4 53.4 55.4 50.8 53.9 55.9 49.7 52.8 54.8 203.3 194.8 188.5 71.7 73.3 74.2 52.0 54.9 56.8 50.6 53.5 55.5 51.1 54.1 56.0 49.8 52.8 54.8 219.6 211.0 204.6 74.4 76.2 77.4 52.7 55.5 57.4 51.0 53.9 55.9 51.6 54.5 56.5 50.1 53.1 55.1 237.0 227.0 221.7 77.2 79.3 80.5 53.4 56.2 58.0 51.5 54.4 56.3 52.1 55.0 57.0 50.4 53.4 55.4 254.0 245.0 238.0 80.2 82.4 83.7 54.3 57.0 58.8 52.1 55.0 56.9 52.8 55.7 57.6 50.9 53.8 55.8 273.0 263.0 256.0 83.1 85.5 87.0 55.2 57.9 59.6 52.9 55.7 57.5 53.5 56.4 58.3 51.4 54.4 56.3 291.0 281.0 274.0 86.0 88.7 90.3 56.2 58.8 60.5 53.7 56.4 58.3 54.2 57.1 59.0 52.0 54.9 56.9 46 164.8 72.2 59.4 58.3 58.9 57.9 180.0 75.6 59.6 58.4 59.0 57.9 196.0 78.9 60.2 58.8 59.4 58.1 211.9 82.3 60.8 59.2 59.9 58.4 228.0 85.6 61.5 59.7 60.5 58.8 246.0 89.1 62.3 60.3 61.1 59.3 263.0 92.5 63.2 61.0 61.8 59.8 49 156.5 73.2 62.3 61.3 61.9 60.9 171.4 76.7 62.5 61.4 62.0 60.9 186.4 80.2 63.0 61.7 62.3 61.1 202.2 83.8 63.5 62.1 62.7 61.3 219.2 87.5 64.2 62.5 63.3 61.7 235.0 91.0 65.0 63.1 64.0 62.2 253.0 94.7 65.9 63.8 64.7 62.7 52 148.2 73.9 65.3 64.3 64.9 63.9 162.7 77.7 65.4 64.4 64.9 63.9 177.9 81.5 65.8 64.6 65.3 64.1 193.4 85.2 66.3 65.0 65.6 64.3 209.3 89.1 66.9 65.4 66.2 64.7 225.0 92.9 67.7* 66.0 66.8 65.1 242.0 96.8 68.5* 66.6 67.5* 65.6 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 61 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — SI (cont) 38AH104 SST (C) −2 0 2 4 6 8 10 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 21 265.0 62.8 34.4 35.7 32.6 33.5 285.0 64.9 35.1 36.5 33.1 34.0 307.0 66.9 36.0 37.5 33.6 34.7 328.0 68.9 36.9 38.5 34.2 35.3 351.0 71.0 37.9 39.6 34.8 36.0 375.0 73.1 38.9 40.7 35.5 36.7 400.0 75.4 39.9 41.9 36.2 37.5 27 245.0 67.7 40.0 41.2 38.6 39.5 264.0 70.1 40.6 41.9 39.1 40.0 285.0 72.6 41.4 42.9 39.6 40.7 306.0 75.0 42.3 43.8 40.2 41.4 328.0 77.5 43.2 44.8 40.8 42.1 351.0 80.0 44.1 45.9 41.5 42.8 374.0 82.6 45.2 47.0 42.2 43.6 30 235.0 70.1 42.8 43.9 41.7 42.6 254.0 72.6 43.4 44.7 42.1 43.1 273.0 75.3 44.1 45.5 42.6 43.7 294.0 78.0 44.9 46.4 43.2 44.4 316.0 80.7 45.8 47.4 43.8 45.1 338.0 83.5 46.8 48.5 44.5 45.8 361.0 86.3 47.8 49.5 45.2 46.6 32 229.0 71.6 44.7 45.8 43.7 44.5 247.0 74.3 45.2 46.5 44.0 45.0 267.0 77.0 46.0 47.3 44.6 45.7 287.0 79.8 46.7 48.2 45.1 46.3 308.0 82.7 47.6 49.2 45.8 47.1 330.0 85.6 48.6 50.2 46.5 47.8 353.0 88.5 49.5 51.3 47.2 48.6 Air Temperature 35 219.0 73.6 47.5 48.6 46.7 47.5 237.0 76.5 48.0 49.2 47.0 48.0 256.0 79.5 48.7 50.0 47.5 48.6 275.0 82.5 49.5 50.9 48.1 49.3 296.0 85.6 50.3 51.8 48.7 50.0 317.0 88.6 51.2 52.8 49.4 50.7 340.0 91.7 52.2 53.9 50.1 51.5 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (kW) 62 Entering Condenser (C) 38 41 43 209.3 199.6 192.4 75.5 77.2 78.3 50.4 53.3 55.2 51.4 54.3 56.2 49.7 52.7 54.6 50.5 53.5 55.5 227.0 217.0 209.8 78.6 80.5 81.8 50.8 53.6 55.5 52.0 54.8 56.7 49.9 52.9 54.9 50.9 53.9 55.8 246.0 235.0 228.0 81.7 84.0 85.3 51.5 54.3 56.1 52.8 55.5 57.4 50.4 53.3 55.3 51.5 54.4 56.4 265.0 254.0 246.0 85.0 87.3 88.8 52.2 54.9 56.7 53.6 56.3 58.1 51.0 53.9 55.8 52.2 55.1 57.0 285.0 273.0 265.0 88.3 90.8 92.4 53.0 55.7 57.5 54.5 57.2 59.0 51.6 54.5 56.4 52.9 55.7 57.7 305.0 294.0 285.0 91.5 94.3 96.1 53.9 56.6 58.4 55.5 58.1 59.9 52.3 55.1 57.1 53.6 56.5 58.4 327.0 313.0 305.0 94.9 97.8 99.7 54.8 57.4 59.2 56.5 59.1 60.8 53.0 55.8 57.8 54.4 57.3 59.2 46 183.1 79.7 58.1 59.1 57.7 58.5 199.8 83.4 58.4 59.5 57.8 58.8 217.0 87.1 58.9 60.1 58.2 59.3 235.0 90.9 59.5 60.8 58.7 59.8 254.0 94.7 60.2 61.7 59.2 60.5 273.0 98.6 61.0 62.6 59.9 61.2 292.0 102.4 61.9 63.5 60.6 62.0 49 173.6 81.0 61.1 61.9 60.7 61.4 190.0 84.9 61.3 62.3 60.8 61.7 207.3 88.8 61.7 62.9 61.1 62.2 225.0 92.8 62.3 63.6 61.5 62.7 242.0 96.8 63.0 64.4 62.1 63.4 261.0 100.8 63.7 65.2 62.7 64.1 281.0 105.0 64.5 66.1 63.4 64.8 52 164.2 82.1 64.0 64.9 63.7 64.4 180.1 86.2 64.1 65.2 63.7 64.6 197.2 90.4 64.6 65.7 64.0 65.1 213.4 94.5 65.1 66.3 64.4 65.6 231.0 98.8 65.7 67.1* 64.9 66.2 250.0 103.0 66.4 67.9* 65.5 66.9 268.0 107.4 67.2 68.7* 66.2 67.6* *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT RATINGS — SI (cont) 38AH124 SST (C) −2 0 2 4 6 8 10 TCG CMP SDT(A OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) TCG CMP SDT(A) OR (B) SCT(A) OR (B) 21 298.0 71.4 34.7 33.9 322.0 73.4 35.2 34.3 346.0 75.2 35.8 34.7 372.0 77.0 36.5 35.3 400.0 78.8 37.2 35.9 428.0 80.6 38.1 36.6 456.0 82.6 39.0 37.3 27 276.0 77.2 40.5 39.9 298.0 79.6 40.9 40.2 322.0 82.0 41.5 40.7 348.0 84.2 42.1 41.2 372.0 86.6 42.9 41.8 400.0 89.2 43.7 42.4 426.0 91.6 44.5 43.1 30 264.0 80.0 43.4 42.9 286.0 82.6 43.8 43.2 310.0 85.2 44.4 43.6 334.0 88.0 45.0 44.1 360.0 90.6 45.7 44.7 386.0 93.2 46.5 45.3 412.0 96.0 47.3 46.0 32 258.0 81.6 45.4 44.9 280.0 84.4 45.8 45.2 302.0 87.4 46.3 45.6 326.0 90.2 46.9 46.1 350.0 93.0 47.6 46.6 376.0 95.8 48.3 47.3 402.0 98.8 49.1 48.0 Air Temperature 35 246.0 84.0 48.3 47.9 268.0 87.2 48.7 48.1 290.0 90.2 49.2 48.5 314.0 93.2 49.7 49.0 338.0 96.4 50.4 49.5 362.0 99.6 51.1 50.2 388.0 102.6 51.9 50.8 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (kW) Entering Condenser (C) 38 41 43 236.0 224.0 218.0 86.2 88.0 89.0 51.3 54.2 56.2 50.9 53.8 55.9 256.0 244.0 238.0 89.4 91.6 92.8 51.6 54.4 56.4 51.1 54.0 56.0 278.0 266.0 258.0 92.8 95.2 96.8 52.0 54.9 56.8 51.5 54.4 56.4 300.0 288.0 280.0 96.2 99.0 100.6 52.6 55.4 57.3 51.9 54.8 56.8 324.0 310.0 302.0 99.6 102.6 104.4 53.2 56.0 57.9 52.5 55.4 57.3 348.0 334.0 326.0 103.0 106.2 108.2 53.9 56.7 58.6 53.1 55.9 57.9 374.0 358.0 350.0 106.4 110.0 112.2 54.7 57.4 59.3 53.7 56.6 58.5 46 206.0 90.8 59.1 58.9 226.0 94.8 59.4 59.0 246.0 99.0 59.7 59.3 268.0 103.0 60.2 59.7 290.0 107.2 60.7 60.2 312.0 111.2 61.4 60.7 334.0 115.4 62.1 61.3 49 195.6 92.0 62.1 61.9 214.0 96.4 62.3 62.0 234.0 100.8 62.7 62.3 254.0 105.2 63.1 62.6 276.0 109.6 63.6 63.1 298.0 114.0 64.2 63.6 320.0 118.4 64.8 64.2 52 185.0 93.2 65.1 64.8 204.0 97.8 65.2 65.0 222.0 102.4 65.6 65.2 242.0 107.2 65.9 65.5 264.0 111.8 66.4 66.0 284.0 116.4 67.0 66.5 306.0 121.2 67.6 67.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 63 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — SI (cont) 38AH134 SST (C) −2 0 2 4 6 8 10 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 21 330.0 80.9 34.7 34.0 33.9 31.9 356.0 83.2 35.2 34.5 34.3 32.4 383.0 85.4 35.8 35.2 34.7 33.0 410.0 87.5 36.5 36.0 35.3 33.6 440.0 89.7 37.2 36.7 35.9 34.3 470.0 91.8 38.1 37.6 36.6 34.9 501.0 94.1 39.0 38.4 37.3 35.6 27 307.0 87.2 40.5 39.8 39.9 37.7 331.0 90.0 40.9 40.2 40.2 38.2 357.0 92.8 41.5 40.9 40.7 38.8 385.0 95.5 42.1 41.6 41.2 39.5 412.0 98.3 42.9 42.3 41.8 40.1 441.0 101.2 43.7 43.1 42.4 40.7 470.0 104.0 44.5 44.0 43.1 41.4 30 295.0 90.1 43.4 42.7 42.9 40.7 319.0 93.1 43.8 43.1 43.2 41.2 345.0 96.2 44.4 43.7 43.6 41.7 371.0 99.4 45.0 44.4 44.1 42.3 398.0 102.4 45.7 45.1 44.7 43.0 426.0 105.5 46.5 45.9 45.3 43.6 455.0 108.7 47.3 46.7 46.0 44.3 32 288.0 91.9 45.4 44.6 44.9 42.6 312.0 95.1 45.8 45.0 45.2 43.1 336.0 98.5 46.3 45.6 45.6 43.7 362.0 101.7 46.9 46.3 46.1 44.3 388.0 105.0 47.6 47.0 46.6 44.9 416.0 108.3 48.3 47.8 47.3 45.5 445.0 111.6 49.1 48.6 48.0 46.2 Air Temperature 35 276.0 94.5 48.3 47.5 47.9 45.5 300.0 98.0 48.7 47.8 48.1 46.0 324.0 101.5 49.2 48.4 48.5 46.5 349.0 105.1 49.7 49.1 49.0 47.1 375.0 108.7 50.4 49.8 49.5 47.7 402.0 112.3 51.1 50.5 50.2 48.4 430.0 115.9 51.9 51.3 50.8 49.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (C) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (C) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (kW) 64 Entering Condenser (C) 38 41 43 265.0 253.0 246.0 96.9 98.9 100.1 51.3 54.2 56.2 50.4 53.4 55.4 50.9 53.8 55.9 48.5 51.4 53.4 287.0 275.0 268.0 100.5 102.9 104.3 51.6 54.4 56.4 50.7 53.6 55.5 51.1 54.0 56.0 48.9 51.7 53.6 311.0 299.0 290.0 104.4 107.0 108.7 52.0 54.9 56.8 51.3 54.1 56.0 51.5 54.4 56.4 49.4 52.3 54.2 335.0 323.0 314.0 108.2 111.2 113.0 52.6 55.4 57.3 51.9 54.7 56.5 51.9 54.8 56.8 50.0 52.8 54.7 361.0 347.0 338.0 112.1 115.4 117.3 53.2 56.0 57.9 52.6 55.3 57.2 52.5 55.4 57.3 50.6 53.4 55.3 387.0 373.0 364.0 116.0 119.5 121.7 53.9 56.7 58.6 53.3 56.1 57.9 53.1 55.9 57.9 51.2 54.0 55.9 415.0 399.0 390.0 119.9 123.8 126.1 54.7 57.4 59.3 54.1 56.8 58.7 53.7 56.6 58.5 51.8 54.7 56.5 46 234.0 102.0 59.1 58.3 58.9 56.3 256.0 106.5 59.4 58.4 59.0 56.5 278.0 111.1 59.7 58.9 59.3 57.0 301.0 115.6 60.2 59.3 59.7 57.5 325.0 120.3 60.7 60.0 60.2 58.1 349.0 124.9 61.4 60.7 60.7 58.7 374.0 129.6 62.1 61.4 61.3 59.3 49 222.8 103.4 62.1 61.3 61.9 59.3 243.0 108.3 62.3 61.4 62.0 59.4 265.0 113.1 62.7 61.8 62.3 59.9 287.0 118.0 63.1 62.2 62.6 60.3 311.0 122.9 63.6 62.8 63.1 60.9 335.0 127.9 64.2 63.4 63.6 61.5 359.0 132.9 64.8 64.2 64.2 62.1 52 211.5 104.8 65.1 64.3 64.8 62.2 232.0 109.9 65.2 64.3 65.0 62.4 253.0 114.9 65.6 64.6 65.2 62.7 274.0 120.1 65.9 65.0 65.5 63.1 297.0 125.3 66.4 65.5 66.0 63.7 320.0 130.6 67.0 66.2 66.5 64.2 344.0 135.9 67.6* 66.9 67.0 64.8 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI 38AH044 CIRCUIT A SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT SCG CMP SDT TCG CMP SDT TCG CMP SDT 21 52.7 12.0 32.8 56.9 12.3 33.4 61.4 12.5 34.0 66.0 12.8 34.7 70.8 13.1 35.5 75.8 13.4 36.3 80.9 13.7 37.1 27 48.5 13.0 38.5 52.6 13.4 39.0 56.9 13.8 39.6 61.4 14.2 40.3 66.0 14.5 41.0 70.8 14.9 41.8 75.7 15.3 42.6 30 46.4 13.5 41.3 50.4 14.0 41.8 54.6 14.4 42.4 59.0 14.8 43.0 63.5 15.2 43.8 68.3 15.6 44.5 73.1 16.0 45.3 32 44.9 13.8 43.2 48.9 14.3 43.7 53.1 14.8 44.3 57.4 15.2 44.9 61.9 15.7 45.6 66.5 16.1 46.4 71.3 16.5 47.1 Air Temperature 35 42.7 14.3 46.1 46.7 14.8 46.5 50.8 15.3 47.1 55.0 15.8 47.7 59.4 16.3 48.4 63.9 16.8 49.1 68.6 17.3 49.9 Entering Condenser (C) 38 41 43 40.5 38.3 36.8 14.6 15.0 15.1 49.0 51.9 53.8 44.4 42.1 40.5 15.2 15.6 15.8 49.4 52.2 54.2 48.4 46.1 44.5 15.8 16.2 16.5 49.9 52.7 54.6 52.6 50.1 48.5 16.3 16.8 17.1 50.5 53.3 55.1 56.9 54.3 52.6 16.9 17.4 17.8 51.1 53.9 55.8 61.3 58.7 56.9 17.4 18.0 18.4 51.8 54.6 56.4 65.9 63.1 61.3 18.0 18.6 19.0 52.6 55.3 57.1 21 53.0 12.4 35.0 57.6 12.6 35.1 62.5 12.8 35.3 67.5 13.0 35.6 72.6 13.3 36.0 77.9 13.5 36.6 83.2 13.7 37.3 27 48.7 13.5 41.0 53.1 13.8 41.0 57.8 14.1 41.2 62.7 14.4 41.4 67.7 14.7 41.8 72.8 15.0 42.3 78.0 15.3 42.8 30 46.4 13.9 44.0 50.8 14.4 44.1 55.4 14.7 44.2 60.2 15.1 44.3 65.1 15.4 44.7 70.2 15.8 45.1 75.3 16.1 45.6 32 44.9 14.2 46.0 49.2 14.7 46.0 53.8 15.1 46.1 58.5 15.5 46.3 63.4 15.9 46.6 68.4 16.3 47.0 73.5 16.6 47.5 Air Temperature 35 42.7 14.6 49.0 46.8 15.2 49.0 51.4 15.6 49.1 56.0 16.1 49.2 60.8 16.5 49.5 65.7 17.0 49.9 70.8 17.4 50.3 Entering Condenser (C) 38 41 43 40.4 38.1 36.5 15.0 15.2 15.4 52.0 55.0 57.0 44.5 42.1 40.5 15.6 15.9 16.1 52.0 55.0 57.0 48.9 46.4 44.8 16.1 16.5 16.8 52.1 55.1 57.1 53.5 50.9 49.1 16.6 17.1 17.4 52.2 55.1 57.1 58.2 55.5 53.7 17.1 17.7 18.0 52.4 55.3 57.3 63.0 60.3 58.4 17.6 18.2 18.6 52.7 55.6 57.6 68.0 65.1 63.2 18.1 18.8 19.2 53.2 56.0 57.9 46 34.5 15.4 56.7 38.2 16.1 57.0 42.1 16.8 57.5 46.0 17.6 57.9 50.1 18.3 58.5 54.3 18.9 59.2 58.5 19.6 59.9 49 32.2 15.6 59.7 35.8 16.4 59.9 39.6 17.1 60.3 43.5 17.9 60.8 47.5 18.7 61.3 51.6 19.4 61.9 55.8 20.2 62.6 52 29.9 15.6 62.6 33.5 16.5 62.7 37.2 17.4 63.1 41.0 18.2 63.6 44.9 19.1 64.1 48.9* 19.9* 64.7* 53.0* 20.7* 65.3* 49 31.9 15.6 63.0 35.6 16.5 63.0 39.7 17.4 63.0 43.9 18.2 63.1 48.3 18.9 63.2 52.8 19.7 63.4 57.5* 20.4* 63.7* 52 29.5* 15.6* 66.0* 33.2* 16.6* 66.0* 37.2* 17.6* 66.0* 41.2* 18.4* 66.1* 45.5* 19.3* 66.2* 50.0* 20.1* 66.3* 54.5* 20.9* 66.5* 49 45.8 21.9 62.2 50.1 22.9 62.5 54.8 23.9 62.8 59.6 24.9 63.2 64.6 25.9 63.8 69.8 27.0 64.4 75.1 28.0 65.1 52 43.3 22.2 65.1 47.5 23.3 65.3 52.1 24.3 65.7 56.7 25.4 66.1 61.5* 26.5* 66.6* 66.6* 27.6* 67.2* 71.7* 28.7* 67.9* 38AH054 CIRCUIT A SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TDG CMP SDT TCG CMP SDT TCG CMP SDT 46 34.2 15.6 60.0 38.0 16.4 60.0 42.2 17.1 60.0 46.5 17.8 60.1 51.0 18.5 60.2 55.7 19.2 60.5 60.4 19.8 60.8 38AH064 CIRCUIT A SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 70.7 16.7 34.9 76.4 17.2 35.4 82.5 17.7 36.1 88.8 18.1 36.8 95.4 18.6 37.7 102.0 19.1 38.6 109.0 19.6 39.5 27 65.0 18.1 40.7 70.5 18.7 41.1 76.3 19.3 41.7 82.3 19.9 42.4 88.5 20.5 43.2 94.9 21.1 44.1 102.0 21.7 44.9 30 62.3 18.8 43.6 67.5 19.4 44.0 73.2 20.1 44.6 79.0 20.7 45.2 85.1 21.4 46.0 91.4 22.0 46.8 97.8 22.7 47.7 LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 32 60.4 19.2 45.5 65.7 19.9 45.9 71.2 20.5 46.5 76.9 21.2 47.1 82.8 21.9 47.8 89.0 22.6 48.6 95.3 23.4 49.5 Air Temperature Entering Condenser (C) 35 38 41 57.7 55.1 52.5 19.8 20.3 20.8 48.4 51.4 54.3 62.8 60.0 57.3 20.5 21.1 21.6 48.8 51.7 54.6 68.2 65.3 62.4 21.2 21.9 22.5 49.3 52.2 55.1 73.8 70.7 67.6 22.0 22.7 23.3 49.9 52.8 55.6 79.5 76.2 73.0 22.8 23.5 24.2 50.6 53.4 56.2 85.5 82.1 78.7 23.5 24.3 25.1 51.4 54.2 57.0 91.7 88.0 84.5 24.3 25.2 26.0 52.2 55.0 57.7 43 50.8 21.1 56.3 55.5 21.9 56.5 60.5 22.8 57.0 65.6 23.7 57.5 70.9 24.7 58.1 76.5 25.6 58.8 82.1 26.5 59.6 46 48.2 21.5 59.2 52.8 22.4 59.4 57.6 23.4 59.9 62.6 24.4 60.3 67.7 25.3 60.9 73.1 26.3 61.6 78.6 27.3 62.3 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 65 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH044 CIRCUIT B SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 52.8 12.2 33.8 57.3 12.4 34.0 62.2 12.6 34.3 67.1 12.8 34.7 72.3 13.0 35.1 77.7 13.2 35.5 83.2 13.3 36.0 27 48.4 13.3 39.8 52.8 13.6 40.0 57.4 13.9 40.2 62.2 14.2 40.6 67.1 14.5 41.0 72.3 14.8 41.4 77.6 15.1 41.9 21 70.0 17.1 36.4 75.7 17.6 36.9 81.7 18.1 37.6 87.9 18.6 38.4 94.4 19.2 39.2 101.0 19.7 40.2 108.0 20.2 41.1 27 64.5 18.5 42.1 69.9 19.1 42.6 75.6 19.7 43.2 81.5 20.3 43.9 87.6 21.0 44.7 94.0 21.6 45.6 101.0 22.3 46.5 30 46.2 13.8 42.8 50.4 14.2 42.9 55.0 14.5 43.2 59.7 14.9 43.5 64.5 15.3 43.9 69.6 15.6 44.4 74.8 15.9 44.8 32 44.7 14.1 44.8 48.9 14.5 44.9 53.4 14.9 45.2 58.0 15.3 45.5 62.8 15.7 45.8 67.8 16.1 46.3 72.9 16.4 46.8 Air Temperature 35 42.4 14.5 47.7 46.5 15.0 47.9 50.9 15.5 48.2 55.4 15.9 48.4 60.1 16.4 48.8 65.0 16.8 49.2 70.0 17.2 49.7 Entering Condenser (C) 38 41 43 40.1 37.8 36.3 14.8 15.1 15.3 50.7 53.7 55.7 44.2 41.8 40.2 15.4 15.8 16.0 50.9 53.8 55.8 48.5 46.0 44.3 16.0 16.4 16.6 51.1 54.0 56.0 52.9 50.3 48.6 16.5 17.0 17.3 51.4 54.3 56.3 57.5 54.8 53.0 17.0 17.6 17.9 51.7 54.6 56.6 62.3 59.5 57.6 17.5 18.1 18.5 52.1 55.0 57.0 67.1 64.2 62.3 18.0 18.6 19.1 52.6 55.5 57.4 46 33.9 15.5 58.7 37.7 16.3 58.8 41.8 17.0 59.0 46.0 17.7 59.2 50.3 18.4 59.5 54.8 19.1 59.9 59.4 19.7 60.3 49 31.6 15.6 61.6 35.3 16.5 61.8 39.3 17.3 61.9 43.3 18.1 62.2 47.6 18.8 62.5 51.9 19.6 62.8 56.4 20.3 63.2 52 29.3 15.7 64.6 32.9 16.6 64.7 36.7 17.5 64.9 40.7 18.4 65.1 44.8 19.2 65.4 49.1* 20.0* 65.8* 53.5* 20.8* 66.1* Air Temperature Entering Condenser (C) 35 38 41 43 57.3 54.7 52.1 50.5 20.0 20.5 21.0 21.3 49.9 52.8 55.7 57.7 62.3 59.5 56.8 55.1 20.8 21.4 21.9 22.2 50.2 53.1 56.0 58.0 67.6 64.7 61.9 60.0 21.6 22.2 22.8 23.1 50.8 53.7 56.5 58.5 73.1 70.0 67.0 65.0 22.4 23.0 23.7 24.1 51.4 54.3 57.1 59.0 78.8 75.6 72.4 70.3 23.2 23.9 24.6 25.0 52.1 54.9 57.7 59.6 84.8 81.4 78.0 75.8 24.0 24.8 25.5 26.0 52.9 55.7 58.4 60.3 90.8 87.2 83.7 81.4 24.8 25.6 26.4 26.9 53.7 56.4 59.2 61.0 46 48.0 21.7 60.6 52.4 22.7 60.9 57.2 23.6 61.3 62.0 24.6 61.8 67.1 25.7 62.4 72.5 26.7 63.1 77.9 27.7 63.8 49 45.5 22.0 63.6 49.8 23.1 63.9 54.4 24.1 64.2 59.1 25.2 64.7 64.0 26.2 65.2 69.2 27.3 65.9 74.5* 28.4* 66.6* 52 43.1* 22.4* 66.5* 47.2* 23.5* 66.8* 51.6* 24.6* 67.2* 56.2 25.7* 67.6* 61.0* 26.8* 68.1 66.0* 27.9* 68.7* 71.0* 29.1* 69.4* 49 51.2 24.1 62.0 56.3 25.3 62.2 61.6 26.5 62.5 67.1 27.7 62.9 72.7 28.8 63.3 78.6 30.0 63.9 84.5 31.1 64.5 52 48.3 24.3 65.0 53.2 25.6 65.1 58.4 26.9 65.4 63.8 28.1 65.8 69.3* 29.4* 66.2* 75.0* 30.6* 66.7* 80.8* 31.8* 67.3* 38AH054 CIRCUIT B SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 30 61.7 19.1 45.0 67.0 19.8 45.5 72.6 20.4 46.1 78.3 21.1 46.7 84.3 21.8 47.5 90.5 22.5 48.3 96.9 23.2 49.2 32 60.0 19.5 47.0 65.1 20.2 47.4 70.6 20.9 48.0 76.2 21.6 48.6 82.1 22.4 49.3 88.2 23.1 50.1 94.5 23.9 51.0 38AH064 CIRCUIT B SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG 66 — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 77.8 19.0 34.5 83.9 19.4 34.8 90.4 19.8 35.3 97.0 20.3 35.9 104.0 20.7 36.6 111.0 21.1 37.4 118.0 21.5 38.2 27 72.2 20.5 40.3 78.1 21.1 40.7 84.4 21.7 41.2 90.8 22.3 41.7 97.4 22.9 42.4 104.0 23.4 43.1 111.0 24.0 43.9 30 69.4 21.2 43.3 75.2 21.9 43.6 81.4 22.5 44.0 87.6 23.2 44.6 94.1 23.9 45.2 101.0 24.5 45.9 108.0 25.2 46.7 Air Temperature Entering Condenser (C) 32 35 38 41 67.5 64.7 61.8 58.9 21.6 22.2 22.8 23.2 45.3 48.2 51.2 54.1 73.2 70.3 67.3 64.3 22.4 23.0 23.7 24.2 45.5 48.4 51.4 54.3 79.3 76.2 73.1 70.0 23.1 23.8 24.5 25.1 46.0 48.9 51.8 54.7 85.5 82.3 79.1 75.8 23.8 24.6 25.4 26.1 46.5 49.4 52.3 55.2 91.9 88.6 85.2 81.8 24.5 25.4 26.2 27.0 47.1 50.0 52.9 55.7 98.5 95.1 91.6 88.0 25.2 26.2 27.1 28.0 47.8 50.7 53.5 56.3 105.0 102.0 98.0 94.4 25.9 27.0 28.0 28.9 48.6 51.4 54.2 57.0 LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 43 57.0 23.5 56.1 62.3 24.5 56.3 67.9 25.5 56.7 73.6 26.5 57.1 79.6 27.5 57.6 85.7 28.5 58.2 91.9 29.5 58.9 46 54.1 23.9 59.1 59.3 25.0 59.2 64.8 26.1 59.6 70.4 27.1 60.0 76.1 28.2 60.4 82.1 29.3 61.1 88.2 30.3 61.7 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH074 CIRCUIT A SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 78.6 18.8 33.9 84.7 19.3 34.4 91.1 19.7 35.0 97.6 20.2 35.7 104.0 20.6 36.4 112.0 21.0 37.2 119.0 21.4 38.0 27 73.2 20.4 39.7 79.1 20.9 40.1 85.3 21.5 40.7 91.5 22.1 41.3 98.1 22.7 42.0 105.0 23.3 42.7 112.0 23.9 43.5 30 70.5 21.1 42.7 76.3 21.7 43.0 82.3 22.4 43.5 88.5 23.0 44.1 94.9 23.7 44.8 102.0 24.4 45.5 108.0 25.0 46.3 Air Temperature Entering Condenser (C) 32 35 38 41 68.6 65.8 63.0 60.1 21.5 22.1 22.7 23.1 44.6 47.6 50.5 53.5 74.4 71.5 68.6 65.6 22.2 22.9 23.5 24.1 44.8 47.7 50.7 53.6 80.3 77.4 74.3 71.3 22.9 23.7 24.4 25.0 45.4 48.2 51.1 53.9 86.4 83.4 80.2 77.1 23.6 24.4 25.2 25.9 46.0 48.8 51.6 54.4 92.8 89.6 86.3 83.1 24.3 25.2 26.1 26.8 46.6 49.4 52.2 55.0 99.4 96.0 92.6 89.2 25.0 26.0 26.9 27.8 47.4 50.2 52.9 55.7 106.0 103.0 99.1 95.5 25.7 26.8 27.8 28.7 48.1 50.9 53.6 56.4 43 58.2 23.4 55.5 63.6 24.4 55.5 69.3 25.4 55.9 75.0 26.3 56.3 80.9 27.3 56.9 87.0 28.3 57.5 93.1 29.3 58.2 46 55.3 23.8 58.5 60.6 24.9 58.5 66.2 25.9 58.7 71.8 27.0 59.1 77.6 28.0 59.6 83.5 29.1 60.3 89.6 30.1 61.0 49 52.4 24.1 61.4 57.6 25.3 61.4 63.1 26.4 61.6 68.6 27.5 61.9 74.3 28.6 62.4 80.1 29.8 63.0 86.0 30.9 63.7 52 49.5 24.3 64.4 54.5 25.6 64.4 59.9 26.8 64.6 65.4 28.0 64.8 70.9 29.2 65.3 76.6* 30.4* 65.8* 82.4* 31.6* 66.4* 49 71.0 33.9 64.7 77.2 35.5 64.7 84.0 37.0 64.8 91.0 38.6 65.0 98.3 40.1 65.2 106.0 41.7 65.6 114.0* 43.3* 66.0* 52 67.8* 34.4* 67.7* 73.8* 36.0* 67.7* 80.4* 37.6* 67.8* 87.2* 39.2* 67.9* 94.3* 40.9* 68.2* 102.0* 42.5* 68.5* 109.0* 44.2* 68.9* 38AH084 CIRCUIT A SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 102.0 27.2 36.7 110.0 28.0 36.8 119.0 28.7 37.1 128.0 29.4 37.5 137.0 30.2 38.0 147.0 31.0 38.7 157.0 31.8 39.5 27 95.0 29.1 42.7 103.0 30.0 42.8 111.0 30.9 43.0 120.0 31.8 43.3 129.0 32.7 43.8 138.0 33.7 44.4 147.0 34.7 45.1 30 91.7 29.9 45.7 99.2 30.9 45.8 107.0 31.9 46.0 116.0 32.9 46.2 125.0 33.9 46.7 134.0 35.0 47.3 143.0 36.0 47.9 32 89.4 30.4 47.7 96.8 31.5 47.8 105.0 32.6 48.0 113.0 33.6 48.2 122.0 34.7 48.6 131.0 35.8 49.2 140.0 36.9 49.8 LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) Air Temperature 35 86.1 31.2 50.7 93.3 32.3 50.8 101.0 33.5 50.9 109.0 34.6 51.2 118.0 35.8 51.5 126.0 37.0 52.0 135.0 38.2 52.6 Entering Condenser (C) 38 41 43 82.8 79.5 77.4 31.8 32.5 32.9 53.6 56.7 58.7 89.8 86.3 84.0 33.1 33.8 34.2 53.7 56.7 58.7 97.4 93.7 91.3 34.3 35.1 35.6 53.9 56.9 58.9 105.0 101.0 98.7 35.6 36.5 37.0 54.1 57.1 59.1 113.0 109.0 107.0 36.8 37.8 38.4 54.5 57.4 59.4 122.0 118.0 115.0 38.1 39.1 39.8 54.9 57.8 59.8 130.0 126.0 123.0 39.4 40.5 41.2 55.5 58.3 60.3 46 74.2 33.4 61.7 80.6 34.9 61.7 87.6 36.3 61.9 94.8 37.8 62.0 102.0 39.3 62.3 110.0 40.8 62.7 118.0 42.3 63.1 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 67 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH074 CIRCUIT B SST (C) −2 0 2 4 6 8 10 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 21 103.0 26.4 34.2 110.0 27.2 34.8 118.0 28.1 35.6 127.0 28.9 36.3 135.0 29.8 37.1 145.0 30.6 38.0 154.0 31.4 38.9 27 96.0 28.3 39.9 103.0 29.3 40.5 111.0 30.3 41.2 119.0 31.3 41.9 127.0 32.3 42.7 136.0 33.3 43.6 145.0 34.4 44.4 30 92.7 29.1 42.8 99.8 30.2 43.3 107.0 31.3 44.0 115.0 32.4 44.7 123.0 33.5 45.5 132.0 34.6 46.3 140.0 35.7 47.2 32 90.5 29.6 44.7 97.5 30.8 45.2 105.0 31.9 45.9 113.0 33.1 46.6 120.0 34.2 47.4 129.0 35.4 48.2 137.0 36.6 49.0 Air Temperature 35 87.3 30.4 47.6 94.1 31.6 48.0 101.0 32.8 48.7 109.0 34.0 49.4 116.0 35.3 50.2 125.0 36.6 51.0 133.0 37.8 51.8 Entering Condenser (C) 38 41 43 84.1 80.9 78.8 31.1 31.8 32.2 50.5 53.4 55.3 90.7 87.4 85.2 32.4 33.1 33.5 50.9 53.7 55.7 97.8 94.2 91.9 33.7 34.5 35.0 51.5 54.3 56.2 105.0 101.0 98.8 35.0 35.8 36.4 52.2 55.0 56.9 112.0 109.0 106.0 36.3 37.2 37.8 52.9 55.7 57.6 120.0 116.0 113.0 37.6 38.7 39.3 53.7 56.5 58.3 128.0 124.0 121.0 39.0 40.1 40.8 54.5 57.3 59.1 46 75.7 32.8 58.2 81.9 34.2 58.5 88.4 35.7 59.1 95.1 37.2 59.7 102.0 38.7 60.4 109.0 40.3 61.1 117.0 41.8 61.9 49 72.6 33.3 61.2 78.6 34.8 61.4 85.0 36.4 61.9 91.5 37.9 62.5 98.2 39.5 63.1 105.0 41.2 63.9 112.0 42.8 64.6 52 69.4 33.8 64.1 75.3 35.4 64.3 81.5 37.0 64.8 87.8 38.6 65.3 94.4 40.3 65.9 101.0* 42.0* 66.6* 108.0* 43.7* 67.4* 21 102.0 26.9 35.7 111.0 27.6 35.8 119.0 28.3 36.2 128.0 29.1 36.7 137.0 29.8 37.3 147.0 30.6 38.1 157.0 31.4 38.9 27 95.6 28.8 41.6 103.0 29.7 41.8 112.0 30.6 42.1 120.0 31.5 42.5 129.0 32.4 43.0 138.0 33.4 43.7 147.0 34.4 44.5 30 92.2 29.6 44.6 99.7 30.6 44.7 108.0 31.6 45.0 116.0 32.6 45.4 125.0 33.6 45.9 134.0 34.7 46.5 143.0 35.7 47.3 32 89.9 30.2 46.6 97.4 31.2 46.7 105.0 32.3 47.0 113.0 33.3 47.3 122.0 34.4 47.8 131.0 35.5 48.4 140.0 36.6 49.1 Air Temperature 35 86.6 30.9 49.6 93.8 32.1 49.7 102.0 33.2 49.9 110.0 34.3 50.2 118.0 35.5 50.7 126.0 36.7 51.3 135.0 37.9 51.9 Entering Condenser (C) 38 41 43 83.3 80.1 77.9 31.6 32.3 32.6 52.6 55.6 57.6 90.3 86.9 84.6 32.8 33.5 34.0 52.7 55.6 57.6 97.9 94.2 91.8 34.0 34.8 35.3 52.9 55.8 57.8 106.0 102.0 99.2 35.3 36.2 36.7 53.1 56.1 58.1 114.0 110.0 107.0 36.5 37.5 38.1 53.6 56.5 58.4 122.0 118.0 115.0 37.8 38.9 39.5 54.1 57.0 58.9 131.0 126.0 123.0 39.1 40.2 40.9 54.8 57.6 59.5 46 74.7 33.2 60.6 81.1 34.7 60.6 88.1 36.1 60.8 95.3 37.5 61.0 103.0 39.0 61.4 111.0 40.5 61.8 118.0 42.0 62.3 49 71.5 33.8 63.6 77.7 35.3 63.6 84.5 36.8 63.7 91.5 38.3 63.9 98.7 39.8 64.3 106.0 41.4 64.7 114.0 43.0 65.2 52 68.4* 34.2* 66.6* 74.4* 35.8* 66.6* 80.8* 37.4* 66.7* 87.7* 39.0* 66.9* 94.7* 40.6* 67.2* 102.0* 42.3* 67.6* 110.0* 43.9* 68.1* 38AH084 CIRCUIT B SST (C) −2 0 2 4 6 8 10 CMP SDT SST TCG 68 — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH094 CIRCUIT A SST (C) −2 0 2 4 6 8 10 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 21 130.0 31.8 35.5 33.6 140.0 32.7 36.2 34.0 150.0 33.7 37.1 34.6 161.0 34.7 38.0 35.2 172.0 35.7 39.0 35.8 183.0 36.7 40.1 36.5 195.0 37.7 41.1 37.2 27 120.0 34.2 41.2 39.7 130.0 35.3 41.8 40.1 140.0 36.5 42.6 40.6 150.0 37.7 43.5 41.2 161.0 38.9 44.4 41.9 172.0 40.1 45.4 42.6 183.0 41.3 46.4 43.3 30 116.0 35.3 44.0 42.8 125.0 36.6 44.5 43.1 135.0 37.9 45.3 43.7 145.0 39.2 46.2 44.3 155.0 40.5 47.1 44.9 166.0 41.8 48.0 45.6 177.0 43.1 49.1 46.4 32 112.0 36.0 45.9 44.8 122.0 37.3 46.4 45.1 131.0 38.7 47.2 45.7 141.0 40.1 48.0 46.3 152.0 41.5 48.9 46.9 162.0 42.9 49.8 47.6 173.0 44.3 50.8 48.4 Air Temperature 35 108.0 37.0 48.8 47.8 117.0 38.4 49.2 48.1 126.0 39.9 49.9 48.6 136.0 41.4 50.7 49.2 146.0 42.9 51.6 49.9 156.0 44.4 52.5 50.6 167.0 45.9 53.5 51.3 Entering Condenser (C) 38 41 43 103.0 97.6 94.2 37.8 38.5 38.9 51.6 54.5 56.5 50.8 53.9 55.9 112.0 107.0 103.0 39.4 40.2 40.7 52.0 54.9 56.8 51.1 54.1 56.0 121.0 116.0 112.0 40.9 41.9 42.5 52.7 55.5 57.4 51.6 54.5 56.5 131.0 125.0 122.0 42.5 43.6 44.3 53.4 56.2 58.0 52.1 55.0 57.0 140.0 135.0 131.0 44.2 45.4 46.1 54.3 57.0 58.8 52.8 55.7 57.6 151.0 145.0 141.0 45.8 47.1 47.9 55.2 57.9 59.6 53.5 56.4 58.3 161.0 155.0 151.0 47.4 48.9 49.8 56.2 58.8 60.5 54.2 57.1 59.0 21 124.0 28.9 34.4 32.6 134.0 29.8 35.1 33.1 144.0 30.7 36.0 33.6 154.0 31.5 36.9 34.2 165.0 32.4 37.9 34.8 176.0 33.3 38.9 35.5 188.0 34.3 39.9 36.2 27 115.0 31.2 40.0 38.6 124.0 32.3 40.6 39.1 134.0 33.4 41.4 39.6 144.0 34.4 42.3 40.2 154.0 35.5 43.2 40.8 165.0 36.6 44.1 41.5 176.0 37.7 45.2 42.2 30 110.0 32.4 42.8 41.7 119.0 33.5 43.4 42.1 128.0 34.7 44.1 42.6 138.0 35.9 44.9 43.2 148.0 37.1 45.8 43.8 159.0 38.3 46.8 44.5 170.0 39.5 47.8 45.2 32 107.0 33.1 44.7 43.7 116.0 34.3 45.2 44.0 125.0 35.5 46.0 44.6 135.0 36.7 46.7 45.1 145.0 38.0 47.6 45.8 155.0 39.3 48.6 46.5 166.0 40.6 49.5 47.2 Air Temperature 35 102.0 34.0 47.5 46.7 111.0 35.3 48.0 47.0 120.0 36.7 48.7 47.5 129.0 38.0 49.5 48.1 139.0 39.4 50.3 48.7 149.0 40.7 51.2 49.4 160.0 42.1 52.2 50.1 Entering Condenser (C) 38 41 43 97.3 92.6 89.4 34.9 35.7 36.2 50.4 53.3 55.2 49.7 52.7 54.6 106.0 101.0 97.8 36.3 37.2 37.8 50.8 53.6 55.5 49.9 52.9 54.9 115.0 110.0 106.0 37.7 38.8 39.4 51.5 54.3 56.1 50.4 53.3 55.3 124.0 119.0 115.0 39.2 40.3 41.0 52.2 54.9 56.7 51.0 53.9 55.8 134.0 128.0 124.0 40.7 41.9 42.6 53.0 55.7 57.5 51.6 54.5 56.4 143.0 138.0 134.0 42.1 43.4 44.3 53.9 56.6 58.4 52.3 55.1 57.1 154.0 147.0 143.0 43.6 45.0 45.9 54.8 57.4 59.2 53.0 55.8 57.8 46 89.1 39.4 59.4 58.9 97.9 41.4 59.6 59.0 107.0 43.3 60.2 59.4 116.0 45.2 60.8 59.9 125.0 47.1 61.5 60.5 135.0 49.1 62.3 61.1 145.0 51.0 63.2 61.8 49 84.0 39.8 62.3 61.9 92.6 41.9 62.5 62.0 101.0 43.9 63.0 62.3 110.0 46.0 63.5 62.7 120.0 48.1 64.2 63.3 129.0 50.1 65.0 64.0 139.0 52.2 65.9 64.7 52 78.8 40.0 65.3 64.9 87.3 42.3 65.4 64.9 96.0 44.5 65.8 65.3 105.0 46.7 66.3 65.6 114.0 48.9 66.9 66.2 123.0 51.1 67.7 66.8 132.0 53.3 68.5* 67.5 38AH104 CIRCUIT A SST (C) −2 0 2 4 6 8 10 CMP SCT SDT SST TCG — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT LEGEND Compressor Power, kW Saturated Condensing Temperature (C) Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 46 84.7 36.8 58.1 57.7 92.8 38.5 58.4 57.8 101.0 40.2 58.9 58.2 110.0 42.0 59.5 58.7 119.0 43.7 60.2 59.2 128.0 45.5 61.0 59.9 137.0 47.2 61.9 60.6 49 80.0 37.3 61.1 60.7 88.0 39.2 61.3 60.8 96.3 41.0 61.7 61.1 105.0 42.8 62.3 61.5 113.0 44.7 63.0 62.1 122.0 46.5 63.7 62.7 132.0 48.4 64.5 63.4 52 75.3 37.7 64.0 63.7 83.1 39.7 64.1 63.7 91.2 41.7 64.6 64.0 99.4 43.6 65.1 64.4 108.0 45.6 65.7 64.9 117.0 47.5 66.4 65.5 126.0 49.5 67.2 66.2 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 69 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH094 CIRCUIT B SST (C) −2 0 2 4 6 8 10 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 21 103.0 26.3 33.8 32.3 111.0 27.0 34.2 32.4 119.0 27.8 34.9 32.8 128.0 28.6 35.6 33.3 137.0 29.4 36.4 33.8 146.0 30.2 37.3 34.3 155.0 31.0 38.2 34.9 27 96.5 28.1 39.6 38.5 104.0 29.0 39.9 38.6 112.0 30.0 40.5 39.0 120.0 30.9 41.2 39.4 129.0 31.9 41.9 39.9 137.0 32.9 42.7 40.4 146.0 33.9 43.6 41.0 30 93.1 29.0 42.5 41.5 101.0 30.0 42.8 41.7 108.0 31.0 43.4 42.0 116.0 32.1 44.0 42.4 124.0 33.1 44.7 42.9 133.0 34.2 45.5 43.5 142.0 35.3 46.3 44.1 32 90.9 29.6 44.5 43.6 98.2 30.6 44.8 43.7 106.0 31.7 45.3 44.0 114.0 32.8 45.9 44.4 122.0 33.9 46.5 44.9 130.0 35.0 47.3 45.5 139.0 36.2 48.2 46.1 Air Temperature 35 87.6 30.4 47.4 46.7 94.7 31.5 47.7 46.8 102.0 32.6 48.2 47.1 110.0 33.8 48.7 47.4 118.0 35.0 49.3 47.9 126.0 36.2 50.1 48.4 134.0 37.4 50.9 49.0 Entering Condenser (C) 38 41 43 84.3 81.1 78.9 31.1 31.8 32.2 50.4 53.4 55.4 49.7 52.8 54.8 91.3 87.8 85.5 32.3 33.1 33.5 50.6 53.5 55.5 49.8 52.8 54.8 98.6 95.0 92.6 33.5 34.3 34.9 51.0 53.9 55.9 50.1 53.1 55.1 106.0 102.0 99.7 34.7 35.7 36.2 51.5 54.4 56.3 50.4 53.4 55.4 114.0 110.0 107.0 36.0 37.0 37.6 52.1 55.0 56.9 50.9 53.8 55.8 122.0 118.0 115.0 37.3 38.4 39.1 52.9 55.7 57.5 51.4 54.4 56.3 130.0 126.0 123.0 38.6 39.8 40.5 53.7 56.4 58.3 52.0 54.9 56.9 21 141.0 33.9 35.7 33.5 151.0 35.1 36.5 34.0 163.0 36.2 37.5 34.7 174.0 37.4 38.5 35.3 186.0 38.6 39.6 36.0 199.0 39.8 40.7 36.7 212.0 41.1 41.9 37.5 27 130.0 36.5 41.2 39.5 140.0 37.8 41.9 40.0 151.0 39.2 42.9 40.7 162.0 40.6 43.8 41.4 174.0 42.0 44.8 42.1 186.0 43.4 45.9 42.8 198.0 44.9 47.0 43.6 30 125.0 37.7 43.9 42.6 135.0 39.1 44.7 43.1 145.0 40.6 45.5 43.7 156.0 42.1 46.4 44.4 168.0 43.6 47.4 45.1 179.0 45.2 48.5 45.8 191.0 46.8 49.5 46.6 32 122.0 38.5 45.8 44.5 131.0 40.0 46.5 45.0 142.0 41.5 47.3 45.7 152.0 43.1 48.2 46.3 163.0 44.7 49.2 47.1 175.0 46.3 50.2 47.8 187.0 47.9 51.3 48.6 Air Temperature 35 117.0 39.6 48.6 47.5 126.0 41.2 49.2 48.0 136.0 42.8 50.0 48.6 146.0 44.5 50.9 49.3 157.0 46.2 51.8 50.0 168.0 47.9 52.8 50.7 180.0 49.6 53.9 51.5 Entering Condenser (C) 38 41 43 112.0 107.0 103.0 40.6 41.5 42.1 51.4 54.3 56.2 50.5 53.5 55.5 121.0 116.0 112.0 42.3 43.3 44.0 52.0 54.8 56.7 50.9 53.9 55.8 131.0 125.0 122.0 44.0 45.2 45.9 52.8 55.5 57.4 51.5 54.4 56.4 141.0 135.0 131.0 45.8 47.0 47.8 53.6 56.3 58.1 52.2 55.1 57.0 151.0 145.0 141.0 47.6 48.9 49.8 54.5 57.2 59.0 52.9 55.7 57.7 162.0 156.0 151.0 49.4 50.9 51.8 55.5 58.1 59.9 53.6 56.5 58.4 173.0 166.0 162.0 51.3 52.8 53.8 56.5 59.1 60.8 54.4 57.3 59.2 46 75.7 32.8 58.3 57.9 82.1 34.2 58.4 57.9 89.0 35.6 58.8 58.1 95.9 37.1 59.2 58.4 103.0 38.5 59.7 58.8 111.0 40.0 60.3 59.3 118.0 41.5 61.0 59.8 49 72.5 33.4 61.3 60.9 78.8 34.8 61.4 60.9 85.4 36.3 61.7 61.1 92.2 37.8 62.1 61.3 99.2 39.4 62.5 61.7 106.0 40.9 63.1 62.2 114.0 42.5 63.8 62.7 52 69.4 33.9 64.3 63.9 75.4 35.4 64.4 63.9 81.9 37.0 64.6 64.1 88.4 38.5 65.0 64.3 95.3 40.2 65.4 64.7 102.0 41.8 66.0 65.1 110.0 43.5 66.6 65.6 38AH104 CIRCUIT B SST (C) −2 0 2 4 6 8 10 CMP SCT SDT SST TCG 70 — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT LEGEND Compressor Power, kW Saturated Condensing Temperature (C) Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 46 98.4 42.9 59.1 58.5 107.0 44.9 59.5 58.8 116.0 46.9 60.1 59.3 125.0 48.9 60.8 59.8 135.0 51.0 61.7 60.5 145.0 53.1 62.6 61.2 155.0 55.2 63.5 62.0 49 93.6 43.7 61.9 61.4 102.0 45.7 62.3 61.7 111.0 47.8 62.9 62.2 120.0 50.0 63.6 62.7 129.0 52.1 64.4 63.4 139.0 54.3 65.2 64.1 149.0 56.6 66.1 64.8 52 88.9 44.4 64.9 64.4 97.0 46.5 65.2 64.6 106.0 48.7 65.7 65.1 114.0 50.9 66.3 65.6 123.0 53.2 67.1 66.2 133.0 55.5 67.9 66.9 142.0 57.9 68.7* 67.6 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — SI (cont) 38AH124 MODULE 124A OR 124B; 38AH134 MODULE 134A SST (C) −2 0 2 4 6 8 10 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 21 149.0 35.7 34.7 33.9 161.0 36.7 35.2 34.3 173.0 37.6 35.8 34.7 186.0 38.5 36.5 35.3 200.0 39.4 37.2 35.9 214.0 40.3 38.1 36.6 228.0 41.3 39.0 37.3 27 138.0 38.6 40.5 39.9 149.0 39.8 40.9 40.2 161.0 41.0 41.5 40.7 174.0 42.1 42.1 41.2 186.0 43.3 42.9 41.8 200.0 44.6 43.7 42.4 213.0 45.8 44.5 43.1 30 132.0 40.0 43.4 42.9 143.0 41.3 43.8 43.2 155.0 42.6 44.4 43.6 167.0 44.0 45.0 44.1 180.0 45.3 45.7 44.7 193.0 46.6 46.5 45.3 206.0 48.0 47.3 46.0 32 129.0 40.8 45.4 44.9 140.0 42.2 45.8 45.2 151.0 43.7 46.3 45.6 163.0 45.1 46.9 46.1 175.0 46.5 47.6 46.6 188.0 47.9 48.3 47.3 201.0 49.4 49.1 48.0 Air Temperature 35 123.0 42.0 48.3 47.9 134.0 43.6 48.7 48.1 145.0 45.1 49.2 48.5 157.0 46.6 49.7 49.0 169.0 48.2 50.4 49.5 181.0 49.8 51.1 50.2 194.0 51.3 51.9 50.8 Entering Condenser (C) 38 41 43 118.0 112.0 109.0 43.1 44.0 44.5 51.3 54.2 56.2 50.9 53.8 55.9 128.0 122.0 119.0 44.7 45.8 46.4 51.6 54.4 56.4 51.1 54.0 56.0 139.0 133.0 129.0 46.4 47.6 48.4 52.0 54.9 56.8 51.5 54.4 56.4 150.0 144.0 140.0 48.1 49.5 50.3 52.6 55.4 57.3 51.9 54.8 56.8 162.0 155.0 151.0 49.8 51.3 52.2 53.2 56.0 57.9 52.5 55.4 57.3 174.0 167.0 163.0 51.5 53.1 54.1 53.9 56.7 58.6 53.1 55.9 57.9 187.0 179.0 175.0 53.2 55.0 56.1 54.7 57.4 59.3 53.7 56.6 58.5 27 169.0 48.6 39.8 37.7 182.0 50.2 40.2 38.2 196.0 51.8 40.9 38.8 211.0 53.4 41.6 39.5 226.0 55.0 42.3 40.1 241.0 56.6 43.1 40.7 257.0 58.2 44.0 41.4 30 163.0 50.1 42.7 40.7 176.0 51.8 43.1 41.2 190.0 53.6 43.7 41.7 204.0 55.4 44.4 42.3 218.0 57.1 45.1 43.0 233.0 58.9 45.9 43.6 249.0 60.7 46.7 44.3 32 159.0 51.1 44.6 42.6 172.0 52.9 45.0 43.1 185.0 54.8 45.6 43.7 199.0 56.6 46.3 44.3 213.0 58.5 47.0 44.9 228.0 60.4 47.8 45.5 244.0 62.2 48.6 46.2 Air Temperature 35 153.0 52.5 47.5 45.5 166.0 54.4 47.8 46.0 179.0 56.4 48.4 46.5 192.0 58.5 49.1 47.1 206.0 60.5 49.8 47.7 221.0 62.5 50.5 48.4 236.0 64.6 51.3 49.0 Entering Condenser (C) 38 41 43 147.0 141.0 137.0 53.8 54.9 55.6 50.4 53.4 55.4 48.5 51.4 53.4 159.0 153.0 149.0 55.8 57.1 57.9 50.7 53.6 55.5 48.9 51.7 53.6 172.0 166.0 161.0 58.0 59.4 60.3 51.3 54.1 56.0 49.4 52.3 54.2 185.0 179.0 174.0 60.1 61.7 62.7 51.9 54.7 56.5 50.0 52.8 54.7 199.0 192.0 187.0 62.3 64.1 65.1 52.6 55.3 57.2 50.6 53.4 55.3 213.0 206.0 201.0 64.5 66.4 67.6 53.3 56.1 57.9 51.2 54.0 55.9 228.0 220.0 215.0 66.7 68.8 70.0 54.1 56.8 58.7 51.8 54.7 56.5 46 103.0 45.4 59.1 58.9 113.0 47.4 59.4 59.0 123.0 49.5 59.7 59.3 134.0 51.5 60.2 59.7 145.0 53.6 60.7 60.2 156.0 55.6 61.4 60.7 167.0 57.7 62.1 61.3 49 97.8 46.0 62.1 61.9 107.0 48.2 62.3 62.0 117.0 50.4 62.7 62.3 127.0 52.6 63.1 62.6 138.0 54.8 63.6 63.1 149.0 57.0 64.2 63.6 160.0 59.2 64.8 64.2 52 92.5 46.6 65.1 64.8 102.0 48.9 65.2 65.0 111.0 51.2 65.6 65.2 121.0 53.5 65.9 65.5 132.0 55.9 66.4 66.0 142.0 58.2 67.0 66.5 153.0 60.6 67.6* 67.0 38AH134 MODULE 134B SST (C) −2 0 2 4 6 8 10 CMP SCT SDT SST TCG — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 21 181.0 45.2 34.0 31.9 195.0 46.5 34.5 32.4 210.0 47.8 35.2 33.0 224.0 49.0 36.0 33.6 240.0 50.3 36.7 34.3 256.0 51.5 37.6 34.9 273.0 52.8 38.4 35.6 LEGEND Compressor Power, kW Saturated Condensing Temperature (C) Saturated Discharge Temperature (leaving compressor) (C) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (kW) 46 131.0 56.6 58.3 56.3 143.0 59.1 58.4 56.5 155.0 61.6 58.9 57.0 167.0 64.1 59.3 57.5 180.0 66.7 60.0 58.1 193.0 69.3 60.7 58.7 207.0 71.9 61.4 59.3 49 125.0 57.4 61.3 59.3 136.0 60.1 61.4 59.4 148.0 62.7 61.8 59.9 160.0 65.4 62.2 60.3 173.0 68.1 62.8 60.9 186.0 70.9 63.4 61.5 199.0 73.7 64.2 62.1 52 119.0 58.2 64.3 62.2 130.0 61.0 64.3 62.4 142.0 63.7 64.6 62.7 153.0 66.6 65.0 63.1 165.0 69.4 65.5 63.7 178.0 72.4 66.2 64.2 191.0 75.3 66.9 64.8 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 71 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — ENGLISH 38AH044 SST (F) 20 25 30 35 40 45 50 90 242.0 25.8 111.0 279.0 27.1 111.5 317.0 28.4 112.0 357.0 29.6 113.0 400.0 30.9 113.5 444.0 32.0 115.0 491.0 33.1 117.0 Air Temperature 95 230.0 26.2 116.0 265.0 27.8 116.0 303.0 29.2 116.5 342.0 30.6 118.0 384.0 31.9 118.5 427.0 33.2 120.0 473.0 34.5 121.5 Entering Condenser (F) 100 105 110 216.0 202.0 189.3 26.6 26.9 27.0 121.0 125.5 131.0 251.0 238.0 224.0 28.4 28.8 29.1 121.0 126.0 131.0 289.0 274.0 259.0 30.0 30.6 31.1 121.5 126.5 131.5 328.0 312.0 297.0 31.4 32.3 33.0 122.5 127.0 132.5 368.0 351.0 336.0 33.0 34.0 34.8 123.5 128.0 133.0 411.0 394.0 376.0 34.4 35.5 36.5 124.5 129.5 134.5 455.0 438.0 419.0 35.8 37.1 38.2 126.0 131.0 135.5 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 293.0 22.9 91.0 332.0 23.7 91.6 373.0 24.4 92.4 416.0 25.1 93.6 462.0 25.8 94.9 509.0 26.4 96.4 560.0 27.0 98.0 80 268.0 24.4 102.0 305.0 25.5 101.5 345.0 26.5 102.0 387.0 27.5 103.5 431.0 28.4 104.5 477.0 29.3 106.0 525.0 30.2 107.5 85 255.0 25.1 106.0 292.0 26.3 106.5 331.0 27.5 107.0 372.0 28.6 108.0 415.0 29.7 109.5 460.0 30.6 111.0 508.0 31.7 112.5 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 341.0 27.8 95.5 387.0 28.9 96.0 435.0 29.9 96.7 485.0 30.9 97.7 538.0 31.9 99.2 593.0 32.9 100.9 652.0 34.0 102.7 80 313.0 29.5 105.5 357.0 30.9 105.5 403.0 32.3 106.5 451.0 33.5 107.0 503.0 34.8 108.5 555.0 36.1 110.0 611.0 37.4 112.0 85 299.0 30.2 110.5 342.0 31.8 110.5 386.0 33.3 111.0 434.0 34.8 112.0 485.0 36.1 113.0 537.0 37.6 114.5 592.0 39.1 116.5 90 286.0 30.9 115.5 327.0 32.6 115.5 371.0 34.3 116.0 417.0 35.9 117.0 467.0 37.5 118.0 518.0 39.1 119.5 571.0 40.6 121.0 Air Temperature Entering Condenser (F) 95 100 105 110 272.0 259.0 245.0 231.2 31.5 32.0 32.4 32.6 120.5 125.5 130.5 135.5 312.0 297.0 282.0 268.0 33.4 34.1 34.7 35.1 120.5 125.5 130.5 135.5 355.0 340.0 323.0 308.0 35.3 36.1 36.8 37.4 121.0 126.0 131.0 136.0 401.0 384.0 367.0 350.0 37.0 38.0 38.9 39.7 121.5 126.5 131.5 136.5 449.0 431.0 412.0 395.0 38.7 39.9 41.0 41.9 123.0 128.0 132.5 137.0 499.0 480.0 461.0 442.0 40.4 41.8 43.0 44.1 124.0 128.5 133.5 138.5 551.0 532.0 511.0 491.0 42.2 43.7 45.0 46.3 126.0 130.0 135.0 139.5 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 415.0 33.6 93.4 468.0 34.9 94.0 523.0 36.2 95.0 582.0 37.4 96.3 644.0 38.7 98.0 708.0 40.0 100.0 776.0 41.2 102.0 80 383.0 35.7 103.0 434.0 37.4 104.0 487.0 39.0 104.5 544.0 40.6 105.5 603.0 42.2 107.5 664.0 43.9 109.0 729.0 45.5 111.0 85 368.0 36.7 108.0 417.0 38.6 109.0 469.0 40.3 109.5 525.0 42.1 110.5 582.0 43.9 112.5 642.0 45.7 114.0 706.0 47.5 116.0 90 352.0 37.5 113.0 401.0 39.6 113.5 451.0 41.5 114.5 505.0 43.5 115.5 562.0 45.5 116.5 620.0 47.4 118.5 682.0 49.4 120.5 Air Temperature 95 337.0 38.3 118.0 384.0 40.6 118.5 434.0 42.7 119.0 487.0 44.8 120.5 542.0 47.0 121.5 600.0 49.1 123.5 660.0 51.3 125.0 115 175.9 27.1 135.5 210.0 29.4 136.0 244.0 31.6 136.5 281.0 33.6 136.5 320.0 35.6 138.0 359.0 37.5 139.0 401.0 39.3 140.5 120 162.6 27.0 140.5 195.1 29.6 141.0 230.0 31.9 141.0 265.0 34.1 141.5 303.0 36.3 142.5 343.0 38.4 144.0 384.0 40.4 145.5 125 149.1 26.7 145.5 180.8 29.5 146.0 214.0 32.1 146.0 250.0 34.5 146.5 287.0 36.9 147.5 325.0 39.2 148.5 366.0 41.3 149.5 120 204.9 33.0 145.5 239.2 35.9 145.5 277.0 38.5 145.5 316.0 41.1 146.0 359.0 43.7 146.5 403.0 46.3 148.0 450.0* 48.8* 149.0* 125 191.2* 33.0* 150.5* 225.1* 36.0* 150.5* 261.0* 38.9* 150.5* 300.0* 41.7* 151.0* 341.0* 44.5* 151.5* 385.0* 47.1* 153.0* 431.0* 49.8* 153.5* 120 261.0 40.8 143.0 302.0 43.9 143.0 346.0 47.0 144.0 393.0 50.0 144.5 442.0 53.0 145.5 493.0 56.1 146.6 546.0 59.1 148.5 125 246.0 41.0 148.0 285.0 44.3 148.0 328.0 47.5 149.0 374.0 50.7 149.5 421.0* 54.0* 150.5* 471.0* 57.1* 151.5* 523.0* 60.3* 153.5* 38AH054 SST (F) 20 25 30 35 40 45 50 115 217.6 32.9 140.5 253.0 35.6 140.5 292.0 38.0 141.0 333.0 40.5 141.0 377.0 42.9 142.0 423.0 45.2 143.0 471.0 47.5 144.5 38AH064 SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG 72 — — — — LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) Entering Condenser (F) 100 105 110 321.0 306.0 290.0 39.0 39.6 40.1 123.0 128.0 133.0 367.0 350.0 335.0 41.4 42.2 42.8 123.5 128.5 133.5 416.0 399.0 380.0 43.7 44.7 45.5 124.0 129.0 134.0 467.0 448.0 429.0 46.0 47.2 48.2 125.0 130.0 134.5 521.0 501.0 481.0 48.3 49.6 50.8 126.5 131.5 136.0 578.0 556.0 535.0 50.7 52.2 53.5 128.0 132.5 137.5 636.0 614.0 591.0 53.0 54.7 56.2 130.0 134.5 139.5 115 275.0 40.5 138.0 318.0 43.4 138.0 363.0 46.3 139.0 410.0 49.2 139.5 461.0 52.0 140.5 514.0 54.9 142.5 569.0 57.7 143.5 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT RATINGS ENGLISH (cont) 38AH074 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 513.0 42.4 92.1 574.0 44.1 92.7 638.0 45.8 93.9 706.0 47.7 95.5 776.0 49.5 97.3 850.0 51.2 99.3 930.0 53.0 101.5 80 478.0 44.9 102.0 538.0 47.0 102.5 600.0 49.1 103.5 664.0 51.3 104.5 731.0 53.6 106.5 803.0 55.8 108.5 879.0 57.9 110.5 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 574.0 50.7 97.1 644.0 52.9 97.2 721.0 54.9 97.4 802.0 56.9 98.1 887.0 58.9 99.2 976.0 61.1 100.5 1067.0 63.3 102.5 80 536.0 53.3 107.0 604.0 55.9 107.0 676.0 58.5 107.0 754.0 60.9 108.0 835.0 63.5 109.0 920.0 66.1 110.5 1009.0 68.7 112.0 85 461.0 46.0 107.0 520.0 48.3 107.0 580.0 50.6 108.0 643.0 53.0 109.5 710.0 55.4 111.5 780.0 57.8 113.0 853.0 60.3 115.0 90 444.0 47.1 112.0 501.0 49.6 112.0 561.0 52.1 113.0 623.0 54.6 114.5 688.0 57.2 116.0 756.0 59.8 118.0 828.0 62.5 120.0 Air Temperature 95 427.0 48.1 117.0 482.0 50.7 117.0 541.0 53.4 118.0 603.0 56.1 119.0 666.0 58.9 120.5 733.0 61.8 122.5 803.0 64.6 124.5 Entering Condenser (F) 100 105 110 410.0 393.0 376.0 48.9 49.6 50.2 122.0 126.5 131.5 465.0 446.0 428.0 51.7 52.7 53.5 122.0 127.0 132.0 522.0 503.0 483.0 54.6 55.8 56.8 123.0 128.0 132.5 581.0 561.0 540.0 57.6 58.8 60.1 123.5 128.5 133.5 644.0 622.0 600.0 60.5 62.0 63.4 125.5 130.0 134.5 709.0 686.0 662.0 63.5 65.3 66.8 127.0 131.5 136.5 778.0 753.0 727.0 66.6 68.6 70.3 129.0 133.5 138.0 115 360.0 50.8 136.5 410.0 54.3 137.0 463.0 57.8 137.0 520.0 61.3 138.0 578.0 64.8 139.5 640.0 68.4 141.0 703.0 72.1 143.0 120 342.0 51.2 142.0 392.0 54.9 142.0 444.0 58.6 142.0 499.0 62.3 143.0 557.0 66.0 144.0 616.0 69.8 145.5 678.0 73.7 147.0 125 326.0 51.6 147.0 373.0 55.4 147.0 425.0 59.3 147.0 479.0 63.2 148.0 534.0 67.1 148.5 593.0* 71.1* 150.0* 653.0* 75.1* 152.0* 115 412.0 59.9 142.0 467.0 64.0 142.0 526.0 68.0 142.0 590.0 72.0 143.0 659.0 76.1 143.0 731.0 80.2 144.0 807.0 84.4 145.0 120 395.0 60.6 147.0 448.0 64.8 147.0 506.0 69.0 147.0 568.0 73.2 147.0 634.0 77.5 148.0 705.0 81.8 149.0 779.0 86.2 150.0 125 378.0* 61.1* 152.0* 430.0* 65.5* 152.0* 486.0* 69.9* 152.0* 546.0* 74.4* 152.0* 610.0* 78.8* 153.0* 679.0* 83.3* 154.0* 750.0* 87.9* 154.5* 38AH084 SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG — — — — 85 518.0 54.5 112.0 584.0 57.3 112.0 654.0 60.1 112.0 730.0 62.9 113.0 809.0 65.5 113.5 893.0 68.3 115.0 980.0 71.3 116.5 90 500.0 55.6 117.0 564.0 58.7 117.0 632.0 61.7 117.0 706.0 64.7 118.0 785.0 67.5 118.5 866.0 70.6 119.5 950.0 73.7 121.5 LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) Air Temperature Entering Condenser (F) 95 100 105 110 482.0 464.0 446.0 429.0 56.6 57.6 58.4 59.2 122.0 127.0 132.0 137.0 544.0 524.0 505.0 486.0 59.9 61.0 62.1 63.0 122.0 127.0 132.0 137.0 611.0 590.0 568.0 548.0 63.1 64.5 65.7 66.8 122.0 127.0 132.0 137.0 683.0 660.0 636.0 614.0 66.3 67.9 69.3 70.7 123.0 128.0 133.0 138.0 759.0 734.0 709.0 684.0 69.5 71.3 72.9 74.5 123.5 128.0 133.0 138.0 839.0 811.0 785.0 758.0 72.7 74.7 76.7 78.5 124.5 129.5 134.0 139.0 922.0 892.0 864.0 836.0 76.1 78.3 80.5 82.4 126.0 130.5 135.5 140.5 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 73 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — ENGLISH (cont) 38AH094 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 70 657.0 54.3 93.9 92.1 91.7 90.4 738.0 56.5 95.0 92.4 92.1 90.2 821.0 58.8 96.7 93.3 93.0 90.5 907.0 61.3 98.7 94.7 94.3 91.2 999.0 63.8 101.0 96.5 95.7 92.3 1093.0 66.3 104.0 98.6 97.4 93.6 1193.0 68.9 106.0 101.0 99.1 95.1 80 611.0 57.4 104.0 102.0 102.0 101.0 689.0 60.2 105.0 102.0 102.0 100.0 769.0 62.9 106.0 103.0 103.0 101.0 853.0 65.8 108.0 104.0 104.0 101.0 940.0 68.8 110.0 106.0 106.0 102.0 1031.0 71.8 112.0 108.0 108.0 104.0 1127.0 74.8 115.0 110.0 109.0 105.0 85 588.0 59.0 109.0 107.0 107.0 106.0 663.0 62.0 109.0 107.0 108.0 106.0 743.0 65.0 111.0 108.0 108.0 106.0 825.0 68.1 112.0 109.0 109.0 107.0 911.0 71.3 115.0 111.0 111.0 108.0 1001.0 74.6 117.0 112.0 113.0 109.0 1095.0 77.8 119.0 114.0 114.0 110.0 Air Temperature Entering Condenser (F) 90 95 100 105 564.0 540.0 517.0 494.0 60.2 61.4 62.4 63.2 114.0 119.0 124.0 129.0 112.0 117.0 122.0 127.0 113.0 118.0 123.0 128.0 111.0 116.0 121.0 126.0 638.0 614.0 589.0 564.0 63.5 64.9 66.2 67.3 114.0 119.0 124.0 129.0 112.0 117.0 122.0 127.0 113.0 118.0 123.0 128.0 111.0 116.0 121.0 126.0 716.0 691.0 664.0 638.0 66.8 68.5 70.0 71.5 115.0 120.0 125.0 130.0 113.0 118.0 123.0 127.0 113.0 118.0 123.0 128.0 111.0 116.0 121.0 126.0 798.0 771.0 742.0 714.0 70.2 72.0 73.8 75.5 117.0 122.0 126.0 131.0 114.0 119.0 123.0 128.0 114.0 119.0 124.0 129.0 112.0 117.0 122.0 127.0 882.0 853.0 824.0 793.0 73.6 75.8 77.8 79.7 119.0 124.0 128.0 133.0 115.0 120.0 125.0 129.0 116.0 121.0 126.0 131.0 113.0 118.0 122.0 127.0 970.0 939.0 908.0 877.0 77.1 79.5 81.8 83.9 121.0 126.0 130.0 135.0 117.0 122.0 126.0 131.0 118.0 123.0 127.0 132.0 114.0 119.0 124.0 129.0 1062.0 1029.0 996.0 963.0 80.7 83.3 85.8 88.3 124.0 128.0 133.0 137.0 119.0 124.0 128.0 133.0 119.0 124.0 129.0 134.0 115.0 120.0 125.0 130.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (1000 Btuh) 74 110 470.0 63.9 134.0 132.0 133.0 131.0 538.0 68.3 134.0 132.0 133.0 131.0 611.0 72.7 134.0 132.0 133.0 131.0 686.0 77.0 136.0 133.0 134.0 132.0 764.0 81.4 137.0 134.0 135.0 132.0 845.0 86.0 139.0 136.0 137.0 134.0 929.0 90.5 142.0 137.0 139.0 135.0 115 446.0 64.4 139.0 137.0 138.0 136.0 514.0 69.1 139.0 137.0 138.0 136.0 585.0 73.8 139.0 137.0 138.0 136.0 658.0 78.4 140.0 138.0 139.0 137.0 734.0 83.1 142.0 139.0 140.0 137.0 814.0 87.9 144.0 140.0 142.0 138.0 896.0 92.7 146.0 142.0 143.0 140.0 120 423.0 64.7 144.0 142.0 143.0 142.0 488.0 69.8 144.0 142.0 143.0 141.0 557.0 74.7 144.0 142.0 143.0 141.0 630.0 79.6 145.0 143.0 144.0 142.0 704.0 84.5 146.0 144.0 145.0 142.0 782.0 89.6 148.0 145.0 146.0 143.0 862.0 94.7 150.0 147.0 148.0 145.0 125 400.0 64.8 149.0 147.0 148.0 147.0 463.0 70.2 149.0 147.0 148.0 146.0 531.0 75.5 149.0 147.0 148.0 146.0 602.0 80.7 150.0 148.0 149.0 147.0 675.0 85.9 151.0 149.0 150.0 147.0 751.0 91.2 153.0 150.0 151.0 148.0 829.0 96.6 155.0* 151.0 153.0 149.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT RATINGS — ENGLISH (cont) 38AH104 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 70 747.0 58.4 91.9 93.5 89.8 90.9 837.0 61.0 93.0 95.1 90.2 91.7 932.0 63.8 94.7 97.1 91.2 92.9 1032.0 66.7 96.7 99.4 92.5 94.4 1137.0 69.5 98.9 102.0 94.0 96.0 1247.0 72.4 101.0 105.0 95.6 97.8 1363.0 75.5 104.0 108.0 97.3 99.6 80 689.0 62.2 102.0 103.0 100.0 101.0 777.0 65.2 102.0 104.0 100.0 102.0 869.0 68.5 104.0 106.0 101.0 103.0 964.0 71.8 106.0 108.0 103.0 104.0 1065.0 75.2 108.0 111.0 104.0 106.0 1170.0 78.7 110.0 113.0 106.0 108.0 1281.0 82.2 113.0 116.0 107.0 110.0 85 661.0 63.9 107.0 108.0 105.0 106.0 747.0 67.3 107.0 109.0 105.0 107.0 837.0 70.8 109.0 111.0 106.0 108.0 930.0 74.4 110.0 113.0 108.0 109.0 1029.0 78.1 112.0 115.0 109.0 111.0 1132.0 81.8 115.0 118.0 111.0 113.0 1240.0 85.6 117.0 120.0 112.0 115.0 90 633.0 65.6 112.0 113.0 110.0 111.0 718.0 69.2 112.0 114.0 111.0 112.0 805.0 72.9 113.0 115.0 111.0 113.0 896.0 76.8 115.0 117.0 112.0 114.0 993.0 80.7 117.0 120.0 114.0 116.0 1094.0 84.7 119.0 122.0 116.0 118.0 1199.0 88.8 122.0 125.0 117.0 120.0 Air Temperature Entering Condenser (F) 95 100 105 604.0 577.0 549.0 67.0 68.3 69.5 116.0 121.0 126.0 118.0 123.0 128.0 116.0 121.0 126.0 116.0 122.0 127.0 687.0 658.0 628.0 70.9 72.6 74.0 117.0 122.0 127.0 119.0 123.0 128.0 116.0 121.0 126.0 117.0 122.0 127.0 773.0 742.0 711.0 74.9 76.8 78.5 118.0 123.0 127.0 120.0 125.0 129.0 116.0 121.0 126.0 118.0 123.0 128.0 863.0 829.0 796.0 78.9 81.0 83.1 119.0 124.0 129.0 122.0 126.0 131.0 117.0 122.0 127.0 119.0 124.0 129.0 957.0 921.0 886.0 83.2 85.5 87.8 121.0 126.0 130.0 124.0 128.0 133.0 119.0 124.0 128.0 121.0 126.0 131.0 1054.0 1017.0 980.0 87.4 90.1 92.5 124.0 128.0 132.0 126.0 131.0 135.0 120.0 125.0 130.0 123.0 128.0 132.0 1158.0 1117.0 1077.0 91.7 94.7 97.4 126.0 130.0 135.0 129.0 133.0 138.0 122.0 127.0 132.0 125.0 130.0 134.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (1000 Btuh) 110 523.0 70.5 131.0 133.0 131.0 132.0 599.0 75.2 132.0 133.0 131.0 132.0 680.0 80.0 132.0 134.0 131.0 133.0 763.0 84.9 133.0 136.0 132.0 134.0 851.0 89.9 135.0 137.0 133.0 135.0 942.0 94.9 137.0 140.0 135.0 137.0 1037.0 100.1 139.0 142.0 137.0 139.0 115 495.0 71.3 136.0 138.0 136.0 137.0 571.0 76.4 137.0 138.0 136.0 137.0 649.0 81.4 137.0 139.0 136.0 138.0 731.0 86.6 138.0 140.0 137.0 139.0 816.0 91.8 140.0 142.0 138.0 140.0 905.0 97.1 141.0 144.0 140.0 142.0 998.0 102.6 144.0 146.0 141.0 144.0 120 469.0 71.9 141.0 142.0 141.0 142.0 541.0 77.4 141.0 143.0 141.0 142.0 619.0 82.7 142.0 144.0 141.0 143.0 698.0 88.1 143.0 145.0 142.0 144.0 781.0 93.6 144.0 147.0 143.0 145.0 868.0 99.2 146.0 149.0 144.0 147.0 958.0 104.9 148.0 151.0 146.0 148.0 125 443.0 72.4 146.0 147.0 146.0 147.0 513.0 78.1 146.0 148.0 146.0 147.0 588.0 83.8 147.0 148.0 146.0 148.0 665.0 89.5 148.0 150.0 147.0 148.0 747.0 95.3 149.0 151.0 148.0 150.0 831.0 101.2 150.0 153.0 149.0 151.0 919.0 107.1 152.0 155.0* 151.0 153.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 75 Performance data — 38AH044-134 (cont) CONDENSING UNIT RATINGS — ENGLISH (cont) 38AH124 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) TCG CMP SDT(A) SCT(A) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) OR (B) 70 834.0 67.2 93.3 92.4 940.0 69.8 94.0 92.8 1050.0 72.4 95.0 93.5 1168.0 75.0 96.4 94.6 1290.0 77.6 98.1 95.9 1418.0 80.0 100.0 97.5 1552.0 82.6 102.0 99.3 80 772.0 71.4 103.0 103.0 872.0 74.6 104.0 103.0 980.0 78.0 105.0 103.0 1092.0 81.2 106.0 104.0 1208.0 84.4 108.0 106.0 1332.0 87.8 109.0 107.0 1460.0 91.0 112.0 109.0 85 740.0 73.4 108.0 108.0 840.0 77.0 109.0 108.0 944.0 80.6 110.0 108.0 1052.0 84.2 111.0 109.0 1168.0 87.8 112.0 111.0 1288.0 91.6 114.0 112.0 1414.0 95.2 116.0 114.0 90 710.0 75.2 113.0 113.0 806.0 79.2 114.0 113.0 908.0 83.2 114.0 113.0 1014.0 87.0 116.0 114.0 1126.0 91.0 117.0 116.0 1244.0 95.0 119.0 117.0 1368.0 99.0 121.0 119.0 Air Temperature 95 678.0 76.8 118.0 118.0 772.0 81.0 119.0 118.0 872.0 85.4 119.0 118.0 978.0 89.6 120.0 119.0 1086.0 94.0 122.0 120.0 1202.0 98.2 123.0 122.0 1322.0 102.6 125.0 123.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (1000 Btuh) 76 Entering Condenser (F) 100 105 110 648.0 618.0 588.0 78.0 79.2 80.2 123.0 128.0 133.0 123.0 128.0 133.0 740.0 708.0 674.0 82.8 84.4 85.6 123.0 128.0 133.0 123.0 128.0 133.0 838.0 802.0 768.0 87.4 89.4 91.0 124.0 129.0 134.0 123.0 128.0 133.0 940.0 902.0 864.0 92.0 94.4 96.4 125.0 130.0 135.0 124.0 129.0 134.0 1046.0 1006.0 966.0 96.8 99.4 101.6 126.0 131.0 136.0 125.0 130.0 135.0 1158.0 1116.0 1074.0 101.4 104.4 107.0 128.0 133.0 138.0 127.0 131.0 136.0 1276.0 1232.0 1186.0 106.2 109.4 112.4 130.0 135.0 139.0 128.0 133.0 138.0 115 558.0 81.0 138.0 138.0 642.0 86.8 138.0 138.0 732.0 92.6 139.0 138.0 828.0 98.4 140.0 139.0 926.0 104.0 141.0 140.0 1032.0 109.8 142.0 141.0 1140.0 115.6 144.0 143.0 120 528.0 81.6 143.0 143.0 610.0 87.8 143.0 143.0 698.0 94.0 144.0 143.0 790.0 100.0 144.0 144.0 888.0 106.0 146.0 145.0 988.0 112.2 147.0 146.0 1096.0 118.2 149.0 147.0 125 498.0 82.0 148.0 148.0 578.0 88.6 148.0 148.0 662.0 95.0 149.0 148.0 752.0 101.4 149.0 149.0 848.0 108.0 150.0 150.0 946.0 114.4 152.0 151.0 1050.0 120.8 153.0 152.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT RATINGS — ENGLISH (cont) 38AH134 SST (F) 20 25 30 35 40 45 50 TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) TCG CMP SDT(A) SDT(B) SCT(A) SCT(B) 70 930.0 76.0 93.3 92.0 92.4 87.6 1045.0 79.0 94.0 92.7 92.8 88.6 1164.0 82.0 95.0 93.8 93.5 90.0 1290.0 85.1 96.4 95.4 94.6 91.5 1422.0 88.2 98.1 97.2 95.9 93.0 1561.0 91.2 100.0 99.2 97.5 94.6 1707.0 94.2 102.0 101.0 99.3 96.3 80 864.0 80.6 103.0 102.0 103.0 97.7 974.0 84.3 104.0 102.0 103.0 98.5 1090.0 88.1 105.0 103.0 103.0 99.7 1211.0 91.9 106.0 105.0 104.0 101.0 1337.0 95.7 108.0 107.0 106.0 103.0 1470.0 99.6 109.0 109.0 107.0 104.0 1610.0 103.4 112.0 111.0 109.0 106.0 85 831.0 82.8 108.0 107.0 108.0 103.0 940.0 86.8 109.0 107.0 108.0 103.0 1052.0 90.9 110.0 108.0 108.0 105.0 1170.0 95.1 111.0 110.0 109.0 106.0 1294.0 99.3 112.0 111.0 111.0 107.0 1425.0 103.6 114.0 113.0 112.0 109.0 1562.0 107.8 116.0 115.0 114.0 111.0 90 799.0 84.7 113.0 112.0 113.0 108.0 905.0 89.1 114.0 112.0 113.0 108.0 1015.0 93.6 114.0 113.0 113.0 109.0 1130.0 98.1 116.0 114.0 114.0 111.0 1252.0 102.7 117.0 116.0 116.0 112.0 1379.0 107.3 119.0 118.0 117.0 114.0 1513.0 111.9 121.0 120.0 119.0 116.0 Air Temperature 95 766.0 86.4 118.0 117.0 118.0 113.0 869.0 91.2 119.0 117.0 118.0 113.0 978.0 96.1 119.0 118.0 118.0 114.0 1092.0 100.9 120.0 119.0 119.0 116.0 1210.0 105.9 122.0 121.0 120.0 117.0 1335.0 110.8 123.0 122.0 122.0 119.0 1465.0 115.9 125.0 124.0 123.0 120.0 LEGEND CMP — Compressor Power (kW) SCT(A) — Saturated Condensing Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SCT(B) — Saturated Condensing Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SDT(A) — Saturated Discharge Temperature (F) for Circuit A (38AH094,104), or Module 38AH124A or 134A SDT(B) — Saturated Discharge Temperature (F) for Circuit B (38AH094,104), or Module 38AH124B or 134B SST — Saturated Suction Temperature Entering Condensing Unit TCG — Gross Cooling Capacity (1000 Btuh) Entering Condenser (F) 100 105 110 734.0 702.0 670.0 87.9 89.2 90.3 123.0 128.0 133.0 122.0 127.0 132.0 123.0 128.0 133.0 118.0 123.0 128.0 835.0 801.0 765.0 93.1 94.9 96.3 123.0 128.0 133.0 122.0 127.0 132.0 123.0 128.0 133.0 118.0 123.0 128.0 941.0 904.0 868.0 98.3 100.4 102.2 124.0 129.0 134.0 123.0 127.0 132.0 123.0 128.0 133.0 119.0 124.0 129.0 1052.0 1013.0 973.0 103.5 106.0 108.2 125.0 130.0 135.0 124.0 128.0 133.0 124.0 129.0 134.0 120.0 125.0 130.0 1168.0 1126.0 1084.0 108.9 111.7 114.2 126.0 131.0 136.0 125.0 130.0 135.0 125.0 130.0 135.0 122.0 127.0 131.0 1289.0 1245.0 1200.0 114.2 117.4 120.3 128.0 133.0 138.0 127.0 132.0 136.0 127.0 131.0 136.0 123.0 128.0 133.0 1417.0 1370.0 1322.0 119.7 123.2 126.5 130.0 135.0 139.0 129.0 134.0 138.0 128.0 133.0 138.0 125.0 130.0 134.0 115 638.0 91.3 138.0 137.0 138.0 133.0 731.0 97.7 138.0 137.0 138.0 133.0 830.0 104.0 139.0 137.0 138.0 134.0 934.0 110.4 140.0 138.0 139.0 135.0 1042.0 116.7 141.0 139.0 140.0 136.0 1156.0 123.2 142.0 141.0 141.0 137.0 1274.0 129.8 144.0 143.0 143.0 139.0 120 606.0 92.1 143.0 142.0 143.0 138.0 697.0 98.8 143.0 142.0 143.0 138.0 794.0 105.6 144.0 142.0 143.0 139.0 895.0 112.2 144.0 143.0 144.0 139.0 1001.0 119.0 146.0 144.0 145.0 141.0 1111.0 125.8 147.0 145.0 145.0 142.0 1227.0 132.7 149.0 147.0 147.0 144.0 125 575.0 92.6 148.0 147.0 148.0 143.0 663.0 99.8 148.0 147.0 148.0 143.0 756.0 106.8 149.0 147.0 148.0 144.0 855.0 113.9 149.0 148.0 149.0 144.0 959.0 121.1 150.0 149.0 150.0 145.0 1066.0 128.3 152.0 150.0 150.0 147.0 1179.0 135.5 153.0 152.0 152.0 148.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 77 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH 38AH044 CIRCUIT A SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 90 122.0 12.8 109.0 140.0 13.4 110.0 159.0 14.1 111.0 178.0 14.7 112.0 199.0 15.4 113.0 220.0 16.0 115.0 243.0 16.6 117.0 Air Temperature 95 116.0 13.0 114.0 133.0 13.8 114.0 152.0 144.5 115.0 171.0 15.2 117.0 191.0 15.9 118.0 212.0 16.6 120.0 234.0 17.3 122.0 Entering Condenser (F) 100 105 110 109.0 102.0 95.6 13.2 13.4 13.5 119.0 124.0 129.0 126.0 120.0 113.0 14.1 14.3 14.5 119.0 124.0 129.0 145.0 138.0 130.0 14.9 15.2 15.5 120.0 125.0 130.0 164.0 156.0 149.0 15.6 16.1 16.4 121.0 126.0 131.0 183.0 175.0 168.0 16.4 16.9 17.3 123.0 127.0 132.0 204.0 196.0 187.0 17.2 17.7 18.2 124.0 129.0 134.0 225.0 217.0 208.0 17.9 18.5 19.1 126.0 131.0 135.0 70 147.0 11.3 89.4 166.0 11.7 90.3 186.0 12.1 91.6 207.0 12.5 93.2 229.0 12.9 95.0 252.0 13.3 96.9 276.0 13.7 99.0 80 135.0 12.1 99.1 153.0 12.6 99.9 172.0 13.1 101.0 193.0 13.7 103.0 214.0 14.2 104.0 236.0 14.7 106.0 259.0 15.2 108.0 85 128.0 12.4 104.0 147.0 13.0 105.0 166.1 13.6 106.0 185.0 14.2 107.0 206.0 14.8 109.0 228.0 15.3 111.0 251.0 15.9 113.0 70 146.0 11.8 95.1 166.0 12.2 95.1 188.0 12.5 95.3 210.0 12.8 95.7 234.0 13.1 96.4 258.0 13.4 97.7 284.0 13.7 99.3 80 133.0 12.5 105.0 153.0 13.1 105.0 174.0 13.6 105.0 195.0 14.0 105.0 219.0 14.4 106.0 242.0 14.8 107.0 267.0 15.2 109.0 85 127.0 12.8 110.0 146.0 13.5 110.0 166.0 14.0 110.0 188.0 14.6 110.0 211.0 15.0 111.0 234.0 15.5 112.0 259.0 16.0 113.0 90 121.0 13.1 115.0 139.0 13.8 115.0 159.0 14.5 115.0 180.0 15.1 115.0 203.0 15.6 116.0 226.0 16.2 117.0 250.0 16.7 118.0 Air Temperature Entering Condenser (F) 95 100 105 110 114.0 108.0 101.0 94.2 13.3 13.4 13.5 13.5 120.0 125.0 130.0 135.0 132.0 125.0 118.0 111.0 14.1 14.4 14.6 14.7 120.0 125.0 130.0 135.0 152.0 145.0 137.0 130.0 14.9 15.2 15.5 15.7 120.0 125.0 130.0 135.0 173.0 165.0 157.0 149.0 15.6 16.0 16.4 16.7 120.0 125.0 130.0 135.0 195.0 187.0 178.0 170.0 16.2 16.7 17.2 17.6 121.0 126.0 131.0 135.0 218.0 209.0 201.0 192.0 16.8 17.4 17.9 18.4 121.0 126.0 131.0 136.0 241.0 233.0 224.0 215.0 17.4 18.1 18.7 19.3 123.0 127.0 132.0 137.0 70 197.0 15.7 93.5 222.0 16.3 94.2 249.0 17.0 95.4 278.0 17.6 96.9 308.0 18.3 98.8 339.0 19.0 101.0 372.0 19.6 103.0 80 181.0 16.7 103.0 205.0 17.5 104.0 231.0 18.3 105.0 258.0 19.1 106.0 287.0 19.9 108.0 316.0 20.8 110.0 348.0 21.6 112.0 85 174.0 17.2 108.0 197.0 18.1 109.0 222.0 18.9 110.0 249.0 19.8 111.0 276.0 20.7 113.0 305.0 21.6 115.0 336.0 22.5 117.0 90 166.0 17.6 113.0 189.0 18.6 114.0 213.0 19.5 115.0 239.0 20.5 116.0 266.0 21.5 117.0 294.0 22.4 119.0 324.0 23.4 121.0 Air Temperature 95 159.0 18.0 118.0 181.0 19.1 119.0 205.0 20.1 119.0 230.0 21.1 121.0 256.0 22.2 122.0 284.0 23.2 124.0 313.0 24.3 126.0 115 88.9 13.6 134.0 106.0 14.7 134.0 123.0 15.7 135.0 141.0 16.7 135.0 160.0 17.7 137.0 179.0 18.7 138.0 199.0 19.6 140.0 120 82.2 13.5 139.0 98.6 14.8 139.0 116.0 15.9 139.0 133.0 17.0 140.0 152.0 18.1 141.0 171.0 19.1 143.0 191.0 20.1 145.0 125 75.5 13.4 144.0 91.5 14.8 144.0 108.0 16.0 144.0 126.0 17.2 145.0 144.0 18.4 146.0 162.0 19.5 147.0 182.0 20.6 149.0 120 80.9 13.4 145.0 97.2 14.8 145.0 115.0 16.0 145.0 133.0 17.2 145.0 153.0 18.3 145.0 174.0 19.4 146.0 196.0* 20.4* 146.0* 125 74.2* 13.2* 150.0* 90.1* 14.7* 150.0* 107.0* 16.1* 150.0* 125.0* 17.4* 150.0* 145.0* 18.6* 150.0* 166.0* 19.7* 151.0* 187.0* 20.8* 151.0* 120 124.0 19.5 143.0 143.0 20.9 143.0 163.0 22.3 144.0 185.0 23.7 145.0 208.0 25.1 146.0 232.0 26.6 147.0 257.0 28.0 149.0 125 117.0 19.7 148.0 135.0 21.2 148.0 155.0 22.6 149.0 176.0 24.1 150.0 198.0* 25.6* 151.0* 221.0* 27.1* 152.0* 246.0* 28.6* 154.0* 38AH054 CIRCUIT A SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 115 87.6 13.5 140.0 104.0 14.8 140.0 122.0 15.9 140.0 141.0 17.0 140.0 162.0 18.0 140.0 183.0 18.9 141.0 206.0 19.8 142.0 38AH064 CIRCUIT A SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG 78 — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) Entering Condenser (F) 100 105 110 151.0 144.0 137.0 18.4 18.7 19.0 123.0 128.0 133.0 173.0 165.0 158.0 19.5 19.9 20.3 124.0 129.0 134.0 196.0 188.0 179.0 20.6 21.1 21.6 124.0 129.0 134.0 220.0 211.0 202.0 21.7 22.3 22.8 125.0 130.0 135.0 246.0 236.0 227.0 22.8 23.4 24.0 127.0 132.0 136.0 273.0 262.0 252.0 24.0 24.7 25.3 129.0 133.0 138.0 301.0 290.0 279.0 25.1 25.9 26.6 131.0 135.0 140.0 115 130.0 19.3 138.0 150.0 20.6 138.0 171.0 21.9 139.0 193.0 23.3 140.0 217.0 24.6 141.0 242.0 26.0 143.0 268.0 27.3 144.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH044 CIRCUIT B SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 90 120.0 13.0 113.0 139.0 13.7 113.0 158.0 14.3 113.0 179.0 14.9 114.0 201.0 15.5 114.0 224.0 16.0 115.0 248.0 16.5 117.0 Air Temperature 95 114.0 13.2 118.0 132.0 14.0 118.0 151.0 14.7 118.0 171.0 15.4 119.0 193.0 16.0 119.0 215.0 16.6 120.0 239.0 17.2 121.0 Entering Condenser (F) 100 105 110 107.0 100.0 93.7 13.4 13.5 13.5 123.0 127.0 132.0 125.0 118.0 111.0 14.3 14.5 14.6 123.0 128.0 133.0 144.0 136.0 129.0 15.1 15.4 15.6 123.0 128.0 133.0 164.0 156.0 148.0 15.8 16.2 16.6 124.0 128.0 133.0 185.0 176.0 168.0 16.6 17.1 17.4 124.0 129.0 134.0 207.0 198.0 189.0 17.2 17.8 18.3 125.0 130.0 135.0 230.0 221.0 211.0 17.9 18.6 19.1 126.0 131.0 136.0 70 146.0 11.6 92.6 166.0 12.0 92.9 187.0 12.3 93.2 209.0 12.6 93.9 233.0 12.9 94.7 257.0 13.1 95.8 284.0 13.3 97.0 80 133.0 12.3 103.0 152.0 12.9 103.0 173.0 13.4 103.0 194.0 13.8 104.0 217.0 14.2 105.0 241.0 14.6 106.0 266.0 15.0 107.0 85 127.0 12.7 108.0 145.0 13.3 108.0 165.0 13.9 108.0 187.0 14.4 109.0 209.0 14.9 110.0 232.0 15.3 111.0 257.0 15.8 112.0 70 195.0 16.0 96.0 221.0 16.7 96.8 247.0 17.4 98.1 275.0 18.1 99.7 304.0 18.8 102.0 335.0 19.5 104.0 368.0 20.3 106.0 80 180.0 17.0 106.0 204.0 17.8 106.0 229.0 18.7 108.0 256.0 19.5 109.0 284.0 20.4 111.0 313.0 21.3 113.0 344.0 22.2 115.0 85 172.0 17.4 111.0 196.0 18.3 111.0 220.0 19.3 112.0 246.0 20.2 114.0 274.0 21.1 115.0 303.0 22.1 117.0 333.0 23.1 120.0 90 165.0 17.8 116.0 188.0 18.8 116.0 212.0 19.8 117.0 237.0 20.8 119.0 264.0 21.9 120.0 292.0 22.9 122.0 321.0 23.9 124.0 Air Temperature Entering Condenser (F) 95 100 105 110 158.0 151.0 144.0 137.0 18.2 18.6 18.9 19.1 121.0 126.0 131.0 136.0 180.0 172.0 164.0 157.0 19.3 19.7 20.1 20.4 121.0 126.0 131.0 136.0 203.0 195.0 186.0 178.0 20.4 20.9 21.3 21.7 122.0 127.0 132.0 137.0 228.0 219.0 210.0 201.0 21.4 22.0 22.5 23.0 123.0 128.0 133.0 138.0 254.0 244.0 234.0 225.0 22.5 23.2 23.8 24.3 125.0 130.0 134.0 139.0 281.0 271.0 260.0 250.0 23.6 24.4 25.1 25.7 127.0 131.0 136.0 141.0 310.0 299.0 287.0 276.0 24.8 25.6 26.3 27.0 129.0 133.0 138.0 142.0 70 218.0 17.9 93.2 246.0 18.6 93.7 274.0 19.2 94.5 304.0 19.8 95.7 336.0 20.4 97.1 369.0 21.0 98.9 404.0 21.6 101.0 80 202.0 19.0 103.0 229.0 19.9 104.0 256.0 20.7 104.0 286.0 21.5 105.0 316.0 22.3 107.0 348.0 23.1 108.0 381.0 23.9 110.0 85 194.0 19.5 108.0 220.0 20.5 109.0 247.0 21.4 109.0 276.0 22.3 110.0 306.0 23.2 112.0 337.0 24.1 113.0 370.0 25.0 115.0 90 186.0 19.9 113.0 212.0 21.0 113.0 238.0 22.0 114.0 266.0 23.0 115.0 296.0 24.0 116.0 326.0 25.0 118.0 358.0 26.0 120.0 Air Temperature 95 178.0 20.3 118.0 203.0 21.5 118.0 229.0 22.6 119.0 257.0 23.7 120.0 286.0 24.8 121.0 316.0 25.9 123.0 347.0 27.0 124.0 115 87.0 13.5 137.0 104.0 14.7 138.0 121.0 15.9 138.0 140.0 16.9 138.0 160.0 17.9 139.0 180.0 18.8 140.0 202.0 19.7 141.0 120 80.4 13.5 142.0 96.5 14.8 143.0 114.0 16.0 143.0 132.0 17.1 143.0 151.0 18.2 144.0 172.0 19.3 145.0 193.0 20.3 146.0 125 73.6 13.3 147.0 89.3 14.7 148.0 106.0 16.1 148.0 124.0 17.3 148.0 143.0 18.5 149.0 163.0 19.7 150.0 184.0 20.7 150.0 120 124.0 19.6 146.0 142.0 21.1 146.0 162.0 22.5 146.0 183.0 23.9 147.0 206.0 25.4 148.0 229.0 26.9 150.0 254.0* 28.4* 152.0* 125 117.0* 19.8* 151.0* 135.0* 21.3* 151.0* 154.0* 22.8* 151.0* 175.0* 24.3* 152.0* 196.0* 25.9* 153.0* 219.0* 27.4* 155.0* 244.0* 29.0* 156.0* 120 137.0 21.3 143.0 159.0 23.0 143.0 183.0 24.7 144.0 208.0 26.3 144.0 234.0 27.9 145.0 261.0 29.5 146.0 289.0 31.1 148.0 125 129.0 21.3 148.0 150.0 23.1 148.0 173.0 24.9 149.0 198.0 26.6 149.0 223.0* 28.4* 150.0* 250.0* 30.0* 151.0* 277.0* 31.7* 153.0* 38AH054 CIRCUIT B SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 115 130.0 19.4 141.0 149.0 20.8 141.0 170.0 22.1 142.0 192.0 23.5 142.0 215.0 24.9 144.0 240.0 26.3 145.0 265.0 27.7 147.0 38AH064 CIRCUIT B SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) Entering Condenser (F) 100 105 110 170.0 162.0 153.0 20.6 20.9 21.1 123.0 128.0 133.0 194.0 185.0 177.0 21.9 22.3 22.5 123.0 128.0 133.0 220.0 211.0 201.0 23.1 23.6 24.0 124.0 129.0 134.0 247.0 237.0 227.0 24.3 24.9 25.4 125.0 130.0 134.0 275.0 265.0 254.0 25.5 26.2 26.8 126.0 131.0 136.0 305.0 294.0 283.0 26.7 27.5 28.2 127.0 132.0 137.0 335.0 324.0 312.0 27.9 28.8 29.6 129.0 134.0 139.0 115 145.0 21.2 138.0 168.0 22.8 138.0 192.0 24.4 139.0 217.0 25.9 139.0 244.0 27.4 140.0 272.0 28.9 142.0 301.0 30.4 143.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 79 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH074 CIRCUIT A SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 221.0 17.8 92.4 249.0 18.4 92.7 277.0 19.0 93.6 307.0 19.7 95.0 338.0 20.3 96.7 370.0 20.9 98.6 405.0 21.5 101.0 80 205.0 18.9 102.0 232.0 19.7 103.0 260.0 20.5 103.0 288.0 21.3 104.0 318.0 22.2 106.0 350.0 23.0 108.0 383.0 23.7 110.0 85 197.0 19.4 107.0 224.0 20.3 107.0 251.0 21.2 108.0 279.0 22.1 109.0 309.0 23.0 111.0 340.0 23.9 112.0 372.0 24.8 114.0 90 189.0 19.9 112.0 215.0 20.9 112.0 242.0 21.9 113.0 270.0 22.8 114.0 299.0 23.8 115.0 329.0 24.8 117.0 361.0 25.8 119.0 Air Temperature 95 181.0 20.3 117.0 206.0 21.4 117.0 233.0 22.5 118.0 261.0 23.5 119.0 289.0 24.6 120.0 319.0 25.7 122.0 350.0 26.8 124.0 Entering Condenser (F) 100 105 110 173.0 165.0 157.0 20.6 20.9 21.0 122.0 127.0 132.0 198.0 189.0 180.0 21.8 22.2 22.5 122.0 127.0 132.0 224.0 215.0 206.0 23.0 23.5 23.9 123.0 128.0 133.0 251.0 242.0 232.0 24.2 24.7 25.3 123.0 128.0 133.0 279.0 269.0 259.0 25.3 26.0 26.6 125.0 129.0 134.0 308.0 298.0 287.0 26.5 27.3 28.0 126.0 131.0 136.0 339.0 328.0 316.0 27.7 28.6 29.4 128.0 133.0 137.0 70 286.0 25.5 98.1 321.0 26.6 98.1 360.0 27.6 98.3 400.0 28.6 98.9 443.0 29.6 99.9 488.0 30.7 101.0 534.0 31.8 103.0 80 267.0 26.8 108.0 301.0 28.1 108.0 337.0 29.4 108.0 376.0 30.6 109.0 417.0 31.9 110.0 460.0 33.2 111.0 505.0 34.5 113.0 85 258.0 27.4 113.0 291.0 28.8 113.0 326.0 30.2 113.0 364.0 31.6 114.0 404.0 32.9 114.0 446.0 34.3 116.0 490.0 35.8 117.0 90 249.0 27.9 118.0 281.0 29.5 118.0 315.0 31.0 118.0 352.0 32.5 119.0 392.0 33.9 119.0 433.0 35.5 120.0 475.0 37.0 122.0 Air Temperature Entering Condenser (F) 95 100 105 110 240.0 231.0 222.0 214.0 28.4 28.9 29.3 29.7 123.0 128.0 133.0 138.0 271.0 261.0 252.0 242.0 30.1 30.6 31.2 31.6 123.0 128.0 133.0 138.0 305.0 294.0 283.0 273.0 31.7 32.4 33.0 33.5 123.0 128.0 133.0 138.0 341.0 329.0 317.0 306.0 33.3 34.1 34.8 35.5 124.0 129.0 134.0 139.0 379.0 366.0 354.0 341.0 34.9 35.8 36.6 37.4 124.0 129.0 134.0 139.0 419.0 405.0 392.0 379.0 36.5 37.5 38.5 39.4 125.0 130.0 135.0 140.0 461.0 446.0 432.0 418.0 38.2 39.3 40.4 41.3 127.0 131.0 136.0 141.0 115 149.0 21.2 137.0 172.0 22.8 137.0 196.0 24.3 137.0 222.0 25.8 138.0 249.0 27.2 139.0 277.0 28.7 140.0 305.0 30.2 142.0 120 140.0 21.3 142.0 163.0 23.0 142.0 187.0 24.6 142.0 212.0 26.2 143.0 239.0 27.7 143.0 266.0 29.3 145.0 294.0 30.9 146.0 125 132.0 21.3 147.0 154.0 23.1 147.0 178.0 24.8 147.0 203.0 26.5 148.0 228.0 28.2 148.0 255.0* 29.9* 149.0* 282.0* 31.5* 151.0* 120 197.0 30.4 148.0 223.0 32.5 148.0 252.0 34.6 148.0 283.0 36.7 148.0 316.0 38.9 149.0 352.0 41.0 150.0 389.0* 43.2* 151.0* 125 188.0* 30.6* 153.0* 214.0* 32.8* 153.0* 242.0* 35.0* 153.0* 272.0* 37.3* 153.0* 304.0* 39.5* 154.0* 339.0* 41.8* 155.0* 375.0* 44.1* 155.0* 38AH084 CIRCUIT A SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG 80 — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) 115 205.0 30.0 143.0 233.0 32.1 143.0 262.0 34.1 143.0 294.0 36.1 144.0 329.0 38.2 144.0 365.0 40.2 145.0 403.0 42.3 146.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH074 CIRCUIT B SST (F) 20 25 30 35 40 45 50 TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT 70 292.0 24.6 91.7 325.0 25.7 92.7 361.0 26.8 94.2 399.0 28.0 96.0 438.0 29.2 97.9 480.0 30.3 100.0 525.0 31.5 102.0 80 273.0 26.0 102.0 306.0 27.3 102.0 340.0 28.6 104.0 376.0 30.0 105.0 413.0 31.4 107.0 453.0 32.8 109.0 496.0 34.2 111.0 85 264.0 26.6 107.0 296.0 28.0 107.0 329.0 29.4 108.0 364.0 30.9 110.0 401.0 32.4 112.0 440.0 33.9 114.0 481.0 35.5 116.0 90 255.0 27.2 112.0 286.0 28.7 112.0 319.0 30.2 113.0 353.0 31.8 115.0 389.0 33.4 117.0 427.0 35.0 119.0 467.0 36.7 121.0 Air Temperature 95 246.0 27.8 117.0 276.0 29.3 117.0 308.0 30.9 118.0 342.0 32.6 119.0 377.0 34.3 121.0 414.0 36.1 123.0 453.0 37.8 125.0 Entering Condenser (F) 100 105 110 237.0 228.0 219.0 28.3 28.7 29.2 122.0 126.0 131.0 267.0 257.0 248.0 29.9 30.5 31.0 122.0 127.0 132.0 298.0 288.0 277.0 31.6 32.3 32.9 123.0 128.0 132.0 330.0 319.0 308.0 33.4 34.1 34.8 124.0 129.0 134.0 365.0 353.0 341.0 35.2 36.0 36.8 126.0 131.0 135.0 401.0 388.0 375.0 37.0 38.0 38.8 128.0 132.0 137.0 439.0 425.0 411.0 38.9 40.0 40.9 130.0 134.0 139.0 115 211.0 29.6 136.0 238.0 31.5 137.0 267.0 33.5 137.0 298.0 35.5 138.0 329.0 37.6 140.0 363.0 39.7 142.0 398.0 41.9 144.0 120 202.0 29.9 142.0 229.0 31.9 142.0 257.0 34.0 142.0 287.0 36.1 143.0 318.0 38.3 145.0 350.0 40.5 146.0 384.0 42.8 148.0 125 194.0 30.3 147.0 219.0 32.3 147.0 247.0 34.5 147.0 276.0 36.7 148.0 306.0 38.9 149.0 338.0* 41.2* 151.0* 371.0* 43.6* 153.0* 70 288.0 25.2 96.1 323.0 26.3 96.2 361.0 27.3 96.5 402.0 28.3 97.3 444.0 29.3 98.5 488.0 30.4 100.0 533.0 31.5 102.0 80 269.0 26.5 106.0 303.0 27.8 106.0 339.0 29.1 106.0 378.0 30.3 107.0 418.0 31.6 108.0 460.0 32.9 110.0 504.0 34.2 111.0 85 260.0 27.1 111.0 293.0 28.5 111.0 328.0 29.9 111.0 366.0 31.3 112.0 405.0 32.6 113.0 447.0 34.0 114.0 490.0 35.5 116.0 90 251.0 27.7 116.0 283.0 29.2 116.0 317.0 30.7 116.0 354.0 32.2 117.0 393.0 33.6 118.0 433.0 35.1 119.0 475.0 36.7 121.0 Air Temperature 95 242.0 28.2 121.0 273.0 29.8 121.0 306.0 31.4 121.0 342.0 33.0 122.0 380.0 34.6 123.0 420.0 36.2 124.0 461.0 37.9 125.0 Entering Condenser (F) 100 105 110 233.0 224.0 215.0 28.7 29.1 29.5 126.0 131.0 136.0 263.0 253.0 244.0 30.4 30.9 31.4 126.0 131.0 136.0 296.0 285.0 275.0 32.1 32.7 33.3 126.0 131.0 136.0 331.0 319.0 308.0 33.8 34.5 35.2 127.0 132.0 137.0 368.0 355.0 343.0 35.5 36.3 37.1 127.0 132.0 137.0 406.0 393.0 379.0 37.2 38.2 39.1 129.0 133.0 138.0 446.0 432.0 418.0 39.0 40.1 41.1 130.0 135.0 140.0 115 207.0 29.9 141.0 234.0 31.9 141.0 264.0 33.9 141.0 296.0 35.9 142.0 330.0 37.9 142.0 366.0 40.0 143.0 404.0 42.1 144.0 120 198.0 30.2 146.0 225.0 32.3 146.0 254.0 34.4 146.0 285.0 36.5 146.0 318.0 38.6 147.0 353.0 40.8 148.0 390.0 43.0 149.0 125 190.0* 30.5* 151.0* 216.0* 32.7* 151.0* 244.0* 34.9* 151.0* 274.0* 37.1* 151.0* 306.0* 39.3* 152.0* 340.0* 41.5* 153.0* 375.0* 43.8* 154.0* 38AH084 CIRCUIT B SST (F) 20 25 30 35 40 45 50 CMP SDT SST TCG — — — — TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT TCG CMP SDT LEGEND Compressor Power, kW Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 81 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH094 CIRCUIT A SST (F) 20 25 30 35 40 45 50 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 70 366.0 29.7 93.9 91.7 411.0 30.9 95.0 92.1 457.0 32.2 96.7 93.0 505.0 33.6 98.7 94.3 556.0 35.0 101.0 95.7 608.0 36.4 104.0 97.4 663.0 37.8 106.0 99.1 80 338.0 31.4 104.0 102.0 382.0 33.0 105.0 102.0 427.0 34.5 106.0 103.0 474.0 36.1 108.0 104.0 522.0 37.8 110.0 106.0 573.0 39.4 112.0 108.0 626.0 41.1 115.0 109.0 85 324.0 32.3 109.0 107.0 367.0 34.0 109.0 108.0 412.0 35.7 111.0 108.0 458.0 37.4 112.0 109.0 506.0 39.2 115.0 111.0 556.0 41.0 117.0 113.0 608.0 42.8 119.0 114.0 90 310.0 33.0 114.0 113.0 352.0 34.8 114.0 113.0 396.0 36.7 115.0 113.0 442.0 38.6 117.0 114.0 489.0 40.5 119.0 116.0 538.0 42.4 121.0 118.0 589.0 44.4 124.0 119.0 Air