38a C5pd 38AKS028 044 38AKS

User Manual: 38AKS028-044

Open the PDF directly: View PDF PDF.
Page Count: 108

Download38a-c5pd 38AKS028-044 38AKS
Open PDF In BrowserView PDF
Product
Data

38AK007-012
38AKS008-044
with 40RM007-034
Commercial Air-Cooled
Split Systems
50 Hz
Nominal: 19.0 to 127.0 kW (5.3 to 35.8 Tons)

Features/Benefits
These dependable split systems match Carrier’s indoorair handlers with outdoor
condensing units for a wide
selection of commercial
cooling solutions.
Constructed for long life
38AK007,008,012
38AKS008,009,012

38AKS013-024

Model 38AK (hermetic compressor
units) and 38AKS (semi-hermetic compressor) units are designed and built to
last. The copper tube-aluminum fin
outdoor coil construction provides
years of trouble-free operation. Where
conditions require them, copper fin
coils are also available. Cabinets are
constructed of prepainted galvanized
steel, delivering unparalleled protection
from the environment. Inside and outside surfaces are protected to ensure
long life, good looks, and reliable operation. Safety controls are used for enhanced system protection and
reliability.

Efficient operation
Building owners will appreciate the
high unit EERs (Energy Efficiency Ratios) offered by the 38AK and 38AKS
units. These units provide greater efficiency than similar units in the marketplace, which translates into year-round
operating savings.

40RM007-012

Copyright 2001 Carrier Corporation

Form 38A-C5PD

Controls for performance
dependability
The 38AK and 38AKS condensing
units offer the building owner operating controls and components designed
for performance dependability. The
highly efficient hermetic and semihermetic compressors are engineered
for long life and durability. The compressors include overload protection
and vibration isolation for enhancement of quiet operation. The highpressure switch protects the entire refrigeration system from abnormally
high operating pressures. A lowpressure switch protects the system
from low-pressure conditions, including loss of charge.
The 38AK007-012 and
38AKS008-012 units include CycleLOC™ anti-short-cycling protection
which helps to protect the units against
compressor failure. The 38AKS013044 units include a compressor recycle
delay timer to prevent short-cycling.
The 24-v control circuit transformer
permits quick, easy wiring of standard
and programmable 24-v thermostats.
The 38AK012 and 38AKS008-044
units include a crankcase heater to
eliminate liquid slugging at start-up.
Units with semi-hermetic compressors
are also equipped with an oil-level sight
glass.
Latest safety standards for 38AK
and 38AKS units are assured through
UL (Underwriters’ Laboratories)
(U.S.A. standard) and CSA (Canadian
Standards Association) listings.

Innovative Carrier 40RM packaged air handlers are custom
matched to 38AK and 38AKS
condensing units
The 40RM Series has excellent fan
performance, efficient directexpansion (DX) coils, a unique combination of indoor-air quality features,
and easy installation. Its versatility and

2

state-of-the-art features help to ensure
that your split system provides economical performance now and in the
future.
Indoor-air quality (IAQ) features — The unique combination of
IAQ features in the 40RM Series air
handlers help to ensure that only
clean, fresh, conditioned air is delivered to the occupied space.
Direct-expansion (DX) cooling coils
prevent the build-up of humidity in
the room, even during part-load
conditions. Unit sizes 012 and above
feature dual-circuit coils for improved
temperature control.
Standard 51-mm (2-in.) disposable
filters remove dust and airborne particles from the occupied space.
Thermal insulation contains an immobilized anti-microbial agent to inhibit the growth of bacteria and fungi. The
anti-microbial agent is registered with
the U.S.A. Environmental Protection
Agency (EPA).
The pitched PVC drain pan can be
adjusted for a right- or left-hand
connection to suit many applications
and provide positive drainage, and
prevent standing condensate.
The 40RM accessory economizer
can provide ventilation air to improve
indoor air quality. When used in conjunction with CO2 sensors, the economizer admits fresh outdoor air to replace stale, recirculated indoor air.
Economy — The 40RM Series packaged air handlers have low initial costs,
and they continue to save money by
providing reduced installation expense
and energy-efficient performance.
Quick installation is ensured by the
multipoise design. Units can be installed in either the horizontal or vertical (upflow) configuration without modifications. Fan motors and contactors
are prewired and thermostatic

expansion valves (TXVs) are factoryinstalled on all 40RM models.
High efficiency, precision-balanced
fans minimize air turbulence, surging,
and unbalanced operation, cutting operation expenses.
The economizer accessory precisely
controls the blend of outdoor air and
room air to achieve comfort levels.
When the outside air enthalpy is suitable, outside air dampers can fully
open to provide “free” cooling without
energizing mechanical cooling.
Rugged dependability — 40RM
units are made to last. The die-formed
galvanized steel panels ensure structural integrity under all operating conditions. Galvanized steel fan housings are
securely mounted to a die-formed galvanized steel fan deck.
Rugged pillow-block bearings
(40RM014-034) are securely fastened
to the solid steel fan shaft with split
collets and clamp locking devices.
Smaller unit sizes have spider-type
bearings.
Coil flexibility — Model 40RM
direct-expansion coils have galvanized
steel casings; inlet and outlet connections are on the same end. The
coils are designed for use with
Refrigerant 22 and have copper tubes
mechanically bonded to aluminum
sine-wave fins. The coils include
matched, factory-installed TXVs with
matching distributor nozzles.
Easier installation and service —
The multipoise design and component
layout help you to get the unit installed
and running quickly. Units can be converted from horizontal to vertical operation by simply repositioning the unit.
Drain pan connections are duplicated
on both sides of the unit. The filters,
motor, drive, TXVs, and coil connections are all easily accessed by removing a single side panel.

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature — 38AK Units . . . . . . . . . . . . . . . . . . . . . . . . 3
Model Number Nomenclature — 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature — 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . 5
Capacity Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-18
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-26
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28-74
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75-79
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80-83
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Typical Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85-87
Application Data — 38AK007-012, 38AKS008-012 . . . . . . . . . . . . . . . . . 88
Application Data — 38AKS013-024 . . . . . . . . . . . . . . . . . . . . . . . . . . .89-91
Application Data — 38AKS028-044 . . . . . . . . . . . . . . . . . . . . . . . . . . .92,93
Application Data — 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94-98
Guide Specifications — 38AK007-012, 38AKS008-012 . . . . . . . . . . .99,100
Guide Specifications — 38AKS013-024 . . . . . . . . . . . . . . . . . . . . . .101,102
Guide Specifications — 38AKS028-044 . . . . . . . . . . . . . . . . . . . . . .103-105
Guide Specifications — 40RM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106-108

Model number nomenclature — 38AK units

*Gross capacity based on 36 C air temperature entering condenser and 8 C saturated suction temperature.
†Gross capacity based on 95 F air temperature entering condenser and 45 F saturated suction temperature.

3

Model number nomenclature — 38AKS units
38AKS
38AKS – Commercial Air-Cooled
Condensing Units (Semi-Hermetic)
Nominal Capacity – kW* (Tons†)
008 – 24.3 (6.8)
016 – 45.7 (12.8)
009 – 29.9 (8.4)
024 – 64.3 (18.0)
012 – 29.5 (8.3)
028 – 82.8 (23.4)
013 – 30.4 (8.5)
034 – 94.5 (26.7)
014 – 36.6 (10.3) 044 – 127.0 (35.8)

008

––

–

9

0

3

––
Not Used

Packaging
0 – Base Unit
3 – Export

Revision Number
0 – Original

Not Used
Condenser Coil Fin Material
– – Aluminum (Standard)
C – Copper (Optional)
K – Pre-Coated Aluminum (Optional, 013-044 Only)
V – Pre-Coated Aluminum (Optional, 008-012 Only)
SO – Post-Coated Aluminum (Contact Factory)
SO – Post-Coated Copper (Contact Factory)

Voltage Designation
3 – 346-3-50**
8 – 230-3-50
9 – 400-3-50

LEGEND
SO — Special Order
*Gross capacity based on 36 C air temperature entering condenser and 8 C saturated suction temperature.
†Gross capacity based on 95 F air temperature entering condenser and 45 F saturated suction temperature.
**024-044 only.

38AK, 38AKS008-012 UNITS

4

38AKS013-044 UNITS

Model number nomenclature — 40RM units

*The YC and WD option codes for all 034 size units designate standard motor and high-static drive.

40RM UNITS

5

Capacity summary
CONDENSING
UNIT
38AK007

38AK008

38AKS008

38AKS009

38AK012

38AKS012

38AKS013

38AKS014

38AKS016

38AKS024

38AKS028

38AKS034
38AKS044

AIRHANDLING
UNIT
40RM007
40RM008
40RM007
40RM008
40RM012
40RM007
40RM008
40RM012
40RM008
40RM012
40RM008
40RM012
40RM014
40RM008
40RM012
40RM014
40RM008
40RM012
40RM014
40RM012
40RM014
40RM016
40RM014
40RM016
40RM024
40RM016
40RM024
40RM028
40RM024
40RM028
40RM034
40RM028
40RM034
40RM034

AIR-HANDLING
UNIT AIRFLOW
L/s
Cfm
1150
2,400
1400
3,000
1150
2,400
1400
3,000
1900
4,000
1150
2,400
1400
3,000
1900
4,000
1400
3,000
1900
4,000
1400
3,000
1900
4,000
2350
5,000
1400
3,000
1900
4,000
2350
5,000
1400
3,000
1900
4,000
2350
5,000
1900
4,000
2350
5,000
2800
6,000
2350
5,000
2800
6,000
3800
8,000
2800
6,000
3800
8,000
4700
10,000
3800
8,000
4700
10,000
5650
12,000
4700
10,000
5650
12,000
5650
12,000

SYSTEM GROSS CAPACITY
(Standard 3-Row Coil)
kW*
Btuh†
17.8
60,800
19.9
68,000
21.0
71,700
22.7
77,500
25.2
86,000
22.6
77,000
24.2
82,000
26.3
89,000
28.0
95,000
30.6
104,000
28.7
98,000
30.5
104,000
31.6
108,000
27.7
94,000
30.3
103,000
31.5
107,000
28.3
96,000
31.0
105,000
32.2
109,000
35.2
120,000
36.8
125,000
39.1
133,000
43.1
146,000
46.2
157,000
49.6
167,000
58.0
197,000
63.3
215,000
67.0
226,000
75.6
256,000
80.4
273,000
84.6
288,000
88.2
298,000
93.1
316,000
113.8
385,000

SYSTEM GROSS CAPACITY
(High-Capacity 4-Row Coil)
kW*
Btuh†
19.7
67,100
20.8
71,000
23.7
80,900
25.2
86,100
27.0
92,000
23.2
79,000
24.7
84,300
26.5
90,500
28.8
98,100
31.1
106,200
30.4
103,600
33.1
112,900
34.8
118,700
28.8
98,100
31.1
106,200
32.9
112,400
30.0
102,400
32.4
110,600
34.3
117,000
37.0
126,100
39.0
133,000
41.9
143,000
48.4
165,000
51.2
174,600
54.7
186,500
59.5
203,100
65.7
224,100
69.3
236,300
83.8
285,800
84.3
287,700
88.7
302,800
89.9
306,800
94.8
323,500
111.8
381,600

LEGEND
db — Dry Bulb
wb — Wet Bulb
SST — Saturated Suction Temperature
*System gross capacities are rated according to indoor unit airflow, 35 C air temperature entering
condenser, and 20 C wb air temperature entering evaporator.
†System gross capacities are rated according to indoor unit airflow, 95 F air temperature entering
condenser, and 67 F wb air temperature entering evaporator.
**Condensing unit gross capacity based on 36 C air temperature entering condenser and 8 C SST.
††Condensing unit gross capacity based on 95 F air temperature entering condenser and
45 F SST.

6

CONDENSING UNIT
ONLY GROSS CAPACITY
kW**
Btuh††
19.0

64,000

24.2

81,500

24.3

81,700

29.9

101,000

31.9

108,000

29.5

99,200

30.4

102,000

36.6

123,000

45.7

154,000

64.3

216,000

82.8

281,000

94.5

320,000

127.0

429,000

Options and accessories
38AK, 38AKS options
Condenser coil options are available to match coil
construction to site conditions for the best corrosion
durability. Pre-coated coils provide protection in mild
coastal environments. All copper coils are best suited for
moderate coastal applications, while post-coated coils provide superior protection in severe coastal and industrial
applications.

38AK, 38AKS accessories
Electric unloader package (38AKS012-044) includes hardware and solenoid valve to convert a pressureoperated unloader to electric unloading.
–20 F low-ambient temperature kit (Motormaster® I
— 38AK007, 38AKS013-044; Motormaster III —
38AK008,012, 38AKS008-012) controls outdoor-fan
motor operation to maintain the correct head pressure at
low outdoor ambient temperatures. Only one low ambient
temperature kit is required per unit.
Gage panel package provides a suction and a discharge
pressure gage for the refrigerant circuit.
Carrier’s line of thermostats provide both programmable and non-programmable capability with the new
Debonair® line of commercial programmable thermostats. The TEMP System controls offer communication
capability with staged heating and cooling, the Commercial Electronic thermostats provide 7-day programmable

capability for economical applications, while the
non-programmable thermostats offer a multitude of
staged heating and cooling subbase options.
Winter start package (38AK007-012, 38AKS008024) bypasses the low-pressure switch to permit unit
start-up at low ambient temperatures.
Hail guard package (38AK007-012, 38AKS008012) protects coils against damage from flying debris and
hail.
ModuPanel™ control box allows 38AKS028-044 systems to operate as VAV (variable air volume) systems. Includes microprocessor, satellite sequencer, 4 status lights,
5-hour bypass timer, and locked enclosure.
Hot-gas bypass kit (38AKS028-044) prevents the indoor coil from freezing up during low airflow or low
return-air temperature applications by maintaining minimum suction pressure.
Condenser coil grille package (38AK007-012,
38AKS008-024) protects condensing unit coil from impact by large objects and vandalism.
Part-winding-start timing relay (38AKS028-044)
reduces inrush current and locked rotor amps on start-up.
The 220-v and 346-v units have part-winding start as a
standard feature. All 400-v units require a special order to
change circuit breakers, contactors, and compressor before timing relay can be added for part-winding start.

CONDENSER COIL PROTECTION APPLICATIONS
DESCRIPTION
(Enviro-Shield™ Option)
Standard, Al/Cu
Pre-Coated Al/Cu
Cu/Cu
Post-Coated Al/Cu
Post-Coated Cu/Cu
Al/Cu
Cu/Cu
Enviro-Shield
Post-Coated
Pre-Coated

—
—
—
—
—

Standard
Non-Corrosive
X

Mild
Coastal

ENVIRONMENT*
Moderate
Severe
Coastal
Coastal

Industrial

Combined Coastal
and Industrial

X
X
X
X

X

LEGEND
Aluminum Fin with Copper Tube Coil
Copper Fin with Copper Tube Coil
Family of Coil Protection Options
Organic Coating Applied to Entire Coil Assembly
Epoxy Coating Applied to Fin Stock Material

*See “Selection Guide: Environmental Corrosion Protection” Catalog No. 811-217 for more information.

7

Options and accessories (cont)
40RM factory-installed options
Alternate fan motors and drives are available to provide the widest possible range of performance.
High-capacity 4-row coils are available to provide increased latent and sensible capacities (40RM only).
Prepainted steel units are available from the factory for
applications that require painted units. Units are painted
with American Sterling Gray color.

40RM field-installed accessories
Two-row hot water coils have copper tubes mechanically bonded to aluminum plate fins and non-ferrous
headers.
One-row steam coil has copper tubes and aluminum
fins. The Inner Distributing Tube (IDT) design provides
uniform temperatures across the coil face. The steam coil
has a broad operating pressure range; up to 175 psig
(1207 kPag) at 400 F (204.4 C) and up to 300 psig
(2069 kPag) at 300 F (148.9 C). The IDT steam coils are
especially suited to applications where sub-freezing air enters the unit.
Electric resistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
single-point power connection is included.
Economizer (enthalpy controlled) provides ventilation
air and “free” cooling if outside ambient temperature and
humidity are suitable. Can also be used with CO2 sensors
to help meet indoor air quality requirements.
Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available unpainted or painted. Field assembly required.
Return-air grille provides a protective barrier over the
return-air opening and gives a finished appearance to units
installed in the occupied space. Accessory is available unpainted or painted.

8

Subbase provides a stable, raised platform and room for
condensate drain trap connection for vertical floor-mounted
units. Accessory is available unpainted or painted.
Overhead suspension package includes necessary
brackets to support units in horizontal ceiling installations.
CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when
the CO2 level in the space exceeds the set point. A Carrier
Comfort System programmable thermostat can be used to
override the sensor if the outside air temperature is too
high or too low.
Carrier’s line of thermostats provide both programmable and non-programmable capability with the new
Debonair® line of commercial programmable thermostats, the TEMP System controls offer communication capability with staged heating and cooling, the Commercial
Electronic thermostats provide 7-day programmable
capability for economical applications, while the NonProgrammable thermostats offer a multitude of staged
heating and cooling subbase options.
Condensate drain trap includes an overflow shutoff
switch that can be wired to turn off the unit if the trap becomes plugged. Kit also includes a wire harness that can be
connected to an alarm if desired. The transparent trap is
designed for easy service and maintenance.
UV-C germicidal lamps kill mold and fungus, which may
grow on evaporator coil and condensate pan surfaces. The
use of UV-C germicidal lamps eliminates the foul odors
that result from this growth of mold and fungus. It also provides a self-cleaning function for the evaporator coil and
drain pan.

CARRIER THERMOSTATS
DEBONAIR® COMMERCIAL PROGRAMMABLE
THERMOSTAT

TEMP SYSTEM THERMOSTAT
WITH TIMECLOCK

Carrier
®

Pm
COOL

AUTO
HEAT

COMMERCIAL ELECTRONIC THERMOSTAT

NON-PROGRAMMABLE THERMOSTAT
H

C

9

Options and accessories (cont)
40RM WITH DISCHARGE PLENUM, RETURN
GRILLE, AND SUBBASE

40RM WITH HOT WATER OR STEAM COIL
HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT

40RM WITH ECONOMIZER
AND UV-C GERMICIDAL LAMPS

ECONOMIZER

UV-C GERMICIDAL LAMPS

10

FAN COIL
UNIT

40RM WITH CONDENSATE TRAP

Physical data — SI
38AK007-012, 38AKS008-012
UNIT 38
NOMINAL CAPACITY (kW)*
OPERATING WEIGHT (kg)
Aluminum-Fin Coils (Standard)
Copper-Fin Coils (Optional)
RIGGING WEIGHT (kg)
Aluminum-Fin Coils (Standard)
Copper-Fin Coils (Optional)
REFRIGERANT†
Operating Charge, Typical (kg)**
Shipping Charge (kg)
COMPRESSOR
Model
No. Cylinders (ea)
Speed (r/s)
Oil Charge (L) (ea)
CONDENSER FAN
Qty...r/s
Diameter (mm)
Motor kW (NEMA)
Nominal Airflow (L/s)
CONDENSER COIL
Rows...Fins/m
Face Area (m2)
Storage Capacity (kg)
CONTROLS
Pressurestat Settings (kPa)
High Cutout
Cut-in
Low
Cutout
Cut-in
PIPING CONNECTIONS (Sweat)
Suction (in.)
Liquid (in.)

AK007
19.0

AK008
24.3

AK012
32.9

AKS008
24.3

AKS009
29.9

AKS012
29.5

154
175

178
208

193
228

231
262

256
287

256
287

176
198
R-22
5.17
0.91
Reciprocating,
Hermetic

200
228

215
250

254
285

279
309

279
309

6.17
0.91

7.48
0.91

6.49
0.91

7.44
0.91

7.44
0.91

Scroll Hermetic

H26A72Q

ZR94KC

2
48.4
1.92

—
48.4
2.51

1490
1.14
5.1

Reciprocating, Semi-Hermetic

ZR125KC

06DA818

06DA824

—
4
6
48.4
24.2
24.2
3.25
2.60
3.78
Propeller; Direct Drive
1...16.0
660
0.25
2550
2750
2550
2550
Enhanced Copper Tubes, Aluminum Lanced Fins
2...670
1.67
1.90
1.67
1.67
7.5
8.6
7.5
7.5

06DH824
(See Note)
6
24.2
3.78

2550
1.67
7.5

2937 ± 48
2206 ± 138
48 ± 20
151 ± 34
11 / 8
1/2

11 / 8
1/2

11 / 8
5/8

11 / 8
1/2

11 / 8
5/8

11 / 8
5/8

LEGEND
NEMA — National Electrical Manufacturers Association (U.S.A. Standard)
*Based on operation at 8 C saturated suction temperature and 36 C outdoor ambient
temperature.
†Unit is factory supplied with holding charge only.
**Typical operating charge with 7.6 m of interconnecting piping.
NOTE: Unit 38AKS012 has one step of unloading. Full load is 100% of capacity, and one
step of unloading is 67% capacity. Unit 38AKS012 has the following unloader settings:
Load is 483 kPa ± 6.9 kPa and unload is 414 kPa ± 13.8 kPa.

11

Physical data — SI (cont)
38AKS013-024
UNIT 38AKS
NOMINAL CAPACITY (kW)*
OPERATING WEIGHT (kg)
With Aluminum-Fin Coil
With Copper-Fin Coil
REFRIGERANT†
Operating Charge, Typical (kg)**
Shipping Charge (kg)
COMPRESSOR
Model
No. Cylinders
Speed (r/s)
Oil Charge (L)
Capacity Steps (%)
Accessory
Standard
Unloader Settings (kPa)
Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...r/s
Diameter (mm)
Nominal kW
Nominal Airflow (L/s Total)
Watts (total)
CONDENSER COIL
Rows...Fins/m
Face Area (sq m)
Storage Capacity (kg)||
CONTROLS
Pressurestat (kPa)
High Pressure
Cutout
Cut-in
Low-Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (kPa)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (C)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

013
30.4

014
36.6

016
45.7

024
64.3

332
374
R-22
10.0
0.95

353
417

358
421

408
472

06DD824
6
24.2
4.73
33††, 66, 100
66, 100

2...590
2.71
12.3

10.4
10.4
1.40
1.40
Reciprocating, Semi-Hermetic
06DD328
06DD537
6
6

06E4250
4

4.73

4.73

7.33

33††, 66, 100
66, 100

33††, 66, 100
66, 100

—
50, 100

483 ± 6.9
414 ± 13.8
125
Axial Flow, Direct Drive
2...15.0
660
0.37
4660
1050
Copper Tubes, Aluminum Fins
3...590
3...590
2.71
2.71
18.3
18.1

3...590
2.71
18.1

2724 ± 69
2034 ± 138
186 ± 28
462 ± 48

Compressor
93.3
11 / 8

1758 ± 69
1103 ± 69
Fusible Plug
Compressor
Compressor
93.3
93.3
13 / 8

*Based on operation at 8 C saturated suction temperature and 36 C outdoor ambient
temperature.
†Unit is factory-supplied with holding charge only.
**With 7.6 m of interconnecting piping. Operating charge is approximate for maximum
system capacity.
††Indicates capacity step (%) with electric unloader accessory.
||Storage capacity is measured at liquid saturated temperatures of 51.7 C for
38AKS013, 50.6 C for 38AKS014, and 54.4 C for 38AKS016 and 024.

12

12.7
1.40

13 / 8
5/
8
3/
8

Liquid Line
98.9
15 / 8

38AKS028-044
UNIT 38AKS
NOMINAL CAPACITY (kW)*
OPERATING WEIGHTS (kg)
With Aluminum-Fin Coils
With Copper-Fin Coils
REFRIGERANT
Operating Charge, Typical (kg)
COMPRESSOR
Model
No. Cylinders (ea)
Speed (r/s)
Oil (L)
Capacity Steps
Unloader Settings (kPag)
No. 1 Load
Unload
No. 2 Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...r/s
Diameter (mm)
Nominal kW
Nominal Airflow (L/s)
Watts (Total)
CONDENSER COIL
Rows...Fins/m
Face Area (sq m)
Storage Capacity (kg) — 80% Full at 51.7 C
CONTROLS
High-Pressure Switch (kPag)
Cutout
Cut-in
Low-Pressure Switch (kPag)
Cutout
Cut-in
Oil Pressure Switch (kPag)
Close on Rise
Open on Fall
FAN CYCLING CONTROLS
Operating Pressure (kPag)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (C)
PIPING CONNECTIONS (in. OD)
Suction
Liquid
Hot Gas Stub

028
82.8

034
94.5

044
127.0

748
818

818
1106
911
1246
R-22
13.8
19.7
29.5
Reciprocating, Semi-hermetic
06E9265
06E9275
06E9299
6
6
6
24.2
8.99
8.99
9.46
100%, 66%, 33%
524
400
538
414
180
Propeller Type — Direct Drive
2...15.8
3...15.8
762
0.75
7400
11,180
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...748
3...670
3...670
3.64
3.64
5.43
17.1
25.7
38.3
2937 ± 48
2206 ± 138
186 ± 21
303 ± 34
62
43
1758 ± 69
1103 ± 69
Fusible Plug
Liquid and Suction Line
98.9
15 / 8

21 / 8
7/
8
5/
8

21 / 8

*Based on operation at 8 C saturated suction temperature and 36 C outdoor ambient temperature.

13

Physical data — SI (cont)
40RM
UNIT 40RM
NOMINAL CAPACITY (kW)
OPERATING WEIGHT (kg)
Base Unit with TXV (3-Row/4-Row)
Plenum
FANS
Qty...Diam. (mm)
Nominal Airflow (L/s)
Airflow Range (L/s)
Nominal Motor kW (Standard Motor)
230-3-50, 400-3-50
Motor Speed (r/s)
230-3-50, 400-3-50
REFRIGERANT
Operating charge (kg)
(approx per circuit)*
DIRECT-EXPANSION COIL
Max Working Pressure (kPag)
Face Area (sq m)
No. of Splits
No. of Circuits per Split (3-Row/4-Row)
Split Type...Percentage
Fins/m
STEAM COIL
Max Working Pressure
(kPag at 204.4 C)
Total Face Area (sq m)
Rows...Fins/m
HOT WATER COIL
Max Working Pressure (kPag)
Total Face Area (sq m)
Rows...Fins/m
Water Volume
(L)
(m3)
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF)
DX Coil — Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (Male PVC)
FILTERS
Quantity...Size (mm)
Access Location
LEGEND
DX — Direct Expansion
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

14

007
21

008
26

012
35

014
43

016
52

024
70

028
87

034
105

173/181
80

175/183
80

184/193
80

304/315
102

311/323
102

313/331
102

463/470
148

467/482
148

1...381
1...381
1...381
2...381
2...381
2...381
2...457
2...457
1133
1604
1888
2360
2831
3775
4719
5663
850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079
1.79

1.79

2.16

2.16

23.8

23.8

23.8

23.8

2.16

3.73

5.60

7.46

23.8

23.8

23.8

23.8

1.13/1.13

1.59/1.59

2.04/2.04

2.27/2.27

2.30
2
15/20

2.77
2
18/24

591

591

1.24
1...394

1.39
1...394

1.39
1...394

1.24
2...335

1.39
2...493

1.39
2...493

R-22
1.36

1.36

0.68/0.68

0.90/0.90

Enhanced Copper Tubes, Aluminum Sine-Wave Fins
2999
0.93
0.93
1.64
1.85
2
2
2
2
9/9
9/16
12/16
13/18
Face...50/50
670
591
591
670

0.62
1
12/12
—
591

0.77
1
15/15
—
591

0.62
1...355

0.62
1...355

0.62
1...355

1.24
1...394

0.62
2...335

0.62
2...335

0.62
2...335

1.24
2...335

1207
1.24
1...394
1034

31.4
0.031
1...11/8

1...11/8
1... 5/8
1...21/2
1...11/2
1...11/2
1...11/2

1.24
2...335
52.6
0.052

2...11/8

1...11/2
1...11/2

4...406 x 610 x 51

2...11/8

2...11/8

54.1
0.054
2...11/8
2...5/8
1...21/2
1...21/2
1...2
1...2

1...11/4
Throwaway — Factory Supplied
4...406 x 508 x 51
4...406 x 610 x 51
Right or Left Side

2...13/8

2...13/8

4...508 x 610 x 51
4...508 x 635 x 51

Physical data — English
38AK007-012, 38AKS008-012
UNIT 38
NOMINAL CAPACITY (tons)*
OPERATING WEIGHT (lb)
Aluminum Coils (Standard)
Copper Coils (Optional)
RIGGING WEIGHT (lb)
Aluminum Fin Coils (Standard)
Copper Fin Coils (Optional)
REFRIGERANT†
Operating Charge, Typical (lb)**
Shipping Charge (lb)
COMPRESSOR
Model
No. Cylinders (ea)
Speed (rpm)
Oil Charge (oz) (ea)
CONDENSER FAN
Qty...Rpm
Diameter (in.)
Motor Hp (NEMA)
Nominal Airflow (Cfm)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)
CONTROLS
Pressurestat Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
PIPING CONNECTIONS (Sweat)
Suction (in.)
Liquid (in.)

AK007
5.3

AK008
6.8

AK012
9.3

AKS008
6.8

AKS009
8.4

AKS012
8.3

340
386

392
460

426
503

510
578

564
632

564
632

390
436

442
510

476
553

560
628

614
682

614
682

11.4
2.0
Reciprocating,
Hermetic

13.6
2.0

16.5
2.0

14.3
2.0

16.4
2.0

16.4
2.0

H26A72Q

ZR94KC

2
3500
65

—
3500
85

R-22

3800
12.24
11.26

Scroll Hermetic

Reciprocating, Semi-Hermetic

ZR125KC

06DA818

06DA824

—
4
6
3500
1460
1460
110
88
128
Propeller; Direct Drive
1...960
26
1/
3
6500
7000
6500
6500
Enhanced Copper Tubes, Aluminum Lanced Fins
2...17
18.0
20.50
18.0
18.0
16.56
18.87
16.56
16.56

06DH824
(See Note)
6
1460
128

6500
18.0
16.56

426 ± 7
320 ± 20
7± 3
22 ± 5
11 / 8
1/2

11 / 8
1/2

11 / 8
5/8

11 / 8
1/2

11 / 8
5/8

11 / 8
5/8

LEGEND
NEMA — National Electrical Manufacturers Association
*Based on operation at 45 F saturated suction temperature and 95 F outdoor ambient.
†Unit is factory supplied with holding charge only.
**Typical operating charge with 25 ft of interconnecting piping.
NOTE: Unit 38AKS012 has one step of unloading. Full load is 100% of capacity, and one
step of unloading is 67% capacity. Unit 38AKS012 has the following unloader settings: Load
is 70 ± 1 psig and unload is 60 ± 2 psig.

15

Physical data — English (cont)
38AKS013-024
UNIT 38AKS
NOMINAL CAPACITY (tons)*
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coil
With Copper-Fin Coil
REFRIGERANT†
Operating Charge, Typical (lb)**
Shipping Charge (lb)
COMPRESSOR
Model
No. Cylinders
Speed (rpm)
Oil Charge (pt)
Capacity Steps
Accessory
Standard
Unloader Setting (psig)
Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm, total)
Watts (total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb)||
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close (psig)
Open (psig)
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. ODM)
Suction
Liquid
Hot Gas Stub

013
8.5

014
10.3

016
12.8

024
18.0

732
825

779
919

789
929

900
1040

22
2.1
06DD824
6
10
33††, 66, 100
66, 100

2...15
29.2
27.2

R-22
23
23
3.1
3.1
Reciprocating, Semi-Hermetic
06DD328
06DD537
6
6
1450
10
10
33††, 66, 100
66, 100

70 ± 1
60 ± 2
125
Axial Flow, Direct Drive
2...900
26
1/
2
9210
1050
Copper Tubes, Aluminum Fins
3...15
3...15
29.2
29.2
40.0
39.8

06E4250
4
15.5
—
50, 100

3...15
29.2
39.8

395 ± 10
295 ± 20
27 ± 4
67 ± 7
255 ± 10
160 ± 10
Fusible Plug
Compressor
200

Compressor
200

11 / 8

13 / 8

*Based on operation at 45 F saturated suction temperature and 95 F outdoor ambient.
†Unit is factory-supplied with holding charge only.
**With 25 ft of interconnecting piping. Operating charge is approximate for maximum
system capacity.
††Indicates capacity step (%) with electric unloader accessory.
||Storage capacity is measured at liquid saturated temperatures of 125 F for 38AKS013,
123 F for 38AKS014, and 130 F for 38AKS016 and 024.

16

33††, 66, 100
66, 100

28
3.1

5/8
3/8

Compressor
200

Liquid Line
210

13 / 8

15 / 8

38AKS028-044
UNIT 38AKS
NOMINAL CAPACITY (tons)*
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coils
With Copper-Fin Coils
REFRIGERANT
Operating Charge, Typical (lb)
COMPRESSOR
Model
No. Cylinders (ea)
Speed (rpm)
Oil (pt)
Capacity Steps
Unloader Setting (psig)
No. 1 Load
Unload
No. 2 Load
Unload
Crankcase Heater Watts
CONDENSER FANS
Qty...Rpm
Diameter (in.)
Nominal Hp
Nominal Airflow (cfm)
Watts (Total)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq ft)
Storage Capacity (lb) — 80% Full at 125 F
CONTROLS
High-Pressure Switch (psig)
Cutout
Cut-in
Low-Pressure Switch (psig)
Cutout
Cut-in
Oil Pressure Switch (psig)
Close on Rise
Open on Fall
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close
Open
PRESSURE RELIEF
Location
Temperature (F)
PIPING CONNECTIONS (in. OD)
Suction
Liquid
Hot Gas Stub

028
23.4

034
26.7

044
35.8

1650
1804

1803
2437
2009
2745
R-22
30.5
43.5
65.0
Reciprocating, Semi-Hermetic
06E9265
06E9275
06E9299
6
6
6
1450
20.0
20.0
19.0
100%, 66%, 33%
76
58
78
60
180
Propeller Type — Direct Drive
2...950
3...950
30
1.0
15,700
23,700
1490
1750
1520
Enhanced Copper Tubes, Lanced Aluminum Fins
2...19
3...17
3...17
39.2
39.2
58.4
37.7
56.6
84.4
426 ± 7
320 ± 20
27 ± 3
44 ± 5
9.0
6.2
255 ± 10
160 ± 10
Fusible Plug
Liquid and Suction Line
210
15 / 8

21 / 8
7/
8
5/
8

21 / 8

*Based on operation at 45 F saturated suction temperature and 95 F outdoor ambient.

17

Physical data — English (cont)
40RM
UNIT 40RM
007
008
012
014
016
024
028
034
6
71 / 2
10
121/2
15
20
25
30
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
381/399
385/404
405/425
670/695
685/713
690/730
1020/1050
1030/1062
Base Unit with TXV (3-Row/4-Row)
175
175
175
225
225
225
325
325
Plenum
FANS
1...15
1...15
1...15
2...15
2...15
2...15
2...18
2...18
Qty...Diam. (in.)
2400
3000
4000
5000
6000
8000
10,000
12,000
Nominal Airflow (cfm)
1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
2.4
2.4
2.9
2.9
2.9
5.0
7.5
10.0
230-3-50, 400-3-50
Motor Speed (rpm)
1425
230-3-50, 400-3-50
R-22
REFRIGERANT
Operating charge (lb)
3.0
3.0
1.5/1.5
2.0/2.0
2.5/2.5
3.5/3.5
4.5/4.5
5.0/5.0
(approx per circuit)*
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
DIRECT-EXPANSION COIL
435
Max Working Pressure (psig)
6.67
8.33
10.0
13.25
17.67
19.88
24.86
29.83
Face Area (sq ft)
1
1
2
2
2
2
2
2
No. of Splits
—
—
Face...50/50
Split Type...Percentage
12/12
15/15
9/9
9/12
12/16
13/18
15/20
18/24
No. of Circuits per Split (3-Row/4-Row)
15
15
17
15
15
17
15
15
Fins/in.
STEAM COIL
175
Max Working Pressure (psig at 400 F)
6.67
6.67
6.67
13.33
13.33
13.33
15.0
15.0
Total Face Area (sq ft)
1...9
1...9
1...9
1...10
1...10
1...10
1...10
1...10
Rows...Fins/in.
HOT WATER COIL
150
Max Working Pressure (psig)
6.67
6.67
6.67
13.33
13.33
13.33
15.0
15.0
Total Face Area (sq ft)
2...8.5
2...8.5
2...8.5
2...8.5
2...8.5
2...8.5
2...12.5
2...12.5
Rows...Fins/in.
Water Volume
8.3
13.9
14.3
(gal)
1.1
1.85
1.90
(ft3)
PIPING CONNECTIONS,
Quantity...Size (in.)
1...11/8
2...11/8
2...11/8
2...11/8
2...11/8
2...13/8
2...13/8
1...11/8
DX Coil — Suction (ODF)
1...5/8
1...5/8
DX Coil — Liquid Refrigerant (ODF)
1...21/2
1...21/2
Steam Coil, In (MPT)
1...21/2
1...11/2
Steam Coil, Out (MPT)
1...11/2
1...2
1...11/2
Hot Water Coil, In (MPT)
1...11/2
1...2
1...11/2
Hot Water Coil, Out (MPT)
1...11/4
Condensate (Male PVC)
Throwaway — Factory Supplied
FILTERS
4...16 x 20 x 2
4...20 x 24 x 2
4...16 x 24 x 2
Quantity...Size (in.)
4...16 x 24 x 2
4...20 x 25 x 2
Right or Left Side
Access Location
LEGEND
TXV — Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

18

Dimensions
38AK007-012, 38AKS008-012
ELECTRICAL CONNECTIONS
DIMENSION CHART
UNIT
38AK

UNIT W/
ALUMINUM
COIL

DIM. A
1′-61/2″
[470]
1′-8″
008
[508]
1′-9″
012
[533]
1′-6″
S008
[457]
1′-7″
S009,S012 [483]
007

DIM. B
1′-23/4″
[375]
1′-61/2″
[470]
1′-8″
[508]
1′-43/4″
[426]
1′-5″
[432]

UNIT W/
COPPER COIL

DIM. C

DIM. D

DIM. E

DIM. F

DIM. A DIM. B
1′-8″
1′-3″
1′-21/4″
—
[508]
[381]
[362]
1′-91/2″ 1′-6″ 2′-913/16″ 1′-3″
[546]
[457]
[859]
[381]
1′-10″
1′-7″
2′-0″
1′-3″
[559]
[482]
[610]
[381]
1′-71/2″ 1′-41/2″ 2′-913/16″ 1′-3″
[495]
[419]
[859]
[381]
1′-71/2″ 1′-4″ 2′-913/16″ 1′-3″
[495]
[406]
[859]
[381]

1′-45/16″
[415]
2′-5/16″
[613]
2′-5/16″
[613]
2′-5/16″
[613]
2′-5/16″
[613]

2′-95/16″
[847]
3′-57/16″
[1053]
3′-57/16″
[1053]
3′-57/16″
[1053]
3′-57/16″
[1053]

CONNECTION SIZES
13/8″ Dia [35] Field Power Supply Hole
2″ Dia [51] Power Supply Knockout
21/2″ Dia [64] Power Supply Knockout
7/8″ Dia [22] Field Control Wiring Hole

AA
BB
CC
DD

SERVICE VALVE CONNECTIONS
UNIT 38AK
007
008
012
S008
S009,012

SUCTION
11/8″ [28.6]
11/8″ [28.6]
11/8″ [28.6]
11/8″ [28.6]
11/8″ [28.6]

LIQUID
2″ [12.7]
1/2″ [12.7]
5/8″ [15.9]
1/ ″ [12.7]
2
5/8″ [15.9]
1/

WEIGHT DISTRIBUTION
UNIT
38AK

STD
UNIT
Kg Lb

007
008
012
S008
S009,S012

154
178
193
231
256

007
008
012
S008
S009,S012

175
209
228
262
287

NOTES:
1. Dimensions in [

CORNER CORNER CORNER CORNER
W
X
Y
Z
Kg Lb Kg Lb Kg Lb Kg Lb
With Aluminum Coil
340 39
86 24
53 35
77 86 124
392 41
91 38
84 48 105 51 113
426 44
96 45
99 53 117 51 113
510 52 114 40
89 60 133 78 173
564 60 133 44
97 64 141 88 193
With Copper Coil
386 48 106 30
65 37
82 60 133
460 54 120 45 100 51 113 58 127
503 57 126 57 126 51 113 58 127
578 65 143 48 106 78 173 85 187
632 73 161 52 114 88 193 94 207

] are in millimeters.

2.

Center of Gravity. See chart for dimensions.

3.

Direction of airflow.

4. Minimum clearance shall be as follows: (local codes or jurisdiction may prevail)
a. Bottom to combustible surfaces, 0 in. [0 mm].
b. Either left or rear side of condensing unit must have 36-in. [914] clearance for
proper airflow; the remaining side(s) must have 12-in. [305] clearance each.
c. Overhead, 60 in. [1524], to assure proper condenser fan operation.
d. Between units, control box side, 42 in. [1067] per NEC (National Electrical Code)
(U.S.A. Standard) or equivalent local electrical code.
e. Between unit and ungrounded surfaces, control box side, 36 in.[914] per NEC or
equivalent local electrical code.
f. Between unit and block or concrete walls and other grounded surfaces: control box
side, 42 in. [1067] per NEC or equivalent local electrical code.
5. With the exception of the clearance for the condenser coil as stated in note 4b, a
removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or Class A, B, or C roof
covering material.
7. Certified dimension drawings available on request.

19

Dimensions (cont)
38AKS013-024

NOTES:
1. Service clearances are as follows:
Side (compressor) — 31/2 ft (1067 mm)
Side (opposite compressor) — 3 ft (914 mm)
Ends — 2 ft (610 mm)
Top — 5 ft (1524 mm)
2. See page 21 for corner weights and unit center of
gravity.

20

38AKS013-024 (cont)

UNIT
38AKS
013
013C
014
014C
016
016C
024
024C

CENTER OF GRAVITY (in.)
X
Y
in.
mm
in.
mm
38
965
17
432
38
965
19
483
38
965
16
406
38
965
18
457
38
965
16
406
38
965
18
457
37
940
17
432
37
940
19
483

UNIT
38AKS
013
013C
014
014C
016
016C
024
024C

TOTAL
WEIGHT
lb
732
825
779
919
789
929
900
1040

kg
332
374
353
417
358
421
409
472

OPERATIONAL CORNER WEIGHTS
A
B
C
D
lb kg lb kg lb kg lb kg
142 64 138 63 225 102 227 103
178 81 172 78 236 107 239 108
143 65 140 64 247 112 249 113
197 89 191 87 264 120 267 121
143 65 143 65 250 113 253 115
197 89 194 88 267 121 271 123
178 81 168 76 269 122 285 129
232 105 219 99 286 130 303 137

LEGEND
C — Copper Fin Coils

21

Dimensions (cont)
38AKS028, 034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
028
028C
034
034C

WEIGHT
(lb)
1650
1804
1803
2009

WEIGHT
(kg)
748
818
818
911

NOTE: A “C” in model number indicates unit has optional
factory-installed copper-fin coil.
4. Dimensions in [ ] are millimeters.

APPROXIMATE OPERATING WEIGHT*
AT SUPPORT POINTS — LB (KG)*
UNIT
38AKS
028
034

1

2

3

*Standard copper tube aluminum-fin coil.

22

4

418
626
242
364
(189.6) (284.0) (109.8) (165.1)
459
673
272
399
(208.2) (305.3) (123.4) (181.0)

TOTAL
1650
(748.4)
1803
(817.8)

38AKS044

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT
38AKS
044
044C

WEIGHT
(lb)
2437
2745

WEIGHT
(kg)
1106
1246

NOTE: A “C” in model number indicates unit has
optional factory-installed copper-fin coil.

APPROX. OPER. WT*
AT LIFTING HOLES — LB (KG)*
UNIT
38AKS
044

1

2

3

4

864
1077
221
275
(391.9) (488.5) (100.2) (124.7)

TOTAL
2437
(1106)

*Standard copper tube aluminum-fin coil.

23

Dimensions (cont)
40RM007-012
LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 76 mm (3 in.), 762 mm (2′-6″) with electric heat accessory
• Front: 762 mm (2′-6″)
• Right Side: 762 mm (2′-6″)
• Left Side: 762 mm (2′-6″)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.

UNIT
40RM
007
Standard 3-Row Coil
008
Standard 3-Row Coil
012
Standard 3-Row Coil
007
High-Capacity
4-Row Coil
008
High-Capacity
4-Row Coil
012
High-Capacity
4-Row Coil

24

UNIT WEIGHT —
LB (KG)
381 (173)
385 (175)
405 (184)
399 (181)

404 (184)

425 (193)

40RM014-024

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
• Rear: 76 mm (3 in.), 762 mm (2′-6″) with electric heat accessory
• Front: 762 mm (2′-6″)
• Right Side: 762 mm (2′-6″)
• Left Side: 762 mm (2′-6″)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
UNIT
UNIT WEIGHT —
40RM
LB (KG)
014
670 (304)
Standard 3-Row Coil
016
685 (311)
Standard 3-Row Coil
024
690 (313)
Standard 3-Row Coil
014
695 (315)
High-Capacity 4-Row Coil
016
713 (323)
High-Capacity 4-Row Coil
024
730 (331)
High-Capacity 4-Row Coil

25

Dimensions (cont)
40RM028, 034

LEGEND
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [

] are in millimeters.

2.
Direction of airflow.
3. Recommended clearance:
• Rear: 76 mm (3 in.), 762 mm (2′-6″) with electric
heat accessory
• Front: 762 mm (2′-6″)
• Right Side: 762 mm (2′-6″)
• Left Side: 762 mm (2′-6″)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.
UNIT
UNIT WEIGHT —
40RM
LB (KG)
028
1020 (463)
Standard 3-Row Coil
034
1030 (467)
Standard 3-Row Coil
028
1050 (470)
High-Capacity 4-Row Coil
034
1062 (482)
High-Capacity 4-Row Coil

26

Selection procedure — SI
NOTE: Pages 35-43 and 52-57 contain combination ratings for the 38AK and 38AKS units matched with 40RM
Series air handlers.
I Determine cooling load, evaporator-air temperature, and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . . . . 62 kW
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . . . . 48 kW
Temperature Air Entering Condenser (Edb) . . . 36 C
Temperature Air Entering
Evaporator (db/wb) . . . . . . . 26.7 C db, 20 C wb
Evaporator Air Quantity . . . . . . . . . . . . . . 3800 L/s
External Static Pressure . . . . . . . . . . . . . . . .100 Pa
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . 8 m (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AKS024 matched with a
40RM024. (See Combination Ratings table, page 41.)
This 38AKS024/40RM024 condensing unit-air
handler combination provides 62.7 kW of total cooling
capacity and 49.3 kW of sensible capacity at the given
conditions. If other temperatures or airflow values are
required, interpolate the values from the combination
ratings.
III Determine sizes of liquid and suction lines.
Enter Refrigerant Piping Sizes table (page 90). The
sizes shown are based on an equivalent length of pipe.

This equivalent length is equal to the linear length of
pipe indicated at the top of each sizing column, plus a
50% allowance for fitting losses. (For a more accurate
determination of actual equivalent length in place of
using the estimated 50% value, refer to Carrier System
Design Manual.) For this example, note in the linear
length column that the proper pipe size is 5/8 in. for
the liquid line and 15/8 in. for the suction line.
IV Determine
fan
rpm
and
bhp
(brake
horsepower).
At the Air Handler Fan Performance table (page 64),
enter the 40RM024 section at 3800 L/s and move to
the 100 Pa External Static Pressure (ESP) column.
Note that the conditions require 12.84 r/s at 2.52 kW.
V Determine motor and drive.
For the 40RM024 units, find the type of drive that satisfies the 12.84 r/s requirement in the 40RM Drive
Data tables on pages 95 and 96. The Standard Drive
— SI table shows an r/s range of 11.9 to 14.6 for the
40RM024 unit, which satisfies the r/s requirement for
the example described.
Next, enter the 40RM Fan Motor Data tables on
page 94, and find that for the 40RM024 unit, an standard motor has a motor kW of 3.73 which satisfies the
bhp requirement for the example described. Select the
standard motor and standard drive combination (option
code GC or ED).

Selection procedure — English
NOTE: Pages 44-51 and 58-63 contain combination ratings for the 38AK and 38AKS units matched with 40RM
Series air handlers.
I Determine cooling load, evaporator-air temperature, and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . .210,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . .175,000 Btuh
Temperature Air Entering Condenser (Edb) . . . .95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity . . . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . . . .0.8 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . .40 ft (Linear)
II Select condensing unit air-handler combination.
For this example, select a 38AKS024 matched with a
40RM024. (See Combination Ratings table, page 49.)
This 38AKS024/40RM024 condensing unit-air
handler combination provides 214,600 Btuh of total
cooling capacity and 179,000 Btuh of sensible capacity at the given conditions. If other temperatures or airflow values are required, interpolate the values from the
combination ratings.
III Determine sizes of liquid and suction lines.
Enter Refrigerant Piping Sizes table (page 90). The
sizes shown are based on an equivalent length of pipe.

This equivalent length is equal to the linear length of
pipe indicated at the top of each sizing column, plus a
50% allowance for fitting losses. (For a more accurate
determination of actual equivalent length in place of
using the estimated 50% value, refer to Carrier System
Design Manual.) For this example, note in the linear
length column that the proper pipe size is 5/8 in. for
the liquid line and 15/8 in. for the suction line.
IV Determine
fan
rpm
and
bhp
(brake
horsepower).
At the Air Handler Fan Performance table (page 66),
enter the 40RM024 section at 8000 cfm and move to
the 0.80 in. wg External Static Pressure (ESP) column.
Note that the conditions require 876 rpm at 4.21 bhp.
V Determine motor and drive.
For the 40RM024 units, find the type of drive that satisfies the 876 rpm requirement in the 40RM Drive
Data tables on pages 97 and 98. The Medium-Static
Drive — English table shows an rpm range of 814 to
1018 for the 40RM024 unit, which satisfies the rpm
requirement for the example described.
Next, enter the 40RM Fan Motor Data tables on
page 95, and find that for the 40RM024 unit, an alternate motor has a motor hp of 7.5 which satisfies the
bhp requirement for the example described. Select the
alternate motor and medium-static drive combination
(option code TC or RD).

