RM6 7897073uk
User Manual: RM6
Open the PDF directly: View PDF .
Page Count: 74
Download | |
Open PDF In Browser | View PDF |
RM6 ENGLISH MV distribution factory built assemblies at your service instructions for use foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 symbols and conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . distribution rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . maintenance rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4 4 4 general description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 circuit breaker and switch function . . . . . . . . . . . . . . . . . . . . . . . . . . . . fuse- switch and switch function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ”switchboard coupling” switch and circuit breakers . . . . . . . . . . . . . cable connection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . metering cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . single- line diagramms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5 6 6 6 7 instructions for putting the RM6 into operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 prior to energising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pressure check of unit in operation . . . . . . . . . . . . . . . . . . . . . . . . . . . unit with pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . position of the VPIS or VDS voltage indicator units (optional) . . . . . phase concordance unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . rules for the use of phase concordance unit . . . . . . . . . . . . . . . . . . . . RM6 equipped with VDS voltage detection units . . . . . . . . . . . . . . . . choosing the HV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . sealing of DE- Mt cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 9 10 12 13 13 16 17 20 instructions for putting into operation the protection relay for circuit - breaker . . . . . . 23 VIP400 / VIP410 presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . presentation of VIP40/45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sepam series 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . standard assignment of inputs/outputs and customised configuration human- machine interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 27 31 35 36 38 38 operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 operating and viewing substation condition . . . . . . . . . . . . . . . . . . . . operating safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . key- locking (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . padlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . overcurrent indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LV connection indicator Flair 2xD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . detector pending fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ammeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . standard operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . connection of Cts to the 3 MV cables . . . . . . . . . . . . . . . . . . . . . . . . . . voltage detection relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . detection sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . configuration of thresholds and time delays . . . . . . . . . . . . . . . . . . . . suggested choice for VD23 settings . . . . . . . . . . . . . . . . . . . . . . . . . . . access to the cable compartments . . . . . . . . . . . . . . . . . . . . . . . . . . . . access to the MV compartment of the DE- Mt cubicle . . . . . . . . . . . 43 45 45 45 47 48 48 53 53 54 55 55 56 56 57 58 preventive maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 standard operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . harsh operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 60 corrective maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . maintenance summarising table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . replacing a fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . access to the LV compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . replacing a motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . replacing the LV contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 61 65 68 68 69 07897073EN01 revision : 11 1 processing when dismantling the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 processing of SF6 gas when dismantling the equipment . . . . . . . . . 70 2 07897073EN01 revision : 11 foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER DANGER: failure to follow this instruction will result in death or serious injury. AVERTISSEMENT WARNING: failure to follow this instruction may result in death or serious injury. as per iso 3864- 2 ATTENTION CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION - ADVICE We draw your attention to this specific point. contact the Schneider Electric service unit for diagnosis and advice You can log on to: WWW.SCHNEIDER- ELECTRIC.COM Call your sales representative who will put you in contact with the closest SCHNEIDER- ELECTRIC service centre. 07897073EN01 revision : 11 3 distribution rules CAUTION CAUTION The aim of this publication is to enable the RM6 unit to be installed correctly. safety rules This document is not a commercial document.It is a strictly technical document drawn up by Schneider Electric. WARNING CAUTION All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. WARNING Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric. The contractor must be certified and authorised to manipulate and perform work on the RM6 unit. protective equipment For each operation, it is mandatory to use safety equipment appropriate: - Personal Protective Equipment (PPE) - Collective Protection Equipment (CPE) Eye protection must be worn Safety overalls must be worn Safety gloves must be worn Safety helmet must be worn Safety boots must be worn Ear protection must be worn maintenance rules NEVER USE SOLVENTS AND ALCOHOL WE DRAW YOUR ATTENTION TO THE RISK OF USING HIGH PRESSURE CLEANING PROCESSES 4 07897073EN01 revision : 11 general description G circuit breaker and switch function C DKL N F E P B A M H IDI A : operating mechanism front plate comprising the mimic diagram B : information plates C : earthing switch operating shaft D : switch operating shaft E : function position indicator F : voltage indicator G : LV connection access trunking H : connection bushing access panel K : VIP30/35 and VIP300 protection relays L : D function opening pushbutton fuse - switch and switch G function M : rating plate N : pressure switch or gauge label P : pressure switch or gauge N F E P C D B A J H IQI A : operating mechanism front plate comprising the mimic diagram B : information plate C : earthing switch operating shaft D : switch operating shaft 07897073EN01 revision : 11 E F G H : function position indicator : voltage indicator : LV connection access trunking : connection bushing access panel J : rating plate N : pressure switch or gauge label P : pressure switch or gauge 5 ”switchboard coupling” switch and circuit breakers Example presented : 1: DE- BC station with earthing switch D F A B D G B C A C F E E 2: DE- IC station with earthing switch 2 1 A: control panel featuring the mimic panel B: earthing switch operating shaft C: switch operating shaft D: voltage indicator E: connection bushing access panel F: rating plate G: characteristics plates cable connection function A: control panel featuring the mimic panel B: earthing switch operating shaft C: switch operating shaft D: voltage indicator E: connection bushing access panel F: plate characteristics A Exemple presented : DE- O B A: characteristics plate B: rating plate C: connection bushing access panel C metering cubicle with LV compartment 1 1 without LV compartment 5 3 2 4 1: LV compartment 2: voltage transformer access panel 3: characteristics plate 6 4: access panel to current transformer 5: LV compartment 07897073EN01 revision : 11 single- line diagramms NE = No Extensible DE = Double Extensible LE = Left Extensible RE = Right Extensible DE - IIBI RE - DIDI NE - D TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER’ TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER’ NE - IQI DE - III NETWORK ’SWITCH ’ TRANSFORMER PROTECTION BY ’FUSE- SWITCH COMBINAISON’ DE - DD TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER ’ 07897073EN01 revision : 11 DE - IDD TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER’ LINE PROTECTION BY ’CIRCUIT- BREAKER’ NE - IDI TRANSFORMER PROTECTION BY’ CIRCUIT- BREAKER’ DE - IIBc SWITCHBOARD COUPLING ’CIRCUIT- BREAKER’ 7 ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... 8 07897073EN01 revision : 11 instructions for putting the RM6 into operation prior to energising Check that the connection bushings are fitted with connectors or with insulating caps. Check that the RM6 is connected to the substation earth. pressure check of unit in operation CAUTION unit with manometer Case 1: needle in green zone Case 2: ENERGISED RM6 UNIT The RM6 unit is operating normally. H The RM6 unit must be replaced urgently. H It can remain energised until replacement. H All opening or closing operations are forbidden. H To replace the RM6, power off the unit. H WARNING needle in red zone 07897073EN01 revision : 11 9 warning label recalls the safety rules unit with pressure switch LCD display check Press the “TEST” button. The LCD screen should display: If nothing is displayed, check that the 8- point connector on the pressure switch wiring harness at the rear of the LCD display is correctly connected. H Contact the after sales service. www.schneider- electric.com Note: The LCD display is selfpowered by piezoelectric buttons (“TEST” and “DENSITY SWITCH”). Pressing on one of these buttons will turn on the display for a few seconds. H pressure check Press the “DENSITY CHECK” button. The LCD screen displays: Case 1: OK The RM6 unit is operating normally. H 10 07897073EN01 revision : 11 Cas n° 2 : LOW / OK The RM6 unit must be replaced. It can remain energised until replacement. H All operations can be performed while energised. H H CAUTION Case 3: VERY LOW / NOT OK WARNING The RM6 unit must be replaced urgently. H It can remain energised until replacement. H All opening or closing operations are forbidden. H To replace the RM6, power off the unit. H warning label recalls the safety rules 07897073EN01 revision : 11 11 position of the VPIS or VDS voltage indicator units (optional) 1 2 3 1 and 3 :voltage presence on network cables. 2 : voltage presence downstream of fuses for a switch combination or on the outgoing cable for a circuit - breaker. VPIS- V1 : production until February 2009. VPIS- V2 : production starting from March 2009. VPIS presentation of VPIS- V1 and VPIS- V2 VPIS :Voltage Presence Indicating System, a case with 3 built - in lights. characteristics operating instructions Conforming to IEC 61958, relative to voltage presence. A A WARNING The indication provided by a VPIS- V1 or V2 alone is not sufficient to ensure that the system is de- energised. INFORMATION When the ambient lighting is particularly bright, it may be necessary to improve visibility by protecting the indication. 12 B B A : voltage presence indicator light (one for each phase) B : connection point designed for the connection of a phase concordance unit (one for each phase) 07897073EN01 revision : 11 phase concordance unit principle Phase concordance testing for VPIS- V1 and VPIS- V2 must be carried out each time a cable is connected to a functional unit. It is a way of making sure that all three cables are each connected to the corresponding phase of the substation. The principle of the phase concordance unit is that it allows a check of the phase concordance between 2 energised functional input units on the same substation. reminder of accessories that can be used for phase concordance test Phase concordance unit V1. (51191954FA) rules for the use of phase concordance unit Phase concordance unit V2. (VPI62421 WARNING IT IS IMPOSSIBLE TO CARRY OUT A PHASE CONCORDANCE TEST WITH 2 VPIS OF DIFFERENT TYPES Balanced phases : - the phase concordance unit light (1) is untit. Unbalanced phases : - the phase concordance unit light (1) is lit. 1 1 07897073EN01 revision : 11 13 rules for choosing phase concordance unit phase concordance unit functional unit 1 functional unit 2 V1 compatibility result corrective actions V1 OK V1 V2 V2 OK Replace VPIS- V1 by VPIS- V2. Use a phase concordance unit V2. OK Use a phase concordance unit V2. OK Replace VPIS- V1 units by VPIS- V2 units OR test with 1 phase concordance unit V1. OK Replace VPIS- V1 with VPIS- V2. V2 V1 V1 V1 V2 V2 V2 OK check before phase concordance test Please refer to the previous chapters in the event of test malfunctioning. TEST 1 2 Visual checking of the indicator lights on the VPIS units of functional unit 1 and of functional unit 2 Phase concordance unit check choice 14 On each functional unit test phases 1 and 3. RESULT ACTION The 3 indicator lights of each VPIS are on. The 2 functional units are energised, the VPIS units are operating and the check can continue. The 3 indicator lights of the VPIS are off. The functional unit is not energised or the VPIS is defective. Apply power to the functional unit. If VPIS- V1 remains unlit, replaced it by a VPIS- V2. One or 2 indicator lights unlit. The VPIS is probably defective. Replace by a VPIS- V2. functional unit 1 You can test. functional unit 2 You cannot test them. The choice of the phase concordance unit is wrong or it is not functionning correctly. 07897073EN01 revision : 11 phase condordance test The 3 indicator lights of the 2 VPIS are lit and the phase concordance unit is correct, meaning that phase concordance test can be performed. lexique phase concordance unit LED lit LED unlit or Functional unit n° 2 L1 L2 L3 Conclusion regarding phase concordance L1 L2 Connection is satisfactory. L3 L1 L2 Reverse the MV cables connected to L1 and L2 on one of the 2 functional units Functional unit n° 1 L3 L1 L2 Reverse the MV cables connected to L2 and L3 on one of the 2 functional units L3 L1 L2 Reverse the MV cables connected to L1 and L3 on one of the 2 functional units L3 L1 L2 Change the position of each MV cable on one of the 2 functional units L3 L1 L2 Change the position of each MV cable on one of the 2 functional units L3 07897073EN01 revision : 11 15 RM6 equipped with VDS voltage detection units B B VDS: Voltage Detecting System, unit with connectors used to plug in individual indicators. A: protective covers. B: connections points used to connect an individual indicator. A A A characteristics The voltage detector system equipping your RM6 is of the separate VDS type, HR system. It complies with standard IEC 61243- 5. instructions for using the interface Each time the interface is used, put back the protective covers. Do not use connectors enabling short - circuiting of the interface, in networks with unearthed or earthed neutral by resonant circuit. accessories usable at the interface Individual voltage indicator for HR system. Universal phase concordance unit. CAUTION The reliability of the information provided is guaranteed only by use of accessories conform to standard IEC 61243- 5: to use them, follow the instructions of the accessory manufacturer. Other devices must only be used at the interface if they exhibit the same dielectric strength as an indicator. 16 07897073EN01 revision : 11 choosing the HV fuses Dimensions of the Fusarc CF fuses (DIN) For installation of fuses of other manufacturers, please consult us. The rating of the fuses to be fitted in the RM6 protection function depends on the following factors (among others): H operating voltage. H transformer rating. H fuse technology (manufacturer). Ø Ø45 Dimensions of the Soléfuse fuses (UTE) 33 . L 33 27 Ø55 450 Various fuse types with striker with average energy can be fitted : - as per standard UTE NFC 13.100, UTE NFC 64.210 of the Soléfuse type. - as per recommendation IEC 282.1 and dimensions DIN 43.625 of the Fusarc CF type. Example: general case for protection of a 400 kVA – 10 kV transformer, 63 A Soléfuse fuses or 50A Fusarc CF fuses will be chosen. 35 H rated voltage rating (kV) rating to (A) 7,2 à 24 6,3 à 63 rating voltage (kV) rating to (A) lenght (mm) diamater to (mm) 12 10 à 20 292 50,5 25 à 40 292 57 50 à 100 292 78,5 24 Our products are guaranteed only with the fuses mentioned in this document. 125 442 86 10 à 20 442 50,5 25 à 40 442 57 50 à 63 442 78,5 80 à 100 442 86 To install fuses of other brands, please ask “Schneider Electric” support. IEC & UTE standards require that all 3 fuses are to be replaced after the fusion of one fuse. selection table (”) In the case of an external trip system (eg.:overcurrent relay). (rating in A, use without overload at –25C < < 40C). Solefuse operating voltage (kV) For any values inclued in the table, please consult us. In this case of an overload beyond 40° C, please consult us. A calculation must be carried out to guarantee coordination of fuse fuse- switches. (*)SIBA types fuses at 160A/12kV reférence 30- 020- 13. fuse type Please consult us. Transformer rating (kvA) 50 75 100 125 160 200 250 315 400 500 630 800 1000 31,5 31,5 63 63 63 63 63 10 16 16 31,5 31,5 31,5 63 63 63 63 15 16 16 16 16 16 43 43 43 43 43 63 20 16 16 16 16 16 16 43 43 43 43 43 1250 1600 2000 Rated voltage (kV) (norme UTE NFC : 130.100, 64.210) 5,5 16 7,2 24 63 Fusarc CF et SIBA (*) (General case, IEC 60282- 1, standard CEI62271- 105 (to replace IEC 60420) and DIN 43625 standard) 3 20 31,5 40 50 50 63 80 100 125* 160” 3,3 20 25 40 40 40 63 80 80 125* 125* 160“ 4,2 20 25 25 40 50 50 63 80 80 100 125* 160“ 5,5 16 20 25 25 40 40 50 63 80 80 100 125* 160” 6 16 20 25 25 31,5 40 50 50 63 80 100 125* 160” 6,6 10 20 25 25 31,5 40 50 50 63 63 80 100 125* 160” 10 10 10 16 20 25 25 31,5 40 50 50 63 80 100 125* 11 10 10 16 20 20 25 25 40 40 50 50 63 80 100 13,8 10 10 10 16 16 20 25 31,5 40 40 50 50 63 100* 15 10 10 10 10 16 20 25 31,5 31,5 40 50 50 63 80 100* 20 10 10 10 10 16 16 20 25 25 31,5 40 40 63 63 80 100* 22 10 10 10 10 10 16 16 20 25 31,5 40 40 50 63 80 100* 07897073EN01 revision : 11 12 125* 24 17 fitting HV fuses CAUTION Before performing these operations, close the earthing switch. CAUTION Repeat the operations below for all 3 fuses. To remove the cover: lift it and pull it towards you. The instructions are visible on the cover. Release the plug and push the extraction handle manually to release the plug (tap with the palm of your hand to detach the plug seal if necessary). Fit the plug as far as it will go and swivel it to the left to extract it. Let the plug hang. Ensure the plugs are clean before fitting them. To clean the plugs, consult the preventive maintenance section. 18 07897073EN01 revision : 11 fitting a DIN fuse (Fusarc CF) rm6 On no account must a fuse that has been knocked be installed. A test prior to installation using a monitor is recommended. Recover the centring devices in the bag supplied with the substation. Insert the fuse in the compartment.Fit the centring device on the fuse. Insert the plug pins in the plinth and swivel it round to the right. Fix the fuse on the plug using a torque wrench with end BTR no. 5 and insert the fuse in the compartment. Tightening torque: 15 Nm. Insert the plug and fuse assembly in the compartment.Insert the plug pins in the plinth and swivel it round to the right. Press to insert the assembly in the downstream clamp. fitting an UTE fuse (Solefuse) CAUTION On no account must a fuse that has been knocked be installed. A test prior to installation using a monitor is recommended. direction for mounting a fuse with striker CAUTION Fuse blowing releases a striker that causes three- phase opening of the switch and prevents it from reclosing. Percuteur Striker pin Schlagstift Percussore The end of the fuse equipped with the striker is marked. 07897073EN01 revision : 11 The technical data and mounting direction of the fuse are printed on the body.(striker facing upwards). 19 locking the plug Make sure that the handle trunnions are inserted in the plinth slots and lock the plug manually by folding down the operating handle. sealing of DE- Mt cubicle without LV compartment Plug with fuse blowing release, used to cause three- phase opening of the switch. Press the switch to position it. A: rear sealing B: front sealing C: seal + wire; steel C B A A A 20 07897073EN01 revision : 11 with LV compartment A: sealing of the LV compartment B: seal + wire steel B 07897073EN01 revision : 11 21 ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... 22 07897073EN01 revision : 11 instructions for putting into operation the protection relay for circuit- breaker CAUTION The VIP parameters must be set correctly in order for the circuit breaker function well. VIP400 / VIP410 presentation The User- Machine Interface (UMI) on the front panel of VIP relays consists of a display, LEDs and keys. A sealable pivoting flap can prevent access to the setting keys by unauthorized persons. 1: 2: 3: 4: Display Status LEDs Fault indication LEDs Zone for a user- customizable label with pictograms of the fault indication LEDs 5: Acknowledgement key 6: Identification label 7: Sealing ring 8: Selection keys 9: Key for selecting menus and testing LEDs. When the VIP is not supplied with power, this key can also be used to start the VIP from the battery in order to enter settings 10: Menu pictograms 11: Menu selection pointer 12: Battery compartment and socket for connecting the pocket battery module 13: Settings protective flap 14: Confirm entry key 15: Abort entry key 16: Setting keys status LEDs Pictogram Flap closed Flap open The status LEDs provide information about the VIP general status: H Function VIP400 VIP410 Green LED: auxiliary power supply present - H Red LED permanently on: VIP unavailable (VIP in the fail- safe position). H H Red LED flashing: a failure has been detected but does not involve the VIP going into the fail- safe position. H H Yellow LED flashing: communication active - H INFORMATION- ADVICE NRJED311206EN : reference manual is available on : www.schneider- electric.com or call your sales representative who will put you in contact with the closet SCHNEIDER- ELECTRIC service center 07897073EN01 revision : 11 23 operation VIP relays have fault indication LEDs. They flash to indicate a fault, as shown in the table below : Fault Indication LEDs Pictogram Ext. Fault VIP400 VIP410 Detection of a fault by the phase overcurrent protection or in the event of tripping by the temporary test mode H H Detection of a fault by the earth fault protection H H Detection of a fault by the thermal overload protection H H Tripping by a volt- free contact connected to the external trip input - H After a trip, the fault indication LEDs are powered by the battery embedded in the VIP or by the VIP410 auxiliary power supply. Fault indication by the LEDs can be stopped: H by pressing the Reset key H automatically by the reappearance of a current in the network higher than the pick - up current H automatically after 24 hours H by remote control order via the communication (VIP410) For the first 3 LEDs, faster flashing may occur before the protection trips, to indicate the following information : Pictogram Overshoot Overshoot of the instantaneous set point for phase overcurrent protection (I> or I>> or I>>> pickup outputs Overshoot of the instantaneous set point for earth fault protection (Io> or Io>> pick - up outputs) Overshoot of the alarm set point for thermal overload protection note 24 In custom mode, the protection set points may not be assigned to the Mitop trip unit output. In this case, the fault indication LED may be active, without being associated with the circuit breaker trip. Depending on the application, this can indicate the presence of a fault without tripping the circuit breaker The fault indication LED pictograms can be customized by sticking a label to the right of the LEDs. 07897073EN01 revision : 11 display The display is an LCD unit. It is only back - lit on the VIP410, when the auxiliary power supply is present. menu organization All the data available in the VIP relay is divided between 3 menus: H The metering menu contains the current measurements, peak demand currents, load history, event records, fault trip counter and the breaking current history. selecting a screen in a menu First line: symbols for electrical values or function name H Second line: displays the values of measurements or parameters associated with the function H A menu pointer, on the left, it is pointing to the pictogram for the selected menu H Each VIP function is presented in a screen consisting of the following items: The protection menu contains the essential settings for setting up the protection functions H The parameters menu contains the parameters that are used to adapt VIP operation to particular applications. H Etape 1 When a VIP is new, all the parameters in this menu have a default value. The protection functions are operational even with the parameters menu default values. Action Press the key to select one of the 3 menus The menu pointer indicates the selected menu : : Metering menu : Protection menu : Parameters menu 2 Press the or keys to scroll through the screens in the select menu, until the desired screen diplayed default screen A default screen is displayed automatically 3 minutes after the last keystroke. This default screen is the screen displaying the phase currents. operation according to the power supply mode (VIP400) The VIP400 is a stand- alone protection relay powered by its current sensors. When current is present in the medium- voltage (MV) network, the protections and the display work and it is possible to enter settings and view measurements. The current in the MV network on which the VIP operates is called the ’pick - up current’. When no current is flowing through the circuit breaker (for example circuit breaker open), or when the current in the MV network is too low, the VIP is off and nothing appears on its display. If current appears, the protection functions are activated and trip the circuit breaker - or not - according to their settings. The additional time taken by the VIP to start when current appears is called the ’pick - up time’. More information on the value of the pick - up current and the pick up time are available in the VIP Function Characteristics Please consult the reference NRJED311207EN. 07897073EN01 revision : 11 25 operation according to the power supply mode (VIP410) The VIP410 is a relay with a dual power supply. It is powered both autonomously by its sensors and by the auxiliary power supply. Like for the VIP400, the self- powered supply allow the protection functions to work even if the auxiliary power supply fails. The auxiliary power supply is used to power functions that do not depend on the current being present in the MV network. These functions are marked in the function table (Please consult the reference NRJED311207EN). The auxiliary power supply must be present in order them to work. integral battery The VIP has an integral battery. It is used to: H activate the user- machine interface in order to enter settings when the VIP is not supplied with power H illuminate the fault indication LEDs when the VIP is no longer supplied with power after giving theopening order to the circuit breaker H power the internal calendar When the VIP is not supplied with power: Pressing and holding down the key will activate battery- powered operation of the user- machine interface. It is then possible to access the menus in order to enter settings. In this case, the display turns off automatically after 3 minutes of inactivity on the keypad. H The pocket battery module is an accessory that can be connected to the front panel of VIP relays. It contains a battery that can be used to power the VIP in order to: H enter settings if the integral battery is missing and if the VIP is not powered by the current sensors H test the VIP, please consult the reference NRJED311207EN. H pocket battery module The protection functions are activated automatically if the current reappears. The integral battery plays no part in operating the protection functions. The protection functions work even when there is no battery. NOTE : H in battery operation mode, the VIP processor runs with a reduced clock frequency to ensure the battery life is maintained. As a result, the user- machine interface may be slower to react. during a setting operation with the VIP powered by its internal battery alone, the clock display is not refreshed on screen. However the internal clock increments normally. H display the cause of the last trip by the VIP’ please consult the reference NRJED311207EN. H more information on connecting the pocket battery module to the VIP is available in the Connection to the VIP ’ please consult the reference NRJED311207EN. battery module The pocket battery module should only be used during maintenance or commissioning by qualified personnel and must never be left permanently connected to a running VIP. 26 LV434206 07897073EN01 revision : 11 presentation of VIP40/45 1: Display 2: Lugs for opening the transparent protective flap 3: Transparent protective flap 4: Imax. peak demand display button 5: Sealing ring 6: Test/Reset button 7: Status LED 8: Space for a user- customizable label 9: Trip fault indication LED 10: Identification label 11: Symbol indicating that it is necessary to read the manual 12: Battery display 12 The display is an LCD unit During operation, the display indicates the value of the current on each phase in succession Each phase remains displayed for 3 seconds before automatically changing to the next. The display is in amps, on three digits. The display is in amps, on three digits. NOTE: If the phase current is less than the pick - up current (Please you consult the reference NRJED311207EN), the VIP is not activated and the display is off. lugs for opening the transparent protective flap To open the flap, pull both lugs simultaneously. The flap pivots open on its 2 bottom hinges. Imax. button: peak demand display Pressing the Imax. button triggers a sequence displaying the peak demand currents for all 3 phases in succession. After this sequence, the VIP automatically returns to displaying the phase currents. H H INFORMATIONINFORMATION- ADVICE CONSEIL NRJED311207EN : reference manual is available on : www.schneider- electric.com or call your sales representative who will put you in contact with the closet SCHNEIDER- ELECTRIC service center 07897073EN01 revision : 11 27 Test/Reset button After a trip, pressing this button stops the flashing trip indication. This button can also be used to: H test the built - in battery. When pressing the Test/Reset button, the fault indication LED lights up immediately to indicate that the battery is OK. perform the ’lamp test’ if the relay is supplied with power. Pressing the Test/Reset button for 5 seconds causes all the display segments and the status LED to light up, and displays the software version number. H voyant d’état Pictogram Color Red Event LED permanently on: the VIP has gone into the fail- safe position following detection by the embedded self- tests of the failure of one of its internal components, involving a risk of nuisance tripping. In this case, the VIP is no longer operational NOTE: This LED may light up briefly when the VIP is energized: this is normal and does not indicate a failure. LED flashing: the VIP has detected a failure not involving a risk of nuisance tripping. In this case, the VIP has not gone into the fail- safe position.Intervention is required as soon as possible (Please you consult the reference NRJED311207EN.) The LED stops flashing as soon as the failure disappears. space for user- customizable label There is a special space for a user- customizable label for the Trip LED. Trip LED: fault Indication The fault indication LED flashes to indicate that the VIP has sent a trip order to the circuit breaker. Aftercircuit breaker opening, when the VIP is no longer supplied with power by its sensor, the built - in battery makes the LED flash. The LED stops flashing: H automatically after 24 hours H when the current returns, on circuit breaker closing (if the current is higher than the pick - up current) identification Label The identification label on the front panel is used to identify the VIP: H product name H product reference H serial number symbol : necessary reading of manual The 28 when the Test/Reset button is pressed H when the pocket battery module is connected then disconnected NOTE: The VIP built - in battery only supplies power to the fault indication LED and displays the type of fault. It has no role in operating the protection functions. H symbol indicates that it is necessary to read the VIP reference manual before working on the product. 07897073EN01 revision : 11 VIP40/45 settings front panel When the protective flap is opened, you can enter the protection settings by means of the rotary switches. VIP40 To do this, use a 3 mm flat blade screwdriver VIP45 1 Phase overcurrent protection adjustment dial 1 Phase overcurrent protection adjustment dial 2 Setting range selector switch 2 Setting range selector switch 3 Advanced settings protective cover 3 Earth fault protection set point adjustment dial 4 Connection port for the pocket battery module 5 Trip test button 5 Advanced settings protective cover 4 Earth fault protection time delay adjustment dial 6 Connection port for the pocket battery module 7 Trip test button phase overcurrent protection adjustment dial The setting is entered directly in Amps using the 9- position switch.(I>) The selector switch has 2 graduated rings. The range is selected using the setting range selector switch. earth fault protection adjustment dial The set point is set directly in Amps using the 9- position switch..(Io>) The time delay setting is entered directly in seconds using the 9- position switch.(to>) NOTE: the earth fault protection adjustment dials are only found on the VIP45. temporary display of the changed setting When VIP relays are energized, they display temporarily the value of the setting after a switch has changed position. advanced settings To access the advanced settings, remove the advanced settings protective cover. 07897073EN01 revision : 11 Both settings can be entered using a single selector switch: H discrimination with the LV CB H earth fault protection inrush current delay 29 connection port for the pocket battery module The connector is used to connect the pocket battery module so that the VIPs can be energized and tested. Please consult the reference NRJED311207EN NOTE:the pocket battery module should only be used during maintenance or commissioning by qualified personnel and must never be left permanently connected to a running VIP. Trip test button The Trip test button is used for testing VIPs. A 5 mm diameter pointed tool is needed to activate it. More information is available in the section describing Commissioning. Please consult the reference NRJED311207EN frequency The network frequency (50 Hz or 60 Hz) is a parameter that must be known for operation of the VIP40 and VIP45 signal processing algorithms. They therefore have an automatic frequency recognition system. The recognized value (50 Hz or 60 Hz) is stored and the VIP works permanently with this value. This stored value will be used each time the VIP starts For the VIP to recognize the network frequency and store it, it has to detect a current on phase 1 for a minimum period of 5 seconds in the range 50 Hz +/- 2 Hz or 60 Hz +/- 2 Hz. This detection happens when the VIP starts. 30 07897073EN01 revision : 11 For further information on the Sepam series10, download the reference manual from our website: www.schneider- electric.com Sepam series 10 protection of HV/LV transformers protection of HV networks Sepam 10 relays fitted to RM6 circuit breakers require an auxiliary power supply. Sepam 10A: - provides protection against overloads (thermal overload protection), phase- phase faults and phase- earth faults. It has: - 4 logic inputs and 7 configurable relay outputs - a communication port Sepam 10B: - provides protection against overloads (thermal overload protection), phase- phase faults and phase- earth faults. It has: - 3 configurable relay outputs Functions Protection types Earth current maximum protection Standard Very sensitive Phase current maximum protection Thermal overload protection Cold load pickup (low sensitivity of phase and earth current maximum protection settings) Logic discrimination Await logic emission Await logic reception External tripping Measurements Measurement of earth current Measurement of phase currents Phase current maximum readings Control and monitoring Circuit breaker tripping and rearmament locking Trip signalling Tripping circuit monitoring Circuit breaker remote control Recording of last fault Recording of last 5 events Communication Modbus IEC 60870- 5- 103 Function available Function available depending of Sepam model Inputs / Outputs (Number) Earth current inputs Phase current inputs Relay logic outputs Logic inputs RS 485 communication port 07897073EN01 revision : 11 31 earth current (ANSI 50N- 51N) Earth current maximum protection enables overcurrents due to phase- to- earth faults to be detected. It makes use of the measurement of the earth current’s fundamental component. 2 independent thresholds (Io> and Io>>) H the lower threshold (Io>) can be set to either a definite time (DT) or an inverse time (IDMT) curve, with the choice of standardised curve (IEC, IEEE, RI) and the possibility of activating an inverse time duration. H the upper threshold (Io>>) has only a definite time (DT) setting. The minimum setting gives instantaneous operation (ANSI 50 function). Depending on the level of sensitivity required, there are 2 types of Sepam: Sensitivity Sensor Standard 3 CT CRa 200/1 or CRb 1250/1 Very sensitive CSH200 core balance CT phase current maximum protection (ANSI 50- 51) Phase current maximum protection enables overcurrents due to phase- to- phase faults to be detected. It makes use of the measurement of the fundamental component of the currents from the 3 phase CTs. thermal overload protection (ANSI 49RMS) This protection enables cables and HV/LV transformers to be protected against overloads based on the measurement of absorbed current. This protection uses a thermal model based on current measurements to evaluate temperature rise. The current used for this protection is a 3- phase RMS current that takes into account up to 13th order harmonics. 32 2 independent thresholds (I> and I>>) H the lower threshold (I>) can be set to either a definite time (DT) or an inverse time (IDMT) curve, with the choice of standardised curve (IEC, IEEE, RI) and the possibility of activating an inverse time duration. H the upper threshold (I>>) has only a definite time (DT) setting. The minimum setting gives instantaneous operation (ANSI 50 function). This protection has 2 settings: maximum allowable continuous current, which corresponds to the maximum thermal withstand of the equipment to be protected (this allowable continuous current corresponds to a temperature rise of 100%) H heating/cooling time constant of the equipment. H 07897073EN01 revision : 11 low sensitivity of phase and earth current maximum protection settings (Cold Load Pick - Up) The cold load pickup function avoids nuisance tripping when the equipment is powered- up, especially after a long break in operation. It allows the protection thresholds to be temporarily increased. High currents at cold load pickup may be due to: H simultaneous powering- up of all the loads in an installation. H power transformer magnetising currents. H motor starting currents. Protection concerned Operating means Phase current maximum protection After circuit breaker closing, the tripping thresholds (I> or I>>) are increased or blocked for the set duration. Earth current maximum protection After circuit breaker closing, the tripping thresholds (Io> or Io>>) are increased or blocked for the set duration. Or The protection is restrained by the detection of sensor saturation (measurement of 2nd order harmonic level). logic discrimination (ANSI 68) This function achieves: H tripping discrimination in the event of a short - circuit between phases, or from phase to earth, for all network types H reduced tripping time of the circuit breaker that is closest to the source. external tripping The Sepam series 10A enables, via a logic input, a tripping order from an external protection means to be taken into account. earth current measurement This measurement enables the value of the fundamental component of the earth current to be displayed. phase current measurements These measurements enable the RMS value of the phase currents to be displayed; it takes into account up to 13th order harmonics. phase current maximum readings This function enables the largest average current value of each of the 3 phases to be displayed, as well as giving the highest absorbed current during load peaks. 07897073EN01 revision : 11 All Sepam series 10B and 10A are able to emit an await logic order should a fault be detected by the phase and earth current maximum protection functions. Only the Sepam series 10A is able to receive an await logic order that blocks its tripping signal. A safety mechanism ensures the protection operates in the event of a fault with the blocking signal wiring. This function displays the 3 phase currents. 33 latching / resetting ANSI 86 Output relay latching can be configured. Latch tripping orders are memorised and must be reset in order to put the equipment back into service. circuit breaker remote control - Sepam 10A This function enables remote operation of the circuit breaker via the communication. A Sepam logic input allows the operating mode (local or remote) to be selected. recording of the last fault Sepam 10B This function enables the characteristics of the last fault to be displayed. The Sepam indicates the cause of the fault, the value of the phase currents and the earth current when the fault occurred, and the time and date of the fault. This information is memorised until the next fault occurs. Cause of faults recorded: I>, I>>, Io>, Io>> and thermal protection. recording of the last 5 events - Sepam 10A This function enables the characteristics of the last 5 events to be displayed. For each event, the Sepam indicates its cause, the value of the 3 phase currents and the earth current when the event occurred, and the time and date of the event. Events are numbered in the order they occur and the last 5 can be displayed. The following events are recorded: H tripping due to I>, I>>, Io> or Io>>, thermal protection H tripping by external input H tripping circuit fault H circuit breaker opening and closing via the communication H tripping due to logic discrimination safety protection. communication Sepam 10A One RS 485 communication port. 2 protocols available, chosen by configuration: Modbus, IEC 60870- 5- 103. Communication enables the following functions to be carried out remotely: H measurement readings, H status readings H event readings and time- stamped measurements (2 tables of 100 events available) H time setting and synchronisation H remote control orders. operating language When delivered, the default language is English. The following languages can be selected: UK English, US English, Spanish, French, Italian, German, Turkish, Portuguese. 34 Resetting can be done: - by pressing the Reset button; - via the Sepam 10A communication port. 07897073EN01 revision : 11 standard assignment of inputs/outputs and customised configuration The configuration is customised using the Sepam humanmachine interface, without the need for a PC. Sepam 10A Logic inputs Standard assignment Configurable I1 Circuit breaker open No I2 Circuit breaker closed No I3 External tripping Yes I4 Local- Remote Yes Relay outputs Standard assignment Configurable O1 Circuit breaker tripping Yes O2 Locking of circuit breaker latching Yes O3 Trip signalling Yes O4 Circuit breaker remote closing Yes O5 Await logic emission Yes O6 Trip circuit fault signalling Yes O7 Watchdog No Relay outputs Standard assignment Configurable O1 Circuit breaker tripping Yes O2 Locking of circuit breaker latching Yes O3 Trip signalling Yes Sepam 10B 07897073EN01 revision : 11 35 human- machine interface front panel The Human- Machine Interface on the Sepam front panel is made up of a display, indicator lamps and buttons. Access to the setting buttons by unauthorised personnel can be prohibited using the pivoting and lead- sealable cover. The illustrations below show the 2 positions of this cover. 1: 2: 3: 4: Display Status indicator lamps Fault indicator lamps Zone for a customised pictogram label of fault indicator lamps 5: Button for resetting the Sepam and the maximum value readings 6: Identification zone 7: Lead sealing ring 8: Selection buttons 9: Menu selection and indicator lamp test button 10: Menu pictograms 11: Menu selection pointer 12: Battery compartment (Sepam series 10A) 13: Settings protection cover 14: Entry validation button 15: Entry abort button 16: Setting buttons status indicator lamps The status indicator lamps provide information on the Sepam status. Pictogram Function Sepam series 10 Green lamp: Sepam powered - up Red lamp: Sepam unavailable (Sepam in fall- back position) Yellow lamp: communication active 36 07897073EN01 revision : 11 fault indicator lamps The fault indicator lamps flash as described in the table below to signal a fault: Pictogram Sepam series 10 FThreshold exceeded Phase current maximum protection instantaneous threshold exceeded (I> or I>> pickup output) Earth current maximum protection instantaneous threshold exceeded (Io> or Io>> pickup output) Thermal protection alarm threshold exceeded The fault indicator lamp is latched in standard operating mode. If, when customising the operating mode (at the time of commissioning), the latching of a fault indicator lamp has been cancelled, the fault indicator lamp goes out as soon as the fault is no longer present. Pictogram For the first 3 lamps, they may flash at a faster rate before the protection trips to signal the following information: Fault Sepam series 10 Detection of a fault by the phase current maximum protection Detection of a fault by the earth current maximum protection Detection of a fault by the thermal protection External tripping identification zone VIP400 The identification zone on the front panel enables a Sepam to be identified: 1 : Identification code 2 : Reference 3 : Supply voltage 4 : Serial number VIP410 Refer to the Identification section for the identification code key. 07897073EN01 revision : 11 37 identification identification code The identification code of a Sepam series10 is an alphanumeric code that defines the main functions of the Sepam. It is made up of several fields: Sepam 10 family Model B: phase and earth current maximum protection settings A: phase and earth current maximum protection settings, logic inputs and communication port Number of current inputs 4: 3 phase current inputs + 1 earth current input Sensitivity of earth current maximum protection 1: standard (0.1...24 In) CT 3: very sensitive (0.2...24 A and 2...240 A) CSH200 Supply voltage A: 24...125 V DC and 100...120 V AC E: 110...250 V DC and 100...240 V AC operating instructions accessing information display 38 During operation, when the settings protection cover is closed, the user has access to the following: H reading of measurements, settings, protection types and parameters. H local fault signalling. H last fault resetting. H reading of last recorded faults. H resetting of maximum values. H testing of indicator lamps and the display. 1. Press to select one of the 3 menus. 2. The pointer shows the selected menu: Measurements Protection types Parameters 3. Press and to select the information to be displayed. 07897073EN01 revision : 11 resetting 1. A fault detected by the Sepam is signalled by: - a message on the display - a flashing indicator lamp 2. Press to reset the fault. 3. The indicator lamp goes out and the message disappears setting instructions Knowledge of electrical network protection is required for choosing appropriate settings. Only those people with the required skills are authorised to set the Sepam. Not abiding by this instruction may cause injury and damage to equipment and property. All protection is inhibited by default. To make the protection operational, it must be activated and set - up when commissioning the RM6. CAUTION accessing parameters and settings 07897073EN01 revision : 11 1. Open the settings protection cover. 2. Press to select the protection or parameter menu. 3. Select the protection type or parameter to be set using and . 4. Enter the password if requested. 5. Press to select the value to be modified. 6. The selected value flashes. 7. Press or to increment or decrement the value. 8. Press to validate the new value or press to cancel. 9. The value stops flashing. 39 setting ranges The setting ranges that can be used for the lower threshold depend on the circuit breaker type: D or B, and the type of sensors fitted to the RM6. Circuit breaker type Type of sensors Functions D B Cra 200/1 CRb 1250/1 Code ANSI Phase current 50- 51 20- 200A 125- 630A Earth current 50N- 51N 20- 200A 125- 630A Very sensitive earth current 50G- 51G 2- 240A 0,2- 24A 2- 240A 0,2- 24A factory set parameters Sepam 10A and 10B standard earth Sepam 10A and 10B very sensitive earth The transformer ratios of the phase and earth CTs (Io by summing) are factory set. If by error you have deleted the settings, you can find the type of CT fitted to your RM6 in the inspection report supplied with the equipment and on the CT support, where a label with the information can be found (see image aside). The factory set measurement range is 2- 240A; this can be changed. To change to the 0.2- 24A range, you should: 1- Bring up Io 0.2- 24A in the RATING screen. 2- 40 Change the wiring at the CSH input, terminals 11- 21 on the Sepam connector marked B. 07897073EN01 revision : 11 configuring the logic inputs For the Sepam series10 A, logic input operation must be adapted to the type of voltage: AC or DC. The type of voltage must be configured in the LOG INPUTS screen of the parameter menu. The default value is DC. accessing phase current inputs Connector B for connecting the current sensors is a short - circuiting connector. It can be disconnected on- load; disconnecting it does not open the sensors’ secondary circuit. Remove the short - circuiting connector without disconnecting the wires connected to it. Use another connector to connect your generator. 07897073EN01 revision : 11 B 41 ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... 42 07897073EN01 revision : 11 operating instructions operating and viewing substation condition A E description A: earthing switch operating shaft B: switch function operating shaft C: fuse- switch combination function operating shaft D: position indicator E: fuse- switch combination function opening pushbutton F: padlocking handle D F B C closing a switch Initial state: H switch open H earthing switch open Left the operating shaft protective cover. Activate the switch operating mechanism to the right. The indicator moves to the closed position, and access to the earthing switch operating shaft is blocked. opening a switch Initial state H switch closed H earthing switch open Activate the switch operating mechanism to the left. 07897073EN01 revision : 11 The indicator moves to the open position, and access to the earthing switch operating shaft is freed. 43 closing an earthing switch Initial state: H earthing switch open H switch or circuit - breaker open DANGER If the incoming line is powered on, do not close the earthing switch. Lift the operating shaft protective cover. Separate the pallet with the end of the lever, then activate the earthing switch operating mechanism to the right. The indicator moves to the earth position and access to the earthing switch operating shaft is blocked. Separate the pallet with the end of the lever, then activate the switch operating mechanism to the left. The indicator moves to the open position, and access to the switch or circuit - breaker operating shaft is freed. Lift the operating shaft protective cover. Activate the switch operating mechanism to the right. The indicator moves to the closed position, and access to the earthing switch is blocked. Press the opening pushbutton of the circuit - breaker or fuse- switch combination. The indicator moves to the open position, and access to the earthing switch is freed. opening an earthing switch Initial state : H earthing switch closed H switch or circuit - breaker open closing a circuit - breaker or fuse - switch combination Initial state : H circuit - breaker or fuse- switch open H earthing switch open opening a circuit - breaker or fuse - switch combination Initial state : H circuit - breaker or fuse- switch open H earthing switch open 44 07897073EN01 revision : 11 operating safety Switch or circuit - breaker closed... ...the earthing switch is blocked. Earthing switch closed... ...the switch or circuit - breaker is blocked. key- locking (optional) The switches and the circuit - breaker are locked in the open position. The earthing switches are locked in position : H open H open/closed There are various possible locking diagrams. H network switch and network outgoing circuit - breaker - semi- crossed locking - crossed locking H Transformer outgoer : - RM6/ transformer - RM6/ low voltage - RM6/ ransformer/low voltage padlocking Switch and earthing switch with a degree of protection IP3X, fit a padlock 6mm < handle diameter < 8 mm. operating shaft padlocking handle 07897073EN01 revision : 11 45 padlocking the opening pushbutton Fit the padlock on the opening pushbutton 6mm < handle diameter < 8 mm. A: fuse- switch combined function or circuit breaker opening push botton. A A B with motorization lock option NEUTRALIZED VERSION B: circuit - breaker motorized C: position of the switch ON C C C ON : AUTHORIZED ENGINE OFF : LOCKED ENGINE OFF C OFF padlocking the operating shafts of the switch with the operating mechanism front plate removed fit a padlock 6mm < handle diameter < 8 mm. in one of the 2 marked holes. A: padlocking the earthing switch in the open or closed position B: padlocking the switch in the open or closed position padlocking the operating shafts of the circuit - breaker with the operating mechanism front plate removed fit a padlock 6mm < handle diameter < 8 mm. in one of the 2 marked holes. A: padlocking the earthing switch in the open or closed position B: padlocking the switch in the open or closed position 46 A B A B 07897073EN01 revision : 11 overcurrent indicator An overcurrent indicator of the Alpha M or Alpha E type can be optionally fitted one of the line switch. 4 detection thresholds are possible – 400 A, 600 A, 800 A, 1000 A. Alpha M type indicator 1 operation If the reaction current exceeds the pre- set threshold, the indicator will send an optical signal on the faulty phase. The signal will remain visible until it is manually reset. 2 1) Threshold overshoot optical signal, one for each phase. 2) Rotary resetting and operating test button (turn quickly). Alpha E type indicator 1 3 2 operation If the reaction current exceeds the pre- set threshold, the indicator will send an optical signal on the faulty phase. The signal will remain visible for a time that can be pre- set. 2 hours or 4 hours. Manual resetting is possible. 1) Threshold overshoot optical signal, one for each phase. 2) Time during which the signal remains visible. Resetting is automatic. 3) Resetting and operating test pushbutton. threshold change for Alpha M and Alpha E type indicator CAUTION To change threshold, cable appropriately according to the diagram opposite. The terminal block is placed behind the device. 07897073EN01 revision : 11 47 LV connection indicator Flair 2xD FLAIR 21D The Flair 21D, 22D and 23DV fault passage indicator is self- powered by the measurement sensors. A minimum 2A current is required in the MV cable to start up the Flair 21D display, an energy storage guarantees a 4 hours minimum autonomy. The Flair devices have an output contact for interfacing with a SCADA system. Flair 23DV has to be supplied from 24Vdc to 48 Vdc for a permanent display operating and for the outdoor lamp supply.(With a single zero sequence CT, self powering is not possible). Flair 22D/23DV can be connected to a voltage presence indicating system (VPIS) provided with a voltage output (VPIS- VO). In this case, for greater reliability, fault detection is confirmed by voltage absence without taking into account the current. FLAIR 22D, et 23DV detector pending fault ammeter mode 48 In the absence of a fault, a load current indication is displayed. The amperage of each phase L1 - L2 - L3 is displayed in succession with its reference on the left of the display. Example, For a load current of 80 A : for L1 then for L2 and for L3 When Flair 22D/23DV is provided with an earth CT (B type mounting), display of M2 and M3 only. For each phase: if I>720A display: if I±2A display: (Low Power). 07897073EN01 revision : 11 maximeter mode To access the maximeter function, press once the “Imax.” button. For each phase, an indication of the maximum load currents since the last reset is displayed. Example: for a max. current of 500 A in phase 1: followed by M2 and M3. then , The maximeters scroll only once. All the maximeter values are reset by simultaneous actuation of the “Test/Reset” and “Imax.” buttons during scrolling. When Flair 22D is provided with an earth CT (B type mounting), display of M2 and M3 only. detector in fault indication Event A : the current exceeds one of the thresholds set for a period ² acknowledge time. Event B : the line current disappears (or absence of U with VPIS- VO option, on Flair 22D/23DV) Fault indication is active when A is followed by B within a lapse of time of less than 70 s. Phase- to - earth fault detected : display of or or , (or if earth CT). the indicator lamp flashes (1 flash every 3 s) and the output contact is activated. H Phase- to - phase fault detected: display of (Over current), the indicator lamp flashes (2 flashes every 6 s) and the output contact is activated. For these 2 types of faults, the indicator lamp remains flashing until it is reset (Reset), which can be achieved by: H current recovery > 70 s, configurable time delay on Flair 22D/23DV (Reset active if “Automatic reset” is not on “OFF”) H U recovery, if VPIS- VO option on Flair 22D/23DV (Reset active if “Automatic reset” is not on “OFF”) H end of the time delay, (4 hours on Flair 21D, configurable on Flair 22D/23DV) H a press on external Reset H manual actuation of the “Test/Reset” button. H maintenance 07897073EN01 revision : 11 The Flair 21D fault passage indicator requires no maintenance (no electric cells or batteries to be changed regularly) H The lithium battery of the Flair 22D indicator should be changed about every 15 years. (for the battery replacement process, call your sales representative who will put you in contact with the closest : SCHNEIDER- ELECTRIC group service centre. You can log on to : www.schneider- electric.com) H The lithium battery of the BVP option (external indicator unit with incorporated battery) is to be changed every 15 years. H 49 settings The Flair devices (>2010) are a fault passage indicator without settings (automatic mode). However, it is possible to perform specific override settings. In manual mode, settings are made : using the 3 buttons located under the display, (Flair 22D/23DV). by micro- switches (drawing opposite).(Flair 21D) The changes are taken into account after a press on the “Test/Reset” button. H H In AUTO mode I>; I0>, the manual settings are not active. Test mode A press on the “Test/Reset” button activates Test mode. The indicator lamp flashes, and the BVP and the “OUT” output are activated until the end of the test. H The display successively shows and and (software version) H H setting parameter scrolling sequence in Test mode for Flair 21D (automatic on test mode) Setting of automatic fault detection (*) or Network frequency or Imax threshold “I >” (Over Current) (A) to Zero sequence threshold “Io>“ (Earth Fault) (A) timer reset to ammeter mode 10s or “Test/Reset” When ”Auto” is ”ON”: Flair 21D uses the following values for fault detection: H frequency = self- detection H zero sequence threshold = automatic fault detection for any fault > 20 A H Imax threshold = automatic fault detection for any fault > 200 A H H H H H 50 acknowledge time = 40 ms Inrush= 3s CT type = CT1 ( can be changed to CT2 by actualing the buttoms) Automatic reset = 70s (if automatic reset =on) Timer reset= 4h 07897073EN01 revision : 11 settings mode (Flair 22D and Flair 23DV) 07897073EN01 revision : 11 During the Test mode, a press on the button provides access to Settings mode (display ). 1) A press on the button displays the first parameter to be set 2) Several presses on the button scroll the parameters in a loop. At this stage, with no actuation of or during 10 s, the indicator returns to ammeter mode. 3) Press the button to display the current value of the selected parameter 4) Press the button again to activate setting of this value: the display flashes for 5 s 5) During flashing, press successively to display the desired value 6) Confirm by pressing the button; without confirmation within a period of 15 s, return to display of the parameters without change in the value. Each press on the “Esc“ (Return) button takes you back to the preceding stage. 51 connection BVP: External indicator unit with incorporated battery Connection of CTs to the 3 MV cables H Cable Length : 3 m max. H Cross section: max. 1.5 mm2 H CTR2200 : mounting without common point (6 wires) H MF1 : mounting with or without common point (4 or 6 wires) CTs connection SCADA output Important note (for MF1 split core CTs): H Mount the 3 CTs facing in the same direction H Run the screen earth braid of the MV cable back inside the CT. Type CT1 Réf. Product EMS58351 Flair 21D EMS58352 Flair 22D EMS58353 Flair 23DV 59925 CTR2200 Description Common point Fault passage indicator 6- wire mounting CTR2200 or MF1 CTs Phase CT for RM6 cubicle bushing CT2 59963 MF1 4- wire mounting MF1 CTs Phase CT for cable (split toroidal core) 59928 MFC3 3 crimp- on (pour MF1) connectors for 6- wire mounting Flair 22D and Flair 23DV CTs connexion (wires not supplied) 59962 Faisceau MF1 CT connector cable or MFH for 4- wires BVE: External indicator unit mounting (A or B type) 59922 Flair 21D BVP 59988 Flair 22D BVE 59927 MFH2200 External indicator unit SCADA output Earth CT (split toroidal core) VPIS- Vo Common point 4- wire mounting 6- wire mounting Type A Type A Type B Type A MF1 CTs MF1/MFH CTs MF1 CTs CTR2200 CTs Type C mouting ’single zero sequence CT’possible only with flair 23DV 52 07897073EN01 revision : 11 ammeter The Amp 21D is an ammeter, for cubicle, automatic and self powered. The Amp 21D comes into operation whenever the current is greater than 3 A on the network. Test L1 L2 L3 A Test button I max. I max. button Easergy Amp21D EMS58401 Load current indication standard operating measuring mode maximeter mode Equipment’s standard operating mode. The AMP 21D ammeter displays in succession, by scrolling, the currents on phases L1, L2 and L3, and saves to memory the maximum values. Maximeter mode (I max.) A press on the “I max.” button activates the Maximeter mode. This mode allows display of the I maximum values occurring on the three network phases since the previous initialization. At the end of the maximeters’display cycle, the Amp 21D automatically returns to Measuring mode. The maximeter is reset by simultaneously pressing the “Test” and “I max.” buttons. 07897073EN01 revision : 11 53 Test mode Choice of CT type: H The CT1 option corresponds to ( ref.59925) phase CTs H The CT2 option corresponds to ( ref.59963) phase CTs H Factory setting: CT1. connection of CTs to the 3 MV cables Cable length: max. 3 m Cross section: max. 1.5 mm2 H 3 phase CTs without common point on a screw - on terminal block (6 wires) H MF1: mounting with or without common point (4 or 6 wires) H H CT connection IMPORTANT (for MF1 split core CTs) H Mount the 3 CTs facing in the same direction H Run the earth braid of the MV cable screen back inside the CT. Assembly 6 wires CTR2200 or MF1 phase CTs Common point Assembly 4 wires MF1 phase CTs references Type Ref. Product Description EMS58401 Amp21D MV ammeter CT1 59925 CTR2200 Phase CT for RM6 cubicle CT2 59963 MF1 Phase CT for cable (split toroid) 59928 Set of 3 connectors for MF1 59962 CONNECTING HARNESS FOR MF1 54 3 crimp- on connectors (wires not supplied) Connecting harness for MF1 for assembly 4 wires (A or B type) 07897073EN01 revision : 11 voltage detection relay The VD23 is a voltage presence and absence detection relay. It uses the VPIS V2- V0 as sensor, and operates with a 24 or 48 Vdc external power supply. operation : automatic frequency detection Calibration: At power up, the VD23 automatically detects voltage presence and the network frequency, and then performs self- calibration. Measuring mode: 3 seconds after calibration, the VD23 displays, by scrolling, the percentages of the nominal voltage detected on each phase : calibration performed Line- to - neutral voltages 3s Line- to - line voltages 3s 3s 3s 3s 3s 3s 3s Detection of Voltage presence: When the voltage percentage becomes greater than the set threshold for all the configured phases, then the VD23 lights the voltage presence indicator and activates (or releases in inverted mode) relay R1. detection sequence Detection of Voltage absence: When the voltage percentage becomes less than the set threshold for all the configured phases, then the VD23 lights the voltage absence indicator and activates (or releases in inverted mode) relay R2. threshold paramater Configuration: voltages V1,V2,V3, direct mode R1: terminal = relay rest position: voltage loss on at least one of the phases R2: terminal = relay rest position: voltage presence on at least one of the phases A configurable time delay is applied for control of R1 and R2:T12 = time delay for R1 changeover upon voltage loss T11 = time delay for R1 changeover upon voltage recovery T21 = time delay for R2 changeover upon voltage lossT22 = time delay for R2 changeover upon voltage recovery 07897073EN01 revision : 11 indicator indicator 55 Mode selection Measuring mode Product name Test mode Software version Digits test Network frequency or Type of measurement Configuration mode Parameters defined by micro switches line- to- line line- to- neutral Parameters setup mode To set the parameter values, see the section below Relay output Phase 1 inverted measured direct Voltage presence Voltage absence Calibration mode configuration of thresholds and time delays The parameter values (white screen in the above diagram) can be modified as follows: SW 1 SW 2 SW 1 SW 2 56 3 4 5 6 not measured not measured Phase 3 Residual voltage measured measured not measured not measured % of nominal voltage (10% increments) Phase voltage threshold to Residual voltage threshold to % of nominal voltage (10% increments) Activation time delay R1 (direct) to 0 to 1 s (0.1s increments) 1 to 21 s (2s increments) Release time delay R1 (direct) to 0 to 1 s (0.1s increments) 1 to 3 s (0.5s increments) Phase voltage threshold to % of nominal voltage (10% increments) Activation time delay R2 (direct) to 0 to 1 s (0.1s increments) 1 to 21 s (2s increments) Release time delay R2 (direct) to 0 to 1 s (0.1s increments) 1 to 3 s (0.5s increments) or Forced calibration 1s when the value of the parameter is displayed, a press on the key causes the display to flash for 5 s H during flashing, press successively to display the desired value H Set to OFF to retain the last calibration performed Calibration performed normally Error in calibration: voltage levels too low confirm this value by pressing the button; without confirmation within a period of 15 s, return to display of the parameters without change in the value. Each press on the “Esc” button takes you back to the preceding stage. H EARTH FAULT DETECTION EARTHED OR IMPEDANT GROUNDING DETECTOR measured Automatic calibration suggested choice for VD23 settings VOLTAGE Phase 2 ISOLATED NEUTRAL COMPENSATED NEUTRAL V1+V2+V3+V0 V1.V2.V3.V0 R1 3 4 5 6 U12+U13+U23 U12.U13.U23. 3 4 5 6 U12+U13+U23 U12.U13.U23. R1 07897073EN01 revision : 11 access to the cable compartments access to the cable connection compartments without interlocking CAUTION The HV cables must be de- energised for access to the compartments. Open the switch and close the earthing switch. connection on busbar (O function and T function) WARNING To remove an access panel, remove the 2 upper screws, lift and pull towards you. THE COMPETE SWITCHBOARD (ALL THE RM6 CONNECTED TOGETHER) MUST BE DE- ENERGISED OPEN ALL SWITCHES CONNECTED TO THE BUSBAR CLOSE ALL ASSOCIATED EARTHING SWITCHES access to the cable connection compartments with interlocking (optional) Functional unit in operation, switch closed. The access panel is locked. Open the switch. The access panel remains locked. Close the earthing switch. The access panel is released. Access panel removed, the earthing switch can now be re- opened. Optionally Switch and circuit - breaker closing is inhibited if the access panel is removed. 07897073EN01 revision : 11 57 Earthing switch open: the access panel cannot be put back. If the connectors so allow, DC current can be injected to monitor cable insulation or search for faults. Close the earthing switch. Put back the access panel. Open the earthing switch. access to the MV compartment of the DE- Mt cubicle DANGER (B) Opening of panel (A) authorized only if : - all upstream connection(s) locked- out in OPEN position - all downstream connection(s) locked- out in OPEN position. H En optional: a key lock exists (example B) DANGER Intervention inside the DE- Mt cubicle is authorised only if: the 3 busbars are grounded, via a temporary connection or via an earthing switch (upstream or downstream). 58 (A) To remove the access panel (A), remove the 3 upper screws, then raise and pull toward yourself. 07897073EN01 revision : 11 preventive maintenance standard operating conditions CAUTION maintenance summarising table description operation material cleaning cloth cleaning sponge, clear water panelling earthing covers device panelling CAUTION We draw your attention to the risk of using high pressure cleaning processes. Schneider Electric cannot therefore guarantee the reliability of equipment that have been cleaned in this manner, even if cleaning was followed by lubrication. The main drawbacks of this process are: H deterioration due to jet pressure and impossibility of relubricating the inaccessible fixing points H risk of overheating due to presence of solvent on the contact zones. H elimination of special protections. Clean using a dry cloth. earthing covers CAUTION maintenance cycle and operations 07897073EN01 revision : 11 This operation can be performed in event of excessive soiling. Clean using a sponge and clear water. Do not use alcohol or other solvents to clean. This device is designed to operate for 30 years or for 1000 operations in normal conditions of use as per standard IEC 62271- 1. The following are recommended: - an O/C operation every 6 years for motorised functional units and/or functional units with a latching mechanism (Q and D/B function) - replacement of batteries is recommended every 4 years - inspection every 5 years of the condition of the mechanisms (pollution, corossion) and the cleanliness of the earthing covers (pollution). 59 harsh operating conditions To ensure proper operation of the RM6 in harsh operating conditions, we strongly recommend regular maintenance of the cubicle and its installation. Recommended inspection frequency: at least once a year During the inspection, check the 6 following points: 1 LV compartment 2 earthing covers symptoms: condensation, presence of humidity check: for rust on the LV electric and electronic parts solutions: dry the environment replace the damaged parts fit heating resistances (optional) symptoms: humidity, dust check: surface cleanliness solutions: dry the environment clean using a clean cloth and water (no alcohol or solvent) 3 mechanical operating mechanisms 11 symptoms: humidity, condensation on live parts 2 3 3 14 55 check: for red rust on moving parts solutions: find and treat the origin of condensation phenomena follow up the damage replace the operating mechanism if required (refer to reference: 07897270) 4 MV socket and cable symptoms: presence of corona discharge or odours check: connections (may be damaged) 6 6 trench symptoms: humidity check: for presence of water in the trench solutions: pump out water drain the trench (if necessary add sand) In case sand is added in the trench, take care that the cables are still fixed correctly and that no additional stress is added to the bushings 60 solutions: fit new sockets 5 fuse compartments symptoms: humidity + dust check: proper operation of the VPIS solutions: clean the outside surface of the fuse compartments using a cloth and clear water 07897073EN01 revision : 11 corrective maintenance foreword The corrective maintenance operations enable replacement of subassemblies. The operations quoted in the following summarising table can be performed by the customer or by Schneider Electric’s after- sales representatives. For any other maintenance operations, contact the representatives of your nearest Groupe Schneider. After each operation, perform the electrical tests according to current standards. - Nylstop (self - locking nut) Contact washer Locking rings Mechanical pin To access the various devices: open the switches H close the earthing switches H cut the supply to the LV circuits CAUTION H On replacement, all the accessories below must be replaced with new equipment. maintenance summarising table description réalisation replacing a voltage indicator SCHNEIDER ELECTRIC or Customer replacing a fuse (MV) SCHNEIDER ELECTRIC or Customer replacing the charging motor SCHNEIDER ELECTRIC or Customer replacing a printed circuit SCHNEIDER ELECTRIC or Customer replacing the indicating contact SCHNEIDER ELECTRIC or Customer replacement of the voltage presence unit (VPIS) type VPIS- V1 by type VPIS- V2 VPIS- V1: production until February 2009 removing the VPIS- V1 voltage presence unit A VPIS- V2: production from March 2009 onwards B CAUTION The screws (A) must be retained. Unscrew the 2 self- tapping screws (A). Remove the VPIS 1 voltage presence box (B). B Disconnect the VPIS1 voltage presence unit (B). 07897073EN01 revision : 11 61 contents of the kit VPIS- V2 1: 2: 3: 4: 1 indicator unit cable gland seals surge arrestor screws (x4) 2 4 3 The screws removed earlier are reused. (2 self - tapping screws) mounting the voltage presence unit (VPIS- V2) 3 2 5 5 checks to be made before continuing with the operation RM6 Position the cable gland seal (2) on the voltage presence connection (5). Check that the seal is in the correct position. Clip the cable harness connector (5) onto the VPIS protection (3) and fit the seal Check the condition of the wiring harness (5) and the VPIS 2 rating using the optional diagnostic tool (VPI62420) (not included in the kit) or see correspondence table below. VPI62403 7,4 A VPI62404 10,7 A VPI62406 22,4 A VPI62408 47,2 A Min Max Min Max Min Max Min Max 2,5 kV 3,2 kV 3,3 kV 7,7 kV 8,8 kV 16,0 kV 16,1 kV 23,0 kV 5.3 kV 10.6 kV 7.6 kV 15.4 kV 16 kV 32.5 kV RM6 50 - 60Hz standard RM6 50 - 60Hz BUSHING WELL only Key 62 Un : network voltage Minimum and maximum network voltage in 50Hz and 60Hz. 07897073EN01 revision : 11 Please refer to the chapter entitled ”contents of the kit” 1 3 Screw the indicator unit (1) onto the VPIS surge arrestor (3) using the 4 screws. CAUTION Tighten the screws to exert slight pressure on the cable gland seal without distorting it. Install the voltage presence unit in the correct position using the 2 self- tapping screws removed earlier. ATTENTION The screws removed earlier are reused. 07897073EN01 revision : 11 63 replacement of the voltage presence unit (VPIS) type VPIS- V2 by type VPIS- V2 removing the VPIS 2 voltage presence unit CAUTION The screws must be retained. Remove the 2 screws from the front panel. mounting the new VPIS 2 voltage presence unit ATTENTION Only the indicator unit is to be changed. Contact the Schneider Electric administration for recycling products at the end of their service life. Discard the faulty indicator unit. Leave the existing surge arrestor and seal. Remove the unit. Remove the 4 screws from the indicator unit. Install the new voltage presence indicator unit. Screw up the 4 screws. Tighten the screws to exert slight pressure on the cable gland seal without distorting it. CAUTION The screws removed earlier are reused. Install the voltage presence unit in the correct position using the 2 self- tapping screws removed earlier. 64 07897073EN01 revision : 11 replacing a fuse Standard IEC 252 paragraph 23.2 recommends replacement of the 3 HV fuses after blowing of one of the fuses. removal CAUTION Before performing these operations, remember that you close the earthing switch. CAUTION Repeat the following operations for all 3 fuses. To remove the cover: lift it and pull it towards you. The instructions are visible on the cover. Release the plug and push the extraction handle manually to unlock the plug (tap with the palm of your hand to separate the seal from the plug if necessary). Move the plug up to the limit stop, swivel it towards the left to remove it. Recover the centring device at the top of the fuse. Extract the fuse. removing a DIN fuse (Fusarc CF) 07897073EN01 revision : 11 65 removing a UTE fuse (Solefuse) Loosen the fuse using a wrench with end BTR n° . 5. Let the plug hang down from its supporting string. If the fuse plugs are dirty, clean the conical surface using silicon oil. Then wipe it down with a clean cloth to dry it. Huile Rhodorsil 47V50. Distributed by Rhone Poulenc (chimie Lyon) FRANCE Talc the clean surface with natural talc to avoid clinging between the plug and fuse compartment. The surface must appear smooth without lumps. TALC : westmin 8. Distributed by Ets Ledoux Bordeaux FRANCE cleaning the plugs fitting a DIN fuse CAUTION On no account must a fuse that has been knocked be installed. A test prior to installation using a monitor is recommended. Insert the fuse in the compartment. Fit the centring device on the fuse. Insert the plug pins in the plinth and swivel it round to the right. 66 07897073EN01 revision : 11 fitting a fuse with striker Fuse blowing releases a striker that causes three- phase opening of the switch and prevents it from reclosing. Percuteur Striker pin Schlagstift Percussore The end of the fuse equipped with the striker is marked. The technical data and mounting direction of the fuse are printed on the body. (striker facing upwards). fitting a UTE fuse CAUTION On no account must a fuse that has been knocked be installed. A test prior to installation using a monitor is recommended. 15 Nm Fix the fuse on the plug using a torque wrench with end BTR n° . 5 and insert the fuse in the compartment. Insert the plug and fuse assembly in the compartment. Insert the plug pins in the plinth and swivel it round to the right. Make sure that the handle trunnions are inserted in the plinth slots and lock the plug. Never use the operating lever to lock the plug. For replacement of a fuse that has struck, press the switch to put it back in position. locking the plug 07897073EN01 revision : 11 67 access to the LV compartment dismantling 1- Remove the fuse compartment cover (pull towards you) 2- Remove the LV cable trough 6 screws (HM6x16) 3- Remove the self- cutting screws 2 3 1 reassembling Reassemble in opposite order to disassembly. H replacing a motor removal CAUTION LV circuit de- energized. fitting 68 Remove the 3 nuts fixing the motor support. Disconnect the motor supply wiring. Remove the motor support by pulling it backwards. Fit the new motor in the opposite order to removal. Tightening torque: 28 Nm. Fit the trunking and the cover. 07897073EN01 revision : 11 replacing the LV contacts Disassemble the pilot light support. removal B CAUTION S1 LV circuit de- energized A Remove the position indicator A. Remove interlocking B. (elastic ring and spring) Remove contact support S1 without disconnecting the wiring. S2 Remove contact S3 without disconnecting the wiring. S3 S41 S5 Remove the contact support S2, S4, S5, S6 and S7 without disconnecting the wiring. fitting the contacts and wiring connection 13 Nm S1 Fit contacts S1 to S7 to replace the former contacts. Fit the position indicator and interlocking. 07897073EN01 revision : 11 Disconnect the contact wiring S1 disassembled, and connect it to the new contact. Repeat this operation for all the contacts (S2 to S7). 69 processing when dismantling the equipment processing of SF6 gas when dismantling the equipment conformity rules 70 The SF6 gas must be removed before any dismantling operation can be carried out, according to the procedures described in IEC 61634 and according to the following instructions. The removed gas must be processed in compliance with IEC 60480. The after sales of SCHNEIDER ELECTRIC can propose a complete offer. - dismantling and recycling of the RM6 units - treatment of the SF6 gas. Finally a certificate will be provied to you. 07897073EN01 revision : 11 ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... 07897073EN01 revision : 11 71 ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... ..................................................................................................................................................................... 72 07897073EN01 revision : 11 group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F- 92500 Rueil- Malmaison (France) Tel : +33 (0)1 41 29 85 00 http://www.schneider- electric.com 07897073EN01 revision : 11 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 12/2014
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Create Date : 2015:02:03 14:11:25+01:00 Modify Date : 2015:02:03 14:56:26+01:00 XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26 Metadata Date : 2015:02:03 14:56:26+01:00 Producer : Acrobat Distiller 10.1.7 (Windows) Format : application/pdf Title : untitled Document ID : uuid:f1c1d51b-d8e7-40d5-aa8e-ec516eb0e577 Instance ID : uuid:ab27567e-56be-4f3c-9f43-0f0aa65580a8 Page Count : 74EXIF Metadata provided by EXIF.tools