981 0516 Onan 10KW HDKAG Genset Service Manual (10 1997) W 1051 Supl
User Manual: 981-0516 Onan 10KW HDKAG Genset Service manual (10-1997) w-981-1051 Supl
Open the PDF directly: View PDF .
Page Count: 67
Download | |
Open PDF In Browser | View PDF |
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x 17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print. Service Manual 10.0 kW HDKAG Generator Sets Printed in U.S.A. 981-0516 10-97 Supplement 981Ć1051 Date: 02Ć05 Insert withĆ Title: HDKAG Service Manual Number (Date): 981Ć0516 (10Ć97) This Supplement transmits changes to Figure 4-5 to illustrate the location of the voltage adjustment pot on newer voltage regulator boards. Replace Sheet 4-5/4-6 with the attached sheet. Page 1 of 1 Redistribution or publication of this document, by any means, is strictly prohibited. GENERATOR OPERATION which in turn supplies the field. Rated output voltage is thereby maintained as the load varies. Refer to Figures 4-3 and 4-4, the generator schematics, while working through the following description. ELECTRONIC VOLTAGE REGULATOR 1. Voltage regulator VR1 (three-phase: VR21) supplies DC to the field winding (F1 - F2 leads) through brushes and slip rings, thereby establishing a revolving 4-pole magnetic field. The battery is connected during startup to initiate field excitation. Voltage regulator VR1 supplies field current during operation. Rated output voltage is maintained as the generator load varies, by varying field current to maintain field strength proportional to the load. 2. The revolving magnetic field induces AC in the stator windings (T1 - T2 and T3 - T4) which are connected to the load. 3. Under light load, the stator windings can supply sufficient current for the field to maintain rated output voltage. 4. As the load increases, load currents increase, resulting in a proportional increase of current, The voltage regulator controls the output of the generator so that a constant voltage is maintained under varying load conditions. Only the basic functions of the regulator are described (Figure 4-5). Voltage from quadrature windings Q1/Q2 supply power to the voltage regulator itself. The voltage regulator in turn supplies an excitation voltage (F1/F2) that is directly proportionate to the output voltage (L1/L0) it senses. Any changes in the generator output voltage produce a corresponding change in the excitation voltage provided by the regulator. On the HDKAG, the voltage regulator assembly includes a potentiometer which enables a slight degree of output voltage adjustment. The voltage regulator assembly contains no user-serviceable parts. If the assembly fails, it must be replaced. NEWER BOARDS CAUTION: The V/Hz Break Point Pot is Factory Set and Sealed. DO NOT ADJUST. OLDER BOARDS VOLTAGE ADJUST: Trim pot adjusts output voltage level. Turn pot clockwise to increase voltage. Turn pot counterclockwise to decrease voltage. FIGURE 4-5. ADJUSTMENTS ON GENSET VOLTAGE REGULATOR BOARD 4-5 Redistribution or publication of this document, by any means, is strictly prohibited. GENERATOR SERVICE 4. Install the new brushes and springs in the holder and keep them in place during assembly by inserting a piece of wire through the holder, as shown in Figure 4-7. Always disconnect the battery cables (negative [-] first) from the battery to prevent accidental starting of the set while servicing the generator. 5. Install the brush holder. After tightening the mounting screws, pull out the brush retaining wire. WARNING Accidental starting of the set while working on it can cause severe injury. To prevent accidental starting, disconnect the battery cables (negative [-] first) from the battery. 6. Connect the F1 lead to the inner brush terminal (nearest the rotor windings). Connect the F2 lead to the outer brush terminal (nearest the end bell). The negative (-) cable is always disconnected first, and connected last, to prevent arcing if a tool accidentally touches the frame or other grounded metal parts of the set while disconnecting or connecting the positive (+) cable. Arcing can ignite the explosive hydrogen gas given off by the battery, and cause severe injury. Slip Ring Inspection/Replacement Inspect the slip rings for grooves, pits or other damage. If dust has accumulated on any generator components, they can be cleaned with filtered lowpressure air. 1. Examine the slip rings while servicing the brushes. Brush Inspection/Replacement The generator should be inspected for brush wear and cleaning every six months. 2. If the rings need cleaning or service, remove the rotor from the generator and dress the rings on a lathe. WARNING Accidental starting of the generator set can cause severe personal injury or death. Stop the generator set and disable by disconnecting the starting battery cables (negative [-] cable first) before inspecting the generator. CAUTION Dressing the slip rings on a lathe improperly may damage the generator rotor. Make certain that only an experienced technician performs this job. 1. Remove the access cover for the brush assembly. 2. Check the brushes for wear with a piece of wire marked off 1 inch (25 mm) from one end (Figure 4-6). Replace the brush and the spring if the wire goes into the brush holder 1 inch or more. 3. To replace brushes, remove the brush holder by disconnecting the two leads to the holder and removing the two mounting screws. Generator Bearing Inspect the bearing for evidence of outer case rotation every 1000 hours of use. The bearing should be replaced every five years, because the bearing grease gradually deteriorates due to oxidation. Replace the O-ring if it shows evidence of wear or deterioration. Renew grease if necessary (moly only). 4-6 Redistribution or publication of this document, by any means, is strictly prohibited. California Proposition 65 Warning Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm. Redistribution or publication of this document, by any means, is strictly prohibited. Table of Contents SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-1 1-1 1-1 1-1 1-3 2 ENGINE CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start Control at Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2-1 2-1 2-6 3 ENGINE CONTROL SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [A] Battery Check (BT1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [B] Battery Cable Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [C] Battery Charging Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [D] Start Solenoid Check (K11) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [E] Heater (Glow Plug) Relay Check (K13) . . . . . . . . . . . . . . . . . . . . . . . . . . [F] Fuel Solenoid Check (K14) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [G] Start/Stop Switch Check (S11) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [H] Power Relay Check (A11-K12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3-1 3-1 3-1 3-1 3-1 3-2 3-2 3-2 3-2 4 GENERATOR/VOLTAGE REGULATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Generator Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Generator Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Generator Disassembly/Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4-1 4-5 4-5 4-6 4-8 5 GENERATOR/REGULATOR TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . 5-1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Troubleshooting Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 6 GENERATOR/REGULATOR TESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [A] Testing Field Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [B] Testing Generator Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [C] Testing Generator Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [D] Dynamic Rotor/Stator Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [E] Voltage Regulator Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [F] Wiring Harness Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [G] Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [H] Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6-1 6-1 6-1 6-2 6-3 6-5 6-5 6-5 6-5 Redistribution or publication of this document, by any means, is strictly prohibited. i 7 ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Generator Set Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2 Oil and Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4 Fan Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7 Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9 Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9 AC Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10 Crankcase Breather . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10 Muffler/Spark Arrester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11 Cleaning the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11 Initial Starting and Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11 8 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1 Redistribution or publication of this document, by any means, is strictly prohibited. ii Safety Precautions Thoroughly read the OPERATOR’S MANUAL before operating the genset. Safe operation and top performance can be obtained only with proper operation and maintenance. • Used engine oil has been identified by some state and federal agencies as causing cancer or reproductive toxicity. Do not ingest, inhale, or contact used oil or its vapors. The following symbols in this Manual alert you to potential hazards to the operator, service person and equipment. • Benzene and lead in some gasolines have been identified by some state and federal agencies as causing cancer or reproductive toxicity. Do not to ingest, inhale or contact gasoline or its vapors. Alerts you to an immediate hazard which will result in severe personal injury or death. • Do not work on the genset when mentally or physically fatigued or after consuming alcohol or drugs. Alerts you to a hazard or unsafe practice which can result in severe personal injury or death. • Carefully follow all applicable local, state and federal codes. Alerts you to a hazard or unsafe practice which can result in personal injury or equipment damage. GENERATOR VOLTAGE IS DEADLY! • Generator output connections must be made by a qualified electrician in accordance with applicable codes. Electricity, fuel, exhaust, moving parts and batteries present hazards which can result in severe personal injury or death. • Make sure all fasteners are secure and torqued properly. • The genset must not be connected to the public utility or any other source of electrical power. Connection could lead to electrocution of utility workers, damage to equipment and fire. An approved switching device must be used to prevent interconnections. • Keep the genset and its compartment clean. Excess oil and oily rags can catch fire. Dirt and gear stowed in the compartment can restrict cooling air. • Use caution when working on live electrical equipment. Remove jewelry, make sure clothing and shoes are dry and stand on a dry wooden platform on the ground or floor. • Let the engine cool down before removing the coolant pressure cap or opening the coolant drain. Hot coolant under pressure can spray out and cause severe burns. FUEL IS FLAMMABLE AND EXPLOSIVE GENERAL PRECAUTIONS • Keep ABC fire extinguishers handy. • Keep flames, cigarettes, sparks, pilot lights, electrical arc-producing equipment and switches and all other sources of ignition well away from areas where fuel fumes are present and areas sharing ventilation. • Before working on the genset, disconnect the negative (- ) battery cable at the battery to prevent starting. • Fuel lines must be secured, free of leaks and separated or shielded from electrical wiring. • Use caution when making adjustments while the genset is running—hot, moving or electrically live parts can cause severe personal injury or death. • Use approved non-conductive flexible fuel hose for fuel connections at the genset. Redistribution or publication of this document, by any means, is strictly prohibited. iii ENGINE EXHAUST IS DEADLY! BATTERY GAS IS EXPLOSIVE • Learn the symptoms of carbon monoxide poisoning in this Manual. • Wear safety glasses and do not smoke while servicing batteries. • Never sleep in the vehicle while the genset is running unless the vehicle has a working carbon monoxide detector. • When disconnecting or reconnecting battery cables, always disconnect the negative (- ) battery cable first and reconnect it last to reduce arcing. • The exhaust system must be installed in accordance with the genset Installation Manual. • Do not use engine cooling air to heat the vehicle interior. DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS • Make sure there is ample fresh air when operating the genset in a confined area. Flammable vapor can cause a diesel engine to overspeed and become difficult to stop, resulting in possible fire, explosion, severe personal injury and death. Do not operate a diesel-powered genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the genset safely. Contact your authorized Onan/Cummins dealer or distributor for more information. MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH • Do not wear loose clothing or jewelry near moving parts such as PTO shafts, fans, belts and pulleys. • Keep hands away from moving parts. • Keep guards in place over fans, belts, pulleys, etc. Mobile-3 Redistribution or publication of this document, by any means, is strictly prohibited. iv 1. Introduction ABOUT THIS MANUAL SAFETY CONSIDERATIONS This manual contains troubleshooting and repair data for these components of the HDKAG generator set: Generator sets present safety hazards that the technician must know about. Read the precautions on the inside cover of this manual. Familiarize yourself with the hazards shown in Table 1-1. When the hazards are known, approach the job with a safetyconscious attitude. Being safety-conscious is the best way to avoid injury. Reduce the chance of an accident with the following safeguards. • Control • Generator See the Engine Service Manual for engine information. Safeguards To Avoid Hazards Study this manual carefully. Heed all warnings and cautions. Proper use and maintenance can result in longer set life, better performance and safer operation. • Use Protective Clothing. Protect your body by wearing protective clothing such as: • Safety shoes • Gloves • Safety glasses • Hard hats This manual contains basic wiring diagrams and schematics for troubleshooting. Technicians should use the wiring diagram and schematic shipped with each unit. Update these diagrams and schematics when the set is modified. Leave rings and jewelry off. Do not wear loose clothing that might get caught on equipment. PC board information is limited; in the field, it is more efficient to replace the boards than to attempt repair. • Reduce Workshop Hazards. • Keep guards and shields in place on ASSISTANCE machinery • Maintain equipment in good working order • Store flammable liquids in approved When contacting an Onan distributor, supply the complete model number and serial number shown on the Onan nameplate on the side of the generator control box. • • • TEST EQUIPMENT • • • • • • • • Multimeter/digital VOM AC voltmeter DC voltmeter Frequency meter Jumper leads Load test panel Megger or insulation resistance meter Wheatstone bridge or digital ohmmeter • containers away from open flame, spark, pilot light, cigarette, or other ignition source Keep the workshop clean and well-lighted Provide adequate ventilation Keep a fire extinguisher and safety equipment nearby Be prepared to respond to an emergency • Develop Safe Work Habits. Unsafe actions are the source of most accidents with tools and machines. Be familiar with the equipment and know how to use it safely. Use the right tool for the job, and check its condition before starting. Observe the warnings and cautions in this manual and take special precautions when working around electrical equipment. Do not work alone if possible and do not take unnecessary risks. WARNING Incorrect service or replacement of parts can result in severe personal injury, death, and /or equipment damage. Service personnel must be qualified to perform electrical and mechanical service. 1-1 Redistribution or publication of this document, by any means, is strictly prohibited. • Be prepared if an accident occurs. to be ready to respond to an accident. Learn to be safety conscious and make safe practices a part of your work routine. Do not work when tired or after consuming any alcohol or drug that makes the operation of equipment unsafe. Agencies such as the Red Cross and local police and fire departments offer courses in first aid, CPR, and fire control. Take advantage of this information TABLE 1-1 HAZARDS AND THEIR SOURCES • Fire and explosions • Leaking fuel • Hydrogen gas from charging battery • Oily rags improperly stored • Flammable liquids improperly stored • Any fire, flame, spark, pilot light, arcproducing equipment or other ignition sources • Burns • Hot exhaust pipes • Hot engine and generator surfaces • Hot engine oil • Electrical short in DC wiring system • Hot engine coolant • Poisonous gases • Carbon monoxide from faulty exhaust pipes, joints or hangers • Operating generator set where exhaust gases can accumulate • Electrical shock (AC) • Improper genset load connections • Faulty RV wiring • Faulty electrical appliance • Faulty genset wiring • Working in damp conditions • Jewelry touching electrical components • Rotating Machinery • Flywheel fan guard not in place • Jewelry or loose clothing catching in moving parts • Slippery Surfaces • Leaking or spilled oil • Heavy Objects • Removing generator set from RV • Removing heavy components 1-2 Redistribution or publication of this document, by any means, is strictly prohibited. 3. Disconnect the remote control plug wire from the generator set (if applicable). SET REMOVAL Some service procedures require removing the generator set from the vehicle. Because of the wide variety of installations, it is not possible to specify exact removal procedures for each genset. If a satisfactory method for removing a particular set cannot be determined, contact the vehicle manufacturer or the set installer for their recommendations. 4. Disconnect the generator load wires. Tag for identification when reconnecting. 5. Disconnect the exhaust system and support brackets or hangers, to allow set removal. WARNING Generator sets are heavy and they can cause severe personal injury or death if dropped during removal. Use adequate lifting devices to provide sufficient support for the set. Keep hands and feet clear while lifting the generator set. Before starting set removal, place the transmission in park, set the emergency brake, and remove the negative (-) cable from the vehicle ignition system battery to avoid inadvertent movement of the vehicle. 6. Disconnect the fuel line at the genset housing. Securely plug the end of the fuel line to prevent fuel leakage. 7. Verify that the set is adequately supported before loosening any mounting bolts or support members. WARNING Leakage of fuel presents the hazard of fire or explosion that can cause severe personal injury or death. Make certain all fuel line openings are plugged. Before disconnecting the fuel line, be certain there are no ignition sources such as flame, spark, pilot light, cigarette, etc., near the generator set. Keep an ABC type fire extinguisher nearby. Disconnecting Generator Set Systems Some installations require partial removal of the set to gain access to the battery cable, fuel line, and other connections. Read this entire section before starting set removal. The following steps are a general guideline. WARNING Leakage of fuel in or around the generator set compartment presents the hazard of fire or explosion that can cause severe personal injury or death. Do not disconnect or connect battery cables if fuel vapors are present. Ventilate the compartment thoroughly: park vehicles outdoors in a well ventilated area. When reinstalling the set, be sure all mounting hardware, and electrical, exhaust, and fuel system components are connected exactly as they were before removal. See the appropriate installation manual during reinstallation for important safety precautions. 1. Disconnect the generator set negative (-) battery cable at the battery terminal. Check for oil and fuel leaks. Check the exhaust system audibly and visually with the generator set running. Repair leaks immediately. Replace worn, damaged, or corroded exhaust and fuel line components before leaks occur. 2. Disconnect the generator set positive (+) battery cable from the wire harness. 1-3 Redistribution or publication of this document, by any means, is strictly prohibited. Blank Page 1-4 Redistribution or publication of this document, by any means, is strictly prohibited. 2. Engine Controls Control Components GENERAL The following describes the basic engine control components and how they function. This section describes the generator set preheat/ start/run control system. The set may be started either at the onboard DC control box or by using a remotely mounted start control. A11 Engine Monitor Circuit Board: A circuit board that monitors the engine control system functions. This includes starting, stopping, and fault system operation. Terminals are included for making remote connections. See Figure 2-1. START CONTROL AT SET The set is started with a Start/Stop/Preheat switch on the front panel of the DC control box. Component references are found on wiring/schematic diagrams in the Wiring Diagrams section of this manual. Two relays soldered into the engine monitor board are not serviceable. They function as follows: • Power relay K12 connects battery B+ to the The DC control box does not contain meters and is designed for remote mounting within limits of the wire harness (approximately 32 inches [813 mm]). An optional remote control panel with meters is available in a kit from Onan. control meters and fuel solenoid during operation. • Starter protection relay K15 is AC operated. When the Start switch is pressed, B+ is connected to K11 start solenoid through the K15 NC contacts until the generator output reaches about 90 volts AC. At this voltage K15 activates and disconnects the starter circuit. Switches Start-Stop/Preheat Switch S11: Starts and stops the unit locally. Preheat function occurs when the switch is held in the Stop position. The unit may also be operated from a remote switch wired to receptacle J3 on the rear panel. Circuit Breakers K11 Start Solenoid: Located over the engine monitor circuit board (above K13 glow plug heater solenoid). It connects battery B+ to the start solenoid, K13 heater solenoid, fuel solenoid and meters during cranking. DC Control Breaker CB11: A 15 ampere DC breaker providing protection to the control box wiring and remote wiring from short circuits or overload. Also serves as an emergency stop switch. K13 Glow Plug Heater Solenoid: Located directly above the monitor circuit board. Connects B+ to the engine glow plugs during cranking. It is energized by K11 start solenoid. Fault Breaker CB12: A manual reset breaker that shuts down the engine for low oil pressure and high coolant temperatures. K14 Fuel Solenoid: It opens the fuel control valve when the start/stop switch is placed in the Start position. 