TYPE

DESCRIPTION

LAMP

MANUF.

VOLT.

TOTAL
WATTS

BALLAST

A1

2X4 RECESSED, LENSED, GRID CEILING,
STATIC, FLUSH STEEL DOOR, TRIPLE
GASKETING, STEEL HOUSING WITH WHITE
ENAMEL, SPEC. GRADE

(2) F32T8/35000K

LITHONIA SP8

120

73

ELECTRONIC
RAPID START

120

67

DIMMING

120

232

MH DUAL

120

326

MH DUAL

6" SQUARE RECESSED DOWNLIGHT, CLEAR
SPECULAR REFLECTOR
DIRECTIONAL RECESSED DOWNLIGHT, DIE
CAST ALUMINUM OPTICAL ASSEMBLY
DIRECTIONAL RECESSED DOWNLIGHT, DIE
CAST ALUMINUM OPTICAL ASSEMBLY
DIRECTIONAL RECESSED DOWNLIGHT, DIE
CAST ALUMINUM OPTICAL ASSEMBLY

(2) F32TBX/3000K 4PIN

KURT VERSON

(2) PAR30 35MH/3000K +
(2) AR111 75W/3000K
(2) PAR30 70MH/3000K +
(2) AR111 75W/3000K

SISTEMA 8240MH30
SISTEMA 8240MH70

(2) AR111 75W/3000K

SISTEMA 8220-AR

120

150

NA

B5

CYLINDRICAL DOWNLIGHT, PENDANT
MOUNTED, CLEAR ALZAK REFLECTOR,
BLACK FINISH, MOUNTING HEIGHT 10' FROM
FLOOR

(1) F32TBX/3000K 4 PIN

DELRAY CP8100

120

32

DIMMING

B6

DECORATIVE 9"X9" SQUARE DOWNLIGHT,
CLEAR ACRYLIC FINISH WITH TRANSLUCENT
DIFFUSED COATING

(2) 32WTBX/3000K

LIGHTOLIER
SL207A

120

67

ELECTRONIC
RAPID START

B7

4" LOW VOLTAGE DOWNLIGHT, OPEN CLEAR
CONE, SPECULAR LOW IRIDESCENT FINISH,
LENS OPTION

(1) 20WMR16 FL

GOTHAM DLV

120

20

NA

B8

1" RECESSED DOWNLIGHT, LENSED
PINHOLE, FLOOD DISTRIBUTION

(1) 20WMR16 FL

GOTHAM DLV

120

20

NA

D1

CUSTOM DECORATIVE CHANDELIER,
FROSTED SQUARE LAMP SHADE, SQUARE
SHAPE, COVE FOR HOUSING CEILING
HIGHLIGHT FIXTURES, DARK BRONZE FINISH

(108) 40W HALOGEN G9
FROSTED

SEE DETAIL

120

4320

NA

D2

DECORATIVE PENDANT, BRONZE FINISH,
CLEAR AND FROSTED GLASS DIFFUSER

(1)40W HALOGEN G9
FROSTED

ZANEEN D4-1027

120

40

NA

O1

SPHERE SHAPED DIE-CAST ALUMINUM
HOUSING, PRISMATIC GLASS LENS,
RECTANGULAR WIDE DISTRIBUTION, DARK
BRONZE FINISH, UL LISTED FOR WET
LOCATIONS, FOUR FIXTURE HEADS, ONE
MOUNTED AT 19'-8", ONE AT 18'-8", TWO
MOUNTED ON SIDES AT 17'-8"

(1) PAR56 100MH/3000K

STERNER
CALLISTOR-12

120

125

MH DUAL

O2

LIGHT SPOT WITH 9 LED IN STAINLESS
STEEL, OPAL OPTIC COVER, TRANSFORMER
INCLUDE IN FIXTURE

(9) WHITE LEDS
INCLUDED WITH
FIXTURE

ANSORG
LED DOT

24

2

NA

O3

COMPACT LINE VOLTAGE FIXTURE, FULLY
ADJUSTABLE MOUNTING, SIPHONE
PROTECTION SYSTEM, BRONZE FINISH,
LANDSCAPE ACCENT, UL LISTED FOR WET
LOCATIONS

(1) PAR20 50W

LUMIERE
CORONADO 806

120

50

NA

O4

RERCESSED INGRADE WELL UPLIGHT
FIXTURE, CAST BRONZE DOOR, SPOT
DISTRIBUTION, DOUBLE LENS, UL LISTED
FOR WET LOCATION

(1) PAR56 100MH
ED17/3000K

HYDRELL M9700

120

125

MH DUAL

O5

INDIRECT RECESSED HOLE IN THE WALL
LIGHT NICHE FOR EXTERIOR STUCCO
CONSTRUCTION, UL LISTED FOR WE
LOCATIONS

(1) F32TBX/3000K 4 PIN

ENGINEERED
LIGHT PRODUCTS
HITW-EX

120

36

ELECTRONIC
RAPID START

B1
B2
B3
B4

O6

FLEXIBLE LED COMPACT LINEAR RAIL
FIXTURE, CLEAR POLYCARBONATE LENS, 8'
SECTIONS, UL LISTED FOR WET LOCATIONS,
INCLUDE TRANSFORMER

LED OPTION

ARDEE CLM

12

48

48

O7

SPHERE SHAPED DIE-CAST ALUMINUM
HOUSING, PRISMATIC GLASS LENS,
RECTANGULAR WIDE DISTRIBUTION, DARK
BRONZE FINISH, UL LISTED FOR WET
LOCATIONS, TWO FIXTURE HEADS, ONE
MOUNTED AT 15'-8", ONE MOUNTED AT 14'-8"

(1) PAR56 70MH/3000K

STERNER
CALLISTOR-12

120

88

MH DUAL

NA

STERNAR RTS

NA

NA

NA

NA

STERNAR RTS

NA

NA

NA

P1
P2

ROUND TAPERED STELL POLE, DARK
BRONZE FINISH, 20' POLE HEIGHT
ROUND TAPERED STELL POLE, DARK
BRONZE FINISH, 16' POLE HEIGHT

T1

8" OPEN TRACK FIXTURE, DIFFUSE
ALLUMINUM REFL., WIDE FLOOD
DISTRIBUTION

(1) PAR30 70MH/3000K

LITHONIA LTD
REFL

120

85

MH SINGLE

T2B

SURFACE MOUNTED 120V TRACK SYSTEM, 4'
SECTIONS, BLACK FINISH

NA

NORDIC
ALUMINUM

120

NA

NA

T3

LOW VOLTAGE DECORATIVE SPOT,
SURFACED MOUNTED, WHITE FNISH,
SQUARE SHAPED

(1)75W HALOGEN MR20

ZANEEN D9-2018

120

75

NA

A1

Specification Premium T8 Troffers

Lensed Troffers

Intended Use

Standard latch provides spring action.
Door latches and hinges from either side.

Specification premium, high performance, static T8 luminaires provide general illumination for recessed applications; ideal for restricted plenum spaces.

SP8

Improved performance – higher fixture
efficiency and reduced lamp image.

Static

Integral T-bar safety clips are standard
– no need to install separate clips.

Features

Aluminum door frames available, flush or
regressed.

Innovative low-profile design optimized
around T8 lamps, low-profile electronic
ballasts and T8 compact sockets.

Compatible with virtually all ceiling types.
Field trim modification kits also available.
See page 48.

Hemmed sides provide smooth edges for
easy handling during installation.

U.S. patents – 6,210,025; 6,231,213;
6,213,625; 2,288,471.

Standard steel door frame features precise flush-mitered corners.

Listings – UL Listed (standard). CSA Certified or NOM Certified (see Options).

Unique door frame design delivers a premium extruded appearance.
Housing and door frame interface provides a superior mechanical light seal
without the use of foam gasketing.

Ordering Information

Series
2SP8 2' wide

Example: 2SP8 G 3 32 A12 120 1/3 GEB

Frame type

Number
of lamps
2, 3, 41, 61
Not included.

Trim type
G Grid
F Flanged
MT Modular
fit-in

Lamp type
17 17W T8 (24")
U31 31W T8 U (15/8"
leg)
U316 31W T8 U (6" leg)2
32 32W T8 (48")
CF39 39W TT5 (16")
CF40 40W TT5 (24")
CF50 50W TT5 (24")
CF55 55W TT5 (24")

Voltage

(blank) Flush steel, white
FN Flush aluminum, natural
FM Flush aluminum, matte
black
FW Flush aluminum, white
RN Regressed aluminum,
natural
RM Regressed aluminum,
matte black
RW Regressed aluminum,
white

NOTES:
1 4- and 6-lamp models available with 17W and 32W
straight tubes only.
2 Not available on 3-lamp fixtures. Use U31.
3 Standard A12 diffuser has reverse apex technology.

Options
1/3
1/4
GEB

120
277
347
MVOLT*
Others available.

GEB10IS

* 120-277V. Must specify
GEB10IS.

GEB10RS
CSA
NOM

One 3-lamp ballast
One 4-lamp ballast
Electronic ballast,
<20% THD
T8 electronic ballast,
<10% THD, instant
start
T8 electronic ballast,
<10% THD, rapid start
CSA Certified
NOM Certified

See pages 90 & 91 for others.

Diffuser type
A12
A12125
RA125
A19
K20
84Y
PC1S
PC2S
PC3S

#12 pattern acrylic3
#12 pattern acrylic, .125" thick
#12 pattern acrylic, .125" thick (reverse apex)
#19 pattern acrylic, .156" thick
#20 pattern acrylic, .140" thick
Holophane 8224 with overlay
½"x½"x½" plastic cube louver, silver
1½"x1½"x1" plastic cube louver, silver with flange
¾"x¾"x½" plastic cube louver, silver

Availability and Dimensions
Nominal
Size

2x2

2x4

Series
2SP8
2SP8
2SP8
2SP8
2SP8
2SP8

Number
of Lamps
2
2
3
3
4
2, 3, 4, 6

Lamp
Type
17, U31, U316, CF39
CF40, CF50, CF55
17, U31, CF39
CF40, CF50, CF55
17
32

Height
in.(cm)
311/16 (9.3)
311/16 (9.3)
311/16 (9.3)
311/16 (9.3)
311/16 (9.3)
311/16 (9.3)

www.lithonia.com
keyword: SP8

Fluorescent / PSG8

35

Universal Start Fluorescent Lamps 32 Watts Bulb T8 Base Med. Bipin Product Number 0... Page 1 of 2
A1

Universal Start Fluorescent Lamps
Feature

T8 Medium Bipin featuring HIVISION® Phosphor

Watts

32

Bulb

T8

Base

Med. Bipin

Product Number

046677-27274-0

Ordering Code

F32T8/TL735/ALTO UPC

Package Quantity

25

Description

TL 735, 3500K

CRI

78

Design Lumens

2710

Nominal Length

48

Approximate Initial

2850

Lumens
Rated Avg. Life

20,000

(Hrs.),
3-Hr. Start
Rated Avg. Life

20,000

(Hrs.),
12-Hr. Start

Images

Literature

Other Information

+ Family Photo

+ Family Brochure

• Energy Saving Product

+ Product Logo

+ MSDS S09-98001

• Meets US Federal Minimum

+ Product Photo

Efficiency Standard

+ Printable Page
+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

Rated average life under specified test conditions with Programmed Start ballasts with lamps

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.
+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

For expected lamp lumen output, commercial ballast manufacturers can advise the appropriate

Ballast Factor for each of their ballasts when they are informed of the designated lamp. The Ballast

http://www.nam.lighting.philips.com/us/ecatalog/fluor/displayfluor.php?id=107

4/3/2005

Universal Start Fluorescent Lamps 32 Watts Bulb T8 Base Med. Bipin Product Number 0... Page 2 of 2

Factor is a multiplier applied to the designated lamp lumen output.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
+

Universal T8 lamps have full rated life on Instant Start, Rapid Start and Programmed Start

ballasts.
+
+

Features ALTO® Lamp Technology
High Color Rendering Lamps (CRI 70-79)
Information for this product last modified on November 20 2002.

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/fluor/displayfluor.php?id=107

4/3/2005

A1

R-2P32-TP
Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

Electrical Specifications

Lamp Type

Num.
of
Lamp
s
2
2

* F32T8
F32T8/U

Rated
Lamp
Watts

Min. Start
Temp
(°F/C)

Input
Current
(Amps)

Input
Power
(Watts)

Ballast
Factor

MAX
THD
%

Power
Factor

Lamp
Current
Crest Factor

B.E.F.

32
31.2

50/10
50/10

0.64
0.64

73
73

0.94
0.94

10
10

0.97
0.97

1.4
1.4

1.29
1.29

Wiring Diagram
LINE

BLACK
WHITE
YELLOW
YELLOW

MARK III
Magnetic
Rapid Start
Series
120
60 HZ
Active

Enclosure
BLUE
BLUE
RED
RED

BALLAST

H

LAMP
W

LAMP

M
L

CASE "T"

Diag. 21
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)

Enclosure Dimensions

Standard Lead Length (inches)
Black
White
Blue
Red
Yellow
Gray
Violet

in.
20
20
24
24
36

cm.
50.8
50.8
61
61
91.4
0
0

in.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White

cm.
0
0
0
0
0
0
0

OverAll (L)
9.50 "
9 1/2
24.1 cm

Width (W)
2.375 "
2 3/8
6 cm

Height (H) Mounting (M)
1.5 "
8.90625 "
1 1/2
8 29/32
3.8 cm
22.6 cm

Revised 08/14/2003
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

Section H fronts_UG 12/6/02 11:58 PM Page 15

B1
Socket
Bracket

Alzak
Reflector

Lamp
(By Others)

Vented
Top

Venting
Slot

Vertical
Safety Full Lens Trim Square Aperture
Trim
Adjustment Chain (Optional)
Frame

Rail
Support (2)

Cone Retaining
Spring

H8643

H23

Shallow Depth, Wide Beam Downlight
One 26-32-42W Triple Tube Compact Fluorescent
6" Square Parabolic Trim
Custom (2) 32W Triple Tube
Compact Fluorescent,
consulted manufacture.
Optics and Applications
The socket is mounted horizontally in an ellipsoidal primary
reflector for wide distribution and reduced recess depth in
shallow plenums. Use in low to medium height ceilings for
corridors, entries and for general and area lighting.
Design Features
A steel housing protects and aligns reflectors and lamps.
The socket and ballast will accept all triple tube wattages
interchangeably. The square trim is stabilized by a
proprietary steel web to prevent racking and is held to the
ceiling by constant pressure springs. Maximum ceiling
thickness 11/2". Ballast and lamp service from below.
Finish
Housings and structural parts are painted matte black to
suppress stray light leaks. Standard trims are anodized
Softglow® clear. Special finishes, textures and colors are
available, see below under Accessories.
Trim Textures
Textured trims create a subtle new aperture appearance.
Select among different embossed patterns to match the
ambiance of the space being illuminated. Refer to Squares
brochure for descriptive photos.

Dimensions and Lamps

D

General
Fixtures are pre-wired, UL and C-UL listed for eight wire
75°C branch circuit wiring. Union made IBEW. Luminaire
Efficiency Rating (LER) data is in the photometric directory
located in Section Z.

A

B
A
Number Depth
1

H8643

C

B
C
Aperture Width

6 " sq.
6 /2"
165mm 153mm

D
Length

Lamps

1

13 /2"
19"
26-32-42W TripleTube
343mm 483mm compact fluorescent

Brightness
Number

Lamps

85°

75°

65°

55°

45°

H8643

32W T/E Osram/Syl
32W PL-T Philips
42W PL-T Philips
42W T/E Osram/Syl

31
37
40
53

97
108
151
185

203
218
273
367

1221
6698
6857
4566

10019
13729
19941
17420

Data in footlamberts. Photometer readings, Maximum Brightness Method.

Matching Square Units
Vertical lamp fluorescent
Low voltage
PAR lamps
Directional
Halogena, A lamps
Tungsten halogen
Metal halide
Wall washer

Page
Pages
Pages
Page
Page
Page
Pages
Page

Ballasts
Fully electronic, microprocessor controlled with programmed
start to assure rated lamp life. Input voltage ranges from
120V through 277V. Operates 26, 32 or 42W lamps
interchangeably. Power factor .98, starting temperature
0°F (-18°C), THD<10%. Pre-heat start < 1.0 second. End
of lamp life protection. Rated for > 50,000 starts.

H22
H5, H6
H7, H8, H9
H9
H10
H11
H26, H27, H28
H37

Accessories
R2 26" support rails.
WT White trim flange.
WHT White complete trim.
R5 52" support rails.
SB Softglow black.
BP Ball Peen texture.
SG Softglow gold.
CG Corrugated texture.
SH Softglow mocha.
DS Distressed texture.
SP Softglow graphite.
WV Woven texture.
ST Softglow titanium.
LL Linear spread lens.
SW Softglow wheat.
LP Large prism lens.
SY Softglow pewter.
MP Microprism lens.
V347 347 volt ballast.
SZ Softglow bronze.
BR Bright trim finish.
FC Four cell cross baffle.
FR Frosting on lens.
DM Dimming ballast.
F
Fuse.
Specify watts and volts.
EM Emergency power includes integral charger light
and test switch visible through aperture. Battery
operation for 90 minutes.
FLT6 Full lens trim, specify lens type, e.g. H8643-FLT6LL.
WRL Wattage restriction label, specify wattage.

Kurt Versen Company

Point Source Lighting
Westwood, New Jersey 07675

Section H backs_UG 12/3/02 1:43 AM Page 15

H23 H8643
Performance Datachart
Single Unit Initial Footcandles, 30" Work Plane

Ceiling to Floor

Multiple Units Initial Footcandles, 30" Work Plane

H8643 One 32W Philips Triple Tube Read Top Data
H8643 One 42W Philips Triple Tube Read Bottom Data
10°

Nadir

20°

Ceiling 80%

30°

Walls 50%

Floor 20%

Spacing is Maximum Over Work Plane

FC

FC

Diam

FC

Diam

FC

Diam

Spacing

RCR 1

RCR 3

RCR 8

19
29

18
27

2'
2'

16
21

4'
4'

10
13

6'
6'

8'

7'
6'

23
38

19
32

15
21

21
18

13
19

2'
2'

11
15

5'
5'

7
10

8'
8'

9'

8'
7'

16
27

14
23

11
15

10
16

10
14

3'
3'

8
11

5'
5'

5
7

9'
9'

10'

9'
8'

12
20

10
17

8
11

8
12

8
11

3'
3'

7
9

6'
6'

4
6

10'
10'

11'

10'
9'

10
16

8
14

6
9

6
10

6
9

3'
3'

5
7

7'
7'

3
4

11'
11'

12'

12'
10'

8
13

6
11

5
7

Candlepower Distribution
85°

60

°

75°
120

0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90

65°

180
55°
240
45°

300
360

35°

420
90°

480

0°

540
600

5°

15°

25°

H8643 One 32W Triple Tube Philips
Eff. 39% S/M 0° 1.30 S/M 90° 1.14

°
*

°

75°
176

0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90

65°

264
55°
352
45°

440
528

35°

616
0°

704

90°
792
880

5°

15°

25°

H8643 One 42W Triple Tube Philips
Eff. 38% S/M 0° 1.07 S/M 90° 1.06

°
*

0°

90°

2400*

2400*

48

560
561
568
585
588
558
521
455
358
256
165
92
22
9
0
0
0
0
0

560
565
579
581
567
516
431
359
283
194
124
59
21
12
0
0
0
0
0

96

Vertical Angles
Initial Lamp Lumens

85°

88

See notes 2, 3 and 4.

Candelas

55°
192

288
336

35°

90°

384

0°

432
480

5°

15°

25°

H8643 One 32W Triple Tube Osram Sylvania
Eff. 33% S/M 0° 1.36 S/M 90° 1.24

90°
75

880
866
842
813
768
694
619
508
386
266
172
107
50
19
0
0
0
0
0

880
869
843
816
781
710
602
461
322
235
173
113
50
17
0
0
0
0
0

150

Kurt Versen Company, Westwood, New Jersey

45°

240

3200*

1 Softglow® cone multipliers: Gold x .89, Wheat x .87, Pewter x .73,
Mocha x .75, Graphite x .70, Titanium x .70, Bronze x .68.
2 Single unit Datachart pattern diameters are determined by the number
of degrees from each side of nadir. Therefore a 20° diameter
represents a total 40° pattern width at the work plane 30" above the
floor. Footcandle values are at the edge of that diameter.
3 Datachart spacing is rounded off to the nearest foot.
4 Data by IES methods. Compact fluorescent data vary due to lamp
lumen differences, power input, burning position, ambient temperature
and ballast characteristics. A modification factor should be applied.
5 Brightness data from the Average Luminance Method are inaccurate
for small aperture downlights. They are theoretical calculations derived
for large surfaces such as troffers. For a complete discussion refer to
section Z brochure Z1.

0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90

65°

144

0°

Notes

°

75°

3200*

Vertical Angles
Initial Lamp Lumens

85°

°

0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90

65°

225
55°
300
45°

450
35°
90°

600

0°

675
750

5°

15°

25°

H8643 One 42W Triple Tube Osram Sylvania
Eff. 35% S/M 0° 1.21 S/M 90° 1.13

457
466
464
469
475
448
457
396
316
233
136
52
13
8
6
0
0
0
0

457
460
470
476
473
452
399
337
255
170
99
34
14
9
7
0
0
0
0

*

75°

525

90°
2400*

Vertical Angles
° Initial
Lamp Lumens

85°

375

0°
2400*

0°

90°

3200*

3200*

757
750
751
746
725
718
632
529
408
288
185
102
40
15
0
0
0
0
0

757
761
741
704
647
625
569
454
315
194
128
81
36
15
0
0
0
0
0

Vertical Angles
° Initial
Lamp Lumens

*

Coefficients of Utilization
Ceiling

80%

Wall % 70
RCR

50

30

70%
10

50

10

50%
50

10

30%

0

50

10

0

Zonal Cavity Method - Floor Reflectance 20%

1

.43

.41

.40

.39

.41

.39

.39

.38

.38

.36

.35

2

.40

.38

.36

.35

.37

.34

.36

.34

.35

.33

.31

3

.38

.35

.33

.31

.34

.31

.33

.30

.32

.30

.29

4

.35

.32

.30

.28

.32

.28

.31

.27

.30

.27

.26

5

.33

.29

.27

.25

.29

.25

.28

.25

.28

.24

.24

6

.31

.27

.25

.23

.27

.23

.26

.22

.26

.22

.22

7

.29

.25

.23

.21

.25

.21

.24

.21

.24

.20

.20

8

.28

.23

.21

.19

.23

.19

.23

.19

.22

.19

.18

9

.26

.22

.19

.18

.22

.18

.21

.17

.21

.17

.17

10

.25

.20

.18

.16

.20

.16

.20

.16

.20

.16

.16

H8643 One 42W Philips
H8643 One 32W Philips x 1.00

H8643 One 42W Osram x .93
H8643 One 42W Osram x .86

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 1 of 2
B1

PL-T Triple 4-Pin Fluorescent Lamp
Feature

High color rendering, high efficacy lamps
feature 4-pin base for use with preheat, rapid
start, electronic and dimming circuits.
Featuring ALTO® Lamp Technology

Watts

32

Bulb

PL-T

Base

GX24q-3

Product

046677-26832-6

Number
Ordering

PL-T 32W/830/4P/ALTO

Code
Generic

CFTR32W/GX24q/830

Designation
Package

12

Quantity
Description

3000K

CRI

82

Avg. Hrs.

10,000

Life
Design

2040

Lumens
M.O.L.

5 5/8

Lumens

2400

Images

Literature

Other Information

+ ALTO Product Logo

+ ALTO Family Brochure

• Energy Saving Product

+ Family Photo

+ MSDS S08-98001

+ Printable Page

+ Product Photo

+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

This Product Contains Amalgam

+

High Color Rendering Lamp

Features ALTO® Lamp Technology
+ Rated average life under specified test conditions with Programmed Start ballasts with lamps
+

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 2 of 2

+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
Information for this product last modified on September 25, 2001

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

B1

IZT-2T42-M3-BS@120
Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

Electrical Specifications

Lamp Type

* CFM32W/GX24Q
CFM42W/GX24Q
CFTR57W/GX24Q
CFTR70W/GX24Q

Num.
of
Lamp
s
2
2
1
1

Rated
Lamp
Watts

Min.
Start
Temp
(°F/C)
50/10
50/10
50/10
50/10

32
42
57
70

MARK VII 0-10V
Electronic Dimming
Programmed Start
Series
120-277
50/60 HZ
Active

Input
Current
(Amps)

Input Power
(Watts)
(min/max)

Ballast Factor
(min/max)

MAX
THD
%

Power
Factor

Lamp
Current
Crest Factor

B.E.F.

0.63
0.82
0.55
0.67

19/75
18/98
18/66
18/80

0.05/1.00
0.05/1.00
0.05/1.00
0.05/1.00

10
10
10
10

0.99
0.99
0.99
0.99

1.4
1.4
1.7
1.7

1.33
1.02
1.52
1.25

Wiring Diagram

Enclosure

WIRING: (2) TRIPLE LAMPS
LINE
CLASS 1&2
CIRCUIT
10V, 0.5mA

BLACK
WHITE
VIOLET
(+)
GREY (-)
GREEN

BLUE
BALLAST Y E L L O W
RED

Green Terminal must be Grounded
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)

Enclosure Dimensions

Standard Lead Length (inches)
Black
White
Blue
Red
Yellow
Gray
Violet

in.
0
0
0
0
0
0
0

cm.
0
0
0
0
0
0
0

in.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White

cm.
0
0
0
0
0
0
0

OverAll (L)
6.28 "
6 7/25
16 cm

Width (W)
3.00 "
3
7.6 cm

Height (H) Mounting (M)
1.29 "
2.00 "
1 29/100
2
3.3 cm
5.1 cm

Revised 08/27/2003
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

IZT-2T42-M3-BS@120

Electrical Specifications
Notes:

Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

MARK VII 0-10V
Electronic Dimming
Programmed Start
Series
120-277
50/60 HZ
Active

Section I - Physical Characteristics
1.1 Ballast shall be physically interchangeable with standard electromagnetic or standard electronic ballasts, where applicable.
1.2 Ballast shall be available in a plastic/metal can or all metal can construction to meet all plenum requirements.
1.3 Ballast shall be provided with poke-in wire trap connectors or integral leads color coded per ANSI C82.11.
Section II - Performance Requirements
2.1 Ballast shall be Programmed Start.
2.2 Ballast shall be provided with integral protection circuitry to withstand connection of low voltage control leads to mains power supply. In
this event, ballast shall default to maximum light output.
2.3 Ballast shall contain auto restart circuitry in order to restart lamps without resetting power.
2.4 Ballast shall operate from 50/60 Hz input source of 120V or 277V with sustained variations of +/- 10% (voltage and frequency) with no
damage to the ballast. IntelliVolt models shall operate from 50/60 Hz input source of 120V through 277V with sustained variations of +/- 10%
(voltage and frequency) with no damage to the ballast.
2.5 Ballast shall be high frequency electronic type and operate lamps at a frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
2.6 Ballast shall have a Power Factor greater than 0.98 at full light output and greater than 0.90 throughout the dimming range for primary lamp.
2.7 Ballast shall have a maximum ballast factor of 1.00 (1.18 for HL versions) at maximum light output and 0.03 at minimum light output for
primary lamp application.
2.8 Ballast shall provide for a Lamp Current Crest Factor of 1.7 or less throughout the dimming range in accordance with lamp manufacturer
recommendations.
2.9 Ballast input current shall have Total Harmonic Distortion (THD) of less than 10% when operated at nominal line voltage with primary lamp.
2.10 Ballast shall have a Class A sound rating.
2.11 Ballast shall have a minimum starting temperature of 10C (50F) for primary lamp.
2.12 Ballast shall provide Lamp EOL Protection Circuit for all T5, T5/HO, CFL lamps, and T8 lamps operating on 4-lamp ballast.
2.13 Ballast shall control lamp light output from 100% - 3% relative light output for T8 and CFL lamps and 100% - 1% relative light output for
T5/HO lamps.
2.14 Ballast shall ignite the lamps at any light output setting without first going to another output setting.
2.15 Ballast shall tolerate sustained open circuit and short circuit output conditions without damage.
Section III - Regulatory Requirements
3.1 Ballast shall not contain any Polychlorinated Biphenyl (PCB).
3.2 Ballast shall be Underwriters Laboratories (UL) listed, Class P and Type 1 Outdoor; and Canadian Standards Association (CSA) certified
where applicable.
3.3 Ballast shall comply with ANSI C62.41 Category A for Transient protection.
3.4 Ballast shall comply with ANSI C82.11 where applicable.
3.5 Ballast shall comply with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 18,
Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
Section IV - Other
4.1 Ballast shall be manufactured in a factory certified to ISO 9002 Quality System Standards.
4.2 Ballast shall carry a five-year warranty from date of manufacture against defects in material or workmanship, including replacement, for
operation at a maximum case temperature of 70C.

4.3 Manufacturer shall have a fifteen-year history of producing electronic ballasts for the North American market.
4.4 Ballast shall be controlled by a Class 1 or Class 2 low voltage 0-10VDC controller.
4.5 Ballast shall be Advance Transformer part # _____________ or approved equal.

Revised 08/27/2003
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER - 10275 WEST HIGGINS ROAD
ROSEMONT, ILLINOIS 60018
TELEPHONE: (847) 390-5000 FAX: (847) 390-5109

B2
20

MULTIPLE LARGE

Toronto University Architecture Dept.

21

MULTIPLE LARGE

(MH)
8-7/8"

Multiple Large Four
8240-AR

4 x AR 111 75 W

8240-PAR

4 x PAR 30 75 W

8240-MH35

2 x AR 111 75 W +
2 x Metal Halide PAR 30 35 W

(PAR/AR)
7-3/8"

Newtown restaurant, Foti & Drouin designers

8240-MH70

Fixture to be oriented linearly as
12-5/8" x 12-5/8"
multiply large six below
but with
4 lamps.

13-3/4"

8240-4MH35 4 x Metal Halide PAR 30 35 W
2 x AR 111 75 W +
2 x Metal Halide PAR 30 70 W

8240-4MH70 4 x Metal Halide PAR 30 70 W
8340-PAR

4 x PAR 38 90W

8340-MH

4 x Metal Halide PAR 38 70W

13-3/4"

6 x PAR 30 75 W

8260-MH35

4 x AR 111 75 W +
2 x Metal Halide PAR 30 35 W

8260-MH70

4 x AR 111 75 W+
2 x Metal Halide PAR 30 70 W

8360-PAR

6 x PAR 38 90 W

8360-MH

2 x Metal Halide PAR 38 70W +

7-1/4"

6 x AR 111 75 W

8260-PAR

(PAR/AR)
7-3/8"

8260-AR

(MH)
8-7/8"

Multiple Large Six

6-1/2" x 38"
39"

4 x PAR 38 90 W

ACCESSORIES FOR MULTIPLE LARGE
1"

8211 Cross Baffle for PAR 30

These are standard configurations.
Custom configurations available upon request.

8311 Cross Baffle for PAR 38

8812 for PAR, AR 111
00 frosted
05 red
06 yellow
09 blue
24 clear
10

Protected MasterColor Ceramic Metal Halide Lamp 39 Watts Bulb PAR-30L Base Med. ... Page 1 of 2
B3

Protected MasterColor® Ceramic Metal Halide Lamp
Feature

PAR Style. Open or Enclosed Luminaires.
Lifetime Color Stability Within +/- 200K

Watts

39

Bulb

PAR-30L

Base

Med.

Product Number

046677-22330-5

Ordering Code

CDM35/PAR30L/M/FL

Package Quantity 6
Description

G, PAR WISO Flood 30 degrees
FadeBlock 7400 MBCP

ANSI

M130/O

Code/Ballast Ref.
CRI

81

Rated Avg. Life

9000

(Hrs.)
M.O.L.

4 3/4

Approximate

2200

Initial Lumens
Approximate

1760

Mean Lumens
CCT

3000

Images

Literature

Other Information

+ Family Photo

+ Family Brochure

+ Printable Page

+ Product Logo

+ MSDS S15-95005

+ View Compatible Ballasts

+ Product Photo

+ Photometric Data
+ Technical Data Sheet

+ Send this Link
+ Bookmark this Page
† Heat resisting glass bulb

Footnotes
MasterColor® Metal Halide Lamps are not recommended for use on dimmers and are not
warranted if used on dimmer systems.

+
+

"Operate only on thermally protected ballasts"

UV filtered design (Fade-Block™).
+ Click here for Recommended Warnings, Cautions and Operating Instructions.
+
+

Supply volts must be +/- 5% of rated ballast line volts for reactor type and +/- 10% for CWA or

electronic ballasts.
+

Requires a ballast specified or approved for Philips Metal Halide lamp or one designed to the

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=26

4/3/2005

Protected MasterColor Ceramic Metal Halide Lamp 39 Watts Bulb PAR-30L Base Med. ... Page 2 of 2

indicated ANSI Standard. A pulse ignitor is required. Sockets and wiring must withstand starting
pulse.
+

Approximate lumen output at 40% of lamp rated average life.

+

Approximate lumen values listed are for vertical operation of the lamp.

+

Rated average life is the life obtained, on the average, from large representative groups of lamps

in laboratory tests under controlled conditions at 10 or more operating hours per start. It is based
on survival of at least 50% of the lamps and allows for individual lamps or groups of lamps to vary
considerably from the average. For lamps with a rated average life of 24,000 hours, life is based on
survival of 67% of the lamps.
+

ANSI CODE RATING, E - Enclosed, O - Open, S - Open or Enclosed

+

Click here for specific product and ordering information on this lamp.

+

Heat resisting glass bulb

+

Excellent color rendition - up to 92 CRI
Information for this product last modified on June 22 2004.

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=26

4/3/2005

B2

Metal
Halide
Lamp Ballast

Catalog Number 71A50Y1
For 39W
M130
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA
3 X 4 CORE - 2 COIL UNIT
5.10 "
4.50"

0.7"

1.0"

A

B
MAX.

0.25" WIDE
2 SLOTS

3.95"
3.50"

4 HOLES
CLEARED
FOR #10
THRU-BOLTS

2.45"

2.80"

Capacitor: 7C100M30-R

2.90"

INPUT VOLTS
100 200
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±10%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
0.56 0.28
Open Circuit...............................................
1.30 0.70
Starting......................................................
0.50 0.25
UL TEMPERATURE RATINGS
Insulation Class
H(180°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-30°F or -35°C
NOM. OPEN CIRCUIT VOLTAGE
248
INPUT VOLTAGE AT LAMP DROPOUT...........................
70 140
INPUT WATTS
53
RECOMMENDED FUSE (Amps).....................................
3
2
CORE and COIL
Dimension (A)
0.85
Dimension (B)
1.95
Weight (lbs.)
3
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
10.0
Volts (min.)
280
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
1500
2 seconds
2500
Open Circuit Voltage Test (Volts)
223-273
Short-Circuit Current Test (Amps)
Secondary Current
0.60-0.74
Input Current..............................................

0.38 0.19
0.58 0.29

-

-

-

Wiring Diagram:
LAMP

CAP
LINE V
LINE V

X3

X1

IGNITOR
CAP

LAMP

LINE V

X2

COM
LINE V

Capacitance:
Dia/Oval Dim:
Height:
Temp Rating:

10
1.5
2.9
105°C

COM

COM

Fig. K

Ordering Information

Ignitor: LI533-H4

Order Suffix
500D.

Description
Ballast With Ignitor and Dry Film Capacitor

Ballast to Lamp Distance
(BTL) = 5 feet
Temp Rating: 105°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

04/15/02

B2,B3,B4

B3
20

MULTIPLE LARGE

Toronto University Architecture Dept.

21

MULTIPLE LARGE

(MH)
8-7/8"

Multiple Large Four
8240-AR

4 x AR 111 75 W

8240-PAR

4 x PAR 30 75 W

8240-MH35

2 x AR 111 75 W +
2 x Metal Halide PAR 30 35 W

(PAR/AR)
7-3/8"

Newtown restaurant, Foti & Drouin designers

8240-MH70

Fixture to be oriented linearly as
multiply large six below, but with four
12-5/8" x 12-5/8"
lamps.

13-3/4"

8240-4MH35 4 x Metal Halide PAR 30 35 W
2 x AR 111 75 W +
2 x Metal Halide PAR 30 70 W

8240-4MH70 4 x Metal Halide PAR 30 70 W
8340-PAR

4 x PAR 38 90W

8340-MH

4 x Metal Halide PAR 38 70W

13-3/4"

6 x PAR 30 75 W

8260-MH35

4 x AR 111 75 W +
2 x Metal Halide PAR 30 35 W

8260-MH70

4 x AR 111 75 W+
2 x Metal Halide PAR 30 70 W

8360-PAR

6 x PAR 38 90 W

8360-MH

2 x Metal Halide PAR 38 70W +

7-1/4"

6 x AR 111 75 W

8260-PAR

(PAR/AR)
7-3/8"

8260-AR

(MH)
8-7/8"

Multiple Large Six

6-1/2" x 38"
39"

4 x PAR 38 90 W

ACCESSORIES FOR MULTIPLE LARGE
1"

8211 Cross Baffle for PAR 30

These are standard configurations.
Custom configurations available upon request.

8311 Cross Baffle for PAR 38

8812 for PAR, AR 111
00 frosted
05 red
06 yellow
09 blue
24 clear
10

Protected MasterColor Ceramic Metal Halide Lamp 70 Watts Bulb PAR-30L Base Med. ... Page 1 of 2
B3

Protected MasterColor® Ceramic Metal Halide Lamp
Feature

PAR Style. Open or Enclosed Luminaires.
Lifetime Color Stability Within +/- 200K

Watts

70

Bulb

PAR-30L

Base

Med.

Product Number

046677-23221-5

Ordering Code

CDM70/PAR30L/M/FL

Package Quantity 6
Description

G, PAR WISO Flood 40 degrees
FadeBlock 10,000 MBCP

ANSI

M143/M98/O

Code/Ballast Ref.
CRI

82

Rated Avg. Life

9000

(Hrs.)
M.O.L.

4 3/4

Approximate

4850

Initial Lumens
Approximate

3880

Mean Lumens
CCT

3000

Images

Literature

Other Information

+ Family Photo

+ Family Brochure

+ Printable Page

+ Product Logo

+ MSDS S15-95004

+ View Compatible Ballasts

+ Product Photo

+ MSDS S15-95005
+ Photometric Data

+ Send this Link
+ Bookmark this Page
† Heat resisting glass bulb

+ Technical Data Sheet

Footnotes
+

ANSI CODE RATING, E - Enclosed, O - Open, S - Open or Enclosed

+

Rated average life is the life obtained, on the average, from large representative groups of lamps

in laboratory tests under controlled conditions at 10 or more operating hours per start. It is based
on survival of at least 50% of the lamps and allows for individual lamps or groups of lamps to vary
considerably from the average. For lamps with a rated average life of 24,000 hours, life is based on
survival of 67% of the lamps.
+

Approximate lumen values listed are for vertical operation of the lamp.

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=28

4/3/2005

Protected MasterColor Ceramic Metal Halide Lamp 70 Watts Bulb PAR-30L Base Med. ... Page 2 of 2

+

Click here for Recommended Warnings, Cautions and Operating Instructions.

+

Approximate lumen output at 40% of lamp rated average life.

+

Requires a ballast specified or approved for Philips Metal Halide lamp or one designed to the

indicated ANSI Standard. A pulse ignitor is required. Sockets and wiring must withstand starting
pulse.
+

Supply volts must be +/- 5% of rated ballast line volts for reactor type and +/- 10% for CWA or

electronic ballasts.
+

UV filtered design (Fade-Block™).

MasterColor® Metal Halide Lamps are not recommended for use on dimmers and are not
warranted if used on dimmer systems.

