Technical Data

PowerFlex® 4 and
PowerFlex® 40
AC Drives

PowerFlex® 4 and PowerFlex® 40 AC Drives Technical Data
Providing users with powerful motor speed control in a compact, space
saving design, the Allen-Bradley PowerFlex 4 and 40 AC drives are the
smallest and most cost-effective members of the PowerFlex family of drives.
Available in power ratings from 0.2 to 11 kW (0.25 to 15 HP) and in voltage
classes of 120, 240, 480 and 600 volts, PowerFlex 4 and 40 are designed to
meet global OEM and end-user demands for flexibility, space savings, ease
of use and are cost-effective alternatives for speed control of applications
such as machine tools, fans, pumps and conveyors and material handling
systems.

Table of Contents
Description
Page
PowerFlex 4 and 40 Common Attributes . . . . . . . . . . . . . . . . . . . . . . . 3
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PowerFlex 40 Advanced Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communication & Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Feature Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
User Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Parameter Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Shaded areas are applicable to PowerFlex 40 only.

2
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

PowerFlex 4-Class Common Attributes
Packaging and Mounting
• Installation can be a virtual snap using the DIN rail mounting feature
on A and B frame drives. Panel mounting is also available, providing
added flexibility.
• Flange mount drives are available to reduce overall enclosure size.
• Zero Stacking™ is allowable for ambient temperatures up to 40°C,
saving valuable panel space. 50°C ambient temperatures are permitted
with minimal spacing between drives.
• Integral filtering is available on all 230V single phase ratings,
providing a cost-effective means of meeting EN55011, Class A and B
EMC requirements. External filters provide compliance to Class A and B
requirements for all PowerFlex 4 and 40 ratings.
• An optional IP30 (NEMA 1) conduit box is easily adapted to the
standard IP20 (NEMA Type Open) product, providing increased
environmental ratings.

Start Up, Programming and Operation
• An integral keypad provides out of the box operation using the local
potentiometer and control keys.
• The 10 most common application parameters are contained in the Basic
Program Group, making programming fast and easy.
• The programming keys have the same function as all other PowerFlex
drives, so if you can program one PowerFlex drive, you can program them
all.
• 4 digit display with 10 additional LED indicators provides an intuitive
display of drive status and information.
• Integral RS-485 communications can be used for programming from a
PC. It can also be used in a multi-drop network configuration. A serial
converter module provides connectivity to any controller with a DF1 port.
• A NEMA Type 4X remote and NEMA Type 1 hand-held LCD keypad
provide additional programming and control flexibility, both featuring the
popular CopyCat function.

Optimized Performance
• Removable MOV to ground provides trouble-free operation when used
on ungrounded distribution systems.
• A relay pre-charge limits inrush current.
• Integral brake transistor, available on all ratings (except no brake
version), provides dynamic braking capability with simple low cost brake
resistors.
• DIP switch settable 24V DC sink or source control for control wiring
flexibility.
• 150% overload for 60 seconds or 200% overload for 3 seconds provides
robust overload protection.
• Adjustable PWM frequency up to 16 kHz ensures quiet operation.

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

3

Performance
Sensorless Vector Performance
PowerFlex 4
• Drive automatically provides auto boost
(IR compensation) and slip compensation.
• Provides excellent speed regulation and high levels of torque
across the entire speed range of the drive, and improved
speed regulation even as loading increases.

Sensorless Vector Control
AB PowerFlex 40 3Hp - High Speed

PowerFlex 40

• The Autotune feature allows the PowerFlex 40 to adapt to
individual motor characteristics.

3.0
Torque (Per-Unit)

• Sensorless Vector Control provides exceptional speed
regulation and very high levels of torque across the entire
speed range of the drive.

2.5
2.0
1.5
1.0
0.5
0.0
0

10

20

30

40

50

60

Frequency (HZ)

Performance
• This graph depicts the ability of a PowerFlex 40 drive to
accelerate into at least 150% load. A PowerFlex 4 will perform
similarly, but with a slightly higher acceleration time.
• At 100% motor load, the drive will run the motor at
synchronous speed.

Current
Speed

• Excellent current regulation.
• Linear acceleration.
• Best in class digital input response time and repeatability.

4

Torque

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

70

80

90

100

PowerFlex 40 Advanced Features
Performance
• Sensorless Vector Control develops high torque over a wide speed
range and adapts to individual motor characteristics.
• Variable PWM allows the drive to output more current at low
frequencies.
• Integral PID functionality enhances application flexibility.
• Timer, Counter, Basic Logic and StepLogic™ functions can reduce
hardware design costs and simplify control schemes.
• Timer function: Relay or opto outputs controlled by drive performing
timer function. Timer is initiated by activating a digital input
programmed as “Timer Start.”
• Counter function: Relay or opto outputs controlled by drive
performing counter function. Counter function is activated by a digital
input programmed as “Counter Input.”
• Basic Logic: Relay or opto outputs controlled by status of digital
inputs programmed as “Logic Inputs.” Performs basic Boolean logic.
• StepLogic: Logic-based steps using preset speed settings. Each step
can be programmed for a specific speed, direction and accel/decel
profile. Drive outputs can be used to indicate which step is being
performed.

I/O
Analog Signal Follwer

• Two (2) Analog Inputs (one unipolar and one bipolar) are
independently isolated from the rest of the drive I/O. These inputs can be
toggled between via a digital input.
• Three (3) fixed and four (4) fully programmable Digital Inputs
provide application versatility.

Drive 1

Drive 2

Analog Out

Analog In

Common

14

+

16

• One (1) Analog Output is DIP switch selectable for either 0-10V or 020mA. This scalable, 10-bit output is suitable for metering or as a speed
reference for another drive.

-/+ 10V
Common

13
14

• Two (2) Opto Outputs and one (1) form C relay output can be used to
indicate various drive, motor or logic conditions.

Communications
• Integral communication cards such as DeviceNet™, EtherNet/IP and
Profibus can improve machine performance.
• Field installed option allows for future addition of stand-alone drives
to a network.
• Online EDS file creation with RS NetWorx providing ease of set-up on
a network.

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

5

Communications & Software
Versatile Programming and Network Solutions
• PowerFlex 4 and PowerFlex 40 are compatible
with any device that acts as a RTU Master and
supports standard 03 and 06 RTU commands.
• A network can be configured using PowerFlex
40 drives with optional communication cards
for high performance and flexible configuration
capabilities.
• DeviceNet

RTU
up to 31 PowerFlex 4 or PowerFlex 40 drives
Network Communication
Node 1

Node 2

Node 3

• EtherNet/IP
• Profibus

PowerFlex 40
PowerFlex 40
PowerFlex 40
with Comms card with Comms card with Comms card

• A multi-drive solution can be reached using a
single PowerFlex 40 DeviceNet option, with
the ability for up to five (5) drives to reside on
one (1) node.

DeviceNet

RTU

• Integral RS485 communications enable the
drives to be used in a multi-drop network
configuration. A serial converter module (SCM)
provides connectivity to any controller with a
DF1 port. The SCM can be eliminated if the
controller acts as a RTU Master.

up to 4 PowerFlex 4 or PowerFlex 40 drives

DF1

RTU
SCM

up to 31 PowerFlex 4 or PowerFlex 40 drives

PC Programming Software
Through the use of a Serial Converter Module and
DriveExplorer™ or DriveTools™ SP software, programming
can be greatly simplified.

DriveExplorer Software
• View and modify drive and adapter parameters in a
method similar to the file management capability of
Microsoft Windows Explorer.
• Operate the drive via an on-screen Control Bar, which is
a tool that allows you to start, stop, and change the
speed reference of the drive.
• Save, restore and print parameter information.
• Compare current parameters with factory defaults or
previously saved parameter values.
• Edit, upload and download parameters.

DriveTools SP Software
• Online and offline programming capability
• In-grid and dialog-based parameter editing
• Immediate visual indication of drive and communication status when viewing online drive
• Integrated HTML Help architecture
6

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Feature Comparison

Use the chart below to assist in determining which product is most appropriate for an application.

Feature
Catalog Reference
Maximum (kW)HP Rating/Input Voltage

Overload Capacity

22A…
(1.1)1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(3.7) 5 HP/230V, 3ø
(3.7) 5 HP/460V, 3ø
150% for 60 seconds
200% for 3 seconds
●
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●

NEMA 1/IP30 Option
EMC Filtering
DIN Rail Mounting Standard
Integral Keypad with Speed Pot
Keypad - Remote LCD
Keypad CopyCat Function
Control Type
Internal DB Transistor
Preset Speeds
Carrier Frequency
Skip Frequency
Process Control Loop
StepLogic Functionality
Timer/Counter Functions
Control Voltage
Discrete Inputs

●
●
●
V/Hz
●
Not available on no brake models.
4
2-16 kHz

24V sink/source
3 fixed for START/STOP/REV
2 fully programmable
1
(0-10V or 4-20 mA)

Analog Input - Unipolar
Analog Input - Bipolar
Analog Response
Relay Output
Digital/Optocoupler Output
Analog Output

2 Hz (500 ms)
1 - N.O/N.C. dry contact

Integral RS485
RS232 (Requires use of Serial Converter Module)
DeviceNet
EtherNet/IP
Profibus

●
●

22B…
(1.1) 1.5 HP/115V, 1ø
(2.2) 3 HP/230V, 1ø
(7.5) 10 HP/230V, 3ø
(11.0) 15 HP/460V, 3ø
(11.0) 15 HP/600V, 3ø
150% for 60 seconds
200% for 3 seconds
●
Internal - 1ø, 230V
External - All 1ø, 115V and 3ø Ratings
●
(Through 5 HP)
●
●
●
Sensorless Vector & V/Hz
●
8
2-16 kHz
●
●
(PID)
●
●
24V sink/source
3 fixed for START/STOP/REV
4 fully programmable
2
(0-10V and 4-20 mA)
1
(+/- 10V) ➊
100 Hz (10 ms)
1 - N.O./N.C. dry contact
2
●
(0-10V or 4-20 mA)
●
●
●
●
●

➊ When using bipolar input, the 0-10V unipolar input cannot be used.

7
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Catalog Number Explanation

1-3

4

5

6-8

9

Position
10

11

13-14

12(1)

22A

-

A

1P5

N

1

1

4

AA

Drive

Dash

Voltage Rating

Rating

Enclosure

HIM

Emission Class

Version

Optional

Code
22A
22B

Code
3
4

PowerFlex 4
PowerFlex 40
Code
V
A
B
D
E

Voltage
120V AC
240V AC
240V AC
480V AC
600V AC

Ph.
1
1
3
3
3

Code
0
1
Code
1

Code
N
F
H

Rating
Not Filtered
Filtered

Interface Module
Fixed Keypad

Code
AA
Thru
ZZ

Purpose
Reserved for
custom firmware

Enclosure
Panel Mount - IP 20 (NEMA Type Open)
Flange Mount - IP 20 (NEMA Type Open)
Replacement Plate Drive - IP 20 (NEMA Type Open)
- Contact factory for ordering information.

Output Current @ 100-120V Input
Code Amps
kW (HP)
1P5
1.5
0.2 (0.25)
2P3
2.3
0.4 (0.5)
4P5
4.5
0.75 (1.0)
5P0
5.0
0.75 (1.0)
6P0
6.0
1.1 (1.5)

Output Current @ 200-240 Input, NO BRAKE (2)
Code Amps
kW (HP)
1P4
1.4
0.2 (0.25)
2P1
2.1
0.4 (0.5)
3P6
3.6
0.75 (1.0)
6P8
6.8
1.5 (2.0)
9P6
9.6
2.2 (3.0)

Output Current @ 200-240V Input
Code Amps
kW (HP)
1P5
1.5
0.2 (0.25)
2P3
2.3
0.4 (0.5)
4P5
4.5
0.75 (1.0)
5P0
5.0
0.75 (1.0)
8P0
8.0
1.5 (2.0)
012
12.0
2.2 (3.0)
017
17.5
3.7 (5.0)
024
24.0
5.5 (7.5)
033
33.0
7.5 (10.0)

Output Current @ 380-480V Input
Code Amps
kW (HP)
1P4
1.4
0.4 (0.5)
2P3
2.3
0.75 (1.0)
4P0
4.0
1.5 (2.0)
6P0
6.0
2.2 (3.0)
8P7
8.7
3.7 (5.0)
010
10.5
4.0 (5.0)
012
12.0
5.5 (7.5)
017
17.0
7.5 (10.0)
024
24.0
11.0 (15.0)

(1)
(2)

Version
No Brake IGBT
Standard

Output Current @ 460-600V Input
Code Amps
kW (HP)
1P7
1.7
0.75 (1.0)
3P0
3.0
1.5 (2.0)
4P2
4.2
2.2 (3.0)
6P6
6.6
4.0 (5.0)
9P9
9.9
5.5 (7.5)
012
12.0
7.5 (10.0)
019
19.0
11.0 (15.0)

Position 12 of the Catalog Number now indicates drive version. All PowerFlex 4 and 40 drives are equipped with RS485 communication.
PowerFlex 4 option only.

8
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Product Selection
Drive Ratings

PowerFlex 4

Input Voltage

kW

HP

120V 50/60 Hz
1-Phase
No Filter

0.2
0.4
0.75
1.1
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11.0
0.75
1.5
2.2
4.0
5.5
7.5
11.0

0.25
0.5
1.0
1.5
0.25
0.5
1.0
2.0
3.0
0.25
0.5
1.0
2.0
3.0
0.25
0.5
1.0
2.0
3.0
0.25
0.5
1.0
2.0
3.0
0.25
0.5
1.0
2.0
3.0
5.0
7.5
11
0.5
1.0
2.0
3.0
5.0
5.0
7.5
10.0
15.0
1.0
2.0
3.0
5.0
7.5
10.0
15.0

240V 50/60 Hz
1-Phase
NO BRAKE
No Filter

240V 50/60 Hz
1-Phase
NO BRAKE
With Integral
“S Type” EMC
Filter ➊
240V 50/60 Hz
1-Phase
With Integral
“S Type” EMC
Filter ➊
240V 50/60 Hz
1-Phase
No Filter

240V 50/60 Hz
3-Phase
No Filter

480V 50/60 Hz
3-Phase
No Filter

600V 50/60 Hz
3-Phase
No Filter

➊

Output
Current
1.5A
2.3A
4.5A
6.0A
1.4A
2.1A
3.6A
6.8A
9.6
1.4A
2.1A
3.6A
6.8A
9.6
1.5A
2.3A
4.5A
8.0A
—
1.5A
2.3A
4.5A
8.0A
—
1.5A
2.3A
4.5A
8.0A
12.0A
17.5A
—
—
1.4A
2.3A
4.0A
6.0A
8.7A
—
—
—
—
—
—
—
—
—
—
—

Catalog Number Frame
Size
22A-V1P5N104
A
22A-V2P3N104
A
22A-V4P5N104
B
22A-V6P0N104
B
22A-A1P4N103
A
22A-A2P1N103
A
22A-A3P6N103
A
22A-A6P8N103
B
22A-A9P6N103
B
22A-A1P4N113
A
22A-A2P1N113
A
22A-A3P6N113
A
22A-A6P8N113
B
22A-A9P6N113
B
22A-A1P5N114
A
22A-A2P3N114
A
22A-A4P5N114
A
22A-A8P0N114
B
—
—
22A-A1P5N104
A
22A-A2P3N104
A
22A-A4P5N104
A
22A-A8P0N104
B
—
—
22A-B1P5N104
A
22A-B2P3N104
A
22A-B4P5N104
A
22A-B8P0N104
A
22A-B012N104
B
22A-B017N104
B
—
—
—
—
22A-D1P4N104
A
22A-D2P3N104
A
22A-D4P0N104
A
22A-D6P0N104
B
22A-D8P7N104
B
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—

IP 20 Flange Mount PowerFlex 40

IP 20 Flange Mount

Catalog Number

Catalog Number

22A-V1P5F104
22A-V2P3F104
22A-V4P5F104
22A-V6P0F104
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22A-A1P5F104
22A-A2P3F104
22A-A4P5F104
22A-A8P0F104
—
22A-B1P5F104
22A-B2P3F104
22A-B4P5F104
22A-B8P0F104
22A-B012F104
22A-B017F104
—
—
22A-D1P4F104
22A-D2P3F104
22A-D4P0F104
22A-D6P0F104
22A-D8P7F104
—
—
—
—
—
—
—
—
—
—
—

Output
Current
—
2.3A
5.0A
6.0A
—
—
—
—
—
—
—
—
—
—
—
2.3A
5.0A
8.0A
12.0A
—
2.3A
5.0A
8.0A
12.0A
—
2.3A
5.0A
8.0A
12.0A
17.5A
24.0A
33.0A
1.4A
2.3A
4.0A
6.0A
—
10.5A
12.0A
17.0A
24.0A
1.7A
3.0A
4.2A
6.6A
9.9A
12.0A
19.0A

Catalog Number Frame
Size
—
—
22B-V2P3N104
B
22B-V5P0N104
B
22B-V6P0N104
B
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22B-A2P3N114
B
22B-A5P0N114
B
22B-A8P0N114
B
22B-A012N114
C
—
—
22B-A2P3N104
B
22B-A5P0N104
B
22B-A8P0N104
B
22B-A012N104
C
—
—
22B-B2P3N104
B
22B-B5P0N104
B
22B-B8P0N104
B
22B-B012N104
B
22B-B017N104
B
22B-B024N104
C
22B-B033N104
C
22B-D1P4N104
B
22B-D2P3N104
B
22B-D4P0N104
B
22B-D6P0N104
B
—
—
22B-D010N104
B
22B-D012N104
C
22B-D017N104
C
22B-D024N104
C
22B-E1P7N104
B
22B-E3P0N104
B
22B-E4P2N104
B
22B-E6P6N104
B
22B-E9P9N104
C
22B-E012N104
C
22B-E019N104
C

—
22B-V2P3F104
22B-V5P0F104
22B-V6P0F104
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22B-A2P3F104
22B-A5P0F104
22B-A8P0F104
22B-A012F104
—
22B-B2P3F104
22B-B5P0F104
22B-B8P0F104
22B-B012F104
22B-B017F104
22B-B024F104
22B-B033F104
22B-D1P4F104
22B-D2P3F104
22B-D4P0F104
22B-D6P0F104
—
22B-D010F104
22B-D012F104
22B-D017F104
22B-D024F104
22B-E1P7F104
22B-E3P0F104
22B-E4P2F104
22B-E6P6F104
22B-E9P9F104
22B-E012F104
22B-E019F104

This filter is suitable for use with a cable length of at least 10 meters for Class A and 1 meter for Class B environments.

Shaded areas denote options for PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

9

User Installed Options

IP30/NEMA 1/UL Type 1 Conversion Kit
Item

Description

Drive
Frame

IP30/NEMA 1/UL Type 1 Kit Field installed kit. Converts drive to IP30/NEMA 1/UL Type 1 enclosure. Includes conduit box A
with mounting screws and plastic top panel.
B
C
IP30/NEMA 1/UL Type 1 Kit Field installed kit. Converts drive to IP30/NEMA 1/UL Type 1 enclosure. Includes
B
with Communication Option communication option conduit box with mounting screws and plastic top panel.
C

PowerFlex 4
Catalog
Number ➋
22-JBAA
22-JBAB
–
–
–

PowerFlex 40
Catalog
Number ➋
–
22-JBAB
22-JBAC
22-JBCB
22-JBCC

Human Interface Module Option Kits and Accessories
Item

Description

Catalog Number ➋

Remote Human Interface
Modules (HIMs)

LCD Display, Remote Panel Mount, Digital Speed Control, Full Numeric Keypad, CopyCat capable, IP66
(NEMA Type 4X/12) indoor use only, Includes 2.9 meter cable.
LCD Display, Remote Handheld, Digital Speed Control, Full Numeric Keypad, CopyCat capable, IP30
(NEMA Type 1), Includes 1.0 meter cable, Panel Mount with optional Bezel Kit.
Panel Mount for LCD Display, Remote Handheld unit, IP30 (NEMA Type 1), Includes a 22-RJ45CBL-C20 cable.
DSI HIM Cable (DSI HIM to RJ45 cable)
1.0 Meter (3.3 Feet)
2.9 Meter (9.51 Feet)

22-HIM-C2S ➊
22-HIM-C2
22-HIM-A3

Bezel Kit
DSI HIM Cable

22-HIM-B1
22-HIM-H10
22-HIM-H30

Communication Option Kits
Item

Description

Catalog Number ➋

Serial Converter Module
(RS485 to RS232)

Provides serial communication via DF1 protocol for use with DriveExplorer™ and DriveExecutive™ software.
Smart Self-powered Serial Converter (RS-232) includes:
DSI to RS232 serial converter
DriveExplorer Lite Version 3.01 or later
1203-SFC and 22-RJ45CBL-C20 Cables
2.0 meter RJ45 to RJ45 cable, male to male connectors.
Embedded communication option for use with the PowerFlex family of drives.
Requires a Communication Adapter Cover (Ordered Separately).
DeviceNet
EtherNet/IP
Profibus
Houses the optional communication adapters. These covers add 25 mm (0.98 in.) to the overall depth of the drive.
PowerFlex 40 Drive Frame B
PowerFlex 40 Drive Frame C
2.0 meter serial cable with a locking low profile connector to connect to the serial converter and a 9-pin subminiature D female connector to connect to a computer.
For use when connecting the serial converter to DriveExplorer on a handheld PC.
RJ45 one to two port splitter cable.
RJ45 120 Ohm resistor (2 pieces).
RJ45 Two position terminal block (5 pieces).

22-SCM-232

DSI Cable
Communication Adapters

Communication Adapter
Covers
Serial Cable
Null Cable Converter
Splitter Cable
Terminating Resistors
Terminal Block

22-RJ45CBL-C20

22-COMM-D
22-COMM-E
22-COMM-P
22B-CCB
22B-CCC
1203-SFC
1203-SNM
AK-U0-RJ45-SC1
AK-U0-RJ45-TR1
AK-U0-RJ45-TB2P

PC Programming Software
Item

Description

DriveTools SP Software,
Version 2.02 or later

“Windows” based software package that provides an intuitive means for monitoring or configuring Allen-Bradley 9303-4DTE01ENE
drives and communications adapters online and offline.
Compatibility: Windows 98, ME, NT, 4.0 (Service Pack 3 or later), 2000 and XP. ➌
“Windows” based software package that provides an intuitive means for monitoring or configuring Allen-Bradley 9306-4EXP01ENE
drives and communications adapters online and offline.
Compatibility: Windows 98, ME, NT, 4.0 (Service Pack 3 or later), 2000 and XP. ➌

DriveExplorer™ Software,
Version 4.02 or later

Catalog Number

➊ The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement.
➋ For pricing information, refer to the PowerFlex 4 and 40 AC Drives Price List, publication 22-PL001x-EN-P.
➌ See www.ab.com/drive/ for support devices.

10

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

User Installed Options

DC Bus Inductors
Input Voltage
240V 50/60 Hz 3-Phase
480V 50/60 Hz 3-Phase

600V 50/60 Hz 3-Phase

kW
5.5
7.5
5.5
7.5
11.0
5.5
7.5
11.0

HP
7.5
10.0
7.5
10.0
15.0
7.5
10.0
15.0

Amps
32
40
18
25
32
12
18
25

Inductance
mh
0.85
0.5
3.75
4.0
2.68
6.0
6.0
4.0

MTE Catalog Number
32RB001
40RB001
18RB004
25RB005
32RB003
12RB004
18RB005
25RB005

Dynamic Brake Resistors

3% Line Reactors

Drive Ratings
Input Voltage kW
120V 50/60 Hz 0.2
1-Phase
0.4
0.75
1.1
240V 50/60 Hz 0.2
1-Phase
0.4
0.75
1.5
2.2
240V 50/60 Hz 0.2
3-Phase
0.4
0.75
1.5
2.2
3.7
5.5
7.5
480V 50/60 Hz 0.4
3-Phase
0.75
1.5
2.2
4.0
5.5
7.5
11.0
600V 50/60 Hz 0.75
3-Phase
1.5
No Filter
2.2
4.0
5.5
7.5
11.0

Input
Voltage
240V
50/60 Hz
3-Phase

HP
0.25
0.5
1.0
1.5
0.25
0.5
1.0
2.0
3.0
0.25
0.5
1.0
2.0
3.0
5.0
7.5
10.0
0.5
1.0
2.0
3.0
5.0
7.5
10.0
15.0
1.0
2.0
3.0
5.0
7.5
10.0
15.0

PowerFlex 4
PowerFlex 40
Catalog Number ➊ Catalog Number ➊
AK-R2-091P500
–
AK-R2-091P500
AK-R2-091P500
AK-R2-091P500
AK-R2-091P500
–
AK-R2-091P500
AK-R2-091P500
AK-R2-091P500
–
AK-R2-047P500
AK-R2-091P500
–
AK-R2-091P500
AK-R2-091P500
AK-R2-091P500
AK-R2-047P500
AK-R2-047P500
–
AK-R2-030P1K2
–
AK-R2-030P1K2
AK-R2-360P500
AK-R2-360P500
AK-R2-360P500
AK-R2-120P1K2
AK-R2-120P1K2
–
AK-R2-120P1K2
–
AK-R2-120P1K2
–
AK-R2-120P1K2➋
–
AK-R2-360P500
–
AK-R2-360P500
–
AK-R2-120P1K2
–
AK-R2-120P1K2
–
AK-R2-120P1K2
–
AK-R2-120P1K2
–
AK-R2-120P1K2➋

480V
50/60 Hz
3-Phase

600V
50/60 Hz
3-Phase
No Filter

kW HP
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11.0
0.75
1.5
2.2
4.0
5.5
7.5
11.0

0.25
0.5
1.0
2.0
3.0
5.0
7.5
10.0
0.5
1.0
2.0
3.0
5.0
5.0
7.5
10.0
15.0
1.0
2.0
3.0
5.0
7.5
10.0
15.0

Fundamental
Amps
2
4
8
8
12
18
25
35
2
4
4
8
8
12
12
18
25
2
4
4
8
12
12
18

Max Continuous Amps
3
6
12
12
18
27
37.5
52.5
3
6
6
12
12
18
18
27
37.5
3
6
6
12
18
18
27

Inductance
mh
12.0
12.0
3.0
1.5
1.25
0.8
0.5
0.4
20.0
9.0
6.5
5.0
3.0
2.5
2.5
1.5
1.2
20.0
6.5
6.5
5.0
2.5
2.5
1.5

Watts
Loss
7.5 W
21 W
29 W
19.5 W
26 W
36 W
48 W
49 W
11.3 W
20 W
20 W
25.3 W
29 W
31 W
31 W
43 W
52 W
11.3 W
20 W
20 W
25.3 W
31 W
31 W
43 W

Catalog
Number ➊
1321-3R2-A
1321-3R4-D
1321-3R8-B
1321-3R8-A
1321-3R12-A
1321-3R18-A
1321-3R25-A
1321-3R35-A
1321-3R2-B
1321-3R4-C
1321-3R4-B
1321-3R8-C
1321-3R8-B
1321-3R12-B
1321-3R12-B
1321-3R18-B
1321-3R25-B
1321-3R2-B
1321-3R4-B
1321-3R4-B
1321-3R8-C
1321-3R12-B
1321-3R12-B
1321-3R18-B

➊ Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5%
impedance reactor types are also available. Refer to publication 1321-TD001x-EN-P.

➊ Resistors listed in this table are rated for a minimum 5% duty cycle.
See publication no. PFLEX-AT001x-EN-P for additional information.
➋ Requires two resistors wired in parallel.

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

11

User Installed Options

PowerFlex 4 EMC Filters
Drive Ratings
Input Voltage
120V 50/60 Hz
1-Phase
240V 50/60 Hz
1-Phase

240V 50/60 Hz
3-Phase

480V 50/60 Hz
3-Phase

kW
0.2
0.4
0.75
0.2
0.4
0.75
1.5
0.2
0.4
0.75
1.5
2.2
3.7
0.4
0.75
1.5
2.2
4.0

HP
0.25
0.5
1.0
0.25
0.5
1.0
2.0
0.25
0.5
1.0
2.0
3.0
5.0
0.5
1.0
2.0
3.0
5.0

PowerFlex 40 EMC Filters

S Type Filter
Catalog Number ➊
–
–
–
➌
➌
➌
➌
22-RF9P5-AS
22-RF9P5-AS
22-RF9P5-AS
22-RF9P5-AS
22-RF021-BS
22-RF021-BS
22-RF5P7-AS
22-RF5P7-AS
22-RF5P7-AS
22-RF012-BS
22-RF012-BS

L Type Filter
Catalog Number ➋
22-RF010-AL
22-RF010-AL
22-RF018-BL
22-RF010-AL
22-RF010-AL
22-RF010-AL
22-RF018-BL
22-RF9P5-AL
22-RF9P5-AL
22-RF9P5-AL
22-RF9P5-AL
22-RF021-BL
22-RF021-BL
22-RF5P7-AL
22-RF5P7-AL
22-RF5P7-AL
22-RF012-BL
22-RF012-BL

Drive Ratings
Input Voltage
120V 50/60 Hz
1-Phase
240V 50/60 Hz
1-Phase

240V 50/60 Hz
3-Phase

480V 50/60 Hz
3-Phase

600V 50/60 Hz
3-Phase

kW
0.4
0.75
1.1
0.4
0.75
1.5
2.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11.0
0.75
1.5
2.2
4.0
5.5
7.5
11.0

HP
0.5
1.0
1.5
0.5
1.0
2.0
3.0
0.5
1.0
2.0
3.0
5.0
7.5
10.0
0.5
1.0
2.0
3.0
5.0
7.5
10.0
15.0
1.0
2.0
3.0
5.0
7.5
10.0
15.0

S Type Filter
Catalog Number ➊
–
–
–
➌
➌
➌
➌
22-RF021-BS ➍
22-RF021-BS ➍
22-RF021-BS ➍
22-RF021-BS ➍
22-RF021-BS ➍
22-RF034-CS
22-RF034-CS
22-RF012-BS
22-RF012-BS
22-RF012-BS
22-RF012-BS
22-RF012-BS
22-RF018-CS
22-RF018-CS
22-RF026-CS
–
–
–
–
–
–
–

➊ This filter is suitable for use with a cable length up to 10 meters for Class A and 1 meter for Class B environments.
➋ This filter is suitable for use with a cable length up to 100 meters for Class A and 5 meters for Class B environments.
➌ Drives are available in these ratings with internal “S Type” filters.
➍ Filter must be Series B or later.

12

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

L Type Filter
Catalog Number ➋
22-RF018-BL
22-RF018-BL
22-RF018-BL
22-RF018-BL
22-RF018-BL
22-RF018-BL
22-RF025-CL
22-RF021-BL
22-RF021-BL
22-RF021-BL
22-RF021-BL
22-RF021-BL
22-RF034-CL
22-RF034-CL
22-RF012-BL
22-RF012-BL
22-RF012-BL
22-RF012-BL
22-RF012-BL
22-RF018-CL
22-RF018-CL
22-RF026-CL
22-RF008-BL
22-RF008-BL
22-RF008-BL
22-RF008-BL
22-RF015-CL
22-RF015-CL
22-RF024-CL

Installation Considerations

PowerFlex 4 and 40 drives have the following built in protective features to help simplify installation.
• Ground fault protection while starting and running ensures reliable operation
• Electronic motor overload protection increases motor life
• Removable MOV to ground ensures compatibility with ungrounded systems
• 6kV transient protection provides increased robustness for 380-480V system voltages
There are many other factors that must be considered for optimal performance in any given application. The block diagram below
highlights the primary installation considerations. Consult the PowerFlex 4 or PowerFlex 40 User Manual, Publications 22A-UM001…
or 22B-UM001… available online at www.ab.com/manuals/dr, for detailed recommendations on input power conditioning, CE
conformance (EMC filtering), dynamic braking, reflected wave protection, motor cable types and motor cable distances.

Block Diagram
Branch Circuit Protective Devices – See Specifications on page 17
Input Power Conditioning – See Line Reactors on page 11
Line (EMC) Filter – See page 12

Integral Keypad

Reflected Wave Protection – (Consult the appropriate User Manual)
Motor Cable Type and Length Recommendations –
(Consult the appropriate User Manual)
Class 10 Overload Protection – Provided by the PowerFlex drive
Motor – See publication MOTORS-CA001...

13
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Control Wiring
PowerFlex 4
• The control logic is 24V DC and can be set for either Sink or
Source control via a DIP switch setting.
01

• Control terminal screws are sized for a conventional blade
screw driver.

02
03
SNK

• I/O Terminals 1, 2 and 3 are dedicated for Stop, Start and
Reverse operation respectively. These I/O Terminals can be
programmed for 2- or 3-Wire operation to meet application
requirements.
• I/O Terminals 4 and 5 are programmable and provide added
flexibility. Programmable functions include:
–
–
–
–

Local Control
Jog
Second Accel/Decel
Clear Fault

– Preset Frequencies
– RS485 Control
– Auxiliary Fault

SRC

04
05
06
+24V
+10V

11
12
13

Relay N.O.
Relay Common
Relay N.C.

• Speed can be controlled via a 0-10V input or 4-20 mA input.
Both are electrically isolated from the drive.
• One form C relay can be programmed to provide the status
of a wide variety of drive conditions.

R1

14

R2

15

R3

16

Stop

Typical
Typical
SRC Wiring SNK Wiring

Start/Run FWD
Dir/Run REV
Digital Common
Digital Input 1
Digital Input 2
+24V DC
+10V DC
0-10V In
Analog Common
4-20mA In
RS485 Shield

01 02 03 04 05 06
R1 R2 R3
SNK

11

12 13 14 15 16

RS485
(DSI)
81

SRC

Factory Installed Jumper

• The drive is shipped with a jumper installed between
I/O Terminals 01 and 11 to allow out of box operation from the keypad.
No.
R1
R2
R3

Signal
Relay N.O.
Relay Common
Relay N.C.

Default
Fault
–
Fault

Description
Normally open contact for output relay.
Common for output relay.
Normally closed contact for output relay.

Sink/Source DIP
Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01
02
03

Resistive
Inductive

30V DC
3.0 A
0.5 A

125V AC
3.0 A
0.5 A

240V AC
3.0 A
0.5 A

Coast
Not Active
Not Active

The factory installed jumper or a normally closed input must be present for the drive to start.
Command comes from the integral keypad by default. To disable reverse operation, see A095 [Reverse Disable].

04
05
06
11

Stop(1)
Start/Run FWD
Direction/Run
REV
Digital Common
Digital Input 1
Digital Input 2
+24V DC

–
Preset Freq
Preset Freq
–

12

+10V DC

–

13

0-10V In(1)

Not Active

14
15

Analog Common –
Not Active
4-20mA In (1)

16

RS485 (DSI)
Shield

For digital inputs. Electronically isolated with digital inputs from analog I/O.
Program with A051 [Digital In1 Sel].
Program with A052 [Digital In2 Sel].
Drive supplied power for digital inputs.
Maximum output current is 100mA.
Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.
For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.
For 0-10V In or 4-20mA In. Electronically isolated with analog inputs from digital I/O.
For external 4-20mA input supply
(input impedance = 250 ohm).
Terminal should be connected to safety ground - PE when using the RS485 (DSI) communications port.

(1)

–

Only one analog frequency source may be connected at a time. If more than one reference is connected at the same time, an undetermined frequency reference will result.

14
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Control Wiring
PowerFlex 40
Enable
Jumper

• The control logic is 24V DC and can be set for either Sink or
Source control via a DIP switch setting.

(4)

01
02

• Control terminal screws are sized for a conventional blade screw
driver.

03
SNK

SRC

04

• I/O Terminals 1, 2 and 3 are dedicated for Stop, Start and
Reverse operation respectively. These I/O Terminals can be
programmed for 2- or 3-Wire operation to meet application
requirements.

05
06
07
08
09

• I/O Terminals 5, 6, 7 and 8 are programmable and provide added
flexibility. Programmable functions include Local Control, Jog,
Second Accel/Decel, Clear Fault, Preset Frequencies, RS485
Control and Auxiliary Fault.
• Speed can be controlled via a 0-10V input and/or 4-20 mA input.
Both inputs are independently isolated from the rest of the drive
and can be used for applications such as PID. Voltage input can
be programmed for bipolar operation.
• The drive is shipped with a jumper installed between I/O
Terminals 01 and 11 to allow out of box operation from the
keypad.

+24V
11
+10V

12
13
14

Relay N.O.
Relay Common
Relay N.C.

R1

0-10V

R2

0/4-20mA

15
16
17

R3
30V DC
50mA
Non-inductive
0-10V

0-20mA
R1 R2 R3

Analog Output Select

18
19

Stop

Typical
SRC Wiring

(1)(4)

Start/Run FWD

Typical
SNK Wiring

(2)

Direction/Run REV
Digital Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Opto Common
+24V DC
+10V DC
0-10V (or ±10V) Input
Analog Common
Pot must be
1-10k ohm
2 Watt Min.

4-20mA Input
Analog Output

Common

Opto Output 1

(3)
24V

Opto Output 2
RS485 Shield

ENBL

01 02 03 04 05 06 07 08 09
SNK
11 12 13 14 15 16 17 18 19

Enable
Jumper

(4)

RS485
(DSI)

SRC

Factory Installed Jumper
No.
R1
R2
R3

Signal
Relay N.O.
Relay Common
Relay N.C.

1

Default
Fault
–
Fault

Description
Normally open contact for output relay.
Common for output relay.
Normally closed contact for output relay.

Analog Output Select
DIP Switch
Sink/Source
DIP Switch

0-10V

Sets analog output to either voltage or current. Setting must match A065 [Analog Out Sel].

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01
02
03
04
05
06
07
08
09
11

Stop
Start/Run FWD
Direction/Run REV
Digital Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Opto Common
+24V DC

Coast
Not Active
Not Active
–
Preset Freq
Preset Freq
Local
Jog Forward
–
–

The factory installed jumper or a normally closed input must be present for the drive to start.
Command comes from the integral keypad by default. To disable reverse operation, see A095 [Reverse Disable].

12

+10V DC

–

13

±10V In (1)

Not Active

14

Analog Common

–

For digital inputs. Electronically isolated with digital inputs from analog I/O and opto outputs.
Program with A051 [Digital In1 Sel].
Program with A052 [Digital In2 Sel].
Program with A053 [Digital In3 Sel].
Program with A054 [Digital In4 Sel].
For opto-coupled outputs. Electronically isolated with opto outputs from analog I/O and digital inputs.
Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100mA.
Referenced to Analog Common.
Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.
For external 0-10V (unipolar) or ±10V (bipolar) input supply (input impedance = 100k ohm) or potentiometer
wiper.
For 0-10V In or 4-20mA In. Electronically isolated with analog inputs and outputs from digital I/O and opto
outputs.

15
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Control Wiring
No.
15

4-20mA In (1)

Default
Not Active

16

Analog Output

OutFreq 0-10

17
18
19

Opto Output 1
Opto Output 2
RS485 (DSI) Shield

MotorRunning
At Frequency
–

(1)

Signal

Description
For external 4-20mA input supply
(input impedance = 250 ohm).
The default analog output is 0-10V. To covert to a current value, change the Analog Output Select DIP Switch
to 0-20mA. Program with A065 [Analog Out Sel]. Max analog value can be scaled with A066 [Analog Out High].
Maximum Load:4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
Program with A058 [Opto Out1 Sel]
Program with A061 [Opto Out2 Sel]
Terminal should be connected to safety ground - PE when using the RS485 (DSI) communications port.