27

Performance data
CONDENSING UNIT RATINGS — SI
38AK007
SST
(C)
–4
–2
0
2
4
6
8
10

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

38AK012
Air Temperature Entering Condenser (C)
28
32
36
40
44
48
52
13.4
12.5
11.7
10.9
10.0
9.20
8.36
4.33
4.45
4.56
4.67
4.78
4.89
5.00
39.6
43.4
47.3
51.2
55.0
58.9
62.8
14.5
13.7
12.9
12.0
11.2
10.4
9.51
4.48
4.61
4.73
4.86
4.98
5.11
5.23
40.2
43.9
47.7
51.4
55.1
58.8
62.6
15.7
14.9
14.1
13.2
12.3
11.5
10.6
4.63
4.77
4.91
5.05
5.19
5.32
5.46
40.9
44.5
48.2
51.8
55.5
59.1
62.7
17.0
16.1
15.2
14.4
13.5
12.6
11.8
4.78
4.93
5.09
5.24
5.39
5.55
5.70
41.7
45.3
48.9
52.5
56.1
59.7
63.3
18.2
17.4
16.5
15.6
14.7
13.8
12.9
4.93
5.10
5.27
5.44
5.60
5.77
5.94
42.5
46.1
49.6
53.2
56.8
60.4
63.9
19.5
18.7
17.7
16.8
15.9
15.0
14.1
5.08
5.27
5.45
5.63
5.82
6.00
6.18
43.4
46.9
50.5
54.0
57.6
61.1
64.7
20.9
20.0
19.0
18.1
17.2
16.3
15.3
5.23
5.44
5.63
5.83
6.03
6.23
6.42
44.3
47.8
51.3
54.9
58.4
61.9
65.4
22.3
21.3
20.4
19.4
18.5
17.5
16.6
5.39
5.61
5.82
6.03
6.24
6.46
6.67
45.2
48.7
52.2
55.7
59.2
62.7
66.2

38AK008
SST
(C)
–4
–2
0
2
4
6
8
10

—
CDT
kW
SST
TC

28

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

—
—
—
—
—

SST
(C)
–4
–2
0
2
4
6
8
10

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

28
23.9
7.96
39.7
25.5
8.11
40.3
27.1
8.27
40.9
28.8
8.45
41.6
30.5
8.64
42.3
32.3
8.84
43.1
34.2
9.06
43.9
36.1
9.28
44.8

Air Temperature Entering Condenser (C)
32
36
40
44
48
52
23.0
22.1
21.2
20.2
19.3
18.3
8.40
8.87
9.37
9.90
10.4
11.0
43.5
47.4
51.3
55.3
59.2
63.2
24.5
23.6
22.6
21.6
20.6
19.6
8.54
8.99
9.47
9.99
10.5
11.0
44.0
47.8
51.7
55.5
59.4
63.3
26.1
25.1
24.1
23.1
22.0
20.9
8.69
9.12
9.59
10.1
10.6
11.1
44.6
48.3
52.1
55.9
59.7
63.5
27.8
26.7
25.6
24.5
23.4
22.3
8.86
9.29
9.74
10.2
10.7
11.2
45.2
48.9
52.6
56.4
60.1
63.8
29.5
28.4
27.2
26.1
24.9
23.7
9.05
9.47
9.92
10.4
10.9
11.3
46.0
49.6
53.2
56.9
60.6
64.3
31.2
30.1
28.9
27.7
26.4
25.2
9.26
9.68
10.1
10.6
11.0
11.5
46.7
50.3
53.9
57.6
61.2
64.9
33.1
31.9
30.7
29.4
28.1
26.8
9.47
9.89
10.3
10.8
11.2
11.7
47.5
51.1
54.6
58.2
61.9
65.5
35.0
33.8
32.5
31.1
29.7
28.4
9.70
10.1
10.6
11.0
11.5
11.9
48.3
51.8
55.4
59.0
62.5
66.1

28
16.5
4.79
39.3
18.2
4.92
40.1
19.9
5.05
41.0
21.6
5.18
41.8
23.3
5.31
42.7
25.0
5.44
43.6
26.7
5.58
44.5
28.5
5.71
45.4

Air Temperature Entering Condenser (C)
32
36
40
44
48
52
15.6
14.7
13.8
12.9
11.9
11.0
5.01
5.22
5.40
5.55
5.70
5.84
43.0
46.7
50.5
54.2
58.0
61.8
17.3
16.3
15.3
14.4
13.4
12.4
5.17
5.40
5.61
5.78
5.95
6.12
43.8
47.5
51.3
55.0
58.7
62.5
18.9
17.9
16.9
15.8
14.8
13.8
5.32
5.58
5.81
6.01
6.21
6.40
44.7
48.4
52.1
55.8
59.5
63.2
20.5
19.5
18.4
17.3
16.3
15.2
5.48
5.76
6.02
6.24
6.46
6.68
45.5
49.2
52.9
56.5
60.2
63.9
22.2
21.1
20.0
18.8
17.7
16.6
5.63
5.94
6.22
6.47
6.72
6.96
46.4
50.0
53.7
57.3
61.0
64.6
23.8
22.7
21.5
20.3
19.1
18.0
5.79
6.12
6.43
6.70
6.97
7.24
47.2
50.8
54.5
58.1
61.7
65.3
25.5
24.3
23.1
21.8
20.6
19.4
5.94
6.30
6.63
6.93
7.23
7.52
48.1
51.7
55.3
58.9
62.5
66.1
27.2
26.0
24.7
23.4
22.1
20.8
6.10
6.48
6.83
7.16
7.48
7.80
49.0
52.6
56.1
59.7
63.3
66.8

38AKS008
Air Temperature Entering Condenser (C)
28
32
36
40
44
48
52
17.9
17.1
16.3
15.5
14.7
13.8
12.9
5.40
5.69
5.99
6.30
6.62
6.93
7.25
40.0
43.9
47.8
51.8
55.7
59.6
63.5
19.1
18.3
17.5
16.7
15.8
14.9
14.0
5.48
5.76
6.06
6.37
6.69
7.01
7.33
40.5
44.3
48.2
52.1
56.0
59.9
63.8
20.4
19.6
18.7
17.9
16.9
16.0
15.1
5.56
5.84
6.14
6.44
6.76
7.08
7.40
41.0
44.9
48.7
52.5
56.4
60.2
64.1
21.8
20.9
20.0
19.1
18.1
17.2
16.2
5.65
5.93
6.22
6.53
6.84
7.16
7.48
41.6
45.4
49.2
53.0
56.8
60.7
64.5
23.2
22.3
21.4
20.4
19.4
18.4
17.3
5.75
6.03
6.33
6.63
6.94
7.26
7.57
42.2
46.0
49.8
53.6
57.4
61.1
64.9
24.6
23.7
22.8
21.7
20.7
19.6
18.6
5.85
6.14
6.44
6.74
7.05
7.36
7.68
42.9
46.7
50.5
54.2
58.0
61.7
65.4
26.1
25.2
24.2
23.1
22.0
20.9
19.8
5.96
6.25
6.55
6.86
7.17
7.48
7.79
43.6
47.4
51.1
54.9
58.6
62.3
66.0
27.7
26.7
25.7
24.6
23.4
22.3
21.1
6.07
6.37
6.67
6.98
7.29
7.61
7.92
44.4
48.1
51.9
55.6
59.3
62.9
66.6

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (C)
Compressor Power
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)

SST
(C)
–4
–2
0
2
4
6
8
10

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

CONDENSING UNIT RATINGS — SI (cont)
38AKS009
SST
(C)
–4
–2
0
2
4
6
8
10

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

38AKS013
Air Temperature Entering Condenser (C)
28
32
36
40
44
48
52
20.7
19.5
18.3
17.1
15.9
14.7
13.5
6.30
6.56
6.80
7.02
7.19
7.36
7.52
41.5
45.1
48.7
52.3
55.9
59.5
63.0
22.7
21.5
20.2
19.0
17.7
16.4
15.2
6.54
6.83
7.10
7.34
7.54
7.73
7.93
42.7
46.2
49.8
53.4
56.9
60.4
64.0
24.8
23.5
22.1
20.8
19.5
18.2
16.8
6.78
7.09
7.39
7.66
7.89
8.11
8.33
43.8
47.3
50.8
54.4
57.9
61.4
64.9
26.9
25.5
24.1
22.7
21.3
19.9
18.5
7.02
7.36
7.68
7.98
8.23
8.48
8.73
44.9
48.4
51.9
55.4
58.9
62.4
65.8
29.0
27.5
26.0
24.6
23.1
21.6
20.2
7.27
7.63
7.98
8.30
8.58
8.86
9.14
46.0
49.5
52.9
56.4
59.9
63.3
66.8
31.0
29.5
27.9
26.4
24.9
23.4
21.8
7.51
7.90
8.27
8.62
8.93
9.23
9.54
47.1
50.5
54.0
57.4
60.9
64.3
67.7
33.1
31.5
29.9
28.3
26.7
25.1
23.5
7.75
8.17
8.57
8.94
9.28
9.61
9.95
48.2
51.6
55.1
58.5
61.9
65.3
68.7
35.3
33.6
31.9
30.3
28.6
26.9
—
8.00
8.44
8.87
9.26
9.63
9.99
—
49.4
52.8
56.2
59.6
62.9
66.3
—

–4
–2
0
2
4
6
8
10

—
CDT
kW
SST
TC

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

—
—
—
—
—

–8
–4
0
4
8
12

28
20.3
6.28
41.3
22.4
6.52
42.4
24.4
6.75
43.5
26.4
6.99
44.6
28.5
7.23
45.7
30.5
7.46
46.8
32.6
7.70
47.9
34.8
7.94
49.0

Air Temperature Entering Condenser (C)
32
36
40
44
48
52
19.2
18.0
16.8
15.6
14.4
13.3
6.55
6.80
7.01
7.19
7.33
7.46
44.9
48.6
52.1
55.7
59.3
62.9
21.1
19.9
18.6
17.4
16.2
14.9
6.81
7.09
7.33
7.53
7.71
7.86
46.0
49.6
53.1
56.7
60.2
63.8
23.1
21.8
20.5
19.2
17.9
16.6
7.07
7.38
7.64
7.87
8.08
8.26
47.0
50.6
54.1
57.7
61.2
64.7
25.1
23.7
22.3
21.0
19.6
18.2
7.34
7.66
7.96
8.22
8.45
8.66
48.1
51.6
55.1
58.6
62.2
65.7
27.1
25.6
24.2
22.7
21.3
19.9
7.60
7.95
8.27
8.56
8.82
9.06
49.1
52.6
56.1
59.6
63.1
66.6
29.0
27.5
26.0
24.5
23.0
21.5
7.86
8.24
8.59
8.90
9.19
9.46
50.2
53.7
57.1
60.6
64.1
67.5
31.0
29.5
27.9
26.3
24.8
23.2
8.12
8.53
8.90
9.25
9.57
9.86
51.3
54.7
58.1
61.6
65.0
68.5
33.1
31.5
29.8
28.2
26.5
24.9
8.39
8.82
9.22
9.59
9.94
10.3
52.4
55.8
59.2
62.6
66.0
69.4

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

Air Temperature Entering Condenser (C)
20
30
35
40
46
52
20.7
18.2
17.0
15.7
14.3
12.9
5.6
6.3
6.5
6.8
7.0
7.2
31.1
40.2
44.8
49.3
54.8
60.3
24.1
21.3
20.0
18.6
17.0
15.4
5.9
6.7
7.1
7.4
7.7
8.0
32.7
41.8
46.2
50.8
56.3
61.7
27.9
24.8
23.2
21.7
19.9
18.2
6.3
7.2
7.6
8.0
8.4
8.7
34.4
43.4
47.9
52.4
57.8
63.2
32.1
28.6
26.8
25.2
23.2
21.2
6.6
7.7
8.2
8.6
9.1
9.5
36.3
45.2
49.7
54.1
59.5
64.8
36.6
32.7
30.8
28.9
27.7
24.5
6.9
8.2
8.7
9.3
9.8
10.3
38.3
47.2
51.6
56.0
61.3
66.5
41.4
37.1
35.0
33.0
30.5
28.1
7.3
8.7
9.3
9.9
10.6
11.1
40.6
49.3
53.6
58.0
63.2
68.4

38AKS014
SST
(C)
–8

38AKS012
SST
(C)

SST
(C)

–4
0
4
8
12

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

Air Temperature Entering Condenser (C)
20
30
35
40
46
52
25.0
22.0
20.6
19.2
17.6
16.0
6.6
7.5
7.9
8.2
8.7
9.0
31.1
40.3
44.9
49.5
55.1
60.6
29.1
25.8
24.2
22.6
20.7
19.0
7.0
8.0
8.5
8.9
9.4
9.9
32.7
41.8
46.4
50.9
56.4
61.9
33.6
29.9
28.1
26.3
24.2
22.2
7.5
8.6
9.1
9.6
10.2
10.8
34.5
43.5
48.0
52.5
58.0
63.4
38.6
34.4
32.4
30.4
28.0
25.8
7.9
9.2
9.8
10.4
11.0
11.7
36.4
45.3
49.8
54.2
60.0
65.0
44.0
39.3
37.0
34.8
32.2
29.7
8.4
9.8
10.5
11.1
11.9
12.6
38.4
47.3
51.7
56.1
61.4
66.7
49.7
44.6
42.1
39.6
36.7
—
8.9
10.5
11.2
11.9
12.7
—
40.7
49.4
53.7
58.1
63.3
—

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (C)
Compressor Power
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)

29

Performance data (cont)
CONDENSING UNIT RATINGS — SI (cont)
38AKS016
SST
(C)
–8
–4
0
4
8
12

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

38AKS028
Air Temperature Entering Condenser (C)
20
30
35
40
46
52
31.7
27.9
26.0
24.2
22.1
20.2
9.4
10.3
10.7
11.1
11.4
11.7
33.7
42.7
47.2
51.7
57.1
62.5
36.8
32.5
30.5
28.4
26.1
23.8
10.1
11.2
11.7
12.2
12.6
13.0
35.7
44.6
49.0
53.5
58.8
64.1
42.5
37.6
35.3
33.0
30.4
—
10.9
12.2
12.8
13.3
13.9
—
37.8
46.6
51.0
55.4
60.7
—
48.6
43.2
40.6
38.0
35.1
—
11.7
13.2
13.9
14.5
15.1
—
40.2
48.8
53.1
57.5
62.7
—
55.1
49.2
46.3
43.5
40.1
—
12.6
14.3
15.0
15.7
16.5
—
42.7
51.2
55.4
59.7
64.8
—
62.2
55.6
52.4
49.3
—
—
13.4
15.3
16.2
17.0
—
—
45.3
53.7
57.9
62.1
—
—

SST
(C)
–6
–4
–2
0
2
4
6

38AKS024
SST
(C)
–2
0
2
4
6
8
10

—
CDT
kW
SST
TC

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

—
—
—
—
—

Air Temperature Entering Condenser (C)
20
30
35
40
46
52
53.4
46.8
43.4
39.9
35.7
31.4
12.6
14.2
14.9
15.4
15.9
16.4
34.3
43.3
47.7
52.2
57.4
62.7
58.2
51.3
47.7
44.1
39.7
35.2
13.1
14.8
15.5
16.2
16.8
17.3
35.6
44.5
48.9
53.3
58.5
63.7
63.0
55.8
52.1
48.3
43.7
39.1
13.5
15.4
16.2
16.9
17.6
18.3
36.9
45.7
50.0
54.4
59.6
64.7
67.9
60.3
56.4
52.5
47.7
42.9
14.0
16.0
16.9
17.6
18.4
19.2
38.2
46.9
51.2
55.5
60.6
65.8
72.7
64.8
60.8
56.7
51.7
46.7
14.5
16.6
17.5
18.4
19.3
20.1
39.6
48.1
52.4
56.6
61.7
66.8
77.5
69.3
65.1
60.9
55.7
50.6
15.0
17.2
18.2
19.1
20.1
21.0
40.9
49.3
53.5
57.7
62.8
67.8
82.4
73.8
69.5
65.1
59.7
54.4
15.5
17.8
18.9
19.9
20.9
22.0
42.2
50.5
54.7
58.8
63.8
68.8

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (C)
Compressor Power
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)

8
10

Air Temperature Entering Condenser (C)
32
36
40
44
48
52.4
49.5
46.6
43.8
41.0
18.0
18.6
19.1
19.6
20.0
44.8
48.5
52.1
55.8
59.6
57.3
54.2
51.1
48.1
45.2
18.9
19.5
20.1
20.6
21.1
45.7
49.3
52.9
56.5
60.2
61.1
57.8
54.7
51.5
48.5
19.5
20.3
20.9
21.5
22.0
46.4
50.0
53.6
57.1
60.7
66.4
62.9
59.6
56.3
53.0
20.4
21.2
21.9
22.6
23.1
47.4
50.9
54.5
58.0
61.6
71.9
68.3
64.7
61.2
57.7
21.3
22.2
23.0
23.7
24.3
48.5
52.0
55.4
59.0
62.5
76.3
72.5
68.7
65.0
61.4
22.0
22.9
23.8
24.5
25.2
49.3
52.8
56.2
59.7
63.2
82.3
78.3
74.3
70.3
66.5
23.0
23.9
24.8
25.7
26.5
50.5
53.9
57.3
60.8
64.2
87.0
82.8
78.6
74.5
70.5
23.7
24.7
25.7
26.6
27.4
51.4
54.8
58.2
61.6
65.0
93.5
89.0
84.6
80.3
76.0
24.6
25.7
26.8
27.8
28.7
52.7
56.0
59.4
62.8
66.1

52
38.3
20.4
63.3
42.3
21.5
63.8
45.4
22.4
64.4
49.7
23.7
65.1
54.3
24.9
66.0
57.8
25.9
66.7
62.7
27.2
67.7
66.5
28.2
68.4
71.7
29.5
69.5

28
62.4
20.0
42.1
68.7
20.7
42.2
73.3
21.3
42.7
79.5
22.1
43.6
85.9
23.0
44.6
90.9
23.7
45.4
97.8
24.6
46.6
103.0
25.2
47.5
110.0
26.2
48.8

Air Temperature Entering Condenser (C)
32
36
40
44
48
58.9
55.3
51.7
48.1
44.5
20.6
21.2
21.6
21.9
22.2
46.0
50.0
54.1
58.0
62.0
65.0
61.3
57.6
53.7
49.9
21.4
22.2
22.7
23.2
23.5
46.1
50.1
54.1
58.1
62.1
69.7
66.0
62.1
58.2
54.3
22.1
22.9
23.5
24.1
24.5
46.4
50.2
54.1
58.1
62.0
75.8
72.1
68.3
64.3
60.3
23.0
23.9
24.6
25.2
25.8
47.2
50.8
54.5
58.3
62.1
82.1
78.2
74.3
70.3
66.3
24.0
24.9
25.7
26.4
27.1
48.1
51.7
55.2
58.9
62.5
87.0
83.0
79.0
74.9
70.8
24.7
25.7
26.6
27.4
28.1
48.9
52.5
56.0
59.5
63.1
93.6
89.5
85.3
81.0
76.8
25.7
26.8
27.8
28.6
29.4
50.1
53.5
57.0
60.5
64.0
98.8
94.5
90.2
85.8
81.4
26.4
27.6
28.6
29.6
30.5
50.9
54.4
57.8
61.3
64.7
106.0 101.0 96.9
92.3
87.7
27.4
28.7 29.8
30.9
31.9
52.2
55.6
59.0
62.4
65.8

52
40.8
22.2
66.1
46.1
23.7
66.1
50.3
24.8
66.1
56.1
26.2
66.1
62.1
27.6
66.2
66.6
28.7
66.6
72.4
30.1
67.5
76.9
31.2
68.2
83.0
32.7
69.2

38AKS034
SST
(C)
–6
–4
–2
0
2
4
6
8
10

30

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

28
55.3
17.4
41.2
60.4
18.2
42.1
64.4
18.8
42.9
69.9
19.6
43.9
75.6
20.5
45.0
80.2
21.1
45.9
86.4
22.0
47.1
91.2
22.6
48.0
97.9
23.5
49.3

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

CONDENSING UNIT RATINGS — SI (cont)
38AKS044
SST
(C)
–6
–4
–2
0
2
4
6
8
10

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

Air Temperature Entering Condenser (C)
28
32
36
40
44
48
52
82.8
78.8
74.8
70.9
67.1
63.3
59.5
27.3
28.1
29.0
29.7
30.4
31.0
31.5
41.4
45.3
49.3
53.3
57.3
61.3
65.3
90.9
86.5
82.3
78.0
73.9
69.8
65.7
28.3
29.3
30.3
31.1
31.9
32.6
33.2
41.3
45.3
49.3
53.3
57.3
61.3
65.3
97.3
92.7
88.2
83.7
79.4
75.0
70.7
29.0
30.1
31.2
32.2
33.0
33.8
34.5
41.4
45.3
49.3
53.3
57.3
61.3
65.3
106.0 101.0 96.5
91.7
87.1
82.4
77.8
30.0
31.2 32.4
33.5
34.5
35.4
36.2
41.8
45.6
49.4
53.4
57.3
61.3
65.3
115.0 110.0 105.0 99.9
95.1
90.2
85.3
31.2
32.5
33.7 34.9
36.0
37.0
37.9
42.5
46.2
50.0
53.7
57.5
61.4
65.4
121.0 116.0 111.0 106.0 101.0 96.1
91.1
32.1
33.5
34.8
36.0
37.2 38.2
39.2
43.2
46.9
50.5
54.2
58.0
61.7
65.5
130.0 125.0 120.0 114.0 109.0 104.0 98.8
33.3
34.8
36.2
37.6
38.8
40.0 41.1
44.2
47.8
51.5
55.1
58.7
62.4
66.1
138.0 132.0 127.0 121.0 116.0 110.0 105.0
34.2
35.8
37.3
38.8
40.1
41.3
42.5
45.0
48.6
52.2
55.8
59.4
63.0
66.7
148.0 142.0 136.0 130.0 124.0 118.0 113.0
35.5
37.2
38.8
40.4
41.8
43.2
44.4
46.1
49.7
53.2
56.8
60.4
64.0
67.6

—
CDT
kW
SST
TC

—
—
—
—
—

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (C)
Compressor Power
Saturated Suction Temperature (C)
Gross Cooling Capacity (kW)

CONDENSING UNIT RATINGS — ENGLISH
38AK007
SST
(F)
TC
25 kW
CDT
TC
30 kW
CDT
TC
35 kW
CDT
TC
40 kW
CDT
TC
45 kW
CDT
TC
50 kW
CDT
—
CDT
kW
SST
TC

—
—
—
—
—

80
46.8
4.30
101
52.3
4.50
103
58.1
4.69
105
64.1
4.90
107
70.4
5.10
109
77.0
5.32
111

Air Temperature Entering Condenser (F)
85
95
100
105
115
120
44.9 40.9 38.9 36.9 32.9 31.0
4.39 4.54 4.62 4.70 4.85 4.93
106
115
120
125
135
140
50.4 46.4 44.4 42.4 38.4 36.4
4.60 4.78 4.87 4.96 5.14 5.23
107
116
121
126
135
139
56.2 52.1 50.0 48.0 43.8 41.8
4.81 5.02 5.12 5.23 5.44 5.54
109
118
123
127
136
141
62.1 57.9 55.8 53.7 49.5 47.4
5.03 5.26 5.38 5.50 5.74 5.86
111
120
125
129
138
142
68.4 64.0 61.8 59.6 55.3 53.1
5.25 5.51 5.65 5.78 6.05 6.18
113
122
127
131
140
144
74.9 70.4 68.1 65.8 61.3 59.0
5.47 5.77 5.91 6.06 6.36 6.50
116
124
129
133
142
146

125
29.0
5.01
144
34.4
5.32
144
39.7
5.65
145
45.2
5.98
147
50.9
6.31
149
56.7
6.65
151

38AK008
SST
(F)
TC
25 kW
CDT
TC
30 kW
CDT
TC
35 kW
CDT
TC
40 kW
CDT
TC
45 kW
CDT
TC
50 kW
CDT

80
62.0
5.31
102
68.1
5.42
103
74.5
5.54
104
81.1
5.67
106
88.1
5.82
108
95.4
5.97
110

Air Temperature Entering Condenser (F)
85
95
100
105
115
120
60.3 56.6 54.7 52.8 48.7 46.6
5.50 5.91 6.13 6.35 6.79 7.01
107
116
121
126
136
141
66.2 62.3 60.3 58.2 54.0 51.9
5.61 6.01 6.22 6.44 6.89 7.11
108
117
122
127
137
142
72.5 68.3 66.2 63.9 59.4 57.2
5.73 6.13 6.34 6.55 7.00 7.22
109
119
123
128
138
143
79.1 74.7 72.4 70.1 65.2 62.8
5.87 6.27 6.48 6.69 7.13 7.35
111
120
125
130
139
144
86.1 81.5 79.1 76.5 71.3 68.7
6.02 6.43 6.64 6.85 7.28 7.50
112
122
127
131
141
145
93.3 88.6 86.0 83.4 77.8 75.1
6.18 6.60 6.81 7.02 7.46 7.58
114
124
128
133
142
147

125
44.6
7.23
146
49.7
7.34
146
54.9
7.44
147
60.3
7.57
148
66.1
7.72
150
72.3
7.89
151

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (F)
Compressor Power
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

31

Performance data (cont)
CONDENSING UNIT RATINGS — ENGLISH (cont)
38AK012
SST
(F)
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

38AKS009
80
82.7
7.83
101
90.3
8.04
103
98.2
8.28
104
107
8.55
106
115
8.84
108
124
9.15
111

Air Temperature Entering Condenser (F)
85
95
100
105
115
120
80.7 76.5 74.4 72.2 67.6 65.3
8.12 8.75 9.09 9.45 10.2 10.6
106
116
121
125
135
140
88.1 83.6 81.3 78.9 74.1 71.7
8.32 8.92 9.24 9.58 10.3 10.7
107
117
121
126
136
141
95.9 91.1 88.6 86.0 80.8 78.2
8.56 9.14 9.45 9.78 10.5 10.8
109
118
123
127
137
142
104 99.1 96.3 93.6 87.9 85.1
8.83 9.40 9.70 10.0 10.7 11.0
111
120
124
129
138
143
113
108
105
102 95.6 92.6
9.12 9.70 10.0 10.3 10.9 11.3
113
122
126
131
140
144
122
116
113
110
104
100
9.43 10.0 10.3 10.6 11.2 11.6
115
124
128
133
142
146

80
57.8
4.72
101
65.9
4.89
103
74.0
5.06
105
82.1
5.23
107
90.2
5.40
109
98.7
5.57
112

Air Temperature Entering Condenser (F)
85
95
100
105
115
120
55.6 51.2 49.1 46.9 42.5 40.3
4.88 5.18 5.32 5.44 5.64 5.74
105
114
119
124
133
138
63.5 58.9 56.5 54.2 49.4 47.1
5.08 5.43 5.58 5.73 5.98 6.10
107
117
121
126
135
140
71.5 66.5 63.9 61.4 56.4 53.8
5.27 5.67 5.85 6.02 6.32 6.47
109
119
123
128
137
142
79.4 74.1 71.4 68.7 63.3 60.6
5.47 5.91 6.11 6.31 6.65 6.83
112
121
125
130
139
144
87.4 81.7 78.8 76.0 70.3 67.4
5.66 6.15 6.38 6.59 6.99 7.19
114
123
127
132
141
145
95.8 89.7 86.7 83.6 77.5 74.5
5.85 6.39 6.64 6.88 7.33 7.55
116
125
129
134
143
147

125
62.9
10.9
145
69.2
11.0
145
75.5
11.1
146
82.2
11.3
147
89.5
11.6
149
97.2
11.9
150

38AKS008
SST
(F)
25
30
35
40
45
50

—
CDT
kW
SST
TC

32

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

—
—
—
—
—

SST
(F)
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

80
72.3
6.22
105
82.2
6.54
108
92.1
6.87
110
102
7.19
113
112
7.51
116
122
7.85
119

Air Temperature Entering Condenser (F)
85
95
100
105
115
120
69.5 63.7 61.0 58.2 52.4 49.6
6.41 6.76 6.92 7.07 7.30 7.41
109
118
123
127
136
141
79.1 73.0 70.0 66.9 60.8 57.7
6.76 7.16 7.35 7.52 7.80 7.94
112
121
125
130
139
143
88.8 82.2 79.0 75.7 69.1 65.8
7.11 7.56 7.77 7.96 8.30 8.48
115
123
128
132
141
145
98.5 91.5 88.0 84.5 77.5 74.0
7.46 7.96 8.19 8.41 8.81 9.01
117
126
130
135
143
148
108
101 97.0 93.2 85.8 82.1
7.81 8.36 8.62 8.86 9.31 9.54
120
129
133
137
146
150
118
110
106
102 94.6 90.7
8.16 8.76 9.05 9.32 9.82 10.1
123
132
136
140
149
153

125
46.7
7.53
145
54.6
8.09
147
62.6
8.65
150
70.5
9.20
152
78.4
9.76
154
—
—
—

80
71.0
6.20
104
80.8
6.51
107
90.6
6.83
110
100
7.15
113
110
7.47
115
121
7.79
118

Air Temperature Entering Condenser (F)
85
95
100
105
115
68.2
62.8
60.0
57.1
51.5
6.40
6.76
6.91
7.06
7.30
109
118
122
127
136
77.8
71.9
68.8
65.8
59.8
6.74
7.15
7.33
7.50
7.79
111
120
125
129
138
87.4
81.0
77.7
74.5
68.0
7.08
7.54
7.75
7.94
8.29
114
123
127
132
141
97.0
90.1
86.6
83.1
76.3
7.42
7.93
8.16
8.38
8.79
117
126
130
134
143
107
99.2
95.5
91.8
84.6
7.76
8.32
8.58
8.83
9.28
120
128
132
137
145
117
109
105
101
93.2
8.11
8.72
9.00
9.28
9.79
122
131
135
139
148

125
45.9
7.47
145
53.8
8.02
147
61.7
8.58
149
69.5
9.13
152
77.4
9.68
154
85.5
10.2
156

38AKS012

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (F)
Compressor Power
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

125
38.1
5.84
143
44.7
6.23
144
51.3
6.62
146
57.9
7.00
148
64.5
7.39
150
71.4
7.77
152

SST
(F)
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

CONDENSING UNIT RATINGS — ENGLISH (cont)
38AKS016

38AKS013
SST
(F)
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

20
25
30
35
40
45
50

Air Temperature Entering Condenser (F)
70
85
95
100
115
125
73
66
61
59
52
47
5.8
6.4
6.7
6.9
7.3
7.5
91
104
113
118
132
141
82
74
68
66
58
53
6.0
6.7
7.1
7.3
7.7
8.0
93
106
115
120
134
143
90
82
76
73
65
60
6.3
7.0
7.5
7.7
8.2
8.5
95
108
117
122
135
144
100
90
84
81
72
67
6.5
7.4
7.9
8.1
8.7
9.1
97
111
120
124
137
146
110
100
93
90
80
74
6.8
7.7
8.3
8.5
9.2
9.6
99
113
122
126
140
148
120
109
102
99
89
82
7.0
8.0
8.6
8.9
9.7
10.2
102
115
124
128
142
151
131
120
112
108
97
90
7.3
8.4
9.0
9.3
10.2
10.7
105
118
127
131
144
153

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

20
25
30
35
40
45
50

—
CDT
kW
SST
TC

—
—
—
—
—

20
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

Air Temperature Entering Condenser (F)
70
85
95
100
115
125
112
101
94
90
80
73
9.7
10.6
11.0
11.3
11.8
12.1
96
109
118
122
136
145
125
112
104
101
89
82
10.3
11.2
11.8
12.0
12.7
13.0
98
111
120
125
138
149
138
124
116
112
99
91
10.8
11.9
12.5
12.8
13.5
13.9
101
114
123
127
140
147
152
137
128
123
110
—
11.4
12.5
13.2
13.5
14.4
—
103
117
125
130
143
—
166
151
141
136
121
—
12.0
13.2
14.0
14.4
15.3
—
107
119
128
132
145
—
181
165
154
149
133
—
12.6
14.0
14.8
15.2
16.2
—
110
122
131
135
148
—
198
180
168
163
—
—
13.2
14.7
15.6
16.0
—
—
113
126
134
138
—
—

38AKS024

38AKS014
SST
(F)

SST
(F)

Air Temperature Entering Condenser (F)
70
85
95
100
115
125
89
80
74
71
63
58
6.8
7.6
8.1
8.3
8.9
9.3
91
105
114
118
132
141
98
89
83
80
71
65
7.2
8.0
8.5
8.8
9.5
9.9
93
106
116
120
134
143
109
99
92
89
79
73
7.5
8.4
9.0
9.2
10.0
10.5
95
109
118
122
136
145
120
109
102
98
88
81
7.8
8.8
9.4
9.7
10.6
11.1
97
111
120
124
138
147
132
120
112
108
97
90
8.1
9.2
9.9
10.2
11.1
11.7
100
113
122
126
140
149
145
132
123
119
107
99
8.5
9.6
10.4
10.7
11.7
12.4
102
115
124
129
142
151
158
144
135
130
117
109
8.8
10.1
10.8
11.2
12.3
13.0
105
118
127
131
144
153

SST
(F)
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

Air Temperature Entering Condenser (F)
80
85
95
100
115
125
152
146
134
128
122
109
13.1
13.5
14.2
14.5
14.8
15.2
102
107
116
120
125
134
174
168
155
148
141
128
13.9
14.3
15.1
15.5
15.8
16.3
106
110
119
123
128
136
196
189
175
168
161
147
14.7
15.2
16.1
16.5
16.9
17.5
109
113
122
126
130
139
218
211
196
188
181
166
15.4
16.0
17.0
17.5
17.9
18.6
112
116
125
129
133
142
240
232
216
209
201
184
16.2
16.8
17.9
18.4
18.9
19.8
115
119
128
132
136
144
262
254
237
229
220
203
17.0
17.6
18.9
19.4
20.0
20.9
118
122
130
135
139
147

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (F)
Compressor Power
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

33

Performance data (cont)
CONDENSING UNIT RATINGS (cont)
38AKS028
SST
(F)
20
25
30
35
40
45
50

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

38AKS044
Air Temperature Entering Condenser (F)
85
95
100
105
115
120
125
181.0 167.0 161.0 154.0 141.0 134.0 128.0
17.4
18.3
18.6
19.0
19.6
19.8
20.0
108.0 117.0 122.0 126.0 136.0 141.0 145.0
202.0 187.0 180.0 173.0 159.0 152.0 145.0
18.5
19.4
19.8
20.2
20.9
21.2
21.5
110.0 119.0 124.0 128.0 137.0 142.0 146.0
225.0 209.0 201.0 193.0 178.0 171.0 163.0
19.5
20.6
21.0
21.5
22.3
22.7
23.0
112.0 121.0 126.0 130.0 139.0 143.0 148.0
249.0 231.0 223.0 215.0 198.0 190.0 182.0
20.6
21.7
22.3
22.8
23.7
24.2
24.6
115.0 123.0 128.0 132.0 141.0 145.0 150.0
274.0 256.0 246.0 237.0 220.0 211.0 202.0
21.6
23.0
23.6
24.1
25.2
25.7
26.2
117.0 126.0 130.0 135.0 143.0 148.0 152.0
301.0 281.0 271.0 261.0 242.0 233.0 224.0
22.8
24.2
24.9
25.5
26.7
27.3
27.8
120.0 129.0 133.0 137.0 146.0 150.0 154.0
329.0 307.0 297.0 287.0 266.0 256.0 246.0
23.9
25.5
26.2
26.9
28.3
28.9
29.5
123.0 131.0 136.0 140.0 148.0 152.0 157.0

38AKS034
SST
(F)
20
25
30
35
40
45
50

34

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

85
203.0
20.0
110.0
230.0
21.0
110.0
256.0
22.0
112.0
283.0
23.1
114.0
311.0
24.3
117.0
340.0
25.4
119.0
371.0
26.6
122.0

Air Temperature Entering Condenser (F)
95
100
105
115
120
125
187.0 178.0 170.0 153.0 145.0 136.0
20.8
21.1
21.4
21.8
21.8
21.8
120.0 125.0 130.0 140.0 145.0 150.0
212.0 204.0 195.0 176.0 167.0 158.0
22.0
22.4
22.8
23.4
23.6
23.7
120.0 125.0 130.0 140.0 145.0 150.0
239.0 230.0 221.0 202.0 192.0 182.0
23.2
23.7
24.1
24.9
25.3
25.5
121.0 126.0 130.0 140.0 145.0 150.0
265.0 256.0 247.0 228.0 218.0 208.0
24.4
25.0
25.5
26.5
26.9
27.2
123.0 127.0 132.0 141.0 146.0 150.0
292.0 282.0 273.0 253.0 243.0 233.0
25.7
26.4
27.0
28.1
28.6
29.0
125.0 130.0 134.0 143.0 147.0 152.0
320.0 310.0 300.0 279.0 269.0 259.0
27.0
27.8
28.5
29.7
30.3
30.8
128.0 132.0 136.0 145.0 149.0 154.0
350.0 339.0 328.0 307.0 296.0 285.0
28.4
29.2
30.0
31.4
32.1
32.7
130.0 135.0 139.0 148.0 152.0 156.0

SST
(F)
20
25
30
35
40
45
50

—
CDT
kW
SST
TC

TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT
TC
kW
CDT

—
—
—
—
—

85
271.0
27.3
109.0
305.0
28.6
109.0
341.0
29.9
109.0
377.0
31.3
111.0
415.0
32.9
113.0
455.0
34.5
115.0
497.0
36.1
117.0

Air Temperature Entering Condenser (F)
95
100
105
115
120
125
252.0 243.0 234.0 216.0 208.0 199.0
28.5
29.0
29.5
30.3
30.7
31.0
119.0 124.0 129.0 139.0 144.0 149.0
284.0 274.0 264.0 245.0 235.0 225.0
30.0
30.7
31.3
32.3
32.8
33.2
119.0 124.0 129.0 139.0 144.0 149.0
319.0 308.0 297.0 275.0 265.0 254.0
31.5
32.3
33.0
34.2
34.8
35.3
119.0 124.0 129.0 139.0 144.0 149.0
355.0 343.0 332.0 309.0 297.0 286.0
33.1
33.9
34.7
36.1
36.8
37.4
120.0 125.0 129.0 139.0 144.0 149.0
391.0 379.0 367.0 343.0 331.0 319.0
34.8
35.7
36.6
38.2
38.9
39.6
122.0 126.0 131.0 140.0 145.0 150.0
429.0 416.0 403.0 377.0 365.0 352.0
36.6
37.6
38.6
40.3
41.1
41.9
124.0 128.0 133.0 142.0 147.0 151.0
468.0 455.0 441.0 413.0 400.0 386.0
38.4
39.5
40.6
42.5
43.5
44.3
126.0 131.0 135.0 144.0 149.0 153.0

LEGEND
Out of Range
Saturated Discharge Temperature at Compressor (F)
Compressor Power
Saturated Suction Temperature (F)
Gross Cooling Capacity (1000 Btuh)

COMBINATION RATINGS — SI
38AK007/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
850
1150
Air Ent
Cond
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
19.0 17.8 15.7 19.8 18.7 16.8 20.4
TC
32 SHC 10.1 11.9 15.4 11.4 13.7 16.8 12.5
5.12 4.98 4.72 5.23 5.08 4.85 5.29
kW
18.4 17.2 15.1 19.2 18.0 16.3 19.7
TC
36 SHC 9.86 11.7 15.1 11.1 13.5 16.3 12.3
5.37 5.21 4.92 5.47 5.31 5.08 5.54
kW
17.8 16.6 14.5 18.5 17.3 15.8 19.0
TC
40 SHC 9.62 11.4 14.5 10.9 13.2 15.8 12.1
5.60 5.42 5.13 5.71 5.54 5.30 5.78
kW
17.1 15.9 14.0 17.8 16.6 15.2 18.2
TC
44 SHC 9.37 11.2 14.0 10.7 13.0 15.2 11.8
5.82 5.64 5.32 5.94 5.75 5.53 6.01
kW
16.3 15.2 13.4 17.0 15.9 14.7 17.4
TC
48 SHC 9.12 10.9 13.4 10.4 12.7 14.7 11.6
6.04 5.84 5.51 6.16 5.96 5.75 6.24
kW
15.6 14.5 12.8 16.2 15.2 14.1 16.6
TC
52 SHC 8.85 10.6 12.8 10.1 12.4 14.1 11.3
6.24 6.03 5.69 6.37 6.16 5.96 6.45
kW
38AK007/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
Air Ent
Cond
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
21.2 19.9 17.7 22.0 20.8 19.4 22.5
TC
32 SHC 11.7 14.0 17.7 13.5 16.5 19.4 15.1
5.43 5.27 5.01 5.53 5.38 5.21 5.60
kW
20.5 19.2 17.1 21.3 20.1 18.8 21.8
TC
36 SHC 11.4 13.7 17.1 13.2 16.2 18.8 14.9
5.69 5.52 5.24 5.79 5.63 5.46 5.86
kW
19.8 18.5 16.5 20.5 19.3 18.2 21.0
TC
40 SHC 11.2 13.5 16.5 13.0 15.9 18.2 14.6
5.94 5.75 5.46 6.05 5.87 5.71 6.12
kW
19.0 17.7 16.0 19.7 18.5 17.6 20.1
TC
44 SHC 10.9 13.2 16.0 12.7 15.6 17.6 14.3
6.17 5.97 5.69 6.29 6.10 5.95 6.36
kW
18.2 17.0 15.4 18.8 17.7 17.0 19.3
TC
48 SHC 10.6 12.9 15.4 12.4 15.3 17.0 14.0
6.40 6.19 5.91 6.52 6.33 6.19 6.60
kW
17.3 16.2 14.8 18.0 16.9 16.3 18.4
TC
52 SHC 10.4 12.6 14.8 12.1 14.9 16.3 13.7
6.63 6.40 6.13 6.74 6.54 6.42 6.83
kW
—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

16
17.9
17.9
4.99
17.4
17.4
5.23
16.9
16.9
5.47
16.3
16.3
5.69
15.7
15.7
5.92
15.1
15.1
6.15

38AK008/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
850
1150
Air Ent
Cond
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
22.1 20.8 18.5 23.1 21.8 19.6 23.8
TC
32 SHC 11.2 13.1 16.7 12.4 14.8 19.4 13.6
6.00 5.88 5.67 6.10 5.98 5.77 6.16
kW
21.5 20.3 18.0 22.4 21.2 19.1 23.1
TC
36 SHC 11.0 12.8 16.4 12.2 14.6 19.0 13.4
6.36 6.24 6.02 6.46 6.34 6.13 6.52
kW
20.8 19.6 17.4 21.8 20.6 18.5 22.4
TC
40 SHC 10.7 12.6 16.1 12.0 14.3 18.5 13.1
6.73 6.61 6.39 6.84 6.71 6.50 6.90
kW
19.9 18.8 16.7 20.8 19.7 17.7 21.4
TC
44 SHC 10.4 12.2 15.8 11.6 14.0 17.7 12.8
7.21 7.09 6.87 7.31 7.18 6.98 7.38
kW
19.4 18.3 16.3 20.2 19.1 17.3 20.8
TC
48 SHC 10.2 12.0 15.5 11.4 13.8 17.3 12.5
7.1 7.39 7.17 7.61 7.48 7.28 7.67
kW
18.7 17.6 15.6 19.4 18.3 16.6 19.9
TC
52 SHC 9.89 11.7 15.2 11.1 13.5 16.6 12.2
7.91 7.79 7.57 8.01 7.88 7.68 8.07
kW

16
20.6
20.6
5.36
20.0
20.0
5.63
19.4
19.4
5.88
18.7
18.7
6.13
18.0
18.0
6.38
17.3
17.3
6.61

38AK008/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
Air Ent
Cond
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
23.8 22.5 20.1 24.8 23.5 21.4 25.5
TC
32 SHC 12.5 14.7 19.2 14.1 17.1 21.4 15.7
6.13 6.01 5.78 6.22 6.10 5.91 6.28
kW
23.2 21.9 19.5 24.1 22.9 20.9 24.7
TC
36 SHC 12.2 14.5 18.9 13.9 16.9 20.9 15.5
6.49 6.37 6.14 6.59 6.46 6.26 6.65
kW
22.5 21.2 18.9 23.4 22.1 20.3 23.9
TC
40 SHC 11.9 14.2 18.6 13.6 16.6 20.3 15.2
6.86 6.73 6.50 6.96 6.83 6.64 7.03
kW
21.7 20.5 18.3 22.5 21.3 19.7 23.1
TC
44 SHC 11.7 13.9 18.3 13.3 16.3 19.7 14.9
7.25 7.12 6.88 7.34 7.21 7.03 7.41
kW
20.9 19.7 17.6 21.7 20.5 19.1 22.2
TC
48 SHC 11.4 13.6 17.6 13.0 16.0 19.1 14.6
7.64 7.51 7.28 7.73 7.60 7.43 7.79
kW
20.0 18.9 16.9 20.8 19.7 18.4 21.2
TC
52 SHC 11.1 13.3 16.9 12.7 15.6 18.4 14.3
8.04 7.90 7.67 8.13 8.00 7.84 8.19
kW

1450
20
19.2
15.4
5.15
18.6
15.1
5.38
17.9
14.8
5.61
17.1
14.5
5.84
16.4
14.2
6.05
15.6
13.9
6.25

1800
20
21.4
18.7
5.45
20.7
18.3
5.71
19.9
18.0
5.96
19.1
17.5
6.19
18.3
17.1
6.43
17.5
16.5
6.66

1450
20
22.5
16.5
6.04
21.9
16.2
6.40
21.2
16.0
6.77
20.2
15.6
7.25
19.6
15.4
7.54
18.8
15.1
7.94

16
20.5
20.5
5.86
19.9
19.9
6.21
19.4
19.4
6.58
18.7
18.7
7.08
18.2
18.2
7.38
17.6
17.6
7.79

1800
20
24.2
19.3
6.16
23.5
19.1
6.52
22.7
18.7
6.90
21.9
18.4
7.27
21.1
18.0
7.66
20.2
17.7
8.06

16
22.7
22.7
6.02
22.2
22.2
6.39
21.6
21.6
6.77
20.9
20.9
7.17
20.3
20.3
7.57
19.5
19.5
7.98

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving
indoor coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s

Ldb C = Edb C –

where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to the actual length plus a 50% allowance for
fitting losses.) For other equivalent lengths, refer to the Carrier
System Design Manual, Part 3, for line losses.

35

Performance data (cont)
COMBINATION RATINGS — SI (cont)
38AK008/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
26.8 25.4 23.3 27.4 26.1 24.9 27.9
TC
15.5 18.9 23.3 17.5 21.6 24.9 19.2
SHC
32
6.97 6.84 6.64 7.04 6.91 6.79 7.08
kW
26.0 24.6 22.7 26.6 25.4 24.3 27.1
TC
15.3 18.6 22.7 17.2 21.2 24.3 19.0
36
SHC
7.38 7.24 7.04 7.45 7.32 7.20 7.49
kW
25.2 23.9 22.1 25.8 24.6 23.6 26.2
TC
15.0 18.3 22.1 16.9 20.9 23.6 18.7
SHC
40
7.80 7.66 7.46 7.87 7.73 7.63 7.92
kW
24.3 23.0 21.4 24.9 23.7 22.9 25.2
TC
14.7 17.9 21.4 16.6 20.5 22.9 18.3
44
SHC
8.23 8.08 7.90 8.30 8.16 8.07 8.34
kW
23.3 22.1 20.7 23.9 22.8 22.1 24.2
TC
14.3 17.6 20.7 16.2 20.1 22.1 18.0
SHC
48
8.66 8.51 8.35 8.73 8.60 8.51 8.78
kW
22.4 21.2 20.0 22.9 21.8 21.3 23.2
TC
14.0 17.2 20.0 15.9 19.6 21.3 17.6
SHC
52
9.10 8.96 8.81 9.17 9.04 8.97 9.22
kW
38AKS008/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
850
1150
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
23.6 21.9 19.8 24.8 23.1 21.1 25.5
TC
12.2 14.2 19.8 13.6 16.4 21.1 15.4
32
SHC
5.77 5.62 5.43 5.88 5.72 5.55 5.94
kW
22.9 21.3 19.3 24.0 22.4 20.5 24.7
TC
11.9 13.9 19.3 13.3 16.1 20.5 15.1
36
SHC
6.15 5.96 5.73 6.27 6.08 5.87 6.34
kW
22.2 20.5 18.5 23.3 21.6 19.7 23.9
TC
11.6 13.6 18.5 13.0 15.7 19.7 14.8
40
SHC
6.52 6.31 6.06 6.65 6.44 6.21 6.73
kW
21.4 19.8 17.9 22.4 20.8 19.1 22.9
TC
11.3 13.2 17.9 12.6 15.3 19.1 14.5
44
SHC
6.87 6.62 6.34 7.02 6.77 6.51 7.10
kW
20.6 19.0 17.2 21.6 20.0 18.3 22.1
TC
11.0 12.9 17.2 12.3 14.9 18.3 14.2
48
SHC
7.24 6.96 6.64 7.40 7.12 6.83 7.49
kW
19.9 18.3 16.6 20.7 19.2 17.6 21.2
TC
10.7 12.5 16.6 11.9 14.5 17.6 13.9
SHC
52
7.61 7.30 6.96 7.78 7.47 7.17 7.87
kW
—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

36

16
26.0
26.0
6.90
25.3
25.3
7.31
24.6
24.6
7.74
23.8
23.8
8.18
23.0
23.0
8.62
22.1
22.1
9.08

38AKS008/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
25.7 23.7 21.6 26.6 24.9 22.9 27.3
TC
13.7 16.0 21.6 15.9 18.2 22.9 17.7
SHC
32
5.95 5.78 5.60 6.04 5.88 5.71 6.10
kW
24.8 23.0 21.0 25.7 24.0 22.2 26.3
TC
13.3 15.6 21.0 15.5 17.8 22.2 17.4
36
SHC
6.36 6.15 5.93 6.46 6.27 6.06 6.53
kW
24.0 22.2 20.2 24.9 23.2 21.4 25.5
TC
13.0 15.2 20.2 15.2 17.4 21.4 17.1
SHC
40
6.75 6.52 6.27 6.85 6.64 6.42 6.93
kW
23.1 21.3 19.4 23.9 22.3 20.6 24.4
TC
12.6 14.8 19.4 14.9 16.9 20.6 16.7
44
SHC
7.13 6.86 6.57 7.25 7.00 6.74 7.33
kW
22.3 20.5 18.6 23.0 21.4 19.8 23.5
TC
12.3 14.4 18.6 14.6 16.5 19.8 16.4
SHC
48
7.52 7.21 6.89 7.64 7.37 7.09 7.73
kW
21.4 19.7 17.9 22.0 20.5 19.0 22.5
TC
11.9 14.0 17.9 14.2 16.0 19.0 16.0
SHC
52
7.92 7.58 7.22 8.04 7.74 7.43 8.13
kW

16
21.9
21.9
5.63
21.3
21.3
5.97
20.6
20.6
6.32
19.9
19.9
6.63
19.1
19.1
6.97
18.4
18.4
7.31

38AKS008/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
20
16
28.0 26.0 23.9 — 27.0 25.2 — 27.5 26.3
TC
16.6 19.2 23.9 — 22.0 25.2 — 24.9 26.3
32
SHC
6.16 5.98 5.80 — 6.07 5.91 — 6.12 6.01
kW
— 25.1 23.1 — 26.0 24.4 — 26.5 25.4
TC
— 18.8 23.1 — 21.6 24.4 — 24.4 25.4
36
SHC
— 6.39 6.16 — 6.49 6.31 — 6.54 6.42
kW
— 24.2 22.2 — 25.1 23.5 — 25.5 24.5
TC
— 18.4 22.2 — 21.2 23.5 — 24.0 24.5
40
SHC
— 6.77 6.52 — 6.88 6.68 — 6.93 6.81
kW
— 23.2 21.3 — 24.0 22.5 — 24.4 23.5
TC
— 17.9 21.3 — 20.7 22.5 — 23.4 23.5
44
SHC
— 7.14 6.86 — 7.26 7.04 — 7.33 7.19
kW
— 22.3 20.5 — 23.0 21.6 —
—
—
TC
— 17.5 20.5 — 20.3 21.6 —
—
—
48
SHC
— 7.52 7.21 — 7.65 7.41 —
—
—
kW
— 21.3 19.6 —
—
—
—
—
—
TC
— 17.1 19.6 —
—
—
—
—
—
SHC
52
— 7.89 7.56 —
—
—
—
—
—
kW

2350
20
26.7
23.8
6.96
25.9
2.34
7.37
25.1
23.0
7.79
24.2
22.4
8.22
23.3
21.8
8.66
22.4
21.1
9.10

1450
20
23.9
17.9
5.80
23.2
17.6
6.17
22.3
17.2
6.53
21.5
16.7
6.88
20.6
16.3
7.23
19.8
15.9
7.59

1800
20
25.6
20.3
5.95
24.7
19.9
6.35
23.8
19.5
6.72
22.8
19.0
7.09
21.9
18.6
7.46
21.0
18.1
7.84

16
23.8
23.8
5.79
23.1
23.1
6.16
22.3
22.3
6.52
21.4
21.4
6.87
20.6
20.6
7.23
19.7
19.7
7.59

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving
indoor coil (hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s

Ldb C = Edb C –

where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting piping sized to the outdoor unit field connections. (Equivalent length is equal to the actual length plus a 50% allowance for
fitting losses.) For other equivalent lengths, refer to the Carrier
System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — SI (cont)
38AKS009/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
1800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
20
29.4 27.2 24.8 30.7 28.7 26.3 31.6 29 7
TC
15.2 17.7 24.8 17.4 20.1 26.3 19.1 22.2
32 SHC
7.88 7.60 7.27 8.06 7.79 7.47 8.18 7.93
kW
28.4 26.3 23.9 29.6 27.7 25.4 30.5 28.6
TC
14.8 17.2 23.9 17.0 19.6 25.4 18.8 21.7
36 SHC
8.34 8.02 7.67 8.53 8.24 7.89 8.66 8.38
kW
27.4 25.4 23.1 28.6 26.7 24.5 29.4 27.6
TC
14.4 16.7 23.1 16.6 19.1 24.5 18.4 21.2
40 SHC
8.79 8.45 8.06 8.99 8.67 8.30 9.12 8.81
kW
26.4 24.4 22.2 27.5 25.7 23.6 28.2 26.4
TC
14.0 16.3 22.2 16.2 18.6 23.6 18.0 20.7
44 SHC
9.23 8.84 8.41 9.43 9.08 8.67 9.57 9.23
kW
25.4 23.5 21.4 26.3 24.6 22.6 27.0 25.3
TC
13.5 15.8 21.4 15.8 18.1 22.6 17.6 20.2
48 SHC
9.68 9.24 8.78 9.89 9.50 9.06 10.04 9.66
kW
—
22.4 20.4
—
23.4 21.6
—
24.1
TC
—
15.3 20.4
—
17.5 21.6
—
19.6
52 SHC
—
9.69 9.19
—
9.94 9.49
—
10.11
kW
38AKS009/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
32.5 30.2 27.6 33.7 31.5 29.2
—
TC
18.1 21.0 27.6 20.2 24.1 29.2
—
32 SHC
8.30 7.99 7.65 8.47 8.16 7.86
—
kW
31.4 29.1 26.6 32.6 30.3 28.1
—
TC
17.7 20.5 26.6 19.8 23.5 28.1
—
36 SHC
8.79 8.45 8.07 8.97 8.63 8.31
—
kW
30.2 28.0 25.6 31.3 29.1 27.1
—
TC
17.3 20.1 25.6 19.3 23.0 27.1
—
40 SHC
9.26 8.89 8.49 9.45 9.08 8.74
—
kW
29.0 26.9 24.6 30.0 27.9 26.0
—
TC
16.9 19.6 24.6 18.9 22.5 26.0
—
44 SHC
9.72 9.31 8.88 9.93 9.51 9.15
—
kW
27.7 25.7 23.6
—
27.6 24.9
—
TC
16.5 19.0 23.6
—
21.9 24.9
—
48 SHC
10.20 9.74 9.27
—
9.96 9.57
—
kW
—
24.4 22.5
—
25.3 23.7
—
TC
—
18.5 22.5
—
21.3 23.7
—
52 SHC
—
10.19 9.70
—
10.41 10.02
—
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

16
27.3
27.3
7.61
26.3
26.3
8.04
25.4
25.4
8.46
24.5
24.5
8.85
23.5
23.5
9.26
22.5
22.5
9.71

38AK012/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
29.8 28.2 25.1 31.3 29.7 26.8 32.3
TC
14.9 17.3 22.0 16.8 20.0 26.2 18.6
32 SHC
7.33 7.16 6.85 7.50 7.32 7.02 7.60
kW
29.1 27.5 24.5 30.5 28.9 26.1 31.5
TC
14.6 17.0 21.7 16.5 19.7 25.9 18.3
36 SHC
7.74 7.56 7.25 7.90 7.72 7.42 8.01
kW
28.3 26.7 23.8 29.6 28.1 25.4 30.5
TC
14.3 16.6 21.3 16.2 19.4 25.4 18.0
40 SHC
8.16 7.99 7.69 8.32 8.14 7.85 8.43
kW
27.4 25.9 23.1 28.7 27.2 24.6 29.5
TC
13.9 16.3 21.0 15.8 19.0 24.6 17.6
44 SHC
8.61 8.44 8.16 8.76 8.58 8.31 8.86
kW
26.5 25.0 22.3 27.7 26.2 23.9 28.5
TC
13.6 15.9 20.6 15.5 18.6 23.9 17.3
48 SHC
9.07 8.91 8.64 9.21 9.04 8.78 9.31
kW
25.6 24.2 21.6 26.7 25.3 23.1 27.4
TC
13.2 15.6 20.2 15.1 18.3 23.1 16.9
52 SHC
9.54 9.38 9.13 9.68 9.51 9.27 9.77
kW

20
16
32.2 30.4
27.0 30.4
8.26 8.02
31.0 29.3
26.5 29.3
8.74 8.48
29.8 28.3
25.9 28.3
9.19 8.93
28.5 27.1
25.3 27.1
9.63 9.37
27.2 26.0
24.7 26.0
10.08 9.81
25.8 24.7
21.9 24.7
10.53 10.28

38AK012/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
32.1 30.5 27.6 33.2 31.5 29.2 33.8
TC
17.4 20.8 27.2 19.5 23.7 29.2 21.4
32 SHC
8.79 8.58 8.23 8.92 8.71 8.42 9.00
kW
31.3 29.7 26.9 32.3 30.7 28.5 32.9
TC
17.1 20.5 26.8 19.1 23.4 28.5 21.1
36 SHC
9.26 9.05 8.70 9.39 9.18 8.90 9.47
kW
30.4 28.8 26.1 31.3 29.8 27.8 31.9
TC
16.7 20.1 26.1 18.8 23.0 27.8 20.8
40 SHC
9.75 9.55 9.21 9.88 9.67 9.41 9.96
kW
29.4 27.9 25.3 30.3 28.8 27.0 30.8
TC
16.4 19.8 25.3 18.5 22.6 27.0 20.4
44 SHC
10.3 10.1 9.74 10.4 10.2 9.95 10.5
kW
28.4 26.9 24.5 29.2 27.8 26.2 29.7
TC
16.0 19.4 24.5 18.1 22.2 26.2 20.0
48 SHC
10.8 10.6 10.3 10.9 10.7 10.5 11.0
kW
27.4 25.9 23.8 28.1 26.7 25.4 28.6
TC
15.7 19.0 23.8 17.7 21.8 25.4 19.7
52 SHC
11.3 11.1 10.9 11.4 11.3 11.1 11.5
kW

2350

1800
20
30.7
22.6
7.43
29.9
22.3
7.83
29.0
21.9
8.25
28.0
21.6
8.68
27.1
21.2
9.14
26.0
20.8
9.60

16
28.2
28.2
7.16
27.5
27.5
7.57
26.8
26.8
8.00
26.1
26.1
8.47
25.4
25.4
8.94
24.6
24.6
9.43

2350
20
32.2
26.4
8.80
31.4
26.1
9.27
30.4
25.7
9.76
29.4
25.2
10.3
28.4
24.8
10.8
27.3
24.3
11.3

16
30.7
30.7
8.61
30.0
30.0
9.09
29.2
29.2
9.60
28.4
28.4
10.1
27.5
27.5
10.7
26.6
26.6
11.2

3. Formulas:
Ldb C = Edb C –

SHCkW x 1000
1.23 x L/s

Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s
where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

37

Performance data (cont)
COMBINATION RATINGS — SI (cont)
38AK012/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1750
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
33.5 31.8 28.9 34.5 32.8 30.9 35.1
TC
18.9 22.8 28.9 21.4 26.3 30.9 23.7
32 SHC
7.41 7.23 6.95 7.51 7.34 7.14 7.57
kW
32.7 31.0 28.2 33.6 31.9 30.2 34.2
TC
18.6 22.5 28.2 21.1 25.9 30.2 23.3
36 SHC
7.80 7.63 7.35 7.90 7.73 7.55 7.97
kW
31.7 30.1 27.5 32.6 31.0 29.5 33.1
TC
18.2 22.1 27.5 20.7 25.5 29.5 23.0
40 SHC
8.22 8.04 7.78 8.31 8.14 7.98 8.38
kW
30.7 29.1 26.7 31.5 30.0 28.6 32.0
TC
17.9 21.8 26.7 20.3 25.1 28.6 22.6
44 SHC
8.65 8.48 8.23 8.74 8.57 8.43 8.80
kW
29.6 28.1 25.9 30.4 28.9 27.8 30.9
TC
17.5 21.4 25.9 20.0 24.7 27.8 22.2
48 SHC
9.10 8.93 8.71 9.18 9.02 8.90 9.24
kW
28.5 27.1 25.2 29.2 27.9 26.9 29.7
TC
17.1 21.0 25.2 19.6 24.2 26.9 21.8
52 SHC
9.55 9.39 9.21 9.64 9.48 9.38 9.68
kW

