38AD028 38ARZ ARD

User Manual: 38AD028

Open the PDF directly: View PDF PDF.
Page Count: 52

1
Carrier’s air-cooled split systems:
provide a logical solution for
commercial needs
have a rugged, dependable
construction
Features/Benefits
These dependable split
systems match Carrier’s
indoor-air handlers and direct-
expansion coils with outdoor
condensing units for a wide
selection of commercial
cooling solutions.
Up to 11.0 EER
The high efficiency split commercial split
system combining the 38ARZ/ARD
outdoor condensing unit with 40RM air
handling unit can save 20-27% of energy
consumption.
Constructed for long life
The 38ARZ (single circuit, scroll
compressor) and 38ARD (dual circuit,
scroll compressor) models are designed and
built to last. The copper tube-aluminum fin
outdoor coil construction provides years of
trouble-free operation. Where conditions
require, a range of Enviro-Shield coil
protection options are available. Cabinets
are constructed of prepainted galvanized
steel, delivering unparalleled protection
from the environment. Inside and outside
surfaces are protected to ensure long life,
good looks, and reliable operation. Safety
controls are used for enhanced system
protection and reliability.
Product Data
The 38ARZ/ARD condensing units with scroll compressors match Carrier’s 40RM
indoor-air handlers for a wide selection of dependable commercial cooling solutions.
38AR-03 PD 50Hz CKAC 2010
38ARZ/ARD
Commercial Air-Cooled Split
Sizes 007 - 028
With 40RM007-028
5-24 Nominal Tons - 50Hz
2
2
Efficient operation
Building owners will appreciate the high unit EERs
(Energy Efficiency Ratios) offered by the 38AR units.
These units provide greater efficiency than similar
units in the marketplace, which translates into year-
round operating savings.
Controls for performance dependability
The 38AR condensing units offer the building owner
operating controls and components designed for
performance dependability. The highly efficient
compressors are engineered for long life and
durability. The compressors include overload
protection and vibration isolation for quiet operation.
The high pressure switch protects the entire
refrigeration system from abnormally high operating
pressures. A low pressure switch protects the system
from loss of charge.
The 38ARD014-028units feature 2 compressors and 2
refrigerant circuits that provide continuous air
conditioning and design flexibility.
All units include a crankcase heater to eliminate liquid
slugging at start-up. The latest safety standards for
38AR units are UL, compliant.
Innovative Carrier 40RM packaged air
handlers are custom matched to 38AR
condensing units
The 40RM Series has excellent fan performance,
efficient direct-expansion (DX) coils, a unique
combination of indoor-air quality options, and is easy
to install. Its versatility and state-of-the art features
help to ensure economical performance of the split
system both now and in the future.
Indoor-air quality (IAQ) features —
The unique combination of IAQ features in the 40RM
Series air handlers help to ensure that only clean,
fresh, conditioned air is delivered to the occupied
space.
Direct-expansion (DX) cooling coils prevent the build-
up of humidity in the room, even during part-load
conditions. Unit sizes of 10 tons and larger feature
dual-circuit coils for improved temperature control.
Standard 1-in. aluminum washable filters remove dust
and airborne particles from the occupied space for
cleaner air.
The pitched, non-corroding drain pan can be adjusted
for a right-hand or left-hand connection to suit many
applications and provide positive drainage and prevent
standing condensate.
Economy The 40RM Series packaged air handlers
have low initial costs, and provide reduced installation
expense and energy-efficient performance.
Quick installation is ensured by the multipoise design.
Units can be installed in either the horizontal or
vertical configuration without modifications. Fan
motors and contactors are prewired and thermostatic
expansion valves (TXVs) are factory-installed on all
40RM models.
High efficiency, precision-balanced fans minimize air
turbulence, surging, and unbalanced operation, cutting
operation expenses.
Rugged dependability The 40RM series units are
made to last. The die-formed galvanized steel panels
ensure structural integrity under all operating
conditions. Galvanized steel fan housings are securely
mounted to a galvanized steel fan deck. Rugged
pillow-block bearings (40RM014-034) are securely
fastened to the solid steel fan shaft with split collets
and clamp locking devices. Smaller unit sizes have
spider-type bearings.
Coil flexibility Model 40RM directexpansion coils
have galvanized steel casings; inlet and outlet
connections are on the same end. The coils are
designed for use with R-22 refrigerant and have 3/8-in.
diameter copper tubes mechanically bonded to
aluminum sine-wave fins.
The coils include matched, factoryinstalled
thermostatic expansion valves (TXVs) with matching
distributor nozzles.
Easier installation and service —
The multipoise design and component layout ensures
quick unit installation and operation. Units can be
converted from horizontal to vertical operation by
simply repositioning the unit. Drain pan connections
are duplicated on both sides of the unit. The filters,
motor, drive, TXVs, and coil connections are all easily
accessed by removing side panels.
3
3
Model number nomenclature
Z007 -- - 9 0 1 S
Type
38AR–Commercial Air-
Cooled Condenser
S - High Ambient
Packaging
1 - Standard
Z-Single Circuit
D- Dual Circuit Design Series
0 - Original Design
Nominal Capacity in-Tons
007 - 5.0
Voltage
008 - 7 .0 Tons 9 4003–50
012 - 8.7 Tons
014 - 10. Tons
016 - 14Tons
Fin Type
024 - Tons -- - Standard Bare Fins
C- Cu/Cu Coil
P- Pre-Coated Blue Fins
-- - Not Used
Table of Contents
Page.
38ARZ/ARD
Features/Benefits………………………………………………………………………………………. 1
ModelNumber Nomenclature………………………………………………………………………….. 3
Physical Data……………………………………………………………………………………………. 4
ARI Capacity ratings 50Hz ……………………………………………………………………………. 6
Options and accessories ………………………………………………………………………………. 7
Electrical Data…………………………………………………………………………………………… 7
Base Unit Dimensions………………………………………………………………………………….. 8-10
Performance data ……………………………………………………………………………………… 11-20
Application Data………………………………………………………………………………………… 21
Typical Wiring Schematic………………………………………………………………………………. 22-26
40RM
Model number nomenclature………………………………………………………………………….. 27
Physical Data……………………………………………………………………………………………. 28,29
Options and accessories ………………………………………………………………………………. 30-32
Base Unit Dimensions………………………………………………………………………………….. 33-40
Fan Performance Data ……………………………………………………………………………….. 41-47
Electrical Data…………………………………………………………………………………………… 48-50
Typical piping and wiring ……………………………………………………………………………… 51-54
Application Data………………………………………………………………………………………… 54-58
Guide Specifications
Guide Specifications —38ARZ007-012………………………………………..…………………… 59,60
Guide specifications— 38ARD014-028 ……………………………………………………………. 61,62
Guide specifications —40RM………………………………………………………………………… 63,64
38AR
8
18.1
Tons
028 - Tons
24
4
4
Physical Data – English
UNIT 38AR
ARZ ARD
007 008 012 014 016 024
NOMINAL CAPACITY (Tons) 5.0 7 9.3 10 1418
OPERATING WEIGHT (lb)
Aluminium Coils (Standard)
Cooper Coils (Optional)
300
352
383
484
430
531
676
822
740
886
764
904
COMPRESSOR Scroll
Qty
Oil Charge (oz) 88 90 110 60(ea) 85(ea) 110(ea)
REFRIGERANT TYPE *
Operating Charge, Typical (lb) **
Shipping Charge (lb)
R22
12 20 22 11.5/circuit 14/circuit
2.0 3.1
FINISH Gray
CONDENSER FAN Propeller Type
Qty…RPM 2…700 2…920 2…900
Diameter
Nominal Air Flow (Total CFM)
22 in 26 in
5000 5800 9210
Motor HP-Shaft 2x1/8 2x1/4 2x1/2
CONDENSER COIL (Qty) 2
Face Area (sq ft Total)) 29.2 29.2
Rows…Fins/in. 1…17 2…17 3…15
Storage Capacity (lb)*** 17.3 34.2 48
CONTROLS
Pressurerestart Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
428 ± 10
320 ± 20
27 ± 3
44 ± 5
428 ± 10
320 ± 20
27 ± 4
44 ± 7
DISCHARGE GAS THERMOSTAT (0F)
Cutout
Cut-in
--- 270 ± 9
190 ± 13 ---
PRESSURE RELIEF
Location
Tempreature
Suction Line
200
Liquid Line
200
PIPING CONNECTION
Qty…Suction 1…1 1/8 1…1 1/8 1…1 3/8 2…1 3/8
Qty…Liquid 1… 3/8 1… 3/8 1… 1/2 2… 1/2
Hot Gas Stub 3/8
*Unit is factory-supplied with holding charge only.
**Typical operating charge with 25 ft of interconnecting piping.
***Storage capacity of condenser coil with coil 80% full of liquid R-22 at 95 F.
.0.8.
1
028
24
127
153
111(ea)
17.97
2…900
30 in
1300
2x1
50.4
3…16
-
428 ± 10
320 ± 20
27 ± 4
44 ± 7
---
Liquid Line
200
2…1 3/8
2… 5/8
-
9
2
/circuit
0
SHIPPING DIMENSIONS (in) (W X H X D) (59.2X45.5X39) (72.6X44.25X41.7) (96.5X49.6 X54.3)
UNIT 38AR
ARZ ARD
007 008 012 014 016 024 028
5
6
Capacity ratings 50 Hz
LEGEND
db — Dry Bulb
wb — Wet Bulb
SST — Saturated Suction Temperature
*System gross capacities are rated according to indoor unit airflow, 35 C air temperature entering condenser, and 20 C wb air temperature entering
evaporator.
†System gross capacities are rated according to indoor unit airflow, 95 F air temperature entering condenser, and 67 F wb air temperature entering
evaporator.
**Condensing unit gross capacity based on 36 C air temperature entering condenser and 8 C SST.
††Condensing unit gross capacity based on 95 F air temperature entering condenser and 45 F SST.
SOUND LEVELS, dB — 38AR UNITS
UNIT
38AR
SOUND
RATING
dB(A)
OCTAVEBANDS
631252505001000200040008000
Z007
Z008
Z012
80.0
84.0
85.0
71.5
84.1
88.7
76.8
84.5
85.4
75.3
80.4
81.7
74.0
78.6
80.9
73.9
77.2
82.1
74.1
76.9
76.2
73.5
78.8
73.6
64.0
72.5
67.1
D014
D016
D024
86.9
87.5
88.0

90.9
90.9
90.9
86.1
86.1
86.1
83.1
83.4
83.8
84.0
84.5
84.5
73.5
76.6
79.2
71.7
73.2
74.3
66.7
63.5
65.5
NOTES:
1. 38ARZ unit is in accordance with ARI 270-95 Sound Rating of Unitary Equipment.
2. Estimated sound power levels, dB re 1 Picowatt. 38ARD014-024 and 38AKS data is based upon a limited amount of actual testing with the estimated sound power
data being generated from this data in accordance with ARI Standard 370 for large outdoor refrigerating and air-conditioning equipment. Since this data is estimated, the
sound power levels should not be guaranteed or certified as being the actual sound power levels.
3. The acoustic center of the unit is located at the geometric center of the unit.
ESTIMATED SOUND POWER LEVELS (Lw) — 40RM007-028
UNITCFMdB(A)OCTAVEBANDCENTERFREQUENCY
63125250500100020004000
40RM007240086.393.289.285.284.280.278.274.2
40RM008300088.395.391.387.386.382.380.376.3
40RM012400091.698.694.690.689.685.683.679.6
40RM014500091.197.393.389.390.384.382.378.3
40RM016600092.798.994.990.991.985.983.979.9
40RM024800096.4102.698.694.695.689.687.683.6
CONDENSINGUNITAIRHANDLER/INDOOR
COIL
SYSTEMGROSSCAPACITYCONDENSINGUNIT
ONLYGROSSCAPACITY
kW* Btuh kW**Btuh
38ARZ00740RM007
40RM008
18.4
19.0
62,200
64,30018.060,300
38ARZ008
40RM007
40RM008
40RM012
23.3
24.0
25.4
78,700
81,400
86,100
25.083,900
38ARZ012
40RM008
40RM012
40RM014
30.1
31.9
33.4
102,000
108,000
113,000
33.2112,000
38ARD014

40RM014

40.4
138,000
41.6142,000
38ARD016
40RM016

56.3
192,00057.8197,200
38ARD024

40RM024

63.0215,000
64.6218,000
38ARD028

40RM028

81.1276,600
84.0286,700
D02894.8 91.4 88.1 85.8 86.4 81.5 75.2 67.4
40RM02810000 96.2102.598.594.595.589.587.583.5
6
7
Options and accessories
38AR, options
Enviro-Shield condenser options offer pre-coated coils that provide protection in mild coastal
environments. Several options are available to match coil protection to site conditions for optimum durability.
See table below. Consult your Carrier representative for further information.
Non-fused disconnect switch to remove power locally at the condensing unit. This switch also includes a
power lockout capability to protect the service person. This lockout switch saves the service person time and
effort because there is no need to access a distant disconnect switch while servicing the unit.
Carrier’s line of thermostats provide both programmable and non-programmable capability with the new
Debonair® line of commercial programmable thermostats. The Commercial Electronic thermostats provide
7-day programmable capability for economical applications.
PremierLink™ Controller is a field retrofit split system control compatible with the Carrier Comfort Network
(CCN) and other building automation systems (BAS). This control is designed to allow users the access and
ability to change factory-defined settings thus expanding the function of the standard unit.
CONDENSER COIL OPTIONS
COPPERͲTUBECOILS
WITHENVIROͲSHIELDOPTION
ENVIRONMENT
Standard MildCoastal ModerateCoastal
AlFins(StandardCoils) X
CuFins X
AlFins,PreͲCoated X
LEGEND
Al — Aluminum
Cu — Copper
Electrical data
UNIT
SIZE
38AR
NOMINAL
VOLTAGE
V-Ph-Hz
VOLTAGE
RANGE*
COMPRESSOR
1
COMPRESSOR
2
FAN MOTORS
(Qty 2)
POWER
SUPPLY
MIN MAX RLA LRA RLA LRA FLA
(ea)
LRA
(ea) MCA MOCP
Z007 400-3-50 360 440 9.6 82-- -- 0.5 0.9 12.4 20
Z008 400-3-50 360 440 13.5 95 -- -- 0.8 1.6 17.9 30
Z012 400-3-50 360 440 20.7 130 -- -- 0.8 1.6 26.9 45
D014 400-3-50 360 440 9.6 829.6 821.7 -- 27.8 30
D016 400-3-50 360 440 13.5 95 13.5 95 1.7 -- 38.0 45
D024 400-3-50 360 440 20.7 130 20.7 130 1.7 7.5 56.0 70
LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps per NEC, Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA — Rated Load Amps (compressor)
*Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with
theNational Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
D028 400-3-50 360 440 22.9 145 22.9 145 3.0 -- 80
63.3
7
8
Base Unit Dimensions – 38ARZ 007 – 012
38ARZ Size
Approximate Shipping Weight Approx. Shipping Dimensions
( A x B x C )
With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG LB KG LB mm inch
007 154 339 178 392
(1504X1157X992) (59.2X45.5X39) 008 192 422 238 524
012 213 467 259 570
8
9
Base Unit Dimensions – 38ARD 014 – 024
38ARD Size
Approximate Shipping Weight Approx. Shipping Dimensions
( A x B x C )
With Standard Al/Cu Coil With Optional Cu/Cu Coil
KG LB KG LB mm inch
014 357 785 423 931
(1844X1124X1058) (72.6X44.25X41.7) 016 386 849 452 994
024 397 873 461 1014
9
10
Base Unit Dimensions – 38ARD 028
10
12
CONDENSING UNIT RATINGS — ENGLISH
38ARZ007
SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 105 115
25
TC
kW
SDT
44.80
3.50
99.8
43.60
3.72
105.0
41.20
4.15
115.0
40.00
4.39
120.0
38.80
4.63
124.0
36.30
5.12
134.0
30
TC
kW
SDT
49.40
3.56
101.0
48.20
3.78
106.0
45.60
4.20
116.0
44.30
4.45
121.0
43.00
4.69
125.0
40.40
5.18
135.0
35
TC
kW
SDT
54.30
3.63
102.0
52.90
3.85
107.0
50.30
4.28
117.0
48.90
4.52
122.0
47.50
4.77
127.0
44.70
5.25
136.0
40
TC
kW
SDT
59.50
3.71
104.0
58.00
3.93
109.0
55.10
4.36
118.0
53.70
4.60
123.0
52.20
4.85
128.0
49.20
5.34
138.0
45
TC
kW
SDT
65.00
3.81
106.0
63.40
4.02
110.0
60.30
4.45
120.0
58.70
4.70
125.0
57.10
4.94
130.0
54.00
5.44
139.0
50
TC
kW
SDT
70.70
3.91
108.0
69.10
4.12
112.0
65.80
4.56
122.0
64.10
4.80
127.0
62.40
5.05
131.0
59.00
5.54
141.0
38ARZ008
SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 105 115
25
TC
kW
SDT
61.30
4.79
98.5
59.40
5.07
103.0
55.50
5.65
113.0
53.40
5.96
118.0
51.40
6.27
123.0
47.10
6.93
133.0
30
TC
kW
SDT
68.30
4.81
98.8
66.40
5.09
104.0
62.30
5.68
114.0
60.20
5.99
119.0
58.00
6.31
123.0
53.60
6.99
133.0
35
TC
kW
SDT
75.50
4.88
99.9
73.50
5.15
105.0
69.30
5.74
114.0
67.10
6.06
119.0
64.90
6.38
124.0
60.30
7.06
134.0
40
TC
kW
SDT
83.00
4.97
101.0
80.80
5.24
106.0
76.40
5.84
116.0
74.10
6.16
121.0
71.80
6.48
125.0
67.00
7.17
135.0
45
TC
kW
SDT
90.90
5.06
103.0
88.60
5.34
108.0
83.90
5.94
117.0
81.50
6.27
122.0
79.10
6.59
127.0
74.10
7.29
136.0
50
TC
kW
SDT
99.20
5.17
105.0
96.80
5.45
110.0
91.80
6.06
119.0
89.20
6.39
124.0
86.70
6.72
128.0
81.40
7.43
138.0
38ARZ012
SST (F) Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25
TC
kW
SDT
85.00
6.64
101.0
82.70
6.94
106.0
77.90
7.57
116.0
75.50
7.90
121.0
73.10
8.25
126.0
67.90
8.98
136.0
30
TC
kW
SDT
93.30
6.81
102.0
90.90
7.09
107.0
85.80
7.69
116.0
83.20
8.01
121.0
80.50
8.35
126.0
75.10
9.06
136.0
35
TC
kW
SDT
102.00
7.01
103.0
99.50
7.29
108.0
94.00
7.87
117.0
91.20
8.18
122.0
88.40
8.50
127.0
82.60
9.18
136.0
40
TC
kW
SDT
111.00
7.24
104.0
108.00
7.52
109.0
103.00
8.11
119.0
99.70
8.41
123.0
96.70
8.72
128.0
90.40
9.37
138.0
45
TC
kW
SDT
121.00
7.49
106.0
118.00
7.78
111.0
112.00
8.37
120.0
109.00
8.67
125.0
105.00
8.98
130.0
98.70
9.61
139.0
50
TC
kW
SDT
130.00
7.76
108.0
128.00
8.06
113.0
121.00
8.66
122.0
118.00
8.96
127.0
115.00
9.27
131.0
107.00
9.90
140.0
38ARD024
SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 115 125
25
TC
kW
SDT
177.00
12.70
95.9
165.00
14.00
110.0
156.00
15.60
120.0
151.00
16.30
125.0
137.00
18.40
139.0
123.00
19.40
148.0
30
TC
kW
SDT
193.00
13.20
97.7
180.00
14.80
112.0
170.00
16.00
121.0
165.00
16.70
126.0
150.00
18.80
140.0
138.00
20.00
150.0
35
TC
kW
SDT
210.00
13.70
99.8
195.00
15.30
114.0
185.00
16.50
123.0
179.00
17.10
128.0
163.00
19.10
142.0
151.00
20.50
151.0
40
TC
kW
SDT
227.00
14.20
102.0
212.00
15.90
116.0
201.00
17.00
125.0
195.00
17.60
130.0
177.00
19.60
143.0
165.00
21.00
153.0
45
TC
kW
SDT
246.00
14.80
104.0
230.00
16.50
118.0
218.00
17.60
127.0
211.00
18.20
132.0
192.00
20.10
145.0
179.00
21.50
154.0
50
TC
kW
SDT
265.00
15.40
107.0
248.00
17.10
121.0
235.00
18.30
130.0
229.00
18.90
134.0
208.00
20.80
147.0
194.00
22.10
156.0
kW — Compressor Power
SDT — Saturated Discharge Temperature (F)
SST — Saturated Suction Temperature (F)
TC — Gross Cooling Capacity (1000 Btuh)
38ARD014
SST
(F)
Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25 TC
kW
SDT
120.3
7.6
109
117.1
7.93
115
110.3
8.02
122
102.0
9.88
129
96.7
10.93
138
321.1
11.38
142
30 TC
kW
SDT
126.3
7.67
110
123.1
7.98
116
116.3
8.55
123
108.6
9.97
130
102.3
11.02
138
99.6
11.48
142
35 TC
kW
SDT
132.4
7.73
111
129.0
8.02
117
122.3
9.07
124
115.2
10.05
131
107.9
11.1
138
358.5
11.58
143
40 TC
kW
SDT
145.0
7.87
113
141.6
8.15
117
134.4
9.22
124
126.9
10.23
131
119.2
11.29
140
115.8
11.80
145
45 TC
kW
SDT
159.1
8.04
115
155.0
8.48
118
142.1
9.41
126
139.2
10.43
135
130.4
11.74
142
127.7
12.135
147
50 TC
kW
SDT
172.1
8.22
117
169.4
8.66
120
161.1
9.6
127
152.6
10.61
133
142.4
12.1
142
138.5
12.415
148
38ARD016
SST
(F)
Air Temperature Entering Condenser (F)
80 85 95 100 105 115
25 TC
kW
SDT
165.1
10.21
109
160.8
10.66
113
151.4
10.78
122
140.3
13.28
129
133.2
14.69
138
129.6
15.30
142
30 TC
kW
SDT
173.3
10.30
110
168.9
10.72
114
159.7
11.49
122
149.3
13.39
130
140.8
14.80
138
137.1
15.43
142
35 TC
kW
SDT
181.6
10.38
111
177.1
10.78
115
167.9
12.19
122
158.3
13.5
131
148.4
14.91
138
144.6
15.56
143
40 TC
kW
SDT
199.0
10.57
113
194.2
10.95
117
184.5
12.39
124
174.3
13.75
131
163.9
15.17
138
543.4
15.86
144
45 TC
kW
SDT
218.2
10.8
113
212.6
11.39
118
197.2
12.64
126
191.2
14.01
135
179.3
15.78
140
175.6
16.31
146
50 TC
kW
SDT
236.0
11.04
115
232.3
11.63
120
221.1
12.9
127
209.5
14.26
133
195.7
16.25
142
190.4
16.68
148
38ARD028
SST Air Temperature Entering Condenser (F)
( F ) 80 85 95 100 115 125
28
TC 238.98
17.97
105.80
232.12 217.96 199.02 181.25 175.41
kW 18.76 18.98 23.38 26.92 27.99
SDT 111.20 118.40 125.60 137.30 141.80
30
TC 251.31
18.12
106.70
244.32 229.73 212.47 192.37 186.35
kW 18.87 20.22 23.58 27.15 28.26
SDT 111.20 118.40 125.60 137.75 141.80
35
TC 263.65
18.27
107.60
256.51 241.50 225.91 203.49 197.28
kW 18.98 21.45 23.77 27.39 28.52
SDT 111.20 118.40 125.60 138.20 141.80
40
TC 289.54
18.61
109.40
282.07 266.17 249.69 225.24 217.62
kW 19.28 21.84 24.20 27.93 29.14
SDT 113.00 120.20 122.00 135.50 143.60
45
TC 318.31
19.01
111.20
309.33 286.68 274.90 249.40 243.45
kW 20.05 22.25 24.66 28.71 29.63
SDT 114.80 122.00 131.00 141.80 147.20
50
TC 344.71
19.44
111.20
338.71 320.76 302.17 271.24 262.86
kW 20.47 22.71 25.11 29.36 30.10
SDT 116.60 123.80 129.20 142.70 149.00
11
17
Performance data 50Hz – Cont.
COMBINATION RATINGS — ENGLISH
38ARZ007/40RM007
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 57.2 58.5 63.1 68.4 61.8 61.9 65.6 70.9 65.1 65.1 67.3 72.5
80 SHC 57.20 54.50 45.40 35.80 61.80 61.80 52.30 40.00 65.10 65.10 58.50 44.00
kW 3.67 3.69 3.77 3.86 3.75 3.75 3.81 3.90 3.80 3.80 3.84 3.93
TC 56.4 57.5 62.0 67.3 60.9 61.0 64.5 69.7 64.1 64.1 66.1 71.2
85 SHC 56.40 54.00 45.00 35.40 60.90 60.90 51.90 39.60 64.10 64.10 58.00 43.60
kW 3.90 3.92 3.99 4.09 3.97 3.98 4.03 4.13 4.03 4.03 4.06 4.16
TC 54.8 55.7 59.9 65.1 59.2 59.2 62.2 67.3 62.1 62.2 63.8 68.7
95 SHC 54.80 53.00 44.20 34.60 59.20 59.20 51.00 38.80 62.10 62.20 57.00 42.80
kW 4.35 4.36 4.44 4.54 4.43 4.43 4.48 4.58 4.48 4.48 4.51 4.61
TC 54.0 54.7 58.8 63.9 58.2 58.2 61.0 66.0 61.1 61.1 62.6 67.4
100 SHC 54.00 52.50 43.70 34.10 58.20 58.20 50.50 38.40 61.10 61.10 56.50 42.40
kW 4.61 4.62 4.70 4.79 4.68 4.68 4.74 4.83 4.74 4.74 4.77 4.86
TC 53.1 53.7 57.7 62.6 57.2 57.2 59.9 64.7 60.1 60.1 61.4 66.1
105 SHC 53.10 51.90 43.30 33.70 57.20 57.20 50.00 38.00 60.10 60.10 55.90 42.00
kW 4.86 4.87 4.95 5.05 4.94 4.94 4.99 5.09 5.00 5.00 5.02 5.12
115
TC
SHC
kW
51.4
51.40
5.38
51.7
50.80
5.38
55.5
42.40
5.46
60.2
32.90
5.56
55.3
55.30
5.46
55.3
55.30
5.46
57.5
49.10
5.50
62.1
37.10
5.60
58.0
58.00
5.52
58.0
58.00
5.51
58.9
54.90
5.53
63.4
41.10
5.63
118.4
TC
SHC
kW
50.89
50.89
5.54
51.10
50.47
5.53
54.84
42.13
5.61
59.48
32.66
5.71
54.73
54.73
5.62
54.73
54.73
5.62
56.78
48.83
5.65
61.32
36.83
5.75
57.37
57.37
5.68
57.37
57.37
5.66
58.15
54.60
5.68
62.59
40.83
5.78
38ARZ007/40RM008
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2250 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 61.3 61.5 65.5 70.9 65.6 65.6 67.8 73.0 68.6 68.6 69.4 74.2
80 SHC 61.30 60.90 51.10 39.3 65.60 65.6 59.0 44.4 68.6 68.6 65.6 49.2
kW 3.74 3.74 3.81 3.90 3.81 3.81 3.85 3.94 3.86 3.86 3.88 3.96
TC 60.4 60.6 64.4 69.7 64.7 64.7 66.6 71.7 67.5 67.5 68.3 72.9
85 SHC 60.40 60.10 50.60 38.9 64.70 64.7 58.5 44.0 67.50 67.50 65.00 48.80
kW 3.96 3.97 4.03 4.13 4.04 4.04 4.07 4.16 4.09 4.09 4.10 4.19
TC 58.7 58.7 62.1 67.3 62.7 62.7 64.3 69.2 65.4 65.4 65.9 70.3
95 SHC 58.70 58.70 49.80 38.1 62.70 62.7 57.6 43.2 65.4 65.4 63.8 47.9
kW 4.42 4.42 4.48 4.58 4.49 4.49 4.52 4.62 4.55 4.54 4.55 4.64
TC 57.7 57.7 61.0 66.0 61.6 61.6 63.0 67.8 64.3 64.3 64.7 68.9
100 SHC 57.70 57.70 49.30 37.7 61.60 61.6 57.0 42.8 64.3 64.3 63.0 47.5
kW 4.67 4.68 4.74 4.84 4.75 4.75 4.78 4.87 4.80 4.80 4.81 4.89
TC 56.7 56.8 59.8 64.7 60.6 60.6 61.8 66.5 63.2 63.2 63.4 67.5
105 SHC 56.70 56.80 48.80 37.2 60.60 60.6 56.5 42.3 63.2 63.2 62.3 47.1
kW 4.93 4.93 4.99 5.09 5.01 5.01 5.03 5.13 5.06 5.06 5.06 5.15
TC 54.8 54.8 57.4 62.1 58.5 58.5 59.3 63.8 61.0 61.0 61.0 64.8
115 SHC 54.80 54.80 47.90 36.4 58.50 58.5 55.4 41.5 61.0 61.0 60.8 46.2
kW 5.44 5.44 5.50 5.61 5.53 5.52 5.54 5.64 5.58 5.58 5.57 5.66
38ARZ008/40RM007
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
1800 2400 3000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 68.3 72.6 79.0 85.7 74.9 76.8 82.9 89.6 79.4 80.0 85.5 92.1
80 SHC 68.30 61.50 52.00 42.20 74.90 70.80 59.00 46.50 79.40 78.30 65.50 50.40
kW 4.81 4.85 4.92 5.00 4.88 4.89 4.96 5.05 4.93 4.93 5.00 5.08
TC 67.4 71.4 77.7 84.3 73.8 75.5 81.5 88.1 78.2 78.7 84.0 90.5
85 SHC 67.40 60.90 51.40 41.70 73.80 70.20 58.40 46.00 78.20 77.40 64.90 49.80
kW 5.11 5.15 5.22 5.30 5.17 5.19 5.27 5.35 5.23 5.23 5.30 5.38
TC 65.4 68.9 75.0 81.5 71.6 72.9 78.7 85.1 75.9 76.1 81.0 87.4
95 SHC 65.40 59.70 50.30 40.60 71.60 68.80 57.30 44.90 75.90 75.60 63.80 48.80
kW 5.71 5.74 5.82 5.91 5.77 5.79 5.87 5.96 5.83 5.83 5.90 5.99
TC 64.4 67.6 73.6 80.0 70.4 71.6 77.1 83.5 74.6 74.7 79.4 85.7
100 SHC 64.40 59.10 49.70 40.00 70.40 68.10 56.70 44.30 74.60 74.50 63.10 48.20
kW 6.03 6.07 6.15 6.25 6.11 6.12 6.20 6.30 6.17 6.17 6.24 6.34
TC 63.3 66.2 72.2 78.5 69.2 70.2 75.6 81.9 73.3 73.3 77.8 84.1
105 SHC 63.30 58.40 49.10 39.50 69.20 67.30 56.10 43.80 73.30 73.30 62.50 47.70
kW 6.36 6.40 6.49 6.59 6.44 6.46 6.54 6.64 6.50 6.50 6.57 6.68
TC 61.2 63.6 69.3 75.5 66.8 67.4 72.4 78.7 70.7 70.6 74.5 80.7
115 SHC 61.20 57.10 47.90 38.30 66.80 65.80 54.90 42.60 70.70 70.60 61.30 46.50
kW 7.01 7.06 7.15 7.27 7.11 7.12 7.21 7.33 7.17 7.17 7.25 7.36
118.4
TC
SHC
kW
54.23
54.23
5.57
54.20
54.20
5.57
56.68
47.63
5.63
61.32
36.16
5.74
57.87
57.87
5.66
57.87
57.87
5.65
58.55
55.07
5.67
62.99
41.26
5.77
60.34
60.34
5.71
60.34
60.34
5.71
60.28
60.35
5.70
63.99
45.93
5.79
118.4
TC 60.57 62.82 68.43 74.60 66.08 66.56 71.44 77.74 69.92 69.79 73.51 79.68
SHC 60.57 56.71 47.54 37.94 66.08 65.35 54.54 42.24 69.92 69.79 60.94 46.14
kW 7.17 7.23 7.32 7.44 7.28 7 .29 7.38 7.50 7.34 7.34 7.42 7.53
12
18
38ARZ008/40RM008
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2250 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 74.1 76.4 82.5 89.1 80.2 80.6 85.7 92.3 84.3 84.3 88.0 94.4
80 SHC 74.10 69.40 57.90 45.80 80.20 79.10 66.10 50.80 84.30 84.30 73.70 55.40
kW 4.87 4.89 4.96 5.04 4.93 4.94 5.00 5.08 4.98 4.98 5.03 5.11
TC 73.0 75.1 81.1 87.6 79.0 79.3 84.3 90.8 83.1 83.0 86.4 92.8
85 SHC 73.00 68.70 57.30 45.20 79.00 78.20 65.60 50.30 83.10 83.00 73.10 54.90
kW 5.17 5.19 5.26 5.34 5.23 5.24 5.30 5.39 5.29 5.28 5.33 5.41
TC 70.9 72.6 78.3 84.8 76.6 76.7 81.4 87.8 80.5 80.5 83.4 89.6
95 SHC 70.90 67.40 56.20 44.20 76.60 76.40 64.50 49.30 80.50 80.50 71.90 53.90
kW 5.76 5.78 5.86 5.96 5.84 5.84 5.91 6.00 5.90 5.89 5.94 6.03
TC 69.7 71.2 76.8 83.2 75.3 75.4 79.8 86.1 79.2 79.1 81.8 87.8
100 SHC 69.70 66.70 55.60 43.60 75.30 75.20 63.90 48.70 79.20 79.10 71.20 53.30
kW 6.10 6.11 6.20 6.30 6.17 6.18 6.25 6.34 6.23 6.23 6.27 6.37
TC 68.6 69.8 75.3 81.6 74.0 74.1 78.2 84.4 77.8 77.7 80.1 86.1
105 SHC 68.60 66.00 55.00 43.00 74.00 74.10 63.30 48.10 77.80 77.70 70.50 52.80
kW 6.43 6.45 6.53 6.64 6.51 6.51 6.58 6.68 6.57 6.57 6.61 6.71
TC 66.3 67.1 72.3 78.4 71.5 71.4 75.0 80.9 75.0 75.0 76.9 82.6
115 SHC 66.30 64.60 53.80 41.90 71.50 71.40 62.10 46.90 75.00 75.00 69.20 51.70
kW 7.09 7.11 7.21 7.32 7.19 7.19 7.26 7.36 7.25 7.25 7.29 7.39
TC 65.61 66.29 71.40 77.44 70.75 70.59 74.04 79.85 74.16 74.19 75.94 81.55
118.4 SHC 65.61 64.18 53.44 41.57 70.75 70.59 61.74 46.54 74.16 74.19 68.81 51.37
kW 7.29 7.31 7.41 7.52 7.39 7.39 7.46 7.56 7.45 7.45 7.49 7.59
38ARZ008/40RM012
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 82.4 82.7 87.9 94.6 87.9 87.9 90.8 97.2 91.7 91.7 92.9 98.8
SHC 82.40 81.60 8.20 52.30 87.90 87.90 78.50 58.80 91.70 91.70 87.10 64.90
kW 4.96 4.96 5.03 5.11 5.03 5.03 5.06 5.14 5.07 5.07 5.09 5.16
85 TC 81.1 81.4 86.3 93.0 86.6 86.6 89.2 95.5 90.3 90.2 91.3 97.1
SHC 81.10 80.60 67.60 51.70 86.60 86.60 77.90 58.30 90.30 90.20 86.40 64.30
kW 5.26 5.26 5.33 5.42 5.33 5.33 5.37 5.45 5.38 5.38 5.39 5.47
95 TC 78.7 78.7 83.3 89.8 83.8 83.8 86.1 92.2 87.4 87.3 88.1 93.7
SHC 8.70 78.60 66.40 50.60 83.80 83.80 76.60 57.30 87.40 87.30 84.80 63.30
kW 5.87 5.87 5.93 6.03 5.94 5.94 5.98 6.07 5.99 5.99 6.01 6.09
100 TC 77.3 77.3 81.6 88.0 82.4 82.4 84.3 90.3 85.8 85.8 86.4 91.7
SHC 77.30 77.30 65.08 50.10 82.40 82.40 75.90 56.60 85.80 85.80 83.80 62.70
kW 6.21 6.21 6.27 6.37 6.28 6.28 6.32 6.41 6.34 6.34 6.35 6.43
105 TC 75.9 76.0 79.9 86.3 80.9 80.9 82.6 88.5 84.3 84.2 84.7 89.8
SHC 75.90 76.00 65.10 49.50 80.90 80.90 75.20 56.00 84.30 84.20 82.80 62.10
kW 6.54 6.55 6.61 6.71 6.62 6.63 6.66 6.75 6.68 6.68 6.69 6.77
115 TC 73.2 73.2 76.6 82.7 78.0 78.0 79.2 84.7 81.2 81.1 81.3 86.0
SHC 73.20 73.20 63.80 48.30 78.00 78.00 73.70 54.80 81.20 81.10 80.80 60.90
kW 7.22 7.22 7.28 7.40 7.31 7.31 7.34 7.43 7.37 7.37 7.37 7.46
38ARZ012/40RM008
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
2250 3000 3750
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 88.7 94.4 102.0 110.0 96.6 99.8 107.0 115.0 102.0 104.0 110.0 118.0
80 SHC 88.40 78.50 66.30 54.00 96.60 90.10 74.90 59.20 102.00 99.60 82.80 63.90
kW 6.71 6.83 7.01 7.22 6.88 6.96 7.14 7.35 7.02 7.04 7.22 7.43
TC 87.4 92.9 101.0 109.0 95.2 98.1 105.0 113.0 101.0 102.0 109.0 116.0
85 SHC 87.20 77.80 65.60 53.30 95.20 89.30 74.20 58.50 101.00 98.50 82.10 63.30
kW 7.04 7.15 7.33 7.54 7.20 7.27 7.45 7.67 7.34 7.36 7.53 7.75
TC 84.8 89.8 97.3 105.0 92.5 94.8 102.0 110.0 97.8 98.5 105.0 113.0
95 SHC 84.80 76.30 64.20 51.90 92.50 87.60 72.80 57.20 97.80 96.50 80.70 61.90
kW 7.68 7.78 7.96 8.17 7.84 7.89 8.09 8.31 7.97 7.99 8.16 8.39
TC 83.5 88.1 95.4 103.0 91.0 93.0 99.9 108.0 96.1 96.6 103.0 110.0
100 SHC 83.50 75.40 63.40 51.20 91.00 86.60 72.00 56.40 96.10 95.20 79.80 61.10
kW 8.03 8.12 8.29 8.51 8.19 8.23 8.42 8.65 8.32 8.33 8.50 8.73
TC 82.2 86.4 93.6 101.0 89.4 91.1 97.8 105.0 94.5 94.8 101.0 108.0
105 SHC 82.20 74.50 62.60 50.40 89.40 85.60 71.20 55.60 94.50 94.00 79.00 60.30
kW 8.38 8.46 8.63 8.84 8.53 8.57 8.75 8.98 8.66 8.67 8.83 9.06
TC 79.5 83.0 89.8 97.1 86.4 87.5 93.8 101.0 91.1 91.1 96.3 104.0
115 SHC 79.50 72.80 61.00 48.80 86.40 83.70 69.50 54.10 91.10 91.10 77.30 58.80
kW 9.07 9.14 9.31 9.51 9.22 9.25 9.42 9.66 9.34 9.34 9.50 9.73
118.4
TC 78.69 81.98 88.66 95.93 85.50 86.42 92.60 99.80 90.08 89.99 94.89 102.80
SHC 78.69 72.29 60.52 48.32 85.50 83.13 68.99 53.65 90.08 90.23 76.79 58.35
kW 9.24 9.31 48 9.68 9.39 9.42 9.59 9.83 9.51 9.51 9.67 9.90
13
19
Performance data 50Hz – Cont.