0-10V In and 4-20mA In are distinct input channels and may be connected simultaneously.
Inputs may be used independently for speed control or jointly when operating in PID mode.

16
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Specifications

Spec

Drive Ratings — PowerFlex 4
Output Ratings

Input Ratings
Voltage
Catalog Number kW (HP)
Amps Range
kVA
Amps
100 - 120V AC – 1-Phase Input, 0 - 230V 3-Phase Output
22A-V1P5N104
0.2 (0.25)
1.5
90-126
0.75
6.0
22A-V2P3N104
0.4 (0.5)
2.3
90-126
1.15
9.0
22A-V4P5N104
0.75 (1.0)
4.5
90-126
2.25
18.0
22A-V6P0N104
1.1 (1.5)
6.0
90-126
3.00
24.0
200 - 240V AC – 1-Phase Input, 0 - 230V 3-Phase Output (No Brake) ➌
22A-A1P4N103
0.2 (0.25)
1.4
180-265
0.7
3.2
22A-A2P1N103
0.4 (0.5)
2.1
180-265
1.05
5.3
22A-A3P6N103
0.75 (1.0)
3.6
180-265
1.8
9.2
22A-A6P8N103
1.5 (2.0)
6.8
180-265
3.4
14.2
22A-A9P6N103
2.2 (3.0)
9.6
180-265
4.8
19.6
200 - 240V AC – 1-Phase Input, 0 - 230V 3-Phase Output ➌
22A-A1P5N104
0.2 (0.25)
1.5
180-265
0.75
5.0
22A-A2P3N104
0.4 (0.5)
2.3
180-265
1.15
6.0
22A-A4P5N104
0.75 (1.0)
4.5
180-265
2.25
10.0
22A-A8P0N104
1.5 (2.0)
8.0
180-265
4.0
18.0
200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22A-B1P5N104
0.2 (0.25)
1.5
180-265
0.75
1.8
22A-B2P3N104
0.4 (0.5)
2.3
180-265
1.15
2.5
22A-B4P5N104
0.75 (1.0)
4.5
180-265
2.25
5.2
22A-B8P0N104
1.5 (2.0)
8.0
180-265
4.0
9.5
22A-B012N104
2.2 (3.0)
12.0
180-265
5.5
15.5
22A-B017N104
3.7 (5.0)
17.5
180-265
8.6
21.0
380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output
22A-D1P4N104
0.4 (0.5)
1.4
340-528
1.4
1.8
22A-D2P3N104
0.75 (1.0)
2.3
340-528
2.3
3.2
22A-D4P0N104
1.5 (2.0)
4.0
340-528
4.0
5.7
22A-D6P0N104
2.2 (3.0)
6.0
340-528
5.9
7.5
22A-D8P7N104
3.7 (5.0)
8.7
340-528
8.6
9.0

Branch Circuit Protection
Power Dissipation
140M Motor
Fuses ➊ Protectors ➋
Contactors Internal
Total
10
15
30
40

140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
140M-D8E-C32

100-C09
100-C12
100-C23
100-C37

10
9
12
12

25
30
50
70

6
10
15
25
30

140M-C2E-B40
140M-C2E-B63
140M-C2E-C16
140M-C2E-C16
140M-D8E-C25

100-C09
100-C09
100-C12
100-C16
100-C23

10
9
12
16
11

25
30
50
80
110

10
10
15
30

140M-C2E-B63
140M-C2E-B63
140M-C2E-C16
140M-D8E-C20

100-C09
100-C09
100-C12
100-C23

10
9
12
16

25
30
50
80

3
6
10
15
25
35

140M-C2E-B25
140M-C2E-B40
140M-C2E-C10
140M-C2E-C16
140M-C2E-C16
140M-F8E-C25

100-C09
100-C09
100-C09
100-C12
100-C16
100-C23

10
9
12
16
16
16

25
30
50
80
115
165

3
6
10
15
15

140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16

100-C09
100-C09
100-C09
100-C09
100-C16

15
13
13
17
14

30
40
60
90
145

➊ Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
➋ Refer to Bulletin 140M Motor Protectors Selection Guide, publication 140-SG001... to determine the frame and breaking capacity required for your application.
➌ 200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114 or N103 to N113.

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

17

Specifications
Drive Ratings — PowerFlex 40
Output Ratings

Input Ratings
Voltage
Catalog Number kW (HP)
Amps Range
kVA
100 - 120V AC – 1-Phase Input, 0 - 230V 3-Phase Output
22B-V2P3N104
0.4 (0.5)
2.3
90-132
1.15
22B-V5P0N104
0.75 (1.0)
5.0
90-132
2.45
22B-V6P0N104
1.1 (1.5)
6.0
90-132
3.0
200 - 240V AC – 1-Phase Input, 0 - 230V 3-Phase Output ➌
22B-A2P3N104
0.4 (0.5)
2.3
180-264
1.15
22B-A5P0N104
0.75 (1.0)
5.0
180-264
2.45
22B-A8P0N104
1.5 (2.0)
8.0
180-264
4.0
22B-A012N104
2.2 (3.0)
12.0
180-264
5.5
200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22B-B2P3N104
0.4 (0.5)
2.3
180-264
1.15
22B-B5P0N104
0.75 (1.0)
5.0
180-264
2.45
22B-B8P0N104
1.5 (2.0)
8.0
180-264
4.0
22B-B012N104
2.2 (3.0)
12.0
180-264
5.5
22B-B017N104
3.7 (5.0)
17.5
180-264
8.6
22B-B024N104
5.5 (7.5)
24.0
180-264
11.8
22B-B033N104
7.5 (10.0)
33.0
180-264
16.3
380 - 480V AC – 3-Phase Input, 0 - 460V 3-Phase Output
22B-D1P4N104
0.4 (0.5)
1.4
342-528
1.4
22B-D2P3N104
0.75 (1.0)
2.3
342-528
2.3
22B-D4P0N104
1.5 (2.0)
4.0
342-528
4.0
22B-D6P0N104
2.2 (3.0)
6.0
342-528
5.9
22B-D010N104
4.0 (5.0)
10.5
342-528
10.3
22B-D012N104
5.5 (7.5)
12.0
342-528
11.8
22B-D017N104
7.5 (10.0)
17.0
342-528
16.8
22B-D024N104
11.0 (15.0) 24.0
342-528
23.4
460 - 600V AC – 3-Phase Input, 0 - 575V 3-Phase Output
22B-E1P7N104
0.75 (1.0)
1.7
414-660
2.1
22B-E3P0N104
1.5 (2.0)
3.0
414-660
3.65
22B-E4P2N104
2.2 (3.0)
4.2
414-660
5.2
22B-E6P6N104
4.0 (5.0)
6.6
414-660
8.1
22B-E9P9N104
5.5 (7.5)
9.9
414-660
12.1
22B-E012N104
7.5 (10.0)
12.2
414-660
14.9
22B-E019N104
11.0 (15.0) 19.0
414-660
23.1

Amps

Branch Circuit Protection
Power Dissipation
140M Motor
Fuses ➊ Protectors ➋
Contactors Internal
Total

9.0
20.3
24.0

15
35
40

140M-C2E-C16
140M-D8E-C20
140M-F8E-C32

100-C12
100-C23
100-C37

9
12
12

30
55
70

6.0
12.0
18.0
25.0

10
20
30
40

140M-C2E-B63
140M-C2E-C16
140M-D8E-C20
140M-F8E-C32

100-C09
100-C12
100-C23
100-C37

9
12
16
11

30
55
80
110

2.5
5.7
9.5
15.5
21.0
26.1
34.6

6
10
15
25
35
40
60

140M-C2E-B40
140M-C2E-C10
140M-C2E-C16
140M-C2E-C16
140M-F8E-C25
140M-F8E-C32
140M-G8E-C45

100-C07
100-C09
100-C12
100-C23
100-C23
100-C37
100-C60

9
12
16
16
16
28
28

30
55
80
115
165
225
290

1.8
3.2
5.7
7.5
13.0
14.2
18.4
26.0

3
6
10
15
20
25
30
50

140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
140M-D8E-C20
140M-F8E-C32

100-C07
100-C07
100-C09
100-C09
100-C23
100-C23
100-C23
100-C43

15
13
13
17
14
23
24
25

30
40
60
90
150
160
200
285

2.3
3.8
5.3
8.3
11.2
13.7
24.1

6
6
10
15
20
25
40

140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
140M-C2E-C16
140M-D8E-C25

100-C09
100-C09
100-C09
100-C09
100-C16
100-C23
100-C30

13
13
17
14
23
24
25

40
60
90
150
160
200
285

➊ Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
➋ Refer to Bulletin 140M Motor Protectors Selection Guide, publication 140-SG001... to determine the frame and breaking capacity required for your application.
➌ 200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N104 to N114 or N103 to N113.

18

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Specifications
Input/Output Ratings
Output Frequency: 0-240 Hz (Programmable)
Efficiency: 97.5% (Typical)

Approvals
0-400 Hz (Programmable)

LIST

ED 966X

UL
®

I ND

LIST

UL508C

CO N T E Q

C

ED 966X

UL
®

I ND

CSA 22.2

CO N T E Q

EMC Directive 89/336
LV:
EN 50178, EN 60204
EMC: EN 61800-3, EN 50081-1, EN 50082-2

Digital Control Inputs (Input Current = 6mA)
Analog Control Inputs
SRC (Source) Mode:
SNK (Sink) Mode:
4-20mA Analog: 250 ohm input impedance
18-24V = ON
0-6V = ON
0-10V DC Analog: 100k ohm input impedance
0-6V = OFF
18-24V = OFF
External Pot: 1-10k ohms, 2 Watt minimum
Control Output
Programmable Output (form C relay)
Opto Outputs
Analog Output (10-bit)
Resistive Rating: 3.0A at 30V DC, 3.0A at 125V AC, 3.0A at 240V AC
30V DC, 50 mA
0-10V, 1k ohm Min.
Inductive Rating: 0.5A at 30V DC, 0.5A at 125V AC, 0.5A at 240V AC
Non-inductive
4-20 mA, 525 ohm Max.
Fuses and Circuit Breakers
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
Recommended Circuit Breakers: HMCP circuit breaker or equivalent.
Protective Features
Motor Protection: I2t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)
Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage: 100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)
460-600V AC Input – Trip occurs at 1005V DC bus voltage (equivalent to 711V AC incoming line)
Under Voltage: 100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)
460-600V AC Input – If P042 = 1 “High Voltage” trip occurs at 487V DC bus voltage (344V AC incoming line);
If P042 = 0 “Low Voltage” trip occurs at 390V DC bus voltage (275V AC incoming line)
Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds
Dynamic Braking
Internal brake IGBT included with all ratings except No Brake drives (Cat. Nos. 22A-AxPxN103 or 22A-AxPxN113). Refer to page 11 for ordering
information.
Environment
Altitude:
1000 m (3300 ft) max. without derating
Ambient Operating Temperature
IP20:
–10 to 50 degrees C (14 to 122 degrees F)
NEMA 1:
–10 to 40 degrees C (14 to 104 degrees F)
Cooling Method Fan:
All drive ratings
Storage Temperature:
–40 to 85 degrees C (–40 to 185 degrees F)
Important: Drive must not be installed in an area where the ambient atmosphere contains
Atmosphere:
volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of
time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock (operating):
15G peak for 11ms duration (±1.0ms)
Vibration (operating):
1G peak, 5 to 2000 Hz
Control
Carrier Frequency
2-16 kHz. Drive rating based on 4 kHz.
Frequency Accuracy
Digital Input:
Within ±0.05% of set output frequency.
Analog Input:
Within 0.5% of maximum output frequency.
Analog Output:
±2% of full scale, 10-bit resolution
Speed Regulation - Open Loop with Slip
±2% of base speed across a 40:1 speed range.
Compensation:
1% of base speed across a 60:1 speed range.
Stop Modes:
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold and
S Curve.
Accel/Decel:
Two independently programmable accel and decel times. Each time may be programmed from 0 600 seconds in 0.1 second increments.
Intermittent Overload:
150% Overload capability for up to 1 minute
200% Overload capability for up to 3 seconds
Electronic Motor Overload Protection
Class 10 protection with speed sensitive response.

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

19

Parameter Descriptions

Parameter
Number
Display Group
d001
d002
d003
d004
d005
d006
d007-d009
d010
d012
d013
d014
d015
d016
d017
d018
d019
d020
d021
d022
d023
d024
d025
d026
d028

Parameter Name

Description

Output Freq
Commanded Freq
Output Current
Output Voltage
DC Bus Voltage
Drive Status
Fault x Code
Process Display
Control Source
Contrl In Status
Dig In Status
Comm Status
Control SW Ver
Drive Type
Elapsed Run Time
Testpoint Data
Analog In 0-10V
Analog In 4-20mA
Output Power
Output Power Fctr
Drive Temp
Counter Status
Timer Status
Stp Logic Status

Output frequency present at T1, T2 & T3 (U, V & W)
Value of the active frequency command
Output current present at T1, T2 & T3 (U, V & W)
Output voltage present at T1, T2 & T3 (U, V & W)
Present DC bus voltage level
Present operating condition of the drive
A code that represents a drive fault
The output frequency scaled by parameter A099 [Process Factor]
Displays the source of the Start Command and Speed Reference
Status of the control terminal block control inputs
Status of the control terminal block digital inputs
Status of the communications ports
Main Control Board software version
Used by Rockwell Automation field service personnel
Accumulated time drive is outputting power
The present value of the function selected in parameter A102 [Testpoint Sel]
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts)
The present value of the current at I/O Terminal 15 (0.0% = 4 mA, 100.0% = 20 mA)
Output power present at T1, T2 & T3 (U, V & W)
The angle in electrical degrees between motor voltage and motor current
Present operating temperature of the drive power section
The current value of the counter when counter is enabled
The current value of the timer when timer is enabled
When P038 [Speed Reference] is set to 6 “Stp Logic”, this parameter will display the current step
logic profile as defined by parameters A140-A147 [Stp Logic x]
Displays the current value of the motor torque current as measured by the drive

Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only

20 to drive rated volts
10 to 240 Hz
15 to 400 Hz
0.0 Amps to (Drive Rated Amps x 2) in units of 0.1 Amps
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 240.0 Hz
0.0 to 400.0 Hz
6 settings; Keypad, 3-Wire, 2-Wire, 2-Wire Level Sensitive, 2-Wire High Speed, Comm Port
7 settings; Keypad, 3-Wire, 2-Wire, 2-Wire Level Sensitive, 2-Wire High Speed, Comm Port,
Momentary FWD/REV
8 settings; Ramp-Clear Fault, Coast-Clear Fault, DC Brake-Clear Fault, DC Brake w/ShutoffClear Fault, Ramp, Coast, DC Brake, DC Brake w/Shutoff
10 settings; Ramp-Clear Fault, Coast-Clear Fault, DC Brake-Clear Fault, DC Brake w/ShutoffClear Fault, Ramp, Coast, DC Brake, DC Brake w/Shutoff, Ramp Stop w/EM Brake Control-Clear
Fault, Ramp Stop w/EM Brake Control
6 settings; Drive Potentiometer, Internal Freq, 0-10V Input/Remote Potentiometer, 4-20 mA Input,
Preset Freq 0-3, Communications Port
8 settings; Drive Potentiometer, Internal Freq, 0-10V Input/Remote Potentiometer, 4-20 mA Input,
Preset Freq 0-7, Communications Port, Step Logic, Analog In Mult
0.0 to 600.0 seconds
0.1 to 600.0 seconds
Used to reset drive to factory default settings
Sets the voltage class of 600V drives, Low Voltage (460/480V) or High Voltage (575/600V)

Based on Drive Rating
60 Hz
60 Hz
Based on Drive Rating
0.0 Hz
0.0 Hz
60.0 Hz
60.0 Hz
Keypad
Keypad

d29
Torque Current
Basic Program Group
P031
Motor NP Volts
P032
Motor NP Hertz
P033
P034

Motor OL Current
Minimum Freq

P035

Maximum Freq

P036

Start Source

P037

Stop Mode

P038

Speed Reference

P039
Accel Time 1
P040
Decel Time 1
P041
Reset To Defalts
P042
Voltage Class
Advanced Program Group
A051
Digital In1 Sel
A052
Digital In2 Sel

20

16 settings; Not Used, Accel 2 & Decel 2, Jog, Auxiliary Fault, Preset Frequencies, Local, Comm
Port, Clear Fault, Ramp Stop Clear Fault, Coast Stop Clear Fault, DC Brake Clear Fault, Jog
Forward, Jog Reverse, 10V In Control, 20 mA In Control, Analog Invert
27 settings; Not Used, Accel 2 & Decel 2, Jog, Auxiliary Fault, Preset Frequencies, Local, Comm
Port, Clear Fault, Ramp Stop - Clear Fault, Coast Stop - Clear Fault, DC Brake - Clear Fault, Jog
Forward, Jog Reverse, 10V In Control, 20 mA In Control, PID Disable, MOP Up, MOP Down,
Timer Start, Counter In, Reset Timer, Reset Counter, Reset Timer and Counter, Logic In1, Logic
In2, Current Limit2, Analog Invert

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Factory Default

Read Only

Ramp, CF (Clear Fault)
Ramp, CF (Clear Fault)

Drive Pot
Drive Pot
10.0 Secs
10.0 Secs
Ready/Idle
High Voltage (575/600V)
Preset Freq

Parameter Descriptions
Parameter
Number
A053
A054

Parameter Name

Description

Digital In3 Sel
Digital In4 Sel

27 settings; Not Used, Accel 2 & Decel 2, Jog, Auxiliary Fault, Preset Frequencies, Local, Comm
Port, Clear Fault, Ramp Stop - Clear Fault, Coast Stop - Clear Fault, DC Brake - Clear Fault, Jog
Forward, Jog Reverse, 10V In Control, 20 mA In Control, PID Disable, MOP Up, MOP Down,
Timer Start, Counter In, Reset Timer, Reset Counter, Reset Timer and Counter, Logic In1, Logic
In2, Current Limit2, Analog Invert
13 different settings for a variety of drive status conditions
23 different settings for a variety of drive status conditions
0.0 to 9999
23 settings; Ready/Fault, At Frequency, Motor Running, Reverse, Motor Overload, Ramp
Regulator, Above Frequency, Above Current, Above DC Voltage, Retries Exceeded, Above
Analog Voltage, Logic In1, Logic In2, Logic 1 & 2, Logic 1 or 2, Step Logic Out, Timer Out, Counter
Out, Above PF Angle, Analog Input Loss, Param Control, Non-Recoverable Fault, EM Brake
Control
0.0 to 9999
23 settings; Ready/Fault, At Frequency, Motor Running, Reverse, Motor Overload, Ramp
Regulator, Above Frequency, Above Current, Above DC Voltage, Retries Exceeded, Above
Analog Voltage, Logic In1, Logic In2, Logic 1 & 2, Logic 1 or 2, Step Logic Out, Timer Out, Counter
Out, Above PF Angle, Analog Input Loss, Param Control, Non-Recoverable Fault, EM Brake
Control
0.0 to 9999
Determines the logic (NO or NC) of the opto outputs, 4 settings - NO/NO, NC/NO, NO/NC, NC/NC
Sets the analog output signal mode, various settings

A055

Relay Out Sel

A056
A058

Relay Out Level
Opto Out1 Sel

A059
A061

Opto Out1 Level
Opto Out2 Sel

A062
A064
A065

Opto Out2 Level
Opto Out Logic
Analog Out Sel

A066
A067
A068
A069

Analog Out High
Accel Time 2
Decel Time 2
Internal Freq

A070

Preset Freq 0

A071

Preset Freq 1

A072

Preset Freq 2

A073

Preset Freq 3

A074
A075
A076
A077
A078
A079
A080

Preset Freq 4
Preset Freq 5
Preset Freq 6
Preset Freq 7
Jog Frequency
Jog Accel/Decel
DC Brake Time