+
+

Excellent color rendition - up to 92 CRI

+

Heat resisting glass bulb

+

Click here for specific product and ordering information on this lamp.
Information for this product last modified on June 22 2004.

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=28

4/3/2005

B3

Metal
Halide
Lamp Ballast

Catalog Number 71A5282
For 70W
M98/M143
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA
3 X 4 CORE - 2 COIL UNIT
5.10 "
4.50"

0.7"

1.0"

A

B
MAX.

0.25" WIDE
2 SLOTS

3.95"
3.50"

4 HOLES
CLEARED
FOR #10
THRU-BOLTS

2.45"

2.80"

Capacitor: 7C080L33-R

2.90"

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±7%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
0.80 0.35
Open Circuit...............................................
1.90 0.80
Starting......................................................
0.55 0.25
UL TEMPERATURE RATINGS
Insulation Class
H(180°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
255
INPUT VOLTAGE AT LAMP DROPOUT...........................
90 208
INPUT WATTS
88
RECOMMENDED FUSE (Amps).....................................
4
2
CORE and COIL
Dimension (A)
1.45
Dimension (B)
2.75
Weight (lbs.)
5
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
8.0
Volts (min.)
280
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
2000
2 seconds
2500
Open Circuit Voltage Test (Volts)
230-280
Short-Circuit Current Test (Amps)
Secondary Current
0.95-1.25
Input Current..............................................

0.55 0.25
0.80 0.45

-

-

-

Wiring Diagram:
LAMP

CAP
LINE V
LINE V

X3

X1

IGNITOR
CAP

LAMP

LINE V

X2

COM
LINE V

Capacitance:
Dia/Oval Dim:
Height:
Temp Rating:

8
1.25
2.9
105°C

COM

COM

Fig. K

Ordering Information

Ignitor: LI533-H4

Order Suffix
500D.
510D.
600.
610.

Description
Ballast With Ignitor and Dry Film Capacitor
Ballast w/Welded Bracket, Ignitor, & Dry Film Capacitor
Ballast and Ignitor, No Capacitor
Ballast with Welded Bracket and Ignitor, No Capacitor

Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 105°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

11/08/00

B4
18

MULTIPLE LARGE

Designed for use in commercial spaces, like shops, restaurants,and displays, the
multiple downlights are suitable in all projects where directional lighting is desired.
Available in halogen, metal halide or a combination of both, the multiple is
a versatile solution for applications where more than one lamp type is needed.
This new serie of multi lamp downlights supports up to six independently
directional units.
Optical assemblies are adjustable in virtually all directions. This series are
supplied with new construction plaster frame and integral electronic transformers
and/or electronic ballasts, 120 volts (277-347 volts upon request).
Relamping is simple and does not require tools.

Directional recessed downlight provides
direct light.
Die cast aluminum optical assembly,
steel frame, body and fastener.
Uses PAR 30 and PAR 38 halogen, PAR 30,
PAR 38 metal halide and AR111 low voltage.
Available in grey.

19

MULTIPLE LARGE

1 x AR 111 75 W

8210-PAR

1 x PAR 30 75 W

8210-MH35

1 x Metal Halide PAR 30 35 W

8210-MH70

1 x Metal Halide PAR 30 70 W

8310-PAR

1 x PAR 38 90W

8310-MH

1 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

8210-AR

7-1/4"

Multiple Large Single

(MH)
8-7/8"

Toronto University Architecture Dept.

6-1/2"x 6-1/2"

7-1/4"

2 x PAR 30 75 W

8220-1MH35

1 x AR 111 75 W+Metal Halide PAR 30 35 W

8220-1MH70

1 x AR 111 75 W+Metal Halide PAR 30 70 W

8220-2MH35

2 x Metal Halide PAR 30 35 W

8220-2MH70

2 x Metal Halide PAR 30 70 W

8320-PAR

2 x PAR 38 90W

8320-MH

2 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

2 x AR 111 75 W

8220-PAR

7-1/4 "

8220-AR

(MH)
8-7/8"

Multiple Large Double

6-1/2" x 12-5/8"
13-3/4"

8230-PAR

3 x PAR 30 75 W

8230-1MH35

2 x AR 111 75 W+Metal Halide PAR 30 35 W

8230-1MH70

2 x AR 111 75 W+Metal Halide PAR 30 70 W

8230-3MH35

3 x Metal Halide PAR 30 35 W

8230-3MH70

3 x Metal Halide PAR 30 70 W

8330-PAR

3 x PAR 38 90W

8330-MH

3 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

3 x AR 111 75 W

6-1/2" x 19"

7-1/4"

8230-AR

(MH)
8-7/8"

Multiple Large Triple

20-1/8"

These are standard configurations. Custom configurations available upon request.
10

B4
18

MULTIPLE LARGE

Designed for use in commercial spaces, like shops, restaurants,and displays, the
multiple downlights are suitable in all projects where directional lighting is desired.
Available in halogen, metal halide or a combination of both, the multiple is
a versatile solution for applications where more than one lamp type is needed.
This new serie of multi lamp downlights supports up to six independently
directional units.
Optical assemblies are adjustable in virtually all directions. This series are
supplied with new construction plaster frame and integral electronic transformers
and/or electronic ballasts, 120 volts (277-347 volts upon request).
Relamping is simple and does not require tools.

Directional recessed downlight provides
direct light.
Die cast aluminum optical assembly,
steel frame, body and fastener.
Uses PAR 30 and PAR 38 halogen, PAR 30,
PAR 38 metal halide and AR111 low voltage.
Available in grey.

19

MULTIPLE LARGE

1 x AR 111 75 W

8210-PAR

1 x PAR 30 75 W

8210-MH35

1 x Metal Halide PAR 30 35 W

8210-MH70

1 x Metal Halide PAR 30 70 W

8310-PAR

1 x PAR 38 90W

8310-MH

1 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

8210-AR

7-1/4"

Multiple Large Single

(MH)
8-7/8"

Toronto University Architecture Dept.

6-1/2"x 6-1/2"

7-1/4"

2 x PAR 30 75 W

8220-1MH35

1 x AR 111 75 W+Metal Halide PAR 30 35 W

8220-1MH70

1 x AR 111 75 W+Metal Halide PAR 30 70 W

8220-2MH35

2 x Metal Halide PAR 30 35 W

8220-2MH70

2 x Metal Halide PAR 30 70 W

8320-PAR

2 x PAR 38 90W

8320-MH

2 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

2 x AR 111 75 W

8220-PAR

7-1/4 "

8220-AR

(MH)
8-7/8"

Multiple Large Double

6-1/2" x 12-5/8"
13-3/4"

8230-PAR

3 x PAR 30 75 W

8230-1MH35

2 x AR 111 75 W+Metal Halide PAR 30 35 W

8230-1MH70

2 x AR 111 75 W+Metal Halide PAR 30 70 W

8230-3MH35

3 x Metal Halide PAR 30 35 W

8230-3MH70

3 x Metal Halide PAR 30 70 W

8330-PAR

3 x PAR 38 90W

8330-MH

3 x Metal Halide PAR 38 70W

(PAR/AR)
7-3/8"

3 x AR 111 75 W

6-1/2" x 19"

7-1/4"

8230-AR

(MH)
8-7/8"

Multiple Large Triple

20-1/8"

These are standard configurations. Custom configurations available upon request.
10

B5

DELRAY

8" CYLINDER VERTICAL LAMP DOWNLIGHT

18"

Clear Alzak®

14" NOTE:

D1, D3, and EM

Black Baffle

Accessories
add 4” to height

Pendant mount
Cylinder

Splay with
Fresnel Lens

8"

SPECIFICATION INFORMATION
CYLINDER HOUSING

BALLAST

Pendant mounted cylinder is
constructed of seamless extruded
aluminum with a powder coat
finish. Standard height is 14” ,
dimming and emergency ballast
add 4” to height. Fixture mounts
to standard juction box. Pendant is
1/8 IPS steel and is standard in 18”
(optional length can be specified)

Electronic enclosed, class P, HPF
is supplied standard in 120V or
277V. Ballasts use 4 pin lamps
and provide rapid start, .99 power
factor with THD<10%. Dimming
ballast controls lumen output
down to +- 5% and is available from
Lutron D1 and D4 and Advance D3 .
All require compatible dimmers.

REFLECTOR

ELECTRICAL

Reflector is available in thirty
degree cutoff .30 . Finishes are
Clear A or Gold G Alzak for
anodized, specular, durable and
anti-iridescent reflectors.

U.L. listed for use in damp
locations.

TRIM OPTIONS
B black baffle
G gold Alzak
SP splay fesnel lens

ACCESSORIES
B black baffle
BA ball aligner canopy
D1 Lutron Hi-Lume dimming

ballast adds 4” to length
D3 Advance dimming ballast adds

4” to length
D4 Lutron Tu-Wire dimming

ballast 120V only
EM emergency power pack ignites

1 lamp for 90 minutes adds 4” to
length
RC retro-fit for existing cylinder
(consult factory)
X custom pendant length (specify
length)

INCORPORATED

CP8100

Gold Alzak®

LIGHTING

FINISHES
BM brushed metal
BZ bronze
K black
W white

ORDERING INFORMATION
LAMP
1-18 18 watt triple tube
1-26 26 watt triple tube
1-32 32 watt triple tube
1-42 42 watt triple tube

120V ELECT.
CP8118.1E 18watt triple tube
CP8126.1E 26watt triple tube
CP8132.1E 32watt triple tube
CP8142.1E 42watt triple tube

277V ELECT.
CP8118.2E 18watt triple tube
CP8126.2E 26watt triple tube
CP8132.2E 32watt triple tube
CP8142.2E 42watt triple tube

11916
VALERIO ST.
NORTH

FINISH MUST BE SPECIFIED

HOLLYWOOD,
CALIFORNIA
91605

SUBMITTAL INFORMATION
TYPE:
DESCRIPTION:

PROJECT:

PHONE

NOTES:

818 982 3701
FAX
818 982 3715

CLEAR ALZAK 30°
CP8118

CLEAR ALZAK 30°
CP8126

14"

CLEAR ALZAK 30°
CP8132

14"

CP8142

14"

8"

CLEAR ALZAK 30°

14"

8"

8"

8"

CONE OF LIGHT
FC/0•

MTG. HT.

DIA.

FC/0•

MTG. HT.

DIA.

FC/0•

MTG. HT.

DIA.

FC/0•

MTG. HT.

DIA.

4'

65

3.7

4'

81

3.7

4'

95

4.2

4'

123

4.3

6'

29

5.5

6'

39

5.5

6'

42

6.4

6'

54

6.6

8'

17

7.3

8'

19

7.3

8'

24

8.5

8'

31

8.8

10'

11

9.2

10'

12

9.2

10'

15

10.7

10'

19

10.9

12'

8

11.0

12'

9

11.0

12'

11

12.8

12'

14

12.9

50% FC at edge

50% FC at edge

50% FC at edge

50% FC at edge

CP DISTRIBUTION
90°

90°
260

60°

400

310

60°

30°

90°

90°

200

60°

60°

400

520

620

800

600

780

930

1200

30°

800

30°

1040

1000

30°

1240

1300

1600
2000

1550

COEFFICIENTS OF UTILIZATION
% CEILING 80 (20% FLOOR)
% WALL 70
50
30

% CEILING 80 (20% FLOOR)
% WALL 70
50
30

% CEILING 80 (20% FLOOR)
% WALL 70
50
30

% CEILING 80 (20% FLOOR)
% WALL 70
50
30

0
1
2
3
4
5
6
7
8
9
10

0
1
2
3
4
5
6
7
8
9
10

0
1
2
3
4
5
6
7
8
9
10

0
1
2
3
4
5
6
7
8
9
10

75
72
70
67
64
62
59
57
54
52
50

75
71
67
64
60
57
55
52
49
47
44

75
70
65
61
58
54
52
49
46
43
41

71
69
66
63
61
58
55
53
50
48
46

71
67
63
60
57
53
51
48
45
43
40

71
66
61
57
54
50
48
45
42
39
37

84
80
77
73
70
67
63
60
57
54
51

84
78
74
69
65
61
58
54
50
47
44

84
77
71
66
62
57
54
50
46
43
40

79
76
73
69
66
63
60
57
54
51
49

79
74
70
66
62
58
55
51
48
45
42

NOTES
CP8118

CP8126

CP8132

CP8142

1-18 watt triple tube
G24q-2 electronic socket
Total lumens-1250
Spacing criteria-.9
Gold Alzak x.90

1-26 watt triple tube
G24q-3 electronic socket
Total lumens-1800
Spacing criteria-.9
Gold Alzak x.90

1-32 watt triple tube
G24q-3 electronic socket
Total lumens-2400
Spacing criteria-.9
Gold Alzak x.90

1-42 watt triple tube
G24q-4 electronic socket
Total lumens-3200
Spacing criteria-.9
Gold Alzak x.90

79
73
67
63
58
55
51
48
44
41
39

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 1 of 2
B5

PL-T Triple 4-Pin Fluorescent Lamp
Feature

High color rendering, high efficacy lamps
feature 4-pin base for use with preheat, rapid
start, electronic and dimming circuits.
Featuring ALTO® Lamp Technology

Watts

32

Bulb

PL-T

Base

GX24q-3

Product

046677-26832-6

Number
Ordering

PL-T 32W/830/4P/ALTO

Code
Generic

CFTR32W/GX24q/830

Designation
Package

12

Quantity
Description

3000K

CRI

82

Avg. Hrs.

10,000

Life
Design

2040

Lumens
M.O.L.

5 5/8

Lumens

2400

Images

Literature

Other Information

+ ALTO Product Logo

+ ALTO Family Brochure

• Energy Saving Product

+ Family Photo

+ MSDS S08-98001

+ Printable Page

+ Product Photo

+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

This Product Contains Amalgam

+

High Color Rendering Lamp

Features ALTO® Lamp Technology
+ Rated average life under specified test conditions with Programmed Start ballasts with lamps
+

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 2 of 2

+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
Information for this product last modified on September 25, 2001

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

B5

IZT-2T42-M3-BS@120
Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

Electrical Specifications

Lamp Type

* CFM32W/GX24Q
CFM42W/GX24Q
CFTR57W/GX24Q
CFTR70W/GX24Q

Num.
of
Lamp
s
2
2
1
1

Rated
Lamp
Watts

Min.
Start
Temp
(°F/C)
50/10
50/10
50/10
50/10

32
42
57
70

MARK VII 0-10V
Electronic Dimming
Programmed Start
Series
120-277
50/60 HZ
Active

Input
Current
(Amps)

Input Power
(Watts)
(min/max)

Ballast Factor
(min/max)

MAX
THD
%

Power
Factor

Lamp
Current
Crest Factor

B.E.F.

0.63
0.82
0.55
0.67

19/75
18/98
18/66
18/80

0.05/1.00
0.05/1.00
0.05/1.00
0.05/1.00

10
10
10
10

0.99
0.99
0.99
0.99

1.4
1.4
1.7
1.7

1.33
1.02
1.52
1.25

Wiring Diagram

Enclosure

WIRING: (2) TRIPLE LAMPS
LINE
CLASS 1&2
CIRCUIT
10V, 0.5mA

BLACK
WHITE
VIOLET
(+)
GREY (-)
GREEN

BLUE
BALLAST Y E L L O W
RED

Green Terminal must be Grounded
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)

Enclosure Dimensions

Standard Lead Length (inches)
Black
White
Blue
Red
Yellow
Gray
Violet

in.
0
0
0
0
0
0
0

cm.
0
0
0
0
0
0
0

in.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White

cm.
0
0
0
0
0
0
0

OverAll (L)
6.28 "
6 7/25
16 cm

Width (W)
3.00 "
3
7.6 cm

Height (H) Mounting (M)
1.29 "
2.00 "
1 29/100
2
3.3 cm
5.1 cm

Revised 08/27/2003
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

IZT-2T42-M3-BS@120

Electrical Specifications
Notes:

Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

MARK VII 0-10V
Electronic Dimming
Programmed Start
Series
120-277
50/60 HZ
Active

Section I - Physical Characteristics
1.1 Ballast shall be physically interchangeable with standard electromagnetic or standard electronic ballasts, where applicable.
1.2 Ballast shall be available in a plastic/metal can or all metal can construction to meet all plenum requirements.
1.3 Ballast shall be provided with poke-in wire trap connectors or integral leads color coded per ANSI C82.11.
Section II - Performance Requirements
2.1 Ballast shall be Programmed Start.
2.2 Ballast shall be provided with integral protection circuitry to withstand connection of low voltage control leads to mains power supply. In
this event, ballast shall default to maximum light output.
2.3 Ballast shall contain auto restart circuitry in order to restart lamps without resetting power.
2.4 Ballast shall operate from 50/60 Hz input source of 120V or 277V with sustained variations of +/- 10% (voltage and frequency) with no
damage to the ballast. IntelliVolt models shall operate from 50/60 Hz input source of 120V through 277V with sustained variations of +/- 10%
(voltage and frequency) with no damage to the ballast.
2.5 Ballast shall be high frequency electronic type and operate lamps at a frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
2.6 Ballast shall have a Power Factor greater than 0.98 at full light output and greater than 0.90 throughout the dimming range for primary lamp.
2.7 Ballast shall have a maximum ballast factor of 1.00 (1.18 for HL versions) at maximum light output and 0.03 at minimum light output for
primary lamp application.
2.8 Ballast shall provide for a Lamp Current Crest Factor of 1.7 or less throughout the dimming range in accordance with lamp manufacturer
recommendations.
2.9 Ballast input current shall have Total Harmonic Distortion (THD) of less than 10% when operated at nominal line voltage with primary lamp.
2.10 Ballast shall have a Class A sound rating.
2.11 Ballast shall have a minimum starting temperature of 10C (50F) for primary lamp.
2.12 Ballast shall provide Lamp EOL Protection Circuit for all T5, T5/HO, CFL lamps, and T8 lamps operating on 4-lamp ballast.
2.13 Ballast shall control lamp light output from 100% - 3% relative light output for T8 and CFL lamps and 100% - 1% relative light output for
T5/HO lamps.
2.14 Ballast shall ignite the lamps at any light output setting without first going to another output setting.
2.15 Ballast shall tolerate sustained open circuit and short circuit output conditions without damage.
Section III - Regulatory Requirements
3.1 Ballast shall not contain any Polychlorinated Biphenyl (PCB).
3.2 Ballast shall be Underwriters Laboratories (UL) listed, Class P and Type 1 Outdoor; and Canadian Standards Association (CSA) certified
where applicable.
3.3 Ballast shall comply with ANSI C62.41 Category A for Transient protection.
3.4 Ballast shall comply with ANSI C82.11 where applicable.
3.5 Ballast shall comply with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 18,
Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
Section IV - Other
4.1 Ballast shall be manufactured in a factory certified to ISO 9002 Quality System Standards.
4.2 Ballast shall carry a five-year warranty from date of manufacture against defects in material or workmanship, including replacement, for
operation at a maximum case temperature of 70C.

4.3 Manufacturer shall have a fifteen-year history of producing electronic ballasts for the North American market.
4.4 Ballast shall be controlled by a Class 1 or Class 2 low voltage 0-10VDC controller.
4.5 Ballast shall be Advance Transformer part # _____________ or approved equal.

Revised 08/27/2003
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER - 10275 WEST HIGGINS ROAD
ROSEMONT, ILLINOIS 60018
TELEPHONE: (847) 390-5000 FAX: (847) 390-5109

B6
9" x 9" Floating Paper
Optic Forms

Spectral
Architectural Lighting

04-05

SL207C

2-26/32/42W Triple Twin Tube

Ceiling Cutout : 9 5/8" (245mm) X 9 5/8" (245mm)
Ordering Guide (complete unit only)
Cat. No.
SL207CTEU
SL207CTE3

Lamp (Triple Twin Tube)
2-26/32/42W TTT

Volts

Finish

120/277V
347V

SL207CPPU

2-26W TTT

120/277V (HDF)

SL207CPOU

2-32/42W TTT

120/277V (HDF)

Clear acrylic with white lacquer lens and brushed stainless steel square trim.