2-1 Redistribution or publication of this document, by any means, is strictly prohibited. S11 START-STOPPREHEAT SWITCH COVER J3 REMOTE CONNECTION J1 AC INPUT A11 ENGINE MONITOR CIRCUIT BOARD RELAY - START SOLENOID J2 ENGINE HARNESS DC WIRING HARNESS CR2 RECTIFIER ASSEMBLY DC CONTROL BREAKER CB11 CB12 FAULT BREAKER 300-3203 FIGURE 2-1. HDKAG GENERATOR SET DC CONTROL BOX Engine Monitors Oil Pressure Monitors Refer to Figure 2-2 for the location of the oil pressure monitors. This section briefly describes the engine sensors (switches) and optional gauge senders. The sensors protect the engine from unfavorable operating conditions; the senders are used with the operational remote panel. These sealed units are not repairable. Do not use a substitute part if replacement is necessary, since they are close-tolerance parts made for a specific application. Oil Pressure Sender E1: The sender resistance changes with oil pressure and results in a reading on the (optional) oil pressure meter. The meter range is 0 to 100 psi (0 to 700 kPa). Low Oil Pressure Switch S1: This switch closes if oil pressure drops to 9 psi (62 kPa), activating the fault breaker and stopping the engine. Control Power Latch S6: This oil pressure switch closes at 5 psi (34 kPa) and provides a latch function for the control circuits. When closed, the switch supplies a ground path for relay K12 on the engine monitor board. The safety sensors (switches) close the fault circuit to ground if abnormal operating conditions exist, tripping the fault breaker CB12 to stop the engine. See Figure 2-2 and the schematic in Figure 2-3. 2-2 Redistribution or publication of this document, by any means, is strictly prohibited. OIL PRESSURE SWITCH (S1) (SHUTDOWN) OIL PRESSURE SENDER (M12) COOLANT SHUTDOWN SWITCH (S2) OIL PRESSURE SWITCH (S6) (POWER LATCH) COOLANT TEMPERATURE SENDER (E2) FIGURE 2-2. HDKAG FAULT SENSOR LOCATIONS 2-3 Redistribution or publication of this document, by any means, is strictly prohibited. Start-Disconnect Sequence: As the generator gains speed and output voltage, A11-K15 starter protection relay energizes at about 90 VAC. A11-K15 NC contact opens and de-energizes start solenoid relay K11. K11 then disconnects B+ from the starter solenoid (to stop the cranking motor) and from the glow plug heaters. If the generator fails to develop voltage, the engine will attempt to start but will stop as soon as the Start switch is released. Engine Temperature Monitors Refer to Figure 2-2 for the location of the engine temperature sensors. Coolant Temperature Sender E2: The resistance of the sender unit changes with the engine coolant temperature and causes a reading on the coolant temperature meter (optional). The meter range is 100° to 250° F (40° to 121° C). The two K15 NO (normally open) contacts close and function as follows: High Coolant Temperature Switch S2: This switch closes if the coolant temperature rises to 250° F (121° C), activating the fault breaker CB12 and stopping the engine. • Closes circuit for S1 and S2 (low oil pressure and high coolant temperature switches respectively) Control Operation To understand control operation, refer to the following text and the schematic diagram (Figure 2-3). • Provides another ground path for K12 coil Starting Sequence: When start/stop switch S11 is held in the Stop (preheat) position, battery B+ is connected to the coil of heater relay K13. The relay contacts close and connect B+ to heaters HR1 HR4. Battery Charge Circuit: Alternator G1, powered by a belt from the engine, supplies B+ voltage to recharge the generator set starting battery through circuit breaker CB13. After the preheat time interval, the operator holds S11 in the Start position. This connects B+ to K14 fuel solenoid relay and through A11-K15 NC (normally closed) contacts to K11 start solenoid relay. These relays actuate K1 fuel solenoid, B1 solenoid/ starter motor and heaters HR1 - HR4 (via K13 NC contacts). Stopping Sequence: Placing S11 in the Stop position puts B+ (through diode CR2) on the ground side of the A11-K12 power relay. This causes K12 to deenergize and disconnect B+ from CB12 and K1 fuel solenoid. De-energizing K1 shuts off the fuel flow to stop the engine. (through K11 coil) similar to S6. Fault Shutdown: Fault breaker CB12 opens to stop the engine any time a fault sensor closes the circuit to ground. The fault sensors as shown in Figure 2-2 are: A11-K12 power relay is actuated after a short delay, when the control power latch switch S6 closes. S6 is closed when oil pressure rises to 5 psi (34 kPa), assuring engine lubrication before the set reaches full operating speed. Normally open (NO) contacts on A11-K12 close, supplying B+ to the other components on the engine monitor board. • S1 low oil pressure • S2 high coolant temperature 2-4 Redistribution or publication of this document, by any means, is strictly prohibited. ENGINE PARTS B1 BT1 E1 E2 HR1-4 E5 K1 S1 S2 S6 G1 Starter and solenoid Battery (12V) Sender (oil pressure) Sender (coolant temperature) Heater - glow plug Fuel pump - electric Fuel solenoid Switch - low oil pressure Switch - high coolant temperature Switch - control power latch Alternator CONTROL BOX PARTS A11 CB11, 13 CB12 K11 PCB assy - engine monitor Circuit breaker (control) Circuit breaker (fault) Relay - start solenoid (starter) (12 V) A11-K12 Relay - power K13 Relay - heater K14 Relay - fuel solenoid A11 - K15 Relay - starter protection K15 Relay A11 - R1 Resistor (K12) A11 - R2 Resistor (LOP timing) S11 Switch - start/stop/preheat J3 - J4 Connector - remote FIGURE 2-3. DC CONTROL SCHEMATIC DIAGRAM 2-5 Redistribution or publication of this document, by any means, is strictly prohibited. Remote Control Operation (Optional): The generator set may be operated from a remote switch connected to the control receptacle J3. Installation instructions are furnished with the kit available from Onan. See Figure 2-4. J4 CONTROL TROUBLESHOOTING The information in this section is divided into three flow charts. Determine the problem and then refer to the appropriate flow chart (A, B, or C) for the troubleshooting procedures. J3 A. Engine does not crank. B. Engine cranks but does not start. C. Engine starts but stops after running several seconds. Before starting a troubleshooting procedure, make a few simple checks that may expose the problem and cut down on troubleshooting time. START-STOP/ PREHEAT RUN LIGHT • Check all modifications, repairs, and re- OIL PRESSURE placements performed since last satisfactory operation of set. A loose wire connection overlooked when installing a replacement part could cause problems. An incorrect connection, an opened switch or circuit breaker, or a loose plug-in are all potential problems that can be eliminated by a visual check. WATER TEMPERATURE • Unless absolutely sure that panel instruRUNNING TIME METER ments are accurate, use portable test meters for troubleshooting. To troubleshoot a problem, start at the upper-left corner of chart and answer all questions either YES or NO. Follow the chart until the problem is found, performing referenced adjustments or test procedures. Refer to Figures 2-1 through 2-4 for locating control components, leads, terminals and other check points. FIGURE 2-4. REMOTE CONTROL WIRING DIAGRAM 2-6 Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART A. ENGINE DOES NOT CRANK Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. WARNING START Is battery dead? yes no Check CB11 circuit breaker. If okay, jumper battery cable B+ connection to B1 starter solenoid terminal. Does engine crank? no Check battery per Checkout [A] and recharge or replace. Check battery charger operation per Checkout [C]. Check battery cables for clean tight connections (ref. Checkout [B]). Check B1 starter solenoid and motor: if bad, repair or replace. yes With S11 in Start position, is battery voltage present between K11 terminal S and ground? no yes If K11 does not energize, test per Checkout [D] and replace if bad. Is battery voltage present at B1 solenoid terminal with S11 in Start position? no 2-7 Check B+ wiring to S11, and between S11 and K11. Check NC contacts of A11-K15. Replace if bad. Check B+ wiring between K11 and B1 solenoid terminal. Replace if bad. Check K1 plunger travel for freedom to bottom in solenoid (necessary to open pull coil circuit). Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART B. ENGINE CRANKS BUT DOES NOT START WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. START Is engine getting fuel? Exhaust smoke should be blue-white and fuel flow steady from fuel return line. no Check fuel system: fuel tank level, shut-off valves, fuel lines and connections, fuel filters, fuel pump and injection pump. Okay? yes Does K14 fuel solenoid energize when S11 is in Start position? yes no Is battery B+ applied to glow plug heaters when switch S11 is in Preheat and Start positions? yes Check B+ circuit through S11. Test S11 per Checkout [G]. Test K14 per Checkout [F]. no Incorrect fuel? See Operator’s Manual recommendations. Check switch S11 per Checkout [G]. Check heater relay per Checkout [E]. Check heater wiring. 2-8 Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART C. ENGINE STARTS BUT STOPS AFTER RUNNING SEVERAL SECONDS WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. Is a fault condition indicated by fault breaker CB12 on control panel? yes Check for a possible fault condition. If none, check fault monitors S1 through S4 and fault breaker CB12 for improper wiring. no Check relay K12 per Checkout [H]. Is K12 good? no yes Does DC control breaker trip after generator set is started? yes 2-9 Check for closing of S6 power latch switch. If switch is OK, check mechanical adjustment of K1 solenoid: is rod adjusted to correct length to allow the hold-in coil of K1 to latch? If K1 adjustment is OK and problem remains, replace engine monitor PC board. Check all B+ wiring for shorts to ground. Check fuel solenoid adjustment. Redistribution or publication of this document, by any means, is strictly prohibited. Blank Page 2-10 Redistribution or publication of this document, by any means, is strictly prohibited. 