A081
A082
A083
A084

DC Brake Level
DB Resistor Sel
S Curve %
Boost Select

A085
A086
A087
A088
A089
A090
A091
A092
A093
A094
A095

Start Boost
Break Voltage
Break Frequency
Maximum Voltage
Current Limit 1
Motor OL Select
PWM Frequency
Auto Rstrt Tries
Auto Rstrt Delay
Start At PowerUp
Reverse Disable

Factory Default

0 to 800%
0.0 to 600.0 seconds
0.1 to 600.0 seconds
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 240.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to (Value set in P035 [Maximum Freq]
0.1 to 600.0 seconds
0.0 to 90.0 seconds
0.0 to 99.9 seconds
0.0 to (Drive Rated Amps x 1.8)
Used to set percent duty cycle for external dynamic braking
0 to 100%
14 boost settings (in % of P031 [Motor NP Volts]), redefines the Volts per Hertz curve
15 boost settings (in % of P031 [Motor NP Volts]), redefines the Volts per Hertz curve
0.0 to 25.0%
0.0 to 100.0%
0.0 to 400.0 Hz
20 to Drive Rated Volts
0.1 to (Drive Rated Amps x 1.8)
3 settings; No Derate, Minimum Derate, Maximum Derate
2.0 to 16.0 kHz
0 to 9
0.0 to 300.0 seconds
2 settings; Disabled, Enabled
2 settings; Reverse Enabled, Reverse Disabled

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Local
Jog Forward

Ready/Fault
Ready/Fault
0.0
MotorRunning

0.0
At Frequency

0.0
NO/NO
Output Freq 0-10,
0V=0Hz
100%
20.0 Secs
20.0 Secs
60.0 Hz
60.0 Hz
0.0 Hz
0.0 Hz
5.0 Hz
5.0 Hz
10.0 Hz
10.0 Hz
20.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
10.0 Hz
10.0 Secs
0.0 Secs
0.0 Secs
Drive Rated Amps x 0.05
Disabled
0% (Disabled)
5.0 (2.5 for 5 HP drives)
5.0, CT (2.5 CT for
5-15 HP drives)
2.5%
25.0%
15.0 Hz
Drive Rated Volts
Drive Rated Amps x 1.5
No Derate
4.0 kHz
0
1.0 Secs
Disabled
Rev Enabled

21

Parameter Descriptions

Parameter
Parameter Name
Number
Advanced Program Group, Continued
A096
Flying Start En
A097
Compensation
A098
SW Current Trip
A099
Process Factor
A100
Fault Clear
A101
Program Lock
A102
Testpoint Sel
A103
Comm Data Rate
A104
Comm Node Addr
A105
Comm Loss Action
A106
Comm Loss Time
A107
Comm Format
A108
Language
A109
A110
A111
A112
A113
A114
A115
A116
A117
A118
A119
A120
A121
A122
A123
A124
A125
A126
A127
A128
A129
A130
A131
A132

Anlg Out Setpt
Anlg In 0-10V Lo
Anlg In 0-10V Hi
Anlg In4-20mA Lo
Anlg In4-20mA Hi
Slip Hertz @ FLA
Process Time Lo
Process Time Hi
Bus Reg Mode
Current Limit 2
Skip Frequency
Skip Freq Band
Stall Fault Time
Analog In Loss
10V Bipolar Enbl
Var PWM Disable
Torque Perf Mode
Motor NP FLA
Autotune
IR Voltage Drop
Flux Current Ref
PID Trim Hi
PID Trim Lo
PID Ref Sel

A133
A134
A135
A136
A137
A138
A139
A140-A147
A150-157
A160
A161
A162

PID Feedback Sel
PID Prop Gain
PID Integ Time
PID Diff Rate
PID Setpoint
PID Deadband
PID Preload
Stp Logic 0-7
Stp Logic Time 0-7
EM Brk Off Delay
EM Brk On Delay
MOP Reset Sel

22

Description

2 settings; Disabled, Enabled
4 settings; Disabled, Electrical, Mechanical, Both
Software instantaneous trip, 0.0 to (Drive Rated Amps x 2)
0.1 to 999.9
Resets a fault and clears the fault queue
Protects parameters against change by unauthorized personnel
Used by Rockwell Automation field service personnel
6 settings; 1200, 2400, 4800, 9600, 19.2K, 38.4K
1 to 247
4 settings; Fault, Coast to Stop, Stop, Continue Last Speed
0.1 to 60.0 seconds
6 settings; RTU 8-N-1, RTU 8-E-1, RTU 8-O-1, RTU 8-N-2, RTU 8-E-2, RTU 8-O-2
11 settings; English, Francais, Espanol, Italiano, Deutsch, Reserved, Portugues, Reserved,
Reserved, Nederlands
0.0/100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 100.0%
0.0 to 10.0 Hz
0.00 to 99.99
0.00 to 99.99
0/1
0.1 to (Drive Rated Amps x 1.8)
0 to 400 Hz
0.0 to 30.0 Hz
6 settings; 60 Seconds, 120 Seconds, 240 Seconds, 360 Seconds, 480 Seconds, Fit Disabled
7 settings; Disabled, Fault (F29), Stop, Zero Ref, Min Freq Ref, Max Freq Ref, Int Freq Ref
2 settings; Uni-Polar In, Bi-Polar In
2 settings; Enabled, Disabled
2 settings; V/Hz, Sensorless Vector
Drive Rated Amps x 0.1/2
3 settings; Ready/Idle, Static Tune, Rotate Tune
0.0 to 230.0 VAC
0.00 to Motor NP Volts
0.0 to 400.0
0.0 to 400.0
9 settings; PID Disabled, PID Setpoint, 0-10V Input, 4-20mA Input, Comm Port, Setpoint - Trim,
0-10V - Trim, 4-20mA - Trim, Comm - Trim
3 settings; 0-10V Input, 4-20mA Input, Comm Port
0.00 to 99.99
0.0 to 999.9 Seconds
0.00 to 99.99 (1/Secs)
0.0 to 100.0%
0.0 to 10.0%
0.0 to 400.0 Hz
0001 to BAFF
0.0 to 999.9 Seconds
0.01/10.00 Secs
0.01/10.00 Secs
2 settings; Zero MOP Ref, Save MOP Ref

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Factory Default

Disabled
Electrical
0.0 (Disabled)
30.0
Ready/Idle
Unlocked
400
9600
100
Fault
5.0 Secs
RTU 8-N-1
English
100.0%
0.0%
100.0%
0.0%
100.0%
2.0 Hz
0.00
0.00
Disabled
Drive Rated Amps x 1.5
0 Hz
0.0 Hz
60 Seconds
Disabled
Uni-Polar In
Enabled
Sensrls Vect
Drive Rated Amps
Ready/Idle
Based on Drive Rating
Based on Drive Rating
60.0
0.1
PID Disabled
0-10V Input
0.01
0.1
0.01
0.0%
0.0%
0.0
00F1
30.0
2.0 Secs
2.0 Secs
Zero MOP Ref

Dimensions
Approximate Dimensions
A
D

C

F

E BG

5.5 (0.22)

Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
Frame
A
B
C

A
80 (3.15)
100 (3.94)
130 (5.1)

B➊
152 (5.98)
180 (7.09)
260 (10.2)

C
136 (5.35)
136 (5.35)
180 (7.1)

D
67 (2.64)
87 (3.43)
116 (4.57)

E
140 (5.51
168 (6.61)
246 (9.7)

F
59.3 (2.33)
87.4 (3.44)
–

G➋
185 (7.28)
213 (8.39)
320 (12.6)

Shipping Weight
1.4 (3.1)
2.2 (4.9)
4.3 (9.5)

➊ Overall height of standard IP 20/Open Type Drive.
➋ Overall height of drive with IP 30/NEMA 1/UL Type 1 option kit installed.

Ratings are in kW and (HP).
PowerFlex 4 — Frame
A

120V AC – 1-Phase
0.2 (0.25)
0.4(0.5)

240V AC – 1-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)

B

0.75 (1.0)
1.1 (1.5)

1.5 (2.0)

PowerFlex 40 — Frame 120V AC – 1-Phase
B
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)

240V AC – 1-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)

C

2.2 (3.0)

240V AC – 3-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)

240V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10.0)

480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)

480V AC – 3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)

600V AC – 3-Phase
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)

23
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Dimensions
Flange Mount Drive
8
(0.31)

114
(4.49)

175
(6.89)

5.3
(0.21)

92.8
(3.65)

145
(5.71)

54.7
(2.15)

195
(7.68)
179
(7.05)

210
(8.27)

97.5
(3.84)

16
(0.63)

49
(1.93)

8
(0.31)

98
(3.86) 130
(5.12)

Frame A — PowerFlex 4 only
119.3
(4.70)
214
(8.43)

145
(5.71)

6.5
(0.26)

244
(9.61)

94.3
(3.71)

63.1
(2.48)

23.5
(0.93)

197
(7.76)
210
(8.27)

225
(8.86)

250
(9.84)

98.5
(3.88)
5.3
(0.21)
22B-CCB
31
(1.22)

14
(0.55)

49
(1.93)

98
(3.86)

7.5
(0.30)
160
(6.30)

Frame B— PowerFlex 4 and PowerFlex 40

130.3
(5.13)
300
(11.81)

138.2
(5.44)

5.3
(0.21)

164
(6.46)

8
(0.31)

105.8
(4.17)

307.5
(12.11)

230.6
(9.08)

291.5
(11.48)

325
(12.8)

153.8
(6.06)

76.9
(3.03)

90
(3.54)

22B-CCC
180
(7.09)

8
(0.31)

Frame C—PowerFlex 40 only

24

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Dimensions
IP 30/NEMA Type 1/UL Type 1 Option Kit without Communication Options
PowerFlex 4 uses Frames A & B. PowerFlex 40 uses Frames B & C.
59.2
(2.33)
40.0
(1.57)
20.7
(0.81)

∅ 22.2
(0.88)