Temperature 95 295.0 33.6 119.0 118.0 337.0 35.6 119.0 118.0 381.0 37.6 120.0 118.0 426.0 39.6 122.0 119.0 472.0 41.7 124.0 121.0 520.0 43.8 126.0 123.0 570.0 45.9 128.0 124.0 Entering Condenser (F) 100 105 110 281.0 266.0 251.0 34.1 34.4 34.7 124.0 129.0 134.0 123.0 128.0 133.0 322.0 307.0 291.0 36.3 36.8 37.3 124.0 129.0 134.0 123.0 128.0 133.0 365.0 349.0 333.0 38.4 39.2 39.8 125.0 130.0 134.0 123.0 128.0 133.0 409.0 392.0 376.0 40.6 41.5 42.3 126.0 131.0 136.0 124.0 129.0 134.0 455.0 437.0 420.0 42.8 43.9 44.8 128.0 133.0 137.0 126.0 131.0 135.0 502.0 484.0 465.0 45.1 46.2 47.4 130.0 135.0 139.0 127.0 132.0 137.0 551.0 532.0 512.0 47.3 48.7 49.9 133.0 137.0 142.0 129.0 134.0 139.0 70 349.0 27.0 91.9 89.8 392.0 28.1 93.0 90.2 437.0 29.3 94.7 91.2 484.0 30.6 96.7 92.5 534.0 38.1 98.9 94.0 586.0 33.0 101.0 95.6 640.0 34.3 104.0 97.3 80 321.0 28.8 102.0 100.0 363.0 30.1 102.0 100.0 407.0 31.6 104.0 101.0 452.0 33.0 106.0 103.0 500.0 34.5 108.0 104.0 550.0 36.0 110.0 106.0 602.0 37.5 113.0 107.0 85 308.0 29.6 107.0 105.0 349.0 31.1 107.0 105.0 392.0 32.7 109.0 106.0 436.0 34.3 110.0 108.0 483.0 35.9 112.0 109.0 532.0 37.5 115.0 111.0 583.0 39.2 117.0 112.0 90 294.0 30.4 112.0 110.0 335.0 32.0 112.0 111.0 377.0 33.7 113.0 111.0 420.0 35.4 115.0 112.0 466.0 37.1 117.0 114.0 514.0 38.9 119.0 116.0 564.0 40.7 122.0 117.0 Air Temperature 95 280.0 31.0 116.0 116.0 320.0 32.8 117.0 116.0 361.0 34.6 118.0 116.0 404.0 36.4 119.0 117.0 449.0 38.3 121.0 119.0 495.0 40.2 124.0 120.0 544.0 42.1 126.0 122.0 Entering Condenser (F) 100 105 110 267.0 253.0 240.0 31.6 32.1 32.5 121.0 126.0 131.0 121.0 126.0 131.0 306.0 291.0 277.0 33.6 34.2 34.7 122.0 127.0 132.0 121.0 126.0 131.0 346.0 331.0 316.0 35.5 36.3 37.0 123.0 127.0 132.0 121.0 126.0 131.0 388.0 372.0 356.0 37.4 38.4 39.2 124.0 129.0 133.0 122.0 127.0 132.0 432.0 415.0 398.0 39.4 40.5 41.5 126.0 130.0 135.0 124.0 128.0 133.0 478.0 460.0 442.0 41.5 42.6 43.8 128.0 132.0 137.0 125.0 130.0 135.0 525.0 506.0 487.0 43.5 44.8 46.1 130.0 135.0 139.0 127.0 132.0 137.0 115 236.0 34.8 139.0 138.0 276.0 37.6 139.0 138.0 317.0 40.3 139.0 138.0 359.0 43.0 140.0 139.0 402.0 45.7 142.0 140.0 447.0 48.4 144.0 142.0 493.0 51.1 146.0 143.0 120 221.0 34.7 144.0 143.0 260.0 37.8 144.0 143.0 300.0 40.7 144.0 143.0 342.0 43.6 145.0 144.0 384.0 46.4 146.0 145.0 428.0 49.3 148.0 146.0 473.0 52.2 150.0 148.0 125 207.0 34.5 149.0 148.0 244.0 37.8 149.0 148.0 284.0 41.0 149.0 148.0 325.0 44.1 150.0 149.0 367.0 47.1 151.0 150.0 410.0 50.1 153.0 151.0 454.0 53.2 155.0* 153.0 38AH104 CIRCUIT A SST (F) 20 25 30 35 40 45 50 CMP SCT SDT SST TCG 82 — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT LEGEND Compressor Power, kW Saturated Condensing Temperature (F) Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) 115 226.0 32.8 136.0 136.0 263.0 35.2 137.0 136.0 301.0 37.6 137.0 136.0 340.0 40.0 138.0 137.0 381.0 42.4 140.0 138.0 424.0 44.8 141.0 140.0 468.0 47.3 144.0 141.0 120 213.0 32.9 141.0 141.0 248.0 35.6 141.0 141.0 286.0 38.1 142.0 141.0 324.0 40.7 143.0 142.0 364.0 43.2 144.0 143.0 406.0 45.8 146.0 144.0 449.0 48.4 148.0 146.0 125 200.0 33.0 146.0 146.0 234.0 35.8 146.0 146.0 271.0 38.6 147.0 146.0 308.0 41.3 148.0 147.0 348.0 44.0 149.0 148.0 388.0 46.7 150.0 149.0 431.0 49.4 152.0 151.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH094 CIRCUIT B SST (F) 20 25 30 35 40 45 50 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 70 291.0 24.6 92.1 90.4 327.0 25.6 92.4 90.2 364.0 26.6 93.3 90.5 402.0 27.7 94.7 91.2 443.0 28.8 96.5 92.3 485.0 29.9 98.6 93.6 530.0 31.1 101.0 95.1 80 273.0 26.0 102.0 101.0 307.0 27.2 102.0 100.0 342.0 28.4 103.0 101.0 379.0 29.7 104.0 101.0 418.0 31.0 106.0 102.0 458.0 32.4 108.0 104.0 501.0 33.7 110.0 105.0 85 264.0 26.7 107.0 106.0 296.0 28.0 107.0 106.0 331.0 29.3 108.0 106.0 367.0 30.7 109.0 107.0 405.0 32.1 111.0 108.0 445.0 33.6 112.0 109.0 487.0 35.0 114.0 110.0 90 254.0 27.2 112.0 111.0 286.0 28.7 112.0 111.0 320.0 30.1 113.0 111.0 356.0 31.6 114.0 112.0 393.0 33.1 115.0 113.0 432.0 34.7 117.0 114.0 473.0 36.3 119.0 115.0 Air Temperature 95 245.0 27.8 117.0 116.0 277.0 29.3 117.0 116.0 310.0 30.9 118.0 116.0 345.0 32.4 119.0 117.0 381.0 34.1 120.0 118.0 419.0 35.7 122.0 119.0 459.0 37.4 124.0 120.0 Entering Condenser (F) 100 105 110 236.0 228.0 219.0 28.3 28.8 29.2 122.0 127.0 132.0 121.0 126.0 131.0 267.0 257.0 247.0 29.9 30.5 31.0 122.0 127.0 132.0 121.0 126.0 131.0 299.0 289.0 278.0 31.6 32.3 32.9 123.0 127.0 132.0 121.0 126.0 131.0 333.0 322.0 310.0 33.2 34.0 34.7 123.0 128.0 133.0 122.0 127.0 132.0 369.0 356.0 344.0 35.0 35.8 36.6 125.0 129.0 134.0 122.0 127.0 132.0 406.0 393.0 380.0 36.7 37.7 38.6 126.0 131.0 136.0 124.0 129.0 134.0 445.0 431.0 417.0 38.5 39.6 40.6 128.0 133.0 137.0 125.0 130.0 135.0 70 398.0 31.4 93.5 90.9 445.0 32.9 95.1 91.7 495.0 34.5 97.1 92.9 548.0 36.1 99.4 94.4 603.0 37.7 102.0 96.0 661.0 39.4 105.0 97.8 723.0 41.2 108.0 99.6 80 368.0 33.4 103.0 101.0 414.0 35.1 104.0 102.0 462.0 36.9 106.0 103.0 512.0 38.8 108.0 104.0 565.0 40.7 111.0 106.0 620.0 42.7 113.0 108.0 679.0 44.7 116.0 110.0 85 353.0 34.3 108.0 106.0 398.0 36.2 109.0 107.0 445.0 38.1 111.0 108.0 494.0 40.1 113.0 109.0 546.0 42.2 115.0 111.0 600.0 44.3 118.0 113.0 657.0 46.4 120.0 115.0 90 339.0 35.2 113.0 111.0 383.0 37.2 114.0 112.0 428.0 39.2 115.0 113.0 476.0 41.4 117.0 114.0 527.0 43.6 120.0 116.0 580.0 45.8 122.0 118.0 635.0 48.1 125.0 120.0 Air Temperature 95 324.0 36.0 118.0 116.0 367.0 38.1 119.0 117.0 412.0 40.3 120.0 118.0 459.0 42.5 122.0 119.0 508.0 44.9 124.0 121.0 559.0 47.2 126.0 123.0 614.0 49.6 129.0 125.0 Entering Condenser (F) 100 105 110 310.0 296.0 283.0 36.7 37.4 38.0 123.0 128.0 133.0 122.0 127.0 132.0 352.0 337.0 322.0 39.0 39.8 40.5 123.0 128.0 133.0 122.0 127.0 132.0 396.0 380.0 364.0 41.3 42.2 43.0 125.0 129.0 134.0 123.0 128.0 133.0 441.0 424.0 407.0 43.6 44.7 45.7 126.0 131.0 136.0 124.0 129.0 134.0 489.0 471.0 453.0 46.1 47.3 48.4 128.0 133.0 137.0 126.0 131.0 135.0 539.0 520.0 500.0 48.6 49.9 51.1 131.0 135.0 140.0 128.0 132.0 137.0 592.0 571.0 550.0 51.2 52.6 54.0 133.0 138.0 142.0 130.0 134.0 139.0 115 210.0 29.6 137.0 136.0 238.0 31.5 137.0 136.0 268.0 33.5 137.0 136.0 299.0 35.4 138.0 137.0 332.0 37.4 139.0 137.0 367.0 39.5 140.0 138.0 403.0 41.6 142.0 140.0 120 202.0 30.0 142.0 142.0 228.0 32.0 142.0 141.0 257.0 34.0 142.0 141.0 288.0 36.0 143.0 142.0 320.0 38.1 144.0 142.0 354.0 40.3 145.0 143.0 389.0 42.5 147.0 145.0 125 193.0 30.3 147.0 147.0 219.0 32.4 147.0 146.0 247.0 34.5 147.0 146.0 277.0 36.6 148.0 147.0 308.0 38.8 149.0 147.0 341.0 41.1 150.0 148.0 375.0 43.4 151.0 149.0 38AH104 CIRCUIT B SST (F) 20 25 30 35 40 45 50 CMP SCT SDT SST TCG — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT LEGEND Compressor Power, kW Saturated Condensing Temperature (F) Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) 115 269.0 38.5 138.0 137.0 308.0 41.2 138.0 137.0 348.0 43.8 139.0 138.0 391.0 46.6 140.0 139.0 435.0 49.4 142.0 140.0 481.0 52.3 144.0 142.0 530.0 55.3 146.0 144.0 120 256.0 39.0 142.0 142.0 293.0 41.8 143.0 142.0 333.0 44.6 144.0 143.0 374.0 47.4 145.0 144.0 417.0 50.4 147.0 145.0 462.0 53.4 149.0 147.0 509.0 56.5 151.0 148.0 125 243.0 39.4 147.0 147.0 279.0 42.3 148.0 147.0 317.0 45.2 148.0 148.0 357.0 48.2 150.0 148.0 399.0 51.3 151.0 150.0 443.0 54.5 153.0 151.0 488.0 57.7 155.0* 153.0 *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. 83 Performance data — 38AH044-134 (cont) CONDENSING UNIT CIRCUIT AND MODULE RATINGS — ENGLISH (cont) 38AH124 MODULE 124A OR 124B; 38AH134 MODULE 134A SST (F) 20 25 30 35 40 45 50 TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 70 417.0 33.6 93.3 92.4 470.0 34.9 94.0 92.8 525.0 36.2 95.0 93.5 584.0 37.5 96.4 94.6 645.0 38.8 98.1 95.9 709.0 40.0 100.0 97.5 776.0 41.3 102.0 99.3 80 386.0 35.7 103.0 103.0 436.0 37.3 104.0 103.0 490.0 39.0 105.0 103.0 546.0 40.6 106.0 104.0 604.0 42.2 108.0 106.0 666.0 43.9 109.0 107.0 730.0 45.5 112.0 109.0 85 370.0 36.7 108.0 108.0 420.0 38.5 109.0 108.0 472.0 40.3 110.0 108.0 526.0 42.1 111.0 109.0 584.0 43.9 112.0 111.0 644.0 45.8 114.0 112.0 707.0 47.6 116.0 114.0 90 355.0 37.6 113.0 113.0 403.0 39.6 114.0 113.0 454.0 41.6 114.0 113.0 507.0 43.5 116.0 114.0 563.0 45.5 117.0 116.0 622.0 47.5 119.0 117.0 684.0 49.5 121.0 119.0 Air Temperature 95 339.0 38.4 118.0 118.0 386.0 40.5 119.0 118.0 436.0 42.7 119.0 118.0 489.0 44.8 120.0 119.0 543.0 47.0 122.0 120.0 601.0 49.1 123.0 122.0 661.0 51.3 125.0 123.0 Entering Condenser (F) 100 105 110 324.0 309.0 294.0 39.0 39.6 40.1 123.0 128.0 133.0 123.0 128.0 133.0 370.0 354.0 337.0 41.4 42.2 42.8 123.0 128.0 133.0 123.0 128.0 133.0 419.0 401.0 384.0 43.7 44.7 45.5 124.0 129.0 134.0 123.0 128.0 133.0 470.0 451.0 432.0 46.0 47.2 48.2 125.0 130.0 135.0 124.0 129.0 134.0 523.0 503.0 483.0 48.4 49.7 50.8 126.0 131.0 136.0 125.0 130.0 135.0 579.0 558.0 537.0 50.7 52.2 53.5 128.0 133.0 138.0 127.0 131.0 136.0 638.0 616.0 593.0 53.1 54.7 56.2 130.0 135.0 139.0 128.0 133.0 138.0 115 279.0 40.5 138.0 138.0 321.0 43.4 138.0 138.0 366.0 46.3 139.0 138.0 414.0 49.2 140.0 139.0 463.0 52.0 141.0 140.0 516.0 54.9 142.0 141.0 570.0 57.8 144.0 143.0 120 264.0 40.8 143.0 143.0 305.0 43.9 143.0 143.0 349.0 47.0 144.0 143.0 395.0 50.0 144.0 144.0 444.0 53.0 146.0 145.0 494.0 56.1 147.0 146.0 548.0 59.1 149.0 147.0 125 249.0 41.0 148.0 148.0 289.0 44.3 148.0 148.0 331.0 47.5 149.0 148.0 376.0 50.7 149.0 149.0 424.0 54.0 150.0 150.0 473.0 57.2 152.0 151.0 525.0 60.4 153.0 152.0 80 478.0 44.9 102.0 97.7 538.0 47.0 102.0 98.5 600.0 49.1 103.0 99.7 665.0 51.3 105.0 101.0 733.0 53.5 107.0 103.0 804.0 55.7 109.0 104.0 880.0 57.9 111.0 106.0 85 461.0 46.1 107.0 103.0 520.0 48.3 107.0 103.0 580.0 50.6 108.0 105.0 644.0 53.0 110.0 106.0 710.0 55.4 111.0 107.0 781.0 57.8 113.0 109.0 855.0 60.2 115.0 111.0 90 444.0 47.1 112.0 108.0 502.0 49.5 112.0 108.0 561.0 52.0 113.0 109.0 623.0 54.6 114.0 111.0 689.0 57.2 116.0 112.0 757.0 59.8 118.0 114.0 829.0 62.4 120.0 116.0 Air Temperature 95 427.0 48.0 117.0 113.0 483.0 50.7 117.0 113.0 542.0 53.4 118.0 114.0 603.0 56.1 119.0 116.0 667.0 58.9 121.0 117.0 734.0 61.7 122.0 119.0 804.0 64.6 124.0 120.0 Entering Condenser (F) 100 105 110 410.0 393.0 376.0 48.9 49.6 50.2 122.0 127.0 132.0 118.0 123.0 128.0 465.0 447.0 428.0 51.7 52.7 53.5 122.0 127.0 132.0 118.0 123.0 128.0 522.0 503.0 484.0 54.6 55.7 56.7 123.0 127.0 132.0 119.0 124.0 129.0 582.0 562.0 541.0 57.5 58.8 60.0 124.0 128.0 133.0 120.0 125.0 130.0 645.0 623.0 601.0 60.5 62.0 63.4 125.0 130.0 135.0 122.0 127.0 131.0 710.0 687.0 663.0 63.5 65.2 66.8 127.0 132.0 136.0 123.0 128.0 133.0 779.0 754.0 729.0 66.6 68.5 70.3 129.0 134.0 138.0 125.0 130.0 134.0 115 359.0 50.8 137.0 133.0 410.0 54.3 137.0 133.0 464.0 57.7 137.0 134.0 520.0 61.2 138.0 135.0 579.0 64.7 139.0 136.0 640.0 68.3 141.0 137.0 704.0 72.0 143.0 139.0 120 342.0 51.3 142.0 138.0 392.0 54.9 142.0 138.0 445.0 58.6 142.0 139.0 500.0 62.2 143.0 139.0 557.0 66.0 144.0 141.0 617.0 69.7 145.0 142.0 679.0 73.6 147.0 144.0 125 326.0 51.6 147.0 143.0 374.0 55.5 147.0 143.0 425.0 59.3 147.0 144.0 479.0 63.2 148.0 144.0 535.0 67.1 149.0 145.0 593.0 71.1 150.0 147.0 654.0 75.1 152.0 148.0 38AH134 MODULE 134B SST (F) 20 25 30 35 40 45 50 CMP SCT SDT SST TCG 84 — — — — — TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT TCG CMP SDT SCT 70 513.0 42.4 92.0 87.6 575.0 44.1 92.7 88.6 639.0 45.8 93.8 90.0 706.0 47.6 95.4 91.5 777.0 49.4 97.2 93.0 852.0 51.2 99.2 94.6 931.0 52.9 101.0 96.3 LEGEND Compressor Power, kW Saturated Condensing Temperature (F) Saturated Discharge Temperature (leaving compressor) (F) Saturated Suction Temperature (entering condensing unit) Total Cooling Capacity, Gross (1000 Btuh) *May require replacement of the high-pressure cutout switches with switches of a higher setting. NOTES: 1. Ratings are based on 15 F superheat and use of R-22 refrigerant. 2. Ratings include suction line losses due to an accumulator. Typical piping and wiring — 38AH044-134 ROOFTOP INSTALLATION — UNIT 38AH104 WITH SINGLE AIR HANDLER SHOWN LEGEND TXV — Thermostatic Expansion Valve Line Voltage Piping Double Riser Piping (If Required) *Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. Face-split connection shown; row-split connection also possible. 4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor. 85 Typical piping and wiring — 38AH044-134 (cont) GROUND-LEVEL INSTALLATION — UNIT 38AH104 WITH SINGLE AIR HANDLER SHOWN LEGEND TXV — Thermostatic Expansion Valve Line Voltage Piping *Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation. Face-split connection shown; row-split connection also possible. 4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor. 86 Electrical data — 38AH044-134 38AH044-084 UNIT 38AH VOLTAGE DESIGNATION 044 054 064 074 084 COMPRESSOR MODEL (A/B DUAL-CIRCUIT) (A1/A2 SINGLE-CIRCUIT) 800 (PW) 900 300 (PW) 900 300 (PW) 900 300 (PW) 900 300 (PW) 900 300 (PW) NAMEPLATE VOLTS-PH-Hz SUPPLY VOLTAGE* 06E-250/265 06E-265/275 06E-275/299 06E-299/299 COMPRESSOR† Min Max MCA MOCP ICF 198 348 325 342 325 342 325 342 325 342 325 254 440 367 440 367 440 367 440 367 440 367 174.6 100.0 100.0 101.1 107.0 114.1 129.8 140.6 170.8 165.2 205.3 225 100 125 125 150 150 175 200 250 225 250 296.7 219.6 165.9 269.6 198.9 335.6 230.5 403.8 300.4 428.4 334.9 230-3-50 380/415-3-50 346-3-50 380/415-3-50 346-3-50 380/415-3-50 346-3-50 380/415-3-50 346-3-50 380/415-3-50 346-3-50 06E-250/250 POWER SUPPLY A RLA 67.9 34.6 33.3 34.6 33.3 43.6 44.9 46.8 53.8 65.4 79.5 B LRA 207 173 115 173 115 223 148 280 168 345 229 RLA 67.9 34.6 33.3 43.6 44.9 46.8 53.8 65.4 79.5 65.4 79.5 LRA 207 173 115 223 148 280 168 345 229 345 229 38AH094,104 SUPPLY COMPRESSOR NAMEPLATE VOLTAGE* UNIT VOLTAGE A1/A2/B1/B2 38AH DESIGNATION VOLTS-PH-Hz MODEL NO. Min Max 094 104 300 (PW) 900 300 (PW) 900 06E-275/250/ 299/— 06E-265/250/ 265/265 346-3-50 380/415-3-50 346-3-50 380/415-3-50 325 342 325 342 380 440 380 440 POWER SUPPLY MCA MOCP ICF 212.9 181.2 205.6 194.3 250 225 250 225 343 444 298 363 COMPRESSOR† A1 RLA LRA 53.8 168 46.8 280 44.9 148 43.6 223 A2 RLA LRA 33.3 115 34.6 173 33.3 229 34.6 173 B1 B2 RLA LRA RLA LRA 79.5 229 — — 65.4 345 — — 44.9 148 49.9 148 43.6 223 43.6 223 38AH124,134 UNIT 38AH MODULE 124A 124B 134A 134B VOLTAGE DESIGNATION 300 (PW) 900 300 (PW) 900 COMPRESSOR A1/A2 MODEL NO. 06E-275/265 06E-299/275 NAMEPLATE VOLTS-PH-Hz SUPPLY VOLTAGE* POWER SUPPLY** Min Max MCA MOCP ICF 346-3-50 325 367 129.8 175 380/415-3-50 346-3-50 380/415-3-50 342 325 342 440 367 440 114.1 170.8 140.6 150 250 200 COMPRESSOR† A1 A2 231 RLA 53.8 LRA 168 RLA 44.9 LRA 148 336 300 404 46.8 79.5 65.4 280 229 345 43.6 53.8 46.8 223 168 280 See Legend and Notes on page 88. 87 Electrical Data — 38AH044-134 (cont) FANS UNIT/MODULE 38AH 044 054 064 074 084 094 104 CONTROL CIRCUIT CONDENSER FAN MOTORS Nameplate Qty Hp Total (No.) FLA Each Volts-Ph-Hz kW 230-3-50 (1,2) 5.5 (3,4) 5.4 380/415-3-50 4 1 6.2 (1-4) 3.0 346-3-50 (1-4) 4.4 380/415-3-50 4 (1-4) 3.0 1 6.2 346-3-50 (1-4) 4.4 380/415-3-50 4 (1-4) 3.0 1 6.2 346-3-50 (1-4) 4.4 380/415-3-50 6 (1-6) 3.0 1 9.3 346-3-50 (1-6) 4.4 380/415-3-50 6 (1-6) 3.0 1 9.3 346-3-50 (1-6) 4.4 380/415-3-50 (1-6) 4.4 6 1 9.4 346-3-50 (1-6) 3.0 380/415-3-50 6 (1-6) 4.4 1 9.5 346-3-50 (1-6) 3.0 124A 124B 134A 380/415-3-50 346-3-50 4 1 6.4 (1-4) 4.4 (1-4) 3.0 134B 380/415-3-50 346-3-50 6 1 9.2 (1-6) 4.4 (1-6) 3.0 38AH 044-134 -800 -300 -900 UNIT POWER V-Ph-Hz 230-3-50 346-3-50 380/415-3-50 CONTROL POWER V-Ph-Hz Min Max 230-1-50 207 253 200-1-50 180 220 230-1-50 207 253 AMPS 2.0 2.4 2.0 LEGEND (for pages 87 and 88) AWG FLA ICF — American Wire Gage — Full Load Amps — Maximum Instantaneous Current Flow During Starting. (The point in the starting sequence where the sum of the LRA for the starting compressors, plus the total RLA for all running compressors plus the FLA for all running fan motors is maximum.) IFC — Indoor-Fan Contactor kcmil — Thousand Circular Mils LLS — Liquid Line Solenoid LRA — Locked Rotor Amps MCA — Minimum Circuit Amps (used for sizing; complies with National Electrical Code [NEC] section 430-24, U.S.A.) MOCP — Maximum Overcurrent Protection (used for sizing disconnect; complies with NEC Article 440-22, U.S.A.) PW — Part Wind RLA — Rated Load Amps *Units are suitable for use on electrical systems where voltage supplied to unit terminals is within listed minimum to maximum limits. †Compressors are across-the-line start unless voltage designation shows (PW). **38AH124 and 134 units require a separate power supply for each unit module. NOTES: 1. Maximum allowable phase imbalance: Voltage — 2% Amps — 10% 2. Maximum incoming wire size for terminal block is 500 kcmil. 3. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for each terminal block is 500 kcmil. 4. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be class 1 wiring. 88 5. Field-supplied components (IFC, LLS-A, and LLS-B) must have a maximum sealed coil rating of 30 va each or less (0.13 amp at 230 vac). Thermostats must have a minimum pilot duty rating as follows: 38AH VA (Each Stage) AMPS CONTROL CIRCUIT VOLTAGE 044-084 094 104 124 134 300 275 325 300 300 1.30 1.15 1.35 1.30 1.30 240 6. Units have the following va of power available for field-installed accessories: 38AH044-084 — 175 va 38AH094 — 140 va 38AH104 — 130 va 38AH124,134 — 175 va each module 7. To minimize voltage drop, the following wire sizes are recommended: LENGTH (Ft) Up to 50 50-75 More Than 75 INSULATED WIRE — AWG (35 C Minimum) No. 18 No. 16 No. 14 8. Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module has a control box. 9. All fans are protected by a single circuit breaker. Controls — 38AH044-084 Operating sequence Circuits A1 and B1 are controlled by independent circuitry. It is therefore possible to maintain partial cooling capability even if one compressor is inoperable. NOTE: Single-circuit units do not have independent control circuitry. On a call for cooling, the first-stage cooling thermostat TC1 closes, energizing the first stage of the condenser fans and timer motor TM-A (TM for single-circuit units). After 12 seconds, the timer energizes lead compressor contactor C-A1 and the lead compressor starts. (Circuit A compressor is the lead on dual-circuit units, and compressor A1 is the lead on single-circuit units.) At the same time, solenoid drop relay SDR2 energizes and closes its contacts, which energizes and opens liquid line solenoid valve LLS-A (LLS-A1 for single-circuit units). Circuit A (compressor A1 for singlecircuit units) is now operational. A set of bypass contacts in timer TM-A allows the circuit A compressor (compressor A1 for single-circuit units) 40 seconds to build sufficient oil pressure. If the oil pressure is insufficient after 40 seconds, circuit A (compressor A1 for single-circuit units) shuts down and must be reset manually. A second set of bypass contacts in timer TM-A (TM for single-circuit units) allows the refrigerant circuit 21⁄2 minutes to build sufficient low-side pressure. This time delay is a start-up feature for low ambient conditions; no accessory is required. If refrigerant circuit pressure is insufficient to close the low-pressure switch after 21⁄2 minutes, the circuit A compressor (compressor A1 for single-circuit units) shuts down for 51⁄2 minutes and then automatically attempts to restart. No manual reset is required. Dual-circuit units — If circuit A is insufficient for the cooling requirements, second-stage thermostat TC2 closes to bring circuit B on line. Circuit B follows the same sequence of operation as circuit A, except a relay delays circuit B compressor start-up for 40 seconds after a call for cooling. Because circuit A has a 12-second delay after TC1 closes, and circuit B has a 40-second delay after TC2 closes, the two compressors cannot start at the same time. Optional single-circuit units — If compressor A1 is insufficient for the cooling requirements, second-stage thermostat TC2 closes, which opens liquid line solenoid valve LLS-A2. Compressor A2 starts only after the D-D2 contacts in timer TM close (approximately 21⁄2 minutes after compressor A1 is energized) and the suction pressure is sufficient to close capacity control pressure switches CCPS1 and CCPS2. All units — When the fan switch on the thermostat is set for automatic operation (AUTO), the field-supplied indoorfan contactor (IFC) is cycled with the lead compressor. If the fan switch is set at the continuous position (CONT), the IFC is energized as long as the unit power is on. NOTE: Liquid line solenoid valves must be field-supplied and installed at the evaporator for both dual- and optional single-circuit units. 89 Controls — 38AH094-134 Operating sequence Units are controlled with electromechanical components. Each refrigeration circuit is operated by an independent timer motor which controls the operation sequence of each circuit. It is possible to maintain partial cooling capability even if one circuit is inoperable. On a call for cooling, first stage cooling thermostat TC1 closes. Condenser fans and timer motor (TM) are energized. After approximately 7 seconds, timer contacts E-E1 close. Approximately 12 seconds after TC1 closes, normally open timer contacts B-B1 close for 1 second. This energizes compressor A1 contacts CA1 and starts the compressor. At the same time, solenoid drop relays (SDRs) and liquid line solenoid valve no. 1 (LLS-A1) open, and timer relay no. 1 (TR1) is energized. Normally open TR1 contacts close, completing a circuit around B-B1 and through compressor A1 contactors to maintain compressor operation when B-B1 contacts open. Contacts E-E1 remain closed for approximately 40 seconds to bypass the oil pressure switch. If oil pressure is insufficient when contacts E-E1 open, the compressor stops, the timer cycles off, and the control circuit locks out. At start-up, timer motor contacts D-D1 are closed, bypassing low-pressure relay contacts LPR-A for 21⁄2 minutes. This provides a winter start-up feature. Approximately 21⁄2 minutes after TC1 closes, timer contacts D-D1 open and D-D2 close. If pressure is insufficient to close the low-pressure switch, the low-pressure switch relay remains open, the compressor shuts down, and the Time Guardt control is initiated. Time Guard control prevents compressor from restarting for 5 minutes after the demand for cooling is satisfied. 90 Units 38AH094 and 104 — If circuit A operation is insufficient for the cooling requirements, the thermostat second stage TC2 closes to bring circuit B on-line for cooling. This circuit follows the same sequence of operation as the lead circuit, except a 60-second time-delay relay (TDR) delays compressor start-up for 60 seconds after the call for cooling. Modules 124A, 124B, 134A, and 134B — If compressor A1 is insufficient for the cooling requirements, the thermostat second stage closes, which opens the liquid line solenoid valve LLS-A2. Compressor A2 starts only after D-D2 contacts in the timer close and the suction pressure is sufficient to close the capacity control switches. All units — When the fan switch is set for automatic (AUTO) operation, the indoor-fan contactor (IFC) is cycled with the lead compressor. If the fan switch is set for continuous (CONT), the IFC is energized as long as the unit power is on. Restart after stoppage by safety control — The highpressure switch, compressor discharge gas thermostats, and the oil pressure switch must be reset manually by breaking the control power supply at any of the following points: Control circuit fuse, fan motor circuit breaker, or thermostat. Restart follows the Time Guardt control 5-minute delay. Stoppage by low-pressure switch results in Time Guard control 5-minute delay, then unit attempts to restart. The compressor motor overcurrent protectors are manual-reset circuit breakers. Reset of control circuit may also be necessary. Typical control wiring schematic — 38AH044-134 24-V THERMOSTAT CONTROL WIRING — DUAL-CIRCUIT UNITS 38AH044-084 CR HD IFC IFR kcmil LLS R RV TB LEGEND Control Relay Heating Device Indoor Fan Contactor Indoor-Fan Relay Thousand Circular Mils Liquid Line Solenoid Heating Relay (fieldsupplied 24-v sealed coil, 10 va maximum rating) — Reversing Valve — Terminal Block Factory Wiring Field Wiring — — — — — — — *Jumper removed only when separate 24-v transformer power source is used to power the 33CSUCE-06 relay pack. †To control heating device and provide automatic indoor-fan operation on heating. NOTE: Field-supplied liquid line solenoid valves installed at the evaporator are required on all units. Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac. 91 Typical control wiring schematic — 38AH044-134 (cont) 24-V THERMOSTAT CONTROL WIRING — UNITS 38AH094 AND 104 CR HD IFC IFR LLS R RV TB 92 LEGEND Control Relay Heating Device Indoor Fan Contactor Indoor-Fan Relay Liquid Line Solenoid Heating Relay (fieldsupplied 24-v sealed coil, 10 va maximum rating) — Reversing Valve — Terminal Block Factory Wiring Field Wiring — — — — — — *Jumper removed only when separate 24-v transformer power source is used to power the 33CSUCE-06 relay pack. †To control heating device and provide automatic indoor-fan operation on heating. NOTE: Field-supplied liquid line solenoid valves installed at the evaporator are required on all units. Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac. 24-V THERMOSTAT CONTROL WIRING — UNITS 38AH124 AND 134 CR HD IFC IFR LLS R RV TB LEGEND Control Relay Heating Device Indoor Fan Contactor Indoor-Fan Relay Liquid Line Solenoid Heating Relay (fieldsupplied 24-v sealed coil, 10 va maximum rating) — Reversing Valve — Terminal Block Factory Wiring Field Wiring — — — — — — *Jumper removed only when separate 24-v transformer power source is used to power the 33CSUCE-06 relay pack. †To control heating device and provide automatic indoor-fan operation on heating. NOTES: 1. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units. 2. Disconnect black wire from CR2 terminal 6; cap loose end and secure. Connect new field-supplied wire from CR2 terminal 6 to TB3 terminal 1 on module 124B or 134B. Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac. 93 Application data — 38AH044-134 Operating limits Maximum cooling load . . . . . . . . . . . . . . . . 51.7 C (125 F) Minimum return-air temperature . . . . . . . . . 12.8 C (55 F) Maximum return-air temperature . . . . . . . . 35.0 C (95 F) Range of acceptable saturation suction temperature . . . . . . −6.7 to 10.0 C (20 to 50 F) Maximum discharge temperature . . . . . . 135.0 C (275 F) Minimum discharge superheat . . . . . . . . . . . 15.6 C (60 F) NOTES: 1. Select indoor equipment at no less than 40 L/s/kW (300 cfm/ton) nominal condensing unit capacity. 2. Total combined draw of the 2 field-supplied liquid line solenoid valves and one air handler fan contactor must not exceed 90 volt-amperes (va). If the specified voltamperes must be exceeded, use a remote relay to control the load. 3. Select equipment to match or to be slightly less than peak load. 4. Evaluate oil return when selecting vapor line sizes, especially for partial load conditions. 5. Indoor fan must operate when outdoor unit is operating. 6. For VAV systems, the total building load is NOT the sum of the individual peak loads. Equipment selected for the sum of the individual peak loads will be oversized. 7. For VAV systems with supply- to return-air recycling, use the equipment room as a return-air plenum. 8. To minimize air recirculation, do not use concentric supply and return grilles. LIQUID LINE DATA UNIT 38AH 044 054 064 074 084 094 104 124 134 MAXIMUM ALLOWABLE LIQUID LIFT m 17.5 23.0 19.8 11.4 23.0 14.0 12.8 19.8 11.4 ft 57.5 75.0 65.0 37.5 75.0 46.0 42.0 65.0 37.5 044 054 064 074 084 094 104 124 134 CAPACITY/STAGE (%) Standard Dual-Circuit Units Optional Single-Circuit Units 100, 75, 50, 25 100, 75, 50, 25 100, 79, 42, 21 100, 80, 56, 37 100, 84, 48, 32 100, 82, 55, 36 100, 86, 43, 29 100, 81, 57, 38 100, 83, 50, 33 100, 83, 50, 33 100, 85, 55, 44, 33, 22 — 100, 91, 74, 65, 47, 38, 26, 17 — 100, 91, 77, 68, 50, 41, 27, 18 — 100, 90, 76, 66, 45, 37, 25, 16 — *Additional unloading available with field-installed accessory unloader. NOTES: 1. Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C (95 F) outdoor-air temperature. 2. Single-circuit option available for sizes 044-084 only. UNLOADING SEQUENCES — OPTIONAL VARIABLE AIR VOLUME (VAV) UNITS UNIT 38AH 044 054 064 074 084 094 104 124 134 CAPACITY/STAGE (%) Standard Dual-Circuit Units Optional Single-Circuit Units 100, 75, 50, 25 100, 75, 50, 25 100, 79, 58, 42, 21 100, 80, 61, 56, 37 100, 84, 69, 48, 32, 16 100, 82, 64, 55, 36, 18 100, 86, 71, 43, 29, 14 100, 81, 62, 57, 38, 19 100, 83, 67, 50, 33, 17 100, 83, 67, 50, 33, 17 100, 85, 70, 55, 44, 33, 22 — 100, 91, 74, 65, 47, 38, 26, 17 — 100, 91, 82, 77, 68, 50, 41, 32, 27, 18, 9 — 100, 90, 79, 76, 66, 45, 37, 28, 25, 16, 8 — NOTES: 1. Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C (95 F) outdoor-air temperature. 2. Single-circuit option available for sizes 044-084 only. 94 48.3 7 1.1 2 NOTE: Values shown are for units operating at 7.2 C (45 F) saturated suction at condensing unit and 35 C (95 F) entering outdoor air. UNLOADING SEQUENCES — STANDARD CONSTANT VOLUME (CV) UNITS* UNIT 38AH LIQUID LINE Max Allowable Max Allowable Pressure Drop Temp Loss kPa Psi C F MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND UNLOADING SEQUENCES — 38AH044-084 DUAL-CIRCUIT UNITS UNIT 38AH 044 054 064 074 084 QUANTITY OF LOADED COMPRESSOR CYLINDERS Ckt A 4 2 4 2 4 2 2 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 Ckt B 4 4 0 0 6 6 4 0 0 6 6 6 0 0 0 6 6 6 0 0 0 6 6 6 0 0 0 MINIMUM OUTDOOR OPERATING TEMP w/Std Fans w/MotormasterT III Control C F C F SYSTEM CAPACITY (%) Total 8 6 4 2 10 8 6* 4 2 12 10 8* 6 4 2* 12 10 8* 6 4 2* 12 10 8* 6 4 2* 100 75 50 25 100 79 58* 42 21 100 84 69* 48 32 16* 100 86 71* 43 29 14* 100 83 67* 50 33 17* *Requires units with VAV (variable air volume) factory-supplied option. NOTES: 1. Units have 2 independent refrigeration circuits. Circuit A is lead circuit. 10.0 50 −28.9 −20 8.9 48 −28.9 −20 3.9 39 −28.9 −20 −0.6 31 −28.9 −20 −6.7 20 −28.9 −20 2. Minimum operating temperature is the higher outdoor temperature of the 2 circuits. 3. Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing temperature and 100% capacity. MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND UNLOADING SEQUENCES — 38AH044-084 SINGLE-CIRCUIT UNITS UNIT 38AH 044 054 064 074 084 QUANTITY OF LOADED CYLINDERS SYSTEM CAPACITY (%) 8 6 4 2 10 8 6* 6 4 12 10 8* 6 4 2* 12 10 8* 6 4 2* 12 10 8* 6 4 2* 100 75 50 25 100 80 61* 56 37 100 82 64* 55 36 18* 100 81 62* 57 38 19* 100 83 67* 50 33 17* *Requires VAV (variable air volume) factory-supplied option or accessory unloader. MINIMUM OUTDOOR OPERATING TEMP w/Std Fans w/Motormaster III Control C F C F 8.3 47 −28.9 −20 5.0 41 −28.9 −20 3.3 38 −28.9 −20 −5.6 22 −28.9 −20 −6.7 20 −28.9 −20 NOTE: Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing temperature and 100% capacity. 95 Application data — 38AH044-134 (cont) MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND UNLOADING SEQUENCES — 38AH094-134 DUAL CIRCUIT UNITS UNIT 38AH 094 104 124 134 QUANTITY OF LOADED COMPRESSOR CYLINDERS Ckt A Ckt B Total SYSTEM CAPACITY (%) 10 10 10 10 8 6 4 10 10 10 10 10 10 10 8 6 4 2† 12 12 12 12 12 12 12 10 8 6 4 2* 12 12 12 12 12 12 12 10 8 6 4 2* 6 4 2* 0 0 0 0 12 10 8† 6 4 2† 0 0 0 0 0 12 10 8† 6 4 2† 0 0 0 0 0 0 12 10 8 6 4 2† 0 0 0 0 0 0 16 14 12 10 8 6 4 22 20 18 16 14 12 10 8 6 4 2 24 22 20 18 16 14 12 10 8 6 4 2 24 22 20 18 16 14 12 10 8 6 4 2 100 85 70* 55 44 33 22 100 91 82† 74 65 56† 47 38 26 17 9† 100 91 82* 77 68 59† 50 41 32* 27 18 9* 100 90 79* 76 66 56† 45 37 28* 25 16 8* *Requires VAV (variable air volume) unit or accessory unloader(s) field installed on circuit lead compressor. Lead compressor is identified in Physical Data section, pages 47-50. †Requires field-installed accessory unloader on circuit lead compressor. Lead compressor is identified in Physical Data section, pages 47-50. 96 MINIMUM OUTDOOR OPERATING TEMP W/Std Fans w/MotormasterT III Control Ckt A Ckt B C F C F C F −13.9 7 −3.9 25 −28.9 −20 −10.0 14 −15.0 5 −28.9 −20 3.3 38 3.3 38 −28.9 −20 3.3 38 −5.6 22 −28.9 −20 NOTES: 1. Temperatures calculated with the minimum number of fans operating per circuit. 2. For 38AH124 and 134 units, circuit A is Module 38AH124A or 134A. Circuit B is Module 38AH124B or 134B. 3. Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing temperature and 100% capacity. REFRIGERANT PIPING REQUIREMENTS 38AH044-084 DUAL-CIRCUIT UNITS UNIT 38AH 044 054 064 074 084 Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B 15-25 (4.6-7.6) L S 5 ⁄8 13⁄8 5 ⁄8 13⁄8 5 ⁄8 13⁄8 7 ⁄8 15⁄8 7 ⁄8 15⁄8 7 ⁄8 15⁄8 7 ⁄8 15⁄8 7 ⁄8 21⁄8 7 ⁄8 21⁄8 7 ⁄8 21⁄8 TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M) 25-50 50-75 75-100 100-150 (7.6-15.2) (15.2-22.9) (22.9-30.5) (30.5-45.7) L S L S L S L S 7 ⁄8 7⁄8 7⁄8 7 ⁄8 15⁄8 15⁄8 21⁄8 21⁄8 7 ⁄8 7⁄8 7⁄8 7 ⁄8 15⁄8 15⁄8 21⁄8 21⁄8 5 5 1 7 ⁄8 7 7 7 1 ⁄8 ⁄8 1 ⁄8 ⁄8 2 ⁄8 ⁄8 21⁄8 7 ⁄8 7⁄8 7⁄8 15⁄8 21⁄8 21⁄8 11⁄8 21⁄8 7⁄8 7 ⁄8 7⁄8 15⁄8 21⁄8† 21⁄8† 11⁄8 21⁄8† 7 ⁄8 7⁄8 7⁄8 21⁄8 21⁄8 21⁄8 11⁄8 25⁄8* 7 ⁄8 7⁄8 7⁄8 21⁄8 21⁄8 21⁄8 11⁄8 25⁄8† 7 ⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8 11⁄8 25⁄8 7 ⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8† 11⁄8 25⁄8† 7 ⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8 11⁄8 25⁄8 LEGEND L — Liquid Line S — Suction Line *Double suction riser required on units with field installed unloader on circuit B compressor if condensing unit is elevated above evaporator. †Double suction riser required on units with field installed unloader on circuit B compressor if condensing unit is elevated above evaporator. **Double suction riser required on all unit configurations if condensing unit is elevated above evaporator. NOTES: 1. Addition of 2 unloaders to circuit B compressor is not recommended. 2. 38AH094 and 38AH104 piping sizes apply only to factory supplied unit configurations. They do NOT take into account any field installed unloaders. 3. Piping sizes are based on unit operation above 40 F (4.4 C) saturated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System Design Manual, E20-IIT piping design program, or ASHRAE Handbook to select proper line sizes. 4. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings. 150-200 (45.7-61.0) L S 7 ⁄8 21⁄8 7 ⁄8 21⁄8 7 ⁄8 21⁄8 11⁄8 25⁄8*† 11⁄8 25⁄8** 11⁄8 25⁄8* 11⁄8 25⁄8† 11⁄8 25⁄8 11⁄8 25⁄8† 11⁄8 25⁄8 5. Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and efficiency. 6. Double suction risers may be required if condensing unit is elevated above the evaporator. See footnotes and double suction riser table below. 7. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems. 8. All pipe sizes are OD inches. Equivalent sizes in millimeters follow: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 REFRIGERANT PIPING REQUIREMENTS FOR DOUBLE SUCTION RISERS, 38AH054-104 DUAL-CIRCUIT UNITS UNIT 38AH 054 064 074 084 Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B Ckt A Ckt B A — — 13⁄8 — — — — — 50-75 (15.2-22.9) B — — 15⁄8 — — — — — TOTAL LINEAR LENGTH 75-100 (22.9-30.5) C A B — — — — — — 21⁄8 13⁄8 15⁄8 — — — — — — — — — — 15⁄8 21⁄8 — — — LEGEND — — Not Required Pipe A — Suction Riser Without Trap Pipe B — Suction Riser With Trap Pipe C — Suction Line to Condensing Unit NOTES: 1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers. 2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings. 3. Suction and liquid line sizing is based on pressure drop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency. OF INTERCONNECTING PIPE — FT (M) 100-150 (30.5-45.7) C A B C A — — — — — — — — — 15⁄8 21⁄8 15⁄8 15⁄8 21⁄8 15⁄8 — 15⁄8 21⁄8 25⁄8 15⁄8 — 15⁄8 21⁄8 25⁄8 15⁄8 — — — — — 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 — — — — — 150-200 (45.7-61.0) B — 21⁄8 21⁄8 21⁄8 21⁄8 — 21⁄8 — C — 25⁄8 25⁄8 25⁄8 25⁄8 — 25⁄8 — 4. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems. 5. All pipe sizes are OD inches. Equivalent sizes in millimeters follows: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 97 Application data — 38AH044-134 (cont) 38AH044-084 OPTIONAL SINGLE-CIRCUIT UNITS; 38AH124,134 MODULAR UNITS (DUAL-CIRCUIT) UNIT 38AH 15-20 (4.6-6.1) L S 7⁄8 21⁄8 7⁄8 21⁄8 044 054 064; Modules 124A, 124B, 134A 074; Module 134B 084 TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M) 20-50 50-75 75-100 100-150 (6.1-15.2) (15.2-22.9) (22.9-30.5) (30.5-45.7) L S L S L S L S 7⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8* 11⁄8 25⁄8* 11⁄8 21⁄8 11⁄8 25⁄8* 11⁄8 25⁄8* 11⁄8 25⁄8* 150-200 (45.7-61.0) L S 13⁄8 25⁄8* 13⁄8 31⁄8* 78 ⁄ 21⁄8 11⁄8 25⁄8† 11⁄8 25⁄8† 11⁄8 78 ⁄ 21⁄8 11⁄8 25⁄8† 11⁄8 25⁄8† 13⁄8 11⁄8 21⁄8 11⁄8 25⁄8† 13⁄8 31⁄8* 13⁄8 LEGEND CV — Constant Volume L — Liquid Line S — Suction Line VAV — Variable Air Volume *Double suction riser required on all units configurations if condensing unit is elevated above evaporator. †Double suction riser required on units with factory installed VAV option or CV units with additional field installed unloader on circuit A1 (lead) compressor if condensing unit is elevated above evaporator. NOTES: 1. Double risers are required if condensing unit is elevated above evaporator. See footnotes and double suction riser table below. 2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings. 3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure drop. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency. 25⁄8† 13⁄8 31⁄8* 13⁄8 31⁄8* 31⁄8* 13⁄8 31⁄8* 13⁄8 31⁄8* 31⁄8* 13⁄8 31⁄8* 15⁄8 35⁄8* 4. Suction line sizing is based on using the same diameter tube from the evaporator riser outlet to the condensing unit. 5. Suction line riser selections are based on using maximum possible unloaders. 6. Refer to Carrier System Design Manual or to E20-IIT design programs for further information on selecting pipe sizes for split systems. 7. All pipe sizes are OD inches; equivalent sizes in millimeters follow: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 35⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 92.1 38AH044-084 OPTIONAL SINGLE-CIRCUIT UNITS; 38AH124,134 MODULAR UNITS (DUAL-CIRCUIT) — DOUBLE SUCTION RISER UNIT 38AH 044 054 064; Modules 124A, 124B, 134A 074; Module 134B 084 — Pipe A Pipe B Pipe C — — — — 15-20 (4.6-6.1) A B C — — — — — — TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M) 20-50 50-75 75-100 100-150 (6.1-15.2) (15.2-22.9) (22.9-30.5) (30.5-45.7) A B C A B C A B C A B C — — — — — — 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 25⁄8 — — — 15⁄8 21⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 21⁄8 25⁄8 150-200 (45.7-61.0) A B C 15⁄8 25⁄8 25⁄8 15⁄8 25⁄8 31⁄8 — — — 15⁄8 21⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 31⁄8 15⁄8 25⁄8 31⁄8 — — — 15⁄8 21⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 31⁄8 15⁄8 25⁄8 31⁄8 15⁄8 31⁄8 35⁄8 — — — 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 31⁄8 15⁄8 25⁄8 31⁄8 15⁄8 25⁄8 31⁄8 15⁄8 31⁄8 35⁄8 LEGEND Not Required Suction Riser Without Trap Suction Riser With Trap Suction Line to Condensing Unit NOTES: 1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers. 2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings. 3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure drop. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency. 4. Suction line sizing is based on using the same diameter tube from the evaporator riser outlet to the condensing unit. 98 5. Suction line riser selections are based on using maximum possible unloaders. 6. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems. 7. All pipe sizes are OD inches; equivalent sizes in millimeters follow: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 35⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 92.1 REFRIGERANT PIPING REQUIREMENTS 38AH094,104 DUAL-CIRCUIT UNITS UNIT 38AH Ckt A Ckt B Ckt A Ckt B 094 104 15-25 (4.6-7.6) L S 7⁄8 21⁄8 7⁄8 21⁄8 7⁄8 21⁄8 7⁄8 21⁄8 TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE - FT (M) 25-50 50-75 75-100 100-150 (7.6-15.2) (15.2-22.9) (22.9-30.5) (30.5-45.7) L S L S L S L S 11⁄8 21⁄8 11⁄8 25⁄8** 11⁄8 25⁄8** 11⁄8 25⁄8** 7⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8*† 11⁄8 25⁄8*† 7⁄8 21⁄8 11⁄8 21⁄8 11⁄8 25⁄8** 11⁄8 25⁄8** 11⁄8 21⁄8 11⁄8 25⁄8 11⁄8 25⁄8 13⁄8 25⁄8 LEGEND L — Liquid Line S — Suction Line *Double suction riser required on units with field installed unloader on circuit B compressor if condensing unit is elevated above evaporator. †Double suction riser required on units with field installed unloader on circuit B compressor if condensing unit is elevated above evaporator. **Double suction riser required on all unit configurations if condensing unit is elevated above evaporator. NOTES: 1. Double risers are required if condensing unit is elevated above evaporator. See footnotes and double suction riser table below. 2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings. 3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure drop. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency. 150-200 (45.7-61.0) L S 13⁄8 31⁄8** 11⁄8 25⁄8*† 13⁄8 31⁄8** 13⁄8 31⁄8** 4. Suction line sizing is based on using the same diameter tube from the evaporator riser outlet to the condensing unit. 5. Suction line riser selections are based on using maximum possible unloaders. 6. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems. 7. All pipe sizes are OD inches; equivalent sizes in millimeters follow: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 35⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 92.1 38AH094,104 DUAL-CIRCUIT UNITS, DOUBLE SUCTION RISER UNIT 38AH Ckt A Ckt B Ckt A Ckt B 094 104 — Pipe A Pipe B Pipe C — — — — A 13⁄8 — — — 50-75 (15.2-22.9) B 21⁄8 — — — TOTAL LINEAR LENGTH 75-100 (22.9-30.5) C A B 25⁄8 13⁄8 21⁄8 — 13⁄8 21⁄8 21⁄8 — 13⁄8 — — — LEGEND Not Required Suction Riser Without Trap Suction Riser With Trap Suction Line to Condensing Unit NOTES: 1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers. 2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings. 3. Suction line sizing is based on 1.1 C (2 F) pressure drop at nominal rating conditions. Liquid line sizing is based on 1.1 C (2 F) pressure drop. Higher design pressure drop criteria may allow selection of smaller pipe sizes but at a penalty of decreased system capacity and efficiency. 4. Suction line sizing is based on using the same diameter tube from the evaporator riser outlet to the condensing unit. OF INTERCONNECTING PIPE — FT (M) 100-150 (30.5-45.7) C A B C A 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 25⁄8 15⁄8 21⁄8 25⁄8 15⁄8 — — — — 15⁄8 150-200 (45.7-61.0) B 25⁄8 21⁄8 25⁄8 25⁄8 C 31⁄8 25⁄8 31⁄8 31⁄8 5. Suction line riser selections are based on using maximum possible unloaders. 6. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems. 7. All pipe sizes are OD inches; equivalent sizes in millimeters follow: in. 5⁄8 7⁄8 11⁄8 13⁄8 15⁄8 21⁄8 25⁄8 31⁄8 35⁄8 mm 15.9 22.2 28.6 34.9 41.3 54.0 66.7 79.4 92.1 99 Application data — 38AH044-134 (cont) REFRIGERANT PIPING REQUIREMENTS DOUBLE SUCTION RISER CONSTRUCTION A B C D RED. STR — — — — — — LEGEND Pipe A, Suction Riser, Lower Trap Pipe B, Suction Riser with Trap Suction Line to Condensing Unit Pipe D, Suction Riser Short Lift Reducer Street NOTE: Short riser, pipe D, is used when routing suction line to condensing unit connection. See table below: UNIT 38AH 044 054 064 074 084 094 104 124A,B 134A,B PIPE D DIAMETER* Dual Circuit Single Circuit A B 5 5 1 ⁄8 21⁄8 1 ⁄8 15⁄8 15⁄8 21⁄8 15⁄8 21⁄8 21⁄8 21⁄8 21⁄8 21⁄8 21⁄8 21⁄8 25⁄8 21⁄8 21⁄8 — 21⁄8 21⁄8 — 1 1 2 ⁄8 — 2 ⁄8 1 1 2 ⁄8 2 ⁄8 — *Maximum length of riser is 3 ft (914 mm). 100 Guide specifications — 38AH024-034 Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 63 to 87 kW (18 to 25 Tons), Nominal Carrier Model Number: 38AH Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall have 2 independent refrigeration circuits and shall consist of dual semi-hermetic reciprocating compressors, air-cooled coils, propeller-type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract drawings. Unit shall be used in refrigeration circuit matched with a packaged fan-coil unit or direct-expansion cooler. 1.02 QUALITY ASSURANCE A. Unit shall be rated in accordance with ARI Standard 365, latest edition (U.S.A. standard). B. Unit construction shall comply with latest edition of ANSI/ASHRAE and with NEC (U.S.A. standard). C. Unit shall be manufactured in a facility registered to ISO (International Standards Organization) 9002 manufacturing quality standard. D. Unit shall be constructed in accordance with UL standards (U.S.A.). E. Unit cabinet shall be capable of withstanding 500-hour salt-spray exposure per ASTM B117 (U.S.A) (scribed specimen). F. Air-cooled condenser coils shall be leak tested at 1034 kPa (150 psig) and pressure tested at 3310 kPa (480 psig). 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be shipped as single package only, and shall be stored and handled per unit manufacturer’s recommendations. 1.04 WARRANTY For inclusion by specifying engineer. Part 2 — Products 2.01 EQUIPMENT A. General: Factory assembled, single-piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressors, holding charge, and special features required prior to field start-up. B. Unit Cabinet: 1. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a prepainted, baked enamel finish. 2. Unit access panels shall be hinged for control box service access. 3. Lifting holes shall be provided to facilitate rigging. C. Fans: 1. Condenser fans shall be direct-drive propeller type, discharging air vertically upward. 2. Condenser fan motors shall be 3-phase type with class B insulation and permanently lubricated bearings. Class F fan motors shall be available as a factory-installed option. 3. Shafts shall have inherent corrosion resistance. 4. Fan blades shall be statically and dynamically balanced. 5. Condenser fan openings shall be equipped with PVC-coated steel wire safety guards. D. Compressors: 1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type. 2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge, suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil dilution. 3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less than 95%. 4. Compressor speed shall not exceed 24.3 r/s (1460 rpm). 5. Lead compressor shall unload using suction cutoff unloading (electrical solenoid unloading shall be available as an accessory). E. Condenser Coils: 1. Condenser coils shall be air cooled, circuited for integral subcooler. 2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless copper tubes which are then cleaned, dehydrated, and sealed. Copper fins and precoated aluminum fins shall be available as options. F. Refrigeration Components: Refrigeration circuit components shall include hot gas muffler, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding charge, and compressor oil. 101 Guide specifications — 38AH024-034 (cont) G. Controls and Safeties: 1. Minimum control functions shall include: a. Power and control terminal blocks. b. Five-minute Time Guardt protection to prevent compressor short-cycling. c. Lockout on auto-reset safety until reset from thermostat. d. Capacity control on the lead compressor shall be by suction cutoff unloaders in response to compressor suction pressure. Electric solenoid unloading shall be available as an accessory. e. Head pressure control for mild ambient temperature operation by fan cycling. One condenser fan shall be cycled by ambient temperature to maintain proper head pressure. 2. Minimum safety devices shall include: Automatic reset (after resetting first at thermostat) a. High discharge-temperature cutout. b. Low suction-pressure cutout. c. Condenser fan motors to be protected against overloads or single-phase condition by internal overloads. d. Low oil-pressure cutout. Manual reset at the unit a. Electrical overload protection through the use of definite-purpose contactors and calibrated, ambient compensated, magnetic trip circuit breakers. Circuit breakers shall open all 3 phases in the event of an overload in any one of the phases or a single-phase condition. b. High discharge-pressure cutout. H. Operating Characteristics: 1. The capacity of the condensing unit shall meet or at a suction temperature of exceed . The power consumption at full load shall not exceed kW. 2. The combination of the condensing unit and the evaporator or fan coil unit shall have a total net cooling capacity of or greater at an , entering-air temairflow rate of perature at the evaporator at wet bulb and dry bulb, and air entering the condensing unit at . 3. The system shall have an EER of or greater at standard ARI conditions. 102 I. Electrical Requirements: 1. Nominal unit electrical characteristics shall be v, 3-ph, 50 Hz. The unit shall be capable of satisfactory operation within voltage limits of v to v. 2. Unit electrical power shall be single point connection. 3. Unit control circuit shall be 230 v for 380/415 v and 230 v units, or 200 v for 346 v units. J. Special Features: Certain standard features are not applicable when the features designated * are specified. For assistance in amending the specifications, your local Carrier Sales Office should be contacted. * 1. Unloader Conversion Kit: Unloader valve, piston, and hardware shall be supplied to convert any pressure-operated compressor unloader to electrical unloading. Accessory ModuPanel™ or field-supplied step controller shall be provided for electrical unloading. * 2. Gage Panel: A gage panel package shall be provided which includes a suction and discharge pressure gage for each refrigerant circuit. 3. Thermostat Controls: a. Debonair™ programmable multi-stage thermostat with 7-day clock, holiday scheduling, large Thermoglow™ display, remote sensor capability, and Title 24 compliance. b. TEMP System programmable communicating multi-stage thermostat with fan switch, timeclock, LCD display, °F/°C capability, and CCN (Carrier Comfort Network) compatibility. c. Commercial Electronic Thermostat with 7-day timeclock, auto-changeover, multi-stage capability, and large LCD temperature display. d. Non-programmable thermostat with fan switch subbase. 4. Electric Unloader Package: Electric unloader shall provide an additional step of electric unloading. 5. Pressure Unloader Package: Pressure unloader shall provide an additional step of pressure unloading. * * * 6. ModuPanel™ Control: Control shall provide 10-step microprocessorbased control for variable air volume applications. 7. Motormastert III Control: Control shall maintain correct condensing pressure at low ambient temperatures. 8. VAV (Variable Air Volume) Modification: Unit shall be supplied from the factory with necessary wiring modifications for connection to a field-supplied ModuPanel discharge air controller. The VAV modification shall include 2 electric unloaders on the lead compressor. 9. Optional Condenser Coil Materials: a. Pre-Coated Aluminum-Fin Coils: Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b. Copper-Fin Coils: Shall be constructed of copper fins mechanically bonded to copper tubes. All copper construction shall provide protection in moderate coastal applications. c. Post-Coated Aluminum-Fin Coils: Shall have a durable organic coating uniformly applied over all coil surfaces. Coating shall be deep brown color applied by a dip and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall withstand 1,000-hour salt spray test in accordance with ASTM B117. Coil construction shall be aluminum fins mechanically bonded to copper tubes. d. Post-Coated Copper-Fin Coils: Shall have a durable organic coating uniformly applied over all coil surfaces. Coating shall be deep brown color applied by a dip and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall withstand 1,000-hour salt spray test in accordance with ASTM B117. Coil construction shall be copper fins mechanically bonded to copper tubes. 10. Class F Motors: Shall provide additional motor insulation for highambient temperature environments. 