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

38

16
27.0
27.0
7.60
26.1
26.1
8.04
25.2
25.2
8.46
24.3
24.3
8.85
23.3
23.3
9.25
22.3
22.3
9.65

38AKS012/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1750
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
34.0 31.1 28.9
—
32.3 30.6
—
TC
19.8 23.1 28.9
—
27.1 30.6
—
32 SHC
8.51 8.13 7.85
—
8.29 8.07
—
kW
32.9 30.0 27.9
—
31.2 29.6
—
TC
19.4 22.6 27.9
—
26.6 29.6
—
36 SHC
9.02 8.60 8.30
—
8.77 8.54
—
kW
31.6 28.8 26.8
—
29.9 28.5
—
TC
18.9 22.1 26.8
—
26.0 28.5
—
40 SHC
9.51 9.04 8.73
—
9.23 8.99
—
kW
30.3 27.5 25.8
—
28.6 27.3
—
TC
18.4 21.5 25.8
—
25.4 27.3
—
44 SHC
10.03 9.49 9.14
—
9.69 9.45
—
kW
—
26.4 24.7
—
27.4 26.3
—
TC
—
21.0 24.7
—
24.9 26.3
—
48 SHC
—
9.91 9.55
—
10.13 9.88
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
52 SHC
—
—
—
—
—
—
—
kW

2950
20
33.5
29.3
7.41
32.6
28.8
7.80
31.7
28.4
8.22
30.6
27.8
8.65
29.6
27.2
9.09
28.5
26.6
9.55

38AKS012/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000
1400
1800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
20
29.1 26.9 24.5 30.4 28.4 26.0 31.3 29.4
TC
15.1 17.5 24.5 17.2 20.0 26.0 19.0 22.1
32 SHC
7.87 7.59 7.28 8.04 7.78 7.47 8.15 7.91
kW
28.1 26.0 23.6 29.4 27.4 25.1 30.2 28.3
TC
14.7 17.1 23.6 16.9 19.5 25.1 18.7 21.6
36 SHC
8.33 8.02 7.68 8.51 8.23 7.89 8.64 8.36
kW
27.2 25.1 22.8 28.3 26.4 24.2 29.1 27.3
TC
14.3 16.6 22.8 16.5 19.0 24.2 18.3 21.1
40 SHC
8.78 8.44 8.07 8.97 8.66 8.30 9.10 8.80
kW
26.2 24.2 22.0 27.2 25.4 23.3 27.9 26.2
TC
13.9 16.2 22.0 16.1 18.5 23.3 17.9 20.6
44 SHC
9.23 8.84 8.41 9.43 9.07 8.67 9.57 9.22
kW
25.2 23.2 21.0 26.2 24.4 22.4 26.9 25.1
TC
13.5 15.7 21.0 15.7 18.0 22.4 17.5 20.1
48 SHC
9.66 9.23 8.78 9.86 9.48 9.06 10.01 9.63
kW
—
22.2 20.2
—
23.2 21.4
—
23.8
TC
—
15.2 20.2
—
17.4 21.4
—
19.5
52 SHC
—
9.63 9.13
—
9.89 9.44
—
10.05
kW

—
Edb
Ewb
kW
SHC
TC

16
32.5
32.5
7.30
31.7
31.7
7.70
30.9
30.9
8.13
30.0
30.0
8.57
29.0
29.0
9.03
28.1
28.1
9.51

38AKS012/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
32.1 29.8 27.3 33.4 31.1 28.9
—
TC
18.0 20.9 27.3 20.1 23.9 28.9
—
32 SHC
8.26 7.97 7.64 8.43 8.13 7.85
—
kW
31.1 28.8 26.3 32.3 30.0 27.9
—
TC
17.6 20.4 26.3 19.7 23.4 27.9
—
36 SHC
8.76 8.43 8.07 8.93 8.60 8.29
—
kW
29.9 27.7 25.4
—
28.8 26.8
—
TC
17.2 19.9 25.4
—
22.9 26.8
—
40 SHC
9.23 8.87 8.48
—
9.05 8.73
—
kW
28.7 26.6 24.4
—
27.6 25.8
—
TC
16.9 19.4 24.4
—
22.3 25.8
—
44 SHC
9.72 9.30 8.87
—
9.51 9.14
—
kW
27.6 25.5 23.3
—
26.5 24.7
—
TC
16.5 19.0 23.3
—
21.8 24.7
—
48 SHC
10.17 9.72 9.26
—
9.93 9.55
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
52 SHC
—
—
—
—
—
—
—
kW

2350
20
31.8
26.8
8.23
30.7
26.3
8.71
29.5
25.8
9.16
28.2
25.2
9.62
27.1
24.7
10.05
—
—
—

16
30.1
30.1
8.00
29.1
29.1
8.47
28.0
28.0
8.91
26.9
26.9
9.36
25.8
25.8
9.79
—
—
—

2950
20
16
33.3 31.9
30.6 31.9
8.42 8.24
32.2 30.9
30.0 30.9
8.92 8.73
30.8 29.7
29.4 29.7
9.38 9.20
29.5 28.5
28.8 28.5
9.87 9.68
28.3 27.5
28.2 27.5
10.32 10.14
—
—
—
—
—
—

3. Formulas:
Ldb C = Edb C –

SHCkW x 1000
1.23 x L/s

Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s
where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — SI (cont)
38AKS013/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1000/
1400
1800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
20
32.2 30.0 27.3 33.9 31.7 29.0 35.0 32.9
TC
16.4 19.0 27.3 18.5 21.7 29.0 20.3 23.8
20 SHC
6.61 6.46 6.28 6.72 6.57 6.39 6.79 6.65
kW
30.5 28.3 25.8 32.0 29.9 27.4 32.9 31.0
TC
15.7 18.2 25.8 17.8 20.8 27.4 19.6 22.9
28 SHC
7.61 7.37 7.10 7.77 7.55 7.27 7.88 7.67
kW
29.6 27.5 25.0 31.0 29.0 26.6 31.9 30.0
TC
15.3 17.8 25.0 17.5 20.3 26.6 19.2 22.4
32 SHC
8.12 7.85 7.55 8.28 8.03 7.74 8.40 8.16
kW
28.7 26.6 24.2 30.0 28.0 25.7 30.9 29.0
TC
14.9 17.4 24.2 17.1 19.8 25.7 18.9 21.9
36 SHC
8.67 8.49 8.29 8.78 8.61 8.41 8.86 8.70
kW
27.8 25.8 23.5 29.0 27.1 24.9 29.8 28.0
TC
14.6 17.0 23.5 16.7 19.3 24.9 18.5 21.4
40 SHC
9.10 8.71 8.28 9.31 8.96 8.55 9.47 9.13
kW
27.3 25.0 22.6 28.5 26.4 24.1 29.3 27.4
TC
14.3 16.6 22.6 16.5 19.0 24.1 18.4 21.1
44 SHC
9.49 9.13 8.72 9.69 9.36 8.97 9.84 9.51
kW
26.4 24.2 21.8 27.5 25.5 23.3 28.3 26.4
TC
13.9 16.2 21.8 16.2 18.5 23.3 18.0 20.7
48 SHC
9.92 9.53 9.11 10.12 9.77 9.37 10.27 9.92
kW
25.0 23.1 21.0 25.9 24.2 22.3 26.5 24.9
TC
13.4 15.7 21.0 15.6 17.9 22.3 17.4 19.9
52 SHC
10.42 9.96 9.46 10.64 10.22 9.77 10.79 10.39
kW

16
30.0
30.0
6.46
28.4
28.4
7.38
27.6
27.6
7.86
26.7
26.7
8.50
25.9
25.9
8.73
25.1
25.1
9.14
24.3
24.3
9.55
23.2
23.2
9.98

38AKS013/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1750
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
38.1 35.1 32.4 39.4 36.5 34.2 40.2
TC
21.3 24.9 32.4 24.3 29.1 34.2 27.3
20 SHC
7.00 6.80 6.62 7.09 6.89 6.74 7.14
kW
35.8 32.9 30.5 37.0 34.2 32.2 37.7
TC
20.5 23.9 30.5 23.4 28.0 32.2 26.4
28 SHC
8.20 7.87 7.61 8.32 8.02 7.80 8.40
kW
34.7 31.8 29.5 35.8 33.0 31.2 36.4
TC
20.0 23.4 29.5 22.9 27.5 31.2 26.0
32 SHC
8.74 8.38 8.10 8.87 8.53 8.31 8.95
kW
33.5 30.6 28.5 34.5 31.9 30.2 35.2
TC
19.6 22.9 28.5 22.5 26.9 30.2 25.6
36 SHC
9.09 8.84 8.66 9.18 8.94 8.80 9.23
kW
32.3 29.5 27.6 33.2 30.6 29.2 33.8
TC
19.1 22.4 27.6 22.0 26.4 29.2 25.1
40 SHC
9.94 9.41 9.05 10.12 9.63 9.35 10.23
kW
32.1 29.0 26.9 33.1 30.2 28.6 33.7
TC
19.0 22.2 26.9 22.0 26.2 28.6 25.1
44 SHC
10.29 9.78 9.43 10.46 9.98 9.72 10.56
kW
30.9 27.9 25.9 31.9 29.1 27.6 32.5
TC
18.6 21.7 25.9 21.6 25.7 27.6 24.7
48 SHC
10.74 10.19 9.84 10.91 10.40 10.15 11.01
kW
28.7 26.1 24.5 29.4 27.0 26.0 29.9
TC
17.8 20.9 24.5 20.7 24.7 26.0 23.8
52 SHC
11.32 10.68 10.30 11.50 10.91 10.65 11.61
kW

38AKS013/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
20
16
35.9 33.5 30.6 37.4 35.0 32.4 38.3 35.9 33.6
TC
19.2 22.5 30.6 21.6 25.7 32.4 24.0 28.7 33.6
20 SHC
6.85 6.69 6.50 6.95 6.79 6.62 7.01 6.86 6.70
kW
33.8 31.5 28.8 35.2 32.9 30.5 36.0 33.7 31.7
TC
18.5 21.6 28.8 20.8 24.7 30.5 23.2 27.7 31.7
28 SHC
7.98 7.72 7.43 8.13 7.87 7.61 8.21 7.96 7.74
kW
32.8 30.5 27.9 34.1 31.8 29.5 34.8 32.5 30.7
TC
18.2 21.1 27.9 20.3 24.2 29.5 22.8 27.2 30.7
32 SHC
8.50 8.22 7.90 8.66 8.38 8.10 8.75 8.47 8.25
kW
31.7 29.4 27.0 32.9 30.7 28.5 33.6 31.4 29.7
TC
17.8 20.7 27.0 19.9 23.7 28.5 22.4 26.6 29.7
36 SHC
8.93 8.74 8.52 9.04 8.84 8.66 9.10 8.90 8.76
kW
30.6 28.4 26.1 31.7 29.5 27.5 32.3 30.2 28.7
TC
17.5 20.2 26.1 19.5 23.2 27.5 22.0 26.1 28.7
40 SHC
9.62 9.21 8.77 9.83 9.42 9.04 9.95 9.55 9.26
kW
30.2 27.8 25.3 31.4 29.0 26.9 32.1 29.8 28.1
TC
17.3 20.0 25.3 19.4 23.0 26.9 21.9 25.9 28.1
44 SHC
9.98 9.59 9.17 10.18 9.79 9.43 10.29 9.91 9.64
kW
29.2 26.8 24.4 30.3 28.0 25.9 30.9 28.6 27.1
TC
17.0 19.5 24.4 19.0 22.5 25.9 21.5 21.9 27.1
48 SHC
10.42
10.00 9.57 10.62 10.21 9.84 10.74 10.32 10.06
kW
27.3 25.2 23.2 28.2 26.2 24.5 28.6 26.7 25.6
TC
16.4 18.8 23.2 18.2 21.7 24.5 20.7 24.5 25.6
52 SHC
10.97 10.48 9.99 11.19 10.70 10.30 11.31 10.83 10.56
kW

38AKS014/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1450
1900
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
40.4 37.7 34.2 42.3 39.6 36.3 43.5
TC
20.6 24.3 34.2 23.4 27.8 36.3 25.8
20 SHC
8.07 7.81 7.49 8.25 7.99 7.69 8.36
kW
38.2 35.6 32.4 39.9 37.3 34.3 41.0
TC
19.9 23.4 32.4 22.5 26.7 34.3 24.9
28 SHC
9.28 8.98 8.61 9.48 9.18 8.83 9.60
kW
37.0 34.5 31.4 38.7 36.1 33.3 39.6
TC
19.6 22.9 31.4 22.0 26.2 33.3 24.5
32 SHC
9.90 9.56 9.15 10.12 9.78 9.40 10.25
kW
35.9 33.4 30.5 37.4 34.9 32.3 38.3
TC
19.2 22.4 30.5 21.6 25.6 32.3 24.0
36 SHC
10.51
10.13 9.69 10.75 10.37 9.96 10.89
kW
34.7 32.3 29.5 36.2 33.8 31.2 37.0
TC
18.8 22.0 29.5 21.1 25.1 31.2 23.6
40 SHC
11.09 10.70 10.26 11.32 10.93 10.53 11.46
kW
33.6 31.2 28.5 34.9 32.6 30.2 35.7
TC
18.4 21.5 28.5 20.7 24.6 30.2 23.1
44 SHC
11.73
11.26 10.74 11.99 11.53 11.07 12.15
kW
32.4 30.1 27.5 33.7 31.4 29.1 34.4
TC
18.0 21.0 27.5 20.2 24.0 29.1 22.7
48 SHC
12.36 11.85 11.28 12.64 12.13 11.64 12.80
kW
—
25.2 23.2
—
26.2 24.5
—
TC
—
18.8 23.2
—
21.7 24.5
—
52 SHC
—
10.48
9.99
—
10.70
10.30
—
kW

2950
20
26
37.6 35.7
32.6 35.7
6.97 6.84
35.2 33.6
31.5 33.6
8.13 7.95
34.0 32.6
30.9 32.6
8.66 8.48
32.8 31.5
30.3 31.5
9.03 8.91
31.5 30.4
29.7 30.4
9.80 9.58
31.2 30.0
29.6 30.0
10.15 9.95
30.1 29.0
29.0 29.0
10.58 10.38
27.9 27.1
27.9 27.1
11.12 10.93

2350
20
40.9
31.0
8.11
38.4
29.9
9.31
37.2
29.3
9.92
35.9
28.7
10.52
34.6
28.1
11.07
33.4
27.6
11.69
32.1
21.9
12.30
26.7
24.5
10.83

16
37.7
37.7
7.82
35.6
35.6
8.99
34.6
34.6
9.57
33.5
33.5
10.16
32.5
32.5
10.73
31.4
31.4
11.30
30.3
30.3
11.90
25.6
25.6
10.56

See Legend and Notes on page 43.

39

Performance data (cont)
COMBINATION RATINGS — SI (cont)
38AKS014/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1750
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
43.0 39.8 36.4 44.8 41.6 38.5 45.9
TC
23.2 27.1 36.4 26.2 31.4 38.5 29.2
20 SHC
8.31 8.01 7.70 8.47 8.18 7.89 8.57
kW
40.6 37.4 34.4 42.1 39.1 36.4 43.1
TC
22.3 26.0 34.4 25.2 30.2 36.4 28.3
28 SHC
9.56 9.20 8.84 9.74 9.39 9.07 9.85
kW
39.3 36.2 33.4 40.8 37.8 35.3 41.7
TC
21.8 25.5 33.4 24.7 29.6 35.3 27.8
32 SHC
10.21 9.79 9.41 10.40 10.00 9.66 10.52
kW
38.0 35.0 32.3 39.4 36.5 34.2 40.2
TC
21.3 24.9 32.3 24.3 29.0 34.2 27.3
36 SHC
10.85 10.38 9.97 11.05 10.61 10.26 11.18
kW
36.8 33.8 31.3 38.0 35.2 33.1 38.8
TC
20.8 24.4 31.3 23.8 28.5 33.1 26.8
40 SHC
11.42 10.94 10.54 11.62 11.16 10.83 11.74
kW
35.5 32.6 30.2 36.7 33.9 32.0 37.4
TC
20.4 23.8 30.2 23.3 27.9 32.0 26.4
44 SHC
12.12 11.54 11.07 12.35 11.80 11.42 12.49
kW
34.3 31.3 29.1 35.4 32.6 30.8
—
TC
19.9 23.3 29.1 22.8 27.3 30.8
—
48 SHC
12.77 12.13 11.64 13.01 12.41 12.02
—
kW
—
26.1 24.5
—
—
26.0
—
TC
—
20.9 24.5
—
—
26.0
—
52 SHC
—
10.68 10.30
—
—
10.65
—
kW
38AKS014/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2100
2800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
46.1 42.8 39.4 47.6 44.5 41.5 49.1
TC
25.9 30.4 39.4 29.2 34.8 41.5 32.9
20 SHC
8.59 8.29 7.97 8.73 8.44 8.17 8.88
kW
43.3 40.1 37.0 44.6 41.6 39.0 46.0
TC
24.9 29.2 37.0 28.1 33.5 39.0 31.9
28 SHC
9.87 9.51 9.15 10.02 9.68 9.38 10.19
kW
41.8 38.8 35.9 43.0 40.2 37.8 44.4
TC
24.3 28.6 35.9 27.6 32.8 37.8 31.3
32 SHC
10.54 10.13 9.74 10.70 10.32 10.00 10.89
kW
40.4 37.4 34.7 41.5 38.7 36.5 42.8
TC
23.8 28.0 34.7 27.0 32.1 36.5 30.8
36 SHC
11.21 10.75 10.33 11.37 10.95 10.60 11.58
kW
39.0 36.1 33.5 40.0 37.3 35.2 41.3
TC
23.3 27.4 33.5 26.5 31.5 35.2 30.2
40 SHC
11.76 11.30 10.89 11.93 11.50 11.16 12.14
kW
37.6 34.7 32.2 38.5 35.9 33.9 39.8
TC
22.7 26.8 32.2 25.9 30.8 33.9 29.7
44 SHC
12.52 11.96 11.47 12.70 12.19 11.80 12.95
kW
—
33.4 31.0
—
34.5 32.6
—
TC
—
26.2 31.0
—
30.2 32.6
—
48 SHC
—
12.58 12.06
—
12.82 12.41
—
kW
—
—
25.8
—
—
—
—
TC
—
—
25.8
—
—
—
—
52 SHC
—
—
10.62
—
—
—
—
kW
See Legend and Notes on page 43.

40

16
40.1
40.1
8.04
37.9
37.9
9.25
36.8
36.8
9.86
35.6
35.6
10.48
34.5
34.5
11.05
33.3
33.3
11.69
32.2
32.2
12.31
—
—
—

38AKS016/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
1750
2350
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
49.6 46.3 41.8 51.9 48.5 44.1 53.4
TC
25.7 30.0 41.8 28.8 34.6 44.1 31.7
20 SHC
11.84 11.38 10.76 12.16 11.69 11.08 12.36
kW
46.9 43.6 39.6 49.0 45.7 41.8 50.3
TC
24.6 28.8 39.6 27.7 33.2 41.8 30.7
28 SHC
13.35 12.78 12.08 13.71 13.14 12.47 13.95
kW
45.5 42.2 38.4 47.5 44.2 40.6 48.7
TC
24.1 28.1 38.4 27.2 32.6 40.6 30.1
32 SHC
14.10 13.49 12.78 14.47 13.86 13.18 14.71
kW
44.1 40.8 37.3 45.9 42.7 39.4 47.1
TC
23.6 27.5 37.3 26.6 31.9 39.4 29.6
36 SHC
14.81 14.17 13.46 15.18 14.54 13.88 15.41
kW
42.7 39.4 36.0 44.4 41.2 38.1 45.5
TC
23.1 26.9 36.0 26.1 31.2 38.1 29.1
40 SHC
15.52 14.81 14.07 15.90 15.21 14.52 16.15
kW
41.2 38.1 34.9 42.8 39.7 36.9 43.9
TC
22.5 26.3 34.9 25.5 30.5 36.9 28.5
44 SHC
16.23 15.41 14.60 16.65 15.85 15.11 16.91
kW
—
31.3 29.1
—
32.6 30.8
—
TC
—
23.3 29.1
—
27.3 30.8
—
48 SHC
—
12.13 11.64
—
12.41 12.02
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
52 SHC
—
—
—
—
—
—
—
kW

16
43.3
43.3
8.33
40.7
40.7
9.57
39.4
39.4
10.21
38.0
38.0
10.84
36.7
36.7
11.40
35.4
35.4
12.09
34.1
34.1
12.73
—
—
—

38AKS016/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2100
2800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
53.7 50.0 45.7 55.8 52.3 48.4 57.6
TC
28.8 33.6 45.7 32.2 38.4 48.4 35.8
20 SHC
12.40 11.89 11.30 12.69 12.21 11.67 12.94
kW
50.5 47.0 43.1 52.4 49.1 45.5 54.1
TC
27.6 32.2 43.1 31.0 36.9 45.5 34.7
28 SHC
13.99 13.37 12.69 14.31 13.73 13.12 14.61
kW
49.0 45.5 41.7 50.7 47.4 44.1 52.4
TC
32 SHC
27.0 31.6 41.7 30.3 36.1 44.1 34.0
14.75 14.10 13.40 15.07 14.46 13.84 15.39
kW
47.3 43.9 40.4 49.0 45.8 42.6 50.6
TC
26.4 30.9 40.4 29.7 35.4 42.6 33.4
36 SHC
15.46 14.78 14.08 15.78 15.14 14.53 16.10
kW
45.8 42.4 39.0 47.3 44.1 41.2 48.8
TC
25.8 30.2 39.0 29.1 34.6 41.2 32.8
40 SHC
16.19 15.46 14.72 16.52 15.84 15.19 16.87
kW
44.1 40.8 37.6
—
42.4 39.7
—
TC
25.2 29.5 37.6
—
33.8 39.7
—
44 SHC
16.96 16.13 15.31
—
16.54 15.84
—
kW
—
33.4 31.0
—
—
32.6
—
TC
—
26.2 31.0
—
—
32.6
—
48 SHC
—
12.58 12.06
—
—
12.41
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
52 SHC
—
—
—
—
—
—
—
kW

2950
20
42.8
35.1
8.29
40.2
33.8
9.52
38.9
33.2
10.15
37.6
32.6
10.77
36.2
32.0
11.33
34.9
31.3
12.00
33.6
30.7
12.62
—
—
—

3500
20
45.8
38.4
8.56
42.8
36.9
9.82
41.3
36.1
10.48
39.8
35.4
11.12
38.4
34.6
11.67
36.9
33.9
12.39
—
—
—
—
—
—

2950
20
49.9
38.4
11.88
47.0
37.0
13.37
45.5
36.3
14.10
44.0
35.6
14.79
42.5
34.9
15.48
40.9
34.2
16.15
—
—
—
—
—
—

16
45.9
45.9
11.33
43.5
43.5
12.77
42.3
42.3
13.50
41.0
41.0
14.21
39.7
39.7
14.88
38.5
38.5
15.52
32.2
32.2
12.31
—
—
—

3500
20
53.8
42.6
12.42
50.5
40.8
13.98
48.8
40.0
14.72
47.1
39.1
15.41
45.4
38.2
16.12
43.6
37.3
16.86
—
—
—
—
—
—

16
50.3
50.3
11.93
47.4
47.4
13.44
45.9
45.9
14.18
44.4
44.4
14.88
42.9
42.9
15.57
41.4
41.4
16.27
—
—
—
—
—
—

COMBINATION RATINGS — SI (cont)
38AKS016/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2900
3800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
58.5 54.2 50.3 60.3 56.3 53.1 61.5
TC
20 SHC
32.9 40.3 50.3 38.0 46.5 53.1 42.4
13.07 12.48 11.94 13.32 12.77 12.32 13.49
kW
54.9 50.8 47.3 56.5 52.8 49.9 57.6
TC
31.5 38.9 47.3 36.7 44.9 49.9 41.0
28 SHC
14.75 14.03 13.42 15.03 14.38 13.88 15.21
kW
53.1 49.0 45.7 54.6 51.0 48.3 55.6
TC
30.8 38.2 45.7 36.0 44.0 48.3 40.3
32 SHC
15.52 14.77 14.15 15.81 15.13 14.63 15.99
kW
51.2 47.3 44.2 52.7 49.1 46.7 53.6
TC
30.0 37.5 44.2 35.3 43.2 46.7 39.6
36 SHC
16.23 15.45 14.83 16.51 15.81 15.32 16.69
kW
49.5 45.6 42.6 50.8 47.4 45.1 51.7
TC
29.3 36.8 42.6 34.6 42.4 45.1 38.9
40 SHC
17.00 16.15 15.51 17.29 16.54 16.04 17.48
kW
—
43.7 41.0
—
45.4 43.3
—
TC
—
36.0 41.0
—
41.6 43.3
—
44 SHC
—
16.88 16.18
—
17.32 16.78
—
kW
—
—
33.5
—
—
—
—
TC
—
—
33.5
—
—
—
—
48 SHC
—
—
12.60
—
—
—
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
52 SHC
—
—
—
—
—
—
—
kW
38AKS024/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2100
2800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
66.0 61.5 55.2 69.5 65.1 59.0 71.9
TC
33.5 38.7 55.2 37.1 44.2 59.0 40.8
20 SHC
13.80 13.33 12.68 14.16 13.71 13.07 14.42
kW
62.5 58.1 52.3 65.7 61.4 55.8 68.0
TC
32.1 37.2 52.3 35.8 42.5 55.8 39.4
28 SHC
15.69 15.13 14.38 16.09 15.55 14.83 16.39
kW
60.7 56.4 50.7 63.7 59.5 54.2 66.0
TC
31.5 36.4 50.7 35.1 41.7 54.2 38.7
32 SHC
16.60 15.97 15.16 17.03 16.43 15.65 17.36
kW
58.8 54.5 49.2 61.7 57.5 52.5 63.9
TC
30.8 35.6 49.2 34.3 40.8 52.5 38.0
36 SHC
17.49 16.79 15.91 17.96 17.28 16.45 18.32
kW
56.9 52.6 47.4 59.6 55.5 50.6 61.7
TC
30.0 34.7 47.4 33.6 39.8 50.6 37.3
40 SHC
18.43 17.72 16.86 18.88 18.20 17.39 19.24
kW
54.9 50.6 45.7 57.4 53.3 48.8 59.5
TC
29.3 33.9 45.7 32.8 38.8 48.8 36.5
44 SHC
19.28 18.49 17.56 19.75 18.99 18.13 20.16
kW
52.8 48.6 43.9 55.1 51.2 46.9 57.2
TC
28.5 33.0 43.9 31.9 37.8 46.9 35.7
48 SHC
20.20 19.24 18.17 20.73 19.82 18.84 21.20
kW
50.6 46.6 42.1 52.8 48.9 44.9
—
TC
27.7 32.0 42.1 31.1 36.8 44.9
—
52 SHC
21.03 20.06 19.01 21.55 20.63 19.67
—
kW

16
55.2
55.2
12.62
52.0
52.0
14.24
50.3
50.3
15.01
48.6
48.6
15.71
47.0
47.0
16.46
—
—
—
—
—
—
—
—
—

38AKS024/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2900
3800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
73.4 68.3 62.0 76.6 71.2 65.6 78.6
TC
38.8 46.0 62.0 43.9 53.1 65.6 48.4
20 SHC
14.57 14.04 13.39 14.91 14.34 13.76 15.12
kW
69.4 64.3 58.6 72.3 67.1 62.0 74.1
TC
37.2 44.4 58.6 42.3 51.3 62.0 46.8
28 SHC
16.56 15.92 15.19 16.93 16.27 15.62 17.16
kW
67.3 62.3 56.8 70.0 64.9 60.2 71.7
TC
36.4 43.6 56.8 41.5 50.3 60.2 46.0
32 SHC
17.55 16.83 16.04 17.94 17.21 16.52 18.20
kW
65.1 60.2 55.0 67.7 62.7 58.3 69.3
TC
35.5 42.7 55.0 40.7 49.3 58.3 45.1
36 SHC
18.52 17.71 16.86 18.94 18.13 17.40 19.20
kW
62.9 58.0 53.0 65.3 60.5 56.3 66.9
TC
34.7 41.8 53.0 39.8 48.3 56.3 44.3
40 SHC
19.43 18.61 17.79 19.84 19.03 18.33 20.10
kW
60.6 55.7 51.0 62.8 58.1 54.2 64.3
TC
33.7 40.9 51.0 38.9 47.3 54.2 43.3
44 SHC
20.36 19.43 18.56 20.78 19.90 19.16 21.06
kW
58.2 53.3 49.0 60.3 55.7 52.1 61.7
TC
32.8 39.9 49.0 38.0 46.2 52.1 42.4
48 SHC
21.43 20.32 19.32 21.91 20.87 20.03 22.23
kW
—
50.9 46.9
—
53.3 49.9
—
TC
—
39.0 46.9
—
45.1 49.9
—
52 SHC
—
21.11 20.14
—
21.66 20.86
—
kW

16
61.3
61.3
13.31
58.0
58.0
15.12
56.4
56.4
15.97
54.7
54.7
16.81
52.8
52.8
17.75
50.9
50.9
18.54
49.0
49.0
19.33
47.0
47.0
20.17

38AKS024/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
3500
4700
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
79.4 73.2 67.2 82.0 75.8 71.1 83.5
TC
44.0 52.4 67.2 50.1 61.1 71.1 56.0
20 SHC
15.20 14.56 13.9 15.46 14.82 14.33 15.63
kW
75.1 68.3 63.4 77.2 71.2 67.2 78.6
TC
42.4 51.0 63.4 48.4 59.2 67.2 54.3
28 SHC
17.29 16.42 15.80 17.56 16.80 16.28 17.74
kW
72.8 65.7 61.4 74.8 68.9 65.2 76.1
TC
41.5 50.3 61.4 47.6 58.1 65.2 53.4
32 SHC
18.35 17.33 16.71 18.64 17.78 17.24 18.82
kW
70.5 63.1 59.4 72.2 66.4 63.1 73.4
TC
40.7 49.5 59.4 46.7 57.1 63.1 52.5
36 SHC
19.39 18.19 17.48 19.68 18.73 18.18 19.88
kW
68.1 60.5 57.3 69.7 63.9 60.9 70.8
TC
39.8 48.8 57.3 45.8 56.0 60.9 51.7
40 SHC
20.31 19.03 18.50 20.57 19.61 19.10 20.75
kW
65.6 57.7 55.1 67.0 61.3 58.7 68.0
TC
38.9 48.0 55.1 44.9 54.9 58.7 50.7
44 SHC
21.31 19.82 19.32 21.58 20.50 20.00 21.76
kW
—
54.9 52.8
—
58.7 56.4
—
TC
—
47.2 52.8
—
53.7 56.4
—
48 SHC
—
20.68 20.20
—
21.55 21.01
—
kW
—
52.1 50.5
—
56.0 54.0
—
TC
—
46.4 50.5
—
52.6 54.0
—
52 SHC
—
21.37 21.00
—
22.30 21.83
—
kW

4700
20
57.9
52.1
12.98
54.2
50.4
14.62
52.3
49.5
15.37
50.4
48.6
16.06
48.5
47.8
16.80
—
—
—
—
—
—
—
—
—

3500
20
67.1
49.4
13.92
63.3
47.5
15.79
61.4
46.5
16.70
59.4
45.4
17.58
57.3
44.4
18.50
55.1
43.2
19.33
52.9
42.1
20.21
50.6
40.9
21.02

4700
20
73.6
59.3
14.60
69.3
57.3
16.55
67.1
56.3
17.52
64.8
55.2
18.47
62.4
54.2
19.36
60.0
53.0
20.25
57.5
21.9
21.27
—
—
—

16
68.4
68.4
14.05
64.7
64.7
15.97
62.8
62.8
16.91
60.9
60.9
17.83
58.8
58.8
18.76
56.7
56.7
19.63
54.6
54.6
20.60
52.3
52.3
21.43

5900
20
78.4
68.7
15.10
73.7
66.6
17.12
71.3
65.5
18.13
68.8
64.4
19.12
66.3
63.3
20.00
63.6
62.1
20.93
—
—
—
—
—
—

16
74.3
74.3
14.66
70.3
70.3
16.68
68.2
68.2
17.69
66.1
66.1
18.68
63.9
63.9
19.61
61.6
61.6
20.56
59.3
59.3
21.69
—
—
—

See Legend and Notes on page 43.

41

Performance data (cont)
COMBINATION RATINGS — SI (cont)
38AKS028/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
2900
3800
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
86.6 81.7 73.9 90.6 84.8 77.6 93.1
TC
44.0 51.5 73.9 48.9 59.2 77.6 53.4
20 SHC
19.70 19.31 18.70 20.01 19.55 18.99 20.20
kW
81.9 77.1 70.0 85.6 80.0 73.6 87.8
TC
42.2 49.6 70.0 47.1 57.1 73.6 51.6
28 SHC
21.44 20.84 19.95 21.90 21.20 20.39 22.18
kW
79.4 74.6 67.8 82.9 77.5 71.3 85.0
TC
41.2 48.6 67.8 46.1 55.9 71.3 50.6
32 SHC
22.57 21.85 20.84 23.09 22.28 21.36 23.41
kW
77.0 72.2 65.8 80.2 74.9 69.2 82.2
TC
40.2 47.6 65.8 45.2 54.8 69.2 49.6
36 SHC
23.66 22.81 21.67 24.23 23.30 22.28 24.59
kW
74.4 69.7 63.7 77.4 72.4 67.0 79.3
TC
39.2 46.6 63.7 44.2 53.6 67.0 48.6
40 SHC
24.82 23.84 22.58 25.45 24.39 23.27 25.84
kW
71.8 67.1 61.4 74.6 69.7 64.6 76.4
TC
38.2 45.5 61.4 43.2 52.4 64.6 47.6
44 SHC
26.02 25.01 23.79 26.63 25.57 24.49 27.01
kW
69.7 64.3 58.1 72.8 67.2 61.8 74.8
TC
37.3 44.4 58.1 42.5 51.3 61.8 47.0
48 SHC
27.31 25.93 24.73 28.10 26.68 25.30 28.61
kW
—
61.9 56.1
—
64.8 59.7
—
TC
—
43.4 56.1
—
50.2 59.7
—
52 SHC
—
26.99 25.46
—
27.74 26.40
—
kW
38AKS028/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
3500
4700
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
93.2 89.7 80.1 96.9 90.7 83.9 99.0
TC
49.1 57.0 80.1 55.3 67.5 83.9 61.2
20 SHC
20.21 19.94 19.18 20.50 20.02 19.48 20.67
kW
88.2 83.8 75.7 91.4 85.4 79.4 93.2
TC
47.3 55.3 75.7 53.4 65.2 79.4 59.2
28 SHC
22.22 21.68 20.65 22.62 21.87 21.13 22.85
kW
85.5 80.7 73.3 88.5 82.5 77.0 90.2
TC
46.3 54.4 73.3 52.4 64.0 77.0 58.2
32 SHC
23.48 22.76 21.66 23.92 23.03 22.21 24.18
kW
82.8 77.6 71.0 85.5 79.7 74.6 87.1
TC
45.3 53.6 71.0 51.3 62.8 74.6 57.1
36 SHC
24.70 23.77 22.60 25.18 24.14 23.25 25.46
kW
80.0 74.5 68.6 82.4 76.7 72.2 83.9
TC
44.2 52.7 68.6 50.2 61.5 72.2 56.1
40 SHC
26.00 24.83 23.61 26.50 25.31 24.36 26.81
kW
77.3 71.3 66.1 79.4 73.8 69.7 80.8
TC
43.2 51.8 66.1 49.2 60.3 69.7 55.0
44 SHC
27.19 25.91 24.80 27.66 26.45 25.56 27.95
kW
—
68.5 63.3
—
71.7 67.3
—
TC
—
51.0 63.3
—
59.4 67.3
—
48 SHC
—
27.02 25.68
—
27.83 26.71
—
kW
—
65.6 61.0
—
—
65.0
—
TC
—
50.2 61.0
—
—
65.0
—
52 SHC
—
27.96 26.75
—
—
27.81
—
kW
See Legend and Notes on page 43.

42

16
80.5
80.5
19.22
76.4
76.4
20.75
74.1
74.1
21.78
71.9
71.9
22.76
69.6
69.6
23.82
67.2
67.2
25.04
64.7
64.7
26.04
62.5
62.5
27.15

38AKS028/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
99.5 92.5 85.7 102.5 95.8 90.0 104.3
TC
54.0 65.4 85.7
61.7 75.3 90.0
68.7
20 SHC
20.71 20.16 19.62 20.94 20.42 19.96 21.09
kW
93.9 86.8 80.8 96.4 90.0 85.0 98.0
TC
51.9 63.0 80.8 59.6 72.7 85.0 66.6
28 SHC
22.94 22.05 21.30 23.25 22.45 21.82 23.45
kW
91.0 83.8 78.2 93.3 86.9 82.3 94.8
TC
50.8 61.8 78.2 58.5 71.4 82.3 65.5
32 SHC
24.29 23.22 22.38 24.64 23.68 23.00 24.86
kW
87.9 80.8 75.6 90.0 83.8 79.6 91.4
TC
49.6 60.5 75.6 57.3 70.0 79.6 64.4
36 SHC
25.61 24.34 23.42 25.98 24.87 24.14 26.22
kW
84.8 77.7 73.0 86.6 80.6 76.9 87.9
TC
48.4 59.2 73.0 56.1 68.6 76.9 63.2
40 SHC
27.00 25.50 24.52 27.38 26.11 25.34 27.64
kW
81.8 74.6 70.2
—
77.4 74.1
—
TC
47.3 57.9 70.2
—
67.2 74.1
—
44 SHC
28.17 26.62 25.68
—
27.23 26.52
—
kW
—
72.5 67.8
—
—
72.2
—
TC
—
57.1 67.8
—
—
72.2
—
48 SHC
—
28.03 26.82
—
—
27.96
—
kW
—
—
65.3
—
—
—
—
TC
—
—
65.3
—
—
—
—
52 SHC
—
—
27.88
—
—
—
—
kW

16
87.1
87.1
19.74
82.6
82.6
21.52
80.1
80.1
22.68
77.7
77.7
23.79
75.2
75.2
24.98
72.6
72.6
26.20
70.7
70.7
27.56
—
—
—

38AKS034/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
3500
4700
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
100.5 98.5 86.7 104.9 98.6 90.5 107.4
TC
51.9 59.4 86.7
58.1 71.0 90.5
64.0
20 SHC
22.37 22.22 21.34 22.69 22.23 21.63 22.88
kW
95.4 92.3 82.0 99.2 93.0 85.8 101.5
TC
49.9 57.7 82.0 56.1 68.6 85.8
62.0
28 SHC
24.32 23.96 22.78 24.77 24.05 23.22 25.02
kW
92.8 89.1 79.5 96.4 90.2 83.4 98.6
TC
49.0 55.8 79.5 55.2 67.3 83.4 61.0
32 SHC
25.59 25.09 23.80 26.08 25.24 24.32 26.37
kW
90.2 86.1 77.3 93.6 87.5 81.1 95.6
TC
48.0 56.0 77.3 54.2 66.1 81.1 60.0
36 SHC
26.91 25.25 24.85 27.45 26.57 25.46 27.77
kW
87.5 82.9 74.9 90.7 84.6 78.7 92.5
TC
47.0 55.1 74.9 53.1 64.9 78.7 59.0
40 SHC
28.16 27.41 26.10 26.68 27.68 26.72 28.98
kW
84.7 79.6 72.4 87.7 81.6 76.1 89.4
TC
46.0 54.2 72.4 52.1 63.6 76.1 57.9
44 SHC
29.38 28.32 26.80 29.99 28.72 27.59 30.35
kW
82.8 76.3 68.8 86.0 79.0 73.1 88.0
TC
45.3 53.2 68.8 51.5 62.5 73.1 57.5
48 SHC
30.70 29.30 27.66 31.40 29.87 28.60 31.83
kW
80.1 73.1 66.4 83.0 76.0 70.7 84.9
TC
44.3 52.3 66.4 50.5 61.2 70.7 56.4
52 SHC
31.95 30.27 28.65 32.65 30.98 29.69 33.11
kW

4700
20
87.7
65.8
19.78
82.7
63.5
21.54
80.0
62.2
22.66
77.4
61.0
23.74
74.7
59.8
24.87
71.9
58.5
26.04
69.6
21.9
27.30
—
—
—

5900
20
93.5
75.4
20.24
88.0
72.9
22.20
85.1
71.6
23.42
82.2
70.3
24.59
79.2
69.0
25.82
76.2
67.7
26.96
—
—
—
—
—
—

7050
20
98.7
84.4
20.54
92.7
81.7
22.78
89.5
80.3
24.08
86.3
78.9
25.32
83.0
77.4
26.62
79.8
76.0
27.74
—
—
—
—
—
—

16
93.5
93.5
20.24
88.4
88.4
22.25
85.7
85.7
23.51
83.0
83.0
24.73
80.1
80.1
26.02
77.3
77.3
27.20
—
—
—
—
—
—

5900
20
101.6
78.9
22.45
95.9
76.4
24.38
93.0
75.1
25.62
90.2
73.9
26.91
87.3
72.6
28.12
84.2
71.2
29.28
82.0
70.3
30.53
79.0
68.9
31.70

16
93.8
93.8
21.87
89.1
89.1
23.59
86.6
86.6
24.76
84.3
84.3
25.97
81.9
81.9
27.24
79.3
79.3
28.25
76.8
76.8
29.39
74.3
74.3
30.56

COMBINATION RATINGS — SI (cont)
38AKS034/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
107.5 100.9 92.9 111.2 104.4 97.3 113.4
TC
57.1 68.9 92.9
64.7 79.0 97.3
71.7
20 SHC
22.89 22.40 21.81 23.16 22.66 22.13 23.33
kW
101.9 95.0 87.8 105.1 98.4 92.1 107.0
TC
55.0 66.4 87.8
62.6 76.4 92.1
69.6
28 SHC
25.07 24.27 23.44 25.44 24.66 23.94 25.66
kW
99.1 92.0 85.1 102.1 95.3 89.5 104.0
TC
53.9 65.2 85.1
61.5 75.1 89.5
68.6
32 SHC
26.44 25.48 24.56 26.85 25.94 25.14 27.10
kW
96.2 89.0 82.7 98.9 92.3 86.9 100.7
TC
52.8 64.0 82.7 60.4 73.8 86.9
67.5
36 SHC
27.87 26.73 25.71 28.31 27.25 26.39 28.59
kW
93.3 86.0 80.0 95.8 89.2 84.2 97.4
TC
51.7 62.7 80.0 59.3 72.4 84.2 66.4
40 SHC
29.10 27.91 26.94 29.51 28.44 27.63 29.78
kW
90.2 82.8 77.3 92.5 86.0 81.5 94.0
TC
50.5 61.4 77.3 58.2 71.0 81.5 65.3
44 SHC
30.52 28.98 27.82 31.00 29.64 28.70 31.31
kW
89.0 80.3 74.1 91.6 84.0 79.0 93.4
TC
50.0 60.3 74.1 57.9 70.1 79.0 65.0
48 SHC
32.05 30.15 28.82 32.61 30.96 29.88 32.99
kW
—
77.2 71.5
—
80.8 76.3
—
TC
—
59.0 71.5
—
68.7 76.3
—
52 SHC
—
31.25 29.88
—
32.12 31.04
—
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 26.7 C db air entering indoor coil.

7050
20
107.4
88.3
22.88
101.3
85.5
25.00
98.2
84.2
26.32
95.1
82.8
27.70
92.0
81.4
28.89
88.7
79.9
30.20
87.1
79.2
32.64
83.8
77.7
32.85

16
100.9
100.9
22.40
95.7
95.7
24.36
93.0
93.0
25.62
90.4
90.4
26.95
87.7
87.7
28.19
84.9
84.9
29.41
83.0
83.0
30.74
80.2
80.2
31.98

38AKS044/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s
Temp (C)
4250
5650
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
22
20
16
22
20
16
22
125.9 118.7 105.4 132.8 123.7 111.1 136.7
TC
64.2 76.3 105.4 72.2 87.5 111.1 79.4
20 SHC
29.60 29.04 28.01 30.14 29.43 28.45 30.44
kW
121.1 114.0 102.1 127.1 118.6 107.5 130.6
TC
62.4 74.3 102.1 70.3 85.2 107.5 77.4
28 SHC
32.30 31.50 30.16 32.98 32.02 30.77 33.36
kW
118.8 112.0 101.3 124.2 116.3 106.3 127.2
TC
61.5 73.5 101.3 69.2 84.2 106.3 76.2
32 SHC
33.92 32.94 31.41 34.68 33.55 32.13 35.12
kW
115.9 108.8 98.4 120.9 113.0 103.5 123.9
TC
60.3 72.1 98.4
68.1 82.8 103.5 75.2
36 SHC
35.55 34.43 32.81 36.35 35.10 33.61 36.81
kW
112.3 104.9 95.0 117.1 109.1 100.1 119.9
TC
59.0 70.5 95.0
66.8 81.1 100.1 73.8
40 SHC
37.31 36.03 34.35 38.13 36.75 35.22 38.61
kW
109.3 101.6 92.2 113.9 105.8 97.3 116.6
TC
57.8 69.2 92.2
65.7 79.6 97.3
72.7
44 SHC
38.86 37.43 35.68 39.71 38.21 36.63 40.21
kW
106.5 97.9 88.3 111.2 102.4 93.9 114.0
TC
56.8 67.6 88.3
64.7 78.2 93.9
71.9
48 SHC
40.58 38.61 36.43 41.64 39.64 37.69 42.28
kW
103.5 94.7 85.7 107.9 99.2 91.2 110.5
TC
55.6 66.3 85.7
63.6 76.7 91.2
70.7
52 SHC
42.27 40.10 37.87 43.34 41.19 39.22 43.99
kW

7050
20
128.1
97.5
29.77
122.6
95.1
32.47
119.9
93.9
34.08
116.7
92.4
35.68
112.7
90.6
37.38
109.4
89.2
38.88
106.3
87.8
40.53
103.0
86.3
42.13

16
115.8
115.8
28.82
112.0
112.0
31.27
110.4
110.4
32.72
107.7
107.7
34.26
104.3
104.3
35.94
101.5
101.5
37.41
98.4
98.4
38.72
95.7
95.7
40.33

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s
Ldb C = Edb C –

where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

43

Performance data (cont)
COMBINATION RATINGS — ENGLISH
38AK007/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
66.7 61.0 55.9 69.4 63.8 59.4 71.2
TC
34.2 42.9 51.1 38.2 49.3 58.5 41.7
85 SHC
4.98 4.79 4.62 5.08 4.88 4.73 5.14
kW
63.8 58.2 53.2 66.4 60.8 56.8 68.0
TC
33.2 41.7 49.7 37.1 48.1 56.6 40.7
95 SHC
5.33 5.11 2.94 5.43 5.21 5.05 5.49
kW
62.3 56.7 51.9 64.8 59.3 55.5 66.3
TC
32.6 41.1 49.0 36.6 47.5 55.5 40.2
100 SHC
5.49 5.26 5.06 5.60 5.37 5.21 5.66
kW
60.7 55.2 50.5 63.1 57.7 54.2 64.6
TC
32.0 40.5 48.2 36.0 46.9 54.2 39.6
105 SHC
5.65 5.41 5.20 5.76 5.52 5.36 5.83
kW
57.4 52.0 47.6 59.6 54.3 51.5 61.0
TC
30.8 39.3 46.6 34.8 45.5 51.5 38.4
115 SHC
5.96 5.69 5.47 6.08 5.81 5.67 6.15
kW
53.9 48.6 44.8 55.9 50.8 48.7 57.2
TC
29.6 37.9 44.6 33.5 44.1 48.7 37.2
125 SHC
6.25 5.95 5.73 6.37 6.08 5.96 6.45
kW
38AK007/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
74.7 68.6 63.7 77.2 71.3 68.3 78.8
TC
40.5 52.0 62.1 45.6 60.2 68.3 50.4
85 SHC
5.30 5.09 4.93 5.38 5.18 5.08 5.44
kW
71.4 65.4 60.9 73.8 68.0 65.5 75.2
TC
39.3 50.7 60.3 44.4 58.8 65.5 49.2
95 SHC
5.66 5.43 5.26 5.75 5.53 5.43 5.81
kW
69.7 63.8 59.4 72.0 66.3 64.1 73.4
TC
38.7 50.0 59.2 43.8 58.1 64.1 48.6
100 SHC
5.84 5.59 5.41 5.93 5.70 5.61 5.99
kW
67.9 62.1 58.0 70.1 64.5 62.6 71.4
TC
38.1 49.3 58.0 43.2 57.3 62.6 48.0
105 SHC
6.01 5.75 5.58 6.11 5.86 5.78 6.17
kW
64.1 58.4 55.1 66.1 60.8 59.5 67.4
TC
36.8 47.9 55.1 42.0 55.7 59.5 46.7
115 SHC
6.34 6.06 5.89 6.45 6.18 6.11 6.50
kW
60.2 54.7 52.1 62.0 57.0 56.2 63.1
TC
35.4 46.4 52.1 40.6 53.9 56.2 45.4
125 SHC
6.65 6.34 6.19 6.75 6.47 6.42 6.82
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.

44

62
62.5
62.5
4.84
60.0
60.0
5.18
58.7
58.7
5.34
57.4
57.4
5.50
54.5
54.5
5.81
51.5
51.5
6.12

38AK008/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
77.0 71.1 65.5 80.5 74.5 69.2 82.7
TC
38.0 46.8 55.5 41.8 53.1 63.7 45.3
85 SHC
5.78 5.63 5.48 5.88 5.72 5.58 5.93
kW
74.2 68.5 63.0 77.5 71.7 66.6 79.6
TC
36.9 45.7 54.2 40.7 51.9 62.4 44.2
95 SHC
6.28 6.12 5.97 6.38 6.21 6.06 6.43
kW
72.7
67.
61.8 75.9 70.2 65.2 77.9
TC
36.3 45.1 53.6 40.2 51.3 61.6 43.7
100 SHC
6.54 6.37 6.22 6.64 6.46 6.32 6.69
kW
71.2 65.6 60.4 74.2 68.6 63.8 76.2
TC
35.7 44.4 52.9 39.6 50.7 60.8 43.1
105 SHC
6.80 6.63 6.48 6.90 6.72 6.58 6.96
kW
67.8 62.5 57.6 70.6 65.2 60.8 72.4
TC
34.4 43.1 51.5 38.2 49.3 59.1 41.7
115 SHC
7.33 7.16 7.02 7.43 7.25 7.12 7.49
kW
64.3 59.2 54.6 66.8 61.7 57.7 68.4
TC
33.1 41.8 50.0 36.9 47.9 57.1 40.4
125 SHC
7.89 7.72 7.57 7.98 7.81 7.67 8.04
kW

62
71.7
71.7
5.20
68.8
68.8
5.56
67.3
67.3
5.74
65.7
65.7
5.91
62.4
62.4
6.25
58.9
58.9
6.58

38AK008/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
83.8 77.5 71.9 86.8 80.6 75.8 88.8
TC
43.0 54.3 65.1 47.8 62.2 74.5 52.4
85 SHC
5.92 5.76 5.61 6.00 5.84 5.71 6.06
kW
80.7 74.6 69.1 83.6 77.5 73.0 85.4
TC
41.9 53.1 63.7 46.7 61.0 72.5 51.2
95 SHC
6.43 6.25 6.10 6.51 6.33 6.21 6.57
kW
79.0 73.0 67.7 81.8 75.8 71.5 83.6
TC
41.2 52.4 63.0 46.1 60.3 71.4 50.6
100 SHC
6.68 6.51 6.35 6.77 6.59 6.46 6.82
kW
77.2 71.3 66.2 79.9 74.0 70.1 81.6
TC
40.6 51.7 62.2 45.5 59.6 70.0 50.0
105 SHC
6.95 6.76 6.61 7.03 6.85 6.73 7.09
kW
73.5 67.8 63.1 75.9 70.3 67.0 77.5
TC
39.3 50.3 60.5 44.1 58.1 67.0 48.6
115 SHC
7.48 7.30 7.15 7.57 7.38 7.27 7.62
kW
69.4 64.1 59.8 71.6 66.4 63.8 73.0
TC
37.8 48.8 58.5 42.6 56.5 63.8 47.1
125 SHC
8.03 7.84 7.70 8.12 7.93 7.84 8.17
kW

3000
67
65.6
55.0
4.95
62.6
53.8
5.28
61.0
53.1
5.43
59.4
52.4
5.59
56.0
51.0
5.89
52.4
49.2
6.17

3750
67
73.2
67.2
5.25
69.9
65.6
5.60
68.2
64.7
5.77
66.4
63.8
5.94
62.7
61.6
6.26
59.0
58.9
6.58

3000
67
76.7
58.9
5.77
73.8
57.7
6.27
72.2
57.1
6.52
70.5
56.4
6.78
67.0
55.0
7.31
63.3
53.4
7.86

62
71.9
70.3
5.65
69.3
68.6
6.14
67.9
67.5
6.39
66.5
66.4
6.66
63.6
63.6
7.20
60.6
60.6
7.77

3750
67
82.7
69.4
5.89
79.5
68.1
6.39
77.7
67.3
6.65
75.9
66.6
6.91
72.0
64.8
7.43
68.0
63.0
7.98

62
79.2
79.2
5.80
76.6
76.6
6.31
75.1
75.1
6.57
73.6
73.6
6.83
70.3
70.3
7.38
66.8
66.8
7.94

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm

Ldb F = Edb F –

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — ENGLISH (cont)
38AK008/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
93.2 86.6 81.6 95.7 89.4 86.8 97.3
TC
51.8 67.4 80.7 58.5 77.9 86.8 64.6
85 SHC
6.72 6.54 6.40 6.79 6.62 6.54 6.84
kW
89.7 83.3 78.7 92.1 86.0 83.8 93.5
TC
50.6 66.1 78.5 57.2 76.4 83.8 63.3
95 SHC
7.29 7.09 6.96 7.36 7.18 7.11 7.40
kW
87.8 81.4 77.2 90.1 84.1 82.2 91.5
TC
49.9 65.4 77.1 56.5 75.6 82.2 62.7
100 SHC
7.58 7.38 7.24 7.65 7.46 7.40 7.70
kW
85.8 79.6 75.6 88.0 82.2 80.5 89.3
TC
49.2 64.6 75.6 55.9 74.7 80.5 62.0
105 SHC
7.87 7.67 7.54 7.95 7.75 7.70 7.99
kW
81.5 75.5 72.3 83.5 78.0 76.9 84.7
TC
47.7 63.0 72.3 54.4 72.8 76.9 60.5
115 SHC
8.46 8.25 8.15 8.54 8.35 8.31 8.58
kW
76.9 71.3 68.8 78.6 73.7 73.0 79.8
TC
46.2 61.3 68.8 52.8 70.6 73.0 58.9
125 SHC
9.08 8.87 8.78 9.15 8.96 8.94 9.19
kW
38AKS008/40RM007 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
82.6 76.3 69.4 86.5 80.3 73.4 88.8
TC
41.5 50.9 65.1 45.9 59.7 73.4 51.6
85 SHC
5.55 5.40 5.23 5.64 5.49 5.33 5.69
kW
79.1 73.1 66.6 82.7 76.7 70.4 84.8
TC
40.0 49.6 62.8 44.5 58.3 70.4 50.3
95 SHC
6.07 5.88 5.67 6.18 5.99 5.79 6.25
kW
77.2 71.4 65.1 80.7 74.9 68.9 82.7
TC
39.2 49.0 61.6 43.8 57.5 68.8 49.6
100 SHC
6.32 6.11 5.88 6.45 6.24 6.02 6.52
kW
75.4 69.6 63.5 78.7 73.0 67.3 80.6
TC
38.5 48.3 60.3 43.0 56.8 67.2 48.9
105 SHC
6.57 6.35 6.11 6.69 6.47 6.25 6.77
kW
71.6 66.1 60.3 74.7 69.2 64.0 76.4
TC
36.8 47.0 57.7 41.5 55.3 64.0 47.5
115 SHC
7.05 6.79 6.51 7.20 6.94 6.68 7.29
kW
67.6 62.4 57.1 70.4 65.2 60.6
—
TC
35.1 45.5 55.0 39.9 53.7 60.6
—
125 SHC
7.57 7.27 6.95 7.74 7.43 7.16
—
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.

62
90.4
90.4
6.64
87.3
87.3
7.21
85.6
85.6
7.51
83.8
83.8
7.81
79.9
79.9
8.41
75.8
75.8
9.04

38AKS008/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
89.3 82.5 75.7 92.2 86.3 80.2 94.4
TC
46.0 58.8 73.1 53.7 67.9 80.2 58.7
85 SHC
5.70 5.54 5.38 5.77 5.63 5.49 5.83
kW
85.3 78.8 72.4 87.8 82.3 76.7 89.8
TC
44.3 57.2 70.2 52.3 66.2 76.7 57.1
95 SHC
6.26 6.06 5.86 6.34 6.17 5.99 6.41
kW
83.2 76.9 70.7 85.6 80.2 74.9 87.5
TC
43.5 56.4 68.7 51.5 65.3 74.9 56.3
100 SHC
6.54 6.31 6.08 6.63 6.53 6.24 6.70
kW
81.2 75.0 68.9 83.4 78.2 73.1 85.3
TC
42.7 55.6 67.2 50.8 64.4 73.1 55.5
105 SHC
6.79 6.55 6.32 6.87 6.67 6.48 6.95
kW
77.0 71.0 65.3 78.9 73.9 69.4 80.6
TC
40.9 53.8 64.1 49.3 62.6 69.4 53.9
115 SHC
7.31 7.03 6.75 7.41 7.17 6.95 7.49
kW
72.5 66.9 61.6 74.1 69.5 65.5 75.6
TC
39.1 52.0 60.9 47.7 60.8 65.5 52.1
125 SHC
7.86 7.53 7.22 7.96 7.68 7.45 8.05
kW

67
89.0
76.6
5.70
84.8
74.9
6.26
82.7
74.1
6.52
80.6
73.2
6.77
76.2
71.5
7.28
71.6
69.6
7.81

62
83.6
83.6
5.57
80.0
80.0
6.10
78.1
78.1
6.36
76.3
76.3
6.60
72.5
72.5
7.10
68.5
68.5
7.62

62
76.5
76.5
5.40
73.4
73.4
5.89
71.8
71.8
6.13
70.2
70.2
6.37
66.9
66.9
6.82
63.4
63.5
7.32

38AKS008/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
67
97.3 90.2 83.8
—
93.6 88.7 101.6 95.5
TC
52.8 70.9 82.8
—
81.4 88.7
69.8 94.1
85 SHC
5.89 5.73 5.57
—
5.81 5.69 6.00 5.85
kW
92.7 85.9 79.9
—
89.0 84.7 96.5 90.7
TC
50.9 69.1 79.6
—
79.3 84.7 68.0 92.2
95 SHC
6.50 6.28 6.09
—
6.38 6.24 6.62 6.43
kW
—
83.7 77.9
—
86.7 82.6 93.9 88.3
TC
—
68.2 77.9
—
78.2 82.6 67.1 91.2
100 SHC
—
6.56 6.35
—
6.67 6.52 6.93 6.72
kW
—
81.6 75.9
—
84.5 80.5 91.5 85.9
TC
—
67.2 76.3
—
77.2 80.5 66.3 90.2
105 SHC
—
6.80 6.59
—
6.91 6.76 7.18 6.97
kW
—
77.1 71.8
—
79.3 76.3
—
—
TC
—
65.3 72.8
—
75.0 76.3
—
—
115 SHC
—
7.32 7.06
—
7.45 7.28
—
—
kW
—
72.4 67.5
—
—
—
—
—
TC
—
63.3 69.3
—
—
—
—
—
125 SHC
—
7.86 7.57
—
—
—
—
—
kW

62
93.0
93.0
5.79
88.9
88.9
6.38
86.7
86.7
6.67
84.7
84.7
6.92
—
—
—
—
—
—

5000
67
91.5
86.4
6.67
88.0
84.6
7.24
86.2
83.6
7.53
84.2
82.3
7.82
80.1
79.5
8.42
75.8
75.8
9.04

3000
67
83.1
66.2
5.56
79.4
64.8
5.08
77.4
64.0
6.33
75.5
63.3
6.57
71.6
61.8
7.05
67.4
60.3
7.56

3750

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm

Ldb F = Edb F –

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

45

Performance data (cont)
COMBINATION RATINGS — ENGLISH (cont)
38AKS009/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
3750
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
67
102.7 94.9 86.7 107.0 99.9 91.7 109.9 103.2
TC
51.5 64.2 82.5
58.7 73.6 91.6
64.1 82.3
85 SHC
7.62 7.33 7.03 7.77 7.51 7.21 7.88 7.63
kW
98.2 90.5 82.5 102.2 95.3 87.5 104.9 98.5
TC
49.7 62.3 78.9
57.0 71.6 87.5
62.3 80.4
95 SHC
8.24 7.92 7.58 8.41 8.12 7.79 8.53 8.25
kW
95.7 88.3 80.7 99.3 92.7 85.5 101.9 95.8
TC
48.6 61.4 77.3 56.1 70.6 85.5
61.3 79.3
100 SHC
8.56 8.20 7.84 8.73 8.42 8.07 8.85 8.56
kW
93.2 96.0 78.7 96.6 90.2 83.4 99.0 93.2
TC
47.6 60.4 75.6 55.2 69.5 83.4 60.3 78.3
105 SHC
8.86 8.49 8.11 9.03 8.71 8.35 9.16 8.86
kW
88.2 81.3 74.5 91.2 85.2 79.0 93.4 87.9
TC
45.6 58.3 72.0 53.4 67.4 79.0 58.3 76.2
115 SHC
9.46 9.04 8.63 9.63 9.27 8.90 9.77 9.44
kW
—
76.5 70.1
—
80.0 74.5
—
82.6
TC
—
56.2 68.2
—
65.2 74.5
—
74.0
125 SHC
—
9.63 9.17
—
9.87 9.48
—
10.05
kW
38AKS009/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
113.0 104.8 96.9 116.9 109.2 102.4 119.1
TC
59.2 77.2 93.7
67.1 88.5 102.4 75.8
85 SHC
7.99 7.69 7.40 8.14 7.85 7.60 8.22
kW
108.1 99.9 92.3 111.8 104.2 97.8
—
TC
57.2 75.1 89.9
65.1 86.2 97.8
—
95 SHC
8.66 8.32 7.99 8.81 8.49 8.22
—
kW
105.0 97.2 89.9 108.4 101.2 95.2
—
TC
55.9 73.9 87.9
63.8 84.8 95.2
—
100 SHC
9.00 8.63 8.28 9.16 8.82 8.54
—
kW
102.1 94.5 87.5 105.2 98.3 92.7
—
TC
54.7 72.8 85.9
62.6 83.5 92.7
—
105 SHC
9.32 8.93 8.57 9.48 9.12 8.83
—
kW
96.4 89.1 82.6
—
92.6 87.7
—
TC
52.4 70.5 81.9
—
80.9 87.7
—
115 SHC
9.95 9.51 9.12
—
9.72 9.42
—
kW
—
83.6 77.6
—
86.8 82.5
—
TC
—
68.1 77.7
—
78.2 82.5
—
125 SHC
—
10.13 9.70
—
10.35 10.05
—
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.

46

62
95.4
95.4
7.35
91.2
91.2
7.95
89.1
89.1
8.24
86.9
86.9
8.54
82.5
82.5
9.11
77.8
77.8
9.72

38AK012/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
105 96.9 89.7 110
102 94.9 112
TC
51.5 63.5 75.1 56.9 72.4 87.3 62.2
85 SHC
7.12 6.88 6.67 7.27 7.02 6.81 7.36
kW
101 93.5 86.6 106 98.0 91.6 108
TC
50.1 61.9 73.6 55.6 70.9 85.6 60.8
95 SHC
7.68 7.43 7.22 7.82 7.57 7.37 7.92
kW
99.3 91.8 85.1 104 96.1 89.8 106
TC
49.3 61.2 72.8 54.8 70.2 84.7 60.0
100 SHC
7.97 7.73 7.52 8.11 7.86 7.55 8.20
kW
97.4 90.0 83.3 101 94.1 88.0 104
TC
48.6 60.4 72.0 54.0 69.3 83.8 59.3
105 SHC
8.27 8.03 7.83 8.41 8.16 7.97 8.50
kW
93.2 86.1 79.7 96.9 89.8 84.2 99.2
TC
47.0 58.7 70.2 52.4 67.6 81.7 57.6
115 SHC
8.89 8.66 8.47 9.02 8.78 8.60 9.10
kW
88.6 82.0 76.0 92.0 85.3 80.3 94.1
TC
45.3 57.0 68.4 50.7 65.8 79.3 55.9
125 SHC
9.54 9.32 9.15 9.66 9.44 9.27 9.74
kW

62
106.9
106.9
7.77
102.4
102.4
8.42
99.8
99.7
8.75
97.2
97.2
9.07
92.1
92.1
9.69
86.8
86.8
10.36

38AK012/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
112
104 96.9 116
108
102
118
TC
58.2 74.0 89.1 65.2 85.4 102 72.0
85 SHC
8.50 8.22 7.98 8.64 8.36 8.16 8.73
kW
108
100 93.5 111
104 98.9 114
TC
56.7 72.4 87.4 63.8 83.8 98.9 70.6
95 SHC
9.15 8.86 8.62 9.29 9.00 8.82 9.37
kW
106 98.1 91.8 109
102 97.2 111
TC
56.0 71.6 86.5 63.0 83.0 97.2 69.8
100 SHC
9.49 9.20 8.96 9.63 9.34 9.16 9.71
kW
104 96.1 89.9 107 99.5 95.4 109
TC
55.2 70.8 85.5 62.3 82.1 95.4 69.0
105 SHC
9.84 9.55 9.32 9.97 9.68 9.51 10.0
kW
99.0 91.8 86.0 102 95.0 91.6 104
TC
53.5 69.1 83.4 60.6 80.3 91.6 67.3
115 SHC
10.6 10.3 10.1 10.7 10.4 10.3 10.8
kW
94.0 87.2 82.1 96.6 90.2 87.5 98.3
TC
51.8 67.3 81.0 58.8 78.3 87.5 65.5
125 SHC
11.3 11.0 10.9 11.4 11.2 11.0 11.5
kW

5000
67
111.8
100.8
7.95
106.7
98.7
8.60
103.4
97.4
8.93
100.4
96.1
9.23
94.5
93.7
9.83
88.4
91.3
10.47

3750
67
105
80.9
7.12
101
79.4
7.67
98.9
78.6
7.95
96.8
77.7
8.25
92.3
75.9
8.86
87.7
74.1
9.51

62
98.8
97.3
6.93
95.5
95.0
7.49
93.8
93.7
7.78
92.0
92.0
8.09
88.3
88.3
8.73
84.5
84.5
9.41

5000
67
110
95.8
8.45
106
94.1
9.09
104
93.2
9.43
102
92.2
9.77
97.3
90.1
10.5
92.3
87.7
11.2

62
107
107
8.33
104
104
8.99
102
102
9.34
99.9
99.9
9.69
95.8
95.8
10.4
91.4
91.4
11.2

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm

Ldb F = Edb F –

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — ENGLISH (cont)
38AK012/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
117
109
102
120
112
108
122
TC
63.9 82.7 99.4 71.8 95.3 108 79.3
85 SHC
7.18 6.94 7.18 7.28 7.04 6.92 7.34
kW
113
105 98.6 116
108
105
118
TC
62.5 81.2 97.1 70.4 93.6 105 77.8
95 SHC
7.72 7.48 7.30 7.82 7.58 7.47 7.88
kW
111
103 96.8 114
106
103
116
TC
61.6 80.3 95.9 69.6 92.7 103 77.0
100 SHC
8.01 7.76 7.59 8.10 7.86 7.77 8.16
kW
108
101 94.9 111
104
101
113
TC
60.8 79.4 94.5 68.8 91.7 101 76.2
105 SHC
8.30 8.05 7.88 8.39 8.15 8.06 8.45
kW
103 96.0 91.1 106 98.9 96.8 108
TC
59.1 77.6 91.1 67.0 89.6 96.8 74.4
115 SHC
8.90 8.66 8.52 8.99 8.76 8.69 9.04
kW
98.2 91.3 87.3 101 94.1 92.6 102
TC
57.3 75.7 87.3 65.3 87.3 92.6 72.6
125 SHC
9.53 9.31 9.20 9.623 9.40 9.35 9.66
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

62
94.4
94.4
7.33
90.4
90.4
7.94
88.2
88.2
8.24
86.1
86.1
8.53
81.7
81.7
9.11
77.2
77.2
9.67

38AKS013/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
3750
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
67
62
103.5 95.9 88.0 107.7 100.9 92.8 110.5 104.1 96.4
TC
51.9 64.7 83.6
58.9 74.0 92.8
64.3 82.6 96.4
85 SHC
7.82 7.56 7.30 7.96 7.73 7.46 8.05 7.84 7.58
kW
99.0 91.5 83.7 102.8 96.1 88.5 105.5 99.2 92.2
TC
50.0 62.8 79.9
57.3 72.0 88.5
62.5 80.7 92.2
95 SHC
8.50 8.25 7.99 8.63 8.40 8.15 8.72 8.51 8.27
kW
97.0 89.5 81.9 100.7 94.1 86.7 103.4 97.2 90.3
TC
49.2 61.9 78.4
56.6 71.1 86.7
61.8 79.9 90.3
100 SHC
8.81 8.48 8.14 8.98 8.68 8.35 9.09 8.82 8.51
kW
94.8 87.4 79.9 98.4 91.8 84.7 101.0 94.9 88.3
TC
48.3 61.0 76.6 55.8 70.2 84.7
60.9 78.9 88.3
105 SHC
9.13 8.77 8.41 9.30 8.98 8.64 9.42 9.13 8.81
kW
90.5 83.1 75.8 93.7 87.3 80.6 96.2 90.3 84.2
TC
46.5 59.1 73.1 54.2 68.3 80.6 59.3 77.1 84.2
115 SHC
9.78 9.37 8.97 9.96 9.61 9.23 10.10 9.77 9.44
kW
85.6 78.9 72.3 88.3 82.5 76.7 90.4 85.2 80.1
TC
44.5 57.3 70.1 52.4 66.3 76.7 57.3 75.1 80.1
125 SHC
10.47 9.97 9.47 10.67 10.24 9.81 10.83 10.44 10.06
kW

6250
67
115
106
7.11
111
104
7.66
108
103
7.94
106
102
8.23
101
98.9
8.83
96.4
95.6
9.47

38AKS012/40RM008 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
2250
3000
3750
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
67
101.9 93.8 85.5 106.3 99.0 90.6 109.3 102.4
TC
51.2 63.8 81.4
58.4 73.2 90.6
63.8 81.9
85 SHC
7.59 7.31 7.03 7.73 7.49 7.20 7.84 7.60
kW
97.1 89.6 81.9 100.9 94.2 86.7 103.5 97.3
TC
49.2 61.9 78.4
56.6 71.2 86.7
61.8 79.9
95 SHC
8.23 7.91 7.58 8.39 8.11 7.79 8.51 8.24
kW
94.7 87.4 79.9 98.2 91.7 84.6
—
94.8
TC
48.2 61.0 76.6 55.7 70.2 84.6
—
78.9
100 SHC
8.54 8.20 7.84 8.71 8.40 8.07
—
8.54
kW
92.3 85.1 77.8 95.6 89.3 82.5
—
92.2
TC
47.2 60.0 74.9 54.9 69.1 82.5
—
77.9
105 SHC
8.86 8.48 8.11 9.03 8.70 8.35
—
8.85
kW
87.4 80.5 73.7 90.3 84.3 78.3
—
87.1
TC
45.2 58.0 71.3 53.1 67.0 78.3
—
75.8
115 SHC
9.45 9.04 8.64 9.62 9.26 8.91
—
9.43
kW
—
75.9 69.4
—
79.3 73.8
—
—
TC
—
55.9 67.7
—
64.9 73.8
—
—
125 SHC
—
9.57 9.13
—
9.81 9.43
—
—
kW
38AKS012/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
112.5 104.0 95.8 116.5 108.5 101.5 118.8
TC
59.0 76.8 92.9
67.0 88.2 101.5 75.7
85 SHC
7.95 7.66 7.38 8.08 7.81 7.57 8.16
kW
106.6 98.7 91.3 110.1 102.8 96.7
—
TC
56.6 74.6 89.1
64.5 85.6 96.7
—
95 SHC
8.64 8.30 7.98 8.79 8.47 8.21
—
kW
103.8 96.1 89.4 107.1 100.0 94.2
—
TC
55.5 73.5 87.1
63.4 84.3 94.2
—
100 SHC
8.97 8.61 8.27 9.13 8.79 8.52
—
kW
101.1 93.5 86.6
—
97.2 91.8
—
TC
54.3 72.4 85.1
—
83.0 91.8
—
105 SHC
9.31 8.92 8.56
—
9.11 8.83
—
kW
95.5 88.3 81.8
—
91.7 86.8
—
TC
52.1 70.1 81.2
—
80.5 86.8
—
115 SHC
9.92 9.50 9.11
—
9.70 9.41
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
125 SHC
—
—
—
—
—
—
—
kW

62
113
113
7.05
109
109
7.61
107
107
8.90
105
105
8.20
101
101
8.81
96.2
96.2
9.47

38AKS012/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
118.3 108.5 101.8 121.8 113.1 108.0
—
TC
66.1 85.6 100.6 75.6 101.3 108.0
—
85 SHC
8.14 7.81 7.58 8.26 7.97 7.79
—
kW
111.8 102.7 96.7
—
106.8 102.6
—
TC
63.6 82.9 96.3
—
98.6 102.6
—
95 SHC
8.86 8.47 8.21
—
8.64 8.47
—
kW
108.8 99.9 94.2
—
103.8 100.0
—
TC
62.5 81.6 94.2
—
97.4 100.0
—
100 SHC
9.21 8.79 8.52
—
8.97 8.79
—
kW
105.8 97.0 91.6
—
100.9 97.3
—
TC
61.3 80.3 92.0
—
96.1 97.3
—
105 SHC
9.55 9.10 8.82
—
9.30 9.12
—
kW
—
91.4 86.6
—
95.0 92.1
—
TC
—
77.7 87.7
—
93.6 92.1
—
115 SHC
—
9.68 9.40
—
9.89 9.72
—
kW
—
—
—
—
89.0 86.7
—
TC
—
—
—
—
91.0 86.7
—
125 SHC
—
—
—
—
10.49 10.32
—
kW

5000
67
111.2
100.5
7.90
105.1
98.1
8.57
102.2
96.9
8.90
99.3
95.7
9.22
93.6
93.3
9.81
—
—
—

62
106.2
106.2
7.73
101.2
101.2
8.41
98.7
98.7
8.73
96.2
96.2
9.06
91.3
91.3
9.67
—
—
—

6250
67
115.9
113.7
8.06
109.3
110.6
8.75
106.3
109.2
9.09
103.2
107.8
9.42
97.2
105.0
10.02
—
—
—

62
113.0
113.0
7.96
107.3
107.3
8.67
104.6
104.6
9.01
101.9
101.9
9.35
96.4
96.4
9.98
—
—
—

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F –
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

47

Performance data (cont)
COMBINATION RATINGS — ENGLISH (cont)
38AKS013/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
113.5 105.6 97.9 117.3 109.9 103.2 119.4
TC
59.4 77.5 94.6
67.3 88.8 103.2 75.9
85 SHC
8.15 7.89 7.63 8.28 8.03 7.81 8.35
kW
108.5 100.7 93.2 112.1 104.8 98.6 114.1
TC
57.4 75.4 90.7
65.3 86.5 98.6
74.1
95 SHC
8.82 8.56 8.31 8.94 8.69 8.49 9.00
kW
106.4 98.6 91.2 109.8 102.6 96.6 111.8
TC
56.5 74.5 89.0
64.4 85.5 96.6
73.3
100 SHC
9.23 8.88 8.56 9.38 9.06 8.79 9.47
kW
104.0 96.2 89.0 107.4 100.2 94.3 109.3
TC
55.6 73.5 87.2
63.4 84.4 94.3
72.4
105 SHC
9.57 9.19 8.85 9.73 9.38 9.10 9.82
kW
99.3 91.6 84.6 102.4 95.3 89.9 104.2
TC
53.6 71.5 83.5
61.5 82.2 89.9
70.6
115 SHC
10.27 9.84 9.45 10.45 10.05 9.75 10.54
kW
93.3 86.3 80.1 95.9 89.6 85.0 97.4
TC
51.2 69.3 79.7 59.0 79.5 85.0 68.3
125 SHC
11.05 10.52 10.06 11.24 10.77 10.42 11.35
kW
38AKS013/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
118.9 109.9 103.5 122.2 114.1 109.3 124.6
TC
66.4 86.3 102.1 75.8 101.8 109.3 85.8
85 SHC
8.33 8.03 7.82 8.44 8.17 8.01 8.52
kW
113.7 104.7 98.7 116.8 108.8 104.5 119.1
TC
64.4 83.9 98.0
73.8 99.5 104.5 83.9
95 SHC
8.99 8.69 8.49 9.09 8.83 8.68 9.17
kW
111.5 102.5 96.6 114.5 106.6 102.4 116.8
TC
63.5 82.8 96.2
73.0 98.5 102.4 83.1
100 SHC
9.46 9.05 8.79 9.59 9.24 9.05 9.69
kW
109.0 100.0 94.3 111.9 104.0 100.1 114.2
TC
62.6 81.7 94.3
72.0 97.4 100.1 82.2
105 SHC
9.81 9.38 9.10 9.95 9.57 9.38 10.06
kW
104.1 95.1 89.7 106.8 99.0 95.5 109.0
TC
60.6 79.4 89.7
70.1 95.3 95.5
80.4
115 SHC
10.54 10.04 9.74 10.69 10.26 10.06 10.81
kW
97.4 89.2 84.7 99.7 92.7 90.0 101.6
TC
58.1 76.7 84.6 67.6 92.6 90.0
77.9
125 SHC
11.36 10.74 10.40 11.53 11.00 10.80 11.67
kW
38AKS014/40RM012 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
129.3 119.5 109.5 134.9 125.4 115.9 138.2
TC
65.9 83.5 104.2 74.0 95.9 115.9 82.4
85 SHC
9.51 9.18 8.85 9.70 9.38 9.06 9.81
kW
123.5 114.3 105.1 128.4 119.6 111.1 131.3
TC
63.5 81.3 100.6 71.5 93.3 111.1 80.0
95 SHC
10.42 10.00 9.58 10.65 10.25 9.86 10.78
kW
120.8 111.6 102.6 125.6 116.9 108.6 128.4
TC
62.4 80.1 98.5 70.5 92.0 108.6 79.0
100 SHC
10.78 10.37 9.95 11.00 10.60 10.23 11.13
kW
118.1 109.1 100.4 122.6 114.1 106.3 125.2
TC
61.3 79.1 96.7 69.3 90.8 106.3 77.9
105 SHC
11.19 10.74 10.30 11.41 10.99 10.60 11.55
kW
112.5 104.0 95.8 116.5 108.5 101.5 118.8
TC
59.0 76.8 92.9
67.0 88.2 101.5 75.7
115 SHC
12.03 11.52 11.03 12.27 11.79 11.37 12.41
kW
—
98.6 91.2
—
102.6 96.6
—
TC
—
74.5 89.0
—
85.5 96.6
—
125 SHC
—
12.37 11.80
—
12.68 12.21
—
kW
—
Edb
Ewb
kW
SHC
TC

48

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

62
107.6
107.6
7.95
103.0
103.0
8.63
101.1
101.1
8.99
98.9
98.9
9.32
94.5
94.5
10.01
89.3
89.3
10.75

38AKS014/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
136.9 125.9 116.7 141.7 131.4 123.8 145.1
TC
73.3 93.6 113.3 83.0 109.2 123.8 92.8
85 SHC
9.76 9.40 9.09 9.92 9.58 9.33 10.04
kW
130.3 119.9 111.7 134.5 125.0 118.4 137.6
TC
70.7 90.0 109.1 80.3 106.4 118.4 90.2
95 SHC
10.73 10.26 9.89 10.92 10.49 10.19 11.06
kW
127.5 117.1 109.2 131.6 122.1 115.8 134.6
TC
69.7 89.6 106.9 79.3 105.2 115.8 89.2
100 SHC
11.09 10.61 10.25 11.27 10.84 10.56 11.41
kW
124.5 114.3 106.8 128.4 119.2 113.3 131.3
TC
68.5 88.3 104.8 78.1 103.9 113.3 88.1
105 SHC
11.51 11.00 10.62 11.70 11.24 10.95 11.85
kW
118.3 108.5 101.8 121.8 113.1 108.0 124.4
TC
66.1 85.6 100.6 75.6 101.3 108.0 85.7
115 SHC
12.38 11.79 11.39 12.59 12.06 11.76 12.74
kW
—
102.5 96.6
—
106.6 102.4
—
TC
—
82.8 96.2
—
98.5 102.4
—
125 SHC
—
12.67 12.21
—
12.99 12.67
—
kW

62
114.0
114.0
8.17
109.1
109.1
8.84
107.1
107.1
9.26
104.8
104.8
9.60
100.2
100.2
10.32
94.3
94.3
11.12

38AKS014/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
145.0 135.2 125.7 148.7 140.7 132.9 152.5
TC
82.7 105.8 124.6 91.2 120.8 132.9 102.9
85 SHC
10.03 9.71 9.39 10.16 9.89 9.63 10.28
kW
137.4 128.4 119.8 140.6 133.4 126.4 144.0
TC
80.0 102.8 119.4 88.1 117.3 126.4 99.9
95 SHC
11.06 10.65 10.26 11.20 10.87 10.56 11.36
kW
134.4 125.5 117.1 137.5 130.4 123.6 140.9
TC
79.0 101.5 116.9 86.9 115.8 123.6 98.7
100 SHC
11.40 11.00 10.61 11.54 11.22 10.91 11.69
kW
131.0 122.5 114.3 133.9 127.1 120.6 137.1
TC
77.8 100.1 114.3 85.6 114.3 120.6 97.4
105 SHC
11.83 11.41 11.00 11.98 11.64 11.31 12.14
kW
124.0 116.2 108.6 126.5 120.4 114.5
—
TC
75.3 97.3 108.6 82.8 111.0 114.5
—
115 SHC
12.72 12.25 11.80 12.87 12.50 12.15
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
125 SHC
—
—
—
—
—
—
—
kW

5000
67
112.4
101.0
8.11
107.2
98.9
8.77
104.9
98.0
9.16
102.4
97.0
9.49
97.4
94.9
10.17
91.3
92.4
10.90

6250
67
116.8
114.1
8.26
111.4
111.6
8.91
109.1
110.5
9.35
106.5
109.3
9.69
101.4
106.9
10.39
94.8
103.8
11.16

5000
67
129.1
107.8
9.50
122.9
105.3
10.40
120.1
104.1
10.75
117.2
103.0
11.14
111.2
100.5
11.95
104.9
98.0
12.86

62
120.8
120.8
9.23
115.9
115.9
10.08
113.5
113.5
10.45
111.1
111.1
10.84
106.2
106.2
11.65
101.1
101.1
12.56

6250
67
135.1
122.6
9.70
128.3
119.5
10.64
125.4
118.1
10.99
122.3
116.7
11.40
115.9
113.7
12.24
—
—
—

62
129.4
129.4
9.51
123.7
123.7
10.43
121.1
121.1
10.80
118.5
118.5
11.21
113.0
113.0
12.06
—
—
—

7500
67
144.1
135.5
10.00
136.4
131.7
11.01
133.4
130.2
11.35
129.9
128.5
11.78
123.0
125.0
12.66
—
—
—

62
138.9
138.9
9.83
132.1
132.1
10.81
129.2
129.2
11.16
126.1
126.1
11.59
119.8
119.8
12.47
—
—
—

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F –
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — ENGLISH (cont)
38AKS016/40RM014 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
158.9 146.6 134.6 165.3 153.4 142.4 169.6
TC
81.7 103.2 128.5 91.6 118.6 142.4 101.2
85 SHC
13.65 12.95 12.27 14.02 13.34 12.71 14.26
kW
151.9 140.2 129.3 157.6 146.4 136.7 161.5
TC
79.0 100.2 124.0 88.8 115.6 136.7 98.5
95 SHC
14.67 13.95 13.28 15.02 14.33 13.74 15.26
kW
148.5 136.9 126.3 154.1 143.0 133.7 158.0
TC
77.7 98.7 121.4 87.5 114.1 133.7 97.2
100 SHC
15.17 14.45 13.80 15.52 14.83 14.26 15.75
kW
145.0 133.5 123.4 150.3 139.4 130.6 154.0
TC
76.4 97.1 119.0 86.1 112.6 130.6 95.9
105 SHC
15.62 14.86 14.20 15.97 15.26 14.68 16.21
kW
137.6 126.5 117.4
—
132.1 124.4
—
TC
73.5 93.9 113.9
—
109.5 124.4
—
115 SHC
16.55 15.72 15.03
—
16.14 15.56
—
kW
—
116.6 109.7
—
120.9 115.5
—
TC
—
89.4 107.4
—
104.7 115.5
—
125 SHC
—
16.46 15.77
—
16.89 16.35
—
kW
38AKS016/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
170.0 157.8 146.2 175.3 164.9 154.7 179.8
TC
91.5 115.9 142.6 101.1 132.6 154.7 112.7
85 SHC
14.28 13.59 12.93 14.59 13.99 13.41 14.85
kW
161.7 150.5 139.9 166.4 157.0 147.8 170.6
TC
88.6 112.7 137.0 97.8 128.7 147.8 109.4
95 SHC
15.28 14.59 13.93 15.56 14.98 14.42 15.82
kW
158.1 147.1 136.8 162.6 153.4 144.4 166.8
TC
87.3 111.1 134.1 96.4 127.0 144.4 108.0
100 SHC
15.76 15.08 14.44 16.04 15.47 14.92 16.30
kW
154.1 143.4 133.2 158.3 149.4 140.9 162.4
TC
85.9 109.5 131.2 94.7 125.1 140.9 106.4
105 SHC
16.22 15.52 14.85 16.50 15.91 15.35 16.76
kW
—
135.9 126.4
—
141.4 133.6
—
TC
—
106.1 125.2
—
121.2 133.6
—
115 SHC
—
16.41 15.71
—
16.83 16.24
—
kW
—
—
116.6
—
—
—
—
TC
—
—
116.5
—
—
—
—
125 SHC
—
—
16.46
—
—
—
—
kW
38AKS016/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
6000
8000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
183.5 170.7 160.5 188.9 176.0 169.9 190.6
TC
85 SHC 104.1 140.0 159.8 120.1 162.7 169.9 133.8
15.06 14.33 13.74 15.37 14.63 14.28 15.46
kW
174.1 162.1 153.0 179.0 166.8 161.9 180.2
TC
95 SHC 100.6 136.5 153.0 116.5 158.9 161.9 130.2
16.04 15.30 14.74 16.34 15.59 15.29 16.41
kW
170.3 158.4 149.5 175.0 163.0 158.4 176.2
TC
99.1 135.0 149.4 115.1 157.2 158.4 128.8
100 SHC
16.51 15.78 15.23 16.80 16.06 15.78 16.87
kW
165.7 154.2 145.7 170.3 158.5 154.4 171.3
TC
97.4 133.3 145.6 113.3 155.4 154.4 127.0
105 SHC
16.99 16.22 15.67 17.29 16.51 16.24 17.35
kW
—
145.6 137.9
—
—
146.3
—
TC
—
129.7 137.9
—
—
146.3
—
115 SHC
—
17.14 16.57
—
—
17.20
—
kW
—
—
—
—
—
—
—
TC
—
—
—
—
—
—
—
125 SHC
—
—
—
—
—
—
—
kW
—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

62
148.5
148.5
13.06
142.6
142.6
14.10
139.5
139.5
14.62
136.4
136.4
15.06
130.0
130.0
15.97
—
—
—

38AKS024/40RM016 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
212.9 194.5 177.5 222.6 205.8 189.5 229.4
TC
85 SHC 106.7 132.4 170.1 118.8 152.4 189.5 130.4
16.07 15.37 14.72 16.44 15.80 15.18 16.70
kW
203.4 186.1 170.1 212.2 196.6 181.5 218.7
TC
95 SHC 103.3 128.6 163.6 114.9 147.9 181.5 126.5
17.33 16.56 15.83 17.73 17.03 16.35 18.02
kW
198.7 181.2 165.0 207.5 191.7 176.6 214.1
TC
100 SHC 101.7 126.4 159.1 113.2 145.6 176.6 124.9
17.96 17.21 16.52 18.33 17.66 17.01 18.62
kW
197.1 179.9 164.0 205.7 190.2 175.4 212.3
TC
105 SHC 101.1 125.8 158.2 112.5 144.9 175.3 124.2
18.15 17.37 16.65 18.54 17.84 17.17 18.83
kW
194.0 177.2 161.7 202.2 187.2 172.9 208.5
TC
115 SHC 100.0 124.7 156.3 111.2 143.4 172.9 122.9
18.55 17.71 16.94 18.96 18.21 17.49 19.28
kW
183.3 168.2 154.1 190.4 177.1 164.4 196.1
TC
96.2 120.6 149.6 106.8 138.5 164.3 118.5
125 SHC
19.75 18.75 17.81 20.23 19.34 18.49 20.61
kW

62
161.3
161.3
13.79
154.1
154.1
14.81
150.7
150.7
15.31
147.1
147.1
15.76
—
—
—
—
—
—

38AKS024/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
6000
8000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
234.3 216.1 199.2 243.5 225.4 211.3 248.0
TC
85 SHC 123.5 158.7 193.5 139.8 183.6 211.3 154.0
16.89 16.19 15.55 17.24 16.55 16.01 17.14
kW
223.4 206.1 190.4 231.9 214.6 202.2 235.8
TC
95 SHC 119.3 154.5 185.8 135.6 179.0 202.2 149.7
18.23 17.45 16.75 18.61 17.83 17.28 18.79
kW
218.0 201.1 185.4 227.6 209.7 197.6 231.4
TC
100 SHC 117.7 152.5 181.5 134.1 177.0 197.6 148.2
18.83 18.06 17.39 19.20 18.43 17.91 19.36
kW
217.1 199.5 184.1 225.5 207.9 196.1 229.3
TC
105 SHC 116.9 151.8 180.3 133.3 176.2 196.1 147.4
19.05 18.26 17.56 19.43 18.64 18.11 19.60
kW
213.2 196.1 181.3 221.4 204.2 193.1 224.8
TC
115 SHC 115.5 150.4 177.9 131.8 174.6 193.1 145.9
19.51 18.65 17.91 19.92 19.06 18.50 20.09
kW
200.5 184.8 171.8 207.6 191.8 182.8 210.3
TC
125 SHC 110.6 145.8 169.6 126.8 169.4 182.8 140.7
20.90 19.85 18.98 11.37 20.32 19.72 21.55
kW

6250
67
157.9
133.3
13.59
150.6
129.9
14.59
147.1
128.2
15.08
143.4
126.5
15.51
135.8
123.0
16.41
—
—
—

7500
67
169.3
148.2
14.25
161.0
144.0
15.23
157.3
142.2
15.71
153.2
140.1
16.16
—
—
—
—
—
—

10,000
67
181.1
182.5
14.92
171.6
178.2
15.88
167.7
176.4
16.35
163.2
174.4
16.82
—
—
—
—
—
—

62
177.5
177.5
14.71
169.1
169.1
15.73
165.6
165.6
16.22
161.5
161.5
16.70
—
—
—
—
—
—

7500
67
213.0
170.0
16.08
203.3
165.1
17.33
198.5
162.7
17.95
196.9
161.9
18.18
193.6
160.3
18.53
182.8
154.9
19.72

62
198.0
198.0
15.51
189.7
189.7
16.72
185.1
185.1
17.37
183.8
183.8
17.55
181.1
181.1
17.91
172.1
172.1
19.01

10,000
67
232.6
206.1
16.82
221.5
201.0
18.15
216.8
198.9
18.74
214.9
198.0
18.95
211.0
196.2
19.40
198.1
190.3
20.74

62
221.1
221.1
16.39
211.7
211.7
17.71
207.4
207.4
18.33
205.8
205.8
18.54
202.6
202.6
18.98
191.7
191.7
20.32

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F –
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

49

Performance data (cont)
COMBINATION RATINGS — ENGLISH (cont)
38AKS024/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
7500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
250.6 229.7 215.7 259.1 238.4 229.3 263.2
TC
85 SHC 139.5 181.8 213.8 159.6 212.6 229.3 179.4
17.51 16.71 16.18 17.83 17.04 16.70 17.99
kW
238.6 218.2 205.9 246.5 226.4 219.2 250.1
TC
95 SHC 135.0 177.2 204.8 155.2 207.7 219.2 175.0
18.92 18.00 17.45 19.27 19.37 18.04 19.43
kW
234.5 213.3 201.2 242.6 221.6 214.9 246.1
TC
100 SHC 133.5 175.2 200.5 153.8 205.7 214.9 173.7
19.49 18.58 18.06 19.84 18.94 18.65 19.99
kW
232.4 211.3 199.5 240.3 219.5 213.2 243.7
TC
105 SHC 132.7 174.4 199.0 153.0 204.9 213.2 172.9
19.74 18.79 18.26 20.10 19.16 18.87 20.26
kW
228.0 207.4 196.3 235.6 215.3 209.6 238.8
TC
115 SHC 131.1 172.8 196.0 151.3 203.1 209.6 171.3
20.25 19.22 18.66 20.63 19.61 19.33 20.79
kW
—
194.3 185.2
—
201.4 197.8
—
TC
—
167.5 185.2
—
197.4 197.8
—
125 SHC
—
20.48 19.88
—
20.96 20.72
—
kW
38AKS028/40RM024 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
6000
8000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
276.7 254.2 231.0 289.4 267.4 245.0 297.0
TC
85 SHC 139.7 174.3 221.2 156.4 201.3 245.0 171.3
21.72 20.72 19.69 22.28 21.30 20.31 22.62
kW
265.3 244.1 222.8 276.9 256.1 236.3 283.6
TC
95 SHC 135.3 170.1 214.1 151.9 196.6 236.3 166.5
23.45 22.43 21.41 24.00 23.00 22.05 24.32
kW
259.0 238.0 217.3 270.4 249.7 230.7 276.7
TC
100 SHC 132.9 167.6 209.2 149.5 193.8 230.7 164.1
24.28 23.18 22.11 24.87 23.79 22.81 25.20
kW
253.0 232.6 212.8 263.8 243.7 226.0 269.7
TC
105 SHC 130.6 165.4 205.4 147.1 191.3 226.0 161.6
25.03 23.85 22.69 25.66 24.49 23.46 26.01
kW
240.9 222.0 204.1 250.7 231.9 216.6 255.6
TC
115 SHC 126.0 161.1 197.7 142.4 186.3 216.6 156.7
26.63 25.34 24.11 27.29 26.01 24.97 27.63
kW
—
210.5 193.6
—
219.8 206.1
—
TC
—
156.4 188.6
—
181.2 206.1
—
125 SHC
—
26.82 25.59
—
27.50 26.50
—
kW
38AKS028/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
7500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
298.5 274.6 252.4 310.3 286.1 267.8 316.9
TC
85 SHC 157.1 200.0 247.5 177.6 232.2 267.8 197.3
22.69 21.63 20.64 23.21 22.14 21.32 23.51
kW
285.4 262.5 242.8 296.2 273.1 257.5 302.0
TC
95 SHC 152.2 195.1 238.6 172.6 226.9 257.5 192.3
24.41 23.31 22.36 24.93 23.82 23.07 25.21
kW
278.8 255.7 236.9 289.3 266.2 251.7 294.9
TC
100 SHC 149.8 192.4 233.2 170.2 224.0 251.7 190.0
25.31 24.10 23.13 25.85 24.65 23.90 26.14
kW
271.9 249.3 231.7 281.9 259.3 246.2 287.1
TC
105 SHC 147.3 189.8 228.5 167.6 221.2 246.2 187.4
26.13 24.82 23.79 26.72 25.40 24.64 27.02
kW
258.1 236.6 221.4 267.2 245.8 235.3 271.6
TC
115 SHC 142.2 184.7 219.0 162.4 215.6 235.3 182.2
27.80 26.33 25.30 28.41 26.96 26.24 28.72
kW
—
224.0 210.2
—
—
224.3
—
TC
—
179.5 208.8
—
—
224.3
—
125 SHC
—
27.80 26.80
—
—
27.82
—
kW
—
Edb
Ewb
kW
SHC
TC

50

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

62
240.5
240.5
17.12
230.1
230.1
18.53
226.1
226.1
19.13
224.3
224.3
19.38
220.5
220.5
18.99
208.0
208.0
21.40

38AKS028/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
9000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
317.8 291.3 271.9 328.5 302.8 289.0 334.2
TC
85 SHC 172.3 224.7 268.2 199.4 261.6 289.0 221.4
23.55 22.37 21.51 24.02 22.88 22.27 24.28
kW
302.9 277.5 260.7 312.6 288.1 277.0 317.6
TC
95 SHC 166.7 219.2 258.0 194.0 255.7 277.0 215.9
25.25 24.03 23.22 25.72 24.54 24.01 25.95
kW
295.9 270.3 254.3 305.4 280.8 270.7 310.1
TC
100 SHC 164.0 216.4 252.3 191.5 252.8 270.7 213.4
26.20 24.86 24.03 26.69 25.41 24.89 26.93
kW
288.2 263.1 248.3 297.1 273.2 264.4 301.5
TC
105 SHC 161.1 213.5 246.8 188.7 249.7 264.4 210.5
27.08 25.62 24.76 27.61 26.21 25.70 27.86
kW
—
248.9 236.5
—
258.1 251.7
—
TC
—
207.9 236.1
—
243.6 251.7
—
115 SHC
—
27.17 26.32
—
27.80 27.36
—
kW
—
—
224.6
—
—
—
—
TC
—
—
224.5
—
—
—
—
125 SHC
—
—
27.84
—
—
—
—
kW

62
256.3
256.3
20.81
247.1
247.1
22.57
241.6
241.6
23.37
236.6
236.6
24.08
226.7
226.7
25.65
216.1
216.1
27.23

38AKS034/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
7500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
322.9 298.4 272.1 336.1 311.1 287.8 344.0
TC
85 SHC 166.0 209.6 265.5 186.7 242.5 287.8 206.3
24.75 23.82 22.82 25.25 24.30 23.42 25.55
kW
310.6 286.4 262.1 323.0 298.4 277.7 330.3
TC
95 SHC 161.5 204.7 256.4 182.1 237.3 277.6 201.8
26.56 25.44 24.31 27.14 26.00 25.03 27.48
kW
304.2 279.9 256.5 316.5 291.8 272.1 323.5
TC
100 SHC 159.1 202.1 251.2 179.8 234.5 272.1 199.5
27.51 26.29 25.12 28.12 26.89 25.90 28.47
kW
297.9 274.0 251.9 309.6 285.5 267.2 316.2
TC
105 SHC 156.8 199.7 247.0 177.4 231.9 267.2 197.1
28.38 27.06 25.83 29.03 27.69 26.68 29.40
kW
284.2 260.6 204.7 295.2 271.5 255.9 301.2
TC
115 SHC 151.8 194.4 236.7 172.3 226.2 255.9 192.1
30.02 28.57 27.34 30.70 29.34 28.28 31.06
kW
271.2 247.3 229.1 281.7 257.8 244.4 287.2
TC
125 SHC 147.0 189.0 226.1 167.6 220.6 244.4 187.4
31.64 29.99 28.73 32.37 30.72 29.79 32.75
kW

12,500
67
246.6
240.0
17.36
234.4
234.6
18.73
230.0
232.7
19.30
227.8
231.7
19.54
223.4
229.8
20.02
—
—
—

10,000
67
276.2
226.0
21.70
264.4
220.6
23.41
258.0
217.6
24.22
251.7
214.8
24.96
239.4
209.2
26.52
—
—
—

12,500
67
295.7
261.4
22.56
282.2
255.5
24.26
275.3
252.5
25.13
268.2
249.4
25.92
254.2
243.3
27.53
—
—
—

62
280.8
280.8
21.90
270.0
270.0
23.67
264.2
264.2
24.55
258.4
258.4
25.35
246.9
246.9
27.03
—
—
—

15,000
67
312.9
295.1
23.33
297.8
288.5
25.01
290.5
285.3
25.92
282.6
281.8
26.76
—
—
—
—
—
—

62
302.9
302.9
22.88
290.3
290.3
24.64
284.0
284.0
25.58
277.3
277.3
26.45
263.9
263.9
28.20
—
—
—

12,500
67
321.0
272.4
24.68
308.1
266.8
26.45
301.5
263.9
27.38
295.0
261.1
28.22
280.9
254.9
29.82
267.3
249.0
31.37

62
301.3
301.3
23.93
291.0
291.0
25.65
285.4
285.4
26.57
280.3
280.3
27.40
268.6
268.6
29.06
257.2
257.2
30.67

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F –
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

COMBINATION RATINGS — ENGLISH (cont)
38AKS034/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
9000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
344.6 317.4 294.0 256.9 330.1 311.5 363.8
TC
85 SHC 182.5 235.1 288.2 209.0 272.7 311.5 231.3
25.57 24.55 23.65 26.04 25.02 24.32 26.30
kW
331.0 304.2 282.8 342.5 316.2 300.1 348.8
TC
95 SHC 177.3 229.8 278.1 204.1 267.1 300.1 226.3
27.51 26.27 25.27 28.05 26.82 26.08 28.34
kW
324.3 297.3 276.8 335.5 309.2 294.1 341.6
TC
100 SHC 174.8 227.1 272.6 201.7 264.2 294.1 223.9
28.51 27.16 26.14 29.08 27.76 27.00 29.38
kW
317.1 290.6 271.3 327.8 302.1 288.4 333.5
TC
105 SHC 172.0 224.4 267.7 199.1 261.4 288.4 221.2
29.45 27.98 26.91 30.05 28.62 27.85 30.36
kW
302.2 276.0 258.9 312.1 286.9 275.7 317.2
TC
115 SHC 166.4 218.6 256.4 193.8 255.2 275.6 215.7
31.12 29.51 28.46 31.74 30.19 29.49 32.05
kW
288.3 261.8 246.5
—
272.5 263.3
—
TC
—
249.4 263.3
—
125 SHC 161.1 213.0 245.1
32.83 30.99 29.93
—
31.73 31.10
—
kW
38AKS044/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm
Temp (F)
9000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
72
67
62
72
67
62
72
413.7 382.6 344.5 432.1 399.8 364.9 443.5
TC
85 SHC 208.7 260.9 334.0 234.4 300.7 364.9 257.8
32.85 31.60 30.08 33.58 32.29 30.89 34.04
kW
399.2 368.7 333.6 416.4 384.9 353.6 426.9
TC
95 SHC 203.2 255.4 324.2 229.1 294.7 353.6 252.3
35.19 33.74 32.08 36.00 34.51 33.03 36.50
kW
391.8 361.5 328.0 408.3 377.3 347.7 418.3
TC
100 SHC 200.4 252.5 319.0 226.4 291.7 347.7 249.4
36.36 34.80 33.08 37.21 35.61 34.09 37.72
kW
384.2 354.1 322.2 400.1 369.5 341.7 409.6
TC
105 SHC 197.5 249.6 313.8 223.6 288.5 341.7 246.5
37.55 35.88 34.11 38.44 36.74 35.20 38.97
kW
368.5 339.0 310.2 383.1 353.5 329.2 391.7
TC
115 SHC 191.5 243.6 302.9 217.8 282.1 329.2 240.6
39.77 37.95 36.17 40.68 38.85 37.35 41.21
kW
352.6 323.3 297.2 366.4 337.2 316.0 374.3
TC
125 SHC 185.5 237.4 291.1 212.2 275.5 316.0 234.8
41.94 39.90 38.08 42.91 40.87 39.39 43.45
kW

15,000
67
340.6
307.3
25.42
326.6
301.1
27.31
319.6
298.0
28.28
312.2
294.8
29.18
296.8
288.0
30.80
282.5
281.7
32.43

62
326.0
326.0
24.87
314.3
314.3
26.74
308.3
308.3
27.72
302.3
302.3
28.63
289.3
289.3
30.33
276.9
276.9
32.04

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

1. Direct interpolation is permissible. Do not extrapolate.
2. SHC is based on 80 F db air entering indoor coil.
3. Formulas:
SHCBtuh
Ldb F = Edb F –
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

15,000
67
412.4
338.8
32.80
397.2
332.2
35.10
389.4
328.7
36.24
381.5
325.2
37.41
365.1
318.1
39.57
348.7
310.8
41.67

62
382.2
382.2
31.59
370.5
370.5
33.83
364.4
364.4
34.95
358.2
358.2
36.11
345.2
345.2
38.33
331.7
331.7
40.48

51

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI
38AK007/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
850
1130
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
18.1 19.7 21.5 19.0 20.6 22.4 20.1
TC
16.3 13.6 10.7 19.0 15.6 12.0 20.1
29 SHC
4.93 5.16 5.40 5.06 5.29 5.53 5.21
kW
17.2 18.8 20.5 18.2 19.6 21.4 19.5
TC
15.9 13.2 10.4 18.2 15.2 11.6 19.5
35 SHC
5.19 5.45 5.72 5.35 5.58 5.85 5.69
kW
16.7 18.3 20.0 17.8 19.1 20.9 18.8
TC
15.6 13.0 10.2 17.8 15.0 11.5 18.8
38 SHC
5.31 5.59 5.87 5.49 5.72 6.00 5.67
kW
16.3 17.8 19.5 17.4 18.6 20.3 18.4
TC
15.4 12.8 10.0 17.4 14.8 11.3 18.4
41 SHC
5.44 5.73 6.02 5.64 5.87 6.16 5.82
kW
15.4 16.8 18.5 16.5 17.6 19.2 17.5
TC
14.9 12.4
9.6
16.5 14.4 10.9 17.5
46 SHC
5.69 5.99 6.31 5.93 6.14 6.46 6.12
kW
38AK007/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19.3 21.0 22.9 20.6 21.8 23.7 21.7
TC
18.7 15.5 12.0 20.6 18.0 13.6 21.7
29 SHC
5.11 5.35 5.60 5.29 5.47 5.72 5.43
kW
18.3 20.0 21.8 19.8 20.8 22.6 20.8
TC
18.3 15.1 11.6 19.8 17.6 13.2 20.8
35 SHC
5.39 5.65 5.92 5.61 5.77 6.05 5.77
kW
17.9 19.5 21.3 19.4 20.3 22.0 20.4
TC
17.9 14.9 11.5 19.4 17.4 13.0 20.4
38 SHC
5.53 5.79 6.08 5.77 5.92 6.21 5.93
kW
17.5 19.0 20.7 18.9 19.7 21.4 19.9
TC
17.5 14.7 11.3 18.9 17.2 12.8 19.9
41 SHC
5.68 5.94 6.24 5.93 6.07 6.37 6.09
kW
16.7 17.9 17.9 18.0 18.5 18.5 18.9
TC
16.7 14.3 14.3 18.0 16.7 16.7 18.9
46 SHC
5.97 6.22 6.22 6.24 6.34 6.34 6.41
kW
38AK008/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
850
1130
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
21.6 23.5 25.4 22.8 24.7 26.7 23.6
TC
18.0 15.2 12.3 20.8 17.2 13.5 23.2
29 SHC
6.01 6.18 6.35 6.11 6.29 6.47 6.19
kW
20.8 22.6 24.5 21.9 23.7 25.6 22.6
TC
17.6 14.8 11.9 20.3 16.8 13.1 22.6
35 SHC
6.49 6.67 6.85 6.60 6.77 6.97 6.67
kW
20.3 22.1 24.0 21.4 23.2 25.1 22.2
TC
17.4 14.6 11.7 20.1 16.6 12.9 22.2
38 SHC
6.73 6.91 7.10 6.85 7.02 7.22 6.92
kW
19.8 21.6 23.4 20.9 22.6 24.5 21.7
TC
17.1 14.4 11.5 19.8 16.4 12.7 21.7
41 SHC
6.99 7.17 7.35 7.10 7.28 7.47 7.18
kW
18.9 20.5 22.3 19.9 21.5 23.3 20.8
TC
16.7 13.9 11.0 19.3 16.0 12.3 20.8
46 SHC
7.54 7.71 7.90 7.64 7.82 8.02 7.74
kW
See Legend and Notes on page 57.