3. Engine Control Service 2. From the battery positive post to the battery terminal stud on the solenoid GENERAL The following checks are referred to in the Control Troubleshooting flow charts. They isolate circuit problems caused by faulty engine control components. Disconnect leads before testing components. Normally these should be less than 0.3 volts. If extra-long battery cables are used, slightly higher voltage drops may result. Thoroughly clean all connections in any part of the circuit showing excessive voltage drop. WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. [C] BATTERY CHARGING CHECK With the engine running, check the DC voltmeter (control option). The 12-volt system should read 13.5 to 15 volts. [A] The power source is a belt-driven alternator. The charge rate/voltage is determined by a voltage regulator located inside the control box. BATTERY CHECK (BT1) Check the battery charge condition with a hydrometer. Electrolyte specific gravity should be about 1.260 for a fully charged battery at 80°F (27°C). If not, add distilled water to keep electrolyte at proper level, then recharge the battery. If the battery will not recharge, replace it. Improper output may be caused by a loose drive belt, poor terminal connections, broken wires, bad regulator or alternator. Checkout procedures for the regulator and alternator are found in the engine service manual. The charge circuit is protected by circuit breaker CB13. If the battery loses excess water, the charge rate may be too high. If the battery charge is not maintained, the charge rate may be too low. See procedure [C]. If the output voltage is high (over 15 volts), check for loose or corroded voltage regulator leads. If this does not correct the problem, the regulator is probably shorted and should be replaced. Ignition of explosive battery gases can cause severe personal injury. Do not permit any flame, spark, cigarette, or other ignition source near the battery. [D] WARNING START SOLENOID CHECK (K11) 1. Apply battery positive (B+) to the terminal marked S. [B] 2. Connect a ground wire to the solenoid terminal marked I. The solenoid should activate. BATTERY CABLE CHECK With the starter motor running, check these voltage drops: 3. If the contacts are good, battery voltage should be read between terminal 1 and ground. The voltage drop measured across the contacts should never exceed one volt in circuit application. 1. From the battery negative post (not the cable clamp) to the cylinder block 3-1 Redistribution or publication of this document, by any means, is strictly prohibited. 3. Open and close switch while observing the ohmmeter. A normally open (NO) switch should indicate infinite resistance when open and continuity when closed. A normally closed (NC) switch should indicate continuity when closed and infinite resistance when open. [E] HEATER (GLOW PLUG) RELAY CHECK (K13) 1. Connect the relay coil voltage across the relay coil terminals. The relay should activate if coil is okay. 4. Replace switch if defective. [H] 2. Connect a voltage source to one side of relay contacts. POWER RELAY CHECK (A11-K12) 3. Connect a voltmeter to other side of relay contact and voltage source. If voltage appears when relay energizes, the contact is good. The voltage reading appears in reverse order when checking normally closed (NC) contacts. Make certain that the genset starting battery is good before beginning this check. 1. Unplug CB12-2A from the circuit breaker. Note the markings on the wire to select the correct one. [F] 2. Locate S6 (oil pressure switch) on the genset (see Figure 2-2). Find the grounded side of S6, using a continuity tester. FUEL SOLENOID CHECK (K14) If there is fuel to the injection pump, but no fuel at the injection nozzle, the fuel solenoid may be defective. 3. Use a jumper to ground the non-grounded side of S6. To check solenoid operation, watch for solenoid actuation when B+ is applied (start switch in start or run position). If there is no actuation when B+ is applied, the fuel solenoid must be replaced. When B+ is removed, the solenoid must de-activate. 4. Use a second jumper from the B+ terminal on the control board to apply B+ to the SW B+ (switched B+) terminal. Fuel pump E5 should start and run. 5. Remove the B+ jumper. If the fuel pump continues to run, K12 is good. If the fuel pump stops, K12 has failed and the A11 control board should be replaced. [G] START/STOP SWITCH CHECK (S11) 1. Remove battery B+ cable. 6. Push the genset STOP button. 2. Place ohmmeter leads across switch. 7. Remove the jumpers and reconnect CB12-2A. 3-2 Redistribution or publication of this document, by any means, is strictly prohibited. 4. Generator/Voltage Regulator erator cooling air which is drawn in through the end bell and discharged through an outlet in the blower end. GENERAL DESCRIPTION The YK generator (Figure 4-1) is a four-pole, revolving field, brush-type design with drip-proof construction. A ball bearing in the end bell supports the outer end of the rotor shaft. The end bell is attached with four studs that thread into the generator adapter casting. The genset brushes are mounted in the end bell (see Figure 4-2). The generator rotor is directly coupled to the engine flywheel with a rigid drive disc. Engine speed determines generator output voltage and frequency. A centrifugal blower on the drive disc circulates genSTATOR ASSEMBLY GENERATOR ADAPTER FAN GUARD END BELL COVER ROTOR ASSEMBLY OUTPUT AND CONTROL LEADS COLLECTOR RINGS GENERATOR DRIVE DISK GENERATOR DRIVE HUB END BELL ASSEMBLY (SEE FIGURE 4−2 FOR BRUSH CONFIGURATION) STATOR ASSEMBLY STATOR WRAPPER END BEARING GENERATOR FAN FIGURE 4-1. YK SERIES GENERATOR 4-1 Redistribution or publication of this document, by any means, is strictly prohibited. LEAD (F1 TO VR1−1) LEAD (F2 TO VR1−2) O−RING BRUSH BLOCK ASSEMBLY FIGURE 4-2. GENSET END BELL WITH BRUSHES 4-2 Redistribution or publication of this document, by any means, is strictly prohibited. FIGURE 4-3. SINGLE-PHASE GENERATOR SCHEMATIC 4-3 Redistribution or publication of this document, by any means, is strictly prohibited. FIGURE 4-4. THREE-PHASE GENERATOR SCHEMATIC 4-4 Redistribution or publication of this document, by any means, is strictly prohibited. which in turn supplies the field. Rated output voltage is thereby maintained as the load varies. GENERATOR OPERATION Refer to Figures 4-3 and 4-4, the generator schematics, while working through the following description. ELECTRONIC VOLTAGE REGULATOR 1. Voltage regulator VR1 (three-phase: VR21) supplies DC to the field winding (F1 - F2 leads) through brushes and slip rings, thereby establishing a revolving 4-pole magnetic field. The battery is connected during startup to initiate field excitation. Voltage regulator VR1 supplies field current during operation. Rated output voltage is maintained as the generator load varies, by varying field current to maintain field strength proportional to the load. 2. The revolving magnetic field induces AC in the stator windings (T1 - T2 and T3 - T4) which are connected to the load. 3. Under light load, the stator windings can supply sufficient current for the field to maintain rated output voltage. 4. As the load increases, load currents increase, resulting in a proportional increase of current, The voltage regulator controls the output of the generator so that a constant voltage is maintained under varying load conditions. Only the basic functions of the regulator are described (Figure 4-5). Voltage from quadrature windings Q1/Q2 supply power to the voltage regulator itself. The voltage regulator in turn supplies an excitation voltage (F1/F2) that is directly proportionate to the output voltage (L1/L0) it senses. Any changes in the generator output voltage produce a corresponding change in the excitation voltage provided by the regulator. On the HDKAG, the voltage regulator assembly includes a potentiometer which enables a slight degree of output voltage adjustment. The voltage regulator assembly contains no user-serviceable parts. If the assembly fails, it must be replaced. VOLTAGE ADJUST: Trim pot adjusts output voltage level. Turn pot clockwise to increase voltage. Turn pot counterclockwise to decrease voltage. BOARD SHOWN WITHOUT COVER FIGURE 4-5. ADJUSTMENTS ON GENSET VOLTAGE REGULATOR BOARD 4-5 Redistribution or publication of this document, by any means, is strictly prohibited. 4. Install the new brushes and springs in the holder and keep them in place during assembly by inserting a piece of wire through the holder, as shown in Figure 4-7. 5. Install the brush holder. After tightening the mounting screws, pull out the brush retaining wire. 6. Connect the F1 lead to the inner brush terminal (nearest the rotor windings). Connect the F2 lead to the outer brush terminal (nearest the end bell). GENERATOR SERVICE Always disconnect the battery cables (negative [-] first) from the battery to prevent accidental starting of the set while servicing the generator. WARNING Accidental starting of the set while working on it can cause severe injury. To prevent accidental starting, disconnect the battery cables (negative [-] first) from the battery. The negative (-) cable is always disconnected first, and connected last, to prevent arcing if a tool accidentally touches the frame or other grounded metal parts of the set while disconnecting or connecting the positive (+) cable. Arcing can ignite the explosive hydrogen gas given off by the battery, and cause severe injury. Slip Ring Inspection/Replacement Inspect the slip rings for grooves, pits or other damage. If dust has accumulated on any generator components, they can be cleaned with filtered lowpressure air. 1. Examine the slip rings while servicing the brushes. 2. If the rings need cleaning or service, remove the rotor from the generator and dress the rings on a lathe. Brush Inspection/Replacement The generator should be inspected for brush wear and cleaning every six months. WARNING Accidental starting of the generator set can cause severe personal injury or death. Stop the generator set and disable by disconnecting the starting battery cables (negative [-] cable first) before inspecting the generator. Dressing the slip rings on a lathe improperly may damage the generator rotor. Make certain that only an experienced technician performs this job. CAUTION 1. Remove the access cover for the brush assembly. 2. Check the brushes for wear with a piece of wire marked off 1 inch (25 mm) from one end (Figure 4-6). Replace the brush and the spring if the wire goes into the brush holder 1 inch or more. 3. To replace brushes, remove the brush holder by disconnecting the two leads to the holder and removing the two mounting screws. Generator Bearing Inspect the bearing for evidence of outer case rotation every 1000 hours of use. The bearing should be replaced every five years, because the bearing grease gradually deteriorates due to oxidation. Replace the O-ring if it shows evidence of wear or deterioration. Renew grease if necessary (moly only). 4-6 Redistribution or publication of this document, by any means, is strictly prohibited. SPRING BRUSH GENERATOR BEARING 1 INCH MEASURING WIRE WIRE ES1676 BRUSH BLOCK ASSEMBLY FIGURE 4-6. CHECKING GENERATOR BEARING AND BRUSH BLOCK HOLDER FIGURE 4-7. BRUSH REPLACEMENT 4-7 Redistribution or publication of this document, by any means, is strictly prohibited. 5. Lift the rear of the set and place a wooden block under the generator adapter to hold the stator and housing in place. Make certain that the engine-to-generator adapter (bolted to the engine) is propped up high enough for the generator adapter assembly (bolted to the generator) to clear the rear genset mounts when it is pulled off the set. A block approximately 3.5 inches wide (standard 2 x 4 lumber width) will hold the adapter high enough. Remove the two rubber vibration isolators whose bolts were removed in the last step. GENERATOR DISASSEMBLY/ASSEMBLY The following sections describe the disassembly and reassembly procedures for the generator. Figure 4-8 illustrates generator disassembly. Generator components are heavy and can cause severe personal injury if dropped during service. Be careful, use appropriate lifting techniques, keep hands and feet clear during service, and use the recommended service procedures. WARNING 6. Remove the end bell cover and disconnect F1 (outer) and F2 (inner) lead wires from the brush holder terminals. Note that the control box and air cleaner assembly need not be removed from the set to disassemble the generator. These components may remain attached to the stator housing, and will be removed with it. 7. Pull each brush away from the commutator rings and insert a piece of stiff wire into the small hole in the brush holder. See Figure 4-7. Disassembly 1. Remove the generator set from the vehicle and place it on a sturdy work bench. Refer to Section 1 of this manual for removal guidelines. Note that the brushes may be secured (as described in the last two steps) at any convenient point during this procedure. 8. Remove four nuts and lock washers from the generator stud bolts. Remove the end bell cover and pry the end bell free of the rotor bearing. Be careful not to damage the brush holder. WARNING Accidental starting of the set can cause severe personal injury or death. Disconnect the battery cables, negative (-) lead first, when repairs are made to the engine, controls or generator. 9. Pull the stator/wrapper assembly with the control boxes off the rotor and away from the engine. Set it aside. 2. Remove the cover from the AC control box and disconnect all stator leads (Q1-Q50/60, T1-T2-T3-T4, F1-F2, S1-S2). Disconnect leads at the load circuit breaker(s). If the lead markings do not clearly identify reconnection, mark the leads with tape. 10. Remove the four bolts that hold the generator adapter and fan guard to the engine-to-generator adapter. Pull the adapter/guard assembly off the adapter and set it aside. 11. Loosen the six bolts that hold the rotor drive disk to the engine flywheel. Loosen these bolts in an alternating pattern, so that the drive disk does not bend from the weight of the rotor. 12. Pull the rotor, fan and drive disk assembly off the flywheel and set them aside. 3. Remove the bonding strap between the stator assembly and the drip pan. 4. Loosen and remove the two bolts that extend through the rear genset mounts (under the stator housing). 4-8 Redistribution or publication of this document, by any means, is strictly prohibited. END BELL ASSEMBLY BRUSH BLOCK O−RING FAN STUD BOLT (1 OF 4) SPRING BRUSH END BEARING END BELL COVER ROTOR ASSEMBLY ENGINE−GENERATOR ADAPTER MOUNTING FOOT STATOR ASSEMBLY xES2095s FIGURE 4-8. GENERATOR DISASSEMBLY/REASSEMBLY 4-9 Redistribution or publication of this document, by any means, is strictly prohibited. 2. Apply Loctite #680 adhesive to the shaft mating surface. 3. Apply Loctite #747 activator to the bearing mating surface. 4. Install the bearing and allow ten minutes curing time before handling the assembly. Rotor Disassembly 1. Place the rotor assembly on a wood block in the horizontal position. The drive disc and fan should not be resting on anything, or distortion may occur. 2. Remove the six bolts that hold the drive disk and fan to the rotor hub. Remove the drive disk and fan. Rotor Reassembly After necessary service checks and repairs are made, the rotor and generator are reassembled using the reverse procedure of disassembly except for the rotor as noted below. Regrease the O-ring using moly grease only. Apply required torque value shown in Figure 4-9. 3. Use a gear puller to remove the end bearing from the rotor shaft. The end bearing will be damaged if pulled on the outer race. If the bearing must be removed, replace it; this bearing should not be reused. CAUTION CAUTION The drive disk will be damaged if the bolts are tightened and it is not properly centered. Center the disk accurately before beginning to tighten the drive disk. Rotor Bearing Replacement 1. Clean the bearing and shaft mating surfaces. 4-10 Redistribution or publication of this document, by any means, is strictly prohibited. COLLECTOR RINGS ROTOR WINDINGS GENERATOR DRIVE DISK REMOVE SIX BOLTS AND WASHERS TO REMOVE DRIVE DISK FROM HUB: TORQUE TO 25−29 N−M WHEN REPLACING GENERATOR DRIVE HUB END BEARING ROTOR ASSEMBLY GENERATOR FAN FIGURE 4-9. ROTOR ASSEMBLY COMPONENTS 4-11 Redistribution or publication of this document, by any means, is strictly prohibited. Blank Page 4-12 Redistribution or publication of this document, by any means, is strictly prohibited. A. NO AC OUTPUT VOLTAGE AT RATED ENGINE RPM GENERAL This section contains troubleshooting information for the HDKAG generator and voltage regulator. Make the following visual checks before starting: B. UNSTABLE OUTPUT VOLTAGE, ENGINE SPEED STABLE • Check any modification or repair that was done since the last satisfactory operation of the set. Verify that it was done properly. C. OUTPUT VOLTAGE TOO HIGH OR TOO LOW • Check to see that generator leads are connected correctly. Also check the voltage regulator and control component connectors. A loose, contaminated, or misplaced wire connection can be detected by close inspection. D. UNBALANCED OUTPUT VOLTAGE To troubleshoot a problem, start at the upper left corner of the chart that corresponds to the problem, and answer all questions either YES or NO. Follow the chart until the problem is found. Perform the referenced test or adjustment procedures in the Generator/Regulator Tests section. • Check for an open circuit breaker. If the breaker is open, check for an overloaded circuit and correct load problems before resetting the breaker. TROUBLESHOOTING PROCEDURES Components referenced in the flow charts, tests and adjustment procedures are found in the schematics and wiring diagrams in Section 9 of this manual. Determine the type of problem, then refer to the corresponding flow chart (A, B, C, or D) for troubleshooting procedures. 5-1 Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART A. NO AC OUTPUT VOLTAGE AT RATED ENGINE RPM WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. START Are load circuit breakers closed? Locate cause of overload and correct as required. Reset breaker, or replace if bad. no yes Check continuity of circuit breakers and replace if necessary. Is circuit open between brush block and voltage regulator? yes Check for continuity and correct if circuit is open. no Test field voltage per TEST [A]. Is there correct field voltage? yes Perform TEST [D]. yes Release brushes if jammed in holder. Clean slip rings if dirty. no Are brushes stuck in holder or not making good contact with slip rings? no Examine brush block connections. Are F1 and F2 leads installed on correct terminals? no Connect brush leads to correct terminals. yes Test continuity of rotor, stator per Tests [B], [C]. Are there opens or grounds? Replace component if defective. yes 5-2 Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART B. UNSTABLE VOLTAGE, ENGINE SPEED STABLE WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. START Are there any broken wires or loose connections on voltage regulator assembly? yes Repair as required. no Repair wiring or replace as required. no Repair or replace as required. no Check wiring harness from regulator assembly to end bell per TEST [F]. Check OK? yes Inspect brushes per procedure in Manual Section 4. Brushes OK? yes Replace the voltage regulator per procedure [E]. CAUTION A new voltage regulator can be damaged by malfunctioning components. Do not install a new voltage regulator until all other problems have been located and corrected. 5-3 Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART C. OUTPUT VOLTAGE TOO HIGH OR TOO LOW WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. START Is engine running at correct RPM? no Set RPM per instructions in appropriate engine manual. yes Set control per Voltage Adjustment [G]. yes Remove part of the set load. yes Are generator output leads properly connected? See TEST [H]. yes Does adjustment of Voltage Adjust control on the regulator board result in correct output voltage? no Is the set AC output overloaded? no Are voltage regulator connections secure? yes CAUTION A new printed circuit board can be damaged by malfunctioning components within the control. Do not install a new PC board until all other problems have been located and corrected. 5-4 Perform procedure [D]. If correctly functioning rotor/stator indicates a bad voltage regulator, replace it per procedure [E]. Redistribution or publication of this document, by any means, is strictly prohibited. FLOW CHART D. UNBALANCED GENERATOR OUTPUT VOLTAGE WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review Safety Precautions. START Remove load at generator terminals. Is output still unbalanced? no Check for correct grounding of generator and load. no Correct as necessary. no Replace stator assembly. yes Are generator leads connected and grounded properly? See Test [C]. yes Is generator stator winding continuous per TEST [C]? yes Check load for ground faults and correct as necessary. 5-5 Redistribution or publication of this document, by any means, is strictly prohibited. Blank Page 5-6 Redistribution or publication of this document, by any means, is strictly prohibited. Section 6. Generator/Regulator Tests GENERAL [B] TESTING GENERATOR ROTOR The following tests and adjustments can be performed without disassembly of the generator. These procedures should be used for testing the generator components and the regulator in conjunction with the Troubleshooting Flow Charts in the Generator/Regulator Troubleshooting section. The generator circuits can be tested without having to disassemble the generator. It is recommended that an ohmmeter be used to check for open circuits and an insulation resistance meter for grounded circuits. An ohmmeter can be used to check for grounded circuits, but it may not be able to detect marginal insulation breakdown. WARNING Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on inside cover page. MEGGER OR INSULATION RESISTANCE METER [A] TESTING FIELD VOLTAGE Field voltage can be tested at the brush holder terminals with a DC voltmeter. Field voltage should fall between 18 and 60 volts. Test at no load and at full load. See Figure 6-1. CONNECT LEADS BETWEEN EACH RING AND ROTOR SHAFT LEAD (F2 TO VR1−2) TEST POINTS ES2068s LEAD (F1 TO VR1−1) FIGURE 6-2. TESTING ROTOR FOR GROUNDS Testing for Grounds Check for grounds between each slip ring and the rotor shaft, Figure 6-2. Use a Megger or insulation resistance meter which applies 500 VDC or more at the test leads. Perform test as follows: 1. Isolate the rotor windings by disconnecting the two leads to the brush holder. 2. Connect test leads between each ring and the rotor shaft in turn. Meter should register 100,000 ohms or greater. BRUSH BLOCK ASSEMBLY 3. If less than 100,000 ohms, rotor is questionable. Thoroughly dry the rotor and retest. FIGURE 6-1. FIELD VOLTAGE TEST POINTS 4. Replace a grounded rotor with a new identical part. 6-1 Redistribution or publication of this document, by any means, is strictly prohibited. [C] TESTING GENERATOR STATOR Testing for Open or Shorted Windings Perform this test with an accurate meter such as a digital ohmmeter. 1. Isolate the rotor windings by disconnecting the two leads to the brush holder. Isolate the stator windings by disconnecting all six stator leads. Test for open circuits between T1-T2, T3-T4 and Q1-Q2, and for grounded circuits between T1, T3 and B1 and the stator laminations or other unpainted grounding point. 2. Using ohmmeter, check resistance between F1 and F2 by connecting leads between the F1 and F2 slip rings, Figure 6-3. Using proper test equipment, check the stator for grounds, opens, and shorts in the windings. Rotor resistances (measured at 25° C) are: Testing for Grounds Standard single-phase: 17.2 ohms Standard three-phase: 19.4 ohms Extended-stack three-phase: 22.5 ohms Extended-stack three-phase “husky”: 25.5 ohms Some generators have ground connections to the frame. Check wiring diagram. All stator leads must be isolated for testing. Use a megger or insulation resistance meter which applies not more than 500 VDC to the test leads (Figure 6-4). Test each stator winding for short to laminations. A reading less than 100,000 ohms indicates a questionable stator. Thoroughly dry the stator and retest. If there is a large difference, replace the defective rotor with a new, identical part. DIGITAL OHMMETER CONNECT LEADS BETWEEN F1, F2 SLIP RINGS CONNECT LEADS BETWEEN EACH WINDING AND GROUND ES2070s ES2069s FIGURE 6-4. TESTING STATOR WINDING FOR GROUNDS FIGURE 6-3. TESTING ROTOR FOR AN OPEN CIRCUIT 6-2 Redistribution or publication of this document, by any means, is strictly prohibited. [D] DYNAMIC ROTOR/STATOR TEST Testing for Open or Shorted Windings Test for continuity between coil leads as shown in Figure 6-5; all pairs should have equal resistance. Use an accurate instrument for this test such as a Wheatstone Bridge. The following procedure serves as a functional voltage regulator check, by determining if the problem is in the voltage regulator or in the generator. The voltage regulator is temporarily replaced with a 12-volt battery (the genset starting battery is usable here); 12 volts applied to the F1/F2 exciter stator should produce approximately 125 volts generator output voltage at L1 and L2, with no load. Stator resistances (measured at 25° C) are: Standard single-phase: T1-T2, T3-T4: 0.221 ohms Q1-Q60: 1.997 ohms Q1-Q50: 2.405 ohms Standard three-phase: T1-T4, T2-T5, T3-T6, T7-T10, T8-T11, T9-T12: 0.505 ohms Q2-T11: 0.252 ohms Extended-stack three-phase: T1-T4, T2-T5, T3-T6, T7-T10, T8-T11, T9-T12: 0.153 ohms Q2-T11: 0.305 ohms Extended-stack three-phase heavy-duty: T1-T4, T2-T5, T3-T6, T7-T10, T8-T11, T9-T12: 0.107 ohms Q2-T11: 0.214 ohms WARNING Electrical shock can cause severe personal injury or death. Do not touch electrical wiring or components during testing. Disconnect electrical power by removing starting battery negative (-) cable before handling electrical wiring or components. Use a sharp voltage probe and touch it carefully to the connector pins or output terminals when making these tests. 1. Stop the generator set. 2. Unplug the voltage regulator from the wiring harness. CAUTION Failure to unplug the voltage regulator at this point in the procedure could lead to equipment damage. If a winding is shorted, open or grounded, replace the stator assembly. Before replacing the assembly, check the leads for broken wires or insulation. 3. Using jumpers and a spare plug or other connector, connect a 12-volt battery to the F1/F2 terminals as illustrated in Figure 6-6. 4. Start the generator set. Use a voltmeter to measure the outputs at J4-4 - J4-6, L1 - L2, L1 L0, L2 - L0, Q60 - Q1 (50 Hz sets: Q50 - Q1), and S1 - S2. The output voltages should read as follows (all voltages apply to both 50 Hz and 60 Hz sets): J4-4 - J4-6: 62 VAC ± 20 VAC L1 - L2: 125 VAC ± 20 VAC L1 - L0: 62 VAC ± 20 VAC L2 - L0: 62 VAC ± 20 VAC Q60 - Q1: 75 VAC ± 20 VAC (50 Hz sets) Q50 - Q1: 75 VAC ± 20 VAC S1 - S2: 62 VAC ± 20 VAC CONNECT LEADS BETWEEN PAIRS OF STATOR WINDING LEADS ES2071s If these voltages are measured, then the generator is operating correctly and the problem is elsewhere. FIGURE 6-5. TESTING STATOR WINDING RESISTANCE 6-3 Redistribution or publication of this document, by any means, is strictly prohibited. MEASURE 125 VAC MEASURE 62 VAC MEASURE 62 VAC − + MEASURE 62 VAC MEASURE 75 VAC APPLY 12 VDC MEASURE 62 VAC MEASURE 75 VAC FIGURE 6-6. DYNAMIC ROTOR/STATOR TEST 6-4 Redistribution or publication of this document, by any means, is strictly prohibited. sure the generator set has stabilized and is running at the correct speed (frequency). The regulator is adjusted with the set running. [E] VOLTAGE REGULATOR REPLACEMENT Use the following procedure for replacing the AC voltage regulator assembly. WARNING Accidental starting of the set can cause severe personal injury or death. Disconnect both battery cables, negative (-) cable first, when repairs are made to the engine, controls, or generator. 1. Stop the generator set and disconnect the starting battery leads, negative (-) lead first. 2. Unscrew the voltage regulator from the control box. WARNING Contact with high voltage can cause severe personal injury or death. Do not touch any exposed wiring or components with any part of the body, clothing, tool or jewelry. Do not use non-insulated tools inside the control. Stand on an insulating mat or dry wood platform when the control doors are open. 3. Disconnect the regulator from the wiring harness. 4. Remove the mounting screws from the old voltage regulator, then install the new regulator. 5. Reconnect the plug connection to the wiring harness. Output voltage adjustments are found on the voltage regulator board under the DC control box. A removable cover protects the board. See Figure 6-7. 6. Set voltage as outlined in [G] Voltage Adjustment. [F] 1. Attach a voltmeter securely to the L1 and L2 leads. WIRING HARNESS CHECK Carefully check the wiring harness as follows: 2. Start the generator set and place a typical load on its output. 1. Inspect all wires for breaks, loose connections, and reversed connections. Refer to applicable wiring diagram. 3. Use a flat-blade screwdriver to set the voltage adjust potentiometer for correct voltage. 2. Remove wires from terminals at each end and with an ohmmeter, check each wire end to end for continuity or opens. For most 60 Hz applications, the ideal setting is 117 VAC at 60-61 hz, measured at the power input of the application. Retighten the locking nut when complete. 3. Using an ohmmeter, check each wire to other wires and to ground for possible shorts or insulation breaks under areas covered by wrapping material. Note that the voltage adjustment pot on the voltage regulator board is a 10-turn potentiometer: it may take several turns to change the voltage noticeably. 4. Reconnect or replace wires/harness according to applicable wiring diagram. [H] [G] RECONNECTION VOLTAGE ADJUSTMENT Generator reconnection is dependent upon the nameplate code. See Section 8 for reconnection diagrams. This section describes adjustment of the genset output voltage. When checking output voltage, be 6-5 Redistribution or publication of this document, by any means, is strictly prohibited. VOLTAGE ADJUST: Trim pot adjusts output voltage level. Turn pot clockwise to increase voltage. Turn pot counterclockwise to decrease voltage. BOARD SHOWN WITHOUT COVER FIGURE 6-7. LOCATION, OUTPUT VOLTAGE ADJUSTMENT 6-6 Redistribution or publication of this document, by any means, is strictly prohibited. Section 7. Routine Maintenance hours indicated, whichever comes first. Refer to the Maintenance Procedures section for instructions. If the generator set will be subjected to extremely hot or dusty conditions, a more frequent maintenance schedule may be necessary. INTRODUCTION This section describes routine maintenance procedures to be performed on the generator set. Most of this information is duplicated in the Operator’s Manual, publication #981-0137. Many of the items in this section refer to the genset engine: for more information, refer to the Engine Workshop Manual. WARNING Accidental starting of the generator set during maintenance can cause severe personal injury or death. Disconnect both generator set starting battery cables, before performing maintenance. Remove the negative (-) cable first to reduce the risk of arcing. MAINTENANCE SCHEDULE Perform each maintenance procedure at the time period indicated or after the number of operating TABLE 7-1. PERIODIC MAINTENANCE SCHEDULE SERVICE THESE ITEMS Inspect set Check oil level Check coolant level Check fuel level Check air cleaner dust cap (clean if required) Check battery charging system Check drive belt tension Clean out spark arrester Check battery specific gravity Change crankcase oil and filter Drain water/sediment from fuel filter Check antifreeze Clean generator assembly Drain sediment from fuel tank Clean crankcase breather Check fuel shut-off linkage Change fuel filter element Check genset brushes Change air cleaner element Clean cooling system Daily or after 8 hours x1 x x x SERVICE TIME Weekly Monthly 6 Months Yearly or or or or after after after after 50 hours 100 hours 250 hours 500 hours x3 x x x4 x x x2 x x x x5 x3 x x x x3 x 1 - Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with genset running and repair any leaks immediately. 2 - Perform after first 35 hours of operation on new genset. 3 - Perform more often in extremely dusty conditions. 4 - Visually check belts for evidence of slippage. 5 - Drain one cup of fuel to remove water and sediment. 7-1 Redistribution or publication of this document, by any means, is strictly prohibited. GENERATOR SET INSPECTION Fuel leakage will create a fire hazard which can result in severe personal injury or death if ignited. While checking for leaks, do not smoke or allow any spark, flame, pilot light or other ignition source in the area. If any leaks are detected, have them corrected immediately. WARNING Inspect the generator set daily or after every eight hours of operation, whichever comes first. Check the exhaust, fuel, and DC electrical systems as described below. Also check the mechanical condition of the set. Engine Gauges (Remote Installation) DC Electrical System Check these gauges while the set is running. With the genset off, check the battery terminals for clean and tight connections. Loose or corroded connections create resistance which can impede starting. Clean and reconnect loose battery cables. Always disconnect the negative battery cable first and connect it last, to reduce the possibility of arcing. Oil Pressure Gauge: Oil pressure should be 40 to 60 psi (276 to 414 kPa) when the engine is at operating temperature. Coolant Temperature Gauge: Coolant temperature should be 165° to 195° F (74° to 91° C), depending on load and ambient temperature. WARNING Ignition of explosive battery gases can cause severe personal injury. Do not smoke. Wear goggles, protective rubber gloves and apron when servicing batteries. DC Voltmeter: Battery voltage during operation should be 14 to 15 volts. Exhaust System Mechanical With the set running, inspect the entire exhaust system including the exhaust manifold, exhaust elbow, muffler and exhaust pipe. Visually and audibly check for leaks at all connections, welds, gaskets, and joints. If any leaks are detected, shut down the genset and do not operate until corrected. Replace corroded exhaust components before leaks occur. Check for any signs of mechanical damage. Start the set and listen for any unusual noises that may indicate mechanical problems. Check the mounting fasteners to make sure the set is secure in its compartment. If an under-floor housing is used, make sure that the set is secured to the housing. Check the condition of the housing components and make sure they are secure to the vehicle. Inhalation of exhaust gases can result in severe personal injury or death. Inspect exhaust system audibly and visually for leaks daily. Repair all leaks immediately. WARNING Make sure that the generator set air inlet and outlet areas are not blocked with debris. Clean the generator set whenever dust and dirt begin to accumulate. Dust and dirt can usually be removed with a damp cloth. Steam cleaning may be needed to remove road contaminants. Do not clean the genset while the engine is running. Protect the generator, air cleaner, control panel, and electrical connections from cleaning solvents. Cleaning solvents can damage electrical connectors. Fuel System With the set running, inspect the fuel supply lines, return lines, filters, and fittings for leaks. Check flexible sections for cuts, cracks and abrasions. See that the fuel lines do not rub against anything that could break them. Replace worn fuel line components before leaks occur. 7-2 Redistribution or publication of this document, by any means, is strictly prohibited. gine oil can cause cancer or reproductive toxicity. When adding, changing or working with used oil, take care not to breathe, ingest or come into excessive contact with these substances. Wash hands after use. Wear protective clothing and equipment. Provide adequate ventilation. OIL AND FILTER CHANGE Change the oil and filter at the intervals listed in Table 7-2. Use oil that meets the API classification and SAE viscosity grade indicated in the previous section. Engine Oil Change Oil Filter Change Run the engine until thoroughly warm. Stop the engine, open the drain valve (Figure 7-1) and drain the oil into a container. When completely drained, close the valve and refill the crankcase with new oil. Spin off the oil filter and discard it. Thoroughly clean the filter mounting surface. Apply a thin film of oil to the filter gasket, and spin the filter on until the gasket just touches the mounting pad. Then turn an additional 3/4 turn. Do not over-tighten the filter. WARNING Hot crankcase oil can cause burns if it is spilled or splashed on skin. Keep fingers and hands clear when removing the oil drain plug and wear protective clothing. With oil in the crankcase, start the set and check for leakage around the filter gasket. Tighten the filter only enough to eliminate leaks. State or federal agencies have determined that prolonged contact with used enWARNING OIL FILL ALTERNATE OIL FILL AT TOP OF CYLINDER HEAD COVER (HIDDEN) OIL DIPSTICK DRAIN VALVE OIL FILTER FIGURE 7-1. ENGINE OIL 7-3 Redistribution or publication of this document, by any means, is strictly prohibited. Add coolant to the recovery tank (or separate expansion tank if equipped) to the full-cold level. COOLING SYSTEM The cooling system must be filled with coolant before the genset can be operated. Cooling system capacity is listed in the Specifications section. Start the engine, then remove the pressure cap and monitor the coolant level. As trapped air is expelled from the system, the coolant level will drop. Add coolant to replace it. Replace the pressure cap when the coolant level is stable. Coolant Requirements Engine coolant must inhibit corrosion and protect against freezing. A 50/50 mixture of ethylene glycol anti-freeze and water is recommended for normal operation and storage. Use only a reliable brand of antifreeze that contains a rust and corrosion inhibitor. The antifreeze must not contain a stop-leak additive. Coolant Level Check the coolant level at the intervals specified in the Periodic Maintenance Schedule. Check by observing the coolant level in the recovery tank (or separate expansion tank if equipped) when the system is cold. See Figure 7-2 for a typical cooling system. Engine coolant is at the proper level when the recovery tank level is between FULL and LOW marks. Do not exceed a 50/50 mixture of ethylene glycol and water. A higher proportion of ethylene glycol will alter the heat transfer properties of the coolant. A 50/50 mixture will provide freeze protection to -34° F (-37° C). Water used for engine coolant should be clean, low in minerals, and free of corrosive chemicals. Use distilled or soft water if available. Avoid the use of well water, which may contain minerals that can clog the heat exchanger core and reduce cooling efficiency. WARNING Coolant in a warm engine is under pressure and can flash to steam causing severe burns if the radiator cap or drain cock are opened. Let the engine cool down before opening the radiator cap or drain cock. Filling the Cooling System The high engine temperature cutoff will shut down the engine in an overheat condition only if the coolant level is sufficiently high to physically contact the shutdown switch. Loss of coolant will allow engine to overheat without protection of shutdown device, thereby causing severe damage to the engine. It is therefore imperative that adequate engine coolant levels be maintained for operational integrity of the cooling system and engine coolant overheat shutdown protection. CAUTION Verify that all drain cocks are closed and all hose clamps are secure. Remove the cooling system pressure cap and slowly fill the cooling system with the coolant mixture. Exceeding the recommended fill rate can cause incomplete filling of the engine block, leading to engine damage during warmup. Always follow the recommended fill procedure. CAUTION 7-4 Redistribution or publication of this document, by any means, is strictly prohibited. HOSE IS CONNECTED AT RADIATOR CAP BRACKET RECOVERY TANK OVERFLOW HOSE RADIATOR COOLANT DRAIN (ON LOWER REAR CORNER OF RADIATOR) G1250s CYLINDER BLOCK COOLANT DRAIN (REAR OF GENSET ENGINE BLOCK SHOWN WITHOUT SHEET METAL, EXHAUST PARTS) FIGURE 7-2. COOLING SYSTEM COMPONENTS 7-5 Redistribution or publication of this document, by any means, is strictly prohibited. FAN BELT Flushing and Cleaning A loose fan belt can cause the engine to overheat. The belt tension must be correct for the set to run well. Once a year, drain, flush and refill the cooling system with new coolant. To drain the system, open the radiator coolant drain and the cylinder block drain on the the rear (non-service access) side of engine. See Figure 7-2. First, remove the generator set’s starting battery cables (negative [-] cable first). WARNING Accidental starting of the set can cause severe personal injury or death. Stop the generator set and disable it by disconnecting the starting battery cables (negative [-] cable first) when maintaining or repairing the engine, controls, or generator. Contact with hot coolant can cause severe burns. Do not bleed hot, pressurized coolant from a closed cooling system. WARNING Chemical Cleaning: Rust and scale slow heat absorption and can block coolant flow. Clean the cooling system if rust and scale have collected on the engine water jacket or in the heat exchanger. Use a good cleaning compound and follow its instructions. To reach the fan belt, remove the belt guard from the front of the set. Do not operate the genset without the belt guard in place. To adjust the belt, loosen the bolt that passes through the long slot in the alternator mounting bracket and slide the alternator until the tension is right. See Figure 7-3. Flushing: After cleaning, or before filling the system with new coolant, drain the system and fill with clean water. Run the genset for 10 minutes, then drain the system completely. Refill with the coolant mixture. Belt tension is correct when a finger pressure of 22 pounds (10 kg) at the middle of the belt deflects it about 0.4 inch (10 mm). CAUTION Never pour hot water into a cold engine or cold water into a hot engine. Doing so can crack the head or the cylinder block. Do not operate the unit without water for even a few minutes. PUMP/ FAN PULLEY ADJUST TENSION HERE Thermostat If the engine overheats or does not reach and maintain a minimum operating temperature, have the thermostat removed and tested. Replace the thermostat with the gasket if necessary. See the Engine Workshop Manual for instructions on thermostat removal and testing. ALTERNATOR Pressure Cap Closed cooling systems use a pressure cap to increase the boiling point of the coolant and allow higher operating temperatures. Replace the pressure cap every two years, or sooner if it malfunctions. CS-1239 FIGURE 7-3. FAN BELT ADJUSTMENT 7-6 Redistribution or publication of this document, by any means, is strictly prohibited. Ignition of fuel can cause serious personal injury or death by fire or explosion. Do not permit any flame, cigarette, pilot light, spark or other igniter near the fuel system. Low fuel in the tank promotes condensation. In warm weather, the fuel tank cools at night quicker than the fuel. If the fuel level is low, the upper portion of the tank will cool more rapidly, forming condensation. In cold weather, the warm fuel returning from the injectors heats the fuel in the supply tank. If the fuel is low, condensation may form on the upper part of the tank. To avoid condensation, fill the fuel tank every time the genset is used. Fuel Recommendation Fuel Filter Use ASTM 2-D (no. 2 Diesel) or ASTM 1-D (No. 1 Diesel) fuel with a minimum Cetane number of 45. Number 2 diesel fuel gives the best economy and performance under most conditions. Use number 1 diesel fuel when ambient temperatures are below 32° F (0° C), and during long periods of light engine load. The wrong fuel or dirty fuel will shorten the life of the fuel filter. See the Periodic Maintenance Schedule for the filter change interval. FUEL SYSTEM Use the best fuel available. Fuel quality is important for dependable performance and satisfactory engine life. WARNING CAUTION Dirt or water in the system will cause severe damage to both the injection pump and the injection nozzles. It is extremely important that the fuel be kept clean and free of water. Use low sulfur content fuel which has a cloud point at least 10 degrees below the lowest expected fuel temperature. (Cloud point is the temperature at which wax crystals begin to form in diesel fuel.) Refer to the Periodic Maintenance Schedule for the recommended filter change interval. However, if the engine shows signs of fuel starvation (reduced power or surging), the fuel filter must be changed. This involves purging the fuel system of trapped air. See Priming the Fuel System later in this section. Fuel Handling Precautions Prevent dirt, water or other contaminants from entering the fuel system. Filter or strain the fuel as the tank is filled. High Pressure Fuel System: The injection pump, fuel injection lines and fuel injectors are the high pressure fuel system. See Figure 7-4. The highpressure system is self-priming; trapped air is forced out through the injection nozzles. CAUTION Due to the precise tolerances of diesel injection systems, dirt or water in the system will cause severe damage to both the injection pump and the injection nozzles. It is extremely important that the fuel be kept clean and water free. Low Pressure Fuel System The electric fuel pump, fuel filter and injection pump inlet comprise the low pressure fuel system. See Figure 7-4. These components are normally primed (purged of trapped air) at set installation. Be sure to check the fuel level in the tank and that the shutoff valve is open. Condensation (water) can cause clogging of fuel filters as well as freezing problems. Water mixing with the sulfur in the fuel forms acid which can corrode and damage engine parts. 7-7 Redistribution or publication of this document, by any means, is strictly prohibited. FUEL RETURN LINE FITTING INJECTION PUMP FUEL INLET INJECTION LINE CONNECTING NUT FUEL FILTER FUEL INLET FUEL PUMP FIGURE 7-4. FUEL SYSTEM 7-8 Redistribution or publication of this document, by any means, is strictly prohibited. 1. Keep the battery case clean and dry. AIR CLEANER 2. Make certain that the battery cable connections are clean and tight. Use a terminal puller tool to remove the battery cables. The air cleaner element (Figure 7-5) is a dry type and should never have oil applied to it. Avoid touching the element except when cleaning it. Instructions for cleaning the element are on a label attached to the element. Change the element yearly, or more often in extremely dusty conditions. OUTLET Remove corrosion from the battery terminal connections. Wash the terminals with an ammonia solution or a solution consisting of 1/4 pound (about 100 grams) of baking soda in 1 quart (about 1 liter) of water. Be sure the vent plugs are tight to prevent cleaning solution from entering the cells. After cleaning, flush the outside of the battery and the surrounding areas with clean water. INLET 3. Identify the cable as positive (+) or negative (-) before making the battery connections. Always connect the negative (-) cable last, to reduce the risk of arcing. AIR CLEANER ELEMENT 4. Maintain the electrolyte level by adding distilled water. Fill each cell to the split-level marker in the battery. The water component of the electrolyte evaporates, but the sulfuric acid component remains. For this reason, add water, not electrolyte to the battery. AIR CLEANER BAND W/CUSHION VALVE 5. Use a battery hydrometer to check the specific gravity of the electrolyte in each battery cell (Figure 7-6). Charge the battery if the specific gravity measures less than 1.215. Do not overcharge the battery. Stop charging the battery when the electrolyte specific gravity reaches 1.260, at approximately 80° F (27° C). WING BOLT FIGURE 7-5. AIR CLEANER ASSEMBLY BATTERY CARE Service the battery at the intervals shown in the maintenance schedule. Check the electrolyte level more frequently during hot weather. Batteries present the hazard of explosion that can result in severe personal injury. Do not smoke or allow any fire, flame, spark, pilot light, arc-producing equipment or other ignition sources around the battery area. Do not disconnect battery cables while the generator set is cranking or running because explosive battery gases could be ignited. SPECIFIC GRAVITY READING SHOULD BE 1.260 AT 80° F (27° C) WARNING WARNING Battery electrolyte can cause severe eye damage and burns to the skin. Wear goggles, rubber gloves and a protective apron when working with batteries. FIGURE 7-6. BATTERY CHECK 7-9 Redistribution or publication of this document, by any means, is strictly prohibited. CRANKCASE BREATHER AC GENERATOR Clean the crankcase breather element at the scheduled intervals, using the following procedure (see Figure 7-7). Generator Brushes The generator should be inspected for brush wear and cleaning as required per the Periodic Maintenance Schedule. Perform this procedure according to the steps in Section 4 of this manual. 1. Remove the cap nuts and gaskets from the top of the cylinder head cover. Carefully remove the cover. Avoid damaging the gasket. 2. From inside the cover, remove two machine screws securing the breather element, plates and shield. Accidental starting of the generator set can cause severe personal injury or death. Stop the generator set and disable by disconnecting the starting battery cables (negative [-] cable first before inspecting the generator. WARNING 3. Clean the element in a suitable solvent. Dry the element, then saturate with engine oil before replacing. Generator Bearing WARNING Many cleaning solvents present a hazard of severe personal injury or death. Follow the manufacturer’s instructions and proceed with care. Inspect the bearing for evidence of outer case rotation every 1000 hours of use. The bearing should be replaced every five years, because the bearing grease gradually deteriorates due to oxidation. See Section 4 of this manual for information on the generator bearing. 4. If necessary, clean other breather components in solvent before reassembling. CAP NUT AND GASKET CYLINDER HEAD COVER FILLER CAP AND GASKET GASKET BREATHER PIPE JOINT BREATHER PIPE ELEMENT PLATE 2 BREATHER ELEMENT ELEMENT PLATE 1 OIL SHIELD FIGURE 7-7. CRANKCASE BREATHER 7-10 Redistribution or publication of this document, by any means, is strictly prohibited. CLEANING THE GENERATOR SET MUFFLER/SPARK ARRESTER Clean the generator set at least every six months. Dust usually can be removed with a damp cloth. Some road contaminants may require steam cleaning. Do not steam clean the generator set while the engine is running. When cleaning, protect the area so spray is not directed into the generator, air cleaner, control box, fuel solenoid, or electrical connections. Do not clean with solvents; they can damage electrical connectors. The exhaust spark arrester mounted inside the muffler is necessary for safe operation. It must be periodically cleaned out for maximum efficiency, and to meet Forest Service requirements (RV use). See the maintenance schedule for cleaning intervals. To clean the spark arrester, park the vehicle on a non-flammable, washable surface, and remove the 1/8 inch pipe plug from the bottom of the muffler. Run the generator set with a full load for five minutes. Stop the generator set and allow the muffler to cool. Replace the pipe plug in the muffler. See Figure 7-8. INITIAL STARTING AND CHECKS WARNING Exhaust gas presents the hazard of severe personal injury or death. Do not operate the generator set inside any room or building. If none of the fuel line junctions have been loosened between the electric fuel pump and the injection pump, the fuel system should not need priming. However, if priming is necessary, it should be done according to the following procedure. Priming the Fuel System CAUTION Priming the fuel system should only be done by a skilled and experienced diesel technician. Incorrect priming could lead to equipment damage or faulty operation. 1. Turn off both DC breakers on the set control box. PIPE PLUG EXS−1190s 2. Disconnect the B+ lead to the fuel pump. 3. Use a clip lead to jumper B+ to the fuel pump. Run the fuel pump for five to ten seconds until the air is purged from the low-pressure fuel system. FIGURE 7-8. EXHAUST MUFFLER 7-11 Redistribution or publication of this document, by any means, is strictly prohibited. Blank Page 7-12 Redistribution or publication of this document, by any means, is strictly prohibited. 8. Wiring Diagrams The electrical schematics and wiring diagrams that apply to the generator set covered in this manual are listed below. WIRING DIAGRAM DRAWING NO. PAGE DC Control Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612-6635 . . . . . . . . . . . . . . . . . . . 8-2 AC Control Assembly (single-phase) . . . . . . . . . . . . . . . . 612-6637 . . . . . . . . . . . . . . . . . . . 8-3 AC Control Assembly (three-phase) . . . . . . . . . . . . . . . . 612-6732 . . . . . . . . . . . . . . . . . . . 8-4 8-1 Redistribution or publication of this document, by any means, is strictly prohibited. 612-6635 Redistribution or publication of this document, by any means, is strictly prohibited. 8-2 P4 J4 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 ( Q1 ) 3 3 ( Q5 0 OR Q6 0 ) 2 2 1 1 L1 L2 REF DES SEE NOTE 1 ( 2) 1 2 3 G1 VR1 L0 T1 VR1 F1 Q6 0 Q1 A1 S1 Q5 0 DWG QTY SIZE ------ ----------- DESCRIPTION WI RE HARNESS LEAD ( F1) LEAD ( F2) GENERATOR VOLTAGE REG- CAP AVR 1 1 1 1 1 AC A1 1 2 T2 S2 F2 PART N0 AC NOTE: T3 1. FROM J2-15 FOR FIELD FLASHING. SEE NOTE 2 T4 2. QUADRATURE POWER CONNECTION Q60-60 HZ, Q50-50 HZ UNITS. MAIN ARMATURE STATOR FIELD SCHEMATIC 3. AVR REFERENCE VOLTAGE. G1 7 6 8 5 9 4 10 3 11 2 VOL TAGE 1 1 0 / 2 2 0 V, 1 1 5 / 2 3 0 V & 1 2 0 / 2 4 0 V AS SHOWN SEE RECONNECTI ON CHART FOR OTHER VOL TAGES A B C 100 120 200 240 100/ 200 120/ 240 60 J 110 115 220 230 110/ 220 115/ 230 50 P L1 L1 HZ CODE L1 S1 S1 S1 Q1 12 T3 1 VR1 SCHEMATI C P4/J4 SEE NOTE 3 L1 2 T1 L2 T4 T2 G1 T2 Q1 Q50 Q60 2 T1 T2 T1 Q50 Q60 2 T2 Q50 Q60 2 S2 L0 T3 T4 T4 S2 L0(N) L0 L1 L2 L2 L0 L 1 L 0 ( N) L 2 T1 T2 T3 T4 T1 T2 T3 T4 DI AGRAM L1 S2 T3 L0 1 Q 0 Q5 T3 L0 S1 S2 F1 F2 Q6 0 T4 T1 Q1 GND SEE NOTE 2 A1 T1 T3 T2 T4 WIRING DIAGRAM GND 1 1 0 / 2 2 0 V, 1 1 5 / 23 0 V & 1 2 0 / 2 4 0V AS SHOWN SEE RECONNECTI ON CHART FOR OTHER VOL TAGES GENERATOR RECONNECTION CHART 612-6637 8-3 Redistribution or publication of this document, by any means, is strictly prohibited. 612-6732 Redistribution or publication of this document, by any means, is strictly prohibited. 8-4 Cummins Power Generation 1400 73rd Avenue N.E. Minneapolis, MN 55432 763-574-5000 Fax: 763-528-7229 Cummins and Onan are registered trademarks of Cummins Inc. Redistribution or publication of this document, by any means, is strictly prohibited.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 2003:03:04 11:35:09Z Modify Date : 2005:04:04 12:21:18-05:00 Page Count : 67 Page Mode : UseOutlines Creation Date : 2003:03:04 11:35:09Z Producer : Acrobat Distiller Command 3.01 for Solaris 2.3 and later (SPARC) Author : ak911 Mod Date : 2005:04:04 12:21:18-05:00 Metadata Date : 2005:04:04 12:21:18-05:00 Creator : ak911 Title : 981-0516 Has XFA : NoEXIF Metadata provided by EXIF.tools