103 Guide specifications — 40RM Commercial Packaged Air-Handling Unit HVAC Guide Specifications Size Range: 2831 to 5663 L/s (6000 to 12,000 Cfm), Nominal Airflow 52 to 105 kW (15 to 30 Tons), Nominal Cooling Carrier Model Number: 40RM Part 1 — General 1.01 SYSTEM DESCRIPTION A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multiposition design and shall be capable of horizontal or vertical (upflow) installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without ductwork). B. Unit shall be used in a refrigerant circuit with a matching air-cooled condensing unit. 1.02 QUALITY ASSURANCE A. Coils shall be designed and tested in accordance with ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition. B. Unit shall be constructed in accordance with ETL (U.S.A.) and ETL, Canada standards. C. Unit insulation and adhesive shall comply with NFPA 90A (U.S.A.) requirements for flame spread and smoke generation. Insulation shall contain a U.S.A. EPAregistered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.). D. Unit shall be manufactured in a facility registered to the ISO 9002/BS5750, Part 2 manufacturing quality standard. E. Direct-expansion coils shall be burst tested at 2999 kPag (435 psig) and leak tested at 1034 kPag (150 psig). 1.03 DELIVERY AND STORAGE Units shall be stored and handled per manufacturer’s recommendations. Part 2 — Products 2.01 EQUIPMENT Indoor mounted, draw-thru, packaged air-handling unit that can be used in a suspended horizontal configuration or vertical (upflow) configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s), motor and drive assembly, prewired fan motor contactor, factory-installed refrigerant metering devices, cooling coil, 51 mm (2-in.) disposable air filters, and condensate drain pans for vertical or horizontal configurations. 104 A. Base Unit: 1. Cabinet shall be constructed of mill-galvanized steel. 2. Cabinet panels shall be fully insulated with 12.7-mm (1⁄2-in.) fire-retardant material. Insulation shall contain a U.S.A. EPA-registered immobilized antimicrobial agent to effectively resist the growth of bacteria and fungi as proven by tests in accordance with ASTM standards G21 and 22 (U.S.A.). 3. Unit shall contain PVC condensate drain pans for both vertical and horizontal applications. Drain pans shall have connections on right and left sides of unit to facilitate field connection. Drain pans shall have the ability to be sloped toward the right or left side of the unit to prevent standing water from accumulating in pans. 4. Unit shall have factory-supplied 51-mm (2-in.) throwaway-type filters installed upstream from the cooling coil. Filter access shall be from either the right or left side of the unit. B. Coils: Coils shall consist of 3 rows of copper tubes with sinewave aluminum fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled to maximize heat transfer. Suction and liquid line connections or supply and discharge connections shall be made on the same side of the coil. Direct-expansion coils shall feature factory-installed thermostatic expansion valves (TXVs) for refrigerant control. The TXVs shall be capable of external adjustment. C. Operating Characteristics: L/s (cfm) Unit shall be capable of providing airflow at an external static pressure of kPag (in. wg). D. Motor: Fan motor of the size and electrical characteristics specified on the equipment schedule shall be factory supplied and installed. E. Factory-Installed Options: 1. Alternate Motor and Drive: An alternate motor and/or medium- or high-static drive shall be available to meet the airflow and external static pressure requirements specified on the equipment schedule. 2. Painted Cabinet: Where conditions require, units shall be painted with an American Sterling Gray finish. F. Field-Installed Accessories: 1. Hot Water Coil: Coil shall be 2-row, U-bend coil with copper tubes and aluminum plate fans bonded to the tubes by mechanical expansion. Coil shall be mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 1034 kPag (150 psig). 2. Steam Distributing Coil: Coil shall consist of 1 row of copper tubes with aluminum plate fins, and shall have inner steam distributing tubes. Coil shall be mounted in a galvanized steel housing that shall be fastened to the unit’s fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 1207 kPag at 204.4 C (175 psig at 400 F). 3. Electric Heaters: Heaters for nominal 230 or 400-volt, 3-phase power supply shall be factory-supplied for field installation as shown on the equipment drawings. Electric heat assembly shall be ETL (U.S.A.) and ETL, Canada agency approved, and shall have single-point power wiring. Heater assembly shall include contactors with 24-v coils, power wiring, 24-v control wiring terminal blocks, and a hinged access panel. Electric heaters shall not be used with discharge plenum. 4. Air Discharge Plenum: Plenum shall be provided to provide free-blow air distribution for vertical floor-mounted units. A grille with moveable vanes for horizontal or vertical airflow adjustment shall be included. Plenum shall be field-assembled and field-installed on the unit’s fan deck for blow-thru air distribution. Plenum shall not be used with electric heaters. 5. Return-Air Grille: Grille shall be factory supplied for field installation on the unit’s return air opening. 6. Unit Subbase: Subbase assembly shall be factory supplied for field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection. 7. Economizer: Economizer for ventilation or ‘‘free’’ cooling shall be factory provided for field installation. For free cooling applications, economizer shall be compatible with factory-supplied thermostat; economizer dampers shall open when outdoor air enthalpy is suitable for free cooling. Economizer shall be compatible with separate CO2 sensor accessory; economizer dampers shall open when indoor CO2 level rises above predetermined set point. Economizer shall include enthalpy control and damper actuator with controls. 8. Thermostat Controls: a. Debonair™ programmable multi-stage thermostat with 7-day clock, holiday scheduling, large Thermoglow™ display, remote sensor capability, and Title 24 compliance. b. TEMP System programmable communicating multi-stage thermostat with fan switch, timeclock, LCD display, °F/°C capability, and CCN (Carrier Comfort Network) compatibility. c. Commercial Electronic Thermostat with 7-day timeclock, auto-changeover, multi-stage capability, and large LCD temperature display. d. Non-programmable thermostat with fan switch subbase. 9. Overhead Suspension Brackets: Package shall include necessary brackets to support units in a horizontal ceiling installation. 10. CO2 Sensor: Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds the predetermined set point. Sensor shall have the capability of being connected to comfort system relay pack or to economizer using fieldsupplied and installed Honeywell dc adapter no. Q769C1004. 11. Condensate Drain Trap: Trap shall have transparent, serviceable design for easy cleaning. Kit shall include overflow shutoff switch and wiring harness for connection to an alarm if desired. 105 Guide specifications — 38AH044-134 Commercial Air-Cooled Condensing Units HVAC Guide Specifications Size Range: 123 to 390 kW (35 to 111 Tons), Nominal Carrier Model Number: 38AH Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit shall have 2 independent refrigeration circuits and shall consist of 2, 3, or 4 semi-hermetic reciprocating compressors, air-cooled coils, propeller-type condenser fans, and a control box. Unit shall discharge supply air upward as shown on contract drawings. Unit shall be used in refrigeration circuit matched with a packaged air-handling unit or direct-expansion coils. 1.02 QUALITY ASSURANCE A. Unit performance shall be rated in accordance with ARI Standard 365 (U.S.A.), latest edition. B. Unit construction shall comply with latest edition of ASHRAE and (U.S.A. Standards) NEC. C. Unit shall be manufactured in a facility registered to ISO 9002 manufacturing quality standard. D. Unit cabinet shall be capable of withstanding 500-hour salt-spray exposure per ASTM B117 (U.S.A.) (scribed specimen). E. Air-cooled condenser coils shall be leak tested at 1034 kPa (150 psig) and pressure tested at 3310 kPa (450 psig). 1.03 DELIVERY, STORAGE, AND HANDLING Unit shall be shipped as single package or 2-container package, and shall be stored and handled per unit manufacturer’s recommendations. 1.04 WARRANTY For inclusion by specifying engineer. Part 2 — Products 2.01 EQUIPMENT A. General: Factory assembled, single-piece or 2-piece, air-cooled condensing unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressors, holding charge (R-22), and special features required prior to field start-up. B. Unit Cabinet: 1. Unit cabinet shall be constructed of galvanized steel, bonderized, and coated with a prepainted, baked enamel finish. 2. Unit access panels shall be hinged for control box service access. 3. Lifting holes shall be provided to facilitate rigging. 106 C. Fans: 1. Condenser fans shall be direct-drive propeller type, discharging air vertically upward. 2. Condenser fan motors shall be 3-phase type with class B insulation and permanently lubricated bearings. Motors shall be drip proof with sealed bearings. Class F fan motors shall be available as a factory-installed option. 3. Shafts shall have inherent corrosion resistance. 4. Fan blades shall be statically and dynamically balanced. 5. Condenser-fan openings shall be equipped with PVC-coated steel wire safety guards. D. Compressors: 1. Compressors shall be manufactured by the condensing unit manufacturer, and shall be serviceable, reciprocating, semi-hermetic type. 2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge, suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil dilution. 3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less than 95%. 4. Compressor speed shall not exceed 24.3 r/s (1460 rpm). 5. Lead compressors on each circuit shall unload using suction cutoff unloading (electric solenoid unloading shall be available as an accessory). E. Condenser Coils: 1. Condenser coils shall be air cooled and circuited for integral subcooler. 2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless copper tubes which are then cleaned, dehydrated, and sealed. Copper fins and precoated aluminum fins shall be available as options. F. Refrigeration Components: Refrigeration circuit components shall include hot gas muffler, suction line accumulator, hot gas bypass stub tubes, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding charge of refrigerant R-22, and compressor oil. 38AH094-134 and all 38AH044-084 single-circuit units shall have suction line accumulators. The VAV units shall also have suction line accumulators. G. Controls and Safeties: 1. Minimum control functions shall include: a. Power and control terminal blocks. b. Five-minute time delay protection to prevent compressor short-cycling. c. Lockout on auto-reset safety until reset from thermostat. d. Capacity control on the lead compressor shall be by suction cutoff unloaders in response to compressor suction pressure. Electric solenoid unloading shall be available as an accessory. e. Head pressure control for mild ambient temperature operation through fan cycling. Condenser fans (except fans 1 and 2) shall be cycled by discharge pressure to maintain proper head pressure. f. Winter start control to prevent nuisance tripouts at low ambient temperatures. 2. Minimum safety devices shall include: Automatic reset (after resetting first at thermostat) a. Low suction pressure cutout. b. Condenser-fan motors protected against overloads or single-phase condition by internal overloads. c. Low oil pressure cutout. Manual reset at the unit a. Electrical overload protection through the use of definite-purpose contactors and calibrated, ambient compensated, magnetic trip circuit breakers. Circuit breakers shall open all 3 phases in the event of an overload in any one of the phases or a single-phase condition. b. High discharge-pressure cutout. H. Operating Characteristics: 1. The capacity of the condensing unit shall meet at a suction temperature of or exceed . The power consumption at full load shall not exceed kW. 2. The combination of the condensing unit and the evaporator or air handling unit shall have a total net cooling capacity of or greater at conentering-air temperature at the ditions of evaporator at wet bulb and dry bulb, and air entering the condensing unit at . 3. The system shall have an Energy Efficiency Ratio (EER) of or greater at standard ARI conditions. I. Electrical Requirements: 1. Nominal unit electrical characteristics shall be v, 3-ph, 50 Hz. The unit shall be capable of satisfactory operation within voltage limits of v to v. 2. Unit or module electrical power shall be singlepoint connection. 3. Unit control circuit shall be 230 v for 230 and 380/415 v units, and 200 v for 346 v units. J. Special Features: 1. Unloader Conversion Kit: Unloader valve, piston, and hardware shall be supplied to convert any pressure-operated compressor unloader to electrical unloading. Accessory ModuPanel™ control or field-supplied step controller shall be required for electrical unloading. 2. Gage Panel: A gage panel package shall be provided which includes a suction and discharge pressure gage for each refrigerant circuit. 3. Accessory Transformer Relay Package: Relay shall be provided for use with a remotecontrol 24-v thermostat. 4. Electric Unloader Package: Electric unloader shall provide an additional step of electric unloading. 5. Pressure Unloader Package: Pressure unloader shall provide an additional step of pressure unloading. 6. ModuPanel Control: Indoor mounted control shall provide 10-step microprocessor-based control for variable air volume (VAV) applications. 7. Low-Ambient Motormastert III Control: Control shall maintain correct condensing pressure at low ambient temperatures. 8. Optional Condenser Coil Materials: a. Pre-Coated Aluminum-Fin Coils: Shall have a durable epoxy-phenolic coating to provide protection in mildly corrosive coastal environments. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier between the aluminum fin and copper tube. Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals. b. Copper-Fin Coils: Shall be constructed of copper fins mechanically bonded to copper tubes. All copper construction shall provide protection in moderate coastal applications. 107 Guide specifications — 38AH044-134 (cont) c. Post-Coated Aluminum-Fin Coils: Shall have a durable organic coating uniformly applied over all coil surfaces. Coating shall be deep brown color applied by a dip and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall withstand 1,000-hour salt spray test in accordance with ASTM (U.S.A.) B117. Coil construction shall be aluminum fins mechanically bonded to copper tubes. d. Post-Coated Copper-Fin Coils: Shall have a durable organic coating uniformly applied over all coil surfaces. Coating shall be deep brown color applied by a dip and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall withstand 1,000-hour salt spray test in accordance with ASTM (U.S.A.) B117. Coil construction shall be copper fins mechanically bonded to copper tubes. 9. Thermostat Controls: a. Debonair™ programmable multi-stage thermostat with 7-day clock, holiday scheduling, large Thermoglow™ display, remote sensor capability, and Title 24 compliance. b. TEMP System programmable communicating multi-stage thermostat with fan switch, timeclock, LCD display, °F/°C capability, and CCN (Carrier Comfort Network) compatibility. c. Commercial Electronic Thermostat with 7-day timeclock, auto-changeover, multi-stage capability, and large LCD temperature display. d. Non-programmable thermostat with fan switch subbase. Carrier Corporation • Syracuse, New York 13221 10. Hail Guard: Unit shall be equipped with louvered condenser coil hail guard protection and installation hardware. 11. Security Grilles: A set of PVC-coated metal grilles complete with support retainers and fasteners shall be provided for the protection of the condensing coils, compressors, or both. 12. Sound Reduction Package Kit: This field-installed accessory kit shall consist of a specially designed fan system containing fans and orifices for reducing system noise without compromising unit performance. No fan motor change shall be required for accessory installation. 13. VAV Control Box: Modification shall include electric unloaders on compressors (1 for 38AH044; 2 for 38AH054084 and 104; 3 for 38AH094; and 4 for 38AH124,134) to make condensing unit compatible with ModuPanel™ VAV controller. Unit shall include factory-installed accumulator. 14. Single-Circuit Modification (sizes 044-084 only) Modification shall include all piping and wiring to make unit single circuit. Unit shall include factory-installed accumulator. 15. Single-Circuit Modification with VAV: Modification shall include piping, wiring, and electric unloaders on compressors (one on 38AH044 and 2 on 38AH054-084) to make unit single circuit, VAV ready. 16. Class F Motors: Shall provide additional motor insulation for highambient temperature environments. 11-98 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 2 Tab 3a 1a Page 108 Catalog No. 003-829 Printed in U.S.A. Printed in U.S.A. Form 38AH-C4PD Replaces: 38AH-C3PD
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : No Create Date : 1998:11:16 16:56:08 Producer : Acrobat Distiller 3.0 for Windows Modify Date : 1998:11:16 17:04:41 Page Count : 108EXIF Metadata provided by EXIF.tools