38ARZ/ARD
Commercial Air-Cooled Split
Sizes 007 - 028
With 40RM007-028
5-24 Nominal Tons - 50Hz

Product Data
The 38ARZ/ARD condensing units with scroll compressors match Carrier’s 40RM
indoor-air handlers for a wide selection of dependable commercial cooling solutions.

Carrier’s air-cooled split systems:
• provide a logical solution for
commercial needs
• have a rugged, dependable
construction

Features/Benefits

These
dependable
split
systems
match
Carrier’s
indoor-air handlers and directexpansion coils with outdoor
condensing units for a wide
selection
of
commercial
cooling solutions.
Up to 11.0 EER

The high efficiency split commercial split
system combining the ARZ/ARD
outdoor condensing unit with 0RM air
handling unit can save 0-% of energy
consumption.

Constructed for long life

The ARZ (single circuit, scroll
compressor) and ARD (dual circuit,
scroll compressor) models are designed and
built to last. The copper tube-aluminum fin
outdoor coil construction provides years of
trouble-free operation. Where conditions
require, a range of Enviro-Shield™ coil
protection options are available. Cabinets
are constructed of prepainted galvanized
steel, delivering unparalleled protection
from the environment. Inside and outside
surfaces are protected to ensure long life,
good looks, and reliable operation. Safety
controls are used for enhanced system
protection
and
reliability.

38AR-03 PD 50Hz CKAC 2010


Efficient operation

The pitched, non-corroding drain pan can be adjusted
for a right-hand or left-hand connection to suit many
applications and provide positive drainage and prevent
standing condensate.

Building owners will appreciate the high unit EERs
(Energy Efficiency Ratios) offered by the AR units.
These units provide greater efficiency than similar
units in the marketplace, which translates into yearround operating savings.

Economy — The 0RM Series packaged air handlers
have low initial costs, and provide reduced installation
expense and energy-efficient performance.
Quick installation is ensured by the multipoise design.
Units can be installed in either the horizontal or
vertical configuration without modifications. Fan
motors and contactors are prewired and thermostatic
expansion valves (TXVs) are factory-installed on all
0RM models.
High efficiency, precision-balanced fans minimize air
turbulence, surging, and unbalanced operation, cutting
operation expenses.

Controls for performance dependability

The AR condensing units offer the building owner
operating controls and components designed for
performance dependability. The highly efficient
compressors are engineered for long life and
durability. The compressors include overload
protection and vibration isolation for quiet operation.
The high pressure switch protects the entire
refrigeration system from abnormally high operating
pressures. A low pressure switch protects the system
from loss of charge.
The ARD0-08 units feature  compressors and 
refrigerant circuits that provide continuous air
conditioning and design flexibility.
All units include a crankcase heater to eliminate liquid
slugging at start-up. The latest safety standards for
AR units are UL, compliant.

Rugged dependability — The 0RM series units are
made to last. The die-formed galvanized steel panels
ensure structural integrity under all operating
conditions. Galvanized steel fan housings are securely
mounted to a galvanized steel fan deck. Rugged
pillow-block bearings (0RM0-0) are securely
fastened to the solid steel fan shaft with split collets
and clamp locking devices. Smaller unit sizes have
spider-type bearings.

Innovative Carrier 40RM packaged air
handlers are custom matched to 38AR
condensing units

Coil flexibility — Model 0RM directexpansion coils
have galvanized steel casings; inlet and outlet
connections are on the same end. The coils are
designed for use with R- refrigerant and have /-in.
diameter copper tubes mechanically bonded to
aluminum sine-wave fins.
The coils include matched, factoryinstalled
thermostatic expansion valves (TXVs) with matching
distributor nozzles.

The 0RM Series has excellent fan performance,
efficient direct-expansion (DX) coils, a unique
combination of indoor-air quality options, and is easy
to install. Its versatility and state-of-the art features
help to ensure economical performance of the split
system both now and in the future.
Indoor-air quality (IAQ) features —
The unique combination of IAQ features in the 0RM
Series air handlers help to ensure that only clean,
fresh, conditioned air is delivered to the occupied
space.
Direct-expansion (DX) cooling coils prevent the buildup of humidity in the room, even during part-load
conditions. Unit sizes of 0 tons and larger feature
dual-circuit coils for improved temperature control.
Standard -in. aluminum washable filters remove dust
and airborne particles from the occupied space for
cleaner air.

Easier installation and service —
The multipoise design and component layout ensures
quick unit installation and operation. Units can be
converted from horizontal to vertical operation by
simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters,
motor, drive, TXVs, and coil connections are all easily
accessed by removing side panels.




Model number nomenclature
38AR

Z

007

--

-

9

Type
38AR–Commercial AirCooled Condenser

0

1

S

S - High Ambient
Packaging
1 - Standard

Z-Single Circuit
D- Dual Circuit

Design Series
0 - Original Design

Nominal Capacity in-Tons
007 - 5.0 Tons
008 - 7 0
. Tons
012 - 8.7 Tons
014 - 10.8 Tons
016 - 14 Tons
024 - 18.1 Tons
028 - 24 Tons

Voltage
9 – 400–3–50
Fin Type
-- - Standard Bare Fins
C- Cu/Cu Coil
P- Pre-Coated Blue Fins

-- - Not Used

Table of Contents

Page.

38ARZ/ARD

Features/Benefits……………………………………………………………………………………….
ModelNumber Nomenclature…………………………………………………………………………..
Physical Data…………………………………………………………………………………………….
ARI Capacity ratings 50Hz …………………………………………………………………………….
Options and accessories ……………………………………………………………………………….
Electrical Data……………………………………………………………………………………………
Base Unit Dimensions…………………………………………………………………………………..
Performance data ………………………………………………………………………………………
Application Data…………………………………………………………………………………………
Typical Wiring Schematic……………………………………………………………………………….

1
3
4
6
7
7
8-10
11-20
21
22-26

Model number nomenclature…………………………………………………………………………..
Physical Data…………………………………………………………………………………………….
Options and accessories ……………………………………………………………………………….
Base Unit Dimensions…………………………………………………………………………………..
Fan Performance Data ………………………………………………………………………………..
Electrical Data……………………………………………………………………………………………
Typical piping and wiring ………………………………………………………………………………
Application Data…………………………………………………………………………………………

27
28, 29
30-32
33-40
41-47
48-50
51-54
54-58

Guide Specifications —38ARZ007-012………………………………………..……………………
Guide specifications— 38ARD014-028 …………………………………………………………….
Guide specifications —40RM…………………………………………………………………………

59,60
61,62
63,64

40RM

Guide Specifications




Physical Data – English
UNIT 38AR
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Aluminium Coils (Standard)
Cooper Coils (Optional)
COMPRESSOR
Qty
Oil Charge (oz)
REFRIGERANT TYPE *
Operating Charge, Typical (lb) **
Shipping Charge (lb)
FINISH
CONDENSER FAN
Qty…RPM
Diameter
Nominal Air Flow (Total CFM)
Motor HP-Shaft
CONDENSER COIL (Qty)
Face Area (sq ft Total))
Rows…Fins/in.
Storage Capacity (lb)***
CONTROLS
Pressurerestart Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
DISCHARGE GAS THERMOSTAT (0F)
Cutout
Cut-in
PRESSURE RELIEF
Location
Tempreature
PIPING CONNECTION
Qty…Suction
Qty…Liquid
Hot Gas Stub
UNIT 38AR
SHIPPING DIMENSIONS (in) (W X H X D)

007
5.0

ARZ
008
7. 0

012
9.3

014
10. 8

ARD
016
14

024
18 .1

028
24

300
352

383
484

430
531

676
822

740
886

764
904

1279
1532

88

90

110

60(ea)

85(ea)

110(ea)

111(ea)

12

20
2.0

22

2…700

22 in

5000
2x1/8

Scroll
R22

Gray
Propeller Type

2…920

5800
2x1/4

29.2

1…17
17.3

11.5/circuit

2

2…17
34.2

428 ± 10
320 ± 20
27 ± 3
44 ± 5
270 ± 9
190 ± 13

---

Suction Line
200
1…1 1/8
1… 3/8

007

1…1 1/8
1… 3/8

ARZ
008
012
(59.2X45.5X39)

*Unit is factory-supplied with holding charge only.
**Typical operating charge with 25 ft of interconnecting piping.
***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.




1…1 3/8
1… 1/2

014
016
024
(72.6X44.25X41.7)

3.1

14/circuit 17.97/circuit

2…900
26 in
9210
2x1/2

2…900
30 in
13000
2x1

29.2
3…15
48

50.4
3…16
-

428 ± 10
320 ± 20
27 ± 4
44 ± 7

428 ± 10
320 ± 20
27 ± 4
44 ± 7

---

---

Liquid Line
200

Liquid Line
200

2…1 3/8
2… 1/2
3/8

2…1 3/8
2… 5/8
-

ARD

028
(96.5X49.6 X54.3)

Capacity ratings 50 Hz
CONDENSINGUNIT

AIRHANDLER/INDOOR
COIL
40RM007
40RM008
40RM007
40RM008
40RM012
40RM008
40RM012
40RM014

40RM014


40RM016


40RM024


40RM028


38ARZ007
38ARZ008

38ARZ012

38ARD014

38ARD016

38ARD024

38ARD028

CONDENSINGUNIT
ONLYGROSSCAPACITY
kW**
Btuh††

SYSTEMGROSSCAPACITY
kW*
18.4
19.0
23.3
24.0
25.4
30.1
31.9
33.4

Btuh†
62,200
64,300
78,700
81,400
86,100
102,000
108,000
113,000

40.4


18.0

60,300

25.0

83,900

33.2

112,000

138,000


41.6

142,000

56.3


192,000

57.8

197,200 

63.0

215,000


64.6

218,000

81.1

276,600


84.0

286,700

LEGEND
db — Dry Bulb
wb — Wet Bulb
SST — Saturated Suction Temperature
*System gross capacities are rated according to indoor unit airflow, 35 C air temperature entering condenser, and 20 C wb air temperature entering
evaporator.
†System gross capacities are rated according to indoor unit airflow, 95 F air temperature entering condenser, and 67 F wb air temperature entering
evaporator.
**Condensing unit gross capacity based on 36 C air temperature entering condenser and 8 C SST.
††Condensing unit gross capacity based on 95 F air temperature entering condenser and 45 F SST.

UNIT
38AR
Z007
Z008
Z012
D014
D016
D024
D028

SOUND
RATING
dB(A)
80.0
84.0
85.0
86.9
87.5
88.0
94.8

SOUND LEVELS, dB — 38AR UNITS

OCTAVEBANDS

63

125

250

500

1000

2000

4000

8000

71.5
84.1
88.7
—
—
—
—

76.8
84.5
85.4
90.9
90.9
90.9
91.4

75.3
80.4
81.7
86.1
86.1
86.1
88.1

74.0
78.6
80.9
83.1
83.4
83.8
85.8

73.9
77.2
82.1
84.0
84.5
84.5
86.4

74.1
76.9
76.2
73.5
76.6
79.2
81.5

73.5
78.8
73.6
71.7
73.2
74.3
75.2

64.0
72.5
67.1
66.7
63.5
65.5
67.4

NOTES:
1. 38ARZ unit is in accordance with ARI 270-95 Sound Rating of Unitary Equipment.
2. Estimated sound power levels, dB re 1 Picowatt. 38ARD014-024 and 38AKS data is based upon a limited amount of actual testing with the estimated sound power
data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and air-conditioning equipment. Since this data is estimated, the
sound power levels should not be guaranteed or certified as being the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of the unit.

ESTIMATED SOUND POWER LEVELS (Lw) — 40RM007-028

UNIT

CFM

dB(A)

40RM007
40RM008
40RM012
40RM014
40RM016
40RM024
40RM028

2400
3000
4000
5000
6000
8000
10000

86.3
88.3
91.6
91.1
92.7
96.4
96.2

63
93.2
95.3
98.6
97.3
98.9
102.6
102.5

125
89.2
91.3
94.6
93.3
94.9
98.6
98.5


OCTAVEBANDCENTERFREQUENCY
250
500
1000
85.2
84.2
80.2
87.3
86.3
82.3
90.6
89.6
85.6
89.3
90.3
84.3
90.9
91.9
85.9
94.6
95.6
89.6
94.5
95.5
89.5




2000
78.2
80.3
83.6
82.3
83.9
87.6
87.5

4000
74.2
76.3
79.6
78.3
79.9
83.6
83.5

Options and accessories
38AR, options

Enviro-Shield™ condenser options offer pre-coated coils that provide protection in mild coastal
environments. Several options are available to match coil protection to site conditions for optimum durability.
See table below. Consult your Carrier representative for further information.
Non-fused disconnect switch to remove power locally at the condensing unit. This switch also includes a
power lockout capability to protect the service person. This lockout switch saves the service person time and
effort because there is no need to access a distant disconnect switch while servicing the unit.
Carrier’s line of thermostats provide both programmable and non-programmable capability with the new
Debonair® line of commercial programmable thermostats. The Commercial Electronic thermostats provide
-day programmable capability for economical applications.
PremierLink™ Controller is a field retrofit split system control compatible with the Carrier Comfort Network
(CCN) and other building automation systems (BAS). This control is designed to allow users the access and
ability to change factory-defined settings thus expanding the function of the standard unit.
CONDENSER COIL OPTIONS
COPPERͲTUBECOILS
WITHENVIROͲSHIELDOPTION
AlFins(StandardCoils)
CuFins

ENVIRONMENT
MildCoastal

Standard
X

ModerateCoastal
X

X

AlFins,PreͲCoated
LEGEND
Al — Aluminum
Cu — Copper

Electrical data

VOLTAGE
RANGE*

COMPRESSOR
1

COMPRESSOR
2

UNIT
SIZE
38AR

NOMINAL
VOLTAGE
V-Ph-Hz

MIN

MAX

RLA

LRA

RLA

LRA

Z007
Z008
Z012
D014
D016
D024
D028

400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50

360
360
360
360
360
360
360

440
440
440
440
440
440
440

9.6
13.5
20.7
9.6
13.5
20.7
22.9

82
95
130
82
95
130
145

---9.6
13.5
20.7
22.9

---82
95
130
145

LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps per NEC, Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA — Rated Load Amps (compressor)

FAN MOTORS
(Qty 2)
FLA
LRA
(ea)
(ea)
0.5
0.9
0.8
1.6
0.8
1.6
1.7
-1.7
-1.7
7.5
3.0
--

POWER
SUPPLY
MCA

MOCP

12.4
17.9
26.9
27.8
38.0
56.0
63.3

20
30
45
30
45
70
80

*Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with
theNational Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.




Base Unit Dimensions – 38ARZ 007 – 012
38ARZ Size
007
008
012

Approximate Shipping Weight
With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
154
339
178
392
192
422
238
524
213
467
259
570




Approx. Shipping Dimensions
(AxBxC)
mm
inch
(1504X1157X992)

(59.2X45.5X39)

Base Unit Dimensions – 38ARD 014 – 024
38ARD Size
014
016
024

Approximate Shipping Weight
With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG
LB
KG
LB
357
785
423
931
386
849
452
994
397
873
461
1014

Approx. Shipping Dimensions
(AxBxC)
mm
inch
(1844X1124X1058)

(72.6X44.25X41.7)




Base Unit Dimensions – 38ARD 028

10


38ARZ007
SST
(F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38ARZ008
SST
(F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38ARZ012
SST (F)
25
30
35
40
45
50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

CONDENSING UNIT RATINGS — ENGLISH
44.80
3.50
99.8
49.40
3.56
101.0
54.30
3.63
102.0
59.50
3.71
104.0
65.00
3.81
106.0
70.70
3.91
108.0

28

30

35

40

45

50

2

SDT

43.60
3.72
105.0
48.20
3.78
106.0
52.90
3.85
107.0
58.00
3.93
109.0
63.40
4.02
110.0
69.10
4.12
112.0

41.20
4.15
115.0
45.60
4.20
116.0
50.30
4.28
117.0
55.10
4.36
118.0
60.30
4.45
120.0
65.80
4.56
122.0

40.00
4.39
120.0
44.30
4.45
121.0
48.90
4.52
122.0
53.70
4.60
123.0
58.70
4.70
125.0
64.10
4.80
127.0

38.80
4.63
124.0
43.00
4.69
125.0
47.50
4.77
127.0
52.20
4.85
128.0
57.10
4.94
130.0
62.40
5.05
131.0

36.30
5.12
134.0
40.40
5.18
135.0
44.70
5.25
136.0
49.20
5.34
138.0
54.00
5.44
139.0
59.00
5.54
141.0

61.30
4.79
98.5
68.30
4.81
98.8
75.50
4.88
99.9
83.00
4.97
101.0
90.90
5.06
103.0
99.20
5.17
105.0

59.40
5.07
103.0
66.40
5.09
104.0
73.50
5.15
105.0
80.80
5.24
106.0
88.60
5.34
108.0
96.80
5.45
110.0

55.50
5.65
113.0
62.30
5.68
114.0
69.30
5.74
114.0
76.40
5.84
116.0
83.90
5.94
117.0
91.80
6.06
119.0

53.40
5.96
118.0
60.20
5.99
119.0
67.10
6.06
119.0
74.10
6.16
121.0
81.50
6.27
122.0
89.20
6.39
124.0

51.40
6.27
123.0
58.00
6.31
123.0
64.90
6.38
124.0
71.80
6.48
125.0
79.10
6.59
127.0
86.70
6.72
128.0

47.10
6.93
133.0
53.60
6.99
133.0
60.30
7.06
134.0
67.00
7.17
135.0
74.10
7.29
136.0
81.40
7.43
138.0

80

238.98
17.97
105.80
251.31
18.12
106.70
263.65
18.27
107.60
289.54
18.61
109.40
318.31
19.01
111.20
344.71
19.44
111.20

82.70
6.94
106.0
90.90
7.09
107.0
99.50
7.29
108.0
108.00
7.52
109.0
118.00
7.78
111.0
128.00
8.06
113.0

77.90
7.57
116.0
85.80
7.69
116.0
94.00
7.87
117.0
103.00
8.11
119.0
112.00
8.37
120.0
121.00
8.66
122.0

75.50
7.90
121.0
83.20
8.01
121.0
91.20
8.18
122.0
99.70
8.41
123.0
109.00
8.67
125.0
118.00
8.96
127.0

73.10
8.25
126.0
80.50
8.35
126.0
88.40
8.50
127.0
96.70
8.72
128.0
105.00
8.98
130.0
115.00
9.27
131.0

Air Temperature Entering Condenser (F)
85
95
100
115

232.12
18.76
111.20
244.32
18.87
111.20
256.51
18.98
111.20
282.07
19.28
113.00
309.33
20.05
114.80
338.71
20.47
116.60

217.96
18.98
118.40
229.73
20.22
118.40
241.50
21.45
118.40
266.17
21.84
120.20
286.68
22.25
122.00
320.76
22.71
123.80

199.02
23.38
125.60
212.47
23.58
125.60
225.91
23.77
125.60
249.69
24.20
122.00
274.90
24.66
131.00
302.17
25.11
129.20

181.25
26.92
137.30
192.37
27.15
137.75
203.49
27.39
138.20
225.24
27.93
135.50
249.40
28.71
141.80
271.24
29.36
142.70

TC
kW
SDT

30

TC
kW
SDT

35

TC
kW
SDT

40

TC
kW
SDT

45

TC
kW
SDT

50

TC
kW
SDT

25

TC
kW
SDT

30

TC
kW
SDT

35

TC
kW
SDT

40

TC
kW
SDT

45

TC
kW
SDT

50

TC
kW
SDT

38ARD024
SST
(F)

Air Temperature Entering Condenser (F)
80
85
95
100
105
115

85.00
6.64
101.0
93.30
6.81
102.0
102.00
7.01
103.0
111.00
7.24
104.0
121.00
7.49
106.0
130.00
7.76
108.0

25

38ARD016
SST
(F)

Air Temperature Entering Condenser (F)
80
85
95
100
105
115

38ARD028

SST
(F)
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW

38ARD014
SST
(F)

Air Temperature Entering Condenser (F)
80
85
95
100
105
115

67.90
8.98
136.0
75.10
9.06
136.0
82.60
9.18
136.0
90.40
9.37
138.0
98.70
9.61
139.0
107.00
9.90
140.0

25
30
35
40
45
50

125

175.41
27.99
141.80
186.35
28.26
141.80
197.28
28.52
141.80
217.62
29.14
143.60
243.45
29.63
147.20
262.86
30.10
149.00

10

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

80
120.3
7.6
109
126.3
7.67
110
132.4
7.73
111
145.0
7.87
113
159.1
8.04
115
172.1
8.22
117

Air Temperature Entering Condenser (F)
85
95
100
105
115
117.1
110.3
102.0
96.7
321.1
7.93
8.02
9.88
10.93
11.38
115
122
129
138
142
123.1
116.3
108.6
102.3
99.6
7.98
8.55
9.97
11.02
11.48
116
123
130
138
142
358.5
107.9
122.3
115.2
129.0
11.58
10.05
11.1
8.02
9.07
143
131
138
124
117
119.2
115.8
134.4
126.9
141.6
11.80
10.23
11.29
9.22
8.15
145
131
140
124
117
155.0
142.1
139.2
130.4
127.7
8.48
9.41
10.43
11.74
12.135
118
126
135
142
147
169.4
161.1
152.6
142.4
138.5
8.66
9.6
10.61
12.1
12.415
120
127
133
142
148

80
165.1
10.21
109
173.3
10.30
110
181.6
10.38
111
199.0
10.57
113
218.2
10.8
113
236.0
11.04
115

Air Temperature Entering Condenser (F)
85
95
100
105
115
160.8
151.4
140.3
133.2
129.6
10.66
10.78
13.28
14.69
15.30
113
122
129
138
142
168.9
159.7
149.3
140.8
137.1
10.72
11.49
13.39
14.80
15.43
114
122
130
138
142
177.1
167.9
158.3
148.4
144.6
10.78
12.19
13.5
14.91
15.56
115
122
131
138
143
194.2
184.5
174.3
163.9
543.4
10.95
12.39
13.75
15.17
15.86
117
124
131
138
144
212.6
197.2
191.2
179.3
175.6
11.39
12.64
14.01
15.78
16.31
118
126
135
140
146
232.3
221.1
209.5
195.7
190.4
11.63
12.9
14.26
16.25
16.68
120
127
133
142
148

80

Air Temperature Entering Condenser (F)
85
95
100
115
125

177.00
12.70
95.9
193.00
13.20
97.7
210.00
13.70
99.8
227.00
14.20
102.0
246.00
14.80
104.0
265.00
15.40
107.0

165.00
14.00
110.0
180.00
14.80
112.0
195.00
15.30
114.0
212.00
15.90
116.0
230.00
16.50
118.0
248.00
17.10
121.0

156.00
15.60
120.0
170.00
16.00
121.0
185.00
16.50
123.0
201.00
17.00
125.0
218.00
17.60
127.0
235.00
18.30
130.0

kW — Compressor Power
SDT — Saturated Discharge Temperature (F)
SST — Saturated Suction Temperature (F)
TC — Gross Cooling Capacity (1000 Btuh)

151.00
16.30
125.0
165.00
16.70
126.0
179.00
17.10
128.0
195.00
17.60
130.0
211.00
18.20
132.0
229.00
18.90
134.0

137.00
18.40
139.0
150.00
18.80
140.0
163.00
19.10
142.0
177.00
19.60
143.0
192.00
20.10
145.0
208.00
20.80
147.0

123.00
19.40
148.0
138.00
20.00
150.0
151.00
20.50
151.0
165.00
21.00
153.0
179.00
21.50
154.0
194.00
22.10
156.0

Performance data 50Hz – Cont.

COMBINATION RATINGS — ENGLISH

38ARZ007/40RM007
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

38ARZ007/40RM008
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

38ARZ008/40RM007
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

1800
57
57.2
57.20
3.67
56.4
56.40
3.90
54.8
54.80
4.35
54.0
54.00
4.61
53.1
53.10
4.86
51.4
51.40
5.38
50.89
50.89
5.54

62
58.5
54.50
3.69
57.5
54.00
3.92
55.7
53.00
4.36
54.7
52.50
4.62
53.7
51.90
4.87
51.7
50.80
5.38
51.10
50.47
5.53

67
63.1
45.40
3.77
62.0
45.00
3.99
59.9
44.20
4.44
58.8
43.70
4.70
57.7
43.30
4.95
55.5
42.40
5.46
54.84
42.13
5.61

72
68.4
35.80
3.86
67.3
35.40
4.09
65.1
34.60
4.54
63.9
34.10
4.79
62.6
33.70
5.05
60.2
32.90
5.56
59.48
32.66
5.71

2250
57
61.3
61.30
3.74
60.4
60.40
3.96
58.7
58.70
4.42
57.7
57.70
4.67
56.7
56.70
4.93
54.8
54.80
5.44
54.23
54.23
5.57

62
61.5
60.90
3.74
60.6
60.10
3.97
58.7
58.70
4.42
57.7
57.70
4.68
56.8
56.80
4.93
54.8
54.80
5.44
54.20
54.20
5.57

67
65.5
51.10
3.81
64.4
50.60
4.03
62.1
49.80
4.48
61.0
49.30
4.74
59.8
48.80
4.99
57.4
47.90
5.50
56.68
47.63
5.63

72
70.9
39.3
3.90
69.7
38.9
4.13
67.3
38.1
4.58
66.0
37.7
4.84
64.7
37.2
5.09
62.1
36.4
5.61
61.32
36.16
5.74

1800
57
68.3
68.30
4.81
67.4
67.40
5.11
65.4
65.40
5.71
64.4
64.40
6.03
63.3
63.30
6.36
61.2
61.20
7.01

60.57
60.57
7.17

62
72.6
61.50
4.85
71.4
60.90
5.15
68.9
59.70
5.74
67.6
59.10
6.07
66.2
58.40
6.40
63.6
57.10
7.06

62.82
56.71
7.23

67
79.0
52.00
4.92
77.7
51.40
5.22
75.0
50.30
5.82
73.6
49.70
6.15
72.2
49.10
6.49
69.3
47.90
7.15

68.43
47.54
7.32

72
85.7
42.20
5.00
84.3
41.70
5.30
81.5
40.60
5.91
80.0
40.00
6.25
78.5
39.50
6.59
75.5
38.30
7.27

74.60
37.94
7.44

Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
61.8
61.9
65.6
70.9
61.80
61.80
52.30
40.00
3.75
3.75
3.81
3.90
60.9
61.0
64.5
69.7
60.90
60.90
51.90
39.60
3.97
3.98
4.03
4.13
59.2
59.2
62.2
67.3
59.20
59.20
51.00
38.80
4.43
4.43
4.48
4.58
58.2
58.2
61.0
66.0
58.20
58.20
50.50
38.40
4.68
4.68
4.74
4.83
57.2
57.2
59.9
64.7
57.20
57.20
50.00
38.00
4.94
4.94
4.99
5.09
62.1
57.5
55.3
55.3
37.10
49.10
55.30
55.30
5.60
5.50
5.46
5.46
61.32
56.78
54.73
54.73
36.83
48.83
54.73
54.73
5.75
5.65
5.62
5.62
Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
65.6
65.6
67.8
73.0
65.60
65.6
59.0
44.4
3.81
3.81
3.85
3.94
64.7
64.7
66.6
71.7
64.70
64.7
58.5
44.0
4.04
4.04
4.07
4.16
62.7
62.7
64.3
69.2
62.70
62.7
57.6
43.2
4.49
4.49
4.52
4.62
61.6
61.6
63.0
67.8
61.60
61.6
57.0
42.8
4.75
4.75
4.78
4.87
60.6
60.6
61.8
66.5
60.60
60.6
56.5
42.3
5.01
5.01
5.03
5.13
58.5
58.5
59.3
63.8
58.50
58.5
55.4
41.5
5.53
5.52
5.54
5.64
62.99
57.87 58.55
57.87
41.26
57.87 55.07
57.87
5.77
5.67
5.65
5.66
Evaporator Air — Cfm
2400
Evaporator Air — Ewb (F)
57
62
67
72
74.9
76.8
82.9
89.6
74.90
70.80
59.00
46.50
4.88
4.89
4.96
5.05
73.8
75.5
81.5
88.1
73.80
70.20
58.40
46.00
5.17
5.19
5.27
5.35
71.6
72.9
78.7
85.1
71.60
68.80
57.30
44.90
5.77
5.79
5.87
5.96
70.4
71.6
77.1
83.5
70.40
68.10
56.70
44.30
6.11
6.12
6.20
6.30
69.2
70.2
75.6
81.9
69.20
67.30
56.10
43.80
6.44
6.46
6.54
6.64
66.8
67.4
72.4
78.7
66.80
65.80
54.90
42.60
7.11
7.12
7.21
7.33
66.08
66.08
7.28

11

66.56
65.35
7 29
.

71.44
54.54
7.38

77.74
42.24
7.50

3000
57
65.1
65.10
3.80
64.1
64.10
4.03
62.1
62.10
4.48
61.1
61.10
4.74
60.1
60.10
5.00
58.0
58.00
5.52
57.37
57.37
5.68

62
65.1
65.10
3.80
64.1
64.10
4.03
62.2
62.20
4.48
61.1
61.10
4.74
60.1
60.10
5.00
58.0
58.00
5.51
57.37
57.37
5.66

67
67.3
58.50
3.84
66.1
58.00
4.06
63.8
57.00
4.51
62.6
56.50
4.77
61.4
55.90
5.02
58.9
54.90
5.53
58.15
54.60
5.68

72
72.5
44.00
3.93
71.2
43.60
4.16
68.7
42.80
4.61
67.4
42.40
4.86
66.1
42.00
5.12
63.4
41.10
5.63
62.59
40.83
5.78

3750
57
68.6
68.6
3.86
67.5
67.50
4.09
65.4
65.4
4.55
64.3
64.3
4.80
63.2
63.2
5.06
61.0
61.0
5.58
60.34
60.34
5.71

62
68.6
68.6
3.86
67.5
67.50
4.09
65.4
65.4
4.54
64.3
64.3
4.80
63.2
63.2
5.06
61.0
61.0
5.58
60.34
60.34
5.71

67
69.4
65.6
3.88
68.3
65.00
4.10
65.9
63.8
4.55
64.7
63.0
4.81
63.4
62.3
5.06
61.0
60.8
5.57
60.28
60.35
5.70

72
74.2
49.2
3.96
72.9
48.80
4.19
70.3
47.9
4.64
68.9
47.5
4.89
67.5
47.1
5.15
64.8
46.2
5.66
63.99
45.93
5.79

3000
57
79.4
79.40
4.93
78.2
78.20
5.23
75.9
75.90
5.83
74.6
74.60
6.17
73.3
73.30
6.50
70.7
70.70
7.17

69.92
69.92
7.34

62
80.0
78.30
4.93
78.7
77.40
5.23
76.1
75.60
5.83
74.7
74.50
6.17
73.3
73.30
6.50
70.6
70.60
7.17

69.79
69.79
7.34

67
85.5
65.50
5.00
84.0
64.90
5.30
81.0
63.80
5.90
79.4
63.10
6.24
77.8
62.50
6.57
74.5
61.30
7.25

73.51
60.94
7.42

72
92.1
50.40
5.08
90.5
49.80
5.38
87.4
48.80
5.99
85.7
48.20
6.34
84.1
47.70
6.68
80.7
46.50
7.36
79.68
46.14
7.53

7

38ARZ008/40RM008
Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW
TC
118.4
SHC
kW

72
89.1
45.80
5.04
87.6
45.20
5.34
84.8
44.20
5.96
83.2
43.60
6.30
81.6
43.00
6.64
78.4
41.90
7.32
77.44
41.57
7.52

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
80.2
80.6
85.7
92.3
80.20
79.10
66.10
50.80
4.93
4.94
5.00
5.08
79.0
79.3
84.3
90.8
79.00
78.20
65.60
50.30
5.23
5.24
5.30
5.39
76.6
76.7
81.4
87.8
76.60
76.40
64.50
49.30
5.84
5.84
5.91
6.00
75.3
75.4
79.8
86.1
75.30
75.20
63.90
48.70
6.17
6.18
6.25
6.34
74.0
74.1
78.2
84.4
74.00
74.10
63.30
48.10
6.51
6.51
6.58
6.68
71.5
71.4
75.0
80.9
71.50
71.40
62.10
46.90
7.19
7.19
7.26
7.36
70.75
70.59
74.04
79.85
70.75
70.59
61.74
46.54
7.39
7.39
7.46
7.56

72
94.6
52.30
5.11
93.0
51.70
5.42
89.8
50.60
6.03
88.0
50.10
6.37
86.3
49.50
6.71
82.7
48.30
7.40

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
87.9
87.9
90.8
97.2
87.90
87.90
78.50
58.80
5.03
5.03
5.06
5.14
86.6
86.6
89.2
95.5
86.60
86.60
77.90
58.30
5.33
5.33
5.37
5.45
83.8
83.8
86.1
92.2
83.80
83.80
76.60
57.30
5.94
5.94
5.98
6.07
82.4
82.4
84.3
90.3
82.40
82.40
75.90
56.60
6.28
6.28
6.32
6.41
80.9
80.9
82.6
88.5
80.90
80.90
75.20
56.00
6.62
6.63
6.66
6.75
78.0
78.0
79.2
84.7
78.00
78.00
73.70
54.80
7.31
7.31
7.34
7.43

Evaporator Air — Cfm
3000
Evaporator Air — Ewb (F)
57
62
67
72
96.6
99.8
107.0
115.0
96.60
90.10
74.90
59.20
6.88
6.96
7.14
7.35
95.2
98.1
105.0
113.0
95.20
89.30
74.20
58.50
7.20
7.27
7.45
7.67
92.5
94.8
102.0
110.0
92.50
87.60
72.80
57.20
7.84
7.89
8.09
8.31
91.0
93.0
99.9
108.0
91.00
86.60
72.00
56.40
8.19
8.23
8.42
8.65
89.4
91.1
97.8
105.0
89.40
85.60
71.20
55.60
8.53
8.57
8.75
8.98
86.4
87.5
93.8
101.0
86.40
83.70
69.50
54.10
9.22
9.25
9.42
9.66

2250
57
74.1
74.10
4.87
73.0
73.00
5.17
70.9
70.90
5.76
69.7
69.70
6.10
68.6
68.60
6.43
66.3
66.30
7.09
65.61
65.61
7.29

62
76.4
69.40
4.89
75.1
68.70
5.19
72.6
67.40
5.78
71.2
66.70
6.11
69.8
66.00
6.45
67.1
64.60
7.11
66.29
64.18
7.31

67
82.5
57.90
4.96
81.1
57.30
5.26
78.3
56.20
5.86
76.8
55.60
6.20
75.3
55.00
6.53
72.3
53.80
7.21
71.40
53.44
7.41

38ARZ008/40RM012
Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW

3000
57
82.4
82.40
4.96
81.1
81.10
5.26
78.7
8.70
5.87
77.3
77.30
6.21
75.9
75.90
6.54
73.2
73.20
7.22

62
82.7
81.60
4.96
81.4
80.60
5.26
78.7
78.60
5.87
77.3
77.30
6.21
76.0
76.00
6.55
73.2
73.20
7.22

67
87.9
8.20
5.03
86.3
67.60
5.33
83.3
66.40
5.93
81.6
65.08
6.27
79.9
65.10
6.61
76.6
63.80
7.28

38ARZ012/40RM008
Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW
TC
118.4
SHC
kW

2250
57
88.7
88.40
6.71
87.4
87.20
7.04
84.8
84.80
7.68
83.5
83.50
8.03
82.2
82.20
8.38
79.5
79.50
9.07

62
94.4
78.50
6.83
92.9
77.80
7.15
89.8
76.30
7.78
88.1
75.40
8.12
86.4
74.50
8.46
83.0
72.80
9.14

67
102.0
66.30
7.01
101.0
65.60
7.33
97.3
64.20
7.96
95.4
63.40
8.29
93.6
62.60
8.63
89.8
61.00
9.31

72
110.0
54.00
7.22
109.0
53.30
7.54
105.0
51.90
8.17
103.0
51.20
8.51
101.0
50.40
8.84
97.1
48.80
9.51

78.69

81.98

88.66

95.93

85.50

86.42

92.60

78.69

72.29

60.52

48.32

85.50

83.13

68.99

9.24

9.31

48

9.68

9.39

9.42

9.59

8
12

3750
57
84.3
84.30
4.98
83.1
83.10
5.29
80.5
80.50
5.90
79.2
79.20
6.23
77.8
77.80
6.57
75.0
75.00
7.25
74.16
74.16
7.45

62
84.3
84.30
4.98
83.0
83.00
5.28
80.5
80.50
5.89
79.1
79.10
6.23
77.7
77.70
6.57
75.0
75.00
7.25
74.19
74.19
7.45

67
88.0
73.70
5.03
86.4
73.10
5.33
83.4
71.90
5.94
81.8
71.20
6.27
80.1
70.50
6.61
76.9
69.20
7.29
75.94
68.81
7.49

72
94.4
55.40
5.11
92.8
54.90
5.41
89.6
53.90
6.03
87.8
53.30
6.37
86.1
52.80
6.71
82.6
51.70
7.39
81.55
51.37
7.59

5000
57
91.7
91.70
5.07
90.3
90.30
5.38
87.4
87.40
5.99
85.8
85.80
6.34
84.3
84.30
6.68
81.2
81.20
7.37

62
91.7
91.70
5.07
90.2
90.20
5.38
87.3
87.30
5.99
85.8
85.80
6.34
84.2
84.20
6.68
81.1
81.10
7.37

67
92.9
87.10
5.09
91.3
86.40
5.39
88.1
84.80
6.01
86.4
83.80
6.35
84.7
82.80
6.69
81.3
80.80
7.37

72
98.8
64.90
5.16
97.1
64.30
5.47
93.7
63.30
6.09
91.7
62.70
6.43
89.8
62.10
6.77
86.0
60.90
7.46

3750
57
102.0
102.00
7.02
101.0
101.00
7.34
97.8
97.80
7.97
96.1
96.10
8.32
94.5
94.50
8.66
91.1
91.10
9.34

62
104.0
99.60
7.04
102.0
98.50
7.36
98.5
96.50
7.99
96.6
95.20
8.33
94.8
94.00
8.67
91.1
91.10
9.34

67
110.0
82.80
7.22
109.0
82.10
7.53
105.0
80.70
8.16
103.0
79.80
8.50
101.0
79.00
8.83
96.3
77.30
9.50

72
118.0
63.90
7.43
116.0
63.30
7.75
113.0
61.90
8.39
110.0
61.10
8.73
108.0
60.30
9.06
104.0
58.80
9.73

99.80

90.08

89.99

94.89

102.80

53.65

90.08

90.23

76.79

58.35

9.83

9.51

9.51

9.67

9.90

Performance data 50Hz – Cont.
38ARZ012/40RM012

Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW
TC
118.4
SHC
kW

72
118.0
60.80
7.43
116.0
60.10
7.75
112.0
58.70
8.39
110.0
57.90
8.72
108.0
57.10
9.05
103.0
55.40
9.71
101.50
54.89
9.91

Evaporator Air — Cfm
4000
Evaporator Air — Ewb (F)
57
62
67
72
107.0
108.0
114.0
122.0
107.0
106.0
88.10
67.50
7.13
7.15
7.31
7.54
105.0
106.0
112.0
120.0
105.0
104.0
87.40
66.80
7.45
7.46
7.63
7.85
102.0
102.0
108.0
116.0
102.0
102.0
85.90
65.40
8.09
8.09
8.26
8.49
100.0
100.0
106.0
114.0
100.0
100.0
85.00
64.60
8.43
8.43
8.59
8.83
98.6
98.5
104.0
111.0
98.60
98.50
84.10
63.80
8.78
8.77
8.93
9.16
95.0
94.7
99.2
107.0
95.00
94.70
82.40
62.10
9.46
9.44
9.59
9.83
93.92
93.56
97.76
105.80
93.92
93.56
81.89
61.59
9.66
9.64
9.79
10.03

72
124.0
66.10
7.59
122.0
65.40
7.91
118.0
63.90
8.55
115.0
63.00
8.88
113.0
62.10
9.21
108.0
60.30
9.87

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
57
62
67
72
114.0
114.0
120.0
128.0
114.00
114.00
97.60
73.70
7.32
7.32
7.46
7.70
112.0
112.0
117.0
126.0
112.00
112.00
96.70
73.00
7.63
7.63
7.78
8.02
109.0
109.0
113.0
121.0
109.0
109.0
95.10
71.50
8.27
8.27
8.41
8.66
107.0
107.0
111.0
119.0
107.00
107.00
94.10
70.60
8.61
8.61
8.74
8.99
105.0
105.0
108.0
116.0
105.00
105.00
93.10
69.70
8.95
8.95
9.07
9.32
100.0
100.0
103.0
111.0
100.00
100.00
91.10
68.00
9.63
9.63
9.73
9.98

3000
57
99.3
99.30
6.94
97.9
97.90
7.26
95.0
95.00
7.90
93.4
93.40
8.25
91.8
91.80
8.59
88.5
88.50
9.28
87.51
87.51
9.49

62
102.0
92.70
7.01
101.0
91.90
7.33
97.1
90.10
7.95
95.2
89.10
8.29
93.3
88.10
8.63
89.5
86.10
9.30
88.36
85.50
9.50

67
110.0
77.20
7.21
108.0
76.40
7.52
104.0
74.90
8.15
102.0
74.00
8.48
100.0
73.20
8.81
95.8
71.40
9.47
94.54
70.86
9.67

38ARZ012/40RM014
Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW

38ARD014/40RM014
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

3750
57
106.0
106.00
7.12
105.0
105.00
7.43
101.0
101.00
8.07
99.6
99.60
8.41
97.8
97.80
8.75
94.1
94.10
9.42

62
108.0
103.00
7.16
106.0
101.00
7.47
102.0
99.40
8.10
100.0
98.10
8.43
98.3
96.80
8.77
94.2
94.20
9.43

67
116.0
85.10
7.36
114.0
84.30
7.67
110.0
82.70
8.30
107.0
81.70
8.63
105.0
80.80
8.96
100.0
78.90
9.61

3750
62
126
112
7.68
124
111
8.16
120
109
9.18
116
106
9.73
114
105
10.3
110
103
11.5
107.9
101.5
12.1
105
99.6
12.8

67
136
93.1
7.73
134
92.2
8.21
130
90.5
9.23
127
89.1
9.73
124
88.2
10.3
119
86.2
11.6
116.4
85.3
12.2
113
84
12.9

72
149
73.8
7.81
147
73
8.29
141
71.4
9.28
138
70.2
9.82
136
69.3
10.4
130
67.5
11.6
127.0
66.5
12.2
123
65.2
12.9

Evaporator Air — Cfm
5000
Evaporator Air — Ewb (F)
62
67
72
133
142.5
155
127
106.6
82.4
7.71
7.762
7.84
131
140.4
153
126
105.6
81.7
8.19
8.229
8.31
127
138.0
148
122
100.0
79.9
9.22
9.3
9.31
124
131.8
143
119
99.98
78.7
9.73
9.824
9.82
122
128.7
140
117
99.01
77.8
10.3
10.31
10.4
117
123.6
135
113
97.09
75.9
11.6
11.57
11.7
114.9
120.9
131.6
110.9
95.0
74.9
12.2
12.2
12.3
112
117.2
127
108
92.24
73.6
12.9
12.94
13

5000
57
112.0
112.00
7.27
111.0
111.00
7.59
107.0
107.00
8.23
105.0
105.00
8.57
103.0
103.00
8.91
99.2
99.20
9.59
98.06
98.06
9.79

62
112.0
112.0
7.27
110.0
110.0
7.59
107.0
107.0
8.23
105.0
105.0
8.57
103.0
103.0
8.91
99.2
99.20
9.58
98.06
98.06
9.78

67
117.0
98.20
7.39
115.0
97.30
7.70
111.0
95.60
8.34
108.0
94.70
8.67
106.0
93.70
9.00
101.0
91.70
9.66
99.50
91.10
9.86

72
125.0
73.70
7.60
123.0
73.00
7.92
118.0
71.60
8.57
116.0
70.80
8.90
113.0
69.90
9.23
109.0
68.30
9.90
107.80
67.82
10.10

6250
57
119.0
119.00
7.45
117.0
117.00
7.77
113.0
113.00
8.42
111.0
111.00
8.75
109.0
109.00
9.09
105.0
105.00
9.77

62
119.0
119.00
7.45
117.0
117.00
7.77
113.0
113.0
8.41
111.0
111.00
8.75
109.0
109.00
9.09
105.0
105.00
9.77

67
122.0
108.00
7.53
120.0
108.00
7.85
116.0
106.0
8.48
113.0
104.00
8.81
111.0
103.00
9.14
106.0
101.00
9.80

72
130.0
80.70
7.76
128.0
80.00
8.08
124.0
78.50
8.72
121.0
77.60
9.06
118.0
76.80
9.39
113.0
75.10
10.10

6250
62
140
135
7.77
138
133
8.23
134
129
9.25
131
126
9.82
129
124
10.4
124
119
11.6
121.4
116.9
12.2
118
114
12.9

67
147
120
7.78
144
119
8.25
139
117
9.26
135
115
9.82
133
114
10.4
127
111
11.6
124.0
109.7
12.2
120
108
12.9

72
159
90.4
7.87
156
89.6
8.34
151
87.9
9.34
146
86.5
9.92
144
85.6
10.41
138.0
83.7
11.67
134.6
82.7
12.3
130
81.3
13.03

19
13

38ARD016/40RM016
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

38ARD024/40RM024
Temp (F) Air Entering
Condenser
(Edb)
80
85
95
100
105
115
118.4
122

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

72
207
99.9
11.3
204
98.7
11.7
197
96
12.7
191
94.1
13.2
186
92.7
13.8
177
89.5
14.8
172.3
88.0
15.3
166
85.9
15.9

Evaporator Air — Cfm
6000
Evaporator Air — Ewb (F)
62
67
72
187
199.4
215
172
135.9
111
10.8
11.06
11.3
184
196
212
170
134.9
109
11.3
11.54
11.8
177
192.0
204
165
131.0
107
12.2
12.50
12.9
172
182.9
197
162
130.2
105
12.8
12.98
13.4
169
178.5
193
159
128.2
104
13.3
13.56
13.9
161
169.6
183
153
125.2
100
14.3
14.62
15
156.7
165.1
177.9
149.6
123.6
98.6
14.8
15.1
15.5
151
159.1
171
145
121.5
96.7
15.5
15.67
16.1

72
237.0
115.1
14.9
233.0
114.2
15.5
224.0
110.4
16.7
219.0
109.4
17.4
214.0
107.6
17.9
204.0
103.8
19.2
199.7
102.6
19.8
194.0
101.0
20.6

Evaporator Air — Cfm
7000
Evaporator Air — Ewb (F)
62
67
72
209.5
223.5
241.0
187.8
156.6
121.7
14.1
14.5
15.1
205.5
220.0
237.0
185.4
155.2
120.8
14.6
15.1
15.6
198.0
211.0
227.5
180.7
151.9
117.0
15.8
16.3
16.9
194.5
206.5
222.5
178.3
150.0
116.0
16.5
16.9
17.5
190.5
201.5
217.5
175.5
148.1
114.2
17.1
17.5
18.1
182.5
187.6
207.0
169.4
140.5
110.4
18.5
20.0
19.4
179.1
184.4
202.5
166.7
138.9
109.2
19.1
20.5
20.0
174.5
180.2
196.5
163.2
136.8
107.6
19.9
21.1
20.8

72
314.7
168.9
20.2
309.5
167.6
21.0
297.1
162.3
22.0
290.6
161
23.4
284.0
158.4
24.2
275.7
153.1
26.0
270.8
152.2
26.8
264.3
151.1
27.8

Evaporator Air — Cfm
8,000
Evaporator Air — Ewb (F)
62
67
72
276.6
293.3
315.2
268.7
224.3
172.3
19.0
19.6
20.3
271.5
288.2
310.1
264.9
223.0
171.1
19.7
20.3
21.1
261.2
276.6
297.2
257.3
218.0
166.0
20.7
21.1
22.1
257.3
270.2
290.8
253.5
215.4
164.7
22.2
22.7
23.5
252.2
263.7
284.3
248.4
212.9
162.2
23.1
23.6
24.3
246.7
257.2
275.6
243
199.3
157.1
25.0
25.3
26.1
243.2
252.6
270.5
239.5
196.9
156.1
25.9
26.1
26.9
238.5
246.5
263.7
234.9
193.8
154.8
27.0
27.2
28.0

4500
62
177
149
10.6
175
148
11.1
168
145
12
163
142
12.5
159
141
13.1
152
137
14.1
148.1
134.9
14.6
143
132
15.2

67
191.5
125.1
10.87
188.2
124
11.35
181.4
120.8
12.31
175.2
119.1
12.88
171.8
117
13.37
163
113.9
14.42
159.0
112.3
14.9
153.6
110.1
15.48

6,000
62
204.0
175.5
13.9
200.0
173.6
14.5
193.0
169.8
15.7
189.0
167.9
16.3
185.0
166.1
17.0
177.0
161.3
18.3
173.6
159.3
18.9
169.0
156.6
19.7

67
219.0
146.2
14.4
216.0
144.4
14.9
207.0
141.5
16.2
203.0
139.6
16.8
198.0
137.7
17.4
189.0
134.9
18.8
185.1
133.3
19.4
180.0
131.1
20.2

38ARD028/40RM028
Temp (F) Air Entering
Condenser
(Edb)
TC
80
SHC
kW
TC
85
SHC
kW
TC
95
SHC
kW
TC
100
SHC
kW
TC
105
SHC
kW
TC
115
SHC
kW
TC
118.4
SHC
kW
TC
122
SHC
kW

20

7000
62
273.6
260.5
18.8
268.4
257.2
19.6
258.6
252.4
20.6
254
247.4
22.1
248.8
243.5
23.0
243.1
239.7
24.8
239.5
237.0
25.6
234.7
233.3
26.7

67
291.9
217.3
19.5
287.3
215.3
20.2
275.5
210.8
21.0
269.7
208.1
22.6
263.1
205.5
23.5
256.4
192.7
25.3
252.0
191.3
26.1
246.1
189.5
27.2

LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input

7500
62
195
184
11
193
182
11.4
186
176
12.4
181
172
13
176
168
13.5
169
160
14.6
164.7
156.6
15.1
159
152
15.7

67
205
160
11.2
202
158
11.6
194
155
12.6
187
153
13.2
183
151
13.7
174
148
14.7
168.9
145.9
15.2
162
143
15.8

8000
62
215.0
200.0
14.2
211.0
197.2
14.8
203.0
191.5
16.0
200.0
188.7
16.6
196.0
184.9
17.3
188.0
177.4
18.7
184.6
174.1
19.3
180.0
169.8
20.2

67
228.0
167.0
14.7
224.0
166.1
15.2
215.0
162.3
16.4
210.0
160.4
17.0
205.0
158.5
17.7
196.0
154.7
19.0
191.7
153.1
19.6
186.0
151.0
20.4

72
245.0
128.3
15.2
241.0
127.4
15.8
231.0
123.6
17.0
226.0
122.7
17.6
221.0
120.8
18.2
210.0
117.0
19.5
205.3
115.8
20.1
199.0
114.2
20.9

9,000
62
282.4
276.3
19.2
277.9
272.5
20.0
267.6
263.6
21.0
263.1
259.2
22.5
258.0
254.1
23.3
252.0
248.2
25.1
248.2
244.5
26.0
243.2
239.5
27.1

SHC — Sensible Heat Capacity (kW) Gross
TC — Total Capacity (kW) Gross

14

72
221
120.8
11.44
217
119.8
12.02
208
117.7
12.98
202
114.9
13.46
197
113.9
14.04
187
111
15.10
182.3
109.3
15.6
176
107.0
16.15

67
296.6
237.6
19.7
291.4
235.7
20.5
279.8
230.6
21.3
273.4
228.1
22.8
267.0
225.6
23.7
259.8
210.8
25.5
255.2
209.3
26.3
249.1
207.4
27.3

72
318.4
180.6
20.4
313.3
179.3
21.2
300.4
174.2
22.2
294
173.0
23.6
286.9
170.4
24.5
278.2
165.3
26.2
273.1
164.1
27.0
266.4
162.5
28.0

Application data
Operating limits – SI (English)
Maximum Outdoor
Temperature
Minimum Outdoor Ambient

Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable Saturation
Suction Temperature Range
Maximum Discharge
Temperature
Minimum Discharge Superheat

52 C (125 F)

LIQUID LINE DATA — 38ARD014-028 UNITS

See Minimum Outdoor-Air
Operating Temperature
table below.

UNIT 38AR

13 C (55 F)

38ARZ007-012
38ARD014-028

35 C (95 F)

16 C (60 F)

For refrigerant lines longer than  lineal ft, a
liquid line solenoid valve installed at the indoor
unit and a suction accumulator are required. Refer
to the Refrigerant Specialties
Part Numbers table.

For applications with liquid lift greater than  m
(0 ft), use /-in. liquid line where / in. is shown;
use /-in. liquid line where / in. is shown. The
maximum liquid lift is  m (0 ft).

REFRIGERANT PIPING SIZES

MAXIMUM REFRIGERANT CHARGE
Z007
Z008
Z012
D014
D016
D024
D028

UNIT
38AR

kg
7.7
15.5
15.5
(2)7.7
(2) 15.5
(2) 15.5
(2) 12.5

MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
UNIT 38AR
38ARZ007-012
38ARD014-024
38ARD028

UNIT
38ARZ007
38ARZ008

38ARZ012
38ARD014
38ARD016
38ARD024
38A RD028

Z007
Z008
Z012
D014
D016
D024

UNIT
38AR

COND
TEMP
C (F)

MINIMUM OUTDOOR TEMP C (F)

32 (90)

10 (50)

32 (90)

15 (59)

Std

LIQUID LINE
SOLENOID VALVE
(LLSV)

1/2

200RB5T4M Qty 2

5/8
1/2

5/8
5/8

D028

0–7.6(0-25)
L
3/8
3/8
1/2
1/2
1/2
1/2

S
1 1/8
1 1/8
1 3/8
1 1/8
1 3/8
1 3/8

0–4 (0-13.1 )
L
5/8

S
1 3 /8

LINEAR LENGTH OF PIPING — M (FT)
7.6–15.2(25-50)
15.2–22.4(50-75)
22.4–30.5(75-100)
Line Size (in. OD)
L
S
L
S
L
S
3/8
1 1/8
3/8
1 1/8
3/8
1 1/8
1/2
1 1/8
1/2
1 1/8
1/2
1 3/8
1/2
1 3/8
1/2
1 3/8
1/2
1 3/8
1/2
1 1/8
1/2
1 1/8
1/2
1 1/8
1/2
1 3/8
1/2
1 3/8
5/8
1 3/8
1/2
1 3/8
5/8
1 3/8
5/8
1 3/8
LINEAR LENGTH OF PIPING — M (FT)
4-10 (13.1-32.8 )
10-22 (32.8-72.2)
22–30.5(72.2-100)
Line Size (in. OD)
L
S
L
S
L
S
7/8
1 5/8
5/8
1 5/8
5/8
1 5/8

LEGEND
L — Liquid Line S — Suction Line
NOTES:
1. Pipe sizes are based on a 2qF loss for liquid and
suction lines.
2. Pipe sizes are based on the maximum linear length,
shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 refrigerant in accordance with
unit installation instructions.

REFRIGERANT SPECIALTIES PART NUMBERS

LIQUID
LINE SIZE
(in.)
3/8
3/8
1/2
1/2
1/2

1.1 (2)

It is recommended that the refrigerant piping for all
commercial split systems include a liquid line
solenoid valve, a liquid line filter drier and a sight
glass.

Liquid line

R-22

48.8 (7)

IMPORTANT: Do not bury refrigerant piping
underground.

135 C (275 F)

lb
17.3
34.2
34.2
(2)17.3
(2)34.2
(2)34.2
(2)27.5

18.2 (60)

LIQUID LINE
Max Allow.
Max Allow.
Pressure Drop
Temp Loss
kPa (psi)
C(°F)

Refrigerant piping

-4 to 13 C (25 to 55 F)

NOTES:
. Select air handler at no less than 0 L/s per kW (00 cfm/ton)
(nominal condensing unit capacity).
. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not exceed 
va. If the specified va must be exceeded, use a remote relay to
control the load.

UNIT 38AR

MAX
ALLOW.
LIFT
m(ft)

LLSV COIL

SIGHT GLASS

FILTER DRIER

SUCTION LINE
ACCUMULATOR

200RB5T4M
200RB5T4M
200RB5T4M
200RB6T4M
200RB5T4M Qty 2

AMG-24/50-60
AMG-24/50-60
AMG-24/50-60
AMG-24/50-60
AMG-24/50-60 Qty 2

AMI1TT3
AMI1TT3
AMI1TT4
AMI1TT4
AMI1TT4 Qty 2

P502-8304S
P502-8304S
P502-8304S
P502-8307S
P502-8304S Qty 2

S-7063S
S-7063S
S-7063S
S-7063
S-7063S Qty 2

200RB5T5M Qty 2

AMG-24/50-60 Qty 2

AMI1TT5 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

200RB6T4M Qty 2
200RB6T5M Qty 2
200RB6T5M Qty 2

AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2
AMG-24/50-60 Qty 2

AMI1TT4 Qty 2
AMI1TT5 Qty 2
AMI1TT5 Qty 2
AMI1TT5 Qty 2

P502-8304S Qty 2
P502-8307S* Qty 2
P502-8307S* Qty 2
P502-8307S* Qty 2

S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2
S-7063S Qty 2

1
15

Typical wiring schematic
38ARZ 400V

2

16

Typical wiring schematic
38ARD 400V

17

3

Typical wiring schematic
38ARD ( Cont. )

Component Arrangement
Control Box

4

18

Typical wiring schematic
38ARD-028 400V

19

25

Typical wiring schematic
38ARD-028 400V ( Cont. )

Component Arrangement
Control Box

6
20

40RM007-034
6-25 Nominal Tons – 50 Hz

Model number nomenclature - 40RM
4 0 R M - 0 1 6 S D

40RM

B 5

1

E D

Factory-Installed Options

Commercial Packaged
Air Handler

Cooling Coil
-

0

ED

Painted, Standard Motor and
Standard Drive

FD

Painted, Standard Motor and
Medium-Static Drive (Not available
for 016-028 50 Hz units)

RD

Painted, Alternate Motor and
Medium-Static Drive (Available for
50 Hz sizes 016,024,028 only)

WD

Painted, Alternate Motor and
High-Static Drive

Direct Expansion

Nominal Capacity
007
6 (21)
008
7-1/2 (26)
012
10 (35)
014
12-1/2 (43)

Tons (kW)
016
15 (52)
024
20 (70)
028
25 (87)
034
30 (105)

S: SAMCO
D: Double Skin
Expansion Device
B
Thermostatic Expansion Valves (40RM )
Voltage Designation (V-Ph-Hz)
8
9

230-3-50
400-3-50

Packaging
1
Standard Domestic
3
Export

Revision Number
0
Original Model

Quality Assurance

21

27

Physical data (Cont.)
40RM - ENGLISH
UNIT 40RM
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit (Double skin) with TXV
Plenum
FANS
Qty...Diam. (in.)
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)*
230-3-50, 400-3-50
Motor Speed (rpm)
230-3-50, 400-3-50

007SD
6

008SD
71/2

012SD
10

014SD
121/2

016SD
15

024SD
20

028SD
25

034SD
30

448
97

452
97

472
97

804
140

819
140

824
140

1188
180

1198
180

1...15
1...15
1...15
2...15
2...15
2...15
2...18
2...18
2400
3000
4000
5000
6000
8000
10,000
12,000
1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
2.4

2.4

2.9

6.67
1
12
3...15

PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil - Suction (ODF)
DX Coil - Liquid Refrigerant (ODF)

1...11/8
1...11/8
1...5/8

5.0

7.5

10.0

3.5/3.5

4.5/4.5

5.0/5.0

Enhanced Copper Tubes, Aluminum Sine-Wave Fins
435
10.0
13.25
17.67
19.88
24.86
2
2
2
2
2
Face...50/50
9
9
12
13
15
3...17
3...15
3...15
3...17
3...15

29.83
2

R-22
3.0

3.0

8.33
1
15
3...15

1.5/1.5

2...11/8

Condensate (PVC)

2.0/2.0

2...11/8

2.5/2.5

2...11/8

2...11/8
2...5/8

2...13/8

18
3...15

2...13/8

1...11/4 ODM/1 IDF

FILTERS

DX TXV -

2.9
1425

REFRIGERANT
Operating charge (lb)
(approx per circuit)²
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
No. of Splits
Split Type...Percentage
No. of Circuits per Split
Rows...Fins/in.

Quantity...Size (in.)
Access Location

2.9

Washable
4...16 x 24 x 1

- Factory Supplied
4...16 x 20 x 1
4...16 x 24 x 1
Front

4...20 x 24 x 1
4...20 x 25 x 1

LEGEND
Direct Expansion
Thermostatic Expansion Valve

*Refer to alternate Fan Motor Data table, page 49, for alternate motor data.
²Units are shipped without refrigerant charge.

29
22

Options and accessories
Factory-installed

Return-air grille provides a protective barrier over the
return-air opening and givesa finished appearanceto units
installed in the occupied space. Accessory is availableun­
painted or painted.
Subbase provides a stable, raised platform and room for
condensatedrain trap connection for verticalfloor-mounted
units. Accessoryis availableunpainted or painted.
Over head suspension package includes necessary brack­
ets to support units in horizontal ceiling installations.
CO 2 sensors can be used in conjunction with the econ­
omizer accessoryto help meet indoor air quality require­
ments. The sensor signals the economizer to open when
the CO2 level in the spaceexceedsthe set point. A Carrier
Comfort Systemprogrammable thermostat can be usedto
override the sensorif the outsideair temperature is too high
or too low.
Carrier's line of ther mostats provide both program­
mable and non-programmable capability with the new
Debonair line of commercial programmable thermostats,
the TEMP System controls offer communication capabil­
ity with stagedheating and cooling, the Commercial Elec­
tronic thermostats provide 7-day programmable capability
for economicalapplications,while the Non-Programmable
thermostatsoffer a multitude of stagedheating and cooling
subbaseoptions.
Condensate drain trap includesan overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includesa wire harnessthat can be con­
nected to an alarm if desired. The transparent trap is de­
signed for easy serviceand maintenance.

options

Alternate fan motors and drives are available to pro­

vide the widest possiblerange of performance.

Field-installed accessories
Electric r esistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
single-point power connection is included.
Economizer (enthalpy contr olled) provides ventilation
air and ``free'' cooling if outside ambient temperature and
humidity are suitable. Can also be used with CO2 sensors
to help meet indoor air quality requirements.
Discharge plenum directs the air discharge directly into
the occupied space;integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available un­
painted or painted. Field assemblyrequired.
Standard units available from the factory are in

Double skin.

30
23

Options and accessories (cont)
CARRIER THERMOSTATS
DEBONAIR COMMERCIAL PROGRAMMABLE
THERMOSTAT

COMMERCIAL ELECTRONIC
THERMOSTAT

®

Pm

AUTO

COOL
HEAT

TEMP SYSTEM THERMOSTAT

NON-PROGRAMMABLE THERMOSTAT
H

C

31
24

  
40RM WITH DISCHARGE PLENUM,
RETURN-AIR GRILLE AND SUBBASE

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE

FAN
COIL
UNIT

40RM WITH ECONOMIZER

40RM WITH CONDENSATE TRAP

ECONOMIZER

32
25

Dimensions
40RM007SD-012SD
UNIT

40RM007SD
40RM008SD
40RM012SD

UNIT WEIGHT
lb (kg)
448 (203)
452 (205)
472 (214)

All the above mentioned weights
are for double skin units.

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [
millimeters.
2.

] are in

Direction of air¯ow .

3. Recommended clearance:
· Rear: 39(76.2 mm) (28-69[762 mm]
with electric heat accessory)
· Front: 28-69 (762 mm)
· Right side: 28-69 (762 mm)
· Left Side: 28-69 (762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied and
field installed.

26

33

Dimensions (cont)
40RM014SD-024SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.
UNIT

3. Recommended clearance:
· Rear: 39 (76.2 mm) (28-69
[762 mm] with electric heat
accessory)
· Front: 28-69 (762 mm)
· Right side: 28-69 (762 mm)
· Left Side: 28-69 (762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM014SD
40RM016SD
40RM024SD

All the weights men­
tioned in the table
are for double skin
units.

4

27

UNITWEIGHT
lb (kg)
804 (364)
819 (371)
824 (373)

Dimensions (cont)
40RM028SD,034SD

TXV -

Thermostatic Expansion
Valve

NOTES:
1. Dimensions in [ ] are in
millimeters.
2.
Direction of airflow.

3. Recommended clearance:
· Rear: 39 (76.2 mm)
· Front: 28-69 (762 mm)
· Right side: 28-69 (762 mm)
· Left Side: 28-69 (762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT
40RM028SD
40RM034SD

UNIT WEIGHT
lb (kg)
1188 (538)
1198 (542)

All the above mentioned weights are for
double skin units.

5
28

OVERHEAD SUSPENSION ACCESSORY
UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTE: Dimensions in [

6

29

] are millimeters.

Dimensions (cont)
PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES
UNIT SIZES 007-012

UNIT SIZES 014-024

NOTE: Dimensions in [

] are millimeters.

7
30

PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES (cont)
UNIT SIZES 028,034

NOTE: Dimensions in [

] are millimeters.

8
31

Dimensions (cont)
ECONOMIZER ACCESSORY
UNIT SIZES 007-012

UNIT SIZES 014-024

UNIT SIZES 028,034

NOTES:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.

39
32

ELECTRIC HEAT ACCESSORY
UNIT SIZES 007-012

UNIT SIZES 014-034

UNIT SIZE
014-024
028,034

A
1�-31⁄4�
[387.4]
1�-33⁄8�
[390.5]

NOTE: Dimensions in [

B
4�-63⁄8�
[1381.1]
5�-47⁄16�
[1636.8]

C
25⁄16�
[58.7]
21⁄16�
[26.9]

D
2�-11⁄4�
[641.4]
2�-63⁄16�
[766.8]

E
105⁄8�
[269.9]
1�-1⁄4�
[311.2]

] are millimeters.

40
33

F
1�-4�
[406.4]
1�-7�
[482.6]

G
1�-45⁄16�
[414.3]
1�-45⁄16�
[414.0]

H
1�-63⁄4�
[476.3]
1�-10�
[558.8]

J
1�-7⁄8�
[327.0]
1�-47⁄16�
[417.1]

FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — 50 HZ, ENGLISH
UNIT

AIRFLOW
(Cfm)

40RM
007

1,800
2,100
2,400
2,700
3,000

40RM
008

2,250
2,600
3,000
3,400
3,750

Rpm

320
373
427
480
533
359
415
478
542
598

0.0

0.2

Bhp

EXTERNAL STATIC PRESSURE (in. wg)
0.4
0.6
0.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp

Rpm

1.0

Rpm

0.32
0.45
0.62
0.82
1.03

472
516
569
624
673

0.44
0.57
0.75
0.95
1.17

560
599
645
695
740

0.55
0.68
0.86
1.08
1.29

634
669
712
758
800

0.65
0.79
0.98
1.20
1.42

700
732
773
815
855

0.75
0.90
1.09
1.31
1.60

759
790
828
869
906

0.86
1.01
1.20
1.43
1.66

814
843
879
918
954

0.96
1.11
1.32
1.55
1.78

0.22
0.31
0.42
0.54
0.69

442
483
526
570
616

0.32
0.42
0.53
0.67
0.82

534
569
606
646
687

0.42
0.53
0.64
0.78
0.94

611
642
676
712
750

0.52
0.63
0.75
0.89
1.05

678
708
739
773
808

0.61
0.73
0.86
1.00
1.16

739
767
796
828
862

Bhp

0.70
0.82
0.96
1.11
1.28

Rpm

1.2

Bhp

795
821
849
880
912

Bhp

0.80
0.92
1.06
1.21
1.39

40RM
012

3,000
3,500
4,000
4,500
5,000

444
518
592
666
740

0.58
0.82
1.11
1.44
1.83

541
604
669
735
803

0.71
0.95
1.25
1.59
1.98

621
677
736
797
861

0.83
1.08
1.38
1.72
2.12

691
742
797
854
914

0.94
1.20
1.51
1.86
2.26

753
801
853
907
964

1.05
1.32
1.63
1.99
2.39

809
855
904
956
1010

1.17
1.44
1.75
2.12
2.53

862
906
953
1003
1055

1.28
1.56
1.88
2.24
2.66

40RM
014

3,750
4,300
5,000
5,700
6,250

0.37
0.53
0.81
1.17
1.51

475
517
573
631
678

0.58
0.78
1.08
1.47
1.83

566
601
650
702
744
581
629
675
730
779

0.80
1.02
1.35
1.76
2.15

1.00
1.35
1.73
2.26
2.81

645
676
719
766
805

1.02
1.26
1.62
2.06
2.47

715
743
782
826
862

1.24
1.50
1.89
2.36
2.79

779
805
841
881
915

1.47
1.74
2.16
2.66
3.11

839
862
896
934
966

1.69
1.99
2.44
2.96
3.43

40RM
016

4,500
5,300
6,000
6,800
7,500

363
416
484
552
605

40RM
024

6,000
7,000
8,000
9,000
10,000

503
586
670
754
838

1.07
1.64
2.37
3.28
4.39

587
660
735
812
891

1.37
1.98
2.74
3.69
4.83

661
726
795
867
941

1.67
2.31
3.12
4.09
5.27

727
787
851
918
988

1.97
2.65
3.49
4.50
5.70

789
844
904
967
1034

2.28
2.99
3.86
4.90
6.14

846
898
954
1014
1077

2.59
3.33
4.23
5.31
6.85

900
948
1001
1059
1120

2.90
3.67
4.61
5.72
7.02

471
550
628
707
785

1.78
2.72
3.93
5.44
7.27

539
608
679
752
826

2.17
3.15
4.40
5.94
7.81

604
665
730
797
867

2.63
3.64
4.92
6.49
8.39

667
720
779
841
907

3.17
4.18
5.48
7.08
9.01

728
774
827
885
947

3.78
4.79
6.09
7.71
9.66

788
827
874
928
986

4.46
5.45
6.76
8.38
10.35

845
878
921
970
1024

40RM
028

40RM
034

7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000

391
460
521
590
651

412
481
549
618
687

0.51
0.80
1.13
1.60
2.10

1.15
1.76
2.55
3.52
4.71

495
551
602
663
718

492
550
610
672
735

0.75
1.08
1.43
1.93
2.45

1.53
2.17
2.99
4.00
5.22

568
616
669
725
783

2.00
2.66
3.50
4.53
5.78

See Legend and Notes on page 47.

4
34

657
700
741
791
837

640
680
726
777
830

1.25
1.63
2.04
2.59
3.16

2.56
3.22
4.07
5.12
6.38

725
764
801
847
890

710
742
782
827
876

1.50
1.91
2.34
2.92
3.52

3.22
3.86
4.70
5.76
7.04

787
823
858
901
941

776
802
836
876
922

1.76
2.20
2.65
3.26
3.88

3.98
4.58
5.40
6.45
7.74

845
878
911
951
990

840
860
889
925
966

2.02
2.48
2.96
3.60
4.24

4.83
5.38
6.17
7.21
8.49

5.22
6.18
7.47
9.10
11.07

Performance data (cont)
FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — 50 Hz, ENGLISH
UNIT

AIRFLOW
(Cfm)

40RM
007

1,800
2,100
2,400
2,700
3,000

Rpm

847
872
899
928
959

1.4

Bhp

Rpm

0.89
1.02
1.16
1.32
1.49

896
920
946
974
1004

1.6

EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
0.98
1.11
1.26
1.42
1.60

942
965
990
1018
1046

1.07
1.21
1.36
1.52
1.71

986
1008
1033
1059
1087

1.16
1.30
1.46
1.63
1.81

1027
1050
1073
1099
1126

1.25
1.40
1.55
1.73
1.92

Rpm
—
—
—
—
—

2.4

Bhp
—
—
—
—
—

2,250
2,600
3,000
3,400
3,750

865
893
928
965
1000

40RM
012

3,000
3,500
4,000
4,500
5,000

911
953
999
1047
1097

1.39
1.67
2.00
2.37
2.79

958
998
1042
1089
1138

1.50
1.79
2.12
2.50
2.92

1002
1041
1084
1129
1177

1.61
1.90
2.24
2.62
3.05

1044
1082
1124
1168
—

1.72
2.02
2.36
2.74
—

1084
1122
1162
—
—

1.83
2.13
2.48
—
—

1123
1159
1199
—
—

1.94
2.25
2.60
—
—

40RM
014

3,750
4,300
5,000
5,700
6,250

899
930
961
999
1036

1.91
2.23
2.71
3.25
3.75

2.29
2.78
3.28
3.94
4.60

947
967
997
1031
1060

2.14
2.48
2.98
3.55
4.07

996
1016
1044
1076
1104

2.37
2.73
3.26
3.86
4.39
2.84
3.38
3.92
4.63
5.34

1044
1062
1089
1120
1147

1046
1072
1098
1132
1164

2.60
2.98
3.53
4.16
4.71

3.12
3.68
4.24
4.98
5.71

1089
1107
1133
1162
1188

1091
1116
1141
1173
—

2.83
3.24
3.81
4.46
5.03
3.41
3.99
4.57
5.33
—

—
—
—
—
—

1133
1157
1181
—
—

—
—
—
—
—

40RM
016

4,500
5,300
6,000
6,800
7,500

894
916
948
984
1014

3.70
4.30
4.91
—
—

40RM
024

6,000
7,000
8,000
9,000
10,000

950
996
1047
1102
1160

3.21
4.02
4.99
6.13
7.46

999
1042
1091
1143
1200

3.53
4.37
5.37
6.54
7.91

1045
1086
1133
1183
—

3.85
4.72
5.75
6.96
—

1089
1129
1173
—
—

4.17
5.07
6.13
—
—

1131
1169
—
—
—

4.50
5.43
—
—
—

1172
—
—
—
—

4.83
—
—
—
—

901
928
966
1011
1062

6.07
6.98
8.24
9.86
11.84

955
978
1011
1052

6.98
7.84
9.07
10.67

1008
1026
1055
1092

7.98
8.76
9.95
11.52

1060
1073
1098
—

9.05
9.74
10.88
—

—
—
—
—

—
—
—
—

—
—
—
—

—
—
—
—

—

—

—

—

—

—

40RM
008

40RM
028

40RM
034

7,500
8,750
10,000
11,250
12,500

9,000
10,500
12,000
13,500
15,000

903
917
941
972
1010

1.06
1.22
1.43
1.66
1.90

5.79
6.26
7.01
8.02
9.29

913
940
973
1010
1043

951
980
1009
1045
1080

963
972
991
1019
1053

1.16
1.33
1.54
1.78
2.02

2.56
3.08
3.60
4.28
4.97

6.83
7.22
7.91
8.89
10.15

958
984
1017
1052
1084

999
1027
1055
1089
1123

1021
1025
1040
1064
1095

1.27
1.43
1.65
1.89
2.13

7.98
8.26
8.89
9.83
11.05

1001
1027
1058
1092
1124

1078
1078
1089
—
—

1.37
1.54
1.76
2.00
2.25

9.21
9.38
9.93
—
—

1042
1067
1098
1131
1162

—
—
—
—
—

—

1.47
1.65
1.87
2.12
2.37

—
—
—
—
—

—

—
—
—
—
—

—
—
—
—
—

—
—
—
—
—

—

—
—
—
—
—

—

See Legend and Notes on page 47.

5
35

Bhp ESP -

FACTOR Y-SUPPLIED FILTER PRESSURE DROP
- ENGLISH

LEGEND
Brake Horsepower Input to Fan
External Static Pressure

40RM
007

AIRFLOW
(Cfm)
1,800
2,400
3,000

PRESSURE DROP
(in. wg)
0.05
0.08
0.11

40RM
008

2,250
3,000
3,750

0.07
0.11
0.15

40RM
012

3,000
4,000
5,000

0.11
0.17
0.23

40RM
014

3,750
5,000
6,250

0.06
0.10
0.13

40RM
016

4,500
6,000
7,500

0.08
0.12
0.17

6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

UNIT

Bold indicates field supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 57-59, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 1-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. For 50 Hz units, the medium- static drive and standard motor
combination is not available for 016-028 sizes. Use alternate
motor if medium-static drive is required for these sizes.

40RM
024
40RM
028
40RM
034

ACCESSORY PLENUM AIR THROW DATA — ENGLISH
(Ft)
UNIT
40RM
007
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use
the following multipliers to determine throw values for other terminal
velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

6

THROW FACTOR
X
X
X

1.50
0.75
0.50

36

AIRFLOW
(Cfm)

VANE DEFLECTION
Straight
211⁄2°
45°

2,400

39

33

24

40RM
008

3,000

45

38

28

40RM
012

4,000

55

46

33

40RM
014

5,000

45

38

28

40RM
016

6,000

50

43

31

40RM
024

8,000

60

51

37

40RM
028

10,000

76

65

47

40RM
034

12,000

85

72

52

ACCESSORY PRESSURE DROP — ENGLISH
(in. wg)
HEATING COILS
Steam
0.10
0.16
0.23

AIRFLOW
(Cfm)

RETURN AIR
GRILLE

40RM
007

1,800
2,400
3,000

DISCHARGE
PLENUM

0.01
0.01
0.02

Hot Water
0.10
0.16
0.23

40RM
008

2,250
3,000
3,750

0.09
0.14
0.21

0.01
0.02
0.03

0.15
0.23
0.35

0.15
0.23
0.35

0.06
0.10
0.15

0.06
0.09
0.15

40RM
012

3,000
4,000
5,000

0.14
0.22
0.32

0.02
0.04
0.06

0.23
0.37
0.53

0.23
0.37
0.53

0.10
0.17
0.26

0.09
0.17
0.28

40RM
014

3,750
5,000
6,250

0.07
0.12
0.17

0.01
0.02
0.02

0.11
0.17
0.25

0.11
0.17
0.25

0.04
0.07
0.11

0.05
0.07
0.11

40RM
016

4,500
6,000
7,500

0.10
0.16
0.23

0.01
0.02
0.03

0.15
0.23
0.33

0.15
0.23
0.33

0.06
0.10
0.15

0.06
0.09
0.15

6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46

0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07

0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34

0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21

UNIT

40RM
024
40RM
028
40RM
034

0.06
0.10
0.14

Electric
0.04
0.06
0.10

ECONOMIZER
0.05
0.07
0.09

7

37

Electrical data

STANDARD MOTORS

UNIT

V*-PH-Hz

VOLTAGE
LIMITS

40RM
007
40RM
008

230-3-50
400-3-50
230-3-50
400-3-50

40RM
012
40RM
014
40RM
016

FAN MOTOR
Hp (kW)

FLA

207-253
360-440
207-253
360-440

2.4
2.4
2.4
2.4

(1.79)
(1.79)
(1.79)
(1.79)

5.2
2.6
5.2
2.6

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

230-3-50
400-3-50

207-253
360-440

40RM
024

230-3-50
400-3-50

40RM
028

230-3-50
400-3-50

207-253
360-440

40RM
034

230-3-50
400-3-50

207-253
360-440

2.9 (2.16)
2.9 (2.16)

207-253
360-440

POWER SUPPLY
Minimum
Circuit
MOCP
Amps
6.5
3.3
6.5
3.3

15
15
15
15

7.5
3.4

9.4
4.3

15
15

7.5
3.4

9.4
4.3

15
15

7.5
3.4

9.4
4.3

15
15

5.0 (3.73)
5.0 (3.73)

15.2
7.6

19.0
9.5

30
15

7.5 (5.59)
7.5 (5.59)
  
10.0 (7.46)
10.0 (7.46)

22.8
11.4

28.5
14.3

50
25

32.2
16.1

40.3
20.1

70
30

.

ALTERNATE MOTORS
FAN MOTOR

UNIT

V*-PH-Hz

VOLTAGE
LIMITS

Hp (kW)

FLA

40RM
007

230-3-50
400-3-50

207-253
360-440

2.4 (1.79)
2.4 (1.79)

5.2
2.6

230-3-50
400-3-50

207-253
360-440

5.0 (3.73)
5.0 (3.73)

5.0 (3.73)
5.0 (3.73)

40RM
008
40RM
012
40RM
014
40RM
016
40RM
024
40RM
028

230-3-50
400-3-50

230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50
230-3-50
400-3-50

207-253
360-440

207-253
360-440
207-253
360-440
207-253
360-440
207-253
360-440

2.9 (2.16)
2.9 (2.16)

5.0 (3.73)
5.0 (3.73)

7.5 (5.59)
7.5 (5.59)

10.0 (7.46)
10.0 (7.46)

6.5
3.3

15
15

15.2
7.6

19.0
9.5

30
15

15.2
7.6

19.0
9.5

7.5
3.4

9.4
4.3

15.2
7.6

19.0
9.5

22.8
11.4

28.5
14.3

32.2
16.1

40.3
20.1

15
15

30
15
30
15
50
25
60
30

Determine maximum deviation from average voltage.
(AB) 397 − 393 = 4 v
(BC) 403 − 397 = 6 v
(AC) 397 − 396 = 1 v
Maximum deviation is 6 v.

LEGEND
FLA
— Full Load Amps
MOCP — Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages
shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’ Labo­
ratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
=
3
= 397

8

POWER SUPPLY
Minimum
Circuit
MOCP
Amps

Determine percent voltage imbalance.
6
397

% Voltage Imbalance = 100 x
= 1.5%

This amount of phase imbalance is satisfactory because it is below the maxi­
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con­
tact your local electric utility company immediately.

38

Electrical data (cont)
ELECTRIC HEATER DATA
HEATER
PART NO.

UNIT

V-PH-Hz

FAN MOTOR
Hp

kW

FLA

Nominal
Capacity (kW)

ELECTRIC HEATER(S)
Actual Capacity (kW)
Stage 1
Stage 2
Total

FLA

MCA*

MOCP*

CAELHEAT001A00

240-3-50

2.4
2.9
5.0

1.79
2.16
3.73

5.2
7.5
15.2

5
5
5

5.0
5.0
5.0

—
—
—

5.0
5.0
5.0

12.0
12.0
12.0

21.5
24.4
34.0

25
25
40

CAELHEAT002A00

400-3-50

2.4
2.9
5.0

1.79
2.16
3.73

2.6
3.4
7.6

5
5
5

3.5
3.5
3.5

—
—
—

3.5
3.5
3.5

5.00
5.00
5.00

9.5
10.5
15.8

15
15
20

240-3-50

2.4
2.9
5.0

1.79
2.16
3.73

5.2
7.5
15.2

10
10
10

10.0
10.0
10.0

—
—
—

10.0
10.0
10.0

24.1
24.1
24.1

36.6
39.4
49.1

40
40
50

CAELHEAT004A00

40RM007-012

CAELHEAT005A00

400-3-50

2.4
2.9
5.0

CAELHEAT007A00

240-3-50

2.4
2.9
5.0

1.79
2.16
3.73

5.2
7.5
15.2

15
15
15

15.0
15.0
15.0

—
—
—

15.0
15.0
15.0

36.1
36.1
36.1

51.6
54.5
64.1

60
60
70

CAELHEAT008A00

400-3-50

2.4
2.9
5.0

1.79
2.16
3.73

2.6
3.4
7.6

15
15
15

10.4
10.4
10.4

—
—
—

10.4
10.4
10.4

15.0
15.0
15.0

22.0
23.0
28.3

25
25
30

CAELHEAT010A00

240-3-50

CAELHEAT011A00

25.1
25.1
25.1

34.6
35.6
40.8

CAELHEAT013A00

40RM008,012

60.1
60.1
60.1

400-3-50

2.4
2.9
5.0

25.0
25.0
25.0

240-3-50

2.4
2.9
5.0

1.79
2.16
3.73

5.2
7.5
15.2

35
35
35

20.0
20.0
20.0

15.0
15.0
15.0

35.0
35.0
35.0

2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5
2.9
5.0
7.5

2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59
2.16
3.73
5.59

7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8
3.4
7.6
11.4
7.5
15.2
22.8

10
10
10
10
10
10
20
20
20
20
20
20
30
30
30
30
30
30
50
50
50

10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0

—
—
—
—
—
—
—
—
—
—
—
—
10.0
10.0
10.0
6.9
7.9
7.9
20.0
20.0
20.0

7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0

5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46
5.59
7.46

22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1
22.8
32.2
11.4
16.1

20
20
20
20
40
40
40
40
50
50
50
50
70
70
70
70

20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8
40.0
40.0
27.8
27.8

—
—
—
—
20.0
20.0
13.9
13.9
20.0
20.0
13.9
13.9
30.0
30.0
20.8
20.8

240-3-50

CAELHEAT020A00

400-3-50

CAELHEAT022A00

240-3-50

CAELHEAT023A00

400-3-50
240-3-50

CAELHEAT026A00

400-3-50

CAELHEAT028A00

240-3-50

CAELHEAT029A00

400-3-50

CAELHEAT031A00

240-3-50

CAELHEAT034A00

10.0
10.0
10.0

10.0
10.0
10.0

400-3-50

40RM028,034

6.9
6.9
6.9

15.0
15.0
15.0

CAELHEAT017A00

CAELHEAT032A00

—
—
—

25
25
25

240-3-50

40RM016,024

6.9
6.9
6.9

5.2
7.5
15.2

CAELHEAT016A00

CAELHEAT025A00

10
10
10

1.79
2.16
3.73

400-3-50

40RM014-024

2.6
3.4
7.6

2.4
2.9
5.0

CAELHEAT014A00

CAELHEAT019A00

1.79
2.16
3.73

400-3-50
240-3-50

CAELHEAT035A00

400-3-50

CAELHEAT037A00

240-3-50

CAELHEAT038A00

400-3-50

2.4
2.9
5.0

2.9
5.0
7.5

1.79
2.16
3.73

1.79
2.16
3.73

2.16
3.73
5.59

2.6
3.4
7.6

25
25
25

2.6
3.4
7.6

35
35
35

3.4
7.6
11.4

50
50
50

10.4
10.4
10.4

13.9
13.9
13.9

20.8
20.8
20.8

6.9
6.9
6.9

10.4
10.4
10.4

13.9
13.9
13.9

15.8
16.8
22.0

20
20
25

81.7
84.6
94.2

90
90
100

84.2
84.2
84.2

111.7
114.6
124.2

125
125
125

10.0
10.0
10.0
6.9
6.9
6.9
20.0
20.0
20.0
13.9
13.9
13.9
30.0
30.0
30.0
20.8
20.8
20.8
50.0
50.0
50.0

24.1
24.1
24.1
10.0
10.0
10.0
48.1
48.1
48.1
20.0
20.0
20.0
72.2
72.2
72.2
30.1
30.1
30.1
120.3
120.3
120.3

39.4
49.1
58.6
16.8
22.0
26.8
69.5
79.1
86.4
29.3
45.1
49.2
99.6
109.2
118.7
41.8
47.1
51.8
159.7
169.4
178.9

40
50
70
20
25
35
70
80
90
30
50
50
100
110
125
50
50
60
175
175
200

20.0
20.0
13.9
13.9
40.0
40.0
27.8
27.8
50.0
50.0
34.7
34.7
70.0
70.0
48.6
48.6

48.1
48.1
20.0
20.0
96.2
96.2
40.1
40.1
120.3
120.3
50.1
50.1
168.4
168.4
70.2
70.2

88.6
100.4
39.3
45.2
148.8
160.5
64.4
70.2
178.9
190.6
76.9
82.8
196.9
208.6
84.4
90.3

90
110
40
50
150
175
70
80
200
200
80
90
200
225
90
100

17.4
17.4
17.4

24.3
24.3
24.3

34.7
34.7
34.7

35.1
35.1
35.1

50.1
50.1
50.1

47.1
48.1
53.4

66.9
72.1
76.9

25
40
50

50
50
60

70
80
80

49
39

FLA
Hp
MCA
MOCP

—
—
—
—

2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static
pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied
motors.

LEGEND
Full Load Amps
Horsepower
Minimum Circuit Amps
Maximum Overcurrent Protection (Amps)

*Values shown are for single-point connection of electric heat accessory and air
handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine
heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v ca­
pacity (kW) by the factor shown in the table below for the unit voltage.
HEATER
ACTUAL HEATER VOLTAGE
RATING
VOLTAGE 200 208 230 240 400 440 460 480 550
240
0.694 0.751 0.918 1
—
—
—
—
—
480
—
—
—
— 0.694 0.84 0.918 1
—
575
—
—
—
—
—
—
—
— 0.915

575 600

—
—
—
—
1 1.089

50
40

Typical piping and wiring
VERTICAL INST ALLA TION - 40RM (TYPICAL)

NEC TXV -

LEGEND
National Electrical Code
Thermostatic Expansion Valve
Piping

*Field supplied.
²Double riser may be required. Consult condensing unit product data catalog for
details.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
migration to the compressor.
5. Internal factory-supplied TXVs not shown.

51
41

HORIZONT AL INST ALLA TION -

NEC TXV -

LEGEND
National Electrical Code
Thermostatic Expansion Valve

40RM (TYPICAL)

2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a spe­
cific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

*Accessory item.
²Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniqes. Refer
to Carrier System Design Manual for details.

52
42

Typical piping and wiring (cont)
WIRE ROUTING, BASE UNIT -

40RM,

WIRE ROUTING, UNIT WITH ELECTRIC HEAT -

NEC -

40RM,

National Electrical Code

3
43

CONTROL WIRING SCHEMA TIC -

TYPICAL

EQUIP
GND
HC
HTR
IFC
IFM
TB

-

LEGEND
Equipment
Ground
Heater Contactor
Heater Element
Indoor Fan Contactor
Indoor Fan Motor
Terminal Block
Factory Wiring
Field Wiring

Application data
The air handler fan must always be operating when the
condensingunit is operating.
Ductwork should be sized according to unit size, not
building load. For larger units with two fans, a split duct
transition is recommendedat the fan outlets, but a plenum
can be usedwith slight reduction in external static pressure
capability.
For variable air volume (VAV) systems with supply-to­
return air recycling, usethe equipment room as a return air
plenum.

Operating limits
Maximum fan speed . . . . . . . . . . . . . . . . 1200 rpm (20 r/s)
40RM007-024
40RM028,034 . . . . . . . . . . . . . . . . 1100 rpm (18.3 r/s)

General
Select equipment to match or to be slightly lessthan peak
load. This providesbetter humidity control, lessunit cycling,
and lesspart-load operation. Equipment should be selected
to perform at no lessthan 300 cfm/ton (40 L/s per kW).

FACTOR Y-INST ALLED NOZZLE AND DISTRIBUTOR DATA
UNIT

40RM007
40RM008
40RM012
40RM014
40RM016
40RM024
40RM028
40RM034

TXV
Qty...Part No.*
1...XVE-5
1...SVE-8
2...XVE-4
2...XVE-5
2...XVE-8
2...XVE-10
2...SVE-15
2...SVE-15

DISTRIBUTOR
Qty...Part No.*
1...1116
1...1126
2...1115
2...1115
2...1116
2...1116
2...1126
2...1126

*Sporlan Valve Co. part numbers shown.

4

44

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...1/4
15...1/4
9...1/4
9...1/4
12...1/4
13...1/4
15...1/4
18...1/4

NOZZLE
Qty...Part No.
1...E5
1...C6
2...E4
2...E5
2...E6
2...E8
2...C10
2...C12

FAN MOTOR
Application data (cont)

DATA -ENGLISH

STANDARD MOTOR (230-3-50 and 400-3-50)

HIGH-ST ATIC DRIVE DATA, 5 0 Hz 40RM
007

UNIT

40RM
008
40RM
007
1425
2.4
56Y
86.4­
5/8
111.8

40RM
012
40RM
008 1425
2.9
56Y
86.4­
111.87/8

SI

40RM
40RM
40RM
024
016
014
40RM
40RM
40RM
40RM
012 1425 014 1425 016
1425024
2.9
2.9
5.0
101.6­56Y
86.4­ 56Y 101.6­ 184T
101.6­
11/8127.0
127.0 7/8
111.8 7/8 127.0

40RM
028
40RM
028
1425
7.5
S213T
109.2­
13/8
134.6

UNIT
Speed (rpm)
1425
Hp
2.4
MOTOR DRIVE
Frame
(NEMA)
56Y
Motor
Pulley
Pitch Diameter
5/8
Shaft Dia (in.)
(mm)
Pulley Factory Setting
2.5
2.5
3.0
2.5
3.0
3.0
3.0
Full Turns Open
FAN DRIVE
ALTERNATE MOTOR (230-3-50 and 400-3-50)
Pulley Pitch Dia (mm)
152
140
140
152
178
163
203
Pulley Bore (mm)
25.4 40RM25.4
25.4
36.5
36.540RM 36.5 40RM49.2
40RM
40RM
40RM
UNIT
014
024 2-B
007
008 1-A
012
Belt No. ­ Section
1-A
1-A
2-A
2-A 016 2-A
Belt Pitch (mm)
947
947
922
922
998
871
935
(rpm)
1425
1425
1425
1425
1425
1425
FANSpeed
SPEEDS
(r/s)
Hp
2.4
5.0
5.0
7.5 14.3
Factory
Setting
15.4 2.9 16.8
19.4
15.4
15.3 5.0
16.7
Frame (NEMA)
56Y
S184T
S184T
S184T 14.9­ S213T12.8­
13.5­ 56Y 14.7­
17.3­
13.5­
13.6­
Range
7/8
7/8
7/8
17.4
19.0
20.0*
17.4
17.0 11/8
18.6
Shaft Dia (in.)
11/8
13/8 15.7
Max Allowable Speed (r/s)
20.0
20.0
20.0
20.0
20.0
20.0
18.3
NEMA - National
Electrical Manufacturers Association (U.S.A.)
Change per 1/2 Turn of
Moveable Motor Pulley
0.395
0.432
0.360
0.395
0.283
0.308
0.247
Flange
MAX FULL TURNS FROM
5
5
6
5
6
6
6
CLOSED POSITION
SHAFTS CENTER DISTANCE
265-313
265-313
234-279
232-279
232-279
207-255
169-240
(mm)

40RM
034
40RM
034
1425
10.0
S215T
109.2­
13/8
134.6

3.0
218
49.2
40RM
028
2-B
960
1425
10.0
13.3
S215T
11.9­
3/8
114.6
18.3
0.230
6
169-240

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 20 r/s.

STANDARD DRIVE DATA, 5 0 Hz UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. ­ Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

5

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

2.4-3.4

2.8-3.8

3.4-4.4

3.4-4.4

3.4-4.4

4.3-5.3

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

2.5

3.0

3.0

3.0

8.0
1
1-A
39.3

8.0
1
1-A
39.3

8.0
1
1-A
40.3

9.0
1 7/16
1-A
42.3

9.0
1 7/16
1-A
42.3

8.6
1 7/16
1-B
41.8

11.0
1 15/16
2-B
43.8

11.0
1 15/16
2-B
43.8

517
428-606
1200

588
499-677
1200

695
606-784
1200

618
538-697
1200

618
538-697
1200

795
713-878
1200

622
557-687
1100

622
557-687
1100

17.8

17.8

17.8

15.9

15.9

13.8

10.8

10.8

5

5

5

5

5

6

6

6

10.44­
12.32

10.44­
12.32

10.44­
12.32

10.44­
12.32

10.44­
12.32

9.12­
10.99

6.67­
9.43

6.67­
9.43

7
45

MEDIUM-ST ATIC DRIVE DATA, 5 0 Hz UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. ­ Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

3.4-4.4

3.4-4.4

3.7-4.7

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

2.5

2.5

3.0

2.5

3.0

3.0

8.0
1
1-A
40.3

7.0
1
1-A
41.3

6.0
1
1-A
37.3

7.5
1 7/16
1-A
39.3

7.9
1 7/16
1-B
39.8

7.0
1 7/16
2-A
36.8

9.4
1 15/16
2-B
39.8

9.4
1 15/16
2-B
39.8

695
606-784
1200

794
692-896
1200

926
808-1045
1200

741
646-836
1200

756
667-848
1200

916
814-1018
1200

728
652-803
1100

728
652-803
1100

17.8

20.4

23.7

19.0

15.1

20.4

12.6

12.6

5

5

5

5

6

5

6

6

10.44­
12.32

10.44­
12.32

10.44­
12.32

10.44­
12.32

9.16­
10.99

9.16­
10.99

6.67­
9.43

6.67­
9.43

HIGH-ST ATIC DRIVE DATA, 5 0 Hz UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. ­ Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
Change per 1/2 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE
(in.)

ENGLISH

40RM
007

40RM
008

40RM
012

40RM
014

40RM
016

40RM
024

40RM
028

40RM
034

3.4-4.4

3.4-4.4

4.0-5.0

3.4-4.4

4.0-5.0

4.0-5.0

4.3-5.3

4.3-5.3

2.5

2.5

3.0

2.5

3.0

3.0

3.0

3.0

6.0
1
1-A
37.3

5.5
1
1-A
37.3

5.5
1
1-A
36.3

6.0
1 7/16
2-A
36.3

7.0
1 7/16
2-A
39.3

6.4
1 7/16
2-A
34.3

8.0
1 15/16
2-B
36.8

8.6
1 15/16
2-B
37.8

926
808­
1045
1200

1010
881­
1140
1200

1166
1036­
1200*
1200

926
808­
1045
1200

916
814­
1018
1200

1002
891­
1113
1200

855
766­
944
1100

795
713­
878
1100

23.7

25.9

21.6

23.7

17.0

18.5

14.8

13.8

5

5

6

5

6

6

6

6

10.44­
12.32

10.44­
12.32

916­
10.99

9.16­
10.99

9.16­
10.99

8.16­
10.02

6.67­
9.43

6.67­
9.43

*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.

8

ENGLISH

46

Guide Specifications 38ARZ007-012
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications

Size Range: 6 to 10 Tons, Nominal
Carrier Model Numbers: 38ARZ, Sizes 007-012
Part 1 — General
.0 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall consist of a reciprocating or scroll airconditioning compressor assembly, an air-cooled
coil, propeller- type condenser fans, and a control
box. Unit shall discharge supply air upward as
shown on contract drawings. Unit shall be used in
a refrigeration circuit matched with a packaged airhandling unit.
.0 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 0-000.
B. Unit construction shall comply with
ANSI/ASHRAE  safety code latest revision and
comply with NEC.
C. Unit shall be constructed in accordance with UL
 standard.
D. Unit cabinet shall be capable of withstanding
00-hour salt spray exposure per ASTM B
(scribed specimen).
E. Air-cooled condenser coils for (ARZ) shall be
leak tested at 00 psig, and pressure tested at 
psig.
F. Unit shall be manufactured in a facility
registered to ISO 00:000 manufacturing quality
standard.
.0 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturer’s recommendations.
.0 WARRANTY (FOR INCLUSION
SPECIFYING ENGINEER.)

BY

Part 2 — Products
.0 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-), and
special features required prior to field start-up.
B. Unit Cabinet:
. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted
baked enamel finish.

. A heavy-gage roll-formed perimeter base rail
with forklift slots and lifting holes shall be
provided to facilitate rigging.
C. Fans:
. Condenser fans shall be direct driven, propeller
type, discharging air vertically upward.
. Fan blades shall be balanced.
. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
. Compressor shall be of the hermetic scroll type
. Compressor shall be mounted on rubber
grommets.
. Compressors shall include overload protection.
. Compressors shall be equipped with a crankcase
heater.
. Compressor shall be equipped with internal high
discharge temperature protection (ARZ00 and
0 only).
E. Condenser Coil:
. Condenser coil shall be air-cooled and circuited
for integral subcooler.
. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include
liquid line service valve, suction line service valve,
a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
. Minimum safety devices which are equipped
with automatic reset (after resetting first at
thermostat), shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
c. High discharge temperature cutout (ARZ00
only).
H. Operating Characteristics:
. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of

59
47

_____ F. The power consumption at full load shall
not exceed _____ kW.
. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and
_____ F dry bulb, and air entering the condensing
unit at _____F.
. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
. Nominal unit electrical characteristics shall be
_____ v, -ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of ____
v to _____ v.
. Unit electrical power shall be single-point
connection.
. Unit control circuit shall contain a -v
transformer for unit control.
J. Special Features:
. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a field-installed accessory. This lowambient control shall regulate speed of the
condenser-fan motors in response to the saturated
condensing temperature of the unit. The control
shall maintain correct condensing pressure at
outdoor temperatures down to –0 F.
. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
. Thermostat Controls:
a. Programmable multi-stage thermostat shall have
-day clock, holiday scheduling, large backlit
display, remote sensor capability, and Title 
compliance.
b. Commercial Electronic Thermostat shall have day timeclock, auto-changeover, multi-stage
capability, and large LCD (liquid crystal display)
temperature display.
c. Carrier PremierLink™ Controller:
This control will function with CCN (Carrier
Comfort Network®) and ComfortVIEW™
software. It shall also be compatible with
ComfortLink™ controllers. It shall be ASHRAE
- compliant and Internet ready. It shall accept
a CO sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready. The
communication rate must be .K or faster. It
shall include an integrated economizer controller.

60
48

Guide specifications— 38ARD014-028
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications

Size Range: 121/2 to 20 Tons, Nominal
Carrier Model Number: 38ARD, Sizes 014-024
Part 1 — General
.0 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall have  independent refrigeration
circuits. Unit shall consist of dual scroll
compressors, an aircooled coil, propeller-type
condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract
drawings. Unit shall be used in a refrigeration
circuit matched with a packaged airhandling unit.
.0 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 0-000, and shall be certified and listed
in the latest ARI directory.
B. Unit construction shall comply with
ANSI/ASHRAE safety code, latest revision, and
comply with NEC.
C. Unit shall be constructed in accordance with UL
 standard and shall carry the UL and UL,
Canada label.
D. Unit cabinet shall be capable of withstanding
00-hour salt spray exposure per ASTM B
(scribed specimen).
E. Air-cooled condenser coils shall be leak tested
at 0 psig, and pressure tested at 0 psig.
F. Unit shall be manufactured in a facility
registered to ISO 00:000 manufacturing quality
standard.
.0 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturer’s recommendations.
.0 WARRANTY (FOR INCLUSION BY
SPECIFYING ENGINEER.)
Part 2 — Products
.0 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-), and
special features required prior to field start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-0
galvanized steel, bonderized and coated with a
prepainted baked enamel finish.
C. Fans:
. Condenser fans shall be direct driven,
propellertype, discharging air vertically upward.
. Fan blades shall be balanced.

. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
. Compressors shall be of the hermetic scroll type.
. Compressors shall be mounted on rubber
grommets.
. Compressors shall include overload protection.
. Compressors shall be equipped with a crankcase
heater.
. Compressors shall be equipped with internal
high discharge temperature protection (ARD0
and 0 only).
E. Condenser Coil:
. Condenser coil shall be air-cooled and circuited
for integral subcooler.
. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include high
side pressure relief device, liquid line service
valve, suction line service valve, a full charge of
compressor oil, and a holding charge of refrigerant.
G. Controls and Safeties:
. Minimum control functions shall include:
a. Power and control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
c. Recycle time delay of five minutes to prevent
compressor short cycling.
. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat):
a. High discharge pressure cutout.
b. Loss-of-charge cutout.
c. Condenser fan motors to be protected against
overload condition by internal overloads.
Manual reset at the unit:
Electrical overload protection through the use of
define-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers.
Circuit breakers shall open all three phases in the
event of an overload in any one of the phases or a
single phase condition.
H. Operating Characteristics:
. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall
not exceed _____ kW.

61
49

. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and _____ F
dry bulb, and air entering the condensing unit at
_____ F.
. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
. Nominal unit electrical characteristics shall be
_____ v, -ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
_____ v to _____ v.
. Unit electrical power shall be single-point
connection.
. Unit control circuit shall contain a -v
transformer for unit control.
J. Special Features:
. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a factory-installed option or as a fieldinstalled accessory. This low-ambient control shall
regulate speed of the condenser-fan motors in
response to the saturated condensing temperature
of the unit. The control shall maintain correct
condensing pressure at outdoor temperatures down
to –0 F.
. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal

environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide
protection
in
moderate
coastal
environments.
. Thermostat Controls:
a. Programmable multi-stage thermostat with -day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title  compliance.
b. Commercial Electronic Thermostat with -day
timeclock, auto-changeover, multistage capability,
and large LCD (liquid crystal display) temperature
display.
c. Carrier PremierLink™ Controller:
This control will function with Carrier Comfort
Network® (CCN) and ComfortVIEW™ software.
It shall also be compatible with ComfortLink™
controllers. It shall be ASHRAE - compliant
and Internet ready. It shall accept a CO sensor in
the conditioned space and be Demand Control
Ventilation (DCV) ready. The communication rate
must be .K or faster. It shall include an
integrated
economizer
controller.

62
50

Guide specifications 40RM
A. Base Unit (Painted):
1. Cabinetshall be constructed of zinc coated steel
and polyester powder painted to protect them
from corrosion in the harsh Middle Eastern climate
and also to increase the colour life in high ultra­
violet (UV) radiation regions.
2. Cabinet panels shall be fully insulated with 1/2 in.
(12.7-mm) fire-retardant material.

Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
SizeRange: 2,400 to 12,000 CFM (1150 to 5650 L/s),
Nominal Airflow 6 t o 3 0 Tons (21 to
105 kW), Nominal Cooling
Carrier Model Numbers: 40RM (Direct-Expansion Coil)

3. Unit shall contain PVC condensate drain pans for
both vertical and horizontal applications. Drain
pans shallhave connectionson right and left sides
of unit to facilitate field connection. Drain pans
shall have the ability to be sloped toward the right
or left side of the unit to prevent standing water
from accumulatingin pans.
4. Unit shall have factory-supplied 1-in. (25.4 mm)
washable-type filters installed upstream from the
cooling coil. Filter access shall be from the front
of the unit.
B. Coils:
Coils shall consist of 3 rows (40RM), of
coppertubes with sine-wave aluminum fins bonded
to the tubes by mechanical expansion. Suction and
liquid line connectionsor supply and discharge con­
nections shallbe made on the same side of the coil.

Part 1 - GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commer­
cial split systems.Unit shall have a multiposition de­
sign and shall be capable of horizontal or vertical
installation on a floor or in a ceiling, with or without
ductwork. (Only vertical units are to be applied with­
out ductwork.)
B. Unit with direct-expansioncoil shall be used in a re­
frigerant circuit with a matching air-cooled con­
densing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed & tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigera­
tion (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada, standardsand shall carry
the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with
NFPA-90A (U.S.A.)requirements for flame spread
and smoke generation.

1. Direct-expansioncoilsshallfeaturefactory-installed
thermostatic expansion valves (TXVs) for refrig­
erant control. The TXVs shall be capable of ex­
ternal adjustment. Direct-expansion heat pump
coils shall have a factory-installedbypassline and
check valve assemblyaround the TXVs to allow
liquid flow from the coil to the outdoor unit during
the heating mode. Coil tubing shall be internally
rifled to maximize heat transfer.

D. Unit shall be manufactured in a facility registered to
the ISO 9002 manufacturing quality standard.
E. Direct-expansionand chilled water coils shallbe burst
and leak tested at 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer's
recommendations.
Par t 2 - Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configu­
ration or a vertical configuration. Unit shall consistof
forward-curved belt-driven centrifugal fan(s), motor &
drive assembly,prewired fan motor contactor, factory­
installedrefrigerant metering devices(direct-expansion
coil units), cooling coil, 1-in. (25.4-mm) washable air
filters, and condensate drain pans for vertical or hori­
zontal configurations.

C. Operating Characteristics:
Unit shall be capable of providing
cfm (L/s)
airflow at an external static pressureof
in. wg
(kPag).
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment scheduleshall be factory
supplied and installed.
Motors rated at 1.3 through 3.7 hp (0.97 through
2.76 kW) shall have internal thermal overload pro­
tection. Motors rated at 5, 7 1/2 , and 10 hp (3.73,
5.60, and 7.46 kW) shall be protected by a circuit
breaker.

63
51

E. Factory-InstalledOptions:
1. Alternate Motor and Drive:
An alternate motor and/or medium- or high-static
drive shall be available to meet the airflow and
external static pressure requirements specified
on the equipment schedule.

6. Thermostat Controls:
a. Debonair programmablemulti-stagethermo­
statwith 7-dayclock, holiday scheduling,large
ThermoglowŸ display, remote sensorcapa­
bility, and Title 24 compliance.
b. TEMP System programmable communicat­
ing multi-stage thermostat with fan switch,
time clock, LCD display,ÉF/ÉC capability,and
CCN compatiblity.
c. CommercialElectronicThermostatwith 7-day
time clock, auto-changeover, multi-stageca­
pability, and large LCD temperature display.
d. Non-programmablethermostatwith fan switch
subbase.
7. Overhead SuspensionPackage:
Package shall include necessary brackets to
support units in a horizontal ceiling installation.
8. CO2 Sensor:
Sensorshallprovide the ability to signalthe econo­
mizer to open when the spaceCO2 levelexceeds
the predetermined set point. Sensor shall have
the capability of being connected to Comfort
System relay pack or to economizer using field­
supplied and -installed Honeywell dc adapter
no. Q769C1004.
9. CondensateDrain Trap:
Trap shall have transparent, serviceabledesign
for easycleaning. Kit shallinclude overflow shut­
off switch and wiring harnessfor connection to
an alarm if desired.

F. Field-InstalledAccessories (ordered from NAO):
1. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz; and 240, 400-volt, 3 phase,
50 Hz power supply shallbe factory-suppliedfor
field installationasshown on the equipmentdraw­
ings. Electricheat assemblyshallbe ETL (U.S.A.)
and ETL, Canada, agency approved, and shall
have single-point power wiring. Heater assem­
bly shallincludecontactorswith 24-V coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged accesspanel. Electric heaters shall not
be used with air discharge plenum.
2. Air Discharge Plenum:
Plenum shall be factory supplied to provide free­
blow air distribution for vertical floor-mounted
units. A grille with moveable vanes for hori­
zontal or vertical airflow adjustment shall be
included. Plenum shall be field-assembledand
field-installedon the unit's fan deck for blow-thru
air distribution. Plenum shall not be used with
electric heaters.
3. Return Air Grille:
Grille shall be factory supplied for field installa­
tion on the unit's return air opening.
4. Unit Subbase:
Subbaseassemblyshall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for
correct condensate drain connection.
5. Economizer:
Economizerfor ventilation or ``free'' cooling shall
be factory provided for field installation on either
return air opening of air handler. For free cool­
ing applications, economizershallbe compatible
with separate thermostat; economizer dampers
shall open when outdoor air enthalpy is suitable
for free cooling. Economizershall be compatible
with separate CO2 sensor accessory; economizer
dampersshall open when indoor CO2 level rises
abovepredetermined setpoint. Economizershall
include enthalpy control and damper actuator.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

2010

52

Form 38AR-01 PD 50Hz CKAC



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1.1-111
Instance ID                     : uuid:f5eaa073-6eec-11df-9068-000393720206
Document ID                     : adobe:docid:indd:8c985e50-6b0f-11df-b9b7-8469e2b7dc1f
Rendition Class                 : proof:pdf
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Y Resolution    : 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00, 72.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1, uuid:eae85c2c-890b-44c9-99a5-c0c012d6d1e1
Manifest Reference Document ID  : uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8, uuid:cdfd9e8c-580c-4629-b183-76bf9f5222b8
Create Date                     : 2010:06:03 11:44:14+03:00
Modify Date                     : 2010:06:03 11:49:46+03:00
Metadata Date                   : 2010:06:03 11:49:46+03:00
Creator Tool                    : Adobe InDesign CS2 (4.0)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 10960 bytes, use -b option to extract)
Format                          : application/pdf
Producer                        : Adobe PDF Library 7.0
Trapped                         : False
Page Count                      : 52
Creator                         : Adobe InDesign CS2 (4.0)
EXIF Metadata provided by EXIF.tools

Navigation menu