How to Mount MasterSwitch VM in a NetShelter Enclosure
1. Attach the brackets to the rear of the strip, using 4 screws (provided) for each bracket. Choose the bracket
and position that best suits your needs.

2. Choose a suitable
location for the
strip. The figure at
right shows the
strip mounted in
four different
locations in the
enclosure. To
avoid interfering
with shelves or
equipment, install
the strip so that it
hangs on the
outside edge of the
vertical rail.

Note: The bracket in ! (at left) is for two-post racks.
Using this bracket may require you to drill holes
in the rack.

3. Insert a caged nut (provided with the enclosure)
above and below a notched hole on a vertical
mounting rail at the highest point in your chosen
location.

4. Align the mounting holes on the top bracket with the
caged nuts you installed in Step 3, and insert two
mounting screws (provided with the enclosure) to
secure the top bracket.

5. Repeat Step 4 for the bottom bracket to secure the
strip to the enclosure.

990-6066A

08-01

How to Set Up MasterSwitch VM
Setting up a single strip

You must perform Step 2 last!

1. Plug the strip into a protected power source
and use the appropriate cable to connect to the
network port on the controller.

Setting up multiple strips (cascading)

Caution:

APC does not recommend plugging
the strip directly into any unprotected power source, such as a wall
outlet.

2. Connect the To PDU port on the controller to the In
port on the strip, using one of the provided gray
communication cables.

You must perform Step 3 last!

1. Plug each strip into a protected power source and
2. Connect the strips using the 10-foot gray commuuse the appropriate cable to connect to the network
nication cable (607-0035A): strip 4 In to strip 3 Out;
port on the controller.
strip 3 In to strip 2 Out; strip 2 In to strip 1 Out.

3. Connect the RJ-11 port labeled To PDU on the
controller to the RJ-11 port labeled In on strip 1, using
one of the provided gray communication cables.

Note: You can also
connect AP9222
strips to
AP9221EXPX166

units in a cascade
configuration.

How to set up PDUs for dual power cord devices
Use the following procedure when cascading
strips that are connected to devices (servers)
with dual power cords.
1. Follow the procedure for setting up multiple
strips. (Attach dual cords to separate strips for
redundancy.)
2. Use the MasterSwitch VM network interface to
configure the redundant strips on the same
synchronized set. Failure to configure synchronized sets will not guarantee “power off”
to both strips at the same time.

Note: See the MasterSwitch VM User’s Guide on
the provided CD or on the Web site for
more information on configuring synchronized sets.

990-6066A

08-01



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Create Date                     : 2001:08:03 08:23:48
Producer                        : Acrobat Distiller 4.05 for Windows
Author                          : bfrankli
Creator                         : PageMaker 6.0
Title                           : Web Addendum.pm6
Modify Date                     : 2001:08:03 08:25:58-05:00
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu