K14175V1 C_7847i Ii 7847i Honeywell Internet Alarm Communicator Installation And Setup Guide

User Manual: 7847i-honeywell-internet-alarm-communicator-installation-and-setup-guide

Open the PDF directly: View PDF PDF.
Page Count: 64

DownloadK14175V1-C_7847i-ii 7847i-honeywell-internet-alarm-communicator-installation-and-setup-guide
Open PDF In BrowserView PDF
AlarmNet 7847i/7847i-E
Internet/Intranet Communication Modules
With Remote Services

Installation and Setup Guide

Requires
Compass Version
1.5.8.54A (or higher)
for IP Downloading

K14175V1

9/10 Rev C

Table of Contents
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

SECTION 1: General Information ........................................................................................................... 1-1
Introduction ............................................................................................................................................................... 1-1
System Features ......................................................................................................................................................... 1-1
About Private Network Application .......................................................................................................................... 1-1
About AlarmNet-i Internet Application..................................................................................................................... 1-2
Encryption ................................................................................................................................................................. 1-2
Enterprise Encryption Related Functions .................................................................................................................. 1-2
Installation Key (for Private LAN) ............................................................................................................................ 1-2
Recovery Mode ......................................................................................................................................................... 1-3
Remote Services ........................................................................................................................................................ 1-3
Modes of Operation ................................................................................................................................................... 1-3
ECP Mode ................................................................................................................................................... 1-3
Zone Trigger Mode ..................................................................................................................................... 1-3
4204 Mode and Two-4204 Mode ................................................................................................................ 1-4
Module Supervision Features .................................................................................................................................... 1-4
Specifications ............................................................................................................................................................ 1-4
Mechanical .................................................................................................................................................. 1-4
Electrical ..................................................................................................................................................... 1-4
Ethernet ....................................................................................................................................................... 1-4
Environmental ............................................................................................................................................. 1-4
ULC Compatibility .................................................................................................................................................... 1-5
SECTION 2: Mounting and Wiring .......................................................................................................... 2-1
Mounting the 7847i/7847i-E ..................................................................................................................................... 2-1
Wiring the 7847i/7847i-E .......................................................................................................................................... 2-2
Wiring for ECP, 4204 and Two-4204 Modes ............................................................................................. 2-2
Wiring for Zone Trigger Mode ................................................................................................................... 2-3
Power Connections and Options................................................................................................................................ 2-4
Ethernet Connections................................................................................................................................................. 2-4
Initial Power-Up Sequence.......................................................................................................................... 2-5
SECTION 3: Programming the 7847i/7847i-E ....................................................................................... 3-1
General Information .................................................................................................................................................. 3-1
Using the AlarmNet Direct Website ........................................................................................................... 3-1
Using a 7720P Programming Tool .............................................................................................................. 3-2
Using the Control Panel Programming Mode ............................................................................................. 3-2
Programming Conventions .......................................................................................................................... 3-2
ECP Mode Programming .......................................................................................................................................... 3-3
ECP Status Codes ................................................................................................................................................ 3-9
Alternative Modes (Zone Trigger, 4204 and Two-4204) .......................................................................................... 3-9
Zone Trigger Mode ..................................................................................................................................... 3-9
4204 Emulation Mode ................................................................................................................................. 3-9
4204 Emulation Mode Options ................................................................................................................... 3-9
Alternative Mode Programming .............................................................................................................................. 3-10
Exiting Programming Mode .................................................................................................................................... 3-20
Setting Factory Defaults .................................................................................................................................... 3-20
SECTION 4: Registration .......................................................................................................................... 4-1
Registering the 7847i/7847i-E ................................................................................................................................... 4-1
i

7847i/7847i-E Installation and Setup Guide
Registering through AlarmNet Direct Website (does not apply if using Private LAN) .............................. 4-1
Using the Tamper Switch ............................................................................................................................ 4-2
Using the Programming Tool ...................................................................................................................... 4-2
Register by Phone ....................................................................................................................................... 4-4
SECTION 5: Programmer Keyboard Commands................................................................................. 5-1
Programmer Keyboard Commands ........................................................................................................................... 5-1
System Status Displays ............................................................................................................................... 5-2
SECTION 6: Network Diagnostics........................................................................................................... 6-1
Running Network Diagnostics on the 7847i/7847i-E using AlarmNet ..................................................................... 6-1
Possible Errors Running Network Diagnostics ........................................................................................... 6-2
Running Network Diagnostics on the 7847i-E using a Private LAN ........................................................................ 6-3
Possible Errors Running Network Diagnostics using a Private LAN ......................................................... 6-4
Appendices ................................................................................................................................................... A-1
Appendix A : Summary of LED Operation ...............................................................................................................A-1
Status Display Operation .............................................................................................................................A-1
Network Connectivity Display ....................................................................................................................A-3
Mode and Status LED Display ....................................................................................................................A-4
Mode and Status Indicator Switch...............................................................................................................A-4
Appendix B : Central Station Messages .................................................................................................................... B-1
Appendix C : IP Downloading .................................................................................................................................. C-1
General Information .................................................................................................................................... C-1
Direct Wire Setup ........................................................................................................................................ C-1
Appendix D : Glossary ..............................................................................................................................................D-1
Summary of Connections Diagram…………………………………………………………..……….Inside Back Cover

ii

S E C T I O N

1

General Information
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section
♦ Introduction
♦ System Features
♦ About Private Network Application
♦ About AlarmNet-i Internet Application
♦ Encryption
♦ Enterprise Related Encryption Functions

♦
♦
♦
♦
♦

Installation Key
Recovery Mode
Remote Services
Modes of Operation
Specifications

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Introduction
AlarmNet’s 7847i Internet Communication Module and 7847i-E Internet/Intranet Communication Module were developed to transport alarm signals via the Internet or Private LAN
(7847i-E only). These easy-to-install devices provide sophisticated data security and
communicate with all AlarmNet central stations through AlarmNet’s server, or directly to a
7810PC or 7810iR-ent Internet/Intranet receiver in a private network application (7847i-E).
In addition to alarm reporting, the 7847i and 7847i-E provide upload/downloading capability
via the internet or a Private LAN (7847i-E only).

UL

The 7847i-E is not UL Listed.

System Features
Basic features of the 7847i and 7847i-E include:
•

Easy CAT-5 10 BaseT connection to a hub or router

•

Installs behind firewalls without compromising network security

•

Supports dynamic or static IP addressing

•

Quick connection to compatible Honeywell series control panels

•

Simple programming using a 7720P programming tool or AlarmNet Direct website

•

Reports fire, burg, and status messages via the Internet (or Intranet for 7847i-E)

•

Allows uploading and downloading of control panel data over the Internet (or Intranet for
7847i-E)

•

Supports remote control of alarm systems via Remote Access feature, and email notification
of events via Multi-Mode feature (Web Service)

About Private Network Application
The 7847i-E may be configured to transmit signals within a private network application to a
7810PC or 7810iR-ent receiver. Up to 300 7847i-E Internet/Intranet Communication
Modules may be routed to a single 7810PC or 7810iR-ent receiver. In a private network
application, the signals are not routed to the AlarmNet Control Center (see Figure 1).

1-1

7847i/7847i-E Installation and Setup Guide
INTRANET

MAS

7810iR-ent

ETHERNET PORT

INTERNET

LAN
(CENTRAL STATION,
BANK, ETC.)

CELL
ROUTER

INTERNET

ALARMNET

ALARMNET - i

7847i-E
7847i-E-031-V0

Figure 1. 7810PC or 7810iR-ent/7847i-E Intranet/Internet Block Diagram
The 7847i/7847i-E module requires an AlarmNet–i account. For new installations, please
obtain the account information from the central station prior to programming this module.
For replacement installations, the AlarmNet-i account is created automatically when the
module is registered (based on the existing account).

About AlarmNet-i Internet Application
AlarmNet-i is a fully encrypted, secure method of delivering alarm messages from a
protected premise to an AlarmNet equipped central station. An Internet Communicator
Module transmits status, supervisory, and alarm messages to the AlarmNet Control Center
using a broadband Internet connection (see Figure 1).
The AlarmNet Control Center identifies, validates, and forwards the messages to the
appropriate AlarmNet central station. An Internet receiver, 7810PC or 7810iR-ent, is
required when receiving Internet signals from the AlarmNet Control Center. AlarmNet-i
has an unlimited account capacity.

Encryption
The 7847i/7847i-E and 7810PC or 7810iR-ent support private key encryption. Private key
encryption means that both the sender and the receiver know the KEY used to encrypt the
data. Each device produced by Honeywell is loaded with a globally unique identifier called a
MAC number, and a large random number or KEY. This KEY and MAC number are also
stored in the AlarmNet servers. When a device contacts AlarmNet it sends the MAC number
in the clear followed by the message that is encrypted using the KEY data. The server looks
up its copy of the KEY based on the MAC number and uses that KEY to decrypt the
message.
The communication devices use 256 bit AES (Rijndael) encryption (which is required for
certain government installations). The AlarmNet-i AES Encryption Software Module
Version 1.0 contained in the Honeywell products has NIST approval. Listings for this
approval can be found at http://csrc.nist.gov/cryptval/aes/aesval.html Certification
number 127.

Enterprise Encryption Related Functions
The previous paragraph described general encryption, and how it functions with AlarmNet.
When used in a Private closed network or Enterprise installations, some additional processes
are required to support encryption. In an enterprise installation the 7810PC or 7810iR-ent
takes on the server function that exists in the AlarmNet Internet installation and has a
process to learn the MAC numbers and KEYs for which it will be responsible.

Installation Key (for Private LAN)
At installation a 10-digit installation key needs to be programmed into every device in the
network. This 10-digit key should be the same for all devices used in the Private LAN mode.
The purpose of this key is to encrypt the private KEY of each subscriber device as it is
registered to the 7810PC or 7810iR-ent so this sensitive data is never sent in the clear. This
KEY is only used for registration purposes and is not used for supervision or alarm
1-2

Section 1: General Information
transmission. Once a device is registered the 7810iR-ent will have a copy of the 7847i-E’s
factory KEY. From this point on the unique factory key is used for communications.

Recovery Mode
Recovery Mode is only available when in Private LAN mode. In the event of a failure of the
7810PC or 7810iR-ent requiring the replacement of the hardware or the erasure of its
memory, the 7810PC or 7810iR-ent supports a Recovery Mode. In Recovery Mode, the
7810PC or 7810iR-ent is programmed with the same 10-digit installation key. When a
7847i-E communicates with the 7810PC or 7810iR-ent and is found not to exist in its
database, a special response is sent back to the 7847i-E requesting it to re-register itself.
The 7847i-E then registers using the 10-digit installation key. When all accounts have been
recovered, Recovery Mode can be turned off to provide better control of registration.

Remote Services

UL

Remote Access and Multi-Mode have not been evaluated by UL.

Honeywell now offers a new series of web based services that provides consumers with the
ability to communicate with their security system remotely in a number of ways. These new
web services will allow users to:
•

Access their security system from a computer via a website (Remote Access feature)

•

Receive email and text message notifications of system events (Multi-Mode feature)

•

Perform system functions and receive confirmations using text messages (SMS feature)

Dealers will initially enroll their customers for web services during account programming
through the AlarmNet Direct website. The features that can be enabled include Remote
Access and Multi-Mode. Once enabled, the specific programming fields associated with these
features can be programmed into the communications device either remotely using the
AlarmNet Direct website or locally using the 7720P programming tool.

Modes of Operation

ULC

Only ECP Mode has been approved for ULC installations.

The 7847i and 7847i-E provide four modes of operation so they can be used with various
types of control panels, as summarized below:
ECP Mode
•

This mode is for use with Honeywell controls that support LRR-ECP communication

•

The module connects to the control’s keypad terminals and provides 2-way communication
with the control using ECP messaging

•

The control treats the module as a Long Range Radio (LRR) device, so program the control
accordingly, including setting the module’s proper LRR device address

•

Panel-generated reports are sent in Contact ID format

•

The module also supports two hardwire zone trigger inputs (zones 6 and 7) – these report in
ADEMCO High-Speed format

Zone Trigger Mode
•

This mode is for use with controls that do not support LRR-ECP communication nor 4204
Relay Modules

•

The module provides six input zones

•

Each zone can be configured for +V, -V, or EOLR triggering

•

Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting

1-3

7847i/7847i-E Installation and Setup Guide
•

Zone 1 and 2 inputs can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively

•

Zone 1 and 2 inputs can also be programmed to report LYNX panic (if used with LYNX
control)

•

Reports are sent in ADEMCO High-Speed format

4204 Mode and Two-4204 Mode
•

This mode is for use with Honeywell controls that do not support LRR-ECP communication,
but that do support 4204 Relay Modules

•

The module connects to the control’s keypad terminals

•

The control treats the module as 4204 Relay Module(s), so program the control accordingly,
including setting the module’s proper 4204 device address

•

4204 mode provides up to four zone inputs, plus two optional trigger zones, depending on
options programmed

•

Two-4204 mode provides up to eight zone inputs, depending on options programmed

•

Each 4204 zone can be programmed for delayed reporting and restoral reporting

•

Reports are sent in ADEMCO High-Speed format

Module Supervision Features
The 7847i/7847i-E provides the following types of supervision and module fault detection:
•

Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the module within a specified time (“Supervision” option),
AlarmNet notifies the central station of a communication failure.

•

Fault output: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
If used, the fault relay will trip when the following conditions occur; tamper*, loss of network
connectivity*, the device is not registered and the device is remotely disabled by AlarmNet.
* Alarm reporting for the noted condition must be enabled for it to trigger the fault relay.

•

Cover tamper condition (“Tamper Rpt” option).

Specifications
Mechanical
Dimensions: 8.4" x 8.0" x 1.5"
Weight: 1 lb.
Electrical
Input Power: 12VDC
Current Drain: 20mA average standby, 75mA peak transmit
Radio Fault Output: Open collector
Input Trigger Levels: (V+) 2V – 14V, (V-) 0V – 1V
Ethernet
Network Standard: IEEE 802.3u compliant
Data Rate: 10Base-T / 100Base-T with auto detect
Ethernet Cable: Cat. 5 (min.), MDI/MDI-X auto crossover
Environmental
Operating temperature: –20º to +55ºC
Storage temperature: –40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
1-4

Section 1: General Information

ULC Compatibility
Model 7847i has only been evaluated for communication with Listed Model 7810PC or
7810iR-ENT internet receiver in combination with Listed Honeywell Model MX8000 or
Silent Knight Model 9500 central station receiver.

1-5

7847i/7847i-E Installation and Setup Guide

1-6

S E C T I O N

2

Mounting and Wiring
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section
♦ Mounting the 7847i/7847i-E

♦ Power Connections and Options

♦ Wiring the 7847i/7847i-E

♦ Ethernet Connections

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Mounting the 7847i/7847i-E
The 7847i/7847i-E must be mounted indoors. To mount the unit, see Figure 2 and complete
the following steps:
1. Unpack the unit and detach the case back by pushing up into the two tabs located at the
bottom of the 7847i/7847i-E module with the blade of a screwdriver while pulling the
case back and case front apart.
2. Locate the case back over the mounting surface such that the opening in the case back is
aligned with the wire/cable access opening (in the mounting surface) while passing the
wires/cable through the opening in the case back, or through the removable knockouts
located on the bottom of the back cover.
3. Secure the case back to the mounting surface using four screws (supplied).
4.

When all wiring is completed, attach the case front of the unit to the case back. Attach
the top first then press the bottom section inward until it snaps into place securely.
Secure bottom using cover securing screw (supplied) as shown below, (required for UL
installations).

5. Twist and remove cap from handle (supplied) and discard handle. Insert cap in top hole
of case back, as shown.
PRESS CAP
INTO PLACE
CASE
BACK

MOUNTING
SCREW (4)
(TYP)

OPTIONAL WIRING
KNOCKOUT
CASE
FRONT

OPTIONAL WIRING
KNOCKOUTS
TAB
TAB
CAP
(TWIST OFF)

COVER SECURING SCREW

7847i-E-022-V1

Figure 2. Mounting the 7847i/7847i-E
2-1

7847i/7847i-E Installation and Setup Guide

Wiring the 7847i/7847i-E
Unshielded, 22 AWG cable is recommended for 7847i/7847i-E power/data wires.

ULC

For ULC Household Fire and Burglary installations, use ECP wiring only.

Wiring for ECP, 4204 and Two-4204 Modes
Most Honeywell ADEMCO control panels support LRR-ECP data communication, (e.g.,
VISTA-10P, VISTA-15P, VISTA-20P, LynxR-I, VISTA-128BP/250BP and the
VISTA-128FBP/250FP). However, there are some panels that do not. Check the Installation
and Setup Guide for the control panel you are using to see if it supports ECP communication.
Connect the 7847i/7847i-E to a compatible Honeywell VISTA control panel's ECP terminals,
in parallel with keypads and other peripheral devices, VIP module, etc. Wire length/gauge
limitations are the same for the module as they are for keypads and other peripheral devices.
To wire the module for ECP communication, see Figure 3 and do the following:
Table 1. Wiring connections for ECP or 4204 modes
7847i/7847i-E

Control

Terminal 3 V+

+12 V Aux

Terminal 4 GND

Ground

Terminal 5 Data In

Data Out

Terminal 6 Data Out

Data In

TB1
+12 V
GND
DATA OUT
DATA IN

RED
BLK
YEL
GRN

3

V+

4

GND

5

ECP DATA IN

6

ECP DATA OUT

CONTROL PANEL

7847i / 7847i-E

7847i-E-019-V0

Figure 3. Wiring a Vista for ECP Mode or 4204 Modes
To install a 7847i/7847i-E with a LynxR-I Security System, wire the devices as shown in
Figure 4 below. Refer to LynxR-I Installation and Setup Guide.

2-2

4-WIRE CABLE (N4632-4)

TB1
RED
BLK

GRN

DATA IN

GND

NC

+12 VDC

DATA OUT

YEL

3

V+

4

GND

5

ECP DATA IN

6

ECP DATA OUT

LYNXR-I CONTROL PANEL

7847i-E-018-V0

BLK

GRN

YEL

RED

Section 2: Mounting and Wiring

7847i / 7847i-E

Figure 4. Wiring a LynxR-I for ECP Mode
Wiring for Zone Trigger Mode
To trip the zone on the 7847i/7847i-E in V+ trigger mode, the positive triggering voltage from
the control panel must be within 2.0V-14V.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip the zone on the 7847i/7847i-E in V- trigger mode, the negative triggering voltage
must be less than 1.0V.
NOTE: LynxR and LynxR-EN have a designated trigger for V- trigger.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control
panel to the zone input of the module, and connect a common ground between the module
and control panel.

UL

The configurations shown in Figures 5a and 5b have not been evaluated by UL.

Examples of zone connections are shown below:
TB1
+12 V

3

V+

GND

4

GND

BELL (+)

5

ZONE INPUT Z1/Z2

(+)
7847i-E-020-V0

( )
CONTROL PANEL

7847i / 7847i-E

Figure 5a. Wiring the 7847i/7847i-E Zone 1 Input for a Positive (+) Triggered Bell Output

TB1
+12 V

3

V+

GND

4

GND

BELL ( )

5

ZONE INPUT Z1/Z2

( )

(+)

7847i / 7847i-E

7847i-E-021-V0

CONTROL PANEL

Figure 5b. Wiring the 7847i/7847i-E Zone 1 Input for a Ground (-) Triggered Bell Output
2-3

7847i/7847i-E Installation and Setup Guide

TB1
1

NOT USED

2

NOT USED

4

GND

5

ZONE INPUT Z1/Z2

9
LRR / AAV
TRIGGER

2K EOL
RESISTOR

8

7847i / 7847i-E

7847i-E-024-V0

LYNXR/LYNXR-EN
CONTROL PANEL

Figure 6. Wiring the 7847i/7847i-E Zone 1 Input to a LynxR Trigger Output
TB1

2K EOL
RESISTOR

1

NOT USED

2

NOT USED

3

ECP (+) VOLTAGE INPUT

4

GND

5

ZONE INPUT Z1/Z2

N.O.

7847i / 7847i-E

7847i-E-028-V0

N.C.

Figure 7. Wiring the 7847i/7847i-E Zone 1 Input for EOL Supervised N.O./N.C. Triggers

Power Connections and Options
Primary power for the 7847i/7847i-E is provided by the auxiliary power output of the control
panel 9.6V –13.8V, typical, or other external power source.
When calculating the total load on the auxiliary power output of the control panel, 20mA
must be budgeted for the 7847i/7847i-E. Under normal operating conditions, the unit will
not pull more than 20mA; however, it will draw 75mA during a transmission.
Connect the wires from the (+) and (–) terminals of the DC power source to terminals V+ and
GND on TB1 of the 7847i/7847i-E. Observe Polarity!
If using an external power source, connect GND from power supply to GND of the control
panel.

Ethernet Connections

UL
•

2-4

1. For UL installations, the Cat. 5 Ethernet connections between the 7847i/7847i-E
and the router cannot exceed 12 feet with both the 7847i/7847i-E and the router
located within the same room.
2. Use a Listed cable/DSL router suited for the application.
Connect one end of the Ethernet cable (Category 5) to the 7847i-E's RJ45 Ethernet
connector and the other end to the cable/DSL router.

Section 2: Mounting and Wiring

Xmit
Shift

7720 PROGRAMMING TOOL

A

BS / ESC

B

1
/

F

6

5
T

S

X

8

7
Shift

3

E

4
N /Y

C

2

D

Space

9
Enter

0

#

TO
ROUTER
TB1
TAMPER
SWITCH/
IB SERVICE

7720P
PROGRAM
CONNECTOR
STATUS
LED
DISPLAY

MODE AND STATUS
LED DISPLAY

RJ45
ETHERNET
PORT
NETWORK
CONNECTIVITY
LED DISPLAY
MODE AND STATUS
INDICATOR SWITCH

7847i-E-016-V0

Figure 8. Ethernet Connections
Initial Power-Up Sequence
Before connecting power, check that the following have been completed:
•

Terminal block TB1 V+ and GND terminals are connected to the control panel's auxiliary
power output: 12 VDC nominal.

•

Power up the control panel.

Initially, all 7847i/7847i-E programming options are set to the factory default settings.
NOTE: Refer to Appendix A for detailed information on LED functions.

2-5

7847i/7847i-E Installation and Setup Guide

2-6

S E C T I O N

3

Programming the 7847i/7847i-E
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section

♦
♦
♦

General Information

♦ Alternative Mode Programming

ECP Mode Programming

♦ Exiting Programming Mode

Alternative Modes (Zone Trigger, 4204 and
Two-4204)

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

General Information
To the control panel, the 7847i/7847i-E Internet/Intranet Communication Modules, when in
ECP Mode, is treated as a long-range radio device.

The 7847i/7847i-E can be configured to deliver alarms via the Internet to an AlarmNet
central station or via a Private LAN (7847i-E only) directly to a 7810PC or 7810iR-ent
receiver. Both methods of communication are encrypted to ensure security. The 7847i and
7847i-E use 256-bit AES (Rijndael) encryption (which is required for certain government
installations).
The 7847i/7847i-E modules require an AlarmNet–i account, except when Private LAN is
enabled on the 7847i-E. Obtain the account information from the central station prior to
programming this module.

You can program a 7847i/7847i-E by one of the following methods:
•

Through the AlarmNet Direct website

•

Through use of a 7720P Programming Tool

•

Through a programming mode in control panel, on panels that support this option (e.g., Vista128BP and FBP)

Using the AlarmNet Direct Website
To program the module via the website (if you are already signed up for this service), go to:
https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
If you are not signed up for this service, click on “Dealer Sign-Up".
Log in and follow the on-screen prompts.
Please have the following information available when programming the module:
1. Primary City ID (two-digit hexadecimal number)
2. Primary Central Station ID (two-digit number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside
module)
After programming is complete, you must transfer the data to the module and the module
must be registered. Refer to Section 4: Registration, for further instructions.

3-1

7847i/7847i-E Installation and Setup Guide
Using a 7720P Programming Tool
Connect the 7720P Programming Tool; refer to Figure 8 in Section 2. The 7847i and 7847i-E
power the 7720P Programming Tool via the programming jack, and automatically senses the
presence of the 7720P when it is plugged in.
Each key of the 7720P has two possible functions: a normal function and a Shift function.
To perform a normal key function, simply press the desired key. To perform a Shift function,
press the [shift] key, and then press the appropriate key.
The prompts in this document reflect use of the 7720P Programming Tool. Table 2 below
lists each normal and shift key function.
Table 2. 7720P Normal and Shift Key (shift LED lit) Functions
KEY
BS/ESC

NORMAL KEY FUNCTION
[BS]: Press to delete entry

↓/↑
N/Y
SHIFT

[↓]: Scroll down programming
[↑]: Scroll up programming
[N]: Press for "NO" answer
[Y]: Press SHIFT-Y for "YES" answer
Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key
is pressed. Press again for each SHIFT function desired.
[1]: For entering the number 1
[A]: For entering letter A
[2]: For entering the number 2
[B]: For entering letter B
[3]: For entering the number 3
[C]: For entering letter C
[4]: For entering the number 4
[D]: For entering letter D
[5]: For entering the number 5
[E]: For entering letter E
[6]: For entering the number 6
[F]: For entering letter F
[7]: For entering the number 7
[S]: For entering letter S
[8]: For entering the number 8
[T]: For entering letter T
[9]: For entering the number 9
[X]: For entering letter X
[SPACE]: For scrolling option list
No SHIFT function
[0]: For entering the number 0
No SHIFT function
[#/ENTER]: Press to accept entries
No SHIFT function

1/A
2/B
3/C
4/D
5/E
6/F
7/S
8/T
9/X
SPACE
0
#/ENTER

SHIFT KEY FUNCTION
[ESC]: Press to quit program mode; also can reset
programming defaults*

* Active only when the "Exit Programming Mode" prompt is displayed.
Using the Control Panel Programming Mode
Some control panels support programming of the 7847i/7847i-E through the control panel
programming mode (e.g., Vista-128BP). If programming through the control panel, only the
ECP Mode programming options are available. The "mode" questions will not be displayed,
and the mode cannot be changed. For a description of key functions on the control panel
keypad, and how they map to the 7720P Programming tool, refer to the control panel's
Programming Guide.
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts
require only a [Y]es or [N]o response, while others require a numerical response (ID
numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an
invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the
current value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not
displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing
any values. Press the [ESC] key to go to the end of the list of questions.

3-2

Section 3: Programming the 7847i/7847i-E

ECP Mode Programming
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device
programming. If this has been done, the following prompt
appears:

Access to Prog
Mode Denied

NOTE: The default programming values for ECP mode are listed in each prompt below.

Table 3: Programming a 7847i-E for ECP mode only.
PROMPTS

ENTRY

OPTIONS

DESCRIPTION

1

Strt Prog Mode?
(Y/N)_

[Y], [N]

Enters programming mode.

2

Enter Password:

[0-9, A-F, N, S,
T, X, Y]

If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.

3

Program Device?
(Y/N)_

[Y], [N]

4

Create Password?
(Y/N)_

[Y], [N]

5

Change Password?
(Y/N)_

[Y], [N]

To begin programming the module, press [Y] and go to
Prompt 9: "Device Mode."
To create a password if none has been assigned, press
[N] and go to Prompt 4: "Create Password."
To change an existing password, press [N] and go to
Prompt 5: "Change Password."
Passwords can be used to protect account and
programming information.
If no password has been assigned, this prompt appears
after pressing [N] at the "Program Device?" prompt.
If a password is desired, press [Y] and go to Prompt 6:
"Enter Password."
If a password has already been assigned, this prompt
appears after pressing [N] at the "Program Device?"
prompt. Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering
a new one, answer [Y] to the "Change Password?"
prompt, then press the [Enter] key when prompted for
the new password and its confirmation.

6

Enter Password

[0-9, A-F, N, S,
T, X, Y]

This prompt is displayed if [Y] was pressed in Prompt 4
or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).

7

Verify Password

[0-9, A-F, N, S,
T, X, Y]

Re-enter the password as confirmation.
If the password doesn't match the first entry, the
following is displayed followed by the "Exit Prog.
Mode?" prompt:
Verify Not OK
PSWD not created

8

Exit Prog. Mode?
(Y/N)_

[Y], [N]
[ESC]

Otherwise, the "Exit Prog. Mode?" prompt is displayed
directly.
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in
this section.

3-3

7847i/7847i-E Installation and Setup Guide
PROMPTS

ENTRY

OPTIONS

DESCRIPTION

• ECP
Press the [space] key to scroll through the modes of
Device Mode
9
• Zone Triggers operation. Press [ENTER] to select ECP mode.
(ECP)_
• 4204 Emu
• Two 4204s
See Table 5 if programming other modes.
Important Information Regarding Multi-Mode Options
Users can receive email notification of system events by using the Multi-Mode feature. In ECP mode, this is
accomplished through emulation of a 4204 relay module, or two 4204 relay modules. When “4204-Sourced” is
selected, the user can be notified of up to four events, plus two additional events if using the optional communication
device zones of 6 and 7. When “2-4204-Sourced” is selected, the user can be notified of up to eight system events.
The Multi-Mode address must match the address of a relay module enabled in the control panel (although you don’t
actually connect a module). If using “2-4204-Sourced,” the address of the second module is automatically assigned
the next device address after the first 4204. Make sure that address is also enabled in the control panel. Program
outputs to trigger on system events the user would like to be notified of through Output Device (Relay) programming
in the control panel. Outputs 1-4 on the first 4204 Device Address map to events 1-4. Outputs 1-4 on the second 4204
Device Address map to events 5-8.
For LynxR-I/ReadyGuardR-I series controls (when available), if "4204 Sourced" is selected, you must enable MultiMode Address 6 or 7 in the control panel. If "2-4204" Sourced is selected, you must enable both (program field *86.
These events are configured at the AlarmNet Total Connect website at: https://services.alarmnet.com/TotalConnect
Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central Station
reporting of critical events (alarms, troubles, etc.).
NOTE: The Multi-Mode option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
Multi Mode
(Disabled)_

• Disabled

12

En.Priv.LAN: Y/N
(N)

[Y], [N]

13

CS IP:
255.255.255.255

12 digit:
xxx.xxx.xxx.xxx

14

CS Port:
(80)

[80]

15

Alarm Delivery:
Only One CS IP_

[Only One CS
IP]
[Fail to CS IP2]

Enable if you want specific events sent by email to the
user.
Select "4204 Sourced" to send up to four events or "2• 2-4204 Sourced
4204 Sourced" to send eight events.
Disable for normal alarm processing and go to Prompt
21: "Primary City ID".
This address must be programmed if using the Multi[01-30]
Multi Mode Addr
11
Mode feature. The device address must be unique from
(12)_
the normal LRR Device Address (Prompt 28), and the
Keypad Address used for Remote Access or Direct Wire
downloading. The address used must also be enabled
as a 4204 relay module in Vista and First Alert control
panels. See Important Information above.
Important Information Regarding Private LAN mode (7847i-E only).
1. Prompts 13-20 apply only if Private LAN was selected in Prompt 12.
2. Prompts 16-18 apply only if Prompt 15: Alarm Delivery is set to “Fail to CS IP2".
10

3-4

• 4204 Sourced

Applies only to 7847i-E. Press [Y] to enable alarm
delivery via a Private LAN to a 7810PC or 7810iR-ent
receiver.
Press [N] to enable alarm delivery over the internet or if
you have a 7847i, and go to Prompt 21: Primary City ID.
Enter the four part primary CS IP address of the
7810PC or 7810iR-ent receiver at the reporting center
to which this device will report. The four parts of the
address must be separated by spaces.
NOTE: This entry CANNOT be left as 255.255.255.255”.
It MUST be programmed with a valid IP address.
Enter the Central Station Port Number.
NOTE: The CS Port number must match the "Listening
Port" question of the 7810PC or 7810iR-ent.
Select the "Only One CS IP" option, if only one Central
Station IP address is desired and go to Prompt 18:
Verify Inst. Key. Select the "Fail to CS IP2" option, if a
secondary Central Station IP address is desired.

Section 3: Programming the 7847i/7847i-E
PROMPTS
16

17

18

19

20

21

Secondary CS IP:
255.255.255.255

ENTRY

OPTIONS
12 digit:
xxx.xxx.xxx.xxx

DESCRIPTION
Enter the four part secondary CS IP address of the

7810PC or 7810iR-ent receiver at the reporting center

to which this device will report. The four parts of the
address must be separated by spaces.
NOTE: This entry CANNOT be left as “255.255.255.255”
if using the Secondary CS IP. It MUST be programmed
with a valid IP address.
Enter the Central Station Port Number.
[80]
Second CS Port:
NOTE: The CS Port number must match the "Listening
(80)
Port" question of the 7810PC or 7810iR-ent.
Sets the supervision timing for the secondary internet
•
30
Day
IP2 Supervision
receiver to send a test alarm if set to Daily or 30 Day,
30 Day_
• Daily
or to send a status message to the 7810PC or 7810iR• Full Rate
ent if the interval is set to Full Rate. Selecting Full
• None
Rate means secondary supervision will be the same as
primary.
NOTE: The second 7810PC or 7810iR-ent must be
programmed to supervise subscribers in order to
generate a communication failure.
Press the [space] key to scroll through the choices.
[0-9]
Enter the 10-digit Installation Key necessary for
Installation Key:
communication with 7810PC or 7810iR-ent. If the key
**********_
entry is invalid, the prompt is repeated. See the
Installation Key paragraph in Section 1 for more
information.
Re-enter the 10-digit Installation Key to verify key.
[0-9]
Verify Inst. Key:
If verification fails, “Verify NOT OK” will be displayed
**********_
for one second and the display will return to the entry
of the installation key.
Important Information Regarding Primary and Secondary Accounts (Questions 21-27)
Account information is provided by the central station administrator. If the control supports secondary
account reporting, you will need secondary account information, unless using a Private LAN (7847i-E). The
City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account. If
Private LAN (7847i-E) is enabled, Prompts 24-27 will not be displayed.
[01-99]
Enter the 2-digit primary city ID, 01-99 (decimal).
Primary City ID
(??)_

22

Primary CS ID
(??)

[01-FE]

Enter the 2-digit primary central station ID number,
01-FE (HEX).

23

Primary Sub ID
(????)

[0001-9999]

Enter the 4-digit subscriber account number for the
primary central station, 0001-9999 (decimal).

24

En. 2 CS Y/N
(N)_

[Y], [N]

Applicable only if control supports Central Station #1
and #2 Category Enable reporting for the LRR device
(e.g., VISTA-128BP, FA1660C, etc.).
Used if reporting to a second central station is desired.
Press [N], go to Prompt 28: "Device Address."

25

2 City ID
(??)_

nd

[01-99]

Enter the 2-digit secondary city ID, 01-99 (decimal).

26

2 CS ID
(??)_

nd

[01-FE]

Enter the 2-digit second central station's ID number,
01-FE (HEX).

27

2 Sub ID
(????)_

nd

[0001-9999]

Enter the 4-digit subscriber account number for the
second central station, 0001-9999.

nd

3-5

7847i/7847i-E Installation and Setup Guide

PROMPTS

ENTRY

OPTIONS

DESCRIPTION

In ECP mode, the 7847i/7847i-E communicates with
the panel as a Long Range Radio (LRR) device. Enter
the appropriate ECP device address. For VISTA-10
and VISTA-20 series control panels, use address 03.
For other controls, see the control panel’s Installation
and Setup Guide.
NOTES:
1. When programming the control, enable the LRR
output.
2. The device address must be unique from the "Keypad
Address" entered in Prompt 31, and the Multi-Mode
Address entered in Prompt 11.
NOTE: The Remote Access option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
Press [Y] to allow the end user to access their system
Remote Access Y/N
29
[Y], [N]
via a website. Availability of this service is controlled
(N)_
by the dealer via the web-based programming tool on
the AlarmNet Direct website.
Applies only to VISTA-128BP/250BP and FBP series
Direct Wire Y/N
30
[Y], [N]
controls,
and FA1600C and FA1700C series controls.
(N)_
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 29: Remote Access is disabled,
skip to Prompt 32: "Supervision."
28

Device Address
(03)_

[01-30]

31

Keypad Address
(28)_

[01-30]

32

3-6

Supervision
(24 Hours)_

• 24 Hours
• 1 Hour
• US UL Line
(6 Min)
• CN UL Line
Lvl 3 (3 Min)
• US UL Line
(90 Sec)
• CN UL Line
Lvl 4 (90 Sec)
• CN UL Line
Lvl 5 (75 Sec)
• None
• 30 Day

Must be programmed if using either the Remote Access
feature or Direct Wire downloading. Enter the
appropriate device address.
NOTES:
1. This address must also be programmed as an alpha
keypad in the control panel or an AUI (Advanced
User Interface) type device, if a full enhanced graphic
interface to the system is desired and the control
panel supports it. DO NOT connect an actual keypad
(or any other device) assigned to this address.
2. If using a compatible LynxR-I series control (when
available), this address must be set to “1.”
3. This address must be unique from the "Device
Address" entered in Prompt 28.
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.

Section 3: Programming the 7847i/7847i-E
PROMPTS
33

34

Old Alarm Time
10 Minutes_

IP Flt Time
(60 mins)_

ENTRY

OPTIONS
•10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[00-99]

DESCRIPTION
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.

UL NOTE: Must be 10 minutes.
Enter the time delay (01-99) in minutes before the
7847i/7847i-E notifies the control panel that there is
loss of contact with the network, or enter 00 if you do
not want the unit to alert the control panel of loss of
contact with the network. The 7847i/7847i-E will alert
the control panel of the loss of contact via a dedicated
status message.
NOTE: Cannot be less than two (02) minutes if Private
LAN is enabled on the 7847i-E and the Supervision
interval is greater than 90 seconds.
UL NOTE: Must be one (01) minute.

35

Flt Rel ON Y/N
(N)_

[Y], [N]

If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault.
Set to [Y] if fail-safe mode is desired.
NOTE: If used, the fault relay will trip when the
following conditions occur: tamper*, loss of network
connectivity*, message communication failure, the
device is not registered and the device is remotely
disabled by AlarmNet.
* Alarm reporting for the noted condition must be
enabled for it to trigger the fault relay.
UL NOTE: Must be set to "Y."

Sends a tamper report on zone 6 when the module
detects a tamper condition. A tamper restore is
automatically sent when the tamper condition clears.
Important Information Regarding Zone Input Options
ECP mode supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of the
zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for the
user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
[Y], [N]
Enables alarm reporting for zone 6.
Enable Zn6 Y/N
37
(N)_
If [N], skip to Prompt 42: "Enable Zn7."
36

Tamper Rpt Y/N
(Y)_

38

Zn6 Trigger Type
(V+)_

39

Invert Zn6 Y/N
(N)_

[Y], [N]

• (V+)
• (V–)
• (EOLR)
[Y], [N]

Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.

3-7

7847i/7847i-E Installation and Setup Guide
PROMPTS

ENTRY

OPTIONS

DESCRIPTION

40

Restore Zn6 Y/N
(Y)_

[Y], [N]

Enables restore reporting for zone 6.

41

Delay Zn6 (secs)
(00)_

[01-15]

Defines the reporting delay in seconds for zone 6.

42

Enable Zn7 Y/N
(N)_

[Y], [N]

Enables alarm reporting for zone 7.
If [N], skip to Prompt 47: "Use DHCP."

43

Zn7 Trigger Type
(V)_

• (V+)
• (V–)
• (EOLR)

Selects the triggering method for this zone input.
Press the [space] key to scroll choices.

44

Invert Zn7 Y/N
(N)_

[Y], [N]

Inverts the alarm and normal states of the zone 7
trigger; otherwise, uses normal input signal.

45

Restore Zn7 Y/N
(Y)_

[Y], [N]

Enables restore reporting for zone 7.

46

Delay Zn7 (secs)
(00)_

[01-15]
[00] = no delay

Defines the reporting delay in seconds for zone 7.

[00] = no delay

Dynamically allocates the IP addresses (recommended);
then skip to Prompt 53: "Review?"
If [N], uses fixed IP addresses.
12 digit:
Enter the 4-part address for this device. The four parts
NIC IP Address:
48
xxx.xxx.xxx.xxx
of the address must be separated by spaces (displayed
255.255.255.255_
as periods in Review mode).
Enter the 32-bit address mask used to indicate the
12 digit:
Subnet Mask:
49
portion (bits) of the IP address that is being used for
xxx.xxx.xxx.xxx
255.255.255.255_
the subnet address. The four parts of the address must
be separated by spaces (displayed as periods in Review
mode).
12 digit:
Enter the 4-part address assigned to the Gateway. The
Gateway IP Addr:
50
xxx.xxx.xxx.xxx
four parts of the address must be separated by spaces
255.255.255.255_
(displayed as periods in Review mode).
Enter
the 4-part IP address assigned to the DNS
12
digit:
DNS Serv IP Addr:
51
(Domain
Name System) server. The four parts of the
xxx.xxx.xxx.xxx
255.255.255.255_
address must be separated by spaces (displayed as
periods in Review mode).
NOTE: The "Enable Pwr Save" option is not available, and is not displayed, if Private LAN is enabled on the 7847i-E.
47

Use DHCP Y/N
(Y)_

52

Enable Pwr Save
(Y)_

53

Review? Y/N

[Y], [N]

[Y], [N]

[Y] = review
[N] = exit

3-8

For 24 hour UL Battery Backup requirement, this
feature must be enabled, or the unit must be powered
by an appropriate UL listed UPS. If connectivity
problems occur with certain routers or switches disable
this option.
This option is forced to [N] when Private LAN is
enabled.
Reviewing Programming Mode Entries
To review the programming options (to ensure that the
correct entries have been made), press [Y]. The
programming prompts are displayed again. Use the
up/down arrow keys to scroll through the program
fields without changing any of the values. If a value
requires change, simply type in the correct value. When
the last field is displayed, the “REVIEW?” prompt
again appears.
To exit the programming mode, press [N] in
response to the "REVIEW?" prompt, and refer to
Exiting Programming Mode at the end of this section.

Section 3: Programming the 7847i/7847i-E
ECP Status Codes
When the 7847i/7847i-E is configured for ECP mode, it sends status messages to the control
panels (e.g., VISTA-10P, VISTA-15P and VISTA-20P series), for tamper, and network
connectivity failures. Some of the control panels display these on the keypad as "LngRng
Radio" followed by a 4-digit code (listed in table 4). In addition, the Contact ID codes (listed
in Appendix B) for these conditions are sent to the central station by the module.
Table 4. Common ECP Keypad Displays Status Codes
STATUS CODE

DESCRIPTION

0000

Control panel lost communication with 7847i/7847i-E.

0880

Tamper detected (cover removed).

0005

Lost Ethernet connectivity.

000F

Not registered; account not activated.

0019

Shutdown.

0400

Power on reset AND the control panel lost communications with
7847i/7847i-E.

0C80

Power on reset AND tamper detected.

0C8F

Power on reset AND tamper detected AND not registered.

Alternative Modes (Zone Trigger, 4204 and Two-4204)
Zone Trigger Mode
There are six input zones available on the 7847i/7847i-E. Zones 1 and 2 are located on TB1
pin 5 and are selectable for +V, –V, or EOLR modes, which can detect both pulsed and steady
signals. The pulsed signal is reported as an alarm on zone 1 (Fire); the steady signal is
reported as an alarm on zone 2 (Burg). The implied pulse count for zone 1 is fixed to 3
pulses. The unit can be programmed to detect a single pulse on the input, characteristic of a
Panic indication on the Lynx Control Panel. If the programming option “Lynx Panic” is
enabled, the unit reports an alarm on zone 3 when it detects this single pulse. No restores
are reported for this zone.
Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10. If the Lynx Panic
feature is being used, do not connect zone 3.
4204 Emulation Mode
In the 4204 Emulation Mode, the 7847i/7847i-E communicates with a compatible Honeywell
VISTA series or First Alert control panel as though it were a 4204 Relay Module. If the Two
4204 Mode is enabled in the module, it acts as two 4204s at consecutive device addresses.
The control panel must be configured to recognize one or two 4204 relay modules accordingly.
On VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13
should not be used when the secondary 4204 is enabled. Messages are sent in Honeywell
High-Speed format.
NOTE: See your control panel Installation and Setup Guide for the number of 4204 modules
supported. The LynxR-I does not support 4204 mode.
4204 Emulation Mode Options
For control panels that do not support ECP communication, the 4204 Emulation modes
provide a means of sending up to eight unique reports based on defined system conditions.
In 4204 mode, the 7847i/7847i-E functions as a logical 4204 Relay Module, where each relay
number, referred in the module as zone number, can be programmed to send a report based
on the output function programmed in the control for that relay. Each relay-zone can also be
programmed to send a restore message of the reported condition, can be set to delay
transmission of messages, and can be programmed to send reports only when a conditional
zone is triggered (armed), (see Zone Input Options later in this section).

3-9

7847i/7847i-E Installation and Setup Guide
In single 4204 mode, the unit supports up to four relay-zones. In two-4204 mode, the unit
functions as two 4204 modules, supporting up to eight relay-zones.
4204 Relay Outputs map to 7847i/7847i-E zones as follows:
First 4204 Zones

Second 4204 Zones

(device address entered in Prompt 23):

(device address entered in Prompt 23, plus 1):

Relay 1 = Zone 1
Relay 2 = Zone 2
Relay 3 = Zone 3
Relay 4 = Zone 4 or conditional zone trigger if
“report only if armed” is selected in
any zone 1-3 when using single 4204
mode.
NOTE: Zone 4 status is not reported when
being used as the conditional (armed) trigger
zone.

Relay 1 = Zone 5
Relay 2 = Zone 6
Relay 3 = Zone 7
Relay 4 = Zone 8 or conditional zone trigger if
“report only if armed” is selected in
any zone 1-7 when using two-4204
mode.
NOTE: Zone 8 status is not reported when
being used as the conditional (armed) trigger
zone or if tamper reporting is enabled.

When using the 7847i/7847i-E in 4204 Emulation Mode, DO NOT enable the Long-Range
Radio module in control panel programming. Instead, enable 4204 relay module address(es)
and program the appropriate relay activation functions for the relay-zones being used. In
some control panels, it is called “relay programming” and in others it is called “output device
programming.” It is recommended that the “close and stay closed” (usually choice 2) action is
selected. Selection of momentary activation will cause the unit to generate an alarm and
NOT a restore, even if the unit is programmed to send a restore for the given zone.
In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone alarms (status
7) are reported with “1” (alarm) or “3” (restore) displayed in the zone position for the respective zone (e.g. alarm on zone 2: 5155 5555 7; restore 5355 5555 7). A supervision fault
trouble message is automatically sent if the module detects no activity on its connection to
the control. The message is: 5555 5515 5; restore message is: 5555 5535 5.
Refer to Table 5 for 4204 Emulation Mode programming and follow the prompts that pertain
to 4204 or Two-4204 mode. A check mark ( ) indicates whether the prompt applies to that
mode.

Alternative Mode Programming
Press the [ENTER] key to begin programming and follow the prompts for the mode of
operation being programmed.
NOTE: The central station can remotely block access to
local device programming. If this has been done,
the following prompt appears:

Access to Prog
Mode Denied

Table 5: Programming a 7847i/7847i-E for Zone Trigger, 4204 Emulation, or Two-4204 Emulation modes.
PROMPTS

ZONE
TRIG.

4204/
2-4204

ENTRY

OPTIONS

DESCRIPTION

1

Strt Prog Mode?
Y/N_





[Y], [N]

Enters programming mode.

2

Enter Password





[0-9, A-F, N,
S, T, X, Y]

3

Program Device?
Y/N_





[Y], [N]

If a password has been previously assigned, this
prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
To begin programming the module, press [Y] and
go to Prompt 9: "Device Mode."
To create a password if none has been assigned,
press [N] and go to Prompt 4: Create Password.
To change an existing password, press [N] and go
to Prompt 5: "Change Password."

3-10

Section 3: Programming the 7847i/7847i-E
PROMPTS

ZONE
TRIG.

4204/
2-4204

ENTRY

OPTIONS

DESCRIPTION

4

Create Password?
Y/N_





[Y], [N]

5

Change
Password?
Y/N_





[Y], [N]

6

Enter Password





[0-9, A-F, N,
S, T, X, Y]

This prompt is displayed if [Y] was pressed in
Prompt 4 or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).

7

Verify Password





[0-9, A-F, N,
S, T, X, Y]

Re-enter the password as confirmation.
If the password doesn't match the first entry, the
following is displayed followed by the "Exit Prog.
Mode?" prompt:

8

Exit Prog. Mode?
Y/N_





[Y], [N]
[ESC]

Passwords can be used to protect account and
programming information.
If no password has been assigned, this prompt
appears after pressing [N] at the "Program
Device?" prompt.
If a password is desired, press [Y] and go to
Prompt 6: "Enter Password."
If a password has already been assigned, this
prompt appears after pressing [N] at the
"Program Device?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without
entering a new one, answer [Y] to the "Change
Password?" prompt, then press the [Enter] key
when prompted for the new password and its
confirmation.

Verify Not OK
PSWD not created
Otherwise, the "Exit Prog. Mode?" prompt is
displayed directly.
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode
paragraph in this section.
Press the [space] key to scroll through the modes
of operation.
Press [ENTER] to select mode.
See Table 3 for ECP mode programming.

• ECP
• Zone Trig.
• 4204 Emu
• Two 4204s
Important Information Regarding Multi-Mode
In Zone Trigger mode, the options for Multi-Mode are "Enabled" or "Disabled." If enabled, whenever a zone on the
communication device is triggered, a corresponding email message is sent INSTEAD of normal central station reports.
Cover tamper will send email event 8. All communication device system events (such as power loss, etc.) are still sent
to AlarmNet.
Events used to send email messages are defined on the Honeywell Total Connect web site, and must correspond to
events triggering the hardwired zones.
9

Device Mode
(ECP)_





Multi-Mode (email notification) is intended as a convenience for the user, and does not replace Central Station
reporting of critical events (alarms, troubles, etc.).
NOTE: The Multi-Mode option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
Enable if you want system events sent by email to
• Enabled

Multi Mode
10
the user.
(Disabled)_
• Disabled
Disable for normal alarm processing and go to
Prompt 20: "Primary City ID".
Important Information Regarding Private LAN mode (7847i-E only).
1. Prompts 12-18 apply only if Private LAN was selected in Prompt 11.
2. Prompts 14-16 apply only if Prompt 14: Alarm Delivery is set to “Fail to CS IP2".

3-11

7847i/7847i-E Installation and Setup Guide
PROMPTS

11

12

13

14

15

16

17

18

19

3-12

ZONE
TRIG.

4204/
2-4204

ENTRY

OPTIONS

DESCRIPTION

Applies only to 7847i-E. Press [Y] to enable alarm
delivery via a Private LAN to a 7810PC or
7810iR-ent receiver.
Press [N] to enable alarm delivery through
AlarmNet and go to Prompt 20: Primary City ID.

Enter
the 4-part primary CS IP address of the
12
digit:

CS IP:
xxx.xxx.xxx.xxx 7810iR-ent receiver at the reporting center to
255.255.255.255
which this device will report. The four parts of
the address must be separated by spaces.
NOTE: This entry CANNOT be left as
“255.255.255.255”. It MUST be programmed with
a valid IP address.

[80]
Enter the Central Station Port Number.

CS Port:
(80)
NOTE: The CS Port number must match the
"Listening Port" question of the 7810PC or
7810iR-ent.

[Only One CS Select the "Only One CS IP" option, if only one

Alarm Delivery:
Central Station IP address is desired and go to
IP]
Only One CS IP_
Prompt 18: "Installation Key".
[Fail to CS
IP2]
Select the "Fail to CS IP2" option, if a secondary
Central Station IP address is desired.


Enter
the 4-part secondary CS IP address of the
12
digit:
Secondary CS IP:
xxx.xxx.xxx.xxx 7810PC or 7810iR-ent receiver at the reporting
255.255.255.255
center to which this device will report. The 4parts of the address must be separated by spaces.
NOTE: This entry CANNOT be left as
“255.255.255.255” if using the Secondary CS IP.
It MUST be programmed with a valid IP address.


[80]
Enter the Central Station Port Number.
Second CS Port:
(80)
NOTE: The CS Port number must match the
"Listening Port" question of the 7810PC or
7810iR-ent.


If 30 Day or Daily is selected, the 7847i-E will
IP2 Supervision
• 30 Day
send a test alarm to the second CS IP within that
30 Day_
• Daily
interval.
• Full Rate
If Full Rate is selected, a status message is sent to
• None
the second CS IP at the same rate as the regular
Supervision Interval (Prompt 27).
NOTE: The second 7810PC or 7810iR-ent must
be programmed to supervise subscribers in order
to generate the communication failure.
Press the [space] key to scroll through the choices.

[0-9]
Enter the 10-digit Installation Key necessary for

Installation Key:
communication with 7810PC or 7810iR-ent. If
**********_
the key entry is invalid, the prompt is repeated.
See the Installation Key paragraph in Section 1
for more information.
Re-enter
the 10-digit Installation Key to verify key.
[0-9]
Verify Inst. Key:
If
verification
fails, “Verify NOT OK” will be
**********_


displayed for one second and the display will
return to the entry of the installation key.
Important Information Regarding Primary (Questions 20-22)
Account information is provided by the central station administrator.
En.Priv.LAN: Y/N
(N)





[Y], [N]

Section 3: Programming the 7847i/7847i-E

PROMPTS

ZONE
TRIG.

4204/
2-4204

ENTRY

OPTIONS

DESCRIPTION

20

Primary City ID
(??)_





[01-99]

Enter the 2-digit primary city ID, 01-99 (decimal).

21

Primary CS ID
(??)





[01-FE]

Enter the 2-digit primary central station ID
number, 01-FE (HEX).

22

Primary Sub ID
(????)





[0001-9999]

Enter the 4-digit subscriber account number,
0001-9999 (decimal).

23

Device Address
(12)_



[01-15]

The 7847i/7847i-E communicates with the control
panel as a 4204 relay module. Enter the
appropriate address. For VISTA-10P, and
FA130CP series control panels, this must be
address 12. For other controls, see the control
panel’s Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to 01-15.
If using 2-4204 mode, the 7847i/7847i-E assigns
the second 4204 to the next higher device
address (e.g., if entering address 12 for the first
4204, then address 13 is automatically assigned
to the second 4204 module). Program the control
panel accordingly.
2. The device address(es) must be unique from the
"Keypad Address" entered in Prompt 26 and any
other address used on the control panel.

NOTE: The Remote Access option is not available, and will not be displayed, when Private LAN is enabled on the 7847i-E.
24

Remote Access
Y/N
(N)_



[Y], [N]

25

Direct Wire
(N)_

Y/N



[Y], [N]

26

Keypad Address
(28)_



[01-30]

Press [Y] to allow the end user to access their
system via a website. Availability of this service
is controlled by the dealer via the web-based
programming tool on the AlarmNet Direct
website.
Applies only to VISTA-128BP/250BP and FBP
series controls, and FA1600C and FA1700C series
controls.
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 24: Remote Access is
disabled, skip to Prompt 27: "Supervision."
Must be programmed if using either the Remote
Access feature or Direct Wire downloading. Enter
the appropriate device address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel. If a full
enhanced graphic interface to the system is
desired, the keypad must also be enabled as an
AUI (Advanced User Interface) device. DO NOT
connect to an actual keypad (or any other
device) assigned to this address.
2. If using a compatible LynxR-I series control
(when available), this address must be set to “1.”
3. This address must be unique from the "Device
Address" entered in Prompt 23, and cannot
equal that device address plus 1 (one) if using 24204 mode.

3-13

7847i/7847i-E Installation and Setup Guide

PROMPTS

ZONE
TRIG.

4204/
2-4204

27

Supervision
(24 Hours)_





28

Old Alarm Time
10 Minutes_





29

IP Flt Time
(60 mins)_





ENTRY

OPTIONS

DESCRIPTION

• 24 Hours
• 1 Hour
• US UL
Line
6 Min
• CN UL Line
Lvl 3 (3 Min)
• US UL
Line 90 Sec
• CN UL Line
Lvl 4 (90 Sec)
• CN UL Line
Lvl 5 (75 Sec)
• None
• 30 Day
•10 Min.
• 15 Min.
• 30 Min.
• 1 Hr
• 2 Hrs
• 4 Hrs
• 8 Hrs
• 12 Hrs
• 24 Hrs

The AlarmNet network or the 7810PC or 7810iRent if Private LAN is enabled on the 7847i-E, must
hear at least one supervisory message from the
module during this supervision period; otherwise,
AlarmNet or the 7810PC or 7810iR-ent if Private
LAN is enabled on the 7847i-E, notifies the central
station that a communication failure has occurred.
If the supervision period is changed after
registration, you must re-register the module.
Press the [space] key to scroll through choices.

[00-99]

Enter the time delay (01-99) in minutes before the
7847i/7847i-E notifies the control panel that there
is loss of contact with the network, or enter 00 if
you do not want the unit to alert the control panel
of loss of contact with the network. The unit will
alert the control panel of the loss of contact via a
dedicated status message.
NOTE: Cannot be less than two (02) minutes if
Private LAN is enabled on the 7847i-E and the
Supervision interval is greater than 90 seconds.

Sets how long an undeliverable alarm is retried
for delivery to the central station. If the message
is not validated, it is retried until the old alarm
time is reached or the message is validated.
Press the [space] key to scroll through choices.

UL NOTE: Must be 10 minutes.

UL NOTE: Must be one (01) minute.
30

Flt Rel ON Y/N
(N)_





[Y], [N]

If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
Set to [Y] if fail-safe mode is desired.
NOTE: If used, the fault relay will trip when the
following conditions occur: tamper*, loss of
network connectivity*, message communication
failure, the device is not registered and the device
is remotely disabled by AlarmNet.
* Alarm reporting for the noted condition must be
enabled for it to trigger the fault relay.
UL NOTE: Must be set to "Y."

31

3-14

Tamper Rpt Y/N
(Y)_





[Y], [N]

Sends a tamper report on zone 8 when the module
detects a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.

Section 3: Programming the 7847i/7847i-E
PROMPTS

32

Lynx Panic Y/N
(N)_

ZONE
TRIG.
TRIG.

4204/
2-4204

ENTRY

OPTIONS

[Y], [N]



DESCRIPTION

Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the
module's zone terminal.
Reports a Panic alarm on zone 3 when the module
detects a single pulse on zone 1.
No restores are generated for a Panic alarm.

Important Information Regarding Zone Input Options
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module’s zone
6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module’s zone terminals
and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a
reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 and 2 terminal can detect both pulsed and steady signals. If connecting the
bell output to the 7847i/7847i-E zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
7847i/7847i-E reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when
it detects a steady signal.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the Telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a Telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for each of
these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following
conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by
open collector, voltage trigger, NO, NC.
Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones are
inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting
(allowing time for the user to abort false alarms).
UL NOTE: Zone restoral must be enabled.
Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if a
conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the
“arming” zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be
programmed as necessary in the control panel. The conditional (arming) zone on the module is a different dedicated
zone for each programming mode, as follows:
Mode
Zone Trigger

Conditional (Arming) Zone
7

4204
2-4204

4
8

IMPORTANT: If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set for
Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the
“arming” trigger connection).
33

Trip Inputs 1or2
w/Bell Out (N)_

[Y], [N]

Use if the zone 1 and 2 connection to the control's
bell output causes a bell fault on the control
panel.
NOTES:
1. If used, EOLR trigger type is not available
for zones 1, 2 and 3.
2. Do not use with Lynx controls.

3-15

7847i/7847i-E Installation and Setup Guide

PROMPTS

34

Telco Zone
(0)_

ZONE
TRIG.

4204/
2-4204





ENTRY

OPTIONS

Zone Trig:
[3-7]
4204: [1-4]
2-4204: [1-8]
[0] = not used

35

Open/Close Zone
(0)_





Zone Trig:
[3-7]
4204: [1-4]
2-4204: [1-8]
[0] = not used

36

Zn1 Trigger Type
(V+)_



37

Invert Zn1 Y/N
(N)_



38

Restore Zn1 Y/N
(Y)_



39

Delay Zn1 (secs)
(00)_



40

Rpt Zn1 ONLY if
Armed (N)_



41

Invert Zn2 Y/N
(N)_

42

Restore Zn2 Y/N
(Y)_

3-16

DESCRIPTION

See Important Information Regarding Zone Input
Options on previous page.
Enter the zone number to be used for Telco line
fault reports. This zone assignment must be
unique from the Open/Close Zone selected in
Prompt 35.
Zone Trigger Mode: If any zone is programmed
for "report only if armed," zone 7 cannot be used.
If Lynx Panic is enabled, zone 3 cannot be used.
4204 Mode: If any zone is programmed for
"report only if armed," zone 4 cannot be used.
2-4204 Mode: If any zone is programmed for
"report only if armed," or if tamper is enabled,
zone 8 cannot be used.
NOTE: Connect the Telco line fault output (or
relay output programmed for "Telco line fault") to
the Telco zone.
Enter the zone number to be used for open/close
(arm/disarm) reports.
This zone assignment must be unique from the
Telco Zone selected in Prompt 34.
Zone Trigger Mode: If any zone is programmed
for "report only if armed," zone 7 cannot be used
as an open/close zone. If Lynx Panic is enabled,
zone 3 cannot be used.
4204 Mode: If any zone is programmed for
"report only if armed," zone 4 cannot be used as
an open/close zone.
2-4204 Mode: If any zone is programmed for
"report only if armed," or if tamper is enabled,
zone 8 cannot be used as an open/close zone.
NOTE: Connect an open/close (arm/disarm)
trigger (or relay output) from the control panel to
the open/close zone.

• (EOLR)
• (V+)
• (V–)
[Y], [N]

Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.



[Y], [N]

Enables restore reporting for zone 1.



[01-15]

Defines the reporting delay in seconds for zone 1.

Inverts the alarm and normal states of the zone 1
trigger; otherwise uses normal input signal.

[00]=no delay


[Y], [N]

[Y], [N]



[Y], [N]

Report alarms on zone 1 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; or zone 8 in 2-4204 mode) is triggered
(armed).
If [N], always reports alarms on zone 1.
Inverts the alarm and normal states of the zone 2
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 2.

Section 3: Programming the 7847i/7847i-E
ZONE
TRIG.

4204/
2-4204

Delay Zn2 (secs)
(00)_





Rpt Zn2 ONLY if
Armed (N)_



PROMPTS

43
44

45

ENTRY

OPTIONS

[01-15]

DESCRIPTION

Defines the reporting delay in seconds for zone 2.

[00]=no delay


[Y], [N]

Reports alarms on zone 2 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered
(armed).
If [N], always reports alarms on zone 2.

If Lynx Panic is enabled, then skip to Prompt 49: "Rpt Zn3 ONLY if Armed."
Selects the triggering method for this zone input.
• (EOLR)

Zn3 Trigger Type
(V+)_
Press
the [space] key to scroll through choices.
• (V+)
• (V–)
[Y], [N]

Inverts the alarm and normal states of the zone 3
trigger; otherwise uses normal input signal.



[Y], [N]

Enables restore reporting for zone 3.



[01-15]

Defines the reporting delay in seconds for zone 3.

46

Invert Zn3 Y/N
(N)_



47

Restore Zn3 Y/N
(Y)_



48

Delay Zn3 (secs)
(00)



49

Rpt Zn3 ONLY if
Armed (N)_



50

Zn4 Trigger Type
(V+)_



51

Invert Zn4 Y/N
(N)_



52

Restore Zn4 Y/N
(Y)_





[Y], [N]

Enables restore reporting for zone 4.

53

Delay Zn4 (secs)
(00)





[01-15]

Defines the reporting delay in seconds for zone 4.

54

Rpt Zn4 ONLY if
Armed (N)_



55

Zn5 Trigger Type
(V+)_

56

[00] = no delay


[Y], [N]

• (EOLR)
• (V+)
• (V–)
[Y], [N]

Reports alarms on zone 3 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered
(armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to "Report
Only if Armed," skip to Prompt 60: "Enable Zn6."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 4
trigger; otherwise uses normal input signal.

[00] = no delay
[Y], [N]

Reports alarms on zone 4 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 24204 mode) is triggered (armed).
If [N], always reports alarms on zone 4.



• (EOLR)
• (V+)
• (V–)

Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.

Invert Zn5 Y/N
(N)_



[Y], [N]

Inverts the alarm and normal states of the zone 5
trigger; otherwise uses normal input signal.

57

Restore Zn5 Y/N
(Y)_



24204
only

[Y], [N]

Enables restore reporting for zone 5.

58

Delay Zn5 (secs)
(00)_



24204
only

[01-15]

Defines the reporting delay in seconds for zone 5.

24204
only

[00] = no delay

3-17

7847i/7847i-E Installation and Setup Guide

PROMPTS

ZONE
TRIG.

4204/
2-4204



24204
only

[Y], [N]

4204
only

[Y], [N]

59

Rpt Zn5 ONLY if
Armed (N)_

60

Enable Zn6 Y/N
(N)_

61

Zn6 Trigger Type
(V+)_



4204
only

62

Invert Zn6 Y/N
(N)_



63

Restore Zn6 Y/N
(Y)_

64

ENTRY

OPTIONS

DESCRIPTION

Reports alarms on zone 5 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 8 in 24204 mode) is triggered (armed).
If [N], always reports alarms on zone 5.
Enables alarm reporting for zone 6.
If [N], skip to Prompt 66: "Enable Zn7."

• (EOLR)
• (V+)
• (V–)

Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.

4204
only

[Y], [N]

Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.





[Y], [N]

Enables restore reporting for zone 6.

Delay Zn6 (secs)
(00)_





[01-15]

Defines the reporting delay in seconds for zone 6.

65

Rpt Zn6 ONLY if
Armed (N)_



66

Enable Zn7 Y/N
(N)_

67

Zn7 Trigger Type
(V+)_



4204
only

68

Invert Zn7 Y/N
(N)_



4204
only

69

Restore Zn7 Y/N
(Y)_





[Y], [N]

Enables restore reporting for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.

70

Delay Zn7 (secs)
(00)_





[01-15]

Defines the reporting delay in seconds for zone 7.
Zone Trigger mode: This question will only be
displayed if zone 7 is not used as the conditional
(arming) trigger zone.
Reports alarms on zone 7 ONLY if the conditional
zone (zone 4 in 4204 mode; zone 8 in 2-4204 mode)
is triggered (armed).
If [N], always reports alarms on zone 7.
2-4204 mode: If any zone is programmed to
"Report Only if Armed," or if tamper is enabled,
skip to Prompt 73: "Use DHCP."

[00] = no
delay


[Y], [N]

Reports alarms on zone 6 ONLY if the conditional
zone (zone 7 in zone trigger mode; zone 4 in 4204
mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 6.

4204
only

[Y], [N]

Enables alarm reporting for zone 7.
If [N], skip to Prompt 73: "Use DHCP."

• (EOLR)
• (V+)
• (V–)
[Y], [N]

Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.

[00] = no
delay

71

Rpt Zn7 ONLY if
Armed (N)_



[Y], [N]

72

Delay Zn8 (secs)
(00)_

24204
only

[01-15]



[Y], [N]

73

3-18

Use DHCP Y/N
(Y)_



Inverts the alarm and normal states of the zone 7
trigger; otherwise uses normal input signal.

Defines the reporting delay in seconds for zone 8.

[00] = no
delay
Dynamically allocates the IP addresses
(recommended).
If Private LAN is enabled, skip to Prompt 79:
"Review." Otherwise, skip to Prompt 78: "Enable
Pwr Save."
If [N], uses fixed IP addresses.

Section 3: Programming the 7847i/7847i-E
PROMPTS

ZONE
TRIG.

4204/
2-4204

ENTRY

OPTIONS

DESCRIPTION

74

NIC IP Address:
255.255.255.255_





12 digit:
xxx.xxx.xxx.x
xx

Enter the 4-part address for this device. The four
parts of the address must be separated by spaces
(displayed as periods in Review mode).

75

Subnet Mask:
255.255.255.255_





12 digit:
xxx.xxx.xxx.x
xx

Enter the 32-bit address mask used to indicate the
portion (bits) of the IP address that is being used
for the subnet address. The four parts of the
address must be separated by spaces (displayed as
periods in Review mode).

76

Gateway IP Addr:
255.255.255.255_





12 digit:
xxx.xxx.xxx.x
xx

Enter the 4-part address assigned to the Gateway.
The four parts of the address must be separated
by spaces (displayed as periods in Review mode).

77

DNS Serv IP
Addr:
255.255.255.255_





12 digit:
xxx.xxx.xxx.x
xx

Enter the 4-part IP address assigned to the DNS
(Domain Name System) server. The four parts of
the address must be separated by spaces
(displayed as periods in Review mode).

NOTE: The "Enable Pwr Save" option is not available, and is not displayed, if Private LAN is enabled on the 7847i-E.
78

79

Enable Pwr Save
(Y)_

Review? Y/N









[Y], [N]

[Y] = review
[N] = exit

For 24 hour UL Battery Backup requirement, this
feature must be enabled, or the unit must be
powered by an appropriate UL listed UPS. If
connectivity problems occur with certain routers
or switches disable this option.
This option is forced to [N] when Private LAN is
enabled.
Reviewing Programming Mode Entries
To review the programming options (to ensure
that the correct entries have been made), press
[Y]. The programming questions are displayed
again. Use the up/down arrow keys to scroll
through the program fields without changing any
of the values. If a value requires change, simply
type in the correct value. When the last field is
displayed, the “REVIEW?” question again
appears.
To exit the programming mode, press [N] in
response to the "REVIEW?" question, and refer to
Exiting Programming Mode below.

3-19

7847i/7847i-E Installation and Setup Guide

Exiting Programming Mode
To exit the programming mode, press [N] in response to the "REVIEW?" question. Then
press [Y] to the "Exit Prog Mode?" question. Upon exiting, the root file is updated to log the
changes made. A message is displayed telling the user that this step is being executed.
When complete, the message "DONE" is displayed to indicate the file was successfully
uploaded.
If critical configuration changes were made, such as the mode of operation, the
7847i/7847i-E will reset to ensure that the programmed features are enabled.
Setting Factory Defaults
To reset the programming options to factory-default values, press [ESC] at the "Exit Prog
Mode?" prompt.
Set Default?
Y/N_

Press [Y] to reset factory default values.
Press [N] to cancel this function.

If you press [Y], all programmed values are reset to the original factory settings. PLEASE
NOTE THAT THIS WILL ERASE ANY PASSWORD THAT MAY HAVE BEEN ENTERED.
After pressing [Y], the Create Password prompt appears (see Prompt 4).

3-20

S E C T I O N

4

Registration
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section

♦

Registering the 7847i/7847i-E

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Registering the 7847i/7847i-E
Once you have initialized and programmed the 7847i/7847i-E, it must be registered to enable
the account. An unregistered unit is indicated on the Status Display LEDs as: Status lit,
Message slow blinking, and Fault not lit. The Internet Link may be lit or blinking. Refer to
Appendix A for a detailed discussion of LED operation.

B

STATUS, GREEN
MESSAGE, YELLOW
FAULT, RED

Figure 9. Unregistered 7847i/7847i-E Status Display In Normal Operation
Throughout this document, the following key is used to describe LED state:
ON

OFF

FAST BLINK

SLOW BLINK

Figure 10. LED Key
To complete the registration process, a 7847i/7847i-E transmits a registration message and
receives a registration validation indicating that the account is now enabled.
You can register the 7847i/7847i-E by one of the following methods:
•

Through the AlarmNet Direct website

•

Through use of the Tamper Switch

•

Through use of a 7720P Programming Tool

•

By phone.

Registering through AlarmNet Direct Website (does not apply if using Private LAN)
If you have programmed the module through AlarmNet Direct, you must then transfer the
data to the module, and register the module.
To do this, please go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
Log in and follow the on-screen prompts.
Please have the following information available when programming the device:
1.
2.
3.
4.

Primary City ID (two-digit number)
Primary Central Station ID (two-digit hexadecimal number)
Primary Subscriber ID (four-digit number)
MAC ID and MAC CRC number (located on outside of box and on label inside
module)
5. Once module is registered, you may log out of the AlarmNet Direct website.
4-1

7847i/7847i-E Installation and Setup Guide
Using the Tamper Switch
Initiate the registration sequence by clicking the Tamper Switch three times.
You can monitor the registration process by viewing the Status Display. The Message
(yellow) LED and the Status (green) LED will blink slowly in unison while the registration is
in progress.
Once the registration has been completed successfully, the 7847i/7847i-E enters normal
operating mode; the Status (green) LED goes out and the Message (yellow) LED is lit to
indicate that the power-on / reset message is waiting to be sent. This message will appear at
the receiving station as “E339 8xx”, where “xx” is the ECP device address. The description
may read “Trouble – Exp. Mod. Reset”. If registration is not validated within 90 seconds, the
unit times out, and the (green) LED will be lit (solid).
If repeated registration attempts time out, check your Internet connection and verify that
7847i/7847i-E account information has been entered correctly.
The power-on/reset message will be sent in ADEMCO High-Speed format if the module is
programmed for zone trigger, 4204 or 2x4204 modes.
Using the Programming Tool
The interactive registration feature allows the installer to register the 7847i/7847i-E through
a series of keyboard commands on the 7720P Programming Tool. This method of registration
lets the installer monitor the registration process.
Registering …

Once the installation is complete, press the [↑] key on the 7720P.
The registration message is sent and the unit waits for the
acknowledgment.

Registration
SUCCESS

If this is a new installation and the city, central station, and
customer numbers have been correctly entered, the 7847i/7847i-E is
registered and this message is displayed. The unit is now in full
service and available for alarm reporting to the central station.

Possible Errors When Configured for Private LAN
Function
Unavailable

The Installation Key MUST be programmed in order to initiate the
Registration process.
This message will be displayed if the key is invalid.

4-2

No Registration
Account Disabled

Account was disabled at the 7810iR-ent prior to the registration
attempt or while registration was in progress.

Registration BAD
Timed Out

If the Registration Key entered is invalid, this message is displayed.

Registration BAD
Account Exists!

This prompt is displayed if the account number programmed in the
7847i-E is already being used for a different 7847i-E in the system.
If a replacement is desired, enable Substitution Mode in the 7810PC
or 7810iR-ent.

Registration BAD
CS Database FULL

This prompt is displayed if the 7810PC or 7810iR-ent receiver has
reached its maximum capacity for accounts. Its database is limited
to 300 subscribers.

Registration BAD

This prompt is displayed if a general problem occurred when the
7847i-E tried to register with the 7810PC or 7810iR-ent.

Section 4: Registration

Possible Errors When Configured for AlarmNet-i
Registration BAD
Timed Out

Displayed if no response to the registration request is received.

Registration BAD
Pri Sub ID BAD

Indicates the city, central station, or customer number for the
Primary account(s) is not accepted. The ID information was either
entered in error, or the central station failed to pre-authorize
programmed ID numbers with AlarmNet customer service.

Registration BAD
2nd Sub ID BAD

Indicates the city, central station, or customer number for the
Secondary account is not accepted. The ID information was either
entered in error, or the central station failed to pre-authorize
programmed ID numbers with AlarmNet customer service.

Registration BAD
Pri&Sec IDs BAD

Displayed when both Primary and Secondary subscriber IDs are
invalid.

Registration BAD
Pri ID – Need PIN

Displayed if this is a repair/replacement, or an error was made in
programming the Primary account information of 7847i/7847i-E for
an existing account. This prompt appears for 2 seconds. See the
Replacing an existing module section below for further displays.

Registration BAD
2nd ID – Need PIN

Displayed if this is a repair/replacement, or an error was made in
programming the Secondary account information of 7847i/7847i-E
for an existing account. This prompt appears for 2 seconds. See the
Replacing an existing module section below for further displays.

Registration BAD
Pri&2nd – Need PIN

Displayed if this is a repair/replacement, or an error was made in
programming BOTH the Primary and Secondary account
information of 7847i/7847i-E for an existing account. This prompt
appears for 2 seconds. See the Replacing an existing module section
below for further displays.

Replacing an existing module using the programming tool
Enter PIN#

This prompt appears after pressing the down arrow [↓
↓] on the
7720P.
NOTE: If it is necessary to exit registration mode, press ESC from
the 7720P programming tool.
Enter a 4-digit alphanumeric PIN number provided by an
authorized AlarmNet representative.
Press the [ENTER] key.

Registering …

The registration message is sent and the unit waits for
acknowledgement.

Registration
SUCCESS

If the PIN is valid, the new 7847i/7847i-E is registered and the old
unit unregistered. Additionally, AlarmNet sends a substitution
alarm to the central station.

Registration BAD

If you entered an invalid PIN, the appropriate message is displayed
depending on which account number is being replaced (see above for
exact wording). The registration process is repeated.
NOTE: Each attempt causes a substitution alarm to be sent to the
central station.

4-3

7847i/7847i-E Installation and Setup Guide
Register by Phone
You can register the module by calling the AlarmNet Technical Assistance Center (TAC) at
1-800-222-6525.
You will need the following information:

4-4

•

MAC number (found on the label).

•

Subscriber information (provided by the central station), including a city code, CSID,
and a subscriber ID.

•

When instructed to do so, triple-click the tamper switch to complete the registration.

S E C T I O N

5

Programmer Keyboard Commands
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Programmer Keyboard Commands
Programmer keyboard commands can be used to quickly view your Internet connectivity
settings and options. Most commands require you to press the [shift] key and then the
designated command key. (See the keys designated in red on the 7720P Programming Tool.)
[A]

7847i-e
x.x.xx

mm/dd/yy

[B]

MAC xxxxxxxxxxxx
MAC CRC
xxxx

[C]

Mon 23 Jul 2007
03:45:23 am

[D]

Physical Link:
GOOD

NIC IP Address:
xxx.xxx.xxx.xxx

Subnet Mask:
xxx.xxx.xxx.xxx

Gateway IP Address:
xxx.xxx.xxx.xxx
DNS Server IP:
xxx.xxx.xxx.xxx

Encryption Test:
AES Passed!

Software Revision
Depending on unit being programmed, either "7847i" or
"7847i-e" will be displayed.
"x.x.xx" indicates the installed software Revision.
Mm/dd/yy indicates month, day and year of the
revision.
MAC Address
“xxxxxxxxxxxx” indicates the 7847i/7847i-E's unique
identification number.
"xxxx" indicates the MAC CRC number. This number is
also found on the label on the module, as well as the
label on the box.
Time
Retrieves the current date and time from the AlarmNet
network in Greenwich Mean Time (GMT). This display
confirms that the module is in sync with network.
Network Diagnostics Display
Indicates whether device has detected a physical
connection to the internet.
Press the [space] key to go to the next field.
IP Information Display
Displays the IP address assigned to this device.
Press the [space] key to go to the next field.
Displays the 32-bit address mask used to indicate the
portion (bits) of the IP address that is being used for
the subnet address.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Displays the IP address assigned to the Gateway.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Displays the IP address assigned to the DNS (Domain
Name System) server.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Performs a self-test of the chosen encryption algorithm.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.

5-1

7847i/7847i-E Installation and Setup Guide
DHCP (Dynamic Host Configuration Protocol) indicates
server is performing satisfactorily.
Press the [space] key to go to the Physical Link display.

DHCP
OK/BAD
[F]

Testing Gateway

Run Network Diagnostic Test
Performs a set of network diagnostics that tests the
integrity of the links between the unit and the various
connection points (Redirs) to AlarmNet. Refer to
Section 6: Network Diagnostics.

System Status Displays
[S]

ECP 67 Tm
xx 5

Flt
OK

1234 67 Tm Flt
5555 xx 5
OK

12345678 Tm
5555555x 5

1234567 Tm
5555555 5

[T]

5-2

Test Msg Sent

Flt
OK

Flt
OK

ECP Mode
Displays the zone and system fault status.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
4204 Emulation Mode
Displays the zone and system fault status.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Two-4204 Emulation Mode
Displays the zone and system fault status.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Zone Trigger Mode
The status of the unit can be viewed on the 7720P. The
status display includes:
• Zone input status (1234567) - the numbers 17 represent the 7 mappings of the zone
input, and follow Honeywell's ADEMCO
high-speed format codes:
1 = New Event
5 = Normal
X = Not Enabled
• Tm – Tamper status follows high-speed format
codes above.
• Flt – Represents radio faults:
OK = Normal ; No fault
I – No network connectivity over IP and
fault time has expired
i – No network connectivity over IP and
fault time has NOT yet expired.
NOTE: The 7720P will not operate if the power line
voltage is removed.
Test Alarm
Sends a test alarm to AlarmNet only if Private LAN is
not enabled; otherwise, it is sent the Primary CS IP and
the Secondary if it is enabled.

Section 5: Programmer Keyboard Commands

[X]

Reset CPU Y/N

Reset the 7847i/7847i-E
Pressing [N] returns to diagnostic mode (blank screen =
enter next command or escape).
Pressing [Y] resets the module (blank screen = reset
complete).

[↑
↑]

Registering …

Registration
Registers a programmed 7847i-E with the 7810PC or
7810iR-ent if it is configured to report on the Private
LAN. If it is configured to report to AlarmNet, the
7847i/7847i-E will register with AlarmNet. Refer to
Section 4: Registration.

Enter PIN#

Registration with PIN for Replacement Module

(UP arrow)

[↓
↓]
(DN arrow)

[0]

Registers a replacement unit with AlarmNet, once
programmed, using the existing PIN #.
If Private LAN is enabled, down arrow is not applicable.
Force Server Update?
Y/N_

Force Upload of Configuration File to Server
Pressing [Y] will force the device to upload its entire
configuration file to the server.
Pressing [N] cancels the operation.
NOTE: If Private LAN is enabled, "Function
Unavailable" is displayed.

[ENTER]

Strt Prog Mode?
Y/N_

Enter Program Mode
Press [Y] to enter program mode; otherwise, press [N].

5-3

7847i/7847i-E Installation and Setup Guide

5-4

S E C T I O N

6

Network Diagnostics
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

In This Section

♦

Running Network Diagnostics on the
7847i/7847i-E using AlarmNet

♦

Running Network Diagnostics on the 7847i-E
using a Private LAN

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Running Network Diagnostics on the 7847i/7847i-E using AlarmNet
The network diagnostic process tests the integrity of the links between the unit and the
various connection points of AlarmNet Control that are known as "Redirects" (Redirs or
RDR).
To initiate the network diagnostics, press the [F] key on the 7720P.
NOTE: The test is performed ONLY if a physical link is detected. If no physical link is
detected, the test is aborted and the following is displayed:
No Physical Link
If a physical link is detected, the diagnostics are performed. The following shows the
progression of the test:
Testing Redir 1

The first step of the test traces the connection to Redir 1 at
AlarmNet Control.

Testing Redir 1
Reached Redir 1

A successful trace to Redir 1 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached Redir 1
Testing Service

After a successful trace to Redir 1, a test of the service at Redir 1 is
performed. That is, the first test determines if a message can reach
AlarmNet Control; this test determines if the connection point
(Redir) at AlarmNet Control knows what to do with the message
once it receives it.

Redir 1
Service OK

The service at AlarmNet Control on Redir 1 is functioning. See
below for possible errors that may occur at this stage of testing.

Testing Redir 2

The first step of the test traces the connection to Redir 2 at
AlarmNet Control.

Testing Redir 2
Reached Redir 2

A successful trace to Redir 2 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached Redir 2
Testing Service

After a successful trace to Redir 2, a test of the service at Redir 2 is
performed. That is, the first test determines if a message can reach
AlarmNet Control; this test determines if the connection point
(Redir) at AlarmNet Control knows what to do with the message
once it receives it.

Redir 2
Service OK

The service at AlarmNet Control on Redir 2 is functioning. See
below for possible errors that may occur at this stage of testing.
6-1

7847i/7847i-E Installation and Setup Guide
Testing Redir 3

The first step of the test traces the connection to Redir 3 at
AlarmNet Control.

Testing Redir 3
Reached Redir 3

A successful trace to Redir 3 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached Redir 3
Testing Service

After a successful trace to Redir 3, a test of the service at Redir 1 is
performed. That is, the first test determines if a message can reach
AlarmNet Control; this test determines if the connection point
(Redir) at AlarmNet Control knows what to do with the message
once it receives it.

Redir 3
Service OK

The service at AlarmNet Control on Redir 3 is functioning. See
below for possible errors that may occur at this stage of testing.

RDR1 RDR2 RDR3
OK
OK
OK

A summary of the tests is displayed after Redir 3 is tested. The
example shows that the tests of all three connection points, or
Redirs, were successful. If an error occurred at any point, the
summary will display “FAIL” under the faulty Redir.

Possible Errors Running Network Diagnostics
Errors may occur at either while tracing the connection to a given Redir or while testing the
service at a given Redir. The following list highlights the most common errors. Please
contact the AlarmNet Technical Assistance Center (TAC) for help regarding any errors NOT
listed below:
Possible Errors

6-2

Testing Redir x
FAIL before Gtwy

While tracing the connection to Redir x, the trace fails before ever
reaching the local gateway (router).

Testing Redir x
FAIL at Gtwy

While tracing the connection to Redir x, the trace fails after
reaching the local gateway (router).

Testing Redir x
FAIL at Pvt IP

While tracing the connection to Redir x, the trace fails after
reaching the private IP.

Testing Redir x
FAIL on IP Addr

While tracing the connection to Redir x, the trace fails after
reaching the public IP.

Redir x
ERR:Proxy 18

After a successful trace to Redir x, the test of the service timed out
without a response.

Section 6: Network Diagnostics

Running Network Diagnostics on the 7847i-E using a Private LAN
The network diagnostic process tests the integrity of the links between the 7847i-E and the
7810PC or 7810iR-ent to which it should report.
To initiate the network diagnostics, press the [F] key on the 7720P.
NOTE: The test is performed ONLY if a physical link is detected. If no physical link is
detected, the test is aborted and the following is displayed:
No Physical Link
If a physical link is detected, the diagnostics are performed. The following shows the
progression of the test:
Testing CSIP 1

The first step of the test traces the connection to CS IP 1.

Testing CSIP 1
Reached CSIP 1

A successful trace to CS IP 1 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached CSIP 1
Testing Service

After a successful trace to CS IP 1, a test of the service at CS IP 1 is
performed. That is, the first test determines if a message can reach
7810PC or 7810iR-ent; this test determines if the connection point
(CSIP) at the 7810PC or 7810iR-ent knows what to do with the
message once it receives it.

CSIP 1
Service OK

The service at the 7810PC or 7810iR-ent on CS IP 1 is functioning.
See below for possible errors that may occur at this stage of testing.

Testing CSIP 2

The first step of the test traces the connection to CS IP 2 at the
7810PC or 7810iR-ent.

Testing CSIP 2
Reached CSIP 2

A successful trace to CS IP 2 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached CSIP 2
Testing Service

After a successful trace to CS IP 2, a test of the service at CS IP 2 is
performed. That is, the first test determines if a message can reach
the 7810PC or 7810iR-ent; this test determines if the connection
point (CSIP) at the 7810PC or 7810iR-ent knows what to do with the
message once it receives it.

CSIP 2
Service OK

The service at the 7810PC or 7810iR-ent on CS IP 2 is functioning.
See below for possible errors that may occur at this stage of testing.

Testing CSIP 3

The first step of the test traces the connection to CS IP 3 at the
7810PC or 7810iR-ent.

Testing CSIP 3
Reached CSIP 3

A successful trace to CS IP 3 is indicated here. See below for
possible errors that may occur at this stage of testing.

Reached CSIP 3
Testing Service

After a successful trace to CS IP 3, a test of the service at CS IP 1 is
performed. That is, the first test determines if a message can reach
the 7810PC or 7810iR-ent; this test determines if the connection
point (CSIP) at the 7810PC or 7810iR-ent knows what to do with the
message once it receives it.

CSIP 3
Service OK

The service at the 7810PC or 7810iR-ent on CS IP 3 is functioning.
See below for possible errors that may occur at this stage of testing.

6-3

7847i/7847i-E Installation and Setup Guide
If CS IP 2 and/or CS IP 3 are not programmed, display will read.

Testing CSIP 2
Does Not Exist
CIP1 CIP2
OK/Fail N/A

CIP3
N/A

A summary of the tests is displayed after CS IP 3 is tested. The
example shows that CS IP 2 and/or CS IP 3 are not programmed.

Possible Errors Running Network Diagnostics using a Private LAN
Errors may occur at either while tracing the connection to a given 7810PC or 7810iR-ent or
while testing the service at a given 7810PC or 7810iR-ent. The following list highlights the
most common errors. Please contact the AlarmNet Technical Assistance Center (TAC) for
help regarding any errors NOT listed below:
Possible Errors

6-4

Testing CSIP x
FAIL before Gtwy

While tracing the connection to CS IP x, the trace fails before ever
reaching the local gateway (router).

Testing CSIP x
FAIL at Gtwy

While tracing the connection to CS IP x, the trace fails after
reaching the local gateway (router).

Testing CSIP x
FAIL on IP Addr

While tracing the connection to CS IP x, the trace fails after
reaching the CS IP.

Appendices
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Appendix A: Summary of LED Operation
Status Display Operation
The 7847i/7847i-E Status Display has three LEDs used to indicate message and device
status:
•

STATUS, green

•

MESSAGE, yellow

•

FAULT, red

GREEN
(STATUS)
YELLOW
(MESSAGE)
RED
(FAULT)

7847i-E-025-V0

Figure 11. 7847i/7847i-E Status Display LEDs with Front Cover Installed

Each LED can have four different states - ON, OFF, FAST BLINK and SLOW BLINK.
Throughout this document, the following key is used to describe LED state:
ON

OFF

FAST BLINK

SLOW BLINK
7847i-E-033-V0

Figure 12. LED Key

A-1

7847i/7847i-E Installation and Setup Guide
Table 6. Status Display Operation
LED COLOR

LED LABEL

DESCRIPTION

GREEN

STATUS

ON – 7847i/7847i-E is NOT registered with AlarmNet or
7810PC or 7810iR-ent if Private LAN is enabled.
OFF – 7847i/7847i-E is registered with AlarmNet or 7810PC or
7810iR-ent if Private LAN is enabled.
FAST BLINK – Download session with Compass in progress.
SLOW BLINK – In unison with yellow LED – registration in
progress.