34.0
(1.34)

75.3
(2.96)
33.0
(1.30)

Frame A — 22-JBAA

79.1 (3.11)
64.1 (2.52)
40.6 (1.60)
25.6 (1.01)

107.0 (4.21)
66.0 (2.60)
24.0 (0.94)

∅ 22.2
(0.87)

∅ 28.5
(1.12)
∅ 22.2
(0.87)

152.2
(5.99)

109.9
(4.33)

111.2
(4.38)

74.3
(2.93)
60.0
(2.36)

33.0
(1.30)

Frame C — 22-JBAC

Frame B — 22-JBAB

PowerFlex 40 IP 30/NEMA 1/UL Type 1 Option Kit with Communication Option
25.0
(0.98)

25.0
(0.98)

108.7 (4.28)
92.2 (3.63)
69.2 (2.72)
45.7 (1.80)

77.5 (3.05)
50.0 (1.97)
22.5 (0.89)

∅ 22.2
(0.87)

22.2 (0.87)

∅ 28.5
(1.12)
∅ 22.2
(0.87)

179.8
(7.08)

134.3
(5.29)

144.8
(5.70)

105.3
(4.15)
64.0
(2.52)

Frame B — 22-JBCB

76.3
(3.00)

109.8
(4.32)
60.0
(2.36)

Frame C — 22-JBCC

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

25

Dimensions
Dynamic Brake Resistors
Dimensions are in millimeters and (inches)
Frame A

Frame B

30.0
(1.18) 60.0
(2.36)

31.0
(1.22)

59.0
(2.32)

Frame

Catalog Number

A

AK-R2-091P500, AK-R2-047P500, AK-R2-360P500

B

AK-R2-030P1K2, AK-R2-120P1K2

C

US

C

US

17.0
(0.67)

61.0
(2.40)

335.0
(13.19)

386.0
(15.20)

405.0
(15.94)

AUTOMATION

ROCKWELL

316.0
(12.44)

ROCKWELL
AUTOMATION

SURFACES MAY BE

13.0
(0.51)

Bulletin 1321-3R Series Line Reactors
Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
A
B

E

D
C

26

Catalog Number
1321-3R2-A
1321-3R2-B
1321-3R4-A
1321-3R4-B
1321-3R4-C
1321-3R8-A
1321-3R8-B
1321-3R8-C
1321-3R12-A
1321-3R12-B
1321-3R18-A
1321-3R18-B
1321-3R25-A
1321-3R35-A

A
112 (4.40)
112 (4.40)
112 (4.40)
112 (4.40)
112 (4.40)
152 (6.00)
152 (6.00)
152 (6.00)
152 (6.00)
152 (6.00)
152 (6.00)
152 (6.00)
183 (7.20)
193 (7.60)

B
104 (4.10)
104 (4.10)
104 (4.10)
104 (4.10)
104 (4.10)
127 (5.00)
127 (5.00)
127 (5.00)
127 (5.00)
127 (5.00)
133 (5.25)
133 (5.25)
146 (5.76)
146 (5.76)

C
70 (2.75)
70 (2.75)
76 (3.00)
76 (3.00)
86 (3.38)
76 (3.00)
76 (3.00)
85 (3.35)
76 (3.00)
76 (3.00)
79 (3.10)
86 (3.40)
85 (3.35)
91 (3.60)

D
50 (1.98)
50 (1.98)
50 (1.98)
50 (1.98)
60 (2.35)
53 (2.10)
53 (2.10)
63 (2.48)
53 (2.10)
53 (2.10)
54 (2.13)
63 (2.48)
60 (2.35)
66 (2.60)

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

E
37 (1.44)
37 (1.44)
37 (1.44)
37 (1.44)
37 (1.44)
51 (2.00)
51 (2.00)
51 (2.00)
51 (2.00)
51 (2.00)
51 (2.00)
51 (2.00)
76 (3.00)
76 (3.00)

Weight
1.8 (4)
1.8 (4)
1.8 (4)
1.8 (4)
2.3 (5)
3.1 (7)
3.6 (8)
4.9 (11)
4.1 (9)
4.5 (10)
4.1 (9)
5.4 (12)
4.9 (11)
6.3 (14)

Dimensions
EMC Line Filters

Frame A EMC Line Filters – Dimensions are in millimeters and (inches)
Catalog Numbers: 22-RF5P7-AS, -AL; 22-RF9P5-AS, -AL; 22-RF010-AL
29.8
(1.17)

50
(1.97)

80
60 (3.15)
(2.36)

Frame B EMC Line Filters – Dimensions are in millimeters and (inches)
Catalog Numbers: 22-RF012-BS, -BL; 22-RF018-BS; 22-RF021-BS, -BL
29.8
(1.17)

220
(8.66)

50
(1.97)

100
78 (3.94)
(3.07)

217
(8.54)

208
(8.19)

17.8
(0.70)

216
(8.50)

5.5 (0.22)

24
(0.94)

229
(9.02)

17.8
(0.70)

24.0
(0.94)

5.5 (0.22)

Frame C EMC Line Filters – Dimensions are in millimeters and (inches)
Catalog Numbers: 22-RF015-CL; 22-RF018-CS, -CL; 22-RF024-CL; 22-RF025-CL; 22-RF026-CS, -CL; 22RF034-CS, -CL
32
(1.26)

60
(2.36)

130
90 (5.12)
(3.54)

297
(11.69)

309
(12.17)
297
(11.69)

17
(0.67)

30
(1.18)

5.5 (0.22)

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

27

Dimensions
Human Interface Module (HIM) Dimensions
NEMA Type 1 Bezel – Dimensions are in millimeters and (inches)
Catalog Number: 22-HIM-B1
93
(3.66)

25.2
(0.99)

11.1
(0.44)

NEMA Type 4X/12 Remote (Panel Mount) Small HIM
– Dimensions are in millimeters and (inches)
Catalog Number: 22-HIM-C2S
25,0
(0.98)

93,0
(3.66)

mm
(in.)

180,0
(7.08)

180
(7.09)
2.0m

2m

67
(2.64)

67
(2.64)

60
(2.36)

60
(2.36)

154
(6.06)

154
(6.06)
4.8
(0.19)

4.8
(0.19)

77
(3.03)

77
(3.03)
19.1
(0.75)

19.1
(0.75)

23.5
(0.93)

23.5
(0.93)

NEMA Type 4X/12 Remote (Panel Mount) HIM – Dimensions are in millimeters and (inches)
Catalog Number: 22-HIM-C2
17.6
(0.69)

78
(3.07)
66
(2.60)

104
(4.09)

194
(7.64)

220
(8.66)

2.9m

125
(4.92)
60.5
(2.38)
19.1
(0.75)

38
(1.50)

4.8
(0.19)

28

Shaded areas are applicable to PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Shaded areas denote options for PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

29

30

Shaded areas denote options for PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

Shaded areas denote options for PowerFlex 40 only.
For further information visit: www.abpowerflex.com or www.ab.com/support/abdrives

31

The Allen-Bradley PowerFlex family of AC drives provides a single-source solution for virtually any drive application
requirement ranging from 0.2 to 3,000 kW (0.25 to 4,000 hp). Significant commonality across multiple platforms
including networks, operator interface, programming and hardware make PowerFlex drives easy to start up, operate and
maintain. Multi-lingual programming, operator interface text and voltage-sensitive defaults in PowerFlex drives will help
global OEMs and end-users save time and money during set-up, integration and maintenance of virtually any automation
system.
Rockwell Automation supports drive users whenever and wherever needed, providing drive specialists and manufacturing
expertise for unmatched service and support around the globe. In fact, one of every five Rockwell Automation employees
is in the field with users every day. Rockwell Automation also offers a full spectrum of value-added services and expertise
to help simplify maintenance and enhance productivity.
Rockwell Automation is committed to helping its customers meet ever-changing demands. PowerFlex drives illustrate our
commitment to user productivity through timely delivery of world-class products and continued backward compatibility
to minimize life-cycle costs. Count on Rockwell Automation to be your Complete Automation™ partner – now and in the
future.
For further information on PowerFlex drives visit our web site at: www.abpowerflex.com

PowerFlex, Zero Stacking, DriveExplorer, DriveTools SP and
Complete Automation are trademarks of Rockwell Automation.
DeviceNet is a trademark of the Open DeviceNet Vendor
Association.

www.rockwellautomation.com
Corporate Headquarters
Rockwell Automation, 777 East Wisconsin Avenue, Suite 1400, Milwaukee, WI, 53202-5302 USA, Tel: (1) 414.212.5200, Fax: (1) 414.212.5201
Headquarters for Allen-Bradley Products, Rockwell Software Products and Global Manufacturing Solutions
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36-BP 3A/B, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, 27/F Citicorp Centre, 18 Whitfield Road, Causeway Bay, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Headquarters for Dodge and Reliance Electric Products
Americas: Rockwell Automation, 6040 Ponders Court, Greenville, SC 29615-4617 USA, Tel: (1) 864.297.4800, Fax: (1) 864.281.2433
Europe: Rockwell Automation, Brühlstraße 22, D-74834 Elztal-Dallau, Germany, Tel: (49) 6261 9410, Fax: (49) 6261 1774
Asia Pacific: Rockwell Automation, 55 Newton Road, #11-01/02 Revenue House, Singapore 307987, Tel: (65) 351 6723, Fax: (65) 355 1733
U.S. Allen-Bradley Drives Technical Support
Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives

Publication 22-TD001B-EN-P — March 2004
Supersedes 22-TD001A-EN-P — January 2003

Copyright ® 2004 Rockwell Automation. All rights reserved. Printed in USA.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : Yes
Modify Date                     : 2004:04:01 09:37:44Z
Create Date                     : 1999:09:02 10:50:32Z
Page Count                      : 32
Creation Date                   : 1999:09:02 10:50:32Z
Mod Date                        : 2004:04:01 09:37:44Z
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : bscampbe
Metadata Date                   : 2004:04:01 09:37:44Z
Creator                         : bscampbe
Title                           : 22-TD001B-EN-P.fm
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu