DB98_20429A_1 AS09HPBN AS 09 12 HPBN Service Manual

User Manual: AS09HPBN

Open the PDF directly: View PDF PDF.
Page Count: 54

DownloadDB98_20429A_1 AS09HPBN AS 09 12 HPBN Service Manual
Open PDF In BrowserView PDF
DB98_20429A(1)_CO

12/24/04 10:54 AM

Page 3

ROOM AIR CONDITIONER
INDOOR UNIT

OUTDOOR UNIT

AS09HPBN
AS12HPBN

AS09HPBX
AS12HPBX

SERVICE
AIR CONDITIONER

Manual
CONTENTS
1. Product Specifications
2. Operating Instructions & Installation
3. Disassembly and Reassembly
4. Refrigerating Cycle Diagram
5. Set Up the Model Option
6. Troubleshooting
7. Exploded Views and Parts List
8. Block Diagram
9. Wiring Diagram

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 1

1. Product Specifications
1-1 Table
Model
Item

AS09HPBN
Indoor unit

Type

Outdoor unit

Indoor unit

Outdoor unit

Wall-mounted

Wall-mounted

kW

2.70

3.50

Heating

kW

2.90

3.80

Dehumidifying

|/h

1.0

1.4

Cooling

Cooling

Air Volume

Heating

Performance

Cooling

Noise

Heating

Energy Efficiency Ratio

Cooling
Heating

Power

m /min
(H/M/L)

7.5/6.9/6.3

25

8.3/7.0/5.7

8.0/7.4/6.8

25

9.5/8.9/8.3

25

dB
(H/M/L)

40/36/32

51/51

43/38/34

53/53

51/51

43/38/34

3

Operating Current

Cooling
Cooling

Starting Current
Length

840

1,090

850

1,180

3.9

5.0

Outer Dimension

Width x Height
x Depth

Weight(Net)
Refrigerant Pipe

95.0
28

m

2.1

2.1

5G

5G

A

250V-10A

250V-10A

mm

950 x 268 x 165

790 x 548 x 285

950 x 268 x 165

790 x 548 x 285

inch

37.4 x 10.6 x 6.5

31.1 x 21.6 x 11.2

37.4 x 10.6 x 6.5

31.1 x 21.6 x 11.2

kg

9.0

33.8

9.0

36.0

mm x L(m)

ø6.35 x 7.5

ø6.35 x 7.5

Gas

mm x L(m)

ø9.52 x 7.5

ø9.52 x 7.5

D x L(mm)

ø18 x 550

ø18 x 550

Rotary, G4A091JU

Rotary, G8C124JU

Type

Induction Motor(PSC)

Induction Motor(PSC)

Rated Output
Oil Type
Type
Motor

99.9
21

Type

Blower

5.4
94.8

Liquid

Drain Hose
Motor

3.7
93.6

A
Number of Core Wire
Capacity

Compressor

3.22
1-220/240-50

%

Heating

Power Cord

3.41

A

Heating

53/53
3.21

1-220/240-50

W

Heating

25

3.21

W/W

Cooling

Power Factor

Size

40/36/32

ph-V-Hz

Power Consumption

Power

AS12HPBN

Type
Rated Output

W

Heat Exchanger
Refrigerant Control Unit

930

1,267

DAPHNE FV68S(PVE)

DAPHNE FV68S(PVE)

Cross-flow

Propeller

Cross-flow

Propeller

Resin / steel

steel

Resin / steel

steel

15

50

15

50

2ROW 12STEP

1ROW 24STEP

2ROW 12STEP

2ROW 24STEP

CAPILLARY TUBE

CAPILLARY TUBE

Freezer Oil Capacity

cc

280

500

Refrigerant to Change(R410A)

g

730

950

Protection Device(OLP)

RBC12054-12500

Cooling Test Condition

INDOOR UNIT : DB27˚C WB19˚C

OUTDOOR UNIT : DB35˚C WB24˚C

Maximum Operation Condition

INDOOR UNIT : DB32˚C WB23˚C

OUTDOOR UNIT : DB43˚C WB26˚C

Samsung Electronics

RBC12128-12500

1

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 2

2. Operating Instructions & Installation
2-1 View of the Unit
2-1-1 Indoor Unit

Air Inlet
Room Temperature sensor

Power(On/Off) button

Air filter
(under the grille)

Airflow blades
(outlet)

Set temperature &
room temperature
Operation indicator
(Auto-Cool, Cool, Dry, Fan : Blue
Auto-Heat, Heat : Orange)

Auto cleaning indicator
(Blue)

Turbo function indicator
(Blue)

Energy saving indicator
(Blue)

Timer indicator
(Orange)

Anion indicator
(Blue)

Fan speed indicator
(Blue)

Remote control sensor

2

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 3

Operating Instructions & Installation

2-1-2 Outdoor Unit

Air Inlet(Rear)

Air Outlet

Connection Valve
(inside)

Samsung Electronics

3

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 4

2-2 Air Conditioner and Accessories
The following accessories are supplied with the air conditioner.
- The number of each accessory is indicated in parentheses.

2-2-1 Accessories in the Indoor Unit Case
Installation Plate (1)

Remote Control (1)

Batteries for
Remote Control (2)

User’s Manual (1)
TIONS
OWNER’S INSTRUC
INSTRUCCIONES
MANUAL DE
PER L’USO
ISTRUZIONIINSTRU
˝ES
MANUAL DE
TION
MANUEL D’UTILISAISUNG
GEBRAUCHSANWE
Air Conditioner
Splut-type Room stico sistema Split
dom
ad unit Separate
Aire acondicionado
d’aria per ambienti
Condizionatorede ar condicionado tipo Split
Aparelho
type s par
Climatiseur de
Geteilte raumklimaanlage

Installation Manual (1)
TIONS
OWNER’S INSTRUC
INSTRUCCIONES
MANUAL DE
PER L’USO
ISTRUZIONIINSTRU
˝ES
MANUAL DE
TION
MANUEL D’UTILISAISUNG
GEBRAUCHSANWE
Air Conditioner
Splut-type Room stico sistema Split
dom
ad unit Separate
Aire acondicionado
d’aria per ambienti
Condizionatorede ar condicionado tipo Split
Aparelho
type s par
Climatiseur de
Geteilte raumklimaanlage

2-2-2 Accessories in the Outdoor Unit Case
5-wire
Assembly Cable (1)

Drain Plug (1)

Rubber Leg (4)

- The flare nuts are attached to the end of each pipe of an evaporator or a service port.
Use the nuts when connecting the pipes.
- The 5-wire assembly cable is optional. If it is not supplied, use the standard cable.
- The drain plug and rubber leg are only included when the air conditioner is supplied without the assembly pipe as seen in the
picture below.
The following connection accessories are optional.
If they are not supplied, you should prepare them before installing the air conditioner.
Assembly Pipe, ø6.35mm Assembly Pipe, ø9.52mm
by 7.5m (1)
by 7.5m (1)

Pipe Clamps A (3)

Pipe Clamps B (3)

PE T3 Foam Tube
Insulation (1)

Vinyl Tape,
Width 50mm (1)

Drain Plug (1)

Rubber Leg (4)

Cement Nail (6)

M4 x 16 Tapping
Screws (10)

Drain Hose,
length 2m (1)

Putty 100g (1)

- If these accessories are supplied, you can find them in the accessory box.

4

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 5

2-3 Installation
2-3-1 Before Installation
Keep the air conditioner outlet and inlet free from its surroundings.
In case of installation, keep the symmetry and fix it to prevent vibration.
The pipe length shall meet the standard as far as possible.

2-3-2 Installation Procedure
■ Location
Install the product in an area to guarantee the best cooling effect, convenience of piping and electric work, and inexistence of
vibration or wind.

■ Wall Drilling
Drill the wall downward in a diameter of 60 to 65mm.

■ Fixing Indoor Unit & Outdoor Unit
Fix the air conditioner indoor unit securely to the wall. Secure the outdoor unit in a suitable position.

■ Pipe Spooling & Connecting
You shall cut the pipe with a pipe cutter and grind all the burrs of the cut surface.
Pipe expansion may continue until the pipe surface becomes uneven or torn apart.
Be sure to use a torque wrench to tighten pipes or flare nuts.

D

Outer Diameter(D)

Torque(kgf.cm)

Depth(A)

6.35mm(1/4")

140~170

1.3mm

9.52mm(3/8")

250~280

1.8mm

A

■ Leak Test
Put an inert gas like nitrogen in the outdoor unit pipe and put soap bubbles or other test liquids on the pipe surface for the leak test.

■ Drain Hose Connecting
Install the drain hose downward to drain water naturally. Be sure to pour water into the hose to check if it drains well.

■ Electric & Earth Work
Electric and earth work shall meet the "Electric Facility Technology Standard" and the "Internal Wire Regulation" of the Electric
Business Laws.

■ Inspection & Trial Run
Upon completion of the tests, you shall make a trial run while you explain the main functions of the air conditioner to finish the
installation.

Samsung Electronics

5

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 6

2-4 Installation Diagram of Indoor Unit and Outdoor Unit
2-4-1 Air-Purge Procedure
1) Connect each assembly pipe to the appropriate
valve on the outdoor unit and tighten the flare nut.

Indoor unit

Outdoor unit

A

Gas pipe side

C

B

Liquid pipe side

D

2) Connect the charging hose of low pressure side
of manifold gauge to the packed valve having a
service port (3/8" Packed valve) as shown at the
figure.

3) Open the valve of the low pressure side of
manifold gauge counter-clockwise.

4) Purge the air from the system using vacuum
pump for about 30 minutes.
- After that, please recheck that pressure is
stabilized.
- Close the valve of the low pressure side of
manifold gauge clockwise.
- Remove the hose of the low pressure side
of manifold gauge.

5) Set valve cork of both liquid side and gas side of
packed valve to the open position.
Vacuum Pump

6) Mount the valve stem nuts to the 2-Way and
3-Way valve. And mount the service port cap to
3-Way valve.

Valve stem

Stem cap

7) Check for gas leakage.
- At this time, especially check for gas
leakage from the 3-Way valve’s stem nuts,
and from the service port cap.

A
(gas)

B
(liquid)

6

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 7

Operating Instructions & Installation

2-4-2 Refrigerant Refill(R410A)
Refill an air conditioner with refrigerant when refrigerant has been leaked at installing or using.

1) Purge air(for new installation only).

2) Turn the 3-Way valve clockwise to close,
connect the pressure gauge (low pressure side) to
the service valve, and open the 3-Way valve
again.

Suspension hook

Compound
gauge

High
pressure
gauge
Hand
wheel

3) Connect the tank to refill with refrigerant.

4) Set the unit to cool operation mode.

Finger tight
fittings
For mounting
other and of
hose when
not in use

Connected to
high pressure
side
Charging line

5) Check the pressure indicated by the pressure
gauge(low pressure side).
* Standard pressure is should be 9.0~10.0kg/cm2
in a regular, high operation mode.

6) Open the refrigerant tank and fill with refrigerant
until the rated pressure is reached.
* It is recommended not to pour the refrigerant
in too quickly, but gradually while operating a
pressure valve.

7) Stop operation of the air conditioner.

8) Close the 3-Way valve, disconnect the
pressure gauge, and open the 3-Way valve
again.

9) Close the cap of each valve.

Samsung Electronics

7

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 8

Operating Instructions & Installation

2-4-3 "Pump down" Procedure
Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area.

1) Remove the caps from the 3-Way valve and the
3-Way valve.

2) Turn the 3-Way valve clockwise to close and
connect a pressure gauge (low pressure side)
to the service valve, and open the 3-Way valve
again.

3-Way Valve

2-Way Valve

3) Set the unit to cool operation mode.
(Check if the compressor is operating.)

4) Turn the 3-Way valve clockwise to close.

5) When the pressure gauge indicates "0" turn the
3-Way valve clockwise to close.

6) Stop operation of the air conditioner.

7) Close the cap of each valve.

Relocation of the air conditioner
• Refer to this procedure when the unit is relocated.
• Carry out the pump down procedure (refer to the details of 'pump down').
• Remove the power cord.
• Disconnect the assembly cable from the indoor and outdoor units.
• Remove the flare nut connecting the indoor unit and the pipe.
• At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
• Disconnect the pipe connected to the outdoor unit.
At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
• Make sure you do not bend the connection pipes in the middle and store together with the cables.
• Move the indoor and outdoor units to a new location.
• Remove the mounting plate for the indoor unit and move it to a new location.

8

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 9

3. Disassembly and Reassembly
Stop operation of the air conditioner and remove the power cord before repairing the unit.

3-1 Indoor Unit
No

Parts

1

Panel Front

Procedure

Remark

1) Stop the air conditioner operation and
shut off the main power.

2) Detach the Front Grille after pushing out it.

3) Loosen 1 of the right screw and detach
the Ass'y display.

4) Loosen 1 of the right screw and detach the
Terminal Cover.
5) Detach the cover PCB-DVM and thermistor
from the Panel Front.

Samsung Electronics

9

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 10

Disassembly and Reassembly

No

Parts

Procedure

Remark

6) Loosen 5 fixing screws of Panel Front.

7) Unlock 2 hooks to fix Panel Front and
Tray Drain.
8) Unlock 2 hooks to fix Panel Front and
Back Body.

10

2

Tray Drain

3

Heat Exchanger

1) Detach the connected wire of Stepping
Motor.
2) Pull Tray Drain out from the Back Body.

1) Loosen 1 fixing earth screw of right side.

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 11

Disassembly and Reassembly

No

Parts

Procedure

Remark

2) Detach the Room Sensor.

3) Detach the Holder Pipe at the rear side
of the unit.

4) Loosen 3 fixing screws of left Holder Evap.

5) Loosen 1 fixing screw of right Holder
Motor.

6) Detach the Heat Exchanger from the
indoor unit.

Samsung Electronics

11

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 12

Disassembly and Reassembly

No

Parts

4

Electrical Parts
(Main PCB)

5

Fan Motor
&
Cross Fan

12

Procedure

Remark

1) Loosen 4 fixing screws of right Holder
control.
2) Take all the connector of PCB upper side
out.(Including Power Cord)
3) Detach the outdoor unit connection wire
from the Terminal Block.
4) Pull the PCB up to detach.

1) Loosen 2 fixing screws and detach the
Motor Holder.
2) Loosen 1 fixing screw of Fan Motor.
3) Detach the Fan Motor from the Fan.
4) Detach the Fan from the left Holder
Bearing.

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 13

3-2 Outdoor Unit
No

Parts

1

Common Work

Procedure

Remark

1) Loosen 1 fixing screw of the Cover-Side.

2) Loosen each 3 fixing screws on both right
and left Cabinet-Side edge and a fixing
screw on the Cabinet-Front lower to detach
the Cabinet-Front.

3) Loosen 6 fixing screws of the Cabinet-Side
RH.

4) Loosen 2 fixing screws of the Cabinet-Side
LF.

Samsung Electronics

13

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 14

Disassembly and Reassembly

No

Parts

2

Fan & Motor

3

Heat Exchanger

4

Compressor

14

Procedure

Remark

1) Detach the Nut Flange.(Turn counterclockwise because the screw is right-handed)
2) Detach the Fan.
3) Loosen 4 fixing screws to detach
the Motor.

1) Loosen 2 fixing screws on both sides.
2) Disassemble the pipe in both inlet and
outlet with welding torch.
3) Detach the Heat Exchanger.

1) Loosen the Terminal Cover nut to open the
Terminal Cover.
2) Disassemble the cloth sound felt.
3) Disassemble the pipe in both inlet and
outlet of the Compressor with welding
torch.
4) Disassemble the pipe in both inlet and
outlet of the Condenser with welding torch.
5) Loosen the 3 bolts at the bottom.
6) Detach the Compressor.

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 15

4. Refrigerating Cycle Diagram
4-1 Refrigerating Cycle Diagram

Outdoor Unit

Indoor Unit

✳Note
Capillary tube
T1

2-Way valve

Check valve

Liquid side

Heat
Exchanger
(Condenser)

Cross fan

Heat
Exchanger
(Evaporator)

Propeller fan

Capillary tube

T2
Gas side
3-Way valve

4-Way valve

Cooling
Compressor

Heating
Gas Leak Check Polnt

Samsung Electronics

15

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 16

4-2 Refrigerant Cycle Characteristic
4-2-1 Capacity Distributions
Capacity Distributions according to indoor and outdoor temperature variation.

■ COOLING MODE
- Indoor Temp. Variation : 21.0˚C ~ 32.4˚C
- Outdoor Temp. Variation : 25.0˚C ~ 45.0˚C

■ AS09HPBN
Cooling Capacity Distribution
Indoor Temp.( C)

Cooling Capacity(kW)

4.0

3.0
DB32.4 / WB24.0
DB30.6 / WB22.5
DB27.0 / WB19.0
2.0

DB24.0 / WB17.0
DB21.0 / WB15.0

1.0
25.0

35.0

45.0

Outdoor Temp.(DB C)

■ AS12HPBN
Cooling Capacity Distribution
6.0

Indoor Temp.( C)

Cooling Capacity(kW)

5.0
4.0

DB32.4/WB24.0
DB30.6/WB22.5
DB27.0/WB19.0
DB24.0/WB17.0
DB21.0/WB15.0

3.0
2.0
1.0
0.0
25

35

45

Outdoor Temp.(DB C)

16

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 17

Refrigerating Cycle Diagram

■ HEATING MODE
- Indoor Temp. Variation : 15.0˚C ~ 25.0˚C
- Outdoor Temp. Variation : 1.0˚C ~ 20.0˚C

■ AS09HPBN

Heating Capacity Distribution

Heating Capacity(kW)

4.00

Indoor Temp.( C)
DB15.0
DB20.0
DB25.0

3.00

2.00

1.00
1.0/0.0

7.0/6.0

20.0/15.0

Outdoor Temp.(DB/WB C)

■ AS12HPBN

Heating Capacity

Heating Capacity Distribution
6.00

Indoor Temp.( C)

5.00

DB15.0
DB20.0
DB25.0

4.00
3.00
2.00
1.00
0.00
1.0/0.0

7.0/6.0

20.0/15.0

Outdoor Temp.(DB/WB C)

Samsung Electronics

17

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 18

Refrigerating Cycle Diagram

4-2-2 Power Consumption Distributions
Power Consumption Distributions according to indoor and outdoor temperature variation.

■ COOLING MODE
- Indoor Temp. Variation : 21.0˚C ~ 32.4˚C
- Outdoor Temp. Variation : 25.0˚C ~ 45.0˚C

■ AS09HPBN
Power consumption Distribution(Cooling mode)
Indoor Temp.( C)

1,100

DB32.4
DB30.6
DB27.0
DB24.0
DB21.5

Power consumption(W)

1,000

/
/
/
/
/

WB24.0
WB22.5
WB19.0
WB19.0
WB15.0

900
800
700
600
500

25

35

45

Outdoor Temp.(DB C)

■ AS12HPBN

Power consumption(W)

Power consumption Distribution(Cooling mode)
1,400

Indoor Temp.( C)

1,300

DB32.4
DB30.6
DB27.0
DB24.0
DB21.5

/
/
/
/
/

WB24.0
WB22.5
WB19.0
WB19.0
WB15.0

1,200
1,100
1,000
900
800
25

35

45

Outdoor Temp.(DB C)

18

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 19

Refrigerating Cycle Diagram

■ HEATING MODE
- Indoor Temp. Variation : 15.0˚C ~ 25.0˚C
- Outdoor Temp. Variation : 1.0˚C ~ 20.0˚C

■ AS09HPBN

Power consumption Distribution(Heating mode)
Indoor Temp.( C)

1,050

Power consumption(W)

DB25.0
950

DB20.0
DB15.0

850

750

650
1.0/0.0

7.0/6.0

20.0/15.0

Outdoor Temp.(DB/WB C)

■ AS12HPBN

Power consumption Distribution(Heating mode)
Indoor Temp.( C)
DB25.0

Power consumption(W)

1,500
1,400

DB20.0
1,300

DB15.0

1,200
1,100
1,000
900
25

35

45

Outdoor Temp.(DB/WB C)

Samsung Electronics

19

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 20

Refrigerating Cycle Diagram

4-2-3 Capacity and Power Consumption Distributions
Capacity and power Consumption distributions according to the length of connecting Pipe between indoor unit and outdoor unit.

■ COOLING MODE

■ AS09HPBN

Power consumption(Cooling)

Cooling Capacity
1,100

Power consumption(W)

Coooling Capacity(kW)

4

3

2

1
7.5

1,000
900
800
700
600
500

15.0

7.5

Length of Connecting Pipe(m)

15.0

Length of Connecting Pipe(m)

■ AS12HPBN

Power consumption(Cooling)

Cooling Capacity
1,300

Power consumption(W)

Cooling Capacity(kW)

3.70

3.50

3.30

3.10

1,100

1,000

900

2.90
7.5

15.0

Length of Connecting Pipe(m)

20

1,200

7.5

15.0

Length of Connecting Pipe(m)

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 21

Refrigerating Cycle Diagram

■ HEATING MODE

■ AS09HPBN

Power consumption(Heating)

Heating Capacity
1,050

Power consumption(W)

Heating Capacity(kW)

4.00

3.00

2.00

1.00
7.5

950

850

750

650
7.5

15.0

Length of Connecting Pipe(m)

15.0

Length of Connecting Pipe(m)

■ AS12HPBN

Power consumption(Heating)

Heating Capacity
1,350

Power consumption(W)

Heating Capacity(kW)

4.30

4.10

3.90

3.70

3.50
7.5

15.0

Length of Connecting Pipe(m)

Samsung Electronics

1,250

1,150

1,050

950
7.5

15.0

Length of Connecting Pipe(m)

21

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 22

Refrigerating Cycle Diagram

4-2-4 Low Pressure Distributions
■ COOLING MODE
- Indoor Temp. Variation : 21.0˚C ~ 32.4˚C
- Outdoor Temp. Variation : 25.0˚C ~ 45.0˚C

■ AS09HPBN

Low Pressure Distribution(Cooling mode)
Indoor Temp.( C)

Low pressure(kg/cm G)

12.0

DB32.4 / WB24.0
DB30.6 / WB22.5

10.0

DB27.0 / WB19.0
DB24.0 / WB17.0
DB21.0 / WB15.0

8.0

6.0

25

35

45

Outdoor Temp.(DB C)

■ AS12HPBN

Low Pressure Distribution(Cooling mode)
Indoor Temp.( C)

Low pressure(kg/cm G)

15.0

13.0

11.0

DB32.4
DB30.6
DB27.0
DB24.0
DB21.5

9.0

/
/
/
/
/

WB24.0
WB22.5
WB19.0
WB19.0
WB15.0

7.0

5.0

25

35

45

Outdoor Temp.(DB C)

22

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 23

Refrigerating Cycle Diagram

4-2-5 Air Volume according to the RPM variation(High/Mid/Low)
■ Indoor Unit

10
9.5
9
8.5
8
7.5
7
6.5
6
5.5
5
High

Mid

Low

12,000BTU-Cooling-Vol.

12,000BTU-Heating-Vol.

19,000BTU-Cooling-Vol.

19,000BTU-Heating-Vol.

RPM

■ Outdoor Unit
The air volume is 25m3/min regardless of model.

Samsung Electronics

23

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 24

Refrigerating Cycle Diagram

4-2-6 Noise Level according to the RPM variation(High/Mid/Low)
■ Indoor Unit

dB 41
39
37
35
33
31
29
27
High

Mid

Low

12,000BTU-Cooling-Noise

12,000BTU-Heating-Noise

19,000BTU-Cooling-Noise

19,000BTU-Heating-Noise

RPM

■ Outdoor Unit
Section
AS09HPBN

AS12HPBN

24

Operation

Noise(dB)

Cooling

51

Heating

51

Cooling

53

Heating

53

Remark

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 25

4-3 Cautions Of using R410A
■ HFCs
1. When installing or removing or servicing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle.
2. When evacuating an air conditioner, always use the vacuum pump to sufficiently evacuate an air conditioner.
3. You must use the specified lubricant(Polyol ester oil), valve and dryer.

■ Lubricants
1. Synthetic Oils : POE, PVE, PAG, AB
2. POE is made from Acid and Alcohol
3. Hydrolysis causes Metallic Soap

Samsung Electronics

25

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 26

5. Set Up the Model Option
5-1 Setting Option Setup Method

ex) Option No. :
Step 1 : Enter the Option Setup mode.
1st

Take out the batteries of remote control.

2nd

Press the temperature
insert the battery again.

3rd

Make sure the remocon display shown as

button simultaneously and

.

Step 2 : Enter the Option Setup mode and select your option according to the following procedure.

1
The default value is
Otherwise, push the

.
button to

.

Every time you push the button, the display panel reads

or

repeatedly.

2
3

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

2

3

1

Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

4

5

Push the

6

4
Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

5

Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

6
✳ Setting is not required if you must
a value which has a
default.

26

Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 27

Set Up the Model Option

7
Press

button, then the default value is

.

8
Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.
9

8

9

Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

7
10

10
11

Push the

12

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

11
Push the

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

12
Push the
✳ Setting is not required if you must
a value which has a
default.

button to set the display panel to

.

Every time you push the button, the display panel reads
...
repeatedly.

Step 3 : Upon completion of the selection, check you made right selections.
Press the Mode Selection key,
The display part shows
Press the Mode Selection key,
The display part shows

to set the display part to

and check the display part.

.
to set the display part to

and check the display part.

.

Step 4 : Pressing the ON/OFF button (
)
When pressing the operation ON/OFF key with the direction of remote control for unit, the sound ''Ding'' or ''Diriring'' is
heard and the OPERATION ICON(
) lamp of the display is flickering at the same time, then the input of option is completed. (If the diriring sound isn't heard, try again pressing the ON/OFF button.)
Step 5 : Unit operation test-run
First, Remove the battery from the remote control.
Second, Re-insert the battery into the remote control.
Third, Press ON/OFF key with the direction of remote control for set.
• Error Mode
1st If all lamps of indoor unit are flickering, plug out, plug in power plug again and press the ON/OFF key to retry.
2nd If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is
set up for its model.

Samsung Electronics

27

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 28

Set Up the Model Option

■ OPTION ITEMS
REMOCON
SEG1

SEG2

SEG3

SEG4

SEG5

SEG6

SEG7

SEG8

SEG9 SEG10 SEG11 SEG12

AS09HPBN

0

2

8

0

2

5

1

7

0

2

0

8

AS12HPBN

0

2

7

3

2

7

1

7

0

2

6

c

MODEL

28

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 29

6. Troubleshooting
6-1 Items to be checked first
1.

The input voltage should be rating voltage ±10% range.
The airconditioner may not operate properly if the voltage is out of this range.

2.

Is the link cable linking the indoor unit and the outdoor unit linked properly?
The indoor unit and the outdoor unit shall be linked by 5 cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the airconditioner may not operate properly.

3.

When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the malfunction of the
airconditioner.
No

Operation of air conditioner

Explanation

1

The OPERATION indication LED(BLUE) blinks when a
power plug of the indoor unit is plugged in for the first
time.

It indicates power is on. The LED stops blinking if the operation ON/OFF button on the remote control unit is pushed.

2

In a COOL operation mode, the compressor does not
operate at a room temperature higher than the setting
temperature that the INDOOR FAN should operate.
[In case of heat pump model]
In a HEAT operation mode, the compressor does not
operate at a room temperature lower than the setting
temperature that indoor fan should operate.

In happens after a delay of 3 minutes when the compressor
is reoperated. The same phenomenon occurs when a power
is on.
As a phenomenon that the compressor is reoperated after a
delay of 3 minutes, the indoor fan is adjusted automatically
with reference to a temperature of the air blew.

3

Fan speed setting is not allowed in DRY(

The speed of the indoor fan is set to LL in DRY mode.
Fan speed is selected automatically in AUTO mode.

4

Compressor stops operation intermittently in DRY(
mode.

5

Timer LED(YELLOW) of the indoor unit lights up and the
air conditioner does not operate.

Timer is being activated and the unit is in ready mode.
The unit operates normally if the timer operation is cancelled.

6

The compressor stops intermittently in a COOL mode or
DRY mode, and fan speed of the indoor unit decreases.

The compressor stops intermittently or the fan speed of the
indoor unit decreases to prevent inside/outside air frozen
depending on the inside/outside air temperature.

7

[In case of heat pump model]
Compressor of the outdoor unit is operating although it is
turned off in a HEAT mode.

When the unit is turned off while de-ice is activated,
the compressor continues operation for up to 9 minutes
(maximum) until the deice is completed.

8

[In case of heat pump model]
The compressor and indoor fan stop intermittently in
HEAT mode.

The compressor and indoor fan stop intermittently if room
temperature exceeds a setting temperature in order to protect
the compressor from overheated air in a HEAT mode.

9

[In case of heat pump model]
Indoor fan and outdoor fan stop operation intermittently
in a HEAT mode.

The compressor operates in a reverse cycle to remove
exterior ice in a HEAT mode, and indoor fan and outdoor fan
do not operate intermittently for within 20% of the total heater
operation

Samsung Electronics

) mode.

)

Compressor operation is controlled automatically in DRY
mode depending on the room temperature and humidity.

29

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 30

Troubleshooting

4.

Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details on the display panel.
Error Mode

LAMP

7-segment Display

Indoor unit room temperature sensor error (open or short)
Indoor unit heat exchanger temperature sensor error (open or short)
Indoor fan motor malfunction
EEPROM error
Option error (option wasn't set up or option data error)

5.

Operation with abnormal motion
No
1

2

30

Display Flickering

Abnormal condition
No response from
the remote control
operation signal.

Unable to operate the
outdoor unit

Inspection
• Plug out and plug in 5 seconds
later.

• Press the TURBO button with the
remote control.
• In 3 minutes, check the voltage
between the indoor unit terminal
block N(1) and 1.

Initial Diagnosis
Able to operate the
remote control.

OK

Unable to operate
the remote control.

Press the
(ON/OFF) button in the
indoor unit.
• If it operates, the remote control and
indoor unit receiver are in trouble.
• If not, the indoor unit is in trouble.

AC198V ~ AC242V

Problem with the outdoor unit or PCB

No power source
displayed.

Problem with the relay (RY71) or PCB

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 31

6-2 Fault Diagnosis by Symptom
6-2-1 No Power (completely dead)-Initial diagnosis
1. Checklist :
1) Is input voltage normal?
2) Is AC power linked correctly?
3) Is input voltage of DC regulator IC KA7805 (IC02) normal? (11VDC-12.5VDC)
4) Is output voltage of DC regulator IC KA7805 (IC02) normal? (4.5VDC-5.5VDC)
2. Troubleshooting procedure

Unplug the power cord and
plug it after 5 seconds

Press the Power Button on the
remote control unit to
operate the air conditioner

operate

◆ Check the display board

does not operate
◆ Check the indoor unit
control board

Check whether 2 wires
of power cord are
connected correctly to the
terminal block and control board.

No
Reconnect wires correctly

Yes
Check whether the fuse on the
control board is normal.
FUSE: 3.15[A]/250[V]

No

Replace fuse

Yes
Check the output of SMPS
on the control board.
Input power: AC230±15%[V]
IC02 Input: DC12[V]
IC02 output: DC5[V]

No

PCB should be replaced

Yes
◆ Check the setting temperature

Samsung Electronics

31

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 32

Troubleshooting

6-2-2 Room temperature sensor failure
Error Mode

LAMP

7-segment Display

Indoor unit room temperature sensor error(open or short)

Detach the assembly sensor from the
ASS'Y PCB CN43 connector and measure
the sensor resistance with an ohmmeter (tester).

Is the sensor resistance value
10KΩ ±3% at the room temperature
of 25˚C?

No

ASS'Y Sensor Replace
SENSOR Resistance Value : 20˚C-12.09kΩ
SENSOR Resistance Value : 30˚C-8.31kΩ
SENSOR Resistance Value : 35˚C-6.94kΩ
SENSOR Resistance Value : 40˚C-5.83kΩ

Yes

Connect the sensor to CN43,
supply power, and measure the voltage of
#1 and #2 of the CN43 connector.

Below 0.5V?

Yes

Poor ASS'Y PCB Replace

No
Yes
Over 4.9V?

Poor ASS'Y PCB Replace

No

MICOM Error or Connector(CN43) check

32

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 33

Troubleshooting

6-2-3 Room Pipe sensor failure
Error Mode

LAMP

7-segment Display

Indoor unit heat exchanger temperature sensor error(open or short)

1. Check the assembly condition of the sensor connector(CN43) on the indoor unit Main PCB and if not assembled, reassemble the
connector accurately.
2. Detach the room pipe sensor connector(CN43) and check the resistance between connector 3 and 4.
Temperature(˚C)

Resistance Value(Kohm)

Temperature(˚C)

Resistance Value(Kohm)

15

14.68

30

8.31

20

12.09

35

6.94

25

10

40

5.83

Others
The data tolerance
is ±3%.

If the above data is not met, replace the room pipe sensor.
3. Assemble the room pipe sensor to PCB, plug in, and check the voltage of connector 3 and 4. If the resistance is below 0.5V or
over 4.9V, replace the indoor Main PCB. (short or disconnected in the PCB board)

Samsung Electronics

33

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 34

Troubleshooting

6-2-4 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
Error Mode

LAMP

7-segment Display

Indoor unit heat exchanger temperature sensor error(open or short)

1. Checklist :
1) Is the indoor unit fan motor properly connected with the connector (CN72)?
2) Is the AC voltage correct?
3) Is HALL IC in indoor fan motor properly connected with the connector (CN44)?
4) Is the running capacitor (CR71) properly connected with PCB board?
2. Troubleshooting procedure

After unplugging out the power cord should
be reconnected within 5 seconds.
Yes
No

Check as in the procedure "No power".

Does the OPERATION lamp blink?
Yes
No
Does the Solid State Relay(SS71) work properly?
Test rod location
+

-

SS71-

SS71-

Micom is
out of order.

Micom should be replaced

Normal
Voltage

12V

Yes
No
Is the supply voltage of the fan motor sufficient?
Test rod location
PCB CN72

Condition

pin #3 and #5

Fan operating

PCB is
out of order.

PCB should be replaced.

Normal
voltage

About AC180V
Motor Fan-Capacitor is out of order

Replace Motor
Fan-Capacitor

Yes

Fan motor is out of order.

34

Fan motor should be replaced.

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 35

Troubleshooting

6-2-5 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1. Checklist :
1) Is input voltage normal?
2) Is the set temperature of the remote control higher than room temperature in COOL mode?
3) Is the set temperature of the remote control lower than room temperature in HEAT mode?
4) Is the POWER IN connector (CN71) linked correctly?
5) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(N(1), 1, 2, 3)?
2. Troubleshooting procedure

After unplugging out the power cord should be
reconnected within 5 seconds.

No

Does the OPERATION lamp blink?

Check as in the procedure "No Power".

Yes
Yes

Does the timer lamp blink during operation?

Room temperature sensor is
out of order

!

No
#

+

-

Condition

Normal
Voltage

IC4 Pin No.38

GND

RY71 ON

DC4.8V

Micom is
out of order.

No

Is the power relay RY71 operated by adjusting the
room temperature?
Test rod location

Sensor Should be
replaced

@

PCB should be
checked.

No
Power relay is
out of order

Is rating voltage ±10% range applied relay between
Terminal block No. N(1) and No. 1
Yes

Power relay should be
replaced.

Outdoor unit is
out of order.
!
Yes

No
@

Is the room sensor normal resistor?
10°C

20°C

30°C

17.96kΩ

12.09kΩ

8.3kΩ

Yes
#

Samsung Electronics

35

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 36

Troubleshooting

6-2-6 When the Up/Down Louver Motor Does Not Operate. (Initial Diagnosis)
1. Checklist :
1) Is input voltage normal?
2) Is the Up/Down louver motor properly connected with the connector (CN61)?
2. Troubleshooting procedure
Remove power cord and plug in again in approx. 5 seconds.

No

Is STD lamp blinking?

Check as in the procedure
"No Power".

Yes
Yes

Does operation start when swing button of the
remote control unit pushed?

Normal

No
Voltage at pin #57~#60 of micom (IC04) change?(Squarewave)

No
Micom (IC04) is faulty.

Yes
No

Voltage at pin #2 ~ #3 of CN61(motor connector)
change?(Squarewave)

Driver IC05/06 (ULN2003A) is faulty.

Yes
Up/Down louver motor is faulty.

6-2-7 In the HEAT mode, When there is no warm air current. Check this first;
1. Is the set temperature of Remote Control lower than room temperature in Heat mode?
2. Is the Indoor PCB properly connected with the CN71 connector?
After training on, the heating operation
should start in 5 minutes.

Yes
Normal

No
Is the number #38 of Micom (IC04) DC5.0V?

No

Abnormal Micom

Yes
Is the number checking #11 of IC05 (ULN2003A) LOW?

No

Abnormal IC05

Yes
Is the voltage between CN71 #1 and CN71 #5 rating voltage ±10% range

No

Abnormal RY73

Yes
Abnormal 4-Way valve of Outdoor Unit.
or connecting Cable

PCB should be replaced.

4-Way valve should be replaced
or connecting Cable Check.

36

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 37

Troubleshooting

6-2-8 When the remote control is not receiving
1. Check if the connector was normally assembled.
2. Put the set in operation and check the voltage of No. 15(+) and No. 16(-) of the main PCB CN91 while operating the
remote control. When the voltage descends below 3V, the assembly module PCB is normal and the main PCB is poor.
Then replace the main PCB.
3. Replace the assembly display PCB because the module PCB is poor if the voltage between No. 15~16 of CN91
maintains 5V after the remote control starts operation.

Samsung Electronics

37

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 38

6-3 PCB Inspection Method
6-3-1 Pre-inspection Notices
1. Check if you pulled out the AC power plug when you eliminate the PCB or front panel.
2. Don't hold the PCB side not impose excessive force on it to eliminate the PCB.
3. Don't pull the lead wire but hold the whole housing to connect or disconnect a connector to the PCB.

6-3-2 Inspection Procedure
1. Check connector connection and peeling of PCB or bronze coating pattern when you think the PCB is broken.
2. The PCB is composed of the 3 parts.
1. ● Main PCB Part : MICOM and surrounding circuit, relay, room fan motor driving circuit and control circuit,
sensor driving circuit, power circuit of DC12V and DC5V, and buzzer driving circuit.
1. ● Display part : LED lamp
1. ● Switch part : Switch

6-3-3 Detailed Inspection Procedure
No

Procedure

1

Plug out and pull the PCB
out of the electronic box.
Check the PCB fuse.

1) Is the fuse disconnected? (F701)

2

Supply power.
If the operating lamp
twinkles at this time,
the above 1)~3) have
no relation.

Checking the power voltage.

3

4

38

Press the ON/OFF button
and operate TURBO
mode.
But, exclude the
RESERVE operation.

Inspection Method

Cause
• Overcurrent
• Indoor Fan Motor Short
• AC Part Pattern Short of the MAIN PCB

1) Is the DB71input voltage AC200V~AC240V?

• Power Cord is fault, Fuse open. Wrong
Power Cable Wiring, AC Part is faulty.

2) Is the voltage between both terminals of the
C103 on the 2nd side of the transformer DC12V
±0.5V?

• Switching Trans or Power Circuit is faulty

3) Is the voltage between both terminals of OUT
and GND of IC02(KA78L05) DC5V ±0.5V?

• Power Circuit is faulty, Load Short

Checking the power voltage.
1) Check the voltage of the relay(RY71) coil(IC05 PIN
#11 and GND : 0V, PIN#6 and GND : 5V) during
operation(3 minutes after TURBO operation).

• Relay(RY71) Coil Disconnection, IC05 is
faulty

2) Check the voltage of both terminals of
terminal block 1 and N(1) after 3 minute
operation.: AC220V

• Relay(RY71) Contact is faulty

Press the ON/OFF button. 1) Is the voltage over AC180V being imposed
on terminal #3 and #5 of the fan motor
1. FAN Speed [High]
connector(CN72)?
2. Continuous Operation

• Fan Motor of the indoor is faulty

2) The fan motor of the indoor unit doesn't run.

• Fan Motor Connector(CN72) is faulty

3) The power voltage between terminal #3 and #5
of the connector(CN72) is 0V.

• ASS'Y Main PCB is faulty
• Connection is faulty

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 39

Troubleshooting

6-3-4 Temperature Sensor Feature Conversion Table(Room Temperature Sensor); 103AT
Temperature Sensor Resistance Temperature Sensor Resistance Temperature Sensor Resistance Temperature Sensor Resistance
[˚C]
[˚C]
[˚C]
[˚C]
[Kohm]
[Kohm]
[Kohm]
[Kohm]
70
69
68
67
66
65
64
63
62
61
60

2.229
2.296
2.365
2.437
2.512
2.589
2.669
2.752
2.838
2.928
3.021

49
48
47
46
45
44
43
42
41
40

4.300
4.444
4.594
4.749
4.912
5.080
5.256
5.439
5.630
5.828

29
28
27
26
25
24
23
22
21
20

8.622
8.944
9.281
9.632
10
10.380
10.780
11.200
11.630
12.090

9
8
7
6
5
4
3
2
1
0

18.700
19.480
20.290
21.150
22.050
22.990
23.900
25.030
26.130
27.280

59
58
57
56
55
54
53
52
51
50

3.116
3.216
3.319
3.426
3.537
3.652
3.772
3.897
4.026
4.161

39
38
37
36
35
34
33
32
31
30

6.033
6.246
6.468
6.699
6.941
7.192
7.455
7.729
8.015
8.313

19
18
17
16
15
14
13
12
11
10

12.560
13.060
13.570
14.120
14.680
15.280
15.900
16.550
17.240
17.960

-1
-2
-3
-4
-5
-6
-7
-8
-9

28.470
29.720
31.040
32.430
33.890
35.430
37.050
38.760
40.560

Temperature Sensor Characteristic Curve
Temperature
(˚C)
70
60
50
40
30

At the temperature of 25˚C(10KΩ)
20
10
0
-10
-9
5

10

15

20

25

30

35

40

Resistance Value (Kohm)

Samsung Electronics

39

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 40

6-4 Main Part Inspection Method
Part
Room Temperature Sensor

Room Fan Motor

Breakdown Inspection Method
Measure resistance with a tester
Normal

At the normal temperature 37kΩ~ 8.3kΩ(-7˚C~+30˚C) *Refer to Table 6-3-4.

Abnormal

∞, 0Ω . . . Open or Short

Measure the resistance between terminals of the connector (CN72) with a tester.
Normal

Abnormal
Outdoor Fan Motor

At the normal temperature (10˚C ~ 30˚C)
Compare terminal

Resistance

Remark

Yellow, Blue

404.4Ω ± 10%

Main

Yellow, Red

340Ω ± 10%

Sub

∞, 0Ω . . . Open or Short

Measure the resistance between motor wires with a tester.
Normal

At the normal temperature (10˚C ~ 30˚C)
Compare terminal

Abnormal
Stepping Motor

40

Resistance

Remark

Yellow, Red

360Ω ± 10%

Main

Black, Yellow

328Ω ± 10%

Sub

∞, 0Ω . . . Open or Short

Measure the resistance between the red wire and each terminal wire with a tester.
Normal

About 300Ω at the normal temperature (20˚C ~ 30˚C)

Abnormal

∞, 0Ω . . . Open or Short

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 41

MEMO

Samsung Electronics

41

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 42

7. Exploded Views and Parts List
7-1 Indoor Unit
17

14
6
14-1

15

11
7

14-2
14-3

12

23

14-4

3
16

14-5

18

23-1
14-6

3-1
3-2

19

13

3-4

9
9-2

10

21
23-2

3-3

9-3

20

9-1

1
1-1

5

24
4
2-5

8

2-4

1-3
2-1
2-5-1

2
2-6

2-2

1-2

22

2-3

You can search for the updated part code
number through the ITSELF.
URL : http://itself.sec.samsung.co.kr

42

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 43

Exploded Views and Parts List

■

Parts List
No.

Code No.

1
1-1
1-2
1-3
2
2-1
2-2
2-3
2-4
2-5
2-5-1
2-6
3
3-1
3-2
3-3
3-4
4
5
6
7
8
9

DB92-00633A
DB64-01210A
DB93-02831A
DB63-01103A
DB94-00629A
DB63-01104A
DB61-02049A
DB61-02053A
DB73-00234A
DB94-00062L
DB67-00510A
DB95-20138A
DB93-02960A
DB61-02056A
DB64-01211A
DB93-02806A
DB93-01369A
DB63-01106A
DB63-01107A
DB61-02050A
DB61-02052A
DB93-02804A
DB96-03835A
DB96-03835B
DB60-00198A
DB60-00203B
DB96-03834A
DB96-03834B
DB67-60030A
DB94-00674A
DB94-00627A
DB31-00270A
DB94-00626A
DB61-02057A
DB61-02047A
DB61-02048A
DB63-01105A
DB91-00287A
DB93-01383G
DB61-02051A
DB67-00508A
DB70-00514A
DB70-00515A
DB70-00516A
DB93-01549B
DB93-03016R
DB92-00643A
DB90-01829A
DB63-01108A
DB64-01276A
DB63-01253A

9-1
9-2
9-3
10
11
12
13
14
14-1
14-2
14-3
14-4
14-5
14-6
15
16
17
18
19
20
21
22
23
23-1
23-2
24

Samsung Electronics

Description
ASS'Y PANEL FRONT
PANEL FRONT
ASS'Y SPEAKER UNIT
FILTER-PRE
ASS'Y TRAY DRAIN
TRAY DRAIN
BLADE-H
BLADE-V
RUBBER-CAP DRAIN
ASS'Y DRAIN-HOSE
DRAIN-CUFF
ASS'Y MOTOR-STEPPING
ASS'Y DISPLAY
HOLDER DISPLAY
WINDOW DISPLAY
ASS'Y PCB DISPLAY
ASS'Y MODULE PCB
COVER TERMINAL
COVER PCB-DVM
HOLDER EVAP
HOLDER MOTOR
ASS'Y CONTROL IN
ASS'Y EVAP TOTAL
ASS'Y EVAP TOTAL
SPACER-EVAP MID
SPACER-EVAP UP
ASS'Y EVAP
ASS'Y EVAP
SPRING-SENSOR
ASS'Y BEARING-RUBBER
ASS'Y-CROSS FAN
MOTOR FAN-IN
ASS'Y BACK BODY
BODY BACK
BUSH BODY LF
BUSH BODY RH
COVER-IONIZER
ASS'Y ELECTRIC-IONIZER
ASS'Y C/W ION
HOLDER-PIPE
CAP SCREW
PLATE-HANGER
PLATE CONTACT
PLATE-CONTROL IN
ASS'Y-CONNECTOR POWER
ASS'Y REMOCON
ASS'Y GRILLE
ASS'Y COVER DISPLAY
COVER DISPLAY
INLAY DISPLAY
COVER CONTROL

Specification
ASS'Y
HIPS
ASS'Y
PP
ASS'Y
ABS
ABS
PP
CR
ASS'Y
ABS
24BYJ48
ASS'Y
HIPS
HIPS
ASS'Y
ASS'Y
HIPS V0
HIPS
ABS
PP
ASS'Y
ASS'Y
ASS'Y
PVC
PVC
FP1.3, H-FIN, 2x12
FP1.5, H-FIN, 2x12
STS 301
ASS’Y, CR 45
ø83 x 719
YDK-20S4D8C-1
ASS'Y
HIPS
HIPS
HIPS
HIPS
ASS'Y
ASS'Y
HIPS
HIPS
SGCC-M, T0.8
SUS 304
SGCC-M
ASS'Y
ARH-1315
ASS'Y
ASS'Y
PC
ACRYL
SGCC-M

Q'TY
AS09HPBN

AS12HPBN

1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1

43

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 44

7-2 Outdoor Unit

21
22-1

22-6

23

22

22-7

22-4

15

22-2

2

22-5

11
24
7

12

3
1
10

14
6

20
18
22-3

17

16

8
19
13
4
9

5

44

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 45

Exploded Views and Parts List

■

Parts List
Description

Specification

Q'TY

No.

Code No.

1

6021-000281

NUT-HEXAGON

M6, ZPC, STS410

2

DB67-50063A

FAN-PROPELLER

AS+G/F 20%, ø405

1

1

3

DB31-10058C

MOTOR FAN OUT

220/240V, 50/60Hz

1

1

4

DB90-01524B

ASS'Y CABINET-FRONT

ASS'Y

1

1

5

DB63-00847A

GUARD FAN

PP

1

1

6

DB64-00982A

CABINET-SIDE LF

SECC-P

1

1

7

DB64-00992A

HANDLE-LF

PP

1

1

8

DB90-01525C

ASS'Y-CABI SIDE RH

ASS'Y

1

1

AS09HPBX

AS12HPBX

1

1

9

DB63-00843A

COVER-SIDE

ABS

1

1

10

DB90-01295C

ASS'Y-BASE OUT

ASS'Y

-

1

DB90-01295E

ASS'Y-BASE OUT

ASS'Y

1

-

11

DB61-02065A

BRACKET MOTOR

SGCC-M

1

1

12

DB61-02066A

BRACKET-VALVE

GALVANIZED STEEL

1

1

13

DB73-00067A

GROMMET-ISOLATOR

NR

-

3

DB73-00070A

GROMMET-ISOLATOR

NR

3

-

14

DB94-00631A

ASS'Y PARTITION

ASS'Y

1

1

15

DB96-03836A

ASS'Y COND

ø7 FP1.5, LOUVER, 2x24

-

1

DB96-03837A

ASS'Y COND

ø7 FP1.4, LOUVER, 1x24

1

-

16

G8C124JU1EL

COMPRESSOR

G8C124

-

1

G4A091JU1EP

COMPRESSOR

G4A091

1

-

17

DB63-20002A

GASKET

EPDM

1

1

18

DB63-10165D

COVER TERMINAL

PBT

1

1

19

DB60-30028A

NUT-WASHER

HEX2C M8 ZPC

3

3

20

DB60-30018A

NUT-FLANGE

M5, SM20C

1

1

21

DB71-00093A

BAR-STEEL

HSWR

1

1

22

DB93-02916A

ASS'Y CONTROL OUT

ASS'Y

-

1

DB93-02916B

ASS'Y CONTROL OUT

ASS'Y

1

-

22-1

DB70-00523A

PLATE-CONTROL OUT

SGCC-M

1

1

22-2

DB33-00049B

SOLENOID-ASS'Y

ASS'Y

1

1

22-3

DB35-00028B

RELAY PROTECTOR O/L

RBC12128-12500

-

1

DB35-00028A

RELAY PROTECTOR O/L

RBC12054-12500

1

-

22-4

DB65-00166A

TERMINAL BLOCK

4P

1

1

22-5

DB93-01547F

ASS'Y LEAD WIRE

ASS'Y

1

1

22-6

2501-001237

CAPACITOR-COMP

35uF/450VAC

-

1

2501-001238

CAPACITOR-COMP

40uF/450VAC

1

-

22-7

2301-001375

CAPACITOR-MOTOR

1.5uF/450VAC

1

1

23

DB96-03828A

ASS'Y VALVE 4WAY

ASS'Y

-

1

DB96-03840A

ASS'Y VALVE 4WAY

ASS'Y

1

-

DB96-03829A

ASS'Y TUBE CAPILLARY

ASS'Y

-

1

DB96-03829B

ASS'Y TUBE CAPILLARY

ASS'Y

1

-

24

Samsung Electronics

45

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 46

7-3 Ass'y-Control In : DB93-02804A

N(1)

■

1

2

3

Parts List
No.

Code No.

1

DB61-02054A

CASE-CONTROL

ABS

1

2

DB65-00103C

ASS'Y-TERMINAL BLOCK

ASS'Y

1

3

DB93-02808A

ASS'Y-MAIN PCB

ASS'Y

1

4

DB93-02809A

ASS'Y-MELODY PCB

ASS'Y

1

5

DB70-00516A

PLATE-TERMINAL LOW

SGCC-M T1.2

1

6

DB61-00171A

HOLDER-WIRE CLAMP

ABS

1

7

6001-000929

SCREW-MACHINE

PH M3 x L22

1

8

6001-001054

SCREW-MACHINE

TH M4 x L10

2

9

DB93-02827A

C/W MAIN TO DISPLAY

ASS'Y

1

10

DB39-00643N

C/W STEP MOTOR UP/DOWN

ASS'Y

1

11

DB32-00020K

ASS'Y-THERMISTOR

4P(103AT)

1

12

DB93-02881A

C/W MELODY TO SPEAKER

ASS'Y

1

13

DB93-02828A

C/W MELODY TO MAIN

ASS'Y

1

14

DB65-10088D

SPEAKER WIRE TIE

-

1

46

Description

Specification

Q'TY

Remark

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 47

8. Block Diagram
* : OPTION

CONTROLLER
IC-MCU
HEAT EXCHANGER SENSOR

• BLADE CONTROL
• INDOOR FAN MOTOR CONTROL
• COMPRESSOR CONTROL

ROOM TEMPERATURE SENSOR

• OUTDOOR FAN MOTOR CONTROL
SIGNAL

INFRARED SIGNAL
RESET
CIRCUIT

• 4-WAY VALVE CONTROL SIGNAL
• TEMPERATURE CONTROL
• TIMER
• BUZZER CONTROL
• ANION CONTROL

OSCILLATION
CIRCUIT

MODE
(AUTO, COOL, DRY, FAN,
HEAT)
TURBO OPERATION

TEMPERATURE
OPERATION
AUTO CLEAN
TURBO
ENERGY SAVING
TIMER
ANION
FAN SPEED

ZERO
VOLTAGE
DETECT

REMOTE CONTROL

POWER ON/OFF

DISPLAY PART

• COMPRESSOR CONTROL
SIGNAL
• OUTDOOR FAN MOTOR
CONTROL SIGNAL
• 4-WAY VALVE CONTROL
SIGNAL

TRIGGER
SIGNAL

INDOOR FAN MOTOR

SSR

• STEPPING MOTOR
CONTROL SIGNAL
• BUZZER CONTROL SIGNAL

FAN SPEED SELECT
(H/M/L/AUTO)
BLADE-H
MOVING SELECT
ON, OFF TIMER
SELECT/CANCEL

• ANION CONTROL SIGNAL*

• COMPRESSOR DRIVE
• OUTDOOR FAN MOTOR
DRIVE
• 4-WAY VALVE DRIVE
• STEPPING MOTOR DRIVE

TEMPERATURE
SELECT(UP/DOWN)

COMPRESSOR
OUTDOOR FAN MOTOR
4-WAY VALVE
BUZZER
ANION

• BUZZER DRIVE
• ANION DRIVE

STEPPING MOTOR
: BLADE UP/DOWN

SLEEP OPERATION
ANION SELECT

DC5V

BUZZER CONTROL PART

VOLTAGE REGULATOR
AUTO CLEAN SELECT
SPEA KER
ENERGY SAVING SELECT
DC12V
SOUND ON/OFF SELECT
DIGITAL

OPTION

SMPS POWER BLOCK

ON/OFF

AC INPUT

Samsung Electronics

47

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 48

9. Wiring Diagram
9-1 Indoor Unit

Code No : DB98-20360A

This Document can not be used without Samsung's authorization.

48

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 49

9-2 Outdoor Unit

C1

MOTOR CAPACITOR

FM1

FAN MOTOR

C2

COMP CAPACITOR

O.L.P

OVER LOAD PROTECTOR

Code No : DB98-21095A

This Document can not be used without Samsung's authorization.

Samsung Electronics

49

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 50

MEMO

50

Samsung Electronics

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 51

MEMO

Samsung Electronics

51

DB98_20429A(1)_1

12/24/04 10:55 AM

Page 52

MEMO

52

Samsung Electronics

DB98_20429A(1)_CO

12/24/04 10:54 AM

Page 2

ELECTRONICS

This Service Manual is a property of Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable
International and/or domestic law.

© Samsung Electronics Co., Ltd. Dec. 2004.
Printed in Korea.
Code No. DB98-20429A(1)



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : No
Create Date                     : 2004:12:24 11:02:41
Producer                        : Acrobat Distiller 4.0 for Macintosh
Author                          : 4
Creator                         : QuarkXPress3.32E: LaserWriter 8 8.7.1
Title                           :  DB98_20429A(1)_1
Modify Date                     : 2004:12:24 11:10:56+09:00
Page Count                      : 54
EXIF Metadata provided by EXIF.tools

Navigation menu