38CKC036 Air 38CKC
User Manual: 38CKC036 Air
Open the PDF directly: View PDF .
Page Count: 20
Download | |
Open PDF In Browser | View PDF |
Product Data 38CKC 50 Hz Air Conditioner 38CKC Sizes 018 thru 060 Model 38CKC 50 Hertz EnergyEfficient Air Conditioner incorporates innovative technology to provide reliable summer cooling performance. Built into these units are the features most desired by customers today, including EER ratings of up to 10.0 when used with components designated by manufacturer. FEATURES/BENEFITS Electrical Range — Single phase units are available in 018, 024, and 036 sizes in 220-240v. Three-phase units are available in 036, 048, and 060 sizes in 400v. Wide Range of Sizes — The 38CKC is available in nominal sizes 018, 024, 036, 048, and 060 to meet the needs of residential and light commercial applications. Weather Armor II Cabinet — The steel is protected with a heavy galvanize coating, and treated with a layer of zinc phosphate. A modified polyester powder coating is then applied and baked on, providing each unit with a hard, smooth finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting, rust-resistant, quality appearance. Totally Enclosed Fan Motor — Means greater reliability under adverse weather conditions and dependable performance for many years. Permanent-split-capacitor-type motors provide more economical operation. Unit Design — Copper tube, enhanced sine wave aluminum fin coil is designed for optimum heat transfer. Copyright 1998 Carrier Corporation Form 38CKC-C3PD Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. Heat pump style drain pan allows for easy removal of water, dirt, and leaves. Application Versatility — The unit can be combined with a wide variety of evaporator coils and blower packages to provide quiet, dependable comfort. Unit can be installed on a roof or at ground level. connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures. Additional Compressor Protection — Each compressor is protected with internal temperatureand current-sensitive overloads. The 048 and 060 sizes have a short cycle protector standard. Easy Serviceability — One access panel provides access to electrical control box. Removal of top allows access to fan motor, compressor, and coil. Safety — All units are designed and manufactured in accordance with Underwriters Laboratories (UL 1995) safety standard for heating and cooling equipment. External Service Valves — Both service valves are brass, front seating type. The 38CKC has sweat field Pressure Switches — All units are equipped with high and low pressure switches. Sound Hood — 38CKC Sizes 036 through 060 have a compressor sound hood for noise attenuation. Quality Assurance REGISTERED QUALITY SYSTEM Model number nomenclature 38CKC 018 7 4 3 Electric Air Conditioner Nominal Capacity 018 — 18,000 Btuh (5.3 Kw) 024 — 24,000 Btuh (7.0 Kw) 036 — 36,000 Btuh (10.6 Kw) Packaging Series 048 — 48,000 Btuh (14.1 Kw) 060 — 60,000 Btuh (17.6 Kw) Electrical 7 — 240-1-50 9 — 400-3-50 The data in this publication is displayed for all series, however, every series may not be available from manufacturer. 2 Physical data UNIT SIZE / SERIES OPERATING WT (Lb/Kg) COMPRESSOR Manufacturer & Type REFRIGERANT Control Charge (Lb/Kg) @ 15 ft / 4.6m COND FAN Air Discharge Air Qty (CFM / L/S) COND COIL Face Area (Sq ft / m2 ) VALVE CONNECT. (In./mm ID) Vapor Liquid REFRIG TUBES* (In./mm OD) Vapor Liquid 018-74 024-74 036-74, 94 048-94 060-94 122 / 55.3 131 / 59.4 148 / 67.1 209 / 94.8 220 / 99.8 Copeland & Recip Copeland & Recip Copeland & Recip Copeland & Scroll Copeland & Scroll 3.4 / 1.5 22 AccuRater® (Bypass Type) 4.8 / 2.2 6.25/2.8 9.75/4.4 3.76 / 1.71 Propeller Type, Direct Drive Vertical 1550 / 724 2600 / 1214 6.2 / 0.574 7.5 / 0.697 5/8 / 15.875 5/8 / 15.875 3300 / 1541 10.8 / 1.003 Sweat 3/4 / 19.05 3/8 / 9.525 3/4 / 19.05 3/8 / 9.525 14.9 / 1.384 22.4 / 2.081 7/8 / 22.225 7/8 / 22.225 1-1/8 / 28.575 * Tube sizes are for runs up to 50 ft (15.24m). For tube set over 50 ft (15.24m), consult Residential Split-System Long-Line Application Guideline. NOTE: See unit Installation Instructions for proper installation. ACCURATER® PISTON CHART UNIT SIZE PISTON IDENTIFICATION NO.* 018-74 57 024-74 63 036-74, 94 73 048-94 90 060-94 101 * Piston listed is for any approved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil. 3 Accessories PART NO. DESCRIPTION KSAHS0301AAA Start Assist–Capacitor/Relay — Sizes 018; 024; 036 (74) KAACS0101PTC Start Assist — PTC — Sizes 018; 024 KAACS0201PTC Start Assist — PTC — Sizes 036 (74) KAALS0101LLS* Liquid Solenoid Valve — All Sizes KSACY0101AAA Cycle Protector — Sizes 018; 024; 036 (74) Standard Cycle Protector — Sizes 036(94); 048; 060 KAAWS0201AAA Winter Start Control — All Sizes KAAFT0101AAA Evaporator Freeze Thermostat — All Sizes KAATD0101TDR Time-Delay Relay — All Sizes KSASF0101AAA Support Feet — All Sizes KAACH1001AAA Crankcase Heater — Sizes 018; 024; 036 (74) KAACF0701SML Coastal Filter — Size 018 KAACF1001MED Coastal Filter — Sizes 024; 036 KAACF1101LRG Coastal Filter — Sizes 048; 060 KAATX0201RPB Thermostatic Expansion Valve (RPB) — Size 018 KAATX0301RPB Thermostatic Expansion Valve (RPB) — Size 024 KAATX0501RPB Thermostatic Expansion Valve (RPB) — Size 036 KAATX0601RPB Thermostatic Expansion Valve (RPB) — Size 048 KAATX0701RPB Thermostatic Expansion Valve (RPB) — Size 060 KAATX0601HSO* Thermostatic Expansion Valve (Hard Shutoff) — Sizes 018; 024; 036 KAATX0701HSO* Thermostatic Expansion Valve (Hard Shutoff) — Sizes 048; 060 P251-0083 (RCD) Low-Ambient Controller — 024-060 KSALA0201R22 Low-Ambient Kit (R22) — All Sizes 32LT66004 (RCD) MotorMaster® Control — 024, 036, (74) 32LT66005 (RCD) MotorMaster® Control — 036, (94); 048; 060 P504–8083S Filter Drier — 018-036 P504–8163S Filter Drier — 048; 060 KSADG0101MIC Discharge Grille — Size 018 KSADG0201SML Discharge Grille — Sizes 024; 036 KSADG0301MED Discharge Grille — Sizes 048; 060 * Do not use hard shutoff TXV with liquid solenoid valve. N/A — Not Applicable THERMOSTAT Thermostat, Auto Changeover, Non-Programmable, °F/°C, 1-Stage Heat, 1-Stage Cool TSTATCCPAC01-B Thermostat, Auto Changeover, 7-Day Programmable, °F/°C, 1-Stage Heat, 1-Stage Cool TSTATCCBAC01 TSTATCCPRH01-B TSTATXXCNV10 TSTATXXSEN01-B 4 DESCRIPTION TSTATCCNAC01-B Builder’s Thermostat, Manual Changeover, Non-Programmable, °F/°C,-Stage Heat, 1-Stage Cool Thermidistat, Programmable/Non-Programmable Thermostat with Humidity Control Thermostat Conversion Kit (4 to 5 Wire) — 10 Pack Outdoor Air Temperature Sensor TSTATXXNBP01 Backplate for Non-Programmable Thermostat TSTATXXPBP01 Backplate for Programmable Thermostat TSTATXXBBP01 Backplate for Builder’s Thermostat Accessory usage guideline ACCESSORY REQUIRED FOR LOW-AMBIENT APPLICATIONS (Below 55°F) (12.8°C) REQUIRED FOR LONG-LINE APPLICATIONS* (Over 50 Ft) (15.24m) Crankcase Heater Yes Yes No Evaporator Freeze Thermostat Yes No No Winter Start Control Yes† No No Accumulator No No No Compressor Start Assist Capacitor and Relay Yes Yes No Low Ambient Controller or MotorMaster® Control Yes No No See Low-Ambient Instructions No No Wind Baffle REQUIRED FOR SEA COAST APPLICATIONS (Within 2 Mi) (3.2km) Coastal Filter No No Yes Support Feet Recommended No Recommended No See Long-Line Application Guideline No Liquid-Line Solenoid Valve or Hard Shutoff TXV * For tubing line sets between 50 (15.24m) and 175 ft (53.34m), refer to Residential Split System Long-Line Application Guideline. † Only when low-pressure switch is used. Accessory description and usage (Listed alphabetically) 1. Coastal Filter A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. SUGGESTED USE: In geographic areas where salt damage could occur. 2. Compressor Start Assist — Capacitor/Relay Type Start capacitor and start relay gives ‘‘hard’’ boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft (15.24m). Installations where outdoor design temperature exceeds 105°F (40.6°C). Replacement installations with hard shutoff expansion valve on indoor coil. 3. Compressor Start Assist — PTC Type Solid-state electrical device which gives a ‘‘soft’’ boost to the compressor at each start-up. SUGGESTED USE: Installations with marginal power supply. Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil. 4. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft (15.24m). When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with low-ambient controller.) All commercial installations. 5. Cycle Protector Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including normal room thermostat cycling. SUGGESTED USE: Installations in areas where power interruptions are frequent. Where user is likely to ‘‘play’’ with the room thermostat. All commercial installations. Installations where interconnecting tube length exceeds 50 ft (15.24m). High-rise applications. 6. Evaporator Freeze Thermostat A SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE: All units where winter start control has been added. 7. Liquid Solenoid Valve (LSV) An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. NOTE: Compressor start assist–capacitor/relay type must also be used. SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline. 8. Low-Ambient Controller Head pressure controller is cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100 °F [37.8°C] high and 60 °F [15.6°C] low). The control will maintain working head pressure a low-ambient temperatures down to 0°F (–17.8°C) when properly installed. SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C). 9. MotorMaster® Control A fan speed control device activated by a temperature sensor.Designed to control condenser fan motor speed n response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F±10°F (37.8°C ± –12.2°C). SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C). All commercial installations 10. Support Feet Four stick-on plastic feet which raise the unit 4 in. (10.16cm) above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes corrosion SUGGESTED USE: Coastal installations. Windy areas or where debris is normally circulating. Rooftop installations 5 Accessory description and usage (Listed alphabetically) continued 11. Thermostatic Expansion Valve (TXV) A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB valves are available. SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. 12. Time-Delay Relay A SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. 13. Winter Start Control A SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions. SUGGESTED USE: All air conditioners where low-ambient controller has been added. Electrical data UNIT SIZE-SERIES 018-74 024-74 036-74 036-94 048-94 060-94 * † ‡ ** V/PH OPER VOLTS* COMPRESSOR Max LRA RLA FAN FLA MCA 55.0 68.0 94.0 42.0 63.0 74.0 9.9 11.6 17.7 6.4 7.95 8.97 0.8 0.65 0.65 0.4 0.7 0.7 13.2 15.2 22.8 8.4 10.7 11.9 Min 230-1 253 207 400-3 440 360 MIN MAX MAX MAX FUSE† WIRE LENGTH LENGTH OR SIZE (Ft) (m) CKT BKR 60°C/75°C** 60°C/75°C‡ 60°C/75°C‡ AMPS 14 14 12 14 14 14 59/56 53/50 55/52 202/192 165/157 152/144 18.0/17.1 16.2/15.2 16.8/15.8 61.8/58.7 50.3/47.9 46.4/44 20 25 35 15 15 20 Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure. Time-delay fuse. Length shown is as measured 1 way along wire path between the unit and service panel for a voltage drop not to exceed 2%. If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140 °F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70). FLA — Full Load Amps LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps NOTES: 1. Control circuit is 24v on all units and requires external power source. 2. Copper wire must be used from service disconnect to unit. 3. All motors/compressors contain internal overload protection. 6 4 4 4 4 4 38CKC024 38CKC036 38CKC048 38CKC060 SERIES 4 4 4 4 4 UNIT 38CKC018 38CKC024 38CKC036 38CKC048 38CKB060 ENGLISH SERIES UNIT 38CKC018 S.I. 30 30 22 1/2 22 1/2 18 In. A 762.0 762.0 571.5 571.5 457.2 mm A 39 15/16 27 5/16 29 15/16 21 15/16 23 15/16 In. B 1014.4 709.6 760.4 557.2 608.8 mm B 3 1/4 3 1/4 3 3/16 3 3/16 3 3/16 In. C 82.6 82.6 81.0 81.0 81.0 mm C 7/8 7/8 3/4 5/8 5/8 In. D 22.2 22.2 19.1 15.9 15.9 mm D 6 1/2 6 1/2 3 11/16 3 11/16 3 In. E 165.1 165.1 93.7 93.7 76.2 mm E 30 x 30 15 In. F 596.9 596.9 460.4 460.4 381.0 mm F B P A SQ D DIA VAPOR LINE CONN AIR DISCHARGE 1 1/4″ (31.8mm) 2 7/8″ C (73.0mm) 3/8 IN. (9.5mm) DIA LIQUID LINE CONN FIELD CONTROL SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE FIELD POWER SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE WITH 1 1/8 IN. (28.6mm) DIA KNOCKOUT AND 1 3/8 IN. (34.9mm) DIA KNOCKOUT 23 1/2 23 1/2 18 1/8 27 1/4 27 1/4 19 3/4 19 3/4 16 5/16 In. G 692.2 692.2 501.7 501.7 414.3 mm G 29 3/4 29 3/4 22 1/4 22 1/4 17 3/4 In. H 755.7 755.7 565.2 565.2 450.9 mm H 20 20 14 3/8 14 3/8 10 3/16 In. J 508.0 508.0 365.1 365.1 258.8 mm J 27 1/16 27 1/16 19 9/16 19 9/16 16 1/8 In. K 687.4 687.4 496.9 496.9 409.6 mm K 29 9/16 29 9/16 22 1/16 22 1/16 17 9/16 In. L 750.9 750.9 560.4 560.4 446.1 mm L 15 1/2 15 10 3/8 10 3/8 7 7/8 In. M 393.7 381.0 263.5 263.5 200.2 mm M NOTES: 1. Allow 30 In. (762.0mm) clearance to service side of unit, 48 In. (1219.2mm) above unit, 6 In. (152.4mm) on one side, 12 In. (308.8mm) on remaining side, and 24In. (609.6mm) between units for proper airflow. 2. Minimum outdoor operating abient in cooing mode is 55°F(13°C), max 125°F(52°C). 3. Series designation is the 13th position of the unit model number. 4. Center of gravity. 18 1/8 762.0 x 762.0 048, 060 22. 1/2 x 22 1/2 18 x 18 UNIT SIZE 571.5 x 571.5 AIR IN 457.2 x 457.2 L 018 H K 024, 036 F G AIR IN J AIR DISCHARGE MINUMUM MOUNTING PAD DIMENSIONS (In.) E AIR IN MINIMUM MOUNTING PAD DIMENSIONS (mm) AIR DISCHARGE (9.5mm) DIA TIEDOWN KNOCKOUTS (2) PLACES 3/8 IN. AIR IN N M 14 3/4 13 10 3/4 10 1/4 8 3/8 In. N 374.7 330.2 273.1 206.4 212.7 mm N 15 14 1/2 10 3/4 10 3/4 10 1/8 In. P 381.0 368.3 273.1 273.1 257.2 mm P 223 217 143 131 119 Lb. SHIPPING WEIGHT 101.4 98.6 64.9 59.4 54.1 kg SHIPPING WEIGHT A97007 Dimensions 7 Combination ratings OUTDOOR UNIT SIZE-SERIES 018-74 024-74 036-74, 94 048-94 060-94 NOMINAL AIRFLOW INDOOR UNIT F(A,B)4ASF018* F(A,B)4ASF024 FG3ASA024 F(A,B)4ASF024* F(A,B)4ASF030 FG3ASA024 F(A,B)4ASF036* F(A,B)4AS(F,B)042 FG3ASA036 F(A,B)4AS(F,B)048* F(A,B)4AS(F,B)060 FG3ASA048 FG3ASA060 F(A,B)4AS(F,B)060* FB4ASB070 FG3ASA060 CFM 600 600 600 800 800 800 1200 1200 1200 1600 1600 1600 1600 1850 1850 1850 L/S 280 280 280 380 380 380 550 550 550 750 750 750 750 850 850 850 COOLING CAP @ 95°F (35°C) Rated Capacity Power Rated BTUH KW KW EER 18,000 5.3 1.96 9.80 19,000 5.6 2.00 10.00 18,500 5.4 2.04 9.80 23,000 6.7 2.75 9.00 23,600 6.9 2.74 9.10 22,000 6.4 2.79 8.70 35,000 10.3 3.91 8.50 35,500 10.4 3.94 8.50 34,000 10.0 3.92 8.00 46,500 13.6 5.07 9.00 47,500 13.9 5.12 9.30 45,500 13.3 5.06 9.00 46,500 13.6 5.11 9.00 57,000 16.7 6.30 9.00 58,000 14.1 6.28 9.00 56,000 16.4 6.30 9.00 COOLING CAP@115°F (46°C) Rated Capacity Power BTUH KW KW 15,700 4.6 2.14 16,800 4.9 2.19 16,276 4.8 2.22 19,900 5.8 3.03 19,948 5.8 3.02 19,271 5.6 3.07 30,500 8.9 4.32 31,020 9.1 4.35 29,521 8.6 4.33 41,500 12.2 5.50 42,794 12.5 5.56 40,475 11.9 5.49 41,525 12.2 5.54 51,200 15.0 7.50 52,183 15.3 7.47 50,365 14.8 7.49 * Tested combination. NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included. 2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures. 3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature. 4. Minimum outdoor operating ambient in cooling mode is 55°F (12.8°C), maximum 125°F (51.7°C). Sound power 8 UNIT SIZE SOUND RATING (dBA) 125 250 500 1000 2000 4000 8000 018-74 77 59.0 66.0 69.0 71.5 70.0 65.0 58.5 024-74 77 52.0 65.5 67.0 69.0 68.0 68.5 63.0 036-74 75 54.0 65.0 66.5 69.5 67.0 66.5 60.5 036-94 78 59.0 68.0 68.0 72.5 73.0 71.0 67.0 048-94 77 52.0 64.0 69.5 70.5 68.5 66.5 63.0 060-94 76 54.5 61.0 66.5 69.5 68.5 68.0 63.5 A-WEIGHTED SOUND POWER LEVELS WITHIN OCTAVE BAND SHOWN Detailed cooling capacities* (S.I.) CONDENSER ENTERING AIR TEMPERATURES °C EVAP AIR L/S 28 32 36 40 44 48 52 Capacity† (KW) Capacity† (KW) Capacity† (KW) Capacity† (KW) Capacity† (KW) Capacity† (KW) Capacity† (KW) Sys. Sys. Sys. Sys. Sys. Sys. Sys. (C) Power Power Power Power Power Power Power EWB Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** 38CKC018-74 Outdoor Section With F(A,B)4ASF018 Indoor Section 240 280 320 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 6.05 5.64 5.25 4.92 4.70 6.20 5.79 5.39 5.08 4.92 6.32 5.90 5.51 5.22 5.12 3.00 3.48 3.96 4.38 4.67 3.15 3.70 4.24 4.68 4.90 3.29 3.91 4.50 4.95 5.10 1.84 1.80 1.76 1.72 1.70 1.89 1.84 1.80 1.77 1.75 1.93 1.88 1.84 1.81 1.80 5.82 5.42 5.04 4.73 4.54 5.96 5.55 5.17 4.88 4.75 6.07 5.66 5.28 5.01 4.94 2.91 1.92 5.58 2.81 1.99 5.33 2.72 2.06 5.09 2.63 2.13 3.39 1.87 5.19 3.30 1.94 4.96 3.20 2.01 4.72 3.11 2.08 3.87 1.82 4.82 3.77 1.89 4.61 3.67 1.96 4.38 3.57 2.02 4.27 1.79 4.53 4.15 1.85 4.33 4.03 1.91 4.13 3.91 1.98 4.51 1.76 4.38 4.36 1.83 4.21 4.20 1.90 4.04 4.03 1.96 3.05 1.96 5.71 2.96 2.04 5.45 2.87 2.11 5.19 2.77 2.18 3.61 1.92 5.32 3.51 1.99 5.07 3.41 2.05 4.83 3.32 2.12 4.14 1.87 4.95 4.04 1.94 4.72 3.94 2.00 4.49 3.82 2.07 4.56 1.83 4.68 4.44 1.90 4.47 4.31 1.96 4.27 4.17 2.03 4.74 1.82 4.58 4.57 1.89 4.41 4.40 1.95 4.23 4.22 2.02 3.19 2.00 5.81 3.10 2.08 5.55 3.00 2.15 5.28 2.91 2.22 3.81 1.96 5.41 3.71 2.03 5.16 3.61 2.10 4.91 3.51 2.16 4.40 1.91 5.05 4.29 1.98 4.82 4.17 2.05 4.59 4.04 2.11 4.82 1.88 4.80 4.68 1.94 4.60 4.54 2.01 4.39 4.38 2.08 4.93 1.87 4.76 4.75 1.94 4.57 4.57 2.01 4.39 4.38 2.08 Multipliers for Determining the Performance With Other Indoor Sections Cooling 4.83 4.48 4.15 3.91 3.86 4.93 4.58 4.26 4.05 4.04 5.01 4.65 4.36 4.19 4.19 2.53 3.01 3.46 3.78 3.85 2.68 3.22 3.70 4.01 4.03 2.81 3.41 3.90 4.19 4.19 2.20 2.14 2.08 2.03 2.02 2.25 2.18 2.13 2.09 2.09 2.29 2.23 2.17 2.14 2.14 4.58 4.23 3.90 3.68 3.66 4.67 4.32 4.02 3.84 3.84 4.73 4.39 4.13 3.99 3.99 2.44 2.91 3.35 3.64 3.66 2.58 3.12 3.56 3.84 3.84 2.71 3.31 3.74 3.99 3.99 2.27 2.20 2.14 2.09 2.09 2.31 2.25 2.19 2.15 2.15 2.36 2.29 2.24 2.21 2.21 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 018 1.00 1.00 FG3ASA 024 1.04 1.04 024 1.07 1.02 — — — 38CKC024-74 Outdoor Section With F(A,B)4ASF024 Indoor Section 340 380 420 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 7.82 7.31 6.82 6.43 6.20 7.97 7.45 6.96 6.59 6.43 8.08 7.56 7.08 6.73 6.62 3.93 4.61 5.27 5.82 6.17 4.08 4.83 5.56 6.13 6.40 4.23 5.05 5.83 6.41 6.60 2.62 2.54 2.46 2.40 2.37 2.66 2.58 2.51 2.45 2.43 2.71 2.63 2.55 2.50 2.48 7.49 7.00 6.53 6.17 5.98 7.63 7.13 6.66 6.32 6.20 7.73 7.23 6.77 6.45 6.38 3.81 2.73 7.16 3.68 2.84 6.83 3.56 2.95 6.49 3.43 3.06 4.48 2.65 6.69 4.35 2.76 6.37 4.22 2.86 6.05 4.10 2.96 5.13 2.57 6.24 5.00 2.67 5.95 4.87 2.77 5.65 4.73 2.87 5.67 2.51 5.90 5.51 2.61 5.64 5.35 2.71 5.37 5.19 2.80 5.96 2.48 5.76 5.74 2.58 5.54 5.52 2.69 5.31 5.30 2.79 3.96 2.78 7.28 3.83 2.89 6.94 3.71 3.00 6.59 3.58 3.11 4.70 2.69 6.80 4.57 2.80 6.47 4.44 2.91 6.14 4.31 3.01 5.42 2.62 6.36 5.28 2.72 6.06 5.14 2.82 5.76 4.99 2.92 5.96 2.56 6.05 5.80 2.66 5.77 5.63 2.76 5.51 5.44 2.86 6.18 2.54 5.96 5.95 2.65 5.73 5.72 2.75 5.48 5.48 2.86 4.11 2.82 7.38 3.98 2.93 7.02 3.85 3.05 6.67 3.72 3.15 4.92 2.74 6.90 4.79 2.84 6.56 4.65 2.95 6.22 4.52 3.05 5.69 2.66 6.46 5.54 2.76 6.16 5.38 2.87 5.86 5.20 2.97 6.24 2.61 6.17 6.06 2.71 5.90 5.86 2.81 5.64 5.63 2.92 6.37 2.59 6.13 6.13 2.70 5.88 5.88 2.81 5.63 5.63 2.92 Multipliers for Determining the Performance With Other Indoor Sections Cooling 6.15 5.73 5.35 5.10 5.07 6.24 5.81 5.46 5.24 5.24 6.31 5.88 5.56 5.38 5.38 3.31 3.97 4.59 5.01 5.06 3.46 4.19 4.82 5.23 5.24 3.60 4.39 5.01 5.38 5.38 3.16 3.05 2.96 2.90 2.89 3.21 3.10 3.01 2.96 2.96 3.25 3.15 3.07 3.02 3.02 5.81 5.41 5.05 4.83 4.82 5.89 5.48 5.17 4.98 4.98 5.95 5.54 5.27 5.12 5.12 3.19 3.84 4.43 4.81 4.82 3.33 4.06 4.64 4.98 4.98 3.47 4.26 4.81 5.12 5.12 3.26 3.15 3.05 2.99 2.99 3.30 3.19 3.11 3.06 3.06 3.35 3.24 3.16 3.12 3.12 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.01 030 1.00 1.00 — — — 38CKC036-74, 94 Outdoor Section With F(A,B)4ASF036 Indoor Section 500 560 640 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 11.9 11.1 10.3 9.76 9.46 12.1 11.3 10.5 10.0 9.79 12.3 11.5 10.8 10.3 10.2 5.99 7.05 8.09 8.93 9.41 6.22 7.40 8.54 9.41 9.76 6.53 7.85 9.10 9.98 10.2 3.68 3.58 3.48 3.41 3.37 3.76 3.66 3.56 3.49 3.46 3.85 3.75 3.66 3.59 3.58 11.4 10.6 9.92 9.37 9.13 11.6 10.8 10.1 9.60 9.44 11.8 11.0 10.3 9.86 9.80 5.81 3.85 10.9 5.62 4.01 10.4 5.43 4.17 9.92 5.25 4.32 6.86 3.74 10.2 6.67 3.89 9.70 6.48 4.04 9.23 6.30 4.19 7.89 3.64 9.48 7.69 3.79 9.05 7.50 3.93 8.62 7.29 4.07 8.70 3.56 8.98 8.47 3.71 8.59 8.23 3.85 8.20 7.99 3.99 9.09 3.53 8.80 8.77 3.68 8.47 8.45 3.83 8.13 8.11 3.97 6.04 3.92 11.1 5.85 4.09 10.6 5.67 4.25 10.1 5.48 4.40 7.21 3.81 10.3 7.02 3.97 9.85 6.83 4.12 9.36 6.64 4.27 8.34 3.71 9.65 8.13 3.87 9.21 7.91 4.01 8.78 7.68 4.16 9.16 3.64 9.19 8.91 3.79 8.79 8.65 3.94 8.41 8.35 4.08 9.42 3.62 9.10 9.08 3.78 8.74 8.73 3.93 8.39 8.39 4.08 6.34 4.02 11.3 6.15 4.18 10.7 5.96 4.34 10.2 5.77 4.50 7.66 3.91 10.5 7.46 4.07 10.0 7.26 4.22 9.50 7.07 4.37 8.88 3.81 9.86 8.64 3.97 9.41 8.37 4.12 8.98 8.08 4.27 9.70 3.75 9.45 9.40 3.90 9.06 9.06 4.06 8.68 8.68 4.21 9.80 3.74 9.43 9.43 3.90 9.06 9.06 4.06 8.68 8.68 4.21 Multipliers for Determining the Performance With Other Indoor Sections Cooling 9.42 8.76 8.18 7.81 7.77 9.54 8.87 8.35 8.03 8.03 9.67 9.00 8.55 8.30 8.30 5.07 6.11 7.07 7.71 7.77 5.30 6.45 7.42 8.02 8.03 5.59 6.88 7.79 8.30 8.30 4.47 4.33 4.20 4.12 4.12 4.55 4.41 4.30 4.23 4.23 4.65 4.51 4.41 4.36 4.36 8.92 8.28 7.74 7.41 7.41 9.03 8.39 7.92 7.65 7.65 9.13 8.50 8.11 7.91 7.91 4.89 5.93 6.84 7.41 7.41 5.12 6.26 7.14 7.65 7.65 5.40 6.69 7.49 7.91 7.91 4.61 4.46 4.34 4.26 4.26 4.69 4.54 4.43 4.37 4.37 4.79 4.64 4.55 4.51 4.51 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.97 1.00 F(A,B)4AS(F,B) 042 1.02 1.01 — — — See notes on pg. 10. 9 Detailed cooling capacities* (S.I.) continued CONDENSER ENTERING AIR TEMPERATURES °C EVAP AIR L/S 28 32 36 40 44 48 52 Capacity† Capacity† Capacity† Capacity† Capacity† Capacity† Capacity† Comp. Comp. Comp. Comp. Comp. Comp. Comp. (KW) (KW) (KW) (KW) (KW) (KW) (KW) (C) Power Power Power Power Power Power Power EWB Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** 38CKC048-94 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 650 750 850 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 15.4 14.4 13.5 12.8 12.5 15.7 14.7 13.8 13.2 13.0 15.9 14.9 14.1 13.5 13.4 7.80 9.23 10.6 11.8 12.4 8.18 9.81 11.4 12.5 12.9 8.56 10.4 12.1 13.2 13.4 4.09 4.01 3.92 3.86 3.83 4.19 4.10 4.02 3.96 3.94 4.28 4.18 4.10 4.05 4.04 14.9 14.0 13.1 12.4 12.1 15.2 14.2 13.4 12.8 12.6 15.4 14.4 13.6 13.1 13.0 7.62 4.35 14.4 7.44 4.63 13.9 7.25 4.91 13.4 7.07 5.22 9.05 4.26 13.5 8.87 4.53 13.0 8.68 4.81 12.6 8.49 5.11 10.5 4.17 12.7 10.3 4.43 12.2 10.1 4.71 11.8 9.87 5.01 11.6 4.11 12.1 11.3 4.36 11.7 11.1 4.64 11.3 10.9 4.94 12.1 4.08 11.8 11.8 4.34 11.5 11.5 4.62 11.1 11.1 4.92 8.01 4.45 14.7 7.82 4.72 14.1 7.64 5.01 13.6 7.45 5.32 9.62 4.35 13.7 9.44 4.62 13.3 9.25 4.90 12.8 9.05 5.21 11.2 4.27 12.9 11.0 4.53 12.5 10.8 4.81 12.0 10.5 5.11 12.3 4.21 12.4 12.1 4.47 12.0 11.8 4.74 11.6 11.5 5.05 12.6 4.19 12.3 12.3 4.46 11.9 11.9 4.74 11.5 11.5 5.04 8.38 4.54 14.9 8.20 4.81 14.3 8.01 5.10 13.8 7.82 5.41 10.2 4.44 13.9 10.0 4.71 13.4 9.81 4.99 12.9 9.61 5.30 11.8 4.35 13.2 11.6 4.62 12.7 11.3 4.90 12.3 11.0 5.21 12.9 4.30 12.7 12.6 4.56 12.3 12.3 4.85 11.9 11.9 5.16 13.0 4.30 12.7 12.7 4.56 12.3 12.3 4.85 11.9 11.9 5.16 Multipliers for Determining the Performance With Other Indoor Sections Cooling 12.9 12.1 11.3 10.8 10.8 13.1 12.3 11.6 11.2 11.2 13.2 12.4 11.8 11.5 11.5 6.88 8.30 9.66 10.6 10.8 7.26 8.86 10.3 11.2 11.2 7.62 9.41 10.7 11.5 11.5 5.55 5.43 5.32 5.24 5.23 5.65 5.53 5.43 5.37 5.37 5.74 5.62 5.53 5.48 5.48 12.4 11.6 10.9 10.4 10.4 12.5 11.8 11.2 10.8 10.8 12.7 11.9 11.4 11.1 11.1 6.69 8.11 9.45 10.3 10.4 7.07 8.67 9.98 10.8 10.8 7.43 9.21 10.4 11.1 11.1 5.90 5.77 5.64 5.56 5.56 5.99 5.86 5.76 5.70 5.70 6.09 5.95 5.87 5.82 5.82 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00 060 1.03 1.01 060 1.00 1.01 38CKC060-94 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 750 850 950 1000 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 22 20 18 16 14 18.8 17.7 16.6 15.7 15.2 19.1 18.0 16.9 16.1 15.7 19.4 18.2 17.1 16.4 16.2 19.5 18.3 17.2 16.5 16.4 9.45 11.2 12.9 14.3 15.1 9.86 11.8 13.7 15.1 15.7 10.2 12.4 14.4 15.8 16.2 10.4 12.6 14.7 16.2 16.4 5.47 5.33 5.20 5.10 5.05 5.60 5.46 5.33 5.23 5.20 5.72 5.57 5.44 5.36 5.34 5.77 5.63 5.50 5.42 5.40 18.2 17.1 16.1 15.2 14.8 18.5 17.4 16.3 15.6 15.3 18.8 17.6 16.6 15.9 15.8 18.9 17.7 16.7 16.0 16.0 9.23 5.88 17.6 9.01 6.31 17.0 8.78 6.77 16.4 8.54 7.27 11.0 5.73 16.6 10.7 6.15 16.0 10.5 6.61 15.4 10.2 7.12 12.6 5.60 15.5 12.4 6.02 15.0 12.2 6.48 14.4 11.9 6.97 14.0 5.50 14.8 13.7 5.92 14.3 13.4 6.38 13.8 13.1 6.87 14.7 5.45 14.4 14.4 5.88 14.0 14.0 6.34 13.6 13.5 6.84 9.63 6.00 17.9 9.41 6.43 17.3 9.17 6.89 16.6 8.93 7.40 11.6 5.85 16.8 11.3 6.28 16.2 11.1 6.74 15.6 10.8 7.24 13.4 5.72 15.8 13.2 6.14 15.2 12.9 6.60 14.7 12.6 7.10 14.8 5.63 15.1 14.5 6.05 14.6 14.2 6.51 14.1 13.8 7.01 15.3 5.60 14.9 14.9 6.03 14.5 14.4 6.49 14.0 14.0 7.00 10.0 6.12 18.1 9.79 6.55 17.5 9.55 7.01 16.8 9.31 7.52 12.1 5.97 17.0 11.9 6.40 16.4 11.7 6.85 15.7 11.4 7.36 14.1 5.84 16.0 13.9 6.26 15.5 13.6 6.72 14.9 13.2 7.23 15.5 5.75 15.4 15.2 6.18 14.9 14.8 6.64 14.4 14.4 7.15 15.8 5.74 15.3 15.3 6.17 14.9 14.9 6.64 14.4 14.4 7.15 10.2 6.18 18.2 9.97 6.60 17.5 9.74 7.07 16.8 9.50 7.57 12.4 6.02 17.1 12.2 6.45 16.5 11.9 6.91 15.8 11.7 7.41 14.5 5.90 16.1 14.2 6.32 15.6 13.8 6.78 15.0 13.5 7.29 15.8 5.81 15.6 15.5 6.24 15.1 15.0 6.71 14.6 14.5 7.22 16.0 5.81 15.5 15.5 6.24 15.0 15.0 6.71 14.6 14.6 7.22 Multipliers for Determining the Performance With Other Indoor Sections Cooling 15.7 14.8 13.9 13.2 13.1 15.9 14.9 14.1 13.6 13.5 16.1 15.1 14.3 13.9 13.9 16.1 15.2 14.4 14.0 14.0 8.30 10.0 11.6 12.8 13.1 8.69 10.6 12.3 13.5 13.5 9.07 11.2 12.9 13.9 13.9 9.25 11.4 13.1 14.0 14.0 7.81 7.64 7.49 7.38 7.36 7.94 7.77 7.62 7.53 7.52 8.06 7.88 7.75 7.68 7.68 8.11 7.94 7.82 7.75 7.75 15.0 14.1 13.2 12.7 12.6 15.2 14.3 13.5 13.0 13.0 15.4 14.4 13.8 13.4 13.4 15.4 14.5 13.9 13.5 13.5 8.06 9.76 11.4 12.5 12.6 8.44 10.3 12.0 13.0 13.0 8.82 10.9 12.5 13.4 13.4 9.00 11.2 12.7 13.5 13.5 8.37 8.19 8.01 7.89 7.88 8.50 8.32 8.16 8.06 8.06 8.62 8.43 8.30 8.22 8.22 8.67 8.49 8.37 8.30 8.30 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.98 0.96 FB4ASB 070 1.02 1.03 — — — * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 7.62m of tubing. If other than 7.62m of tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower motor heat has been subtracted. ‡ Sensible capacities shown are based on 27°C entering air at the indoor coil. For sensible capacities at other than 27 °C, deduct 245 kw per 480 L/S of indoor coil air for each degree below 27°C, or add 245 kw per 480 L/S of indoor coil air per degree above 27 °C. When the required data falls between the published data, interpolation may be performed. ** Unit kw is total of indoor and outdoor unit kilowatts. EWB — Entering Wet Bulb 10 Detailed cooling capacities* (English) OUTDOOR COIL ENTERING AIR TEMPERATURES °F INDOOR COIL AIR CFM 75 85 95 Gross Capacity† (MBtuh) Gross Capacity† (MBtuh) Gross Capacity† (MBtuh) (F) EWB Total Sens‡ 72 67 62 57 72 67 62 57 72 67 62 57 21.7 19.7 17.8 16.7 22.2 20.2 18.3 17.4 22.6 20.5 18.7 18.0 10.4 12.8 15.2 16.7 10.9 13.5 16.1 17.4 11.3 14.2 17.0 18.0 Comp. Power KW** Total Sens‡ Comp. Power KW** Total Sens‡ 105 Comp. Power KW** 115 Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** 125 Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** 38CKC018-74 Outdoor Section With F(A,B)4ASF018 Indoor Section 525 600 675 1.78 1.72 1.67 1.63 1.82 1.76 1.70 1.68 1.85 1.79 1.74 1.72 20.6 10.0 1.89 19.5 9.58 1.99 18.3 9.15 2.09 17.1 18.7 12.4 1.82 17.6 11.9 1.92 16.5 11.5 2.01 15.4 16.9 14.7 1.76 15.9 14.2 1.85 14.9 13.7 1.94 13.9 15.9 15.9 1.73 15.2 15.2 1.82 14.4 14.4 1.92 13.6 21.1 10.4 1.92 19.9 10.0 2.03 18.7 9.56 2.13 17.4 19.1 13.1 1.86 18.0 12.6 1.96 16.9 12.2 2.05 15.7 17.3 15.7 1.80 16.3 15.2 1.89 15.3 14.6 1.98 14.2 16.6 16.6 1.78 15.8 15.8 1.87 15.0 15.0 1.97 14.1 21.4 10.8 1.96 20.2 10.4 2.06 18.9 9.94 2.17 17.7 19.4 13.8 1.90 18.3 13.3 1.99 17.1 12.8 2.09 15.9 17.6 16.5 1.84 16.6 16.0 1.93 15.6 15.4 2.02 14.6 17.2 17.2 1.82 16.4 16.4 1.92 15.5 15.5 2.02 14.6 Multipliers for Determining the Performance With Other Indoor Sections Cooling 8.71 11.0 13.2 13.6 9.12 11.7 14.0 14.1 9.50 12.4 14.6 14.6 2.19 2.10 2.02 2.00 2.23 2.14 2.06 2.06 2.27 2.18 2.11 2.11 15.9 14.2 12.7 12.6 16.1 14.5 13.2 13.2 16.4 14.7 13.6 13.6 8.26 10.6 12.6 12.6 8.66 11.2 13.2 13.2 9.04 11.9 13.6 13.6 2.28 2.18 2.10 2.10 2.32 2.23 2.15 2.15 2.36 2.26 2.20 2.20 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 018 1.00 1.00 FG3ASA 024 1.04 1.04 024 1.07 1.02 — — — 38CKC024-74 Outdoor Section With F(A,B)4ASF024 Indoor Section 700 800 900 72 67 62 57 72 67 62 57 72 67 62 57 27.9 25.4 23.1 21.7 28.5 26.0 23.7 22.6 29.0 26.5 24.2 23.5 13.5 16.6 19.7 21.7 14.1 17.6 21.0 22.6 14.6 18.6 22.3 23.5 2.49 2.39 2.29 2.24 2.55 2.44 2.35 2.31 2.60 2.49 2.40 2.37 26.4 12.9 2.66 24.8 12.3 2.82 23.2 11.7 2.97 21.6 24.0 16.0 2.54 22.5 15.4 2.69 21.1 14.8 2.84 19.6 21.8 19.0 2.44 20.4 18.4 2.58 19.1 17.7 2.72 17.8 20.7 20.7 2.39 19.7 19.7 2.54 18.6 18.6 2.68 17.5 26.9 13.5 2.71 25.3 12.9 2.87 23.7 12.3 3.02 22.0 24.5 17.0 2.60 23.0 16.4 2.75 21.5 15.7 2.89 19.9 22.3 20.4 2.50 20.9 19.7 2.64 19.6 19.0 2.78 18.3 21.6 21.6 2.46 20.5 20.5 2.61 19.4 19.4 2.76 18.2 27.4 14.0 2.76 25.7 13.4 2.92 24.0 12.8 3.08 22.3 25.0 17.9 2.65 23.4 17.3 2.80 21.8 16.7 2.94 20.2 22.8 21.6 2.55 21.4 20.8 2.69 20.1 20.0 2.83 18.8 22.3 22.3 2.53 21.2 21.2 2.68 20.0 20.0 2.83 18.8 Multipliers for Determining the Performance With Other Indoor Sections Cooling 11.1 14.2 17.1 17.5 11.7 15.1 18.2 18.2 12.2 16.0 18.8 18.8 3.11 2.97 2.84 2.82 3.17 3.03 2.91 2.91 3.22 3.08 2.98 2.98 20.0 18.1 16.4 16.4 20.3 18.4 17.0 17.1 20.6 18.6 17.6 17.6 10.5 13.6 16.3 16.4 11.1 14.5 17.0 17.1 11.6 15.4 17.6 17.6 3.25 3.10 2.97 2.96 3.31 3.15 3.05 3.04 3.36 3.21 3.12 3.12 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 024 1.00 1.00 FG3ASA 024 0.97 1.01 030 1.00 1.00 — — — 38CKC036-74, 94 Outdoor Section With F(A,B)4ASF036 Indoor Section 1050 1200 1350 72 67 62 57 72 67 62 57 72 67 62 57 42.5 38.6 35.0 33.2 43.4 39.5 35.9 34.7 44.1 40.1 36.6 35.9 20.6 25.6 30.5 33.2 21.5 27.2 32.6 34.7 22.4 28.7 34.6 35.9 3.51 3.38 3.26 3.20 3.61 3.47 3.35 3.31 3.69 3.55 3.43 3.41 40.2 19.7 3.75 37.9 18.9 3.98 35.6 18.0 4.20 33.2 36.5 24.7 3.60 34.4 23.8 3.82 32.2 22.9 4.03 30.0 33.1 29.6 3.47 31.1 28.6 3.67 29.2 27.6 3.87 27.3 31.7 31.7 3.42 30.2 30.2 3.63 28.6 28.6 3.84 27.0 41.0 20.6 3.84 38.6 19.8 4.07 36.2 18.9 4.29 33.7 37.2 26.3 3.69 35.0 25.3 3.91 32.7 24.4 4.12 30.5 33.9 31.6 3.56 31.9 30.6 3.77 29.9 29.5 3.97 28.1 33.1 33.1 3.53 31.4 31.4 3.75 29.7 29.7 3.96 28.1 41.7 21.5 3.92 39.2 20.6 4.15 36.6 19.7 4.37 34.1 37.9 27.7 3.77 35.5 26.8 3.99 33.2 25.9 4.20 30.8 34.6 33.5 3.65 32.6 32.3 3.86 30.7 30.7 4.07 28.9 34.2 34.2 3.63 32.5 32.5 3.86 30.7 30.7 4.07 28.9 Multipliers for Determining the Performance With Other Indoor Sections Cooling 17.1 22.0 26.6 27.0 18.0 23.5 28.1 28.1 18.8 24.9 28.9 28.9 4.41 4.22 4.06 4.04 4.50 4.32 4.17 4.17 4.59 4.40 4.28 4.29 30.8 27.8 25.3 25.3 31.2 28.2 26.3 26.3 31.5 28.5 27.1 27.1 16.3 21.2 25.3 25.3 17.1 22.6 26.3 26.3 18.0 24.0 27.1 27.1 4.61 4.40 4.24 4.24 4.70 4.50 4.37 4.37 4.79 4.59 4.49 4.49 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4ASF 036 1.00 1.00 FG3ASA 036 0.97 1.00 F(A,B)4AS(F,B) 042 1.02 1.01 — — — See notes on pg. 12. 11 Detailed cooling capacities* (English) continued OUTDOOR COIL ENTERING AIR TEMPERATURES °F INDOOR COIL AIR CFM 75 85 95 Gross Capacity† (MBtuh) Gross Capacity† (MBtuh) Gross Capacity† (MBtuh) (F) EWB Total Sens‡ 72 67 62 57 72 67 62 57 72 67 62 57 54.5 49.9 45.6 43.8 55.5 50.8 46.6 45.5 56.3 51.6 47.5 46.9 26.8 33.7 40.5 43.8 28.0 35.7 43.2 45.5 29.1 37.7 45.7 46.9 Comp. Power KW** Total Sens‡ Comp. Power KW** Total Sens‡ 105 Comp. Power KW** 115 Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** 125 Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** Gross Capacity† (MBtuh) Total Comp. Power Sens‡ KW** 38CKC048-94 Outdoor Section With F(A,B)4AS(F,B)048 Indoor Section 1400 1600 1800 3.86 3.75 3.64 3.60 3.95 3.83 3.73 3.70 4.03 3.91 3.81 3.80 52.3 26.0 4.20 50.0 25.1 4.58 47.6 24.2 4.98 45.2 47.8 32.9 4.08 45.7 32.0 4.44 43.6 31.1 4.82 41.3 43.8 39.6 3.96 41.9 38.6 4.32 39.9 37.6 4.70 37.9 42.3 42.3 3.92 40.7 40.7 4.28 39.1 39.1 4.67 37.5 53.2 27.2 4.29 50.8 26.3 4.67 48.4 25.4 5.07 45.8 48.7 34.9 4.16 46.5 34.0 4.53 44.2 33.1 4.92 41.9 44.8 42.3 4.05 42.8 41.2 4.41 40.8 40.1 4.79 38.8 43.9 43.9 4.03 42.2 42.2 4.39 40.5 40.5 4.78 38.8 53.9 28.3 4.38 51.5 27.4 4.75 48.9 26.6 5.15 46.3 49.4 36.9 4.24 47.1 36.0 4.61 44.8 35.0 5.00 42.3 45.6 44.6 4.14 43.6 43.4 4.49 41.7 41.7 4.89 39.8 45.2 45.2 4.13 43.5 43.5 4.49 41.7 41.7 4.89 39.9 Multipliers for Determining the Performance With Other Indoor Sections Cooling 23.4 30.2 36.6 37.5 24.5 32.2 38.8 38.8 25.6 34.1 39.8 39.9 5.41 5.25 5.11 5.09 5.50 5.34 5.22 5.22 5.59 5.43 5.32 5.32 42.7 39.0 35.8 35.7 43.2 39.6 37.0 37.0 43.6 40.0 37.9 37.9 22.5 29.3 35.4 35.7 23.6 31.3 37.0 37.0 24.7 33.1 37.9 37.9 5.89 5.71 5.55 5.54 5.99 5.80 5.67 5.67 6.07 5.89 5.79 5.79 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 048 1.00 1.00 FG3ASA 048 0.98 1.00 060 1.03 1.01 060 1.00 1.01 38CKC060-94 Outdoor Section With F(A,B)4AS(F,B)060 Indoor Section 1600 1850 2000 2150 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 66.7 61.0 55.8 53.2 68.1 62.3 57.1 55.5 68.7 62.9 57.8 56.7 69.3 63.4 58.4 57.8 32.4 40.6 48.7 53.2 34.0 43.3 52.4 55.5 34.9 44.8 54.4 56.7 35.7 46.3 56.3 57.8 5.11 4.92 4.75 4.67 5.26 5.06 4.90 4.85 5.34 5.14 4.98 4.94 5.42 5.22 5.06 5.04 64.0 31.4 5.63 61.2 30.4 6.21 58.2 29.3 6.86 55.2 58.5 39.6 5.43 56.0 38.5 6.01 53.3 37.4 6.64 50.4 53.6 47.6 5.26 51.3 46.5 5.83 48.8 45.3 6.46 46.3 51.4 51.4 5.19 49.6 49.6 5.76 47.6 47.6 6.41 45.5 65.2 32.9 5.78 62.3 31.9 6.36 59.2 30.8 7.00 56.0 59.7 42.3 5.58 57.0 41.2 6.15 54.1 40.0 6.79 51.2 54.8 51.2 5.41 52.4 50.0 5.97 49.9 48.7 6.61 47.4 53.6 53.6 5.37 51.6 51.6 5.95 49.5 49.5 6.59 47.3 65.8 33.8 5.86 62.8 32.7 6.44 59.6 31.6 7.09 56.3 60.3 43.8 5.66 57.5 42.7 6.23 54.6 41.5 6.87 51.6 55.4 53.2 5.49 53.0 51.8 6.06 50.5 50.3 6.69 48.1 54.7 54.7 5.46 52.6 52.6 6.04 50.4 50.4 6.69 48.1 66.3 34.7 5.94 63.2 33.6 6.52 60.0 32.5 7.17 56.7 60.7 45.3 5.73 57.9 44.1 6.31 54.9 43.0 6.94 51.9 56.0 55.0 5.57 53.7 53.4 6.14 51.3 51.3 6.79 48.9 55.7 55.7 5.56 53.5 53.5 6.14 51.3 51.3 6.79 48.9 Multipliers for Determining the Performance With Other Indoor Sections Cooling 28.1 36.3 44.0 45.5 29.6 38.8 47.1 47.3 30.5 40.3 48.1 48.1 31.3 41.8 48.9 48.9 7.57 7.35 7.15 7.12 7.72 7.49 7.31 7.31 7.80 7.57 7.41 7.41 7.88 7.65 7.51 7.51 51.9 47.5 43.5 43.2 52.6 48.2 44.9 44.9 52.9 48.5 45.7 45.7 53.2 48.8 46.4 46.4 27.0 35.1 42.6 43.2 28.4 37.6 44.9 44.9 29.3 39.1 45.7 45.7 30.1 40.5 46.4 46.4 8.35 8.10 7.86 7.84 8.50 8.25 8.05 8.05 8.58 8.33 8.17 8.17 8.66 8.41 8.27 8.27 Cooling Indoor Section Size Capacity Power Indoor Section Size Capacity Power F(A,B)4AS(F,B) 060 1.00 1.00 FG3ASA 060 0.98 0.96 FB4ASB 070 1.02 1.03 — — — * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower motor heat has been subtracted. ‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80 °F (27 °C), deduct 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed. ** Unit kw is total of indoor and outdoor unit kilowatts. EWB — Entering Wet Bulb 12 Condenser only ratings (S.I.) CONDENSER ENTERING AIR TEMPERATURES °C SST °C 20 24 28 32 36 40 44 48 52 3.62 1.41 46.2 4.01 1.46 46.2 4.40 1.51 46.2 4.81 1.55 46.4 5.23 1.60 46.6 5.65 1.65 46.9 6.09 1.69 47.2 3.32 1.44 50.4 3.70 1.49 50.4 4.08 1.55 50.4 4.48 1.60 50.6 4.89 1.65 50.8 5.30 1.70 51.1 5.73 1.75 51.4 3.04 1.46 54.6 3.40 1.52 54.6 3.77 1.58 54.6 4.15 1.63 54.7 4.55 1.69 54.9 4.95 1.75 55.2 5.37 1.81 55.5 2.76 1.48 58.7 3.11 1.54 58.7 3.46 1.60 58.7 3.82 1.66 58.8 4.21 1.73 59.0 4.60 1.79 59.3 5.01 1.85 59.6 2.50 1.49 62.8 2.83 1.55 62.8 3.15 1.62 62.8 3.50 1.69 62.8 3.87 1.76 63.0 4.25 1.83 63.3 4.64 1.90 63.6 4.66 2.03 50.3 5.09 2.11 51.1 5.51 2.19 51.9 5.96 2.27 52.7 6.42 2.36 53.5 6.90 2.44 54.4 7.39 2.52 55.4 4.33 2.07 54.0 4.74 2.16 54.8 5.15 2.25 55.6 5.58 2.34 56.4 6.02 2.43 57.2 6.47 2.52 58.1 6.95 2.61 59.1 4.00 2.10 57.7 4.39 2.20 58.5 4.78 2.30 59.3 5.20 2.39 60.1 5.62 2.49 60.9 6.06 2.59 61.8 6.52 2.69 62.7 3.67 2.12 61.4 4.05 2.23 62.2 4.43 2.33 62.9 4.82 2.44 63.7 5.23 2.54 64.6 5.65 2.65 65.4 6.08 2.76 66.3 3.36 2.13 65.1 3.71 2.25 65.9 4.07 2.36 66.6 4.45 2.47 67.4 4.84 2.59 68.2 5.24 2.70 69.0 5.65 2.82 69.9 6.83 2.88 47.1 7.47 2.99 47.6 8.11 3.10 48.1 8.78 3.21 48.7 9.48 3.32 49.3 10.2 3.43 49.9 11.0 3.54 50.5 6.36 2.95 51.0 6.98 3.07 51.5 7.60 3.19 52.0 8.24 3.31 52.6 8.91 3.43 53.2 9.60 3.55 53.8 10.3 3.68 54.5 5.88 3.00 55.0 6.49 3.13 55.4 7.09 3.27 55.8 7.71 3.40 56.4 8.36 3.53 57.0 9.02 3.66 57.6 9.72 3.80 58.3 5.41 3.04 58.9 6.00 3.19 59.3 6.58 3.33 59.7 7.18 3.47 60.2 7.80 3.62 60.8 8.44 3.76 61.4 9.11 3.90 62.1 4.95 3.07 62.9 5.51 3.23 63.2 6.07 3.38 63.5 6.66 3.54 64.0 7.25 3.69 64.6 7.87 3.85 65.2 8.51 4.00 65.8 38CKC018-74 –2 0 2 4 6 8 10 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 4.80 1.24 28.5 5.22 1.27 28.4 5.64 1.30 28.4 6.07 1.32 28.4 6.53 1.35 28.4 6.99 1.37 28.4 7.47 1.40 28.3 4.52 1.30 33.1 4.93 1.33 33.1 5.34 1.36 33.1 5.77 1.39 33.2 6.22 1.42 33.3 6.67 1.45 33.4 7.14 1.48 33.5 4.22 1.34 37.6 4.63 1.38 37.6 5.03 1.41 37.6 5.45 1.45 37.7 5.89 1.48 37.9 6.34 1.52 38.1 6.80 1.55 38.2 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 6.03 1.77 35.1 6.52 1.82 35.9 7.02 1.88 36.7 7.53 1.93 37.5 8.07 1.98 38.4 8.62 2.04 39.3 9.19 2.10 40.3 5.69 1.85 38.9 6.16 1.91 39.7 6.64 1.97 40.5 7.14 2.03 41.4 7.65 2.09 42.3 8.18 2.15 43.2 8.74 2.21 44.1 5.34 1.92 42.7 5.80 1.98 43.5 6.26 2.05 44.3 6.74 2.12 45.2 7.24 2.19 46.1 7.75 2.25 47.0 8.29 2.32 47.9 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 8.75 2.48 30.9 9.48 2.55 31.4 10.2 2.62 31.9 11.0 2.69 32.4 11.8 2.76 32.9 12.6 2.83 33.5 13.4 2.90 34.0 8.26 2.60 35.1 8.97 2.68 35.6 9.68 2.76 36.1 10.4 2.83 36.6 11.2 2.91 37.1 12.0 2.99 37.7 12.8 3.07 38.3 7.78 2.70 39.1 8.47 2.79 39.6 9.16 2.88 40.1 9.88 2.97 40.7 10.6 3.06 41.2 11.4 3.15 41.8 12.2 3.24 42.5 3.92 1.38 41.9 4.32 1.42 41.9 4.72 1.46 42.0 5.13 1.50 42.1 5.56 1.54 42.3 6.00 1.58 42.5 6.45 1.62 42.8 38CKC024-74 –2 0 2 4 6 8 10 5.00 1.98 46.5 5.44 2.05 47.3 5.89 2.13 48.1 6.35 2.20 48.9 6.83 2.27 49.8 7.32 2.35 50.7 7.84 2.43 51.7 38CKC036-74, 94 –2 0 2 4 6 8 10 7.30 2.80 43.1 7.97 2.89 43.6 8.63 2.99 44.1 9.33 3.09 44.7 10.0 3.19 45.3 10.8 3.29 45.9 11.6 3.39 46.5 See notes on pg. 14. 13 Condenser only ratings (S.I.) continued CONDENSER ENTERING AIR TEMPERATURES °C SST °C 20 24 28 32 36 40 44 48 52 10.0 4.15 50.4 10.9 4.24 51.2 11.8 4.34 52.0 12.7 4.44 52.9 13.6 4.54 53.7 14.5 4.64 54.5 15.4 4.74 55.3 9.58 4.42 54.5 10.4 4.52 55.3 11.3 4.63 56.1 12.2 4.74 56.9 13.0 4.84 57.7 13.9 4.95 58.5 14.8 5.06 59.3 9.15 4.71 58.6 9.99 4.83 59.4 10.8 4.94 60.2 11.7 5.05 61.0 12.5 5.17 61.8 13.3 5.28 62.6 14.2 5.39 63.4 8.76 5.02 62.5 9.56 5.14 63.3 10.4 5.26 64.2 11.2 5.38 65.0 12.0 5.51 65.8 12.8 5.63 66.6 13.6 5.75 67.4 8.42 5.34 66.3 9.17 5.47 67.2 9.93 5.60 68.0 10.7 5.73 68.9 11.4 5.86 69.7 12.2 5.99 70.6 12.9 6.12 71.4 13.3 4.88 51.2 14.2 4.97 51.9 15.2 5.06 52.6 16.1 5.16 53.4 17.1 5.27 54.2 18.2 5.39 55.1 19.3 5.51 55.9 12.8 5.29 55.3 13.6 5.39 56.0 14.5 5.49 56.8 15.5 5.59 57.5 16.5 5.71 58.3 17.5 5.82 59.2 18.5 5.95 60.0 12.2 5.72 59.3 13.1 5.83 60.0 13.9 5.94 60.8 14.8 6.06 61.6 15.8 6.18 62.4 16.7 6.30 63.3 17.7 6.43 64.1 11.7 6.17 63.2 12.5 6.29 64.0 13.3 6.41 64.8 14.2 6.54 65.6 15.1 6.67 66.5 16.0 6.80 67.3 16.9 6.93 68.1 11.1 6.63 67.0 11.9 6.76 67.9 12.7 6.89 68.7 13.5 7.02 69.5 14.4 7.16 70.4 15.2 7.31 71.3 16.1 7.46 72.2 38CKC048-94 –2 0 2 4 6 8 10 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 11.7 3.18 33.9 12.7 3.25 34.7 13.6 3.32 35.5 14.6 3.40 36.3 15.6 3.47 37.1 16.6 3.54 37.8 17.6 3.61 38.6 11.3 3.41 38.1 12.2 3.48 38.9 13.2 3.56 39.7 14.2 3.64 40.5 15.1 3.71 41.3 16.1 3.79 42.1 17.1 3.87 42.9 10.9 3.64 42.2 11.8 3.73 43.0 12.8 3.81 43.8 13.7 3.90 44.6 14.6 3.98 45.4 15.6 4.06 46.2 16.5 4.15 47.0 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 15.4 3.48 34.6 16.4 3.56 35.3 17.4 3.64 36.0 18.5 3.73 36.8 19.7 3.83 37.6 20.9 3.93 38.5 22.1 4.04 39.3 14.9 3.78 38.7 15.9 3.86 39.5 16.9 3.95 40.2 18.0 4.04 41.0 19.1 4.14 41.8 20.2 4.25 42.6 21.4 4.36 43.5 14.4 4.12 42.9 15.3 4.21 43.6 16.3 4.30 44.4 17.4 4.39 45.1 18.4 4.49 46.0 19.6 4.60 46.8 20.7 4.72 47.7 10.5 3.89 46.4 11.4 3.98 47.2 12.3 4.07 48.0 13.2 4.16 48.8 14.1 4.25 49.6 15.0 4.35 50.4 16.0 4.44 51.2 38CKC060-94 –2 0 2 4 6 8 10 SST TCG KW SDT 14 — Saturated Temperature Entering Compressor (°C) — Gross Cooling Capacity (Kw) — Total Power (Kw) — Saturated Temperature Leaving Compressor (°C) 13.8 4.49 47.0 14.8 4.58 47.8 15.8 4.67 48.5 16.7 4.77 49.3 17.8 4.87 50.1 18.9 4.98 50.9 20.0 5.10 51.8 Condenser only ratings (English) CONDENSER ENTERING AIR TEMPERATURES °F SST °F 55 65 75 85 95 105 115 125 13.2 1.43 113.0 15.1 1.49 113.0 17.0 1.55 114.0 19.0 1.61 114.0 21.1 1.68 115.0 23.3 1.73 116.0 11.8 1.47 124.0 13.6 1.54 124.0 15.4 1.62 124.0 17.4 1.69 125.0 19.4 1.76 126.0 21.5 1.83 127.0 10.4 1.50 134.0 12.1 1.58 134.0 13.9 1.67 134.0 15.7 1.75 135.0 17.7 1.83 136.0 19.7 1.91 137.0 9.11 1.52 144.0 10.6 1.61 144.0 12.3 1.70 145.0 14.1 1.80 145.0 15.9 1.89 146.0 17.9 1.99 147.0 16.8 2.05 121.0 18.9 2.17 123.0 21.0 2.28 125.0 23.2 2.39 128.0 25.6 2.50 130.0 28.1 2.62 132.0 15.2 2.12 131.0 17.2 2.24 133.0 19.2 2.37 135.0 21.3 2.50 137.0 23.5 2.62 139.0 25.8 2.75 142.0 13.6 2.16 140.0 15.5 2.30 142.0 17.4 2.44 144.0 19.3 2.58 146.0 21.4 2.73 148.0 23.6 2.87 151.0 12.1 2.18 149.0 13.8 2.34 151.0 15.6 2.50 153.0 17.4 2.65 155.0 19.4 2.81 157.0 21.5 2.97 160.0 24.7 2.91 115.0 27.7 3.06 117.0 30.9 3.21 118.0 34.3 3.35 120.0 37.9 3.50 121.0 41.7 3.66 123.0 22.4 3.01 125.0 25.3 3.18 126.0 28.4 3.35 128.0 31.6 3.52 129.0 34.9 3.69 131.0 38.5 3.87 133.0 20.1 3.09 135.0 22.9 3.28 136.0 25.8 3.47 137.0 28.9 3.66 139.0 32.1 3.86 141.0 35.4 4.05 142.0 17.9 3.14 145.0 20.5 3.35 146.0 23.3 3.57 147.0 26.2 3.78 148.0 29.2 4.00 150.0 32.4 4.21 152.0 35.9 4.12 122.0 40.2 4.26 124.0 44.4 4.39 126.0 48.7 4.53 128.0 53.0 4.66 130.0 57.4 4.80 132.0 33.8 4.50 132.0 37.9 4.65 134.0 42.0 4.80 136.0 46.1 4.95 138.0 50.1 5.10 140.0 54.4 5.26 142.0 31.7 4.92 142.0 35.6 5.08 144.0 39.5 5.25 146.0 43.3 5.41 148.0 47.2 5.57 150.0 51.3 5.75 152.0 30.0 5.37 152.0 33.6 5.55 154.0 37.2 5.73 156.0 40.7 5.91 158.0 44.3 6.09 160.0 48.2 6.28 162.0 38CKC018-74 30 35 40 45 50 55 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 18.7 1.15 67.5 20.7 1.18 66.9 22.8 1.20 66.2 25.1 1.23 65.2 27.3 1.26 65.4 29.7 1.29 65.6 17.4 1.23 79.8 19.4 1.27 79.6 21.5 1.30 79.5 23.7 1.33 79.4 25.9 1.37 79.1 28.3 1.40 78.6 16.1 1.31 91.4 18.0 1.35 91.4 20.0 1.39 91.6 22.2 1.43 91.8 24.4 1.47 92.0 26.7 1.52 92.3 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 23.5 1.64 83.2 26.0 1.69 85.1 28.6 1.75 87.3 31.3 1.81 89.5 34.1 1.87 91.8 37.1 1.93 94.3 21.8 1.76 92.9 24.2 1.83 94.9 26.7 1.90 97.0 29.3 1.97 99.3 32.0 2.05 102.0 34.8 2.12 104.0 20.2 1.87 103.0 22.4 1.96 105.0 24.8 2.04 107.0 27.2 2.12 109.0 29.8 2.21 111.0 32.6 2.30 114.0 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 34.0 2.28 74.2 37.6 2.36 75.3 41.4 2.43 76.4 45.4 2.51 77.5 49.6 2.59 78.7 54.1 2.67 79.9 31.7 2.46 84.9 35.2 2.55 86.1 38.8 2.65 87.3 42.7 2.74 88.6 46.8 2.83 90.0 51.0 2.93 91.4 29.3 2.63 95.3 32.7 2.74 96.6 36.2 2.85 97.9 39.9 2.96 99.3 43.8 3.07 101.0 47.9 3.18 102.0 TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 43.7 2.84 80.0 48.5 2.92 81.9 53.3 3.00 83.8 58.1 3.09 85.6 62.8 3.17 87.5 67.9 3.26 89.5 41.9 3.12 90.5 46.6 3.21 92.5 51.3 3.31 94.5 55.9 3.41 96.4 60.6 3.50 98.4 65.5 3.60 100.0 40.0 3.43 101.0 44.6 3.54 103.0 49.1 3.65 105.0 53.7 3.75 107.0 58.2 3.86 109.0 63.0 3.97 111.0 14.6 1.38 103.0 16.6 1.43 103.0 18.5 1.48 103.0 20.6 1.53 103.0 22.8 1.58 104.0 25.0 1.63 104.0 38CKC024-74 30 35 40 45 50 55 18.5 1.97 112.0 20.6 2.07 114.0 22.9 2.17 116.0 25.2 2.26 118.0 27.7 2.36 121.0 30.3 2.47 123.0 38CKC036-74, 94 30 35 40 45 50 55 27.0 2.78 105.0 30.2 2.91 107.0 33.6 3.04 108.0 37.1 3.17 110.0 40.9 3.30 111.0 44.8 3.43 113.0 38CKC048-94 30 35 40 45 50 55 38.1 3.77 111.0 42.5 3.89 113.0 46.9 4.01 115.0 51.3 4.13 117.0 55.7 4.25 119.0 60.3 4.37 122.0 See notes on pg. 16. 15 Condenser only ratings (English) continued CONDENSER ENTERING AIR TEMPERATURES °F SST °F 55 65 75 85 95 105 115 125 47.3 4.81 123.0 51.7 4.94 125.0 56.3 5.08 127.0 61.2 5.23 129.0 66.3 5.40 131.0 71.6 5.57 133.0 44.6 5.39 133.0 48.8 5.53 135.0 53.2 5.68 137.0 57.9 5.84 139.0 62.8 6.01 141.0 67.8 6.19 143.0 41.9 6.00 143.0 45.9 6.17 145.0 50.1 6.34 147.0 54.5 6.51 149.0 59.1 6.68 151.0 63.9 6.87 153.0 39.2 6.65 153.0 43.0 6.83 155.0 46.9 7.01 157.0 51.0 7.21 159.0 55.3 7.42 161.0 59.8 7.62 164.0 38CKC060-94 30 35 40 45 50 55 SST TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT TCG KW SDT 57.0 3.02 81.1 62.2 3.12 82.9 67.6 3.25 84.9 73.3 3.38 86.9 79.3 3.52 89.0 85.6 3.67 91.3 54.7 3.39 91.7 59.7 3.50 93.5 64.9 3.63 95.4 70.5 3.76 97.5 76.3 3.91 99.7 82.3 4.07 102.0 52.3 3.81 102.0 57.1 3.93 104.0 62.2 4.06 106.0 67.5 4.20 108.0 73.1 4.35 110.0 78.8 4.51 112.0 49.8 4.28 112.0 54.4 4.41 114.0 59.3 4.54 116.0 64.4 4.69 118.0 69.8 4.85 121.0 75.3 5.01 123.0 — Saturated Temperature Entering Compressor (°F) — Gross Cooling Capacity (1000 Btuh) — Total Power (Kw) — Saturated Temperature Leaving Compressor (°F) System Design Summary 1. 2. 3. 4. 5. 6. 7. 8. 9. 16 Intended for outdoor installation with free air inlet and outlet.Outdoor an external static pressure available is less than 0.01-in. wg. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C). Maximum outdoor operating air temperature is 125°F (51°C). For reliable operation, unit should be level in all horizontal planes. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above + 50 ft (15.24m), indoor coil below = 150 ft (45.72m). (See items 6 and 7 following.) For interconnecting refrigerant tube lengths between 50 ft (15.24m) and 175 ft (53.3m), consult Residential Split-System Long-Line Application Guideline available from equipment distributor. Crankcase heater required when interconnection refrigerant tube length exceeds 50 ft (15.24m) If any refrigerant tubing is buried, provide a minimum 6 in. (152mm) vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. (912mm) may be buried without further consideration. For buried lines longer than 3 ft. (912mm) consult your local distributor. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided. Guide specifications GENERAL System Description Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit. Quality Assurance Unit shall be manufactured in a facility registered to ISO9001/BS5750 Part II, International Standard for quality systems. Unit will be rated in accordance with the latest edition of ARI Standard 210. Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC (U.S.A. Standard). Unit will be constructed in accordance with UL standards. Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test (U.S.A. Standard). Air-cooled condenser coils will be leak tested at 150 psig (1034 KPa) and pressure tested at 300 psig (2068 KPa). Delivery, Storage, and Handling Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations. PRODUCTS Equipment Factory assembled, single piece, air-cooled condensing unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge (R-22), and special features required prior to field start-up. Unit Cabinet Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint. Fans Condenser fan will be direct-drive propeller type, discharging air upward. Air-Cooled, Split-System Air Conditioner 38CKC 1-1/2 to 5 Tons Nominal (5.2 to 17.5 Kw) Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings. Shafts will be corrosion resistant. Fan blades will be statically and dynamically balanced. Condenser fan openings will be equipped with PVC-coated steel wire safety guards. Compressor Compressor will be hermetically sealed. Compressor will be mounted on rubber vibration isolators. Condenser Coil Condenser coil will be air cooled. Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components Refrigeration circuit components will include liquid line shutoff valve with sweat connections, suction shutoff valves with sweat connections, system charge of refrigerant R-22, and compressor oil. Operating Characteristics The capacity of the unit will meet or exceed _____ Btuh (kw) at a suction temperature of _____ °F (°C). The power consumption at full load will not exceed _____ kw. Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh (kw) or greater at conditions of _____ CFM (L/S) entering air temperature at the evaporator at _____ °F (°C) wet bulb and _____ °F (°C) dry bulb, and air entering the unit at _____ °F (°C). Electrical Requirements Nominal unit electrical characteristics will be _____ v, __ phase, 50 hertz. The unit will be capable of satisfactory operation within voltage limits of _____ v to _____ v. Unit electrical power will be single point connection. Control circuit will be 24v. Special Features Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements. 17 18 19 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training A94328 Carrier Corporation • Indianapolis, IN 46231 1-99 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 2 4 Tab 3a 1a 2a Page 20 Catalog No. 003-839 Printed in U.S.A. PC 101 Form 38CKC-C3PD Replaces: 38CKC-C2PD
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.1 Linearized : No Page Count : 20 Create Date : 1999:02:19 11:37:20 Producer : Acrobat Distiller 2.0 for WindowsEXIF Metadata provided by EXIF.tools