RM6 7897073uk

User Manual: RM6

Open the PDF directly: View PDF PDF.
Page Count: 74

DownloadRM6 7897073uk
Open PDF In BrowserView PDF
RM6
ENGLISH

MV distribution
factory built assemblies
at your service

instructions for
use

foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

symbols and conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
distribution rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
maintenance rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3
4
4
4

general description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5

circuit breaker and switch function . . . . . . . . . . . . . . . . . . . . . . . . . . . .
fuse- switch and switch function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
”switchboard coupling” switch and circuit breakers . . . . . . . . . . . . .
cable connection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
metering cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
single- line diagramms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5
5
6
6
6
7

instructions for putting the RM6 into operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

prior to energising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
pressure check of unit in operation . . . . . . . . . . . . . . . . . . . . . . . . . . .
unit with pressure switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
position of the VPIS or VDS voltage indicator units (optional) . . . . .
phase concordance unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
rules for the use of phase concordance unit . . . . . . . . . . . . . . . . . . . .
RM6 equipped with VDS voltage detection units . . . . . . . . . . . . . . . .
choosing the HV fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
sealing of DE- Mt cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9
9
10
12
13
13
16
17
20

instructions for putting into operation the protection relay for circuit - breaker . . . . . .

23

VIP400 / VIP410 presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
presentation of VIP40/45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sepam series 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
standard assignment of inputs/outputs and customised configuration
human- machine interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23
27
31
35
36
38
38

operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

43

operating and viewing substation condition . . . . . . . . . . . . . . . . . . . .
operating safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
key- locking (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
padlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
overcurrent indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LV connection indicator Flair 2xD . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
detector pending fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ammeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
standard operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
connection of Cts to the 3 MV cables . . . . . . . . . . . . . . . . . . . . . . . . . .
voltage detection relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
detection sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
configuration of thresholds and time delays . . . . . . . . . . . . . . . . . . . .
suggested choice for VD23 settings . . . . . . . . . . . . . . . . . . . . . . . . . . .
access to the cable compartments . . . . . . . . . . . . . . . . . . . . . . . . . . . .
access to the MV compartment of the DE- Mt cubicle . . . . . . . . . . .

43
45
45
45
47
48
48
53
53
54
55
55
56
56
57
58

preventive maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59

standard operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
harsh operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59
60

corrective maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

61

foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
maintenance summarising table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
replacing a fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
access to the LV compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
replacing a motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
replacing the LV contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

61
61
65
68
68
69

07897073EN01 revision : 11

1

processing when dismantling the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

70

processing of SF6 gas when dismantling the equipment . . . . . . . . .

70

2

07897073EN01 revision : 11

foreword

symbols and
conventions

Caution:
you will find all the symbols
below throughout the document,
indicating the hazard levels
depending on the different types
of situation.

DANGER
DANGER: failure to follow this
instruction will result in death or serious injury.

AVERTISSEMENT
WARNING: failure to follow this instruction may
result in death or serious injury.
as per iso 3864- 2

ATTENTION
CAUTION: failure to follow this instruction may
result in injuries.
This alert signal can also be used to indicate
practices that could damage the SM6 unit.

INFORMATION - ADVICE
We draw your attention to this specific point.

contact the Schneider
Electric service unit for
diagnosis and advice

You can log on to:

WWW.SCHNEIDER- ELECTRIC.COM
Call your sales representative who will put you in contact
with the closest SCHNEIDER- ELECTRIC service centre.

07897073EN01 revision : 11

3

distribution rules

CAUTION

CAUTION

The aim of this publication
is to enable the RM6 unit
to be installed correctly.

safety rules

This document is not a commercial
document.It is a strictly technical
document drawn up by
Schneider Electric.

WARNING

CAUTION
All the operations described below
must be performed in compliance
with applicable safety standards,
under the responsibility
of a competent authority.
WARNING

Only undertake the work after
having read and understood
all the explanations given in this
document.
If you have any difficulty complying
with these rules, please contact
Schneider Electric.

The contractor must be certified
and authorised to manipulate and
perform work on the RM6 unit.

protective equipment
For each operation, it is mandatory
to use safety equipment
appropriate:
- Personal Protective Equipment
(PPE)
- Collective Protection Equipment
(CPE)

Eye protection must
be worn

Safety overalls must be
worn

Safety gloves must be
worn

Safety helmet must be
worn

Safety boots must be worn

Ear protection must
be worn

maintenance rules
NEVER USE SOLVENTS AND ALCOHOL

WE DRAW YOUR ATTENTION TO THE RISK
OF USING HIGH PRESSURE CLEANING
PROCESSES

4

07897073EN01 revision : 11

general description

G

circuit breaker and switch
function

C

DKL

N F E P

B
A
M
H

IDI

A : operating mechanism front
plate comprising the mimic
diagram
B : information plates
C : earthing switch operating
shaft
D : switch operating shaft
E : function position indicator

F : voltage indicator
G : LV connection access trunking
H : connection bushing access
panel
K : VIP30/35 and VIP300
protection relays
L : D function opening
pushbutton

fuse - switch and switch

G

function

M : rating plate
N : pressure switch or gauge
label
P : pressure switch or gauge

N F E P

C D

B
A
J
H

IQI

A : operating mechanism front
plate comprising the mimic
diagram
B : information plate
C : earthing switch operating shaft
D : switch operating shaft

07897073EN01 revision : 11

E
F
G
H

: function position indicator
: voltage indicator
: LV connection access trunking
: connection bushing access
panel

J : rating plate
N : pressure switch or gauge
label
P : pressure switch or gauge

5

”switchboard coupling”
switch and circuit
breakers
Example presented :
1: DE- BC station with earthing
switch

D

F
A

B

D
G

B

C

A

C
F
E

E

2: DE- IC station with earthing
switch

2

1
A: control panel
featuring the mimic panel
B: earthing switch operating
shaft
C: switch operating shaft
D: voltage indicator
E: connection bushing access
panel
F: rating plate
G: characteristics plates

cable connection
function

A: control panel
featuring the mimic panel
B: earthing switch operating
shaft
C: switch operating shaft
D: voltage indicator
E: connection bushing access
panel
F: plate characteristics

A

Exemple presented : DE- O

B

A: characteristics plate
B: rating plate
C: connection bushing access
panel

C

metering cubicle
with LV compartment

1

1

without LV compartment

5

3
2
4

1: LV compartment
2: voltage transformer access
panel
3: characteristics plate
6

4: access panel to current
transformer
5: LV compartment
07897073EN01 revision : 11

single- line diagramms
NE = No Extensible
DE = Double Extensible

LE = Left Extensible
RE = Right Extensible

DE - IIBI

RE - DIDI

NE - D

TRANSFORMER PROTECTION
BY ’CIRCUIT- BREAKER’

TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER’

NE - IQI

DE - III

NETWORK ’SWITCH ’

TRANSFORMER PROTECTION BY ’FUSE- SWITCH COMBINAISON’

DE - DD

TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER ’

07897073EN01 revision : 11

DE - IDD

TRANSFORMER PROTECTION BY ’CIRCUIT- BREAKER’

LINE PROTECTION BY ’CIRCUIT- BREAKER’

NE - IDI

TRANSFORMER PROTECTION BY’ CIRCUIT- BREAKER’

DE - IIBc

SWITCHBOARD COUPLING ’CIRCUIT- BREAKER’

7

.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................

8

07897073EN01 revision : 11

instructions for putting
the RM6 into operation

prior to energising

Check that the connection
bushings are fitted with connectors
or with insulating caps.

Check that the RM6 is connected
to the substation earth.

pressure check of unit
in operation
CAUTION

unit with manometer
Case 1:
needle in green zone

Case 2:

ENERGISED RM6 UNIT

The RM6 unit is operating normally.

H

The RM6 unit must be replaced
urgently.
H It can remain energised until
replacement.
H All opening or closing operations are forbidden.
H To replace the RM6, power off
the unit.
H

WARNING
needle in red zone

07897073EN01 revision : 11

9

warning label
recalls the safety rules

unit with pressure
switch
LCD display check
Press the “TEST” button. The LCD
screen should display:

If nothing is displayed, check
that the 8- point connector on the
pressure switch wiring harness at
the rear of the LCD display is correctly connected.
H Contact the after sales service.
www.schneider- electric.com
Note: The LCD display is selfpowered by piezoelectric buttons
(“TEST” and “DENSITY SWITCH”).
Pressing on one of these buttons
will turn on the display for a few
seconds.
H

pressure check
Press the “DENSITY CHECK” button. The LCD screen displays:
Case 1: OK
The RM6 unit is operating normally.

H

10

07897073EN01 revision : 11

Cas n° 2 : LOW / OK

The RM6 unit must be replaced.
It can remain energised until
replacement.
H All operations can be performed
while energised.
H
H

CAUTION

Case 3: VERY LOW / NOT OK
WARNING

The RM6 unit must be replaced
urgently.
H It can remain energised until
replacement.
H All opening or closing operations are forbidden.
H To replace the RM6, power off
the unit.
H

warning label
recalls the safety rules

07897073EN01 revision : 11

11

position of the VPIS or
VDS voltage indicator
units (optional)

1

2

3

1 and 3 :voltage presence on
network cables.

2 : voltage presence downstream
of fuses for a switch combination
or on the outgoing cable
for a circuit - breaker.

VPIS- V1 : production until
February 2009.

VPIS- V2 : production starting
from March 2009.

VPIS
presentation of VPIS- V1
and VPIS- V2
VPIS :Voltage Presence Indicating
System, a case with 3 built - in
lights.

characteristics

operating instructions

Conforming to IEC 61958, relative
to voltage presence.

A

A

WARNING
The indication provided by a
VPIS- V1 or V2 alone is not sufficient to ensure that the system is
de- energised.
INFORMATION
When the ambient lighting is particularly bright, it may be necessary
to improve visibility by protecting
the indication.

12

B

B

A : voltage presence indicator
light (one for each phase)
B : connection point designed for
the connection of a phase
concordance unit (one for
each phase)

07897073EN01 revision : 11

phase concordance
unit

principle

Phase concordance testing for
VPIS- V1 and VPIS- V2 must be
carried out each time a cable is
connected to a functional unit.

It is a way of making sure that all
three cables are each connected
to the corresponding phase of
the substation.

The principle of the phase
concordance unit is that it allows
a check of the phase concordance between 2 energised
functional input units on the
same substation.

reminder of accessories that
can be used for phase
concordance test

Phase concordance unit V1.
(51191954FA)

rules for the use of
phase concordance
unit

Phase concordance unit V2.
(VPI62421

WARNING
IT IS IMPOSSIBLE TO CARRY
OUT A PHASE CONCORDANCE
TEST WITH 2 VPIS OF
DIFFERENT TYPES

Balanced phases :
- the phase concordance unit light
(1) is untit.
Unbalanced phases :
- the phase concordance unit light
(1) is lit.

1
1

07897073EN01 revision : 11

13

rules for choosing phase
concordance unit
phase
concordance
unit

functional unit
1

functional unit
2

V1

compatibility
result

corrective actions

V1
OK

V1

V2

V2

OK

Replace VPIS- V1 by VPIS- V2.
Use a phase concordance unit V2.

OK

Use a phase concordance unit V2.

OK

Replace VPIS- V1 units by VPIS- V2 units
OR test with 1 phase concordance unit
V1.

OK

Replace VPIS- V1 with VPIS- V2.

V2

V1

V1

V1

V2

V2

V2
OK

check before phase
concordance test

Please refer to the previous chapters
in the event of test malfunctioning.

TEST

1

2

Visual checking of the indicator
lights on the VPIS units of functional
unit 1 and of functional unit 2
Phase concordance unit
check choice

14

On each
functional
unit test
phases 1
and 3.

RESULT

ACTION

The 3 indicator lights of each VPIS
are on.

The 2 functional units are energised, the VPIS units are operating
and the check can continue.

The 3 indicator lights of the VPIS
are off. The functional unit is not
energised or the VPIS is defective.

Apply power to the functional unit.
If VPIS- V1 remains unlit, replaced
it by a VPIS- V2.

One or 2 indicator lights unlit.

The VPIS is probably defective.
Replace by a VPIS- V2.

functional unit 1

You can test.

functional unit 2

You cannot test them.
The choice of the phase concordance unit is wrong or it is not
functionning correctly.

07897073EN01 revision : 11

phase condordance test
The 3 indicator lights of the 2 VPIS are lit and the phase concordance unit is correct, meaning that phase concordance test can be performed.

lexique

phase concordance unit LED lit

LED unlit

or

Functional unit n° 2
L1

L2

L3

Conclusion regarding phase concordance

L1
L2

Connection is satisfactory.

L3
L1
L2

Reverse the MV cables connected to L1 and L2
on one of the 2 functional units

Functional unit n° 1

L3
L1
L2

Reverse the MV cables connected to L2 and L3
on one of the 2 functional units

L3
L1
L2

Reverse the MV cables connected to L1 and L3
on one of the 2 functional units

L3
L1
L2

Change the position of each MV cable on one of
the 2 functional units

L3
L1
L2

Change the position of each MV cable on one of
the 2 functional units

L3

07897073EN01 revision : 11

15

RM6 equipped with
VDS voltage detection
units

B

B

VDS: Voltage Detecting System,
unit with connectors used to plug
in individual indicators.
A: protective covers.
B: connections points used
to connect an individual
indicator.

A

A

A

characteristics

The voltage detector system
equipping your RM6 is of the
separate VDS type, HR system.

It complies with standard
IEC 61243- 5.

instructions
for using the interface

Each time the interface is used,
put back the protective covers.

Do not use connectors enabling
short - circuiting of the interface,
in networks with unearthed or
earthed neutral by resonant circuit.

accessories usable
at the interface

Individual voltage indicator for HR
system.
Universal phase concordance unit.
CAUTION
The reliability of the information
provided is guaranteed only by
use of accessories conform to
standard IEC 61243- 5: to use
them, follow the instructions of the
accessory manufacturer.
Other devices must only be used
at the interface if they exhibit the
same dielectric strength as an
indicator.

16

07897073EN01 revision : 11

choosing the HV fuses

Dimensions of the Fusarc CF
fuses (DIN)

For installation of fuses of other
manufacturers, please consult
us.

The rating of the fuses to be fitted
in the RM6 protection function
depends on the following factors
(among others):
H operating voltage.
H transformer rating.
H fuse technology (manufacturer).

Ø

Ø45

Dimensions of the Soléfuse
fuses (UTE)

33

.

L

33

27

Ø55
450

Various fuse types with striker
with average energy can be fitted :
- as per standard UTE NFC
13.100, UTE NFC 64.210
of the Soléfuse type.
- as per recommendation
IEC 282.1 and dimensions
DIN 43.625 of the Fusarc CF type.
Example: general case for
protection of a 400 kVA – 10 kV
transformer, 63 A Soléfuse fuses or
50A Fusarc CF fuses will be
chosen.

35

H

rated voltage rating
(kV)

rating to (A)

7,2 à 24

6,3 à 63

rating
voltage
(kV)

rating to
(A)

lenght
(mm)

diamater
to (mm)

12

10 à 20

292

50,5

25 à 40

292

57

50 à 100

292

78,5

24

Our products are guaranteed only with
the fuses mentioned in this document.

125

442

86

10 à 20

442

50,5

25 à 40

442

57

50 à 63

442

78,5

80 à 100

442

86

To install fuses of other brands, please
ask “Schneider Electric” support.

IEC & UTE standards require that all
3 fuses are to be replaced after the
fusion of one fuse.

selection table

(”) In the case of an external trip system
(eg.:overcurrent relay).

(rating in A, use without overload
at –25C <  < 40C).

Solefuse

operating
voltage
(kV)

For any values inclued in the table, please
consult us.
In this case of an overload beyond 40° C,
please consult us.

A calculation must be carried out to
guarantee coordination of fuse
fuse- switches.

(*)SIBA types fuses at 160A/12kV
reférence 30- 020- 13.
fuse type

Please consult us.

Transformer rating (kvA)
50

75

100

125

160

200

250

315

400

500

630

800

1000

31,5

31,5

63

63

63

63

63

10

16

16

31,5

31,5

31,5

63

63

63

63

15

16

16

16

16

16

43

43

43

43

43

63

20

16

16

16

16

16

16

43

43

43

43

43

1250

1600

2000

Rated
voltage
(kV)

(norme UTE NFC : 130.100, 64.210)
5,5

16

7,2
24
63

Fusarc CF et SIBA (*) (General case, IEC 60282- 1, standard CEI62271- 105 (to replace IEC 60420) and DIN 43625 standard)
3

20

31,5

40

50

50

63

80

100

125*

160”

3,3

20

25

40

40

40

63

80

80

125*

125*

160“

4,2

20

25

25

40

50

50

63

80

80

100

125* 160“

5,5

16

20

25

25

40

40

50

63

80

80

100

125* 160”

6

16

20

25

25

31,5

40

50

50

63

80

100

125* 160”

6,6

10

20

25

25

31,5

40

50

50

63

63

80

100

125*

160”

10

10

10

16

20

25

25

31,5

40

50

50

63

80

100

125*

11

10

10

16

20

20

25

25

40

40

50

50

63

80

100

13,8

10

10

10

16

16

20

25

31,5

40

40

50

50

63

100*

15

10

10

10

10

16

20

25

31,5

31,5

40

50

50

63

80

100*

20

10

10

10

10

16

16

20

25

25

31,5

40

40

63

63

80

100*

22

10

10

10

10

10

16

16

20

25

31,5

40

40

50

63

80

100*

07897073EN01 revision : 11

12

125*
24

17

fitting HV fuses
CAUTION

Before performing these
operations, close the earthing
switch.

CAUTION

Repeat the operations below for
all 3 fuses.
To remove the cover: lift it and pull
it towards you.
The instructions are visible
on the cover.

Release the plug and push the
extraction handle manually to
release the plug (tap with the palm
of your hand to detach the plug
seal if necessary).

Fit the plug as far as it will go and
swivel it to the left to extract it.

Let the plug hang.
Ensure the plugs are clean before
fitting them.
To clean the plugs, consult the
preventive maintenance section.

18

07897073EN01 revision : 11

fitting a DIN fuse
(Fusarc CF)

rm6

On no account must a fuse that
has been knocked be installed.
A test prior to installation using
a monitor is recommended.

Recover the centring devices in the
bag supplied with the substation.

Insert the fuse in the
compartment.Fit the centring
device on the fuse.
Insert the plug pins in the plinth
and swivel it round to the right.

Fix the fuse on the plug using a
torque wrench with end BTR no. 5
and insert the fuse in the
compartment.
Tightening torque: 15 Nm.

Insert the plug and fuse assembly
in the compartment.Insert the plug
pins in the plinth and swivel it
round to the right.
Press to insert the assembly in the
downstream clamp.

fitting an UTE fuse
(Solefuse)
CAUTION
On no account must a fuse that
has been knocked be installed.
A test prior to installation using
a monitor is recommended.

direction for mounting
a fuse with striker
CAUTION
Fuse blowing releases a striker
that causes three- phase opening
of the switch and prevents it from
reclosing.

Percuteur
Striker pin
Schlagstift
Percussore

The end of the fuse equipped with
the striker is marked.

07897073EN01 revision : 11

The technical data and mounting
direction of the fuse are printed on
the body.(striker facing upwards).
19

locking the plug

Make sure that the handle
trunnions are inserted in the plinth
slots and lock the plug manually
by folding down the operating
handle.

sealing of DE- Mt
cubicle
without LV compartment

Plug with fuse blowing release,
used to cause three- phase
opening of the switch.
Press the switch to position it.