3
38ARZ012/40RM012
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3000 4000 5000
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 99.3 102.0 110.0 118.0 107.0 108.0 114.0 122.0 112.0 112.0 117.0 125.0
80 SHC 99.30 92.70 77.20 60.80 107.0 106.0 88.10 67.50 112.00 112.0 98.20 73.70
kW 6.94 7.01 7.21 7.43 7.13 7.15 7.31 7.54 7.27 7.27 7.39 7.60
TC 97.9 101.0 108.0 116.0 105.0 106.0 112.0 120.0 111.0 110.0 115.0 123.0
85 SHC 97.90 91.90 76.40 60.10 105.0 104.0 87.40 66.80 111.00 110.0 97.30 73.00
kW 7.26 7.33 7.52 7.75 7.45 7.46 7.63 7.85 7.59 7.59 7.70 7.92
TC 95.0 97.1 104.0 112.0 102.0 102.0 108.0 116.0 107.0 107.0 111.0 118.0
95 SHC 95.00 90.10 74.90 58.70 102.0 102.0 85.90 65.40 107.00 107.0 95.60 71.60
kW 7.90 7.95 8.15 8.39 8.09 8.09 8.26 8.49 8.23 8.23 8.34 8.57
TC 93.4 95.2 102.0 110.0 100.0 100.0 106.0 114.0 105.0 105.0 108.0 116.0
100 SHC 93.40 89.10 74.00 57.90 100.0 100.0 85.00 64.60 105.00 105.0 94.70 70.80
kW 8.25 8.29 8.48 8.72 8.43 8.43 8.59 8.83 8.57 8.57 8.67 8.90
TC 91.8 93.3 100.0 108.0 98.6 98.5 104.0 111.0 103.0 103.0 106.0 113.0
105 SHC 91.80 88.10 73.20 57.10 98.60 98.50 84.10 63.80 103.00 103.0 93.70 69.90
kW 8.59 8.63 8.81 9.05 8.78 8.77 8.93 9.16 8.91 8.91 9.00 9.23
TC 88.5 89.5 95.8 103.0 95.0 94.7 99.2 107.0 99.2 99.2 101.0 109.0
115 SHC 88.50 86.10 71.40 55.40 95.00 94.70 82.40 62.10 99.20 99.20 91.70 68.30
kW 9.28 9.30 9.47 9.71 9.46 9.44 9.59 9.83 9.59 9.58 9.66 9.90
TC 87.51 88.36 94.54 101.50 93.92 93.56 97.76 105.80 98.06 98.06 99.50 107.80
118.4 SHC 87.51 85.50 70.86 54.89 93.92 93.56 81.89 61.59 98.06 98.06 91.10 67.82
kW 9.49 9.50 9.67 9.91 9.66 9.64 9.79 10.03 9.79 9.78 9.86 10.10
38ARZ012/40RM014
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
TC 106.0 108.0 116.0 124.0 114.0 114.0 120.0 128.0 119.0 119.0 122.0 130.0
80 SHC 106.00 103.00 85.10 66.10 114.00 114.00 97.60 73.70 119.00 119.00 108.00 80.70
kW 7.12 7.16 7.36 7.59 7.32 7.32 7.46 7.70 7.45 7.45 7.53 7.76
TC 105.0 106.0 114.0 122.0 112.0 112.0 117.0 126.0 117.0 117.0 120.0 128.0
85 SHC 105.00 101.00 84.30 65.40 112.00 112.00 96.70 73.00 117.00 117.00 108.00 80.00
kW 7.43 7.47 7.67 7.91 7.63 7.63 7.78 8.02 7.77 7.77 7.85 8.08
TC 101.0 102.0 110.0 118.0 109.0 109.0 113.0 121.0 113.0 113.0 116.0 124.0
95 SHC 101.00 99.40 82.70 63.90 109.0 109.0 95.10 71.50 113.00 113.0 106.0 78.50
kW 8.07 8.10 8.30 8.55 8.27 8.27 8.41 8.66 8.42 8.41 8.48 8.72
TC 99.6 100.0 107.0 115.0 107.0 107.0 111.0 119.0 111.0 111.0 113.0 121.0
100 SHC 99.60 98.10 81.70 63.00 107.00 107.00 94.10 70.60 111.00 111.00 104.00 77.60
kW 8.41 8.43 8.63 8.88 8.61 8.61 8.74 8.99 8.75 8.75 8.81 9.06
TC 97.8 98.3 105.0 113.0 105.0 105.0 108.0 116.0 109.0 109.0 111.0 118.0
105 SHC 97.80 96.80 80.80 62.10 105.00 105.00 93.10 69.70 109.00 109.00 103.00 76.80
kW 8.75 8.77 8.96 9.21 8.95 8.95 9.07 9.32 9.09 9.09 9.14 9.39
TC 94.1 94.2 100.0 108.0 100.0 100.0 103.0 111.0 105.0 105.0 106.0 113.0
115 SHC 94.10 94.20 78.90 60.30 100.00 100.00 91.10 68.00 105.00 105.00 101.00 75.10
kW 9.42 9.43 9.61 9.87 9.63 9.63 9.73 9.98 9.77 9.77 9.80 10.10
38ARD014/40RM014
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
3750 5000 6250
Evaporator Air — Ewb (F)
62 67 72 62 67 72 62 67 72
TC 126 136 149 133 142.5 155 140 147 159
80 SHC 112 93.1 73.8 127 106.6 82.4 135 120 90.4
kW 7.68 7.73 7.81 7.71 7.762 7.84 7.77 7.78 7.87
TC 124 134 147 131 140.4 153 138 144 156
85 SHC 111 92.2 73 126 105.6 81.7 133 119 89.6
kW 8.16 8.21 8.29 8.19 8.229 8.31 8.23 8.25 8.34
TC 120 130 141 127 138.0 148 134 139 151
95 SHC 109 90.5 71.4 122 100.0 79.9 129 117 87.9
kW 9.18 9.23 9.28 9.22 9.3 9.31 9.25 9.26 9.34
TC 116 127 138 124 131.8 143 131 135 146
100 SHC 106 89.1 70.2 119 99.98 78.7 126 115 86.5
kW 9.73 9.73 9.82 9.73 9.824 9.82 9.82 9.82 9.92
TC 114 124 136 122 128.7 140 129 133 144
105 SHC 105 88.2 69.3 117 99.01 77.8 124 114 85.6
kW 10.3 10.3 10.4 10.3 10.31 10.4 10.4 10.4 10.41
TC 110 119 130 117 123.6 135 124 127 138.0
115 SHC 103 86.2 67.5 113 97.09 75.9 119 111 83.7
kW 11.5 11.6 11.6 11.6 11.57 11.7 11.6 11.6 11.67
TC 107.9 116.4 127.0 114.9 120.9 131.6 121.4 124.0 134.6
118.4 SHC 101.5 85.3 66.5 110.9 95.0 74.9 116.9 109.7 82.7
kW 12.1 12.2 12.2 12.2 12.2 12.3 12.2 12.2 12.3
TC 105 113 123 112 117.2 127 118 120 130
122 SHC 99.6 84 65.2 108 92.24 73.6 114 108 81.3
kW 12.8 12.9 12.9 12.9 12.94 13 12.9 12.9 13.03
14
20
38ARD016/40RM016
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
62 67 72 62 67 72 62 67 72
TC 177 191.5 207 187 199.4 215 195 205 221
80 SHC 149 125.1 99.9 172 135.9 111 184 160 120.8
kW 10.6 10.87 11.3 10.8 11.06 11.3 11 11.2 11.44
TC 175 188.2 204 184 196 212 193 202 217
85 SHC 148 124 98.7 170 134.9 109 182 158 119.8
kW 11.1 11.35 11.7 11.3 11.54 11.8 11.4 11.6 12.02
TC 168 181.4 197 177 192.0 204 186 194 208
95 SHC 145 120.8 96 165 131.0 107 176 155 117.7
kW 12 12.31 12.7 12.2 12.50 12.9 12.4 12.6 12.98
TC 163 175.2 191 172 182.9 197 181 187 202
100 SHC 142 119.1 94.1 162 130.2 105 172 153 114.9
kW 12.5 12.88 13.2 12.8 12.98 13.4 13 13.2 13.46
TC 159 171.8 186 169 178.5 193 176 183 197
105 SHC 141 117 92.7 159 128.2 104 168 151 113.9
kW 13.1 13.37 13.8 13.3 13.56 13.9 13.5 13.7 14.04
TC 152 163 177 161 169.6 183 169 174 187
115 SHC 137 113.9 89.5 153 125.2 100 160 148 111
kW 14.1 14.42 14.8 14.3 14.62 15 14.6 14.7 15.10
TC 148.1 159.0 172.3 156.7 165.1 177.9 164.7 168.9 182.3
118.4 SHC 134.9 112.3 88.0 149.6 123.6 98.6 156.6 145.9 109.3
kW 14.6 14.9 15.3 14.8 15.1 15.5 15.1 15.2 15.6
TC 143 153.6 166 151 159.1 171 159 162 176
122 SHC 132 110.1 85.9 145 121.5 96.7 152 143 107.0
kW 15.2 15.48 15.9 15.5 15.67 16.1 15.7 15.8 16.15
38ARD024/40RM024
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
6,000 7000 8000
Evaporator Air — Ewb (F)
62 67 72 62 67 72 62 67 72
80
TC 204.0 219.0 237.0 209.5 223.5 241.0 215.0 228.0 245.0
SHC 175.5 146.2 115.1 187.8 156.6 121.7 200.0 167.0 128.3
kW 13.9 14.4 14.9 14.1 14.5 15.1 14.2 14.7 15.2
85
TC 200.0 216.0 233.0 205.5 220.0 237.0 211.0 224.0 241.0
SHC 173.6 144.4 114.2 185.4 155.2 120.8 197.2 166.1 127.4
kW 14.5 14.9 15.5 14.6 15.1 15.6 14.8 15.2 15.8
95
TC 193.0 207.0 224.0 198.0 211.0 227.5 203.0 215.0 231.0
SHC 169.8 141.5 110.4 180.7 151.9 117.0 191.5 162.3 123.6
kW 15.7 16.2 16.7 15.8 16.3 16.9 16.0 16.4 17.0
100
TC 189.0 203.0 219.0 194.5 206.5 222.5 200.0 210.0 226.0
SHC 167.9 139.6 109.4 178.3 150.0 116.0 188.7 160.4 122.7
kW 16.3 16.8 17.4 16.5 16.9 17.5 16.6 17.0 17.6
105
TC 185.0 198.0 214.0 190.5 201.5 217.5 196.0 205.0 221.0
SHC 166.1 137.7 107.6 175.5 148.1 114.2 184.9 158.5 120.8
kW 17.0 17.4 17.9 17.1 17.5 18.1 17.3 17.7 18.2
115
TC 177.0 189.0 204.0 182.5 187.6 207.0 188.0 196.0 210.0
SHC 161.3 134.9 103.8 169.4 140.5 110.4 177.4 154.7 117.0
kW 18.3 18.8 19.2 18.5 20.0 19.4 18.7 19.0 19.5
118.4
TC 173.6 185.1 199.7 179.1 184.4 202.5 184.6 191.7 205.3
SHC 159.3 133.3 102.6 166.7 138.9 109.2 174.1 153.1 115.8
kW 18.9 19.4 19.8 19.1 20.5 20.0 19.3 19.6 20.1
122
TC 169.0 180.0 194.0 174.5 180.2 196.5 180.0 186.0 199.0
SHC 156.6 131.1 101.0 163.2 136.8 107.6 169.8 151.0 114.2
kW 19.7 20.2 20.6 19.9 21.1 20.8 20.2 20.4 20.9
38ARD028/40RM028
Temp (F) Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
7000 8,000 9,000
Evaporator Air — Ewb (F)
62 67 72 62 67 72 62 67 72
TC 273.6 291.9 314.7 276.6 293.3 315.2 282.4 296.6 318.4
80 SHC 260.5 217.3 168.9 268.7 224.3 172.3 276.3 237.6 180.6
kW 18.8 19.5 20.2 19.0 19.6 20.3 19.2 19.7 20.4
TC 268.4 287.3 309.5 271.5 288.2 310.1 277.9 291.4 313.3
85 SHC 257.2 215.3 167.6 264.9 223.0 171.1 272.5 235.7 179.3
kW 19.6 20.2 21.0 19.7 20.3 21.1 20.0 20.5 21.2
TC 258.6 275.5 297.1 261.2 276.6 297.2 267.6 279.8 300.4
95 SHC 252.4 210.8 162.3 257.3 218.0 166.0 263.6 230.6 174.2
kW 20.6 21.0 22.0 20.7 21.1 22.1 21.0 21.3 22.2
TC 254 269.7 290.6 257.3 270.2 290.8 263.1 273.4 294
100 SHC 247.4 208.1 161 253.5 215.4 164.7 259.2 228.1 173.0
kW 22.1 22.6 23.4 22.2 22.7 23.5 22.5 22.8 23.6
TC 248.8 263.1 284.0 252.2 263.7 284.3 258.0 267.0 286.9
105 SHC 243.5 205.5 158.4 248.4 212.9 162.2 254.1 225.6 170.4
kW 23.0 23.5 24.2 23.1 23.6 24.3 23.3 23.7 24.5
TC 243.1 256.4 275.7 246.7 257.2 275.6 252.0 259.8 278.2
115 SHC 239.7 192.7 153.1 243 199.3 157.1 248.2 210.8 165.3
kW 24.8 25.3 26.0 25.0 25.3 26.1 25.1 25.5 26.2
TC 239.5 252.0 270.8 243.2 252.6 270.5 248.2 255.2 273.1
118.4 SHC 237.0 191.3 152.2 239.5 196.9 156.1 244.5 209.3 164.1
kW 25.6 26.1 26.8 25.9 26.1 26.9 26.0 26.3 27.0
TC 234.7 246.1 264.3 238.5 246.5 263.7 243.2 249.1 266.4
122 SHC 233.3 189.5 151.1 234.9 193.8 154.8 239.5 207.4 162.5
kW 26.7 27.2 27.8 27.0 27.2 28.0 27.1 27.3 28.0
LEGEND
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input
SHC — Sensible Heat Capacity (kW) Gross
TC — Total Capacity (kW) Gross
15
21
Application data
Operating limits – SI (English)
Maximum Outdoor
Temperature
52 C (125 F)
Minimum Outdoor Ambient See Minimum Outdoor-Air
Operating Temperature
table below.
Minimum Return-Air
Temperature 13 C (55 F)
Maximum Return-Air
Temperature 35 C (95 F)
Normal Acceptable Saturation
Suction Temperature Range -4 to 13 C (25 to 55 F)
Maximum Discharge
Temperature 135 C (275 F)
Minimum Discharge Superheat 16 C (60 F)
NOTES:
1. Select air handler at no less than 40 L/s per kW (300 cfm/ton)
(nominal condensing unit capacity).
2. Total combined draw of the field-supplied liquid line
solenoid valve and air handler fan contactor must not exceed 22
va. If the specified va must be exceeded, use a remote relay to
control the load.
Liquid line
For applications with liquid lift greater than 6 m
(20 ft), use 1/2-in. liquid line where 3/8in. is shown;
use 5/8-in. liquid line where 1/2in. is shown. The
maximum liquid lift is 18 m (60 ft).
MAXIMUM REFRIGERANT CHARGE
UNIT 38AR R-22
lb kg
Z007 17.3 7.7
Z008 34.2 15.5
Z012 34.2 15.5
D014 (2)17.3 (2)7.7
D016 (2)34.2 (2) 15.5
D024 (2)34.2 (2) 15.5
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
UNIT 38AR
COND
TEMP
C (F)
MINIMUM OUTDOOR TEMP C (F)
Std
38ARZ007-012
38ARD014-024 32 (90) 10 (50)
LIQUID LINE DATA — 38ARD014-028 UNITS
UNIT 38AR
MAX
ALLOW.
LIFT
m(ft)
LIQUID LINE
Max Allow.
Pressure Drop
kPa (psi)
Max Allow.
Temp Loss
C(°F)
38ARZ007-012
38ARD014-02818.2 (60) 48.8 (7) 1.1 (2)
Refrigerant piping
IMPORTANT: Do not bury refrigerant piping
underground.
It is recommended that the refrigerant piping for all
commercial split systems include a liquid line
solenoid valve, a liquid line filter drier and a sight
glass.
For refrigerant lines longer than 75 lineal ft, a
liquid line solenoid valve installed at the indoor
unit and a suction accumulator are required. Refer
to the Refrigerant Specialties
Part Numbers table.
REFRIGERANT PIPING SIZES
UNIT
38AR
LINEAR LENGTH OF PIPING — M (FT)
0–7.6(0-25) 7.6–15.2(25-50) 15.2–22.4(50-75) 22.4–30.5(75-100)
Line Size (in. OD)
L S L S L S L S
Z007 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8 3/8 1 1/8
Z008 3/8 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8
Z012 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8
D014
D016 1/2 1 3/8 1/2 1 3/8 1/2 1 3/8 5/8 1 3/8
D024 1/2 1 3/8 1/2 1 3/8 5/8 1 3/8 5/8 1 3/8
LEGEND
L — Liquid Line S — Suction Line
NOTES:
1. Pipe sizes are based on a 2qF loss for liquid and
suction lines.
2. Pipe sizes are based on the maximum linear length,
shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 refrigerant in accordance with
unit installation instructions.
REFRIGERANT SPECIALTIES PART NUMBERS
UNIT
LIQUID
LINE SIZE
(in.)
LIQUID LINE
SOLENOID VALVE
(LLSV)
LLSV COIL SIGHT GLASS FILTER DRIER SUCTION LINE
ACCUMULATOR
38ARZ007 3/8 200RB5T4M AMG-24/50-60 AMI1TT3 P502-8304S S-7063S
38ARZ008 3/8 200RB5T4M AMG-24/50-60 AMI1TT3 P502-8304S S-7063S
1/2 200RB5T4M AMG-24/50-60 AMI1TT4 P502-8304S S-7063S
38ARZ012 1/2 200RB6T4M AMG-24/50-60 AMI1TT4 P502-8307S S-7063
38ARD014 1/2 200RB5T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
38ARD016 1/2 200RB5T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
5/8 200RB5T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
38ARD024 1/2 200RB6T4M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2
5/8 200RB6T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2
1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
D028 (2)27.5 (2) 12.5
38ARD028 32 (90) 15 (59)
UNIT
38AR
LINEAR LENGTH OF PIPING — M (FT)
0–4 (0-13.1 ) 4-10 (13.1-32.8 ) 10-22 (32.8-72.2) 22–30.5(72.2-100)
Line Size (in. OD)
L S L S L S L S
D028 5 /8 1 3 /8 5/8 1 5/8 5/8 1 5/8 7/8 15/8
38ARD0285/8 200RB6T5M Qty 2 AMG-24/50-60 Qty 2 AMI1TT5 Qty 2 P502-8307S* Qty 2 S-7063S Qty 2
16
22
38ARZ 400V
Typical wiring schematic
17
23
38ARD400V
Typical wiring schematic
18
38ARD ( Cont. )
Typical wiring schematic
Component Arrangement
Control Box
24
19
38ARD-028 400V
Typical wiring schematic
25
20
38ARD-028 400V ( Cont. )
Typical wiring schematic
Component Arrangement
Control Box
26
21
27
Model number nomenclature - 40RM
Quality Assurance
40RM007-034
6-25 Nominal Tons  50 Hz
40RM-016SD B5 0 1 ED
40RM Commercial Packaged
Air Handler
S: SAMCO
D: Double Skin
Voltage Designation (V-Ph-Hz)
8230-3-50
9400-3-50
Revision Number
0Original Model
Factory-Installed Options
ED
FD
Painted, Standard Motor and
Standard Drive
Painted, Standard Motor and
Medium-Static Drive (Not available
for 016-028 50 Hz units)
RD
WD
Painted, Alternate Motor and
Medium-Static Drive (Available for
50 Hz sizes 016,024,028 only)
Painted, Alternate Motor and
High-Static Drive
Packaging
1Standard Domestic
3Export
Cooling Coil
-Direct Expansion
Nominal Capacity Tons (kW)
007 6 (21) 016 15 (52)
008 7-1/2 (26) 024 20 (70)
028 25 (87)
012 10 (35)
034 30 (105)
014 12-1/2 (43)
Expansion Device
BThermostatic Expansion Valves (40RM )
22
29
40RM - ENGLISH
UNIT 40RM 007SD 008SD 012SD 014SD 016SD 024SD 028SD 034SD
NOMINAL CAPACITY (Tons) 12
1/2
7
1
/
2
6 10 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit (Double skin) with TXV 448 452 472 804 819 824 1188 1198
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8000 10,000 12,000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp (Standard Motor)*
230-3-50, 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
230-3-50, 400-3-50 1425
REFRIGERANT R-22
Operating charge (lb) 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
(approx per circuit)²
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83
No. of Splits 1 1 2 2 2 2 2 2
Split Type...Percentage - - Face...50/50
No. of Circuits per Split 12 15 9 9 12 13 15 18
Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil - Suction (ODF) 1...1
1/8
1...1
1/8
2...1
1/8
2...1
1/8
2...1
1/8
2...1
1/8
2...1
3/8
2...1
3/8
DX Coil - Liquid Refrigerant (ODF) 1...
5/8
2...
5/8
Condensate (PVC) 1...1
1/4
ODM/1 IDF
FILTERS Washable - Factory Supplied
4...16 x 20 x 1 4...20 x 24 x 1
Quantity...Size (in.) 4...16 x 24 x 1 4...16 x 24 x 1 4...20 x 25 x 1
Access Location Front
LEGEND
DX - Direct Expansion
TXV - Thermostatic Expansion Valve
*Refer to alternate Fan Motor Data table, page 49, for alternate motor data.
²Units are shipped without refrigerant charge.
Physical data (Cont.)
23
30
Options and accessories
Factory-installed options
Alternate fan motors and drives are availableto pro-
vide the widest possiblerange of performance.
Field-installed accessories
Electric resistance heat coils havean open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard. Terminal block for
single-point power connection is included.
Economizer (enthalpy contr olled) provides ventilation
air and ``free'' cooling if outside ambient temperature and
humidity are suitable.Can also be used with CO
2
sensors
to help meet indoor air quality requirements.
Discharge plenum directs the air discharge directly into
the occupiedspace;integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available un-
painted or painted. Field assemblyrequired.
Standard units available from the factory are in
Double skin.
Return-air grille provides a protective barrier over the
return-air opening and givesa finished appearanceto units
installed in the occupied space. Accessoryis availableun-
painted or painted.
Subbase provides a stable,raised platform and room for
condensatedrain trap connectionfor verticalfloor-mounted
units. Accessoryis availableunpainted or painted.
Over head suspension package includes necessarybrack-
ets to support units in horizontal ceiling installations.
CO
2
sensors can be used in conjunction with the econ-
omizer accessoryto help meet indoor air quality require-
ments. The sensor signalsthe economizer to open when
the CO
2
levelin the spaceexceedsthe setpoint. A Carrier
Comfort Systemprogrammable thermostat can be usedto
overridethe sensorif the outsideair temperatureistoo high
or too low.
Carrier's line of ther mostats provide both program-
mable and non-programmable capability with the new
Debonair line of commercial programmable thermostats,
the TEMP System controls offer communication capabil-
ity with stagedheatingandcooling, the Commercial Elec-
tronic thermostats provide 7-day programmablecapability
for economicalapplications,while the Non-Programmable
thermostatsoffer a multitude of stagedheating and cooling
subbaseoptions.
Condensate drain trap includesan overflow shutoff switch
that can be wired to turn off the unit if the trap becomes
plugged. Kit also includesa wire harnessthat can be con-
nected to an alarm if desired. The transparent trap is de-
signedfor easyserviceand maintenance.
24
31
CARRIER THERMOSTATS
DEBONAIR COMMERCIAL PROGRAMMABLE
THERMOSTAT
AUTO
Pm
COOL
HEAT
®
TEMP SYSTEM THERMOSTAT
COMMERCIAL ELECTRONIC
THERMOSTAT
NON-PROGRAMMABLE THERMOSTAT
H
C
Options and accessories (cont)
25
32
40RM WITH DISCHARGE PLENUM,
RETURN-AIR GRILLE AND SUBBASE
DISCHARGE
PLENUM
RETURN-AIR
GRILLE
SUBBASE
FAN
COIL
UNIT
40RM WITH ECONOMIZER
ECONOMIZER
40RM WITH CONDENSATE TRAP
26
33
Dimensions
40RM007SD-012SD
UNIT WEIGHT
UNIT lb (kg)
40RM007SD 448 (203)
40RM008SD 452 (205)
40RM012SD 472 (214)
TXV - Thermostatic Expansion
Valve
NOTES:
1. Dimensions in [ ] are in
millimeters.
2. Direction of air¯ow.
3. Recommended clearance:
· Rear: 39(76.2mm)(28-69[762mm]
with electric heat accessory)
· Front: 28-69(762 mm)
· Right side: 28-69(762 mm)
· Left Side: 28-69(762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied and
field installed.
All the above mentioned weights
are for double skin units.
27
34
Dimensions (cont)
40RM014SD-024SD
UNIT UNITWEIGHT
lb (kg)
40RM014SD 804 (364)
40RM016SD 819 (371)
40RM024SD 824 (373)
TXV - Thermostatic Expansion
Valve
NOTES:
1. Dimensions in [ ] are in
millimeters.
2. Direction of airflow.
3. Recommended clearance:
· Rear: 39 (76.2 mm) (28-69
[762 mm] with electric heat
accessory)
· Front: 28-69(762 mm)
· Right side: 28-69(762 mm)
· Left Side: 28-69(762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
All the weights men-
tioned in the table
are for double skin
units.
UNIT
28
35
40RM028SD,034SD
TXV - Thermostatic Expansion
Valve
NOTES:
1. Dimensions in [ ] are in
millimeters.
2. Direction of airflow.
3. Recommended clearance:
· Rear: 39(76.2 mm)
· Front: 28-69(762 mm)
· Right side: 28-69(762 mm)
· Left Side: 28-69(762 mm)
· Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by
Carrier.
5. Duct flange is factory supplied
and field installed.
UNIT WEIGHT
UNIT lb (kg)
40RM028SD 1188 (538)
40RM034SD 1198 (542)
All the above mentioned weights are for
double skin units.
Dimensions (cont)
29
36
OVERHEAD SUSPENSION ACCESSORY
UNIT SIZES 007-012
UNIT SIZES 014-024
UNIT SIZES 028,034
NOTE: Dimensions in [ ] are millimeters.
30
37
PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES
UNIT SIZES 007-012
UNIT SIZES 014-024
NOTE: Dimensions in [ ] are millimeters.
Dimensions (cont)
31
38
PLENUM, RETURN-AIR GRILLE, AND SUBBASE ACCESSORIES (cont)
UNIT SIZES 028,034
NOTE: Dimensions in [ ] are millimeters.
32
39
ECONOMIZER ACCESSORY
UNIT SIZES 007-012
UNIT SIZES 014-024
UNIT SIZES 028,034
NOTES:
1. For horizontal unit applications, economizer can be attached to end of unit opposite duct connections.
2. Dimensions in [ ] are millimeters.
Dimensions (cont)
33
40
ELECTRIC HEAT ACCESSORY
UNIT SIZES 007-012
UNIT SIZES 014-034
UNIT SIZE A B C D E F G H J
014-024 1-3
1
4
[387.4]
4-6
3
8
[1381.1]
2
5
16
[58.7]
2-1
1
4
[641.4]
10
5
8
[269.9]
1-4
[406.4]
1-4
5
16
[414.3]
1-6
3
4
[476.3]
1-
7
8
[327.0]
028,034 1-3
3
8
[390.5]
5-4
7
16
[1636.8]
2
1
16
[26.9]
2-6
3
16
[766.8]
1-
1
4
[311.2]
1-7
[482.6]
1-4
5
16
[414.0]
1-10
[558.8]
1-4
7
16
[417.1]
NOTE: Dimensions in [ ] are millimeters.
34
44
FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — 50 HZ, ENGLISH
UNIT AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
40RM
007
1,800
2,100
2,400
2,700
3,000
320
373
427
480
533
0.22
0.31
0.42
0.54
0.69
442
483
526
570
616
0.32
0.42
0.53
0.67
0.82
534
569
606
646
687
0.42
0.53
0.64
0.78
0.94
611
642
676
712
750
0.52
0.63
0.75
0.89
1.05
678
708
739
773
808
0.61
0.73
0.86
1.00
1.16
739
767
796
828
862
0.70
0.82
0.96
1.11
1.28
795
821
849
880
912
0.80
0.92
1.06
1.21
1.39
40RM
008
2,250
2,600
3,000
3,400
3,750
359
415
478
542
598
0.32
0.45
0.62
0.82
1.03
472
516
569
624
673
0.44
0.57
0.75
0.95
1.17
560
599
645
695
740
0.55
0.68
0.86
1.08
1.29
634
669
712
758
800
0.65
0.79
0.98
1.20
1.42
700
732
773
815
855
0.75
0.90
1.09
1.31
1.60
759
790
828
869
906
0.86
1.01
1.20
1.43
1.66
814
843
879
918
954
0.96
1.11
1.32
1.55
1.78
40RM
012
3,000
3,500
4,000
4,500
5,000
444
518
592
666
740
0.58
0.82
1.11
1.44
1.83
541
604
669
735
803
0.71
0.95
1.25
1.59
1.98
621
677
736
797
861
0.83
1.08
1.38
1.72
2.12
691
742
797
854
914
0.94
1.20
1.51
1.86
2.26
753
801
853
907
964
1.05
1.32
1.63
1.99
2.39
809
855
904
956
1010
1.17
1.44
1.75
2.12
2.53
862
906
953
1003
1055
1.28
1.56
1.88
2.24
2.66
40RM
014
3,750
4,300
5,000
5,700
6,250
363
416
484
552
605
0.37
0.53
0.81
1.17
1.51
475
517
573
631
678
0.58
0.78
1.08
1.47
1.83
566
601
650
702
744
0.80
1.02
1.35
1.76
2.15
645
676
719
766
805
1.02
1.26
1.62
2.06
2.47
715
743
782
826
862
1.24
1.50
1.89
2.36
2.79
779
805
841
881
915
1.47
1.74
2.16
2.66
3.11
839
862
896
934
966
1.69
1.99
2.44
2.96
3.43
40RM
016
4,500
5,300
6,000
6,800
7,500
391
460
521
590
651
0.51
0.80
1.13
1.60
2.10
495
551
602
663
718
0.75
1.08
1.43
1.93
2.45
581
629
675
730
779
1.00
1.35
1.73
2.26
2.81
657
700
741
791
837
1.25
1.63
2.04
2.59
3.16
725
764
801
847
890
1.50
1.91
2.34
2.92
3.52
787
823
858
901
941
1.76
2.20
2.65
3.26
3.88
845
878
911
951
990
2.02
2.48
2.96
3.60
4.24
40RM
024
6,000
7,000
8,000
9,000
10,000
503
586
670
754
838
1.07
1.64
2.37
3.28
4.39
587
660
735
812
891
1.37
1.98
2.74
3.69
4.83
661
726
795
867
941
1.67
2.31
3.12
4.09
5.27
727
787
851
918
988
1.97
2.65
3.49
4.50
5.70
789
844
904
967
1034
2.28
2.99
3.86
4.90
6.14
846
898
954
1014
1077
2.59
3.33
4.23
5.31
6.85
900
948
1001
1059
1120
2.90
3.67
4.61
5.72
7.02
40RM
028
7,500
8,750
10,000
11,250
12,500
412
481
549
618
687
1.15
1.76
2.55
3.52
4.71
492
550
610
672
735
1.53
2.17
2.99
4.00
5.22
568
616
669
725
783
2.00
2.66
3.50
4.53
5.78
640
680
726
777
830
2.56
3.22
4.07
5.12
6.38
710
742
782
827
876
3.22
3.86
4.70
5.76
7.04
776
802
836
876
922
3.98
4.58
5.40
6.45
7.74
840
860
889
925
966
4.83
5.38
6.17
7.21
8.49
40RM
034
9,000
10,500
12,000
13,500
15,000
471
550
628
707
785
1.78
2.72
3.93
5.44
7.27
539
608
679
752
826
2.17
3.15
4.40
5.94
7.81
604
665
730
797
867
2.63
3.64
4.92
6.49
8.39
667
720
779
841
907
3.17
4.18
5.48
7.08
9.01
728
774
827
885
947
3.78
4.79
6.09
7.71
9.66
788
827
874
928
986
4.46
5.45
6.76
8.38
10.35
845
878
921
970
1024
5.22
6.18
7.47
9.10
11.07
See Legend and Notes on page 47.