YELLOW

MESSAGE

ON – Message transmission pending.
QUICK PERIODIC BLINK – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle, power abnormal.
– In unison with green LED , registration in
progress.

RED

FAULT

ON – No contact with the network.
OFF– Normal.
SLOW BLINK – Loss of communication with the panel (ECP fault).
FAST BLINK – No network contact AND loss of communication
with the panel.

A

B

STATUS, GREEN

STATUS, GREEN

MESSAGE, YELLOW

MESSAGE, YELLOW

FAULT, RED

FAULT, RED

Figure 13. A Registered 7847i/7847i-E Status Display (A) and
an Unregistered 7847i/7847i-E Status Display in Normal Operating State(B)

The sequence below illustrates LED operation when 7847i/7847i-E transmits a message.
1

2

3

4

STATUS, GREEN
MESSAGE, YELLOW
FAULT, RED

Figure 14. LED Sequence for a Registered 7847i/7847i-E Message Transmission

A-2

Appendices
Network Connectivity Display
The Network Connectivity display can only be viewed with the cover removed. It is used as a
visual indication of 7847i/7847i-E network activity.

NETWORK COLLISION (YEL)
LINK SPEED (GRN)
ETHERNET LINK/ACTIVITY (GRN)

NETWORK CONNECTIVITY
LED DISPLAY

7847i-E-032-V0

Figure 15. 7847i/7847i-E Network Connectivity Display
The Network Connectivity Display consists of three LEDs. They function as follows:
LED COLOR

LED LABEL

YELLOW

NETWORK
COLLISION

1ST GREEN

LINK SPEED

2ND GREEN

ETHERNET
LINK /
ACTIVITY

DESCRIPTION
BLINKING – Network collision detected.
OFF – Normal.
ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.
ON – Ethernet link detected.
OFF – No Ethernet link detected.
FAST BLINK – Transmitting/Receiving data.

NOTE: When "Enable Pwr Save" is enabled, LED status is displayed once every 15 seconds.

A-3

7847i/7847i-E Installation and Setup Guide
Mode and Status LED Display
The Mode and Status LED Display consists of 4 LEDs. LED 1 (red LED on the left) will be
off, LED 2 and 3 (yellow LEDs) indicate operation mode. LED 4 (1st green LED) displays Web
connection status; LEDs 5 and 6 are not used.
Mode and Status Indicator Switch
Press and hold the Mode and Status Indicator Switch to change the LED functions in order
to view the mode of operation and network carrier status. When the switch is held down,
LED 1 (red LED on the left) will be off, and the LEDs from left to right have the following
meanings:
Table 7. LED Functions with Mode and Status Indicator Switch Depressed
LED 1

LED 3

LED 2
st

LED 4

nd

st

(red)

(1 yellow)

(2 yellow)

(1 green)

OFF

in combination
with LED 3

in combination
with LED 2

Web
Connection

Table 7a. Operation Modes
LED 2

LED 3

OPERATION
MODE

(1 yellow)

(2 yellow)

ECP
Zone
4204
2 – 4204

OFF
ON
OFF
ON

OFF
OFF
ON
ON

st

nd

Table 7b. Status Indications
STATUS
OFF
SLOW BLINK
NORMAL BLINK
FAST BLINK
ON

A-4

LED 4
st

(1 green)
No Web connection
Trying to connect
–
Web communication
Connected to Web

Appendix B: Central Station Messages
The following messages are sent by the 7847i/7847i-E module for the conditions listed below.

Table 8. Central Station Messages

Alarm Condition

ECP Mode
Alarm Code

Power On Reset
Tamper

E339 C08xx*
E341 C08xx*

ECP Supervision
Communication Path
Supervision

Zone and 4204
Modes
Alarm Code

Zone and 4204
Modes
Restore Code

R341 C08xx*

5551 5555 6
5555 5551 7

5555 5553 7

E355 C0000

R355 C0000

5555 5515 5

5555 5535 5

E954 C0951

R350** C0951
R954 C0951

5555 5551 5

5555 5553 6
5555 5553 5

E954 C0952

R954 C0952

(7847i and 7847i-e in
AlarmNet Mode)

Primary CS IP
Supervision

ECP Mode
Restore Code

(7847i-E, Private LAN ONLY)

Secondary CS IP
Supervision
(7847i-E, Private LAN ONLY)

Swinger Suppression
Telco
Open/Close
Test

5555 5555 9

5555 5551 1
0D00 0005 0
5555 5155 6
2 sent in
selected zone
5555 5555 9

5555 5553 1
5555 5355 6
4 sent in
selected zone

* xx = 7847i/7847i-E Device Address
** R350 is generated ONLY if Ethernet was not available for at least a duration of the Fault Time period.
The control panel sends its own general code (E353) for a trouble condition.

B-1

7847i/7847i-E Installation and Setup Guide

B-2

Appendix C: IP Downloading
General Information
The 7847i/7847i-E can be used to provide high-speed up/downloading to Honeywell VISTA
and LynxR-I control panels. This allows site maintenance independent of central station
monitoring, and modification to sites through an Intranet or globally via the Internet.
Residential panels that support IP downloading (e.g., Vista-20P and LynxR-I) are connected
to the unit through the ECP bus. Currently, commercial controls such as VISTA-128BP and
FBP support IP downloading through use of a Direct Wire connection (using the trigger
cable).

UL

Downloading may only be performed if a technician is at the site.

Direct Wire Setup
To perform IP up/downloading using Direct Wire, the unit requires that Direct Wire
downloading over IP programming is enabled (Direct Wire Y/N), and that the ECP Device
Address on which the unit communicates with the control panel as a keypad is entered
(Keypad Address). Additionally, the 7847i/7847i-E must be connected by cable as shown
below to the panels listed.
NOTES:
1. For Direct Wire IP downloading on Commercial Fire panels (e.g. VISTA-128FBP,
FA1700C), Program Field 3*19 Enable J2 Header Printer Port must be set to "1".
2. This feature is not available if device is set for zone trigger mode.
3. If using the RS232 Home Automation features, you cannot use Direct Wire Downloading.
This includes customers using WinpakSE and ProWatch.
VISTA-128BP/250BP
FA1660C
J8 CONNECTOR
1

2

3

4

5

6

7

7847i / 7847i-E
PROGRAMMER
PORT
8

9
WHITE
BLACK

BLUE

K4668WH
RJ 11 CABLE

ND

ND

BLUE

GR
OU

GREEN

BROWN
T6

GR
OU

RED
ND

T5
OU

OU

YELLOW
GR
OU

3
IN

PR

INT

IN

2

ER

DT

R GREY

VIOLET

NU

TB 1
1
2
3
4
5
6
7
8
9
10
11

4142 TR CABLE

PARTS SUPPLIED WITH DOWNLOADER KIT P/N VBPCOMKIT

7847i / 7847i-E

VISTA-128FBP/250FBP
FA1670C /FA1700C
J2 CONNECTOR

4100SM
9

TO
AUX PWR 1
OUTPUT

+ (TO TERM 11)
- (TO TERM 12)

VIOLET

8

GRAY

7

YELLOW

6

WHITE

RED

5

T
2
OU
T
5
OU
T
1
GR
OU
ND
IN
PU
T
1

OU

T

6

GREEN

4

OU

BLUE

3
T

7

3

BROWN

2

OU

T
OU

OU

T

4

BLACK

1

7847i-E-026-V0

8

+ PWR

7

- (GND)

6

RXD

5

not used

4

not used

3

TXD

2

not used

1

not used

4142 TR CABLE
RED BLUE WHITE

PARTS SUPPLIED WITH DOWNLOADER KIT P/N VFBPCOMKIT

PROGRAMMER
PORT

TB 1
1
2
3
4
5
6
7
8
9
10
11

K14394LF 25-PIN TO RJ11 CABLE
7847i-E-027-V0

Figure 16. Cable Connections for IP Downloading
C-1

7847i/7847i-E Installation and Setup Guide
Prior to IP up/downloading over an Intranet (Private LAN), setup of the Honeywell Compass
Connect Server and Honeywell Compass downloader is required. Refer to the Compass
Connect Server Installation and Setup Guide (K10178V1) and the Compass IP Downloading
Supplement (K10441V1) for setup instructions.
The figures below show data flow depending on whether the system is set up for use with the
Internet or Intranet.

VISTA PANEL

COMPASS

INTERNET

7847i / 7847i-E

ALARMNET
ROUTING CENTER

Figure 17. Internet Flow Diagram

VISTA
PANELS

7810iR-ent
COMPASS

7847i-E

CONTROL
SERVER

DATA
SERVER

Figure 18. Private LAN (Intranet) Flow Diagram

C-2

Appendix D: Glossary
AES – Advanced Encryption Standard
DHCP – Dynamic Host Configuration Protocol. Provides a mechanism for allocating IP
addresses dynamically so that addresses can be reused when hosts no longer need them.
DNS – Domain Name System. A distributed hierarchical naming system used to resolve
domain names (e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1.).
DSL – Digital Subscriber Line
Gateway IP Address – A gateway (sometimes called a router) is a computer and/or software
used to connect two or more networks (including incompatible networks) and translates
information from one network to the other. The Gateway IP address is the IP address for the
gateway.
IP – Internet Protocol
IP Address – A unique number consisting of four parts separated by periods, sometimes
called a "dotted quad.," for example: 204.17.29.11, assigned to every computer/workstation
connected to the Internet. IP numbers can be "static" (assigned and unchanging) or
"dynamic," assigned via DHCP at each and every startup.
ISP – Internet Service Provider
LAN – Local Area Network
MAC Address – The hardware address of a device connected to a network.
NAT – Network Address Translation
PPP – Point-to-Point Protocol
PPPoE – Point-to-Point Protocol over Ethernet
Subnet Mask – A Subnet is a portion of a network that shares a network address with other
portions of the network, and is distinguished by a subnet number. The Subnet Mask is a 32bit address mask used in IP to indicate the bits of an IP address that are being used for the
subnet address.
TCP/IP – Transmission Control Protocol / Internet protocol

D-1

7847i/7847i-E Installation and Setup Guide

D-2

NOTES:

NOTES:

NOTES:

NOTES:

7847i/ 7847i-E Summary of Connections
STATUS LED
MESSAGE LED
FAULT LED

7720P PROGRAMMER PORT/
PANEL DOWNLOAD PORT
TB 1
1
2
3
4
5
6
7
8
9
10
11

NOT USED
NOT USED
12V DC IN
GND
ZONE INPUT Z1/Z2 or ECP INPUT
ZONE INPUT Z3 or ECP OUTPUT
ZONE INPUT Z4 or NOT USED
ZONE INPUT Z5 or NOT USED
ZONE INPUT Z6 or NOT USED
ZONE INPUT Z7 or NOT USED
OPEN COLLECTOR FAULT OUTPUT

MODE AND
STATUS
LED DISPLAY

MODE AND
STATUS
INDICATOR
SWITCH

1

MOUNTING HOLE
(FUTURE USE)

TAMPER
SWITCH

RJ45
ETHERNET
PORT

NETWORK
CONNECTIVITY
LED DISPLAY

7847i-E-015-V0

TB1 Wiring for 7847i/7847i-E Internet/Intranet Communication Module
TB1

2 x 4204 Mode

4204 Mode

Zone Mode

ECP Mode

Wire Color

1

---

---

---

---

2

---

---

---

---

3

12VDC

12VDC

12VDC

12VDC

RED

4

GND

GND

GND

GND

BLK

5

ECP IN

ECP IN

Z1/Z2

ECP IN

YEL

6

ECP OUT

ECP OUT

Z3

ECP OUT

GRN

7

NOT USED

NOT USED

Z4

NOT USED

8

NOT USED

NOT USED

Z5

NOT USED

9

NOT USED

Z6

Z6

Z6

10

NOT USED

Z7

Z7

Z7

11

FLT OUT

FLT OUT

FLT OUT

FLT OUT

WARRANTY INFORMATION
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa

2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright  2007 Honeywell International Inc.

www.honeywell.com/security.com

ÊK14175V1BŠ
K14175V1 9/10 Rev C



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04
Format                          : application/pdf
Creator                         : e651448
Title                           : Microsoft Word - K14175V1-C_7847i-ii
Create Date                     : 2013:04:30 13:43:49Z
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2013:05:02 16:59:20-04:00
Metadata Date                   : 2013:05:02 16:59:20-04:00
Producer                        : GPL Ghostscript 8.15
Document ID                     : uuid:604e7ef3-8395-4fae-b782-67b86fb2e88b
Instance ID                     : uuid:ea005975-c4cc-4109-8350-90aa29367117
Page Count                      : 64
Author                          : e651448
EXIF Metadata provided by EXIF.tools

Navigation menu