52

22
23.0
13.2
5.61
22.0
12.8
5.94
21.4
12.6
6.09
20.8
12.4
6.25
19.6
12.0
6.55

38AK008/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
23.2 25.2 27.3 24.4 26.3 28.4 25.5
TC
20.7 17.2 13.5 23.8 19.7 15.1 25.5
29 SHC
6.18 6.36 6.55 6.28 6.47 6.66 6.39
kW
22.3 24.2 26.2 23.4 25.2 27.2 24.6
TC
20.2 16.8 13.2 23.4 19.3 14.7 24.6
35 SHC
6.68 6.86 7.06 6.77 6.96 7.17 6.90
kW
21.8 23.7 25.7 22.9 24.6 26.6 24.1
TC
20.0 16.6 12.9 22.9 19.1 14.5 24.1
38 SHC
6.93 7.11 7.31 7.03 7.21 7.42 7.15
kW
21.3 23.1 25.1 22.4 24.0 26.0 23.6
TC
19.7 16.3 12.7 22.4 18.8 14.3 23.6
41 SHC
7.19 7.37 7.57 7.29 7.46 7.67 7.41
kW
20.2 22.0 23.8 21.5 22.8 24.7 22.6
TC
19.3 15.9 12.3 21.5 18.4 13.8 22.6
46 SHC
7.73 7.91 8.12 7.86 8.01 8.21 7.97
kW

22
24.2
15.0
5.79
23.1
14.6
6.12
22.5
14.4
6.28
21.9
14.2
6.44
19.0
18.7
6.43

38AK008/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1416
1888
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
25.6 27.2 29.4 27.3 28.1 30.1 28.5
TC
25.5 20.8 15.8 27.3 24.1 17.8 28.5
29 SHC
6.44 6.58 6.79 6.59 6.67 6.86 6.71
kW
24.7 26.1 28.1 26.3 27.0 28.9 27.4
TC
24.7 20.4 15.4 26.3 23.6 17.4 27.4
35 SHC
6.96 7.08 7.29 7.11 7.17 7.37 7.22
kW
24.2 25.5 27.5 25.8 26.3 28.2 26.8
TC
24.2 20.2 15.2 25.8 23.4 17.2 26.8
38 SHC
7.20 7.33 7.55 7.37 7.42 7.62 7.47
kW
23.7 24.9 26.8 25.2 25.7 27.5 26.2
TC
23.7 20.0 15.0 25.2 23.1 16.9 26.2
41 SHC
7.47 7.59 7.81 7.63 7.68 7.87 7.74
kW
22.6 23.6 25.4 24.1 24.3 26.0 25.0
TC
22.6 19.5 14.5 24.1 22.6 16.5 25.0
46 SHC
8.03 8.14 8.36 8.19 8.22 8.42 8.30
kW

22
27.5
14.7
6.55
26.4
14.3
7.05
25.8
14.1
7.30
25.2
13.9
7.55
23.9
13.5
8.08

38AK012/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
1770
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
27.5 29.9 32.5 29.1 31.5 34.1 30.2 32.6 35.1
TC
22.7 19.1 15.3 26.3 21.7 16.9 29.4 24.2 18.5
29 SHC
7.78 8.04 8.32 7.95 8.22 8.51 8.07 8.34 8.63
kW
26.6 28.9 31.3 28.0 30.3 32.8 29.0 31.3 33.8
TC
22.2 18.6 14.8 25.8 21.2 16.5 29.0 23.7 18.0
35 SHC
8.40 8.66 8.95 8.56 8.83 9.13 8.68 8.95 9.25
kW
26.1 28.3 30.7 27.4 29.7 32.1 28.4 30.6 33.1
TC
22.0 18.4 14.6 25.5 21.0 16.2 28.4 23.4 17.7
38 SHC
8.73 8.98 9.27 8.87 9.14 9.44 9.00 9.26 9.56
kW
25.5 27.9 30.1 26.9 29.1 31.4 27.9 30.0 32.4
TC
21.8 18.2 14.4 25.2 20.7 16.0 27.9 23.2 17.5
41 SHC
9.05 9.41 9.59 9.20 9.46 9.76 9.32 9.58 9.88
kW
24.4 26.5 28.7 25.7 27.7 30.3 26.8 28.5 30.8
TC
21.2 17.6 13.8 24.7 20.2 15.6 26.8 22.7 17.0
46 SHC
9.77 10.00 10.27 9.92 10.16 10.71 10.03 10.26 10.55
kW

1420
19
21.2
17.5
5.37
20.2
17.1
5.67
19.7
16.9
5.82
19.2
16.7
5.96
18.0
16.2
6.23

1770
19
22.4
20.2
5.54
21.3
19.7
5.85
20.7
19.5
5.99
20.2
19.2
6.14
19.0
18.7
6.43

1420
19
25.5
19.1
6.36
24.4
18.7
6.85
23.9
18.5
7.10
23.3
18.3
7.35
22.1
17.8
7.88

1770
19
27.0
22.0
6.53
25.9
21.6
7.02
25.3
21.4
7.28
24.7
21.1
7.53
23.4
20.6
8.08

22
29.1
16.5
6.72
27.9
16.1
7.24
27.3
15.9
7.49
26.6
15.7
7.74
25.2
15.2
8.29

2360
19
28.8
27.0
6.73
27.6
26.4
7.23
27.0
26.2
7.49
26.3
25.8
7.75
25.0
25.0
8.30

22
30.7
19.7
6.91
29.4
19.3
7.42
28.7
19.1
7.67
28.0
18.9
7.92
26.4
18.4
8.46

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI (cont)
38AK012/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
30.9 33.2 35.9 32.5 34.4 37.1 33.4 35.3 37.9
TC
28.1 23.1 17.9 32.5 26.4 20.0 33.4 29.7 22.0
29 SHC
7.92 8.18 8.47 8.10 8.32 8.62 7.55 8.41 8.70
kW
29.7 31.9 34.5 31.4 33.0 35.6 32.9 33.9 36.4
TC
27.5 22.6 17.4 31.4 26.0 19.5 32.9 29.1 21.5
35 SHC
8.53 8.77 9.08 8.71 8.90 9.21 8.89 9.00 9.30
kW
29.1 31.3 33.8 30.8 32.3 34.8 32.3 33.1 35.6
TC
27.2 22.3 17.2 30.8 25.7 19.2 32.3 28.9 21.2
38 SHC
8.83 9.08 9.38 9.03 9.20 9.51 9.20 9.30 9.60
kW
28.5 30.6 33.0 30.4 31.6 34.0 31.6 32.4 34.7
TC
26.9 22.0 16.9 30.4 25.4 18.9 31.6 28.5 20.9
41 SHC
9.14 9.39 9.69 9.47 9.50 9.81 9.51 9.60 9.90
kW
27.2 29.1 31.9 29.0 30.1 32.3 30.3 30.8 33.0
TC
26.3 21.5 16.5 29.0 24.8 18.4 30.3 27.9 20.4
46 SHC
9.83 10.05 10.63 10.04 10.17 10.46 10.20 10.27 10.54
kW

38AKS008/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
22.6 24.7 27.0 23.8 25.9 28.2 25.2
TC
20.4 17.0 13.4 23.8 19.6 15.0 25.2
29 SHC
5.61 5.81 6.00 5.72 5.92 6.11 5.84
kW
21.6 23.7 25.8 22.8 24.7 26.9 24.2
TC
19.9 16.5 13.0 22.8 19.1 14.6 24.2
35 SHC
6.06 6.30 6.53 6.20 6.41 6.65 6.35
kW
21.1 23.1 25.2 22.4 24.1 26.2 23.6
TC
19.6 16.3 12.8 22.4 18.8 14.3 23.6
38 SHC
6.27 6.53 6.79 6.43 6.65 6.90 6.59
kW
20.5 22.5 24.6 21.9 23.5 25.6 23.1
TC
19.4 16.1 12.6 21.9 18.6 14.1 23.1
41 SHC
6.48 6.75 7.03 6.67 6.88 7.15 6.83
kW
19.4 21.3 23.3 20.9 22.2 24.2 22.0
TC
18.8 15.6 12.1 20.9 18.1 13.7 22.0
46 SHC
6.90 7.21 7.52 7.14 7.36 7.66 7.33
kW

38AK012/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1770
2360
2950
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
32.4 34.9 37.7 34.4 36.2 38.9 36.0 37.0 39.7
TC
31.3 25.8 19.8 34.4 29.9 22.3 36.0 33.6 24.7
29 SHC
8.06 8.35 8.66 8.28 8.49 8.80 8.46 8.59 8.89
kW
31.1 33.6 36.2 33.2 34.7 37.4 34.8 35.5 38.1
TC
30.6 25.3 19.3 33.2 29.3 21.8 34.8 32.9 24.1
35 SHC
8.65 8.94 9.26 8.89 9.08 9.40 9.08 9.17 9.50
kW
30.5 32.8 35.5 32.6 34.0 36.6 34.1 34.7 37.3
TC
30.5 25.0 19.1 32.6 29.0 21.6 34.1 32.5 23.9
38 SHC
8.96 9.24 9.56 9.20 9.38 9.71 9.39 9.47 9.80
kW
30.1 32.1 34.6 32.1 33.2 35.7 33.4 33.9 36.4
TC
30.1 24.7 18.7 32.1 28.7 21.3 33.4 32.1 23.6
41 SHC
9.41 9.55 9.87 9.67 9.69 10.01 9.71 9.77 10.10
kW
28.7 30.6 33.0 30.6 31.6 33.9 31.9 32.2 34.5
TC
28.7 24.1 18.2 30.6 28.0 20.7 31.9 31.3 23.0
46 SHC
9.99 10.23 10.53 10.22 10.35 10.67 10.39 10.43 10.74
kW

38AKS008/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
25.2 26.8 29.2 27.0 27.8 30.0 28.3
TC
25.2 20.7 15.8 27.0 23.9 17.7 28.3
29 SHC
5.88 6.03 6.22 6.04 6.11 6.28 6.15
kW
24.2 25.6 27.8 25.9 26.5 28.6 27.0
TC
24.2 20.2 15.3 25.9 23.4 17.3 27.0
35 SHC
6.38 6.54 6.77 6.57 6.64 6.85 6.69
kW
23.7 25.0 27.1 25.3 25.8 27.9 26.4
TC
23.7 20.0 15.0 25.3 23.2 17.0 26.4
38 SHC
6.62 6.78 7.03 6.83 6.88 7.11 6.95
kW
23.1 24.3 26.4 24.7 25.2 27.1 25.8
TC
23.1 19.7 14.8 24.7 22.9 16.8 25.8
41 SHC
6.86 7.02 7.29 7.08 7.12 7.37 7.21
kW
22.1 23.0 25.0 23.5 23.8 25.6 24.6
TC
22.1 19.2 14.3 23.5 22.3 16.3 24.6
46 SHC
7.35 7.50 7.81 7.58 7.62 7.89 7.74
kW

38AKS008/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
850
1130
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
20.9 23.0 25.1 22.2 24.2 26.4 23.0
TC
17.7 14.9 12.1 20.4 17.0 13.4 23.0
29 SHC
5.40 5.60 5.79 5.53 5.72 5.90 5.61
kW
20.0 21.9 24.0 21.2 23.1 25.2 22.1
TC
17.2 14.5 11.7 20.0 16.6 13.0 22.1
35 SHC
5.82 6.06 6.29 5.97 6.20 6.42 6.07
kW
19.5 21.4 23.4 20.7 22.6 24.6 21.6
TC
17.0 14.3 11.5 19.7 16.4 12.8 21.6
38 SHC
6.02 6.28 6.53 6.18 6.43 6.67 6.30
kW
19.1 20.9 22.9 20.2 22.0 24.0 21.1
TC
16.8 14.1 11.2 19.5 16.2 12.5 21.1
41 SHC
6.22 6.49 6.76 6.38 6.65 6.91 6.52
kW
18.1 19.8 21.7 19.1 20.8 22.7 20.2
TC
16.3 13.6 10.8 19.1 15.7 12.1 20.2
46 SHC
6.63 6.93 7.23 6.79 7.09 7.40 6.99
kW

38AKS009/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
26.1 28.6 31.3 27.6 30.2 32.9 28.7
TC
22.0 18.6 15.1 25.5 21.2 16.7 28.7
29 SHC
7.21 7.52 7.82 7.40 7.70 8.01 7.54
kW
24.9 27.3 29.8 26.3 28.7 31.3 27.4
TC
21.4 18.0 14.5 24.9 20.7 16.1 27.4
35 SHC
7.73 8.08 8.43 7.94 8.28 8.62 8.10
kW
24.2 26.6 29.1 25.7 28.0 30.5 26.8
TC
21.1 17.8 14.2 24.6 20.4 15.8 26.8
38 SHC
7.98 8.35 8.72 8.21 8.56 8.93 8.38
kW
23.6 25.9 28.4 25.0 27.3 29.8 26.2
TC
20.8 17.5 13.9 24.2 20.1 15.6 26.2
41 SHC
8.24 8.63 9.02 8.48 8.86 9.24 8.67
kW
22.4 24.5 26.9 23.6 25.8 28.1 25.0
TC
20.2 16.9 13.4 23.6 19.5 15.0 25.0
46 SHC
8.75 9.17 9.60 8.99 9.40 9.84 9.26
kW

1420
19
25.1
19.0
5.80
23.9
18.5
6.28
23.3
18.3
6.51
22.7
18.1
6.74
21.5
17.6
7.20

22
27.2
14.6
5.98
26.0
14.2
6.51
25.4
14.0
6.76
24.7
13.7
7.00
23.4
13.3
7.49

1770
19
26.7
21.9
5.98
25.4
21.4
6.49
24.8
21.2
6.74
24.1
20.9
6.97
22.8
20.4
7.45

22
29.0
16.5
6.17
27.6
16.0
6.72
26.9
15.8
6.98
26.2
15.6
7.24
24.8
15.1
7.76

2360
19
28.6
26.9
6.17
27.2
26.3
6.71
26.5
25.9
6.96
25.9
25.6
7.22
24.6
24.6
7.74

22
30.7
19.7
6.33
29.1
19.2
6.90
28.4
19.0
7.16
27.6
18.8
7.42
26.0
18.3
7.95

1770
19
31.2
23.7
7.83
29.7
23.1
8.42
28.9
22.8
8.70
28.1
22.5
8.99
26.5
21.9
9.54

22
33.9
18.2
8.13
32.3
17.6
8.76
31.5
17.4
9.07
30.7
17.0
9.37
28.9
16.5
9.98

See Legend and Notes on page 57.

53

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI (cont)
38AKS009/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
29.1 31.5 34.3 31.0 32.7 35.6 32.6 33.7 36.4
TC
27.2 22.5 17.4 31.0 25.8 19.5 32.6 28.9 21.5
29 SHC
7.75 8.04 8.36 7.97 8.17 8.49 8.17 8.27 8.57
kW
27.7 30.0 32.7 29.7 31.1 33.8 31.2 32.0 34.6
TC
26.5 21.8 16.9 29.7 25.2 18.9 31.2 28.3 20.9
35 SHC
8.30 8.62 8.99 8.58 8.76 9.12 8.78 8.89 9.22
kW
27.0 29.2 31.9 29.0 30.3 32.9 30.5 31.2 33.6
TC
26.2 21.5 16.6 29.0 24.9 18.6 30.5 28.0 20.6
38 SHC
8.58 8.91 9.30 8.88 9.06 9.44 9.10 9.20 9.54
kW
26.4 28.4 31.0 28.3 29.5 32.0 29.8 30.4 32.7
TC
25.8 21.2 16.3 28.3 24.6 18.3 29.8 27.6 20.3
41 SHC
8.87 9.20 9.61 9.19 9.37 9.76 9.42 9.51 9.86
kW
25.1 26.8 29.3 27.0 27.9 30.2 28.3 28.7 30.9
TC
25.1 20.6 15.7 27.0 23.9 17.7 28.3 26.9 19.7
46 SHC
9.43 9.75 10.20 9.78 9.95 10.36 10.03 10.09 10.48
kW

38AKS012/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1770
2360
2950
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
30.7 33.4 36.4 33.0 34.7 37.6 34.7 35.5 38.5
TC
30.4 26.4 22.0 33.0 30.1 24.3 34.7 33.3 26.5
29 SHC
7.84 8.16 8.48 8.10 8.31 8.64 8.30 8.41 8.74
kW
29.3 31.7 34.6 31.6 32.9 35.8 33.2 33.7 36.5
TC
29.3 25.6 21.2 31.6 29.2 23.5 33.2 32.3 25.6
35 SHC
8.43 8.78 9.14 8.75 8.95 9.31 8.96 9.04 9.41
kW
28.7 30.9 33.7 30.9 32.0 34.8 32.4 32.8 35.5
TC
28.7 25.2 20.8 30.9 28.8 23.1 32.4 31.8 25.2
38 SHC
8.75 9.09 9.48 9.07 9.26 9.65 9.29 9.35 9.74
kW
28.0 30.0 32.8 30.2 31.1 33.8 31.6 31.8 34.5
TC
28.0 24.8 20.4 30.2 28.4 22.7 31.6 31.2 24.8
41 SHC
9.06 9.40 9.81 9.40 9.57 9.98 9.63 9.67 10.08
kW
26.7 28.3 30.9 28.6 29.3 31.9 30.0 30.1 32.5
TC
26.7 24.0 19.6 28.6 27.5 21.8 30.0 30.1 23.9
46 SHC
9.65 9.98 10.45 10.02 10.15 10.61 10.26 10.27 10.71
kW

38AKS012/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
26.1 28.6 31.3 27.6 30.2 32.9 28.7
TC
22.0 18.6 15.1 25.5 21.2 16.7 28.7
29 SHC
7.21 7.52 7.82 7.40 7.70 8.01 7.54
kW
24.9 27.3 29.8 26.3 28.7 31.3 27.4
TC
21.4 18.0 14.5 24.9 20.7 16.1 27.4
35 SHC
7.73 8.08 8.43 7.94 8.28 8.62 8.10
kW
24.2 26.6 29.1 25.7 28.0 30.5 26.8
TC
21.1 17.8 14.2 24.6 20.4 15.8 26.8
38 SHC
7.98 8.35 8.72 8.21 8.56 8.93 8.38
kW
23.6 25.9 28.4 25.0 27.3 29.8 26.2
TC
20.8 17.5 13.9 24.2 20.1 15.6 26.2
41 SHC
8.24 8.63 9.02 8.48 8.86 9.24 8.67
kW
22.4 24.5 26.9 23.6 25.8 28.1 25.0
TC
20.2 16.9 13.4 23.6 19.5 15.0 25.0
46 SHC
8.75 9.17 9.60 8.99 9.40 9.84 9.26
kW

22
33.9
18.2
8.13
32.3
17.6
8.76
31.5
17.4
9.07
30.7
17.0
9.37
28.9
16.5
9.98

38AKS013/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1060
1420
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
27.1 29.7 32.5 28.8 31.5 34.3 29.9
TC
22.5 19.1 15.6 26.1 21.8 17.2 29.1
29 SHC
6.81 7.06 7.30 6.97 7.21 7.45 7.08
kW
25.8 28.4 31.1 27.4 30.0 32.7 28.5
TC
21.9 18.5 15.0 25.4 21.2 16.7 28.5
35 SHC
7.37 7.66 7.95 7.55 7.83 8.12 7.67
kW
25.2 27.7 30.3 26.7 29.2 31.9 27.8
TC
21.6 18.2 14.7 25.1 20.9 16.4 27.8
38 SHC
7.64 7.96 8.26 7.84 8.14 8.44 7.97
kW
24.5 27.0 29.6 26.0 28.5 31.1 27.2
TC
21.3 17.9 14.4 24.7 20.6 16.1 27.2
41 SHC
7.90 8.24 8.57 8.11 8.44 8.76 8.26
kW
23.2 25.5 28.0 24.6 26.9 29.4 25.9
TC
20.6 17.3 13.8 24.0 20.0 15.5 25.9
46 SHC
8.44 8.82 9.19 8.66 9.03 9.40 8.87
kW

38AKS012/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
29.1 31.5 34.3 31.0 32.7 35.6 32.6 33.7 36.4
TC
27.2 22.5 17.4 31.0 25.8 19.5 32.6 28.9 21.5
29 SHC
7.75 8.04 8.36 7.97 8.17 8.49 8.17 8.27 8.57
kW
27.7 30.0 32.7 29.7 31.1 33.8 31.2 32.0 34.6
TC
26.5 21.8 16.9 29.7 25.2 18.9 31.2 28.3 20.9
35 SHC
8.30 8.62 8.99 8.58 8.76 9.12 8.78 8.89 9.22
kW
27.0 29.2 31.9 29.0 30.3 32.9 30.5 31.2 33.6
TC
26.2 21.5 16.6 29.0 24.9 18.6 30.5 28.0 20.6
38 SHC
8.58 8.91 9.30 8.88 9.06 9.44 9.10 9.20 9.54
kW
26.4 28.4 31.0 28.3 29.5 32.0 29.8 30.4 32.7
TC
25.8 21.2 16.3 28.3 24.6 18.3 29.8 27.6 20.3
41 SHC
8.87 9.20 9.61 9.19 9.37 9.76 9.42 9.51 9.86
kW
25.1 26.8 29.3 27.0 27.9 30.2 28.3 28.7 30.9
TC
25.1 20.6 15.7 27.0 23.9 17.7 28.3 26.9 19.7
46 SHC
9.43 9.75 10.20 9.78 9.95 10.36 10.03 10.09 10.48
kW

38AKS013/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
30.2 32.8 35.7 32.0 34.1 37.1 33.8
TC
27.7 22.9 18.0 32.0 26.3 20.0 33.8
29 SHC
7.08 7.30 7.54 7.23 7.40 7.64 7.38
kW
28.8 31.2 34.1 30.7 32.4 35.2 32.4
TC
27.0 22.3 17.3 30.7 25.7 19.4 32.4
35 SHC
7.68 7.94 8.23 7.89 8.06 8.33 8.05
kW
28.1 30.4 33.2 30.0 31.6 34.3 31.6
TC
26.7 22.0 17.0 30.0 25.4 19.1 31.6
38 SHC
7.98 8.25 8.56 8.21 8.38 8.67 8.38
kW
27.3 29.6 32.3 29.3 30.7 33.3 30.9
TC
26.3 21.7 16.7 29.3 25.1 18.7 30.9
41 SHC
8.27 8.55 8.88 8.53 8.69 9.00 8.71
kW
25.9 27.9 30.4 27.9 29.0 31.4 29.3
TC
25.6 21.0 16.1 27.9 24.4 18.1 29.3
46 SHC
8.86 9.15 9.52 9.16 9.31 9.65 9.37
kW

See Legend and Notes on page 57.

54

1770
19
31.2
23.7
7.83
29.7
23.1
8.42
28.9
22.8
8.70
28.1
22.5
8.99
26.5
21.9
9.54

1770
19
32.6
24.2
7.31
31.1
23.6
7.95
30.2
23.3
8.26
29.4
23.0
8.55
27.7
22.3
9.15

22
35.5
18.8
7.54
33.9
18.2
8.23
33.0
17.9
8.57
32.1
17.6
8.88
30.3
17.0
9.52

2360
19
35.1
29.5
7.48
33.4
28.9
8.15
32.5
28.5
8.48
31.6
28.1
8.80
29.8
27.5
9.43

22
38.0
22.0
7.70
36.0
21.4
8.41
35.1
21.0
8.76
34.1
20.7
9.09
32.1
20.1
9.75

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI (cont)

22
40.1
24.9
7.89
38.0
24.2
8.63
36.9
23.8
8.98
35.9
23.5
9.33
33.8
22.8
10.02

38AKS014/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2120
2830
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
38.6 42.2 46.1 41.3 44.0 47.9 43.6
TC
36.8 29.0 20.1 41.3 34.5 23.5 43.6
29 SHC
8.46 8.68 8.89 8.63 8.79 8.98 8.76
kW
36.9 40.2 43.9 39.6 41.9 45.6 41.8
TC
36.0 28.4 19.6 39.6 33.8 23.0 41.8
35 SHC
9.31 9.57 9.85 9.52 9.70 9.97 9.69
kW
36.0 39.2 42.8 38.8 40.8 44.5 40.9
TC
36.0 28.1 19.3 38.8 33.7 22.7 40.9
38 SHC
9.72 10.00 10.31 9.96 10.14 10.45 10.14
kW
35.5 38.2 41.8 38.0 39.7 43.3 40.0
TC
35.5 27.9 19.1 38.0 33.3 22.5 40.0
41 SHC
10.30 10.43 10.76 10.40 10.57 10.90 10.59
kW
33.6 36.2 39.6 36.3 37.6 41.0 38.1
TC
33.6 27.3 18.6 36.3 32.6 22.0 38.1
46 SHC
10.93 11.26 11.65 11.26 11.41 11.80 11.47
kW

38AKS014/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1420
1890
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
19
22
33.9 37.0 40.4 35.9 38.7 42.1 37.7 39.9 43.4
TC
29.5 24.7 19.7 34.2 28.1 21.8 37.7 31.4 23.8
29 SHC
8.27 8.50 8.75 8.43 8.62 8.86 8.55 8.71 8.94
kW
32.4 35.3 38.6 34.4 36.9 40.2 36.2 38.1 41.3
TC
28.8 24.0 19.0 33.3 27.4 21.1 36.2 30.8 23.1
35 SHC
9.03 9.31 9.60 9.22 9.46 9.74 9.39 9.55 9.84
kW
31.7 34.5 37.7 33.6 36.0 39.2 35.4 37.1 40.3
TC
28.4 23.6 18.7 33.0 27.0 20.8 35.4 30.4 22.8
38 SHC
9.40 9.70 10.02 9.61 9.86 10.18 9.80 9.97 10.27
kW
31.0 33.7 36.8 32.8 35.1 38.3 34.7 36.5 39.3
TC
28.1 23.3 18.3 32.8 26.7 20.4 34.7 30.2 22.4
41 SHC
9.77 10.09 10.44 9.98 10.25 10.60 10.21 10.51 10.70
kW
29.5 32.0 35.0 31.4 33.3 36.3 33.1 34.3 37.2
TC
27.4 22.6 17.7 31.4 26.0 19.7 33.1 29.2 21.8
46 SHC
10.49 10.86 11.26 10.77 11.03 11.42 11.01 11.17 11.53
kW

38AKS016/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1770
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
43.8 47.9 52.2 46.3 50.4 54.8 48.0
TC
35.5 28.0 20.3 41.9 32.6 23.0 48.0
29 SHC
11.96 12.41 12.86 12.23 12.67 13.13 12.42
kW
42.0 45.9 50.1 44.3 48.3 53.2 46.1
TC
34.8 27.3 19.7 41.0 32.0 22.6 46.1
35 SHC
12.95 13.48 14.01 13.27 13.78 14.82 13.51
kW
41.1 44.9 49.3 43.4 47.2 51.4 45.2
TC
34.4 27.0 19.5 40.7 31.7 22.1 45.2
38 SHC
13.43 14.00 14.80 13.78 14.33 14.89 14.04
kW
40.2 43.9 47.9 42.4 46.2 50.2 44.3
TC
34.1 26.7 19.1 40.3 31.4 21.8 44.3
41 SHC
13.91 14.52 15.12 14.29 14.87 15.46 14.57
kW
38.3 41.9 45.7 40.4 43.9 47.8 42.5
TC
33.4 26.1 18.5 39.4 30.7 21.3 42.5
46 SHC
14.90 15.56 16.23 15.29 15.94 16.61 15.67
kW

38AKS014/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1770
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
36.0 39.4 42.8 38.0 41.0 44.7 40.2
TC
33.2 27.5 21.6 38.0 31.7 24.2 40.2
29 SHC
8.36 8.59 8.81 8.50 8.70 8.92 8.64
kW
34.2 38.0 41.4 36.4 38.9 42.3 38.3
TC
32.3 27.0 21.1 36.4 30.8 23.4 38.3
35 SHC
9.16 9.72 10.01 9.36 9.57 9.85 9.52
kW
33.4 36.4 39.7 35.6 37.9 41.2 37.5
TC
31.8 26.3 20.5 35.6 30.5 23.0 37.5
38 SHC
9.55 9.86 10.17 9.78 10.00 10.30 9.96
kW
32.8 35.5 38.7 35.0 37.2 40.1 36.9
TC
31.6 25.9 20.1 35.0 30.2 22.7 36.9
41 SHC
10.09 10.27 10.60 10.34 10.57 10.75 10.55
kW
30.9 33.6 36.6 33.2 34.9 37.9 34.9
TC
30.5 25.2 19.3 33.2 29.3 21.9 34.9
46 SHC
10.69 11.06 11.45 11.01 11.24 11.62 11.25
kW

38AKS016/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2120
2830
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
46.6 50.9 55.3 49.2 53.5 58.0 51.5
TC
41.3 34.5 27.4 47.6 39.7 30.6 51.5
29 SHC
12.23 12.68 13.15 12.51 12.96 13.41 12.74
kW
44.7 48.8 53.0 47.1 51.1 54.9 49.6
TC
40.3 33.6 26.5 46.3 38.8 29.5 49.6
35 SHC
13.28 13.80 14.34 13.60 14.10 14.64 13.92
kW
43.7 47.7 51.9 46.0 49.9 54.5 48.7
TC
39.8 33.2 26.1 46.0 38.3 29.4 48.7
38 SHC
13.79 14.36 14.92 14.12 14.65 15.48 14.49
kW
42.8 46.7 51.1 45.1 49.1 52.9 47.9
TC
39.4 32.8 25.8 45.1 38.1 28.8 47.9
41 SHC
14.29 14.90 15.67 14.66 15.43 15.80 15.20
kW
40.7 45.1 48.4 43.2 46.3 50.3 45.6
TC
38.4 32.2 24.8 43.2 36.9 27.9 45.6
46 SHC
15.30 16.42 16.65 15.76 16.30 16.96 16.18
kW

38AKS013/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
1770
2360
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
31.9 34.7 37.8 34.1 36.1 39.2 35.9
TC
31.0 25.8 19.9 34.1 29.9 22.5 35.9
29 SHC
7.23 7.47 7.71 7.42 7.59 7.82 7.57
kW
30.3 33.0 35.9 32.7 34.2 37.2 34.3
TC
30.3 25.1 19.3 32.7 29.1 21.8 34.3
35 SHC
7.87 8.14 8.43 8.10 8.28 8.56 8.28
kW
29.6 32.1 35.0 31.9 33.3 36.2 33.5
TC
29.6 24.7 18.9 31.9 28.8 21.5 33.5
38 SHC
8.19 8.47 8.78 8.44 8.61 8.91 8.62
kW
28.9 31.2 34.0 31.2 32.4 35.2 32.7
TC
28.9 24.4 18.6 31.2 28.4 21.1 32.7
41 SHC
8.50 8.79 9.13 8.78 8.93 9.26 8.96
kW
27.5 29.4 32.1 29.6 30.4 33.1 31.0
TC
27.5 23.7 17.9 29.6 27.6 20.4 31.0
46 SHC
9.13 9.42 9.80 9.44 9.56 9.93 9.64
kW

2950
19
37.0
33.5
7.66
35.9
33.4
8.69
34.1
32.3
8.69
33.2
31.8
9.02
31.2
30.8
9.67

2950
19
22
42.2 45.9
35.6 26.7
8.77 8.98
40.0 43.4
34.8 25.8
9.67 9.93
39.0 42.6
34.2 25.5
10.10 10.59
38.2 41.1
34.2 25.0
10.70 10.85
35.7 38.8
32.9 24.3
11.34 11.72

3540
19
45.2
39.5
8.85
42.9
38.7
9.77
42.2
38.8
10.42
40.7
37.9
10.66
38.5
36.9
11.51

22
49.2
26.7
9.04
46.7
26.2
10.04
45.5
25.9
10.52
44.3
25.7
10.98
41.9
25.2
11.89

2950
19
52.2
37.0
12.86
49.9
36.4
14.00
48.8
36.1
14.54
47.9
35.9
15.30
45.2
35.1
16.16

22
56.6
25.6
13.31
54.1
25.0
14.52
52.9
24.7
15.11
51.7
24.5
15.68
49.1
23.9
16.82

3540
19
55.0
44.4
13.11
52.6
43.4
14.28
51.3
42.9
14.84
50.1
42.5
15.40
47.6
41.4
16.52

22
59.7
33.6
13.57
57.0
32.7
14.81
55.7
32.2
15.42
54.3
31.8
16.01
51.6
30.9
17.19

See Legend and Notes on page 57.

55

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI (cont)
38AKS016/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2830
3780
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
50.5 55.0 59.7 54.0 57.1 61.9 56.7
TC
48.7 38.0 26.1 54.0 45.2 30.5 56.7
29 SHC
12.79 13.27 13.75 13.17 13.48 13.97 13.44
kW
48.4 53.4 57.2 52.0 54.6 59.2 54.6
TC
48.4 37.7 25.6 52.0 44.6 30.0 54.6
35 SHC
13.89 14.99 14.99 14.35 14.69 15.24 14.68
kW
47.3 51.4 56.3 51.0 53.3 57.8 53.6
TC
47.3 37.1 25.4 51.0 44.3 29.7 53.6
38 SHC
14.43 15.00 15.87 14.93 15.27 15.85 15.30
kW
46.3 50.2 54.6 50.0 52.1 56.5 52.4
TC
46.3 36.8 25.0 50.0 44.0 29.4 52.4
41 SHC
14.96 15.55 16.19 15.51 15.84 16.46 15.89
kW
44.6 48.5 52.0 47.9 50.2 53.7 50.1
TC
44.6 36.6 24.4 47.9 44.0 28.8 50.1
46 SHC
16.13 17.08 17.39 16.70 17.38 17.68 17.08
kW
38AKS024/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2120
2830
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
53.8 58.8 64.2 57.2 62.3 67.6 59.5
TC
43.1 34.1 25.0 50.9 39.9 28.2 57.3
29 SHC
16.04 16.76 17.54 16.52 17.27 18.03 16.85
kW
51.6 57.2 61.4 54.5 59.5 64.6 56.7
TC
42.2 33.7 24.2 49.8 39.0 27.4 56.6
35 SHC
17.29 18.60 18.92 17.78 18.59 19.43 18.14
kW
50.3 55.1 60.0 53.3 58.1 63.1 55.5
TC
41.7 32.9 23.7 49.3 38.6 27.0 55.5
38 SHC
17.88 18.74 19.60 18.41 19.25 20.13 18.79
kW
49.1 53.7 58.6 52.0 56.6 61.5 54.2
TC
41.3 32.5 23.3 48.7 38.2 26.6 54.2
41 SHC
18.50 19.39 20.30 19.06 19.92 20.83 19.47
kW
46.7 51.1 55.7 49.3 53.7 58.4 51.7
TC
40.4 31.6 22.5 47.5 37.4 25.9 51.7
46 SHC
19.76 20.72 21.70 20.35 21.30 22.27 20.86
kW
38AKS024/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2830
3780
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
60.2 65.7 71.5 63.3 68.8 74.8 66.7
TC
54.1 45.0 35.5 62.1 51.8 39.8 66.7
29 SHC
17.00 17.77 18.58 17.43 18.21 19.04 17.89
kW
57.6 62.9 69.5 60.6 65.6 71.3 64.1
TC
52.7 43.8 34.9 60.6 50.5 38.6 64.1
35 SHC
18.19 19.03 20.65 18.66 19.46 20.37 19.22
kW
56.8 61.4 66.9 59.3 64.0 69.6 62.7
TC
52.5 43.2 33.8 59.3 49.9 38.0 62.7
38 SHC
19.05 19.64 20.56 19.27 20.07 21.01 19.85
kW
54.8 59.9 65.3 58.1 62.4 67.8 61.3
TC
51.4 42.6 33.2 58.1 49.3 37.4 61.3
41 SHC
19.31 20.26 21.22 19.92 20.70 21.67 20.50
kW
52.1 56.8 62.0 55.6 59.1 64.3 59.4
TC
50.1 41.4 32.1 55.6 48.0 36.2 59.4
46 SHC
20.49 21.48 22.53 21.23 21.96 23.00 22.45
kW
See Legend and Notes on page 57.

56

22
63.3
34.7
14.12
60.6
34.1
15.41
59.6
34.1
16.32
57.6
33.5
16.62
54.7
33.0
17.84

38AKS024/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
3540
4720
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
64.1 69.9 76.1 68.6 72.6 78.8 72.2
TC
62.1 51.6 39.9 68.6 59.8 45.0 72.2
29 SHC
17.96 18.80 19.69 18.60 19.20 20.09 19.11
kW
62.2 66.6 72.5 65.9 69.2 75.1 69.3
TC
62.0 50.3 38.7 65.9 58.4 43.8 69.3
35 SHC
19.94 20.08 21.05 19.95 20.52 21.46 20.49
kW
60.0 65.4 70.8 64.5 67.5 73.3 67.8
TC
60.0 50.0 38.1 64.5 57.8 43.2 67.8
38 SHC
19.82 20.92 21.72 20.61 21.16 22.17 21.19
kW
58.5 63.4 69.1 63.1 65.8 71.5 66.3
TC
58.5 49.1 37.5 63.1 57.2 42.6 66.3
41 SHC
20.43 21.38 22.41 21.30 21.83 22.87 21.90
kW
56.8 60.1 65.5 60.3 62.2 68.9 63.2
TC
56.8 47.8 36.3 60.3 55.8 41.7 63.2
46 SHC
22.37 22.62 23.74 22.65 23.07 24.94 23.25
kW

22
69.9
31.3
18.35
66.7
30.6
19.77
65.1
30.2
20.48
63.5
29.8
21.21
60.1
29.1
22.64

38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
2830
3780
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
75.4 82.6 90.3 80.3 87.6 95.4 83.4
TC
60.2 48.3 36.1 71.3 56.2 40.6 80.6
29 SHC
21.83 22.91 24.02 22.58 23.64 24.76 23.05
kW
72.0 79.0 86.4 76.6 83.7 91.1 79.6
TC
58.9 47.0 34.9 69.8 55.0 39.5 79.6
35 SHC
23.31 24.51 25.75 24.13 25.32 26.55 24.63
kW
70.3 77.2 84.4 74.6 81.7 89.0 77.7
TC
58.2 46.4 34.4 69.0 54.4 39.0 77.7
38 SHC
24.04 25.28 26.58 24.85 26.12 27.40 25.39
kW
68.6 75.3 82.4 72.8 79.6 86.8 76.2
TC
57.6 45.8 33.8 68.4 53.8 38.4 76.2
41 SHC
24.80 26.11 27.46 25.62 26.96 28.31 26.27
kW
65.2 71.6 78.3 69.1 75.4 82.2 72.8
TC
56.3 44.7 32.6 66.8 52.6 37.3 72.8
46 SHC
26.26 27.68 29.15 27.11 28.52 29.99 27.95
kW

22
76.8
43.6
19.32
73.1
42.4
20.66
71.3
41.8
21.32
69.5
41.2
21.99
65.9
40.0
23.32

38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
3540
4720
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
77.1 84.3 91.7 81.3 88.3 95.8 85.2
TC
67.1 53.1 38.5 78.8 62.1 43.8 85.2
29 SHC
22.01 23.07 24.15 22.65 23.67 24.75 23.20
kW
73.7 80.4 87.6 77.5 84.2 91.4 81.8
TC
65.8 51.8 37.4 77.5 60.9 42.8 81.8
35 SHC
23.52 24.68 25.87 24.18 25.34 26.51 24.90
kW
71.9 78.6 85.5 75.7 82.1 89.2 80.1
TC
65.1 51.3 36.9 75.7 60.3 42.3 80.1
38 SHC
24.25 25.47 26.71 24.94 26.12 27.39 25.75
kW
70.2 76.6 83.4 74.1 80.0 86.8 78.3
TC
64.4 50.7 36.3 74.1 59.7 41.7 78.3
41 SHC
25.01 26.27 27.57 25.76 26.93 28.24 26.61
kW
66.5 72.7 79.1 70.8 75.7 82.2 74.7
TC
63.0 49.5 35.3 70.8 58.5 40.7 74.7
46 SHC
26.45 27.84 29.26 27.41 28.49 29.92 28.27
kW

4720
19
58.5
51.8
13.64
55.9
51.0
14.85
54.6
50.6
15.43
53.3
50.2
16.01
50.5
49.1
17.15

3540
19
64.6
45.2
17.59
61.6
44.4
18.95
60.1
43.9
19.62
58.6
43.5
20.29
55.4
42.6
21.64

4720
19
70.8
57.9
18.48
67.4
56.6
19.75
65.8
56.0
20.37
64.1
55.2
21.00
60.8
53.9
22.29

5900
19
74.5
67.2
19.49
70.8
65.6
20.76
69.0
64.9
21.41
67.3
64.1
22.09
63.6
62.3
23.34

22
80.7
49.8
20.37
76.8
48.5
21.77
74.9
47.9
22.43
72.9
47.3
23.14
68.9
46.1
24.44

4720
19
90.9
63.7
24.14
86.6
62.5
25.80
84.4
61.9
26.60
82.2
61.2
27.46
77.8
60.0
29.06

22
98.8
45.0
25.26
94.1
44.0
27.05
91.8
43.4
27.92
89.5
42.9
28.81
84.7
41.7
30.52

5900
19
91.0
70.6
24.06
86.6
69.4
25.71
84.4
68.7
26.52
82.1
68.1
27.34
77.7
66.8
28.94

22
98.6
48.9
25.15
93.8
47.9
26.92
91.4
47.4
27.77
89.0
46.8
28.65
84.2
45.7
30.35

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI (cont)
38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
81.9 89.4 97.2 86.8 93.1 101.0 91.6
TC
76.0 60.0 42.9 86.8 70.8
49.3 91.6
29 SHC
22.84 23.92 25.03 23.51 24.46 25.57 24.21
kW
78.2 85.3 92.8 83.4 88.7 96.2 87.8
TC
74.8 58.8 41.8 83.4 69.5 48.1 87.8
35 SHC
24.40 25.59 26.84 25.26 26.15 27.39 25.98
kW
76.2 83.1 90.6 81.7 86.4 93.8 85.9
TC
73.8 58.2 41.3 81.7 68.9 47.6 85.9
38 SHC
25.14 26.38 27.70 26.10 26.97 28.27 26.84
kW
74.3 81.0 88.2 79.9 84.2 91.4 84.0
TC
72.7 57.6 40.7 79.9 68.3 47.1 84.0
41 SHC
25.92 27.22 28.58 26.99 27.83 29.18 27.77
kW
70.6 76.7 83.6 76.2 79.7 86.5 80.1
TC
70.6 56.3 39.6 76.2 67.0 46.0 80.1
46 SHC
27.44 28.82 30.28 28.68 29.46 30.91 29.54
kW
38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
3540
4720
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
82.0 89.5 97.4 86.3 93.9 101.8 89.9
TC
69.0 54.8 40.1 81.1 63.7
45.3 89.9
29 SHC
23.75 24.89 26.04 24.40 25.54 26.70 24.96
kW
78.5 85.7 93.3 82.7 89.8 97.4 86.5
TC
67.6 53.5 39.0 79.6 62.5 44.2 86.5
35 SHC
25.19 26.45 27.75 25.93 27.17 28.43 26.59
kW
76.7 83.8 91.1 80.8 87.8 95.2 84.8
TC
66.9 52.9 38.4 78.7 62.0 43.7 84.8
38 SHC
25.88 27.20 28.55 26.67 27.94 29.27 27.39
kW
74.9 81.8 88.9 78.7 85.6 92.9 83.0
TC
66.3 52.3 37.8 78.7 61.4 43.1 83.0
41 SHC
26.61 27.98 29.38 27.39 28.74 30.13 28.22
kW
71.2 77.7 84.5 75.0 81.2 88.2 79.4
TC
64.9 51.0 36.7 75.0 60.1 42.1 79.4
46 SHC
27.99 29.48 31.00 28.88 30.27 31.81 29.86
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (kW) Gross
Total Capacity (kW) Gross

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.

2. SHC is based on 26.7 C db air entering indoor coil.

22
103.4
55.3
25.92
98.5
54.3
27.76
96.0
53.7
28.66
93.5
53.2
29.59
88.4
52.1
31.32

38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
87.2 95.0 103.1 91.6 99.2 107.4 96.6
TC
78.5 61.7
44.4 91.6 72.5
50.8 96.6
29 SHC
24.55 25.70 26.90 25.21 26.34 27.53 25.95
kW
83.4 90.9 98.7 88.1 94.7 102.6 93.0
TC
76.9 60.5 43.3 88.1 71.3
49.7 93.0
35 SHC
26.07 27.35 28.66 26.87 27.99 29.32 27.72
kW
81.5 88.9 96.5 86.4 92.5 100.2 91.1
TC
76.2 59.9 42.7 86.4 70.6
49.1 91.1
38 SHC
26.88 28.15 29.51 27.69 28.80 30.17 28.56
kW
79.6 86.7 94.2 84.6 90.1 97.7 89.1
TC
75.4 59.3 42.1 84.6 70.0 48.6 89.1
41 SHC
27.57 28.97 30.40 28.55 29.63 31.06 29.42
kW
75.5 82.2 89.5 81.0 85.4 92.6 85.1
TC
73.5 58.0 41.0 81.0 68.7 47.4 85.1
46 SHC
28.99 30.49 32.08 30.21 31.18 32.75 31.11
kW

22
104.8
50.4
27.15
100.2
49.3
28.90
97.8
48.8
29.76
95.4
48.3
30.63
90.4
47.1
32.29

38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s
Temp (C)
4250
5660
Air Entering
Condenser
Evaporator Air — Ewb (C)
(Edb)
17
19
22
17
19
22
17
101.8 110.9 120.4 107.5 116.6 126.2 111.3
TC
84.1 66.8 49.1 99.1 77.7 55.4 111.3
29 SHC
33.03 34.90 36.81 34.20 36.06 38.02 34.97
kW
97.8 106.5 115.7 102.9 111.7 120.9 107.1
TC
82.6
65.4 47.8 97.1 76.2 54.1 107.1
35 SHC
34.80 36.76 38.83 35.94 37.95 40.03 36.90
kW
95.8 104.3 113.2 100.7 109.3 118.2 105.2
TC
81.8
64.7 47.2 96.2 75.5 53.4 105.2
38 SHC
35.71 37.74 39.87 36.87 38.91 41.05 37.96
kW
93.7 102.1 110.8 98.6 106.8 115.5 103.1
TC
81.0
64.0 46.5 95.2
74.8 52.8 103.1
41 SHC
36.56 38.69 40.89 37.78 39.85 42.05 38.93
kW
89.4 97.3 105.6 93.8 101.7 109.9 98.8
TC
79.4 62.5
45.1 93.8
73.3 51.4 98.8
46 SHC
38.19 40.43 42.74 39.46 41.63 43.95 40.85
kW

7080
19
95.6
80.7
24.82
91.0
79.4
26.54
88.7
78.7
27.38
86.3
77.9
28.24
81.5
76.4
29.85

5900
19
96.9
72.3
25.98
92.6
71.1
27.65
90.4
70.5
28.43
88.1
69.8
29.23
83.4
68.5
30.76

7080
19
101.8
82.6
26.72
97.2
81.2
28.39
94.8
80.6
29.21
92.4
79.9
30.06
87.6
78.4
31.66

22
110.0
56.8
27.91
105.1
55.7
29.73
102.6
55.2
30.58
100.0
54.6
31.49
94.8
53.5
33.21

7080
19
120.2
87.8
36.77
115.1
86.4
38.70
112.5
85.7
39.69
109.9
85.0
40.65
104.6
83.5
42.46

22
129.9
61.4
38.73
124.3
60.1
40.79
121.4
59.5
41.83
118.6
58.8
42.84
112.8
57.5
44.79

3. Formulas:
SHCkW x 1000
1.23 x L/s
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCkW x 1000
Ldb C: hlwb = hewb –
1.20 x L/s
Ldb C = Edb C –

where hewb = enthalpy of air entering evaporator coil (kj/kg).
4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
piping sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

57

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH
38AK007/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
61.7 67.4 73.4 64.9 70.5 76.6 68.5
TC
55.6 46.4 36.7 64.7 53.4 41.0 68.5
85 SHC
4.93 5.16 5.40 5.06 5.29 5.53 5.21
kW
58.6 64.3 70.2 62.1 67.1 73.1 66.8
TC
54.2 45.1 35.5 62.1 52.0 39.7 66.8
95 SHC
5.19 5.45 5.72 5.35 5.58 5.85 5.69
kW
57.2 62.6 68.5 60.8 65.4 71.2 64.2
TC
53.4 44.5 34.8 60.8 51.4 39.1 64.2
100 SHC
5.31 5.59 5.87 5.49 5.72 6.00 5.67
kW
55.6 61.0 66.7 59.4 63.6 69.4 62.7
TC
52.7 43.8 34.2 59.4 50.7 38.5 62.7
105 SHC
5.44 5.73 6.02 5.64 5.87 6.16 5.82
kW
52.5 57.5 63.0 56.5 60.0 65.5 59.7
TC
51.0 42.4 32.9 56.5 49.3 37.2 59.7
115 SHC
5.69 5.99 6.31 5.93 6.14 6.46 6.12
kW
38AK007/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
65.8 71.7 78.1 70.5 74.6 80.9 74.1
TC
63.8 53.0 41.0 70.5 61.5 46.3 74.1
85 SHC
5.11 5.35 5.60 5.29 5.47 5.72 5.43
kW
62.7 68.3 74.5 67.6 71.0 77.2 71.2
TC
62.7 51.7 39.7 67.6 60.2 45.0 71.2
95 SHC
5.39 5.65 5.92 5.61 5.77 6.05 5.77
kW
61.3 66.6 72.6 66.2 69.2 75.2 69.6
TC
61.3 51.0 39.1 66.2 59.4 44.4 69.6
100 SHC
5.53 5.79 6.08 5.77 5.92 6.21 5.93
kW
59.9 64.8 70.7 64.6 67.2 73.2 67.9
TC
59.9 50.3 38.5 64.6 58.7 43.7 67.9
105 SHC
5.68 5.94 6.24 5.93 6.07 6.37 6.09
kW
57.0 61.1 61.1 61.5 63.3 63.3 64.5
TC
57.0 49.0 49.0 61.5 57.1 57.1 64.5
115 SHC
5.97 6.22 6.22 6.24 6.34 6.34 6.41
kW
38AK008/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
73.8 80.2 86.9 77.8 84.3 91.1 80.6
TC
61.4 51.8 41.9 70.9 58.9 46.2 79.1
85 SHC
6.01 6.18 6.35 6.11 6.29 6.47 6.19
kW
70.9 77.1 83.6 74.6 80.9 87.5 77.3
TC
60.0 50.5 40.6 69.3 57.5 44.9 77.3
95 SHC
6.49 6.67 6.85 6.60 6.77 6.97 6.67
kW
69.3 75.4 81.9 73.1 79.1 85.6 75.8
TC
59.3 49.8 40.0 68.5 56.8 44.2 75.8
100 SHC
6.73 6.91 7.10 6.85 7.02 7.22 6.92
kW
67.8 73.7 79.9 71.4 77.3 83.6 74.2
TC
58.5 49.1 39.2 67.7 56.1 43.5 74.2
105 SHC
6.99 7.17 7.35 7.10 7.28 7.47 7.18
kW
64.5 70.2 76.1 67.8 73.4 79.5 71.0
TC
57.0 47.6 37.7 65.9 54.5 42.0 71.0
115 SHC
7.54 7.71 7.90 7.64 7.82 8.02 7.74
kW
See Legend and Notes on page 63.

58

72
78.6
45.0
5.61
75.0
43.7
5.94
73.1
43.1
6.09
71.1
42.4
6.25
67.1
41.1
6.55

38AK008/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
79.3 86.0 93.1 83.3 89.8 97.0 87.2
TC
70.5 58.7 46.3 81.4 67.3 51.6 87.2
85 SHC
6.18 6.36 6.55 6.28 6.47 6.66 6.39
kW
76.2 82.7 89.5 79.8 86.1 93.0 84.1
TC
69.1 57.3 44.9 79.8 65.9 50.2 84.1
95 SHC
6.68 6.86 7.06 6.77 6.96 7.17 6.90
kW
74.5 80.9 87.6 78.3 84.1 91.0 82.5
TC
68.2 56.6 44.2 78.3 65.1 49.5 82.5
100 SHC
6.93 7.11 7.31 7.03 7.21 7.42 7.15
kW
72.7 79.0 85.6 76.7 82.1 88.8 80.7
TC
67.4 55.8 43.5 76.7 64.3 48.7 80.7
105 SHC
7.19 7.37 7.57 7.29 7.46 7.67 7.41
kW
69.1 75.0 81.3 73.4 77.9 84.2 77.1
TC
65.8 54.2 41.9 73.4 62.7 47.2 77.1
115 SHC
7.73 7.91 8.12 7.86 8.01 8.21 7.97
kW

72
82.8
51.2
5.79
78.8
49.9
6.12
76.8
49.2
6.28
74.6
48.5
6.44
64.9
63.7
6.43

38AK008/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
87.5 92.9 100.3 93.2 96.1 102.9 97.3
TC
87.0 71.2
54.1 93.2 82.2
60.8 97.3
85 SHC
6.44 6.58 6.79 6.59 6.67 6.86 6.71
kW
84.3 89.1 96.1 89.9 92.0 98.6 93.6
TC
84.3 69.7 52.6 89.9 80.7 59.4 93.6
95 SHC
6.96 7.08 7.29 7.11 7.17 7.37 7.22
kW
82.6 87.1 93.9 88.1 89.9 96.4 91.7
TC
82.6 69.0 51.9 88.1 79.8 58.6 91.7
100 SHC
7.20 7.33 7.55 7.37 7.42 7.62 7.47
kW
80.9 85.0 91.6 86.2 87.7 94.0 89.6
TC
80.9 68.2 51.1 86.2 78.9 57.8 89.6
105 SHC
7.47 7.59 7.81 7.63 7.68 7.87 7.74
kW
77.3 80.6 86.9 82.1 83.1 88.9 85.4
TC
77.3 66.5 49.5 82.1 77.2 56.2 85.4
115 SHC
8.03 8.14 8.36 8.19 8.22 8.42 8.30
kW

72
93.8
50.2
6.55
90.1
48.9
7.05
88.1
48.2
7.30
86.0
47.5
7.55
81.5
46.0
8.08

38AK012/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
94.1 102.3 111.0 99.4 107.7 116.4 103.0
TC
77.7
65.1 52.3 89.8
74.2 57.8 100.3
85 SHC
7.78 8.04 8.32 7.95 8.22 8.51 8.07
kW
90.8 98.7 107.0 95.6 103.6 112.1 99.0
TC
76.0 63.5 50.7 88.0
72.6 56.2 99.0
95 SHC
8.40 8.66 8.95 8.56 8.83 9.13 8.68
kW
89.1 96.8 104.9 93.7 101.5 109.7 97.1
TC
75.2 62.7
49.9 87.1
71.7 55.4 97.1
100 SHC
8.73 8.98 9.27 8.87 9.14 9.44 9.00
kW
87.2 95.2 102.7 91.7 99.3 107.3 95.2
TC
74.3 62.1
49.1 86.2 70.8
54.5 95.2
105 SHC
9.05 9.41 9.59 9.20 9.46 9.76 9.32
kW
83.4 90.5 98.0 87.7 94.7 103.6 91.4
TC
72.5 60.1 47.2 84.3 69.1
53.4 91.4
115 SHC
9.77 10.00 10.27 9.92 10.16 10.71 10.03
kW

3000
67
72.5
59.8
5.37
69.0
58.4
5.67
67.3
57.7
5.82
65.5
57.0
5.96
61.6
55.3
6.23

3750
67
76.4
69.1
5.54
72.7
67.4
5.85
70.8
66.7
5.99
68.8
65.7
6.14
64.9
63.7
6.43

3000
67
87.0
65.4
6.36
83.5
64.0
6.85
81.5
63.2
7.10
79.6
62.5
7.35
75.4
60.9
7.88

3750
67
92.2
75.3
6.53
88.3
73.7
7.02
86.3
73.1
7.28
84.2
72.2
7.53
79.9
70.4
8.08

72
99.4
56.5
6.72
95.3
55.1
7.24
93.1
54.4
7.49
90.9
53.6
7.74
86.2
52.1
8.29

5000
67
98.3
92.1
6.73
94.3
90.1
7.23
92.1
89.3
7.49
89.9
88.3
7.75
85.4
85.4
8.30

72
104.8
67.4
6.91
100.4
66.0
7.42
98.0
65.2
7.67
95.5
64.5
7.92
90.3
62.8
8.46

3750
67
111.2
82.6
8.34
106.9
80.9
8.95
104.7
80.1
9.26
102.3
79.2
9.58
97.4
77.4
10.26

72
120.0
63.0
8.63
115.4
61.4
9.25
113.0
60.6
9.56
110.5
59.8
9.88
105.2
58.0
10.55

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH (cont)
38AK012/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
105.4 113.4 122.5 110.9 117.6 126.7 113.9
TC
95.9 78.8 61.3 110.9 90.3 68.3 113.9
85 SHC
7.92 8.18 8.47 8.10 8.32 8.62 7.55
kW
101.5 109.1 117.9 107.2 112.9 121.7 112.5
TC
94.0 77.1 59.6 107.2 88.6 66.6 112.5
95 SHC
8.53 8.77 9.08 8.71 8.90 9.21 8.89
kW
99.4 106.8 115.4 105.3 110.4 118.9 110.3
TC
93.0
76.2 58.7 105.3 87.7 65.6 110.3
100 SHC
8.83 9.08 9.38 9.03 9.20 9.51 9.20
kW
97.3 104.4 112.8 103.8 107.8 116.2 108.1
TC
91.9
75.2 57.7 103.8 86.9 64.7 108.1
105 SHC
9.14 9.39 9.69 9.47 9.50 9.81 9.51
kW
92.9 99.4 108.8 99.0 102.6 110.4 103.4
TC
89.8 73.3
56.5 99.0
84.8 62.8 103.4
115 SHC
9.83 10.05 10.63 10.04 10.17 10.46 10.20
kW
38AK012/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
110.7 119.4 128.8 117.5 123.5 132.9 122.9
TC
85 SHC 107.1 88.2 67.8 117.5 102.0 76.3 122.9
8.06 8.35 8.66 8.28 8.49 8.80 8.46
kW
106.4 114.7 123.7 113.4 118.7 127.7 118.7
TC
95 SHC 104.5 86.3 66.0 113.4 100.1 74.5 118.7
8.65 8.94 9.26 8.89 9.08 9.40 9.08
kW
104.1 112.2 121.1 111.3 116.1 124.9 116.5
TC
100 SHC 104.1 85.3 65.1 111.3 99.1 73.6 116.5
8.96 9.24 9.56 9.20 9.38 9.71 9.39
kW
102.7 109.7 118.3 109.6 113.5 122.0 114.1
TC
105 SHC 102.7 84.3 64.0 109.6 98.0 72.7 114.1
9.41 9.55 9.87 9.67 9.69 10.01 9.71
kW
97.9 104.4 112.7 104.5 107.8 115.9 109.0
TC
97.9
82.3 62.1 104.5 95.7 70.6 109.0
115 SHC
9.99 10.23 10.53 10.22 10.35 10.67 10.39
kW
38AKS008/40RM007 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
1800
2400
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
71.5 78.4 85.6 75.7 82.7 90.0 78.6
TC
60.3 51.0 41.4 69.8 58.2 45.8 78.6
85 SHC
5.40 5.60 5.79 5.53 5.72 5.90 5.61
kW
68.3 74.9 81.9 72.4 79.0 86.0 75.3
TC
58.8 49.5 39.9 68.2 56.7 44.3 75.3
95 SHC
5.82 6.06 6.29 5.97 6.20 6.42 6.07
kW
66.7 73.2 80.0 70.6 77.1 84.0 73.7
TC
58.0 48.8 39.1 67.4 55.9 43.6 73.7
100 SHC
6.02 6.28 6.53 6.18 6.43 6.67 6.30
kW
65.1 71.4 78.1 68.9 75.2 81.9 72.2
TC
57.2 48.0 38.4 66.5 55.2 42.9 72.2
105 SHC
6.22 6.49 6.76 6.38 6.65 6.91 6.52
kW
61.8 67.8 74.2 65.1 71.1 77.7 69.0
TC
55.6 46.5 36.9 65.1 53.6 41.4 69.0
115 SHC
6.63 6.93 7.23 6.79 7.09 7.40 6.99
kW

72
129.4
75.1
8.70
124.2
73.4
9.30
121.4
72.5
9.60
118.6
71.5
9.90
112.6
69.6
10.54

38AKS008/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
77.3 84.5 92.1 81.3 88.5 96.3 86.0
TC
69.6 58.0 45.9 81.3 66.8 51.4 86.0
85 SHC
5.61 5.81 6.00 5.72 5.92 6.11 5.84
kW
73.7 80.8 88.2 78.0 84.3 91.8 82.5
TC
67.9 56.5 44.4 78.0 65.2 49.8 82.5
95 SHC
6.06 6.30 6.53 6.20 6.41 6.65 6.35
kW
72.0 78.8 86.1 76.3 82.2 89.6 80.7
TC
67.0 55.7 43.7 76.3 64.4 49.0 80.7
100 SHC
6.27 6.53 6.79 6.43 6.65 6.90 6.59
kW
70.1 76.8 84.0 74.7 80.1 87.3 78.9
TC
66.2 54.9 42.9 74.7 63.5 48.2 78.9
105 SHC
6.48 6.75 7.03 6.67 6.88 7.15 6.83
kW
66.4 72.7 79.6 71.3 75.8 82.7 75.3
TC
64.3 53.3 41.3 71.3 61.9 46.6 75.3
115 SHC
6.90 7.21 7.52 7.14 7.36 7.66 7.33
kW

72
135.7
84.3
8.89
130.2
82.5
9.50
127.3
81.5
9.80
124.3
80.6
10.10
118.0
78.5
10.74

38AKS008/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
85.9 91.7 99.6 92.2 95.0 102.6 96.5
TC
85.9 70.7 53.8 92.2 81.7
60.6 96.5
85 SHC
5.88 6.03 6.22 6.04 6.11 6.28 6.15
kW
82.5 87.4 95.0 88.4 90.5 97.6 92.4
TC
82.5 69.1 52.1 88.4 80.0 59.0 92.4
95 SHC
6.38 6.54 6.77 6.57 6.64 6.85 6.69
kW
80.8 85.2 92.6 86.5 88.2 95.2 90.3
TC
80.8 68.3 51.3 86.5 79.1 58.2 90.3
100 SHC
6.62 6.78 7.03 6.83 6.88 7.11 6.95
kW
79.0 83.1 90.2 84.5 85.9 92.6 88.2
TC
79.0 67.4 50.5 84.5 78.0 57.4 88.2
105 SHC
6.86 7.02 7.29 7.08 7.12 7.37 7.21
kW
75.3 78.5 85.3 80.4 81.3 87.4 83.9
TC
75.3 65.6 48.9 80.4 76.3 55.7 83.9
115 SHC
7.35 7.50 7.81 7.58 7.62 7.89 7.74
kW

72
93.0
49.9
5.98
88.8
48.4
6.51
86.6
47.7
6.76
84.4
46.9
7.00
79.9
45.3
7.49

38AKS009/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
89.1 97.7 106.7 94.2 103.0 112.2 98.0
TC
75.2 63.5
51.5 87.1
72.6 57.0 98.0
85 SHC
7.21 7.52 7.82 7.40 7.70 8.01 7.54
kW
84.9 93.2 101.9 89.9 98.1 107.0 93.7
TC
73.2 61.6
49.5 85.0 70.6
55.1 93.7
95 SHC
7.73 8.08 8.43 7.94 8.28 8.62 8.10
kW
82.7 90.9 99.4 87.6 95.7 104.3 91.6
TC
72.1 60.7 48.6 83.9 69.6
54.1 91.6
100 SHC
7.98 8.35 8.72 8.21 8.56 8.93 8.38
kW
80.6 88.5 96.9 85.3 93.2 101.7 89.6
TC
71.1 59.7 47.6 82.6 68.6
53.2 89.6
105 SHC
8.24 8.63 9.02 8.48 8.86 9.24 8.67
kW
76.3 83.8 91.8 80.6 88.0 96.1 85.4
TC
69.1 57.7 45.7 80.6 66.6 51.2 85.4
115 SHC
8.75 9.17 9.60 8.99 9.40 9.84 9.26
kW

5000
67
120.5
101.3
8.41
115.7
99.3
9.00
113.2
98.5
9.30
110.6
97.4
9.60
105.3
95.2
10.27

6250
67
126.5
114.8
8.59
121.2
112.2
9.17
118.5
111.1
9.47
115.8
109.8
9.77
109.9
106.9
10.43

3000
67
85.6
64.8
5.80
81.6
63.3
6.28
79.5
62.4
6.51
77.5
61.7
6.74
73.3
60.0
7.20

3750
67
91.1
74.8
5.98
86.7
73.1
6.49
84.6
72.3
6.74
82.4
71.4
6.97
77.8
69.5
7.45

72
98.9
56.3
6.17
94.3
54.8
6.72
91.9
54.0
6.98
89.5
53.2
7.24
84.7
51.6
7.76

5000
67
97.5
91.7
6.17
92.9
89.8
6.71
90.6
88.5
6.96
88.4
87.4
7.22
83.9
83.9
7.74

72
104.7
67.3
6.33
99.5
65.7
6.90
96.9
64.8
7.16
94.3
64.0
7.42
88.9
62.4
7.95

3750
67
106.7
80.8
7.83
101.4
78.8
8.42
98.8
77.8
8.70
96.1
76.7
8.99
90.6
74.7
9.54

72
115.9
62.1
8.13
110.4
60.2
8.76
107.6
59.3
9.07
104.7
58.2
9.37
98.8
56.2
9.98

See Legend and Notes on page 63.

59

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH (cont)
38AKS009/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
99.3 107.5 117.3 105.8 111.8 121.5 111.5
TC
92.8
76.7 59.6 105.8 88.2 66.6 111.5
85 SHC
7.75 8.04 8.36 7.97 8.17 8.49 8.17
kW
94.6 102.4 111.8 101.5 106.2 115.4 106.6
TC
90.5
74.5 57.6 101.5 86.2 64.5 106.6
95 SHC
8.30 8.62 8.99 8.58 8.76 9.12 8.78
kW
92.3 99.7 108.9 99.1 103.5 112.3 104.2
TC
89.4 73.5
56.6 99.1
85.0 63.5 104.2
100 SHC
8.58 8.91 9.30 8.88 9.06 9.44 9.10
kW
90.0 97.0 105.9 96.8 100.7 109.3 101.8
TC
88.2 72.6
55.5 96.8
83.9 62.5 101.8
105 SHC
8.87 9.20 9.61 9.19 9.37 9.76 9.42
kW
85.6 91.6 100.0 92.1 95.1 103.1 96.7
TC
85.6 70.4
53.5 92.1 81.7
60.3 96.7
115 SHC
9.43 9.75 10.20 9.78 9.95 10.36 10.03
kW
38AKS012/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
89.1 97.7 106.7 94.2 103.0 112.2 98.0
TC
75.2 63.5
51.5 87.1
72.6 57.0 98.0
85 SHC
7.21 7.52 7.82 7.40 7.70 8.01 7.54
kW
84.9 93.2 101.9 89.9 98.1 107.0 93.7
TC
73.2 61.6
49.5 85.0 70.6
55.1 93.7
95 SHC
7.73 8.08 8.43 7.94 8.28 8.62 8.10
kW
82.7 90.9 99.4 87.6 95.7 104.3 91.6
TC
72.1 60.7 48.6 83.9 69.6
54.1 91.6
100 SHC
7.98 8.35 8.72 8.21 8.56 8.93 8.38
kW
80.6 88.5 96.9 85.3 93.2 101.7 89.6
TC
71.1 59.7 47.6 82.6 68.6
53.2 89.6
105 SHC
8.24 8.63 9.02 8.48 8.86 9.24 8.67
kW
76.3 83.8 91.8 80.6 88.0 96.1 85.4
TC
69.1 57.7 45.7 80.6 66.6 51.2 85.4
115 SHC
8.75 9.17 9.60 8.99 9.40 9.84 9.26
kW
38AKS012/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
99.3 107.5 117.3 105.8 111.8 121.5 111.5
TC
92.8
76.7 59.6 105.8 88.2 66.6 111.5
85 SHC
7.75 8.04 8.36 7.97 8.17 8.49 8.17
kW
94.6 102.4 111.8 101.5 106.2 115.4 106.6
TC
90.5
74.5 57.6 101.5 86.2 64.5 106.6
95 SHC
8.30 8.62 8.99 8.58 8.76 9.12 8.78
kW
92.3 99.7 108.9 99.1 103.5 112.3 104.2
TC
89.4 73.5
56.6 99.1
85.0 63.5 104.2
100 SHC
8.58 8.91 9.30 8.88 9.06 9.44 9.10
kW
90.0 97.0 105.9 96.8 100.7 109.3 101.8
TC
88.2 72.6
55.5 96.8
83.9 62.5 101.8
105 SHC
8.87 9.20 9.61 9.19 9.37 9.76 9.42
kW
85.6 91.6 100.0 92.1 95.1 103.1 96.7
TC
85.6 70.4
53.5 92.1 81.7
60.3 96.7
115 SHC
9.43 9.75 10.20 9.78 9.95 10.36 10.03
kW
See Legend and Notes on page 63.

60

72
124.2
73.4
8.57
118.0
71.3
9.22
114.9
70.3
9.54
111.7
69.2
9.86
105.4
67.3
10.48

38AKS012/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
104.9 113.9 124.2 112.7 118.4 128.5 118.6
TC
85 SHC 103.9 90.2 75.1 112.7 102.7 83.2 118.6
7.84 8.16 8.48 8.10 8.31 8.64 8.30
kW
100.1 108.3 118.0 107.9 112.4 122.1 113.3
TC
95 SHC 100.1 87.4 72.3 107.9 99.9 80.3 113.3
8.43 8.78 9.14 8.75 8.95 9.31 8.96
kW
97.9 105.4 115.0 105.5 109.4 118.9 110.6
TC
97.9
86.1 71.0 105.5 98.4 78.9 110.6
100 SHC
8.75 9.09 9.48 9.07 9.26 9.65 9.29
kW
95.6 102.6 111.9 103.0 106.3 115.6 108.0
TC
95.6
84.8 69.6 103.0 96.9 77.4 108.0
105 SHC
9.06 9.40 9.81 9.40 9.57 9.98 9.63
kW
91.1 96.7 105.6 97.8 100.0 108.8 102.5
TC
91.1 82.0
66.9 97.8
93.8 74.6 102.5
115 SHC
9.65 9.98 10.45 10.02 10.15 10.61 10.26
kW

72
115.9
62.1
8.13
110.4
60.2
8.76
107.6
59.3
9.07
104.7
58.2
9.37
98.8
56.2
9.98

38AKS013/40RM008 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
2250
3000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
92.5 101.5 111.1 98.2 107.4 117.2 102.3
TC
76.9
65.3 53.3 89.1
74.4 58.9 99.5
85 SHC
6.81 7.06 7.30 6.97 7.21 7.45 7.08
kW
88.1 96.9 106.2 93.5 102.4 111.7 97.2
TC
74.8 63.3
51.3 86.7
72.3 56.9 97.2
95 SHC
7.37 7.66 7.95 7.55 7.83 8.12 7.67
kW
86.0 94.5 103.6 91.2 99.8 109.0 95.0
TC
73.8 62.3
50.3 85.7 71.3
55.9 95.0
100 SHC
7.64 7.96 8.26 7.84 8.14 8.44 7.97
kW
83.7 92.1 101.0 88.8 97.3 106.3 92.8
TC
72.7 61.2
49.3 84.5 70.3
54.9 92.8
105 SHC
7.90 8.24 8.57 8.11 8.44 8.76 8.26
kW
79.3 87.2 95.7 83.9 91.8 100.5 88.5
TC
70.5 59.2 47.2 81.9 68.2
52.9 88.5
115 SHC
8.44 8.82 9.19 8.66 9.03 9.40 8.87
kW

72
124.2
73.4
8.57
118.0
71.3
9.22
114.9
70.3
9.54
111.7
69.2
9.86
105.4
67.3
10.48

38AKS013/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
103.3 112.0 122.1 109.4 116.5 126.6 115.5
TC
94.8 78.3 61.3 109.4 89.8 68.4 115.5
85 SHC
7.08 7.30 7.54 7.23 7.40 7.64 7.38
kW
98.3 106.6 116.3 105.0 110.6 120.3 110.5
TC
92.3
76.1 59.2 105.0 87.8 66.2 110.5
95 SHC
7.68 7.94 8.23 7.89 8.06 8.33 8.05
kW
95.9 103.8 113.3 102.6 107.8 117.1 108.0
TC
91.3
75.1 58.1 102.6 86.8 65.1 108.0
100 SHC
7.98 8.25 8.56 8.21 8.38 8.67 8.38
kW
93.4 101.0 110.3 100.2 104.9 113.9 105.4
TC
90.0
74.0 57.1 100.2 85.6 64.0 105.4
105 SHC
8.27 8.55 8.88 8.53 8.69 9.00 8.71
kW
88.6 95.2 104.0 95.3 99.0 107.3 100.2
TC
87.3 71.8
54.9 95.3 83.2
61.8 100.2
115 SHC
8.86 9.15 9.52 9.16 9.31 9.65 9.37
kW

5000
67
115.0
98.8
8.27
109.3
96.6
8.89
106.6
95.5
9.20
103.7
94.3
9.51
97.9
91.9
10.09

3750
67
106.7
80.8
7.83
101.4
78.8
8.42
98.8
77.8
8.70
96.1
76.7
8.99
90.6
74.7
9.54

5000
67
115.0
98.8
8.27
109.3
96.6
8.89
106.6
95.5
9.20
103.7
94.3
9.51
97.9
91.9
10.09

6250
67
121.2
113.6
8.41
115.1
110.4
9.04
111.9
108.6
9.35
108.7
106.7
9.67
102.7
102.7
10.27

72
131.4
90.3
8.74
124.7
87.5
9.41
121.3
86.0
9.74
117.9
84.6
10.08
110.9
81.6
10.71

3750
67
111.4
82.7
7.31
106.1
80.6
7.95
103.3
79.5
8.26
100.4
78.5
8.55
94.7
76.3
9.15

72
121.3
64.1
7.54
115.6
62.1
8.23
112.7
61.1
8.57
109.6
60.0
8.88
103.5
57.9
9.52

5000
67
119.9
100.9
7.48
113.9
98.5
8.15
111.0
97.4
8.48
108.0
96.1
8.80
101.7
93.8
9.43

72
129.6
75.2
7.70
123.1
72.9
8.41
119.8
71.9
8.76
116.5
70.8
9.09
109.7
68.6
9.75

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH (cont)
38AKS013/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
108.9 118.5 129.0 116.5 123.3 133.8 122.7
TC
85 SHC 106.0 88.0 68.1 116.5 101.9 76.8 122.7
7.23 7.47 7.71 7.42 7.59 7.82 7.57
kW
103.6 112.6 122.7 111.5 117.0 127.1 117.3
TC
95 SHC 103.6 85.6 65.8 111.5 99.5 74.6 117.3
7.87 8.14 8.43 8.10 8.28 8.56 8.28
kW
101.1 109.7 119.5 109.0 113.8 123.6 114.5
TC
100 SHC 101.1 84.5 64.7 109.0 98.3 73.4 114.5
8.19 8.47 8.78 8.44 8.61 8.91 8.62
kW
98.7 106.7 116.3 106.5 110.6 120.1 111.7
TC
98.7
83.4 63.6 106.5 97.0 72.2 111.7
105 SHC
8.50 8.79 9.13 8.78 8.93 9.26 8.96
kW
94.0 100.5 109.7 101.2 103.9 113.0 106.0
TC
94.0
81.0 61.3 101.2 94.3 69.8 106.0
115 SHC
9.13 9.42 9.80 9.44 9.56 9.93 9.64
kW
38AKS014/40RM012 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3000
4000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
115.8 126.3 137.9 122.7 132.1 143.8 128.7
TC
85 SHC 100.7 84.2 67.3 116.7 95.9 74.4 128.7
8.27 8.50 8.75 8.43 8.62 8.86 8.55
kW
110.8 120.7 131.8 117.3 126.1 137.2 123.6
TC
98.3 81.9 64.9 113.6 93.5 72.0 123.6
95 SHC
9.03 9.31 9.60 9.22 9.46 9.74 9.39
kW
108.3 117.9 128.7 114.6 123.1 134.0 121.1
TC
97.2 80.7 63.8 112.5 92.2 70.9 121.1
100 SHC
9.40 9.70 10.02 9.61 9.86 10.18 9.80
kW
105.8 115.0 125.6 111.9 119.9 130.7 118.5
TC
96.0 79.5 62.6 111.9 91.0 69.8 118.5
105 SHC
9.77 10.09 10.44 9.98 10.25 10.60 10.21
kW
100.6 109.3 119.4 107.2 113.8 123.9 113.2
TC
93.5 77.1 60.4 107.2 88.8 67.4 113.2
115 SHC
10.49 10.86 11.26 10.77 11.03 11.42 11.01
kW
38AKS014/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
123.1 134.4 146.3 129.9 140.1 152.8 137.4
TC
85 SHC 113.3 94.1 73.8 129.9 108.4 82.8 137.4
8.36 8.59 8.81 8.50 8.70 8.92 8.64
kW
116.8 129.8 141.5 124.2 133.0 144.5 130.9
TC
95 SHC 110.4 92.1 72.0 124.2 105.3 80.1 130.9
9.16 9.72 10.01 9.36 9.57 9.85 9.52
kW
114.0 124.4 135.6 121.5 129.5 140.7 128.0
TC
100 SHC 108.7 89.8 69.9 121.5 104.2 78.6 128.0
9.55 9.86 10.17 9.78 10.00 10.30 9.96
kW
112.0 121.1 132.0 119.5 127.2 137.0 125.9
TC
105 SHC 107.9 88.6 68.6 119.5 103.1 77.4 125.9
10.09 10.27 10.60 10.34 10.57 10.75 10.55
kW
105.4 114.6 125.0 113.3 119.3 129.5 119.3
TC
115 SHC 104.2 86.1 66.1 113.3 100.2 74.8 119.3
10.69 11.06 11.45 11.01 11.24 11.62 11.25
kW

72
136.8
84.9
7.89
129.7
82.5
8.63
126.2
81.3
8.98
122.6
80.2
9.33
115.3
77.9
10.02

38AKS014/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
131.8 144.1 157.3 140.9 150.2 163.6 148.8
TC
85 SHC 125.8 99.0 68.6 140.9 117.9 80.1 148.8
8.46 8.68 8.89 8.63 8.79 8.98 8.76
kW
125.9 137.3 150.0 135.4 143.0 155.8 142.8
TC
95 SHC 122.9 97.1 66.9 135.4 115.6 78.4 142.8
9.31 9.57 9.85 9.52 9.70 9.97 9.69
kW
122.9 134.0 146.3 132.6 139.4 151.9 139.6
TC
100 SHC 122.9 96.1 66.0 132.6 115.0 77.6 139.6
9.72 10.00 10.31 9.96 10.14 10.45 10.14
kW
121.2 130.6 142.7 129.7 135.6 147.9 136.4
TC
105 SHC 121.2 95.2 65.2 129.7 113.8 76.7 136.4
10.30 10.43 10.76 10.40 10.57 10.90 10.59
kW
114.7 123.8 135.3 123.9 128.3 139.9 130.2
TC
115 SHC 114.7 93.3 63.5 123.9 111.5 75.0 130.2
10.93 11.26 11.65 11.26 11.41 11.80 11.47
kW

72
148.2
81.4
8.94
141.2
79.1
9.84
137.7
77.8
10.27
134.1
76.6
10.70
126.9
74.3
11.53

38AKS016/40RM014 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
3750
5000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
149.6 163.5 178.2 158.2 172.3 187.2 163.9
TC
85 SHC 121.1 95.5 69.3 143.1 111.4 78.5 163.9
11.96 12.41 12.86 12.23 12.67 13.13 12.42
kW
143.5 156.9 171.0 151.4 165.0 181.8 157.6
TC
95 SHC 118.7 93.3 67.3 140.1 109.2 77.2 157.6
12.95 13.48 14.01 13.27 13.78 14.82 13.51
kW
140.3 153.4 168.4 148.2 161.4 175.4 154.3
TC
100 SHC 117.6 92.2 66.7 139.0 108.1 75.5 154.3
13.43 14.00 14.80 13.78 14.33 14.89 14.04
kW
137.2 150.0 163.6 144.9 157.7 171.4 151.3
TC
105 SHC 116.4 91.1 65.2 137.7 107.1 74.6 151.3
13.91 14.52 15.12 14.29 14.87 15.46 14.57
kW
131.0 143.2 156.0 138.0 150.1 163.3 145.2
TC
115 SHC 114.1 89.0 63.2 134.7 105.0 72.7 145.2
14.90 15.56 16.23 15.29 15.94 16.61 15.67
kW

72
156.7
91.0
8.98
148.1
88.1
9.93
145.4
87.2
10.59
140.3
85.5
10.85
132.4
82.9
11.72

38AKS016/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
159.3 173.7 189.0 168.0 182.7 198.1 175.8
TC
85 SHC 140.9 117.7 93.4 162.6 135.5 104.5 175.8
12.23 12.68 13.15 12.51 12.96 13.41 12.74
kW
152.6 166.6 181.1 161.0 174.6 187.6 169.5
TC
95 SHC 137.6 114.7 90.5 158.0 132.4 100.9 169.5
13.28 13.80 14.34 13.60 14.10 14.64 13.92
kW
149.3 163.0 177.3 157.3 170.5 186.2 166.2
TC
100 SHC 135.9 113.3 89.1 157.3 130.8 100.4 166.2
13.79 14.36 14.92 14.12 14.65 15.48 14.49
kW
146.0 159.4 174.5 154.1 167.6 180.7 163.6
TC
105 SHC 134.4 111.9 88.1 154.1 130.1 98.5 163.6
14.29 14.90 15.67 14.66 15.43 15.80 15.20
kW
139.0 154.0 165.2 147.7 158.2 171.8 155.8
TC
115 SHC 131.1 109.9 84.7 147.7 126.0 95.4 155.8
15.30 16.42 16.65 15.76 16.30 16.96 16.18
kW

6250
67
126.4
114.5
7.66
122.5
114.1
8.69
116.5
110.2
8.69
113.2
108.7
9.02
106.6
105.1
9.67

5000
67
136.4
107.2
8.71
130.0
105.2
9.55
126.8
103.9
9.97
124.5
103.2
10.51
117.2
99.8
11.17

6250
67
144.0
121.6
8.77
136.7
119.0
9.67
133.0
116.9
10.10
130.5
116.6
10.70
122.0
112.4
11.34

7500
67
154.3
134.9
8.85
146.6
132.2
9.77
144.3
132.5
10.42
139.0
129.5
10.66
131.5
126.1
11.51

72
167.9
91.2
9.04
159.6
89.5
10.04
155.4
88.5
10.52
151.2
87.7
10.98
142.9
86.0
11.89

6250
67
178.1
126.3
12.86
170.5
124.2
14.00
166.5
123.1
14.54
163.7
122.5
15.30
154.5
119.9
16.16

72
193.3
87.4
13.31
184.8
85.5
14.52
180.8
84.5
15.11
176.5
83.5
15.68
167.7
81.5
16.82

7500
67
188.0
151.6
13.11
179.5
148.2
14.28
175.4
146.6
14.84
171.1
145.1
15.40
162.6
141.6
16.52

72
203.7
114.6
13.57
194.7
111.6
14.81
190.1
110.0
15.42
185.5
108.5
16.01
176.2
105.4
17.19

See Legend and Notes on page 63.

61

Performance data (cont)
COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH (cont)
38AKS016/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
6,000
8,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
172.3 187.7 204.0 184.4 194.8 211.4 193.7
TC
85 SHC 166.3 129.9 89.3 184.4 154.5 104.2 193.7
12.79 13.27 13.75 13.17 13.48 13.97 13.44
kW
165.3 182.3 195.4 177.6 186.5 202.2 186.6
TC
95 SHC 165.3 128.6 87.3 177.6 152.3 102.3 186.6
13.89 14.99 14.99 14.35 14.69 15.24 14.68
kW
161.7 175.5 192.3 174.1 182.2 197.5 183.0
TC
100 SHC 161.7 126.7 86.8 174.1 151.3 101.3 183.0
14.43 15.00 15.87 14.93 15.27 15.85 15.30
kW
158.2 171.5 186.5 170.7 177.9 192.9 179.1
TC
105 SHC 158.2 125.6 85.3 170.7 150.2 100.3 179.1
14.96 15.55 16.19 15.51 15.84 16.46 15.89
kW
152.4 165.6 177.5 163.6 171.5 183.3 171.3
TC
115 SHC 152.4 125.0 83.2 163.6 150.3 98.3 171.3
16.13 17.08 17.39 16.70 17.38 17.68 17.08
kW
38AKS024/40RM016 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
4500
6000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
183.9 201.0 219.3 195.2 212.8 231.0 203.0
TC
85 SHC 147.1 116.6 85.3 173.8 136.1 96.3 195.6
16.04 16.76 17.54 16.52 17.27 18.03 16.85
kW
176.1 195.4 209.8 186.3 203.1 220.6 193.7
TC
95 SHC 144.2 115.1 82.7 169.9 133.2 93.5 193.3
17.29 18.60 18.92 17.78 18.59 19.43 18.14
kW
171.8 188.0 205.0 181.9 198.3 215.3 189.4
TC
100 SHC 142.4 112.3 80.9 168.2 131.7 92.2 189.4
17.88 18.74 19.60 18.41 19.25 20.13 18.79
kW
167.8 183.4 200.2 177.5 193.4 210.0 185.1
TC
105 SHC 141.1 110.9 79.6 166.3 130.3 90.9 185.1
18.50 19.39 20.30 19.06 19.92 20.83 19.47
kW
159.4 174.4 190.2 168.5 183.5 199.3 176.5
TC
115 SHC 137.8 108.1 76.9 162.1 127.6 88.4 176.5
19.76 20.72 21.70 20.35 21.30 22.27 20.86
kW
38AKS024/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
6,000
8,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
205.7 224.5 244.3 216.1 235.1 255.4 227.7
TC
85 SHC 184.9 153.8 121.3 212.2 176.8 135.8 227.7
17.00 17.77 18.58 17.43 18.21 19.04 17.89
kW
196.8 214.7 237.4 206.9 224.1 243.6 218.8
TC
95 SHC 180.1 149.7 119.0 206.9 172.6 131.7 218.8
18.19 19.03 20.65 18.66 19.46 20.37 19.22
kW
193.8 209.7 228.4 202.6 218.5 237.6 214.1
TC
100 SHC 179.4 147.6 115.5 202.6 170.3 129.6 214.1
19.05 19.64 20.56 19.27 20.07 21.01 19.85
kW
187.1 204.6 222.9 198.5 213.0 231.7 209.5
TC
105 SHC 175.7 145.6 113.5 198.5 168.3 127.6 209.5
19.31 20.26 21.22 19.92 20.70 21.67 20.50
kW
177.9 194.1 211.6 190.0 202.0 219.7 202.9
TC
115 SHC 171.0 141.5 109.5 190.0 164.0 123.5 202.9
20.49 21.48 22.53 21.23 21.96 23.00 22.45
kW
See Legend and Notes on page 63.

62

72
216.3
118.4
14.12
206.8
116.5
15.41
203.5
116.3
16.32
196.9
114.5
16.62
186.8
112.6
17.84

38AKS024/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
219.1 238.8 259.8 234.2 248.0 269.2 246.5
TC
85 SHC 212.0 176.1 136.4 234.2 204.1 153.7 246.5
17.96 18.80 19.69 18.60 19.20 20.09 19.11
kW
212.5 227.5 247.7 224.9 236.3 256.6 236.6
TC
95 SHC 211.7 171.8 132.0 224.9 199.4 149.6 236.6
19.94 20.08 21.05 19.95 20.52 21.46 20.49
kW
205.0 223.4 241.9 220.4 230.6 250.5 231.6
TC
100 SHC 205.0 170.8 130.1 220.4 197.5 147.7 231.6
19.82 20.92 21.72 20.61 21.16 22.17 21.19
kW
199.7 216.6 235.9 215.6 224.7 244.1 226.3
TC
105 SHC 199.7 167.7 128.0 215.6 195.3 145.5 226.3
20.43 21.38 22.41 21.30 21.83 22.87 21.90
kW
194.0 205.4 223.7 206.1 212.6 235.2 215.7
TC
115 SHC 194.0 163.3 123.9 206.1 190.4 142.5 215.7
22.37 22.62 23.74 22.65 23.07 24.94 23.25
kW

72
238.8
106.9
18.35
228.0
104.4
19.77
222.4
103.1
20.48
216.9
101.8
21.21
205.3
99.3
22.64

38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
6,000
8,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
257.4 282.2 308.4 274.1 299.2 325.8 284.9
TC
85 SHC 205.5 164.8 123.1 243.4 191.9 138.8 275.4
21.83 22.91 24.02 22.58 23.64 24.76 23.05
kW
245.9 269.7 295.2 261.5 285.8 311.3 272.0
TC
95 SHC 201.1 160.7 119.4 238.5 188.0 135.0 272.0
23.31 24.51 25.75 24.13 25.32 26.55 24.63
kW
240.1 263.5 288.4 254.7 278.9 303.9 265.3
TC
100 SHC 198.8 158.6 117.4 235.6 185.9 133.2 265.3
24.04 25.28 26.58 24.85 26.12 27.40 25.39
kW
234.4 257.2 281.4 248.5 271.8 296.3 260.1
TC
105 SHC 196.7 156.6 115.5 233.7 183.9 131.2 260.1
24.80 26.11 27.46 25.62 26.96 28.31 26.27
kW
222.7 244.6 267.5 235.9 257.4 280.9 248.8
TC
115 SHC 192.3 152.5 111.5 228.2 179.7 127.5 248.8
26.26 27.68 29.15 27.11 28.52 29.99 27.95
kW

72
262.2
149.0
19.32
249.8
144.8
20.66
243.6
142.7
21.32
237.5
140.8
21.99
225.1
136.7
23.32

38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
263.5 287.8 313.2 277.6 301.7 327.2 290.9
TC
85 SHC 229.3 181.2 131.6 269.1 212.1 149.7 290.9
22.01 23.07 24.15 22.65 23.67 24.75 23.20
kW
251.6 274.7 299.0 264.8 287.7 312.1 279.3
TC
95 SHC 224.7 177.1 127.8 264.8 208.0 146.1 279.3
23.52 24.68 25.87 24.18 25.34 26.51 24.90
kW
245.7 268.3 292.0 258.5 280.4 304.7 273.5
TC
100 SHC 222.5 175.1 126.0 258.5 206.1 144.4 273.5
24.25 25.47 26.71 24.94 26.12 27.39 25.75
kW
239.6 261.6 284.7 253.0 273.0 296.6 267.5
TC
105 SHC 220.0 173.1 124.1 253.0 204.1 142.6 267.5
25.01 26.27 27.57 25.76 26.93 28.24 26.61
kW
227.1 248.2 270.3 241.9 258.4 280.7 255.1
TC
115 SHC 215.1 169.0 120.5 241.9 199.8 138.9 255.1
26.45 27.84 29.26 27.41 28.49 29.92 28.27
kW

10,000
67
199.7
176.8
13.64
190.9
174.1
14.85
186.4
172.7
15.43
181.9
171.3
16.01
172.6
167.6
17.15

7500
67
220.5
154.4
17.59
210.5
151.7
18.95
205.2
150.0
19.62
200.0
148.7
20.29
189.2
145.6
21.64

10,000
67
241.6
197.7
18.48
230.2
193.3
19.75
224.7
191.3
20.37
218.8
188.6
21.00
207.5
184.2
22.29

12,500
67
254.5
229.5
19.49
241.7
224.0
20.76
235.8
221.6
21.41
229.8
219.0
22.09
217.3
212.8
23.34

72
275.5
170.0
20.37
262.2
165.8
21.77
255.7
163.6
22.43
249.1
161.6
23.14
235.4
157.4
24.44

10,000
67
310.4
217.4
24.14
295.7
213.4
25.80
288.3
211.4
26.60
280.8
209.2
27.46
265.9
204.9
29.06

72
337.3
153.8
25.26
321.5
150.2
27.05
313.7
148.3
27.92
305.5
146.4
28.81
289.4
142.6
30.52

12,500
67
310.7
241.2
24.06
295.6
236.9
25.71
288.1
234.7
26.52
280.4
232.5
27.34
265.3
228.1
28.94

72
336.6
167.2
25.15
320.4
163.5
26.92
312.3
161.7
27.77
304.1
159.7
28.65
287.7
156.2
30.35

COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH (cont)
38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
279.7 305.5 332.1 296.4 318.0 345.0 312.8
TC
85 SHC 259.7 204.9 146.4 296.4 241.8 168.3 312.8
22.84 23.92 25.03 23.51 24.46 25.57 24.21
kW
267.2 291.2 317.0 284.9 302.8 328.6 299.8
TC
95 SHC 255.4 200.8 142.6 284.9 237.5 164.4 299.8
24.40 25.59 26.84 25.26 26.15 27.39 25.98
kW
260.4 284.0 309.4 278.9 295.1 320.4 293.4
TC
100 SHC 252.0 198.9 140.9 278.9 235.3 162.6 293.4
25.14 26.38 27.70 26.10 26.97 28.27 26.84
kW
253.7 276.7 301.3 272.8 287.5 312.1 286.8
TC
105 SHC 248.4 196.7 139.0 272.8 233.2 160.9 286.8
25.92 27.22 28.58 26.99 27.83 29.18 27.77
kW
241.1 262.0 285.5 260.3 272.1 295.5 273.6
TC
115 SHC 241.1 192.4 135.2 260.3 228.8 157.2 273.6
27.44 28.82 30.28 28.68 29.46 30.91 29.54
kW
38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
7,500
10,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
280.1 305.6 332.5 294.8 320.8 347.7 307.1
TC
85 SHC 235.6 187.1 137.0 276.9 217.7 154.8 307.1
23.75 24.89 26.04 24.40 25.54 26.70 24.96
kW
267.9 292.7 318.7 282.5 306.8 332.7 295.4
TC
95 SHC 230.9 182.8 133.3 271.9 213.6 151.0 295.4
25.19 26.45 27.75 25.93 27.17 28.43 26.59
kW
261.8 286.0 311.1 276.0 299.7 325.0 289.5
TC
100 SHC 228.6 180.6 131.1 268.8 211.6 149.2 289.5
25.88 27.20 28.55 26.67 27.94 29.27 27.39
kW
255.7 279.2 303.7 268.8 292.5 317.1 283.4
TC
105 SHC 226.3 178.5 129.1 268.8 209.5 147.4 283.4
26.61 27.98 29.38 27.39 28.74 30.13 28.22
kW
243.0 265.3 288.7 256.2 277.4 301.1 271.0
TC
115 SHC 221.5 174.2 125.2 256.2 205.3 143.6 271.0
27.99 29.48 31.00 28.88 30.27 31.81 29.86
kW

—
Edb
Ewb
kW
SHC
TC

—
—
—
—
—
—

LEGEND
Out of Range
Entering Dry Bulb
Entering Wet Bulb
Compressor Motor Power Input
Sensible Heat Capacity (1000 Btuh) Gross
Total Capacity (1000 Btuh) Gross

1. Direct interpolation is permissible. Do not extrapolate.

2. SHC is based on 80 F db air entering indoor coil.

72
353.3
189.0
25.92
336.3
185.4
27.76
327.9
183.6
28.66
319.3
181.8
29.59
301.9
177.9
31.32

38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
297.9 324.3 352.1 312.9 338.8 366.7 330.1
TC
85 SHC 267.9 210.7 151.5 312.9 247.8 173.3 330.1
24.55 25.70 26.90 25.21 26.34 27.53 25.95
kW
284.9 310.5 337.1 300.9 323.5 350.5 317.7
TC
95 SHC 262.5 206.5 147.7 300.9 243.5 169.7 317.7
26.07 27.35 28.66 26.87 27.99 29.32 27.72
kW
278.3 303.5 329.5 295.0 315.7 342.2 311.0
TC
100 SHC 260.2 204.5 145.9 295.0 241.3 167.8 311.0
26.81 28.15 29.51 27.69 28.80 30.17 28.56
kW
271.7 296.2 321.7 289.0 307.8 333.7 304.3
TC
105 SHC 257.6 202.4 143.9 289.0 239.1 165.8 304.3
27.57 28.97 30.40 28.55 29.63 31.06 29.42
kW
257.9 280.9 305.5 276.5 291.8 316.4 290.6
TC
115 SHC 251.0 198.0 139.9 276.5 234.5 161.9 290.6
28.99 30.49 32.08 30.21 31.18 32.75 31.11
kW

72
357.9
172.1
27.15
342.2
168.4
28.90
334.2
166.7
29.76
325.8
164.8
30.63
308.7
160.8
32.29

38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm
Temp (F)
9,000
12,000
Air Entering
Condenser
Evaporator Air — Ewb (F)
(Edb)
62
67
72
62
67
72
62
347.6 378.8 411.3 367.0 398.3 431.0 380.2
TC
85 SHC 287.1 228.1 167.7 338.3 265.2 189.3 380.2
33.03 34.90 36.81 34.20 36.06 38.02 34.97
kW
334.0 363.8 395.1 351.4 381.6 412.9 365.8
TC
95 SHC 282.2 223.4 163.4 331.7 260.3 184.7 365.8
34.80 36.76 38.83 35.94 37.95 40.03 36.90
kW
327.2 356.3 386.8 344.0 373.1 403.6 359.2
TC
100 SHC 279.4 221.0 161.2 328.7 257.8 182.5 359.2
35.71 37.74 39.87 36.87 38.91 41.05 37.96
kW
319.9 348.7 378.4 336.6 364.6 394.3 352.0
TC
105 SHC 276.5 218.5 159.0 325.2 255.4 180.2 352.0
36.56 38.69 40.89 37.78 39.85 42.05 38.93
kW
305.3 332.4 360.5 320.5 347.2 375.3 337.6
TC
115 SHC 271.1 213.5 153.9 320.5 250.4 175.6 337.6
38.19 40.43 42.74 39.46 41.63 43.95 40.85
kW

15,000
67
326.3
275.6
24.82
310.6
271.3
26.54
302.8
268.8
27.38
294.6
266.0
28.24
278.4
260.8
29.85

12,500
67
331.0
246.9
25.98
316.4
242.9
27.65
308.7
240.7
28.43
300.9
238.5
29.23
285.0
234.0
30.76

15,000
67
347.7
282.1
26.72
331.8
277.4
28.39
323.8
275.1
29.21
315.7
272.9
30.06
299.1
267.7
31.66

72
375.8
194.1
27.91
358.8
190.2
29.73
350.3
188.5
30.58
341.5
186.6
31.49
323.6
182.7
33.21

15,000
67
410.6
300.0
36.77
393.1
295.2
38.70
384.3
292.8
39.69
375.4
290.3
40.65
357.2
285.1
42.46

72
443.5
209.8
38.73
424.4
205.3
40.79
414.8
203.2
41.83
405.0
201.0
42.84
385.3
196.5
44.79

3. Formulas:
SHCBtuh
1.10 x cfm
Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor coil
(hlwb)
TCBtuh
Ldb F: hlwb = hewb –
4.5 x cfm
Ldb F = Edb F –

where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting piping
sized to the outdoor unit field connections. (Equivalent length is equal to the
actual length plus a 50% allowance for fitting losses.) For other equivalent
lengths, refer to the Carrier System Design Manual, Part 3, for line losses.

63

Performance data (cont)
40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 0-300 Pa ESP — SI

40RM
007

850
990
1130
1270
1420

r/s
6.64
7.43
8.30
9.06
9.91

kW
0.14
0.21
0.30
0.41
0.55

r/s
7.56
8.28
9.02
9.79
10.58

kW
0.18
0.25
0.35
0.47
0.61

EXTERNAL STATIC PRESSURE (Pa)
100
150
200
r/s
kW
r/s
kW
r/s
0.35
11.88
9.13
0.26
10.56
0.44
12.22
9.71
0.34
11.00
0.45
11.55
0.55
12.67
10.36
0.58
12.17
0.69
13.20
11.06
11.78
0.74
12.83
0.86
13.80

40RM
008

1060
1230
1420
1600
1770

4.55
5.37
9.21
10.25
11.18

0.06
0.11
0.48
0.68
0.90

8.21
8.99
9.92
10.89
11.76

0.27
0.38
0.55
0.75
0.98

9.67
10.37
11.22
12.09
12.88

0.37
0.49
0.67
0.90
1.14

10.93
11.55
12.33
13.15
13.90

0.46
0.60
0.80
1.04
1.30

12.11
12.62
13.33
14.10
14.82

0.57
0.71
0.92
1.18
1.45

13.23
13.65
14.27
14.99
15.67

0.68
0.84
1.05
1.33
1.61

14.30
14.64
15.17
15.83
16.46

0.81
0.96
1.19
1.47
1.77

40RM
012

1420
1650
1890
2120
2360

6.65
10.06
11.33
12.61
13.90

0.22
0.68
0.99
1.38
1.87

9.55
10.69
11.88
13.11
14.36

0.51
0.76
1.08
1.49
1.99

10.89
11.90
12.96
14.08
15.23

0.64
0.91
1.25
1.68
2.21

12.04
13.00
13.99
15.02
16.10

0.77
1.06
1.43
1.88
2.42

13.06
13.97
14.93
15.92
16.94

0.89
1.20
1.59
2.07
2.64

14.02
14.86
15.78
16.74
17.73

1.02
1.35
1.76
2.26
2.85

14.93
15.70
16.58
17.51
18.48

1.15
1.50
1.92
2.44
3.06

40RM
014

1770
2030
2360
2690
2950

6.57
7.27
8.20
9.16
9.93

0.30
0.43
0.64
0.92
1.18

7.54
8.11
8.92
9.79
10.50

0.39
0.52
0.74
1.02
1.30

9.31
9.76
10.38
11.07
11.66

0.60
0.75
0.98
1.27
1.56

10.72
11.16
11.73
12.33
12.83

0.82
1.00
1.26
1.58
1.87

11.95
12.36
12.91
13.48
13.95

1.04
1.25
1.55
1.90
2.22

13.09
13.44
13.97
14.53
14.98

1.27
1.50
1.84
2.23
2.58

14.13
14.45
14.93
15.48
15.92

1.52
1.76
2.13
2.56
2.94

40RM
016

2120
2500
2830
3210
3540

7.13
8.13
9.03
10.07
10.99

0.44
0.68
0.96
1.37
1.81

7.91
8.80
9.63
10.62
11.50

0.52
0.78
1.07
1.48
1.93

9.50
10.15
10.81
11.66
12.45

0.74
1.00
1.30
1.73
2.20

10.94
11.48
12.01
12.71
13.40

0.99
1.27
1.58
2.01
2.49

12.17
12.70
13.18
13.77
14.35

1.25
1.57
1.90
2.35
2.83

13.26
13.78
14.25
14.80
15.31

1.51
1.87
2.24
2.71
3.20

14.26
14.76
15.23
15.76
16.24

1.77
2.18
2.58
3.09
3.60

40RM
024

2830
3300
3780
4250
4720

8.86
10.14
11.43
12.74
14.05

0.94
1.44
2.11
2.96
4.01

9.48
10.69
11.93
13.19
14.47

1.04
1.56
2.25
3.12
4.19

10.65
11.70
12.84
14.02
15.23

1.26
1.81
2.52
3.43
4.54

11.84
12.71
13.71
14.81
15.96

1.53
2.08
2.81
3.74
4.88

13.01
13.73
14.60
15.59
16.66

1.85
2.41
3.14
4.08
5.24

14.10
14.74
15.49
16.37
17.36

2.19
2.77
3.51
4.45
5.62

15.08
15.71
16.39
17.17
18.07

2.53
3.15
3.91
4.85
6.03

40RM
028

3540
4130
4720
5310
5900

7.60
8.68
9.78
10.89
12.00

0.96
1.47
2.15
3.01
4.07

8.16
9.18
10.23
11.30
12.38

1.09
1.62
2.32
3.20
4.29

9.27
10.13
11.07
12.06
13.09

1.38
1.94
2.67
3.59
4.72

10.34
11.07
11.89
12.80
13.75

1.68
2.29
3.05
4.00
5.17

11.30
11.99
12.72
13.53
14.41

1.97
2.63
3.45
4.43
5.63

12.15
12.84
13.53
14.27
15.07

2.28
2.97
3.84
4.88
6.11

12.97
13.60
14.29
14.99
15.74

2.68
3.32
4.23
5.33
6.61

40RM
034

4250
4960
5660
6370
7080

8.68
9.93
11.21
12.51
13.82

1.48
2.35
3.45
4.85
6.59

9.17
10.38
11.63
12.89
14.17

1.68
2.53
3.66
5.08
6.85

10.27
11.21
12.38
13.58
14.81

2.07
2.90
4.07
5.54
7.36

11.27
11.99
13.08
14.22
15.40

2.41
3.28
4.49
6.01
7.88

12.19
12.78
13.76
14.83
15.97

2.77
3.68
4.93
6.49
8.40

13.03
13.56
14.45
15.44
16.52

3.13
4.10
5.39
6.99
8.94

13.81
14.32
15.14
16.05
17.06

3.50
4.51
5.87
7.51
9.49

UNIT
(Standard
3-Row Coil)

AIRFLOW
(L/s)

0

50

LEGEND

kW
0.45
0.54
0.66
0.81
0.99

250
r/s
13.08
13.37
13.73
14.19
14.72

kW
0.55
0.66
0.78
0.94
1.12

300
r/s
14.16
14.44
14.76
15.14
15.61

kW
0.66
0.78
0.91
1.07
1.26

40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — SI

ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination is required.
Refer to fan motor and drive tables, pages 94-98, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm (18.3 r/s) for unit sizes 028
and 034; 1200 rpm (20 r/s) for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51 mm (2-in.)
filters, and unit casing. See right for factory-supplied filter pressure drop.
3. The medium-static drive and standard motor combination is NOT AVAILABLE for 40RM016-028 units. Use the alternate motor if medium-static
drive is required for these sizes.

UNIT
40RM
007

008
012

014
016

024
028

034

64

AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

PRESSURE DROP
(Pa)
13
20
28
17
27
38
28
42
56
15
24
33
20
30
42
32
47
64
36
55
76
47
71
98

40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 350-600 Pa ESP — SI
UNIT
(Standard
3-Row Coil)

AIRFLOW
(L/s)

350

400

EXTERNAL STATIC PRESSURE (Pa)
450
500
r/s
kW
r/s
kW
16.94
1.01
17.74
1.13
17.25
1.16
18.07
1.30
17.53
1.33
18.36
1.48
17.82
1.51
18.64
1.67
18.14
1.72
18.94
1.89

40RM
007

850
990
1130
1270
1420

r/s
15.16
15.44
15.73
16.07
16.48

kW
0.78
0.90
1.05
1.21
1.41

r/s
16.08
16.38
16.65
16.96
17.32

kW
0.89
1.03
1.19
1.36
1.56

40RM
008

1060
1230
1420
1600
1770

15.31
15.60
16.05
16.64
17.23

0.94
1.10
1.33
1.62
1.93

16.25
16.51
16.90
17.42
17.97

1.07
1.24
1.48
1.78
2.09

17.14
17.39
17.74
18.20
18.70

1.20
1.39
1.64
1.94
2.26

17.98
18.23
18.54
18.95
19.41

40RM
012

1420
1650
1890
2120
2360

15.81
16.51
17.34
18.24
19.18

1.29
1.65
2.09
2.63
3.27

16.67
17.29
18.06
18.93
19.85

1.44
1.80
2.26
2.82
3.48

17.51
18.05
18.77
19.59
—

1.60
1.97
2.43
3.00
—

40RM
014

1770
2030
2360
2690
2950

15.15
15.41
15.84
16.36
16.79

1.77
2.04
2.43
2.89
3.30

16.13
16.34
16.70
17.19
17.61

2.04
2.32
2.74
3.23
3.66

17.10
17.24
17.54
17.98
18.39

40RM
016

2120
2500
2830
3210
3540

15.20
15.67
16.13
16.66
17.13

2.05
2.49
2.92
3.48
4.02

16.12
16.53
16.97
17.50
17.97

2.33
2.80
3.27
3.87
4.45

40RM
024

2830
3300
3780
4250
4720

15.90
16.50
17.13
17.88
18.77

2.86
3.53
4.32
5.30
6.52

16.75
17.33
17.97
18.67
19.43

40RM
028

3540
4130
4720
5310
5900

13.85
14.31
14.99
15.68
16.39

3.29
3.71
4.62
5.77
7.10

40RM
034

4250
4960
5660
6370
7080

14.43
15.04
15.81
16.66
17.61

3.88
4.92
6.34
8.04
10.06

550

600

r/s
18.51
18.84
19.14
19.42
19.71

kW
1.26
1.43
1.62
1.83
2.06

r/s
19.25
19.58
19.89
—
—

kW
1.39
1.57
1.77
—
—

1.34
1.54
1.80
2.11
2.44

18.77
19.03
19.32
19.69
—

1.48
1.70
1.97
2.29
—

19.53
19.80
—
—
—

1.63
1.86
—
—
—

18.32
18.80
19.45
—
—

1.76
2.13
2.61
—
—

19.11
19.53
—
—
—

1.92
2.31
—
—
—

19.87
—
—
—
—

2.09
—
—
—
—

2.33
2.62
3.05
3.57
4.03

18.00
18.07
18.35
18.75
19.13

2.62
2.92
3.38
3.92
4.40

18.85
18.92
19.14
19.49
19.84

2.92
3.24
3.71
4.27
4.77

19.68
19.73
19.83
—
—

3.22
3.56
4.06
—
—

16.98
17.35
17.77
18.29
18.75

2.62
3.12
3.62
4.26
4.88

17.83
18.13
18.53
19.03
19.50

2.92
3.44
3.97
4.65
5.30

18.67
18.90
19.26
19.75
—

3.24
3.77
4.33
5.04
—

19.47
19.65
19.97
—
—

3.57
4.12
4.69
—
—

3.18
3.91
4.76
5.76
6.99

17.53
18.17
18.83
19.48
—

3.52
4.32
5.22
6.24
—

18.30
18.92
19.55
—
—

3.89
4.70
5.67
—
—

19.03
19.60
—
—
—

4.23
5.10
—
—
—

—
—
—
—
—

—
—
—
—
—

14.50
15.01
15.65
16.34
17.03

3.80
4.17
5.02
6.20
7.60

15.22
15.74
16.27
16.95
17.64

4.40
4.79
5.46
6.64
8.08

15.83
16.33
16.88
17.53
18.22

5.13
5.37
5.97
7.09
8.57

16.42
17.00
17.50
18.09
—

5.74
6.04
6.57
7.58
—

—
—
—
—
—

—
—
—
—
—

14.98
15.71
16.47
17.27
18.16

4.36
5.32
6.81
8.57
10.64

15.84
16.33
17.10
17.88
—

4.96
5.74
7.28
9.10
—

16.48
16.93
17.69
—
—

5.50
6.20
7.74
—
—

17.16
17.51
18.26
—
—

6.21
6.70
8.21
—
—

17.96
18.09
—
—
—

7.26
7.29
—
—
—

LEGEND

40RM FACTORY-SUPPLIED FILTER PRESSURE DROP — SI

ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination is required.
Refer to fan motor and drive tables, pages 94-98, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm (18.3 r/s) for unit sizes 028
and 034; 1200 rpm (20 r/s) for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51 mm (2-in.)
filters, and unit casing. See right for factory-supplied filter pressure drop.
3. The medium-static drive and standard motor combination is NOT AVAILABLE for 40RM016-028 units. Use the alternate motor if medium-static
drive is required for these sizes.

UNIT
40RM
007
008

012
014

016
024

028
034

AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

PRESSURE DROP
(Pa)
13
20
28
17
27
38
28
42
56
15
24
33
20
30
42
32
47
64
36
55
76
47
71
98

65

Performance data (cont)
40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — ENGLISH

40RM
007

1,800
2,100
2,400
2,700
3,000

Rpm
399
446
498
544
594

Bhp
0.19
0.28
0.40
0.55
0.73

Rpm
454
497
541
588
635

Bhp
0.24
0.34
0.47
0.63
0.82

EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
548
0.35
634
0.47
713
0.60
0.59
733
0.73
583
0.46
660
0.60
693
0.74
760
0.89
622
0.78
730
0.93
792
1.09
663
707
0.99
770
1.15
828
1.32

40RM
008

2,250
2,600
3,000
3,400
3,750

273
322
552
615
671

0.08
0.15
0.65
0.91
1.20

493
540
595
653
706

0.37
0.52
0.73
1.01
1.31

580
622
673
726
773

0.49
0.66
0.91
1.21
1.53

656
693
740
789
834

0.62
0.81
1.07
1.40
1.74

727
757
800
846
889

40RM
012

3,000
3,500
4,000
4,500
5,000

399
604
680
756
834

0.29
0.92
1.33
1.86
2.51

573
641
713
787
861

0.69
1.02
1.45
1.99
2.67

654
714
778
845
914

0.86
1.22
1.68
2.26
2.96

722
780
839
901
966

1.03
1.42
1.91
2.52
3.25

40RM
014

3,750
4,300
5,000
5,700
6,250

394
436
492
550
596

0.40
0.57
0.86
1.23
1.59

453
487
535
587
630

0.52
0.70
0.99
1.37
1.74

558
586
623
664
700

0.80
1.00
1.31
1.71
2.09

643
670
704
740
770

40RM
016

4,500
5,300
6,000
6,800
7,500

428
488
542
604
660

0.59
0.92
1.29
1.83
2.42

475
528
578
637
690

0.70
1.04
1.43
1.99
2.59

570
609
649
700
747

0.99
1.34
1.74
2.32
2.95

40RM
024

6,000
7,000
8,000
9,000
10,000

532
608
686
764
843

1.25
1.93
2.83
3.97
5.38

569
641
716
791
868

1.39
2.09
3.01
4.18
5.62

639
702
770
841
914

40RM
028

7,500
8,750
10,000
11,250
12,500

456
521
587
653
720

1.29
1.98
2.88
4.03
5.46

490
551
614
678
743

1.47
2.18
3.11
4.29
5.75

40RM
034

9,000
10,500
12,000
13,500
15,000

521
596
673
751
829

1.99
3.16
4.63
6.51
8.84

550
623
698
773
850

2.25
3.40
4.90
6.82
9.19

UNIT
(Standard
3-Row Coil)

AIRFLOW
(Cfm)

0.0

0.2

1.2
Bhp
0.74
0.88
1.05
1.26
1.50

Rpm
850
867
885
909
937

Bhp
0.89
1.05
1.22
1.44
1.69

0.76
0.96
1.24
1.59
1.95

794
819
856
899
940

0.92
1.12
1.41
1.78
2.16

858
878
910
950
988

1.08
1.29
1.60
1.97
2.37

784
838
896
955
1016

1.19
1.61
2.14
2.78
3.54

841
892
947
1005
1064

1.37
1.81
2.36
3.03
3.82

896
942
995
1051
1109

1.55
2.01
2.58
3.28
4.11

1.10
1.34
1.69
2.11
2.51

717
742
775
809
837

1.39
1.67
2.08
2.55
2.97

785
806
838
872
899

1.71
2.01
2.47
2.99
3.45

848
867
896
929
955

2.04
2.36
2.86
3.43
3.94

656
689
721
763
804

1.33
1.71
2.11
2.70
3.34

730
762
791
826
861

1.68
2.11
2.55
3.15
3.79

796
827
855
888
919

2.02
2.51
3.00
3.64
4.29

856
886
914
946
975

2.38
2.92
3.46
4.15
4.83

1.69
2.42
3.38
4.59
6.09

711
763
823
888
957

2.06
2.80
3.77
5.02
6.55

781
824
876
935
1000

2.48
3.23
4.21
5.47
7.02

846
885
930
982
1042

2.93
3.71
4.70
5.96
7.53

905
943
983
1030
1084

3.39
4.23
5.24
6.51
8.08

556
608
664
724
785

1.85
2.61
3.59
4.82
6.33

621
664
714
768
825

2.25
3.07
4.09
5.37
6.93

678
720
763
812
865

2.64
3.53
4.62
5.95
7.55

729
770
812
856
904

3.06
3.99
5.15
6.54
8.20

778
816
857
899
944

3.60
4.45
5.68
7.14
8.86

616
672
743
815
888

2.77
3.89
5.45
7.44
9.88

676
720
785
853
924

3.23
4.40
6.02
8.06
10.57

731
767
826
890
958

3.72
4.94
6.62
8.71
11.27

782
814
867
927
991

4.20
5.50
7.23
9.38
11.99

829
859
908
963
1024

4.70
6.05
7.87
10.07
12.73

LEGEND
ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination is required.
Refer to fan motor and drive tables, pages 94-98, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm (18.3 r/s) for unit sizes 028
and 034; 1200 rpm (20 r/s) for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51 mm (2-in.)
filters, and unit casing. See right for factory-supplied filter pressure drop.
3. The medium-static drive and standard motor combination is NOT AVAILABLE for 40RM016-028 units. Use the alternate motor if medium-static
drive is required for these sizes.

40RM FACTORY-SUPPLIED FILTER PRESSURE DROP —
ENGLISH
UNIT
40RM
007

008
012

014
016

024
028

034

66

1.0
Rpm
785
802
824
851
883

AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10 000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — ENGLISH
UNIT
(Standard
3-Row Coil)

AIRFLOW
(Cfm)

1.4

1.6

EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
Rpm
Bhp
Rpm
Bhp
1016
1.36
1065
1.52
1035
1.56
1084
1.74
1052
1.78
1101
1.98
1069
2.03
1118
2.24
1089
2.31
1136
2.53

40RM
007

1,800
2,100
2,400
2,700
3,000

Rpm
910
927
944
964
989

Bhp
1.04
1.21
1.41
1.63
1.89

Rpm
965
983
999
1018
1039

Bhp
1.20
1.38
1.59
1.82
2.10

40RM
008

2,250
2,600
3,000
3,400
3,750

918
936
963
998
1034

1.26
1.48
1.79
2.18
2.58

975
991
1014
1045
1078

1.43
1.67
1.99
2.39
2.80

1029
1044
1064
1092
1122

1.62
1.87
2.20
2.61
3.03

1079
1094
1113
1137
1164

40RM
012

3,000
3,500
4,000
4,500
5,000

949
990
1040
1094
1151

1.74
2.21
2.80
3.53
4.39

1000
1037
1084
1136
1191

1.93
2.42
3.03
3.78
4.66

1050
1083
1126
1176
—

2.14
2.64
3.26
4.03
—

40RM
014

3,750
4,300
5,000
5,700
6,250

909
925
950
981
1007

2.37
2.73
3.26
3.88
4.42

968
980
1002
1031
1057

2.74
3.11
3.67
4.33
4.91

1026
1034
1052
1079
1103

40RM
016

4,500
5,300
6,000
6,800
7,500

912
940
968
1000
1028

2.75
3.33
3.92
4.67
5.39

967
992
1018
1050
1078

3.13
3.75
4.38
5.19
5.97

40RM
024

6,000
7,000
8,000
9,000
10,000

954
990
1028
1073
1126

3.83
4.74
5.79
7.11
8.75

1005
1040
1078
1120
1166

4.27
5.24
6.38
7.72
9.37

40RM
028

7,500
8,750
10,000
11,250
12,500

831
859
900
941
984

4.41
4.97
6.20
7.73
9.53

870
901
939
980
1022

40RM
034

9,000
10,500
12,000
13,500
15,000

866
902
949
1000
1057

5.20
6.60
8.50
10.78
13.49

899
942
988
1036
1090

2.2

2.4

Rpm
1111
1131
1149
1165
1183

Bhp
1.69
1.92
2.18
2.45
2.76

Rpm
1155
1175
1193
—
—

Bhp
1.86
2.11
2.38
—
—

1.80
2.07
2.42
2.83
3.27

1126
1142
1159
1182
—

1.99
2.28
2.64
3.07
—

1172
1188
—
—
—

2.18
2.49
—
—
—

1099
1128
1167
—
—

2.36
2.86
3.50
—
—

1147
1172
—
—
—

2.58
3.10
—
—
—

1192
—
—
—
—

2.81
—
—
—
—

3.12
3.52
4.09
4.79
5.40

1080
1084
1101
1125
1148

3.51
3.92
4.53
5.25
5.90

1131
1135
1148
1169
1191

3.92
4.35
4.98
5.73
6.40

1019
1041
1066
1097
1125

3.52
4.18
4.85
5.71
6.54

1070
1088
1112
1142
1170

3.92
4.61
5.32
6.23
7.11

5.10
5.59
6.74
8.32
10.19

1052
1090
1130
1169
—
913
944
976
1017
1058

4.72
5.80
7.00
8.37
—
5.90
6.42
7.33
8.90
10.84

1098
1135
1173
—
—
950
980
1013
1052
1093

5.22
6.30
7.60
—
—
6.88
7.20
8.00
9.51
11.49

5.85
7.14
9.14
11.49
14.28

950
980
1026
1073
—

6.65
7.70
9.76
12.21
—

989
1016
1062
—
—

7.38
8.31
10.38
—
—

1120
1134
1156
1185
—
1142
1176
—
—
—
985
1020
1050
1086
—
1029
1051
1095
—
—

4.35
5.06
5.80
6.76
—
5.67
6.84
—
—
—
7.70
8.10
8.82
10.16
—
8.32
8.99
11.01
—
—

1181
1184
1190
—
—
1168
1179
1198
—
—
—
—
—
—
—
—
—
—
—
—
1077
1085
—
—
—

4.32
4.78
5.44
—
—
4.79
5.52
6.29
—
—
—
—
—
—
—
—
—
—
—
—
9.74
9.77
—
—
—

LEGEND
ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination is required.
Refer to fan motor and drive tables, pages 94-98, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm (18.3 r/s) for unit sizes 028
and 034; 1200 rpm (20 r/s) for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 51 mm (2-in.)
filters, and unit casing. See right for factory-supplied filter pressure drop.
3. The medium-static drive and standard motor combination is NOT AVAILABLE for 40RM016-028 units. Use the alternate motor if medium-static
drive is required for these sizes.

40RM FACTORY-SUPPLIED FILTER PRESSURE DROP —
ENGLISH
UNIT
40RM
007

008
012

014
016

024
028

034

AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10 000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

67

Performance data (cont)
FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
0-300 Pa ESP — 50 Hz, SI
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(L/s)

EXTERNAL STATIC PRESSURE (Pa)
100
150
200

50

250

300

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

007

850
990
1130
1270
1420

6.98
7.84
8.73
9.63
10.55

0.16
0.23
0.33
0.45
0.61

7.86
8.64
9.46
10.31
11.18

0.19
0.27
0.38
0.51
0.67

9.40
10.03
10.75
11.51
12.30

0.27
0.36
0.48
0.62
0.80

10.81
11.31
11.91
12.58
13.31

0.37
0.46
0.59
0.74
0.92

12.11
12.52
13.01
13.60
14.26

0.47
0.57
0.70
0.86
1.05

13.29
13.65
14.07
14.58
15.17

0.57
0.69
0.83
0.99
1.19

14.36
14.71
15.08
15.53
16.05

0.69
0.81
0.96
1.13
1.33

008

1060
1230
1420
1600
1770

4.83
5.81
9.65
10.76
11.74

0.07
0.14
0.52
0.74
0.97

8.50
9.35
10.35
11.39
12.32

0.29
0.41
0.59
0.81
1.06

9.91
10.67
11.59
12.54
13.40

0.38
0.52
0.71
0.96
1.22

11.15
11.81
12.66
13.55
14.37

0.48
0.63
0.84
1.10
1.38

12.32
12.88
13.64
14.48
15.25

0.59
0.74
0.97
1.24
1.53

13.44
13.90
14.57
15.34
16.07

0.71
0.87
1.10
1.39
1.69

14.50
14.89
15.47
16.17
16.86

0.83
1.00
1.24
1.53
1.85

012

1420
1650
1890
2120
2360

7.02
10.44
11.76
13.10
14.45

0.26
0.73
1.06
1.48
2.01

9.86
11.06
12.31
13.59
14.89

0.54
0.80
1.15
1.58
2.12

11.17
12.25
13.38
14.55
15.76

0.67
0.96
1.32
1.78
2.34

12.28
13.31
14.37
15.48
16.62

0.79
1.10
1.49
1.97
2.56

13.29
14.25
15.28
16.34
17.43

0.92
1.25
1.66
2.17
2.77

14.23
15.13
16.11
17.14
18.20

1.05
1.39
1.83
2.35
2.98

15.14
15.96
16.89
17.89
18.92

1.19
1.54
1.99
2.54
3.19

014

1770
2030
2360
2690
2950

6.84
7.58
8.57
9.59
10.40

0.32
0.46
0.69
0.99
1.28

7.78
8.40
9.27
10.20
10.96

0.41
0.55
0.79
1.10
1.39

9.46
9.98
10.68
11.44
12.09

0.62
0.78
1.04
1.36
1.67

10.82
11.31
11.96
12.64
13.21

0.83
1.03
1.31
1.66
1.98

12.02
12.47
13.09
13.74
14.27

1.05
1.27
1.60
1.98
2.33

13.13
13.52
14.11
14.74
15.25

1.28
1.52
1.88
2.30
2.68

14.19
14.51
15.05
15.65
16.15

1.53
1.78
2.17
2.63
3.03

016

2120
2500
2830
3210
3540

7.28
8.32
9.25
10.33
11.29

0.45
0.71
1.00
1.42
1.88

8.05
8.97
9.83
10.85
11.77

0.54
0.80
1.10
1.54
2.01

9.60
10.29
10.99
11.87
12.69

0.75
1.02
1.33
1.78
2.27

11.00
11.59
12.16
12.90
13.62

1.00
1.30
1.62
2.07
2.56

12.21
12.78
13.29
13.93
14.56

1.26
1.59
1.93
2.40
2.90

13.28
13.84
14.34
14.93
15.49

1.51
1.89
2.27
2.76
3.27

14.27
14.80
15.30
15.87
16.40

1.78
2.19
2.60
3.14
3.67

024

2830
3300
3780
4250
4720

9.03
10.34
11.67
13.01
14.36

0.96
1.48
2.17
3.05
4.15

9.62
10.86
12.14
13.44
14.75

1.06
1.60
2.31
3.21
4.32

10.77
11.85
13.02
14.23
15.48

1.29
1.85
2.58
3.51
4.66

11.94
12.84
13.88
15.00
16.18

1.56
2.12
2.87
3.82
4.99

13.08
13.85
14.75
15.77
16.87

1.87
2.45
3.20
4.16
5.35

14.15
14.84
15.63
16.54
17.56

2.20
2.80
3.56
4.53
5.73

15.12
15.78
16.50
17.32
18.26

2.54
3.18
3.96
4.94
6.14

028

3540
4130
4720
5310
5900

7.94
9.08
10.24
11.42
12.60

1.04
1.59
2.33
3.26
4.42

8.51
9.57
10.68
11.81
12.96

1.18
1.75
2.51
3.46
4.64

9.65
10.55
11.53
12.57
13.65

1.48
2.10
2.88
3.88
5.09

10.73
11.52
12.39
13.33
14.33

1.79
2.46
3.29
4.32
5.57

11.68
12.45
13.24
14.09
15.01

2.10
2.81
3.70
4.77
6.07

12.53
13.28
14.05
14.85
15.70

2.46
3.17
4.11
5.24
6.58

13.40
14.04
14.80
15.58
16.38

2.95
3.55
4.51
5.70
7.10

034

4250
4960
5660
6370
7080

8.99
10.33
11.68
13.04
14.42

1.62
2.51
3.68
5.18
7.05

9.49
10.77
12.07
13.40
14.74

1.78
2.70
3.90
5.42
7.31

10.44
11.59
12.81
14.07
15.36

2.12
3.08
4.33
5.90
7.84

11.39
12.40
13.52
14.71
15.94

2.49
3.49
4.77
6.39
8.38

12.32
13.22
14.23
15.34
16.51

2.86
3.92
5.25
6.90
8.93

13.18
14.03
14.95
15.97
17.08

3.22
4.35
5.74
7.44
9.51

13.95
14.79
15.66
16.61
17.65

3.59
4.78
6.23
7.98
10.10

See Legend and Notes on page 72.

68

0

FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
350-600 Pa ESP — 50 Hz, SI
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(L/s)

350

EXTERNAL STATIC PRESSURE (Pa)
450
500

400

550

600

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

r/s

kW

007

850
850
1130
1270
1420

15.34
15.69
16.04
16.44
16.91

0.80
0.94
1.09
1.27
1.49

16.25
16.61
16.95
17.32
17.75

0.92
1.07
1.23
1.42
1.64

17.10
17.47
17.81
18.17
18.56

1.03
1.20
1.38
1.58
1.81

17.90
18.28
18.63
18.97
19.34

1.16
1.33
1.53
1.74
1.97

18.66
19.04
19.40
19.75
—

1.28
1.47
1.67
1.90
—

19.39
19.77
—
—
—

1.41
1.61
—
—
—

008

1060
1230
1420
1600
1770

15.50
15.84
16.34
16.97
17.61

0.96
1.14
1.38
1.69
2.01

16.43
16.75
17.19
17.76
18.35

1.10
1.28
1.54
1.85
2.18

17.31
17.62
18.01
18.52
19.07

1.23
1.43
1.70
2.02
2.35

18.14
18.45
18.81
19.27
19.77

1.37
1.58
1.86
2.19
2.53

18.93
19.24
19.59
—
—

1.51
1.74
2.03
—
—

19.68
—
—
—
—

1.66
—
—
—
—

012

1420
1650
1890
2120
2360

16.02
16.76
17.64
18.60
19.61

1.33
1.70
2.16
2.73
3.40

16.87
17.53
18.35
19.28
—

1.48
1.85
2.33
2.91
—

17.71
18.29
19.05
19.93
—

1.64
2.02
2.51
3.10
—

18.52
19.04
19.74
—
—

1.80
2.19
2.69
—
—

19.30
19.77
—
—
—

1.97
2.37
—
—
—

—
—
—
—
—

—
—
—
—
—

014

1770
2030
2360
2690
2950

15.21
15.46
15.94
16.51
16.99

1.78
2.05
2.46
2.95
3.39

16.19
16.37
16.78
17.32
17.78

2.06
2.33
2.77
3.28
3.74

17.13
17.26
17.60
18.09
18.54

2.34
2.63
3.08
3.62
4.10

18.04
18.12
18.40
18.84
19.26

2.64
2.94
3.40
3.96
4.47

18.91
18.96
19.18
19.57
19.96

2.94
3.26
3.73
4.31
4.84

19.75
19.78
19.94
—
—

3.25
3.59
4.07
—
—

016

2120
2500
2830
3210
3540

15.21
15.69
16.18
16.75
17.26

2.05
2.49
2.94
3.52
4.09

16.11
16.54
17.01
17.57
18.07

2.33
2.80
3.28
3.90
4.50

16.98
17.35
17.79
18.34
18.84

2.62
3.12
3.63
4.29
4.93

17.83
18.14
18.54
19.08
19.57

2.93
3.44
3.97
4.67
5.35

18.66
18.90
19.27
19.78
—

3.24
3.77
4.33
5.06
—

19.47
19.64
19.97
—
—

3.57
4.11
4.69
—
—

024

2830
3300
3780
4250
4720

16.01
16.67
17.35
18.11
18.96

2.88
3.57
4.39
5.37
6.58

16.85
17.50
18.17
18.88
19.67

3.22
3.96
4.82
5.83
7.05

17.64
18.28
18.95
19.63
—

3.56
4.36
5.27
6.31
—

18.39
19.03
19.68
—
—

3.91
4.75
5.72
—
—

19.12
19.73
—
—
—

4.26
5.15
—
—
—

—
—
—
—
—

—
—
—
—
—

028

3540
4130
4720
5310
5900

14.57
14.76
15.49
16.26
17.04

3.97
3.99
4.92
6.15
7.61

14.95
15.51
16.15
16.91
17.68

4.41
4.57
5.37
6.61
8.11

15.67
16.36
16.78
17.51
18.28

5.07
5.46
5.88
7.08
8.62

16.50
17.00
17.42
18.10
—

5.59
6.04
6.50
7.58
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

034

4250
4960
5660
6370
7080

14.68
15.51
16.35
17.24
18.22

4.00
5.20
6.72
8.54
10.70

15.38
16.17
17.01
17.87
—

4.49
5.63
7.21
9.10
—

16.12
16.80
17.64
—
—

5.14
6.09
7.69
—
—

17.00
17.41
18.23
—
—

6.15
6.61
8.18
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

See Legend and Notes on page 72.

69

Performance data (cont)
FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
0.0-1.2 in. wg ESP — 50 Hz, ENGLISH
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8

0.2

1.0

1.2

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

007

1,800
2,100
2,400
2,700
3,000

419
471
524
578
633

0.21
0.31
0.44
0.61
0.81

471
519
568
619
671

0.26
0.37
0.51
0.69
0.90

564
602
645
690
738

0.37
0.49
0.64
0.84
1.07

649
679
715
755
799

0.49
0.62
0.79
0.99
1.24

727
751
781
816
856

0.63
0.77
0.94
1.15
1.41

797
819
844
875
910

0.77
0.92
1.11
1.33
1.60

862
882
905
932
963

0.92
1.09
1.28
1.51
1.79

008

2,250
2,600
3,000
3,400
3,750

290
349
579
646
705

0.10
0.19
0.70
0.99
1.31

510
561
621
683
739

0.39
0.55
0.79
1.09
1.42

594
640
695
752
804

0.51
0.70
0.96
1.29
1.63

669
709
759
813
862

0.65
0.84
1.12
1.48
1.85

739
773
818
869
915

0.79
1.00
1.30
1.67
2.05

806
834
874
920
964

0.95
1.16
1.47
1.86
2.26

870
893
928
970
1011

1.12
1.34
1.66
2.06
2.48

012

3,000
3,500
4,000
4,500
5,000

421
626
706
786
867

0.35
0.98
1.42
1.99
2.70

592
664
738
815
893

0.73
1.08
1.54
2.12
2.84

670
735
803
873
946

0.90
1.28
1.77
2.39
3.14

737
798
862
929
997

1.06
1.48
2.00
2.65
3.43

797
855
917
980
1046

1.23
1.67
2.23
2.90
3.72

854
908
967
1028
1092

1.41
1.87
2.45
3.16
4.00

908
958
1014
1073
1135

1.59
2.07
2.67
3.41
4.28

014

3,750
4,300
5,000
5,700
6,250

410
455
514
575
624

0.43
0.62
0.92
1.32
1.71

467
504
556
612
657

0.55
0.74
1.06
1.47
1.87

567
599
641
686
725

0.83
1.05
1.39
1.82
2.24

649
679
718
759
793

1.12
1.38
1.76
2.23
2.66

721
748
786
825
856

1.41
1.70
2.14
2.66
3.12

788
811
847
884
915

1.72
2.04
2.52
3.09
3.59

851
871
903
939
969

2.05
2.39
2.91
3.52
4.06

016

4,500
5,300
6,000
6,800
7,500

437
499
555
620
677

0.61
0.95
1.34
1.91
2.52

483
538
590
651
706

0.72
1.07
1.48
2.06
2.69

576
617
659
712
761

1.01
1.37
1.79
2.39
3.04

660
696
730
774
817

1.35
1.74
2.17
2.78
3.44

732
767
798
836
873

1.69
2.13
2.59
3.22
3.89

797
830
860
896
929

2.03
2.53
3.04
3.71
4.39

856
888
918
952
984

2.38
2.94
3.49
4.21
4.93

024

6,000
7,000
8,000
9,000
10,000

542
620
700
781
862

1.29
1.99
2.92
4.10
5.56

577
652
728
806
885

1.42
2.15
3.10
4.30
5.79

646
711
781
854
929

1.72
2.48
3.46
4.71
6.24

716
771
833
900
971

2.09
2.85
3.85
5.13
6.70

785
831
885
946
1012

2.51
3.28
4.29
5.58
7.18

849
890
938
993
1054

2.95
3.76
4.78
6.08
7.69

907
947
990
1039
1096

3.40
4.27
5.32
6.62
8.24

028

7,500
8,750
10,000
11,250
12,500

476
545
615
685
756

1.39
2.14
3.12
4.37
5.92

510
574
641
709
778

1.58
2.35
3.36
4.64
6.22

579
633
692
754
819

1.99
2.81
3.87
5.20
6.83

644
691
743
800
860

2.40
3.29
4.41
5.79
7.47

701
747
794
845
901

2.81
3.77
4.96
6.40
8.14

752
797
843
891
942

3.29
4.25
5.51
7.02
8.83

804
842
888
935
983

3.96
4.76
6.05
7.64
9.52

034

9,000
10,500
12,000
13,500
15,000

539
620
701
783
865

2.18
3.37
4.94
6.95
9.45

569
646
724
804
884

2.39
3.62
5.22
7.27
9.81

626
695
769
844
921

2.85
4.13
5.80
7.91
10.52

683
744
811
883
956

3.34
4.68
6.40
8.57
11.24

739
793
854
920
991

3.83
5.25
7.04
9.26
11.98

791
842
897
958
1025

4.32
5.83
7.69
9.97
12.75

837
888
940
996
1059

4.82
6.41
8.36
10.71
13.54

See Legend and Notes on page 72.

70

0.0

FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
1.4-2.4 in. wg ESP — 50 Hz, ENGLISH
UNIT
40RM
(High-Capacity
4-Row Coil)

AIRFLOW
(Cfm)

1.4

1.6

EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0

2.2

2.4

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

007

1,800
2,100
2,400
2,700
3,000

921
942
963
987
1015

1.07
1.26
1.47
1.71
1.99

975
997
1017
1039
1065

1.23
1.43
1.66
1.91
2.20

1026
1048
1069
1090
1113

1.39
1.61
1.85
2.12
2.42

1074
1097
1118
1138
1161

1.55
1.79
2.05
2.33
2.65

1120
1143
1164
1185
—

1.72
1.97
2.25
2.55
—

1164
1186
—
—
—

1.90
2.16
—
—
—

008

2,250
2,600
3,000
3,400
3,750

930
950
980
1018
1057

1.29
1.53
1.86
2.26
2.69

986
1005
1031
1065
1101

1.47
1.72
2.06
2.48
2.92

1039
1057
1081
1111
1144

1.65
1.92
2.27
2.70
3.15

1089
1107
1129
1156
1186

1.84
2.13
2.49
2.93
3.39

1136
1154
1175
—
—

2.03
2.33
2.72
—
—

1181
—
—
—
—

2.22
—
—
—
—

012

3,000
3,500
4,000
4,500
5,000

961
1005
1058
1116
1176

1.78
2.27
2.90
3.66
4.56

1012
1052
1101
1157
—

1.98
2.49
3.13
3.91
—

1062
1098
1143
1196
—

2.19
2.71
3.36
4.16
—

1111
1142
1184
—
—

2.41
2.94
3.60
—
—

1158
1186
—
—
—

2.64
3.18
—
—
—

—
—
—
—
—

—
—
—
—
—

014

3,750
4,300
5,000
5,700
6,250

912
928
956
990
1019

2.39
2.75
3.30
3.96
4.54

971
982
1007
1039
1067

2.76
3.13
3.71
4.40
5.02

1028
1036
1056
1086
1112

3.14
3.53
4.13
4.85
5.50

1083
1087
1104
1130
1156

3.54
3.94
4.56
5.31
5.99

1135
1138
1151
1174
1198

3.95
4.37
5.00
5.78
6.49

1185
1187
1196
—
—

4.36
4.81
5.46
—
—

016

4,500
5,300
6,000
6,800
7,500

912
942
971
1005
1036

2.75
3.34
3.95
4.72
5.48

967
992
1020
1054
1084

3.12
3.76
4.40
5.23
6.04

1019
1041
1067
1101
1131

3.52
4.18
4.86
5.75
6.61

1070
1088
1112
1145
1174

3.92
4.61
5.33
6.27
7.17

1120
1134
1156
1187
—

4.35
5.06
5.81
6.79
—

1168
1179
1198
—
—

4.79
5.52
6.29
—
—

024

6,000
7,000
8,000
9,000
10,000

961
1000
1041
1086
1138

3.86
4.79
5.88
7.21
8.83

1011
1050
1090
1133
1180

4.31
5.32
6.47
7.82
9.46

1058
1097
1137
1178
—

4.77
5.85
7.07
8.47
—

1104
1142
1181
—
—

5.24
6.38
7.67
—
—

1147
1184
—
—
—

5.71
6.91
—
—
—

—
—
—
—
—

—
—
—
—
—

028

7,500
8,750
10,000
11,250
12,500

874
886
930
976
1023

5.33
5.36
6.60
8.25
10.20

897
930
969
1014
1061

5.91
6.13
7.20
8.86
10.88

940
982
1007
1051
1097

6.80
7.32
7.89
9.49
11.56

990
1020
1045
1086
—

7.50
8.10
8.71
10.17
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

034

9,000
10,500
12,000
13,500
15,000

881
930
981
1035
1093

5.37
6.97
9.02
11.45
14.35

923
970
1021
1072
—

6.03
7.55
9.67
12.20
—

967
1008
1058
—
—

6.89
8.17
10.32
—
—

1020
1045
1094
—
—

8.25
8.86
10.97
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

See Legend and Notes on page 72.

71

Performance data (cont)
LEGEND AND NOTES FOR STANDARD AND HIGH-CAPACITY COIL
FAN PERFORMANCE DATA TABLES (English)
LEGEND
Bhp — Brake Horsepower Input to Fan
ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 94-98, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean
2-in. filters, and unit casing. See table at right for factory-supplied
filter pressure drop.
3. For 50 Hz units, the medium-static drive and standard motor combination is not available for 016-028 sizes. Use alternate motor if
medium-static drive is required for these sizes.

FACTORY-SUPPLIED FILTER PRESSURE DROP
— ENGLISH
UNIT
40RM
007
008
012
014
016
024
028
034

AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11
0.07
0.11
0.15
0.11
0.17
0.23
0.06
0.10
0.13
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

LEGEND AND NOTES FOR STANDARD AND HIGH CAPACITY COIL
FAN PERFORMANCE DATA TABLES (SI)
LEGEND
ESP — External Static Pressure
Bold indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 94-98, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and
034; 20 r/s for all other sizes.
2. Fan performance is based on deductions for wet coil, clean
51-mm filters, and unit casing. See table at right for factory-supplied filter pressure drop.
3. For 50 Hz units, the medium-static drive and standard motor combination is not available for 016-028 sizes. Use alternate motor if
medium-static drive is required for these sizes.

FACTORY-SUPPLIED FILTER PRESSURE DROP — SI
UNIT
40RM
007
008
012
014
016
024
028
034

72

AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

PRESSURE DROP
(Pa)
13
20
28
17
27
38
28
42
56
15
24
33
20
30
42
32
47
64
36
55
76
47
71
98

40RM ACCESSORY PLENUM AIR THROW DATA — SI
(m)
UNIT
40RM

AIRFLOW
(L/s)

007
008
012
014
016
024
028
034

1150
1400
1900
2350
2800
3800
4700
5650

Straight
11.71
13.87
16.65
13.77
15.41
18.17
23.26
25.97

VANE DEFLECTION
221/2°
45°
9.91
7.20
11.71
8.63
13.93
9.99
11.63
8.57
13.25
9.55
15.44
11.20
19.89
14.38
22.00
15.89

NOTE: Throw distances shown are for 0.381 m/sec terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(m/sec)
0.254
0.508
0.762

40RM ACCESSORY PLENUM AIR THROW DATA —
ENGLISH (Ft)
UNIT
40RM

AIRFLOW
(Cfm)

007
008
012
014
016
024
028
034

2,400
3,000
4,000
5,000
6,000
8,000
10,000
12,000

Straight
39
45
55
45
50
60
76
85

VANE DEFLECTION
221/2°
33
38
46
38
43
51
65
72

45°
24
28
33
28
31
37
47
52

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following
multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X 1.50
X 0.75
X 0.50

THROW FACTOR
X 1.50
X 0.75
X 0.50

40RM ACCESSORY PRESSURE DROP — SI (Pa)
UNIT
40RM
007

008

012

014

016

024

028

034

AIRFLOW
(L/s)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

15
25
36
20
34
51
36
56
79
18
29
43
24
39
56
41
64
91
37
59
86
50
80
114

2
3
5
2
5
8
5
10
15
2
5
5
2
5
7
5
10
15
5
7
12
7
12
17

Hot Water
25
41
60
33
57
85
60
93
132
26
43
62
36
57
82
60
93
132
67
109
157
92
147
210

HEATING COILS
Steam
25
41
60
33
57
85
60
93
132
26
43
62
36
57
82
60
93
132
67
109
157
92
147
210

Electric
9
16
26
12
24
39
26
43
65
10
17
26
14
24
37
26
43
65
22
39
60
32
56
85

ECONOMIZER
12
18
23
13
22
39
23
43
69
12
17
27
15
22
37
23
43
69
15
22
35
20
35
52

40RM ACCESSORY PRESSURE DROP — ENGLISH (in. wg)
UNIT
40RM
007

008

012

014

016

024

028

034

AIRFLOW
(Cfm)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.06
0.10
0.14
0.09
0.14
0.21
0.14
0.22
0.32
0.07
0.12
0.17
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46

0.01
0.01
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.01
0.02
0.02
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07

Hot Water
0.10
0.16
0.23
0.15
0.23
0.35
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

HEATING COILS
Steam
0.10
0.16
0.23
0.15
0.23
0.35
0.23
0.37
0.53
0.11
0.17
0.25
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

Electric
0.04
0.06
0.10
0.06
0.10
0.15
0.10
0.17
0.26
0.04
0.07
0.11
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34

ECONOMIZER
0.05
0.07
0.09
0.06
0.09
0.15
0.09
0.17
0.28
0.05
0.07
0.11
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21

73

Performance data (cont)
40RM HYDRONIC HEATING CAPACITIES — SI
UNIT
40RM

AIRFLOW
(L/s)
850
1150
1450
1000
1400
1800
1450
1900
2350
1750
2350
2950
2100
2800
3500
2900
3800
4700
3500
4700
5900
4250
5650
7050

007

008

012

014

016

024

028

034

1-ROW
STEAM*
Cap.

Ldb

43
53
62
48
59
71
62
72
82
108
122
136
117
129
140
135
140
146
149
166
183
164
180
196

57
53
51
55
50
47
50
46
44
66
58
53
61
53
48
53
46
41
50
44
41
47
41
38

2-ROW
HOT WATER COIL†
Water
Cap.
Ldb
Flow
(L/s)
46
59
1.0
53
53
1.2
61
50
1.3
50
56
1.1
60
50
1.3
70
47
1.5
88
65
1.9
90
54
2.0
93
48
2.0
106
65
2.3
120
57
2.6
134
52
2.9
120
62
2.6
137
55
3.0
154
51
3.3
150
58
3.3
170
52
3.7
191
49
4.1
189
60
4.1
218
53
4.7
247
50
5.4
215
57
4.7
247
51
5.4
278
48
6.0

40RM HYDRONIC HEATING CAPACITIES — ENGLISH

PD
10.2
12.8
16.0
11.5
15.3
19.5
15.0
24.7
24.5
12.4
15.2
17.9
13.3
16.2
19.5
15.6
18.6
22.3
16.9
20.8
25.4
18.5
22.8
27.7

UNIT
40RM

AIRFLOW
(Cfm)
1,800
2,400
3,000
2,250
3,000
3,750
3,000
4,000
5,000
3,750
5,000
6,250
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

007

008

012

014

016

024

028

034

1-ROW
STEAM*
Cap.

Ldb

Cap.

146
173
209
168
209
240
209
243
279
370
425
465
402
458
479
458
487
499
511
575
626
560
621
670

134
126
123
129
123
117
123
115
111
150
137
128
141
129
118
129
115
105
122
112
106
117
107
101

156.0
183.0
206.0
174.0
206.0
238.0
299.0
275.0
316.0
362.0
409.0
456.0
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
735.0
850.0
950.0

2-ROW
HOT WATER COIL†
Water
Ldb
Flow
(Gpm)
140
15.6
131
18.3
124
20.6
133
17.4
124
20.6
118
23.8
152
29.9
124
27.5
119
31.6
149
36.2
136
40.9
128
45.6
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2
136
73.5
126
85.0
119
95.0

PD
3.4
4.3
5.2
4.0
5.2
6.5
5.0
6.6
8.2
4.2
5.1
6.0
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
6.2
7.8
9.3

LEGEND
Cap. — Capacity (kW)
Ldb — Leaving-Air Dry-Bulb Temp (C)
PD
— Pressure Drop (kPa)

LEGEND
Cap. — Capacity (Btuh in thousands)
Ldb — Leaving-Air Dry-Bulb Temp (F)
PD
— Pressure Drop (ft water)

*Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam coils are
non-freeze type.
†Based on 93.3 C entering-water temperature, 11.1 C water temperature drop,
15.6 C entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 1207 kPag at 204.4 C.

*Based on 5 psig steam, 60 F entering-air temperature. All steam coils are nonfreeze type.
†Based on 200 F entering-water temperature, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 175 psig at 400 F.
Capacity (Btuh)
1.1 x cfm
3. See Heating Correction Factors table.

Capacity (kW)
1.23 x 10-3 x L/s
3. See Heating Correction Factors table.

2. Leaving db = ent db (F) +

2. Leaving db = ent db (C) +

40RM HEATING CORRECTION FACTORS — SI
Water Temp
Drop
(C)

5

11

16

Steam Pressure
(kPag)
0
14
35

HOT WATER COIL
Ent Water
Entering-Air Temp (C)
Temp
4
10
16
20
(C)
60
0.72
0.64
0.55
0.50
70
0.87
0.79
0.71
0.65
80
1.02
0.94
0.86
0.80
90
1.17
1.09
1.01
0.95
100
1.32
1.24
1.16
1.10
60
0.65
0.56
0.48
0.42
70
0.80
0.72
0.63
0.58
80
0.95
0.87
0.79
0.73
90
1.10
1.02
0.94
0.89
100
1.26
1.18
1.09
1.04
60
0.56
0.48
0.39
0.33
70
0.72
0.63
0.55
0.49
80
0.87
0.79
0.70
0.65
90
1.02
0.94
0.86
0.81
100
1.18
1.10
1.02
0.97

4
1.07
1.10
1.14

STEAM COIL
Entering-Air Temp (C)
10
16
20
0.99
0.91
0.86
1.02
0.95
0.90
1.07
0.99
0.95

40RM HEATING CORRECTION FACTORS — ENGLISH

25
0.43
0.58
0.73
0.89
1.04
0.35
0.51
0.66
0.82
0.97
0.26
0.42
0.58
0.74
0.90

25
0.80
0.84
0.89

NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air
temperature using formula in Note 2 of Hydronic Heating Capacities table.

74

Water Temp
Drop
(F)

10

20

30

Steam Pressure
(kPag)
0
2
5

HOT WATER COIL
Ent Water
Entering-Air Temp (F)
Temp
40
50
60
70
(F)
140
0.72
0.64
0.57
0.49
160
0.89
0.81
0.74
0.66
180
1.06
0.98
0.90
0.83
200
1.22
1.15
1.07
1.00
220
1.39
1.32
1.24
1.17
140
0.64
0.57
0.49
0.41
160
0.81
0.74
0.66
0.58
180
0.98
0.91
0.83
0.75
200
1.15
1.08
1.00
0.93
220
1.32
1.25
1.17
1.10
140
0.56
0.49
0.41
0.33
160
0.74
0.66
0.58
0.51
180
0.91
0.83
0.76
0.68
200
1.08
1.00
0.93
0.85
220
1.25
1.18
1.10
1.03

40
1.06
1.09
1.13

STEAM COIL
Entering-Air Temp (F)
50
60
70
0.98
0.91
0.85
1.02
0.95
0.89
1.06
1.00
0.93

80
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95

80
0.78
0.82
0.87

NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually operating. Correct leaving-air
temperature using formula in Note 2 of Hydronic Heating Capacities table.

Typical piping and wiring
ROOFTOP INSTALLATION — 38AK007-012, 38AKS008-012

LEGEND
LLSV — Liquid Line Solenoid Valve
NEC — National Electrical Code
TXV — Thermostatic Expansion Valve
*Accessory item.
†Field supplied.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

75

Typical piping and wiring (cont)
ROOFTOP INSTALLATION — 38AKS013-024

LEGEND
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.
†Double riser may be required. See Application Data,
page 90.

76

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer
to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

GROUND LEVEL INSTALLATION — 38AKS013-024

LEGEND
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
migration to the compressor.
5. Internal factory-supplied TXVs not shown.

77

Typical piping and wiring (cont)
ROOFTOP INSTALLATION — 38AKS028-044

LEGEND
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.
†Double riser may be required. See Application Data on page 93.

78

NOTES:
1. All piping must follow standard refrigerant piping techniques.
Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national
codes.
3. Wiring and piping shown are general points-of-connection
guides only and are not intended for, or to include all details for,
a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

GROUND-LEVEL INSTALLATION — 38AKS028-044

LEGEND
TXV — Thermostatic Expansion Valve
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.

79

Electrical data
38AK007-012, 38AKS008-044
UNIT
38AK
007
008
012
S008
S009
S012
S013
S014
S016
S024
S028
S034

S044

FLA —
HACR —
LRA —
MCA —
MOCP—
NEC —
OFM —
RLA —

NOMINAL VOLTAGE
(V-Ph-Hz)
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50
346-3-50
230-3-50
400-3-50

VOLTAGE RANGE*
Min
Max
198
242
360
440
198
242
360
440
198
242
360
440
198
253
342
460
198
253
342
460
198
253
342
460
198
264
342
457
198
264
342
457
198
264
342
457
311
380
198
254
342
440
311
380
198
254
342
440
311
380
198
254
342
440
311
380
198
254
342
440

LEGEND
Full Load Amps
Heating, Air Conditioning, Refrigeration
Locked Rotor Amps
Minimum Circuit Amps per NEC Section 430-24
Maximum Overcurrent Protection
National Electrical Code (U.S.A. Standard)
Outdoor-Fan Motor
Rated Load Amps (Compressor)

*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Value in parenthesis ( ) is FLA of second fan motor.
**Fuse or HACR circuit breaker.

FIELD POWER WIRE SIZE
UNIT
38AKS
028
034
044

VOLTAGE
(3 Ph, 50 Hz)
346
230
400
346
230
400
346
230
400

FIELD POWER WIRE SIZE
TB1 WILL ACCEPT
14 to 2/0 AWG
14 to 2/0 AWG
6 AWG to 350 kcmil
14 to 2/0 AWG
14 to 2/0 AWG
6 AWG to 350 kcmil
14 to 2/0 AWG

LEGEND
AWG — American Wire Gage
kcmil — Thousand circular mils (formerly MCM)
TB
— Terminal Block

80

COMPRESSOR
RLA
LRA
21.8
158
10.0
79
28.8
195
14.7
95
37.8
239
17.2
125
31.5
160
15.7
80
39.7
198
19.9
99
39.7
198
19.9
99
32.9
128
20.0
74
35.7
143
22.1
83
47.9
200
29.3
115
33.3
115
67.9
207
34.6
173
44.9
155
76.9
205
43.6
223
53.9
176
85.9
220
50.0
253
79.5
240
105.1
327
65.4
345

Qty
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3

OFM
FLA (ea)†
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
3.5 (2.9)
4.4
6.4
3.0
4.4
6.4
3.0
4.4
6.4
3.0

POWER SUPPLY
MCA
MOCP**
28.8
35
14.0
20
37.5
45
19.9
25
48.8
60
23.0
30
40.9
50
21.1
25
51.1
60
26.4
30
52.7
60
26.3
30
47.5
80
31.4
50
51.0
80
34.0
50
66.9
100
43.0
70
50.5
80
88.1
150
49.3
80
64.9
100
109.0
175
60.5
100
76.1
125
120.2
200
68.5
110
112.6
175
150.6
250
90.8
150

NOTES:
1. Control circuit is 24 v on all units and requires an external power
source.
2. MCA and MOCP values are calculated in accordance with NEC
(National Electric Code) (U.S.A. Standard), Article 440.
3. Motor FLA and RLA values are established in accordance with UL
(Underwriters’ Laboratories) Standard 1995 (U.S.A. standard).
4. 38AKS028-044 Units Only:
220-v and 346-v units are part-wind-start units; the value under compressor LRA is for the first winding energized. The 400-v units are
across-the-line-start units; value shown is for all windings energized.

40RM STANDARD MOTORS
FAN MOTOR
UNIT
40RM
007
008
012
014
016
024
028
034

V*-PH-Hz

VOLTAGE
LIMITS

kW (Hp)

FLA

230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50

207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440

1.79 (2.4)
1.79 (2.4)
1.79 (2.4)
1.79 (2.4)
2.16 (2.9)
2.16 (2.9)
2.16 (2.9)
2.16 (2.9)
2.16 (2.9)
2.16 (2.9)
3.73 (5.0)
3.73 (5.0)
5.59 (7.5)
5.59 (7.5)
7.46 (10.0)
7.46 (10.0)

5.2
2.6
5.2
2.6
7.5
3.4
7.5
3.4
7.5
3.4
13.2
7.6
19.8
11.4
28.0
16.1

LEGEND
FLA — Full Load Amps
MOCP— Maximum Overcurrent Protection

POWER SUPPLY
Minimum
Circuit
MOCP
Amps
6.5
15
3.3
15
6.5
15
3.3
15
9.4
15
4.3
15
9.4
15
4.3
15
9.4
15
4.3
15
16.5
25
9.5
15
24.8
40
14.3
25
35.0
60
20.1
30

*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.

40RM ALTERNATE MOTORS
FAN MOTOR
UNIT
40RM
007
008
012
014
016
024
028

V*-PH-Hz

VOLTAGE
LIMITS

kW (Hp)

FLA

230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50

207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440

1.79 (2.4)
1.79 (2.4)
2.16 (2.9)
2.16 (2.9)
3.73 (5.0)
3.73 (5.0)
3.73 (5.0)
3.73 (5.0)
3.73 (5.0)
3.73 (5.0)
5.59 (7.5)
5.59 (7.5)
7.46 (10.0)
7.46 (10.0)

5.2
2.6
7.5
3.4
13.2
7.6
15.2
7.6
13.2
7.6
19.8
11.4
28.0
16.1

LEGEND
FLA — Full Load Amps
MOCP— Maximum Overcurrent Protection

POWER SUPPLY
Minimum
Circuit
MOCP
Amps
6.5
15
3.3
15
9.4
15
4.3
15
16.5
25
9.5
15
19.0
30
9.5
15
16.5
25
9.5
15
24.8
40
14.3
25
35.0
60
20.1
30

*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.

40RM FAN CONTACTOR COIL
UNIT
40RM

VOLTAGE
(vac)

007-034

24

MAXIMUM
HOLDING
VA
10

81

Electrical data (cont)
40RM ELECTRIC HEATER DATA
UNIT
40RM

FAN MOTOR

HEATER
PART NO.

V-PH-Hz

CAELHEAT001A00

240-3-50

CAELHEAT002A00

400-3-50

CAELHEAT004A00

240-3-50

CAELHEAT005A00

400-3-50

CAELHEAT007A00

240-3-50

CAELHEAT008A00

400-3-50

CAELHEAT010A00

240-3-50

CAELHEAT011A00

400-3-50

CAELHEAT013A00

240-3-50

CAELHEAT014A00

400-3-50

CAELHEAT016A00

240-3-50

CAELHEAT017A00

400-3-50

CAELHEAT019A00

240-3-50

CAELHEAT020A00

400-3-50

CAELHEAT022A00

240-3-50

CAELHEAT023A00

400-3-50

CAELHEAT025A00

240-3-50

CAELHEAT026A00

400-3-50

007-012

008-012

014-024

016-024

82

Hp

kW

FLA

2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.4
2.9
5.0
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5

1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
1.79
2.16
3.73
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59

5.2
7.5
15.2
2.6
3.4
7.6
5.2
7.5
15.2
2.6
3.4
7.6
5.2
7.5
15.2
2.6
3.4
7.6
5.2
7.5
15.2
2.6
3.4
7.6
5.2
7.5
15.2
2.6
3.4
7.6
7.5
13.2
19.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
13.2
19.8
3.4
7.6
11.4

Nominal
Capacity
(kW)
5
5
5
5
5
5
10
10
10
10
10
10
15
15
15
15
15
15
25
25
25
25
25
25
35
35
35
35
35
35
10
10
10
10
10
10
20
20
20
20
20
20
30
30
30
30
30
30
50
50
50
50
50
50

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1

Stage 2

Total

5.0
5.0
5.0
3.5
3.5
3.5
10.0
10.0
10.0
6.9
6.9
6.9
15.0
15.0
15.0
10.4
10.4
10.4
15.0
15.0
15.0
10.4
10.4
10.4
20.0
20.0
20.0
13.9
13.9
13.9
10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8

—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
10.0
10.0
10.0
6.9
6.9
6.9
15.0
15.0
15.0
10.4
10.4
10.4
—
—
—
—
—
—
—
—
—
—
—
—
10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9

5.0
5.0
5.0
3.5
3.5
3.5
10.0
10.0
10.0
6.9
6.9
6.9
15.0
15.0
15.0
10.4
10.4
10.4
25.0
25.0
25.0
17.4
17.4
17.4
35.0
35.0
35.0
24.3
24.3
24.3
10.0
10.0
10.0
6.9
6.9
6.9
19.9
19.9
19.9
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
50.0
50.0
50.0
34.7
34.7
34.7

FLA
12.0
12.0
12.0
5.00
5.00
5.00
24.1
24.1
24.1
10.0
10.0
10.0
36.1
36.1
36.1
15.0
15.0
15.0
60.1
60.1
60.1
25.1
25.1
25.1
84.2
84.2
84.2
35.1
35.1
35.1
24.1
24.1
24.1
10.0
10.0
10.0
47.9
47.9
47.9
20.0
20.0
20.0
72.2
72.2
72.2
30.1
30.1
30.1
120.3
120.3
120.3
50.1
50.1
50.1

MCA*

MOCP*

21.5
24.4
34.0
9.5
10.5
15.8
36.6
39.4
49.2
15.8
16.8
22.0
51.6
54.5
64.1
22.0
23.0
28.3
81.7
84.6
94.2
34.6
35.6
40.8
111.7
114.6
124.2
47.1
48.1
53.4
39.4
46.6
54.8
16.8
22.0
26.8
69.2
76.3
84.6
29.3
45.1
49.2
99.6
106.7
115.0
41.8
47.1
51.8
159.7
166.9
175.1
66.9
72.1
76.9

25
25
40
15
15
20
40
40
50
20
20
25
60
60
70
25
25
30
90
90
100
25
40
50
125
125
125
50
50
60
40
50
60
20
25
35
70
80
90
30
50
50
100
110
125
50
50
60
175
175
200
70
80
80

40RM ELECTRIC HEATER DATA (cont)
UNIT
40RM

FAN MOTOR

HEATER
PART NO.

V-PH-Hz

CAELHEAT028A00

240-3-50

CAELHEAT029A00

400-3-50

CAELHEAT031A00

240-3-50

CAELHEAT032A00

400-3-50

CAELHEAT034A00

240-3-50

CAELHEAT035A00

400-3-50

CAELHEAT037A00

240-3-50

CAELHEAT038A00

400-3-50

028,034

FLA
Hp
MCA
MOCP

—
—
—
—

Hp

kW

FLA

7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

19.8
28.0
11.4
16.1
19.8
22.8
11.4
16.1
22.8
32.2
11.4
16.1
19.8
28.8
11.4
16.1

Nominal
Capacity
(kW)
20
20
20
20
40
40
40
40
50
50
50
50
70
70
70
70

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1

Stage 2

Total

19.9
19.9
13.9
13.9
20.0
20.0
13.8
13.8
30.0
30.0
20.8
20.8
40.0
40.0
27.8
27.8

—
—
—
—
20.0
20.0
13.8
13.8
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8

19.9
19.9
13.9
13.9
40.0
40.0
27.8
27.8
50.0
50.0
34.7
34.7
70.0
70.0
48.6
48.6

FLA
47.9
47.9
20.0
20.0
96.2
96.2
39.9
39.9
120.3
120.3
50.1
50.1
168.4
168.4
70.2
70.2

MCA*

MOCP*

84.6
94.8
39.3
45.2
145.0
155.3
64.1
70.0
175.1
185.4
76.9
82.8
193.1
208.4
84.4
90.3

90
110
40
50
150
175
70
80
200
200
80
90
200
225
90
100

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection

*Values shown are for single-point connection of electric heat accessory and air handler.
NOTES:
1. MCA and MOCP values apply to both standard and alternate factory-supplied motors.
2. Electric resistance heaters are rated at 240 v and 480 v. To determine heater capacity
(kW) at unit nameplate multiply the 240-v or 480-v capacity (kW) by the multipliers
shown in the table below.
HEATER RATING
VOLTAGE
240
480

200
0.694
—

ACTUAL HEATER VOLTAGE AT SITE
208
230
240
400
440
460
0.751 0.918
1.0
—
—
—
—
—
—
0.694 0.840 0.918

480
—
1.0

3. Heater coils are 24 v and require 8 va holding current.
4. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
5. Approximate shipping weights:
CAELHEAT001A00 – 014A00 = 55 lbs each
CAELHEAT016A00 – 026A00 = 60 lbs each
CAELHEAT028A00 – 038A00 = 75 lbs each

83

Controls
Operating sequence — 38AK007-012,
38AKS008-012
At start-up, the thermostat calls for cooling. With all safety
devices satisfied, the compressor contactor and fan contactor energize, causing the compressor and outdoor-fan
motor to operate. Contacts energize, allowing the fieldsupplied and -installed indoor-fan contactor to function. A
field-supplied and -installed liquid line valve also opens,
allowing the system to function in Cooling mode. As cooling demand is satisfied, the thermostat contacts break,
deenergizing the contactor and causing the system to shut
off. The liquid line solenoid valve closes, minimizing the
potential for refrigerant migration. The compressor does
not restart until the thermostat again calls for cooling. If a
demand for cooling occurs within 5 minutes after the thermostat is satisfied, the system will not restart because of
the Time Guard® II device. After the 5-minute time period,
the system will restart as normal on thermostat demand.
The system is protected with a Cycle-LOC™ device so that
the compressor will not start if a high-pressure or lowpressure fault occurs. To reset the Cycle-LOC device, set
the thermostat to eliminate the cooling demand, then
return to original set point. This should be done only once,
and if system shuts down due to the same fault, determine
the problem before attempting to reset the Cycle-LOC
device.

Operating sequence — 38AKS013-024
When the first stage of cooling thermostat closes, the timer
starts. After approximately 3 seconds, the timer activates
the compressor and fan motor no. 1 contactors. When
the liquid pressure builds to approximately 1772 kPag
(257 psig), fan motor no. 2 is energized.
On demand for additional cooling capacity, the second
stage of the cooling thermostat closes, energizing a fieldsupplied liquid line solenoid (LLS) valve, which opens. This
increases the suction pressure, causing the compressor to
operate at higher capacity (compressor loads).
When the fan switch is set at AUTO, the indoor-air fan
cycles with the compressor. When the switch is set at
CONT, the indoor-air fan runs continuously.
At shutdown, the Time Guard II timer prevents the compressor from restarting for approximately 5 minutes.
In addition, a field-supplied solenoid valve wired in parallel with the compressor contactor coil shuts off the liquid
line to prevent refrigerant migration back to the compressor during the off cycle.

84

Operating sequence — 38AKS028-044
When space thermostat calls for cooling, the no. 1 condenser fan and compressor starts after control module
(CM) initial time delay of 3 (+2/-1) seconds. If an optional
airflow switch is used, compressor and no. 1 condensing
fan will not start until sufficient indoor airflow has closed
the switch. After 3 seconds the compressor starts and the
liquid line solenoid valve (for solenoid drop control) opens.
The crankcase heater is deenergized. If the head pressure
reaches 1793 kPag (260 psig), the second condenser fan
starts.
If cooling demand is low, suction pressure at the compressor drops. As the pressure drops, the compressor
unloads 2 banks of cylinders as required. If cooling demand
is high and 2-stage operation is used, the second step of
the thermostat activates the capacity control liquid line
solenoid which activates the second stage evaporator coil.
The compressor cylinders load or unload in response to
compressor suction pressure to meet evaporator load.
Two minutes after the compressor starts, the bypass
relay (BPR) timer is deenergized and the low-pressure
switch (LPS) bypass is deactivated. If the LPS trips during
the first 2 minutes of operation, the compressor remains
operational. If a high-pressure switch (HPS) trips at any
time, or the LPS trips after 2 minutes, the compressor cannot restart until the control circuit power is interrupted due
to the CM lockout feature.
As the space cooling load is satisfied, the second stage of
the thermostat opens, and closes the field-supplied capacity control liquid line solenoid valve to deactivate the second stage coil. The compressor adjusts the number of
active cylinders to meet the new load. When the space
temperature is satisfied, the first stage of the thermostat
opens and the control relay and the BPR open. This closes
the solenoid drop control valve. The compressor stops and
the crankcase heater is energized, preventing refrigerant
from migrating to the compressor during the off cycle
(solenoid drop refrigerant control). The CM anti-shortcycling timer is energized and runs for approximately
5 minutes. During this time, the compressor is not able to
restart.

Typical control wiring
TEMP SYSTEM APPLICATIONS — 38AK007-012, 38AKS008-012
NETWORK

BLACK (-)
RED (+)
GREEN (GRD)
RED (-)

BLACK (+)

REMOTE ROOM
TEMP. SENSOR

J3
WHITE
RED
BLUE
YELLOW
GREEN
IAQ SWITCH

FIG. “A”
HUMIDITY SENSOR
WHT
RED

WHT
RED

FAN STATUS SWITCH

HS

SEE “A”
GRN
BLK

10
11

BLACK

OAT

FILTER STATUS SWITCH
GRN
BLK

FSS

10
11

SAT

BLACK
BLACK
DX RED
RED
RED

WHT
RED
BLUE
YEL
GRN
6
7
2
1
8
9
COOL
10 LEDS
11
12
13
14
15
16
17

1
2
HEAT

ECON
FAN
H2
H1 (NC)
H1 (NO)
HT COM
FAN ECON
C2
C1
COOL COM
24 VAC
CHRS

FAN

COOL*
24 VAC
24 VAC
COMMON

SINGLE ZONE RELAY PACK CIRCUIT BOARD
LEGEND
DX
FSS
HS
IAQ
IFC
LED
LLSV
OAT
SAT
TB

—
—
—
—
—
—
—
—
—
—

Direct Expansion Coil Sensor
Filter Status Switch
Humidity Sensor
Indoor Air Quality
Indoor-Fan Contactor
Light-Emitting Diode
Liquid Line Solenoid Valve
Outdoor Air Temperature Sensor
Supply Air Temperature Sensor
Terminal Block
Marked Terminal

CONNECTION
BOARD (TB)
R

Factory Wiring

1

Field Control Wiring

Y1
2
Y2

*Single zone relay pack requires 10 va.
†Field-supplied.

3

NOTE: Humidity Sensor and filter status switch
cannot be wired at the same time.

4

W1

5
LLSV†

W2
G

6
C
7
X

IFC †

8

38AK,AKS CONDENSING UNIT

85

Typical control wiring (cont)
TEMP SYSTEM APPLICATIONS — 38AKS013-024
NETWORK

BLACK (-)
RED (+)
GREEN (GRD)
RED (-)

REMOTE ROOM
TEMP. SENSOR

BLACK (+)
J3
WHITE
RED
BLUE
YELLOW
GREEN
IAQ SWITCH

FIG. “A”
HUMIDITY SENSOR
WHT
RED

WHT
RED

FAN STATUS SWITCH

HS

SEE “A”
GRN
BLK

BLACK

10
11

OAT

SAT

FILTER STATUS SWITCH
FSS

GRN
BLK

BLACK
BLACK
DX RED
RED
RED

10
11

WHT
RED
BLUE
YEL
GRN
6
7
2
1
8
9
COOL
LEDS
10
11
12
13
14
15
16
17

1
2
HEAT

ECON
FAN
H2
H1 (NC)
H1 (NO)
HT COM
FAN ECON
C2
C1
COOL COM
24 VAC
CHRS

FAN
HEAT 2
HEAT 1
COOL 2
COOL 1
R
24 VAC
COMMON

SINGLE ZONE RELAY PACK CIRCUIT BOARD

TERMINAL BLOCK (TB2)
IN CONTROL BOX
1

c

TIME GUARD® CIRCUIT

2
3
4
5
6
7
NOTE 1

8

IFC
LLSV*

9
R1

NOTE 2
R2

C
DX
FSS
HD
HS
IAQ
IFC
LED
LLSV
OAT
R

—
—
—
—
—
—
—
—
—
—
—

SAT

—

LEGEND
Compressor Contactor
Direct Expansion Coil Sensor
Filter Status Switch
Heating Device
Humidity Sensor
Indoor Air Quality
Indoor Fan Contactor
Light-Emitting Diode
Liquid Line Solenoid Valve
Outdoor Air Temperature Sensor
Heat Control Relay (field-supplied, 24-volt
seated coil, 10-va max rating)
Supply Air Temperature Sensor
Factory Wiring
Field Control Wiring

86

L2

HD1

R1
L1

HD2
R2

*Field supplied.
NOTES:
1. Combination LLSV plus IFC VA should not exceed 30 VA.
2. Do not exceed 5 VA (24 VAC) per coil.
3. If the VA values in Notes 1 and 2 must be exceeded, use accessory
relay-transformer package 38AE900001.
4. Wiring diagrams are general guides only and are not intended for a
specific installation. Refer to individual product installation and wiring
literature.
5. Humidity Sensor and filter status switch cannot be wired at the same
time.

87

—

—
—
—

LLS2

LLSV
NEC
TB

Factory-Installed Wiring

Field Control Wiring

LEGEND
Airflow Switch
Circuit Breaker
Equipment
Fuse
Ground
Liquid Line Solenoid for
Solenoid Drop Control
Liquid Line Solenoid for
Capacity Control
Liquid Line Solenoid Valve
National Electrical Code
Terminal Block
Field Power Wiring

NOTES:
1. Factory wiring in accordance with
NEC. Any field modifications or
additions must be in compliance
with all applicable codes.
2. All field interlock contacts must
have minimum rating of 180-va
pilot duty plus capacity required
for field-installed equipment. All
field interlock contacts in the 24-v
control circuit must have minimum rating of 70-va pilot duty
plus capacity required for fieldinstalled equipment.
3. For internal unit wiring, reference
wiring book or unit wiring label
diagram. TB2 is 115-1-60, TB3 is
24-1-60.
4. The following components are
not located in the 38AKS unit
control box: LLS1, LLS2, field
control thermostat, AFS, alarm
shut-off switch, and alarm or
light.

*Field-supplied.

—
—
—
—
—
—

AFS
CB
EQUIP
FU
GND
LLS1

BLU

GRN
BLK

WHT
RED
10
11

WHT
RED

FSS

GRN
BLK
10
11

FILTER STATUS SWITCH

HS

FIG. “A”
HUMIDITY SENSOR

REMOTE ROOM
TEMP. SENSOR

NETWORK

TO COMPRESSOR

YEL

BLACK (-)
RED (+)
GREEN (GRD)

SEE “A”
BLACK
BLACK
OAT SAT DX BLACK
RED
RED
RED

FAN STATUS SWITCH

WHITE
RED
BLUE
YELLOW
GREEN
IAQ SWITCH

BLACK (+)

RED (-)

BRN

22

C1A

12

ORN

23

C2

13
+

1
2
HEAT

4
+ TB2

3

2

1

ECON
FAN
H2
H1 (NC)
H1 (NO)
HT COM
FAN ECON
C2
C1
COOL COM
24 VAC
CHRS

R

HEAT 1

FAN
HEAT 2

COOL 2
COOL 1
R
24 VAC
COMMON

W

Y

GND
AFS

GND

LLS1*

SINGLE ZONE RELAY PACK CIRCUIT BOARD

WHT
RED
BLUE
YEL
GRN
6
7
2
1
8
9 LEDS COOL
10
11
12
13
14
15
16
17

J3

TO COMPRESSOR

RED

21

23

22

21

BLK

C1

11

C2

13

C1

12

C1

11

EQUIP GND
(LLSV)

24V

CB2

LLS2*

21

11

22

12

23

13

A

FIELD SUPPLIED

ALARM
OR
LIGHT

CB1

24

14

[63.5] 2 1/2”
OR
[92.1] 3 5/8”
DIA. HOLE

[22.2] 7/8” DIA. HOLE

7/C
8/X

6/G

2/Y1
3/Y2
4/W1
5/W2

TB3
1/R

ALARM
SHUT-OFF
SWITCH

115V

CB1

FU1

208/230V ONLY

TEMP SYSTEM APPLICATIONS — 38AKS028-044

26

16

13

23

12

22

TB1

11

21

FUSED
NEC DISCONNECT

FIELD POWER SUPPLY

25

15

EQUIP GND

Application data — 38AK007-012, 38AKS008-012
Operating limits — SI

Operating limits — English

Maximum outdoor ambient . . . . . . . . . . . . . . . . . . 52 C
Minimum return-air temperature . . . . . . . . . . . . . . 13 C
Maximum return-air temperature . . . . . . . . . . . . . . 35 C
Range of acceptable saturation
suction temperature. . . . . . . . . . . . . . . . . . –4 to 13 C
Maximum discharge temperature . . . . . . . . . . . . . 135 C
Minimum discharge superheat . . . . . . . . . . . . . . . .33° C
NOTES:
1. Select air handler at no less than 40 L/s per kW
(nominal condensing unit capacity).
2. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not
exceed 20 volt-amperes (va). If the specified voltamperes must be exceeded, use a remote relay to
control the load.

Maximum outdoor ambient . . . . . . . . . . . . . . . . . . 125 F
Minimum return-air temperature . . . . . . . . . . . . . . . 55 F
Maximum return-air temperature . . . . . . . . . . . . . . . 95 F
Range of acceptable saturation
suction temperature . . . . . . . . . . . . . . . . . 25 to 55 F
Maximum discharge temperature . . . . . . . . . . . . . 275 F
Minimum discharge superheat . . . . . . . . . . . . . . . . 60° F
NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal
condensing unit capacity).
2. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not
exceed 20 volt-amperes (va). If the specified voltamperes must be exceeded, use a remote relay to control the load.

REFRIGERANT PIPING SIZES

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE

LINEAR LENGTH OF PIPING — m (ft)
0-7.6
(0-25)

UNIT
38AK

7.6-15.2
(25-50)

15.2-22.9
(50-75)

22.9-30.5
(75-100)

Line Size (in. OD)
L

S

L

S

L

S

L

S

007

1/ 2

11 / 8

1/ 2

11/8

1/ 2

11/8

1/ 2

11 / 8

008

1/ 2

11 / 8

1/ 2

11/8

5/ 8

13/8

5/ 8

13 / 8

012

1/ 2

11 / 8

5/ 8

13/8

5/ 8

13/8

5/ 8

13 / 8

S008

1/ 2

11 / 8

1/ 2

11/8

5/ 8

13/8

5/ 8

13 / 8

S009

1/ 2

11 / 8

5/ 8

11/8

5/ 8

13/8

5/ 8

13 / 8

S012

1/ 2

11 / 8

5/ 8

11/8

5/ 8

13/8

5/ 8

13 / 8

LEGEND
L — Liquid Line
S — Suction Line
NOTES:
1. Pipe sizes are based on a 1° C (2° F) loss for liquid and suction
lines.
2. Pipe sizes are based on the maximum linear length, shown for each
column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
4. Line size conversion to mm:
mm
in.
1/ 2
12.7
5/
15.9
8
1
1 /8
28.6
3
34.9
1 /8

LIQUID LINE DATA

UNIT
38AK
007
008
012
S008
S009
S012

MAX
ALLOWABLE
LIQUID LIFT

LIQUID LINE
Max Allowable
Pressure Drop

Max Allowable
Temp Loss

M

Ft

kPa

psi

C

F

23.2
15.2
17.4
15.2
15.8
15.8

76
50
57
50
52
52

48.3

7

1

2

NOTE: Values shown are for units operating at 7.2 C (45 F) saturated
suction and 35 C (95 F) entering air.

88

UNIT
38AK
007
008
012
S008
S009
S012*

COMPRESSOR
CAPACITY
(%)
100
100
100
100
100
100
67

SATURATED
CONDENSING
TEMP
C

F

32
32
32
32
32
32
27

90
90
90
90
90
90
60

MINIMUM
OUTDOOR TEMP
Base Unit
With
Low Ambient
C
F
Control†
12
53
15
60
11
52
15
60
–29 (–20)
12
53
9
48
11
52

*Unit has one step of unloading.
†38AK007 — Motormaster® I Control only. 38AK008, 38AK012,
38AKS008, 38AKS009, 38AKS012 — Motormaster III Control only.
(Motor change required on 38AK007.)

Application data — 38AKS013-024
Installation

Use of liquid line solenoid valves

Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit
cycling, and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor
unit is operating.
Ductwork should be sized according to unit size, not
building load.
To minimize the possibility of air recirculation, avoid the
use of concentric supply/return grilles.
Indoor equipment should be selected at no less than
40 L/s per kW (300 cfm/ton).

A liquid line solenoid valve is recommended.
For dual coil applications, a single liquid line solenoid
valve is required to deactivate upper second-stage coil.

LOCATION OF ONE LIQUID LINE SOLENOID
VALVE SERVING 2 COIL CIRCUITS
(Solenoid Drop Control)

OPERATING LIMITS
52 C (125 F)
See Minimum Outdoor-Air
Operating Temperature
table below.

Maximum Outdoor Ambient
Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge
Superheat

12.8 C (55 F)

LEGEND
TXV — Thermostatic Expansion Valve

35 C (95 F)
–3.9 to 12.8 C (25 to 55 F)

FACE-SPLIT COIL SUCTION AND
LIQUID LINE PIPING

135 C (275 F)
15.6 C (60 F)

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE

UNIT
38AKS

013

014

016
024

COMPRESSOR
CAPACITY
(%)

SATURATED
CONDENSING
TEMP

C
32
27
21
32
27
21
32
27
21
32
27

100
67
33*
100
67
33*
100
67
33*
100
50

F
90
80
70
90
80
70
90
80
70
90
80

MINIMUM
OUTDOOR-AIR
OPERATING
TEMPERATURE
With
Base
Low-Ambient
Unit
Control†
C
1.7
7.2
12.8
2.8
8.9
13.9
–5.0
2.2
10.0
–9.4
–6.7

F
35
45
55
37
48
57
23
36
50
15
20

C

F

–29

–20

*Requires field-installed unloader.
†Motormaster® I control — 38AKS013-024.

LIQUID LINE DATA
UNIT
38AKS

MAX
ALLOW.
LIFT —
m (ft)

013
014
016
024

15.8 (52)
20.4 (67)
25.0 (82)
26.5 (87)

LIQUID LINE
Max Allow.
Max Allow.
Pressure Drop —
Temp Loss —
kPa (psi)
C (°°F)
48 (7)

LEGEND
TXV — Thermostatic Expansion Valve

1 (2)

NOTE: Data above is for units operating at 8 C (45 F) saturated suction and 35 C
(95 F) entering air.

89

Application data — 38AKS013-024 (cont)
Oil return

Insulation

Condensing units with multiple-step unloading may
require double suction risers to assure proper oil return at
minimum load operating conditions. Reduction of evaporator coil surface should be analyzed to provide sufficient
refrigerant velocity to return oil to the compressor. Liquid
line solenoid valves may be used in certain situations to
accomplish this. Hot gas bypass, if used, should be introduced before the evaporator. Consult Carrier System
Design manual.

Refrigerant suction piping should be insulated in
accordance with guidelines set forth in the Carrier System
Design Manual.
SUCTION LINE PIPING

REFRIGERANT PIPING SIZES — SI
COND
UNIT
38AKS
013
014
016
024

LENGTH OF INTERCONNECTING PIPING (m)
0-4.5
4.5-7.5
7.5-15
15-23
23-30
Line Size (in. OD)
L
S
L
S
L
S
L
S
L
S
1/
5/8
5/8
11/8 1/2 11/8 5/8 13/8
13 / 8
13 / 8 *
2
7/8
1/2
11/8 5/8 13/8 5/8 13/8
15/8* 7/8 15/8*
5/
13/8 5/8 13/8 5/8 15/8* 7/8 15/8* 7/8 15/8*
8
7/
7/
5/
13/8 5/8 13/8 5/8 15/8
15 / 8
15 / 8
8
8
8

LEGEND
A
B
C
D

*Requires a double suction riser if 2 unloaders are used and the evaporator is below the condensing unit. See Refrigerant Piping Sizes —
Double Suction Risers table below and Suction Line Piping figure at
right for more information.
NOTES:
1. Pipe sizes are based on a 1.1 C max loss for liquid lines and 0.8 C
max loss for suction lines, selected at maximum length for each
interval and for matched systems at nominal rating conditions
nominal airflow.
2. Pipe sizes are based on an equivalent length equal to the maximum length of interconnecting piping plus 50% for fittings. A more
accurate estimate may result in smaller sizes.
3. Units must be charged in accordance with the unit installation
instructions.
4. Line size conversion to mm:
mm
in.
1/2
12.7
5/8
15.9
7/
22.2
8
1
28.6
1 /8
3
34.9
1 /8
5
41.3
1 /8
1
54.0
2 /8
5
66.7
2 /8
1
79.4
3 /8

REFRIGERANT PIPING SIZES —
DOUBLE SUCTION RISERS — SI
COND
UNIT
38AKS
013
014
016

LENGTH OF INTERCONNECTING PIPING (m)
7.5-15
18-23
23-30
Line Size (in. OD)
A
B
C
A
B
C
A
B
C
—
—
—
—
—
—
11 / 8 13 / 8 15 / 8
—
11 / 8

—
13 / 8

—
15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

NOTES:
1. See Suction Line Piping figure for “A,” “B,” and “C” dimensions.
2. No double suction risers are needed for unit size 024.

— Suction riser without trap
— Suction riser with trap
— Horizontal suction line to
condensing unit
— Short vertical riser:
38AKS028 — 15/8 in. OD
38AKS034,044 — 21/8 in. OD

REFRIGERANT PIPING SIZES — ENGLISH
COND
UNIT
38AKS
013
014
016
024

LENGTH OF INTERCONNECTING PIPING (FT)
0-15
16-25
25-50
50-75
75-100
Line Size (in. OD)
L
S
L
S
L
S
L
S
L
S
5/8
5/ 8
1/2
11/8 1/2 11/8 5/8 13/8
13/8
13 / 8 *
1/
7/
11/8 5/8 13/8 5/8 13/8
15/8* 7/8 15/8*
2
8
5/8
13/8 5/8 13/8 5/8 15/8* 7/8 15/8* 7/8 15/8*
7/
7/ 8
5/8
13/8 5/8 13/8 5/8 15/8
15/8
15 / 8
8

*Requires a double suction riser if 2 unloaders are used and the evaporator is below the condensing unit. See Refrigerant Piping Sizes —
Double Suction Risers table and Suction Line Piping figure above for
more information.
NOTES:
1. Pipe sizes are based on a 2 F max loss for liquid lines and a 1.5 F
max loss for suction lines, selected at maximum length for each
interval and for matched systems at nominal rating conditions,
nominal airflow.
2. Pipe sizes are based on an equivalent length equal to the maximum length of interconnecting piping plus 50% for fittings. A more
accurate estimate may result in smaller sizes.
3. Units must be charged in accordance with the unit installation
instructions.

REFRIGERANT PIPING SIZES —
DOUBLE SUCTION RISERS — ENGLISH
COND
UNIT
38AKS
013
014
016

LENGTH OF INTERCONNECTING PIPING (FT)
25-50
50-75
75-100
Line Size (in. OD)
A
B
C
A
B
C
A
B
C
—
—
—
—
—
—
11 / 8 13 / 8 15 / 8
—
11 / 8

—
13 / 8

—
15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

11 / 8

13 / 8

15 / 8

NOTES:
1. See Suction Line Piping figure above for “A,” “B,” and “C”
dimensions.
2. No double suction risers are needed for unit size 024.

90

Multiple condensing unit arrangements*
38AKS013-024

38AKS013-024

38AKS013-024
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
†Observe minimum recommended space requirements.
38AKS
013-028

DIMENSIONS (ft)
A
B
4
4

91

Application data — 38AKS028-044
Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling, and less part-load operation.
When selecting vapor line sizes, oil return should be
evaluated, particularly at part-load conditions.
The evaporator fan must always be operating when outdoor fan is operating.
Unit cycles should be limited to 3 or less.
Multiple outdoor units may be used with a single indoor
unit. This involves multiple refrigeration circuits.
IMPORTANT: When application is in a variable air volume (VAV) system, total building load is not the sum of
the individual peak loads. If individual peak loads are
summed, the equipment tends to be oversized for the
load.

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
COMUNIT PRESSOR
38AKS CAPACITY
(%)

028
034
044

SATURATED
CONDENSING
TEMPERATURE
C
32
27
21
32
27
21
32
27
21

100
67
33
100
67
33
100
67
33

F
90
80
70
90
80
70
90
80
70

MAXIMUM LIQUID LIFT
MAXIMUM LIQUID LIFT
m
ft
23
76
20
67
23
76

UNIT 38AKS

To minimize return-air temperature extremes, use the
equipment room as a return-air plenum when applying
VAV systems with supply-to-return air recycle as used with
Carrier VVT® (variable volume and temperature) Control
Systems.
Indoor equipment should be selected at no less than
40 L/s per kW (300 cfm/ton).

MIN OUTDOOR
TEMPERATURE
With
Base
Low Ambient
Unit
Control
C
F
C
F
–6
31
1.7
35
1
34
–1
30
–20
1
34 –29
5.5
42
–3.9 25
–1
30
1.7
35

028
034
044

SUCTION LINE PIPING

OPERATING LIMITS
Maximum Cooling Load
Minimum Cooling Load

46 C (115 F)
Additional head pressure
control may be required
below 1.7 C (35 F) outdoor
ambient.

Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge Temperature
Minimum Discharge Superheat

12.8 C (55 F)

92

LEGEND

35 C (95 F)
1.1 to 12.8 C (30 to 55 F)
146 C (295 F)
15.6 C (60 F)

A
B
C
D

—
—
—
—

Suction riser without trap
Suction riser with trap
Suction line to condensing unit
Short vertical riser:
38AKS028 — 15/8 in. OD
38AKS034,044 — 21/8 in. OD

REFRIGERANT PIPE SIZES (Single Suction Risers)
UNIT
38AKS
028
034
044

LENGTH OF INTERCONNECTING PIPING — m (ft)
7.9-15.2 (26-50)
15.5-22.8 (51-75)
23.2-30.5 (76-100)
L
S
L
S
L
S
7/
7/
7/
21/8*
21/8*
21 / 8 *
8
8
8
7/8
7/8
21 / 8
21 / 8
11 / 8
21 / 8
7/8
21 / 8
11 / 8
25/8*
11 / 8
25 / 8 *

4.9-7.6 (16-25)
L
S
7/
15 / 8
8
7/
21 / 8
8
7/
21 / 8
8

LEGEND
L — Liquid Line
S — Suction Line

30.8-60.9 (101-200)
L
S
7/
21 / 8 *
8
11 / 8
25 / 8 *
11 / 8
31 / 8 *

NOTE: All line sizes are inches OD. See notes on page 73 for metric
conversions.
*IMPORTANT — If condensing unit is above air handler, a double
suction riser is required. See table below for sizing.

REFRIGERANT PIPING SIZES (Double Suction Risers)
UNIT
38AKS
028
034
044

7.9-15.2 (26-50)
A
B
C
15 / 8
21 / 8
15 / 8
—
—
—
—
—
—

LENGTH OF INTERCONNECTING PIPING — m (ft)
15.5-22.8 (51-75)
23.2-30.5 (76-100)
A
B
C
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
15 / 8
21 / 8
—
—
—
—
—
—
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8
15 / 8

30.8-60.9 (101-200)
A
B
C
15 / 8
15 / 8
21 / 8
15 / 8
21 / 8
25 / 8
15 / 8
21 / 8
25 / 8

NOTE: A, B, C dimensions relate to reference diagram.

Multiple condensing unit arrangements*

38AKS028-044

38AKS028-044

38AKS028-044 ONLY
Space for Service and Airflow
*For clearances between controls and grounded surfaces,
check local codes.
†Observe minimum recommended space requirements.
38AKS
028-044

DIMENSIONS (ft)
A
B
4
4

93

Application data — 40RM
Operating limits
Maximum fan speed —
40RM007-024 . . . . . . . . . . . . . . . .20 r/s (1200 rpm)
Maximum fan speed —
40RM028,034 . . . . . . . . . . . . . . 18.3 r/s (1100 rpm)

General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 40 L/s per kW (300 cfm/ton).

The air handler fan must always be operating when the
condensing unit is operating.
Ductwork should be sized according to unit size, not building load. For larger units with two fans, a split duct transition
is recommended at the fan outlets, but a plenum can be used
with slight reduction in external static pressure capability.
For variable air volume (VAV) systems with supply-toreturn air recycling, use the equipment room as a return air
plenum.

40RM FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA
UNIT
40RM
007
008
012
014
016
024
028
034

TXV
Qty...Part No.
TDEBX8
TDEBX8
TDEBX6
TDEBX8
TDEBX8
TDEBXE11
TDEBX11
TDEBX16

DISTRIBUTOR
Qty...Part No.
1...1116
1...1126
2...1115
2...1115
2...1116
2...1116
2...1126
2...1126

FEEDER TUBES
PER DISTRIBUTOR*
12
15
9
9
12
13
15
18

NOZZLE
Qty...Part No.
1...E5
1...C6
2...E4
2...E5
2...E6
2...E8
2...C10
2...C12

*Feeder tube size is 6.35 mm (1/4 in.)
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

40RM FAN MOTOR DATA
STANDARD MOTOR — SI
UNIT
40RM
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)

007

008

012

014

016

024

028

034

23.75
1.79
56Y
15.9

23.75
1.79
56Y
15.9

23.75
2.16
56Y
22.2

23.75
2.16
56Y
22.2

23.75
2.16
56Y
22.2

23.75
3.73
184T
28.6

23.75
5.60
S213T
34.9

23.75
7.46
S215T
34.9

LEGEND
NEMA — National Electrical Manufacturers Association (U.S.A.)
ALTERNATE MOTOR — SI
UNIT
40RM
230-3-50 and 400-3-50
Speed (r/s)
Shaft kW
Frame (NEMA)
Shaft Dia (mm)

007

008

012

014

016

024

028

23.75
1.79
56Y
15.9

23.75
2.16
56Y
22.2

23.75
3.73
S184T
22.2

23.75
3.73
S184T
28.6

23.75
3.73
S184T
28.6

23.75
5.60
S213T
34.9

23.75
7.46
S215T
34.9

LEGEND
NEMA — National Electrical Manufacturers Association (U.S.A.)

94

40RM FAN MOTOR DATA (cont)
STANDARD MOTOR — ENGLISH
UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

007

008

012

014

016

024

028

034

1425
2.4
56Y
5/
8

1425
2.4
56Y
5/
8

1425
2.9
56Y
7/
8

1425
2.9
56Y
7/
8

1425
2.9
56Y
7/
8

1425
5.0
184T
11 / 8

1425
7.5
S213T
13 / 8

1425
10.0
S215T
13 / 8

LEGEND
NEMA — National Electrical Manufacturers Association (U.S.A.)
ALTERNATE MOTOR — ENGLISH
UNIT
40RM
230-3-50 and 400-3-50
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

007

008

012

014

016

024

028

1425
2.4
56Y
5/
8

1425
2.9
56Y
7/
8

1425
5.0
S184T
7/
8

1425
5.0
S184T
11 / 8

1425
5.0
S184T
11 / 8

1425
7.5
S213T
13 / 8

1425
10.0
S215T
13 / 8

LEGEND
NEMA — National Electrical Manufacturers Association (U.S.A.)

40RM DRIVE DATA
STANDARD DRIVE — SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of
Moveable Motor Pulley Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)

007

008

012

014

016

024

028

034

61.086.4

71.196.5

86.4111.8

86.4111.8

86.4111.8

109.2134.6

109.2134.6

109.2134.6

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

203
25.4
1—A
998

203
25.4
1—A
998

203
25.4
1—A
1024

229
36.5
1—A
1074

229
36.5
1—A
1074

218
36.5
1—B
1062

279
49.2
2—B
1113

279
49.2
2—B
1113

8.6
7.110.1
20.0

9.8
8.311.3
20.0

11.6
10.113.1
20.0

10.3
9.011.6
20.0

10.3
9.011.6
20.0

13.3
11.914.6
20.0

10.4
9.311.5
18.3

10.4
9.311.5
18.3

0.297

0.297

0.297

0.265

0.265

0.230

0.180

0.180

5

5

5

5

5

6

6

6

265-313

265-313

265-313

265-313

265-313

232-279

169-240

169-240

95

Application data — 40RM (cont)
40RM DRIVE DATA (cont)
MEDIUM-STATIC DRIVE — SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of Moveable
Motor Pulley Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)

007

008

012

014

016

024

028

034

86.4111.8

86.4111.8

86.4111.8

86.4111.8

94.0119.4

101.6127.0

109.2134.6

109.2134.6

2.5

2.5

2.5

2.5

3.0

2.5

3.0

3.0

203
25.4
1—A
1024

178
25.4
1—A
1049

152
25.4
1—A
947

191
36.5
1—A
998

201
36.5
1—B
1011

178
36.5
2—A
922

239
49.2
2—B
1011

239
49.2
2—B
1011

11.6
10.113.1
20.0

13.2
11.514.9
20.0

15.4
13.517.4
20.0

12.4
10.813.9
20.0

12.6
11.114.1
20.0

15.3
13.617.0
20.0

12.1
10.913.4
18.3

12.1
10.913.4
18.3

0.297

0.340

0.395

0.317

0.252

0.340

0.210

0.210

5

5

5

5

6

5

6

6

265-313

265-313

265-313

265-313

232-279

232-279

169-240

169-240

HIGH-STATIC DRIVE — SI
UNIT
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
Change per 1/2 Turn of Moveable
Motor Pulley Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)

007

008

012

014

016

024

028

034

86.4111.8

86.4111.8

101.6127.0

86.4111.8

101.6127.0

101.6127.0

109.2134.6

109.2134.6

2.5

2.5

3.0

2.5

3.0

3.0

3.0

3.0

152
25.4
1—A
947

140
25.4
1—A
947

140
25.4
1—A
922

152
36.5
2—A
922

178
36.5
2—A
998

163
36.5
2—A
871

203
49.2
2—B
935

218
49.2
2—B
960

15.4
13.517.4
20.0

16.8
14.719.0
20.0

19.4
17.320.0*
20.0

15.4
13.517.4
20.0

15.3
13.617.0
20.0

16.7
14.918.6
20.0

14.3
12.815.7
18.3

13.3
11.914.6
18.3

0.395

0.432

0.360

0.395

0.283

0.308

0.247

0.230

5

5

6

5

6

6

6

6

265-313

265-313

234-279

232-279

232-279

207-255

169-240

169-240

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.

96

40RM DRIVE DATA (cont)
STANDARD DRIVE — ENGLISH
UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of Moveable
Motor Pulley Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)

007

008

012

014

016

024

028

034

2.4-3.4

2.8-3.8

3.4-4.4

3.4-4.4

3.4-4.4

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

8.0
1
1—A
39.3

8.0
1
1—A
39.3

8.0
1
1—A
40.3

9.0
17/16
1—A
42.3

9.0
17/16
1—A
42.3

8.6
17/16
1—B
41.8

11.0
115/16
2—B
43.8

11.0
115/16
2—B
43.8

517
428-606
1200

588
499-677
1200

695
606-784
1200

618
538-697
1200

18
538-697
1200

795
713-878
1200

622
557-687
1100

622
557-687
1100

17.8

17.8

17.8

15.9

15.9

13.8

10.8

10.8

5

5

5

5

5

6

6

6

10.4412.32

10.4412.32

10.4412.32

10.4412.32

10.4412.32

9.1210.99

6.679.43

6.679.43

MEDIUM-STATIC DRIVE — ENGLISH
UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of Moveable
Motor Pulley Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)

007

008

012

014

016

024

028

034

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

3.0

2.5

3.0

3.0

8.0
1
1—A
40.3

7.0
1
1—A
41.3

6.0
1
1—A
37.3

7.5
17/16
1—A
39.3

7.9
17/16
1—B
39.8

7.0
17/16
2—A
36.8

9.4
115/16
2—B
39.8

9.4
115/16
2—B
39.8

695
606-784
1200

794
692-896
1200

926
808-1045
1200

741
646-836
1200

756
667-848
1200

916
814-1018
1200

728
652-803
1100

728
652-803
1100

17.8

20.4

23.7

19.0

15.1

20.4

12.6

12.6

5

5

5

5

6

6

6

6

10.4412.32

10.4412.32

10.4412.32

10.4412.32

9.1610.99

9.1610.99

6.679.43

6.679.43

97

Application data — 40RM (cont)
40RM DRIVE DATA (cont)
HIGH-STATIC DRIVE DATA
UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

007

008

012

014

016

024

028

034

3.4-4.4

3.4-4.4

4.0-5.0

3.4-4.4

4.0-5.0

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

3.0

2.5

3.0

3.0

3.0

3.0

6.0
1
1—A
37.3

5.5
1
1—A
37.3

5.5
1
1—A
36.3

6.0
17/16
2—A
36.3

7.0
17/16
2—A
39.3

6.4
17/16
2—A
34.3

8.0
115/16
2—B
36.8

8.6
115/16
2—B
37.8

926

1010

926

916

1002

855

795

808-1045

881-1140

808-1045

814-1018

891-1113

766-944

713-878

1200

1200

1166
10361200*
1200

1200

1200

1200

1100

1100

23.7

25.9

21.6

23.7

17.0

18.5

14.8

13.8

5

5

6

5

6

6

6

6

10.4412.32

10.4412.32

9.1610.99

9.1610.99

9.1610.99

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.

98

8.1610.02

6.679.43

6.679.43

Guide specifications —
38AKS007-012, 38AKS008-012
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 19.0 to 32.9 kW (5.4 to 9.4 Tons)
Nominal
Carrier Model Numbers: 38AK, Sizes 007 to 012
38AKS, Sizes 008 to 012
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable
for on-the-ground or rooftop installation. Unit shall
consist of a reciprocating air-conditioning compressor
assembly, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit shall discharge supply air
upward as shown on contract drawings. Unit shall be
used in a refrigeration circuit matched with a packaged air-handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard 210/240-89 and 270-84 (U.S.A. standards).
B. Unit shall be manufactured in a facility registered to
ISO 9001 manufacturing quality standard.
C. Unit construction shall comply with ASHRAE 15
(U.S.A. standard) safety code latest revision and comply with NEC (U.S.A. standard).
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(U.S.A.) (scribed specimen).
E. Air-cooled condenser coils for semi-hermetic
compressor units (38AKS) shall be leak tested at
1034 kPag (150 psig) and pressure tested at
3309 kPag (480 psig). Air-cooled condenser coils for
hermetic compressor units (38AK) shall be leak tested
at 1379 kPag (200 psig), and pressure tested at
2951 kPag (428 psig).
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit manufacturer’s recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior
to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted
baked enamel finish.

C.

D.

E.

F.

G.

H.

2. A heavy-gage roll-formed perimeter base rail
with forklift slots and lifting holes shall be provided to facilitate rigging.
Fans:
1. Condenser fans shall be direct driven, propellertype, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be corrosion resistant.
Compressor:
1. Compressor shall be of the hermetic type (AK)
or semi-hermetic reciprocating type (AKS).
2. Compressor shall be mounted on vibration
isolators.
3. Semi-hermetic compressors (AKS units) shall
have crankcase heaters, oil level sight glasses,
discharge service valve, and a totally reversible
positive displacement oil pump.
4. Unloader (33% reduction) shall be standard (on
38AKS012 units only).
5. Compressors shall include overload protection.
6. The 38AK012 unit shall have a crankcase
heater.
Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved seamless copper tubes which are
then cleaned, dehydrated, and sealed.
Refrigeration Components:
Refrigeration circuit components shall include liquid
line service valve, suction line service valve, liquid filter drier, a full charge of compressor oil, and a holding charge of refrigerant. Unit 38AK012 shall include
an accumulator.
Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped with
automatic reset (after resetting first at thermostat), shall include:
a. High discharge pressure cutout.
b. Low suction pressure cutout.
Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed Btuh at a suction temperature of
. The power consumption at full load shall
not exceed
kW.
99

Guide specifications —
38AKS007-012, 38AKS008-012 (cont)
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of
or greater at condientering-air temperature at the
tions of
evaporator at
wet bulb and
dry bulb, and air entering the condens.
ing unit at
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control Accessory:
Low-ambient control shall regulate speed of
condenser-fan motor in response to the saturated condensing temperature of the unit. The
control shall maintain correct condensing pressure at outdoor temperatures down to –29 C
(–20 F). (Motor change required.)
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to the
fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper-fins mechanically bonded to copper-tubes. All copper construction shall provide protection in moderate
coastal environments.
c. Post-Coated Aluminum-Fin Coils:
Shall have a durable organic coating uniformly applied over all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall

100

4.

5.

6.

7.

8.

withstand 1,000-hour salt spray test in
accordance with ASTM B117 (U.S.A.). Coil
construction shall be aluminum fins mechanically bonded to copper tubes.
d. Post-Coated Copper-Fin Coils:
Shall have a durable organic coating uniformly applied over all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall
withstand 1,000-hour salt spray test in accordance with ASTM B117 (U.S.A.). Coil construction shall be copper fins mechanically
bonded to copper tubes.
Thermostat Controls:
a. Debonair® programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow™ display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating multi-stage thermostat with fan switch,
timeclock, LCD display, °F/°C capability,
and CCN (Carrier Comfort Network)
compatibility.
c. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
d. Non-programmable thermostat with fan
switch subbase.
Hail Guard Package:
Hail guard package shall protect coils against
damage from hail and other flying debris.
Winter Start Package:
Package shall provide a timed bypass of lowpressure switch on start-up at low-ambient
temperatures.
Condenser Coil Grille:
Grille shall add decorative appearance to unit
and protect condenser coil after installation.
Electric Solenoid Unloader:
Electric unloader valve piston, coil, and hardware
shall be supplied to convert the pressureoperated compressor unloader to electric
unloading (38AKS012 only).

Guide specifications — 38AKS013-024
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 30.4 to 64.3 kW (8.5 to 18.0 Tons),
Nominal
Carrier Model Number: 38AKS, Sizes 013-024
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable
for on-the-ground or rooftop installation. Unit shall
consist of a semi-hermetic reciprocating compressor,
an air-cooled coil, propeller-type condenser fans, and
a control box. Unit shall discharge supply air upward
as shown on contract drawings. Unit shall be used in
a refrigeration circuit to match a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard
360 (U.S.A. standard), latest edition.
B. Unit shall be manufactured in a facility registered to
ISO 9002 manufacturing quality standard.
C. Unit construction shall comply with latest edition of
ANSI/ASHRAE and with NEC (U.S.A. standard).
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(U.S.A. standards) (scribed specimen).
E. Air-cooled condenser coils shall be leak tested
at 1034 kPag (150 psig) and pressure tested at
3310 kPag (480 psig).
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as a single package only, and
shall be stored and handled per manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior
to field start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted, baked
enamel finish.
C. Fans:
1. Condenser fans shall be direct-drive propeller
type, discharging air vertically upward.
2. Condenser fan motor no. 1 shall be ball bearing
type compatible with accessory Motormaster® I
low-ambient control.
3. Shafts shall have inherent corrosion resistance.

D.

E.

F.

G.

4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
Compressor:
1. Compressor shall be serviceable, reciprocating,
semi-hermetic type.
2. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
3. Compressor shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.2 r/s
(1450 rpm).
5. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to copper tubes which are
then cleaned, dehydrated, and sealed. Aluminum
fins with an epoxy phenolic coating and copper
fins shall be available as options.
Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line
shutoff valve, suction and discharge shutoff valves,
holding charge of refrigerant R-22, and compressor
oil.
Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Five-minute Time Guard® II protection to
prevent compressor short-cycling.
c. Capacity control on the compressor shall be
by suction cutoff unloader in response to
compressor suction pressure. Electric solenoid unloading shall be available as an
accessory.
d. Head pressure control to –9.4 C (15 F) by fan
cycling. One condenser fan shall be cycled by
discharge pressure to maintain proper head
pressure.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at
thermostat)
a. High discharge-pressure cutout.
b. Low suction pressure cutout.

101

Guide specifications — 38AKS013-024 (cont)
c. Condenser fan motors to be protected
against overload condition by internal
overloads.
Manual reset at the unit
Electrical overload protection through the use of
definite-purpose contactors and calibrated, ambient compensated, magnetic trip circuit breakers.
Circuit breakers shall open all 3 phases in the
event of an overload in any one of the phases or
a single-phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed
at a suction temperature of
. The power consumption at full load shall
not exceed
kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of
or greater at conditions of
entering-air temperature at the
wet bulb and
dry
evaporator at
bulb, and air entering the condensing unit at
.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single point
connection.
3. Unit control circuit shall contain a 24-v transformer for unit control, with capacity to operate
an indoor fan interlock.
J. Special Features:
1. Low-Ambient Control:
Control shall regulate fan motor speed in
response to the saturated condensing temperature of the unit. The control shall allow the unit
to operate down to an ambient temperature of
–29 C (–20 F).
2. Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert the pressure-operated
compressor unloader to electric unloading.
3. Winter Start:
A winter start control shall be provided to
prevent nuisance tripouts at low ambient
temperatures.
4. Condenser Coil Grille Package:
Grilles shall protect the condenser coils after unit
installation.

102

5. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
6. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to the
fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper-fins mechanically bonded to copper-tubes. All copper construction shall provide protection in moderate
coastal applicationss.
c. Post-Coated Aluminum-Fin Coils:
Shall have a durable organic coating uniformly applied to all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall
withstand 1,000-hour salt spray test in
accordance with ASTM B117 (U.S.A.). Coil
construction shall be aluminum fins mechanically bonded to copper tubes.
d. Post-Coated Copper-Fin Coils:
Shall have a durable organic coating uniformly applied to all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall
withstand 1,000-hour salt spray test in
accordance with ASTM B117 (U.S.A.). Coil
construction shall be copper fins mechanically
bonded to copper tubes.
7. Thermostat Controls:
a. Debonair® programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow™ display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating multi-stage thermostat with fan switch,
timeclock, LCD display, °F/°C capability,
and CCN (Carrier Comfort Network)
compatibility.
c. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage capability, and large LCD temperature display.
d. Non-programmable thermostat with fan
switch subbase.

Guide specifications — 38AKS028-044
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 82.8 to 127.0 kW (23.5 to 35.8 Tons),
Nominal
Carrier Model Number: 38AKS, Sizes 028-044
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable
for on-the-ground or rooftop installation. Unit shall
consist of a semi-hermetic reciprocating compressor,
an air-cooled coil, propeller-type condenser fans, and
a control box. Unit shall discharge supply air upward
as shown on contract drawings. Unit shall be used in
a refrigeration circuit to match a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard
360 (U.S.A. standard), latest edition.
B. Unit shall be manufactured in a facility registered to
ISO 9002 manufacturing quality standard.
C. Unit construction shall comply with ANSI/ASHRAE
15 latest revision safety code and comply with NEC
(U.S.A. standards).
D. Unit shall be constructed in accordance with UL
standards (U.S.A.).
E. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(U.S.A.) (scribed specimen).
F. Air-cooled condenser coils shall be leak tested at
1034 kPa (150 psig) and pressure tested at 3310 kPa
(480 psig).
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled per unit manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER.)
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressor, holding charge (R-22), and special features required prior
to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted,
baked enamel finish.
2. End unit access panel shall be hinged for compressor and control box service access.
3. Lifting holes shall be provided to facilitate
rigging.

C. Fans:
1. Condenser fans shall be direct-driven propeller
type, discharging air vertically upward.
2. Condenser fan motors shall be totally enclosed,
3-phase type with class B insulation and with
permanently lubricated bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressor:
1. Compressor shall be reciprocating, serviceable,
semi-hermetic type.
2. Compressor shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an
insert-type, factory-sized crankcase heater to
control oil dilution.
3. Compressor shall be mounted on spring vibration isolators with an isolation efficiency of no
less than 95%.
4. Compressor speed shall not exceed 24.2 r/s
(1450 rpm).
5. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
available as an accessory).
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
dehydrated, and sealed. Epoxy phenolic fin coating shall be available as an option.
3. Coil shall be protected by a sheet metal casing to
eliminate the need for wind baffles for low ambient temperature operation.
4. Coil shall be protected to avoid damage due to
the elements and vandalism.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line shutoff valve, suction and discharge shutoff valves, holding
charge of refrigerant R-22, and compressor oil.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Five-minute recycle protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.
d. Capacity control on the compressor shall be
by suction cutoff unloaders in response to
compressor suction pressure. Electric
103

Guide specifications — 38AKS028-044 (cont)
solenoid unloading shall be available as an
accessory.
e. A solenoid valve shall be provided for solenoid drop control.
f. Head pressure control to –6 C (31 F) by fan
cycling. One condenser fan shall be cycled by
discharge pressure to maintain proper head
pressure.
g. Winter start control to prevent nuisance tripouts at low ambient temperatures.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at control circuit power supply)
a. High discharge-pressure cutout.
b. Low suction-pressure cutout.
c. Condenser fan motors to be protected
against overload or single-phase condition by
internal overloads.
Manual reset at the unit
a. Low oil-pressure cutout.
b. Compressor electrical overload protection
through the use of definite-purpose contactors and calibrated, ambient-compensated,
magnetic-trip circuit breakers. Circuit breakers shall open all 3 phases in the event of an
overload in any one of the phases or a
single-phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed
at a suction temperature of
. The power consumption at full load shall
kW.
not exceed
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of
or greater at conditions of:
entering-air temperature at the
evaporator at
wet bulb and
dry
bulb, and air entering the condensing unit at
.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 50 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single point
connection.
3. Unit control circuit shall contain a 24-v transformer for unit control, with capacity to operate
an indoor fan interlock.
J. Special Features:
1. Low-Ambient Control:
Control shall regulate fan motor speed in
response to the saturated condensing temperature of the unit. The control shall be capable of

104

2.

3.

4.

5.

6.

7.

maintaining a condensing temperature of
37.8 C (100 F) ± 5.6 C (10° F) with outdoor
temperatures at –28 C (–20 F). (Motor change
required.)
Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert any pressure-operated
compressor unloader to 220-v electric unloading. Accessory ModuPanel™ control box or fieldsupplied step controller shall be provided for
electrical unloading.
Hot-Gas Bypass:
A hot-gas bypass valve and a pilot line solenoid
valve shall be provided for low-load operation of
the refrigeration system.
Part-Winding Start:
Part-winding start shall be provided to reduce
inrush current and locked rotor amps on
start-up.
Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for the refrigerant circuit.
ModuPanel Control Box:
Control box shall be provided to allow system to
operate as a VAV (variable air volume) system.
Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
coastal environments. Coating shall be
applied to the aluminum fin stock prior to the
fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
Epoxy-phenolic barrier shall minimize galvanic action between dissimilar metals.
b. Copper-Fin Coils:
Shall be constructed of copper-fins mechanically bonded to copper-tubes All copper construction shall provide protection in moderate
coastal environments.
c. Post-Coated Aluminum-Fin Coils:
Shall have a durable organic coating uniformly applied to all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall
withstand 1,000-hour salt spray test in
accordance with ASTM B117 (U.S.A.). Coil
construction shall be aluminum fins mechanically bonded to copper tubes.

d. Post-Coated Copper-Fin Coils:
Shall have a durable organic coating uniformly applied to all coil surfaces. Coating
shall be deep brown color applied by a dip
and bake process to ensure complete encapsulation of all coil surfaces. Coated coil shall
withstand 1,000-hour salt spray test in
accordance with ASTM B117 (U.S.A.). Coil
construction shall be copper fins mechanically
bonded to copper tubes.
8. Thermostat Controls:
a. Debonair® programmable multi-stage thermostat with 7-day clock, holiday scheduling,

large Thermoglow™ display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating multi-stage thermostat with fan switch,
timeclock, LCD display, °F/°C capability,
and CCN (Carrier Comfort Network)
compatibility.
c. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multistage capability, and large LCD temperature
display.
d. Non-programmable thermostat with fan
switch subbase.

105

Guide specifications — 40RM
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
Size Range: 1150 to 5650 L/s (2400 to 12,000 Cfm)
Nominal Airflow
21 to 105 kW (6 to 30 Tons)
Nominal Cooling
Carrier Model Number: 40RM
Part 1 — General
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multiposition
design and shall be capable of horizontal or vertical
(upflow) installation on a floor or in a ceiling, with or
without ductwork. (Only vertical units are to be
applied without ductwork.)
B. Unit shall be used in a refrigerant circuit with a
matching air-cooled condensing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigeration (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada standards.
C. Unit insulation and adhesive shall comply with NFPA
90A (U.S.A.) requirements for flame spread and
smoke generation. Insulation shall contain an EPAregistered immobilized anti-microbial agent to effectively resist the growth of bacteria and fungi as
proven by tests in accordance with ASTM standards
G21 and 22 (U.S.A.).
D. Unit shall be manufactured in a facility registered to
the ISO 9002/BS 5750, Part 2 manufacturing quality standard.
E. Direct-expansion and chilled water coils shall be burst
tested at 2999 kPag (435 psig) and leak tested at
1034 kPag (150 psig).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer’s
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER)
Part 2 — Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling
unit that can be used in a suspended horizontal configuration or vertical (upflow) configuration. Unit shall
consist of forward-curved belt-driven centrifugal fan(s),
motor and drive assembly, prewired fan motor contactor, factory-installed refrigerant metering devices,
cooling coil, 51-mm (2-in.) disposable air filters, and
condensate drain pans for vertical or horizontal
configurations.

106

A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized
steel.
2. Cabinet panels shall be fully insulated with
12.7-mm (1/2-in.) fire-retardant material. Insulation shall contain an U.S.A. EPA-registered
immobilized anti-microbial agent to effectively
resist the growth of bacteria and fungi as proven
by tests in accordance with ASTM standards
G21 and 22 (U.S.A.).
3. Unit shall contain PVC condensate drain pans
for both vertical and horizontal applications.
Drain pans shall have connections on right and
left sides of unit to facilitate field connection.
Drain pans shall have the ability to be sloped
toward the right or left side of the unit to prevent
standing water from accumulating in pans.
4. Unit shall have factory-supplied 51-mm (2-in.)
throwaway-type filters installed upstream from the
cooling coil. Filter access shall be from either the
right or left side of the unit.
B. Coils:
Coils shall consist of 3 rows of copper tubes with
sine-wave aluminum fins bonded to the tubes by
mechanical expansion. Coil tubing shall be internally
rifled to maximize heat transfer. Suction and liquid
line connections or supply and discharge connections
shall be made on the same side of the coil.
Direct-expansion coils shall feature factory-installed
thermostatic expansion valves (TXVs) for refrigerant
control. The TXVs shall be capable of external
adjustment.
C. Operating Characteristics:
Unit shall be capable of providing
L/s (cfm)
kPag
airflow at an external static pressure of
(in. wg).
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
supplied and installed.
E. Factory-Installed Options:
1. High Capacity Coil:
The high capacity coil consists of 4 rows of
3/ -in. copper tubes with sine-wave aluminum
8
fins bonded to the tubes by mechanical expansion. Coil tubing shall be internally rifled to maximize heat transfer. Suction and liquid line
connections shall be made on the same side of
the coil. Direct-expansion coils shall feature factory-installed thermostatic expansion valves
(TXVs) for refrigerant control. The TXVs shall be
capable of external adjustment.

2. Alternate Motor and Drive:
An alternate motor and/or medium- or highstatic drive shall be available to meet the airflow
and external static pressure requirements specified on the equipment schedule.
3. External Paint:
Where conditions require, units shall be painted
with an American Sterling Gray finish.
F. Field-Installed Accessories:
1. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper
tubes and aluminum plate fins bonded to the
tubes by mechanical expansion. Coil shall be
mounted in a galvanized steel housing that shall
be fastened to the unit’s fan deck for blow-thru
heating operation. Coil shall have maximum
working pressure of 1034 kPag (150 psig).
2. Steam Distributing Coil:
Coil shall consist of one row of copper tubes
with aluminum plate fins, and shall have inner
steam distributing tubes. Coil shall be mounted in
a galvanized steel housing and shall be fastened
to the unit’s fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 1207 kPag at 204.4 C (175 psig at
400 F).
3. Electric Heaters:
Heaters for nominal 230 or 400-volt, 3-phase
power supply shall be factory-supplied for field
installation as shown on the equipment drawings. Electric heat assembly shall be ETL (U.S.A)
and ETL Canada agency approved, and shall
have single-point power wiring. Heater assembly
shall include contactors with 24-v coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged access panel. Electric heaters shall not
be used with air discharge plenum.
4. Air Discharge Plenum:
Plenum shall be factory supplied to provide freeblow air distribution for vertical floor-mounted
units. A grille with moveable vanes for horizontal
or vertical airflow adjustment shall be included.
Plenum shall be field-assembled and fieldinstalled on the unit’s fan deck for blow-thru air
distribution. Plenum shall not be used with electric heaters.
5. Return-Air Grille:
Grille shall be factory supplied for field installation on the unit’s return air opening.
6. Unit Subbase:
Subbase assembly shall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection.

7. Economizer:
Economizer for ventilation or “free” cooling shall
be factory provided for field installation. For free
cooling applications, economizer shall be compatible with factory-supplied thermostat; economizer dampers shall open when outdoor air
enthalpy is suitable for free cooling. Economizer
shall be compatible with separate CO2 sensor
accessory; economizer dampers shall open when
indoor CO2 level rises above predetermined set
point. Economizer shall include enthalpy control
and damper actuator.
8. Thermostat Controls:
a. Debonair® programmable multi-stage thermostat with 7-day clock, holiday scheduling,
large Thermoglow™ display, remote sensor
capability, and Title 24 compliance.
b. TEMP System programmable communicating
multistage thermostat with fan switch, timeclock, LCD display, °F/°C capability, and
CCN (Carrier Comfort Network) compatibility.
c. Commercial Electronic Thermostat with
7-day timeclock, auto-changeover, multi-stage
capability, and large LCD temperature
display.
d. Non-programmable thermostat with fan
switch subbase.
9. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
10. CO2 Sensor:
Sensor shall provide the ability to signal the
economizer to open when the space CO2 level
exceeds the predetermined set point. Sensor
shall have the capability of being directly connected to Comfort System relay pack or to economizer using field- supplied and -installed
Honeywell dc adapter no. Q769C1004.
11. Condensate Drain Trap:
Trap accessory shall include an integral overflow
switch that shall cause the air conditioning system to shut down if the trap fails to drain.
12. UV-C Germicidal Lamps:
a. UV-C emitters and fixtures shall be specifically designed for use inside an HVAC system. An ASME nozzled test apparatus using
a 45 F (7.2 C) airstream moving at not less
than 400 fpm (189 liters/sec.) shall measure
individual lamp output. Lamp output at
253.7 nm shall not be less than 10µW/cm2
per inch of arc length measured at a distance
of one meter.
b. UV-C power supplies shall be high efficiency, electric type which are matched to
the emitters and are capable of producing
the specified output intensity with an input
power no more than 80 watts.

107

Guide specifications — 40RM (cont)
either directly or indirectly through reflection.
e. Emitters and fixtures shall be installed at
right angles to the conforming lines of the
coil fins, such that through incident angle
reflection, UV-C energy strikes all target
surfaces of the coil, drain pan, and the
available line of sight airstream.

c. Emitters and fixtures shall be installed in
sufficient quantity and arranged so as to
provide an equal distribution of UV-C
energy on the coil and drain pan.
d. The minimum UV-C energy striking the
leading edge of the coil fins shall be not
less than 820 µW/cm2 at the closest point
and through placement, not less than
60% of that value at the farthest point.
Equal amounts are to strike the drain pan,

Carrier Corporation • Syracuse, New York 13221

2-01

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2 4
New Book 2
Pg 108
Catalog No. 013-823
Printed in U.S.A.
Form 38A-C5PD
Replaces: 38A-C4PD
Tab 3a 1a 2a
Tab AC2



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Create Date                     : 2001:02:28 16:13:29
Producer                        : Acrobat Distiller 4.0 for Windows
Author                          : cact04p
Creator                         : ADOBEPS4.DRV Version 4.20
Title                           : 38a-c5pd.fm
Modify Date                     : 2001:02:28 16:13:30-05:00
Page Count                      : 108
EXIF Metadata provided by EXIF.tools

Navigation menu