35
45
FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — 50 Hz, ENGLISH
UNIT AIRFLOW
(Cfm) 1.4
Rpm Bhp
1.6
Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
1.8 2.0 2.2
Rpm Bhp Rpm Bhp Rpm Bhp
2.4
Rpm Bhp
1,800 847 0.89 896 0.98 942 1.07 986 1.16 1027 1.25
40RM
007
2,100
2,400
2,700
872
899
928
1.02
1.16
1.32
920
946
974
1.11
1.26
1.42
965
990
1018
1.21
1.36
1.52
1008
1033
1059
1.30
1.46
1.63
1050
1073
1099
1.40
1.55
1.73
3,000 959 1.49 1004 1.60 1046 1.71
1087 1.81 1126 1.92
— —
40RM
008
2,250
2,600
3,000
3,400
865
893
928
965
1.06
1.22
1.43
1.66
913
940
973
1010
1.16
1.33
1.54
1.78
958
984
1017
1052
1.27
1.43
1.65
1.89
1001
1027
1058
1092
1.37
1.54
1.76
2.00
1042
1067
1098
1131
1.47
1.65
1.87
2.12
3,750 1000 1.90 1043 2.02 1084 2.13 1124 2.25
1162 2.37
— —
3,000 911 1.39 958 1.50 1002 1.61 1044 1.72 1084 1.83 1123 1.94
40RM
012
3,500
4,000
4,500
953
999
1047
1.67
2.00
2.37
998
1042
1089
1.79
2.12
2.50
1041
1084
1129
1.90
2.24
2.62
1082
1124
1168
2.02
2.36
2.74
1122
1162
2.13
2.48
1159
1199
2.25
2.60
5,000 1097 2.79 1138 2.92 1177 3.05 — — — — — —
3,750 894 1.91 947 2.14 996 2.37 1044 2.60
1089 2.83
— —
40RM
014
4,300
5,000
5,700
916
948
984
2.23
2.71
3.25
967
997
1031
2.48
2.98
3.55
1016
1044
1076
2.73
3.26
3.86
1062
1089
1120
2.98
3.53
4.16
1107
1133
1162
3.24
3.81
4.46
6,250 1014 3.75
1060 4.07 1104 4.39
1147 4.71 1188 5.03
4,500 899 2.29 951 2.56 999 2.84
1046 3.12 1091 3.41 1133 3.70
40RM
016
5,300
6,000
6,800
930
961
999
2.78
3.28
3.94
980
1009
1045
3.08
3.60
4.28
1027
1055
1089
3.38
3.92
4.63
1072
1098
1132
3.68
4.24
4.98
1116
1141
1173
3.99
4.57
5.33
1157
1181
4.30
4.91
7,500 1036 4.60 1080 4.97 1123 5.34 1164 5.71 ————
6,000 950 3.21 999 3.53 1045 3.85 1089 4.17
1131 4.50 1172 4.83
40RM
024
7,000
8,000
9,000
996
1047
1102
4.02
4.99
6.13
1042
1091
1143
4.37
5.37
6.54
1086
1133
1183
4.72
5.75
6.96
1129
1173
5.07
6.13
1169
5.43
10,000 1160 7.46 1200 7.91 — — — — — — — —
7,500 903 5.79
963 6.83 1021 7.98 1078 9.21
————
40RM
028
8,750
10,000
11,250
917
941
972
6.26
7.01
8.02
972
991
1019
7.22
7.91
8.89
1025
1040
1064
8.26
8.89
9.83
1078
1089
9.38
9.93
12,500
1010 9.29
1053 10.15 1095 11.05 — — — — — —
9,000
901 6.07 955 6.98 1008 7.98 1060 9.05
————
40RM
034
10,500
12,000
13,500
928
966
1011
6.98
8.24
9.86
978
1011
1052
7.84
9.07
10.67
1026
1055
1092
8.76
9.95
11.52
1073
1098
9.74
10.88
15,000 1062 11.84 —————————
See Legend and Notes on page 47.
Performance data (cont)
36
46
LEGEND FACTOR Y-SUPPLIED FILTER PRESSURE DROP
Bhp - Brake Horsepower Input to Fan - ENGLISH
ESP - External Static Pressure
Bold
indicates field supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables, pages 57-59, to complete selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 1-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. For 50 Hz units, the medium- static drive and standard motor
combination is not available for 016-028 sizes. Use alternate
motor if medium-static drive is required for these sizes.
UNIT AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
40RM
007
1,800
2,400
3,000
0.05
0.08
0.11
40RM
008
2,250
3,000
3,750
0.07
0.11
0.15
40RM
012
3,000
4,000
5,000
0.11
0.17
0.23
40RM
014
3,750
5,000
6,250
0.06
0.10
0.13
40RM
016
4,500
6,000
7,500
0.08
0.12
0.17
40RM
024
6,000
8,000
10,000
0.12
0.19
0.26
40RM
028
7,500
10,000
12,500
0.15
0.22
0.30
40RM
034
9,000
12,000
15,000
0.19
0.29
0.40
ACCESSORY PLENUM AIR THROW DATA — ENGLISH
(Ft)
UNIT AIRFLOW
(Cfm)
VANE DEFLECTION
Straight 21
1
2
° 45°
40RM
007 2,400 39 33 24
40RM
008 3,000 45 38 28
40RM
012 4,000 55 46 33
40RM
014 5,000 45 38 28
40RM
016 6,000 50 43 31
40RM
024 8,000 60 51 37
40RM
028 10,000 76 65 47
40RM
034 12,000 85 72 52
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use
the following multipliers to determine throw values for other terminal
velocities.
TERMINAL VELOCITY
(Fpm) THROW FACTOR
50 X 1.50
100 X 0.75
150 X 0.50
37
47
ACCESSORY PRESSURE DROP — SI
(Pa)
UNIT AIRFLOW
(L/s)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
HEATING COILS ECONOMIZER
Hot Water Steam Electric
40RM
007
850
1150
1450
15
25
36
2
3
5
25
41
60
25
41
60
9
16
26
12
18
23
40RM
008
1000
1400
1800
20
34
51
2
5
8
33
57
85
33
57
85
12
24
39
13
22
39
40RM
012
1450
1900
2350
36
56
79
5
10
15
60
93
132
60
93
132
26
43
65
23
43
69
40RM 1750 18 2 26 26 10 12
2350 29 5 43 43 17 17
014 2950 43 5 62 62 26 27
40RM
016
2100
2800
3500
24
39
56
2
5
7
36
57
82
36
57
82
14
24
37
15
22
37
40RM 2900 41 5 60 60 26 23
3800 64 10 93 93 43 43
024 4700 91 15 132 132 65 69
40RM 3500 37 5 67 67 22 15
4700 59 7 109 109 39 22
028 5900 86 12 157 157 60 35
40RM 4250 50 7 92 92 32 20
5650 80 12 147 147 56 35
034 7050 114 17 210 210 85 52
ACCESSORY PRESSURE DROP — ENGLISH
(in. wg)
UNIT AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
HEATING COILS ECONOMIZER
Hot Water Steam Electric
40RM
007
1,800
2,400
3,000
0.06
0.10
0.14
0.01
0.01
0.02
0.10
0.16
0.23
0.10
0.16
0.23
0.04
0.06
0.10
0.05
0.07
0.09
40RM
008
2,250
3,000
3,750
0.09
0.14
0.21
0.01
0.02
0.03
0.15
0.23
0.35
0.15
0.23
0.35
0.06
0.10
0.15
0.06
0.09
0.15
40RM
012
3,000
4,000
5,000
0.14
0.22
0.32
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
40RM
014
3,750
5,000
6,250
0.07
0.12
0.17
0.01
0.02
0.02
0.11
0.17
0.25
0.11
0.17
0.25
0.04
0.07
0.11
0.05
0.07
0.11
40RM
016
4,500
6,000
7,500
0.10
0.16
0.23
0.01
0.02
0.03
0.15
0.23
0.33
0.15
0.23
0.33
0.06
0.10
0.15
0.06
0.09
0.15
40RM
024
6,000
8,000
10,000
0.16
0.26
0.37
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
40RM
028
7,500
10,000
12,500
0.15
0.24
0.34
0.02
0.03
0.05
0.28
0.44
0.63
0.28
0.44
0.63
0.09
0.16
0.24
0.06
0.09
0.14
40RM
034
9,000
12,000
15,000
0.20
0.32
0.46
0.03
0.05
0.07
0.37
0.59
0.85
0.37
0.59
0.85
0.13
0.22
0.34
0.08
0.14
0.21
Performance data (cont)
38
48
ALTERNATE MOTORS
UNIT V*-PH-Hz VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit
Amps
MOCP
40RM
007
230-3-50 207-253 2.4 (1.79) 5.2 6.5 15
400-3-50 360-440 2.4 (1.79) 2.6 3.3 15
40RM
008
230-3-50 207-253 2.9 (2.16) 7.5 9.4 15
400-3-50 360-440 2.9 (2.16) 3.4 4.3 15
40RM
012
230-3-50 207-253 5.0 (3.73) 15.2 19.0 30
400-3-50 360-440 5.0 (3.73) 7.6 9.5 15
40RM
014
230-3-50 207-253 5.0 (3.73) 15.2 19.0 30
400-3-50 360-440 5.0 (3.73) 7.6 9.5 15
40RM
016
230-3-50 207-253 5.0 (3.73) 15.2 19.0 30
400-3-50 360-440 5.0 (3.73) 7.6 9.5 15
40RM
024
230-3-50 207-253 7.5 (5.59) 22.8 28.5 50
400-3-50 360-440 7.5 (5.59) 11.4 14.3 25
40RM
028
230-3-50 207-253 10.0 (7.46) 32.2 40.3 60
400-3-50 360-440 10.0 (7.46) 16.1 20.1 30
LEGEND
FLA Full Load Amps
MOCP — Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages
shown. Voltages should not exceed the limits shown in the Voltage Limits column.
NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accordance
with NEC (National Electrical Code) (U.S.A. standard), Article 440.
2. Motor FLA values are established in accordance with UL (Underwriters’ Labo-
ratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v 393 + 403 + 396
Average Voltage = 3
1192
=3
= 397
Determine maximum deviation from average voltage.
(AB) 397 − 393 = 4 v
(BC) 403 − 397 = 6 v
(AC) 397 − 396 = 1 v
Maximum deviation is 6 v.
Determine percent voltage imbalance.
6
% Voltage Imbalance = 100 x 397
= 1.5%
This amount of phase imbalance is satisfactory because it is below the maxi-
mum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.
STANDARD MOTORS
UNIT V*-PH-Hz VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit
Amps
MOCP
40RM
007
230-3-50 207-253 2.4 (1.79) 5.2 6.5 15
400-3-50 360-440 2.4 (1.79) 2.6 3.3 15
40RM
008
230-3-50 207-253 2.4 (1.79) 5.2 6.5 15
400-3-50 360-440 2.4 (1.79) 2.6 3.3 15
40RM
012
230-3-50 207-253 2.9 (2.16) 7.5 9.4 15
400-3-50 360-440 2.9 (2.16) 3.4 4.3 15
40RM
014
230-3-50 207-253 2.9 (2.16) 7.5 9.4 15
400-3-50 360-440 2.9 (2.16) 3.4 4.3 15
40RM
016
230-3-50 207-253 2.9 (2.16) 7.5 9.4 15
400-3-50 360-440 2.9 (2.16) 3.4 4.3 15
40RM
024
230-3-50 207-253 5.0 (3.73) 15.2 19.0 30
400-3-50 360-440 5.0 (3.73) 7.6 9.5 15
40RM
028
230-3-50 207-253 7.5 (5.59) 22.8 28.5 50
400-3-50 360-440 7.5 (5.59) 11.4 14.3 25
40RM
034 230-3-50 207-253 10.0 (7.46) 32.2 40.3 70
400-3-50 360-440 10.0 (7.46) 16.1 20.1 30
.
Electrical data
39
49
Electrical data (cont)
ELECTRIC HEATER DATA
HEATER
PART NO. UNIT V-PH-Hz FAN MOTOR ELECTRIC HEATER(S)
MCA* MOCP*
Nominal Actual Capacity (kW) FLA
Hp kW FLA Capacity (kW) Stage 1 Stage 2 Total
CAELHEAT001A00
2.4 1.79 5.2 5 5.0 5.0 12.0 21.5 25
240-3-50 2.9 2.16 7.5 5 5.0 5.0 12.0 24.4 25
5.0 3.73 15.2 5 5.0 5.0 12.0 34.0 40
CAELHEAT002A00
2.4 1.79 2.6 5 3.5 3.5 5.00 9.5 15
400-3-50 2.9 2.16 3.4 5 3.5 3.5 5.00 10.5 15
5.0 3.73 7.6 5 3.5 3.5 5.00 15.8 20
CAELHEAT004A00
40RM007-012 240-3-50
2.4
2.9
5.0
1.79
2.16
3.73
5.2
7.5
15.2
10
10
10
10.0
10.0
10.0
10.0
10.0
10.0
24.1
24.1
24.1
36.6
39.4
49.1
40
40
50
CAELHEAT005A00
2.4 1.79 2.6 10 6.9 6.9 10.0 15.8 20
400-3-50 2.9 2.16 3.4 10 6.9 6.9 10.0 16.8 20
5.0 3.73 7.6 10 6.9 6.9 10.0 22.0 25
CAELHEAT007A00 2.4 1.79 5.2 15 15.0 15.0 36.1 51.6 60
240-3-50 2.9 2.16 7.5 15 15.0 15.0 36.1 54.5 60
5.0 3.73 15.2 15 15.0 15.0 36.1 64.1 70
CAELHEAT008A00 2.4 1.79 2.6 15 10.4 10.4 15.0 22.0 25
400-3-50 2.9 2.16 3.4 15 10.4 10.4 15.0 23.0 25
5.0 3.73 7.6 15 10.4 10.4 15.0 28.3 30
CAELHEAT010A00 240-3-50
2.4
2.9
5.0
1.79
2.16
3.73
5.2
7.5
15.2
25
25
25
15.0
15.0
15.0
10.0
10.0
10.0
25.0
25.0
25.0
60.1
60.1
60.1
81.7
84.6
94.2
90
90
100
CAELHEAT011A00 2.4 1.79 2.6 25 10.4 6.9 17.4 25.1 34.6 25
400-3-50 2.9 2.16 3.4 25 10.4 6.9 17.4 25.1 35.6 40
5.0 3.73 7.6 25 10.4 6.9 17.4 25.1 40.8 50
CAELHEAT013A00
40RM008,012
240-3-50
2.4
2.9
5.0
1.79
2.16
3.73
5.2
7.5
15.2
35
35
35
20.0
20.0
20.0
15.0
15.0
15.0
35.0
35.0
35.0
84.2
84.2
84.2
111.7
114.6
124.2
125
125
125
CAELHEAT014A00 2.4 1.79 2.6 35 13.9 10.4 24.3 35.1 47.1 50
400-3-50 2.9 2.16 3.4 35 13.9 10.4 24.3 35.1 48.1 50
5.0 3.73 7.6 35 13.9 10.4 24.3 35.1 53.4 60
CAELHEAT016A00
2.9 2.16 7.5 10 10.0 10.0 24.1 39.4 40
240-3-50 5.0 3.73 15.2 10 10.0 10.0 24.1 49.1 50
7.5 5.59 22.8 10 10.0 10.0 24.1 58.6 70
CAELHEAT017A00 2.9 2.16 3.4 10 6.9 6.9 10.0 16.8 20
400-3-50 5.0 3.73 7.6 10 6.9 6.9 10.0 22.0 25
7.5 5.59 11.4 10 6.9 6.9 10.0 26.8 35
CAELHEAT019A00 40RM014-024 240-3-50
2.9
5.0
7.5
2.16
3.73
5.59
7.5
15.2
22.8
20
20
20
20.0
20.0
20.0
20.0
20.0
20.0
48.1
48.1
48.1
69.5
79.1
86.4
70
80
90
CAELHEAT020A00 2.9 2.16 3.4 20 13.9 13.9 20.0 29.3 30
400-3-50 5.0 3.73 7.6 20 13.9 13.9 20.0 45.1 50
7.5 5.59 11.4 20 13.9 13.9 20.0 49.2 50
CAELHEAT022A00 2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100
240-3-50 5.0 3.73 15.2 30 20.0 10.0 30.0 72.2 109.2 110
7.5 5.59 22.8 30 20.0 10.0 30.0 72.2 118.7 125
CAELHEAT023A00 2.9 2.16 3.4 30 13.9 6.9 20.8 30.1 41.8 50
400-3-50 5.0 3.73 7.6 30 13.9 7.9 20.8 30.1 47.1 50
7.5 5.59 11.4 30 13.9 7.9 20.8 30.1 51.8 60
CAELHEAT025A00 2.9 2.16 7.5 50 30.0 20.0 50.0 120.3 159.7 175
40RM016,024
240-3-50 5.0
7.5
3.73
5.59
15.2
22.8
50
50
30.0
30.0
20.0
20.0
50.0
50.0
120.3
120.3
169.4
178.9
175
200
CAELHEAT026A00
2.9 2.16 3.4 50 20.8 13.9 34.7 50.1 66.9 70
400-3-50 5.0 3.73 7.6 50 20.8 13.9 34.7 50.1 72.1 80
7.5 5.59 11.4 50 20.8 13.9 34.7 50.1 76.9 80
CAELHEAT028A00 240-3-50 7.5
10.0
5.59
7.46
22.8
32.2
20
20
20.0
20.0
20.0
20.0
48.1
48.1
88.6
100.4
90
110
CAELHEAT029A00 400-3-50 7.5
10.0
5.59
7.46
11.4
16.1
20
20
13.9
13.9
13.9
13.9
20.0
20.0
39.3
45.2
40
50
40RM028,034
CAELHEAT031A00 240-3-50 7.5
10.0
5.59
7.46
22.8
32.2
40
40
20.0
20.0
20.0
20.0
40.0
40.0
96.2
96.2
148.8
160.5
150
175
CAELHEAT032A00 400-3-50 7.5
10.0
5.59
7.46
11.4
16.1
40
40
13.9
13.9
13.9
13.9
27.8
27.8
40.1
40.1
64.4
70.2
70
80
CAELHEAT034A00 240-3-50 7.5
10.0
5.59
7.46
22.8
32.2
50
50
30.0
30.0
20.0
20.0
50.0
50.0
120.3
120.3
178.9
190.6
200
200
CAELHEAT035A00 400-3-50 7.5
10.0
5.59
7.46
11.4
16.1
50
50
20.8
20.8
13.9
13.9
34.7
34.7
50.1
50.1
76.9
82.8
80
90
CAELHEAT037A00 240-3-50 7.5
10.0
5.59
7.46
22.8
32.2
70
70
40.0
40.0
30.0
30.0
70.0
70.0
168.4
168.4
196.9
208.6
200
225
CAELHEAT038A00 400-3-50 7.5
10.0
5.59
7.46
11.4
16.1
70
70
27.8
27.8
20.8
20.8
48.6
48.6
70.2
70.2
84.4
90.3
90
100
40
50
LEGEND
FLA Full Load Amps
Hp Horsepower
MCA Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (Amps)
*Values shown are for single-point connection of electric heat accessory and air
handler.
†Single-phase motors. All other motors are 3-phase.
NOTES:
1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To determine
heater capacity (kW) at unit nameplate multiply the 240-v, 480-v, or 575-v ca-
pacity (kW) by the factor shown in the table below for the unit voltage.
2. The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.
3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total external static
pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-supplied
motors.
HEATER
RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1 — — — — —
480 — — 0.694 0.84 0.918 1 — — —
575 — — — — — 0.915 1 1.089
41
51
Typical piping and wiring
VERTICAL INSTALLA TION - 40RM (TYPICAL)
LEGEND NOTES:
NEC - National Electrical Code 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
TXV - Thermostatic Expansion Valve Manual for details.
2. All wiring must comply with the applicable local and national codes.
Piping 3. Wiring and piping shown are general points-of-connection guides only and are not intended
*Field supplied. for, or to include all details for, a specific installation.
²Double riser may be required. Consult con- 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
densing unit product data catalog for migration to the compressor.
details. 5. Internal factory-supplied TXVs not shown.
42
52
HORIZONT AL INSTALLA TION - 40RM (TYPICAL)
LEGEND 2. All wiring must comply with the applicable local and national codes.
NEC - National Electrical Code 3. Wiring and piping shown are general points-of-connection guides
TXV - Thermostatic Expansion Valve only and are not intended for, or to include all details for, a spe-
cific installation.
*Accessory item. 4. Liquid line solenoid valve (solenoid drop control) is recommended
²Field supplied. to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
NOTES:
1. All piping must follow standard refrigerant piping techniqes. Refer
to Carrier System Design Manual for details.
43
53
WIRE ROUTING, BASE UNIT - 40RM,
WIRE ROUTING, UNIT WITH ELECTRIC HEAT - 40RM,
NEC - National Electrical Code
Typical piping and wiring (cont)
44
54
CONTROL WIRING SCHEMA TIC - TYPICAL
EQUIP
GND
HC
HTR
IFC
IFM
TB
LEGEND
-Equipment
-Ground
-Heater Contactor
-Heater Element
-Indoor Fan Contactor
-Indoor Fan Motor
-Terminal Block
Factory Wiring
Field Wiring
Application data
Operating limits The air handler fan must alwaysbe operating when the
Maximum fan speed-
40RM007-024
condensingunit is operating.
........... . . . . . 1200 rpm (20 r/s) Ductwork should be sized according to unit size, not
building load. For larger units with two fans, a split duct
40RM028,034 . . . . . . . . . . . . . . . . 1100 rpm (18.3 r/s) transition is recommendedat the fan outlets, but a plenum
General can be usedwith slight reduction in external static pressure
capability.
Selectequipment to match or to be slightly lessthan peak For variable air volume (VAV) systemswith supply-to-
load. This providesbetter humidity control, lessunit cycling,
and lesspart-load operation. Equipment shouldbe selected return air recycling,usethe equipment room asa return air
to perform at no lessthan 300 cfm/ton (40 L/s per kW). plenum.
FACTOR Y-INSTALLED NOZZLE AND DISTRIBUTOR DATA
UNIT TXV
Qty...Part No.*
DISTRIBUTOR
Qty...Part No.*
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
NOZZLE
Qty...Part No.
40RM007 1...XVE-5 1...1116 12...
1/4
1...E5
40RM008 1...SVE-8 1...1126 15...
1/4
1...C6
40RM012 2...XVE-4 2...1115 9...
1/4
2...E4
40RM014 2...XVE-5 2...1115 9...
1/4
2...E5
40RM016 2...XVE-8 2...1116 12...
1/4
2...E6
40RM024 2...XVE-10 2...1116 13...
1/4
2...E8
40RM028 2...SVE-15 2...1126 15...
1/4
2...C10
40RM034 2...SVE-15 2...1126 18...
1/4
2...C12
*Sporlan Valve Co. part numbers shown.
45
55
FAN MOTOR DATA - SI
40RM 40RM 40RM
40RM 40RM 40RM 40RM
40RM
UNIT 007 008 012 016
014 024 028 034
STANDARD MOTOR (230-3-50 and 400-3-50)
Speed (r/s) 23.75 23.75 23.75 23.75 23.75 23.75 23.75 23.75
Shaft kW 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (mm) 15.9 15.9 22.2 22.2 22.2 28.6 34.9 34.9
40RM 40RM 40RM
40RM 40RM 40RM
40RM
UNIT 007 008 012 016
014 024 028
ALTERNATE MOTOR (230-3-50 and 400-3-50)
Speed (r/s) 23.75 23.75 23.75 23.75 23.75 23.75 23.75
Shaft kW 1.79 2.16 3.73 3.73 3.73 5.60 7.46
Frame (NEMA) 56Y 56Y S184T S184T S184T S213T S215T
Shaft Dia (mm) 22.2 22.2 22.2 28.6 28.6 34.9 34.9
NEMA - National Electrical Manufacturers Association (U.S.A.)
Application data (cont)
FAN MOTOR DATA -ENGLISH
UNIT 40RM
007
40RM
008 40RM
012
40RM
014
40RM
016 40RM
024 40RM
028 40RM
034
STANDARD MOTOR (230-3-50 and 400-3-50)
Speed (rpm) 1425 1425 1425 1425 1425 1425 1425 1425
Hp 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y 184T S213T S215T
Shaft Dia (in.)
5/8 5/8 7/8 7/8 7/8
1
1/8
1
3/8
1
3/8
ALTERNATE MOTOR (230-3-50 and 400-3-50)
Speed (rpm) 1425 1425 1425 1425 1425 1425 1425
Hp 2.4 2.9 5.0 5.0 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y S184T S184T S184T S213T S215T
Shaft Dia (in.)
7/8 7/8 7/8
1
1/8
1
1/8
1
3/8
1
3/8
NEMA - National Electrical Manufacturers Association (U.S.A.)
UNIT 40RM
007
40RM
008
40RM
012 40RM
014
40RM
016 40RM
024
40RM
028
57
HIGH-ST ATIC DRIVE DATA, 50 Hz - SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter
(mm)
86.4-
111.8 86.4-
111.8 101.6-
127.0 86.4-
111.8 101.6-
127.0 101.6-
127.0 109.2-
134.6 109.2-
134.6
Pulley Factory Setting
Full Turns Open 2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (mm) 152 140 140 152 178 163 203 218
Pulley Bore (mm) 25.4 25.4 25.4 36.5 36.5 36.5 49.2 49.2
Belt No. - Section 1-A 1-A 1-A 2-A 2-A 2-A 2-B 2-B
Belt Pitch (mm) 947 947 922 922 998 871 935 960
FAN SPEEDS (r/s)
Factory Setting 15.4 16.8 19.4 15.4 15.3 16.7 14.3 13.3
Range 13.5-
17.4 14.7-
19.0 17.3-
20.0* 13.5-
17.4 13.6-
17.0 14.9-
18.6 12.8-
15.7 11.9-
14.6
Max Allowable Speed (r/s) 20.0 20.0 20.0 20.0 20.0 20.0 18.3 18.3
Change per
1/2
Turn of
Moveable Motor Pulley
Flange
0.395 0.432 0.360 0.395 0.283 0.308 0.247 0.230
MAX FULL TURNS FROM
CLOSED POSITION 5 5 6 5 6 6 6 6
SHAFTS CENTER DISTANCE
(mm) 265-313 265-313 234-279 232-279 232-279 207-255 169-240 169-240
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 20 r/s.
40RM
007
40RM
008
40RM
012 40RM
014
40RM
016 40RM
024
40RM
028
40RM
034
STANDARD DRIVE DATA, 50 Hz - ENGLISH
UNIT 40RM
007
40RM
008 40RM
012 40RM
014 40RM
016 40RM
024
40RM
028 40RM
034
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.) 2.4-3.4 2.8-3.8 3.4-4.4 3.4-4.4 3.4-4.4 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.0 8.0 8.0 9.0 9.0 8.6 11.0 11.0
Pulley Bore (in.) 111 1 7/16 17/16 1 7/16 1 15/16 1 15/16
Belt No. - Section 1-A 1-A 1-A 1-A 1-A 1-B 2-B 2-B
Belt Pitch (in.) 39.3 39.3 40.3 42.3 42.3 41.8 43.8 43.8
FAN SPEEDS (rpm)
Factory Setting 517 588 695 618 618 795 622 622
Range 428-606 499-677 606-784 538-697 538-697 713-878 557-687 557-687
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100
Change per
1/2
Turn of
Moveable Motor Pulley
Flange
17.8 17.8 17.8 15.9 15.9 13.8 10.8 10.8
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 5 5 6 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.12- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
Application data (cont)
46
58
MEDIUM-ST ATIC DRIVE DATA, 50 Hz - ENGLISH
UNIT 40RM
007
40RM
008
40RM
012
40RM
014
40RM
016
40RM
024 40RM
028
40RM
034
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.) 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 2.5 2.5 3.0 2.5 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 8.0 7.0 6.0 7.5 7.9 7.0 9.4 9.4
Pulley Bore (in.) 1 1 1 1 7/16 17/16 17/16 115/16 115/16
Belt No. - Section 1-A 1-A 1-A 1-A 1-B 2-A 2-B 2-B
Belt Pitch (in.) 40.3 41.3 37.3 39.3 39.8 36.8 39.8 39.8
FAN SPEEDS (rpm)
Factory Setting 695 794 926 741 756 916 728 728
Range 606-784 692-896 808-1045 646-836 667-848 814-1018 652-803 652-803
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100
Change per
1/2
Turn of
Moveable Motor Pulley
Flange
17.8 20.4 23.7 19.0 15.1 20.4 12.6 12.6
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 5 6 5 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 9.16- 9.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 10.99 10.99 9.43 9.43
HIGH-ST ATIC DRIVE DATA, 50 Hz - ENGLISH
UNIT 40RM
007
40RM
008
40RM
012
40RM
014
40RM
016 40RM
024
40RM
028
40RM
034
MOTOR DRIVE
Motor Pulley Pitch Diameter
(in.) 3.4-4.4 3.4-4.4 4.0-5.0 3.4-4.4 4.0-5.0 4.0-5.0 4.3-5.3 4.3-5.3
Pulley Factory Setting
Full Turns Open 2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 6.0 5.5 5.5 6.0 7.0 6.4 8.0 8.6
Pulley Bore (in.) 1 1 117/16 17/16 17/16 115/16 115/16
Belt No. - Section 1-A 1-A 1-A 2-A 2-A 2-A 2-B 2-B
Belt Pitch (in.) 37.3 37.3 36.3 36.3 39.3 34.3 36.8 37.8
FAN SPEEDS (rpm)
Factory Setting 926 1010 1166 926 916 1002 855 795
Range 808-
1045 881-
1140 1036-
1200* 808-
1045 814-
1018 891-
1113 766-
944 713-
878
Max Allowable Speed (rpm) 1200 1200 1200 1200 1200 1200 1100 1100
Change per
1/2
Turn of
Moveable Motor Pulley
Flange
23.7 25.9 21.6 23.7 17.0 18.5 14.8 13.8
MAX FULL TURNS FROM
CLOSED POSITION 5 5 6 5 6 6 6 6
SHAFTS CENTER DISTANCE
(in.)
10.44-
12.32 10.44-
12.32 916-
10.99 9.16-
10.99 9.16-
10.99 8.16-
10.02 6.67-
9.43 6.67-
9.43
*It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT
exceed 1200 rpm.
47
59
Guide Specifications 38ARZ007-012
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 6 to 10 Tons, Nominal
Carrier Model Numbers: 38ARZ, Sizes 007-012
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall consist of a reciprocating or scroll air-
conditioning compressor assembly, an air-cooled
coil, propeller- type condenser fans, and a control
box. Unit shall discharge supply air upward as
shown on contract drawings. Unit shall be used in
a refrigeration circuit matched with a packaged air-
handling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000.
B. Unit construction shall comply with
ANSI/ASHRAE 15 safety code latest revision and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils for (38ARZ) shall be
leak tested at 200 psig, and pressure tested at 428
psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturer’s recommendations.
1.04 WARRANTY (FOR INCLUSION BY
SPECIFYING ENGINEER.)
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized
steel, bonderized and coated with a prepainted
baked enamel finish.
2. A heavy-gage roll-formed perimeter base rail
with forklift slots and lifting holes shall be
provided to facilitate rigging.
C. Fans:
1. Condenser fans shall be direct driven, propeller
type, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressor shall be of the hermetic scroll type
2. Compressor shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressor shall be equipped with internal high
discharge temperature protection (38ARZ007 and
012 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include
liquid line service valve, suction line service valve,
a full charge of compressor oil, and a holding
charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
2. Minimum safety devices which are equipped
with automatic reset (after resetting first at
thermostat), shall include:
a. High discharge pressure cutout.
b. Low pressure cutout.
c. High discharge temperature cutout (38ARZ008
only).
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of
48
60
_____ F. The power consumption at full load shall
not exceed _____ kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and
_____ F dry bulb, and air entering the condensing
unit at _____F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of ____
v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a field-installed accessory. This low-
ambient control shall regulate speed of the
condenser-fan motors in response to the saturated
condensing temperature of the unit. The control
shall maintain correct condensing pressure at
outdoor temperatures down to –20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide protection in moderate coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat shall have
7-day clock, holiday scheduling, large backlit
display, remote sensor capability, and Title 24
compliance.
b. Commercial Electronic Thermostat shall have 7-
day timeclock, auto-changeover, multi-stage
capability, and large LCD (liquid crystal display)
temperature display.
c. Carrier PremierLink™ Controller:
This control will function with CCN (Carrier
Comfort Network®) and ComfortVIEW™
software. It shall also be compatible with
ComfortLink™ controllers. It shall be ASHRAE
62-99 compliant and Internet ready. It shall accept
a CO2sensor in the conditioned space and be
Demand Control Ventilation (DCV) ready. The
communication rate must be 38.4K or faster. It
shall include an integrated economizer controller.
49
61
Guide specifications— 38ARD014-028
Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 121/2to 20 Tons, Nominal
Carrier Model Number: 38ARD, Sizes 014-024
Part 1 — General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit
suitable for on-the-ground or rooftop installation.
Unit shall have 2 independent refrigeration
circuits. Unit shall consist of dual scroll
compressors, an aircooled coil, propeller-type
condenser fans, and a control box. Unit shall
discharge supply air upward as shown on contract
drawings. Unit shall be used in a refrigeration
circuit matched with a packaged airhandling unit.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI
Standard 360-2000, and shall be certified and listed
in the latest ARI directory.
B. Unit construction shall comply with
ANSI/ASHRAE safety code, latest revision, and
comply with NEC.
C. Unit shall be constructed in accordance with UL
1995 standard and shall carry the UL and UL,
Canada label.
D. Unit cabinet shall be capable of withstanding
500-hour salt spray exposure per ASTM B117
(scribed specimen).
E. Air-cooled condenser coils shall be leak tested
at 150 psig, and pressure tested at 480 psig.
F. Unit shall be manufactured in a facility
registered to ISO 9001:2000 manufacturing quality
standard.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package only, and
shall be stored and handled according to unit
manufacturer’s recommendations.
1.04 WARRANTY (FOR INCLUSION BY
SPECIFYING ENGINEER.)
Part 2 — Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single piece, air-cooled
condensing unit. Contained within the unit
enclosure shall be all factory wiring, piping,
controls, compressor, holding charge (R-22), and
special features required prior to field start-up.
B. Unit Cabinet:
Unit cabinet shall be constructed of G-90
galvanized steel, bonderized and coated with a
prepainted baked enamel finish.
C. Fans:
1. Condenser fans shall be direct driven,
propellertype, discharging air vertically upward.
2. Fan blades shall be balanced.
3. Condenser fan discharge openings shall be
equipped with PVC-coated steel wire safety
guards.
4. Condenser fan and motor shaft shall be
corrosion resistant.
D. Compressor:
1. Compressors shall be of the hermetic scroll type.
2. Compressors shall be mounted on rubber
grommets.
3. Compressors shall include overload protection.
4. Compressors shall be equipped with a crankcase
heater.
5. Compressors shall be equipped with internal
high discharge temperature protection (38ARD016
and 024 only).
E. Condenser Coil:
1. Condenser coil shall be air-cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins
(copper fins optional) mechanically bonded to
internally grooved seamless copper tubes which
are then cleaned, dehydrated, and sealed.
F. Refrigeration Components:
Refrigeration circuit components shall include high
side pressure relief device, liquid line service
valve, suction line service valve, a full charge of
compressor oil, and a holding charge of refrigerant.
G. Controls and Safeties:
1. Minimum control functions shall include:
a. Power and control wire terminal blocks.
b. Compressor lockout on auto-reset safety until
reset from thermostat.
c. Recycle time delay of five minutes to prevent
compressor short cycling.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at thermostat):
a. High discharge pressure cutout.
b. Loss-of-charge cutout.
c. Condenser fan motors to be protected against
overload condition by internal overloads.
Manual reset at the unit:
Electrical overload protection through the use of
define-purpose contactors and calibrated, ambient
compensated, magnetic trip circuit breakers.
Circuit breakers shall open all three phases in the
event of an overload in any one of the phases or a
single phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet
or exceed _____ Btuh at a suction temperature of
_____ F. The power consumption at full load shall
not exceed _____ kW.
50
62
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
cooling capacity of _____ Btuh or greater at
conditions of _____ cfm entering-air temperature
at the evaporator at _____ F wet bulb and _____ F
dry bulb, and air entering the condensing unit at
_____ F.
3. The system shall have an EER of _____ Btuh/
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
_____ v, 3-ph, 50 Hz. The unit shall be capable of
satisfactory operation within voltage limits of
_____ v to _____ v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v
transformer for unit control.
J. Special Features:
1. Low-Ambient Temperature Control:
A low-ambient temperature control shall be
available as a factory-installed option or as a field-
installed accessory. This low-ambient control shall
regulate speed of the condenser-fan motors in
response to the saturated condensing temperature
of the unit. The control shall maintain correct
condensing pressure at outdoor temperatures down
to –20 F.
2. Gage Panel Package:
Gage panel package shall include a suction and
discharge pressure gage.
3. Optional Condenser Coil Materials:
a. Pre-Coated Aluminum-Fin Coils:
Coils shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive coastal
environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
process to create an inert barrier between the
aluminum fin and copper tube. Epoxy-phenolic
barrier shall minimize galvanic action between
dissimilar metals.
b. Copper-Fin Coils:
Coils shall be constructed of copper-fins
mechanically bonded to copper-tubes and copper
tube sheets. A polymer strip shall prevent coil
assembly from contacting sheet metal coil pan to
minimize potential for galvanic corrosion between
the coil and pan. All copper construction shall
provide protection in moderate coastal
environments.
4. Thermostat Controls:
a. Programmable multi-stage thermostat with 7-day
clock, holiday scheduling, large backlit display,
remote sensor capability, and Title 24 compliance.
b. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multistage capability,
and large LCD (liquid crystal display) temperature
display.
c. Carrier PremierLink™ Controller:
This control will function with Carrier Comfort
Network® (CCN) and ComfortVIEW™ software.
It shall also be compatible with ComfortLink™
controllers. It shall be ASHRAE 62-99 compliant
and Internet ready. It shall accept a CO2sensor in
the conditioned space and be Demand Control
Ventilation (DCV) ready. The communication rate
must be 38.4K or faster. It shall include an
integrated economizer controller.
51
63
Guide specifications 40RM
Commercial Packaged Air-Handling Unit
HVAC Guide Specifications
SizeRange: 2,400 to 12,000 CFM (1150 to 5650 L/s),
Nominal Airflow 6 to 30 Tons (21 to
105 kW), Nominal Cooling
Carrier Model Numbers: 40RM (Direct-Expansion Coil)
Part 1 - GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for usein commer-
cial split systems.Unit shall have a multiposition de-
sign and shall be capable of horizontal or vertical
installation on a floor or in a ceiling, with or without
ductwork. (Only vertical units are to be applied with-
out ductwork.)
B. Unit with direct-expansioncoil shall be usedin a re-
frigerant circuit with a matching air-cooled con-
densing unit.
1.02 QUALITY ASSURANCE
A. Coils shallbe designed & tested in accordance with
ASHRAE 15 Safety Code for MechanicalRefrigera-
tion (U.S.A.), latest edition.
B. Unit shall be constructed in accordance with ETL
(U.S.A.) and ETL, Canada,standardsand shall carry
the ETL and ETL, Canada, labels.
C. Unit insulation and adhesive shall comply with
NFPA-90A (U.S.A.)requirements for flame spread
and smoke generation.
D. Unit shall be manufactured in a facility registered to
the ISO 9002 manufacturing quality standard.
E. Direct-expansionand chilledwater coilsshallbe burst
and leak testedat 435 psi (2999 kPa).
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturer's
recommendations.
Par t 2 - Products
2.01 EQUIPMENT
Indoor mounted,draw-thru, packaged air-handling unit
that can be used in a suspended horizontal configu-
ration or a verticalconfiguration. Unit shallconsistof
forward-curved belt-driven centrifugal fan(s), motor &
driveassembly,prewired fan motor contactor, factory-
installedrefrigerant metering devices(direct-expansion
coil units), cooling coil, 1-in. (25.4-mm) washable air
filters, and condensate drain pans for vertical or hori-
zontal configurations.
A. Base Unit (Painted):
1. Cabinetshall be constructed of zinc coated steel
and polyester powder painted to protect them
from corrosion in the harsh Middle Eastern climate
and also to increase the colour life in high ultra-
violet (UV) radiation regions.
2. Cabinet panels shall be fully insulatedwith
1/2
in.
(12.7-mm) fire-retardant material.
3. Unit shallcontain PVC condensate drain pans for
both vertical and horizontal applications. Drain
pansshallhaveconnectionson right and left sides
of unit to facilitate field connection. Drain pans
shallhavethe ability to be slopedtoward the right
or left side of the unit to prevent standing water
from accumulatingin pans.
4. Unit shall have factory-supplied 1-in. (25.4 mm)
washable-type filters installed upstream from the
cooling coil. Filter access shall be from the front
of the unit.
B. Coils:
Coils shall consist of 3 rows (40RM), of
coppertubes with sine-wave aluminum fins bonded
to the tubes by mechanical expansion. Suction and
liquid line connectionsor supplyand discharge con
-
nections shallbe made on the sameside of the coil.
1. Direct-expansioncoilsshallfeaturefactory-installed
thermostatic expansion valves (TXVs) for refrig-
erant control. The TXVs shall be capable of ex-
ternal adjustment. Direct-expansion heat pump
coils shall have a factory-installedbypassline and
check valve assemblyaround the TXVs to allow
liquid flow from the coil to the outdoor unit during
the heating mode. Coil tubing shall be internally
rifled to maximize heat transfer.
C. Operating Characteristics:
Unit shall be capable of providing cfm (L/s)
airflow at an external staticpressureof in. wg
(kPag).
D. Motor:
Fan motor of the size and electrical characteristics
specifiedon the equipment scheduleshall be factory
supplied and installed.
Motors rated at 1.3 through 3.7 hp (0.97 through
2.76 kW) shall have internal thermal overload pro-
tection. Motors rated at 5, 7
1/2
, and 10 hp (3.73,
5.60, and 7.46 kW) shall be protected by a circuit
breaker.
52
E. Factory-InstalledOptions:
1. Alternate Motor and Drive:
An alternatemotor and/or medium-or high-static
drive shall be available to meet the airflow and
external static pressure requirements specified
on the equipment schedule.
F. Field-InstalledAccessories (ordered from NAO):
1.
2.
3.
Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz; and 240, 400-volt, 3 phase,
50 Hz power supplyshallbe factory-suppliedfor
fieldinstallationasshownon the equipmentdraw-
ings.Electricheat assemblyshallbeETL (U.S.A.)
and ETL, Canada, agency approved, and shall
have single-point power wiring. Heater assem-
blyshallincludecontactorswith 24-V coils, power
wiring, 24-v control wiring terminal blocks, and
a hinged accesspanel. Electric heatersshall not
be usedwith air discharge plenum.
4.
Air Discharge Plenum:
Plenumshallbe factory suppliedto provide free-
blow air distribution for vertical floor-mounted
units. A grille with moveable vanes for hori-
zontal or vertical airflow adjustment shall be
included. Plenum shall be field-assembledand
field-installedon the unit's fan deckfor blow-thru
air distribution. Plenum shall not be used with
electric heaters.
5.
Return Air Grille:
Grille shall be factory supplied for field installa-
tion on the unit's return air opening.
6.
Unit Subbase:
Subbaseassemblyshall be factory supplied for
field installation. Subbase shall elevate floor-
mounted vertical units to provide access for
correct condensate drain connection.
7.
Economizer:
Economizerfor ventilation or ``free'' cooling shall
be factory provided for field installationon either
return air opening of air handler. For free cool-
ing applications,economizershallbe compatible
with separatethermostat; economizer dampers
shall open when outdoor air enthalpy is suitable
for free cooling. Economizershallbe compatible
with separate CO
2
sensor accessory; economizer
dampersshallopen when indoor CO
2
levelrises
abovepredetermined setpoint. Economizershall
include enthalpy control and damper actuator.
8.
Thermostat Controls:
a. Debonairprogrammablemulti-stagethermo-
statwith 7-dayclock,holidayscheduling,large
ThermoglowŸ display, remote sensorcapa-
bility, and Title 24 compliance.
b. TEMP System programmable communicat-
ing multi-stage thermostat with fan switch,
time clock,LCD display,ÉF/ÉC capability, and
CCN compatiblity.
c. CommercialElectronicThermostatwith 7-day
time clock, auto-changeover, multi-stageca-
pability, and large LCD temperature display.
d. Non-programmablethermostatwith fanswitch
subbase.
9.
Overhead SuspensionPackage:
Package shall include necessary brackets to
support units in a horizontal ceiling installation.
CO
2
Sensor:
Sensorshallprovide the ability to signalthe econo-
mizerto open when the spaceCO
2
levelexceeds
the predetermined set point. Sensor shall have
the capability of being connected to Comfort
Systemrelay pack or to economizer using field-
supplied and -installed Honeywell dc adapter
no. Q769C1004.
CondensateDrain Trap:
Trap shall have transparent, serviceabledesign
for easycleaning.Kit shallincludeoverflow shut-
off switch and wiring harnessfor connection to
an alarm if desired.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
2010 Form 38AR-01 PD 50Hz CKAC