120V (MARK-10)

Stainless steel screws .

SL207CTZ1
SL207CTZ2
SL207CTR1
SL207CTR2

2-26W TTT

2-32/42W TTT

277V (MARK-10)
120V (MARK-10)
277V (MARK-10)

Features
1. Lens : 40mm thick clear acrylic finished with a translucent diffused coating.
2. Trim Ring : 18 ga. Steel. Brushed Stainless finish.
3. Upper Reflector: High efficiency, 97%, Specular Clear.
4. Housing: 20ga. Galvanized formed steel. Centerline notches and
holes for consistent alignment of multiple fixtures. Accommodates
ceilings up to 1 1/4" (31mm) thick.
5. Ballast Assembly: Door-mounted for easy service, allows replacement
from inside of fixture.
6. Junction Box: 14 ga. Galvanized steel. Accessible from inside and
outside of the fixture. Outside J-box door is hinged for easy access.
7. Mounting Brackets: 16 ga. steel. Use 18" (457 mm) mounting bars
(optional) or with standard 3/4" (19 mm), 1-1/2" (38 mm) lathing channels
(by others) or 1/2” (13 mm) tubing (by others). Adjust vertically from
inside of fixture.
8. Junction Box: CSA certified for through branch circuit wiring
with maximum of 8 no. 12, 90º C conductors.

Electrical
Ballast : Electronic Program Rapid Start T4 quad lamp ballast. Universal
voltage "U" ballast automatically detect 120 volts or 277 volts operation. No
visible flicker on starting, internally fused and protection circuit for lamp end of
life. Sound rated “A”. Designed for removal without tools from inside of luminaire
for easy field inspection or service replacement.
TE : 26/32/42W TTT non-dimming
PP : 26W TTT HDF dimming
PO : 32/42W TTT HDF dimming
TZ : 26W TTT MARK-10 dimming
TR : 32/42W TTT MARK-10 dimming
Lampholder : 26/32W : G24q-3 base, 42W : G24q-4 (4-pins)

Options and Accessories
Mounting bars: 1950 (set of 2) 18" (457 mm) long. 1951 (set of 2) 30"
(762 mm) long.
T-Bar Anchor Clips : 1956 (set of 4) For anchoring mounting bars to
T-Bar runners.

Mounting
Recessed, Non-IC Type (non thermal insulation contact).

Finish
Lens : Clear acrylic with white lacquer
Square Trim : Brushed Stainless steel

Labels
UL "c/us" Listed. Suitable for wet locations.

WE RESERVE THE RIGHT TO CHANGE DETAILS OF DESIGN, MATERIALS AND FINISH, IN ANY WAY
THAT WILL NOT ALTER INSTALLED APPEARANCE OR REDUCE FUNCTION AND PERFORMANCE.

Lightolier Canada, 3015 Louis Amos Lachine, (Quebec) H8T 1C4

04-05

Floating Paper 9" x 9"
Optic Forms
2-26/32/42W Triple Twin Tube

Spectral
Architectural Lighting

SL207C

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 1 of 2
B6

PL-T Triple 4-Pin Fluorescent Lamp
Feature

High color rendering, high efficacy lamps
feature 4-pin base for use with preheat, rapid
start, electronic and dimming circuits.
Featuring ALTO® Lamp Technology

Watts

32

Bulb

PL-T

Base

GX24q-3

Product

046677-26832-6

Number
Ordering

PL-T 32W/830/4P/ALTO

Code
Generic

CFTR32W/GX24q/830

Designation
Package

12

Quantity
Description

3000K

CRI

82

Avg. Hrs.

10,000

Life
Design

2040

Lumens
M.O.L.

5 5/8

Lumens

2400

Images

Literature

Other Information

+ ALTO Product Logo

+ ALTO Family Brochure

• Energy Saving Product

+ Family Photo

+ MSDS S08-98001

+ Printable Page

+ Product Photo

+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

This Product Contains Amalgam

+

High Color Rendering Lamp

Features ALTO® Lamp Technology
+ Rated average life under specified test conditions with Programmed Start ballasts with lamps
+

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 2 of 2

+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
Information for this product last modified on September 25, 2001

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

B6

ICF-2S42-M2-BS@120
Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

Electrical Specifications

Lamp Type

(1) FC9T5 & (1)
FC12T5
CFM26W/GX24Q
* CFM32W/GX24q
CFM42W/GX24q
CFM57W/GX24Q
CFM70W/GX24Q
CFQ26W/G24q
CFS28W/GR10q
CFS38W/GR10q
FT24W/2G11
FT40W/2G11/RS

Num.
of
Lamp
s
2

Rated
Lamp
Watts

Min. Start
Temp
(°F/C)

Input
Current
(Amps)

62

0/-18

2
2
2
1
1
2
2
2
2
2

26
32
42
57
70
26
28
38
24
40

0/-18
0/-18
0/-18
32/00
14/-10
0/-18
0/-18
0/-18
0/-18
0/-18

Wiring Diagram

BLUE

BLACK
WHITE

Ballast
Factor

MAX
THD
%

Power
Factor

MAX Lamp
Current
Crest Factor

B.E.F.

0.51

Input
Power
(ANSI
Watts)
61

0.85

10

0.98

1.5

1.39

0.46
0.57
0.78
0.50
0.63
0.43
0.48
0.55
0.40
0.66

55
68
93
59
75
52
57
62
48
78

1.00
0.98
0.97
0.94
0.96
1.00
1.00
0.80
0.93
0.95

10
10
10
10
10
10
10
10
15
10

0.98
0.98
0.99
0.98
0.98
0.98
0.98
0.98
0.98
0.99

1.5
1.5
1.5
1.5
1.6
1.5
1.5
1.5
1.5
1.5

1.82
1.44
1.04
1.59
1.28
1.92
1.75
1.29
1.94
1.22

Enclosure

WIRING: (2) LAMPS

LINE

SMARTMATE
Electronic
Programmed Start
Series
120-277
50/60 HZ
Active

(1) LAMP

BLUE

BALLAST Y E L L O W

GREEN

RED

RED

Green Terminal must be Grounded
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)

Enclosure Dimensions

Standard Lead Length (inches)
Black
White
Blue
Red
Yellow
Gray
Violet

in.
0.0
0.0
0.0
0.0
0

cm.

in.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White

cm.

OverAll (L)
4.98 "
4 49/50
12.6 cm

Width (W)
3.00 "
3
7.6 cm

Height (H) Mounting (M)
1.29 "
2.00 "
1 29/100
2
3.3 cm
5.1 cm

Revised 09/02/2004
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

ICF-2S42-M2-BS@120

Electrical Specifications
Notes:

Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

SMARTMATE
Electronic
Programmed Start
Series
120-277
50/60 HZ
Active

Section I - Physical Characteristics
1.1 Ballast shall be physically interchangeable with standard electromagnetic or standard electronic ballasts, where applicable.
1.2 Ballast shall be available in a plastic/metal can or all metal can construction to meet all plenum requirements.
1.3 Ballast shall be provided with poke-in wire trap connectors color coded per ANSI C82.11.
Section II - Performance Requirements
2.1 Ballast shall be Programmed Start except for ballasts with -QS suffix, which shall be Rapid Start.
2.2 Ballast shall contain auto restart circuitry in order to restart lamps without resetting power.
2.3 Ballast shall operate from 50/60 Hz input source of 120V through 277V with sustained variations of +/- 10% (voltage and frequency) with
no damage to the IntelliVolt ballast. RCF models shall operate from 60 Hz input source of 120V with sustained variations of +/- 10% (voltage
and frequency) with no damage to the ballast.
2.4 Ballast shall be high frequency electronic type and operate lamps at a frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
2.5 Ballast shall have a Power Factor greater than 0.98 for primary lamp.
2.6 Ballast shall have a minimum ballast factor of 1.00 for primary lamp application.
2.7 Ballast shall provide for a Lamp Current Crest Factor of 1.7 or less in accordance with lamp manufacturer recommendations.
2.8 Ballast input current shall have Total Harmonic Distortion (THD) of less than 10% when operated at nominal line voltage with primary lamp.
2.9 Ballast shall have a Class A sound rating.
2.10 Ballast shall have a minimum starting temperature of -18C (0F) for primary lamp. Ballasts for PL-H lamps shall have a minimum starting
temperature of -30C (-20F) for primary lamp.
2.11 Ballast shall provide Lamp EOL Protection Circuit which meets NEMA recommendations.
2.12 Ballast shall tolerate sustained open circuit and short circuit output conditions without damage.
Section III - Regulatory Requirements
3.1 Ballast shall not contain any Polychlorinated Biphenyl (PCB).
3.2 Ballast shall be Underwriters Laboratories (UL) listed, Class P and Type 1 Outdoor; and Canadian Standards Association (CSA) certified
where applicable.
3.3 Ballast shall be Underwriters Laboratories (UL) rated for use in air-handling spaces.
3.4 Ballast shall comply with ANSI C62.41 Category A for Transient protection.
3.5 Ballast shall comply with ANSI C82.11 where applicable.
3.6 Ballast shall comply with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 18,
Non-Consumer (Class A) for EMI/RFI (conducted and radiated) except for RCF models which shall be Consumer (Class B).
Section IV - Other
4.1 Ballast shall be manufactured in a factory certified to ISO 9002 Quality System Standards.
4.2 Ballast shall carry a five-year warranty from date of manufacture against defects in material or workmanship, including replacement, for
operation at a maximum case temperature of 75C and three-years for a maximum case temperature of 85C (90C 3year warranty for ICF1H120XX-XX, ICF2S70-XX-XX and ICF2S4290C-XX-XX modesls).
4.3 Manufacturer shall have a fifteen-year history of producing electronic ballasts for the North American market.
4.4 Ballast shall be Advance Transformer part # _____________ or approved equal.

Revised 09/02/2004
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER - 10275 WEST HIGGINS ROAD
ROSEMONT, ILLINOIS 60018
TELEPHONE: (847) 390-5000 FAX: (847) 390-5109

B7
FEATURES

OPTICAL SYSTEM
•
Internal housing components painted matte black. Lamp
snoot minimizes stray light in housing.
•
Finishing trim is microgroove black baffle with white painted
flange or specular, semi-diffuse or highly specular cone
with flange that matches cone finish. White painted flange
optional.
•
Optical system retained by self-aligning butterfly support
springs.
•
Accommodates up to two lenses, filters or louvers.
•
Softening lens standard (supplied).
MECHANICAL SYSTEM
• Black painted housing features tool-less top access and
accommodates a maximum 2" ceiling thickness.
• Re-lamp capability from above or below ceiling.
• Mounting bars are 16-gauge galvanized steel with continuous 4" vertical adjustment, held in place with tool-less, integral cam-action locking. Post installation adjustment possible without the use of tools from above or below the ceiling. Shipped pre-installed.
• Secondary housing adjustment system for precise, final
flange to ceiling alignment.
• Painted steel junction box with bottom-hinged access covers and spring latches. Four combination 1/2"-3/4" knockouts
for straight-through conduit runs. Capacity: 8(4 in, 4 out) No.
12 AWG conductors, rated for 90°C.
ELECTRICAL SYSTEM
• Tool-less access door provides access to junction box
through the aperture.
• Replaceable socket assembly. MR16 socket assembly standard (20W - 75W).
• Magnetic step-down transformer (replaceable without the
use of tools).
• Thermally-activated insulation detector (replaceable without the use of tools).
LISTING
• Fixtures are UL listed for thru-branch wiring, recessed mounting and damp locations. Listed and labeled to comply with
Canadian Standards.

Type

Catalog number

.........................

................................................................................

.........................

................................................................................

Low Voltage Downlights

4" DLV
Downlight
Open Cone

6-3/4 (17.1)

Aperture:
Ceiling opening:
Overlap trim:

4-5/16 (11.0)
4-7/8 (12.4)
5-7/16 (13.8)

All dimensions are
inches (centimeters).

13-3/4
(34.9)

16-1/8 (41.0)

Example:

ORDERING INFORMATION

DLV DWN MR16 4AC 120

Choose the boldface catalog nomenclature that best suits your needs and write it on the appropriate line.
Order accessories as separate catalog numbers (shipped separately).
DLV

DWN

Series
DLV

Lamp designation
MR16

MR11

Configuration
DWN

ALR12
ALR18
AR70

1

MR16 capability
(Standard)
MR11 capability
ALR12 capability
ALR18 capability
AR70 capability

Cone/Color
2

4BC

4AC
4PC
4WTC
4UBC
4GC
4CC

2

4WC

2

4MB

NOTES
1 Clear safety lens standard with AR70 lamp designation.
2 Not available with finishes.
3 For compatible Reloc systems, refer to options and
accessories tab.

2

4WB

Black
Clear
Pewter
Wheat
Umber
Gold
Champagne gold
White
Contoured black baffle
Contoured white baffle

Finish
(blank)

LD

LS

Specular
low
iridescent
Semidiffuse
low
iridescent
Highly
specular

Volt
120

Options
TRW

277
347

LRC

3

White painted flange.
(Standard with WC, MB,
and WB.)
Provides compatibility
with Lithonia Reloc System.

Accessories
• For lens accessories, refer to options and accessories tab.
• For lamp options, refer to options and accessories tab.

DLV 4

DLV-140

4" DLV

Downlight, Gotham Series

Distribution curve

Distribution data

DLV DWN MR16 4AC,

90°
1200
2400
3600
4800
6000

0°

0°
5°
15°
25°
35°
45° 45°
55°
65°
75°
85°
90°

90°
1600
3200
4800
6400
8000

0°

90°
400
800
1200
1600
2000

0°

90°
600
1200
1800
2400
3000

0°

From 0°

cp.

5263
3805
936
114
12
3
4
8
5
3
0

Lumens

301
262
58
8
2
5
6
5
5

Zone

Lumens %lamp

0°-30°
0°-40°
0°-60°
0°-90°
90°-180°
0°-180°

622
630
637
654
0
654

70.7
71.6
72.4
74.3
0.0
74.3*

* Efficiency

rf
20%
rc
80%
70%
50%
rw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

84
80
77
74
72
70
68
66
65
63

82
78
74
71
69
67
65
63
62
61

82
79
76
73
71
69
67
66
64
63

81
77
73
71
68
66
65
63
62
60

79
76
74
72
70
68
67
65
64
63

78
75
72
70
68
66
64
63
61
60

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

174.0
93.6
58.3
39.8
28.9

50%
10%
beam angle 15.6° beam angle 35.1°
fc at
fc at
Beam
beam
Beam beam
diameter
edge diameter edge

1.5'
2.1'
2.6'
3.2'
3.7'

87.0
46.8
29.2
19.9
14.4

3.5' 17.4
4.8' 9.4
6.0' 5.8
7.3' 4.0
8.6' 2.9

cp.

7027
5017
1182
126
15
0
0
0
0
0
0

Lumens

398
334
74
11
0
0
0
0
0

Zone

Lumens %lamp

0°-30°
0°-40°
0°-60°
0°-90°
90°-180°
0°-180°

806
817
817
817
0
817

73.2
74.2
74.2
74.2
0.0
74.2*

* Efficiency

rf
20%
rc
80%
70%
50%
rw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

84
81
78
76
73
72
70
68
67
65

83
79
76
73
71
69
67
66
64
63

83
80
77
75
73
71
69
68
66
65

82
78
75
73
70
69
67
65
64
63

80
77
75
73
72
70
69
67
66
65

79
76
74
72
70
68
66
65
64
62

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

232.3
124.9
77.9
53.1
38.6

50%
10%
beam angle 15.3° beam angle 34.2°
fc at
fc at
Beam beam
Beam beam
diameter edge
diameter edge

1.5' 116.1
2.0' 62.5
2.6' 38.9
3.1' 26.6
3.6' 19.3

3.4' 23.2
4.6' 12.5
5.8' 7.8
7.1' 5.3
8.3' 3.9

, 50MR16Q/40/FL (EXN) lamp, 0.5 s/mh, 880 rated lumens, test no. 2198040605
From 0°

0°
5°
15°
25°
35°
45° 45°
55°
65°
75°
85°
90°

DLV DWN MR16 4AC

Single luminaire data 30" above floor

65MR16Q/10/NSP (FPA) lamp, 0.3 s/mh, 1100 rated lumens, test no. 2198040602

0°
5°
15°
25°
35°
45° 45°
55°
65°
75°
85°
90°

DLV DWN MR16 4AC

Coefficient of utilization

Q50MR16/C/NSP15 (EXT) lamp, 0.3 s/mh, 880 rated lumens, test no. 2198043004

From 0°

DLV DWN MR16 4AC,

Output data

cp.

1773
1646
962
291
43
1
0
0
0
0
0

Lumens

147
262
139
29
1
0
0
0
0

Zone

Lumens %lamp

0°-30°
0°-40°
0°-60°
0°-90°
90°-180°
0°-180°

548
577
578
578
0
578

62.3
65.6
65.7
65.7
0.0
65.7*

* Efficiency

rf
20%
rc
80%
70%
50%
rw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

74
70
67
64
61
59
57
54
53
51

73
68
64
61
58
56
54
52
50
48

73
69
66
63
61
58
56
54
52
51

71
67
64
61
58
56
53
51
49
48

70
67
64
62
60
57
55
54
52
50

69
65
62
60
57
55
53
51
49
48

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

58.6
31.5
19.6
13.4
9.7

50%
10%
beam angle 29.5° beam angle 52.1°
fc at
fc at
Beam beam
Beam beam
diameter edge
diameter edge

2.9' 29.3
4.0' 15.8
5.0' 9.8
6.1' 6.7
7.1' 4.9

5.4'
7.3'
9.3'
11.2'
13.2'

5.9
3.2
2.0
1.3
1.0

, Q71MR16/C/FL40 (EYC) lamp, 0.5 s/mh, 1100 rated lumens, test no. 2198043005
From 0°

0°
5°
15°
25°
35°
45° 45°
55°
65°
75°
85°
90°

cp.

Lumens

2280
2027
1190
405
62
0
1
1
1
1
0

182
325
189
42
1
1
1
1
1

Zone

Lumens %lamp

0°-30°
0°-40°
0°-60°
0°-90°
90°-180°
0°-180°

696
738
741
744
0
744

63.3
67.1
67.3
67.6
0.0
67.6*

* Efficiency

NOTES
1 Tested to current IES and NEMA standards under stabilized laboratory
conditions. Various operating factors can cause differences between
laboratory data and actual field measurements. Dimensions and
specifications are based on the most current available data and are
subject to change without notice.

DLV-140

©2003 Gotham, Rev. 01/03
DLV-140.P65

rf
20%
rc
80%
70%
50%
rw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

76
72
68
65
63
60
58
55
53
52

75
70
66
62
59
57
54
52
50
48

74
71
68
65
62
59
57
55
53
51

73
69
65
62
59
57
54
52
50
48

72
69
66
63
61
59
56
54
53
51

71
67
64
61
58
56
54
52
50
48

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

75.4
40.5
25.3
17.2
12.5

50%
10%
beam angle 28.6° beam angle 52.9°
fc at
fc at
Beam beam
Beam beam
diameter edge
diameter edge

2.8' 37.7
3.8' 20.3
4.8' 12.6
5.9' 8.6
6.9' 6.3

5.5'
7.5'
9.5'
11.4'
13.4'

7.5
4.1
2.5
1.7
1.3

Long Life ESX 20W GU5.3 12V MR16 10D CL 1CT

Page 1 of 3
B7,B8

Long Life ESX 20W GU5.3 12V MR16 10D CL 1CT
| Save PDF | Open PDF

General

PRODUCT DATA
Product Number

378141

Full product name

Long Life ESX 20W GU5.3 12V MR16 10D CL 1CT

Ordering Code

20MRC16/SP10

Pack type

1 Lamp in a Folding Carton

Pieces per pack

1

Packs per case

50

Pack UPC

046677378141

EAN2US

-

Case Bar Code

50046677378146

Successor Product number

-

ANSI Code Halogen

ESX

Wattage[W ]

20W

Base

GU5.3 [GU5.3]

Voltage[V ]

12V

Bulb

MR16 [MR 16inch/50mm]

Beam Angle[D ]

10D

Bulb Finish

CL [Clear]

Packing Type

1CT [1 Lamp in a Folding Carton]

Operating Position

Universal[Universal]

Packing Configuration

10X5F

Rated Avg. Life[hr ]

-

Dimmable

Yes

Approx. MBCP[cd ]

-

Color Rendering Index[Ra8 ]

100

Color Temperature[K ]

3000

Overall Length C[mm ]

46

Diameter D[mm ]

50

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

Long Life ESX 20W GU5.3 12V MR16 10D CL 1CT

Page 2 of 3

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

Long Life ESX 20W GU5.3 12V MR16 10D CL 1CT

Page 3 of 3

Dimensions

PRODUCT DIMENSIONS
Characteristic

Value

Overall Length C (DTB)

46 mm

Diameter D (DTB)

50 mm

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

D1

FIXTURE D1 CUSTOM

D1

D2
JOB: __________________________

LOCATION: ____________________
CATALOG: DECORATIVE D4 2003/04

DATE: _________________________

PRODUCT SPECIFICATIONS
STYLE # D4-1027
SERIES NAME: ICE
STRUCTURE: Metal
COLOR /FINISH: Aluminum

Custom Bronze Finish

43” / 112 cm

DIFFUSER: Clear and Frost Glass
LAMP TYPE: Halogen G9 Frost
MAX WATT: 1 x 40W

ADA

DIMENSIONS: W. 4 ½” x Ht. 43” x Ext. 4 ½”
4 ½” / 11 cm

APPROVALS: Approved by CSA for
North American Standards.
NOTES: _________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
ZANEEN LIGHTING 65 DENSLEY AVE. TORONTO, ONTARIO, CANADA M6M 2P5
PH: 800.388.3382 / 416.247.9221 FAX: 416.247.9319 www.zaneen.com zaneen@zaneen.com

D2

O1

Job Name:

CALLISTO-12

Fixture Type:
Job Number:
Distributor:
Distributor P.O. :

1. H O U S I N G

CL12

Housing: two-piece die-cast aluminum with
internal component mounting bosses.

10.39"
3.45"

14.30"
13.38"
12"

Door frame: one-piece die-cast aluminum
secured with three phillips head screws.

9.81"

Lens assembly: various clear or prismatic glass
lens (beam dependant) gasketed
to door to ensure a tight seal.

9.62"
0.18"
EPA (fixture only): 0.62

2"

FIXTURE WEIGHT: 28 LBS.

The luminaire shall be cULus listed for wet
locations and manufactured from UL-recognized
components.

(shown with optional
eggcrate shield)

2. L A M P W A T T A G E
METAL HALIDE (H.I.D.) ED17

HIGH PRESSURE SODIUM (H.I.D.)

ED17

70 WATT METAL HALIDE

(70MH)

100 WATT HIGH PRESSURE SODIUM

(100HPS)

100 WATT METAL HALIDE

(100MH)

150 WATT HIGH PRESSURE SODIUM

(150HPS)

150 WATT METAL HALIDE

(150MH)

175 WATT METAL HALIDE

(175MH)

Quartz WATTAGE

PAR56

(500QTZ)

500 WATT QUARTZ HALOGEN

(Electronic ballast available only in 70MH or 100MH)

3. B E A M P A T T E R N
METAL HALIDE & HIGH PRESSURE SODIUM

INCANDESCENT
NARROW
SPOT

SPOT

(SP)

RECTANGULAR
NARROW (RN)

RECTANGULAR
MEDIUM (RM)

(NSP)

RECTANGULAR
WIDE (RW)
MEDIUM
FLOOD

RECTANGULAR
NARROW
VERTICAL (RNV)

Item Number:

ORDER NUMBER:

1

RECTANGULAR
MEDIUM
VERTICAL (RMV)

2

3

RECTANGULAR
WIDE
VERTICAL (RWV)

4

5

FLOOD

6

(WFL)

7

8

9

10

MOUNTING
OPTION

SHIELD
OPTION

FINISH

GENERAL
OPTION

YK

CL12
HOUSING

WIDE

(MFL)

LAMP
WATTAGE

BEAM
PATTERN

VOLTAGE

BALLAST
(FOR HID)

MODEL
STYLE

4. V O L T A G E

5. B A L L A S T (H.I.D. ONLY)

120

277

CORE & COIL

208

347

ELECTRONIC

240

480

6. M O D E L

(C)

YOKE

(YK)

(EB)

(Ballast is an integral part of the fixture housing.)
(Electronic ballast available only in 70WMH and 100WMH,
and in 120 or 277 volt. Rated for -20 F (-28.9 C).)

(Electronic ballast available only in 120 or 277 volts.)
(Quartz available in 120 volt only.)

(Core and coil ballast is high-power factor and rated for -20 F (-28.9 C).)

7. M O U N T I N G O P T I O N S
BASE PLATE

(BP) 0.56"
(4)

6.00" DIA.
BOLTCIRCLE

WALL BRACKET (WB)
1.81"
1.16"
3/ 8" LOCKING
BOLT
CANBE MOUNTED
TO2" PIPE (MAX) WITH
5/ 8" PIVOT U-BOLTS (U-BOLTS
BOLT
BY OTHERS)
3/ 4" MOUNTING
HARDWARE

6.00"

3/ 4" MOUNTING
HARDWARE
1.38"

BASE PAD (PD)
2.06"
I.D.

6.00"

2.38"
O.D.

SLIP FITTER
3.44"
3.13"

3.50"

CASTDUCTILE IRON
WALLBRACKETAND
HORIZONTALSECTOR

6.25"

0.56"
(4)

3.50"
4.50"

.25"
ALLCOMPONENTS STEEL.
WELDCONSTRUCTION

8. O P T I O N A L S H I E L D S

(SF)
TOFIT2" (2.38" O.D.)
PIPE TENONX 4.00" LONG
(MIN.)
REMOVABLE
PIPE PLUGFOR
3/ 4" MOUNTING INSTALLING
HARDWARE
WATER-TITE
CONNECTOR
(SUPPLIED)

5.63"
WATER-TITE
CONNECTOR
REMOVABLE
SPLICE INSPECTION
COVER
CASTTENZALLOY
FITTER

REMOVABLE
HOLE PLUGFOR
1/ 2" SET SIDE YOKE
SCREWS MOUNTING

EGGCRATE

(EC)

VER. LOUVER (VL)
6.17"

HOR. LOUVER

7.90"
6.17"

6.17"

2.46"

7.90"

3.0"

TOP SHIELD (TS)
6.17"
4.0"

CUSTOM SHIELD

(HL)

6.17""

3.0"

6.17"

(CS)

The eggcrate is the only shield finished to match luminaire.
Standard shield finish is black unless otherwise specified.

6.17"

9. F I N I S H

10. G E N E R A L O P T I O N S

(BK)
DARK BRONZE
(BZ)
WHITE
(WH)
NATURAL ALUMINUM
(AL)
NON-STANDARD
(NS)

INCLUDE LAMP

BLACK

(2" SCH. 40
STEELPIPE)
(for use with SF option)

8.00"
5.50"

.38"

CASTDUCTILE IRON
SURFACE BASE

6.00" DIA.
BOLTCIRCLE

1.50"

1.50"

0.56"
(4)

(LP)

SAFETY CABLE

(SC)

FUSE LUMINAIRE

(FL)

(SELECT 'LP' ONLY IF A LAMP IS TO BE INCLUDED)

70MH

ED17

100HPS

ED17

100MH

ED17

150HPS

ED17

150MH

ED17

175MH

ED17

500QTZ PAR56

REMARKS:
S t e r n e r L i g h t i n g S y s t e m s I n c o r p o r at e d
351 LEWIS AVENUE WEST, P.O. BOX 805 WINSTED, MN 55395-0805
T E L 3 2 0 . 4 8 5 . 2 1 4 1 FA X 3 2 0 . 4 8 5 . 2 8 8 1 T O L L - F R E E 8 0 0 . 3 2 8 . 7 4 8 0
2/2002

w w w. s t e r n e r l i g h t i n g . c o m

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Page 1 of 3
O1

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB
| Save PDF | Open PDF

General

PRODUCT DATA
Product Number

233684

Full product name

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Ordering Code

MHC100/U/MP/3K ALTO

Pack type

1 Sleeve Open End

Pieces per pack

1

Packs per case

12

Pack UPC

046677233686

EAN2US

-

Case Bar Code

50046677233681

Successor Product number

-

Wattage[W ]

100W

Color Code

830 [CCT of 3000K]

Base

Med [Medium]

Bulb

ED17P [Diameter: 2.125 inch Protected]

Bulb Finish

CL [Clear]

Feature

ALTO+FB [ALTO® + FadeBlock™]

Base Information

Brass[Brass Base]

Bulb Material

Hard Glass

Execution

Protected

Operating Position

Universal[Universal]

Packing Type

1SL[1 Sleeve Open End]

Packing Configuration

12

Rated Avg. Life[hr ]

16000

Mercury Weight[mg ]

7.2

ANSI Code HID

M140/M90/O

Lamp Voltage[V ]

101

Color Rendering Index[Ra8 ]

85

Color Designation

Warm White

Color Temperature[K ]

3000

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Initial Lumens[Lm ]

Page 2 of 3

8600

Design Mean Lumens[Lm ]

6450

Light Center Length L [inch][in ]

3.438

Max Overall Length (MOL) - C[in ]

5.438

Diameter D[in ]

2.125

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Page 3 of 3

Dimensions

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

O1

Metal
Halide
Lamp Ballast

Catalog Number 72C5381
For 100W M90/M140
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA

10.50"

CASE "F-1"

2.63"

11.13"

3.19"

11.75"

Capacitor:

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±12%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
1.10 0.48
Open Circuit...............................................
2.55 1.10
Starting......................................................
2.20 0.95
UL TEMPERATURE RATINGS
Insulation Class
A (105°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
277
INPUT VOLTAGE AT LAMP DROPOUT...........................
72 166
INPUT WATTS
125
RECOMMENDED FUSE (Amps).....................................
6
3
CORE and COIL
Dimension (A)
Dimension (B)
Weight (lbs.)
11
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
Volts (min.)
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
1600
2 seconds
2000
Open Circuit Voltage Test (Volts)
250-305
Short-Circuit Current Test (Amps)
Secondary Current
1.30-1.60
Input Current..............................................

0.70 0.30
1.10 0.50

-

-

-

Wiring Diagram:
All Lead Lengths 12"

277 V

The capacitor is included as
part of the potted assembly.

120V

COMMON

YELLOW/BLUE
BLACK

BALLAST

WHITE
RED

LAMP
GROUND CASE

F-Can Wiring Diagram

Ordering Information

Ignitor: IN CAN

Order Suffix

Description

The ignitor is included as
part of the potted assembly.
Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 90°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

09/03/99

O2
Lichtpunkt mit 9 LED aus Edelstahl, mit klarem Abdeckglas zur punktuellen Beleuchtung oder in opaler Optik mit
homogener Leuchtdichte.
Light spot with 9 LED in stainless steel, with clear glass cover for point illumination or in opal optic with homogenous luminance.
Spot lumineux avec 9 LED en acier inoxidable, avec verre de protection transparent pour un éclairage ponctuel,
ou verre de couleur opale pour une luminosité homogène.

03
03
03
03
03

LBS
LBS
LBS
LBS
LBS

4201
4211
4221
4231
4241

rot/red/rouge
gelb/yellow/jaune
grün/green/vert
blau/blue/bleu
weiß/white/blanc

ø 48

min. 40

LEDdot

ø 40

Sonderfarben auf Anfrage.
Special colours on request.
Couleurs spéciaux sur demande.

NV

LED
LED dot
24 V DC
1,2 W
0,1 kg

144

IP65

F

Anschluß mit 2-poligem Kabel.
Begeh- und überrollbar, jedoch
nicht für Verkehrswege zugelassen.
Connection via 2-pole cable. Driveover proof but not approved for
traffic ways.
Connexion par câble 2-pôle.
Resistant à la charge à court terme.

230/240 V
15 LE 0026 24 V/20 W/IP 20
15 LE 0059 24 V/75 W/IP 20
15 LE 9120 24 V/120 W/IP 20

Farbcodierung und technische Hinweise siehe Anhang/Colour code and technical informations see appendix/Code de couleur et informations techniques voir notes annexe
Technische Änderungen vorbehalten! Subject to technical alterations! Sous réserve de modification technique! ©Ansorg GmbH

®

Lumière
DESCRIPTION

S P E C I F I C AT I O N F E AT U R E S

Coronado 806 is a ultra-compact
line voltage fixture for use with
PAR20 halogen lamps. The fully
adjustable mounting stem
provides 340° tilt and 360°
rotation for easy aiming. Various
lenses, louvers and color or
dichroic filters can be combined –
up to three at once – to create
multiple lighting effects. Lumière’s
exclusive Siphon Protection
System (S.P.S.) prevents water
from siphoning into the fixture
through its own lead wires.

M AT E R I A L

Catalog #

Hood and mounting stem are
precision-machined from
corrosion-resistant 6061-T6
aluminum billet. Housing is
die-cast aluminum.

Type

O3

Project
Comments
Prepared by

FINISH

Fixtures are double protected
by a chromate conversion
undercoating and polyester
powdercoat paint finish,
surpassing the rigorous
demands of the outdoor
environment. A variety of
standard colors are available.
HOOD

Hood is removable for easy
relamping and accepts up to
three internal accessories at
once (lenses, louvers, filters)
to achieve multiple lighting
effects. Weep holes prevent
water and mineral stains from
collecting on the lens, even in
the straight-up position.
GASKET

Housing and hood are sealed with
a high temperature silicone o-ring
gasket to prevent water intrusion.
LENS

Tempered glass lens, factory
sealed with high temperature
adhesive to prevent water
intrusion and breakage due to

Date

thermal shock.
MOUNTING STEM

Adjustable side-mounted
swivel stem provides 340° tilt
and 360° rotation for easy
aiming. Equipped with standard
1/2" NPS threaded male fitting.
Stainless steel aim-locking
mechanisms are standard.
Lumière’s exclusive Siphon
Protection System (S.P.S.)
prevents water from siphoning
into the fixture through its own
lead wires.
HARDWARE

Stainless steel hardware is
standard to provide maximum
corrosion-resistance.
SOCKET

Ceramic socket with 200° C
Teflon® coated lead wires and
medium base.

CORONADO
806
5 0 W (max.) P A R 2 0
Halogen
L I N E V O LT A G E

ELECTRICAL

Operates with 120V line voltage.

ACCENT/FLOOD

LAMP

Not included. Available from
Lumière as an accessory – see
Lamps under Optical Accessories
on the reverse side of this page.

ø2-3/4"
[70mm]

6-3/8"
[162mm]

L A B E L S & A P P R O VA L S

UL and cUL listed, standard
wet label. Manufactured to
ISO 9001-2000 Quality Systems
Standard. IBEW union made.
WARRANTY

Lumière warrants its fixtures
against defects in materials &
workmanship for three (3)
years. Auxiliary equipment
such as transformers, ballasts
and lamps carry the original
manufacturer’s warranty.

1-3/4"
[44mm]

Coronado 806

O R D E R I N G I N F O R M AT I O N
S A M P L E N U M B E R : 8 0 6 - 5 0 PA R 2 0 - 1 2 0 - B K

Model

Source

Vo l t s

806

50PAR20

120

806

Halogen
50PAR20 = 50W/PAR20/medium
Lamp not included

WWW.COOPERLIGHTING.COM

120 = 120V

Finish

Accessories
(Order Separately)

Painted
BK = Black
BZ = Bronze
CS = City silver
VE = Verde
WT= White

Consult your representative for additional options and finishes.

See reverse page

ADL032489

CORONADO 806

P H O T O M E T R I C D ATA

Coronado 806
Lamp=50PAR20/NSP
CBCP=5000

Cone of Light
Distance to
Illuminated Plane

Initial Nadir
Footcandles

25'0"
20'0"
15'0"
12'0"
10'0"
8'0"

Coronado 806
Lamp=50PAR20/NFL
CBCP=1400

Beam
Diameter
10'0"
8'0"
6'0"
5'0"
4'0"
3'0"

8
13
23
35
50
80

Cone of Light
Distance to
Illuminated Plane

Initial Nadir
Footcandles

25'0"
20'0"
15'0"
12'0"
10'0"
8'0"

Beam
Diameter
20'0"
16'0"
12'0"
9'6"
8'0"
6'6"

2
3
6
9
13
20

L A M P I N F O R M AT I O N

Lamp
50PAR20/NSP
50PAR20/NFL

ANSI Code
-----

Watts
50
50

Beam Spread
10°
30°

CBCP
5000
1400

°K
-----

Life (hrs.)
2000
2000

Base
medium
medium

Volts
120
120

NOTE: Inferior quality lamps may adversely affect the performance of this product. Use only name brand lamps from reputable lamp manufacturers.

OPTICAL ACCESSORIES

Color & Dichroic Filters
F22-20 = Red color
F33-20 = Blue color
F44-20 = Green color
F55-20 = Yellow color
F66-20 = Mercury vapor color

F71-20 =
F72-20 =
F73-20 =
F74-20 =
F75-20 =

Peach dichroic
Amber dichroic
Green dichroic
Medium blue dichroic
Yellow dichroic

F76-20 =
F77-20 =
F78-20 =
F79-20 =
F80-20 =

Red dichroic
Dark blue dichroic
Light blue dichroic
Neutral density dichroic
Magenta dichroic

Lamps
HP2050-NSP = 50-watt PAR20 lamp - narrow spot
HP2050-NFL = 50-watt PAR20 lamp - narrow flood
Lower wattage lamps and/or additional distributions may be available. See the Accessories & Technical Data section of this catalog for details.

Lenses & Louvers
DIF-20 = Diffused lens
LSL-20 = Linear spread lens
OSL-20 = Overall spread lens
LVR-20 = Hex cell louver
Glare Shields
FH20 = Angled glare shield (specify finish: BK, BZ, CS, VE, WT)

MOUNTING ACCESSORIES

See the Accessories & Technical Data section of this catalog for details.

NOTES AND FORMULAS

• Beam diameter is to 50% of maximum footcandles, rounded to the nearest half-foot.
• Footcandle values are initial. Apply appropriate light loss factors where necessary.
• Bare lamp data shown. Consult lamp manufacturers to obtain detailed specifications for their lamps.
Specifications and Dimensions subject to change without notice.

Lumière • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801

ADL032489

Halogena 50W Med 120V PAR20 FL 25D CL 1CT

Page 1 of 3
O3

Halogena 50W Med 120V PAR20 FL 25D CL 1CT
| Save PDF | Open PDF

General

PRODUCT DATA
Product Number

389163

Full product name

Halogena 50W Med 120V PAR20 FL 25D CL 1CT

Ordering Code

50PAR20/HAL/NFL30

Pack type

1 Lamp in a Folding Carton

Pieces per pack

1

Packs per case

6

Pack UPC

046677229115

EAN2US

-

Case Bar Code

50046677389166

Successor Product number

-

Wattage[W ]

50W

Base

Med [Medium]

Voltage[V ]

120V

Bulb

PAR20 [PAR 20inch/63mm]

Beam Description

FL [Flood]

Beam Angle[D ]

25D

Bulb Finish

CL [Clear]

Packing Type

1CT [1 Lamp in a Folding Carton]

Base Information

Brass[Brass Base]

Bulb Material

Hard Glass

Reflector Finish

Aluminized

Filament Shape

CC-8[Axial]

Operating Position

Universal[Universal]

Packing Configuration

6

Atmosphere

Gas

Rated Avg. Life[hr ]

3000

Approx. MBCP[cd ]

900

Color Rendering Index[Ra8 ]

100

Color Temperature[K ]

2800

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

Halogena 50W Med 120V PAR20 FL 25D CL 1CT

Page 2 of 3

Initial Lumens[Lm ]

525

Max Overall Length (MOL) - C[in ]

3.375

Diameter D[in ]

2.5

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

Halogena 50W Med 120V PAR20 FL 25D CL 1CT

Page 3 of 3

Dimensions

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

O4

M9700 SERIES
METAL HALIDE 175 WATT MAX.
MODULAR IN-GRADE LUMINAIRE
DOUBLE LENS
DESCRIPTION:
The M9700 series modular in-grade lights are Multi-Purpose units
designed for Flush Mounting in a variety of substrates or materials.
The M9700’s are used to uplight Architectural and Landscape
features. The units consist of a Factory –Sealed, thermally protected
Lamp Module. Power Module is in a secured Rough-In section (RIS)
which includes Channeled Convective Cooling, an integral Junction
Box, and Door Assembly. The double lensed version offers Lamp
Module Aiming and feature Aim-Lock™ to allow maintenance and
relamping without re-aiming. The M9700 has a small footprint with a
cylinder configuration.

TYPE ___________________________________
MODEL #: ______________________________
ELECTRICAL ENTRIES/JUNCTION BOX: Two PG 16 or two
3/4" NPT bottom openings, standard. One hole is provided with
IP68 cord seal that accepts ø10mm to ø14 mm cable (outside
U.S. only). Second hole plugged. Box suitable for through branch
wiring. Splicing volume 52 cu. in.
ACCESSORIES: Internal Glare Control, Internal Honeycomb
Louvers, Rock Guards, Trim Rings, Re-enterable Potting
Compound, Polycarbonate Covers, External Glare Shields are
available.
NOTE: HYDREL RESERVES THE RIGHT TO CHANGE
ANY SPECIFICATION WITHOUT NOTICE.
Any dimension on this sheet is to be assumed as a reference dimension:
“Used for information purposes only. It does not govern manufacturing or
inspection requirements.” (ANSI Y14.5-1973)

SPECIFICATIONS:
DOOR FINISH: Cast aluminum, cast bronze, cast aluminum or
bronze with stainless perforated trim insert or Stainless Steel. Round
or square with two stainless steel captive fasteners that lock the Lamp
Module into the Rough-In Section.
ROUGH-IN SECTION: Injection molded polymer with integral
junction box for branch wiring, U.V. stabilized, impact and corrosion
resistant for use in all types of environ- ments. Houses Power
Module, Lamp Modules and finishing components. Adjustment ring
provides 360° aim rotation with keyed section to receive Lamp
Module. Ring locks into position with stainless steel fasteners. RIS
has a cylinder/vault configuration.

12”
(305)

LAMP MODULE: Stainless steel, sealed and purged of all moisture
with silicone gaskets, stainless steel clamp band and single fastener.
Electrical connection to Lamp Module is done through submersible
connector with gold-plated contacts. THERMALLY PROTECTED.
LAMP INCLUDED
M9740 MODEL

LAMP TYPES: See ordering guide. If a specific lamp is desired,
specify manufacturer's lamp number, most lamps can be supplied.
LAMP INCLUDED.

13”
(330)

VOLTAGES: 120V, 208V, 240V, 277V, 347V - 60 Hz, 220V, 230V,
240V - 50 Hz. Some restrictions may apply.
LIGHT DISTRIBUTIONS (Non Reflectorized Lamps):
TSP (G-12 T6 Lamps)
SP (E-17, Elliptical)
NFL (E-17, Elliptical, T6)
MFL (E-17, Elliptical, T6)
WFL (E-17, Elliptical)
WWD (E-17, Elliptical)
FINISHING SECTION:

Double Lens: Includes 360° Aim-LockTM Module Support Ring,
Door Assembly, Tilt Ring, and Module Indexing Segment
providing maintenance and relamping without re-aiming. The
Lamp Module is suspended below the door lens in a surface
adjustable, 15° tilt mechanism. The insulating air layer reduces
surface temperatures. Active lenses are available to bend beams
(10° tilt and 20° tilt).
POWER MODULE: Ballast is encapsulated in a custom-heat
dissipating epoxy resin to eliminate all moisture intrusion to the
ballast. Provided with submersible rated cord/connector for
connection to integral junction box and lamp module. HID ballasts are
magnetic. THERMALLY PROTECTED.

HYDREL is a registered trademark of Lithonia Lighting

M9720 MODEL
STAINLESS STEEL DOOR

12”
(305)
1 3/4”
(45)

13”
(330)

20”
(508)

M9740 MODEL
STAINLESS STEEL DOOR

PATENT PENDING
UL/CE

12881 BRADLEY AVENUE, SYLMAR, CALIFORNIA 91342 • PHONE: 818/362-9465 • FAX: 818/362-6548

HYDREL STANDARD DATA SHEET/M9720 1/2002

FIXTURE OPTIONS
Ordering and Specification Guide

M9720 A 35MT6 120 TSP 34BNPT STR
Model:
M9720
M9740

Round Double Lens
Square Double Lens

Material:
A
Aluminum
B
Bronze
ABL
Aluminum with black paint
ASP
Aluminum with stainless perf.*
BBP
Bronze with brass perf.*
BSP
Bronze with stainless perf.*
SS
Stainless steel
*ASP, BBP, BSP not available with M9740
(square double lens) model
Lamp Type: (Lamp Included)
US
European
HID
50S
(HPS)
E17, med. base
Elliptical, E27 base
70S
(HPS)
E17, med. base
Elliptical, E27 base*
100S
(HPS)
E17, med. base
Elliptical, E27 base*
150S
(HPS)
E17, med. base
E26**
50M
(MH)
E17, med. base
N/A
70M
(MH)
E17, med. base
Elliptical, E27 base
100M
(MH)
E17, med. base
Elliptical, E27 base
150M
(MH)
E17, med. base
Elliptical, E27 base
175M
(MH)
E17, med. base
N/A
50H
(MV)
E17, med. base
Elliptical, E27 base
75H
(MV)
E17, med. base
N/A
80H
(MV)
N/A
Elliptical, E27 base
100H
(MV)
E17, med. base
Elliptical, E27 base
175H
(MV)
E17, med. base
N/A
35MT6 (MH)
T6, G-12 base
T-6, G12 base
70MT6 (MH)
T6, G-12 base
T-6, G12 base
150MT6 (MH)
T6, G-12 base
T-6, G12 base
HID, PAR Lamps (PAR-38, med. base)***
P3870M WFL
(MH, 70W, wide flood)
P3870M FL
(MH, 70W, flood)
P3870M SP
(MH, 70W, spot)
P38100M WFL
(MH, 100W, wide flood)
P38100M FL
(MH, 100W, flood)
P38100M SP
(MH, 100W, spot)
P38100H FL
(MV, 100W, flood)
P38100H SP
(MV, 100W, spot)
P38175H FL
(MV, 175W, flood)
P38175H SP
(MV, 175W, spot)
P38175M FL
(MH, 175W, flood)
P38175M SP
(MH, 175W, spot)
***HID PAR lamps not available with E27 base
**Not CE listed
*Note: No internal accessories available with E27
base 70S or 100S
Voltage:
60HZ
50HZ
120
22050HZ
208
23050HZ
220
24050HZ
240
277
347
Not all Voltage/Lamp combinations are available,
consult factory for more information.

HYDREL is a registered trademark of Lithonia Lighting

Distributions:
TSP
(G-12 T6 Lamps)
SP
(E-17, Elliptical, PAR-38)
NFL
(E-17, Elliptical, T6)
MFL
(E-17, Elliptical, T6, PAR-38)
WFL
(E-17, Elliptical, PAR-38)
WWD
(E-17, Elliptical)
Conduit Entries:
12BNPT
1/2" NPT bottom
12SNPT
1/2" NPT side
34BNPT
3/4" NPT bottom
34SNPT
3/4" NPT side
1BNPT
1" NPT bottom
PG16B
PG16 bottom
PG16S
PG16 side
Accessories:
FLC5
5° Axial Spread Lens
GS
Glare Shield++
IHL38
Internal Honeycomb Louver (PAR-38 Lamps)
IHL
Internal Honeycomb Louver (Non-Adjustable)
ISS
Internal Source Shield (150W max, Elliptical
and T-6 lamps only)
LC
Polycarbonate Protective Cover++
RG
Rockguard++
STR
Stainless Steel Trim Ring, Round
STS
Stainless Steel Trim Ring, Square
FLC10
10° Tilt Lens
FLC20
20° Tilt Lens
PC2112
20 cu. in. Re-enterable Potting Compound
WWL
Wall Wash Louver
++

Not available with Stainless Steel (SS) model

For Replacement Parts Consult Factory

12881 BRADLEY AVENUE, SYLMAR, CALIFORNIA 91342 • PHONE: 818/362-9465 • FAX: 818/362-6548

HYDREL STANDARD DATA SHEETS/M9720 1/2002

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Page 1 of 3
O4

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB
| Save PDF | Open PDF

General

PRODUCT DATA
Product Number

233684

Full product name

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Ordering Code

MHC100/U/MP/3K ALTO

Pack type

1 Sleeve Open End

Pieces per pack

1

Packs per case

12

Pack UPC

046677233686

EAN2US

-

Case Bar Code

50046677233681

Successor Product number

-

Wattage[W ]

100W

Color Code

830 [CCT of 3000K]

Base

Med [Medium]

Bulb

ED17P [Diameter: 2.125 inch Protected]

Bulb Finish

CL [Clear]

Feature

ALTO+FB [ALTO® + FadeBlock™]

Base Information

Brass[Brass Base]

Bulb Material

Hard Glass

Execution

Protected

Operating Position

Universal[Universal]

Packing Type

1SL[1 Sleeve Open End]

Packing Configuration

12

Rated Avg. Life[hr ]

16000

Mercury Weight[mg ]

7.2

ANSI Code HID

M140/M90/O

Lamp Voltage[V ]

101

Color Rendering Index[Ra8 ]

85

Color Designation

Warm White

Color Temperature[K ]

3000

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Initial Lumens[Lm ]

Page 2 of 3

8600

Design Mean Lumens[Lm ]

6450

Light Center Length L [inch][in ]

3.438

Max Overall Length (MOL) - C[in ]

5.438

Diameter D[in ]

2.125

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 100W/830 Med ED17P CL ALTO+FB

Page 3 of 3

Dimensions

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

O4

Metal
Halide
Lamp Ballast

Catalog Number 72C5381
For 100W M90/M140
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA

10.50"

CASE "F-1"

2.63"

11.13"

3.19"

11.75"

Capacitor:

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±12%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
1.10 0.48
Open Circuit...............................................
2.55 1.10
Starting......................................................
2.20 0.95
UL TEMPERATURE RATINGS
Insulation Class
A (105°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
277
INPUT VOLTAGE AT LAMP DROPOUT...........................
72 166
INPUT WATTS
125
RECOMMENDED FUSE (Amps).....................................
6
3
CORE and COIL
Dimension (A)
Dimension (B)
Weight (lbs.)
11
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
Volts (min.)
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
1600
2 seconds
2000
Open Circuit Voltage Test (Volts)
250-305
Short-Circuit Current Test (Amps)
Secondary Current
1.30-1.60
Input Current..............................................

0.70 0.30
1.10 0.50

-

-

-

Wiring Diagram:
All Lead Lengths 12"

277 V

The capacitor is included as
part of the potted assembly.

120V

COMMON

YELLOW/BLUE
BLACK

BALLAST

WHITE
RED

LAMP
GROUND CASE

F-Can Wiring Diagram

Ordering Information

Ignitor: IN CAN

Order Suffix

Description

The ignitor is included as
part of the potted assembly.
Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 90°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

09/03/99

05

ENGINEERED
LIGHTING PRODUCTS

HITW-EX SERIES
RECESSED Hole In The Wall Light Niche
For Exterior Stucco Construction

Wall Washer

Indirect

Floor
Washer

Ideal placement is
18˝ to 30˝ from the
bottom edge of
fixture to the ground.
WL-2

O5
ENGINEERED
LIGHTING PRODUCTS

HITW-EX SERIES
RECESSED Hole In The Wall Light Niche
For Exterior Stucco Construction

SYSTEM

7/8˝

Recessed, fiberglass reinforced, composite fixture
for use in exterior stucco construction. The cast
fixture appears to be part of the architecture and
looks like a custom formed “light niche” that blends
with any exterior motif. Non I.C. Rated.
UL/CUL Wet Location listed.

16˝

17-1/2˝
14-1/4˝

16˝

17-1/2˝
6˝

SPECIFICATIONS
Recessed fixture for use with a 20 watt Incandescent,
13 watt PL, or 26 watt Quad lamp. The cast fixture
houses a ballast box with heat sink that includes
wiring, socket, ballast and reflector. Incandescent
fixture also has thermal protector. Fluorescent fixtures
provide knock-outs for through wiring. Casting is
secured to the 20 gauge electro-plated galvanized
steel fixture back box and a 18 gauge electro-plated
galvanized steel frame with lexan lens and silicone
gaskets seal the lamp compartment.
Frame, ballast box, and fixture back box are TGIC
polyester powder coated. Composite casting is water
and high impact resistant. Use “Weld-crete” to finish
surface to match exterior stucco.

OPTIONS
Ballast

Low Temp 120 HPF Electronic (Standard)
Low Temp 277 HPF Electronic

①
Fixture mounts
directly to studs
that are 16˝ on
center.

③
Finish & paint,
then carefully
make electrical
connections.

13˝

4-1/16˝

Section

Front View

Model No.
120 IN-HITW-EX
113 PL-HITW-EX
126 QD-HITW-EX

Lamp
20 watt Mini Can Incandescent
13 watt PL
26 watt Quad

NOTE: All fluorescent fixtures have electronic ballast with -20° starting temperature.

Installation should be coordinated between
electrician and exterior finish contractor.

32W Triple Tube,
consulted
manufacturer.

The exterior finish contractor must provide
waterproof seal where fixture joins the building.

See Installation Instructions.

②
Allow at least 16˝ of
additional conduit to
connect power.

④
The finished fixture
blends with any
architecture.

© 2003 Engineered Lighting Products. 1997/Rev. 2002

10768 LOWER AZUSA ROAD • EL MONTE • CA 91731 • 626-579-0943 • FAX: 626-579-6803 • E-mail: elp2@aol.com • WEB: www.elplighting.com

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 1 of 2
O5

PL-T Triple 4-Pin Fluorescent Lamp
Feature

High color rendering, high efficacy lamps
feature 4-pin base for use with preheat, rapid
start, electronic and dimming circuits.
Featuring ALTO® Lamp Technology

Watts

32

Bulb

PL-T

Base

GX24q-3

Product

046677-26832-6

Number
Ordering

PL-T 32W/830/4P/ALTO

Code
Generic

CFTR32W/GX24q/830

Designation
Package

12

Quantity
Description

3000K

CRI

82

Avg. Hrs.

10,000

Life
Design

2040

Lumens
M.O.L.

5 5/8

Lumens

2400

Images

Literature

Other Information

+ ALTO Product Logo

+ ALTO Family Brochure

• Energy Saving Product

+ Family Photo

+ MSDS S08-98001

+ Printable Page

+ Product Photo

+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

This Product Contains Amalgam

+

High Color Rendering Lamp

Features ALTO® Lamp Technology
+ Rated average life under specified test conditions with Programmed Start ballasts with lamps
+

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 2 of 2

+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
Information for this product last modified on September 25, 2001

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

O7

Metal
Halide
Lamp Ballast

Catalog Number 71A5282
For 70W
M98/M143
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA
3 X 4 CORE - 2 COIL UNIT
5.10 "
4.50"

0.7"

1.0"

A

B
MAX.

0.25" WIDE
2 SLOTS

3.95"
3.50"

4 HOLES
CLEARED
FOR #10
THRU-BOLTS

2.45"

2.80"

Capacitor: 7C080L33-R

2.90"

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±7%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
0.80 0.35
Open Circuit...............................................
1.90 0.80
Starting......................................................
0.55 0.25
UL TEMPERATURE RATINGS
Insulation Class
H(180°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
255
INPUT VOLTAGE AT LAMP DROPOUT...........................
90 208
INPUT WATTS
88
RECOMMENDED FUSE (Amps).....................................
4
2
CORE and COIL
Dimension (A)
1.45
Dimension (B)
2.75
Weight (lbs.)
5
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
8.0
Volts (min.)
280
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
2000
2 seconds
2500
Open Circuit Voltage Test (Volts)
230-280
Short-Circuit Current Test (Amps)
Secondary Current
0.95-1.25
Input Current..............................................

0.55 0.25
0.80 0.45

-

-

-

Wiring Diagram:
LAMP

CAP
LINE V
LINE V

X3

X1

IGNITOR
CAP

LAMP

LINE V

X2

COM
LINE V

Capacitance:
Dia/Oval Dim:
Height:
Temp Rating:

8
1.25
2.9
105°C

COM

COM

Fig. K

Ordering Information

Ignitor: LI533-H4

Order Suffix
500D.
510D.
600.
610.

Description
Ballast With Ignitor and Dry Film Capacitor
Ballast w/Welded Bracket, Ignitor, & Dry Film Capacitor
Ballast and Ignitor, No Capacitor
Ballast with Welded Bracket and Ignitor, No Capacitor

Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 105°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

11/08/00

05

ENGINEERED
LIGHTING PRODUCTS

HITW-EX SERIES
RECESSED Hole In The Wall Light Niche
For Exterior Stucco Construction

Wall Washer

Indirect

Floor
Washer

Ideal placement is
18˝ to 30˝ from the
bottom edge of
fixture to the ground.
WL-2

O5
ENGINEERED
LIGHTING PRODUCTS

HITW-EX SERIES
RECESSED Hole In The Wall Light Niche
For Exterior Stucco Construction

SYSTEM

7/8˝

Recessed, fiberglass reinforced, composite fixture
for use in exterior stucco construction. The cast
fixture appears to be part of the architecture and
looks like a custom formed “light niche” that blends
with any exterior motif. Non I.C. Rated.
UL/CUL Wet Location listed.

16˝

17-1/2˝
14-1/4˝

16˝

17-1/2˝
6˝

SPECIFICATIONS
Recessed fixture for use with a 20 watt Incandescent,
13 watt PL, or 26 watt Quad lamp. The cast fixture
houses a ballast box with heat sink that includes
wiring, socket, ballast and reflector. Incandescent
fixture also has thermal protector. Fluorescent fixtures
provide knock-outs for through wiring. Casting is
secured to the 20 gauge electro-plated galvanized
steel fixture back box and a 18 gauge electro-plated
galvanized steel frame with lexan lens and silicone
gaskets seal the lamp compartment.
Frame, ballast box, and fixture back box are TGIC
polyester powder coated. Composite casting is water
and high impact resistant. Use “Weld-crete” to finish
surface to match exterior stucco.

OPTIONS
Ballast

Low Temp 120 HPF Electronic (Standard)
Low Temp 277 HPF Electronic

①
Fixture mounts
directly to studs
that are 16˝ on
center.

③
Finish & paint,
then carefully
make electrical
connections.

13˝

4-1/16˝

Section

Front View

Model No.
120 IN-HITW-EX
113 PL-HITW-EX
126 QD-HITW-EX

Lamp
20 watt Mini Can Incandescent
13 watt PL
26 watt Quad

NOTE: All fluorescent fixtures have electronic ballast with -20° starting temperature.

Installation should be coordinated between
electrician and exterior finish contractor.

32W Triple Tube,
consulted
manufacturer.

The exterior finish contractor must provide
waterproof seal where fixture joins the building.

See Installation Instructions.

②
Allow at least 16˝ of
additional conduit to
connect power.

④
The finished fixture
blends with any
architecture.

© 2003 Engineered Lighting Products. 1997/Rev. 2002

10768 LOWER AZUSA ROAD • EL MONTE • CA 91731 • 626-579-0943 • FAX: 626-579-6803 • E-mail: elp2@aol.com • WEB: www.elplighting.com

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 1 of 2
O5

PL-T Triple 4-Pin Fluorescent Lamp
Feature

High color rendering, high efficacy lamps
feature 4-pin base for use with preheat, rapid
start, electronic and dimming circuits.
Featuring ALTO® Lamp Technology

Watts

32

Bulb

PL-T

Base

GX24q-3

Product

046677-26832-6

Number
Ordering

PL-T 32W/830/4P/ALTO

Code
Generic

CFTR32W/GX24q/830

Designation
Package

12

Quantity
Description

3000K

CRI

82

Avg. Hrs.

10,000

Life
Design

2040

Lumens
M.O.L.

5 5/8

Lumens

2400

Images

Literature

Other Information

+ ALTO Product Logo

+ ALTO Family Brochure

• Energy Saving Product

+ Family Photo

+ MSDS S08-98001

+ Printable Page

+ Product Photo

+ View Compatible Ballasts
+ Send this Link
+ Bookmark this Page

Footnotes
+

This Product Contains Amalgam

+

High Color Rendering Lamp

Features ALTO® Lamp Technology
+ Rated average life under specified test conditions with Programmed Start ballasts with lamps
+

turned off and restarted no more frequently than once every 3 operating hours. Lamp life is
appreciably longer if lamps are started less frequently.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

PL-T Triple 4-Pin Fluorescent Lamp 32 Watts Bulb PL-T Base GX24q-3 Product Numbe... Page 2 of 2

+

Approximate Initial Lumens. The lamp lumen output is based upon lamp performance after 100

hours of operating life, when the output is measured during operation on a reference ballast under
standard laboratory conditions.
+

Design Lumens are the approximate lamp lumen output at 40% of the lamp's Rated Average Life.

This output is based upon measurements obtained during lamp operation on a reference ballast
under standard laboratory conditions.
Information for this product last modified on September 25, 2001

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/cfl/displaycfl.php?id=131

4/3/2005

B5

ICF-2S26-H1-LD@120
Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

Electrical Specifications

Lamp Type

Num.
of
Lamp
s
CFM26W/GX24Q
1
CFM26W/GX24q
2
* CFM32W/GX24q
1
CFM42W/GX24q
1
CFQ26W/G24q
1
CFQ26W/G24q
2
CFS21W/GR10q
2
FT24W/2G11
2

Rated
Lamp
Watts

Min. Start
Temp
(°F/C)

Input
Current
(Amps)

26
26
32
42
26
26
21
24

0/-18
0/-18
0/-18
0/-18
0/-18
0/-18
0/-18
0/-18

0.24
0.45
0.31
0.38
0.23
0.43
0.42
0.41

Wiring Diagram

BLUE

BLACK
WHITE

Ballast
Factor

MAX
THD
%

Power
Factor

MAX Lamp
Current
Crest Factor

B.E.F.

1.10
1.00
0.98
0.98
1.00
1.00
1.12
0.93

10
10
10
10
10
10
10
10

0.98
0.99
0.98
0.98
0.98
0.99
0.99
0.99

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

3.79
1.85
2.72
2.13
3.70
1.96
2.20
1.94

Enclosure

WIRING: (2) LAMPS

LINE

Input
Power
(ANSI
Watts)
29
54
36
46
27
51
51
48

SMARTMATE
Electronic
Programmed Start
Series
120-277
50/60 HZ
Active

(1) LAMP

BLUE

BALLAST Y E L L O W

GREEN

RED

RED

Green Terminal must be Grounded
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)

Enclosure Dimensions

Standard Lead Length (inches)
Black
White
Blue
Red
Yellow
Gray
Violet

in.
0.0
0.0
0.0
0.0
0

cm.

in.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White

cm.

OverAll (L)
4.98 "
4 49/50
12.6 cm

Width (W)
2.4 "
2 2/5
6.1 cm

Height (H) Mounting (M)
1.0 "
4.6 "
1
4 3/5
2.5 cm
11.7 cm

Revised 09/02/2004
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

ICF-2S26-H1-LD@120

Electrical Specifications
Notes:

Brand Name
Ballast Type
Starting Method
Lamp Connection
Input Voltage
Input Frequency
Status

SMARTMATE
Electronic
Programmed Start
Series
120-277
50/60 HZ
Active

Section I - Physical Characteristics
1.1 Ballast shall be physically interchangeable with standard electromagnetic or standard electronic ballasts, where applicable.
1.2 Ballast shall be available in a plastic/metal can or all metal can construction to meet all plenum requirements.
1.3 Ballast shall be provided with poke-in wire trap connectors color coded per ANSI C82.11.
Section II - Performance Requirements
2.1 Ballast shall be Programmed Start except for ballasts with -QS suffix, which shall be Rapid Start.
2.2 Ballast shall contain auto restart circuitry in order to restart lamps without resetting power.
2.3 Ballast shall operate from 50/60 Hz input source of 120V through 277V with sustained variations of +/- 10% (voltage and frequency) with
no damage to the IntelliVolt ballast. RCF models shall operate from 60 Hz input source of 120V with sustained variations of +/- 10% (voltage
and frequency) with no damage to the ballast.
2.4 Ballast shall be high frequency electronic type and operate lamps at a frequency above 42 kHz to avoid interference with infrared devices
and eliminate visible flicker.
2.5 Ballast shall have a Power Factor greater than 0.98 for primary lamp.
2.6 Ballast shall have a minimum ballast factor of 1.00 for primary lamp application.
2.7 Ballast shall provide for a Lamp Current Crest Factor of 1.7 or less in accordance with lamp manufacturer recommendations.
2.8 Ballast input current shall have Total Harmonic Distortion (THD) of less than 10% when operated at nominal line voltage with primary lamp.
2.9 Ballast shall have a Class A sound rating.
2.10 Ballast shall have a minimum starting temperature of -18C (0F) for primary lamp. Ballasts for PL-H lamps shall have a minimum starting
temperature of -30C (-20F) for primary lamp.
2.11 Ballast shall provide Lamp EOL Protection Circuit which meets NEMA recommendations.
2.12 Ballast shall tolerate sustained open circuit and short circuit output conditions without damage.
Section III - Regulatory Requirements
3.1 Ballast shall not contain any Polychlorinated Biphenyl (PCB).
3.2 Ballast shall be Underwriters Laboratories (UL) listed, Class P and Type 1 Outdoor; and Canadian Standards Association (CSA) certified
where applicable.
3.3 Ballast shall be Underwriters Laboratories (UL) rated for use in air-handling spaces.
3.4 Ballast shall comply with ANSI C62.41 Category A for Transient protection.
3.5 Ballast shall comply with ANSI C82.11 where applicable.
3.6 Ballast shall comply with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 18,
Non-Consumer (Class A) for EMI/RFI (conducted and radiated) except for RCF models which shall be Consumer (Class B).
Section IV - Other
4.1 Ballast shall be manufactured in a factory certified to ISO 9002 Quality System Standards.
4.2 Ballast shall carry a five-year warranty from date of manufacture against defects in material or workmanship, including replacement, for
operation at a maximum case temperature of 75C and three-years for a maximum case temperature of 85C (90C 3year warranty for ICF1H120XX-XX, ICF2S70-XX-XX and ICF2S4290C-XX-XX modesls).
4.3 Manufacturer shall have a fifteen-year history of producing electronic ballasts for the North American market.
4.4 Ballast shall be Advance Transformer part # _____________ or approved equal.

Revised 09/02/2004
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance can vary
depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER - 10275 WEST HIGGINS ROAD
ROSEMONT, ILLINOIS 60018
TELEPHONE: (847) 390-5000 FAX: (847) 390-5109

O6

Clikstrip

UV-protected lens
CLM Series

CLM Series delivers low voltage linear lighting for outdoor
applications such as building facades, signage, pedestrian

Extruded lens clasps

walkways and landscape accenting. The small scale
shallow profile aluminum extrusion houses Clikstrip™ and
offers many options for outdoor as well as indoor lighting.

Features

• Gasketed aluminum housing finished in
satin anodized or painted. Blends well in all
architectural environments.
• Gasketed stamped aluminum end plates maintain a
water resistant enclosure.
• Extruded aluminum lens clasps, patent pending.
Permits servicing of the fixture by removing
the lens without tools. Consult factory for tamperproof option.
• UV-protected clear polycarbonate lens.
• Choice of mounting provides installation flexibility.
• Choice of shielding options.
Gasketed aluminum housing

• Delivered from factory with
Clikstrip™ installed – order separately.
• Optional factory-installed parabolic lamp reflectors.
• Requires remote power supply.
• UL/c Listed wet location and IP64 rated for use with
10 watt max lamps in base up or base down position.

Gasketed end plates

O6

CLM Series
Clikstrip™ miniature wet location

CLM Series is delivered with factory installed
Clikstrip™ which must be ordered separately

Ardee’s Clikstrip™ product specification formula allows you to specify each component that will best achieve the lighting results you need. To specify a complete
catalog number choose one item from the selection available in each module.
CLX
Series

0
Mounting

CLX - TB for wiring
in CLM Series housing

0 - mounted
to CLM Series
housing

X
Color

X
Clip Type

XX
X
Unit
of
Nominal Length Measurement
W- white C - standard standard sizes
F - feet
profile
in 1'
B - black chrome
increments
M - metric
from 01' to 16'
G - standard or half meter
profile gold increments
from 0.5 to
N - high
4.5 meters
profile
chrome
08'

X
Center-to-Center
Lamp Spacing
S - standard
17/8" o.c.
A - alternate
33/4" o.c.
C - custom (O.C.
dimension to be
called out in
product
description)

-X
C
Festoon
Lamp Style
Lamp Type*
I - incandescent C - clear

X
Lamp
Voltage
2 - 12 volt

X
Lamp
Wattage
3 - 3 watt

X - xenon

F - frosted

4 - 24 volt

5 - 5 watt

A - argon

R - red

6 - 6 watt

L - looped

B - blue

8 - 8.5 watt

W- LED element

G - green

1 - 10 watt

Y - yellow

A - LED
element AC

R - high
profile gold

W- solar blue
D - LED
element DC

or
LED element

Clikstrip™ LED Element

80

90

ZONAL
LUMENS
10.4

70

28.4
38.2
36.3

60

LEDs are the newest choice of designers for
energy efficient, low maintenance lighting
applications. Our LED Elements combine
energy efficiency and long life with low heat
generation and high light intensity in a “lamp”
specially designed to install into Clikstrip.™
White LED elements are standard but other
colors are available for custom applications.

50

29.2

Features

21.2

• LED lamp color: 5000°K. LED lamp life: 60,000 hours.
Consult factory for LED lamp color options.
• Total power consumption: 1 watt.
• Patent pending.

40

10.9

30

20

5.6
0

10

0
45
90

SPREAD

DISTANCE
6"
152 mm
12"
305 mm
18"
457 mm
24"
610 mm
30"
762 mm
36"
914 mm
42"
1066 mm
48"
1219 mm
60"
1524 mm
72"
1829 mm
84"
2134 mm

FC
432
108
48
27
17
12
9
7
4
3
2

3.1

Photometric report: WW2D
Ordering information

Test report number:
Description:

Part
Numbers

Rated lumens:

WW2A
WW4A
WW2D

Description

White LEDs 12 VAC
White LEDs 24 VAC
White LEDs 12 VDC Class II only

actual size

Clikstrip™ Materials Specification
extrusion UL/C recognized PES (polyethersulfone) with a thermal
deflection temperature of 397°F.
conductors Solid hard drawn copper.
terminal block UL/C recognized part made with nylon (insulator polyamide)
casing with nickel-plated brass contacts.
lampholder clips Tempered spring steel finished in bright nickel or gold.

11729.0
18 1-watt white LED elements installed on 3' Clikstrip
12 volt DC power supply
10.2 per element

O7

Job Name:

CALLISTO-12

Fixture Type:
Job Number:
Distributor:
Distributor P.O. :

1. H O U S I N G

CL12

Housing: two-piece die-cast aluminum with
internal component mounting bosses.

10.39"
3.45"

14.30"
13.38"
12"

Door frame: one-piece die-cast aluminum
secured with three phillips head screws.

9.81"

Lens assembly: various clear or prismatic glass
lens (beam dependant) gasketed
to door to ensure a tight seal.

9.62"
0.18"
EPA (fixture only): 0.62

2"

FIXTURE WEIGHT: 28 LBS.

The luminaire shall be cULus listed for wet
locations and manufactured from UL-recognized
components.

(shown with optional
eggcrate shield)

2. L A M P W A T T A G E
METAL HALIDE (H.I.D.) ED17

HIGH PRESSURE SODIUM (H.I.D.)

ED17

70 WATT METAL HALIDE

(70MH)

100 WATT HIGH PRESSURE SODIUM

(100HPS)

100 WATT METAL HALIDE

(100MH)

150 WATT HIGH PRESSURE SODIUM

(150HPS)

150 WATT METAL HALIDE

(150MH)

175 WATT METAL HALIDE

(175MH)

Quartz WATTAGE

PAR56

(500QTZ)

500 WATT QUARTZ HALOGEN

(Electronic ballast available only in 70MH or 100MH)

3. B E A M P A T T E R N
METAL HALIDE & HIGH PRESSURE SODIUM

INCANDESCENT
NARROW
SPOT

SPOT

(SP)

RECTANGULAR
NARROW (RN)

RECTANGULAR
MEDIUM (RM)

(NSP)

RECTANGULAR
WIDE (RW)
MEDIUM
FLOOD

RECTANGULAR
NARROW
VERTICAL (RNV)

Item Number:

ORDER NUMBER:

1

RECTANGULAR
MEDIUM
VERTICAL (RMV)

2

3

RECTANGULAR
WIDE
VERTICAL (RWV)

4

5

FLOOD

6

(WFL)

7

8

9

10

MOUNTING
OPTION

SHIELD
OPTION

FINISH

GENERAL
OPTION

YK

CL12
HOUSING

WIDE

(MFL)

LAMP
WATTAGE

BEAM
PATTERN

VOLTAGE

BALLAST
(FOR HID)

MODEL
STYLE

07

4. V O L T A G E

5. B A L L A S T (H.I.D. ONLY)

120

277

CORE & COIL

208

347

ELECTRONIC

240

480

6. M O D E L

(C)

YOKE

(YK)

(EB)

(Ballast is an integral part of the fixture housing.)
(Electronic ballast available only in 70WMH and 100WMH,
and in 120 or 277 volt. Rated for -20 F (-28.9 C).)

(Electronic ballast available only in 120 or 277 volts.)
(Quartz available in 120 volt only.)

(Core and coil ballast is high-power factor and rated for -20 F (-28.9 C).)

7. M O U N T I N G O P T I O N S
BASE PLATE

(BP) 0.56"
(4)

6.00" DIA.
BOLTCIRCLE

WALL BRACKET (WB)
1.81"
1.16"
3/ 8" LOCKING
BOLT
CANBE MOUNTED
TO2" PIPE (MAX) WITH
5/ 8" PIVOT U-BOLTS (U-BOLTS
BOLT
BY OTHERS)
3/ 4" MOUNTING
HARDWARE

6.00"

3/ 4" MOUNTING
HARDWARE
1.38"

BASE PAD (PD)
2.06"
I.D.

6.00"

2.38"
O.D.

SLIP FITTER
3.44"
3.13"

3.50"

CASTDUCTILE IRON
WALLBRACKETAND
HORIZONTALSECTOR

6.25"

0.56"
(4)

3.50"
4.50"

.25"
ALLCOMPONENTS STEEL.
WELDCONSTRUCTION

8. O P T I O N A L S H I E L D S

(SF)
TOFIT2" (2.38" O.D.)
PIPE TENONX 4.00" LONG
(MIN.)
REMOVABLE
PIPE PLUGFOR
3/ 4" MOUNTING INSTALLING
HARDWARE
WATER-TITE
CONNECTOR
(SUPPLIED)

5.63"
WATER-TITE
CONNECTOR
REMOVABLE
SPLICE INSPECTION
COVER
CASTTENZALLOY
FITTER

REMOVABLE
HOLE PLUGFOR
1/ 2" SET SIDE YOKE
SCREWS MOUNTING

EGGCRATE

(EC)

VER. LOUVER (VL)
6.17"

HOR. LOUVER

7.90"
6.17"

6.17"

2.46"

7.90"

3.0"

TOP SHIELD (TS)
6.17"
4.0"

CUSTOM SHIELD

(HL)

6.17""

3.0"

6.17"

(CS)

The eggcrate is the only shield finished to match luminaire.
Standard shield finish is black unless otherwise specified.

6.17"

9. F I N I S H

10. G E N E R A L O P T I O N S

(BK)
DARK BRONZE
(BZ)
WHITE
(WH)
NATURAL ALUMINUM
(AL)
NON-STANDARD
(NS)

INCLUDE LAMP

BLACK

(2" SCH. 40
STEELPIPE)
(for use with SF option)

8.00"
5.50"

.38"

CASTDUCTILE IRON
SURFACE BASE

6.00" DIA.
BOLTCIRCLE

1.50"

1.50"

0.56"
(4)

(LP)

SAFETY CABLE

(SC)

FUSE LUMINAIRE

(FL)

(SELECT 'LP' ONLY IF A LAMP IS TO BE INCLUDED)

70MH

ED17

100HPS

ED17

100MH

ED17

150HPS

ED17

150MH

ED17

175MH

ED17

500QTZ PAR56

REMARKS:
S t e r n e r L i g h t i n g S y s t e m s I n c o r p o r at e d
351 LEWIS AVENUE WEST, P.O. BOX 805 WINSTED, MN 55395-0805
T E L 3 2 0 . 4 8 5 . 2 1 4 1 FA X 3 2 0 . 4 8 5 . 2 8 8 1 T O L L - F R E E 8 0 0 . 3 2 8 . 7 4 8 0
2/2002

w w w. s t e r n e r l i g h t i n g . c o m

MasterColor CDM 70W/830 Med ED17P CL ALTO+FB

Page 1 of 3
O7

MasterColor CDM 70W/830 Med ED17P CL ALTO+FB
| Save PDF | Open PDF

General

PRODUCT DATA
Product Number

233668

Full product name

MasterColor CDM 70W/830 Med ED17P CL ALTO+FB

Ordering Code

MHC70/U/MP/3K ALTO

Pack type

1 Sleeve Open End

Pieces per pack

1

Packs per case

12

Pack UPC

046677233662

EAN2US

-

Case Bar Code

50046677233667

Successor Product number

-

Wattage[W ]

70W

Color Code

830 [CCT of 3000K]

Base

Med [Medium]

Bulb

ED17P [Diameter: 2.125 inch Protected]

Bulb Finish

CL [Clear]

Feature

ALTO+FB [ALTO® + FadeBlock™]

Base Information

Brass[Brass Base]

Bulb Material

Hard Glass

Execution

Protected

Operating Position

Universal[Universal]

Packing Type

1SL[1 Sleeve Open End]

Packing Configuration

12

Rated Avg. Life[hr ]

16000

Mercury Weight[mg ]

6.6

ANSI Code HID

M143/M98/O

Lamp Voltage[V ]

100

Color Rendering Index[Ra8 ]

85

Color Designation

Warm White

Color Temperature[K ]

3000

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 70W/830 Med ED17P CL ALTO+FB

Initial Lumens[Lm ]

Page 2 of 3

5900

Design Mean Lumens[Lm ]

4365

Light Center Length L [inch][in ]

3.438

Max Overall Length (MOL) - C[in ]

5.438

Diameter D[in ]

2.125

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

MasterColor CDM 70W/830 Med ED17P CL ALTO+FB

Page 3 of 3

Dimensions

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.prismaecat.lighting.philips.com/LightSite/Whirlwind.aspx?eca=LNPPLA&cpf=... 4/3/2005

O7

Metal
Halide
Lamp Ballast

Catalog Number 71A5282
For 70W
M98/M143
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA
3 X 4 CORE - 2 COIL UNIT
5.10 "
4.50"

0.7"

1.0"

A

B
MAX.

0.25" WIDE
2 SLOTS

3.95"
3.50"

4 HOLES
CLEARED
FOR #10
THRU-BOLTS

2.45"

2.80"

Capacitor: 7C080L33-R

2.90"

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±7%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
0.80 0.35
Open Circuit...............................................
1.90 0.80
Starting......................................................
0.55 0.25
UL TEMPERATURE RATINGS
Insulation Class
H(180°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
255
INPUT VOLTAGE AT LAMP DROPOUT...........................
90 208
INPUT WATTS
88
RECOMMENDED FUSE (Amps).....................................
4
2
CORE and COIL
Dimension (A)
1.45
Dimension (B)
2.75
Weight (lbs.)
5
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
8.0
Volts (min.)
280
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
2000
2 seconds
2500
Open Circuit Voltage Test (Volts)
230-280
Short-Circuit Current Test (Amps)
Secondary Current
0.95-1.25
Input Current..............................................

0.55 0.25
0.80 0.45

-

-

-

Wiring Diagram:
LAMP

CAP
LINE V
LINE V

X3

X1

IGNITOR
CAP

LAMP

LINE V

X2

COM
LINE V

Capacitance:
Dia/Oval Dim:
Height:
Temp Rating:

8
1.25
2.9
105°C

COM

COM

Fig. K

Ordering Information

Ignitor: LI533-H4

Order Suffix
500D.
510D.
600.
610.

Description
Ballast With Ignitor and Dry Film Capacitor
Ballast w/Welded Bracket, Ignitor, & Dry Film Capacitor
Ballast and Ignitor, No Capacitor
Ballast with Welded Bracket and Ignitor, No Capacitor

Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 105°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

11/08/00

P1

RTs – ROUND TAPERED STEEL POLES
ORDER E XA MPLE

(1)

(2)

(3)

(4)

(5)

(6)

(7)

RTS20

5.9 x 3.1

0.120

28

H

PRP

BK

ORDERING SEQUENCE
DIAMETER
(TAPERED)

(7)

(4)

RTS16

PRP
See Pole
Data Table
Below

DF

Polyurethane
Finish

Duplex Groundfault
Receptacle
(15 amp, mounted
24" above grade)

BK

Black

BZ

Dark Bronze

(arm mount fixtures only)

WH

White

Break-Away Banner
Arm Coupling

AL

Natural
Aluminum

NS

Non-Standard
Finish

PRP Pole Top Photocell
Receptacle
BN

BZ

(can use 0.75" or 1.25"
pipe arms)
(consult factory for specific
ordering info.)

(consult factory)

SEE FIXTURE
DETAIL
NOTES:
1) RTS12, 16, 20, 25, 30, 35, & 39 are available in 0.120" wall standard.
2) '10' applies to both arm & yoke mount fixtures.
3) See below table for dimensions & bolt info.

P O L E D ATA

14"

4.6" x 3.0"

11 ga.

10.9

5.2" x 3.0"

11 ga.

8.5

5.9" x 3.1"

11 ga.

9.2

6.5" x 3.0"

11 ga.

7.7

6.9" x 3.0"

11 ga.

6.2

7.6" x 3.0"

11 ga.

6.3

8.4" x 3.0"

11 ga.

6.0

NOTES: Responsibility lies with the specifier for correct pole selection based on local codes and standards for the job location.
(see Wind Map on page 13 for details)

9

P2

RTs – ROUND TAPERED STEEL POLES
ORDER E XA MPLE

(1)

(2)

(3)

(4)

(5)

(6)

(7)

RTS20

5.9 x 3.1

0.120

28

H

PRP

BK

ORDERING SEQUENCE
DIAMETER
(TAPERED)

(7)

(4)

RTS16

PRP
See Pole
Data Table
Below

DF

Polyurethane
Finish

Duplex Groundfault
Receptacle
(15 amp, mounted
24" above grade)

BK

Black

BZ

Dark Bronze

(arm mount fixtures only)

WH

White

Break-Away Banner
Arm Coupling

AL

Natural
Aluminum

NS

Non-Standard
Finish

PRP Pole Top Photocell
Receptacle
BN

BZ

(can use 0.75" or 1.25"
pipe arms)
(consult factory for specific
ordering info.)

(consult factory)

SEE FIXTURE
DETAIL
NOTES:
1) RTS12, 16, 20, 25, 30, 35, & 39 are available in 0.120" wall standard.
2) '10' applies to both arm & yoke mount fixtures.
3) See below table for dimensions & bolt info.

P O L E D ATA

14"

4.6" x 3.0"

11 ga.

10.9

5.2" x 3.0"

11 ga.

8.5

5.9" x 3.1"

11 ga.

9.2

6.5" x 3.0"

11 ga.

7.7

6.9" x 3.0"

11 ga.

6.2

7.6" x 3.0"

11 ga.

6.3

8.4" x 3.0"

11 ga.

6.0

NOTES: Responsibility lies with the specifier for correct pole selection based on local codes and standards for the job location.
(see Wind Map on page 13 for details)

9

T1
Catalog Number

Notes

Type

FEATURES & SPECIFICATIONS
INTENDED USE
Accent lighting applications where color, extended lamp life and
efficiency are important.

H.I.D.

LTD REFL

CONSTRUCTION
Polyester powder painted aluminum ballast housing.
Polyester powder painted aluminum socket housing and protective cowl.

Open Reflector
Color-Corrected or Standard Metal Halide
ED-17, E-17 or BD-17 Lamp

Metal yoke rotates 330° horizontally and up to 90° from vertical.
Two opposed knobs lock vertical position.
Injection-molded track mounting adaptor for easy attachment to 1 or 2
circuit Lithonia Track. Available with optional direct J-box mount.
Track mounted fixtures include a secondary locking clip.
Available in white or black finishes.
OPTICAL SYSTEM
Optical system designed specifically for clear, medium-base metal halide
lamp.
Spun, clear anodized aluminum reflector available in spot, narrow flood
or wide flood distributions.
ELECTRICAL SYSTEM
Medium-base porcelain socket with nickel-plated screw shell (open
reflector requires protected lamp).
Available for 50, 70, 100 or 150 watt metal halide lamps (see sheet 115-LTDREFL for 50 watt, 120-LTD-REFL for 70 watt, and 125-LTD-REFL for 100 watt).
High power factor, core and coil ballast.
CM option provides direct J-box mount and ballast that operates with
either 120 or 277 volt.
LISTING
Fixtures are UL 1574 or 1598 listed.
Listed and labeled to comply with Canadian Standards.

7-3/4 (19.7)

EMB: 15-1/16 (38.3)

EMB: 8-5/8 (14.3)

8-3/8 (21.3)

All dimensions are inches (centimeters).

ORDERING INFORMATION

Example: LTD REFL 150M NFL EMB WH

Choose the boldface catalog nomenclature that best suits your needs and
write it on the appropriate line.

LTD

REFL

150M

Series

Head Style

Wattage/lamp

Distribution

LTD

REFL Open reflector

150M 150W metal
halide

SP Spot
EMB Electromagnetic ballast
NFL Narrow flood
WFL Wide flood

1

2

Ballast

NOTES:
1 Supplied with socket designed for protected lamp unless CGL option is selected.
2 Available with clear anodized finish only.
3 Philips ceramic metal halide lamp shipped standard. Consult factory for other lamp options.
4 CM option with EMB ballast uses 120/277 dual tap ballast.

Downlighting and Track

Sheet#:LTD-REFL-150M

Finish
WH White
DBL Black

Options
CM4 For direct
mount to 4"
octagon
J-box (by
others)
CGL Clear
tempered
glass lens
WLP 3 With lamp
(shipped
separately)

HID-160

LTD REFL Open Reflector/Color Corrected or Standard Metal Halide
Distribution curve

Distribution data

Output data

Coefficient of utilization

Illuminance Data at 30" Above Floor for
a Single Luminaire

LTD REFL 150M SP, (1) MHC150/U/MP/4K, 12400 lumens per lamp, 0.13 s/mh, test no. LTL8975
From 0°

o

90
42000
84000
126000
168000
210000

0o

cp.

Lumens

0° 206295
5° 66831 4860
15° 3082 1094
25° 1279 576
45o 35° 1138 734
45° 1885 1311
55° 397 533
65° 142 136
75°
76
117
85°
13
52
90°
0

Zone

Lumens %lamp

0°-30° 6529.9
0°-40° 7263.6
0°-60° 9107.5
0°-90° 9412.5
90°-180° 0.0
0°-180° 9412.5

52.7
58.6
73.4
75.9
0.0
75.9*

*Efficiency

ρf
20%
ρc
80%
70%
50%
ρw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

84
79
75
71
68
65
63
61
59
57

83
76
71
67
64
61
59
57
55
54

83
78
74
70
67
65
62
60
59
57

81
75
71
67
64
61
59
57
55
54

80
75
72
69
66
63
61
60
58
57

78
73
69
66
63
60
58
56
55
54

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

6819.7
3667.5
2285.8
1559.9
1131.9

50%
10%
beam angle 7.5° beam angle 16.6°
fc at
fc at
Beam beam
Beam
beam
diameter edge
diameter edge

0.7 3409.8
1.0 1833.7
1.2 1142.9
1.5 779.9
1.8 566.0

1.6
2.2
2.8
3.4
3.9

682.0
366.7
228.6
156.0
113.2

LTD REFL 150M NFL, (1) MHC150/U/MP/4K, 12400 lumens per lamp, 0.51 s/mh, test no. LTL8976
From 0°

90o
6400
12800

45o

19200
25600
32000

0o

cp.

Lumens

0° 28913
5° 31549 2769
15° 14470 3786
25° 1567 867
35° 996 631
45° 983 757
55° 311 376
65°
80
82
75°
59
58
85°
29
37
90°
0

Zone

Lumens %lamp

0°-30° 7422.7
0°-40° 8053.8
0°-60° 9186.3
0°-90° 9363.3
90°-180° 0.0
0°-180° 9363.3

59.9
64.9
74.1
75.5
0.0
75.5*

*Efficiency

ρf
20%
ρc
80%
70%
50%
ρw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

84
79
75
71
68
65
62
60
58
56

82
76
71
67
64
61
58
56
54
52

83
78
74
70
67
64
62
59
57
55

81
75
71
67
63
61
58
56
54
52

79
75
72
69
66
63
61
59
57
55

78
73
69
66
63
60
57
55
53
52

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

955.8
514.0
320.4
218.6
158.6

50%
10%
beam angle 28.7° beam angle 41.9°
fc at
fc at
Beam beam
Beam
beam
diameter edge
diameter edge

2.8
3.8
4.9
5.9
6.9

477.9
257.0
160.2
109.3
79.3

4.2
5.7
7.3
8.8
10.3

95.6
51.4
32.0
21.9
15.9

LTD REFL 150M WFL, (1) MHC150/U/MP/4K, 12400 lumens per lamp, 0.95 s/mh, test no. LTL8978
o

90
1200
2400

45o

3600
4800
6000

0o

From 0°

cp.

0°
5°
15°
25°
35°
45°
55°
65°
75°
85°
90°

5852
5845
5512
4058
2742
2016
814
345
142
43
0

Lumens

556
1528
1860
1729
1563
847
346
155
45

Zone

Lumens %lamp

0°-30° 3944.1
0°-40° 5673.6
0°-60° 8083.7
0°-90° 8630.4
90°-180° 0.0
0°-180° 8630.4

31.8
45.8
65.2
69.6
0.0
69.6*

*Efficiency

ρf
20%
ρc
80%
70%
50%
ρw 50% 30% 50% 30% 50% 30%

1
2
3
4
5
6
7
8
9
10

75
68
62
56
51
47
43
40
37
35

73
64
57
51
46
42
38
35
32
30

74
67
61
55
51
46
43
40
37
35

72
63
56
51
446
42
38
35
32
30

71
64
59
54
49
45
39
39
36
34

69
62
55
50
45
41
34
34
32
30

Initial fc
Mount at beam
height center

8'
10'
12'
14'
16'

193.5
104.0
64.8
44.2
32.1

50%
beam angle 51°
fc at
Beam beam
diameter edge

5.2
7.2
9.1
11.0
12.9

96.7
52.0
32.4
22.1
16.1

10%
beam angle 94.9°
fc at
Beam
beam
diameter edge

12.0
16.3
20.7
25.0
29.4

Philips MHC150/U/MP/3K has a rated lamp life of 9,000 hours.
NOTES:
1 For electrical characteristics, refer to electrical data tab.
2 Tested to current IES and NEMA standards under stabilized laboratory
conditions. Various operating factors can cause differences between
laboratory data and actual field measurements. Dimensions and specifications are based on the most current available data and are subject to
change without notice.

Lithonia Lighting

Sheet#:LTD-REFL-150M

©2001 Acuity Lighting Group, Inc. 06/03 LTD-REFL-150M.p65

Acuity Lighting Group, Inc.
Recessed Downlighting
One Lithonia Way, Conyers, GA 30012
Phone: 800-315-4935 Fax: 770-860-3106
In Canada: 1100 50th Ave., Lachine, Quebec H8T 2V3
www.lithonia.com

19.3
10.4
6.5
4.4
3.2

Protected MasterColor Ceramic Metal Halide Lamp 70 Watts Bulb PAR-30L Base Med. ... Page 1 of 2
T1

Protected MasterColor® Ceramic Metal Halide Lamp
Feature

PAR Style. Open or Enclosed Luminaires.
Lifetime Color Stability Within +/- 200K

Watts

70

Bulb

PAR-30L

Base

Med.

Product Number

046677-23221-5

Ordering Code

CDM70/PAR30L/M/FL

Package Quantity 6
Description

G, PAR WISO Flood 40 degrees
FadeBlock 10,000 MBCP

ANSI

M143/M98/O

Code/Ballast Ref.
CRI

82

Rated Avg. Life

9000

(Hrs.)
M.O.L.

4 3/4

Approximate

4850

Initial Lumens
Approximate

3880

Mean Lumens
CCT

3000

Images

Literature

Other Information

+ Family Photo

+ Family Brochure

+ Printable Page

+ Product Logo

+ MSDS S15-95004

+ View Compatible Ballasts

+ Product Photo

+ MSDS S15-95005
+ Photometric Data

+ Send this Link
+ Bookmark this Page
† Heat resisting glass bulb

+ Technical Data Sheet

Footnotes
+

ANSI CODE RATING, E - Enclosed, O - Open, S - Open or Enclosed

+

Rated average life is the life obtained, on the average, from large representative groups of lamps

in laboratory tests under controlled conditions at 10 or more operating hours per start. It is based
on survival of at least 50% of the lamps and allows for individual lamps or groups of lamps to vary
considerably from the average. For lamps with a rated average life of 24,000 hours, life is based on
survival of 67% of the lamps.
+

Approximate lumen values listed are for vertical operation of the lamp.

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=28

4/3/2005

Protected MasterColor Ceramic Metal Halide Lamp 70 Watts Bulb PAR-30L Base Med. ... Page 2 of 2

+

Click here for Recommended Warnings, Cautions and Operating Instructions.

+

Approximate lumen output at 40% of lamp rated average life.

+

Requires a ballast specified or approved for Philips Metal Halide lamp or one designed to the

indicated ANSI Standard. A pulse ignitor is required. Sockets and wiring must withstand starting
pulse.
+

Supply volts must be +/- 5% of rated ballast line volts for reactor type and +/- 10% for CWA or

electronic ballasts.
+

UV filtered design (Fade-Block™).

MasterColor® Metal Halide Lamps are not recommended for use on dimmers and are not
warranted if used on dimmer systems.

+
+

Excellent color rendition - up to 92 CRI

+

Heat resisting glass bulb

+

Click here for specific product and ordering information on this lamp.
Information for this product last modified on June 22 2004.

©2004-2005 Koninklijke Philips Electronics N.V. All rights reserved. Privacy policy
Philips. Access to and use of this Web Site is subject to these Terms of use.

http://www.nam.lighting.philips.com/us/ecatalog/hid/displayhid.php?id=28

4/3/2005

T1

Metal
Halide
Lamp Ballast

Catalog Number 71A5282
For 70W
M98/M143
60 Hz HX-HPF
Status: Active

DIMENSIONS AND DATA
3 X 4 CORE - 2 COIL UNIT
5.10 "
4.50"

0.7"

1.0"

A

B
MAX.

0.25" WIDE
2 SLOTS

3.95"
3.50"

4 HOLES
CLEARED
FOR #10
THRU-BOLTS

2.45"

2.80"

Capacitor: 7C080L33-R

2.90"

INPUT VOLTS
120 277
HX-HPF
CIRCUIT TYPE
90%
POWER FACTOR (min)
REGULATION
±5%
Line Volts
±7%
Lamp Watts
LINE CURRENT (Amps)
Operating...................................................
0.80 0.35
Open Circuit...............................................
1.90 0.80
Starting......................................................
0.55 0.25
UL TEMPERATURE RATINGS
Insulation Class
H(180°C)
Coil Temperature Code
A
A
1029
MIN. AMBIENT STARTING TEMP.
-20°F or -30°C
NOM. OPEN CIRCUIT VOLTAGE
255
INPUT VOLTAGE AT LAMP DROPOUT...........................
90 208
INPUT WATTS
88
RECOMMENDED FUSE (Amps).....................................
4
2
CORE and COIL
Dimension (A)
1.45
Dimension (B)
2.75
Weight (lbs.)
5
Lead Lengths
12"
CAPACITOR REQUIREMENT
Microfarads
8.0
Volts (min.)
280
Fault Current Withstand (amps)
60 Hz TEST PROCEDURES (Refer to Advance Test
Procedure for HID Ballasts - Form 1270)
High Potential Test (Volts)
1 minute
2000
2 seconds
2500
Open Circuit Voltage Test (Volts)
230-280
Short-Circuit Current Test (Amps)
Secondary Current
0.95-1.25
Input Current..............................................

0.55 0.25
0.80 0.45

-

-

-

Wiring Diagram:
LAMP

CAP
LINE V
LINE V

X3

X1

IGNITOR
CAP

LAMP

LINE V

X2

COM
LINE V

Capacitance:
Dia/Oval Dim:
Height:
Temp Rating:

8
1.25
2.9
105°C

COM

COM

Fig. K

Ordering Information

Ignitor: LI533-H4

Order Suffix
500D.
510D.
600.
610.

Description
Ballast With Ignitor and Dry Film Capacitor
Ballast w/Welded Bracket, Ignitor, & Dry Film Capacitor
Ballast and Ignitor, No Capacitor
Ballast with Welded Bracket and Ignitor, No Capacitor

Ballast to Lamp Distance
(BTL) = 15 feet
Temp Rating: 105°C
Data is based upon tests performed by Advance Transformer in a controlled environment and representitive of relative performance.
Actual performance can vary depending on operating conditions. Specifications are subject to change without notice.

ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086

11/08/00

T3
JOB: __________________________

LOCATION: ____________________
CATALOG: DECORATIVE D9 SUPPLEMENT 2004/05

DATE: _________________________

PRODUCT SPECIFICATIONS
STYLE # D9-2016
SERIES NAME: DAU SPOT

12” / 30.8 cm

STRUCTURE: Metal
COLOR /FINISH: Brushed Aluminum
DIFFUSER: N/A

10” / 26 cm

MATT WHITE FINISH

LAMP TYPE: Halogen GZ10 MR20
MAX WATT: 2 x 75W
DIMENSIONS: D. 12” x Ht. 10”
APPROVALS: Approved by CSA for
North American Standards.
NOTES: _________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
ZANEEN LIGHTING 65 DENSLEY AVE. TORONTO, ONTARIO, CANADA M6M 2P5
PH: 800.388.3382 / 416.247.9221 FAX: 416.247.9319 www.zaneen.com zaneen@zaneen.com

Luminaire Comparison

Metal Halide
Max/Min ratio for
shadows:
2:1

Halogen
Max/Min ratio for
shadows:
6:1

Halogen
Max/Min ratio for
sparkle:
15:1

Metal Halide
Max/Min ratio for
sparkle:
2:1



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 99
Has XFA                         : No
XMP Toolkit                     : XMP toolkit 2.9.1-13, framework 1.6
About                           : uuid:f5e9ff44-7041-483a-873c-49d22347b7ff
Modify Date                     : 2005:04:06 15:57:41-04:00
Create Date                     : 2005:04:05 12:45:15-04:00
Metadata Date                   : 2005:04:06 15:57:41-04:00
Document ID                     : uuid:4676b4be-1d5f-4462-b396-ec0de85613c1
Format                          : application/pdf
Creator                         : Adobe Acrobat 6.0
Producer                        : Adobe Acrobat 6.0
EXIF Metadata provided by EXIF.tools

Navigation menu