A: rear sealing
B: front sealing
C: seal + wire; steel

C

B
A

A
A

20

07897073EN01 revision : 11

with LV compartment

A: sealing of the LV compartment
B: seal + wire steel

B

07897073EN01 revision : 11

21

.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................

22

07897073EN01 revision : 11

instructions for putting into operation
the protection relay for circuit- breaker

CAUTION

The VIP parameters must be set
correctly in order for the circuit
breaker function well.

VIP400 / VIP410
presentation

The User- Machine Interface (UMI)
on the front panel of VIP relays
consists of a display, LEDs and
keys. A sealable pivoting flap can
prevent access to the setting keys
by unauthorized persons.
1:
2:
3:
4:

Display
Status LEDs
Fault indication LEDs
Zone for a user- customizable
label with pictograms of the
fault indication LEDs
5: Acknowledgement key
6: Identification label
7: Sealing ring
8: Selection keys
9: Key for selecting menus and
testing LEDs. When the VIP is
not supplied with power, this
key can also be used to
start the VIP from the battery
in order to enter settings
10: Menu pictograms
11: Menu selection pointer
12: Battery compartment and
socket for connecting the
pocket battery module
13: Settings protective flap
14: Confirm entry key
15: Abort entry key
16: Setting keys

status LEDs
Pictogram

Flap closed

Flap open

The status LEDs provide
information about the VIP general
status:

H

Function

VIP400

VIP410

Green LED: auxiliary power supply present

-

H

Red LED permanently on: VIP unavailable (VIP in the fail- safe position).

H

H

Red LED flashing: a failure has been detected but does not involve the VIP
going into the fail- safe position.

H

H

Yellow LED flashing: communication active

-

H

INFORMATION- ADVICE
NRJED311206EN : reference manual is available on : www.schneider- electric.com
or call your sales representative who will put you in contact with the closet SCHNEIDER- ELECTRIC
service center
07897073EN01 revision : 11

23

operation

VIP relays have fault indication
LEDs. They flash to indicate a fault,
as shown in the table below :

Fault Indication LEDs
Pictogram

Ext.

Fault

VIP400

VIP410

Detection of a fault by the phase overcurrent protection or in the event of
tripping by the temporary test mode

H

H

Detection of a fault by the earth fault protection

H

H

Detection of a fault by the thermal overload protection

H

H

Tripping by a volt- free contact connected to the external trip input

-

H

After a trip, the fault indication
LEDs are powered by the battery
embedded in the VIP or by the
VIP410 auxiliary power supply.

Fault indication by the LEDs can
be stopped:
H by pressing the Reset key
H automatically by the reappearance of a current in the network
higher than the pick - up current
H automatically after 24 hours
H by remote control order via the
communication (VIP410)

For the first 3 LEDs, faster flashing
may occur before the protection
trips, to indicate the following
information :
Pictogram

Overshoot
Overshoot of the instantaneous set point for phase
overcurrent protection (I> or I>> or I>>> pickup outputs
Overshoot of the instantaneous set point for earth fault
protection (Io> or Io>> pick - up outputs)
Overshoot of the alarm set point for thermal overload
protection

note

24

In custom mode, the protection set
points may not be assigned to the
Mitop trip unit output.
In this case, the fault indication
LED may be active, without being
associated with the circuit breaker
trip.

Depending on the application, this
can indicate the presence of a fault
without tripping the circuit breaker
The fault indication LED pictograms can be customized by sticking a label to the right of the
LEDs.

07897073EN01 revision : 11

display
The display is an LCD unit.
It is only back - lit on the VIP410,
when the auxiliary power supply is
present.

menu organization
All the data available in the VIP
relay is divided between 3 menus:
H The metering menu
contains
the current measurements, peak
demand currents, load history,
event records, fault trip counter
and the breaking current history.

selecting a screen
in a menu

First line: symbols for electrical
values or function name
H Second line: displays the
values of measurements or
parameters associated with the
function
H A menu pointer, on the left, it is
pointing to the pictogram for the
selected menu
H

Each VIP function is presented in a
screen consisting of the following
items:

The protection menu
contains the essential settings
for setting up the protection functions
H The parameters menu
contains the parameters that
are used to adapt VIP operation to
particular applications.
H

Etape
1

When a VIP is new, all the parameters in this menu have a default
value.
The protection functions are operational even with the parameters
menu default values.

Action
Press the

key to select one of the 3 menus

The menu pointer

indicates the selected menu :

: Metering menu
: Protection menu
: Parameters menu
2

Press the
or
keys to scroll through
the screens in the select menu, until the desired screen diplayed

default screen

A default screen is displayed automatically 3 minutes after the last
keystroke.

This default screen is the
screen displaying the phase
currents.

operation according to the
power supply mode
(VIP400)

The VIP400 is a stand- alone protection relay powered by its current sensors.
When current is present in the
medium- voltage (MV) network,
the protections and the display
work and it is possible to enter settings and view measurements.
The current in the MV network on
which the VIP operates is called
the ’pick - up current’.
When no current is flowing through
the circuit breaker (for example circuit breaker open), or when the
current in the MV network is too
low, the VIP is off and nothing
appears on its display.
If current appears, the protection
functions are activated and trip the
circuit breaker - or not - according to their settings.

The additional time taken by the
VIP to start when current appears
is called the ’pick - up time’.
More information on the value of
the pick - up current and the pick up time are available in the VIP
Function Characteristics
Please consult the reference
NRJED311207EN.

07897073EN01 revision : 11

25

operation according to the
power supply mode
(VIP410)

The VIP410 is a relay with a dual
power supply. It is powered both
autonomously by its sensors and
by the auxiliary power supply.
Like for the VIP400, the
self- powered supply allow the
protection functions to work even if
the auxiliary power supply fails.

The auxiliary power supply is used
to power functions that do not
depend on the current being
present in the MV network. These
functions are marked in the
function table (Please consult the
reference NRJED311207EN). The
auxiliary power supply must be
present in order them to work.

integral battery

The VIP has an integral battery. It
is used to:
H activate the user- machine
interface in order to enter settings
when the VIP is not supplied with
power
H illuminate the fault indication
LEDs when the VIP is no longer
supplied with power after giving
theopening order to the circuit
breaker
H power the internal calendar
When the VIP is not supplied with
power:
Pressing and holding down the
key will activate battery- powered
operation of the user- machine
interface. It is then possible to
access the menus in order to enter
settings.
In this case, the display
turns off automatically after 3
minutes of inactivity on the keypad.

H

The pocket battery module is an
accessory that can be connected
to the front panel of VIP relays. It
contains a battery that can be
used to power the VIP in order to:
H enter settings if the integral battery is missing and if the VIP is not
powered by the current sensors
H test the VIP, please consult the
reference NRJED311207EN.

H

pocket battery module

The protection functions are
activated automatically if the current reappears.
The integral battery plays no part
in operating the protection functions. The protection functions
work even when there is no battery.

NOTE :
H in battery operation mode, the
VIP processor runs with a reduced
clock frequency to ensure the battery life is maintained. As a result,
the user- machine interface may
be slower to react.
during a setting operation with
the VIP powered by its internal
battery alone, the clock display is
not refreshed on screen. However
the internal clock increments normally.

H

display the cause of the last trip
by the VIP’ please consult the reference NRJED311207EN.
H more information on connecting
the pocket battery module to the
VIP is available in the Connection
to the VIP ’ please consult the reference NRJED311207EN.

battery module
The pocket battery module should
only be used during maintenance
or commissioning by qualified personnel and must never be left
permanently connected to a running VIP.

26

LV434206

07897073EN01 revision : 11

presentation
of VIP40/45
1: Display
2: Lugs for opening the
transparent protective flap
3: Transparent protective flap
4: Imax. peak demand display
button
5: Sealing ring
6: Test/Reset button
7: Status LED
8: Space for a user- customizable
label
9: Trip fault indication LED
10: Identification label
11: Symbol indicating that it is
necessary to read the manual
12: Battery

display

12

The display is an LCD unit
During operation, the display
indicates the value of the current
on each phase in succession
Each phase remains displayed for
3 seconds before automatically
changing to the next. The display
is in amps, on three digits.

The display is in amps, on three
digits.
NOTE: If the phase current is less
than the pick - up current (Please
you consult the reference
NRJED311207EN), the VIP is not
activated and the display is off.

lugs for opening the transparent protective flap

To open the flap, pull both lugs
simultaneously.

The flap pivots open on its 2 bottom hinges.

Imax. button: peak demand
display

Pressing the Imax. button triggers
a sequence displaying the peak
demand currents for all 3 phases
in succession.

After this sequence, the VIP automatically returns to displaying the
phase currents.

H
H

INFORMATIONINFORMATION- ADVICE
CONSEIL
NRJED311207EN : reference manual is available on : www.schneider- electric.com
or call your sales representative who will put you in contact with the closet SCHNEIDER- ELECTRIC
service center

07897073EN01 revision : 11

27

Test/Reset button

After a trip, pressing this button
stops the flashing trip indication.
This button can also be used to:
H test the built - in battery. When
pressing the Test/Reset button, the
fault indication LED lights up
immediately to indicate that the
battery is OK.

perform the ’lamp test’ if the
relay is supplied with power. Pressing the Test/Reset button for
5 seconds causes all the display
segments and the status LED to
light up, and displays the software
version number.

H

voyant d’état
Pictogram

Color
Red

Event
LED permanently on: the VIP has gone into the fail- safe position following detection by the embedded self- tests of the failure of one of its internal components,
involving a risk of nuisance tripping. In this case, the VIP is no longer operational
NOTE: This LED may light up briefly when the VIP is energized: this is normal and
does not indicate a failure.
LED flashing: the VIP has detected a failure not involving a risk of nuisance tripping.
In this case, the VIP has not gone into the fail- safe position.Intervention is required
as soon as possible (Please you consult the reference NRJED311207EN.) The LED
stops flashing as soon as the failure disappears.

space for user- customizable label

There is a special space for a
user- customizable label for the
Trip LED.

Trip LED: fault Indication

The fault indication LED flashes to
indicate that the VIP has sent a trip
order to the circuit breaker.
Aftercircuit breaker opening, when
the VIP is no longer supplied with
power by its sensor, the built - in
battery makes the LED flash.
The LED stops flashing:
H automatically after 24 hours
H when the current returns, on
circuit breaker closing (if the current is higher than the pick - up
current)

identification Label

The identification label on the front
panel is used to identify the VIP:
H product name
H product reference
H serial number

symbol : necessary reading
of manual

The

28

when the Test/Reset button is
pressed
H when the pocket battery module
is connected then disconnected
NOTE: The VIP built - in battery
only supplies power to the fault
indication LED and displays the
type of fault.
It has no role in operating the protection functions.
H

symbol indicates that it

is necessary to read the VIP reference manual before working on
the product.

07897073EN01 revision : 11

VIP40/45 settings
front panel

When the protective flap is opened, you can enter the protection
settings by means of the rotary
switches.

VIP40

To do this, use a 3 mm flat blade
screwdriver

VIP45

1 Phase overcurrent protection adjustment dial

1 Phase overcurrent protection adjustment dial

2 Setting range selector switch

2 Setting range selector switch

3 Advanced settings protective cover

3 Earth fault protection set point adjustment dial

4 Connection port for the pocket battery module
5 Trip test button

5 Advanced settings protective cover

4 Earth fault protection time delay adjustment dial
6 Connection port for the pocket battery module
7 Trip test button

phase overcurrent protection adjustment dial

The setting is entered directly in
Amps using the 9- position
switch.(I>)
The selector switch has 2 graduated rings.

The range is selected using the
setting range selector switch.

earth fault protection
adjustment dial

The set point is set directly in
Amps using the 9- position
switch..(Io>)
The time delay setting is entered
directly in seconds using the
9- position switch.(to>)

NOTE: the earth fault protection
adjustment dials are only found on
the VIP45.

temporary display of the
changed setting

When VIP relays are energized,
they display temporarily the value
of the setting after a switch has
changed position.

advanced settings

To access the advanced settings,
remove the advanced settings protective cover.

07897073EN01 revision : 11

Both settings can be entered using
a single selector switch:
H discrimination with the LV CB
H earth fault protection inrush current delay

29

connection port for the
pocket battery module

The connector is used to connect
the pocket battery module so that
the VIPs can be energized and
tested.
Please consult the reference
NRJED311207EN
NOTE:the pocket battery module
should only be used during
maintenance or commissioning by
qualified personnel and must
never be left permanently connected to a running VIP.

Trip test button

The Trip test button is used for
testing VIPs.
A 5 mm diameter pointed tool is
needed to activate it.
More information is available in the
section describing Commissioning.
Please consult the reference
NRJED311207EN

frequency

The network frequency (50 Hz or
60 Hz) is a parameter that must be
known for operation of the VIP40
and VIP45 signal processing algorithms.
They therefore have an automatic
frequency recognition system.
The recognized value
(50 Hz or 60 Hz) is stored and the
VIP works permanently with this
value.
This stored value will be used each
time the VIP starts
For the VIP to recognize the network frequency and store it, it has
to detect a current on phase 1 for
a minimum period of 5 seconds in
the range 50 Hz +/- 2 Hz or 60
Hz +/- 2 Hz.
This detection happens when
the VIP starts.

30

07897073EN01 revision : 11

For further information on the
Sepam series10, download the
reference manual from our website:
www.schneider- electric.com

Sepam series 10
protection of HV/LV transformers
protection of HV networks
Sepam 10 relays fitted to RM6 circuit breakers require an auxiliary
power supply.

Sepam 10A:
- provides protection against
overloads (thermal overload protection), phase- phase faults and
phase- earth faults.
It has:
- 4 logic inputs and 7 configurable relay outputs
- a communication port

Sepam 10B:
- provides protection against overloads (thermal overload protection), phase- phase faults and
phase- earth faults.
It has:
- 3 configurable relay outputs

Functions
Protection types
Earth current maximum protection

Standard
Very sensitive

Phase current maximum protection
Thermal overload protection
Cold load pickup (low sensitivity of phase and
earth current maximum protection settings)
Logic discrimination
Await logic emission
Await logic reception
External tripping
Measurements
Measurement of earth current
Measurement of phase currents
Phase current maximum readings
Control and monitoring
Circuit breaker tripping and rearmament locking
Trip signalling
Tripping circuit monitoring
Circuit breaker remote control
Recording of last fault
Recording of last 5 events
Communication
Modbus
IEC 60870- 5- 103

Function available
Function available depending of Sepam model

Inputs / Outputs (Number)
Earth current inputs
Phase current inputs
Relay logic outputs
Logic inputs
RS 485 communication port

07897073EN01 revision : 11

31

earth current (ANSI
50N- 51N)

Earth current maximum protection
enables overcurrents due to
phase- to- earth faults to be
detected. It makes use of the measurement of the earth current’s
fundamental component.

2 independent thresholds (Io>
and Io>>)
H the lower threshold (Io>) can
be set to either a definite time (DT)
or an inverse time (IDMT) curve,
with the choice of standardised
curve (IEC, IEEE, RI) and the possibility of activating an inverse time
duration.
H the upper threshold (Io>>) has
only a definite time (DT) setting.
The minimum setting gives instantaneous operation (ANSI 50 function).

Depending on the level of sensitivity required, there are 2 types of
Sepam:
Sensitivity

Sensor

Standard

3 CT CRa 200/1 or CRb 1250/1

Very sensitive

CSH200 core balance CT

phase current maximum
protection (ANSI 50- 51)

Phase current maximum protection
enables overcurrents due to
phase- to- phase faults to be
detected. It makes use of the measurement of the fundamental component of the currents from the 3
phase CTs.

thermal overload protection
(ANSI 49RMS)

This protection enables cables and
HV/LV transformers to be protected against overloads based on
the measurement of absorbed current.
This protection uses a thermal
model based on current measurements to evaluate temperature
rise. The current used for this protection is a 3- phase RMS current
that takes into account up to 13th
order harmonics.

32

2 independent thresholds (I>
and I>>)
H the lower threshold (I>) can be
set to either a definite time (DT) or
an inverse time (IDMT) curve, with
the choice of standardised curve
(IEC, IEEE, RI) and the possibility
of activating an inverse time duration.
H the upper threshold (I>>) has
only a definite time (DT) setting.
The minimum setting gives instantaneous operation (ANSI 50 function).

This protection has 2 settings:
maximum allowable continuous
current, which corresponds to the
maximum thermal withstand of the
equipment to be protected (this
allowable continuous current corresponds to a temperature rise of
100%)
H heating/cooling time constant of
the equipment.
H

07897073EN01 revision : 11

low sensitivity of phase and
earth current maximum
protection settings (Cold
Load Pick - Up)

The cold load pickup function
avoids nuisance tripping when the
equipment is powered- up, especially after a long break in operation. It allows the protection thresholds to be temporarily increased.

High currents at cold load pickup may be due to:
H simultaneous powering- up of
all the loads in an installation.
H power transformer magnetising
currents.
H motor starting currents.

Protection concerned

Operating means

Phase current maximum protection

After circuit breaker closing, the tripping thresholds (I> or I>>) are
increased or blocked for the set duration.

Earth current maximum protection

After circuit breaker closing, the tripping thresholds (Io> or Io>>) are
increased or blocked for the set duration.
Or
The protection is restrained by the detection of sensor saturation (measurement of 2nd order harmonic level).

logic discrimination
(ANSI 68)

This function achieves:
H tripping discrimination in the
event of a short - circuit between
phases, or from phase to earth, for
all network types
H reduced tripping time of the circuit breaker that is closest to the
source.

external tripping

The Sepam series 10A enables,
via a logic input, a tripping order
from an external protection means
to be taken into account.

earth current measurement

This measurement enables the
value of the fundamental component of the earth current to be displayed.

phase current measurements

These measurements enable the
RMS value of the phase currents to
be displayed; it takes into account
up to 13th order harmonics.

phase current maximum
readings

This function enables the largest
average current value of each of
the 3 phases to be displayed, as
well as giving the highest absorbed current during load peaks.

07897073EN01 revision : 11

All Sepam series 10B and 10A
are able to emit an await logic
order should a fault be detected
by the phase and earth current
maximum protection functions.
Only the Sepam series 10A is
able to receive an await logic
order that blocks its tripping
signal. A safety mechanism ensures the protection operates in the
event of a fault with the blocking
signal wiring.

This function displays the 3 phase
currents.

33

latching / resetting ANSI 86

Output relay latching can be configured. Latch tripping orders are
memorised and must be reset in
order to put the equipment back
into service.

circuit breaker remote
control - Sepam 10A

This function enables remote operation of the circuit breaker via the
communication. A Sepam logic
input allows the operating mode
(local or remote) to be selected.

recording of the last fault Sepam 10B

This function enables the characteristics of the last fault to be displayed. The Sepam indicates the
cause of the fault, the value of the
phase currents and the earth current when the fault occurred, and
the time and date of the fault.
This information is memorised until
the next fault occurs.

Cause of faults recorded: I>,
I>>, Io>, Io>> and thermal protection.

recording of the last 5
events - Sepam 10A

This function enables the characteristics of the last 5 events to be displayed. For each event, the Sepam
indicates its cause, the value of the
3 phase currents and the earth
current when the event occurred,
and the time and date of the event.
Events are numbered in the order
they occur and the last 5 can be
displayed.

The following events are recorded:
H tripping due to I>, I>>, Io> or
Io>>, thermal protection
H tripping by external input
H tripping circuit fault
H circuit breaker opening and closing via the communication
H tripping due to logic discrimination safety protection.

communication Sepam 10A

One RS 485 communication port.
2 protocols available, chosen by
configuration: Modbus, IEC
60870- 5- 103.

Communication enables the following functions to be carried out
remotely:
H measurement readings,
H status readings
H event readings and time- stamped measurements (2 tables of
100 events available)
H time setting and synchronisation
H remote control orders.

operating language

When delivered, the default language is English. The following
languages can be selected: UK
English, US English, Spanish,
French, Italian, German, Turkish,
Portuguese.

34

Resetting can be done:
- by pressing the Reset button;
- via the Sepam 10A communication port.

07897073EN01 revision : 11

standard assignment of
inputs/outputs and customised configuration
The configuration is customised
using the Sepam humanmachine interface, without the
need for a PC.

Sepam 10A
Logic inputs

Standard assignment

Configurable

I1

Circuit breaker open

No

I2

Circuit breaker closed

No

I3

External tripping

Yes

I4

Local- Remote

Yes

Relay outputs

Standard assignment

Configurable

O1

Circuit breaker tripping

Yes

O2

Locking of circuit breaker latching

Yes

O3

Trip signalling

Yes

O4

Circuit breaker remote closing

Yes

O5

Await logic emission

Yes

O6

Trip circuit fault signalling

Yes

O7

Watchdog

No

Relay outputs

Standard assignment

Configurable

O1

Circuit breaker tripping

Yes

O2

Locking of circuit breaker latching

Yes

O3

Trip signalling

Yes

Sepam 10B

07897073EN01 revision : 11

35

human- machine
interface
front panel

The Human- Machine Interface on
the Sepam front panel is made up
of a display, indicator lamps and
buttons.

Access to the setting buttons by
unauthorised personnel can be
prohibited using the pivoting and
lead- sealable cover. The illustrations below show the 2 positions of
this cover.

1:
2:
3:
4:

Display
Status indicator lamps
Fault indicator lamps
Zone for a customised
pictogram label of fault
indicator lamps
5: Button for resetting the
Sepam and the maximum
value readings
6: Identification zone
7: Lead sealing ring
8: Selection buttons
9: Menu selection and indicator
lamp test button
10: Menu pictograms
11: Menu selection pointer
12: Battery compartment
(Sepam series 10A)
13: Settings protection cover
14: Entry validation button
15: Entry abort button
16: Setting buttons

status indicator lamps

The status indicator lamps provide
information on the Sepam status.

Pictogram

Function

Sepam series 10

Green lamp: Sepam powered - up
Red lamp: Sepam unavailable
(Sepam in fall- back position)
Yellow lamp: communication active

36

07897073EN01 revision : 11

fault indicator lamps

The fault indicator lamps flash as
described in the table below to
signal a fault:

Pictogram

Sepam series 10

FThreshold exceeded
Phase current maximum protection instantaneous threshold
exceeded (I> or I>> pickup output)
Earth current maximum protection instantaneous threshold
exceeded (Io> or Io>> pickup output)
Thermal protection alarm threshold exceeded

The fault indicator lamp is latched
in standard operating mode.
If, when customising the operating
mode (at the time of commissioning), the latching of a fault indicator lamp has been cancelled, the
fault indicator lamp goes out as
soon as the fault is no longer present.
Pictogram

For the first 3 lamps, they may
flash at a faster rate before the protection trips to signal the following
information:

Fault

Sepam series 10

Detection of a fault by the phase current maximum protection
Detection of a fault by the earth current maximum protection
Detection of a fault by the thermal protection
External tripping

identification zone

VIP400

The identification zone on the front
panel enables a Sepam to be identified:
1 : Identification code
2 : Reference
3 : Supply voltage
4 : Serial number

VIP410

Refer to the Identification section
for the identification code key.
07897073EN01 revision : 11

37

identification
identification code

The identification code of a Sepam
series10 is an alphanumeric code
that defines the main functions of
the Sepam. It is made up of several fields:

Sepam 10 family
Model
B: phase and earth current maximum protection
settings
A: phase and earth current maximum protection
settings, logic inputs and communication port
Number of current inputs
4: 3 phase current inputs + 1 earth current input
Sensitivity of earth current maximum protection
1: standard (0.1...24 In) CT
3: very sensitive (0.2...24 A and 2...240 A)
CSH200
Supply voltage
A: 24...125 V DC and 100...120 V AC
E: 110...250 V DC and 100...240 V AC

operating instructions
accessing information

display

38

During operation, when the settings protection cover is closed,
the user has access to the following:
H reading of measurements, settings, protection types and parameters.
H local fault signalling.
H last fault resetting.
H reading of last recorded faults.
H resetting of maximum values.
H testing of indicator lamps and
the display.
1. Press
to select one of the 3
menus.
2. The pointer shows the selected menu:
Measurements
Protection types
Parameters
3. Press
and
to select
the information to be displayed.

07897073EN01 revision : 11

resetting

1. A fault detected by the Sepam
is signalled by:
- a message on the display
- a flashing indicator lamp
2. Press
to reset the fault.
3. The indicator lamp goes out
and the message disappears

setting instructions

Knowledge of electrical network
protection is required for choosing
appropriate settings.
Only those people with the required skills are authorised to set the
Sepam.
Not abiding by this instruction
may cause injury and damage to
equipment and property.
All protection is inhibited by
default. To make the protection
operational, it must be activated
and set - up when commissioning
the RM6.

CAUTION

accessing parameters and
settings

07897073EN01 revision : 11

1. Open the settings protection
cover.
2. Press
to select the protection or parameter menu.
3. Select the protection type or
parameter to be set using
and
.
4. Enter the password if requested.
5. Press
to select the value to
be modified.
6. The selected value flashes.
7. Press
or to increment or
decrement the value.
8. Press to validate the new
value or press to cancel.
9. The value stops flashing.

39

setting ranges

The setting ranges that can be
used for the lower threshold
depend on the circuit breaker type:
D or B, and the type of sensors fitted to the RM6.

Circuit breaker type
Type of sensors
Functions

D

B

Cra 200/1

CRb 1250/1

Code ANSI

Phase current

50- 51

20- 200A

125- 630A

Earth current

50N- 51N

20- 200A

125- 630A

Very sensitive earth current

50G- 51G

2- 240A
0,2- 24A

2- 240A
0,2- 24A

factory set parameters
Sepam 10A and 10B standard
earth

Sepam 10A and 10B
very sensitive earth

The transformer ratios of the phase
and earth CTs (Io by summing) are
factory set. If by error you have
deleted the settings, you can find
the type of CT fitted to your RM6 in
the inspection report supplied with
the equipment and on the CT support, where a label with the information can be found (see image
aside).

The factory set measurement
range is 2- 240A; this can be
changed.
To change to the 0.2- 24A range,
you should:
1- Bring up Io 0.2- 24A in the
RATING screen.
2-

40

Change the wiring at the CSH
input, terminals 11- 21 on the
Sepam connector marked B.

07897073EN01 revision : 11

configuring the logic inputs

For the Sepam series10 A, logic
input operation must be adapted
to the type of voltage: AC or DC.
The type of voltage must be configured in the LOG INPUTS screen
of the parameter menu. The
default value is DC.

accessing phase current
inputs

Connector B for connecting the
current sensors is a short - circuiting connector. It can be disconnected on- load; disconnecting it
does not open the sensors’ secondary circuit. Remove the short - circuiting connector without disconnecting the wires connected to it.
Use another connector to connect
your generator.

07897073EN01 revision : 11

B

41

.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................

42

07897073EN01 revision : 11

operating instructions

operating and viewing
substation condition

A

E

description
A: earthing switch operating
shaft
B: switch function operating
shaft
C: fuse- switch combination
function operating shaft
D: position indicator
E: fuse- switch combination
function opening pushbutton
F: padlocking handle

D

F
B
C

closing a switch
Initial state:
H switch open
H earthing switch open

Left the operating shaft protective
cover.
Activate the switch operating
mechanism to the right.

The indicator moves to the closed
position, and access to the
earthing switch operating shaft is
blocked.

opening a switch
Initial state
H switch closed
H earthing switch open

Activate the switch operating
mechanism to the left.

07897073EN01 revision : 11

The indicator moves to the open
position, and access to the
earthing switch operating shaft is
freed.

43

closing an earthing switch
Initial state:
H earthing switch open
H switch or circuit - breaker open
DANGER
If the incoming line is powered
on, do not close the earthing
switch.

Lift the operating shaft protective
cover.
Separate the pallet with the end of
the lever, then activate the
earthing switch operating
mechanism to the right.

The indicator moves to the earth
position and access to the earthing
switch operating shaft is
blocked.

Separate the pallet with the end of
the lever, then activate the switch
operating mechanism to the left.

The indicator moves to the open
position, and access to the switch
or circuit - breaker operating shaft
is freed.

Lift the operating shaft protective
cover.
Activate the switch operating
mechanism to the right.

The indicator moves to the closed
position, and access to the
earthing switch is blocked.

Press the opening pushbutton of
the circuit - breaker or fuse- switch
combination.

The indicator moves to the open
position, and access to the
earthing switch is freed.

opening an earthing switch
Initial state :
H earthing switch closed
H switch or circuit - breaker open

closing a circuit - breaker
or fuse - switch
combination
Initial state :
H circuit - breaker or fuse- switch
open
H earthing switch open

opening a circuit - breaker
or fuse - switch
combination
Initial state :
H circuit - breaker or fuse- switch
open
H earthing switch open

44

07897073EN01 revision : 11

operating safety

Switch or circuit - breaker closed...

...the earthing switch is blocked.

Earthing switch closed...

...the switch or circuit - breaker
is blocked.

key- locking (optional)

The switches and the
circuit - breaker are locked
in the open position. The earthing
switches are locked in position :
H open
H open/closed
There are various possible locking
diagrams.
H network switch and network
outgoing circuit - breaker
- semi- crossed locking
- crossed locking
H Transformer outgoer :
- RM6/ transformer
- RM6/ low voltage
- RM6/ ransformer/low voltage

padlocking

Switch and earthing switch with
a degree of protection IP3X,
fit a padlock
6mm < handle diameter < 8 mm.

operating shaft padlocking
handle

07897073EN01 revision : 11

45

padlocking the opening
pushbutton
Fit the padlock on the opening
pushbutton
6mm < handle diameter < 8 mm.
A: fuse- switch combined function
or circuit breaker opening push
botton.

A
A

B

with motorization lock
option

NEUTRALIZED VERSION

B: circuit - breaker motorized
C: position of the switch

ON
C
C
C

ON : AUTHORIZED ENGINE
OFF : LOCKED ENGINE

OFF

C

OFF

padlocking the operating
shafts of the switch with the
operating mechanism front
plate removed
fit a padlock
6mm < handle diameter < 8 mm.
in one of the 2 marked holes.
A: padlocking the earthing switch
in the open or closed position
B: padlocking the switch in the
open or closed position

padlocking the operating
shafts of the
circuit - breaker with the
operating mechanism front
plate removed
fit a padlock
6mm < handle diameter < 8 mm.
in one of the 2 marked holes.
A: padlocking the earthing switch
in the open or closed position
B: padlocking the switch in the
open or closed position
46

A
B

A

B

07897073EN01 revision : 11

overcurrent indicator
An overcurrent indicator of the
Alpha M or Alpha E type can be
optionally fitted one of the line
switch.
4 detection thresholds are possible
– 400 A, 600 A, 800 A, 1000 A.

Alpha M type indicator

1

operation

If the reaction current exceeds the
pre- set threshold, the indicator
will send an optical signal on the
faulty phase. The signal will remain
visible until it is manually reset.

2

1) Threshold overshoot optical
signal, one for each phase.
2) Rotary resetting and operating
test button (turn quickly).

Alpha E type indicator

1

3
2

operation

If the reaction current exceeds the
pre- set threshold, the indicator
will send an optical signal on the
faulty phase. The signal will remain
visible for a time that can be
pre- set.
2 hours or 4 hours.
Manual resetting is possible.

1) Threshold overshoot optical
signal, one for each phase.
2) Time during which the signal
remains visible.
Resetting is automatic.
3) Resetting and operating test
pushbutton.

threshold change for Alpha
M and Alpha E type
indicator
CAUTION

To change threshold, cable
appropriately according to the
diagram opposite. The terminal
block is placed behind the device.

07897073EN01 revision : 11

47

LV connection indicator
Flair 2xD

FLAIR 21D

The Flair 21D, 22D and 23DV fault
passage indicator is self- powered
by the measurement sensors.
A minimum 2A current is required
in the MV cable to start up the
Flair 21D display, an energy storage guarantees a 4 hours minimum autonomy.
The Flair devices have an output
contact for interfacing with a
SCADA system.

Flair 23DV has to be supplied
from 24Vdc to 48 Vdc for a permanent display operating and for the
outdoor lamp supply.(With a single
zero sequence CT, self powering is
not possible).

Flair 22D/23DV can be connected
to a voltage presence indicating
system (VPIS) provided with a voltage output (VPIS- VO). In this
case, for greater reliability, fault
detection is confirmed by voltage
absence without taking into
account the current.

FLAIR 22D, et 23DV

detector pending fault
ammeter mode

48

In the absence of a fault, a load current indication is displayed.
The amperage of each phase L1 - L2 - L3 is displayed in succession
with its reference on the left of the display.
Example,
For a load current of 80 A :
for L1
then
for L2
and
for L3
When Flair 22D/23DV is provided with an earth CT (B type mounting),
display of M2 and M3 only.
For each phase: if I>720A display:
if I±2A display:
(Low Power).

07897073EN01 revision : 11

maximeter mode

To access the maximeter function, press once the “Imax.” button.
For each phase, an indication of the maximum load currents since the
last reset is displayed.
Example:
for a max. current of 500 A in phase 1:
followed by M2 and M3.

then

,

The maximeters scroll only once.
All the maximeter values are reset by simultaneous actuation of the
“Test/Reset” and “Imax.” buttons during scrolling.
When Flair 22D is provided with an earth CT (B type mounting), display
of M2 and M3 only.

detector in fault indication

Event A :
the current exceeds one of the thresholds set for
a period ² acknowledge time.
Event B :
the line current disappears (or absence of U with VPIS- VO option, on
Flair 22D/23DV)
Fault indication is active when A is followed by B within a lapse of time of
less than 70 s.
Phase- to - earth fault detected :
display of
or
or
, (or
if earth CT).
the indicator lamp
flashes (1 flash every 3 s) and the output contact is
activated.

H

Phase- to - phase fault detected:
display of
(Over current),
the indicator lamp
flashes (2 flashes every 6 s) and the output
contact is activated.
For these 2 types of faults, the indicator lamp remains flashing until it is
reset (Reset), which can be achieved by:

H

current recovery > 70 s, configurable time delay on Flair 22D/23DV
(Reset active if “Automatic reset” is not on “OFF”)
H U recovery, if VPIS- VO option on Flair 22D/23DV (Reset active if
“Automatic reset” is not on “OFF”)
H end of the time delay, (4 hours on Flair 21D, configurable on Flair
22D/23DV)
H a press on external Reset
H manual actuation of the “Test/Reset” button.
H

maintenance

07897073EN01 revision : 11

The Flair 21D fault passage indicator requires no maintenance (no
electric cells or batteries to be changed regularly)
H The lithium battery of the Flair 22D indicator should be changed about
every 15 years. (for the battery replacement process, call your sales
representative who will put you in contact with the closest :
SCHNEIDER- ELECTRIC group service centre. You can log on to :
www.schneider- electric.com)
H The lithium battery of the BVP option (external indicator unit with
incorporated battery) is to be changed every 15 years.
H

49

settings

The Flair devices (>2010) are a fault passage indicator without settings
(automatic mode).
However, it is possible to perform specific override settings.
In manual mode, settings are made :
using the 3 buttons located under the display, (Flair 22D/23DV).
by micro- switches (drawing opposite).(Flair 21D) The changes are
taken into account after a press on the “Test/Reset” button.

H
H

In AUTO mode I>; I0>, the manual settings are not active.

Test mode

A press on the “Test/Reset” button activates Test mode.
The indicator lamp
flashes, and the BVP and the “OUT” output are
activated until the end of the test.
H The display successively shows
and
and
(software
version)
H
H

setting parameter scrolling
sequence in Test mode for
Flair 21D (automatic on test
mode)

Setting of
automatic fault
detection (*)

or

Network
frequency

or

Imax threshold
“I >”
(Over Current)
(A)
to

Zero sequence
threshold “Io>“
(Earth Fault) (A)

timer reset

to
ammeter mode
10s or “Test/Reset”

When ”Auto” is ”ON”:
Flair 21D uses the following values for fault detection:
H frequency = self- detection
H zero sequence threshold = automatic fault detection for any fault > 20 A
H Imax threshold = automatic fault detection for any fault > 200 A
H
H
H
H
H

50

acknowledge time = 40 ms
Inrush= 3s
CT type = CT1 ( can be changed to CT2 by actualing the buttoms)
Automatic reset = 70s (if automatic reset =on)
Timer reset= 4h

07897073EN01 revision : 11

settings mode (Flair 22D
and Flair 23DV)

07897073EN01 revision : 11

During the Test mode, a press on the
button provides access to
Settings mode (display
).
1) A press on the
button displays the first parameter to be set
2) Several presses on the
button scroll the parameters in a loop.
At this stage, with no actuation of
or
during 10 s,
the indicator returns to ammeter mode.
3) Press the
button to display the current value of the
selected parameter
4) Press the
button again to activate setting of this value:
the display flashes for 5 s
5) During flashing, press
successively to display the desired value
6) Confirm by pressing the
button; without confirmation within a
period of 15 s, return to display of the parameters without change
in the value.
Each press on the “Esc“ (Return) button takes you back to the preceding
stage.

51

connection

BVP:
External indicator
unit with
incorporated battery

Connection of CTs to the 3 MV
cables
H Cable Length : 3 m max.
H Cross section: max. 1.5 mm2
H CTR2200 : mounting without
common point (6 wires)
H MF1 : mounting with or without
common point (4 or 6 wires)

CTs connection

SCADA
output

Important note
(for MF1 split core CTs):
H Mount the 3 CTs facing in the
same direction
H Run the screen earth braid of
the MV cable back inside the CT.
Type

CT1

Réf.

Product

EMS58351

Flair 21D

EMS58352

Flair 22D

EMS58353

Flair 23DV

59925

CTR2200

Description

Common
point

Fault passage
indicator

6- wire mounting
CTR2200 or MF1 CTs

Phase CT for RM6
cubicle bushing

CT2

59963

MF1

4- wire mounting
MF1 CTs

Phase CT for cable
(split toroidal core)

59928

MFC3

3 crimp- on

(pour MF1)

connectors for
6- wire mounting

Flair 22D and Flair 23DV CTs connexion

(wires not supplied)
59962

Faisceau MF1

CT connector cable

or MFH

for 4- wires

BVE:
External indicator
unit

mounting (A or B
type)
59922

Flair 21D BVP

59988

Flair 22D BVE

59927

MFH2200

External indicator unit
SCADA
output

Earth CT
(split toroidal core)

VPIS- Vo

Common
point

4- wire mounting

6- wire mounting
Type A
Type A

Type B

Type A

MF1 CTs

MF1/MFH CTs

MF1 CTs

CTR2200 CTs

Type C mouting ’single zero sequence CT’possible only with flair 23DV

52

07897073EN01 revision : 11

ammeter
The Amp 21D is an ammeter, for
cubicle, automatic and self powered.
The Amp 21D comes into
operation whenever the current is
greater than 3 A on the network.

Test

L1
L2
L3

A

Test button

I max.

I max. button
Easergy
Amp21D
EMS58401

Load current indication

standard operating
measuring mode

maximeter mode

Equipment’s standard operating
mode.
The AMP 21D ammeter displays in
succession, by scrolling, the currents on phases L1,
L2 and L3, and saves to memory
the maximum values.

Maximeter mode (I max.) A press
on the “I max.” button activates the
Maximeter mode.
This mode allows display of the I
maximum values occurring on the
three network phases since the
previous initialization.

At the end of the maximeters’display cycle, the Amp 21D automatically returns to Measuring mode.
The maximeter is reset by simultaneously pressing the “Test” and “I
max.” buttons.

07897073EN01 revision : 11

53

Test mode

Choice of CT type:
H The CT1 option corresponds to
( ref.59925) phase CTs
H The CT2 option corresponds to
( ref.59963) phase CTs
H Factory setting: CT1.

connection of CTs
to the 3 MV cables
Cable length: max. 3 m
Cross section: max. 1.5 mm2
H 3 phase CTs without common
point on a screw - on terminal
block (6 wires)
H MF1: mounting with or without
common point (4 or 6 wires)
H
H

CT connection

IMPORTANT
(for MF1 split core CTs)
H Mount the 3 CTs facing in the
same direction
H Run the earth braid of the MV
cable screen back inside the CT.

Assembly 6 wires
CTR2200 or MF1
phase CTs

Common
point

Assembly 4 wires
MF1 phase CTs

references
Type Ref.

Product

Description

EMS58401

Amp21D

MV ammeter

CT1

59925

CTR2200

Phase CT for RM6 cubicle

CT2

59963

MF1

Phase CT for cable (split toroid)

59928

Set of 3 connectors for MF1

59962

CONNECTING HARNESS FOR MF1

54

3 crimp- on connectors (wires not
supplied)
Connecting harness for MF1 for
assembly 4 wires (A or B type)

07897073EN01 revision : 11

voltage detection relay
The VD23 is a voltage presence
and absence detection relay.
It uses the VPIS V2- V0 as sensor,
and operates with a 24 or 48 Vdc
external power supply.

operation

: automatic frequency detection

Calibration:
At power up, the VD23 automatically detects voltage presence and
the network frequency, and then
performs self- calibration.
Measuring mode:
3 seconds after calibration, the
VD23 displays, by scrolling, the
percentages of the nominal
voltage detected on each phase

: calibration performed

Line- to - neutral voltages
3s

Line- to - line voltages
3s

3s

3s

3s

3s

3s

3s

Detection of Voltage presence:
When the voltage percentage
becomes greater than the set threshold for all the configured
phases, then the VD23 lights the
voltage presence indicator and
activates (or releases in inverted
mode) relay R1.

detection sequence

Detection of Voltage absence:
When the voltage percentage
becomes less than the set threshold for all the configured
phases, then the VD23 lights the
voltage absence indicator and
activates (or releases in inverted
mode) relay R2.

threshold paramater

Configuration: voltages V1,V2,V3,
direct mode
R1: terminal
= relay rest position: voltage loss on at least one of
the phases
R2: terminal
= relay rest
position: voltage presence on at
least one of the phases
A configurable time delay is
applied for control of R1
and R2:T12 = time delay for R1
changeover upon voltage loss
T11 = time delay for R1
changeover upon voltage recovery
T21 = time delay for R2
changeover upon voltage lossT22
= time delay for R2 changeover
upon voltage recovery

07897073EN01 revision : 11

indicator
indicator

55

Mode selection

Measuring
mode
Product
name

Test mode

Software
version

Digits
test

Network frequency
or

Type of
measurement

Configuration mode
Parameters defined
by micro switches

line- to- line

line- to- neutral

Parameters setup
mode
To set the parameter
values, see the
section below

Relay
output

Phase
1

inverted

measured

direct

Voltage
presence

Voltage
absence

Calibration mode

configuration of
thresholds and time
delays
The parameter values (white
screen in the above diagram) can
be modified as follows:

SW 1
SW 2
SW 1
SW 2

56

3 4 5 6

not
measured

not
measured

Phase
3

Residual
voltage

measured

measured

not
measured

not
measured
% of nominal voltage
(10% increments)

Phase voltage
threshold

to

Residual voltage
threshold

to

% of nominal voltage
(10% increments)

Activation time
delay R1 (direct)

to

0 to 1 s (0.1s increments)
1 to 21 s (2s increments)

Release time delay
R1 (direct)

to

0 to 1 s (0.1s increments)
1 to 3 s (0.5s increments)

Phase voltage
threshold

to

% of nominal voltage
(10% increments)

Activation time
delay R2 (direct)

to

0 to 1 s (0.1s increments)
1 to 21 s (2s increments)

Release time delay
R2 (direct)

to

0 to 1 s (0.1s increments)
1 to 3 s (0.5s increments)

or

Forced
calibration

1s

when the value of the parameter
is displayed, a press on the
key
causes the display to flash for 5 s
H during flashing, press
successively
to display the
desired value
H

Set to OFF to retain the last calibration
performed
Calibration performed normally
Error in calibration:
voltage levels too low

confirm this value by pressing
the
button; without confirmation
within a period of 15 s, return
to display of the parameters
without change in the value. Each
press on the “Esc” button takes
you back to the preceding stage.

H

EARTH FAULT DETECTION

EARTHED OR IMPEDANT
GROUNDING

DETECTOR

measured

Automatic
calibration

suggested choice for VD23
settings
VOLTAGE

Phase
2

ISOLATED NEUTRAL

COMPENSATED NEUTRAL

V1+V2+V3+V0
V1.V2.V3.V0
R1
3 4 5 6

U12+U13+U23
U12.U13.U23.

3 4 5 6

U12+U13+U23
U12.U13.U23.

R1

07897073EN01 revision : 11

access to the cable
compartments
access to the cable
connection compartments
without interlocking
CAUTION
The HV cables must be
de- energised for access
to the compartments.
Open the switch and close the
earthing switch.

connection on busbar (O
function and T function)

WARNING

To remove an access panel,
remove the 2 upper screws, lift
and pull towards you.

THE COMPETE SWITCHBOARD
(ALL THE RM6 CONNECTED TOGETHER)
MUST BE DE- ENERGISED

OPEN ALL SWITCHES CONNECTED TO THE BUSBAR
CLOSE ALL ASSOCIATED EARTHING SWITCHES

access to the cable
connection compartments
with interlocking
(optional)

Functional unit in operation,
switch closed.
The access panel is locked.

Open the switch.
The access panel remains locked.

Close the earthing switch.
The access panel is released.

Access panel removed,
the earthing switch can now
be re- opened.

Optionally
Switch and circuit - breaker closing
is inhibited if the access panel
is removed.

07897073EN01 revision : 11

57

Earthing switch open: the access
panel cannot be put back.
If the connectors so allow,
DC current can be injected to
monitor cable insulation or search
for faults.

Close the earthing switch.

Put back the access panel.

Open the earthing switch.

access to the MV
compartment of the
DE- Mt cubicle
DANGER
(B)
Opening of panel (A)
authorized only if :
- all upstream connection(s)
locked- out in OPEN position
- all downstream connection(s)
locked- out in OPEN position.

H

En optional:
a key lock exists
(example B)

DANGER

Intervention inside the DE- Mt
cubicle is authorised only if:
the 3 busbars are grounded,
via a temporary connection or via
an earthing switch (upstream or
downstream).

58

(A)

To remove the access panel (A),
remove the 3 upper screws,
then raise and pull toward yourself.

07897073EN01 revision : 11

preventive maintenance

standard operating
conditions

CAUTION

maintenance summarising
table
description

operation

material

cleaning

cloth

cleaning

sponge, clear water

panelling

earthing covers

device panelling
CAUTION

We draw your attention to the risk
of using high pressure cleaning
processes.
Schneider Electric cannot
therefore guarantee the
reliability of equipment that have
been cleaned in this manner,
even if cleaning was followed by
lubrication.

The main drawbacks of this
process are:
H deterioration due to jet pressure
and impossibility of relubricating
the inaccessible fixing points
H risk of overheating due to
presence of solvent on the contact
zones.
H elimination of special
protections.

Clean using a dry cloth.

earthing covers
CAUTION

maintenance cycle and
operations

07897073EN01 revision : 11

This operation can be performed
in event of excessive soiling.
Clean using a sponge and clear
water. Do not use alcohol or other
solvents to clean.

This device is designed to operate
for 30 years or for 1000 operations
in normal conditions of use as per
standard IEC 62271- 1.

The following are recommended:
- an O/C operation every 6 years
for motorised functional units
and/or functional units with
a latching mechanism
(Q and D/B function)
- replacement of batteries is
recommended every 4 years
- inspection every 5 years of the
condition of the mechanisms (pollution, corossion) and the cleanliness of the earthing covers (pollution).

59

harsh operating conditions
To ensure proper operation of the RM6 in harsh operating conditions, we strongly recommend regular
maintenance of the cubicle and its installation.
Recommended inspection frequency: at least once a year
During the inspection, check the 6 following points:

1 LV compartment

2 earthing covers

symptoms: condensation, presence of humidity
check: for rust on the LV electric and electronic
parts
solutions:
dry the environment
replace the damaged parts
fit heating resistances (optional)

symptoms: humidity, dust
check: surface cleanliness
solutions:
dry the environment
clean using a clean cloth and water
(no alcohol or solvent)

3 mechanical operating mechanisms
11

symptoms: humidity, condensation on live parts

2
3
3
14

55

check: for red rust on moving parts
solutions:
find and treat the origin of condensation phenomena
follow up the damage
replace the operating mechanism if required
(refer to reference: 07897270)

4

MV socket and cable

symptoms: presence of corona discharge
or odours
check: connections (may be damaged)

6
6 trench
symptoms: humidity
check: for presence of water in the trench
solutions:
pump out water
drain the trench
(if necessary add sand)
In case sand is added in the trench, take care
that the cables are still fixed correctly and that no
additional stress is added to the bushings
60

solutions:
fit new sockets

5

fuse compartments

symptoms: humidity + dust
check: proper operation of the VPIS
solutions:
clean the outside surface of the fuse compartments
using a cloth and clear water

07897073EN01 revision : 11

corrective maintenance

foreword
The corrective maintenance
operations enable replacement of
subassemblies.
The operations quoted in the
following summarising table can
be performed by the customer or
by Schneider Electric’s
after- sales representatives.
For any other maintenance
operations, contact the
representatives of your nearest
Groupe Schneider.

After each operation, perform
the electrical tests according to
current standards.

-

Nylstop (self - locking nut)
Contact washer
Locking rings
Mechanical pin

To access the various devices:
open the switches
H close the earthing switches
H cut the supply to the LV circuits

CAUTION

H

On replacement, all the
accessories below must be
replaced with new equipment.

maintenance summarising table
description

réalisation

replacing a voltage indicator

SCHNEIDER ELECTRIC or Customer

replacing a fuse (MV)

SCHNEIDER ELECTRIC or Customer

replacing the charging motor

SCHNEIDER ELECTRIC or Customer

replacing a printed circuit

SCHNEIDER ELECTRIC or Customer

replacing the indicating contact

SCHNEIDER ELECTRIC or Customer

replacement of the voltage
presence unit (VPIS) type
VPIS- V1 by type VPIS- V2

VPIS- V1: production until
February 2009

removing the VPIS- V1
voltage presence unit

A

VPIS- V2: production from March
2009 onwards

B

CAUTION
The screws (A) must be retained.
Unscrew the 2 self- tapping
screws (A).

Remove the VPIS 1 voltage presence box (B).

B

Disconnect the VPIS1 voltage presence unit (B).

07897073EN01 revision : 11

61

contents of the kit
VPIS- V2
1:
2:
3:
4:

1

indicator unit
cable gland seals
surge arrestor
screws (x4)

2

4

3

The screws removed earlier are
reused. (2 self - tapping screws)

mounting the voltage
presence unit (VPIS- V2)

3

2

5

5

checks to be made before
continuing with the operation

RM6

Position the cable gland seal (2)
on the voltage presence connection (5). Check that the seal is in
the correct position.

Clip the cable harness connector
(5) onto the VPIS protection (3)
and fit the seal

Check the condition of the wiring
harness (5) and the VPIS 2 rating
using the optional diagnostic

tool (VPI62420) (not included in
the kit) or see correspondence
table below.

VPI62403
7,4 A

VPI62404
10,7 A

VPI62406
22,4 A

VPI62408
47,2 A

Min

Max

Min

Max

Min

Max

Min

Max

2,5 kV

3,2 kV

3,3 kV

7,7 kV

8,8 kV

16,0 kV

16,1 kV

23,0 kV

5.3 kV

10.6 kV

7.6 kV

15.4 kV

16 kV

32.5 kV

RM6 50 - 60Hz
standard

RM6 50 - 60Hz
BUSHING
WELL only

Key

62

Un : network
voltage

Minimum and maximum network
voltage in 50Hz and 60Hz.

07897073EN01 revision : 11

Please refer to the chapter entitled ”contents of the kit”
1

3

Screw the indicator unit (1) onto
the VPIS surge arrestor (3) using
the 4 screws.

CAUTION
Tighten the screws to exert slight
pressure on the cable gland seal
without distorting it.

Install the voltage presence unit in
the correct position using the 2
self- tapping screws removed earlier.
ATTENTION
The screws removed earlier are
reused.

07897073EN01 revision : 11

63

replacement of the voltage
presence unit (VPIS) type
VPIS- V2 by type VPIS- V2
removing the VPIS 2
voltage presence unit

CAUTION
The screws must be retained.
Remove the 2 screws from the
front panel.

mounting the new
VPIS 2 voltage presence
unit
ATTENTION
Only the indicator unit is to be
changed.
Contact the Schneider Electric
administration for recycling products at the end of their service
life.

Discard the faulty indicator unit.
Leave the existing surge arrestor
and seal.

Remove the unit.
Remove the 4 screws from the
indicator unit.

Install the new voltage presence
indicator unit.

Screw up the 4 screws.
Tighten the screws to exert slight
pressure on the cable gland seal
without distorting it.

CAUTION
The screws removed earlier are
reused.

Install the voltage presence unit in
the correct position using the 2
self- tapping screws removed earlier.

64

07897073EN01 revision : 11

replacing a fuse

Standard IEC 252 paragraph 23.2
recommends replacement of
the 3 HV fuses after blowing
of one of the fuses.

removal
CAUTION

Before performing these
operations, remember that you
close the earthing switch.

CAUTION

Repeat the following operations
for all 3 fuses.
To remove the cover: lift it and pull
it towards you.
The instructions are visible on the
cover.

Release the plug and push the
extraction handle manually to
unlock the plug (tap with the palm
of your hand to separate the seal
from the plug if necessary).

Move the plug up to the limit stop,
swivel it towards the left to remove it.

Recover the centring device at the
top of the fuse.

Extract the fuse.

removing a DIN fuse
(Fusarc CF)

07897073EN01 revision : 11

65

removing a UTE fuse
(Solefuse)

Loosen the fuse using a wrench
with end BTR n° . 5.

Let the plug hang down from
its supporting string.

If the fuse plugs are dirty, clean the
conical surface using silicon oil.
Then wipe it down with a clean
cloth to dry it.
Huile Rhodorsil 47V50.
Distributed by Rhone Poulenc
(chimie Lyon) FRANCE

Talc the clean surface with natural
talc to avoid clinging between the
plug and fuse compartment.
The surface must appear smooth
without lumps.
TALC : westmin 8.
Distributed by Ets Ledoux
Bordeaux FRANCE

cleaning the plugs

fitting a DIN fuse
CAUTION
On no account must a fuse that
has been knocked be installed.
A test prior to installation using
a monitor is recommended.

Insert the fuse in the compartment.
Fit the centring device on the fuse.
Insert the plug pins in the plinth
and swivel it round to the right.
66

07897073EN01 revision : 11

fitting a fuse with striker
Fuse blowing releases a striker
that causes three- phase opening
of the switch and prevents it from
reclosing.

Percuteur
Striker pin
Schlagstift
Percussore

The end of the fuse equipped with
the striker is marked.

The technical data and mounting
direction of the fuse are printed on
the body.
(striker facing upwards).

fitting a UTE fuse
CAUTION
On no account must a fuse that
has been knocked be installed.
A test prior to installation using
a monitor is recommended.

15 Nm

Fix the fuse on the plug using
a torque wrench with end
BTR n° . 5 and insert the fuse
in the compartment.

Insert the plug and fuse assembly
in the compartment.
Insert the plug pins in the plinth
and swivel it round to the right.

Make sure that the handle
trunnions are inserted in the plinth
slots and lock the plug.
Never use the operating lever to
lock the plug.

For replacement of a fuse that has
struck, press the switch to put it
back in position.

locking the plug

07897073EN01 revision : 11

67

access to the LV compartment
dismantling

1- Remove the fuse compartment
cover
(pull towards you)
2- Remove the LV cable trough
6 screws (HM6x16)
3- Remove the self- cutting
screws

2
3
1

reassembling

Reassemble in opposite order
to disassembly.

H

replacing a motor
removal
CAUTION
LV circuit de- energized.

fitting

68

Remove the 3 nuts fixing
the motor support.
Disconnect the motor
supply wiring.

Remove the motor support by
pulling it backwards.

Fit the new motor in the opposite
order to removal.
Tightening torque: 28 Nm.

Fit the trunking and the cover.

07897073EN01 revision : 11

replacing the LV
contacts
Disassemble the pilot light
support.

removal
B

CAUTION

S1

LV circuit de- energized

A
Remove the position indicator A.
Remove interlocking B.
(elastic ring and spring)

Remove contact support S1
without disconnecting the wiring.

S2

Remove contact S3 without
disconnecting the wiring.

S3

S41

S5

Remove the contact support
S2, S4, S5, S6 and S7 without
disconnecting the wiring.

fitting the contacts and
wiring connection

13 Nm

S1

Fit contacts S1 to S7 to replace the
former contacts.
Fit the position indicator and
interlocking.

07897073EN01 revision : 11

Disconnect the contact wiring
S1 disassembled, and connect
it to the new contact.
Repeat this operation for all
the contacts (S2 to S7).
69

processing when
dismantling the equipment

processing of SF6 gas
when dismantling the
equipment
conformity rules

70

The SF6 gas must be removed
before any dismantling operation
can be carried out, according to
the procedures described in
IEC 61634 and according to the
following instructions. The removed gas must be processed in
compliance with IEC 60480.

The after sales of SCHNEIDER
ELECTRIC can propose a complete offer.
- dismantling and recycling of the
RM6 units
- treatment of the SF6 gas.
Finally a certificate will be provied
to you.

07897073EN01 revision : 11

.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................

07897073EN01 revision : 11

71

.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................
.....................................................................................................................................................................

72

07897073EN01 revision : 11

group Schneider Electric service
centers are there for:
engineering and technical
assistance
start-up
training
preventive and corrective
maintenance
adaptation work
spare parts
Call your sales representative
who will put you in touch with
your nearest group Schneider
Electric service centers.

Schneider Electric Industries SAS
89, boulevard Franklin Roosevelt
F- 92500 Rueil- Malmaison (France)
Tel : +33 (0)1 41 29 85 00
http://www.schneider- electric.com

07897073EN01 revision : 11

As standards, specifications and designs change from time
to time, please ask for confirmation of the information given
in this publication.

Conception, rédaction: Service Documentation
Technique T&D

Edition du :

12/2014



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Create Date                     : 2015:02:03 14:11:25+01:00
Modify Date                     : 2015:02:03 14:56:26+01:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2015:02:03 14:56:26+01:00
Producer                        : Acrobat Distiller 10.1.7 (Windows)
Format                          : application/pdf
Title                           : untitled
Document ID                     : uuid:f1c1d51b-d8e7-40d5-aa8e-ec516eb0e577
Instance ID                     : uuid:ab27567e-56be-4f3c-9f43-0f0aa65580a8
Page Count                      : 74
EXIF Metadata provided by EXIF.tools

Navigation menu